AG2-151 Phase I Study Report

v1.00 released 2025-10-29 20:58

Trices Lake - James River Tap 115 kV

60.0 MW Capacity / 100.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Cumberland Solar, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed a Solar generating facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — Cumberland County, Virginia. The installed facilities will have a total capability of 100.0 MW with 60.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-151
Project Name:
Trices Lake - James River Tap 115 kV
Project Developer Name:
Cumberland Solar, LLC
State:
Virginia
County:
Cumberland
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
100.0
MWE:
100.0
MWC:
60.0
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AG2-151 will interconnect on the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) transmission system by tapping the Trices Lake DP - James River 115 kV Line.

.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AG2-151 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-151Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$1,200,000$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$12,000,000$12,000,000
Network Upgrades$4,200,000$4,200,000
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$19,302,389$19,302,389
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$36,702,389$35,502,389

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AG2-151

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AG2-151 Project due at DP1
ABA - B
AG2-151$3,550,239$400,000$3,150,239

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Interconnection Facilities
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Install the Point of Change in Ownership (PCO) disconnect switch, the overhead line conductor from the PCO to the bus position that serves as the Point of Interconnection (POI), as well as any metering and associated protection equipment.$1,200,000 $1,200,000
Stand-Alone Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Construct a new three breaker ring bus switching station on the Trices Lake DP - Trices Lake Tap 115 kV Line 4.$12,000,000 $12,000,000
Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Remove, modify, and/or install backbones, structures, conductors, and supporting equipment to re-arrange transmission line and tie-in substation. Install static poles and shield wiring for substation protection and install fiber cable for communication if needed.$4,200,000 $4,200,000

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 36 to 40 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2028 load flow model and the results were verified by Dominion.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-151 was evaluated as a 100.0 MW (60.0 MW Capacity) injection in the Dominion area.

AG2-151 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 100.0 MW (100.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
3BREMO-3FORK UNION 115.0 kV Ckt 2 line
DVP_P1-2: LN 2193_SRT-A
SingleAC127.14 %134.42B170.910.89
GD2DVP
3FORK UNION-6FORK UNION 115.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 2193_SRT-A
SingleAC119.58 %291.21B348.2217.8
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC203.13 %678.68B1378.67.01
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC185.6 %830.0C1540.59.18
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC185.6 %830.0C1540.499.18
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC173.49 %830.0C1439.979.59
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC173.49 %830.0C1439.979.59
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-3
SingleAC158.61 %678.68B1076.4814.37
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: 242T2027_SRT-A
BreakerAC148.82 %830.0C1235.2218.92
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Base Case
SingleAC113.92 %678.68A773.166.36
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC113.5 %830.0C942.098.46
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P7-1: LN 2066-282_SRT-S
TowerAC111.23 %830.0C923.198.91
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P7-1: LN 219-282_SRT-A
TowerAC110.89 %830.0C920.438.91
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P2-2: DOOMS B2_SRT-A
BusAC106.99 %830.0C887.989.92
GD2DVP
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 2028_SRT-A
SingleAC118.12 %800.88B946.0323.31
GD2DVP
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC117.42 %800.88B940.3715.13
GD2DVP
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
DVP_P4-2: 2028T2054_SRT-A
BreakerAC109.11 %980.0C1069.2530.73
GD2DVP
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
DVP_P4-2: 233T2028_SRT-A
BreakerAC107.38 %980.0C1052.3230.69
GD2DVP
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC107.32 %980.0C1051.7119.91
GD2DVP
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC107.31 %980.0C1051.6319.91
GD2DVP
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
DVP_P4-2: 2028T2193_SRT-A
BreakerAC107.22 %980.0C1050.7229.42
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC202.03 %678.68B1371.177.01
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC184.71 %830.0C1533.119.18
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC184.71 %830.0C1533.19.18
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC172.6 %830.0C1432.619.59
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC172.6 %830.0C1432.619.59
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-3
SingleAC157.52 %678.68B1069.0314.37
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: 202712_SRT-S
BreakerAC147.93 %830.0C1227.7918.92
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Base Case
SingleAC112.86 %678.68A765.976.36
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC112.65 %830.0C934.978.46
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P7-1: LN 2066-282_SRT-S
TowerAC110.36 %830.0C916.08.91
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P7-1: LN 219-282_SRT-A
TowerAC110.03 %830.0C913.268.91
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P2-2: DOOMS B2_SRT-A
BusAC106.13 %830.0C880.869.92
GD2DVP
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 2028_SRT-A
SingleAC121.53 %800.88B973.323.31
GD2DVP
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC119.72 %800.88B958.8515.13
GD2DVP
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 2028T2054_SRT-A
BreakerAC113.1 %980.0C1108.430.73
GD2DVP
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 233T2028_SRT-A
BreakerAC111.37 %980.0C1091.4630.69
GD2DVP
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 2028T2193_SRT-A
BreakerAC111.25 %980.0C1090.2729.42
GD2DVP
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
DVP_P4-2: WT2193_SRT-A
BreakerAC111.23 %980.0C1090.0529.42
GD2DVP
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 202872_SRT-A
BreakerAC110.91 %980.0C1086.9329.42
GD2DVP
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line
DVP_P1-2: LN 553_SRT-S
SingleAC122.22 %984.18B1202.886.84
GD2DVP
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC110.1 %984.18B1083.627.05
GD2DVP
6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line
DVP_P1-2: LN 2199_SRT-A-1
SingleAC167.54 %819.68B1373.274.16
GD2DVP
6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line
DVP_P1-2: LN 2331_SRT-A
SingleAC162.72 %819.68B1333.764.16
GD2DVP
6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-1
TowerAC160.76 %1003.0C1612.446.31
GD2DVP
6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-2
TowerAC154.66 %1003.0C1551.266.31
GD2DVP
6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line
DVP_P4-2: 2199T2331_SRT-A
BreakerAC140.15 %1003.0C1405.755.47
GD2DVP
6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line
DVP_P4-2: 2278T2331_SRT-A
BreakerAC136.11 %1003.0C1365.225.47
GD2DVP
6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line
DVP_P2-2: GERMANNA_SRT-A
BusAC134.77 %1003.0C1351.735.47
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
PEPCO_P1_5070_SRT-A
SingleAC152.59 %1331.98B2032.493.82
GD2DVP
6EDMONSON-6SEDGE HILL 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC103.9 %997.0C1035.97.27
GD2DVP
6EDMONSON-6SEDGE HILL 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC102.06 %997.0C1017.587.28
GD2DVP
6EDMONSON-6SEDGE HILL 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC102.05 %997.0C1017.417.28
GD2DVP
6ELMONT-6HANOVER 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC105.87 %1123.3B1189.213.15
GD2DVP
6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 1 transformer
DVP_P4-5: 556X2_SRT-S
BreakerAC139.23 %1050.6C1462.747.26
GD2DVP
6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 2 transformer
DVP_P4-5: 556X1_SRT-S
BreakerAC138.76 %1053.0C1461.127.26
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC196.14 %678.68B1331.1421.64
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC182.57 %830.0C1515.3728.43
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC182.57 %830.0C1515.3428.43
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC175.31 %830.0C1455.0828.82
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC175.31 %830.0C1455.0828.82
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-3
SingleAC162.3 %678.68B1101.5128.5
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P4-2: 202712_SRT-S
BreakerAC153.09 %830.0C1270.6637.53
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P7-1: LN 39-91_SRT-A-2
TowerAC119.33 %830.0C990.4732.43
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P2-2: DOOMS B2_SRT-A
BusAC117.39 %830.0C974.3132.4
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC112.5 %830.0C933.7827.74
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Base Case
SingleAC108.58 %678.68A736.9221.01
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P7-1: LN 2066-282_SRT-S
TowerAC108.52 %830.0C900.7528.17
GD2DVP
6GERMANNA-6CIRRUS 230.0 kV Ckt 1 line
DVP_P1-2: LN 2304_SRT-A-2
SingleAC131.47 %984.18B1293.883.93
GD2DVP
6GERMANNA-6CIRRUS 230.0 kV Ckt 1 line
DVP_P1-2: LN 2202_SRT-A
SingleAC129.23 %984.18B1271.873.94
GD2DVP
6GERMANNA-6CIRRUS 230.0 kV Ckt 1 line
DVP_P4-2: 220232_SRT-A
BreakerAC107.97 %1204.0C1299.95.18
GD2DVP
6GERMANNA-6CIRRUS 230.0 kV Ckt 1 line
DVP_P4-2: 2304T2202_SRT-A
BreakerAC107.86 %1204.0C1298.625.18
GD2DVP
6GERMANNA-6CIRRUS 230.0 kV Ckt 1 line
DVP_P4-2: G2T2202_SRT-A
BreakerAC104.49 %1204.0C1258.15.2
GD2DVP
6GERMANNA-6CIRRUS 230.0 kV Ckt 1 line
DVP_P4-2: H3T255_SRT-A
BreakerAC101.59 %1204.0C1223.185.19
GD2DVP
6GERMANNA-6CIRRUS 230.0 kV Ckt 1 line
DVP_P4-2: 25532_SRT-A
BreakerAC101.59 %1204.0C1223.185.19
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC198.54 %661.76B1313.8821.64
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC185.18 %809.0C1498.128.43
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC185.18 %809.0C1498.0828.43
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC177.73 %809.0C1437.8228.82
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC177.73 %809.0C1437.8228.82
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-3
SingleAC163.84 %661.76B1084.2328.5
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: 242T2027_SRT-A
BreakerAC154.93 %809.0C1253.3837.53
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P7-1: LN 39-91_SRT-A-2
TowerAC120.29 %809.0C973.1732.43
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P2-2: DOOMS B2_SRT-A
BusAC118.3 %809.0C957.0132.4
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC113.29 %809.0C916.4827.74
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P7-1: LN 2066-282_SRT-S
TowerAC109.2 %809.0C883.4628.17
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Base Case
SingleAC108.74 %661.76A719.6221.01
GD2DVP
6HANOVER-6FOUR RIVERS 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC100.18 %1123.3B1125.323.15
GD2DVP
6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line
DVP_P1-2: LN 553_SRT-S
SingleAC114.98 %984.18B1131.576.84
GD2DVP
6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC103.16 %984.18B1015.267.05
GD2DVP
6KYSER-6LUCKYHILL 230.0 kV Ckt 1 line
DVP_P1-2: LN 2304_SRT-A-2
SingleAC110.02 %984.18B1082.793.93
GD2DVP
6KYSER-6LUCKYHILL 230.0 kV Ckt 1 line
DVP_P1-2: LN 2202_SRT-A
SingleAC107.83 %984.18B1061.233.94
GD2DVP
6LOISACT-6S ANNA 230.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-1
TowerAC151.67 %886.0C1343.836.43
GD2DVP
6LOISACT-6S ANNA 230.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-2
TowerAC144.74 %886.0C1282.436.43
GD2DVP
6LOISACT-6S ANNA 230.0 kV Ckt 1 line
DVP_P1-2: LN 2199_SRT-A-1
SingleAC139.51 %798.06B1113.344.25
GD2DVP
6LOISACT-6S ANNA 230.0 kV Ckt 1 line
DVP_P1-2: LN 2331_SRT-A
SingleAC134.58 %798.06B1074.064.25
GD2DVP
6LOISACT-6S ANNA 230.0 kV Ckt 1 line
DVP_P4-2: 2199T2331_SRT-A
BreakerAC128.74 %886.0C1140.665.59
GD2DVP
6LOISACT-6S ANNA 230.0 kV Ckt 1 line
DVP_P4-2: 2278T2331_SRT-A
BreakerAC124.2 %886.0C1100.45.59
GD2DVP
6LOISACT-6S ANNA 230.0 kV Ckt 1 line
DVP_P2-2: GERMANNA_SRT-A
BusAC122.62 %886.0C1086.445.59
GD2DVP
6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line
DVP_P1-2: LN 2199_SRT-A-1
SingleAC167.53 %819.68B1373.244.16
GD2DVP
6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line
DVP_P1-2: LN 2331_SRT-A
SingleAC162.71 %819.68B1333.734.16
GD2DVP
6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-1
TowerAC160.76 %1003.0C1612.426.31
GD2DVP
6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-2
TowerAC154.66 %1003.0C1551.246.31
GD2DVP
6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line
DVP_P4-2: 2199T2331_SRT-A
BreakerAC140.15 %1003.0C1405.735.47
GD2DVP
6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line
DVP_P4-2: 2278T2331_SRT-A
BreakerAC136.11 %1003.0C1365.25.47
GD2DVP
6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line
DVP_P2-2: GERMANNA_SRT-A
BusAC134.77 %1003.0C1351.715.47
GD2DVP
6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 2199_SRT-A-1
SingleAC145.7 %819.68B1194.244.15
GD2DVP
6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-1
TowerAC142.58 %1003.0C1430.16.3
GD2DVP
6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 2331_SRT-A
SingleAC140.96 %819.68B1155.444.15
GD2DVP
6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-2
TowerAC136.48 %1003.0C1368.926.3
GD2DVP
6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line
DVP_P4-2: 2199T2331_SRT-A
BreakerAC121.7 %1003.0C1220.625.46
GD2DVP
6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line
DVP_P4-2: 2278T2331_SRT-A
BreakerAC117.73 %1003.0C1180.845.46
GD2DVP
6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line
DVP_P2-2: GERMANNA_SRT-A
BusAC116.31 %1003.0C1166.615.46
GD2DVP
6LUCKYHILL-6REMNGTN 230.0 kV Ckt 1 line
DVP_P1-2: LN 2304_SRT-A-2
SingleAC106.93 %984.18B1052.423.93
GD2DVP
6LUCKYHILL-6REMNGTN 230.0 kV Ckt 1 line
DVP_P1-2: LN 2202_SRT-A
SingleAC104.73 %984.18B1030.783.94
GD2DVP
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
DVP_P1-2: LN 563_SRT-S
SingleAC137.15 %1057.5B1450.336.61
GD2DVP
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
DVP_P4-2: 562T563_SRT-S
BreakerAC125.36 %1265.1C1585.988.71
GD2DVP
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
DVP_P4-2: 56372_SRT-S
BreakerAC123.56 %1265.1C1563.158.7
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC195.13 %661.76B1291.3121.64
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC182.39 %809.0C1475.5728.43
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC182.39 %809.0C1475.5428.43
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC174.94 %809.0C1415.2728.82
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC174.94 %809.0C1415.2728.82
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-3
SingleAC160.44 %661.76B1061.728.5
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P4-2: 242T2027_SRT-A
BreakerAC152.15 %809.0C1230.8737.53
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P7-1: LN 39-91_SRT-A-2
TowerAC117.53 %809.0C950.832.43
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P2-2: DOOMS B2_SRT-A
BusAC115.53 %809.0C934.6332.4
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC110.52 %809.0C894.1127.74
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P7-1: LN 2066-282_SRT-S
TowerAC106.44 %809.0C861.0728.17
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Base Case
SingleAC105.36 %661.76A697.2321.01
GD2DVP
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
DVP_P1-2: LN 2028_SRT-A
SingleAC127.75 %800.88B1023.0923.28
GD2DVP
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC125.17 %800.88B1002.4615.1
GD2DVP
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
DVP_P4-2: 2028T2054_SRT-A
BreakerAC119.58 %980.0C1171.8730.69
GD2DVP
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
DVP_P4-2: 233T2028_SRT-A
BreakerAC117.83 %980.0C1154.7730.65
GD2DVP
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
DVP_P4-2: 2028T2193_SRT-A
BreakerAC117.74 %980.0C1153.8129.38
GD2DVP
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
DVP_P4-2: WT2193_SRT-A
BreakerAC117.71 %980.0C1153.5829.38
GD2DVP
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
DVP_P4-2: 202872_SRT-A
BreakerAC117.39 %980.0C1150.4529.38
GD2DVP
6PROFFIT-6HOLLYMD 230.0 kV Ckt 1 line
DVP_P1-2: LN 553_SRT-S
SingleAC118.67 %984.18B1167.966.84
GD2DVP
6PROFFIT-6HOLLYMD 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC106.71 %984.18B1050.187.05
GD2DVP
6S ANNA-6DESPER 230.0 kV Ckt 1 line
DVP_P1-2: LN 2199_SRT-A-1
SingleAC161.07 %819.68B1320.254.18
GD2DVP
6S ANNA-6DESPER 230.0 kV Ckt 1 line
DVP_P1-2: LN 2331_SRT-A
SingleAC156.26 %819.68B1280.874.18
GD2DVP
6S ANNA-6DESPER 230.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-1
TowerAC154.71 %1003.0C1551.766.34
GD2DVP
6S ANNA-6DESPER 230.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-2
TowerAC148.61 %1003.0C1490.536.34
GD2DVP
6S ANNA-6DESPER 230.0 kV Ckt 1 line
DVP_P4-2: 2199T2331_SRT-A
BreakerAC134.32 %1003.0C1347.195.5
GD2DVP
6S ANNA-6DESPER 230.0 kV Ckt 1 line
DVP_P4-2: 2278T2331_SRT-A
BreakerAC130.29 %1003.0C1306.85.5
GD2DVP
6S ANNA-6DESPER 230.0 kV Ckt 1 line
DVP_P2-2: GERMANNA_SRT-A
BusAC128.93 %1003.0C1293.135.5
GD2DVP
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC108.88 %1105.0C1203.127.29
GD2DVP
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC106.72 %1105.0C1179.247.31
GD2DVP
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC106.7 %1105.0C1179.057.31
GD2DVP
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
DVP_P4-5: 593X1_SRT-A
BreakerAC104.45 %1105.0C1154.157.19
GD2DVP
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
DVP_P4-5: 593X2_SRT-A
BreakerAC104.44 %1105.0C1154.097.2
GD2DVP
6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line
DVP_P1-2: LN 2199_SRT-A-1
SingleAC147.08 %819.68B1205.624.15
GD2DVP
6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-1
TowerAC143.73 %1003.0C1441.586.3
GD2DVP
6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line
DVP_P1-2: LN 2331_SRT-A
SingleAC142.35 %819.68B1166.84.15
GD2DVP
6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-2
TowerAC137.63 %1003.0C1380.46.3
GD2DVP
6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line
DVP_P4-2: 2199T2331_SRT-A
BreakerAC122.83 %1003.0C1231.965.46
GD2DVP
6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line
DVP_P4-2: 2278T2331_SRT-A
BreakerAC118.86 %1003.0C1192.155.46
GD2DVP
6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line
DVP_P2-2: GERMANNA_SRT-A
BusAC117.44 %1003.0C1177.955.46
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
PEPCO_P1_5070_SRT-A
SingleAC140.61 %1478.62B2079.093.82
GD2DVP
8BRAMBLETON-AH1-727 TP 500.0 kV Ckt 1 line
DVP_P1-2: LN 9344_SRT-A
SingleAC106.63 %3256.16B3472.078.95
GD2DVP
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
SingleAC132.78 %4070.2B5404.528.06
GD2DVP
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-S
SingleAC123.02 %4070.2B5007.087.84
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC173.01 %4070.2B7041.7810.63
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC153.9 %4070.2B6264.07.12
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Base Case
SingleAC118.98 %4070.2A4842.757.11
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P7-1: LN 2054-2135_SRT-A
TowerAC107.76 %5011.0C5399.8511.94
GD2DVP
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-S
SingleAC126.22 %4070.2B5137.227.9
GD2DVP
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
SingleAC124.64 %4070.2B5073.157.7
GD2DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC130.67 %3220.44B4208.16.36
GD2DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC130.56 %3220.44B4204.636.39
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC175.45 %3220.44B5650.149.11
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC136.69 %3220.44B4402.077.05
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Base Case
SingleAC113.34 %3193.18A3619.136.63
GD2DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
SingleAC150.27 %3220.44B4839.457.17
GD2DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-S
SingleAC147.45 %3220.44B4748.67.33
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC172.64 %3220.44B5559.888.42
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC171.66 %3220.44B5528.278.48
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Base Case
SingleAC118.49 %3193.18A3783.566.39
GD2DVP/PJM
8POSSUM-BURCHES 500.0 kV Ckt 1 line
AP_P1-2_PE-500-406T_SRT-A
SingleAC105.05 %2913.06B3060.216.0
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC179.85 %3220.44B5791.828.67
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC175.06 %3220.44B5637.78.48
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Base Case
SingleAC129.41 %3220.44A4167.616.52
GD2DVP
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC113.0 %1105.0C1248.617.26
GD2DVP
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC110.45 %1105.0C1220.467.28
GD2DVP
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC110.42 %1105.0C1220.197.28
GD2DVP
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-5: 593X1_SRT-A
BreakerAC108.84 %1105.0C1202.697.17
GD2DVP
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-5: 593X2_SRT-A
BreakerAC108.84 %1105.0C1202.637.17
GD2DVP
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC103.96 %903.34B939.115.52
GD2DVP
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC102.05 %903.34B921.895.52
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC239.46 %541.0B1295.467.25
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC234.05 %541.0B1266.237.26
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC234.0 %541.0B1265.967.26
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-5: 593X1_SRT-A
BreakerAC231.01 %541.0B1249.797.15
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-5: 593X2_SRT-A
BreakerAC231.0 %541.0B1249.747.15
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC192.41 %508.54B978.465.5
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC189.13 %508.54B961.815.5
GD2DVP
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
DVP_P1-2: LN 2028_SRT-A
SingleAC127.59 %800.88B1021.8223.29
GD2DVP
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC125.65 %800.88B1006.3115.12
GD2DVP
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
DVP_P4-2: 2028T2054_SRT-A
BreakerAC119.54 %980.0C1171.5330.7
GD2DVP
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
DVP_P4-2: 233T2028_SRT-A
BreakerAC117.8 %980.0C1154.4230.67
GD2DVP
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
DVP_P4-2: 2028T2193_SRT-A
BreakerAC117.69 %980.0C1153.3229.4
GD2DVP
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
DVP_P4-2: WT2193_SRT-A
BreakerAC117.66 %980.0C1153.0929.4
GD2DVP
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
DVP_P4-2: 202872_SRT-A
BreakerAC117.34 %980.0C1149.9529.4
GD2DVP
AG1-098 TP-6FINNEYWOOD 230.0 kV Ckt 1 line
DVP_P4-6: CHASE C T342_SRT-A
BreakerAC122.09 %699.0C853.3913.93
GD2DVP
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
DVP_P1-2: LN 2028_SRT-A
SingleAC122.8 %800.88B983.4723.31
GD2DVP
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC120.99 %800.88B969.0115.13
GD2DVP
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
DVP_P4-2: 2028T2054_SRT-A
BreakerAC114.14 %980.0C1118.5930.73
GD2DVP
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
DVP_P4-2: 233T2028_SRT-A
BreakerAC112.41 %980.0C1101.6330.69
GD2DVP
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
DVP_P4-2: 2028T2193_SRT-A
BreakerAC112.29 %980.0C1100.4429.42
GD2DVP
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
DVP_P4-2: WT2193_SRT-A
BreakerAC112.27 %980.0C1100.2229.42
GD2DVP
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
DVP_P4-2: 202872_SRT-A
BreakerAC111.95 %980.0C1097.129.42
GD2DVP
AH1-012 TP-6SOUTH HALL 230.0 kV Ckt 1 line
DVP_P1-2: LN 2199_SRT-A-1
SingleAC147.17 %819.68B1206.364.15
GD2DVP
AH1-012 TP-6SOUTH HALL 230.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-1
TowerAC143.81 %1003.0C1442.376.3
GD2DVP
AH1-012 TP-6SOUTH HALL 230.0 kV Ckt 1 line
DVP_P1-2: LN 2331_SRT-A
SingleAC142.44 %819.68B1167.534.15
GD2DVP
AH1-012 TP-6SOUTH HALL 230.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-2
TowerAC137.71 %1003.0C1381.196.3
GD2DVP
AH1-012 TP-6SOUTH HALL 230.0 kV Ckt 1 line
DVP_P4-2: 2199T2331_SRT-A
BreakerAC122.9 %1003.0C1232.75.46
GD2DVP
AH1-012 TP-6SOUTH HALL 230.0 kV Ckt 1 line
DVP_P4-2: 2278T2331_SRT-A
BreakerAC118.93 %1003.0C1192.895.46
GD2DVP
AH1-012 TP-6SOUTH HALL 230.0 kV Ckt 1 line
DVP_P2-2: GERMANNA_SRT-A
BusAC117.52 %1003.0C1178.695.46
GD2DVP
AH1-377 TP-AG1-098 TP 230.0 kV Ckt 1 line
DVP_P4-6: CHASE C T342_SRT-A
BreakerAC111.73 %699.0C780.9713.93

Details for 3BREMO-3FORK UNION 115.0 kV Ckt 2 line l/o DVP_P1-2: LN 2193_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3BREMO-3FORK UNION 115.0 kV Ckt 2 line
Contingency Name:
DVP_P1-2: LN 2193_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.14 %
Rating:134.42 MVA
Rating Type:B
MVA to Mitigate:170.9
MW Contribution:10.89
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
5.623
270494AE1-108_GEN
Solar/Wind Harmer
1.915
971845AH1-439 GEN
Solar/Wind Harmer
4.381
970285AG2-188 GEN
Solar/Wind Harmer
7.378
315657AE1-056 GEN
Solar/Wind Harmer
1.97
3151921BEARGRDN G2
50/50
1.153
970221AG2-151 GEN
Solar/Wind Harmer
10.888
3146776BUCKING
Solar/Wind Harmer
0.035
3146926FARMVIL
Solar/Wind Harmer
0.046
942461AE2-259 GEN
Solar/Wind Harmer
0
316313AB2-026
Solar/Wind Harmer
0.04
316258AE1-075 C
Solar/Wind Harmer
0.048
316405AF2-144 C
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
0.97
958131AF2-107 GEN
Solar/Wind Harmer
1.795
970909AG2-566 GEN
Solar/Wind Harmer
0.616
3147133PAMPLIN
Solar/Wind Harmer
0.179
971193AH1-056 GEN
Solar/Wind Harmer
3.478
3151931BEARGRDN S1
50/50
1.488
3151911BEARGRDN G1
50/50
1.153
971377AH1-170 GEN
Solar/Wind Harmer
2.178
3147623JAMES R
Solar/Wind Harmer
0.473
972003AH1-546 GEN
Solar/Wind Harmer
5.071
970937AG2-583 GEN
Solar/Wind Harmer
6.217
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.039
3146926FARMVIL
Solar/Wind Harmer
0.046
316336AC2-165 C
Solar/Wind Harmer
0.003
3143336POWHATN
Solar/Wind Harmer
1.141
957481AF2-042 GEN
Solar/Wind Harmer
6.597
971489AH1-241 GEN
Solar/Wind Harmer
10.888
3146776BUCKING
Solar/Wind Harmer
0.393
3146776BUCKING
Solar/Wind Harmer
0.032
970301AG2-198 GEN
Solar/Wind Harmer
2.465
3147133PAMPLIN
Solar/Wind Harmer
0.057
3147133PAMPLIN
Solar/Wind Harmer
0.046
970099AG2-077 GEN
Solar/Wind Harmer
2.639
315821AE2-092 GEN
Solar/Wind Helper
3.5
LAGNLTFEXP_LAGN->PJM
CLTF
0.382
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.075
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.596
MECLTFEXP_MEC->PJM
CLTF
0.084
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.754
TVALTFEXP_TVA->PJM
CLTF
0.189
NYPJM->LTFIMP_NY
CLTF
0.111
LGEELTFEXP_LGEE->PJM
CLTF
0.016
WECLTFEXP_WEC->PJM
CLTF
0.006
CPLELTFEXP_CPLE->PJM
CLTF
0.882
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.601

Details for 3FORK UNION-6FORK UNION 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3FORK UNION-6FORK UNION 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 2193_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.58 %
Rating:291.21 MVA
Rating Type:B
MVA to Mitigate:348.22
MW Contribution:17.8
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
2.427
3151911BEARGRDN G1
50/50
1.881
3144293JTRSVLE
50/50
0.295
971377AH1-170 GEN
Solar/Wind Harmer
3.559
3147623JAMES R
Solar/Wind Harmer
0.773
972003AH1-546 GEN
Solar/Wind Harmer
8.271
970937AG2-583 GEN
Solar/Wind Harmer
10.129
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.064
3146926FARMVIL
Solar/Wind Harmer
0.076
316336AC2-165 C
Solar/Wind Harmer
0.005
3143336POWHATN
Solar/Wind Harmer
1.851
963171AG1-166 GEN
Solar/Wind Harmer
0.466
971563AH1-280 GEN
Solar/Wind Harmer
0.932
970685AG2-442 GEN
Solar/Wind Harmer
5.936
957481AF2-042 GEN
Solar/Wind Harmer
10.616
972205AH1-687 GEN
50/50
9.173
971447AH1-217 GEN
Solar/Wind Harmer
10.245
270494AE1-108_GEN
Solar/Wind Harmer
3.133
971845AH1-439 GEN
Solar/Wind Harmer
7.142
970285AG2-188 GEN
Solar/Wind Harmer
12.024
315657AE1-056 GEN
Solar/Wind Harmer
3.204
946301AF1-294 GEN
Solar/Wind Harmer
1.725
961791AG1-021 GEN
Solar/Wind Harmer
0.839
970683AG2-441 GEN
Solar/Wind Harmer
5.3
970681AG2-440 GEN
Solar/Wind Harmer
4.24
3144303KENBRDG
Solar/Wind Harmer
0.057
971443AH1-215 GEN
Solar/Wind Harmer
1.183
3138266HYDRAULIC
Solar/Wind Helper
0.011
3138266HYDRAULIC
Solar/Wind Helper
0.007
3151921BEARGRDN G2
50/50
1.881
3144293JTRSVLE
50/50
0.295
966251AG1-494 GEN
50/50
1.024
970221AG2-151 GEN
Solar/Wind Harmer
17.795
3146776BUCKING
Solar/Wind Harmer
0.058
3146926FARMVIL
Solar/Wind Harmer
0.076
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.066
316258AE1-075 C
Solar/Wind Harmer
0.079
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
1.573
958131AF2-107 GEN
Solar/Wind Harmer
2.955
970909AG2-566 GEN
Solar/Wind Harmer
1.002
3147133PAMPLIN
Solar/Wind Harmer
0.292
971193AH1-056 GEN
Solar/Wind Harmer
5.657
963181AG1-167 GEN
Solar/Wind Harmer
0.35
959311AF2-222 GEN
Solar/Wind Harmer
6.536
970257AG2-171 GEN
Solar/Wind Harmer
2.276
315785AD2-033 C
Solar/Wind Harmer
0.551
964241AG1-285 GEN
Solar/Wind Harmer
3.933
3144293JTRSVLE
50/50
0.295
3144293JTRSVLE
50/50
0.249
971489AH1-241 GEN
Solar/Wind Harmer
17.795
315821AE2-092 GEN
Solar/Wind Harmer
0.014
3146776BUCKING
Solar/Wind Harmer
0.641
3146776BUCKING
Solar/Wind Harmer
0.052
970301AG2-198 GEN
Solar/Wind Harmer
4.006
3147133PAMPLIN
Solar/Wind Harmer
0.093
3147133PAMPLIN
Solar/Wind Harmer
0.074
958211AF2-115 GEN
Solar/Wind Harmer
1.049
963191AG1-168 GEN
Solar/Wind Harmer
0.35
971741AH1-377 GEN
Solar/Wind Harmer
8.325
316034AC1-036 C
Solar/Wind Harmer
0.005
970323AG2-213 GEN
Solar/Wind Harmer
3.035
971775AH1-396 GEN
Solar/Wind Harmer
0.114
970099AG2-077 GEN
Solar/Wind Harmer
4.247
LAGNLTFEXP_LAGN->PJM
CLTF
0.668
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.404
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.062
MECLTFEXP_MEC->PJM
CLTF
0.174
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.89
TVALTFEXP_TVA->PJM
CLTF
0.332
SIGELTFEXP_SIGE->PJM
CLTF
0.005
NYPJM->LTFIMP_NY
CLTF
0.217
LGEELTFEXP_LGEE->PJM
CLTF
0.042
WECLTFEXP_WEC->PJM
CLTF
0.018
CPLELTFEXP_CPLE->PJM
CLTF
1.434
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.91

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:203.13 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1378.6
MW Contribution:7.01
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.548
3144293JTRSVLE
50/50
0.754
970413AG2-270 GEN
50/50
10.906
3151591KERR 2
50/50
0.234
3151031BRUNSWICKG2
50/50
1.135
3151261ROARAP2
50/50
0.101
3150861SPRUNCD
50/50
0.398
3151391GASTONA
50/50
0.204
3151411GASTONB
50/50
0.204
3146776BUCKING
Solar/Wind Harmer
0.141
3146926FARMVIL
Solar/Wind Harmer
0.188
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
316313AB2-026
Solar/Wind Harmer
0.171
316258AE1-075 C
Solar/Wind Harmer
0.204
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.088
970909AG2-566 GEN
Solar/Wind Harmer
2.566
3147133PAMPLIN
Solar/Wind Harmer
0.741
971193AH1-056 GEN
Solar/Wind Harmer
14.378
963181AG1-167 GEN
Solar/Wind Harmer
0.893
959311AF2-222 GEN
Solar/Wind Harmer
16.945
970257AG2-171 GEN
Solar/Wind Harmer
5.919
315785AD2-033 C
Solar/Wind Harmer
1.44
964241AG1-285 GEN
Solar/Wind Harmer
10.432
316131AB2-060 GEN
Solar/Wind Harmer
0.453
970221AG2-151 GEN
Solar/Wind Harmer
7.009
316478AD1-087 GEN
Solar/Wind Harmer
0.407
316486AD2-202 GEN
Solar/Wind Harmer
0.12
3147043LAWRENC
Solar/Wind Harmer
0.063
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.061
313506AB2-031 GEN
Solar/Wind Harmer
0.265
971683AH1-343 GEN
Solar/Wind Harmer
3.059
970917AG2-570 GEN
Solar/Wind Harmer
7.384
316365GEN2_N
Solar/Wind Harmer
0.176
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
957521AF2-046 GEN
Solar/Wind Harmer
5.572
961681AG1-008 GEN
Solar/Wind Harmer
5.572
3145796HORNRTN
Solar/Wind Harmer
0.297
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316210AC1-098 GEN
Solar/Wind Harmer
0.686
316463AE2-346 GEN
Solar/Wind Harmer
0.063
316140AB2-099
Solar/Wind Harmer
0.026
962331AG1-082 GEN
Solar/Wind Harmer
0.783
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.073
316327AA2-057 GEN
Solar/Wind Harmer
0.108
3145273HOLLAND
Solar/Wind Harmer
0.054
315813AE1-149 C
Solar/Wind Harmer
3.784
3156021HOLLOMANSOL
Solar/Wind Harmer
0.322
315839AE2-212 C
Solar/Wind Harmer
0.001
315724AD1-057 GEN
Solar/Wind Harmer
0.265
970659AG2-427 GEN
Solar/Wind Harmer
0.747
316083AB2-161 GEN
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
0.07
3146233WITAKRS
Solar/Wind Harmer
0.351
3146233WITAKRS
Solar/Wind Harmer
0.048
3138543CONSLDL
Solar/Wind Harmer
0.046
315737AD1-076 GEN
Solar/Wind Harmer
0.896
971157AH1-035 GEN
Solar/Wind Harmer
0.836
965281AG1-393 GEN
Solar/Wind Harmer
0.741
315614AA2-178 GEN
Solar/Wind Harmer
0.398
3146376EDENTON
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
316435W1029_GEN3
Solar/Wind Harmer
0
316320Y1-086
Solar/Wind Harmer
0
3146456SLIGO L269
Solar/Wind Harmer
0.069
971153AH1-033 GEN
Solar/Wind Harmer
0.794
944581AF1-123 GEN
Solar/Wind Harmer
15.457
944601AF1-125 GEN
Solar/Wind Harmer
15.219
3145963POPLR C
Solar/Wind Harmer
0.069
3151101ELIZAR3
Adder
6.349
3144873MCLAUGH
Solar/Wind Harmer
0.002
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.068
971623AH1-311 GEN
Solar/Wind Harmer
0.136
3144536CHRHLND
Solar/Wind Harmer
0.01
3145933PARMELE
Solar/Wind Harmer
0.068
966801AG1-551 GEN
Solar/Wind Harmer
0.788
961601AG1-000A GEN
Solar/Wind Harmer
4.808
315773AC2-141 GEN
Solar/Wind Harmer
2.468
3146073TAR RVR
Solar/Wind Harmer
0.067
3146083TARBORO
Solar/Wind Harmer
0.067
316283AC2-100 C
Solar/Wind Harmer
0.132
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.027
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.798
3151171GRAVELC
Adder
0.923
961611AG1-000B GEN
Solar/Wind Harmer
1.758
315778AD1-151 GEN
Solar/Wind Harmer
5.261
970129AG2-093 GEN
Solar/Wind Harmer
3.971
970133AG2-095 GEN
Solar/Wind Harmer
0.63
3144216WINCHST
Adder
0.231
3150921YORKTN3
Adder
1.525
3142946ENON
Solar/Wind Harmer
0.02
316382AG1-145 C
Solar/Wind Harmer
0
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.175
316499AE2-029_GEN
Solar/Wind Helper
0.514
3132273ORANGE
Solar/Wind Helper
0.027
315616AA1-038_C
Solar/Wind Helper
0.545
3147666LOUISA
Solar/Wind Helper
0.273
3144293JTRSVLE
50/50
0.754
3144293JTRSVLE
50/50
0.635
970535AG2-341 GEN
50/50
2.24
3152661PLYWOOD A
50/50
0.227
3151041BRUNSWICKG3
50/50
1.135
972187AH1-678 GEN
50/50
2.606
315242AE2-183_GT2
50/50
1.418
315241AE2-183_GT1
50/50
1.409
972185AH1-677 GEN
50/50
5.111
970533AG2-339 GEN
50/50
7.548
970531AG2-338 GEN
50/50
3.019
3146776BUCKING
Solar/Wind Harmer
1.571
3146776BUCKING
Solar/Wind Harmer
0.127
970301AG2-198 GEN
Solar/Wind Harmer
10.262
3147133PAMPLIN
Solar/Wind Harmer
0.236
3147133PAMPLIN
Solar/Wind Harmer
0.189
958211AF2-115 GEN
Solar/Wind Harmer
2.678
963191AG1-168 GEN
Solar/Wind Harmer
0.893
971741AH1-377 GEN
Solar/Wind Harmer
21.598
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
7.892
971775AH1-396 GEN
Solar/Wind Harmer
0.296
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971489AH1-241 GEN
Solar/Wind Harmer
7.009
971223AH1-071 GEN
Solar/Wind Harmer
1.334
962561AG1-105 GEN
Solar/Wind Harmer
5.681
939181AE1-148 GEN
Solar/Wind Harmer
5.661
970099AG2-077 GEN
Solar/Wind Harmer
12.506
964791AG1-342 GEN
Solar/Wind Harmer
2.195
3146843MT LREL
Solar/Wind Harmer
0.114
3146843MT LREL
Solar/Wind Harmer
0.114
3143526WINTERP
Solar/Wind Harmer
0.547
970933AG2-581 GEN
Solar/Wind Harmer
7.995
316181AB2-040 GEN
Solar/Wind Harmer
0.124
3145593CAROLNA
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.083
966811AG1-552 GEN
Solar/Wind Harmer
0.899
3145593CAROLNA
Solar/Wind Harmer
0.103
3145783HORNRTN
Solar/Wind Harmer
1.451
3145783HORNRTN
Solar/Wind Harmer
1.161
3145783HORNRTN
Solar/Wind Harmer
0.363
3145783HORNRTN
Solar/Wind Harmer
0.145
316426AA2-053 GEN
Solar/Wind Harmer
0.274
3144356SAPONY
Solar/Wind Harmer
0.654
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
0.503
3145893MURPHYS
Solar/Wind Harmer
0.135
316274AC1-208 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
0.223
3146173TUNIS
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
315742AE1-103 GEN
Solar/Wind Harmer
0.001
970657AG2-426 GEN
Solar/Wind Harmer
2.47
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.223
3146376EDENTON
Solar/Wind Harmer
0.308
3146376EDENTON
Solar/Wind Harmer
0.308
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146386ELIZ CT
Solar/Wind Harmer
0.069
316240AF1-291 C
Solar/Wind Harmer
0.001
3130086AYDLETT
Solar/Wind Harmer
0.275
3137176SLIGO L2192
Solar/Wind Harmer
0.273
3146456SLIGO L269
Solar/Wind Harmer
1.215
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.038
316339AD2-160 GEN
Solar/Wind Harmer
0.111
3145506HICKORY
Solar/Wind Harmer
0.274
3145506HICKORY
Solar/Wind Harmer
0.165
3145506HICKORY
Solar/Wind Harmer
0.041
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.066
316036AC1-147 C
Solar/Wind Harmer
0.013
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.505
316222AC1-221 GEN
Solar/Wind Harmer
0.283
316263AC1-034 GEN
Solar/Wind Harmer
2.586
3145933PARMELE
Solar/Wind Harmer
0.135
3145933PARMELE
Solar/Wind Harmer
0.068
961601AG1-000A GEN
Solar/Wind Harmer
1.202
3145493TOT1
Solar/Wind Harmer
0.156
3145453TOT5
Solar/Wind Harmer
0.094
3145603CNETO
Solar/Wind Harmer
0.063
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.074
3142366NRTHEST
Adder
0.195
3142946ENON
Solar/Wind Harmer
0.006
3150691DARBY 3
Adder
4.195
3150701DARBY 4
Adder
4.185
3150681DARBY 2
Adder
4.18
3150671DARBY 1
Adder
4.175
942751AE2-291 GEN
Solar/Wind Harmer
3.155
966001AG1-469 GEN
Solar/Wind Helper
0.19
972205AH1-687 GEN
50/50
22.18
316303AF2-085
50/50
2.224
3151541CLOVER2
50/50
2.487
3151611KERR 4
50/50
0.234
3151621KERR 5
50/50
0.234
3151631KERR 6
50/50
0.234
3151641KERR 7
50/50
0.234
963041AG1-153 GEN
50/50
2.299
315244AE2-183_ST
50/50
2.451
3151281ROARAP4
50/50
0.1
3151281ROARAP4
50/50
0.094
971285AH1-108 GEN
50/50
0.651
315779AE2-040
50/50
1.092
971845AH1-439 GEN
Solar/Wind Harmer
17.513
970285AG2-188 GEN
Solar/Wind Harmer
29.552
315657AE1-056 GEN
Solar/Wind Harmer
8.144
946301AF1-294 GEN
Solar/Wind Harmer
4.404
961791AG1-021 GEN
Solar/Wind Harmer
2.143
970683AG2-441 GEN
Solar/Wind Harmer
13.644
970681AG2-440 GEN
Solar/Wind Harmer
10.915
3144303KENBRDG
Solar/Wind Harmer
0.148
971443AH1-215 GEN
Solar/Wind Harmer
3.079
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316233AE1-074 FULL
Solar/Wind Harmer
0.084
971281AH1-106 GEN
Solar/Wind Harmer
1.459
971283AH1-107 GEN
Solar/Wind Harmer
1.459
316118AC1-105 GEN
Solar/Wind Harmer
0.27
270494AE1-108_GEN
Solar/Wind Harmer
1.236
970831AG2-522 GEN
Solar/Wind Harmer
4.291
3147173SINAI
Solar/Wind Harmer
0.095
3147243WELCO
Solar/Wind Harmer
0.059
971967AH1-528 GEN
Solar/Wind Harmer
14.709
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
18.242
970673AG2-436 GEN
Solar/Wind Harmer
12.162
941031AE2-094 GEN
Solar/Wind Harmer
15.639
944011AF1-069 GEN
Solar/Wind Harmer
5.11
3137643SOCKMAN
Solar/Wind Harmer
0.336
970085AG2-068 GEN
Solar/Wind Harmer
4.411
970581AG2-369 GEN
Solar/Wind Harmer
3.794
315607AA1-063A GEN
Solar/Wind Harmer
0.164
3146043SEABORD
Solar/Wind Harmer
0.08
315814AE2-033 C
Solar/Wind Harmer
6.192
316315AB2-025 C
Solar/Wind Harmer
0.063
970865AG2-541 GEN
Solar/Wind Harmer
2.68
965291AG1-394 GEN
Solar/Wind Harmer
0.339
315652AC1-086 GEN
Solar/Wind Harmer
8.307
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
3145796HORNRTN
Solar/Wind Harmer
0.238
3145796HORNRTN
Solar/Wind Harmer
0.03
3143316POE
Solar/Wind Harmer
0.292
3146033SCOT NK
Solar/Wind Harmer
0.294
3145513AHOSKIE
Solar/Wind Harmer
0.153
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.146
3145683EARLEYS
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
3146206CASHIE
Solar/Wind Harmer
0.07
970601AG2-382 GEN
Solar/Wind Harmer
2.62
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.048
316311AC2-079 GEN
Solar/Wind Harmer
2.01
316319Z2-044 C
Solar/Wind Harmer
0
315732AD1-074 GEN1
Solar/Wind Harmer
0.4
315733AD1-074 GEN2
Solar/Wind Harmer
0.4
315735AD1-075 GEN1
Solar/Wind Harmer
0.2
3130546PLYMOUTH
Solar/Wind Harmer
0.07
315835AF2-110_GEN
Solar/Wind Harmer
0.478
315816AE2-034 GEN
Solar/Wind Harmer
0.298
3130156CHOWAN
Solar/Wind Harmer
0.069
3130156CHOWAN
Solar/Wind Harmer
0.069
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3146486SUNBURY
Solar/Wind Harmer
0.069
3146486SUNBURY
Solar/Wind Harmer
0.069
316321Z2-027
Solar/Wind Harmer
0.013
3145176PASQUOTANK
Solar/Wind Harmer
0.043
3146396TANGLEW
Solar/Wind Harmer
0.19
316305AF2-043 C
Solar/Wind Harmer
0.001
313526AB2-022
Solar/Wind Harmer
0.037
3146406KITTY HAWK
Solar/Wind Harmer
0.009
319010AE1-072 C
Solar/Wind Harmer
0.346
957871AF2-081 GEN
Solar/Wind Harmer
3.419
3151081ELIZAR1
Adder
6.268
3151091ELIZAR2
Adder
6.16
3152611GOSPORTB
Adder
0.871
3152621GOSPORTC
Adder
0.739
3152601GOSPORTA
Adder
0.682
3145573BETHELC
Solar/Wind Harmer
0.067
3145573BETHELC
Solar/Wind Harmer
0.067
316420AA1-050 GEN
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
2.903
316005AA1-067
Solar/Wind Harmer
0.072
3145746EVERETS
Solar/Wind Harmer
0.267
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
970181AG2-120 GEN
Solar/Wind Harmer
0.836
971445AH1-216 GEN
Solar/Wind Harmer
4.703
972265AH1-717 GEN
Adder
5.124
3151201GRAVEL4
Adder
4.803
3151191GRAVEL3
Adder
4.742
3151211GRAVEL5
Adder
4.742
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.353
316123AC1-075 GEN
Solar/Wind Harmer
0.09
970165AG2-112 GEN
Solar/Wind Harmer
0.531
970163AG2-111 GEN
Solar/Wind Harmer
0.506
971447AH1-217 GEN
Solar/Wind Harmer
1.848
971167AH1-042 GEN
Solar/Wind Harmer
5.088
3138283WHITEMARSH
Solar/Wind Harmer
0.013
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.105
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.12
3151931BEARGRDN S1
50/50
5.869
3151911BEARGRDN G1
50/50
4.548
3144293JTRSVLE
50/50
0.754
970119AG2-088 GEN
50/50
16.679
3151531CLOVER1
50/50
2.499
3151601KERR 3
50/50
0.234
3151581KERR 1
50/50
0.083
3147043LAWRENC
50/50
1
3151051BRUNSWICKS1
50/50
2.357
3151021BRUNSWICKG1
50/50
1.135
971451AH1-221 GEN
50/50
3.449
315243AE2-183_GT3
50/50
1.418
3151261ROARAP2
50/50
0.103
3150851SPRUNCC
50/50
0.398
3151391GASTONA
50/50
0.204
3151411GASTONB
50/50
0.204
972003AH1-546 GEN
Solar/Wind Harmer
20.039
970937AG2-583 GEN
Solar/Wind Harmer
24.928
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.157
3146926FARMVIL
Solar/Wind Harmer
0.188
316336AC2-165 C
Solar/Wind Harmer
0.012
3143336POWHATN
Solar/Wind Harmer
4.81
963171AG1-166 GEN
Solar/Wind Harmer
1.19
971563AH1-280 GEN
Solar/Wind Harmer
2.381
970685AG2-442 GEN
Solar/Wind Harmer
15.281
962491AG1-098 GEN
Solar/Wind Harmer
8.349
315693AD1-088 GEN
Solar/Wind Harmer
6.776
316237AB2-079_GEN
Solar/Wind Harmer
0.001
971377AH1-170 GEN
Solar/Wind Harmer
1.402
3147623JAMES R
Solar/Wind Harmer
0.305
3143226MDLTHAN
Solar/Wind Harmer
0.125
957481AF2-042 GEN
Solar/Wind Harmer
31.266
970401AG2-262 GEN
Solar/Wind Harmer
0.671
315687AD1-152 GEN
Solar/Wind Harmer
0.003
3143526WINTERP
Solar/Wind Harmer
0.547
971065AG2-659 GEN
Solar/Wind Harmer
4.446
316129AC1-054 GEN
Solar/Wind Harmer
0.385
971795AH1-408 GEN
Solar/Wind Harmer
6.611
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.847
970919AG2-571 GEN
Solar/Wind Harmer
2.953
970087AG2-069 GEN
Solar/Wind Harmer
6.617
3145783HORNRTN
Solar/Wind Harmer
0.082
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
6.459
316023GEN1_S
Solar/Wind Harmer
0.176
939411AE1-173 GEN
Solar/Wind Harmer
33.156
3146263WOODLND
Solar/Wind Harmer
0.076
316011AB1-132 GEN
Solar/Wind Harmer
1.373
962571AG1-106 GEN
Solar/Wind Harmer
1.074
3145893MURPHYS
Solar/Wind Harmer
0.301
3145893MURPHYS
Solar/Wind Harmer
0.334
3145796HORNRTN
Solar/Wind Harmer
0.245
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316212AC1-099_GEN
Solar/Wind Harmer
0.382
3145823KELFORD
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
315722AD1-056 GEN
Solar/Wind Harmer
0.447
970659AG2-427 GEN
Solar/Wind Harmer
3.416
316381AD1-082 GEN
Solar/Wind Harmer
0.074
970661AG2-428 GEN
Solar/Wind Harmer
7.004
3146206CASHIE
Solar/Wind Harmer
0.07
971547AH1-271 GEN
Solar/Wind Harmer
1.497
3142543TWELFTH
Solar/Wind Harmer
0.007
3146233WITAKRS
Solar/Wind Harmer
0.278
316093AE2-104_GEN
Solar/Wind Harmer
1.171
3145663CRESWEL
Solar/Wind Harmer
0.194
971163AH1-040 GEN
Solar/Wind Harmer
5.558
3130156CHOWAN
Solar/Wind Harmer
0.069
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.223
3146516WINFALL
Solar/Wind Harmer
0.069
315671AE2-027_GEN
Solar/Wind Harmer
4.41
316246AF1-032 C
Solar/Wind Harmer
0.031
3146456SLIGO L269
Solar/Wind Harmer
0.069
316388AE2-253 GEN
Solar/Wind Harmer
0.215
944591AF1-124 GEN
Solar/Wind Harmer
15.512
3145963POPLR C
Solar/Wind Harmer
0.069
316174AB2-169 GEN
Solar/Wind Harmer
0.002
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.853
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.054
316359AB2-059 GEN
Solar/Wind Harmer
0.244
316049AB1-081 GEN
Solar/Wind Harmer
0.389
3142053HEARTS
Solar/Wind Harmer
0.12
316072AD1-144
Solar/Wind Harmer
0.025
3146293MARTNCO
Solar/Wind Harmer
0.063
316294AC1-161 GEN
Solar/Wind Harmer
1.171
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.067
3145493TOT1
Solar/Wind Harmer
0.3
316494AC1-189 GEN
Solar/Wind Harmer
0.227
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.267
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
961611AG1-000B GEN
Solar/Wind Harmer
3.457
971647AH1-324 GEN
Solar/Wind Harmer
2.81
971069AG2-661 GEN
Solar/Wind Harmer
1.169
316458AB2-190 GEN2
Solar/Wind Harmer
0.353
970129AG2-093 GEN
Solar/Wind Harmer
1.869
944631AF1-128 GEN
Adder
29.45
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971317AH1-138 GEN
Solar/Wind Harmer
0.439
316159AE1-175 C
Solar/Wind Harmer
0.05
3142433PROV 92
Solar/Wind Harmer
0.226
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.056
316192AB2-158 GEN
Solar/Wind Helper
0.823
3147666LOUISA
Solar/Wind Helper
0.475
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.726
MECLTFEXP_MEC->PJM
CLTF
0.354
LAGNLTFEXP_LAGN->PJM
CLTF
1.781
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.535
TVALTFEXP_TVA->PJM
CLTF
0.87
SIGELTFEXP_SIGE->PJM
CLTF
0.008
CPLELTFEXP_CPLE->PJM
CLTF
4.352
NYPJM->LTFIMP_NY
CLTF
0.579
LGEELTFEXP_LGEE->PJM
CLTF
0.048
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.276
WECLTFEXP_WEC->PJM
CLTF
0.018

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:185.6 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1540.5
MW Contribution:9.18
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.146
316303AF2-085
50/50
2.223
3151541CLOVER2
50/50
2.485
3151611KERR 4
50/50
0.233
3151621KERR 5
50/50
0.233
3151631KERR 6
50/50
0.233
3151641KERR 7
50/50
0.233
971845AH1-439 GEN
Solar/Wind Harmer
23.024
970285AG2-188 GEN
Solar/Wind Harmer
36.67
315657AE1-056 GEN
Solar/Wind Harmer
9.935
946301AF1-294 GEN
Solar/Wind Harmer
6.417
961791AG1-021 GEN
Solar/Wind Harmer
3.13
970683AG2-441 GEN
Solar/Wind Harmer
17.94
970681AG2-440 GEN
Solar/Wind Harmer
14.352
3144303KENBRDG
Solar/Wind Harmer
-0.017
971443AH1-215 GEN
Solar/Wind Harmer
4.049
316239AB2-077_GEN
Solar/Wind Harmer
0.467
316238AB2-078_GEN
Solar/Wind Harmer
0.467
316233AE1-074 FULL
Solar/Wind Harmer
0.318
971281AH1-106 GEN
Solar/Wind Harmer
1.921
971283AH1-107 GEN
Solar/Wind Harmer
1.921
316118AC1-105 GEN
Solar/Wind Harmer
0.807
270494AE1-108_GEN
Solar/Wind Harmer
2.995
970831AG2-522 GEN
Solar/Wind Harmer
5.644
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
19.409
946281AF1-292 GEN
Solar/Wind Harmer
0.222
316087AB2-174 GEN
Solar/Wind Harmer
1.385
970673AG2-436 GEN
Solar/Wind Harmer
20.177
970673AG2-436 GEN
Solar/Wind Harmer
10.216
941031AE2-094 GEN
Solar/Wind Harmer
17.883
944011AF1-069 GEN
Solar/Wind Harmer
5.603
3137643SOCKMAN
Solar/Wind Harmer
-0.038
970085AG2-068 GEN
Solar/Wind Harmer
5.805
970581AG2-369 GEN
Solar/Wind Harmer
4.993
971285AH1-108 GEN
Adder
0.613
315607AA1-063A GEN
Solar/Wind Harmer
0.911
3146043SEABORD
Solar/Wind Harmer
-0.009
315814AE2-033 C
Solar/Wind Harmer
8.189
316315AB2-025 C
Solar/Wind Harmer
0.237
970865AG2-541 GEN
Solar/Wind Harmer
3.523
965291AG1-394 GEN
Solar/Wind Harmer
0.761
315652AC1-086 GEN
Solar/Wind Harmer
9.545
316318V4-068
Solar/Wind Harmer
0.211
3151931BEARGRDN S1
50/50
5.86
3151911BEARGRDN G1
50/50
4.541
3144293JTRSVLE
50/50
0.753
970119AG2-088 GEN
50/50
16.672
3151531CLOVER1
50/50
2.497
3151601KERR 3
50/50
0.233
3151581KERR 1
50/50
0.083
972003AH1-546 GEN
Solar/Wind Harmer
26.388
970937AG2-583 GEN
Solar/Wind Harmer
32.774
316322AB2-045
Solar/Wind Harmer
1.483
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.021
316336AC2-165 C
Solar/Wind Harmer
6.018
3143336POWHATN
Solar/Wind Harmer
3.603
963171AG1-166 GEN
Solar/Wind Harmer
3.13
971563AH1-280 GEN
Solar/Wind Harmer
3.13
970685AG2-442 GEN
Solar/Wind Harmer
20.093
962491AG1-098 GEN
Solar/Wind Harmer
10.981
315693AD1-088 GEN
Solar/Wind Harmer
7.922
316237AB2-079_GEN
Solar/Wind Harmer
0.467
971377AH1-170 GEN
Solar/Wind Harmer
1.836
3147623JAMES R
Solar/Wind Harmer
0.227
3143226MDLTHAN
Solar/Wind Harmer
-0.014
957481AF2-042 GEN
Solar/Wind Harmer
41.127
970401AG2-262 GEN
Solar/Wind Harmer
0.837
315687AD1-152 GEN
Solar/Wind Harmer
1.432
3143526WINTERP
Solar/Wind Harmer
-0.061
3147043LAWRENC
Adder
0.942
971065AG2-659 GEN
Solar/Wind Harmer
5.848
316129AC1-054 GEN
Solar/Wind Harmer
1.008
971795AH1-408 GEN
Solar/Wind Harmer
8.35
316003AC1-222 GEN
Solar/Wind Harmer
0.972
960081AF2-299 GEN
Solar/Wind Harmer
1.114
970919AG2-571 GEN
Solar/Wind Harmer
2.952
970087AG2-069 GEN
Solar/Wind Harmer
8.708
3145783HORNRTN
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.375
316190AA2-174 GEN
Solar/Wind Harmer
0.112
940641AE2-051 GEN
Solar/Wind Harmer
8.503
3151921BEARGRDN G2
50/50
4.541
3144293JTRSVLE
50/50
0.753
970413AG2-270 GEN
50/50
10.895
3151591KERR 2
50/50
0.233
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
4.6
316313AB2-026
Solar/Wind Harmer
0.819
316258AE1-075 C
Solar/Wind Harmer
0.737
316405AF2-144 C
Solar/Wind Harmer
0.778
3143336POWHATN
Solar/Wind Harmer
3.062
970909AG2-566 GEN
Solar/Wind Harmer
2.562
3147133PAMPLIN
Solar/Wind Harmer
-0.083
971193AH1-056 GEN
Solar/Wind Harmer
16.559
963181AG1-167 GEN
Solar/Wind Harmer
2.348
959311AF2-222 GEN
Solar/Wind Harmer
22.325
970257AG2-171 GEN
Solar/Wind Harmer
7.783
315785AD2-033 C
Solar/Wind Harmer
4.506
964241AG1-285 GEN
Solar/Wind Harmer
13.718
316131AB2-060 GEN
Solar/Wind Harmer
1.742
970221AG2-151 GEN
Solar/Wind Harmer
9.178
316478AD1-087 GEN
Solar/Wind Harmer
1.133
316486AD2-202 GEN
Solar/Wind Harmer
0.332
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.322
960061AF2-297 GEN
Solar/Wind Harmer
5.34
966621AG1-532 GEN
Solar/Wind Harmer
0.201
313506AB2-031 GEN
Solar/Wind Harmer
0.773
970917AG2-570 GEN
Solar/Wind Harmer
23.32
971683AH1-343 GEN
Solar/Wind Harmer
4.021
3150861SPRUNCD
Adder
0.375
316365GEN2_N
Solar/Wind Harmer
0.594
3156081AA2-088 GEN
Solar/Wind Harmer
2.773
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.624
961681AG1-008 GEN
Solar/Wind Harmer
6.624
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.302
316463AE2-346 GEN
Solar/Wind Harmer
0.133
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.031
316317KELFORD C
Solar/Wind Harmer
0.388
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.813
3145273HOLLAND
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
4.985
3156021HOLLOMANSOL
Solar/Wind Harmer
1.073
315839AE2-212 C
Solar/Wind Harmer
0.24
970659AG2-427 GEN
Solar/Wind Harmer
0.748
316083AB2-161 GEN
Solar/Wind Harmer
1.288
315724AD1-057 GEN
Solar/Wind Harmer
0.456
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.033
316023GEN1_S
Solar/Wind Harmer
0.594
939411AE1-173 GEN
Solar/Wind Harmer
43.657
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.775
962571AG1-106 GEN
Solar/Wind Harmer
1.22
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.723
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.219
316381AD1-082 GEN
Solar/Wind Harmer
0.728
315722AD1-056 GEN
Solar/Wind Harmer
0.83
970661AG2-428 GEN
Solar/Wind Harmer
8.41
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
1.971
3146233WITAKRS
Solar/Wind Harmer
-0.031
316093AE2-104_GEN
Solar/Wind Harmer
2.275
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.318
3130156CHOWAN
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
1.92
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.811
316246AF1-032 C
Solar/Wind Harmer
0.157
3146456SLIGO L269
Solar/Wind Harmer
-0.008
316388AE2-253 GEN
Solar/Wind Harmer
0.521
944591AF1-124 GEN
Solar/Wind Harmer
35.229
3150981CHESPKA
Adder
0.854
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
944631AF1-128 GEN
Adder
29.484
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.057
316192AB2-158 GEN
Solar/Wind Helper
0.927
3147666LOUISA
Solar/Wind Helper
0.538
3146033SCOT NK
Solar/Wind Harmer
-0.033
3145513AHOSKIE
Solar/Wind Harmer
0.072
961941AG1-037 GEN
Solar/Wind Harmer
0.062
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.449
315833AF1-017_GEN
Solar/Wind Harmer
1.494
316349AD2-085 GEN
Solar/Wind Harmer
0.7
316311AC2-079 GEN
Solar/Wind Harmer
3.968
316319Z2-044 C
Solar/Wind Harmer
0.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.583
315733AD1-074 GEN2
Solar/Wind Harmer
1.583
315735AD1-075 GEN1
Solar/Wind Harmer
0.792
315835AF2-110_GEN
Solar/Wind Harmer
0.978
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.632
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
1.92
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.209
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.142
316305AF2-043 C
Solar/Wind Harmer
0.233
313526AB2-022
Solar/Wind Harmer
0.209
319010AE1-072 C
Solar/Wind Harmer
1.562
3146406KITTY HAWK
Solar/Wind Harmer
0.006
957871AF2-081 GEN
Solar/Wind Harmer
3.86
3151081ELIZAR1
Adder
6.271
3151091ELIZAR2
Adder
6.162
3152611GOSPORTB
Adder
0.871
3152621GOSPORTC
Adder
0.739
3152601GOSPORTA
Adder
0.682
972265AH1-717 GEN
Adder
5.127
3151201GRAVEL4
Adder
4.806
3151191GRAVEL3
Adder
4.745
3151211GRAVEL5
Adder
4.745
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.121
3144293JTRSVLE
50/50
0.753
3144293JTRSVLE
50/50
0.634
970535AG2-341 GEN
50/50
2.238
3146776BUCKING
Solar/Wind Harmer
-0.175
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.493
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.913
963191AG1-168 GEN
Solar/Wind Harmer
2.348
971741AH1-377 GEN
Solar/Wind Harmer
28.4
316034AC1-036 C
Solar/Wind Harmer
0.386
970323AG2-213 GEN
Solar/Wind Harmer
10.377
971775AH1-396 GEN
Solar/Wind Harmer
1.478
313527AB2-043 GEN
Solar/Wind Harmer
2.568
971489AH1-241 GEN
Solar/Wind Harmer
8.713
971223AH1-071 GEN
Solar/Wind Harmer
1.756
962561AG1-105 GEN
Solar/Wind Harmer
7.471
939181AE1-148 GEN
Solar/Wind Harmer
7.446
970099AG2-077 GEN
Solar/Wind Harmer
16.451
964791AG1-342 GEN
Solar/Wind Harmer
2.74
3146843MT LREL
Solar/Wind Harmer
-0.013
3146843MT LREL
Solar/Wind Harmer
-0.013
3143526WINTERP
Solar/Wind Harmer
-0.061
970933AG2-581 GEN
Solar/Wind Harmer
10.52
972187AH1-678 GEN
Adder
2.454
972185AH1-677 GEN
Adder
4.815
316181AB2-040 GEN
Solar/Wind Harmer
1.342
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
1.047
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.088
3145783HORNRTN
Solar/Wind Harmer
0.87
3145783HORNRTN
Solar/Wind Harmer
0.272
3145783HORNRTN
Solar/Wind Harmer
0.109
316426AA2-053 GEN
Solar/Wind Harmer
0.92
3144356SAPONY
Solar/Wind Harmer
0.307
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
316274AC1-208 GEN
Solar/Wind Harmer
0.909
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.852
970657AG2-426 GEN
Solar/Wind Harmer
2.477
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.932
3146376EDENTON
Solar/Wind Harmer
0.231
3146376EDENTON
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.405
316433W1029_GEN2
Solar/Wind Harmer
1.405
316240AF1-291 C
Solar/Wind Harmer
0.233
3146386ELIZ CT
Solar/Wind Harmer
-0.008
3130086AYDLETT
Solar/Wind Harmer
-0.031
3137176SLIGO L2192
Solar/Wind Harmer
-0.031
3146456SLIGO L269
Solar/Wind Harmer
0.912
316018AA1-139 ULT2
Solar/Wind Harmer
0.661
316017AA1-139 ULT1
Solar/Wind Harmer
0.625
316339AD2-160 GEN
Solar/Wind Harmer
0.521
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.529
3142366NRTHEST
Adder
0.195
3150691DARBY 3
Adder
4.201
3150701DARBY 4
Adder
4.191
3150681DARBY 2
Adder
4.186
3150671DARBY 1
Adder
4.181
966001AG1-469 GEN
Solar/Wind Helper
0.199
3146233WITAKRS
Solar/Wind Harmer
0.164
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.488
971157AH1-035 GEN
Solar/Wind Harmer
0.978
965281AG1-393 GEN
Solar/Wind Harmer
0.977
315614AA2-178 GEN
Solar/Wind Harmer
0.842
3146376EDENTON
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316435W1029_GEN3
Solar/Wind Harmer
1.405
316320Y1-086
Solar/Wind Harmer
0.453
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.941
944581AF1-123 GEN
Solar/Wind Harmer
35.103
3151101ELIZAR3
Adder
6.351
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.801
3151171GRAVELC
Adder
0.924
3144216WINCHST
Adder
0.232
3150921YORKTN3
Adder
1.526
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.176
316499AE2-029_GEN
Solar/Wind Helper
0.517
3132273ORANGE
Solar/Wind Helper
0.028
3147666LOUISA
Solar/Wind Helper
0.309
315616AA1-038_C
Solar/Wind Helper
0.548
944601AF1-125 GEN
Solar/Wind Harmer
11.266
LAGNLTFEXP_LAGN->PJM
CLTF
1.77
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
0.346
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.515
TVALTFEXP_TVA->PJM
CLTF
0.864
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.574
LGEELTFEXP_LGEE->PJM
CLTF
0.044
WECLTFEXP_WEC->PJM
CLTF
0.016
CPLELTFEXP_CPLE->PJM
CLTF
4.345
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.202

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:185.6 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1540.49
MW Contribution:9.18
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.86
3151911BEARGRDN G1
50/50
4.54
3144293JTRSVLE
50/50
0.753
970119AG2-088 GEN
50/50
16.671
3151531CLOVER1
50/50
2.497
3151601KERR 3
50/50
0.233
3151581KERR 1
50/50
0.083
972003AH1-546 GEN
Solar/Wind Harmer
26.387
970937AG2-583 GEN
Solar/Wind Harmer
32.773
316322AB2-045
Solar/Wind Harmer
1.483
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.021
316336AC2-165 C
Solar/Wind Harmer
6.018
3143336POWHATN
Solar/Wind Harmer
3.603
963171AG1-166 GEN
Solar/Wind Harmer
3.13
971563AH1-280 GEN
Solar/Wind Harmer
3.13
970685AG2-442 GEN
Solar/Wind Harmer
20.093
962491AG1-098 GEN
Solar/Wind Harmer
10.981
315693AD1-088 GEN
Solar/Wind Harmer
7.922
316237AB2-079_GEN
Solar/Wind Harmer
0.467
971377AH1-170 GEN
Solar/Wind Harmer
1.835
3147623JAMES R
Solar/Wind Harmer
0.227
3143226MDLTHAN
Solar/Wind Harmer
-0.014
957481AF2-042 GEN
Solar/Wind Harmer
41.127
970401AG2-262 GEN
Solar/Wind Harmer
0.837
315687AD1-152 GEN
Solar/Wind Harmer
1.432
3143526WINTERP
Solar/Wind Harmer
-0.061
3147043LAWRENC
Adder
0.942
971065AG2-659 GEN
Solar/Wind Harmer
5.848
316129AC1-054 GEN
Solar/Wind Harmer
1.008
971795AH1-408 GEN
Solar/Wind Harmer
8.349
316003AC1-222 GEN
Solar/Wind Harmer
0.972
960081AF2-299 GEN
Solar/Wind Harmer
1.114
970919AG2-571 GEN
Solar/Wind Harmer
2.952
970087AG2-069 GEN
Solar/Wind Harmer
8.708
3145783HORNRTN
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.375
316190AA2-174 GEN
Solar/Wind Harmer
0.112
940641AE2-051 GEN
Solar/Wind Harmer
8.503
316023GEN1_S
Solar/Wind Harmer
0.594
939411AE1-173 GEN
Solar/Wind Harmer
43.657
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.775
962571AG1-106 GEN
Solar/Wind Harmer
1.22
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.723
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.219
316381AD1-082 GEN
Solar/Wind Harmer
0.728
315722AD1-056 GEN
Solar/Wind Harmer
0.83
970661AG2-428 GEN
Solar/Wind Harmer
8.41
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
1.971
3146233WITAKRS
Solar/Wind Harmer
-0.031
316093AE2-104_GEN
Solar/Wind Harmer
2.275
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.318
3130156CHOWAN
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
1.92
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.811
316246AF1-032 C
Solar/Wind Harmer
0.157
3146456SLIGO L269
Solar/Wind Harmer
-0.008
316388AE2-253 GEN
Solar/Wind Harmer
0.521
944591AF1-124 GEN
Solar/Wind Harmer
35.23
3150981CHESPKA
Adder
0.854
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
944631AF1-128 GEN
Adder
29.485
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.057
316192AB2-158 GEN
Solar/Wind Helper
0.928
3147666LOUISA
Solar/Wind Helper
0.539
972205AH1-687 GEN
50/50
22.145
316303AF2-085
50/50
2.223
3151541CLOVER2
50/50
2.485
3151611KERR 4
50/50
0.233
3151621KERR 5
50/50
0.233
3151631KERR 6
50/50
0.233
3151641KERR 7
50/50
0.233
971845AH1-439 GEN
Solar/Wind Harmer
23.024
970285AG2-188 GEN
Solar/Wind Harmer
36.669
315657AE1-056 GEN
Solar/Wind Harmer
9.935
946301AF1-294 GEN
Solar/Wind Harmer
6.417
961791AG1-021 GEN
Solar/Wind Harmer
3.13
970683AG2-441 GEN
Solar/Wind Harmer
17.94
970681AG2-440 GEN
Solar/Wind Harmer
14.352
3144303KENBRDG
Solar/Wind Harmer
-0.017
971443AH1-215 GEN
Solar/Wind Harmer
4.049
316239AB2-077_GEN
Solar/Wind Harmer
0.467
316238AB2-078_GEN
Solar/Wind Harmer
0.467
316233AE1-074 FULL
Solar/Wind Harmer
0.318
971281AH1-106 GEN
Solar/Wind Harmer
1.921
971283AH1-107 GEN
Solar/Wind Harmer
1.921
316118AC1-105 GEN
Solar/Wind Harmer
0.807
270494AE1-108_GEN
Solar/Wind Harmer
2.995
970831AG2-522 GEN
Solar/Wind Harmer
5.644
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
19.408
946281AF1-292 GEN
Solar/Wind Harmer
0.222
316087AB2-174 GEN
Solar/Wind Harmer
1.385
970673AG2-436 GEN
Solar/Wind Harmer
20.177
970673AG2-436 GEN
Solar/Wind Harmer
10.216
941031AE2-094 GEN
Solar/Wind Harmer
17.883
944011AF1-069 GEN
Solar/Wind Harmer
5.603
3137643SOCKMAN
Solar/Wind Harmer
-0.038
970085AG2-068 GEN
Solar/Wind Harmer
5.805
970581AG2-369 GEN
Solar/Wind Harmer
4.993
971285AH1-108 GEN
Adder
0.613
315607AA1-063A GEN
Solar/Wind Harmer
0.911
3146043SEABORD
Solar/Wind Harmer
-0.009
315814AE2-033 C
Solar/Wind Harmer
8.189
316315AB2-025 C
Solar/Wind Harmer
0.237
970865AG2-541 GEN
Solar/Wind Harmer
3.523
965291AG1-394 GEN
Solar/Wind Harmer
0.761
315652AC1-086 GEN
Solar/Wind Harmer
9.545
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.033
3146033SCOT NK
Solar/Wind Harmer
-0.033
3145513AHOSKIE
Solar/Wind Harmer
0.072
961941AG1-037 GEN
Solar/Wind Harmer
0.062
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.449
315833AF1-017_GEN
Solar/Wind Harmer
1.494
316349AD2-085 GEN
Solar/Wind Harmer
0.7
316311AC2-079 GEN
Solar/Wind Harmer
3.968
316319Z2-044 C
Solar/Wind Harmer
0.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.583
315733AD1-074 GEN2
Solar/Wind Harmer
1.583
315735AD1-075 GEN1
Solar/Wind Harmer
0.792
315835AF2-110_GEN
Solar/Wind Harmer
0.978
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.632
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
1.92
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.209
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.142
316305AF2-043 C
Solar/Wind Harmer
0.233
313526AB2-022
Solar/Wind Harmer
0.209
319010AE1-072 C
Solar/Wind Harmer
1.562
3146406KITTY HAWK
Solar/Wind Harmer
0.006
957871AF2-081 GEN
Solar/Wind Harmer
3.86
3151081ELIZAR1
Adder
6.271
3151091ELIZAR2
Adder
6.162
3152611GOSPORTB
Adder
0.871
3152621GOSPORTC
Adder
0.739
3152601GOSPORTA
Adder
0.682
972265AH1-717 GEN
Adder
5.127
3151201GRAVEL4
Adder
4.806
3151191GRAVEL3
Adder
4.746
3151211GRAVEL5
Adder
4.746
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.121
3144293JTRSVLE
50/50
0.753
3144293JTRSVLE
50/50
0.634
970535AG2-341 GEN
50/50
2.237
3146776BUCKING
Solar/Wind Harmer
-0.175
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.493
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.913
963191AG1-168 GEN
Solar/Wind Harmer
2.348
971741AH1-377 GEN
Solar/Wind Harmer
28.4
316034AC1-036 C
Solar/Wind Harmer
0.386
970323AG2-213 GEN
Solar/Wind Harmer
10.377
971775AH1-396 GEN
Solar/Wind Harmer
1.478
313527AB2-043 GEN
Solar/Wind Harmer
2.568
971489AH1-241 GEN
Solar/Wind Harmer
8.713
971223AH1-071 GEN
Solar/Wind Harmer
1.756
962561AG1-105 GEN
Solar/Wind Harmer
7.471
939181AE1-148 GEN
Solar/Wind Harmer
7.446
970099AG2-077 GEN
Solar/Wind Harmer
16.451
964791AG1-342 GEN
Solar/Wind Harmer
2.74
3146843MT LREL
Solar/Wind Harmer
-0.013
3146843MT LREL
Solar/Wind Harmer
-0.013
3143526WINTERP
Solar/Wind Harmer
-0.061
970933AG2-581 GEN
Solar/Wind Harmer
10.52
972187AH1-678 GEN
Adder
2.454
972185AH1-677 GEN
Adder
4.815
316181AB2-040 GEN
Solar/Wind Harmer
1.342
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
1.047
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.088
3145783HORNRTN
Solar/Wind Harmer
0.87
3145783HORNRTN
Solar/Wind Harmer
0.272
3145783HORNRTN
Solar/Wind Harmer
0.109
316426AA2-053 GEN
Solar/Wind Harmer
0.92
3144356SAPONY
Solar/Wind Harmer
0.307
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
316274AC1-208 GEN
Solar/Wind Harmer
0.909
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.852
970657AG2-426 GEN
Solar/Wind Harmer
2.477
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.932
3146376EDENTON
Solar/Wind Harmer
0.231
3146376EDENTON
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.405
316433W1029_GEN2
Solar/Wind Harmer
1.405
316240AF1-291 C
Solar/Wind Harmer
0.233
3146386ELIZ CT
Solar/Wind Harmer
-0.008
3130086AYDLETT
Solar/Wind Harmer
-0.031
3137176SLIGO L2192
Solar/Wind Harmer
-0.031
3146456SLIGO L269
Solar/Wind Harmer
0.912
316018AA1-139 ULT2
Solar/Wind Harmer
0.661
316017AA1-139 ULT1
Solar/Wind Harmer
0.625
316339AD2-160 GEN
Solar/Wind Harmer
0.521
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.53
3142366NRTHEST
Adder
0.195
3150691DARBY 3
Adder
4.201
3150701DARBY 4
Adder
4.191
3150681DARBY 2
Adder
4.186
3150671DARBY 1
Adder
4.181
966001AG1-469 GEN
Solar/Wind Helper
0.199
3151921BEARGRDN G2
50/50
4.54
3144293JTRSVLE
50/50
0.753
970413AG2-270 GEN
50/50
10.894
3151591KERR 2
50/50
0.233
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
4.6
316313AB2-026
Solar/Wind Harmer
0.819
316258AE1-075 C
Solar/Wind Harmer
0.737
316405AF2-144 C
Solar/Wind Harmer
0.778
3143336POWHATN
Solar/Wind Harmer
3.062
970909AG2-566 GEN
Solar/Wind Harmer
2.562
3147133PAMPLIN
Solar/Wind Harmer
-0.083
971193AH1-056 GEN
Solar/Wind Harmer
16.559
963181AG1-167 GEN
Solar/Wind Harmer
2.348
959311AF2-222 GEN
Solar/Wind Harmer
22.325
970257AG2-171 GEN
Solar/Wind Harmer
7.783
315785AD2-033 C
Solar/Wind Harmer
4.506
964241AG1-285 GEN
Solar/Wind Harmer
13.718
316131AB2-060 GEN
Solar/Wind Harmer
1.742
970221AG2-151 GEN
Solar/Wind Harmer
9.177
316478AD1-087 GEN
Solar/Wind Harmer
1.133
316486AD2-202 GEN
Solar/Wind Harmer
0.332
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.322
960061AF2-297 GEN
Solar/Wind Harmer
5.34
966621AG1-532 GEN
Solar/Wind Harmer
0.201
313506AB2-031 GEN
Solar/Wind Harmer
0.773
970917AG2-570 GEN
Solar/Wind Harmer
23.32
971683AH1-343 GEN
Solar/Wind Harmer
4.021
3150861SPRUNCD
Adder
0.375
316365GEN2_N
Solar/Wind Harmer
0.594
3156081AA2-088 GEN
Solar/Wind Harmer
2.773
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.624
961681AG1-008 GEN
Solar/Wind Harmer
6.624
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.302
316463AE2-346 GEN
Solar/Wind Harmer
0.133
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.031
316317KELFORD C
Solar/Wind Harmer
0.388
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.813
3145273HOLLAND
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
4.985
3156021HOLLOMANSOL
Solar/Wind Harmer
1.073
315839AE2-212 C
Solar/Wind Harmer
0.24
970659AG2-427 GEN
Solar/Wind Harmer
0.748
316083AB2-161 GEN
Solar/Wind Harmer
1.288
315724AD1-057 GEN
Solar/Wind Harmer
0.456
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
-0.008
3146233WITAKRS
Solar/Wind Harmer
0.164
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.488
971157AH1-035 GEN
Solar/Wind Harmer
0.978
965281AG1-393 GEN
Solar/Wind Harmer
0.977
315614AA2-178 GEN
Solar/Wind Harmer
0.842
3146376EDENTON
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316435W1029_GEN3
Solar/Wind Harmer
1.405
316320Y1-086
Solar/Wind Harmer
0.453
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.941
944581AF1-123 GEN
Solar/Wind Harmer
35.103
3151101ELIZAR3
Adder
6.351
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.801
3151171GRAVELC
Adder
0.924
3144216WINCHST
Adder
0.232
3150921YORKTN3
Adder
1.526
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.176
316499AE2-029_GEN
Solar/Wind Helper
0.517
3132273ORANGE
Solar/Wind Helper
0.028
3147666LOUISA
Solar/Wind Helper
0.31
315616AA1-038_C
Solar/Wind Helper
0.549
944601AF1-125 GEN
Solar/Wind Harmer
11.266
LAGNLTFEXP_LAGN->PJM
CLTF
1.769
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
0.346
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.514
TVALTFEXP_TVA->PJM
CLTF
0.864
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.574
LGEELTFEXP_LGEE->PJM
CLTF
0.044
WECLTFEXP_WEC->PJM
CLTF
0.016
CPLELTFEXP_CPLE->PJM
CLTF
4.345
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.201

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.49 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1439.97
MW Contribution:9.59
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.746
3144293JTRSVLE
50/50
0.629
970535AG2-341 GEN
50/50
2.158
3146776BUCKING
Solar/Wind Harmer
-0.177
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.372
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.88
963191AG1-168 GEN
Solar/Wind Harmer
2.328
971741AH1-377 GEN
Solar/Wind Harmer
28.01
316034AC1-036 C
Solar/Wind Harmer
0.38
970323AG2-213 GEN
Solar/Wind Harmer
10.214
971775AH1-396 GEN
Solar/Wind Harmer
1.455
3151921BEARGRDN G2
50/50
4.601
3144293JTRSVLE
50/50
0.746
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
316313AB2-026
Solar/Wind Harmer
0.868
316258AE1-075 C
Solar/Wind Harmer
0.782
316405AF2-144 C
Solar/Wind Harmer
0.825
3143336POWHATN
Solar/Wind Harmer
3.247
942461AE2-259 GEN
Solar/Wind Harmer
4.59
970909AG2-566 GEN
Solar/Wind Harmer
2.539
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.45
963181AG1-167 GEN
Solar/Wind Harmer
2.328
959311AF2-222 GEN
Solar/Wind Harmer
22.003
970257AG2-171 GEN
Solar/Wind Harmer
7.661
315785AD2-033 C
Solar/Wind Harmer
4.427
964241AG1-285 GEN
Solar/Wind Harmer
13.397
316131AB2-060 GEN
Solar/Wind Harmer
1.694
970221AG2-151 GEN
Solar/Wind Harmer
9.59
316478AD1-087 GEN
Solar/Wind Harmer
1.073
316486AD2-202 GEN
Solar/Wind Harmer
0.314
3147043LAWRENC
Solar/Wind Harmer
-0.007
3150861SPRUNCD
Adder
0.417
316248AF1-058 C
Solar/Wind Harmer
0.306
960061AF2-297 GEN
Solar/Wind Harmer
5.079
966621AG1-532 GEN
Solar/Wind Harmer
0.189
313506AB2-031 GEN
Solar/Wind Harmer
0.727
971683AH1-343 GEN
Solar/Wind Harmer
3.823
970917AG2-570 GEN
Solar/Wind Harmer
20.936
316365GEN2_N
Solar/Wind Harmer
0.554
3143096IRON208
Adder
0.298
3143096IRON208
Adder
0.292
3156081AA2-088 GEN
Solar/Wind Harmer
2.589
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
315839AE2-212 C
Solar/Wind Harmer
0.237
957521AF2-046 GEN
Solar/Wind Harmer
6.176
961681AG1-008 GEN
Solar/Wind Harmer
6.176
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
965281AG1-393 GEN
Solar/Wind Harmer
0.97
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.214
315813AE1-149 C
Solar/Wind Harmer
4.801
316463AE2-346 GEN
Solar/Wind Harmer
0.124
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.959
316317KELFORD C
Solar/Wind Harmer
0.361
3145823KELFORD
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
0.714
316083AB2-161 GEN
Solar/Wind Harmer
1.228
970661AG2-428 GEN
Solar/Wind Harmer
1.415
316327AA2-057 GEN
Solar/Wind Harmer
0.756
3145273HOLLAND
Solar/Wind Harmer
-0.006
970133AG2-095 GEN
Solar/Wind Harmer
0.837
3156021HOLLOMANSOL
Solar/Wind Harmer
0.996
315724AD1-057 GEN
Solar/Wind Harmer
0.424
970129AG2-093 GEN
Solar/Wind Harmer
4.142
3146206CASHIE
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.153
3146233WITAKRS
Solar/Wind Harmer
-0.005
315778AD1-151 GEN
Solar/Wind Harmer
6.319
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.378
971157AH1-035 GEN
Solar/Wind Harmer
0.905
315614AA2-178 GEN
Solar/Wind Harmer
0.779
3146376EDENTON
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.298
961611AG1-000B GEN
Solar/Wind Harmer
1.508
316320Y1-086
Solar/Wind Harmer
0.418
3145963POPLR C
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151221GRAVEL6
Adder
4.597
3151171GRAVELC
Adder
0.884
3144873MCLAUGH
Solar/Wind Harmer
0
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.866
3144216WINCHST
Adder
0.221
3150921YORKTN3
Adder
1.456
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3148013FISHERV
Solar/Wind Helper
0.171
316499AE2-029_GEN
Solar/Wind Helper
0.503
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.534
3147666LOUISA
Solar/Wind Helper
0.265
944581AF1-123 GEN
Solar/Wind Harmer
1.127
972205AH1-687 GEN
50/50
22.442
316303AF2-085
50/50
2.627
971845AH1-439 GEN
Solar/Wind Harmer
23.203
970285AG2-188 GEN
Solar/Wind Harmer
36.921
315657AE1-056 GEN
Solar/Wind Harmer
9.87
946301AF1-294 GEN
Solar/Wind Harmer
6.363
961791AG1-021 GEN
Solar/Wind Harmer
3.104
970683AG2-441 GEN
Solar/Wind Harmer
17.731
970681AG2-440 GEN
Solar/Wind Harmer
14.185
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.983
316239AB2-077_GEN
Solar/Wind Harmer
0.453
316238AB2-078_GEN
Solar/Wind Harmer
0.453
316233AE1-074 FULL
Solar/Wind Harmer
0.37
971281AH1-106 GEN
Solar/Wind Harmer
2.234
971283AH1-107 GEN
Solar/Wind Harmer
2.234
270494AE1-108_GEN
Solar/Wind Harmer
3.125
316118AC1-105 GEN
Solar/Wind Harmer
0.772
970831AG2-522 GEN
Solar/Wind Harmer
5.366
971285AH1-108 GEN
Adder
0.682
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
946281AF1-292 GEN
Solar/Wind Harmer
0.209
971967AH1-528 GEN
Solar/Wind Harmer
17.53
316087AB2-174 GEN
Solar/Wind Harmer
1.303
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970673AG2-436 GEN
Solar/Wind Harmer
17.985
970673AG2-436 GEN
Solar/Wind Harmer
9.106
941031AE2-094 GEN
Solar/Wind Harmer
15.864
944011AF1-069 GEN
Solar/Wind Harmer
4.971
315607AA1-063A GEN
Solar/Wind Harmer
0.854
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.213
970581AG2-369 GEN
Solar/Wind Harmer
4.483
970865AG2-541 GEN
Solar/Wind Harmer
3.349
315814AE2-033 C
Solar/Wind Harmer
7.587
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.711
3143316POE
Solar/Wind Harmer
-0.031
315652AC1-086 GEN
Solar/Wind Harmer
8.889
316318V4-068
Solar/Wind Harmer
0.196
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315833AF1-017_GEN
Solar/Wind Harmer
1.402
316349AD2-085 GEN
Solar/Wind Harmer
0.657
971447AH1-217 GEN
Solar/Wind Harmer
2.63
316311AC2-079 GEN
Solar/Wind Harmer
3.722
316132AB2-190 GEN1
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.197
316319Z2-044 C
Solar/Wind Harmer
0.403
315835AF2-110_GEN
Solar/Wind Harmer
0.908
316369SG1_INVT
Solar/Wind Harmer
1.296
315732AD1-074 GEN1
Solar/Wind Harmer
1.466
315733AD1-074 GEN2
Solar/Wind Harmer
1.466
315735AD1-075 GEN1
Solar/Wind Harmer
0.733
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
0.585
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.775
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316305AF2-043 C
Solar/Wind Harmer
0.216
316321Z2-027
Solar/Wind Harmer
0.193
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
313526AB2-022
Solar/Wind Harmer
0.193
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
972265AH1-717 GEN
Adder
4.91
3151201GRAVEL4
Adder
4.602
3151191GRAVEL3
Adder
4.544
3151211GRAVEL5
Adder
4.544
3152611GOSPORTB
Adder
0.805
3152621GOSPORTC
Adder
0.683
3152601GOSPORTA
Adder
0.63
971445AH1-216 GEN
Solar/Wind Harmer
4.395
3151081ELIZAR1
Adder
5.792
3151091ELIZAR2
Adder
5.691
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.103
3148013FISHERV
Solar/Wind Helper
0.098
3148463FAIRFLD
Solar/Wind Helper
0.118
3151931BEARGRDN S1
50/50
5.938
3151911BEARGRDN G1
50/50
4.601
3144293JTRSVLE
50/50
0.746
970119AG2-088 GEN
50/50
19.705
972003AH1-546 GEN
Solar/Wind Harmer
26.72
970937AG2-583 GEN
Solar/Wind Harmer
33.599
316322AB2-045
Solar/Wind Harmer
1.495
3146776BUCKING
Solar/Wind Harmer
-0.018
316336AC2-165 C
Solar/Wind Harmer
6.302
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.82
963171AG1-166 GEN
Solar/Wind Harmer
3.104
971563AH1-280 GEN
Solar/Wind Harmer
3.104
970685AG2-442 GEN
Solar/Wind Harmer
19.859
3143226MDLTHAN
Solar/Wind Harmer
-0.017
962491AG1-098 GEN
Solar/Wind Harmer
10.562
971377AH1-170 GEN
Solar/Wind Harmer
1.918
3147623JAMES R
Solar/Wind Harmer
0.237
315693AD1-088 GEN
Solar/Wind Harmer
7.599
316237AB2-079_GEN
Solar/Wind Harmer
0.453
3143526WINTERP
Solar/Wind Harmer
-0.071
957481AF2-042 GEN
Solar/Wind Harmer
38.757
970401AG2-262 GEN
Solar/Wind Harmer
0.805
315687AD1-152 GEN
Solar/Wind Harmer
1.355
3147043LAWRENC
Adder
0.898
971065AG2-659 GEN
Solar/Wind Harmer
5.572
316129AC1-054 GEN
Solar/Wind Harmer
0.96
971795AH1-408 GEN
Solar/Wind Harmer
7.936
3150851SPRUNCC
Adder
0.417
316003AC1-222 GEN
Solar/Wind Harmer
0.924
960081AF2-299 GEN
Solar/Wind Harmer
1.049
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
3142543TWELFTH
Solar/Wind Harmer
-0.001
970919AG2-571 GEN
Solar/Wind Harmer
2.65
970087AG2-069 GEN
Solar/Wind Harmer
7.82
316023GEN1_S
Solar/Wind Harmer
0.554
940641AE2-051 GEN
Solar/Wind Harmer
7.517
3143096IRON208
Adder
0.298
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.653
962571AG1-106 GEN
Solar/Wind Harmer
1.136
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
939411AE1-173 GEN
Solar/Wind Harmer
38.95
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.803
316212AC1-099_GEN
Solar/Wind Harmer
0.674
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.029
316381AD1-082 GEN
Solar/Wind Harmer
0.694
970661AG2-428 GEN
Solar/Wind Harmer
7.982
315722AD1-056 GEN
Solar/Wind Harmer
0.771
970129AG2-093 GEN
Solar/Wind Harmer
1.678
316458AB2-190 GEN2
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.827
3146233WITAKRS
Solar/Wind Harmer
-0.029
971069AG2-661 GEN
Solar/Wind Harmer
1.154
316093AE2-104_GEN
Solar/Wind Harmer
2.113
944631AF1-128 GEN
Adder
30.658
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.772
971647AH1-324 GEN
Solar/Wind Harmer
3.605
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.775
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.535
316246AF1-032 C
Solar/Wind Harmer
0.145
3145963POPLR C
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
316174AB2-169 GEN
Solar/Wind Harmer
1.097
3151171GRAVELC
Adder
0.673
316375AC2-012 GEN
Solar/Wind Harmer
2.457
3145336SMITFLD
Solar/Wind Harmer
-0.028
3150981CHESPKA
Adder
0.789
944591AF1-124 GEN
Solar/Wind Harmer
32.38
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.798
3147666LOUISA
Solar/Wind Helper
0.46
971223AH1-071 GEN
Solar/Wind Harmer
2.076
313527AB2-043 GEN
Solar/Wind Harmer
2.493
971489AH1-241 GEN
Solar/Wind Harmer
9.104
3143526WINTERP
Solar/Wind Harmer
-0.071
962561AG1-105 GEN
Solar/Wind Harmer
7.195
939181AE1-148 GEN
Solar/Wind Harmer
7.148
970099AG2-077 GEN
Solar/Wind Harmer
15.503
964791AG1-342 GEN
Solar/Wind Harmer
2.634
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970933AG2-581 GEN
Solar/Wind Harmer
9.649
316181AB2-040 GEN
Solar/Wind Harmer
1.262
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.983
3145593CAROLNA
Solar/Wind Harmer
0.073
972187AH1-678 GEN
Adder
2.2
972185AH1-677 GEN
Adder
4.302
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
316274AC1-208 GEN
Solar/Wind Harmer
0.849
316240AF1-291 C
Solar/Wind Harmer
0.235
944641AF1-129 GEN
Adder
33.028
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.793
970657AG2-426 GEN
Solar/Wind Harmer
2.358
970657AG2-426 GEN
Solar/Wind Harmer
0.493
316065AD1-022 GEN
Solar/Wind Harmer
3.643
316033AB2-134 GEN
Solar/Wind Harmer
2.34
315697AD1-025 GEN
Solar/Wind Harmer
1.468
3142366NRTHEST
Adder
0.21
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.298
316433W1029_GEN2
Solar/Wind Harmer
1.298
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316222AC1-221 GEN
Solar/Wind Harmer
0.722
3130086AYDLETT
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.75
3142956BIRDNECK
Solar/Wind Harmer
0.381
316316AC1-027 C
Solar/Wind Harmer
0.218
316236AE1-162_GEN
Solar/Wind Harmer
0.214
316036AC1-147 C
Solar/Wind Harmer
0.192
3150991CHESPKB
Adder
0.662
3150991CHESPKB
Adder
0.646
3150691DARBY 3
Adder
4.502
3150701DARBY 4
Adder
4.491
3150681DARBY 2
Adder
4.486
3150671DARBY 1
Adder
4.481
966001AG1-469 GEN
Solar/Wind Helper
0.186
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.012
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.013
LAGNLTFEXP_LAGN->PJM
CLTF
1.555
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.345
MECLTFEXP_MEC->PJM
CLTF
0.252
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.774
TVALTFEXP_TVA->PJM
CLTF
0.758
SIGELTFEXP_SIGE->PJM
CLTF
0.005
NYPJM->LTFIMP_NY
CLTF
0.536
LGEELTFEXP_LGEE->PJM
CLTF
0.012
CPLELTFEXP_CPLE->PJM
CLTF
3.992
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.116

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.49 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1439.97
MW Contribution:9.59
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.601
3144293JTRSVLE
50/50
0.746
972205AH1-687 GEN
50/50
22.442
316303AF2-085
50/50
2.627
971845AH1-439 GEN
Solar/Wind Harmer
23.203
970285AG2-188 GEN
Solar/Wind Harmer
36.921
315657AE1-056 GEN
Solar/Wind Harmer
9.87
946301AF1-294 GEN
Solar/Wind Harmer
6.363
961791AG1-021 GEN
Solar/Wind Harmer
3.104
970683AG2-441 GEN
Solar/Wind Harmer
17.731
970681AG2-440 GEN
Solar/Wind Harmer
14.185
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.983
316239AB2-077_GEN
Solar/Wind Harmer
0.453
316238AB2-078_GEN
Solar/Wind Harmer
0.453
316233AE1-074 FULL
Solar/Wind Harmer
0.37
971281AH1-106 GEN
Solar/Wind Harmer
2.234
971283AH1-107 GEN
Solar/Wind Harmer
2.234
270494AE1-108_GEN
Solar/Wind Harmer
3.125
316118AC1-105 GEN
Solar/Wind Harmer
0.772
970831AG2-522 GEN
Solar/Wind Harmer
5.366
971285AH1-108 GEN
Adder
0.682
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
946281AF1-292 GEN
Solar/Wind Harmer
0.209
971967AH1-528 GEN
Solar/Wind Harmer
17.53
316087AB2-174 GEN
Solar/Wind Harmer
1.303
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970673AG2-436 GEN
Solar/Wind Harmer
17.985
970673AG2-436 GEN
Solar/Wind Harmer
9.106
941031AE2-094 GEN
Solar/Wind Harmer
15.864
944011AF1-069 GEN
Solar/Wind Harmer
4.971
315607AA1-063A GEN
Solar/Wind Harmer
0.854
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.213
970581AG2-369 GEN
Solar/Wind Harmer
4.483
970865AG2-541 GEN
Solar/Wind Harmer
3.349
315814AE2-033 C
Solar/Wind Harmer
7.587
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.711
3143316POE
Solar/Wind Harmer
-0.031
315652AC1-086 GEN
Solar/Wind Harmer
8.889
316318V4-068
Solar/Wind Harmer
0.196
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315833AF1-017_GEN
Solar/Wind Harmer
1.402
316349AD2-085 GEN
Solar/Wind Harmer
0.657
971447AH1-217 GEN
Solar/Wind Harmer
2.63
316311AC2-079 GEN
Solar/Wind Harmer
3.722
316132AB2-190 GEN1
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.197
316319Z2-044 C
Solar/Wind Harmer
0.403
315835AF2-110_GEN
Solar/Wind Harmer
0.908
316369SG1_INVT
Solar/Wind Harmer
1.296
315732AD1-074 GEN1
Solar/Wind Harmer
1.466
315733AD1-074 GEN2
Solar/Wind Harmer
1.466
315735AD1-075 GEN1
Solar/Wind Harmer
0.733
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
0.585
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.775
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316305AF2-043 C
Solar/Wind Harmer
0.216
316321Z2-027
Solar/Wind Harmer
0.193
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
313526AB2-022
Solar/Wind Harmer
0.193
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
972265AH1-717 GEN
Adder
4.91
3151201GRAVEL4
Adder
4.602
3151191GRAVEL3
Adder
4.544
3151211GRAVEL5
Adder
4.544
3152611GOSPORTB
Adder
0.805
3152621GOSPORTC
Adder
0.683
3152601GOSPORTA
Adder
0.63
971445AH1-216 GEN
Solar/Wind Harmer
4.395
3151081ELIZAR1
Adder
5.792
3151091ELIZAR2
Adder
5.691
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.103
3148013FISHERV
Solar/Wind Helper
0.098
3148463FAIRFLD
Solar/Wind Helper
0.118
3151931BEARGRDN S1
50/50
5.938
3151911BEARGRDN G1
50/50
4.601
3144293JTRSVLE
50/50
0.746
970119AG2-088 GEN
50/50
19.705
972003AH1-546 GEN
Solar/Wind Harmer
26.72
970937AG2-583 GEN
Solar/Wind Harmer
33.599
316322AB2-045
Solar/Wind Harmer
1.495
3146776BUCKING
Solar/Wind Harmer
-0.018
316336AC2-165 C
Solar/Wind Harmer
6.302
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.82
963171AG1-166 GEN
Solar/Wind Harmer
3.104
971563AH1-280 GEN
Solar/Wind Harmer
3.104
970685AG2-442 GEN
Solar/Wind Harmer
19.859
3143226MDLTHAN
Solar/Wind Harmer
-0.017
962491AG1-098 GEN
Solar/Wind Harmer
10.562
971377AH1-170 GEN
Solar/Wind Harmer
1.918
3147623JAMES R
Solar/Wind Harmer
0.237
315693AD1-088 GEN
Solar/Wind Harmer
7.599
316237AB2-079_GEN
Solar/Wind Harmer
0.453
3143526WINTERP
Solar/Wind Harmer
-0.071
957481AF2-042 GEN
Solar/Wind Harmer
38.757
970401AG2-262 GEN
Solar/Wind Harmer
0.805
315687AD1-152 GEN
Solar/Wind Harmer
1.355
3147043LAWRENC
Adder
0.898
971065AG2-659 GEN
Solar/Wind Harmer
5.572
316129AC1-054 GEN
Solar/Wind Harmer
0.96
971795AH1-408 GEN
Solar/Wind Harmer
7.936
3150851SPRUNCC
Adder
0.417
316003AC1-222 GEN
Solar/Wind Harmer
0.924
960081AF2-299 GEN
Solar/Wind Harmer
1.049
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
3142543TWELFTH
Solar/Wind Harmer
-0.001
970919AG2-571 GEN
Solar/Wind Harmer
2.65
970087AG2-069 GEN
Solar/Wind Harmer
7.82
316023GEN1_S
Solar/Wind Harmer
0.554
940641AE2-051 GEN
Solar/Wind Harmer
7.517
3143096IRON208
Adder
0.298
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.653
962571AG1-106 GEN
Solar/Wind Harmer
1.136
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
939411AE1-173 GEN
Solar/Wind Harmer
38.95
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.803
316212AC1-099_GEN
Solar/Wind Harmer
0.674
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.029
316381AD1-082 GEN
Solar/Wind Harmer
0.694
970661AG2-428 GEN
Solar/Wind Harmer
7.982
315722AD1-056 GEN
Solar/Wind Harmer
0.771
970129AG2-093 GEN
Solar/Wind Harmer
1.678
316458AB2-190 GEN2
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.827
3146233WITAKRS
Solar/Wind Harmer
-0.029
971069AG2-661 GEN
Solar/Wind Harmer
1.154
316093AE2-104_GEN
Solar/Wind Harmer
2.113
944631AF1-128 GEN
Adder
30.658
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.772
971647AH1-324 GEN
Solar/Wind Harmer
3.605
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.775
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.535
316246AF1-032 C
Solar/Wind Harmer
0.145
3145963POPLR C
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
316174AB2-169 GEN
Solar/Wind Harmer
1.097
3151171GRAVELC
Adder
0.673
316375AC2-012 GEN
Solar/Wind Harmer
2.457
3145336SMITFLD
Solar/Wind Harmer
-0.028
3150981CHESPKA
Adder
0.789
944591AF1-124 GEN
Solar/Wind Harmer
32.38
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.798
3147666LOUISA
Solar/Wind Helper
0.46
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
316313AB2-026
Solar/Wind Harmer
0.868
316258AE1-075 C
Solar/Wind Harmer
0.782
316405AF2-144 C
Solar/Wind Harmer
0.825
3143336POWHATN
Solar/Wind Harmer
3.247
942461AE2-259 GEN
Solar/Wind Harmer
4.59
970909AG2-566 GEN
Solar/Wind Harmer
2.539
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.45
963181AG1-167 GEN
Solar/Wind Harmer
2.328
959311AF2-222 GEN
Solar/Wind Harmer
22.003
970257AG2-171 GEN
Solar/Wind Harmer
7.661
315785AD2-033 C
Solar/Wind Harmer
4.427
964241AG1-285 GEN
Solar/Wind Harmer
13.397
316131AB2-060 GEN
Solar/Wind Harmer
1.694
970221AG2-151 GEN
Solar/Wind Harmer
9.59
316478AD1-087 GEN
Solar/Wind Harmer
1.073
316486AD2-202 GEN
Solar/Wind Harmer
0.314
3147043LAWRENC
Solar/Wind Harmer
-0.007
3150861SPRUNCD
Adder
0.417
316248AF1-058 C
Solar/Wind Harmer
0.306
960061AF2-297 GEN
Solar/Wind Harmer
5.079
966621AG1-532 GEN
Solar/Wind Harmer
0.189
313506AB2-031 GEN
Solar/Wind Harmer
0.727
971683AH1-343 GEN
Solar/Wind Harmer
3.823
970917AG2-570 GEN
Solar/Wind Harmer
20.936
316365GEN2_N
Solar/Wind Harmer
0.554
3143096IRON208
Adder
0.298
3143096IRON208
Adder
0.292
3156081AA2-088 GEN
Solar/Wind Harmer
2.589
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
315839AE2-212 C
Solar/Wind Harmer
0.237
957521AF2-046 GEN
Solar/Wind Harmer
6.176
961681AG1-008 GEN
Solar/Wind Harmer
6.176
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
965281AG1-393 GEN
Solar/Wind Harmer
0.97
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.214
315813AE1-149 C
Solar/Wind Harmer
4.801
316463AE2-346 GEN
Solar/Wind Harmer
0.124
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.959
316317KELFORD C
Solar/Wind Harmer
0.361
3145823KELFORD
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
0.714
316083AB2-161 GEN
Solar/Wind Harmer
1.228
970661AG2-428 GEN
Solar/Wind Harmer
1.415
316327AA2-057 GEN
Solar/Wind Harmer
0.756
3145273HOLLAND
Solar/Wind Harmer
-0.006
970133AG2-095 GEN
Solar/Wind Harmer
0.837
3156021HOLLOMANSOL
Solar/Wind Harmer
0.996
315724AD1-057 GEN
Solar/Wind Harmer
0.424
970129AG2-093 GEN
Solar/Wind Harmer
4.142
3146206CASHIE
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.153
3146233WITAKRS
Solar/Wind Harmer
-0.005
315778AD1-151 GEN
Solar/Wind Harmer
6.319
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.378
971157AH1-035 GEN
Solar/Wind Harmer
0.905
315614AA2-178 GEN
Solar/Wind Harmer
0.779
3146376EDENTON
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.298
961611AG1-000B GEN
Solar/Wind Harmer
1.508
316320Y1-086
Solar/Wind Harmer
0.418
3145963POPLR C
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151221GRAVEL6
Adder
4.597
3151171GRAVELC
Adder
0.884
3144873MCLAUGH
Solar/Wind Harmer
0
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.866
3144216WINCHST
Adder
0.221
3150921YORKTN3
Adder
1.456
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3148013FISHERV
Solar/Wind Helper
0.171
316499AE2-029_GEN
Solar/Wind Helper
0.503
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.534
3147666LOUISA
Solar/Wind Helper
0.265
944581AF1-123 GEN
Solar/Wind Harmer
1.127
3144293JTRSVLE
50/50
0.746
3144293JTRSVLE
50/50
0.629
970535AG2-341 GEN
50/50
2.158
3146776BUCKING
Solar/Wind Harmer
-0.177
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.372
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.88
963191AG1-168 GEN
Solar/Wind Harmer
2.328
971741AH1-377 GEN
Solar/Wind Harmer
28.01
316034AC1-036 C
Solar/Wind Harmer
0.38
970323AG2-213 GEN
Solar/Wind Harmer
10.214
971775AH1-396 GEN
Solar/Wind Harmer
1.455
971223AH1-071 GEN
Solar/Wind Harmer
2.076
313527AB2-043 GEN
Solar/Wind Harmer
2.493
971489AH1-241 GEN
Solar/Wind Harmer
9.104
3143526WINTERP
Solar/Wind Harmer
-0.071
962561AG1-105 GEN
Solar/Wind Harmer
7.195
939181AE1-148 GEN
Solar/Wind Harmer
7.148
970099AG2-077 GEN
Solar/Wind Harmer
15.503
964791AG1-342 GEN
Solar/Wind Harmer
2.634
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970933AG2-581 GEN
Solar/Wind Harmer
9.649
316181AB2-040 GEN
Solar/Wind Harmer
1.262
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.983
3145593CAROLNA
Solar/Wind Harmer
0.073
972187AH1-678 GEN
Adder
2.2
972185AH1-677 GEN
Adder
4.302
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
316274AC1-208 GEN
Solar/Wind Harmer
0.849
316240AF1-291 C
Solar/Wind Harmer
0.235
944641AF1-129 GEN
Adder
33.028
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.793
970657AG2-426 GEN
Solar/Wind Harmer
2.358
970657AG2-426 GEN
Solar/Wind Harmer
0.493
316065AD1-022 GEN
Solar/Wind Harmer
3.643
316033AB2-134 GEN
Solar/Wind Harmer
2.34
315697AD1-025 GEN
Solar/Wind Harmer
1.468
3142366NRTHEST
Adder
0.21
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.298
316433W1029_GEN2
Solar/Wind Harmer
1.298
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316222AC1-221 GEN
Solar/Wind Harmer
0.722
3130086AYDLETT
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.75
3142956BIRDNECK
Solar/Wind Harmer
0.381
316316AC1-027 C
Solar/Wind Harmer
0.218
316236AE1-162_GEN
Solar/Wind Harmer
0.214
316036AC1-147 C
Solar/Wind Harmer
0.192
3150991CHESPKB
Adder
0.662
3150991CHESPKB
Adder
0.646
3150691DARBY 3
Adder
4.502
3150701DARBY 4
Adder
4.491
3150681DARBY 2
Adder
4.486
3150671DARBY 1
Adder
4.481
966001AG1-469 GEN
Solar/Wind Helper
0.186
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.012
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.013
LAGNLTFEXP_LAGN->PJM
CLTF
1.555
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.345
MECLTFEXP_MEC->PJM
CLTF
0.252
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.774
TVALTFEXP_TVA->PJM
CLTF
0.758
SIGELTFEXP_SIGE->PJM
CLTF
0.005
NYPJM->LTFIMP_NY
CLTF
0.536
LGEELTFEXP_LGEE->PJM
CLTF
0.012
CPLELTFEXP_CPLE->PJM
CLTF
3.992
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.116

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:158.61 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1076.48
MW Contribution:14.37
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
5.993
3144293JTRSVLE
50/50
0.881
3151591KERR 2
50/50
0.215
970413AG2-270 GEN
50/50
9.663
3151261ROARAP2
50/50
0.069
3146776BUCKING
Solar/Wind Harmer
0.182
3146926FARMVIL
Solar/Wind Harmer
0.234
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
970909AG2-566 GEN
Solar/Wind Harmer
3.007
3147133PAMPLIN
Solar/Wind Harmer
0.876
971193AH1-056 GEN
Solar/Wind Harmer
16.999
970221AG2-151 GEN
Solar/Wind Harmer
14.368
963181AG1-167 GEN
Solar/Wind Harmer
1.043
959311AF2-222 GEN
Solar/Wind Harmer
19.082
970257AG2-171 GEN
Solar/Wind Harmer
6.613
315785AD2-033 C
Solar/Wind Harmer
1.59
964241AG1-285 GEN
Solar/Wind Harmer
11.084
316131AB2-060 GEN
Solar/Wind Harmer
0.467
316478AD1-087 GEN
Solar/Wind Harmer
0.361
316486AD2-202 GEN
Solar/Wind Harmer
0.106
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.73
3147043LAWRENC
Solar/Wind Harmer
0.052
958131AF2-107 GEN
Solar/Wind Harmer
2.449
971683AH1-343 GEN
Solar/Wind Harmer
2.857
313506AB2-031 GEN
Solar/Wind Harmer
0.184
3144293JTRSVLE
50/50
0.881
3144293JTRSVLE
50/50
0.742
970535AG2-341 GEN
50/50
2.183
3152661PLYWOOD A
50/50
0.212
3146776BUCKING
Solar/Wind Harmer
2.017
3146776BUCKING
Solar/Wind Harmer
0.163
970301AG2-198 GEN
Solar/Wind Harmer
12.027
3147133PAMPLIN
Solar/Wind Harmer
0.279
3147133PAMPLIN
Solar/Wind Harmer
0.223
971489AH1-241 GEN
Solar/Wind Harmer
14.368
958211AF2-115 GEN
Solar/Wind Harmer
3.13
963191AG1-168 GEN
Solar/Wind Harmer
1.043
971741AH1-377 GEN
Solar/Wind Harmer
24.65
316034AC1-036 C
Solar/Wind Harmer
0.015
970323AG2-213 GEN
Solar/Wind Harmer
8.817
971775AH1-396 GEN
Solar/Wind Harmer
0.331
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
5.577
315821AE2-092 GEN
Solar/Wind Harmer
0.007
939181AE1-148 GEN
Solar/Wind Harmer
5.338
964791AG1-342 GEN
Solar/Wind Harmer
2.134
3146843MT LREL
Solar/Wind Harmer
0.111
3146843MT LREL
Solar/Wind Harmer
0.111
970099AG2-077 GEN
Solar/Wind Harmer
10.736
970933AG2-581 GEN
Solar/Wind Harmer
5.58
316181AB2-040 GEN
Solar/Wind Harmer
0.086
942751AE2-291 GEN
Solar/Wind Harmer
3.114
3145593CAROLNA
Solar/Wind Harmer
0.057
3145593CAROLNA
Solar/Wind Harmer
0.057
966811AG1-552 GEN
Solar/Wind Harmer
0.619
3145593CAROLNA
Solar/Wind Harmer
0.071
966001AG1-469 GEN
Solar/Wind Helper
0.14
3151931BEARGRDN S1
50/50
7.734
3151911BEARGRDN G1
50/50
5.993
3144293JTRSVLE
50/50
0.881
3151601KERR 3
50/50
0.215
3151581KERR 1
50/50
0.077
3151531CLOVER1
50/50
2.214
3147043LAWRENC
50/50
0.833
3151261ROARAP2
50/50
0.071
970937AG2-583 GEN
Solar/Wind Harmer
39.544
316336AC2-165 C
Solar/Wind Harmer
0.025
972003AH1-546 GEN
Solar/Wind Harmer
26.303
316322AB2-045
Solar/Wind Harmer
0.004
3146776BUCKING
Solar/Wind Harmer
0.202
3146926FARMVIL
Solar/Wind Harmer
0.234
971377AH1-170 GEN
Solar/Wind Harmer
2.874
3147623JAMES R
Solar/Wind Harmer
0.624
963171AG1-166 GEN
Solar/Wind Harmer
1.391
971563AH1-280 GEN
Solar/Wind Harmer
2.782
970685AG2-442 GEN
Solar/Wind Harmer
17.514
962491AG1-098 GEN
Solar/Wind Harmer
8.209
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
6.543
970401AG2-262 GEN
Solar/Wind Harmer
0.652
957481AF2-042 GEN
Solar/Wind Harmer
26.84
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.856
316129AC1-054 GEN
Solar/Wind Harmer
0.33
316003AC1-222 GEN
Solar/Wind Harmer
0.002
971795AH1-408 GEN
Solar/Wind Harmer
5.259
960081AF2-299 GEN
Solar/Wind Harmer
0.593
972205AH1-687 GEN
50/50
29.229
3151611KERR 4
50/50
0.215
3151621KERR 5
50/50
0.215
3151631KERR 6
50/50
0.215
3151641KERR 7
50/50
0.215
3151541CLOVER2
50/50
2.204
3151281ROARAP4
50/50
0.069
3151281ROARAP4
50/50
0.065
971845AH1-439 GEN
Solar/Wind Harmer
22.434
970285AG2-188 GEN
Solar/Wind Harmer
37.679
315657AE1-056 GEN
Solar/Wind Harmer
9.629
946301AF1-294 GEN
Solar/Wind Harmer
5.147
961791AG1-021 GEN
Solar/Wind Harmer
2.504
970683AG2-441 GEN
Solar/Wind Harmer
15.638
970681AG2-440 GEN
Solar/Wind Harmer
12.51
270494AE1-108_GEN
Solar/Wind Harmer
2.538
3144303KENBRDG
Solar/Wind Harmer
0.165
971443AH1-215 GEN
Solar/Wind Harmer
3.431
971447AH1-217 GEN
Solar/Wind Harmer
5.812
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.256
3147173SINAI
Solar/Wind Harmer
0.087
3147243WELCO
Solar/Wind Harmer
0.055
970831AG2-522 GEN
Solar/Wind Harmer
3.614
970865AG2-541 GEN
Solar/Wind Harmer
2.528
316123AC1-075 GEN
Solar/Wind Harmer
0.087
970165AG2-112 GEN
Solar/Wind Harmer
0.513
970163AG2-111 GEN
Solar/Wind Harmer
0.49
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.232
3138266HYDRAULIC
Solar/Wind Helper
0.014
3138266HYDRAULIC
Solar/Wind Helper
0.009
LAGNLTFEXP_LAGN->PJM
CLTF
1.359
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.534
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.133
MECLTFEXP_MEC->PJM
CLTF
0.325
SIGELTFEXP_SIGE->PJM
CLTF
0.008
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.117
TVALTFEXP_TVA->PJM
CLTF
0.671
NYPJM->LTFIMP_NY
CLTF
0.488
LGEELTFEXP_LGEE->PJM
CLTF
0.069
WECLTFEXP_WEC->PJM
CLTF
0.029
CPLELTFEXP_CPLE->PJM
CLTF
3.067
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.792

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 242T2027_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 242T2027_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.82 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1235.22
MW Contribution:18.92
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
29.229
971845AH1-439 GEN
Solar/Wind Harmer
29.538
970285AG2-188 GEN
Solar/Wind Harmer
46.824
315657AE1-056 GEN
Solar/Wind Harmer
11.763
3151921BEARGRDN G2
50/50
5.993
3144293JTRSVLE
50/50
0.881
3146776BUCKING
Solar/Wind Harmer
-0.02
3146926FARMVIL
Solar/Wind Harmer
-0.026
942461AE2-259 GEN
Solar/Wind Harmer
5.592
970909AG2-566 GEN
Solar/Wind Harmer
3.007
3147133PAMPLIN
Solar/Wind Harmer
-0.098
971193AH1-056 GEN
Solar/Wind Harmer
19.605
970221AG2-151 GEN
Solar/Wind Harmer
18.917
963181AG1-167 GEN
Solar/Wind Harmer
2.748
959311AF2-222 GEN
Solar/Wind Harmer
25.175
970257AG2-171 GEN
Solar/Wind Harmer
8.707
315785AD2-033 C
Solar/Wind Harmer
4.981
964241AG1-285 GEN
Solar/Wind Harmer
14.595
316131AB2-060 GEN
Solar/Wind Harmer
1.799
316478AD1-087 GEN
Solar/Wind Harmer
1.005
316486AD2-202 GEN
Solar/Wind Harmer
0.294
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.911
3147043LAWRENC
Solar/Wind Harmer
-0.006
958131AF2-107 GEN
Solar/Wind Harmer
3.26
971683AH1-343 GEN
Solar/Wind Harmer
3.762
966621AG1-532 GEN
Solar/Wind Harmer
0.141
313506AB2-031 GEN
Solar/Wind Harmer
0.538
3151931BEARGRDN S1
50/50
7.734
3151911BEARGRDN G1
50/50
5.993
3144293JTRSVLE
50/50
0.881
970937AG2-583 GEN
Solar/Wind Harmer
52.066
316336AC2-165 C
Solar/Wind Harmer
12.588
972003AH1-546 GEN
Solar/Wind Harmer
34.691
316322AB2-045
Solar/Wind Harmer
1.907
3146776BUCKING
Solar/Wind Harmer
-0.022
3146926FARMVIL
Solar/Wind Harmer
-0.026
971377AH1-170 GEN
Solar/Wind Harmer
3.783
3147623JAMES R
Solar/Wind Harmer
0.468
963171AG1-166 GEN
Solar/Wind Harmer
3.664
971563AH1-280 GEN
Solar/Wind Harmer
3.664
970685AG2-442 GEN
Solar/Wind Harmer
23.061
962491AG1-098 GEN
Solar/Wind Harmer
10.808
316237AB2-079_GEN
Solar/Wind Harmer
0.475
315693AD1-088 GEN
Solar/Wind Harmer
7.658
970401AG2-262 GEN
Solar/Wind Harmer
0.815
957481AF2-042 GEN
Solar/Wind Harmer
35.339
315687AD1-152 GEN
Solar/Wind Harmer
1.264
971065AG2-659 GEN
Solar/Wind Harmer
5.078
316129AC1-054 GEN
Solar/Wind Harmer
0.863
3147043LAWRENC
Adder
0.785
316003AC1-222 GEN
Solar/Wind Harmer
0.902
971795AH1-408 GEN
Solar/Wind Harmer
6.647
960081AF2-299 GEN
Solar/Wind Harmer
0.78
3144293JTRSVLE
50/50
0.881
3144293JTRSVLE
50/50
0.742
970535AG2-341 GEN
50/50
2.183
3146776BUCKING
Solar/Wind Harmer
-0.226
3146776BUCKING
Solar/Wind Harmer
-0.018
970301AG2-198 GEN
Solar/Wind Harmer
15.836
3147133PAMPLIN
Solar/Wind Harmer
-0.031
3147133PAMPLIN
Solar/Wind Harmer
-0.025
971489AH1-241 GEN
Solar/Wind Harmer
17.959
958211AF2-115 GEN
Solar/Wind Harmer
4.579
963191AG1-168 GEN
Solar/Wind Harmer
2.748
971741AH1-377 GEN
Solar/Wind Harmer
32.456
316034AC1-036 C
Solar/Wind Harmer
0.432
970323AG2-213 GEN
Solar/Wind Harmer
11.609
971775AH1-396 GEN
Solar/Wind Harmer
1.653
313527AB2-043 GEN
Solar/Wind Harmer
2.63
962561AG1-105 GEN
Solar/Wind Harmer
7.343
315821AE2-092 GEN
Solar/Wind Harmer
2.71
939181AE1-148 GEN
Solar/Wind Harmer
7.029
964791AG1-342 GEN
Solar/Wind Harmer
2.668
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.136
970933AG2-581 GEN
Solar/Wind Harmer
7.348
316181AB2-040 GEN
Solar/Wind Harmer
0.933
942751AE2-291 GEN
Solar/Wind Harmer
4.1
3145593CAROLNA
Solar/Wind Harmer
-0.006
3145593CAROLNA
Solar/Wind Harmer
-0.006
966811AG1-552 GEN
Solar/Wind Harmer
0.721
3145593CAROLNA
Solar/Wind Harmer
0.053
966001AG1-469 GEN
Solar/Wind Helper
0.14
946301AF1-294 GEN
Solar/Wind Harmer
7.51
961791AG1-021 GEN
Solar/Wind Harmer
3.664
970683AG2-441 GEN
Solar/Wind Harmer
20.59
970681AG2-440 GEN
Solar/Wind Harmer
16.472
270494AE1-108_GEN
Solar/Wind Harmer
6.187
3144303KENBRDG
Solar/Wind Harmer
-0.019
971443AH1-215 GEN
Solar/Wind Harmer
4.518
971447AH1-217 GEN
Solar/Wind Harmer
7.652
316239AB2-077_GEN
Solar/Wind Harmer
0.475
316238AB2-078_GEN
Solar/Wind Harmer
0.475
316118AC1-105 GEN
Solar/Wind Harmer
0.766
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
970831AG2-522 GEN
Solar/Wind Harmer
4.758
970865AG2-541 GEN
Solar/Wind Harmer
3.329
316123AC1-075 GEN
Solar/Wind Harmer
0.768
970165AG2-112 GEN
Solar/Wind Harmer
0.676
970163AG2-111 GEN
Solar/Wind Harmer
0.645
946281AF1-292 GEN
Solar/Wind Harmer
0.155
316087AB2-174 GEN
Solar/Wind Harmer
0.965
3137643SOCKMAN
Solar/Wind Harmer
-0.026
3138266HYDRAULIC
Solar/Wind Helper
0.014
3138266HYDRAULIC
Solar/Wind Helper
0.009
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.534
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.133
MECLTFEXP_MEC->PJM
CLTF
0.325
LAGNLTFEXP_LAGN->PJM
CLTF
1.359
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.117
TVALTFEXP_TVA->PJM
CLTF
0.671
SIGELTFEXP_SIGE->PJM
CLTF
0.008
CPLELTFEXP_CPLE->PJM
CLTF
3.067
NYPJM->LTFIMP_NY
CLTF
0.488
LGEELTFEXP_LGEE->PJM
CLTF
0.069
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.792
WECLTFEXP_WEC->PJM
CLTF
0.029

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.92 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:773.16
MW Contribution:6.36
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.707
3151911BEARGRDN G1
50/50
4.422
3144293JTRSVLE
50/50
0.69
970119AG2-088 GEN
50/50
12.707
3151531CLOVER1
50/50
2.017
3151601KERR 3
50/50
0.192
3151581KERR 1
50/50
0.069
3147043LAWRENC
50/50
0.8
3151261ROARAP2
50/50
0.077
3150851SPRUNCC
50/50
0.297
3151051BRUNSWICKS1
50/50
1.63
3151021BRUNSWICKG1
50/50
0.785
971451AH1-221 GEN
50/50
2.385
315243AE2-183_GT3
50/50
0.972
972003AH1-546 GEN
Solar/Wind Harmer
19.447
970937AG2-583 GEN
Solar/Wind Harmer
23.874
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.151
3146926FARMVIL
Solar/Wind Harmer
0.178
316336AC2-165 C
Solar/Wind Harmer
0.011
3143336POWHATN
Solar/Wind Harmer
4.396
963171AG1-166 GEN
Solar/Wind Harmer
1.09
971563AH1-280 GEN
Solar/Wind Harmer
2.18
970685AG2-442 GEN
Solar/Wind Harmer
13.857
962491AG1-098 GEN
Solar/Wind Harmer
7.06
971377AH1-170 GEN
Solar/Wind Harmer
1.272
3147623JAMES R
Solar/Wind Harmer
0.276
315693AD1-088 GEN
Solar/Wind Harmer
5.685
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Harmer
0.095
970401AG2-262 GEN
Solar/Wind Harmer
0.559
957481AF2-042 GEN
Solar/Wind Harmer
24.966
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.579
316129AC1-054 GEN
Solar/Wind Harmer
0.309
3143526WINTERP
Solar/Wind Harmer
0.415
971795AH1-408 GEN
Solar/Wind Harmer
5.206
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.641
3145783HORNRTN
Solar/Wind Harmer
0.061
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
2.047
970087AG2-069 GEN
Solar/Wind Harmer
4.587
316023GEN1_S
Solar/Wind Harmer
0.127
3147983MERCK5
Solar/Wind Helper
0.057
972205AH1-687 GEN
50/50
21.569
316303AF2-085
50/50
1.694
3151541CLOVER2
50/50
2.007
3151611KERR 4
50/50
0.192
3151621KERR 5
50/50
0.192
3151631KERR 6
50/50
0.192
3151641KERR 7
50/50
0.192
3151281ROARAP4
50/50
0.075
3151281ROARAP4
50/50
0.07
971285AH1-108 GEN
50/50
0.486
963041AG1-153 GEN
50/50
1.59
315244AE2-183_ST
50/50
1.681
971845AH1-439 GEN
Solar/Wind Harmer
16.786
970285AG2-188 GEN
Solar/Wind Harmer
28.258
315657AE1-056 GEN
Solar/Wind Harmer
7.498
946301AF1-294 GEN
Solar/Wind Harmer
4.032
961791AG1-021 GEN
Solar/Wind Harmer
1.962
970683AG2-441 GEN
Solar/Wind Harmer
12.373
970681AG2-440 GEN
Solar/Wind Harmer
9.898
3144303KENBRDG
Solar/Wind Harmer
0.132
971443AH1-215 GEN
Solar/Wind Harmer
2.755
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Harmer
1.107
316118AC1-105 GEN
Solar/Wind Harmer
0.222
970831AG2-522 GEN
Solar/Wind Harmer
3.422
316233AE1-074 FULL
Solar/Wind Harmer
0.064
971281AH1-106 GEN
Solar/Wind Harmer
1.107
971283AH1-107 GEN
Solar/Wind Harmer
1.107
3147173SINAI
Solar/Wind Harmer
0.077
3147243WELCO
Solar/Wind Harmer
0.048
316087AB2-174 GEN
Solar/Wind Harmer
0.002
971967AH1-528 GEN
Solar/Wind Harmer
10.427
3137643SOCKMAN
Solar/Wind Harmer
0.253
970865AG2-541 GEN
Solar/Wind Harmer
2.127
315607AA1-063A GEN
Solar/Wind Harmer
0.122
3146043SEABORD
Solar/Wind Harmer
0.059
970673AG2-436 GEN
Solar/Wind Harmer
12.427
970673AG2-436 GEN
Solar/Wind Harmer
8.285
970085AG2-068 GEN
Solar/Wind Harmer
3.058
970581AG2-369 GEN
Solar/Wind Harmer
2.63
941031AE2-094 GEN
Solar/Wind Harmer
10.513
944011AF1-069 GEN
Solar/Wind Harmer
3.435
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.108
3148013FISHERV
Solar/Wind Helper
0.103
3148463FAIRFLD
Solar/Wind Helper
0.124
3151921BEARGRDN G2
50/50
4.422
3144293JTRSVLE
50/50
0.69
970413AG2-270 GEN
50/50
8.802
3151591KERR 2
50/50
0.192
3151261ROARAP2
50/50
0.076
3150861SPRUNCD
50/50
0.297
3151031BRUNSWICKG2
50/50
0.785
3146776BUCKING
Solar/Wind Harmer
0.136
3146926FARMVIL
Solar/Wind Harmer
0.178
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.156
316258AE1-075 C
Solar/Wind Harmer
0.187
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.737
970909AG2-566 GEN
Solar/Wind Harmer
2.353
3147133PAMPLIN
Solar/Wind Harmer
0.682
971193AH1-056 GEN
Solar/Wind Harmer
13.238
963181AG1-167 GEN
Solar/Wind Harmer
0.817
959311AF2-222 GEN
Solar/Wind Harmer
15.236
970257AG2-171 GEN
Solar/Wind Harmer
5.302
315785AD2-033 C
Solar/Wind Harmer
1.283
964241AG1-285 GEN
Solar/Wind Harmer
9.125
316131AB2-060 GEN
Solar/Wind Harmer
0.39
970221AG2-151 GEN
Solar/Wind Harmer
6.362
316478AD1-087 GEN
Solar/Wind Harmer
0.328
316486AD2-202 GEN
Solar/Wind Harmer
0.096
3147043LAWRENC
Solar/Wind Harmer
0.05
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.274
971683AH1-343 GEN
Solar/Wind Harmer
2.442
313506AB2-031 GEN
Solar/Wind Harmer
0.2
970917AG2-570 GEN
Solar/Wind Harmer
5.117
316365GEN2_N
Solar/Wind Harmer
0.127
3148013FISHERV
Solar/Wind Helper
0.18
316499AE2-029_GEN
Solar/Wind Helper
0.518
315616AA1-038_C
Solar/Wind Helper
0.562
3132273ORANGE
Solar/Wind Helper
0.024
3144293JTRSVLE
50/50
0.69
3144293JTRSVLE
50/50
0.581
970535AG2-341 GEN
50/50
1.885
3152661PLYWOOD A
50/50
0.185
3151041BRUNSWICKG3
50/50
0.785
972187AH1-678 GEN
50/50
1.802
315242AE2-183_GT2
50/50
0.972
315241AE2-183_GT1
50/50
0.966
972185AH1-677 GEN
50/50
3.505
970533AG2-339 GEN
50/50
5.074
970531AG2-338 GEN
50/50
2.029
3146776BUCKING
Solar/Wind Harmer
1.508
3146776BUCKING
Solar/Wind Harmer
0.122
970301AG2-198 GEN
Solar/Wind Harmer
9.412
3147133PAMPLIN
Solar/Wind Harmer
0.217
3147133PAMPLIN
Solar/Wind Harmer
0.174
958211AF2-115 GEN
Solar/Wind Harmer
2.452
963191AG1-168 GEN
Solar/Wind Harmer
0.817
971741AH1-377 GEN
Solar/Wind Harmer
19.558
316034AC1-036 C
Solar/Wind Harmer
0.012
970323AG2-213 GEN
Solar/Wind Harmer
7.069
971775AH1-396 GEN
Solar/Wind Harmer
0.265
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971489AH1-241 GEN
Solar/Wind Harmer
6.362
962561AG1-105 GEN
Solar/Wind Harmer
4.763
939181AE1-148 GEN
Solar/Wind Harmer
4.697
971223AH1-071 GEN
Solar/Wind Harmer
1.017
964791AG1-342 GEN
Solar/Wind Harmer
1.83
3146843MT LREL
Solar/Wind Harmer
0.095
3146843MT LREL
Solar/Wind Harmer
0.095
970099AG2-077 GEN
Solar/Wind Harmer
9.986
3143526WINTERP
Solar/Wind Harmer
0.415
970933AG2-581 GEN
Solar/Wind Harmer
5.925
316181AB2-040 GEN
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.062
3145593CAROLNA
Solar/Wind Harmer
0.062
966811AG1-552 GEN
Solar/Wind Harmer
0.675
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.086
3145783HORNRTN
Solar/Wind Harmer
0.869
3145783HORNRTN
Solar/Wind Harmer
0.271
3145783HORNRTN
Solar/Wind Harmer
0.109
316426AA2-053 GEN
Solar/Wind Harmer
0.204
966001AG1-469 GEN
Solar/Wind Helper
0.174
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.118
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.349
LAGNLTFEXP_LAGN->PJM
CLTF
0.897
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.208
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.783
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.427
NYPJM->LTFIMP_NY
CLTF
0.345
CPLELTFEXP_CPLE->PJM
CLTF
3.08
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.625
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:113.5 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:942.09
MW Contribution:8.46
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
21.638
971845AH1-439 GEN
Solar/Wind Harmer
22.236
970285AG2-188 GEN
Solar/Wind Harmer
35.347
315657AE1-056 GEN
Solar/Wind Harmer
9.306
946301AF1-294 GEN
Solar/Wind Harmer
5.986
961791AG1-021 GEN
Solar/Wind Harmer
2.92
970683AG2-441 GEN
Solar/Wind Harmer
16.617
970681AG2-440 GEN
Solar/Wind Harmer
13.294
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.713
316239AB2-077_GEN
Solar/Wind Harmer
0.415
316238AB2-078_GEN
Solar/Wind Harmer
0.415
270494AE1-108_GEN
Solar/Wind Harmer
2.712
316118AC1-105 GEN
Solar/Wind Harmer
0.698
970831AG2-522 GEN
Solar/Wind Harmer
4.772
316233AE1-074 FULL
Solar/Wind Harmer
0.248
971281AH1-106 GEN
Solar/Wind Harmer
1.497
971283AH1-107 GEN
Solar/Wind Harmer
1.497
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
946281AF1-292 GEN
Solar/Wind Harmer
0.179
316087AB2-174 GEN
Solar/Wind Harmer
1.119
971967AH1-528 GEN
Solar/Wind Harmer
14.578
3137643SOCKMAN
Solar/Wind Harmer
-0.03
970865AG2-541 GEN
Solar/Wind Harmer
2.95
315607AA1-063A GEN
Solar/Wind Harmer
0.728
3146043SEABORD
Solar/Wind Harmer
-0.007
971285AH1-108 GEN
Adder
0.475
970673AG2-436 GEN
Solar/Wind Harmer
14.663
970673AG2-436 GEN
Solar/Wind Harmer
7.425
970085AG2-068 GEN
Solar/Wind Harmer
4.347
970581AG2-369 GEN
Solar/Wind Harmer
3.738
941031AE2-094 GEN
Solar/Wind Harmer
12.804
944011AF1-069 GEN
Solar/Wind Harmer
4.012
965291AG1-394 GEN
Solar/Wind Harmer
0.596
315652AC1-086 GEN
Solar/Wind Harmer
7.525
316318V4-068
Solar/Wind Harmer
0.165
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.026
3151921BEARGRDN G2
50/50
4.436
3144293JTRSVLE
50/50
0.702
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
942461AE2-259 GEN
Solar/Wind Harmer
4.35
316313AB2-026
Solar/Wind Harmer
0.755
316258AE1-075 C
Solar/Wind Harmer
0.68
316405AF2-144 C
Solar/Wind Harmer
0.717
3143336POWHATN
Solar/Wind Harmer
2.824
3144293JTRSVLE
50/50
0.702
3144293JTRSVLE
50/50
0.591
3146776BUCKING
Solar/Wind Harmer
-0.17
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.577
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.65
963191AG1-168 GEN
Solar/Wind Harmer
2.19
971741AH1-377 GEN
Solar/Wind Harmer
26.202
316034AC1-036 C
Solar/Wind Harmer
0.354
970323AG2-213 GEN
Solar/Wind Harmer
9.526
971775AH1-396 GEN
Solar/Wind Harmer
1.357
313527AB2-043 GEN
Solar/Wind Harmer
2.287
971489AH1-241 GEN
Solar/Wind Harmer
8.033
962561AG1-105 GEN
Solar/Wind Harmer
6.548
939181AE1-148 GEN
Solar/Wind Harmer
6.48
964791AG1-342 GEN
Solar/Wind Harmer
2.393
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.726
971223AH1-071 GEN
Solar/Wind Harmer
1.368
3143526WINTERP
Solar/Wind Harmer
-0.048
970933AG2-581 GEN
Solar/Wind Harmer
8.213
316181AB2-040 GEN
Solar/Wind Harmer
1.084
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.846
3145593CAROLNA
Solar/Wind Harmer
0.062
3145783HORNRTN
Solar/Wind Harmer
0.879
3145783HORNRTN
Solar/Wind Harmer
0.703
3145783HORNRTN
Solar/Wind Harmer
0.22
3145783HORNRTN
Solar/Wind Harmer
0.088
316426AA2-053 GEN
Solar/Wind Harmer
0.74
972187AH1-678 GEN
Adder
1.814
972185AH1-677 GEN
Adder
3.525
316274AC1-208 GEN
Solar/Wind Harmer
0.733
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.184
3145796HORNRTN
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.012
316222AC1-221 GEN
Solar/Wind Harmer
0.66
3146173TUNIS
Solar/Wind Harmer
-0.006
3146173TUNIS
Solar/Wind Harmer
-0.006
3144356SAPONY
Solar/Wind Harmer
0.227
966001AG1-469 GEN
Solar/Wind Helper
0.172
315814AE2-033 C
Solar/Wind Harmer
6.071
316315AB2-025 C
Solar/Wind Harmer
0.175
3145513AHOSKIE
Solar/Wind Harmer
0.056
961941AG1-037 GEN
Solar/Wind Harmer
0.049
3145513AHOSKIE
Solar/Wind Harmer
-0.006
3145683EARLEYS
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.006
3145683EARLEYS
Solar/Wind Harmer
-0.006
316319Z2-044 C
Solar/Wind Harmer
0.351
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.108
3148013FISHERV
Solar/Wind Helper
0.103
3148463FAIRFLD
Solar/Wind Helper
0.125
3151931BEARGRDN S1
50/50
5.725
3151911BEARGRDN G1
50/50
4.436
3144293JTRSVLE
50/50
0.702
972003AH1-546 GEN
Solar/Wind Harmer
25.74
970937AG2-583 GEN
Solar/Wind Harmer
31.567
316322AB2-045
Solar/Wind Harmer
1.434
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.02
316336AC2-165 C
Solar/Wind Harmer
5.64
3143336POWHATN
Solar/Wind Harmer
3.322
963171AG1-166 GEN
Solar/Wind Harmer
2.92
971563AH1-280 GEN
Solar/Wind Harmer
2.92
970685AG2-442 GEN
Solar/Wind Harmer
18.611
962491AG1-098 GEN
Solar/Wind Harmer
9.593
316237AB2-079_GEN
Solar/Wind Harmer
0.415
315693AD1-088 GEN
Solar/Wind Harmer
6.877
971377AH1-170 GEN
Solar/Wind Harmer
1.692
3147623JAMES R
Solar/Wind Harmer
0.209
970401AG2-262 GEN
Solar/Wind Harmer
0.731
957481AF2-042 GEN
Solar/Wind Harmer
34.315
3143226MDLTHAN
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
1.213
971065AG2-659 GEN
Solar/Wind Harmer
4.98
3147043LAWRENC
Adder
0.793
316129AC1-054 GEN
Solar/Wind Harmer
0.856
971795AH1-408 GEN
Solar/Wind Harmer
6.949
3143526WINTERP
Solar/Wind Harmer
-0.048
316003AC1-222 GEN
Solar/Wind Harmer
0.825
960081AF2-299 GEN
Solar/Wind Harmer
0.9
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.09
3150851SPRUNCC
Adder
0.29
970919AG2-571 GEN
Solar/Wind Harmer
2.207
970087AG2-069 GEN
Solar/Wind Harmer
6.521
316023GEN1_S
Solar/Wind Harmer
0.461
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.4
962571AG1-106 GEN
Solar/Wind Harmer
0.962
316212AC1-099_GEN
Solar/Wind Harmer
0.58
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.196
3146173TUNIS
Solar/Wind Harmer
-0.006
3145823KELFORD
Solar/Wind Harmer
-0.006
3145683EARLEYS
Solar/Wind Harmer
-0.006
3146233WITAKRS
Solar/Wind Harmer
-0.025
315722AD1-056 GEN
Solar/Wind Harmer
0.666
940641AE2-051 GEN
Solar/Wind Harmer
5.935
3147983MERCK5
Solar/Wind Helper
0.057
970909AG2-566 GEN
Solar/Wind Harmer
2.388
3147133PAMPLIN
Solar/Wind Harmer
-0.078
971193AH1-056 GEN
Solar/Wind Harmer
15.51
963181AG1-167 GEN
Solar/Wind Harmer
2.19
959311AF2-222 GEN
Solar/Wind Harmer
20.551
970257AG2-171 GEN
Solar/Wind Harmer
7.144
315785AD2-033 C
Solar/Wind Harmer
4.119
964241AG1-285 GEN
Solar/Wind Harmer
12.377
316131AB2-060 GEN
Solar/Wind Harmer
1.556
970221AG2-151 GEN
Solar/Wind Harmer
8.461
316478AD1-087 GEN
Solar/Wind Harmer
0.958
316486AD2-202 GEN
Solar/Wind Harmer
0.28
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.275
960061AF2-297 GEN
Solar/Wind Harmer
4.563
966621AG1-532 GEN
Solar/Wind Harmer
0.162
971683AH1-343 GEN
Solar/Wind Harmer
3.393
313506AB2-031 GEN
Solar/Wind Harmer
0.625
3150861SPRUNCD
Adder
0.29
970917AG2-570 GEN
Solar/Wind Harmer
17.439
316365GEN2_N
Solar/Wind Harmer
0.461
3146263WOODLND
Solar/Wind Harmer
-0.007
3156081AA2-088 GEN
Solar/Wind Harmer
2.164
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316210AC1-098 GEN
Solar/Wind Harmer
1.044
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.046
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.183
961681AG1-008 GEN
Solar/Wind Harmer
5.183
3146173TUNIS
Solar/Wind Harmer
-0.006
316327AA2-057 GEN
Solar/Wind Harmer
0.657
316317KELFORD C
Solar/Wind Harmer
0.306
3145823KELFORD
Solar/Wind Harmer
-0.006
316283AC2-100 C
Solar/Wind Harmer
0.608
316463AE2-346 GEN
Solar/Wind Harmer
0.104
316140AB2-099
Solar/Wind Harmer
0.044
962331AG1-082 GEN
Solar/Wind Harmer
0.807
3146233WITAKRS
Solar/Wind Harmer
0.133
3146233WITAKRS
Solar/Wind Harmer
-0.004
315724AD1-057 GEN
Solar/Wind Harmer
0.366
3138543CONSLDL
Solar/Wind Harmer
-0.004
3148013FISHERV
Solar/Wind Helper
0.18
316499AE2-029_GEN
Solar/Wind Helper
0.518
315616AA1-038_C
Solar/Wind Helper
0.568
3132273ORANGE
Solar/Wind Helper
0.023
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.137
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.398
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.933
MECLTFEXP_MEC->PJM
CLTF
0.009
LAGNLTFEXP_LAGN->PJM
CLTF
1.413
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.319
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.666
CPLELTFEXP_CPLE->PJM
CLTF
3.817
NYPJM->LTFIMP_NY
CLTF
0.342
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.59
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2066-282_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2066-282_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:111.23 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:923.19
MW Contribution:8.91
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.81
3151911BEARGRDN G1
50/50
4.502
3144293JTRSVLE
50/50
0.7
970119AG2-088 GEN
50/50
16.441
972003AH1-546 GEN
Solar/Wind Harmer
26.109
970937AG2-583 GEN
Solar/Wind Harmer
32.485
316322AB2-045
Solar/Wind Harmer
1.45
3146776BUCKING
Solar/Wind Harmer
-0.017
316336AC2-165 C
Solar/Wind Harmer
5.96
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.567
963171AG1-166 GEN
Solar/Wind Harmer
2.908
971563AH1-280 GEN
Solar/Wind Harmer
2.908
970685AG2-442 GEN
Solar/Wind Harmer
18.475
971377AH1-170 GEN
Solar/Wind Harmer
1.782
3147623JAMES R
Solar/Wind Harmer
0.221
962491AG1-098 GEN
Solar/Wind Harmer
9.39
3143226MDLTHAN
Solar/Wind Harmer
-0.014
315693AD1-088 GEN
Solar/Wind Harmer
6.718
316237AB2-079_GEN
Solar/Wind Harmer
0.403
970401AG2-262 GEN
Solar/Wind Harmer
0.704
957481AF2-042 GEN
Solar/Wind Harmer
33.096
315687AD1-152 GEN
Solar/Wind Harmer
1.157
971065AG2-659 GEN
Solar/Wind Harmer
4.696
3147043LAWRENC
Adder
0.745
316129AC1-054 GEN
Solar/Wind Harmer
0.805
971795AH1-408 GEN
Solar/Wind Harmer
6.476
316003AC1-222 GEN
Solar/Wind Harmer
0.786
960081AF2-299 GEN
Solar/Wind Harmer
0.821
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.081
970919AG2-571 GEN
Solar/Wind Harmer
2.043
970087AG2-069 GEN
Solar/Wind Harmer
6.029
3147983MERCK5
Solar/Wind Helper
0.056
3151921BEARGRDN G2
50/50
4.502
3144293JTRSVLE
50/50
0.7
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.811
316258AE1-075 C
Solar/Wind Harmer
0.73
316405AF2-144 C
Solar/Wind Harmer
0.77
3143336POWHATN
Solar/Wind Harmer
3.032
942461AE2-259 GEN
Solar/Wind Harmer
4.363
970909AG2-566 GEN
Solar/Wind Harmer
2.388
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.482
963181AG1-167 GEN
Solar/Wind Harmer
2.181
959311AF2-222 GEN
Solar/Wind Harmer
20.337
970257AG2-171 GEN
Solar/Wind Harmer
7.06
315785AD2-033 C
Solar/Wind Harmer
4.062
964241AG1-285 GEN
Solar/Wind Harmer
12.123
970221AG2-151 GEN
Solar/Wind Harmer
8.911
316131AB2-060 GEN
Solar/Wind Harmer
1.517
316478AD1-087 GEN
Solar/Wind Harmer
0.922
316486AD2-202 GEN
Solar/Wind Harmer
0.27
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.261
960061AF2-297 GEN
Solar/Wind Harmer
4.339
971683AH1-343 GEN
Solar/Wind Harmer
3.24
966621AG1-532 GEN
Solar/Wind Harmer
0.148
313506AB2-031 GEN
Solar/Wind Harmer
0.568
970917AG2-570 GEN
Solar/Wind Harmer
16.142
3148013FISHERV
Solar/Wind Helper
0.177
316499AE2-029_GEN
Solar/Wind Helper
0.512
315616AA1-038_C
Solar/Wind Helper
0.557
3132273ORANGE
Solar/Wind Helper
0.023
972205AH1-687 GEN
50/50
21.959
316303AF2-085
50/50
2.192
971845AH1-439 GEN
Solar/Wind Harmer
22.482
970285AG2-188 GEN
Solar/Wind Harmer
35.716
315657AE1-056 GEN
Solar/Wind Harmer
9.289
946301AF1-294 GEN
Solar/Wind Harmer
5.962
961791AG1-021 GEN
Solar/Wind Harmer
2.908
970683AG2-441 GEN
Solar/Wind Harmer
16.495
970681AG2-440 GEN
Solar/Wind Harmer
13.196
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.668
316239AB2-077_GEN
Solar/Wind Harmer
0.403
316238AB2-078_GEN
Solar/Wind Harmer
0.403
270494AE1-108_GEN
Solar/Wind Harmer
2.875
316118AC1-105 GEN
Solar/Wind Harmer
0.668
970831AG2-522 GEN
Solar/Wind Harmer
4.476
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
971967AH1-528 GEN
Solar/Wind Harmer
13.768
946281AF1-292 GEN
Solar/Wind Harmer
0.164
316087AB2-174 GEN
Solar/Wind Harmer
1.019
970865AG2-541 GEN
Solar/Wind Harmer
2.825
3137643SOCKMAN
Solar/Wind Harmer
-0.028
970673AG2-436 GEN
Solar/Wind Harmer
13.72
970673AG2-436 GEN
Solar/Wind Harmer
6.947
315607AA1-063A GEN
Solar/Wind Harmer
0.655
3146043SEABORD
Solar/Wind Harmer
-0.006
970085AG2-068 GEN
Solar/Wind Harmer
4.019
970581AG2-369 GEN
Solar/Wind Harmer
3.457
941031AE2-094 GEN
Solar/Wind Harmer
11.99
944011AF1-069 GEN
Solar/Wind Harmer
3.757
971447AH1-217 GEN
Solar/Wind Harmer
2.264
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.102
3148463FAIRFLD
Solar/Wind Helper
0.123
3144293JTRSVLE
50/50
0.7
3144293JTRSVLE
50/50
0.589
3146776BUCKING
Solar/Wind Harmer
-0.172
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.575
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.636
963191AG1-168 GEN
Solar/Wind Harmer
2.181
971741AH1-377 GEN
Solar/Wind Harmer
26.113
316034AC1-036 C
Solar/Wind Harmer
0.35
970323AG2-213 GEN
Solar/Wind Harmer
9.413
971775AH1-396 GEN
Solar/Wind Harmer
1.34
971489AH1-241 GEN
Solar/Wind Harmer
8.46
971223AH1-071 GEN
Solar/Wind Harmer
1.732
313527AB2-043 GEN
Solar/Wind Harmer
2.226
962561AG1-105 GEN
Solar/Wind Harmer
6.315
939181AE1-148 GEN
Solar/Wind Harmer
6.206
964791AG1-342 GEN
Solar/Wind Harmer
2.303
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.238
970933AG2-581 GEN
Solar/Wind Harmer
7.823
316181AB2-040 GEN
Solar/Wind Harmer
0.986
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.766
3145593CAROLNA
Solar/Wind Harmer
0.057
972187AH1-678 GEN
Adder
1.696
3145783HORNRTN
Solar/Wind Harmer
0.793
3145783HORNRTN
Solar/Wind Harmer
0.635
3145783HORNRTN
Solar/Wind Harmer
0.198
3145783HORNRTN
Solar/Wind Harmer
0.079
316426AA2-053 GEN
Solar/Wind Harmer
0.667
972185AH1-677 GEN
Adder
3.297
966001AG1-469 GEN
Solar/Wind Helper
0.17
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.108
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.318
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.251
LAGNLTFEXP_LAGN->PJM
CLTF
0.917
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.775
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.437
CPLELTFEXP_CPLE->PJM
CLTF
3.065
NYPJM->LTFIMP_NY
CLTF
0.338
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.788
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 219-282_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 219-282_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.89 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:920.43
MW Contribution:8.91
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.81
3151911BEARGRDN G1
50/50
4.502
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
16.437
972003AH1-546 GEN
Solar/Wind Harmer
26.108
970937AG2-583 GEN
Solar/Wind Harmer
32.483
316322AB2-045
Solar/Wind Harmer
1.45
3146776BUCKING
Solar/Wind Harmer
-0.017
316336AC2-165 C
Solar/Wind Harmer
5.96
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.567
963171AG1-166 GEN
Solar/Wind Harmer
2.908
3151921BEARGRDN G2
50/50
4.502
3144293JTRSVLE
50/50
0.699
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.811
316258AE1-075 C
Solar/Wind Harmer
0.73
316405AF2-144 C
Solar/Wind Harmer
0.77
3143336POWHATN
Solar/Wind Harmer
3.032
942461AE2-259 GEN
Solar/Wind Harmer
4.363
970909AG2-566 GEN
Solar/Wind Harmer
2.387
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.48
963181AG1-167 GEN
Solar/Wind Harmer
2.181
959311AF2-222 GEN
Solar/Wind Harmer
20.333
970257AG2-171 GEN
Solar/Wind Harmer
7.059
315785AD2-033 C
Solar/Wind Harmer
4.061
964241AG1-285 GEN
Solar/Wind Harmer
12.12
970221AG2-151 GEN
Solar/Wind Harmer
8.909
316131AB2-060 GEN
Solar/Wind Harmer
1.516
316478AD1-087 GEN
Solar/Wind Harmer
0.922
316486AD2-202 GEN
Solar/Wind Harmer
0.27
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.261
960061AF2-297 GEN
Solar/Wind Harmer
4.337
971683AH1-343 GEN
Solar/Wind Harmer
3.239
966621AG1-532 GEN
Solar/Wind Harmer
0.148
313506AB2-031 GEN
Solar/Wind Harmer
0.568
970917AG2-570 GEN
Solar/Wind Harmer
16.134
3148013FISHERV
Solar/Wind Helper
0.177
316499AE2-029_GEN
Solar/Wind Helper
0.512
315616AA1-038_C
Solar/Wind Helper
0.557
3132273ORANGE
Solar/Wind Helper
0.023
971563AH1-280 GEN
Solar/Wind Harmer
2.908
970685AG2-442 GEN
Solar/Wind Harmer
18.472
971377AH1-170 GEN
Solar/Wind Harmer
1.782
3147623JAMES R
Solar/Wind Harmer
0.221
962491AG1-098 GEN
Solar/Wind Harmer
9.388
3143526WINTERP
Solar/Wind Harmer
-0.072
3143226MDLTHAN
Solar/Wind Harmer
-0.014
315693AD1-088 GEN
Solar/Wind Harmer
6.716
316237AB2-079_GEN
Solar/Wind Harmer
0.403
970401AG2-262 GEN
Solar/Wind Harmer
0.703
957481AF2-042 GEN
Solar/Wind Harmer
33.086
315687AD1-152 GEN
Solar/Wind Harmer
1.156
971065AG2-659 GEN
Solar/Wind Harmer
4.694
3147043LAWRENC
Adder
0.744
316129AC1-054 GEN
Solar/Wind Harmer
0.804
971795AH1-408 GEN
Solar/Wind Harmer
6.473
316003AC1-222 GEN
Solar/Wind Harmer
0.786
960081AF2-299 GEN
Solar/Wind Harmer
0.821
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.081
970919AG2-571 GEN
Solar/Wind Harmer
2.042
970087AG2-069 GEN
Solar/Wind Harmer
6.026
3147983MERCK5
Solar/Wind Helper
0.056
972205AH1-687 GEN
50/50
21.958
316303AF2-085
50/50
2.192
971845AH1-439 GEN
Solar/Wind Harmer
22.48
970285AG2-188 GEN
Solar/Wind Harmer
35.714
315657AE1-056 GEN
Solar/Wind Harmer
9.288
946301AF1-294 GEN
Solar/Wind Harmer
5.962
961791AG1-021 GEN
Solar/Wind Harmer
2.908
970683AG2-441 GEN
Solar/Wind Harmer
16.493
970681AG2-440 GEN
Solar/Wind Harmer
13.194
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.667
316233AE1-074 FULL
Solar/Wind Harmer
0.373
971281AH1-106 GEN
Solar/Wind Harmer
2.251
971283AH1-107 GEN
Solar/Wind Harmer
2.251
316239AB2-077_GEN
Solar/Wind Harmer
0.403
316238AB2-078_GEN
Solar/Wind Harmer
0.403
270494AE1-108_GEN
Solar/Wind Harmer
2.874
316118AC1-105 GEN
Solar/Wind Harmer
0.668
970831AG2-522 GEN
Solar/Wind Harmer
4.474
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
971967AH1-528 GEN
Solar/Wind Harmer
13.762
946281AF1-292 GEN
Solar/Wind Harmer
0.163
316087AB2-174 GEN
Solar/Wind Harmer
1.018
970865AG2-541 GEN
Solar/Wind Harmer
2.824
3137643SOCKMAN
Solar/Wind Harmer
-0.028
970673AG2-436 GEN
Solar/Wind Harmer
13.713
970673AG2-436 GEN
Solar/Wind Harmer
6.943
315607AA1-063A GEN
Solar/Wind Harmer
0.655
3146043SEABORD
Solar/Wind Harmer
-0.006
970085AG2-068 GEN
Solar/Wind Harmer
4.017
970581AG2-369 GEN
Solar/Wind Harmer
3.455
941031AE2-094 GEN
Solar/Wind Harmer
11.984
944011AF1-069 GEN
Solar/Wind Harmer
3.755
971447AH1-217 GEN
Solar/Wind Harmer
2.263
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.102
3148463FAIRFLD
Solar/Wind Helper
0.123
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.589
3146776BUCKING
Solar/Wind Harmer
-0.172
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.574
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.635
963191AG1-168 GEN
Solar/Wind Harmer
2.181
971741AH1-377 GEN
Solar/Wind Harmer
26.109
316034AC1-036 C
Solar/Wind Harmer
0.35
970323AG2-213 GEN
Solar/Wind Harmer
9.412
971775AH1-396 GEN
Solar/Wind Harmer
1.34
971489AH1-241 GEN
Solar/Wind Harmer
8.458
3143526WINTERP
Solar/Wind Harmer
-0.072
971223AH1-071 GEN
Solar/Wind Harmer
1.731
313527AB2-043 GEN
Solar/Wind Harmer
2.225
962561AG1-105 GEN
Solar/Wind Harmer
6.313
939181AE1-148 GEN
Solar/Wind Harmer
6.204
964791AG1-342 GEN
Solar/Wind Harmer
2.302
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.234
970933AG2-581 GEN
Solar/Wind Harmer
7.82
316181AB2-040 GEN
Solar/Wind Harmer
0.986
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.766
3145593CAROLNA
Solar/Wind Harmer
0.057
972187AH1-678 GEN
Adder
1.695
3145783HORNRTN
Solar/Wind Harmer
0.793
3145783HORNRTN
Solar/Wind Harmer
0.634
3145783HORNRTN
Solar/Wind Harmer
0.198
3145783HORNRTN
Solar/Wind Harmer
0.079
316426AA2-053 GEN
Solar/Wind Harmer
0.667
972185AH1-677 GEN
Adder
3.295
966001AG1-469 GEN
Solar/Wind Helper
0.17
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.11
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.323
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.243
LAGNLTFEXP_LAGN->PJM
CLTF
0.913
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.768
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.435
CPLELTFEXP_CPLE->PJM
CLTF
3.062
NYPJM->LTFIMP_NY
CLTF
0.339
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.758
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P2-2: DOOMS B2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: DOOMS B2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:106.99 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:887.98
MW Contribution:9.92
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.707
3144293JTRSVLE
50/50
0.595
3146776BUCKING
Solar/Wind Harmer
-0.173
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.692
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.674
963191AG1-168 GEN
Solar/Wind Harmer
2.204
971741AH1-377 GEN
Solar/Wind Harmer
26.373
316034AC1-036 C
Solar/Wind Harmer
0.354
970323AG2-213 GEN
Solar/Wind Harmer
9.533
971775AH1-396 GEN
Solar/Wind Harmer
1.358
971489AH1-241 GEN
Solar/Wind Harmer
9.417
313527AB2-043 GEN
Solar/Wind Harmer
2.264
962561AG1-105 GEN
Solar/Wind Harmer
6.428
939181AE1-148 GEN
Solar/Wind Harmer
6.336
964791AG1-342 GEN
Solar/Wind Harmer
2.344
971223AH1-071 GEN
Solar/Wind Harmer
1.371
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.47
315821AE2-092 GEN
Solar/Wind Harmer
1.938
3143526WINTERP
Solar/Wind Harmer
-0.048
970933AG2-581 GEN
Solar/Wind Harmer
7.992
316181AB2-040 GEN
Solar/Wind Harmer
1.038
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.805
3145593CAROLNA
Solar/Wind Harmer
0.059
3145783HORNRTN
Solar/Wind Harmer
0.834
3145783HORNRTN
Solar/Wind Harmer
0.667
3145783HORNRTN
Solar/Wind Harmer
0.209
3145783HORNRTN
Solar/Wind Harmer
0.083
316426AA2-053 GEN
Solar/Wind Harmer
0.703
972187AH1-678 GEN
Adder
1.74
972185AH1-677 GEN
Adder
3.384
316274AC1-208 GEN
Solar/Wind Harmer
0.685
966001AG1-469 GEN
Solar/Wind Helper
0.173
972205AH1-687 GEN
50/50
22.086
971845AH1-439 GEN
Solar/Wind Harmer
22.632
970285AG2-188 GEN
Solar/Wind Harmer
35.96
315657AE1-056 GEN
Solar/Wind Harmer
9.382
946301AF1-294 GEN
Solar/Wind Harmer
6.025
961791AG1-021 GEN
Solar/Wind Harmer
2.939
970683AG2-441 GEN
Solar/Wind Harmer
16.685
970681AG2-440 GEN
Solar/Wind Harmer
13.348
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.715
316239AB2-077_GEN
Solar/Wind Harmer
0.41
316238AB2-078_GEN
Solar/Wind Harmer
0.41
270494AE1-108_GEN
Solar/Wind Harmer
3.2
316118AC1-105 GEN
Solar/Wind Harmer
0.68
971447AH1-217 GEN
Solar/Wind Harmer
3.32
970831AG2-522 GEN
Solar/Wind Harmer
4.615
316233AE1-074 FULL
Solar/Wind Harmer
0.247
971281AH1-106 GEN
Solar/Wind Harmer
1.493
971283AH1-107 GEN
Solar/Wind Harmer
1.493
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
946281AF1-292 GEN
Solar/Wind Harmer
0.172
316087AB2-174 GEN
Solar/Wind Harmer
1.072
971967AH1-528 GEN
Solar/Wind Harmer
14.102
3137643SOCKMAN
Solar/Wind Harmer
-0.029
970865AG2-541 GEN
Solar/Wind Harmer
2.881
971285AH1-108 GEN
Adder
0.469
315607AA1-063A GEN
Solar/Wind Harmer
0.692
3146043SEABORD
Solar/Wind Harmer
-0.007
970673AG2-436 GEN
Solar/Wind Harmer
14.087
970673AG2-436 GEN
Solar/Wind Harmer
7.133
970085AG2-068 GEN
Solar/Wind Harmer
4.125
970581AG2-369 GEN
Solar/Wind Harmer
3.547
941031AE2-094 GEN
Solar/Wind Harmer
12.32
944011AF1-069 GEN
Solar/Wind Harmer
3.86
965291AG1-394 GEN
Solar/Wind Harmer
0.567
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.128
3148013FISHERV
Solar/Wind Helper
0.123
3148463FAIRFLD
Solar/Wind Helper
0.129
3151931BEARGRDN S1
50/50
5.844
3151911BEARGRDN G1
50/50
4.528
3144293JTRSVLE
50/50
0.707
972003AH1-546 GEN
Solar/Wind Harmer
26.264
970937AG2-583 GEN
Solar/Wind Harmer
32.188
316322AB2-045
Solar/Wind Harmer
1.459
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.02
316336AC2-165 C
Solar/Wind Harmer
5.739
3143336POWHATN
Solar/Wind Harmer
3.376
963171AG1-166 GEN
Solar/Wind Harmer
2.939
971563AH1-280 GEN
Solar/Wind Harmer
2.939
970685AG2-442 GEN
Solar/Wind Harmer
18.688
971377AH1-170 GEN
Solar/Wind Harmer
1.984
3147623JAMES R
Solar/Wind Harmer
0.245
962491AG1-098 GEN
Solar/Wind Harmer
9.522
315693AD1-088 GEN
Solar/Wind Harmer
6.816
316237AB2-079_GEN
Solar/Wind Harmer
0.41
970401AG2-262 GEN
Solar/Wind Harmer
0.716
3143226MDLTHAN
Solar/Wind Harmer
-0.011
957481AF2-042 GEN
Solar/Wind Harmer
33.676
315687AD1-152 GEN
Solar/Wind Harmer
1.177
971065AG2-659 GEN
Solar/Wind Harmer
4.828
3147043LAWRENC
Adder
0.772
316129AC1-054 GEN
Solar/Wind Harmer
0.829
3143526WINTERP
Solar/Wind Harmer
-0.048
971795AH1-408 GEN
Solar/Wind Harmer
6.741
316003AC1-222 GEN
Solar/Wind Harmer
0.801
960081AF2-299 GEN
Solar/Wind Harmer
0.865
3145783HORNRTN
Solar/Wind Harmer
-0.007
3150851SPRUNCC
Adder
0.287
316190AA2-174 GEN
Solar/Wind Harmer
0.085
970919AG2-571 GEN
Solar/Wind Harmer
2.097
970087AG2-069 GEN
Solar/Wind Harmer
6.187
316023GEN1_S
Solar/Wind Harmer
0.439
3146263WOODLND
Solar/Wind Harmer
-0.006
3147983MERCK5
Solar/Wind Helper
0.059
3151921BEARGRDN G2
50/50
4.528
3144293JTRSVLE
50/50
0.707
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
942461AE2-259 GEN
Solar/Wind Harmer
4.401
316313AB2-026
Solar/Wind Harmer
0.767
316258AE1-075 C
Solar/Wind Harmer
0.691
316405AF2-144 C
Solar/Wind Harmer
0.729
3143336POWHATN
Solar/Wind Harmer
2.87
970909AG2-566 GEN
Solar/Wind Harmer
2.41
3147133PAMPLIN
Solar/Wind Harmer
-0.078
971193AH1-056 GEN
Solar/Wind Harmer
15.637
963181AG1-167 GEN
Solar/Wind Harmer
2.204
959311AF2-222 GEN
Solar/Wind Harmer
20.588
970257AG2-171 GEN
Solar/Wind Harmer
7.15
315785AD2-033 C
Solar/Wind Harmer
4.116
970221AG2-151 GEN
Solar/Wind Harmer
9.919
964241AG1-285 GEN
Solar/Wind Harmer
12.307
316131AB2-060 GEN
Solar/Wind Harmer
1.542
316478AD1-087 GEN
Solar/Wind Harmer
0.938
316486AD2-202 GEN
Solar/Wind Harmer
0.275
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.266
960061AF2-297 GEN
Solar/Wind Harmer
4.421
966621AG1-532 GEN
Solar/Wind Harmer
0.156
971683AH1-343 GEN
Solar/Wind Harmer
3.303
313506AB2-031 GEN
Solar/Wind Harmer
0.598
3150861SPRUNCD
Adder
0.287
970917AG2-570 GEN
Solar/Wind Harmer
16.566
316365GEN2_N
Solar/Wind Harmer
0.439
3156081AA2-088 GEN
Solar/Wind Harmer
2.059
3146263WOODLND
Solar/Wind Harmer
-0.006
3148013FISHERV
Solar/Wind Helper
0.214
316499AE2-029_GEN
Solar/Wind Helper
0.539
315616AA1-038_C
Solar/Wind Helper
0.586
3132273ORANGE
Solar/Wind Helper
0.024
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.124
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.365
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.226
LAGNLTFEXP_LAGN->PJM
CLTF
0.913
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.923
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.434
CPLELTFEXP_CPLE->PJM
CLTF
3.156
NYPJM->LTFIMP_NY
CLTF
0.354
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.645
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 6BREMO-AG2-583 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.12 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:946.03
MW Contribution:23.31
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.618
3144293JTRSVLE
50/50
0.52
970535AG2-341 GEN
50/50
1.297
971489AH1-241 GEN
Solar/Wind Harmer
23.308
3146776BUCKING
Solar/Wind Harmer
1.512
3146776BUCKING
Solar/Wind Harmer
0.122
315821AE2-092 GEN
Solar/Wind Harmer
0.018
970301AG2-198 GEN
Solar/Wind Harmer
8.441
3147133PAMPLIN
Solar/Wind Harmer
0.197
3147133PAMPLIN
Solar/Wind Harmer
0.158
958211AF2-115 GEN
Solar/Wind Harmer
2.196
963191AG1-168 GEN
Solar/Wind Harmer
0.732
971741AH1-377 GEN
Solar/Wind Harmer
16.934
316034AC1-036 C
Solar/Wind Harmer
0.01
970323AG2-213 GEN
Solar/Wind Harmer
5.97
971775AH1-396 GEN
Solar/Wind Harmer
0.224
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.408
964791AG1-342 GEN
Solar/Wind Harmer
1.297
3146843MT LREL
Solar/Wind Harmer
0.067
3146843MT LREL
Solar/Wind Harmer
0.067
939181AE1-148 GEN
Solar/Wind Harmer
3.054
3143526WINTERP
Solar/Wind Helper
0.904
3151921BEARGRDN G2
50/50
4.57
3144293JTRSVLE
50/50
0.618
966251AG1-494 GEN
50/50
1.545
3151591KERR 2
50/50
0.12
970221AG2-151 GEN
Solar/Wind Harmer
23.308
3146776BUCKING
Solar/Wind Harmer
0.136
3146926FARMVIL
Solar/Wind Harmer
0.171
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
2.11
3147133PAMPLIN
Solar/Wind Harmer
0.62
971193AH1-056 GEN
Solar/Wind Harmer
12.029
963181AG1-167 GEN
Solar/Wind Harmer
0.732
959311AF2-222 GEN
Solar/Wind Harmer
13.003
958131AF2-107 GEN
Solar/Wind Harmer
4.145
970257AG2-171 GEN
Solar/Wind Harmer
4.477
315785AD2-033 C
Solar/Wind Harmer
1.066
964241AG1-285 GEN
Solar/Wind Harmer
7.188
316131AB2-060 GEN
Solar/Wind Harmer
0.295
316313AB2-026
Solar/Wind Helper
0.958
316258AE1-075 C
Solar/Wind Helper
0.862
316405AF2-144 C
Solar/Wind Helper
0.719
972205AH1-687 GEN
50/50
22.289
3151611KERR 4
50/50
0.12
3151621KERR 5
50/50
0.12
3151631KERR 6
50/50
0.12
3151641KERR 7
50/50
0.12
971447AH1-217 GEN
Solar/Wind Harmer
12.416
971845AH1-439 GEN
Solar/Wind Harmer
16.793
970285AG2-188 GEN
Solar/Wind Harmer
28.117
270494AE1-108_GEN
Solar/Wind Harmer
4.14
315657AE1-056 GEN
Solar/Wind Harmer
6.813
946301AF1-294 GEN
Solar/Wind Harmer
3.611
961791AG1-021 GEN
Solar/Wind Harmer
1.757
970683AG2-441 GEN
Solar/Wind Harmer
10.806
970681AG2-440 GEN
Solar/Wind Harmer
8.645
3144303KENBRDG
Solar/Wind Harmer
0.112
971443AH1-215 GEN
Solar/Wind Harmer
2.318
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.153
316233AE1-074 FULL
Solar/Wind Helper
0.266
3151931BEARGRDN S1
50/50
5.898
3151911BEARGRDN G1
50/50
4.57
3144293JTRSVLE
50/50
0.618
3151601KERR 3
50/50
0.12
3151581KERR 1
50/50
0.043
972003AH1-546 GEN
Solar/Wind Harmer
20.008
971377AH1-170 GEN
Solar/Wind Harmer
4.662
3147623JAMES R
Solar/Wind Harmer
1.013
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.151
3146926FARMVIL
Solar/Wind Harmer
0.171
963171AG1-166 GEN
Solar/Wind Harmer
0.976
971563AH1-280 GEN
Solar/Wind Harmer
1.952
970685AG2-442 GEN
Solar/Wind Harmer
12.103
316237AB2-079_GEN
Solar/Wind Harmer
0.001
962491AG1-098 GEN
Solar/Wind Harmer
4.891
315693AD1-088 GEN
Solar/Wind Harmer
3.821
970401AG2-262 GEN
Solar/Wind Harmer
0.396
962751AG1-124 GEN
Solar/Wind Harmer
2.983
316336AC2-165 C
Solar/Wind Helper
3.978
3143226MDLTHAN
Solar/Wind Helper
0.214
3143526WINTERP
Solar/Wind Helper
0.904
LAGNLTFEXP_LAGN->PJM
CLTF
1.363
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.841
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.476
MECLTFEXP_MEC->PJM
CLTF
0.813
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.179
TVALTFEXP_TVA->PJM
CLTF
0.699
SIGELTFEXP_SIGE->PJM
CLTF
0.026
NYPJM->LTFIMP_NY
CLTF
0.404
LGEELTFEXP_LGEE->PJM
CLTF
0.328
WECLTFEXP_WEC->PJM
CLTF
0.165
CPLELTFEXP_CPLE->PJM
CLTF
1.292
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.85

Details for 6BREMO-AG2-583 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.42 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:940.37
MW Contribution:15.13
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
2.966
3144293JTRSVLE
50/50
0.503
970413AG2-270 GEN
50/50
9.546
966251AG1-494 GEN
50/50
1.198
3151591KERR 2
50/50
0.135
970221AG2-151 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
0.094
3146926FARMVIL
Solar/Wind Harmer
0.129
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
1.869
3147133PAMPLIN
Solar/Wind Harmer
0.497
971193AH1-056 GEN
Solar/Wind Harmer
9.642
963181AG1-167 GEN
Solar/Wind Harmer
0.595
959311AF2-222 GEN
Solar/Wind Harmer
11.09
970257AG2-171 GEN
Solar/Wind Harmer
3.859
315785AD2-033 C
Solar/Wind Harmer
0.934
958131AF2-107 GEN
Solar/Wind Harmer
2.955
316478AD1-087 GEN
Solar/Wind Harmer
0.356
316486AD2-202 GEN
Solar/Wind Harmer
0.105
964241AG1-285 GEN
Solar/Wind Harmer
6.636
316131AB2-060 GEN
Solar/Wind Harmer
0.284
3148013FISHERV
Solar/Wind Harmer
0.071
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.932
971683AH1-343 GEN
Solar/Wind Harmer
2.348
316313AB2-026
Solar/Wind Helper
1.245
316258AE1-075 C
Solar/Wind Helper
1.12
316405AF2-144 C
Solar/Wind Helper
0.933
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.709
315839AE2-212 C
Solar/Wind Helper
0.155
972205AH1-687 GEN
50/50
14.467
3151541CLOVER2
50/50
2.177
3151611KERR 4
50/50
0.135
3151621KERR 5
50/50
0.135
3151631KERR 6
50/50
0.135
3151641KERR 7
50/50
0.135
971447AH1-217 GEN
Solar/Wind Harmer
8.145
971845AH1-439 GEN
Solar/Wind Harmer
11.716
970285AG2-188 GEN
Solar/Wind Harmer
19.851
270494AE1-108_GEN
Solar/Wind Harmer
2.723
315657AE1-056 GEN
Solar/Wind Harmer
5.462
946301AF1-294 GEN
Solar/Wind Harmer
2.936
961791AG1-021 GEN
Solar/Wind Harmer
1.429
970683AG2-441 GEN
Solar/Wind Harmer
9.008
970681AG2-440 GEN
Solar/Wind Harmer
7.206
3144303KENBRDG
Solar/Wind Harmer
0.096
971443AH1-215 GEN
Solar/Wind Harmer
2.005
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.188
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.069
3147243WELCO
Solar/Wind Harmer
0.043
970865AG2-541 GEN
Solar/Wind Harmer
2.13
316123AC1-075 GEN
Solar/Wind Harmer
0.077
970165AG2-112 GEN
Solar/Wind Harmer
0.459
970163AG2-111 GEN
Solar/Wind Harmer
0.438
316233AE1-074 FULL
Solar/Wind Helper
0.38
316312AB1-027
Solar/Wind Helper
0.217
316132AB2-190 GEN1
Solar/Wind Helper
0.639
3151931BEARGRDN S1
50/50
3.828
3151911BEARGRDN G1
50/50
2.966
3144293JTRSVLE
50/50
0.503
3151531CLOVER1
50/50
2.188
3151601KERR 3
50/50
0.135
3151581KERR 1
50/50
0.048
972003AH1-546 GEN
Solar/Wind Harmer
13.118
971377AH1-170 GEN
Solar/Wind Harmer
3.027
3147623JAMES R
Solar/Wind Harmer
0.658
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
963171AG1-166 GEN
Solar/Wind Harmer
0.794
971563AH1-280 GEN
Solar/Wind Harmer
1.587
970685AG2-442 GEN
Solar/Wind Harmer
10.089
962491AG1-098 GEN
Solar/Wind Harmer
7.03
315693AD1-088 GEN
Solar/Wind Harmer
5.777
957481AF2-042 GEN
Solar/Wind Harmer
29.163
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.003
970401AG2-262 GEN
Solar/Wind Harmer
0.451
316003AC1-222 GEN
Solar/Wind Harmer
0.002
316336AC2-165 C
Solar/Wind Helper
5.135
3143226MDLTHAN
Solar/Wind Helper
0.3
3143526WINTERP
Solar/Wind Helper
1.294
3142543TWELFTH
Solar/Wind Helper
0.014
3142416OLDCHRC
Solar/Wind Helper
0.296
3142416OLDCHRC
Solar/Wind Helper
0.113
316458AB2-190 GEN2
Solar/Wind Helper
0.639
3144293JTRSVLE
50/50
0.503
3144293JTRSVLE
50/50
0.423
970535AG2-341 GEN
50/50
1.349
3152661PLYWOOD A
50/50
0.157
971489AH1-241 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
1.049
3146776BUCKING
Solar/Wind Harmer
0.085
315821AE2-092 GEN
Solar/Wind Harmer
0.013
970301AG2-198 GEN
Solar/Wind Harmer
7.476
971741AH1-377 GEN
Solar/Wind Harmer
16.133
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.127
958211AF2-115 GEN
Solar/Wind Harmer
1.786
963191AG1-168 GEN
Solar/Wind Harmer
0.595
316034AC1-036 C
Solar/Wind Harmer
0.009
970323AG2-213 GEN
Solar/Wind Harmer
5.145
971775AH1-396 GEN
Solar/Wind Harmer
0.193
970099AG2-077 GEN
Solar/Wind Harmer
11.665
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.768
964791AG1-342 GEN
Solar/Wind Harmer
1.475
3146843MT LREL
Solar/Wind Harmer
0.077
3146843MT LREL
Solar/Wind Harmer
0.077
939181AE1-148 GEN
Solar/Wind Harmer
3.325
3143526WINTERP
Solar/Wind Helper
1.294
316240AF1-291 C
Solar/Wind Helper
0.162
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.156
316075AC2-137 C
Solar/Wind Helper
0.172
LAGNLTFEXP_LAGN->PJM
CLTF
1.406
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.581
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
1.069
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.04
TVALTFEXP_TVA->PJM
CLTF
0.731
SIGELTFEXP_SIGE->PJM
CLTF
0.035
NYPJM->LTFIMP_NY
CLTF
0.331
LGEELTFEXP_LGEE->PJM
CLTF
0.459
WECLTFEXP_WEC->PJM
CLTF
0.235
CPLELTFEXP_CPLE->PJM
CLTF
0.611
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.053

Details for 6BREMO-AG2-583 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2028T2054_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.11 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1069.25
MW Contribution:30.73
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.302
971447AH1-217 GEN
Solar/Wind Harmer
16.384
971845AH1-439 GEN
Solar/Wind Harmer
22.121
970285AG2-188 GEN
Solar/Wind Harmer
34.956
270494AE1-108_GEN
Solar/Wind Harmer
10.113
315657AE1-056 GEN
Solar/Wind Harmer
8.325
946301AF1-294 GEN
Solar/Wind Harmer
5.269
961791AG1-021 GEN
Solar/Wind Harmer
2.57
970683AG2-441 GEN
Solar/Wind Harmer
14.23
970681AG2-440 GEN
Solar/Wind Harmer
11.384
3144303KENBRDG
Solar/Wind Harmer
-0.013
971443AH1-215 GEN
Solar/Wind Harmer
3.053
316239AB2-077_GEN
Solar/Wind Harmer
0.296
316238AB2-078_GEN
Solar/Wind Harmer
0.296
316118AC1-105 GEN
Solar/Wind Harmer
0.458
316233AE1-074 FULL
Solar/Wind Helper
0.267
3144293JTRSVLE
50/50
0.618
3144293JTRSVLE
50/50
0.521
971489AH1-241 GEN
Solar/Wind Harmer
29.175
3146776BUCKING
Solar/Wind Harmer
-0.169
3146776BUCKING
Solar/Wind Harmer
-0.014
315821AE2-092 GEN
Solar/Wind Harmer
6.931
970301AG2-198 GEN
Solar/Wind Harmer
11.113
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.213
963191AG1-168 GEN
Solar/Wind Harmer
1.928
971741AH1-377 GEN
Solar/Wind Harmer
22.291
316034AC1-036 C
Solar/Wind Harmer
0.292
970323AG2-213 GEN
Solar/Wind Harmer
7.861
971775AH1-396 GEN
Solar/Wind Harmer
1.119
313527AB2-043 GEN
Solar/Wind Harmer
1.646
962561AG1-105 GEN
Solar/Wind Harmer
4.489
964791AG1-342 GEN
Solar/Wind Harmer
1.622
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
939181AE1-148 GEN
Solar/Wind Harmer
4.018
3143526WINTERP
Solar/Wind Helper
0.909
3151931BEARGRDN S1
50/50
5.901
3151911BEARGRDN G1
50/50
4.573
3144293JTRSVLE
50/50
0.618
972003AH1-546 GEN
Solar/Wind Harmer
26.402
971377AH1-170 GEN
Solar/Wind Harmer
6.146
3147623JAMES R
Solar/Wind Harmer
0.761
316322AB2-045
Solar/Wind Harmer
1.43
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
963171AG1-166 GEN
Solar/Wind Harmer
2.57
971563AH1-280 GEN
Solar/Wind Harmer
2.57
970685AG2-442 GEN
Solar/Wind Harmer
15.938
316237AB2-079_GEN
Solar/Wind Harmer
0.296
962491AG1-098 GEN
Solar/Wind Harmer
6.43
315693AD1-088 GEN
Solar/Wind Harmer
4.464
970401AG2-262 GEN
Solar/Wind Harmer
0.496
962751AG1-124 GEN
Solar/Wind Harmer
4.423
316336AC2-165 C
Solar/Wind Helper
3.979
3143226MDLTHAN
Solar/Wind Helper
0.215
3143526WINTERP
Solar/Wind Helper
0.909
3151921BEARGRDN G2
50/50
4.573
3144293JTRSVLE
50/50
0.618
970221AG2-151 GEN
Solar/Wind Harmer
30.731
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.035
970909AG2-566 GEN
Solar/Wind Harmer
2.11
3147133PAMPLIN
Solar/Wind Harmer
-0.069
971193AH1-056 GEN
Solar/Wind Harmer
13.876
963181AG1-167 GEN
Solar/Wind Harmer
1.928
959311AF2-222 GEN
Solar/Wind Harmer
17.157
958131AF2-107 GEN
Solar/Wind Harmer
5.552
970257AG2-171 GEN
Solar/Wind Harmer
5.895
315785AD2-033 C
Solar/Wind Harmer
3.34
964241AG1-285 GEN
Solar/Wind Harmer
9.463
316131AB2-060 GEN
Solar/Wind Harmer
1.135
316313AB2-026
Solar/Wind Helper
0.959
316258AE1-075 C
Solar/Wind Helper
0.863
316405AF2-144 C
Solar/Wind Helper
0.719
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.277
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.604
MECLTFEXP_MEC->PJM
CLTF
0.866
LAGNLTFEXP_LAGN->PJM
CLTF
1.429
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.252
TVALTFEXP_TVA->PJM
CLTF
0.733
SIGELTFEXP_SIGE->PJM
CLTF
0.027
CPLELTFEXP_CPLE->PJM
CLTF
1.307
NYPJM->LTFIMP_NY
CLTF
0.421
LGEELTFEXP_LGEE->PJM
CLTF
0.351
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.286
WECLTFEXP_WEC->PJM
CLTF
0.177

Details for 6BREMO-AG2-583 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 233T2028_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.38 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1052.32
MW Contribution:30.69
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.618
3144293JTRSVLE
50/50
0.521
971489AH1-241 GEN
Solar/Wind Harmer
29.14
3146776BUCKING
Solar/Wind Harmer
-0.169
3146776BUCKING
Solar/Wind Harmer
-0.014
315821AE2-092 GEN
Solar/Wind Harmer
6.892
970301AG2-198 GEN
Solar/Wind Harmer
11.114
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.212
963191AG1-168 GEN
Solar/Wind Harmer
1.927
971741AH1-377 GEN
Solar/Wind Harmer
22.295
316034AC1-036 C
Solar/Wind Harmer
0.292
970323AG2-213 GEN
Solar/Wind Harmer
7.86
971775AH1-396 GEN
Solar/Wind Harmer
1.119
313527AB2-043 GEN
Solar/Wind Harmer
1.646
962561AG1-105 GEN
Solar/Wind Harmer
4.487
964791AG1-342 GEN
Solar/Wind Harmer
1.621
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
939181AE1-148 GEN
Solar/Wind Harmer
4.02
3143526WINTERP
Solar/Wind Helper
0.905
3151931BEARGRDN S1
50/50
5.898
3151911BEARGRDN G1
50/50
4.57
3144293JTRSVLE
50/50
0.618
972003AH1-546 GEN
Solar/Wind Harmer
26.389
971377AH1-170 GEN
Solar/Wind Harmer
6.139
3147623JAMES R
Solar/Wind Harmer
0.76
316322AB2-045
Solar/Wind Harmer
1.43
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
963171AG1-166 GEN
Solar/Wind Harmer
2.57
971563AH1-280 GEN
Solar/Wind Harmer
2.57
970685AG2-442 GEN
Solar/Wind Harmer
15.936
316237AB2-079_GEN
Solar/Wind Harmer
0.296
962491AG1-098 GEN
Solar/Wind Harmer
6.439
315693AD1-088 GEN
Solar/Wind Harmer
4.471
970401AG2-262 GEN
Solar/Wind Harmer
0.495
962751AG1-124 GEN
Solar/Wind Harmer
4.364
316336AC2-165 C
Solar/Wind Helper
3.978
3143226MDLTHAN
Solar/Wind Helper
0.214
3143526WINTERP
Solar/Wind Helper
0.905
3151921BEARGRDN G2
50/50
4.57
3144293JTRSVLE
50/50
0.618
970221AG2-151 GEN
Solar/Wind Harmer
30.694
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.034
970909AG2-566 GEN
Solar/Wind Harmer
2.11
3147133PAMPLIN
Solar/Wind Harmer
-0.069
971193AH1-056 GEN
Solar/Wind Harmer
13.873
963181AG1-167 GEN
Solar/Wind Harmer
1.927
959311AF2-222 GEN
Solar/Wind Harmer
17.156
958131AF2-107 GEN
Solar/Wind Harmer
5.522
970257AG2-171 GEN
Solar/Wind Harmer
5.895
315785AD2-033 C
Solar/Wind Harmer
3.339
964241AG1-285 GEN
Solar/Wind Harmer
9.464
316131AB2-060 GEN
Solar/Wind Harmer
1.135
316313AB2-026
Solar/Wind Helper
0.959
316258AE1-075 C
Solar/Wind Helper
0.862
316405AF2-144 C
Solar/Wind Helper
0.719
972205AH1-687 GEN
50/50
22.291
971447AH1-217 GEN
Solar/Wind Harmer
16.353
971845AH1-439 GEN
Solar/Wind Harmer
22.112
970285AG2-188 GEN
Solar/Wind Harmer
34.943
270494AE1-108_GEN
Solar/Wind Harmer
10.095
315657AE1-056 GEN
Solar/Wind Harmer
8.324
946301AF1-294 GEN
Solar/Wind Harmer
5.268
961791AG1-021 GEN
Solar/Wind Harmer
2.57
970683AG2-441 GEN
Solar/Wind Harmer
14.229
970681AG2-440 GEN
Solar/Wind Harmer
11.383
3144303KENBRDG
Solar/Wind Harmer
-0.013
971443AH1-215 GEN
Solar/Wind Harmer
3.053
316239AB2-077_GEN
Solar/Wind Harmer
0.296
316238AB2-078_GEN
Solar/Wind Harmer
0.296
316118AC1-105 GEN
Solar/Wind Harmer
0.458
316233AE1-074 FULL
Solar/Wind Helper
0.266
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.897
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.492
MECLTFEXP_MEC->PJM
CLTF
0.819
LAGNLTFEXP_LAGN->PJM
CLTF
1.371
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.188
TVALTFEXP_TVA->PJM
CLTF
0.704
SIGELTFEXP_SIGE->PJM
CLTF
0.026
CPLELTFEXP_CPLE->PJM
CLTF
1.294
NYPJM->LTFIMP_NY
CLTF
0.406
LGEELTFEXP_LGEE->PJM
CLTF
0.331
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.906
WECLTFEXP_WEC->PJM
CLTF
0.166

Details for 6BREMO-AG2-583 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.32 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1051.71
MW Contribution:19.91
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
2.964
3144293JTRSVLE
50/50
0.504
3151931BEARGRDN S1
50/50
3.826
3151911BEARGRDN G1
50/50
2.964
970221AG2-151 GEN
Solar/Wind Harmer
19.915
3146776BUCKING
Solar/Wind Harmer
-0.01
3146926FARMVIL
Solar/Wind Harmer
-0.014
942461AE2-259 GEN
Solar/Wind Harmer
3.135
970909AG2-566 GEN
Solar/Wind Harmer
1.873
3147133PAMPLIN
Solar/Wind Harmer
-0.056
971193AH1-056 GEN
Solar/Wind Harmer
11.141
963181AG1-167 GEN
Solar/Wind Harmer
1.571
959311AF2-222 GEN
Solar/Wind Harmer
14.674
970257AG2-171 GEN
Solar/Wind Harmer
5.097
315785AD2-033 C
Solar/Wind Harmer
2.934
958131AF2-107 GEN
Solar/Wind Harmer
3.94
316478AD1-087 GEN
Solar/Wind Harmer
0.998
316486AD2-202 GEN
Solar/Wind Harmer
0.292
964241AG1-285 GEN
Solar/Wind Harmer
8.775
316131AB2-060 GEN
Solar/Wind Harmer
1.1
3148013FISHERV
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.235
960061AF2-297 GEN
Solar/Wind Harmer
3.902
971683AH1-343 GEN
Solar/Wind Harmer
3.125
316313AB2-026
Solar/Wind Helper
1.246
316258AE1-075 C
Solar/Wind Helper
1.122
316405AF2-144 C
Solar/Wind Helper
0.934
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.718
972205AH1-687 GEN
50/50
14.458
971447AH1-217 GEN
Solar/Wind Harmer
10.717
971845AH1-439 GEN
Solar/Wind Harmer
15.427
970285AG2-188 GEN
Solar/Wind Harmer
24.673
270494AE1-108_GEN
Solar/Wind Harmer
6.636
315657AE1-056 GEN
Solar/Wind Harmer
6.684
946301AF1-294 GEN
Solar/Wind Harmer
4.293
961791AG1-021 GEN
Solar/Wind Harmer
2.094
970683AG2-441 GEN
Solar/Wind Harmer
11.891
970681AG2-440 GEN
Solar/Wind Harmer
9.513
3144303KENBRDG
Solar/Wind Harmer
-0.011
971443AH1-215 GEN
Solar/Wind Harmer
2.648
971967AH1-528 GEN
Solar/Wind Harmer
23.681
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.294
316238AB2-078_GEN
Solar/Wind Harmer
0.294
316118AC1-105 GEN
Solar/Wind Harmer
0.567
3148133STUARTS
Solar/Wind Harmer
-0.005
3148013FISHERV
Solar/Wind Harmer
-0.005
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
970865AG2-541 GEN
Solar/Wind Harmer
2.835
316123AC1-075 GEN
Solar/Wind Harmer
0.694
970165AG2-112 GEN
Solar/Wind Harmer
0.611
970163AG2-111 GEN
Solar/Wind Harmer
0.583
316233AE1-074 FULL
Solar/Wind Helper
0.382
316312AB1-027
Solar/Wind Helper
0.22
316132AB2-190 GEN1
Solar/Wind Helper
0.649
315839AE2-212 C
Solar/Wind Helper
0.157
3144293JTRSVLE
50/50
0.504
972003AH1-546 GEN
Solar/Wind Harmer
17.291
971377AH1-170 GEN
Solar/Wind Harmer
3.983
3147623JAMES R
Solar/Wind Harmer
0.493
316322AB2-045
Solar/Wind Harmer
0.992
3146776BUCKING
Solar/Wind Harmer
-0.012
3146926FARMVIL
Solar/Wind Harmer
-0.014
963171AG1-166 GEN
Solar/Wind Harmer
2.094
971563AH1-280 GEN
Solar/Wind Harmer
2.094
970685AG2-442 GEN
Solar/Wind Harmer
13.318
962491AG1-098 GEN
Solar/Wind Harmer
9.296
315693AD1-088 GEN
Solar/Wind Harmer
6.792
957481AF2-042 GEN
Solar/Wind Harmer
38.61
315687AD1-152 GEN
Solar/Wind Harmer
1.176
316237AB2-079_GEN
Solar/Wind Harmer
0.294
970401AG2-262 GEN
Solar/Wind Harmer
0.568
316003AC1-222 GEN
Solar/Wind Harmer
0.733
316336AC2-165 C
Solar/Wind Helper
5.14
3143226MDLTHAN
Solar/Wind Helper
0.302
3143526WINTERP
Solar/Wind Helper
1.302
3142543TWELFTH
Solar/Wind Helper
0.014
3142416OLDCHRC
Solar/Wind Helper
0.3
3142416OLDCHRC
Solar/Wind Helper
0.115
316458AB2-190 GEN2
Solar/Wind Helper
0.649
3142433PROV 92
Solar/Wind Helper
0.45
3144293JTRSVLE
50/50
0.504
3144293JTRSVLE
50/50
0.424
971489AH1-241 GEN
Solar/Wind Harmer
18.907
3146776BUCKING
Solar/Wind Harmer
-0.117
3146776BUCKING
Solar/Wind Harmer
-0.01
315821AE2-092 GEN
Solar/Wind Harmer
4.838
970301AG2-198 GEN
Solar/Wind Harmer
9.862
971741AH1-377 GEN
Solar/Wind Harmer
21.292
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.014
958211AF2-115 GEN
Solar/Wind Harmer
2.618
963191AG1-168 GEN
Solar/Wind Harmer
1.571
316034AC1-036 C
Solar/Wind Harmer
0.253
970323AG2-213 GEN
Solar/Wind Harmer
6.795
971775AH1-396 GEN
Solar/Wind Harmer
0.968
970933AG2-581 GEN
Solar/Wind Harmer
11.81
970099AG2-077 GEN
Solar/Wind Harmer
15.444
313527AB2-043 GEN
Solar/Wind Harmer
1.614
962561AG1-105 GEN
Solar/Wind Harmer
4.999
964791AG1-342 GEN
Solar/Wind Harmer
1.858
3146843MT LREL
Solar/Wind Harmer
-0.009
3146843MT LREL
Solar/Wind Harmer
-0.009
939181AE1-148 GEN
Solar/Wind Harmer
4.411
3143526WINTERP
Solar/Wind Helper
1.302
316240AF1-291 C
Solar/Wind Helper
0.165
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.158
316075AC2-137 C
Solar/Wind Helper
0.175
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.852
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.843
MECLTFEXP_MEC->PJM
CLTF
1.109
LAGNLTFEXP_LAGN->PJM
CLTF
1.488
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.29
TVALTFEXP_TVA->PJM
CLTF
0.772
SIGELTFEXP_SIGE->PJM
CLTF
0.036
CPLELTFEXP_CPLE->PJM
CLTF
0.722
NYPJM->LTFIMP_NY
CLTF
0.343
LGEELTFEXP_LGEE->PJM
CLTF
0.473
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.487
WECLTFEXP_WEC->PJM
CLTF
0.242

Details for 6BREMO-AG2-583 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.31 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1051.63
MW Contribution:19.91
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
3.826
3151911BEARGRDN G1
50/50
2.964
3144293JTRSVLE
50/50
0.504
972003AH1-546 GEN
Solar/Wind Harmer
17.291
971377AH1-170 GEN
Solar/Wind Harmer
3.983
3147623JAMES R
Solar/Wind Harmer
0.493
316322AB2-045
Solar/Wind Harmer
0.992
3146776BUCKING
Solar/Wind Harmer
-0.012
3146926FARMVIL
Solar/Wind Harmer
-0.014
963171AG1-166 GEN
Solar/Wind Harmer
2.094
971563AH1-280 GEN
Solar/Wind Harmer
2.094
970685AG2-442 GEN
Solar/Wind Harmer
13.318
962491AG1-098 GEN
Solar/Wind Harmer
9.296
315693AD1-088 GEN
Solar/Wind Harmer
6.792
957481AF2-042 GEN
Solar/Wind Harmer
38.61
315687AD1-152 GEN
Solar/Wind Harmer
1.176
316237AB2-079_GEN
Solar/Wind Harmer
0.294
970401AG2-262 GEN
Solar/Wind Harmer
0.568
316003AC1-222 GEN
Solar/Wind Harmer
0.733
316336AC2-165 C
Solar/Wind Helper
5.14
3143226MDLTHAN
Solar/Wind Helper
0.302
3143526WINTERP
Solar/Wind Helper
1.302
3142543TWELFTH
Solar/Wind Helper
0.014
3142416OLDCHRC
Solar/Wind Helper
0.3
3142416OLDCHRC
Solar/Wind Helper
0.115
316458AB2-190 GEN2
Solar/Wind Helper
0.649
3142433PROV 92
Solar/Wind Helper
0.45
972205AH1-687 GEN
50/50
14.458
971447AH1-217 GEN
Solar/Wind Harmer
10.717
971845AH1-439 GEN
Solar/Wind Harmer
15.427
970285AG2-188 GEN
Solar/Wind Harmer
24.673
270494AE1-108_GEN
Solar/Wind Harmer
6.636
315657AE1-056 GEN
Solar/Wind Harmer
6.684
946301AF1-294 GEN
Solar/Wind Harmer
4.293
961791AG1-021 GEN
Solar/Wind Harmer
2.094
970683AG2-441 GEN
Solar/Wind Harmer
11.891
970681AG2-440 GEN
Solar/Wind Harmer
9.513
3144303KENBRDG
Solar/Wind Harmer
-0.011
971443AH1-215 GEN
Solar/Wind Harmer
2.648
971967AH1-528 GEN
Solar/Wind Harmer
23.681
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.294
316238AB2-078_GEN
Solar/Wind Harmer
0.294
316118AC1-105 GEN
Solar/Wind Harmer
0.567
3148133STUARTS
Solar/Wind Harmer
-0.005
3148013FISHERV
Solar/Wind Harmer
-0.005
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
970865AG2-541 GEN
Solar/Wind Harmer
2.835
316123AC1-075 GEN
Solar/Wind Harmer
0.694
970165AG2-112 GEN
Solar/Wind Harmer
0.611
970163AG2-111 GEN
Solar/Wind Harmer
0.583
316233AE1-074 FULL
Solar/Wind Helper
0.382
316312AB1-027
Solar/Wind Helper
0.22
316132AB2-190 GEN1
Solar/Wind Helper
0.649
3144293JTRSVLE
50/50
0.504
3144293JTRSVLE
50/50
0.424
971489AH1-241 GEN
Solar/Wind Harmer
18.907
3146776BUCKING
Solar/Wind Harmer
-0.117
3146776BUCKING
Solar/Wind Harmer
-0.01
315821AE2-092 GEN
Solar/Wind Harmer
4.838
970301AG2-198 GEN
Solar/Wind Harmer
9.862
971741AH1-377 GEN
Solar/Wind Harmer
21.292
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.014
958211AF2-115 GEN
Solar/Wind Harmer
2.618
963191AG1-168 GEN
Solar/Wind Harmer
1.571
316034AC1-036 C
Solar/Wind Harmer
0.253
970323AG2-213 GEN
Solar/Wind Harmer
6.795
971775AH1-396 GEN
Solar/Wind Harmer
0.968
970933AG2-581 GEN
Solar/Wind Harmer
11.81
970099AG2-077 GEN
Solar/Wind Harmer
15.444
313527AB2-043 GEN
Solar/Wind Harmer
1.614
962561AG1-105 GEN
Solar/Wind Harmer
4.999
964791AG1-342 GEN
Solar/Wind Harmer
1.858
3146843MT LREL
Solar/Wind Harmer
-0.009
3146843MT LREL
Solar/Wind Harmer
-0.009
939181AE1-148 GEN
Solar/Wind Harmer
4.411
3143526WINTERP
Solar/Wind Helper
1.302
316240AF1-291 C
Solar/Wind Helper
0.165
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.158
316075AC2-137 C
Solar/Wind Helper
0.175
3151921BEARGRDN G2
50/50
2.964
3144293JTRSVLE
50/50
0.504
970221AG2-151 GEN
Solar/Wind Harmer
19.915
3146776BUCKING
Solar/Wind Harmer
-0.01
3146926FARMVIL
Solar/Wind Harmer
-0.014
942461AE2-259 GEN
Solar/Wind Harmer
3.135
970909AG2-566 GEN
Solar/Wind Harmer
1.873
3147133PAMPLIN
Solar/Wind Harmer
-0.056
971193AH1-056 GEN
Solar/Wind Harmer
11.141
963181AG1-167 GEN
Solar/Wind Harmer
1.571
959311AF2-222 GEN
Solar/Wind Harmer
14.674
970257AG2-171 GEN
Solar/Wind Harmer
5.097
315785AD2-033 C
Solar/Wind Harmer
2.934
958131AF2-107 GEN
Solar/Wind Harmer
3.94
316478AD1-087 GEN
Solar/Wind Harmer
0.998
316486AD2-202 GEN
Solar/Wind Harmer
0.292
964241AG1-285 GEN
Solar/Wind Harmer
8.775
316131AB2-060 GEN
Solar/Wind Harmer
1.1
3148013FISHERV
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.235
960061AF2-297 GEN
Solar/Wind Harmer
3.902
971683AH1-343 GEN
Solar/Wind Harmer
3.125
316313AB2-026
Solar/Wind Helper
1.246
316258AE1-075 C
Solar/Wind Helper
1.122
316405AF2-144 C
Solar/Wind Helper
0.934
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.718
315839AE2-212 C
Solar/Wind Helper
0.157
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.852
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.843
MECLTFEXP_MEC->PJM
CLTF
1.109
LAGNLTFEXP_LAGN->PJM
CLTF
1.488
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.29
TVALTFEXP_TVA->PJM
CLTF
0.772
SIGELTFEXP_SIGE->PJM
CLTF
0.036
CPLELTFEXP_CPLE->PJM
CLTF
0.722
NYPJM->LTFIMP_NY
CLTF
0.343
LGEELTFEXP_LGEE->PJM
CLTF
0.473
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.487
WECLTFEXP_WEC->PJM
CLTF
0.242

Details for 6BREMO-AG2-583 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2193_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2028T2193_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.22 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1050.72
MW Contribution:29.42
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.627
3144293JTRSVLE
50/50
0.627
970221AG2-151 GEN
Solar/Wind Harmer
29.423
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.089
970909AG2-566 GEN
Solar/Wind Harmer
2.141
3147133PAMPLIN
Solar/Wind Harmer
-0.07
971193AH1-056 GEN
Solar/Wind Harmer
14.068
963181AG1-167 GEN
Solar/Wind Harmer
1.955
959311AF2-222 GEN
Solar/Wind Harmer
17.41
970257AG2-171 GEN
Solar/Wind Harmer
5.984
958131AF2-107 GEN
Solar/Wind Harmer
5.299
315785AD2-033 C
Solar/Wind Harmer
3.39
964241AG1-285 GEN
Solar/Wind Harmer
9.615
316131AB2-060 GEN
Solar/Wind Harmer
1.154
316313AB2-026
Solar/Wind Helper
0.949
316258AE1-075 C
Solar/Wind Helper
0.854
316405AF2-144 C
Solar/Wind Helper
0.711
3151931BEARGRDN S1
50/50
5.972
3151911BEARGRDN G1
50/50
4.627
3144293JTRSVLE
50/50
0.627
972003AH1-546 GEN
Solar/Wind Harmer
26.719
971377AH1-170 GEN
Solar/Wind Harmer
5.885
3147623JAMES R
Solar/Wind Harmer
0.728
316322AB2-045
Solar/Wind Harmer
1.448
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
963171AG1-166 GEN
Solar/Wind Harmer
2.607
971563AH1-280 GEN
Solar/Wind Harmer
2.607
970685AG2-442 GEN
Solar/Wind Harmer
16.168
316237AB2-079_GEN
Solar/Wind Harmer
0.301
962491AG1-098 GEN
Solar/Wind Harmer
6.56
315693AD1-088 GEN
Solar/Wind Harmer
4.557
970401AG2-262 GEN
Solar/Wind Harmer
0.503
962751AG1-124 GEN
Solar/Wind Harmer
4.196
316336AC2-165 C
Solar/Wind Helper
3.937
3143226MDLTHAN
Solar/Wind Helper
0.212
3143526WINTERP
Solar/Wind Helper
0.892
972205AH1-687 GEN
50/50
22.568
971447AH1-217 GEN
Solar/Wind Harmer
15.499
971845AH1-439 GEN
Solar/Wind Harmer
22.397
970285AG2-188 GEN
Solar/Wind Harmer
35.395
270494AE1-108_GEN
Solar/Wind Harmer
9.679
315657AE1-056 GEN
Solar/Wind Harmer
8.441
946301AF1-294 GEN
Solar/Wind Harmer
5.344
961791AG1-021 GEN
Solar/Wind Harmer
2.607
970683AG2-441 GEN
Solar/Wind Harmer
14.436
970681AG2-440 GEN
Solar/Wind Harmer
11.549
3144303KENBRDG
Solar/Wind Harmer
-0.013
971443AH1-215 GEN
Solar/Wind Harmer
3.098
316239AB2-077_GEN
Solar/Wind Harmer
0.301
316238AB2-078_GEN
Solar/Wind Harmer
0.301
316118AC1-105 GEN
Solar/Wind Harmer
0.465
316233AE1-074 FULL
Solar/Wind Helper
0.262
3144293JTRSVLE
50/50
0.627
3144293JTRSVLE
50/50
0.528
971489AH1-241 GEN
Solar/Wind Harmer
27.933
3146776BUCKING
Solar/Wind Harmer
-0.171
3146776BUCKING
Solar/Wind Harmer
-0.014
315821AE2-092 GEN
Solar/Wind Harmer
6.525
970301AG2-198 GEN
Solar/Wind Harmer
11.274
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.258
963191AG1-168 GEN
Solar/Wind Harmer
1.955
971741AH1-377 GEN
Solar/Wind Harmer
22.629
316034AC1-036 C
Solar/Wind Harmer
0.297
970323AG2-213 GEN
Solar/Wind Harmer
7.978
971775AH1-396 GEN
Solar/Wind Harmer
1.136
313527AB2-043 GEN
Solar/Wind Harmer
1.674
962561AG1-105 GEN
Solar/Wind Harmer
4.561
964791AG1-342 GEN
Solar/Wind Harmer
1.647
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
939181AE1-148 GEN
Solar/Wind Harmer
4.097
3143526WINTERP
Solar/Wind Helper
0.892
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.454
MECLTFEXP_MEC->PJM
CLTF
0.798
LAGNLTFEXP_LAGN->PJM
CLTF
1.355
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.224
TVALTFEXP_TVA->PJM
CLTF
0.694
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
1.323
NYPJM->LTFIMP_NY
CLTF
0.404
LGEELTFEXP_LGEE->PJM
CLTF
0.321
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.76
WECLTFEXP_WEC->PJM
CLTF
0.161

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:202.03 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1371.17
MW Contribution:7.01
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.548
3144293JTRSVLE
50/50
0.754
970413AG2-270 GEN
50/50
10.906
3151591KERR 2
50/50
0.234
3151031BRUNSWICKG2
50/50
1.135
3151261ROARAP2
50/50
0.101
3150861SPRUNCD
50/50
0.398
3151391GASTONA
50/50
0.204
3151411GASTONB
50/50
0.204
3146776BUCKING
Solar/Wind Harmer
0.141
3146926FARMVIL
Solar/Wind Harmer
0.188
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
316313AB2-026
Solar/Wind Harmer
0.171
316258AE1-075 C
Solar/Wind Harmer
0.204
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.088
970909AG2-566 GEN
Solar/Wind Harmer
2.566
3147133PAMPLIN
Solar/Wind Harmer
0.741
971193AH1-056 GEN
Solar/Wind Harmer
14.378
963181AG1-167 GEN
Solar/Wind Harmer
0.893
959311AF2-222 GEN
Solar/Wind Harmer
16.945
970257AG2-171 GEN
Solar/Wind Harmer
5.919
315785AD2-033 C
Solar/Wind Harmer
1.44
964241AG1-285 GEN
Solar/Wind Harmer
10.432
316131AB2-060 GEN
Solar/Wind Harmer
0.453
970221AG2-151 GEN
Solar/Wind Harmer
7.009
316478AD1-087 GEN
Solar/Wind Harmer
0.407
316486AD2-202 GEN
Solar/Wind Harmer
0.12
3147043LAWRENC
Solar/Wind Harmer
0.063
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.061
313506AB2-031 GEN
Solar/Wind Harmer
0.265
971683AH1-343 GEN
Solar/Wind Harmer
3.059
970917AG2-570 GEN
Solar/Wind Harmer
7.384
316365GEN2_N
Solar/Wind Harmer
0.176
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
957521AF2-046 GEN
Solar/Wind Harmer
5.572
961681AG1-008 GEN
Solar/Wind Harmer
5.572
3145796HORNRTN
Solar/Wind Harmer
0.297
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316210AC1-098 GEN
Solar/Wind Harmer
0.686
316463AE2-346 GEN
Solar/Wind Harmer
0.063
316140AB2-099
Solar/Wind Harmer
0.026
962331AG1-082 GEN
Solar/Wind Harmer
0.783
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.073
316327AA2-057 GEN
Solar/Wind Harmer
0.108
3145273HOLLAND
Solar/Wind Harmer
0.054
315813AE1-149 C
Solar/Wind Harmer
3.784
3156021HOLLOMANSOL
Solar/Wind Harmer
0.322
315839AE2-212 C
Solar/Wind Harmer
0.001
315724AD1-057 GEN
Solar/Wind Harmer
0.265
970659AG2-427 GEN
Solar/Wind Harmer
0.747
316083AB2-161 GEN
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
0.07
3146233WITAKRS
Solar/Wind Harmer
0.351
3146233WITAKRS
Solar/Wind Harmer
0.048
3138543CONSLDL
Solar/Wind Harmer
0.046
315737AD1-076 GEN
Solar/Wind Harmer
0.896
971157AH1-035 GEN
Solar/Wind Harmer
0.836
965281AG1-393 GEN
Solar/Wind Harmer
0.741
315614AA2-178 GEN
Solar/Wind Harmer
0.398
3146376EDENTON
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
316435W1029_GEN3
Solar/Wind Harmer
0
316320Y1-086
Solar/Wind Harmer
0
3146456SLIGO L269
Solar/Wind Harmer
0.069
971153AH1-033 GEN
Solar/Wind Harmer
0.794
944581AF1-123 GEN
Solar/Wind Harmer
15.457
944601AF1-125 GEN
Solar/Wind Harmer
15.219
3145963POPLR C
Solar/Wind Harmer
0.069
3151101ELIZAR3
Adder
6.349
3144873MCLAUGH
Solar/Wind Harmer
0.002
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.068
971623AH1-311 GEN
Solar/Wind Harmer
0.136
3144536CHRHLND
Solar/Wind Harmer
0.01
3145933PARMELE
Solar/Wind Harmer
0.068
966801AG1-551 GEN
Solar/Wind Harmer
0.788
961601AG1-000A GEN
Solar/Wind Harmer
4.808
315773AC2-141 GEN
Solar/Wind Harmer
2.468
3146073TAR RVR
Solar/Wind Harmer
0.067
3146083TARBORO
Solar/Wind Harmer
0.067
316283AC2-100 C
Solar/Wind Harmer
0.132
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.027
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.798
3151171GRAVELC
Adder
0.923
961611AG1-000B GEN
Solar/Wind Harmer
1.758
315778AD1-151 GEN
Solar/Wind Harmer
5.261
3144293JTRSVLE
50/50
0.754
3144293JTRSVLE
50/50
0.635
970535AG2-341 GEN
50/50
2.24
3152661PLYWOOD A
50/50
0.227
3151041BRUNSWICKG3
50/50
1.135
972187AH1-678 GEN
50/50
2.606
315242AE2-183_GT2
50/50
1.418
315241AE2-183_GT1
50/50
1.409
972185AH1-677 GEN
50/50
5.111
970533AG2-339 GEN
50/50
7.548
970531AG2-338 GEN
50/50
3.019
3146776BUCKING
Solar/Wind Harmer
1.571
3146776BUCKING
Solar/Wind Harmer
0.127
970301AG2-198 GEN
Solar/Wind Harmer
10.262
3147133PAMPLIN
Solar/Wind Harmer
0.236
3147133PAMPLIN
Solar/Wind Harmer
0.189
958211AF2-115 GEN
Solar/Wind Harmer
2.678
963191AG1-168 GEN
Solar/Wind Harmer
0.893
971741AH1-377 GEN
Solar/Wind Harmer
21.598
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
7.892
971775AH1-396 GEN
Solar/Wind Harmer
0.296
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971489AH1-241 GEN
Solar/Wind Harmer
7.009
971223AH1-071 GEN
Solar/Wind Harmer
1.334
962561AG1-105 GEN
Solar/Wind Harmer
5.681
939181AE1-148 GEN
Solar/Wind Harmer
5.661
970099AG2-077 GEN
Solar/Wind Harmer
12.506
964791AG1-342 GEN
Solar/Wind Harmer
2.195
3146843MT LREL
Solar/Wind Harmer
0.114
3146843MT LREL
Solar/Wind Harmer
0.114
3143526WINTERP
Solar/Wind Harmer
0.547
970933AG2-581 GEN
Solar/Wind Harmer
7.995
316181AB2-040 GEN
Solar/Wind Harmer
0.124
3145593CAROLNA
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.083
966811AG1-552 GEN
Solar/Wind Harmer
0.899
3145593CAROLNA
Solar/Wind Harmer
0.103
3145783HORNRTN
Solar/Wind Harmer
1.451
3145783HORNRTN
Solar/Wind Harmer
1.161
3145783HORNRTN
Solar/Wind Harmer
0.363
3145783HORNRTN
Solar/Wind Harmer
0.145
316426AA2-053 GEN
Solar/Wind Harmer
0.274
3144356SAPONY
Solar/Wind Harmer
0.654
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
0.503
3145893MURPHYS
Solar/Wind Harmer
0.135
316274AC1-208 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
0.223
3146173TUNIS
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
315742AE1-103 GEN
Solar/Wind Harmer
0.001
970657AG2-426 GEN
Solar/Wind Harmer
2.47
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.223
3146376EDENTON
Solar/Wind Harmer
0.308
3146376EDENTON
Solar/Wind Harmer
0.308
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146386ELIZ CT
Solar/Wind Harmer
0.069
316240AF1-291 C
Solar/Wind Harmer
0.001
3130086AYDLETT
Solar/Wind Harmer
0.275
3137176SLIGO L2192
Solar/Wind Harmer
0.273
3146456SLIGO L269
Solar/Wind Harmer
1.215
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.038
316339AD2-160 GEN
Solar/Wind Harmer
0.111
3145506HICKORY
Solar/Wind Harmer
0.274
3145506HICKORY
Solar/Wind Harmer
0.165
3145506HICKORY
Solar/Wind Harmer
0.041
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.066
316036AC1-147 C
Solar/Wind Harmer
0.013
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.505
316222AC1-221 GEN
Solar/Wind Harmer
0.283
316263AC1-034 GEN
Solar/Wind Harmer
2.586
3145933PARMELE
Solar/Wind Harmer
0.135
3145933PARMELE
Solar/Wind Harmer
0.068
961601AG1-000A GEN
Solar/Wind Harmer
1.202
3145493TOT1
Solar/Wind Harmer
0.156
3145453TOT5
Solar/Wind Harmer
0.094
3145603CNETO
Solar/Wind Harmer
0.063
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.074
3142366NRTHEST
Adder
0.195
3142946ENON
Solar/Wind Harmer
0.006
3150691DARBY 3
Adder
4.195
3150701DARBY 4
Adder
4.185
3150681DARBY 2
Adder
4.18
3150671DARBY 1
Adder
4.175
942751AE2-291 GEN
Solar/Wind Harmer
3.155
966001AG1-469 GEN
Solar/Wind Helper
0.19
972205AH1-687 GEN
50/50
22.18
316303AF2-085
50/50
2.224
3151541CLOVER2
50/50
2.487
3151611KERR 4
50/50
0.234
3151621KERR 5
50/50
0.234
3151631KERR 6
50/50
0.234
3151641KERR 7
50/50
0.234
963041AG1-153 GEN
50/50
2.299
315244AE2-183_ST
50/50
2.451
3151281ROARAP4
50/50
0.1
3151281ROARAP4
50/50
0.094
971285AH1-108 GEN
50/50
0.651
315779AE2-040
50/50
1.092
971845AH1-439 GEN
Solar/Wind Harmer
17.513
970285AG2-188 GEN
Solar/Wind Harmer
29.552
315657AE1-056 GEN
Solar/Wind Harmer
8.144
946301AF1-294 GEN
Solar/Wind Harmer
4.404
961791AG1-021 GEN
Solar/Wind Harmer
2.143
970683AG2-441 GEN
Solar/Wind Harmer
13.644
970681AG2-440 GEN
Solar/Wind Harmer
10.915
3144303KENBRDG
Solar/Wind Harmer
0.148
971443AH1-215 GEN
Solar/Wind Harmer
3.079
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316233AE1-074 FULL
Solar/Wind Harmer
0.084
971281AH1-106 GEN
Solar/Wind Harmer
1.459
971283AH1-107 GEN
Solar/Wind Harmer
1.459
316118AC1-105 GEN
Solar/Wind Harmer
0.27
270494AE1-108_GEN
Solar/Wind Harmer
1.236
970831AG2-522 GEN
Solar/Wind Harmer
4.291
3147173SINAI
Solar/Wind Harmer
0.095
3147243WELCO
Solar/Wind Harmer
0.059
971967AH1-528 GEN
Solar/Wind Harmer
14.709
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
18.242
970673AG2-436 GEN
Solar/Wind Harmer
12.162
941031AE2-094 GEN
Solar/Wind Harmer
15.639
944011AF1-069 GEN
Solar/Wind Harmer
5.11
3137643SOCKMAN
Solar/Wind Harmer
0.336
970085AG2-068 GEN
Solar/Wind Harmer
4.411
970581AG2-369 GEN
Solar/Wind Harmer
3.794
315607AA1-063A GEN
Solar/Wind Harmer
0.164
3146043SEABORD
Solar/Wind Harmer
0.08
315814AE2-033 C
Solar/Wind Harmer
6.192
316315AB2-025 C
Solar/Wind Harmer
0.063
970865AG2-541 GEN
Solar/Wind Harmer
2.68
965291AG1-394 GEN
Solar/Wind Harmer
0.339
315652AC1-086 GEN
Solar/Wind Harmer
8.307
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
3145796HORNRTN
Solar/Wind Harmer
0.238
3145796HORNRTN
Solar/Wind Harmer
0.03
3143316POE
Solar/Wind Harmer
0.292
3146033SCOT NK
Solar/Wind Harmer
0.294
3145513AHOSKIE
Solar/Wind Harmer
0.153
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.146
3145683EARLEYS
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
3146206CASHIE
Solar/Wind Harmer
0.07
970601AG2-382 GEN
Solar/Wind Harmer
2.62
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.048
316311AC2-079 GEN
Solar/Wind Harmer
2.01
316319Z2-044 C
Solar/Wind Harmer
0
315732AD1-074 GEN1
Solar/Wind Harmer
0.4
315733AD1-074 GEN2
Solar/Wind Harmer
0.4
315735AD1-075 GEN1
Solar/Wind Harmer
0.2
3130546PLYMOUTH
Solar/Wind Harmer
0.07
315835AF2-110_GEN
Solar/Wind Harmer
0.478
315816AE2-034 GEN
Solar/Wind Harmer
0.298
3130156CHOWAN
Solar/Wind Harmer
0.069
3130156CHOWAN
Solar/Wind Harmer
0.069
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3146486SUNBURY
Solar/Wind Harmer
0.069
3146486SUNBURY
Solar/Wind Harmer
0.069
316321Z2-027
Solar/Wind Harmer
0.013
3145176PASQUOTANK
Solar/Wind Harmer
0.043
3146396TANGLEW
Solar/Wind Harmer
0.19
316305AF2-043 C
Solar/Wind Harmer
0.001
313526AB2-022
Solar/Wind Harmer
0.037
3146406KITTY HAWK
Solar/Wind Harmer
0.009
319010AE1-072 C
Solar/Wind Harmer
0.346
957871AF2-081 GEN
Solar/Wind Harmer
3.419
3151081ELIZAR1
Adder
6.268
3151091ELIZAR2
Adder
6.16
3152611GOSPORTB
Adder
0.871
3152621GOSPORTC
Adder
0.739
3152601GOSPORTA
Adder
0.682
3145573BETHELC
Solar/Wind Harmer
0.067
3145573BETHELC
Solar/Wind Harmer
0.067
316420AA1-050 GEN
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
2.903
316005AA1-067
Solar/Wind Harmer
0.072
3145746EVERETS
Solar/Wind Harmer
0.267
3151931BEARGRDN S1
50/50
5.869
3151911BEARGRDN G1
50/50
4.548
3144293JTRSVLE
50/50
0.754
970119AG2-088 GEN
50/50
16.679
3151531CLOVER1
50/50
2.499
3151601KERR 3
50/50
0.234
3151581KERR 1
50/50
0.083
3147043LAWRENC
50/50
1
3151051BRUNSWICKS1
50/50
2.357
3151021BRUNSWICKG1
50/50
1.135
971451AH1-221 GEN
50/50
3.449
315243AE2-183_GT3
50/50
1.418
3151261ROARAP2
50/50
0.103
3150851SPRUNCC
50/50
0.398
3151391GASTONA
50/50
0.204
3151411GASTONB
50/50
0.204
972003AH1-546 GEN
Solar/Wind Harmer
20.039
970937AG2-583 GEN
Solar/Wind Harmer
24.928
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.157
3146926FARMVIL
Solar/Wind Harmer
0.188
316336AC2-165 C
Solar/Wind Harmer
0.012
3143336POWHATN
Solar/Wind Harmer
4.81
963171AG1-166 GEN
Solar/Wind Harmer
1.19
971563AH1-280 GEN
Solar/Wind Harmer
2.381
970685AG2-442 GEN
Solar/Wind Harmer
15.281
962491AG1-098 GEN
Solar/Wind Harmer
8.349
315693AD1-088 GEN
Solar/Wind Harmer
6.776
316237AB2-079_GEN
Solar/Wind Harmer
0.001
971377AH1-170 GEN
Solar/Wind Harmer
1.402
3147623JAMES R
Solar/Wind Harmer
0.305
3143226MDLTHAN
Solar/Wind Harmer
0.125
957481AF2-042 GEN
Solar/Wind Harmer
31.266
970401AG2-262 GEN
Solar/Wind Harmer
0.671
315687AD1-152 GEN
Solar/Wind Harmer
0.003
3143526WINTERP
Solar/Wind Harmer
0.547
971065AG2-659 GEN
Solar/Wind Harmer
4.446
316129AC1-054 GEN
Solar/Wind Harmer
0.385
971795AH1-408 GEN
Solar/Wind Harmer
6.611
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.847
970919AG2-571 GEN
Solar/Wind Harmer
2.953
970087AG2-069 GEN
Solar/Wind Harmer
6.617
3145783HORNRTN
Solar/Wind Harmer
0.082
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
6.459
316023GEN1_S
Solar/Wind Harmer
0.176
939411AE1-173 GEN
Solar/Wind Harmer
33.156
3146263WOODLND
Solar/Wind Harmer
0.076
316011AB1-132 GEN
Solar/Wind Harmer
1.373
962571AG1-106 GEN
Solar/Wind Harmer
1.074
3145893MURPHYS
Solar/Wind Harmer
0.301
3145893MURPHYS
Solar/Wind Harmer
0.334
3145796HORNRTN
Solar/Wind Harmer
0.245
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316212AC1-099_GEN
Solar/Wind Harmer
0.382
3145823KELFORD
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
315722AD1-056 GEN
Solar/Wind Harmer
0.447
970659AG2-427 GEN
Solar/Wind Harmer
3.416
316381AD1-082 GEN
Solar/Wind Harmer
0.074
970661AG2-428 GEN
Solar/Wind Harmer
7.004
3146206CASHIE
Solar/Wind Harmer
0.07
971547AH1-271 GEN
Solar/Wind Harmer
1.497
3142543TWELFTH
Solar/Wind Harmer
0.007
3146233WITAKRS
Solar/Wind Harmer
0.278
316093AE2-104_GEN
Solar/Wind Harmer
1.171
3145663CRESWEL
Solar/Wind Harmer
0.194
971163AH1-040 GEN
Solar/Wind Harmer
5.558
3130156CHOWAN
Solar/Wind Harmer
0.069
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.223
3146516WINFALL
Solar/Wind Harmer
0.069
315671AE2-027_GEN
Solar/Wind Harmer
4.41
316246AF1-032 C
Solar/Wind Harmer
0.031
3146456SLIGO L269
Solar/Wind Harmer
0.069
316388AE2-253 GEN
Solar/Wind Harmer
0.215
944591AF1-124 GEN
Solar/Wind Harmer
15.512
3145963POPLR C
Solar/Wind Harmer
0.069
316174AB2-169 GEN
Solar/Wind Harmer
0.002
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.853
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.054
316359AB2-059 GEN
Solar/Wind Harmer
0.244
316049AB1-081 GEN
Solar/Wind Harmer
0.389
3142053HEARTS
Solar/Wind Harmer
0.12
316072AD1-144
Solar/Wind Harmer
0.025
3146293MARTNCO
Solar/Wind Harmer
0.063
316294AC1-161 GEN
Solar/Wind Harmer
1.171
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.067
3145493TOT1
Solar/Wind Harmer
0.3
316494AC1-189 GEN
Solar/Wind Harmer
0.227
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.267
3143096IRON208
Adder
0.277
970129AG2-093 GEN
Solar/Wind Harmer
3.971
970133AG2-095 GEN
Solar/Wind Harmer
0.63
3144216WINCHST
Adder
0.231
3150921YORKTN3
Adder
1.525
3142946ENON
Solar/Wind Harmer
0.02
316382AG1-145 C
Solar/Wind Harmer
0
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.175
316499AE2-029_GEN
Solar/Wind Helper
0.514
3132273ORANGE
Solar/Wind Helper
0.027
315616AA1-038_C
Solar/Wind Helper
0.545
3147666LOUISA
Solar/Wind Helper
0.273
3151171GRAVELC
Adder
0.702
961611AG1-000B GEN
Solar/Wind Harmer
3.457
971647AH1-324 GEN
Solar/Wind Harmer
2.81
971069AG2-661 GEN
Solar/Wind Harmer
1.169
316458AB2-190 GEN2
Solar/Wind Harmer
0.353
970129AG2-093 GEN
Solar/Wind Harmer
1.869
944631AF1-128 GEN
Adder
29.45
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971317AH1-138 GEN
Solar/Wind Harmer
0.439
316159AE1-175 C
Solar/Wind Harmer
0.05
3142433PROV 92
Solar/Wind Harmer
0.226
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.056
316192AB2-158 GEN
Solar/Wind Helper
0.823
3147666LOUISA
Solar/Wind Helper
0.475
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
970181AG2-120 GEN
Solar/Wind Harmer
0.836
971445AH1-216 GEN
Solar/Wind Harmer
4.703
972265AH1-717 GEN
Adder
5.124
3151201GRAVEL4
Adder
4.803
3151191GRAVEL3
Adder
4.742
3151211GRAVEL5
Adder
4.742
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.353
316123AC1-075 GEN
Solar/Wind Harmer
0.09
970165AG2-112 GEN
Solar/Wind Harmer
0.531
970163AG2-111 GEN
Solar/Wind Harmer
0.506
971447AH1-217 GEN
Solar/Wind Harmer
1.848
971167AH1-042 GEN
Solar/Wind Harmer
5.088
3138283WHITEMARSH
Solar/Wind Harmer
0.013
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.105
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.12
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.726
MECLTFEXP_MEC->PJM
CLTF
0.354
LAGNLTFEXP_LAGN->PJM
CLTF
1.781
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.535
TVALTFEXP_TVA->PJM
CLTF
0.87
SIGELTFEXP_SIGE->PJM
CLTF
0.008
CPLELTFEXP_CPLE->PJM
CLTF
4.352
NYPJM->LTFIMP_NY
CLTF
0.579
LGEELTFEXP_LGEE->PJM
CLTF
0.048
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.276
WECLTFEXP_WEC->PJM
CLTF
0.018

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:184.71 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1533.11
MW Contribution:9.18
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.86
3151911BEARGRDN G1
50/50
4.541
3144293JTRSVLE
50/50
0.753
970119AG2-088 GEN
50/50
16.672
3151531CLOVER1
50/50
2.497
3151601KERR 3
50/50
0.233
3151581KERR 1
50/50
0.083
972003AH1-546 GEN
Solar/Wind Harmer
26.388
970937AG2-583 GEN
Solar/Wind Harmer
32.774
316322AB2-045
Solar/Wind Harmer
1.483
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.021
316336AC2-165 C
Solar/Wind Harmer
6.018
3143336POWHATN
Solar/Wind Harmer
3.603
963171AG1-166 GEN
Solar/Wind Harmer
3.13
971563AH1-280 GEN
Solar/Wind Harmer
3.13
970685AG2-442 GEN
Solar/Wind Harmer
20.093
962491AG1-098 GEN
Solar/Wind Harmer
10.981
315693AD1-088 GEN
Solar/Wind Harmer
7.922
316237AB2-079_GEN
Solar/Wind Harmer
0.467
971377AH1-170 GEN
Solar/Wind Harmer
1.836
3147623JAMES R
Solar/Wind Harmer
0.227
3143226MDLTHAN
Solar/Wind Harmer
-0.014
957481AF2-042 GEN
Solar/Wind Harmer
41.127
970401AG2-262 GEN
Solar/Wind Harmer
0.837
315687AD1-152 GEN
Solar/Wind Harmer
1.432
3143526WINTERP
Solar/Wind Harmer
-0.061
3147043LAWRENC
Adder
0.942
971065AG2-659 GEN
Solar/Wind Harmer
5.848
316129AC1-054 GEN
Solar/Wind Harmer
1.008
971795AH1-408 GEN
Solar/Wind Harmer
8.35
316003AC1-222 GEN
Solar/Wind Harmer
0.972
960081AF2-299 GEN
Solar/Wind Harmer
1.114
970919AG2-571 GEN
Solar/Wind Harmer
2.952
970087AG2-069 GEN
Solar/Wind Harmer
8.708
3145783HORNRTN
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.375
316190AA2-174 GEN
Solar/Wind Harmer
0.112
940641AE2-051 GEN
Solar/Wind Harmer
8.503
316023GEN1_S
Solar/Wind Harmer
0.594
939411AE1-173 GEN
Solar/Wind Harmer
43.657
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.775
962571AG1-106 GEN
Solar/Wind Harmer
1.22
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
3145796HORNRTN
Solar/Wind Harmer
-0.027
3151921BEARGRDN G2
50/50
4.541
3144293JTRSVLE
50/50
0.753
970413AG2-270 GEN
50/50
10.895
3151591KERR 2
50/50
0.233
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
4.6
316313AB2-026
Solar/Wind Harmer
0.819
316258AE1-075 C
Solar/Wind Harmer
0.737
316405AF2-144 C
Solar/Wind Harmer
0.778
3143336POWHATN
Solar/Wind Harmer
3.062
970909AG2-566 GEN
Solar/Wind Harmer
2.562
3147133PAMPLIN
Solar/Wind Harmer
-0.083
971193AH1-056 GEN
Solar/Wind Harmer
16.559
963181AG1-167 GEN
Solar/Wind Harmer
2.348
959311AF2-222 GEN
Solar/Wind Harmer
22.325
970257AG2-171 GEN
Solar/Wind Harmer
7.783
315785AD2-033 C
Solar/Wind Harmer
4.506
964241AG1-285 GEN
Solar/Wind Harmer
13.718
316131AB2-060 GEN
Solar/Wind Harmer
1.742
970221AG2-151 GEN
Solar/Wind Harmer
9.178
316478AD1-087 GEN
Solar/Wind Harmer
1.133
316486AD2-202 GEN
Solar/Wind Harmer
0.332
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.322
960061AF2-297 GEN
Solar/Wind Harmer
5.34
966621AG1-532 GEN
Solar/Wind Harmer
0.201
313506AB2-031 GEN
Solar/Wind Harmer
0.773
970917AG2-570 GEN
Solar/Wind Harmer
23.32
971683AH1-343 GEN
Solar/Wind Harmer
4.021
3150861SPRUNCD
Adder
0.375
316365GEN2_N
Solar/Wind Harmer
0.594
3156081AA2-088 GEN
Solar/Wind Harmer
2.773
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.624
961681AG1-008 GEN
Solar/Wind Harmer
6.624
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.302
316463AE2-346 GEN
Solar/Wind Harmer
0.133
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.031
316317KELFORD C
Solar/Wind Harmer
0.388
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.813
3145273HOLLAND
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
4.985
3156021HOLLOMANSOL
Solar/Wind Harmer
1.073
315839AE2-212 C
Solar/Wind Harmer
0.24
970659AG2-427 GEN
Solar/Wind Harmer
0.748
316083AB2-161 GEN
Solar/Wind Harmer
1.288
315724AD1-057 GEN
Solar/Wind Harmer
0.456
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
-0.008
3146233WITAKRS
Solar/Wind Harmer
0.164
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.488
971157AH1-035 GEN
Solar/Wind Harmer
0.978
965281AG1-393 GEN
Solar/Wind Harmer
0.977
315614AA2-178 GEN
Solar/Wind Harmer
0.842
3146376EDENTON
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316435W1029_GEN3
Solar/Wind Harmer
1.405
316320Y1-086
Solar/Wind Harmer
0.453
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.941
944581AF1-123 GEN
Solar/Wind Harmer
35.103
3151101ELIZAR3
Adder
6.351
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.801
3151171GRAVELC
Adder
0.924
3144216WINCHST
Adder
0.232
3150921YORKTN3
Adder
1.526
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.176
316499AE2-029_GEN
Solar/Wind Helper
0.517
3132273ORANGE
Solar/Wind Helper
0.028
3147666LOUISA
Solar/Wind Helper
0.309
315616AA1-038_C
Solar/Wind Helper
0.548
944601AF1-125 GEN
Solar/Wind Harmer
11.266
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.723
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.219
316381AD1-082 GEN
Solar/Wind Harmer
0.728
315722AD1-056 GEN
Solar/Wind Harmer
0.83
970661AG2-428 GEN
Solar/Wind Harmer
8.41
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
1.971
3146233WITAKRS
Solar/Wind Harmer
-0.031
316093AE2-104_GEN
Solar/Wind Harmer
2.275
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.318
3130156CHOWAN
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
1.92
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.811
316246AF1-032 C
Solar/Wind Harmer
0.157
3146456SLIGO L269
Solar/Wind Harmer
-0.008
316388AE2-253 GEN
Solar/Wind Harmer
0.521
944591AF1-124 GEN
Solar/Wind Harmer
35.229
3150981CHESPKA
Adder
0.854
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
944631AF1-128 GEN
Adder
29.484
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.057
316192AB2-158 GEN
Solar/Wind Helper
0.927
3147666LOUISA
Solar/Wind Helper
0.538
972205AH1-687 GEN
50/50
22.146
316303AF2-085
50/50
2.223
3151541CLOVER2
50/50
2.485
3151611KERR 4
50/50
0.233
3151621KERR 5
50/50
0.233
3151631KERR 6
50/50
0.233
3151641KERR 7
50/50
0.233
971845AH1-439 GEN
Solar/Wind Harmer
23.024
970285AG2-188 GEN
Solar/Wind Harmer
36.67
315657AE1-056 GEN
Solar/Wind Harmer
9.935
946301AF1-294 GEN
Solar/Wind Harmer
6.417
961791AG1-021 GEN
Solar/Wind Harmer
3.13
970683AG2-441 GEN
Solar/Wind Harmer
17.94
970681AG2-440 GEN
Solar/Wind Harmer
14.352
3144303KENBRDG
Solar/Wind Harmer
-0.017
971443AH1-215 GEN
Solar/Wind Harmer
4.049
316239AB2-077_GEN
Solar/Wind Harmer
0.467
316238AB2-078_GEN
Solar/Wind Harmer
0.467
316233AE1-074 FULL
Solar/Wind Harmer
0.318
971281AH1-106 GEN
Solar/Wind Harmer
1.921
971283AH1-107 GEN
Solar/Wind Harmer
1.921
316118AC1-105 GEN
Solar/Wind Harmer
0.807
270494AE1-108_GEN
Solar/Wind Harmer
2.995
970831AG2-522 GEN
Solar/Wind Harmer
5.644
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
19.409
946281AF1-292 GEN
Solar/Wind Harmer
0.222
316087AB2-174 GEN
Solar/Wind Harmer
1.385
970673AG2-436 GEN
Solar/Wind Harmer
20.177
970673AG2-436 GEN
Solar/Wind Harmer
10.216
941031AE2-094 GEN
Solar/Wind Harmer
17.883
944011AF1-069 GEN
Solar/Wind Harmer
5.603
3137643SOCKMAN
Solar/Wind Harmer
-0.038
970085AG2-068 GEN
Solar/Wind Harmer
5.805
970581AG2-369 GEN
Solar/Wind Harmer
4.993
971285AH1-108 GEN
Adder
0.613
315607AA1-063A GEN
Solar/Wind Harmer
0.911
3146043SEABORD
Solar/Wind Harmer
-0.009
315814AE2-033 C
Solar/Wind Harmer
8.189
316315AB2-025 C
Solar/Wind Harmer
0.237
970865AG2-541 GEN
Solar/Wind Harmer
3.523
965291AG1-394 GEN
Solar/Wind Harmer
0.761
315652AC1-086 GEN
Solar/Wind Harmer
9.545
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.033
3146033SCOT NK
Solar/Wind Harmer
-0.033
3145513AHOSKIE
Solar/Wind Harmer
0.072
961941AG1-037 GEN
Solar/Wind Harmer
0.062
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.449
315833AF1-017_GEN
Solar/Wind Harmer
1.494
316349AD2-085 GEN
Solar/Wind Harmer
0.7
316311AC2-079 GEN
Solar/Wind Harmer
3.968
316319Z2-044 C
Solar/Wind Harmer
0.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.583
315733AD1-074 GEN2
Solar/Wind Harmer
1.583
315735AD1-075 GEN1
Solar/Wind Harmer
0.792
315835AF2-110_GEN
Solar/Wind Harmer
0.978
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.632
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
1.92
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.209
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.142
316305AF2-043 C
Solar/Wind Harmer
0.233
313526AB2-022
Solar/Wind Harmer
0.209
319010AE1-072 C
Solar/Wind Harmer
1.562
3146406KITTY HAWK
Solar/Wind Harmer
0.006
957871AF2-081 GEN
Solar/Wind Harmer
3.86
3151081ELIZAR1
Adder
6.271
3151091ELIZAR2
Adder
6.162
3152611GOSPORTB
Adder
0.871
3152621GOSPORTC
Adder
0.739
3152601GOSPORTA
Adder
0.682
972265AH1-717 GEN
Adder
5.127
3151201GRAVEL4
Adder
4.806
3151191GRAVEL3
Adder
4.745
3151211GRAVEL5
Adder
4.745
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3144293JTRSVLE
50/50
0.753
3144293JTRSVLE
50/50
0.634
970535AG2-341 GEN
50/50
2.238
3146776BUCKING
Solar/Wind Harmer
-0.175
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.493
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.913
963191AG1-168 GEN
Solar/Wind Harmer
2.348
971741AH1-377 GEN
Solar/Wind Harmer
28.4
316034AC1-036 C
Solar/Wind Harmer
0.386
970323AG2-213 GEN
Solar/Wind Harmer
10.377
971775AH1-396 GEN
Solar/Wind Harmer
1.478
313527AB2-043 GEN
Solar/Wind Harmer
2.568
971489AH1-241 GEN
Solar/Wind Harmer
8.713
971223AH1-071 GEN
Solar/Wind Harmer
1.756
962561AG1-105 GEN
Solar/Wind Harmer
7.471
939181AE1-148 GEN
Solar/Wind Harmer
7.446
970099AG2-077 GEN
Solar/Wind Harmer
16.451
964791AG1-342 GEN
Solar/Wind Harmer
2.74
3146843MT LREL
Solar/Wind Harmer
-0.013
3146843MT LREL
Solar/Wind Harmer
-0.013
3143526WINTERP
Solar/Wind Harmer
-0.061
970933AG2-581 GEN
Solar/Wind Harmer
10.52
972187AH1-678 GEN
Adder
2.454
972185AH1-677 GEN
Adder
4.815
316181AB2-040 GEN
Solar/Wind Harmer
1.342
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
1.047
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.088
3145783HORNRTN
Solar/Wind Harmer
0.87
3145783HORNRTN
Solar/Wind Harmer
0.272
3145783HORNRTN
Solar/Wind Harmer
0.109
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.121
316426AA2-053 GEN
Solar/Wind Harmer
0.92
3144356SAPONY
Solar/Wind Harmer
0.307
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
316274AC1-208 GEN
Solar/Wind Harmer
0.909
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.852
970657AG2-426 GEN
Solar/Wind Harmer
2.477
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.932
3146376EDENTON
Solar/Wind Harmer
0.231
3146376EDENTON
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.405
316433W1029_GEN2
Solar/Wind Harmer
1.405
316240AF1-291 C
Solar/Wind Harmer
0.233
3146386ELIZ CT
Solar/Wind Harmer
-0.008
3130086AYDLETT
Solar/Wind Harmer
-0.031
3137176SLIGO L2192
Solar/Wind Harmer
-0.031
3146456SLIGO L269
Solar/Wind Harmer
0.912
316018AA1-139 ULT2
Solar/Wind Harmer
0.661
316017AA1-139 ULT1
Solar/Wind Harmer
0.625
316339AD2-160 GEN
Solar/Wind Harmer
0.521
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.529
3142366NRTHEST
Adder
0.195
3150691DARBY 3
Adder
4.201
3150701DARBY 4
Adder
4.191
3150681DARBY 2
Adder
4.186
3150671DARBY 1
Adder
4.181
966001AG1-469 GEN
Solar/Wind Helper
0.199
LAGNLTFEXP_LAGN->PJM
CLTF
1.77
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
0.346
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.515
TVALTFEXP_TVA->PJM
CLTF
0.864
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.574
LGEELTFEXP_LGEE->PJM
CLTF
0.044
WECLTFEXP_WEC->PJM
CLTF
0.016
CPLELTFEXP_CPLE->PJM
CLTF
4.345
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.202

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:184.71 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1533.1
MW Contribution:9.18
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.54
3144293JTRSVLE
50/50
0.753
970413AG2-270 GEN
50/50
10.894
3151591KERR 2
50/50
0.233
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
4.6
316313AB2-026
Solar/Wind Harmer
0.819
316258AE1-075 C
Solar/Wind Harmer
0.737
316405AF2-144 C
Solar/Wind Harmer
0.778
3143336POWHATN
Solar/Wind Harmer
3.062
970909AG2-566 GEN
Solar/Wind Harmer
2.562
3147133PAMPLIN
Solar/Wind Harmer
-0.083
971193AH1-056 GEN
Solar/Wind Harmer
16.559
963181AG1-167 GEN
Solar/Wind Harmer
2.348
959311AF2-222 GEN
Solar/Wind Harmer
22.325
970257AG2-171 GEN
Solar/Wind Harmer
7.783
315785AD2-033 C
Solar/Wind Harmer
4.506
964241AG1-285 GEN
Solar/Wind Harmer
13.718
316131AB2-060 GEN
Solar/Wind Harmer
1.742
970221AG2-151 GEN
Solar/Wind Harmer
9.177
316478AD1-087 GEN
Solar/Wind Harmer
1.133
316486AD2-202 GEN
Solar/Wind Harmer
0.332
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.322
960061AF2-297 GEN
Solar/Wind Harmer
5.34
966621AG1-532 GEN
Solar/Wind Harmer
0.201
313506AB2-031 GEN
Solar/Wind Harmer
0.773
970917AG2-570 GEN
Solar/Wind Harmer
23.32
971683AH1-343 GEN
Solar/Wind Harmer
4.021
3150861SPRUNCD
Adder
0.375
316365GEN2_N
Solar/Wind Harmer
0.594
3156081AA2-088 GEN
Solar/Wind Harmer
2.773
3151931BEARGRDN S1
50/50
5.86
3151911BEARGRDN G1
50/50
4.54
3144293JTRSVLE
50/50
0.753
970119AG2-088 GEN
50/50
16.671
3151531CLOVER1
50/50
2.497
3151601KERR 3
50/50
0.233
3151581KERR 1
50/50
0.083
972003AH1-546 GEN
Solar/Wind Harmer
26.387
970937AG2-583 GEN
Solar/Wind Harmer
32.773
316322AB2-045
Solar/Wind Harmer
1.483
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.021
316336AC2-165 C
Solar/Wind Harmer
6.018
3143336POWHATN
Solar/Wind Harmer
3.603
963171AG1-166 GEN
Solar/Wind Harmer
3.13
971563AH1-280 GEN
Solar/Wind Harmer
3.13
970685AG2-442 GEN
Solar/Wind Harmer
20.093
962491AG1-098 GEN
Solar/Wind Harmer
10.981
315693AD1-088 GEN
Solar/Wind Harmer
7.922
316237AB2-079_GEN
Solar/Wind Harmer
0.467
971377AH1-170 GEN
Solar/Wind Harmer
1.835
3147623JAMES R
Solar/Wind Harmer
0.227
3143226MDLTHAN
Solar/Wind Harmer
-0.014
957481AF2-042 GEN
Solar/Wind Harmer
41.127
970401AG2-262 GEN
Solar/Wind Harmer
0.837
315687AD1-152 GEN
Solar/Wind Harmer
1.432
3143526WINTERP
Solar/Wind Harmer
-0.061
3147043LAWRENC
Adder
0.942
971065AG2-659 GEN
Solar/Wind Harmer
5.848
316129AC1-054 GEN
Solar/Wind Harmer
1.008
971795AH1-408 GEN
Solar/Wind Harmer
8.349
316003AC1-222 GEN
Solar/Wind Harmer
0.972
960081AF2-299 GEN
Solar/Wind Harmer
1.114
970919AG2-571 GEN
Solar/Wind Harmer
2.952
970087AG2-069 GEN
Solar/Wind Harmer
8.708
3145783HORNRTN
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.375
316190AA2-174 GEN
Solar/Wind Harmer
0.112
940641AE2-051 GEN
Solar/Wind Harmer
8.503
316023GEN1_S
Solar/Wind Harmer
0.594
939411AE1-173 GEN
Solar/Wind Harmer
43.657
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.775
962571AG1-106 GEN
Solar/Wind Harmer
1.22
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.723
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.219
316381AD1-082 GEN
Solar/Wind Harmer
0.728
315722AD1-056 GEN
Solar/Wind Harmer
0.83
970661AG2-428 GEN
Solar/Wind Harmer
8.41
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146206CASHIE
Solar/Wind Harmer
-0.008
972205AH1-687 GEN
50/50
22.145
316303AF2-085
50/50
2.223
971547AH1-271 GEN
Solar/Wind Harmer
1.971
3146233WITAKRS
Solar/Wind Harmer
-0.031
316093AE2-104_GEN
Solar/Wind Harmer
2.275
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.318
3130156CHOWAN
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
1.92
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.811
316246AF1-032 C
Solar/Wind Harmer
0.157
3146456SLIGO L269
Solar/Wind Harmer
-0.008
316388AE2-253 GEN
Solar/Wind Harmer
0.521
944591AF1-124 GEN
Solar/Wind Harmer
35.23
3150981CHESPKA
Adder
0.854
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
944631AF1-128 GEN
Adder
29.485
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.057
316192AB2-158 GEN
Solar/Wind Helper
0.928
3147666LOUISA
Solar/Wind Helper
0.539
3151541CLOVER2
50/50
2.485
3151611KERR 4
50/50
0.233
3151621KERR 5
50/50
0.233
3151631KERR 6
50/50
0.233
3151641KERR 7
50/50
0.233
971845AH1-439 GEN
Solar/Wind Harmer
23.024
970285AG2-188 GEN
Solar/Wind Harmer
36.669
315657AE1-056 GEN
Solar/Wind Harmer
9.935
946301AF1-294 GEN
Solar/Wind Harmer
6.417
961791AG1-021 GEN
Solar/Wind Harmer
3.13
970683AG2-441 GEN
Solar/Wind Harmer
17.94
970681AG2-440 GEN
Solar/Wind Harmer
14.352
3144303KENBRDG
Solar/Wind Harmer
-0.017
971443AH1-215 GEN
Solar/Wind Harmer
4.049
316239AB2-077_GEN
Solar/Wind Harmer
0.467
316238AB2-078_GEN
Solar/Wind Harmer
0.467
316233AE1-074 FULL
Solar/Wind Harmer
0.318
971281AH1-106 GEN
Solar/Wind Harmer
1.921
971283AH1-107 GEN
Solar/Wind Harmer
1.921
316118AC1-105 GEN
Solar/Wind Harmer
0.807
270494AE1-108_GEN
Solar/Wind Harmer
2.995
970831AG2-522 GEN
Solar/Wind Harmer
5.644
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
19.408
946281AF1-292 GEN
Solar/Wind Harmer
0.222
316087AB2-174 GEN
Solar/Wind Harmer
1.385
970673AG2-436 GEN
Solar/Wind Harmer
20.177
970673AG2-436 GEN
Solar/Wind Harmer
10.216
941031AE2-094 GEN
Solar/Wind Harmer
17.883
944011AF1-069 GEN
Solar/Wind Harmer
5.603
3137643SOCKMAN
Solar/Wind Harmer
-0.038
970085AG2-068 GEN
Solar/Wind Harmer
5.805
970581AG2-369 GEN
Solar/Wind Harmer
4.993
971285AH1-108 GEN
Adder
0.613
315607AA1-063A GEN
Solar/Wind Harmer
0.911
3146043SEABORD
Solar/Wind Harmer
-0.009
315814AE2-033 C
Solar/Wind Harmer
8.189
316315AB2-025 C
Solar/Wind Harmer
0.237
970865AG2-541 GEN
Solar/Wind Harmer
3.523
965291AG1-394 GEN
Solar/Wind Harmer
0.761
315652AC1-086 GEN
Solar/Wind Harmer
9.545
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.033
3146033SCOT NK
Solar/Wind Harmer
-0.033
3145513AHOSKIE
Solar/Wind Harmer
0.072
961941AG1-037 GEN
Solar/Wind Harmer
0.062
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.449
315833AF1-017_GEN
Solar/Wind Harmer
1.494
316349AD2-085 GEN
Solar/Wind Harmer
0.7
316311AC2-079 GEN
Solar/Wind Harmer
3.968
316319Z2-044 C
Solar/Wind Harmer
0.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.583
315733AD1-074 GEN2
Solar/Wind Harmer
1.583
315735AD1-075 GEN1
Solar/Wind Harmer
0.792
315835AF2-110_GEN
Solar/Wind Harmer
0.978
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.632
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
1.92
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.209
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.142
316305AF2-043 C
Solar/Wind Harmer
0.233
313526AB2-022
Solar/Wind Harmer
0.209
319010AE1-072 C
Solar/Wind Harmer
1.562
3146406KITTY HAWK
Solar/Wind Harmer
0.006
957871AF2-081 GEN
Solar/Wind Harmer
3.86
3151081ELIZAR1
Adder
6.271
3151091ELIZAR2
Adder
6.162
3152611GOSPORTB
Adder
0.871
3152621GOSPORTC
Adder
0.739
3152601GOSPORTA
Adder
0.682
972265AH1-717 GEN
Adder
5.127
3151201GRAVEL4
Adder
4.806
3151191GRAVEL3
Adder
4.746
3151211GRAVEL5
Adder
4.746
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.121
3144293JTRSVLE
50/50
0.753
3144293JTRSVLE
50/50
0.634
970535AG2-341 GEN
50/50
2.237
3146776BUCKING
Solar/Wind Harmer
-0.175
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.493
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.913
963191AG1-168 GEN
Solar/Wind Harmer
2.348
971741AH1-377 GEN
Solar/Wind Harmer
28.4
316034AC1-036 C
Solar/Wind Harmer
0.386
970323AG2-213 GEN
Solar/Wind Harmer
10.377
971775AH1-396 GEN
Solar/Wind Harmer
1.478
313527AB2-043 GEN
Solar/Wind Harmer
2.568
971489AH1-241 GEN
Solar/Wind Harmer
8.713
971223AH1-071 GEN
Solar/Wind Harmer
1.756
962561AG1-105 GEN
Solar/Wind Harmer
7.471
939181AE1-148 GEN
Solar/Wind Harmer
7.446
970099AG2-077 GEN
Solar/Wind Harmer
16.451
964791AG1-342 GEN
Solar/Wind Harmer
2.74
3146843MT LREL
Solar/Wind Harmer
-0.013
3146843MT LREL
Solar/Wind Harmer
-0.013
3143526WINTERP
Solar/Wind Harmer
-0.061
970933AG2-581 GEN
Solar/Wind Harmer
10.52
972187AH1-678 GEN
Adder
2.454
972185AH1-677 GEN
Adder
4.815
316181AB2-040 GEN
Solar/Wind Harmer
1.342
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
1.047
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.088
3145783HORNRTN
Solar/Wind Harmer
0.87
3145783HORNRTN
Solar/Wind Harmer
0.272
3145783HORNRTN
Solar/Wind Harmer
0.109
316426AA2-053 GEN
Solar/Wind Harmer
0.92
3144356SAPONY
Solar/Wind Harmer
0.307
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
316274AC1-208 GEN
Solar/Wind Harmer
0.909
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.852
970657AG2-426 GEN
Solar/Wind Harmer
2.477
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.932
3146376EDENTON
Solar/Wind Harmer
0.231
3146376EDENTON
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.405
316433W1029_GEN2
Solar/Wind Harmer
1.405
316240AF1-291 C
Solar/Wind Harmer
0.233
3146386ELIZ CT
Solar/Wind Harmer
-0.008
3130086AYDLETT
Solar/Wind Harmer
-0.031
3137176SLIGO L2192
Solar/Wind Harmer
-0.031
3146456SLIGO L269
Solar/Wind Harmer
0.912
316018AA1-139 ULT2
Solar/Wind Harmer
0.661
316017AA1-139 ULT1
Solar/Wind Harmer
0.625
316339AD2-160 GEN
Solar/Wind Harmer
0.521
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.53
3142366NRTHEST
Adder
0.195
3150691DARBY 3
Adder
4.201
3150701DARBY 4
Adder
4.191
3150681DARBY 2
Adder
4.186
3150671DARBY 1
Adder
4.181
966001AG1-469 GEN
Solar/Wind Helper
0.199
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.624
961681AG1-008 GEN
Solar/Wind Harmer
6.624
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.302
316463AE2-346 GEN
Solar/Wind Harmer
0.133
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.031
316317KELFORD C
Solar/Wind Harmer
0.388
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.813
3145273HOLLAND
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
4.985
3156021HOLLOMANSOL
Solar/Wind Harmer
1.073
315839AE2-212 C
Solar/Wind Harmer
0.24
970659AG2-427 GEN
Solar/Wind Harmer
0.748
316083AB2-161 GEN
Solar/Wind Harmer
1.288
315724AD1-057 GEN
Solar/Wind Harmer
0.456
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
-0.008
3146233WITAKRS
Solar/Wind Harmer
0.164
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.488
971157AH1-035 GEN
Solar/Wind Harmer
0.978
965281AG1-393 GEN
Solar/Wind Harmer
0.977
315614AA2-178 GEN
Solar/Wind Harmer
0.842
3146376EDENTON
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316435W1029_GEN3
Solar/Wind Harmer
1.405
316320Y1-086
Solar/Wind Harmer
0.453
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.941
944581AF1-123 GEN
Solar/Wind Harmer
35.103
3151101ELIZAR3
Adder
6.351
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.801
3151171GRAVELC
Adder
0.924
3144216WINCHST
Adder
0.232
3150921YORKTN3
Adder
1.526
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.176
316499AE2-029_GEN
Solar/Wind Helper
0.517
3132273ORANGE
Solar/Wind Helper
0.028
3147666LOUISA
Solar/Wind Helper
0.31
315616AA1-038_C
Solar/Wind Helper
0.549
944601AF1-125 GEN
Solar/Wind Harmer
11.266
LAGNLTFEXP_LAGN->PJM
CLTF
1.769
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
0.346
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.514
TVALTFEXP_TVA->PJM
CLTF
0.864
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.574
LGEELTFEXP_LGEE->PJM
CLTF
0.044
WECLTFEXP_WEC->PJM
CLTF
0.016
CPLELTFEXP_CPLE->PJM
CLTF
4.345
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.201

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:172.6 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1432.61
MW Contribution:9.59
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.442
316303AF2-085
50/50
2.627
971845AH1-439 GEN
Solar/Wind Harmer
23.203
970285AG2-188 GEN
Solar/Wind Harmer
36.921
315657AE1-056 GEN
Solar/Wind Harmer
9.87
3151921BEARGRDN G2
50/50
4.601
3144293JTRSVLE
50/50
0.746
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
316313AB2-026
Solar/Wind Harmer
0.868
316258AE1-075 C
Solar/Wind Harmer
0.782
316405AF2-144 C
Solar/Wind Harmer
0.825
3143336POWHATN
Solar/Wind Harmer
3.247
942461AE2-259 GEN
Solar/Wind Harmer
4.59
970909AG2-566 GEN
Solar/Wind Harmer
2.539
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.45
963181AG1-167 GEN
Solar/Wind Harmer
2.328
959311AF2-222 GEN
Solar/Wind Harmer
22.003
970257AG2-171 GEN
Solar/Wind Harmer
7.661
315785AD2-033 C
Solar/Wind Harmer
4.427
964241AG1-285 GEN
Solar/Wind Harmer
13.397
316131AB2-060 GEN
Solar/Wind Harmer
1.694
970221AG2-151 GEN
Solar/Wind Harmer
9.59
316478AD1-087 GEN
Solar/Wind Harmer
1.073
316486AD2-202 GEN
Solar/Wind Harmer
0.314
3147043LAWRENC
Solar/Wind Harmer
-0.007
3144293JTRSVLE
50/50
0.746
3144293JTRSVLE
50/50
0.629
970535AG2-341 GEN
50/50
2.158
3146776BUCKING
Solar/Wind Harmer
-0.177
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.372
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.88
963191AG1-168 GEN
Solar/Wind Harmer
2.328
971741AH1-377 GEN
Solar/Wind Harmer
28.01
316034AC1-036 C
Solar/Wind Harmer
0.38
970323AG2-213 GEN
Solar/Wind Harmer
10.214
971775AH1-396 GEN
Solar/Wind Harmer
1.455
971223AH1-071 GEN
Solar/Wind Harmer
2.076
313527AB2-043 GEN
Solar/Wind Harmer
2.493
971489AH1-241 GEN
Solar/Wind Harmer
9.104
3143526WINTERP
Solar/Wind Harmer
-0.071
962561AG1-105 GEN
Solar/Wind Harmer
7.195
939181AE1-148 GEN
Solar/Wind Harmer
7.148
970099AG2-077 GEN
Solar/Wind Harmer
15.503
964791AG1-342 GEN
Solar/Wind Harmer
2.634
3146843MT LREL
Solar/Wind Harmer
-0.012
946301AF1-294 GEN
Solar/Wind Harmer
6.363
961791AG1-021 GEN
Solar/Wind Harmer
3.104
970683AG2-441 GEN
Solar/Wind Harmer
17.731
970681AG2-440 GEN
Solar/Wind Harmer
14.185
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.983
316239AB2-077_GEN
Solar/Wind Harmer
0.453
316238AB2-078_GEN
Solar/Wind Harmer
0.453
316233AE1-074 FULL
Solar/Wind Harmer
0.37
971281AH1-106 GEN
Solar/Wind Harmer
2.234
971283AH1-107 GEN
Solar/Wind Harmer
2.234
270494AE1-108_GEN
Solar/Wind Harmer
3.125
316118AC1-105 GEN
Solar/Wind Harmer
0.772
970831AG2-522 GEN
Solar/Wind Harmer
5.366
971285AH1-108 GEN
Adder
0.682
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
946281AF1-292 GEN
Solar/Wind Harmer
0.209
971967AH1-528 GEN
Solar/Wind Harmer
17.53
316087AB2-174 GEN
Solar/Wind Harmer
1.303
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970673AG2-436 GEN
Solar/Wind Harmer
17.985
970673AG2-436 GEN
Solar/Wind Harmer
9.106
941031AE2-094 GEN
Solar/Wind Harmer
15.864
944011AF1-069 GEN
Solar/Wind Harmer
4.971
3151931BEARGRDN S1
50/50
5.938
3151911BEARGRDN G1
50/50
4.601
3144293JTRSVLE
50/50
0.746
970119AG2-088 GEN
50/50
19.705
972003AH1-546 GEN
Solar/Wind Harmer
26.72
970937AG2-583 GEN
Solar/Wind Harmer
33.599
316322AB2-045
Solar/Wind Harmer
1.495
3146776BUCKING
Solar/Wind Harmer
-0.018
316336AC2-165 C
Solar/Wind Harmer
6.302
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.82
963171AG1-166 GEN
Solar/Wind Harmer
3.104
971563AH1-280 GEN
Solar/Wind Harmer
3.104
970685AG2-442 GEN
Solar/Wind Harmer
19.859
3143226MDLTHAN
Solar/Wind Harmer
-0.017
962491AG1-098 GEN
Solar/Wind Harmer
10.562
971377AH1-170 GEN
Solar/Wind Harmer
1.918
3147623JAMES R
Solar/Wind Harmer
0.237
315693AD1-088 GEN
Solar/Wind Harmer
7.599
316237AB2-079_GEN
Solar/Wind Harmer
0.453
3143526WINTERP
Solar/Wind Harmer
-0.071
957481AF2-042 GEN
Solar/Wind Harmer
38.757
970401AG2-262 GEN
Solar/Wind Harmer
0.805
315687AD1-152 GEN
Solar/Wind Harmer
1.355
3147043LAWRENC
Adder
0.898
971065AG2-659 GEN
Solar/Wind Harmer
5.572
316129AC1-054 GEN
Solar/Wind Harmer
0.96
971795AH1-408 GEN
Solar/Wind Harmer
7.936
3150851SPRUNCC
Adder
0.417
316003AC1-222 GEN
Solar/Wind Harmer
0.924
960081AF2-299 GEN
Solar/Wind Harmer
1.049
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
3142543TWELFTH
Solar/Wind Harmer
-0.001
970919AG2-571 GEN
Solar/Wind Harmer
2.65
970087AG2-069 GEN
Solar/Wind Harmer
7.82
316023GEN1_S
Solar/Wind Harmer
0.554
940641AE2-051 GEN
Solar/Wind Harmer
7.517
3143096IRON208
Adder
0.298
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.653
962571AG1-106 GEN
Solar/Wind Harmer
1.136
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
939411AE1-173 GEN
Solar/Wind Harmer
38.95
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.803
316212AC1-099_GEN
Solar/Wind Harmer
0.674
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.029
316381AD1-082 GEN
Solar/Wind Harmer
0.694
970661AG2-428 GEN
Solar/Wind Harmer
7.982
315722AD1-056 GEN
Solar/Wind Harmer
0.771
970129AG2-093 GEN
Solar/Wind Harmer
1.678
316458AB2-190 GEN2
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.827
3146233WITAKRS
Solar/Wind Harmer
-0.029
971069AG2-661 GEN
Solar/Wind Harmer
1.154
316093AE2-104_GEN
Solar/Wind Harmer
2.113
315607AA1-063A GEN
Solar/Wind Harmer
0.854
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.213
970581AG2-369 GEN
Solar/Wind Harmer
4.483
970865AG2-541 GEN
Solar/Wind Harmer
3.349
315814AE2-033 C
Solar/Wind Harmer
7.587
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.711
3143316POE
Solar/Wind Harmer
-0.031
315652AC1-086 GEN
Solar/Wind Harmer
8.889
316318V4-068
Solar/Wind Harmer
0.196
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315833AF1-017_GEN
Solar/Wind Harmer
1.402
316349AD2-085 GEN
Solar/Wind Harmer
0.657
971447AH1-217 GEN
Solar/Wind Harmer
2.63
316311AC2-079 GEN
Solar/Wind Harmer
3.722
316132AB2-190 GEN1
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.197
316319Z2-044 C
Solar/Wind Harmer
0.403
315835AF2-110_GEN
Solar/Wind Harmer
0.908
316369SG1_INVT
Solar/Wind Harmer
1.296
315732AD1-074 GEN1
Solar/Wind Harmer
1.466
315733AD1-074 GEN2
Solar/Wind Harmer
1.466
315735AD1-075 GEN1
Solar/Wind Harmer
0.733
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
0.585
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.775
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316305AF2-043 C
Solar/Wind Harmer
0.216
316321Z2-027
Solar/Wind Harmer
0.193
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
313526AB2-022
Solar/Wind Harmer
0.193
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
972265AH1-717 GEN
Adder
4.91
3151201GRAVEL4
Adder
4.602
3151191GRAVEL3
Adder
4.544
3151211GRAVEL5
Adder
4.544
3152611GOSPORTB
Adder
0.805
3152621GOSPORTC
Adder
0.683
3152601GOSPORTA
Adder
0.63
971445AH1-216 GEN
Solar/Wind Harmer
4.395
3151081ELIZAR1
Adder
5.792
3151091ELIZAR2
Adder
5.691
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.103
3148013FISHERV
Solar/Wind Helper
0.098
3148463FAIRFLD
Solar/Wind Helper
0.118
3146843MT LREL
Solar/Wind Harmer
-0.012
970933AG2-581 GEN
Solar/Wind Harmer
9.649
316181AB2-040 GEN
Solar/Wind Harmer
1.262
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.983
3145593CAROLNA
Solar/Wind Harmer
0.073
972187AH1-678 GEN
Adder
2.2
972185AH1-677 GEN
Adder
4.302
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
316274AC1-208 GEN
Solar/Wind Harmer
0.849
316240AF1-291 C
Solar/Wind Harmer
0.235
944641AF1-129 GEN
Adder
33.028
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.793
970657AG2-426 GEN
Solar/Wind Harmer
2.358
970657AG2-426 GEN
Solar/Wind Harmer
0.493
316065AD1-022 GEN
Solar/Wind Harmer
3.643
316033AB2-134 GEN
Solar/Wind Harmer
2.34
315697AD1-025 GEN
Solar/Wind Harmer
1.468
3142366NRTHEST
Adder
0.21
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3150861SPRUNCD
Adder
0.417
316248AF1-058 C
Solar/Wind Harmer
0.306
960061AF2-297 GEN
Solar/Wind Harmer
5.079
966621AG1-532 GEN
Solar/Wind Harmer
0.189
313506AB2-031 GEN
Solar/Wind Harmer
0.727
971683AH1-343 GEN
Solar/Wind Harmer
3.823
970917AG2-570 GEN
Solar/Wind Harmer
20.936
316365GEN2_N
Solar/Wind Harmer
0.554
3143096IRON208
Adder
0.298
3143096IRON208
Adder
0.292
3156081AA2-088 GEN
Solar/Wind Harmer
2.589
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
315839AE2-212 C
Solar/Wind Harmer
0.237
957521AF2-046 GEN
Solar/Wind Harmer
6.176
961681AG1-008 GEN
Solar/Wind Harmer
6.176
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
965281AG1-393 GEN
Solar/Wind Harmer
0.97
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.214
315813AE1-149 C
Solar/Wind Harmer
4.801
316463AE2-346 GEN
Solar/Wind Harmer
0.124
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.959
316317KELFORD C
Solar/Wind Harmer
0.361
3145823KELFORD
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
0.714
316083AB2-161 GEN
Solar/Wind Harmer
1.228
970661AG2-428 GEN
Solar/Wind Harmer
1.415
316327AA2-057 GEN
Solar/Wind Harmer
0.756
3145273HOLLAND
Solar/Wind Harmer
-0.006
970133AG2-095 GEN
Solar/Wind Harmer
0.837
3156021HOLLOMANSOL
Solar/Wind Harmer
0.996
315724AD1-057 GEN
Solar/Wind Harmer
0.424
970129AG2-093 GEN
Solar/Wind Harmer
4.142
3146206CASHIE
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.153
3146233WITAKRS
Solar/Wind Harmer
-0.005
315778AD1-151 GEN
Solar/Wind Harmer
6.319
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.378
971157AH1-035 GEN
Solar/Wind Harmer
0.905
315614AA2-178 GEN
Solar/Wind Harmer
0.779
3146376EDENTON
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
30.658
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.772
971647AH1-324 GEN
Solar/Wind Harmer
3.605
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.775
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.535
316246AF1-032 C
Solar/Wind Harmer
0.145
3145963POPLR C
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
316174AB2-169 GEN
Solar/Wind Harmer
1.097
3151171GRAVELC
Adder
0.673
316375AC2-012 GEN
Solar/Wind Harmer
2.457
3145336SMITFLD
Solar/Wind Harmer
-0.028
3150981CHESPKA
Adder
0.789
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
944591AF1-124 GEN
Solar/Wind Harmer
32.38
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.798
3147666LOUISA
Solar/Wind Helper
0.46
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.298
961611AG1-000B GEN
Solar/Wind Harmer
1.508
316320Y1-086
Solar/Wind Harmer
0.418
3145963POPLR C
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151221GRAVEL6
Adder
4.597
3151171GRAVELC
Adder
0.884
3144873MCLAUGH
Solar/Wind Harmer
0
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.866
3144216WINCHST
Adder
0.221
3150921YORKTN3
Adder
1.456
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3148013FISHERV
Solar/Wind Helper
0.171
316499AE2-029_GEN
Solar/Wind Helper
0.503
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.534
3147666LOUISA
Solar/Wind Helper
0.265
944581AF1-123 GEN
Solar/Wind Harmer
1.127
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.298
316433W1029_GEN2
Solar/Wind Harmer
1.298
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316222AC1-221 GEN
Solar/Wind Harmer
0.722
3130086AYDLETT
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.75
3142956BIRDNECK
Solar/Wind Harmer
0.381
316316AC1-027 C
Solar/Wind Harmer
0.218
316236AE1-162_GEN
Solar/Wind Harmer
0.214
316036AC1-147 C
Solar/Wind Harmer
0.192
3150991CHESPKB
Adder
0.662
3150991CHESPKB
Adder
0.646
3150691DARBY 3
Adder
4.502
3150701DARBY 4
Adder
4.491
3150681DARBY 2
Adder
4.486
3150671DARBY 1
Adder
4.481
966001AG1-469 GEN
Solar/Wind Helper
0.186
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.012
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.013
LAGNLTFEXP_LAGN->PJM
CLTF
1.555
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.345
MECLTFEXP_MEC->PJM
CLTF
0.252
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.774
TVALTFEXP_TVA->PJM
CLTF
0.758
SIGELTFEXP_SIGE->PJM
CLTF
0.005
NYPJM->LTFIMP_NY
CLTF
0.536
LGEELTFEXP_LGEE->PJM
CLTF
0.012
CPLELTFEXP_CPLE->PJM
CLTF
3.992
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.116

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:172.6 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1432.61
MW Contribution:9.59
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.746
3144293JTRSVLE
50/50
0.629
970535AG2-341 GEN
50/50
2.158
3146776BUCKING
Solar/Wind Harmer
-0.177
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.372
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.88
963191AG1-168 GEN
Solar/Wind Harmer
2.328
971741AH1-377 GEN
Solar/Wind Harmer
28.01
316034AC1-036 C
Solar/Wind Harmer
0.38
970323AG2-213 GEN
Solar/Wind Harmer
10.214
971775AH1-396 GEN
Solar/Wind Harmer
1.455
971223AH1-071 GEN
Solar/Wind Harmer
2.076
313527AB2-043 GEN
Solar/Wind Harmer
2.493
971489AH1-241 GEN
Solar/Wind Harmer
9.104
3143526WINTERP
Solar/Wind Harmer
-0.071
962561AG1-105 GEN
Solar/Wind Harmer
7.195
939181AE1-148 GEN
Solar/Wind Harmer
7.148
970099AG2-077 GEN
Solar/Wind Harmer
15.503
964791AG1-342 GEN
Solar/Wind Harmer
2.634
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970933AG2-581 GEN
Solar/Wind Harmer
9.649
316181AB2-040 GEN
Solar/Wind Harmer
1.262
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.983
3145593CAROLNA
Solar/Wind Harmer
0.073
972187AH1-678 GEN
Adder
2.2
972185AH1-677 GEN
Adder
4.302
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
316274AC1-208 GEN
Solar/Wind Harmer
0.849
316240AF1-291 C
Solar/Wind Harmer
0.235
944641AF1-129 GEN
Adder
33.028
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.793
970657AG2-426 GEN
Solar/Wind Harmer
2.358
970657AG2-426 GEN
Solar/Wind Harmer
0.493
316065AD1-022 GEN
Solar/Wind Harmer
3.643
316033AB2-134 GEN
Solar/Wind Harmer
2.34
315697AD1-025 GEN
Solar/Wind Harmer
1.468
3142366NRTHEST
Adder
0.21
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
972205AH1-687 GEN
50/50
22.442
316303AF2-085
50/50
2.627
971845AH1-439 GEN
Solar/Wind Harmer
23.203
970285AG2-188 GEN
Solar/Wind Harmer
36.921
315657AE1-056 GEN
Solar/Wind Harmer
9.87
946301AF1-294 GEN
Solar/Wind Harmer
6.363
961791AG1-021 GEN
Solar/Wind Harmer
3.104
970683AG2-441 GEN
Solar/Wind Harmer
17.731
970681AG2-440 GEN
Solar/Wind Harmer
14.185
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.983
316239AB2-077_GEN
Solar/Wind Harmer
0.453
316238AB2-078_GEN
Solar/Wind Harmer
0.453
316233AE1-074 FULL
Solar/Wind Harmer
0.37
971281AH1-106 GEN
Solar/Wind Harmer
2.234
971283AH1-107 GEN
Solar/Wind Harmer
2.234
270494AE1-108_GEN
Solar/Wind Harmer
3.125
316118AC1-105 GEN
Solar/Wind Harmer
0.772
970831AG2-522 GEN
Solar/Wind Harmer
5.366
971285AH1-108 GEN
Adder
0.682
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.298
316433W1029_GEN2
Solar/Wind Harmer
1.298
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316222AC1-221 GEN
Solar/Wind Harmer
0.722
3130086AYDLETT
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
946281AF1-292 GEN
Solar/Wind Harmer
0.209
971967AH1-528 GEN
Solar/Wind Harmer
17.53
316087AB2-174 GEN
Solar/Wind Harmer
1.303
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970673AG2-436 GEN
Solar/Wind Harmer
17.985
970673AG2-436 GEN
Solar/Wind Harmer
9.106
941031AE2-094 GEN
Solar/Wind Harmer
15.864
944011AF1-069 GEN
Solar/Wind Harmer
4.971
315607AA1-063A GEN
Solar/Wind Harmer
0.854
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.213
970581AG2-369 GEN
Solar/Wind Harmer
4.483
970865AG2-541 GEN
Solar/Wind Harmer
3.349
315814AE2-033 C
Solar/Wind Harmer
7.587
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.711
3143316POE
Solar/Wind Harmer
-0.031
315652AC1-086 GEN
Solar/Wind Harmer
8.889
316318V4-068
Solar/Wind Harmer
0.196
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315833AF1-017_GEN
Solar/Wind Harmer
1.402
316349AD2-085 GEN
Solar/Wind Harmer
0.657
971447AH1-217 GEN
Solar/Wind Harmer
2.63
316311AC2-079 GEN
Solar/Wind Harmer
3.722
316132AB2-190 GEN1
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.197
316319Z2-044 C
Solar/Wind Harmer
0.403
315835AF2-110_GEN
Solar/Wind Harmer
0.908
316369SG1_INVT
Solar/Wind Harmer
1.296
315732AD1-074 GEN1
Solar/Wind Harmer
1.466
315733AD1-074 GEN2
Solar/Wind Harmer
1.466
315735AD1-075 GEN1
Solar/Wind Harmer
0.733
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
0.585
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.775
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316305AF2-043 C
Solar/Wind Harmer
0.216
316321Z2-027
Solar/Wind Harmer
0.193
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
313526AB2-022
Solar/Wind Harmer
0.193
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
972265AH1-717 GEN
Adder
4.91
3151201GRAVEL4
Adder
4.602
3151191GRAVEL3
Adder
4.544
3151211GRAVEL5
Adder
4.544
3152611GOSPORTB
Adder
0.805
3152621GOSPORTC
Adder
0.683
3152601GOSPORTA
Adder
0.63
971445AH1-216 GEN
Solar/Wind Harmer
4.395
3151081ELIZAR1
Adder
5.792
3151091ELIZAR2
Adder
5.691
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.103
3148013FISHERV
Solar/Wind Helper
0.098
3148463FAIRFLD
Solar/Wind Helper
0.118
3151931BEARGRDN S1
50/50
5.938
3151911BEARGRDN G1
50/50
4.601
3144293JTRSVLE
50/50
0.746
970119AG2-088 GEN
50/50
19.705
972003AH1-546 GEN
Solar/Wind Harmer
26.72
970937AG2-583 GEN
Solar/Wind Harmer
33.599
316322AB2-045
Solar/Wind Harmer
1.495
3146776BUCKING
Solar/Wind Harmer
-0.018
316336AC2-165 C
Solar/Wind Harmer
6.302
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.82
963171AG1-166 GEN
Solar/Wind Harmer
3.104
971563AH1-280 GEN
Solar/Wind Harmer
3.104
970685AG2-442 GEN
Solar/Wind Harmer
19.859
3143226MDLTHAN
Solar/Wind Harmer
-0.017
962491AG1-098 GEN
Solar/Wind Harmer
10.562
971377AH1-170 GEN
Solar/Wind Harmer
1.918
3147623JAMES R
Solar/Wind Harmer
0.237
315693AD1-088 GEN
Solar/Wind Harmer
7.599
316237AB2-079_GEN
Solar/Wind Harmer
0.453
3143526WINTERP
Solar/Wind Harmer
-0.071
957481AF2-042 GEN
Solar/Wind Harmer
38.757
970401AG2-262 GEN
Solar/Wind Harmer
0.805
315687AD1-152 GEN
Solar/Wind Harmer
1.355
3147043LAWRENC
Adder
0.898
971065AG2-659 GEN
Solar/Wind Harmer
5.572
316129AC1-054 GEN
Solar/Wind Harmer
0.96
971795AH1-408 GEN
Solar/Wind Harmer
7.936
3150851SPRUNCC
Adder
0.417
316003AC1-222 GEN
Solar/Wind Harmer
0.924
960081AF2-299 GEN
Solar/Wind Harmer
1.049
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
3142543TWELFTH
Solar/Wind Harmer
-0.001
970919AG2-571 GEN
Solar/Wind Harmer
2.65
970087AG2-069 GEN
Solar/Wind Harmer
7.82
316023GEN1_S
Solar/Wind Harmer
0.554
940641AE2-051 GEN
Solar/Wind Harmer
7.517
3143096IRON208
Adder
0.298
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.653
962571AG1-106 GEN
Solar/Wind Harmer
1.136
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
939411AE1-173 GEN
Solar/Wind Harmer
38.95
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.803
316212AC1-099_GEN
Solar/Wind Harmer
0.674
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.029
316381AD1-082 GEN
Solar/Wind Harmer
0.694
970661AG2-428 GEN
Solar/Wind Harmer
7.982
315722AD1-056 GEN
Solar/Wind Harmer
0.771
970129AG2-093 GEN
Solar/Wind Harmer
1.678
316458AB2-190 GEN2
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.827
3146233WITAKRS
Solar/Wind Harmer
-0.029
971069AG2-661 GEN
Solar/Wind Harmer
1.154
316093AE2-104_GEN
Solar/Wind Harmer
2.113
944631AF1-128 GEN
Adder
30.658
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.772
971647AH1-324 GEN
Solar/Wind Harmer
3.605
3151921BEARGRDN G2
50/50
4.601
3144293JTRSVLE
50/50
0.746
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
316313AB2-026
Solar/Wind Harmer
0.868
316258AE1-075 C
Solar/Wind Harmer
0.782
316405AF2-144 C
Solar/Wind Harmer
0.825
3143336POWHATN
Solar/Wind Harmer
3.247
942461AE2-259 GEN
Solar/Wind Harmer
4.59
970909AG2-566 GEN
Solar/Wind Harmer
2.539
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.45
963181AG1-167 GEN
Solar/Wind Harmer
2.328
959311AF2-222 GEN
Solar/Wind Harmer
22.003
970257AG2-171 GEN
Solar/Wind Harmer
7.661
315785AD2-033 C
Solar/Wind Harmer
4.427
964241AG1-285 GEN
Solar/Wind Harmer
13.397
316131AB2-060 GEN
Solar/Wind Harmer
1.694
970221AG2-151 GEN
Solar/Wind Harmer
9.59
316478AD1-087 GEN
Solar/Wind Harmer
1.073
316486AD2-202 GEN
Solar/Wind Harmer
0.314
3147043LAWRENC
Solar/Wind Harmer
-0.007
3150861SPRUNCD
Adder
0.417
316248AF1-058 C
Solar/Wind Harmer
0.306
960061AF2-297 GEN
Solar/Wind Harmer
5.079
966621AG1-532 GEN
Solar/Wind Harmer
0.189
313506AB2-031 GEN
Solar/Wind Harmer
0.727
971683AH1-343 GEN
Solar/Wind Harmer
3.823
970917AG2-570 GEN
Solar/Wind Harmer
20.936
316365GEN2_N
Solar/Wind Harmer
0.554
3143096IRON208
Adder
0.298
3143096IRON208
Adder
0.292
3156081AA2-088 GEN
Solar/Wind Harmer
2.589
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
315839AE2-212 C
Solar/Wind Harmer
0.237
957521AF2-046 GEN
Solar/Wind Harmer
6.176
961681AG1-008 GEN
Solar/Wind Harmer
6.176
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
965281AG1-393 GEN
Solar/Wind Harmer
0.97
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.214
315813AE1-149 C
Solar/Wind Harmer
4.801
316463AE2-346 GEN
Solar/Wind Harmer
0.124
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.959
316317KELFORD C
Solar/Wind Harmer
0.361
3145823KELFORD
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
0.714
316083AB2-161 GEN
Solar/Wind Harmer
1.228
970661AG2-428 GEN
Solar/Wind Harmer
1.415
316327AA2-057 GEN
Solar/Wind Harmer
0.756
3145273HOLLAND
Solar/Wind Harmer
-0.006
970133AG2-095 GEN
Solar/Wind Harmer
0.837
3156021HOLLOMANSOL
Solar/Wind Harmer
0.996
315724AD1-057 GEN
Solar/Wind Harmer
0.424
970129AG2-093 GEN
Solar/Wind Harmer
4.142
3146206CASHIE
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.153
3146233WITAKRS
Solar/Wind Harmer
-0.005
315778AD1-151 GEN
Solar/Wind Harmer
6.319
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.378
971157AH1-035 GEN
Solar/Wind Harmer
0.905
315614AA2-178 GEN
Solar/Wind Harmer
0.779
3146376EDENTON
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.298
961611AG1-000B GEN
Solar/Wind Harmer
1.508
316320Y1-086
Solar/Wind Harmer
0.418
3145963POPLR C
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151221GRAVEL6
Adder
4.597
3151171GRAVELC
Adder
0.884
3144873MCLAUGH
Solar/Wind Harmer
0
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.866
3144216WINCHST
Adder
0.221
3150921YORKTN3
Adder
1.456
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3148013FISHERV
Solar/Wind Helper
0.171
316499AE2-029_GEN
Solar/Wind Helper
0.503
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.534
3147666LOUISA
Solar/Wind Helper
0.265
944581AF1-123 GEN
Solar/Wind Harmer
1.127
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.775
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.535
316246AF1-032 C
Solar/Wind Harmer
0.145
3145963POPLR C
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
316174AB2-169 GEN
Solar/Wind Harmer
1.097
3151171GRAVELC
Adder
0.673
316375AC2-012 GEN
Solar/Wind Harmer
2.457
3145336SMITFLD
Solar/Wind Harmer
-0.028
3150981CHESPKA
Adder
0.789
944591AF1-124 GEN
Solar/Wind Harmer
32.38
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.798
3147666LOUISA
Solar/Wind Helper
0.46
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.75
3142956BIRDNECK
Solar/Wind Harmer
0.381
316316AC1-027 C
Solar/Wind Harmer
0.218
316236AE1-162_GEN
Solar/Wind Harmer
0.214
316036AC1-147 C
Solar/Wind Harmer
0.192
3150991CHESPKB
Adder
0.662
3150991CHESPKB
Adder
0.646
3150691DARBY 3
Adder
4.502
3150701DARBY 4
Adder
4.491
3150681DARBY 2
Adder
4.486
3150671DARBY 1
Adder
4.481
966001AG1-469 GEN
Solar/Wind Helper
0.186
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.012
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.013
LAGNLTFEXP_LAGN->PJM
CLTF
1.555
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.345
MECLTFEXP_MEC->PJM
CLTF
0.252
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.774
TVALTFEXP_TVA->PJM
CLTF
0.758
SIGELTFEXP_SIGE->PJM
CLTF
0.005
NYPJM->LTFIMP_NY
CLTF
0.536
LGEELTFEXP_LGEE->PJM
CLTF
0.012
CPLELTFEXP_CPLE->PJM
CLTF
3.992
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.116

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:157.52 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1069.03
MW Contribution:14.37
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
5.993
3144293JTRSVLE
50/50
0.881
3151591KERR 2
50/50
0.215
970413AG2-270 GEN
50/50
9.663
3151261ROARAP2
50/50
0.069
3146776BUCKING
Solar/Wind Harmer
0.182
3146926FARMVIL
Solar/Wind Harmer
0.234
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
970909AG2-566 GEN
Solar/Wind Harmer
3.007
3147133PAMPLIN
Solar/Wind Harmer
0.876
971193AH1-056 GEN
Solar/Wind Harmer
16.999
970221AG2-151 GEN
Solar/Wind Harmer
14.368
963181AG1-167 GEN
Solar/Wind Harmer
1.043
959311AF2-222 GEN
Solar/Wind Harmer
19.082
970257AG2-171 GEN
Solar/Wind Harmer
6.613
315785AD2-033 C
Solar/Wind Harmer
1.59
964241AG1-285 GEN
Solar/Wind Harmer
11.084
316131AB2-060 GEN
Solar/Wind Harmer
0.467
316478AD1-087 GEN
Solar/Wind Harmer
0.361
316486AD2-202 GEN
Solar/Wind Harmer
0.106
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.73
3147043LAWRENC
Solar/Wind Harmer
0.052
958131AF2-107 GEN
Solar/Wind Harmer
2.449
971683AH1-343 GEN
Solar/Wind Harmer
2.857
313506AB2-031 GEN
Solar/Wind Harmer
0.184
3144293JTRSVLE
50/50
0.881
3144293JTRSVLE
50/50
0.742
970535AG2-341 GEN
50/50
2.183
3152661PLYWOOD A
50/50
0.212
3146776BUCKING
Solar/Wind Harmer
2.017
3146776BUCKING
Solar/Wind Harmer
0.163
970301AG2-198 GEN
Solar/Wind Harmer
12.027
3147133PAMPLIN
Solar/Wind Harmer
0.279
3147133PAMPLIN
Solar/Wind Harmer
0.223
971489AH1-241 GEN
Solar/Wind Harmer
14.368
958211AF2-115 GEN
Solar/Wind Harmer
3.13
963191AG1-168 GEN
Solar/Wind Harmer
1.043
971741AH1-377 GEN
Solar/Wind Harmer
24.65
316034AC1-036 C
Solar/Wind Harmer
0.015
970323AG2-213 GEN
Solar/Wind Harmer
8.817
971775AH1-396 GEN
Solar/Wind Harmer
0.331
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
5.577
315821AE2-092 GEN
Solar/Wind Harmer
0.007
939181AE1-148 GEN
Solar/Wind Harmer
5.338
964791AG1-342 GEN
Solar/Wind Harmer
2.134
3146843MT LREL
Solar/Wind Harmer
0.111
3146843MT LREL
Solar/Wind Harmer
0.111
970099AG2-077 GEN
Solar/Wind Harmer
10.736
970933AG2-581 GEN
Solar/Wind Harmer
5.58
316181AB2-040 GEN
Solar/Wind Harmer
0.086
942751AE2-291 GEN
Solar/Wind Harmer
3.114
3145593CAROLNA
Solar/Wind Harmer
0.057
3145593CAROLNA
Solar/Wind Harmer
0.057
966811AG1-552 GEN
Solar/Wind Harmer
0.619
3145593CAROLNA
Solar/Wind Harmer
0.071
966001AG1-469 GEN
Solar/Wind Helper
0.14
3151931BEARGRDN S1
50/50
7.734
3151911BEARGRDN G1
50/50
5.993
3144293JTRSVLE
50/50
0.881
3151601KERR 3
50/50
0.215
3151581KERR 1
50/50
0.077
3151531CLOVER1
50/50
2.214
3147043LAWRENC
50/50
0.833
3151261ROARAP2
50/50
0.071
970937AG2-583 GEN
Solar/Wind Harmer
39.544
316336AC2-165 C
Solar/Wind Harmer
0.025
972003AH1-546 GEN
Solar/Wind Harmer
26.303
316322AB2-045
Solar/Wind Harmer
0.004
3146776BUCKING
Solar/Wind Harmer
0.202
3146926FARMVIL
Solar/Wind Harmer
0.234
971377AH1-170 GEN
Solar/Wind Harmer
2.874
3147623JAMES R
Solar/Wind Harmer
0.624
963171AG1-166 GEN
Solar/Wind Harmer
1.391
971563AH1-280 GEN
Solar/Wind Harmer
2.782
970685AG2-442 GEN
Solar/Wind Harmer
17.514
962491AG1-098 GEN
Solar/Wind Harmer
8.209
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
6.543
970401AG2-262 GEN
Solar/Wind Harmer
0.652
957481AF2-042 GEN
Solar/Wind Harmer
26.84
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.856
316129AC1-054 GEN
Solar/Wind Harmer
0.33
316003AC1-222 GEN
Solar/Wind Harmer
0.002
971795AH1-408 GEN
Solar/Wind Harmer
5.259
960081AF2-299 GEN
Solar/Wind Harmer
0.593
972205AH1-687 GEN
50/50
29.229
3151611KERR 4
50/50
0.215
3151621KERR 5
50/50
0.215
3151631KERR 6
50/50
0.215
3151641KERR 7
50/50
0.215
3151541CLOVER2
50/50
2.204
3151281ROARAP4
50/50
0.069
3151281ROARAP4
50/50
0.065
971845AH1-439 GEN
Solar/Wind Harmer
22.434
970285AG2-188 GEN
Solar/Wind Harmer
37.679
315657AE1-056 GEN
Solar/Wind Harmer
9.629
946301AF1-294 GEN
Solar/Wind Harmer
5.147
961791AG1-021 GEN
Solar/Wind Harmer
2.504
970683AG2-441 GEN
Solar/Wind Harmer
15.638
970681AG2-440 GEN
Solar/Wind Harmer
12.51
270494AE1-108_GEN
Solar/Wind Harmer
2.538
3144303KENBRDG
Solar/Wind Harmer
0.165
971443AH1-215 GEN
Solar/Wind Harmer
3.431
971447AH1-217 GEN
Solar/Wind Harmer
5.812
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.256
3147173SINAI
Solar/Wind Harmer
0.087
3147243WELCO
Solar/Wind Harmer
0.055
970831AG2-522 GEN
Solar/Wind Harmer
3.614
970865AG2-541 GEN
Solar/Wind Harmer
2.528
316123AC1-075 GEN
Solar/Wind Harmer
0.087
970165AG2-112 GEN
Solar/Wind Harmer
0.513
970163AG2-111 GEN
Solar/Wind Harmer
0.49
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.232
3138266HYDRAULIC
Solar/Wind Helper
0.014
3138266HYDRAULIC
Solar/Wind Helper
0.009
LAGNLTFEXP_LAGN->PJM
CLTF
1.359
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.534
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.133
MECLTFEXP_MEC->PJM
CLTF
0.325
SIGELTFEXP_SIGE->PJM
CLTF
0.008
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.117
TVALTFEXP_TVA->PJM
CLTF
0.671
NYPJM->LTFIMP_NY
CLTF
0.488
LGEELTFEXP_LGEE->PJM
CLTF
0.069
WECLTFEXP_WEC->PJM
CLTF
0.029
CPLELTFEXP_CPLE->PJM
CLTF
3.067
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.792

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 202712_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 202712_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:147.93 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1227.79
MW Contribution:18.92
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
29.229
971845AH1-439 GEN
Solar/Wind Harmer
29.538
970285AG2-188 GEN
Solar/Wind Harmer
46.824
315657AE1-056 GEN
Solar/Wind Harmer
11.763
946301AF1-294 GEN
Solar/Wind Harmer
7.51
961791AG1-021 GEN
Solar/Wind Harmer
3.664
970683AG2-441 GEN
Solar/Wind Harmer
20.59
970681AG2-440 GEN
Solar/Wind Harmer
16.472
270494AE1-108_GEN
Solar/Wind Harmer
6.187
3144303KENBRDG
Solar/Wind Harmer
-0.019
971443AH1-215 GEN
Solar/Wind Harmer
4.518
971447AH1-217 GEN
Solar/Wind Harmer
7.652
316239AB2-077_GEN
Solar/Wind Harmer
0.475
316238AB2-078_GEN
Solar/Wind Harmer
0.475
316118AC1-105 GEN
Solar/Wind Harmer
0.766
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
970831AG2-522 GEN
Solar/Wind Harmer
4.758
970865AG2-541 GEN
Solar/Wind Harmer
3.329
316123AC1-075 GEN
Solar/Wind Harmer
0.768
970165AG2-112 GEN
Solar/Wind Harmer
0.676
970163AG2-111 GEN
Solar/Wind Harmer
0.645
946281AF1-292 GEN
Solar/Wind Harmer
0.155
316087AB2-174 GEN
Solar/Wind Harmer
0.965
3137643SOCKMAN
Solar/Wind Harmer
-0.026
3138266HYDRAULIC
Solar/Wind Helper
0.014
3138266HYDRAULIC
Solar/Wind Helper
0.009
3151931BEARGRDN S1
50/50
7.734
3151911BEARGRDN G1
50/50
5.993
3144293JTRSVLE
50/50
0.881
970937AG2-583 GEN
Solar/Wind Harmer
52.066
316336AC2-165 C
Solar/Wind Harmer
12.588
972003AH1-546 GEN
Solar/Wind Harmer
34.691
316322AB2-045
Solar/Wind Harmer
1.907
3146776BUCKING
Solar/Wind Harmer
-0.022
3146926FARMVIL
Solar/Wind Harmer
-0.026
971377AH1-170 GEN
Solar/Wind Harmer
3.783
3147623JAMES R
Solar/Wind Harmer
0.468
963171AG1-166 GEN
Solar/Wind Harmer
3.664
971563AH1-280 GEN
Solar/Wind Harmer
3.664
970685AG2-442 GEN
Solar/Wind Harmer
23.061
962491AG1-098 GEN
Solar/Wind Harmer
10.808
316237AB2-079_GEN
Solar/Wind Harmer
0.475
315693AD1-088 GEN
Solar/Wind Harmer
7.658
970401AG2-262 GEN
Solar/Wind Harmer
0.815
957481AF2-042 GEN
Solar/Wind Harmer
35.339
315687AD1-152 GEN
Solar/Wind Harmer
1.264
971065AG2-659 GEN
Solar/Wind Harmer
5.078
316129AC1-054 GEN
Solar/Wind Harmer
0.863
3147043LAWRENC
Adder
0.785
316003AC1-222 GEN
Solar/Wind Harmer
0.902
971795AH1-408 GEN
Solar/Wind Harmer
6.647
960081AF2-299 GEN
Solar/Wind Harmer
0.78
3151921BEARGRDN G2
50/50
5.993
3144293JTRSVLE
50/50
0.881
3146776BUCKING
Solar/Wind Harmer
-0.02
3146926FARMVIL
Solar/Wind Harmer
-0.026
942461AE2-259 GEN
Solar/Wind Harmer
5.592
970909AG2-566 GEN
Solar/Wind Harmer
3.007
3147133PAMPLIN
Solar/Wind Harmer
-0.098
971193AH1-056 GEN
Solar/Wind Harmer
19.605
970221AG2-151 GEN
Solar/Wind Harmer
18.917
963181AG1-167 GEN
Solar/Wind Harmer
2.748
959311AF2-222 GEN
Solar/Wind Harmer
25.175
970257AG2-171 GEN
Solar/Wind Harmer
8.707
315785AD2-033 C
Solar/Wind Harmer
4.981
964241AG1-285 GEN
Solar/Wind Harmer
14.595
316131AB2-060 GEN
Solar/Wind Harmer
1.799
316478AD1-087 GEN
Solar/Wind Harmer
1.005
316486AD2-202 GEN
Solar/Wind Harmer
0.294
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.911
3147043LAWRENC
Solar/Wind Harmer
-0.006
958131AF2-107 GEN
Solar/Wind Harmer
3.26
971683AH1-343 GEN
Solar/Wind Harmer
3.762
966621AG1-532 GEN
Solar/Wind Harmer
0.141
313506AB2-031 GEN
Solar/Wind Harmer
0.538
3144293JTRSVLE
50/50
0.881
3144293JTRSVLE
50/50
0.742
970535AG2-341 GEN
50/50
2.183
3146776BUCKING
Solar/Wind Harmer
-0.226
3146776BUCKING
Solar/Wind Harmer
-0.018
970301AG2-198 GEN
Solar/Wind Harmer
15.836
3147133PAMPLIN
Solar/Wind Harmer
-0.031
3147133PAMPLIN
Solar/Wind Harmer
-0.025
971489AH1-241 GEN
Solar/Wind Harmer
17.959
958211AF2-115 GEN
Solar/Wind Harmer
4.579
963191AG1-168 GEN
Solar/Wind Harmer
2.748
971741AH1-377 GEN
Solar/Wind Harmer
32.456
316034AC1-036 C
Solar/Wind Harmer
0.432
970323AG2-213 GEN
Solar/Wind Harmer
11.609
971775AH1-396 GEN
Solar/Wind Harmer
1.653
313527AB2-043 GEN
Solar/Wind Harmer
2.63
962561AG1-105 GEN
Solar/Wind Harmer
7.343
315821AE2-092 GEN
Solar/Wind Harmer
2.71
939181AE1-148 GEN
Solar/Wind Harmer
7.029
964791AG1-342 GEN
Solar/Wind Harmer
2.668
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.136
970933AG2-581 GEN
Solar/Wind Harmer
7.348
316181AB2-040 GEN
Solar/Wind Harmer
0.933
942751AE2-291 GEN
Solar/Wind Harmer
4.1
3145593CAROLNA
Solar/Wind Harmer
-0.006
3145593CAROLNA
Solar/Wind Harmer
-0.006
966811AG1-552 GEN
Solar/Wind Harmer
0.721
3145593CAROLNA
Solar/Wind Harmer
0.053
966001AG1-469 GEN
Solar/Wind Helper
0.14
LAGNLTFEXP_LAGN->PJM
CLTF
1.359
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.534
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.133
MECLTFEXP_MEC->PJM
CLTF
0.325
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.117
TVALTFEXP_TVA->PJM
CLTF
0.671
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.488
LGEELTFEXP_LGEE->PJM
CLTF
0.069
WECLTFEXP_WEC->PJM
CLTF
0.029
CPLELTFEXP_CPLE->PJM
CLTF
3.067
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.792

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.86 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:765.97
MW Contribution:6.36
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.707
3151911BEARGRDN G1
50/50
4.422
3144293JTRSVLE
50/50
0.69
970119AG2-088 GEN
50/50
12.707
3151531CLOVER1
50/50
2.017
3151601KERR 3
50/50
0.192
3151581KERR 1
50/50
0.069
3147043LAWRENC
50/50
0.8
3151261ROARAP2
50/50
0.077
3150851SPRUNCC
50/50
0.297
3151051BRUNSWICKS1
50/50
1.63
3151021BRUNSWICKG1
50/50
0.785
971451AH1-221 GEN
50/50
2.385
315243AE2-183_GT3
50/50
0.972
972003AH1-546 GEN
Solar/Wind Harmer
19.447
970937AG2-583 GEN
Solar/Wind Harmer
23.874
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.151
3146926FARMVIL
Solar/Wind Harmer
0.178
316336AC2-165 C
Solar/Wind Harmer
0.011
3143336POWHATN
Solar/Wind Harmer
4.396
963171AG1-166 GEN
Solar/Wind Harmer
1.09
971563AH1-280 GEN
Solar/Wind Harmer
2.18
970685AG2-442 GEN
Solar/Wind Harmer
13.857
962491AG1-098 GEN
Solar/Wind Harmer
7.06
971377AH1-170 GEN
Solar/Wind Harmer
1.272
3147623JAMES R
Solar/Wind Harmer
0.276
315693AD1-088 GEN
Solar/Wind Harmer
5.685
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Harmer
0.095
970401AG2-262 GEN
Solar/Wind Harmer
0.559
957481AF2-042 GEN
Solar/Wind Harmer
24.966
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.579
316129AC1-054 GEN
Solar/Wind Harmer
0.309
3143526WINTERP
Solar/Wind Harmer
0.415
971795AH1-408 GEN
Solar/Wind Harmer
5.206
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.641
3145783HORNRTN
Solar/Wind Harmer
0.061
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
2.047
970087AG2-069 GEN
Solar/Wind Harmer
4.587
316023GEN1_S
Solar/Wind Harmer
0.127
3147983MERCK5
Solar/Wind Helper
0.057
972205AH1-687 GEN
50/50
21.569
316303AF2-085
50/50
1.694
3151541CLOVER2
50/50
2.007
3151611KERR 4
50/50
0.192
3151621KERR 5
50/50
0.192
3151631KERR 6
50/50
0.192
3151641KERR 7
50/50
0.192
3151281ROARAP4
50/50
0.075
3151281ROARAP4
50/50
0.07
971285AH1-108 GEN
50/50
0.486
963041AG1-153 GEN
50/50
1.59
315244AE2-183_ST
50/50
1.681
971845AH1-439 GEN
Solar/Wind Harmer
16.786
970285AG2-188 GEN
Solar/Wind Harmer
28.258
315657AE1-056 GEN
Solar/Wind Harmer
7.498
946301AF1-294 GEN
Solar/Wind Harmer
4.032
961791AG1-021 GEN
Solar/Wind Harmer
1.962
970683AG2-441 GEN
Solar/Wind Harmer
12.373
970681AG2-440 GEN
Solar/Wind Harmer
9.898
3144303KENBRDG
Solar/Wind Harmer
0.132
971443AH1-215 GEN
Solar/Wind Harmer
2.755
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Harmer
1.107
316118AC1-105 GEN
Solar/Wind Harmer
0.222
970831AG2-522 GEN
Solar/Wind Harmer
3.422
316233AE1-074 FULL
Solar/Wind Harmer
0.064
971281AH1-106 GEN
Solar/Wind Harmer
1.107
971283AH1-107 GEN
Solar/Wind Harmer
1.107
3147173SINAI
Solar/Wind Harmer
0.077
3147243WELCO
Solar/Wind Harmer
0.048
316087AB2-174 GEN
Solar/Wind Harmer
0.002
971967AH1-528 GEN
Solar/Wind Harmer
10.427
3137643SOCKMAN
Solar/Wind Harmer
0.253
970865AG2-541 GEN
Solar/Wind Harmer
2.127
315607AA1-063A GEN
Solar/Wind Harmer
0.122
3146043SEABORD
Solar/Wind Harmer
0.059
970673AG2-436 GEN
Solar/Wind Harmer
12.427
970673AG2-436 GEN
Solar/Wind Harmer
8.285
970085AG2-068 GEN
Solar/Wind Harmer
3.058
970581AG2-369 GEN
Solar/Wind Harmer
2.63
941031AE2-094 GEN
Solar/Wind Harmer
10.513
944011AF1-069 GEN
Solar/Wind Harmer
3.435
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.108
3148013FISHERV
Solar/Wind Helper
0.103
3148463FAIRFLD
Solar/Wind Helper
0.124
3151921BEARGRDN G2
50/50
4.422
3144293JTRSVLE
50/50
0.69
970413AG2-270 GEN
50/50
8.802
3151591KERR 2
50/50
0.192
3151261ROARAP2
50/50
0.076
3150861SPRUNCD
50/50
0.297
3151031BRUNSWICKG2
50/50
0.785
3146776BUCKING
Solar/Wind Harmer
0.136
3146926FARMVIL
Solar/Wind Harmer
0.178
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.156
316258AE1-075 C
Solar/Wind Harmer
0.187
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.737
970909AG2-566 GEN
Solar/Wind Harmer
2.353
3147133PAMPLIN
Solar/Wind Harmer
0.682
971193AH1-056 GEN
Solar/Wind Harmer
13.238
963181AG1-167 GEN
Solar/Wind Harmer
0.817
959311AF2-222 GEN
Solar/Wind Harmer
15.236
970257AG2-171 GEN
Solar/Wind Harmer
5.302
315785AD2-033 C
Solar/Wind Harmer
1.283
964241AG1-285 GEN
Solar/Wind Harmer
9.125
316131AB2-060 GEN
Solar/Wind Harmer
0.39
970221AG2-151 GEN
Solar/Wind Harmer
6.362
316478AD1-087 GEN
Solar/Wind Harmer
0.328
316486AD2-202 GEN
Solar/Wind Harmer
0.096
3147043LAWRENC
Solar/Wind Harmer
0.05
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.274
971683AH1-343 GEN
Solar/Wind Harmer
2.442
313506AB2-031 GEN
Solar/Wind Harmer
0.2
970917AG2-570 GEN
Solar/Wind Harmer
5.117
316365GEN2_N
Solar/Wind Harmer
0.127
3148013FISHERV
Solar/Wind Helper
0.18
316499AE2-029_GEN
Solar/Wind Helper
0.518
315616AA1-038_C
Solar/Wind Helper
0.562
3132273ORANGE
Solar/Wind Helper
0.024
3144293JTRSVLE
50/50
0.69
3144293JTRSVLE
50/50
0.581
970535AG2-341 GEN
50/50
1.885
3152661PLYWOOD A
50/50
0.185
3151041BRUNSWICKG3
50/50
0.785
972187AH1-678 GEN
50/50
1.802
315242AE2-183_GT2
50/50
0.972
315241AE2-183_GT1
50/50
0.966
972185AH1-677 GEN
50/50
3.505
970533AG2-339 GEN
50/50
5.074
970531AG2-338 GEN
50/50
2.029
3146776BUCKING
Solar/Wind Harmer
1.508
3146776BUCKING
Solar/Wind Harmer
0.122
970301AG2-198 GEN
Solar/Wind Harmer
9.412
3147133PAMPLIN
Solar/Wind Harmer
0.217
3147133PAMPLIN
Solar/Wind Harmer
0.174
958211AF2-115 GEN
Solar/Wind Harmer
2.452
963191AG1-168 GEN
Solar/Wind Harmer
0.817
971741AH1-377 GEN
Solar/Wind Harmer
19.558
316034AC1-036 C
Solar/Wind Harmer
0.012
970323AG2-213 GEN
Solar/Wind Harmer
7.069
971775AH1-396 GEN
Solar/Wind Harmer
0.265
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971489AH1-241 GEN
Solar/Wind Harmer
6.362
962561AG1-105 GEN
Solar/Wind Harmer
4.763
939181AE1-148 GEN
Solar/Wind Harmer
4.697
971223AH1-071 GEN
Solar/Wind Harmer
1.017
964791AG1-342 GEN
Solar/Wind Harmer
1.83
3146843MT LREL
Solar/Wind Harmer
0.095
3146843MT LREL
Solar/Wind Harmer
0.095
970099AG2-077 GEN
Solar/Wind Harmer
9.986
3143526WINTERP
Solar/Wind Harmer
0.415
970933AG2-581 GEN
Solar/Wind Harmer
5.925
316181AB2-040 GEN
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.062
3145593CAROLNA
Solar/Wind Harmer
0.062
966811AG1-552 GEN
Solar/Wind Harmer
0.675
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.086
3145783HORNRTN
Solar/Wind Harmer
0.869
3145783HORNRTN
Solar/Wind Harmer
0.271
3145783HORNRTN
Solar/Wind Harmer
0.109
316426AA2-053 GEN
Solar/Wind Harmer
0.204
966001AG1-469 GEN
Solar/Wind Helper
0.174
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.118
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.349
LAGNLTFEXP_LAGN->PJM
CLTF
0.897
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.208
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.783
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.427
NYPJM->LTFIMP_NY
CLTF
0.345
CPLELTFEXP_CPLE->PJM
CLTF
3.08
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.625
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:112.65 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:934.97
MW Contribution:8.46
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.702
3144293JTRSVLE
50/50
0.591
3146776BUCKING
Solar/Wind Harmer
-0.17
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.577
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.65
963191AG1-168 GEN
Solar/Wind Harmer
2.19
971741AH1-377 GEN
Solar/Wind Harmer
26.202
316034AC1-036 C
Solar/Wind Harmer
0.354
970323AG2-213 GEN
Solar/Wind Harmer
9.526
971775AH1-396 GEN
Solar/Wind Harmer
1.357
313527AB2-043 GEN
Solar/Wind Harmer
2.287
971489AH1-241 GEN
Solar/Wind Harmer
8.033
962561AG1-105 GEN
Solar/Wind Harmer
6.548
939181AE1-148 GEN
Solar/Wind Harmer
6.48
964791AG1-342 GEN
Solar/Wind Harmer
2.393
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.726
971223AH1-071 GEN
Solar/Wind Harmer
1.368
3143526WINTERP
Solar/Wind Harmer
-0.048
970933AG2-581 GEN
Solar/Wind Harmer
8.213
316181AB2-040 GEN
Solar/Wind Harmer
1.084
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.846
3145593CAROLNA
Solar/Wind Harmer
0.062
3145783HORNRTN
Solar/Wind Harmer
0.879
3145783HORNRTN
Solar/Wind Harmer
0.703
3145783HORNRTN
Solar/Wind Harmer
0.22
3145783HORNRTN
Solar/Wind Harmer
0.088
316426AA2-053 GEN
Solar/Wind Harmer
0.74
972187AH1-678 GEN
Adder
1.814
972185AH1-677 GEN
Adder
3.525
316274AC1-208 GEN
Solar/Wind Harmer
0.733
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.184
3145796HORNRTN
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.012
316222AC1-221 GEN
Solar/Wind Harmer
0.66
3146173TUNIS
Solar/Wind Harmer
-0.006
3146173TUNIS
Solar/Wind Harmer
-0.006
3144356SAPONY
Solar/Wind Harmer
0.227
966001AG1-469 GEN
Solar/Wind Helper
0.172
972205AH1-687 GEN
50/50
21.638
971845AH1-439 GEN
Solar/Wind Harmer
22.236
970285AG2-188 GEN
Solar/Wind Harmer
35.347
315657AE1-056 GEN
Solar/Wind Harmer
9.306
946301AF1-294 GEN
Solar/Wind Harmer
5.986
961791AG1-021 GEN
Solar/Wind Harmer
2.92
970683AG2-441 GEN
Solar/Wind Harmer
16.617
970681AG2-440 GEN
Solar/Wind Harmer
13.294
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.713
316239AB2-077_GEN
Solar/Wind Harmer
0.415
316238AB2-078_GEN
Solar/Wind Harmer
0.415
270494AE1-108_GEN
Solar/Wind Harmer
2.712
316118AC1-105 GEN
Solar/Wind Harmer
0.698
970831AG2-522 GEN
Solar/Wind Harmer
4.772
316233AE1-074 FULL
Solar/Wind Harmer
0.248
971281AH1-106 GEN
Solar/Wind Harmer
1.497
971283AH1-107 GEN
Solar/Wind Harmer
1.497
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
946281AF1-292 GEN
Solar/Wind Harmer
0.179
316087AB2-174 GEN
Solar/Wind Harmer
1.119
971967AH1-528 GEN
Solar/Wind Harmer
14.578
3137643SOCKMAN
Solar/Wind Harmer
-0.03
970865AG2-541 GEN
Solar/Wind Harmer
2.95
315607AA1-063A GEN
Solar/Wind Harmer
0.728
3146043SEABORD
Solar/Wind Harmer
-0.007
971285AH1-108 GEN
Adder
0.475
970673AG2-436 GEN
Solar/Wind Harmer
14.663
970673AG2-436 GEN
Solar/Wind Harmer
7.425
970085AG2-068 GEN
Solar/Wind Harmer
4.347
970581AG2-369 GEN
Solar/Wind Harmer
3.738
941031AE2-094 GEN
Solar/Wind Harmer
12.804
944011AF1-069 GEN
Solar/Wind Harmer
4.012
965291AG1-394 GEN
Solar/Wind Harmer
0.596
315652AC1-086 GEN
Solar/Wind Harmer
7.525
316318V4-068
Solar/Wind Harmer
0.165
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.026
315814AE2-033 C
Solar/Wind Harmer
6.071
316315AB2-025 C
Solar/Wind Harmer
0.175
3145513AHOSKIE
Solar/Wind Harmer
0.056
961941AG1-037 GEN
Solar/Wind Harmer
0.049
3145513AHOSKIE
Solar/Wind Harmer
-0.006
3145683EARLEYS
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.006
3145683EARLEYS
Solar/Wind Harmer
-0.006
316319Z2-044 C
Solar/Wind Harmer
0.351
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.108
3148013FISHERV
Solar/Wind Helper
0.103
3148463FAIRFLD
Solar/Wind Helper
0.125
3151931BEARGRDN S1
50/50
5.725
3151911BEARGRDN G1
50/50
4.436
3144293JTRSVLE
50/50
0.702
972003AH1-546 GEN
Solar/Wind Harmer
25.74
970937AG2-583 GEN
Solar/Wind Harmer
31.567
316322AB2-045
Solar/Wind Harmer
1.434
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.02
316336AC2-165 C
Solar/Wind Harmer
5.64
3143336POWHATN
Solar/Wind Harmer
3.322
963171AG1-166 GEN
Solar/Wind Harmer
2.92
971563AH1-280 GEN
Solar/Wind Harmer
2.92
970685AG2-442 GEN
Solar/Wind Harmer
18.611
962491AG1-098 GEN
Solar/Wind Harmer
9.593
316237AB2-079_GEN
Solar/Wind Harmer
0.415
315693AD1-088 GEN
Solar/Wind Harmer
6.877
971377AH1-170 GEN
Solar/Wind Harmer
1.692
3147623JAMES R
Solar/Wind Harmer
0.209
970401AG2-262 GEN
Solar/Wind Harmer
0.731
957481AF2-042 GEN
Solar/Wind Harmer
34.315
3143226MDLTHAN
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
1.213
971065AG2-659 GEN
Solar/Wind Harmer
4.98
3147043LAWRENC
Adder
0.793
316129AC1-054 GEN
Solar/Wind Harmer
0.856
971795AH1-408 GEN
Solar/Wind Harmer
6.949
3143526WINTERP
Solar/Wind Harmer
-0.048
316003AC1-222 GEN
Solar/Wind Harmer
0.825
960081AF2-299 GEN
Solar/Wind Harmer
0.9
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.09
3150851SPRUNCC
Adder
0.29
970919AG2-571 GEN
Solar/Wind Harmer
2.207
970087AG2-069 GEN
Solar/Wind Harmer
6.521
316023GEN1_S
Solar/Wind Harmer
0.461
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.4
962571AG1-106 GEN
Solar/Wind Harmer
0.962
316212AC1-099_GEN
Solar/Wind Harmer
0.58
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.196
3146173TUNIS
Solar/Wind Harmer
-0.006
3145823KELFORD
Solar/Wind Harmer
-0.006
3145683EARLEYS
Solar/Wind Harmer
-0.006
3146233WITAKRS
Solar/Wind Harmer
-0.025
315722AD1-056 GEN
Solar/Wind Harmer
0.666
940641AE2-051 GEN
Solar/Wind Harmer
5.935
3147983MERCK5
Solar/Wind Helper
0.057
3151921BEARGRDN G2
50/50
4.436
3144293JTRSVLE
50/50
0.702
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
942461AE2-259 GEN
Solar/Wind Harmer
4.35
316313AB2-026
Solar/Wind Harmer
0.755
316258AE1-075 C
Solar/Wind Harmer
0.68
316405AF2-144 C
Solar/Wind Harmer
0.717
3143336POWHATN
Solar/Wind Harmer
2.824
970909AG2-566 GEN
Solar/Wind Harmer
2.388
3147133PAMPLIN
Solar/Wind Harmer
-0.078
971193AH1-056 GEN
Solar/Wind Harmer
15.51
963181AG1-167 GEN
Solar/Wind Harmer
2.19
959311AF2-222 GEN
Solar/Wind Harmer
20.551
970257AG2-171 GEN
Solar/Wind Harmer
7.144
315785AD2-033 C
Solar/Wind Harmer
4.119
964241AG1-285 GEN
Solar/Wind Harmer
12.377
316131AB2-060 GEN
Solar/Wind Harmer
1.556
970221AG2-151 GEN
Solar/Wind Harmer
8.461
316478AD1-087 GEN
Solar/Wind Harmer
0.958
316486AD2-202 GEN
Solar/Wind Harmer
0.28
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.275
960061AF2-297 GEN
Solar/Wind Harmer
4.563
966621AG1-532 GEN
Solar/Wind Harmer
0.162
971683AH1-343 GEN
Solar/Wind Harmer
3.393
313506AB2-031 GEN
Solar/Wind Harmer
0.625
3150861SPRUNCD
Adder
0.29
970917AG2-570 GEN
Solar/Wind Harmer
17.439
316365GEN2_N
Solar/Wind Harmer
0.461
3146263WOODLND
Solar/Wind Harmer
-0.007
3156081AA2-088 GEN
Solar/Wind Harmer
2.164
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316210AC1-098 GEN
Solar/Wind Harmer
1.044
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.046
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.183
961681AG1-008 GEN
Solar/Wind Harmer
5.183
3146173TUNIS
Solar/Wind Harmer
-0.006
316327AA2-057 GEN
Solar/Wind Harmer
0.657
316317KELFORD C
Solar/Wind Harmer
0.306
3145823KELFORD
Solar/Wind Harmer
-0.006
316283AC2-100 C
Solar/Wind Harmer
0.608
316463AE2-346 GEN
Solar/Wind Harmer
0.104
316140AB2-099
Solar/Wind Harmer
0.044
962331AG1-082 GEN
Solar/Wind Harmer
0.807
3146233WITAKRS
Solar/Wind Harmer
0.133
3146233WITAKRS
Solar/Wind Harmer
-0.004
315724AD1-057 GEN
Solar/Wind Harmer
0.366
3138543CONSLDL
Solar/Wind Harmer
-0.004
3148013FISHERV
Solar/Wind Helper
0.18
316499AE2-029_GEN
Solar/Wind Helper
0.518
315616AA1-038_C
Solar/Wind Helper
0.568
3132273ORANGE
Solar/Wind Helper
0.023
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.137
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.398
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.933
MECLTFEXP_MEC->PJM
CLTF
0.009
LAGNLTFEXP_LAGN->PJM
CLTF
1.413
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.319
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.666
CPLELTFEXP_CPLE->PJM
CLTF
3.817
NYPJM->LTFIMP_NY
CLTF
0.342
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.59
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2066-282_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2066-282_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.36 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:916.0
MW Contribution:8.91
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
21.959
316303AF2-085
50/50
2.192
971845AH1-439 GEN
Solar/Wind Harmer
22.482
970285AG2-188 GEN
Solar/Wind Harmer
35.716
315657AE1-056 GEN
Solar/Wind Harmer
9.289
946301AF1-294 GEN
Solar/Wind Harmer
5.962
961791AG1-021 GEN
Solar/Wind Harmer
2.908
970683AG2-441 GEN
Solar/Wind Harmer
16.495
970681AG2-440 GEN
Solar/Wind Harmer
13.196
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.668
316239AB2-077_GEN
Solar/Wind Harmer
0.403
316238AB2-078_GEN
Solar/Wind Harmer
0.403
270494AE1-108_GEN
Solar/Wind Harmer
2.875
3151921BEARGRDN G2
50/50
4.502
3144293JTRSVLE
50/50
0.7
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.811
316258AE1-075 C
Solar/Wind Harmer
0.73
316405AF2-144 C
Solar/Wind Harmer
0.77
3143336POWHATN
Solar/Wind Harmer
3.032
942461AE2-259 GEN
Solar/Wind Harmer
4.363
970909AG2-566 GEN
Solar/Wind Harmer
2.388
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.482
963181AG1-167 GEN
Solar/Wind Harmer
2.181
959311AF2-222 GEN
Solar/Wind Harmer
20.337
970257AG2-171 GEN
Solar/Wind Harmer
7.06
315785AD2-033 C
Solar/Wind Harmer
4.062
964241AG1-285 GEN
Solar/Wind Harmer
12.123
970221AG2-151 GEN
Solar/Wind Harmer
8.911
316131AB2-060 GEN
Solar/Wind Harmer
1.517
316478AD1-087 GEN
Solar/Wind Harmer
0.922
316486AD2-202 GEN
Solar/Wind Harmer
0.27
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.261
960061AF2-297 GEN
Solar/Wind Harmer
4.339
971683AH1-343 GEN
Solar/Wind Harmer
3.24
966621AG1-532 GEN
Solar/Wind Harmer
0.148
313506AB2-031 GEN
Solar/Wind Harmer
0.568
970917AG2-570 GEN
Solar/Wind Harmer
16.142
3148013FISHERV
Solar/Wind Helper
0.177
316499AE2-029_GEN
Solar/Wind Helper
0.512
315616AA1-038_C
Solar/Wind Helper
0.557
3132273ORANGE
Solar/Wind Helper
0.023
3151931BEARGRDN S1
50/50
5.81
3151911BEARGRDN G1
50/50
4.502
3144293JTRSVLE
50/50
0.7
970119AG2-088 GEN
50/50
16.441
972003AH1-546 GEN
Solar/Wind Harmer
26.109
970937AG2-583 GEN
Solar/Wind Harmer
32.485
316322AB2-045
Solar/Wind Harmer
1.45
3146776BUCKING
Solar/Wind Harmer
-0.017
316336AC2-165 C
Solar/Wind Harmer
5.96
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.567
963171AG1-166 GEN
Solar/Wind Harmer
2.908
971563AH1-280 GEN
Solar/Wind Harmer
2.908
970685AG2-442 GEN
Solar/Wind Harmer
18.475
971377AH1-170 GEN
Solar/Wind Harmer
1.782
3147623JAMES R
Solar/Wind Harmer
0.221
962491AG1-098 GEN
Solar/Wind Harmer
9.39
3143226MDLTHAN
Solar/Wind Harmer
-0.014
315693AD1-088 GEN
Solar/Wind Harmer
6.718
316237AB2-079_GEN
Solar/Wind Harmer
0.403
970401AG2-262 GEN
Solar/Wind Harmer
0.704
957481AF2-042 GEN
Solar/Wind Harmer
33.096
315687AD1-152 GEN
Solar/Wind Harmer
1.157
971065AG2-659 GEN
Solar/Wind Harmer
4.696
3147043LAWRENC
Adder
0.745
316129AC1-054 GEN
Solar/Wind Harmer
0.805
971795AH1-408 GEN
Solar/Wind Harmer
6.476
316003AC1-222 GEN
Solar/Wind Harmer
0.786
960081AF2-299 GEN
Solar/Wind Harmer
0.821
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.081
970919AG2-571 GEN
Solar/Wind Harmer
2.043
970087AG2-069 GEN
Solar/Wind Harmer
6.029
3147983MERCK5
Solar/Wind Helper
0.056
316118AC1-105 GEN
Solar/Wind Harmer
0.668
970831AG2-522 GEN
Solar/Wind Harmer
4.476
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
971967AH1-528 GEN
Solar/Wind Harmer
13.768
946281AF1-292 GEN
Solar/Wind Harmer
0.164
316087AB2-174 GEN
Solar/Wind Harmer
1.019
970865AG2-541 GEN
Solar/Wind Harmer
2.825
3137643SOCKMAN
Solar/Wind Harmer
-0.028
970673AG2-436 GEN
Solar/Wind Harmer
13.72
970673AG2-436 GEN
Solar/Wind Harmer
6.947
315607AA1-063A GEN
Solar/Wind Harmer
0.655
3146043SEABORD
Solar/Wind Harmer
-0.006
970085AG2-068 GEN
Solar/Wind Harmer
4.019
970581AG2-369 GEN
Solar/Wind Harmer
3.457
941031AE2-094 GEN
Solar/Wind Harmer
11.99
944011AF1-069 GEN
Solar/Wind Harmer
3.757
971447AH1-217 GEN
Solar/Wind Harmer
2.264
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.102
3148463FAIRFLD
Solar/Wind Helper
0.123
3144293JTRSVLE
50/50
0.7
3144293JTRSVLE
50/50
0.589
3146776BUCKING
Solar/Wind Harmer
-0.172
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.575
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.636
963191AG1-168 GEN
Solar/Wind Harmer
2.181
971741AH1-377 GEN
Solar/Wind Harmer
26.113
316034AC1-036 C
Solar/Wind Harmer
0.35
970323AG2-213 GEN
Solar/Wind Harmer
9.413
971775AH1-396 GEN
Solar/Wind Harmer
1.34
971489AH1-241 GEN
Solar/Wind Harmer
8.46
971223AH1-071 GEN
Solar/Wind Harmer
1.732
313527AB2-043 GEN
Solar/Wind Harmer
2.226
962561AG1-105 GEN
Solar/Wind Harmer
6.315
939181AE1-148 GEN
Solar/Wind Harmer
6.206
964791AG1-342 GEN
Solar/Wind Harmer
2.303
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.238
970933AG2-581 GEN
Solar/Wind Harmer
7.823
316181AB2-040 GEN
Solar/Wind Harmer
0.986
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.766
3145593CAROLNA
Solar/Wind Harmer
0.057
972187AH1-678 GEN
Adder
1.696
3145783HORNRTN
Solar/Wind Harmer
0.793
3145783HORNRTN
Solar/Wind Harmer
0.635
3145783HORNRTN
Solar/Wind Harmer
0.198
3145783HORNRTN
Solar/Wind Harmer
0.079
316426AA2-053 GEN
Solar/Wind Harmer
0.667
972185AH1-677 GEN
Adder
3.297
966001AG1-469 GEN
Solar/Wind Helper
0.17
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.108
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.318
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.251
LAGNLTFEXP_LAGN->PJM
CLTF
0.917
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.775
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.437
CPLELTFEXP_CPLE->PJM
CLTF
3.065
NYPJM->LTFIMP_NY
CLTF
0.338
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.788
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 219-282_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 219-282_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.03 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:913.26
MW Contribution:8.91
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.589
3146776BUCKING
Solar/Wind Harmer
-0.172
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.574
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.635
963191AG1-168 GEN
Solar/Wind Harmer
2.181
971741AH1-377 GEN
Solar/Wind Harmer
26.109
316034AC1-036 C
Solar/Wind Harmer
0.35
970323AG2-213 GEN
Solar/Wind Harmer
9.412
971775AH1-396 GEN
Solar/Wind Harmer
1.34
971489AH1-241 GEN
Solar/Wind Harmer
8.458
3143526WINTERP
Solar/Wind Harmer
-0.072
971223AH1-071 GEN
Solar/Wind Harmer
1.731
313527AB2-043 GEN
Solar/Wind Harmer
2.225
962561AG1-105 GEN
Solar/Wind Harmer
6.313
939181AE1-148 GEN
Solar/Wind Harmer
6.204
964791AG1-342 GEN
Solar/Wind Harmer
2.302
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.234
970933AG2-581 GEN
Solar/Wind Harmer
7.82
316181AB2-040 GEN
Solar/Wind Harmer
0.986
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.766
3145593CAROLNA
Solar/Wind Harmer
0.057
972187AH1-678 GEN
Adder
1.695
3145783HORNRTN
Solar/Wind Harmer
0.793
3145783HORNRTN
Solar/Wind Harmer
0.634
3145783HORNRTN
Solar/Wind Harmer
0.198
3145783HORNRTN
Solar/Wind Harmer
0.079
316426AA2-053 GEN
Solar/Wind Harmer
0.667
972185AH1-677 GEN
Adder
3.295
966001AG1-469 GEN
Solar/Wind Helper
0.17
972205AH1-687 GEN
50/50
21.958
316303AF2-085
50/50
2.192
971845AH1-439 GEN
Solar/Wind Harmer
22.48
970285AG2-188 GEN
Solar/Wind Harmer
35.714
315657AE1-056 GEN
Solar/Wind Harmer
9.288
946301AF1-294 GEN
Solar/Wind Harmer
5.962
961791AG1-021 GEN
Solar/Wind Harmer
2.908
970683AG2-441 GEN
Solar/Wind Harmer
16.493
970681AG2-440 GEN
Solar/Wind Harmer
13.194
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.667
316233AE1-074 FULL
Solar/Wind Harmer
0.373
971281AH1-106 GEN
Solar/Wind Harmer
2.251
971283AH1-107 GEN
Solar/Wind Harmer
2.251
316239AB2-077_GEN
Solar/Wind Harmer
0.403
316238AB2-078_GEN
Solar/Wind Harmer
0.403
270494AE1-108_GEN
Solar/Wind Harmer
2.874
316118AC1-105 GEN
Solar/Wind Harmer
0.668
970831AG2-522 GEN
Solar/Wind Harmer
4.474
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
971967AH1-528 GEN
Solar/Wind Harmer
13.762
946281AF1-292 GEN
Solar/Wind Harmer
0.163
316087AB2-174 GEN
Solar/Wind Harmer
1.018
970865AG2-541 GEN
Solar/Wind Harmer
2.824
3137643SOCKMAN
Solar/Wind Harmer
-0.028
970673AG2-436 GEN
Solar/Wind Harmer
13.713
970673AG2-436 GEN
Solar/Wind Harmer
6.943
315607AA1-063A GEN
Solar/Wind Harmer
0.655
3146043SEABORD
Solar/Wind Harmer
-0.006
970085AG2-068 GEN
Solar/Wind Harmer
4.017
970581AG2-369 GEN
Solar/Wind Harmer
3.455
941031AE2-094 GEN
Solar/Wind Harmer
11.984
944011AF1-069 GEN
Solar/Wind Harmer
3.755
971447AH1-217 GEN
Solar/Wind Harmer
2.263
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.102
3148463FAIRFLD
Solar/Wind Helper
0.123
3151931BEARGRDN S1
50/50
5.81
3151911BEARGRDN G1
50/50
4.502
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
16.437
972003AH1-546 GEN
Solar/Wind Harmer
26.108
970937AG2-583 GEN
Solar/Wind Harmer
32.483
316322AB2-045
Solar/Wind Harmer
1.45
3146776BUCKING
Solar/Wind Harmer
-0.017
316336AC2-165 C
Solar/Wind Harmer
5.96
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.567
963171AG1-166 GEN
Solar/Wind Harmer
2.908
971563AH1-280 GEN
Solar/Wind Harmer
2.908
970685AG2-442 GEN
Solar/Wind Harmer
18.472
971377AH1-170 GEN
Solar/Wind Harmer
1.782
3147623JAMES R
Solar/Wind Harmer
0.221
962491AG1-098 GEN
Solar/Wind Harmer
9.388
3143526WINTERP
Solar/Wind Harmer
-0.072
3143226MDLTHAN
Solar/Wind Harmer
-0.014
315693AD1-088 GEN
Solar/Wind Harmer
6.716
316237AB2-079_GEN
Solar/Wind Harmer
0.403
970401AG2-262 GEN
Solar/Wind Harmer
0.703
957481AF2-042 GEN
Solar/Wind Harmer
33.086
315687AD1-152 GEN
Solar/Wind Harmer
1.156
971065AG2-659 GEN
Solar/Wind Harmer
4.694
3147043LAWRENC
Adder
0.744
316129AC1-054 GEN
Solar/Wind Harmer
0.804
971795AH1-408 GEN
Solar/Wind Harmer
6.473
316003AC1-222 GEN
Solar/Wind Harmer
0.786
960081AF2-299 GEN
Solar/Wind Harmer
0.821
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.081
970919AG2-571 GEN
Solar/Wind Harmer
2.042
970087AG2-069 GEN
Solar/Wind Harmer
6.026
3147983MERCK5
Solar/Wind Helper
0.056
3151921BEARGRDN G2
50/50
4.502
3144293JTRSVLE
50/50
0.699
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.811
316258AE1-075 C
Solar/Wind Harmer
0.73
316405AF2-144 C
Solar/Wind Harmer
0.77
3143336POWHATN
Solar/Wind Harmer
3.032
942461AE2-259 GEN
Solar/Wind Harmer
4.363
970909AG2-566 GEN
Solar/Wind Harmer
2.387
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.48
963181AG1-167 GEN
Solar/Wind Harmer
2.181
959311AF2-222 GEN
Solar/Wind Harmer
20.333
970257AG2-171 GEN
Solar/Wind Harmer
7.059
315785AD2-033 C
Solar/Wind Harmer
4.061
964241AG1-285 GEN
Solar/Wind Harmer
12.12
970221AG2-151 GEN
Solar/Wind Harmer
8.909
316131AB2-060 GEN
Solar/Wind Harmer
1.516
316478AD1-087 GEN
Solar/Wind Harmer
0.922
316486AD2-202 GEN
Solar/Wind Harmer
0.27
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.261
960061AF2-297 GEN
Solar/Wind Harmer
4.337
971683AH1-343 GEN
Solar/Wind Harmer
3.239
966621AG1-532 GEN
Solar/Wind Harmer
0.148
313506AB2-031 GEN
Solar/Wind Harmer
0.568
970917AG2-570 GEN
Solar/Wind Harmer
16.134
3148013FISHERV
Solar/Wind Helper
0.177
316499AE2-029_GEN
Solar/Wind Helper
0.512
315616AA1-038_C
Solar/Wind Helper
0.557
3132273ORANGE
Solar/Wind Helper
0.023
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.11
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.323
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.243
LAGNLTFEXP_LAGN->PJM
CLTF
0.913
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.768
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.435
CPLELTFEXP_CPLE->PJM
CLTF
3.062
NYPJM->LTFIMP_NY
CLTF
0.339
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.758
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P2-2: DOOMS B2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: DOOMS B2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:106.13 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:880.86
MW Contribution:9.92
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.707
3144293JTRSVLE
50/50
0.595
3146776BUCKING
Solar/Wind Harmer
-0.173
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.692
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.674
963191AG1-168 GEN
Solar/Wind Harmer
2.204
971741AH1-377 GEN
Solar/Wind Harmer
26.373
316034AC1-036 C
Solar/Wind Harmer
0.354
970323AG2-213 GEN
Solar/Wind Harmer
9.533
971775AH1-396 GEN
Solar/Wind Harmer
1.358
971489AH1-241 GEN
Solar/Wind Harmer
9.417
313527AB2-043 GEN
Solar/Wind Harmer
2.264
962561AG1-105 GEN
Solar/Wind Harmer
6.428
939181AE1-148 GEN
Solar/Wind Harmer
6.336
964791AG1-342 GEN
Solar/Wind Harmer
2.344
971223AH1-071 GEN
Solar/Wind Harmer
1.371
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.47
315821AE2-092 GEN
Solar/Wind Harmer
1.938
3143526WINTERP
Solar/Wind Harmer
-0.048
970933AG2-581 GEN
Solar/Wind Harmer
7.992
316181AB2-040 GEN
Solar/Wind Harmer
1.038
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.805
3145593CAROLNA
Solar/Wind Harmer
0.059
3145783HORNRTN
Solar/Wind Harmer
0.834
3145783HORNRTN
Solar/Wind Harmer
0.667
3145783HORNRTN
Solar/Wind Harmer
0.209
3145783HORNRTN
Solar/Wind Harmer
0.083
316426AA2-053 GEN
Solar/Wind Harmer
0.703
972187AH1-678 GEN
Adder
1.74
972185AH1-677 GEN
Adder
3.384
316274AC1-208 GEN
Solar/Wind Harmer
0.685
966001AG1-469 GEN
Solar/Wind Helper
0.173
972205AH1-687 GEN
50/50
22.086
971845AH1-439 GEN
Solar/Wind Harmer
22.632
970285AG2-188 GEN
Solar/Wind Harmer
35.96
315657AE1-056 GEN
Solar/Wind Harmer
9.382
946301AF1-294 GEN
Solar/Wind Harmer
6.025
961791AG1-021 GEN
Solar/Wind Harmer
2.939
970683AG2-441 GEN
Solar/Wind Harmer
16.685
970681AG2-440 GEN
Solar/Wind Harmer
13.348
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.715
316239AB2-077_GEN
Solar/Wind Harmer
0.41
316238AB2-078_GEN
Solar/Wind Harmer
0.41
270494AE1-108_GEN
Solar/Wind Harmer
3.2
316118AC1-105 GEN
Solar/Wind Harmer
0.68
971447AH1-217 GEN
Solar/Wind Harmer
3.32
970831AG2-522 GEN
Solar/Wind Harmer
4.615
316233AE1-074 FULL
Solar/Wind Harmer
0.247
971281AH1-106 GEN
Solar/Wind Harmer
1.493
971283AH1-107 GEN
Solar/Wind Harmer
1.493
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
946281AF1-292 GEN
Solar/Wind Harmer
0.172
316087AB2-174 GEN
Solar/Wind Harmer
1.072
971967AH1-528 GEN
Solar/Wind Harmer
14.102
3137643SOCKMAN
Solar/Wind Harmer
-0.029
970865AG2-541 GEN
Solar/Wind Harmer
2.881
971285AH1-108 GEN
Adder
0.469
315607AA1-063A GEN
Solar/Wind Harmer
0.692
3146043SEABORD
Solar/Wind Harmer
-0.007
970673AG2-436 GEN
Solar/Wind Harmer
14.087
970673AG2-436 GEN
Solar/Wind Harmer
7.133
970085AG2-068 GEN
Solar/Wind Harmer
4.125
970581AG2-369 GEN
Solar/Wind Harmer
3.547
941031AE2-094 GEN
Solar/Wind Harmer
12.32
944011AF1-069 GEN
Solar/Wind Harmer
3.86
965291AG1-394 GEN
Solar/Wind Harmer
0.567
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.128
3148013FISHERV
Solar/Wind Helper
0.123
3148463FAIRFLD
Solar/Wind Helper
0.129
3151931BEARGRDN S1
50/50
5.844
3151911BEARGRDN G1
50/50
4.528
3144293JTRSVLE
50/50
0.707
972003AH1-546 GEN
Solar/Wind Harmer
26.264
970937AG2-583 GEN
Solar/Wind Harmer
32.188
316322AB2-045
Solar/Wind Harmer
1.459
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.02
316336AC2-165 C
Solar/Wind Harmer
5.739
3143336POWHATN
Solar/Wind Harmer
3.376
963171AG1-166 GEN
Solar/Wind Harmer
2.939
971563AH1-280 GEN
Solar/Wind Harmer
2.939
970685AG2-442 GEN
Solar/Wind Harmer
18.688
971377AH1-170 GEN
Solar/Wind Harmer
1.984
3147623JAMES R
Solar/Wind Harmer
0.245
962491AG1-098 GEN
Solar/Wind Harmer
9.522
315693AD1-088 GEN
Solar/Wind Harmer
6.816
316237AB2-079_GEN
Solar/Wind Harmer
0.41
970401AG2-262 GEN
Solar/Wind Harmer
0.716
3143226MDLTHAN
Solar/Wind Harmer
-0.011
957481AF2-042 GEN
Solar/Wind Harmer
33.676
315687AD1-152 GEN
Solar/Wind Harmer
1.177
971065AG2-659 GEN
Solar/Wind Harmer
4.828
3147043LAWRENC
Adder
0.772
316129AC1-054 GEN
Solar/Wind Harmer
0.829
3143526WINTERP
Solar/Wind Harmer
-0.048
971795AH1-408 GEN
Solar/Wind Harmer
6.741
316003AC1-222 GEN
Solar/Wind Harmer
0.801
960081AF2-299 GEN
Solar/Wind Harmer
0.865
3145783HORNRTN
Solar/Wind Harmer
-0.007
3150851SPRUNCC
Adder
0.287
316190AA2-174 GEN
Solar/Wind Harmer
0.085
970919AG2-571 GEN
Solar/Wind Harmer
2.097
970087AG2-069 GEN
Solar/Wind Harmer
6.187
316023GEN1_S
Solar/Wind Harmer
0.439
3146263WOODLND
Solar/Wind Harmer
-0.006
3147983MERCK5
Solar/Wind Helper
0.059
3151921BEARGRDN G2
50/50
4.528
3144293JTRSVLE
50/50
0.707
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
942461AE2-259 GEN
Solar/Wind Harmer
4.401
316313AB2-026
Solar/Wind Harmer
0.767
316258AE1-075 C
Solar/Wind Harmer
0.691
316405AF2-144 C
Solar/Wind Harmer
0.729
3143336POWHATN
Solar/Wind Harmer
2.87
970909AG2-566 GEN
Solar/Wind Harmer
2.41
3147133PAMPLIN
Solar/Wind Harmer
-0.078
971193AH1-056 GEN
Solar/Wind Harmer
15.637
963181AG1-167 GEN
Solar/Wind Harmer
2.204
959311AF2-222 GEN
Solar/Wind Harmer
20.588
970257AG2-171 GEN
Solar/Wind Harmer
7.15
315785AD2-033 C
Solar/Wind Harmer
4.116
970221AG2-151 GEN
Solar/Wind Harmer
9.919
964241AG1-285 GEN
Solar/Wind Harmer
12.307
316131AB2-060 GEN
Solar/Wind Harmer
1.542
316478AD1-087 GEN
Solar/Wind Harmer
0.938
316486AD2-202 GEN
Solar/Wind Harmer
0.275
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.266
960061AF2-297 GEN
Solar/Wind Harmer
4.421
966621AG1-532 GEN
Solar/Wind Harmer
0.156
971683AH1-343 GEN
Solar/Wind Harmer
3.303
313506AB2-031 GEN
Solar/Wind Harmer
0.598
3150861SPRUNCD
Adder
0.287
970917AG2-570 GEN
Solar/Wind Harmer
16.566
316365GEN2_N
Solar/Wind Harmer
0.439
3156081AA2-088 GEN
Solar/Wind Harmer
2.059
3146263WOODLND
Solar/Wind Harmer
-0.006
3148013FISHERV
Solar/Wind Helper
0.214
316499AE2-029_GEN
Solar/Wind Helper
0.539
315616AA1-038_C
Solar/Wind Helper
0.586
3132273ORANGE
Solar/Wind Helper
0.024
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.124
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.365
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.226
LAGNLTFEXP_LAGN->PJM
CLTF
0.913
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.923
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.434
CPLELTFEXP_CPLE->PJM
CLTF
3.156
NYPJM->LTFIMP_NY
CLTF
0.354
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.645
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.53 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:973.3
MW Contribution:23.31
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.618
3144293JTRSVLE
50/50
0.52
970535AG2-341 GEN
50/50
1.297
971489AH1-241 GEN
Solar/Wind Harmer
23.308
3146776BUCKING
Solar/Wind Harmer
1.512
3146776BUCKING
Solar/Wind Harmer
0.122
315821AE2-092 GEN
Solar/Wind Harmer
0.018
970301AG2-198 GEN
Solar/Wind Harmer
8.441
3147133PAMPLIN
Solar/Wind Harmer
0.197
3147133PAMPLIN
Solar/Wind Harmer
0.158
958211AF2-115 GEN
Solar/Wind Harmer
2.196
963191AG1-168 GEN
Solar/Wind Harmer
0.732
971741AH1-377 GEN
Solar/Wind Harmer
16.934
316034AC1-036 C
Solar/Wind Harmer
0.01
970323AG2-213 GEN
Solar/Wind Harmer
5.97
971775AH1-396 GEN
Solar/Wind Harmer
0.224
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.408
964791AG1-342 GEN
Solar/Wind Harmer
1.297
3146843MT LREL
Solar/Wind Harmer
0.067
3146843MT LREL
Solar/Wind Harmer
0.067
3151931BEARGRDN S1
50/50
5.898
3151911BEARGRDN G1
50/50
4.57
3144293JTRSVLE
50/50
0.618
3151601KERR 3
50/50
0.12
3151581KERR 1
50/50
0.043
970937AG2-583 GEN
Solar/Wind Harmer
37.481
972003AH1-546 GEN
Solar/Wind Harmer
20.008
971377AH1-170 GEN
Solar/Wind Harmer
4.662
3147623JAMES R
Solar/Wind Harmer
1.013
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.151
3146926FARMVIL
Solar/Wind Harmer
0.171
963171AG1-166 GEN
Solar/Wind Harmer
0.976
971563AH1-280 GEN
Solar/Wind Harmer
1.952
970685AG2-442 GEN
Solar/Wind Harmer
12.103
316237AB2-079_GEN
Solar/Wind Harmer
0.001
962491AG1-098 GEN
Solar/Wind Harmer
4.891
315693AD1-088 GEN
Solar/Wind Harmer
3.821
970401AG2-262 GEN
Solar/Wind Harmer
0.396
962751AG1-124 GEN
Solar/Wind Harmer
2.983
316336AC2-165 C
Solar/Wind Helper
3.978
3143226MDLTHAN
Solar/Wind Helper
0.214
3143526WINTERP
Solar/Wind Helper
0.904
972205AH1-687 GEN
50/50
22.289
3151611KERR 4
50/50
0.12
3151621KERR 5
50/50
0.12
3151631KERR 6
50/50
0.12
3151641KERR 7
50/50
0.12
971447AH1-217 GEN
Solar/Wind Harmer
12.416
971845AH1-439 GEN
Solar/Wind Harmer
16.793
970285AG2-188 GEN
Solar/Wind Harmer
28.117
270494AE1-108_GEN
Solar/Wind Harmer
4.14
315657AE1-056 GEN
Solar/Wind Harmer
6.813
946301AF1-294 GEN
Solar/Wind Harmer
3.611
961791AG1-021 GEN
Solar/Wind Harmer
1.757
970683AG2-441 GEN
Solar/Wind Harmer
10.806
970681AG2-440 GEN
Solar/Wind Harmer
8.645
3144303KENBRDG
Solar/Wind Harmer
0.112
971443AH1-215 GEN
Solar/Wind Harmer
2.318
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.153
316233AE1-074 FULL
Solar/Wind Helper
0.266
3151921BEARGRDN G2
50/50
4.57
3144293JTRSVLE
50/50
0.618
966251AG1-494 GEN
50/50
1.545
3151591KERR 2
50/50
0.12
970221AG2-151 GEN
Solar/Wind Harmer
23.308
3146776BUCKING
Solar/Wind Harmer
0.136
3146926FARMVIL
Solar/Wind Harmer
0.171
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
2.11
3147133PAMPLIN
Solar/Wind Harmer
0.62
971193AH1-056 GEN
Solar/Wind Harmer
12.029
963181AG1-167 GEN
Solar/Wind Harmer
0.732
959311AF2-222 GEN
Solar/Wind Harmer
13.003
958131AF2-107 GEN
Solar/Wind Harmer
4.145
970257AG2-171 GEN
Solar/Wind Harmer
4.477
315785AD2-033 C
Solar/Wind Harmer
1.066
964241AG1-285 GEN
Solar/Wind Harmer
7.188
316131AB2-060 GEN
Solar/Wind Harmer
0.295
316313AB2-026
Solar/Wind Helper
0.958
316258AE1-075 C
Solar/Wind Helper
0.862
316405AF2-144 C
Solar/Wind Helper
0.719
939181AE1-148 GEN
Solar/Wind Harmer
3.054
3143526WINTERP
Solar/Wind Helper
0.904
LAGNLTFEXP_LAGN->PJM
CLTF
1.363
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.841
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.476
MECLTFEXP_MEC->PJM
CLTF
0.813
SIGELTFEXP_SIGE->PJM
CLTF
0.026
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.179
TVALTFEXP_TVA->PJM
CLTF
0.699
NYPJM->LTFIMP_NY
CLTF
0.404
LGEELTFEXP_LGEE->PJM
CLTF
0.328
WECLTFEXP_WEC->PJM
CLTF
0.165
CPLELTFEXP_CPLE->PJM
CLTF
1.292
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.85

Details for 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.72 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:958.85
MW Contribution:15.13
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
14.467
3151541CLOVER2
50/50
2.177
3151611KERR 4
50/50
0.135
3151621KERR 5
50/50
0.135
3151631KERR 6
50/50
0.135
3151641KERR 7
50/50
0.135
971447AH1-217 GEN
Solar/Wind Harmer
8.145
971845AH1-439 GEN
Solar/Wind Harmer
11.716
970285AG2-188 GEN
Solar/Wind Harmer
19.851
270494AE1-108_GEN
Solar/Wind Harmer
2.723
315657AE1-056 GEN
Solar/Wind Harmer
5.462
946301AF1-294 GEN
Solar/Wind Harmer
2.936
961791AG1-021 GEN
Solar/Wind Harmer
1.429
970683AG2-441 GEN
Solar/Wind Harmer
9.008
970681AG2-440 GEN
Solar/Wind Harmer
7.206
3144303KENBRDG
Solar/Wind Harmer
0.096
971443AH1-215 GEN
Solar/Wind Harmer
2.005
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.188
3148133STUARTS
Solar/Wind Harmer
0.042
3151921BEARGRDN G2
50/50
2.966
3144293JTRSVLE
50/50
0.503
970413AG2-270 GEN
50/50
9.546
966251AG1-494 GEN
50/50
1.198
3151591KERR 2
50/50
0.135
970221AG2-151 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
0.094
3146926FARMVIL
Solar/Wind Harmer
0.129
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
1.869
3147133PAMPLIN
Solar/Wind Harmer
0.497
971193AH1-056 GEN
Solar/Wind Harmer
9.642
963181AG1-167 GEN
Solar/Wind Harmer
0.595
959311AF2-222 GEN
Solar/Wind Harmer
11.09
3144293JTRSVLE
50/50
0.503
3144293JTRSVLE
50/50
0.423
970535AG2-341 GEN
50/50
1.349
3152661PLYWOOD A
50/50
0.157
971489AH1-241 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
1.049
3146776BUCKING
Solar/Wind Harmer
0.085
315821AE2-092 GEN
Solar/Wind Harmer
0.013
970301AG2-198 GEN
Solar/Wind Harmer
7.476
971741AH1-377 GEN
Solar/Wind Harmer
16.133
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.127
958211AF2-115 GEN
Solar/Wind Harmer
1.786
963191AG1-168 GEN
Solar/Wind Harmer
0.595
316034AC1-036 C
Solar/Wind Harmer
0.009
970323AG2-213 GEN
Solar/Wind Harmer
5.145
971775AH1-396 GEN
Solar/Wind Harmer
0.193
970099AG2-077 GEN
Solar/Wind Harmer
11.665
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.768
964791AG1-342 GEN
Solar/Wind Harmer
1.475
3146843MT LREL
Solar/Wind Harmer
0.077
3146843MT LREL
Solar/Wind Harmer
0.077
939181AE1-148 GEN
Solar/Wind Harmer
3.325
3143526WINTERP
Solar/Wind Helper
1.294
316240AF1-291 C
Solar/Wind Helper
0.162
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.156
316075AC2-137 C
Solar/Wind Helper
0.172
970257AG2-171 GEN
Solar/Wind Harmer
3.859
315785AD2-033 C
Solar/Wind Harmer
0.934
958131AF2-107 GEN
Solar/Wind Harmer
2.955
316478AD1-087 GEN
Solar/Wind Harmer
0.356
316486AD2-202 GEN
Solar/Wind Harmer
0.105
964241AG1-285 GEN
Solar/Wind Harmer
6.636
316131AB2-060 GEN
Solar/Wind Harmer
0.284
3148013FISHERV
Solar/Wind Harmer
0.071
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.932
971683AH1-343 GEN
Solar/Wind Harmer
2.348
316313AB2-026
Solar/Wind Helper
1.245
316258AE1-075 C
Solar/Wind Helper
1.12
316405AF2-144 C
Solar/Wind Helper
0.933
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.709
315839AE2-212 C
Solar/Wind Helper
0.155
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.069
3147243WELCO
Solar/Wind Harmer
0.043
970865AG2-541 GEN
Solar/Wind Harmer
2.13
316123AC1-075 GEN
Solar/Wind Harmer
0.077
970165AG2-112 GEN
Solar/Wind Harmer
0.459
970163AG2-111 GEN
Solar/Wind Harmer
0.438
316233AE1-074 FULL
Solar/Wind Helper
0.38
316312AB1-027
Solar/Wind Helper
0.217
316132AB2-190 GEN1
Solar/Wind Helper
0.639
3151931BEARGRDN S1
50/50
3.828
3151911BEARGRDN G1
50/50
2.966
3144293JTRSVLE
50/50
0.503
3151531CLOVER1
50/50
2.188
3151601KERR 3
50/50
0.135
3151581KERR 1
50/50
0.048
970937AG2-583 GEN
Solar/Wind Harmer
28.699
972003AH1-546 GEN
Solar/Wind Harmer
13.118
971377AH1-170 GEN
Solar/Wind Harmer
3.027
3147623JAMES R
Solar/Wind Harmer
0.658
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
963171AG1-166 GEN
Solar/Wind Harmer
0.794
971563AH1-280 GEN
Solar/Wind Harmer
1.587
970685AG2-442 GEN
Solar/Wind Harmer
10.089
962491AG1-098 GEN
Solar/Wind Harmer
7.03
315693AD1-088 GEN
Solar/Wind Harmer
5.777
957481AF2-042 GEN
Solar/Wind Harmer
29.163
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.003
970401AG2-262 GEN
Solar/Wind Harmer
0.451
316003AC1-222 GEN
Solar/Wind Harmer
0.002
316336AC2-165 C
Solar/Wind Helper
5.135
3143226MDLTHAN
Solar/Wind Helper
0.3
3143526WINTERP
Solar/Wind Helper
1.294
3142543TWELFTH
Solar/Wind Helper
0.014
3142416OLDCHRC
Solar/Wind Helper
0.296
3142416OLDCHRC
Solar/Wind Helper
0.113
316458AB2-190 GEN2
Solar/Wind Helper
0.639
LAGNLTFEXP_LAGN->PJM
CLTF
1.406
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.581
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
1.069
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.04
TVALTFEXP_TVA->PJM
CLTF
0.731
SIGELTFEXP_SIGE->PJM
CLTF
0.035
NYPJM->LTFIMP_NY
CLTF
0.331
LGEELTFEXP_LGEE->PJM
CLTF
0.459
WECLTFEXP_WEC->PJM
CLTF
0.235
CPLELTFEXP_CPLE->PJM
CLTF
0.611
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.053

Details for 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2028T2054_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.1 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1108.4
MW Contribution:30.73
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.901
3151911BEARGRDN G1
50/50
4.573
3144293JTRSVLE
50/50
0.618
970937AG2-583 GEN
Solar/Wind Harmer
49.358
972003AH1-546 GEN
Solar/Wind Harmer
26.402
971377AH1-170 GEN
Solar/Wind Harmer
6.146
3147623JAMES R
Solar/Wind Harmer
0.761
316322AB2-045
Solar/Wind Harmer
1.43
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
963171AG1-166 GEN
Solar/Wind Harmer
2.57
971563AH1-280 GEN
Solar/Wind Harmer
2.57
970685AG2-442 GEN
Solar/Wind Harmer
15.938
316237AB2-079_GEN
Solar/Wind Harmer
0.296
962491AG1-098 GEN
Solar/Wind Harmer
6.43
315693AD1-088 GEN
Solar/Wind Harmer
4.464
970401AG2-262 GEN
Solar/Wind Harmer
0.496
962751AG1-124 GEN
Solar/Wind Harmer
4.423
316336AC2-165 C
Solar/Wind Helper
3.979
3143226MDLTHAN
Solar/Wind Helper
0.215
3143526WINTERP
Solar/Wind Helper
0.909
3151921BEARGRDN G2
50/50
4.573
3144293JTRSVLE
50/50
0.618
970221AG2-151 GEN
Solar/Wind Harmer
30.731
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.035
970909AG2-566 GEN
Solar/Wind Harmer
2.11
3147133PAMPLIN
Solar/Wind Harmer
-0.069
971193AH1-056 GEN
Solar/Wind Harmer
13.876
963181AG1-167 GEN
Solar/Wind Harmer
1.928
959311AF2-222 GEN
Solar/Wind Harmer
17.157
958131AF2-107 GEN
Solar/Wind Harmer
5.552
970257AG2-171 GEN
Solar/Wind Harmer
5.895
315785AD2-033 C
Solar/Wind Harmer
3.34
964241AG1-285 GEN
Solar/Wind Harmer
9.463
316131AB2-060 GEN
Solar/Wind Harmer
1.135
316313AB2-026
Solar/Wind Helper
0.959
316258AE1-075 C
Solar/Wind Helper
0.863
316405AF2-144 C
Solar/Wind Helper
0.719
972205AH1-687 GEN
50/50
22.302
971447AH1-217 GEN
Solar/Wind Harmer
16.384
971845AH1-439 GEN
Solar/Wind Harmer
22.121
970285AG2-188 GEN
Solar/Wind Harmer
34.956
270494AE1-108_GEN
Solar/Wind Harmer
10.113
315657AE1-056 GEN
Solar/Wind Harmer
8.325
946301AF1-294 GEN
Solar/Wind Harmer
5.269
961791AG1-021 GEN
Solar/Wind Harmer
2.57
970683AG2-441 GEN
Solar/Wind Harmer
14.23
970681AG2-440 GEN
Solar/Wind Harmer
11.384
3144303KENBRDG
Solar/Wind Harmer
-0.013
971443AH1-215 GEN
Solar/Wind Harmer
3.053
316239AB2-077_GEN
Solar/Wind Harmer
0.296
316238AB2-078_GEN
Solar/Wind Harmer
0.296
316118AC1-105 GEN
Solar/Wind Harmer
0.458
316233AE1-074 FULL
Solar/Wind Helper
0.267
3144293JTRSVLE
50/50
0.618
3144293JTRSVLE
50/50
0.521
971489AH1-241 GEN
Solar/Wind Harmer
29.175
3146776BUCKING
Solar/Wind Harmer
-0.169
3146776BUCKING
Solar/Wind Harmer
-0.014
315821AE2-092 GEN
Solar/Wind Harmer
6.931
970301AG2-198 GEN
Solar/Wind Harmer
11.113
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.213
963191AG1-168 GEN
Solar/Wind Harmer
1.928
971741AH1-377 GEN
Solar/Wind Harmer
22.291
316034AC1-036 C
Solar/Wind Harmer
0.292
970323AG2-213 GEN
Solar/Wind Harmer
7.861
971775AH1-396 GEN
Solar/Wind Harmer
1.119
313527AB2-043 GEN
Solar/Wind Harmer
1.646
962561AG1-105 GEN
Solar/Wind Harmer
4.489
964791AG1-342 GEN
Solar/Wind Harmer
1.622
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
939181AE1-148 GEN
Solar/Wind Harmer
4.018
3143526WINTERP
Solar/Wind Helper
0.909
LAGNLTFEXP_LAGN->PJM
CLTF
1.429
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.277
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.604
MECLTFEXP_MEC->PJM
CLTF
0.866
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.252
TVALTFEXP_TVA->PJM
CLTF
0.733
SIGELTFEXP_SIGE->PJM
CLTF
0.027
CPLELTFEXP_CPLE->PJM
CLTF
1.307
NYPJM->LTFIMP_NY
CLTF
0.421
LGEELTFEXP_LGEE->PJM
CLTF
0.351
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.286
WECLTFEXP_WEC->PJM
CLTF
0.177

Details for 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 233T2028_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.37 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1091.46
MW Contribution:30.69
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.898
3151911BEARGRDN G1
50/50
4.57
3144293JTRSVLE
50/50
0.618
970937AG2-583 GEN
Solar/Wind Harmer
49.351
972003AH1-546 GEN
Solar/Wind Harmer
26.389
971377AH1-170 GEN
Solar/Wind Harmer
6.139
3147623JAMES R
Solar/Wind Harmer
0.76
316322AB2-045
Solar/Wind Harmer
1.43
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
963171AG1-166 GEN
Solar/Wind Harmer
2.57
971563AH1-280 GEN
Solar/Wind Harmer
2.57
970685AG2-442 GEN
Solar/Wind Harmer
15.936
316237AB2-079_GEN
Solar/Wind Harmer
0.296
962491AG1-098 GEN
Solar/Wind Harmer
6.439
315693AD1-088 GEN
Solar/Wind Harmer
4.471
970401AG2-262 GEN
Solar/Wind Harmer
0.495
962751AG1-124 GEN
Solar/Wind Harmer
4.364
316336AC2-165 C
Solar/Wind Helper
3.978
3143226MDLTHAN
Solar/Wind Helper
0.214
3143526WINTERP
Solar/Wind Helper
0.905
3151921BEARGRDN G2
50/50
4.57
3144293JTRSVLE
50/50
0.618
970221AG2-151 GEN
Solar/Wind Harmer
30.694
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.034
970909AG2-566 GEN
Solar/Wind Harmer
2.11
3147133PAMPLIN
Solar/Wind Harmer
-0.069
971193AH1-056 GEN
Solar/Wind Harmer
13.873
963181AG1-167 GEN
Solar/Wind Harmer
1.927
959311AF2-222 GEN
Solar/Wind Harmer
17.156
958131AF2-107 GEN
Solar/Wind Harmer
5.522
970257AG2-171 GEN
Solar/Wind Harmer
5.895
315785AD2-033 C
Solar/Wind Harmer
3.339
964241AG1-285 GEN
Solar/Wind Harmer
9.464
316131AB2-060 GEN
Solar/Wind Harmer
1.135
316313AB2-026
Solar/Wind Helper
0.959
316258AE1-075 C
Solar/Wind Helper
0.862
316405AF2-144 C
Solar/Wind Helper
0.719
972205AH1-687 GEN
50/50
22.291
971447AH1-217 GEN
Solar/Wind Harmer
16.353
971845AH1-439 GEN
Solar/Wind Harmer
22.112
970285AG2-188 GEN
Solar/Wind Harmer
34.943
270494AE1-108_GEN
Solar/Wind Harmer
10.095
315657AE1-056 GEN
Solar/Wind Harmer
8.324
946301AF1-294 GEN
Solar/Wind Harmer
5.268
961791AG1-021 GEN
Solar/Wind Harmer
2.57
970683AG2-441 GEN
Solar/Wind Harmer
14.229
970681AG2-440 GEN
Solar/Wind Harmer
11.383
3144303KENBRDG
Solar/Wind Harmer
-0.013
971443AH1-215 GEN
Solar/Wind Harmer
3.053
316239AB2-077_GEN
Solar/Wind Harmer
0.296
316238AB2-078_GEN
Solar/Wind Harmer
0.296
316118AC1-105 GEN
Solar/Wind Harmer
0.458
316233AE1-074 FULL
Solar/Wind Helper
0.266
3144293JTRSVLE
50/50
0.618
3144293JTRSVLE
50/50
0.521
971489AH1-241 GEN
Solar/Wind Harmer
29.14
3146776BUCKING
Solar/Wind Harmer
-0.169
3146776BUCKING
Solar/Wind Harmer
-0.014
315821AE2-092 GEN
Solar/Wind Harmer
6.892
970301AG2-198 GEN
Solar/Wind Harmer
11.114
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.212
963191AG1-168 GEN
Solar/Wind Harmer
1.927
971741AH1-377 GEN
Solar/Wind Harmer
22.295
316034AC1-036 C
Solar/Wind Harmer
0.292
970323AG2-213 GEN
Solar/Wind Harmer
7.86
971775AH1-396 GEN
Solar/Wind Harmer
1.119
313527AB2-043 GEN
Solar/Wind Harmer
1.646
962561AG1-105 GEN
Solar/Wind Harmer
4.487
964791AG1-342 GEN
Solar/Wind Harmer
1.621
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
939181AE1-148 GEN
Solar/Wind Harmer
4.02
3143526WINTERP
Solar/Wind Helper
0.905
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.897
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.492
MECLTFEXP_MEC->PJM
CLTF
0.819
LAGNLTFEXP_LAGN->PJM
CLTF
1.371
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.188
TVALTFEXP_TVA->PJM
CLTF
0.704
SIGELTFEXP_SIGE->PJM
CLTF
0.026
CPLELTFEXP_CPLE->PJM
CLTF
1.294
NYPJM->LTFIMP_NY
CLTF
0.406
LGEELTFEXP_LGEE->PJM
CLTF
0.331
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.906
WECLTFEXP_WEC->PJM
CLTF
0.166

Details for 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2193_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2028T2193_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.25 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1090.27
MW Contribution:29.42
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.972
3151911BEARGRDN G1
50/50
4.627
3144293JTRSVLE
50/50
0.627
970937AG2-583 GEN
Solar/Wind Harmer
49.759
972003AH1-546 GEN
Solar/Wind Harmer
26.719
971377AH1-170 GEN
Solar/Wind Harmer
5.885
3147623JAMES R
Solar/Wind Harmer
0.728
316322AB2-045
Solar/Wind Harmer
1.448
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
963171AG1-166 GEN
Solar/Wind Harmer
2.607
971563AH1-280 GEN
Solar/Wind Harmer
2.607
970685AG2-442 GEN
Solar/Wind Harmer
16.168
316237AB2-079_GEN
Solar/Wind Harmer
0.301
962491AG1-098 GEN
Solar/Wind Harmer
6.56
315693AD1-088 GEN
Solar/Wind Harmer
4.557
970401AG2-262 GEN
Solar/Wind Harmer
0.503
962751AG1-124 GEN
Solar/Wind Harmer
4.196
316336AC2-165 C
Solar/Wind Helper
3.937
3143226MDLTHAN
Solar/Wind Helper
0.212
3143526WINTERP
Solar/Wind Helper
0.892
972205AH1-687 GEN
50/50
22.568
971447AH1-217 GEN
Solar/Wind Harmer
15.499
971845AH1-439 GEN
Solar/Wind Harmer
22.397
970285AG2-188 GEN
Solar/Wind Harmer
35.395
270494AE1-108_GEN
Solar/Wind Harmer
9.679
315657AE1-056 GEN
Solar/Wind Harmer
8.441
946301AF1-294 GEN
Solar/Wind Harmer
5.344
961791AG1-021 GEN
Solar/Wind Harmer
2.607
970683AG2-441 GEN
Solar/Wind Harmer
14.436
970681AG2-440 GEN
Solar/Wind Harmer
11.549
3144303KENBRDG
Solar/Wind Harmer
-0.013
971443AH1-215 GEN
Solar/Wind Harmer
3.098
316239AB2-077_GEN
Solar/Wind Harmer
0.301
316238AB2-078_GEN
Solar/Wind Harmer
0.301
316118AC1-105 GEN
Solar/Wind Harmer
0.465
316233AE1-074 FULL
Solar/Wind Helper
0.262
3144293JTRSVLE
50/50
0.627
3144293JTRSVLE
50/50
0.528
971489AH1-241 GEN
Solar/Wind Harmer
27.933
3146776BUCKING
Solar/Wind Harmer
-0.171
3146776BUCKING
Solar/Wind Harmer
-0.014
315821AE2-092 GEN
Solar/Wind Harmer
6.525
970301AG2-198 GEN
Solar/Wind Harmer
11.274
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.258
963191AG1-168 GEN
Solar/Wind Harmer
1.955
971741AH1-377 GEN
Solar/Wind Harmer
22.629
316034AC1-036 C
Solar/Wind Harmer
0.297
970323AG2-213 GEN
Solar/Wind Harmer
7.978
971775AH1-396 GEN
Solar/Wind Harmer
1.136
313527AB2-043 GEN
Solar/Wind Harmer
1.674
962561AG1-105 GEN
Solar/Wind Harmer
4.561
964791AG1-342 GEN
Solar/Wind Harmer
1.647
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
939181AE1-148 GEN
Solar/Wind Harmer
4.097
3143526WINTERP
Solar/Wind Helper
0.892
3151921BEARGRDN G2
50/50
4.627
3144293JTRSVLE
50/50
0.627
970221AG2-151 GEN
Solar/Wind Harmer
29.423
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.089
970909AG2-566 GEN
Solar/Wind Harmer
2.141
3147133PAMPLIN
Solar/Wind Harmer
-0.07
971193AH1-056 GEN
Solar/Wind Harmer
14.068
963181AG1-167 GEN
Solar/Wind Harmer
1.955
959311AF2-222 GEN
Solar/Wind Harmer
17.41
970257AG2-171 GEN
Solar/Wind Harmer
5.984
958131AF2-107 GEN
Solar/Wind Harmer
5.299
315785AD2-033 C
Solar/Wind Harmer
3.39
964241AG1-285 GEN
Solar/Wind Harmer
9.615
316131AB2-060 GEN
Solar/Wind Harmer
1.154
316313AB2-026
Solar/Wind Helper
0.949
316258AE1-075 C
Solar/Wind Helper
0.854
316405AF2-144 C
Solar/Wind Helper
0.711
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.454
MECLTFEXP_MEC->PJM
CLTF
0.798
LAGNLTFEXP_LAGN->PJM
CLTF
1.355
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.224
TVALTFEXP_TVA->PJM
CLTF
0.694
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
1.323
NYPJM->LTFIMP_NY
CLTF
0.404
LGEELTFEXP_LGEE->PJM
CLTF
0.321
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.76
WECLTFEXP_WEC->PJM
CLTF
0.161

Details for 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: WT2193_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT2193_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.23 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1090.05
MW Contribution:29.42
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.627
3144293JTRSVLE
50/50
0.627
970221AG2-151 GEN
Solar/Wind Harmer
29.423
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.089
970909AG2-566 GEN
Solar/Wind Harmer
2.141
3147133PAMPLIN
Solar/Wind Harmer
-0.07
971193AH1-056 GEN
Solar/Wind Harmer
14.068
963181AG1-167 GEN
Solar/Wind Harmer
1.955
959311AF2-222 GEN
Solar/Wind Harmer
17.41
970257AG2-171 GEN
Solar/Wind Harmer
5.984
958131AF2-107 GEN
Solar/Wind Harmer
5.299
315785AD2-033 C
Solar/Wind Harmer
3.39
964241AG1-285 GEN
Solar/Wind Harmer
9.615
316131AB2-060 GEN
Solar/Wind Harmer
1.154
316313AB2-026
Solar/Wind Helper
0.949
316258AE1-075 C
Solar/Wind Helper
0.854
316405AF2-144 C
Solar/Wind Helper
0.711
3151931BEARGRDN S1
50/50
5.972
3151911BEARGRDN G1
50/50
4.627
3144293JTRSVLE
50/50
0.627
970937AG2-583 GEN
Solar/Wind Harmer
49.759
972003AH1-546 GEN
Solar/Wind Harmer
26.719
971377AH1-170 GEN
Solar/Wind Harmer
5.885
3147623JAMES R
Solar/Wind Harmer
0.728
316322AB2-045
Solar/Wind Harmer
1.448
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
963171AG1-166 GEN
Solar/Wind Harmer
2.607
971563AH1-280 GEN
Solar/Wind Harmer
2.607
970685AG2-442 GEN
Solar/Wind Harmer
16.168
316237AB2-079_GEN
Solar/Wind Harmer
0.301
962491AG1-098 GEN
Solar/Wind Harmer
6.56
315693AD1-088 GEN
Solar/Wind Harmer
4.557
970401AG2-262 GEN
Solar/Wind Harmer
0.503
962751AG1-124 GEN
Solar/Wind Harmer
4.196
316336AC2-165 C
Solar/Wind Helper
3.937
3143226MDLTHAN
Solar/Wind Helper
0.212
3143526WINTERP
Solar/Wind Helper
0.892
972205AH1-687 GEN
50/50
22.568
971447AH1-217 GEN
Solar/Wind Harmer
15.499
971845AH1-439 GEN
Solar/Wind Harmer
22.397
970285AG2-188 GEN
Solar/Wind Harmer
35.395
270494AE1-108_GEN
Solar/Wind Harmer
9.679
315657AE1-056 GEN
Solar/Wind Harmer
8.441
946301AF1-294 GEN
Solar/Wind Harmer
5.344
961791AG1-021 GEN
Solar/Wind Harmer
2.607
970683AG2-441 GEN
Solar/Wind Harmer
14.436
970681AG2-440 GEN
Solar/Wind Harmer
11.549
3144303KENBRDG
Solar/Wind Harmer
-0.013
971443AH1-215 GEN
Solar/Wind Harmer
3.098
316239AB2-077_GEN
Solar/Wind Harmer
0.301
316238AB2-078_GEN
Solar/Wind Harmer
0.301
316118AC1-105 GEN
Solar/Wind Harmer
0.465
316233AE1-074 FULL
Solar/Wind Helper
0.262
3144293JTRSVLE
50/50
0.627
3144293JTRSVLE
50/50
0.528
971489AH1-241 GEN
Solar/Wind Harmer
27.933
3146776BUCKING
Solar/Wind Harmer
-0.171
3146776BUCKING
Solar/Wind Harmer
-0.014
315821AE2-092 GEN
Solar/Wind Harmer
6.525
970301AG2-198 GEN
Solar/Wind Harmer
11.274
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.258
963191AG1-168 GEN
Solar/Wind Harmer
1.955
971741AH1-377 GEN
Solar/Wind Harmer
22.629
316034AC1-036 C
Solar/Wind Harmer
0.297
970323AG2-213 GEN
Solar/Wind Harmer
7.978
971775AH1-396 GEN
Solar/Wind Harmer
1.136
313527AB2-043 GEN
Solar/Wind Harmer
1.674
962561AG1-105 GEN
Solar/Wind Harmer
4.561
964791AG1-342 GEN
Solar/Wind Harmer
1.647
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
939181AE1-148 GEN
Solar/Wind Harmer
4.097
3143526WINTERP
Solar/Wind Helper
0.892
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.454
MECLTFEXP_MEC->PJM
CLTF
0.798
LAGNLTFEXP_LAGN->PJM
CLTF
1.355
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.224
TVALTFEXP_TVA->PJM
CLTF
0.694
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
1.323
NYPJM->LTFIMP_NY
CLTF
0.404
LGEELTFEXP_LGEE->PJM
CLTF
0.321
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.76
WECLTFEXP_WEC->PJM
CLTF
0.161

Details for 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 202872_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 202872_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.91 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1086.93
MW Contribution:29.42
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.627
3144293JTRSVLE
50/50
0.627
970221AG2-151 GEN
Solar/Wind Harmer
29.423
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.089
970909AG2-566 GEN
Solar/Wind Harmer
2.141
3147133PAMPLIN
Solar/Wind Harmer
-0.07
971193AH1-056 GEN
Solar/Wind Harmer
14.068
963181AG1-167 GEN
Solar/Wind Harmer
1.955
959311AF2-222 GEN
Solar/Wind Harmer
17.41
970257AG2-171 GEN
Solar/Wind Harmer
5.984
958131AF2-107 GEN
Solar/Wind Harmer
5.299
315785AD2-033 C
Solar/Wind Harmer
3.39
964241AG1-285 GEN
Solar/Wind Harmer
9.615
316131AB2-060 GEN
Solar/Wind Harmer
1.154
316313AB2-026
Solar/Wind Helper
0.949
316258AE1-075 C
Solar/Wind Helper
0.854
316405AF2-144 C
Solar/Wind Helper
0.711
3151931BEARGRDN S1
50/50
5.972
3151911BEARGRDN G1
50/50
4.627
3144293JTRSVLE
50/50
0.627
970937AG2-583 GEN
Solar/Wind Harmer
49.759
972003AH1-546 GEN
Solar/Wind Harmer
26.719
971377AH1-170 GEN
Solar/Wind Harmer
5.885
3147623JAMES R
Solar/Wind Harmer
0.728
316322AB2-045
Solar/Wind Harmer
1.448
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
963171AG1-166 GEN
Solar/Wind Harmer
2.607
971563AH1-280 GEN
Solar/Wind Harmer
2.607
970685AG2-442 GEN
Solar/Wind Harmer
16.168
316237AB2-079_GEN
Solar/Wind Harmer
0.301
962491AG1-098 GEN
Solar/Wind Harmer
6.56
315693AD1-088 GEN
Solar/Wind Harmer
4.557
970401AG2-262 GEN
Solar/Wind Harmer
0.503
962751AG1-124 GEN
Solar/Wind Harmer
4.196
316336AC2-165 C
Solar/Wind Helper
3.937
3143226MDLTHAN
Solar/Wind Helper
0.212
3143526WINTERP
Solar/Wind Helper
0.892
972205AH1-687 GEN
50/50
22.568
971447AH1-217 GEN
Solar/Wind Harmer
15.499
971845AH1-439 GEN
Solar/Wind Harmer
22.397
970285AG2-188 GEN
Solar/Wind Harmer
35.395
270494AE1-108_GEN
Solar/Wind Harmer
9.679
315657AE1-056 GEN
Solar/Wind Harmer
8.441
946301AF1-294 GEN
Solar/Wind Harmer
5.344
961791AG1-021 GEN
Solar/Wind Harmer
2.607
970683AG2-441 GEN
Solar/Wind Harmer
14.436
970681AG2-440 GEN
Solar/Wind Harmer
11.549
3144303KENBRDG
Solar/Wind Harmer
-0.013
971443AH1-215 GEN
Solar/Wind Harmer
3.098
316239AB2-077_GEN
Solar/Wind Harmer
0.301
316238AB2-078_GEN
Solar/Wind Harmer
0.301
316118AC1-105 GEN
Solar/Wind Harmer
0.465
316233AE1-074 FULL
Solar/Wind Helper
0.262
3144293JTRSVLE
50/50
0.627
3144293JTRSVLE
50/50
0.528
971489AH1-241 GEN
Solar/Wind Harmer
27.933
3146776BUCKING
Solar/Wind Harmer
-0.171
3146776BUCKING
Solar/Wind Harmer
-0.014
315821AE2-092 GEN
Solar/Wind Harmer
6.525
970301AG2-198 GEN
Solar/Wind Harmer
11.274
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.258
963191AG1-168 GEN
Solar/Wind Harmer
1.955
971741AH1-377 GEN
Solar/Wind Harmer
22.629
316034AC1-036 C
Solar/Wind Harmer
0.297
970323AG2-213 GEN
Solar/Wind Harmer
7.978
971775AH1-396 GEN
Solar/Wind Harmer
1.136
313527AB2-043 GEN
Solar/Wind Harmer
1.674
962561AG1-105 GEN
Solar/Wind Harmer
4.561
964791AG1-342 GEN
Solar/Wind Harmer
1.647
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
939181AE1-148 GEN
Solar/Wind Harmer
4.097
3143526WINTERP
Solar/Wind Helper
0.892
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.454
MECLTFEXP_MEC->PJM
CLTF
0.798
LAGNLTFEXP_LAGN->PJM
CLTF
1.355
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.224
TVALTFEXP_TVA->PJM
CLTF
0.694
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
1.323
NYPJM->LTFIMP_NY
CLTF
0.404
LGEELTFEXP_LGEE->PJM
CLTF
0.321
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.76
WECLTFEXP_WEC->PJM
CLTF
0.161

Details for 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 553_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.22 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1202.88
MW Contribution:6.84
Bus #Bus NameTypeMW Contribution
23503501NHY_Z2-039
50/50
0.005
315821AE2-092 GEN
Solar/Wind Harmer
0.008
971489AH1-241 GEN
Solar/Wind Harmer
6.84
3146776BUCKING
Solar/Wind Harmer
0.395
3146776BUCKING
Solar/Wind Harmer
0.032
3132123MT JACKSON
Solar/Wind Harmer
0.208
970117AG2-086 GEN
Solar/Wind Harmer
1.594
970117AG2-086 GEN
Solar/Wind Harmer
1.063
966001AG1-469 GEN
Solar/Wind Helper
0.735
315651AD1-115 GEN
Solar/Wind Helper
0.962
972205AH1-687 GEN
50/50
5.876
3151881LOWMORC
50/50
1.119
3151881LOWMORC
50/50
1.101
3151861LOWMORA
50/50
1.084
3152181CUNINGC
50/50
0.816
972193AH1-681 GEN
50/50
2.399
3152011BATH 1A
50/50
2.071
3152021BATH 2B
50/50
2.071
3152031BATH 3C
50/50
2.071
3152041BATH 4D
50/50
2.067
3138266HYDRAULIC
Solar/Wind Harmer
0.011
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3148133STUARTS
Solar/Wind Harmer
0.083
3148013FISHERV
Solar/Wind Harmer
0.079
971447AH1-217 GEN
Solar/Wind Harmer
3.945
3151921BEARGRDN G2
50/50
1.205
3137383CUSHAW
50/50
0.022
3151861LOWMORA
50/50
1.128
3152191CUNINGD
50/50
1.776
3152171CUNINGB
50/50
0.767
972255AH1-712 GEN
50/50
53.693
315760AF1-028 GEN
50/50
15.215
3152051BATH 5E
50/50
2.069
3148013FISHERV
Solar/Wind Harmer
0.138
970221AG2-151 GEN
Solar/Wind Harmer
6.84
315616AA1-038_C
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.036
3146926FARMVIL
Solar/Wind Harmer
0.044
958131AF2-107 GEN
Solar/Wind Harmer
1.93
942461AE2-259 GEN
Solar/Wind Harmer
0
3132273ORANGE
Solar/Wind Helper
0.105
3147666LOUISA
Solar/Wind Helper
1.085
316170AC1-121 GEN2
Solar/Wind Helper
0.475
270494AE1-108_GEN
Solar/Wind Harmer
1.309
3148463FAIRFLD
Solar/Wind Harmer
0.099
971845AH1-439 GEN
Solar/Wind Harmer
4.376
970285AG2-188 GEN
Solar/Wind Harmer
7.313
316164AC1-076 GEN
Solar/Wind Helper
1.19
3151931BEARGRDN S1
50/50
1.555
3151911BEARGRDN G1
50/50
1.205
3152161CUNINGA
50/50
0.763
972277AH1-723 GEN
50/50
62.568
3152061BATH 6F
50/50
2.078
23503401SHY_Z2-039
50/50
0.003
971377AH1-170 GEN
Solar/Wind Harmer
1.368
3147623JAMES R
Solar/Wind Harmer
0.297
972003AH1-546 GEN
Solar/Wind Harmer
5.266
315705AF1-075 GEN
Solar/Wind Harmer
4.096
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.039
970937AG2-583 GEN
Solar/Wind Harmer
6.041
3147983MERCK5
Solar/Wind Harmer
0.038
3146926FARMVIL
Solar/Wind Harmer
0.044
316336AC2-165 C
Solar/Wind Harmer
0.002
316192AB2-158 GEN
Solar/Wind Helper
3.262
3147666LOUISA
Solar/Wind Helper
1.887
316254AC1-120 GEN1
Solar/Wind Helper
1.426
316006AB2-029 C
Solar/Wind Helper
0.088
LAGNLTFEXP_LAGN->PJM
CLTF
2.697
CBM West 1LTFEXP_CBM-W1->PJM
CBM
16.766
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.191
MECLTFEXP_MEC->PJM
CLTF
2.078
SIGELTFEXP_SIGE->PJM
CLTF
0.068
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.536
TVALTFEXP_TVA->PJM
CLTF
1.4
NYPJM->LTFIMP_NY
CLTF
0.747
LGEELTFEXP_LGEE->PJM
CLTF
0.893
WECLTFEXP_WEC->PJM
CLTF
0.458
CPLELTFEXP_CPLE->PJM
CLTF
0.939
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.474

Details for 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.1 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1083.62
MW Contribution:7.05
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
1.262
3137383CUSHAW
50/50
0.018
3151861LOWMORA
50/50
0.943
315760AF1-028 GEN
50/50
12.698
3152051BATH 5E
50/50
1.654
3144293JTRSVLE
50/50
0.21
3152191CUNINGD
50/50
1.059
3152171CUNINGB
50/50
0.457
972255AH1-712 GEN
50/50
32.018
970221AG2-151 GEN
Solar/Wind Harmer
7.052
3148013FISHERV
Solar/Wind Harmer
0.123
3146776BUCKING
Solar/Wind Harmer
0.039
3146926FARMVIL
Solar/Wind Harmer
0.052
315616AA1-038_C
Solar/Wind Harmer
0.001
942461AE2-259 GEN
Solar/Wind Harmer
0
316313AB2-026
Solar/Wind Harmer
0.042
316258AE1-075 C
Solar/Wind Harmer
0.05
316405AF2-144 C
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
1.009
958131AF2-107 GEN
Solar/Wind Harmer
1.905
3147133PAMPLIN
Solar/Wind Harmer
0.206
971193AH1-056 GEN
Solar/Wind Harmer
3.999
970909AG2-566 GEN
Solar/Wind Harmer
0.694
963181AG1-167 GEN
Solar/Wind Harmer
0.249
3132273ORANGE
Solar/Wind Helper
0.106
3147666LOUISA
Solar/Wind Helper
1.086
316170AC1-121 GEN2
Solar/Wind Helper
0.478
972205AH1-687 GEN
50/50
6.155
3151881LOWMORC
50/50
0.936
3151881LOWMORC
50/50
0.921
3151861LOWMORA
50/50
0.906
3152011BATH 1A
50/50
1.656
3152021BATH 2B
50/50
1.656
3152031BATH 3C
50/50
1.655
3152041BATH 4D
50/50
1.652
3152181CUNINGC
50/50
0.486
972193AH1-681 GEN
50/50
1.431
3138266HYDRAULIC
Solar/Wind Harmer
0.011
3138266HYDRAULIC
Solar/Wind Harmer
0.007
971447AH1-217 GEN
Solar/Wind Harmer
4.022
3148133STUARTS
Solar/Wind Harmer
0.074
3148013FISHERV
Solar/Wind Harmer
0.071
270494AE1-108_GEN
Solar/Wind Harmer
1.339
971845AH1-439 GEN
Solar/Wind Harmer
4.834
970285AG2-188 GEN
Solar/Wind Harmer
8.151
3148463FAIRFLD
Solar/Wind Harmer
0.083
315657AE1-056 GEN
Solar/Wind Harmer
2.265
946301AF1-294 GEN
Solar/Wind Harmer
1.229
961791AG1-021 GEN
Solar/Wind Harmer
0.598
970683AG2-441 GEN
Solar/Wind Harmer
3.826
970681AG2-440 GEN
Solar/Wind Harmer
3.061
316164AC1-076 GEN
Solar/Wind Helper
1.194
3151931BEARGRDN S1
50/50
1.629
3151911BEARGRDN G1
50/50
1.262
3152061BATH 6F
50/50
1.661
3144293JTRSVLE
50/50
0.21
23503401SHY_Z2-039
50/50
0.002
3152161CUNINGA
50/50
0.455
972277AH1-723 GEN
50/50
37.31
971377AH1-170 GEN
Solar/Wind Harmer
1.41
3147623JAMES R
Solar/Wind Harmer
0.306
972003AH1-546 GEN
Solar/Wind Harmer
5.557
970937AG2-583 GEN
Solar/Wind Harmer
6.724
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.043
3146926FARMVIL
Solar/Wind Harmer
0.052
315705AF1-075 GEN
Solar/Wind Harmer
3.448
3147983MERCK5
Solar/Wind Harmer
0.033
316336AC2-165 C
Solar/Wind Harmer
0.003
3143336POWHATN
Solar/Wind Harmer
1.187
963171AG1-166 GEN
Solar/Wind Harmer
0.332
971563AH1-280 GEN
Solar/Wind Harmer
0.664
970685AG2-442 GEN
Solar/Wind Harmer
4.286
316192AB2-158 GEN
Solar/Wind Helper
3.267
3147666LOUISA
Solar/Wind Helper
1.889
316254AC1-120 GEN1
Solar/Wind Helper
1.434
316006AB2-029 C
Solar/Wind Helper
0.088
3144293JTRSVLE
50/50
0.21
3144293JTRSVLE
50/50
0.177
23503501NHY_Z2-039
50/50
0.004
971489AH1-241 GEN
Solar/Wind Harmer
7.052
315821AE2-092 GEN
Solar/Wind Harmer
0.008
3146776BUCKING
Solar/Wind Harmer
0.434
3146776BUCKING
Solar/Wind Harmer
0.035
3147133PAMPLIN
Solar/Wind Harmer
0.066
3147133PAMPLIN
Solar/Wind Harmer
0.052
970301AG2-198 GEN
Solar/Wind Harmer
2.774
958211AF2-115 GEN
Solar/Wind Harmer
0.747
963191AG1-168 GEN
Solar/Wind Harmer
0.249
971741AH1-377 GEN
Solar/Wind Harmer
5.799
966001AG1-469 GEN
Solar/Wind Helper
0.74
315651AD1-115 GEN
Solar/Wind Helper
0.968
LAGNLTFEXP_LAGN->PJM
CLTF
2.954
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.521
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.505
MECLTFEXP_MEC->PJM
CLTF
2.015
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.46
TVALTFEXP_TVA->PJM
CLTF
1.519
SIGELTFEXP_SIGE->PJM
CLTF
0.065
NYPJM->LTFIMP_NY
CLTF
0.852
LGEELTFEXP_LGEE->PJM
CLTF
0.839
WECLTFEXP_WEC->PJM
CLTF
0.429
CPLELTFEXP_CPLE->PJM
CLTF
1.993
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.046

Details for 6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2199_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2199_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:167.54 %
Rating:819.68 MVA
Rating Type:B
MVA to Mitigate:1373.27
MW Contribution:4.16
Bus #Bus NameTypeMW Contribution
3151791S ANNAG2
50/50
1.912
3151781S ANNAS1
50/50
0.982
3151741LOISA C
50/50
1.993
3151751LOISA D
50/50
36.446
3151931BEARGRDN S1
50/50
0.958
3151911BEARGRDN G1
50/50
0.743
316192AB2-158 GEN
Solar/Wind Harmer
4.181
315683AE1-153 C
Solar/Wind Harmer
41.163
316254AC1-120 GEN1
Solar/Wind Harmer
0.299
971377AH1-170 GEN
Solar/Wind Harmer
0.831
3147623JAMES R
Solar/Wind Harmer
0.181
972003AH1-546 GEN
Solar/Wind Harmer
3.241
970937AG2-583 GEN
Solar/Wind Harmer
3.705
316322AB2-045
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.024
3147666LOUISA
Solar/Wind Helper
2.95
972205AH1-687 GEN
50/50
3.622
3147346CASHSCORNER
Solar/Wind Harmer
1.128
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3138266HYDRAULIC
Solar/Wind Harmer
0.004
316164AC1-076 GEN
Solar/Wind Harmer
0.131
971447AH1-217 GEN
Solar/Wind Harmer
2.376
3148133STUARTS
Solar/Wind Harmer
0.044
3148013FISHERV
Solar/Wind Harmer
0.042
270494AE1-108_GEN
Solar/Wind Harmer
0.776
971845AH1-439 GEN
Solar/Wind Harmer
2.669
970285AG2-188 GEN
Solar/Wind Harmer
4.452
3151771S ANNAG1
50/50
1.912
3151801S ANNAS2
50/50
0.982
3151761LOISA E
50/50
74.304
972183AH1-676 GEN
50/50
587.5
3151921BEARGRDN G2
50/50
0.743
3132273ORANGE
Solar/Wind Harmer
0.067
316170AC1-121 GEN2
Solar/Wind Harmer
0.15
970221AG2-151 GEN
Solar/Wind Harmer
4.157
3148013FISHERV
Solar/Wind Harmer
0.074
3146776BUCKING
Solar/Wind Harmer
0.022
3147666LOUISA
Solar/Wind Helper
1.696
3151731LOISA B
50/50
36.446
3151721LOISA A
50/50
36.258
966001AG1-469 GEN
Solar/Wind Harmer
0.277
315651AD1-115 GEN
Solar/Wind Harmer
0.004
971489AH1-241 GEN
Solar/Wind Harmer
4.157
315821AE2-092 GEN
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.241
3146776BUCKING
Solar/Wind Harmer
0.019
LAGNLTFEXP_LAGN->PJM
CLTF
1.002
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.145
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.947
MECLTFEXP_MEC->PJM
CLTF
0.771
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.222
TVALTFEXP_TVA->PJM
CLTF
0.525
NYPJM->LTFIMP_NY
CLTF
0.398
LGEELTFEXP_LGEE->PJM
CLTF
0.336
WECLTFEXP_WEC->PJM
CLTF
0.169
CPLELTFEXP_CPLE->PJM
CLTF
0.277
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.505

Details for 6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2331_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2331_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:162.72 %
Rating:819.68 MVA
Rating Type:B
MVA to Mitigate:1333.76
MW Contribution:4.16
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
3.622
3147346CASHSCORNER
Solar/Wind Harmer
1.128
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3138266HYDRAULIC
Solar/Wind Harmer
0.004
316164AC1-076 GEN
Solar/Wind Harmer
0.131
971447AH1-217 GEN
Solar/Wind Harmer
2.376
3148133STUARTS
Solar/Wind Harmer
0.044
3148013FISHERV
Solar/Wind Harmer
0.042
270494AE1-108_GEN
Solar/Wind Harmer
0.776
971845AH1-439 GEN
Solar/Wind Harmer
2.669
970285AG2-188 GEN
Solar/Wind Harmer
4.452
3151731LOISA B
50/50
36.446
3151721LOISA A
50/50
36.258
966001AG1-469 GEN
Solar/Wind Harmer
0.277
315651AD1-115 GEN
Solar/Wind Harmer
0.004
971489AH1-241 GEN
Solar/Wind Harmer
4.157
315821AE2-092 GEN
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.241
3146776BUCKING
Solar/Wind Harmer
0.019
3151771S ANNAG1
50/50
1.912
3151801S ANNAS2
50/50
0.982
3151761LOISA E
50/50
74.304
972183AH1-676 GEN
50/50
587.5
3151921BEARGRDN G2
50/50
0.743
3132273ORANGE
Solar/Wind Harmer
0.067
316170AC1-121 GEN2
Solar/Wind Harmer
0.15
970221AG2-151 GEN
Solar/Wind Harmer
4.157
3148013FISHERV
Solar/Wind Harmer
0.074
3146776BUCKING
Solar/Wind Harmer
0.022
3147666LOUISA
Solar/Wind Helper
1.696
3151791S ANNAG2
50/50
1.912
3151781S ANNAS1
50/50
0.982
3151741LOISA C
50/50
1.993
3151751LOISA D
50/50
36.446
3151931BEARGRDN S1
50/50
0.958
3151911BEARGRDN G1
50/50
0.743
316192AB2-158 GEN
Solar/Wind Harmer
4.181
315683AE1-153 C
Solar/Wind Harmer
41.163
316254AC1-120 GEN1
Solar/Wind Harmer
0.299
971377AH1-170 GEN
Solar/Wind Harmer
0.831
3147623JAMES R
Solar/Wind Harmer
0.181
972003AH1-546 GEN
Solar/Wind Harmer
3.241
970937AG2-583 GEN
Solar/Wind Harmer
3.705
316322AB2-045
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.024
3147666LOUISA
Solar/Wind Helper
2.95
LAGNLTFEXP_LAGN->PJM
CLTF
1.002
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.145
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.947
MECLTFEXP_MEC->PJM
CLTF
0.771
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.222
TVALTFEXP_TVA->PJM
CLTF
0.525
NYPJM->LTFIMP_NY
CLTF
0.398
LGEELTFEXP_LGEE->PJM
CLTF
0.336
WECLTFEXP_WEC->PJM
CLTF
0.169
CPLELTFEXP_CPLE->PJM
CLTF
0.277
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.505

Details for 6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:160.76 %
Rating:1003.0 MVA
Rating Type:C
MVA to Mitigate:1612.44
MW Contribution:6.31
Bus #Bus NameTypeMW Contribution
3151731LOISA B
50/50
41.011
3151721LOISA A
50/50
40.799
966001AG1-469 GEN
Solar/Wind Harmer
1.242
971489AH1-241 GEN
Solar/Wind Harmer
5.993
315821AE2-092 GEN
Solar/Wind Harmer
2.063
3146776BUCKING
Solar/Wind Harmer
-0.031
3146776BUCKING
Solar/Wind Harmer
-0.003
3147346CASHSCORNER
Solar/Wind Harmer
0.957
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
972205AH1-687 GEN
Adder
3.94
971447AH1-217 GEN
Solar/Wind Harmer
3.605
3148133STUARTS
Solar/Wind Harmer
-0.006
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
2.184
971845AH1-439 GEN
Solar/Wind Harmer
4.1
970285AG2-188 GEN
Solar/Wind Harmer
6.466
3151791S ANNAG2
50/50
2.137
3151781S ANNAS1
50/50
1.098
3151741LOISA C
50/50
2.243
3151751LOISA D
50/50
41.011
316192AB2-158 GEN
Solar/Wind Harmer
10.432
315683AE1-153 C
Solar/Wind Harmer
61.269
971377AH1-170 GEN
Solar/Wind Harmer
1.262
3147623JAMES R
Solar/Wind Harmer
0.156
972003AH1-546 GEN
Solar/Wind Harmer
4.942
970937AG2-583 GEN
Solar/Wind Harmer
5.698
316322AB2-045
Solar/Wind Harmer
0.265
3146776BUCKING
Solar/Wind Harmer
-0.003
315705AF1-075 GEN
Solar/Wind Harmer
2.901
3147666LOUISA
Solar/Wind Helper
2.639
3151771S ANNAG1
50/50
2.137
3151801S ANNAS2
50/50
1.098
3151761LOISA E
50/50
83.609
972183AH1-676 GEN
50/50
664.157
970221AG2-151 GEN
Solar/Wind Harmer
6.312
3148013FISHERV
Solar/Wind Harmer
-0.009
3146776BUCKING
Solar/Wind Harmer
-0.003
316499AE2-029_GEN
Solar/Wind Harmer
0.52
3147666LOUISA
Solar/Wind Helper
1.517
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.354
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.41
MECLTFEXP_MEC->PJM
CLTF
0.932
LAGNLTFEXP_LAGN->PJM
CLTF
1.253
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.732
TVALTFEXP_TVA->PJM
CLTF
0.654
SIGELTFEXP_SIGE->PJM
CLTF
0.03
CPLELTFEXP_CPLE->PJM
CLTF
0.472
NYPJM->LTFIMP_NY
CLTF
0.481
LGEELTFEXP_LGEE->PJM
CLTF
0.402
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.001
WECLTFEXP_WEC->PJM
CLTF
0.203

Details for 6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:154.66 %
Rating:1003.0 MVA
Rating Type:C
MVA to Mitigate:1551.26
MW Contribution:6.31
Bus #Bus NameTypeMW Contribution
3151731LOISA B
50/50
41.011
3151721LOISA A
50/50
40.799
966001AG1-469 GEN
Solar/Wind Harmer
1.242
971489AH1-241 GEN
Solar/Wind Harmer
5.993
315821AE2-092 GEN
Solar/Wind Harmer
2.063
3146776BUCKING
Solar/Wind Harmer
-0.031
3146776BUCKING
Solar/Wind Harmer
-0.003
3147346CASHSCORNER
Solar/Wind Harmer
0.957
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
972205AH1-687 GEN
Adder
3.94
971447AH1-217 GEN
Solar/Wind Harmer
3.605
3148133STUARTS
Solar/Wind Harmer
-0.006
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
2.184
971845AH1-439 GEN
Solar/Wind Harmer
4.1
970285AG2-188 GEN
Solar/Wind Harmer
6.466
3151791S ANNAG2
50/50
2.137
3151781S ANNAS1
50/50
1.098
3151741LOISA C
50/50
2.243
3151751LOISA D
50/50
41.011
316192AB2-158 GEN
Solar/Wind Harmer
10.432
971377AH1-170 GEN
Solar/Wind Harmer
1.262
3147623JAMES R
Solar/Wind Harmer
0.156
972003AH1-546 GEN
Solar/Wind Harmer
4.942
970937AG2-583 GEN
Solar/Wind Harmer
5.698
316322AB2-045
Solar/Wind Harmer
0.265
3146776BUCKING
Solar/Wind Harmer
-0.003
315705AF1-075 GEN
Solar/Wind Harmer
2.901
3147666LOUISA
Solar/Wind Helper
2.639
3151771S ANNAG1
50/50
2.137
3151801S ANNAS2
50/50
1.098
3151761LOISA E
50/50
83.609
972183AH1-676 GEN
50/50
664.157
970221AG2-151 GEN
Solar/Wind Harmer
6.312
3148013FISHERV
Solar/Wind Harmer
-0.009
3146776BUCKING
Solar/Wind Harmer
-0.003
316499AE2-029_GEN
Solar/Wind Harmer
0.52
3147666LOUISA
Solar/Wind Helper
1.517
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.354
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.41
MECLTFEXP_MEC->PJM
CLTF
0.932
LAGNLTFEXP_LAGN->PJM
CLTF
1.253
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.732
TVALTFEXP_TVA->PJM
CLTF
0.654
SIGELTFEXP_SIGE->PJM
CLTF
0.03
CPLELTFEXP_CPLE->PJM
CLTF
0.472
NYPJM->LTFIMP_NY
CLTF
0.481
LGEELTFEXP_LGEE->PJM
CLTF
0.402
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.001
WECLTFEXP_WEC->PJM
CLTF
0.203

Details for 6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2199T2331_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2199T2331_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:140.15 %
Rating:1003.0 MVA
Rating Type:C
MVA to Mitigate:1405.75
MW Contribution:5.47
Bus #Bus NameTypeMW Contribution
3147346CASHSCORNER
Solar/Wind Harmer
0.846
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
316164AC1-076 GEN
Solar/Wind Harmer
0.881
972205AH1-687 GEN
Adder
3.413
971447AH1-217 GEN
Solar/Wind Harmer
3.128
3148133STUARTS
Solar/Wind Harmer
-0.005
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
1.891
971845AH1-439 GEN
Solar/Wind Harmer
3.515
970285AG2-188 GEN
Solar/Wind Harmer
5.533
3151791S ANNAG2
50/50
1.912
3151781S ANNAS1
50/50
0.982
3151741LOISA C
50/50
1.993
3151751LOISA D
50/50
36.446
316192AB2-158 GEN
Solar/Wind Harmer
9.886
315683AE1-153 C
Solar/Wind Harmer
54.197
316254AC1-120 GEN1
Solar/Wind Harmer
1.273
971377AH1-170 GEN
Solar/Wind Harmer
1.095
3147623JAMES R
Solar/Wind Harmer
0.135
972003AH1-546 GEN
Solar/Wind Harmer
4.275
970937AG2-583 GEN
Solar/Wind Harmer
4.879
316322AB2-045
Solar/Wind Harmer
0.228
3146776BUCKING
Solar/Wind Harmer
-0.003
3147666LOUISA
Solar/Wind Helper
2.95
3151771S ANNAG1
50/50
1.912
3151801S ANNAS2
50/50
0.982
3151761LOISA E
50/50
74.304
972183AH1-676 GEN
50/50
587.5
3132273ORANGE
Solar/Wind Harmer
-0.007
316170AC1-121 GEN2
Solar/Wind Harmer
0.424
970221AG2-151 GEN
Solar/Wind Harmer
5.473
3148013FISHERV
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Harmer
-0.002
3147666LOUISA
Solar/Wind Helper
1.696
3151731LOISA B
50/50
36.446
3151721LOISA A
50/50
36.258
966001AG1-469 GEN
Solar/Wind Harmer
1.01
315651AD1-115 GEN
Solar/Wind Harmer
5.728
971489AH1-241 GEN
Solar/Wind Harmer
5.196
315821AE2-092 GEN
Solar/Wind Harmer
1.795
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.145
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.947
MECLTFEXP_MEC->PJM
CLTF
0.771
LAGNLTFEXP_LAGN->PJM
CLTF
1.002
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.222
TVALTFEXP_TVA->PJM
CLTF
0.525
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
0.277
NYPJM->LTFIMP_NY
CLTF
0.398
LGEELTFEXP_LGEE->PJM
CLTF
0.336
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.505
WECLTFEXP_WEC->PJM
CLTF
0.169

Details for 6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2278T2331_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2278T2331_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:136.11 %
Rating:1003.0 MVA
Rating Type:C
MVA to Mitigate:1365.22
MW Contribution:5.47
Bus #Bus NameTypeMW Contribution
3151771S ANNAG1
50/50
1.912
3151801S ANNAS2
50/50
0.982
3151761LOISA E
50/50
74.304
972183AH1-676 GEN
50/50
587.5
3132273ORANGE
Solar/Wind Harmer
-0.007
316170AC1-121 GEN2
Solar/Wind Harmer
0.424
970221AG2-151 GEN
Solar/Wind Harmer
5.473
3148013FISHERV
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Harmer
-0.002
3147666LOUISA
Solar/Wind Helper
1.696
3151791S ANNAG2
50/50
1.912
3151781S ANNAS1
50/50
0.982
3151741LOISA C
50/50
1.993
3151751LOISA D
50/50
36.446
316192AB2-158 GEN
Solar/Wind Harmer
9.886
315683AE1-153 C
Solar/Wind Harmer
54.197
316254AC1-120 GEN1
Solar/Wind Harmer
1.273
971377AH1-170 GEN
Solar/Wind Harmer
1.095
3147623JAMES R
Solar/Wind Harmer
0.135
972003AH1-546 GEN
Solar/Wind Harmer
4.275
970937AG2-583 GEN
Solar/Wind Harmer
4.879
316322AB2-045
Solar/Wind Harmer
0.228
3146776BUCKING
Solar/Wind Harmer
-0.003
3147666LOUISA
Solar/Wind Helper
2.95
3151731LOISA B
50/50
36.446
3151721LOISA A
50/50
36.258
966001AG1-469 GEN
Solar/Wind Harmer
1.01
315651AD1-115 GEN
Solar/Wind Harmer
5.728
971489AH1-241 GEN
Solar/Wind Harmer
5.196
315821AE2-092 GEN
Solar/Wind Harmer
1.795
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
3147346CASHSCORNER
Solar/Wind Harmer
0.846
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
316164AC1-076 GEN
Solar/Wind Harmer
0.881
972205AH1-687 GEN
Adder
3.413
971447AH1-217 GEN
Solar/Wind Harmer
3.128
3148133STUARTS
Solar/Wind Harmer
-0.005
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
1.891
971845AH1-439 GEN
Solar/Wind Harmer
3.515
970285AG2-188 GEN
Solar/Wind Harmer
5.533
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.145
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.947
MECLTFEXP_MEC->PJM
CLTF
0.771
LAGNLTFEXP_LAGN->PJM
CLTF
1.002
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.222
TVALTFEXP_TVA->PJM
CLTF
0.525
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
0.277
NYPJM->LTFIMP_NY
CLTF
0.398
LGEELTFEXP_LGEE->PJM
CLTF
0.336
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.505
WECLTFEXP_WEC->PJM
CLTF
0.169

Details for 6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line l/o DVP_P2-2: GERMANNA_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: GERMANNA_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:134.77 %
Rating:1003.0 MVA
Rating Type:C
MVA to Mitigate:1351.73
MW Contribution:5.47
Bus #Bus NameTypeMW Contribution
3151791S ANNAG2
50/50
1.912
3151781S ANNAS1
50/50
0.982
3151741LOISA C
50/50
1.993
3151751LOISA D
50/50
36.446
316192AB2-158 GEN
Solar/Wind Harmer
9.886
316254AC1-120 GEN1
Solar/Wind Harmer
1.273
3147346CASHSCORNER
Solar/Wind Harmer
0.846
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
316164AC1-076 GEN
Solar/Wind Harmer
0.881
972205AH1-687 GEN
Adder
3.413
971447AH1-217 GEN
Solar/Wind Harmer
3.128
3148133STUARTS
Solar/Wind Harmer
-0.005
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
1.891
971845AH1-439 GEN
Solar/Wind Harmer
3.515
970285AG2-188 GEN
Solar/Wind Harmer
5.533
3151731LOISA B
50/50
36.446
3151721LOISA A
50/50
36.258
966001AG1-469 GEN
Solar/Wind Harmer
1.01
315651AD1-115 GEN
Solar/Wind Harmer
5.728
971489AH1-241 GEN
Solar/Wind Harmer
5.196
315821AE2-092 GEN
Solar/Wind Harmer
1.795
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
3151771S ANNAG1
50/50
1.912
3151801S ANNAS2
50/50
0.982
3151761LOISA E
50/50
74.304
972183AH1-676 GEN
50/50
587.5
3132273ORANGE
Solar/Wind Harmer
-0.007
316170AC1-121 GEN2
Solar/Wind Harmer
0.424
970221AG2-151 GEN
Solar/Wind Harmer
5.473
3148013FISHERV
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Harmer
-0.002
3147666LOUISA
Solar/Wind Helper
1.696
971377AH1-170 GEN
Solar/Wind Harmer
1.095
3147623JAMES R
Solar/Wind Harmer
0.135
972003AH1-546 GEN
Solar/Wind Harmer
4.275
970937AG2-583 GEN
Solar/Wind Harmer
4.879
316322AB2-045
Solar/Wind Harmer
0.228
3146776BUCKING
Solar/Wind Harmer
-0.003
3147666LOUISA
Solar/Wind Helper
2.95
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.145
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.947
MECLTFEXP_MEC->PJM
CLTF
0.771
LAGNLTFEXP_LAGN->PJM
CLTF
1.002
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.222
TVALTFEXP_TVA->PJM
CLTF
0.525
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
0.277
NYPJM->LTFIMP_NY
CLTF
0.398
LGEELTFEXP_LGEE->PJM
CLTF
0.336
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.505
WECLTFEXP_WEC->PJM
CLTF
0.169

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o PEPCO_P1_5070_SRT-A


Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
PEPCO_P1_5070_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:152.59 %
Rating:1331.98 MVA
Rating Type:B
MVA to Mitigate:2032.49
MW Contribution:3.82
Bus #Bus NameTypeMW Contribution
3152111X4-039 GT1
50/50
1.838
315747AE2-019 GEN
50/50
13.176
3150021OMF B
50/50
0.216
3150101POSSM6S
50/50
1.296
3150081POSSM6A
50/50
0.848
3150151POSSMC1
50/50
1.143
3150151POSSMC1
50/50
1.143
3150231REMNGT3
50/50
14.281
3150241REMNGT4
50/50
13.316
972217AH1-693 GEN
50/50
1.756
963691AG1-221 GEN
Solar/Wind Harmer
2.312
971455AH1-223 GEN
Solar/Wind Harmer
2.312
3141196NOKESVL
Solar/Wind Harmer
0.429
972199AH1-684 GEN
Adder
1.903
3150301M RUN C
Adder
13.349
3150291M RUN B
Adder
13.25
3150331BIRCHWDA
Adder
16.626
3141316ARNOLDS
Adder
0.229
316044AC1-158 PL1
Solar/Wind Harmer
0.461
316450AC1-158 RIC
Solar/Wind Harmer
0.123
3150401LDYSMT4
Adder
12.678
3150371LDYSMT1
Adder
12.251
316170AC1-121 GEN2
Solar/Wind Harmer
0.1
970737AG2-469 GEN
Solar/Wind Harmer
3.872
3141906WESTMOR
Solar/Wind Harmer
0.036
3132273ORANGE
Solar/Wind Harmer
0.018
971781AH1-399 GEN
Solar/Wind Harmer
0.118
3147666LOUISA
Solar/Wind Harmer
0.204
3150351NORNECKC2
Adder
0.884
316404AE1-155 C
Solar/Wind Harmer
0.019
3151761LOISA E
Adder
11.415
972183AH1-676 GEN
Adder
92.045
970009AG2-005 GEN
Solar/Wind Harmer
0.643
316473AC1-191 GEN
Solar/Wind Harmer
0.29
962971AG1-146 GEN
Solar/Wind Harmer
1.373
3142416OLDCHRC
Solar/Wind Harmer
0.821
3141766HARMONY
Solar/Wind Harmer
1.129
316156AD2-030 GEN
Solar/Wind Harmer
0.063
3141873WAN 176
Solar/Wind Harmer
1.505
316280AD1-041 GEN
Solar/Wind Harmer
0.002
316203AE2-005 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
0.432
970293AG2-193 GEN
Solar/Wind Harmer
0.899
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3142946ENON
Solar/Wind Harmer
0.028
3150861SPRUNCD
Adder
0.385
316382AG1-145 C
Solar/Wind Harmer
0.001
970133AG2-095 GEN
Solar/Wind Harmer
0.794
970129AG2-093 GEN
Solar/Wind Harmer
4.984
3150921YORKTN3
Adder
2.069
315778AD1-151 GEN
Solar/Wind Harmer
6.579
965281AG1-393 GEN
Solar/Wind Harmer
0.877
3144216WINCHST
Adder
0.31
315839AE2-212 C
Solar/Wind Harmer
0.001
961611AG1-000B GEN
Solar/Wind Harmer
2.181
3151221GRAVEL6
Adder
5.934
3151171GRAVELC
Adder
1.142
3145336SMITFLD
Solar/Wind Harmer
0.033
315813AE1-149 C
Solar/Wind Harmer
4.334
315773AC2-141 GEN
Solar/Wind Harmer
2.962
970659AG2-427 GEN
Solar/Wind Harmer
0.856
316083AB2-161 GEN
Solar/Wind Harmer
0.001
3144536CHRHLND
Solar/Wind Harmer
0.012
3151101ELIZAR3
Adder
7.489
970661AG2-428 GEN
Solar/Wind Harmer
1.707
3144873MCLAUGH
Solar/Wind Harmer
0.002
944581AF1-123 GEN
Solar/Wind Harmer
18.149
944601AF1-125 GEN
Solar/Wind Harmer
17.869
3146456SLIGO L269
Solar/Wind Harmer
0.08
971153AH1-033 GEN
Solar/Wind Harmer
0.925
316320Y1-086
Solar/Wind Harmer
0
316313AB2-026
Solar/Wind Harmer
0.05
316258AE1-075 C
Solar/Wind Harmer
0.06
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
1.2
316435W1029_GEN3
Solar/Wind Harmer
0
972289AH1-729 GEN
50/50
13.249
3150091POSSM6B
50/50
0.848
3150071POSSM 5
50/50
52.224
3150181POSSMC2
50/50
1.152
3150181POSSMC2
50/50
1.143
3150181POSSMC2
50/50
1.143
316447AC1-158 HLD
Solar/Wind Harmer
1.014
3150391LDYSMT3
Adder
12.655
972195AH1-682 GEN
Adder
1.663
315651AD1-115 GEN
Solar/Wind Harmer
0.003
315673AE1-157 GEN
Solar/Wind Harmer
6.396
957411AF2-035 GEN
Solar/Wind Harmer
3.895
970317AG2-208 GEN
Solar/Wind Harmer
3.609
316468AD1-105 GEN
Solar/Wind Harmer
-0.029
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.913
3150341NORNECKC1
Adder
0.906
966001AG1-469 GEN
Solar/Wind Harmer
0.051
958261AF2-120 GEN
Solar/Wind Harmer
2.86
3152131X4-039 ST
50/50
2.892
3152121X4-039 GT2
50/50
1.833
3150011OMF A
50/50
0.216
3140676OCCOQUN
50/50
0.286
970467AG2-304 GEN
50/50
14.788
972223AH1-696 GEN
50/50
9.026
3150151POSSMC1
50/50
1.143
3141346CRANES
50/50
0.127
3150221REMNGT2
50/50
13.228
972201AH1-685 GEN
50/50
2.282
3150211REMNGT1
Adder
12.383
3150281M RUN A
Adder
13.357
316006AB2-029 C
Solar/Wind Harmer
0.001
971685AH1-345 GEN
Solar/Wind Harmer
0.73
316045AC1-158 PL2
Solar/Wind Harmer
1.475
972197AH1-683 GEN
Adder
1.98
972219AH1-694 GEN
Adder
1.425
316254AC1-120 GEN1
Solar/Wind Harmer
0.2
972135AH1-637 GEN
Solar/Wind Harmer
0.781
966881AG1-559 GEN
Solar/Wind Harmer
0.105
315683AE1-153 C
Solar/Wind Harmer
7.218
3147666LOUISA
Solar/Wind Harmer
0.355
316192AB2-158 GEN
Solar/Wind Harmer
0.501
316337AD2-073 GEN
Solar/Wind Harmer
0.077
3150351NORNECKC2
Adder
0.87
3141726DUNNSVL
Solar/Wind Harmer
0.348
962861AG1-135 GEN
Solar/Wind Harmer
2.764
3151751LOISA D
Adder
5.599
3138133OCRAN
Solar/Wind Harmer
0.051
3142416OLDCHRC
Solar/Wind Harmer
0.22
3142416OLDCHRC
Solar/Wind Harmer
0.084
3141766HARMONY
Solar/Wind Harmer
0.017
971777AH1-397 GEN
Solar/Wind Harmer
0.223
3141843SHACKLE
Adder
0.432
3142433PROV 92
Solar/Wind Harmer
0.337
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143526WINTERP
Solar/Wind Harmer
0.435
3142543TWELFTH
Solar/Wind Harmer
0.008
3150851SPRUNCC
Adder
0.385
944631AF1-128 GEN
Adder
39.853
3143226MDLTHAN
Solar/Wind Harmer
0.083
316159AE1-175 C
Solar/Wind Harmer
0.072
971317AH1-138 GEN
Solar/Wind Harmer
0.618
970129AG2-093 GEN
Solar/Wind Harmer
2.345
316458AB2-190 GEN2
Solar/Wind Harmer
0.442
315671AE2-027_GEN
Solar/Wind Harmer
5.273
3138126ROCKLANDING
Solar/Wind Harmer
0.038
3151731LOISA B
Adder
5.599
3151721LOISA A
Adder
5.57
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.271
3142366NRTHEST
Adder
0.276
3150691DARBY 3
Adder
6.069
3150701DARBY 4
Adder
6.055
3150681DARBY 2
Adder
6.048
3150671DARBY 1
Adder
6.041
316075AC2-137 C
Solar/Wind Harmer
0.023
3142946ENON
Solar/Wind Harmer
0.008
3143526WINTERP
Solar/Wind Harmer
0.435
971223AH1-071 GEN
Solar/Wind Harmer
0.89
944641AF1-129 GEN
Adder
39.415
316240AF1-291 C
Solar/Wind Harmer
0.001
316033AB2-134 GEN
Solar/Wind Harmer
0.005
315697AD1-025 GEN
Solar/Wind Harmer
0.092
316236AE1-162_GEN
Solar/Wind Harmer
0.001
970657AG2-426 GEN
Solar/Wind Harmer
2.829
970657AG2-426 GEN
Solar/Wind Harmer
0.593
316036AC1-147 C
Solar/Wind Harmer
0.015
3150991CHESPKB
Adder
0.845
3150991CHESPKB
Adder
0.825
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.077
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3145506HICKORY
Solar/Wind Harmer
0.321
3145506HICKORY
Solar/Wind Harmer
0.193
3145506HICKORY
Solar/Wind Harmer
0.048
316339AD2-160 GEN
Solar/Wind Harmer
0.13
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.045
3137176SLIGO L2192
Solar/Wind Harmer
0.319
3146456SLIGO L269
Solar/Wind Harmer
1.416
3130086AYDLETT
Solar/Wind Harmer
0.32
3146386ELIZ CT
Solar/Wind Harmer
0.08
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.079
3144356SAPONY
Solar/Wind Harmer
0.657
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.345
3146376EDENTON
Solar/Wind Harmer
0.345
972185AH1-677 GEN
Adder
4.331
972187AH1-678 GEN
Adder
2.184
970933AG2-581 GEN
Solar/Wind Harmer
6.107
316065AD1-022 GEN
Solar/Wind Harmer
3.475
3145893MURPHYS
Solar/Wind Harmer
0.503
3145893MURPHYS
Solar/Wind Harmer
0.135
3146173TUNIS
Solar/Wind Harmer
0.075
3146173TUNIS
Solar/Wind Harmer
0.075
970099AG2-077 GEN
Solar/Wind Harmer
7.908
316181AB2-040 GEN
Solar/Wind Harmer
0.107
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.044
971741AH1-377 GEN
Solar/Wind Harmer
7.304
3146516WINFALL
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.079
3145273HOLLAND
Solar/Wind Harmer
0.059
3146376EDENTON
Solar/Wind Harmer
0.078
315614AA2-178 GEN
Solar/Wind Harmer
0.439
971157AH1-035 GEN
Solar/Wind Harmer
0.911
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
315737AD1-076 GEN
Solar/Wind Harmer
0.975
3146206CASHIE
Solar/Wind Harmer
0.075
316365GEN2_N
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
970917AG2-570 GEN
Solar/Wind Harmer
6.681
957521AF2-046 GEN
Solar/Wind Harmer
5.587
961681AG1-008 GEN
Solar/Wind Harmer
5.587
3146173TUNIS
Solar/Wind Harmer
0.075
3156021HOLLOMANSOL
Solar/Wind Harmer
0.339
316463AE2-346 GEN
Solar/Wind Harmer
0.064
316140AB2-099
Solar/Wind Harmer
0.027
962331AG1-082 GEN
Solar/Wind Harmer
0.795
3146263WOODLND
Solar/Wind Harmer
0.074
313506AB2-031 GEN
Solar/Wind Harmer
0.228
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3145963POPLR C
Solar/Wind Harmer
0.074
970909AG2-566 GEN
Solar/Wind Harmer
0.785
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.073
3147043LAWRENC
Solar/Wind Harmer
0.044
3146776BUCKING
Solar/Wind Harmer
0.026
3146926FARMVIL
Solar/Wind Harmer
0.044
3145796HORNRTN
Solar/Wind Harmer
0.291
3145796HORNRTN
Solar/Wind Harmer
0.073
942461AE2-259 GEN
Solar/Wind Harmer
0
316478AD1-087 GEN
Solar/Wind Harmer
0.254
316486AD2-202 GEN
Solar/Wind Harmer
0.075
3147133PAMPLIN
Solar/Wind Harmer
0.227
971193AH1-056 GEN
Solar/Wind Harmer
4.404
963181AG1-167 GEN
Solar/Wind Harmer
0.289
3144293JTRSVLE
Adder
0.23
316210AC1-098 GEN
Solar/Wind Harmer
0.668
972255AH1-712 GEN
Adder
36.775
3145933PARMELE
Solar/Wind Harmer
0.072
966801AG1-551 GEN
Solar/Wind Harmer
0.836
959311AF2-222 GEN
Solar/Wind Harmer
6.376
970257AG2-171 GEN
Solar/Wind Harmer
2.293
970221AG2-151 GEN
Solar/Wind Harmer
3.817
315785AD2-033 C
Solar/Wind Harmer
0.582
964241AG1-285 GEN
Solar/Wind Harmer
4.753
316131AB2-060 GEN
Solar/Wind Harmer
0.224
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
315724AD1-057 GEN
Solar/Wind Harmer
0.266
316327AA2-057 GEN
Solar/Wind Harmer
0.106
3146233WITAKRS
Solar/Wind Harmer
0.35
3146233WITAKRS
Solar/Wind Harmer
0.047
3146073TAR RVR
Solar/Wind Harmer
0.07
3146083TARBORO
Solar/Wind Harmer
0.07
3138543CONSLDL
Solar/Wind Harmer
0.046
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.069
961601AG1-000A GEN
Solar/Wind Harmer
4.912
971623AH1-311 GEN
Solar/Wind Harmer
0.138
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.87
971683AH1-343 GEN
Solar/Wind Harmer
2.391
3148013FISHERV
Solar/Wind Harmer
0.065
316283AC2-100 C
Solar/Wind Harmer
0.124
315616AA1-038_C
Solar/Wind Harmer
0
3151861LOWMORA
Adder
0.645
958131AF2-107 GEN
Solar/Wind Harmer
1.618
226910AB2-157 C
Solar/Wind Helper
0.02
227287AC2-120 GEN
Solar/Wind Helper
0.49
237030AB1-096 C
Solar/Wind Helper
0.083
223402AF1-300 C
Solar/Wind Helper
0.397
205917AD1-020 ES
Solar/Wind Helper
0.318
238221AF1-254 C O1
Solar/Wind Helper
0.179
235067AD1-061 GEN
Solar/Wind Helper
0.312
233982AB2-133 GEN
Solar/Wind Helper
0.216
233918AB1-142 GEN
Solar/Wind Helper
0.303
233994AC2-023 GEN
Solar/Wind Helper
0.577
233996TM1833_GEN
Solar/Wind Helper
0.157
233997TMININ_4.2
Solar/Wind Helper
0.157
233940AF2-379 C
Solar/Wind Helper
0.037
234015AF2-250 C
Solar/Wind Helper
0.023
233952AC2-187 GEN
Solar/Wind Helper
0.139
232406W1-004 FULL
Solar/Wind Helper
0.304
233971AC1-093 C
Solar/Wind Helper
0.214
230430AE1-229_GEN
Solar/Wind Helper
1.995
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.089
228729W2-030 C
Solar/Wind Helper
0.065
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20716028EGP_W2-019
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.037
20715028HAN_X4-015
Solar/Wind Helper
0.033
970301AG2-198 GEN
Solar/Wind Harmer
3.138
316426AA2-053 GEN
Solar/Wind Harmer
0.248
3146776BUCKING
Solar/Wind Harmer
0.293
3145593CAROLNA
Solar/Wind Harmer
0.073
3145593CAROLNA
Solar/Wind Harmer
0.073
3146776BUCKING
Solar/Wind Harmer
0.024
966811AG1-552 GEN
Solar/Wind Harmer
0.795
3145593CAROLNA
Solar/Wind Harmer
0.091
3145783HORNRTN
Solar/Wind Harmer
1.299
3145783HORNRTN
Solar/Wind Harmer
1.039
3145783HORNRTN
Solar/Wind Harmer
0.325
3145783HORNRTN
Solar/Wind Harmer
0.13
3145796HORNRTN
Solar/Wind Harmer
0.219
3147133PAMPLIN
Solar/Wind Harmer
0.072
3147133PAMPLIN
Solar/Wind Harmer
0.058
958211AF2-115 GEN
Solar/Wind Harmer
0.866
963191AG1-168 GEN
Solar/Wind Harmer
0.289
3144293JTRSVLE
Adder
0.23
3144293JTRSVLE
Adder
0.193
3145933PARMELE
Solar/Wind Harmer
0.144
3145933PARMELE
Solar/Wind Harmer
0.072
316274AC1-208 GEN
Solar/Wind Harmer
0.372
316034AC1-036 C
Solar/Wind Harmer
0.005
970323AG2-213 GEN
Solar/Wind Harmer
3.057
971775AH1-396 GEN
Solar/Wind Harmer
0.115
971489AH1-241 GEN
Solar/Wind Harmer
3.817
313527AB2-043 GEN
Solar/Wind Harmer
0.001
939181AE1-148 GEN
Solar/Wind Harmer
3.402
3145493TOT1
Solar/Wind Harmer
0.162
3145453TOT5
Solar/Wind Harmer
0.097
3145603CNETO
Solar/Wind Harmer
0.065
315821AE2-092 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
3.322
961601AG1-000A GEN
Solar/Wind Harmer
1.228
316263AC1-034 GEN
Solar/Wind Harmer
2.624
964791AG1-342 GEN
Solar/Wind Harmer
1.322
3146843MT LREL
Solar/Wind Harmer
0.069
3146843MT LREL
Solar/Wind Harmer
0.069
316222AC1-221 GEN
Solar/Wind Harmer
0.264
971761AH1-387 GEN
Solar/Wind Harmer
1.238
942751AE2-291 GEN
Solar/Wind Harmer
3.276
3132123MT JACKSON
Solar/Wind Harmer
0.183
970117AG2-086 GEN
Solar/Wind Harmer
1.401
970117AG2-086 GEN
Solar/Wind Harmer
0.934
226929AD2-058 GEN
Solar/Wind Helper
0.143
237025AB1-124 C
Solar/Wind Helper
0.193
237006AB1-125 GEN
Solar/Wind Helper
0.145
23777801MSM_W1-116
Solar/Wind Helper
0.13
237034AC2-136 C
Solar/Wind Helper
0.205
205916AD1-020 GEN
Solar/Wind Helper
1.48
208835TUHI V3-051
Solar/Wind Helper
0.019
208835TUHI V3-051
Solar/Wind Helper
0.019
237001AB1-127_GEN
Solar/Wind Helper
0.307
237002AB1-128_GEN
Solar/Wind Helper
0.298
235063AE1-101 C2
Solar/Wind Helper
1.064
20390526W1-045 C
Solar/Wind Helper
0.252
23777901MDS_W4-102
Solar/Wind Helper
0.105
235020AA1-095 C
Solar/Wind Helper
0.029
233933AB2-153 GEN
Solar/Wind Helper
0.14
233944AB2-135 GEN
Solar/Wind Helper
0.355
232424Y1-079 C
Solar/Wind Helper
0.07
233987AB2-037 GEN
Solar/Wind Helper
1.406
233946AB2-136 GEN
Solar/Wind Helper
0.341
234036AF2-325 C
Solar/Wind Helper
0.025
233901CHERRYDALE C
Solar/Wind Helper
0.139
232408W1-005 C
Solar/Wind Helper
0.304
232410W1-006 C
Solar/Wind Helper
0.304
233939AC1-091 C
Solar/Wind Helper
0.209
233970AC1-092 C
Solar/Wind Helper
0.209
230433AD2-135 GEN
Solar/Wind Helper
0.01
219921AF1-264
Solar/Wind Helper
0.03
230407AD2-065 C
Solar/Wind Helper
0.024
219615MILLCREEK C
Solar/Wind Helper
0.016
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20714928UPF_X1-085
Solar/Wind Helper
0.003
20720628TIN_W1-124
Solar/Wind Helper
0.11
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.009
207442AE1-156 GEN
Solar/Wind Helper
0.188
20676128MHD_W3-029
Solar/Wind Helper
0.055
20671828STAW2-080
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
207471AF2-354 C
Solar/Wind Helper
0.097
20674928WA_W3-044
Solar/Wind Helper
0.056
964851AG1-348 GEN
Solar/Wind Helper
0.046
20674128FR_U2-059
Solar/Wind Helper
0.002
20676228FRD_X1-012
Solar/Wind Helper
0.052
966111AG1-480 GEN
Solar/Wind Helper
0.042
211065PSPA IPP
Solar/Wind Helper
0.085
211065PSPA IPP
Solar/Wind Helper
0.085
208972BECR K09
Solar/Wind Helper
0.178
961431AF2-434 GEN
Solar/Wind Helper
0.236
209029WAYMART-WD
Solar/Wind Helper
0.443
209054AE2-059 GEN
Solar/Wind Helper
0.042
946751AF1-339 GEN
Solar/Wind Helper
0.233
209137AF2-361 C
Solar/Wind Helper
0.708
219276PARKLANDSO C
Solar/Wind Helper
0.052
20714528FRN_Y2-051
Solar/Wind Helper
0.033
20720528MAN_W1-024
Solar/Wind Helper
0.016
219612MATRIX C
Solar/Wind Helper
0.014
218438BLK ROCK C
Solar/Wind Helper
0.016
20673728F2S_V4-070
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
219919AE1-041 FULL
Solar/Wind Helper
0.002
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
207510AF2-138 C
Solar/Wind Helper
0.046
20674628WNG_W3-110
Solar/Wind Helper
0.051
963161AG1-165 GEN
Solar/Wind Helper
0.242
963071AG1-156 GEN
Solar/Wind Helper
0.783
209027LOR2_Q27
Solar/Wind Helper
0.557
961331AF2-424 GEN
Solar/Wind Helper
0.237
961421AF2-433 GEN
Solar/Wind Helper
0.236
957921AF2-086 GEN
Solar/Wind Helper
0.234
946691AF1-333 GEN
Solar/Wind Helper
0.233
946741AF1-338 GEN
Solar/Wind Helper
0.233
209067AE2-060 GEN
Solar/Wind Helper
0.042
971069AG2-661 GEN
Solar/Wind Harmer
1.462
971647AH1-324 GEN
Solar/Wind Harmer
3.497
961611AG1-000B GEN
Solar/Wind Harmer
4.29
3151171GRAVELC
Adder
0.868
3145336SMITFLD
Solar/Wind Harmer
0.325
316294AC1-161 GEN
Solar/Wind Harmer
1.405
970659AG2-427 GEN
Solar/Wind Harmer
3.913
316381AD1-082 GEN
Solar/Wind Harmer
0.084
316375AC2-012 GEN
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
8.025
3150981CHESPKA
Adder
1.007
944591AF1-124 GEN
Solar/Wind Harmer
18.213
316072AD1-144
Solar/Wind Harmer
0.029
316388AE2-253 GEN
Solar/Wind Harmer
0.251
3146456SLIGO L269
Solar/Wind Harmer
0.08
939411AE1-173 GEN
Solar/Wind Harmer
34.166
316246AF1-032 C
Solar/Wind Harmer
0.036
940641AE2-051 GEN
Solar/Wind Harmer
6.396
316093AE2-104_GEN
Solar/Wind Harmer
1.342
3143336POWHATN
Solar/Wind Harmer
1.412
3146516WINFALL
Solar/Wind Harmer
0.256
3146516WINFALL
Solar/Wind Harmer
0.079
316336AC2-165 C
Solar/Wind Harmer
0.003
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.078
3145663CRESWEL
Solar/Wind Harmer
0.215
971163AH1-040 GEN
Solar/Wind Harmer
6.133
970937AG2-583 GEN
Solar/Wind Harmer
4.64
3146206CASHIE
Solar/Wind Harmer
0.075
971547AH1-271 GEN
Solar/Wind Harmer
1.606
316023GEN1_S
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
0.301
3145893MURPHYS
Solar/Wind Harmer
0.334
970919AG2-571 GEN
Solar/Wind Harmer
2.672
970087AG2-069 GEN
Solar/Wind Harmer
5.999
3146173TUNIS
Solar/Wind Harmer
0.075
960081AF2-299 GEN
Solar/Wind Harmer
0.714
3145683EARLEYS
Solar/Wind Harmer
0.074
957481AF2-042 GEN
Solar/Wind Harmer
19.771
3146263WOODLND
Solar/Wind Harmer
0.074
315693AD1-088 GEN
Solar/Wind Harmer
3.545
962491AG1-098 GEN
Solar/Wind Harmer
4.214
971795AH1-408 GEN
Solar/Wind Harmer
4.913
3145963POPLR C
Solar/Wind Harmer
0.074
316011AB1-132 GEN
Solar/Wind Harmer
1.337
962571AG1-106 GEN
Solar/Wind Harmer
1.046
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.073
3147043LAWRENC
Adder
0.664
972003AH1-546 GEN
Solar/Wind Harmer
3.117
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.029
3146926FARMVIL
Solar/Wind Harmer
0.044
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145783HORNRTN
Solar/Wind Harmer
0.073
3145796HORNRTN
Solar/Wind Harmer
0.24
3145796HORNRTN
Solar/Wind Harmer
0.073
963171AG1-166 GEN
Solar/Wind Harmer
0.385
971563AH1-280 GEN
Solar/Wind Harmer
0.77
3144293JTRSVLE
Adder
0.23
316212AC1-099_GEN
Solar/Wind Harmer
0.372
970685AG2-442 GEN
Solar/Wind Harmer
5.37
972277AH1-723 GEN
Adder
42.854
3146293MARTNCO
Solar/Wind Harmer
0.067
316129AC1-054 GEN
Solar/Wind Harmer
0.27
971377AH1-170 GEN
Solar/Wind Harmer
0.763
3147623JAMES R
Solar/Wind Harmer
0.166
971065AG2-659 GEN
Solar/Wind Harmer
3.053
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315722AD1-056 GEN
Solar/Wind Harmer
0.448
315687AD1-152 GEN
Solar/Wind Harmer
0.002
316494AC1-189 GEN
Solar/Wind Harmer
0.238
3146233WITAKRS
Solar/Wind Harmer
0.278
961671AG1-007 GEN
Solar/Wind Harmer
0.011
3146083TARBORO
Solar/Wind Harmer
0.07
3145493TOT1
Solar/Wind Harmer
0.31
316359AB2-059 GEN
Solar/Wind Harmer
0.248
316049AB1-081 GEN
Solar/Wind Harmer
0.395
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.055
3142053HEARTS
Solar/Wind Harmer
0.122
970401AG2-262 GEN
Solar/Wind Harmer
0.404
316003AC1-222 GEN
Solar/Wind Harmer
0.002
315705AF1-075 GEN
Solar/Wind Harmer
2.472
3147983MERCK5
Solar/Wind Harmer
0.024
23779801AA1-109
Solar/Wind Helper
0.218
223401AF1-299 GEN
Solar/Wind Helper
0.397
966131AG1-482 GEN
Solar/Wind Helper
0.111
237080AD1-060 GEN
Solar/Wind Helper
0.221
235062AE1-101 C1
Solar/Wind Helper
1.064
237038AE2-054 C
Solar/Wind Helper
0.173
233930AB2-032 GEN
Solar/Wind Helper
0.23
233915AB1-141 GEN
Solar/Wind Helper
0.303
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
233998TM1NIN_3.36
Solar/Wind Helper
0.157
232428Y3-058 C
Solar/Wind Helper
0.203
233954AC2-188 GEN
Solar/Wind Helper
0.139
232404W1-003 C
Solar/Wind Helper
0.304
233950AC2-186 GEN
Solar/Wind Helper
0.07
232434Z2-077 GEN
Solar/Wind Helper
0.076
233972AC1-094 C
Solar/Wind Helper
0.181
205941AD2-115 GEN
Solar/Wind Helper
0.302
230434AG1-499 GEN
Solar/Wind Helper
0.136
230511AF1-262
Solar/Wind Helper
0.009
219258KINSLEYDEP C
Solar/Wind Helper
0.045
228728W1-130C
Solar/Wind Helper
0.032
219904AC1-010 C
Solar/Wind Helper
0.036
219907AC1-030 C
Solar/Wind Helper
0.02
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
20720728JCB_W1-129
Solar/Wind Helper
0.033
207445AB1-138_GEN
Solar/Wind Helper
0.061
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
207454AA2-184 E
Solar/Wind Helper
0.18
20715228NPK_W1-113
Solar/Wind Helper
0.045
20742028HF_AC1-207
Solar/Wind Helper
0.082
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
20675428EAM_W2-061
Solar/Wind Helper
0.009
218428ETC SOLAR C
Solar/Wind Helper
0.003
20676428JCR_X2-075
Solar/Wind Helper
0.039
217213AMBOY SO C
Solar/Wind Helper
0.017
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.013
207437AD2-070 GEN
Solar/Wind Helper
0.079
207439AE1-081 C O1
Solar/Wind Helper
0.011
207518AF1-320_GEN
Solar/Wind Helper
0.9
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
212266LOR1
Solar/Wind Helper
0.026
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.829
946731AF1-337 GEN
Solar/Wind Helper
0.233
209071AE2-133 GEN
Solar/Wind Helper
0.042
970053AG2-049 GEN
50/50
2.022
3138216PACIFIC
Solar/Wind Harmer
0.025
316411AF1-147_GEN1
Solar/Wind Harmer
0.003
316415AF1-147_GEN2
Solar/Wind Harmer
0.003
3141426STAFORD
Solar/Wind Harmer
0.023
3150411LDYSMT5
Adder
12.718
3150381LDYSMT2
Adder
12.172
972213AH1-691 GEN
Adder
2.059
972215AH1-692 GEN
Adder
2.059
316164AC1-076 GEN
Solar/Wind Harmer
0.132
944491AF1-114 GEN
Solar/Wind Harmer
0
316223AC1-118
Solar/Wind Harmer
0.064
972189AH1-679 GEN
Adder
1.467
3141813NORNECK
Solar/Wind Harmer
0.087
970327AG2-215 GEN
Solar/Wind Harmer
2.824
962981AG1-147 GEN
Solar/Wind Harmer
3.203
3141783LANCAST
Solar/Wind Harmer
0.051
3141783LANCAST
Solar/Wind Harmer
0.034
3138133OCRAN
Solar/Wind Harmer
0.025
3141913WHIT STONE
Solar/Wind Harmer
0.085
3147346CASHSCORNER
Solar/Wind Harmer
0.196
316312AB1-027
Solar/Wind Harmer
0.152
316314AB2-024 C
Solar/Wind Harmer
0
316059AD1-063 C
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.017
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
2.507
3143873LANEXA
Solar/Wind Harmer
0.051
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
971167AH1-042 GEN
Solar/Wind Harmer
7.477
315976AC1-164 GENA
Solar/Wind Harmer
8.72
316169AC1-164_GENC
Solar/Wind Harmer
7.533
315975AC1-164 GENB
Solar/Wind Harmer
0.258
316233AE1-074 FULL
Solar/Wind Harmer
0.067
971281AH1-106 GEN
Solar/Wind Harmer
1.161
971283AH1-107 GEN
Solar/Wind Harmer
1.161
971285AH1-108 GEN
Adder
0.631
3138283WHITEMARSH
Solar/Wind Harmer
0.019
316132AB2-190 GEN1
Solar/Wind Harmer
0.442
316369SG1_INVT
Solar/Wind Harmer
0.003
972265AH1-717 GEN
Adder
6.337
3151201GRAVEL4
Adder
5.94
3151191GRAVEL3
Adder
5.865
3151211GRAVEL5
Adder
5.865
971445AH1-216 GEN
Solar/Wind Harmer
5.723
3143316POE
Solar/Wind Harmer
0.321
3151081ELIZAR1
Adder
7.394
3151091ELIZAR2
Adder
7.266
3152611GOSPORTB
Adder
1.027
3152621GOSPORTC
Adder
0.872
3152601GOSPORTA
Adder
0.804
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.055
316311AC2-079 GEN
Solar/Wind Harmer
2.303
957871AF2-081 GEN
Solar/Wind Harmer
3.99
316305AF2-043 C
Solar/Wind Harmer
0.001
319010AE1-072 C
Solar/Wind Harmer
0.403
3146406KITTY HAWK
Solar/Wind Harmer
0.01
315835AF2-110_GEN
Solar/Wind Harmer
0.548
313526AB2-022
Solar/Wind Harmer
0.043
3146486SUNBURY
Solar/Wind Harmer
0.079
3146486SUNBURY
Solar/Wind Harmer
0.079
316321Z2-027
Solar/Wind Harmer
0.015
3146396TANGLEW
Solar/Wind Harmer
0.219
3145176PASQUOTANK
Solar/Wind Harmer
0.049
316315AB2-025 C
Solar/Wind Harmer
0.064
315814AE2-033 C
Solar/Wind Harmer
6.204
941031AE2-094 GEN
Solar/Wind Harmer
14.412
944011AF1-069 GEN
Solar/Wind Harmer
4.709
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.078
3130156CHOWAN
Solar/Wind Harmer
0.078
970673AG2-436 GEN
Solar/Wind Harmer
16.54
970673AG2-436 GEN
Solar/Wind Harmer
11.027
971967AH1-528 GEN
Solar/Wind Harmer
12.344
315816AE2-034 GEN
Solar/Wind Harmer
0.329
3130546PLYMOUTH
Solar/Wind Harmer
0.076
315732AD1-074 GEN1
Solar/Wind Harmer
0.435
315733AD1-074 GEN2
Solar/Wind Harmer
0.435
315735AD1-075 GEN1
Solar/Wind Harmer
0.218
965291AG1-394 GEN
Solar/Wind Harmer
0.336
3146206CASHIE
Solar/Wind Harmer
0.075
970601AG2-382 GEN
Solar/Wind Harmer
2.811
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
970085AG2-068 GEN
Solar/Wind Harmer
4
970581AG2-369 GEN
Solar/Wind Harmer
3.44
3145513AHOSKIE
Solar/Wind Harmer
0.156
3145513AHOSKIE
Solar/Wind Harmer
0.074
3146043SEABORD
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.149
3145683EARLEYS
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.074
315607AA1-063A GEN
Solar/Wind Harmer
0.152
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.294
315652AC1-086 GEN
Solar/Wind Harmer
8.087
972205AH1-687 GEN
Adder
3.134
970285AG2-188 GEN
Solar/Wind Harmer
5.802
971845AH1-439 GEN
Solar/Wind Harmer
3.325
3145796HORNRTN
Solar/Wind Harmer
0.233
3145796HORNRTN
Solar/Wind Harmer
0.029
3146033SCOT NK
Solar/Wind Harmer
0.29
315657AE1-056 GEN
Solar/Wind Harmer
2.494
946301AF1-294 GEN
Solar/Wind Harmer
1.424
961791AG1-021 GEN
Solar/Wind Harmer
0.693
970683AG2-441 GEN
Solar/Wind Harmer
4.794
970681AG2-440 GEN
Solar/Wind Harmer
3.836
970831AG2-522 GEN
Solar/Wind Harmer
3.066
972193AH1-681 GEN
Adder
1.643
3144303KENBRDG
Solar/Wind Harmer
0.057
971443AH1-215 GEN
Solar/Wind Harmer
1.204
971447AH1-217 GEN
Solar/Wind Harmer
2.163
316005AA1-067
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.282
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
970181AG2-120 GEN
Solar/Wind Harmer
0.883
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3138266HYDRAULIC
Solar/Wind Harmer
0.003
3138266HYDRAULIC
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
3.032
316420AA1-050 GEN
Solar/Wind Harmer
0.002
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.07
3145573BETHELC
Solar/Wind Harmer
0.07
316118AC1-105 GEN
Solar/Wind Harmer
0.176
3147173SINAI
Solar/Wind Harmer
0.067
3147243WELCO
Solar/Wind Harmer
0.042
270494AE1-108_GEN
Solar/Wind Harmer
0.802
3148133STUARTS
Solar/Wind Harmer
0.039
3148013FISHERV
Solar/Wind Harmer
0.037
970865AG2-541 GEN
Solar/Wind Harmer
2.214
316123AC1-075 GEN
Solar/Wind Harmer
0.084
970165AG2-112 GEN
Solar/Wind Harmer
0.5
970163AG2-111 GEN
Solar/Wind Harmer
0.477
3148463FAIRFLD
Solar/Wind Harmer
0.06
3151881LOWMORC
Adder
0.64
3151881LOWMORC
Adder
0.63
3151861LOWMORA
Adder
0.62
960921AF2-383 GEN
Solar/Wind Helper
0.279
205943AE1-185 GEN
Solar/Wind Helper
0.387
205956AE1-196_GEN
Solar/Wind Helper
0.385
205932AD2-116_GEN
Solar/Wind Helper
0.385
959381AF2-229 GEN
Solar/Wind Helper
0.257
237085AD2-009_GEN
Solar/Wind Helper
0.97
203975AE1-071-GEN
Solar/Wind Helper
1.713
233935AB2-179 C
Solar/Wind Helper
0.772
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.575
233990AG1-397 GEN
Solar/Wind Helper
0.162
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.208
964001AG1-254 GEN
Solar/Wind Helper
0.565
219914AD2-027 C
Solar/Wind Helper
0.068
227927V4-067C
Solar/Wind Helper
0.006
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
219607WPEMNERT C
Solar/Wind Helper
0.047
214067T20SOLAR
Solar/Wind Helper
0.007
20715728PEM_W1-119
Solar/Wind Helper
0.056
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
966261AG1-495 GEN
Solar/Wind Helper
0.047
20675928HOL_W4-097
Solar/Wind Helper
0.029
207530AG1-191 GEN
Solar/Wind Helper
0.038
207484AF2-139 C O1
Solar/Wind Helper
0.048
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
20675128HRM_W1-127
Solar/Wind Helper
0.017
209116AE2-175 GEN
Solar/Wind Helper
1.004
961261AF2-417 GEN
Solar/Wind Helper
0.241
959431AF2-234 GEN
Solar/Wind Helper
0.466
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
959421AF2-233 GEN
Solar/Wind Helper
0.233
238208AF1-136 C
Solar/Wind Helper
0.089
LAGNLTFEXP_LAGN->PJM
CLTF
6.324
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.485
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.592
MECLTFEXP_MEC->PJM
CLTF
4.449
SIGELTFEXP_SIGE->PJM
CLTF
0.14
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.565
TVALTFEXP_TVA->PJM
CLTF
3.188
NYPJM->LTFIMP_NY
CLTF
2.575
LGEELTFEXP_LGEE->PJM
CLTF
1.805
WECLTFEXP_WEC->PJM
CLTF
0.962
CPLELTFEXP_CPLE->PJM
CLTF
5.065
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.965

Details for 6EDMONSON-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6SEDGE HILL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.9 %
Rating:997.0 MVA
Rating Type:C
MVA to Mitigate:1035.9
MW Contribution:7.27
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
13.015
3144293JTRSVLE
50/50
0.686
3151601KERR 3
50/50
0.363
3151581KERR 1
50/50
0.13
3151931BEARGRDN S1
50/50
1.418
3151911BEARGRDN G1
50/50
1.099
315687AD1-152 GEN
Solar/Wind Harmer
9.7
957481AF2-042 GEN
Solar/Wind Harmer
201.833
315693AD1-088 GEN
Solar/Wind Harmer
29.361
962491AG1-098 GEN
Solar/Wind Harmer
38.734
3146926FARMVIL
Solar/Wind Harmer
-0.019
316322AB2-045
Solar/Wind Harmer
0.788
3146776BUCKING
Solar/Wind Harmer
-0.009
963171AG1-166 GEN
Solar/Wind Harmer
2.851
971563AH1-280 GEN
Solar/Wind Harmer
2.851
970685AG2-442 GEN
Solar/Wind Harmer
18.365
971065AG2-659 GEN
Solar/Wind Harmer
7.646
972003AH1-546 GEN
Solar/Wind Harmer
7.552
316129AC1-054 GEN
Solar/Wind Harmer
1.263
316237AB2-079_GEN
Solar/Wind Harmer
0.417
971377AH1-170 GEN
Solar/Wind Harmer
1.453
3147623JAMES R
Solar/Wind Harmer
0.18
970937AG2-583 GEN
Solar/Wind Harmer
7.798
316336AC2-165 C
Solar/Wind Harmer
1.386
3147043LAWRENC
Adder
0.584
3143336POWHATN
Solar/Wind Harmer
0.814
316003AC1-222 GEN
Solar/Wind Helper
1.516
3147123OTTER R
Solar/Wind Helper
0.083
3147312GRETNA
Solar/Wind Helper
0.093
3146802CHATHAM
Solar/Wind Helper
0.087
270016AE1-250 BESS
Solar/Wind Helper
0.416
3151541CLOVER2
50/50
12.953
3151611KERR 4
50/50
0.363
3151621KERR 5
50/50
0.363
3151631KERR 6
50/50
0.363
3151641KERR 7
50/50
0.363
972205AH1-687 GEN
50/50
5.359
971967AH1-528 GEN
Solar/Wind Harmer
119.231
970285AG2-188 GEN
Solar/Wind Harmer
22.292
971845AH1-439 GEN
Solar/Wind Harmer
12.82
315657AE1-056 GEN
Solar/Wind Harmer
9.035
946301AF1-294 GEN
Solar/Wind Harmer
5.845
961791AG1-021 GEN
Solar/Wind Harmer
2.851
970683AG2-441 GEN
Solar/Wind Harmer
16.398
970681AG2-440 GEN
Solar/Wind Harmer
13.118
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.717
316239AB2-077_GEN
Solar/Wind Harmer
0.417
316238AB2-078_GEN
Solar/Wind Harmer
0.417
970831AG2-522 GEN
Solar/Wind Harmer
6.725
971447AH1-217 GEN
Solar/Wind Harmer
3.924
270494AE1-108_GEN
Solar/Wind Harmer
2.176
3147173SINAI
Solar/Wind Helper
0.374
3147243WELCO
Solar/Wind Helper
0.234
316123AC1-075 GEN
Solar/Wind Helper
1.587
316118AC1-105 GEN
Solar/Wind Helper
0.947
270455AD2-022 GEN
Solar/Wind Helper
0.922
270457AD2-023 GEN
Solar/Wind Helper
0.608
3144293JTRSVLE
50/50
0.686
3144293JTRSVLE
50/50
0.578
970535AG2-341 GEN
50/50
2.746
970099AG2-077 GEN
Solar/Wind Harmer
80.733
970933AG2-581 GEN
Solar/Wind Harmer
59.456
971741AH1-377 GEN
Solar/Wind Harmer
54.374
970301AG2-198 GEN
Solar/Wind Harmer
21.608
3147133PAMPLIN
Solar/Wind Harmer
-0.024
3147133PAMPLIN
Solar/Wind Harmer
-0.019
3146776BUCKING
Solar/Wind Harmer
-0.093
3146776BUCKING
Solar/Wind Harmer
-0.008
958211AF2-115 GEN
Solar/Wind Harmer
3.564
963191AG1-168 GEN
Solar/Wind Harmer
2.139
316034AC1-036 C
Solar/Wind Harmer
0.354
970323AG2-213 GEN
Solar/Wind Harmer
9.517
971775AH1-396 GEN
Solar/Wind Harmer
1.355
939181AE1-148 GEN
Solar/Wind Harmer
10.582
313527AB2-043 GEN
Solar/Wind Harmer
2.387
971489AH1-241 GEN
Solar/Wind Harmer
6.899
315821AE2-092 GEN
Solar/Wind Harmer
1.789
316222AC1-221 GEN
Solar/Wind Helper
1.594
316197AC1-042 GEN
Solar/Wind Helper
0.109
270013AE1-250 PV
Solar/Wind Helper
0.416
3146843MT LREL
Solar/Wind Helper
0.112
3146843MT LREL
Solar/Wind Helper
0.112
970413AG2-270 GEN
50/50
56.795
3144293JTRSVLE
50/50
0.686
3151591KERR 2
50/50
0.363
3151921BEARGRDN G2
50/50
1.099
316478AD1-087 GEN
Solar/Wind Harmer
5.94
316486AD2-202 GEN
Solar/Wind Harmer
1.74
970909AG2-566 GEN
Solar/Wind Harmer
4.103
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.165
3147133PAMPLIN
Solar/Wind Harmer
-0.075
971193AH1-056 GEN
Solar/Wind Harmer
15.059
3146776BUCKING
Solar/Wind Harmer
-0.008
963181AG1-167 GEN
Solar/Wind Harmer
2.139
959311AF2-222 GEN
Solar/Wind Harmer
20.462
970257AG2-171 GEN
Solar/Wind Harmer
7.138
315785AD2-033 C
Solar/Wind Harmer
4.14
964241AG1-285 GEN
Solar/Wind Harmer
12.684
316131AB2-060 GEN
Solar/Wind Harmer
1.616
970221AG2-151 GEN
Solar/Wind Harmer
7.267
3147043LAWRENC
Solar/Wind Harmer
-0.004
316313AB2-026
Solar/Wind Harmer
0.185
316258AE1-075 C
Solar/Wind Harmer
0.166
316405AF2-144 C
Solar/Wind Harmer
0.176
3143336POWHATN
Solar/Wind Harmer
0.692
316248AF1-058 C
Solar/Wind Helper
0.503
316283AC2-100 C
Solar/Wind Helper
1.45
3147312GRETNA
Solar/Wind Helper
0.023
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.756
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.372
VTFLTFEXP_VFT->PJM
CMTX
1.612
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.251
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.119
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.61
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.686
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
2.242

Details for 6EDMONSON-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6SEDGE HILL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.06 %
Rating:997.0 MVA
Rating Type:C
MVA to Mitigate:1017.58
MW Contribution:7.28
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
13.001
3144293JTRSVLE
50/50
0.685
3151601KERR 3
50/50
0.362
3151581KERR 1
50/50
0.129
3151931BEARGRDN S1
50/50
1.421
3151911BEARGRDN G1
50/50
1.101
315687AD1-152 GEN
Solar/Wind Harmer
9.69
957481AF2-042 GEN
Solar/Wind Harmer
201.613
315693AD1-088 GEN
Solar/Wind Harmer
29.329
962491AG1-098 GEN
Solar/Wind Harmer
38.693
3146926FARMVIL
Solar/Wind Harmer
-0.019
316322AB2-045
Solar/Wind Harmer
0.788
3146776BUCKING
Solar/Wind Harmer
-0.009
963171AG1-166 GEN
Solar/Wind Harmer
2.847
971563AH1-280 GEN
Solar/Wind Harmer
2.847
970685AG2-442 GEN
Solar/Wind Harmer
18.33
971065AG2-659 GEN
Solar/Wind Harmer
7.623
972003AH1-546 GEN
Solar/Wind Harmer
7.562
316129AC1-054 GEN
Solar/Wind Harmer
1.259
316237AB2-079_GEN
Solar/Wind Harmer
0.415
971377AH1-170 GEN
Solar/Wind Harmer
1.456
3147623JAMES R
Solar/Wind Harmer
0.18
970937AG2-583 GEN
Solar/Wind Harmer
7.825
316336AC2-165 C
Solar/Wind Harmer
1.396
3147043LAWRENC
Adder
0.584
3143336POWHATN
Solar/Wind Harmer
0.821
316003AC1-222 GEN
Solar/Wind Helper
1.523
3147123OTTER R
Solar/Wind Helper
0.083
3147312GRETNA
Solar/Wind Helper
0.093
3146802CHATHAM
Solar/Wind Helper
0.087
270016AE1-250 BESS
Solar/Wind Helper
0.421
3151541CLOVER2
50/50
12.939
3151611KERR 4
50/50
0.362
3151621KERR 5
50/50
0.362
3151631KERR 6
50/50
0.362
3151641KERR 7
50/50
0.362
972205AH1-687 GEN
50/50
5.369
971967AH1-528 GEN
Solar/Wind Harmer
119.102
970285AG2-188 GEN
Solar/Wind Harmer
22.288
971845AH1-439 GEN
Solar/Wind Harmer
12.819
315657AE1-056 GEN
Solar/Wind Harmer
9.023
946301AF1-294 GEN
Solar/Wind Harmer
5.836
961791AG1-021 GEN
Solar/Wind Harmer
2.847
970683AG2-441 GEN
Solar/Wind Harmer
16.366
970681AG2-440 GEN
Solar/Wind Harmer
13.093
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.708
316239AB2-077_GEN
Solar/Wind Harmer
0.415
316238AB2-078_GEN
Solar/Wind Harmer
0.415
970831AG2-522 GEN
Solar/Wind Harmer
6.705
971447AH1-217 GEN
Solar/Wind Harmer
3.932
270494AE1-108_GEN
Solar/Wind Harmer
2.178
3147173SINAI
Solar/Wind Helper
0.376
3147243WELCO
Solar/Wind Helper
0.235
316123AC1-075 GEN
Solar/Wind Helper
1.594
316118AC1-105 GEN
Solar/Wind Helper
0.953
270455AD2-022 GEN
Solar/Wind Helper
0.936
270457AD2-023 GEN
Solar/Wind Helper
0.617
3144293JTRSVLE
50/50
0.685
3144293JTRSVLE
50/50
0.577
970535AG2-341 GEN
50/50
2.737
970099AG2-077 GEN
Solar/Wind Harmer
80.645
970933AG2-581 GEN
Solar/Wind Harmer
59.392
971741AH1-377 GEN
Solar/Wind Harmer
54.323
970301AG2-198 GEN
Solar/Wind Harmer
21.589
3147133PAMPLIN
Solar/Wind Harmer
-0.024
3147133PAMPLIN
Solar/Wind Harmer
-0.019
3146776BUCKING
Solar/Wind Harmer
-0.093
3146776BUCKING
Solar/Wind Harmer
-0.008
958211AF2-115 GEN
Solar/Wind Harmer
3.559
963191AG1-168 GEN
Solar/Wind Harmer
2.135
316034AC1-036 C
Solar/Wind Harmer
0.353
970323AG2-213 GEN
Solar/Wind Harmer
9.495
971775AH1-396 GEN
Solar/Wind Harmer
1.352
939181AE1-148 GEN
Solar/Wind Harmer
10.548
313527AB2-043 GEN
Solar/Wind Harmer
2.378
971489AH1-241 GEN
Solar/Wind Harmer
6.911
315821AE2-092 GEN
Solar/Wind Harmer
1.794
316222AC1-221 GEN
Solar/Wind Helper
1.608
316197AC1-042 GEN
Solar/Wind Helper
0.109
270013AE1-250 PV
Solar/Wind Helper
0.421
3146843MT LREL
Solar/Wind Helper
0.113
3146843MT LREL
Solar/Wind Helper
0.113
970413AG2-270 GEN
50/50
56.734
3144293JTRSVLE
50/50
0.685
3151591KERR 2
50/50
0.362
3151921BEARGRDN G2
50/50
1.101
316478AD1-087 GEN
Solar/Wind Harmer
5.933
316486AD2-202 GEN
Solar/Wind Harmer
1.738
970909AG2-566 GEN
Solar/Wind Harmer
4.099
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.161
3147133PAMPLIN
Solar/Wind Harmer
-0.075
971193AH1-056 GEN
Solar/Wind Harmer
15.038
3146776BUCKING
Solar/Wind Harmer
-0.008
963181AG1-167 GEN
Solar/Wind Harmer
2.135
959311AF2-222 GEN
Solar/Wind Harmer
20.417
970257AG2-171 GEN
Solar/Wind Harmer
7.122
315785AD2-033 C
Solar/Wind Harmer
4.129
964241AG1-285 GEN
Solar/Wind Harmer
12.645
316131AB2-060 GEN
Solar/Wind Harmer
1.61
970221AG2-151 GEN
Solar/Wind Harmer
7.28
3147043LAWRENC
Solar/Wind Harmer
-0.004
316313AB2-026
Solar/Wind Harmer
0.187
316258AE1-075 C
Solar/Wind Harmer
0.168
316405AF2-144 C
Solar/Wind Harmer
0.177
3143336POWHATN
Solar/Wind Harmer
0.698
316248AF1-058 C
Solar/Wind Helper
0.505
316283AC2-100 C
Solar/Wind Helper
1.462
3147312GRETNA
Solar/Wind Helper
0.023
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.769
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.415
VTFLTFEXP_VFT->PJM
CMTX
1.784
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.284
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.201
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.675
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.798
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
2.312

Details for 6EDMONSON-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6SEDGE HILL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.05 %
Rating:997.0 MVA
Rating Type:C
MVA to Mitigate:1017.41
MW Contribution:7.28
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
13.001
3144293JTRSVLE
50/50
0.685
3151601KERR 3
50/50
0.362
3151581KERR 1
50/50
0.129
3151931BEARGRDN S1
50/50
1.421
3151911BEARGRDN G1
50/50
1.101
315687AD1-152 GEN
Solar/Wind Harmer
9.69
957481AF2-042 GEN
Solar/Wind Harmer
201.613
315693AD1-088 GEN
Solar/Wind Harmer
29.329
962491AG1-098 GEN
Solar/Wind Harmer
38.693
3146926FARMVIL
Solar/Wind Harmer
-0.019
316322AB2-045
Solar/Wind Harmer
0.788
3146776BUCKING
Solar/Wind Harmer
-0.009
963171AG1-166 GEN
Solar/Wind Harmer
2.847
971563AH1-280 GEN
Solar/Wind Harmer
2.847
3151541CLOVER2
50/50
12.939
3151611KERR 4
50/50
0.362
3151621KERR 5
50/50
0.362
3151631KERR 6
50/50
0.362
3151641KERR 7
50/50
0.362
972205AH1-687 GEN
50/50
5.369
971967AH1-528 GEN
Solar/Wind Harmer
119.102
970285AG2-188 GEN
Solar/Wind Harmer
22.288
971845AH1-439 GEN
Solar/Wind Harmer
12.819
315657AE1-056 GEN
Solar/Wind Harmer
9.023
946301AF1-294 GEN
Solar/Wind Harmer
5.836
961791AG1-021 GEN
Solar/Wind Harmer
2.847
970683AG2-441 GEN
Solar/Wind Harmer
16.366
970681AG2-440 GEN
Solar/Wind Harmer
13.093
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.708
316239AB2-077_GEN
Solar/Wind Harmer
0.415
316238AB2-078_GEN
Solar/Wind Harmer
0.415
970831AG2-522 GEN
Solar/Wind Harmer
6.705
971447AH1-217 GEN
Solar/Wind Harmer
3.932
270494AE1-108_GEN
Solar/Wind Harmer
2.178
3147173SINAI
Solar/Wind Helper
0.376
3147243WELCO
Solar/Wind Helper
0.235
316123AC1-075 GEN
Solar/Wind Helper
1.594
316118AC1-105 GEN
Solar/Wind Helper
0.953
270455AD2-022 GEN
Solar/Wind Helper
0.936
270457AD2-023 GEN
Solar/Wind Helper
0.617
3144293JTRSVLE
50/50
0.685
3144293JTRSVLE
50/50
0.577
970535AG2-341 GEN
50/50
2.737
970099AG2-077 GEN
Solar/Wind Harmer
80.645
970933AG2-581 GEN
Solar/Wind Harmer
59.392
971741AH1-377 GEN
Solar/Wind Harmer
54.323
970301AG2-198 GEN
Solar/Wind Harmer
21.589
3147133PAMPLIN
Solar/Wind Harmer
-0.024
3147133PAMPLIN
Solar/Wind Harmer
-0.019
3146776BUCKING
Solar/Wind Harmer
-0.093
3146776BUCKING
Solar/Wind Harmer
-0.008
958211AF2-115 GEN
Solar/Wind Harmer
3.559
963191AG1-168 GEN
Solar/Wind Harmer
2.135
316034AC1-036 C
Solar/Wind Harmer
0.353
970323AG2-213 GEN
Solar/Wind Harmer
9.495
971775AH1-396 GEN
Solar/Wind Harmer
1.352
939181AE1-148 GEN
Solar/Wind Harmer
10.548
313527AB2-043 GEN
Solar/Wind Harmer
2.378
971489AH1-241 GEN
Solar/Wind Harmer
6.911
315821AE2-092 GEN
Solar/Wind Harmer
1.794
316222AC1-221 GEN
Solar/Wind Helper
1.608
316197AC1-042 GEN
Solar/Wind Helper
0.109
270013AE1-250 PV
Solar/Wind Helper
0.421
3146843MT LREL
Solar/Wind Helper
0.113
3146843MT LREL
Solar/Wind Helper
0.113
970413AG2-270 GEN
50/50
56.734
3144293JTRSVLE
50/50
0.685
3151591KERR 2
50/50
0.362
3151921BEARGRDN G2
50/50
1.101
316478AD1-087 GEN
Solar/Wind Harmer
5.933
316486AD2-202 GEN
Solar/Wind Harmer
1.738
970909AG2-566 GEN
Solar/Wind Harmer
4.099
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.161
3147133PAMPLIN
Solar/Wind Harmer
-0.075
971193AH1-056 GEN
Solar/Wind Harmer
15.038
3146776BUCKING
Solar/Wind Harmer
-0.008
963181AG1-167 GEN
Solar/Wind Harmer
2.135
959311AF2-222 GEN
Solar/Wind Harmer
20.417
970257AG2-171 GEN
Solar/Wind Harmer
7.122
315785AD2-033 C
Solar/Wind Harmer
4.129
964241AG1-285 GEN
Solar/Wind Harmer
12.645
316131AB2-060 GEN
Solar/Wind Harmer
1.61
970221AG2-151 GEN
Solar/Wind Harmer
7.28
3147043LAWRENC
Solar/Wind Harmer
-0.004
316313AB2-026
Solar/Wind Harmer
0.187
316258AE1-075 C
Solar/Wind Harmer
0.168
316405AF2-144 C
Solar/Wind Harmer
0.177
3143336POWHATN
Solar/Wind Harmer
0.698
316248AF1-058 C
Solar/Wind Helper
0.505
316283AC2-100 C
Solar/Wind Helper
1.462
3147312GRETNA
Solar/Wind Helper
0.023
970685AG2-442 GEN
Solar/Wind Harmer
18.33
971065AG2-659 GEN
Solar/Wind Harmer
7.623
972003AH1-546 GEN
Solar/Wind Harmer
7.562
316129AC1-054 GEN
Solar/Wind Harmer
1.259
316237AB2-079_GEN
Solar/Wind Harmer
0.415
971377AH1-170 GEN
Solar/Wind Harmer
1.456
3147623JAMES R
Solar/Wind Harmer
0.18
970937AG2-583 GEN
Solar/Wind Harmer
7.825
316336AC2-165 C
Solar/Wind Harmer
1.396
3147043LAWRENC
Adder
0.584
3143336POWHATN
Solar/Wind Harmer
0.821
316003AC1-222 GEN
Solar/Wind Helper
1.523
3147123OTTER R
Solar/Wind Helper
0.083
3147312GRETNA
Solar/Wind Helper
0.093
3146802CHATHAM
Solar/Wind Helper
0.087
270016AE1-250 BESS
Solar/Wind Helper
0.421
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.769
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.415
VTFLTFEXP_VFT->PJM
CMTX
1.784
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.284
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.201
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.675
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.798
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
2.312

Details for 6ELMONT-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6ELMONT-6HANOVER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.87 %
Rating:1123.3 MVA
Rating Type:B
MVA to Mitigate:1189.21
MW Contribution:3.15
Bus #Bus NameTypeMW Contribution
3143096IRON208
50/50
0.63
3150641CHESTS8
50/50
0.434
3142416OLDCHRC
Solar/Wind Harmer
0.437
3142416OLDCHRC
Solar/Wind Harmer
0.168
3142543TWELFTH
Solar/Wind Harmer
0.014
944631AF1-128 GEN
Adder
64.319
3150851SPRUNCC
Adder
0.622
315671AE2-027_GEN
Solar/Wind Harmer
8.029
970129AG2-093 GEN
Solar/Wind Harmer
3.524
316458AB2-190 GEN2
Solar/Wind Harmer
0.662
3142433PROV 92
Solar/Wind Harmer
0.488
3142433PROV 92
Adder
0.237
3142433PROV 92
Adder
0.237
971069AG2-661 GEN
Solar/Wind Harmer
2.148
3143526WINTERP
Solar/Wind Harmer
0.621
316159AE1-175 C
Solar/Wind Harmer
0.102
971647AH1-324 GEN
Solar/Wind Harmer
4.981
961611AG1-000B GEN
Solar/Wind Harmer
6.001
3151171GRAVELC
Adder
1.187
971317AH1-138 GEN
Solar/Wind Harmer
0.83
3141766HARMONY
Solar/Wind Harmer
0.022
971777AH1-397 GEN
Solar/Wind Harmer
0.293
3141843SHACKLE
Adder
0.567
3138126ROCKLANDING
Solar/Wind Harmer
0.051
970659AG2-427 GEN
Solar/Wind Harmer
5.319
316381AD1-082 GEN
Solar/Wind Harmer
0.114
970661AG2-428 GEN
Solar/Wind Harmer
10.707
3145336SMITFLD
Solar/Wind Harmer
0.43
3143226MDLTHAN
Solar/Wind Harmer
0.103
316072AD1-144
Solar/Wind Harmer
0.037
3138133OCRAN
Solar/Wind Harmer
0.061
316375AC2-012 GEN
Solar/Wind Harmer
0.003
3150981CHESPKA
Adder
1.26
316294AC1-161 GEN
Solar/Wind Harmer
1.73
316093AE2-104_GEN
Solar/Wind Harmer
1.674
944591AF1-124 GEN
Solar/Wind Harmer
22.475
316388AE2-253 GEN
Solar/Wind Harmer
0.31
316246AF1-032 C
Solar/Wind Harmer
0.045
3146456SLIGO L269
Solar/Wind Harmer
0.099
3146516WINFALL
Solar/Wind Harmer
0.312
3146516WINFALL
Solar/Wind Harmer
0.096
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.093
3145663CRESWEL
Solar/Wind Harmer
0.255
971163AH1-040 GEN
Solar/Wind Harmer
7.278
962861AG1-135 GEN
Solar/Wind Harmer
2.836
939411AE1-173 GEN
Solar/Wind Harmer
37.741
3146206CASHIE
Solar/Wind Harmer
0.088
971547AH1-271 GEN
Solar/Wind Harmer
1.872
972277AH1-723 GEN
Adder
52.282
3145893MURPHYS
Solar/Wind Harmer
0.349
3145893MURPHYS
Solar/Wind Harmer
0.388
316023GEN1_S
Solar/Wind Harmer
0.195
3143336POWHATN
Solar/Wind Harmer
1.539
3146173TUNIS
Solar/Wind Harmer
0.086
3145683EARLEYS
Solar/Wind Harmer
0.085
940641AE2-051 GEN
Solar/Wind Harmer
6.781
3146263WOODLND
Solar/Wind Harmer
0.084
3141726DUNNSVL
Solar/Wind Harmer
0.336
3145963POPLR C
Solar/Wind Harmer
0.084
960081AF2-299 GEN
Solar/Wind Harmer
0.803
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145823KELFORD
Solar/Wind Harmer
0.083
316011AB1-132 GEN
Solar/Wind Harmer
1.509
962571AG1-106 GEN
Solar/Wind Harmer
1.181
316336AC2-165 C
Solar/Wind Harmer
0.003
316190AA2-174 GEN
Solar/Wind Harmer
0
3145796HORNRTN
Solar/Wind Harmer
0.269
3145796HORNRTN
Solar/Wind Harmer
0.082
3145783HORNRTN
Solar/Wind Harmer
0.081
971795AH1-408 GEN
Solar/Wind Harmer
5.392
3146293MARTNCO
Solar/Wind Harmer
0.074
3147043LAWRENC
Adder
0.72
316212AC1-099_GEN
Solar/Wind Harmer
0.411
3150351NORNECKC2
Adder
0.791
3145746EVERETS
Solar/Wind Harmer
0.078
3145746EVERETS
Solar/Wind Harmer
0.078
315722AD1-056 GEN
Solar/Wind Harmer
0.488
316494AC1-189 GEN
Solar/Wind Harmer
0.258
970919AG2-571 GEN
Solar/Wind Harmer
2.678
970087AG2-069 GEN
Solar/Wind Harmer
6.009
961671AG1-007 GEN
Solar/Wind Harmer
0.011
3146083TARBORO
Solar/Wind Harmer
0.075
3145493TOT1
Solar/Wind Harmer
0.333
316129AC1-054 GEN
Solar/Wind Harmer
0.282
3146233WITAKRS
Solar/Wind Harmer
0.297
971065AG2-659 GEN
Solar/Wind Harmer
3.171
316359AB2-059 GEN
Solar/Wind Harmer
0.263
316049AB1-081 GEN
Solar/Wind Harmer
0.419
3145543BTLEBRO
Solar/Wind Harmer
0.073
3145543BTLEBRO
Solar/Wind Harmer
0.059
3142053HEARTS
Solar/Wind Harmer
0.129
957481AF2-042 GEN
Solar/Wind Harmer
19.524
315693AD1-088 GEN
Solar/Wind Harmer
3.47
962491AG1-098 GEN
Solar/Wind Harmer
4.117
970937AG2-583 GEN
Solar/Wind Harmer
4.364
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970685AG2-442 GEN
Solar/Wind Harmer
5.162
963171AG1-166 GEN
Solar/Wind Harmer
0.367
971563AH1-280 GEN
Solar/Wind Harmer
0.733
3144293JTRSVLE
Adder
0.219
315687AD1-152 GEN
Solar/Wind Harmer
0.002
3146926FARMVIL
Solar/Wind Harmer
0.04
970401AG2-262 GEN
Solar/Wind Harmer
0.392
316337AD2-073 GEN
Solar/Wind Harmer
0.057
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.026
3150611CHESTG7
50/50
0.857
3150631CHESTG8
50/50
0.843
316312AB1-027
Solar/Wind Harmer
0.301
971285AH1-108 GEN
Adder
1.017
315976AC1-164 GENA
Solar/Wind Harmer
13.778
316169AC1-164_GENC
Solar/Wind Harmer
11.903
315975AC1-164 GENB
Solar/Wind Harmer
0.408
971167AH1-042 GEN
Solar/Wind Harmer
10.969
316132AB2-190 GEN1
Solar/Wind Harmer
0.662
3142433PROV 92
Adder
0.237
3142433PROV 92
Adder
0.237
316233AE1-074 FULL
Solar/Wind Harmer
0.096
971281AH1-106 GEN
Solar/Wind Harmer
1.657
971283AH1-107 GEN
Solar/Wind Harmer
1.657
316369SG1_INVT
Solar/Wind Harmer
0.004
3143873LANEXA
Solar/Wind Harmer
0.07
316314AB2-024 C
Solar/Wind Harmer
0
3143316POE
Solar/Wind Harmer
0.442
972265AH1-717 GEN
Adder
8.661
3151201GRAVEL4
Adder
8.12
3151191GRAVEL3
Adder
8.017
3151211GRAVEL5
Adder
8.017
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
3.288
315662AE1-191 GEN
Solar/Wind Harmer
0.004
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971445AH1-216 GEN
Solar/Wind Harmer
7.593
3141873WAN 176
Solar/Wind Harmer
0.021
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.071
316311AC2-079 GEN
Solar/Wind Harmer
2.965
3141913WHIT STONE
Solar/Wind Harmer
0.103
3138133OCRAN
Solar/Wind Harmer
0.031
3152611GOSPORTB
Adder
1.285
3152621GOSPORTC
Adder
1.09
3152601GOSPORTA
Adder
1.006
3151081ELIZAR1
Adder
9.234
3151091ELIZAR2
Adder
9.074
3141783LANCAST
Solar/Wind Harmer
0.06
3141783LANCAST
Solar/Wind Harmer
0.04
315835AF2-110_GEN
Solar/Wind Harmer
0.683
316305AF2-043 C
Solar/Wind Harmer
0.001
957871AF2-081 GEN
Solar/Wind Harmer
4.929
319010AE1-072 C
Solar/Wind Harmer
0.497
3146406KITTY HAWK
Solar/Wind Harmer
0.012
313526AB2-022
Solar/Wind Harmer
0.053
3146486SUNBURY
Solar/Wind Harmer
0.098
3146486SUNBURY
Solar/Wind Harmer
0.098
316321Z2-027
Solar/Wind Harmer
0.018
3146396TANGLEW
Solar/Wind Harmer
0.268
3145176PASQUOTANK
Solar/Wind Harmer
0.06
962981AG1-147 GEN
Solar/Wind Harmer
3.537
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
316315AB2-025 C
Solar/Wind Harmer
0.076
315814AE2-033 C
Solar/Wind Harmer
7.456
3130156CHOWAN
Solar/Wind Harmer
0.093
3130156CHOWAN
Solar/Wind Harmer
0.093
970327AG2-215 GEN
Solar/Wind Harmer
3.018
315816AE2-034 GEN
Solar/Wind Harmer
0.39
3130546PLYMOUTH
Solar/Wind Harmer
0.089
315732AD1-074 GEN1
Solar/Wind Harmer
0.51
315733AD1-074 GEN2
Solar/Wind Harmer
0.51
315735AD1-075 GEN1
Solar/Wind Harmer
0.255
965291AG1-394 GEN
Solar/Wind Harmer
0.392
3146206CASHIE
Solar/Wind Harmer
0.088
970601AG2-382 GEN
Solar/Wind Harmer
3.275
972193AH1-681 GEN
Adder
2.005
3145893MURPHYS
Solar/Wind Harmer
0.235
3145893MURPHYS
Solar/Wind Harmer
0.087
3145513AHOSKIE
Solar/Wind Harmer
0.179
3145513AHOSKIE
Solar/Wind Harmer
0.086
3145683EARLEYS
Solar/Wind Harmer
0.17
3145683EARLEYS
Solar/Wind Harmer
0.085
3145683EARLEYS
Solar/Wind Harmer
0.085
3146043SEABORD
Solar/Wind Harmer
0.084
315607AA1-063A GEN
Solar/Wind Harmer
0.172
315652AC1-086 GEN
Solar/Wind Harmer
9.127
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.328
3145796HORNRTN
Solar/Wind Harmer
0.261
3145796HORNRTN
Solar/Wind Harmer
0.033
3146033SCOT NK
Solar/Wind Harmer
0.324
941031AE2-094 GEN
Solar/Wind Harmer
14.626
944011AF1-069 GEN
Solar/Wind Harmer
4.779
3141813NORNECK
Solar/Wind Harmer
0.079
970673AG2-436 GEN
Solar/Wind Harmer
16.734
970673AG2-436 GEN
Solar/Wind Harmer
11.156
316005AA1-067
Solar/Wind Harmer
0.084
3145746EVERETS
Solar/Wind Harmer
0.31
3145746EVERETS
Solar/Wind Harmer
0.078
3145746EVERETS
Solar/Wind Harmer
0.078
3145746EVERETS
Solar/Wind Harmer
0.078
970181AG2-120 GEN
Solar/Wind Harmer
0.97
971967AH1-528 GEN
Solar/Wind Harmer
12.447
957861AF2-080 GEN
Solar/Wind Harmer
3.293
316420AA1-050 GEN
Solar/Wind Harmer
0.002
970831AG2-522 GEN
Solar/Wind Harmer
3.224
970085AG2-068 GEN
Solar/Wind Harmer
4.006
970581AG2-369 GEN
Solar/Wind Harmer
3.445
3145573BETHELC
Solar/Wind Harmer
0.075
3145573BETHELC
Solar/Wind Harmer
0.075
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
1.169
3144303KENBRDG
Solar/Wind Harmer
0.056
970683AG2-441 GEN
Solar/Wind Harmer
4.609
970681AG2-440 GEN
Solar/Wind Harmer
3.687
946301AF1-294 GEN
Solar/Wind Harmer
1.357
961791AG1-021 GEN
Solar/Wind Harmer
0.66
315657AE1-056 GEN
Solar/Wind Harmer
2.362
316118AC1-105 GEN
Solar/Wind Harmer
0.169
970285AG2-188 GEN
Solar/Wind Harmer
5.153
971845AH1-439 GEN
Solar/Wind Harmer
2.936
3147173SINAI
Solar/Wind Harmer
0.064
3147243WELCO
Solar/Wind Harmer
0.04
972205AH1-687 GEN
Adder
2.638
970865AG2-541 GEN
Solar/Wind Harmer
2.043
971447AH1-217 GEN
Solar/Wind Harmer
1.766
3141426STAFORD
Solar/Wind Helper
0.033
316003AC1-222 GEN
Solar/Wind Harmer
0.002
972003AH1-546 GEN
Solar/Wind Harmer
2.646
971377AH1-170 GEN
Solar/Wind Harmer
0.63
3147623JAMES R
Solar/Wind Harmer
0.137
971645AH1-323 GEN
50/50
17.435
3143096IRON208
50/50
0.63
3143096IRON208
50/50
0.617
316473AC1-191 GEN
Solar/Wind Harmer
0.571
3142416OLDCHRC
Solar/Wind Harmer
1.631
970293AG2-193 GEN
Solar/Wind Harmer
1.601
3150861SPRUNCD
Adder
0.622
3142946ENON
Solar/Wind Harmer
0.045
970133AG2-095 GEN
Solar/Wind Harmer
1.231
970129AG2-093 GEN
Solar/Wind Harmer
7.489
965281AG1-393 GEN
Solar/Wind Harmer
1.32
315839AE2-212 C
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.237
3142433PROV 92
Adder
0.237
315778AD1-151 GEN
Solar/Wind Harmer
9.667
316382AG1-145 C
Solar/Wind Harmer
0.001
961611AG1-000B GEN
Solar/Wind Harmer
3.052
315813AE1-149 C
Solar/Wind Harmer
6.039
3151221GRAVEL6
Adder
8.11
3151171GRAVELC
Adder
1.56
3141766HARMONY
Solar/Wind Harmer
1.48
3141843SHACKLE
Adder
0.567
316203AE2-005 GEN
Solar/Wind Harmer
0
3144216WINCHST
Adder
0.416
3150921YORKTN3
Adder
2.767
970659AG2-427 GEN
Solar/Wind Harmer
1.163
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.002
971781AH1-399 GEN
Solar/Wind Harmer
0.143
970661AG2-428 GEN
Solar/Wind Harmer
2.277
3145336SMITFLD
Solar/Wind Harmer
0.043
316156AD2-030 GEN
Solar/Wind Harmer
0.079
3141873WAN 176
Solar/Wind Harmer
1.904
3144536CHRHLND
Solar/Wind Harmer
0.015
3144873MCLAUGH
Solar/Wind Harmer
0.003
3151101ELIZAR3
Adder
9.352
315773AC2-141 GEN
Solar/Wind Harmer
3.646
944581AF1-123 GEN
Solar/Wind Harmer
22.395
944601AF1-125 GEN
Solar/Wind Harmer
22.05
3146456SLIGO L269
Solar/Wind Harmer
0.099
971153AH1-033 GEN
Solar/Wind Harmer
1.142
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.096
3145273HOLLAND
Solar/Wind Harmer
0.072
3146626S HERTFORD
Solar/Wind Harmer
0.096
962971AG1-146 GEN
Solar/Wind Harmer
1.516
3146376EDENTON
Solar/Wind Harmer
0.093
970009AG2-005 GEN
Solar/Wind Harmer
0.687
315614AA2-178 GEN
Solar/Wind Harmer
0.521
971157AH1-035 GEN
Solar/Wind Harmer
1.07
315737AD1-076 GEN
Solar/Wind Harmer
1.143
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146206CASHIE
Solar/Wind Harmer
0.088
972255AH1-712 GEN
Adder
44.866
316404AE1-155 C
Solar/Wind Harmer
0.02
3145893MURPHYS
Solar/Wind Harmer
0.146
3145893MURPHYS
Solar/Wind Harmer
0.087
957521AF2-046 GEN
Solar/Wind Harmer
6.466
961681AG1-008 GEN
Solar/Wind Harmer
6.466
316365GEN2_N
Solar/Wind Harmer
0.195
316313AB2-026
Solar/Wind Harmer
0.055
316258AE1-075 C
Solar/Wind Harmer
0.065
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
1.308
3146173TUNIS
Solar/Wind Harmer
0.086
3156021HOLLOMANSOL
Solar/Wind Harmer
0.391
316463AE2-346 GEN
Solar/Wind Harmer
0.074
316140AB2-099
Solar/Wind Harmer
0.031
962331AG1-082 GEN
Solar/Wind Harmer
0.914
3146263WOODLND
Solar/Wind Harmer
0.084
3145963POPLR C
Solar/Wind Harmer
0.084
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
316317KELFORD C
Solar/Wind Harmer
0.008
3145823KELFORD
Solar/Wind Harmer
0.083
313506AB2-031 GEN
Solar/Wind Harmer
0.255
3145796HORNRTN
Solar/Wind Harmer
0.326
3145796HORNRTN
Solar/Wind Harmer
0.082
3145933PARMELE
Solar/Wind Harmer
0.08
966801AG1-551 GEN
Solar/Wind Harmer
0.93
3147043LAWRENC
Solar/Wind Harmer
0.048
316210AC1-098 GEN
Solar/Wind Harmer
0.737
3150351NORNECKC2
Adder
0.804
3145746EVERETS
Solar/Wind Harmer
0.078
3145746EVERETS
Solar/Wind Harmer
0.078
315724AD1-057 GEN
Solar/Wind Harmer
0.289
316327AA2-057 GEN
Solar/Wind Harmer
0.115
970917AG2-570 GEN
Solar/Wind Harmer
6.696
3146073TAR RVR
Solar/Wind Harmer
0.075
3146083TARBORO
Solar/Wind Harmer
0.075
3146233WITAKRS
Solar/Wind Harmer
0.375
3146233WITAKRS
Solar/Wind Harmer
0.051
3138543CONSLDL
Solar/Wind Harmer
0.049
961601AG1-000A GEN
Solar/Wind Harmer
5.215
3145543BTLEBRO
Solar/Wind Harmer
0.073
3145543BTLEBRO
Solar/Wind Harmer
0.073
971623AH1-311 GEN
Solar/Wind Harmer
0.147
316478AD1-087 GEN
Solar/Wind Harmer
0.249
316486AD2-202 GEN
Solar/Wind Harmer
0.073
316131AB2-060 GEN
Solar/Wind Harmer
0.221
964241AG1-285 GEN
Solar/Wind Harmer
4.675
315785AD2-033 C
Solar/Wind Harmer
0.567
970257AG2-171 GEN
Solar/Wind Harmer
2.225
959311AF2-222 GEN
Solar/Wind Harmer
6.171
970909AG2-566 GEN
Solar/Wind Harmer
0.738
963181AG1-167 GEN
Solar/Wind Harmer
0.275
3144293JTRSVLE
Adder
0.219
3147133PAMPLIN
Solar/Wind Harmer
0.215
971193AH1-056 GEN
Solar/Wind Harmer
4.17
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.04
3146776BUCKING
Solar/Wind Harmer
0.023
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.742
971683AH1-343 GEN
Solar/Wind Harmer
2.232
316283AC2-100 C
Solar/Wind Harmer
0.116
970221AG2-151 GEN
Solar/Wind Harmer
3.149
966881AG1-559 GEN
Solar/Wind Helper
1.213
3142296MT RD221
50/50
0.632
3142366NRTHEST
50/50
0.551
3150691DARBY 3
50/50
11.896
3150701DARBY 4
50/50
11.869
3150681DARBY 2
50/50
11.855
3150671DARBY 1
50/50
11.841
3150621CHESTS7
50/50
0.394
966871AG1-558 GEN
Solar/Wind Harmer
0.195
316075AC2-137 C
Solar/Wind Harmer
0.04
3142946ENON
Solar/Wind Harmer
0.013
944641AF1-129 GEN
Adder
63.125
316240AF1-291 C
Solar/Wind Harmer
0.001
3143526WINTERP
Solar/Wind Harmer
0.621
316033AB2-134 GEN
Solar/Wind Harmer
0.007
315697AD1-025 GEN
Solar/Wind Harmer
0.134
316468AD1-105 GEN
Solar/Wind Harmer
-0.035
970657AG2-426 GEN
Solar/Wind Harmer
3.808
970657AG2-426 GEN
Solar/Wind Harmer
0.798
316236AE1-162_GEN
Solar/Wind Harmer
0.001
971223AH1-071 GEN
Solar/Wind Harmer
1.1
316036AC1-147 C
Solar/Wind Harmer
0.019
3150991CHESPKB
Adder
1.057
3150991CHESPKB
Adder
1.031
316316AC1-027 C
Solar/Wind Harmer
0.096
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.003
3145506HICKORY
Solar/Wind Harmer
0.398
3145506HICKORY
Solar/Wind Harmer
0.239
3145506HICKORY
Solar/Wind Harmer
0.06
316339AD2-160 GEN
Solar/Wind Harmer
0.161
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.055
3137176SLIGO L2192
Solar/Wind Harmer
0.393
3146456SLIGO L269
Solar/Wind Harmer
1.748
3130086AYDLETT
Solar/Wind Harmer
0.394
3146386ELIZ CT
Solar/Wind Harmer
0.098
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.096
3146516WINFALL
Solar/Wind Harmer
0.096
3146516WINFALL
Solar/Wind Harmer
0.096
3146626S HERTFORD
Solar/Wind Harmer
0.096
3146626S HERTFORD
Solar/Wind Harmer
0.096
3144356SAPONY
Solar/Wind Harmer
0.792
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.415
3146376EDENTON
Solar/Wind Harmer
0.415
316065AD1-022 GEN
Solar/Wind Harmer
4.058
958261AF2-120 GEN
Solar/Wind Harmer
2.891
3145893MURPHYS
Solar/Wind Harmer
0.583
3145893MURPHYS
Solar/Wind Harmer
0.157
3146173TUNIS
Solar/Wind Harmer
0.086
3146173TUNIS
Solar/Wind Harmer
0.086
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.05
316181AB2-040 GEN
Solar/Wind Harmer
0.12
316426AA2-053 GEN
Solar/Wind Harmer
0.278
3145796HORNRTN
Solar/Wind Harmer
0.245
3145593CAROLNA
Solar/Wind Harmer
0.082
3145593CAROLNA
Solar/Wind Harmer
0.082
966811AG1-552 GEN
Solar/Wind Harmer
0.885
3145593CAROLNA
Solar/Wind Harmer
0.102
3145783HORNRTN
Solar/Wind Harmer
1.442
3145783HORNRTN
Solar/Wind Harmer
1.154
3145783HORNRTN
Solar/Wind Harmer
0.361
3145783HORNRTN
Solar/Wind Harmer
0.144
3145933PARMELE
Solar/Wind Harmer
0.16
3145933PARMELE
Solar/Wind Harmer
0.08
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.831
3150341NORNECKC1
Adder
0.824
316274AC1-208 GEN
Solar/Wind Harmer
0.408
972185AH1-677 GEN
Adder
4.375
972187AH1-678 GEN
Adder
2.202
970933AG2-581 GEN
Solar/Wind Harmer
6.122
3145493TOT1
Solar/Wind Harmer
0.174
3145453TOT5
Solar/Wind Harmer
0.104
3145603CNETO
Solar/Wind Harmer
0.07
961601AG1-000A GEN
Solar/Wind Harmer
1.304
316263AC1-034 GEN
Solar/Wind Harmer
2.784
970099AG2-077 GEN
Solar/Wind Harmer
7.81
939181AE1-148 GEN
Solar/Wind Harmer
3.417
313527AB2-043 GEN
Solar/Wind Harmer
0.001
971741AH1-377 GEN
Solar/Wind Harmer
6.934
316034AC1-036 C
Solar/Wind Harmer
0.005
970323AG2-213 GEN
Solar/Wind Harmer
2.967
971775AH1-396 GEN
Solar/Wind Harmer
0.111
970301AG2-198 GEN
Solar/Wind Harmer
2.952
958211AF2-115 GEN
Solar/Wind Harmer
0.825
963191AG1-168 GEN
Solar/Wind Harmer
0.275
3144293JTRSVLE
Adder
0.219
3144293JTRSVLE
Adder
0.184
3147133PAMPLIN
Solar/Wind Harmer
0.068
3147133PAMPLIN
Solar/Wind Harmer
0.055
962561AG1-105 GEN
Solar/Wind Harmer
3.235
964791AG1-342 GEN
Solar/Wind Harmer
1.284
3146843MT LREL
Solar/Wind Harmer
0.067
3146843MT LREL
Solar/Wind Harmer
0.067
3146776BUCKING
Solar/Wind Harmer
0.258
3146776BUCKING
Solar/Wind Harmer
0.021
316222AC1-221 GEN
Solar/Wind Harmer
0.248
971489AH1-241 GEN
Solar/Wind Harmer
3.149
LAGNLTFEXP_LAGN->PJM
CLTF
4.321
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.477
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.705
MECLTFEXP_MEC->PJM
CLTF
2.537
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.837
TVALTFEXP_TVA->PJM
CLTF
2.185
SIGELTFEXP_SIGE->PJM
CLTF
0.079
NYPJM->LTFIMP_NY
CLTF
0.971
LGEELTFEXP_LGEE->PJM
CLTF
0.994
WECLTFEXP_WEC->PJM
CLTF
0.514
CPLELTFEXP_CPLE->PJM
CLTF
4.707
CBM West 2LTFEXP_CBM-W2->PJM
CBM
24.626

Details for 6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-5: 556X2_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-5: 556X2_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.23 %
Rating:1050.6 MVA
Rating Type:C
MVA to Mitigate:1462.74
MW Contribution:7.26
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
8.294
3151611KERR 4
50/50
0.512
3151621KERR 5
50/50
0.512
3151631KERR 6
50/50
0.512
3151641KERR 7
50/50
0.512
972205AH1-687 GEN
50/50
5.225
315657AE1-056 GEN
Solar/Wind Harmer
12.067
946301AF1-294 GEN
Solar/Wind Harmer
8.13
961791AG1-021 GEN
Solar/Wind Harmer
3.966
970683AG2-441 GEN
Solar/Wind Harmer
24.284
970681AG2-440 GEN
Solar/Wind Harmer
19.428
3144303KENBRDG
Solar/Wind Harmer
-0.024
971443AH1-215 GEN
Solar/Wind Harmer
5.973
316239AB2-077_GEN
Solar/Wind Harmer
0.866
316238AB2-078_GEN
Solar/Wind Harmer
0.866
970285AG2-188 GEN
Solar/Wind Harmer
23.989
316118AC1-105 GEN
Solar/Wind Harmer
1.858
3147173SINAI
Solar/Wind Harmer
-0.026
3147243WELCO
Solar/Wind Harmer
-0.016
971845AH1-439 GEN
Solar/Wind Harmer
13.717
970865AG2-541 GEN
Solar/Wind Harmer
8.867
970831AG2-522 GEN
Solar/Wind Harmer
9.395
316123AC1-075 GEN
Solar/Wind Harmer
2.019
970165AG2-112 GEN
Solar/Wind Harmer
1.778
970163AG2-111 GEN
Solar/Wind Harmer
1.696
971447AH1-217 GEN
Solar/Wind Harmer
3.892
270494AE1-108_GEN
Solar/Wind Harmer
2.597
270455AD2-022 GEN
Solar/Wind Harmer
1.324
270457AD2-023 GEN
Solar/Wind Harmer
0.671
3143316POE
Solar/Wind Helper
0.479
319010AE1-072 C
Solar/Wind Helper
1.317
316305AF2-043 C
Solar/Wind Helper
0.151
3151531CLOVER1
50/50
8.333
3144293JTRSVLE
50/50
0.954
3151601KERR 3
50/50
0.512
3151581KERR 1
50/50
0.183
3151931BEARGRDN S1
50/50
1.383
3151911BEARGRDN G1
50/50
1.071
315693AD1-088 GEN
Solar/Wind Harmer
31.661
962491AG1-098 GEN
Solar/Wind Harmer
41.781
957481AF2-042 GEN
Solar/Wind Harmer
136.799
315687AD1-152 GEN
Solar/Wind Harmer
4.384
3146926FARMVIL
Solar/Wind Harmer
-0.021
963171AG1-166 GEN
Solar/Wind Harmer
3.966
971563AH1-280 GEN
Solar/Wind Harmer
3.966
970685AG2-442 GEN
Solar/Wind Harmer
27.199
316237AB2-079_GEN
Solar/Wind Harmer
0.866
970401AG2-262 GEN
Solar/Wind Harmer
1.795
316322AB2-045
Solar/Wind Harmer
0.84
3146776BUCKING
Solar/Wind Harmer
-0.01
316003AC1-222 GEN
Solar/Wind Harmer
2.424
971065AG2-659 GEN
Solar/Wind Harmer
10.717
316129AC1-054 GEN
Solar/Wind Harmer
1.767
972003AH1-546 GEN
Solar/Wind Harmer
7.559
3147043LAWRENC
Adder
0.99
971377AH1-170 GEN
Solar/Wind Harmer
1.453
3147623JAMES R
Solar/Wind Harmer
0.18
3147123OTTER R
Solar/Wind Harmer
-0.006
971795AH1-408 GEN
Solar/Wind Harmer
7.507
970937AG2-583 GEN
Solar/Wind Harmer
6.673
3147312GRETNA
Solar/Wind Harmer
-0.007
3146802CHATHAM
Solar/Wind Harmer
-0.007
941801AE2-185 GEN
Solar/Wind Harmer
3.291
316294AC1-161 GEN
Solar/Wind Helper
2.492
316375AC2-012 GEN
Solar/Wind Helper
0.324
316388AE2-253 GEN
Solar/Wind Helper
0.45
3145336SMITFLD
Solar/Wind Helper
0.467
3146456SLIGO L269
Solar/Wind Helper
0.116
316246AF1-032 C
Solar/Wind Helper
0.129
316072AD1-144
Solar/Wind Helper
0.129
970413AG2-270 GEN
50/50
36.366
3144293JTRSVLE
50/50
0.954
3151591KERR 2
50/50
0.512
3151921BEARGRDN G2
50/50
1.071
970909AG2-566 GEN
Solar/Wind Harmer
4.458
316478AD1-087 GEN
Solar/Wind Harmer
3.778
316486AD2-202 GEN
Solar/Wind Harmer
1.106
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
5.027
3147133PAMPLIN
Solar/Wind Harmer
-0.101
971193AH1-056 GEN
Solar/Wind Harmer
20.111
963181AG1-167 GEN
Solar/Wind Harmer
2.974
959311AF2-222 GEN
Solar/Wind Harmer
31.935
970257AG2-171 GEN
Solar/Wind Harmer
11.4
315785AD2-033 C
Solar/Wind Harmer
6.828
964241AG1-285 GEN
Solar/Wind Harmer
22.977
316131AB2-060 GEN
Solar/Wind Harmer
3.126
316248AF1-058 C
Solar/Wind Harmer
0.799
960061AF2-297 GEN
Solar/Wind Harmer
13.263
3146776BUCKING
Solar/Wind Harmer
-0.009
971683AH1-343 GEN
Solar/Wind Harmer
10.071
316283AC2-100 C
Solar/Wind Harmer
1.212
3147043LAWRENC
Solar/Wind Harmer
-0.007
970221AG2-151 GEN
Solar/Wind Harmer
7.265
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
3.291
958131AF2-107 GEN
Solar/Wind Harmer
2.165
315773AC2-141 GEN
Solar/Wind Helper
2.933
3144873MCLAUGH
Solar/Wind Helper
0.003
3144536CHRHLND
Solar/Wind Helper
0.018
3145336SMITFLD
Solar/Wind Helper
0.047
3146456SLIGO L269
Solar/Wind Helper
0.116
3144293JTRSVLE
50/50
0.954
3144293JTRSVLE
50/50
0.803
970535AG2-341 GEN
50/50
4.477
3152661PLYWOOD A
50/50
0.537
971741AH1-377 GEN
Solar/Wind Harmer
58.955
970301AG2-198 GEN
Solar/Wind Harmer
23.48
970099AG2-077 GEN
Solar/Wind Harmer
54.72
3147133PAMPLIN
Solar/Wind Harmer
-0.032
3147133PAMPLIN
Solar/Wind Harmer
-0.026
958211AF2-115 GEN
Solar/Wind Harmer
4.957
963191AG1-168 GEN
Solar/Wind Harmer
2.974
316034AC1-036 C
Solar/Wind Harmer
0.564
970323AG2-213 GEN
Solar/Wind Harmer
15.2
971775AH1-396 GEN
Solar/Wind Harmer
2.165
313527AB2-043 GEN
Solar/Wind Harmer
4.69
939181AE1-148 GEN
Solar/Wind Harmer
15.738
962561AG1-105 GEN
Solar/Wind Harmer
15.589
964791AG1-342 GEN
Solar/Wind Harmer
5.876
3146843MT LREL
Solar/Wind Harmer
-0.027
3146843MT LREL
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.099
3146776BUCKING
Solar/Wind Harmer
-0.008
942751AE2-291 GEN
Solar/Wind Harmer
10.674
316222AC1-221 GEN
Solar/Wind Harmer
1.342
971489AH1-241 GEN
Solar/Wind Harmer
6.897
316217AC1-145 GEN
Solar/Wind Harmer
1.425
316197AC1-042 GEN
Solar/Wind Harmer
1.08
942671AE2-283 GEN
Solar/Wind Harmer
2.907
315821AE2-092 GEN
Solar/Wind Harmer
1.728
316036AC1-147 C
Solar/Wind Helper
0.189
3142956BIRDNECK
Solar/Wind Helper
0.083
316316AC1-027 C
Solar/Wind Helper
0.194
316185AD1-033 GEN
Solar/Wind Helper
0.577
3145506HICKORY
Solar/Wind Helper
0.484
3145506HICKORY
Solar/Wind Helper
0.291
3145506HICKORY
Solar/Wind Helper
0.073
316339AD2-160 GEN
Solar/Wind Helper
0.45
316018AA1-139 ULT2
Solar/Wind Helper
0.505
316017AA1-139 ULT1
Solar/Wind Helper
0.536
316236AE1-162_GEN
Solar/Wind Helper
0.157
3137176SLIGO L2192
Solar/Wind Helper
0.462
3130086AYDLETT
Solar/Wind Helper
0.459
LAGNLTFEXP_LAGN->PJM
CLTF
2.391
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.001
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.345
MECLTFEXP_MEC->PJM
CLTF
1.48
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.949
TVALTFEXP_TVA->PJM
CLTF
1.221
SIGELTFEXP_SIGE->PJM
CLTF
0.047
NYPJM->LTFIMP_NY
CLTF
0.45
LGEELTFEXP_LGEE->PJM
CLTF
0.594
WECLTFEXP_WEC->PJM
CLTF
0.305
CPLELTFEXP_CPLE->PJM
CLTF
2.622
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.961

Details for 6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: 556X1_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-5: 556X1_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.76 %
Rating:1053.0 MVA
Rating Type:C
MVA to Mitigate:1461.12
MW Contribution:7.26
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
8.284
3151611KERR 4
50/50
0.511
3151621KERR 5
50/50
0.511
3151631KERR 6
50/50
0.511
3151641KERR 7
50/50
0.511
972205AH1-687 GEN
50/50
5.219
315657AE1-056 GEN
Solar/Wind Harmer
12.053
946301AF1-294 GEN
Solar/Wind Harmer
8.121
961791AG1-021 GEN
Solar/Wind Harmer
3.962
970683AG2-441 GEN
Solar/Wind Harmer
24.258
970681AG2-440 GEN
Solar/Wind Harmer
19.406
3144303KENBRDG
Solar/Wind Harmer
-0.024
971443AH1-215 GEN
Solar/Wind Harmer
5.967
316239AB2-077_GEN
Solar/Wind Harmer
0.865
3151531CLOVER1
50/50
8.324
3144293JTRSVLE
50/50
0.953
3151601KERR 3
50/50
0.511
3151581KERR 1
50/50
0.182
3151931BEARGRDN S1
50/50
1.381
3151911BEARGRDN G1
50/50
1.07
315693AD1-088 GEN
Solar/Wind Harmer
31.626
962491AG1-098 GEN
Solar/Wind Harmer
41.735
957481AF2-042 GEN
Solar/Wind Harmer
136.647
315687AD1-152 GEN
Solar/Wind Harmer
4.379
3146926FARMVIL
Solar/Wind Harmer
-0.021
963171AG1-166 GEN
Solar/Wind Harmer
3.962
971563AH1-280 GEN
Solar/Wind Harmer
3.962
970685AG2-442 GEN
Solar/Wind Harmer
27.168
316237AB2-079_GEN
Solar/Wind Harmer
0.865
970401AG2-262 GEN
Solar/Wind Harmer
1.793
316322AB2-045
Solar/Wind Harmer
0.839
3146776BUCKING
Solar/Wind Harmer
-0.01
316003AC1-222 GEN
Solar/Wind Harmer
2.421
971065AG2-659 GEN
Solar/Wind Harmer
10.705
316129AC1-054 GEN
Solar/Wind Harmer
1.765
972003AH1-546 GEN
Solar/Wind Harmer
7.55
3147043LAWRENC
Adder
0.989
971377AH1-170 GEN
Solar/Wind Harmer
1.451
3147623JAMES R
Solar/Wind Harmer
0.18
3147123OTTER R
Solar/Wind Harmer
-0.006
971795AH1-408 GEN
Solar/Wind Harmer
7.499
970937AG2-583 GEN
Solar/Wind Harmer
6.666
3147312GRETNA
Solar/Wind Harmer
-0.007
3146802CHATHAM
Solar/Wind Harmer
-0.007
941801AE2-185 GEN
Solar/Wind Harmer
3.288
316294AC1-161 GEN
Solar/Wind Helper
2.489
316375AC2-012 GEN
Solar/Wind Helper
0.324
316388AE2-253 GEN
Solar/Wind Helper
0.45
3145336SMITFLD
Solar/Wind Helper
0.467
3146456SLIGO L269
Solar/Wind Helper
0.116
316246AF1-032 C
Solar/Wind Helper
0.128
316072AD1-144
Solar/Wind Helper
0.128
970413AG2-270 GEN
50/50
36.326
3144293JTRSVLE
50/50
0.953
3151591KERR 2
50/50
0.511
3151921BEARGRDN G2
50/50
1.07
970909AG2-566 GEN
Solar/Wind Harmer
4.453
316478AD1-087 GEN
Solar/Wind Harmer
3.774
316486AD2-202 GEN
Solar/Wind Harmer
1.105
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
5.021
3147133PAMPLIN
Solar/Wind Harmer
-0.1
971193AH1-056 GEN
Solar/Wind Harmer
20.089
963181AG1-167 GEN
Solar/Wind Harmer
2.971
959311AF2-222 GEN
Solar/Wind Harmer
31.9
970257AG2-171 GEN
Solar/Wind Harmer
11.387
315785AD2-033 C
Solar/Wind Harmer
6.821
964241AG1-285 GEN
Solar/Wind Harmer
22.951
316131AB2-060 GEN
Solar/Wind Harmer
3.123
316248AF1-058 C
Solar/Wind Harmer
0.798
960061AF2-297 GEN
Solar/Wind Harmer
13.248
3146776BUCKING
Solar/Wind Harmer
-0.009
971683AH1-343 GEN
Solar/Wind Harmer
10.06
316283AC2-100 C
Solar/Wind Harmer
1.21
3147043LAWRENC
Solar/Wind Harmer
-0.007
970221AG2-151 GEN
Solar/Wind Harmer
7.257
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
3.288
958131AF2-107 GEN
Solar/Wind Harmer
2.163
315773AC2-141 GEN
Solar/Wind Helper
2.93
3144873MCLAUGH
Solar/Wind Helper
0.003
3144536CHRHLND
Solar/Wind Helper
0.018
3145336SMITFLD
Solar/Wind Helper
0.047
3146456SLIGO L269
Solar/Wind Helper
0.116
316238AB2-078_GEN
Solar/Wind Harmer
0.865
970285AG2-188 GEN
Solar/Wind Harmer
23.962
316118AC1-105 GEN
Solar/Wind Harmer
1.856
3147173SINAI
Solar/Wind Harmer
-0.026
3147243WELCO
Solar/Wind Harmer
-0.016
971845AH1-439 GEN
Solar/Wind Harmer
13.702
970865AG2-541 GEN
Solar/Wind Harmer
8.857
970831AG2-522 GEN
Solar/Wind Harmer
9.385
316123AC1-075 GEN
Solar/Wind Harmer
2.017
970165AG2-112 GEN
Solar/Wind Harmer
1.776
970163AG2-111 GEN
Solar/Wind Harmer
1.694
971447AH1-217 GEN
Solar/Wind Harmer
3.888
270494AE1-108_GEN
Solar/Wind Harmer
2.594
270455AD2-022 GEN
Solar/Wind Harmer
1.322
270457AD2-023 GEN
Solar/Wind Harmer
0.671
3143316POE
Solar/Wind Helper
0.479
319010AE1-072 C
Solar/Wind Helper
1.315
316305AF2-043 C
Solar/Wind Helper
0.151
3144293JTRSVLE
50/50
0.953
3144293JTRSVLE
50/50
0.802
970535AG2-341 GEN
50/50
4.472
3152661PLYWOOD A
50/50
0.536
971741AH1-377 GEN
Solar/Wind Harmer
58.889
970301AG2-198 GEN
Solar/Wind Harmer
23.454
970099AG2-077 GEN
Solar/Wind Harmer
54.659
3147133PAMPLIN
Solar/Wind Harmer
-0.032
3147133PAMPLIN
Solar/Wind Harmer
-0.026
958211AF2-115 GEN
Solar/Wind Harmer
4.952
963191AG1-168 GEN
Solar/Wind Harmer
2.971
316034AC1-036 C
Solar/Wind Harmer
0.563
970323AG2-213 GEN
Solar/Wind Harmer
15.183
971775AH1-396 GEN
Solar/Wind Harmer
2.162
313527AB2-043 GEN
Solar/Wind Harmer
4.685
939181AE1-148 GEN
Solar/Wind Harmer
15.721
962561AG1-105 GEN
Solar/Wind Harmer
15.572
964791AG1-342 GEN
Solar/Wind Harmer
5.869
3146843MT LREL
Solar/Wind Harmer
-0.027
3146843MT LREL
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.099
3146776BUCKING
Solar/Wind Harmer
-0.008
942751AE2-291 GEN
Solar/Wind Harmer
10.662
316222AC1-221 GEN
Solar/Wind Harmer
1.341
971489AH1-241 GEN
Solar/Wind Harmer
6.89
316217AC1-145 GEN
Solar/Wind Harmer
1.423
316197AC1-042 GEN
Solar/Wind Harmer
1.079
942671AE2-283 GEN
Solar/Wind Harmer
2.904
315821AE2-092 GEN
Solar/Wind Harmer
1.726
316036AC1-147 C
Solar/Wind Helper
0.188
3142956BIRDNECK
Solar/Wind Helper
0.083
316316AC1-027 C
Solar/Wind Helper
0.194
316185AD1-033 GEN
Solar/Wind Helper
0.577
3145506HICKORY
Solar/Wind Helper
0.484
3145506HICKORY
Solar/Wind Helper
0.29
3145506HICKORY
Solar/Wind Helper
0.073
316339AD2-160 GEN
Solar/Wind Helper
0.45
316018AA1-139 ULT2
Solar/Wind Helper
0.504
316017AA1-139 ULT1
Solar/Wind Helper
0.536
316236AE1-162_GEN
Solar/Wind Helper
0.157
3137176SLIGO L2192
Solar/Wind Helper
0.461
3130086AYDLETT
Solar/Wind Helper
0.459
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.989
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.34
MECLTFEXP_MEC->PJM
CLTF
1.478
LAGNLTFEXP_LAGN->PJM
CLTF
2.389
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.942
TVALTFEXP_TVA->PJM
CLTF
1.22
SIGELTFEXP_SIGE->PJM
CLTF
0.046
CPLELTFEXP_CPLE->PJM
CLTF
2.619
NYPJM->LTFIMP_NY
CLTF
0.449
LGEELTFEXP_LGEE->PJM
CLTF
0.593
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.946
WECLTFEXP_WEC->PJM
CLTF
0.305

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:196.14 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1331.14
MW Contribution:21.64
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.706
3144293JTRSVLE
50/50
0.594
970535AG2-341 GEN
50/50
2.11
3152661PLYWOOD A
50/50
0.217
3151041BRUNSWICKG3
50/50
1.059
972187AH1-678 GEN
50/50
2.43
3151921BEARGRDN G2
50/50
4.238
3144293JTRSVLE
50/50
0.706
970413AG2-270 GEN
50/50
10.245
3151591KERR 2
50/50
0.22
3151031BRUNSWICKG2
50/50
1.059
3151261ROARAP2
50/50
0.095
3150861SPRUNCD
50/50
0.364
966251AG1-494 GEN
50/50
1.288
970221AG2-151 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
0.132
3146926FARMVIL
Solar/Wind Harmer
0.176
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.159
316258AE1-075 C
Solar/Wind Harmer
0.19
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.801
970909AG2-566 GEN
Solar/Wind Harmer
2.396
3147133PAMPLIN
Solar/Wind Harmer
0.693
971193AH1-056 GEN
Solar/Wind Harmer
13.448
963181AG1-167 GEN
Solar/Wind Harmer
0.835
959311AF2-222 GEN
Solar/Wind Harmer
15.884
970257AG2-171 GEN
Solar/Wind Harmer
5.55
315785AD2-033 C
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
9.804
316131AB2-060 GEN
Solar/Wind Harmer
0.426
958131AF2-107 GEN
Solar/Wind Harmer
3.651
316478AD1-087 GEN
Solar/Wind Harmer
0.382
316486AD2-202 GEN
Solar/Wind Harmer
0.112
3147043LAWRENC
Solar/Wind Harmer
0.059
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.912
971683AH1-343 GEN
Solar/Wind Harmer
3.032
313506AB2-031 GEN
Solar/Wind Harmer
0.248
970917AG2-570 GEN
Solar/Wind Harmer
6.901
316365GEN2_N
Solar/Wind Harmer
0.164
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
0.117
3145893MURPHYS
Solar/Wind Harmer
0.07
957521AF2-046 GEN
Solar/Wind Harmer
5.202
961681AG1-008 GEN
Solar/Wind Harmer
5.202
3145796HORNRTN
Solar/Wind Harmer
0.279
3145796HORNRTN
Solar/Wind Harmer
0.07
316210AC1-098 GEN
Solar/Wind Harmer
0.644
3146173TUNIS
Solar/Wind Harmer
0.069
316463AE2-346 GEN
Solar/Wind Harmer
0.059
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.732
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.069
316327AA2-057 GEN
Solar/Wind Harmer
0.102
315724AD1-057 GEN
Solar/Wind Harmer
0.25
3145273HOLLAND
Solar/Wind Harmer
0.05
3156021HOLLOMANSOL
Solar/Wind Harmer
0.301
3146233WITAKRS
Solar/Wind Harmer
0.331
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3146206CASHIE
Solar/Wind Harmer
0.065
315813AE1-149 C
Solar/Wind Harmer
3.482
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316283AC2-100 C
Solar/Wind Harmer
0.127
315839AE2-212 C
Solar/Wind Harmer
0.001
315737AD1-076 GEN
Solar/Wind Harmer
0.835
970661AG2-428 GEN
Solar/Wind Harmer
1.373
971157AH1-035 GEN
Solar/Wind Harmer
0.778
315614AA2-178 GEN
Solar/Wind Harmer
0.37
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.129
3146376EDENTON
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
4.548
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316435W1029_GEN3
Solar/Wind Harmer
0
965281AG1-393 GEN
Solar/Wind Harmer
0.68
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
316320Y1-086
Solar/Wind Harmer
0
3145933PARMELE
Solar/Wind Harmer
0.063
966801AG1-551 GEN
Solar/Wind Harmer
0.74
3146456SLIGO L269
Solar/Wind Harmer
0.063
971153AH1-033 GEN
Solar/Wind Harmer
0.732
944581AF1-123 GEN
Solar/Wind Harmer
14.239
944601AF1-125 GEN
Solar/Wind Harmer
14.019
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3151101ELIZAR3
Adder
5.847
3144873MCLAUGH
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.009
315773AC2-141 GEN
Solar/Wind Harmer
2.27
3145336SMITFLD
Solar/Wind Harmer
0.025
3151221GRAVEL6
Adder
4.403
3151171GRAVELC
Adder
0.847
961611AG1-000B GEN
Solar/Wind Harmer
1.612
3143096IRON208
Adder
0.252
3143096IRON208
Adder
0.247
315778AD1-151 GEN
Solar/Wind Harmer
4.818
970129AG2-093 GEN
Solar/Wind Harmer
3.634
970133AG2-095 GEN
Solar/Wind Harmer
0.576
316499AE2-029_GEN
Solar/Wind Helper
0.501
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.3
3148013FISHERV
Solar/Wind Helper
0.129
315616AA1-038_C
Solar/Wind Helper
0.524
3151931BEARGRDN S1
50/50
5.469
3151911BEARGRDN G1
50/50
4.238
3144293JTRSVLE
50/50
0.706
970119AG2-088 GEN
50/50
15.414
3151531CLOVER1
50/50
2.348
3151601KERR 3
50/50
0.22
3151581KERR 1
50/50
0.079
3147043LAWRENC
50/50
0.939
3151051BRUNSWICKS1
50/50
2.197
3151021BRUNSWICKG1
50/50
1.059
971451AH1-221 GEN
50/50
3.216
315243AE2-183_GT3
50/50
1.321
3151261ROARAP2
50/50
0.097
3150851SPRUNCC
50/50
0.364
972003AH1-546 GEN
Solar/Wind Harmer
18.676
971377AH1-170 GEN
Solar/Wind Harmer
4.327
3147623JAMES R
Solar/Wind Harmer
0.94
970937AG2-583 GEN
Solar/Wind Harmer
23.217
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.147
3146926FARMVIL
Solar/Wind Harmer
0.176
316336AC2-165 C
Solar/Wind Harmer
0.011
3143336POWHATN
Solar/Wind Harmer
4.472
963171AG1-166 GEN
Solar/Wind Harmer
1.114
971563AH1-280 GEN
Solar/Wind Harmer
2.228
970685AG2-442 GEN
Solar/Wind Harmer
14.313
962491AG1-098 GEN
Solar/Wind Harmer
7.815
315693AD1-088 GEN
Solar/Wind Harmer
6.344
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Harmer
0.116
957481AF2-042 GEN
Solar/Wind Harmer
29.295
970401AG2-262 GEN
Solar/Wind Harmer
0.638
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
4.184
3143526WINTERP
Solar/Wind Harmer
0.504
316129AC1-054 GEN
Solar/Wind Harmer
0.363
971795AH1-408 GEN
Solar/Wind Harmer
6.199
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.793
970919AG2-571 GEN
Solar/Wind Harmer
2.76
970087AG2-069 GEN
Solar/Wind Harmer
6.187
3145783HORNRTN
Solar/Wind Harmer
0.076
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
5.984
316023GEN1_S
Solar/Wind Harmer
0.164
939411AE1-173 GEN
Solar/Wind Harmer
30.681
316011AB1-132 GEN
Solar/Wind Harmer
1.286
962571AG1-106 GEN
Solar/Wind Harmer
1.007
3146263WOODLND
Solar/Wind Harmer
0.071
3145893MURPHYS
Solar/Wind Harmer
0.281
3145893MURPHYS
Solar/Wind Harmer
0.312
3145796HORNRTN
Solar/Wind Harmer
0.23
3145796HORNRTN
Solar/Wind Harmer
0.07
316212AC1-099_GEN
Solar/Wind Harmer
0.359
3146173TUNIS
Solar/Wind Harmer
0.069
3145823KELFORD
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
315722AD1-056 GEN
Solar/Wind Harmer
0.422
3146233WITAKRS
Solar/Wind Harmer
0.263
3146206CASHIE
Solar/Wind Harmer
0.065
971547AH1-271 GEN
Solar/Wind Harmer
1.396
970659AG2-427 GEN
Solar/Wind Harmer
3.146
316381AD1-082 GEN
Solar/Wind Harmer
0.068
970661AG2-428 GEN
Solar/Wind Harmer
6.453
3145663CRESWEL
Solar/Wind Harmer
0.181
971163AH1-040 GEN
Solar/Wind Harmer
5.167
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.052
316359AB2-059 GEN
Solar/Wind Harmer
0.231
316049AB1-081 GEN
Solar/Wind Harmer
0.368
3142053HEARTS
Solar/Wind Harmer
0.113
316093AE2-104_GEN
Solar/Wind Harmer
1.081
3130156CHOWAN
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3142543TWELFTH
Solar/Wind Harmer
0.006
3146516WINFALL
Solar/Wind Harmer
0.207
3146516WINFALL
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.283
316246AF1-032 C
Solar/Wind Harmer
0.029
3146293MARTNCO
Solar/Wind Harmer
0.059
316494AC1-189 GEN
Solar/Wind Harmer
0.214
3146456SLIGO L269
Solar/Wind Harmer
0.063
316388AE2-253 GEN
Solar/Wind Harmer
0.198
944591AF1-124 GEN
Solar/Wind Harmer
14.289
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
315671AE2-027_GEN
Solar/Wind Harmer
4.043
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
1.077
3145336SMITFLD
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
0.644
961611AG1-000B GEN
Solar/Wind Harmer
3.17
971647AH1-324 GEN
Solar/Wind Harmer
2.576
3143096IRON208
Adder
0.252
971069AG2-661 GEN
Solar/Wind Harmer
1.071
316458AB2-190 GEN2
Solar/Wind Harmer
0.323
970129AG2-093 GEN
Solar/Wind Harmer
1.71
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.903
3147666LOUISA
Solar/Wind Helper
0.521
972205AH1-687 GEN
50/50
20.67
316303AF2-085
50/50
2.055
3151541CLOVER2
50/50
2.336
3151611KERR 4
50/50
0.22
3151621KERR 5
50/50
0.22
3151631KERR 6
50/50
0.22
3151641KERR 7
50/50
0.22
963041AG1-153 GEN
50/50
2.144
315244AE2-183_ST
50/50
2.284
3151281ROARAP4
50/50
0.094
3151281ROARAP4
50/50
0.088
971285AH1-108 GEN
50/50
0.596
315779AE2-040
50/50
1.013
971447AH1-217 GEN
Solar/Wind Harmer
11.337
971845AH1-439 GEN
Solar/Wind Harmer
16.33
970285AG2-188 GEN
Solar/Wind Harmer
27.559
270494AE1-108_GEN
Solar/Wind Harmer
3.817
315657AE1-056 GEN
Solar/Wind Harmer
7.617
946301AF1-294 GEN
Solar/Wind Harmer
4.122
961791AG1-021 GEN
Solar/Wind Harmer
2.005
970683AG2-441 GEN
Solar/Wind Harmer
12.78
970681AG2-440 GEN
Solar/Wind Harmer
10.224
3144303KENBRDG
Solar/Wind Harmer
0.139
971443AH1-215 GEN
Solar/Wind Harmer
2.888
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.258
316233AE1-074 FULL
Solar/Wind Harmer
0.078
971281AH1-106 GEN
Solar/Wind Harmer
1.344
971283AH1-107 GEN
Solar/Wind Harmer
1.344
970831AG2-522 GEN
Solar/Wind Harmer
4.036
3147173SINAI
Solar/Wind Harmer
0.092
3147243WELCO
Solar/Wind Harmer
0.057
971967AH1-528 GEN
Solar/Wind Harmer
13.711
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
16.986
970673AG2-436 GEN
Solar/Wind Harmer
11.324
941031AE2-094 GEN
Solar/Wind Harmer
14.544
944011AF1-069 GEN
Solar/Wind Harmer
4.752
3137643SOCKMAN
Solar/Wind Harmer
0.315
970865AG2-541 GEN
Solar/Wind Harmer
2.702
970085AG2-068 GEN
Solar/Wind Harmer
4.124
970581AG2-369 GEN
Solar/Wind Harmer
3.547
315607AA1-063A GEN
Solar/Wind Harmer
0.154
3146043SEABORD
Solar/Wind Harmer
0.075
315814AE2-033 C
Solar/Wind Harmer
5.747
316315AB2-025 C
Solar/Wind Harmer
0.059
965291AG1-394 GEN
Solar/Wind Harmer
0.317
315652AC1-086 GEN
Solar/Wind Harmer
7.782
3145893MURPHYS
Solar/Wind Harmer
0.19
3145893MURPHYS
Solar/Wind Harmer
0.07
3145796HORNRTN
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.028
3146033SCOT NK
Solar/Wind Harmer
0.276
316123AC1-075 GEN
Solar/Wind Harmer
0.094
970165AG2-112 GEN
Solar/Wind Harmer
0.558
970163AG2-111 GEN
Solar/Wind Harmer
0.532
3145513AHOSKIE
Solar/Wind Harmer
0.143
3145513AHOSKIE
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3143316POE
Solar/Wind Harmer
0.269
316319Z2-044 C
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.065
970601AG2-382 GEN
Solar/Wind Harmer
2.444
315732AD1-074 GEN1
Solar/Wind Harmer
0.373
315733AD1-074 GEN2
Solar/Wind Harmer
0.373
315735AD1-075 GEN1
Solar/Wind Harmer
0.187
3130546PLYMOUTH
Solar/Wind Harmer
0.065
315816AE2-034 GEN
Solar/Wind Harmer
0.277
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.044
316311AC2-079 GEN
Solar/Wind Harmer
1.853
315835AF2-110_GEN
Solar/Wind Harmer
0.441
3130156CHOWAN
Solar/Wind Harmer
0.064
3130156CHOWAN
Solar/Wind Harmer
0.064
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
316321Z2-027
Solar/Wind Harmer
0.012
3145176PASQUOTANK
Solar/Wind Harmer
0.039
3146396TANGLEW
Solar/Wind Harmer
0.175
316420AA1-050 GEN
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.034
316305AF2-043 C
Solar/Wind Harmer
0.001
957861AF2-080 GEN
Solar/Wind Harmer
2.737
3146406KITTY HAWK
Solar/Wind Harmer
0.008
319010AE1-072 C
Solar/Wind Harmer
0.319
957871AF2-081 GEN
Solar/Wind Harmer
3.153
316005AA1-067
Solar/Wind Harmer
0.068
3145746EVERETS
Solar/Wind Harmer
0.252
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
970181AG2-120 GEN
Solar/Wind Harmer
0.787
3151081ELIZAR1
Adder
5.773
3151091ELIZAR2
Adder
5.672
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.68
3152601GOSPORTA
Adder
0.628
971445AH1-216 GEN
Solar/Wind Harmer
4.321
972265AH1-717 GEN
Adder
4.702
3151201GRAVEL4
Adder
4.408
3151191GRAVEL3
Adder
4.352
3151211GRAVEL5
Adder
4.352
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.323
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.077
3148013FISHERV
Solar/Wind Helper
0.074
3148463FAIRFLD
Solar/Wind Helper
0.116
315242AE2-183_GT2
50/50
1.321
315241AE2-183_GT1
50/50
1.313
972185AH1-677 GEN
50/50
4.762
970533AG2-339 GEN
50/50
7.019
970531AG2-338 GEN
50/50
2.808
971489AH1-241 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
1.465
3146776BUCKING
Solar/Wind Harmer
0.119
315821AE2-092 GEN
Solar/Wind Harmer
0.014
970301AG2-198 GEN
Solar/Wind Harmer
9.583
3147133PAMPLIN
Solar/Wind Harmer
0.221
3147133PAMPLIN
Solar/Wind Harmer
0.176
958211AF2-115 GEN
Solar/Wind Harmer
2.506
963191AG1-168 GEN
Solar/Wind Harmer
0.835
971741AH1-377 GEN
Solar/Wind Harmer
20.177
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.401
971775AH1-396 GEN
Solar/Wind Harmer
0.278
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971223AH1-071 GEN
Solar/Wind Harmer
1.233
962561AG1-105 GEN
Solar/Wind Harmer
5.397
939181AE1-148 GEN
Solar/Wind Harmer
5.333
970099AG2-077 GEN
Solar/Wind Harmer
11.718
964791AG1-342 GEN
Solar/Wind Harmer
2.089
3146843MT LREL
Solar/Wind Harmer
0.109
3146843MT LREL
Solar/Wind Harmer
0.109
3143526WINTERP
Solar/Wind Harmer
0.504
970933AG2-581 GEN
Solar/Wind Harmer
7.465
316181AB2-040 GEN
Solar/Wind Harmer
0.116
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.078
966811AG1-552 GEN
Solar/Wind Harmer
0.843
3145593CAROLNA
Solar/Wind Harmer
0.097
3145783HORNRTN
Solar/Wind Harmer
1.361
3145783HORNRTN
Solar/Wind Harmer
1.089
3145783HORNRTN
Solar/Wind Harmer
0.34
3145783HORNRTN
Solar/Wind Harmer
0.136
316426AA2-053 GEN
Solar/Wind Harmer
0.256
3144356SAPONY
Solar/Wind Harmer
0.607
316274AC1-208 GEN
Solar/Wind Harmer
0.366
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.042
3145893MURPHYS
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
0.126
3145796HORNRTN
Solar/Wind Harmer
0.209
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
315742AE1-103 GEN
Solar/Wind Harmer
0.001
316222AC1-221 GEN
Solar/Wind Harmer
0.272
316065AD1-022 GEN
Solar/Wind Harmer
3.004
970657AG2-426 GEN
Solar/Wind Harmer
2.275
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
2.446
3146376EDENTON
Solar/Wind Harmer
0.286
3146376EDENTON
Solar/Wind Harmer
0.286
961601AG1-000A GEN
Solar/Wind Harmer
1.137
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3145493TOT1
Solar/Wind Harmer
0.148
3145453TOT5
Solar/Wind Harmer
0.089
3145603CNETO
Solar/Wind Harmer
0.059
3146386ELIZ CT
Solar/Wind Harmer
0.064
3145933PARMELE
Solar/Wind Harmer
0.127
3145933PARMELE
Solar/Wind Harmer
0.063
3130086AYDLETT
Solar/Wind Harmer
0.253
3137176SLIGO L2192
Solar/Wind Harmer
0.252
3146456SLIGO L269
Solar/Wind Harmer
1.121
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.035
316339AD2-160 GEN
Solar/Wind Harmer
0.103
3145506HICKORY
Solar/Wind Harmer
0.253
3145506HICKORY
Solar/Wind Harmer
0.152
3145506HICKORY
Solar/Wind Harmer
0.038
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.061
942751AE2-291 GEN
Solar/Wind Harmer
3.43
316240AF1-291 C
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.012
3150991CHESPKB
Adder
0.659
3150991CHESPKB
Adder
0.643
944641AF1-129 GEN
Adder
29.755
316236AE1-162_GEN
Solar/Wind Harmer
0
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.068
966001AG1-469 GEN
Solar/Wind Helper
0.206
LAGNLTFEXP_LAGN->PJM
CLTF
1.972
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.131
MECLTFEXP_MEC->PJM
CLTF
0.546
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.458
TVALTFEXP_TVA->PJM
CLTF
0.973
NYPJM->LTFIMP_NY
CLTF
0.616
LGEELTFEXP_LGEE->PJM
CLTF
0.137
WECLTFEXP_WEC->PJM
CLTF
0.063
CPLELTFEXP_CPLE->PJM
CLTF
4.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.705

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:182.57 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1515.37
MW Contribution:28.43
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.704
970221AG2-151 GEN
Solar/Wind Harmer
28.432
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.296
316313AB2-026
Solar/Wind Harmer
0.761
316258AE1-075 C
Solar/Wind Harmer
0.685
316405AF2-144 C
Solar/Wind Harmer
0.723
3143336POWHATN
Solar/Wind Harmer
2.847
970909AG2-566 GEN
Solar/Wind Harmer
2.392
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.485
963181AG1-167 GEN
Solar/Wind Harmer
2.197
959311AF2-222 GEN
Solar/Wind Harmer
20.924
970257AG2-171 GEN
Solar/Wind Harmer
7.297
315785AD2-033 C
Solar/Wind Harmer
4.227
964241AG1-285 GEN
Solar/Wind Harmer
12.89
316131AB2-060 GEN
Solar/Wind Harmer
1.639
958131AF2-107 GEN
Solar/Wind Harmer
4.847
316478AD1-087 GEN
Solar/Wind Harmer
1.065
316486AD2-202 GEN
Solar/Wind Harmer
0.312
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.31
960061AF2-297 GEN
Solar/Wind Harmer
5.143
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.986
313506AB2-031 GEN
Solar/Wind Harmer
0.724
970917AG2-570 GEN
Solar/Wind Harmer
21.795
3150861SPRUNCD
Adder
0.344
316365GEN2_N
Solar/Wind Harmer
0.555
3156081AA2-088 GEN
Solar/Wind Harmer
2.586
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.185
961681AG1-008 GEN
Solar/Wind Harmer
6.185
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146173TUNIS
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.125
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.963
316317KELFORD C
Solar/Wind Harmer
0.363
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.766
315724AD1-057 GEN
Solar/Wind Harmer
0.43
3145273HOLLAND
Solar/Wind Harmer
-0.006
3156021HOLLOMANSOL
Solar/Wind Harmer
1.002
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.587
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
1.186
315839AE2-212 C
Solar/Wind Harmer
0.22
970661AG2-428 GEN
Solar/Wind Harmer
1.373
315737AD1-076 GEN
Solar/Wind Harmer
1.386
316283AC2-100 C
Solar/Wind Harmer
0.686
971157AH1-035 GEN
Solar/Wind Harmer
0.911
315614AA2-178 GEN
Solar/Wind Harmer
0.783
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
972205AH1-687 GEN
50/50
20.633
316303AF2-085
50/50
2.054
971447AH1-217 GEN
Solar/Wind Harmer
14.897
971845AH1-439 GEN
Solar/Wind Harmer
21.465
970285AG2-188 GEN
Solar/Wind Harmer
34.19
270494AE1-108_GEN
Solar/Wind Harmer
9.286
315657AE1-056 GEN
Solar/Wind Harmer
9.291
946301AF1-294 GEN
Solar/Wind Harmer
6.004
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
16.801
970681AG2-440 GEN
Solar/Wind Harmer
13.441
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.796
316239AB2-077_GEN
Solar/Wind Harmer
0.439
316238AB2-078_GEN
Solar/Wind Harmer
0.439
316118AC1-105 GEN
Solar/Wind Harmer
0.773
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.769
971283AH1-107 GEN
Solar/Wind Harmer
1.769
970831AG2-522 GEN
Solar/Wind Harmer
5.308
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.09
946281AF1-292 GEN
Solar/Wind Harmer
0.208
316087AB2-174 GEN
Solar/Wind Harmer
1.297
970673AG2-436 GEN
Solar/Wind Harmer
18.787
970673AG2-436 GEN
Solar/Wind Harmer
9.512
941031AE2-094 GEN
Solar/Wind Harmer
16.63
944011AF1-069 GEN
Solar/Wind Harmer
5.211
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970865AG2-541 GEN
Solar/Wind Harmer
3.55
970085AG2-068 GEN
Solar/Wind Harmer
5.427
970581AG2-369 GEN
Solar/Wind Harmer
4.667
315607AA1-063A GEN
Solar/Wind Harmer
0.852
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.6
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.71
315652AC1-086 GEN
Solar/Wind Harmer
8.941
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
316123AC1-075 GEN
Solar/Wind Harmer
0.832
970165AG2-112 GEN
Solar/Wind Harmer
0.733
970163AG2-111 GEN
Solar/Wind Harmer
0.699
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316319Z2-044 C
Solar/Wind Harmer
0.41
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.217
315732AD1-074 GEN1
Solar/Wind Harmer
1.475
315733AD1-074 GEN2
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.737
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316349AD2-085 GEN
Solar/Wind Harmer
0.645
315816AE2-034 GEN
Solar/Wind Harmer
0.587
316311AC2-079 GEN
Solar/Wind Harmer
3.659
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.779
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
316321Z2-027
Solar/Wind Harmer
0.193
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.193
316420AA1-050 GEN
Solar/Wind Harmer
0.816
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.858
3146516WINFALL
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.896
316435W1029_GEN3
Solar/Wind Harmer
1.299
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.419
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.891
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3144293JTRSVLE
50/50
0.704
3144293JTRSVLE
50/50
0.593
970535AG2-341 GEN
50/50
2.107
971489AH1-241 GEN
Solar/Wind Harmer
26.992
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.547
970301AG2-198 GEN
Solar/Wind Harmer
12.599
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
963191AG1-168 GEN
Solar/Wind Harmer
2.197
971741AH1-377 GEN
Solar/Wind Harmer
26.527
316034AC1-036 C
Solar/Wind Harmer
0.362
970323AG2-213 GEN
Solar/Wind Harmer
9.73
971775AH1-396 GEN
Solar/Wind Harmer
1.386
313527AB2-043 GEN
Solar/Wind Harmer
2.416
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.096
939181AE1-148 GEN
Solar/Wind Harmer
7.013
970099AG2-077 GEN
Solar/Wind Harmer
15.412
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.821
972187AH1-678 GEN
Adder
2.289
316181AB2-040 GEN
Solar/Wind Harmer
1.257
972185AH1-677 GEN
Adder
4.486
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.855
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.79
316222AC1-221 GEN
Solar/Wind Harmer
0.745
316065AD1-022 GEN
Solar/Wind Harmer
3.665
970657AG2-426 GEN
Solar/Wind Harmer
2.282
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
3.387
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.822
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.78
966001AG1-469 GEN
Solar/Wind Helper
0.216
3151931BEARGRDN S1
50/50
5.46
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.704
970119AG2-088 GEN
50/50
15.406
972003AH1-546 GEN
Solar/Wind Harmer
24.588
971377AH1-170 GEN
Solar/Wind Harmer
5.686
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.518
316322AB2-045
Solar/Wind Harmer
1.382
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.598
3143336POWHATN
Solar/Wind Harmer
3.349
963171AG1-166 GEN
Solar/Wind Harmer
2.929
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
18.817
962491AG1-098 GEN
Solar/Wind Harmer
10.277
315693AD1-088 GEN
Solar/Wind Harmer
7.416
316237AB2-079_GEN
Solar/Wind Harmer
0.439
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.531
970401AG2-262 GEN
Solar/Wind Harmer
0.797
315687AD1-152 GEN
Solar/Wind Harmer
1.353
971065AG2-659 GEN
Solar/Wind Harmer
5.503
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.948
971795AH1-408 GEN
Solar/Wind Harmer
7.828
316003AC1-222 GEN
Solar/Wind Harmer
0.95
960081AF2-299 GEN
Solar/Wind Harmer
1.043
970919AG2-571 GEN
Solar/Wind Harmer
2.759
970087AG2-069 GEN
Solar/Wind Harmer
8.141
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
940641AE2-051 GEN
Solar/Wind Harmer
7.878
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.555
939411AE1-173 GEN
Solar/Wind Harmer
40.398
316011AB1-132 GEN
Solar/Wind Harmer
1.663
962571AG1-106 GEN
Solar/Wind Harmer
1.142
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.68
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.782
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.838
970659AG2-427 GEN
Solar/Wind Harmer
3.885
316381AD1-082 GEN
Solar/Wind Harmer
0.67
970661AG2-428 GEN
Solar/Wind Harmer
7.748
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.803
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.974
316049AB1-081 GEN
Solar/Wind Harmer
0.78
316093AE2-104_GEN
Solar/Wind Harmer
2.1
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
315800Z1-036_GEN1
Solar/Wind Harmer
1.779
316174AB2-169 GEN
Solar/Wind Harmer
1.109
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
316246AF1-032 C
Solar/Wind Harmer
0.144
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
944591AF1-124 GEN
Solar/Wind Harmer
32.454
3150981CHESPKA
Adder
0.786
3151171GRAVELC
Adder
0.645
3143096IRON208
Adder
0.253
944631AF1-128 GEN
Adder
26.841
316192AB2-158 GEN
Solar/Wind Helper
1.013
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
316305AF2-043 C
Solar/Wind Harmer
0.215
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
3151081ELIZAR1
Adder
5.776
3151091ELIZAR2
Adder
5.675
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.681
3152601GOSPORTA
Adder
0.628
972265AH1-717 GEN
Adder
4.706
3151201GRAVEL4
Adder
4.411
3151191GRAVEL3
Adder
4.355
3151211GRAVEL5
Adder
4.355
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
3151101ELIZAR3
Adder
5.849
3151221GRAVEL6
Adder
4.406
3151171GRAVELC
Adder
0.848
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.338
3148013FISHERV
Solar/Wind Helper
0.13
315616AA1-038_C
Solar/Wind Helper
0.528
944581AF1-123 GEN
Solar/Wind Harmer
20.452
LAGNLTFEXP_LAGN->PJM
CLTF
1.959
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.573
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.107
MECLTFEXP_MEC->PJM
CLTF
0.537
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.437
TVALTFEXP_TVA->PJM
CLTF
0.967
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.612
LGEELTFEXP_LGEE->PJM
CLTF
0.133
WECLTFEXP_WEC->PJM
CLTF
0.061
CPLELTFEXP_CPLE->PJM
CLTF
4.206
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.627

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:182.57 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1515.34
MW Contribution:28.43
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.46
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.704
970119AG2-088 GEN
50/50
15.406
972003AH1-546 GEN
Solar/Wind Harmer
24.587
971377AH1-170 GEN
Solar/Wind Harmer
5.686
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.517
316322AB2-045
Solar/Wind Harmer
1.382
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.597
3143336POWHATN
Solar/Wind Harmer
3.349
963171AG1-166 GEN
Solar/Wind Harmer
2.929
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
18.817
962491AG1-098 GEN
Solar/Wind Harmer
10.277
315693AD1-088 GEN
Solar/Wind Harmer
7.416
316237AB2-079_GEN
Solar/Wind Harmer
0.439
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.531
970401AG2-262 GEN
Solar/Wind Harmer
0.797
315687AD1-152 GEN
Solar/Wind Harmer
1.353
971065AG2-659 GEN
Solar/Wind Harmer
5.503
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.948
971795AH1-408 GEN
Solar/Wind Harmer
7.828
316003AC1-222 GEN
Solar/Wind Harmer
0.95
960081AF2-299 GEN
Solar/Wind Harmer
1.043
970919AG2-571 GEN
Solar/Wind Harmer
2.759
970087AG2-069 GEN
Solar/Wind Harmer
8.141
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
940641AE2-051 GEN
Solar/Wind Harmer
7.878
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.555
939411AE1-173 GEN
Solar/Wind Harmer
40.398
316011AB1-132 GEN
Solar/Wind Harmer
1.663
962571AG1-106 GEN
Solar/Wind Harmer
1.142
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.68
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.782
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.838
970659AG2-427 GEN
Solar/Wind Harmer
3.885
316381AD1-082 GEN
Solar/Wind Harmer
0.67
970661AG2-428 GEN
Solar/Wind Harmer
7.748
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.803
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.974
316049AB1-081 GEN
Solar/Wind Harmer
0.78
316093AE2-104_GEN
Solar/Wind Harmer
2.1
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
315800Z1-036_GEN1
Solar/Wind Harmer
1.779
316174AB2-169 GEN
Solar/Wind Harmer
1.109
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
316246AF1-032 C
Solar/Wind Harmer
0.144
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
972205AH1-687 GEN
50/50
20.633
316303AF2-085
50/50
2.054
971447AH1-217 GEN
Solar/Wind Harmer
14.896
971845AH1-439 GEN
Solar/Wind Harmer
21.465
970285AG2-188 GEN
Solar/Wind Harmer
34.19
270494AE1-108_GEN
Solar/Wind Harmer
9.286
315657AE1-056 GEN
Solar/Wind Harmer
9.291
946301AF1-294 GEN
Solar/Wind Harmer
6.004
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
16.8
970681AG2-440 GEN
Solar/Wind Harmer
13.44
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.796
316239AB2-077_GEN
Solar/Wind Harmer
0.439
3144293JTRSVLE
50/50
0.704
3144293JTRSVLE
50/50
0.593
970535AG2-341 GEN
50/50
2.107
971489AH1-241 GEN
Solar/Wind Harmer
26.992
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.547
970301AG2-198 GEN
Solar/Wind Harmer
12.599
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
963191AG1-168 GEN
Solar/Wind Harmer
2.197
971741AH1-377 GEN
Solar/Wind Harmer
26.527
316034AC1-036 C
Solar/Wind Harmer
0.361
970323AG2-213 GEN
Solar/Wind Harmer
9.729
971775AH1-396 GEN
Solar/Wind Harmer
1.386
313527AB2-043 GEN
Solar/Wind Harmer
2.416
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.096
939181AE1-148 GEN
Solar/Wind Harmer
7.013
970099AG2-077 GEN
Solar/Wind Harmer
15.412
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.821
972187AH1-678 GEN
Adder
2.289
316181AB2-040 GEN
Solar/Wind Harmer
1.257
972185AH1-677 GEN
Adder
4.486
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.855
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.79
316222AC1-221 GEN
Solar/Wind Harmer
0.745
316065AD1-022 GEN
Solar/Wind Harmer
3.665
970657AG2-426 GEN
Solar/Wind Harmer
2.282
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
3.387
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.822
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316238AB2-078_GEN
Solar/Wind Harmer
0.439
316118AC1-105 GEN
Solar/Wind Harmer
0.773
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.769
971283AH1-107 GEN
Solar/Wind Harmer
1.769
970831AG2-522 GEN
Solar/Wind Harmer
5.308
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.09
946281AF1-292 GEN
Solar/Wind Harmer
0.208
316087AB2-174 GEN
Solar/Wind Harmer
1.297
970673AG2-436 GEN
Solar/Wind Harmer
18.787
970673AG2-436 GEN
Solar/Wind Harmer
9.512
941031AE2-094 GEN
Solar/Wind Harmer
16.63
944011AF1-069 GEN
Solar/Wind Harmer
5.211
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970865AG2-541 GEN
Solar/Wind Harmer
3.55
970085AG2-068 GEN
Solar/Wind Harmer
5.427
970581AG2-369 GEN
Solar/Wind Harmer
4.667
315607AA1-063A GEN
Solar/Wind Harmer
0.852
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.6
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.71
315652AC1-086 GEN
Solar/Wind Harmer
8.941
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
316123AC1-075 GEN
Solar/Wind Harmer
0.832
970165AG2-112 GEN
Solar/Wind Harmer
0.733
970163AG2-111 GEN
Solar/Wind Harmer
0.699
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316319Z2-044 C
Solar/Wind Harmer
0.41
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.217
315732AD1-074 GEN1
Solar/Wind Harmer
1.475
315733AD1-074 GEN2
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.737
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316349AD2-085 GEN
Solar/Wind Harmer
0.645
315816AE2-034 GEN
Solar/Wind Harmer
0.587
316311AC2-079 GEN
Solar/Wind Harmer
3.659
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.779
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.193
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.193
316305AF2-043 C
Solar/Wind Harmer
0.215
316420AA1-050 GEN
Solar/Wind Harmer
0.816
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
3151081ELIZAR1
Adder
5.776
3151091ELIZAR2
Adder
5.675
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.681
3152601GOSPORTA
Adder
0.628
972265AH1-717 GEN
Adder
4.706
3151201GRAVEL4
Adder
4.411
3151191GRAVEL3
Adder
4.355
3151211GRAVEL5
Adder
4.355
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
944591AF1-124 GEN
Solar/Wind Harmer
32.454
3150981CHESPKA
Adder
0.786
3151171GRAVELC
Adder
0.645
3143096IRON208
Adder
0.253
944631AF1-128 GEN
Adder
26.842
316192AB2-158 GEN
Solar/Wind Helper
1.014
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
316433W1029_GEN2
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.781
966001AG1-469 GEN
Solar/Wind Helper
0.216
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.704
970221AG2-151 GEN
Solar/Wind Harmer
28.431
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.296
316313AB2-026
Solar/Wind Harmer
0.761
316258AE1-075 C
Solar/Wind Harmer
0.685
316405AF2-144 C
Solar/Wind Harmer
0.723
3143336POWHATN
Solar/Wind Harmer
2.847
970909AG2-566 GEN
Solar/Wind Harmer
2.392
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.484
963181AG1-167 GEN
Solar/Wind Harmer
2.197
959311AF2-222 GEN
Solar/Wind Harmer
20.924
970257AG2-171 GEN
Solar/Wind Harmer
7.297
315785AD2-033 C
Solar/Wind Harmer
4.227
964241AG1-285 GEN
Solar/Wind Harmer
12.89
316131AB2-060 GEN
Solar/Wind Harmer
1.639
958131AF2-107 GEN
Solar/Wind Harmer
4.847
316478AD1-087 GEN
Solar/Wind Harmer
1.065
316486AD2-202 GEN
Solar/Wind Harmer
0.312
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.31
960061AF2-297 GEN
Solar/Wind Harmer
5.143
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.986
313506AB2-031 GEN
Solar/Wind Harmer
0.724
970917AG2-570 GEN
Solar/Wind Harmer
21.795
3150861SPRUNCD
Adder
0.344
316365GEN2_N
Solar/Wind Harmer
0.555
3156081AA2-088 GEN
Solar/Wind Harmer
2.585
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.185
961681AG1-008 GEN
Solar/Wind Harmer
6.185
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146173TUNIS
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.125
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.963
316317KELFORD C
Solar/Wind Harmer
0.363
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.766
315724AD1-057 GEN
Solar/Wind Harmer
0.43
3145273HOLLAND
Solar/Wind Harmer
-0.006
3156021HOLLOMANSOL
Solar/Wind Harmer
1.002
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.587
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
1.186
315839AE2-212 C
Solar/Wind Harmer
0.22
970661AG2-428 GEN
Solar/Wind Harmer
1.373
315737AD1-076 GEN
Solar/Wind Harmer
1.386
316283AC2-100 C
Solar/Wind Harmer
0.686
971157AH1-035 GEN
Solar/Wind Harmer
0.911
315614AA2-178 GEN
Solar/Wind Harmer
0.783
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.858
3146516WINFALL
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.896
316435W1029_GEN3
Solar/Wind Harmer
1.299
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.419
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.891
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151101ELIZAR3
Adder
5.85
3151221GRAVEL6
Adder
4.406
3151171GRAVELC
Adder
0.848
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.339
3148013FISHERV
Solar/Wind Helper
0.13
315616AA1-038_C
Solar/Wind Helper
0.528
944581AF1-123 GEN
Solar/Wind Harmer
20.452
LAGNLTFEXP_LAGN->PJM
CLTF
1.959
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.572
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.107
MECLTFEXP_MEC->PJM
CLTF
0.537
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.437
TVALTFEXP_TVA->PJM
CLTF
0.967
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.612
LGEELTFEXP_LGEE->PJM
CLTF
0.133
WECLTFEXP_WEC->PJM
CLTF
0.061
CPLELTFEXP_CPLE->PJM
CLTF
4.206
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.626

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:175.31 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1455.08
MW Contribution:28.82
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.533
3151911BEARGRDN G1
50/50
4.287
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
18.19
972003AH1-546 GEN
Solar/Wind Harmer
24.898
971377AH1-170 GEN
Solar/Wind Harmer
5.763
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.282
316322AB2-045
Solar/Wind Harmer
1.394
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.86
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
963171AG1-166 GEN
Solar/Wind Harmer
2.905
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
18.606
3143226MDLTHAN
Solar/Wind Harmer
-0.015
962491AG1-098 GEN
Solar/Wind Harmer
9.894
315693AD1-088 GEN
Solar/Wind Harmer
7.12
316237AB2-079_GEN
Solar/Wind Harmer
0.427
3143526WINTERP
Solar/Wind Harmer
-0.065
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.362
972205AH1-687 GEN
50/50
20.91
316303AF2-085
50/50
2.425
971447AH1-217 GEN
Solar/Wind Harmer
15.108
971845AH1-439 GEN
Solar/Wind Harmer
21.634
970285AG2-188 GEN
Solar/Wind Harmer
34.428
270494AE1-108_GEN
Solar/Wind Harmer
9.407
315657AE1-056 GEN
Solar/Wind Harmer
9.233
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
16.612
970681AG2-440 GEN
Solar/Wind Harmer
13.29
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.737
316239AB2-077_GEN
Solar/Wind Harmer
0.427
316238AB2-078_GEN
Solar/Wind Harmer
0.427
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316118AC1-105 GEN
Solar/Wind Harmer
0.741
970831AG2-522 GEN
Solar/Wind Harmer
5.054
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
946281AF1-292 GEN
Solar/Wind Harmer
0.196
971967AH1-528 GEN
Solar/Wind Harmer
16.369
316087AB2-174 GEN
Solar/Wind Harmer
1.222
970865AG2-541 GEN
Solar/Wind Harmer
3.392
3137643SOCKMAN
Solar/Wind Harmer
-0.033
970673AG2-436 GEN
Solar/Wind Harmer
16.777
970673AG2-436 GEN
Solar/Wind Harmer
8.495
315607AA1-063A GEN
Solar/Wind Harmer
0.8
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.588
970535AG2-341 GEN
50/50
2.034
971489AH1-241 GEN
Solar/Wind Harmer
27.358
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.65
970301AG2-198 GEN
Solar/Wind Harmer
12.49
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.631
963191AG1-168 GEN
Solar/Wind Harmer
2.179
971741AH1-377 GEN
Solar/Wind Harmer
26.175
316034AC1-036 C
Solar/Wind Harmer
0.356
970323AG2-213 GEN
Solar/Wind Harmer
9.582
971775AH1-396 GEN
Solar/Wind Harmer
1.365
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.349
3143526WINTERP
Solar/Wind Harmer
-0.065
962561AG1-105 GEN
Solar/Wind Harmer
6.845
939181AE1-148 GEN
Solar/Wind Harmer
6.741
964791AG1-342 GEN
Solar/Wind Harmer
2.511
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.545
970933AG2-581 GEN
Solar/Wind Harmer
9.023
316181AB2-040 GEN
Solar/Wind Harmer
1.184
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.923
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.055
3145783HORNRTN
Solar/Wind Harmer
0.958
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.016
316426AA2-053 GEN
Solar/Wind Harmer
0.809
3144356SAPONY
Solar/Wind Harmer
0.264
316274AC1-208 GEN
Solar/Wind Harmer
0.799
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.235
315742AE1-103 GEN
Solar/Wind Harmer
0.736
970657AG2-426 GEN
Solar/Wind Harmer
2.172
970657AG2-426 GEN
Solar/Wind Harmer
0.454
316222AC1-221 GEN
Solar/Wind Harmer
0.698
316065AD1-022 GEN
Solar/Wind Harmer
3.4
942751AE2-291 GEN
Solar/Wind Harmer
4.316
316263AC1-034 GEN
Solar/Wind Harmer
3.148
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.622
316033AB2-134 GEN
Solar/Wind Harmer
2.144
315697AD1-025 GEN
Solar/Wind Harmer
1.345
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.2
316433W1029_GEN2
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316018AA1-139 ULT2
Solar/Wind Harmer
0.563
316017AA1-139 ULT1
Solar/Wind Harmer
0.531
316339AD2-160 GEN
Solar/Wind Harmer
0.443
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.691
3142956BIRDNECK
Solar/Wind Harmer
0.351
316316AC1-027 C
Solar/Wind Harmer
0.201
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.082
3150701DARBY 4
Adder
4.072
3150681DARBY 2
Adder
4.067
3150671DARBY 1
Adder
4.063
966001AG1-469 GEN
Solar/Wind Helper
0.202
941031AE2-094 GEN
Solar/Wind Harmer
14.78
944011AF1-069 GEN
Solar/Wind Harmer
4.631
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.884
970581AG2-369 GEN
Solar/Wind Harmer
4.201
315814AE2-033 C
Solar/Wind Harmer
7.048
316315AB2-025 C
Solar/Wind Harmer
0.204
965291AG1-394 GEN
Solar/Wind Harmer
0.664
315652AC1-086 GEN
Solar/Wind Harmer
8.34
316123AC1-075 GEN
Solar/Wind Harmer
0.797
970165AG2-112 GEN
Solar/Wind Harmer
0.701
970163AG2-111 GEN
Solar/Wind Harmer
0.669
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.381
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.985
315833AF1-017_GEN
Solar/Wind Harmer
1.293
316349AD2-085 GEN
Solar/Wind Harmer
0.606
316311AC2-079 GEN
Solar/Wind Harmer
3.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.367
315733AD1-074 GEN2
Solar/Wind Harmer
1.367
315735AD1-075 GEN1
Solar/Wind Harmer
0.684
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.68
315816AE2-034 GEN
Solar/Wind Harmer
0.544
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.645
316369SG1_INVT
Solar/Wind Harmer
1.188
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.757
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.895
316321Z2-027
Solar/Wind Harmer
0.178
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
316305AF2-043 C
Solar/Wind Harmer
0.199
313526AB2-022
Solar/Wind Harmer
0.178
316005AA1-067
Solar/Wind Harmer
0.133
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.865
3146406KITTY HAWK
Solar/Wind Harmer
0.005
319010AE1-072 C
Solar/Wind Harmer
1.33
957871AF2-081 GEN
Solar/Wind Harmer
3.284
3152611GOSPORTB
Adder
0.742
3152621GOSPORTC
Adder
0.629
3152601GOSPORTA
Adder
0.581
3151081ELIZAR1
Adder
5.335
3151091ELIZAR2
Adder
5.243
972265AH1-717 GEN
Adder
4.506
3151201GRAVEL4
Adder
4.224
3151191GRAVEL3
Adder
4.17
3151211GRAVEL5
Adder
4.17
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
315687AD1-152 GEN
Solar/Wind Harmer
1.282
971065AG2-659 GEN
Solar/Wind Harmer
5.251
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.904
971795AH1-408 GEN
Solar/Wind Harmer
7.449
3150851SPRUNCC
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.906
960081AF2-299 GEN
Solar/Wind Harmer
0.983
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
970919AG2-571 GEN
Solar/Wind Harmer
2.482
970087AG2-069 GEN
Solar/Wind Harmer
7.326
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.518
940641AE2-051 GEN
Solar/Wind Harmer
6.973
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.551
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
316212AC1-099_GEN
Solar/Wind Harmer
0.635
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.08
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
5.319
970659AG2-427 GEN
Solar/Wind Harmer
3.71
316381AD1-082 GEN
Solar/Wind Harmer
0.639
315722AD1-056 GEN
Solar/Wind Harmer
0.728
970661AG2-428 GEN
Solar/Wind Harmer
7.356
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
970129AG2-093 GEN
Solar/Wind Harmer
1.536
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316458AB2-190 GEN2
Solar/Wind Harmer
0.68
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.303
316359AB2-059 GEN
Solar/Wind Harmer
0.905
316049AB1-081 GEN
Solar/Wind Harmer
0.725
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.951
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
316174AB2-169 GEN
Solar/Wind Harmer
1.029
315800Z1-036_GEN1
Solar/Wind Harmer
1.645
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
971647AH1-324 GEN
Solar/Wind Harmer
3.305
316246AF1-032 C
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.913
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.242
316388AE2-253 GEN
Solar/Wind Harmer
0.443
316375AC2-012 GEN
Solar/Wind Harmer
2.263
3150981CHESPKA
Adder
0.727
3151171GRAVELC
Adder
0.617
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.88
3147666LOUISA
Solar/Wind Helper
0.508
944591AF1-124 GEN
Solar/Wind Harmer
8.419
3151921BEARGRDN G2
50/50
4.287
3144293JTRSVLE
50/50
0.699
970221AG2-151 GEN
Solar/Wind Harmer
28.817
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.807
316258AE1-075 C
Solar/Wind Harmer
0.726
316405AF2-144 C
Solar/Wind Harmer
0.766
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.288
970909AG2-566 GEN
Solar/Wind Harmer
2.372
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.388
963181AG1-167 GEN
Solar/Wind Harmer
2.179
959311AF2-222 GEN
Solar/Wind Harmer
20.632
970257AG2-171 GEN
Solar/Wind Harmer
7.186
315785AD2-033 C
Solar/Wind Harmer
4.155
964241AG1-285 GEN
Solar/Wind Harmer
12.598
316131AB2-060 GEN
Solar/Wind Harmer
1.595
958131AF2-107 GEN
Solar/Wind Harmer
4.893
316478AD1-087 GEN
Solar/Wind Harmer
1.01
316486AD2-202 GEN
Solar/Wind Harmer
0.296
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.904
3150861SPRUNCD
Adder
0.382
971683AH1-343 GEN
Solar/Wind Harmer
3.805
966621AG1-532 GEN
Solar/Wind Harmer
0.177
313506AB2-031 GEN
Solar/Wind Harmer
0.682
970917AG2-570 GEN
Solar/Wind Harmer
19.61
316365GEN2_N
Solar/Wind Harmer
0.518
3156081AA2-088 GEN
Solar/Wind Harmer
2.417
3146263WOODLND
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.773
961681AG1-008 GEN
Solar/Wind Harmer
5.773
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316210AC1-098 GEN
Solar/Wind Harmer
1.142
3146173TUNIS
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
316140AB2-099
Solar/Wind Harmer
0.048
962331AG1-082 GEN
Solar/Wind Harmer
0.898
316317KELFORD C
Solar/Wind Harmer
0.338
3145823KELFORD
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.89
316327AA2-057 GEN
Solar/Wind Harmer
0.714
315813AE1-149 C
Solar/Wind Harmer
4.418
970659AG2-427 GEN
Solar/Wind Harmer
0.658
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
0.4
3145273HOLLAND
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
1.304
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315737AD1-076 GEN
Solar/Wind Harmer
1.285
971157AH1-035 GEN
Solar/Wind Harmer
0.844
970129AG2-093 GEN
Solar/Wind Harmer
3.791
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.725
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.787
961601AG1-000A GEN
Solar/Wind Harmer
2.655
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.827
316320Y1-086
Solar/Wind Harmer
0.387
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.801
961611AG1-000B GEN
Solar/Wind Harmer
1.383
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.404
3151221GRAVEL6
Adder
4.219
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
315616AA1-038_C
Solar/Wind Helper
0.514
LAGNLTFEXP_LAGN->PJM
CLTF
1.764
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.055
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.782
MECLTFEXP_MEC->PJM
CLTF
0.452
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.761
TVALTFEXP_TVA->PJM
CLTF
0.87
SIGELTFEXP_SIGE->PJM
CLTF
0.012
NYPJM->LTFIMP_NY
CLTF
0.577
LGEELTFEXP_LGEE->PJM
CLTF
0.104
WECLTFEXP_WEC->PJM
CLTF
0.046
CPLELTFEXP_CPLE->PJM
CLTF
3.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.641

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:175.31 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1455.08
MW Contribution:28.82
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.588
970535AG2-341 GEN
50/50
2.034
971489AH1-241 GEN
Solar/Wind Harmer
27.358
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.65
970301AG2-198 GEN
Solar/Wind Harmer
12.49
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.631
963191AG1-168 GEN
Solar/Wind Harmer
2.179
971741AH1-377 GEN
Solar/Wind Harmer
26.175
316034AC1-036 C
Solar/Wind Harmer
0.356
970323AG2-213 GEN
Solar/Wind Harmer
9.582
971775AH1-396 GEN
Solar/Wind Harmer
1.365
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.349
3143526WINTERP
Solar/Wind Harmer
-0.065
962561AG1-105 GEN
Solar/Wind Harmer
6.845
939181AE1-148 GEN
Solar/Wind Harmer
6.741
964791AG1-342 GEN
Solar/Wind Harmer
2.511
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.545
970933AG2-581 GEN
Solar/Wind Harmer
9.023
316181AB2-040 GEN
Solar/Wind Harmer
1.184
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.923
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.055
3145783HORNRTN
Solar/Wind Harmer
0.958
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.016
316426AA2-053 GEN
Solar/Wind Harmer
0.809
3144356SAPONY
Solar/Wind Harmer
0.264
316274AC1-208 GEN
Solar/Wind Harmer
0.799
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
972205AH1-687 GEN
50/50
20.91
316303AF2-085
50/50
2.425
971447AH1-217 GEN
Solar/Wind Harmer
15.108
971845AH1-439 GEN
Solar/Wind Harmer
21.634
970285AG2-188 GEN
Solar/Wind Harmer
34.428
270494AE1-108_GEN
Solar/Wind Harmer
9.407
315657AE1-056 GEN
Solar/Wind Harmer
9.233
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
16.612
970681AG2-440 GEN
Solar/Wind Harmer
13.29
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.737
316239AB2-077_GEN
Solar/Wind Harmer
0.427
316238AB2-078_GEN
Solar/Wind Harmer
0.427
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316118AC1-105 GEN
Solar/Wind Harmer
0.741
970831AG2-522 GEN
Solar/Wind Harmer
5.054
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
946281AF1-292 GEN
Solar/Wind Harmer
0.196
971967AH1-528 GEN
Solar/Wind Harmer
16.369
316087AB2-174 GEN
Solar/Wind Harmer
1.222
970865AG2-541 GEN
Solar/Wind Harmer
3.392
3137643SOCKMAN
Solar/Wind Harmer
-0.033
970673AG2-436 GEN
Solar/Wind Harmer
16.777
970673AG2-436 GEN
Solar/Wind Harmer
8.495
315607AA1-063A GEN
Solar/Wind Harmer
0.8
941031AE2-094 GEN
Solar/Wind Harmer
14.78
944011AF1-069 GEN
Solar/Wind Harmer
4.631
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.884
970581AG2-369 GEN
Solar/Wind Harmer
4.201
315814AE2-033 C
Solar/Wind Harmer
7.048
316315AB2-025 C
Solar/Wind Harmer
0.204
965291AG1-394 GEN
Solar/Wind Harmer
0.664
315652AC1-086 GEN
Solar/Wind Harmer
8.34
316123AC1-075 GEN
Solar/Wind Harmer
0.797
970165AG2-112 GEN
Solar/Wind Harmer
0.701
970163AG2-111 GEN
Solar/Wind Harmer
0.669
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3151931BEARGRDN S1
50/50
5.533
3151911BEARGRDN G1
50/50
4.287
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
18.19
972003AH1-546 GEN
Solar/Wind Harmer
24.898
971377AH1-170 GEN
Solar/Wind Harmer
5.763
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.282
316322AB2-045
Solar/Wind Harmer
1.394
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.86
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
963171AG1-166 GEN
Solar/Wind Harmer
2.905
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
18.606
3143226MDLTHAN
Solar/Wind Harmer
-0.015
962491AG1-098 GEN
Solar/Wind Harmer
9.894
315693AD1-088 GEN
Solar/Wind Harmer
7.12
316237AB2-079_GEN
Solar/Wind Harmer
0.427
3143526WINTERP
Solar/Wind Harmer
-0.065
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.362
315687AD1-152 GEN
Solar/Wind Harmer
1.282
971065AG2-659 GEN
Solar/Wind Harmer
5.251
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.904
971795AH1-408 GEN
Solar/Wind Harmer
7.449
3150851SPRUNCC
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.906
960081AF2-299 GEN
Solar/Wind Harmer
0.983
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
970919AG2-571 GEN
Solar/Wind Harmer
2.482
970087AG2-069 GEN
Solar/Wind Harmer
7.326
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.518
940641AE2-051 GEN
Solar/Wind Harmer
6.973
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.551
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
316212AC1-099_GEN
Solar/Wind Harmer
0.635
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.08
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
5.319
970659AG2-427 GEN
Solar/Wind Harmer
3.71
316381AD1-082 GEN
Solar/Wind Harmer
0.639
315722AD1-056 GEN
Solar/Wind Harmer
0.728
970661AG2-428 GEN
Solar/Wind Harmer
7.356
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
970129AG2-093 GEN
Solar/Wind Harmer
1.536
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316458AB2-190 GEN2
Solar/Wind Harmer
0.68
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.303
316359AB2-059 GEN
Solar/Wind Harmer
0.905
316049AB1-081 GEN
Solar/Wind Harmer
0.725
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.951
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
316174AB2-169 GEN
Solar/Wind Harmer
1.029
315800Z1-036_GEN1
Solar/Wind Harmer
1.645
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
971647AH1-324 GEN
Solar/Wind Harmer
3.305
316246AF1-032 C
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.913
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.242
316388AE2-253 GEN
Solar/Wind Harmer
0.443
316375AC2-012 GEN
Solar/Wind Harmer
2.263
3150981CHESPKA
Adder
0.727
3151171GRAVELC
Adder
0.617
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.88
3147666LOUISA
Solar/Wind Helper
0.508
944591AF1-124 GEN
Solar/Wind Harmer
8.419
3151921BEARGRDN G2
50/50
4.287
3144293JTRSVLE
50/50
0.699
970221AG2-151 GEN
Solar/Wind Harmer
28.817
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.807
316258AE1-075 C
Solar/Wind Harmer
0.726
316405AF2-144 C
Solar/Wind Harmer
0.766
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.288
970909AG2-566 GEN
Solar/Wind Harmer
2.372
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.388
963181AG1-167 GEN
Solar/Wind Harmer
2.179
959311AF2-222 GEN
Solar/Wind Harmer
20.632
970257AG2-171 GEN
Solar/Wind Harmer
7.186
315785AD2-033 C
Solar/Wind Harmer
4.155
964241AG1-285 GEN
Solar/Wind Harmer
12.598
316131AB2-060 GEN
Solar/Wind Harmer
1.595
958131AF2-107 GEN
Solar/Wind Harmer
4.893
316478AD1-087 GEN
Solar/Wind Harmer
1.01
316486AD2-202 GEN
Solar/Wind Harmer
0.296
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.904
3150861SPRUNCD
Adder
0.382
971683AH1-343 GEN
Solar/Wind Harmer
3.805
966621AG1-532 GEN
Solar/Wind Harmer
0.177
313506AB2-031 GEN
Solar/Wind Harmer
0.682
970917AG2-570 GEN
Solar/Wind Harmer
19.61
316365GEN2_N
Solar/Wind Harmer
0.518
3156081AA2-088 GEN
Solar/Wind Harmer
2.417
3146263WOODLND
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.773
961681AG1-008 GEN
Solar/Wind Harmer
5.773
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316210AC1-098 GEN
Solar/Wind Harmer
1.142
3146173TUNIS
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
316140AB2-099
Solar/Wind Harmer
0.048
962331AG1-082 GEN
Solar/Wind Harmer
0.898
316317KELFORD C
Solar/Wind Harmer
0.338
3145823KELFORD
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.89
316327AA2-057 GEN
Solar/Wind Harmer
0.714
315813AE1-149 C
Solar/Wind Harmer
4.418
970659AG2-427 GEN
Solar/Wind Harmer
0.658
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
0.4
3145273HOLLAND
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
1.304
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315737AD1-076 GEN
Solar/Wind Harmer
1.285
971157AH1-035 GEN
Solar/Wind Harmer
0.844
970129AG2-093 GEN
Solar/Wind Harmer
3.791
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.725
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.787
961601AG1-000A GEN
Solar/Wind Harmer
2.655
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.827
316320Y1-086
Solar/Wind Harmer
0.387
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.801
961611AG1-000B GEN
Solar/Wind Harmer
1.383
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.404
3151221GRAVEL6
Adder
4.219
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
315616AA1-038_C
Solar/Wind Helper
0.514
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.381
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.985
315833AF1-017_GEN
Solar/Wind Harmer
1.293
316349AD2-085 GEN
Solar/Wind Harmer
0.606
316311AC2-079 GEN
Solar/Wind Harmer
3.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.367
315733AD1-074 GEN2
Solar/Wind Harmer
1.367
315735AD1-075 GEN1
Solar/Wind Harmer
0.684
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.68
315816AE2-034 GEN
Solar/Wind Harmer
0.544
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.645
316369SG1_INVT
Solar/Wind Harmer
1.188
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.757
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.895
316321Z2-027
Solar/Wind Harmer
0.178
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
316305AF2-043 C
Solar/Wind Harmer
0.199
313526AB2-022
Solar/Wind Harmer
0.178
316005AA1-067
Solar/Wind Harmer
0.133
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.865
3146406KITTY HAWK
Solar/Wind Harmer
0.005
319010AE1-072 C
Solar/Wind Harmer
1.33
957871AF2-081 GEN
Solar/Wind Harmer
3.284
3152611GOSPORTB
Adder
0.742
3152621GOSPORTC
Adder
0.629
3152601GOSPORTA
Adder
0.581
3151081ELIZAR1
Adder
5.335
3151091ELIZAR2
Adder
5.243
972265AH1-717 GEN
Adder
4.506
3151201GRAVEL4
Adder
4.224
3151191GRAVEL3
Adder
4.17
3151211GRAVEL5
Adder
4.17
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.235
315742AE1-103 GEN
Solar/Wind Harmer
0.736
970657AG2-426 GEN
Solar/Wind Harmer
2.172
970657AG2-426 GEN
Solar/Wind Harmer
0.454
316222AC1-221 GEN
Solar/Wind Harmer
0.698
316065AD1-022 GEN
Solar/Wind Harmer
3.4
942751AE2-291 GEN
Solar/Wind Harmer
4.316
316263AC1-034 GEN
Solar/Wind Harmer
3.148
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.622
316033AB2-134 GEN
Solar/Wind Harmer
2.144
315697AD1-025 GEN
Solar/Wind Harmer
1.345
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.2
316433W1029_GEN2
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316018AA1-139 ULT2
Solar/Wind Harmer
0.563
316017AA1-139 ULT1
Solar/Wind Harmer
0.531
316339AD2-160 GEN
Solar/Wind Harmer
0.443
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.691
3142956BIRDNECK
Solar/Wind Harmer
0.351
316316AC1-027 C
Solar/Wind Harmer
0.201
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.082
3150701DARBY 4
Adder
4.072
3150681DARBY 2
Adder
4.067
3150671DARBY 1
Adder
4.063
966001AG1-469 GEN
Solar/Wind Helper
0.202
LAGNLTFEXP_LAGN->PJM
CLTF
1.764
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.055
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.782
MECLTFEXP_MEC->PJM
CLTF
0.452
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.761
TVALTFEXP_TVA->PJM
CLTF
0.87
SIGELTFEXP_SIGE->PJM
CLTF
0.012
NYPJM->LTFIMP_NY
CLTF
0.577
LGEELTFEXP_LGEE->PJM
CLTF
0.104
WECLTFEXP_WEC->PJM
CLTF
0.046
CPLELTFEXP_CPLE->PJM
CLTF
3.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.641

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:162.3 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1101.51
MW Contribution:28.5
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
7.21
3151911BEARGRDN G1
50/50
5.587
3144293JTRSVLE
50/50
0.823
3151601KERR 3
50/50
0.202
3151581KERR 1
50/50
0.072
3151531CLOVER1
50/50
2.069
3147043LAWRENC
50/50
0.777
970937AG2-583 GEN
Solar/Wind Harmer
36.866
316336AC2-165 C
Solar/Wind Harmer
0.024
972003AH1-546 GEN
Solar/Wind Harmer
24.522
971377AH1-170 GEN
Solar/Wind Harmer
5.701
3147623JAMES R
Solar/Wind Harmer
1.238
316322AB2-045
Solar/Wind Harmer
0.004
3146776BUCKING
Solar/Wind Harmer
0.188
3146926FARMVIL
Solar/Wind Harmer
0.218
963171AG1-166 GEN
Solar/Wind Harmer
1.299
971563AH1-280 GEN
Solar/Wind Harmer
2.599
970685AG2-442 GEN
Solar/Wind Harmer
16.367
962491AG1-098 GEN
Solar/Wind Harmer
7.651
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
6.098
970401AG2-262 GEN
Solar/Wind Harmer
0.618
957481AF2-042 GEN
Solar/Wind Harmer
24.997
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.611
316129AC1-054 GEN
Solar/Wind Harmer
0.309
316003AC1-222 GEN
Solar/Wind Harmer
0.002
971795AH1-408 GEN
Solar/Wind Harmer
4.899
962751AG1-124 GEN
Solar/Wind Harmer
3.147
960081AF2-299 GEN
Solar/Wind Harmer
0.55
972205AH1-687 GEN
50/50
27.249
3151611KERR 4
50/50
0.202
3151621KERR 5
50/50
0.202
3151631KERR 6
50/50
0.202
3151641KERR 7
50/50
0.202
3151541CLOVER2
50/50
2.059
971447AH1-217 GEN
Solar/Wind Harmer
15.037
971845AH1-439 GEN
Solar/Wind Harmer
20.916
970285AG2-188 GEN
Solar/Wind Harmer
35.131
270494AE1-108_GEN
Solar/Wind Harmer
5.032
315657AE1-056 GEN
Solar/Wind Harmer
8.99
946301AF1-294 GEN
Solar/Wind Harmer
4.808
961791AG1-021 GEN
Solar/Wind Harmer
2.339
970683AG2-441 GEN
Solar/Wind Harmer
14.613
970681AG2-440 GEN
Solar/Wind Harmer
11.691
3144303KENBRDG
Solar/Wind Harmer
0.154
971443AH1-215 GEN
Solar/Wind Harmer
3.209
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.244
3147173SINAI
Solar/Wind Harmer
0.084
3147243WELCO
Solar/Wind Harmer
0.052
970831AG2-522 GEN
Solar/Wind Harmer
3.381
970865AG2-541 GEN
Solar/Wind Harmer
2.545
316123AC1-075 GEN
Solar/Wind Harmer
0.091
970165AG2-112 GEN
Solar/Wind Harmer
0.539
970163AG2-111 GEN
Solar/Wind Harmer
0.514
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
3151921BEARGRDN G2
50/50
5.587
3144293JTRSVLE
50/50
0.823
3151591KERR 2
50/50
0.202
970413AG2-270 GEN
50/50
9.029
966251AG1-494 GEN
50/50
1.716
970221AG2-151 GEN
Solar/Wind Harmer
28.504
3146776BUCKING
Solar/Wind Harmer
0.169
3146926FARMVIL
Solar/Wind Harmer
0.218
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
970909AG2-566 GEN
Solar/Wind Harmer
2.804
3147133PAMPLIN
Solar/Wind Harmer
0.818
971193AH1-056 GEN
Solar/Wind Harmer
15.872
963181AG1-167 GEN
Solar/Wind Harmer
0.975
959311AF2-222 GEN
Solar/Wind Harmer
17.841
970257AG2-171 GEN
Solar/Wind Harmer
6.184
315785AD2-033 C
Solar/Wind Harmer
1.488
958131AF2-107 GEN
Solar/Wind Harmer
4.835
964241AG1-285 GEN
Solar/Wind Harmer
10.382
316131AB2-060 GEN
Solar/Wind Harmer
0.438
316478AD1-087 GEN
Solar/Wind Harmer
0.337
316486AD2-202 GEN
Solar/Wind Harmer
0.099
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.582
3147043LAWRENC
Solar/Wind Harmer
0.049
971683AH1-343 GEN
Solar/Wind Harmer
2.828
3132273ORANGE
Solar/Wind Helper
0.023
3144293JTRSVLE
50/50
0.823
3144293JTRSVLE
50/50
0.693
970535AG2-341 GEN
50/50
2.047
3152661PLYWOOD A
50/50
0.202
971489AH1-241 GEN
Solar/Wind Harmer
28.504
3146776BUCKING
Solar/Wind Harmer
1.881
3146776BUCKING
Solar/Wind Harmer
0.152
315821AE2-092 GEN
Solar/Wind Harmer
0.02
970301AG2-198 GEN
Solar/Wind Harmer
11.214
3147133PAMPLIN
Solar/Wind Harmer
0.26
3147133PAMPLIN
Solar/Wind Harmer
0.208
958211AF2-115 GEN
Solar/Wind Harmer
2.924
963191AG1-168 GEN
Solar/Wind Harmer
0.975
971741AH1-377 GEN
Solar/Wind Harmer
22.982
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.246
971775AH1-396 GEN
Solar/Wind Harmer
0.309
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
5.277
964791AG1-342 GEN
Solar/Wind Harmer
2.024
3146843MT LREL
Solar/Wind Harmer
0.105
3146843MT LREL
Solar/Wind Harmer
0.105
939181AE1-148 GEN
Solar/Wind Harmer
5.007
970099AG2-077 GEN
Solar/Wind Harmer
9.999
970933AG2-581 GEN
Solar/Wind Harmer
5.154
942751AE2-291 GEN
Solar/Wind Harmer
3.374
966001AG1-469 GEN
Solar/Wind Helper
0.159
LAGNLTFEXP_LAGN->PJM
CLTF
1.554
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.084
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.539
MECLTFEXP_MEC->PJM
CLTF
0.508
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.128
TVALTFEXP_TVA->PJM
CLTF
0.776
NYPJM->LTFIMP_NY
CLTF
0.525
LGEELTFEXP_LGEE->PJM
CLTF
0.153
WECLTFEXP_WEC->PJM
CLTF
0.071
CPLELTFEXP_CPLE->PJM
CLTF
2.979
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.201

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P4-2: 202712_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 202712_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:153.09 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1270.66
MW Contribution:37.53
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
5.587
3144293JTRSVLE
50/50
0.823
970221AG2-151 GEN
Solar/Wind Harmer
37.53
3146776BUCKING
Solar/Wind Harmer
-0.019
3146926FARMVIL
Solar/Wind Harmer
-0.024
942461AE2-259 GEN
Solar/Wind Harmer
5.218
970909AG2-566 GEN
Solar/Wind Harmer
2.804
3147133PAMPLIN
Solar/Wind Harmer
-0.092
971193AH1-056 GEN
Solar/Wind Harmer
18.305
963181AG1-167 GEN
Solar/Wind Harmer
2.566
972205AH1-687 GEN
50/50
27.249
971447AH1-217 GEN
Solar/Wind Harmer
19.799
971845AH1-439 GEN
Solar/Wind Harmer
27.54
970285AG2-188 GEN
Solar/Wind Harmer
43.657
270494AE1-108_GEN
Solar/Wind Harmer
12.267
315657AE1-056 GEN
Solar/Wind Harmer
10.983
946301AF1-294 GEN
Solar/Wind Harmer
7.014
961791AG1-021 GEN
Solar/Wind Harmer
3.422
970683AG2-441 GEN
Solar/Wind Harmer
19.241
970681AG2-440 GEN
Solar/Wind Harmer
15.393
3144303KENBRDG
Solar/Wind Harmer
-0.017
971443AH1-215 GEN
Solar/Wind Harmer
4.225
316239AB2-077_GEN
Solar/Wind Harmer
0.446
316238AB2-078_GEN
Solar/Wind Harmer
0.446
316118AC1-105 GEN
Solar/Wind Harmer
0.73
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
970831AG2-522 GEN
Solar/Wind Harmer
4.452
970865AG2-541 GEN
Solar/Wind Harmer
3.351
316123AC1-075 GEN
Solar/Wind Harmer
0.806
970165AG2-112 GEN
Solar/Wind Harmer
0.709
970163AG2-111 GEN
Solar/Wind Harmer
0.677
946281AF1-292 GEN
Solar/Wind Harmer
0.144
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
3144293JTRSVLE
50/50
0.823
3144293JTRSVLE
50/50
0.693
970535AG2-341 GEN
50/50
2.047
971489AH1-241 GEN
Solar/Wind Harmer
35.629
3146776BUCKING
Solar/Wind Harmer
-0.21
3146776BUCKING
Solar/Wind Harmer
-0.017
315821AE2-092 GEN
Solar/Wind Harmer
7.77
970301AG2-198 GEN
Solar/Wind Harmer
14.765
3147133PAMPLIN
Solar/Wind Harmer
-0.029
3147133PAMPLIN
Solar/Wind Harmer
-0.023
958211AF2-115 GEN
Solar/Wind Harmer
4.277
963191AG1-168 GEN
Solar/Wind Harmer
2.566
971741AH1-377 GEN
Solar/Wind Harmer
30.26
316034AC1-036 C
Solar/Wind Harmer
0.404
970323AG2-213 GEN
Solar/Wind Harmer
10.857
971775AH1-396 GEN
Solar/Wind Harmer
1.546
3151931BEARGRDN S1
50/50
7.21
3151911BEARGRDN G1
50/50
5.587
3144293JTRSVLE
50/50
0.823
970937AG2-583 GEN
Solar/Wind Harmer
48.541
316336AC2-165 C
Solar/Wind Harmer
11.736
972003AH1-546 GEN
Solar/Wind Harmer
32.342
971377AH1-170 GEN
Solar/Wind Harmer
7.506
3147623JAMES R
Solar/Wind Harmer
0.929
316322AB2-045
Solar/Wind Harmer
1.778
3146776BUCKING
Solar/Wind Harmer
-0.021
3146926FARMVIL
Solar/Wind Harmer
-0.024
963171AG1-166 GEN
Solar/Wind Harmer
3.422
971563AH1-280 GEN
Solar/Wind Harmer
3.422
970685AG2-442 GEN
Solar/Wind Harmer
21.55
962491AG1-098 GEN
Solar/Wind Harmer
10.074
316237AB2-079_GEN
Solar/Wind Harmer
0.446
315693AD1-088 GEN
Solar/Wind Harmer
7.137
970401AG2-262 GEN
Solar/Wind Harmer
0.773
957481AF2-042 GEN
Solar/Wind Harmer
32.913
315687AD1-152 GEN
Solar/Wind Harmer
1.189
971065AG2-659 GEN
Solar/Wind Harmer
4.755
316129AC1-054 GEN
Solar/Wind Harmer
0.808
3147043LAWRENC
Adder
0.732
316003AC1-222 GEN
Solar/Wind Harmer
0.879
971795AH1-408 GEN
Solar/Wind Harmer
6.192
962751AG1-124 GEN
Solar/Wind Harmer
4.595
960081AF2-299 GEN
Solar/Wind Harmer
0.724
959311AF2-222 GEN
Solar/Wind Harmer
23.538
970257AG2-171 GEN
Solar/Wind Harmer
8.143
315785AD2-033 C
Solar/Wind Harmer
4.66
958131AF2-107 GEN
Solar/Wind Harmer
6.437
964241AG1-285 GEN
Solar/Wind Harmer
13.669
316131AB2-060 GEN
Solar/Wind Harmer
1.687
316478AD1-087 GEN
Solar/Wind Harmer
0.939
316486AD2-202 GEN
Solar/Wind Harmer
0.275
316248AF1-058 C
Solar/Wind Harmer
0.284
960061AF2-297 GEN
Solar/Wind Harmer
4.717
3147043LAWRENC
Solar/Wind Harmer
-0.005
971683AH1-343 GEN
Solar/Wind Harmer
3.724
966621AG1-532 GEN
Solar/Wind Harmer
0.131
3132273ORANGE
Solar/Wind Helper
0.023
313527AB2-043 GEN
Solar/Wind Harmer
2.466
962561AG1-105 GEN
Solar/Wind Harmer
6.948
964791AG1-342 GEN
Solar/Wind Harmer
2.529
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
939181AE1-148 GEN
Solar/Wind Harmer
6.592
970099AG2-077 GEN
Solar/Wind Harmer
13.165
970933AG2-581 GEN
Solar/Wind Harmer
6.786
942751AE2-291 GEN
Solar/Wind Harmer
4.443
966001AG1-469 GEN
Solar/Wind Helper
0.159
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.084
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.539
MECLTFEXP_MEC->PJM
CLTF
0.508
LAGNLTFEXP_LAGN->PJM
CLTF
1.554
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.128
TVALTFEXP_TVA->PJM
CLTF
0.776
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CPLELTFEXP_CPLE->PJM
CLTF
2.979
NYPJM->LTFIMP_NY
CLTF
0.525
LGEELTFEXP_LGEE->PJM
CLTF
0.153
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.201
WECLTFEXP_WEC->PJM
CLTF
0.071

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 39-91_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 39-91_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:119.33 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:990.47
MW Contribution:32.43
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.448
3144293JTRSVLE
50/50
0.697
970221AG2-151 GEN
Solar/Wind Harmer
32.428
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
942461AE2-259 GEN
Solar/Wind Harmer
4.331
316313AB2-026
Solar/Wind Harmer
0.751
316258AE1-075 C
Solar/Wind Harmer
0.676
316405AF2-144 C
Solar/Wind Harmer
0.713
3143336POWHATN
Solar/Wind Harmer
2.809
970909AG2-566 GEN
Solar/Wind Harmer
2.37
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.405
963181AG1-167 GEN
Solar/Wind Harmer
2.173
959311AF2-222 GEN
Solar/Wind Harmer
20.328
970257AG2-171 GEN
Solar/Wind Harmer
7.062
315785AD2-033 C
Solar/Wind Harmer
4.068
958131AF2-107 GEN
Solar/Wind Harmer
5.359
964241AG1-285 GEN
Solar/Wind Harmer
12.184
316131AB2-060 GEN
Solar/Wind Harmer
1.528
316478AD1-087 GEN
Solar/Wind Harmer
0.928
316486AD2-202 GEN
Solar/Wind Harmer
0.272
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.272
960061AF2-297 GEN
Solar/Wind Harmer
4.511
971683AH1-343 GEN
Solar/Wind Harmer
3.497
966621AG1-532 GEN
Solar/Wind Harmer
0.153
313506AB2-031 GEN
Solar/Wind Harmer
0.589
3150861SPRUNCD
Adder
0.274
970917AG2-570 GEN
Solar/Wind Harmer
16.228
316365GEN2_N
Solar/Wind Harmer
0.43
3148013FISHERV
Solar/Wind Helper
0.221
316499AE2-029_GEN
Solar/Wind Helper
0.571
315616AA1-038_C
Solar/Wind Helper
0.608
3144293JTRSVLE
50/50
0.697
3144293JTRSVLE
50/50
0.587
971489AH1-241 GEN
Solar/Wind Harmer
30.786
3146776BUCKING
Solar/Wind Harmer
-0.17
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.481
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.621
963191AG1-168 GEN
Solar/Wind Harmer
2.173
971741AH1-377 GEN
Solar/Wind Harmer
25.942
316034AC1-036 C
Solar/Wind Harmer
0.35
970323AG2-213 GEN
Solar/Wind Harmer
9.416
972205AH1-687 GEN
50/50
21.692
971447AH1-217 GEN
Solar/Wind Harmer
18.622
971845AH1-439 GEN
Solar/Wind Harmer
22.237
270494AE1-108_GEN
Solar/Wind Harmer
10.551
970285AG2-188 GEN
Solar/Wind Harmer
35.335
315657AE1-056 GEN
Solar/Wind Harmer
9.243
946301AF1-294 GEN
Solar/Wind Harmer
5.939
961791AG1-021 GEN
Solar/Wind Harmer
2.897
970683AG2-441 GEN
Solar/Wind Harmer
16.461
970681AG2-440 GEN
Solar/Wind Harmer
13.169
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.67
316239AB2-077_GEN
Solar/Wind Harmer
0.407
316238AB2-078_GEN
Solar/Wind Harmer
0.407
316118AC1-105 GEN
Solar/Wind Harmer
0.689
970831AG2-522 GEN
Solar/Wind Harmer
4.571
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
316233AE1-074 FULL
Solar/Wind Harmer
0.238
971281AH1-106 GEN
Solar/Wind Harmer
1.438
971283AH1-107 GEN
Solar/Wind Harmer
1.438
970865AG2-541 GEN
Solar/Wind Harmer
3.115
946281AF1-292 GEN
Solar/Wind Harmer
0.169
316087AB2-174 GEN
Solar/Wind Harmer
1.055
971967AH1-528 GEN
Solar/Wind Harmer
13.769
3137643SOCKMAN
Solar/Wind Harmer
-0.029
316123AC1-075 GEN
Solar/Wind Harmer
0.731
970165AG2-112 GEN
Solar/Wind Harmer
0.643
970163AG2-111 GEN
Solar/Wind Harmer
0.614
315607AA1-063A GEN
Solar/Wind Harmer
0.681
971285AH1-108 GEN
Adder
0.449
3146043SEABORD
Solar/Wind Harmer
-0.007
970673AG2-436 GEN
Solar/Wind Harmer
13.72
970673AG2-436 GEN
Solar/Wind Harmer
6.947
970085AG2-068 GEN
Solar/Wind Harmer
4.042
970581AG2-369 GEN
Solar/Wind Harmer
3.477
941031AE2-094 GEN
Solar/Wind Harmer
11.972
944011AF1-069 GEN
Solar/Wind Harmer
3.751
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.132
3148013FISHERV
Solar/Wind Helper
0.127
3148463FAIRFLD
Solar/Wind Helper
0.134
3132273ORANGE
Solar/Wind Helper
0.026
3151931BEARGRDN S1
50/50
5.74
3151911BEARGRDN G1
50/50
4.448
3144293JTRSVLE
50/50
0.697
971377AH1-170 GEN
Solar/Wind Harmer
6.486
3147623JAMES R
Solar/Wind Harmer
0.803
972003AH1-546 GEN
Solar/Wind Harmer
25.797
970937AG2-583 GEN
Solar/Wind Harmer
31.587
316322AB2-045
Solar/Wind Harmer
1.434
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.02
316336AC2-165 C
Solar/Wind Harmer
5.623
3143336POWHATN
Solar/Wind Harmer
3.304
963171AG1-166 GEN
Solar/Wind Harmer
2.897
971563AH1-280 GEN
Solar/Wind Harmer
2.897
970685AG2-442 GEN
Solar/Wind Harmer
18.436
962491AG1-098 GEN
Solar/Wind Harmer
9.378
316237AB2-079_GEN
Solar/Wind Harmer
0.407
315693AD1-088 GEN
Solar/Wind Harmer
6.713
970401AG2-262 GEN
Solar/Wind Harmer
0.72
957481AF2-042 GEN
Solar/Wind Harmer
33.181
3143226MDLTHAN
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
1.173
971065AG2-659 GEN
Solar/Wind Harmer
4.785
3147043LAWRENC
Adder
0.762
316129AC1-054 GEN
Solar/Wind Harmer
0.821
971795AH1-408 GEN
Solar/Wind Harmer
6.648
3143526WINTERP
Solar/Wind Harmer
-0.046
316003AC1-222 GEN
Solar/Wind Harmer
0.833
960081AF2-299 GEN
Solar/Wind Harmer
0.851
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.084
3150851SPRUNCC
Adder
0.274
970919AG2-571 GEN
Solar/Wind Harmer
2.054
970087AG2-069 GEN
Solar/Wind Harmer
6.064
316023GEN1_S
Solar/Wind Harmer
0.43
3147983MERCK5
Solar/Wind Helper
0.062
971775AH1-396 GEN
Solar/Wind Harmer
1.341
313527AB2-043 GEN
Solar/Wind Harmer
2.245
962561AG1-105 GEN
Solar/Wind Harmer
6.444
939181AE1-148 GEN
Solar/Wind Harmer
6.287
964791AG1-342 GEN
Solar/Wind Harmer
2.356
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.272
971223AH1-071 GEN
Solar/Wind Harmer
1.326
3143526WINTERP
Solar/Wind Harmer
-0.046
970933AG2-581 GEN
Solar/Wind Harmer
7.828
316181AB2-040 GEN
Solar/Wind Harmer
1.022
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.794
3145593CAROLNA
Solar/Wind Harmer
0.059
3145783HORNRTN
Solar/Wind Harmer
0.823
3145783HORNRTN
Solar/Wind Harmer
0.658
3145783HORNRTN
Solar/Wind Harmer
0.206
3145783HORNRTN
Solar/Wind Harmer
0.082
316426AA2-053 GEN
Solar/Wind Harmer
0.692
972187AH1-678 GEN
Adder
1.699
972185AH1-677 GEN
Adder
3.299
966001AG1-469 GEN
Solar/Wind Helper
0.187
3132123MT JACKSON
Solar/Wind Helper
0.368
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.035
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.087
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.798
MECLTFEXP_MEC->PJM
CLTF
0.142
LAGNLTFEXP_LAGN->PJM
CLTF
1.208
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.305
TVALTFEXP_TVA->PJM
CLTF
0.589
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CPLELTFEXP_CPLE->PJM
CLTF
3.247
NYPJM->LTFIMP_NY
CLTF
0.409
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.539

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P2-2: DOOMS B2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: DOOMS B2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:117.39 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:974.31
MW Contribution:32.4
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.696
3144293JTRSVLE
50/50
0.586
315821AE2-092 GEN
Solar/Wind Harmer
10.863
971489AH1-241 GEN
Solar/Wind Harmer
30.763
3146776BUCKING
Solar/Wind Harmer
-0.17
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.465
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.616
963191AG1-168 GEN
Solar/Wind Harmer
2.17
971741AH1-377 GEN
Solar/Wind Harmer
25.905
316034AC1-036 C
Solar/Wind Harmer
0.349
970323AG2-213 GEN
Solar/Wind Harmer
9.401
971775AH1-396 GEN
Solar/Wind Harmer
1.339
313527AB2-043 GEN
Solar/Wind Harmer
2.24
962561AG1-105 GEN
Solar/Wind Harmer
6.427
939181AE1-148 GEN
Solar/Wind Harmer
6.27
964791AG1-342 GEN
Solar/Wind Harmer
2.35
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.235
971223AH1-071 GEN
Solar/Wind Harmer
1.322
3143526WINTERP
Solar/Wind Harmer
-0.046
970933AG2-581 GEN
Solar/Wind Harmer
7.8
316181AB2-040 GEN
Solar/Wind Harmer
1.018
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.791
3145593CAROLNA
Solar/Wind Harmer
0.058
3145783HORNRTN
Solar/Wind Harmer
0.819
3145783HORNRTN
Solar/Wind Harmer
0.655
3145783HORNRTN
Solar/Wind Harmer
0.205
3145783HORNRTN
Solar/Wind Harmer
0.082
316426AA2-053 GEN
Solar/Wind Harmer
0.689
972187AH1-678 GEN
Adder
1.691
972185AH1-677 GEN
Adder
3.285
966001AG1-469 GEN
Solar/Wind Helper
0.188
3132123MT JACKSON
Solar/Wind Helper
0.367
972205AH1-687 GEN
50/50
21.676
971447AH1-217 GEN
Solar/Wind Harmer
18.608
971845AH1-439 GEN
Solar/Wind Harmer
22.218
270494AE1-108_GEN
Solar/Wind Harmer
10.541
970285AG2-188 GEN
Solar/Wind Harmer
35.303
315657AE1-056 GEN
Solar/Wind Harmer
9.23
946301AF1-294 GEN
Solar/Wind Harmer
5.931
961791AG1-021 GEN
Solar/Wind Harmer
2.893
970683AG2-441 GEN
Solar/Wind Harmer
16.436
970681AG2-440 GEN
Solar/Wind Harmer
13.149
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.664
316239AB2-077_GEN
Solar/Wind Harmer
0.406
316238AB2-078_GEN
Solar/Wind Harmer
0.406
316118AC1-105 GEN
Solar/Wind Harmer
0.687
970831AG2-522 GEN
Solar/Wind Harmer
4.556
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
316233AE1-074 FULL
Solar/Wind Harmer
0.237
971281AH1-106 GEN
Solar/Wind Harmer
1.433
971283AH1-107 GEN
Solar/Wind Harmer
1.433
970865AG2-541 GEN
Solar/Wind Harmer
3.104
946281AF1-292 GEN
Solar/Wind Harmer
0.169
316087AB2-174 GEN
Solar/Wind Harmer
1.051
971967AH1-528 GEN
Solar/Wind Harmer
13.715
3137643SOCKMAN
Solar/Wind Harmer
-0.028
316123AC1-075 GEN
Solar/Wind Harmer
0.728
970165AG2-112 GEN
Solar/Wind Harmer
0.641
970163AG2-111 GEN
Solar/Wind Harmer
0.611
315607AA1-063A GEN
Solar/Wind Harmer
0.678
971285AH1-108 GEN
Adder
0.447
3146043SEABORD
Solar/Wind Harmer
-0.007
970673AG2-436 GEN
Solar/Wind Harmer
13.659
970673AG2-436 GEN
Solar/Wind Harmer
6.916
970085AG2-068 GEN
Solar/Wind Harmer
4.024
970581AG2-369 GEN
Solar/Wind Harmer
3.461
941031AE2-094 GEN
Solar/Wind Harmer
11.918
944011AF1-069 GEN
Solar/Wind Harmer
3.734
3138266HYDRAULIC
Solar/Wind Helper
0.021
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.136
3148013FISHERV
Solar/Wind Helper
0.13
3148463FAIRFLD
Solar/Wind Helper
0.135
3151931BEARGRDN S1
50/50
5.736
3151911BEARGRDN G1
50/50
4.444
3144293JTRSVLE
50/50
0.696
971377AH1-170 GEN
Solar/Wind Harmer
6.481
3147623JAMES R
Solar/Wind Harmer
0.802
972003AH1-546 GEN
Solar/Wind Harmer
25.777
970937AG2-583 GEN
Solar/Wind Harmer
31.56
316322AB2-045
Solar/Wind Harmer
1.433
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.02
316336AC2-165 C
Solar/Wind Harmer
5.617
3143336POWHATN
Solar/Wind Harmer
3.3
963171AG1-166 GEN
Solar/Wind Harmer
2.893
971563AH1-280 GEN
Solar/Wind Harmer
2.893
970685AG2-442 GEN
Solar/Wind Harmer
18.409
962491AG1-098 GEN
Solar/Wind Harmer
9.357
316237AB2-079_GEN
Solar/Wind Harmer
0.406
315693AD1-088 GEN
Solar/Wind Harmer
6.698
970401AG2-262 GEN
Solar/Wind Harmer
0.718
957481AF2-042 GEN
Solar/Wind Harmer
33.088
3143226MDLTHAN
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
1.169
971065AG2-659 GEN
Solar/Wind Harmer
4.77
3147043LAWRENC
Adder
0.76
316129AC1-054 GEN
Solar/Wind Harmer
0.818
971795AH1-408 GEN
Solar/Wind Harmer
6.626
3143526WINTERP
Solar/Wind Harmer
-0.046
316003AC1-222 GEN
Solar/Wind Harmer
0.83
960081AF2-299 GEN
Solar/Wind Harmer
0.847
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.084
3150851SPRUNCC
Adder
0.273
970919AG2-571 GEN
Solar/Wind Harmer
2.045
970087AG2-069 GEN
Solar/Wind Harmer
6.037
316023GEN1_S
Solar/Wind Harmer
0.428
3147983MERCK5
Solar/Wind Helper
0.063
3151921BEARGRDN G2
50/50
4.444
3144293JTRSVLE
50/50
0.696
970221AG2-151 GEN
Solar/Wind Harmer
32.404
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
942461AE2-259 GEN
Solar/Wind Harmer
4.326
316313AB2-026
Solar/Wind Harmer
0.75
316258AE1-075 C
Solar/Wind Harmer
0.675
316405AF2-144 C
Solar/Wind Harmer
0.712
3143336POWHATN
Solar/Wind Harmer
2.805
970909AG2-566 GEN
Solar/Wind Harmer
2.367
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.384
963181AG1-167 GEN
Solar/Wind Harmer
2.17
959311AF2-222 GEN
Solar/Wind Harmer
20.295
970257AG2-171 GEN
Solar/Wind Harmer
7.05
315785AD2-033 C
Solar/Wind Harmer
4.061
958131AF2-107 GEN
Solar/Wind Harmer
5.349
964241AG1-285 GEN
Solar/Wind Harmer
12.16
316131AB2-060 GEN
Solar/Wind Harmer
1.525
316478AD1-087 GEN
Solar/Wind Harmer
0.925
316486AD2-202 GEN
Solar/Wind Harmer
0.271
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.271
960061AF2-297 GEN
Solar/Wind Harmer
4.496
971683AH1-343 GEN
Solar/Wind Harmer
3.484
966621AG1-532 GEN
Solar/Wind Harmer
0.153
313506AB2-031 GEN
Solar/Wind Harmer
0.586
3150861SPRUNCD
Adder
0.273
970917AG2-570 GEN
Solar/Wind Harmer
16.156
316365GEN2_N
Solar/Wind Harmer
0.428
3148013FISHERV
Solar/Wind Helper
0.227
316499AE2-029_GEN
Solar/Wind Helper
0.572
315616AA1-038_C
Solar/Wind Helper
0.611
3132273ORANGE
Solar/Wind Helper
0.026
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.046
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.122
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.731
MECLTFEXP_MEC->PJM
CLTF
0.113
LAGNLTFEXP_LAGN->PJM
CLTF
1.172
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.249
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.571
SIGELTFEXP_SIGE->PJM
CLTF
0.001
CPLELTFEXP_CPLE->PJM
CLTF
3.227
NYPJM->LTFIMP_NY
CLTF
0.42
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.302

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:112.5 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:933.78
MW Contribution:27.74
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.655
3144293JTRSVLE
50/50
0.551
971489AH1-241 GEN
Solar/Wind Harmer
26.337
3146776BUCKING
Solar/Wind Harmer
-0.158
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.386
970301AG2-198 GEN
Solar/Wind Harmer
11.705
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.404
963191AG1-168 GEN
Solar/Wind Harmer
2.042
971741AH1-377 GEN
Solar/Wind Harmer
24.381
316034AC1-036 C
Solar/Wind Harmer
0.331
970323AG2-213 GEN
Solar/Wind Harmer
8.895
971775AH1-396 GEN
Solar/Wind Harmer
1.267
313527AB2-043 GEN
Solar/Wind Harmer
2.141
962561AG1-105 GEN
Solar/Wind Harmer
6.187
972205AH1-687 GEN
50/50
20.143
971447AH1-217 GEN
Solar/Wind Harmer
14.529
971845AH1-439 GEN
Solar/Wind Harmer
20.7
970285AG2-188 GEN
Solar/Wind Harmer
32.906
270494AE1-108_GEN
Solar/Wind Harmer
9.015
315657AE1-056 GEN
Solar/Wind Harmer
8.675
946301AF1-294 GEN
Solar/Wind Harmer
5.582
961791AG1-021 GEN
Solar/Wind Harmer
2.723
970683AG2-441 GEN
Solar/Wind Harmer
15.505
970681AG2-440 GEN
Solar/Wind Harmer
12.404
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.467
316239AB2-077_GEN
Solar/Wind Harmer
0.389
316238AB2-078_GEN
Solar/Wind Harmer
0.389
316118AC1-105 GEN
Solar/Wind Harmer
0.665
970831AG2-522 GEN
Solar/Wind Harmer
4.449
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
316233AE1-074 FULL
Solar/Wind Harmer
0.225
971281AH1-106 GEN
Solar/Wind Harmer
1.359
971283AH1-107 GEN
Solar/Wind Harmer
1.359
946281AF1-292 GEN
Solar/Wind Harmer
0.166
970865AG2-541 GEN
Solar/Wind Harmer
2.988
316087AB2-174 GEN
Solar/Wind Harmer
1.035
971967AH1-528 GEN
Solar/Wind Harmer
13.383
3137643SOCKMAN
Solar/Wind Harmer
-0.028
315607AA1-063A GEN
Solar/Wind Harmer
0.672
3146043SEABORD
Solar/Wind Harmer
-0.007
316123AC1-075 GEN
Solar/Wind Harmer
0.694
970165AG2-112 GEN
Solar/Wind Harmer
0.611
970163AG2-111 GEN
Solar/Wind Harmer
0.583
970085AG2-068 GEN
Solar/Wind Harmer
4
970581AG2-369 GEN
Solar/Wind Harmer
3.44
970673AG2-436 GEN
Solar/Wind Harmer
13.415
970673AG2-436 GEN
Solar/Wind Harmer
6.792
971285AH1-108 GEN
Adder
0.428
3138266HYDRAULIC
Solar/Wind Helper
0.021
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.08
3148013FISHERV
Solar/Wind Helper
0.077
3148463FAIRFLD
Solar/Wind Helper
0.12
3151931BEARGRDN S1
50/50
5.33
3151911BEARGRDN G1
50/50
4.13
3144293JTRSVLE
50/50
0.655
972003AH1-546 GEN
Solar/Wind Harmer
23.962
971377AH1-170 GEN
Solar/Wind Harmer
5.548
3147623JAMES R
Solar/Wind Harmer
0.687
970937AG2-583 GEN
Solar/Wind Harmer
29.352
316322AB2-045
Solar/Wind Harmer
1.334
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.233
3143336POWHATN
Solar/Wind Harmer
3.078
963171AG1-166 GEN
Solar/Wind Harmer
2.723
971563AH1-280 GEN
Solar/Wind Harmer
2.723
970685AG2-442 GEN
Solar/Wind Harmer
17.365
962491AG1-098 GEN
Solar/Wind Harmer
8.919
316237AB2-079_GEN
Solar/Wind Harmer
0.389
315693AD1-088 GEN
Solar/Wind Harmer
6.394
970401AG2-262 GEN
Solar/Wind Harmer
0.692
957481AF2-042 GEN
Solar/Wind Harmer
31.87
3143226MDLTHAN
Solar/Wind Harmer
-0.01
315687AD1-152 GEN
Solar/Wind Harmer
1.137
971065AG2-659 GEN
Solar/Wind Harmer
4.648
3147043LAWRENC
Adder
0.737
316129AC1-054 GEN
Solar/Wind Harmer
0.798
971795AH1-408 GEN
Solar/Wind Harmer
6.453
3143526WINTERP
Solar/Wind Harmer
-0.043
316003AC1-222 GEN
Solar/Wind Harmer
0.805
960081AF2-299 GEN
Solar/Wind Harmer
0.832
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.083
970919AG2-571 GEN
Solar/Wind Harmer
2.03
970087AG2-069 GEN
Solar/Wind Harmer
6
3150851SPRUNCC
Adder
0.261
3147983MERCK5
Solar/Wind Helper
0.055
3151921BEARGRDN G2
50/50
4.13
3144293JTRSVLE
50/50
0.655
970221AG2-151 GEN
Solar/Wind Harmer
27.742
3146776BUCKING
Solar/Wind Harmer
-0.014
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.053
316313AB2-026
Solar/Wind Harmer
0.699
316258AE1-075 C
Solar/Wind Harmer
0.63
316405AF2-144 C
Solar/Wind Harmer
0.664
3143336POWHATN
Solar/Wind Harmer
2.616
970909AG2-566 GEN
Solar/Wind Harmer
2.223
3147133PAMPLIN
Solar/Wind Harmer
-0.072
971193AH1-056 GEN
Solar/Wind Harmer
14.459
963181AG1-167 GEN
Solar/Wind Harmer
2.042
959311AF2-222 GEN
Solar/Wind Harmer
19.185
970257AG2-171 GEN
Solar/Wind Harmer
6.671
315785AD2-033 C
Solar/Wind Harmer
3.847
964241AG1-285 GEN
Solar/Wind Harmer
11.573
316131AB2-060 GEN
Solar/Wind Harmer
1.457
958131AF2-107 GEN
Solar/Wind Harmer
4.54
316478AD1-087 GEN
Solar/Wind Harmer
0.893
316486AD2-202 GEN
Solar/Wind Harmer
0.261
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.264
960061AF2-297 GEN
Solar/Wind Harmer
4.376
971683AH1-343 GEN
Solar/Wind Harmer
3.368
966621AG1-532 GEN
Solar/Wind Harmer
0.15
313506AB2-031 GEN
Solar/Wind Harmer
0.578
970917AG2-570 GEN
Solar/Wind Harmer
16.041
3150861SPRUNCD
Adder
0.261
316499AE2-029_GEN
Solar/Wind Helper
0.505
3148013FISHERV
Solar/Wind Helper
0.133
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.545
939181AE1-148 GEN
Solar/Wind Harmer
6.061
964791AG1-342 GEN
Solar/Wind Harmer
2.266
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
12.748
971223AH1-071 GEN
Solar/Wind Harmer
1.248
3143526WINTERP
Solar/Wind Harmer
-0.043
970933AG2-581 GEN
Solar/Wind Harmer
7.571
316181AB2-040 GEN
Solar/Wind Harmer
1.004
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.784
3145593CAROLNA
Solar/Wind Harmer
0.058
3145783HORNRTN
Solar/Wind Harmer
0.814
3145783HORNRTN
Solar/Wind Harmer
0.651
3145783HORNRTN
Solar/Wind Harmer
0.204
3145783HORNRTN
Solar/Wind Harmer
0.081
316426AA2-053 GEN
Solar/Wind Harmer
0.684
972187AH1-678 GEN
Adder
1.664
972185AH1-677 GEN
Adder
3.229
966001AG1-469 GEN
Solar/Wind Helper
0.189
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.045
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.115
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.309
MECLTFEXP_MEC->PJM
CLTF
0.208
LAGNLTFEXP_LAGN->PJM
CLTF
1.574
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.039
TVALTFEXP_TVA->PJM
CLTF
0.757
SIGELTFEXP_SIGE->PJM
CLTF
0.003
CPLELTFEXP_CPLE->PJM
CLTF
3.638
NYPJM->LTFIMP_NY
CLTF
0.389
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.961

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.58 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:736.92
MW Contribution:21.01
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.314
3151911BEARGRDN G1
50/50
4.118
3144293JTRSVLE
50/50
0.644
3151531CLOVER1
50/50
1.885
3151601KERR 3
50/50
0.18
3151581KERR 1
50/50
0.064
970119AG2-088 GEN
50/50
11.599
3147043LAWRENC
50/50
0.746
3151261ROARAP2
50/50
0.072
972003AH1-546 GEN
Solar/Wind Harmer
18.108
971377AH1-170 GEN
Solar/Wind Harmer
4.203
3147623JAMES R
Solar/Wind Harmer
0.913
970937AG2-583 GEN
Solar/Wind Harmer
22.204
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.14
3146926FARMVIL
Solar/Wind Harmer
0.165
316336AC2-165 C
Solar/Wind Harmer
0.01
3143336POWHATN
Solar/Wind Harmer
4.074
963171AG1-166 GEN
Solar/Wind Harmer
1.017
971563AH1-280 GEN
Solar/Wind Harmer
2.035
970685AG2-442 GEN
Solar/Wind Harmer
12.945
962491AG1-098 GEN
Solar/Wind Harmer
6.577
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
5.296
970401AG2-262 GEN
Solar/Wind Harmer
0.531
957481AF2-042 GEN
Solar/Wind Harmer
23.244
3143226MDLTHAN
Solar/Wind Harmer
0.087
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.352
316129AC1-054 GEN
Solar/Wind Harmer
0.289
971795AH1-408 GEN
Solar/Wind Harmer
4.849
3143526WINTERP
Solar/Wind Harmer
0.377
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.595
3145783HORNRTN
Solar/Wind Harmer
0.057
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.752
972205AH1-687 GEN
50/50
20.083
3151541CLOVER2
50/50
1.876
3151611KERR 4
50/50
0.18
3151621KERR 5
50/50
0.18
3151631KERR 6
50/50
0.18
3151641KERR 7
50/50
0.18
316303AF2-085
50/50
1.546
3151281ROARAP4
50/50
0.07
3151281ROARAP4
50/50
0.066
971447AH1-217 GEN
Solar/Wind Harmer
11.004
971845AH1-439 GEN
Solar/Wind Harmer
15.632
970285AG2-188 GEN
Solar/Wind Harmer
26.316
270494AE1-108_GEN
Solar/Wind Harmer
3.693
315657AE1-056 GEN
Solar/Wind Harmer
6.997
946301AF1-294 GEN
Solar/Wind Harmer
3.764
961791AG1-021 GEN
Solar/Wind Harmer
1.831
970683AG2-441 GEN
Solar/Wind Harmer
11.558
970681AG2-440 GEN
Solar/Wind Harmer
9.247
3144303KENBRDG
Solar/Wind Harmer
0.124
971443AH1-215 GEN
Solar/Wind Harmer
2.576
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.212
970831AG2-522 GEN
Solar/Wind Harmer
3.201
3147173SINAI
Solar/Wind Harmer
0.074
3147243WELCO
Solar/Wind Harmer
0.046
316233AE1-074 FULL
Solar/Wind Harmer
0.058
971281AH1-106 GEN
Solar/Wind Harmer
1.006
971283AH1-107 GEN
Solar/Wind Harmer
1.006
970865AG2-541 GEN
Solar/Wind Harmer
2.17
316087AB2-174 GEN
Solar/Wind Harmer
0.002
971967AH1-528 GEN
Solar/Wind Harmer
9.597
3137643SOCKMAN
Solar/Wind Harmer
0.235
3138266HYDRAULIC
Solar/Wind Helper
0.021
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.08
3148013FISHERV
Solar/Wind Helper
0.077
3148463FAIRFLD
Solar/Wind Helper
0.119
3151921BEARGRDN G2
50/50
4.118
3144293JTRSVLE
50/50
0.644
970413AG2-270 GEN
50/50
8.224
3151591KERR 2
50/50
0.18
966251AG1-494 GEN
50/50
1.173
3151261ROARAP2
50/50
0.07
970221AG2-151 GEN
Solar/Wind Harmer
21.013
3146776BUCKING
Solar/Wind Harmer
0.126
3146926FARMVIL
Solar/Wind Harmer
0.165
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.144
316258AE1-075 C
Solar/Wind Harmer
0.173
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.463
970909AG2-566 GEN
Solar/Wind Harmer
2.192
3147133PAMPLIN
Solar/Wind Harmer
0.637
971193AH1-056 GEN
Solar/Wind Harmer
12.353
963181AG1-167 GEN
Solar/Wind Harmer
0.763
959311AF2-222 GEN
Solar/Wind Harmer
14.242
970257AG2-171 GEN
Solar/Wind Harmer
4.957
315785AD2-033 C
Solar/Wind Harmer
1.2
964241AG1-285 GEN
Solar/Wind Harmer
8.548
958131AF2-107 GEN
Solar/Wind Harmer
3.44
316131AB2-060 GEN
Solar/Wind Harmer
0.366
316478AD1-087 GEN
Solar/Wind Harmer
0.307
316486AD2-202 GEN
Solar/Wind Harmer
0.09
3147043LAWRENC
Solar/Wind Harmer
0.047
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.155
971683AH1-343 GEN
Solar/Wind Harmer
2.44
313506AB2-031 GEN
Solar/Wind Harmer
0.186
316499AE2-029_GEN
Solar/Wind Helper
0.505
3148013FISHERV
Solar/Wind Helper
0.133
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.54
3144293JTRSVLE
50/50
0.644
3144293JTRSVLE
50/50
0.543
970535AG2-341 GEN
50/50
1.768
3152661PLYWOOD A
50/50
0.177
971489AH1-241 GEN
Solar/Wind Harmer
21.013
3146776BUCKING
Solar/Wind Harmer
1.404
3146776BUCKING
Solar/Wind Harmer
0.114
315821AE2-092 GEN
Solar/Wind Harmer
0.014
970301AG2-198 GEN
Solar/Wind Harmer
8.767
3147133PAMPLIN
Solar/Wind Harmer
0.203
3147133PAMPLIN
Solar/Wind Harmer
0.162
958211AF2-115 GEN
Solar/Wind Harmer
2.289
963191AG1-168 GEN
Solar/Wind Harmer
0.763
971741AH1-377 GEN
Solar/Wind Harmer
18.217
316034AC1-036 C
Solar/Wind Harmer
0.011
970323AG2-213 GEN
Solar/Wind Harmer
6.61
971775AH1-396 GEN
Solar/Wind Harmer
0.248
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
4.515
939181AE1-148 GEN
Solar/Wind Harmer
4.407
964791AG1-342 GEN
Solar/Wind Harmer
1.738
3146843MT LREL
Solar/Wind Harmer
0.09
3146843MT LREL
Solar/Wind Harmer
0.09
970099AG2-077 GEN
Solar/Wind Harmer
9.298
971223AH1-071 GEN
Solar/Wind Harmer
0.928
3143526WINTERP
Solar/Wind Harmer
0.377
970933AG2-581 GEN
Solar/Wind Harmer
5.476
316181AB2-040 GEN
Solar/Wind Harmer
0.087
3145593CAROLNA
Solar/Wind Harmer
0.058
3145593CAROLNA
Solar/Wind Harmer
0.058
966811AG1-552 GEN
Solar/Wind Harmer
0.627
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.01
3145783HORNRTN
Solar/Wind Harmer
0.808
3145783HORNRTN
Solar/Wind Harmer
0.253
3145783HORNRTN
Solar/Wind Harmer
0.101
966001AG1-469 GEN
Solar/Wind Helper
0.19
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.029
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.072
LAGNLTFEXP_LAGN->PJM
CLTF
1.122
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.673
MECLTFEXP_MEC->PJM
CLTF
0.138
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.815
TVALTFEXP_TVA->PJM
CLTF
0.547
SIGELTFEXP_SIGE->PJM
CLTF
0.002
NYPJM->LTFIMP_NY
CLTF
0.391
CPLELTFEXP_CPLE->PJM
CLTF
2.992
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.238

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2066-282_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2066-282_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.52 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:900.75
MW Contribution:28.17
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.192
3144293JTRSVLE
50/50
0.653
970221AG2-151 GEN
Solar/Wind Harmer
28.166
3146776BUCKING
Solar/Wind Harmer
-0.014
3146926FARMVIL
Solar/Wind Harmer
-0.019
316313AB2-026
Solar/Wind Harmer
0.752
316258AE1-075 C
Solar/Wind Harmer
0.677
316405AF2-144 C
Solar/Wind Harmer
0.714
3143336POWHATN
Solar/Wind Harmer
2.812
942461AE2-259 GEN
Solar/Wind Harmer
4.067
970909AG2-566 GEN
Solar/Wind Harmer
2.224
3147133PAMPLIN
Solar/Wind Harmer
-0.072
971193AH1-056 GEN
Solar/Wind Harmer
14.446
963181AG1-167 GEN
Solar/Wind Harmer
2.036
959311AF2-222 GEN
Solar/Wind Harmer
19.01
970257AG2-171 GEN
Solar/Wind Harmer
6.601
315785AD2-033 C
Solar/Wind Harmer
3.8
964241AG1-285 GEN
Solar/Wind Harmer
11.356
958131AF2-107 GEN
Solar/Wind Harmer
4.67
316131AB2-060 GEN
Solar/Wind Harmer
1.422
316478AD1-087 GEN
Solar/Wind Harmer
0.862
316486AD2-202 GEN
Solar/Wind Harmer
0.252
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.252
960061AF2-297 GEN
Solar/Wind Harmer
4.181
971683AH1-343 GEN
Solar/Wind Harmer
3.236
966621AG1-532 GEN
Solar/Wind Harmer
0.138
313506AB2-031 GEN
Solar/Wind Harmer
0.528
316499AE2-029_GEN
Solar/Wind Helper
0.5
3148013FISHERV
Solar/Wind Helper
0.13
3151931BEARGRDN S1
50/50
5.41
3151911BEARGRDN G1
50/50
4.192
3144293JTRSVLE
50/50
0.653
970119AG2-088 GEN
50/50
15.082
972003AH1-546 GEN
Solar/Wind Harmer
24.312
971377AH1-170 GEN
Solar/Wind Harmer
5.633
3147623JAMES R
Solar/Wind Harmer
0.697
970937AG2-583 GEN
Solar/Wind Harmer
30.216
316322AB2-045
Solar/Wind Harmer
1.35
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.534
3146926FARMVIL
Solar/Wind Harmer
-0.019
3143336POWHATN
Solar/Wind Harmer
3.308
963171AG1-166 GEN
Solar/Wind Harmer
2.715
971563AH1-280 GEN
Solar/Wind Harmer
2.715
970685AG2-442 GEN
Solar/Wind Harmer
17.259
962491AG1-098 GEN
Solar/Wind Harmer
8.747
3143226MDLTHAN
Solar/Wind Harmer
-0.013
316237AB2-079_GEN
Solar/Wind Harmer
0.378
315693AD1-088 GEN
Solar/Wind Harmer
6.258
970401AG2-262 GEN
Solar/Wind Harmer
0.669
957481AF2-042 GEN
Solar/Wind Harmer
30.813
315687AD1-152 GEN
Solar/Wind Harmer
1.088
971065AG2-659 GEN
Solar/Wind Harmer
4.397
3147043LAWRENC
Adder
0.694
316129AC1-054 GEN
Solar/Wind Harmer
0.753
971795AH1-408 GEN
Solar/Wind Harmer
6.032
316003AC1-222 GEN
Solar/Wind Harmer
0.772
960081AF2-299 GEN
Solar/Wind Harmer
0.762
3147983MERCK5
Solar/Wind Helper
0.055
972205AH1-687 GEN
50/50
20.447
316303AF2-085
50/50
2.011
971447AH1-217 GEN
Solar/Wind Harmer
14.757
971845AH1-439 GEN
Solar/Wind Harmer
20.937
970285AG2-188 GEN
Solar/Wind Harmer
33.263
270494AE1-108_GEN
Solar/Wind Harmer
9.168
315657AE1-056 GEN
Solar/Wind Harmer
8.668
946301AF1-294 GEN
Solar/Wind Harmer
5.566
961791AG1-021 GEN
Solar/Wind Harmer
2.715
970683AG2-441 GEN
Solar/Wind Harmer
15.41
970681AG2-440 GEN
Solar/Wind Harmer
12.328
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.43
316239AB2-077_GEN
Solar/Wind Harmer
0.378
316238AB2-078_GEN
Solar/Wind Harmer
0.378
316118AC1-105 GEN
Solar/Wind Harmer
0.639
970831AG2-522 GEN
Solar/Wind Harmer
4.187
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
970865AG2-541 GEN
Solar/Wind Harmer
2.88
946281AF1-292 GEN
Solar/Wind Harmer
0.152
971967AH1-528 GEN
Solar/Wind Harmer
12.673
316087AB2-174 GEN
Solar/Wind Harmer
0.946
3137643SOCKMAN
Solar/Wind Harmer
-0.026
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.118
3144293JTRSVLE
50/50
0.653
3144293JTRSVLE
50/50
0.55
971489AH1-241 GEN
Solar/Wind Harmer
26.74
3146776BUCKING
Solar/Wind Harmer
-0.16
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.489
970301AG2-198 GEN
Solar/Wind Harmer
11.714
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.394
963191AG1-168 GEN
Solar/Wind Harmer
2.036
971741AH1-377 GEN
Solar/Wind Harmer
24.324
316034AC1-036 C
Solar/Wind Harmer
0.327
970323AG2-213 GEN
Solar/Wind Harmer
8.802
971775AH1-396 GEN
Solar/Wind Harmer
1.253
313527AB2-043 GEN
Solar/Wind Harmer
2.088
971223AH1-071 GEN
Solar/Wind Harmer
1.589
962561AG1-105 GEN
Solar/Wind Harmer
5.986
939181AE1-148 GEN
Solar/Wind Harmer
5.822
964791AG1-342 GEN
Solar/Wind Harmer
2.188
3146843MT LREL
Solar/Wind Harmer
-0.01
3146843MT LREL
Solar/Wind Harmer
-0.01
970099AG2-077 GEN
Solar/Wind Harmer
12.325
970933AG2-581 GEN
Solar/Wind Harmer
7.23
316181AB2-040 GEN
Solar/Wind Harmer
0.916
3145593CAROLNA
Solar/Wind Harmer
-0.006
3145593CAROLNA
Solar/Wind Harmer
-0.006
966811AG1-552 GEN
Solar/Wind Harmer
0.712
3145593CAROLNA
Solar/Wind Harmer
0.053
966001AG1-469 GEN
Solar/Wind Helper
0.187
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.535
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.02
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.044
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.714
MECLTFEXP_MEC->PJM
CLTF
0.159
LAGNLTFEXP_LAGN->PJM
CLTF
1.141
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.807
TVALTFEXP_TVA->PJM
CLTF
0.557
SIGELTFEXP_SIGE->PJM
CLTF
0.003
CPLELTFEXP_CPLE->PJM
CLTF
2.977
NYPJM->LTFIMP_NY
CLTF
0.385
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.39

Details for 6GERMANNA-6CIRRUS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2304_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6GERMANNA-6CIRRUS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2304_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.47 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1293.88
MW Contribution:3.93
Bus #Bus NameTypeMW Contribution
3151741LOISA C
50/50
1.633
3151751LOISA D
50/50
29.856
3151791S ANNAG2
50/50
1.517
3151781S ANNAS1
50/50
0.779
3151931BEARGRDN S1
50/50
0.911
3151911BEARGRDN G1
50/50
0.706
315683AE1-153 C
Solar/Wind Harmer
52.577
316192AB2-158 GEN
Solar/Wind Harmer
2.449
316254AC1-120 GEN1
Solar/Wind Harmer
0.201
971377AH1-170 GEN
Solar/Wind Harmer
0.786
3147623JAMES R
Solar/Wind Harmer
0.171
972003AH1-546 GEN
Solar/Wind Harmer
3.107
970937AG2-583 GEN
Solar/Wind Harmer
3.763
316322AB2-045
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.024
972183AH1-676 GEN
50/50
491.529
3151761LOISA E
50/50
60.868
3151771S ANNAG1
50/50
1.517
3151801S ANNAS2
50/50
0.779
3151921BEARGRDN G2
50/50
0.706
3132273ORANGE
Solar/Wind Harmer
0.054
316170AC1-121 GEN2
Solar/Wind Harmer
0.101
970221AG2-151 GEN
Solar/Wind Harmer
3.929
3148013FISHERV
Solar/Wind Harmer
0.066
3146776BUCKING
Solar/Wind Harmer
0.022
3151731LOISA B
50/50
29.856
3151721LOISA A
50/50
29.702
966001AG1-469 GEN
Solar/Wind Harmer
0.231
971489AH1-241 GEN
Solar/Wind Harmer
3.929
315821AE2-092 GEN
Solar/Wind Harmer
0.004
315651AD1-115 GEN
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.242
3146776BUCKING
Solar/Wind Harmer
0.02
972205AH1-687 GEN
50/50
3.443
3147346CASHSCORNER
Solar/Wind Harmer
0.945
3138266HYDRAULIC
Solar/Wind Harmer
0.006
3138266HYDRAULIC
Solar/Wind Harmer
0.004
971447AH1-217 GEN
Solar/Wind Harmer
2.235
316164AC1-076 GEN
Solar/Wind Harmer
0.1
3148133STUARTS
Solar/Wind Harmer
0.04
3148013FISHERV
Solar/Wind Harmer
0.038
270494AE1-108_GEN
Solar/Wind Harmer
0.739
971845AH1-439 GEN
Solar/Wind Harmer
2.694
970285AG2-188 GEN
Solar/Wind Harmer
4.539
LAGNLTFEXP_LAGN->PJM
CLTF
1.34
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.412
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.486
MECLTFEXP_MEC->PJM
CLTF
0.864
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.634
TVALTFEXP_TVA->PJM
CLTF
0.692
SIGELTFEXP_SIGE->PJM
CLTF
0.028
NYPJM->LTFIMP_NY
CLTF
0.531
LGEELTFEXP_LGEE->PJM
CLTF
0.36
WECLTFEXP_WEC->PJM
CLTF
0.18
CPLELTFEXP_CPLE->PJM
CLTF
0.975
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.999

Details for 6GERMANNA-6CIRRUS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2202_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6GERMANNA-6CIRRUS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2202_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:129.23 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1271.87
MW Contribution:3.94
Bus #Bus NameTypeMW Contribution
3151771S ANNAG1
50/50
1.517
3151801S ANNAS2
50/50
0.78
972183AH1-676 GEN
50/50
491.693
3151761LOISA E
50/50
60.888
3151921BEARGRDN G2
50/50
0.707
3132273ORANGE
Solar/Wind Harmer
0.054
316170AC1-121 GEN2
Solar/Wind Harmer
0.101
970221AG2-151 GEN
Solar/Wind Harmer
3.937
3148013FISHERV
Solar/Wind Harmer
0.066
3146776BUCKING
Solar/Wind Harmer
0.022
972205AH1-687 GEN
50/50
3.45
3147346CASHSCORNER
Solar/Wind Harmer
0.945
3138266HYDRAULIC
Solar/Wind Harmer
0.006
3138266HYDRAULIC
Solar/Wind Harmer
0.004
971447AH1-217 GEN
Solar/Wind Harmer
2.24
316164AC1-076 GEN
Solar/Wind Harmer
0.1
3148133STUARTS
Solar/Wind Harmer
0.04
3148013FISHERV
Solar/Wind Harmer
0.038
270494AE1-108_GEN
Solar/Wind Harmer
0.741
971845AH1-439 GEN
Solar/Wind Harmer
2.7
970285AG2-188 GEN
Solar/Wind Harmer
4.55
3151741LOISA C
50/50
1.633
3151791S ANNAG2
50/50
1.517
3151781S ANNAS1
50/50
0.78
3151751LOISA D
50/50
29.866
3151931BEARGRDN S1
50/50
0.913
3151911BEARGRDN G1
50/50
0.707
315683AE1-153 C
Solar/Wind Harmer
52.588
316254AC1-120 GEN1
Solar/Wind Harmer
0.201
971377AH1-170 GEN
Solar/Wind Harmer
0.787
3147623JAMES R
Solar/Wind Harmer
0.171
972003AH1-546 GEN
Solar/Wind Harmer
3.113
970937AG2-583 GEN
Solar/Wind Harmer
3.772
316322AB2-045
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.024
3151731LOISA B
50/50
29.866
3151721LOISA A
50/50
29.712
966001AG1-469 GEN
Solar/Wind Harmer
0.231
971489AH1-241 GEN
Solar/Wind Harmer
3.937
315821AE2-092 GEN
Solar/Wind Harmer
0.004
315651AD1-115 GEN
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.242
3146776BUCKING
Solar/Wind Harmer
0.02
LAGNLTFEXP_LAGN->PJM
CLTF
1.362
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.574
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.529
MECLTFEXP_MEC->PJM
CLTF
0.883
SIGELTFEXP_SIGE->PJM
CLTF
0.028
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.667
TVALTFEXP_TVA->PJM
CLTF
0.704
NYPJM->LTFIMP_NY
CLTF
0.524
LGEELTFEXP_LGEE->PJM
CLTF
0.368
WECLTFEXP_WEC->PJM
CLTF
0.184
CPLELTFEXP_CPLE->PJM
CLTF
0.987
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.149

Details for 6GERMANNA-6CIRRUS 230.0 kV Ckt 1 line l/o DVP_P4-2: 220232_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6GERMANNA-6CIRRUS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 220232_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.97 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1299.9
MW Contribution:5.18
Bus #Bus NameTypeMW Contribution
3151731LOISA B
50/50
29.866
3151721LOISA A
50/50
29.712
966001AG1-469 GEN
Solar/Wind Harmer
0.841
971489AH1-241 GEN
Solar/Wind Harmer
4.921
315821AE2-092 GEN
Solar/Wind Harmer
1.668
315651AD1-115 GEN
Solar/Wind Harmer
3.247
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
3151741LOISA C
50/50
1.633
3151791S ANNAG2
50/50
1.517
3151781S ANNAS1
50/50
0.78
3151751LOISA D
50/50
29.866
315683AE1-153 C
Solar/Wind Harmer
69.241
316254AC1-120 GEN1
Solar/Wind Harmer
0.856
971377AH1-170 GEN
Solar/Wind Harmer
1.037
3147623JAMES R
Solar/Wind Harmer
0.128
972003AH1-546 GEN
Solar/Wind Harmer
4.105
970937AG2-583 GEN
Solar/Wind Harmer
4.966
316322AB2-045
Solar/Wind Harmer
0.229
3146776BUCKING
Solar/Wind Harmer
-0.003
3151771S ANNAG1
50/50
1.517
3151801S ANNAS2
50/50
0.78
972183AH1-676 GEN
50/50
491.693
3151761LOISA E
50/50
60.888
3132273ORANGE
Solar/Wind Harmer
-0.006
316170AC1-121 GEN2
Solar/Wind Harmer
0.285
970221AG2-151 GEN
Solar/Wind Harmer
5.183
3148013FISHERV
Solar/Wind Harmer
-0.007
3146776BUCKING
Solar/Wind Harmer
-0.002
3147346CASHSCORNER
Solar/Wind Harmer
0.709
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
0
972205AH1-687 GEN
Adder
3.251
971447AH1-217 GEN
Solar/Wind Harmer
2.949
316164AC1-076 GEN
Solar/Wind Harmer
0.674
3148133STUARTS
Solar/Wind Harmer
-0.004
3148013FISHERV
Solar/Wind Harmer
-0.004
270494AE1-108_GEN
Solar/Wind Harmer
1.806
971845AH1-439 GEN
Solar/Wind Harmer
3.555
970285AG2-188 GEN
Solar/Wind Harmer
5.655
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.574
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.529
MECLTFEXP_MEC->PJM
CLTF
0.883
LAGNLTFEXP_LAGN->PJM
CLTF
1.362
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.667
TVALTFEXP_TVA->PJM
CLTF
0.704
SIGELTFEXP_SIGE->PJM
CLTF
0.028
CPLELTFEXP_CPLE->PJM
CLTF
0.987
NYPJM->LTFIMP_NY
CLTF
0.524
LGEELTFEXP_LGEE->PJM
CLTF
0.368
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.149
WECLTFEXP_WEC->PJM
CLTF
0.184

Details for 6GERMANNA-6CIRRUS 230.0 kV Ckt 1 line l/o DVP_P4-2: 2304T2202_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6GERMANNA-6CIRRUS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2304T2202_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.86 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1298.62
MW Contribution:5.18
Bus #Bus NameTypeMW Contribution
3151741LOISA C
50/50
1.633
3151791S ANNAG2
50/50
1.517
3151781S ANNAS1
50/50
0.78
3151751LOISA D
50/50
29.866
315683AE1-153 C
Solar/Wind Harmer
69.241
316254AC1-120 GEN1
Solar/Wind Harmer
0.856
971377AH1-170 GEN
Solar/Wind Harmer
1.037
3147623JAMES R
Solar/Wind Harmer
0.128
972003AH1-546 GEN
Solar/Wind Harmer
4.105
970937AG2-583 GEN
Solar/Wind Harmer
4.966
316322AB2-045
Solar/Wind Harmer
0.229
3146776BUCKING
Solar/Wind Harmer
-0.003
3147346CASHSCORNER
Solar/Wind Harmer
0.709
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
0
972205AH1-687 GEN
Adder
3.251
971447AH1-217 GEN
Solar/Wind Harmer
2.949
316164AC1-076 GEN
Solar/Wind Harmer
0.674
3148133STUARTS
Solar/Wind Harmer
-0.004
3148013FISHERV
Solar/Wind Harmer
-0.004
270494AE1-108_GEN
Solar/Wind Harmer
1.806
971845AH1-439 GEN
Solar/Wind Harmer
3.555
970285AG2-188 GEN
Solar/Wind Harmer
5.654
3151731LOISA B
50/50
29.866
3151721LOISA A
50/50
29.712
966001AG1-469 GEN
Solar/Wind Harmer
0.841
971489AH1-241 GEN
Solar/Wind Harmer
4.921
315821AE2-092 GEN
Solar/Wind Harmer
1.668
315651AD1-115 GEN
Solar/Wind Harmer
3.247
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
3151771S ANNAG1
50/50
1.517
3151801S ANNAS2
50/50
0.78
972183AH1-676 GEN
50/50
491.688
3151761LOISA E
50/50
60.888
3132273ORANGE
Solar/Wind Harmer
-0.006
316170AC1-121 GEN2
Solar/Wind Harmer
0.285
970221AG2-151 GEN
Solar/Wind Harmer
5.183
3148013FISHERV
Solar/Wind Harmer
-0.007
3146776BUCKING
Solar/Wind Harmer
-0.002
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.569
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.527
MECLTFEXP_MEC->PJM
CLTF
0.882
LAGNLTFEXP_LAGN->PJM
CLTF
1.361
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.666
TVALTFEXP_TVA->PJM
CLTF
0.703
SIGELTFEXP_SIGE->PJM
CLTF
0.028
CPLELTFEXP_CPLE->PJM
CLTF
0.987
NYPJM->LTFIMP_NY
CLTF
0.524
LGEELTFEXP_LGEE->PJM
CLTF
0.368
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.144
WECLTFEXP_WEC->PJM
CLTF
0.184

Details for 6GERMANNA-6CIRRUS 230.0 kV Ckt 1 line l/o DVP_P4-2: G2T2202_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6GERMANNA-6CIRRUS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: G2T2202_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.49 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1258.1
MW Contribution:5.2
Bus #Bus NameTypeMW Contribution
3151741LOISA C
50/50
1.634
3151781S ANNAS1
50/50
0.78
3151751LOISA D
50/50
29.884
315683AE1-153 C
Solar/Wind Harmer
69.269
316254AC1-120 GEN1
Solar/Wind Harmer
0.858
971377AH1-170 GEN
Solar/Wind Harmer
1.04
3147623JAMES R
Solar/Wind Harmer
0.129
972003AH1-546 GEN
Solar/Wind Harmer
4.12
970937AG2-583 GEN
Solar/Wind Harmer
4.988
316322AB2-045
Solar/Wind Harmer
0.23
3146776BUCKING
Solar/Wind Harmer
-0.003
3147346CASHSCORNER
Solar/Wind Harmer
0.709
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
0
972205AH1-687 GEN
Adder
3.262
971447AH1-217 GEN
Solar/Wind Harmer
2.96
316164AC1-076 GEN
Solar/Wind Harmer
0.676
3148133STUARTS
Solar/Wind Harmer
-0.004
3148013FISHERV
Solar/Wind Harmer
-0.004
270494AE1-108_GEN
Solar/Wind Harmer
1.814
971845AH1-439 GEN
Solar/Wind Harmer
3.571
970285AG2-188 GEN
Solar/Wind Harmer
5.681
3151731LOISA B
50/50
29.884
3151721LOISA A
50/50
29.73
966001AG1-469 GEN
Solar/Wind Harmer
0.842
971489AH1-241 GEN
Solar/Wind Harmer
4.939
315821AE2-092 GEN
Solar/Wind Harmer
1.674
315651AD1-115 GEN
Solar/Wind Harmer
3.261
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
3151771S ANNAG1
50/50
1.518
972183AH1-676 GEN
50/50
491.994
3151761LOISA E
50/50
60.926
3132273ORANGE
Solar/Wind Harmer
-0.006
316170AC1-121 GEN2
Solar/Wind Harmer
0.286
970221AG2-151 GEN
Solar/Wind Harmer
5.202
3148013FISHERV
Solar/Wind Harmer
-0.007
3146776BUCKING
Solar/Wind Harmer
-0.002
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.87
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.606
MECLTFEXP_MEC->PJM
CLTF
0.917
LAGNLTFEXP_LAGN->PJM
CLTF
1.403
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.729
TVALTFEXP_TVA->PJM
CLTF
0.724
SIGELTFEXP_SIGE->PJM
CLTF
0.029
CPLELTFEXP_CPLE->PJM
CLTF
1.009
NYPJM->LTFIMP_NY
CLTF
0.511
LGEELTFEXP_LGEE->PJM
CLTF
0.382
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.423
WECLTFEXP_WEC->PJM
CLTF
0.192

Details for 6GERMANNA-6CIRRUS 230.0 kV Ckt 1 line l/o DVP_P4-2: H3T255_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6GERMANNA-6CIRRUS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H3T255_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.59 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1223.18
MW Contribution:5.19
Bus #Bus NameTypeMW Contribution
3147346CASHSCORNER
Solar/Wind Harmer
0.709
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
0
972205AH1-687 GEN
Adder
3.253
971447AH1-217 GEN
Solar/Wind Harmer
2.951
316164AC1-076 GEN
Solar/Wind Harmer
0.675
3148133STUARTS
Solar/Wind Harmer
-0.004
3148013FISHERV
Solar/Wind Harmer
-0.004
270494AE1-108_GEN
Solar/Wind Harmer
1.808
971845AH1-439 GEN
Solar/Wind Harmer
3.559
3151731LOISA B
50/50
29.87
3151721LOISA A
50/50
29.716
971133AH1-012 GEN
50/50
7.708
966001AG1-469 GEN
Solar/Wind Harmer
0.841
971489AH1-241 GEN
Solar/Wind Harmer
4.925
315821AE2-092 GEN
Solar/Wind Harmer
1.67
315651AD1-115 GEN
Solar/Wind Harmer
3.25
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
970285AG2-188 GEN
Solar/Wind Harmer
5.66
972183AH1-676 GEN
50/50
491.758
3151771S ANNAG1
50/50
1.517
3151761LOISA E
50/50
60.896
3147666LOUISA
Solar/Wind Harmer
-0.111
3132273ORANGE
Solar/Wind Harmer
-0.006
316170AC1-121 GEN2
Solar/Wind Harmer
0.286
970221AG2-151 GEN
Solar/Wind Harmer
5.187
3148013FISHERV
Solar/Wind Harmer
-0.007
3146776BUCKING
Solar/Wind Harmer
-0.002
3151741LOISA C
50/50
1.633
3151781S ANNAS1
50/50
0.78
3151751LOISA D
50/50
29.87
315683AE1-153 C
Solar/Wind Harmer
69.247
316192AB2-158 GEN
Solar/Wind Harmer
5.795
3147666LOUISA
Solar/Wind Harmer
-0.194
316254AC1-120 GEN1
Solar/Wind Harmer
0.857
971377AH1-170 GEN
Solar/Wind Harmer
1.037
3147623JAMES R
Solar/Wind Harmer
0.128
972003AH1-546 GEN
Solar/Wind Harmer
4.109
970937AG2-583 GEN
Solar/Wind Harmer
4.971
316322AB2-045
Solar/Wind Harmer
0.229
3146776BUCKING
Solar/Wind Harmer
-0.003
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.638
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.545
MECLTFEXP_MEC->PJM
CLTF
0.89
LAGNLTFEXP_LAGN->PJM
CLTF
1.371
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.681
TVALTFEXP_TVA->PJM
CLTF
0.708
SIGELTFEXP_SIGE->PJM
CLTF
0.029
CPLELTFEXP_CPLE->PJM
CLTF
0.992
NYPJM->LTFIMP_NY
CLTF
0.521
LGEELTFEXP_LGEE->PJM
CLTF
0.371
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.208
WECLTFEXP_WEC->PJM
CLTF
0.186

Details for 6GERMANNA-6CIRRUS 230.0 kV Ckt 1 line l/o DVP_P4-2: 25532_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6GERMANNA-6CIRRUS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 25532_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.59 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1223.18
MW Contribution:5.19
Bus #Bus NameTypeMW Contribution
3151731LOISA B
50/50
29.87
3151721LOISA A
50/50
29.716
971133AH1-012 GEN
50/50
7.708
966001AG1-469 GEN
Solar/Wind Harmer
0.841
971489AH1-241 GEN
Solar/Wind Harmer
4.925
315821AE2-092 GEN
Solar/Wind Harmer
1.67
315651AD1-115 GEN
Solar/Wind Harmer
3.25
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
3147346CASHSCORNER
Solar/Wind Harmer
0.709
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
0
972205AH1-687 GEN
Adder
3.253
971447AH1-217 GEN
Solar/Wind Harmer
2.951
316164AC1-076 GEN
Solar/Wind Harmer
0.675
3148133STUARTS
Solar/Wind Harmer
-0.004
3148013FISHERV
Solar/Wind Harmer
-0.004
270494AE1-108_GEN
Solar/Wind Harmer
1.808
971845AH1-439 GEN
Solar/Wind Harmer
3.559
970285AG2-188 GEN
Solar/Wind Harmer
5.66
972183AH1-676 GEN
50/50
491.758
3151771S ANNAG1
50/50
1.517
3151761LOISA E
50/50
60.896
3147666LOUISA
Solar/Wind Harmer
-0.111
3132273ORANGE
Solar/Wind Harmer
-0.006
316170AC1-121 GEN2
Solar/Wind Harmer
0.286
970221AG2-151 GEN
Solar/Wind Harmer
5.187
3148013FISHERV
Solar/Wind Harmer
-0.007
3146776BUCKING
Solar/Wind Harmer
-0.002
3151741LOISA C
50/50
1.633
3151781S ANNAS1
50/50
0.78
3151751LOISA D
50/50
29.87
315683AE1-153 C
Solar/Wind Harmer
69.247
316192AB2-158 GEN
Solar/Wind Harmer
5.795
3147666LOUISA
Solar/Wind Harmer
-0.194
316254AC1-120 GEN1
Solar/Wind Harmer
0.857
971377AH1-170 GEN
Solar/Wind Harmer
1.037
3147623JAMES R
Solar/Wind Harmer
0.128
972003AH1-546 GEN
Solar/Wind Harmer
4.109
970937AG2-583 GEN
Solar/Wind Harmer
4.971
316322AB2-045
Solar/Wind Harmer
0.229
3146776BUCKING
Solar/Wind Harmer
-0.003
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.638
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.545
MECLTFEXP_MEC->PJM
CLTF
0.89
LAGNLTFEXP_LAGN->PJM
CLTF
1.371
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.681
TVALTFEXP_TVA->PJM
CLTF
0.708
SIGELTFEXP_SIGE->PJM
CLTF
0.029
CPLELTFEXP_CPLE->PJM
CLTF
0.992
NYPJM->LTFIMP_NY
CLTF
0.521
LGEELTFEXP_LGEE->PJM
CLTF
0.371
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.208
WECLTFEXP_WEC->PJM
CLTF
0.186

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:198.54 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:1313.88
MW Contribution:21.64
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.706
3144293JTRSVLE
50/50
0.594
970535AG2-341 GEN
50/50
2.11
3152661PLYWOOD A
50/50
0.217
3151041BRUNSWICKG3
50/50
1.059
972187AH1-678 GEN
50/50
2.43
315242AE2-183_GT2
50/50
1.321
3151931BEARGRDN S1
50/50
5.469
3151911BEARGRDN G1
50/50
4.238
3144293JTRSVLE
50/50
0.706
970119AG2-088 GEN
50/50
15.414
3151531CLOVER1
50/50
2.348
3151601KERR 3
50/50
0.22
3151581KERR 1
50/50
0.079
3151921BEARGRDN G2
50/50
4.238
3144293JTRSVLE
50/50
0.706
970413AG2-270 GEN
50/50
10.245
3151591KERR 2
50/50
0.22
3151031BRUNSWICKG2
50/50
1.059
3151261ROARAP2
50/50
0.095
3150861SPRUNCD
50/50
0.364
966251AG1-494 GEN
50/50
1.288
970221AG2-151 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
0.132
3146926FARMVIL
Solar/Wind Harmer
0.176
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.159
316258AE1-075 C
Solar/Wind Harmer
0.19
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.801
970909AG2-566 GEN
Solar/Wind Harmer
2.396
3147133PAMPLIN
Solar/Wind Harmer
0.693
971193AH1-056 GEN
Solar/Wind Harmer
13.448
963181AG1-167 GEN
Solar/Wind Harmer
0.835
959311AF2-222 GEN
Solar/Wind Harmer
15.884
970257AG2-171 GEN
Solar/Wind Harmer
5.55
315785AD2-033 C
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
9.804
316131AB2-060 GEN
Solar/Wind Harmer
0.426
958131AF2-107 GEN
Solar/Wind Harmer
3.651
316478AD1-087 GEN
Solar/Wind Harmer
0.382
316486AD2-202 GEN
Solar/Wind Harmer
0.112
3147043LAWRENC
Solar/Wind Harmer
0.059
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.912
971683AH1-343 GEN
Solar/Wind Harmer
3.032
313506AB2-031 GEN
Solar/Wind Harmer
0.248
970917AG2-570 GEN
Solar/Wind Harmer
6.901
316365GEN2_N
Solar/Wind Harmer
0.164
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
0.117
3145893MURPHYS
Solar/Wind Harmer
0.07
957521AF2-046 GEN
Solar/Wind Harmer
5.202
961681AG1-008 GEN
Solar/Wind Harmer
5.202
3145796HORNRTN
Solar/Wind Harmer
0.279
3145796HORNRTN
Solar/Wind Harmer
0.07
316210AC1-098 GEN
Solar/Wind Harmer
0.644
3146173TUNIS
Solar/Wind Harmer
0.069
316463AE2-346 GEN
Solar/Wind Harmer
0.059
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.732
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.069
316327AA2-057 GEN
Solar/Wind Harmer
0.102
315724AD1-057 GEN
Solar/Wind Harmer
0.25
3145273HOLLAND
Solar/Wind Harmer
0.05
3156021HOLLOMANSOL
Solar/Wind Harmer
0.301
3146233WITAKRS
Solar/Wind Harmer
0.331
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3146206CASHIE
Solar/Wind Harmer
0.065
315813AE1-149 C
Solar/Wind Harmer
3.482
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316283AC2-100 C
Solar/Wind Harmer
0.127
315839AE2-212 C
Solar/Wind Harmer
0.001
315737AD1-076 GEN
Solar/Wind Harmer
0.835
970661AG2-428 GEN
Solar/Wind Harmer
1.373
971157AH1-035 GEN
Solar/Wind Harmer
0.778
315614AA2-178 GEN
Solar/Wind Harmer
0.37
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.129
3146376EDENTON
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
4.548
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316435W1029_GEN3
Solar/Wind Harmer
0
965281AG1-393 GEN
Solar/Wind Harmer
0.68
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
316320Y1-086
Solar/Wind Harmer
0
3145933PARMELE
Solar/Wind Harmer
0.063
966801AG1-551 GEN
Solar/Wind Harmer
0.74
3146456SLIGO L269
Solar/Wind Harmer
0.063
971153AH1-033 GEN
Solar/Wind Harmer
0.732
944581AF1-123 GEN
Solar/Wind Harmer
14.239
944601AF1-125 GEN
Solar/Wind Harmer
14.019
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3151101ELIZAR3
Adder
5.847
3144873MCLAUGH
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.009
315773AC2-141 GEN
Solar/Wind Harmer
2.27
3145336SMITFLD
Solar/Wind Harmer
0.025
3151221GRAVEL6
Adder
4.403
3151171GRAVELC
Adder
0.847
961611AG1-000B GEN
Solar/Wind Harmer
1.612
3143096IRON208
Adder
0.252
3143096IRON208
Adder
0.247
315778AD1-151 GEN
Solar/Wind Harmer
4.818
970129AG2-093 GEN
Solar/Wind Harmer
3.634
970133AG2-095 GEN
Solar/Wind Harmer
0.576
316499AE2-029_GEN
Solar/Wind Helper
0.501
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.3
3148013FISHERV
Solar/Wind Helper
0.129
315616AA1-038_C
Solar/Wind Helper
0.524
3147043LAWRENC
50/50
0.939
3151051BRUNSWICKS1
50/50
2.197
3151021BRUNSWICKG1
50/50
1.059
971451AH1-221 GEN
50/50
3.216
315243AE2-183_GT3
50/50
1.321
3151261ROARAP2
50/50
0.097
3150851SPRUNCC
50/50
0.364
972003AH1-546 GEN
Solar/Wind Harmer
18.676
971377AH1-170 GEN
Solar/Wind Harmer
4.327
3147623JAMES R
Solar/Wind Harmer
0.94
970937AG2-583 GEN
Solar/Wind Harmer
23.217
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.147
3146926FARMVIL
Solar/Wind Harmer
0.176
316336AC2-165 C
Solar/Wind Harmer
0.011
3143336POWHATN
Solar/Wind Harmer
4.472
963171AG1-166 GEN
Solar/Wind Harmer
1.114
971563AH1-280 GEN
Solar/Wind Harmer
2.228
970685AG2-442 GEN
Solar/Wind Harmer
14.313
962491AG1-098 GEN
Solar/Wind Harmer
7.815
315693AD1-088 GEN
Solar/Wind Harmer
6.344
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Harmer
0.116
957481AF2-042 GEN
Solar/Wind Harmer
29.295
970401AG2-262 GEN
Solar/Wind Harmer
0.638
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
4.184
3143526WINTERP
Solar/Wind Harmer
0.504
316129AC1-054 GEN
Solar/Wind Harmer
0.363
971795AH1-408 GEN
Solar/Wind Harmer
6.199
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.793
970919AG2-571 GEN
Solar/Wind Harmer
2.76
970087AG2-069 GEN
Solar/Wind Harmer
6.187
3145783HORNRTN
Solar/Wind Harmer
0.076
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
5.984
316023GEN1_S
Solar/Wind Harmer
0.164
939411AE1-173 GEN
Solar/Wind Harmer
30.681
316011AB1-132 GEN
Solar/Wind Harmer
1.286
962571AG1-106 GEN
Solar/Wind Harmer
1.007
3146263WOODLND
Solar/Wind Harmer
0.071
3145893MURPHYS
Solar/Wind Harmer
0.281
3145893MURPHYS
Solar/Wind Harmer
0.312
3145796HORNRTN
Solar/Wind Harmer
0.23
3145796HORNRTN
Solar/Wind Harmer
0.07
316212AC1-099_GEN
Solar/Wind Harmer
0.359
3146173TUNIS
Solar/Wind Harmer
0.069
3145823KELFORD
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
315722AD1-056 GEN
Solar/Wind Harmer
0.422
3146233WITAKRS
Solar/Wind Harmer
0.263
3146206CASHIE
Solar/Wind Harmer
0.065
971547AH1-271 GEN
Solar/Wind Harmer
1.396
970659AG2-427 GEN
Solar/Wind Harmer
3.146
316381AD1-082 GEN
Solar/Wind Harmer
0.068
970661AG2-428 GEN
Solar/Wind Harmer
6.453
3145663CRESWEL
Solar/Wind Harmer
0.181
971163AH1-040 GEN
Solar/Wind Harmer
5.167
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.052
316359AB2-059 GEN
Solar/Wind Harmer
0.231
316049AB1-081 GEN
Solar/Wind Harmer
0.368
3142053HEARTS
Solar/Wind Harmer
0.113
316093AE2-104_GEN
Solar/Wind Harmer
1.081
3130156CHOWAN
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3142543TWELFTH
Solar/Wind Harmer
0.006
3146516WINFALL
Solar/Wind Harmer
0.207
3146516WINFALL
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.283
316246AF1-032 C
Solar/Wind Harmer
0.029
3146293MARTNCO
Solar/Wind Harmer
0.059
316494AC1-189 GEN
Solar/Wind Harmer
0.214
3146456SLIGO L269
Solar/Wind Harmer
0.063
316388AE2-253 GEN
Solar/Wind Harmer
0.198
944591AF1-124 GEN
Solar/Wind Harmer
14.289
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
315671AE2-027_GEN
Solar/Wind Harmer
4.043
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
1.077
3145336SMITFLD
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
0.644
961611AG1-000B GEN
Solar/Wind Harmer
3.17
971647AH1-324 GEN
Solar/Wind Harmer
2.576
3143096IRON208
Adder
0.252
971069AG2-661 GEN
Solar/Wind Harmer
1.071
316458AB2-190 GEN2
Solar/Wind Harmer
0.323
970129AG2-093 GEN
Solar/Wind Harmer
1.71
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.903
3147666LOUISA
Solar/Wind Helper
0.521
972205AH1-687 GEN
50/50
20.67
316303AF2-085
50/50
2.055
3151541CLOVER2
50/50
2.336
3151611KERR 4
50/50
0.22
3151621KERR 5
50/50
0.22
3151631KERR 6
50/50
0.22
3151641KERR 7
50/50
0.22
963041AG1-153 GEN
50/50
2.144
315244AE2-183_ST
50/50
2.284
315241AE2-183_GT1
50/50
1.313
972185AH1-677 GEN
50/50
4.762
970533AG2-339 GEN
50/50
7.019
970531AG2-338 GEN
50/50
2.808
971489AH1-241 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
1.465
3146776BUCKING
Solar/Wind Harmer
0.119
315821AE2-092 GEN
Solar/Wind Harmer
0.014
970301AG2-198 GEN
Solar/Wind Harmer
9.583
3147133PAMPLIN
Solar/Wind Harmer
0.221
3147133PAMPLIN
Solar/Wind Harmer
0.176
958211AF2-115 GEN
Solar/Wind Harmer
2.506
963191AG1-168 GEN
Solar/Wind Harmer
0.835
971741AH1-377 GEN
Solar/Wind Harmer
20.177
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.401
971775AH1-396 GEN
Solar/Wind Harmer
0.278
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971223AH1-071 GEN
Solar/Wind Harmer
1.233
962561AG1-105 GEN
Solar/Wind Harmer
5.397
939181AE1-148 GEN
Solar/Wind Harmer
5.333
970099AG2-077 GEN
Solar/Wind Harmer
11.718
964791AG1-342 GEN
Solar/Wind Harmer
2.089
3146843MT LREL
Solar/Wind Harmer
0.109
3146843MT LREL
Solar/Wind Harmer
0.109
3143526WINTERP
Solar/Wind Harmer
0.504
970933AG2-581 GEN
Solar/Wind Harmer
7.465
316181AB2-040 GEN
Solar/Wind Harmer
0.116
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.078
966811AG1-552 GEN
Solar/Wind Harmer
0.843
3145593CAROLNA
Solar/Wind Harmer
0.097
3145783HORNRTN
Solar/Wind Harmer
1.361
3145783HORNRTN
Solar/Wind Harmer
1.089
3145783HORNRTN
Solar/Wind Harmer
0.34
3145783HORNRTN
Solar/Wind Harmer
0.136
316426AA2-053 GEN
Solar/Wind Harmer
0.256
3144356SAPONY
Solar/Wind Harmer
0.607
316274AC1-208 GEN
Solar/Wind Harmer
0.366
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.042
3145893MURPHYS
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
0.126
3145796HORNRTN
Solar/Wind Harmer
0.209
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
315742AE1-103 GEN
Solar/Wind Harmer
0.001
316222AC1-221 GEN
Solar/Wind Harmer
0.272
316065AD1-022 GEN
Solar/Wind Harmer
3.004
970657AG2-426 GEN
Solar/Wind Harmer
2.275
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
2.446
3146376EDENTON
Solar/Wind Harmer
0.286
3146376EDENTON
Solar/Wind Harmer
0.286
961601AG1-000A GEN
Solar/Wind Harmer
1.137
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3145493TOT1
Solar/Wind Harmer
0.148
3145453TOT5
Solar/Wind Harmer
0.089
3145603CNETO
Solar/Wind Harmer
0.059
3146386ELIZ CT
Solar/Wind Harmer
0.064
3145933PARMELE
Solar/Wind Harmer
0.127
3145933PARMELE
Solar/Wind Harmer
0.063
3130086AYDLETT
Solar/Wind Harmer
0.253
3137176SLIGO L2192
Solar/Wind Harmer
0.252
3146456SLIGO L269
Solar/Wind Harmer
1.121
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.035
316339AD2-160 GEN
Solar/Wind Harmer
0.103
3145506HICKORY
Solar/Wind Harmer
0.253
3145506HICKORY
Solar/Wind Harmer
0.152
3145506HICKORY
Solar/Wind Harmer
0.038
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.061
942751AE2-291 GEN
Solar/Wind Harmer
3.43
316240AF1-291 C
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.012
3150991CHESPKB
Adder
0.659
3150991CHESPKB
Adder
0.643
944641AF1-129 GEN
Adder
29.755
316236AE1-162_GEN
Solar/Wind Harmer
0
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.068
966001AG1-469 GEN
Solar/Wind Helper
0.206
3151281ROARAP4
50/50
0.094
3151281ROARAP4
50/50
0.088
971285AH1-108 GEN
50/50
0.596
315779AE2-040
50/50
1.013
971447AH1-217 GEN
Solar/Wind Harmer
11.337
971845AH1-439 GEN
Solar/Wind Harmer
16.33
970285AG2-188 GEN
Solar/Wind Harmer
27.559
270494AE1-108_GEN
Solar/Wind Harmer
3.817
315657AE1-056 GEN
Solar/Wind Harmer
7.617
946301AF1-294 GEN
Solar/Wind Harmer
4.122
961791AG1-021 GEN
Solar/Wind Harmer
2.005
970683AG2-441 GEN
Solar/Wind Harmer
12.78
970681AG2-440 GEN
Solar/Wind Harmer
10.224
3144303KENBRDG
Solar/Wind Harmer
0.139
971443AH1-215 GEN
Solar/Wind Harmer
2.888
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.258
316233AE1-074 FULL
Solar/Wind Harmer
0.078
971281AH1-106 GEN
Solar/Wind Harmer
1.344
971283AH1-107 GEN
Solar/Wind Harmer
1.344
970831AG2-522 GEN
Solar/Wind Harmer
4.036
3147173SINAI
Solar/Wind Harmer
0.092
3147243WELCO
Solar/Wind Harmer
0.057
971967AH1-528 GEN
Solar/Wind Harmer
13.711
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
16.986
970673AG2-436 GEN
Solar/Wind Harmer
11.324
941031AE2-094 GEN
Solar/Wind Harmer
14.544
944011AF1-069 GEN
Solar/Wind Harmer
4.752
3137643SOCKMAN
Solar/Wind Harmer
0.315
970865AG2-541 GEN
Solar/Wind Harmer
2.702
970085AG2-068 GEN
Solar/Wind Harmer
4.124
970581AG2-369 GEN
Solar/Wind Harmer
3.547
315607AA1-063A GEN
Solar/Wind Harmer
0.154
3146043SEABORD
Solar/Wind Harmer
0.075
315814AE2-033 C
Solar/Wind Harmer
5.747
316315AB2-025 C
Solar/Wind Harmer
0.059
965291AG1-394 GEN
Solar/Wind Harmer
0.317
315652AC1-086 GEN
Solar/Wind Harmer
7.782
3145893MURPHYS
Solar/Wind Harmer
0.19
3145893MURPHYS
Solar/Wind Harmer
0.07
3145796HORNRTN
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.028
3146033SCOT NK
Solar/Wind Harmer
0.276
316123AC1-075 GEN
Solar/Wind Harmer
0.094
970165AG2-112 GEN
Solar/Wind Harmer
0.558
970163AG2-111 GEN
Solar/Wind Harmer
0.532
3145513AHOSKIE
Solar/Wind Harmer
0.143
3145513AHOSKIE
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3143316POE
Solar/Wind Harmer
0.269
316319Z2-044 C
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.065
970601AG2-382 GEN
Solar/Wind Harmer
2.444
315732AD1-074 GEN1
Solar/Wind Harmer
0.373
315733AD1-074 GEN2
Solar/Wind Harmer
0.373
315735AD1-075 GEN1
Solar/Wind Harmer
0.187
3130546PLYMOUTH
Solar/Wind Harmer
0.065
315816AE2-034 GEN
Solar/Wind Harmer
0.277
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.044
316311AC2-079 GEN
Solar/Wind Harmer
1.853
315835AF2-110_GEN
Solar/Wind Harmer
0.441
3130156CHOWAN
Solar/Wind Harmer
0.064
3130156CHOWAN
Solar/Wind Harmer
0.064
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
316321Z2-027
Solar/Wind Harmer
0.012
3145176PASQUOTANK
Solar/Wind Harmer
0.039
3146396TANGLEW
Solar/Wind Harmer
0.175
316420AA1-050 GEN
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.034
316305AF2-043 C
Solar/Wind Harmer
0.001
957861AF2-080 GEN
Solar/Wind Harmer
2.737
3146406KITTY HAWK
Solar/Wind Harmer
0.008
319010AE1-072 C
Solar/Wind Harmer
0.319
957871AF2-081 GEN
Solar/Wind Harmer
3.153
316005AA1-067
Solar/Wind Harmer
0.068
3145746EVERETS
Solar/Wind Harmer
0.252
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
970181AG2-120 GEN
Solar/Wind Harmer
0.787
3151081ELIZAR1
Adder
5.773
3151091ELIZAR2
Adder
5.672
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.68
3152601GOSPORTA
Adder
0.628
971445AH1-216 GEN
Solar/Wind Harmer
4.321
972265AH1-717 GEN
Adder
4.702
3151201GRAVEL4
Adder
4.408
3151191GRAVEL3
Adder
4.352
3151211GRAVEL5
Adder
4.352
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.323
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.077
3148013FISHERV
Solar/Wind Helper
0.074
3148463FAIRFLD
Solar/Wind Helper
0.116
LAGNLTFEXP_LAGN->PJM
CLTF
1.972
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.131
MECLTFEXP_MEC->PJM
CLTF
0.546
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.458
TVALTFEXP_TVA->PJM
CLTF
0.973
NYPJM->LTFIMP_NY
CLTF
0.616
LGEELTFEXP_LGEE->PJM
CLTF
0.137
WECLTFEXP_WEC->PJM
CLTF
0.063
CPLELTFEXP_CPLE->PJM
CLTF
4.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.705

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:185.18 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1498.1
MW Contribution:28.43
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.633
316303AF2-085
50/50
2.054
971447AH1-217 GEN
Solar/Wind Harmer
14.897
971845AH1-439 GEN
Solar/Wind Harmer
21.465
970285AG2-188 GEN
Solar/Wind Harmer
34.19
270494AE1-108_GEN
Solar/Wind Harmer
9.286
315657AE1-056 GEN
Solar/Wind Harmer
9.291
946301AF1-294 GEN
Solar/Wind Harmer
6.004
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
16.801
970681AG2-440 GEN
Solar/Wind Harmer
13.441
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.796
316239AB2-077_GEN
Solar/Wind Harmer
0.439
316238AB2-078_GEN
Solar/Wind Harmer
0.439
316118AC1-105 GEN
Solar/Wind Harmer
0.773
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.769
971283AH1-107 GEN
Solar/Wind Harmer
1.769
970831AG2-522 GEN
Solar/Wind Harmer
5.308
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.09
946281AF1-292 GEN
Solar/Wind Harmer
0.208
316087AB2-174 GEN
Solar/Wind Harmer
1.297
3144293JTRSVLE
50/50
0.704
3144293JTRSVLE
50/50
0.593
970535AG2-341 GEN
50/50
2.107
971489AH1-241 GEN
Solar/Wind Harmer
26.992
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.547
970301AG2-198 GEN
Solar/Wind Harmer
12.599
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
963191AG1-168 GEN
Solar/Wind Harmer
2.197
971741AH1-377 GEN
Solar/Wind Harmer
26.527
316034AC1-036 C
Solar/Wind Harmer
0.362
970323AG2-213 GEN
Solar/Wind Harmer
9.73
971775AH1-396 GEN
Solar/Wind Harmer
1.386
313527AB2-043 GEN
Solar/Wind Harmer
2.416
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.096
3151931BEARGRDN S1
50/50
5.46
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.704
970119AG2-088 GEN
50/50
15.406
972003AH1-546 GEN
Solar/Wind Harmer
24.588
971377AH1-170 GEN
Solar/Wind Harmer
5.686
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.518
316322AB2-045
Solar/Wind Harmer
1.382
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.598
3143336POWHATN
Solar/Wind Harmer
3.349
963171AG1-166 GEN
Solar/Wind Harmer
2.929
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
18.817
962491AG1-098 GEN
Solar/Wind Harmer
10.277
315693AD1-088 GEN
Solar/Wind Harmer
7.416
316237AB2-079_GEN
Solar/Wind Harmer
0.439
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.531
970401AG2-262 GEN
Solar/Wind Harmer
0.797
315687AD1-152 GEN
Solar/Wind Harmer
1.353
971065AG2-659 GEN
Solar/Wind Harmer
5.503
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.948
971795AH1-408 GEN
Solar/Wind Harmer
7.828
316003AC1-222 GEN
Solar/Wind Harmer
0.95
960081AF2-299 GEN
Solar/Wind Harmer
1.043
970919AG2-571 GEN
Solar/Wind Harmer
2.759
970087AG2-069 GEN
Solar/Wind Harmer
8.141
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
940641AE2-051 GEN
Solar/Wind Harmer
7.878
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.555
939411AE1-173 GEN
Solar/Wind Harmer
40.398
316011AB1-132 GEN
Solar/Wind Harmer
1.663
962571AG1-106 GEN
Solar/Wind Harmer
1.142
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.68
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.782
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.838
970659AG2-427 GEN
Solar/Wind Harmer
3.885
316381AD1-082 GEN
Solar/Wind Harmer
0.67
970661AG2-428 GEN
Solar/Wind Harmer
7.748
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.803
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.974
316049AB1-081 GEN
Solar/Wind Harmer
0.78
316093AE2-104_GEN
Solar/Wind Harmer
2.1
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
315800Z1-036_GEN1
Solar/Wind Harmer
1.779
316174AB2-169 GEN
Solar/Wind Harmer
1.109
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
316246AF1-032 C
Solar/Wind Harmer
0.144
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
944591AF1-124 GEN
Solar/Wind Harmer
32.454
3150981CHESPKA
Adder
0.786
3151171GRAVELC
Adder
0.645
3143096IRON208
Adder
0.253
944631AF1-128 GEN
Adder
26.841
316192AB2-158 GEN
Solar/Wind Helper
1.013
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
939181AE1-148 GEN
Solar/Wind Harmer
7.013
970099AG2-077 GEN
Solar/Wind Harmer
15.412
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.821
972187AH1-678 GEN
Adder
2.289
316181AB2-040 GEN
Solar/Wind Harmer
1.257
972185AH1-677 GEN
Adder
4.486
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.855
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.79
316222AC1-221 GEN
Solar/Wind Harmer
0.745
316065AD1-022 GEN
Solar/Wind Harmer
3.665
970657AG2-426 GEN
Solar/Wind Harmer
2.282
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
3.387
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.822
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.78
966001AG1-469 GEN
Solar/Wind Helper
0.216
970673AG2-436 GEN
Solar/Wind Harmer
18.787
970673AG2-436 GEN
Solar/Wind Harmer
9.512
941031AE2-094 GEN
Solar/Wind Harmer
16.63
944011AF1-069 GEN
Solar/Wind Harmer
5.211
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970865AG2-541 GEN
Solar/Wind Harmer
3.55
970085AG2-068 GEN
Solar/Wind Harmer
5.427
970581AG2-369 GEN
Solar/Wind Harmer
4.667
315607AA1-063A GEN
Solar/Wind Harmer
0.852
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.6
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.71
315652AC1-086 GEN
Solar/Wind Harmer
8.941
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
316123AC1-075 GEN
Solar/Wind Harmer
0.832
970165AG2-112 GEN
Solar/Wind Harmer
0.733
970163AG2-111 GEN
Solar/Wind Harmer
0.699
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316319Z2-044 C
Solar/Wind Harmer
0.41
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.217
315732AD1-074 GEN1
Solar/Wind Harmer
1.475
315733AD1-074 GEN2
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.737
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316349AD2-085 GEN
Solar/Wind Harmer
0.645
315816AE2-034 GEN
Solar/Wind Harmer
0.587
316311AC2-079 GEN
Solar/Wind Harmer
3.659
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.779
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
316321Z2-027
Solar/Wind Harmer
0.193
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.193
316420AA1-050 GEN
Solar/Wind Harmer
0.816
316305AF2-043 C
Solar/Wind Harmer
0.215
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
3151081ELIZAR1
Adder
5.776
3151091ELIZAR2
Adder
5.675
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.681
3152601GOSPORTA
Adder
0.628
972265AH1-717 GEN
Adder
4.706
3151201GRAVEL4
Adder
4.411
3151191GRAVEL3
Adder
4.355
3151211GRAVEL5
Adder
4.355
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.704
970221AG2-151 GEN
Solar/Wind Harmer
28.432
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.296
316313AB2-026
Solar/Wind Harmer
0.761
316258AE1-075 C
Solar/Wind Harmer
0.685
316405AF2-144 C
Solar/Wind Harmer
0.723
3143336POWHATN
Solar/Wind Harmer
2.847
970909AG2-566 GEN
Solar/Wind Harmer
2.392
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.485
963181AG1-167 GEN
Solar/Wind Harmer
2.197
959311AF2-222 GEN
Solar/Wind Harmer
20.924
970257AG2-171 GEN
Solar/Wind Harmer
7.297
315785AD2-033 C
Solar/Wind Harmer
4.227
964241AG1-285 GEN
Solar/Wind Harmer
12.89
316131AB2-060 GEN
Solar/Wind Harmer
1.639
958131AF2-107 GEN
Solar/Wind Harmer
4.847
316478AD1-087 GEN
Solar/Wind Harmer
1.065
316486AD2-202 GEN
Solar/Wind Harmer
0.312
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.31
960061AF2-297 GEN
Solar/Wind Harmer
5.143
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.986
313506AB2-031 GEN
Solar/Wind Harmer
0.724
970917AG2-570 GEN
Solar/Wind Harmer
21.795
3150861SPRUNCD
Adder
0.344
316365GEN2_N
Solar/Wind Harmer
0.555
3156081AA2-088 GEN
Solar/Wind Harmer
2.586
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.185
961681AG1-008 GEN
Solar/Wind Harmer
6.185
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146173TUNIS
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.125
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.963
316317KELFORD C
Solar/Wind Harmer
0.363
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.766
315724AD1-057 GEN
Solar/Wind Harmer
0.43
3145273HOLLAND
Solar/Wind Harmer
-0.006
3156021HOLLOMANSOL
Solar/Wind Harmer
1.002
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.587
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
1.186
315839AE2-212 C
Solar/Wind Harmer
0.22
970661AG2-428 GEN
Solar/Wind Harmer
1.373
315737AD1-076 GEN
Solar/Wind Harmer
1.386
316283AC2-100 C
Solar/Wind Harmer
0.686
971157AH1-035 GEN
Solar/Wind Harmer
0.911
315614AA2-178 GEN
Solar/Wind Harmer
0.783
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.858
3146516WINFALL
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.896
316435W1029_GEN3
Solar/Wind Harmer
1.299
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.419
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.891
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151101ELIZAR3
Adder
5.849
3151221GRAVEL6
Adder
4.406
3151171GRAVELC
Adder
0.848
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.338
3148013FISHERV
Solar/Wind Helper
0.13
315616AA1-038_C
Solar/Wind Helper
0.528
944581AF1-123 GEN
Solar/Wind Harmer
20.452
LAGNLTFEXP_LAGN->PJM
CLTF
1.959
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.573
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.107
MECLTFEXP_MEC->PJM
CLTF
0.537
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.437
TVALTFEXP_TVA->PJM
CLTF
0.967
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.612
LGEELTFEXP_LGEE->PJM
CLTF
0.133
WECLTFEXP_WEC->PJM
CLTF
0.061
CPLELTFEXP_CPLE->PJM
CLTF
4.206
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.627

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:185.18 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1498.08
MW Contribution:28.43
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.633
316303AF2-085
50/50
2.054
971447AH1-217 GEN
Solar/Wind Harmer
14.896
971845AH1-439 GEN
Solar/Wind Harmer
21.465
970285AG2-188 GEN
Solar/Wind Harmer
34.19
270494AE1-108_GEN
Solar/Wind Harmer
9.286
315657AE1-056 GEN
Solar/Wind Harmer
9.291
946301AF1-294 GEN
Solar/Wind Harmer
6.004
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
16.8
970681AG2-440 GEN
Solar/Wind Harmer
13.44
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.796
316239AB2-077_GEN
Solar/Wind Harmer
0.439
316238AB2-078_GEN
Solar/Wind Harmer
0.439
316118AC1-105 GEN
Solar/Wind Harmer
0.773
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.769
971283AH1-107 GEN
Solar/Wind Harmer
1.769
970831AG2-522 GEN
Solar/Wind Harmer
5.308
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.09
946281AF1-292 GEN
Solar/Wind Harmer
0.208
316087AB2-174 GEN
Solar/Wind Harmer
1.297
970673AG2-436 GEN
Solar/Wind Harmer
18.787
970673AG2-436 GEN
Solar/Wind Harmer
9.512
941031AE2-094 GEN
Solar/Wind Harmer
16.63
944011AF1-069 GEN
Solar/Wind Harmer
5.211
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970865AG2-541 GEN
Solar/Wind Harmer
3.55
970085AG2-068 GEN
Solar/Wind Harmer
5.427
970581AG2-369 GEN
Solar/Wind Harmer
4.667
315607AA1-063A GEN
Solar/Wind Harmer
0.852
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.6
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.71
315652AC1-086 GEN
Solar/Wind Harmer
8.941
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
316123AC1-075 GEN
Solar/Wind Harmer
0.832
970165AG2-112 GEN
Solar/Wind Harmer
0.733
970163AG2-111 GEN
Solar/Wind Harmer
0.699
3145513AHOSKIE
Solar/Wind Harmer
0.067
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.704
970221AG2-151 GEN
Solar/Wind Harmer
28.431
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.296
316313AB2-026
Solar/Wind Harmer
0.761
316258AE1-075 C
Solar/Wind Harmer
0.685
316405AF2-144 C
Solar/Wind Harmer
0.723
3143336POWHATN
Solar/Wind Harmer
2.847
970909AG2-566 GEN
Solar/Wind Harmer
2.392
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.484
963181AG1-167 GEN
Solar/Wind Harmer
2.197
959311AF2-222 GEN
Solar/Wind Harmer
20.924
970257AG2-171 GEN
Solar/Wind Harmer
7.297
315785AD2-033 C
Solar/Wind Harmer
4.227
964241AG1-285 GEN
Solar/Wind Harmer
12.89
316131AB2-060 GEN
Solar/Wind Harmer
1.639
958131AF2-107 GEN
Solar/Wind Harmer
4.847
316478AD1-087 GEN
Solar/Wind Harmer
1.065
316486AD2-202 GEN
Solar/Wind Harmer
0.312
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.31
960061AF2-297 GEN
Solar/Wind Harmer
5.143
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.986
313506AB2-031 GEN
Solar/Wind Harmer
0.724
970917AG2-570 GEN
Solar/Wind Harmer
21.795
3150861SPRUNCD
Adder
0.344
316365GEN2_N
Solar/Wind Harmer
0.555
3156081AA2-088 GEN
Solar/Wind Harmer
2.585
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.185
961681AG1-008 GEN
Solar/Wind Harmer
6.185
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146173TUNIS
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.125
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.963
316317KELFORD C
Solar/Wind Harmer
0.363
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.766
315724AD1-057 GEN
Solar/Wind Harmer
0.43
3145273HOLLAND
Solar/Wind Harmer
-0.006
3156021HOLLOMANSOL
Solar/Wind Harmer
1.002
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.587
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
1.186
315839AE2-212 C
Solar/Wind Harmer
0.22
970661AG2-428 GEN
Solar/Wind Harmer
1.373
315737AD1-076 GEN
Solar/Wind Harmer
1.386
316283AC2-100 C
Solar/Wind Harmer
0.686
971157AH1-035 GEN
Solar/Wind Harmer
0.911
315614AA2-178 GEN
Solar/Wind Harmer
0.783
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.858
3146516WINFALL
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.896
316435W1029_GEN3
Solar/Wind Harmer
1.299
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.419
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.891
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151101ELIZAR3
Adder
5.85
3151221GRAVEL6
Adder
4.406
3151171GRAVELC
Adder
0.848
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.339
3148013FISHERV
Solar/Wind Helper
0.13
315616AA1-038_C
Solar/Wind Helper
0.528
944581AF1-123 GEN
Solar/Wind Harmer
20.452
3151931BEARGRDN S1
50/50
5.46
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.704
970119AG2-088 GEN
50/50
15.406
972003AH1-546 GEN
Solar/Wind Harmer
24.587
971377AH1-170 GEN
Solar/Wind Harmer
5.686
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.517
316322AB2-045
Solar/Wind Harmer
1.382
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.597
3143336POWHATN
Solar/Wind Harmer
3.349
963171AG1-166 GEN
Solar/Wind Harmer
2.929
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
18.817
962491AG1-098 GEN
Solar/Wind Harmer
10.277
315693AD1-088 GEN
Solar/Wind Harmer
7.416
316237AB2-079_GEN
Solar/Wind Harmer
0.439
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.531
970401AG2-262 GEN
Solar/Wind Harmer
0.797
315687AD1-152 GEN
Solar/Wind Harmer
1.353
971065AG2-659 GEN
Solar/Wind Harmer
5.503
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.948
971795AH1-408 GEN
Solar/Wind Harmer
7.828
316003AC1-222 GEN
Solar/Wind Harmer
0.95
960081AF2-299 GEN
Solar/Wind Harmer
1.043
970919AG2-571 GEN
Solar/Wind Harmer
2.759
970087AG2-069 GEN
Solar/Wind Harmer
8.141
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
940641AE2-051 GEN
Solar/Wind Harmer
7.878
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.555
939411AE1-173 GEN
Solar/Wind Harmer
40.398
316011AB1-132 GEN
Solar/Wind Harmer
1.663
962571AG1-106 GEN
Solar/Wind Harmer
1.142
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.68
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.782
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.838
970659AG2-427 GEN
Solar/Wind Harmer
3.885
316381AD1-082 GEN
Solar/Wind Harmer
0.67
970661AG2-428 GEN
Solar/Wind Harmer
7.748
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.803
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.974
316049AB1-081 GEN
Solar/Wind Harmer
0.78
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316319Z2-044 C
Solar/Wind Harmer
0.41
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.217
315732AD1-074 GEN1
Solar/Wind Harmer
1.475
315733AD1-074 GEN2
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.737
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316349AD2-085 GEN
Solar/Wind Harmer
0.645
315816AE2-034 GEN
Solar/Wind Harmer
0.587
316311AC2-079 GEN
Solar/Wind Harmer
3.659
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.779
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.193
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.193
316305AF2-043 C
Solar/Wind Harmer
0.215
316420AA1-050 GEN
Solar/Wind Harmer
0.816
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
3151081ELIZAR1
Adder
5.776
3151091ELIZAR2
Adder
5.675
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.681
3152601GOSPORTA
Adder
0.628
972265AH1-717 GEN
Adder
4.706
3151201GRAVEL4
Adder
4.411
3151191GRAVEL3
Adder
4.355
3151211GRAVEL5
Adder
4.355
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
316093AE2-104_GEN
Solar/Wind Harmer
2.1
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
315800Z1-036_GEN1
Solar/Wind Harmer
1.779
316174AB2-169 GEN
Solar/Wind Harmer
1.109
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3144293JTRSVLE
50/50
0.704
3144293JTRSVLE
50/50
0.593
970535AG2-341 GEN
50/50
2.107
971489AH1-241 GEN
Solar/Wind Harmer
26.992
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.547
970301AG2-198 GEN
Solar/Wind Harmer
12.599
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
963191AG1-168 GEN
Solar/Wind Harmer
2.197
971741AH1-377 GEN
Solar/Wind Harmer
26.527
316034AC1-036 C
Solar/Wind Harmer
0.361
970323AG2-213 GEN
Solar/Wind Harmer
9.729
971775AH1-396 GEN
Solar/Wind Harmer
1.386
313527AB2-043 GEN
Solar/Wind Harmer
2.416
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.096
939181AE1-148 GEN
Solar/Wind Harmer
7.013
970099AG2-077 GEN
Solar/Wind Harmer
15.412
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.821
972187AH1-678 GEN
Adder
2.289
316181AB2-040 GEN
Solar/Wind Harmer
1.257
972185AH1-677 GEN
Adder
4.486
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.855
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.79
316222AC1-221 GEN
Solar/Wind Harmer
0.745
316065AD1-022 GEN
Solar/Wind Harmer
3.665
970657AG2-426 GEN
Solar/Wind Harmer
2.282
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
3.387
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.822
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.781
966001AG1-469 GEN
Solar/Wind Helper
0.216
3145493TOT1
Solar/Wind Harmer
0.212
316246AF1-032 C
Solar/Wind Harmer
0.144
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
944591AF1-124 GEN
Solar/Wind Harmer
32.454
3150981CHESPKA
Adder
0.786
3151171GRAVELC
Adder
0.645
3143096IRON208
Adder
0.253
944631AF1-128 GEN
Adder
26.842
316192AB2-158 GEN
Solar/Wind Helper
1.014
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
LAGNLTFEXP_LAGN->PJM
CLTF
1.959
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.572
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.107
MECLTFEXP_MEC->PJM
CLTF
0.537
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.437
TVALTFEXP_TVA->PJM
CLTF
0.967
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.612
LGEELTFEXP_LGEE->PJM
CLTF
0.133
WECLTFEXP_WEC->PJM
CLTF
0.061
CPLELTFEXP_CPLE->PJM
CLTF
4.206
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.626

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:177.73 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1437.82
MW Contribution:28.82
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.533
3151911BEARGRDN G1
50/50
4.287
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
18.19
972003AH1-546 GEN
Solar/Wind Harmer
24.898
971377AH1-170 GEN
Solar/Wind Harmer
5.763
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.282
316322AB2-045
Solar/Wind Harmer
1.394
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.86
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
963171AG1-166 GEN
Solar/Wind Harmer
2.905
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
18.606
3143226MDLTHAN
Solar/Wind Harmer
-0.015
962491AG1-098 GEN
Solar/Wind Harmer
9.894
315693AD1-088 GEN
Solar/Wind Harmer
7.12
316237AB2-079_GEN
Solar/Wind Harmer
0.427
3143526WINTERP
Solar/Wind Harmer
-0.065
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.362
315687AD1-152 GEN
Solar/Wind Harmer
1.282
971065AG2-659 GEN
Solar/Wind Harmer
5.251
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.904
971795AH1-408 GEN
Solar/Wind Harmer
7.449
3150851SPRUNCC
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.906
960081AF2-299 GEN
Solar/Wind Harmer
0.983
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
970919AG2-571 GEN
Solar/Wind Harmer
2.482
970087AG2-069 GEN
Solar/Wind Harmer
7.326
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.518
940641AE2-051 GEN
Solar/Wind Harmer
6.973
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.551
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
316212AC1-099_GEN
Solar/Wind Harmer
0.635
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.08
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
5.319
970659AG2-427 GEN
Solar/Wind Harmer
3.71
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.588
970535AG2-341 GEN
50/50
2.034
971489AH1-241 GEN
Solar/Wind Harmer
27.358
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.65
970301AG2-198 GEN
Solar/Wind Harmer
12.49
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.631
963191AG1-168 GEN
Solar/Wind Harmer
2.179
971741AH1-377 GEN
Solar/Wind Harmer
26.175
316034AC1-036 C
Solar/Wind Harmer
0.356
970323AG2-213 GEN
Solar/Wind Harmer
9.582
971775AH1-396 GEN
Solar/Wind Harmer
1.365
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.349
3143526WINTERP
Solar/Wind Harmer
-0.065
962561AG1-105 GEN
Solar/Wind Harmer
6.845
939181AE1-148 GEN
Solar/Wind Harmer
6.741
964791AG1-342 GEN
Solar/Wind Harmer
2.511
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.545
970933AG2-581 GEN
Solar/Wind Harmer
9.023
316181AB2-040 GEN
Solar/Wind Harmer
1.184
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.923
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.055
3145783HORNRTN
Solar/Wind Harmer
0.958
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.016
316426AA2-053 GEN
Solar/Wind Harmer
0.809
3144356SAPONY
Solar/Wind Harmer
0.264
316274AC1-208 GEN
Solar/Wind Harmer
0.799
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
972205AH1-687 GEN
50/50
20.91
316303AF2-085
50/50
2.425
971447AH1-217 GEN
Solar/Wind Harmer
15.108
971845AH1-439 GEN
Solar/Wind Harmer
21.634
970285AG2-188 GEN
Solar/Wind Harmer
34.428
270494AE1-108_GEN
Solar/Wind Harmer
9.407
315657AE1-056 GEN
Solar/Wind Harmer
9.233
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
16.612
970681AG2-440 GEN
Solar/Wind Harmer
13.29
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.737
316239AB2-077_GEN
Solar/Wind Harmer
0.427
316238AB2-078_GEN
Solar/Wind Harmer
0.427
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316118AC1-105 GEN
Solar/Wind Harmer
0.741
970831AG2-522 GEN
Solar/Wind Harmer
5.054
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
316381AD1-082 GEN
Solar/Wind Harmer
0.639
315722AD1-056 GEN
Solar/Wind Harmer
0.728
970661AG2-428 GEN
Solar/Wind Harmer
7.356
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
970129AG2-093 GEN
Solar/Wind Harmer
1.536
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316458AB2-190 GEN2
Solar/Wind Harmer
0.68
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.303
316359AB2-059 GEN
Solar/Wind Harmer
0.905
316049AB1-081 GEN
Solar/Wind Harmer
0.725
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.951
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
316174AB2-169 GEN
Solar/Wind Harmer
1.029
315800Z1-036_GEN1
Solar/Wind Harmer
1.645
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
971647AH1-324 GEN
Solar/Wind Harmer
3.305
316246AF1-032 C
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.913
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.242
316388AE2-253 GEN
Solar/Wind Harmer
0.443
316375AC2-012 GEN
Solar/Wind Harmer
2.263
3150981CHESPKA
Adder
0.727
3151171GRAVELC
Adder
0.617
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.88
3147666LOUISA
Solar/Wind Helper
0.508
944591AF1-124 GEN
Solar/Wind Harmer
8.419
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.235
315742AE1-103 GEN
Solar/Wind Harmer
0.736
970657AG2-426 GEN
Solar/Wind Harmer
2.172
970657AG2-426 GEN
Solar/Wind Harmer
0.454
316222AC1-221 GEN
Solar/Wind Harmer
0.698
316065AD1-022 GEN
Solar/Wind Harmer
3.4
942751AE2-291 GEN
Solar/Wind Harmer
4.316
316263AC1-034 GEN
Solar/Wind Harmer
3.148
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.622
316033AB2-134 GEN
Solar/Wind Harmer
2.144
315697AD1-025 GEN
Solar/Wind Harmer
1.345
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.2
316433W1029_GEN2
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316018AA1-139 ULT2
Solar/Wind Harmer
0.563
316017AA1-139 ULT1
Solar/Wind Harmer
0.531
316339AD2-160 GEN
Solar/Wind Harmer
0.443
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.691
3142956BIRDNECK
Solar/Wind Harmer
0.351
316316AC1-027 C
Solar/Wind Harmer
0.201
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.082
3150701DARBY 4
Adder
4.072
3150681DARBY 2
Adder
4.067
3150671DARBY 1
Adder
4.063
966001AG1-469 GEN
Solar/Wind Helper
0.202
946281AF1-292 GEN
Solar/Wind Harmer
0.196
971967AH1-528 GEN
Solar/Wind Harmer
16.369
316087AB2-174 GEN
Solar/Wind Harmer
1.222
970865AG2-541 GEN
Solar/Wind Harmer
3.392
3137643SOCKMAN
Solar/Wind Harmer
-0.033
970673AG2-436 GEN
Solar/Wind Harmer
16.777
970673AG2-436 GEN
Solar/Wind Harmer
8.495
315607AA1-063A GEN
Solar/Wind Harmer
0.8
941031AE2-094 GEN
Solar/Wind Harmer
14.78
944011AF1-069 GEN
Solar/Wind Harmer
4.631
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.884
970581AG2-369 GEN
Solar/Wind Harmer
4.201
315814AE2-033 C
Solar/Wind Harmer
7.048
316315AB2-025 C
Solar/Wind Harmer
0.204
965291AG1-394 GEN
Solar/Wind Harmer
0.664
315652AC1-086 GEN
Solar/Wind Harmer
8.34
316123AC1-075 GEN
Solar/Wind Harmer
0.797
970165AG2-112 GEN
Solar/Wind Harmer
0.701
970163AG2-111 GEN
Solar/Wind Harmer
0.669
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.381
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.985
315833AF1-017_GEN
Solar/Wind Harmer
1.293
316349AD2-085 GEN
Solar/Wind Harmer
0.606
316311AC2-079 GEN
Solar/Wind Harmer
3.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.367
315733AD1-074 GEN2
Solar/Wind Harmer
1.367
315735AD1-075 GEN1
Solar/Wind Harmer
0.684
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.68
315816AE2-034 GEN
Solar/Wind Harmer
0.544
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.645
316369SG1_INVT
Solar/Wind Harmer
1.188
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.757
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.895
316321Z2-027
Solar/Wind Harmer
0.178
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
316305AF2-043 C
Solar/Wind Harmer
0.199
313526AB2-022
Solar/Wind Harmer
0.178
316005AA1-067
Solar/Wind Harmer
0.133
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.865
3146406KITTY HAWK
Solar/Wind Harmer
0.005
319010AE1-072 C
Solar/Wind Harmer
1.33
957871AF2-081 GEN
Solar/Wind Harmer
3.284
3152611GOSPORTB
Adder
0.742
3152621GOSPORTC
Adder
0.629
3152601GOSPORTA
Adder
0.581
3151081ELIZAR1
Adder
5.335
3151091ELIZAR2
Adder
5.243
972265AH1-717 GEN
Adder
4.506
3151201GRAVEL4
Adder
4.224
3151191GRAVEL3
Adder
4.17
3151211GRAVEL5
Adder
4.17
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
3151921BEARGRDN G2
50/50
4.287
3144293JTRSVLE
50/50
0.699
970221AG2-151 GEN
Solar/Wind Harmer
28.817
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.807
316258AE1-075 C
Solar/Wind Harmer
0.726
316405AF2-144 C
Solar/Wind Harmer
0.766
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.288
970909AG2-566 GEN
Solar/Wind Harmer
2.372
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.388
963181AG1-167 GEN
Solar/Wind Harmer
2.179
959311AF2-222 GEN
Solar/Wind Harmer
20.632
970257AG2-171 GEN
Solar/Wind Harmer
7.186
315785AD2-033 C
Solar/Wind Harmer
4.155
964241AG1-285 GEN
Solar/Wind Harmer
12.598
316131AB2-060 GEN
Solar/Wind Harmer
1.595
958131AF2-107 GEN
Solar/Wind Harmer
4.893
316478AD1-087 GEN
Solar/Wind Harmer
1.01
316486AD2-202 GEN
Solar/Wind Harmer
0.296
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.904
3150861SPRUNCD
Adder
0.382
971683AH1-343 GEN
Solar/Wind Harmer
3.805
966621AG1-532 GEN
Solar/Wind Harmer
0.177
313506AB2-031 GEN
Solar/Wind Harmer
0.682
970917AG2-570 GEN
Solar/Wind Harmer
19.61
316365GEN2_N
Solar/Wind Harmer
0.518
3156081AA2-088 GEN
Solar/Wind Harmer
2.417
3146263WOODLND
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.773
961681AG1-008 GEN
Solar/Wind Harmer
5.773
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316210AC1-098 GEN
Solar/Wind Harmer
1.142
3146173TUNIS
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
316140AB2-099
Solar/Wind Harmer
0.048
962331AG1-082 GEN
Solar/Wind Harmer
0.898
316317KELFORD C
Solar/Wind Harmer
0.338
3145823KELFORD
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.89
316327AA2-057 GEN
Solar/Wind Harmer
0.714
315813AE1-149 C
Solar/Wind Harmer
4.418
970659AG2-427 GEN
Solar/Wind Harmer
0.658
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
0.4
3145273HOLLAND
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
1.304
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315737AD1-076 GEN
Solar/Wind Harmer
1.285
971157AH1-035 GEN
Solar/Wind Harmer
0.844
970129AG2-093 GEN
Solar/Wind Harmer
3.791
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.725
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.787
961601AG1-000A GEN
Solar/Wind Harmer
2.655
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.827
316320Y1-086
Solar/Wind Harmer
0.387
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.801
961611AG1-000B GEN
Solar/Wind Harmer
1.383
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.404
3151221GRAVEL6
Adder
4.219
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
315616AA1-038_C
Solar/Wind Helper
0.514
LAGNLTFEXP_LAGN->PJM
CLTF
1.764
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.055
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.782
MECLTFEXP_MEC->PJM
CLTF
0.452
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.761
TVALTFEXP_TVA->PJM
CLTF
0.87
SIGELTFEXP_SIGE->PJM
CLTF
0.012
NYPJM->LTFIMP_NY
CLTF
0.577
LGEELTFEXP_LGEE->PJM
CLTF
0.104
WECLTFEXP_WEC->PJM
CLTF
0.046
CPLELTFEXP_CPLE->PJM
CLTF
3.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.641

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:177.73 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1437.82
MW Contribution:28.82
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.588
970535AG2-341 GEN
50/50
2.034
971489AH1-241 GEN
Solar/Wind Harmer
27.358
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.65
970301AG2-198 GEN
Solar/Wind Harmer
12.49
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.631
963191AG1-168 GEN
Solar/Wind Harmer
2.179
971741AH1-377 GEN
Solar/Wind Harmer
26.175
316034AC1-036 C
Solar/Wind Harmer
0.356
970323AG2-213 GEN
Solar/Wind Harmer
9.582
971775AH1-396 GEN
Solar/Wind Harmer
1.365
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.349
3143526WINTERP
Solar/Wind Harmer
-0.065
962561AG1-105 GEN
Solar/Wind Harmer
6.845
939181AE1-148 GEN
Solar/Wind Harmer
6.741
964791AG1-342 GEN
Solar/Wind Harmer
2.511
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.545
970933AG2-581 GEN
Solar/Wind Harmer
9.023
316181AB2-040 GEN
Solar/Wind Harmer
1.184
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.923
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.055
3145783HORNRTN
Solar/Wind Harmer
0.958
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.016
316426AA2-053 GEN
Solar/Wind Harmer
0.809
3144356SAPONY
Solar/Wind Harmer
0.264
316274AC1-208 GEN
Solar/Wind Harmer
0.799
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.235
315742AE1-103 GEN
Solar/Wind Harmer
0.736
970657AG2-426 GEN
Solar/Wind Harmer
2.172
970657AG2-426 GEN
Solar/Wind Harmer
0.454
316222AC1-221 GEN
Solar/Wind Harmer
0.698
316065AD1-022 GEN
Solar/Wind Harmer
3.4
942751AE2-291 GEN
Solar/Wind Harmer
4.316
316263AC1-034 GEN
Solar/Wind Harmer
3.148
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.622
316033AB2-134 GEN
Solar/Wind Harmer
2.144
315697AD1-025 GEN
Solar/Wind Harmer
1.345
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.2
316433W1029_GEN2
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316018AA1-139 ULT2
Solar/Wind Harmer
0.563
316017AA1-139 ULT1
Solar/Wind Harmer
0.531
316339AD2-160 GEN
Solar/Wind Harmer
0.443
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.691
3142956BIRDNECK
Solar/Wind Harmer
0.351
316316AC1-027 C
Solar/Wind Harmer
0.201
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.082
3150701DARBY 4
Adder
4.072
3150681DARBY 2
Adder
4.067
3150671DARBY 1
Adder
4.063
966001AG1-469 GEN
Solar/Wind Helper
0.202
3151931BEARGRDN S1
50/50
5.533
3151911BEARGRDN G1
50/50
4.287
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
18.19
972003AH1-546 GEN
Solar/Wind Harmer
24.898
971377AH1-170 GEN
Solar/Wind Harmer
5.763
3147623JAMES R
Solar/Wind Harmer
0.713
972205AH1-687 GEN
50/50
20.91
316303AF2-085
50/50
2.425
971447AH1-217 GEN
Solar/Wind Harmer
15.108
971845AH1-439 GEN
Solar/Wind Harmer
21.634
970285AG2-188 GEN
Solar/Wind Harmer
34.428
270494AE1-108_GEN
Solar/Wind Harmer
9.407
315657AE1-056 GEN
Solar/Wind Harmer
9.233
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
16.612
970681AG2-440 GEN
Solar/Wind Harmer
13.29
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.737
316239AB2-077_GEN
Solar/Wind Harmer
0.427
316238AB2-078_GEN
Solar/Wind Harmer
0.427
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316118AC1-105 GEN
Solar/Wind Harmer
0.741
970831AG2-522 GEN
Solar/Wind Harmer
5.054
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
946281AF1-292 GEN
Solar/Wind Harmer
0.196
971967AH1-528 GEN
Solar/Wind Harmer
16.369
316087AB2-174 GEN
Solar/Wind Harmer
1.222
970865AG2-541 GEN
Solar/Wind Harmer
3.392
3137643SOCKMAN
Solar/Wind Harmer
-0.033
970673AG2-436 GEN
Solar/Wind Harmer
16.777
970673AG2-436 GEN
Solar/Wind Harmer
8.495
315607AA1-063A GEN
Solar/Wind Harmer
0.8
941031AE2-094 GEN
Solar/Wind Harmer
14.78
944011AF1-069 GEN
Solar/Wind Harmer
4.631
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.884
970581AG2-369 GEN
Solar/Wind Harmer
4.201
315814AE2-033 C
Solar/Wind Harmer
7.048
316315AB2-025 C
Solar/Wind Harmer
0.204
965291AG1-394 GEN
Solar/Wind Harmer
0.664
315652AC1-086 GEN
Solar/Wind Harmer
8.34
316123AC1-075 GEN
Solar/Wind Harmer
0.797
970165AG2-112 GEN
Solar/Wind Harmer
0.701
970163AG2-111 GEN
Solar/Wind Harmer
0.669
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.381
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.985
315833AF1-017_GEN
Solar/Wind Harmer
1.293
316349AD2-085 GEN
Solar/Wind Harmer
0.606
316311AC2-079 GEN
Solar/Wind Harmer
3.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.367
315733AD1-074 GEN2
Solar/Wind Harmer
1.367
315735AD1-075 GEN1
Solar/Wind Harmer
0.684
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.68
315816AE2-034 GEN
Solar/Wind Harmer
0.544
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.645
316369SG1_INVT
Solar/Wind Harmer
1.188
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.757
3146486SUNBURY
Solar/Wind Harmer
-0.007
3151921BEARGRDN G2
50/50
4.287
3144293JTRSVLE
50/50
0.699
970221AG2-151 GEN
Solar/Wind Harmer
28.817
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.807
316258AE1-075 C
Solar/Wind Harmer
0.726
316405AF2-144 C
Solar/Wind Harmer
0.766
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.288
970909AG2-566 GEN
Solar/Wind Harmer
2.372
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.388
963181AG1-167 GEN
Solar/Wind Harmer
2.179
959311AF2-222 GEN
Solar/Wind Harmer
20.632
970257AG2-171 GEN
Solar/Wind Harmer
7.186
315785AD2-033 C
Solar/Wind Harmer
4.155
964241AG1-285 GEN
Solar/Wind Harmer
12.598
316131AB2-060 GEN
Solar/Wind Harmer
1.595
958131AF2-107 GEN
Solar/Wind Harmer
4.893
316478AD1-087 GEN
Solar/Wind Harmer
1.01
316486AD2-202 GEN
Solar/Wind Harmer
0.296
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.904
3150861SPRUNCD
Adder
0.382
971683AH1-343 GEN
Solar/Wind Harmer
3.805
966621AG1-532 GEN
Solar/Wind Harmer
0.177
313506AB2-031 GEN
Solar/Wind Harmer
0.682
970917AG2-570 GEN
Solar/Wind Harmer
19.61
316365GEN2_N
Solar/Wind Harmer
0.518
3156081AA2-088 GEN
Solar/Wind Harmer
2.417
3146263WOODLND
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.773
961681AG1-008 GEN
Solar/Wind Harmer
5.773
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316210AC1-098 GEN
Solar/Wind Harmer
1.142
3146173TUNIS
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
316140AB2-099
Solar/Wind Harmer
0.048
962331AG1-082 GEN
Solar/Wind Harmer
0.898
316317KELFORD C
Solar/Wind Harmer
0.338
3145823KELFORD
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.89
316327AA2-057 GEN
Solar/Wind Harmer
0.714
315813AE1-149 C
Solar/Wind Harmer
4.418
970659AG2-427 GEN
Solar/Wind Harmer
0.658
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
0.4
3145273HOLLAND
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
1.304
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315737AD1-076 GEN
Solar/Wind Harmer
1.285
971157AH1-035 GEN
Solar/Wind Harmer
0.844
970129AG2-093 GEN
Solar/Wind Harmer
3.791
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.725
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.787
961601AG1-000A GEN
Solar/Wind Harmer
2.655
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.827
316320Y1-086
Solar/Wind Harmer
0.387
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.801
961611AG1-000B GEN
Solar/Wind Harmer
1.383
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.404
3151221GRAVEL6
Adder
4.219
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
315616AA1-038_C
Solar/Wind Helper
0.514
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.895
316321Z2-027
Solar/Wind Harmer
0.178
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
316305AF2-043 C
Solar/Wind Harmer
0.199
313526AB2-022
Solar/Wind Harmer
0.178
316005AA1-067
Solar/Wind Harmer
0.133
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.865
3146406KITTY HAWK
Solar/Wind Harmer
0.005
319010AE1-072 C
Solar/Wind Harmer
1.33
957871AF2-081 GEN
Solar/Wind Harmer
3.284
3152611GOSPORTB
Adder
0.742
3152621GOSPORTC
Adder
0.629
3152601GOSPORTA
Adder
0.581
3151081ELIZAR1
Adder
5.335
3151091ELIZAR2
Adder
5.243
972265AH1-717 GEN
Adder
4.506
3151201GRAVEL4
Adder
4.224
3151191GRAVEL3
Adder
4.17
3151211GRAVEL5
Adder
4.17
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
970937AG2-583 GEN
Solar/Wind Harmer
31.282
316322AB2-045
Solar/Wind Harmer
1.394
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.86
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
963171AG1-166 GEN
Solar/Wind Harmer
2.905
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
18.606
3143226MDLTHAN
Solar/Wind Harmer
-0.015
962491AG1-098 GEN
Solar/Wind Harmer
9.894
315693AD1-088 GEN
Solar/Wind Harmer
7.12
316237AB2-079_GEN
Solar/Wind Harmer
0.427
3143526WINTERP
Solar/Wind Harmer
-0.065
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.362
315687AD1-152 GEN
Solar/Wind Harmer
1.282
971065AG2-659 GEN
Solar/Wind Harmer
5.251
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.904
971795AH1-408 GEN
Solar/Wind Harmer
7.449
3150851SPRUNCC
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.906
960081AF2-299 GEN
Solar/Wind Harmer
0.983
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
970919AG2-571 GEN
Solar/Wind Harmer
2.482
970087AG2-069 GEN
Solar/Wind Harmer
7.326
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.518
940641AE2-051 GEN
Solar/Wind Harmer
6.973
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.551
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
316212AC1-099_GEN
Solar/Wind Harmer
0.635
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.08
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
5.319
970659AG2-427 GEN
Solar/Wind Harmer
3.71
316381AD1-082 GEN
Solar/Wind Harmer
0.639
315722AD1-056 GEN
Solar/Wind Harmer
0.728
970661AG2-428 GEN
Solar/Wind Harmer
7.356
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
970129AG2-093 GEN
Solar/Wind Harmer
1.536
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316458AB2-190 GEN2
Solar/Wind Harmer
0.68
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.303
316359AB2-059 GEN
Solar/Wind Harmer
0.905
316049AB1-081 GEN
Solar/Wind Harmer
0.725
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.951
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
316174AB2-169 GEN
Solar/Wind Harmer
1.029
315800Z1-036_GEN1
Solar/Wind Harmer
1.645
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
971647AH1-324 GEN
Solar/Wind Harmer
3.305
316246AF1-032 C
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.913
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.242
316388AE2-253 GEN
Solar/Wind Harmer
0.443
316375AC2-012 GEN
Solar/Wind Harmer
2.263
3150981CHESPKA
Adder
0.727
3151171GRAVELC
Adder
0.617
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.88
3147666LOUISA
Solar/Wind Helper
0.508
944591AF1-124 GEN
Solar/Wind Harmer
8.419
LAGNLTFEXP_LAGN->PJM
CLTF
1.764
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.055
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.782
MECLTFEXP_MEC->PJM
CLTF
0.452
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.761
TVALTFEXP_TVA->PJM
CLTF
0.87
SIGELTFEXP_SIGE->PJM
CLTF
0.012
NYPJM->LTFIMP_NY
CLTF
0.577
LGEELTFEXP_LGEE->PJM
CLTF
0.104
WECLTFEXP_WEC->PJM
CLTF
0.046
CPLELTFEXP_CPLE->PJM
CLTF
3.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.641

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:163.84 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:1084.23
MW Contribution:28.5
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
5.587
3144293JTRSVLE
50/50
0.823
3151591KERR 2
50/50
0.202
970413AG2-270 GEN
50/50
9.029
966251AG1-494 GEN
50/50
1.716
970221AG2-151 GEN
Solar/Wind Harmer
28.504
3146776BUCKING
Solar/Wind Harmer
0.169
3146926FARMVIL
Solar/Wind Harmer
0.218
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
970909AG2-566 GEN
Solar/Wind Harmer
2.804
3147133PAMPLIN
Solar/Wind Harmer
0.818
971193AH1-056 GEN
Solar/Wind Harmer
15.872
963181AG1-167 GEN
Solar/Wind Harmer
0.975
959311AF2-222 GEN
Solar/Wind Harmer
17.841
970257AG2-171 GEN
Solar/Wind Harmer
6.184
315785AD2-033 C
Solar/Wind Harmer
1.488
958131AF2-107 GEN
Solar/Wind Harmer
4.835
964241AG1-285 GEN
Solar/Wind Harmer
10.382
972205AH1-687 GEN
50/50
27.249
3151611KERR 4
50/50
0.202
3151621KERR 5
50/50
0.202
3151631KERR 6
50/50
0.202
3151641KERR 7
50/50
0.202
3151541CLOVER2
50/50
2.059
971447AH1-217 GEN
Solar/Wind Harmer
15.037
3144293JTRSVLE
50/50
0.823
3144293JTRSVLE
50/50
0.693
970535AG2-341 GEN
50/50
2.047
3152661PLYWOOD A
50/50
0.202
971489AH1-241 GEN
Solar/Wind Harmer
28.504
3146776BUCKING
Solar/Wind Harmer
1.881
3146776BUCKING
Solar/Wind Harmer
0.152
315821AE2-092 GEN
Solar/Wind Harmer
0.02
970301AG2-198 GEN
Solar/Wind Harmer
11.214
3147133PAMPLIN
Solar/Wind Harmer
0.26
3147133PAMPLIN
Solar/Wind Harmer
0.208
958211AF2-115 GEN
Solar/Wind Harmer
2.924
963191AG1-168 GEN
Solar/Wind Harmer
0.975
971741AH1-377 GEN
Solar/Wind Harmer
22.982
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.246
971775AH1-396 GEN
Solar/Wind Harmer
0.309
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
5.277
964791AG1-342 GEN
Solar/Wind Harmer
2.024
3146843MT LREL
Solar/Wind Harmer
0.105
3146843MT LREL
Solar/Wind Harmer
0.105
939181AE1-148 GEN
Solar/Wind Harmer
5.007
970099AG2-077 GEN
Solar/Wind Harmer
9.999
970933AG2-581 GEN
Solar/Wind Harmer
5.154
942751AE2-291 GEN
Solar/Wind Harmer
3.374
966001AG1-469 GEN
Solar/Wind Helper
0.159
316131AB2-060 GEN
Solar/Wind Harmer
0.438
316478AD1-087 GEN
Solar/Wind Harmer
0.337
316486AD2-202 GEN
Solar/Wind Harmer
0.099
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.582
3147043LAWRENC
Solar/Wind Harmer
0.049
971683AH1-343 GEN
Solar/Wind Harmer
2.828
3132273ORANGE
Solar/Wind Helper
0.023
3151931BEARGRDN S1
50/50
7.21
3151911BEARGRDN G1
50/50
5.587
3144293JTRSVLE
50/50
0.823
3151601KERR 3
50/50
0.202
3151581KERR 1
50/50
0.072
3151531CLOVER1
50/50
2.069
3147043LAWRENC
50/50
0.777
970937AG2-583 GEN
Solar/Wind Harmer
36.866
316336AC2-165 C
Solar/Wind Harmer
0.024
972003AH1-546 GEN
Solar/Wind Harmer
24.522
971377AH1-170 GEN
Solar/Wind Harmer
5.701
3147623JAMES R
Solar/Wind Harmer
1.238
316322AB2-045
Solar/Wind Harmer
0.004
3146776BUCKING
Solar/Wind Harmer
0.188
3146926FARMVIL
Solar/Wind Harmer
0.218
963171AG1-166 GEN
Solar/Wind Harmer
1.299
971563AH1-280 GEN
Solar/Wind Harmer
2.599
970685AG2-442 GEN
Solar/Wind Harmer
16.367
962491AG1-098 GEN
Solar/Wind Harmer
7.651
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
6.098
970401AG2-262 GEN
Solar/Wind Harmer
0.618
957481AF2-042 GEN
Solar/Wind Harmer
24.997
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.611
316129AC1-054 GEN
Solar/Wind Harmer
0.309
316003AC1-222 GEN
Solar/Wind Harmer
0.002
971795AH1-408 GEN
Solar/Wind Harmer
4.899
962751AG1-124 GEN
Solar/Wind Harmer
3.147
960081AF2-299 GEN
Solar/Wind Harmer
0.55
971845AH1-439 GEN
Solar/Wind Harmer
20.916
970285AG2-188 GEN
Solar/Wind Harmer
35.131
270494AE1-108_GEN
Solar/Wind Harmer
5.032
315657AE1-056 GEN
Solar/Wind Harmer
8.99
946301AF1-294 GEN
Solar/Wind Harmer
4.808
961791AG1-021 GEN
Solar/Wind Harmer
2.339
970683AG2-441 GEN
Solar/Wind Harmer
14.613
970681AG2-440 GEN
Solar/Wind Harmer
11.691
3144303KENBRDG
Solar/Wind Harmer
0.154
971443AH1-215 GEN
Solar/Wind Harmer
3.209
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.244
3147173SINAI
Solar/Wind Harmer
0.084
3147243WELCO
Solar/Wind Harmer
0.052
970831AG2-522 GEN
Solar/Wind Harmer
3.381
970865AG2-541 GEN
Solar/Wind Harmer
2.545
316123AC1-075 GEN
Solar/Wind Harmer
0.091
970165AG2-112 GEN
Solar/Wind Harmer
0.539
970163AG2-111 GEN
Solar/Wind Harmer
0.514
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
LAGNLTFEXP_LAGN->PJM
CLTF
1.554
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.084
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.539
MECLTFEXP_MEC->PJM
CLTF
0.508
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.128
TVALTFEXP_TVA->PJM
CLTF
0.776
NYPJM->LTFIMP_NY
CLTF
0.525
LGEELTFEXP_LGEE->PJM
CLTF
0.153
WECLTFEXP_WEC->PJM
CLTF
0.071
CPLELTFEXP_CPLE->PJM
CLTF
2.979
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.201

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 242T2027_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 242T2027_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.93 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1253.38
MW Contribution:37.53
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
27.249
971447AH1-217 GEN
Solar/Wind Harmer
19.799
971845AH1-439 GEN
Solar/Wind Harmer
27.54
970285AG2-188 GEN
Solar/Wind Harmer
43.657
270494AE1-108_GEN
Solar/Wind Harmer
12.267
315657AE1-056 GEN
Solar/Wind Harmer
10.983
946301AF1-294 GEN
Solar/Wind Harmer
7.014
961791AG1-021 GEN
Solar/Wind Harmer
3.422
970683AG2-441 GEN
Solar/Wind Harmer
19.241
970681AG2-440 GEN
Solar/Wind Harmer
15.393
3144303KENBRDG
Solar/Wind Harmer
-0.017
971443AH1-215 GEN
Solar/Wind Harmer
4.225
316239AB2-077_GEN
Solar/Wind Harmer
0.446
316238AB2-078_GEN
Solar/Wind Harmer
0.446
316118AC1-105 GEN
Solar/Wind Harmer
0.73
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
970831AG2-522 GEN
Solar/Wind Harmer
4.452
970865AG2-541 GEN
Solar/Wind Harmer
3.351
316123AC1-075 GEN
Solar/Wind Harmer
0.806
970165AG2-112 GEN
Solar/Wind Harmer
0.709
970163AG2-111 GEN
Solar/Wind Harmer
0.677
946281AF1-292 GEN
Solar/Wind Harmer
0.144
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
3151931BEARGRDN S1
50/50
7.21
3151911BEARGRDN G1
50/50
5.587
3144293JTRSVLE
50/50
0.823
970937AG2-583 GEN
Solar/Wind Harmer
48.541
316336AC2-165 C
Solar/Wind Harmer
11.736
972003AH1-546 GEN
Solar/Wind Harmer
32.342
971377AH1-170 GEN
Solar/Wind Harmer
7.506
3147623JAMES R
Solar/Wind Harmer
0.929
316322AB2-045
Solar/Wind Harmer
1.778
3146776BUCKING
Solar/Wind Harmer
-0.021
3146926FARMVIL
Solar/Wind Harmer
-0.024
963171AG1-166 GEN
Solar/Wind Harmer
3.422
971563AH1-280 GEN
Solar/Wind Harmer
3.422
970685AG2-442 GEN
Solar/Wind Harmer
21.55
962491AG1-098 GEN
Solar/Wind Harmer
10.074
316237AB2-079_GEN
Solar/Wind Harmer
0.446
315693AD1-088 GEN
Solar/Wind Harmer
7.137
970401AG2-262 GEN
Solar/Wind Harmer
0.773
957481AF2-042 GEN
Solar/Wind Harmer
32.913
315687AD1-152 GEN
Solar/Wind Harmer
1.189
971065AG2-659 GEN
Solar/Wind Harmer
4.755
316129AC1-054 GEN
Solar/Wind Harmer
0.808
3147043LAWRENC
Adder
0.732
316003AC1-222 GEN
Solar/Wind Harmer
0.879
971795AH1-408 GEN
Solar/Wind Harmer
6.192
962751AG1-124 GEN
Solar/Wind Harmer
4.595
960081AF2-299 GEN
Solar/Wind Harmer
0.724
3151921BEARGRDN G2
50/50
5.587
3144293JTRSVLE
50/50
0.823
970221AG2-151 GEN
Solar/Wind Harmer
37.53
3146776BUCKING
Solar/Wind Harmer
-0.019
3146926FARMVIL
Solar/Wind Harmer
-0.024
942461AE2-259 GEN
Solar/Wind Harmer
5.218
970909AG2-566 GEN
Solar/Wind Harmer
2.804
3147133PAMPLIN
Solar/Wind Harmer
-0.092
971193AH1-056 GEN
Solar/Wind Harmer
18.305
963181AG1-167 GEN
Solar/Wind Harmer
2.566
959311AF2-222 GEN
Solar/Wind Harmer
23.538
970257AG2-171 GEN
Solar/Wind Harmer
8.143
315785AD2-033 C
Solar/Wind Harmer
4.66
958131AF2-107 GEN
Solar/Wind Harmer
6.437
964241AG1-285 GEN
Solar/Wind Harmer
13.669
316131AB2-060 GEN
Solar/Wind Harmer
1.687
316478AD1-087 GEN
Solar/Wind Harmer
0.939
316486AD2-202 GEN
Solar/Wind Harmer
0.275
316248AF1-058 C
Solar/Wind Harmer
0.284
960061AF2-297 GEN
Solar/Wind Harmer
4.717
3147043LAWRENC
Solar/Wind Harmer
-0.005
971683AH1-343 GEN
Solar/Wind Harmer
3.724
966621AG1-532 GEN
Solar/Wind Harmer
0.131
3132273ORANGE
Solar/Wind Helper
0.023
3144293JTRSVLE
50/50
0.823
3144293JTRSVLE
50/50
0.693
970535AG2-341 GEN
50/50
2.047
971489AH1-241 GEN
Solar/Wind Harmer
35.629
3146776BUCKING
Solar/Wind Harmer
-0.21
3146776BUCKING
Solar/Wind Harmer
-0.017
315821AE2-092 GEN
Solar/Wind Harmer
7.77
970301AG2-198 GEN
Solar/Wind Harmer
14.765
3147133PAMPLIN
Solar/Wind Harmer
-0.029
3147133PAMPLIN
Solar/Wind Harmer
-0.023
958211AF2-115 GEN
Solar/Wind Harmer
4.277
963191AG1-168 GEN
Solar/Wind Harmer
2.566
971741AH1-377 GEN
Solar/Wind Harmer
30.26
316034AC1-036 C
Solar/Wind Harmer
0.404
970323AG2-213 GEN
Solar/Wind Harmer
10.857
971775AH1-396 GEN
Solar/Wind Harmer
1.546
313527AB2-043 GEN
Solar/Wind Harmer
2.466
962561AG1-105 GEN
Solar/Wind Harmer
6.948
964791AG1-342 GEN
Solar/Wind Harmer
2.529
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
939181AE1-148 GEN
Solar/Wind Harmer
6.592
970099AG2-077 GEN
Solar/Wind Harmer
13.165
970933AG2-581 GEN
Solar/Wind Harmer
6.786
942751AE2-291 GEN
Solar/Wind Harmer
4.443
966001AG1-469 GEN
Solar/Wind Helper
0.159
LAGNLTFEXP_LAGN->PJM
CLTF
1.554
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.084
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.539
MECLTFEXP_MEC->PJM
CLTF
0.508
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.128
TVALTFEXP_TVA->PJM
CLTF
0.776
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.525
LGEELTFEXP_LGEE->PJM
CLTF
0.153
WECLTFEXP_WEC->PJM
CLTF
0.071
CPLELTFEXP_CPLE->PJM
CLTF
2.979
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.201

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 39-91_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 39-91_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:120.29 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:973.17
MW Contribution:32.43
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.697
3144293JTRSVLE
50/50
0.587
971489AH1-241 GEN
Solar/Wind Harmer
30.786
3146776BUCKING
Solar/Wind Harmer
-0.17
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.481
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.621
963191AG1-168 GEN
Solar/Wind Harmer
2.173
971741AH1-377 GEN
Solar/Wind Harmer
25.942
316034AC1-036 C
Solar/Wind Harmer
0.35
970323AG2-213 GEN
Solar/Wind Harmer
9.416
971775AH1-396 GEN
Solar/Wind Harmer
1.341
313527AB2-043 GEN
Solar/Wind Harmer
2.245
962561AG1-105 GEN
Solar/Wind Harmer
6.444
939181AE1-148 GEN
Solar/Wind Harmer
6.287
964791AG1-342 GEN
Solar/Wind Harmer
2.356
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.272
971223AH1-071 GEN
Solar/Wind Harmer
1.326
3143526WINTERP
Solar/Wind Harmer
-0.046
970933AG2-581 GEN
Solar/Wind Harmer
7.828
316181AB2-040 GEN
Solar/Wind Harmer
1.022
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.794
3145593CAROLNA
Solar/Wind Harmer
0.059
3145783HORNRTN
Solar/Wind Harmer
0.823
3145783HORNRTN
Solar/Wind Harmer
0.658
3145783HORNRTN
Solar/Wind Harmer
0.206
3145783HORNRTN
Solar/Wind Harmer
0.082
316426AA2-053 GEN
Solar/Wind Harmer
0.692
972187AH1-678 GEN
Adder
1.699
972185AH1-677 GEN
Adder
3.299
966001AG1-469 GEN
Solar/Wind Helper
0.187
3132123MT JACKSON
Solar/Wind Helper
0.368
972205AH1-687 GEN
50/50
21.692
971447AH1-217 GEN
Solar/Wind Harmer
18.622
971845AH1-439 GEN
Solar/Wind Harmer
22.237
270494AE1-108_GEN
Solar/Wind Harmer
10.551
970285AG2-188 GEN
Solar/Wind Harmer
35.335
315657AE1-056 GEN
Solar/Wind Harmer
9.243
946301AF1-294 GEN
Solar/Wind Harmer
5.939
961791AG1-021 GEN
Solar/Wind Harmer
2.897
970683AG2-441 GEN
Solar/Wind Harmer
16.461
970681AG2-440 GEN
Solar/Wind Harmer
13.169
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.67
316239AB2-077_GEN
Solar/Wind Harmer
0.407
316238AB2-078_GEN
Solar/Wind Harmer
0.407
316118AC1-105 GEN
Solar/Wind Harmer
0.689
970831AG2-522 GEN
Solar/Wind Harmer
4.571
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
316233AE1-074 FULL
Solar/Wind Harmer
0.238
971281AH1-106 GEN
Solar/Wind Harmer
1.438
971283AH1-107 GEN
Solar/Wind Harmer
1.438
970865AG2-541 GEN
Solar/Wind Harmer
3.115
946281AF1-292 GEN
Solar/Wind Harmer
0.169
316087AB2-174 GEN
Solar/Wind Harmer
1.055
971967AH1-528 GEN
Solar/Wind Harmer
13.769
3137643SOCKMAN
Solar/Wind Harmer
-0.029
316123AC1-075 GEN
Solar/Wind Harmer
0.731
970165AG2-112 GEN
Solar/Wind Harmer
0.643
970163AG2-111 GEN
Solar/Wind Harmer
0.614
315607AA1-063A GEN
Solar/Wind Harmer
0.681
971285AH1-108 GEN
Adder
0.449
3146043SEABORD
Solar/Wind Harmer
-0.007
970673AG2-436 GEN
Solar/Wind Harmer
13.72
970673AG2-436 GEN
Solar/Wind Harmer
6.947
970085AG2-068 GEN
Solar/Wind Harmer
4.042
970581AG2-369 GEN
Solar/Wind Harmer
3.477
941031AE2-094 GEN
Solar/Wind Harmer
11.972
944011AF1-069 GEN
Solar/Wind Harmer
3.751
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.132
3148013FISHERV
Solar/Wind Helper
0.127
3148463FAIRFLD
Solar/Wind Helper
0.134
3151931BEARGRDN S1
50/50
5.74
3151911BEARGRDN G1
50/50
4.448
3144293JTRSVLE
50/50
0.697
971377AH1-170 GEN
Solar/Wind Harmer
6.486
3147623JAMES R
Solar/Wind Harmer
0.803
972003AH1-546 GEN
Solar/Wind Harmer
25.797
970937AG2-583 GEN
Solar/Wind Harmer
31.587
316322AB2-045
Solar/Wind Harmer
1.434
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.02
316336AC2-165 C
Solar/Wind Harmer
5.623
3143336POWHATN
Solar/Wind Harmer
3.304
963171AG1-166 GEN
Solar/Wind Harmer
2.897
971563AH1-280 GEN
Solar/Wind Harmer
2.897
970685AG2-442 GEN
Solar/Wind Harmer
18.436
962491AG1-098 GEN
Solar/Wind Harmer
9.378
316237AB2-079_GEN
Solar/Wind Harmer
0.407
315693AD1-088 GEN
Solar/Wind Harmer
6.713
970401AG2-262 GEN
Solar/Wind Harmer
0.72
957481AF2-042 GEN
Solar/Wind Harmer
33.181
3143226MDLTHAN
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
1.173
971065AG2-659 GEN
Solar/Wind Harmer
4.785
3147043LAWRENC
Adder
0.762
316129AC1-054 GEN
Solar/Wind Harmer
0.821
971795AH1-408 GEN
Solar/Wind Harmer
6.648
3143526WINTERP
Solar/Wind Harmer
-0.046
316003AC1-222 GEN
Solar/Wind Harmer
0.833
960081AF2-299 GEN
Solar/Wind Harmer
0.851
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.084
3150851SPRUNCC
Adder
0.274
970919AG2-571 GEN
Solar/Wind Harmer
2.054
970087AG2-069 GEN
Solar/Wind Harmer
6.064
316023GEN1_S
Solar/Wind Harmer
0.43
3147983MERCK5
Solar/Wind Helper
0.062
3151921BEARGRDN G2
50/50
4.448
3144293JTRSVLE
50/50
0.697
970221AG2-151 GEN
Solar/Wind Harmer
32.428
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
942461AE2-259 GEN
Solar/Wind Harmer
4.331
316313AB2-026
Solar/Wind Harmer
0.751
316258AE1-075 C
Solar/Wind Harmer
0.676
316405AF2-144 C
Solar/Wind Harmer
0.713
3143336POWHATN
Solar/Wind Harmer
2.809
970909AG2-566 GEN
Solar/Wind Harmer
2.37
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.405
963181AG1-167 GEN
Solar/Wind Harmer
2.173
959311AF2-222 GEN
Solar/Wind Harmer
20.328
970257AG2-171 GEN
Solar/Wind Harmer
7.062
315785AD2-033 C
Solar/Wind Harmer
4.068
958131AF2-107 GEN
Solar/Wind Harmer
5.359
964241AG1-285 GEN
Solar/Wind Harmer
12.184
316131AB2-060 GEN
Solar/Wind Harmer
1.528
316478AD1-087 GEN
Solar/Wind Harmer
0.928
316486AD2-202 GEN
Solar/Wind Harmer
0.272
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.272
960061AF2-297 GEN
Solar/Wind Harmer
4.511
971683AH1-343 GEN
Solar/Wind Harmer
3.497
966621AG1-532 GEN
Solar/Wind Harmer
0.153
313506AB2-031 GEN
Solar/Wind Harmer
0.589
3150861SPRUNCD
Adder
0.274
970917AG2-570 GEN
Solar/Wind Harmer
16.228
316365GEN2_N
Solar/Wind Harmer
0.43
3148013FISHERV
Solar/Wind Helper
0.221
316499AE2-029_GEN
Solar/Wind Helper
0.571
315616AA1-038_C
Solar/Wind Helper
0.608
3132273ORANGE
Solar/Wind Helper
0.026
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.035
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.087
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.798
MECLTFEXP_MEC->PJM
CLTF
0.142
LAGNLTFEXP_LAGN->PJM
CLTF
1.208
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.305
TVALTFEXP_TVA->PJM
CLTF
0.589
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CPLELTFEXP_CPLE->PJM
CLTF
3.247
NYPJM->LTFIMP_NY
CLTF
0.409
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.539

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P2-2: DOOMS B2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: DOOMS B2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:118.3 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:957.01
MW Contribution:32.4
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.696
3144293JTRSVLE
50/50
0.586
315821AE2-092 GEN
Solar/Wind Harmer
10.863
971489AH1-241 GEN
Solar/Wind Harmer
30.763
3146776BUCKING
Solar/Wind Harmer
-0.17
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.465
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3151931BEARGRDN S1
50/50
5.736
3151911BEARGRDN G1
50/50
4.444
3144293JTRSVLE
50/50
0.696
971377AH1-170 GEN
Solar/Wind Harmer
6.481
3147623JAMES R
Solar/Wind Harmer
0.802
972003AH1-546 GEN
Solar/Wind Harmer
25.777
970937AG2-583 GEN
Solar/Wind Harmer
31.56
316322AB2-045
Solar/Wind Harmer
1.433
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.02
316336AC2-165 C
Solar/Wind Harmer
5.617
3143336POWHATN
Solar/Wind Harmer
3.3
963171AG1-166 GEN
Solar/Wind Harmer
2.893
971563AH1-280 GEN
Solar/Wind Harmer
2.893
970685AG2-442 GEN
Solar/Wind Harmer
18.409
962491AG1-098 GEN
Solar/Wind Harmer
9.357
316237AB2-079_GEN
Solar/Wind Harmer
0.406
315693AD1-088 GEN
Solar/Wind Harmer
6.698
970401AG2-262 GEN
Solar/Wind Harmer
0.718
957481AF2-042 GEN
Solar/Wind Harmer
33.088
3143226MDLTHAN
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
1.169
3151921BEARGRDN G2
50/50
4.444
3144293JTRSVLE
50/50
0.696
970221AG2-151 GEN
Solar/Wind Harmer
32.404
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
942461AE2-259 GEN
Solar/Wind Harmer
4.326
316313AB2-026
Solar/Wind Harmer
0.75
316258AE1-075 C
Solar/Wind Harmer
0.675
316405AF2-144 C
Solar/Wind Harmer
0.712
3143336POWHATN
Solar/Wind Harmer
2.805
970909AG2-566 GEN
Solar/Wind Harmer
2.367
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.384
963181AG1-167 GEN
Solar/Wind Harmer
2.17
959311AF2-222 GEN
Solar/Wind Harmer
20.295
970257AG2-171 GEN
Solar/Wind Harmer
7.05
315785AD2-033 C
Solar/Wind Harmer
4.061
958131AF2-107 GEN
Solar/Wind Harmer
5.349
964241AG1-285 GEN
Solar/Wind Harmer
12.16
316131AB2-060 GEN
Solar/Wind Harmer
1.525
316478AD1-087 GEN
Solar/Wind Harmer
0.925
316486AD2-202 GEN
Solar/Wind Harmer
0.271
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.271
960061AF2-297 GEN
Solar/Wind Harmer
4.496
971683AH1-343 GEN
Solar/Wind Harmer
3.484
966621AG1-532 GEN
Solar/Wind Harmer
0.153
313506AB2-031 GEN
Solar/Wind Harmer
0.586
3150861SPRUNCD
Adder
0.273
970917AG2-570 GEN
Solar/Wind Harmer
16.156
316365GEN2_N
Solar/Wind Harmer
0.428
3148013FISHERV
Solar/Wind Helper
0.227
316499AE2-029_GEN
Solar/Wind Helper
0.572
315616AA1-038_C
Solar/Wind Helper
0.611
3132273ORANGE
Solar/Wind Helper
0.026
972205AH1-687 GEN
50/50
21.676
971447AH1-217 GEN
Solar/Wind Harmer
18.608
971845AH1-439 GEN
Solar/Wind Harmer
22.218
270494AE1-108_GEN
Solar/Wind Harmer
10.541
970285AG2-188 GEN
Solar/Wind Harmer
35.303
315657AE1-056 GEN
Solar/Wind Harmer
9.23
946301AF1-294 GEN
Solar/Wind Harmer
5.931
961791AG1-021 GEN
Solar/Wind Harmer
2.893
970683AG2-441 GEN
Solar/Wind Harmer
16.436
970681AG2-440 GEN
Solar/Wind Harmer
13.149
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.664
316239AB2-077_GEN
Solar/Wind Harmer
0.406
316238AB2-078_GEN
Solar/Wind Harmer
0.406
316118AC1-105 GEN
Solar/Wind Harmer
0.687
970831AG2-522 GEN
Solar/Wind Harmer
4.556
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
316233AE1-074 FULL
Solar/Wind Harmer
0.237
971281AH1-106 GEN
Solar/Wind Harmer
1.433
971283AH1-107 GEN
Solar/Wind Harmer
1.433
970865AG2-541 GEN
Solar/Wind Harmer
3.104
946281AF1-292 GEN
Solar/Wind Harmer
0.169
316087AB2-174 GEN
Solar/Wind Harmer
1.051
971967AH1-528 GEN
Solar/Wind Harmer
13.715
3137643SOCKMAN
Solar/Wind Harmer
-0.028
316123AC1-075 GEN
Solar/Wind Harmer
0.728
970165AG2-112 GEN
Solar/Wind Harmer
0.641
970163AG2-111 GEN
Solar/Wind Harmer
0.611
315607AA1-063A GEN
Solar/Wind Harmer
0.678
971285AH1-108 GEN
Adder
0.447
3146043SEABORD
Solar/Wind Harmer
-0.007
970673AG2-436 GEN
Solar/Wind Harmer
13.659
970673AG2-436 GEN
Solar/Wind Harmer
6.916
970085AG2-068 GEN
Solar/Wind Harmer
4.024
970581AG2-369 GEN
Solar/Wind Harmer
3.461
941031AE2-094 GEN
Solar/Wind Harmer
11.918
944011AF1-069 GEN
Solar/Wind Harmer
3.734
3138266HYDRAULIC
Solar/Wind Helper
0.021
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.136
3148013FISHERV
Solar/Wind Helper
0.13
3148463FAIRFLD
Solar/Wind Helper
0.135
971065AG2-659 GEN
Solar/Wind Harmer
4.77
3147043LAWRENC
Adder
0.76
316129AC1-054 GEN
Solar/Wind Harmer
0.818
971795AH1-408 GEN
Solar/Wind Harmer
6.626
3143526WINTERP
Solar/Wind Harmer
-0.046
316003AC1-222 GEN
Solar/Wind Harmer
0.83
960081AF2-299 GEN
Solar/Wind Harmer
0.847
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.084
3150851SPRUNCC
Adder
0.273
970919AG2-571 GEN
Solar/Wind Harmer
2.045
970087AG2-069 GEN
Solar/Wind Harmer
6.037
316023GEN1_S
Solar/Wind Harmer
0.428
3147983MERCK5
Solar/Wind Helper
0.063
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.616
963191AG1-168 GEN
Solar/Wind Harmer
2.17
971741AH1-377 GEN
Solar/Wind Harmer
25.905
316034AC1-036 C
Solar/Wind Harmer
0.349
970323AG2-213 GEN
Solar/Wind Harmer
9.401
971775AH1-396 GEN
Solar/Wind Harmer
1.339
313527AB2-043 GEN
Solar/Wind Harmer
2.24
962561AG1-105 GEN
Solar/Wind Harmer
6.427
939181AE1-148 GEN
Solar/Wind Harmer
6.27
964791AG1-342 GEN
Solar/Wind Harmer
2.35
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.235
971223AH1-071 GEN
Solar/Wind Harmer
1.322
3143526WINTERP
Solar/Wind Harmer
-0.046
970933AG2-581 GEN
Solar/Wind Harmer
7.8
316181AB2-040 GEN
Solar/Wind Harmer
1.018
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.791
3145593CAROLNA
Solar/Wind Harmer
0.058
3145783HORNRTN
Solar/Wind Harmer
0.819
3145783HORNRTN
Solar/Wind Harmer
0.655
3145783HORNRTN
Solar/Wind Harmer
0.205
3145783HORNRTN
Solar/Wind Harmer
0.082
316426AA2-053 GEN
Solar/Wind Harmer
0.689
972187AH1-678 GEN
Adder
1.691
972185AH1-677 GEN
Adder
3.285
966001AG1-469 GEN
Solar/Wind Helper
0.188
3132123MT JACKSON
Solar/Wind Helper
0.367
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.046
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.122
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.731
MECLTFEXP_MEC->PJM
CLTF
0.113
LAGNLTFEXP_LAGN->PJM
CLTF
1.172
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.249
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.571
SIGELTFEXP_SIGE->PJM
CLTF
0.001
CPLELTFEXP_CPLE->PJM
CLTF
3.227
NYPJM->LTFIMP_NY
CLTF
0.42
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.302

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:113.29 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:916.48
MW Contribution:27.74
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.655
3144293JTRSVLE
50/50
0.551
971489AH1-241 GEN
Solar/Wind Harmer
26.337
3146776BUCKING
Solar/Wind Harmer
-0.158
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.386
970301AG2-198 GEN
Solar/Wind Harmer
11.705
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.404
963191AG1-168 GEN
Solar/Wind Harmer
2.042
971741AH1-377 GEN
Solar/Wind Harmer
24.381
316034AC1-036 C
Solar/Wind Harmer
0.331
970323AG2-213 GEN
Solar/Wind Harmer
8.895
971775AH1-396 GEN
Solar/Wind Harmer
1.267
313527AB2-043 GEN
Solar/Wind Harmer
2.141
962561AG1-105 GEN
Solar/Wind Harmer
6.187
939181AE1-148 GEN
Solar/Wind Harmer
6.061
964791AG1-342 GEN
Solar/Wind Harmer
2.266
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
12.748
971223AH1-071 GEN
Solar/Wind Harmer
1.248
3143526WINTERP
Solar/Wind Harmer
-0.043
970933AG2-581 GEN
Solar/Wind Harmer
7.571
316181AB2-040 GEN
Solar/Wind Harmer
1.004
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.784
3145593CAROLNA
Solar/Wind Harmer
0.058
3145783HORNRTN
Solar/Wind Harmer
0.814
3145783HORNRTN
Solar/Wind Harmer
0.651
3145783HORNRTN
Solar/Wind Harmer
0.204
3145783HORNRTN
Solar/Wind Harmer
0.081
316426AA2-053 GEN
Solar/Wind Harmer
0.684
972187AH1-678 GEN
Adder
1.664
972185AH1-677 GEN
Adder
3.229
966001AG1-469 GEN
Solar/Wind Helper
0.189
972205AH1-687 GEN
50/50
20.143
971447AH1-217 GEN
Solar/Wind Harmer
14.529
971845AH1-439 GEN
Solar/Wind Harmer
20.7
970285AG2-188 GEN
Solar/Wind Harmer
32.906
270494AE1-108_GEN
Solar/Wind Harmer
9.015
315657AE1-056 GEN
Solar/Wind Harmer
8.675
946301AF1-294 GEN
Solar/Wind Harmer
5.582
961791AG1-021 GEN
Solar/Wind Harmer
2.723
970683AG2-441 GEN
Solar/Wind Harmer
15.505
970681AG2-440 GEN
Solar/Wind Harmer
12.404
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.467
316239AB2-077_GEN
Solar/Wind Harmer
0.389
316238AB2-078_GEN
Solar/Wind Harmer
0.389
316118AC1-105 GEN
Solar/Wind Harmer
0.665
970831AG2-522 GEN
Solar/Wind Harmer
4.449
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
316233AE1-074 FULL
Solar/Wind Harmer
0.225
971281AH1-106 GEN
Solar/Wind Harmer
1.359
971283AH1-107 GEN
Solar/Wind Harmer
1.359
946281AF1-292 GEN
Solar/Wind Harmer
0.166
970865AG2-541 GEN
Solar/Wind Harmer
2.988
316087AB2-174 GEN
Solar/Wind Harmer
1.035
971967AH1-528 GEN
Solar/Wind Harmer
13.383
3137643SOCKMAN
Solar/Wind Harmer
-0.028
315607AA1-063A GEN
Solar/Wind Harmer
0.672
3146043SEABORD
Solar/Wind Harmer
-0.007
316123AC1-075 GEN
Solar/Wind Harmer
0.694
970165AG2-112 GEN
Solar/Wind Harmer
0.611
970163AG2-111 GEN
Solar/Wind Harmer
0.583
970085AG2-068 GEN
Solar/Wind Harmer
4
970581AG2-369 GEN
Solar/Wind Harmer
3.44
970673AG2-436 GEN
Solar/Wind Harmer
13.415
970673AG2-436 GEN
Solar/Wind Harmer
6.792
971285AH1-108 GEN
Adder
0.428
3138266HYDRAULIC
Solar/Wind Helper
0.021
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.08
3148013FISHERV
Solar/Wind Helper
0.077
3148463FAIRFLD
Solar/Wind Helper
0.12
3151931BEARGRDN S1
50/50
5.33
3151911BEARGRDN G1
50/50
4.13
3144293JTRSVLE
50/50
0.655
972003AH1-546 GEN
Solar/Wind Harmer
23.962
971377AH1-170 GEN
Solar/Wind Harmer
5.548
3147623JAMES R
Solar/Wind Harmer
0.687
970937AG2-583 GEN
Solar/Wind Harmer
29.352
316322AB2-045
Solar/Wind Harmer
1.334
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.233
3143336POWHATN
Solar/Wind Harmer
3.078
963171AG1-166 GEN
Solar/Wind Harmer
2.723
971563AH1-280 GEN
Solar/Wind Harmer
2.723
970685AG2-442 GEN
Solar/Wind Harmer
17.365
962491AG1-098 GEN
Solar/Wind Harmer
8.919
316237AB2-079_GEN
Solar/Wind Harmer
0.389
315693AD1-088 GEN
Solar/Wind Harmer
6.394
970401AG2-262 GEN
Solar/Wind Harmer
0.692
957481AF2-042 GEN
Solar/Wind Harmer
31.87
3143226MDLTHAN
Solar/Wind Harmer
-0.01
315687AD1-152 GEN
Solar/Wind Harmer
1.137
971065AG2-659 GEN
Solar/Wind Harmer
4.648
3147043LAWRENC
Adder
0.737
316129AC1-054 GEN
Solar/Wind Harmer
0.798
971795AH1-408 GEN
Solar/Wind Harmer
6.453
3143526WINTERP
Solar/Wind Harmer
-0.043
316003AC1-222 GEN
Solar/Wind Harmer
0.805
960081AF2-299 GEN
Solar/Wind Harmer
0.832
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.083
970919AG2-571 GEN
Solar/Wind Harmer
2.03
970087AG2-069 GEN
Solar/Wind Harmer
6
3150851SPRUNCC
Adder
0.261
3147983MERCK5
Solar/Wind Helper
0.055
3151921BEARGRDN G2
50/50
4.13
3144293JTRSVLE
50/50
0.655
970221AG2-151 GEN
Solar/Wind Harmer
27.742
3146776BUCKING
Solar/Wind Harmer
-0.014
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.053
316313AB2-026
Solar/Wind Harmer
0.699
316258AE1-075 C
Solar/Wind Harmer
0.63
316405AF2-144 C
Solar/Wind Harmer
0.664
3143336POWHATN
Solar/Wind Harmer
2.616
970909AG2-566 GEN
Solar/Wind Harmer
2.223
3147133PAMPLIN
Solar/Wind Harmer
-0.072
971193AH1-056 GEN
Solar/Wind Harmer
14.459
963181AG1-167 GEN
Solar/Wind Harmer
2.042
959311AF2-222 GEN
Solar/Wind Harmer
19.185
970257AG2-171 GEN
Solar/Wind Harmer
6.671
315785AD2-033 C
Solar/Wind Harmer
3.847
964241AG1-285 GEN
Solar/Wind Harmer
11.573
316131AB2-060 GEN
Solar/Wind Harmer
1.457
958131AF2-107 GEN
Solar/Wind Harmer
4.54
316478AD1-087 GEN
Solar/Wind Harmer
0.893
316486AD2-202 GEN
Solar/Wind Harmer
0.261
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.264
960061AF2-297 GEN
Solar/Wind Harmer
4.376
971683AH1-343 GEN
Solar/Wind Harmer
3.368
966621AG1-532 GEN
Solar/Wind Harmer
0.15
313506AB2-031 GEN
Solar/Wind Harmer
0.578
970917AG2-570 GEN
Solar/Wind Harmer
16.041
3150861SPRUNCD
Adder
0.261
316499AE2-029_GEN
Solar/Wind Helper
0.505
3148013FISHERV
Solar/Wind Helper
0.133
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.545
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.045
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.115
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.309
MECLTFEXP_MEC->PJM
CLTF
0.208
LAGNLTFEXP_LAGN->PJM
CLTF
1.574
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.039
TVALTFEXP_TVA->PJM
CLTF
0.757
SIGELTFEXP_SIGE->PJM
CLTF
0.003
CPLELTFEXP_CPLE->PJM
CLTF
3.638
NYPJM->LTFIMP_NY
CLTF
0.389
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.961

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2066-282_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2066-282_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:109.2 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:883.46
MW Contribution:28.17
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.192
3144293JTRSVLE
50/50
0.653
970221AG2-151 GEN
Solar/Wind Harmer
28.166
3146776BUCKING
Solar/Wind Harmer
-0.014
3146926FARMVIL
Solar/Wind Harmer
-0.019
316313AB2-026
Solar/Wind Harmer
0.752
316258AE1-075 C
Solar/Wind Harmer
0.677
316405AF2-144 C
Solar/Wind Harmer
0.714
3143336POWHATN
Solar/Wind Harmer
2.812
942461AE2-259 GEN
Solar/Wind Harmer
4.067
970909AG2-566 GEN
Solar/Wind Harmer
2.224
3147133PAMPLIN
Solar/Wind Harmer
-0.072
3151931BEARGRDN S1
50/50
5.41
3151911BEARGRDN G1
50/50
4.192
3144293JTRSVLE
50/50
0.653
970119AG2-088 GEN
50/50
15.082
972003AH1-546 GEN
Solar/Wind Harmer
24.312
971377AH1-170 GEN
Solar/Wind Harmer
5.633
3147623JAMES R
Solar/Wind Harmer
0.697
970937AG2-583 GEN
Solar/Wind Harmer
30.216
316322AB2-045
Solar/Wind Harmer
1.35
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.534
3146926FARMVIL
Solar/Wind Harmer
-0.019
3143336POWHATN
Solar/Wind Harmer
3.308
963171AG1-166 GEN
Solar/Wind Harmer
2.715
971563AH1-280 GEN
Solar/Wind Harmer
2.715
970685AG2-442 GEN
Solar/Wind Harmer
17.259
962491AG1-098 GEN
Solar/Wind Harmer
8.747
3143226MDLTHAN
Solar/Wind Harmer
-0.013
316237AB2-079_GEN
Solar/Wind Harmer
0.378
315693AD1-088 GEN
Solar/Wind Harmer
6.258
970401AG2-262 GEN
Solar/Wind Harmer
0.669
957481AF2-042 GEN
Solar/Wind Harmer
30.813
315687AD1-152 GEN
Solar/Wind Harmer
1.088
971065AG2-659 GEN
Solar/Wind Harmer
4.397
3147043LAWRENC
Adder
0.694
316129AC1-054 GEN
Solar/Wind Harmer
0.753
971795AH1-408 GEN
Solar/Wind Harmer
6.032
316003AC1-222 GEN
Solar/Wind Harmer
0.772
960081AF2-299 GEN
Solar/Wind Harmer
0.762
3147983MERCK5
Solar/Wind Helper
0.055
972205AH1-687 GEN
50/50
20.447
316303AF2-085
50/50
2.011
971447AH1-217 GEN
Solar/Wind Harmer
14.757
971845AH1-439 GEN
Solar/Wind Harmer
20.937
970285AG2-188 GEN
Solar/Wind Harmer
33.263
270494AE1-108_GEN
Solar/Wind Harmer
9.168
315657AE1-056 GEN
Solar/Wind Harmer
8.668
946301AF1-294 GEN
Solar/Wind Harmer
5.566
961791AG1-021 GEN
Solar/Wind Harmer
2.715
970683AG2-441 GEN
Solar/Wind Harmer
15.41
970681AG2-440 GEN
Solar/Wind Harmer
12.328
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.43
316239AB2-077_GEN
Solar/Wind Harmer
0.378
316238AB2-078_GEN
Solar/Wind Harmer
0.378
316118AC1-105 GEN
Solar/Wind Harmer
0.639
970831AG2-522 GEN
Solar/Wind Harmer
4.187
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
970865AG2-541 GEN
Solar/Wind Harmer
2.88
946281AF1-292 GEN
Solar/Wind Harmer
0.152
971967AH1-528 GEN
Solar/Wind Harmer
12.673
316087AB2-174 GEN
Solar/Wind Harmer
0.946
3137643SOCKMAN
Solar/Wind Harmer
-0.026
3138266HYDRAULIC
Solar/Wind Helper
0.02
3144293JTRSVLE
50/50
0.653
3144293JTRSVLE
50/50
0.55
971489AH1-241 GEN
Solar/Wind Harmer
26.74
3146776BUCKING
Solar/Wind Harmer
-0.16
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.489
970301AG2-198 GEN
Solar/Wind Harmer
11.714
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.394
963191AG1-168 GEN
Solar/Wind Harmer
2.036
971741AH1-377 GEN
Solar/Wind Harmer
24.324
316034AC1-036 C
Solar/Wind Harmer
0.327
970323AG2-213 GEN
Solar/Wind Harmer
8.802
971775AH1-396 GEN
Solar/Wind Harmer
1.253
313527AB2-043 GEN
Solar/Wind Harmer
2.088
971223AH1-071 GEN
Solar/Wind Harmer
1.589
962561AG1-105 GEN
Solar/Wind Harmer
5.986
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.118
939181AE1-148 GEN
Solar/Wind Harmer
5.822
964791AG1-342 GEN
Solar/Wind Harmer
2.188
3146843MT LREL
Solar/Wind Harmer
-0.01
3146843MT LREL
Solar/Wind Harmer
-0.01
970099AG2-077 GEN
Solar/Wind Harmer
12.325
970933AG2-581 GEN
Solar/Wind Harmer
7.23
316181AB2-040 GEN
Solar/Wind Harmer
0.916
3145593CAROLNA
Solar/Wind Harmer
-0.006
3145593CAROLNA
Solar/Wind Harmer
-0.006
966811AG1-552 GEN
Solar/Wind Harmer
0.712
3145593CAROLNA
Solar/Wind Harmer
0.053
966001AG1-469 GEN
Solar/Wind Helper
0.187
971193AH1-056 GEN
Solar/Wind Harmer
14.446
963181AG1-167 GEN
Solar/Wind Harmer
2.036
959311AF2-222 GEN
Solar/Wind Harmer
19.01
970257AG2-171 GEN
Solar/Wind Harmer
6.601
315785AD2-033 C
Solar/Wind Harmer
3.8
964241AG1-285 GEN
Solar/Wind Harmer
11.356
958131AF2-107 GEN
Solar/Wind Harmer
4.67
316131AB2-060 GEN
Solar/Wind Harmer
1.422
316478AD1-087 GEN
Solar/Wind Harmer
0.862
316486AD2-202 GEN
Solar/Wind Harmer
0.252
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.252
960061AF2-297 GEN
Solar/Wind Harmer
4.181
971683AH1-343 GEN
Solar/Wind Harmer
3.236
966621AG1-532 GEN
Solar/Wind Harmer
0.138
313506AB2-031 GEN
Solar/Wind Harmer
0.528
316499AE2-029_GEN
Solar/Wind Helper
0.5
3148013FISHERV
Solar/Wind Helper
0.13
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.535
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.02
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.044
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.714
MECLTFEXP_MEC->PJM
CLTF
0.159
LAGNLTFEXP_LAGN->PJM
CLTF
1.141
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.807
TVALTFEXP_TVA->PJM
CLTF
0.557
SIGELTFEXP_SIGE->PJM
CLTF
0.003
CPLELTFEXP_CPLE->PJM
CLTF
2.977
NYPJM->LTFIMP_NY
CLTF
0.385
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.39

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.74 %
Rating:661.76 MVA
Rating Type:A
MVA to Mitigate:719.62
MW Contribution:21.01
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.083
3151541CLOVER2
50/50
1.876
3151931BEARGRDN S1
50/50
5.314
3151911BEARGRDN G1
50/50
4.118
3144293JTRSVLE
50/50
0.644
3151531CLOVER1
50/50
1.885
3151601KERR 3
50/50
0.18
3151581KERR 1
50/50
0.064
970119AG2-088 GEN
50/50
11.599
3147043LAWRENC
50/50
0.746
3151261ROARAP2
50/50
0.072
972003AH1-546 GEN
Solar/Wind Harmer
18.108
971377AH1-170 GEN
Solar/Wind Harmer
4.203
3147623JAMES R
Solar/Wind Harmer
0.913
970937AG2-583 GEN
Solar/Wind Harmer
22.204
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.14
3146926FARMVIL
Solar/Wind Harmer
0.165
316336AC2-165 C
Solar/Wind Harmer
0.01
3143336POWHATN
Solar/Wind Harmer
4.074
963171AG1-166 GEN
Solar/Wind Harmer
1.017
971563AH1-280 GEN
Solar/Wind Harmer
2.035
970685AG2-442 GEN
Solar/Wind Harmer
12.945
962491AG1-098 GEN
Solar/Wind Harmer
6.577
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
5.296
970401AG2-262 GEN
Solar/Wind Harmer
0.531
957481AF2-042 GEN
Solar/Wind Harmer
23.244
3143226MDLTHAN
Solar/Wind Harmer
0.087
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.352
316129AC1-054 GEN
Solar/Wind Harmer
0.289
971795AH1-408 GEN
Solar/Wind Harmer
4.849
3143526WINTERP
Solar/Wind Harmer
0.377
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.595
3145783HORNRTN
Solar/Wind Harmer
0.057
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.752
3144293JTRSVLE
50/50
0.644
3144293JTRSVLE
50/50
0.543
970535AG2-341 GEN
50/50
1.768
3152661PLYWOOD A
50/50
0.177
971489AH1-241 GEN
Solar/Wind Harmer
21.013
3146776BUCKING
Solar/Wind Harmer
1.404
3146776BUCKING
Solar/Wind Harmer
0.114
315821AE2-092 GEN
Solar/Wind Harmer
0.014
970301AG2-198 GEN
Solar/Wind Harmer
8.767
3147133PAMPLIN
Solar/Wind Harmer
0.203
3147133PAMPLIN
Solar/Wind Harmer
0.162
958211AF2-115 GEN
Solar/Wind Harmer
2.289
963191AG1-168 GEN
Solar/Wind Harmer
0.763
971741AH1-377 GEN
Solar/Wind Harmer
18.217
316034AC1-036 C
Solar/Wind Harmer
0.011
970323AG2-213 GEN
Solar/Wind Harmer
6.61
971775AH1-396 GEN
Solar/Wind Harmer
0.248
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
4.515
939181AE1-148 GEN
Solar/Wind Harmer
4.407
964791AG1-342 GEN
Solar/Wind Harmer
1.738
3146843MT LREL
Solar/Wind Harmer
0.09
3146843MT LREL
Solar/Wind Harmer
0.09
970099AG2-077 GEN
Solar/Wind Harmer
9.298
971223AH1-071 GEN
Solar/Wind Harmer
0.928
3143526WINTERP
Solar/Wind Harmer
0.377
970933AG2-581 GEN
Solar/Wind Harmer
5.476
316181AB2-040 GEN
Solar/Wind Harmer
0.087
3145593CAROLNA
Solar/Wind Harmer
0.058
3145593CAROLNA
Solar/Wind Harmer
0.058
966811AG1-552 GEN
Solar/Wind Harmer
0.627
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.01
3145783HORNRTN
Solar/Wind Harmer
0.808
3145783HORNRTN
Solar/Wind Harmer
0.253
3145783HORNRTN
Solar/Wind Harmer
0.101
966001AG1-469 GEN
Solar/Wind Helper
0.19
3151611KERR 4
50/50
0.18
3151621KERR 5
50/50
0.18
3151631KERR 6
50/50
0.18
3151641KERR 7
50/50
0.18
316303AF2-085
50/50
1.546
3151281ROARAP4
50/50
0.07
3151281ROARAP4
50/50
0.066
971447AH1-217 GEN
Solar/Wind Harmer
11.004
971845AH1-439 GEN
Solar/Wind Harmer
15.632
970285AG2-188 GEN
Solar/Wind Harmer
26.316
270494AE1-108_GEN
Solar/Wind Harmer
3.693
315657AE1-056 GEN
Solar/Wind Harmer
6.997
946301AF1-294 GEN
Solar/Wind Harmer
3.764
961791AG1-021 GEN
Solar/Wind Harmer
1.831
970683AG2-441 GEN
Solar/Wind Harmer
11.558
970681AG2-440 GEN
Solar/Wind Harmer
9.247
3144303KENBRDG
Solar/Wind Harmer
0.124
971443AH1-215 GEN
Solar/Wind Harmer
2.576
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.212
970831AG2-522 GEN
Solar/Wind Harmer
3.201
3147173SINAI
Solar/Wind Harmer
0.074
3147243WELCO
Solar/Wind Harmer
0.046
316233AE1-074 FULL
Solar/Wind Harmer
0.058
971281AH1-106 GEN
Solar/Wind Harmer
1.006
971283AH1-107 GEN
Solar/Wind Harmer
1.006
970865AG2-541 GEN
Solar/Wind Harmer
2.17
316087AB2-174 GEN
Solar/Wind Harmer
0.002
971967AH1-528 GEN
Solar/Wind Harmer
9.597
3137643SOCKMAN
Solar/Wind Harmer
0.235
3138266HYDRAULIC
Solar/Wind Helper
0.021
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.08
3148013FISHERV
Solar/Wind Helper
0.077
3148463FAIRFLD
Solar/Wind Helper
0.119
3151921BEARGRDN G2
50/50
4.118
3144293JTRSVLE
50/50
0.644
970413AG2-270 GEN
50/50
8.224
3151591KERR 2
50/50
0.18
966251AG1-494 GEN
50/50
1.173
3151261ROARAP2
50/50
0.07
970221AG2-151 GEN
Solar/Wind Harmer
21.013
3146776BUCKING
Solar/Wind Harmer
0.126
3146926FARMVIL
Solar/Wind Harmer
0.165
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.144
316258AE1-075 C
Solar/Wind Harmer
0.173
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.463
970909AG2-566 GEN
Solar/Wind Harmer
2.192
3147133PAMPLIN
Solar/Wind Harmer
0.637
971193AH1-056 GEN
Solar/Wind Harmer
12.353
963181AG1-167 GEN
Solar/Wind Harmer
0.763
959311AF2-222 GEN
Solar/Wind Harmer
14.242
970257AG2-171 GEN
Solar/Wind Harmer
4.957
315785AD2-033 C
Solar/Wind Harmer
1.2
964241AG1-285 GEN
Solar/Wind Harmer
8.548
958131AF2-107 GEN
Solar/Wind Harmer
3.44
316131AB2-060 GEN
Solar/Wind Harmer
0.366
316478AD1-087 GEN
Solar/Wind Harmer
0.307
316486AD2-202 GEN
Solar/Wind Harmer
0.09
3147043LAWRENC
Solar/Wind Harmer
0.047
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.155
971683AH1-343 GEN
Solar/Wind Harmer
2.44
313506AB2-031 GEN
Solar/Wind Harmer
0.186
316499AE2-029_GEN
Solar/Wind Helper
0.505
3148013FISHERV
Solar/Wind Helper
0.133
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.54
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.029
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.072
LAGNLTFEXP_LAGN->PJM
CLTF
1.122
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.673
MECLTFEXP_MEC->PJM
CLTF
0.138
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.815
TVALTFEXP_TVA->PJM
CLTF
0.547
SIGELTFEXP_SIGE->PJM
CLTF
0.002
NYPJM->LTFIMP_NY
CLTF
0.391
CPLELTFEXP_CPLE->PJM
CLTF
2.992
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.238

Details for 6HANOVER-6FOUR RIVERS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6HANOVER-6FOUR RIVERS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.18 %
Rating:1123.3 MVA
Rating Type:B
MVA to Mitigate:1125.32
MW Contribution:3.15
Bus #Bus NameTypeMW Contribution
3143096IRON208
50/50
0.63
3150641CHESTS8
50/50
0.434
3142416OLDCHRC
Solar/Wind Harmer
0.437
3142416OLDCHRC
Solar/Wind Harmer
0.168
3142543TWELFTH
Solar/Wind Harmer
0.014
944631AF1-128 GEN
Adder
64.319
3150851SPRUNCC
Adder
0.622
315671AE2-027_GEN
Solar/Wind Harmer
8.029
970129AG2-093 GEN
Solar/Wind Harmer
3.524
316458AB2-190 GEN2
Solar/Wind Harmer
0.662
3142433PROV 92
Solar/Wind Harmer
0.488
3142433PROV 92
Adder
0.237
3142433PROV 92
Adder
0.237
971069AG2-661 GEN
Solar/Wind Harmer
2.148
3143526WINTERP
Solar/Wind Harmer
0.621
316159AE1-175 C
Solar/Wind Harmer
0.102
971647AH1-324 GEN
Solar/Wind Harmer
4.981
961611AG1-000B GEN
Solar/Wind Harmer
6.001
3151171GRAVELC
Adder
1.187
971317AH1-138 GEN
Solar/Wind Harmer
0.83
3141766HARMONY
Solar/Wind Harmer
0.022
971777AH1-397 GEN
Solar/Wind Harmer
0.293
3141843SHACKLE
Adder
0.567
3138126ROCKLANDING
Solar/Wind Harmer
0.051
3150611CHESTG7
50/50
0.857
3150631CHESTG8
50/50
0.843
316312AB1-027
Solar/Wind Harmer
0.301
971285AH1-108 GEN
Adder
1.017
315976AC1-164 GENA
Solar/Wind Harmer
13.778
316169AC1-164_GENC
Solar/Wind Harmer
11.903
315975AC1-164 GENB
Solar/Wind Harmer
0.408
971167AH1-042 GEN
Solar/Wind Harmer
10.969
316132AB2-190 GEN1
Solar/Wind Harmer
0.662
3142433PROV 92
Adder
0.237
3142433PROV 92
Adder
0.237
316233AE1-074 FULL
Solar/Wind Harmer
0.096
971281AH1-106 GEN
Solar/Wind Harmer
1.657
971283AH1-107 GEN
Solar/Wind Harmer
1.657
316369SG1_INVT
Solar/Wind Harmer
0.004
3143873LANEXA
Solar/Wind Harmer
0.07
316314AB2-024 C
Solar/Wind Harmer
0
3143316POE
Solar/Wind Harmer
0.442
972265AH1-717 GEN
Adder
8.661
3151201GRAVEL4
Adder
8.12
3151191GRAVEL3
Adder
8.017
3151211GRAVEL5
Adder
8.017
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
3.288
315662AE1-191 GEN
Solar/Wind Harmer
0.004
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971445AH1-216 GEN
Solar/Wind Harmer
7.593
3141873WAN 176
Solar/Wind Harmer
0.021
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.071
316311AC2-079 GEN
Solar/Wind Harmer
2.965
3141913WHIT STONE
Solar/Wind Harmer
0.103
3138133OCRAN
Solar/Wind Harmer
0.031
3152611GOSPORTB
Adder
1.285
3152621GOSPORTC
Adder
1.09
3152601GOSPORTA
Adder
1.006
3151081ELIZAR1
Adder
9.234
3151091ELIZAR2
Adder
9.074
3141783LANCAST
Solar/Wind Harmer
0.06
3141783LANCAST
Solar/Wind Harmer
0.04
315835AF2-110_GEN
Solar/Wind Harmer
0.683
316305AF2-043 C
Solar/Wind Harmer
0.001
957871AF2-081 GEN
Solar/Wind Harmer
4.929
319010AE1-072 C
Solar/Wind Harmer
0.497
3146406KITTY HAWK
Solar/Wind Harmer
0.012
313526AB2-022
Solar/Wind Harmer
0.053
3146486SUNBURY
Solar/Wind Harmer
0.098
3146486SUNBURY
Solar/Wind Harmer
0.098
316321Z2-027
Solar/Wind Harmer
0.018
3146396TANGLEW
Solar/Wind Harmer
0.268
3145176PASQUOTANK
Solar/Wind Harmer
0.06
962981AG1-147 GEN
Solar/Wind Harmer
3.537
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
316315AB2-025 C
Solar/Wind Harmer
0.076
315814AE2-033 C
Solar/Wind Harmer
7.456
3130156CHOWAN
Solar/Wind Harmer
0.093
3130156CHOWAN
Solar/Wind Harmer
0.093
970327AG2-215 GEN
Solar/Wind Harmer
3.018
315816AE2-034 GEN
Solar/Wind Harmer
0.39
3130546PLYMOUTH
Solar/Wind Harmer
0.089
315732AD1-074 GEN1
Solar/Wind Harmer
0.51
315733AD1-074 GEN2
Solar/Wind Harmer
0.51
315735AD1-075 GEN1
Solar/Wind Harmer
0.255
965291AG1-394 GEN
Solar/Wind Harmer
0.392
3146206CASHIE
Solar/Wind Harmer
0.088
970601AG2-382 GEN
Solar/Wind Harmer
3.275
972193AH1-681 GEN
Adder
2.005
3145893MURPHYS
Solar/Wind Harmer
0.235
3145893MURPHYS
Solar/Wind Harmer
0.087
3145513AHOSKIE
Solar/Wind Harmer
0.179
3145513AHOSKIE
Solar/Wind Harmer
0.086
3145683EARLEYS
Solar/Wind Harmer
0.17
3145683EARLEYS
Solar/Wind Harmer
0.085
3145683EARLEYS
Solar/Wind Harmer
0.085
3146043SEABORD
Solar/Wind Harmer
0.084
315607AA1-063A GEN
Solar/Wind Harmer
0.172
315652AC1-086 GEN
Solar/Wind Harmer
9.127
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.328
3145796HORNRTN
Solar/Wind Harmer
0.261
3145796HORNRTN
Solar/Wind Harmer
0.033
3146033SCOT NK
Solar/Wind Harmer
0.324
941031AE2-094 GEN
Solar/Wind Harmer
14.626
944011AF1-069 GEN
Solar/Wind Harmer
4.779
3141813NORNECK
Solar/Wind Harmer
0.079
970673AG2-436 GEN
Solar/Wind Harmer
16.734
970673AG2-436 GEN
Solar/Wind Harmer
11.156
316005AA1-067
Solar/Wind Harmer
0.084
3145746EVERETS
Solar/Wind Harmer
0.31
3145746EVERETS
Solar/Wind Harmer
0.078
3145746EVERETS
Solar/Wind Harmer
0.078
3145746EVERETS
Solar/Wind Harmer
0.078
970181AG2-120 GEN
Solar/Wind Harmer
0.97
971967AH1-528 GEN
Solar/Wind Harmer
12.447
957861AF2-080 GEN
Solar/Wind Harmer
3.293
316420AA1-050 GEN
Solar/Wind Harmer
0.002
970831AG2-522 GEN
Solar/Wind Harmer
3.224
970085AG2-068 GEN
Solar/Wind Harmer
4.006
970581AG2-369 GEN
Solar/Wind Harmer
3.445
3145573BETHELC
Solar/Wind Harmer
0.075
3145573BETHELC
Solar/Wind Harmer
0.075
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
1.169
3144303KENBRDG
Solar/Wind Harmer
0.056
970683AG2-441 GEN
Solar/Wind Harmer
4.609
970681AG2-440 GEN
Solar/Wind Harmer
3.687
946301AF1-294 GEN
Solar/Wind Harmer
1.357
961791AG1-021 GEN
Solar/Wind Harmer
0.66
315657AE1-056 GEN
Solar/Wind Harmer
2.362
316118AC1-105 GEN
Solar/Wind Harmer
0.169
970285AG2-188 GEN
Solar/Wind Harmer
5.153
971845AH1-439 GEN
Solar/Wind Harmer
2.936
3147173SINAI
Solar/Wind Harmer
0.064
3147243WELCO
Solar/Wind Harmer
0.04
971645AH1-323 GEN
50/50
17.435
3143096IRON208
50/50
0.63
3143096IRON208
50/50
0.617
316473AC1-191 GEN
Solar/Wind Harmer
0.571
3142416OLDCHRC
Solar/Wind Harmer
1.631
970293AG2-193 GEN
Solar/Wind Harmer
1.601
3150861SPRUNCD
Adder
0.622
3142946ENON
Solar/Wind Harmer
0.045
970133AG2-095 GEN
Solar/Wind Harmer
1.231
970129AG2-093 GEN
Solar/Wind Harmer
7.489
970659AG2-427 GEN
Solar/Wind Harmer
5.319
316381AD1-082 GEN
Solar/Wind Harmer
0.114
970661AG2-428 GEN
Solar/Wind Harmer
10.707
3145336SMITFLD
Solar/Wind Harmer
0.43
3143226MDLTHAN
Solar/Wind Harmer
0.103
316072AD1-144
Solar/Wind Harmer
0.037
3138133OCRAN
Solar/Wind Harmer
0.061
316375AC2-012 GEN
Solar/Wind Harmer
0.003
3150981CHESPKA
Adder
1.26
316294AC1-161 GEN
Solar/Wind Harmer
1.73
316093AE2-104_GEN
Solar/Wind Harmer
1.674
944591AF1-124 GEN
Solar/Wind Harmer
22.475
316388AE2-253 GEN
Solar/Wind Harmer
0.31
316246AF1-032 C
Solar/Wind Harmer
0.045
3146456SLIGO L269
Solar/Wind Harmer
0.099
3146516WINFALL
Solar/Wind Harmer
0.312
3146516WINFALL
Solar/Wind Harmer
0.096
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.093
3145663CRESWEL
Solar/Wind Harmer
0.255
971163AH1-040 GEN
Solar/Wind Harmer
7.278
962861AG1-135 GEN
Solar/Wind Harmer
2.836
939411AE1-173 GEN
Solar/Wind Harmer
37.741
3146206CASHIE
Solar/Wind Harmer
0.088
971547AH1-271 GEN
Solar/Wind Harmer
1.872
972277AH1-723 GEN
Adder
52.282
3145893MURPHYS
Solar/Wind Harmer
0.349
3145893MURPHYS
Solar/Wind Harmer
0.388
316023GEN1_S
Solar/Wind Harmer
0.195
3143336POWHATN
Solar/Wind Harmer
1.539
3146173TUNIS
Solar/Wind Harmer
0.086
3145683EARLEYS
Solar/Wind Harmer
0.085
940641AE2-051 GEN
Solar/Wind Harmer
6.781
3146263WOODLND
Solar/Wind Harmer
0.084
3141726DUNNSVL
Solar/Wind Harmer
0.336
3145963POPLR C
Solar/Wind Harmer
0.084
960081AF2-299 GEN
Solar/Wind Harmer
0.803
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145823KELFORD
Solar/Wind Harmer
0.083
316011AB1-132 GEN
Solar/Wind Harmer
1.509
962571AG1-106 GEN
Solar/Wind Harmer
1.181
316336AC2-165 C
Solar/Wind Harmer
0.003
316190AA2-174 GEN
Solar/Wind Harmer
0
3145796HORNRTN
Solar/Wind Harmer
0.269
3145796HORNRTN
Solar/Wind Harmer
0.082
3145783HORNRTN
Solar/Wind Harmer
0.081
971795AH1-408 GEN
Solar/Wind Harmer
5.392
3146293MARTNCO
Solar/Wind Harmer
0.074
3147043LAWRENC
Adder
0.72
316212AC1-099_GEN
Solar/Wind Harmer
0.411
3150351NORNECKC2
Adder
0.791
3145746EVERETS
Solar/Wind Harmer
0.078
3145746EVERETS
Solar/Wind Harmer
0.078
315722AD1-056 GEN
Solar/Wind Harmer
0.488
316494AC1-189 GEN
Solar/Wind Harmer
0.258
970919AG2-571 GEN
Solar/Wind Harmer
2.678
970087AG2-069 GEN
Solar/Wind Harmer
6.009
961671AG1-007 GEN
Solar/Wind Harmer
0.011
3146083TARBORO
Solar/Wind Harmer
0.075
3145493TOT1
Solar/Wind Harmer
0.333
316129AC1-054 GEN
Solar/Wind Harmer
0.282
3146233WITAKRS
Solar/Wind Harmer
0.297
971065AG2-659 GEN
Solar/Wind Harmer
3.171
965281AG1-393 GEN
Solar/Wind Harmer
1.32
315839AE2-212 C
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.237
3142433PROV 92
Adder
0.237
315778AD1-151 GEN
Solar/Wind Harmer
9.667
316382AG1-145 C
Solar/Wind Harmer
0.001
961611AG1-000B GEN
Solar/Wind Harmer
3.052
315813AE1-149 C
Solar/Wind Harmer
6.039
3151221GRAVEL6
Adder
8.11
3151171GRAVELC
Adder
1.56
3141766HARMONY
Solar/Wind Harmer
1.48
3141843SHACKLE
Adder
0.567
316203AE2-005 GEN
Solar/Wind Harmer
0
3144216WINCHST
Adder
0.416
3150921YORKTN3
Adder
2.767
970659AG2-427 GEN
Solar/Wind Harmer
1.163
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.002
971781AH1-399 GEN
Solar/Wind Harmer
0.143
970661AG2-428 GEN
Solar/Wind Harmer
2.277
3145336SMITFLD
Solar/Wind Harmer
0.043
316156AD2-030 GEN
Solar/Wind Harmer
0.079
3141873WAN 176
Solar/Wind Harmer
1.904
3144536CHRHLND
Solar/Wind Harmer
0.015
3144873MCLAUGH
Solar/Wind Harmer
0.003
3151101ELIZAR3
Adder
9.352
315773AC2-141 GEN
Solar/Wind Harmer
3.646
944581AF1-123 GEN
Solar/Wind Harmer
22.395
944601AF1-125 GEN
Solar/Wind Harmer
22.05
3146456SLIGO L269
Solar/Wind Harmer
0.099
971153AH1-033 GEN
Solar/Wind Harmer
1.142
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.096
3145273HOLLAND
Solar/Wind Harmer
0.072
3146626S HERTFORD
Solar/Wind Harmer
0.096
962971AG1-146 GEN
Solar/Wind Harmer
1.516
3146376EDENTON
Solar/Wind Harmer
0.093
970009AG2-005 GEN
Solar/Wind Harmer
0.687
315614AA2-178 GEN
Solar/Wind Harmer
0.521
971157AH1-035 GEN
Solar/Wind Harmer
1.07
315737AD1-076 GEN
Solar/Wind Harmer
1.143
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146206CASHIE
Solar/Wind Harmer
0.088
972255AH1-712 GEN
Adder
44.865
316404AE1-155 C
Solar/Wind Harmer
0.02
3145893MURPHYS
Solar/Wind Harmer
0.146
3145893MURPHYS
Solar/Wind Harmer
0.087
957521AF2-046 GEN
Solar/Wind Harmer
6.466
961681AG1-008 GEN
Solar/Wind Harmer
6.466
316365GEN2_N
Solar/Wind Harmer
0.195
316313AB2-026
Solar/Wind Harmer
0.055
316258AE1-075 C
Solar/Wind Harmer
0.065
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
1.308
3146173TUNIS
Solar/Wind Harmer
0.086
3156021HOLLOMANSOL
Solar/Wind Harmer
0.391
316463AE2-346 GEN
Solar/Wind Harmer
0.074
316140AB2-099
Solar/Wind Harmer
0.031
962331AG1-082 GEN
Solar/Wind Harmer
0.914
3142296MT RD221
50/50
0.632
3142366NRTHEST
50/50
0.551
3150691DARBY 3
50/50
11.896
3150701DARBY 4
50/50
11.869
3150681DARBY 2
50/50
11.855
3150671DARBY 1
50/50
11.841
3150621CHESTS7
50/50
0.394
966871AG1-558 GEN
Solar/Wind Harmer
0.195
316075AC2-137 C
Solar/Wind Harmer
0.04
3142946ENON
Solar/Wind Harmer
0.013
944641AF1-129 GEN
Adder
63.125
316240AF1-291 C
Solar/Wind Harmer
0.001
3143526WINTERP
Solar/Wind Harmer
0.621
316033AB2-134 GEN
Solar/Wind Harmer
0.007
315697AD1-025 GEN
Solar/Wind Harmer
0.134
316468AD1-105 GEN
Solar/Wind Harmer
-0.035
970657AG2-426 GEN
Solar/Wind Harmer
3.808
970657AG2-426 GEN
Solar/Wind Harmer
0.798
316236AE1-162_GEN
Solar/Wind Harmer
0.001
971223AH1-071 GEN
Solar/Wind Harmer
1.1
316036AC1-147 C
Solar/Wind Harmer
0.019
3150991CHESPKB
Adder
1.057
3150991CHESPKB
Adder
1.031
316316AC1-027 C
Solar/Wind Harmer
0.096
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.003
3145506HICKORY
Solar/Wind Harmer
0.398
3145506HICKORY
Solar/Wind Harmer
0.239
3145506HICKORY
Solar/Wind Harmer
0.06
316339AD2-160 GEN
Solar/Wind Harmer
0.161
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.055
3137176SLIGO L2192
Solar/Wind Harmer
0.393
3146456SLIGO L269
Solar/Wind Harmer
1.748
3130086AYDLETT
Solar/Wind Harmer
0.394
3146386ELIZ CT
Solar/Wind Harmer
0.098
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.096
3146516WINFALL
Solar/Wind Harmer
0.096
3146516WINFALL
Solar/Wind Harmer
0.096
3146626S HERTFORD
Solar/Wind Harmer
0.096
3146626S HERTFORD
Solar/Wind Harmer
0.096
3144356SAPONY
Solar/Wind Harmer
0.792
316359AB2-059 GEN
Solar/Wind Harmer
0.263
316049AB1-081 GEN
Solar/Wind Harmer
0.419
3145543BTLEBRO
Solar/Wind Harmer
0.073
3145543BTLEBRO
Solar/Wind Harmer
0.059
3142053HEARTS
Solar/Wind Harmer
0.129
957481AF2-042 GEN
Solar/Wind Harmer
19.524
315693AD1-088 GEN
Solar/Wind Harmer
3.47
962491AG1-098 GEN
Solar/Wind Harmer
4.117
970937AG2-583 GEN
Solar/Wind Harmer
4.364
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970685AG2-442 GEN
Solar/Wind Harmer
5.162
963171AG1-166 GEN
Solar/Wind Harmer
0.367
971563AH1-280 GEN
Solar/Wind Harmer
0.733
3144293JTRSVLE
Adder
0.219
315687AD1-152 GEN
Solar/Wind Harmer
0.002
3146926FARMVIL
Solar/Wind Harmer
0.04
970401AG2-262 GEN
Solar/Wind Harmer
0.392
316337AD2-073 GEN
Solar/Wind Harmer
0.057
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.026
316003AC1-222 GEN
Solar/Wind Harmer
0.002
972003AH1-546 GEN
Solar/Wind Harmer
2.646
971377AH1-170 GEN
Solar/Wind Harmer
0.63
3147623JAMES R
Solar/Wind Harmer
0.137
3146263WOODLND
Solar/Wind Harmer
0.084
3145963POPLR C
Solar/Wind Harmer
0.084
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
316317KELFORD C
Solar/Wind Harmer
0.008
3145823KELFORD
Solar/Wind Harmer
0.083
313506AB2-031 GEN
Solar/Wind Harmer
0.255
3145796HORNRTN
Solar/Wind Harmer
0.326
3145796HORNRTN
Solar/Wind Harmer
0.082
3145933PARMELE
Solar/Wind Harmer
0.08
966801AG1-551 GEN
Solar/Wind Harmer
0.93
3147043LAWRENC
Solar/Wind Harmer
0.048
316210AC1-098 GEN
Solar/Wind Harmer
0.737
3150351NORNECKC2
Adder
0.804
3145746EVERETS
Solar/Wind Harmer
0.078
3145746EVERETS
Solar/Wind Harmer
0.078
315724AD1-057 GEN
Solar/Wind Harmer
0.289
316327AA2-057 GEN
Solar/Wind Harmer
0.115
970917AG2-570 GEN
Solar/Wind Harmer
6.696
3146073TAR RVR
Solar/Wind Harmer
0.075
3146083TARBORO
Solar/Wind Harmer
0.075
3146233WITAKRS
Solar/Wind Harmer
0.375
3146233WITAKRS
Solar/Wind Harmer
0.051
3138543CONSLDL
Solar/Wind Harmer
0.049
961601AG1-000A GEN
Solar/Wind Harmer
5.215
3145543BTLEBRO
Solar/Wind Harmer
0.073
3145543BTLEBRO
Solar/Wind Harmer
0.073
971623AH1-311 GEN
Solar/Wind Harmer
0.147
316478AD1-087 GEN
Solar/Wind Harmer
0.249
316486AD2-202 GEN
Solar/Wind Harmer
0.073
316131AB2-060 GEN
Solar/Wind Harmer
0.221
964241AG1-285 GEN
Solar/Wind Harmer
4.675
315785AD2-033 C
Solar/Wind Harmer
0.567
970257AG2-171 GEN
Solar/Wind Harmer
2.225
959311AF2-222 GEN
Solar/Wind Harmer
6.171
970909AG2-566 GEN
Solar/Wind Harmer
0.738
963181AG1-167 GEN
Solar/Wind Harmer
0.275
3144293JTRSVLE
Adder
0.219
3147133PAMPLIN
Solar/Wind Harmer
0.215
971193AH1-056 GEN
Solar/Wind Harmer
4.17
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.04
3146776BUCKING
Solar/Wind Harmer
0.023
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.742
971683AH1-343 GEN
Solar/Wind Harmer
2.232
316283AC2-100 C
Solar/Wind Harmer
0.116
970221AG2-151 GEN
Solar/Wind Harmer
3.149
966881AG1-559 GEN
Solar/Wind Helper
1.213
972205AH1-687 GEN
Adder
2.638
970865AG2-541 GEN
Solar/Wind Harmer
2.043
971447AH1-217 GEN
Solar/Wind Harmer
1.766
3141426STAFORD
Solar/Wind Helper
0.033
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.415
3146376EDENTON
Solar/Wind Harmer
0.415
316065AD1-022 GEN
Solar/Wind Harmer
4.058
958261AF2-120 GEN
Solar/Wind Harmer
2.891
3145893MURPHYS
Solar/Wind Harmer
0.583
3145893MURPHYS
Solar/Wind Harmer
0.157
3146173TUNIS
Solar/Wind Harmer
0.086
3146173TUNIS
Solar/Wind Harmer
0.086
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.05
316181AB2-040 GEN
Solar/Wind Harmer
0.12
316426AA2-053 GEN
Solar/Wind Harmer
0.278
3145796HORNRTN
Solar/Wind Harmer
0.245
3145593CAROLNA
Solar/Wind Harmer
0.082
3145593CAROLNA
Solar/Wind Harmer
0.082
966811AG1-552 GEN
Solar/Wind Harmer
0.885
3145593CAROLNA
Solar/Wind Harmer
0.102
3145783HORNRTN
Solar/Wind Harmer
1.442
3145783HORNRTN
Solar/Wind Harmer
1.154
3145783HORNRTN
Solar/Wind Harmer
0.361
3145783HORNRTN
Solar/Wind Harmer
0.144
3145933PARMELE
Solar/Wind Harmer
0.16
3145933PARMELE
Solar/Wind Harmer
0.08
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.831
3150341NORNECKC1
Adder
0.824
316274AC1-208 GEN
Solar/Wind Harmer
0.408
972185AH1-677 GEN
Adder
4.375
972187AH1-678 GEN
Adder
2.202
970933AG2-581 GEN
Solar/Wind Harmer
6.122
3145493TOT1
Solar/Wind Harmer
0.174
3145453TOT5
Solar/Wind Harmer
0.104
3145603CNETO
Solar/Wind Harmer
0.07
961601AG1-000A GEN
Solar/Wind Harmer
1.304
316263AC1-034 GEN
Solar/Wind Harmer
2.784
970099AG2-077 GEN
Solar/Wind Harmer
7.81
939181AE1-148 GEN
Solar/Wind Harmer
3.417
313527AB2-043 GEN
Solar/Wind Harmer
0.001
971741AH1-377 GEN
Solar/Wind Harmer
6.934
316034AC1-036 C
Solar/Wind Harmer
0.005
970323AG2-213 GEN
Solar/Wind Harmer
2.967
971775AH1-396 GEN
Solar/Wind Harmer
0.111
970301AG2-198 GEN
Solar/Wind Harmer
2.952
958211AF2-115 GEN
Solar/Wind Harmer
0.825
963191AG1-168 GEN
Solar/Wind Harmer
0.275
3144293JTRSVLE
Adder
0.219
3144293JTRSVLE
Adder
0.184
3147133PAMPLIN
Solar/Wind Harmer
0.068
3147133PAMPLIN
Solar/Wind Harmer
0.055
962561AG1-105 GEN
Solar/Wind Harmer
3.235
964791AG1-342 GEN
Solar/Wind Harmer
1.284
3146843MT LREL
Solar/Wind Harmer
0.067
3146843MT LREL
Solar/Wind Harmer
0.067
3146776BUCKING
Solar/Wind Harmer
0.258
3146776BUCKING
Solar/Wind Harmer
0.021
316222AC1-221 GEN
Solar/Wind Harmer
0.248
971489AH1-241 GEN
Solar/Wind Harmer
3.149
LAGNLTFEXP_LAGN->PJM
CLTF
4.321
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.476
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.705
MECLTFEXP_MEC->PJM
CLTF
2.537
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.837
TVALTFEXP_TVA->PJM
CLTF
2.185
SIGELTFEXP_SIGE->PJM
CLTF
0.079
NYPJM->LTFIMP_NY
CLTF
0.971
LGEELTFEXP_LGEE->PJM
CLTF
0.994
WECLTFEXP_WEC->PJM
CLTF
0.514
CPLELTFEXP_CPLE->PJM
CLTF
4.707
CBM West 2LTFEXP_CBM-W2->PJM
CBM
24.626

Details for 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 553_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.98 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1131.57
MW Contribution:6.84
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
1.555
3151911BEARGRDN G1
50/50
1.205
3152161CUNINGA
50/50
0.763
972277AH1-723 GEN
50/50
62.568
3152061BATH 6F
50/50
2.078
23503401SHY_Z2-039
50/50
0.003
971377AH1-170 GEN
Solar/Wind Harmer
1.368
3147623JAMES R
Solar/Wind Harmer
0.297
972003AH1-546 GEN
Solar/Wind Harmer
5.266
315705AF1-075 GEN
Solar/Wind Harmer
4.096
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.039
970937AG2-583 GEN
Solar/Wind Harmer
6.041
3147983MERCK5
Solar/Wind Harmer
0.038
3146926FARMVIL
Solar/Wind Harmer
0.044
316336AC2-165 C
Solar/Wind Harmer
0.002
316192AB2-158 GEN
Solar/Wind Helper
3.262
3147666LOUISA
Solar/Wind Helper
1.887
316254AC1-120 GEN1
Solar/Wind Helper
1.426
316006AB2-029 C
Solar/Wind Helper
0.088
972205AH1-687 GEN
50/50
5.876
3151881LOWMORC
50/50
1.119
3151881LOWMORC
50/50
1.101
3151861LOWMORA
50/50
1.084
3152181CUNINGC
50/50
0.816
972193AH1-681 GEN
50/50
2.399
3152011BATH 1A
50/50
2.071
3152021BATH 2B
50/50
2.071
3152031BATH 3C
50/50
2.071
3152041BATH 4D
50/50
2.067
3138266HYDRAULIC
Solar/Wind Harmer
0.011
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3148133STUARTS
Solar/Wind Harmer
0.083
3148013FISHERV
Solar/Wind Harmer
0.079
971447AH1-217 GEN
Solar/Wind Harmer
3.945
270494AE1-108_GEN
Solar/Wind Harmer
1.309
3148463FAIRFLD
Solar/Wind Harmer
0.099
971845AH1-439 GEN
Solar/Wind Harmer
4.376
970285AG2-188 GEN
Solar/Wind Harmer
7.313
316164AC1-076 GEN
Solar/Wind Helper
1.19
3151921BEARGRDN G2
50/50
1.205
3137383CUSHAW
50/50
0.022
3151861LOWMORA
50/50
1.128
3152191CUNINGD
50/50
1.776
3152171CUNINGB
50/50
0.767
972255AH1-712 GEN
50/50
53.693
315760AF1-028 GEN
50/50
15.215
3152051BATH 5E
50/50
2.069
3148013FISHERV
Solar/Wind Harmer
0.138
970221AG2-151 GEN
Solar/Wind Harmer
6.84
315616AA1-038_C
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.036
3146926FARMVIL
Solar/Wind Harmer
0.044
958131AF2-107 GEN
Solar/Wind Harmer
1.93
942461AE2-259 GEN
Solar/Wind Harmer
0
3132273ORANGE
Solar/Wind Helper
0.105
3147666LOUISA
Solar/Wind Helper
1.085
316170AC1-121 GEN2
Solar/Wind Helper
0.475
23503501NHY_Z2-039
50/50
0.005
315821AE2-092 GEN
Solar/Wind Harmer
0.008
971489AH1-241 GEN
Solar/Wind Harmer
6.84
3146776BUCKING
Solar/Wind Harmer
0.395
3146776BUCKING
Solar/Wind Harmer
0.032
3132123MT JACKSON
Solar/Wind Harmer
0.208
970117AG2-086 GEN
Solar/Wind Harmer
1.594
970117AG2-086 GEN
Solar/Wind Harmer
1.063
966001AG1-469 GEN
Solar/Wind Helper
0.735
315651AD1-115 GEN
Solar/Wind Helper
0.962
LAGNLTFEXP_LAGN->PJM
CLTF
2.697
CBM West 1LTFEXP_CBM-W1->PJM
CBM
16.766
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.191
MECLTFEXP_MEC->PJM
CLTF
2.078
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.536
TVALTFEXP_TVA->PJM
CLTF
1.4
SIGELTFEXP_SIGE->PJM
CLTF
0.068
NYPJM->LTFIMP_NY
CLTF
0.747
LGEELTFEXP_LGEE->PJM
CLTF
0.893
WECLTFEXP_WEC->PJM
CLTF
0.458
CPLELTFEXP_CPLE->PJM
CLTF
0.939
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.474

Details for 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.16 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1015.26
MW Contribution:7.05
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
1.629
3151911BEARGRDN G1
50/50
1.262
3152061BATH 6F
50/50
1.661
3144293JTRSVLE
50/50
0.21
23503401SHY_Z2-039
50/50
0.002
3152161CUNINGA
50/50
0.455
972277AH1-723 GEN
50/50
37.31
971377AH1-170 GEN
Solar/Wind Harmer
1.41
3147623JAMES R
Solar/Wind Harmer
0.306
972003AH1-546 GEN
Solar/Wind Harmer
5.557
970937AG2-583 GEN
Solar/Wind Harmer
6.724
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.043
3146926FARMVIL
Solar/Wind Harmer
0.052
315705AF1-075 GEN
Solar/Wind Harmer
3.448
3147983MERCK5
Solar/Wind Harmer
0.033
316336AC2-165 C
Solar/Wind Harmer
0.003
3143336POWHATN
Solar/Wind Harmer
1.187
963171AG1-166 GEN
Solar/Wind Harmer
0.332
971563AH1-280 GEN
Solar/Wind Harmer
0.664
970685AG2-442 GEN
Solar/Wind Harmer
4.286
316192AB2-158 GEN
Solar/Wind Helper
3.267
3147666LOUISA
Solar/Wind Helper
1.889
316254AC1-120 GEN1
Solar/Wind Helper
1.434
316006AB2-029 C
Solar/Wind Helper
0.088
3144293JTRSVLE
50/50
0.21
3144293JTRSVLE
50/50
0.177
23503501NHY_Z2-039
50/50
0.004
971489AH1-241 GEN
Solar/Wind Harmer
7.052
315821AE2-092 GEN
Solar/Wind Harmer
0.008
3146776BUCKING
Solar/Wind Harmer
0.434
3146776BUCKING
Solar/Wind Harmer
0.035
3147133PAMPLIN
Solar/Wind Harmer
0.066
3147133PAMPLIN
Solar/Wind Harmer
0.052
970301AG2-198 GEN
Solar/Wind Harmer
2.774
958211AF2-115 GEN
Solar/Wind Harmer
0.747
963191AG1-168 GEN
Solar/Wind Harmer
0.249
971741AH1-377 GEN
Solar/Wind Harmer
5.799
966001AG1-469 GEN
Solar/Wind Helper
0.74
315651AD1-115 GEN
Solar/Wind Helper
0.968
972205AH1-687 GEN
50/50
6.155
3151881LOWMORC
50/50
0.936
3151881LOWMORC
50/50
0.921
3151861LOWMORA
50/50
0.906
3152011BATH 1A
50/50
1.656
3152021BATH 2B
50/50
1.656
3152031BATH 3C
50/50
1.655
3152041BATH 4D
50/50
1.652
3152181CUNINGC
50/50
0.486
972193AH1-681 GEN
50/50
1.431
3138266HYDRAULIC
Solar/Wind Harmer
0.011
3138266HYDRAULIC
Solar/Wind Harmer
0.007
971447AH1-217 GEN
Solar/Wind Harmer
4.022
3148133STUARTS
Solar/Wind Harmer
0.074
3148013FISHERV
Solar/Wind Harmer
0.071
270494AE1-108_GEN
Solar/Wind Harmer
1.339
971845AH1-439 GEN
Solar/Wind Harmer
4.834
970285AG2-188 GEN
Solar/Wind Harmer
8.151
3148463FAIRFLD
Solar/Wind Harmer
0.083
315657AE1-056 GEN
Solar/Wind Harmer
2.265
946301AF1-294 GEN
Solar/Wind Harmer
1.229
961791AG1-021 GEN
Solar/Wind Harmer
0.598
970683AG2-441 GEN
Solar/Wind Harmer
3.826
970681AG2-440 GEN
Solar/Wind Harmer
3.061
316164AC1-076 GEN
Solar/Wind Helper
1.194
3151921BEARGRDN G2
50/50
1.262
3137383CUSHAW
50/50
0.018
3151861LOWMORA
50/50
0.943
315760AF1-028 GEN
50/50
12.698
3152051BATH 5E
50/50
1.654
3144293JTRSVLE
50/50
0.21
3152191CUNINGD
50/50
1.059
3152171CUNINGB
50/50
0.457
972255AH1-712 GEN
50/50
32.018
970221AG2-151 GEN
Solar/Wind Harmer
7.052
3148013FISHERV
Solar/Wind Harmer
0.123
3146776BUCKING
Solar/Wind Harmer
0.039
3146926FARMVIL
Solar/Wind Harmer
0.052
315616AA1-038_C
Solar/Wind Harmer
0.001
942461AE2-259 GEN
Solar/Wind Harmer
0
316313AB2-026
Solar/Wind Harmer
0.042
316258AE1-075 C
Solar/Wind Harmer
0.05
316405AF2-144 C
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
1.009
958131AF2-107 GEN
Solar/Wind Harmer
1.905
3147133PAMPLIN
Solar/Wind Harmer
0.206
971193AH1-056 GEN
Solar/Wind Harmer
3.999
970909AG2-566 GEN
Solar/Wind Harmer
0.694
963181AG1-167 GEN
Solar/Wind Harmer
0.249
3132273ORANGE
Solar/Wind Helper
0.106
3147666LOUISA
Solar/Wind Helper
1.086
316170AC1-121 GEN2
Solar/Wind Helper
0.478
LAGNLTFEXP_LAGN->PJM
CLTF
2.954
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.521
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.505
MECLTFEXP_MEC->PJM
CLTF
2.015
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.46
TVALTFEXP_TVA->PJM
CLTF
1.519
SIGELTFEXP_SIGE->PJM
CLTF
0.065
NYPJM->LTFIMP_NY
CLTF
0.852
LGEELTFEXP_LGEE->PJM
CLTF
0.839
WECLTFEXP_WEC->PJM
CLTF
0.429
CPLELTFEXP_CPLE->PJM
CLTF
1.993
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.046

Details for 6KYSER-6LUCKYHILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2304_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6KYSER-6LUCKYHILL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2304_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.02 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1082.79
MW Contribution:3.93
Bus #Bus NameTypeMW Contribution
972183AH1-676 GEN
50/50
491.529
3151761LOISA E
50/50
60.868
3151771S ANNAG1
50/50
1.517
3151801S ANNAS2
50/50
0.779
3151921BEARGRDN G2
50/50
0.706
3132273ORANGE
Solar/Wind Harmer
0.054
316170AC1-121 GEN2
Solar/Wind Harmer
0.101
970221AG2-151 GEN
Solar/Wind Harmer
3.929
3148013FISHERV
Solar/Wind Harmer
0.066
3146776BUCKING
Solar/Wind Harmer
0.022
972205AH1-687 GEN
50/50
3.443
3147346CASHSCORNER
Solar/Wind Harmer
0.945
3138266HYDRAULIC
Solar/Wind Harmer
0.006
3138266HYDRAULIC
Solar/Wind Harmer
0.004
971447AH1-217 GEN
Solar/Wind Harmer
2.235
316164AC1-076 GEN
Solar/Wind Harmer
0.1
3148133STUARTS
Solar/Wind Harmer
0.04
3148013FISHERV
Solar/Wind Harmer
0.038
270494AE1-108_GEN
Solar/Wind Harmer
0.739
971845AH1-439 GEN
Solar/Wind Harmer
2.694
970285AG2-188 GEN
Solar/Wind Harmer
4.539
3151741LOISA C
50/50
1.633
3151751LOISA D
50/50
29.856
3151791S ANNAG2
50/50
1.517
3151781S ANNAS1
50/50
0.779
3151931BEARGRDN S1
50/50
0.911
3151911BEARGRDN G1
50/50
0.706
315683AE1-153 C
Solar/Wind Harmer
52.577
316192AB2-158 GEN
Solar/Wind Harmer
2.449
316254AC1-120 GEN1
Solar/Wind Harmer
0.201
971377AH1-170 GEN
Solar/Wind Harmer
0.786
3147623JAMES R
Solar/Wind Harmer
0.171
972003AH1-546 GEN
Solar/Wind Harmer
3.107
970937AG2-583 GEN
Solar/Wind Harmer
3.763
316322AB2-045
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.024
3151731LOISA B
50/50
29.856
3151721LOISA A
50/50
29.702
966001AG1-469 GEN
Solar/Wind Harmer
0.231
971489AH1-241 GEN
Solar/Wind Harmer
3.929
315821AE2-092 GEN
Solar/Wind Harmer
0.004
315651AD1-115 GEN
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.242
3146776BUCKING
Solar/Wind Harmer
0.02
LAGNLTFEXP_LAGN->PJM
CLTF
1.34
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.412
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.486
MECLTFEXP_MEC->PJM
CLTF
0.864
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.634
TVALTFEXP_TVA->PJM
CLTF
0.692
SIGELTFEXP_SIGE->PJM
CLTF
0.028
NYPJM->LTFIMP_NY
CLTF
0.531
LGEELTFEXP_LGEE->PJM
CLTF
0.36
WECLTFEXP_WEC->PJM
CLTF
0.18
CPLELTFEXP_CPLE->PJM
CLTF
0.975
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.999

Details for 6KYSER-6LUCKYHILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2202_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6KYSER-6LUCKYHILL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2202_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.83 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1061.23
MW Contribution:3.94
Bus #Bus NameTypeMW Contribution
3151741LOISA C
50/50
1.633
3151791S ANNAG2
50/50
1.517
3151781S ANNAS1
50/50
0.78
3151751LOISA D
50/50
29.866
3151931BEARGRDN S1
50/50
0.913
3151911BEARGRDN G1
50/50
0.707
315683AE1-153 C
Solar/Wind Harmer
52.588
316254AC1-120 GEN1
Solar/Wind Harmer
0.201
971377AH1-170 GEN
Solar/Wind Harmer
0.787
3147623JAMES R
Solar/Wind Harmer
0.171
972003AH1-546 GEN
Solar/Wind Harmer
3.113
970937AG2-583 GEN
Solar/Wind Harmer
3.772
316322AB2-045
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.024
3151731LOISA B
50/50
29.866
3151721LOISA A
50/50
29.712
966001AG1-469 GEN
Solar/Wind Harmer
0.231
971489AH1-241 GEN
Solar/Wind Harmer
3.937
315821AE2-092 GEN
Solar/Wind Harmer
0.004
315651AD1-115 GEN
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.242
3146776BUCKING
Solar/Wind Harmer
0.02
972205AH1-687 GEN
50/50
3.45
3147346CASHSCORNER
Solar/Wind Harmer
0.945
3138266HYDRAULIC
Solar/Wind Harmer
0.006
3138266HYDRAULIC
Solar/Wind Harmer
0.004
971447AH1-217 GEN
Solar/Wind Harmer
2.24
316164AC1-076 GEN
Solar/Wind Harmer
0.1
3148133STUARTS
Solar/Wind Harmer
0.04
3148013FISHERV
Solar/Wind Harmer
0.038
270494AE1-108_GEN
Solar/Wind Harmer
0.741
971845AH1-439 GEN
Solar/Wind Harmer
2.7
970285AG2-188 GEN
Solar/Wind Harmer
4.55
3151771S ANNAG1
50/50
1.517
3151801S ANNAS2
50/50
0.78
972183AH1-676 GEN
50/50
491.693
3151761LOISA E
50/50
60.888
3151921BEARGRDN G2
50/50
0.707
3132273ORANGE
Solar/Wind Harmer
0.054
316170AC1-121 GEN2
Solar/Wind Harmer
0.101
970221AG2-151 GEN
Solar/Wind Harmer
3.937
3148013FISHERV
Solar/Wind Harmer
0.066
3146776BUCKING
Solar/Wind Harmer
0.022
LAGNLTFEXP_LAGN->PJM
CLTF
1.362
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.574
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.529
MECLTFEXP_MEC->PJM
CLTF
0.883
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.667
TVALTFEXP_TVA->PJM
CLTF
0.704
SIGELTFEXP_SIGE->PJM
CLTF
0.028
NYPJM->LTFIMP_NY
CLTF
0.524
LGEELTFEXP_LGEE->PJM
CLTF
0.368
WECLTFEXP_WEC->PJM
CLTF
0.184
CPLELTFEXP_CPLE->PJM
CLTF
0.987
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.149

Details for 6LOISACT-6S ANNA 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
6LOISACT-6S ANNA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:151.67 %
Rating:886.0 MVA
Rating Type:C
MVA to Mitigate:1343.83
MW Contribution:6.43
Bus #Bus NameTypeMW Contribution
3151731LOISA B
50/50
41.13
3151721LOISA A
50/50
40.918
966001AG1-469 GEN
Solar/Wind Harmer
1.246
971489AH1-241 GEN
Solar/Wind Harmer
6.108
315821AE2-092 GEN
Solar/Wind Harmer
2.104
3146776BUCKING
Solar/Wind Harmer
-0.032
3146776BUCKING
Solar/Wind Harmer
-0.003
3147346CASHSCORNER
Solar/Wind Harmer
0.96
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
972205AH1-687 GEN
Adder
4.014
971447AH1-217 GEN
Solar/Wind Harmer
3.674
3148133STUARTS
Solar/Wind Harmer
-0.006
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
2.235
971845AH1-439 GEN
Solar/Wind Harmer
4.204
970285AG2-188 GEN
Solar/Wind Harmer
6.637
3151741LOISA C
50/50
2.249
3151751LOISA D
50/50
41.13
315683AE1-153 C
Solar/Wind Harmer
61.45
971377AH1-170 GEN
Solar/Wind Harmer
1.287
3147623JAMES R
Solar/Wind Harmer
0.159
972003AH1-546 GEN
Solar/Wind Harmer
5.039
970937AG2-583 GEN
Solar/Wind Harmer
5.838
316322AB2-045
Solar/Wind Harmer
0.272
3146776BUCKING
Solar/Wind Harmer
-0.003
315705AF1-075 GEN
Solar/Wind Harmer
2.99
3147983MERCK5
Solar/Wind Harmer
-0.003
316192AB2-158 GEN
Solar/Wind Helper
4.556
3147666LOUISA
Solar/Wind Helper
2.625
3151761LOISA E
50/50
83.853
972183AH1-676 GEN
50/50
666.124
970221AG2-151 GEN
Solar/Wind Harmer
6.434
3148013FISHERV
Solar/Wind Harmer
-0.01
3146776BUCKING
Solar/Wind Harmer
-0.003
316499AE2-029_GEN
Solar/Wind Harmer
0.534
3147666LOUISA
Solar/Wind Helper
1.51
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.296
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.916
MECLTFEXP_MEC->PJM
CLTF
1.156
LAGNLTFEXP_LAGN->PJM
CLTF
1.523
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.134
TVALTFEXP_TVA->PJM
CLTF
0.789
SIGELTFEXP_SIGE->PJM
CLTF
0.037
CPLELTFEXP_CPLE->PJM
CLTF
0.618
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.494
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.793
WECLTFEXP_WEC->PJM
CLTF
0.254

Details for 6LOISACT-6S ANNA 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6LOISACT-6S ANNA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:144.74 %
Rating:886.0 MVA
Rating Type:C
MVA to Mitigate:1282.43
MW Contribution:6.43
Bus #Bus NameTypeMW Contribution
3151731LOISA B
50/50
41.13
3151721LOISA A
50/50
40.918
966001AG1-469 GEN
Solar/Wind Harmer
1.246
971489AH1-241 GEN
Solar/Wind Harmer
6.108
315821AE2-092 GEN
Solar/Wind Harmer
2.104
3146776BUCKING
Solar/Wind Harmer
-0.032
3146776BUCKING
Solar/Wind Harmer
-0.003
3147346CASHSCORNER
Solar/Wind Harmer
0.96
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
972205AH1-687 GEN
Adder
4.014
971447AH1-217 GEN
Solar/Wind Harmer
3.674
3148133STUARTS
Solar/Wind Harmer
-0.006
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
2.235
971845AH1-439 GEN
Solar/Wind Harmer
4.204
970285AG2-188 GEN
Solar/Wind Harmer
6.637
3151741LOISA C
50/50
2.249
3151751LOISA D
50/50
41.13
971377AH1-170 GEN
Solar/Wind Harmer
1.287
3147623JAMES R
Solar/Wind Harmer
0.159
972003AH1-546 GEN
Solar/Wind Harmer
5.039
970937AG2-583 GEN
Solar/Wind Harmer
5.838
316322AB2-045
Solar/Wind Harmer
0.272
3146776BUCKING
Solar/Wind Harmer
-0.003
315705AF1-075 GEN
Solar/Wind Harmer
2.99
3147983MERCK5
Solar/Wind Harmer
-0.003
316192AB2-158 GEN
Solar/Wind Helper
4.556
3147666LOUISA
Solar/Wind Helper
2.625
3151761LOISA E
50/50
83.853
972183AH1-676 GEN
50/50
666.124
970221AG2-151 GEN
Solar/Wind Harmer
6.434
3148013FISHERV
Solar/Wind Harmer
-0.01
3146776BUCKING
Solar/Wind Harmer
-0.003
316499AE2-029_GEN
Solar/Wind Harmer
0.534
3147666LOUISA
Solar/Wind Helper
1.51
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.296
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.916
MECLTFEXP_MEC->PJM
CLTF
1.156
LAGNLTFEXP_LAGN->PJM
CLTF
1.523
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.134
TVALTFEXP_TVA->PJM
CLTF
0.789
SIGELTFEXP_SIGE->PJM
CLTF
0.037
CPLELTFEXP_CPLE->PJM
CLTF
0.618
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.494
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.793
WECLTFEXP_WEC->PJM
CLTF
0.254

Details for 6LOISACT-6S ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2199_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
6LOISACT-6S ANNA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2199_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.51 %
Rating:798.06 MVA
Rating Type:B
MVA to Mitigate:1113.34
MW Contribution:4.25
Bus #Bus NameTypeMW Contribution
3151731LOISA B
50/50
36.566
3151721LOISA A
50/50
36.377
966001AG1-469 GEN
Solar/Wind Harmer
0.278
315651AD1-115 GEN
Solar/Wind Harmer
0.004
971489AH1-241 GEN
Solar/Wind Harmer
4.25
315821AE2-092 GEN
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.248
3146776BUCKING
Solar/Wind Harmer
0.02
972205AH1-687 GEN
50/50
3.7
3147346CASHSCORNER
Solar/Wind Harmer
1.132
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3138266HYDRAULIC
Solar/Wind Harmer
0.004
316164AC1-076 GEN
Solar/Wind Harmer
0.133
971447AH1-217 GEN
Solar/Wind Harmer
2.429
3148133STUARTS
Solar/Wind Harmer
0.045
3148013FISHERV
Solar/Wind Harmer
0.043
270494AE1-108_GEN
Solar/Wind Harmer
0.797
971845AH1-439 GEN
Solar/Wind Harmer
2.748
970285AG2-188 GEN
Solar/Wind Harmer
4.589
3151741LOISA C
50/50
2
3151751LOISA D
50/50
36.566
3151931BEARGRDN S1
50/50
0.979
3151911BEARGRDN G1
50/50
0.759
315683AE1-153 C
Solar/Wind Harmer
41.3
316254AC1-120 GEN1
Solar/Wind Harmer
0.303
971377AH1-170 GEN
Solar/Wind Harmer
0.85
3147623JAMES R
Solar/Wind Harmer
0.185
972003AH1-546 GEN
Solar/Wind Harmer
3.315
970937AG2-583 GEN
Solar/Wind Harmer
3.812
316322AB2-045
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.025
316192AB2-158 GEN
Solar/Wind Helper
5.098
3147666LOUISA
Solar/Wind Helper
2.936
3151761LOISA E
50/50
74.547
972183AH1-676 GEN
50/50
589.467
3151921BEARGRDN G2
50/50
0.759
3132273ORANGE
Solar/Wind Harmer
0.067
316170AC1-121 GEN2
Solar/Wind Harmer
0.152
970221AG2-151 GEN
Solar/Wind Harmer
4.25
3148013FISHERV
Solar/Wind Harmer
0.075
3146776BUCKING
Solar/Wind Harmer
0.022
3147666LOUISA
Solar/Wind Helper
1.688
LAGNLTFEXP_LAGN->PJM
CLTF
1.272
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.087
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.452
MECLTFEXP_MEC->PJM
CLTF
0.994
SIGELTFEXP_SIGE->PJM
CLTF
0.032
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.624
TVALTFEXP_TVA->PJM
CLTF
0.66
NYPJM->LTFIMP_NY
CLTF
0.312
LGEELTFEXP_LGEE->PJM
CLTF
0.427
WECLTFEXP_WEC->PJM
CLTF
0.22
CPLELTFEXP_CPLE->PJM
CLTF
0.423
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.297

Details for 6LOISACT-6S ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2331_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6LOISACT-6S ANNA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2331_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:134.58 %
Rating:798.06 MVA
Rating Type:B
MVA to Mitigate:1074.06
MW Contribution:4.25
Bus #Bus NameTypeMW Contribution
3151741LOISA C
50/50
2
3151751LOISA D
50/50
36.566
3151931BEARGRDN S1
50/50
0.979
3151911BEARGRDN G1
50/50
0.759
315683AE1-153 C
Solar/Wind Harmer
41.3
316254AC1-120 GEN1
Solar/Wind Harmer
0.303
971377AH1-170 GEN
Solar/Wind Harmer
0.85
3147623JAMES R
Solar/Wind Harmer
0.185
972003AH1-546 GEN
Solar/Wind Harmer
3.315
970937AG2-583 GEN
Solar/Wind Harmer
3.812
316322AB2-045
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.025
316192AB2-158 GEN
Solar/Wind Helper
5.098
3147666LOUISA
Solar/Wind Helper
2.936
972205AH1-687 GEN
50/50
3.7
3147346CASHSCORNER
Solar/Wind Harmer
1.132
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3138266HYDRAULIC
Solar/Wind Harmer
0.004
316164AC1-076 GEN
Solar/Wind Harmer
0.133
971447AH1-217 GEN
Solar/Wind Harmer
2.429
3148133STUARTS
Solar/Wind Harmer
0.045
3148013FISHERV
Solar/Wind Harmer
0.043
270494AE1-108_GEN
Solar/Wind Harmer
0.797
971845AH1-439 GEN
Solar/Wind Harmer
2.748
970285AG2-188 GEN
Solar/Wind Harmer
4.589
3151761LOISA E
50/50
74.547
972183AH1-676 GEN
50/50
589.467
3151921BEARGRDN G2
50/50
0.759
3132273ORANGE
Solar/Wind Harmer
0.067
316170AC1-121 GEN2
Solar/Wind Harmer
0.152
970221AG2-151 GEN
Solar/Wind Harmer
4.25
3148013FISHERV
Solar/Wind Harmer
0.075
3146776BUCKING
Solar/Wind Harmer
0.022
3147666LOUISA
Solar/Wind Helper
1.688
3151731LOISA B
50/50
36.566
3151721LOISA A
50/50
36.377
966001AG1-469 GEN
Solar/Wind Harmer
0.278
315651AD1-115 GEN
Solar/Wind Harmer
0.004
971489AH1-241 GEN
Solar/Wind Harmer
4.25
315821AE2-092 GEN
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.248
3146776BUCKING
Solar/Wind Harmer
0.02
LAGNLTFEXP_LAGN->PJM
CLTF
1.272
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.087
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.452
MECLTFEXP_MEC->PJM
CLTF
0.994
SIGELTFEXP_SIGE->PJM
CLTF
0.032
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.624
TVALTFEXP_TVA->PJM
CLTF
0.66
NYPJM->LTFIMP_NY
CLTF
0.312
LGEELTFEXP_LGEE->PJM
CLTF
0.427
WECLTFEXP_WEC->PJM
CLTF
0.22
CPLELTFEXP_CPLE->PJM
CLTF
0.423
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.297

Details for 6LOISACT-6S ANNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 2199T2331_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6LOISACT-6S ANNA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2199T2331_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.74 %
Rating:886.0 MVA
Rating Type:C
MVA to Mitigate:1140.66
MW Contribution:5.59
Bus #Bus NameTypeMW Contribution
3151761LOISA E
50/50
74.547
972183AH1-676 GEN
50/50
589.467
3132273ORANGE
Solar/Wind Harmer
-0.007
316170AC1-121 GEN2
Solar/Wind Harmer
0.429
970221AG2-151 GEN
Solar/Wind Harmer
5.595
3148013FISHERV
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Harmer
-0.002
3147666LOUISA
Solar/Wind Helper
1.688
3151741LOISA C
50/50
2
3151751LOISA D
50/50
36.566
315683AE1-153 C
Solar/Wind Harmer
54.379
316254AC1-120 GEN1
Solar/Wind Harmer
1.288
971377AH1-170 GEN
Solar/Wind Harmer
1.119
3147623JAMES R
Solar/Wind Harmer
0.138
972003AH1-546 GEN
Solar/Wind Harmer
4.372
970937AG2-583 GEN
Solar/Wind Harmer
5.019
316322AB2-045
Solar/Wind Harmer
0.234
3146776BUCKING
Solar/Wind Harmer
-0.003
316192AB2-158 GEN
Solar/Wind Helper
5.098
3147666LOUISA
Solar/Wind Helper
2.936
3151731LOISA B
50/50
36.566
3151721LOISA A
50/50
36.377
966001AG1-469 GEN
Solar/Wind Harmer
1.014
315651AD1-115 GEN
Solar/Wind Harmer
5.814
971489AH1-241 GEN
Solar/Wind Harmer
5.312
315821AE2-092 GEN
Solar/Wind Harmer
1.835
3146776BUCKING
Solar/Wind Harmer
-0.028
3146776BUCKING
Solar/Wind Harmer
-0.002
3147346CASHSCORNER
Solar/Wind Harmer
0.849
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
316164AC1-076 GEN
Solar/Wind Harmer
0.897
972205AH1-687 GEN
Adder
3.487
971447AH1-217 GEN
Solar/Wind Harmer
3.198
3148133STUARTS
Solar/Wind Harmer
-0.005
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
1.942
971845AH1-439 GEN
Solar/Wind Harmer
3.618
970285AG2-188 GEN
Solar/Wind Harmer
5.703
LAGNLTFEXP_LAGN->PJM
CLTF
1.272
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.087
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.452
MECLTFEXP_MEC->PJM
CLTF
0.994
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.624
TVALTFEXP_TVA->PJM
CLTF
0.66
SIGELTFEXP_SIGE->PJM
CLTF
0.032
NYPJM->LTFIMP_NY
CLTF
0.312
LGEELTFEXP_LGEE->PJM
CLTF
0.427
WECLTFEXP_WEC->PJM
CLTF
0.22
CPLELTFEXP_CPLE->PJM
CLTF
0.423
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.297

Details for 6LOISACT-6S ANNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 2278T2331_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6LOISACT-6S ANNA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2278T2331_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.2 %
Rating:886.0 MVA
Rating Type:C
MVA to Mitigate:1100.4
MW Contribution:5.59
Bus #Bus NameTypeMW Contribution
3147346CASHSCORNER
Solar/Wind Harmer
0.849
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
316164AC1-076 GEN
Solar/Wind Harmer
0.897
972205AH1-687 GEN
Adder
3.487
971447AH1-217 GEN
Solar/Wind Harmer
3.198
3148133STUARTS
Solar/Wind Harmer
-0.005
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
1.942
971845AH1-439 GEN
Solar/Wind Harmer
3.618
970285AG2-188 GEN
Solar/Wind Harmer
5.703
3151741LOISA C
50/50
2
3151751LOISA D
50/50
36.566
315683AE1-153 C
Solar/Wind Harmer
54.379
316254AC1-120 GEN1
Solar/Wind Harmer
1.288
971377AH1-170 GEN
Solar/Wind Harmer
1.119
3147623JAMES R
Solar/Wind Harmer
0.138
972003AH1-546 GEN
Solar/Wind Harmer
4.372
970937AG2-583 GEN
Solar/Wind Harmer
5.019
316322AB2-045
Solar/Wind Harmer
0.234
3146776BUCKING
Solar/Wind Harmer
-0.003
316192AB2-158 GEN
Solar/Wind Helper
5.098
3147666LOUISA
Solar/Wind Helper
2.936
3151761LOISA E
50/50
74.547
972183AH1-676 GEN
50/50
589.467
3132273ORANGE
Solar/Wind Harmer
-0.007
316170AC1-121 GEN2
Solar/Wind Harmer
0.429
970221AG2-151 GEN
Solar/Wind Harmer
5.595
3148013FISHERV
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Harmer
-0.002
3147666LOUISA
Solar/Wind Helper
1.688
3151731LOISA B
50/50
36.566
3151721LOISA A
50/50
36.377
966001AG1-469 GEN
Solar/Wind Harmer
1.014
315651AD1-115 GEN
Solar/Wind Harmer
5.814
971489AH1-241 GEN
Solar/Wind Harmer
5.312
315821AE2-092 GEN
Solar/Wind Harmer
1.835
3146776BUCKING
Solar/Wind Harmer
-0.028
3146776BUCKING
Solar/Wind Harmer
-0.002
LAGNLTFEXP_LAGN->PJM
CLTF
1.272
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.087
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.452
MECLTFEXP_MEC->PJM
CLTF
0.994
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.624
TVALTFEXP_TVA->PJM
CLTF
0.66
SIGELTFEXP_SIGE->PJM
CLTF
0.032
NYPJM->LTFIMP_NY
CLTF
0.312
LGEELTFEXP_LGEE->PJM
CLTF
0.427
WECLTFEXP_WEC->PJM
CLTF
0.22
CPLELTFEXP_CPLE->PJM
CLTF
0.423
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.297

Details for 6LOISACT-6S ANNA 230.0 kV Ckt 1 line l/o DVP_P2-2: GERMANNA_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6LOISACT-6S ANNA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: GERMANNA_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:122.62 %
Rating:886.0 MVA
Rating Type:C
MVA to Mitigate:1086.44
MW Contribution:5.59
Bus #Bus NameTypeMW Contribution
3151731LOISA B
50/50
36.566
3151721LOISA A
50/50
36.377
966001AG1-469 GEN
Solar/Wind Harmer
1.014
315651AD1-115 GEN
Solar/Wind Harmer
5.814
971489AH1-241 GEN
Solar/Wind Harmer
5.312
315821AE2-092 GEN
Solar/Wind Harmer
1.835
3146776BUCKING
Solar/Wind Harmer
-0.028
3146776BUCKING
Solar/Wind Harmer
-0.002
3151741LOISA C
50/50
2
3151751LOISA D
50/50
36.566
316254AC1-120 GEN1
Solar/Wind Harmer
1.288
971377AH1-170 GEN
Solar/Wind Harmer
1.119
3147623JAMES R
Solar/Wind Harmer
0.138
972003AH1-546 GEN
Solar/Wind Harmer
4.372
970937AG2-583 GEN
Solar/Wind Harmer
5.019
316322AB2-045
Solar/Wind Harmer
0.234
3146776BUCKING
Solar/Wind Harmer
-0.003
316192AB2-158 GEN
Solar/Wind Helper
5.098
3147666LOUISA
Solar/Wind Helper
2.936
3151761LOISA E
50/50
74.547
972183AH1-676 GEN
50/50
589.467
3132273ORANGE
Solar/Wind Harmer
-0.007
316170AC1-121 GEN2
Solar/Wind Harmer
0.429
970221AG2-151 GEN
Solar/Wind Harmer
5.595
3148013FISHERV
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Harmer
-0.002
3147666LOUISA
Solar/Wind Helper
1.688
3147346CASHSCORNER
Solar/Wind Harmer
0.849
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
316164AC1-076 GEN
Solar/Wind Harmer
0.897
972205AH1-687 GEN
Adder
3.487
971447AH1-217 GEN
Solar/Wind Harmer
3.198
3148133STUARTS
Solar/Wind Harmer
-0.005
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
1.942
971845AH1-439 GEN
Solar/Wind Harmer
3.618
970285AG2-188 GEN
Solar/Wind Harmer
5.703
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.087
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.452
MECLTFEXP_MEC->PJM
CLTF
0.994
LAGNLTFEXP_LAGN->PJM
CLTF
1.272
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.624
TVALTFEXP_TVA->PJM
CLTF
0.66
SIGELTFEXP_SIGE->PJM
CLTF
0.032
CPLELTFEXP_CPLE->PJM
CLTF
0.423
NYPJM->LTFIMP_NY
CLTF
0.312
LGEELTFEXP_LGEE->PJM
CLTF
0.427
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.297
WECLTFEXP_WEC->PJM
CLTF
0.22

Details for 6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2199_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2199_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:167.53 %
Rating:819.68 MVA
Rating Type:B
MVA to Mitigate:1373.24
MW Contribution:4.16
Bus #Bus NameTypeMW Contribution
3151731LOISA B
50/50
36.446
3151721LOISA A
50/50
36.258
3151771S ANNAG1
50/50
1.912
3151801S ANNAS2
50/50
0.982
3151761LOISA E
50/50
74.304
972183AH1-676 GEN
50/50
587.5
3151921BEARGRDN G2
50/50
0.743
3132273ORANGE
Solar/Wind Harmer
0.067
316170AC1-121 GEN2
Solar/Wind Harmer
0.15
970221AG2-151 GEN
Solar/Wind Harmer
4.157
3148013FISHERV
Solar/Wind Harmer
0.074
3146776BUCKING
Solar/Wind Harmer
0.022
3147666LOUISA
Solar/Wind Helper
1.696
966001AG1-469 GEN
Solar/Wind Harmer
0.277
315651AD1-115 GEN
Solar/Wind Harmer
0.004
971489AH1-241 GEN
Solar/Wind Harmer
4.157
315821AE2-092 GEN
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.241
3146776BUCKING
Solar/Wind Harmer
0.019
3151791S ANNAG2
50/50
1.912
3151781S ANNAS1
50/50
0.982
3151741LOISA C
50/50
1.993
3151751LOISA D
50/50
36.446
3151931BEARGRDN S1
50/50
0.958
3151911BEARGRDN G1
50/50
0.743
316192AB2-158 GEN
Solar/Wind Harmer
4.181
315683AE1-153 C
Solar/Wind Harmer
41.163
316254AC1-120 GEN1
Solar/Wind Harmer
0.299
971377AH1-170 GEN
Solar/Wind Harmer
0.831
3147623JAMES R
Solar/Wind Harmer
0.181
972003AH1-546 GEN
Solar/Wind Harmer
3.241
970937AG2-583 GEN
Solar/Wind Harmer
3.705
316322AB2-045
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.024
3147666LOUISA
Solar/Wind Helper
2.95
972205AH1-687 GEN
50/50
3.622
3147346CASHSCORNER
Solar/Wind Harmer
1.128
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3138266HYDRAULIC
Solar/Wind Harmer
0.004
316164AC1-076 GEN
Solar/Wind Harmer
0.131
971447AH1-217 GEN
Solar/Wind Harmer
2.376
3148133STUARTS
Solar/Wind Harmer
0.044
3148013FISHERV
Solar/Wind Harmer
0.042
270494AE1-108_GEN
Solar/Wind Harmer
0.776
971845AH1-439 GEN
Solar/Wind Harmer
2.669
970285AG2-188 GEN
Solar/Wind Harmer
4.452
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.145
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.947
MECLTFEXP_MEC->PJM
CLTF
0.771
LAGNLTFEXP_LAGN->PJM
CLTF
1.002
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.222
TVALTFEXP_TVA->PJM
CLTF
0.525
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
0.277
NYPJM->LTFIMP_NY
CLTF
0.398
LGEELTFEXP_LGEE->PJM
CLTF
0.336
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.505
WECLTFEXP_WEC->PJM
CLTF
0.169

Details for 6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2331_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2331_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:162.71 %
Rating:819.68 MVA
Rating Type:B
MVA to Mitigate:1333.73
MW Contribution:4.16
Bus #Bus NameTypeMW Contribution
3151771S ANNAG1
50/50
1.912
3151801S ANNAS2
50/50
0.982
3151761LOISA E
50/50
74.304
972183AH1-676 GEN
50/50
587.5
3151921BEARGRDN G2
50/50
0.743
3132273ORANGE
Solar/Wind Harmer
0.067
316170AC1-121 GEN2
Solar/Wind Harmer
0.15
970221AG2-151 GEN
Solar/Wind Harmer
4.157
3148013FISHERV
Solar/Wind Harmer
0.074
3146776BUCKING
Solar/Wind Harmer
0.022
3147666LOUISA
Solar/Wind Helper
1.696
3151731LOISA B
50/50
36.446
3151721LOISA A
50/50
36.258
966001AG1-469 GEN
Solar/Wind Harmer
0.277
315651AD1-115 GEN
Solar/Wind Harmer
0.004
971489AH1-241 GEN
Solar/Wind Harmer
4.157
315821AE2-092 GEN
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.241
3146776BUCKING
Solar/Wind Harmer
0.019
3151791S ANNAG2
50/50
1.912
3151781S ANNAS1
50/50
0.982
3151741LOISA C
50/50
1.993
3151751LOISA D
50/50
36.446
3151931BEARGRDN S1
50/50
0.958
3151911BEARGRDN G1
50/50
0.743
316192AB2-158 GEN
Solar/Wind Harmer
4.181
315683AE1-153 C
Solar/Wind Harmer
41.163
316254AC1-120 GEN1
Solar/Wind Harmer
0.299
971377AH1-170 GEN
Solar/Wind Harmer
0.831
3147623JAMES R
Solar/Wind Harmer
0.181
972003AH1-546 GEN
Solar/Wind Harmer
3.241
970937AG2-583 GEN
Solar/Wind Harmer
3.705
316322AB2-045
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.024
3147666LOUISA
Solar/Wind Helper
2.95
972205AH1-687 GEN
50/50
3.622
3147346CASHSCORNER
Solar/Wind Harmer
1.128
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3138266HYDRAULIC
Solar/Wind Harmer
0.004
316164AC1-076 GEN
Solar/Wind Harmer
0.131
971447AH1-217 GEN
Solar/Wind Harmer
2.376
3148133STUARTS
Solar/Wind Harmer
0.044
3148013FISHERV
Solar/Wind Harmer
0.042
270494AE1-108_GEN
Solar/Wind Harmer
0.776
971845AH1-439 GEN
Solar/Wind Harmer
2.669
970285AG2-188 GEN
Solar/Wind Harmer
4.452
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.145
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.947
MECLTFEXP_MEC->PJM
CLTF
0.771
LAGNLTFEXP_LAGN->PJM
CLTF
1.002
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.222
TVALTFEXP_TVA->PJM
CLTF
0.525
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
0.277
NYPJM->LTFIMP_NY
CLTF
0.398
LGEELTFEXP_LGEE->PJM
CLTF
0.336
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.505
WECLTFEXP_WEC->PJM
CLTF
0.169

Details for 6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:160.76 %
Rating:1003.0 MVA
Rating Type:C
MVA to Mitigate:1612.42
MW Contribution:6.31
Bus #Bus NameTypeMW Contribution
3151731LOISA B
50/50
41.011
3151721LOISA A
50/50
40.799
966001AG1-469 GEN
Solar/Wind Harmer
1.242
971489AH1-241 GEN
Solar/Wind Harmer
5.993
315821AE2-092 GEN
Solar/Wind Harmer
2.063
3146776BUCKING
Solar/Wind Harmer
-0.031
3146776BUCKING
Solar/Wind Harmer
-0.003
3147346CASHSCORNER
Solar/Wind Harmer
0.957
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
972205AH1-687 GEN
Adder
3.94
971447AH1-217 GEN
Solar/Wind Harmer
3.605
3148133STUARTS
Solar/Wind Harmer
-0.006
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
2.184
971845AH1-439 GEN
Solar/Wind Harmer
4.1
970285AG2-188 GEN
Solar/Wind Harmer
6.466
3151791S ANNAG2
50/50
2.137
3151781S ANNAS1
50/50
1.098
3151741LOISA C
50/50
2.243
3151751LOISA D
50/50
41.011
316192AB2-158 GEN
Solar/Wind Harmer
10.432
315683AE1-153 C
Solar/Wind Harmer
61.269
971377AH1-170 GEN
Solar/Wind Harmer
1.262
3147623JAMES R
Solar/Wind Harmer
0.156
972003AH1-546 GEN
Solar/Wind Harmer
4.942
970937AG2-583 GEN
Solar/Wind Harmer
5.698
316322AB2-045
Solar/Wind Harmer
0.265
3146776BUCKING
Solar/Wind Harmer
-0.003
315705AF1-075 GEN
Solar/Wind Harmer
2.901
3147666LOUISA
Solar/Wind Helper
2.639
3151771S ANNAG1
50/50
2.137
3151801S ANNAS2
50/50
1.098
3151761LOISA E
50/50
83.609
972183AH1-676 GEN
50/50
664.157
970221AG2-151 GEN
Solar/Wind Harmer
6.312
3148013FISHERV
Solar/Wind Harmer
-0.009
3146776BUCKING
Solar/Wind Harmer
-0.003
316499AE2-029_GEN
Solar/Wind Harmer
0.52
3147666LOUISA
Solar/Wind Helper
1.517
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.354
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.41
MECLTFEXP_MEC->PJM
CLTF
0.932
LAGNLTFEXP_LAGN->PJM
CLTF
1.253
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.732
TVALTFEXP_TVA->PJM
CLTF
0.654
SIGELTFEXP_SIGE->PJM
CLTF
0.03
CPLELTFEXP_CPLE->PJM
CLTF
0.472
NYPJM->LTFIMP_NY
CLTF
0.481
LGEELTFEXP_LGEE->PJM
CLTF
0.402
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.001
WECLTFEXP_WEC->PJM
CLTF
0.203

Details for 6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:154.66 %
Rating:1003.0 MVA
Rating Type:C
MVA to Mitigate:1551.24
MW Contribution:6.31
Bus #Bus NameTypeMW Contribution
3147346CASHSCORNER
Solar/Wind Harmer
0.957
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
972205AH1-687 GEN
Adder
3.94
971447AH1-217 GEN
Solar/Wind Harmer
3.605
3148133STUARTS
Solar/Wind Harmer
-0.006
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
2.184
971845AH1-439 GEN
Solar/Wind Harmer
4.1
970285AG2-188 GEN
Solar/Wind Harmer
6.466
3151771S ANNAG1
50/50
2.137
3151801S ANNAS2
50/50
1.098
3151761LOISA E
50/50
83.609
972183AH1-676 GEN
50/50
664.157
970221AG2-151 GEN
Solar/Wind Harmer
6.312
3148013FISHERV
Solar/Wind Harmer
-0.009
3146776BUCKING
Solar/Wind Harmer
-0.003
316499AE2-029_GEN
Solar/Wind Harmer
0.52
3147666LOUISA
Solar/Wind Helper
1.517
3151731LOISA B
50/50
41.011
3151721LOISA A
50/50
40.799
966001AG1-469 GEN
Solar/Wind Harmer
1.242
971489AH1-241 GEN
Solar/Wind Harmer
5.993
315821AE2-092 GEN
Solar/Wind Harmer
2.063
3146776BUCKING
Solar/Wind Harmer
-0.031
3146776BUCKING
Solar/Wind Harmer
-0.003
3151791S ANNAG2
50/50
2.137
3151781S ANNAS1
50/50
1.098
3151741LOISA C
50/50
2.243
3151751LOISA D
50/50
41.011
316192AB2-158 GEN
Solar/Wind Harmer
10.432
971377AH1-170 GEN
Solar/Wind Harmer
1.262
3147623JAMES R
Solar/Wind Harmer
0.156
972003AH1-546 GEN
Solar/Wind Harmer
4.942
970937AG2-583 GEN
Solar/Wind Harmer
5.698
316322AB2-045
Solar/Wind Harmer
0.265
3146776BUCKING
Solar/Wind Harmer
-0.003
315705AF1-075 GEN
Solar/Wind Harmer
2.901
3147666LOUISA
Solar/Wind Helper
2.639
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.354
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.41
MECLTFEXP_MEC->PJM
CLTF
0.932
LAGNLTFEXP_LAGN->PJM
CLTF
1.253
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.732
TVALTFEXP_TVA->PJM
CLTF
0.654
SIGELTFEXP_SIGE->PJM
CLTF
0.03
CPLELTFEXP_CPLE->PJM
CLTF
0.472
NYPJM->LTFIMP_NY
CLTF
0.481
LGEELTFEXP_LGEE->PJM
CLTF
0.402
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.001
WECLTFEXP_WEC->PJM
CLTF
0.203

Details for 6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line l/o DVP_P4-2: 2199T2331_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2199T2331_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:140.15 %
Rating:1003.0 MVA
Rating Type:C
MVA to Mitigate:1405.73
MW Contribution:5.47
Bus #Bus NameTypeMW Contribution
3147346CASHSCORNER
Solar/Wind Harmer
0.846
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
316164AC1-076 GEN
Solar/Wind Harmer
0.881
972205AH1-687 GEN
Adder
3.413
971447AH1-217 GEN
Solar/Wind Harmer
3.128
3148133STUARTS
Solar/Wind Harmer
-0.005
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
1.891
971845AH1-439 GEN
Solar/Wind Harmer
3.515
970285AG2-188 GEN
Solar/Wind Harmer
5.533
3151791S ANNAG2
50/50
1.912
3151781S ANNAS1
50/50
0.982
3151741LOISA C
50/50
1.993
3151751LOISA D
50/50
36.446
316192AB2-158 GEN
Solar/Wind Harmer
9.886
315683AE1-153 C
Solar/Wind Harmer
54.197
316254AC1-120 GEN1
Solar/Wind Harmer
1.273
971377AH1-170 GEN
Solar/Wind Harmer
1.095
3147623JAMES R
Solar/Wind Harmer
0.135
972003AH1-546 GEN
Solar/Wind Harmer
4.275
970937AG2-583 GEN
Solar/Wind Harmer
4.879
316322AB2-045
Solar/Wind Harmer
0.228
3146776BUCKING
Solar/Wind Harmer
-0.003
3147666LOUISA
Solar/Wind Helper
2.95
3151771S ANNAG1
50/50
1.912
3151801S ANNAS2
50/50
0.982
3151761LOISA E
50/50
74.304
972183AH1-676 GEN
50/50
587.5
3132273ORANGE
Solar/Wind Harmer
-0.007
316170AC1-121 GEN2
Solar/Wind Harmer
0.424
970221AG2-151 GEN
Solar/Wind Harmer
5.473
3148013FISHERV
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Harmer
-0.002
3147666LOUISA
Solar/Wind Helper
1.696
3151731LOISA B
50/50
36.446
3151721LOISA A
50/50
36.258
966001AG1-469 GEN
Solar/Wind Harmer
1.01
315651AD1-115 GEN
Solar/Wind Harmer
5.728
971489AH1-241 GEN
Solar/Wind Harmer
5.196
315821AE2-092 GEN
Solar/Wind Harmer
1.795
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
LAGNLTFEXP_LAGN->PJM
CLTF
1.002
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.145
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.947
MECLTFEXP_MEC->PJM
CLTF
0.771
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.222
TVALTFEXP_TVA->PJM
CLTF
0.525
SIGELTFEXP_SIGE->PJM
CLTF
0.025
NYPJM->LTFIMP_NY
CLTF
0.398
LGEELTFEXP_LGEE->PJM
CLTF
0.336
WECLTFEXP_WEC->PJM
CLTF
0.169
CPLELTFEXP_CPLE->PJM
CLTF
0.277
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.505

Details for 6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line l/o DVP_P4-2: 2278T2331_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2278T2331_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:136.11 %
Rating:1003.0 MVA
Rating Type:C
MVA to Mitigate:1365.2
MW Contribution:5.47
Bus #Bus NameTypeMW Contribution
3151791S ANNAG2
50/50
1.912
3151781S ANNAS1
50/50
0.982
3151741LOISA C
50/50
1.993
3151751LOISA D
50/50
36.446
316192AB2-158 GEN
Solar/Wind Harmer
9.886
315683AE1-153 C
Solar/Wind Harmer
54.197
316254AC1-120 GEN1
Solar/Wind Harmer
1.273
971377AH1-170 GEN
Solar/Wind Harmer
1.095
3147623JAMES R
Solar/Wind Harmer
0.135
972003AH1-546 GEN
Solar/Wind Harmer
4.275
970937AG2-583 GEN
Solar/Wind Harmer
4.879
316322AB2-045
Solar/Wind Harmer
0.228
3146776BUCKING
Solar/Wind Harmer
-0.003
3147666LOUISA
Solar/Wind Helper
2.95
3151771S ANNAG1
50/50
1.912
3151801S ANNAS2
50/50
0.982
3151761LOISA E
50/50
74.304
972183AH1-676 GEN
50/50
587.5
3132273ORANGE
Solar/Wind Harmer
-0.007
316170AC1-121 GEN2
Solar/Wind Harmer
0.424
970221AG2-151 GEN
Solar/Wind Harmer
5.473
3148013FISHERV
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Harmer
-0.002
3147666LOUISA
Solar/Wind Helper
1.696
3147346CASHSCORNER
Solar/Wind Harmer
0.846
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
316164AC1-076 GEN
Solar/Wind Harmer
0.881
972205AH1-687 GEN
Adder
3.413
971447AH1-217 GEN
Solar/Wind Harmer
3.128
3148133STUARTS
Solar/Wind Harmer
-0.005
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
1.891
971845AH1-439 GEN
Solar/Wind Harmer
3.515
970285AG2-188 GEN
Solar/Wind Harmer
5.533
3151731LOISA B
50/50
36.446
3151721LOISA A
50/50
36.258
966001AG1-469 GEN
Solar/Wind Harmer
1.01
315651AD1-115 GEN
Solar/Wind Harmer
5.728
971489AH1-241 GEN
Solar/Wind Harmer
5.196
315821AE2-092 GEN
Solar/Wind Harmer
1.795
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
LAGNLTFEXP_LAGN->PJM
CLTF
1.002
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.145
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.947
MECLTFEXP_MEC->PJM
CLTF
0.771
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.222
TVALTFEXP_TVA->PJM
CLTF
0.525
SIGELTFEXP_SIGE->PJM
CLTF
0.025
NYPJM->LTFIMP_NY
CLTF
0.398
LGEELTFEXP_LGEE->PJM
CLTF
0.336
WECLTFEXP_WEC->PJM
CLTF
0.169
CPLELTFEXP_CPLE->PJM
CLTF
0.277
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.505

Details for 6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line l/o DVP_P2-2: GERMANNA_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: GERMANNA_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:134.77 %
Rating:1003.0 MVA
Rating Type:C
MVA to Mitigate:1351.71
MW Contribution:5.47
Bus #Bus NameTypeMW Contribution
3151731LOISA B
50/50
36.446
3151721LOISA A
50/50
36.258
966001AG1-469 GEN
Solar/Wind Harmer
1.01
315651AD1-115 GEN
Solar/Wind Harmer
5.728
971489AH1-241 GEN
Solar/Wind Harmer
5.196
315821AE2-092 GEN
Solar/Wind Harmer
1.795
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
3147346CASHSCORNER
Solar/Wind Harmer
0.846
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
316164AC1-076 GEN
Solar/Wind Harmer
0.881
972205AH1-687 GEN
Adder
3.413
971447AH1-217 GEN
Solar/Wind Harmer
3.128
3148133STUARTS
Solar/Wind Harmer
-0.005
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
1.891
971845AH1-439 GEN
Solar/Wind Harmer
3.515
970285AG2-188 GEN
Solar/Wind Harmer
5.533
3151791S ANNAG2
50/50
1.912
3151781S ANNAS1
50/50
0.982
3151741LOISA C
50/50
1.993
3151751LOISA D
50/50
36.446
316192AB2-158 GEN
Solar/Wind Harmer
9.886
316254AC1-120 GEN1
Solar/Wind Harmer
1.273
971377AH1-170 GEN
Solar/Wind Harmer
1.095
3147623JAMES R
Solar/Wind Harmer
0.135
972003AH1-546 GEN
Solar/Wind Harmer
4.275
970937AG2-583 GEN
Solar/Wind Harmer
4.879
316322AB2-045
Solar/Wind Harmer
0.228
3146776BUCKING
Solar/Wind Harmer
-0.003
3147666LOUISA
Solar/Wind Helper
2.95
3151771S ANNAG1
50/50
1.912
3151801S ANNAS2
50/50
0.982
3151761LOISA E
50/50
74.304
972183AH1-676 GEN
50/50
587.5
3132273ORANGE
Solar/Wind Harmer
-0.007
316170AC1-121 GEN2
Solar/Wind Harmer
0.424
970221AG2-151 GEN
Solar/Wind Harmer
5.473
3148013FISHERV
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Harmer
-0.002
3147666LOUISA
Solar/Wind Helper
1.696
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.145
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.947
MECLTFEXP_MEC->PJM
CLTF
0.771
LAGNLTFEXP_LAGN->PJM
CLTF
1.002
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.222
TVALTFEXP_TVA->PJM
CLTF
0.525
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
0.277
NYPJM->LTFIMP_NY
CLTF
0.398
LGEELTFEXP_LGEE->PJM
CLTF
0.336
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.505
WECLTFEXP_WEC->PJM
CLTF
0.169

Details for 6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2199_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2199_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:145.7 %
Rating:819.68 MVA
Rating Type:B
MVA to Mitigate:1194.24
MW Contribution:4.15
Bus #Bus NameTypeMW Contribution
3151791S ANNAG2
50/50
1.911
3151781S ANNAS1
50/50
0.982
3151741LOISA C
50/50
1.992
3151751LOISA D
50/50
36.435
3151931BEARGRDN S1
50/50
0.956
3151911BEARGRDN G1
50/50
0.741
3147666LOUISA
Solar/Wind Harmer
3.006
316192AB2-158 GEN
Solar/Wind Harmer
4.18
315683AE1-153 C
Solar/Wind Harmer
41.15
316254AC1-120 GEN1
Solar/Wind Harmer
0.299
971377AH1-170 GEN
Solar/Wind Harmer
0.83
3147623JAMES R
Solar/Wind Harmer
0.18
972003AH1-546 GEN
Solar/Wind Harmer
3.234
970937AG2-583 GEN
Solar/Wind Harmer
3.695
316322AB2-045
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.024
972205AH1-687 GEN
50/50
3.614
3147346CASHSCORNER
Solar/Wind Harmer
1.128
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3138266HYDRAULIC
Solar/Wind Harmer
0.004
316164AC1-076 GEN
Solar/Wind Harmer
0.13
971447AH1-217 GEN
Solar/Wind Harmer
2.371
3148133STUARTS
Solar/Wind Harmer
0.044
3148013FISHERV
Solar/Wind Harmer
0.042
270494AE1-108_GEN
Solar/Wind Harmer
0.774
971845AH1-439 GEN
Solar/Wind Harmer
2.662
3151771S ANNAG1
50/50
1.911
3151801S ANNAS2
50/50
0.982
3151761LOISA E
50/50
74.281
972183AH1-676 GEN
50/50
587.315
3151921BEARGRDN G2
50/50
0.741
3147666LOUISA
Solar/Wind Harmer
1.729
3132273ORANGE
Solar/Wind Harmer
0.067
316170AC1-121 GEN2
Solar/Wind Harmer
0.15
970221AG2-151 GEN
Solar/Wind Harmer
4.148
3148013FISHERV
Solar/Wind Harmer
0.074
3146776BUCKING
Solar/Wind Harmer
0.022
3151731LOISA B
50/50
36.435
3151721LOISA A
50/50
36.247
966001AG1-469 GEN
Solar/Wind Harmer
0.277
315651AD1-115 GEN
Solar/Wind Harmer
0.004
971489AH1-241 GEN
Solar/Wind Harmer
4.148
315821AE2-092 GEN
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.24
3146776BUCKING
Solar/Wind Harmer
0.019
LAGNLTFEXP_LAGN->PJM
CLTF
0.977
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.963
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.899
MECLTFEXP_MEC->PJM
CLTF
0.75
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.184
TVALTFEXP_TVA->PJM
CLTF
0.512
NYPJM->LTFIMP_NY
CLTF
0.406
LGEELTFEXP_LGEE->PJM
CLTF
0.327
WECLTFEXP_WEC->PJM
CLTF
0.165
CPLELTFEXP_CPLE->PJM
CLTF
0.264
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.337

Details for 6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:142.58 %
Rating:1003.0 MVA
Rating Type:C
MVA to Mitigate:1430.1
MW Contribution:6.3
Bus #Bus NameTypeMW Contribution
3147346CASHSCORNER
Solar/Wind Harmer
0.957
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
972205AH1-687 GEN
Adder
3.933
971447AH1-217 GEN
Solar/Wind Harmer
3.598
3148133STUARTS
Solar/Wind Harmer
-0.006
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
2.18
971845AH1-439 GEN
Solar/Wind Harmer
4.09
3151791S ANNAG2
50/50
2.136
3151781S ANNAS1
50/50
1.098
3151741LOISA C
50/50
2.242
3151771S ANNAG1
50/50
2.136
3151801S ANNAS2
50/50
1.098
3151761LOISA E
50/50
83.586
972183AH1-676 GEN
50/50
663.972
3147666LOUISA
Solar/Wind Harmer
-0.203
970221AG2-151 GEN
Solar/Wind Harmer
6.301
3148013FISHERV
Solar/Wind Harmer
-0.009
3146776BUCKING
Solar/Wind Harmer
-0.003
316499AE2-029_GEN
Solar/Wind Harmer
0.518
3151731LOISA B
50/50
41
3151721LOISA A
50/50
40.788
966001AG1-469 GEN
Solar/Wind Harmer
1.242
971489AH1-241 GEN
Solar/Wind Harmer
5.982
315821AE2-092 GEN
Solar/Wind Harmer
2.06
3146776BUCKING
Solar/Wind Harmer
-0.031
3146776BUCKING
Solar/Wind Harmer
-0.003
970285AG2-188 GEN
Solar/Wind Harmer
6.451
3151751LOISA D
50/50
41
3147666LOUISA
Solar/Wind Harmer
-0.354
316192AB2-158 GEN
Solar/Wind Harmer
10.429
315683AE1-153 C
Solar/Wind Harmer
61.252
971377AH1-170 GEN
Solar/Wind Harmer
1.26
3147623JAMES R
Solar/Wind Harmer
0.156
972003AH1-546 GEN
Solar/Wind Harmer
4.933
970937AG2-583 GEN
Solar/Wind Harmer
5.684
316322AB2-045
Solar/Wind Harmer
0.265
3146776BUCKING
Solar/Wind Harmer
-0.003
315705AF1-075 GEN
Solar/Wind Harmer
2.892
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.172
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.363
MECLTFEXP_MEC->PJM
CLTF
0.912
LAGNLTFEXP_LAGN->PJM
CLTF
1.228
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.694
TVALTFEXP_TVA->PJM
CLTF
0.641
SIGELTFEXP_SIGE->PJM
CLTF
0.03
CPLELTFEXP_CPLE->PJM
CLTF
0.459
NYPJM->LTFIMP_NY
CLTF
0.489
LGEELTFEXP_LGEE->PJM
CLTF
0.394
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.833
WECLTFEXP_WEC->PJM
CLTF
0.198

Details for 6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2331_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2331_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:140.96 %
Rating:819.68 MVA
Rating Type:B
MVA to Mitigate:1155.44
MW Contribution:4.15
Bus #Bus NameTypeMW Contribution
3151731LOISA B
50/50
36.435
3151721LOISA A
50/50
36.247
966001AG1-469 GEN
Solar/Wind Harmer
0.277
315651AD1-115 GEN
Solar/Wind Harmer
0.004
971489AH1-241 GEN
Solar/Wind Harmer
4.148
315821AE2-092 GEN
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.24
3146776BUCKING
Solar/Wind Harmer
0.019
972205AH1-687 GEN
50/50
3.614
3147346CASHSCORNER
Solar/Wind Harmer
1.128
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3138266HYDRAULIC
Solar/Wind Harmer
0.004
316164AC1-076 GEN
Solar/Wind Harmer
0.13
971447AH1-217 GEN
Solar/Wind Harmer
2.371
3148133STUARTS
Solar/Wind Harmer
0.044
3148013FISHERV
Solar/Wind Harmer
0.042
270494AE1-108_GEN
Solar/Wind Harmer
0.774
971845AH1-439 GEN
Solar/Wind Harmer
2.662
3151791S ANNAG2
50/50
1.911
3151781S ANNAS1
50/50
0.982
3151741LOISA C
50/50
1.992
3151751LOISA D
50/50
36.435
3151931BEARGRDN S1
50/50
0.956
3151911BEARGRDN G1
50/50
0.741
3147666LOUISA
Solar/Wind Harmer
3.006
316192AB2-158 GEN
Solar/Wind Harmer
4.18
315683AE1-153 C
Solar/Wind Harmer
41.15
316254AC1-120 GEN1
Solar/Wind Harmer
0.299
971377AH1-170 GEN
Solar/Wind Harmer
0.83
3147623JAMES R
Solar/Wind Harmer
0.18
972003AH1-546 GEN
Solar/Wind Harmer
3.234
970937AG2-583 GEN
Solar/Wind Harmer
3.695
316322AB2-045
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.024
3151771S ANNAG1
50/50
1.911
3151801S ANNAS2
50/50
0.982
3151761LOISA E
50/50
74.281
972183AH1-676 GEN
50/50
587.315
3151921BEARGRDN G2
50/50
0.741
3147666LOUISA
Solar/Wind Harmer
1.729
3132273ORANGE
Solar/Wind Harmer
0.067
316170AC1-121 GEN2
Solar/Wind Harmer
0.15
970221AG2-151 GEN
Solar/Wind Harmer
4.148
3148013FISHERV
Solar/Wind Harmer
0.074
3146776BUCKING
Solar/Wind Harmer
0.022
LAGNLTFEXP_LAGN->PJM
CLTF
0.977
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.963
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.899
MECLTFEXP_MEC->PJM
CLTF
0.75
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.184
TVALTFEXP_TVA->PJM
CLTF
0.512
NYPJM->LTFIMP_NY
CLTF
0.406
LGEELTFEXP_LGEE->PJM
CLTF
0.327
WECLTFEXP_WEC->PJM
CLTF
0.165
CPLELTFEXP_CPLE->PJM
CLTF
0.264
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.337

Details for 6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:136.48 %
Rating:1003.0 MVA
Rating Type:C
MVA to Mitigate:1368.92
MW Contribution:6.3
Bus #Bus NameTypeMW Contribution
3151731LOISA B
50/50
41
3151721LOISA A
50/50
40.788
966001AG1-469 GEN
Solar/Wind Harmer
1.242
971489AH1-241 GEN
Solar/Wind Harmer
5.982
315821AE2-092 GEN
Solar/Wind Harmer
2.06
3146776BUCKING
Solar/Wind Harmer
-0.031
3146776BUCKING
Solar/Wind Harmer
-0.003
3147346CASHSCORNER
Solar/Wind Harmer
0.957
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
972205AH1-687 GEN
Adder
3.933
971447AH1-217 GEN
Solar/Wind Harmer
3.598
3148133STUARTS
Solar/Wind Harmer
-0.006
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
2.18
971845AH1-439 GEN
Solar/Wind Harmer
4.09
970285AG2-188 GEN
Solar/Wind Harmer
6.451
3151791S ANNAG2
50/50
2.136
3151781S ANNAS1
50/50
1.098
3151741LOISA C
50/50
2.242
3151751LOISA D
50/50
41
3147666LOUISA
Solar/Wind Harmer
-0.354
316192AB2-158 GEN
Solar/Wind Harmer
10.429
971377AH1-170 GEN
Solar/Wind Harmer
1.26
3147623JAMES R
Solar/Wind Harmer
0.156
972003AH1-546 GEN
Solar/Wind Harmer
4.933
970937AG2-583 GEN
Solar/Wind Harmer
5.684
316322AB2-045
Solar/Wind Harmer
0.265
3146776BUCKING
Solar/Wind Harmer
-0.003
315705AF1-075 GEN
Solar/Wind Harmer
2.892
3151771S ANNAG1
50/50
2.136
3151801S ANNAS2
50/50
1.098
3151761LOISA E
50/50
83.586
972183AH1-676 GEN
50/50
663.972
3147666LOUISA
Solar/Wind Harmer
-0.203
970221AG2-151 GEN
Solar/Wind Harmer
6.301
3148013FISHERV
Solar/Wind Harmer
-0.009
3146776BUCKING
Solar/Wind Harmer
-0.003
316499AE2-029_GEN
Solar/Wind Harmer
0.518
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.172
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.363
MECLTFEXP_MEC->PJM
CLTF
0.912
LAGNLTFEXP_LAGN->PJM
CLTF
1.228
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.694
TVALTFEXP_TVA->PJM
CLTF
0.641
SIGELTFEXP_SIGE->PJM
CLTF
0.03
CPLELTFEXP_CPLE->PJM
CLTF
0.459
NYPJM->LTFIMP_NY
CLTF
0.489
LGEELTFEXP_LGEE->PJM
CLTF
0.394
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.833
WECLTFEXP_WEC->PJM
CLTF
0.198

Details for 6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2199T2331_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2199T2331_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.7 %
Rating:1003.0 MVA
Rating Type:C
MVA to Mitigate:1220.62
MW Contribution:5.46
Bus #Bus NameTypeMW Contribution
3147346CASHSCORNER
Solar/Wind Harmer
0.846
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
316164AC1-076 GEN
Solar/Wind Harmer
0.879
972205AH1-687 GEN
Adder
3.406
971447AH1-217 GEN
Solar/Wind Harmer
3.122
3148133STUARTS
Solar/Wind Harmer
-0.005
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
1.886
971845AH1-439 GEN
Solar/Wind Harmer
3.505
3151791S ANNAG2
50/50
1.911
3151781S ANNAS1
50/50
0.982
3151741LOISA C
50/50
1.992
3151751LOISA D
50/50
36.435
3147666LOUISA
Solar/Wind Harmer
-0.336
316192AB2-158 GEN
Solar/Wind Harmer
9.884
3151731LOISA B
50/50
36.435
3151721LOISA A
50/50
36.247
966001AG1-469 GEN
Solar/Wind Harmer
1.01
315651AD1-115 GEN
Solar/Wind Harmer
5.72
971489AH1-241 GEN
Solar/Wind Harmer
5.185
315821AE2-092 GEN
Solar/Wind Harmer
1.791
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
3151771S ANNAG1
50/50
1.911
3151801S ANNAS2
50/50
0.982
3151761LOISA E
50/50
74.281
972183AH1-676 GEN
50/50
587.315
3147666LOUISA
Solar/Wind Harmer
-0.193
3132273ORANGE
Solar/Wind Harmer
-0.007
316170AC1-121 GEN2
Solar/Wind Harmer
0.424
970221AG2-151 GEN
Solar/Wind Harmer
5.462
3148013FISHERV
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Harmer
-0.002
315683AE1-153 C
Solar/Wind Harmer
54.18
316254AC1-120 GEN1
Solar/Wind Harmer
1.271
971377AH1-170 GEN
Solar/Wind Harmer
1.092
3147623JAMES R
Solar/Wind Harmer
0.135
972003AH1-546 GEN
Solar/Wind Harmer
4.266
970937AG2-583 GEN
Solar/Wind Harmer
4.865
316322AB2-045
Solar/Wind Harmer
0.227
3146776BUCKING
Solar/Wind Harmer
-0.003
LAGNLTFEXP_LAGN->PJM
CLTF
0.977
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.963
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.899
MECLTFEXP_MEC->PJM
CLTF
0.75
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.184
TVALTFEXP_TVA->PJM
CLTF
0.512
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
0.264
NYPJM->LTFIMP_NY
CLTF
0.406
LGEELTFEXP_LGEE->PJM
CLTF
0.327
WECLTFEXP_WEC->PJM
CLTF
0.165
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.337

Details for 6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2278T2331_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2278T2331_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.73 %
Rating:1003.0 MVA
Rating Type:C
MVA to Mitigate:1180.84
MW Contribution:5.46
Bus #Bus NameTypeMW Contribution
3151771S ANNAG1
50/50
1.911
3151801S ANNAS2
50/50
0.982
3151761LOISA E
50/50
74.281
972183AH1-676 GEN
50/50
587.315
3147666LOUISA
Solar/Wind Harmer
-0.193
3132273ORANGE
Solar/Wind Harmer
-0.007
316170AC1-121 GEN2
Solar/Wind Harmer
0.424
970221AG2-151 GEN
Solar/Wind Harmer
5.462
3148013FISHERV
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Harmer
-0.002
3151791S ANNAG2
50/50
1.911
3151781S ANNAS1
50/50
0.982
3151741LOISA C
50/50
1.992
3151751LOISA D
50/50
36.435
3147666LOUISA
Solar/Wind Harmer
-0.336
316192AB2-158 GEN
Solar/Wind Harmer
9.884
315683AE1-153 C
Solar/Wind Harmer
54.18
316254AC1-120 GEN1
Solar/Wind Harmer
1.271
971377AH1-170 GEN
Solar/Wind Harmer
1.092
3147623JAMES R
Solar/Wind Harmer
0.135
972003AH1-546 GEN
Solar/Wind Harmer
4.266
970937AG2-583 GEN
Solar/Wind Harmer
4.865
316322AB2-045
Solar/Wind Harmer
0.227
3146776BUCKING
Solar/Wind Harmer
-0.003
3151731LOISA B
50/50
36.435
3151721LOISA A
50/50
36.247
966001AG1-469 GEN
Solar/Wind Harmer
1.01
315651AD1-115 GEN
Solar/Wind Harmer
5.72
971489AH1-241 GEN
Solar/Wind Harmer
5.185
315821AE2-092 GEN
Solar/Wind Harmer
1.791
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
3147346CASHSCORNER
Solar/Wind Harmer
0.846
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
316164AC1-076 GEN
Solar/Wind Harmer
0.879
972205AH1-687 GEN
Adder
3.406
971447AH1-217 GEN
Solar/Wind Harmer
3.122
3148133STUARTS
Solar/Wind Harmer
-0.005
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
1.886
971845AH1-439 GEN
Solar/Wind Harmer
3.505
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.963
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.899
MECLTFEXP_MEC->PJM
CLTF
0.75
LAGNLTFEXP_LAGN->PJM
CLTF
0.977
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.184
TVALTFEXP_TVA->PJM
CLTF
0.512
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
0.264
NYPJM->LTFIMP_NY
CLTF
0.406
LGEELTFEXP_LGEE->PJM
CLTF
0.327
WECLTFEXP_WEC->PJM
CLTF
0.165
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.337

Details for 6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line l/o DVP_P2-2: GERMANNA_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: GERMANNA_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:116.31 %
Rating:1003.0 MVA
Rating Type:C
MVA to Mitigate:1166.61
MW Contribution:5.46
Bus #Bus NameTypeMW Contribution
3147346CASHSCORNER
Solar/Wind Harmer
0.846
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
316164AC1-076 GEN
Solar/Wind Harmer
0.879
972205AH1-687 GEN
Adder
3.406
971447AH1-217 GEN
Solar/Wind Harmer
3.122
3148133STUARTS
Solar/Wind Harmer
-0.005
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
1.886
971845AH1-439 GEN
Solar/Wind Harmer
3.505
3151731LOISA B
50/50
36.435
3151721LOISA A
50/50
36.247
966001AG1-469 GEN
Solar/Wind Harmer
1.01
315651AD1-115 GEN
Solar/Wind Harmer
5.72
971489AH1-241 GEN
Solar/Wind Harmer
5.185
3151771S ANNAG1
50/50
1.911
3151801S ANNAS2
50/50
0.982
3151761LOISA E
50/50
74.281
972183AH1-676 GEN
50/50
587.315
3147666LOUISA
Solar/Wind Harmer
-0.193
3132273ORANGE
Solar/Wind Harmer
-0.007
316170AC1-121 GEN2
Solar/Wind Harmer
0.424
970221AG2-151 GEN
Solar/Wind Harmer
5.462
3148013FISHERV
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Harmer
-0.002
315821AE2-092 GEN
Solar/Wind Harmer
1.791
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
3151791S ANNAG2
50/50
1.911
3151781S ANNAS1
50/50
0.982
3151741LOISA C
50/50
1.992
3151751LOISA D
50/50
36.435
3147666LOUISA
Solar/Wind Harmer
-0.336
316192AB2-158 GEN
Solar/Wind Harmer
9.884
316254AC1-120 GEN1
Solar/Wind Harmer
1.271
971377AH1-170 GEN
Solar/Wind Harmer
1.092
3147623JAMES R
Solar/Wind Harmer
0.135
972003AH1-546 GEN
Solar/Wind Harmer
4.266
970937AG2-583 GEN
Solar/Wind Harmer
4.865
316322AB2-045
Solar/Wind Harmer
0.227
3146776BUCKING
Solar/Wind Harmer
-0.003
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.963
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.899
MECLTFEXP_MEC->PJM
CLTF
0.75
LAGNLTFEXP_LAGN->PJM
CLTF
0.977
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.184
TVALTFEXP_TVA->PJM
CLTF
0.512
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
0.264
NYPJM->LTFIMP_NY
CLTF
0.406
LGEELTFEXP_LGEE->PJM
CLTF
0.327
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.337
WECLTFEXP_WEC->PJM
CLTF
0.165

Details for 6LUCKYHILL-6REMNGTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2304_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6LUCKYHILL-6REMNGTN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2304_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.93 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1052.42
MW Contribution:3.93
Bus #Bus NameTypeMW Contribution
3151731LOISA B
50/50
29.856
3151721LOISA A
50/50
29.702
966001AG1-469 GEN
Solar/Wind Harmer
0.231
971489AH1-241 GEN
Solar/Wind Harmer
3.929
315821AE2-092 GEN
Solar/Wind Harmer
0.004
315651AD1-115 GEN
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.242
3146776BUCKING
Solar/Wind Harmer
0.02
972183AH1-676 GEN
50/50
491.529
3151761LOISA E
50/50
60.868
3151771S ANNAG1
50/50
1.517
3151801S ANNAS2
50/50
0.779
3151921BEARGRDN G2
50/50
0.706
3132273ORANGE
Solar/Wind Harmer
0.054
316170AC1-121 GEN2
Solar/Wind Harmer
0.101
970221AG2-151 GEN
Solar/Wind Harmer
3.929
3148013FISHERV
Solar/Wind Harmer
0.066
3146776BUCKING
Solar/Wind Harmer
0.022
972205AH1-687 GEN
50/50
3.443
3147346CASHSCORNER
Solar/Wind Harmer
0.945
3138266HYDRAULIC
Solar/Wind Harmer
0.006
3138266HYDRAULIC
Solar/Wind Harmer
0.004
971447AH1-217 GEN
Solar/Wind Harmer
2.235
316164AC1-076 GEN
Solar/Wind Harmer
0.1
3148133STUARTS
Solar/Wind Harmer
0.04
3148013FISHERV
Solar/Wind Harmer
0.038
270494AE1-108_GEN
Solar/Wind Harmer
0.739
971845AH1-439 GEN
Solar/Wind Harmer
2.694
970285AG2-188 GEN
Solar/Wind Harmer
4.539
3151741LOISA C
50/50
1.633
3151751LOISA D
50/50
29.856
3151791S ANNAG2
50/50
1.517
3151781S ANNAS1
50/50
0.779
3151931BEARGRDN S1
50/50
0.911
3151911BEARGRDN G1
50/50
0.706
315683AE1-153 C
Solar/Wind Harmer
52.577
316192AB2-158 GEN
Solar/Wind Harmer
2.449
316254AC1-120 GEN1
Solar/Wind Harmer
0.201
971377AH1-170 GEN
Solar/Wind Harmer
0.786
3147623JAMES R
Solar/Wind Harmer
0.171
972003AH1-546 GEN
Solar/Wind Harmer
3.107
970937AG2-583 GEN
Solar/Wind Harmer
3.763
316322AB2-045
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.024
LAGNLTFEXP_LAGN->PJM
CLTF
1.34
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.412
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.486
MECLTFEXP_MEC->PJM
CLTF
0.864
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.634
TVALTFEXP_TVA->PJM
CLTF
0.692
SIGELTFEXP_SIGE->PJM
CLTF
0.028
NYPJM->LTFIMP_NY
CLTF
0.531
LGEELTFEXP_LGEE->PJM
CLTF
0.36
WECLTFEXP_WEC->PJM
CLTF
0.18
CPLELTFEXP_CPLE->PJM
CLTF
0.975
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.999

Details for 6LUCKYHILL-6REMNGTN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2202_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6LUCKYHILL-6REMNGTN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2202_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.73 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1030.78
MW Contribution:3.94
Bus #Bus NameTypeMW Contribution
3151741LOISA C
50/50
1.633
3151791S ANNAG2
50/50
1.517
3151781S ANNAS1
50/50
0.78
3151751LOISA D
50/50
29.866
3151931BEARGRDN S1
50/50
0.913
3151911BEARGRDN G1
50/50
0.707
315683AE1-153 C
Solar/Wind Harmer
52.588
316254AC1-120 GEN1
Solar/Wind Harmer
0.201
971377AH1-170 GEN
Solar/Wind Harmer
0.787
3147623JAMES R
Solar/Wind Harmer
0.171
972003AH1-546 GEN
Solar/Wind Harmer
3.113
970937AG2-583 GEN
Solar/Wind Harmer
3.772
316322AB2-045
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.024
3151731LOISA B
50/50
29.866
3151721LOISA A
50/50
29.712
966001AG1-469 GEN
Solar/Wind Harmer
0.231
971489AH1-241 GEN
Solar/Wind Harmer
3.937
315821AE2-092 GEN
Solar/Wind Harmer
0.004
315651AD1-115 GEN
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.242
3146776BUCKING
Solar/Wind Harmer
0.02
972205AH1-687 GEN
50/50
3.45
3147346CASHSCORNER
Solar/Wind Harmer
0.945
3138266HYDRAULIC
Solar/Wind Harmer
0.006
3138266HYDRAULIC
Solar/Wind Harmer
0.004
971447AH1-217 GEN
Solar/Wind Harmer
2.24
316164AC1-076 GEN
Solar/Wind Harmer
0.1
3148133STUARTS
Solar/Wind Harmer
0.04
3148013FISHERV
Solar/Wind Harmer
0.038
270494AE1-108_GEN
Solar/Wind Harmer
0.741
971845AH1-439 GEN
Solar/Wind Harmer
2.7
970285AG2-188 GEN
Solar/Wind Harmer
4.55
3151771S ANNAG1
50/50
1.517
3151801S ANNAS2
50/50
0.78
972183AH1-676 GEN
50/50
491.693
3151761LOISA E
50/50
60.888
3151921BEARGRDN G2
50/50
0.707
3132273ORANGE
Solar/Wind Harmer
0.054
316170AC1-121 GEN2
Solar/Wind Harmer
0.101
970221AG2-151 GEN
Solar/Wind Harmer
3.937
3148013FISHERV
Solar/Wind Harmer
0.066
3146776BUCKING
Solar/Wind Harmer
0.022
LAGNLTFEXP_LAGN->PJM
CLTF
1.362
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.574
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.529
MECLTFEXP_MEC->PJM
CLTF
0.883
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.667
TVALTFEXP_TVA->PJM
CLTF
0.704
SIGELTFEXP_SIGE->PJM
CLTF
0.028
NYPJM->LTFIMP_NY
CLTF
0.524
LGEELTFEXP_LGEE->PJM
CLTF
0.368
WECLTFEXP_WEC->PJM
CLTF
0.184
CPLELTFEXP_CPLE->PJM
CLTF
0.987
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.149

Details for 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:137.15 %
Rating:1057.5 MVA
Rating Type:B
MVA to Mitigate:1450.33
MW Contribution:6.61
Bus #Bus NameTypeMW Contribution
970119AG2-088 GEN
50/50
52.941
3150851SPRUNCC
50/50
1.044
3143096IRON208
50/50
0.687
3151931BEARGRDN S1
50/50
1.658
3151911BEARGRDN G1
50/50
1.285
3143226MDLTHAN
Solar/Wind Harmer
0.397
3143526WINTERP
Solar/Wind Harmer
1.653
3143336POWHATN
Solar/Wind Harmer
5.221
316336AC2-165 C
Solar/Wind Harmer
0.01
970937AG2-583 GEN
Solar/Wind Harmer
12.089
3142543TWELFTH
Solar/Wind Harmer
0.016
972003AH1-546 GEN
Solar/Wind Harmer
5.766
944631AF1-128 GEN
Adder
61.208
315671AE2-027_GEN
Solar/Wind Harmer
7.993
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.05
971377AH1-170 GEN
Solar/Wind Harmer
1.322
3147623JAMES R
Solar/Wind Harmer
0.287
970129AG2-093 GEN
Solar/Wind Harmer
3.337
316458AB2-190 GEN2
Solar/Wind Harmer
0.626
971069AG2-661 GEN
Solar/Wind Harmer
2.011
3146926FARMVIL
Solar/Wind Harmer
0.068
3142416OLDCHRC
Solar/Wind Harmer
0.283
3142416OLDCHRC
Solar/Wind Harmer
0.109
3142433PROV 92
Solar/Wind Harmer
0.434
3142433PROV 92
Adder
0.211
3142433PROV 92
Adder
0.211
971647AH1-324 GEN
Solar/Wind Harmer
4.589
970659AG2-427 GEN
Solar/Wind Harmer
5.129
316381AD1-082 GEN
Solar/Wind Harmer
0.11
961611AG1-000B GEN
Solar/Wind Harmer
5.476
970661AG2-428 GEN
Solar/Wind Harmer
10.195
3151171GRAVELC
Adder
1.069
963171AG1-166 GEN
Solar/Wind Harmer
0.527
971563AH1-280 GEN
Solar/Wind Harmer
1.053
3144293JTRSVLE
Adder
0.314
3145336SMITFLD
Solar/Wind Harmer
0.384
970685AG2-442 GEN
Solar/Wind Harmer
7.154
971777AH1-397 GEN
Solar/Wind Harmer
0.248
3141843SHACKLE
Adder
0.481
316159AE1-175 C
Solar/Wind Harmer
0.081
3141766HARMONY
Solar/Wind Harmer
0.018
3138126ROCKLANDING
Solar/Wind Harmer
0.042
316072AD1-144
Solar/Wind Harmer
0.033
316093AE2-104_GEN
Solar/Wind Harmer
1.516
971317AH1-138 GEN
Solar/Wind Harmer
0.671
962491AG1-098 GEN
Solar/Wind Harmer
5.114
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
1.112
315693AD1-088 GEN
Solar/Wind Harmer
4.267
316023GEN1_S
Solar/Wind Harmer
0.199
316246AF1-032 C
Solar/Wind Harmer
0.04
3150861SPRUNCD
50/50
1.044
3143096IRON208
50/50
0.687
3143096IRON208
50/50
0.673
3151921BEARGRDN G2
50/50
1.285
316313AB2-026
Solar/Wind Harmer
0.185
316258AE1-075 C
Solar/Wind Harmer
0.222
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.438
3146776BUCKING
Solar/Wind Harmer
0.045
970221AG2-151 GEN
Solar/Wind Harmer
6.608
965281AG1-393 GEN
Solar/Wind Harmer
1.316
315839AE2-212 C
Solar/Wind Harmer
0.001
970133AG2-095 GEN
Solar/Wind Harmer
1.182
970293AG2-193 GEN
Solar/Wind Harmer
1.304
3142946ENON
Solar/Wind Harmer
0.04
970129AG2-093 GEN
Solar/Wind Harmer
7.091
315778AD1-151 GEN
Solar/Wind Harmer
9.051
3146926FARMVIL
Solar/Wind Harmer
0.068
315813AE1-149 C
Solar/Wind Harmer
5.92
316473AC1-191 GEN
Solar/Wind Harmer
0.369
3142416OLDCHRC
Solar/Wind Harmer
1.056
3142433PROV 92
Adder
0.211
3142433PROV 92
Adder
0.211
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970659AG2-427 GEN
Solar/Wind Harmer
1.122
316083AB2-161 GEN
Solar/Wind Harmer
0.001
961611AG1-000B GEN
Solar/Wind Harmer
2.784
970909AG2-566 GEN
Solar/Wind Harmer
1.096
970661AG2-428 GEN
Solar/Wind Harmer
2.168
3147133PAMPLIN
Solar/Wind Harmer
0.316
971193AH1-056 GEN
Solar/Wind Harmer
6.137
3151221GRAVEL6
Adder
7.305
3151171GRAVELC
Adder
1.406
963181AG1-167 GEN
Solar/Wind Harmer
0.395
3144293JTRSVLE
Adder
0.314
3145336SMITFLD
Solar/Wind Harmer
0.038
316303AF2-085
50/50
7.059
971285AH1-108 GEN
50/50
1.708
972205AH1-687 GEN
50/50
6.267
316233AE1-074 FULL
Solar/Wind Harmer
0.255
971281AH1-106 GEN
Solar/Wind Harmer
4.412
971283AH1-107 GEN
Solar/Wind Harmer
4.412
971845AH1-439 GEN
Solar/Wind Harmer
5.597
970285AG2-188 GEN
Solar/Wind Harmer
9.622
971447AH1-217 GEN
Solar/Wind Harmer
3.562
316132AB2-190 GEN1
Solar/Wind Harmer
0.626
3143316POE
Solar/Wind Harmer
0.447
971167AH1-042 GEN
Solar/Wind Harmer
9.861
316369SG1_INVT
Solar/Wind Harmer
0.004
316312AB1-027
Solar/Wind Harmer
0.195
3142433PROV 92
Adder
0.211
3142433PROV 92
Adder
0.211
270494AE1-108_GEN
Solar/Wind Harmer
1.234
315976AC1-164 GENA
Solar/Wind Harmer
10.641
316169AC1-164_GENC
Solar/Wind Harmer
9.193
315975AC1-164 GENB
Solar/Wind Harmer
0.315
315657AE1-056 GEN
Solar/Wind Harmer
3.476
972265AH1-717 GEN
Adder
7.802
3151201GRAVEL4
Adder
7.314
3151191GRAVEL3
Adder
7.221
3151211GRAVEL5
Adder
7.221
3143873LANEXA
Solar/Wind Harmer
0.059
946301AF1-294 GEN
Solar/Wind Harmer
1.948
961791AG1-021 GEN
Solar/Wind Harmer
0.948
316315AB2-025 C
Solar/Wind Harmer
0.079
315814AE2-033 C
Solar/Wind Harmer
7.71
971445AH1-216 GEN
Solar/Wind Harmer
6.794
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.066
316311AC2-079 GEN
Solar/Wind Harmer
2.751
970683AG2-441 GEN
Solar/Wind Harmer
6.388
970681AG2-440 GEN
Solar/Wind Harmer
5.11
970189AG2-124 GEN
Solar/Wind Harmer
2.786
316314AB2-024 C
Solar/Wind Harmer
0
3144303KENBRDG
Solar/Wind Harmer
0.074
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
1.553
3142366NRTHEST
50/50
0.483
3150691DARBY 3
50/50
10.163
3150701DARBY 4
50/50
10.139
3150681DARBY 2
50/50
10.127
3150671DARBY 1
50/50
10.115
944641AF1-129 GEN
50/50
66.432
971223AH1-071 GEN
Solar/Wind Harmer
4.235
3143526WINTERP
Solar/Wind Harmer
1.653
316240AF1-291 C
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.497
3146776BUCKING
Solar/Wind Harmer
0.04
971489AH1-241 GEN
Solar/Wind Harmer
6.608
3142946ENON
Solar/Wind Harmer
0.012
3142296MT RD221
Adder
0.38
316033AB2-134 GEN
Solar/Wind Harmer
0.006
315697AD1-025 GEN
Solar/Wind Harmer
0.124
316075AC2-137 C
Solar/Wind Harmer
0.03
966871AG1-558 GEN
Solar/Wind Harmer
0.126
970657AG2-426 GEN
Solar/Wind Harmer
3.648
970657AG2-426 GEN
Solar/Wind Harmer
0.765
970301AG2-198 GEN
Solar/Wind Harmer
4.386
3147133PAMPLIN
Solar/Wind Harmer
0.101
3147133PAMPLIN
Solar/Wind Harmer
0.081
971741AH1-377 GEN
Solar/Wind Harmer
9.881
958211AF2-115 GEN
Solar/Wind Harmer
1.185
963191AG1-168 GEN
Solar/Wind Harmer
0.395
3144293JTRSVLE
Adder
0.314
3144293JTRSVLE
Adder
0.265
3144356SAPONY
Solar/Wind Harmer
0.819
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316034AC1-036 C
Solar/Wind Harmer
0.007
970323AG2-213 GEN
Solar/Wind Harmer
3.955
971775AH1-396 GEN
Solar/Wind Harmer
0.148
315821AE2-092 GEN
Solar/Wind Harmer
0.006
316036AC1-147 C
Solar/Wind Harmer
0.017
3150991CHESPKB
Adder
0.933
3150991CHESPKB
Adder
0.911
316316AC1-027 C
Solar/Wind Harmer
0.085
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.003
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3145506HICKORY
Solar/Wind Harmer
0.351
3145506HICKORY
Solar/Wind Harmer
0.211
3145506HICKORY
Solar/Wind Harmer
0.053
316339AD2-160 GEN
Solar/Wind Harmer
0.142
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.049
3137176SLIGO L2192
Solar/Wind Harmer
0.349
3146456SLIGO L269
Solar/Wind Harmer
1.551
3130086AYDLETT
Solar/Wind Harmer
0.35
3146386ELIZ CT
Solar/Wind Harmer
0.087
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.087
3146516WINFALL
Solar/Wind Harmer
0.087
3146516WINFALL
Solar/Wind Harmer
0.087
970933AG2-581 GEN
Solar/Wind Harmer
6.917
3146626S HERTFORD
Solar/Wind Harmer
0.086
3146626S HERTFORD
Solar/Wind Harmer
0.086
970099AG2-077 GEN
Solar/Wind Harmer
9.151
313527AB2-043 GEN
Solar/Wind Harmer
0.001
972185AH1-677 GEN
Adder
4.805
316181AB2-040 GEN
Solar/Wind Harmer
0.124
3146376EDENTON
Solar/Wind Harmer
0.379
3146376EDENTON
Solar/Wind Harmer
0.379
972187AH1-678 GEN
Adder
2.42
3145893MURPHYS
Solar/Wind Harmer
0.563
3145893MURPHYS
Solar/Wind Harmer
0.151
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.05
3146173TUNIS
Solar/Wind Harmer
0.083
3146173TUNIS
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.083
966811AG1-552 GEN
Solar/Wind Harmer
0.901
3145593CAROLNA
Solar/Wind Harmer
0.103
316426AA2-053 GEN
Solar/Wind Harmer
0.28
316065AD1-022 GEN
Solar/Wind Harmer
3.808
3145783HORNRTN
Solar/Wind Harmer
1.465
3145783HORNRTN
Solar/Wind Harmer
1.172
3145783HORNRTN
Solar/Wind Harmer
0.366
3145783HORNRTN
Solar/Wind Harmer
0.146
939181AE1-148 GEN
Solar/Wind Harmer
3.944
3145796HORNRTN
Solar/Wind Harmer
0.246
316468AD1-105 GEN
Solar/Wind Harmer
-0.026
958261AF2-120 GEN
Solar/Wind Harmer
2.652
962561AG1-105 GEN
Solar/Wind Harmer
3.799
316274AC1-208 GEN
Solar/Wind Harmer
0.409
964791AG1-342 GEN
Solar/Wind Harmer
1.497
3146843MT LREL
Solar/Wind Harmer
0.078
3146843MT LREL
Solar/Wind Harmer
0.078
3145933PARMELE
Solar/Wind Harmer
0.154
3145933PARMELE
Solar/Wind Harmer
0.077
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.795
3150341NORNECKC1
Adder
0.788
3145493TOT1
Solar/Wind Harmer
0.172
3145453TOT5
Solar/Wind Harmer
0.103
3145603CNETO
Solar/Wind Harmer
0.069
961601AG1-000A GEN
Solar/Wind Harmer
1.303
316263AC1-034 GEN
Solar/Wind Harmer
2.786
316222AC1-221 GEN
Solar/Wind Harmer
0.261
316447AC1-158 HLD
Solar/Wind Helper
1.867
316059AD1-063 C
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.018
3138283WHITEMARSH
Solar/Wind Harmer
0.021
315835AF2-110_GEN
Solar/Wind Harmer
0.619
3152611GOSPORTB
Adder
1.135
3152621GOSPORTC
Adder
0.963
3152601GOSPORTA
Adder
0.888
3151081ELIZAR1
Adder
8.147
3151091ELIZAR2
Adder
8.006
3141913WHIT STONE
Solar/Wind Harmer
0.088
316305AF2-043 C
Solar/Wind Harmer
0.001
3138133OCRAN
Solar/Wind Harmer
0.026
957871AF2-081 GEN
Solar/Wind Harmer
4.367
319010AE1-072 C
Solar/Wind Harmer
0.441
3146406KITTY HAWK
Solar/Wind Harmer
0.011
3146486SUNBURY
Solar/Wind Harmer
0.087
3146486SUNBURY
Solar/Wind Harmer
0.087
313526AB2-022
Solar/Wind Harmer
0.047
941031AE2-094 GEN
Solar/Wind Harmer
16.035
944011AF1-069 GEN
Solar/Wind Harmer
5.239
316321Z2-027
Solar/Wind Harmer
0.016
3145176PASQUOTANK
Solar/Wind Harmer
0.054
3146396TANGLEW
Solar/Wind Harmer
0.24
3141783LANCAST
Solar/Wind Harmer
0.052
3141783LANCAST
Solar/Wind Harmer
0.035
971967AH1-528 GEN
Solar/Wind Harmer
13.837
970673AG2-436 GEN
Solar/Wind Harmer
18.368
970673AG2-436 GEN
Solar/Wind Harmer
12.246
316087AB2-174 GEN
Solar/Wind Harmer
0.002
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
0.085
965291AG1-394 GEN
Solar/Wind Harmer
0.378
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3145893MURPHYS
Solar/Wind Harmer
0.227
3145893MURPHYS
Solar/Wind Harmer
0.084
3137643SOCKMAN
Solar/Wind Harmer
0.336
962981AG1-147 GEN
Solar/Wind Harmer
3.138
3146043SEABORD
Solar/Wind Harmer
0.084
315816AE2-034 GEN
Solar/Wind Harmer
0.36
315607AA1-063A GEN
Solar/Wind Harmer
0.171
315652AC1-086 GEN
Solar/Wind Harmer
9.169
3130546PLYMOUTH
Solar/Wind Harmer
0.083
315732AD1-074 GEN1
Solar/Wind Harmer
0.476
315733AD1-074 GEN2
Solar/Wind Harmer
0.476
315735AD1-075 GEN1
Solar/Wind Harmer
0.238
3145513AHOSKIE
Solar/Wind Harmer
0.173
3145513AHOSKIE
Solar/Wind Harmer
0.083
3146206CASHIE
Solar/Wind Harmer
0.083
970601AG2-382 GEN
Solar/Wind Harmer
3.084
970327AG2-215 GEN
Solar/Wind Harmer
2.71
3145683EARLEYS
Solar/Wind Harmer
0.164
3145683EARLEYS
Solar/Wind Harmer
0.082
3145683EARLEYS
Solar/Wind Harmer
0.082
970831AG2-522 GEN
Solar/Wind Harmer
3.502
970085AG2-068 GEN
Solar/Wind Harmer
4.372
970581AG2-369 GEN
Solar/Wind Harmer
3.76
3145796HORNRTN
Solar/Wind Harmer
0.262
3145796HORNRTN
Solar/Wind Harmer
0.033
3146033SCOT NK
Solar/Wind Harmer
0.319
972189AH1-679 GEN
Adder
1.329
3141813NORNECK
Solar/Wind Harmer
0.076
316005AA1-067
Solar/Wind Harmer
0.081
3145746EVERETS
Solar/Wind Harmer
0.301
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
970181AG2-120 GEN
Solar/Wind Harmer
0.942
316118AC1-105 GEN
Solar/Wind Harmer
0.194
957861AF2-080 GEN
Solar/Wind Harmer
3.228
316319Z2-044 C
Solar/Wind Harmer
0
316420AA1-050 GEN
Solar/Wind Harmer
0.002
3145573BETHELC
Solar/Wind Harmer
0.074
3145573BETHELC
Solar/Wind Harmer
0.074
3147173SINAI
Solar/Wind Harmer
0.072
3147243WELCO
Solar/Wind Harmer
0.045
970865AG2-541 GEN
Solar/Wind Harmer
2.225
316223AC1-118
Solar/Wind Harmer
0.043
316123AC1-075 GEN
Solar/Wind Harmer
0.08
970165AG2-112 GEN
Solar/Wind Harmer
0.477
970163AG2-111 GEN
Solar/Wind Harmer
0.455
940641AE2-051 GEN
Solar/Wind Harmer
7.055
939411AE1-173 GEN
Solar/Wind Harmer
37.578
3138133OCRAN
Solar/Wind Harmer
0.053
316388AE2-253 GEN
Solar/Wind Harmer
0.275
3146456SLIGO L269
Solar/Wind Harmer
0.088
944591AF1-124 GEN
Solar/Wind Harmer
19.745
960081AF2-299 GEN
Solar/Wind Harmer
0.838
971795AH1-408 GEN
Solar/Wind Harmer
5.798
3147043LAWRENC
Adder
0.785
3146516WINFALL
Solar/Wind Harmer
0.281
3146516WINFALL
Solar/Wind Harmer
0.087
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
957481AF2-042 GEN
Solar/Wind Harmer
22.879
3130156CHOWAN
Solar/Wind Harmer
0.085
316237AB2-079_GEN
Solar/Wind Harmer
0.001
316294AC1-161 GEN
Solar/Wind Harmer
1.467
3145893MURPHYS
Solar/Wind Harmer
0.336
3145893MURPHYS
Solar/Wind Harmer
0.374
3145663CRESWEL
Solar/Wind Harmer
0.235
971163AH1-040 GEN
Solar/Wind Harmer
6.72
316011AB1-132 GEN
Solar/Wind Harmer
1.515
962571AG1-106 GEN
Solar/Wind Harmer
1.186
3146173TUNIS
Solar/Wind Harmer
0.083
316190AA2-174 GEN
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.083
971547AH1-271 GEN
Solar/Wind Harmer
1.762
3146263WOODLND
Solar/Wind Harmer
0.082
3145783HORNRTN
Solar/Wind Harmer
0.082
970919AG2-571 GEN
Solar/Wind Harmer
2.926
3145683EARLEYS
Solar/Wind Harmer
0.082
970087AG2-069 GEN
Solar/Wind Harmer
6.559
316129AC1-054 GEN
Solar/Wind Harmer
0.308
3145796HORNRTN
Solar/Wind Harmer
0.27
3145796HORNRTN
Solar/Wind Harmer
0.082
971065AG2-659 GEN
Solar/Wind Harmer
3.493
3145823KELFORD
Solar/Wind Harmer
0.081
962861AG1-135 GEN
Solar/Wind Harmer
2.586
3145963POPLR C
Solar/Wind Harmer
0.08
316174AB2-169 GEN
Solar/Wind Harmer
0.002
316212AC1-099_GEN
Solar/Wind Harmer
0.408
315687AD1-152 GEN
Solar/Wind Harmer
0.003
3141726DUNNSVL
Solar/Wind Harmer
0.313
970401AG2-262 GEN
Solar/Wind Harmer
0.457
315722AD1-056 GEN
Solar/Wind Harmer
0.488
3146293MARTNCO
Solar/Wind Harmer
0.071
3150351NORNECKC2
Adder
0.757
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
316494AC1-189 GEN
Solar/Wind Harmer
0.253
3146233WITAKRS
Solar/Wind Harmer
0.298
961671AG1-007 GEN
Solar/Wind Harmer
0.011
3146083TARBORO
Solar/Wind Harmer
0.074
3145493TOT1
Solar/Wind Harmer
0.33
3145543BTLEBRO
Solar/Wind Harmer
0.073
3145543BTLEBRO
Solar/Wind Harmer
0.059
316359AB2-059 GEN
Solar/Wind Harmer
0.263
316049AB1-081 GEN
Solar/Wind Harmer
0.42
3142053HEARTS
Solar/Wind Harmer
0.129
316003AC1-222 GEN
Solar/Wind Harmer
0.002
316337AD2-073 GEN
Solar/Wind Harmer
0.06
316045AC1-158 PL2
Solar/Wind Helper
2.716
3147666LOUISA
Solar/Wind Helper
0.467
316192AB2-158 GEN
Solar/Wind Helper
0.764
3141843SHACKLE
Adder
0.481
316203AE2-005 GEN
Solar/Wind Harmer
0
959311AF2-222 GEN
Solar/Wind Harmer
8.32
316382AG1-145 C
Solar/Wind Harmer
0.001
970257AG2-171 GEN
Solar/Wind Harmer
2.966
316280AD1-041 GEN
Solar/Wind Harmer
0.002
3141766HARMONY
Solar/Wind Harmer
1.23
315785AD2-033 C
Solar/Wind Harmer
0.744
3144216WINCHST
Adder
0.345
3144536CHRHLND
Solar/Wind Harmer
0.014
316156AD2-030 GEN
Solar/Wind Harmer
0.067
3141873WAN 176
Solar/Wind Harmer
1.611
3150921YORKTN3
Adder
2.265
3144873MCLAUGH
Solar/Wind Harmer
0.002
3151101ELIZAR3
Adder
8.251
3145273HOLLAND
Solar/Wind Harmer
0.066
316365GEN2_N
Solar/Wind Harmer
0.199
964241AG1-285 GEN
Solar/Wind Harmer
5.88
3146456SLIGO L269
Solar/Wind Harmer
0.088
971153AH1-033 GEN
Solar/Wind Harmer
1.013
944581AF1-123 GEN
Solar/Wind Harmer
19.675
944601AF1-125 GEN
Solar/Wind Harmer
19.372
316320Y1-086
Solar/Wind Harmer
0
316435W1029_GEN3
Solar/Wind Harmer
0.001
3147043LAWRENC
Solar/Wind Harmer
0.052
3146516WINFALL
Solar/Wind Harmer
0.087
3146626S HERTFORD
Solar/Wind Harmer
0.086
316131AB2-060 GEN
Solar/Wind Harmer
0.271
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
313506AB2-031 GEN
Solar/Wind Harmer
0.264
3146376EDENTON
Solar/Wind Harmer
0.085
315773AC2-141 GEN
Solar/Wind Harmer
3.093
3145893MURPHYS
Solar/Wind Harmer
0.141
3145893MURPHYS
Solar/Wind Harmer
0.084
962971AG1-146 GEN
Solar/Wind Harmer
1.345
315614AA2-178 GEN
Solar/Wind Harmer
0.481
957521AF2-046 GEN
Solar/Wind Harmer
6.241
961681AG1-008 GEN
Solar/Wind Harmer
6.241
316478AD1-087 GEN
Solar/Wind Harmer
0.292
316486AD2-202 GEN
Solar/Wind Harmer
0.086
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3146173TUNIS
Solar/Wind Harmer
0.083
971157AH1-035 GEN
Solar/Wind Harmer
0.997
315737AD1-076 GEN
Solar/Wind Harmer
1.067
316463AE2-346 GEN
Solar/Wind Harmer
0.071
316140AB2-099
Solar/Wind Harmer
0.03
962331AG1-082 GEN
Solar/Wind Harmer
0.882
3146206CASHIE
Solar/Wind Harmer
0.083
970009AG2-005 GEN
Solar/Wind Harmer
0.617
3146263WOODLND
Solar/Wind Harmer
0.082
970917AG2-570 GEN
Solar/Wind Harmer
7.314
3156021HOLLOMANSOL
Solar/Wind Harmer
0.373
3145796HORNRTN
Solar/Wind Harmer
0.327
3145796HORNRTN
Solar/Wind Harmer
0.082
971781AH1-399 GEN
Solar/Wind Harmer
0.107
316317KELFORD C
Solar/Wind Harmer
0.008
3145823KELFORD
Solar/Wind Harmer
0.081
316404AE1-155 C
Solar/Wind Harmer
0.018
3145963POPLR C
Solar/Wind Harmer
0.08
316210AC1-098 GEN
Solar/Wind Harmer
0.732
315724AD1-057 GEN
Solar/Wind Harmer
0.29
3145933PARMELE
Solar/Wind Harmer
0.077
966801AG1-551 GEN
Solar/Wind Harmer
0.897
316327AA2-057 GEN
Solar/Wind Harmer
0.115
3150351NORNECKC2
Adder
0.769
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
3146233WITAKRS
Solar/Wind Harmer
0.375
3146233WITAKRS
Solar/Wind Harmer
0.051
3138543CONSLDL
Solar/Wind Harmer
0.049
3146073TAR RVR
Solar/Wind Harmer
0.074
3146083TARBORO
Solar/Wind Harmer
0.074
3145543BTLEBRO
Solar/Wind Harmer
0.073
3145543BTLEBRO
Solar/Wind Harmer
0.073
961601AG1-000A GEN
Solar/Wind Harmer
5.213
971623AH1-311 GEN
Solar/Wind Harmer
0.147
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.088
971683AH1-343 GEN
Solar/Wind Harmer
2.46
316283AC2-100 C
Solar/Wind Harmer
0.122
3141906WESTMOR
Solar/Wind Harmer
0.024
958131AF2-107 GEN
Solar/Wind Harmer
1.633
316044AC1-158 PL1
Solar/Wind Helper
0.848
316450AC1-158 RIC
Solar/Wind Helper
0.226
3147666LOUISA
Solar/Wind Helper
0.269
LAGNLTFEXP_LAGN->PJM
CLTF
3.494
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.354
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.067
MECLTFEXP_MEC->PJM
CLTF
1.74
SIGELTFEXP_SIGE->PJM
CLTF
0.053
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.348
TVALTFEXP_TVA->PJM
CLTF
1.763
NYPJM->LTFIMP_NY
CLTF
1.086
LGEELTFEXP_LGEE->PJM
CLTF
0.65
WECLTFEXP_WEC->PJM
CLTF
0.327
CPLELTFEXP_CPLE->PJM
CLTF
4.706
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.653

Details for 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.36 %
Rating:1265.1 MVA
Rating Type:C
MVA to Mitigate:1585.98
MW Contribution:8.71
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
7.054
971285AH1-108 GEN
50/50
1.707
972205AH1-687 GEN
50/50
6.277
316233AE1-074 FULL
Solar/Wind Harmer
0.961
971281AH1-106 GEN
Solar/Wind Harmer
5.803
971283AH1-107 GEN
Solar/Wind Harmer
5.803
971845AH1-439 GEN
Solar/Wind Harmer
7.405
970285AG2-188 GEN
Solar/Wind Harmer
12.021
971447AH1-217 GEN
Solar/Wind Harmer
4.697
316132AB2-190 GEN1
Solar/Wind Harmer
1.321
3143316POE
Solar/Wind Harmer
-0.05
971167AH1-042 GEN
Solar/Wind Harmer
11.94
316369SG1_INVT
Solar/Wind Harmer
2.209
316312AB1-027
Solar/Wind Harmer
0.411
3142433PROV 92
Adder
0.21
3142433PROV 92
Adder
0.21
270494AE1-108_GEN
Solar/Wind Harmer
3.015
315976AC1-164 GENA
Solar/Wind Harmer
12.09
316169AC1-164_GENC
Solar/Wind Harmer
10.444
315975AC1-164 GENB
Solar/Wind Harmer
0.358
315657AE1-056 GEN
Solar/Wind Harmer
4.288
946301AF1-294 GEN
Solar/Wind Harmer
2.872
961791AG1-021 GEN
Solar/Wind Harmer
1.401
972265AH1-717 GEN
Adder
7.73
3151201GRAVEL4
Adder
7.246
3151191GRAVEL3
Adder
7.154
3151211GRAVEL5
Adder
7.154
316315AB2-025 C
Solar/Wind Harmer
0.301
315814AE2-033 C
Solar/Wind Harmer
10.33
3143873LANEXA
Solar/Wind Harmer
-0.007
970683AG2-441 GEN
Solar/Wind Harmer
8.501
970681AG2-440 GEN
Solar/Wind Harmer
6.8
315833AF1-017_GEN
Solar/Wind Harmer
2.038
316349AD2-085 GEN
Solar/Wind Harmer
0.954
971445AH1-216 GEN
Solar/Wind Harmer
6.636
316311AC2-079 GEN
Solar/Wind Harmer
5.405
3144303KENBRDG
Solar/Wind Harmer
-0.008
971443AH1-215 GEN
Solar/Wind Harmer
2.068
316314AB2-024 C
Solar/Wind Harmer
0.887
315662AE1-191 GEN
Solar/Wind Harmer
1.241
315666AE1-190 GEN
Solar/Wind Harmer
0.31
316059AD1-063 C
Solar/Wind Harmer
0.232
957601AF2-054 GEN
Solar/Wind Harmer
0.301
3141873WAN 176
Solar/Wind Harmer
-0.002
315835AF2-110_GEN
Solar/Wind Harmer
1.256
941031AE2-094 GEN
Solar/Wind Harmer
18.82
944011AF1-069 GEN
Solar/Wind Harmer
5.897
957831AF2-077 GEN
Solar/Wind Harmer
0.301
3138283WHITEMARSH
Solar/Wind Harmer
0.016
971967AH1-528 GEN
Solar/Wind Harmer
18.721
970673AG2-436 GEN
Solar/Wind Harmer
20.845
970673AG2-436 GEN
Solar/Wind Harmer
10.555
946281AF1-292 GEN
Solar/Wind Harmer
0.222
3152611GOSPORTB
Adder
1.118
3152621GOSPORTC
Adder
0.949
3152601GOSPORTA
Adder
0.875
3151081ELIZAR1
Adder
8.028
3151091ELIZAR2
Adder
7.888
316305AF2-043 C
Solar/Wind Harmer
0.296
3141913WHIT STONE
Solar/Wind Harmer
-0.01
3138133OCRAN
Solar/Wind Harmer
-0.003
316087AB2-174 GEN
Solar/Wind Harmer
1.39
3146486SUNBURY
Solar/Wind Harmer
-0.01
3146486SUNBURY
Solar/Wind Harmer
-0.01
957871AF2-081 GEN
Solar/Wind Harmer
4.862
319010AE1-072 C
Solar/Wind Harmer
1.965
3146406KITTY HAWK
Solar/Wind Harmer
0.008
316239AB2-077_GEN
Solar/Wind Harmer
0.292
316238AB2-078_GEN
Solar/Wind Harmer
0.292
313526AB2-022
Solar/Wind Harmer
0.261
316321Z2-027
Solar/Wind Harmer
0.261
3145176PASQUOTANK
Solar/Wind Harmer
-0.006
3146396TANGLEW
Solar/Wind Harmer
0.178
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
965291AG1-394 GEN
Solar/Wind Harmer
0.85
315611Z1-036_GEN2
Solar/Wind Harmer
2.363
3137643SOCKMAN
Solar/Wind Harmer
-0.038
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
3146043SEABORD
Solar/Wind Harmer
-0.009
315607AA1-063A GEN
Solar/Wind Harmer
0.957
316318V4-068
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
-0.009
972189AH1-679 GEN
Adder
1.322
315652AC1-086 GEN
Solar/Wind Harmer
9.306
970119AG2-088 GEN
50/50
52.906
3150851SPRUNCC
50/50
1.043
3143096IRON208
50/50
0.685
3151931BEARGRDN S1
50/50
1.661
3151911BEARGRDN G1
50/50
1.287
3143226MDLTHAN
Solar/Wind Harmer
-0.044
3143526WINTERP
Solar/Wind Harmer
-0.185
3143336POWHATN
Solar/Wind Harmer
3.915
316336AC2-165 C
Solar/Wind Harmer
5.205
970937AG2-583 GEN
Solar/Wind Harmer
15.927
3142543TWELFTH
Solar/Wind Harmer
-0.002
972003AH1-546 GEN
Solar/Wind Harmer
7.621
944631AF1-128 GEN
Adder
60.98
315671AE2-027_GEN
Solar/Wind Harmer
10.549
316322AB2-045
Solar/Wind Harmer
0.472
3146776BUCKING
Solar/Wind Harmer
-0.006
971377AH1-170 GEN
Solar/Wind Harmer
1.743
3147623JAMES R
Solar/Wind Harmer
0.216
970129AG2-093 GEN
Solar/Wind Harmer
2.995
316458AB2-190 GEN2
Solar/Wind Harmer
1.321
3146926FARMVIL
Solar/Wind Harmer
-0.008
971069AG2-661 GEN
Solar/Wind Harmer
2.001
3142416OLDCHRC
Solar/Wind Harmer
-0.032
3142416OLDCHRC
Solar/Wind Harmer
-0.012
3142433PROV 92
Solar/Wind Harmer
-0.048
3142433PROV 92
Adder
0.21
3142433PROV 92
Adder
0.21
971647AH1-324 GEN
Solar/Wind Harmer
6.002
970659AG2-427 GEN
Solar/Wind Harmer
6.334
316381AD1-082 GEN
Solar/Wind Harmer
1.083
961611AG1-000B GEN
Solar/Wind Harmer
5.745
970661AG2-428 GEN
Solar/Wind Harmer
12.22
963171AG1-166 GEN
Solar/Wind Harmer
1.401
971563AH1-280 GEN
Solar/Wind Harmer
1.401
3144293JTRSVLE
Adder
0.317
3151171GRAVELC
Adder
1.059
970685AG2-442 GEN
Solar/Wind Harmer
9.521
3145336SMITFLD
Solar/Wind Harmer
-0.042
971777AH1-397 GEN
Solar/Wind Harmer
1.23
3141843SHACKLE
Adder
0.476
316159AE1-175 C
Solar/Wind Harmer
0.278
3141766HARMONY
Solar/Wind Harmer
-0.002
962491AG1-098 GEN
Solar/Wind Harmer
6.852
315693AD1-088 GEN
Solar/Wind Harmer
5.084
316023GEN1_S
Solar/Wind Harmer
0.679
3138126ROCKLANDING
Solar/Wind Harmer
0.031
316093AE2-104_GEN
Solar/Wind Harmer
2.922
316072AD1-144
Solar/Wind Harmer
0.203
939411AE1-173 GEN
Solar/Wind Harmer
50.033
971317AH1-138 GEN
Solar/Wind Harmer
1.242
960081AF2-299 GEN
Solar/Wind Harmer
1.115
971795AH1-408 GEN
Solar/Wind Harmer
7.407
316375AC2-012 GEN
Solar/Wind Harmer
3.414
3150981CHESPKA
Adder
1.096
3147043LAWRENC
Adder
0.794
957481AF2-042 GEN
Solar/Wind Harmer
30.736
316246AF1-032 C
Solar/Wind Harmer
0.199
3138133OCRAN
Solar/Wind Harmer
-0.006
316388AE2-253 GEN
Solar/Wind Harmer
0.656
3146456SLIGO L269
Solar/Wind Harmer
-0.01
316237AB2-079_GEN
Solar/Wind Harmer
0.292
944591AF1-124 GEN
Solar/Wind Harmer
44.111
3146516WINFALL
Solar/Wind Harmer
-0.031
3146516WINFALL
Solar/Wind Harmer
-0.01
315800Z1-036_GEN1
Solar/Wind Harmer
2.363
3130156CHOWAN
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
-0.038
970919AG2-571 GEN
Solar/Wind Harmer
2.997
3145893MURPHYS
Solar/Wind Harmer
0.281
316011AB1-132 GEN
Solar/Wind Harmer
1.976
3150351NORNECKC2
Adder
0.748
316045AC1-158 PL2
Solar/Wind Helper
2.728
3147666LOUISA
Solar/Wind Helper
0.47
316192AB2-158 GEN
Solar/Wind Helper
0.767
3150861SPRUNCD
50/50
1.043
3143096IRON208
50/50
0.685
3143096IRON208
50/50
0.672
3151921BEARGRDN G2
50/50
1.287
316313AB2-026
Solar/Wind Harmer
0.89
316258AE1-075 C
Solar/Wind Harmer
0.801
316405AF2-144 C
Solar/Wind Harmer
0.845
3143336POWHATN
Solar/Wind Harmer
3.328
3146776BUCKING
Solar/Wind Harmer
-0.005
970221AG2-151 GEN
Solar/Wind Harmer
8.715
315839AE2-212 C
Solar/Wind Harmer
0.419
965281AG1-393 GEN
Solar/Wind Harmer
1.738
970133AG2-095 GEN
Solar/Wind Harmer
1.553
970293AG2-193 GEN
Solar/Wind Harmer
1.709
3142946ENON
Solar/Wind Harmer
-0.004
970129AG2-093 GEN
Solar/Wind Harmer
7.393
3146926FARMVIL
Solar/Wind Harmer
-0.008
315778AD1-151 GEN
Solar/Wind Harmer
10.957
315813AE1-149 C
Solar/Wind Harmer
7.813
316473AC1-191 GEN
Solar/Wind Harmer
1.315
3142416OLDCHRC
Solar/Wind Harmer
1.229
3142433PROV 92
Adder
0.21
3142433PROV 92
Adder
0.21
942461AE2-259 GEN
Solar/Wind Harmer
1.815
970659AG2-427 GEN
Solar/Wind Harmer
1.122
316083AB2-161 GEN
Solar/Wind Harmer
1.918
970909AG2-566 GEN
Solar/Wind Harmer
1.109
961611AG1-000B GEN
Solar/Wind Harmer
2.451
970661AG2-428 GEN
Solar/Wind Harmer
2.166
3147133PAMPLIN
Solar/Wind Harmer
-0.036
971193AH1-056 GEN
Solar/Wind Harmer
7.146
963181AG1-167 GEN
Solar/Wind Harmer
1.051
3144293JTRSVLE
Adder
0.317
3151221GRAVEL6
Adder
7.238
3151171GRAVELC
Adder
1.393
3145336SMITFLD
Solar/Wind Harmer
-0.004
959311AF2-222 GEN
Solar/Wind Harmer
11.099
970257AG2-171 GEN
Solar/Wind Harmer
3.95
3141843SHACKLE
Adder
0.476
316203AE2-005 GEN
Solar/Wind Harmer
4.409
315785AD2-033 C
Solar/Wind Harmer
2.356
316382AG1-145 C
Solar/Wind Harmer
0.312
316280AD1-041 GEN
Solar/Wind Harmer
0.776
3141766HARMONY
Solar/Wind Harmer
0.913
3144216WINCHST
Adder
0.34
3144536CHRHLND
Solar/Wind Harmer
-0.002
316156AD2-030 GEN
Solar/Wind Harmer
0.269
3141873WAN 176
Solar/Wind Harmer
1.195
316365GEN2_N
Solar/Wind Harmer
0.679
964241AG1-285 GEN
Solar/Wind Harmer
7.839
3150921YORKTN3
Adder
2.229
3145273HOLLAND
Solar/Wind Harmer
-0.007
966621AG1-532 GEN
Solar/Wind Harmer
0.201
3144873MCLAUGH
Solar/Wind Harmer
0
3147043LAWRENC
Solar/Wind Harmer
-0.006
3151101ELIZAR3
Adder
8.131
316131AB2-060 GEN
Solar/Wind Harmer
1.059
3146456SLIGO L269
Solar/Wind Harmer
-0.01
971153AH1-033 GEN
Solar/Wind Harmer
1.185
316320Y1-086
Solar/Wind Harmer
0.568
313506AB2-031 GEN
Solar/Wind Harmer
0.777
316435W1029_GEN3
Solar/Wind Harmer
1.751
944581AF1-123 GEN
Solar/Wind Harmer
43.953
944601AF1-125 GEN
Solar/Wind Harmer
43.267
3146516WINFALL
Solar/Wind Harmer
-0.01
3146626S HERTFORD
Solar/Wind Harmer
-0.01
3156081AA2-088 GEN
Solar/Wind Harmer
3.115
316478AD1-087 GEN
Solar/Wind Harmer
0.83
316486AD2-202 GEN
Solar/Wind Harmer
0.243
3146376EDENTON
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
0.066
3145893MURPHYS
Solar/Wind Harmer
-0.009
970917AG2-570 GEN
Solar/Wind Harmer
23.678
3150351NORNECKC2
Adder
0.761
316044AC1-158 PL1
Solar/Wind Helper
0.852
316450AC1-158 RIC
Solar/Wind Helper
0.227
3147666LOUISA
Solar/Wind Helper
0.27
3142366NRTHEST
50/50
0.481
3150691DARBY 3
50/50
10.129
3150701DARBY 4
50/50
10.105
3150681DARBY 2
50/50
10.093
3150671DARBY 1
50/50
10.082
944641AF1-129 GEN
50/50
66.507
971223AH1-071 GEN
Solar/Wind Harmer
5.573
3143526WINTERP
Solar/Wind Harmer
-0.185
316240AF1-291 C
Solar/Wind Harmer
0.438
3146776BUCKING
Solar/Wind Harmer
-0.056
3146776BUCKING
Solar/Wind Harmer
-0.005
971489AH1-241 GEN
Solar/Wind Harmer
8.274
3142946ENON
Solar/Wind Harmer
-0.001
3142296MT RD221
Adder
0.379
316033AB2-134 GEN
Solar/Wind Harmer
3.986
315697AD1-025 GEN
Solar/Wind Harmer
2.5
316075AC2-137 C
Solar/Wind Harmer
0.333
966871AG1-558 GEN
Solar/Wind Harmer
0.367
966871AG1-558 GEN
Solar/Wind Harmer
0.126
970657AG2-426 GEN
Solar/Wind Harmer
3.655
970657AG2-426 GEN
Solar/Wind Harmer
0.764
970301AG2-198 GEN
Solar/Wind Harmer
5.841
3147133PAMPLIN
Solar/Wind Harmer
-0.011
3147133PAMPLIN
Solar/Wind Harmer
-0.009
971741AH1-377 GEN
Solar/Wind Harmer
13.177
958211AF2-115 GEN
Solar/Wind Harmer
1.751
963191AG1-168 GEN
Solar/Wind Harmer
1.051
3144293JTRSVLE
Adder
0.317
3144293JTRSVLE
Adder
0.267
3144356SAPONY
Solar/Wind Harmer
0.389
316236AE1-162_GEN
Solar/Wind Harmer
0.322
316034AC1-036 C
Solar/Wind Harmer
0.195
970323AG2-213 GEN
Solar/Wind Harmer
5.267
971775AH1-396 GEN
Solar/Wind Harmer
0.75
316441AF1-014 GEN
Solar/Wind Harmer
0.705
315821AE2-092 GEN
Solar/Wind Harmer
2.144
970933AG2-581 GEN
Solar/Wind Harmer
9.321
316036AC1-147 C
Solar/Wind Harmer
0.266
3150991CHESPKB
Adder
0.92
3150991CHESPKB
Adder
0.898
972185AH1-677 GEN
Adder
4.927
315742AE1-103 GEN
Solar/Wind Harmer
1.029
970099AG2-077 GEN
Solar/Wind Harmer
12.294
316316AC1-027 C
Solar/Wind Harmer
0.301
3142956BIRDNECK
Solar/Wind Harmer
0.526
972187AH1-678 GEN
Adder
2.481
313527AB2-043 GEN
Solar/Wind Harmer
1.585
316185AD1-033 GEN
Solar/Wind Harmer
1.029
3145506HICKORY
Solar/Wind Harmer
-0.039
3145506HICKORY
Solar/Wind Harmer
-0.023
3145506HICKORY
Solar/Wind Harmer
-0.006
316339AD2-160 GEN
Solar/Wind Harmer
0.656
316018AA1-139 ULT2
Solar/Wind Harmer
0.833
316017AA1-139 ULT1
Solar/Wind Harmer
0.787
3137176SLIGO L2192
Solar/Wind Harmer
-0.038
3146456SLIGO L269
Solar/Wind Harmer
1.148
3130086AYDLETT
Solar/Wind Harmer
-0.039
3146386ELIZ CT
Solar/Wind Harmer
-0.01
316181AB2-040 GEN
Solar/Wind Harmer
1.349
316431W1029_GEN1
Solar/Wind Harmer
1.751
316433W1029_GEN2
Solar/Wind Harmer
1.751
3146516WINFALL
Solar/Wind Harmer
-0.01
3146516WINFALL
Solar/Wind Harmer
-0.01
3146516WINFALL
Solar/Wind Harmer
-0.01
3146626S HERTFORD
Solar/Wind Harmer
-0.01
3146626S HERTFORD
Solar/Wind Harmer
-0.01
3146376EDENTON
Solar/Wind Harmer
0.282
3146376EDENTON
Solar/Wind Harmer
0.282
3145893MURPHYS
Solar/Wind Harmer
0.264
3145893MURPHYS
Solar/Wind Harmer
-0.017
3150341NORNECKC1
Adder
0.786
3150341NORNECKC1
Adder
0.779
316447AC1-158 HLD
Solar/Wind Helper
1.875
LAGNLTFEXP_LAGN->PJM
CLTF
3.549
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.546
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.162
MECLTFEXP_MEC->PJM
CLTF
1.768
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.514
TVALTFEXP_TVA->PJM
CLTF
1.79
SIGELTFEXP_SIGE->PJM
CLTF
0.054
NYPJM->LTFIMP_NY
CLTF
1.094
LGEELTFEXP_LGEE->PJM
CLTF
0.661
WECLTFEXP_WEC->PJM
CLTF
0.333
CPLELTFEXP_CPLE->PJM
CLTF
4.781
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.949

Details for 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: 56372_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.56 %
Rating:1265.1 MVA
Rating Type:C
MVA to Mitigate:1563.15
MW Contribution:8.7
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
7.071
971285AH1-108 GEN
50/50
1.718
972205AH1-687 GEN
50/50
6.266
316233AE1-074 FULL
Solar/Wind Harmer
0.964
971281AH1-106 GEN
Solar/Wind Harmer
5.823
971283AH1-107 GEN
Solar/Wind Harmer
5.823
971845AH1-439 GEN
Solar/Wind Harmer
7.348
970285AG2-188 GEN
Solar/Wind Harmer
11.918
316132AB2-190 GEN1
Solar/Wind Harmer
1.338
971447AH1-217 GEN
Solar/Wind Harmer
4.689
3143316POE
Solar/Wind Harmer
-0.052
971167AH1-042 GEN
Solar/Wind Harmer
12.093
316369SG1_INVT
Solar/Wind Harmer
2.235
316312AB1-027
Solar/Wind Harmer
0.416
3142433PROV 92
Adder
0.212
3142433PROV 92
Adder
0.212
315976AC1-164 GENA
Solar/Wind Harmer
12.24
316169AC1-164_GENC
Solar/Wind Harmer
10.574
315975AC1-164 GENB
Solar/Wind Harmer
0.362
270494AE1-108_GEN
Solar/Wind Harmer
3.007
316315AB2-025 C
Solar/Wind Harmer
0.31
315814AE2-033 C
Solar/Wind Harmer
10.64
972265AH1-717 GEN
Adder
7.808
3151201GRAVEL4
Adder
7.319
3151191GRAVEL3
Adder
7.227
3151211GRAVEL5
Adder
7.227
315657AE1-056 GEN
Solar/Wind Harmer
4.225
3143873LANEXA
Solar/Wind Harmer
-0.007
946301AF1-294 GEN
Solar/Wind Harmer
2.828
961791AG1-021 GEN
Solar/Wind Harmer
1.38
315833AF1-017_GEN
Solar/Wind Harmer
2.058
316349AD2-085 GEN
Solar/Wind Harmer
0.964
971445AH1-216 GEN
Solar/Wind Harmer
6.695
316311AC2-079 GEN
Solar/Wind Harmer
5.457
970683AG2-441 GEN
Solar/Wind Harmer
8.368
970681AG2-440 GEN
Solar/Wind Harmer
6.695
316314AB2-024 C
Solar/Wind Harmer
0.899
315662AE1-191 GEN
Solar/Wind Harmer
1.258
315666AE1-190 GEN
Solar/Wind Harmer
0.314
316059AD1-063 C
Solar/Wind Harmer
0.235
3144303KENBRDG
Solar/Wind Harmer
-0.008
971443AH1-215 GEN
Solar/Wind Harmer
2.035
957601AF2-054 GEN
Solar/Wind Harmer
0.305
3141873WAN 176
Solar/Wind Harmer
-0.002
957831AF2-077 GEN
Solar/Wind Harmer
0.305
3138283WHITEMARSH
Solar/Wind Harmer
0.016
315835AF2-110_GEN
Solar/Wind Harmer
1.263
946281AF1-292 GEN
Solar/Wind Harmer
0.224
3141913WHIT STONE
Solar/Wind Harmer
-0.01
3152611GOSPORTB
Adder
1.125
3152621GOSPORTC
Adder
0.955
3152601GOSPORTA
Adder
0.881
3151081ELIZAR1
Adder
8.079
3151091ELIZAR2
Adder
7.939
3138133OCRAN
Solar/Wind Harmer
-0.003
316305AF2-043 C
Solar/Wind Harmer
0.297
316087AB2-174 GEN
Solar/Wind Harmer
1.398
957871AF2-081 GEN
Solar/Wind Harmer
4.888
3146486SUNBURY
Solar/Wind Harmer
-0.01
3146486SUNBURY
Solar/Wind Harmer
-0.01
319010AE1-072 C
Solar/Wind Harmer
1.975
3146406KITTY HAWK
Solar/Wind Harmer
0.008
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
313526AB2-022
Solar/Wind Harmer
0.262
316321Z2-027
Solar/Wind Harmer
0.262
3146396TANGLEW
Solar/Wind Harmer
0.179
3145176PASQUOTANK
Solar/Wind Harmer
-0.006
315611Z1-036_GEN2
Solar/Wind Harmer
2.371
965291AG1-394 GEN
Solar/Wind Harmer
0.851
3137643SOCKMAN
Solar/Wind Harmer
-0.038
941031AE2-094 GEN
Solar/Wind Harmer
17.899
944011AF1-069 GEN
Solar/Wind Harmer
5.608
3130156CHOWAN
Solar/Wind Harmer
-0.01
3130156CHOWAN
Solar/Wind Harmer
-0.01
316239AB2-077_GEN
Solar/Wind Harmer
0.287
316238AB2-078_GEN
Solar/Wind Harmer
0.287
315652AC1-086 GEN
Solar/Wind Harmer
10.692
971967AH1-528 GEN
Solar/Wind Harmer
17.858
3146043SEABORD
Solar/Wind Harmer
-0.009
316318V4-068
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
-0.009
315607AA1-063A GEN
Solar/Wind Harmer
0.958
962981AG1-147 GEN
Solar/Wind Harmer
4.144
972189AH1-679 GEN
Adder
1.34
970673AG2-436 GEN
Solar/Wind Harmer
16.786
970673AG2-436 GEN
Solar/Wind Harmer
8.499
970119AG2-088 GEN
50/50
53.032
3150851SPRUNCC
50/50
1.05
3143096IRON208
50/50
0.691
3151931BEARGRDN S1
50/50
1.658
3151911BEARGRDN G1
50/50
1.285
3143226MDLTHAN
Solar/Wind Harmer
-0.045
3143526WINTERP
Solar/Wind Harmer
-0.185
3143336POWHATN
Solar/Wind Harmer
3.921
316336AC2-165 C
Solar/Wind Harmer
5.212
970937AG2-583 GEN
Solar/Wind Harmer
15.928
3142543TWELFTH
Solar/Wind Harmer
-0.002
972003AH1-546 GEN
Solar/Wind Harmer
7.6
944631AF1-128 GEN
Adder
61.666
315671AE2-027_GEN
Solar/Wind Harmer
10.745
316322AB2-045
Solar/Wind Harmer
0.469
3146776BUCKING
Solar/Wind Harmer
-0.006
971377AH1-170 GEN
Solar/Wind Harmer
1.74
3147623JAMES R
Solar/Wind Harmer
0.215
970129AG2-093 GEN
Solar/Wind Harmer
3.033
316458AB2-190 GEN2
Solar/Wind Harmer
1.338
971069AG2-661 GEN
Solar/Wind Harmer
2.026
3146926FARMVIL
Solar/Wind Harmer
-0.007
3142416OLDCHRC
Solar/Wind Harmer
-0.032
3142416OLDCHRC
Solar/Wind Harmer
-0.012
3142433PROV 92
Solar/Wind Harmer
-0.049
3142433PROV 92
Adder
0.212
3142433PROV 92
Adder
0.212
971647AH1-324 GEN
Solar/Wind Harmer
6.07
970659AG2-427 GEN
Solar/Wind Harmer
6.44
316381AD1-082 GEN
Solar/Wind Harmer
1.101
961611AG1-000B GEN
Solar/Wind Harmer
5.807
970661AG2-428 GEN
Solar/Wind Harmer
12.397
3151171GRAVELC
Adder
1.07
963171AG1-166 GEN
Solar/Wind Harmer
1.38
971563AH1-280 GEN
Solar/Wind Harmer
1.38
3144293JTRSVLE
Adder
0.313
3145336SMITFLD
Solar/Wind Harmer
-0.043
970685AG2-442 GEN
Solar/Wind Harmer
9.372
971777AH1-397 GEN
Solar/Wind Harmer
1.247
3141843SHACKLE
Adder
0.482
316159AE1-175 C
Solar/Wind Harmer
0.282
3141766HARMONY
Solar/Wind Harmer
-0.002
316023GEN1_S
Solar/Wind Harmer
0.689
3138126ROCKLANDING
Solar/Wind Harmer
0.031
316093AE2-104_GEN
Solar/Wind Harmer
2.937
316072AD1-144
Solar/Wind Harmer
0.204
971317AH1-138 GEN
Solar/Wind Harmer
1.259
960081AF2-299 GEN
Solar/Wind Harmer
1.124
316375AC2-012 GEN
Solar/Wind Harmer
3.436
3150981CHESPKA
Adder
1.103
962491AG1-098 GEN
Solar/Wind Harmer
6.636
971795AH1-408 GEN
Solar/Wind Harmer
7.428
3138133OCRAN
Solar/Wind Harmer
-0.006
3147043LAWRENC
Adder
0.794
316246AF1-032 C
Solar/Wind Harmer
0.2
315693AD1-088 GEN
Solar/Wind Harmer
4.92
316388AE2-253 GEN
Solar/Wind Harmer
0.66
3146456SLIGO L269
Solar/Wind Harmer
-0.01
944591AF1-124 GEN
Solar/Wind Harmer
44.378
939411AE1-173 GEN
Solar/Wind Harmer
48.513
3146516WINFALL
Solar/Wind Harmer
-0.031
3146516WINFALL
Solar/Wind Harmer
-0.01
940641AE2-051 GEN
Solar/Wind Harmer
9.075
315800Z1-036_GEN1
Solar/Wind Harmer
2.371
3130156CHOWAN
Solar/Wind Harmer
-0.01
316237AB2-079_GEN
Solar/Wind Harmer
0.287
316011AB1-132 GEN
Solar/Wind Harmer
1.988
962571AG1-106 GEN
Solar/Wind Harmer
1.366
3145893MURPHYS
Solar/Wind Harmer
-0.038
3145893MURPHYS
Solar/Wind Harmer
0.281
957481AF2-042 GEN
Solar/Wind Harmer
29.606
3150351NORNECKC2
Adder
0.759
316045AC1-158 PL2
Solar/Wind Helper
2.706
3147666LOUISA
Solar/Wind Helper
0.466
316192AB2-158 GEN
Solar/Wind Helper
0.76
3150861SPRUNCD
50/50
1.05
3143096IRON208
50/50
0.691
3143096IRON208
50/50
0.677
3151921BEARGRDN G2
50/50
1.285
316313AB2-026
Solar/Wind Harmer
0.891
316258AE1-075 C
Solar/Wind Harmer
0.802
316405AF2-144 C
Solar/Wind Harmer
0.846
3143336POWHATN
Solar/Wind Harmer
3.333
315839AE2-212 C
Solar/Wind Harmer
0.428
965281AG1-393 GEN
Solar/Wind Harmer
1.772
970133AG2-095 GEN
Solar/Wind Harmer
1.574
3146776BUCKING
Solar/Wind Harmer
-0.005
970221AG2-151 GEN
Solar/Wind Harmer
8.699
970293AG2-193 GEN
Solar/Wind Harmer
1.728
3142946ENON
Solar/Wind Harmer
-0.004
970129AG2-093 GEN
Solar/Wind Harmer
7.488
315778AD1-151 GEN
Solar/Wind Harmer
11.091
315813AE1-149 C
Solar/Wind Harmer
7.967
3146926FARMVIL
Solar/Wind Harmer
-0.007
316473AC1-191 GEN
Solar/Wind Harmer
1.33
3142416OLDCHRC
Solar/Wind Harmer
1.243
3142433PROV 92
Adder
0.212
3142433PROV 92
Adder
0.212
970659AG2-427 GEN
Solar/Wind Harmer
1.141
316083AB2-161 GEN
Solar/Wind Harmer
1.949
942461AE2-259 GEN
Solar/Wind Harmer
1.79
961611AG1-000B GEN
Solar/Wind Harmer
2.478
970661AG2-428 GEN
Solar/Wind Harmer
2.197
970909AG2-566 GEN
Solar/Wind Harmer
1.087
3151221GRAVEL6
Adder
7.311
3151171GRAVELC
Adder
1.407
3147133PAMPLIN
Solar/Wind Harmer
-0.035
971193AH1-056 GEN
Solar/Wind Harmer
7.041
963181AG1-167 GEN
Solar/Wind Harmer
1.035
3144293JTRSVLE
Adder
0.313
3145336SMITFLD
Solar/Wind Harmer
-0.004
3141843SHACKLE
Adder
0.482
316203AE2-005 GEN
Solar/Wind Harmer
4.468
316382AG1-145 C
Solar/Wind Harmer
0.316
959311AF2-222 GEN
Solar/Wind Harmer
10.922
316280AD1-041 GEN
Solar/Wind Harmer
0.786
3141766HARMONY
Solar/Wind Harmer
0.925
970257AG2-171 GEN
Solar/Wind Harmer
3.886
3144216WINCHST
Adder
0.344
315785AD2-033 C
Solar/Wind Harmer
2.318
316365GEN2_N
Solar/Wind Harmer
0.689
316156AD2-030 GEN
Solar/Wind Harmer
0.272
3141873WAN 176
Solar/Wind Harmer
1.211
3144536CHRHLND
Solar/Wind Harmer
-0.002
3150921YORKTN3
Adder
2.258
966621AG1-532 GEN
Solar/Wind Harmer
0.203
3145273HOLLAND
Solar/Wind Harmer
-0.007
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
8.182
3147043LAWRENC
Solar/Wind Harmer
-0.006
964241AG1-285 GEN
Solar/Wind Harmer
7.705
3146456SLIGO L269
Solar/Wind Harmer
-0.01
971153AH1-033 GEN
Solar/Wind Harmer
1.191
316320Y1-086
Solar/Wind Harmer
0.57
944581AF1-123 GEN
Solar/Wind Harmer
44.219
944601AF1-125 GEN
Solar/Wind Harmer
43.529
313506AB2-031 GEN
Solar/Wind Harmer
0.781
316435W1029_GEN3
Solar/Wind Harmer
1.758
3146516WINFALL
Solar/Wind Harmer
-0.01
3146626S HERTFORD
Solar/Wind Harmer
-0.01
316131AB2-060 GEN
Solar/Wind Harmer
1.04
3156081AA2-088 GEN
Solar/Wind Harmer
3.122
3146376EDENTON
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
0.066
3145893MURPHYS
Solar/Wind Harmer
-0.009
962971AG1-146 GEN
Solar/Wind Harmer
1.776
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
957521AF2-046 GEN
Solar/Wind Harmer
7.444
961681AG1-008 GEN
Solar/Wind Harmer
7.444
3150351NORNECKC2
Adder
0.772
316044AC1-158 PL1
Solar/Wind Helper
0.845
316450AC1-158 RIC
Solar/Wind Helper
0.225
3147666LOUISA
Solar/Wind Helper
0.268
3142366NRTHEST
50/50
0.486
3150691DARBY 3
50/50
10.231
3150701DARBY 4
50/50
10.207
3150681DARBY 2
50/50
10.195
3150671DARBY 1
50/50
10.183
944641AF1-129 GEN
50/50
67.565
971223AH1-071 GEN
Solar/Wind Harmer
5.586
3143526WINTERP
Solar/Wind Harmer
-0.185
316240AF1-291 C
Solar/Wind Harmer
0.446
3146776BUCKING
Solar/Wind Harmer
-0.055
3146776BUCKING
Solar/Wind Harmer
-0.005
971489AH1-241 GEN
Solar/Wind Harmer
8.259
3142946ENON
Solar/Wind Harmer
-0.001
3142296MT RD221
Adder
0.383
316033AB2-134 GEN
Solar/Wind Harmer
4.034
315697AD1-025 GEN
Solar/Wind Harmer
2.53
316075AC2-137 C
Solar/Wind Harmer
0.337
966871AG1-558 GEN
Solar/Wind Harmer
0.371
966871AG1-558 GEN
Solar/Wind Harmer
0.127
970657AG2-426 GEN
Solar/Wind Harmer
3.712
970657AG2-426 GEN
Solar/Wind Harmer
0.776
3144356SAPONY
Solar/Wind Harmer
0.401
970301AG2-198 GEN
Solar/Wind Harmer
5.724
3147133PAMPLIN
Solar/Wind Harmer
-0.011
3147133PAMPLIN
Solar/Wind Harmer
-0.009
971741AH1-377 GEN
Solar/Wind Harmer
12.88
958211AF2-115 GEN
Solar/Wind Harmer
1.725
963191AG1-168 GEN
Solar/Wind Harmer
1.035
3144293JTRSVLE
Adder
0.313
3144293JTRSVLE
Adder
0.263
316236AE1-162_GEN
Solar/Wind Harmer
0.325
316441AF1-014 GEN
Solar/Wind Harmer
0.714
316034AC1-036 C
Solar/Wind Harmer
0.192
970323AG2-213 GEN
Solar/Wind Harmer
5.182
971775AH1-396 GEN
Solar/Wind Harmer
0.738
315821AE2-092 GEN
Solar/Wind Harmer
2.142
316036AC1-147 C
Solar/Wind Harmer
0.268
3150991CHESPKB
Adder
0.926
3150991CHESPKB
Adder
0.903
315742AE1-103 GEN
Solar/Wind Harmer
1.033
316316AC1-027 C
Solar/Wind Harmer
0.303
3142956BIRDNECK
Solar/Wind Harmer
0.529
316185AD1-033 GEN
Solar/Wind Harmer
1.035
3145506HICKORY
Solar/Wind Harmer
-0.039
3145506HICKORY
Solar/Wind Harmer
-0.023
3145506HICKORY
Solar/Wind Harmer
-0.006
316339AD2-160 GEN
Solar/Wind Harmer
0.66
316018AA1-139 ULT2
Solar/Wind Harmer
0.838
316017AA1-139 ULT1
Solar/Wind Harmer
0.791
3137176SLIGO L2192
Solar/Wind Harmer
-0.039
3146456SLIGO L269
Solar/Wind Harmer
1.154
3130086AYDLETT
Solar/Wind Harmer
-0.039
3146386ELIZ CT
Solar/Wind Harmer
-0.01
316181AB2-040 GEN
Solar/Wind Harmer
1.355
316431W1029_GEN1
Solar/Wind Harmer
1.758
316433W1029_GEN2
Solar/Wind Harmer
1.758
3146516WINFALL
Solar/Wind Harmer
-0.01
3146516WINFALL
Solar/Wind Harmer
-0.01
3146516WINFALL
Solar/Wind Harmer
-0.01
3146626S HERTFORD
Solar/Wind Harmer
-0.01
3146626S HERTFORD
Solar/Wind Harmer
-0.01
313527AB2-043 GEN
Solar/Wind Harmer
1.557
3146376EDENTON
Solar/Wind Harmer
0.283
3146376EDENTON
Solar/Wind Harmer
0.283
970933AG2-581 GEN
Solar/Wind Harmer
8.917
3145893MURPHYS
Solar/Wind Harmer
0.265
3145893MURPHYS
Solar/Wind Harmer
-0.017
970099AG2-077 GEN
Solar/Wind Harmer
11.843
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
972185AH1-677 GEN
Adder
4.694
972187AH1-678 GEN
Adder
2.365
3150341NORNECKC1
Adder
0.798
3150341NORNECKC1
Adder
0.791
316447AC1-158 HLD
Solar/Wind Helper
1.861
LAGNLTFEXP_LAGN->PJM
CLTF
3.457
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.232
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.004
MECLTFEXP_MEC->PJM
CLTF
1.722
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.237
TVALTFEXP_TVA->PJM
CLTF
1.744
SIGELTFEXP_SIGE->PJM
CLTF
0.053
CPLELTFEXP_CPLE->PJM
CLTF
4.658
NYPJM->LTFIMP_NY
CLTF
1.079
LGEELTFEXP_LGEE->PJM
CLTF
0.644
WECLTFEXP_WEC->PJM
CLTF
0.324
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.458

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:195.13 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:1291.31
MW Contribution:21.64
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.238
3144293JTRSVLE
50/50
0.706
970413AG2-270 GEN
50/50
10.245
3151591KERR 2
50/50
0.22
3151031BRUNSWICKG2
50/50
1.059
3151261ROARAP2
50/50
0.095
3150861SPRUNCD
50/50
0.364
966251AG1-494 GEN
50/50
1.288
970221AG2-151 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
0.132
3146926FARMVIL
Solar/Wind Harmer
0.176
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.159
316258AE1-075 C
Solar/Wind Harmer
0.19
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.801
970909AG2-566 GEN
Solar/Wind Harmer
2.396
3147133PAMPLIN
Solar/Wind Harmer
0.693
971193AH1-056 GEN
Solar/Wind Harmer
13.448
963181AG1-167 GEN
Solar/Wind Harmer
0.835
959311AF2-222 GEN
Solar/Wind Harmer
15.884
970257AG2-171 GEN
Solar/Wind Harmer
5.55
315785AD2-033 C
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
9.804
316131AB2-060 GEN
Solar/Wind Harmer
0.426
958131AF2-107 GEN
Solar/Wind Harmer
3.651
316478AD1-087 GEN
Solar/Wind Harmer
0.382
316486AD2-202 GEN
Solar/Wind Harmer
0.112
3147043LAWRENC
Solar/Wind Harmer
0.059
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.912
971683AH1-343 GEN
Solar/Wind Harmer
3.032
313506AB2-031 GEN
Solar/Wind Harmer
0.248
970917AG2-570 GEN
Solar/Wind Harmer
6.901
316365GEN2_N
Solar/Wind Harmer
0.164
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
0.117
3145893MURPHYS
Solar/Wind Harmer
0.07
957521AF2-046 GEN
Solar/Wind Harmer
5.202
961681AG1-008 GEN
Solar/Wind Harmer
5.202
3145796HORNRTN
Solar/Wind Harmer
0.279
3145796HORNRTN
Solar/Wind Harmer
0.07
316210AC1-098 GEN
Solar/Wind Harmer
0.644
3146173TUNIS
Solar/Wind Harmer
0.069
316463AE2-346 GEN
Solar/Wind Harmer
0.059
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.732
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.069
316327AA2-057 GEN
Solar/Wind Harmer
0.102
315724AD1-057 GEN
Solar/Wind Harmer
0.25
3145273HOLLAND
Solar/Wind Harmer
0.05
3156021HOLLOMANSOL
Solar/Wind Harmer
0.301
3146233WITAKRS
Solar/Wind Harmer
0.331
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3146206CASHIE
Solar/Wind Harmer
0.065
315813AE1-149 C
Solar/Wind Harmer
3.482
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316283AC2-100 C
Solar/Wind Harmer
0.127
315839AE2-212 C
Solar/Wind Harmer
0.001
315737AD1-076 GEN
Solar/Wind Harmer
0.835
970661AG2-428 GEN
Solar/Wind Harmer
1.373
971157AH1-035 GEN
Solar/Wind Harmer
0.778
315614AA2-178 GEN
Solar/Wind Harmer
0.37
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.129
3146376EDENTON
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
4.548
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316435W1029_GEN3
Solar/Wind Harmer
0
965281AG1-393 GEN
Solar/Wind Harmer
0.68
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
316320Y1-086
Solar/Wind Harmer
0
3145933PARMELE
Solar/Wind Harmer
0.063
966801AG1-551 GEN
Solar/Wind Harmer
0.74
3146456SLIGO L269
Solar/Wind Harmer
0.063
971153AH1-033 GEN
Solar/Wind Harmer
0.732
944581AF1-123 GEN
Solar/Wind Harmer
14.239
944601AF1-125 GEN
Solar/Wind Harmer
14.019
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3151101ELIZAR3
Adder
5.847
3144873MCLAUGH
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.009
3151931BEARGRDN S1
50/50
5.469
3151911BEARGRDN G1
50/50
4.238
3144293JTRSVLE
50/50
0.706
970119AG2-088 GEN
50/50
15.414
3151531CLOVER1
50/50
2.348
3151601KERR 3
50/50
0.22
3151581KERR 1
50/50
0.079
3147043LAWRENC
50/50
0.939
3151051BRUNSWICKS1
50/50
2.197
3151021BRUNSWICKG1
50/50
1.059
971451AH1-221 GEN
50/50
3.216
315243AE2-183_GT3
50/50
1.321
3151261ROARAP2
50/50
0.097
3150851SPRUNCC
50/50
0.364
972003AH1-546 GEN
Solar/Wind Harmer
18.676
971377AH1-170 GEN
Solar/Wind Harmer
4.327
3147623JAMES R
Solar/Wind Harmer
0.94
970937AG2-583 GEN
Solar/Wind Harmer
23.217
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.147
3146926FARMVIL
Solar/Wind Harmer
0.176
316336AC2-165 C
Solar/Wind Harmer
0.011
3143336POWHATN
Solar/Wind Harmer
4.472
963171AG1-166 GEN
Solar/Wind Harmer
1.114
971563AH1-280 GEN
Solar/Wind Harmer
2.228
970685AG2-442 GEN
Solar/Wind Harmer
14.313
962491AG1-098 GEN
Solar/Wind Harmer
7.815
315693AD1-088 GEN
Solar/Wind Harmer
6.344
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Harmer
0.116
957481AF2-042 GEN
Solar/Wind Harmer
29.295
970401AG2-262 GEN
Solar/Wind Harmer
0.638
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
4.184
3143526WINTERP
Solar/Wind Harmer
0.504
316129AC1-054 GEN
Solar/Wind Harmer
0.363
971795AH1-408 GEN
Solar/Wind Harmer
6.199
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.793
970919AG2-571 GEN
Solar/Wind Harmer
2.76
970087AG2-069 GEN
Solar/Wind Harmer
6.187
3145783HORNRTN
Solar/Wind Harmer
0.076
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
5.984
316023GEN1_S
Solar/Wind Harmer
0.164
939411AE1-173 GEN
Solar/Wind Harmer
30.681
316011AB1-132 GEN
Solar/Wind Harmer
1.286
962571AG1-106 GEN
Solar/Wind Harmer
1.007
3146263WOODLND
Solar/Wind Harmer
0.071
3145893MURPHYS
Solar/Wind Harmer
0.281
3145893MURPHYS
Solar/Wind Harmer
0.312
3145796HORNRTN
Solar/Wind Harmer
0.23
3145796HORNRTN
Solar/Wind Harmer
0.07
316212AC1-099_GEN
Solar/Wind Harmer
0.359
3146173TUNIS
Solar/Wind Harmer
0.069
3145823KELFORD
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
315722AD1-056 GEN
Solar/Wind Harmer
0.422
3146233WITAKRS
Solar/Wind Harmer
0.263
3146206CASHIE
Solar/Wind Harmer
0.065
971547AH1-271 GEN
Solar/Wind Harmer
1.396
970659AG2-427 GEN
Solar/Wind Harmer
3.146
316381AD1-082 GEN
Solar/Wind Harmer
0.068
970661AG2-428 GEN
Solar/Wind Harmer
6.453
3145663CRESWEL
Solar/Wind Harmer
0.181
971163AH1-040 GEN
Solar/Wind Harmer
5.167
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.052
316359AB2-059 GEN
Solar/Wind Harmer
0.231
316049AB1-081 GEN
Solar/Wind Harmer
0.368
3142053HEARTS
Solar/Wind Harmer
0.113
316093AE2-104_GEN
Solar/Wind Harmer
1.081
3130156CHOWAN
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3142543TWELFTH
Solar/Wind Harmer
0.006
3146516WINFALL
Solar/Wind Harmer
0.207
3146516WINFALL
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.283
316246AF1-032 C
Solar/Wind Harmer
0.029
3146293MARTNCO
Solar/Wind Harmer
0.059
316494AC1-189 GEN
Solar/Wind Harmer
0.214
3146456SLIGO L269
Solar/Wind Harmer
0.063
316388AE2-253 GEN
Solar/Wind Harmer
0.198
944591AF1-124 GEN
Solar/Wind Harmer
14.289
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
972205AH1-687 GEN
50/50
20.67
316303AF2-085
50/50
2.055
3151541CLOVER2
50/50
2.336
3151611KERR 4
50/50
0.22
3151621KERR 5
50/50
0.22
3151631KERR 6
50/50
0.22
3151641KERR 7
50/50
0.22
963041AG1-153 GEN
50/50
2.144
315244AE2-183_ST
50/50
2.284
3151281ROARAP4
50/50
0.094
3151281ROARAP4
50/50
0.088
971285AH1-108 GEN
50/50
0.596
315779AE2-040
50/50
1.013
971447AH1-217 GEN
Solar/Wind Harmer
11.337
971845AH1-439 GEN
Solar/Wind Harmer
16.33
970285AG2-188 GEN
Solar/Wind Harmer
27.559
270494AE1-108_GEN
Solar/Wind Harmer
3.817
315657AE1-056 GEN
Solar/Wind Harmer
7.617
946301AF1-294 GEN
Solar/Wind Harmer
4.122
961791AG1-021 GEN
Solar/Wind Harmer
2.005
970683AG2-441 GEN
Solar/Wind Harmer
12.78
970681AG2-440 GEN
Solar/Wind Harmer
10.224
3144303KENBRDG
Solar/Wind Harmer
0.139
971443AH1-215 GEN
Solar/Wind Harmer
2.888
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.258
316233AE1-074 FULL
Solar/Wind Harmer
0.078
971281AH1-106 GEN
Solar/Wind Harmer
1.344
971283AH1-107 GEN
Solar/Wind Harmer
1.344
970831AG2-522 GEN
Solar/Wind Harmer
4.036
3147173SINAI
Solar/Wind Harmer
0.092
3147243WELCO
Solar/Wind Harmer
0.057
971967AH1-528 GEN
Solar/Wind Harmer
13.711
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
16.986
970673AG2-436 GEN
Solar/Wind Harmer
11.324
941031AE2-094 GEN
Solar/Wind Harmer
14.544
944011AF1-069 GEN
Solar/Wind Harmer
4.752
3137643SOCKMAN
Solar/Wind Harmer
0.315
970865AG2-541 GEN
Solar/Wind Harmer
2.702
970085AG2-068 GEN
Solar/Wind Harmer
4.124
970581AG2-369 GEN
Solar/Wind Harmer
3.547
315607AA1-063A GEN
Solar/Wind Harmer
0.154
3146043SEABORD
Solar/Wind Harmer
0.075
315814AE2-033 C
Solar/Wind Harmer
5.747
316315AB2-025 C
Solar/Wind Harmer
0.059
965291AG1-394 GEN
Solar/Wind Harmer
0.317
315652AC1-086 GEN
Solar/Wind Harmer
7.782
3145893MURPHYS
Solar/Wind Harmer
0.19
3145893MURPHYS
Solar/Wind Harmer
0.07
3145796HORNRTN
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.028
3146033SCOT NK
Solar/Wind Harmer
0.276
316123AC1-075 GEN
Solar/Wind Harmer
0.094
970165AG2-112 GEN
Solar/Wind Harmer
0.558
970163AG2-111 GEN
Solar/Wind Harmer
0.532
3145513AHOSKIE
Solar/Wind Harmer
0.143
3145513AHOSKIE
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3143316POE
Solar/Wind Harmer
0.269
316319Z2-044 C
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.065
970601AG2-382 GEN
Solar/Wind Harmer
2.444
315732AD1-074 GEN1
Solar/Wind Harmer
0.373
315733AD1-074 GEN2
Solar/Wind Harmer
0.373
315735AD1-075 GEN1
Solar/Wind Harmer
0.187
3130546PLYMOUTH
Solar/Wind Harmer
0.065
315816AE2-034 GEN
Solar/Wind Harmer
0.277
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.044
316311AC2-079 GEN
Solar/Wind Harmer
1.853
315835AF2-110_GEN
Solar/Wind Harmer
0.441
3144293JTRSVLE
50/50
0.706
3144293JTRSVLE
50/50
0.594
970535AG2-341 GEN
50/50
2.11
3152661PLYWOOD A
50/50
0.217
3151041BRUNSWICKG3
50/50
1.059
972187AH1-678 GEN
50/50
2.43
315242AE2-183_GT2
50/50
1.321
315241AE2-183_GT1
50/50
1.313
972185AH1-677 GEN
50/50
4.762
970533AG2-339 GEN
50/50
7.019
970531AG2-338 GEN
50/50
2.808
971489AH1-241 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
1.465
3146776BUCKING
Solar/Wind Harmer
0.119
315821AE2-092 GEN
Solar/Wind Harmer
0.014
970301AG2-198 GEN
Solar/Wind Harmer
9.583
3147133PAMPLIN
Solar/Wind Harmer
0.221
3147133PAMPLIN
Solar/Wind Harmer
0.176
958211AF2-115 GEN
Solar/Wind Harmer
2.506
963191AG1-168 GEN
Solar/Wind Harmer
0.835
971741AH1-377 GEN
Solar/Wind Harmer
20.177
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.401
971775AH1-396 GEN
Solar/Wind Harmer
0.278
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971223AH1-071 GEN
Solar/Wind Harmer
1.233
962561AG1-105 GEN
Solar/Wind Harmer
5.397
939181AE1-148 GEN
Solar/Wind Harmer
5.333
970099AG2-077 GEN
Solar/Wind Harmer
11.718
964791AG1-342 GEN
Solar/Wind Harmer
2.089
3146843MT LREL
Solar/Wind Harmer
0.109
3146843MT LREL
Solar/Wind Harmer
0.109
3143526WINTERP
Solar/Wind Harmer
0.504
970933AG2-581 GEN
Solar/Wind Harmer
7.465
316181AB2-040 GEN
Solar/Wind Harmer
0.116
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.078
966811AG1-552 GEN
Solar/Wind Harmer
0.843
3145593CAROLNA
Solar/Wind Harmer
0.097
3145783HORNRTN
Solar/Wind Harmer
1.361
3145783HORNRTN
Solar/Wind Harmer
1.089
3145783HORNRTN
Solar/Wind Harmer
0.34
3145783HORNRTN
Solar/Wind Harmer
0.136
316426AA2-053 GEN
Solar/Wind Harmer
0.256
3144356SAPONY
Solar/Wind Harmer
0.607
316274AC1-208 GEN
Solar/Wind Harmer
0.366
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.042
3145893MURPHYS
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
0.126
3145796HORNRTN
Solar/Wind Harmer
0.209
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
315742AE1-103 GEN
Solar/Wind Harmer
0.001
316222AC1-221 GEN
Solar/Wind Harmer
0.272
316065AD1-022 GEN
Solar/Wind Harmer
3.004
970657AG2-426 GEN
Solar/Wind Harmer
2.275
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
2.446
3146376EDENTON
Solar/Wind Harmer
0.286
3146376EDENTON
Solar/Wind Harmer
0.286
961601AG1-000A GEN
Solar/Wind Harmer
1.137
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3145493TOT1
Solar/Wind Harmer
0.148
3145453TOT5
Solar/Wind Harmer
0.089
3145603CNETO
Solar/Wind Harmer
0.059
3146386ELIZ CT
Solar/Wind Harmer
0.064
3145933PARMELE
Solar/Wind Harmer
0.127
3145933PARMELE
Solar/Wind Harmer
0.063
3130086AYDLETT
Solar/Wind Harmer
0.253
3137176SLIGO L2192
Solar/Wind Harmer
0.252
3146456SLIGO L269
Solar/Wind Harmer
1.121
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.035
316339AD2-160 GEN
Solar/Wind Harmer
0.103
3145506HICKORY
Solar/Wind Harmer
0.253
3145506HICKORY
Solar/Wind Harmer
0.152
3145506HICKORY
Solar/Wind Harmer
0.038
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.061
942751AE2-291 GEN
Solar/Wind Harmer
3.43
316240AF1-291 C
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.012
3150991CHESPKB
Adder
0.659
3150991CHESPKB
Adder
0.643
944641AF1-129 GEN
Adder
29.755
316236AE1-162_GEN
Solar/Wind Harmer
0
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.068
966001AG1-469 GEN
Solar/Wind Helper
0.206
315671AE2-027_GEN
Solar/Wind Harmer
4.043
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
1.077
3145336SMITFLD
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
0.644
961611AG1-000B GEN
Solar/Wind Harmer
3.17
971647AH1-324 GEN
Solar/Wind Harmer
2.576
3143096IRON208
Adder
0.252
971069AG2-661 GEN
Solar/Wind Harmer
1.071
316458AB2-190 GEN2
Solar/Wind Harmer
0.323
970129AG2-093 GEN
Solar/Wind Harmer
1.71
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.903
3147666LOUISA
Solar/Wind Helper
0.521
315773AC2-141 GEN
Solar/Wind Harmer
2.27
3145336SMITFLD
Solar/Wind Harmer
0.025
3151221GRAVEL6
Adder
4.403
3151171GRAVELC
Adder
0.847
961611AG1-000B GEN
Solar/Wind Harmer
1.612
3143096IRON208
Adder
0.252
3143096IRON208
Adder
0.247
315778AD1-151 GEN
Solar/Wind Harmer
4.818
970129AG2-093 GEN
Solar/Wind Harmer
3.634
970133AG2-095 GEN
Solar/Wind Harmer
0.576
316499AE2-029_GEN
Solar/Wind Helper
0.501
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.3
3148013FISHERV
Solar/Wind Helper
0.129
315616AA1-038_C
Solar/Wind Helper
0.524
3130156CHOWAN
Solar/Wind Harmer
0.064
3130156CHOWAN
Solar/Wind Harmer
0.064
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
316321Z2-027
Solar/Wind Harmer
0.012
3145176PASQUOTANK
Solar/Wind Harmer
0.039
3146396TANGLEW
Solar/Wind Harmer
0.175
316420AA1-050 GEN
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.034
316305AF2-043 C
Solar/Wind Harmer
0.001
957861AF2-080 GEN
Solar/Wind Harmer
2.737
3146406KITTY HAWK
Solar/Wind Harmer
0.008
319010AE1-072 C
Solar/Wind Harmer
0.319
957871AF2-081 GEN
Solar/Wind Harmer
3.153
316005AA1-067
Solar/Wind Harmer
0.068
3145746EVERETS
Solar/Wind Harmer
0.252
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
970181AG2-120 GEN
Solar/Wind Harmer
0.787
3151081ELIZAR1
Adder
5.773
3151091ELIZAR2
Adder
5.672
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.68
3152601GOSPORTA
Adder
0.628
971445AH1-216 GEN
Solar/Wind Harmer
4.321
972265AH1-717 GEN
Adder
4.702
3151201GRAVEL4
Adder
4.408
3151191GRAVEL3
Adder
4.352
3151211GRAVEL5
Adder
4.352
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.323
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.077
3148013FISHERV
Solar/Wind Helper
0.074
3148463FAIRFLD
Solar/Wind Helper
0.116
LAGNLTFEXP_LAGN->PJM
CLTF
1.972
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.131
MECLTFEXP_MEC->PJM
CLTF
0.546
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.458
TVALTFEXP_TVA->PJM
CLTF
0.973
NYPJM->LTFIMP_NY
CLTF
0.616
LGEELTFEXP_LGEE->PJM
CLTF
0.137
WECLTFEXP_WEC->PJM
CLTF
0.063
CPLELTFEXP_CPLE->PJM
CLTF
4.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.705

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:182.39 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1475.57
MW Contribution:28.43
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.633
316303AF2-085
50/50
2.054
971447AH1-217 GEN
Solar/Wind Harmer
14.897
971845AH1-439 GEN
Solar/Wind Harmer
21.465
970285AG2-188 GEN
Solar/Wind Harmer
34.19
270494AE1-108_GEN
Solar/Wind Harmer
9.286
315657AE1-056 GEN
Solar/Wind Harmer
9.291
946301AF1-294 GEN
Solar/Wind Harmer
6.004
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
16.801
970681AG2-440 GEN
Solar/Wind Harmer
13.441
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.796
316239AB2-077_GEN
Solar/Wind Harmer
0.439
316238AB2-078_GEN
Solar/Wind Harmer
0.439
316118AC1-105 GEN
Solar/Wind Harmer
0.773
316233AE1-074 FULL
Solar/Wind Harmer
0.293
3151931BEARGRDN S1
50/50
5.46
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.704
970119AG2-088 GEN
50/50
15.406
972003AH1-546 GEN
Solar/Wind Harmer
24.588
971377AH1-170 GEN
Solar/Wind Harmer
5.686
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.518
316322AB2-045
Solar/Wind Harmer
1.382
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.598
3143336POWHATN
Solar/Wind Harmer
3.349
963171AG1-166 GEN
Solar/Wind Harmer
2.929
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
18.817
962491AG1-098 GEN
Solar/Wind Harmer
10.277
315693AD1-088 GEN
Solar/Wind Harmer
7.416
316237AB2-079_GEN
Solar/Wind Harmer
0.439
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.531
970401AG2-262 GEN
Solar/Wind Harmer
0.797
315687AD1-152 GEN
Solar/Wind Harmer
1.353
971065AG2-659 GEN
Solar/Wind Harmer
5.503
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.948
971795AH1-408 GEN
Solar/Wind Harmer
7.828
316003AC1-222 GEN
Solar/Wind Harmer
0.95
960081AF2-299 GEN
Solar/Wind Harmer
1.043
970919AG2-571 GEN
Solar/Wind Harmer
2.759
970087AG2-069 GEN
Solar/Wind Harmer
8.141
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
940641AE2-051 GEN
Solar/Wind Harmer
7.878
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.555
939411AE1-173 GEN
Solar/Wind Harmer
40.398
316011AB1-132 GEN
Solar/Wind Harmer
1.663
962571AG1-106 GEN
Solar/Wind Harmer
1.142
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.68
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.782
3146233WITAKRS
Solar/Wind Harmer
-0.029
3144293JTRSVLE
50/50
0.704
3144293JTRSVLE
50/50
0.593
970535AG2-341 GEN
50/50
2.107
971489AH1-241 GEN
Solar/Wind Harmer
26.992
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.547
970301AG2-198 GEN
Solar/Wind Harmer
12.599
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
963191AG1-168 GEN
Solar/Wind Harmer
2.197
971741AH1-377 GEN
Solar/Wind Harmer
26.527
971281AH1-106 GEN
Solar/Wind Harmer
1.769
971283AH1-107 GEN
Solar/Wind Harmer
1.769
970831AG2-522 GEN
Solar/Wind Harmer
5.308
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.09
946281AF1-292 GEN
Solar/Wind Harmer
0.208
316087AB2-174 GEN
Solar/Wind Harmer
1.297
970673AG2-436 GEN
Solar/Wind Harmer
18.787
970673AG2-436 GEN
Solar/Wind Harmer
9.512
941031AE2-094 GEN
Solar/Wind Harmer
16.63
944011AF1-069 GEN
Solar/Wind Harmer
5.211
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970865AG2-541 GEN
Solar/Wind Harmer
3.55
970085AG2-068 GEN
Solar/Wind Harmer
5.427
970581AG2-369 GEN
Solar/Wind Harmer
4.667
315607AA1-063A GEN
Solar/Wind Harmer
0.852
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.6
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.71
315652AC1-086 GEN
Solar/Wind Harmer
8.941
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
316123AC1-075 GEN
Solar/Wind Harmer
0.832
970165AG2-112 GEN
Solar/Wind Harmer
0.733
970163AG2-111 GEN
Solar/Wind Harmer
0.699
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316319Z2-044 C
Solar/Wind Harmer
0.41
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.217
315732AD1-074 GEN1
Solar/Wind Harmer
1.475
315733AD1-074 GEN2
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.737
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316349AD2-085 GEN
Solar/Wind Harmer
0.645
315816AE2-034 GEN
Solar/Wind Harmer
0.587
316311AC2-079 GEN
Solar/Wind Harmer
3.659
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.779
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
316321Z2-027
Solar/Wind Harmer
0.193
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.193
316420AA1-050 GEN
Solar/Wind Harmer
0.816
316305AF2-043 C
Solar/Wind Harmer
0.215
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
3151081ELIZAR1
Adder
5.776
3151091ELIZAR2
Adder
5.675
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.681
3152601GOSPORTA
Adder
0.628
972265AH1-717 GEN
Adder
4.706
3151201GRAVEL4
Adder
4.411
3151191GRAVEL3
Adder
4.355
3151211GRAVEL5
Adder
4.355
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
316034AC1-036 C
Solar/Wind Harmer
0.362
970323AG2-213 GEN
Solar/Wind Harmer
9.73
971775AH1-396 GEN
Solar/Wind Harmer
1.386
313527AB2-043 GEN
Solar/Wind Harmer
2.416
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.096
939181AE1-148 GEN
Solar/Wind Harmer
7.013
970099AG2-077 GEN
Solar/Wind Harmer
15.412
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.821
972187AH1-678 GEN
Adder
2.289
316181AB2-040 GEN
Solar/Wind Harmer
1.257
972185AH1-677 GEN
Adder
4.486
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.855
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.79
316222AC1-221 GEN
Solar/Wind Harmer
0.745
316065AD1-022 GEN
Solar/Wind Harmer
3.665
970657AG2-426 GEN
Solar/Wind Harmer
2.282
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
3.387
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.822
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.78
966001AG1-469 GEN
Solar/Wind Helper
0.216
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.838
970659AG2-427 GEN
Solar/Wind Harmer
3.885
316381AD1-082 GEN
Solar/Wind Harmer
0.67
970661AG2-428 GEN
Solar/Wind Harmer
7.748
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.803
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.974
316049AB1-081 GEN
Solar/Wind Harmer
0.78
316093AE2-104_GEN
Solar/Wind Harmer
2.1
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
315800Z1-036_GEN1
Solar/Wind Harmer
1.779
316174AB2-169 GEN
Solar/Wind Harmer
1.109
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
316246AF1-032 C
Solar/Wind Harmer
0.144
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
944591AF1-124 GEN
Solar/Wind Harmer
32.454
3150981CHESPKA
Adder
0.786
3151171GRAVELC
Adder
0.645
3143096IRON208
Adder
0.253
944631AF1-128 GEN
Adder
26.841
316192AB2-158 GEN
Solar/Wind Helper
1.013
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.704
970221AG2-151 GEN
Solar/Wind Harmer
28.432
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.296
316313AB2-026
Solar/Wind Harmer
0.761
316258AE1-075 C
Solar/Wind Harmer
0.685
316405AF2-144 C
Solar/Wind Harmer
0.723
3143336POWHATN
Solar/Wind Harmer
2.847
970909AG2-566 GEN
Solar/Wind Harmer
2.392
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.485
963181AG1-167 GEN
Solar/Wind Harmer
2.197
959311AF2-222 GEN
Solar/Wind Harmer
20.924
970257AG2-171 GEN
Solar/Wind Harmer
7.297
315785AD2-033 C
Solar/Wind Harmer
4.227
964241AG1-285 GEN
Solar/Wind Harmer
12.89
316131AB2-060 GEN
Solar/Wind Harmer
1.639
958131AF2-107 GEN
Solar/Wind Harmer
4.847
316478AD1-087 GEN
Solar/Wind Harmer
1.065
316486AD2-202 GEN
Solar/Wind Harmer
0.312
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.31
960061AF2-297 GEN
Solar/Wind Harmer
5.143
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.986
313506AB2-031 GEN
Solar/Wind Harmer
0.724
970917AG2-570 GEN
Solar/Wind Harmer
21.795
3150861SPRUNCD
Adder
0.344
316365GEN2_N
Solar/Wind Harmer
0.555
3156081AA2-088 GEN
Solar/Wind Harmer
2.586
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.185
961681AG1-008 GEN
Solar/Wind Harmer
6.185
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146173TUNIS
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.125
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.963
316317KELFORD C
Solar/Wind Harmer
0.363
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.766
315724AD1-057 GEN
Solar/Wind Harmer
0.43
3145273HOLLAND
Solar/Wind Harmer
-0.006
3156021HOLLOMANSOL
Solar/Wind Harmer
1.002
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.587
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
1.186
315839AE2-212 C
Solar/Wind Harmer
0.22
970661AG2-428 GEN
Solar/Wind Harmer
1.373
315737AD1-076 GEN
Solar/Wind Harmer
1.386
316283AC2-100 C
Solar/Wind Harmer
0.686
971157AH1-035 GEN
Solar/Wind Harmer
0.911
315614AA2-178 GEN
Solar/Wind Harmer
0.783
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.858
3146516WINFALL
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.896
316435W1029_GEN3
Solar/Wind Harmer
1.299
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.419
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.891
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151101ELIZAR3
Adder
5.849
3151221GRAVEL6
Adder
4.406
3151171GRAVELC
Adder
0.848
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.338
3148013FISHERV
Solar/Wind Helper
0.13
315616AA1-038_C
Solar/Wind Helper
0.528
944581AF1-123 GEN
Solar/Wind Harmer
20.452
LAGNLTFEXP_LAGN->PJM
CLTF
1.959
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.573
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.107
MECLTFEXP_MEC->PJM
CLTF
0.537
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.437
TVALTFEXP_TVA->PJM
CLTF
0.967
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.612
LGEELTFEXP_LGEE->PJM
CLTF
0.133
WECLTFEXP_WEC->PJM
CLTF
0.061
CPLELTFEXP_CPLE->PJM
CLTF
4.206
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.627

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:182.39 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1475.54
MW Contribution:28.43
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.633
316303AF2-085
50/50
2.054
971447AH1-217 GEN
Solar/Wind Harmer
14.896
971845AH1-439 GEN
Solar/Wind Harmer
21.465
970285AG2-188 GEN
Solar/Wind Harmer
34.19
270494AE1-108_GEN
Solar/Wind Harmer
9.286
315657AE1-056 GEN
Solar/Wind Harmer
9.291
946301AF1-294 GEN
Solar/Wind Harmer
6.004
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
16.8
970681AG2-440 GEN
Solar/Wind Harmer
13.44
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.796
316239AB2-077_GEN
Solar/Wind Harmer
0.439
316238AB2-078_GEN
Solar/Wind Harmer
0.439
316118AC1-105 GEN
Solar/Wind Harmer
0.773
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.769
971283AH1-107 GEN
Solar/Wind Harmer
1.769
970831AG2-522 GEN
Solar/Wind Harmer
5.308
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.09
946281AF1-292 GEN
Solar/Wind Harmer
0.208
316087AB2-174 GEN
Solar/Wind Harmer
1.297
970673AG2-436 GEN
Solar/Wind Harmer
18.787
970673AG2-436 GEN
Solar/Wind Harmer
9.512
941031AE2-094 GEN
Solar/Wind Harmer
16.63
944011AF1-069 GEN
Solar/Wind Harmer
5.211
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970865AG2-541 GEN
Solar/Wind Harmer
3.55
970085AG2-068 GEN
Solar/Wind Harmer
5.427
970581AG2-369 GEN
Solar/Wind Harmer
4.667
315607AA1-063A GEN
Solar/Wind Harmer
0.852
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.6
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.71
315652AC1-086 GEN
Solar/Wind Harmer
8.941
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
316123AC1-075 GEN
Solar/Wind Harmer
0.832
3144293JTRSVLE
50/50
0.704
3144293JTRSVLE
50/50
0.593
970535AG2-341 GEN
50/50
2.107
971489AH1-241 GEN
Solar/Wind Harmer
26.992
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.547
970301AG2-198 GEN
Solar/Wind Harmer
12.599
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
963191AG1-168 GEN
Solar/Wind Harmer
2.197
971741AH1-377 GEN
Solar/Wind Harmer
26.527
316034AC1-036 C
Solar/Wind Harmer
0.361
970323AG2-213 GEN
Solar/Wind Harmer
9.729
971775AH1-396 GEN
Solar/Wind Harmer
1.386
313527AB2-043 GEN
Solar/Wind Harmer
2.416
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.096
939181AE1-148 GEN
Solar/Wind Harmer
7.013
970099AG2-077 GEN
Solar/Wind Harmer
15.412
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.821
972187AH1-678 GEN
Adder
2.289
316181AB2-040 GEN
Solar/Wind Harmer
1.257
972185AH1-677 GEN
Adder
4.486
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.855
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.79
316222AC1-221 GEN
Solar/Wind Harmer
0.745
316065AD1-022 GEN
Solar/Wind Harmer
3.665
970657AG2-426 GEN
Solar/Wind Harmer
2.282
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
3.387
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.822
3146516WINFALL
Solar/Wind Harmer
-0.007
970165AG2-112 GEN
Solar/Wind Harmer
0.733
970163AG2-111 GEN
Solar/Wind Harmer
0.699
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316319Z2-044 C
Solar/Wind Harmer
0.41
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.217
315732AD1-074 GEN1
Solar/Wind Harmer
1.475
315733AD1-074 GEN2
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.737
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316349AD2-085 GEN
Solar/Wind Harmer
0.645
315816AE2-034 GEN
Solar/Wind Harmer
0.587
316311AC2-079 GEN
Solar/Wind Harmer
3.659
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.779
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.193
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.193
316305AF2-043 C
Solar/Wind Harmer
0.215
316420AA1-050 GEN
Solar/Wind Harmer
0.816
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.781
966001AG1-469 GEN
Solar/Wind Helper
0.216
3151931BEARGRDN S1
50/50
5.46
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.704
970119AG2-088 GEN
50/50
15.406
972003AH1-546 GEN
Solar/Wind Harmer
24.587
971377AH1-170 GEN
Solar/Wind Harmer
5.686
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.517
316322AB2-045
Solar/Wind Harmer
1.382
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.597
3143336POWHATN
Solar/Wind Harmer
3.349
963171AG1-166 GEN
Solar/Wind Harmer
2.929
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
18.817
962491AG1-098 GEN
Solar/Wind Harmer
10.277
315693AD1-088 GEN
Solar/Wind Harmer
7.416
316237AB2-079_GEN
Solar/Wind Harmer
0.439
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.531
970401AG2-262 GEN
Solar/Wind Harmer
0.797
315687AD1-152 GEN
Solar/Wind Harmer
1.353
971065AG2-659 GEN
Solar/Wind Harmer
5.503
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.948
971795AH1-408 GEN
Solar/Wind Harmer
7.828
316003AC1-222 GEN
Solar/Wind Harmer
0.95
960081AF2-299 GEN
Solar/Wind Harmer
1.043
970919AG2-571 GEN
Solar/Wind Harmer
2.759
970087AG2-069 GEN
Solar/Wind Harmer
8.141
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
940641AE2-051 GEN
Solar/Wind Harmer
7.878
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.555
939411AE1-173 GEN
Solar/Wind Harmer
40.398
316011AB1-132 GEN
Solar/Wind Harmer
1.663
962571AG1-106 GEN
Solar/Wind Harmer
1.142
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.68
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.782
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.838
970659AG2-427 GEN
Solar/Wind Harmer
3.885
316381AD1-082 GEN
Solar/Wind Harmer
0.67
970661AG2-428 GEN
Solar/Wind Harmer
7.748
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.803
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.974
316049AB1-081 GEN
Solar/Wind Harmer
0.78
316093AE2-104_GEN
Solar/Wind Harmer
2.1
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
315800Z1-036_GEN1
Solar/Wind Harmer
1.779
316174AB2-169 GEN
Solar/Wind Harmer
1.109
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
316246AF1-032 C
Solar/Wind Harmer
0.144
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
944591AF1-124 GEN
Solar/Wind Harmer
32.454
3150981CHESPKA
Adder
0.786
3151171GRAVELC
Adder
0.645
3143096IRON208
Adder
0.253
944631AF1-128 GEN
Adder
26.842
316192AB2-158 GEN
Solar/Wind Helper
1.014
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
3151081ELIZAR1
Adder
5.776
3151091ELIZAR2
Adder
5.675
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.681
3152601GOSPORTA
Adder
0.628
972265AH1-717 GEN
Adder
4.706
3151201GRAVEL4
Adder
4.411
3151191GRAVEL3
Adder
4.355
3151211GRAVEL5
Adder
4.355
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.704
970221AG2-151 GEN
Solar/Wind Harmer
28.431
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.296
316313AB2-026
Solar/Wind Harmer
0.761
316258AE1-075 C
Solar/Wind Harmer
0.685
316405AF2-144 C
Solar/Wind Harmer
0.723
3143336POWHATN
Solar/Wind Harmer
2.847
970909AG2-566 GEN
Solar/Wind Harmer
2.392
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.484
963181AG1-167 GEN
Solar/Wind Harmer
2.197
959311AF2-222 GEN
Solar/Wind Harmer
20.924
970257AG2-171 GEN
Solar/Wind Harmer
7.297
315785AD2-033 C
Solar/Wind Harmer
4.227
964241AG1-285 GEN
Solar/Wind Harmer
12.89
316131AB2-060 GEN
Solar/Wind Harmer
1.639
958131AF2-107 GEN
Solar/Wind Harmer
4.847
316478AD1-087 GEN
Solar/Wind Harmer
1.065
316486AD2-202 GEN
Solar/Wind Harmer
0.312
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.31
960061AF2-297 GEN
Solar/Wind Harmer
5.143
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.986
313506AB2-031 GEN
Solar/Wind Harmer
0.724
970917AG2-570 GEN
Solar/Wind Harmer
21.795
3150861SPRUNCD
Adder
0.344
316365GEN2_N
Solar/Wind Harmer
0.555
3156081AA2-088 GEN
Solar/Wind Harmer
2.585
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.185
961681AG1-008 GEN
Solar/Wind Harmer
6.185
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146173TUNIS
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.125
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.963
316317KELFORD C
Solar/Wind Harmer
0.363
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.766
315724AD1-057 GEN
Solar/Wind Harmer
0.43
3145273HOLLAND
Solar/Wind Harmer
-0.006
3156021HOLLOMANSOL
Solar/Wind Harmer
1.002
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.587
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
1.186
315839AE2-212 C
Solar/Wind Harmer
0.22
970661AG2-428 GEN
Solar/Wind Harmer
1.373
315737AD1-076 GEN
Solar/Wind Harmer
1.386
316283AC2-100 C
Solar/Wind Harmer
0.686
971157AH1-035 GEN
Solar/Wind Harmer
0.911
315614AA2-178 GEN
Solar/Wind Harmer
0.783
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.858
3146516WINFALL
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.896
316435W1029_GEN3
Solar/Wind Harmer
1.299
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.419
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.891
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151101ELIZAR3
Adder
5.85
3151221GRAVEL6
Adder
4.406
3151171GRAVELC
Adder
0.848
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.339
3148013FISHERV
Solar/Wind Helper
0.13
315616AA1-038_C
Solar/Wind Helper
0.528
944581AF1-123 GEN
Solar/Wind Harmer
20.452
LAGNLTFEXP_LAGN->PJM
CLTF
1.959
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.572
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.107
MECLTFEXP_MEC->PJM
CLTF
0.537
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.437
TVALTFEXP_TVA->PJM
CLTF
0.967
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.612
LGEELTFEXP_LGEE->PJM
CLTF
0.133
WECLTFEXP_WEC->PJM
CLTF
0.061
CPLELTFEXP_CPLE->PJM
CLTF
4.206
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.626

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:174.94 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1415.27
MW Contribution:28.82
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.533
3151911BEARGRDN G1
50/50
4.287
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
18.19
972003AH1-546 GEN
Solar/Wind Harmer
24.898
971377AH1-170 GEN
Solar/Wind Harmer
5.763
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.282
316322AB2-045
Solar/Wind Harmer
1.394
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.86
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
963171AG1-166 GEN
Solar/Wind Harmer
2.905
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
18.606
3143226MDLTHAN
Solar/Wind Harmer
-0.015
962491AG1-098 GEN
Solar/Wind Harmer
9.894
315693AD1-088 GEN
Solar/Wind Harmer
7.12
316237AB2-079_GEN
Solar/Wind Harmer
0.427
3143526WINTERP
Solar/Wind Harmer
-0.065
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.362
315687AD1-152 GEN
Solar/Wind Harmer
1.282
971065AG2-659 GEN
Solar/Wind Harmer
5.251
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.904
971795AH1-408 GEN
Solar/Wind Harmer
7.449
3150851SPRUNCC
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.906
960081AF2-299 GEN
Solar/Wind Harmer
0.983
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
970919AG2-571 GEN
Solar/Wind Harmer
2.482
970087AG2-069 GEN
Solar/Wind Harmer
7.326
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.518
940641AE2-051 GEN
Solar/Wind Harmer
6.973
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.551
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
316212AC1-099_GEN
Solar/Wind Harmer
0.635
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.08
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
5.319
970659AG2-427 GEN
Solar/Wind Harmer
3.71
316381AD1-082 GEN
Solar/Wind Harmer
0.639
315722AD1-056 GEN
Solar/Wind Harmer
0.728
970661AG2-428 GEN
Solar/Wind Harmer
7.356
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
970129AG2-093 GEN
Solar/Wind Harmer
1.536
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.588
970535AG2-341 GEN
50/50
2.034
971489AH1-241 GEN
Solar/Wind Harmer
27.358
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.65
970301AG2-198 GEN
Solar/Wind Harmer
12.49
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.631
963191AG1-168 GEN
Solar/Wind Harmer
2.179
971741AH1-377 GEN
Solar/Wind Harmer
26.175
316034AC1-036 C
Solar/Wind Harmer
0.356
970323AG2-213 GEN
Solar/Wind Harmer
9.582
971775AH1-396 GEN
Solar/Wind Harmer
1.365
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.349
3143526WINTERP
Solar/Wind Harmer
-0.065
962561AG1-105 GEN
Solar/Wind Harmer
6.845
939181AE1-148 GEN
Solar/Wind Harmer
6.741
964791AG1-342 GEN
Solar/Wind Harmer
2.511
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.545
970933AG2-581 GEN
Solar/Wind Harmer
9.023
316181AB2-040 GEN
Solar/Wind Harmer
1.184
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.923
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.055
3145783HORNRTN
Solar/Wind Harmer
0.958
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.016
316426AA2-053 GEN
Solar/Wind Harmer
0.809
3144356SAPONY
Solar/Wind Harmer
0.264
316274AC1-208 GEN
Solar/Wind Harmer
0.799
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.235
315742AE1-103 GEN
Solar/Wind Harmer
0.736
970657AG2-426 GEN
Solar/Wind Harmer
2.172
970657AG2-426 GEN
Solar/Wind Harmer
0.454
316222AC1-221 GEN
Solar/Wind Harmer
0.698
316065AD1-022 GEN
Solar/Wind Harmer
3.4
942751AE2-291 GEN
Solar/Wind Harmer
4.316
316263AC1-034 GEN
Solar/Wind Harmer
3.148
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.622
316033AB2-134 GEN
Solar/Wind Harmer
2.144
315697AD1-025 GEN
Solar/Wind Harmer
1.345
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.2
316433W1029_GEN2
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316018AA1-139 ULT2
Solar/Wind Harmer
0.563
316017AA1-139 ULT1
Solar/Wind Harmer
0.531
316339AD2-160 GEN
Solar/Wind Harmer
0.443
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.691
3142956BIRDNECK
Solar/Wind Harmer
0.351
316316AC1-027 C
Solar/Wind Harmer
0.201
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.082
3150701DARBY 4
Adder
4.072
3150681DARBY 2
Adder
4.067
3150671DARBY 1
Adder
4.063
966001AG1-469 GEN
Solar/Wind Helper
0.202
972205AH1-687 GEN
50/50
20.91
316303AF2-085
50/50
2.425
971447AH1-217 GEN
Solar/Wind Harmer
15.108
971845AH1-439 GEN
Solar/Wind Harmer
21.634
970285AG2-188 GEN
Solar/Wind Harmer
34.428
270494AE1-108_GEN
Solar/Wind Harmer
9.407
315657AE1-056 GEN
Solar/Wind Harmer
9.233
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
16.612
970681AG2-440 GEN
Solar/Wind Harmer
13.29
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.737
316239AB2-077_GEN
Solar/Wind Harmer
0.427
316238AB2-078_GEN
Solar/Wind Harmer
0.427
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316118AC1-105 GEN
Solar/Wind Harmer
0.741
970831AG2-522 GEN
Solar/Wind Harmer
5.054
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
946281AF1-292 GEN
Solar/Wind Harmer
0.196
971967AH1-528 GEN
Solar/Wind Harmer
16.369
316087AB2-174 GEN
Solar/Wind Harmer
1.222
970865AG2-541 GEN
Solar/Wind Harmer
3.392
3137643SOCKMAN
Solar/Wind Harmer
-0.033
970673AG2-436 GEN
Solar/Wind Harmer
16.777
970673AG2-436 GEN
Solar/Wind Harmer
8.495
315607AA1-063A GEN
Solar/Wind Harmer
0.8
941031AE2-094 GEN
Solar/Wind Harmer
14.78
944011AF1-069 GEN
Solar/Wind Harmer
4.631
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.884
970581AG2-369 GEN
Solar/Wind Harmer
4.201
315814AE2-033 C
Solar/Wind Harmer
7.048
316315AB2-025 C
Solar/Wind Harmer
0.204
965291AG1-394 GEN
Solar/Wind Harmer
0.664
315652AC1-086 GEN
Solar/Wind Harmer
8.34
316123AC1-075 GEN
Solar/Wind Harmer
0.797
970165AG2-112 GEN
Solar/Wind Harmer
0.701
970163AG2-111 GEN
Solar/Wind Harmer
0.669
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.381
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.985
315833AF1-017_GEN
Solar/Wind Harmer
1.293
316349AD2-085 GEN
Solar/Wind Harmer
0.606
316311AC2-079 GEN
Solar/Wind Harmer
3.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.367
315733AD1-074 GEN2
Solar/Wind Harmer
1.367
315735AD1-075 GEN1
Solar/Wind Harmer
0.684
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.68
315816AE2-034 GEN
Solar/Wind Harmer
0.544
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.645
316369SG1_INVT
Solar/Wind Harmer
1.188
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.757
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.895
316321Z2-027
Solar/Wind Harmer
0.178
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
316305AF2-043 C
Solar/Wind Harmer
0.199
313526AB2-022
Solar/Wind Harmer
0.178
316005AA1-067
Solar/Wind Harmer
0.133
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.865
3146406KITTY HAWK
Solar/Wind Harmer
0.005
319010AE1-072 C
Solar/Wind Harmer
1.33
957871AF2-081 GEN
Solar/Wind Harmer
3.284
3152611GOSPORTB
Adder
0.742
3152621GOSPORTC
Adder
0.629
3152601GOSPORTA
Adder
0.581
3151081ELIZAR1
Adder
5.335
3151091ELIZAR2
Adder
5.243
972265AH1-717 GEN
Adder
4.506
3151201GRAVEL4
Adder
4.224
3151191GRAVEL3
Adder
4.17
3151211GRAVEL5
Adder
4.17
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
316458AB2-190 GEN2
Solar/Wind Harmer
0.68
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.303
316359AB2-059 GEN
Solar/Wind Harmer
0.905
316049AB1-081 GEN
Solar/Wind Harmer
0.725
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.951
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
316174AB2-169 GEN
Solar/Wind Harmer
1.029
315800Z1-036_GEN1
Solar/Wind Harmer
1.645
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
971647AH1-324 GEN
Solar/Wind Harmer
3.305
316246AF1-032 C
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.913
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.242
316388AE2-253 GEN
Solar/Wind Harmer
0.443
316375AC2-012 GEN
Solar/Wind Harmer
2.263
3150981CHESPKA
Adder
0.727
3151171GRAVELC
Adder
0.617
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.88
3147666LOUISA
Solar/Wind Helper
0.508
944591AF1-124 GEN
Solar/Wind Harmer
8.419
3151921BEARGRDN G2
50/50
4.287
3144293JTRSVLE
50/50
0.699
970221AG2-151 GEN
Solar/Wind Harmer
28.817
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.807
316258AE1-075 C
Solar/Wind Harmer
0.726
316405AF2-144 C
Solar/Wind Harmer
0.766
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.288
970909AG2-566 GEN
Solar/Wind Harmer
2.372
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.388
963181AG1-167 GEN
Solar/Wind Harmer
2.179
959311AF2-222 GEN
Solar/Wind Harmer
20.632
970257AG2-171 GEN
Solar/Wind Harmer
7.186
315785AD2-033 C
Solar/Wind Harmer
4.155
964241AG1-285 GEN
Solar/Wind Harmer
12.598
316131AB2-060 GEN
Solar/Wind Harmer
1.595
958131AF2-107 GEN
Solar/Wind Harmer
4.893
316478AD1-087 GEN
Solar/Wind Harmer
1.01
316486AD2-202 GEN
Solar/Wind Harmer
0.296
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.904
3150861SPRUNCD
Adder
0.382
971683AH1-343 GEN
Solar/Wind Harmer
3.805
966621AG1-532 GEN
Solar/Wind Harmer
0.177
313506AB2-031 GEN
Solar/Wind Harmer
0.682
970917AG2-570 GEN
Solar/Wind Harmer
19.61
316365GEN2_N
Solar/Wind Harmer
0.518
3156081AA2-088 GEN
Solar/Wind Harmer
2.417
3146263WOODLND
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.773
961681AG1-008 GEN
Solar/Wind Harmer
5.773
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316210AC1-098 GEN
Solar/Wind Harmer
1.142
3146173TUNIS
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
316140AB2-099
Solar/Wind Harmer
0.048
962331AG1-082 GEN
Solar/Wind Harmer
0.898
316317KELFORD C
Solar/Wind Harmer
0.338
3145823KELFORD
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.89
316327AA2-057 GEN
Solar/Wind Harmer
0.714
315813AE1-149 C
Solar/Wind Harmer
4.418
970659AG2-427 GEN
Solar/Wind Harmer
0.658
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
0.4
3145273HOLLAND
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
1.304
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315737AD1-076 GEN
Solar/Wind Harmer
1.285
971157AH1-035 GEN
Solar/Wind Harmer
0.844
970129AG2-093 GEN
Solar/Wind Harmer
3.791
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.725
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.787
961601AG1-000A GEN
Solar/Wind Harmer
2.655
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.827
316320Y1-086
Solar/Wind Harmer
0.387
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.801
961611AG1-000B GEN
Solar/Wind Harmer
1.383
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.404
3151221GRAVEL6
Adder
4.219
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
315616AA1-038_C
Solar/Wind Helper
0.514
LAGNLTFEXP_LAGN->PJM
CLTF
1.764
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.055
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.782
MECLTFEXP_MEC->PJM
CLTF
0.452
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.761
TVALTFEXP_TVA->PJM
CLTF
0.87
SIGELTFEXP_SIGE->PJM
CLTF
0.012
NYPJM->LTFIMP_NY
CLTF
0.577
LGEELTFEXP_LGEE->PJM
CLTF
0.104
WECLTFEXP_WEC->PJM
CLTF
0.046
CPLELTFEXP_CPLE->PJM
CLTF
3.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.641

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:174.94 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1415.27
MW Contribution:28.82
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.588
970535AG2-341 GEN
50/50
2.034
971489AH1-241 GEN
Solar/Wind Harmer
27.358
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.65
970301AG2-198 GEN
Solar/Wind Harmer
12.49
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.631
963191AG1-168 GEN
Solar/Wind Harmer
2.179
971741AH1-377 GEN
Solar/Wind Harmer
26.175
316034AC1-036 C
Solar/Wind Harmer
0.356
970323AG2-213 GEN
Solar/Wind Harmer
9.582
971775AH1-396 GEN
Solar/Wind Harmer
1.365
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.349
3143526WINTERP
Solar/Wind Harmer
-0.065
962561AG1-105 GEN
Solar/Wind Harmer
6.845
939181AE1-148 GEN
Solar/Wind Harmer
6.741
964791AG1-342 GEN
Solar/Wind Harmer
2.511
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.545
970933AG2-581 GEN
Solar/Wind Harmer
9.023
316181AB2-040 GEN
Solar/Wind Harmer
1.184
3151931BEARGRDN S1
50/50
5.533
3151911BEARGRDN G1
50/50
4.287
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
18.19
972003AH1-546 GEN
Solar/Wind Harmer
24.898
971377AH1-170 GEN
Solar/Wind Harmer
5.763
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.282
316322AB2-045
Solar/Wind Harmer
1.394
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.86
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
963171AG1-166 GEN
Solar/Wind Harmer
2.905
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
18.606
3143226MDLTHAN
Solar/Wind Harmer
-0.015
962491AG1-098 GEN
Solar/Wind Harmer
9.894
315693AD1-088 GEN
Solar/Wind Harmer
7.12
316237AB2-079_GEN
Solar/Wind Harmer
0.427
3143526WINTERP
Solar/Wind Harmer
-0.065
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.362
315687AD1-152 GEN
Solar/Wind Harmer
1.282
971065AG2-659 GEN
Solar/Wind Harmer
5.251
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.904
971795AH1-408 GEN
Solar/Wind Harmer
7.449
3150851SPRUNCC
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.906
972205AH1-687 GEN
50/50
20.91
316303AF2-085
50/50
2.425
971447AH1-217 GEN
Solar/Wind Harmer
15.108
971845AH1-439 GEN
Solar/Wind Harmer
21.634
970285AG2-188 GEN
Solar/Wind Harmer
34.428
270494AE1-108_GEN
Solar/Wind Harmer
9.407
315657AE1-056 GEN
Solar/Wind Harmer
9.233
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
16.612
970681AG2-440 GEN
Solar/Wind Harmer
13.29
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.737
316239AB2-077_GEN
Solar/Wind Harmer
0.427
316238AB2-078_GEN
Solar/Wind Harmer
0.427
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316118AC1-105 GEN
Solar/Wind Harmer
0.741
970831AG2-522 GEN
Solar/Wind Harmer
5.054
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
946281AF1-292 GEN
Solar/Wind Harmer
0.196
971967AH1-528 GEN
Solar/Wind Harmer
16.369
316087AB2-174 GEN
Solar/Wind Harmer
1.222
970865AG2-541 GEN
Solar/Wind Harmer
3.392
3137643SOCKMAN
Solar/Wind Harmer
-0.033
970673AG2-436 GEN
Solar/Wind Harmer
16.777
970673AG2-436 GEN
Solar/Wind Harmer
8.495
315607AA1-063A GEN
Solar/Wind Harmer
0.8
941031AE2-094 GEN
Solar/Wind Harmer
14.78
944011AF1-069 GEN
Solar/Wind Harmer
4.631
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.884
970581AG2-369 GEN
Solar/Wind Harmer
4.201
315814AE2-033 C
Solar/Wind Harmer
7.048
316315AB2-025 C
Solar/Wind Harmer
0.204
965291AG1-394 GEN
Solar/Wind Harmer
0.664
315652AC1-086 GEN
Solar/Wind Harmer
8.34
316123AC1-075 GEN
Solar/Wind Harmer
0.797
970165AG2-112 GEN
Solar/Wind Harmer
0.701
970163AG2-111 GEN
Solar/Wind Harmer
0.669
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.381
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.985
315833AF1-017_GEN
Solar/Wind Harmer
1.293
316349AD2-085 GEN
Solar/Wind Harmer
0.606
316311AC2-079 GEN
Solar/Wind Harmer
3.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.367
315733AD1-074 GEN2
Solar/Wind Harmer
1.367
315735AD1-075 GEN1
Solar/Wind Harmer
0.684
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.68
315816AE2-034 GEN
Solar/Wind Harmer
0.544
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.645
316369SG1_INVT
Solar/Wind Harmer
1.188
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.757
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.895
316321Z2-027
Solar/Wind Harmer
0.178
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
316305AF2-043 C
Solar/Wind Harmer
0.199
313526AB2-022
Solar/Wind Harmer
0.178
316005AA1-067
Solar/Wind Harmer
0.133
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.865
3146406KITTY HAWK
Solar/Wind Harmer
0.005
319010AE1-072 C
Solar/Wind Harmer
1.33
957871AF2-081 GEN
Solar/Wind Harmer
3.284
3152611GOSPORTB
Adder
0.742
3152621GOSPORTC
Adder
0.629
3152601GOSPORTA
Adder
0.581
3151081ELIZAR1
Adder
5.335
3151091ELIZAR2
Adder
5.243
972265AH1-717 GEN
Adder
4.506
3151201GRAVEL4
Adder
4.224
3151191GRAVEL3
Adder
4.17
3151211GRAVEL5
Adder
4.17
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
3151921BEARGRDN G2
50/50
4.287
3144293JTRSVLE
50/50
0.699
970221AG2-151 GEN
Solar/Wind Harmer
28.817
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.807
316258AE1-075 C
Solar/Wind Harmer
0.726
316405AF2-144 C
Solar/Wind Harmer
0.766
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.288
970909AG2-566 GEN
Solar/Wind Harmer
2.372
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.388
963181AG1-167 GEN
Solar/Wind Harmer
2.179
959311AF2-222 GEN
Solar/Wind Harmer
20.632
970257AG2-171 GEN
Solar/Wind Harmer
7.186
315785AD2-033 C
Solar/Wind Harmer
4.155
964241AG1-285 GEN
Solar/Wind Harmer
12.598
316131AB2-060 GEN
Solar/Wind Harmer
1.595
958131AF2-107 GEN
Solar/Wind Harmer
4.893
316478AD1-087 GEN
Solar/Wind Harmer
1.01
316486AD2-202 GEN
Solar/Wind Harmer
0.296
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.904
3150861SPRUNCD
Adder
0.382
971683AH1-343 GEN
Solar/Wind Harmer
3.805
966621AG1-532 GEN
Solar/Wind Harmer
0.177
313506AB2-031 GEN
Solar/Wind Harmer
0.682
970917AG2-570 GEN
Solar/Wind Harmer
19.61
316365GEN2_N
Solar/Wind Harmer
0.518
3156081AA2-088 GEN
Solar/Wind Harmer
2.417
3146263WOODLND
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.773
961681AG1-008 GEN
Solar/Wind Harmer
5.773
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316210AC1-098 GEN
Solar/Wind Harmer
1.142
3146173TUNIS
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
316140AB2-099
Solar/Wind Harmer
0.048
962331AG1-082 GEN
Solar/Wind Harmer
0.898
316317KELFORD C
Solar/Wind Harmer
0.338
3145823KELFORD
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.89
316327AA2-057 GEN
Solar/Wind Harmer
0.714
315813AE1-149 C
Solar/Wind Harmer
4.418
970659AG2-427 GEN
Solar/Wind Harmer
0.658
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
0.4
3145273HOLLAND
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
1.304
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315737AD1-076 GEN
Solar/Wind Harmer
1.285
971157AH1-035 GEN
Solar/Wind Harmer
0.844
970129AG2-093 GEN
Solar/Wind Harmer
3.791
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.725
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.787
961601AG1-000A GEN
Solar/Wind Harmer
2.655
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.827
316320Y1-086
Solar/Wind Harmer
0.387
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.801
961611AG1-000B GEN
Solar/Wind Harmer
1.383
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.404
3151221GRAVEL6
Adder
4.219
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
315616AA1-038_C
Solar/Wind Helper
0.514
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.923
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.055
3145783HORNRTN
Solar/Wind Harmer
0.958
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.016
316426AA2-053 GEN
Solar/Wind Harmer
0.809
3144356SAPONY
Solar/Wind Harmer
0.264
316274AC1-208 GEN
Solar/Wind Harmer
0.799
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.235
315742AE1-103 GEN
Solar/Wind Harmer
0.736
970657AG2-426 GEN
Solar/Wind Harmer
2.172
970657AG2-426 GEN
Solar/Wind Harmer
0.454
316222AC1-221 GEN
Solar/Wind Harmer
0.698
316065AD1-022 GEN
Solar/Wind Harmer
3.4
942751AE2-291 GEN
Solar/Wind Harmer
4.316
316263AC1-034 GEN
Solar/Wind Harmer
3.148
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.622
316033AB2-134 GEN
Solar/Wind Harmer
2.144
315697AD1-025 GEN
Solar/Wind Harmer
1.345
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.2
316433W1029_GEN2
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316018AA1-139 ULT2
Solar/Wind Harmer
0.563
316017AA1-139 ULT1
Solar/Wind Harmer
0.531
316339AD2-160 GEN
Solar/Wind Harmer
0.443
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.691
3142956BIRDNECK
Solar/Wind Harmer
0.351
316316AC1-027 C
Solar/Wind Harmer
0.201
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.082
3150701DARBY 4
Adder
4.072
3150681DARBY 2
Adder
4.067
3150671DARBY 1
Adder
4.063
966001AG1-469 GEN
Solar/Wind Helper
0.202
960081AF2-299 GEN
Solar/Wind Harmer
0.983
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
970919AG2-571 GEN
Solar/Wind Harmer
2.482
970087AG2-069 GEN
Solar/Wind Harmer
7.326
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.518
940641AE2-051 GEN
Solar/Wind Harmer
6.973
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.551
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
316212AC1-099_GEN
Solar/Wind Harmer
0.635
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.08
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
5.319
970659AG2-427 GEN
Solar/Wind Harmer
3.71
316381AD1-082 GEN
Solar/Wind Harmer
0.639
315722AD1-056 GEN
Solar/Wind Harmer
0.728
970661AG2-428 GEN
Solar/Wind Harmer
7.356
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
970129AG2-093 GEN
Solar/Wind Harmer
1.536
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316458AB2-190 GEN2
Solar/Wind Harmer
0.68
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.303
316359AB2-059 GEN
Solar/Wind Harmer
0.905
316049AB1-081 GEN
Solar/Wind Harmer
0.725
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.951
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
316174AB2-169 GEN
Solar/Wind Harmer
1.029
315800Z1-036_GEN1
Solar/Wind Harmer
1.645
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
971647AH1-324 GEN
Solar/Wind Harmer
3.305
316246AF1-032 C
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.913
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.242
316388AE2-253 GEN
Solar/Wind Harmer
0.443
316375AC2-012 GEN
Solar/Wind Harmer
2.263
3150981CHESPKA
Adder
0.727
3151171GRAVELC
Adder
0.617
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.88
3147666LOUISA
Solar/Wind Helper
0.508
944591AF1-124 GEN
Solar/Wind Harmer
8.419
LAGNLTFEXP_LAGN->PJM
CLTF
1.764
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.055
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.782
MECLTFEXP_MEC->PJM
CLTF
0.452
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.761
TVALTFEXP_TVA->PJM
CLTF
0.87
SIGELTFEXP_SIGE->PJM
CLTF
0.012
NYPJM->LTFIMP_NY
CLTF
0.577
LGEELTFEXP_LGEE->PJM
CLTF
0.104
WECLTFEXP_WEC->PJM
CLTF
0.046
CPLELTFEXP_CPLE->PJM
CLTF
3.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.641

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:160.44 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:1061.7
MW Contribution:28.5
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
27.249
3151611KERR 4
50/50
0.202
3151621KERR 5
50/50
0.202
3151631KERR 6
50/50
0.202
3151641KERR 7
50/50
0.202
3151541CLOVER2
50/50
2.059
971447AH1-217 GEN
Solar/Wind Harmer
15.037
971845AH1-439 GEN
Solar/Wind Harmer
20.916
970285AG2-188 GEN
Solar/Wind Harmer
35.131
270494AE1-108_GEN
Solar/Wind Harmer
5.032
315657AE1-056 GEN
Solar/Wind Harmer
8.99
946301AF1-294 GEN
Solar/Wind Harmer
4.808
961791AG1-021 GEN
Solar/Wind Harmer
2.339
970683AG2-441 GEN
Solar/Wind Harmer
14.613
970681AG2-440 GEN
Solar/Wind Harmer
11.691
3144303KENBRDG
Solar/Wind Harmer
0.154
971443AH1-215 GEN
Solar/Wind Harmer
3.209
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.244
3147173SINAI
Solar/Wind Harmer
0.084
3147243WELCO
Solar/Wind Harmer
0.052
970831AG2-522 GEN
Solar/Wind Harmer
3.381
970865AG2-541 GEN
Solar/Wind Harmer
2.545
316123AC1-075 GEN
Solar/Wind Harmer
0.091
970165AG2-112 GEN
Solar/Wind Harmer
0.539
970163AG2-111 GEN
Solar/Wind Harmer
0.514
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
3144293JTRSVLE
50/50
0.823
3144293JTRSVLE
50/50
0.693
970535AG2-341 GEN
50/50
2.047
3152661PLYWOOD A
50/50
0.202
971489AH1-241 GEN
Solar/Wind Harmer
28.504
3146776BUCKING
Solar/Wind Harmer
1.881
3146776BUCKING
Solar/Wind Harmer
0.152
315821AE2-092 GEN
Solar/Wind Harmer
0.02
970301AG2-198 GEN
Solar/Wind Harmer
11.214
3147133PAMPLIN
Solar/Wind Harmer
0.26
3147133PAMPLIN
Solar/Wind Harmer
0.208
958211AF2-115 GEN
Solar/Wind Harmer
2.924
963191AG1-168 GEN
Solar/Wind Harmer
0.975
971741AH1-377 GEN
Solar/Wind Harmer
22.982
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.246
971775AH1-396 GEN
Solar/Wind Harmer
0.309
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
5.277
964791AG1-342 GEN
Solar/Wind Harmer
2.024
3146843MT LREL
Solar/Wind Harmer
0.105
3146843MT LREL
Solar/Wind Harmer
0.105
939181AE1-148 GEN
Solar/Wind Harmer
5.007
970099AG2-077 GEN
Solar/Wind Harmer
9.999
970933AG2-581 GEN
Solar/Wind Harmer
5.154
942751AE2-291 GEN
Solar/Wind Harmer
3.374
966001AG1-469 GEN
Solar/Wind Helper
0.159
3151921BEARGRDN G2
50/50
5.587
3144293JTRSVLE
50/50
0.823
3151591KERR 2
50/50
0.202
970413AG2-270 GEN
50/50
9.029
966251AG1-494 GEN
50/50
1.716
970221AG2-151 GEN
Solar/Wind Harmer
28.504
3146776BUCKING
Solar/Wind Harmer
0.169
3146926FARMVIL
Solar/Wind Harmer
0.218
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
970909AG2-566 GEN
Solar/Wind Harmer
2.804
3147133PAMPLIN
Solar/Wind Harmer
0.818
971193AH1-056 GEN
Solar/Wind Harmer
15.872
963181AG1-167 GEN
Solar/Wind Harmer
0.975
959311AF2-222 GEN
Solar/Wind Harmer
17.841
970257AG2-171 GEN
Solar/Wind Harmer
6.184
315785AD2-033 C
Solar/Wind Harmer
1.488
958131AF2-107 GEN
Solar/Wind Harmer
4.835
964241AG1-285 GEN
Solar/Wind Harmer
10.382
316131AB2-060 GEN
Solar/Wind Harmer
0.438
316478AD1-087 GEN
Solar/Wind Harmer
0.337
316486AD2-202 GEN
Solar/Wind Harmer
0.099
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.582
3147043LAWRENC
Solar/Wind Harmer
0.049
971683AH1-343 GEN
Solar/Wind Harmer
2.828
3132273ORANGE
Solar/Wind Helper
0.023
3151931BEARGRDN S1
50/50
7.21
3151911BEARGRDN G1
50/50
5.587
3144293JTRSVLE
50/50
0.823
3151601KERR 3
50/50
0.202
3151581KERR 1
50/50
0.072
3151531CLOVER1
50/50
2.069
3147043LAWRENC
50/50
0.777
970937AG2-583 GEN
Solar/Wind Harmer
36.866
316336AC2-165 C
Solar/Wind Harmer
0.024
972003AH1-546 GEN
Solar/Wind Harmer
24.522
971377AH1-170 GEN
Solar/Wind Harmer
5.701
3147623JAMES R
Solar/Wind Harmer
1.238
316322AB2-045
Solar/Wind Harmer
0.004
3146776BUCKING
Solar/Wind Harmer
0.188
3146926FARMVIL
Solar/Wind Harmer
0.218
963171AG1-166 GEN
Solar/Wind Harmer
1.299
971563AH1-280 GEN
Solar/Wind Harmer
2.599
970685AG2-442 GEN
Solar/Wind Harmer
16.367
962491AG1-098 GEN
Solar/Wind Harmer
7.651
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
6.098
970401AG2-262 GEN
Solar/Wind Harmer
0.618
957481AF2-042 GEN
Solar/Wind Harmer
24.997
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.611
316129AC1-054 GEN
Solar/Wind Harmer
0.309
316003AC1-222 GEN
Solar/Wind Harmer
0.002
971795AH1-408 GEN
Solar/Wind Harmer
4.899
962751AG1-124 GEN
Solar/Wind Harmer
3.147
960081AF2-299 GEN
Solar/Wind Harmer
0.55
LAGNLTFEXP_LAGN->PJM
CLTF
1.554
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.084
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.539
MECLTFEXP_MEC->PJM
CLTF
0.508
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.128
TVALTFEXP_TVA->PJM
CLTF
0.776
NYPJM->LTFIMP_NY
CLTF
0.525
LGEELTFEXP_LGEE->PJM
CLTF
0.153
WECLTFEXP_WEC->PJM
CLTF
0.071
CPLELTFEXP_CPLE->PJM
CLTF
2.979
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.201

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 242T2027_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 242T2027_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:152.15 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1230.87
MW Contribution:37.53
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
27.249
971447AH1-217 GEN
Solar/Wind Harmer
19.799
971845AH1-439 GEN
Solar/Wind Harmer
27.54
970285AG2-188 GEN
Solar/Wind Harmer
43.657
270494AE1-108_GEN
Solar/Wind Harmer
12.267
315657AE1-056 GEN
Solar/Wind Harmer
10.983
946301AF1-294 GEN
Solar/Wind Harmer
7.014
961791AG1-021 GEN
Solar/Wind Harmer
3.422
970683AG2-441 GEN
Solar/Wind Harmer
19.241
970681AG2-440 GEN
Solar/Wind Harmer
15.393
3144303KENBRDG
Solar/Wind Harmer
-0.017
971443AH1-215 GEN
Solar/Wind Harmer
4.225
316239AB2-077_GEN
Solar/Wind Harmer
0.446
316238AB2-078_GEN
Solar/Wind Harmer
0.446
316118AC1-105 GEN
Solar/Wind Harmer
0.73
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
970831AG2-522 GEN
Solar/Wind Harmer
4.452
970865AG2-541 GEN
Solar/Wind Harmer
3.351
316123AC1-075 GEN
Solar/Wind Harmer
0.806
970165AG2-112 GEN
Solar/Wind Harmer
0.709
970163AG2-111 GEN
Solar/Wind Harmer
0.677
946281AF1-292 GEN
Solar/Wind Harmer
0.144
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
3151931BEARGRDN S1
50/50
7.21
3151911BEARGRDN G1
50/50
5.587
3144293JTRSVLE
50/50
0.823
970937AG2-583 GEN
Solar/Wind Harmer
48.541
316336AC2-165 C
Solar/Wind Harmer
11.736
972003AH1-546 GEN
Solar/Wind Harmer
32.342
971377AH1-170 GEN
Solar/Wind Harmer
7.506
3147623JAMES R
Solar/Wind Harmer
0.929
316322AB2-045
Solar/Wind Harmer
1.778
3146776BUCKING
Solar/Wind Harmer
-0.021
3146926FARMVIL
Solar/Wind Harmer
-0.024
963171AG1-166 GEN
Solar/Wind Harmer
3.422
971563AH1-280 GEN
Solar/Wind Harmer
3.422
970685AG2-442 GEN
Solar/Wind Harmer
21.55
962491AG1-098 GEN
Solar/Wind Harmer
10.074
316237AB2-079_GEN
Solar/Wind Harmer
0.446
315693AD1-088 GEN
Solar/Wind Harmer
7.137
970401AG2-262 GEN
Solar/Wind Harmer
0.773
957481AF2-042 GEN
Solar/Wind Harmer
32.913
315687AD1-152 GEN
Solar/Wind Harmer
1.189
971065AG2-659 GEN
Solar/Wind Harmer
4.755
316129AC1-054 GEN
Solar/Wind Harmer
0.808
3147043LAWRENC
Adder
0.732
316003AC1-222 GEN
Solar/Wind Harmer
0.879
971795AH1-408 GEN
Solar/Wind Harmer
6.192
962751AG1-124 GEN
Solar/Wind Harmer
4.595
960081AF2-299 GEN
Solar/Wind Harmer
0.724
3151921BEARGRDN G2
50/50
5.587
3144293JTRSVLE
50/50
0.823
970221AG2-151 GEN
Solar/Wind Harmer
37.53
3146776BUCKING
Solar/Wind Harmer
-0.019
3146926FARMVIL
Solar/Wind Harmer
-0.024
942461AE2-259 GEN
Solar/Wind Harmer
5.218
970909AG2-566 GEN
Solar/Wind Harmer
2.804
3147133PAMPLIN
Solar/Wind Harmer
-0.092
971193AH1-056 GEN
Solar/Wind Harmer
18.305
963181AG1-167 GEN
Solar/Wind Harmer
2.566
959311AF2-222 GEN
Solar/Wind Harmer
23.538
970257AG2-171 GEN
Solar/Wind Harmer
8.143
315785AD2-033 C
Solar/Wind Harmer
4.66
958131AF2-107 GEN
Solar/Wind Harmer
6.437
964241AG1-285 GEN
Solar/Wind Harmer
13.669
316131AB2-060 GEN
Solar/Wind Harmer
1.687
316478AD1-087 GEN
Solar/Wind Harmer
0.939
316486AD2-202 GEN
Solar/Wind Harmer
0.275
316248AF1-058 C
Solar/Wind Harmer
0.284
960061AF2-297 GEN
Solar/Wind Harmer
4.717
3147043LAWRENC
Solar/Wind Harmer
-0.005
971683AH1-343 GEN
Solar/Wind Harmer
3.724
966621AG1-532 GEN
Solar/Wind Harmer
0.131
3132273ORANGE
Solar/Wind Helper
0.023
3144293JTRSVLE
50/50
0.823
3144293JTRSVLE
50/50
0.693
970535AG2-341 GEN
50/50
2.047
971489AH1-241 GEN
Solar/Wind Harmer
35.629
3146776BUCKING
Solar/Wind Harmer
-0.21
3146776BUCKING
Solar/Wind Harmer
-0.017
315821AE2-092 GEN
Solar/Wind Harmer
7.77
970301AG2-198 GEN
Solar/Wind Harmer
14.765
3147133PAMPLIN
Solar/Wind Harmer
-0.029
3147133PAMPLIN
Solar/Wind Harmer
-0.023
958211AF2-115 GEN
Solar/Wind Harmer
4.277
963191AG1-168 GEN
Solar/Wind Harmer
2.566
971741AH1-377 GEN
Solar/Wind Harmer
30.26
316034AC1-036 C
Solar/Wind Harmer
0.404
970323AG2-213 GEN
Solar/Wind Harmer
10.857
971775AH1-396 GEN
Solar/Wind Harmer
1.546
313527AB2-043 GEN
Solar/Wind Harmer
2.466
962561AG1-105 GEN
Solar/Wind Harmer
6.948
964791AG1-342 GEN
Solar/Wind Harmer
2.529
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
939181AE1-148 GEN
Solar/Wind Harmer
6.592
970099AG2-077 GEN
Solar/Wind Harmer
13.165
970933AG2-581 GEN
Solar/Wind Harmer
6.786
942751AE2-291 GEN
Solar/Wind Harmer
4.443
966001AG1-469 GEN
Solar/Wind Helper
0.159
LAGNLTFEXP_LAGN->PJM
CLTF
1.554
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.084
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.539
MECLTFEXP_MEC->PJM
CLTF
0.508
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.128
TVALTFEXP_TVA->PJM
CLTF
0.776
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.525
LGEELTFEXP_LGEE->PJM
CLTF
0.153
WECLTFEXP_WEC->PJM
CLTF
0.071
CPLELTFEXP_CPLE->PJM
CLTF
2.979
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.201

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 39-91_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 39-91_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:117.53 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:950.8
MW Contribution:32.43
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
21.692
971447AH1-217 GEN
Solar/Wind Harmer
18.622
971845AH1-439 GEN
Solar/Wind Harmer
22.237
270494AE1-108_GEN
Solar/Wind Harmer
10.551
970285AG2-188 GEN
Solar/Wind Harmer
35.335
315657AE1-056 GEN
Solar/Wind Harmer
9.243
946301AF1-294 GEN
Solar/Wind Harmer
5.939
961791AG1-021 GEN
Solar/Wind Harmer
2.897
970683AG2-441 GEN
Solar/Wind Harmer
16.461
970681AG2-440 GEN
Solar/Wind Harmer
13.169
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.67
316239AB2-077_GEN
Solar/Wind Harmer
0.407
316238AB2-078_GEN
Solar/Wind Harmer
0.407
316118AC1-105 GEN
Solar/Wind Harmer
0.689
970831AG2-522 GEN
Solar/Wind Harmer
4.571
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
316233AE1-074 FULL
Solar/Wind Harmer
0.238
971281AH1-106 GEN
Solar/Wind Harmer
1.438
971283AH1-107 GEN
Solar/Wind Harmer
1.438
970865AG2-541 GEN
Solar/Wind Harmer
3.115
946281AF1-292 GEN
Solar/Wind Harmer
0.169
316087AB2-174 GEN
Solar/Wind Harmer
1.055
971967AH1-528 GEN
Solar/Wind Harmer
13.769
3137643SOCKMAN
Solar/Wind Harmer
-0.029
316123AC1-075 GEN
Solar/Wind Harmer
0.731
970165AG2-112 GEN
Solar/Wind Harmer
0.643
970163AG2-111 GEN
Solar/Wind Harmer
0.614
315607AA1-063A GEN
Solar/Wind Harmer
0.681
971285AH1-108 GEN
Adder
0.449
3146043SEABORD
Solar/Wind Harmer
-0.007
970673AG2-436 GEN
Solar/Wind Harmer
13.72
3151921BEARGRDN G2
50/50
4.448
3144293JTRSVLE
50/50
0.697
970221AG2-151 GEN
Solar/Wind Harmer
32.428
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
942461AE2-259 GEN
Solar/Wind Harmer
4.331
316313AB2-026
Solar/Wind Harmer
0.751
316258AE1-075 C
Solar/Wind Harmer
0.676
316405AF2-144 C
Solar/Wind Harmer
0.713
3143336POWHATN
Solar/Wind Harmer
2.809
970909AG2-566 GEN
Solar/Wind Harmer
2.37
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.405
963181AG1-167 GEN
Solar/Wind Harmer
2.173
3144293JTRSVLE
50/50
0.697
3144293JTRSVLE
50/50
0.587
971489AH1-241 GEN
Solar/Wind Harmer
30.786
3146776BUCKING
Solar/Wind Harmer
-0.17
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.481
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.621
963191AG1-168 GEN
Solar/Wind Harmer
2.173
971741AH1-377 GEN
Solar/Wind Harmer
25.942
316034AC1-036 C
Solar/Wind Harmer
0.35
959311AF2-222 GEN
Solar/Wind Harmer
20.328
970257AG2-171 GEN
Solar/Wind Harmer
7.062
315785AD2-033 C
Solar/Wind Harmer
4.068
958131AF2-107 GEN
Solar/Wind Harmer
5.359
964241AG1-285 GEN
Solar/Wind Harmer
12.184
316131AB2-060 GEN
Solar/Wind Harmer
1.528
316478AD1-087 GEN
Solar/Wind Harmer
0.928
316486AD2-202 GEN
Solar/Wind Harmer
0.272
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.272
960061AF2-297 GEN
Solar/Wind Harmer
4.511
971683AH1-343 GEN
Solar/Wind Harmer
3.497
966621AG1-532 GEN
Solar/Wind Harmer
0.153
313506AB2-031 GEN
Solar/Wind Harmer
0.589
3150861SPRUNCD
Adder
0.274
970917AG2-570 GEN
Solar/Wind Harmer
16.228
316365GEN2_N
Solar/Wind Harmer
0.43
3148013FISHERV
Solar/Wind Helper
0.221
316499AE2-029_GEN
Solar/Wind Helper
0.571
315616AA1-038_C
Solar/Wind Helper
0.608
3132273ORANGE
Solar/Wind Helper
0.026
3151931BEARGRDN S1
50/50
5.74
3151911BEARGRDN G1
50/50
4.448
3144293JTRSVLE
50/50
0.697
971377AH1-170 GEN
Solar/Wind Harmer
6.486
3147623JAMES R
Solar/Wind Harmer
0.803
972003AH1-546 GEN
Solar/Wind Harmer
25.797
970937AG2-583 GEN
Solar/Wind Harmer
31.587
316322AB2-045
Solar/Wind Harmer
1.434
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.02
316336AC2-165 C
Solar/Wind Harmer
5.623
3143336POWHATN
Solar/Wind Harmer
3.304
963171AG1-166 GEN
Solar/Wind Harmer
2.897
971563AH1-280 GEN
Solar/Wind Harmer
2.897
970685AG2-442 GEN
Solar/Wind Harmer
18.436
962491AG1-098 GEN
Solar/Wind Harmer
9.378
316237AB2-079_GEN
Solar/Wind Harmer
0.407
315693AD1-088 GEN
Solar/Wind Harmer
6.713
970401AG2-262 GEN
Solar/Wind Harmer
0.72
957481AF2-042 GEN
Solar/Wind Harmer
33.181
3143226MDLTHAN
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
1.173
971065AG2-659 GEN
Solar/Wind Harmer
4.785
3147043LAWRENC
Adder
0.762
316129AC1-054 GEN
Solar/Wind Harmer
0.821
971795AH1-408 GEN
Solar/Wind Harmer
6.648
3143526WINTERP
Solar/Wind Harmer
-0.046
316003AC1-222 GEN
Solar/Wind Harmer
0.833
960081AF2-299 GEN
Solar/Wind Harmer
0.851
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.084
3150851SPRUNCC
Adder
0.274
970919AG2-571 GEN
Solar/Wind Harmer
2.054
970087AG2-069 GEN
Solar/Wind Harmer
6.064
316023GEN1_S
Solar/Wind Harmer
0.43
3147983MERCK5
Solar/Wind Helper
0.062
970673AG2-436 GEN
Solar/Wind Harmer
6.947
970085AG2-068 GEN
Solar/Wind Harmer
4.042
970581AG2-369 GEN
Solar/Wind Harmer
3.477
941031AE2-094 GEN
Solar/Wind Harmer
11.972
944011AF1-069 GEN
Solar/Wind Harmer
3.751
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.132
3148013FISHERV
Solar/Wind Helper
0.127
3148463FAIRFLD
Solar/Wind Helper
0.134
970323AG2-213 GEN
Solar/Wind Harmer
9.416
971775AH1-396 GEN
Solar/Wind Harmer
1.341
313527AB2-043 GEN
Solar/Wind Harmer
2.245
962561AG1-105 GEN
Solar/Wind Harmer
6.444
939181AE1-148 GEN
Solar/Wind Harmer
6.287
964791AG1-342 GEN
Solar/Wind Harmer
2.356
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.272
971223AH1-071 GEN
Solar/Wind Harmer
1.326
3143526WINTERP
Solar/Wind Harmer
-0.046
970933AG2-581 GEN
Solar/Wind Harmer
7.828
316181AB2-040 GEN
Solar/Wind Harmer
1.022
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.794
3145593CAROLNA
Solar/Wind Harmer
0.059
3145783HORNRTN
Solar/Wind Harmer
0.823
3145783HORNRTN
Solar/Wind Harmer
0.658
3145783HORNRTN
Solar/Wind Harmer
0.206
3145783HORNRTN
Solar/Wind Harmer
0.082
316426AA2-053 GEN
Solar/Wind Harmer
0.692
972187AH1-678 GEN
Adder
1.699
972185AH1-677 GEN
Adder
3.299
966001AG1-469 GEN
Solar/Wind Helper
0.187
3132123MT JACKSON
Solar/Wind Helper
0.368
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.035
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.087
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.798
MECLTFEXP_MEC->PJM
CLTF
0.142
LAGNLTFEXP_LAGN->PJM
CLTF
1.208
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.305
TVALTFEXP_TVA->PJM
CLTF
0.589
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CPLELTFEXP_CPLE->PJM
CLTF
3.247
NYPJM->LTFIMP_NY
CLTF
0.409
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.539

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P2-2: DOOMS B2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: DOOMS B2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:115.53 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:934.63
MW Contribution:32.4
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.444
972205AH1-687 GEN
50/50
21.676
971447AH1-217 GEN
Solar/Wind Harmer
18.608
971845AH1-439 GEN
Solar/Wind Harmer
22.218
270494AE1-108_GEN
Solar/Wind Harmer
10.541
970285AG2-188 GEN
Solar/Wind Harmer
35.303
315657AE1-056 GEN
Solar/Wind Harmer
9.23
946301AF1-294 GEN
Solar/Wind Harmer
5.931
961791AG1-021 GEN
Solar/Wind Harmer
2.893
970683AG2-441 GEN
Solar/Wind Harmer
16.436
970681AG2-440 GEN
Solar/Wind Harmer
13.149
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.664
316239AB2-077_GEN
Solar/Wind Harmer
0.406
316238AB2-078_GEN
Solar/Wind Harmer
0.406
316118AC1-105 GEN
Solar/Wind Harmer
0.687
970831AG2-522 GEN
Solar/Wind Harmer
4.556
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
316233AE1-074 FULL
Solar/Wind Harmer
0.237
971281AH1-106 GEN
Solar/Wind Harmer
1.433
971283AH1-107 GEN
Solar/Wind Harmer
1.433
970865AG2-541 GEN
Solar/Wind Harmer
3.104
946281AF1-292 GEN
Solar/Wind Harmer
0.169
316087AB2-174 GEN
Solar/Wind Harmer
1.051
971967AH1-528 GEN
Solar/Wind Harmer
13.715
3137643SOCKMAN
Solar/Wind Harmer
-0.028
316123AC1-075 GEN
Solar/Wind Harmer
0.728
970165AG2-112 GEN
Solar/Wind Harmer
0.641
970163AG2-111 GEN
Solar/Wind Harmer
0.611
315607AA1-063A GEN
Solar/Wind Harmer
0.678
971285AH1-108 GEN
Adder
0.447
3146043SEABORD
Solar/Wind Harmer
-0.007
970673AG2-436 GEN
Solar/Wind Harmer
13.659
970673AG2-436 GEN
Solar/Wind Harmer
6.916
970085AG2-068 GEN
Solar/Wind Harmer
4.024
970581AG2-369 GEN
Solar/Wind Harmer
3.461
941031AE2-094 GEN
Solar/Wind Harmer
11.918
944011AF1-069 GEN
Solar/Wind Harmer
3.734
3138266HYDRAULIC
Solar/Wind Helper
0.021
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.136
3148013FISHERV
Solar/Wind Helper
0.13
3148463FAIRFLD
Solar/Wind Helper
0.135
3151931BEARGRDN S1
50/50
5.736
3151911BEARGRDN G1
50/50
4.444
3144293JTRSVLE
50/50
0.696
971377AH1-170 GEN
Solar/Wind Harmer
6.481
3147623JAMES R
Solar/Wind Harmer
0.802
972003AH1-546 GEN
Solar/Wind Harmer
25.777
970937AG2-583 GEN
Solar/Wind Harmer
31.56
316322AB2-045
Solar/Wind Harmer
1.433
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.02
316336AC2-165 C
Solar/Wind Harmer
5.617
3143336POWHATN
Solar/Wind Harmer
3.3
963171AG1-166 GEN
Solar/Wind Harmer
2.893
971563AH1-280 GEN
Solar/Wind Harmer
2.893
970685AG2-442 GEN
Solar/Wind Harmer
18.409
962491AG1-098 GEN
Solar/Wind Harmer
9.357
316237AB2-079_GEN
Solar/Wind Harmer
0.406
315693AD1-088 GEN
Solar/Wind Harmer
6.698
970401AG2-262 GEN
Solar/Wind Harmer
0.718
957481AF2-042 GEN
Solar/Wind Harmer
33.088
3143226MDLTHAN
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
1.169
971065AG2-659 GEN
Solar/Wind Harmer
4.77
3147043LAWRENC
Adder
0.76
316129AC1-054 GEN
Solar/Wind Harmer
0.818
971795AH1-408 GEN
Solar/Wind Harmer
6.626
3143526WINTERP
Solar/Wind Harmer
-0.046
316003AC1-222 GEN
Solar/Wind Harmer
0.83
960081AF2-299 GEN
Solar/Wind Harmer
0.847
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.084
3150851SPRUNCC
Adder
0.273
970919AG2-571 GEN
Solar/Wind Harmer
2.045
970087AG2-069 GEN
Solar/Wind Harmer
6.037
316023GEN1_S
Solar/Wind Harmer
0.428
3147983MERCK5
Solar/Wind Helper
0.063
3144293JTRSVLE
50/50
0.696
970221AG2-151 GEN
Solar/Wind Harmer
32.404
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
942461AE2-259 GEN
Solar/Wind Harmer
4.326
316313AB2-026
Solar/Wind Harmer
0.75
316258AE1-075 C
Solar/Wind Harmer
0.675
316405AF2-144 C
Solar/Wind Harmer
0.712
3143336POWHATN
Solar/Wind Harmer
2.805
970909AG2-566 GEN
Solar/Wind Harmer
2.367
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.384
963181AG1-167 GEN
Solar/Wind Harmer
2.17
959311AF2-222 GEN
Solar/Wind Harmer
20.295
970257AG2-171 GEN
Solar/Wind Harmer
7.05
315785AD2-033 C
Solar/Wind Harmer
4.061
958131AF2-107 GEN
Solar/Wind Harmer
5.349
964241AG1-285 GEN
Solar/Wind Harmer
12.16
316131AB2-060 GEN
Solar/Wind Harmer
1.525
316478AD1-087 GEN
Solar/Wind Harmer
0.925
316486AD2-202 GEN
Solar/Wind Harmer
0.271
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.271
960061AF2-297 GEN
Solar/Wind Harmer
4.496
971683AH1-343 GEN
Solar/Wind Harmer
3.484
966621AG1-532 GEN
Solar/Wind Harmer
0.153
313506AB2-031 GEN
Solar/Wind Harmer
0.586
3150861SPRUNCD
Adder
0.273
970917AG2-570 GEN
Solar/Wind Harmer
16.156
316365GEN2_N
Solar/Wind Harmer
0.428
3148013FISHERV
Solar/Wind Helper
0.227
316499AE2-029_GEN
Solar/Wind Helper
0.572
315616AA1-038_C
Solar/Wind Helper
0.611
3132273ORANGE
Solar/Wind Helper
0.026
3144293JTRSVLE
50/50
0.696
3144293JTRSVLE
50/50
0.586
315821AE2-092 GEN
Solar/Wind Harmer
10.863
971489AH1-241 GEN
Solar/Wind Harmer
30.763
3146776BUCKING
Solar/Wind Harmer
-0.17
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.465
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.616
963191AG1-168 GEN
Solar/Wind Harmer
2.17
971741AH1-377 GEN
Solar/Wind Harmer
25.905
316034AC1-036 C
Solar/Wind Harmer
0.349
970323AG2-213 GEN
Solar/Wind Harmer
9.401
971775AH1-396 GEN
Solar/Wind Harmer
1.339
313527AB2-043 GEN
Solar/Wind Harmer
2.24
962561AG1-105 GEN
Solar/Wind Harmer
6.427
939181AE1-148 GEN
Solar/Wind Harmer
6.27
964791AG1-342 GEN
Solar/Wind Harmer
2.35
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.235
971223AH1-071 GEN
Solar/Wind Harmer
1.322
3143526WINTERP
Solar/Wind Harmer
-0.046
970933AG2-581 GEN
Solar/Wind Harmer
7.8
316181AB2-040 GEN
Solar/Wind Harmer
1.018
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.791
3145593CAROLNA
Solar/Wind Harmer
0.058
3145783HORNRTN
Solar/Wind Harmer
0.819
3145783HORNRTN
Solar/Wind Harmer
0.655
3145783HORNRTN
Solar/Wind Harmer
0.205
3145783HORNRTN
Solar/Wind Harmer
0.082
316426AA2-053 GEN
Solar/Wind Harmer
0.689
972187AH1-678 GEN
Adder
1.691
972185AH1-677 GEN
Adder
3.285
966001AG1-469 GEN
Solar/Wind Helper
0.188
3132123MT JACKSON
Solar/Wind Helper
0.367
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.046
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.122
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.731
MECLTFEXP_MEC->PJM
CLTF
0.113
LAGNLTFEXP_LAGN->PJM
CLTF
1.172
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.249
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.571
SIGELTFEXP_SIGE->PJM
CLTF
0.001
CPLELTFEXP_CPLE->PJM
CLTF
3.227
NYPJM->LTFIMP_NY
CLTF
0.42
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.302

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:110.52 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:894.11
MW Contribution:27.74
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.143
971447AH1-217 GEN
Solar/Wind Harmer
14.529
971845AH1-439 GEN
Solar/Wind Harmer
20.7
970285AG2-188 GEN
Solar/Wind Harmer
32.906
270494AE1-108_GEN
Solar/Wind Harmer
9.015
315657AE1-056 GEN
Solar/Wind Harmer
8.675
946301AF1-294 GEN
Solar/Wind Harmer
5.582
961791AG1-021 GEN
Solar/Wind Harmer
2.723
970683AG2-441 GEN
Solar/Wind Harmer
15.505
970681AG2-440 GEN
Solar/Wind Harmer
12.404
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.467
316239AB2-077_GEN
Solar/Wind Harmer
0.389
316238AB2-078_GEN
Solar/Wind Harmer
0.389
316118AC1-105 GEN
Solar/Wind Harmer
0.665
970831AG2-522 GEN
Solar/Wind Harmer
4.449
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
316233AE1-074 FULL
Solar/Wind Harmer
0.225
971281AH1-106 GEN
Solar/Wind Harmer
1.359
971283AH1-107 GEN
Solar/Wind Harmer
1.359
946281AF1-292 GEN
Solar/Wind Harmer
0.166
970865AG2-541 GEN
Solar/Wind Harmer
2.988
316087AB2-174 GEN
Solar/Wind Harmer
1.035
971967AH1-528 GEN
Solar/Wind Harmer
13.383
3137643SOCKMAN
Solar/Wind Harmer
-0.028
315607AA1-063A GEN
Solar/Wind Harmer
0.672
3146043SEABORD
Solar/Wind Harmer
-0.007
316123AC1-075 GEN
Solar/Wind Harmer
0.694
970165AG2-112 GEN
Solar/Wind Harmer
0.611
970163AG2-111 GEN
Solar/Wind Harmer
0.583
970085AG2-068 GEN
Solar/Wind Harmer
4
970581AG2-369 GEN
Solar/Wind Harmer
3.44
970673AG2-436 GEN
Solar/Wind Harmer
13.415
970673AG2-436 GEN
Solar/Wind Harmer
6.792
971285AH1-108 GEN
Adder
0.428
3138266HYDRAULIC
Solar/Wind Helper
0.021
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.08
3148013FISHERV
Solar/Wind Helper
0.077
3148463FAIRFLD
Solar/Wind Helper
0.12
3151931BEARGRDN S1
50/50
5.33
3151911BEARGRDN G1
50/50
4.13
3144293JTRSVLE
50/50
0.655
972003AH1-546 GEN
Solar/Wind Harmer
23.962
971377AH1-170 GEN
Solar/Wind Harmer
5.548
3147623JAMES R
Solar/Wind Harmer
0.687
970937AG2-583 GEN
Solar/Wind Harmer
29.352
316322AB2-045
Solar/Wind Harmer
1.334
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.233
3143336POWHATN
Solar/Wind Harmer
3.078
963171AG1-166 GEN
Solar/Wind Harmer
2.723
971563AH1-280 GEN
Solar/Wind Harmer
2.723
970685AG2-442 GEN
Solar/Wind Harmer
17.365
962491AG1-098 GEN
Solar/Wind Harmer
8.919
316237AB2-079_GEN
Solar/Wind Harmer
0.389
315693AD1-088 GEN
Solar/Wind Harmer
6.394
970401AG2-262 GEN
Solar/Wind Harmer
0.692
957481AF2-042 GEN
Solar/Wind Harmer
31.87
3143226MDLTHAN
Solar/Wind Harmer
-0.01
315687AD1-152 GEN
Solar/Wind Harmer
1.137
971065AG2-659 GEN
Solar/Wind Harmer
4.648
3147043LAWRENC
Adder
0.737
316129AC1-054 GEN
Solar/Wind Harmer
0.798
971795AH1-408 GEN
Solar/Wind Harmer
6.453
3143526WINTERP
Solar/Wind Harmer
-0.043
316003AC1-222 GEN
Solar/Wind Harmer
0.805
960081AF2-299 GEN
Solar/Wind Harmer
0.832
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.083
970919AG2-571 GEN
Solar/Wind Harmer
2.03
970087AG2-069 GEN
Solar/Wind Harmer
6
3150851SPRUNCC
Adder
0.261
3147983MERCK5
Solar/Wind Helper
0.055
3151921BEARGRDN G2
50/50
4.13
3144293JTRSVLE
50/50
0.655
970221AG2-151 GEN
Solar/Wind Harmer
27.742
3146776BUCKING
Solar/Wind Harmer
-0.014
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.053
316313AB2-026
Solar/Wind Harmer
0.699
316258AE1-075 C
Solar/Wind Harmer
0.63
316405AF2-144 C
Solar/Wind Harmer
0.664
3143336POWHATN
Solar/Wind Harmer
2.616
970909AG2-566 GEN
Solar/Wind Harmer
2.223
3147133PAMPLIN
Solar/Wind Harmer
-0.072
971193AH1-056 GEN
Solar/Wind Harmer
14.459
963181AG1-167 GEN
Solar/Wind Harmer
2.042
959311AF2-222 GEN
Solar/Wind Harmer
19.185
970257AG2-171 GEN
Solar/Wind Harmer
6.671
315785AD2-033 C
Solar/Wind Harmer
3.847
964241AG1-285 GEN
Solar/Wind Harmer
11.573
316131AB2-060 GEN
Solar/Wind Harmer
1.457
958131AF2-107 GEN
Solar/Wind Harmer
4.54
316478AD1-087 GEN
Solar/Wind Harmer
0.893
316486AD2-202 GEN
Solar/Wind Harmer
0.261
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.264
960061AF2-297 GEN
Solar/Wind Harmer
4.376
971683AH1-343 GEN
Solar/Wind Harmer
3.368
966621AG1-532 GEN
Solar/Wind Harmer
0.15
313506AB2-031 GEN
Solar/Wind Harmer
0.578
970917AG2-570 GEN
Solar/Wind Harmer
16.041
3150861SPRUNCD
Adder
0.261
316499AE2-029_GEN
Solar/Wind Helper
0.505
3148013FISHERV
Solar/Wind Helper
0.133
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.545
3144293JTRSVLE
50/50
0.655
3144293JTRSVLE
50/50
0.551
971489AH1-241 GEN
Solar/Wind Harmer
26.337
3146776BUCKING
Solar/Wind Harmer
-0.158
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.386
970301AG2-198 GEN
Solar/Wind Harmer
11.705
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.404
963191AG1-168 GEN
Solar/Wind Harmer
2.042
971741AH1-377 GEN
Solar/Wind Harmer
24.381
316034AC1-036 C
Solar/Wind Harmer
0.331
970323AG2-213 GEN
Solar/Wind Harmer
8.895
971775AH1-396 GEN
Solar/Wind Harmer
1.267
313527AB2-043 GEN
Solar/Wind Harmer
2.141
962561AG1-105 GEN
Solar/Wind Harmer
6.187
939181AE1-148 GEN
Solar/Wind Harmer
6.061
964791AG1-342 GEN
Solar/Wind Harmer
2.266
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
12.748
971223AH1-071 GEN
Solar/Wind Harmer
1.248
3143526WINTERP
Solar/Wind Harmer
-0.043
970933AG2-581 GEN
Solar/Wind Harmer
7.571
316181AB2-040 GEN
Solar/Wind Harmer
1.004
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.784
3145593CAROLNA
Solar/Wind Harmer
0.058
3145783HORNRTN
Solar/Wind Harmer
0.814
3145783HORNRTN
Solar/Wind Harmer
0.651
3145783HORNRTN
Solar/Wind Harmer
0.204
3145783HORNRTN
Solar/Wind Harmer
0.081
316426AA2-053 GEN
Solar/Wind Harmer
0.684
972187AH1-678 GEN
Adder
1.664
972185AH1-677 GEN
Adder
3.229
966001AG1-469 GEN
Solar/Wind Helper
0.189
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.045
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.115
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.309
MECLTFEXP_MEC->PJM
CLTF
0.208
LAGNLTFEXP_LAGN->PJM
CLTF
1.574
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.039
TVALTFEXP_TVA->PJM
CLTF
0.757
SIGELTFEXP_SIGE->PJM
CLTF
0.003
CPLELTFEXP_CPLE->PJM
CLTF
3.638
NYPJM->LTFIMP_NY
CLTF
0.389
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.961

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2066-282_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2066-282_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.44 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:861.07
MW Contribution:28.17
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.41
3151911BEARGRDN G1
50/50
4.192
3144293JTRSVLE
50/50
0.653
970119AG2-088 GEN
50/50
15.082
972003AH1-546 GEN
Solar/Wind Harmer
24.312
971377AH1-170 GEN
Solar/Wind Harmer
5.633
3147623JAMES R
Solar/Wind Harmer
0.697
970937AG2-583 GEN
Solar/Wind Harmer
30.216
316322AB2-045
Solar/Wind Harmer
1.35
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.534
3146926FARMVIL
Solar/Wind Harmer
-0.019
3151921BEARGRDN G2
50/50
4.192
3144293JTRSVLE
50/50
0.653
970221AG2-151 GEN
Solar/Wind Harmer
28.166
3146776BUCKING
Solar/Wind Harmer
-0.014
3146926FARMVIL
Solar/Wind Harmer
-0.019
316313AB2-026
Solar/Wind Harmer
0.752
316258AE1-075 C
Solar/Wind Harmer
0.677
316405AF2-144 C
Solar/Wind Harmer
0.714
3143336POWHATN
Solar/Wind Harmer
2.812
942461AE2-259 GEN
Solar/Wind Harmer
4.067
970909AG2-566 GEN
Solar/Wind Harmer
2.224
3147133PAMPLIN
Solar/Wind Harmer
-0.072
3144293JTRSVLE
50/50
0.653
3144293JTRSVLE
50/50
0.55
971489AH1-241 GEN
Solar/Wind Harmer
26.74
3146776BUCKING
Solar/Wind Harmer
-0.16
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.489
970301AG2-198 GEN
Solar/Wind Harmer
11.714
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.394
963191AG1-168 GEN
Solar/Wind Harmer
2.036
971741AH1-377 GEN
Solar/Wind Harmer
24.324
316034AC1-036 C
Solar/Wind Harmer
0.327
970323AG2-213 GEN
Solar/Wind Harmer
8.802
971775AH1-396 GEN
Solar/Wind Harmer
1.253
313527AB2-043 GEN
Solar/Wind Harmer
2.088
971223AH1-071 GEN
Solar/Wind Harmer
1.589
962561AG1-105 GEN
Solar/Wind Harmer
5.986
939181AE1-148 GEN
Solar/Wind Harmer
5.822
964791AG1-342 GEN
Solar/Wind Harmer
2.188
3146843MT LREL
Solar/Wind Harmer
-0.01
3146843MT LREL
Solar/Wind Harmer
-0.01
970099AG2-077 GEN
Solar/Wind Harmer
12.325
970933AG2-581 GEN
Solar/Wind Harmer
7.23
316181AB2-040 GEN
Solar/Wind Harmer
0.916
3145593CAROLNA
Solar/Wind Harmer
-0.006
3145593CAROLNA
Solar/Wind Harmer
-0.006
966811AG1-552 GEN
Solar/Wind Harmer
0.712
3145593CAROLNA
Solar/Wind Harmer
0.053
966001AG1-469 GEN
Solar/Wind Helper
0.187
971193AH1-056 GEN
Solar/Wind Harmer
14.446
963181AG1-167 GEN
Solar/Wind Harmer
2.036
959311AF2-222 GEN
Solar/Wind Harmer
19.01
970257AG2-171 GEN
Solar/Wind Harmer
6.601
315785AD2-033 C
Solar/Wind Harmer
3.8
964241AG1-285 GEN
Solar/Wind Harmer
11.356
958131AF2-107 GEN
Solar/Wind Harmer
4.67
316131AB2-060 GEN
Solar/Wind Harmer
1.422
316478AD1-087 GEN
Solar/Wind Harmer
0.862
316486AD2-202 GEN
Solar/Wind Harmer
0.252
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.252
960061AF2-297 GEN
Solar/Wind Harmer
4.181
971683AH1-343 GEN
Solar/Wind Harmer
3.236
966621AG1-532 GEN
Solar/Wind Harmer
0.138
313506AB2-031 GEN
Solar/Wind Harmer
0.528
316499AE2-029_GEN
Solar/Wind Helper
0.5
3148013FISHERV
Solar/Wind Helper
0.13
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.535
3143336POWHATN
Solar/Wind Harmer
3.308
963171AG1-166 GEN
Solar/Wind Harmer
2.715
971563AH1-280 GEN
Solar/Wind Harmer
2.715
970685AG2-442 GEN
Solar/Wind Harmer
17.259
962491AG1-098 GEN
Solar/Wind Harmer
8.747
3143226MDLTHAN
Solar/Wind Harmer
-0.013
316237AB2-079_GEN
Solar/Wind Harmer
0.378
315693AD1-088 GEN
Solar/Wind Harmer
6.258
970401AG2-262 GEN
Solar/Wind Harmer
0.669
957481AF2-042 GEN
Solar/Wind Harmer
30.813
315687AD1-152 GEN
Solar/Wind Harmer
1.088
971065AG2-659 GEN
Solar/Wind Harmer
4.397
3147043LAWRENC
Adder
0.694
316129AC1-054 GEN
Solar/Wind Harmer
0.753
971795AH1-408 GEN
Solar/Wind Harmer
6.032
316003AC1-222 GEN
Solar/Wind Harmer
0.772
960081AF2-299 GEN
Solar/Wind Harmer
0.762
3147983MERCK5
Solar/Wind Helper
0.055
972205AH1-687 GEN
50/50
20.447
316303AF2-085
50/50
2.011
971447AH1-217 GEN
Solar/Wind Harmer
14.757
971845AH1-439 GEN
Solar/Wind Harmer
20.937
970285AG2-188 GEN
Solar/Wind Harmer
33.263
270494AE1-108_GEN
Solar/Wind Harmer
9.168
315657AE1-056 GEN
Solar/Wind Harmer
8.668
946301AF1-294 GEN
Solar/Wind Harmer
5.566
961791AG1-021 GEN
Solar/Wind Harmer
2.715
970683AG2-441 GEN
Solar/Wind Harmer
15.41
970681AG2-440 GEN
Solar/Wind Harmer
12.328
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.43
316239AB2-077_GEN
Solar/Wind Harmer
0.378
316238AB2-078_GEN
Solar/Wind Harmer
0.378
316118AC1-105 GEN
Solar/Wind Harmer
0.639
970831AG2-522 GEN
Solar/Wind Harmer
4.187
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
970865AG2-541 GEN
Solar/Wind Harmer
2.88
946281AF1-292 GEN
Solar/Wind Harmer
0.152
971967AH1-528 GEN
Solar/Wind Harmer
12.673
316087AB2-174 GEN
Solar/Wind Harmer
0.946
3137643SOCKMAN
Solar/Wind Harmer
-0.026
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.118
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.02
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.044
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.714
MECLTFEXP_MEC->PJM
CLTF
0.159
LAGNLTFEXP_LAGN->PJM
CLTF
1.141
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.807
TVALTFEXP_TVA->PJM
CLTF
0.557
SIGELTFEXP_SIGE->PJM
CLTF
0.003
CPLELTFEXP_CPLE->PJM
CLTF
2.977
NYPJM->LTFIMP_NY
CLTF
0.385
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.39

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.36 %
Rating:661.76 MVA
Rating Type:A
MVA to Mitigate:697.23
MW Contribution:21.01
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.118
3144293JTRSVLE
50/50
0.644
970413AG2-270 GEN
50/50
8.224
3151591KERR 2
50/50
0.18
966251AG1-494 GEN
50/50
1.173
3151261ROARAP2
50/50
0.07
970221AG2-151 GEN
Solar/Wind Harmer
21.013
3146776BUCKING
Solar/Wind Harmer
0.126
3146926FARMVIL
Solar/Wind Harmer
0.165
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.144
316258AE1-075 C
Solar/Wind Harmer
0.173
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.463
3151931BEARGRDN S1
50/50
5.314
3151911BEARGRDN G1
50/50
4.118
3144293JTRSVLE
50/50
0.644
3151531CLOVER1
50/50
1.885
3151601KERR 3
50/50
0.18
3151581KERR 1
50/50
0.064
970119AG2-088 GEN
50/50
11.599
3147043LAWRENC
50/50
0.746
3151261ROARAP2
50/50
0.072
972003AH1-546 GEN
Solar/Wind Harmer
18.108
971377AH1-170 GEN
Solar/Wind Harmer
4.203
3147623JAMES R
Solar/Wind Harmer
0.913
970937AG2-583 GEN
Solar/Wind Harmer
22.204
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.14
3146926FARMVIL
Solar/Wind Harmer
0.165
316336AC2-165 C
Solar/Wind Harmer
0.01
3143336POWHATN
Solar/Wind Harmer
4.074
963171AG1-166 GEN
Solar/Wind Harmer
1.017
971563AH1-280 GEN
Solar/Wind Harmer
2.035
970685AG2-442 GEN
Solar/Wind Harmer
12.945
962491AG1-098 GEN
Solar/Wind Harmer
6.577
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
5.296
970401AG2-262 GEN
Solar/Wind Harmer
0.531
957481AF2-042 GEN
Solar/Wind Harmer
23.244
3143226MDLTHAN
Solar/Wind Harmer
0.087
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.352
316129AC1-054 GEN
Solar/Wind Harmer
0.289
971795AH1-408 GEN
Solar/Wind Harmer
4.849
3143526WINTERP
Solar/Wind Harmer
0.377
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.595
3145783HORNRTN
Solar/Wind Harmer
0.057
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.752
972205AH1-687 GEN
50/50
20.083
3151541CLOVER2
50/50
1.876
3151611KERR 4
50/50
0.18
3151621KERR 5
50/50
0.18
3151631KERR 6
50/50
0.18
3151641KERR 7
50/50
0.18
316303AF2-085
50/50
1.546
3151281ROARAP4
50/50
0.07
3151281ROARAP4
50/50
0.066
971447AH1-217 GEN
Solar/Wind Harmer
11.004
971845AH1-439 GEN
Solar/Wind Harmer
15.632
970285AG2-188 GEN
Solar/Wind Harmer
26.316
270494AE1-108_GEN
Solar/Wind Harmer
3.693
315657AE1-056 GEN
Solar/Wind Harmer
6.997
946301AF1-294 GEN
Solar/Wind Harmer
3.764
961791AG1-021 GEN
Solar/Wind Harmer
1.831
970683AG2-441 GEN
Solar/Wind Harmer
11.558
970681AG2-440 GEN
Solar/Wind Harmer
9.247
3144303KENBRDG
Solar/Wind Harmer
0.124
971443AH1-215 GEN
Solar/Wind Harmer
2.576
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.212
970831AG2-522 GEN
Solar/Wind Harmer
3.201
3147173SINAI
Solar/Wind Harmer
0.074
3147243WELCO
Solar/Wind Harmer
0.046
316233AE1-074 FULL
Solar/Wind Harmer
0.058
971281AH1-106 GEN
Solar/Wind Harmer
1.006
971283AH1-107 GEN
Solar/Wind Harmer
1.006
970865AG2-541 GEN
Solar/Wind Harmer
2.17
316087AB2-174 GEN
Solar/Wind Harmer
0.002
971967AH1-528 GEN
Solar/Wind Harmer
9.597
3137643SOCKMAN
Solar/Wind Harmer
0.235
3138266HYDRAULIC
Solar/Wind Helper
0.021
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.08
3148013FISHERV
Solar/Wind Helper
0.077
3148463FAIRFLD
Solar/Wind Helper
0.119
970909AG2-566 GEN
Solar/Wind Harmer
2.192
3147133PAMPLIN
Solar/Wind Harmer
0.637
971193AH1-056 GEN
Solar/Wind Harmer
12.353
963181AG1-167 GEN
Solar/Wind Harmer
0.763
959311AF2-222 GEN
Solar/Wind Harmer
14.242
970257AG2-171 GEN
Solar/Wind Harmer
4.957
315785AD2-033 C
Solar/Wind Harmer
1.2
964241AG1-285 GEN
Solar/Wind Harmer
8.548
958131AF2-107 GEN
Solar/Wind Harmer
3.44
316131AB2-060 GEN
Solar/Wind Harmer
0.366
316478AD1-087 GEN
Solar/Wind Harmer
0.307
316486AD2-202 GEN
Solar/Wind Harmer
0.09
3147043LAWRENC
Solar/Wind Harmer
0.047
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.155
971683AH1-343 GEN
Solar/Wind Harmer
2.44
313506AB2-031 GEN
Solar/Wind Harmer
0.186
316499AE2-029_GEN
Solar/Wind Helper
0.505
3148013FISHERV
Solar/Wind Helper
0.133
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.54
3144293JTRSVLE
50/50
0.644
3144293JTRSVLE
50/50
0.543
970535AG2-341 GEN
50/50
1.768
3152661PLYWOOD A
50/50
0.177
971489AH1-241 GEN
Solar/Wind Harmer
21.013
3146776BUCKING
Solar/Wind Harmer
1.404
3146776BUCKING
Solar/Wind Harmer
0.114
315821AE2-092 GEN
Solar/Wind Harmer
0.014
970301AG2-198 GEN
Solar/Wind Harmer
8.767
3147133PAMPLIN
Solar/Wind Harmer
0.203
3147133PAMPLIN
Solar/Wind Harmer
0.162
958211AF2-115 GEN
Solar/Wind Harmer
2.289
963191AG1-168 GEN
Solar/Wind Harmer
0.763
971741AH1-377 GEN
Solar/Wind Harmer
18.217
316034AC1-036 C
Solar/Wind Harmer
0.011
970323AG2-213 GEN
Solar/Wind Harmer
6.61
971775AH1-396 GEN
Solar/Wind Harmer
0.248
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
4.515
939181AE1-148 GEN
Solar/Wind Harmer
4.407
964791AG1-342 GEN
Solar/Wind Harmer
1.738
3146843MT LREL
Solar/Wind Harmer
0.09
3146843MT LREL
Solar/Wind Harmer
0.09
970099AG2-077 GEN
Solar/Wind Harmer
9.298
971223AH1-071 GEN
Solar/Wind Harmer
0.928
3143526WINTERP
Solar/Wind Harmer
0.377
970933AG2-581 GEN
Solar/Wind Harmer
5.476
316181AB2-040 GEN
Solar/Wind Harmer
0.087
3145593CAROLNA
Solar/Wind Harmer
0.058
3145593CAROLNA
Solar/Wind Harmer
0.058
966811AG1-552 GEN
Solar/Wind Harmer
0.627
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.01
3145783HORNRTN
Solar/Wind Harmer
0.808
3145783HORNRTN
Solar/Wind Harmer
0.253
3145783HORNRTN
Solar/Wind Harmer
0.101
966001AG1-469 GEN
Solar/Wind Helper
0.19
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.029
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.072
LAGNLTFEXP_LAGN->PJM
CLTF
1.122
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.673
MECLTFEXP_MEC->PJM
CLTF
0.138
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.815
TVALTFEXP_TVA->PJM
CLTF
0.547
SIGELTFEXP_SIGE->PJM
CLTF
0.002
NYPJM->LTFIMP_NY
CLTF
0.391
CPLELTFEXP_CPLE->PJM
CLTF
2.992
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.238

Details for 6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.75 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:1023.09
MW Contribution:23.28
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.564
3144293JTRSVLE
50/50
0.616
966251AG1-494 GEN
50/50
1.534
3151591KERR 2
50/50
0.118
316313AB2-026
Solar/Wind Harmer
0.508
316258AE1-075 C
Solar/Wind Harmer
0.609
316405AF2-144 C
Solar/Wind Harmer
0.006
3143336POWHATN
Solar/Wind Harmer
12.186
970221AG2-151 GEN
Solar/Wind Harmer
23.276
3146776BUCKING
Solar/Wind Harmer
0.136
3146926FARMVIL
Solar/Wind Harmer
0.171
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
2.104
3147133PAMPLIN
Solar/Wind Harmer
0.618
971193AH1-056 GEN
Solar/Wind Harmer
11.992
963181AG1-167 GEN
Solar/Wind Harmer
0.73
959311AF2-222 GEN
Solar/Wind Harmer
12.95
958131AF2-107 GEN
Solar/Wind Harmer
4.127
970257AG2-171 GEN
Solar/Wind Harmer
4.458
315785AD2-033 C
Solar/Wind Harmer
1.061
964241AG1-285 GEN
Solar/Wind Harmer
7.147
316131AB2-060 GEN
Solar/Wind Harmer
0.293
972205AH1-687 GEN
50/50
22.262
3151611KERR 4
50/50
0.118
3151621KERR 5
50/50
0.118
3151631KERR 6
50/50
0.118
3151641KERR 7
50/50
0.118
971447AH1-217 GEN
Solar/Wind Harmer
12.398
971845AH1-439 GEN
Solar/Wind Harmer
16.766
970285AG2-188 GEN
Solar/Wind Harmer
28.069
270494AE1-108_GEN
Solar/Wind Harmer
4.133
315657AE1-056 GEN
Solar/Wind Harmer
6.793
946301AF1-294 GEN
Solar/Wind Harmer
3.599
961791AG1-021 GEN
Solar/Wind Harmer
1.751
970683AG2-441 GEN
Solar/Wind Harmer
10.766
970681AG2-440 GEN
Solar/Wind Harmer
8.613
3144303KENBRDG
Solar/Wind Harmer
0.111
971443AH1-215 GEN
Solar/Wind Harmer
2.308
3151931BEARGRDN S1
50/50
5.89
3151911BEARGRDN G1
50/50
4.564
3144293JTRSVLE
50/50
0.616
3151601KERR 3
50/50
0.118
3151581KERR 1
50/50
0.042
3143336POWHATN
Solar/Wind Harmer
14.336
316336AC2-165 C
Solar/Wind Harmer
0.029
970937AG2-583 GEN
Solar/Wind Harmer
37.444
972003AH1-546 GEN
Solar/Wind Harmer
19.982
971377AH1-170 GEN
Solar/Wind Harmer
4.655
3147623JAMES R
Solar/Wind Harmer
1.011
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.151
3146926FARMVIL
Solar/Wind Harmer
0.171
963171AG1-166 GEN
Solar/Wind Harmer
0.973
971563AH1-280 GEN
Solar/Wind Harmer
1.945
970685AG2-442 GEN
Solar/Wind Harmer
12.058
316237AB2-079_GEN
Solar/Wind Harmer
0.001
962491AG1-098 GEN
Solar/Wind Harmer
4.857
315693AD1-088 GEN
Solar/Wind Harmer
3.792
970401AG2-262 GEN
Solar/Wind Harmer
0.393
962751AG1-124 GEN
Solar/Wind Harmer
2.954
3143226MDLTHAN
Solar/Wind Helper
0.215
3143526WINTERP
Solar/Wind Helper
0.91
3144293JTRSVLE
50/50
0.616
3144293JTRSVLE
50/50
0.519
970535AG2-341 GEN
50/50
1.287
971489AH1-241 GEN
Solar/Wind Harmer
23.276
3146776BUCKING
Solar/Wind Harmer
1.51
3146776BUCKING
Solar/Wind Harmer
0.122
315821AE2-092 GEN
Solar/Wind Harmer
0.018
970301AG2-198 GEN
Solar/Wind Harmer
8.415
3147133PAMPLIN
Solar/Wind Harmer
0.197
3147133PAMPLIN
Solar/Wind Harmer
0.157
958211AF2-115 GEN
Solar/Wind Harmer
2.189
963191AG1-168 GEN
Solar/Wind Harmer
0.73
971741AH1-377 GEN
Solar/Wind Harmer
16.874
316034AC1-036 C
Solar/Wind Harmer
0.01
970323AG2-213 GEN
Solar/Wind Harmer
5.944
971775AH1-396 GEN
Solar/Wind Harmer
0.223
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.379
964791AG1-342 GEN
Solar/Wind Harmer
1.285
3146843MT LREL
Solar/Wind Harmer
0.067
3146843MT LREL
Solar/Wind Harmer
0.067
939181AE1-148 GEN
Solar/Wind Harmer
3.025
3143526WINTERP
Solar/Wind Helper
0.91
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.151
316233AE1-074 FULL
Solar/Wind Helper
0.267
LAGNLTFEXP_LAGN->PJM
CLTF
1.269
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.166
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.3
MECLTFEXP_MEC->PJM
CLTF
0.735
SIGELTFEXP_SIGE->PJM
CLTF
0.023
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.039
TVALTFEXP_TVA->PJM
CLTF
0.652
NYPJM->LTFIMP_NY
CLTF
0.434
LGEELTFEXP_LGEE->PJM
CLTF
0.296
WECLTFEXP_WEC->PJM
CLTF
0.147
CPLELTFEXP_CPLE->PJM
CLTF
1.241
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.227

Details for 6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.17 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:1002.46
MW Contribution:15.1
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
3.821
3151911BEARGRDN G1
50/50
2.961
3144293JTRSVLE
50/50
0.501
3151531CLOVER1
50/50
2.175
3151601KERR 3
50/50
0.134
3151581KERR 1
50/50
0.048
3143336POWHATN
Solar/Wind Harmer
12.647
316336AC2-165 C
Solar/Wind Harmer
0.025
970937AG2-583 GEN
Solar/Wind Harmer
28.662
972003AH1-546 GEN
Solar/Wind Harmer
13.092
971377AH1-170 GEN
Solar/Wind Harmer
3.021
3147623JAMES R
Solar/Wind Harmer
0.656
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
963171AG1-166 GEN
Solar/Wind Harmer
0.79
971563AH1-280 GEN
Solar/Wind Harmer
1.581
970685AG2-442 GEN
Solar/Wind Harmer
10.044
962491AG1-098 GEN
Solar/Wind Harmer
6.995
315693AD1-088 GEN
Solar/Wind Harmer
5.748
957481AF2-042 GEN
Solar/Wind Harmer
29.002
3151921BEARGRDN G2
50/50
2.961
3144293JTRSVLE
50/50
0.501
970413AG2-270 GEN
50/50
9.49
966251AG1-494 GEN
50/50
1.187
3151591KERR 2
50/50
0.134
316313AB2-026
Solar/Wind Harmer
0.448
316258AE1-075 C
Solar/Wind Harmer
0.537
316405AF2-144 C
Solar/Wind Harmer
0.005
3143336POWHATN
Solar/Wind Harmer
10.75
970221AG2-151 GEN
Solar/Wind Harmer
15.103
3146776BUCKING
Solar/Wind Harmer
0.094
3146926FARMVIL
Solar/Wind Harmer
0.129
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
1.863
3147133PAMPLIN
Solar/Wind Harmer
0.495
971193AH1-056 GEN
Solar/Wind Harmer
9.605
963181AG1-167 GEN
Solar/Wind Harmer
0.593
959311AF2-222 GEN
Solar/Wind Harmer
11.036
970257AG2-171 GEN
Solar/Wind Harmer
3.839
315785AD2-033 C
Solar/Wind Harmer
0.929
958131AF2-107 GEN
Solar/Wind Harmer
2.937
316478AD1-087 GEN
Solar/Wind Harmer
0.354
316486AD2-202 GEN
Solar/Wind Harmer
0.104
964241AG1-285 GEN
Solar/Wind Harmer
6.596
316131AB2-060 GEN
Solar/Wind Harmer
0.282
3148013FISHERV
Solar/Wind Harmer
0.07
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.906
971683AH1-343 GEN
Solar/Wind Harmer
2.326
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.716
315839AE2-212 C
Solar/Wind Helper
0.157
3144293JTRSVLE
50/50
0.501
3144293JTRSVLE
50/50
0.422
970535AG2-341 GEN
50/50
1.338
3152661PLYWOOD A
50/50
0.156
971489AH1-241 GEN
Solar/Wind Harmer
15.103
3146776BUCKING
Solar/Wind Harmer
1.047
3146776BUCKING
Solar/Wind Harmer
0.085
315821AE2-092 GEN
Solar/Wind Harmer
0.012
970301AG2-198 GEN
Solar/Wind Harmer
7.451
971741AH1-377 GEN
Solar/Wind Harmer
16.073
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.126
958211AF2-115 GEN
Solar/Wind Harmer
1.778
963191AG1-168 GEN
Solar/Wind Harmer
0.593
316034AC1-036 C
Solar/Wind Harmer
0.009
970323AG2-213 GEN
Solar/Wind Harmer
5.119
971775AH1-396 GEN
Solar/Wind Harmer
0.192
970099AG2-077 GEN
Solar/Wind Harmer
11.601
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.739
964791AG1-342 GEN
Solar/Wind Harmer
1.463
3146843MT LREL
Solar/Wind Harmer
0.076
3146843MT LREL
Solar/Wind Harmer
0.076
939181AE1-148 GEN
Solar/Wind Harmer
3.296
3143526WINTERP
Solar/Wind Helper
1.3
316240AF1-291 C
Solar/Wind Helper
0.164
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.158
316075AC2-137 C
Solar/Wind Helper
0.174
972205AH1-687 GEN
50/50
14.44
3151541CLOVER2
50/50
2.164
3151611KERR 4
50/50
0.134
3151621KERR 5
50/50
0.134
3151631KERR 6
50/50
0.134
3151641KERR 7
50/50
0.134
971447AH1-217 GEN
Solar/Wind Harmer
8.127
971845AH1-439 GEN
Solar/Wind Harmer
11.689
970285AG2-188 GEN
Solar/Wind Harmer
19.803
270494AE1-108_GEN
Solar/Wind Harmer
2.716
315657AE1-056 GEN
Solar/Wind Harmer
5.441
946301AF1-294 GEN
Solar/Wind Harmer
2.925
961791AG1-021 GEN
Solar/Wind Harmer
1.423
970683AG2-441 GEN
Solar/Wind Harmer
8.968
970681AG2-440 GEN
Solar/Wind Harmer
7.174
3144303KENBRDG
Solar/Wind Harmer
0.096
971443AH1-215 GEN
Solar/Wind Harmer
1.995
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.186
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.04
3147173SINAI
Solar/Wind Harmer
0.068
3147243WELCO
Solar/Wind Harmer
0.043
970865AG2-541 GEN
Solar/Wind Harmer
2.11
316233AE1-074 FULL
Solar/Wind Helper
0.382
316312AB1-027
Solar/Wind Helper
0.219
316132AB2-190 GEN1
Solar/Wind Helper
0.646
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.003
970401AG2-262 GEN
Solar/Wind Harmer
0.447
316003AC1-222 GEN
Solar/Wind Harmer
0.002
3143226MDLTHAN
Solar/Wind Helper
0.301
3143526WINTERP
Solar/Wind Helper
1.3
3142543TWELFTH
Solar/Wind Helper
0.014
3142416OLDCHRC
Solar/Wind Helper
0.299
3142416OLDCHRC
Solar/Wind Helper
0.115
316458AB2-190 GEN2
Solar/Wind Helper
0.646
3142433PROV 92
Solar/Wind Helper
0.449
LAGNLTFEXP_LAGN->PJM
CLTF
1.312
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.906
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.527
MECLTFEXP_MEC->PJM
CLTF
0.991
SIGELTFEXP_SIGE->PJM
CLTF
0.032
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.9
TVALTFEXP_TVA->PJM
CLTF
0.684
NYPJM->LTFIMP_NY
CLTF
0.361
LGEELTFEXP_LGEE->PJM
CLTF
0.427
WECLTFEXP_WEC->PJM
CLTF
0.217
CPLELTFEXP_CPLE->PJM
CLTF
0.56
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.43

Details for 6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2028T2054_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.58 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1171.87
MW Contribution:30.69
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.567
3144293JTRSVLE
50/50
0.616
316313AB2-026
Solar/Wind Harmer
2.443
316258AE1-075 C
Solar/Wind Harmer
2.199
316405AF2-144 C
Solar/Wind Harmer
2.321
3143336POWHATN
Solar/Wind Harmer
9.137
970221AG2-151 GEN
Solar/Wind Harmer
30.689
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.025
970909AG2-566 GEN
Solar/Wind Harmer
2.104
3147133PAMPLIN
Solar/Wind Harmer
-0.069
971193AH1-056 GEN
Solar/Wind Harmer
13.833
963181AG1-167 GEN
Solar/Wind Harmer
1.921
959311AF2-222 GEN
Solar/Wind Harmer
17.086
958131AF2-107 GEN
Solar/Wind Harmer
5.529
970257AG2-171 GEN
Solar/Wind Harmer
5.87
315785AD2-033 C
Solar/Wind Harmer
3.324
964241AG1-285 GEN
Solar/Wind Harmer
9.41
316131AB2-060 GEN
Solar/Wind Harmer
1.128
3151931BEARGRDN S1
50/50
5.894
3151911BEARGRDN G1
50/50
4.567
3144293JTRSVLE
50/50
0.616
3143336POWHATN
Solar/Wind Harmer
10.75
316336AC2-165 C
Solar/Wind Harmer
14.671
970937AG2-583 GEN
Solar/Wind Harmer
49.309
972003AH1-546 GEN
Solar/Wind Harmer
26.368
971377AH1-170 GEN
Solar/Wind Harmer
6.138
3147623JAMES R
Solar/Wind Harmer
0.76
316322AB2-045
Solar/Wind Harmer
1.428
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
963171AG1-166 GEN
Solar/Wind Harmer
2.562
971563AH1-280 GEN
Solar/Wind Harmer
2.562
970685AG2-442 GEN
Solar/Wind Harmer
15.878
316237AB2-079_GEN
Solar/Wind Harmer
0.294
962491AG1-098 GEN
Solar/Wind Harmer
6.385
315693AD1-088 GEN
Solar/Wind Harmer
4.43
970401AG2-262 GEN
Solar/Wind Harmer
0.491
962751AG1-124 GEN
Solar/Wind Harmer
4.381
3143226MDLTHAN
Solar/Wind Helper
0.216
3143526WINTERP
Solar/Wind Helper
0.915
3144293JTRSVLE
50/50
0.616
3144293JTRSVLE
50/50
0.519
971489AH1-241 GEN
Solar/Wind Harmer
29.135
3146776BUCKING
Solar/Wind Harmer
-0.169
3146776BUCKING
Solar/Wind Harmer
-0.014
315821AE2-092 GEN
Solar/Wind Harmer
6.917
970301AG2-198 GEN
Solar/Wind Harmer
11.079
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.202
963191AG1-168 GEN
Solar/Wind Harmer
1.921
971741AH1-377 GEN
Solar/Wind Harmer
22.212
316034AC1-036 C
Solar/Wind Harmer
0.291
970323AG2-213 GEN
Solar/Wind Harmer
7.827
971775AH1-396 GEN
Solar/Wind Harmer
1.115
313527AB2-043 GEN
Solar/Wind Harmer
1.635
962561AG1-105 GEN
Solar/Wind Harmer
4.451
964791AG1-342 GEN
Solar/Wind Harmer
1.607
3146843MT LREL
Solar/Wind Harmer
-0.007
3146843MT LREL
Solar/Wind Harmer
-0.007
939181AE1-148 GEN
Solar/Wind Harmer
3.98
3143526WINTERP
Solar/Wind Helper
0.915
972205AH1-687 GEN
50/50
22.274
971447AH1-217 GEN
Solar/Wind Harmer
16.359
971845AH1-439 GEN
Solar/Wind Harmer
22.085
970285AG2-188 GEN
Solar/Wind Harmer
34.896
270494AE1-108_GEN
Solar/Wind Harmer
10.095
315657AE1-056 GEN
Solar/Wind Harmer
8.3
946301AF1-294 GEN
Solar/Wind Harmer
5.252
961791AG1-021 GEN
Solar/Wind Harmer
2.562
970683AG2-441 GEN
Solar/Wind Harmer
14.177
970681AG2-440 GEN
Solar/Wind Harmer
11.342
3144303KENBRDG
Solar/Wind Harmer
-0.013
971443AH1-215 GEN
Solar/Wind Harmer
3.039
316239AB2-077_GEN
Solar/Wind Harmer
0.294
316238AB2-078_GEN
Solar/Wind Harmer
0.294
316118AC1-105 GEN
Solar/Wind Harmer
0.454
316233AE1-074 FULL
Solar/Wind Helper
0.269
LAGNLTFEXP_LAGN->PJM
CLTF
1.335
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.601
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.428
MECLTFEXP_MEC->PJM
CLTF
0.788
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.112
TVALTFEXP_TVA->PJM
CLTF
0.686
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
1.256
NYPJM->LTFIMP_NY
CLTF
0.451
LGEELTFEXP_LGEE->PJM
CLTF
0.319
WECLTFEXP_WEC->PJM
CLTF
0.159
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.662

Details for 6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 233T2028_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.83 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1154.77
MW Contribution:30.65
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.263
971447AH1-217 GEN
Solar/Wind Harmer
16.328
971845AH1-439 GEN
Solar/Wind Harmer
22.076
970285AG2-188 GEN
Solar/Wind Harmer
34.884
270494AE1-108_GEN
Solar/Wind Harmer
10.078
315657AE1-056 GEN
Solar/Wind Harmer
8.298
946301AF1-294 GEN
Solar/Wind Harmer
5.251
961791AG1-021 GEN
Solar/Wind Harmer
2.562
970683AG2-441 GEN
Solar/Wind Harmer
14.176
970681AG2-440 GEN
Solar/Wind Harmer
11.34
3144293JTRSVLE
50/50
0.616
3144293JTRSVLE
50/50
0.519
971489AH1-241 GEN
Solar/Wind Harmer
29.1
3146776BUCKING
Solar/Wind Harmer
-0.169
3146776BUCKING
Solar/Wind Harmer
-0.014
315821AE2-092 GEN
Solar/Wind Harmer
6.877
970301AG2-198 GEN
Solar/Wind Harmer
11.08
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.202
963191AG1-168 GEN
Solar/Wind Harmer
1.921
971741AH1-377 GEN
Solar/Wind Harmer
22.216
316034AC1-036 C
Solar/Wind Harmer
0.291
970323AG2-213 GEN
Solar/Wind Harmer
7.826
971775AH1-396 GEN
Solar/Wind Harmer
1.115
313527AB2-043 GEN
Solar/Wind Harmer
1.635
962561AG1-105 GEN
Solar/Wind Harmer
4.449
964791AG1-342 GEN
Solar/Wind Harmer
1.606
3146843MT LREL
Solar/Wind Harmer
-0.007
3146843MT LREL
Solar/Wind Harmer
-0.007
939181AE1-148 GEN
Solar/Wind Harmer
3.982
3143526WINTERP
Solar/Wind Helper
0.911
3144303KENBRDG
Solar/Wind Harmer
-0.013
971443AH1-215 GEN
Solar/Wind Harmer
3.039
316239AB2-077_GEN
Solar/Wind Harmer
0.294
316238AB2-078_GEN
Solar/Wind Harmer
0.294
316118AC1-105 GEN
Solar/Wind Harmer
0.453
316233AE1-074 FULL
Solar/Wind Helper
0.268
3151921BEARGRDN G2
50/50
4.565
3144293JTRSVLE
50/50
0.616
316313AB2-026
Solar/Wind Harmer
2.444
316258AE1-075 C
Solar/Wind Harmer
2.2
316405AF2-144 C
Solar/Wind Harmer
2.321
3143336POWHATN
Solar/Wind Harmer
9.139
970221AG2-151 GEN
Solar/Wind Harmer
30.652
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.024
970909AG2-566 GEN
Solar/Wind Harmer
2.104
3147133PAMPLIN
Solar/Wind Harmer
-0.069
971193AH1-056 GEN
Solar/Wind Harmer
13.831
963181AG1-167 GEN
Solar/Wind Harmer
1.921
959311AF2-222 GEN
Solar/Wind Harmer
17.085
958131AF2-107 GEN
Solar/Wind Harmer
5.499
970257AG2-171 GEN
Solar/Wind Harmer
5.87
315785AD2-033 C
Solar/Wind Harmer
3.324
964241AG1-285 GEN
Solar/Wind Harmer
9.411
316131AB2-060 GEN
Solar/Wind Harmer
1.128
3151931BEARGRDN S1
50/50
5.891
3151911BEARGRDN G1
50/50
4.565
3144293JTRSVLE
50/50
0.616
3143336POWHATN
Solar/Wind Harmer
10.752
316336AC2-165 C
Solar/Wind Harmer
14.673
970937AG2-583 GEN
Solar/Wind Harmer
49.302
972003AH1-546 GEN
Solar/Wind Harmer
26.356
971377AH1-170 GEN
Solar/Wind Harmer
6.13
3147623JAMES R
Solar/Wind Harmer
0.759
316322AB2-045
Solar/Wind Harmer
1.427
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
963171AG1-166 GEN
Solar/Wind Harmer
2.562
971563AH1-280 GEN
Solar/Wind Harmer
2.562
970685AG2-442 GEN
Solar/Wind Harmer
15.877
316237AB2-079_GEN
Solar/Wind Harmer
0.294
962491AG1-098 GEN
Solar/Wind Harmer
6.393
315693AD1-088 GEN
Solar/Wind Harmer
4.437
970401AG2-262 GEN
Solar/Wind Harmer
0.491
962751AG1-124 GEN
Solar/Wind Harmer
4.322
3143226MDLTHAN
Solar/Wind Helper
0.216
3143526WINTERP
Solar/Wind Helper
0.911
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.222
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.316
MECLTFEXP_MEC->PJM
CLTF
0.742
LAGNLTFEXP_LAGN->PJM
CLTF
1.277
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.048
TVALTFEXP_TVA->PJM
CLTF
0.657
SIGELTFEXP_SIGE->PJM
CLTF
0.023
CPLELTFEXP_CPLE->PJM
CLTF
1.243
NYPJM->LTFIMP_NY
CLTF
0.436
LGEELTFEXP_LGEE->PJM
CLTF
0.299
WECLTFEXP_WEC->PJM
CLTF
0.149
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.282

Details for 6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2193_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2028T2193_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.74 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1153.81
MW Contribution:29.38
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.964
3151911BEARGRDN G1
50/50
4.622
3144293JTRSVLE
50/50
0.625
3143336POWHATN
Solar/Wind Harmer
10.796
316336AC2-165 C
Solar/Wind Harmer
14.747
970937AG2-583 GEN
Solar/Wind Harmer
49.71
972003AH1-546 GEN
Solar/Wind Harmer
26.686
971377AH1-170 GEN
Solar/Wind Harmer
5.876
3147623JAMES R
Solar/Wind Harmer
0.727
316322AB2-045
Solar/Wind Harmer
1.446
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
963171AG1-166 GEN
Solar/Wind Harmer
2.598
971563AH1-280 GEN
Solar/Wind Harmer
2.598
970685AG2-442 GEN
Solar/Wind Harmer
16.109
316237AB2-079_GEN
Solar/Wind Harmer
0.299
962491AG1-098 GEN
Solar/Wind Harmer
6.515
315693AD1-088 GEN
Solar/Wind Harmer
4.524
970401AG2-262 GEN
Solar/Wind Harmer
0.499
962751AG1-124 GEN
Solar/Wind Harmer
4.155
3143226MDLTHAN
Solar/Wind Helper
0.213
3143526WINTERP
Solar/Wind Helper
0.898
3151921BEARGRDN G2
50/50
4.622
3144293JTRSVLE
50/50
0.625
316313AB2-026
Solar/Wind Harmer
2.454
316258AE1-075 C
Solar/Wind Harmer
2.209
316405AF2-144 C
Solar/Wind Harmer
2.33
3143336POWHATN
Solar/Wind Harmer
9.176
970221AG2-151 GEN
Solar/Wind Harmer
29.38
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.079
970909AG2-566 GEN
Solar/Wind Harmer
2.134
3147133PAMPLIN
Solar/Wind Harmer
-0.07
971193AH1-056 GEN
Solar/Wind Harmer
14.026
963181AG1-167 GEN
Solar/Wind Harmer
1.949
959311AF2-222 GEN
Solar/Wind Harmer
17.34
970257AG2-171 GEN
Solar/Wind Harmer
5.958
958131AF2-107 GEN
Solar/Wind Harmer
5.276
315785AD2-033 C
Solar/Wind Harmer
3.375
964241AG1-285 GEN
Solar/Wind Harmer
9.562
316131AB2-060 GEN
Solar/Wind Harmer
1.147
972205AH1-687 GEN
50/50
22.541
971447AH1-217 GEN
Solar/Wind Harmer
15.474
971845AH1-439 GEN
Solar/Wind Harmer
22.361
970285AG2-188 GEN
Solar/Wind Harmer
35.336
270494AE1-108_GEN
Solar/Wind Harmer
9.661
315657AE1-056 GEN
Solar/Wind Harmer
8.416
946301AF1-294 GEN
Solar/Wind Harmer
5.326
961791AG1-021 GEN
Solar/Wind Harmer
2.598
970683AG2-441 GEN
Solar/Wind Harmer
14.383
970681AG2-440 GEN
Solar/Wind Harmer
11.506
3144303KENBRDG
Solar/Wind Harmer
-0.013
971443AH1-215 GEN
Solar/Wind Harmer
3.085
316239AB2-077_GEN
Solar/Wind Harmer
0.299
316238AB2-078_GEN
Solar/Wind Harmer
0.299
316118AC1-105 GEN
Solar/Wind Harmer
0.461
316233AE1-074 FULL
Solar/Wind Helper
0.264
3144293JTRSVLE
50/50
0.625
3144293JTRSVLE
50/50
0.526
971489AH1-241 GEN
Solar/Wind Harmer
27.893
3146776BUCKING
Solar/Wind Harmer
-0.171
3146776BUCKING
Solar/Wind Harmer
-0.014
315821AE2-092 GEN
Solar/Wind Harmer
6.511
970301AG2-198 GEN
Solar/Wind Harmer
11.24
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.248
963191AG1-168 GEN
Solar/Wind Harmer
1.949
971741AH1-377 GEN
Solar/Wind Harmer
22.55
316034AC1-036 C
Solar/Wind Harmer
0.295
970323AG2-213 GEN
Solar/Wind Harmer
7.944
971775AH1-396 GEN
Solar/Wind Harmer
1.131
313527AB2-043 GEN
Solar/Wind Harmer
1.663
962561AG1-105 GEN
Solar/Wind Harmer
4.522
964791AG1-342 GEN
Solar/Wind Harmer
1.633
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
939181AE1-148 GEN
Solar/Wind Harmer
4.059
3143526WINTERP
Solar/Wind Helper
0.898
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.022
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.278
MECLTFEXP_MEC->PJM
CLTF
0.72
LAGNLTFEXP_LAGN->PJM
CLTF
1.261
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.084
TVALTFEXP_TVA->PJM
CLTF
0.647
SIGELTFEXP_SIGE->PJM
CLTF
0.023
CPLELTFEXP_CPLE->PJM
CLTF
1.273
NYPJM->LTFIMP_NY
CLTF
0.433
LGEELTFEXP_LGEE->PJM
CLTF
0.289
WECLTFEXP_WEC->PJM
CLTF
0.143
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.137

Details for 6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: WT2193_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT2193_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.71 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1153.58
MW Contribution:29.38
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.964
3151911BEARGRDN G1
50/50
4.622
3144293JTRSVLE
50/50
0.625
3143336POWHATN
Solar/Wind Harmer
10.796
316336AC2-165 C
Solar/Wind Harmer
14.747
970937AG2-583 GEN
Solar/Wind Harmer
49.71
972003AH1-546 GEN
Solar/Wind Harmer
26.686
971377AH1-170 GEN
Solar/Wind Harmer
5.876
3147623JAMES R
Solar/Wind Harmer
0.727
316322AB2-045
Solar/Wind Harmer
1.446
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
963171AG1-166 GEN
Solar/Wind Harmer
2.598
971563AH1-280 GEN
Solar/Wind Harmer
2.598
970685AG2-442 GEN
Solar/Wind Harmer
16.109
316237AB2-079_GEN
Solar/Wind Harmer
0.299
962491AG1-098 GEN
Solar/Wind Harmer
6.515
315693AD1-088 GEN
Solar/Wind Harmer
4.524
970401AG2-262 GEN
Solar/Wind Harmer
0.499
962751AG1-124 GEN
Solar/Wind Harmer
4.155
3143226MDLTHAN
Solar/Wind Helper
0.213
3143526WINTERP
Solar/Wind Helper
0.898
3151921BEARGRDN G2
50/50
4.622
3144293JTRSVLE
50/50
0.625
316313AB2-026
Solar/Wind Harmer
2.454
316258AE1-075 C
Solar/Wind Harmer
2.209
316405AF2-144 C
Solar/Wind Harmer
2.33
3143336POWHATN
Solar/Wind Harmer
9.176
970221AG2-151 GEN
Solar/Wind Harmer
29.38
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.079
970909AG2-566 GEN
Solar/Wind Harmer
2.134
3147133PAMPLIN
Solar/Wind Harmer
-0.07
971193AH1-056 GEN
Solar/Wind Harmer
14.026
963181AG1-167 GEN
Solar/Wind Harmer
1.949
959311AF2-222 GEN
Solar/Wind Harmer
17.34
970257AG2-171 GEN
Solar/Wind Harmer
5.958
958131AF2-107 GEN
Solar/Wind Harmer
5.276
315785AD2-033 C
Solar/Wind Harmer
3.375
964241AG1-285 GEN
Solar/Wind Harmer
9.562
316131AB2-060 GEN
Solar/Wind Harmer
1.147
972205AH1-687 GEN
50/50
22.541
971447AH1-217 GEN
Solar/Wind Harmer
15.474
971845AH1-439 GEN
Solar/Wind Harmer
22.361
970285AG2-188 GEN
Solar/Wind Harmer
35.336
270494AE1-108_GEN
Solar/Wind Harmer
9.661
315657AE1-056 GEN
Solar/Wind Harmer
8.416
946301AF1-294 GEN
Solar/Wind Harmer
5.326
961791AG1-021 GEN
Solar/Wind Harmer
2.598
970683AG2-441 GEN
Solar/Wind Harmer
14.383
970681AG2-440 GEN
Solar/Wind Harmer
11.506
3144303KENBRDG
Solar/Wind Harmer
-0.013
971443AH1-215 GEN
Solar/Wind Harmer
3.085
316239AB2-077_GEN
Solar/Wind Harmer
0.299
316238AB2-078_GEN
Solar/Wind Harmer
0.299
316118AC1-105 GEN
Solar/Wind Harmer
0.461
316233AE1-074 FULL
Solar/Wind Helper
0.264
3144293JTRSVLE
50/50
0.625
3144293JTRSVLE
50/50
0.526
971489AH1-241 GEN
Solar/Wind Harmer
27.893
3146776BUCKING
Solar/Wind Harmer
-0.171
3146776BUCKING
Solar/Wind Harmer
-0.014
315821AE2-092 GEN
Solar/Wind Harmer
6.511
970301AG2-198 GEN
Solar/Wind Harmer
11.24
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.248
963191AG1-168 GEN
Solar/Wind Harmer
1.949
971741AH1-377 GEN
Solar/Wind Harmer
22.55
316034AC1-036 C
Solar/Wind Harmer
0.295
970323AG2-213 GEN
Solar/Wind Harmer
7.944
971775AH1-396 GEN
Solar/Wind Harmer
1.131
313527AB2-043 GEN
Solar/Wind Harmer
1.663
962561AG1-105 GEN
Solar/Wind Harmer
4.522
964791AG1-342 GEN
Solar/Wind Harmer
1.633
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
939181AE1-148 GEN
Solar/Wind Harmer
4.059
3143526WINTERP
Solar/Wind Helper
0.898
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.022
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.278
MECLTFEXP_MEC->PJM
CLTF
0.72
LAGNLTFEXP_LAGN->PJM
CLTF
1.261
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.084
TVALTFEXP_TVA->PJM
CLTF
0.647
SIGELTFEXP_SIGE->PJM
CLTF
0.023
CPLELTFEXP_CPLE->PJM
CLTF
1.273
NYPJM->LTFIMP_NY
CLTF
0.433
LGEELTFEXP_LGEE->PJM
CLTF
0.289
WECLTFEXP_WEC->PJM
CLTF
0.143
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.137

Details for 6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 202872_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 202872_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.39 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1150.45
MW Contribution:29.38
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.625
3144293JTRSVLE
50/50
0.526
971489AH1-241 GEN
Solar/Wind Harmer
27.893
3146776BUCKING
Solar/Wind Harmer
-0.171
3146776BUCKING
Solar/Wind Harmer
-0.014
315821AE2-092 GEN
Solar/Wind Harmer
6.511
970301AG2-198 GEN
Solar/Wind Harmer
11.24
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.248
963191AG1-168 GEN
Solar/Wind Harmer
1.949
971741AH1-377 GEN
Solar/Wind Harmer
22.55
316034AC1-036 C
Solar/Wind Harmer
0.295
970323AG2-213 GEN
Solar/Wind Harmer
7.944
971775AH1-396 GEN
Solar/Wind Harmer
1.131
313527AB2-043 GEN
Solar/Wind Harmer
1.663
962561AG1-105 GEN
Solar/Wind Harmer
4.522
964791AG1-342 GEN
Solar/Wind Harmer
1.633
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
939181AE1-148 GEN
Solar/Wind Harmer
4.059
3143526WINTERP
Solar/Wind Helper
0.898
972205AH1-687 GEN
50/50
22.541
971447AH1-217 GEN
Solar/Wind Harmer
15.474
971845AH1-439 GEN
Solar/Wind Harmer
22.361
970285AG2-188 GEN
Solar/Wind Harmer
35.336
270494AE1-108_GEN
Solar/Wind Harmer
9.661
315657AE1-056 GEN
Solar/Wind Harmer
8.416
946301AF1-294 GEN
Solar/Wind Harmer
5.326
961791AG1-021 GEN
Solar/Wind Harmer
2.598
970683AG2-441 GEN
Solar/Wind Harmer
14.383
970681AG2-440 GEN
Solar/Wind Harmer
11.506
3151921BEARGRDN G2
50/50
4.622
3144293JTRSVLE
50/50
0.625
316313AB2-026
Solar/Wind Harmer
2.454
316258AE1-075 C
Solar/Wind Harmer
2.209
316405AF2-144 C
Solar/Wind Harmer
2.33
3143336POWHATN
Solar/Wind Harmer
9.176
970221AG2-151 GEN
Solar/Wind Harmer
29.38
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.079
970909AG2-566 GEN
Solar/Wind Harmer
2.134
3147133PAMPLIN
Solar/Wind Harmer
-0.07
971193AH1-056 GEN
Solar/Wind Harmer
14.026
963181AG1-167 GEN
Solar/Wind Harmer
1.949
959311AF2-222 GEN
Solar/Wind Harmer
17.34
970257AG2-171 GEN
Solar/Wind Harmer
5.958
958131AF2-107 GEN
Solar/Wind Harmer
5.276
315785AD2-033 C
Solar/Wind Harmer
3.375
964241AG1-285 GEN
Solar/Wind Harmer
9.562
316131AB2-060 GEN
Solar/Wind Harmer
1.147
3151931BEARGRDN S1
50/50
5.964
3151911BEARGRDN G1
50/50
4.622
3144293JTRSVLE
50/50
0.625
3143336POWHATN
Solar/Wind Harmer
10.796
316336AC2-165 C
Solar/Wind Harmer
14.747
970937AG2-583 GEN
Solar/Wind Harmer
49.71
972003AH1-546 GEN
Solar/Wind Harmer
26.686
971377AH1-170 GEN
Solar/Wind Harmer
5.876
3147623JAMES R
Solar/Wind Harmer
0.727
316322AB2-045
Solar/Wind Harmer
1.446
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
963171AG1-166 GEN
Solar/Wind Harmer
2.598
971563AH1-280 GEN
Solar/Wind Harmer
2.598
970685AG2-442 GEN
Solar/Wind Harmer
16.109
316237AB2-079_GEN
Solar/Wind Harmer
0.299
962491AG1-098 GEN
Solar/Wind Harmer
6.515
315693AD1-088 GEN
Solar/Wind Harmer
4.524
970401AG2-262 GEN
Solar/Wind Harmer
0.499
962751AG1-124 GEN
Solar/Wind Harmer
4.155
3143226MDLTHAN
Solar/Wind Helper
0.213
3143526WINTERP
Solar/Wind Helper
0.898
3144303KENBRDG
Solar/Wind Harmer
-0.013
971443AH1-215 GEN
Solar/Wind Harmer
3.085
316239AB2-077_GEN
Solar/Wind Harmer
0.299
316238AB2-078_GEN
Solar/Wind Harmer
0.299
316118AC1-105 GEN
Solar/Wind Harmer
0.461
316233AE1-074 FULL
Solar/Wind Helper
0.264
LAGNLTFEXP_LAGN->PJM
CLTF
1.261
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.022
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.278
MECLTFEXP_MEC->PJM
CLTF
0.72
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.084
TVALTFEXP_TVA->PJM
CLTF
0.647
SIGELTFEXP_SIGE->PJM
CLTF
0.023
CPLELTFEXP_CPLE->PJM
CLTF
1.273
NYPJM->LTFIMP_NY
CLTF
0.433
LGEELTFEXP_LGEE->PJM
CLTF
0.289
WECLTFEXP_WEC->PJM
CLTF
0.143
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.137

Details for 6PROFFIT-6HOLLYMD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6PROFFIT-6HOLLYMD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 553_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.67 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1167.96
MW Contribution:6.84
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
1.555
3151911BEARGRDN G1
50/50
1.205
3152161CUNINGA
50/50
0.763
972277AH1-723 GEN
50/50
62.568
3152061BATH 6F
50/50
2.078
23503401SHY_Z2-039
50/50
0.003
971377AH1-170 GEN
Solar/Wind Harmer
1.368
3147623JAMES R
Solar/Wind Harmer
0.297
972003AH1-546 GEN
Solar/Wind Harmer
5.266
315705AF1-075 GEN
Solar/Wind Harmer
4.096
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.039
970937AG2-583 GEN
Solar/Wind Harmer
6.041
3147983MERCK5
Solar/Wind Harmer
0.038
3146926FARMVIL
Solar/Wind Harmer
0.044
316336AC2-165 C
Solar/Wind Harmer
0.002
316192AB2-158 GEN
Solar/Wind Helper
3.262
3147666LOUISA
Solar/Wind Helper
1.887
316254AC1-120 GEN1
Solar/Wind Helper
1.426
316006AB2-029 C
Solar/Wind Helper
0.088
972205AH1-687 GEN
50/50
5.876
3151881LOWMORC
50/50
1.119
3151881LOWMORC
50/50
1.101
3151861LOWMORA
50/50
1.084
3152181CUNINGC
50/50
0.816
972193AH1-681 GEN
50/50
2.399
3152011BATH 1A
50/50
2.071
3152021BATH 2B
50/50
2.071
3152031BATH 3C
50/50
2.071
3152041BATH 4D
50/50
2.067
3138266HYDRAULIC
Solar/Wind Harmer
0.011
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3148133STUARTS
Solar/Wind Harmer
0.083
3148013FISHERV
Solar/Wind Harmer
0.079
971447AH1-217 GEN
Solar/Wind Harmer
3.945
270494AE1-108_GEN
Solar/Wind Harmer
1.309
3148463FAIRFLD
Solar/Wind Harmer
0.099
971845AH1-439 GEN
Solar/Wind Harmer
4.376
970285AG2-188 GEN
Solar/Wind Harmer
7.313
316164AC1-076 GEN
Solar/Wind Helper
1.19
3151921BEARGRDN G2
50/50
1.205
3137383CUSHAW
50/50
0.022
3151861LOWMORA
50/50
1.128
3152191CUNINGD
50/50
1.776
3152171CUNINGB
50/50
0.767
972255AH1-712 GEN
50/50
53.693
315760AF1-028 GEN
50/50
15.215
3152051BATH 5E
50/50
2.069
3148013FISHERV
Solar/Wind Harmer
0.138
970221AG2-151 GEN
Solar/Wind Harmer
6.84
315616AA1-038_C
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.036
3146926FARMVIL
Solar/Wind Harmer
0.044
958131AF2-107 GEN
Solar/Wind Harmer
1.93
942461AE2-259 GEN
Solar/Wind Harmer
0
3132273ORANGE
Solar/Wind Helper
0.105
3147666LOUISA
Solar/Wind Helper
1.085
316170AC1-121 GEN2
Solar/Wind Helper
0.475
23503501NHY_Z2-039
50/50
0.005
315821AE2-092 GEN
Solar/Wind Harmer
0.008
971489AH1-241 GEN
Solar/Wind Harmer
6.84
3146776BUCKING
Solar/Wind Harmer
0.395
3146776BUCKING
Solar/Wind Harmer
0.032
3132123MT JACKSON
Solar/Wind Harmer
0.208
970117AG2-086 GEN
Solar/Wind Harmer
1.594
970117AG2-086 GEN
Solar/Wind Harmer
1.063
966001AG1-469 GEN
Solar/Wind Helper
0.735
315651AD1-115 GEN
Solar/Wind Helper
0.962
LAGNLTFEXP_LAGN->PJM
CLTF
2.697
CBM West 1LTFEXP_CBM-W1->PJM
CBM
16.766
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.191
MECLTFEXP_MEC->PJM
CLTF
2.078
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.536
TVALTFEXP_TVA->PJM
CLTF
1.4
SIGELTFEXP_SIGE->PJM
CLTF
0.068
NYPJM->LTFIMP_NY
CLTF
0.747
LGEELTFEXP_LGEE->PJM
CLTF
0.893
WECLTFEXP_WEC->PJM
CLTF
0.458
CPLELTFEXP_CPLE->PJM
CLTF
0.939
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.474

Details for 6PROFFIT-6HOLLYMD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6PROFFIT-6HOLLYMD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.71 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1050.18
MW Contribution:7.05
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.21
3144293JTRSVLE
50/50
0.177
23503501NHY_Z2-039
50/50
0.004
971489AH1-241 GEN
Solar/Wind Harmer
7.052
315821AE2-092 GEN
Solar/Wind Harmer
0.008
3146776BUCKING
Solar/Wind Harmer
0.434
3146776BUCKING
Solar/Wind Harmer
0.035
3147133PAMPLIN
Solar/Wind Harmer
0.066
3147133PAMPLIN
Solar/Wind Harmer
0.052
970301AG2-198 GEN
Solar/Wind Harmer
2.774
958211AF2-115 GEN
Solar/Wind Harmer
0.747
963191AG1-168 GEN
Solar/Wind Harmer
0.249
971741AH1-377 GEN
Solar/Wind Harmer
5.799
966001AG1-469 GEN
Solar/Wind Helper
0.74
315651AD1-115 GEN
Solar/Wind Helper
0.968
3151921BEARGRDN G2
50/50
1.262
3137383CUSHAW
50/50
0.018
3151861LOWMORA
50/50
0.943
315760AF1-028 GEN
50/50
12.698
3152051BATH 5E
50/50
1.654
3144293JTRSVLE
50/50
0.21
3152191CUNINGD
50/50
1.059
3152171CUNINGB
50/50
0.457
972255AH1-712 GEN
50/50
32.018
970221AG2-151 GEN
Solar/Wind Harmer
7.052
3148013FISHERV
Solar/Wind Harmer
0.123
3146776BUCKING
Solar/Wind Harmer
0.039
3146926FARMVIL
Solar/Wind Harmer
0.052
315616AA1-038_C
Solar/Wind Harmer
0.001
942461AE2-259 GEN
Solar/Wind Harmer
0
316313AB2-026
Solar/Wind Harmer
0.042
316258AE1-075 C
Solar/Wind Harmer
0.05
316405AF2-144 C
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
1.009
958131AF2-107 GEN
Solar/Wind Harmer
1.905
3147133PAMPLIN
Solar/Wind Harmer
0.206
971193AH1-056 GEN
Solar/Wind Harmer
3.999
970909AG2-566 GEN
Solar/Wind Harmer
0.694
963181AG1-167 GEN
Solar/Wind Harmer
0.249
3132273ORANGE
Solar/Wind Helper
0.106
3147666LOUISA
Solar/Wind Helper
1.086
316170AC1-121 GEN2
Solar/Wind Helper
0.478
972205AH1-687 GEN
50/50
6.155
3151881LOWMORC
50/50
0.936
3151881LOWMORC
50/50
0.921
3151861LOWMORA
50/50
0.906
3152011BATH 1A
50/50
1.656
3152021BATH 2B
50/50
1.656
3152031BATH 3C
50/50
1.655
3152041BATH 4D
50/50
1.652
3152181CUNINGC
50/50
0.486
972193AH1-681 GEN
50/50
1.431
3138266HYDRAULIC
Solar/Wind Harmer
0.011
3138266HYDRAULIC
Solar/Wind Harmer
0.007
971447AH1-217 GEN
Solar/Wind Harmer
4.022
3148133STUARTS
Solar/Wind Harmer
0.074
3148013FISHERV
Solar/Wind Harmer
0.071
270494AE1-108_GEN
Solar/Wind Harmer
1.339
971845AH1-439 GEN
Solar/Wind Harmer
4.834
970285AG2-188 GEN
Solar/Wind Harmer
8.151
3148463FAIRFLD
Solar/Wind Harmer
0.083
315657AE1-056 GEN
Solar/Wind Harmer
2.265
946301AF1-294 GEN
Solar/Wind Harmer
1.229
961791AG1-021 GEN
Solar/Wind Harmer
0.598
970683AG2-441 GEN
Solar/Wind Harmer
3.826
970681AG2-440 GEN
Solar/Wind Harmer
3.061
316164AC1-076 GEN
Solar/Wind Helper
1.194
3151931BEARGRDN S1
50/50
1.629
3151911BEARGRDN G1
50/50
1.262
3152061BATH 6F
50/50
1.661
3144293JTRSVLE
50/50
0.21
23503401SHY_Z2-039
50/50
0.002
3152161CUNINGA
50/50
0.455
972277AH1-723 GEN
50/50
37.31
971377AH1-170 GEN
Solar/Wind Harmer
1.41
3147623JAMES R
Solar/Wind Harmer
0.306
972003AH1-546 GEN
Solar/Wind Harmer
5.557
970937AG2-583 GEN
Solar/Wind Harmer
6.724
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.043
3146926FARMVIL
Solar/Wind Harmer
0.052
315705AF1-075 GEN
Solar/Wind Harmer
3.448
3147983MERCK5
Solar/Wind Harmer
0.033
316336AC2-165 C
Solar/Wind Harmer
0.003
3143336POWHATN
Solar/Wind Harmer
1.187
963171AG1-166 GEN
Solar/Wind Harmer
0.332
971563AH1-280 GEN
Solar/Wind Harmer
0.664
970685AG2-442 GEN
Solar/Wind Harmer
4.286
316192AB2-158 GEN
Solar/Wind Helper
3.267
3147666LOUISA
Solar/Wind Helper
1.889
316254AC1-120 GEN1
Solar/Wind Helper
1.434
316006AB2-029 C
Solar/Wind Helper
0.088
LAGNLTFEXP_LAGN->PJM
CLTF
2.954
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.521
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.505
MECLTFEXP_MEC->PJM
CLTF
2.015
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.46
TVALTFEXP_TVA->PJM
CLTF
1.519
SIGELTFEXP_SIGE->PJM
CLTF
0.065
NYPJM->LTFIMP_NY
CLTF
0.852
LGEELTFEXP_LGEE->PJM
CLTF
0.839
WECLTFEXP_WEC->PJM
CLTF
0.429
CPLELTFEXP_CPLE->PJM
CLTF
1.993
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.046

Details for 6S ANNA-6DESPER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2199_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
6S ANNA-6DESPER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2199_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:161.07 %
Rating:819.68 MVA
Rating Type:B
MVA to Mitigate:1320.25
MW Contribution:4.18
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
3.638
3147346CASHSCORNER
Solar/Wind Harmer
1.129
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3138266HYDRAULIC
Solar/Wind Harmer
0.004
316164AC1-076 GEN
Solar/Wind Harmer
0.131
971447AH1-217 GEN
Solar/Wind Harmer
2.387
3148133STUARTS
Solar/Wind Harmer
0.044
3148013FISHERV
Solar/Wind Harmer
0.043
270494AE1-108_GEN
Solar/Wind Harmer
0.78
971845AH1-439 GEN
Solar/Wind Harmer
2.686
970285AG2-188 GEN
Solar/Wind Harmer
4.481
3151731LOISA B
50/50
36.472
3151721LOISA A
50/50
36.283
966001AG1-469 GEN
Solar/Wind Harmer
0.277
315651AD1-115 GEN
Solar/Wind Harmer
0.004
971489AH1-241 GEN
Solar/Wind Harmer
4.176
315821AE2-092 GEN
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.242
3146776BUCKING
Solar/Wind Harmer
0.02
3151771S ANNAG1
50/50
1.913
3151801S ANNAS2
50/50
0.983
3151761LOISA E
50/50
74.355
972183AH1-676 GEN
50/50
587.912
3151921BEARGRDN G2
50/50
0.746
3132273ORANGE
Solar/Wind Harmer
0.067
316170AC1-121 GEN2
Solar/Wind Harmer
0.15
970221AG2-151 GEN
Solar/Wind Harmer
4.176
3148013FISHERV
Solar/Wind Harmer
0.074
3146776BUCKING
Solar/Wind Harmer
0.022
3147666LOUISA
Solar/Wind Helper
1.694
3151791S ANNAG2
50/50
1.913
3151781S ANNAS1
50/50
0.983
3151741LOISA C
50/50
1.994
3151751LOISA D
50/50
36.472
3151931BEARGRDN S1
50/50
0.963
3151911BEARGRDN G1
50/50
0.746
315683AE1-153 C
Solar/Wind Harmer
41.191
316254AC1-120 GEN1
Solar/Wind Harmer
0.3
971377AH1-170 GEN
Solar/Wind Harmer
0.835
3147623JAMES R
Solar/Wind Harmer
0.181
972003AH1-546 GEN
Solar/Wind Harmer
3.257
970937AG2-583 GEN
Solar/Wind Harmer
3.728
316322AB2-045
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.024
316192AB2-158 GEN
Solar/Wind Helper
5.116
3147666LOUISA
Solar/Wind Helper
2.947
LAGNLTFEXP_LAGN->PJM
CLTF
1.059
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.552
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.053
MECLTFEXP_MEC->PJM
CLTF
0.818
SIGELTFEXP_SIGE->PJM
CLTF
0.027
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.306
TVALTFEXP_TVA->PJM
CLTF
0.553
NYPJM->LTFIMP_NY
CLTF
0.38
LGEELTFEXP_LGEE->PJM
CLTF
0.355
WECLTFEXP_WEC->PJM
CLTF
0.18
CPLELTFEXP_CPLE->PJM
CLTF
0.308
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.881

Details for 6S ANNA-6DESPER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2331_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6S ANNA-6DESPER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2331_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:156.26 %
Rating:819.68 MVA
Rating Type:B
MVA to Mitigate:1280.87
MW Contribution:4.18
Bus #Bus NameTypeMW Contribution
3151791S ANNAG2
50/50
1.913
3151781S ANNAS1
50/50
0.983
3151741LOISA C
50/50
1.994
3151751LOISA D
50/50
36.472
3151931BEARGRDN S1
50/50
0.963
3151911BEARGRDN G1
50/50
0.746
315683AE1-153 C
Solar/Wind Harmer
41.191
316254AC1-120 GEN1
Solar/Wind Harmer
0.3
971377AH1-170 GEN
Solar/Wind Harmer
0.835
3147623JAMES R
Solar/Wind Harmer
0.181
972003AH1-546 GEN
Solar/Wind Harmer
3.257
970937AG2-583 GEN
Solar/Wind Harmer
3.728
316322AB2-045
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.024
316192AB2-158 GEN
Solar/Wind Helper
5.116
3147666LOUISA
Solar/Wind Helper
2.947
972205AH1-687 GEN
50/50
3.638
3147346CASHSCORNER
Solar/Wind Harmer
1.129
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3138266HYDRAULIC
Solar/Wind Harmer
0.004
316164AC1-076 GEN
Solar/Wind Harmer
0.131
971447AH1-217 GEN
Solar/Wind Harmer
2.387
3148133STUARTS
Solar/Wind Harmer
0.044
3148013FISHERV
Solar/Wind Harmer
0.043
270494AE1-108_GEN
Solar/Wind Harmer
0.78
971845AH1-439 GEN
Solar/Wind Harmer
2.686
970285AG2-188 GEN
Solar/Wind Harmer
4.481
3151771S ANNAG1
50/50
1.913
3151801S ANNAS2
50/50
0.983
3151761LOISA E
50/50
74.355
972183AH1-676 GEN
50/50
587.912
3151921BEARGRDN G2
50/50
0.746
3132273ORANGE
Solar/Wind Harmer
0.067
316170AC1-121 GEN2
Solar/Wind Harmer
0.15
970221AG2-151 GEN
Solar/Wind Harmer
4.176
3148013FISHERV
Solar/Wind Harmer
0.074
3146776BUCKING
Solar/Wind Harmer
0.022
3147666LOUISA
Solar/Wind Helper
1.694
3151731LOISA B
50/50
36.472
3151721LOISA A
50/50
36.283
966001AG1-469 GEN
Solar/Wind Harmer
0.277
315651AD1-115 GEN
Solar/Wind Harmer
0.004
971489AH1-241 GEN
Solar/Wind Harmer
4.176
315821AE2-092 GEN
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.242
3146776BUCKING
Solar/Wind Harmer
0.02
LAGNLTFEXP_LAGN->PJM
CLTF
1.059
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.552
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.053
MECLTFEXP_MEC->PJM
CLTF
0.818
SIGELTFEXP_SIGE->PJM
CLTF
0.027
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.306
TVALTFEXP_TVA->PJM
CLTF
0.553
NYPJM->LTFIMP_NY
CLTF
0.38
LGEELTFEXP_LGEE->PJM
CLTF
0.355
WECLTFEXP_WEC->PJM
CLTF
0.18
CPLELTFEXP_CPLE->PJM
CLTF
0.308
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.881

Details for 6S ANNA-6DESPER 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
6S ANNA-6DESPER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:154.71 %
Rating:1003.0 MVA
Rating Type:C
MVA to Mitigate:1551.76
MW Contribution:6.34
Bus #Bus NameTypeMW Contribution
3147346CASHSCORNER
Solar/Wind Harmer
0.957
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
972205AH1-687 GEN
Adder
3.955
971447AH1-217 GEN
Solar/Wind Harmer
3.619
3148133STUARTS
Solar/Wind Harmer
-0.006
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
2.195
971845AH1-439 GEN
Solar/Wind Harmer
4.122
970285AG2-188 GEN
Solar/Wind Harmer
6.502
3151791S ANNAG2
50/50
2.138
3151781S ANNAS1
50/50
1.098
3151741LOISA C
50/50
2.244
3151751LOISA D
50/50
41.036
315683AE1-153 C
Solar/Wind Harmer
61.307
971377AH1-170 GEN
Solar/Wind Harmer
1.268
3147623JAMES R
Solar/Wind Harmer
0.157
972003AH1-546 GEN
Solar/Wind Harmer
4.962
970937AG2-583 GEN
Solar/Wind Harmer
5.727
316322AB2-045
Solar/Wind Harmer
0.267
3146776BUCKING
Solar/Wind Harmer
-0.003
315705AF1-075 GEN
Solar/Wind Harmer
2.919
316192AB2-158 GEN
Solar/Wind Helper
4.574
3151771S ANNAG1
50/50
2.138
3151801S ANNAS2
50/50
1.098
3151761LOISA E
50/50
83.66
972183AH1-676 GEN
50/50
664.569
970221AG2-151 GEN
Solar/Wind Harmer
6.338
3148013FISHERV
Solar/Wind Harmer
-0.009
3146776BUCKING
Solar/Wind Harmer
-0.003
316499AE2-029_GEN
Solar/Wind Harmer
0.523
3147666LOUISA
Solar/Wind Helper
1.516
3151731LOISA B
50/50
41.036
3151721LOISA A
50/50
40.824
966001AG1-469 GEN
Solar/Wind Harmer
1.243
971489AH1-241 GEN
Solar/Wind Harmer
6.017
315821AE2-092 GEN
Solar/Wind Harmer
2.072
3146776BUCKING
Solar/Wind Harmer
-0.032
3146776BUCKING
Solar/Wind Harmer
-0.003
3147666LOUISA
Solar/Wind Helper
2.636
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.761
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.516
MECLTFEXP_MEC->PJM
CLTF
0.979
LAGNLTFEXP_LAGN->PJM
CLTF
1.31
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.816
TVALTFEXP_TVA->PJM
CLTF
0.682
SIGELTFEXP_SIGE->PJM
CLTF
0.032
CPLELTFEXP_CPLE->PJM
CLTF
0.503
NYPJM->LTFIMP_NY
CLTF
0.463
LGEELTFEXP_LGEE->PJM
CLTF
0.422
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.377
WECLTFEXP_WEC->PJM
CLTF
0.214

Details for 6S ANNA-6DESPER 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6S ANNA-6DESPER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:148.61 %
Rating:1003.0 MVA
Rating Type:C
MVA to Mitigate:1490.53
MW Contribution:6.34
Bus #Bus NameTypeMW Contribution
3147346CASHSCORNER
Solar/Wind Harmer
0.957
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
972205AH1-687 GEN
Adder
3.955
971447AH1-217 GEN
Solar/Wind Harmer
3.619
3148133STUARTS
Solar/Wind Harmer
-0.006
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
2.195
971845AH1-439 GEN
Solar/Wind Harmer
4.122
970285AG2-188 GEN
Solar/Wind Harmer
6.502
3151771S ANNAG1
50/50
2.138
3151801S ANNAS2
50/50
1.098
3151761LOISA E
50/50
83.66
972183AH1-676 GEN
50/50
664.569
970221AG2-151 GEN
Solar/Wind Harmer
6.338
3148013FISHERV
Solar/Wind Harmer
-0.009
3146776BUCKING
Solar/Wind Harmer
-0.003
316499AE2-029_GEN
Solar/Wind Harmer
0.523
3147666LOUISA
Solar/Wind Helper
1.516
3151731LOISA B
50/50
41.036
3151721LOISA A
50/50
40.824
966001AG1-469 GEN
Solar/Wind Harmer
1.243
971489AH1-241 GEN
Solar/Wind Harmer
6.017
315821AE2-092 GEN
Solar/Wind Harmer
2.072
3146776BUCKING
Solar/Wind Harmer
-0.032
3146776BUCKING
Solar/Wind Harmer
-0.003
3151791S ANNAG2
50/50
2.138
3151781S ANNAS1
50/50
1.098
3151741LOISA C
50/50
2.244
3151751LOISA D
50/50
41.036
971377AH1-170 GEN
Solar/Wind Harmer
1.268
3147623JAMES R
Solar/Wind Harmer
0.157
972003AH1-546 GEN
Solar/Wind Harmer
4.962
970937AG2-583 GEN
Solar/Wind Harmer
5.727
316322AB2-045
Solar/Wind Harmer
0.267
3146776BUCKING
Solar/Wind Harmer
-0.003
315705AF1-075 GEN
Solar/Wind Harmer
2.919
316192AB2-158 GEN
Solar/Wind Helper
4.574
3147666LOUISA
Solar/Wind Helper
2.636
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.761
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.516
MECLTFEXP_MEC->PJM
CLTF
0.979
LAGNLTFEXP_LAGN->PJM
CLTF
1.31
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.816
TVALTFEXP_TVA->PJM
CLTF
0.682
SIGELTFEXP_SIGE->PJM
CLTF
0.032
CPLELTFEXP_CPLE->PJM
CLTF
0.503
NYPJM->LTFIMP_NY
CLTF
0.463
LGEELTFEXP_LGEE->PJM
CLTF
0.422
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.377
WECLTFEXP_WEC->PJM
CLTF
0.214

Details for 6S ANNA-6DESPER 230.0 kV Ckt 1 line l/o DVP_P4-2: 2199T2331_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6S ANNA-6DESPER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2199T2331_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.32 %
Rating:1003.0 MVA
Rating Type:C
MVA to Mitigate:1347.19
MW Contribution:5.5
Bus #Bus NameTypeMW Contribution
3147346CASHSCORNER
Solar/Wind Harmer
0.847
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
316164AC1-076 GEN
Solar/Wind Harmer
0.884
972205AH1-687 GEN
Adder
3.428
971447AH1-217 GEN
Solar/Wind Harmer
3.143
3148133STUARTS
Solar/Wind Harmer
-0.005
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
1.902
971845AH1-439 GEN
Solar/Wind Harmer
3.536
970285AG2-188 GEN
Solar/Wind Harmer
5.568
3151791S ANNAG2
50/50
1.913
3151781S ANNAS1
50/50
0.983
3151741LOISA C
50/50
1.994
3151751LOISA D
50/50
36.472
315683AE1-153 C
Solar/Wind Harmer
54.235
316254AC1-120 GEN1
Solar/Wind Harmer
1.276
971377AH1-170 GEN
Solar/Wind Harmer
1.1
3147623JAMES R
Solar/Wind Harmer
0.136
972003AH1-546 GEN
Solar/Wind Harmer
4.295
970937AG2-583 GEN
Solar/Wind Harmer
4.908
316322AB2-045
Solar/Wind Harmer
0.229
3146776BUCKING
Solar/Wind Harmer
-0.003
316192AB2-158 GEN
Solar/Wind Helper
5.116
3147666LOUISA
Solar/Wind Helper
2.947
3151771S ANNAG1
50/50
1.913
3151801S ANNAS2
50/50
0.983
3151761LOISA E
50/50
74.355
972183AH1-676 GEN
50/50
587.912
3132273ORANGE
Solar/Wind Harmer
-0.007
316170AC1-121 GEN2
Solar/Wind Harmer
0.425
970221AG2-151 GEN
Solar/Wind Harmer
5.499
3148013FISHERV
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Harmer
-0.002
3147666LOUISA
Solar/Wind Helper
1.694
3151731LOISA B
50/50
36.472
3151721LOISA A
50/50
36.283
966001AG1-469 GEN
Solar/Wind Harmer
1.011
315651AD1-115 GEN
Solar/Wind Harmer
5.746
971489AH1-241 GEN
Solar/Wind Harmer
5.221
315821AE2-092 GEN
Solar/Wind Harmer
1.803
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
LAGNLTFEXP_LAGN->PJM
CLTF
1.059
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.552
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.053
MECLTFEXP_MEC->PJM
CLTF
0.818
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.306
TVALTFEXP_TVA->PJM
CLTF
0.553
SIGELTFEXP_SIGE->PJM
CLTF
0.027
NYPJM->LTFIMP_NY
CLTF
0.38
LGEELTFEXP_LGEE->PJM
CLTF
0.355
WECLTFEXP_WEC->PJM
CLTF
0.18
CPLELTFEXP_CPLE->PJM
CLTF
0.308
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.881

Details for 6S ANNA-6DESPER 230.0 kV Ckt 1 line l/o DVP_P4-2: 2278T2331_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6S ANNA-6DESPER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2278T2331_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.29 %
Rating:1003.0 MVA
Rating Type:C
MVA to Mitigate:1306.8
MW Contribution:5.5
Bus #Bus NameTypeMW Contribution
3147346CASHSCORNER
Solar/Wind Harmer
0.847
3151791S ANNAG2
50/50
1.913
3151781S ANNAS1
50/50
0.983
3151741LOISA C
50/50
1.994
3151751LOISA D
50/50
36.472
315683AE1-153 C
Solar/Wind Harmer
54.235
316254AC1-120 GEN1
Solar/Wind Harmer
1.276
971377AH1-170 GEN
Solar/Wind Harmer
1.1
3147623JAMES R
Solar/Wind Harmer
0.136
972003AH1-546 GEN
Solar/Wind Harmer
4.295
970937AG2-583 GEN
Solar/Wind Harmer
4.908
316322AB2-045
Solar/Wind Harmer
0.229
3146776BUCKING
Solar/Wind Harmer
-0.003
316192AB2-158 GEN
Solar/Wind Helper
5.116
3147666LOUISA
Solar/Wind Helper
2.947
3151771S ANNAG1
50/50
1.913
3151801S ANNAS2
50/50
0.983
3151761LOISA E
50/50
74.355
972183AH1-676 GEN
50/50
587.912
3132273ORANGE
Solar/Wind Harmer
-0.007
316170AC1-121 GEN2
Solar/Wind Harmer
0.425
970221AG2-151 GEN
Solar/Wind Harmer
5.499
3148013FISHERV
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Harmer
-0.002
3147666LOUISA
Solar/Wind Helper
1.694
3151731LOISA B
50/50
36.472
3151721LOISA A
50/50
36.283
966001AG1-469 GEN
Solar/Wind Harmer
1.011
315651AD1-115 GEN
Solar/Wind Harmer
5.746
971489AH1-241 GEN
Solar/Wind Harmer
5.221
315821AE2-092 GEN
Solar/Wind Harmer
1.803
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
316164AC1-076 GEN
Solar/Wind Harmer
0.884
972205AH1-687 GEN
Adder
3.428
971447AH1-217 GEN
Solar/Wind Harmer
3.143
3148133STUARTS
Solar/Wind Harmer
-0.005
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
1.902
971845AH1-439 GEN
Solar/Wind Harmer
3.536
970285AG2-188 GEN
Solar/Wind Harmer
5.568
LAGNLTFEXP_LAGN->PJM
CLTF
1.059
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.552
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.053
MECLTFEXP_MEC->PJM
CLTF
0.818
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.306
TVALTFEXP_TVA->PJM
CLTF
0.553
SIGELTFEXP_SIGE->PJM
CLTF
0.027
NYPJM->LTFIMP_NY
CLTF
0.38
LGEELTFEXP_LGEE->PJM
CLTF
0.355
WECLTFEXP_WEC->PJM
CLTF
0.18
CPLELTFEXP_CPLE->PJM
CLTF
0.308
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.881

Details for 6S ANNA-6DESPER 230.0 kV Ckt 1 line l/o DVP_P2-2: GERMANNA_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6S ANNA-6DESPER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: GERMANNA_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:128.93 %
Rating:1003.0 MVA
Rating Type:C
MVA to Mitigate:1293.13
MW Contribution:5.5
Bus #Bus NameTypeMW Contribution
3151731LOISA B
50/50
36.472
3151721LOISA A
50/50
36.283
966001AG1-469 GEN
Solar/Wind Harmer
1.011
315651AD1-115 GEN
Solar/Wind Harmer
5.746
971489AH1-241 GEN
Solar/Wind Harmer
5.221
315821AE2-092 GEN
Solar/Wind Harmer
1.803
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
3147346CASHSCORNER
Solar/Wind Harmer
0.847
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
316164AC1-076 GEN
Solar/Wind Harmer
0.884
972205AH1-687 GEN
Adder
3.428
971447AH1-217 GEN
Solar/Wind Harmer
3.143
3148133STUARTS
Solar/Wind Harmer
-0.005
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
1.902
971845AH1-439 GEN
Solar/Wind Harmer
3.536
970285AG2-188 GEN
Solar/Wind Harmer
5.568
3151771S ANNAG1
50/50
1.913
3151801S ANNAS2
50/50
0.983
3151761LOISA E
50/50
74.355
972183AH1-676 GEN
50/50
587.912
3132273ORANGE
Solar/Wind Harmer
-0.007
316170AC1-121 GEN2
Solar/Wind Harmer
0.425
970221AG2-151 GEN
Solar/Wind Harmer
5.499
3151791S ANNAG2
50/50
1.913
3151781S ANNAS1
50/50
0.983
3151741LOISA C
50/50
1.994
3151751LOISA D
50/50
36.472
316254AC1-120 GEN1
Solar/Wind Harmer
1.276
971377AH1-170 GEN
Solar/Wind Harmer
1.1
3147623JAMES R
Solar/Wind Harmer
0.136
972003AH1-546 GEN
Solar/Wind Harmer
4.295
970937AG2-583 GEN
Solar/Wind Harmer
4.908
316322AB2-045
Solar/Wind Harmer
0.229
3146776BUCKING
Solar/Wind Harmer
-0.003
316192AB2-158 GEN
Solar/Wind Helper
5.116
3147666LOUISA
Solar/Wind Helper
2.947
3148013FISHERV
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Harmer
-0.002
3147666LOUISA
Solar/Wind Helper
1.694
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.552
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.053
MECLTFEXP_MEC->PJM
CLTF
0.818
LAGNLTFEXP_LAGN->PJM
CLTF
1.059
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.306
TVALTFEXP_TVA->PJM
CLTF
0.553
SIGELTFEXP_SIGE->PJM
CLTF
0.027
CPLELTFEXP_CPLE->PJM
CLTF
0.308
NYPJM->LTFIMP_NY
CLTF
0.38
LGEELTFEXP_LGEE->PJM
CLTF
0.355
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.881
WECLTFEXP_WEC->PJM
CLTF
0.18

Details for 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.88 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1203.12
MW Contribution:7.29
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
47.203
3144293JTRSVLE
50/50
1.01
3151591KERR 2
50/50
0.537
3151921BEARGRDN G2
50/50
1.074
316248AF1-058 C
Solar/Wind Harmer
1.794
960061AF2-297 GEN
Solar/Wind Harmer
29.766
316478AD1-087 GEN
Solar/Wind Harmer
4.933
316486AD2-202 GEN
Solar/Wind Harmer
1.445
971683AH1-343 GEN
Solar/Wind Harmer
22.023
970909AG2-566 GEN
Solar/Wind Harmer
3.703
316131AB2-060 GEN
Solar/Wind Harmer
3.921
964241AG1-285 GEN
Solar/Wind Harmer
28.048
315785AD2-033 C
Solar/Wind Harmer
7.977
970257AG2-171 GEN
Solar/Wind Harmer
13.098
959311AF2-222 GEN
Solar/Wind Harmer
36.247
963181AG1-167 GEN
Solar/Wind Harmer
3.151
3147133PAMPLIN
Solar/Wind Harmer
-0.104
971193AH1-056 GEN
Solar/Wind Harmer
20.727
942461AE2-259 GEN
Solar/Wind Harmer
4.793
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.538
970221AG2-151 GEN
Solar/Wind Harmer
7.287
966621AG1-532 GEN
Solar/Wind Harmer
0.168
313506AB2-031 GEN
Solar/Wind Harmer
0.617
316313AB2-026
Solar/Wind Harmer
0.177
316258AE1-075 C
Solar/Wind Harmer
0.159
316405AF2-144 C
Solar/Wind Harmer
0.168
3143336POWHATN
Solar/Wind Harmer
0.661
316283AC2-100 C
Solar/Wind Helper
2.321
3151531CLOVER1
50/50
10.817
3144293JTRSVLE
50/50
1.01
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3147043LAWRENC
50/50
1.438
3151561HALLBR1
50/50
0.348
3151931BEARGRDN S1
50/50
1.386
3151911BEARGRDN G1
50/50
1.074
315687AD1-152 GEN
Solar/Wind Harmer
7.758
316003AC1-222 GEN
Solar/Wind Harmer
5.37
957481AF2-042 GEN
Solar/Wind Harmer
169.864
315693AD1-088 GEN
Solar/Wind Harmer
25.266
962491AG1-098 GEN
Solar/Wind Harmer
33.395
970401AG2-262 GEN
Solar/Wind Harmer
3.255
316237AB2-079_GEN
Solar/Wind Harmer
1.109
970685AG2-442 GEN
Solar/Wind Harmer
29.964
963171AG1-166 GEN
Solar/Wind Harmer
4.201
971563AH1-280 GEN
Solar/Wind Harmer
4.201
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.371
316322AB2-045
Solar/Wind Harmer
0.76
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.88
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.352
971795AH1-408 GEN
Solar/Wind Harmer
10.596
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.538
971377AH1-170 GEN
Solar/Wind Harmer
1.457
3147623JAMES R
Solar/Wind Harmer
0.18
970937AG2-583 GEN
Solar/Wind Harmer
7.58
960081AF2-299 GEN
Solar/Wind Harmer
0.929
316336AC2-165 C
Solar/Wind Harmer
1.333
3143336POWHATN
Solar/Wind Harmer
0.777
3151541CLOVER2
50/50
10.765
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
972205AH1-687 GEN
50/50
5.237
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.767
971967AH1-528 GEN
Solar/Wind Harmer
100.764
970865AG2-541 GEN
Solar/Wind Harmer
19.09
316123AC1-075 GEN
Solar/Wind Harmer
4.175
970165AG2-112 GEN
Solar/Wind Harmer
3.676
970163AG2-111 GEN
Solar/Wind Harmer
3.506
316239AB2-077_GEN
Solar/Wind Harmer
1.109
316238AB2-078_GEN
Solar/Wind Harmer
1.109
971443AH1-215 GEN
Solar/Wind Harmer
6.887
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.754
970681AG2-440 GEN
Solar/Wind Harmer
21.403
946301AF1-294 GEN
Solar/Wind Harmer
8.613
961791AG1-021 GEN
Solar/Wind Harmer
4.201
315657AE1-056 GEN
Solar/Wind Harmer
12.436
970285AG2-188 GEN
Solar/Wind Harmer
21.464
971845AH1-439 GEN
Solar/Wind Harmer
12.355
970831AG2-522 GEN
Solar/Wind Harmer
10.03
971447AH1-217 GEN
Solar/Wind Harmer
3.932
270494AE1-108_GEN
Solar/Wind Harmer
2.515
946281AF1-292 GEN
Solar/Wind Harmer
0.185
316087AB2-174 GEN
Solar/Wind Harmer
1.12
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.372
270457AD2-023 GEN
Solar/Wind Helper
0.904
3152661PLYWOOD A
50/50
1.087
3144293JTRSVLE
50/50
1.01
3144293JTRSVLE
50/50
0.851
970535AG2-341 GEN
50/50
5.156
970099AG2-077 GEN
Solar/Wind Harmer
67.945
970933AG2-581 GEN
Solar/Wind Harmer
50.247
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.651
962561AG1-105 GEN
Solar/Wind Harmer
26.897
971741AH1-377 GEN
Solar/Wind Harmer
48.415
970301AG2-198 GEN
Solar/Wind Harmer
19.501
313527AB2-043 GEN
Solar/Wind Harmer
5.92
970323AG2-213 GEN
Solar/Wind Harmer
17.464
971775AH1-396 GEN
Solar/Wind Harmer
2.487
316034AC1-036 C
Solar/Wind Harmer
0.648
958211AF2-115 GEN
Solar/Wind Harmer
5.252
963191AG1-168 GEN
Solar/Wind Harmer
3.151
942751AE2-291 GEN
Solar/Wind Harmer
21.312
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.148
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.964
316197AC1-042 GEN
Solar/Wind Harmer
1.489
942671AE2-283 GEN
Solar/Wind Harmer
4.009
971489AH1-241 GEN
Solar/Wind Harmer
6.918
315821AE2-092 GEN
Solar/Wind Harmer
1.803
316181AB2-040 GEN
Solar/Wind Harmer
1.071
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.79
3145593CAROLNA
Solar/Wind Harmer
0.058
316222AC1-221 GEN
Solar/Wind Helper
2.556
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.834
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.63
VTFLTFEXP_VFT->PJM
CMTX
1.304
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.8
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.891
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.495
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.478
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.359

Details for 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.72 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1179.24
MW Contribution:7.31
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
47.114
3144293JTRSVLE
50/50
1.009
3151591KERR 2
50/50
0.536
3151921BEARGRDN G2
50/50
1.077
316248AF1-058 C
Solar/Wind Harmer
1.79
960061AF2-297 GEN
Solar/Wind Harmer
29.705
316478AD1-087 GEN
Solar/Wind Harmer
4.923
316486AD2-202 GEN
Solar/Wind Harmer
1.442
971683AH1-343 GEN
Solar/Wind Harmer
21.974
970909AG2-566 GEN
Solar/Wind Harmer
3.698
316131AB2-060 GEN
Solar/Wind Harmer
3.913
964241AG1-285 GEN
Solar/Wind Harmer
27.993
315785AD2-033 C
Solar/Wind Harmer
7.962
970257AG2-171 GEN
Solar/Wind Harmer
13.074
959311AF2-222 GEN
Solar/Wind Harmer
36.183
963181AG1-167 GEN
Solar/Wind Harmer
3.146
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.696
942461AE2-259 GEN
Solar/Wind Harmer
4.788
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.511
970221AG2-151 GEN
Solar/Wind Harmer
7.306
966621AG1-532 GEN
Solar/Wind Harmer
0.168
313506AB2-031 GEN
Solar/Wind Harmer
0.617
316313AB2-026
Solar/Wind Harmer
0.179
316258AE1-075 C
Solar/Wind Harmer
0.161
316405AF2-144 C
Solar/Wind Harmer
0.17
3143336POWHATN
Solar/Wind Harmer
0.67
3151531CLOVER1
50/50
10.796
3144293JTRSVLE
50/50
1.009
3151601KERR 3
50/50
0.536
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.437
3151561HALLBR1
50/50
0.346
3151931BEARGRDN S1
50/50
1.389
3151911BEARGRDN G1
50/50
1.077
315687AD1-152 GEN
Solar/Wind Harmer
7.743
316003AC1-222 GEN
Solar/Wind Harmer
5.358
957481AF2-042 GEN
Solar/Wind Harmer
169.548
315693AD1-088 GEN
Solar/Wind Harmer
25.22
962491AG1-098 GEN
Solar/Wind Harmer
33.335
970401AG2-262 GEN
Solar/Wind Harmer
3.248
316237AB2-079_GEN
Solar/Wind Harmer
1.106
970685AG2-442 GEN
Solar/Wind Harmer
29.914
963171AG1-166 GEN
Solar/Wind Harmer
4.195
971563AH1-280 GEN
Solar/Wind Harmer
4.195
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.337
316322AB2-045
Solar/Wind Harmer
0.76
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.875
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.366
971795AH1-408 GEN
Solar/Wind Harmer
10.594
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.511
971377AH1-170 GEN
Solar/Wind Harmer
1.461
3147623JAMES R
Solar/Wind Harmer
0.181
970937AG2-583 GEN
Solar/Wind Harmer
7.619
960081AF2-299 GEN
Solar/Wind Harmer
0.931
316336AC2-165 C
Solar/Wind Harmer
1.347
3143336POWHATN
Solar/Wind Harmer
0.788
3151541CLOVER2
50/50
10.745
3151611KERR 4
50/50
0.536
3151621KERR 5
50/50
0.536
3151631KERR 6
50/50
0.536
3151641KERR 7
50/50
0.536
972205AH1-687 GEN
50/50
5.251
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.759
971967AH1-528 GEN
Solar/Wind Harmer
100.577
970865AG2-541 GEN
Solar/Wind Harmer
19.046
316123AC1-075 GEN
Solar/Wind Harmer
4.164
970165AG2-112 GEN
Solar/Wind Harmer
3.666
970163AG2-111 GEN
Solar/Wind Harmer
3.497
316239AB2-077_GEN
Solar/Wind Harmer
1.106
316238AB2-078_GEN
Solar/Wind Harmer
1.106
971443AH1-215 GEN
Solar/Wind Harmer
6.874
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.709
970681AG2-440 GEN
Solar/Wind Harmer
21.367
946301AF1-294 GEN
Solar/Wind Harmer
8.599
961791AG1-021 GEN
Solar/Wind Harmer
4.195
315657AE1-056 GEN
Solar/Wind Harmer
12.418
970285AG2-188 GEN
Solar/Wind Harmer
21.458
971845AH1-439 GEN
Solar/Wind Harmer
12.354
970831AG2-522 GEN
Solar/Wind Harmer
10.001
971447AH1-217 GEN
Solar/Wind Harmer
3.943
270494AE1-108_GEN
Solar/Wind Harmer
2.518
946281AF1-292 GEN
Solar/Wind Harmer
0.185
316087AB2-174 GEN
Solar/Wind Harmer
1.121
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.392
270457AD2-023 GEN
Solar/Wind Helper
0.917
3152661PLYWOOD A
50/50
1.084
3144293JTRSVLE
50/50
1.009
3144293JTRSVLE
50/50
0.85
970535AG2-341 GEN
50/50
5.143
970099AG2-077 GEN
Solar/Wind Harmer
67.819
970933AG2-581 GEN
Solar/Wind Harmer
50.154
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.629
962561AG1-105 GEN
Solar/Wind Harmer
26.841
971741AH1-377 GEN
Solar/Wind Harmer
48.342
970301AG2-198 GEN
Solar/Wind Harmer
19.474
313527AB2-043 GEN
Solar/Wind Harmer
5.908
970323AG2-213 GEN
Solar/Wind Harmer
17.432
971775AH1-396 GEN
Solar/Wind Harmer
2.482
316034AC1-036 C
Solar/Wind Harmer
0.646
958211AF2-115 GEN
Solar/Wind Harmer
5.244
963191AG1-168 GEN
Solar/Wind Harmer
3.146
942751AE2-291 GEN
Solar/Wind Harmer
21.251
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.099
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.952
316197AC1-042 GEN
Solar/Wind Harmer
1.48
942671AE2-283 GEN
Solar/Wind Harmer
3.984
971489AH1-241 GEN
Solar/Wind Harmer
6.936
315821AE2-092 GEN
Solar/Wind Harmer
1.81
316181AB2-040 GEN
Solar/Wind Harmer
1.071
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.789
3145593CAROLNA
Solar/Wind Harmer
0.058
316222AC1-221 GEN
Solar/Wind Helper
2.576
316283AC2-100 C
Solar/Wind Helper
2.34
270018AE2-047 C O1
Solar/Wind Helper
0.398
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.854
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.69
VTFLTFEXP_VFT->PJM
CMTX
1.552
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.847
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.009
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.588
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.64
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.461

Details for 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.7 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1179.05
MW Contribution:7.31
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.745
3151611KERR 4
50/50
0.536
3151621KERR 5
50/50
0.536
3151631KERR 6
50/50
0.536
3151641KERR 7
50/50
0.536
972205AH1-687 GEN
50/50
5.251
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.759
971967AH1-528 GEN
Solar/Wind Harmer
100.577
970865AG2-541 GEN
Solar/Wind Harmer
19.046
316123AC1-075 GEN
Solar/Wind Harmer
4.164
970165AG2-112 GEN
Solar/Wind Harmer
3.666
970163AG2-111 GEN
Solar/Wind Harmer
3.497
316239AB2-077_GEN
Solar/Wind Harmer
1.106
316238AB2-078_GEN
Solar/Wind Harmer
1.106
971443AH1-215 GEN
Solar/Wind Harmer
6.874
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.709
970681AG2-440 GEN
Solar/Wind Harmer
21.367
946301AF1-294 GEN
Solar/Wind Harmer
8.599
961791AG1-021 GEN
Solar/Wind Harmer
4.195
315657AE1-056 GEN
Solar/Wind Harmer
12.418
970285AG2-188 GEN
Solar/Wind Harmer
21.458
971845AH1-439 GEN
Solar/Wind Harmer
12.354
970831AG2-522 GEN
Solar/Wind Harmer
10.001
971447AH1-217 GEN
Solar/Wind Harmer
3.943
270494AE1-108_GEN
Solar/Wind Harmer
2.518
946281AF1-292 GEN
Solar/Wind Harmer
0.185
316087AB2-174 GEN
Solar/Wind Harmer
1.121
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.392
270457AD2-023 GEN
Solar/Wind Helper
0.917
970413AG2-270 GEN
50/50
47.114
3144293JTRSVLE
50/50
1.009
3151591KERR 2
50/50
0.536
3151921BEARGRDN G2
50/50
1.077
316248AF1-058 C
Solar/Wind Harmer
1.79
960061AF2-297 GEN
Solar/Wind Harmer
29.705
316478AD1-087 GEN
Solar/Wind Harmer
4.923
316486AD2-202 GEN
Solar/Wind Harmer
1.442
971683AH1-343 GEN
Solar/Wind Harmer
21.974
970909AG2-566 GEN
Solar/Wind Harmer
3.698
316131AB2-060 GEN
Solar/Wind Harmer
3.913
964241AG1-285 GEN
Solar/Wind Harmer
27.993
315785AD2-033 C
Solar/Wind Harmer
7.962
970257AG2-171 GEN
Solar/Wind Harmer
13.074
959311AF2-222 GEN
Solar/Wind Harmer
36.183
963181AG1-167 GEN
Solar/Wind Harmer
3.146
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.696
942461AE2-259 GEN
Solar/Wind Harmer
4.788
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.511
970221AG2-151 GEN
Solar/Wind Harmer
7.306
966621AG1-532 GEN
Solar/Wind Harmer
0.168
313506AB2-031 GEN
Solar/Wind Harmer
0.617
316313AB2-026
Solar/Wind Harmer
0.179
316258AE1-075 C
Solar/Wind Harmer
0.161
316405AF2-144 C
Solar/Wind Harmer
0.17
3151531CLOVER1
50/50
10.796
3144293JTRSVLE
50/50
1.009
3151601KERR 3
50/50
0.536
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.437
3151561HALLBR1
50/50
0.346
3151931BEARGRDN S1
50/50
1.389
3151911BEARGRDN G1
50/50
1.077
315687AD1-152 GEN
Solar/Wind Harmer
7.743
316003AC1-222 GEN
Solar/Wind Harmer
5.358
957481AF2-042 GEN
Solar/Wind Harmer
169.548
315693AD1-088 GEN
Solar/Wind Harmer
25.22
962491AG1-098 GEN
Solar/Wind Harmer
33.335
970401AG2-262 GEN
Solar/Wind Harmer
3.248
316237AB2-079_GEN
Solar/Wind Harmer
1.106
970685AG2-442 GEN
Solar/Wind Harmer
29.914
963171AG1-166 GEN
Solar/Wind Harmer
4.195
971563AH1-280 GEN
Solar/Wind Harmer
4.195
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.337
316322AB2-045
Solar/Wind Harmer
0.76
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.875
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.366
971795AH1-408 GEN
Solar/Wind Harmer
10.594
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.511
971377AH1-170 GEN
Solar/Wind Harmer
1.461
3147623JAMES R
Solar/Wind Harmer
0.181
970937AG2-583 GEN
Solar/Wind Harmer
7.619
960081AF2-299 GEN
Solar/Wind Harmer
0.931
316336AC2-165 C
Solar/Wind Harmer
1.347
3143336POWHATN
Solar/Wind Harmer
0.788
3152661PLYWOOD A
50/50
1.084
3144293JTRSVLE
50/50
1.009
3144293JTRSVLE
50/50
0.85
970535AG2-341 GEN
50/50
5.143
970099AG2-077 GEN
Solar/Wind Harmer
67.819
970933AG2-581 GEN
Solar/Wind Harmer
50.154
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.629
962561AG1-105 GEN
Solar/Wind Harmer
26.841
971741AH1-377 GEN
Solar/Wind Harmer
48.342
970301AG2-198 GEN
Solar/Wind Harmer
19.474
313527AB2-043 GEN
Solar/Wind Harmer
5.908
970323AG2-213 GEN
Solar/Wind Harmer
17.432
971775AH1-396 GEN
Solar/Wind Harmer
2.482
316034AC1-036 C
Solar/Wind Harmer
0.646
958211AF2-115 GEN
Solar/Wind Harmer
5.244
963191AG1-168 GEN
Solar/Wind Harmer
3.146
942751AE2-291 GEN
Solar/Wind Harmer
21.251
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.099
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.952
316197AC1-042 GEN
Solar/Wind Harmer
1.48
942671AE2-283 GEN
Solar/Wind Harmer
3.984
971489AH1-241 GEN
Solar/Wind Harmer
6.936
315821AE2-092 GEN
Solar/Wind Harmer
1.81
316181AB2-040 GEN
Solar/Wind Harmer
1.071
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.789
3145593CAROLNA
Solar/Wind Harmer
0.058
316222AC1-221 GEN
Solar/Wind Helper
2.576
3143336POWHATN
Solar/Wind Harmer
0.67
316283AC2-100 C
Solar/Wind Helper
2.34
270018AE2-047 C O1
Solar/Wind Helper
0.398
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.854
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.69
VTFLTFEXP_VFT->PJM
CMTX
1.552
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.847
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.009
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.588
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.64
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.461

Details for 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.45 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1154.15
MW Contribution:7.19
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
10.918
3144293JTRSVLE
50/50
1.004
3151601KERR 3
50/50
0.536
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.435
3151561HALLBR1
50/50
0.35
3151931BEARGRDN S1
50/50
1.368
3151911BEARGRDN G1
50/50
1.06
315687AD1-152 GEN
Solar/Wind Harmer
7.81
957481AF2-042 GEN
Solar/Wind Harmer
173.007
316003AC1-222 GEN
Solar/Wind Harmer
5.389
970401AG2-262 GEN
Solar/Wind Harmer
3.261
315693AD1-088 GEN
Solar/Wind Harmer
24.89
962491AG1-098 GEN
Solar/Wind Harmer
32.899
316237AB2-079_GEN
Solar/Wind Harmer
1.107
970685AG2-442 GEN
Solar/Wind Harmer
29.8
963171AG1-166 GEN
Solar/Wind Harmer
4.173
971563AH1-280 GEN
Solar/Wind Harmer
4.173
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.345
316322AB2-045
Solar/Wind Harmer
0.75
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.876
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.257
971795AH1-408 GEN
Solar/Wind Harmer
10.577
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.561
971377AH1-170 GEN
Solar/Wind Harmer
1.439
3147623JAMES R
Solar/Wind Harmer
0.178
970937AG2-583 GEN
Solar/Wind Harmer
7.48
960081AF2-299 GEN
Solar/Wind Harmer
0.928
316336AC2-165 C
Solar/Wind Harmer
1.315
3143336POWHATN
Solar/Wind Harmer
0.767
3151541CLOVER2
50/50
10.866
3151611KERR 4
50/50
0.536
3151621KERR 5
50/50
0.536
3151631KERR 6
50/50
0.536
3151641KERR 7
50/50
0.536
972205AH1-687 GEN
50/50
5.169
3147173SINAI
Solar/Wind Harmer
-0.06
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.778
970865AG2-541 GEN
Solar/Wind Harmer
19.161
316123AC1-075 GEN
Solar/Wind Harmer
4.191
970165AG2-112 GEN
Solar/Wind Harmer
3.69
970163AG2-111 GEN
Solar/Wind Harmer
3.52
316239AB2-077_GEN
Solar/Wind Harmer
1.107
316238AB2-078_GEN
Solar/Wind Harmer
1.107
971443AH1-215 GEN
Solar/Wind Harmer
6.858
3152661PLYWOOD A
50/50
1.09
3144293JTRSVLE
50/50
1.004
3144293JTRSVLE
50/50
0.845
970535AG2-341 GEN
50/50
5.145
970099AG2-077 GEN
Solar/Wind Harmer
69.203
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.672
962561AG1-105 GEN
Solar/Wind Harmer
26.937
971741AH1-377 GEN
Solar/Wind Harmer
47.726
970301AG2-198 GEN
Solar/Wind Harmer
19.228
313527AB2-043 GEN
Solar/Wind Harmer
5.909
970323AG2-213 GEN
Solar/Wind Harmer
17.388
971775AH1-396 GEN
Solar/Wind Harmer
2.476
316034AC1-036 C
Solar/Wind Harmer
0.645
942751AE2-291 GEN
Solar/Wind Harmer
21.395
958211AF2-115 GEN
Solar/Wind Harmer
5.217
963191AG1-168 GEN
Solar/Wind Harmer
3.13
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.11
3146776BUCKING
Solar/Wind Harmer
-0.089
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.974
316197AC1-042 GEN
Solar/Wind Harmer
1.496
942671AE2-283 GEN
Solar/Wind Harmer
4.029
971489AH1-241 GEN
Solar/Wind Harmer
6.83
315821AE2-092 GEN
Solar/Wind Harmer
1.78
316181AB2-040 GEN
Solar/Wind Harmer
1.069
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.789
3145593CAROLNA
Solar/Wind Harmer
0.058
316222AC1-221 GEN
Solar/Wind Helper
2.541
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.607
970681AG2-440 GEN
Solar/Wind Harmer
21.285
946301AF1-294 GEN
Solar/Wind Harmer
8.556
961791AG1-021 GEN
Solar/Wind Harmer
4.173
315657AE1-056 GEN
Solar/Wind Harmer
12.343
970285AG2-188 GEN
Solar/Wind Harmer
21.187
971845AH1-439 GEN
Solar/Wind Harmer
12.195
970831AG2-522 GEN
Solar/Wind Harmer
10.008
971447AH1-217 GEN
Solar/Wind Harmer
3.882
270494AE1-108_GEN
Solar/Wind Harmer
2.486
946281AF1-292 GEN
Solar/Wind Harmer
0.185
316087AB2-174 GEN
Solar/Wind Harmer
1.118
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.363
270457AD2-023 GEN
Solar/Wind Helper
0.898
970413AG2-270 GEN
50/50
47.647
3144293JTRSVLE
50/50
1.004
3151591KERR 2
50/50
0.536
3151921BEARGRDN G2
50/50
1.06
316248AF1-058 C
Solar/Wind Harmer
1.8
960061AF2-297 GEN
Solar/Wind Harmer
29.874
316478AD1-087 GEN
Solar/Wind Harmer
4.979
316486AD2-202 GEN
Solar/Wind Harmer
1.458
971683AH1-343 GEN
Solar/Wind Harmer
22.104
970909AG2-566 GEN
Solar/Wind Harmer
3.651
316131AB2-060 GEN
Solar/Wind Harmer
3.913
964241AG1-285 GEN
Solar/Wind Harmer
27.972
315785AD2-033 C
Solar/Wind Harmer
7.946
970257AG2-171 GEN
Solar/Wind Harmer
13.041
959311AF2-222 GEN
Solar/Wind Harmer
36.078
963181AG1-167 GEN
Solar/Wind Harmer
3.13
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.572
942461AE2-259 GEN
Solar/Wind Harmer
4.746
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.561
970221AG2-151 GEN
Solar/Wind Harmer
7.194
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.616
316313AB2-026
Solar/Wind Harmer
0.174
316258AE1-075 C
Solar/Wind Harmer
0.157
316405AF2-144 C
Solar/Wind Harmer
0.166
3143336POWHATN
Solar/Wind Harmer
0.652
316283AC2-100 C
Solar/Wind Helper
2.307
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.83
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.615
VTFLTFEXP_VFT->PJM
CMTX
1.248
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.788
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.862
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.474
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.441
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.337

Details for 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.44 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1154.09
MW Contribution:7.2
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.865
3151611KERR 4
50/50
0.536
3151531CLOVER1
50/50
10.918
3144293JTRSVLE
50/50
1.004
3151601KERR 3
50/50
0.536
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.436
3151561HALLBR1
50/50
0.35
3151931BEARGRDN S1
50/50
1.368
3151911BEARGRDN G1
50/50
1.06
315687AD1-152 GEN
Solar/Wind Harmer
7.809
957481AF2-042 GEN
Solar/Wind Harmer
172.984
316003AC1-222 GEN
Solar/Wind Harmer
5.389
970401AG2-262 GEN
Solar/Wind Harmer
3.261
315693AD1-088 GEN
Solar/Wind Harmer
24.893
962491AG1-098 GEN
Solar/Wind Harmer
32.903
316237AB2-079_GEN
Solar/Wind Harmer
1.107
970685AG2-442 GEN
Solar/Wind Harmer
29.801
963171AG1-166 GEN
Solar/Wind Harmer
4.174
971563AH1-280 GEN
Solar/Wind Harmer
4.174
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.345
316322AB2-045
Solar/Wind Harmer
0.75
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.876
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.258
971795AH1-408 GEN
Solar/Wind Harmer
10.578
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.561
971377AH1-170 GEN
Solar/Wind Harmer
1.439
3147623JAMES R
Solar/Wind Harmer
0.178
970937AG2-583 GEN
Solar/Wind Harmer
7.481
960081AF2-299 GEN
Solar/Wind Harmer
0.928
316336AC2-165 C
Solar/Wind Harmer
1.315
3143336POWHATN
Solar/Wind Harmer
0.767
3151621KERR 5
50/50
0.536
3151631KERR 6
50/50
0.536
3151641KERR 7
50/50
0.536
972205AH1-687 GEN
50/50
5.17
3147173SINAI
Solar/Wind Harmer
-0.06
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.778
970865AG2-541 GEN
Solar/Wind Harmer
19.161
316123AC1-075 GEN
Solar/Wind Harmer
4.19
970165AG2-112 GEN
Solar/Wind Harmer
3.69
970163AG2-111 GEN
Solar/Wind Harmer
3.52
316239AB2-077_GEN
Solar/Wind Harmer
1.107
316238AB2-078_GEN
Solar/Wind Harmer
1.107
971443AH1-215 GEN
Solar/Wind Harmer
6.858
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.608
970681AG2-440 GEN
Solar/Wind Harmer
21.286
946301AF1-294 GEN
Solar/Wind Harmer
8.556
961791AG1-021 GEN
Solar/Wind Harmer
4.174
315657AE1-056 GEN
Solar/Wind Harmer
12.344
970285AG2-188 GEN
Solar/Wind Harmer
21.189
971845AH1-439 GEN
Solar/Wind Harmer
12.197
970831AG2-522 GEN
Solar/Wind Harmer
10.008
971447AH1-217 GEN
Solar/Wind Harmer
3.882
270494AE1-108_GEN
Solar/Wind Harmer
2.486
946281AF1-292 GEN
Solar/Wind Harmer
0.185
316087AB2-174 GEN
Solar/Wind Harmer
1.118
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.363
270457AD2-023 GEN
Solar/Wind Helper
0.898
3152661PLYWOOD A
50/50
1.09
3144293JTRSVLE
50/50
1.004
3144293JTRSVLE
50/50
0.845
970535AG2-341 GEN
50/50
5.145
970099AG2-077 GEN
Solar/Wind Harmer
69.194
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.672
962561AG1-105 GEN
Solar/Wind Harmer
26.937
971741AH1-377 GEN
Solar/Wind Harmer
47.731
970301AG2-198 GEN
Solar/Wind Harmer
19.23
313527AB2-043 GEN
Solar/Wind Harmer
5.909
970323AG2-213 GEN
Solar/Wind Harmer
17.389
971775AH1-396 GEN
Solar/Wind Harmer
2.476
316034AC1-036 C
Solar/Wind Harmer
0.645
942751AE2-291 GEN
Solar/Wind Harmer
21.394
958211AF2-115 GEN
Solar/Wind Harmer
5.217
963191AG1-168 GEN
Solar/Wind Harmer
3.13
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.11
3146776BUCKING
Solar/Wind Harmer
-0.089
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.974
316197AC1-042 GEN
Solar/Wind Harmer
1.496
942671AE2-283 GEN
Solar/Wind Harmer
4.029
971489AH1-241 GEN
Solar/Wind Harmer
6.83
315821AE2-092 GEN
Solar/Wind Harmer
1.78
316181AB2-040 GEN
Solar/Wind Harmer
1.069
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.789
3145593CAROLNA
Solar/Wind Harmer
0.058
316222AC1-221 GEN
Solar/Wind Helper
2.541
970413AG2-270 GEN
50/50
47.644
3144293JTRSVLE
50/50
1.004
3151591KERR 2
50/50
0.536
3151921BEARGRDN G2
50/50
1.06
316248AF1-058 C
Solar/Wind Harmer
1.8
960061AF2-297 GEN
Solar/Wind Harmer
29.873
316478AD1-087 GEN
Solar/Wind Harmer
4.978
316486AD2-202 GEN
Solar/Wind Harmer
1.458
971683AH1-343 GEN
Solar/Wind Harmer
22.104
970909AG2-566 GEN
Solar/Wind Harmer
3.651
316131AB2-060 GEN
Solar/Wind Harmer
3.913
964241AG1-285 GEN
Solar/Wind Harmer
27.973
315785AD2-033 C
Solar/Wind Harmer
7.946
970257AG2-171 GEN
Solar/Wind Harmer
13.042
959311AF2-222 GEN
Solar/Wind Harmer
36.079
963181AG1-167 GEN
Solar/Wind Harmer
3.13
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.573
942461AE2-259 GEN
Solar/Wind Harmer
4.746
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.561
970221AG2-151 GEN
Solar/Wind Harmer
7.195
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.616
316313AB2-026
Solar/Wind Harmer
0.174
316258AE1-075 C
Solar/Wind Harmer
0.157
316405AF2-144 C
Solar/Wind Harmer
0.166
3143336POWHATN
Solar/Wind Harmer
0.652
316283AC2-100 C
Solar/Wind Helper
2.307
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.83
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.615
VTFLTFEXP_VFT->PJM
CMTX
1.249
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.788
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.862
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.475
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.441
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.337

Details for 6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2199_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2199_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:147.08 %
Rating:819.68 MVA
Rating Type:B
MVA to Mitigate:1205.62
MW Contribution:4.15
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
3.614
3147346CASHSCORNER
Solar/Wind Harmer
1.128
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3138266HYDRAULIC
Solar/Wind Harmer
0.004
316164AC1-076 GEN
Solar/Wind Harmer
0.13
971447AH1-217 GEN
Solar/Wind Harmer
2.371
3148133STUARTS
Solar/Wind Harmer
0.044
3148013FISHERV
Solar/Wind Harmer
0.042
270494AE1-108_GEN
Solar/Wind Harmer
0.774
971845AH1-439 GEN
Solar/Wind Harmer
2.662
971133AH1-012 GEN
50/50
15.027
3151731LOISA B
50/50
36.435
3151721LOISA A
50/50
36.247
966001AG1-469 GEN
Solar/Wind Harmer
0.277
315651AD1-115 GEN
Solar/Wind Harmer
0.004
971489AH1-241 GEN
Solar/Wind Harmer
4.148
315821AE2-092 GEN
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.24
3146776BUCKING
Solar/Wind Harmer
0.019
3151771S ANNAG1
50/50
1.911
3151801S ANNAS2
50/50
0.982
3151761LOISA E
50/50
74.281
972183AH1-676 GEN
50/50
587.315
3151921BEARGRDN G2
50/50
0.741
3147666LOUISA
Solar/Wind Harmer
1.729
3132273ORANGE
Solar/Wind Harmer
0.067
316170AC1-121 GEN2
Solar/Wind Harmer
0.15
970221AG2-151 GEN
Solar/Wind Harmer
4.148
3148013FISHERV
Solar/Wind Harmer
0.074
3146776BUCKING
Solar/Wind Harmer
0.022
3151791S ANNAG2
50/50
1.911
3151781S ANNAS1
50/50
0.982
3151741LOISA C
50/50
1.992
3151751LOISA D
50/50
36.435
3151931BEARGRDN S1
50/50
0.956
3151911BEARGRDN G1
50/50
0.741
3147666LOUISA
Solar/Wind Harmer
3.006
316192AB2-158 GEN
Solar/Wind Harmer
4.18
315683AE1-153 C
Solar/Wind Harmer
41.15
316254AC1-120 GEN1
Solar/Wind Harmer
0.299
971377AH1-170 GEN
Solar/Wind Harmer
0.83
3147623JAMES R
Solar/Wind Harmer
0.18
972003AH1-546 GEN
Solar/Wind Harmer
3.234
970937AG2-583 GEN
Solar/Wind Harmer
3.695
316322AB2-045
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.024
LAGNLTFEXP_LAGN->PJM
CLTF
0.977
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.963
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.899
MECLTFEXP_MEC->PJM
CLTF
0.75
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.184
TVALTFEXP_TVA->PJM
CLTF
0.512
NYPJM->LTFIMP_NY
CLTF
0.406
LGEELTFEXP_LGEE->PJM
CLTF
0.327
WECLTFEXP_WEC->PJM
CLTF
0.165
CPLELTFEXP_CPLE->PJM
CLTF
0.264
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.337

Details for 6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:143.73 %
Rating:1003.0 MVA
Rating Type:C
MVA to Mitigate:1441.58
MW Contribution:6.3
Bus #Bus NameTypeMW Contribution
3147346CASHSCORNER
Solar/Wind Harmer
0.957
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
972205AH1-687 GEN
Adder
3.933
971447AH1-217 GEN
Solar/Wind Harmer
3.598
3148133STUARTS
Solar/Wind Harmer
-0.006
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
2.18
971845AH1-439 GEN
Solar/Wind Harmer
4.09
970285AG2-188 GEN
Solar/Wind Harmer
6.451
3151771S ANNAG1
50/50
2.136
3151801S ANNAS2
50/50
1.098
3151761LOISA E
50/50
83.586
972183AH1-676 GEN
50/50
663.972
3147666LOUISA
Solar/Wind Harmer
-0.203
970221AG2-151 GEN
Solar/Wind Harmer
6.301
3148013FISHERV
Solar/Wind Harmer
-0.009
3146776BUCKING
Solar/Wind Harmer
-0.003
316499AE2-029_GEN
Solar/Wind Harmer
0.518
971133AH1-012 GEN
50/50
15.525
3151731LOISA B
50/50
41
3151721LOISA A
50/50
40.788
966001AG1-469 GEN
Solar/Wind Harmer
1.242
971489AH1-241 GEN
Solar/Wind Harmer
5.982
315821AE2-092 GEN
Solar/Wind Harmer
2.06
3146776BUCKING
Solar/Wind Harmer
-0.031
3146776BUCKING
Solar/Wind Harmer
-0.003
3151791S ANNAG2
50/50
2.136
3151781S ANNAS1
50/50
1.098
3151741LOISA C
50/50
2.242
3151751LOISA D
50/50
41
3147666LOUISA
Solar/Wind Harmer
-0.354
316192AB2-158 GEN
Solar/Wind Harmer
10.429
315683AE1-153 C
Solar/Wind Harmer
61.252
971377AH1-170 GEN
Solar/Wind Harmer
1.26
3147623JAMES R
Solar/Wind Harmer
0.156
972003AH1-546 GEN
Solar/Wind Harmer
4.933
970937AG2-583 GEN
Solar/Wind Harmer
5.684
316322AB2-045
Solar/Wind Harmer
0.265
3146776BUCKING
Solar/Wind Harmer
-0.003
315705AF1-075 GEN
Solar/Wind Harmer
2.892
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.172
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.363
MECLTFEXP_MEC->PJM
CLTF
0.912
LAGNLTFEXP_LAGN->PJM
CLTF
1.228
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.694
TVALTFEXP_TVA->PJM
CLTF
0.641
SIGELTFEXP_SIGE->PJM
CLTF
0.03
CPLELTFEXP_CPLE->PJM
CLTF
0.459
NYPJM->LTFIMP_NY
CLTF
0.489
LGEELTFEXP_LGEE->PJM
CLTF
0.394
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.833
WECLTFEXP_WEC->PJM
CLTF
0.198

Details for 6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2331_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2331_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:142.35 %
Rating:819.68 MVA
Rating Type:B
MVA to Mitigate:1166.8
MW Contribution:4.15
Bus #Bus NameTypeMW Contribution
3151791S ANNAG2
50/50
1.911
3151781S ANNAS1
50/50
0.982
3151741LOISA C
50/50
1.992
3151751LOISA D
50/50
36.435
3151931BEARGRDN S1
50/50
0.956
3151911BEARGRDN G1
50/50
0.741
3147666LOUISA
Solar/Wind Harmer
3.006
316192AB2-158 GEN
Solar/Wind Harmer
4.18
315683AE1-153 C
Solar/Wind Harmer
41.15
316254AC1-120 GEN1
Solar/Wind Harmer
0.299
971377AH1-170 GEN
Solar/Wind Harmer
0.83
3147623JAMES R
Solar/Wind Harmer
0.18
972003AH1-546 GEN
Solar/Wind Harmer
3.234
970937AG2-583 GEN
Solar/Wind Harmer
3.695
316322AB2-045
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.024
972205AH1-687 GEN
50/50
3.614
3147346CASHSCORNER
Solar/Wind Harmer
1.128
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3138266HYDRAULIC
Solar/Wind Harmer
0.004
316164AC1-076 GEN
Solar/Wind Harmer
0.13
971447AH1-217 GEN
Solar/Wind Harmer
2.371
3148133STUARTS
Solar/Wind Harmer
0.044
3148013FISHERV
Solar/Wind Harmer
0.042
270494AE1-108_GEN
Solar/Wind Harmer
0.774
971845AH1-439 GEN
Solar/Wind Harmer
2.662
3151771S ANNAG1
50/50
1.911
3151801S ANNAS2
50/50
0.982
3151761LOISA E
50/50
74.281
972183AH1-676 GEN
50/50
587.315
3151921BEARGRDN G2
50/50
0.741
3147666LOUISA
Solar/Wind Harmer
1.729
3132273ORANGE
Solar/Wind Harmer
0.067
316170AC1-121 GEN2
Solar/Wind Harmer
0.15
970221AG2-151 GEN
Solar/Wind Harmer
4.148
3148013FISHERV
Solar/Wind Harmer
0.074
3146776BUCKING
Solar/Wind Harmer
0.022
971133AH1-012 GEN
50/50
15.027
3151731LOISA B
50/50
36.435
3151721LOISA A
50/50
36.247
966001AG1-469 GEN
Solar/Wind Harmer
0.277
315651AD1-115 GEN
Solar/Wind Harmer
0.004
971489AH1-241 GEN
Solar/Wind Harmer
4.148
315821AE2-092 GEN
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.24
3146776BUCKING
Solar/Wind Harmer
0.019
LAGNLTFEXP_LAGN->PJM
CLTF
0.977
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.963
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.899
MECLTFEXP_MEC->PJM
CLTF
0.75
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.184
TVALTFEXP_TVA->PJM
CLTF
0.512
NYPJM->LTFIMP_NY
CLTF
0.406
LGEELTFEXP_LGEE->PJM
CLTF
0.327
WECLTFEXP_WEC->PJM
CLTF
0.165
CPLELTFEXP_CPLE->PJM
CLTF
0.264
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.337

Details for 6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:137.63 %
Rating:1003.0 MVA
Rating Type:C
MVA to Mitigate:1380.4
MW Contribution:6.3
Bus #Bus NameTypeMW Contribution
3151771S ANNAG1
50/50
2.136
3151801S ANNAS2
50/50
1.098
3151761LOISA E
50/50
83.586
972183AH1-676 GEN
50/50
663.972
3147666LOUISA
Solar/Wind Harmer
-0.203
970221AG2-151 GEN
Solar/Wind Harmer
6.301
3148013FISHERV
Solar/Wind Harmer
-0.009
3146776BUCKING
Solar/Wind Harmer
-0.003
316499AE2-029_GEN
Solar/Wind Harmer
0.518
971133AH1-012 GEN
50/50
15.525
3151731LOISA B
50/50
41
3151721LOISA A
50/50
40.788
966001AG1-469 GEN
Solar/Wind Harmer
1.242
971489AH1-241 GEN
Solar/Wind Harmer
5.982
315821AE2-092 GEN
Solar/Wind Harmer
2.06
3146776BUCKING
Solar/Wind Harmer
-0.031
3146776BUCKING
Solar/Wind Harmer
-0.003
3147346CASHSCORNER
Solar/Wind Harmer
0.957
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
972205AH1-687 GEN
Adder
3.933
971447AH1-217 GEN
Solar/Wind Harmer
3.598
3148133STUARTS
Solar/Wind Harmer
-0.006
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
2.18
971845AH1-439 GEN
Solar/Wind Harmer
4.09
970285AG2-188 GEN
Solar/Wind Harmer
6.451
3151791S ANNAG2
50/50
2.136
3151781S ANNAS1
50/50
1.098
3151741LOISA C
50/50
2.242
3151751LOISA D
50/50
41
3147666LOUISA
Solar/Wind Harmer
-0.354
316192AB2-158 GEN
Solar/Wind Harmer
10.429
971377AH1-170 GEN
Solar/Wind Harmer
1.26
3147623JAMES R
Solar/Wind Harmer
0.156
972003AH1-546 GEN
Solar/Wind Harmer
4.933
970937AG2-583 GEN
Solar/Wind Harmer
5.684
316322AB2-045
Solar/Wind Harmer
0.265
3146776BUCKING
Solar/Wind Harmer
-0.003
315705AF1-075 GEN
Solar/Wind Harmer
2.892
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.172
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.363
MECLTFEXP_MEC->PJM
CLTF
0.912
LAGNLTFEXP_LAGN->PJM
CLTF
1.228
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.694
TVALTFEXP_TVA->PJM
CLTF
0.641
SIGELTFEXP_SIGE->PJM
CLTF
0.03
CPLELTFEXP_CPLE->PJM
CLTF
0.459
NYPJM->LTFIMP_NY
CLTF
0.489
LGEELTFEXP_LGEE->PJM
CLTF
0.394
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.833
WECLTFEXP_WEC->PJM
CLTF
0.198

Details for 6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 2199T2331_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2199T2331_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.83 %
Rating:1003.0 MVA
Rating Type:C
MVA to Mitigate:1231.96
MW Contribution:5.46
Bus #Bus NameTypeMW Contribution
3147346CASHSCORNER
Solar/Wind Harmer
0.846
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
316164AC1-076 GEN
Solar/Wind Harmer
0.879
972205AH1-687 GEN
Adder
3.406
971447AH1-217 GEN
Solar/Wind Harmer
3.122
3148133STUARTS
Solar/Wind Harmer
-0.005
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
1.886
971845AH1-439 GEN
Solar/Wind Harmer
3.505
3151791S ANNAG2
50/50
1.911
3151781S ANNAS1
50/50
0.982
3151741LOISA C
50/50
1.992
3151751LOISA D
50/50
36.435
3147666LOUISA
Solar/Wind Harmer
-0.336
316192AB2-158 GEN
Solar/Wind Harmer
9.884
315683AE1-153 C
Solar/Wind Harmer
54.18
316254AC1-120 GEN1
Solar/Wind Harmer
1.271
971377AH1-170 GEN
Solar/Wind Harmer
1.092
3147623JAMES R
Solar/Wind Harmer
0.135
972003AH1-546 GEN
Solar/Wind Harmer
4.266
970937AG2-583 GEN
Solar/Wind Harmer
4.865
316322AB2-045
Solar/Wind Harmer
0.227
3146776BUCKING
Solar/Wind Harmer
-0.003
3151771S ANNAG1
50/50
1.911
3151801S ANNAS2
50/50
0.982
3151761LOISA E
50/50
74.281
972183AH1-676 GEN
50/50
587.315
3147666LOUISA
Solar/Wind Harmer
-0.193
3132273ORANGE
Solar/Wind Harmer
-0.007
316170AC1-121 GEN2
Solar/Wind Harmer
0.424
970221AG2-151 GEN
Solar/Wind Harmer
5.462
971133AH1-012 GEN
50/50
15.027
3151731LOISA B
50/50
36.435
3151721LOISA A
50/50
36.247
966001AG1-469 GEN
Solar/Wind Harmer
1.01
315651AD1-115 GEN
Solar/Wind Harmer
5.72
971489AH1-241 GEN
Solar/Wind Harmer
5.185
315821AE2-092 GEN
Solar/Wind Harmer
1.791
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
3148013FISHERV
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Harmer
-0.002
LAGNLTFEXP_LAGN->PJM
CLTF
0.977
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.963
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.899
MECLTFEXP_MEC->PJM
CLTF
0.75
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.184
TVALTFEXP_TVA->PJM
CLTF
0.512
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
0.264
NYPJM->LTFIMP_NY
CLTF
0.406
LGEELTFEXP_LGEE->PJM
CLTF
0.327
WECLTFEXP_WEC->PJM
CLTF
0.165
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.337

Details for 6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P4-2: 2278T2331_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2278T2331_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.86 %
Rating:1003.0 MVA
Rating Type:C
MVA to Mitigate:1192.15
MW Contribution:5.46
Bus #Bus NameTypeMW Contribution
3151791S ANNAG2
50/50
1.911
3151781S ANNAS1
50/50
0.982
3151741LOISA C
50/50
1.992
3151751LOISA D
50/50
36.435
3147666LOUISA
Solar/Wind Harmer
-0.336
316192AB2-158 GEN
Solar/Wind Harmer
9.884
315683AE1-153 C
Solar/Wind Harmer
54.18
316254AC1-120 GEN1
Solar/Wind Harmer
1.271
971377AH1-170 GEN
Solar/Wind Harmer
1.092
3147623JAMES R
Solar/Wind Harmer
0.135
972003AH1-546 GEN
Solar/Wind Harmer
4.266
970937AG2-583 GEN
Solar/Wind Harmer
4.865
316322AB2-045
Solar/Wind Harmer
0.227
3146776BUCKING
Solar/Wind Harmer
-0.003
971133AH1-012 GEN
50/50
15.027
3151731LOISA B
50/50
36.435
3151721LOISA A
50/50
36.247
966001AG1-469 GEN
Solar/Wind Harmer
1.01
315651AD1-115 GEN
Solar/Wind Harmer
5.72
971489AH1-241 GEN
Solar/Wind Harmer
5.185
315821AE2-092 GEN
Solar/Wind Harmer
1.791
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
3151771S ANNAG1
50/50
1.911
3151801S ANNAS2
50/50
0.982
3151761LOISA E
50/50
74.281
972183AH1-676 GEN
50/50
587.315
3147666LOUISA
Solar/Wind Harmer
-0.193
3132273ORANGE
Solar/Wind Harmer
-0.007
316170AC1-121 GEN2
Solar/Wind Harmer
0.424
970221AG2-151 GEN
Solar/Wind Harmer
5.462
3148013FISHERV
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Harmer
-0.002
3147346CASHSCORNER
Solar/Wind Harmer
0.846
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
316164AC1-076 GEN
Solar/Wind Harmer
0.879
972205AH1-687 GEN
Adder
3.406
971447AH1-217 GEN
Solar/Wind Harmer
3.122
3148133STUARTS
Solar/Wind Harmer
-0.005
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
1.886
971845AH1-439 GEN
Solar/Wind Harmer
3.505
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.963
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.899
MECLTFEXP_MEC->PJM
CLTF
0.75
LAGNLTFEXP_LAGN->PJM
CLTF
0.977
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.184
TVALTFEXP_TVA->PJM
CLTF
0.512
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
0.264
NYPJM->LTFIMP_NY
CLTF
0.406
LGEELTFEXP_LGEE->PJM
CLTF
0.327
WECLTFEXP_WEC->PJM
CLTF
0.165
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.337

Details for 6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P2-2: GERMANNA_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: GERMANNA_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:117.44 %
Rating:1003.0 MVA
Rating Type:C
MVA to Mitigate:1177.95
MW Contribution:5.46
Bus #Bus NameTypeMW Contribution
3147346CASHSCORNER
Solar/Wind Harmer
0.846
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
316164AC1-076 GEN
Solar/Wind Harmer
0.879
972205AH1-687 GEN
Adder
3.406
971447AH1-217 GEN
Solar/Wind Harmer
3.122
3148133STUARTS
Solar/Wind Harmer
-0.005
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
1.886
971845AH1-439 GEN
Solar/Wind Harmer
3.505
971133AH1-012 GEN
50/50
15.027
3151731LOISA B
50/50
36.435
3151721LOISA A
50/50
36.247
966001AG1-469 GEN
Solar/Wind Harmer
1.01
315651AD1-115 GEN
Solar/Wind Harmer
5.72
971489AH1-241 GEN
Solar/Wind Harmer
5.185
315821AE2-092 GEN
Solar/Wind Harmer
1.791
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
3151771S ANNAG1
50/50
1.911
3151801S ANNAS2
50/50
0.982
3151761LOISA E
50/50
74.281
972183AH1-676 GEN
50/50
587.315
3147666LOUISA
Solar/Wind Harmer
-0.193
3132273ORANGE
Solar/Wind Harmer
-0.007
316170AC1-121 GEN2
Solar/Wind Harmer
0.424
970221AG2-151 GEN
Solar/Wind Harmer
5.462
3148013FISHERV
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Harmer
-0.002
3151791S ANNAG2
50/50
1.911
3151781S ANNAS1
50/50
0.982
3151741LOISA C
50/50
1.992
3151751LOISA D
50/50
36.435
3147666LOUISA
Solar/Wind Harmer
-0.336
316192AB2-158 GEN
Solar/Wind Harmer
9.884
316254AC1-120 GEN1
Solar/Wind Harmer
1.271
971377AH1-170 GEN
Solar/Wind Harmer
1.092
3147623JAMES R
Solar/Wind Harmer
0.135
972003AH1-546 GEN
Solar/Wind Harmer
4.266
970937AG2-583 GEN
Solar/Wind Harmer
4.865
316322AB2-045
Solar/Wind Harmer
0.227
3146776BUCKING
Solar/Wind Harmer
-0.003
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.963
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.899
MECLTFEXP_MEC->PJM
CLTF
0.75
LAGNLTFEXP_LAGN->PJM
CLTF
0.977
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.184
TVALTFEXP_TVA->PJM
CLTF
0.512
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
0.264
NYPJM->LTFIMP_NY
CLTF
0.406
LGEELTFEXP_LGEE->PJM
CLTF
0.327
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.337
WECLTFEXP_WEC->PJM
CLTF
0.165

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o PEPCO_P1_5070_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
PEPCO_P1_5070_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:140.61 %
Rating:1478.62 MVA
Rating Type:B
MVA to Mitigate:2079.09
MW Contribution:3.82
Bus #Bus NameTypeMW Contribution
972289AH1-729 GEN
50/50
13.249
3150091POSSM6B
50/50
0.848
3150071POSSM 5
50/50
52.224
3150181POSSMC2
50/50
1.152
3150181POSSMC2
50/50
1.143
3150181POSSMC2
50/50
1.143
316447AC1-158 HLD
Solar/Wind Harmer
1.014
3150391LDYSMT3
Adder
12.655
972195AH1-682 GEN
Adder
1.663
315651AD1-115 GEN
Solar/Wind Harmer
0.003
315673AE1-157 GEN
Solar/Wind Harmer
6.396
957411AF2-035 GEN
Solar/Wind Harmer
3.895
970317AG2-208 GEN
Solar/Wind Harmer
3.609
316468AD1-105 GEN
Solar/Wind Harmer
-0.029
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.913
3150341NORNECKC1
Adder
0.906
966001AG1-469 GEN
Solar/Wind Harmer
0.051
958261AF2-120 GEN
Solar/Wind Harmer
2.86
3151731LOISA B
Adder
5.599
3151721LOISA A
Adder
5.57
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.271
3142366NRTHEST
Adder
0.276
3150691DARBY 3
Adder
6.069
3150701DARBY 4
Adder
6.055
3150681DARBY 2
Adder
6.048
3150671DARBY 1
Adder
6.041
316075AC2-137 C
Solar/Wind Harmer
0.023
3142946ENON
Solar/Wind Harmer
0.008
3143526WINTERP
Solar/Wind Harmer
0.435
971223AH1-071 GEN
Solar/Wind Harmer
0.89
944641AF1-129 GEN
Adder
39.415
316240AF1-291 C
Solar/Wind Harmer
0.001
316033AB2-134 GEN
Solar/Wind Harmer
0.005
315697AD1-025 GEN
Solar/Wind Harmer
0.092
316236AE1-162_GEN
Solar/Wind Harmer
0.001
970657AG2-426 GEN
Solar/Wind Harmer
2.829
970657AG2-426 GEN
Solar/Wind Harmer
0.593
316036AC1-147 C
Solar/Wind Harmer
0.015
3150991CHESPKB
Adder
0.845
3150991CHESPKB
Adder
0.825
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.077
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3145506HICKORY
Solar/Wind Harmer
0.321
3145506HICKORY
Solar/Wind Harmer
0.193
3145506HICKORY
Solar/Wind Harmer
0.048
316339AD2-160 GEN
Solar/Wind Harmer
0.13
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.045
3137176SLIGO L2192
Solar/Wind Harmer
0.319
3146456SLIGO L269
Solar/Wind Harmer
1.416
3130086AYDLETT
Solar/Wind Harmer
0.32
3146386ELIZ CT
Solar/Wind Harmer
0.08
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.079
3144356SAPONY
Solar/Wind Harmer
0.657
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.345
3146376EDENTON
Solar/Wind Harmer
0.345
972185AH1-677 GEN
Adder
4.331
972187AH1-678 GEN
Adder
2.184
970933AG2-581 GEN
Solar/Wind Harmer
6.107
316065AD1-022 GEN
Solar/Wind Harmer
3.475
3145893MURPHYS
Solar/Wind Harmer
0.503
3145893MURPHYS
Solar/Wind Harmer
0.135
3146173TUNIS
Solar/Wind Harmer
0.075
3146173TUNIS
Solar/Wind Harmer
0.075
970099AG2-077 GEN
Solar/Wind Harmer
7.908
316181AB2-040 GEN
Solar/Wind Harmer
0.107
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.044
971741AH1-377 GEN
Solar/Wind Harmer
7.304
970301AG2-198 GEN
Solar/Wind Harmer
3.138
316426AA2-053 GEN
Solar/Wind Harmer
0.248
3146776BUCKING
Solar/Wind Harmer
0.293
3145593CAROLNA
Solar/Wind Harmer
0.073
3145593CAROLNA
Solar/Wind Harmer
0.073
3146776BUCKING
Solar/Wind Harmer
0.024
966811AG1-552 GEN
Solar/Wind Harmer
0.795
3145593CAROLNA
Solar/Wind Harmer
0.091
3145783HORNRTN
Solar/Wind Harmer
1.299
3145783HORNRTN
Solar/Wind Harmer
1.039
3145783HORNRTN
Solar/Wind Harmer
0.325
3145783HORNRTN
Solar/Wind Harmer
0.13
3145796HORNRTN
Solar/Wind Harmer
0.219
3147133PAMPLIN
Solar/Wind Harmer
0.072
3147133PAMPLIN
Solar/Wind Harmer
0.058
958211AF2-115 GEN
Solar/Wind Harmer
0.866
963191AG1-168 GEN
Solar/Wind Harmer
0.289
3144293JTRSVLE
Adder
0.23
3144293JTRSVLE
Adder
0.193
3145933PARMELE
Solar/Wind Harmer
0.144
3145933PARMELE
Solar/Wind Harmer
0.072
316274AC1-208 GEN
Solar/Wind Harmer
0.372
316034AC1-036 C
Solar/Wind Harmer
0.005
970323AG2-213 GEN
Solar/Wind Harmer
3.057
971775AH1-396 GEN
Solar/Wind Harmer
0.115
3152111X4-039 GT1
50/50
1.838
315747AE2-019 GEN
50/50
13.176
3150021OMF B
50/50
0.216
3150101POSSM6S
50/50
1.296
3150081POSSM6A
50/50
0.848
3150151POSSMC1
50/50
1.143
3150151POSSMC1
50/50
1.143
3150231REMNGT3
50/50
14.281
3150241REMNGT4
50/50
13.316
972217AH1-693 GEN
50/50
1.756
963691AG1-221 GEN
Solar/Wind Harmer
2.312
971455AH1-223 GEN
Solar/Wind Harmer
2.312
3141196NOKESVL
Solar/Wind Harmer
0.429
972199AH1-684 GEN
Adder
1.903
3150301M RUN C
Adder
13.349
3150291M RUN B
Adder
13.25
3150331BIRCHWDA
Adder
16.626
3141316ARNOLDS
Adder
0.229
316044AC1-158 PL1
Solar/Wind Harmer
0.461
316450AC1-158 RIC
Solar/Wind Harmer
0.123
3150401LDYSMT4
Adder
12.678
3150371LDYSMT1
Adder
12.251
316170AC1-121 GEN2
Solar/Wind Harmer
0.1
970737AG2-469 GEN
Solar/Wind Harmer
3.872
3141906WESTMOR
Solar/Wind Harmer
0.036
3132273ORANGE
Solar/Wind Harmer
0.018
971781AH1-399 GEN
Solar/Wind Harmer
0.118
3147666LOUISA
Solar/Wind Harmer
0.204
3150351NORNECKC2
Adder
0.884
316404AE1-155 C
Solar/Wind Harmer
0.019
3151761LOISA E
Adder
11.415
972183AH1-676 GEN
Adder
92.045
970009AG2-005 GEN
Solar/Wind Harmer
0.643
316473AC1-191 GEN
Solar/Wind Harmer
0.29
962971AG1-146 GEN
Solar/Wind Harmer
1.373
3142416OLDCHRC
Solar/Wind Harmer
0.821
3141766HARMONY
Solar/Wind Harmer
1.129
316156AD2-030 GEN
Solar/Wind Harmer
0.063
3141873WAN 176
Solar/Wind Harmer
1.505
316280AD1-041 GEN
Solar/Wind Harmer
0.002
316203AE2-005 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
0.432
970293AG2-193 GEN
Solar/Wind Harmer
0.899
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3142946ENON
Solar/Wind Harmer
0.028
3150861SPRUNCD
Adder
0.385
316382AG1-145 C
Solar/Wind Harmer
0.001
970133AG2-095 GEN
Solar/Wind Harmer
0.794
970129AG2-093 GEN
Solar/Wind Harmer
4.984
3150921YORKTN3
Adder
2.069
315778AD1-151 GEN
Solar/Wind Harmer
6.579
965281AG1-393 GEN
Solar/Wind Harmer
0.877
3144216WINCHST
Adder
0.31
315839AE2-212 C
Solar/Wind Harmer
0.001
961611AG1-000B GEN
Solar/Wind Harmer
2.181
3151221GRAVEL6
Adder
5.934
3151171GRAVELC
Adder
1.142
3145336SMITFLD
Solar/Wind Harmer
0.033
315813AE1-149 C
Solar/Wind Harmer
4.334
315773AC2-141 GEN
Solar/Wind Harmer
2.962
970659AG2-427 GEN
Solar/Wind Harmer
0.856
316083AB2-161 GEN
Solar/Wind Harmer
0.001
3152131X4-039 ST
50/50
2.892
3152121X4-039 GT2
50/50
1.833
3150011OMF A
50/50
0.216
3140676OCCOQUN
50/50
0.286
970467AG2-304 GEN
50/50
14.788
972223AH1-696 GEN
50/50
9.026
3150151POSSMC1
50/50
1.143
3141346CRANES
50/50
0.127
3150221REMNGT2
50/50
13.228
972201AH1-685 GEN
50/50
2.282
3150211REMNGT1
Adder
12.383
3150281M RUN A
Adder
13.357
316006AB2-029 C
Solar/Wind Harmer
0.001
971685AH1-345 GEN
Solar/Wind Harmer
0.73
316045AC1-158 PL2
Solar/Wind Harmer
1.475
972197AH1-683 GEN
Adder
1.98
972219AH1-694 GEN
Adder
1.425
316254AC1-120 GEN1
Solar/Wind Harmer
0.2
972135AH1-637 GEN
Solar/Wind Harmer
0.781
966881AG1-559 GEN
Solar/Wind Harmer
0.105
315683AE1-153 C
Solar/Wind Harmer
7.218
3147666LOUISA
Solar/Wind Harmer
0.355
316192AB2-158 GEN
Solar/Wind Harmer
0.501
316337AD2-073 GEN
Solar/Wind Harmer
0.077
3150351NORNECKC2
Adder
0.87
3141726DUNNSVL
Solar/Wind Harmer
0.348
962861AG1-135 GEN
Solar/Wind Harmer
2.764
3151751LOISA D
Adder
5.599
3138133OCRAN
Solar/Wind Harmer
0.051
3142416OLDCHRC
Solar/Wind Harmer
0.22
3142416OLDCHRC
Solar/Wind Harmer
0.084
3141766HARMONY
Solar/Wind Harmer
0.017
971777AH1-397 GEN
Solar/Wind Harmer
0.223
3141843SHACKLE
Adder
0.432
3142433PROV 92
Solar/Wind Harmer
0.337
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143526WINTERP
Solar/Wind Harmer
0.435
3142543TWELFTH
Solar/Wind Harmer
0.008
3150851SPRUNCC
Adder
0.385
944631AF1-128 GEN
Adder
39.853
3143226MDLTHAN
Solar/Wind Harmer
0.083
316159AE1-175 C
Solar/Wind Harmer
0.072
971317AH1-138 GEN
Solar/Wind Harmer
0.618
970129AG2-093 GEN
Solar/Wind Harmer
2.345
316458AB2-190 GEN2
Solar/Wind Harmer
0.442
315671AE2-027_GEN
Solar/Wind Harmer
5.273
3138126ROCKLANDING
Solar/Wind Harmer
0.038
971069AG2-661 GEN
Solar/Wind Harmer
1.462
971647AH1-324 GEN
Solar/Wind Harmer
3.497
961611AG1-000B GEN
Solar/Wind Harmer
4.29
3151171GRAVELC
Adder
0.868
3145336SMITFLD
Solar/Wind Harmer
0.325
316294AC1-161 GEN
Solar/Wind Harmer
1.405
970659AG2-427 GEN
Solar/Wind Harmer
3.913
316381AD1-082 GEN
Solar/Wind Harmer
0.084
316375AC2-012 GEN
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
8.025
3150981CHESPKA
Adder
1.007
944591AF1-124 GEN
Solar/Wind Harmer
18.213
316072AD1-144
Solar/Wind Harmer
0.029
316388AE2-253 GEN
Solar/Wind Harmer
0.251
3146456SLIGO L269
Solar/Wind Harmer
0.08
939411AE1-173 GEN
Solar/Wind Harmer
34.166
316246AF1-032 C
Solar/Wind Harmer
0.036
940641AE2-051 GEN
Solar/Wind Harmer
6.396
316093AE2-104_GEN
Solar/Wind Harmer
1.342
3143336POWHATN
Solar/Wind Harmer
1.412
3146516WINFALL
Solar/Wind Harmer
0.256
3146516WINFALL
Solar/Wind Harmer
0.079
316336AC2-165 C
Solar/Wind Harmer
0.003
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.078
3145663CRESWEL
Solar/Wind Harmer
0.215
971163AH1-040 GEN
Solar/Wind Harmer
6.133
970937AG2-583 GEN
Solar/Wind Harmer
4.64
3146206CASHIE
Solar/Wind Harmer
0.075
971547AH1-271 GEN
Solar/Wind Harmer
1.606
316023GEN1_S
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
0.301
3145893MURPHYS
Solar/Wind Harmer
0.334
970919AG2-571 GEN
Solar/Wind Harmer
2.672
970087AG2-069 GEN
Solar/Wind Harmer
5.999
3146173TUNIS
Solar/Wind Harmer
0.075
960081AF2-299 GEN
Solar/Wind Harmer
0.714
3145683EARLEYS
Solar/Wind Harmer
0.074
957481AF2-042 GEN
Solar/Wind Harmer
19.771
3146263WOODLND
Solar/Wind Harmer
0.074
315693AD1-088 GEN
Solar/Wind Harmer
3.545
962491AG1-098 GEN
Solar/Wind Harmer
4.214
971795AH1-408 GEN
Solar/Wind Harmer
4.913
3145963POPLR C
Solar/Wind Harmer
0.074
316011AB1-132 GEN
Solar/Wind Harmer
1.337
962571AG1-106 GEN
Solar/Wind Harmer
1.046
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.073
3147043LAWRENC
Adder
0.664
972003AH1-546 GEN
Solar/Wind Harmer
3.117
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.029
3146926FARMVIL
Solar/Wind Harmer
0.044
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145783HORNRTN
Solar/Wind Harmer
0.073
3145796HORNRTN
Solar/Wind Harmer
0.24
3145796HORNRTN
Solar/Wind Harmer
0.073
963171AG1-166 GEN
Solar/Wind Harmer
0.385
971563AH1-280 GEN
Solar/Wind Harmer
0.77
3144293JTRSVLE
Adder
0.23
316212AC1-099_GEN
Solar/Wind Harmer
0.372
970685AG2-442 GEN
Solar/Wind Harmer
5.37
972277AH1-723 GEN
Adder
42.854
3146293MARTNCO
Solar/Wind Harmer
0.067
316129AC1-054 GEN
Solar/Wind Harmer
0.27
971377AH1-170 GEN
Solar/Wind Harmer
0.763
3147623JAMES R
Solar/Wind Harmer
0.166
971065AG2-659 GEN
Solar/Wind Harmer
3.053
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315722AD1-056 GEN
Solar/Wind Harmer
0.448
315687AD1-152 GEN
Solar/Wind Harmer
0.002
316494AC1-189 GEN
Solar/Wind Harmer
0.238
3146233WITAKRS
Solar/Wind Harmer
0.278
961671AG1-007 GEN
Solar/Wind Harmer
0.011
3146083TARBORO
Solar/Wind Harmer
0.07
3145493TOT1
Solar/Wind Harmer
0.31
316359AB2-059 GEN
Solar/Wind Harmer
0.248
316049AB1-081 GEN
Solar/Wind Harmer
0.395
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.055
3142053HEARTS
Solar/Wind Harmer
0.122
970401AG2-262 GEN
Solar/Wind Harmer
0.404
316003AC1-222 GEN
Solar/Wind Harmer
0.002
315705AF1-075 GEN
Solar/Wind Harmer
2.472
3147983MERCK5
Solar/Wind Harmer
0.024
23779801AA1-109
Solar/Wind Helper
0.218
223401AF1-299 GEN
Solar/Wind Helper
0.397
966131AG1-482 GEN
Solar/Wind Helper
0.111
237080AD1-060 GEN
Solar/Wind Helper
0.221
235062AE1-101 C1
Solar/Wind Helper
1.064
237038AE2-054 C
Solar/Wind Helper
0.173
233930AB2-032 GEN
Solar/Wind Helper
0.23
233915AB1-141 GEN
Solar/Wind Helper
0.303
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
233998TM1NIN_3.36
Solar/Wind Helper
0.157
232428Y3-058 C
Solar/Wind Helper
0.203
233954AC2-188 GEN
Solar/Wind Helper
0.139
232404W1-003 C
Solar/Wind Helper
0.304
233950AC2-186 GEN
Solar/Wind Helper
0.07
232434Z2-077 GEN
Solar/Wind Helper
0.076
233972AC1-094 C
Solar/Wind Helper
0.181
205941AD2-115 GEN
Solar/Wind Helper
0.302
230434AG1-499 GEN
Solar/Wind Helper
0.136
230511AF1-262
Solar/Wind Helper
0.009
219258KINSLEYDEP C
Solar/Wind Helper
0.045
228728W1-130C
Solar/Wind Helper
0.032
219904AC1-010 C
Solar/Wind Helper
0.036
219907AC1-030 C
Solar/Wind Helper
0.02
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
20720728JCB_W1-129
Solar/Wind Helper
0.033
207445AB1-138_GEN
Solar/Wind Helper
0.061
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
207454AA2-184 E
Solar/Wind Helper
0.18
20715228NPK_W1-113
Solar/Wind Helper
0.045
20742028HF_AC1-207
Solar/Wind Helper
0.082
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
20675428EAM_W2-061
Solar/Wind Helper
0.009
218428ETC SOLAR C
Solar/Wind Helper
0.003
20676428JCR_X2-075
Solar/Wind Helper
0.039
217213AMBOY SO C
Solar/Wind Helper
0.017
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.013
207437AD2-070 GEN
Solar/Wind Helper
0.079
207439AE1-081 C O1
Solar/Wind Helper
0.011
207518AF1-320_GEN
Solar/Wind Helper
0.9
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
212266LOR1
Solar/Wind Helper
0.026
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.829
946731AF1-337 GEN
Solar/Wind Helper
0.233
209071AE2-133 GEN
Solar/Wind Helper
0.042
3144536CHRHLND
Solar/Wind Harmer
0.012
3151101ELIZAR3
Adder
7.489
970661AG2-428 GEN
Solar/Wind Harmer
1.707
3144873MCLAUGH
Solar/Wind Harmer
0.002
944581AF1-123 GEN
Solar/Wind Harmer
18.149
944601AF1-125 GEN
Solar/Wind Harmer
17.869
3146456SLIGO L269
Solar/Wind Harmer
0.08
971153AH1-033 GEN
Solar/Wind Harmer
0.925
316320Y1-086
Solar/Wind Harmer
0
316313AB2-026
Solar/Wind Harmer
0.05
316258AE1-075 C
Solar/Wind Harmer
0.06
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
1.2
316435W1029_GEN3
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.079
3145273HOLLAND
Solar/Wind Harmer
0.059
3146376EDENTON
Solar/Wind Harmer
0.078
315614AA2-178 GEN
Solar/Wind Harmer
0.439
971157AH1-035 GEN
Solar/Wind Harmer
0.911
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
315737AD1-076 GEN
Solar/Wind Harmer
0.975
3146206CASHIE
Solar/Wind Harmer
0.075
316365GEN2_N
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
970917AG2-570 GEN
Solar/Wind Harmer
6.681
957521AF2-046 GEN
Solar/Wind Harmer
5.587
961681AG1-008 GEN
Solar/Wind Harmer
5.587
3146173TUNIS
Solar/Wind Harmer
0.075
3156021HOLLOMANSOL
Solar/Wind Harmer
0.339
316463AE2-346 GEN
Solar/Wind Harmer
0.064
316140AB2-099
Solar/Wind Harmer
0.027
962331AG1-082 GEN
Solar/Wind Harmer
0.795
3146263WOODLND
Solar/Wind Harmer
0.074
313506AB2-031 GEN
Solar/Wind Harmer
0.228
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3145963POPLR C
Solar/Wind Harmer
0.074
970909AG2-566 GEN
Solar/Wind Harmer
0.785
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.073
3147043LAWRENC
Solar/Wind Harmer
0.044
3146776BUCKING
Solar/Wind Harmer
0.026
3146926FARMVIL
Solar/Wind Harmer
0.044
3145796HORNRTN
Solar/Wind Harmer
0.291
3145796HORNRTN
Solar/Wind Harmer
0.073
942461AE2-259 GEN
Solar/Wind Harmer
0
316478AD1-087 GEN
Solar/Wind Harmer
0.254
316486AD2-202 GEN
Solar/Wind Harmer
0.075
3147133PAMPLIN
Solar/Wind Harmer
0.227
971193AH1-056 GEN
Solar/Wind Harmer
4.404
963181AG1-167 GEN
Solar/Wind Harmer
0.289
3144293JTRSVLE
Adder
0.23
316210AC1-098 GEN
Solar/Wind Harmer
0.668
972255AH1-712 GEN
Adder
36.775
3145933PARMELE
Solar/Wind Harmer
0.072
966801AG1-551 GEN
Solar/Wind Harmer
0.836
959311AF2-222 GEN
Solar/Wind Harmer
6.376
970257AG2-171 GEN
Solar/Wind Harmer
2.293
970221AG2-151 GEN
Solar/Wind Harmer
3.817
315785AD2-033 C
Solar/Wind Harmer
0.582
964241AG1-285 GEN
Solar/Wind Harmer
4.753
316131AB2-060 GEN
Solar/Wind Harmer
0.224
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
315724AD1-057 GEN
Solar/Wind Harmer
0.266
316327AA2-057 GEN
Solar/Wind Harmer
0.106
3146233WITAKRS
Solar/Wind Harmer
0.35
3146233WITAKRS
Solar/Wind Harmer
0.047
3146073TAR RVR
Solar/Wind Harmer
0.07
3146083TARBORO
Solar/Wind Harmer
0.07
3138543CONSLDL
Solar/Wind Harmer
0.046
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.069
961601AG1-000A GEN
Solar/Wind Harmer
4.912
971623AH1-311 GEN
Solar/Wind Harmer
0.138
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.87
971683AH1-343 GEN
Solar/Wind Harmer
2.391
3148013FISHERV
Solar/Wind Harmer
0.065
316283AC2-100 C
Solar/Wind Harmer
0.124
315616AA1-038_C
Solar/Wind Harmer
0
3151861LOWMORA
Adder
0.645
958131AF2-107 GEN
Solar/Wind Harmer
1.618
226910AB2-157 C
Solar/Wind Helper
0.02
227287AC2-120 GEN
Solar/Wind Helper
0.49
237030AB1-096 C
Solar/Wind Helper
0.083
223402AF1-300 C
Solar/Wind Helper
0.397
205917AD1-020 ES
Solar/Wind Helper
0.318
238221AF1-254 C O1
Solar/Wind Helper
0.179
235067AD1-061 GEN
Solar/Wind Helper
0.312
233982AB2-133 GEN
Solar/Wind Helper
0.216
233918AB1-142 GEN
Solar/Wind Helper
0.303
233994AC2-023 GEN
Solar/Wind Helper
0.577
233996TM1833_GEN
Solar/Wind Helper
0.157
233997TMININ_4.2
Solar/Wind Helper
0.157
233940AF2-379 C
Solar/Wind Helper
0.037
234015AF2-250 C
Solar/Wind Helper
0.023
233952AC2-187 GEN
Solar/Wind Helper
0.139
232406W1-004 FULL
Solar/Wind Helper
0.304
233971AC1-093 C
Solar/Wind Helper
0.214
230430AE1-229_GEN
Solar/Wind Helper
1.995
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.089
228729W2-030 C
Solar/Wind Helper
0.065
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20716028EGP_W2-019
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.037
20715028HAN_X4-015
Solar/Wind Helper
0.033
219276PARKLANDSO C
Solar/Wind Helper
0.052
20714528FRN_Y2-051
Solar/Wind Helper
0.033
20720528MAN_W1-024
Solar/Wind Helper
0.016
219612MATRIX C
Solar/Wind Helper
0.014
218438BLK ROCK C
Solar/Wind Helper
0.016
20673728F2S_V4-070
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
219919AE1-041 FULL
Solar/Wind Helper
0.002
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
207510AF2-138 C
Solar/Wind Helper
0.046
20674628WNG_W3-110
Solar/Wind Helper
0.051
963161AG1-165 GEN
Solar/Wind Helper
0.242
963071AG1-156 GEN
Solar/Wind Helper
0.783
209027LOR2_Q27
Solar/Wind Helper
0.557
961331AF2-424 GEN
Solar/Wind Helper
0.237
961421AF2-433 GEN
Solar/Wind Helper
0.236
957921AF2-086 GEN
Solar/Wind Helper
0.234
946691AF1-333 GEN
Solar/Wind Helper
0.233
946741AF1-338 GEN
Solar/Wind Helper
0.233
209067AE2-060 GEN
Solar/Wind Helper
0.042
971489AH1-241 GEN
Solar/Wind Harmer
3.817
313527AB2-043 GEN
Solar/Wind Harmer
0.001
939181AE1-148 GEN
Solar/Wind Harmer
3.402
3145493TOT1
Solar/Wind Harmer
0.162
3145453TOT5
Solar/Wind Harmer
0.097
3145603CNETO
Solar/Wind Harmer
0.065
315821AE2-092 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
3.322
961601AG1-000A GEN
Solar/Wind Harmer
1.228
316263AC1-034 GEN
Solar/Wind Harmer
2.624
964791AG1-342 GEN
Solar/Wind Harmer
1.322
3146843MT LREL
Solar/Wind Harmer
0.069
3146843MT LREL
Solar/Wind Harmer
0.069
316222AC1-221 GEN
Solar/Wind Harmer
0.264
971761AH1-387 GEN
Solar/Wind Harmer
1.238
942751AE2-291 GEN
Solar/Wind Harmer
3.276
3132123MT JACKSON
Solar/Wind Harmer
0.183
970117AG2-086 GEN
Solar/Wind Harmer
1.401
970117AG2-086 GEN
Solar/Wind Harmer
0.934
226929AD2-058 GEN
Solar/Wind Helper
0.143
237025AB1-124 C
Solar/Wind Helper
0.193
237006AB1-125 GEN
Solar/Wind Helper
0.145
23777801MSM_W1-116
Solar/Wind Helper
0.13
237034AC2-136 C
Solar/Wind Helper
0.205
205916AD1-020 GEN
Solar/Wind Helper
1.48
208835TUHI V3-051
Solar/Wind Helper
0.019
208835TUHI V3-051
Solar/Wind Helper
0.019
237001AB1-127_GEN
Solar/Wind Helper
0.307
237002AB1-128_GEN
Solar/Wind Helper
0.298
235063AE1-101 C2
Solar/Wind Helper
1.064
20390526W1-045 C
Solar/Wind Helper
0.252
23777901MDS_W4-102
Solar/Wind Helper
0.105
235020AA1-095 C
Solar/Wind Helper
0.029
233933AB2-153 GEN
Solar/Wind Helper
0.14
233944AB2-135 GEN
Solar/Wind Helper
0.355
232424Y1-079 C
Solar/Wind Helper
0.07
233987AB2-037 GEN
Solar/Wind Helper
1.406
233946AB2-136 GEN
Solar/Wind Helper
0.341
234036AF2-325 C
Solar/Wind Helper
0.025
233901CHERRYDALE C
Solar/Wind Helper
0.139
232408W1-005 C
Solar/Wind Helper
0.304
232410W1-006 C
Solar/Wind Helper
0.304
233939AC1-091 C
Solar/Wind Helper
0.209
233970AC1-092 C
Solar/Wind Helper
0.209
230433AD2-135 GEN
Solar/Wind Helper
0.01
219921AF1-264
Solar/Wind Helper
0.03
230407AD2-065 C
Solar/Wind Helper
0.024
219615MILLCREEK C
Solar/Wind Helper
0.016
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20714928UPF_X1-085
Solar/Wind Helper
0.003
970053AG2-049 GEN
50/50
2.022
3138216PACIFIC
Solar/Wind Harmer
0.025
316411AF1-147_GEN1
Solar/Wind Harmer
0.003
316415AF1-147_GEN2
Solar/Wind Harmer
0.003
3141426STAFORD
Solar/Wind Harmer
0.023
3150411LDYSMT5
Adder
12.718
3150381LDYSMT2
Adder
12.172
972213AH1-691 GEN
Adder
2.059
972215AH1-692 GEN
Adder
2.059
316164AC1-076 GEN
Solar/Wind Harmer
0.132
944491AF1-114 GEN
Solar/Wind Harmer
0
316223AC1-118
Solar/Wind Harmer
0.064
972189AH1-679 GEN
Adder
1.467
3141813NORNECK
Solar/Wind Harmer
0.087
970327AG2-215 GEN
Solar/Wind Harmer
2.824
962981AG1-147 GEN
Solar/Wind Harmer
3.203
3141783LANCAST
Solar/Wind Harmer
0.051
3141783LANCAST
Solar/Wind Harmer
0.034
3138133OCRAN
Solar/Wind Harmer
0.025
3141913WHIT STONE
Solar/Wind Harmer
0.085
3147346CASHSCORNER
Solar/Wind Harmer
0.196
316312AB1-027
Solar/Wind Harmer
0.152
316314AB2-024 C
Solar/Wind Harmer
0
316059AD1-063 C
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.017
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
2.507
3143873LANEXA
Solar/Wind Harmer
0.051
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
971167AH1-042 GEN
Solar/Wind Harmer
7.477
315976AC1-164 GENA
Solar/Wind Harmer
8.72
316169AC1-164_GENC
Solar/Wind Harmer
7.533
315975AC1-164 GENB
Solar/Wind Harmer
0.258
316233AE1-074 FULL
Solar/Wind Harmer
0.067
971281AH1-106 GEN
Solar/Wind Harmer
1.161
971283AH1-107 GEN
Solar/Wind Harmer
1.161
971285AH1-108 GEN
Adder
0.631
3138283WHITEMARSH
Solar/Wind Harmer
0.019
316132AB2-190 GEN1
Solar/Wind Harmer
0.442
316369SG1_INVT
Solar/Wind Harmer
0.003
972265AH1-717 GEN
Adder
6.337
3151201GRAVEL4
Adder
5.94
3151191GRAVEL3
Adder
5.865
3151211GRAVEL5
Adder
5.865
971445AH1-216 GEN
Solar/Wind Harmer
5.723
3143316POE
Solar/Wind Harmer
0.321
3151081ELIZAR1
Adder
7.394
3151091ELIZAR2
Adder
7.266
3152611GOSPORTB
Adder
1.027
3152621GOSPORTC
Adder
0.872
3152601GOSPORTA
Adder
0.804
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.055
316311AC2-079 GEN
Solar/Wind Harmer
2.303
957871AF2-081 GEN
Solar/Wind Harmer
3.99
316305AF2-043 C
Solar/Wind Harmer
0.001
319010AE1-072 C
Solar/Wind Harmer
0.403
3146406KITTY HAWK
Solar/Wind Harmer
0.01
315835AF2-110_GEN
Solar/Wind Harmer
0.548
313526AB2-022
Solar/Wind Harmer
0.043
3146486SUNBURY
Solar/Wind Harmer
0.079
3146486SUNBURY
Solar/Wind Harmer
0.079
316321Z2-027
Solar/Wind Harmer
0.015
3146396TANGLEW
Solar/Wind Harmer
0.219
3145176PASQUOTANK
Solar/Wind Harmer
0.049
316315AB2-025 C
Solar/Wind Harmer
0.064
315814AE2-033 C
Solar/Wind Harmer
6.204
941031AE2-094 GEN
Solar/Wind Harmer
14.412
944011AF1-069 GEN
Solar/Wind Harmer
4.709
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.078
3130156CHOWAN
Solar/Wind Harmer
0.078
970673AG2-436 GEN
Solar/Wind Harmer
16.54
970673AG2-436 GEN
Solar/Wind Harmer
11.027
971967AH1-528 GEN
Solar/Wind Harmer
12.344
315816AE2-034 GEN
Solar/Wind Harmer
0.329
3130546PLYMOUTH
Solar/Wind Harmer
0.076
315732AD1-074 GEN1
Solar/Wind Harmer
0.435
315733AD1-074 GEN2
Solar/Wind Harmer
0.435
315735AD1-075 GEN1
Solar/Wind Harmer
0.218
965291AG1-394 GEN
Solar/Wind Harmer
0.336
3146206CASHIE
Solar/Wind Harmer
0.075
970601AG2-382 GEN
Solar/Wind Harmer
2.811
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
970085AG2-068 GEN
Solar/Wind Harmer
4
970581AG2-369 GEN
Solar/Wind Harmer
3.44
3145513AHOSKIE
Solar/Wind Harmer
0.156
3145513AHOSKIE
Solar/Wind Harmer
0.074
3146043SEABORD
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.149
3145683EARLEYS
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.074
315607AA1-063A GEN
Solar/Wind Harmer
0.152
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.294
315652AC1-086 GEN
Solar/Wind Harmer
8.087
972205AH1-687 GEN
Adder
3.134
970285AG2-188 GEN
Solar/Wind Harmer
5.802
971845AH1-439 GEN
Solar/Wind Harmer
3.325
3145796HORNRTN
Solar/Wind Harmer
0.233
3145796HORNRTN
Solar/Wind Harmer
0.029
3146033SCOT NK
Solar/Wind Harmer
0.29
315657AE1-056 GEN
Solar/Wind Harmer
2.494
946301AF1-294 GEN
Solar/Wind Harmer
1.424
961791AG1-021 GEN
Solar/Wind Harmer
0.693
970683AG2-441 GEN
Solar/Wind Harmer
4.794
970681AG2-440 GEN
Solar/Wind Harmer
3.836
970831AG2-522 GEN
Solar/Wind Harmer
3.066
972193AH1-681 GEN
Adder
1.643
3144303KENBRDG
Solar/Wind Harmer
0.057
971443AH1-215 GEN
Solar/Wind Harmer
1.204
971447AH1-217 GEN
Solar/Wind Harmer
2.163
316005AA1-067
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.282
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
970181AG2-120 GEN
Solar/Wind Harmer
0.883
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3138266HYDRAULIC
Solar/Wind Harmer
0.003
3138266HYDRAULIC
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
3.032
316420AA1-050 GEN
Solar/Wind Harmer
0.002
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.07
3145573BETHELC
Solar/Wind Harmer
0.07
316118AC1-105 GEN
Solar/Wind Harmer
0.176
3147173SINAI
Solar/Wind Harmer
0.067
3147243WELCO
Solar/Wind Harmer
0.042
270494AE1-108_GEN
Solar/Wind Harmer
0.802
3148133STUARTS
Solar/Wind Harmer
0.039
3148013FISHERV
Solar/Wind Harmer
0.037
970865AG2-541 GEN
Solar/Wind Harmer
2.214
316123AC1-075 GEN
Solar/Wind Harmer
0.084
970165AG2-112 GEN
Solar/Wind Harmer
0.5
970163AG2-111 GEN
Solar/Wind Harmer
0.477
3148463FAIRFLD
Solar/Wind Harmer
0.06
3151881LOWMORC
Adder
0.64
3151881LOWMORC
Adder
0.63
3151861LOWMORA
Adder
0.62
960921AF2-383 GEN
Solar/Wind Helper
0.279
205943AE1-185 GEN
Solar/Wind Helper
0.387
205956AE1-196_GEN
Solar/Wind Helper
0.385
205932AD2-116_GEN
Solar/Wind Helper
0.385
959381AF2-229 GEN
Solar/Wind Helper
0.257
237085AD2-009_GEN
Solar/Wind Helper
0.97
203975AE1-071-GEN
Solar/Wind Helper
1.713
233935AB2-179 C
Solar/Wind Helper
0.772
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.575
233990AG1-397 GEN
Solar/Wind Helper
0.162
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.208
964001AG1-254 GEN
Solar/Wind Helper
0.565
219914AD2-027 C
Solar/Wind Helper
0.068
227927V4-067C
Solar/Wind Helper
0.006
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
219607WPEMNERT C
Solar/Wind Helper
0.047
214067T20SOLAR
Solar/Wind Helper
0.007
20715728PEM_W1-119
Solar/Wind Helper
0.056
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
966261AG1-495 GEN
Solar/Wind Helper
0.047
20675928HOL_W4-097
Solar/Wind Helper
0.029
207530AG1-191 GEN
Solar/Wind Helper
0.038
207484AF2-139 C O1
Solar/Wind Helper
0.048
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
20675128HRM_W1-127
Solar/Wind Helper
0.017
209116AE2-175 GEN
Solar/Wind Helper
1.004
961261AF2-417 GEN
Solar/Wind Helper
0.241
959431AF2-234 GEN
Solar/Wind Helper
0.466
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
959421AF2-233 GEN
Solar/Wind Helper
0.233
238208AF1-136 C
Solar/Wind Helper
0.089
20720628TIN_W1-124
Solar/Wind Helper
0.11
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.009
207442AE1-156 GEN
Solar/Wind Helper
0.188
20676128MHD_W3-029
Solar/Wind Helper
0.055
20671828STAW2-080
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
207471AF2-354 C
Solar/Wind Helper
0.097
20674928WA_W3-044
Solar/Wind Helper
0.056
964851AG1-348 GEN
Solar/Wind Helper
0.046
20674128FR_U2-059
Solar/Wind Helper
0.002
20676228FRD_X1-012
Solar/Wind Helper
0.052
966111AG1-480 GEN
Solar/Wind Helper
0.042
211065PSPA IPP
Solar/Wind Helper
0.085
211065PSPA IPP
Solar/Wind Helper
0.085
208972BECR K09
Solar/Wind Helper
0.178
961431AF2-434 GEN
Solar/Wind Helper
0.236
209029WAYMART-WD
Solar/Wind Helper
0.443
209054AE2-059 GEN
Solar/Wind Helper
0.042
946751AF1-339 GEN
Solar/Wind Helper
0.233
209137AF2-361 C
Solar/Wind Helper
0.708
LAGNLTFEXP_LAGN->PJM
CLTF
6.324
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.485
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.592
MECLTFEXP_MEC->PJM
CLTF
4.449
SIGELTFEXP_SIGE->PJM
CLTF
0.14
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.565
TVALTFEXP_TVA->PJM
CLTF
3.188
NYPJM->LTFIMP_NY
CLTF
2.575
LGEELTFEXP_LGEE->PJM
CLTF
1.805
WECLTFEXP_WEC->PJM
CLTF
0.962
CPLELTFEXP_CPLE->PJM
CLTF
5.065
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.965

Details for 8BRAMBLETON-AH1-727 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 9344_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8BRAMBLETON-AH1-727 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 9344_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.63 %
Rating:3256.16 MVA
Rating Type:B
MVA to Mitigate:3472.07
MW Contribution:8.95
Bus #Bus NameTypeMW Contribution
316447AC1-158 HLD
Solar/Wind Harmer
3.008
315651AD1-115 GEN
Solar/Wind Harmer
0.009
971253AH1-086 GEN
50/50
24.442
971257AH1-088 GEN
50/50
5.432
3150301M RUN C
50/50
43.549
3150291M RUN B
50/50
43.226
3150231REMNGT3
50/50
43.711
3150241REMNGT4
50/50
40.756
972217AH1-693 GEN
50/50
5.373
972199AH1-684 GEN
Adder
5.823
3141196NOKESVL
Solar/Wind Harmer
1.195
316044AC1-158 PL1
Solar/Wind Harmer
1.369
316450AC1-158 RIC
Solar/Wind Harmer
0.365
316170AC1-121 GEN2
Solar/Wind Harmer
0.291
3132273ORANGE
Solar/Wind Harmer
0.051
3147666LOUISA
Solar/Wind Harmer
0.563
3150401LDYSMT4
Adder
31.841
3150371LDYSMT1
Adder
30.767
3151761LOISA E
Adder
31.228
972183AH1-676 GEN
Adder
251.695
3150331BIRCHWDA
Adder
38.122
3150151POSSMC1
Adder
2.229
3150151POSSMC1
Adder
2.229
3141316ARNOLDS
Adder
0.53
971781AH1-399 GEN
Solar/Wind Harmer
0.287
970737AG2-469 GEN
Solar/Wind Harmer
9.258
3141906WESTMOR
Solar/Wind Harmer
0.086
316473AC1-191 GEN
Solar/Wind Harmer
0.726
3142416OLDCHRC
Solar/Wind Harmer
2.065
3150351NORNECKC2
Adder
2.16
316404AE1-155 C
Solar/Wind Harmer
0.048
970293AG2-193 GEN
Solar/Wind Harmer
2.259
970009AG2-005 GEN
Solar/Wind Harmer
1.58
962971AG1-146 GEN
Solar/Wind Harmer
3.381
3150861SPRUNCD
Adder
0.972
3143096IRON208
Adder
0.883
3143096IRON208
Adder
0.866
3141766HARMONY
Solar/Wind Harmer
2.802
3142433PROV 92
Adder
0.408
3142433PROV 92
Adder
0.408
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141843SHACKLE
Adder
1.073
3142946ENON
Solar/Wind Harmer
0.07
316280AD1-041 GEN
Solar/Wind Harmer
0.004
316156AD2-030 GEN
Solar/Wind Harmer
0.155
3141873WAN 176
Solar/Wind Harmer
3.731
316382AG1-145 C
Solar/Wind Harmer
0.002
970133AG2-095 GEN
Solar/Wind Harmer
1.99
970129AG2-093 GEN
Solar/Wind Harmer
12.476
965281AG1-393 GEN
Solar/Wind Harmer
2.197
315778AD1-151 GEN
Solar/Wind Harmer
16.459
3150921YORKTN3
Adder
5.164
315839AE2-212 C
Solar/Wind Harmer
0.002
3144216WINCHST
Adder
0.774
961611AG1-000B GEN
Solar/Wind Harmer
5.45
3151221GRAVEL6
Adder
14.814
3151171GRAVELC
Adder
2.85
315813AE1-149 C
Solar/Wind Harmer
10.825
3145336SMITFLD
Solar/Wind Harmer
0.081
315773AC2-141 GEN
Solar/Wind Harmer
7.404
970659AG2-427 GEN
Solar/Wind Harmer
2.135
3144536CHRHLND
Solar/Wind Harmer
0.03
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3151101ELIZAR3
Adder
18.67
3144873MCLAUGH
Solar/Wind Harmer
0.005
944581AF1-123 GEN
Solar/Wind Harmer
45.254
944601AF1-125 GEN
Solar/Wind Harmer
44.557
970661AG2-428 GEN
Solar/Wind Harmer
4.252
3146456SLIGO L269
Solar/Wind Harmer
0.199
971153AH1-033 GEN
Solar/Wind Harmer
2.3
316313AB2-026
Solar/Wind Harmer
0.124
316258AE1-075 C
Solar/Wind Harmer
0.149
316405AF2-144 C
Solar/Wind Harmer
0.001
966001AG1-469 GEN
Solar/Wind Harmer
0.139
3150391LDYSMT3
Adder
31.782
972195AH1-682 GEN
Adder
4.177
3151731LOISA B
Adder
15.317
3151721LOISA A
Adder
15.238
315673AE1-157 GEN
Solar/Wind Harmer
16.074
957411AF2-035 GEN
Solar/Wind Harmer
9.794
970317AG2-208 GEN
Solar/Wind Harmer
9.074
3150071POSSM 5
Adder
101.873
3150181POSSMC2
Adder
2.248
3150181POSSMC2
Adder
2.229
3150181POSSMC2
Adder
2.229
316468AD1-105 GEN
Solar/Wind Harmer
-0.071
966871AG1-558 GEN
Solar/Wind Harmer
0.248
3142296MT RD221
Adder
0.683
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.231
3150341NORNECKC1
Adder
2.213
971223AH1-071 GEN
Solar/Wind Harmer
2.268
3143526WINTERP
Solar/Wind Harmer
1.104
3142366NRTHEST
Adder
0.693
958261AF2-120 GEN
Solar/Wind Harmer
7.015
3150691DARBY 3
Adder
15.26
3150701DARBY 4
Adder
15.225
3150681DARBY 2
Adder
15.207
3150671DARBY 1
Adder
15.189
316075AC2-137 C
Solar/Wind Harmer
0.058
3142946ENON
Solar/Wind Harmer
0.021
944641AF1-129 GEN
Adder
98.867
316240AF1-291 C
Solar/Wind Harmer
0.002
316033AB2-134 GEN
Solar/Wind Harmer
0.012
315697AD1-025 GEN
Solar/Wind Harmer
0.231
316236AE1-162_GEN
Solar/Wind Harmer
0.002
970657AG2-426 GEN
Solar/Wind Harmer
7.052
970657AG2-426 GEN
Solar/Wind Harmer
1.478
316036AC1-147 C
Solar/Wind Harmer
0.037
3150991CHESPKB
Adder
2.106
3150991CHESPKB
Adder
2.056
316316AC1-027 C
Solar/Wind Harmer
0.193
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.006
3145506HICKORY
Solar/Wind Harmer
0.8
3145506HICKORY
Solar/Wind Harmer
0.48
3145506HICKORY
Solar/Wind Harmer
0.12
316339AD2-160 GEN
Solar/Wind Harmer
0.323
316018AA1-139 ULT2
Solar/Wind Harmer
0.005
316017AA1-139 ULT1
Solar/Wind Harmer
0.111
3137176SLIGO L2192
Solar/Wind Harmer
0.792
3146456SLIGO L269
Solar/Wind Harmer
3.521
3130086AYDLETT
Solar/Wind Harmer
0.795
3146386ELIZ CT
Solar/Wind Harmer
0.197
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.195
3146516WINFALL
Solar/Wind Harmer
0.195
3146516WINFALL
Solar/Wind Harmer
0.195
3144356SAPONY
Solar/Wind Harmer
1.625
3146626S HERTFORD
Solar/Wind Harmer
0.194
3146626S HERTFORD
Solar/Wind Harmer
0.194
315742AE1-103 GEN
Solar/Wind Harmer
0.002
3146376EDENTON
Solar/Wind Harmer
0.847
3146376EDENTON
Solar/Wind Harmer
0.847
972185AH1-677 GEN
Adder
10.672
972187AH1-678 GEN
Adder
5.366
970933AG2-581 GEN
Solar/Wind Harmer
14.962
316065AD1-022 GEN
Solar/Wind Harmer
8.417
3145893MURPHYS
Solar/Wind Harmer
1.217
3145893MURPHYS
Solar/Wind Harmer
0.327
3146173TUNIS
Solar/Wind Harmer
0.18
3146173TUNIS
Solar/Wind Harmer
0.18
970099AG2-077 GEN
Solar/Wind Harmer
19.085
316181AB2-040 GEN
Solar/Wind Harmer
0.257
971741AH1-377 GEN
Solar/Wind Harmer
17.523
3142666NORTHAMPTON
Solar/Wind Harmer
0.176
3142666NORTHAMPTON
Solar/Wind Harmer
0.176
3142666NORTHAMPTON
Solar/Wind Harmer
0.176
3142666NORTHAMPTON
Solar/Wind Harmer
0.106
970301AG2-198 GEN
Solar/Wind Harmer
7.522
3143336POWHATN
Solar/Wind Harmer
2.984
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.195
3146626S HERTFORD
Solar/Wind Harmer
0.194
3145273HOLLAND
Solar/Wind Harmer
0.145
3146376EDENTON
Solar/Wind Harmer
0.19
315614AA2-178 GEN
Solar/Wind Harmer
1.07
971157AH1-035 GEN
Solar/Wind Harmer
2.212
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
315737AD1-076 GEN
Solar/Wind Harmer
2.365
970917AG2-570 GEN
Solar/Wind Harmer
16.254
316365GEN2_N
Solar/Wind Harmer
0.409
3146206CASHIE
Solar/Wind Harmer
0.182
3145893MURPHYS
Solar/Wind Harmer
0.304
3145893MURPHYS
Solar/Wind Harmer
0.182
957521AF2-046 GEN
Solar/Wind Harmer
13.506
961681AG1-008 GEN
Solar/Wind Harmer
13.506
3146173TUNIS
Solar/Wind Harmer
0.18
3156021HOLLOMANSOL
Solar/Wind Harmer
0.817
316463AE2-346 GEN
Solar/Wind Harmer
0.154
316140AB2-099
Solar/Wind Harmer
0.064
962331AG1-082 GEN
Solar/Wind Harmer
1.916
3146263WOODLND
Solar/Wind Harmer
0.178
313506AB2-031 GEN
Solar/Wind Harmer
0.548
3142666NORTHAMPTON
Solar/Wind Harmer
0.176
3145963POPLR C
Solar/Wind Harmer
0.176
970909AG2-566 GEN
Solar/Wind Harmer
1.881
316317KELFORD C
Solar/Wind Harmer
0.017
3145823KELFORD
Solar/Wind Harmer
0.176
3147043LAWRENC
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.105
3146776BUCKING
Solar/Wind Harmer
0.063
3145796HORNRTN
Solar/Wind Harmer
0.695
3145796HORNRTN
Solar/Wind Harmer
0.174
316478AD1-087 GEN
Solar/Wind Harmer
0.607
316486AD2-202 GEN
Solar/Wind Harmer
0.178
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3147133PAMPLIN
Solar/Wind Harmer
0.539
971193AH1-056 GEN
Solar/Wind Harmer
10.456
963181AG1-167 GEN
Solar/Wind Harmer
0.685
3144293JTRSVLE
Adder
0.545
316210AC1-098 GEN
Solar/Wind Harmer
1.582
3145933PARMELE
Solar/Wind Harmer
0.17
966801AG1-551 GEN
Solar/Wind Harmer
1.979
316164AC1-076 GEN
Solar/Wind Harmer
0.382
3150411LDYSMT5
Adder
31.941
3150381LDYSMT2
Adder
30.569
972213AH1-691 GEN
Adder
5.171
972215AH1-692 GEN
Adder
5.171
3147346CASHSCORNER
Solar/Wind Harmer
0.532
3141426STAFORD
Solar/Wind Harmer
0.05
972189AH1-679 GEN
Adder
3.695
944491AF1-114 GEN
Solar/Wind Harmer
0.001
316223AC1-118
Solar/Wind Harmer
0.155
316312AB1-027
Solar/Wind Harmer
0.381
3141813NORNECK
Solar/Wind Harmer
0.213
316233AE1-074 FULL
Solar/Wind Harmer
0.17
971281AH1-106 GEN
Solar/Wind Harmer
2.946
971283AH1-107 GEN
Solar/Wind Harmer
2.946
970053AG2-049 GEN
Adder
3.548
970327AG2-215 GEN
Solar/Wind Harmer
6.945
962981AG1-147 GEN
Solar/Wind Harmer
7.889
971285AH1-108 GEN
Adder
1.591
3141783LANCAST
Solar/Wind Harmer
0.126
3141783LANCAST
Solar/Wind Harmer
0.084
315976AC1-164 GENA
Solar/Wind Harmer
21.836
316169AC1-164_GENC
Solar/Wind Harmer
18.864
315975AC1-164 GENB
Solar/Wind Harmer
0.646
3138133OCRAN
Solar/Wind Harmer
0.063
316314AB2-024 C
Solar/Wind Harmer
0.001
3141913WHIT STONE
Solar/Wind Harmer
0.21
3143873LANEXA
Solar/Wind Harmer
0.126
316059AD1-063 C
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.408
3142433PROV 92
Adder
0.408
971167AH1-042 GEN
Solar/Wind Harmer
18.654
970189AG2-124 GEN
Solar/Wind Harmer
6.224
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.042
3138283WHITEMARSH
Solar/Wind Harmer
0.048
316132AB2-190 GEN1
Solar/Wind Harmer
1.107
316369SG1_INVT
Solar/Wind Harmer
0.008
972265AH1-717 GEN
Adder
15.821
3151201GRAVEL4
Adder
14.831
3151191GRAVEL3
Adder
14.643
3151211GRAVEL5
Adder
14.643
3143316POE
Solar/Wind Harmer
0.803
971445AH1-216 GEN
Solar/Wind Harmer
14.282
3151081ELIZAR1
Adder
18.434
3151091ELIZAR2
Adder
18.114
3152611GOSPORTB
Adder
2.56
3152621GOSPORTC
Adder
2.173
3152601GOSPORTA
Adder
2.005
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.137
316311AC2-079 GEN
Solar/Wind Harmer
5.725
957871AF2-081 GEN
Solar/Wind Harmer
9.922
319010AE1-072 C
Solar/Wind Harmer
1.001
316305AF2-043 C
Solar/Wind Harmer
0.002
3146406KITTY HAWK
Solar/Wind Harmer
0.025
315835AF2-110_GEN
Solar/Wind Harmer
1.359
313526AB2-022
Solar/Wind Harmer
0.107
3146486SUNBURY
Solar/Wind Harmer
0.197
3146486SUNBURY
Solar/Wind Harmer
0.197
316321Z2-027
Solar/Wind Harmer
0.037
3146396TANGLEW
Solar/Wind Harmer
0.542
3145176PASQUOTANK
Solar/Wind Harmer
0.122
316315AB2-025 C
Solar/Wind Harmer
0.157
941031AE2-094 GEN
Solar/Wind Harmer
35.747
944011AF1-069 GEN
Solar/Wind Harmer
11.68
315814AE2-033 C
Solar/Wind Harmer
15.327
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
40.848
970673AG2-436 GEN
Solar/Wind Harmer
27.232
3130156CHOWAN
Solar/Wind Harmer
0.19
3130156CHOWAN
Solar/Wind Harmer
0.19
971255AH1-087 GEN
50/50
5.432
971259AH1-089 GEN
50/50
5.432
3150281M RUN A
50/50
43.576
3150221REMNGT2
50/50
40.487
972201AH1-685 GEN
50/50
6.985
3150211REMNGT1
Adder
37.902
316006AB2-029 C
Solar/Wind Harmer
0.002
971685AH1-345 GEN
Solar/Wind Harmer
2.219
316045AC1-158 PL2
Solar/Wind Harmer
4.376
316254AC1-120 GEN1
Solar/Wind Harmer
0.583
315683AE1-153 C
Solar/Wind Harmer
20.71
3147666LOUISA
Solar/Wind Harmer
0.979
316192AB2-158 GEN
Solar/Wind Harmer
1.381
972197AH1-683 GEN
Adder
4.972
972219AH1-694 GEN
Adder
3.58
3151751LOISA D
Adder
15.317
3140676OCCOQUN
Adder
0.566
966881AG1-559 GEN
Solar/Wind Harmer
0.265
3141346CRANES
Adder
0.266
972223AH1-696 GEN
Adder
17.606
3150151POSSMC1
Adder
2.229
972135AH1-637 GEN
Solar/Wind Harmer
1.858
316337AD2-073 GEN
Solar/Wind Harmer
0.187
3142416OLDCHRC
Solar/Wind Harmer
0.554
3142416OLDCHRC
Solar/Wind Harmer
0.212
3150351NORNECKC2
Adder
2.124
3141726DUNNSVL
Solar/Wind Harmer
0.851
3143226MDLTHAN
Solar/Wind Harmer
0.212
3143526WINTERP
Solar/Wind Harmer
1.104
962861AG1-135 GEN
Solar/Wind Harmer
6.784
3150851SPRUNCC
Adder
0.972
3143096IRON208
Adder
0.883
3142543TWELFTH
Solar/Wind Harmer
0.02
3138133OCRAN
Solar/Wind Harmer
0.126
3141766HARMONY
Solar/Wind Harmer
0.042
3142433PROV 92
Solar/Wind Harmer
0.84
3142433PROV 92
Adder
0.408
3142433PROV 92
Adder
0.408
971777AH1-397 GEN
Solar/Wind Harmer
0.554
3141843SHACKLE
Adder
1.073
944631AF1-128 GEN
Adder
99.968
316159AE1-175 C
Solar/Wind Harmer
0.179
971317AH1-138 GEN
Solar/Wind Harmer
1.542
970129AG2-093 GEN
Solar/Wind Harmer
5.871
315671AE2-027_GEN
Solar/Wind Harmer
13.209
316458AB2-190 GEN2
Solar/Wind Harmer
1.107
971069AG2-661 GEN
Solar/Wind Harmer
3.658
3138126ROCKLANDING
Solar/Wind Harmer
0.094
971647AH1-324 GEN
Solar/Wind Harmer
8.741
961611AG1-000B GEN
Solar/Wind Harmer
10.718
3151171GRAVELC
Adder
2.168
3145336SMITFLD
Solar/Wind Harmer
0.811
316294AC1-161 GEN
Solar/Wind Harmer
3.512
970659AG2-427 GEN
Solar/Wind Harmer
9.759
316381AD1-082 GEN
Solar/Wind Harmer
0.21
316375AC2-012 GEN
Solar/Wind Harmer
0.005
3150981CHESPKA
Adder
2.51
944591AF1-124 GEN
Solar/Wind Harmer
45.415
970661AG2-428 GEN
Solar/Wind Harmer
19.99
316072AD1-144
Solar/Wind Harmer
0.072
939411AE1-173 GEN
Solar/Wind Harmer
85.364
940641AE2-051 GEN
Solar/Wind Harmer
15.997
316388AE2-253 GEN
Solar/Wind Harmer
0.625
3146456SLIGO L269
Solar/Wind Harmer
0.199
316246AF1-032 C
Solar/Wind Harmer
0.09
316093AE2-104_GEN
Solar/Wind Harmer
3.331
3143336POWHATN
Solar/Wind Harmer
3.511
3146516WINFALL
Solar/Wind Harmer
0.632
3146516WINFALL
Solar/Wind Harmer
0.195
316336AC2-165 C
Solar/Wind Harmer
0.008
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.19
3145663CRESWEL
Solar/Wind Harmer
0.523
971163AH1-040 GEN
Solar/Wind Harmer
14.962
970937AG2-583 GEN
Solar/Wind Harmer
11.244
970919AG2-571 GEN
Solar/Wind Harmer
6.502
316023GEN1_S
Solar/Wind Harmer
0.409
970087AG2-069 GEN
Solar/Wind Harmer
14.579
3146206CASHIE
Solar/Wind Harmer
0.182
971547AH1-271 GEN
Solar/Wind Harmer
3.887
3145893MURPHYS
Solar/Wind Harmer
0.727
3145893MURPHYS
Solar/Wind Harmer
0.809
3146173TUNIS
Solar/Wind Harmer
0.18
960081AF2-299 GEN
Solar/Wind Harmer
1.72
3145683EARLEYS
Solar/Wind Harmer
0.179
957481AF2-042 GEN
Solar/Wind Harmer
47.712
3146263WOODLND
Solar/Wind Harmer
0.178
315693AD1-088 GEN
Solar/Wind Harmer
8.533
962491AG1-098 GEN
Solar/Wind Harmer
10.141
971795AH1-408 GEN
Solar/Wind Harmer
11.784
3145963POPLR C
Solar/Wind Harmer
0.176
316011AB1-132 GEN
Solar/Wind Harmer
3.202
962571AG1-106 GEN
Solar/Wind Harmer
2.506
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.176
3147043LAWRENC
Adder
1.589
3146926FARMVIL
Solar/Wind Harmer
0.105
316174AB2-169 GEN
Solar/Wind Harmer
0.005
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.07
972003AH1-546 GEN
Solar/Wind Harmer
7.424
3145783HORNRTN
Solar/Wind Harmer
0.174
959311AF2-222 GEN
Solar/Wind Harmer
15.084
970257AG2-171 GEN
Solar/Wind Harmer
5.422
315785AD2-033 C
Solar/Wind Harmer
1.375
964241AG1-285 GEN
Solar/Wind Harmer
11.211
970221AG2-151 GEN
Solar/Wind Harmer
8.948
316131AB2-060 GEN
Solar/Wind Harmer
0.527
3145746EVERETS
Solar/Wind Harmer
0.167
3145746EVERETS
Solar/Wind Harmer
0.167
315724AD1-057 GEN
Solar/Wind Harmer
0.624
316327AA2-057 GEN
Solar/Wind Harmer
0.25
972255AH1-712 GEN
Adder
83.534
3146233WITAKRS
Solar/Wind Harmer
0.817
3146233WITAKRS
Solar/Wind Harmer
0.111
3146073TAR RVR
Solar/Wind Harmer
0.163
3146083TARBORO
Solar/Wind Harmer
0.163
3138543CONSLDL
Solar/Wind Harmer
0.107
961601AG1-000A GEN
Solar/Wind Harmer
11.396
3145543BTLEBRO
Solar/Wind Harmer
0.16
3145543BTLEBRO
Solar/Wind Harmer
0.16
971623AH1-311 GEN
Solar/Wind Harmer
0.32
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
6.556
971683AH1-343 GEN
Solar/Wind Harmer
5.342
316283AC2-100 C
Solar/Wind Harmer
0.274
3148013FISHERV
Solar/Wind Harmer
0.138
315616AA1-038_C
Solar/Wind Harmer
0.001
3151861LOWMORA
Adder
1.283
237061AD1-155 GEN
Solar/Wind Harmer
0.003
238221AF1-254 C O1
Solar/Wind Helper
0.304
237030AB1-096 C
Solar/Wind Helper
0.08
235067AD1-061 GEN
Solar/Wind Helper
0.532
205917AD1-020 ES
Solar/Wind Helper
0.38
233994AC2-023 GEN
Solar/Wind Helper
0.99
233996TM1833_GEN
Solar/Wind Helper
0.269
233997TMININ_4.2
Solar/Wind Helper
0.269
233971AC1-093 C
Solar/Wind Helper
0.369
232406W1-004 FULL
Solar/Wind Helper
0.523
233940AF2-379 C
Solar/Wind Helper
0.064
234015AF2-250 C
Solar/Wind Helper
0.039
233952AC2-187 GEN
Solar/Wind Helper
0.239
233918AB1-142 GEN
Solar/Wind Helper
0.516
233982AB2-133 GEN
Solar/Wind Helper
0.368
230430AE1-229_GEN
Solar/Wind Helper
3.449
230415AB2-049 C
Solar/Wind Helper
0.031
228729W2-030 C
Solar/Wind Helper
0.113
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.056
219291REEVESSOUT C
Solar/Wind Helper
0.012
219912AD2-042 GEN
Solar/Wind Helper
0.153
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.043
219348LDSOLAR C
Solar/Wind Helper
0.117
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.064
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.058
20714528FRN_Y2-051
Solar/Wind Helper
0.058
219276PARKLANDSO C
Solar/Wind Helper
0.091
20720528MAN_W1-024
Solar/Wind Helper
0.029
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.028
219908AB1-139 C
Solar/Wind Helper
0.075
219249CENTRALDIV C
Solar/Wind Helper
0.01
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.09
3145796HORNRTN
Solar/Wind Harmer
0.573
3145796HORNRTN
Solar/Wind Harmer
0.174
963171AG1-166 GEN
Solar/Wind Harmer
0.913
971563AH1-280 GEN
Solar/Wind Harmer
1.826
3144293JTRSVLE
Adder
0.545
316212AC1-099_GEN
Solar/Wind Harmer
0.882
970685AG2-442 GEN
Solar/Wind Harmer
12.717
3146293MARTNCO
Solar/Wind Harmer
0.158
316129AC1-054 GEN
Solar/Wind Harmer
0.638
971065AG2-659 GEN
Solar/Wind Harmer
7.218
971377AH1-170 GEN
Solar/Wind Harmer
1.79
3147623JAMES R
Solar/Wind Harmer
0.389
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3145746EVERETS
Solar/Wind Harmer
0.167
3145746EVERETS
Solar/Wind Harmer
0.167
315722AD1-056 GEN
Solar/Wind Harmer
1.053
315687AD1-152 GEN
Solar/Wind Harmer
0.005
316494AC1-189 GEN
Solar/Wind Harmer
0.556
972277AH1-723 GEN
Adder
97.342
3146233WITAKRS
Solar/Wind Harmer
0.648
961671AG1-007 GEN
Solar/Wind Harmer
0.025
3146083TARBORO
Solar/Wind Harmer
0.163
3145493TOT1
Solar/Wind Harmer
0.723
3145543BTLEBRO
Solar/Wind Harmer
0.16
3145543BTLEBRO
Solar/Wind Harmer
0.128
316359AB2-059 GEN
Solar/Wind Harmer
0.576
316049AB1-081 GEN
Solar/Wind Harmer
0.917
3142053HEARTS
Solar/Wind Harmer
0.282
970401AG2-262 GEN
Solar/Wind Harmer
0.935
316003AC1-222 GEN
Solar/Wind Harmer
0.004
3147983MERCK5
Solar/Wind Harmer
0.05
315705AF1-075 GEN
Solar/Wind Harmer
4.991
23779801AA1-109
Solar/Wind Helper
0.222
237080AD1-060 GEN
Solar/Wind Helper
0.373
237038AE2-054 C
Solar/Wind Helper
0.293
235062AE1-101 C1
Solar/Wind Helper
1.773
233998TM1NIN_3.36
Solar/Wind Helper
0.269
233972AC1-094 C
Solar/Wind Helper
0.312
232404W1-003 C
Solar/Wind Helper
0.523
232428Y3-058 C
Solar/Wind Helper
0.348
232434Z2-077 GEN
Solar/Wind Helper
0.131
232426Y1-080 FULL
Solar/Wind Helper
0.04
233964AF2-378 GEN
Solar/Wind Helper
0.043
233954AC2-188 GEN
Solar/Wind Helper
0.239
233950AC2-186 GEN
Solar/Wind Helper
0.12
232422X3-066 FULL
Solar/Wind Helper
0.117
233930AB2-032 GEN
Solar/Wind Helper
0.391
233915AB1-141 GEN
Solar/Wind Helper
0.516
966131AG1-482 GEN
Solar/Wind Helper
0.138
230511AF1-262
Solar/Wind Helper
0.015
228728W1-130C
Solar/Wind Helper
0.055
230434AG1-499 GEN
Solar/Wind Helper
0.235
219258KINSLEYDEP C
Solar/Wind Helper
0.078
219904AC1-010 C
Solar/Wind Helper
0.062
218660EHAMPSOLAR C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.041
219907AC1-030 C
Solar/Wind Helper
0.035
219304NAMERICA C
Solar/Wind Helper
0.134
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.106
963711AG1-223 GEN
Solar/Wind Helper
0.065
20714828MDF_W3-079
Solar/Wind Helper
0.132
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
207454AA2-184 E
Solar/Wind Helper
0.315
20742028HF_AC1-207
Solar/Wind Helper
0.143
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.077
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.023
205941AD2-115 GEN
Solar/Wind Helper
0.494
207439AE1-081 C O1
Solar/Wind Helper
0.019
20675828AU_W4-064
Solar/Wind Helper
0.03
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.579
20671928W4-073
Solar/Wind Helper
0.09
971967AH1-528 GEN
Solar/Wind Harmer
30.407
315816AE2-034 GEN
Solar/Wind Harmer
0.803
3130546PLYMOUTH
Solar/Wind Harmer
0.184
315732AD1-074 GEN1
Solar/Wind Harmer
1.056
315733AD1-074 GEN2
Solar/Wind Harmer
1.056
315735AD1-075 GEN1
Solar/Wind Harmer
0.529
965291AG1-394 GEN
Solar/Wind Harmer
0.815
970085AG2-068 GEN
Solar/Wind Harmer
9.72
970581AG2-369 GEN
Solar/Wind Harmer
8.359
3146206CASHIE
Solar/Wind Harmer
0.182
970601AG2-382 GEN
Solar/Wind Harmer
6.803
3145893MURPHYS
Solar/Wind Harmer
0.491
3145893MURPHYS
Solar/Wind Harmer
0.182
3145513AHOSKIE
Solar/Wind Harmer
0.376
3145513AHOSKIE
Solar/Wind Harmer
0.179
3146043SEABORD
Solar/Wind Harmer
0.179
3145683EARLEYS
Solar/Wind Harmer
0.358
3145683EARLEYS
Solar/Wind Harmer
0.179
3145683EARLEYS
Solar/Wind Harmer
0.179
315607AA1-063A GEN
Solar/Wind Harmer
0.365
316087AB2-174 GEN
Solar/Wind Harmer
0.005
3137643SOCKMAN
Solar/Wind Harmer
0.704
315652AC1-086 GEN
Solar/Wind Harmer
19.374
970285AG2-188 GEN
Solar/Wind Harmer
13.847
971845AH1-439 GEN
Solar/Wind Harmer
7.933
972205AH1-687 GEN
Adder
7.463
3145796HORNRTN
Solar/Wind Harmer
0.556
3145796HORNRTN
Solar/Wind Harmer
0.07
3146033SCOT NK
Solar/Wind Harmer
0.691
315657AE1-056 GEN
Solar/Wind Harmer
5.923
946301AF1-294 GEN
Solar/Wind Harmer
3.377
961791AG1-021 GEN
Solar/Wind Harmer
1.643
970683AG2-441 GEN
Solar/Wind Harmer
11.355
970681AG2-440 GEN
Solar/Wind Harmer
9.084
970831AG2-522 GEN
Solar/Wind Harmer
7.264
3144303KENBRDG
Solar/Wind Harmer
0.135
971443AH1-215 GEN
Solar/Wind Harmer
2.845
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316005AA1-067
Solar/Wind Harmer
0.179
3145746EVERETS
Solar/Wind Harmer
0.664
3145746EVERETS
Solar/Wind Harmer
0.167
3145746EVERETS
Solar/Wind Harmer
0.167
3145746EVERETS
Solar/Wind Harmer
0.167
970181AG2-120 GEN
Solar/Wind Harmer
2.078
971447AH1-217 GEN
Solar/Wind Harmer
5.04
957861AF2-080 GEN
Solar/Wind Harmer
7.098
316420AA1-050 GEN
Solar/Wind Harmer
0.005
972193AH1-681 GEN
Adder
3.732
316319Z2-044 C
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3138266HYDRAULIC
Solar/Wind Harmer
0.004
3145573BETHELC
Solar/Wind Harmer
0.163
3145573BETHELC
Solar/Wind Harmer
0.163
316118AC1-105 GEN
Solar/Wind Harmer
0.404
3147173SINAI
Solar/Wind Harmer
0.154
3147243WELCO
Solar/Wind Harmer
0.096
270494AE1-108_GEN
Solar/Wind Harmer
1.806
970865AG2-541 GEN
Solar/Wind Harmer
4.891
3148133STUARTS
Solar/Wind Harmer
0.083
3148013FISHERV
Solar/Wind Harmer
0.079
316123AC1-075 GEN
Solar/Wind Harmer
0.181
970165AG2-112 GEN
Solar/Wind Harmer
1.076
970163AG2-111 GEN
Solar/Wind Harmer
1.027
3148463FAIRFLD
Solar/Wind Harmer
0.12
3151881LOWMORC
Adder
1.273
3151881LOWMORC
Adder
1.253
3151861LOWMORA
Adder
1.233
237085AD2-009_GEN
Solar/Wind Helper
1.73
238208AF1-136 C
Solar/Wind Helper
0.215
959381AF2-229 GEN
Solar/Wind Helper
0.375
234033AF1-007_GEN
Solar/Wind Helper
7.236
233923SMA
Solar/Wind Helper
0.988
233990AG1-397 GEN
Solar/Wind Helper
0.278
232432Z2-076 GEN
Solar/Wind Helper
0.069
232436AB1-176 C
Solar/Wind Helper
0.046
233935AB2-179 C
Solar/Wind Helper
1.3
203975AE1-071-GEN
Solar/Wind Helper
2.597
964001AG1-254 GEN
Solar/Wind Helper
0.977
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.027
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.117
219688LUMSOLAR_S C
Solar/Wind Helper
0.041
219607WPEMNERT C
Solar/Wind Helper
0.082
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.097
20715828PEM_W1-120
Solar/Wind Helper
0.097
207459AE1-142 C O1
Solar/Wind Helper
0.295
219620RIDERU C
Solar/Wind Helper
0.001
205943AE1-185 GEN
Solar/Wind Helper
0.503
205956AE1-196_GEN
Solar/Wind Helper
0.502
205932AD2-116_GEN
Solar/Wind Helper
0.502
960921AF2-383 GEN
Solar/Wind Helper
0.358
218526CNTRALGAS2 C
Solar/Wind Helper
0.163
20675528CPH_W2-050
Solar/Wind Helper
0.088
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
966261AG1-495 GEN
Solar/Wind Helper
0.082
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674828DL_W4-046
Solar/Wind Helper
0.008
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.78
316426AA2-053 GEN
Solar/Wind Harmer
0.594
3145593CAROLNA
Solar/Wind Harmer
0.175
3145593CAROLNA
Solar/Wind Harmer
0.175
966811AG1-552 GEN
Solar/Wind Harmer
1.903
3145593CAROLNA
Solar/Wind Harmer
0.218
3146776BUCKING
Solar/Wind Harmer
0.699
3146776BUCKING
Solar/Wind Harmer
0.057
3145783HORNRTN
Solar/Wind Harmer
3.102
3145783HORNRTN
Solar/Wind Harmer
2.482
3145783HORNRTN
Solar/Wind Harmer
0.776
3145783HORNRTN
Solar/Wind Harmer
0.31
3145796HORNRTN
Solar/Wind Harmer
0.521
3147133PAMPLIN
Solar/Wind Harmer
0.172
3147133PAMPLIN
Solar/Wind Harmer
0.137
958211AF2-115 GEN
Solar/Wind Harmer
2.054
963191AG1-168 GEN
Solar/Wind Harmer
0.685
3144293JTRSVLE
Adder
0.545
3144293JTRSVLE
Adder
0.459
3145933PARMELE
Solar/Wind Harmer
0.34
3145933PARMELE
Solar/Wind Harmer
0.17
316274AC1-208 GEN
Solar/Wind Harmer
0.88
316034AC1-036 C
Solar/Wind Harmer
0.012
970323AG2-213 GEN
Solar/Wind Harmer
7.229
971775AH1-396 GEN
Solar/Wind Harmer
0.271
971489AH1-241 GEN
Solar/Wind Harmer
8.948
313527AB2-043 GEN
Solar/Wind Harmer
0.002
939181AE1-148 GEN
Solar/Wind Harmer
8.005
3145493TOT1
Solar/Wind Harmer
0.377
3145453TOT5
Solar/Wind Harmer
0.226
3145603CNETO
Solar/Wind Harmer
0.151
962561AG1-105 GEN
Solar/Wind Harmer
7.712
961601AG1-000A GEN
Solar/Wind Harmer
2.849
316263AC1-034 GEN
Solar/Wind Harmer
6.088
964791AG1-342 GEN
Solar/Wind Harmer
3.061
3146843MT LREL
Solar/Wind Harmer
0.159
3146843MT LREL
Solar/Wind Harmer
0.159
315821AE2-092 GEN
Solar/Wind Harmer
0.01
971761AH1-387 GEN
Solar/Wind Harmer
2.843
316222AC1-221 GEN
Solar/Wind Harmer
0.583
942751AE2-291 GEN
Solar/Wind Harmer
6.934
3132123MT JACKSON
Solar/Wind Harmer
0.381
970117AG2-086 GEN
Solar/Wind Harmer
2.919
970117AG2-086 GEN
Solar/Wind Harmer
1.946
235020AA1-095 C
Solar/Wind Helper
0.059
23777901MDS_W4-102
Solar/Wind Helper
0.197
237034AC2-136 C
Solar/Wind Helper
0.259
23777801MSM_W1-116
Solar/Wind Helper
0.131
237001AB1-127_GEN
Solar/Wind Helper
0.481
237025AB1-124 C
Solar/Wind Helper
0.187
237006AB1-125 GEN
Solar/Wind Helper
0.14
237002AB1-128_GEN
Solar/Wind Helper
0.48
235063AE1-101 C2
Solar/Wind Helper
1.773
20390526W1-045 C
Solar/Wind Helper
0.368
205916AD1-020 GEN
Solar/Wind Helper
1.767
233987AB2-037 GEN
Solar/Wind Helper
2.414
233901CHERRYDALE C
Solar/Wind Helper
0.239
233939AC1-091 C
Solar/Wind Helper
0.361
233970AC1-092 C
Solar/Wind Helper
0.361
232408W1-005 C
Solar/Wind Helper
0.523
232410W1-006 C
Solar/Wind Helper
0.523
233946AB2-136 GEN
Solar/Wind Helper
0.585
234036AF2-325 C
Solar/Wind Helper
0.043
232424Y1-079 C
Solar/Wind Helper
0.12
233944AB2-135 GEN
Solar/Wind Helper
0.605
233933AB2-153 GEN
Solar/Wind Helper
0.239
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.041
219921AF1-264
Solar/Wind Helper
0.052
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.057
963391AG1-188 GEN
Solar/Wind Helper
0.084
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.192
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.017
20673828FLE_V3-070
Solar/Wind Helper
0.092
207442AE1-156 GEN
Solar/Wind Helper
0.329
20676128MHD_W3-029
Solar/Wind Helper
0.097
217081WEATEXAS C
Solar/Wind Helper
0.013
20671828STAW2-080
Solar/Wind Helper
0.027
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20676228FRD_X1-012
Solar/Wind Helper
0.092
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.099
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.074
211065PSPA IPP
Solar/Wind Helper
0.151
211065PSPA IPP
Solar/Wind Helper
0.151
LAGNLTFEXP_LAGN->PJM
CLTF
9.398
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.101
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.667
MECLTFEXP_MEC->PJM
CLTF
5.134
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.867
TVALTFEXP_TVA->PJM
CLTF
4.772
SIGELTFEXP_SIGE->PJM
CLTF
0.16
NYPJM->LTFIMP_NY
CLTF
4.891
LGEELTFEXP_LGEE->PJM
CLTF
2.004
WECLTFEXP_WEC->PJM
CLTF
1.006
CPLELTFEXP_CPLE->PJM
CLTF
10.838
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.117

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:132.78 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5404.52
MW Contribution:8.06
Bus #Bus NameTypeMW Contribution
971507AH1-251 GEN
50/50
17.73
3152251N ANNA1
50/50
14.579
972197AH1-683 GEN
50/50
5.816
972219AH1-694 GEN
50/50
4.188
315052AA1-145 CT2
50/50
2.039
316045AC1-158 PL2
Solar/Wind Harmer
4.87
966881AG1-559 GEN
Solar/Wind Harmer
0.299
3142416OLDCHRC
Solar/Wind Harmer
0.648
3142416OLDCHRC
Solar/Wind Harmer
0.248
3143526WINTERP
Solar/Wind Harmer
1.273
3143096IRON208
Adder
1.025
3150851SPRUNCC
Adder
1.127
3143226MDLTHAN
Solar/Wind Harmer
0.244
3142543TWELFTH
Solar/Wind Harmer
0.023
944631AF1-128 GEN
Adder
115.654
316159AE1-175 C
Solar/Wind Harmer
0.206
970129AG2-093 GEN
Solar/Wind Harmer
6.792
316458AB2-190 GEN2
Solar/Wind Harmer
1.28
315671AE2-027_GEN
Solar/Wind Harmer
15.26
971069AG2-661 GEN
Solar/Wind Harmer
4.23
971647AH1-324 GEN
Solar/Wind Harmer
10.104
971317AH1-138 GEN
Solar/Wind Harmer
1.765
3138126ROCKLANDING
Solar/Wind Harmer
0.108
3142433PROV 92
Solar/Wind Harmer
0.944
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
961611AG1-000B GEN
Solar/Wind Harmer
12.386
971531AH1-263 GEN
50/50
86.379
3150411LDYSMT5
50/50
37.362
3150381LDYSMT2
50/50
35.757
972213AH1-691 GEN
50/50
6.049
972215AH1-692 GEN
50/50
6.049
963051AG1-154 GEN
50/50
4.653
972189AH1-679 GEN
Adder
4.288
316312AB1-027
Solar/Wind Harmer
0.446
316233AE1-074 FULL
Solar/Wind Harmer
0.196
971281AH1-106 GEN
Solar/Wind Harmer
3.397
971283AH1-107 GEN
Solar/Wind Harmer
3.397
971285AH1-108 GEN
Adder
1.844
315976AC1-164 GENA
Solar/Wind Harmer
25.197
316169AC1-164_GENC
Solar/Wind Harmer
21.768
315975AC1-164 GENB
Solar/Wind Harmer
0.745
316164AC1-076 GEN
Solar/Wind Harmer
0.34
316132AB2-190 GEN1
Solar/Wind Harmer
1.28
316369SG1_INVT
Solar/Wind Harmer
0.009
971167AH1-042 GEN
Solar/Wind Harmer
21.021
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
972265AH1-717 GEN
Adder
18.278
3151201GRAVEL4
Adder
17.134
3151191GRAVEL3
Adder
16.917
3151211GRAVEL5
Adder
16.917
971445AH1-216 GEN
Solar/Wind Harmer
16.508
3143316POE
Solar/Wind Harmer
0.927
3143873LANEXA
Solar/Wind Harmer
0.14
3138283WHITEMARSH
Solar/Wind Harmer
0.054
316314AB2-024 C
Solar/Wind Harmer
0.001
3151081ELIZAR1
Adder
21.327
3151091ELIZAR2
Adder
20.956
3152611GOSPORTB
Adder
2.962
3152621GOSPORTC
Adder
2.514
3152601GOSPORTA
Adder
2.319
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.866
315662AE1-191 GEN
Solar/Wind Harmer
0.008
315666AE1-190 GEN
Solar/Wind Harmer
0.002
957871AF2-081 GEN
Solar/Wind Harmer
11.461
3141873WAN 176
Solar/Wind Harmer
0.046
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.158
316311AC2-079 GEN
Solar/Wind Harmer
6.6
319010AE1-072 C
Solar/Wind Harmer
1.156
3146406KITTY HAWK
Solar/Wind Harmer
0.029
316305AF2-043 C
Solar/Wind Harmer
0.002
315835AF2-110_GEN
Solar/Wind Harmer
1.566
313526AB2-022
Solar/Wind Harmer
0.123
3141913WHIT STONE
Solar/Wind Harmer
0.227
3146486SUNBURY
Solar/Wind Harmer
0.227
3152261N ANNA2
50/50
14.578
970497AG2-320 GEN
50/50
26.215
3150401LDYSMT4
50/50
37.246
3150371LDYSMT1
50/50
35.99
315051AA1-145 CT1
50/50
2.03
316044AC1-158 PL1
Solar/Wind Harmer
1.523
316450AC1-158 RIC
Solar/Wind Harmer
0.406
3142416OLDCHRC
Solar/Wind Harmer
2.415
970293AG2-193 GEN
Solar/Wind Harmer
2.624
3143096IRON208
Adder
1.025
3143096IRON208
Adder
1.004
3150861SPRUNCD
Adder
1.127
316473AC1-191 GEN
Solar/Wind Harmer
0.822
3142946ENON
Solar/Wind Harmer
0.081
970133AG2-095 GEN
Solar/Wind Harmer
2.304
316382AG1-145 C
Solar/Wind Harmer
0.002
970129AG2-093 GEN
Solar/Wind Harmer
14.433
315778AD1-151 GEN
Solar/Wind Harmer
19.035
965281AG1-393 GEN
Solar/Wind Harmer
2.538
315839AE2-212 C
Solar/Wind Harmer
0.002
3150921YORKTN3
Adder
5.938
3144216WINCHST
Adder
0.891
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
961611AG1-000B GEN
Solar/Wind Harmer
6.298
315773AC2-141 GEN
Solar/Wind Harmer
8.598
3151221GRAVEL6
Adder
17.114
3151171GRAVELC
Adder
3.293
3145336SMITFLD
Solar/Wind Harmer
0.094
315813AE1-149 C
Solar/Wind Harmer
12.5
3144536CHRHLND
Solar/Wind Harmer
0.035
970659AG2-427 GEN
Solar/Wind Harmer
2.464
944581AF1-123 GEN
Solar/Wind Harmer
52.379
944601AF1-125 GEN
Solar/Wind Harmer
51.572
3151101ELIZAR3
Adder
21.599
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3144873MCLAUGH
Solar/Wind Harmer
0.006
3141766HARMONY
Solar/Wind Harmer
3.092
970661AG2-428 GEN
Solar/Wind Harmer
4.905
3141843SHACKLE
Adder
1.184
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.005
316156AD2-030 GEN
Solar/Wind Harmer
0.17
3141873WAN 176
Solar/Wind Harmer
4.089
3146456SLIGO L269
Solar/Wind Harmer
0.23
971153AH1-033 GEN
Solar/Wind Harmer
2.655
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.224
3146626S HERTFORD
Solar/Wind Harmer
0.223
3145273HOLLAND
Solar/Wind Harmer
0.166
962971AG1-146 GEN
Solar/Wind Harmer
3.551
970009AG2-005 GEN
Solar/Wind Harmer
1.644
3146376EDENTON
Solar/Wind Harmer
0.218
316404AE1-155 C
Solar/Wind Harmer
0.049
315614AA2-178 GEN
Solar/Wind Harmer
1.22
3146486SUNBURY
Solar/Wind Harmer
0.227
3138133OCRAN
Solar/Wind Harmer
0.068
316321Z2-027
Solar/Wind Harmer
0.042
3146396TANGLEW
Solar/Wind Harmer
0.624
3145176PASQUOTANK
Solar/Wind Harmer
0.14
3141783LANCAST
Solar/Wind Harmer
0.135
3141783LANCAST
Solar/Wind Harmer
0.09
316315AB2-025 C
Solar/Wind Harmer
0.18
941031AE2-094 GEN
Solar/Wind Harmer
40.915
944011AF1-069 GEN
Solar/Wind Harmer
13.368
962981AG1-147 GEN
Solar/Wind Harmer
8.287
315814AE2-033 C
Solar/Wind Harmer
17.537
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
970327AG2-215 GEN
Solar/Wind Harmer
7.225
970673AG2-436 GEN
Solar/Wind Harmer
46.61
970673AG2-436 GEN
Solar/Wind Harmer
31.073
3130156CHOWAN
Solar/Wind Harmer
0.218
3130156CHOWAN
Solar/Wind Harmer
0.218
971967AH1-528 GEN
Solar/Wind Harmer
34.545
315816AE2-034 GEN
Solar/Wind Harmer
0.915
3141813NORNECK
Solar/Wind Harmer
0.212
3130546PLYMOUTH
Solar/Wind Harmer
0.209
315732AD1-074 GEN1
Solar/Wind Harmer
1.2
315733AD1-074 GEN2
Solar/Wind Harmer
1.2
315735AD1-075 GEN1
Solar/Wind Harmer
0.6
965291AG1-394 GEN
Solar/Wind Harmer
0.923
3146206CASHIE
Solar/Wind Harmer
0.206
970601AG2-382 GEN
Solar/Wind Harmer
7.712
970085AG2-068 GEN
Solar/Wind Harmer
10.986
970581AG2-369 GEN
Solar/Wind Harmer
9.448
3145893MURPHYS
Solar/Wind Harmer
0.555
3145893MURPHYS
Solar/Wind Harmer
0.206
3145513AHOSKIE
Solar/Wind Harmer
0.424
3145513AHOSKIE
Solar/Wind Harmer
0.203
3145683EARLEYS
Solar/Wind Harmer
0.403
3145683EARLEYS
Solar/Wind Harmer
0.202
3145683EARLEYS
Solar/Wind Harmer
0.202
3146043SEABORD
Solar/Wind Harmer
0.201
315607AA1-063A GEN
Solar/Wind Harmer
0.41
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
21.753
3137643SOCKMAN
Solar/Wind Harmer
0.788
3145796HORNRTN
Solar/Wind Harmer
0.623
3145796HORNRTN
Solar/Wind Harmer
0.078
3146033SCOT NK
Solar/Wind Harmer
0.774
316223AC1-118
Solar/Wind Harmer
0.139
970831AG2-522 GEN
Solar/Wind Harmer
7.995
316005AA1-067
Solar/Wind Harmer
0.2
3145746EVERETS
Solar/Wind Harmer
0.74
3145746EVERETS
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
0.186
970181AG2-120 GEN
Solar/Wind Harmer
2.314
957861AF2-080 GEN
Solar/Wind Harmer
7.879
316420AA1-050 GEN
Solar/Wind Harmer
0.006
3145573BETHELC
Solar/Wind Harmer
0.18
3145573BETHELC
Solar/Wind Harmer
0.18
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
3.007
3144303KENBRDG
Solar/Wind Harmer
0.143
970683AG2-441 GEN
Solar/Wind Harmer
11.901
970681AG2-440 GEN
Solar/Wind Harmer
9.521
946301AF1-294 GEN
Solar/Wind Harmer
3.515
961791AG1-021 GEN
Solar/Wind Harmer
1.71
315657AE1-056 GEN
Solar/Wind Harmer
6.134
970285AG2-188 GEN
Solar/Wind Harmer
13.517
944491AF1-114 GEN
Solar/Wind Harmer
0.001
971845AH1-439 GEN
Solar/Wind Harmer
7.694
316118AC1-105 GEN
Solar/Wind Harmer
0.432
972193AH1-681 GEN
Adder
3.772
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.102
972205AH1-687 GEN
Adder
6.859
971447AH1-217 GEN
Solar/Wind Harmer
4.479
316294AC1-161 GEN
Solar/Wind Harmer
4.079
3151171GRAVELC
Adder
2.504
3145336SMITFLD
Solar/Wind Harmer
0.937
970659AG2-427 GEN
Solar/Wind Harmer
11.263
944591AF1-124 GEN
Solar/Wind Harmer
52.565
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.904
316381AD1-082 GEN
Solar/Wind Harmer
0.242
3141766HARMONY
Solar/Wind Harmer
0.046
970661AG2-428 GEN
Solar/Wind Harmer
23.062
971777AH1-397 GEN
Solar/Wind Harmer
0.612
3141843SHACKLE
Adder
1.184
316072AD1-144
Solar/Wind Harmer
0.084
939411AE1-173 GEN
Solar/Wind Harmer
98.509
940641AE2-051 GEN
Solar/Wind Harmer
18.448
316388AE2-253 GEN
Solar/Wind Harmer
0.722
3146456SLIGO L269
Solar/Wind Harmer
0.23
316246AF1-032 C
Solar/Wind Harmer
0.103
316093AE2-104_GEN
Solar/Wind Harmer
3.838
3138133OCRAN
Solar/Wind Harmer
0.136
3146516WINFALL
Solar/Wind Harmer
0.727
3146516WINFALL
Solar/Wind Harmer
0.224
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.218
962861AG1-135 GEN
Solar/Wind Harmer
6.976
3141726DUNNSVL
Solar/Wind Harmer
0.859
3145663CRESWEL
Solar/Wind Harmer
0.597
971163AH1-040 GEN
Solar/Wind Harmer
17.057
3150351NORNECKC2
Adder
2.113
3143336POWHATN
Solar/Wind Harmer
3.747
970919AG2-571 GEN
Solar/Wind Harmer
7.353
3146206CASHIE
Solar/Wind Harmer
0.206
971547AH1-271 GEN
Solar/Wind Harmer
4.407
316023GEN1_S
Solar/Wind Harmer
0.463
970087AG2-069 GEN
Solar/Wind Harmer
16.479
3145893MURPHYS
Solar/Wind Harmer
0.822
3145893MURPHYS
Solar/Wind Harmer
0.914
3146173TUNIS
Solar/Wind Harmer
0.204
316337AD2-073 GEN
Solar/Wind Harmer
0.177
316336AC2-165 C
Solar/Wind Harmer
0.008
3145683EARLEYS
Solar/Wind Harmer
0.202
3147666LOUISA
Solar/Wind Harmer
0.804
960081AF2-299 GEN
Solar/Wind Harmer
1.928
3146263WOODLND
Solar/Wind Harmer
0.2
3145963POPLR C
Solar/Wind Harmer
0.199
957481AF2-042 GEN
Solar/Wind Harmer
52.836
316011AB1-132 GEN
Solar/Wind Harmer
3.595
962571AG1-106 GEN
Solar/Wind Harmer
2.814
3145823KELFORD
Solar/Wind Harmer
0.198
316190AA2-174 GEN
Solar/Wind Harmer
0
316174AB2-169 GEN
Solar/Wind Harmer
0.005
316192AB2-158 GEN
Solar/Wind Harmer
1.112
971795AH1-408 GEN
Solar/Wind Harmer
13.096
3145783HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.642
3145796HORNRTN
Solar/Wind Harmer
0.195
315693AD1-088 GEN
Solar/Wind Harmer
9.336
3147043LAWRENC
Adder
1.759
962491AG1-098 GEN
Solar/Wind Harmer
11.068
316212AC1-099_GEN
Solar/Wind Harmer
0.984
3146293MARTNCO
Solar/Wind Harmer
0.176
316129AC1-054 GEN
Solar/Wind Harmer
0.701
3145746EVERETS
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
0.186
971065AG2-659 GEN
Solar/Wind Harmer
7.918
315722AD1-056 GEN
Solar/Wind Harmer
1.169
316494AC1-189 GEN
Solar/Wind Harmer
0.617
315687AD1-152 GEN
Solar/Wind Harmer
0.006
961671AG1-007 GEN
Solar/Wind Harmer
0.028
3146083TARBORO
Solar/Wind Harmer
0.18
3145493TOT1
Solar/Wind Harmer
0.8
3146233WITAKRS
Solar/Wind Harmer
0.716
970937AG2-583 GEN
Solar/Wind Harmer
11.013
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970685AG2-442 GEN
Solar/Wind Harmer
13.329
972135AH1-637 GEN
Solar/Wind Harmer
1.522
963171AG1-166 GEN
Solar/Wind Harmer
0.95
971563AH1-280 GEN
Solar/Wind Harmer
1.9
3144293JTRSVLE
Adder
0.567
3145543BTLEBRO
Solar/Wind Harmer
0.176
3145543BTLEBRO
Solar/Wind Harmer
0.141
316359AB2-059 GEN
Solar/Wind Harmer
0.634
316049AB1-081 GEN
Solar/Wind Harmer
1.011
3142053HEARTS
Solar/Wind Harmer
0.311
3146926FARMVIL
Solar/Wind Harmer
0.106
970401AG2-262 GEN
Solar/Wind Harmer
1.001
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.068
972277AH1-723 GEN
Adder
98.366
972003AH1-546 GEN
Solar/Wind Harmer
6.888
316003AC1-222 GEN
Solar/Wind Harmer
0.004
971377AH1-170 GEN
Solar/Wind Harmer
1.612
3147623JAMES R
Solar/Wind Harmer
0.35
3151751LOISA D
Adder
8.04
316254AC1-120 GEN1
Solar/Wind Harmer
0.262
3150351NORNECKC2
Adder
2.148
971781AH1-399 GEN
Solar/Wind Harmer
0.278
316313AB2-026
Solar/Wind Harmer
0.133
316258AE1-075 C
Solar/Wind Harmer
0.159
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
3.185
971157AH1-035 GEN
Solar/Wind Harmer
2.514
315737AD1-076 GEN
Solar/Wind Harmer
2.686
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
970917AG2-570 GEN
Solar/Wind Harmer
18.383
3146206CASHIE
Solar/Wind Harmer
0.206
316365GEN2_N
Solar/Wind Harmer
0.463
3145893MURPHYS
Solar/Wind Harmer
0.344
3145893MURPHYS
Solar/Wind Harmer
0.206
957521AF2-046 GEN
Solar/Wind Harmer
15.264
961681AG1-008 GEN
Solar/Wind Harmer
15.264
3146173TUNIS
Solar/Wind Harmer
0.204
3156021HOLLOMANSOL
Solar/Wind Harmer
0.924
316463AE2-346 GEN
Solar/Wind Harmer
0.174
316140AB2-099
Solar/Wind Harmer
0.072
962331AG1-082 GEN
Solar/Wind Harmer
2.163
3147666LOUISA
Solar/Wind Harmer
0.462
3146263WOODLND
Solar/Wind Harmer
0.2
3145963POPLR C
Solar/Wind Harmer
0.199
313506AB2-031 GEN
Solar/Wind Harmer
0.614
3142666NORTHAMPTON
Solar/Wind Harmer
0.198
316317KELFORD C
Solar/Wind Harmer
0.019
3145823KELFORD
Solar/Wind Harmer
0.198
3145796HORNRTN
Solar/Wind Harmer
0.778
3145796HORNRTN
Solar/Wind Harmer
0.195
3147043LAWRENC
Solar/Wind Harmer
0.117
3141906WESTMOR
Solar/Wind Harmer
0.077
316478AD1-087 GEN
Solar/Wind Harmer
0.667
316486AD2-202 GEN
Solar/Wind Harmer
0.196
316210AC1-098 GEN
Solar/Wind Harmer
1.765
3145933PARMELE
Solar/Wind Harmer
0.19
966801AG1-551 GEN
Solar/Wind Harmer
2.213
3145746EVERETS
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
0.186
315724AD1-057 GEN
Solar/Wind Harmer
0.693
970737AG2-469 GEN
Solar/Wind Harmer
7.863
970909AG2-566 GEN
Solar/Wind Harmer
1.962
316327AA2-057 GEN
Solar/Wind Harmer
0.277
3146073TAR RVR
Solar/Wind Harmer
0.18
3146083TARBORO
Solar/Wind Harmer
0.18
3146233WITAKRS
Solar/Wind Harmer
0.903
3146233WITAKRS
Solar/Wind Harmer
0.122
316131AB2-060 GEN
Solar/Wind Harmer
0.565
3138543CONSLDL
Solar/Wind Harmer
0.118
964241AG1-285 GEN
Solar/Wind Harmer
11.97
315785AD2-033 C
Solar/Wind Harmer
1.456
970257AG2-171 GEN
Solar/Wind Harmer
5.726
959311AF2-222 GEN
Solar/Wind Harmer
15.895
963181AG1-167 GEN
Solar/Wind Harmer
0.712
3144293JTRSVLE
Adder
0.567
3147133PAMPLIN
Solar/Wind Harmer
0.558
971193AH1-056 GEN
Solar/Wind Harmer
10.829
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
961601AG1-000A GEN
Solar/Wind Harmer
12.564
3145543BTLEBRO
Solar/Wind Harmer
0.176
3145543BTLEBRO
Solar/Wind Harmer
0.176
971623AH1-311 GEN
Solar/Wind Harmer
0.353
3146926FARMVIL
Solar/Wind Harmer
0.106
3146776BUCKING
Solar/Wind Harmer
0.061
972255AH1-712 GEN
Adder
84.412
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
6.993
971683AH1-343 GEN
Solar/Wind Harmer
5.591
970221AG2-151 GEN
Solar/Wind Harmer
8.062
316283AC2-100 C
Solar/Wind Harmer
0.29
3132273ORANGE
Solar/Wind Harmer
0.028
3141316ARNOLDS
Adder
0.324
3150331BIRCHWDA
Adder
21.287
3151761LOISA E
Adder
16.391
316170AC1-121 GEN2
Solar/Wind Harmer
0.131
972183AH1-676 GEN
Adder
128.276
3141196NOKESVL
Solar/Wind Helper
1.252
3150391LDYSMT3
50/50
37.176
972195AH1-682 GEN
50/50
4.885
316447AC1-158 HLD
Solar/Wind Harmer
3.348
315673AE1-157 GEN
Solar/Wind Harmer
17.981
957411AF2-035 GEN
Solar/Wind Harmer
11.052
970317AG2-208 GEN
Solar/Wind Harmer
10.239
3142296MT RD221
Adder
0.803
3142366NRTHEST
Adder
0.809
3150691DARBY 3
Adder
17.772
3150701DARBY 4
Adder
17.73
3150681DARBY 2
Adder
17.71
3150671DARBY 1
Adder
17.689
3143526WINTERP
Solar/Wind Harmer
1.273
316075AC2-137 C
Solar/Wind Harmer
0.067
971223AH1-071 GEN
Solar/Wind Harmer
2.604
966871AG1-558 GEN
Solar/Wind Harmer
0.281
3142946ENON
Solar/Wind Harmer
0.024
944641AF1-129 GEN
Adder
114.635
316240AF1-291 C
Solar/Wind Harmer
0.002
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.267
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316036AC1-147 C
Solar/Wind Harmer
0.043
3150991CHESPKB
Adder
2.436
3150991CHESPKB
Adder
2.378
970657AG2-426 GEN
Solar/Wind Harmer
8.137
970657AG2-426 GEN
Solar/Wind Harmer
1.706
316316AC1-027 C
Solar/Wind Harmer
0.223
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.007
3145506HICKORY
Solar/Wind Harmer
0.925
3145506HICKORY
Solar/Wind Harmer
0.555
3145506HICKORY
Solar/Wind Harmer
0.139
316339AD2-160 GEN
Solar/Wind Harmer
0.374
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.129
3137176SLIGO L2192
Solar/Wind Harmer
0.914
3146456SLIGO L269
Solar/Wind Harmer
4.065
3130086AYDLETT
Solar/Wind Harmer
0.917
3146386ELIZ CT
Solar/Wind Harmer
0.227
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.224
3146516WINFALL
Solar/Wind Harmer
0.224
3146516WINFALL
Solar/Wind Harmer
0.224
3146626S HERTFORD
Solar/Wind Harmer
0.223
3146626S HERTFORD
Solar/Wind Harmer
0.223
3144356SAPONY
Solar/Wind Harmer
1.861
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
0.969
3146376EDENTON
Solar/Wind Harmer
0.969
958261AF2-120 GEN
Solar/Wind Harmer
7.183
972185AH1-677 GEN
Adder
12.157
972187AH1-678 GEN
Adder
6.1
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.219
3150341NORNECKC1
Adder
2.202
316468AD1-105 GEN
Solar/Wind Harmer
-0.069
970933AG2-581 GEN
Solar/Wind Harmer
16.879
316065AD1-022 GEN
Solar/Wind Harmer
9.548
3145893MURPHYS
Solar/Wind Harmer
1.376
3145893MURPHYS
Solar/Wind Harmer
0.37
3146173TUNIS
Solar/Wind Harmer
0.204
3146173TUNIS
Solar/Wind Harmer
0.204
316181AB2-040 GEN
Solar/Wind Harmer
0.288
3142666NORTHAMPTON
Solar/Wind Harmer
0.198
3142666NORTHAMPTON
Solar/Wind Harmer
0.198
3142666NORTHAMPTON
Solar/Wind Harmer
0.198
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
970099AG2-077 GEN
Solar/Wind Harmer
21.134
316426AA2-053 GEN
Solar/Wind Harmer
0.666
3145593CAROLNA
Solar/Wind Harmer
0.196
3145593CAROLNA
Solar/Wind Harmer
0.196
966811AG1-552 GEN
Solar/Wind Harmer
2.127
3145593CAROLNA
Solar/Wind Harmer
0.244
3145783HORNRTN
Solar/Wind Harmer
3.466
3145783HORNRTN
Solar/Wind Harmer
2.773
3145783HORNRTN
Solar/Wind Harmer
0.866
3145783HORNRTN
Solar/Wind Harmer
0.347
3145796HORNRTN
Solar/Wind Harmer
0.584
3145933PARMELE
Solar/Wind Harmer
0.38
3145933PARMELE
Solar/Wind Harmer
0.19
316274AC1-208 GEN
Solar/Wind Harmer
0.98
971741AH1-377 GEN
Solar/Wind Harmer
18.489
970301AG2-198 GEN
Solar/Wind Harmer
7.849
939181AE1-148 GEN
Solar/Wind Harmer
8.688
3145493TOT1
Solar/Wind Harmer
0.417
3145453TOT5
Solar/Wind Harmer
0.25
3145603CNETO
Solar/Wind Harmer
0.167
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.634
971775AH1-396 GEN
Solar/Wind Harmer
0.286
958211AF2-115 GEN
Solar/Wind Harmer
2.137
963191AG1-168 GEN
Solar/Wind Harmer
0.712
3144293JTRSVLE
Adder
0.567
3144293JTRSVLE
Adder
0.477
3147133PAMPLIN
Solar/Wind Harmer
0.178
3147133PAMPLIN
Solar/Wind Harmer
0.142
961601AG1-000A GEN
Solar/Wind Harmer
3.141
316263AC1-034 GEN
Solar/Wind Harmer
6.71
962561AG1-105 GEN
Solar/Wind Harmer
8.256
964791AG1-342 GEN
Solar/Wind Harmer
3.275
3146843MT LREL
Solar/Wind Harmer
0.17
3146843MT LREL
Solar/Wind Harmer
0.17
3146776BUCKING
Solar/Wind Harmer
0.676
3146776BUCKING
Solar/Wind Harmer
0.055
971489AH1-241 GEN
Solar/Wind Harmer
8.062
316222AC1-221 GEN
Solar/Wind Harmer
0.618
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
6.907
966001AG1-469 GEN
Solar/Wind Harmer
0.072
3151731LOISA B
Adder
8.04
3151721LOISA A
Adder
7.998
970865AG2-541 GEN
Solar/Wind Harmer
5.067
316123AC1-075 GEN
Solar/Wind Harmer
0.184
970165AG2-112 GEN
Solar/Wind Harmer
1.09
970163AG2-111 GEN
Solar/Wind Harmer
1.039
270494AE1-108_GEN
Solar/Wind Harmer
1.609
3147346CASHSCORNER
Solar/Wind Harmer
0.278
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316411AF1-147_GEN1
Solar/Wind Helper
0.807
316415AF1-147_GEN2
Solar/Wind Helper
0.807
3138216PACIFIC
Solar/Wind Helper
0.039
LAGNLTFEXP_LAGN->PJM
CLTF
8.029
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.423
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.85
MECLTFEXP_MEC->PJM
CLTF
3.626
SIGELTFEXP_SIGE->PJM
CLTF
0.111
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.001
TVALTFEXP_TVA->PJM
CLTF
4.071
NYPJM->LTFIMP_NY
CLTF
3.261
LGEELTFEXP_LGEE->PJM
CLTF
1.336
WECLTFEXP_WEC->PJM
CLTF
0.644
CPLELTFEXP_CPLE->PJM
CLTF
11.392
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.447

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.02 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5007.08
MW Contribution:7.84
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
14.366
970497AG2-320 GEN
50/50
25.942
3150401LDYSMT4
50/50
36.865
3150371LDYSMT1
50/50
35.621
315051AA1-145 CT1
50/50
2.006
3142416OLDCHRC
Solar/Wind Harmer
2.384
970293AG2-193 GEN
Solar/Wind Harmer
2.591
3143096IRON208
Adder
1.011
3143096IRON208
Adder
0.991
3150861SPRUNCD
Adder
1.112
316473AC1-191 GEN
Solar/Wind Harmer
0.812
3142946ENON
Solar/Wind Harmer
0.08
970133AG2-095 GEN
Solar/Wind Harmer
2.274
316382AG1-145 C
Solar/Wind Harmer
0.002
970129AG2-093 GEN
Solar/Wind Harmer
14.245
315778AD1-151 GEN
Solar/Wind Harmer
18.787
965281AG1-393 GEN
Solar/Wind Harmer
2.505
315839AE2-212 C
Solar/Wind Harmer
0.002
3150921YORKTN3
Adder
5.862
3144216WINCHST
Adder
0.879
3142433PROV 92
Adder
0.453
3142433PROV 92
Adder
0.453
961611AG1-000B GEN
Solar/Wind Harmer
6.216
315773AC2-141 GEN
Solar/Wind Harmer
8.485
3151221GRAVEL6
Adder
16.891
3151171GRAVELC
Adder
3.25
3145336SMITFLD
Solar/Wind Harmer
0.093
315813AE1-149 C
Solar/Wind Harmer
12.335
3144536CHRHLND
Solar/Wind Harmer
0.034
970659AG2-427 GEN
Solar/Wind Harmer
2.431
944581AF1-123 GEN
Solar/Wind Harmer
51.69
944601AF1-125 GEN
Solar/Wind Harmer
50.894
3151101ELIZAR3
Adder
21.316
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3152251N ANNA1
50/50
14.367
972197AH1-683 GEN
50/50
5.757
972219AH1-694 GEN
50/50
4.145
315052AA1-145 CT2
50/50
2.014
966881AG1-559 GEN
Solar/Wind Harmer
0.296
3142416OLDCHRC
Solar/Wind Harmer
0.639
3142416OLDCHRC
Solar/Wind Harmer
0.245
3143526WINTERP
Solar/Wind Harmer
1.255
3143096IRON208
Adder
1.011
3150851SPRUNCC
Adder
1.112
3142543TWELFTH
Solar/Wind Harmer
0.023
3143226MDLTHAN
Solar/Wind Harmer
0.24
944631AF1-128 GEN
Adder
114.169
316159AE1-175 C
Solar/Wind Harmer
0.204
970129AG2-093 GEN
Solar/Wind Harmer
6.704
316458AB2-190 GEN2
Solar/Wind Harmer
1.264
315671AE2-027_GEN
Solar/Wind Harmer
15.06
971069AG2-661 GEN
Solar/Wind Harmer
4.175
971647AH1-324 GEN
Solar/Wind Harmer
9.972
971317AH1-138 GEN
Solar/Wind Harmer
1.742
3138126ROCKLANDING
Solar/Wind Harmer
0.107
3142433PROV 92
Solar/Wind Harmer
0.932
3142433PROV 92
Adder
0.453
3142433PROV 92
Adder
0.453
961611AG1-000B GEN
Solar/Wind Harmer
12.225
316294AC1-161 GEN
Solar/Wind Harmer
4.025
3151171GRAVELC
Adder
2.471
3145336SMITFLD
Solar/Wind Harmer
0.925
970659AG2-427 GEN
Solar/Wind Harmer
11.115
944591AF1-124 GEN
Solar/Wind Harmer
51.874
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.866
316381AD1-082 GEN
Solar/Wind Harmer
0.239
3141766HARMONY
Solar/Wind Harmer
0.046
971777AH1-397 GEN
Solar/Wind Harmer
0.604
3141843SHACKLE
Adder
1.169
970661AG2-428 GEN
Solar/Wind Harmer
22.759
316072AD1-144
Solar/Wind Harmer
0.082
3144873MCLAUGH
Solar/Wind Harmer
0.006
3141766HARMONY
Solar/Wind Harmer
3.053
3141843SHACKLE
Adder
1.169
970661AG2-428 GEN
Solar/Wind Harmer
4.841
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.005
316156AD2-030 GEN
Solar/Wind Harmer
0.168
3141873WAN 176
Solar/Wind Harmer
4.038
3146456SLIGO L269
Solar/Wind Harmer
0.227
971153AH1-033 GEN
Solar/Wind Harmer
2.621
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.221
3146626S HERTFORD
Solar/Wind Harmer
0.22
962971AG1-146 GEN
Solar/Wind Harmer
3.508
3145273HOLLAND
Solar/Wind Harmer
0.164
970009AG2-005 GEN
Solar/Wind Harmer
1.624
3146376EDENTON
Solar/Wind Harmer
0.215
316404AE1-155 C
Solar/Wind Harmer
0.048
315614AA2-178 GEN
Solar/Wind Harmer
1.204
3150351NORNECKC2
Adder
2.123
971781AH1-399 GEN
Solar/Wind Harmer
0.275
316313AB2-026
Solar/Wind Harmer
0.13
316258AE1-075 C
Solar/Wind Harmer
0.156
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
3.126
971157AH1-035 GEN
Solar/Wind Harmer
2.481
315737AD1-076 GEN
Solar/Wind Harmer
2.651
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
970917AG2-570 GEN
Solar/Wind Harmer
18.132
3146206CASHIE
Solar/Wind Harmer
0.204
316365GEN2_N
Solar/Wind Harmer
0.456
3145893MURPHYS
Solar/Wind Harmer
0.34
3145893MURPHYS
Solar/Wind Harmer
0.203
957521AF2-046 GEN
Solar/Wind Harmer
15.061
961681AG1-008 GEN
Solar/Wind Harmer
15.061
3146173TUNIS
Solar/Wind Harmer
0.201
3156021HOLLOMANSOL
Solar/Wind Harmer
0.911
316463AE2-346 GEN
Solar/Wind Harmer
0.172
316140AB2-099
Solar/Wind Harmer
0.071
962331AG1-082 GEN
Solar/Wind Harmer
2.134
3146263WOODLND
Solar/Wind Harmer
0.197
3145963POPLR C
Solar/Wind Harmer
0.196
313506AB2-031 GEN
Solar/Wind Harmer
0.605
3142666NORTHAMPTON
Solar/Wind Harmer
0.196
316317KELFORD C
Solar/Wind Harmer
0.019
3145823KELFORD
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.768
3145796HORNRTN
Solar/Wind Harmer
0.192
3147043LAWRENC
Solar/Wind Harmer
0.115
3141906WESTMOR
Solar/Wind Harmer
0.076
3147666LOUISA
Solar/Wind Harmer
0.435
316478AD1-087 GEN
Solar/Wind Harmer
0.657
316486AD2-202 GEN
Solar/Wind Harmer
0.193
316210AC1-098 GEN
Solar/Wind Harmer
1.741
3145933PARMELE
Solar/Wind Harmer
0.187
966801AG1-551 GEN
Solar/Wind Harmer
2.184
3145746EVERETS
Solar/Wind Harmer
0.183
3145746EVERETS
Solar/Wind Harmer
0.183
970737AG2-469 GEN
Solar/Wind Harmer
7.78
315724AD1-057 GEN
Solar/Wind Harmer
0.684
3150391LDYSMT3
50/50
36.796
972195AH1-682 GEN
50/50
4.835
315673AE1-157 GEN
Solar/Wind Harmer
17.789
957411AF2-035 GEN
Solar/Wind Harmer
10.93
970317AG2-208 GEN
Solar/Wind Harmer
10.126
3142296MT RD221
Adder
0.793
3142366NRTHEST
Adder
0.798
3150691DARBY 3
Adder
17.545
3150701DARBY 4
Adder
17.505
3150681DARBY 2
Adder
17.484
3150671DARBY 1
Adder
17.464
316075AC2-137 C
Solar/Wind Harmer
0.066
3143526WINTERP
Solar/Wind Harmer
1.255
971223AH1-071 GEN
Solar/Wind Harmer
2.567
966871AG1-558 GEN
Solar/Wind Harmer
0.278
3142946ENON
Solar/Wind Harmer
0.024
944641AF1-129 GEN
Adder
113.139
316240AF1-291 C
Solar/Wind Harmer
0.002
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.263
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316036AC1-147 C
Solar/Wind Harmer
0.043
3150991CHESPKB
Adder
2.404
3150991CHESPKB
Adder
2.347
970657AG2-426 GEN
Solar/Wind Harmer
8.03
970657AG2-426 GEN
Solar/Wind Harmer
1.684
316316AC1-027 C
Solar/Wind Harmer
0.22
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.007
3145506HICKORY
Solar/Wind Harmer
0.912
3145506HICKORY
Solar/Wind Harmer
0.547
3145506HICKORY
Solar/Wind Harmer
0.137
316339AD2-160 GEN
Solar/Wind Harmer
0.369
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.127
3137176SLIGO L2192
Solar/Wind Harmer
0.902
3146456SLIGO L269
Solar/Wind Harmer
4.012
3130086AYDLETT
Solar/Wind Harmer
0.905
3146386ELIZ CT
Solar/Wind Harmer
0.224
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.221
3146516WINFALL
Solar/Wind Harmer
0.221
3146516WINFALL
Solar/Wind Harmer
0.221
3146626S HERTFORD
Solar/Wind Harmer
0.22
3146626S HERTFORD
Solar/Wind Harmer
0.22
3144356SAPONY
Solar/Wind Harmer
1.836
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
0.957
3146376EDENTON
Solar/Wind Harmer
0.957
958261AF2-120 GEN
Solar/Wind Harmer
7.097
972185AH1-677 GEN
Adder
11.991
972187AH1-678 GEN
Adder
6.016
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.193
3150341NORNECKC1
Adder
2.176
316468AD1-105 GEN
Solar/Wind Harmer
-0.068
970933AG2-581 GEN
Solar/Wind Harmer
16.641
316065AD1-022 GEN
Solar/Wind Harmer
9.423
3145893MURPHYS
Solar/Wind Harmer
1.358
3145893MURPHYS
Solar/Wind Harmer
0.365
3146173TUNIS
Solar/Wind Harmer
0.201
3146173TUNIS
Solar/Wind Harmer
0.201
316181AB2-040 GEN
Solar/Wind Harmer
0.284
3142666NORTHAMPTON
Solar/Wind Harmer
0.196
3142666NORTHAMPTON
Solar/Wind Harmer
0.196
3142666NORTHAMPTON
Solar/Wind Harmer
0.196
3142666NORTHAMPTON
Solar/Wind Harmer
0.117
970099AG2-077 GEN
Solar/Wind Harmer
20.826
316426AA2-053 GEN
Solar/Wind Harmer
0.657
3145593CAROLNA
Solar/Wind Harmer
0.193
3145593CAROLNA
Solar/Wind Harmer
0.193
966811AG1-552 GEN
Solar/Wind Harmer
2.098
3145593CAROLNA
Solar/Wind Harmer
0.241
3145783HORNRTN
Solar/Wind Harmer
3.419
3145783HORNRTN
Solar/Wind Harmer
2.735
3145783HORNRTN
Solar/Wind Harmer
0.855
3145783HORNRTN
Solar/Wind Harmer
0.342
3145796HORNRTN
Solar/Wind Harmer
0.576
3145933PARMELE
Solar/Wind Harmer
0.375
3145933PARMELE
Solar/Wind Harmer
0.187
316274AC1-208 GEN
Solar/Wind Harmer
0.967
971741AH1-377 GEN
Solar/Wind Harmer
18.163
970301AG2-198 GEN
Solar/Wind Harmer
7.705
939181AE1-148 GEN
Solar/Wind Harmer
8.56
3145493TOT1
Solar/Wind Harmer
0.412
3145453TOT5
Solar/Wind Harmer
0.247
3145603CNETO
Solar/Wind Harmer
0.165
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.506
971775AH1-396 GEN
Solar/Wind Harmer
0.281
958211AF2-115 GEN
Solar/Wind Harmer
2.099
963191AG1-168 GEN
Solar/Wind Harmer
0.7
3144293JTRSVLE
Adder
0.557
3144293JTRSVLE
Adder
0.469
3147133PAMPLIN
Solar/Wind Harmer
0.174
3147133PAMPLIN
Solar/Wind Harmer
0.139
961601AG1-000A GEN
Solar/Wind Harmer
3.1
316263AC1-034 GEN
Solar/Wind Harmer
6.622
962561AG1-105 GEN
Solar/Wind Harmer
8.133
964791AG1-342 GEN
Solar/Wind Harmer
3.227
3146843MT LREL
Solar/Wind Harmer
0.168
3146843MT LREL
Solar/Wind Harmer
0.168
3146776BUCKING
Solar/Wind Harmer
0.66
3146776BUCKING
Solar/Wind Harmer
0.053
971489AH1-241 GEN
Solar/Wind Harmer
7.84
316222AC1-221 GEN
Solar/Wind Harmer
0.61
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
6.812
316447AC1-158 HLD
Solar/Wind Helper
4.161
316327AA2-057 GEN
Solar/Wind Harmer
0.273
970909AG2-566 GEN
Solar/Wind Harmer
1.926
3146073TAR RVR
Solar/Wind Harmer
0.178
3146083TARBORO
Solar/Wind Harmer
0.178
3146233WITAKRS
Solar/Wind Harmer
0.891
3146233WITAKRS
Solar/Wind Harmer
0.121
3138543CONSLDL
Solar/Wind Harmer
0.117
316131AB2-060 GEN
Solar/Wind Harmer
0.557
964241AG1-285 GEN
Solar/Wind Harmer
11.779
315785AD2-033 C
Solar/Wind Harmer
1.432
970257AG2-171 GEN
Solar/Wind Harmer
5.629
959311AF2-222 GEN
Solar/Wind Harmer
15.624
963181AG1-167 GEN
Solar/Wind Harmer
0.7
3144293JTRSVLE
Adder
0.557
3147133PAMPLIN
Solar/Wind Harmer
0.548
971193AH1-056 GEN
Solar/Wind Harmer
10.629
961601AG1-000A GEN
Solar/Wind Harmer
12.399
3145543BTLEBRO
Solar/Wind Harmer
0.174
3145543BTLEBRO
Solar/Wind Harmer
0.174
971623AH1-311 GEN
Solar/Wind Harmer
0.349
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.104
3146776BUCKING
Solar/Wind Harmer
0.059
972255AH1-712 GEN
Adder
83.19
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
6.893
971683AH1-343 GEN
Solar/Wind Harmer
5.511
970221AG2-151 GEN
Solar/Wind Harmer
7.84
316283AC2-100 C
Solar/Wind Harmer
0.286
3141316ARNOLDS
Adder
0.322
3150331BIRCHWDA
Adder
21.148
316044AC1-158 PL1
Solar/Wind Helper
1.891
316450AC1-158 RIC
Solar/Wind Helper
0.504
3141196NOKESVL
Solar/Wind Helper
1.226
971531AH1-263 GEN
50/50
73.177
3150411LDYSMT5
50/50
36.98
3150381LDYSMT2
50/50
35.391
972213AH1-691 GEN
50/50
5.987
972215AH1-692 GEN
50/50
5.987
963051AG1-154 GEN
50/50
4.605
972189AH1-679 GEN
Adder
4.237
316312AB1-027
Solar/Wind Harmer
0.44
316233AE1-074 FULL
Solar/Wind Harmer
0.193
971281AH1-106 GEN
Solar/Wind Harmer
3.35
971283AH1-107 GEN
Solar/Wind Harmer
3.35
971285AH1-108 GEN
Adder
1.819
315976AC1-164 GENA
Solar/Wind Harmer
24.88
316169AC1-164_GENC
Solar/Wind Harmer
21.494
315975AC1-164 GENB
Solar/Wind Harmer
0.736
316132AB2-190 GEN1
Solar/Wind Harmer
1.264
316369SG1_INVT
Solar/Wind Harmer
0.009
971167AH1-042 GEN
Solar/Wind Harmer
20.755
3142433PROV 92
Adder
0.453
3142433PROV 92
Adder
0.453
972265AH1-717 GEN
Adder
18.039
3151201GRAVEL4
Adder
16.911
3151191GRAVEL3
Adder
16.697
3151211GRAVEL5
Adder
16.697
971445AH1-216 GEN
Solar/Wind Harmer
16.292
3143316POE
Solar/Wind Harmer
0.915
3143873LANEXA
Solar/Wind Harmer
0.139
3138283WHITEMARSH
Solar/Wind Harmer
0.053
316314AB2-024 C
Solar/Wind Harmer
0.001
3151081ELIZAR1
Adder
21.046
3151091ELIZAR2
Adder
20.681
3152611GOSPORTB
Adder
2.923
3152621GOSPORTC
Adder
2.481
3152601GOSPORTA
Adder
2.288
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.781
315662AE1-191 GEN
Solar/Wind Harmer
0.008
315666AE1-190 GEN
Solar/Wind Harmer
0.002
957871AF2-081 GEN
Solar/Wind Harmer
11.31
3141873WAN 176
Solar/Wind Harmer
0.045
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.155
316311AC2-079 GEN
Solar/Wind Harmer
6.513
319010AE1-072 C
Solar/Wind Harmer
1.141
3146406KITTY HAWK
Solar/Wind Harmer
0.028
316305AF2-043 C
Solar/Wind Harmer
0.002
315835AF2-110_GEN
Solar/Wind Harmer
1.545
3141913WHIT STONE
Solar/Wind Harmer
0.224
313526AB2-022
Solar/Wind Harmer
0.121
3138133OCRAN
Solar/Wind Harmer
0.067
3146486SUNBURY
Solar/Wind Harmer
0.224
3146486SUNBURY
Solar/Wind Harmer
0.224
316321Z2-027
Solar/Wind Harmer
0.041
3146396TANGLEW
Solar/Wind Harmer
0.616
3145176PASQUOTANK
Solar/Wind Harmer
0.138
3141783LANCAST
Solar/Wind Harmer
0.133
3141783LANCAST
Solar/Wind Harmer
0.089
316315AB2-025 C
Solar/Wind Harmer
0.177
962981AG1-147 GEN
Solar/Wind Harmer
8.186
941031AE2-094 GEN
Solar/Wind Harmer
40.356
944011AF1-069 GEN
Solar/Wind Harmer
13.186
315814AE2-033 C
Solar/Wind Harmer
17.302
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
970327AG2-215 GEN
Solar/Wind Harmer
7.138
970673AG2-436 GEN
Solar/Wind Harmer
45.972
970673AG2-436 GEN
Solar/Wind Harmer
30.648
3130156CHOWAN
Solar/Wind Harmer
0.215
3130156CHOWAN
Solar/Wind Harmer
0.215
971967AH1-528 GEN
Solar/Wind Harmer
34.067
315816AE2-034 GEN
Solar/Wind Harmer
0.903
3141813NORNECK
Solar/Wind Harmer
0.209
3130546PLYMOUTH
Solar/Wind Harmer
0.207
315732AD1-074 GEN1
Solar/Wind Harmer
1.184
315733AD1-074 GEN2
Solar/Wind Harmer
1.184
315735AD1-075 GEN1
Solar/Wind Harmer
0.593
965291AG1-394 GEN
Solar/Wind Harmer
0.91
3146206CASHIE
Solar/Wind Harmer
0.204
970601AG2-382 GEN
Solar/Wind Harmer
7.61
970085AG2-068 GEN
Solar/Wind Harmer
10.836
970581AG2-369 GEN
Solar/Wind Harmer
9.319
3145893MURPHYS
Solar/Wind Harmer
0.548
3145893MURPHYS
Solar/Wind Harmer
0.203
3145513AHOSKIE
Solar/Wind Harmer
0.418
3145513AHOSKIE
Solar/Wind Harmer
0.2
3145683EARLEYS
Solar/Wind Harmer
0.398
3145683EARLEYS
Solar/Wind Harmer
0.199
3145683EARLEYS
Solar/Wind Harmer
0.199
3146043SEABORD
Solar/Wind Harmer
0.198
315607AA1-063A GEN
Solar/Wind Harmer
0.404
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
21.462
3137643SOCKMAN
Solar/Wind Harmer
0.777
3145796HORNRTN
Solar/Wind Harmer
0.615
3145796HORNRTN
Solar/Wind Harmer
0.077
3146033SCOT NK
Solar/Wind Harmer
0.764
316223AC1-118
Solar/Wind Harmer
0.137
970831AG2-522 GEN
Solar/Wind Harmer
7.881
316005AA1-067
Solar/Wind Harmer
0.197
3145746EVERETS
Solar/Wind Harmer
0.73
3145746EVERETS
Solar/Wind Harmer
0.183
3145746EVERETS
Solar/Wind Harmer
0.183
3145746EVERETS
Solar/Wind Harmer
0.183
970181AG2-120 GEN
Solar/Wind Harmer
2.284
957861AF2-080 GEN
Solar/Wind Harmer
7.776
316420AA1-050 GEN
Solar/Wind Harmer
0.006
3145573BETHELC
Solar/Wind Harmer
0.178
3145573BETHELC
Solar/Wind Harmer
0.178
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
2.956
3144303KENBRDG
Solar/Wind Harmer
0.141
970683AG2-441 GEN
Solar/Wind Harmer
11.694
970681AG2-440 GEN
Solar/Wind Harmer
9.355
946301AF1-294 GEN
Solar/Wind Harmer
3.451
961791AG1-021 GEN
Solar/Wind Harmer
1.679
315657AE1-056 GEN
Solar/Wind Harmer
6.021
944491AF1-114 GEN
Solar/Wind Harmer
0.001
970285AG2-188 GEN
Solar/Wind Harmer
13.206
971845AH1-439 GEN
Solar/Wind Harmer
7.514
316118AC1-105 GEN
Solar/Wind Harmer
0.425
972193AH1-681 GEN
Adder
3.717
3147173SINAI
Solar/Wind Harmer
0.161
3147243WELCO
Solar/Wind Harmer
0.101
972205AH1-687 GEN
Adder
6.67
970865AG2-541 GEN
Solar/Wind Harmer
4.995
971447AH1-217 GEN
Solar/Wind Harmer
4.355
939411AE1-173 GEN
Solar/Wind Harmer
97.185
940641AE2-051 GEN
Solar/Wind Harmer
18.198
316388AE2-253 GEN
Solar/Wind Harmer
0.712
3146456SLIGO L269
Solar/Wind Harmer
0.227
316246AF1-032 C
Solar/Wind Harmer
0.102
316093AE2-104_GEN
Solar/Wind Harmer
3.787
3138133OCRAN
Solar/Wind Harmer
0.134
3146516WINFALL
Solar/Wind Harmer
0.717
3146516WINFALL
Solar/Wind Harmer
0.221
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
962861AG1-135 GEN
Solar/Wind Harmer
6.892
3130156CHOWAN
Solar/Wind Harmer
0.215
3141726DUNNSVL
Solar/Wind Harmer
0.848
3145663CRESWEL
Solar/Wind Harmer
0.589
971163AH1-040 GEN
Solar/Wind Harmer
16.833
3150351NORNECKC2
Adder
2.088
3143336POWHATN
Solar/Wind Harmer
3.678
970919AG2-571 GEN
Solar/Wind Harmer
7.253
3146206CASHIE
Solar/Wind Harmer
0.204
971547AH1-271 GEN
Solar/Wind Harmer
4.349
316023GEN1_S
Solar/Wind Harmer
0.456
970087AG2-069 GEN
Solar/Wind Harmer
16.254
3145893MURPHYS
Solar/Wind Harmer
0.811
3145893MURPHYS
Solar/Wind Harmer
0.902
3146173TUNIS
Solar/Wind Harmer
0.201
316337AD2-073 GEN
Solar/Wind Harmer
0.175
3145683EARLEYS
Solar/Wind Harmer
0.199
316336AC2-165 C
Solar/Wind Harmer
0.008
960081AF2-299 GEN
Solar/Wind Harmer
1.901
3146263WOODLND
Solar/Wind Harmer
0.197
3145963POPLR C
Solar/Wind Harmer
0.196
957481AF2-042 GEN
Solar/Wind Harmer
52.064
316011AB1-132 GEN
Solar/Wind Harmer
3.547
962571AG1-106 GEN
Solar/Wind Harmer
2.776
3145823KELFORD
Solar/Wind Harmer
0.195
316190AA2-174 GEN
Solar/Wind Harmer
0
316174AB2-169 GEN
Solar/Wind Harmer
0.005
971795AH1-408 GEN
Solar/Wind Harmer
12.912
3145783HORNRTN
Solar/Wind Harmer
0.192
3145796HORNRTN
Solar/Wind Harmer
0.634
3145796HORNRTN
Solar/Wind Harmer
0.192
3147043LAWRENC
Adder
1.734
315693AD1-088 GEN
Solar/Wind Harmer
9.193
962491AG1-098 GEN
Solar/Wind Harmer
10.897
3147666LOUISA
Solar/Wind Harmer
0.757
316212AC1-099_GEN
Solar/Wind Harmer
0.971
3146293MARTNCO
Solar/Wind Harmer
0.174
316192AB2-158 GEN
Solar/Wind Harmer
1.044
316129AC1-054 GEN
Solar/Wind Harmer
0.691
3145746EVERETS
Solar/Wind Harmer
0.183
3145746EVERETS
Solar/Wind Harmer
0.183
971065AG2-659 GEN
Solar/Wind Harmer
7.805
315722AD1-056 GEN
Solar/Wind Harmer
1.154
316494AC1-189 GEN
Solar/Wind Harmer
0.609
315687AD1-152 GEN
Solar/Wind Harmer
0.006
961671AG1-007 GEN
Solar/Wind Harmer
0.027
3146083TARBORO
Solar/Wind Harmer
0.178
3145493TOT1
Solar/Wind Harmer
0.79
3146233WITAKRS
Solar/Wind Harmer
0.707
316237AB2-079_GEN
Solar/Wind Harmer
0.001
972135AH1-637 GEN
Solar/Wind Harmer
1.506
970685AG2-442 GEN
Solar/Wind Harmer
13.097
970937AG2-583 GEN
Solar/Wind Harmer
10.754
963171AG1-166 GEN
Solar/Wind Harmer
0.933
971563AH1-280 GEN
Solar/Wind Harmer
1.866
3144293JTRSVLE
Adder
0.557
3145543BTLEBRO
Solar/Wind Harmer
0.174
3145543BTLEBRO
Solar/Wind Harmer
0.139
316359AB2-059 GEN
Solar/Wind Harmer
0.626
316049AB1-081 GEN
Solar/Wind Harmer
0.997
3142053HEARTS
Solar/Wind Harmer
0.307
3146926FARMVIL
Solar/Wind Harmer
0.104
970401AG2-262 GEN
Solar/Wind Harmer
0.986
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.066
972277AH1-723 GEN
Adder
96.942
972003AH1-546 GEN
Solar/Wind Harmer
6.703
316003AC1-222 GEN
Solar/Wind Harmer
0.004
971377AH1-170 GEN
Solar/Wind Harmer
1.568
3147623JAMES R
Solar/Wind Harmer
0.341
316045AC1-158 PL2
Solar/Wind Helper
6.052
316006AB2-029 C
Solar/Wind Helper
0.11
316123AC1-075 GEN
Solar/Wind Harmer
0.181
970165AG2-112 GEN
Solar/Wind Harmer
1.074
970163AG2-111 GEN
Solar/Wind Harmer
1.025
270494AE1-108_GEN
Solar/Wind Harmer
1.568
316411AF1-147_GEN1
Solar/Wind Helper
0.784
316415AF1-147_GEN2
Solar/Wind Helper
0.784
3138216PACIFIC
Solar/Wind Helper
0.038
LAGNLTFEXP_LAGN->PJM
CLTF
8.007
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.991
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.831
MECLTFEXP_MEC->PJM
CLTF
3.667
SIGELTFEXP_SIGE->PJM
CLTF
0.112
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.726
TVALTFEXP_TVA->PJM
CLTF
4.059
NYPJM->LTFIMP_NY
CLTF
3.144
LGEELTFEXP_LGEE->PJM
CLTF
1.356
WECLTFEXP_WEC->PJM
CLTF
0.657
CPLELTFEXP_CPLE->PJM
CLTF
11.252
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.535

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:173.01 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:7041.78
MW Contribution:10.63
Bus #Bus NameTypeMW Contribution
971645AH1-323 GEN
50/50
34.852
3151161SURRY 1
50/50
14.066
3142416OLDCHRC
Solar/Wind Harmer
3.771
970293AG2-193 GEN
Solar/Wind Harmer
4.092
3142946ENON
Solar/Wind Harmer
0.127
316382AG1-145 C
Solar/Wind Harmer
0.003
3143096IRON208
Adder
1.57
3143096IRON208
Adder
1.539
3150921YORKTN3
Adder
9.356
3144216WINCHST
Adder
1.402
315773AC2-141 GEN
Solar/Wind Harmer
13.538
970133AG2-095 GEN
Solar/Wind Harmer
3.544
970129AG2-093 GEN
Solar/Wind Harmer
22.266
315778AD1-151 GEN
Solar/Wind Harmer
29.426
961611AG1-000B GEN
Solar/Wind Harmer
9.778
3151221GRAVEL6
Adder
26.624
3151171GRAVELC
Adder
5.122
3150861SPRUNCD
Adder
1.682
3145336SMITFLD
Solar/Wind Harmer
0.146
3144536CHRHLND
Solar/Wind Harmer
0.054
944581AF1-123 GEN
Solar/Wind Harmer
81.792
944601AF1-125 GEN
Solar/Wind Harmer
80.532
3151101ELIZAR3
Adder
33.706
3144873MCLAUGH
Solar/Wind Harmer
0.009
965281AG1-393 GEN
Solar/Wind Harmer
3.845
315839AE2-212 C
Solar/Wind Harmer
0.003
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
3146456SLIGO L269
Solar/Wind Harmer
0.358
971153AH1-033 GEN
Solar/Wind Harmer
4.14
316473AC1-191 GEN
Solar/Wind Harmer
1.209
315813AE1-149 C
Solar/Wind Harmer
19.023
970659AG2-427 GEN
Solar/Wind Harmer
3.767
316083AB2-161 GEN
Solar/Wind Harmer
0.005
970661AG2-428 GEN
Solar/Wind Harmer
7.524
316320Y1-086
Solar/Wind Harmer
0.002
316435W1029_GEN3
Solar/Wind Harmer
0.002
3141766HARMONY
Solar/Wind Harmer
4.656
3146516WINFALL
Solar/Wind Harmer
0.349
3141843SHACKLE
Adder
1.778
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3146626S HERTFORD
Solar/Wind Harmer
0.346
316280AD1-041 GEN
Solar/Wind Harmer
0.007
3145273HOLLAND
Solar/Wind Harmer
0.258
316156AD2-030 GEN
Solar/Wind Harmer
0.254
3141873WAN 176
Solar/Wind Harmer
6.098
3146376EDENTON
Solar/Wind Harmer
0.338
315614AA2-178 GEN
Solar/Wind Harmer
1.889
971157AH1-035 GEN
Solar/Wind Harmer
3.886
315737AD1-076 GEN
Solar/Wind Harmer
4.152
972255AH1-712 GEN
Adder
164.714
3156081AA2-088 GEN
Solar/Wind Harmer
0.008
3146206CASHIE
Solar/Wind Harmer
0.318
3145893MURPHYS
Solar/Wind Harmer
0.528
3145893MURPHYS
Solar/Wind Harmer
0.316
957521AF2-046 GEN
Solar/Wind Harmer
23.434
3152331SURRY 2
50/50
15.859
3142416OLDCHRC
Solar/Wind Harmer
1.011
3142416OLDCHRC
Solar/Wind Harmer
0.387
316159AE1-175 C
Solar/Wind Harmer
0.327
944631AF1-128 GEN
Adder
179.515
3143096IRON208
Adder
1.57
3138126ROCKLANDING
Solar/Wind Harmer
0.171
971317AH1-138 GEN
Solar/Wind Harmer
2.773
316294AC1-161 GEN
Solar/Wind Harmer
6.422
3142543TWELFTH
Solar/Wind Harmer
0.035
970129AG2-093 GEN
Solar/Wind Harmer
10.478
316458AB2-190 GEN2
Solar/Wind Harmer
1.976
971069AG2-661 GEN
Solar/Wind Harmer
6.539
971647AH1-324 GEN
Solar/Wind Harmer
15.662
961611AG1-000B GEN
Solar/Wind Harmer
19.23
3151171GRAVELC
Adder
3.895
3150851SPRUNCC
Adder
1.682
3145336SMITFLD
Solar/Wind Harmer
1.459
944591AF1-124 GEN
Solar/Wind Harmer
82.083
316375AC2-012 GEN
Solar/Wind Harmer
0.009
3150981CHESPKA
Adder
4.531
315671AE2-027_GEN
Solar/Wind Harmer
23.135
316072AD1-144
Solar/Wind Harmer
0.13
316388AE2-253 GEN
Solar/Wind Harmer
1.126
3142433PROV 92
Solar/Wind Harmer
1.432
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
3146456SLIGO L269
Solar/Wind Harmer
0.358
316246AF1-032 C
Solar/Wind Harmer
0.161
970659AG2-427 GEN
Solar/Wind Harmer
17.218
316381AD1-082 GEN
Solar/Wind Harmer
0.371
970661AG2-428 GEN
Solar/Wind Harmer
35.374
3143526WINTERP
Solar/Wind Harmer
1.841
316093AE2-104_GEN
Solar/Wind Harmer
5.955
3141766HARMONY
Solar/Wind Harmer
0.07
3146516WINFALL
Solar/Wind Harmer
1.13
3146516WINFALL
Solar/Wind Harmer
0.349
971777AH1-397 GEN
Solar/Wind Harmer
0.918
3141843SHACKLE
Adder
1.778
939411AE1-173 GEN
Solar/Wind Harmer
148.397
3143226MDLTHAN
Solar/Wind Harmer
0.343
940641AE2-051 GEN
Solar/Wind Harmer
27.456
315800Z1-036_GEN1
Solar/Wind Harmer
0.003
3130156CHOWAN
Solar/Wind Harmer
0.338
3138133OCRAN
Solar/Wind Harmer
0.198
3145663CRESWEL
Solar/Wind Harmer
0.924
971163AH1-040 GEN
Solar/Wind Harmer
26.412
972277AH1-723 GEN
Adder
191.941
3146206CASHIE
Solar/Wind Harmer
0.318
971547AH1-271 GEN
Solar/Wind Harmer
6.801
3145893MURPHYS
Solar/Wind Harmer
1.262
3145893MURPHYS
Solar/Wind Harmer
1.404
3146173TUNIS
Solar/Wind Harmer
0.313
316023GEN1_S
Solar/Wind Harmer
0.699
3145683EARLEYS
Solar/Wind Harmer
0.31
3146263WOODLND
Solar/Wind Harmer
0.306
3142296MT RD221
50/50
1.311
3150691DARBY 3
50/50
29.113
3150701DARBY 4
50/50
29.046
3150681DARBY 2
50/50
29.012
3150671DARBY 1
50/50
28.978
3142366NRTHEST
50/50
1.317
316075AC2-137 C
Solar/Wind Harmer
0.106
3142946ENON
Solar/Wind Harmer
0.038
316033AB2-134 GEN
Solar/Wind Harmer
0.022
315697AD1-025 GEN
Solar/Wind Harmer
0.413
944641AF1-129 GEN
Adder
174.18
316236AE1-162_GEN
Solar/Wind Harmer
0.003
316240AF1-291 C
Solar/Wind Harmer
0.003
316036AC1-147 C
Solar/Wind Harmer
0.067
3150991CHESPKB
Adder
3.801
3150991CHESPKB
Adder
3.71
316316AC1-027 C
Solar/Wind Harmer
0.347
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.01
3145506HICKORY
Solar/Wind Harmer
1.442
3145506HICKORY
Solar/Wind Harmer
0.865
3145506HICKORY
Solar/Wind Harmer
0.217
316339AD2-160 GEN
Solar/Wind Harmer
0.583
316018AA1-139 ULT2
Solar/Wind Harmer
0.009
316017AA1-139 ULT1
Solar/Wind Harmer
0.2
3137176SLIGO L2192
Solar/Wind Harmer
1.425
3146456SLIGO L269
Solar/Wind Harmer
6.337
966871AG1-558 GEN
Solar/Wind Harmer
0.414
3130086AYDLETT
Solar/Wind Harmer
1.43
970657AG2-426 GEN
Solar/Wind Harmer
12.462
970657AG2-426 GEN
Solar/Wind Harmer
2.613
3143526WINTERP
Solar/Wind Harmer
1.841
3146386ELIZ CT
Solar/Wind Harmer
0.354
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.349
3146516WINFALL
Solar/Wind Harmer
0.349
3146516WINFALL
Solar/Wind Harmer
0.349
3146626S HERTFORD
Solar/Wind Harmer
0.346
3146626S HERTFORD
Solar/Wind Harmer
0.346
971223AH1-071 GEN
Solar/Wind Harmer
3.664
315742AE1-103 GEN
Solar/Wind Harmer
0.004
3146376EDENTON
Solar/Wind Harmer
1.504
3146376EDENTON
Solar/Wind Harmer
1.504
3144356SAPONY
Solar/Wind Harmer
2.786
316065AD1-022 GEN
Solar/Wind Harmer
14.743
972185AH1-677 GEN
Adder
17.914
3145893MURPHYS
Solar/Wind Harmer
2.113
3145893MURPHYS
Solar/Wind Harmer
0.568
972187AH1-678 GEN
Adder
8.995
3146173TUNIS
Solar/Wind Harmer
0.313
3146173TUNIS
Solar/Wind Harmer
0.313
970933AG2-581 GEN
Solar/Wind Harmer
24.83
3142666NORTHAMPTON
Solar/Wind Harmer
0.302
3142666NORTHAMPTON
Solar/Wind Harmer
0.302
3142666NORTHAMPTON
Solar/Wind Harmer
0.302
3142666NORTHAMPTON
Solar/Wind Harmer
0.181
316181AB2-040 GEN
Solar/Wind Harmer
0.436
316426AA2-053 GEN
Solar/Wind Harmer
1.013
3145593CAROLNA
Solar/Wind Harmer
0.298
3145593CAROLNA
Solar/Wind Harmer
0.298
966811AG1-552 GEN
Solar/Wind Harmer
3.231
3145593CAROLNA
Solar/Wind Harmer
0.371
3145796HORNRTN
Solar/Wind Harmer
0.889
3145783HORNRTN
Solar/Wind Harmer
5.27
3145783HORNRTN
Solar/Wind Harmer
4.216
3145783HORNRTN
Solar/Wind Harmer
1.317
3145783HORNRTN
Solar/Wind Harmer
0.527
958261AF2-120 GEN
Solar/Wind Harmer
9.788
3145933PARMELE
Solar/Wind Harmer
0.585
3145933PARMELE
Solar/Wind Harmer
0.292
970099AG2-077 GEN
Solar/Wind Harmer
31.087
316274AC1-208 GEN
Solar/Wind Harmer
1.496
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.897
3150341NORNECKC1
Adder
2.874
3145493TOT1
Solar/Wind Harmer
0.64
3145453TOT5
Solar/Wind Harmer
0.384
3145603CNETO
Solar/Wind Harmer
0.256
961601AG1-000A GEN
Solar/Wind Harmer
4.81
316263AC1-034 GEN
Solar/Wind Harmer
10.275
939181AE1-148 GEN
Solar/Wind Harmer
12.944
971741AH1-377 GEN
Solar/Wind Harmer
26.49
313527AB2-043 GEN
Solar/Wind Harmer
0.003
970301AG2-198 GEN
Solar/Wind Harmer
11.171
970323AG2-213 GEN
Solar/Wind Harmer
11.115
971775AH1-396 GEN
Solar/Wind Harmer
0.417
316034AC1-036 C
Solar/Wind Harmer
0.019
962561AG1-105 GEN
Solar/Wind Harmer
12.3
958211AF2-115 GEN
Solar/Wind Harmer
3.071
963191AG1-168 GEN
Solar/Wind Harmer
1.024
3144293JTRSVLE
Adder
0.815
3144293JTRSVLE
Adder
0.686
964791AG1-342 GEN
Solar/Wind Harmer
4.887
3146843MT LREL
Solar/Wind Harmer
0.254
3146843MT LREL
Solar/Wind Harmer
0.254
3147133PAMPLIN
Solar/Wind Harmer
0.254
3147133PAMPLIN
Solar/Wind Harmer
0.203
316468AD1-105 GEN
Solar/Wind Harmer
-0.081
3145963POPLR C
Solar/Wind Harmer
0.306
970919AG2-571 GEN
Solar/Wind Harmer
10.879
970087AG2-069 GEN
Solar/Wind Harmer
24.391
316174AB2-169 GEN
Solar/Wind Harmer
0.008
3145823KELFORD
Solar/Wind Harmer
0.303
960081AF2-299 GEN
Solar/Wind Harmer
2.907
316011AB1-132 GEN
Solar/Wind Harmer
5.469
962571AG1-106 GEN
Solar/Wind Harmer
4.28
316190AA2-174 GEN
Solar/Wind Harmer
0.001
962861AG1-135 GEN
Solar/Wind Harmer
9.564
3145796HORNRTN
Solar/Wind Harmer
0.978
3145796HORNRTN
Solar/Wind Harmer
0.296
3145783HORNRTN
Solar/Wind Harmer
0.296
971795AH1-408 GEN
Solar/Wind Harmer
19.673
3146293MARTNCO
Solar/Wind Harmer
0.271
3147043LAWRENC
Adder
2.638
957481AF2-042 GEN
Solar/Wind Harmer
77.718
316212AC1-099_GEN
Solar/Wind Harmer
1.505
3143336POWHATN
Solar/Wind Harmer
5.15
3141726DUNNSVL
Solar/Wind Harmer
1.146
3145746EVERETS
Solar/Wind Harmer
0.286
3145746EVERETS
Solar/Wind Harmer
0.286
315693AD1-088 GEN
Solar/Wind Harmer
13.658
962491AG1-098 GEN
Solar/Wind Harmer
16.171
315722AD1-056 GEN
Solar/Wind Harmer
1.786
316494AC1-189 GEN
Solar/Wind Harmer
0.948
316129AC1-054 GEN
Solar/Wind Harmer
1.053
971065AG2-659 GEN
Solar/Wind Harmer
11.883
3150351NORNECKC2
Adder
2.758
961671AG1-007 GEN
Solar/Wind Harmer
0.042
3146083TARBORO
Solar/Wind Harmer
0.276
3145493TOT1
Solar/Wind Harmer
1.227
316336AC2-165 C
Solar/Wind Harmer
0.011
3146233WITAKRS
Solar/Wind Harmer
1.096
3145543BTLEBRO
Solar/Wind Harmer
0.27
3145543BTLEBRO
Solar/Wind Harmer
0.216
316359AB2-059 GEN
Solar/Wind Harmer
0.971
316049AB1-081 GEN
Solar/Wind Harmer
1.547
3142053HEARTS
Solar/Wind Harmer
0.476
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
19.275
963171AG1-166 GEN
Solar/Wind Harmer
1.365
971563AH1-280 GEN
Solar/Wind Harmer
2.73
3144293JTRSVLE
Adder
0.815
970401AG2-262 GEN
Solar/Wind Harmer
1.493
3146926FARMVIL
Solar/Wind Harmer
0.147
316337AD2-073 GEN
Solar/Wind Harmer
0.212
970937AG2-583 GEN
Solar/Wind Harmer
14.682
316003AC1-222 GEN
Solar/Wind Harmer
0.006
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.091
972003AH1-546 GEN
Solar/Wind Harmer
9.023
971377AH1-170 GEN
Solar/Wind Harmer
2.126
3147623JAMES R
Solar/Wind Harmer
0.462
970223AG2-152 GEN
Solar/Wind Harmer
12.134
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.1
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.127
3146802CHATHAM
Solar/Wind Harmer
0.119
941801AE2-185 GEN
Solar/Wind Harmer
5.072
972135AH1-637 GEN
Solar/Wind Harmer
1.317
270173AC1-122 GEN
Solar/Wind Harmer
0.358
270030AE2-140 GEN
Solar/Wind Harmer
15.132
962751AG1-124 GEN
Solar/Wind Harmer
6.367
315705AF1-075 GEN
Solar/Wind Harmer
5.115
316045AC1-158 PL2
Solar/Wind Helper
8.011
316006AB2-029 C
Solar/Wind Helper
0.164
316254AC1-120 GEN1
Solar/Wind Helper
1.563
3147666LOUISA
Solar/Wind Helper
1.282
316192AB2-158 GEN
Solar/Wind Helper
2.104
223401AF1-299 GEN
Solar/Wind Helper
0.393
23779801AA1-109
Solar/Wind Helper
0.185
237080AD1-060 GEN
Solar/Wind Helper
0.295
237038AE2-054 C
Solar/Wind Helper
0.233
235062AE1-101 C1
Solar/Wind Helper
1.423
966131AG1-482 GEN
Solar/Wind Helper
0.131
233930AB2-032 GEN
Solar/Wind Helper
0.368
233915AB1-141 GEN
Solar/Wind Helper
0.486
232422X3-066 FULL
Solar/Wind Helper
0.11
233964AF2-378 GEN
Solar/Wind Helper
0.04
232426Y1-080 FULL
Solar/Wind Helper
0.038
232428Y3-058 C
Solar/Wind Helper
0.327
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.491
232434Z2-077 GEN
Solar/Wind Helper
0.123
233954AC2-188 GEN
Solar/Wind Helper
0.225
233950AC2-186 GEN
Solar/Wind Helper
0.112
233972AC1-094 C
Solar/Wind Helper
0.292
3146776BUCKING
Solar/Wind Harmer
0.914
3146776BUCKING
Solar/Wind Harmer
0.074
316222AC1-221 GEN
Solar/Wind Harmer
0.945
971489AH1-241 GEN
Solar/Wind Harmer
10.629
942751AE2-291 GEN
Solar/Wind Harmer
10.765
315821AE2-092 GEN
Solar/Wind Harmer
0.011
270013AE1-250 PV
Solar/Wind Harmer
0.005
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
3.945
316447AC1-158 HLD
Solar/Wind Helper
5.508
315651AD1-115 GEN
Solar/Wind Helper
1.146
226929AD2-058 GEN
Solar/Wind Helper
0.127
23777801MSM_W1-116
Solar/Wind Helper
0.11
237025AB1-124 C
Solar/Wind Helper
0.159
237006AB1-125 GEN
Solar/Wind Helper
0.12
237034AC2-136 C
Solar/Wind Helper
0.207
23777901MDS_W4-102
Solar/Wind Helper
0.152
235020AA1-095 C
Solar/Wind Helper
0.045
237001AB1-127_GEN
Solar/Wind Helper
0.385
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
237002AB1-128_GEN
Solar/Wind Helper
0.384
235063AE1-101 C2
Solar/Wind Helper
1.423
205916AD1-020 GEN
Solar/Wind Helper
1.645
233933AB2-153 GEN
Solar/Wind Helper
0.225
233944AB2-135 GEN
Solar/Wind Helper
0.569
232424Y1-079 C
Solar/Wind Helper
0.112
233987AB2-037 GEN
Solar/Wind Helper
2.265
233946AB2-136 GEN
Solar/Wind Helper
0.549
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
232408W1-005 C
Solar/Wind Helper
0.491
232410W1-006 C
Solar/Wind Helper
0.491
233939AC1-091 C
Solar/Wind Helper
0.338
233970AC1-092 C
Solar/Wind Helper
0.338
238175AF1-290_GEN
Solar/Wind Helper
0.118
230433AD2-135 GEN
Solar/Wind Helper
0.016
230407AD2-065 C
Solar/Wind Helper
0.039
219921AF1-264
Solar/Wind Helper
0.049
961681AG1-008 GEN
Solar/Wind Harmer
23.434
962971AG1-146 GEN
Solar/Wind Harmer
5.016
3156021HOLLOMANSOL
Solar/Wind Harmer
1.422
3146173TUNIS
Solar/Wind Harmer
0.313
316365GEN2_N
Solar/Wind Harmer
0.699
316463AE2-346 GEN
Solar/Wind Harmer
0.267
316140AB2-099
Solar/Wind Harmer
0.111
962331AG1-082 GEN
Solar/Wind Harmer
3.322
970009AG2-005 GEN
Solar/Wind Harmer
2.291
3146263WOODLND
Solar/Wind Harmer
0.306
3145963POPLR C
Solar/Wind Harmer
0.306
970917AG2-570 GEN
Solar/Wind Harmer
27.198
316317KELFORD C
Solar/Wind Harmer
0.029
3145823KELFORD
Solar/Wind Harmer
0.303
3142666NORTHAMPTON
Solar/Wind Harmer
0.302
313506AB2-031 GEN
Solar/Wind Harmer
0.929
3145796HORNRTN
Solar/Wind Harmer
1.185
3145796HORNRTN
Solar/Wind Harmer
0.296
316404AE1-155 C
Solar/Wind Harmer
0.067
3145933PARMELE
Solar/Wind Harmer
0.292
966801AG1-551 GEN
Solar/Wind Harmer
3.408
3147043LAWRENC
Solar/Wind Harmer
0.175
316210AC1-098 GEN
Solar/Wind Harmer
2.699
316313AB2-026
Solar/Wind Harmer
0.183
316258AE1-075 C
Solar/Wind Harmer
0.219
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.377
3145746EVERETS
Solar/Wind Harmer
0.286
3145746EVERETS
Solar/Wind Harmer
0.286
315724AD1-057 GEN
Solar/Wind Harmer
1.059
316478AD1-087 GEN
Solar/Wind Harmer
0.983
316486AD2-202 GEN
Solar/Wind Harmer
0.289
316327AA2-057 GEN
Solar/Wind Harmer
0.423
3150351NORNECKC2
Adder
2.804
3146073TAR RVR
Solar/Wind Harmer
0.276
3146083TARBORO
Solar/Wind Harmer
0.276
3146233WITAKRS
Solar/Wind Harmer
1.382
3146233WITAKRS
Solar/Wind Harmer
0.187
3138543CONSLDL
Solar/Wind Harmer
0.181
961601AG1-000A GEN
Solar/Wind Harmer
19.24
3145543BTLEBRO
Solar/Wind Harmer
0.27
3145543BTLEBRO
Solar/Wind Harmer
0.27
971623AH1-311 GEN
Solar/Wind Harmer
0.541
316131AB2-060 GEN
Solar/Wind Harmer
0.835
964241AG1-285 GEN
Solar/Wind Harmer
17.596
970909AG2-566 GEN
Solar/Wind Harmer
2.793
315785AD2-033 C
Solar/Wind Harmer
2.125
970257AG2-171 GEN
Solar/Wind Harmer
8.336
959311AF2-222 GEN
Solar/Wind Harmer
23.097
963181AG1-167 GEN
Solar/Wind Harmer
1.024
3144293JTRSVLE
Adder
0.815
3147133PAMPLIN
Solar/Wind Harmer
0.798
971193AH1-056 GEN
Solar/Wind Harmer
15.489
971781AH1-399 GEN
Solar/Wind Harmer
0.329
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
10.514
3146926FARMVIL
Solar/Wind Harmer
0.147
971683AH1-343 GEN
Solar/Wind Harmer
8.489
3146776BUCKING
Solar/Wind Harmer
0.082
316283AC2-100 C
Solar/Wind Harmer
0.444
3141906WESTMOR
Solar/Wind Harmer
0.083
970221AG2-151 GEN
Solar/Wind Harmer
10.629
970737AG2-469 GEN
Solar/Wind Harmer
7.511
270197AD1-017 GEN1
Solar/Wind Harmer
1.056
3147312GRETNA
Solar/Wind Harmer
0.032
941821AE2-187 GEN
Solar/Wind Harmer
5.072
270018AE2-047 C O1
Solar/Wind Harmer
0.003
3148013FISHERV
Solar/Wind Harmer
0.154
315616AA1-038_C
Solar/Wind Harmer
0.001
3151861LOWMORA
Adder
1.607
958131AF2-107 GEN
Solar/Wind Harmer
4.297
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.004
971367AH1-164 GEN
Solar/Wind Harmer
2.405
316044AC1-158 PL1
Solar/Wind Helper
2.503
316450AC1-158 RIC
Solar/Wind Helper
0.667
3141196NOKESVL
Solar/Wind Helper
1.389
316170AC1-121 GEN2
Solar/Wind Helper
0.521
3147666LOUISA
Solar/Wind Helper
0.737
227287AC2-120 GEN
Solar/Wind Helper
0.432
226910AB2-157 C
Solar/Wind Helper
0.018
223402AF1-300 C
Solar/Wind Helper
0.393
3132273ORANGE
Solar/Wind Helper
0.053
237030AB1-096 C
Solar/Wind Helper
0.069
972263AH1-716 GEN
50/50
220.54
316312AB1-027
Solar/Wind Harmer
0.696
315976AC1-164 GENA
Solar/Wind Harmer
40.142
316169AC1-164_GENC
Solar/Wind Harmer
34.679
315975AC1-164 GENB
Solar/Wind Harmer
1.188
316132AB2-190 GEN1
Solar/Wind Harmer
1.976
316369SG1_INVT
Solar/Wind Harmer
0.014
972265AH1-717 GEN
Adder
28.433
3151201GRAVEL4
Adder
26.654
3151191GRAVEL3
Adder
26.317
3151211GRAVEL5
Adder
26.317
971445AH1-216 GEN
Solar/Wind Harmer
25.708
971285AH1-108 GEN
Adder
2.752
3151081ELIZAR1
Adder
33.28
3151091ELIZAR2
Adder
32.702
3152611GOSPORTB
Adder
4.621
3152621GOSPORTC
Adder
3.922
3152601GOSPORTA
Adder
3.618
971167AH1-042 GEN
Solar/Wind Harmer
31.907
957871AF2-081 GEN
Solar/Wind Harmer
17.869
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
3138283WHITEMARSH
Solar/Wind Harmer
0.083
319010AE1-072 C
Solar/Wind Harmer
1.802
3146406KITTY HAWK
Solar/Wind Harmer
0.045
316305AF2-043 C
Solar/Wind Harmer
0.003
315833AF1-017_GEN
Solar/Wind Harmer
0.002
316349AD2-085 GEN
Solar/Wind Harmer
0.243
316311AC2-079 GEN
Solar/Wind Harmer
10.187
3143873LANEXA
Solar/Wind Harmer
0.213
316233AE1-074 FULL
Solar/Wind Harmer
0.283
971281AH1-106 GEN
Solar/Wind Harmer
4.913
971283AH1-107 GEN
Solar/Wind Harmer
4.913
315835AF2-110_GEN
Solar/Wind Harmer
2.43
313526AB2-022
Solar/Wind Harmer
0.192
316314AB2-024 C
Solar/Wind Harmer
0.001
3146486SUNBURY
Solar/Wind Harmer
0.352
3146486SUNBURY
Solar/Wind Harmer
0.352
3143316POE
Solar/Wind Harmer
1.396
316321Z2-027
Solar/Wind Harmer
0.065
3146396TANGLEW
Solar/Wind Harmer
0.971
3145176PASQUOTANK
Solar/Wind Harmer
0.218
316059AD1-063 C
Solar/Wind Harmer
0.002
970189AG2-124 GEN
Solar/Wind Harmer
10.307
315662AE1-191 GEN
Solar/Wind Harmer
0.011
315666AE1-190 GEN
Solar/Wind Harmer
0.003
3141873WAN 176
Solar/Wind Harmer
0.069
315611Z1-036_GEN2
Solar/Wind Harmer
0.003
3130156CHOWAN
Solar/Wind Harmer
0.338
3130156CHOWAN
Solar/Wind Harmer
0.338
3141913WHIT STONE
Solar/Wind Harmer
0.333
316315AB2-025 C
Solar/Wind Harmer
0.269
315814AE2-033 C
Solar/Wind Harmer
26.26
3138133OCRAN
Solar/Wind Harmer
0.099
315816AE2-034 GEN
Solar/Wind Harmer
1.417
941031AE2-094 GEN
Solar/Wind Harmer
60.194
944011AF1-069 GEN
Solar/Wind Harmer
19.668
3141783LANCAST
Solar/Wind Harmer
0.195
3141783LANCAST
Solar/Wind Harmer
0.13
3130546PLYMOUTH
Solar/Wind Harmer
0.324
315732AD1-074 GEN1
Solar/Wind Harmer
1.854
315733AD1-074 GEN2
Solar/Wind Harmer
1.854
315735AD1-075 GEN1
Solar/Wind Harmer
0.928
972193AH1-681 GEN
Adder
7.36
970673AG2-436 GEN
Solar/Wind Harmer
68.642
970673AG2-436 GEN
Solar/Wind Harmer
45.761
3146206CASHIE
Solar/Wind Harmer
0.318
970601AG2-382 GEN
Solar/Wind Harmer
11.901
965291AG1-394 GEN
Solar/Wind Harmer
1.416
971967AH1-528 GEN
Solar/Wind Harmer
50.838
3145893MURPHYS
Solar/Wind Harmer
0.852
3145893MURPHYS
Solar/Wind Harmer
0.316
962981AG1-147 GEN
Solar/Wind Harmer
11.703
3145513AHOSKIE
Solar/Wind Harmer
0.651
3145513AHOSKIE
Solar/Wind Harmer
0.311
3145683EARLEYS
Solar/Wind Harmer
0.62
3145683EARLEYS
Solar/Wind Harmer
0.31
3145683EARLEYS
Solar/Wind Harmer
0.31
3146043SEABORD
Solar/Wind Harmer
0.307
970327AG2-215 GEN
Solar/Wind Harmer
10.069
315607AA1-063A GEN
Solar/Wind Harmer
0.625
970085AG2-068 GEN
Solar/Wind Harmer
16.26
970581AG2-369 GEN
Solar/Wind Harmer
13.984
316087AB2-174 GEN
Solar/Wind Harmer
0.009
315652AC1-086 GEN
Solar/Wind Harmer
33.087
3137643SOCKMAN
Solar/Wind Harmer
1.194
3145796HORNRTN
Solar/Wind Harmer
0.948
3145796HORNRTN
Solar/Wind Harmer
0.119
3146033SCOT NK
Solar/Wind Harmer
1.185
316005AA1-067
Solar/Wind Harmer
0.307
3145746EVERETS
Solar/Wind Harmer
1.138
3145746EVERETS
Solar/Wind Harmer
0.286
3145746EVERETS
Solar/Wind Harmer
0.286
3145746EVERETS
Solar/Wind Harmer
0.286
970181AG2-120 GEN
Solar/Wind Harmer
3.56
970831AG2-522 GEN
Solar/Wind Harmer
12.024
957861AF2-080 GEN
Solar/Wind Harmer
12.104
316420AA1-050 GEN
Solar/Wind Harmer
0.009
3141813NORNECK
Solar/Wind Harmer
0.276
3145573BETHELC
Solar/Wind Harmer
0.276
3145573BETHELC
Solar/Wind Harmer
0.276
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.38
3144303KENBRDG
Solar/Wind Harmer
0.208
972189AH1-679 GEN
Adder
4.36
970683AG2-441 GEN
Solar/Wind Harmer
17.21
970681AG2-440 GEN
Solar/Wind Harmer
13.768
946301AF1-294 GEN
Solar/Wind Harmer
5.05
961791AG1-021 GEN
Solar/Wind Harmer
2.457
315657AE1-056 GEN
Solar/Wind Harmer
8.773
316118AC1-105 GEN
Solar/Wind Harmer
0.646
3147173SINAI
Solar/Wind Harmer
0.246
3147243WELCO
Solar/Wind Harmer
0.154
970285AG2-188 GEN
Solar/Wind Harmer
18.408
971845AH1-439 GEN
Solar/Wind Harmer
10.428
970865AG2-541 GEN
Solar/Wind Harmer
7.734
972205AH1-687 GEN
Adder
8.917
316223AC1-118
Solar/Wind Harmer
0.15
316123AC1-075 GEN
Solar/Wind Harmer
0.284
970165AG2-112 GEN
Solar/Wind Harmer
1.683
970163AG2-111 GEN
Solar/Wind Harmer
1.606
971447AH1-217 GEN
Solar/Wind Harmer
5.953
270494AE1-108_GEN
Solar/Wind Harmer
2.206
3148133STUARTS
Solar/Wind Harmer
0.092
3148013FISHERV
Solar/Wind Harmer
0.088
3148463FAIRFLD
Solar/Wind Harmer
0.15
3151881LOWMORC
Adder
1.595
3151881LOWMORC
Adder
1.57
3151861LOWMORA
Adder
1.545
270069AE2-166 C O1
Solar/Wind Harmer
0.005
944491AF1-114 GEN
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316164AC1-076 GEN
Solar/Wind Helper
1.845
316411AF1-147_GEN1
Solar/Wind Helper
1.079
316415AF1-147_GEN2
Solar/Wind Helper
1.079
3138216PACIFIC
Solar/Wind Helper
0.053
3141426STAFORD
Solar/Wind Helper
0.061
237085AD2-009_GEN
Solar/Wind Helper
1.388
960921AF2-383 GEN
Solar/Wind Helper
0.352
233935AB2-179 C
Solar/Wind Helper
1.229
205943AE1-185 GEN
Solar/Wind Helper
0.491
232436AB1-176 C
Solar/Wind Helper
0.043
205932AD2-116_GEN
Solar/Wind Helper
0.491
205956AE1-196_GEN
Solar/Wind Helper
0.491
233923SMA
Solar/Wind Helper
0.927
233990AG1-397 GEN
Solar/Wind Helper
0.261
232432Z2-076 GEN
Solar/Wind Helper
0.065
234033AF1-007_GEN
Solar/Wind Helper
6.788
238208AF1-136 C
Solar/Wind Helper
0.173
964001AG1-254 GEN
Solar/Wind Helper
0.917
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.025
219914AD2-027 C
Solar/Wind Helper
0.11
219272CLEANLIGHT C
Solar/Wind Helper
0.024
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.221
228728W1-130C
Solar/Wind Helper
0.052
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219904AC1-010 C
Solar/Wind Helper
0.058
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219907AC1-030 C
Solar/Wind Helper
0.032
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
238221AF1-254 C O1
Solar/Wind Helper
0.238
235067AD1-061 GEN
Solar/Wind Helper
0.424
205917AD1-020 ES
Solar/Wind Helper
0.354
233918AB1-142 GEN
Solar/Wind Helper
0.486
233982AB2-133 GEN
Solar/Wind Helper
0.346
233994AC2-023 GEN
Solar/Wind Helper
0.929
233996TM1833_GEN
Solar/Wind Helper
0.253
233997TMININ_4.2
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.491
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.225
233971AC1-093 C
Solar/Wind Helper
0.346
230430AE1-229_GEN
Solar/Wind Helper
3.238
230415AB2-049 C
Solar/Wind Helper
0.029
228729W2-030 C
Solar/Wind Helper
0.106
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.052
219912AD2-042 GEN
Solar/Wind Helper
0.144
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.563
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.762
MECLTFEXP_MEC->PJM
CLTF
7.835
LAGNLTFEXP_LAGN->PJM
CLTF
14.625
CBM South 2LTFEXP_CBM-S2->PJM
CBM
39.998
TVALTFEXP_TVA->PJM
CLTF
7.404
SIGELTFEXP_SIGE->PJM
CLTF
0.242
CPLELTFEXP_CPLE->PJM
CLTF
17.713
NYPJM->LTFIMP_NY
CLTF
4.634
LGEELTFEXP_LGEE->PJM
CLTF
3.014
CBM West 2LTFEXP_CBM-W2->PJM
CBM
80.377
WECLTFEXP_WEC->PJM
CLTF
1.525
AG2-052LTFEXP_AG2-052->PJM
LTF
0.084
AH1-155LTFEXP_AH1-155->PJM
LTF
0.126

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:153.9 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:6264.0
MW Contribution:7.12
Bus #Bus NameTypeMW Contribution
971645AH1-323 GEN
50/50
29.723
3150921YORKTN3
50/50
8.624
3144216WINCHST
50/50
1.289
3151101ELIZAR3
50/50
30.975
3151161SURRY 1
50/50
11.975
3142416OLDCHRC
Solar/Wind Harmer
3.208
316382AG1-145 C
Solar/Wind Harmer
0.003
315773AC2-141 GEN
Solar/Wind Harmer
11.84
970293AG2-193 GEN
Solar/Wind Harmer
3.398
944581AF1-123 GEN
Solar/Wind Harmer
71.01
944601AF1-125 GEN
Solar/Wind Harmer
69.916
3142946ENON
Solar/Wind Harmer
0.105
3144873MCLAUGH
Solar/Wind Harmer
0.008
3144536CHRHLND
Solar/Wind Harmer
0.047
3145336SMITFLD
Solar/Wind Harmer
0.125
3151221GRAVEL6
Adder
22.664
3151171GRAVELC
Adder
4.361
3146456SLIGO L269
Solar/Wind Harmer
0.31
971153AH1-033 GEN
Solar/Wind Harmer
3.585
961611AG1-000B GEN
Solar/Wind Harmer
8.272
972255AH1-712 GEN
Adder
157.541
315778AD1-151 GEN
Solar/Wind Harmer
24.551
316320Y1-086
Solar/Wind Harmer
0.002
970129AG2-093 GEN
Solar/Wind Harmer
18.454
970133AG2-095 GEN
Solar/Wind Harmer
2.91
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.301
3142433PROV 92
Adder
0.583
3142433PROV 92
Adder
0.583
316473AC1-191 GEN
Solar/Wind Harmer
1.014
970661AG2-428 GEN
Solar/Wind Harmer
6.346
3141766HARMONY
Solar/Wind Harmer
3.995
3146626S HERTFORD
Solar/Wind Harmer
0.299
316083AB2-161 GEN
Solar/Wind Harmer
0.004
970659AG2-427 GEN
Solar/Wind Harmer
3.158
3141843SHACKLE
Adder
1.519
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
315813AE1-149 C
Solar/Wind Harmer
15.819
316280AD1-041 GEN
Solar/Wind Harmer
0.006
3145273HOLLAND
Solar/Wind Harmer
0.221
316156AD2-030 GEN
Solar/Wind Harmer
0.218
3141873WAN 176
Solar/Wind Harmer
5.232
965281AG1-393 GEN
Solar/Wind Harmer
3.137
315839AE2-212 C
Solar/Wind Harmer
0.002
3143096IRON208
Adder
1.226
3143096IRON208
Adder
1.201
3146376EDENTON
Solar/Wind Harmer
0.291
315614AA2-178 GEN
Solar/Wind Harmer
1.626
971157AH1-035 GEN
Solar/Wind Harmer
3.34
315737AD1-076 GEN
Solar/Wind Harmer
3.567
3146206CASHIE
Solar/Wind Harmer
0.273
3156081AA2-088 GEN
Solar/Wind Harmer
0.006
3145893MURPHYS
Solar/Wind Harmer
0.451
3145893MURPHYS
Solar/Wind Harmer
0.269
957521AF2-046 GEN
Solar/Wind Harmer
20.016
961681AG1-008 GEN
Solar/Wind Harmer
20.016
962971AG1-146 GEN
Solar/Wind Harmer
4.293
3156021HOLLOMANSOL
Solar/Wind Harmer
1.218
3146173TUNIS
Solar/Wind Harmer
0.267
316463AE2-346 GEN
Solar/Wind Harmer
0.229
316140AB2-099
Solar/Wind Harmer
0.095
962331AG1-082 GEN
Solar/Wind Harmer
2.839
316365GEN2_N
Solar/Wind Harmer
0.59
3145963POPLR C
Solar/Wind Harmer
0.263
970009AG2-005 GEN
Solar/Wind Harmer
1.96
3146263WOODLND
Solar/Wind Harmer
0.261
970917AG2-570 GEN
Solar/Wind Harmer
23.14
316317KELFORD C
Solar/Wind Harmer
0.025
3145823KELFORD
Solar/Wind Harmer
0.259
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
313506AB2-031 GEN
Solar/Wind Harmer
0.784
316404AE1-155 C
Solar/Wind Harmer
0.057
3150861SPRUNCD
Adder
1.161
3145796HORNRTN
Solar/Wind Harmer
1.006
3145796HORNRTN
Solar/Wind Harmer
0.251
3145933PARMELE
Solar/Wind Harmer
0.25
966801AG1-551 GEN
Solar/Wind Harmer
2.916
316210AC1-098 GEN
Solar/Wind Harmer
2.297
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
3147043LAWRENC
Solar/Wind Harmer
0.146
315724AD1-057 GEN
Solar/Wind Harmer
0.9
316327AA2-057 GEN
Solar/Wind Harmer
0.36
3150351NORNECKC2
Adder
2.392
316478AD1-087 GEN
Solar/Wind Harmer
0.823
316486AD2-202 GEN
Solar/Wind Harmer
0.242
3146073TAR RVR
Solar/Wind Harmer
0.235
3146083TARBORO
Solar/Wind Harmer
0.235
3146233WITAKRS
Solar/Wind Harmer
1.176
3146233WITAKRS
Solar/Wind Harmer
0.159
3138543CONSLDL
Solar/Wind Harmer
0.154
961601AG1-000A GEN
Solar/Wind Harmer
16.379
3145543BTLEBRO
Solar/Wind Harmer
0.23
3145543BTLEBRO
Solar/Wind Harmer
0.23
971623AH1-311 GEN
Solar/Wind Harmer
0.46
316131AB2-060 GEN
Solar/Wind Harmer
0.687
964241AG1-285 GEN
Solar/Wind Harmer
14.393
315785AD2-033 C
Solar/Wind Harmer
1.721
970257AG2-171 GEN
Solar/Wind Harmer
6.725
959311AF2-222 GEN
Solar/Wind Harmer
18.581
971781AH1-399 GEN
Solar/Wind Harmer
0.272
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
8.82
970909AG2-566 GEN
Solar/Wind Harmer
2.199
963181AG1-167 GEN
Solar/Wind Harmer
0.81
3144293JTRSVLE
Adder
0.645
3147133PAMPLIN
Solar/Wind Harmer
0.627
971193AH1-056 GEN
Solar/Wind Harmer
12.172
971683AH1-343 GEN
Solar/Wind Harmer
7.141
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3142296MT RD221
50/50
1.096
3150991CHESPKB
50/50
3.492
3150991CHESPKB
50/50
3.408
316075AC2-137 C
Solar/Wind Harmer
0.09
3142946ENON
Solar/Wind Harmer
0.031
316036AC1-147 C
Solar/Wind Harmer
0.058
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.301
316185AD1-033 GEN
Solar/Wind Harmer
0.009
316236AE1-162_GEN
Solar/Wind Harmer
0.003
3145506HICKORY
Solar/Wind Harmer
1.25
3145506HICKORY
Solar/Wind Harmer
0.75
3145506HICKORY
Solar/Wind Harmer
0.188
316339AD2-160 GEN
Solar/Wind Harmer
0.505
316018AA1-139 ULT2
Solar/Wind Harmer
0.008
316017AA1-139 ULT1
Solar/Wind Harmer
0.174
3150691DARBY 3
Adder
22.343
3150701DARBY 4
Adder
22.291
3150681DARBY 2
Adder
22.265
3150671DARBY 1
Adder
22.239
3137176SLIGO L2192
Solar/Wind Harmer
1.234
3146456SLIGO L269
Solar/Wind Harmer
5.488
3130086AYDLETT
Solar/Wind Harmer
1.238
316033AB2-134 GEN
Solar/Wind Harmer
0.018
315697AD1-025 GEN
Solar/Wind Harmer
0.346
3146386ELIZ CT
Solar/Wind Harmer
0.306
3142366NRTHEST
Adder
1
316431W1029_GEN1
Solar/Wind Harmer
0.002
316283AC2-100 C
Solar/Wind Harmer
0.376
3146926FARMVIL
Solar/Wind Harmer
0.111
3141906WESTMOR
Solar/Wind Harmer
0.07
3146776BUCKING
Solar/Wind Harmer
0.058
970737AG2-469 GEN
Solar/Wind Harmer
6.299
270197AD1-017 GEN1
Solar/Wind Harmer
0.911
315616AA1-038_C
Solar/Wind Harmer
0.001
3151861LOWMORA
Adder
1.478
3147312GRETNA
Solar/Wind Harmer
0.027
941821AE2-187 GEN
Solar/Wind Harmer
4.349
3148013FISHERV
Solar/Wind Harmer
0.135
316313AB2-026
Solar/Wind Harmer
0.085
316258AE1-075 C
Solar/Wind Harmer
0.102
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.034
970221AG2-151 GEN
Solar/Wind Harmer
7.125
270018AE2-047 C O1
Solar/Wind Harmer
0.003
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
958131AF2-107 GEN
Solar/Wind Harmer
3.424
270336AE1-100 GEN
Solar/Wind Harmer
0.003
971367AH1-164 GEN
Solar/Wind Harmer
2.104
316044AC1-158 PL1
Solar/Wind Helper
2.044
316450AC1-158 RIC
Solar/Wind Helper
0.545
3141196NOKESVL
Solar/Wind Helper
1.216
316170AC1-121 GEN2
Solar/Wind Helper
0.444
227287AC2-120 GEN
Solar/Wind Helper
0.383
226910AB2-157 C
Solar/Wind Helper
0.016
3147666LOUISA
Solar/Wind Helper
0.591
223402AF1-300 C
Solar/Wind Helper
0.346
237030AB1-096 C
Solar/Wind Helper
0.06
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.301
3146516WINFALL
Solar/Wind Harmer
0.301
3146516WINFALL
Solar/Wind Harmer
0.301
966871AG1-558 GEN
Solar/Wind Harmer
0.347
970657AG2-426 GEN
Solar/Wind Harmer
10.482
970657AG2-426 GEN
Solar/Wind Harmer
2.198
3146626S HERTFORD
Solar/Wind Harmer
0.299
3146626S HERTFORD
Solar/Wind Harmer
0.299
944641AF1-129 GEN
Adder
140.632
316240AF1-291 C
Solar/Wind Harmer
0.002
3146376EDENTON
Solar/Wind Harmer
1.297
3146376EDENTON
Solar/Wind Harmer
1.297
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3144356SAPONY
Solar/Wind Harmer
2.337
316065AD1-022 GEN
Solar/Wind Harmer
12.657
972185AH1-677 GEN
Adder
15.245
3145893MURPHYS
Solar/Wind Harmer
1.804
3145893MURPHYS
Solar/Wind Harmer
0.485
972187AH1-678 GEN
Adder
7.651
3146173TUNIS
Solar/Wind Harmer
0.267
3146173TUNIS
Solar/Wind Harmer
0.267
970933AG2-581 GEN
Solar/Wind Harmer
21
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
316426AA2-053 GEN
Solar/Wind Harmer
0.86
316181AB2-040 GEN
Solar/Wind Harmer
0.368
958261AF2-120 GEN
Solar/Wind Harmer
8.365
3145593CAROLNA
Solar/Wind Harmer
0.252
3145593CAROLNA
Solar/Wind Harmer
0.252
966811AG1-552 GEN
Solar/Wind Harmer
2.738
3145593CAROLNA
Solar/Wind Harmer
0.314
3145796HORNRTN
Solar/Wind Harmer
0.754
3145783HORNRTN
Solar/Wind Harmer
4.467
3145783HORNRTN
Solar/Wind Harmer
3.574
3145783HORNRTN
Solar/Wind Harmer
1.117
3145783HORNRTN
Solar/Wind Harmer
0.447
3145933PARMELE
Solar/Wind Harmer
0.501
3145933PARMELE
Solar/Wind Harmer
0.25
316274AC1-208 GEN
Solar/Wind Harmer
1.272
970099AG2-077 GEN
Solar/Wind Harmer
26.046
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.471
3150341NORNECKC1
Adder
2.451
3145493TOT1
Solar/Wind Harmer
0.546
3145453TOT5
Solar/Wind Harmer
0.327
3145603CNETO
Solar/Wind Harmer
0.218
961601AG1-000A GEN
Solar/Wind Harmer
4.095
316263AC1-034 GEN
Solar/Wind Harmer
8.746
939181AE1-148 GEN
Solar/Wind Harmer
10.786
313527AB2-043 GEN
Solar/Wind Harmer
0.003
971741AH1-377 GEN
Solar/Wind Harmer
21.126
962561AG1-105 GEN
Solar/Wind Harmer
10.222
964791AG1-342 GEN
Solar/Wind Harmer
4.068
3146843MT LREL
Solar/Wind Harmer
0.212
3146843MT LREL
Solar/Wind Harmer
0.212
970323AG2-213 GEN
Solar/Wind Harmer
8.967
971775AH1-396 GEN
Solar/Wind Harmer
0.336
316034AC1-036 C
Solar/Wind Harmer
0.015
316468AD1-105 GEN
Solar/Wind Harmer
-0.067
970301AG2-198 GEN
Solar/Wind Harmer
8.797
958211AF2-115 GEN
Solar/Wind Harmer
2.43
963191AG1-168 GEN
Solar/Wind Harmer
0.81
3144293JTRSVLE
Adder
0.645
3144293JTRSVLE
Adder
0.543
3147133PAMPLIN
Solar/Wind Harmer
0.2
3147133PAMPLIN
Solar/Wind Harmer
0.16
316222AC1-221 GEN
Solar/Wind Harmer
0.802
3143526WINTERP
Solar/Wind Harmer
0.968
942751AE2-291 GEN
Solar/Wind Harmer
9.118
3146776BUCKING
Solar/Wind Harmer
0.649
3146776BUCKING
Solar/Wind Harmer
0.052
270013AE1-250 PV
Solar/Wind Harmer
0.004
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.383
315821AE2-092 GEN
Solar/Wind Harmer
0.008
971223AH1-071 GEN
Solar/Wind Harmer
1.43
971489AH1-241 GEN
Solar/Wind Harmer
7.125
316447AC1-158 HLD
Solar/Wind Helper
4.499
315651AD1-115 GEN
Solar/Wind Helper
0.98
226929AD2-058 GEN
Solar/Wind Helper
0.113
23777801MSM_W1-116
Solar/Wind Helper
0.096
237025AB1-124 C
Solar/Wind Helper
0.14
237006AB1-125 GEN
Solar/Wind Helper
0.105
3152331SURRY 2
50/50
13.991
971353AH1-157 GEN
50/50
28.65
970017AG2-010 GEN
50/50
21.737
3150981CHESPKA
50/50
4.162
3142416OLDCHRC
Solar/Wind Harmer
0.86
3142416OLDCHRC
Solar/Wind Harmer
0.33
316159AE1-175 C
Solar/Wind Harmer
0.283
316294AC1-161 GEN
Solar/Wind Harmer
5.617
971317AH1-138 GEN
Solar/Wind Harmer
2.41
3138126ROCKLANDING
Solar/Wind Harmer
0.148
944591AF1-124 GEN
Solar/Wind Harmer
71.262
316375AC2-012 GEN
Solar/Wind Harmer
0.008
3145336SMITFLD
Solar/Wind Harmer
1.25
3151171GRAVELC
Adder
3.316
316388AE2-253 GEN
Solar/Wind Harmer
0.975
316072AD1-144
Solar/Wind Harmer
0.112
3146456SLIGO L269
Solar/Wind Harmer
0.31
961611AG1-000B GEN
Solar/Wind Harmer
16.269
971647AH1-324 GEN
Solar/Wind Harmer
13.184
316246AF1-032 C
Solar/Wind Harmer
0.139
944631AF1-128 GEN
Adder
146.833
972277AH1-723 GEN
Adder
183.583
971069AG2-661 GEN
Solar/Wind Harmer
5.456
316458AB2-190 GEN2
Solar/Wind Harmer
1.639
970129AG2-093 GEN
Solar/Wind Harmer
8.684
316093AE2-104_GEN
Solar/Wind Harmer
5.127
3146516WINFALL
Solar/Wind Harmer
0.976
3146516WINFALL
Solar/Wind Harmer
0.301
3142433PROV 92
Solar/Wind Harmer
1.2
3142433PROV 92
Adder
0.583
3142433PROV 92
Adder
0.583
970661AG2-428 GEN
Solar/Wind Harmer
29.836
3141766HARMONY
Solar/Wind Harmer
0.06
939411AE1-173 GEN
Solar/Wind Harmer
127.601
316381AD1-082 GEN
Solar/Wind Harmer
0.311
970659AG2-427 GEN
Solar/Wind Harmer
14.437
971777AH1-397 GEN
Solar/Wind Harmer
0.785
3141843SHACKLE
Adder
1.519
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
315671AE2-027_GEN
Solar/Wind Harmer
18.84
940641AE2-051 GEN
Solar/Wind Harmer
23.538
3143096IRON208
Adder
1.226
3130156CHOWAN
Solar/Wind Harmer
0.292
3145663CRESWEL
Solar/Wind Harmer
0.795
971163AH1-040 GEN
Solar/Wind Harmer
22.732
3138133OCRAN
Solar/Wind Harmer
0.17
3142543TWELFTH
Solar/Wind Harmer
0.027
3146206CASHIE
Solar/Wind Harmer
0.273
971547AH1-271 GEN
Solar/Wind Harmer
5.835
3145893MURPHYS
Solar/Wind Harmer
1.078
3145893MURPHYS
Solar/Wind Harmer
1.199
3146173TUNIS
Solar/Wind Harmer
0.267
3145683EARLEYS
Solar/Wind Harmer
0.265
316023GEN1_S
Solar/Wind Harmer
0.59
3145963POPLR C
Solar/Wind Harmer
0.263
3146263WOODLND
Solar/Wind Harmer
0.261
316174AB2-169 GEN
Solar/Wind Harmer
0.007
970919AG2-571 GEN
Solar/Wind Harmer
9.256
970087AG2-069 GEN
Solar/Wind Harmer
20.752
3145823KELFORD
Solar/Wind Harmer
0.259
962861AG1-135 GEN
Solar/Wind Harmer
8.175
316011AB1-132 GEN
Solar/Wind Harmer
4.638
962571AG1-106 GEN
Solar/Wind Harmer
3.63
960081AF2-299 GEN
Solar/Wind Harmer
2.448
316190AA2-174 GEN
Solar/Wind Harmer
0
3150851SPRUNCC
Adder
1.161
3145796HORNRTN
Solar/Wind Harmer
0.83
3145796HORNRTN
Solar/Wind Harmer
0.251
3145783HORNRTN
Solar/Wind Harmer
0.251
3146293MARTNCO
Solar/Wind Harmer
0.232
316212AC1-099_GEN
Solar/Wind Harmer
1.281
971795AH1-408 GEN
Solar/Wind Harmer
16.501
3141726DUNNSVL
Solar/Wind Harmer
0.979
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
957481AF2-042 GEN
Solar/Wind Harmer
65.115
3147043LAWRENC
Adder
2.208
315722AD1-056 GEN
Solar/Wind Harmer
1.518
316494AC1-189 GEN
Solar/Wind Harmer
0.81
3150351NORNECKC2
Adder
2.352
315693AD1-088 GEN
Solar/Wind Harmer
11.318
961671AG1-007 GEN
Solar/Wind Harmer
0.036
3146083TARBORO
Solar/Wind Harmer
0.235
3145493TOT1
Solar/Wind Harmer
1.047
316129AC1-054 GEN
Solar/Wind Harmer
0.885
3146233WITAKRS
Solar/Wind Harmer
0.932
962491AG1-098 GEN
Solar/Wind Harmer
13.368
971065AG2-659 GEN
Solar/Wind Harmer
9.97
3145543BTLEBRO
Solar/Wind Harmer
0.23
3145543BTLEBRO
Solar/Wind Harmer
0.184
316359AB2-059 GEN
Solar/Wind Harmer
0.827
316049AB1-081 GEN
Solar/Wind Harmer
1.317
3142053HEARTS
Solar/Wind Harmer
0.405
315687AD1-152 GEN
Solar/Wind Harmer
0.007
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970401AG2-262 GEN
Solar/Wind Harmer
1.243
316337AD2-073 GEN
Solar/Wind Harmer
0.18
970685AG2-442 GEN
Solar/Wind Harmer
15.398
963171AG1-166 GEN
Solar/Wind Harmer
1.08
971563AH1-280 GEN
Solar/Wind Harmer
2.16
3144293JTRSVLE
Adder
0.645
316003AC1-222 GEN
Solar/Wind Harmer
0.005
3143526WINTERP
Solar/Wind Harmer
0.968
3146926FARMVIL
Solar/Wind Harmer
0.111
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.065
970223AG2-152 GEN
Solar/Wind Harmer
10.425
270016AE1-250 BESS
Solar/Wind Harmer
0.004
3147123OTTER R
Solar/Wind Harmer
0.085
972003AH1-546 GEN
Solar/Wind Harmer
5.963
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.109
3146802CHATHAM
Solar/Wind Harmer
0.102
941801AE2-185 GEN
Solar/Wind Harmer
4.349
970937AG2-583 GEN
Solar/Wind Harmer
8.286
316336AC2-165 C
Solar/Wind Harmer
0.005
3143336POWHATN
Solar/Wind Harmer
2.393
972263AH1-716 GEN
50/50
194.204
3151081ELIZAR1
50/50
30.584
3151091ELIZAR2
50/50
30.053
941591AE2-156 GEN
50/50
27.947
3152611GOSPORTB
50/50
4.245
3152621GOSPORTC
50/50
3.603
3152601GOSPORTA
50/50
3.323
315976AC1-164 GENA
Solar/Wind Harmer
34.449
316169AC1-164_GENC
Solar/Wind Harmer
29.761
315975AC1-164 GENB
Solar/Wind Harmer
1.019
316312AB1-027
Solar/Wind Harmer
0.592
971445AH1-216 GEN
Solar/Wind Harmer
22.015
972265AH1-717 GEN
Adder
24.205
3151201GRAVEL4
Adder
22.69
3151191GRAVEL3
Adder
22.403
3151211GRAVEL5
Adder
22.403
957871AF2-081 GEN
Solar/Wind Harmer
15.477
319010AE1-072 C
Solar/Wind Harmer
1.561
3146406KITTY HAWK
Solar/Wind Harmer
0.039
3138283WHITEMARSH
Solar/Wind Harmer
0.072
316305AF2-043 C
Solar/Wind Harmer
0.002
316369SG1_INVT
Solar/Wind Harmer
0.011
972193AH1-681 GEN
Adder
7.039
313526AB2-022
Solar/Wind Harmer
0.166
316132AB2-190 GEN1
Solar/Wind Harmer
1.639
3146486SUNBURY
Solar/Wind Harmer
0.305
3146486SUNBURY
Solar/Wind Harmer
0.305
315835AF2-110_GEN
Solar/Wind Harmer
2.092
316321Z2-027
Solar/Wind Harmer
0.057
3146396TANGLEW
Solar/Wind Harmer
0.839
3145176PASQUOTANK
Solar/Wind Harmer
0.189
316314AB2-024 C
Solar/Wind Harmer
0.001
316311AC2-079 GEN
Solar/Wind Harmer
8.688
315833AF1-017_GEN
Solar/Wind Harmer
0.002
316349AD2-085 GEN
Solar/Wind Harmer
0.207
3143873LANEXA
Solar/Wind Harmer
0.181
3142433PROV 92
Adder
0.583
3142433PROV 92
Adder
0.583
971167AH1-042 GEN
Solar/Wind Harmer
26.63
316059AD1-063 C
Solar/Wind Harmer
0.002
970189AG2-124 GEN
Solar/Wind Harmer
8.811
315662AE1-191 GEN
Solar/Wind Harmer
0.01
315666AE1-190 GEN
Solar/Wind Harmer
0.002
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.059
3130156CHOWAN
Solar/Wind Harmer
0.292
3130156CHOWAN
Solar/Wind Harmer
0.292
3143316POE
Solar/Wind Harmer
1.153
3141913WHIT STONE
Solar/Wind Harmer
0.285
315816AE2-034 GEN
Solar/Wind Harmer
1.219
3138133OCRAN
Solar/Wind Harmer
0.085
316315AB2-025 C
Solar/Wind Harmer
0.226
315814AE2-033 C
Solar/Wind Harmer
22.041
941031AE2-094 GEN
Solar/Wind Harmer
51.279
944011AF1-069 GEN
Solar/Wind Harmer
16.755
3141783LANCAST
Solar/Wind Harmer
0.167
3141783LANCAST
Solar/Wind Harmer
0.111
3130546PLYMOUTH
Solar/Wind Harmer
0.278
315732AD1-074 GEN1
Solar/Wind Harmer
1.593
3143226MDLTHAN
Solar/Wind Harmer
0.134
971377AH1-170 GEN
Solar/Wind Harmer
1.425
3147623JAMES R
Solar/Wind Harmer
0.31
972135AH1-637 GEN
Solar/Wind Harmer
1.098
270173AC1-122 GEN
Solar/Wind Harmer
0.31
270030AE2-140 GEN
Solar/Wind Harmer
13.116
315705AF1-075 GEN
Solar/Wind Harmer
4.718
962751AG1-124 GEN
Solar/Wind Harmer
5.402
316045AC1-158 PL2
Solar/Wind Helper
6.543
316006AB2-029 C
Solar/Wind Helper
0.142
316254AC1-120 GEN1
Solar/Wind Helper
1.333
3147666LOUISA
Solar/Wind Helper
1.029
316192AB2-158 GEN
Solar/Wind Helper
1.689
223401AF1-299 GEN
Solar/Wind Helper
0.346
23779801AA1-109
Solar/Wind Helper
0.161
315733AD1-074 GEN2
Solar/Wind Harmer
1.593
315735AD1-075 GEN1
Solar/Wind Harmer
0.797
970673AG2-436 GEN
Solar/Wind Harmer
58.436
970673AG2-436 GEN
Solar/Wind Harmer
38.957
3146206CASHIE
Solar/Wind Harmer
0.273
970601AG2-382 GEN
Solar/Wind Harmer
10.212
965291AG1-394 GEN
Solar/Wind Harmer
1.209
971967AH1-528 GEN
Solar/Wind Harmer
43.16
3145893MURPHYS
Solar/Wind Harmer
0.728
3145893MURPHYS
Solar/Wind Harmer
0.269
962981AG1-147 GEN
Solar/Wind Harmer
10.018
3145513AHOSKIE
Solar/Wind Harmer
0.556
3145513AHOSKIE
Solar/Wind Harmer
0.266
3145683EARLEYS
Solar/Wind Harmer
0.53
3145683EARLEYS
Solar/Wind Harmer
0.265
3145683EARLEYS
Solar/Wind Harmer
0.265
970327AG2-215 GEN
Solar/Wind Harmer
8.614
3146043SEABORD
Solar/Wind Harmer
0.261
315607AA1-063A GEN
Solar/Wind Harmer
0.531
970085AG2-068 GEN
Solar/Wind Harmer
13.834
970581AG2-369 GEN
Solar/Wind Harmer
11.898
315652AC1-086 GEN
Solar/Wind Harmer
28.063
316087AB2-174 GEN
Solar/Wind Harmer
0.007
3137643SOCKMAN
Solar/Wind Harmer
1.011
3146033SCOT NK
Solar/Wind Harmer
1.01
971285AH1-108 GEN
Adder
1.899
3145796HORNRTN
Solar/Wind Harmer
0.805
3145796HORNRTN
Solar/Wind Harmer
0.101
316005AA1-067
Solar/Wind Harmer
0.262
3145746EVERETS
Solar/Wind Harmer
0.973
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
970181AG2-120 GEN
Solar/Wind Harmer
3.044
957861AF2-080 GEN
Solar/Wind Harmer
10.333
316420AA1-050 GEN
Solar/Wind Harmer
0.008
970831AG2-522 GEN
Solar/Wind Harmer
10.106
3141813NORNECK
Solar/Wind Harmer
0.236
3145573BETHELC
Solar/Wind Harmer
0.235
3145573BETHELC
Solar/Wind Harmer
0.235
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
972189AH1-679 GEN
Adder
3.657
971443AH1-215 GEN
Solar/Wind Harmer
3.537
3144303KENBRDG
Solar/Wind Harmer
0.168
316118AC1-105 GEN
Solar/Wind Harmer
0.54
3147173SINAI
Solar/Wind Harmer
0.207
3147243WELCO
Solar/Wind Harmer
0.129
970683AG2-441 GEN
Solar/Wind Harmer
13.748
970681AG2-440 GEN
Solar/Wind Harmer
10.999
946301AF1-294 GEN
Solar/Wind Harmer
3.996
961791AG1-021 GEN
Solar/Wind Harmer
1.944
315657AE1-056 GEN
Solar/Wind Harmer
6.894
970865AG2-541 GEN
Solar/Wind Harmer
6.515
316233AE1-074 FULL
Solar/Wind Harmer
0.149
971281AH1-106 GEN
Solar/Wind Harmer
2.583
971283AH1-107 GEN
Solar/Wind Harmer
2.583
316223AC1-118
Solar/Wind Harmer
0.126
316123AC1-075 GEN
Solar/Wind Harmer
0.24
970165AG2-112 GEN
Solar/Wind Harmer
1.423
970163AG2-111 GEN
Solar/Wind Harmer
1.357
970285AG2-188 GEN
Solar/Wind Harmer
13.264
971845AH1-439 GEN
Solar/Wind Harmer
7.44
3148463FAIRFLD
Solar/Wind Harmer
0.138
3151881LOWMORC
Adder
1.466
3151881LOWMORC
Adder
1.443
3151861LOWMORA
Adder
1.42
3148133STUARTS
Solar/Wind Harmer
0.081
3148013FISHERV
Solar/Wind Harmer
0.078
972205AH1-687 GEN
Adder
5.785
971447AH1-217 GEN
Solar/Wind Harmer
4.064
270494AE1-108_GEN
Solar/Wind Harmer
1.551
270069AE2-166 C O1
Solar/Wind Harmer
0.004
316164AC1-076 GEN
Solar/Wind Helper
1.573
316411AF1-147_GEN1
Solar/Wind Helper
0.945
316415AF1-147_GEN2
Solar/Wind Helper
0.945
3138216PACIFIC
Solar/Wind Helper
0.046
3141426STAFORD
Solar/Wind Helper
0.055
LAGNLTFEXP_LAGN->PJM
CLTF
12.709
CBM West 1LTFEXP_CBM-W1->PJM
CBM
47.354
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.437
MECLTFEXP_MEC->PJM
CLTF
6.883
SIGELTFEXP_SIGE->PJM
CLTF
0.213
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.309
TVALTFEXP_TVA->PJM
CLTF
6.437
NYPJM->LTFIMP_NY
CLTF
4.044
LGEELTFEXP_LGEE->PJM
CLTF
2.658
WECLTFEXP_WEC->PJM
CLTF
1.346
CPLELTFEXP_CPLE->PJM
CLTF
15.123
CBM West 2LTFEXP_CBM-W2->PJM
CBM
70.159
AG2-052LTFEXP_AG2-052->PJM
LTF
0.074
AH1-155LTFEXP_AH1-155->PJM
LTF
0.112

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.98 %
Rating:4070.2 MVA
Rating Type:A
MVA to Mitigate:4842.75
MW Contribution:7.11
Bus #Bus NameTypeMW Contribution
3142296MT RD221
50/50
1.091
3150691DARBY 3
50/50
22.95
3150701DARBY 4
50/50
22.896
3150681DARBY 2
50/50
22.869
3150671DARBY 1
50/50
22.843
3142366NRTHEST
50/50
1.033
316075AC2-137 C
Solar/Wind Harmer
0.085
966871AG1-558 GEN
Solar/Wind Harmer
0.344
3142946ENON
Solar/Wind Harmer
0.029
316033AB2-134 GEN
Solar/Wind Harmer
0.015
315697AD1-025 GEN
Solar/Wind Harmer
0.295
944641AF1-129 GEN
Adder
124.433
316240AF1-291 C
Solar/Wind Harmer
0.002
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316036AC1-147 C
Solar/Wind Harmer
0.046
3150991CHESPKB
Adder
2.57
3150991CHESPKB
Adder
2.508
316316AC1-027 C
Solar/Wind Harmer
0.234
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.007
3145506HICKORY
Solar/Wind Harmer
0.97
3145506HICKORY
Solar/Wind Harmer
0.582
3145506HICKORY
Solar/Wind Harmer
0.146
316339AD2-160 GEN
Solar/Wind Harmer
0.392
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.135
3137176SLIGO L2192
Solar/Wind Harmer
0.957
3146456SLIGO L269
Solar/Wind Harmer
4.255
3130086AYDLETT
Solar/Wind Harmer
0.96
970657AG2-426 GEN
Solar/Wind Harmer
8.387
970657AG2-426 GEN
Solar/Wind Harmer
1.758
3146386ELIZ CT
Solar/Wind Harmer
0.237
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.232
971645AH1-323 GEN
50/50
29.668
3152191CUNINGD
50/50
5.586
3152171CUNINGB
50/50
2.411
972255AH1-712 GEN
50/50
168.86
3142416OLDCHRC
Solar/Wind Harmer
3.115
970293AG2-193 GEN
Solar/Wind Harmer
3.254
316473AC1-191 GEN
Solar/Wind Harmer
1.006
3142946ENON
Solar/Wind Harmer
0.098
316382AG1-145 C
Solar/Wind Harmer
0.002
3143096IRON208
Adder
1.181
3143096IRON208
Adder
1.157
3142433PROV 92
Adder
0.534
3142433PROV 92
Adder
0.534
3150921YORKTN3
Adder
6.858
3144216WINCHST
Adder
1.022
3141766HARMONY
Solar/Wind Harmer
3.615
3141843SHACKLE
Adder
1.372
970133AG2-095 GEN
Solar/Wind Harmer
2.576
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.005
970129AG2-093 GEN
Solar/Wind Harmer
16.057
316156AD2-030 GEN
Solar/Wind Harmer
0.195
3141873WAN 176
Solar/Wind Harmer
4.689
315778AD1-151 GEN
Solar/Wind Harmer
21.096
961611AG1-000B GEN
Solar/Wind Harmer
6.924
3151221GRAVEL6
Adder
18.744
3151171GRAVELC
Adder
3.606
3150861SPRUNCD
Adder
1.168
3145336SMITFLD
Solar/Wind Harmer
0.101
315773AC2-141 GEN
Solar/Wind Harmer
9.204
965281AG1-393 GEN
Solar/Wind Harmer
2.675
3144536CHRHLND
Solar/Wind Harmer
0.037
315839AE2-212 C
Solar/Wind Harmer
0.002
3151101ELIZAR3
Adder
22.773
3144873MCLAUGH
Solar/Wind Harmer
0.006
944581AF1-123 GEN
Solar/Wind Harmer
54.983
944601AF1-125 GEN
Solar/Wind Harmer
54.137
962971AG1-146 GEN
Solar/Wind Harmer
3.875
315813AE1-149 C
Solar/Wind Harmer
12.831
3146456SLIGO L269
Solar/Wind Harmer
0.24
971153AH1-033 GEN
Solar/Wind Harmer
2.78
970659AG2-427 GEN
Solar/Wind Harmer
2.536
316083AB2-161 GEN
Solar/Wind Harmer
0.003
970661AG2-428 GEN
Solar/Wind Harmer
5.061
970009AG2-005 GEN
Solar/Wind Harmer
1.772
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.232
3146626S HERTFORD
Solar/Wind Harmer
0.23
316404AE1-155 C
Solar/Wind Harmer
0.052
3145273HOLLAND
Solar/Wind Harmer
0.171
3146376EDENTON
Solar/Wind Harmer
0.224
315614AA2-178 GEN
Solar/Wind Harmer
1.24
3150351NORNECKC2
Adder
2.183
971157AH1-035 GEN
Solar/Wind Harmer
2.537
315737AD1-076 GEN
Solar/Wind Harmer
2.707
971781AH1-399 GEN
Solar/Wind Harmer
0.275
3146206CASHIE
Solar/Wind Harmer
0.207
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
3145893MURPHYS
Solar/Wind Harmer
0.34
3145893MURPHYS
Solar/Wind Harmer
0.203
957521AF2-046 GEN
Solar/Wind Harmer
15.055
961681AG1-008 GEN
Solar/Wind Harmer
15.055
3156021HOLLOMANSOL
Solar/Wind Harmer
0.916
3146173TUNIS
Solar/Wind Harmer
0.201
316463AE2-346 GEN
Solar/Wind Harmer
0.171
316140AB2-099
Solar/Wind Harmer
0.071
962331AG1-082 GEN
Solar/Wind Harmer
2.13
3145963POPLR C
Solar/Wind Harmer
0.197
3146263WOODLND
Solar/Wind Harmer
0.195
316317KELFORD C
Solar/Wind Harmer
0.019
3145823KELFORD
Solar/Wind Harmer
0.193
316365GEN2_N
Solar/Wind Harmer
0.432
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3145933PARMELE
Solar/Wind Harmer
0.186
966801AG1-551 GEN
Solar/Wind Harmer
2.17
313506AB2-031 GEN
Solar/Wind Harmer
0.575
3145796HORNRTN
Solar/Wind Harmer
0.739
3145796HORNRTN
Solar/Wind Harmer
0.185
316210AC1-098 GEN
Solar/Wind Harmer
1.695
3145746EVERETS
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
3147043LAWRENC
Solar/Wind Harmer
0.107
315724AD1-057 GEN
Solar/Wind Harmer
0.658
316327AA2-057 GEN
Solar/Wind Harmer
0.264
3146073TAR RVR
Solar/Wind Harmer
0.172
3146083TARBORO
Solar/Wind Harmer
0.172
3146233WITAKRS
Solar/Wind Harmer
0.859
3146233WITAKRS
Solar/Wind Harmer
0.116
3138543CONSLDL
Solar/Wind Harmer
0.113
961601AG1-000A GEN
Solar/Wind Harmer
11.93
3145543BTLEBRO
Solar/Wind Harmer
0.167
3145543BTLEBRO
Solar/Wind Harmer
0.167
971623AH1-311 GEN
Solar/Wind Harmer
0.335
970917AG2-570 GEN
Solar/Wind Harmer
14.887
316313AB2-026
Solar/Wind Harmer
0.103
316258AE1-075 C
Solar/Wind Harmer
0.123
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.467
3141906WESTMOR
Solar/Wind Harmer
0.065
316478AD1-087 GEN
Solar/Wind Harmer
0.557
316486AD2-202 GEN
Solar/Wind Harmer
0.164
316131AB2-060 GEN
Solar/Wind Harmer
0.497
964241AG1-285 GEN
Solar/Wind Harmer
10.495
315785AD2-033 C
Solar/Wind Harmer
1.27
970257AG2-171 GEN
Solar/Wind Harmer
4.984
959311AF2-222 GEN
Solar/Wind Harmer
13.814
970909AG2-566 GEN
Solar/Wind Harmer
1.639
963181AG1-167 GEN
Solar/Wind Harmer
0.614
3144293JTRSVLE
Adder
0.489
3147133PAMPLIN
Solar/Wind Harmer
0.479
971193AH1-056 GEN
Solar/Wind Harmer
9.299
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.089
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
6.236
3146776BUCKING
Solar/Wind Harmer
0.051
3148013FISHERV
Solar/Wind Harmer
0.14
971683AH1-343 GEN
Solar/Wind Harmer
5.137
315616AA1-038_C
Solar/Wind Harmer
0.001
3151861LOWMORA
Adder
1.496
970737AG2-469 GEN
Solar/Wind Harmer
5.853
316283AC2-100 C
Solar/Wind Harmer
0.266
970221AG2-151 GEN
Solar/Wind Harmer
7.112
316044AC1-158 PL1
Solar/Wind Helper
1.64
316450AC1-158 RIC
Solar/Wind Helper
0.438
3141196NOKESVL
Solar/Wind Helper
1.029
227287AC2-120 GEN
Solar/Wind Helper
0.327
226910AB2-157 C
Solar/Wind Helper
0.013
316170AC1-121 GEN2
Solar/Wind Helper
0.36
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
3146626S HERTFORD
Solar/Wind Harmer
0.23
3146626S HERTFORD
Solar/Wind Harmer
0.23
958261AF2-120 GEN
Solar/Wind Harmer
7.587
3146376EDENTON
Solar/Wind Harmer
0.994
3146376EDENTON
Solar/Wind Harmer
0.994
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3143526WINTERP
Solar/Wind Harmer
1.125
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.255
3150341NORNECKC1
Adder
2.237
316468AD1-105 GEN
Solar/Wind Harmer
-0.068
316065AD1-022 GEN
Solar/Wind Harmer
9.583
3145893MURPHYS
Solar/Wind Harmer
1.358
3145893MURPHYS
Solar/Wind Harmer
0.365
3144356SAPONY
Solar/Wind Harmer
1.697
3146173TUNIS
Solar/Wind Harmer
0.201
3146173TUNIS
Solar/Wind Harmer
0.201
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3142666NORTHAMPTON
Solar/Wind Harmer
0.114
316426AA2-053 GEN
Solar/Wind Harmer
0.635
3145933PARMELE
Solar/Wind Harmer
0.373
3145933PARMELE
Solar/Wind Harmer
0.186
316181AB2-040 GEN
Solar/Wind Harmer
0.27
3145593CAROLNA
Solar/Wind Harmer
0.186
3145593CAROLNA
Solar/Wind Harmer
0.186
966811AG1-552 GEN
Solar/Wind Harmer
2.014
3152181CUNINGC
50/50
2.565
972193AH1-681 GEN
50/50
7.545
316312AB1-027
Solar/Wind Harmer
0.575
315976AC1-164 GENA
Solar/Wind Harmer
32.144
316169AC1-164_GENC
Solar/Wind Harmer
27.769
315975AC1-164 GENB
Solar/Wind Harmer
0.951
316314AB2-024 C
Solar/Wind Harmer
0.001
971167AH1-042 GEN
Solar/Wind Harmer
24.413
3142433PROV 92
Adder
0.534
3142433PROV 92
Adder
0.534
3143873LANEXA
Solar/Wind Harmer
0.165
316059AD1-063 C
Solar/Wind Harmer
0.002
3138283WHITEMARSH
Solar/Wind Harmer
0.062
970189AG2-124 GEN
Solar/Wind Harmer
7.953
315662AE1-191 GEN
Solar/Wind Harmer
0.009
315666AE1-190 GEN
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
1.424
3141873WAN 176
Solar/Wind Harmer
0.053
316369SG1_INVT
Solar/Wind Harmer
0.01
972265AH1-717 GEN
Adder
20.019
3151201GRAVEL4
Adder
18.766
3151191GRAVEL3
Adder
18.528
3151211GRAVEL5
Adder
18.528
3141913WHIT STONE
Solar/Wind Harmer
0.256
3138133OCRAN
Solar/Wind Harmer
0.076
971445AH1-216 GEN
Solar/Wind Harmer
17.851
971285AH1-108 GEN
Adder
1.911
3141783LANCAST
Solar/Wind Harmer
0.15
3141783LANCAST
Solar/Wind Harmer
0.1
3151081ELIZAR1
Adder
22.486
3151091ELIZAR2
Adder
22.095
3152611GOSPORTB
Adder
3.124
3152621GOSPORTC
Adder
2.651
3152601GOSPORTA
Adder
2.446
962981AG1-147 GEN
Solar/Wind Harmer
9.042
957871AF2-081 GEN
Solar/Wind Harmer
12.005
319010AE1-072 C
Solar/Wind Harmer
1.21
3146406KITTY HAWK
Solar/Wind Harmer
0.03
316305AF2-043 C
Solar/Wind Harmer
0.002
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.163
316311AC2-079 GEN
Solar/Wind Harmer
6.837
970327AG2-215 GEN
Solar/Wind Harmer
7.789
315835AF2-110_GEN
Solar/Wind Harmer
1.628
313526AB2-022
Solar/Wind Harmer
0.128
3146486SUNBURY
Solar/Wind Harmer
0.236
3146486SUNBURY
Solar/Wind Harmer
0.236
316321Z2-027
Solar/Wind Harmer
0.044
3146396TANGLEW
Solar/Wind Harmer
0.649
3145176PASQUOTANK
Solar/Wind Harmer
0.146
3143316POE
Solar/Wind Harmer
0.911
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.224
3130156CHOWAN
Solar/Wind Harmer
0.224
972189AH1-679 GEN
Adder
3.73
315816AE2-034 GEN
Solar/Wind Harmer
0.93
316233AE1-074 FULL
Solar/Wind Harmer
0.173
971281AH1-106 GEN
Solar/Wind Harmer
3.003
971283AH1-107 GEN
Solar/Wind Harmer
3.003
3141813NORNECK
Solar/Wind Harmer
0.215
3130546PLYMOUTH
Solar/Wind Harmer
0.211
315732AD1-074 GEN1
Solar/Wind Harmer
1.209
315733AD1-074 GEN2
Solar/Wind Harmer
1.209
315735AD1-075 GEN1
Solar/Wind Harmer
0.605
3146206CASHIE
Solar/Wind Harmer
0.207
970601AG2-382 GEN
Solar/Wind Harmer
7.721
965291AG1-394 GEN
Solar/Wind Harmer
0.911
3145893MURPHYS
Solar/Wind Harmer
0.548
3145893MURPHYS
Solar/Wind Harmer
0.203
316315AB2-025 C
Solar/Wind Harmer
0.164
315814AE2-033 C
Solar/Wind Harmer
16.008
3145513AHOSKIE
Solar/Wind Harmer
0.417
3145513AHOSKIE
Solar/Wind Harmer
0.199
3145683EARLEYS
Solar/Wind Harmer
0.397
3145683EARLEYS
Solar/Wind Harmer
0.198
3145683EARLEYS
Solar/Wind Harmer
0.198
3146043SEABORD
Solar/Wind Harmer
0.194
315607AA1-063A GEN
Solar/Wind Harmer
0.395
315652AC1-086 GEN
Solar/Wind Harmer
20.636
3146033SCOT NK
Solar/Wind Harmer
0.749
316087AB2-174 GEN
Solar/Wind Harmer
0.005
3137643SOCKMAN
Solar/Wind Harmer
0.742
3145796HORNRTN
Solar/Wind Harmer
0.591
3145796HORNRTN
Solar/Wind Harmer
0.074
316005AA1-067
Solar/Wind Harmer
0.194
3145746EVERETS
Solar/Wind Harmer
0.72
3145746EVERETS
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
970181AG2-120 GEN
Solar/Wind Harmer
2.254
957861AF2-080 GEN
Solar/Wind Harmer
7.61
941031AE2-094 GEN
Solar/Wind Harmer
32.353
944011AF1-069 GEN
Solar/Wind Harmer
10.571
316420AA1-050 GEN
Solar/Wind Harmer
0.006
970673AG2-436 GEN
Solar/Wind Harmer
37.059
970673AG2-436 GEN
Solar/Wind Harmer
24.706
3145573BETHELC
Solar/Wind Harmer
0.172
3145573BETHELC
Solar/Wind Harmer
0.172
971967AH1-528 GEN
Solar/Wind Harmer
27.582
970831AG2-522 GEN
Solar/Wind Harmer
7.305
316319Z2-044 C
Solar/Wind Harmer
0
970085AG2-068 GEN
Solar/Wind Harmer
8.909
970581AG2-369 GEN
Solar/Wind Harmer
7.662
316223AC1-118
Solar/Wind Harmer
0.117
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
2.618
3144303KENBRDG
Solar/Wind Harmer
0.124
970683AG2-441 GEN
Solar/Wind Harmer
10.305
970681AG2-440 GEN
Solar/Wind Harmer
8.244
946301AF1-294 GEN
Solar/Wind Harmer
3.029
961791AG1-021 GEN
Solar/Wind Harmer
1.473
315657AE1-056 GEN
Solar/Wind Harmer
5.267
316118AC1-105 GEN
Solar/Wind Harmer
0.384
3147173SINAI
Solar/Wind Harmer
0.146
3147243WELCO
Solar/Wind Harmer
0.091
970285AG2-188 GEN
Solar/Wind Harmer
11.379
971845AH1-439 GEN
Solar/Wind Harmer
6.479
3148133STUARTS
Solar/Wind Harmer
0.084
3148013FISHERV
Solar/Wind Harmer
0.081
3148463FAIRFLD
Solar/Wind Harmer
0.139
3151881LOWMORC
Adder
1.484
3151881LOWMORC
Adder
1.461
3151861LOWMORA
Adder
1.437
970865AG2-541 GEN
Solar/Wind Harmer
4.73
972205AH1-687 GEN
Adder
5.79
971447AH1-217 GEN
Solar/Wind Harmer
4.07
316123AC1-075 GEN
Solar/Wind Harmer
0.178
970165AG2-112 GEN
Solar/Wind Harmer
1.054
970163AG2-111 GEN
Solar/Wind Harmer
1.006
270494AE1-108_GEN
Solar/Wind Harmer
1.506
316164AC1-076 GEN
Solar/Wind Helper
1.291
316411AF1-147_GEN1
Solar/Wind Helper
0.798
316415AF1-147_GEN2
Solar/Wind Helper
0.798
3138216PACIFIC
Solar/Wind Helper
0.039
3152161CUNINGA
50/50
2.401
972277AH1-723 GEN
50/50
196.773
3142416OLDCHRC
Solar/Wind Harmer
0.835
3142416OLDCHRC
Solar/Wind Harmer
0.32
316159AE1-175 C
Solar/Wind Harmer
0.248
944631AF1-128 GEN
Adder
136.402
3143096IRON208
Adder
1.181
971317AH1-138 GEN
Solar/Wind Harmer
2.064
3142433PROV 92
Solar/Wind Harmer
1.099
3142433PROV 92
Adder
0.534
3142433PROV 92
Adder
0.534
3138126ROCKLANDING
Solar/Wind Harmer
0.125
3141766HARMONY
Solar/Wind Harmer
0.054
3142543TWELFTH
Solar/Wind Harmer
0.026
971777AH1-397 GEN
Solar/Wind Harmer
0.709
3141843SHACKLE
Adder
1.372
970129AG2-093 GEN
Solar/Wind Harmer
7.556
316458AB2-190 GEN2
Solar/Wind Harmer
1.424
971069AG2-661 GEN
Solar/Wind Harmer
4.688
971647AH1-324 GEN
Solar/Wind Harmer
11.14
961611AG1-000B GEN
Solar/Wind Harmer
13.616
3151171GRAVELC
Adder
2.743
3138133OCRAN
Solar/Wind Harmer
0.153
315671AE2-027_GEN
Solar/Wind Harmer
16.232
3150851SPRUNCC
Adder
1.168
3145336SMITFLD
Solar/Wind Harmer
1.012
316294AC1-161 GEN
Solar/Wind Harmer
4.367
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
3.063
316072AD1-144
Solar/Wind Harmer
0.089
944591AF1-124 GEN
Solar/Wind Harmer
55.179
316388AE2-253 GEN
Solar/Wind Harmer
0.757
3146456SLIGO L269
Solar/Wind Harmer
0.24
970659AG2-427 GEN
Solar/Wind Harmer
11.595
316246AF1-032 C
Solar/Wind Harmer
0.108
316381AD1-082 GEN
Solar/Wind Harmer
0.25
970661AG2-428 GEN
Solar/Wind Harmer
23.793
316093AE2-104_GEN
Solar/Wind Harmer
3.989
3146516WINFALL
Solar/Wind Harmer
0.754
3146516WINFALL
Solar/Wind Harmer
0.232
962861AG1-135 GEN
Solar/Wind Harmer
7.409
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3141726DUNNSVL
Solar/Wind Harmer
0.895
3130156CHOWAN
Solar/Wind Harmer
0.224
3145663CRESWEL
Solar/Wind Harmer
0.606
971163AH1-040 GEN
Solar/Wind Harmer
17.339
3143526WINTERP
Solar/Wind Harmer
1.125
3150351NORNECKC2
Adder
2.147
3146206CASHIE
Solar/Wind Harmer
0.207
971547AH1-271 GEN
Solar/Wind Harmer
4.412
939411AE1-173 GEN
Solar/Wind Harmer
87.698
3145893MURPHYS
Solar/Wind Harmer
0.811
3145893MURPHYS
Solar/Wind Harmer
0.902
3146173TUNIS
Solar/Wind Harmer
0.201
3145683EARLEYS
Solar/Wind Harmer
0.198
3145963POPLR C
Solar/Wind Harmer
0.197
316174AB2-169 GEN
Solar/Wind Harmer
0.005
3146263WOODLND
Solar/Wind Harmer
0.195
3145823KELFORD
Solar/Wind Harmer
0.193
940641AE2-051 GEN
Solar/Wind Harmer
15.435
316023GEN1_S
Solar/Wind Harmer
0.432
316337AD2-073 GEN
Solar/Wind Harmer
0.166
316190AA2-174 GEN
Solar/Wind Harmer
0
316011AB1-132 GEN
Solar/Wind Harmer
3.411
962571AG1-106 GEN
Solar/Wind Harmer
2.669
960081AF2-299 GEN
Solar/Wind Harmer
1.79
3146293MARTNCO
Solar/Wind Harmer
0.173
3145783HORNRTN
Solar/Wind Harmer
0.185
3145796HORNRTN
Solar/Wind Harmer
0.609
3145796HORNRTN
Solar/Wind Harmer
0.185
316212AC1-099_GEN
Solar/Wind Harmer
0.945
3143226MDLTHAN
Solar/Wind Harmer
0.182
3145746EVERETS
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
971795AH1-408 GEN
Solar/Wind Harmer
12.042
3147043LAWRENC
Adder
1.61
316494AC1-189 GEN
Solar/Wind Harmer
0.596
315722AD1-056 GEN
Solar/Wind Harmer
1.11
961671AG1-007 GEN
Solar/Wind Harmer
0.026
3146083TARBORO
Solar/Wind Harmer
0.172
3145493TOT1
Solar/Wind Harmer
0.767
3146233WITAKRS
Solar/Wind Harmer
0.681
316129AC1-054 GEN
Solar/Wind Harmer
0.638
971065AG2-659 GEN
Solar/Wind Harmer
7.177
3145543BTLEBRO
Solar/Wind Harmer
0.167
3145543BTLEBRO
Solar/Wind Harmer
0.134
316359AB2-059 GEN
Solar/Wind Harmer
0.602
316049AB1-081 GEN
Solar/Wind Harmer
0.959
3142053HEARTS
Solar/Wind Harmer
0.295
970919AG2-571 GEN
Solar/Wind Harmer
5.955
970087AG2-069 GEN
Solar/Wind Harmer
13.364
3143336POWHATN
Solar/Wind Harmer
2.903
957481AF2-042 GEN
Solar/Wind Harmer
43.505
315693AD1-088 GEN
Solar/Wind Harmer
7.732
962491AG1-098 GEN
Solar/Wind Harmer
9.171
316336AC2-165 C
Solar/Wind Harmer
0.006
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970685AG2-442 GEN
Solar/Wind Harmer
11.542
315687AD1-152 GEN
Solar/Wind Harmer
0.005
963171AG1-166 GEN
Solar/Wind Harmer
0.819
971563AH1-280 GEN
Solar/Wind Harmer
1.637
3144293JTRSVLE
Adder
0.489
970401AG2-262 GEN
Solar/Wind Harmer
0.887
3146926FARMVIL
Solar/Wind Harmer
0.089
970937AG2-583 GEN
Solar/Wind Harmer
8.957
316003AC1-222 GEN
Solar/Wind Harmer
0.004
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.057
972003AH1-546 GEN
Solar/Wind Harmer
5.812
971377AH1-170 GEN
Solar/Wind Harmer
1.422
3147623JAMES R
Solar/Wind Harmer
0.309
315705AF1-075 GEN
Solar/Wind Harmer
4.935
972135AH1-637 GEN
Solar/Wind Harmer
1.026
970223AG2-152 GEN
Solar/Wind Harmer
7.945
3147123OTTER R
Solar/Wind Harmer
0.068
316045AC1-158 PL2
Solar/Wind Helper
5.251
316006AB2-029 C
Solar/Wind Helper
0.117
316254AC1-120 GEN1
Solar/Wind Helper
1.08
3145593CAROLNA
Solar/Wind Harmer
0.231
3145783HORNRTN
Solar/Wind Harmer
3.287
3145783HORNRTN
Solar/Wind Harmer
2.629
3145783HORNRTN
Solar/Wind Harmer
0.822
3145783HORNRTN
Solar/Wind Harmer
0.329
3145796HORNRTN
Solar/Wind Harmer
0.554
971223AH1-071 GEN
Solar/Wind Harmer
1.938
316274AC1-208 GEN
Solar/Wind Harmer
0.935
972185AH1-677 GEN
Adder
9.694
3145493TOT1
Solar/Wind Harmer
0.4
3145453TOT5
Solar/Wind Harmer
0.24
3145603CNETO
Solar/Wind Harmer
0.16
972187AH1-678 GEN
Adder
4.882
970933AG2-581 GEN
Solar/Wind Harmer
13.585
961601AG1-000A GEN
Solar/Wind Harmer
2.983
316263AC1-034 GEN
Solar/Wind Harmer
6.369
970099AG2-077 GEN
Solar/Wind Harmer
17.402
939181AE1-148 GEN
Solar/Wind Harmer
7.706
313527AB2-043 GEN
Solar/Wind Harmer
0.002
970323AG2-213 GEN
Solar/Wind Harmer
6.645
971775AH1-396 GEN
Solar/Wind Harmer
0.249
316034AC1-036 C
Solar/Wind Harmer
0.011
971741AH1-377 GEN
Solar/Wind Harmer
15.41
970301AG2-198 GEN
Solar/Wind Harmer
6.555
958211AF2-115 GEN
Solar/Wind Harmer
1.842
963191AG1-168 GEN
Solar/Wind Harmer
0.614
3144293JTRSVLE
Adder
0.489
3144293JTRSVLE
Adder
0.411
3147133PAMPLIN
Solar/Wind Harmer
0.153
3147133PAMPLIN
Solar/Wind Harmer
0.122
962561AG1-105 GEN
Solar/Wind Harmer
7.312
964791AG1-342 GEN
Solar/Wind Harmer
2.904
3146843MT LREL
Solar/Wind Harmer
0.151
3146843MT LREL
Solar/Wind Harmer
0.151
3146776BUCKING
Solar/Wind Harmer
0.569
3146776BUCKING
Solar/Wind Harmer
0.046
316222AC1-221 GEN
Solar/Wind Harmer
0.567
315821AE2-092 GEN
Solar/Wind Harmer
0.008
971489AH1-241 GEN
Solar/Wind Harmer
7.112
942751AE2-291 GEN
Solar/Wind Harmer
6.853
316447AC1-158 HLD
Solar/Wind Helper
3.611
226929AD2-058 GEN
Solar/Wind Helper
0.096
315651AD1-115 GEN
Solar/Wind Helper
0.797
LAGNLTFEXP_LAGN->PJM
CLTF
9.82
CBM West 1LTFEXP_CBM-W1->PJM
CBM
38.714
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.519
MECLTFEXP_MEC->PJM
CLTF
5.527
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.055
TVALTFEXP_TVA->PJM
CLTF
4.995
SIGELTFEXP_SIGE->PJM
CLTF
0.173
NYPJM->LTFIMP_NY
CLTF
3.366
LGEELTFEXP_LGEE->PJM
CLTF
2.175
WECLTFEXP_WEC->PJM
CLTF
1.097
CPLELTFEXP_CPLE->PJM
CLTF
10.807
CBM West 2LTFEXP_CBM-W2->PJM
CBM
55.119
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.092

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2054-2135_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2054-2135_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:107.76 %
Rating:5011.0 MVA
Rating Type:C
MVA to Mitigate:5399.85
MW Contribution:11.94
Bus #Bus NameTypeMW Contribution
3142296MT RD221
50/50
1.088
3150691DARBY 3
50/50
22.909
3150701DARBY 4
50/50
22.856
3150681DARBY 2
50/50
22.829
3150671DARBY 1
50/50
22.802
3142366NRTHEST
50/50
1.032
316075AC2-137 C
Solar/Wind Harmer
0.937
966871AG1-558 GEN
Solar/Wind Harmer
1.002
966871AG1-558 GEN
Solar/Wind Harmer
0.343
3142946ENON
Solar/Wind Harmer
-0.003
316441AF1-014 GEN
Solar/Wind Harmer
2.025
316033AB2-134 GEN
Solar/Wind Harmer
9.509
315697AD1-025 GEN
Solar/Wind Harmer
5.964
944641AF1-129 GEN
Adder
124.396
316240AF1-291 C
Solar/Wind Harmer
0.872
3152181CUNINGC
50/50
2.658
972193AH1-681 GEN
50/50
7.817
316312AB1-027
Solar/Wind Harmer
1.214
315976AC1-164 GENA
Solar/Wind Harmer
36.714
316169AC1-164_GENC
Solar/Wind Harmer
31.717
315975AC1-164 GENB
Solar/Wind Harmer
1.086
316314AB2-024 C
Solar/Wind Harmer
2.637
971167AH1-042 GEN
Solar/Wind Harmer
29.653
3142433PROV 92
Adder
0.533
3142433PROV 92
Adder
0.533
3143873LANEXA
Solar/Wind Harmer
-0.018
316059AD1-063 C
Solar/Wind Harmer
0.686
957831AF2-077 GEN
Solar/Wind Harmer
0.905
3138283WHITEMARSH
Solar/Wind Harmer
0.047
315662AE1-191 GEN
Solar/Wind Harmer
3.594
315666AE1-190 GEN
Solar/Wind Harmer
0.899
316132AB2-190 GEN1
Solar/Wind Harmer
3.014
957601AF2-054 GEN
Solar/Wind Harmer
0.883
3141873WAN 176
Solar/Wind Harmer
-0.006
316369SG1_INVT
Solar/Wind Harmer
5.268
972265AH1-717 GEN
Adder
20.013
3151201GRAVEL4
Adder
18.761
3151191GRAVEL3
Adder
18.524
3151211GRAVEL5
Adder
18.524
3141913WHIT STONE
Solar/Wind Harmer
-0.029
971285AH1-108 GEN
Adder
1.915
971445AH1-216 GEN
Solar/Wind Harmer
17.627
3138133OCRAN
Solar/Wind Harmer
-0.009
3141783LANCAST
Solar/Wind Harmer
-0.017
3141783LANCAST
Solar/Wind Harmer
-0.011
3152611GOSPORTB
Adder
3.125
3152621GOSPORTC
Adder
2.652
3152601GOSPORTA
Adder
2.447
3151081ELIZAR1
Adder
22.492
3151091ELIZAR2
Adder
22.101
957871AF2-081 GEN
Solar/Wind Harmer
13.561
962981AG1-147 GEN
Solar/Wind Harmer
11.831
319010AE1-072 C
Solar/Wind Harmer
5.466
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316305AF2-043 C
Solar/Wind Harmer
0.813
315833AF1-017_GEN
Solar/Wind Harmer
5.089
316349AD2-085 GEN
Solar/Wind Harmer
2.383
316311AC2-079 GEN
Solar/Wind Harmer
13.512
315835AF2-110_GEN
Solar/Wind Harmer
3.337
313526AB2-022
Solar/Wind Harmer
0.72
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
316321Z2-027
Solar/Wind Harmer
0.715
3146396TANGLEW
Solar/Wind Harmer
0.488
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3143316POE
Solar/Wind Harmer
-0.102
315611Z1-036_GEN2
Solar/Wind Harmer
6.341
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
972189AH1-679 GEN
Adder
3.686
316233AE1-074 FULL
Solar/Wind Harmer
0.659
971281AH1-106 GEN
Solar/Wind Harmer
3.983
971283AH1-107 GEN
Solar/Wind Harmer
3.983
315816AE2-034 GEN
Solar/Wind Harmer
1.982
3141813NORNECK
Solar/Wind Harmer
-0.024
3152161CUNINGA
50/50
2.487
972277AH1-723 GEN
50/50
203.865
3142416OLDCHRC
Solar/Wind Harmer
-0.093
3142416OLDCHRC
Solar/Wind Harmer
-0.036
316159AE1-175 C
Solar/Wind Harmer
0.864
944631AF1-128 GEN
Adder
136.233
3143096IRON208
Adder
1.18
971317AH1-138 GEN
Solar/Wind Harmer
3.876
3142433PROV 92
Solar/Wind Harmer
-0.123
3142433PROV 92
Adder
0.533
3142433PROV 92
Adder
0.533
3138126ROCKLANDING
Solar/Wind Harmer
0.093
3142543TWELFTH
Solar/Wind Harmer
-0.003
3141766HARMONY
Solar/Wind Harmer
-0.006
971777AH1-397 GEN
Solar/Wind Harmer
3.533
3141843SHACKLE
Adder
1.366
970129AG2-093 GEN
Solar/Wind Harmer
6.804
316458AB2-190 GEN2
Solar/Wind Harmer
3.014
971069AG2-661 GEN
Solar/Wind Harmer
4.686
971647AH1-324 GEN
Solar/Wind Harmer
14.662
961611AG1-000B GEN
Solar/Wind Harmer
14.392
3151171GRAVELC
Adder
2.742
3150851SPRUNCC
Adder
1.17
315671AE2-027_GEN
Solar/Wind Harmer
21.367
3138133OCRAN
Solar/Wind Harmer
-0.017
3145336SMITFLD
Solar/Wind Harmer
-0.113
316294AC1-161 GEN
Solar/Wind Harmer
9.157
316375AC2-012 GEN
Solar/Wind Harmer
9.543
3150981CHESPKA
Adder
3.064
316072AD1-144
Solar/Wind Harmer
0.558
944591AF1-124 GEN
Solar/Wind Harmer
125.296
316388AE2-253 GEN
Solar/Wind Harmer
1.831
3146456SLIGO L269
Solar/Wind Harmer
-0.027
316246AF1-032 C
Solar/Wind Harmer
0.546
970659AG2-427 GEN
Solar/Wind Harmer
14.324
316381AD1-082 GEN
Solar/Wind Harmer
2.471
970661AG2-428 GEN
Solar/Wind Harmer
28.585
316093AE2-104_GEN
Solar/Wind Harmer
7.762
961951AG1-038 GEN
Solar/Wind Harmer
3.489
3146516WINFALL
Solar/Wind Harmer
-0.084
3146516WINFALL
Solar/Wind Harmer
-0.026
962861AG1-135 GEN
Solar/Wind Harmer
9.683
315800Z1-036_GEN1
Solar/Wind Harmer
6.341
3130156CHOWAN
Solar/Wind Harmer
-0.025
964211AG1-282 GEN
Solar/Wind Harmer
0.75
3141726DUNNSVL
Solar/Wind Harmer
-0.099
3143526WINTERP
Solar/Wind Harmer
-0.127
3145663CRESWEL
Solar/Wind Harmer
-0.068
971163AH1-040 GEN
Solar/Wind Harmer
22.96
3150351NORNECKC2
Adder
2.126
3146206CASHIE
Solar/Wind Harmer
-0.023
971547AH1-271 GEN
Solar/Wind Harmer
5.856
939411AE1-173 GEN
Solar/Wind Harmer
115.558
3145893MURPHYS
Solar/Wind Harmer
-0.092
3145893MURPHYS
Solar/Wind Harmer
0.684
3146173TUNIS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.022
3145963POPLR C
Solar/Wind Harmer
-0.022
3146263WOODLND
Solar/Wind Harmer
-0.022
316174AB2-169 GEN
Solar/Wind Harmer
3.418
3145823KELFORD
Solar/Wind Harmer
-0.022
316023GEN1_S
Solar/Wind Harmer
1.473
940641AE2-051 GEN
Solar/Wind Harmer
20.34
316190AA2-174 GEN
Solar/Wind Harmer
0.264
316011AB1-132 GEN
Solar/Wind Harmer
4.47
962571AG1-106 GEN
Solar/Wind Harmer
3.071
960081AF2-299 GEN
Solar/Wind Harmer
2.398
3146293MARTNCO
Solar/Wind Harmer
0.131
3145783HORNRTN
Solar/Wind Harmer
-0.021
316337AD2-073 GEN
Solar/Wind Harmer
0.567
3145796HORNRTN
Solar/Wind Harmer
-0.069
3145796HORNRTN
Solar/Wind Harmer
-0.021
316212AC1-099_GEN
Solar/Wind Harmer
1.818
971795AH1-408 GEN
Solar/Wind Harmer
15.594
3143226MDLTHAN
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
3147043LAWRENC
Adder
1.655
3143336POWHATN
Solar/Wind Harmer
2.398
316494AC1-189 GEN
Solar/Wind Harmer
2.168
316336AC2-165 C
Solar/Wind Harmer
3.489
315722AD1-056 GEN
Solar/Wind Harmer
2.094
970937AG2-583 GEN
Solar/Wind Harmer
14.192
961671AG1-007 GEN
Solar/Wind Harmer
0.249
3146083TARBORO
Solar/Wind Harmer
-0.02
3145493TOT1
Solar/Wind Harmer
0.585
316129AC1-054 GEN
Solar/Wind Harmer
1.724
3146233WITAKRS
Solar/Wind Harmer
-0.077
971065AG2-659 GEN
Solar/Wind Harmer
9.76
972003AH1-546 GEN
Solar/Wind Harmer
9.694
316322AB2-045
Solar/Wind Harmer
0.65
3146776BUCKING
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.019
3145543BTLEBRO
Solar/Wind Harmer
-0.015
316359AB2-059 GEN
Solar/Wind Harmer
2.588
316049AB1-081 GEN
Solar/Wind Harmer
2.071
3142053HEARTS
Solar/Wind Harmer
0.226
3146926FARMVIL
Solar/Wind Harmer
-0.011
971377AH1-170 GEN
Solar/Wind Harmer
2.388
3147623JAMES R
Solar/Wind Harmer
0.296
3144293JTRSVLE
Adder
0.538
3147666LOUISA
Solar/Wind Helper
1.312
316192AB2-158 GEN
Solar/Wind Helper
2.2
316254AC1-120 GEN1
Solar/Wind Helper
1.486
316045AC1-158 PL2
Solar/Wind Helper
5.686
316006AB2-029 C
Solar/Wind Helper
0.141
970919AG2-571 GEN
Solar/Wind Harmer
4.706
971645AH1-323 GEN
50/50
29.57
3152191CUNINGD
50/50
5.787
3152171CUNINGB
50/50
2.498
972255AH1-712 GEN
50/50
174.946
3142416OLDCHRC
Solar/Wind Harmer
3.633
970293AG2-193 GEN
Solar/Wind Harmer
4.275
316473AC1-191 GEN
Solar/Wind Harmer
3.586
3142946ENON
Solar/Wind Harmer
-0.011
316382AG1-145 C
Solar/Wind Harmer
0.97
3143096IRON208
Adder
1.18
3143096IRON208
Adder
1.156
3142433PROV 92
Adder
0.533
3142433PROV 92
Adder
0.533
3150921YORKTN3
Adder
6.848
3144216WINCHST
Adder
1.021
3141766HARMONY
Solar/Wind Harmer
2.7
970133AG2-095 GEN
Solar/Wind Harmer
3.39
3141843SHACKLE
Adder
1.366
316203AE2-005 GEN
Solar/Wind Harmer
12.665
970129AG2-093 GEN
Solar/Wind Harmer
16.797
316280AD1-041 GEN
Solar/Wind Harmer
2.246
315778AD1-151 GEN
Solar/Wind Harmer
25.655
316156AD2-030 GEN
Solar/Wind Harmer
0.788
3141873WAN 176
Solar/Wind Harmer
3.502
961611AG1-000B GEN
Solar/Wind Harmer
6.141
3151221GRAVEL6
Adder
18.739
3151171GRAVELC
Adder
3.605
3150861SPRUNCD
Adder
1.17
3145336SMITFLD
Solar/Wind Harmer
-0.011
315773AC2-141 GEN
Solar/Wind Harmer
11.843
965281AG1-393 GEN
Solar/Wind Harmer
3.521
3144536CHRHLND
Solar/Wind Harmer
-0.004
315839AE2-212 C
Solar/Wind Harmer
0.835
3151101ELIZAR3
Adder
22.78
3144873MCLAUGH
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
124.846
944601AF1-125 GEN
Solar/Wind Harmer
122.898
3146456SLIGO L269
Solar/Wind Harmer
-0.027
971153AH1-033 GEN
Solar/Wind Harmer
3.297
315813AE1-149 C
Solar/Wind Harmer
16.904
962971AG1-146 GEN
Solar/Wind Harmer
5.071
970659AG2-427 GEN
Solar/Wind Harmer
2.538
316083AB2-161 GEN
Solar/Wind Harmer
4.374
970661AG2-428 GEN
Solar/Wind Harmer
5.066
316320Y1-086
Solar/Wind Harmer
1.563
316484AD2-074 GEN
Solar/Wind Harmer
6.667
970009AG2-005 GEN
Solar/Wind Harmer
3.311
316435W1029_GEN3
Solar/Wind Harmer
4.764
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3145273HOLLAND
Solar/Wind Harmer
-0.019
316404AE1-155 C
Solar/Wind Harmer
4.935
3146376EDENTON
Solar/Wind Harmer
-0.025
315614AA2-178 GEN
Solar/Wind Harmer
2.642
3150351NORNECKC2
Adder
2.162
971157AH1-035 GEN
Solar/Wind Harmer
2.989
315737AD1-076 GEN
Solar/Wind Harmer
4.525
3156081AA2-088 GEN
Solar/Wind Harmer
7.605
3146206CASHIE
Solar/Wind Harmer
-0.023
971781AH1-399 GEN
Solar/Wind Harmer
1.433
3145893MURPHYS
Solar/Wind Harmer
0.161
3145893MURPHYS
Solar/Wind Harmer
-0.023
957521AF2-046 GEN
Solar/Wind Harmer
18.088
961681AG1-008 GEN
Solar/Wind Harmer
18.088
3156021HOLLOMANSOL
Solar/Wind Harmer
3.082
3146173TUNIS
Solar/Wind Harmer
-0.023
316463AE2-346 GEN
Solar/Wind Harmer
0.367
316140AB2-099
Solar/Wind Harmer
0.153
962331AG1-082 GEN
Solar/Wind Harmer
2.834
3145963POPLR C
Solar/Wind Harmer
-0.022
3146263WOODLND
Solar/Wind Harmer
-0.022
316317KELFORD C
Solar/Wind Harmer
1.035
3145823KELFORD
Solar/Wind Harmer
-0.022
316365GEN2_N
Solar/Wind Harmer
1.473
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
966621AG1-532 GEN
Solar/Wind Harmer
0.433
313506AB2-031 GEN
Solar/Wind Harmer
1.71
3145933PARMELE
Solar/Wind Harmer
-0.021
966801AG1-551 GEN
Solar/Wind Harmer
2.65
3145796HORNRTN
Solar/Wind Harmer
-0.084
3145796HORNRTN
Solar/Wind Harmer
-0.021
316210AC1-098 GEN
Solar/Wind Harmer
3.272
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
3147043LAWRENC
Solar/Wind Harmer
-0.012
316313AB2-026
Solar/Wind Harmer
0.545
316258AE1-075 C
Solar/Wind Harmer
0.491
316405AF2-144 C
Solar/Wind Harmer
0.518
3143336POWHATN
Solar/Wind Harmer
2.038
315724AD1-057 GEN
Solar/Wind Harmer
1.152
316327AA2-057 GEN
Solar/Wind Harmer
2.017
3146073TAR RVR
Solar/Wind Harmer
-0.02
3146083TARBORO
Solar/Wind Harmer
-0.02
3146233WITAKRS
Solar/Wind Harmer
0.41
3146233WITAKRS
Solar/Wind Harmer
-0.013
3138543CONSLDL
Solar/Wind Harmer
-0.013
3148013FISHERV
Solar/Wind Harmer
-0.019
3146776BUCKING
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
7.647
3145543BTLEBRO
Solar/Wind Harmer
-0.019
3145543BTLEBRO
Solar/Wind Harmer
-0.019
3146926FARMVIL
Solar/Wind Harmer
-0.011
970221AG2-151 GEN
Solar/Wind Harmer
11.942
942461AE2-259 GEN
Solar/Wind Harmer
2.869
970909AG2-566 GEN
Solar/Wind Harmer
1.812
3144293JTRSVLE
Adder
0.538
3151861LOWMORA
Adder
1.73
3147666LOUISA
Solar/Wind Helper
0.754
316170AC1-121 GEN2
Solar/Wind Helper
0.495
3132273ORANGE
Solar/Wind Helper
0.065
316044AC1-158 PL1
Solar/Wind Helper
1.776
316450AC1-158 RIC
Solar/Wind Helper
0.474
3141196NOKESVL
Solar/Wind Helper
1.109
227287AC2-120 GEN
Solar/Wind Helper
0.347
226910AB2-157 C
Solar/Wind Helper
0.014
970917AG2-570 GEN
Solar/Wind Harmer
37.181
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.814
315733AD1-074 GEN2
Solar/Wind Harmer
4.814
315735AD1-075 GEN1
Solar/Wind Harmer
2.408
3146206CASHIE
Solar/Wind Harmer
-0.023
970601AG2-382 GEN
Solar/Wind Harmer
10.248
965291AG1-394 GEN
Solar/Wind Harmer
2.065
316318V4-068
Solar/Wind Harmer
0.574
3145893MURPHYS
Solar/Wind Harmer
-0.062
3145893MURPHYS
Solar/Wind Harmer
-0.023
316315AB2-025 C
Solar/Wind Harmer
0.618
315814AE2-033 C
Solar/Wind Harmer
21.276
3145513AHOSKIE
Solar/Wind Harmer
0.198
961941AG1-037 GEN
Solar/Wind Harmer
0.17
3145513AHOSKIE
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.045
3145683EARLEYS
Solar/Wind Harmer
-0.022
3145683EARLEYS
Solar/Wind Harmer
-0.022
3146043SEABORD
Solar/Wind Harmer
-0.022
315607AA1-063A GEN
Solar/Wind Harmer
2.226
315652AC1-086 GEN
Solar/Wind Harmer
24.035
3146033SCOT NK
Solar/Wind Harmer
-0.085
946281AF1-292 GEN
Solar/Wind Harmer
0.477
316087AB2-174 GEN
Solar/Wind Harmer
3.037
3137643SOCKMAN
Solar/Wind Harmer
-0.084
3145796HORNRTN
Solar/Wind Harmer
-0.067
3145796HORNRTN
Solar/Wind Harmer
-0.008
316005AA1-067
Solar/Wind Harmer
0.418
316236AE1-162_GEN
Solar/Wind Harmer
0.857
316036AC1-147 C
Solar/Wind Harmer
0.744
3150991CHESPKB
Adder
2.571
3150991CHESPKB
Adder
2.509
316316AC1-027 C
Solar/Wind Harmer
0.843
3142956BIRDNECK
Solar/Wind Harmer
1.473
316185AD1-033 GEN
Solar/Wind Harmer
2.888
3145506HICKORY
Solar/Wind Harmer
-0.109
3145506HICKORY
Solar/Wind Harmer
-0.065
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.831
316018AA1-139 ULT2
Solar/Wind Harmer
2.323
316017AA1-139 ULT1
Solar/Wind Harmer
2.195
3137176SLIGO L2192
Solar/Wind Harmer
-0.107
3146456SLIGO L269
Solar/Wind Harmer
3.195
3130086AYDLETT
Solar/Wind Harmer
-0.107
970657AG2-426 GEN
Solar/Wind Harmer
8.416
970657AG2-426 GEN
Solar/Wind Harmer
1.76
3146386ELIZ CT
Solar/Wind Harmer
-0.027
316487AF1-042 GEN
Solar/Wind Harmer
3.489
316431W1029_GEN1
Solar/Wind Harmer
4.764
316433W1029_GEN2
Solar/Wind Harmer
4.764
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
958261AF2-120 GEN
Solar/Wind Harmer
9.913
3146376EDENTON
Solar/Wind Harmer
0.749
3146376EDENTON
Solar/Wind Harmer
0.749
315742AE1-103 GEN
Solar/Wind Harmer
2.636
3143526WINTERP
Solar/Wind Harmer
-0.127
316077AC2-138 C
Solar/Wind Harmer
0.505
3150341NORNECKC1
Adder
2.233
3150341NORNECKC1
Adder
2.216
316065AD1-022 GEN
Solar/Wind Harmer
11.781
316468AD1-105 GEN
Solar/Wind Harmer
2.59
3145893MURPHYS
Solar/Wind Harmer
0.643
3145893MURPHYS
Solar/Wind Harmer
-0.041
3144356SAPONY
Solar/Wind Harmer
0.799
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
316426AA2-053 GEN
Solar/Wind Harmer
2.169
316181AB2-040 GEN
Solar/Wind Harmer
2.968
3145593CAROLNA
Solar/Wind Harmer
-0.021
3145593CAROLNA
Solar/Wind Harmer
-0.021
966811AG1-552 GEN
Solar/Wind Harmer
2.388
3145593CAROLNA
Solar/Wind Harmer
0.176
3145933PARMELE
Solar/Wind Harmer
-0.042
3145933PARMELE
Solar/Wind Harmer
-0.021
3145783HORNRTN
Solar/Wind Harmer
2.507
3145783HORNRTN
Solar/Wind Harmer
2.006
3145783HORNRTN
Solar/Wind Harmer
0.627
3145783HORNRTN
Solar/Wind Harmer
0.251
3145796HORNRTN
Solar/Wind Harmer
-0.063
971223AH1-071 GEN
Solar/Wind Harmer
2.587
316274AC1-208 GEN
Solar/Wind Harmer
2.221
3145493TOT1
Solar/Wind Harmer
0.305
3145453TOT5
Solar/Wind Harmer
0.183
3145603CNETO
Solar/Wind Harmer
0.122
972185AH1-677 GEN
Adder
9.771
972187AH1-678 GEN
Adder
4.927
970933AG2-581 GEN
Solar/Wind Harmer
18.199
3146776BUCKING
Solar/Wind Harmer
-0.077
3146776BUCKING
Solar/Wind Harmer
-0.006
315821AE2-092 GEN
Solar/Wind Harmer
4.01
961601AG1-000A GEN
Solar/Wind Harmer
7.551
316263AC1-034 GEN
Solar/Wind Harmer
8.998
971489AH1-241 GEN
Solar/Wind Harmer
11.337
970301AG2-198 GEN
Solar/Wind Harmer
9.543
971741AH1-377 GEN
Solar/Wind Harmer
22.151
3144293JTRSVLE
Adder
0.538
3144293JTRSVLE
Adder
0.453
316447AC1-158 HLD
Solar/Wind Helper
3.909
966001AG1-469 GEN
Solar/Wind Helper
0.344
315651AD1-115 GEN
Solar/Wind Helper
1.07
226929AD2-058 GEN
Solar/Wind Helper
0.102
3145746EVERETS
Solar/Wind Harmer
-0.082
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
970181AG2-120 GEN
Solar/Wind Harmer
2.71
957861AF2-080 GEN
Solar/Wind Harmer
8.816
316420AA1-050 GEN
Solar/Wind Harmer
2.274
941031AE2-094 GEN
Solar/Wind Harmer
37.192
944011AF1-069 GEN
Solar/Wind Harmer
11.653
970831AG2-522 GEN
Solar/Wind Harmer
9.906
3145573BETHELC
Solar/Wind Harmer
-0.02
3145573BETHELC
Solar/Wind Harmer
-0.02
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
970673AG2-436 GEN
Solar/Wind Harmer
41.288
970673AG2-436 GEN
Solar/Wind Harmer
20.905
316319Z2-044 C
Solar/Wind Harmer
1.082
971967AH1-528 GEN
Solar/Wind Harmer
36.82
3148133STUARTS
Solar/Wind Harmer
-0.012
3148013FISHERV
Solar/Wind Harmer
-0.011
972205AH1-687 GEN
Adder
7.401
971845AH1-439 GEN
Solar/Wind Harmer
10.254
970285AG2-188 GEN
Solar/Wind Harmer
16.872
971447AH1-217 GEN
Solar/Wind Harmer
6.829
3151881LOWMORC
Adder
1.717
3151881LOWMORC
Adder
1.69
3151861LOWMORA
Adder
1.663
316164AC1-076 GEN
Solar/Wind Helper
1.621
316411AF1-147_GEN1
Solar/Wind Helper
0.854
316415AF1-147_GEN2
Solar/Wind Helper
0.854
3138216PACIFIC
Solar/Wind Helper
0.042
3141426STAFORD
Solar/Wind Helper
0.05
CBM West 1LTFEXP_CBM-W1->PJM
CBM
42.549
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.802
MECLTFEXP_MEC->PJM
CLTF
6.015
LAGNLTFEXP_LAGN->PJM
CLTF
10.499
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.17
TVALTFEXP_TVA->PJM
CLTF
5.345
SIGELTFEXP_SIGE->PJM
CLTF
0.188
CPLELTFEXP_CPLE->PJM
CLTF
11.179
NYPJM->LTFIMP_NY
CLTF
3.551
LGEELTFEXP_LGEE->PJM
CLTF
2.38
CBM West 2LTFEXP_CBM-W2->PJM
CBM
59.371
WECLTFEXP_WEC->PJM
CLTF
1.203
AG2-052LTFEXP_AG2-052->PJM
LTF
0.068
AH1-155LTFEXP_AH1-155->PJM
LTF
0.101

Details for 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:126.22 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5137.22
MW Contribution:7.9
Bus #Bus NameTypeMW Contribution
3150411LDYSMT5
50/50
38.405
3150381LDYSMT2
50/50
36.755
972213AH1-691 GEN
50/50
6.217
972215AH1-692 GEN
50/50
6.217
963051AG1-154 GEN
50/50
4.783
972189AH1-679 GEN
50/50
4.654
316312AB1-027
Solar/Wind Harmer
0.455
316233AE1-074 FULL
Solar/Wind Harmer
0.199
971281AH1-106 GEN
Solar/Wind Harmer
3.456
971283AH1-107 GEN
Solar/Wind Harmer
3.456
971285AH1-108 GEN
Adder
1.878
315976AC1-164 GENA
Solar/Wind Harmer
25.718
316169AC1-164_GENC
Solar/Wind Harmer
22.218
315975AC1-164 GENB
Solar/Wind Harmer
0.761
3152261N ANNA2
50/50
14.825
970497AG2-320 GEN
50/50
26.932
3150401LDYSMT4
50/50
38.285
3150371LDYSMT1
50/50
36.994
315051AA1-145 CT1
50/50
2.076
3142416OLDCHRC
Solar/Wind Harmer
2.465
970293AG2-193 GEN
Solar/Wind Harmer
2.678
3143096IRON208
Adder
1.045
3143096IRON208
Adder
1.024
3150861SPRUNCD
Adder
1.148
316473AC1-191 GEN
Solar/Wind Harmer
0.839
3142946ENON
Solar/Wind Harmer
0.083
970133AG2-095 GEN
Solar/Wind Harmer
2.349
316382AG1-145 C
Solar/Wind Harmer
0.002
970129AG2-093 GEN
Solar/Wind Harmer
14.714
315778AD1-151 GEN
Solar/Wind Harmer
19.405
965281AG1-393 GEN
Solar/Wind Harmer
2.587
315839AE2-212 C
Solar/Wind Harmer
0.002
3142433PROV 92
Adder
0.469
3142433PROV 92
Adder
0.469
3150921YORKTN3
Adder
6.055
3144216WINCHST
Adder
0.908
961611AG1-000B GEN
Solar/Wind Harmer
6.42
3151221GRAVEL6
Adder
17.444
3151171GRAVELC
Adder
3.356
315773AC2-141 GEN
Solar/Wind Harmer
8.761
3145336SMITFLD
Solar/Wind Harmer
0.096
315813AE1-149 C
Solar/Wind Harmer
12.736
3144536CHRHLND
Solar/Wind Harmer
0.035
970659AG2-427 GEN
Solar/Wind Harmer
2.51
944581AF1-123 GEN
Solar/Wind Harmer
53.367
944601AF1-125 GEN
Solar/Wind Harmer
52.545
3151101ELIZAR3
Adder
22.008
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3144873MCLAUGH
Solar/Wind Harmer
0.006
3141766HARMONY
Solar/Wind Harmer
3.157
3141843SHACKLE
Adder
1.209
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
970661AG2-428 GEN
Solar/Wind Harmer
4.998
316280AD1-041 GEN
Solar/Wind Harmer
0.005
316156AD2-030 GEN
Solar/Wind Harmer
0.174
3141873WAN 176
Solar/Wind Harmer
4.175
3146456SLIGO L269
Solar/Wind Harmer
0.234
316132AB2-190 GEN1
Solar/Wind Harmer
1.305
316369SG1_INVT
Solar/Wind Harmer
0.009
971167AH1-042 GEN
Solar/Wind Harmer
21.453
3142433PROV 92
Adder
0.469
3142433PROV 92
Adder
0.469
972265AH1-717 GEN
Adder
18.63
3151201GRAVEL4
Adder
17.465
3151191GRAVEL3
Adder
17.243
3151211GRAVEL5
Adder
17.243
971445AH1-216 GEN
Solar/Wind Harmer
16.824
3143873LANEXA
Solar/Wind Harmer
0.143
3143316POE
Solar/Wind Harmer
0.945
3138283WHITEMARSH
Solar/Wind Harmer
0.055
316314AB2-024 C
Solar/Wind Harmer
0.001
3151081ELIZAR1
Adder
21.73
3151091ELIZAR2
Adder
21.353
3152611GOSPORTB
Adder
3.018
3152621GOSPORTC
Adder
2.561
3152601GOSPORTA
Adder
2.363
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
7.011
315662AE1-191 GEN
Solar/Wind Harmer
0.008
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.047
957871AF2-081 GEN
Solar/Wind Harmer
11.676
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.161
316311AC2-079 GEN
Solar/Wind Harmer
6.724
319010AE1-072 C
Solar/Wind Harmer
1.178
3146406KITTY HAWK
Solar/Wind Harmer
0.029
316305AF2-043 C
Solar/Wind Harmer
0.002
315835AF2-110_GEN
Solar/Wind Harmer
1.595
3141913WHIT STONE
Solar/Wind Harmer
0.232
313526AB2-022
Solar/Wind Harmer
0.125
3138133OCRAN
Solar/Wind Harmer
0.069
3146486SUNBURY
Solar/Wind Harmer
0.231
3146486SUNBURY
Solar/Wind Harmer
0.231
316321Z2-027
Solar/Wind Harmer
0.043
3146396TANGLEW
Solar/Wind Harmer
0.635
3145176PASQUOTANK
Solar/Wind Harmer
0.143
3141783LANCAST
Solar/Wind Harmer
0.138
3141783LANCAST
Solar/Wind Harmer
0.092
962981AG1-147 GEN
Solar/Wind Harmer
8.47
316315AB2-025 C
Solar/Wind Harmer
0.183
941031AE2-094 GEN
Solar/Wind Harmer
41.622
944011AF1-069 GEN
Solar/Wind Harmer
13.599
315814AE2-033 C
Solar/Wind Harmer
17.851
970327AG2-215 GEN
Solar/Wind Harmer
7.386
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
47.408
970673AG2-436 GEN
Solar/Wind Harmer
31.605
3130156CHOWAN
Solar/Wind Harmer
0.222
3130156CHOWAN
Solar/Wind Harmer
0.222
971967AH1-528 GEN
Solar/Wind Harmer
35.12
315816AE2-034 GEN
Solar/Wind Harmer
0.932
3141813NORNECK
Solar/Wind Harmer
0.217
3130546PLYMOUTH
Solar/Wind Harmer
0.213
315732AD1-074 GEN1
Solar/Wind Harmer
1.221
315733AD1-074 GEN2
Solar/Wind Harmer
1.221
315735AD1-075 GEN1
Solar/Wind Harmer
0.611
965291AG1-394 GEN
Solar/Wind Harmer
0.939
3146206CASHIE
Solar/Wind Harmer
0.21
970601AG2-382 GEN
Solar/Wind Harmer
7.851
970085AG2-068 GEN
Solar/Wind Harmer
11.171
970581AG2-369 GEN
Solar/Wind Harmer
9.607
3145893MURPHYS
Solar/Wind Harmer
0.565
3145893MURPHYS
Solar/Wind Harmer
0.209
3145513AHOSKIE
Solar/Wind Harmer
0.431
3145513AHOSKIE
Solar/Wind Harmer
0.206
3145683EARLEYS
Solar/Wind Harmer
0.411
3145683EARLEYS
Solar/Wind Harmer
0.205
3145683EARLEYS
Solar/Wind Harmer
0.205
3146043SEABORD
Solar/Wind Harmer
0.205
315607AA1-063A GEN
Solar/Wind Harmer
0.417
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
22.128
3137643SOCKMAN
Solar/Wind Harmer
0.801
3145796HORNRTN
Solar/Wind Harmer
0.634
3145796HORNRTN
Solar/Wind Harmer
0.079
316223AC1-118
Solar/Wind Harmer
0.142
3146033SCOT NK
Solar/Wind Harmer
0.787
970831AG2-522 GEN
Solar/Wind Harmer
8.114
316005AA1-067
Solar/Wind Harmer
0.203
3145746EVERETS
Solar/Wind Harmer
0.753
3145746EVERETS
Solar/Wind Harmer
0.189
3145746EVERETS
Solar/Wind Harmer
0.189
3145746EVERETS
Solar/Wind Harmer
0.189
970181AG2-120 GEN
Solar/Wind Harmer
2.355
957861AF2-080 GEN
Solar/Wind Harmer
8.016
316420AA1-050 GEN
Solar/Wind Harmer
0.006
3145573BETHELC
Solar/Wind Harmer
0.183
3145573BETHELC
Solar/Wind Harmer
0.183
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
3.031
3144303KENBRDG
Solar/Wind Harmer
0.144
970683AG2-441 GEN
Solar/Wind Harmer
11.977
970681AG2-440 GEN
Solar/Wind Harmer
9.582
946301AF1-294 GEN
Solar/Wind Harmer
3.532
961791AG1-021 GEN
Solar/Wind Harmer
1.718
315657AE1-056 GEN
Solar/Wind Harmer
6.158
944491AF1-114 GEN
Solar/Wind Harmer
0.001
970285AG2-188 GEN
Solar/Wind Harmer
13.414
316118AC1-105 GEN
Solar/Wind Harmer
0.437
971845AH1-439 GEN
Solar/Wind Harmer
7.626
972193AH1-681 GEN
Adder
3.818
3147173SINAI
Solar/Wind Harmer
0.166
3147243WELCO
Solar/Wind Harmer
0.104
972205AH1-687 GEN
Adder
6.726
970865AG2-541 GEN
Solar/Wind Harmer
5.131
971447AH1-217 GEN
Solar/Wind Harmer
4.386
316123AC1-075 GEN
Solar/Wind Harmer
0.186
970165AG2-112 GEN
Solar/Wind Harmer
1.103
970163AG2-111 GEN
Solar/Wind Harmer
1.052
270494AE1-108_GEN
Solar/Wind Harmer
1.582
316164AC1-076 GEN
Solar/Wind Helper
1.947
316411AF1-147_GEN1
Solar/Wind Helper
0.8
316415AF1-147_GEN2
Solar/Wind Helper
0.8
3138216PACIFIC
Solar/Wind Helper
0.039
3152251N ANNA1
50/50
14.826
972197AH1-683 GEN
50/50
5.978
972219AH1-694 GEN
50/50
4.304
315052AA1-145 CT2
50/50
2.085
966881AG1-559 GEN
Solar/Wind Harmer
0.307
3142416OLDCHRC
Solar/Wind Harmer
0.661
3142416OLDCHRC
Solar/Wind Harmer
0.253
3143096IRON208
Adder
1.045
3143526WINTERP
Solar/Wind Harmer
1.295
3150851SPRUNCC
Adder
1.148
3142543TWELFTH
Solar/Wind Harmer
0.024
3143226MDLTHAN
Solar/Wind Harmer
0.248
944631AF1-128 GEN
Adder
117.965
316159AE1-175 C
Solar/Wind Harmer
0.21
970129AG2-093 GEN
Solar/Wind Harmer
6.924
316458AB2-190 GEN2
Solar/Wind Harmer
1.305
315671AE2-027_GEN
Solar/Wind Harmer
15.554
971069AG2-661 GEN
Solar/Wind Harmer
4.312
971647AH1-324 GEN
Solar/Wind Harmer
10.299
971317AH1-138 GEN
Solar/Wind Harmer
1.8
3142433PROV 92
Solar/Wind Harmer
0.964
3142433PROV 92
Adder
0.469
3142433PROV 92
Adder
0.469
3138126ROCKLANDING
Solar/Wind Harmer
0.111
961611AG1-000B GEN
Solar/Wind Harmer
12.625
3151171GRAVELC
Adder
2.552
316294AC1-161 GEN
Solar/Wind Harmer
4.156
3145336SMITFLD
Solar/Wind Harmer
0.955
970659AG2-427 GEN
Solar/Wind Harmer
11.475
944591AF1-124 GEN
Solar/Wind Harmer
53.557
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.959
316381AD1-082 GEN
Solar/Wind Harmer
0.247
3141766HARMONY
Solar/Wind Harmer
0.047
971777AH1-397 GEN
Solar/Wind Harmer
0.625
3141843SHACKLE
Adder
1.209
970661AG2-428 GEN
Solar/Wind Harmer
23.497
316072AD1-144
Solar/Wind Harmer
0.085
939411AE1-173 GEN
Solar/Wind Harmer
100.291
971153AH1-033 GEN
Solar/Wind Harmer
2.705
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.228
3146626S HERTFORD
Solar/Wind Harmer
0.227
962971AG1-146 GEN
Solar/Wind Harmer
3.63
3145273HOLLAND
Solar/Wind Harmer
0.17
970009AG2-005 GEN
Solar/Wind Harmer
1.68
3146376EDENTON
Solar/Wind Harmer
0.222
316404AE1-155 C
Solar/Wind Harmer
0.05
315614AA2-178 GEN
Solar/Wind Harmer
1.242
3150351NORNECKC2
Adder
2.198
971781AH1-399 GEN
Solar/Wind Harmer
0.285
971157AH1-035 GEN
Solar/Wind Harmer
2.559
315737AD1-076 GEN
Solar/Wind Harmer
2.735
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
316313AB2-026
Solar/Wind Harmer
0.134
316258AE1-075 C
Solar/Wind Harmer
0.16
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.201
970917AG2-570 GEN
Solar/Wind Harmer
18.693
3146206CASHIE
Solar/Wind Harmer
0.21
316365GEN2_N
Solar/Wind Harmer
0.471
3145893MURPHYS
Solar/Wind Harmer
0.35
3145893MURPHYS
Solar/Wind Harmer
0.209
957521AF2-046 GEN
Solar/Wind Harmer
15.533
961681AG1-008 GEN
Solar/Wind Harmer
15.533
3146173TUNIS
Solar/Wind Harmer
0.207
3156021HOLLOMANSOL
Solar/Wind Harmer
0.94
316463AE2-346 GEN
Solar/Wind Harmer
0.177
316140AB2-099
Solar/Wind Harmer
0.074
962331AG1-082 GEN
Solar/Wind Harmer
2.201
3146263WOODLND
Solar/Wind Harmer
0.204
3145963POPLR C
Solar/Wind Harmer
0.202
313506AB2-031 GEN
Solar/Wind Harmer
0.624
3142666NORTHAMPTON
Solar/Wind Harmer
0.202
316317KELFORD C
Solar/Wind Harmer
0.019
3145823KELFORD
Solar/Wind Harmer
0.201
3145796HORNRTN
Solar/Wind Harmer
0.792
3145796HORNRTN
Solar/Wind Harmer
0.198
3141906WESTMOR
Solar/Wind Harmer
0.079
3147043LAWRENC
Solar/Wind Harmer
0.118
316478AD1-087 GEN
Solar/Wind Harmer
0.676
316486AD2-202 GEN
Solar/Wind Harmer
0.198
316210AC1-098 GEN
Solar/Wind Harmer
1.795
3145933PARMELE
Solar/Wind Harmer
0.193
966801AG1-551 GEN
Solar/Wind Harmer
2.252
970737AG2-469 GEN
Solar/Wind Harmer
8.074
3145746EVERETS
Solar/Wind Harmer
0.189
3145746EVERETS
Solar/Wind Harmer
0.189
315724AD1-057 GEN
Solar/Wind Harmer
0.705
316327AA2-057 GEN
Solar/Wind Harmer
0.281
970909AG2-566 GEN
Solar/Wind Harmer
1.971
3146073TAR RVR
Solar/Wind Harmer
0.183
3146083TARBORO
Solar/Wind Harmer
0.183
3146233WITAKRS
Solar/Wind Harmer
0.919
3146233WITAKRS
Solar/Wind Harmer
0.124
3138543CONSLDL
Solar/Wind Harmer
0.12
3147666LOUISA
Solar/Wind Harmer
0.42
316131AB2-060 GEN
Solar/Wind Harmer
0.572
964241AG1-285 GEN
Solar/Wind Harmer
12.091
315785AD2-033 C
Solar/Wind Harmer
1.468
970257AG2-171 GEN
Solar/Wind Harmer
5.771
959311AF2-222 GEN
Solar/Wind Harmer
16.014
961601AG1-000A GEN
Solar/Wind Harmer
12.778
3145543BTLEBRO
Solar/Wind Harmer
0.179
3145543BTLEBRO
Solar/Wind Harmer
0.179
971623AH1-311 GEN
Solar/Wind Harmer
0.359
963181AG1-167 GEN
Solar/Wind Harmer
0.716
3144293JTRSVLE
Adder
0.57
3147133PAMPLIN
Solar/Wind Harmer
0.56
971193AH1-056 GEN
Solar/Wind Harmer
10.872
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.105
3146776BUCKING
Solar/Wind Harmer
0.06
972255AH1-712 GEN
Adder
85.454
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.086
971683AH1-343 GEN
Solar/Wind Harmer
5.663
316283AC2-100 C
Solar/Wind Harmer
0.294
970221AG2-151 GEN
Solar/Wind Harmer
7.9
3141316ARNOLDS
Adder
0.336
3150331BIRCHWDA
Adder
22.127
316044AC1-158 PL1
Solar/Wind Helper
2.207
316450AC1-158 RIC
Solar/Wind Helper
0.589
3141196NOKESVL
Solar/Wind Helper
1.25
316170AC1-121 GEN2
Solar/Wind Helper
0.431
3150391LDYSMT3
50/50
38.213
972195AH1-682 GEN
50/50
5.022
315673AE1-157 GEN
Solar/Wind Harmer
18.457
957411AF2-035 GEN
Solar/Wind Harmer
11.334
970317AG2-208 GEN
Solar/Wind Harmer
10.501
3142296MT RD221
Adder
0.82
3142366NRTHEST
Adder
0.825
3150691DARBY 3
Adder
18.133
3150701DARBY 4
Adder
18.091
3150681DARBY 2
Adder
18.07
3150671DARBY 1
Adder
18.049
316075AC2-137 C
Solar/Wind Harmer
0.069
3143526WINTERP
Solar/Wind Harmer
1.295
966871AG1-558 GEN
Solar/Wind Harmer
0.287
971223AH1-071 GEN
Solar/Wind Harmer
2.646
3142946ENON
Solar/Wind Harmer
0.025
944641AF1-129 GEN
Adder
116.855
316240AF1-291 C
Solar/Wind Harmer
0.002
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.272
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316036AC1-147 C
Solar/Wind Harmer
0.044
3150991CHESPKB
Adder
2.482
3150991CHESPKB
Adder
2.423
970657AG2-426 GEN
Solar/Wind Harmer
8.291
970657AG2-426 GEN
Solar/Wind Harmer
1.738
316316AC1-027 C
Solar/Wind Harmer
0.227
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.007
3145506HICKORY
Solar/Wind Harmer
0.942
3145506HICKORY
Solar/Wind Harmer
0.565
3145506HICKORY
Solar/Wind Harmer
0.141
316339AD2-160 GEN
Solar/Wind Harmer
0.381
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.131
3137176SLIGO L2192
Solar/Wind Harmer
0.931
3146456SLIGO L269
Solar/Wind Harmer
4.141
3130086AYDLETT
Solar/Wind Harmer
0.934
3146386ELIZ CT
Solar/Wind Harmer
0.231
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.228
3146516WINFALL
Solar/Wind Harmer
0.228
3146516WINFALL
Solar/Wind Harmer
0.228
3146626S HERTFORD
Solar/Wind Harmer
0.227
3146626S HERTFORD
Solar/Wind Harmer
0.227
3144356SAPONY
Solar/Wind Harmer
1.894
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
0.987
3146376EDENTON
Solar/Wind Harmer
0.987
958261AF2-120 GEN
Solar/Wind Harmer
7.345
972185AH1-677 GEN
Adder
12.364
972187AH1-678 GEN
Adder
6.203
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.271
3150341NORNECKC1
Adder
2.253
316468AD1-105 GEN
Solar/Wind Harmer
-0.071
970933AG2-581 GEN
Solar/Wind Harmer
17.147
316065AD1-022 GEN
Solar/Wind Harmer
9.721
3145893MURPHYS
Solar/Wind Harmer
1.401
3145893MURPHYS
Solar/Wind Harmer
0.376
3146173TUNIS
Solar/Wind Harmer
0.207
3146173TUNIS
Solar/Wind Harmer
0.207
316181AB2-040 GEN
Solar/Wind Harmer
0.293
3142666NORTHAMPTON
Solar/Wind Harmer
0.202
3142666NORTHAMPTON
Solar/Wind Harmer
0.202
3142666NORTHAMPTON
Solar/Wind Harmer
0.202
3142666NORTHAMPTON
Solar/Wind Harmer
0.121
970099AG2-077 GEN
Solar/Wind Harmer
21.434
316426AA2-053 GEN
Solar/Wind Harmer
0.677
3145593CAROLNA
Solar/Wind Harmer
0.199
3145593CAROLNA
Solar/Wind Harmer
0.199
966811AG1-552 GEN
Solar/Wind Harmer
2.162
3145593CAROLNA
Solar/Wind Harmer
0.248
3145783HORNRTN
Solar/Wind Harmer
3.524
3145783HORNRTN
Solar/Wind Harmer
2.819
3145783HORNRTN
Solar/Wind Harmer
0.881
3145783HORNRTN
Solar/Wind Harmer
0.352
3145796HORNRTN
Solar/Wind Harmer
0.594
3145933PARMELE
Solar/Wind Harmer
0.387
3145933PARMELE
Solar/Wind Harmer
0.193
316274AC1-208 GEN
Solar/Wind Harmer
0.996
971741AH1-377 GEN
Solar/Wind Harmer
18.605
970301AG2-198 GEN
Solar/Wind Harmer
7.883
939181AE1-148 GEN
Solar/Wind Harmer
8.803
3145493TOT1
Solar/Wind Harmer
0.424
3145453TOT5
Solar/Wind Harmer
0.255
3145603CNETO
Solar/Wind Harmer
0.17
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.695
971775AH1-396 GEN
Solar/Wind Harmer
0.289
961601AG1-000A GEN
Solar/Wind Harmer
3.194
316263AC1-034 GEN
Solar/Wind Harmer
6.824
958211AF2-115 GEN
Solar/Wind Harmer
2.148
963191AG1-168 GEN
Solar/Wind Harmer
0.716
3144293JTRSVLE
Adder
0.57
3144293JTRSVLE
Adder
0.48
3147133PAMPLIN
Solar/Wind Harmer
0.178
3147133PAMPLIN
Solar/Wind Harmer
0.143
962561AG1-105 GEN
Solar/Wind Harmer
8.357
964791AG1-342 GEN
Solar/Wind Harmer
3.316
3146843MT LREL
Solar/Wind Harmer
0.172
3146843MT LREL
Solar/Wind Harmer
0.172
3146776BUCKING
Solar/Wind Harmer
0.67
3146776BUCKING
Solar/Wind Harmer
0.054
316222AC1-221 GEN
Solar/Wind Harmer
0.627
971489AH1-241 GEN
Solar/Wind Harmer
7.9
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
6.989
316447AC1-158 HLD
Solar/Wind Helper
4.858
315651AD1-115 GEN
Solar/Wind Helper
0.961
316388AE2-253 GEN
Solar/Wind Harmer
0.736
940641AE2-051 GEN
Solar/Wind Harmer
18.777
3146456SLIGO L269
Solar/Wind Harmer
0.234
316246AF1-032 C
Solar/Wind Harmer
0.105
316093AE2-104_GEN
Solar/Wind Harmer
3.91
3138133OCRAN
Solar/Wind Harmer
0.139
3146516WINFALL
Solar/Wind Harmer
0.74
3146516WINFALL
Solar/Wind Harmer
0.228
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
962861AG1-135 GEN
Solar/Wind Harmer
7.133
3130156CHOWAN
Solar/Wind Harmer
0.222
3141726DUNNSVL
Solar/Wind Harmer
0.878
3145663CRESWEL
Solar/Wind Harmer
0.608
971163AH1-040 GEN
Solar/Wind Harmer
17.369
3150351NORNECKC2
Adder
2.162
3143336POWHATN
Solar/Wind Harmer
3.766
970919AG2-571 GEN
Solar/Wind Harmer
7.477
3146206CASHIE
Solar/Wind Harmer
0.21
971547AH1-271 GEN
Solar/Wind Harmer
4.486
316023GEN1_S
Solar/Wind Harmer
0.471
970087AG2-069 GEN
Solar/Wind Harmer
16.757
3145893MURPHYS
Solar/Wind Harmer
0.837
3145893MURPHYS
Solar/Wind Harmer
0.931
316337AD2-073 GEN
Solar/Wind Harmer
0.181
3146173TUNIS
Solar/Wind Harmer
0.207
3145683EARLEYS
Solar/Wind Harmer
0.205
960081AF2-299 GEN
Solar/Wind Harmer
1.959
3146263WOODLND
Solar/Wind Harmer
0.204
316336AC2-165 C
Solar/Wind Harmer
0.008
3145963POPLR C
Solar/Wind Harmer
0.202
316011AB1-132 GEN
Solar/Wind Harmer
3.658
962571AG1-106 GEN
Solar/Wind Harmer
2.862
3145823KELFORD
Solar/Wind Harmer
0.201
957481AF2-042 GEN
Solar/Wind Harmer
53.584
316174AB2-169 GEN
Solar/Wind Harmer
0.005
316190AA2-174 GEN
Solar/Wind Harmer
0
971795AH1-408 GEN
Solar/Wind Harmer
13.299
3145783HORNRTN
Solar/Wind Harmer
0.198
3145796HORNRTN
Solar/Wind Harmer
0.653
3145796HORNRTN
Solar/Wind Harmer
0.198
3147043LAWRENC
Adder
1.785
315693AD1-088 GEN
Solar/Wind Harmer
9.451
962491AG1-098 GEN
Solar/Wind Harmer
11.2
316212AC1-099_GEN
Solar/Wind Harmer
1.001
3146293MARTNCO
Solar/Wind Harmer
0.179
3145746EVERETS
Solar/Wind Harmer
0.189
3145746EVERETS
Solar/Wind Harmer
0.189
316129AC1-054 GEN
Solar/Wind Harmer
0.711
971065AG2-659 GEN
Solar/Wind Harmer
8.033
315722AD1-056 GEN
Solar/Wind Harmer
1.189
316494AC1-189 GEN
Solar/Wind Harmer
0.628
972135AH1-637 GEN
Solar/Wind Harmer
1.564
961671AG1-007 GEN
Solar/Wind Harmer
0.028
3146083TARBORO
Solar/Wind Harmer
0.183
3145493TOT1
Solar/Wind Harmer
0.814
3146233WITAKRS
Solar/Wind Harmer
0.728
315687AD1-152 GEN
Solar/Wind Harmer
0.006
3147666LOUISA
Solar/Wind Harmer
0.73
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970685AG2-442 GEN
Solar/Wind Harmer
13.415
3145543BTLEBRO
Solar/Wind Harmer
0.179
3145543BTLEBRO
Solar/Wind Harmer
0.144
316359AB2-059 GEN
Solar/Wind Harmer
0.645
316049AB1-081 GEN
Solar/Wind Harmer
1.028
3142053HEARTS
Solar/Wind Harmer
0.316
963171AG1-166 GEN
Solar/Wind Harmer
0.955
971563AH1-280 GEN
Solar/Wind Harmer
1.909
3144293JTRSVLE
Adder
0.57
970937AG2-583 GEN
Solar/Wind Harmer
10.92
316192AB2-158 GEN
Solar/Wind Harmer
1.002
3146926FARMVIL
Solar/Wind Harmer
0.105
970401AG2-262 GEN
Solar/Wind Harmer
1.013
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.067
972277AH1-723 GEN
Adder
99.579
316003AC1-222 GEN
Solar/Wind Harmer
0.004
972003AH1-546 GEN
Solar/Wind Harmer
6.768
971377AH1-170 GEN
Solar/Wind Harmer
1.58
3147623JAMES R
Solar/Wind Harmer
0.343
316045AC1-158 PL2
Solar/Wind Helper
7.066
316006AB2-029 C
Solar/Wind Helper
0.145
316254AC1-120 GEN1
Solar/Wind Helper
1.294
LAGNLTFEXP_LAGN->PJM
CLTF
8.214
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.47
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.182
MECLTFEXP_MEC->PJM
CLTF
3.753
SIGELTFEXP_SIGE->PJM
CLTF
0.114
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.425
TVALTFEXP_TVA->PJM
CLTF
4.163
NYPJM->LTFIMP_NY
CLTF
3.205
LGEELTFEXP_LGEE->PJM
CLTF
1.386
WECLTFEXP_WEC->PJM
CLTF
0.672
CPLELTFEXP_CPLE->PJM
CLTF
11.58
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.571

Details for 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.64 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5073.15
MW Contribution:7.7
Bus #Bus NameTypeMW Contribution
3150411LDYSMT5
50/50
37.503
3150381LDYSMT2
50/50
35.892
972213AH1-691 GEN
50/50
6.072
972215AH1-692 GEN
50/50
6.072
963051AG1-154 GEN
50/50
4.67
972189AH1-679 GEN
50/50
4.522
316312AB1-027
Solar/Wind Harmer
0.441
971285AH1-108 GEN
Adder
1.812
315976AC1-164 GENA
Solar/Wind Harmer
24.889
316169AC1-164_GENC
Solar/Wind Harmer
21.501
315975AC1-164 GENB
Solar/Wind Harmer
0.736
316233AE1-074 FULL
Solar/Wind Harmer
0.192
971281AH1-106 GEN
Solar/Wind Harmer
3.326
971283AH1-107 GEN
Solar/Wind Harmer
3.326
316132AB2-190 GEN1
Solar/Wind Harmer
1.26
971167AH1-042 GEN
Solar/Wind Harmer
20.74
316369SG1_INVT
Solar/Wind Harmer
0.009
3142433PROV 92
Adder
0.453
3142433PROV 92
Adder
0.453
972265AH1-717 GEN
Adder
17.968
3151201GRAVEL4
Adder
16.844
3151191GRAVEL3
Adder
16.63
3151211GRAVEL5
Adder
16.63
3143873LANEXA
Solar/Wind Harmer
0.139
971445AH1-216 GEN
Solar/Wind Harmer
16.22
316314AB2-024 C
Solar/Wind Harmer
0.001
3138283WHITEMARSH
Solar/Wind Harmer
0.053
3143316POE
Solar/Wind Harmer
0.91
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.779
3151081ELIZAR1
Adder
20.934
3151091ELIZAR2
Adder
20.57
3152611GOSPORTB
Adder
2.907
3152621GOSPORTC
Adder
2.467
3152601GOSPORTA
Adder
2.276
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.045
957871AF2-081 GEN
Solar/Wind Harmer
11.247
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.155
316311AC2-079 GEN
Solar/Wind Harmer
6.478
319010AE1-072 C
Solar/Wind Harmer
1.135
3146406KITTY HAWK
Solar/Wind Harmer
0.028
316305AF2-043 C
Solar/Wind Harmer
0.002
3141913WHIT STONE
Solar/Wind Harmer
0.224
315835AF2-110_GEN
Solar/Wind Harmer
1.537
3138133OCRAN
Solar/Wind Harmer
0.067
313526AB2-022
Solar/Wind Harmer
0.121
3146486SUNBURY
Solar/Wind Harmer
0.222
3146486SUNBURY
Solar/Wind Harmer
0.222
3141783LANCAST
Solar/Wind Harmer
0.133
3141783LANCAST
Solar/Wind Harmer
0.089
316321Z2-027
Solar/Wind Harmer
0.041
3146396TANGLEW
Solar/Wind Harmer
0.612
3145176PASQUOTANK
Solar/Wind Harmer
0.138
962981AG1-147 GEN
Solar/Wind Harmer
8.191
316315AB2-025 C
Solar/Wind Harmer
0.176
970327AG2-215 GEN
Solar/Wind Harmer
7.143
315814AE2-033 C
Solar/Wind Harmer
17.164
941031AE2-094 GEN
Solar/Wind Harmer
39.927
944011AF1-069 GEN
Solar/Wind Harmer
13.046
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.214
3130156CHOWAN
Solar/Wind Harmer
0.214
970673AG2-436 GEN
Solar/Wind Harmer
45.48
970673AG2-436 GEN
Solar/Wind Harmer
30.32
971967AH1-528 GEN
Solar/Wind Harmer
33.699
3141813NORNECK
Solar/Wind Harmer
0.21
315816AE2-034 GEN
Solar/Wind Harmer
0.897
3130546PLYMOUTH
Solar/Wind Harmer
0.205
315732AD1-074 GEN1
Solar/Wind Harmer
1.176
315733AD1-074 GEN2
Solar/Wind Harmer
1.176
315735AD1-075 GEN1
Solar/Wind Harmer
0.588
965291AG1-394 GEN
Solar/Wind Harmer
0.904
3146206CASHIE
Solar/Wind Harmer
0.202
970601AG2-382 GEN
Solar/Wind Harmer
7.556
3145893MURPHYS
Solar/Wind Harmer
0.544
3145893MURPHYS
Solar/Wind Harmer
0.201
970085AG2-068 GEN
Solar/Wind Harmer
10.719
970581AG2-369 GEN
Solar/Wind Harmer
9.218
3145513AHOSKIE
Solar/Wind Harmer
0.415
3145513AHOSKIE
Solar/Wind Harmer
0.198
3145683EARLEYS
Solar/Wind Harmer
0.395
3145683EARLEYS
Solar/Wind Harmer
0.197
3145683EARLEYS
Solar/Wind Harmer
0.197
3146043SEABORD
Solar/Wind Harmer
0.197
315607AA1-063A GEN
Solar/Wind Harmer
0.401
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
21.282
3137643SOCKMAN
Solar/Wind Harmer
0.77
316223AC1-118
Solar/Wind Harmer
0.138
3145796HORNRTN
Solar/Wind Harmer
0.609
3145796HORNRTN
Solar/Wind Harmer
0.076
3146033SCOT NK
Solar/Wind Harmer
0.757
3152251N ANNA1
50/50
13.891
972197AH1-683 GEN
50/50
5.838
972219AH1-694 GEN
50/50
4.203
315052AA1-145 CT2
50/50
2.026
316045AC1-158 PL2
Solar/Wind Harmer
4.381
966881AG1-559 GEN
Solar/Wind Harmer
0.299
3142416OLDCHRC
Solar/Wind Harmer
0.641
3142416OLDCHRC
Solar/Wind Harmer
0.245
3143096IRON208
Adder
1.01
3150851SPRUNCC
Adder
1.107
3142543TWELFTH
Solar/Wind Harmer
0.023
3143526WINTERP
Solar/Wind Harmer
1.246
944631AF1-128 GEN
Adder
114.018
3143226MDLTHAN
Solar/Wind Harmer
0.238
316159AE1-175 C
Solar/Wind Harmer
0.203
970129AG2-093 GEN
Solar/Wind Harmer
6.683
316458AB2-190 GEN2
Solar/Wind Harmer
1.26
315671AE2-027_GEN
Solar/Wind Harmer
15.005
971069AG2-661 GEN
Solar/Wind Harmer
4.161
3142433PROV 92
Solar/Wind Harmer
0.932
3142433PROV 92
Adder
0.453
3142433PROV 92
Adder
0.453
971647AH1-324 GEN
Solar/Wind Harmer
9.937
971317AH1-138 GEN
Solar/Wind Harmer
1.739
3138126ROCKLANDING
Solar/Wind Harmer
0.107
961611AG1-000B GEN
Solar/Wind Harmer
12.179
3151171GRAVELC
Adder
2.462
316294AC1-161 GEN
Solar/Wind Harmer
4.004
3145336SMITFLD
Solar/Wind Harmer
0.921
3141766HARMONY
Solar/Wind Harmer
0.046
971777AH1-397 GEN
Solar/Wind Harmer
0.604
3141843SHACKLE
Adder
1.169
970659AG2-427 GEN
Solar/Wind Harmer
11.057
944591AF1-124 GEN
Solar/Wind Harmer
51.588
316381AD1-082 GEN
Solar/Wind Harmer
0.238
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.851
970661AG2-428 GEN
Solar/Wind Harmer
22.639
316072AD1-144
Solar/Wind Harmer
0.082
316388AE2-253 GEN
Solar/Wind Harmer
0.708
939411AE1-173 GEN
Solar/Wind Harmer
96.357
3146456SLIGO L269
Solar/Wind Harmer
0.225
940641AE2-051 GEN
Solar/Wind Harmer
18.025
316246AF1-032 C
Solar/Wind Harmer
0.101
316093AE2-104_GEN
Solar/Wind Harmer
3.766
3138133OCRAN
Solar/Wind Harmer
0.134
3146516WINFALL
Solar/Wind Harmer
0.713
3146516WINFALL
Solar/Wind Harmer
0.22
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
962861AG1-135 GEN
Solar/Wind Harmer
6.899
3130156CHOWAN
Solar/Wind Harmer
0.214
3141726DUNNSVL
Solar/Wind Harmer
0.85
3150351NORNECKC2
Adder
2.092
3145663CRESWEL
Solar/Wind Harmer
0.585
971163AH1-040 GEN
Solar/Wind Harmer
16.721
3143336POWHATN
Solar/Wind Harmer
3.631
3146206CASHIE
Solar/Wind Harmer
0.202
971547AH1-271 GEN
Solar/Wind Harmer
4.318
970919AG2-571 GEN
Solar/Wind Harmer
7.174
316023GEN1_S
Solar/Wind Harmer
0.453
3145893MURPHYS
Solar/Wind Harmer
0.805
3145893MURPHYS
Solar/Wind Harmer
0.896
316337AD2-073 GEN
Solar/Wind Harmer
0.175
970087AG2-069 GEN
Solar/Wind Harmer
16.078
3146173TUNIS
Solar/Wind Harmer
0.199
3145683EARLEYS
Solar/Wind Harmer
0.197
960081AF2-299 GEN
Solar/Wind Harmer
1.885
3146263WOODLND
Solar/Wind Harmer
0.196
316336AC2-165 C
Solar/Wind Harmer
0.008
3145963POPLR C
Solar/Wind Harmer
0.194
316011AB1-132 GEN
Solar/Wind Harmer
3.518
962571AG1-106 GEN
Solar/Wind Harmer
2.753
3145823KELFORD
Solar/Wind Harmer
0.193
957481AF2-042 GEN
Solar/Wind Harmer
51.474
316174AB2-169 GEN
Solar/Wind Harmer
0.005
316190AA2-174 GEN
Solar/Wind Harmer
0
971795AH1-408 GEN
Solar/Wind Harmer
12.793
3152261N ANNA2
50/50
13.89
970497AG2-320 GEN
50/50
26.316
3150401LDYSMT4
50/50
37.387
3150371LDYSMT1
50/50
36.126
315051AA1-145 CT1
50/50
2.017
316044AC1-158 PL1
Solar/Wind Harmer
1.37
316450AC1-158 RIC
Solar/Wind Harmer
0.365
3142416OLDCHRC
Solar/Wind Harmer
2.389
970293AG2-193 GEN
Solar/Wind Harmer
2.592
3143096IRON208
Adder
1.01
3143096IRON208
Adder
0.989
316473AC1-191 GEN
Solar/Wind Harmer
0.814
3150861SPRUNCD
Adder
1.107
3142946ENON
Solar/Wind Harmer
0.08
970133AG2-095 GEN
Solar/Wind Harmer
2.267
316382AG1-145 C
Solar/Wind Harmer
0.002
970129AG2-093 GEN
Solar/Wind Harmer
14.202
315778AD1-151 GEN
Solar/Wind Harmer
18.726
965281AG1-393 GEN
Solar/Wind Harmer
2.495
315839AE2-212 C
Solar/Wind Harmer
0.002
3142433PROV 92
Adder
0.453
3142433PROV 92
Adder
0.453
3150921YORKTN3
Adder
5.845
3144216WINCHST
Adder
0.877
961611AG1-000B GEN
Solar/Wind Harmer
6.193
3151221GRAVEL6
Adder
16.824
3151171GRAVELC
Adder
3.237
315773AC2-141 GEN
Solar/Wind Harmer
8.441
3145336SMITFLD
Solar/Wind Harmer
0.092
315813AE1-149 C
Solar/Wind Harmer
12.273
3144536CHRHLND
Solar/Wind Harmer
0.034
3141766HARMONY
Solar/Wind Harmer
3.053
3141843SHACKLE
Adder
1.169
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
970659AG2-427 GEN
Solar/Wind Harmer
2.419
3151101ELIZAR3
Adder
21.202
944581AF1-123 GEN
Solar/Wind Harmer
51.405
944601AF1-125 GEN
Solar/Wind Harmer
50.613
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3144873MCLAUGH
Solar/Wind Harmer
0.006
316280AD1-041 GEN
Solar/Wind Harmer
0.005
970661AG2-428 GEN
Solar/Wind Harmer
4.815
316156AD2-030 GEN
Solar/Wind Harmer
0.168
3141873WAN 176
Solar/Wind Harmer
4.037
3146456SLIGO L269
Solar/Wind Harmer
0.225
971153AH1-033 GEN
Solar/Wind Harmer
2.606
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.22
962971AG1-146 GEN
Solar/Wind Harmer
3.51
3146626S HERTFORD
Solar/Wind Harmer
0.218
3145273HOLLAND
Solar/Wind Harmer
0.163
970009AG2-005 GEN
Solar/Wind Harmer
1.625
316404AE1-155 C
Solar/Wind Harmer
0.048
3146376EDENTON
Solar/Wind Harmer
0.214
971781AH1-399 GEN
Solar/Wind Harmer
0.276
3150351NORNECKC2
Adder
2.127
315614AA2-178 GEN
Solar/Wind Harmer
1.196
971157AH1-035 GEN
Solar/Wind Harmer
2.463
315737AD1-076 GEN
Solar/Wind Harmer
2.632
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
316313AB2-026
Solar/Wind Harmer
0.129
316258AE1-075 C
Solar/Wind Harmer
0.154
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
3.087
3146206CASHIE
Solar/Wind Harmer
0.202
970917AG2-570 GEN
Solar/Wind Harmer
17.936
316365GEN2_N
Solar/Wind Harmer
0.453
3145893MURPHYS
Solar/Wind Harmer
0.337
3145893MURPHYS
Solar/Wind Harmer
0.201
957521AF2-046 GEN
Solar/Wind Harmer
14.949
961681AG1-008 GEN
Solar/Wind Harmer
14.949
3146173TUNIS
Solar/Wind Harmer
0.199
3156021HOLLOMANSOL
Solar/Wind Harmer
0.905
316463AE2-346 GEN
Solar/Wind Harmer
0.17
316140AB2-099
Solar/Wind Harmer
0.071
962331AG1-082 GEN
Solar/Wind Harmer
2.118
3146263WOODLND
Solar/Wind Harmer
0.196
3145963POPLR C
Solar/Wind Harmer
0.194
313506AB2-031 GEN
Solar/Wind Harmer
0.6
3142666NORTHAMPTON
Solar/Wind Harmer
0.194
316317KELFORD C
Solar/Wind Harmer
0.019
3145823KELFORD
Solar/Wind Harmer
0.193
3141906WESTMOR
Solar/Wind Harmer
0.077
3145796HORNRTN
Solar/Wind Harmer
0.762
3145796HORNRTN
Solar/Wind Harmer
0.19
3147043LAWRENC
Solar/Wind Harmer
0.114
316210AC1-098 GEN
Solar/Wind Harmer
1.726
316478AD1-087 GEN
Solar/Wind Harmer
0.649
316486AD2-202 GEN
Solar/Wind Harmer
0.191
3145933PARMELE
Solar/Wind Harmer
0.186
966801AG1-551 GEN
Solar/Wind Harmer
2.166
970737AG2-469 GEN
Solar/Wind Harmer
7.816
3145746EVERETS
Solar/Wind Harmer
0.182
3145746EVERETS
Solar/Wind Harmer
0.182
315724AD1-057 GEN
Solar/Wind Harmer
0.678
3147666LOUISA
Solar/Wind Harmer
0.412
316327AA2-057 GEN
Solar/Wind Harmer
0.27
970909AG2-566 GEN
Solar/Wind Harmer
1.901
3146073TAR RVR
Solar/Wind Harmer
0.176
3146083TARBORO
Solar/Wind Harmer
0.176
3146233WITAKRS
Solar/Wind Harmer
0.883
3146233WITAKRS
Solar/Wind Harmer
0.12
3138543CONSLDL
Solar/Wind Harmer
0.116
316131AB2-060 GEN
Solar/Wind Harmer
0.55
964241AG1-285 GEN
Solar/Wind Harmer
11.64
315785AD2-033 C
Solar/Wind Harmer
1.415
970257AG2-171 GEN
Solar/Wind Harmer
5.56
959311AF2-222 GEN
Solar/Wind Harmer
15.432
961601AG1-000A GEN
Solar/Wind Harmer
12.283
3145543BTLEBRO
Solar/Wind Harmer
0.172
3145543BTLEBRO
Solar/Wind Harmer
0.172
3150391LDYSMT3
50/50
37.317
972195AH1-682 GEN
50/50
4.904
316447AC1-158 HLD
Solar/Wind Harmer
3.012
315673AE1-157 GEN
Solar/Wind Harmer
17.997
957411AF2-035 GEN
Solar/Wind Harmer
11.043
970317AG2-208 GEN
Solar/Wind Harmer
10.231
3142296MT RD221
Adder
0.795
3142366NRTHEST
Adder
0.798
3150691DARBY 3
Adder
17.546
3150701DARBY 4
Adder
17.506
3150681DARBY 2
Adder
17.485
3150671DARBY 1
Adder
17.465
316075AC2-137 C
Solar/Wind Harmer
0.066
966871AG1-558 GEN
Solar/Wind Harmer
0.278
3143526WINTERP
Solar/Wind Harmer
1.246
3142946ENON
Solar/Wind Harmer
0.024
971223AH1-071 GEN
Solar/Wind Harmer
2.54
944641AF1-129 GEN
Adder
112.782
316240AF1-291 C
Solar/Wind Harmer
0.002
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.263
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316036AC1-147 C
Solar/Wind Harmer
0.042
3150991CHESPKB
Adder
2.391
3150991CHESPKB
Adder
2.334
970657AG2-426 GEN
Solar/Wind Harmer
7.988
970657AG2-426 GEN
Solar/Wind Harmer
1.675
316316AC1-027 C
Solar/Wind Harmer
0.219
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.006
3145506HICKORY
Solar/Wind Harmer
0.907
3145506HICKORY
Solar/Wind Harmer
0.544
3145506HICKORY
Solar/Wind Harmer
0.136
316339AD2-160 GEN
Solar/Wind Harmer
0.367
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.126
3137176SLIGO L2192
Solar/Wind Harmer
0.897
3146456SLIGO L269
Solar/Wind Harmer
3.989
3130086AYDLETT
Solar/Wind Harmer
0.9
3146386ELIZ CT
Solar/Wind Harmer
0.223
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.22
3146516WINFALL
Solar/Wind Harmer
0.22
3146516WINFALL
Solar/Wind Harmer
0.22
3146626S HERTFORD
Solar/Wind Harmer
0.218
3146626S HERTFORD
Solar/Wind Harmer
0.218
3144356SAPONY
Solar/Wind Harmer
1.822
315742AE1-103 GEN
Solar/Wind Harmer
0.002
958261AF2-120 GEN
Solar/Wind Harmer
7.105
3146376EDENTON
Solar/Wind Harmer
0.951
3146376EDENTON
Solar/Wind Harmer
0.951
972185AH1-677 GEN
Adder
11.862
316468AD1-105 GEN
Solar/Wind Harmer
-0.068
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.197
3150341NORNECKC1
Adder
2.18
972187AH1-678 GEN
Adder
5.952
970933AG2-581 GEN
Solar/Wind Harmer
16.459
316065AD1-022 GEN
Solar/Wind Harmer
9.356
3145893MURPHYS
Solar/Wind Harmer
1.348
3145893MURPHYS
Solar/Wind Harmer
0.362
3146173TUNIS
Solar/Wind Harmer
0.199
3146173TUNIS
Solar/Wind Harmer
0.199
316181AB2-040 GEN
Solar/Wind Harmer
0.282
3142666NORTHAMPTON
Solar/Wind Harmer
0.194
3142666NORTHAMPTON
Solar/Wind Harmer
0.194
3142666NORTHAMPTON
Solar/Wind Harmer
0.194
3142666NORTHAMPTON
Solar/Wind Harmer
0.116
970099AG2-077 GEN
Solar/Wind Harmer
20.59
316426AA2-053 GEN
Solar/Wind Harmer
0.651
3145593CAROLNA
Solar/Wind Harmer
0.192
3145593CAROLNA
Solar/Wind Harmer
0.192
966811AG1-552 GEN
Solar/Wind Harmer
2.08
3145593CAROLNA
Solar/Wind Harmer
0.239
3145783HORNRTN
Solar/Wind Harmer
3.389
3145783HORNRTN
Solar/Wind Harmer
2.711
3145783HORNRTN
Solar/Wind Harmer
0.847
3145783HORNRTN
Solar/Wind Harmer
0.339
3145796HORNRTN
Solar/Wind Harmer
0.571
3145933PARMELE
Solar/Wind Harmer
0.372
3145933PARMELE
Solar/Wind Harmer
0.186
316274AC1-208 GEN
Solar/Wind Harmer
0.958
971741AH1-377 GEN
Solar/Wind Harmer
17.929
970301AG2-198 GEN
Solar/Wind Harmer
7.603
939181AE1-148 GEN
Solar/Wind Harmer
8.466
3145493TOT1
Solar/Wind Harmer
0.408
3145453TOT5
Solar/Wind Harmer
0.245
3145603CNETO
Solar/Wind Harmer
0.163
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.414
971775AH1-396 GEN
Solar/Wind Harmer
0.278
961601AG1-000A GEN
Solar/Wind Harmer
3.071
958211AF2-115 GEN
Solar/Wind Harmer
2.072
963191AG1-168 GEN
Solar/Wind Harmer
0.691
3144293JTRSVLE
Adder
0.55
3144293JTRSVLE
Adder
0.463
316263AC1-034 GEN
Solar/Wind Harmer
6.56
3147133PAMPLIN
Solar/Wind Harmer
0.172
3147133PAMPLIN
Solar/Wind Harmer
0.138
962561AG1-105 GEN
Solar/Wind Harmer
8.039
964791AG1-342 GEN
Solar/Wind Harmer
3.189
3146843MT LREL
Solar/Wind Harmer
0.166
3146843MT LREL
Solar/Wind Harmer
0.166
3146776BUCKING
Solar/Wind Harmer
0.649
3146776BUCKING
Solar/Wind Harmer
0.053
316222AC1-221 GEN
Solar/Wind Harmer
0.603
971489AH1-241 GEN
Solar/Wind Harmer
7.696
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
6.723
970831AG2-522 GEN
Solar/Wind Harmer
7.803
316005AA1-067
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.724
3145746EVERETS
Solar/Wind Harmer
0.182
3145746EVERETS
Solar/Wind Harmer
0.182
3145746EVERETS
Solar/Wind Harmer
0.182
970181AG2-120 GEN
Solar/Wind Harmer
2.265
957861AF2-080 GEN
Solar/Wind Harmer
7.708
316420AA1-050 GEN
Solar/Wind Harmer
0.006
3145573BETHELC
Solar/Wind Harmer
0.176
3145573BETHELC
Solar/Wind Harmer
0.176
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
2.92
3144303KENBRDG
Solar/Wind Harmer
0.139
970683AG2-441 GEN
Solar/Wind Harmer
11.546
970681AG2-440 GEN
Solar/Wind Harmer
9.237
946301AF1-294 GEN
Solar/Wind Harmer
3.407
961791AG1-021 GEN
Solar/Wind Harmer
1.657
315657AE1-056 GEN
Solar/Wind Harmer
5.941
944491AF1-114 GEN
Solar/Wind Harmer
0.001
970285AG2-188 GEN
Solar/Wind Harmer
12.999
971845AH1-439 GEN
Solar/Wind Harmer
7.393
972193AH1-681 GEN
Adder
3.724
316118AC1-105 GEN
Solar/Wind Harmer
0.42
3147173SINAI
Solar/Wind Harmer
0.16
3147243WELCO
Solar/Wind Harmer
0.1
972205AH1-687 GEN
Adder
6.548
970865AG2-541 GEN
Solar/Wind Harmer
4.934
971447AH1-217 GEN
Solar/Wind Harmer
4.275
316123AC1-075 GEN
Solar/Wind Harmer
0.179
970165AG2-112 GEN
Solar/Wind Harmer
1.061
970163AG2-111 GEN
Solar/Wind Harmer
1.012
270494AE1-108_GEN
Solar/Wind Harmer
1.539
316411AF1-147_GEN1
Solar/Wind Helper
0.785
316415AF1-147_GEN2
Solar/Wind Helper
0.785
3138216PACIFIC
Solar/Wind Helper
0.038
963181AG1-167 GEN
Solar/Wind Harmer
0.691
3144293JTRSVLE
Adder
0.55
971623AH1-311 GEN
Solar/Wind Harmer
0.345
3147133PAMPLIN
Solar/Wind Harmer
0.541
971193AH1-056 GEN
Solar/Wind Harmer
10.489
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.102
972255AH1-712 GEN
Adder
83.356
3146776BUCKING
Solar/Wind Harmer
0.058
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
6.812
971683AH1-343 GEN
Solar/Wind Harmer
5.445
316283AC2-100 C
Solar/Wind Harmer
0.283
970221AG2-151 GEN
Solar/Wind Harmer
7.696
3141316ARNOLDS
Adder
0.326
3150331BIRCHWDA
Adder
21.467
3141196NOKESVL
Solar/Wind Helper
1.224
3145783HORNRTN
Solar/Wind Harmer
0.19
3145796HORNRTN
Solar/Wind Harmer
0.628
3145796HORNRTN
Solar/Wind Harmer
0.19
3147043LAWRENC
Adder
1.718
315693AD1-088 GEN
Solar/Wind Harmer
9.086
962491AG1-098 GEN
Solar/Wind Harmer
10.769
316212AC1-099_GEN
Solar/Wind Harmer
0.963
3146293MARTNCO
Solar/Wind Harmer
0.172
3145746EVERETS
Solar/Wind Harmer
0.182
3145746EVERETS
Solar/Wind Harmer
0.182
316129AC1-054 GEN
Solar/Wind Harmer
0.684
971065AG2-659 GEN
Solar/Wind Harmer
7.725
315722AD1-056 GEN
Solar/Wind Harmer
1.144
3147666LOUISA
Solar/Wind Harmer
0.717
316494AC1-189 GEN
Solar/Wind Harmer
0.604
972135AH1-637 GEN
Solar/Wind Harmer
1.514
961671AG1-007 GEN
Solar/Wind Harmer
0.027
3146083TARBORO
Solar/Wind Harmer
0.176
3145493TOT1
Solar/Wind Harmer
0.783
3146233WITAKRS
Solar/Wind Harmer
0.7
315687AD1-152 GEN
Solar/Wind Harmer
0.006
316237AB2-079_GEN
Solar/Wind Harmer
0.001
316192AB2-158 GEN
Solar/Wind Harmer
0.987
970685AG2-442 GEN
Solar/Wind Harmer
12.932
3145543BTLEBRO
Solar/Wind Harmer
0.172
3145543BTLEBRO
Solar/Wind Harmer
0.138
963171AG1-166 GEN
Solar/Wind Harmer
0.921
971563AH1-280 GEN
Solar/Wind Harmer
1.842
3144293JTRSVLE
Adder
0.55
316359AB2-059 GEN
Solar/Wind Harmer
0.62
316049AB1-081 GEN
Solar/Wind Harmer
0.988
3142053HEARTS
Solar/Wind Harmer
0.304
970937AG2-583 GEN
Solar/Wind Harmer
10.585
3146926FARMVIL
Solar/Wind Harmer
0.102
970401AG2-262 GEN
Solar/Wind Harmer
0.974
972277AH1-723 GEN
Adder
97.135
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.065
972003AH1-546 GEN
Solar/Wind Harmer
6.584
316003AC1-222 GEN
Solar/Wind Harmer
0.004
971377AH1-170 GEN
Solar/Wind Harmer
1.539
3147623JAMES R
Solar/Wind Harmer
0.334
316006AB2-029 C
Solar/Wind Helper
0.12
LAGNLTFEXP_LAGN->PJM
CLTF
7.83
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.913
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.507
MECLTFEXP_MEC->PJM
CLTF
3.537
SIGELTFEXP_SIGE->PJM
CLTF
0.108
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.391
TVALTFEXP_TVA->PJM
CLTF
3.97
NYPJM->LTFIMP_NY
CLTF
3.157
LGEELTFEXP_LGEE->PJM
CLTF
1.303
WECLTFEXP_WEC->PJM
CLTF
0.629
CPLELTFEXP_CPLE->PJM
CLTF
11.118
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.426

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.67 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4208.1
MW Contribution:6.36
Bus #Bus NameTypeMW Contribution
970497AG2-320 GEN
50/50
20.809
3150401LDYSMT4
50/50
28.767
3150371LDYSMT1
50/50
27.797
315051AA1-145 CT1
50/50
1.582
971645AH1-323 GEN
50/50
17.655
3142416OLDCHRC
Solar/Wind Harmer
1.87
970293AG2-193 GEN
Solar/Wind Harmer
2.014
3143096IRON208
Adder
0.779
3143096IRON208
Adder
0.764
316473AC1-191 GEN
Solar/Wind Harmer
0.628
3142946ENON
Solar/Wind Harmer
0.062
3150861SPRUNCD
Adder
0.847
970133AG2-095 GEN
Solar/Wind Harmer
1.744
316382AG1-145 C
Solar/Wind Harmer
0.001
970129AG2-093 GEN
Solar/Wind Harmer
10.911
315778AD1-151 GEN
Solar/Wind Harmer
14.378
965281AG1-393 GEN
Solar/Wind Harmer
1.909
315839AE2-212 C
Solar/Wind Harmer
0.001
3150921YORKTN3
Adder
4.486
3144216WINCHST
Adder
0.673
961611AG1-000B GEN
Solar/Wind Harmer
4.749
3142433PROV 92
Adder
0.346
3142433PROV 92
Adder
0.346
3151221GRAVEL6
Adder
12.894
3151171GRAVELC
Adder
2.481
315773AC2-141 GEN
Solar/Wind Harmer
6.451
3145336SMITFLD
Solar/Wind Harmer
0.071
315813AE1-149 C
Solar/Wind Harmer
9.37
3144536CHRHLND
Solar/Wind Harmer
0.026
970659AG2-427 GEN
Solar/Wind Harmer
1.847
3151101ELIZAR3
Adder
16.197
316083AB2-161 GEN
Solar/Wind Harmer
0.002
3144873MCLAUGH
Solar/Wind Harmer
0.004
944581AF1-123 GEN
Solar/Wind Harmer
39.252
944601AF1-125 GEN
Solar/Wind Harmer
38.647
970661AG2-428 GEN
Solar/Wind Harmer
3.678
3141766HARMONY
Solar/Wind Harmer
2.312
3141843SHACKLE
Adder
0.885
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.004
3146456SLIGO L269
Solar/Wind Harmer
0.172
971153AH1-033 GEN
Solar/Wind Harmer
1.991
316156AD2-030 GEN
Solar/Wind Harmer
0.127
3141873WAN 176
Solar/Wind Harmer
3.045
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.168
3146626S HERTFORD
Solar/Wind Harmer
0.167
3145273HOLLAND
Solar/Wind Harmer
0.125
3146376EDENTON
Solar/Wind Harmer
0.164
962971AG1-146 GEN
Solar/Wind Harmer
2.595
315614AA2-178 GEN
Solar/Wind Harmer
0.918
970009AG2-005 GEN
Solar/Wind Harmer
1.196
971157AH1-035 GEN
Solar/Wind Harmer
1.892
315737AD1-076 GEN
Solar/Wind Harmer
2.022
316404AE1-155 C
Solar/Wind Harmer
0.035
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
316313AB2-026
Solar/Wind Harmer
0.098
316258AE1-075 C
Solar/Wind Harmer
0.118
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.362
3146206CASHIE
Solar/Wind Harmer
0.155
3145893MURPHYS
Solar/Wind Harmer
0.259
3145893MURPHYS
Solar/Wind Harmer
0.155
957521AF2-046 GEN
Solar/Wind Harmer
11.485
961681AG1-008 GEN
Solar/Wind Harmer
11.485
316365GEN2_N
Solar/Wind Harmer
0.346
3146173TUNIS
Solar/Wind Harmer
0.153
3156021HOLLOMANSOL
Solar/Wind Harmer
0.696
316463AE2-346 GEN
Solar/Wind Harmer
0.131
316140AB2-099
Solar/Wind Harmer
0.055
962331AG1-082 GEN
Solar/Wind Harmer
1.628
970917AG2-570 GEN
Solar/Wind Harmer
13.535
3150351NORNECKC2
Adder
1.529
3146263WOODLND
Solar/Wind Harmer
0.151
971781AH1-399 GEN
Solar/Wind Harmer
0.197
3145963POPLR C
Solar/Wind Harmer
0.15
3142666NORTHAMPTON
Solar/Wind Harmer
0.149
313506AB2-031 GEN
Solar/Wind Harmer
0.461
316317KELFORD C
Solar/Wind Harmer
0.014
3145823KELFORD
Solar/Wind Harmer
0.149
3145796HORNRTN
Solar/Wind Harmer
0.586
3145796HORNRTN
Solar/Wind Harmer
0.146
3147043LAWRENC
Solar/Wind Harmer
0.088
3145933PARMELE
Solar/Wind Harmer
0.144
966801AG1-551 GEN
Solar/Wind Harmer
1.675
316210AC1-098 GEN
Solar/Wind Harmer
1.333
972255AH1-712 GEN
Adder
72.909
316478AD1-087 GEN
Solar/Wind Harmer
0.497
316486AD2-202 GEN
Solar/Wind Harmer
0.146
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
315724AD1-057 GEN
Solar/Wind Harmer
0.524
316327AA2-057 GEN
Solar/Wind Harmer
0.209
970909AG2-566 GEN
Solar/Wind Harmer
1.479
3146073TAR RVR
Solar/Wind Harmer
0.137
3146083TARBORO
Solar/Wind Harmer
0.137
3146233WITAKRS
Solar/Wind Harmer
0.685
3146233WITAKRS
Solar/Wind Harmer
0.093
3138543CONSLDL
Solar/Wind Harmer
0.09
316131AB2-060 GEN
Solar/Wind Harmer
0.427
964241AG1-285 GEN
Solar/Wind Harmer
9.049
315785AD2-033 C
Solar/Wind Harmer
1.102
970257AG2-171 GEN
Solar/Wind Harmer
4.334
959311AF2-222 GEN
Solar/Wind Harmer
12.033
963181AG1-167 GEN
Solar/Wind Harmer
0.54
3144293JTRSVLE
Adder
0.43
3147133PAMPLIN
Solar/Wind Harmer
0.423
971193AH1-056 GEN
Solar/Wind Harmer
8.213
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
961601AG1-000A GEN
Solar/Wind Harmer
9.544
3145543BTLEBRO
Solar/Wind Harmer
0.134
3145543BTLEBRO
Solar/Wind Harmer
0.134
971623AH1-311 GEN
Solar/Wind Harmer
0.268
3146926FARMVIL
Solar/Wind Harmer
0.08
3147666LOUISA
Solar/Wind Harmer
0.299
3146776BUCKING
Solar/Wind Harmer
0.047
3141906WESTMOR
Solar/Wind Harmer
0.052
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.333
970737AG2-469 GEN
Solar/Wind Harmer
5.097
970221AG2-151 GEN
Solar/Wind Harmer
6.355
971683AH1-343 GEN
Solar/Wind Harmer
4.317
316283AC2-100 C
Solar/Wind Harmer
0.224
227287AC2-120 GEN
Solar/Wind Helper
0.387
226910AB2-157 C
Solar/Wind Helper
0.015
3150411LDYSMT5
50/50
28.857
3150381LDYSMT2
50/50
27.617
972213AH1-691 GEN
50/50
4.672
972215AH1-692 GEN
50/50
4.672
963051AG1-154 GEN
50/50
3.594
972189AH1-679 GEN
50/50
3.546
316312AB1-027
Solar/Wind Harmer
0.345
315976AC1-164 GENA
Solar/Wind Harmer
19.303
316169AC1-164_GENC
Solar/Wind Harmer
16.676
315975AC1-164 GENB
Solar/Wind Harmer
0.571
971285AH1-108 GEN
Adder
1.386
316233AE1-074 FULL
Solar/Wind Harmer
0.145
971281AH1-106 GEN
Solar/Wind Harmer
2.508
971283AH1-107 GEN
Solar/Wind Harmer
2.508
316132AB2-190 GEN1
Solar/Wind Harmer
0.968
316369SG1_INVT
Solar/Wind Harmer
0.007
971167AH1-042 GEN
Solar/Wind Harmer
15.837
3142433PROV 92
Adder
0.346
3142433PROV 92
Adder
0.346
972265AH1-717 GEN
Adder
13.77
3151201GRAVEL4
Adder
12.909
3151191GRAVEL3
Adder
12.745
3151211GRAVEL5
Adder
12.745
971445AH1-216 GEN
Solar/Wind Harmer
12.417
3143873LANEXA
Solar/Wind Harmer
0.105
3138283WHITEMARSH
Solar/Wind Harmer
0.041
3143316POE
Solar/Wind Harmer
0.692
316314AB2-024 C
Solar/Wind Harmer
0.001
3151081ELIZAR1
Adder
15.992
3151091ELIZAR2
Adder
15.714
3152611GOSPORTB
Adder
2.221
3152621GOSPORTC
Adder
1.885
3152601GOSPORTA
Adder
1.739
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
5.131
957871AF2-081 GEN
Solar/Wind Harmer
8.594
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.118
316311AC2-079 GEN
Solar/Wind Harmer
4.949
315662AE1-191 GEN
Solar/Wind Harmer
0.006
315666AE1-190 GEN
Solar/Wind Harmer
0.001
319010AE1-072 C
Solar/Wind Harmer
0.867
3146406KITTY HAWK
Solar/Wind Harmer
0.021
316305AF2-043 C
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.034
315835AF2-110_GEN
Solar/Wind Harmer
1.175
313526AB2-022
Solar/Wind Harmer
0.092
3146486SUNBURY
Solar/Wind Harmer
0.17
3146486SUNBURY
Solar/Wind Harmer
0.17
316321Z2-027
Solar/Wind Harmer
0.032
3146396TANGLEW
Solar/Wind Harmer
0.468
3145176PASQUOTANK
Solar/Wind Harmer
0.105
3141913WHIT STONE
Solar/Wind Harmer
0.168
3138133OCRAN
Solar/Wind Harmer
0.05
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3141783LANCAST
Solar/Wind Harmer
0.099
3141783LANCAST
Solar/Wind Harmer
0.066
316315AB2-025 C
Solar/Wind Harmer
0.133
315814AE2-033 C
Solar/Wind Harmer
13.015
3130156CHOWAN
Solar/Wind Harmer
0.164
3130156CHOWAN
Solar/Wind Harmer
0.164
941031AE2-094 GEN
Solar/Wind Harmer
29.871
944011AF1-069 GEN
Solar/Wind Harmer
9.76
962981AG1-147 GEN
Solar/Wind Harmer
6.055
315816AE2-034 GEN
Solar/Wind Harmer
0.688
970327AG2-215 GEN
Solar/Wind Harmer
5.255
970673AG2-436 GEN
Solar/Wind Harmer
34.096
970673AG2-436 GEN
Solar/Wind Harmer
22.731
971967AH1-528 GEN
Solar/Wind Harmer
25.316
3130546PLYMOUTH
Solar/Wind Harmer
0.158
315732AD1-074 GEN1
Solar/Wind Harmer
0.903
315733AD1-074 GEN2
Solar/Wind Harmer
0.903
315735AD1-075 GEN1
Solar/Wind Harmer
0.452
965291AG1-394 GEN
Solar/Wind Harmer
0.694
3146206CASHIE
Solar/Wind Harmer
0.155
970601AG2-382 GEN
Solar/Wind Harmer
5.807
3145893MURPHYS
Solar/Wind Harmer
0.418
3145893MURPHYS
Solar/Wind Harmer
0.155
3145513AHOSKIE
Solar/Wind Harmer
0.319
3145513AHOSKIE
Solar/Wind Harmer
0.153
3145683EARLEYS
Solar/Wind Harmer
0.304
3145683EARLEYS
Solar/Wind Harmer
0.152
3145683EARLEYS
Solar/Wind Harmer
0.152
970085AG2-068 GEN
Solar/Wind Harmer
8.093
970581AG2-369 GEN
Solar/Wind Harmer
6.96
3146043SEABORD
Solar/Wind Harmer
0.151
315607AA1-063A GEN
Solar/Wind Harmer
0.308
3141813NORNECK
Solar/Wind Harmer
0.151
316087AB2-174 GEN
Solar/Wind Harmer
0.004
315652AC1-086 GEN
Solar/Wind Harmer
16.356
3137643SOCKMAN
Solar/Wind Harmer
0.592
3145796HORNRTN
Solar/Wind Harmer
0.469
3145796HORNRTN
Solar/Wind Harmer
0.059
3146033SCOT NK
Solar/Wind Harmer
0.584
972193AH1-681 GEN
Adder
3.258
970831AG2-522 GEN
Solar/Wind Harmer
6.025
316005AA1-067
Solar/Wind Harmer
0.151
3145746EVERETS
Solar/Wind Harmer
0.561
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
970181AG2-120 GEN
Solar/Wind Harmer
1.754
957861AF2-080 GEN
Solar/Wind Harmer
5.976
316420AA1-050 GEN
Solar/Wind Harmer
0.005
3145573BETHELC
Solar/Wind Harmer
0.137
3145573BETHELC
Solar/Wind Harmer
0.137
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
2.276
3144303KENBRDG
Solar/Wind Harmer
0.108
970683AG2-441 GEN
Solar/Wind Harmer
9.015
970681AG2-440 GEN
Solar/Wind Harmer
7.212
946301AF1-294 GEN
Solar/Wind Harmer
2.664
961791AG1-021 GEN
Solar/Wind Harmer
1.296
315657AE1-056 GEN
Solar/Wind Harmer
4.652
970285AG2-188 GEN
Solar/Wind Harmer
10.359
971845AH1-439 GEN
Solar/Wind Harmer
5.906
316223AC1-118
Solar/Wind Harmer
0.093
316118AC1-105 GEN
Solar/Wind Harmer
0.328
3147173SINAI
Solar/Wind Harmer
0.125
3147243WELCO
Solar/Wind Harmer
0.078
972205AH1-687 GEN
Adder
5.337
971447AH1-217 GEN
Solar/Wind Harmer
3.558
970865AG2-541 GEN
Solar/Wind Harmer
3.939
972197AH1-683 GEN
50/50
4.492
972219AH1-694 GEN
50/50
3.234
315052AA1-145 CT2
50/50
1.589
966881AG1-559 GEN
Solar/Wind Harmer
0.232
3142416OLDCHRC
Solar/Wind Harmer
0.502
3142416OLDCHRC
Solar/Wind Harmer
0.192
3143096IRON208
Adder
0.779
3142543TWELFTH
Solar/Wind Harmer
0.018
944631AF1-128 GEN
Adder
88.024
3150851SPRUNCC
Adder
0.847
316159AE1-175 C
Solar/Wind Harmer
0.157
3143526WINTERP
Solar/Wind Harmer
0.94
970129AG2-093 GEN
Solar/Wind Harmer
5.135
316458AB2-190 GEN2
Solar/Wind Harmer
0.968
971069AG2-661 GEN
Solar/Wind Harmer
3.195
315671AE2-027_GEN
Solar/Wind Harmer
11.489
971647AH1-324 GEN
Solar/Wind Harmer
7.623
971317AH1-138 GEN
Solar/Wind Harmer
1.333
3138126ROCKLANDING
Solar/Wind Harmer
0.082
961611AG1-000B GEN
Solar/Wind Harmer
9.339
3142433PROV 92
Solar/Wind Harmer
0.711
3142433PROV 92
Adder
0.346
3142433PROV 92
Adder
0.346
3151171GRAVELC
Adder
1.887
3143226MDLTHAN
Solar/Wind Harmer
0.177
316294AC1-161 GEN
Solar/Wind Harmer
3.06
3145336SMITFLD
Solar/Wind Harmer
0.705
970659AG2-427 GEN
Solar/Wind Harmer
8.444
316375AC2-012 GEN
Solar/Wind Harmer
0.004
3150981CHESPKA
Adder
2.178
316381AD1-082 GEN
Solar/Wind Harmer
0.182
944591AF1-124 GEN
Solar/Wind Harmer
39.391
970661AG2-428 GEN
Solar/Wind Harmer
17.291
3141766HARMONY
Solar/Wind Harmer
0.035
316072AD1-144
Solar/Wind Harmer
0.063
971777AH1-397 GEN
Solar/Wind Harmer
0.457
3141843SHACKLE
Adder
0.885
316388AE2-253 GEN
Solar/Wind Harmer
0.541
3146456SLIGO L269
Solar/Wind Harmer
0.172
316246AF1-032 C
Solar/Wind Harmer
0.078
316093AE2-104_GEN
Solar/Wind Harmer
2.878
939411AE1-173 GEN
Solar/Wind Harmer
72.518
940641AE2-051 GEN
Solar/Wind Harmer
13.497
3146516WINFALL
Solar/Wind Harmer
0.545
3146516WINFALL
Solar/Wind Harmer
0.168
3138133OCRAN
Solar/Wind Harmer
0.1
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.164
3145663CRESWEL
Solar/Wind Harmer
0.449
971163AH1-040 GEN
Solar/Wind Harmer
12.829
962861AG1-135 GEN
Solar/Wind Harmer
5.046
3143336POWHATN
Solar/Wind Harmer
2.778
3146206CASHIE
Solar/Wind Harmer
0.155
971547AH1-271 GEN
Solar/Wind Harmer
3.318
3145893MURPHYS
Solar/Wind Harmer
0.619
3145893MURPHYS
Solar/Wind Harmer
0.688
316023GEN1_S
Solar/Wind Harmer
0.346
3141726DUNNSVL
Solar/Wind Harmer
0.616
3146173TUNIS
Solar/Wind Harmer
0.153
970919AG2-571 GEN
Solar/Wind Harmer
5.414
3145683EARLEYS
Solar/Wind Harmer
0.152
970087AG2-069 GEN
Solar/Wind Harmer
12.139
3150351NORNECKC2
Adder
1.504
316336AC2-165 C
Solar/Wind Harmer
0.006
3146263WOODLND
Solar/Wind Harmer
0.151
960081AF2-299 GEN
Solar/Wind Harmer
1.445
3145963POPLR C
Solar/Wind Harmer
0.15
3145823KELFORD
Solar/Wind Harmer
0.149
316011AB1-132 GEN
Solar/Wind Harmer
2.703
962571AG1-106 GEN
Solar/Wind Harmer
2.116
316174AB2-169 GEN
Solar/Wind Harmer
0.004
316190AA2-174 GEN
Solar/Wind Harmer
0
971795AH1-408 GEN
Solar/Wind Harmer
9.834
957481AF2-042 GEN
Solar/Wind Harmer
39.2
3145783HORNRTN
Solar/Wind Harmer
0.147
3145796HORNRTN
Solar/Wind Harmer
0.484
3145796HORNRTN
Solar/Wind Harmer
0.146
3147043LAWRENC
Adder
1.322
315693AD1-088 GEN
Solar/Wind Harmer
6.952
962491AG1-098 GEN
Solar/Wind Harmer
8.247
3146293MARTNCO
Solar/Wind Harmer
0.133
316212AC1-099_GEN
Solar/Wind Harmer
0.743
972277AH1-723 GEN
Adder
84.961
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
316337AD2-073 GEN
Solar/Wind Harmer
0.122
316129AC1-054 GEN
Solar/Wind Harmer
0.528
971065AG2-659 GEN
Solar/Wind Harmer
5.969
315722AD1-056 GEN
Solar/Wind Harmer
0.885
316494AC1-189 GEN
Solar/Wind Harmer
0.468
970937AG2-583 GEN
Solar/Wind Harmer
8.39
961671AG1-007 GEN
Solar/Wind Harmer
0.021
3146083TARBORO
Solar/Wind Harmer
0.137
3145493TOT1
Solar/Wind Harmer
0.607
3146233WITAKRS
Solar/Wind Harmer
0.543
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.004
970685AG2-442 GEN
Solar/Wind Harmer
10.097
963171AG1-166 GEN
Solar/Wind Harmer
0.72
971563AH1-280 GEN
Solar/Wind Harmer
1.44
3144293JTRSVLE
Adder
0.43
3145543BTLEBRO
Solar/Wind Harmer
0.134
3145543BTLEBRO
Solar/Wind Harmer
0.107
316359AB2-059 GEN
Solar/Wind Harmer
0.482
316049AB1-081 GEN
Solar/Wind Harmer
0.768
3142053HEARTS
Solar/Wind Harmer
0.236
3146926FARMVIL
Solar/Wind Harmer
0.08
3147666LOUISA
Solar/Wind Harmer
0.52
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.052
970401AG2-262 GEN
Solar/Wind Harmer
0.76
316192AB2-158 GEN
Solar/Wind Harmer
0.724
972003AH1-546 GEN
Solar/Wind Harmer
5.346
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971377AH1-170 GEN
Solar/Wind Harmer
1.271
3147623JAMES R
Solar/Wind Harmer
0.276
972135AH1-637 GEN
Solar/Wind Harmer
0.962
3150391LDYSMT3
50/50
28.713
972195AH1-682 GEN
50/50
3.773
3142296MT RD221
50/50
0.663
3142366NRTHEST
50/50
0.658
315673AE1-157 GEN
Solar/Wind Harmer
13.925
957411AF2-035 GEN
Solar/Wind Harmer
8.572
970317AG2-208 GEN
Solar/Wind Harmer
7.941
3150691DARBY 3
Adder
13.639
3150701DARBY 4
Adder
13.607
3150681DARBY 2
Adder
13.591
3150671DARBY 1
Adder
13.575
316075AC2-137 C
Solar/Wind Harmer
0.052
966871AG1-558 GEN
Solar/Wind Harmer
0.215
3142946ENON
Solar/Wind Harmer
0.018
944641AF1-129 GEN
Adder
86.641
316240AF1-291 C
Solar/Wind Harmer
0.001
3143526WINTERP
Solar/Wind Harmer
0.94
316033AB2-134 GEN
Solar/Wind Harmer
0.011
315697AD1-025 GEN
Solar/Wind Harmer
0.202
971223AH1-071 GEN
Solar/Wind Harmer
1.89
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.032
3150991CHESPKB
Adder
1.827
3150991CHESPKB
Adder
1.783
970657AG2-426 GEN
Solar/Wind Harmer
6.101
970657AG2-426 GEN
Solar/Wind Harmer
1.279
316316AC1-027 C
Solar/Wind Harmer
0.167
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.005
3145506HICKORY
Solar/Wind Harmer
0.693
3145506HICKORY
Solar/Wind Harmer
0.416
3145506HICKORY
Solar/Wind Harmer
0.104
316339AD2-160 GEN
Solar/Wind Harmer
0.28
316018AA1-139 ULT2
Solar/Wind Harmer
0.004
316017AA1-139 ULT1
Solar/Wind Harmer
0.096
3137176SLIGO L2192
Solar/Wind Harmer
0.686
3146456SLIGO L269
Solar/Wind Harmer
3.048
3130086AYDLETT
Solar/Wind Harmer
0.688
3146386ELIZ CT
Solar/Wind Harmer
0.17
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.168
3146516WINFALL
Solar/Wind Harmer
0.168
3146516WINFALL
Solar/Wind Harmer
0.168
3146626S HERTFORD
Solar/Wind Harmer
0.167
3146626S HERTFORD
Solar/Wind Harmer
0.167
3144356SAPONY
Solar/Wind Harmer
1.381
315742AE1-103 GEN
Solar/Wind Harmer
0.002
3146376EDENTON
Solar/Wind Harmer
0.728
3146376EDENTON
Solar/Wind Harmer
0.728
972185AH1-677 GEN
Adder
8.902
972187AH1-678 GEN
Adder
4.473
958261AF2-120 GEN
Solar/Wind Harmer
5.185
316065AD1-022 GEN
Solar/Wind Harmer
7.188
970933AG2-581 GEN
Solar/Wind Harmer
12.41
3145893MURPHYS
Solar/Wind Harmer
1.035
3145893MURPHYS
Solar/Wind Harmer
0.278
3146173TUNIS
Solar/Wind Harmer
0.153
3146173TUNIS
Solar/Wind Harmer
0.153
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.579
3150341NORNECKC1
Adder
1.567
316468AD1-105 GEN
Solar/Wind Harmer
-0.049
3142666NORTHAMPTON
Solar/Wind Harmer
0.149
3142666NORTHAMPTON
Solar/Wind Harmer
0.149
3142666NORTHAMPTON
Solar/Wind Harmer
0.149
3142666NORTHAMPTON
Solar/Wind Harmer
0.09
316181AB2-040 GEN
Solar/Wind Harmer
0.216
316426AA2-053 GEN
Solar/Wind Harmer
0.501
3145593CAROLNA
Solar/Wind Harmer
0.147
3145593CAROLNA
Solar/Wind Harmer
0.147
966811AG1-552 GEN
Solar/Wind Harmer
1.6
3145593CAROLNA
Solar/Wind Harmer
0.184
970099AG2-077 GEN
Solar/Wind Harmer
15.68
3145783HORNRTN
Solar/Wind Harmer
2.61
3145783HORNRTN
Solar/Wind Harmer
2.088
3145783HORNRTN
Solar/Wind Harmer
0.652
3145783HORNRTN
Solar/Wind Harmer
0.261
3145796HORNRTN
Solar/Wind Harmer
0.44
3145933PARMELE
Solar/Wind Harmer
0.288
3145933PARMELE
Solar/Wind Harmer
0.144
316274AC1-208 GEN
Solar/Wind Harmer
0.74
971741AH1-377 GEN
Solar/Wind Harmer
13.893
970301AG2-198 GEN
Solar/Wind Harmer
5.915
3145493TOT1
Solar/Wind Harmer
0.317
3145453TOT5
Solar/Wind Harmer
0.19
3145603CNETO
Solar/Wind Harmer
0.127
939181AE1-148 GEN
Solar/Wind Harmer
6.556
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.01
970323AG2-213 GEN
Solar/Wind Harmer
5.778
971775AH1-396 GEN
Solar/Wind Harmer
0.217
958211AF2-115 GEN
Solar/Wind Harmer
1.62
963191AG1-168 GEN
Solar/Wind Harmer
0.54
3144293JTRSVLE
Adder
0.43
3144293JTRSVLE
Adder
0.362
3147133PAMPLIN
Solar/Wind Harmer
0.135
3147133PAMPLIN
Solar/Wind Harmer
0.108
961601AG1-000A GEN
Solar/Wind Harmer
2.386
316263AC1-034 GEN
Solar/Wind Harmer
5.098
962561AG1-105 GEN
Solar/Wind Harmer
6.266
3146776BUCKING
Solar/Wind Harmer
0.519
3146776BUCKING
Solar/Wind Harmer
0.042
964791AG1-342 GEN
Solar/Wind Harmer
2.488
3146843MT LREL
Solar/Wind Harmer
0.129
3146843MT LREL
Solar/Wind Harmer
0.129
971489AH1-241 GEN
Solar/Wind Harmer
6.355
316222AC1-221 GEN
Solar/Wind Harmer
0.477
226929AD2-058 GEN
Solar/Wind Helper
0.118
LAGNLTFEXP_LAGN->PJM
CLTF
7.584
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.903
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.41
MECLTFEXP_MEC->PJM
CLTF
4.166
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.244
TVALTFEXP_TVA->PJM
CLTF
3.839
SIGELTFEXP_SIGE->PJM
CLTF
0.129
NYPJM->LTFIMP_NY
CLTF
2.846
LGEELTFEXP_LGEE->PJM
CLTF
1.614
WECLTFEXP_WEC->PJM
CLTF
0.82
CPLELTFEXP_CPLE->PJM
CLTF
8.902
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.096

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.56 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4204.63
MW Contribution:6.39
Bus #Bus NameTypeMW Contribution
3150391LDYSMT3
50/50
28.468
972195AH1-682 GEN
50/50
3.741
315673AE1-157 GEN
Solar/Wind Harmer
13.816
957411AF2-035 GEN
Solar/Wind Harmer
8.508
970317AG2-208 GEN
Solar/Wind Harmer
7.883
3142296MT RD221
Adder
0.622
3142366NRTHEST
Adder
0.618
3150691DARBY 3
Adder
13.575
3150701DARBY 4
Adder
13.543
3150681DARBY 2
Adder
13.528
3150671DARBY 1
Adder
13.512
316075AC2-137 C
Solar/Wind Harmer
0.051
966871AG1-558 GEN
Solar/Wind Harmer
0.214
3142946ENON
Solar/Wind Harmer
0.018
944641AF1-129 GEN
Adder
86.296
3143526WINTERP
Solar/Wind Harmer
0.937
316240AF1-291 C
Solar/Wind Harmer
0.001
316033AB2-134 GEN
Solar/Wind Harmer
0.01
315697AD1-025 GEN
Solar/Wind Harmer
0.201
971223AH1-071 GEN
Solar/Wind Harmer
1.886
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.032
3150991CHESPKB
Adder
1.821
3150991CHESPKB
Adder
1.777
970657AG2-426 GEN
Solar/Wind Harmer
6.079
970657AG2-426 GEN
Solar/Wind Harmer
1.274
316316AC1-027 C
Solar/Wind Harmer
0.166
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.005
3145506HICKORY
Solar/Wind Harmer
0.691
3145506HICKORY
Solar/Wind Harmer
0.414
3145506HICKORY
Solar/Wind Harmer
0.104
316339AD2-160 GEN
Solar/Wind Harmer
0.279
316018AA1-139 ULT2
Solar/Wind Harmer
0.004
316017AA1-139 ULT1
Solar/Wind Harmer
0.096
3137176SLIGO L2192
Solar/Wind Harmer
0.683
3146456SLIGO L269
Solar/Wind Harmer
3.038
3130086AYDLETT
Solar/Wind Harmer
0.686
3146386ELIZ CT
Solar/Wind Harmer
0.17
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.168
3146516WINFALL
Solar/Wind Harmer
0.168
3146516WINFALL
Solar/Wind Harmer
0.168
3146626S HERTFORD
Solar/Wind Harmer
0.167
3146626S HERTFORD
Solar/Wind Harmer
0.167
3144356SAPONY
Solar/Wind Harmer
1.377
315742AE1-103 GEN
Solar/Wind Harmer
0.002
3146376EDENTON
Solar/Wind Harmer
0.726
3146376EDENTON
Solar/Wind Harmer
0.726
972185AH1-677 GEN
Adder
8.883
972187AH1-678 GEN
Adder
4.463
958261AF2-120 GEN
Solar/Wind Harmer
5.156
316065AD1-022 GEN
Solar/Wind Harmer
7.167
970933AG2-581 GEN
Solar/Wind Harmer
12.385
3145893MURPHYS
Solar/Wind Harmer
1.032
3145893MURPHYS
Solar/Wind Harmer
0.278
3146173TUNIS
Solar/Wind Harmer
0.153
3146173TUNIS
Solar/Wind Harmer
0.153
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.57
3150341NORNECKC1
Adder
1.558
316468AD1-105 GEN
Solar/Wind Harmer
-0.049
3142666NORTHAMPTON
Solar/Wind Harmer
0.149
3142666NORTHAMPTON
Solar/Wind Harmer
0.149
3142666NORTHAMPTON
Solar/Wind Harmer
0.149
3142666NORTHAMPTON
Solar/Wind Harmer
0.089
316181AB2-040 GEN
Solar/Wind Harmer
0.216
316426AA2-053 GEN
Solar/Wind Harmer
0.5
971531AH1-263 GEN
50/50
38.605
3150411LDYSMT5
50/50
28.611
3150381LDYSMT2
50/50
27.382
972197AH1-683 GEN
50/50
4.454
972219AH1-694 GEN
50/50
3.207
315052AA1-145 CT2
50/50
1.579
966881AG1-559 GEN
Solar/Wind Harmer
0.23
3142416OLDCHRC
Solar/Wind Harmer
0.499
3142416OLDCHRC
Solar/Wind Harmer
0.191
3143096IRON208
Adder
0.776
3142543TWELFTH
Solar/Wind Harmer
0.018
944631AF1-128 GEN
Adder
87.636
3150851SPRUNCC
Adder
0.844
316159AE1-175 C
Solar/Wind Harmer
0.156
3143526WINTERP
Solar/Wind Harmer
0.937
970497AG2-320 GEN
50/50
20.637
3150401LDYSMT4
50/50
28.522
3150371LDYSMT1
50/50
27.56
315051AA1-145 CT1
50/50
1.572
3142416OLDCHRC
Solar/Wind Harmer
1.861
970293AG2-193 GEN
Solar/Wind Harmer
2.005
3143096IRON208
Adder
0.776
3143096IRON208
Adder
0.76
316473AC1-191 GEN
Solar/Wind Harmer
0.625
3142946ENON
Solar/Wind Harmer
0.062
3150861SPRUNCD
Adder
0.844
970133AG2-095 GEN
Solar/Wind Harmer
1.736
316382AG1-145 C
Solar/Wind Harmer
0.001
970129AG2-093 GEN
Solar/Wind Harmer
10.867
315778AD1-151 GEN
Solar/Wind Harmer
14.321
965281AG1-393 GEN
Solar/Wind Harmer
1.902
315839AE2-212 C
Solar/Wind Harmer
0.001
3150921YORKTN3
Adder
4.467
3144216WINCHST
Adder
0.67
961611AG1-000B GEN
Solar/Wind Harmer
4.73
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
3151221GRAVEL6
Adder
12.845
3151171GRAVELC
Adder
2.471
315773AC2-141 GEN
Solar/Wind Harmer
6.428
3145336SMITFLD
Solar/Wind Harmer
0.07
315813AE1-149 C
Solar/Wind Harmer
9.336
3144536CHRHLND
Solar/Wind Harmer
0.026
970659AG2-427 GEN
Solar/Wind Harmer
1.84
3151101ELIZAR3
Adder
16.14
316083AB2-161 GEN
Solar/Wind Harmer
0.002
3144873MCLAUGH
Solar/Wind Harmer
0.004
944581AF1-123 GEN
Solar/Wind Harmer
39.115
944601AF1-125 GEN
Solar/Wind Harmer
38.512
970661AG2-428 GEN
Solar/Wind Harmer
3.665
3141766HARMONY
Solar/Wind Harmer
2.301
3141843SHACKLE
Adder
0.88
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
0.172
971153AH1-033 GEN
Solar/Wind Harmer
1.985
316280AD1-041 GEN
Solar/Wind Harmer
0.004
316156AD2-030 GEN
Solar/Wind Harmer
0.126
3141873WAN 176
Solar/Wind Harmer
3.03
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.168
3146626S HERTFORD
Solar/Wind Harmer
0.167
3145273HOLLAND
Solar/Wind Harmer
0.125
3146376EDENTON
Solar/Wind Harmer
0.163
962971AG1-146 GEN
Solar/Wind Harmer
2.581
315614AA2-178 GEN
Solar/Wind Harmer
0.915
970009AG2-005 GEN
Solar/Wind Harmer
1.189
971157AH1-035 GEN
Solar/Wind Harmer
1.886
315737AD1-076 GEN
Solar/Wind Harmer
2.016
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
316313AB2-026
Solar/Wind Harmer
0.099
316258AE1-075 C
Solar/Wind Harmer
0.118
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.362
316404AE1-155 C
Solar/Wind Harmer
0.035
3146206CASHIE
Solar/Wind Harmer
0.155
3145893MURPHYS
Solar/Wind Harmer
0.258
3145893MURPHYS
Solar/Wind Harmer
0.154
957521AF2-046 GEN
Solar/Wind Harmer
11.452
961681AG1-008 GEN
Solar/Wind Harmer
11.452
316365GEN2_N
Solar/Wind Harmer
0.345
3146173TUNIS
Solar/Wind Harmer
0.153
3156021HOLLOMANSOL
Solar/Wind Harmer
0.694
316463AE2-346 GEN
Solar/Wind Harmer
0.131
316140AB2-099
Solar/Wind Harmer
0.054
962331AG1-082 GEN
Solar/Wind Harmer
1.624
970917AG2-570 GEN
Solar/Wind Harmer
13.506
3146263WOODLND
Solar/Wind Harmer
0.15
3150351NORNECKC2
Adder
1.52
3145963POPLR C
Solar/Wind Harmer
0.149
971781AH1-399 GEN
Solar/Wind Harmer
0.196
3142666NORTHAMPTON
Solar/Wind Harmer
0.149
313506AB2-031 GEN
Solar/Wind Harmer
0.46
316317KELFORD C
Solar/Wind Harmer
0.014
3145823KELFORD
Solar/Wind Harmer
0.149
3145796HORNRTN
Solar/Wind Harmer
0.585
3145796HORNRTN
Solar/Wind Harmer
0.146
3147043LAWRENC
Solar/Wind Harmer
0.087
3145933PARMELE
Solar/Wind Harmer
0.143
966801AG1-551 GEN
Solar/Wind Harmer
1.67
316210AC1-098 GEN
Solar/Wind Harmer
1.33
316478AD1-087 GEN
Solar/Wind Harmer
0.496
316486AD2-202 GEN
Solar/Wind Harmer
0.146
972255AH1-712 GEN
Adder
72.658
3145746EVERETS
Solar/Wind Harmer
0.14
3145746EVERETS
Solar/Wind Harmer
0.14
315724AD1-057 GEN
Solar/Wind Harmer
0.523
970909AG2-566 GEN
Solar/Wind Harmer
1.479
316327AA2-057 GEN
Solar/Wind Harmer
0.209
3146073TAR RVR
Solar/Wind Harmer
0.136
3146083TARBORO
Solar/Wind Harmer
0.136
3146233WITAKRS
Solar/Wind Harmer
0.683
3146233WITAKRS
Solar/Wind Harmer
0.093
3138543CONSLDL
Solar/Wind Harmer
0.09
316131AB2-060 GEN
Solar/Wind Harmer
0.427
964241AG1-285 GEN
Solar/Wind Harmer
9.041
315785AD2-033 C
Solar/Wind Harmer
1.101
970257AG2-171 GEN
Solar/Wind Harmer
4.332
959311AF2-222 GEN
Solar/Wind Harmer
12.029
963181AG1-167 GEN
Solar/Wind Harmer
0.54
3144293JTRSVLE
Adder
0.43
3147133PAMPLIN
Solar/Wind Harmer
0.423
971193AH1-056 GEN
Solar/Wind Harmer
8.216
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.081
961601AG1-000A GEN
Solar/Wind Harmer
9.521
3145543BTLEBRO
Solar/Wind Harmer
0.134
3145543BTLEBRO
Solar/Wind Harmer
0.134
971623AH1-311 GEN
Solar/Wind Harmer
0.268
3147666LOUISA
Solar/Wind Harmer
0.307
3146776BUCKING
Solar/Wind Harmer
0.047
3141906WESTMOR
Solar/Wind Harmer
0.051
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.326
970221AG2-151 GEN
Solar/Wind Harmer
6.386
970737AG2-469 GEN
Solar/Wind Harmer
5.057
971683AH1-343 GEN
Solar/Wind Harmer
4.312
316283AC2-100 C
Solar/Wind Harmer
0.223
227287AC2-120 GEN
Solar/Wind Helper
0.388
226910AB2-157 C
Solar/Wind Helper
0.015
972213AH1-691 GEN
50/50
4.632
972215AH1-692 GEN
50/50
4.632
963051AG1-154 GEN
50/50
3.563
972189AH1-679 GEN
50/50
3.525
316312AB1-027
Solar/Wind Harmer
0.343
315976AC1-164 GENA
Solar/Wind Harmer
19.21
316169AC1-164_GENC
Solar/Wind Harmer
16.596
315975AC1-164 GENB
Solar/Wind Harmer
0.568
971285AH1-108 GEN
Adder
1.381
316233AE1-074 FULL
Solar/Wind Harmer
0.144
971281AH1-106 GEN
Solar/Wind Harmer
2.501
971283AH1-107 GEN
Solar/Wind Harmer
2.501
316132AB2-190 GEN1
Solar/Wind Harmer
0.964
316369SG1_INVT
Solar/Wind Harmer
0.007
971167AH1-042 GEN
Solar/Wind Harmer
15.763
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
972265AH1-717 GEN
Adder
13.718
3151201GRAVEL4
Adder
12.859
3151191GRAVEL3
Adder
12.697
3151211GRAVEL5
Adder
12.697
971445AH1-216 GEN
Solar/Wind Harmer
12.371
3143873LANEXA
Solar/Wind Harmer
0.105
3138283WHITEMARSH
Solar/Wind Harmer
0.04
3143316POE
Solar/Wind Harmer
0.69
3151081ELIZAR1
Adder
15.936
3151091ELIZAR2
Adder
15.659
316314AB2-024 C
Solar/Wind Harmer
0.001
3152611GOSPORTB
Adder
2.213
3152621GOSPORTC
Adder
1.878
3152601GOSPORTA
Adder
1.733
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
5.106
957871AF2-081 GEN
Solar/Wind Harmer
8.564
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.118
316311AC2-079 GEN
Solar/Wind Harmer
4.932
319010AE1-072 C
Solar/Wind Harmer
0.864
315662AE1-191 GEN
Solar/Wind Harmer
0.006
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3146406KITTY HAWK
Solar/Wind Harmer
0.021
316305AF2-043 C
Solar/Wind Harmer
0.001
315835AF2-110_GEN
Solar/Wind Harmer
1.17
3141873WAN 176
Solar/Wind Harmer
0.034
313526AB2-022
Solar/Wind Harmer
0.092
3146486SUNBURY
Solar/Wind Harmer
0.169
3146486SUNBURY
Solar/Wind Harmer
0.169
316321Z2-027
Solar/Wind Harmer
0.031
3146396TANGLEW
Solar/Wind Harmer
0.466
3145176PASQUOTANK
Solar/Wind Harmer
0.105
3141913WHIT STONE
Solar/Wind Harmer
0.167
3138133OCRAN
Solar/Wind Harmer
0.05
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3141783LANCAST
Solar/Wind Harmer
0.099
3141783LANCAST
Solar/Wind Harmer
0.066
316315AB2-025 C
Solar/Wind Harmer
0.133
315814AE2-033 C
Solar/Wind Harmer
12.978
3130156CHOWAN
Solar/Wind Harmer
0.163
3130156CHOWAN
Solar/Wind Harmer
0.163
941031AE2-094 GEN
Solar/Wind Harmer
29.802
944011AF1-069 GEN
Solar/Wind Harmer
9.738
962981AG1-147 GEN
Solar/Wind Harmer
6.022
315816AE2-034 GEN
Solar/Wind Harmer
0.686
970673AG2-436 GEN
Solar/Wind Harmer
34.019
970673AG2-436 GEN
Solar/Wind Harmer
22.68
970327AG2-215 GEN
Solar/Wind Harmer
5.226
971967AH1-528 GEN
Solar/Wind Harmer
25.262
3130546PLYMOUTH
Solar/Wind Harmer
0.157
315732AD1-074 GEN1
Solar/Wind Harmer
0.9
315733AD1-074 GEN2
Solar/Wind Harmer
0.9
315735AD1-075 GEN1
Solar/Wind Harmer
0.451
965291AG1-394 GEN
Solar/Wind Harmer
0.692
3146206CASHIE
Solar/Wind Harmer
0.155
970601AG2-382 GEN
Solar/Wind Harmer
5.789
3145893MURPHYS
Solar/Wind Harmer
0.416
3145893MURPHYS
Solar/Wind Harmer
0.154
3145513AHOSKIE
Solar/Wind Harmer
0.318
3145513AHOSKIE
Solar/Wind Harmer
0.152
3145683EARLEYS
Solar/Wind Harmer
0.303
3145683EARLEYS
Solar/Wind Harmer
0.151
3145683EARLEYS
Solar/Wind Harmer
0.151
970085AG2-068 GEN
Solar/Wind Harmer
8.075
970581AG2-369 GEN
Solar/Wind Harmer
6.945
3146043SEABORD
Solar/Wind Harmer
0.151
315607AA1-063A GEN
Solar/Wind Harmer
0.307
3141813NORNECK
Solar/Wind Harmer
0.15
316087AB2-174 GEN
Solar/Wind Harmer
0.004
315652AC1-086 GEN
Solar/Wind Harmer
16.312
3137643SOCKMAN
Solar/Wind Harmer
0.591
3145796HORNRTN
Solar/Wind Harmer
0.468
3145796HORNRTN
Solar/Wind Harmer
0.058
3146033SCOT NK
Solar/Wind Harmer
0.582
972193AH1-681 GEN
Adder
3.246
970831AG2-522 GEN
Solar/Wind Harmer
6.013
316005AA1-067
Solar/Wind Harmer
0.151
3145746EVERETS
Solar/Wind Harmer
0.559
3145746EVERETS
Solar/Wind Harmer
0.14
3145746EVERETS
Solar/Wind Harmer
0.14
3145746EVERETS
Solar/Wind Harmer
0.14
970181AG2-120 GEN
Solar/Wind Harmer
1.749
957861AF2-080 GEN
Solar/Wind Harmer
5.96
316420AA1-050 GEN
Solar/Wind Harmer
0.005
3145573BETHELC
Solar/Wind Harmer
0.136
3145573BETHELC
Solar/Wind Harmer
0.136
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
2.275
3144303KENBRDG
Solar/Wind Harmer
0.108
970683AG2-441 GEN
Solar/Wind Harmer
9.014
970681AG2-440 GEN
Solar/Wind Harmer
7.211
946301AF1-294 GEN
Solar/Wind Harmer
2.665
961791AG1-021 GEN
Solar/Wind Harmer
1.296
315657AE1-056 GEN
Solar/Wind Harmer
4.654
970285AG2-188 GEN
Solar/Wind Harmer
10.387
971845AH1-439 GEN
Solar/Wind Harmer
5.923
316223AC1-118
Solar/Wind Harmer
0.092
316118AC1-105 GEN
Solar/Wind Harmer
0.328
972205AH1-687 GEN
Adder
5.363
3147173SINAI
Solar/Wind Harmer
0.125
3147243WELCO
Solar/Wind Harmer
0.078
971447AH1-217 GEN
Solar/Wind Harmer
3.576
970865AG2-541 GEN
Solar/Wind Harmer
3.934
970129AG2-093 GEN
Solar/Wind Harmer
5.114
316458AB2-190 GEN2
Solar/Wind Harmer
0.964
971069AG2-661 GEN
Solar/Wind Harmer
3.182
315671AE2-027_GEN
Solar/Wind Harmer
11.444
971647AH1-324 GEN
Solar/Wind Harmer
7.594
971317AH1-138 GEN
Solar/Wind Harmer
1.327
3138126ROCKLANDING
Solar/Wind Harmer
0.082
961611AG1-000B GEN
Solar/Wind Harmer
9.303
3142433PROV 92
Solar/Wind Harmer
0.707
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
3143226MDLTHAN
Solar/Wind Harmer
0.177
3151171GRAVELC
Adder
1.879
316294AC1-161 GEN
Solar/Wind Harmer
3.05
3145336SMITFLD
Solar/Wind Harmer
0.702
970659AG2-427 GEN
Solar/Wind Harmer
8.414
316375AC2-012 GEN
Solar/Wind Harmer
0.004
3150981CHESPKA
Adder
2.17
316381AD1-082 GEN
Solar/Wind Harmer
0.181
944591AF1-124 GEN
Solar/Wind Harmer
39.254
970661AG2-428 GEN
Solar/Wind Harmer
17.23
316072AD1-144
Solar/Wind Harmer
0.063
3141766HARMONY
Solar/Wind Harmer
0.035
971777AH1-397 GEN
Solar/Wind Harmer
0.455
3141843SHACKLE
Adder
0.88
316388AE2-253 GEN
Solar/Wind Harmer
0.539
3146456SLIGO L269
Solar/Wind Harmer
0.172
316246AF1-032 C
Solar/Wind Harmer
0.077
316093AE2-104_GEN
Solar/Wind Harmer
2.869
939411AE1-173 GEN
Solar/Wind Harmer
72.314
940641AE2-051 GEN
Solar/Wind Harmer
13.462
3146516WINFALL
Solar/Wind Harmer
0.544
3146516WINFALL
Solar/Wind Harmer
0.168
3138133OCRAN
Solar/Wind Harmer
0.1
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.163
3145663CRESWEL
Solar/Wind Harmer
0.447
971163AH1-040 GEN
Solar/Wind Harmer
12.788
962861AG1-135 GEN
Solar/Wind Harmer
5.018
3143336POWHATN
Solar/Wind Harmer
2.779
3146206CASHIE
Solar/Wind Harmer
0.155
971547AH1-271 GEN
Solar/Wind Harmer
3.308
3145893MURPHYS
Solar/Wind Harmer
0.617
3145893MURPHYS
Solar/Wind Harmer
0.686
316023GEN1_S
Solar/Wind Harmer
0.345
3141726DUNNSVL
Solar/Wind Harmer
0.612
3146173TUNIS
Solar/Wind Harmer
0.153
970919AG2-571 GEN
Solar/Wind Harmer
5.402
3145683EARLEYS
Solar/Wind Harmer
0.151
970087AG2-069 GEN
Solar/Wind Harmer
12.113
316336AC2-165 C
Solar/Wind Harmer
0.006
3146263WOODLND
Solar/Wind Harmer
0.15
960081AF2-299 GEN
Solar/Wind Harmer
1.442
3150351NORNECKC2
Adder
1.495
3145963POPLR C
Solar/Wind Harmer
0.149
3145823KELFORD
Solar/Wind Harmer
0.149
316011AB1-132 GEN
Solar/Wind Harmer
2.696
962571AG1-106 GEN
Solar/Wind Harmer
2.11
316174AB2-169 GEN
Solar/Wind Harmer
0.004
316190AA2-174 GEN
Solar/Wind Harmer
0
971795AH1-408 GEN
Solar/Wind Harmer
9.812
957481AF2-042 GEN
Solar/Wind Harmer
39.137
3145783HORNRTN
Solar/Wind Harmer
0.146
3145796HORNRTN
Solar/Wind Harmer
0.482
3145796HORNRTN
Solar/Wind Harmer
0.146
3147043LAWRENC
Adder
1.319
315693AD1-088 GEN
Solar/Wind Harmer
6.943
962491AG1-098 GEN
Solar/Wind Harmer
8.237
3146293MARTNCO
Solar/Wind Harmer
0.133
316212AC1-099_GEN
Solar/Wind Harmer
0.741
972277AH1-723 GEN
Adder
84.669
3145746EVERETS
Solar/Wind Harmer
0.14
3145746EVERETS
Solar/Wind Harmer
0.14
316129AC1-054 GEN
Solar/Wind Harmer
0.527
316337AD2-073 GEN
Solar/Wind Harmer
0.122
971065AG2-659 GEN
Solar/Wind Harmer
5.957
315722AD1-056 GEN
Solar/Wind Harmer
0.882
316494AC1-189 GEN
Solar/Wind Harmer
0.467
970937AG2-583 GEN
Solar/Wind Harmer
8.414
961671AG1-007 GEN
Solar/Wind Harmer
0.021
3146083TARBORO
Solar/Wind Harmer
0.136
3145493TOT1
Solar/Wind Harmer
0.606
3146233WITAKRS
Solar/Wind Harmer
0.542
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.004
970685AG2-442 GEN
Solar/Wind Harmer
10.095
963171AG1-166 GEN
Solar/Wind Harmer
0.72
971563AH1-280 GEN
Solar/Wind Harmer
1.44
3144293JTRSVLE
Adder
0.43
3146926FARMVIL
Solar/Wind Harmer
0.081
3145543BTLEBRO
Solar/Wind Harmer
0.134
3145543BTLEBRO
Solar/Wind Harmer
0.107
316359AB2-059 GEN
Solar/Wind Harmer
0.481
316049AB1-081 GEN
Solar/Wind Harmer
0.766
3142053HEARTS
Solar/Wind Harmer
0.236
3147666LOUISA
Solar/Wind Harmer
0.534
316192AB2-158 GEN
Solar/Wind Harmer
0.744
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.052
970401AG2-262 GEN
Solar/Wind Harmer
0.759
972003AH1-546 GEN
Solar/Wind Harmer
5.371
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971377AH1-170 GEN
Solar/Wind Harmer
1.277
3147623JAMES R
Solar/Wind Harmer
0.277
3145593CAROLNA
Solar/Wind Harmer
0.147
3145593CAROLNA
Solar/Wind Harmer
0.147
966811AG1-552 GEN
Solar/Wind Harmer
1.596
3145593CAROLNA
Solar/Wind Harmer
0.183
970099AG2-077 GEN
Solar/Wind Harmer
15.655
3145783HORNRTN
Solar/Wind Harmer
2.603
3145783HORNRTN
Solar/Wind Harmer
2.082
3145783HORNRTN
Solar/Wind Harmer
0.651
3145783HORNRTN
Solar/Wind Harmer
0.26
3145796HORNRTN
Solar/Wind Harmer
0.438
3145933PARMELE
Solar/Wind Harmer
0.287
3145933PARMELE
Solar/Wind Harmer
0.143
316274AC1-208 GEN
Solar/Wind Harmer
0.738
971741AH1-377 GEN
Solar/Wind Harmer
13.893
970301AG2-198 GEN
Solar/Wind Harmer
5.917
939181AE1-148 GEN
Solar/Wind Harmer
6.546
3145493TOT1
Solar/Wind Harmer
0.316
3145453TOT5
Solar/Wind Harmer
0.189
3145603CNETO
Solar/Wind Harmer
0.126
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.01
970323AG2-213 GEN
Solar/Wind Harmer
5.776
971775AH1-396 GEN
Solar/Wind Harmer
0.217
958211AF2-115 GEN
Solar/Wind Harmer
1.621
963191AG1-168 GEN
Solar/Wind Harmer
0.54
3144293JTRSVLE
Adder
0.43
3144293JTRSVLE
Adder
0.362
3147133PAMPLIN
Solar/Wind Harmer
0.135
3147133PAMPLIN
Solar/Wind Harmer
0.108
961601AG1-000A GEN
Solar/Wind Harmer
2.38
316263AC1-034 GEN
Solar/Wind Harmer
5.085
962561AG1-105 GEN
Solar/Wind Harmer
6.258
3146776BUCKING
Solar/Wind Harmer
0.521
3146776BUCKING
Solar/Wind Harmer
0.042
964791AG1-342 GEN
Solar/Wind Harmer
2.485
3146843MT LREL
Solar/Wind Harmer
0.129
3146843MT LREL
Solar/Wind Harmer
0.129
971489AH1-241 GEN
Solar/Wind Harmer
6.386
316222AC1-221 GEN
Solar/Wind Harmer
0.476
226929AD2-058 GEN
Solar/Wind Helper
0.118
LAGNLTFEXP_LAGN->PJM
CLTF
7.576
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.893
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.398
MECLTFEXP_MEC->PJM
CLTF
4.164
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.212
TVALTFEXP_TVA->PJM
CLTF
3.836
SIGELTFEXP_SIGE->PJM
CLTF
0.129
NYPJM->LTFIMP_NY
CLTF
2.848
LGEELTFEXP_LGEE->PJM
CLTF
1.613
WECLTFEXP_WEC->PJM
CLTF
0.819
CPLELTFEXP_CPLE->PJM
CLTF
8.886
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.062

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:175.45 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5650.14
MW Contribution:9.11
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
4.373
3151101ELIZAR3
50/50
30.305
3150861SPRUNCD
50/50
1.461
3151161SURRY 1
50/50
11.304
970917AG2-570 GEN
Solar/Wind Harmer
28.408
315773AC2-141 GEN
Solar/Wind Harmer
11.382
944581AF1-123 GEN
Solar/Wind Harmer
69.733
944601AF1-125 GEN
Solar/Wind Harmer
68.658
3144873MCLAUGH
Solar/Wind Harmer
0.008
3146456SLIGO L269
Solar/Wind Harmer
0.306
971153AH1-033 GEN
Solar/Wind Harmer
3.534
3144536CHRHLND
Solar/Wind Harmer
0.046
316320Y1-086
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
6.41
316083AB2-161 GEN
Solar/Wind Harmer
0.004
970659AG2-427 GEN
Solar/Wind Harmer
3.204
315813AE1-149 C
Solar/Wind Harmer
16.153
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.3
3145336SMITFLD
Solar/Wind Harmer
0.12
3146626S HERTFORD
Solar/Wind Harmer
0.299
315839AE2-212 C
Solar/Wind Harmer
0.002
3145273HOLLAND
Solar/Wind Harmer
0.223
316313AB2-026
Solar/Wind Harmer
0.186
316258AE1-075 C
Solar/Wind Harmer
0.223
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.463
965281AG1-393 GEN
Solar/Wind Harmer
3.139
3151221GRAVEL6
Adder
21.396
3151171GRAVELC
Adder
4.116
3146376EDENTON
Solar/Wind Harmer
0.294
961611AG1-000B GEN
Solar/Wind Harmer
7.797
316365GEN2_N
Solar/Wind Harmer
0.655
315614AA2-178 GEN
Solar/Wind Harmer
1.657
315778AD1-151 GEN
Solar/Wind Harmer
23.065
3156081AA2-088 GEN
Solar/Wind Harmer
0.007
970129AG2-093 GEN
Solar/Wind Harmer
17.309
316478AD1-087 GEN
Solar/Wind Harmer
0.999
316486AD2-202 GEN
Solar/Wind Harmer
0.293
971157AH1-035 GEN
Solar/Wind Harmer
3.43
315737AD1-076 GEN
Solar/Wind Harmer
3.669
3144216WINCHST
Adder
1.072
970133AG2-095 GEN
Solar/Wind Harmer
2.723
3145893MURPHYS
Solar/Wind Harmer
0.474
3145893MURPHYS
Solar/Wind Harmer
0.283
3146206CASHIE
Solar/Wind Harmer
0.283
957521AF2-046 GEN
Solar/Wind Harmer
21.052
961681AG1-008 GEN
Solar/Wind Harmer
21.052
3150921YORKTN3
Adder
7.103
3146173TUNIS
Solar/Wind Harmer
0.281
313506AB2-031 GEN
Solar/Wind Harmer
0.867
3156021HOLLOMANSOL
Solar/Wind Harmer
1.274
316463AE2-346 GEN
Solar/Wind Harmer
0.241
316140AB2-099
Solar/Wind Harmer
0.1
962331AG1-082 GEN
Solar/Wind Harmer
2.99
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3146263WOODLND
Solar/Wind Harmer
0.278
3147043LAWRENC
Solar/Wind Harmer
0.166
316317KELFORD C
Solar/Wind Harmer
0.027
3145823KELFORD
Solar/Wind Harmer
0.275
3145796HORNRTN
Solar/Wind Harmer
1.1
3145796HORNRTN
Solar/Wind Harmer
0.275
3145963POPLR C
Solar/Wind Harmer
0.274
3143096IRON208
Adder
1.147
3143096IRON208
Adder
1.124
316382AG1-145 C
Solar/Wind Harmer
0.002
316210AC1-098 GEN
Solar/Wind Harmer
2.485
3145933PARMELE
Solar/Wind Harmer
0.265
966801AG1-551 GEN
Solar/Wind Harmer
3.091
3142946ENON
Solar/Wind Harmer
0.089
315724AD1-057 GEN
Solar/Wind Harmer
0.985
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
316327AA2-057 GEN
Solar/Wind Harmer
0.393
970909AG2-566 GEN
Solar/Wind Harmer
2.748
316131AB2-060 GEN
Solar/Wind Harmer
0.81
3146233WITAKRS
Solar/Wind Harmer
1.286
3146233WITAKRS
Solar/Wind Harmer
0.174
3138543CONSLDL
Solar/Wind Harmer
0.169
964241AG1-285 GEN
Solar/Wind Harmer
17.051
3146073TAR RVR
Solar/Wind Harmer
0.255
3146083TARBORO
Solar/Wind Harmer
0.255
970293AG2-193 GEN
Solar/Wind Harmer
2.717
3142433PROV 92
Adder
0.492
3142433PROV 92
Adder
0.492
315785AD2-033 C
Solar/Wind Harmer
2.056
961601AG1-000A GEN
Solar/Wind Harmer
17.946
3145543BTLEBRO
Solar/Wind Harmer
0.252
3145543BTLEBRO
Solar/Wind Harmer
0.252
971623AH1-311 GEN
Solar/Wind Harmer
0.505
970257AG2-171 GEN
Solar/Wind Harmer
8.061
959311AF2-222 GEN
Solar/Wind Harmer
22.323
963181AG1-167 GEN
Solar/Wind Harmer
0.987
3144293JTRSVLE
Adder
0.785
3147133PAMPLIN
Solar/Wind Harmer
0.769
971193AH1-056 GEN
Solar/Wind Harmer
14.916
3141843SHACKLE
Adder
1.244
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.005
3141766HARMONY
Solar/Wind Harmer
3.224
316156AD2-030 GEN
Solar/Wind Harmer
0.179
3141873WAN 176
Solar/Wind Harmer
4.293
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
10.242
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3142416OLDCHRC
Solar/Wind Harmer
2.323
3146926FARMVIL
Solar/Wind Harmer
0.141
971683AH1-343 GEN
Solar/Wind Harmer
8.112
962971AG1-146 GEN
Solar/Wind Harmer
3.502
316283AC2-100 C
Solar/Wind Harmer
0.428
316473AC1-191 GEN
Solar/Wind Harmer
0.734
970009AG2-005 GEN
Solar/Wind Harmer
1.596
3146776BUCKING
Solar/Wind Harmer
0.076
316404AE1-155 C
Solar/Wind Harmer
0.046
3150351NORNECKC2
Adder
1.933
970221AG2-151 GEN
Solar/Wind Harmer
9.113
971781AH1-399 GEN
Solar/Wind Harmer
0.197
3141906WESTMOR
Solar/Wind Harmer
0.057
270197AD1-017 GEN1
Solar/Wind Harmer
0.888
270018AE2-047 C O1
Solar/Wind Harmer
0.003
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.176
972255AH1-712 GEN
Adder
66.009
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
970737AG2-469 GEN
Solar/Wind Harmer
5.167
958131AF2-107 GEN
Solar/Wind Harmer
3.333
316044AC1-158 PL1
Solar/Wind Helper
2.198
316450AC1-158 RIC
Solar/Wind Helper
0.586
3147666LOUISA
Solar/Wind Helper
0.715
316170AC1-121 GEN2
Solar/Wind Helper
0.429
3141196NOKESVL
Solar/Wind Helper
1.038
3132273ORANGE
Solar/Wind Helper
0.047
227287AC2-120 GEN
Solar/Wind Helper
0.311
226910AB2-157 C
Solar/Wind Helper
0.013
970119AG2-088 GEN
50/50
49.132
315243AE2-183_GT3
50/50
5.558
3151051BRUNSWICKS1
50/50
9.077
3151021BRUNSWICKG1
50/50
4.373
971451AH1-221 GEN
50/50
13.283
3150981CHESPKA
50/50
4.07
3150851SPRUNCC
50/50
1.461
3152331SURRY 2
50/50
12.331
3143226MDLTHAN
Solar/Wind Harmer
0.368
940641AE2-051 GEN
Solar/Wind Harmer
28.054
939411AE1-173 GEN
Solar/Wind Harmer
145.057
3143526WINTERP
Solar/Wind Harmer
1.742
970919AG2-571 GEN
Solar/Wind Harmer
11.363
970087AG2-069 GEN
Solar/Wind Harmer
25.456
316294AC1-161 GEN
Solar/Wind Harmer
5.4
944591AF1-124 GEN
Solar/Wind Harmer
69.98
316375AC2-012 GEN
Solar/Wind Harmer
0.008
316388AE2-253 GEN
Solar/Wind Harmer
0.96
3146456SLIGO L269
Solar/Wind Harmer
0.306
316246AF1-032 C
Solar/Wind Harmer
0.137
316093AE2-104_GEN
Solar/Wind Harmer
5.099
970661AG2-428 GEN
Solar/Wind Harmer
30.138
316381AD1-082 GEN
Solar/Wind Harmer
0.316
970659AG2-427 GEN
Solar/Wind Harmer
14.649
316072AD1-144
Solar/Wind Harmer
0.109
3146516WINFALL
Solar/Wind Harmer
0.972
3146516WINFALL
Solar/Wind Harmer
0.3
3145336SMITFLD
Solar/Wind Harmer
1.197
957481AF2-042 GEN
Solar/Wind Harmer
79.695
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
5.25
3130156CHOWAN
Solar/Wind Harmer
0.294
3151171GRAVELC
Adder
3.13
961611AG1-000B GEN
Solar/Wind Harmer
15.335
315671AE2-027_GEN
Solar/Wind Harmer
18.679
316023GEN1_S
Solar/Wind Harmer
0.655
971647AH1-324 GEN
Solar/Wind Harmer
12.413
3145663CRESWEL
Solar/Wind Harmer
0.81
971163AH1-040 GEN
Solar/Wind Harmer
23.157
315693AD1-088 GEN
Solar/Wind Harmer
13.873
971069AG2-661 GEN
Solar/Wind Harmer
5.126
962491AG1-098 GEN
Solar/Wind Harmer
16.401
316458AB2-190 GEN2
Solar/Wind Harmer
1.538
970129AG2-093 GEN
Solar/Wind Harmer
8.145
960081AF2-299 GEN
Solar/Wind Harmer
2.73
3138126ROCKLANDING
Solar/Wind Harmer
0.13
3145893MURPHYS
Solar/Wind Harmer
1.134
3145893MURPHYS
Solar/Wind Harmer
1.26
3146206CASHIE
Solar/Wind Harmer
0.283
971547AH1-271 GEN
Solar/Wind Harmer
6.043
3146173TUNIS
Solar/Wind Harmer
0.281
3142543TWELFTH
Solar/Wind Harmer
0.027
3145683EARLEYS
Solar/Wind Harmer
0.279
316011AB1-132 GEN
Solar/Wind Harmer
5.071
962571AG1-106 GEN
Solar/Wind Harmer
3.968
971795AH1-408 GEN
Solar/Wind Harmer
18.591
3146263WOODLND
Solar/Wind Harmer
0.278
316190AA2-174 GEN
Solar/Wind Harmer
0
3147043LAWRENC
Adder
2.5
316336AC2-165 C
Solar/Wind Harmer
0.011
971317AH1-138 GEN
Solar/Wind Harmer
2.057
3145823KELFORD
Solar/Wind Harmer
0.275
3145796HORNRTN
Solar/Wind Harmer
0.907
3145796HORNRTN
Solar/Wind Harmer
0.275
3145783HORNRTN
Solar/Wind Harmer
0.275
3145963POPLR C
Solar/Wind Harmer
0.274
3143096IRON208
Adder
1.147
316174AB2-169 GEN
Solar/Wind Harmer
0.007
316159AE1-175 C
Solar/Wind Harmer
0.235
944631AF1-128 GEN
Adder
128.871
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316212AC1-099_GEN
Solar/Wind Harmer
1.386
316129AC1-054 GEN
Solar/Wind Harmer
1.006
971065AG2-659 GEN
Solar/Wind Harmer
11.378
3146293MARTNCO
Solar/Wind Harmer
0.246
315722AD1-056 GEN
Solar/Wind Harmer
1.662
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
316494AC1-189 GEN
Solar/Wind Harmer
0.872
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3146233WITAKRS
Solar/Wind Harmer
1.019
961671AG1-007 GEN
Solar/Wind Harmer
0.039
3146083TARBORO
Solar/Wind Harmer
0.255
3145493TOT1
Solar/Wind Harmer
1.136
3142433PROV 92
Solar/Wind Harmer
1.012
3142433PROV 92
Adder
0.492
3142433PROV 92
Adder
0.492
316359AB2-059 GEN
Solar/Wind Harmer
0.906
316049AB1-081 GEN
Solar/Wind Harmer
1.444
3145543BTLEBRO
Solar/Wind Harmer
0.252
3145543BTLEBRO
Solar/Wind Harmer
0.202
3142053HEARTS
Solar/Wind Harmer
0.444
970685AG2-442 GEN
Solar/Wind Harmer
18.609
970401AG2-262 GEN
Solar/Wind Harmer
1.452
963171AG1-166 GEN
Solar/Wind Harmer
1.316
971563AH1-280 GEN
Solar/Wind Harmer
2.632
3144293JTRSVLE
Adder
0.785
971777AH1-397 GEN
Solar/Wind Harmer
0.643
3141843SHACKLE
Adder
1.244
3141766HARMONY
Solar/Wind Harmer
0.048
3142416OLDCHRC
Solar/Wind Harmer
0.623
3142416OLDCHRC
Solar/Wind Harmer
0.239
3146926FARMVIL
Solar/Wind Harmer
0.141
3138133OCRAN
Solar/Wind Harmer
0.139
316003AC1-222 GEN
Solar/Wind Harmer
0.006
970937AG2-583 GEN
Solar/Wind Harmer
13.92
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.085
962861AG1-135 GEN
Solar/Wind Harmer
6.647
3141726DUNNSVL
Solar/Wind Harmer
0.786
3150351NORNECKC2
Adder
1.901
972003AH1-546 GEN
Solar/Wind Harmer
8.083
970533AG2-339 GEN
50/50
30.786
970531AG2-338 GEN
50/50
12.314
315242AE2-183_GT2
50/50
5.558
315241AE2-183_GT1
50/50
5.524
972185AH1-677 GEN
50/50
20.036
3151041BRUNSWICKG3
50/50
4.373
972187AH1-678 GEN
50/50
10.036
3150991CHESPKB
50/50
3.415
3150991CHESPKB
50/50
3.333
971223AH1-071 GEN
Solar/Wind Harmer
3.931
3143526WINTERP
Solar/Wind Harmer
1.742
970933AG2-581 GEN
Solar/Wind Harmer
25.944
3144356SAPONY
Solar/Wind Harmer
2.645
316185AD1-033 GEN
Solar/Wind Harmer
0.009
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.295
3145506HICKORY
Solar/Wind Harmer
1.229
3145506HICKORY
Solar/Wind Harmer
0.737
3145506HICKORY
Solar/Wind Harmer
0.184
316036AC1-147 C
Solar/Wind Harmer
0.057
316339AD2-160 GEN
Solar/Wind Harmer
0.497
316018AA1-139 ULT2
Solar/Wind Harmer
0.008
316017AA1-139 ULT1
Solar/Wind Harmer
0.171
3137176SLIGO L2192
Solar/Wind Harmer
1.217
3146456SLIGO L269
Solar/Wind Harmer
5.409
3130086AYDLETT
Solar/Wind Harmer
1.221
3146386ELIZ CT
Solar/Wind Harmer
0.303
970657AG2-426 GEN
Solar/Wind Harmer
10.611
970657AG2-426 GEN
Solar/Wind Harmer
2.224
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.3
3146516WINFALL
Solar/Wind Harmer
0.3
3146516WINFALL
Solar/Wind Harmer
0.3
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3146626S HERTFORD
Solar/Wind Harmer
0.299
3146626S HERTFORD
Solar/Wind Harmer
0.299
970099AG2-077 GEN
Solar/Wind Harmer
31.878
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
1.308
3146376EDENTON
Solar/Wind Harmer
1.308
316240AF1-291 C
Solar/Wind Harmer
0.002
316033AB2-134 GEN
Solar/Wind Harmer
0.017
315697AD1-025 GEN
Solar/Wind Harmer
0.325
944641AF1-129 GEN
Adder
137.21
316065AD1-022 GEN
Solar/Wind Harmer
13.074
3145893MURPHYS
Solar/Wind Harmer
1.897
3145893MURPHYS
Solar/Wind Harmer
0.51
3146173TUNIS
Solar/Wind Harmer
0.281
3146173TUNIS
Solar/Wind Harmer
0.281
316181AB2-040 GEN
Solar/Wind Harmer
0.407
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3142666NORTHAMPTON
Solar/Wind Harmer
0.167
316426AA2-053 GEN
Solar/Wind Harmer
0.935
3145593CAROLNA
Solar/Wind Harmer
0.276
3145593CAROLNA
Solar/Wind Harmer
0.276
966811AG1-552 GEN
Solar/Wind Harmer
2.997
3145593CAROLNA
Solar/Wind Harmer
0.344
3145796HORNRTN
Solar/Wind Harmer
0.825
3145783HORNRTN
Solar/Wind Harmer
4.886
3145783HORNRTN
Solar/Wind Harmer
3.909
3145783HORNRTN
Solar/Wind Harmer
1.222
3145783HORNRTN
Solar/Wind Harmer
0.489
316274AC1-208 GEN
Solar/Wind Harmer
1.384
3145933PARMELE
Solar/Wind Harmer
0.531
3145933PARMELE
Solar/Wind Harmer
0.265
3142946ENON
Solar/Wind Harmer
0.026
971741AH1-377 GEN
Solar/Wind Harmer
26.27
939181AE1-148 GEN
Solar/Wind Harmer
12.567
3142366NRTHEST
Adder
0.844
313527AB2-043 GEN
Solar/Wind Harmer
0.003
970301AG2-198 GEN
Solar/Wind Harmer
10.992
3150691DARBY 3
Adder
18.496
3150701DARBY 4
Adder
18.453
3150681DARBY 2
Adder
18.432
3150671DARBY 1
Adder
18.41
3145493TOT1
Solar/Wind Harmer
0.592
3145453TOT5
Solar/Wind Harmer
0.355
3145603CNETO
Solar/Wind Harmer
0.237
961601AG1-000A GEN
Solar/Wind Harmer
4.486
316263AC1-034 GEN
Solar/Wind Harmer
9.586
316075AC2-137 C
Solar/Wind Harmer
0.069
970323AG2-213 GEN
Solar/Wind Harmer
10.747
971775AH1-396 GEN
Solar/Wind Harmer
0.403
316034AC1-036 C
Solar/Wind Harmer
0.018
962561AG1-105 GEN
Solar/Wind Harmer
11.957
964791AG1-342 GEN
Solar/Wind Harmer
4.752
3146843MT LREL
Solar/Wind Harmer
0.247
3146843MT LREL
Solar/Wind Harmer
0.247
958211AF2-115 GEN
Solar/Wind Harmer
2.961
963191AG1-168 GEN
Solar/Wind Harmer
0.987
3144293JTRSVLE
Adder
0.785
3144293JTRSVLE
Adder
0.661
3147133PAMPLIN
Solar/Wind Harmer
0.245
3147133PAMPLIN
Solar/Wind Harmer
0.196
3142296MT RD221
Adder
0.748
316222AC1-221 GEN
Solar/Wind Harmer
0.912
966871AG1-558 GEN
Solar/Wind Harmer
0.251
3146776BUCKING
Solar/Wind Harmer
0.848
3146776BUCKING
Solar/Wind Harmer
0.069
958261AF2-120 GEN
Solar/Wind Harmer
6.796
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.997
3150341NORNECKC1
Adder
1.981
942751AE2-291 GEN
Solar/Wind Harmer
9.768
971489AH1-241 GEN
Solar/Wind Harmer
9.113
316468AD1-105 GEN
Solar/Wind Harmer
-0.049
270013AE1-250 PV
Solar/Wind Harmer
0.004
315821AE2-092 GEN
Solar/Wind Harmer
0.008
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.248
316447AC1-158 HLD
Solar/Wind Helper
4.837
315651AD1-115 GEN
Solar/Wind Helper
0.937
226929AD2-058 GEN
Solar/Wind Helper
0.091
971377AH1-170 GEN
Solar/Wind Harmer
1.823
3147623JAMES R
Solar/Wind Harmer
0.396
316337AD2-073 GEN
Solar/Wind Harmer
0.146
970223AG2-152 GEN
Solar/Wind Harmer
10.672
270016AE1-250 BESS
Solar/Wind Harmer
0.004
3147123OTTER R
Solar/Wind Harmer
0.084
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.104
3146802CHATHAM
Solar/Wind Harmer
0.098
941801AE2-185 GEN
Solar/Wind Harmer
4.176
972277AH1-723 GEN
Adder
76.921
270030AE2-140 GEN
Solar/Wind Harmer
12.711
316045AC1-158 PL2
Solar/Wind Helper
7.036
3147666LOUISA
Solar/Wind Helper
1.244
316192AB2-158 GEN
Solar/Wind Helper
2.045
316254AC1-120 GEN1
Solar/Wind Helper
1.287
316006AB2-029 C
Solar/Wind Helper
0.13
316303AF2-085
50/50
6.551
315244AE2-183_ST
50/50
9.609
963041AG1-153 GEN
50/50
8.856
315779AE2-040
50/50
4.414
3151081ELIZAR1
50/50
29.922
3151091ELIZAR2
50/50
29.403
941591AE2-156 GEN
50/50
27.332
3152611GOSPORTB
50/50
4.152
3152621GOSPORTC
50/50
3.523
3152601GOSPORTA
50/50
3.25
971285AH1-108 GEN
50/50
2.391
972263AH1-716 GEN
50/50
170.662
941031AE2-094 GEN
Solar/Wind Harmer
63.788
944011AF1-069 GEN
Solar/Wind Harmer
20.842
970673AG2-436 GEN
Solar/Wind Harmer
72.487
970673AG2-436 GEN
Solar/Wind Harmer
48.325
316233AE1-074 FULL
Solar/Wind Harmer
0.268
971281AH1-106 GEN
Solar/Wind Harmer
4.649
971283AH1-107 GEN
Solar/Wind Harmer
4.649
971967AH1-528 GEN
Solar/Wind Harmer
53.477
970085AG2-068 GEN
Solar/Wind Harmer
16.971
970581AG2-369 GEN
Solar/Wind Harmer
14.595
316315AB2-025 C
Solar/Wind Harmer
0.256
315814AE2-033 C
Solar/Wind Harmer
24.917
3143316POE
Solar/Wind Harmer
1.232
957871AF2-081 GEN
Solar/Wind Harmer
15.244
319010AE1-072 C
Solar/Wind Harmer
1.539
3146406KITTY HAWK
Solar/Wind Harmer
0.038
316305AF2-043 C
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.164
315835AF2-110_GEN
Solar/Wind Harmer
2.081
315833AF1-017_GEN
Solar/Wind Harmer
0.002
316349AD2-085 GEN
Solar/Wind Harmer
0.208
316311AC2-079 GEN
Solar/Wind Harmer
8.702
3146486SUNBURY
Solar/Wind Harmer
0.302
3146486SUNBURY
Solar/Wind Harmer
0.302
316321Z2-027
Solar/Wind Harmer
0.056
3146396TANGLEW
Solar/Wind Harmer
0.833
3145176PASQUOTANK
Solar/Wind Harmer
0.187
971445AH1-216 GEN
Solar/Wind Harmer
21.042
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.294
3130156CHOWAN
Solar/Wind Harmer
0.294
972265AH1-717 GEN
Adder
22.85
3151201GRAVEL4
Adder
21.42
3151191GRAVEL3
Adder
21.149
3151211GRAVEL5
Adder
21.149
316369SG1_INVT
Solar/Wind Harmer
0.011
315816AE2-034 GEN
Solar/Wind Harmer
1.242
316132AB2-190 GEN1
Solar/Wind Harmer
1.538
3130546PLYMOUTH
Solar/Wind Harmer
0.286
965291AG1-394 GEN
Solar/Wind Harmer
1.269
315732AD1-074 GEN1
Solar/Wind Harmer
1.639
315733AD1-074 GEN2
Solar/Wind Harmer
1.639
315735AD1-075 GEN1
Solar/Wind Harmer
0.82
3145893MURPHYS
Solar/Wind Harmer
0.765
3145893MURPHYS
Solar/Wind Harmer
0.283
3146206CASHIE
Solar/Wind Harmer
0.283
970601AG2-382 GEN
Solar/Wind Harmer
10.575
316087AB2-174 GEN
Solar/Wind Harmer
0.008
3146043SEABORD
Solar/Wind Harmer
0.28
3145513AHOSKIE
Solar/Wind Harmer
0.586
3145513AHOSKIE
Solar/Wind Harmer
0.28
315607AA1-063A GEN
Solar/Wind Harmer
0.572
3145683EARLEYS
Solar/Wind Harmer
0.558
3145683EARLEYS
Solar/Wind Harmer
0.279
3145683EARLEYS
Solar/Wind Harmer
0.279
315652AC1-086 GEN
Solar/Wind Harmer
30.678
3137643SOCKMAN
Solar/Wind Harmer
1.111
3145796HORNRTN
Solar/Wind Harmer
0.88
3145796HORNRTN
Solar/Wind Harmer
0.11
3146033SCOT NK
Solar/Wind Harmer
1.084
970831AG2-522 GEN
Solar/Wind Harmer
11.448
3138283WHITEMARSH
Solar/Wind Harmer
0.061
316005AA1-067
Solar/Wind Harmer
0.28
3145746EVERETS
Solar/Wind Harmer
1.039
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
970181AG2-120 GEN
Solar/Wind Harmer
3.25
957861AF2-080 GEN
Solar/Wind Harmer
11.129
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316420AA1-050 GEN
Solar/Wind Harmer
0.008
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.255
3145573BETHELC
Solar/Wind Harmer
0.255
971167AH1-042 GEN
Solar/Wind Harmer
22.645
315976AC1-164 GENA
Solar/Wind Harmer
26.291
316169AC1-164_GENC
Solar/Wind Harmer
22.713
315975AC1-164 GENB
Solar/Wind Harmer
0.778
3142433PROV 92
Adder
0.492
3142433PROV 92
Adder
0.492
971443AH1-215 GEN
Solar/Wind Harmer
4.236
3144303KENBRDG
Solar/Wind Harmer
0.201
970683AG2-441 GEN
Solar/Wind Harmer
16.616
970681AG2-440 GEN
Solar/Wind Harmer
13.292
946301AF1-294 GEN
Solar/Wind Harmer
4.868
961791AG1-021 GEN
Solar/Wind Harmer
2.368
3143873LANEXA
Solar/Wind Harmer
0.148
315657AE1-056 GEN
Solar/Wind Harmer
8.449
316118AC1-105 GEN
Solar/Wind Harmer
0.629
970189AG2-124 GEN
Solar/Wind Harmer
7.213
315662AE1-191 GEN
Solar/Wind Harmer
0.008
315666AE1-190 GEN
Solar/Wind Harmer
0.002
316314AB2-024 C
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.048
3147173SINAI
Solar/Wind Harmer
0.24
3147243WELCO
Solar/Wind Harmer
0.15
316312AB1-027
Solar/Wind Harmer
0.429
3141913WHIT STONE
Solar/Wind Harmer
0.234
3138133OCRAN
Solar/Wind Harmer
0.069
3141783LANCAST
Solar/Wind Harmer
0.137
3141783LANCAST
Solar/Wind Harmer
0.091
962981AG1-147 GEN
Solar/Wind Harmer
8.172
970285AG2-188 GEN
Solar/Wind Harmer
17.223
971845AH1-439 GEN
Solar/Wind Harmer
9.707
970327AG2-215 GEN
Solar/Wind Harmer
7.016
970865AG2-541 GEN
Solar/Wind Harmer
7.314
316123AC1-075 GEN
Solar/Wind Harmer
0.262
970165AG2-112 GEN
Solar/Wind Harmer
1.554
970163AG2-111 GEN
Solar/Wind Harmer
1.483
3141813NORNECK
Solar/Wind Harmer
0.191
972205AH1-687 GEN
Adder
7.916
971447AH1-217 GEN
Solar/Wind Harmer
4.969
270494AE1-108_GEN
Solar/Wind Harmer
1.845
972189AH1-679 GEN
Adder
2.488
316223AC1-118
Solar/Wind Harmer
0.103
972193AH1-681 GEN
Adder
2.949
316164AC1-076 GEN
Solar/Wind Helper
1.496
316411AF1-147_GEN1
Solar/Wind Helper
0.807
316415AF1-147_GEN2
Solar/Wind Helper
0.807
3138216PACIFIC
Solar/Wind Helper
0.039
LAGNLTFEXP_LAGN->PJM
CLTF
12.487
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.504
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.654
MECLTFEXP_MEC->PJM
CLTF
6.28
SIGELTFEXP_SIGE->PJM
CLTF
0.191
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.918
TVALTFEXP_TVA->PJM
CLTF
6.285
NYPJM->LTFIMP_NY
CLTF
3.567
LGEELTFEXP_LGEE->PJM
CLTF
2.341
WECLTFEXP_WEC->PJM
CLTF
1.189
CPLELTFEXP_CPLE->PJM
CLTF
16.793
CBM West 2LTFEXP_CBM-W2->PJM
CBM
66.855
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.096

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.69 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4402.07
MW Contribution:7.05
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
5.785
315244AE2-183_ST
50/50
9.174
963041AG1-153 GEN
50/50
8.444
3151081ELIZAR1
50/50
28.413
3151091ELIZAR2
50/50
27.92
941591AE2-156 GEN
50/50
25.939
3152611GOSPORTB
50/50
3.939
3152621GOSPORTC
50/50
3.343
3152601GOSPORTA
50/50
3.084
315779AE2-040
50/50
4.048
970533AG2-339 GEN
50/50
29.471
3151031BRUNSWICKG2
50/50
4.17
3151101ELIZAR3
50/50
28.777
3151161SURRY 1
50/50
10.302
970917AG2-570 GEN
Solar/Wind Harmer
27.004
315773AC2-141 GEN
Solar/Wind Harmer
10.994
944581AF1-123 GEN
Solar/Wind Harmer
66.571
944601AF1-125 GEN
Solar/Wind Harmer
65.546
3144873MCLAUGH
Solar/Wind Harmer
0.007
3146456SLIGO L269
Solar/Wind Harmer
0.29
971153AH1-033 GEN
Solar/Wind Harmer
3.357
316320Y1-086
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.043
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.284
3146626S HERTFORD
Solar/Wind Harmer
0.282
3145273HOLLAND
Solar/Wind Harmer
0.209
3146376EDENTON
Solar/Wind Harmer
0.277
3145336SMITFLD
Solar/Wind Harmer
0.111
970661AG2-428 GEN
Solar/Wind Harmer
5.809
316083AB2-161 GEN
Solar/Wind Harmer
0.004
315614AA2-178 GEN
Solar/Wind Harmer
1.557
970659AG2-427 GEN
Solar/Wind Harmer
2.872
316365GEN2_N
Solar/Wind Harmer
0.603
3151221GRAVEL6
Adder
19.5
3151171GRAVELC
Adder
3.752
971157AH1-035 GEN
Solar/Wind Harmer
3.217
315813AE1-149 C
Solar/Wind Harmer
14.26
315737AD1-076 GEN
Solar/Wind Harmer
3.44
316478AD1-087 GEN
Solar/Wind Harmer
0.932
316486AD2-202 GEN
Solar/Wind Harmer
0.274
3156081AA2-088 GEN
Solar/Wind Harmer
0.006
3146206CASHIE
Solar/Wind Harmer
0.265
3144216WINCHST
Adder
0.999
3145893MURPHYS
Solar/Wind Harmer
0.442
3145893MURPHYS
Solar/Wind Harmer
0.264
3150921YORKTN3
Adder
6.638
957521AF2-046 GEN
Solar/Wind Harmer
19.613
961681AG1-008 GEN
Solar/Wind Harmer
19.613
961611AG1-000B GEN
Solar/Wind Harmer
7.014
3146173TUNIS
Solar/Wind Harmer
0.262
3156021HOLLOMANSOL
Solar/Wind Harmer
1.189
316463AE2-346 GEN
Solar/Wind Harmer
0.224
316140AB2-099
Solar/Wind Harmer
0.093
962331AG1-082 GEN
Solar/Wind Harmer
2.786
3146263WOODLND
Solar/Wind Harmer
0.259
313506AB2-031 GEN
Solar/Wind Harmer
0.8
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
3145963POPLR C
Solar/Wind Harmer
0.256
316317KELFORD C
Solar/Wind Harmer
0.025
3145823KELFORD
Solar/Wind Harmer
0.256
316313AB2-026
Solar/Wind Harmer
0.16
316258AE1-075 C
Solar/Wind Harmer
0.192
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.845
3145796HORNRTN
Solar/Wind Harmer
1.016
3145796HORNRTN
Solar/Wind Harmer
0.254
3147043LAWRENC
Solar/Wind Harmer
0.152
315839AE2-212 C
Solar/Wind Harmer
0.002
315778AD1-151 GEN
Solar/Wind Harmer
20.127
316382AG1-145 C
Solar/Wind Harmer
0.002
965281AG1-393 GEN
Solar/Wind Harmer
2.647
316210AC1-098 GEN
Solar/Wind Harmer
2.301
3145933PARMELE
Solar/Wind Harmer
0.247
966801AG1-551 GEN
Solar/Wind Harmer
2.873
970129AG2-093 GEN
Solar/Wind Harmer
14.877
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
315724AD1-057 GEN
Solar/Wind Harmer
0.909
316327AA2-057 GEN
Solar/Wind Harmer
0.363
3150861SPRUNCD
Adder
1.101
970133AG2-095 GEN
Solar/Wind Harmer
2.289
3146233WITAKRS
Solar/Wind Harmer
1.186
3146233WITAKRS
Solar/Wind Harmer
0.161
3146073TAR RVR
Solar/Wind Harmer
0.236
3146083TARBORO
Solar/Wind Harmer
0.236
3138543CONSLDL
Solar/Wind Harmer
0.156
316131AB2-060 GEN
Solar/Wind Harmer
0.739
964241AG1-285 GEN
Solar/Wind Harmer
15.529
970909AG2-566 GEN
Solar/Wind Harmer
2.481
961601AG1-000A GEN
Solar/Wind Harmer
16.539
3145543BTLEBRO
Solar/Wind Harmer
0.232
3145543BTLEBRO
Solar/Wind Harmer
0.232
971623AH1-311 GEN
Solar/Wind Harmer
0.465
315785AD2-033 C
Solar/Wind Harmer
1.864
970257AG2-171 GEN
Solar/Wind Harmer
7.295
959311AF2-222 GEN
Solar/Wind Harmer
20.178
3142946ENON
Solar/Wind Harmer
0.074
963181AG1-167 GEN
Solar/Wind Harmer
0.885
3144293JTRSVLE
Adder
0.705
3147133PAMPLIN
Solar/Wind Harmer
0.687
971193AH1-056 GEN
Solar/Wind Harmer
13.34
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.346
316156AD2-030 GEN
Solar/Wind Harmer
0.16
3141873WAN 176
Solar/Wind Harmer
3.848
316280AD1-041 GEN
Solar/Wind Harmer
0.004
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141843SHACKLE
Adder
1.102
3143096IRON208
Adder
0.902
3143096IRON208
Adder
0.884
3141766HARMONY
Solar/Wind Harmer
2.867
3142433PROV 92
Adder
0.418
3142433PROV 92
Adder
0.418
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.123
316283AC2-100 C
Solar/Wind Harmer
0.389
971683AH1-343 GEN
Solar/Wind Harmer
7.294
962971AG1-146 GEN
Solar/Wind Harmer
3.148
970293AG2-193 GEN
Solar/Wind Harmer
2.064
970009AG2-005 GEN
Solar/Wind Harmer
1.436
316404AE1-155 C
Solar/Wind Harmer
0.042
3146776BUCKING
Solar/Wind Harmer
0.065
3150351NORNECKC2
Adder
1.745
3142416OLDCHRC
Solar/Wind Harmer
1.55
3141906WESTMOR
Solar/Wind Harmer
0.053
970221AG2-151 GEN
Solar/Wind Harmer
7.048
316473AC1-191 GEN
Solar/Wind Harmer
0.412
970737AG2-469 GEN
Solar/Wind Harmer
4.87
316044AC1-158 PL1
Solar/Wind Helper
1.723
316450AC1-158 RIC
Solar/Wind Helper
0.459
3147666LOUISA
Solar/Wind Helper
0.596
972263AH1-716 GEN
50/50
164.964
941031AE2-094 GEN
Solar/Wind Harmer
61.065
944011AF1-069 GEN
Solar/Wind Harmer
19.952
970673AG2-436 GEN
Solar/Wind Harmer
69.269
970673AG2-436 GEN
Solar/Wind Harmer
46.179
971967AH1-528 GEN
Solar/Wind Harmer
50.977
970085AG2-068 GEN
Solar/Wind Harmer
16.126
970581AG2-369 GEN
Solar/Wind Harmer
13.869
957871AF2-081 GEN
Solar/Wind Harmer
14.487
319010AE1-072 C
Solar/Wind Harmer
1.462
3146406KITTY HAWK
Solar/Wind Harmer
0.036
316315AB2-025 C
Solar/Wind Harmer
0.234
315814AE2-033 C
Solar/Wind Harmer
22.859
316305AF2-043 C
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.156
316321Z2-027
Solar/Wind Harmer
0.053
3146396TANGLEW
Solar/Wind Harmer
0.789
3145176PASQUOTANK
Solar/Wind Harmer
0.177
3146486SUNBURY
Solar/Wind Harmer
0.286
3146486SUNBURY
Solar/Wind Harmer
0.286
315835AF2-110_GEN
Solar/Wind Harmer
1.956
316233AE1-074 FULL
Solar/Wind Harmer
0.226
971281AH1-106 GEN
Solar/Wind Harmer
3.922
971283AH1-107 GEN
Solar/Wind Harmer
3.922
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
316311AC2-079 GEN
Solar/Wind Harmer
8.046
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.192
3130156CHOWAN
Solar/Wind Harmer
0.277
3130156CHOWAN
Solar/Wind Harmer
0.277
971445AH1-216 GEN
Solar/Wind Harmer
19.461
3143316POE
Solar/Wind Harmer
1.085
315816AE2-034 GEN
Solar/Wind Harmer
1.168
972265AH1-717 GEN
Adder
20.825
3151201GRAVEL4
Adder
19.522
3151191GRAVEL3
Adder
19.275
3151211GRAVEL5
Adder
19.275
3130546PLYMOUTH
Solar/Wind Harmer
0.268
315732AD1-074 GEN1
Solar/Wind Harmer
1.536
315733AD1-074 GEN2
Solar/Wind Harmer
1.536
315735AD1-075 GEN1
Solar/Wind Harmer
0.769
965291AG1-394 GEN
Solar/Wind Harmer
1.182
3146206CASHIE
Solar/Wind Harmer
0.265
970601AG2-382 GEN
Solar/Wind Harmer
9.896
3145893MURPHYS
Solar/Wind Harmer
0.713
3145893MURPHYS
Solar/Wind Harmer
0.264
3145513AHOSKIE
Solar/Wind Harmer
0.546
3145513AHOSKIE
Solar/Wind Harmer
0.261
3146043SEABORD
Solar/Wind Harmer
0.26
3145683EARLEYS
Solar/Wind Harmer
0.52
3145683EARLEYS
Solar/Wind Harmer
0.26
3145683EARLEYS
Solar/Wind Harmer
0.26
316087AB2-174 GEN
Solar/Wind Harmer
0.007
315607AA1-063A GEN
Solar/Wind Harmer
0.531
315652AC1-086 GEN
Solar/Wind Harmer
28.344
3137643SOCKMAN
Solar/Wind Harmer
1.027
316369SG1_INVT
Solar/Wind Harmer
0.01
3145796HORNRTN
Solar/Wind Harmer
0.813
3145796HORNRTN
Solar/Wind Harmer
0.102
3146033SCOT NK
Solar/Wind Harmer
1.006
970831AG2-522 GEN
Solar/Wind Harmer
10.563
316132AB2-190 GEN1
Solar/Wind Harmer
1.325
316005AA1-067
Solar/Wind Harmer
0.26
3145746EVERETS
Solar/Wind Harmer
0.964
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
970181AG2-120 GEN
Solar/Wind Harmer
3.014
3138283WHITEMARSH
Solar/Wind Harmer
0.056
971285AH1-108 GEN
Adder
1.802
957861AF2-080 GEN
Solar/Wind Harmer
10.3
316420AA1-050 GEN
Solar/Wind Harmer
0.008
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.236
3145573BETHELC
Solar/Wind Harmer
0.236
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
3.835
3144303KENBRDG
Solar/Wind Harmer
0.182
970683AG2-441 GEN
Solar/Wind Harmer
14.971
970681AG2-440 GEN
Solar/Wind Harmer
11.976
316118AC1-105 GEN
Solar/Wind Harmer
0.574
946301AF1-294 GEN
Solar/Wind Harmer
4.367
961791AG1-021 GEN
Solar/Wind Harmer
2.125
315657AE1-056 GEN
Solar/Wind Harmer
7.556
3147173SINAI
Solar/Wind Harmer
0.219
3147243WELCO
Solar/Wind Harmer
0.137
315976AC1-164 GENA
Solar/Wind Harmer
22.6
316169AC1-164_GENC
Solar/Wind Harmer
19.524
315975AC1-164 GENB
Solar/Wind Harmer
0.669
3141873WAN 176
Solar/Wind Harmer
0.043
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
970189AG2-124 GEN
Solar/Wind Harmer
6.392
971167AH1-042 GEN
Solar/Wind Harmer
19.104
316059AD1-063 C
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.418
3142433PROV 92
Adder
0.418
3143873LANEXA
Solar/Wind Harmer
0.129
316314AB2-024 C
Solar/Wind Harmer
0.001
3141913WHIT STONE
Solar/Wind Harmer
0.21
3138133OCRAN
Solar/Wind Harmer
0.062
3141783LANCAST
Solar/Wind Harmer
0.123
3141783LANCAST
Solar/Wind Harmer
0.082
962981AG1-147 GEN
Solar/Wind Harmer
7.345
970327AG2-215 GEN
Solar/Wind Harmer
6.31
970865AG2-541 GEN
Solar/Wind Harmer
6.523
970285AG2-188 GEN
Solar/Wind Harmer
14.703
971845AH1-439 GEN
Solar/Wind Harmer
8.235
3141813NORNECK
Solar/Wind Harmer
0.172
316123AC1-075 GEN
Solar/Wind Harmer
0.229
970165AG2-112 GEN
Solar/Wind Harmer
1.36
970163AG2-111 GEN
Solar/Wind Harmer
1.297
316312AB1-027
Solar/Wind Harmer
0.286
972205AH1-687 GEN
Adder
6.309
316223AC1-118
Solar/Wind Harmer
0.095
971447AH1-217 GEN
Solar/Wind Harmer
3.746
270494AE1-108_GEN
Solar/Wind Harmer
1.403
316164AC1-076 GEN
Solar/Wind Helper
1.139
970119AG2-088 GEN
50/50
43.39
315243AE2-183_GT3
50/50
5.306
3151051BRUNSWICKS1
50/50
8.655
3151021BRUNSWICKG1
50/50
4.17
971451AH1-221 GEN
50/50
12.666
3150981CHESPKA
50/50
3.862
3152331SURRY 2
50/50
11.978
940641AE2-051 GEN
Solar/Wind Harmer
26.972
939411AE1-173 GEN
Solar/Wind Harmer
139.157
3143226MDLTHAN
Solar/Wind Harmer
0.325
970919AG2-571 GEN
Solar/Wind Harmer
10.802
970087AG2-069 GEN
Solar/Wind Harmer
24.19
316294AC1-161 GEN
Solar/Wind Harmer
5.215
944591AF1-124 GEN
Solar/Wind Harmer
66.808
316375AC2-012 GEN
Solar/Wind Harmer
0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.912
3146456SLIGO L269
Solar/Wind Harmer
0.29
316246AF1-032 C
Solar/Wind Harmer
0.13
316093AE2-104_GEN
Solar/Wind Harmer
4.794
3146516WINFALL
Solar/Wind Harmer
0.92
3146516WINFALL
Solar/Wind Harmer
0.284
316072AD1-144
Solar/Wind Harmer
0.103
3143526WINTERP
Solar/Wind Harmer
1.47
957481AF2-042 GEN
Solar/Wind Harmer
74.795
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.277
3145336SMITFLD
Solar/Wind Harmer
1.108
970661AG2-428 GEN
Solar/Wind Harmer
27.311
316381AD1-082 GEN
Solar/Wind Harmer
0.284
3145663CRESWEL
Solar/Wind Harmer
0.761
971163AH1-040 GEN
Solar/Wind Harmer
21.769
970659AG2-427 GEN
Solar/Wind Harmer
13.13
315693AD1-088 GEN
Solar/Wind Harmer
12.923
316023GEN1_S
Solar/Wind Harmer
0.603
3151171GRAVELC
Adder
2.853
962491AG1-098 GEN
Solar/Wind Harmer
15.256
3146206CASHIE
Solar/Wind Harmer
0.265
971547AH1-271 GEN
Solar/Wind Harmer
5.655
3138126ROCKLANDING
Solar/Wind Harmer
0.121
3145893MURPHYS
Solar/Wind Harmer
1.056
3145893MURPHYS
Solar/Wind Harmer
1.174
961611AG1-000B GEN
Solar/Wind Harmer
13.793
3146173TUNIS
Solar/Wind Harmer
0.262
960081AF2-299 GEN
Solar/Wind Harmer
2.514
3145683EARLEYS
Solar/Wind Harmer
0.26
3146263WOODLND
Solar/Wind Harmer
0.259
971647AH1-324 GEN
Solar/Wind Harmer
11.046
316011AB1-132 GEN
Solar/Wind Harmer
4.685
962571AG1-106 GEN
Solar/Wind Harmer
3.666
316190AA2-174 GEN
Solar/Wind Harmer
0
971795AH1-408 GEN
Solar/Wind Harmer
17.096
3145963POPLR C
Solar/Wind Harmer
0.256
971317AH1-138 GEN
Solar/Wind Harmer
1.913
3145823KELFORD
Solar/Wind Harmer
0.256
3143336POWHATN
Solar/Wind Harmer
4.523
316174AB2-169 GEN
Solar/Wind Harmer
0.007
3145783HORNRTN
Solar/Wind Harmer
0.254
3145796HORNRTN
Solar/Wind Harmer
0.838
3145796HORNRTN
Solar/Wind Harmer
0.254
3147043LAWRENC
Adder
2.297
971069AG2-661 GEN
Solar/Wind Harmer
4.473
315687AD1-152 GEN
Solar/Wind Harmer
0.008
316159AE1-175 C
Solar/Wind Harmer
0.215
316212AC1-099_GEN
Solar/Wind Harmer
1.283
316458AB2-190 GEN2
Solar/Wind Harmer
1.325
3146293MARTNCO
Solar/Wind Harmer
0.229
316129AC1-054 GEN
Solar/Wind Harmer
0.928
970129AG2-093 GEN
Solar/Wind Harmer
7.001
971065AG2-659 GEN
Solar/Wind Harmer
10.492
315671AE2-027_GEN
Solar/Wind Harmer
15.643
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
315722AD1-056 GEN
Solar/Wind Harmer
1.533
3150851SPRUNCC
Adder
1.101
316494AC1-189 GEN
Solar/Wind Harmer
0.807
3146233WITAKRS
Solar/Wind Harmer
0.94
961671AG1-007 GEN
Solar/Wind Harmer
0.036
3146083TARBORO
Solar/Wind Harmer
0.236
3145493TOT1
Solar/Wind Harmer
1.049
316336AC2-165 C
Solar/Wind Harmer
0.009
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3145543BTLEBRO
Solar/Wind Harmer
0.232
3145543BTLEBRO
Solar/Wind Harmer
0.186
316359AB2-059 GEN
Solar/Wind Harmer
0.835
316049AB1-081 GEN
Solar/Wind Harmer
1.331
3142053HEARTS
Solar/Wind Harmer
0.409
970401AG2-262 GEN
Solar/Wind Harmer
1.326
970685AG2-442 GEN
Solar/Wind Harmer
16.767
944631AF1-128 GEN
Adder
106.166
963171AG1-166 GEN
Solar/Wind Harmer
1.18
971563AH1-280 GEN
Solar/Wind Harmer
2.361
3144293JTRSVLE
Adder
0.705
3142543TWELFTH
Solar/Wind Harmer
0.021
971777AH1-397 GEN
Solar/Wind Harmer
0.569
3141843SHACKLE
Adder
1.102
3143096IRON208
Adder
0.902
3141766HARMONY
Solar/Wind Harmer
0.043
3142433PROV 92
Solar/Wind Harmer
0.86
3142433PROV 92
Adder
0.418
3142433PROV 92
Adder
0.418
3138133OCRAN
Solar/Wind Harmer
0.125
316003AC1-222 GEN
Solar/Wind Harmer
0.006
3146926FARMVIL
Solar/Wind Harmer
0.123
970937AG2-583 GEN
Solar/Wind Harmer
11.537
962861AG1-135 GEN
Solar/Wind Harmer
5.983
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.072
3141726DUNNSVL
Solar/Wind Harmer
0.706
3150351NORNECKC2
Adder
1.716
3142416OLDCHRC
Solar/Wind Harmer
0.416
3142416OLDCHRC
Solar/Wind Harmer
0.159
972003AH1-546 GEN
Solar/Wind Harmer
6.522
316337AD2-073 GEN
Solar/Wind Harmer
0.133
971377AH1-170 GEN
Solar/Wind Harmer
1.41
3147623JAMES R
Solar/Wind Harmer
0.306
970223AG2-152 GEN
Solar/Wind Harmer
9.004
270016AE1-250 BESS
Solar/Wind Harmer
0.004
3147123OTTER R
Solar/Wind Harmer
0.068
316045AC1-158 PL2
Solar/Wind Helper
5.515
3147666LOUISA
Solar/Wind Helper
1.037
316192AB2-158 GEN
Solar/Wind Helper
1.708
970531AG2-338 GEN
50/50
11.789
315242AE2-183_GT2
50/50
5.306
315241AE2-183_GT1
50/50
5.273
972185AH1-677 GEN
50/50
19.129
3151041BRUNSWICKG3
50/50
4.17
972187AH1-678 GEN
50/50
9.57
3150991CHESPKB
50/50
3.24
3150991CHESPKB
50/50
3.162
971223AH1-071 GEN
Solar/Wind Harmer
3.471
970933AG2-581 GEN
Solar/Wind Harmer
24.629
316185AD1-033 GEN
Solar/Wind Harmer
0.008
3145506HICKORY
Solar/Wind Harmer
1.168
3145506HICKORY
Solar/Wind Harmer
0.701
3145506HICKORY
Solar/Wind Harmer
0.175
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.28
316036AC1-147 C
Solar/Wind Harmer
0.054
316339AD2-160 GEN
Solar/Wind Harmer
0.472
316018AA1-139 ULT2
Solar/Wind Harmer
0.007
316017AA1-139 ULT1
Solar/Wind Harmer
0.162
3137176SLIGO L2192
Solar/Wind Harmer
1.156
3146456SLIGO L269
Solar/Wind Harmer
5.139
3130086AYDLETT
Solar/Wind Harmer
1.16
3144356SAPONY
Solar/Wind Harmer
2.426
3146386ELIZ CT
Solar/Wind Harmer
0.287
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.284
3146516WINFALL
Solar/Wind Harmer
0.284
3146516WINFALL
Solar/Wind Harmer
0.284
3143526WINTERP
Solar/Wind Harmer
1.47
3146626S HERTFORD
Solar/Wind Harmer
0.282
3146626S HERTFORD
Solar/Wind Harmer
0.282
970099AG2-077 GEN
Solar/Wind Harmer
29.918
3146376EDENTON
Solar/Wind Harmer
1.233
3146376EDENTON
Solar/Wind Harmer
1.233
316236AE1-162_GEN
Solar/Wind Harmer
0.002
315742AE1-103 GEN
Solar/Wind Harmer
0.003
970657AG2-426 GEN
Solar/Wind Harmer
9.567
970657AG2-426 GEN
Solar/Wind Harmer
2.006
316065AD1-022 GEN
Solar/Wind Harmer
12.243
3145893MURPHYS
Solar/Wind Harmer
1.767
3145893MURPHYS
Solar/Wind Harmer
0.475
3146173TUNIS
Solar/Wind Harmer
0.262
3146173TUNIS
Solar/Wind Harmer
0.262
316181AB2-040 GEN
Solar/Wind Harmer
0.376
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
316426AA2-053 GEN
Solar/Wind Harmer
0.866
3145593CAROLNA
Solar/Wind Harmer
0.255
3145593CAROLNA
Solar/Wind Harmer
0.255
966811AG1-552 GEN
Solar/Wind Harmer
2.773
3145593CAROLNA
Solar/Wind Harmer
0.318
316033AB2-134 GEN
Solar/Wind Harmer
0.015
315697AD1-025 GEN
Solar/Wind Harmer
0.287
3145783HORNRTN
Solar/Wind Harmer
4.52
3145783HORNRTN
Solar/Wind Harmer
3.616
3145783HORNRTN
Solar/Wind Harmer
1.13
3145783HORNRTN
Solar/Wind Harmer
0.452
3145796HORNRTN
Solar/Wind Harmer
0.762
3145933PARMELE
Solar/Wind Harmer
0.493
3145933PARMELE
Solar/Wind Harmer
0.247
316274AC1-208 GEN
Solar/Wind Harmer
1.28
971741AH1-377 GEN
Solar/Wind Harmer
23.908
939181AE1-148 GEN
Solar/Wind Harmer
11.558
316240AF1-291 C
Solar/Wind Harmer
0.002
3145493TOT1
Solar/Wind Harmer
0.547
3145453TOT5
Solar/Wind Harmer
0.328
3145603CNETO
Solar/Wind Harmer
0.219
313527AB2-043 GEN
Solar/Wind Harmer
0.003
944641AF1-129 GEN
Adder
111.535
970301AG2-198 GEN
Solar/Wind Harmer
9.924
961601AG1-000A GEN
Solar/Wind Harmer
4.135
316263AC1-034 GEN
Solar/Wind Harmer
8.835
970323AG2-213 GEN
Solar/Wind Harmer
9.727
971775AH1-396 GEN
Solar/Wind Harmer
0.365
316034AC1-036 C
Solar/Wind Harmer
0.017
962561AG1-105 GEN
Solar/Wind Harmer
10.919
964791AG1-342 GEN
Solar/Wind Harmer
4.339
3146843MT LREL
Solar/Wind Harmer
0.226
3146843MT LREL
Solar/Wind Harmer
0.226
3142946ENON
Solar/Wind Harmer
0.022
958211AF2-115 GEN
Solar/Wind Harmer
2.656
963191AG1-168 GEN
Solar/Wind Harmer
0.885
3144293JTRSVLE
Adder
0.705
3144293JTRSVLE
Adder
0.593
3147133PAMPLIN
Solar/Wind Harmer
0.219
3147133PAMPLIN
Solar/Wind Harmer
0.175
316075AC2-137 C
Solar/Wind Harmer
0.055
316222AC1-221 GEN
Solar/Wind Harmer
0.83
3150691DARBY 3
Adder
13.407
3150701DARBY 4
Adder
13.376
3150681DARBY 2
Adder
13.36
3150671DARBY 1
Adder
13.345
958261AF2-120 GEN
Solar/Wind Harmer
6.119
3142366NRTHEST
Adder
0.595
3146776BUCKING
Solar/Wind Harmer
0.717
3146776BUCKING
Solar/Wind Harmer
0.058
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.803
3150341NORNECKC1
Adder
1.788
942751AE2-291 GEN
Solar/Wind Harmer
8.42
971489AH1-241 GEN
Solar/Wind Harmer
7.048
3142296MT RD221
Adder
0.414
270013AE1-250 PV
Solar/Wind Harmer
0.004
966871AG1-558 GEN
Solar/Wind Harmer
0.141
316447AC1-158 HLD
Solar/Wind Helper
3.792
LAGNLTFEXP_LAGN->PJM
CLTF
10.194
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.866
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.385
MECLTFEXP_MEC->PJM
CLTF
4.747
SIGELTFEXP_SIGE->PJM
CLTF
0.142
CBM South 2LTFEXP_CBM-S2->PJM
CBM
32.592
TVALTFEXP_TVA->PJM
CLTF
5.103
NYPJM->LTFIMP_NY
CLTF
2.749
LGEELTFEXP_LGEE->PJM
CLTF
1.702
WECLTFEXP_WEC->PJM
CLTF
0.865
CPLELTFEXP_CPLE->PJM
CLTF
15.205
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.962

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.34 %
Rating:3193.18 MVA
Rating Type:A
MVA to Mitigate:3619.13
MW Contribution:6.63
Bus #Bus NameTypeMW Contribution
970533AG2-339 GEN
50/50
25.341
970531AG2-338 GEN
50/50
10.136
315242AE2-183_GT2
50/50
4.563
315241AE2-183_GT1
50/50
4.535
972185AH1-677 GEN
50/50
16.45
3151041BRUNSWICKG3
50/50
3.586
972187AH1-678 GEN
50/50
8.23
971223AH1-071 GEN
Solar/Wind Harmer
3.255
970933AG2-581 GEN
Solar/Wind Harmer
21.207
3143526WINTERP
Solar/Wind Harmer
1.35
3144356SAPONY
Solar/Wind Harmer
2.053
970099AG2-077 GEN
Solar/Wind Harmer
25.81
316185AD1-033 GEN
Solar/Wind Harmer
0.006
3145506HICKORY
Solar/Wind Harmer
0.89
3145506HICKORY
Solar/Wind Harmer
0.534
3145506HICKORY
Solar/Wind Harmer
0.134
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.213
316339AD2-160 GEN
Solar/Wind Harmer
0.36
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.124
3137176SLIGO L2192
Solar/Wind Harmer
0.883
3146456SLIGO L269
Solar/Wind Harmer
3.926
316036AC1-147 C
Solar/Wind Harmer
0.041
3130086AYDLETT
Solar/Wind Harmer
0.886
3150991CHESPKB
Adder
2.322
3150991CHESPKB
Adder
2.266
3146386ELIZ CT
Solar/Wind Harmer
0.22
970657AG2-426 GEN
Solar/Wind Harmer
7.686
970657AG2-426 GEN
Solar/Wind Harmer
1.611
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.219
3146516WINFALL
Solar/Wind Harmer
0.219
3146516WINFALL
Solar/Wind Harmer
0.219
3146626S HERTFORD
Solar/Wind Harmer
0.218
3146626S HERTFORD
Solar/Wind Harmer
0.218
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
0.961
3146376EDENTON
Solar/Wind Harmer
0.961
316181AB2-040 GEN
Solar/Wind Harmer
0.313
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.128
3145893MURPHYS
Solar/Wind Harmer
1.424
3145893MURPHYS
Solar/Wind Harmer
0.383
3145593CAROLNA
Solar/Wind Harmer
0.211
3145593CAROLNA
Solar/Wind Harmer
0.211
966811AG1-552 GEN
Solar/Wind Harmer
2.295
3145593CAROLNA
Solar/Wind Harmer
0.263
3146173TUNIS
Solar/Wind Harmer
0.211
3146173TUNIS
Solar/Wind Harmer
0.211
316065AD1-022 GEN
Solar/Wind Harmer
9.733
316426AA2-053 GEN
Solar/Wind Harmer
0.714
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3145796HORNRTN
Solar/Wind Harmer
0.632
971741AH1-377 GEN
Solar/Wind Harmer
20.897
3145783HORNRTN
Solar/Wind Harmer
3.74
3145783HORNRTN
Solar/Wind Harmer
2.992
3145783HORNRTN
Solar/Wind Harmer
0.935
3145783HORNRTN
Solar/Wind Harmer
0.374
939181AE1-148 GEN
Solar/Wind Harmer
9.88
970301AG2-198 GEN
Solar/Wind Harmer
8.706
316274AC1-208 GEN
Solar/Wind Harmer
1.058
313527AB2-043 GEN
Solar/Wind Harmer
0.003
316240AF1-291 C
Solar/Wind Harmer
0.002
3145933PARMELE
Solar/Wind Harmer
0.401
3145933PARMELE
Solar/Wind Harmer
0.2
316033AB2-134 GEN
Solar/Wind Harmer
0.012
315697AD1-025 GEN
Solar/Wind Harmer
0.223
970323AG2-213 GEN
Solar/Wind Harmer
8.431
971775AH1-396 GEN
Solar/Wind Harmer
0.316
316034AC1-036 C
Solar/Wind Harmer
0.014
944641AF1-129 GEN
Adder
93.824
962561AG1-105 GEN
Solar/Wind Harmer
9.407
3145493TOT1
Solar/Wind Harmer
0.453
3145453TOT5
Solar/Wind Harmer
0.272
3145603CNETO
Solar/Wind Harmer
0.181
964791AG1-342 GEN
Solar/Wind Harmer
3.74
3146843MT LREL
Solar/Wind Harmer
0.195
3146843MT LREL
Solar/Wind Harmer
0.195
961601AG1-000A GEN
Solar/Wind Harmer
3.447
316263AC1-034 GEN
Solar/Wind Harmer
7.365
958211AF2-115 GEN
Solar/Wind Harmer
2.318
963191AG1-168 GEN
Solar/Wind Harmer
0.773
3144293JTRSVLE
Adder
0.615
3144293JTRSVLE
Adder
0.518
3147133PAMPLIN
Solar/Wind Harmer
0.192
3147133PAMPLIN
Solar/Wind Harmer
0.153
316222AC1-221 GEN
Solar/Wind Harmer
0.714
3142946ENON
Solar/Wind Harmer
0.016
3146776BUCKING
Solar/Wind Harmer
0.65
3146776BUCKING
Solar/Wind Harmer
0.053
3142366NRTHEST
Adder
0.505
3150691DARBY 3
Adder
10.955
3150701DARBY 4
Adder
10.93
3150681DARBY 2
Adder
10.917
3150671DARBY 1
Adder
10.904
316075AC2-137 C
Solar/Wind Harmer
0.04
942751AE2-291 GEN
Solar/Wind Harmer
7.378
958261AF2-120 GEN
Solar/Wind Harmer
4.15
971489AH1-241 GEN
Solar/Wind Harmer
6.633
3142296MT RD221
Adder
0.39
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.211
3150341NORNECKC1
Adder
1.201
966871AG1-558 GEN
Solar/Wind Harmer
0.131
316447AC1-158 HLD
Solar/Wind Helper
3.579
3151031BRUNSWICKG2
50/50
3.586
970413AG2-270 GEN
50/50
21.547
3151101ELIZAR3
50/50
21.88
970917AG2-570 GEN
Solar/Wind Harmer
23.218
316313AB2-026
Solar/Wind Harmer
0.15
316258AE1-075 C
Solar/Wind Harmer
0.18
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.602
316478AD1-087 GEN
Solar/Wind Harmer
0.805
316486AD2-202 GEN
Solar/Wind Harmer
0.236
316365GEN2_N
Solar/Wind Harmer
0.504
944581AF1-123 GEN
Solar/Wind Harmer
50.561
944601AF1-125 GEN
Solar/Wind Harmer
49.783
315773AC2-141 GEN
Solar/Wind Harmer
8.172
3146456SLIGO L269
Solar/Wind Harmer
0.222
971153AH1-033 GEN
Solar/Wind Harmer
2.565
3144873MCLAUGH
Solar/Wind Harmer
0.006
316320Y1-086
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
4.646
316435W1029_GEN3
Solar/Wind Harmer
0.001
316083AB2-161 GEN
Solar/Wind Harmer
0.003
970659AG2-427 GEN
Solar/Wind Harmer
2.32
3146516WINFALL
Solar/Wind Harmer
0.219
315813AE1-149 C
Solar/Wind Harmer
11.679
3144536CHRHLND
Solar/Wind Harmer
0.033
3145273HOLLAND
Solar/Wind Harmer
0.164
3146626S HERTFORD
Solar/Wind Harmer
0.218
3146376EDENTON
Solar/Wind Harmer
0.216
313506AB2-031 GEN
Solar/Wind Harmer
0.667
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
3147043LAWRENC
Solar/Wind Harmer
0.129
315614AA2-178 GEN
Solar/Wind Harmer
1.224
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3145893MURPHYS
Solar/Wind Harmer
0.356
3145893MURPHYS
Solar/Wind Harmer
0.213
315839AE2-212 C
Solar/Wind Harmer
0.002
957521AF2-046 GEN
Solar/Wind Harmer
15.803
961681AG1-008 GEN
Solar/Wind Harmer
15.803
971157AH1-035 GEN
Solar/Wind Harmer
2.546
315737AD1-076 GEN
Solar/Wind Harmer
2.725
3146173TUNIS
Solar/Wind Harmer
0.211
3146206CASHIE
Solar/Wind Harmer
0.211
3145336SMITFLD
Solar/Wind Harmer
0.084
316463AE2-346 GEN
Solar/Wind Harmer
0.181
316140AB2-099
Solar/Wind Harmer
0.075
962331AG1-082 GEN
Solar/Wind Harmer
2.248
3145796HORNRTN
Solar/Wind Harmer
0.842
3145796HORNRTN
Solar/Wind Harmer
0.211
3150861SPRUNCD
Adder
0.97
3146263WOODLND
Solar/Wind Harmer
0.21
3156021HOLLOMANSOL
Solar/Wind Harmer
0.954
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.208
965281AG1-393 GEN
Solar/Wind Harmer
2.207
3145963POPLR C
Solar/Wind Harmer
0.206
3151221GRAVEL6
Adder
14.86
3151171GRAVELC
Adder
2.859
316210AC1-098 GEN
Solar/Wind Harmer
1.894
970909AG2-566 GEN
Solar/Wind Harmer
2.177
316131AB2-060 GEN
Solar/Wind Harmer
0.636
961611AG1-000B GEN
Solar/Wind Harmer
5.383
315724AD1-057 GEN
Solar/Wind Harmer
0.756
964241AG1-285 GEN
Solar/Wind Harmer
13.392
3145933PARMELE
Solar/Wind Harmer
0.2
966801AG1-551 GEN
Solar/Wind Harmer
2.335
316327AA2-057 GEN
Solar/Wind Harmer
0.301
315785AD2-033 C
Solar/Wind Harmer
1.614
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
970257AG2-171 GEN
Solar/Wind Harmer
6.323
959311AF2-222 GEN
Solar/Wind Harmer
17.507
3146233WITAKRS
Solar/Wind Harmer
0.986
3146233WITAKRS
Solar/Wind Harmer
0.134
315778AD1-151 GEN
Solar/Wind Harmer
15.709
3138543CONSLDL
Solar/Wind Harmer
0.129
3146073TAR RVR
Solar/Wind Harmer
0.195
3146083TARBORO
Solar/Wind Harmer
0.195
961601AG1-000A GEN
Solar/Wind Harmer
13.786
3145543BTLEBRO
Solar/Wind Harmer
0.194
3145543BTLEBRO
Solar/Wind Harmer
0.194
971623AH1-311 GEN
Solar/Wind Harmer
0.388
970129AG2-093 GEN
Solar/Wind Harmer
11.71
963181AG1-167 GEN
Solar/Wind Harmer
0.773
3144293JTRSVLE
Adder
0.615
3147133PAMPLIN
Solar/Wind Harmer
0.602
971193AH1-056 GEN
Solar/Wind Harmer
11.673
970133AG2-095 GEN
Solar/Wind Harmer
1.824
3144216WINCHST
Adder
0.716
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
8.068
3150921YORKTN3
Adder
4.712
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.11
3143096IRON208
Adder
0.735
3143096IRON208
Adder
0.72
316382AG1-145 C
Solar/Wind Harmer
0.001
971683AH1-343 GEN
Solar/Wind Harmer
6.321
316283AC2-100 C
Solar/Wind Harmer
0.335
3142946ENON
Solar/Wind Harmer
0.055
3146776BUCKING
Solar/Wind Harmer
0.059
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3141843SHACKLE
Adder
0.766
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.003
316156AD2-030 GEN
Solar/Wind Harmer
0.111
3141873WAN 176
Solar/Wind Harmer
2.658
970293AG2-193 GEN
Solar/Wind Harmer
1.582
3141766HARMONY
Solar/Wind Harmer
1.964
962971AG1-146 GEN
Solar/Wind Harmer
2.151
970009AG2-005 GEN
Solar/Wind Harmer
0.978
3142416OLDCHRC
Solar/Wind Harmer
1.237
316404AE1-155 C
Solar/Wind Harmer
0.028
970221AG2-151 GEN
Solar/Wind Harmer
6.633
3150351NORNECKC2
Adder
1.172
316473AC1-191 GEN
Solar/Wind Harmer
0.383
316044AC1-158 PL1
Solar/Wind Helper
1.626
316450AC1-158 RIC
Solar/Wind Helper
0.434
3147666LOUISA
Solar/Wind Helper
0.562
316303AF2-085
50/50
5.424
315244AE2-183_ST
50/50
7.889
963041AG1-153 GEN
50/50
7.262
315779AE2-040
50/50
3.426
3151541CLOVER2
50/50
4.914
941031AE2-094 GEN
Solar/Wind Harmer
52.507
944011AF1-069 GEN
Solar/Wind Harmer
17.156
970673AG2-436 GEN
Solar/Wind Harmer
59.565
970673AG2-436 GEN
Solar/Wind Harmer
39.71
971967AH1-528 GEN
Solar/Wind Harmer
43.86
970085AG2-068 GEN
Solar/Wind Harmer
13.865
970581AG2-369 GEN
Solar/Wind Harmer
11.924
316233AE1-074 FULL
Solar/Wind Harmer
0.208
971281AH1-106 GEN
Solar/Wind Harmer
3.602
971283AH1-107 GEN
Solar/Wind Harmer
3.602
316315AB2-025 C
Solar/Wind Harmer
0.198
315814AE2-033 C
Solar/Wind Harmer
19.336
3143316POE
Solar/Wind Harmer
0.915
957871AF2-081 GEN
Solar/Wind Harmer
11.058
3151081ELIZAR1
Adder
20.359
3151091ELIZAR2
Adder
20.005
319010AE1-072 C
Solar/Wind Harmer
1.117
3146406KITTY HAWK
Solar/Wind Harmer
0.028
3152611GOSPORTB
Adder
2.823
3152621GOSPORTC
Adder
2.396
3152601GOSPORTA
Adder
2.21
316305AF2-043 C
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.119
315835AF2-110_GEN
Solar/Wind Harmer
1.513
316321Z2-027
Solar/Wind Harmer
0.041
3146396TANGLEW
Solar/Wind Harmer
0.607
3145176PASQUOTANK
Solar/Wind Harmer
0.136
3146486SUNBURY
Solar/Wind Harmer
0.22
3146486SUNBURY
Solar/Wind Harmer
0.22
316311AC2-079 GEN
Solar/Wind Harmer
6.318
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.151
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
316087AB2-174 GEN
Solar/Wind Harmer
0.006
3130156CHOWAN
Solar/Wind Harmer
0.216
3130156CHOWAN
Solar/Wind Harmer
0.216
965291AG1-394 GEN
Solar/Wind Harmer
0.951
315816AE2-034 GEN
Solar/Wind Harmer
0.918
315652AC1-086 GEN
Solar/Wind Harmer
23.483
3137643SOCKMAN
Solar/Wind Harmer
0.852
3145893MURPHYS
Solar/Wind Harmer
0.574
3145893MURPHYS
Solar/Wind Harmer
0.213
3146043SEABORD
Solar/Wind Harmer
0.213
315607AA1-063A GEN
Solar/Wind Harmer
0.434
3130546PLYMOUTH
Solar/Wind Harmer
0.212
315732AD1-074 GEN1
Solar/Wind Harmer
1.217
315733AD1-074 GEN2
Solar/Wind Harmer
1.217
315735AD1-075 GEN1
Solar/Wind Harmer
0.609
3146206CASHIE
Solar/Wind Harmer
0.211
970601AG2-382 GEN
Solar/Wind Harmer
7.883
3145513AHOSKIE
Solar/Wind Harmer
0.441
3145513AHOSKIE
Solar/Wind Harmer
0.211
3145796HORNRTN
Solar/Wind Harmer
0.674
3145796HORNRTN
Solar/Wind Harmer
0.084
971285AH1-108 GEN
Adder
1.587
971445AH1-216 GEN
Solar/Wind Harmer
14.817
3145683EARLEYS
Solar/Wind Harmer
0.42
3145683EARLEYS
Solar/Wind Harmer
0.21
3145683EARLEYS
Solar/Wind Harmer
0.21
970831AG2-522 GEN
Solar/Wind Harmer
8.902
3146033SCOT NK
Solar/Wind Harmer
0.823
972265AH1-717 GEN
Adder
15.87
3151201GRAVEL4
Adder
14.877
3151191GRAVEL3
Adder
14.689
3151211GRAVEL5
Adder
14.689
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316005AA1-067
Solar/Wind Harmer
0.212
3145746EVERETS
Solar/Wind Harmer
0.788
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
970181AG2-120 GEN
Solar/Wind Harmer
2.464
316369SG1_INVT
Solar/Wind Harmer
0.007
971443AH1-215 GEN
Solar/Wind Harmer
3.323
3144303KENBRDG
Solar/Wind Harmer
0.158
957861AF2-080 GEN
Solar/Wind Harmer
8.475
316319Z2-044 C
Solar/Wind Harmer
0
316420AA1-050 GEN
Solar/Wind Harmer
0.006
3145573BETHELC
Solar/Wind Harmer
0.195
3145573BETHELC
Solar/Wind Harmer
0.195
970683AG2-441 GEN
Solar/Wind Harmer
13.022
970681AG2-440 GEN
Solar/Wind Harmer
10.418
316132AB2-190 GEN1
Solar/Wind Harmer
1.041
946301AF1-294 GEN
Solar/Wind Harmer
3.812
961791AG1-021 GEN
Solar/Wind Harmer
1.855
316118AC1-105 GEN
Solar/Wind Harmer
0.495
315657AE1-056 GEN
Solar/Wind Harmer
6.612
3147173SINAI
Solar/Wind Harmer
0.189
3147243WELCO
Solar/Wind Harmer
0.118
3138283WHITEMARSH
Solar/Wind Harmer
0.039
970285AG2-188 GEN
Solar/Wind Harmer
13.256
971845AH1-439 GEN
Solar/Wind Harmer
7.448
970865AG2-541 GEN
Solar/Wind Harmer
5.665
971167AH1-042 GEN
Solar/Wind Harmer
14.133
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3143873LANEXA
Solar/Wind Harmer
0.09
970189AG2-124 GEN
Solar/Wind Harmer
4.44
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.03
316059AD1-063 C
Solar/Wind Harmer
0.001
316123AC1-075 GEN
Solar/Wind Harmer
0.2
970165AG2-112 GEN
Solar/Wind Harmer
1.187
970163AG2-111 GEN
Solar/Wind Harmer
1.132
316314AB2-024 C
Solar/Wind Harmer
0.001
315976AC1-164 GENA
Solar/Wind Harmer
15.083
316169AC1-164_GENC
Solar/Wind Harmer
13.031
315975AC1-164 GENB
Solar/Wind Harmer
0.446
3141913WHIT STONE
Solar/Wind Harmer
0.144
3138133OCRAN
Solar/Wind Harmer
0.043
3141783LANCAST
Solar/Wind Harmer
0.084
3141783LANCAST
Solar/Wind Harmer
0.056
972205AH1-687 GEN
Adder
5.897
962981AG1-147 GEN
Solar/Wind Harmer
5.019
970327AG2-215 GEN
Solar/Wind Harmer
4.3
316312AB1-027
Solar/Wind Harmer
0.228
971447AH1-217 GEN
Solar/Wind Harmer
3.55
3141813NORNECK
Solar/Wind Harmer
0.116
970119AG2-088 GEN
50/50
40.684
315243AE2-183_GT3
50/50
4.563
3151051BRUNSWICKS1
50/50
7.443
3151021BRUNSWICKG1
50/50
3.586
971451AH1-221 GEN
50/50
10.893
3151531CLOVER1
50/50
4.938
3143226MDLTHAN
Solar/Wind Harmer
0.305
940641AE2-051 GEN
Solar/Wind Harmer
22.672
939411AE1-173 GEN
Solar/Wind Harmer
114.479
970919AG2-571 GEN
Solar/Wind Harmer
9.287
970087AG2-069 GEN
Solar/Wind Harmer
20.797
3143526WINTERP
Solar/Wind Harmer
1.35
957481AF2-042 GEN
Solar/Wind Harmer
64.526
3143336POWHATN
Solar/Wind Harmer
4.238
315693AD1-088 GEN
Solar/Wind Harmer
11.177
962491AG1-098 GEN
Solar/Wind Harmer
13.203
316023GEN1_S
Solar/Wind Harmer
0.504
944591AF1-124 GEN
Solar/Wind Harmer
50.741
316294AC1-161 GEN
Solar/Wind Harmer
3.877
316388AE2-253 GEN
Solar/Wind Harmer
0.696
3146456SLIGO L269
Solar/Wind Harmer
0.222
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.768
316246AF1-032 C
Solar/Wind Harmer
0.1
316336AC2-165 C
Solar/Wind Harmer
0.009
316093AE2-104_GEN
Solar/Wind Harmer
3.708
970661AG2-428 GEN
Solar/Wind Harmer
21.842
316381AD1-082 GEN
Solar/Wind Harmer
0.229
960081AF2-299 GEN
Solar/Wind Harmer
2.106
970659AG2-427 GEN
Solar/Wind Harmer
10.606
3146516WINFALL
Solar/Wind Harmer
0.71
3146516WINFALL
Solar/Wind Harmer
0.219
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.216
971795AH1-408 GEN
Solar/Wind Harmer
14.392
316072AD1-144
Solar/Wind Harmer
0.078
315687AD1-152 GEN
Solar/Wind Harmer
0.007
3147043LAWRENC
Adder
1.939
3145663CRESWEL
Solar/Wind Harmer
0.599
971163AH1-040 GEN
Solar/Wind Harmer
17.112
316011AB1-132 GEN
Solar/Wind Harmer
3.881
962571AG1-106 GEN
Solar/Wind Harmer
3.037
3145893MURPHYS
Solar/Wind Harmer
0.851
3145893MURPHYS
Solar/Wind Harmer
0.946
3146173TUNIS
Solar/Wind Harmer
0.211
316190AA2-174 GEN
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.211
971547AH1-271 GEN
Solar/Wind Harmer
4.504
3145336SMITFLD
Solar/Wind Harmer
0.844
3145796HORNRTN
Solar/Wind Harmer
0.695
3145796HORNRTN
Solar/Wind Harmer
0.211
3150851SPRUNCC
Adder
0.97
3146263WOODLND
Solar/Wind Harmer
0.21
3145783HORNRTN
Solar/Wind Harmer
0.21
3145683EARLEYS
Solar/Wind Harmer
0.21
316129AC1-054 GEN
Solar/Wind Harmer
0.783
971065AG2-659 GEN
Solar/Wind Harmer
8.875
3145823KELFORD
Solar/Wind Harmer
0.208
3145963POPLR C
Solar/Wind Harmer
0.206
316174AB2-169 GEN
Solar/Wind Harmer
0.005
3151171GRAVELC
Adder
2.174
316212AC1-099_GEN
Solar/Wind Harmer
1.056
315671AE2-027_GEN
Solar/Wind Harmer
13.019
316237AB2-079_GEN
Solar/Wind Harmer
0.002
961611AG1-000B GEN
Solar/Wind Harmer
10.587
315722AD1-056 GEN
Solar/Wind Harmer
1.275
3146293MARTNCO
Solar/Wind Harmer
0.186
971647AH1-324 GEN
Solar/Wind Harmer
8.529
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
316494AC1-189 GEN
Solar/Wind Harmer
0.664
3146233WITAKRS
Solar/Wind Harmer
0.782
971069AG2-661 GEN
Solar/Wind Harmer
3.491
961671AG1-007 GEN
Solar/Wind Harmer
0.03
3146083TARBORO
Solar/Wind Harmer
0.195
3145493TOT1
Solar/Wind Harmer
0.868
970685AG2-442 GEN
Solar/Wind Harmer
14.585
970401AG2-262 GEN
Solar/Wind Harmer
1.143
316458AB2-190 GEN2
Solar/Wind Harmer
1.041
316359AB2-059 GEN
Solar/Wind Harmer
0.696
316049AB1-081 GEN
Solar/Wind Harmer
1.109
3145543BTLEBRO
Solar/Wind Harmer
0.194
3145543BTLEBRO
Solar/Wind Harmer
0.155
3142053HEARTS
Solar/Wind Harmer
0.341
970129AG2-093 GEN
Solar/Wind Harmer
5.511
963171AG1-166 GEN
Solar/Wind Harmer
1.03
971563AH1-280 GEN
Solar/Wind Harmer
2.061
3144293JTRSVLE
Adder
0.615
3138126ROCKLANDING
Solar/Wind Harmer
0.087
3142543TWELFTH
Solar/Wind Harmer
0.018
3146926FARMVIL
Solar/Wind Harmer
0.11
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971317AH1-138 GEN
Solar/Wind Harmer
1.337
970937AG2-583 GEN
Solar/Wind Harmer
10.797
3143096IRON208
Adder
0.735
316159AE1-175 C
Solar/Wind Harmer
0.149
944631AF1-128 GEN
Adder
81.311
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.065
3142433PROV 92
Solar/Wind Harmer
0.629
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
971777AH1-397 GEN
Solar/Wind Harmer
0.396
3141843SHACKLE
Adder
0.766
3141766HARMONY
Solar/Wind Harmer
0.029
3138133OCRAN
Solar/Wind Harmer
0.086
972003AH1-546 GEN
Solar/Wind Harmer
6.056
3142416OLDCHRC
Solar/Wind Harmer
0.332
3142416OLDCHRC
Solar/Wind Harmer
0.127
962861AG1-135 GEN
Solar/Wind Harmer
4.063
971377AH1-170 GEN
Solar/Wind Harmer
1.327
3147623JAMES R
Solar/Wind Harmer
0.288
3141726DUNNSVL
Solar/Wind Harmer
0.474
3150351NORNECKC2
Adder
1.153
970223AG2-152 GEN
Solar/Wind Harmer
7.902
316045AC1-158 PL2
Solar/Wind Helper
5.205
3147666LOUISA
Solar/Wind Helper
0.977
316192AB2-158 GEN
Solar/Wind Helper
1.608
LAGNLTFEXP_LAGN->PJM
CLTF
9.063
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.006
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.545
MECLTFEXP_MEC->PJM
CLTF
4.353
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.182
TVALTFEXP_TVA->PJM
CLTF
4.543
SIGELTFEXP_SIGE->PJM
CLTF
0.131
NYPJM->LTFIMP_NY
CLTF
2.393
LGEELTFEXP_LGEE->PJM
CLTF
1.582
WECLTFEXP_WEC->PJM
CLTF
0.806
CPLELTFEXP_CPLE->PJM
CLTF
13.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.637

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:150.27 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4839.45
MW Contribution:7.17
Bus #Bus NameTypeMW Contribution
971133AH1-012 GEN
50/50
10.055
3151731LOISA B
50/50
20.602
3151721LOISA A
50/50
20.496
970533AG2-339 GEN
50/50
18.118
970531AG2-338 GEN
50/50
7.247
315242AE2-183_GT2
50/50
3.266
315241AE2-183_GT1
50/50
3.246
972185AH1-677 GEN
50/50
11.773
3151041BRUNSWICKG3
50/50
2.568
972187AH1-678 GEN
50/50
5.893
316447AC1-158 HLD
Solar/Wind Harmer
7.902
966001AG1-469 GEN
Solar/Wind Harmer
0.166
971223AH1-071 GEN
Solar/Wind Harmer
2.353
970933AG2-581 GEN
Solar/Wind Harmer
15.316
315651AD1-115 GEN
Solar/Wind Harmer
0.006
3143526WINTERP
Solar/Wind Harmer
0.921
970099AG2-077 GEN
Solar/Wind Harmer
18.895
3144356SAPONY
Solar/Wind Harmer
1.401
971741AH1-377 GEN
Solar/Wind Harmer
16.521
970301AG2-198 GEN
Solar/Wind Harmer
7.019
3147133PAMPLIN
Solar/Wind Harmer
0.155
3147133PAMPLIN
Solar/Wind Harmer
0.124
958211AF2-115 GEN
Solar/Wind Harmer
1.852
963191AG1-168 GEN
Solar/Wind Harmer
0.617
3144293JTRSVLE
Adder
0.491
3144293JTRSVLE
Adder
0.414
3146776BUCKING
Solar/Wind Harmer
0.611
3146776BUCKING
Solar/Wind Harmer
0.049
316034AC1-036 C
Solar/Wind Harmer
0.011
970323AG2-213 GEN
Solar/Wind Harmer
6.518
971775AH1-396 GEN
Solar/Wind Harmer
0.244
313527AB2-043 GEN
Solar/Wind Harmer
0.002
939181AE1-148 GEN
Solar/Wind Harmer
7.211
316181AB2-040 GEN
Solar/Wind Harmer
0.216
3145593CAROLNA
Solar/Wind Harmer
0.146
3145593CAROLNA
Solar/Wind Harmer
0.146
966811AG1-552 GEN
Solar/Wind Harmer
1.582
3145593CAROLNA
Solar/Wind Harmer
0.182
3142666NORTHAMPTON
Solar/Wind Harmer
0.145
3142666NORTHAMPTON
Solar/Wind Harmer
0.145
3142666NORTHAMPTON
Solar/Wind Harmer
0.145
3142666NORTHAMPTON
Solar/Wind Harmer
0.087
316426AA2-053 GEN
Solar/Wind Harmer
0.49
3145783HORNRTN
Solar/Wind Harmer
2.577
3145783HORNRTN
Solar/Wind Harmer
2.062
3145783HORNRTN
Solar/Wind Harmer
0.644
3145783HORNRTN
Solar/Wind Harmer
0.258
962561AG1-105 GEN
Solar/Wind Harmer
6.941
3145796HORNRTN
Solar/Wind Harmer
0.432
3145506HICKORY
Solar/Wind Harmer
0.574
3145506HICKORY
Solar/Wind Harmer
0.344
3145506HICKORY
Solar/Wind Harmer
0.086
316185AD1-033 GEN
Solar/Wind Harmer
0.004
964791AG1-342 GEN
Solar/Wind Harmer
2.754
316339AD2-160 GEN
Solar/Wind Harmer
0.233
3146843MT LREL
Solar/Wind Harmer
0.143
3146843MT LREL
Solar/Wind Harmer
0.143
316018AA1-139 ULT2
Solar/Wind Harmer
0.004
316017AA1-139 ULT1
Solar/Wind Harmer
0.08
3137176SLIGO L2192
Solar/Wind Harmer
0.57
3146456SLIGO L269
Solar/Wind Harmer
2.535
3130086AYDLETT
Solar/Wind Harmer
0.573
315742AE1-103 GEN
Solar/Wind Harmer
0.002
3145893MURPHYS
Solar/Wind Harmer
0.957
3145893MURPHYS
Solar/Wind Harmer
0.257
3142956BIRDNECK
Solar/Wind Harmer
0
3146386ELIZ CT
Solar/Wind Harmer
0.143
316316AC1-027 C
Solar/Wind Harmer
0.137
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.142
3146516WINFALL
Solar/Wind Harmer
0.142
3146516WINFALL
Solar/Wind Harmer
0.142
3146173TUNIS
Solar/Wind Harmer
0.142
3146173TUNIS
Solar/Wind Harmer
0.142
316036AC1-147 C
Solar/Wind Harmer
0.026
3150991CHESPKB
Adder
1.49
3150991CHESPKB
Adder
1.454
3146626S HERTFORD
Solar/Wind Harmer
0.142
3146626S HERTFORD
Solar/Wind Harmer
0.142
3146376EDENTON
Solar/Wind Harmer
0.63
3146376EDENTON
Solar/Wind Harmer
0.63
316065AD1-022 GEN
Solar/Wind Harmer
6.472
970657AG2-426 GEN
Solar/Wind Harmer
4.92
970657AG2-426 GEN
Solar/Wind Harmer
1.032
316274AC1-208 GEN
Solar/Wind Harmer
0.727
3145933PARMELE
Solar/Wind Harmer
0.271
3145933PARMELE
Solar/Wind Harmer
0.135
971489AH1-241 GEN
Solar/Wind Harmer
7.167
3145493TOT1
Solar/Wind Harmer
0.31
3145453TOT5
Solar/Wind Harmer
0.186
3145603CNETO
Solar/Wind Harmer
0.124
316263AC1-034 GEN
Solar/Wind Harmer
5.078
961601AG1-000A GEN
Solar/Wind Harmer
2.374
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316222AC1-221 GEN
Solar/Wind Harmer
0.509
316240AF1-291 C
Solar/Wind Harmer
0.001
316033AB2-134 GEN
Solar/Wind Harmer
0.007
315697AD1-025 GEN
Solar/Wind Harmer
0.134
944641AF1-129 GEN
Adder
56.042
3152261N ANNA2
50/50
35.375
3151771S ANNAG1
50/50
1.098
3151801S ANNAS2
50/50
0.564
3151761LOISA E
50/50
42.002
972183AH1-676 GEN
50/50
328.628
3151031BRUNSWICKG2
50/50
2.568
316044AC1-158 PL1
Solar/Wind Harmer
3.595
316450AC1-158 RIC
Solar/Wind Harmer
0.958
3147666LOUISA
Solar/Wind Harmer
1.12
3132273ORANGE
Solar/Wind Harmer
0.054
316170AC1-121 GEN2
Solar/Wind Harmer
0.236
316313AB2-026
Solar/Wind Harmer
0.12
316258AE1-075 C
Solar/Wind Harmer
0.144
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.888
970917AG2-570 GEN
Solar/Wind Harmer
16.604
316478AD1-087 GEN
Solar/Wind Harmer
0.59
316486AD2-202 GEN
Solar/Wind Harmer
0.173
970909AG2-566 GEN
Solar/Wind Harmer
1.755
3146926FARMVIL
Solar/Wind Harmer
0.095
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3147133PAMPLIN
Solar/Wind Harmer
0.486
971193AH1-056 GEN
Solar/Wind Harmer
9.427
963181AG1-167 GEN
Solar/Wind Harmer
0.617
3144293JTRSVLE
Adder
0.491
316365GEN2_N
Solar/Wind Harmer
0.345
959311AF2-222 GEN
Solar/Wind Harmer
13.6
3146776BUCKING
Solar/Wind Harmer
0.055
970257AG2-171 GEN
Solar/Wind Harmer
4.889
315785AD2-033 C
Solar/Wind Harmer
1.239
3147043LAWRENC
Solar/Wind Harmer
0.091
964241AG1-285 GEN
Solar/Wind Harmer
10.109
316131AB2-060 GEN
Solar/Wind Harmer
0.475
313506AB2-031 GEN
Solar/Wind Harmer
0.461
3142666NORTHAMPTON
Solar/Wind Harmer
0.145
944581AF1-123 GEN
Solar/Wind Harmer
32.61
944601AF1-125 GEN
Solar/Wind Harmer
32.107
3145796HORNRTN
Solar/Wind Harmer
0.577
3145796HORNRTN
Solar/Wind Harmer
0.144
3156081AA2-088 GEN
Solar/Wind Harmer
0.003
3146456SLIGO L269
Solar/Wind Harmer
0.143
971153AH1-033 GEN
Solar/Wind Harmer
1.656
315773AC2-141 GEN
Solar/Wind Harmer
5.232
3145893MURPHYS
Solar/Wind Harmer
0.239
3145893MURPHYS
Solar/Wind Harmer
0.143
3145273HOLLAND
Solar/Wind Harmer
0.107
316320Y1-086
Solar/Wind Harmer
0.001
957521AF2-046 GEN
Solar/Wind Harmer
10.626
961681AG1-008 GEN
Solar/Wind Harmer
10.626
3146263WOODLND
Solar/Wind Harmer
0.143
3151101ELIZAR3
Adder
13.236
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.142
3146173TUNIS
Solar/Wind Harmer
0.142
3144873MCLAUGH
Solar/Wind Harmer
0.004
3146626S HERTFORD
Solar/Wind Harmer
0.142
316463AE2-346 GEN
Solar/Wind Harmer
0.122
316140AB2-099
Solar/Wind Harmer
0.051
962331AG1-082 GEN
Solar/Wind Harmer
1.513
3146376EDENTON
Solar/Wind Harmer
0.142
315614AA2-178 GEN
Solar/Wind Harmer
0.807
3156021HOLLOMANSOL
Solar/Wind Harmer
0.639
316317KELFORD C
Solar/Wind Harmer
0.014
3145823KELFORD
Solar/Wind Harmer
0.141
970661AG2-428 GEN
Solar/Wind Harmer
2.977
3146206CASHIE
Solar/Wind Harmer
0.14
971157AH1-035 GEN
Solar/Wind Harmer
1.687
315737AD1-076 GEN
Solar/Wind Harmer
1.808
316083AB2-161 GEN
Solar/Wind Harmer
0.002
970659AG2-427 GEN
Solar/Wind Harmer
1.483
316210AC1-098 GEN
Solar/Wind Harmer
1.296
315813AE1-149 C
Solar/Wind Harmer
7.439
3144536CHRHLND
Solar/Wind Harmer
0.021
315724AD1-057 GEN
Solar/Wind Harmer
0.519
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.888
3145963POPLR C
Solar/Wind Harmer
0.138
316327AA2-057 GEN
Solar/Wind Harmer
0.207
3145933PARMELE
Solar/Wind Harmer
0.135
966801AG1-551 GEN
Solar/Wind Harmer
1.578
3146233WITAKRS
Solar/Wind Harmer
0.679
3146233WITAKRS
Solar/Wind Harmer
0.092
3138543CONSLDL
Solar/Wind Harmer
0.089
3145746EVERETS
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
0.134
970221AG2-151 GEN
Solar/Wind Harmer
7.167
3146073TAR RVR
Solar/Wind Harmer
0.134
3146083TARBORO
Solar/Wind Harmer
0.134
3145543BTLEBRO
Solar/Wind Harmer
0.134
3145543BTLEBRO
Solar/Wind Harmer
0.134
971623AH1-311 GEN
Solar/Wind Harmer
0.267
961601AG1-000A GEN
Solar/Wind Harmer
9.498
315839AE2-212 C
Solar/Wind Harmer
0.001
3145336SMITFLD
Solar/Wind Harmer
0.053
3150861SPRUNCD
Adder
0.601
965281AG1-393 GEN
Solar/Wind Harmer
1.359
3151221GRAVEL6
Adder
9.127
3151171GRAVELC
Adder
1.756
971683AH1-343 GEN
Solar/Wind Harmer
4.614
961611AG1-000B GEN
Solar/Wind Harmer
3.281
316283AC2-100 C
Solar/Wind Harmer
0.239
3152251N ANNA1
50/50
35.378
3151791S ANNAG2
50/50
1.098
3151781S ANNAS1
50/50
0.564
3151741LOISA C
50/50
1.127
3151751LOISA D
50/50
20.602
970119AG2-088 GEN
50/50
29.412
315243AE2-183_GT3
50/50
3.266
3151051BRUNSWICKS1
50/50
5.329
3151021BRUNSWICKG1
50/50
2.568
971451AH1-221 GEN
50/50
7.799
316045AC1-158 PL2
Solar/Wind Harmer
11.495
3147666LOUISA
Solar/Wind Harmer
1.947
316192AB2-158 GEN
Solar/Wind Harmer
2.693
316254AC1-120 GEN1
Solar/Wind Harmer
0.471
3143226MDLTHAN
Solar/Wind Harmer
0.22
940641AE2-051 GEN
Solar/Wind Harmer
15.946
3143336POWHATN
Solar/Wind Harmer
3.398
970919AG2-571 GEN
Solar/Wind Harmer
6.642
970087AG2-069 GEN
Solar/Wind Harmer
14.871
939411AE1-173 GEN
Solar/Wind Harmer
79.115
316336AC2-165 C
Solar/Wind Harmer
0.007
3143526WINTERP
Solar/Wind Harmer
0.921
957481AF2-042 GEN
Solar/Wind Harmer
47.237
315693AD1-088 GEN
Solar/Wind Harmer
8.323
962491AG1-098 GEN
Solar/Wind Harmer
9.868
315778AD1-151 GEN
Solar/Wind Harmer
9.406
970129AG2-093 GEN
Solar/Wind Harmer
6.948
315683AE1-153 C
Solar/Wind Harmer
13.39
970937AG2-583 GEN
Solar/Wind Harmer
10.032
3146926FARMVIL
Solar/Wind Harmer
0.095
315687AD1-152 GEN
Solar/Wind Harmer
0.005
963171AG1-166 GEN
Solar/Wind Harmer
0.823
971563AH1-280 GEN
Solar/Wind Harmer
1.646
3144293JTRSVLE
Adder
0.491
316023GEN1_S
Solar/Wind Harmer
0.345
970685AG2-442 GEN
Solar/Wind Harmer
11.466
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.061
960081AF2-299 GEN
Solar/Wind Harmer
1.461
971795AH1-408 GEN
Solar/Wind Harmer
10.127
3147043LAWRENC
Adder
1.373
316237AB2-079_GEN
Solar/Wind Harmer
0.001
971065AG2-659 GEN
Solar/Wind Harmer
6.351
316129AC1-054 GEN
Solar/Wind Harmer
0.559
972003AH1-546 GEN
Solar/Wind Harmer
6.284
316011AB1-132 GEN
Solar/Wind Harmer
2.654
962571AG1-106 GEN
Solar/Wind Harmer
2.077
316190AA2-174 GEN
Solar/Wind Harmer
0
3145783HORNRTN
Solar/Wind Harmer
0.145
944591AF1-124 GEN
Solar/Wind Harmer
32.725
3145796HORNRTN
Solar/Wind Harmer
0.476
3145796HORNRTN
Solar/Wind Harmer
0.144
970401AG2-262 GEN
Solar/Wind Harmer
0.842
316388AE2-253 GEN
Solar/Wind Harmer
0.449
3146456SLIGO L269
Solar/Wind Harmer
0.143
316294AC1-161 GEN
Solar/Wind Harmer
2.482
3145893MURPHYS
Solar/Wind Harmer
0.572
3145893MURPHYS
Solar/Wind Harmer
0.636
316246AF1-032 C
Solar/Wind Harmer
0.064
3146263WOODLND
Solar/Wind Harmer
0.143
316093AE2-104_GEN
Solar/Wind Harmer
2.398
3146516WINFALL
Solar/Wind Harmer
0.461
3146516WINFALL
Solar/Wind Harmer
0.142
3146173TUNIS
Solar/Wind Harmer
0.142
316375AC2-012 GEN
Solar/Wind Harmer
0.004
3150981CHESPKA
Adder
1.776
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.142
3145683EARLEYS
Solar/Wind Harmer
0.141
3145663CRESWEL
Solar/Wind Harmer
0.395
971163AH1-040 GEN
Solar/Wind Harmer
11.283
3145823KELFORD
Solar/Wind Harmer
0.141
970661AG2-428 GEN
Solar/Wind Harmer
13.998
3146206CASHIE
Solar/Wind Harmer
0.14
971547AH1-271 GEN
Solar/Wind Harmer
3
316381AD1-082 GEN
Solar/Wind Harmer
0.146
970659AG2-427 GEN
Solar/Wind Harmer
6.78
316212AC1-099_GEN
Solar/Wind Harmer
0.722
315722AD1-056 GEN
Solar/Wind Harmer
0.876
3145963POPLR C
Solar/Wind Harmer
0.138
316174AB2-169 GEN
Solar/Wind Harmer
0.004
316072AD1-144
Solar/Wind Harmer
0.05
3146293MARTNCO
Solar/Wind Harmer
0.126
3146233WITAKRS
Solar/Wind Harmer
0.538
3145746EVERETS
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
0.134
971377AH1-170 GEN
Solar/Wind Harmer
1.433
3147623JAMES R
Solar/Wind Harmer
0.311
316494AC1-189 GEN
Solar/Wind Harmer
0.453
961671AG1-007 GEN
Solar/Wind Harmer
0.02
3146083TARBORO
Solar/Wind Harmer
0.134
3145493TOT1
Solar/Wind Harmer
0.595
3145543BTLEBRO
Solar/Wind Harmer
0.134
3145543BTLEBRO
Solar/Wind Harmer
0.107
316359AB2-059 GEN
Solar/Wind Harmer
0.48
316049AB1-081 GEN
Solar/Wind Harmer
0.765
3142053HEARTS
Solar/Wind Harmer
0.235
3145336SMITFLD
Solar/Wind Harmer
0.528
316003AC1-222 GEN
Solar/Wind Harmer
0.003
3150851SPRUNCC
Adder
0.601
3151171GRAVELC
Adder
1.335
315671AE2-027_GEN
Solar/Wind Harmer
7.939
961611AG1-000B GEN
Solar/Wind Harmer
6.453
971647AH1-324 GEN
Solar/Wind Harmer
5.166
971069AG2-661 GEN
Solar/Wind Harmer
2.09
316458AB2-190 GEN2
Solar/Wind Harmer
0.619
970129AG2-093 GEN
Solar/Wind Harmer
3.27
316303AF2-085
50/50
3.922
315244AE2-183_ST
50/50
5.646
963041AG1-153 GEN
50/50
5.199
316164AC1-076 GEN
Solar/Wind Harmer
0.44
3147346CASHSCORNER
Solar/Wind Harmer
0.637
941031AE2-094 GEN
Solar/Wind Harmer
37.541
944011AF1-069 GEN
Solar/Wind Harmer
12.266
970673AG2-436 GEN
Solar/Wind Harmer
42.616
970673AG2-436 GEN
Solar/Wind Harmer
28.411
971967AH1-528 GEN
Solar/Wind Harmer
31.505
970085AG2-068 GEN
Solar/Wind Harmer
9.914
970581AG2-369 GEN
Solar/Wind Harmer
8.526
316233AE1-074 FULL
Solar/Wind Harmer
0.142
971281AH1-106 GEN
Solar/Wind Harmer
2.458
971283AH1-107 GEN
Solar/Wind Harmer
2.458
316315AB2-025 C
Solar/Wind Harmer
0.135
315814AE2-033 C
Solar/Wind Harmer
13.201
315657AE1-056 GEN
Solar/Wind Harmer
5.34
946301AF1-294 GEN
Solar/Wind Harmer
3.045
961791AG1-021 GEN
Solar/Wind Harmer
1.481
970285AG2-188 GEN
Solar/Wind Harmer
12.195
970683AG2-441 GEN
Solar/Wind Harmer
10.238
970681AG2-440 GEN
Solar/Wind Harmer
8.19
971845AH1-439 GEN
Solar/Wind Harmer
6.951
3144303KENBRDG
Solar/Wind Harmer
0.122
971443AH1-215 GEN
Solar/Wind Harmer
2.566
3143316POE
Solar/Wind Harmer
0.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316087AB2-174 GEN
Solar/Wind Harmer
0.004
970831AG2-522 GEN
Solar/Wind Harmer
6.33
3137643SOCKMAN
Solar/Wind Harmer
0.589
972205AH1-687 GEN
Adder
6.271
315652AC1-086 GEN
Solar/Wind Harmer
16.059
315607AA1-063A GEN
Solar/Wind Harmer
0.296
3146043SEABORD
Solar/Wind Harmer
0.145
3145796HORNRTN
Solar/Wind Harmer
0.461
3145796HORNRTN
Solar/Wind Harmer
0.058
965291AG1-394 GEN
Solar/Wind Harmer
0.639
957871AF2-081 GEN
Solar/Wind Harmer
7.137
319010AE1-072 C
Solar/Wind Harmer
0.721
3146406KITTY HAWK
Solar/Wind Harmer
0.018
3145893MURPHYS
Solar/Wind Harmer
0.386
3145893MURPHYS
Solar/Wind Harmer
0.143
313526AB2-022
Solar/Wind Harmer
0.077
316305AF2-043 C
Solar/Wind Harmer
0.001
316321Z2-027
Solar/Wind Harmer
0.027
3146396TANGLEW
Solar/Wind Harmer
0.393
3145176PASQUOTANK
Solar/Wind Harmer
0.088
3151081ELIZAR1
Adder
13.069
3151091ELIZAR2
Adder
12.842
3146486SUNBURY
Solar/Wind Harmer
0.142
3146486SUNBURY
Solar/Wind Harmer
0.142
315835AF2-110_GEN
Solar/Wind Harmer
0.978
3152611GOSPORTB
Adder
1.811
3152621GOSPORTC
Adder
1.537
3152601GOSPORTA
Adder
1.418
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3145513AHOSKIE
Solar/Wind Harmer
0.297
3145513AHOSKIE
Solar/Wind Harmer
0.142
316311AC2-079 GEN
Solar/Wind Harmer
4.069
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.097
3130156CHOWAN
Solar/Wind Harmer
0.142
3130156CHOWAN
Solar/Wind Harmer
0.142
3145683EARLEYS
Solar/Wind Harmer
0.283
3145683EARLEYS
Solar/Wind Harmer
0.141
3145683EARLEYS
Solar/Wind Harmer
0.141
315816AE2-034 GEN
Solar/Wind Harmer
0.605
316118AC1-105 GEN
Solar/Wind Harmer
0.363
3146206CASHIE
Solar/Wind Harmer
0.14
970601AG2-382 GEN
Solar/Wind Harmer
5.25
3130546PLYMOUTH
Solar/Wind Harmer
0.14
315732AD1-074 GEN1
Solar/Wind Harmer
0.807
315733AD1-074 GEN2
Solar/Wind Harmer
0.807
315735AD1-075 GEN1
Solar/Wind Harmer
0.404
3146033SCOT NK
Solar/Wind Harmer
0.56
3147173SINAI
Solar/Wind Harmer
0.138
3147243WELCO
Solar/Wind Harmer
0.086
316319Z2-044 C
Solar/Wind Harmer
0
316005AA1-067
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
0.535
3145746EVERETS
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
0.134
970181AG2-120 GEN
Solar/Wind Harmer
1.673
957861AF2-080 GEN
Solar/Wind Harmer
5.784
316420AA1-050 GEN
Solar/Wind Harmer
0.004
3145573BETHELC
Solar/Wind Harmer
0.134
3145573BETHELC
Solar/Wind Harmer
0.134
971445AH1-216 GEN
Solar/Wind Harmer
9.249
971285AH1-108 GEN
Adder
0.983
971447AH1-217 GEN
Solar/Wind Harmer
3.898
972265AH1-717 GEN
Adder
9.747
3151201GRAVEL4
Adder
9.137
3151191GRAVEL3
Adder
9.022
3151211GRAVEL5
Adder
9.022
970865AG2-541 GEN
Solar/Wind Harmer
4.136
316369SG1_INVT
Solar/Wind Harmer
0.004
316132AB2-190 GEN1
Solar/Wind Harmer
0.619
270494AE1-108_GEN
Solar/Wind Harmer
1.368
LAGNLTFEXP_LAGN->PJM
CLTF
5.7
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.38
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.621
MECLTFEXP_MEC->PJM
CLTF
2.309
SIGELTFEXP_SIGE->PJM
CLTF
0.069
CBM South 2LTFEXP_CBM-S2->PJM
CBM
19.49
TVALTFEXP_TVA->PJM
CLTF
2.869
NYPJM->LTFIMP_NY
CLTF
2.592
LGEELTFEXP_LGEE->PJM
CLTF
0.801
WECLTFEXP_WEC->PJM
CLTF
0.384
CPLELTFEXP_CPLE->PJM
CLTF
9.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.291

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:147.45 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4748.6
MW Contribution:7.33
Bus #Bus NameTypeMW Contribution
971133AH1-012 GEN
50/50
10.162
3151731LOISA B
50/50
19.381
3151721LOISA A
50/50
19.281
970533AG2-339 GEN
50/50
19.027
970531AG2-338 GEN
50/50
7.611
315242AE2-183_GT2
50/50
3.43
315241AE2-183_GT1
50/50
3.409
972185AH1-677 GEN
50/50
12.365
3151041BRUNSWICKG3
50/50
2.697
972187AH1-678 GEN
50/50
6.189
966001AG1-469 GEN
Solar/Wind Harmer
0.142
971223AH1-071 GEN
Solar/Wind Harmer
2.468
970933AG2-581 GEN
Solar/Wind Harmer
16.076
3143526WINTERP
Solar/Wind Harmer
0.974
970099AG2-077 GEN
Solar/Wind Harmer
19.819
3144356SAPONY
Solar/Wind Harmer
1.482
971741AH1-377 GEN
Solar/Wind Harmer
17.227
970301AG2-198 GEN
Solar/Wind Harmer
7.308
3147133PAMPLIN
Solar/Wind Harmer
0.161
3147133PAMPLIN
Solar/Wind Harmer
0.129
958211AF2-115 GEN
Solar/Wind Harmer
1.931
963191AG1-168 GEN
Solar/Wind Harmer
0.644
3144293JTRSVLE
Adder
0.512
3144293JTRSVLE
Adder
0.431
316034AC1-036 C
Solar/Wind Harmer
0.012
970323AG2-213 GEN
Solar/Wind Harmer
6.815
971775AH1-396 GEN
Solar/Wind Harmer
0.256
313527AB2-043 GEN
Solar/Wind Harmer
0.002
939181AE1-148 GEN
Solar/Wind Harmer
7.578
316181AB2-040 GEN
Solar/Wind Harmer
0.229
3146776BUCKING
Solar/Wind Harmer
0.63
3146776BUCKING
Solar/Wind Harmer
0.051
3145593CAROLNA
Solar/Wind Harmer
0.154
3145593CAROLNA
Solar/Wind Harmer
0.154
966811AG1-552 GEN
Solar/Wind Harmer
1.673
3145593CAROLNA
Solar/Wind Harmer
0.192
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
3142666NORTHAMPTON
Solar/Wind Harmer
0.092
316426AA2-053 GEN
Solar/Wind Harmer
0.518
3145783HORNRTN
Solar/Wind Harmer
2.725
3145783HORNRTN
Solar/Wind Harmer
2.18
3145783HORNRTN
Solar/Wind Harmer
0.681
3145783HORNRTN
Solar/Wind Harmer
0.273
316185AD1-033 GEN
Solar/Wind Harmer
0.004
3145506HICKORY
Solar/Wind Harmer
0.612
3145506HICKORY
Solar/Wind Harmer
0.367
3145506HICKORY
Solar/Wind Harmer
0.092
316339AD2-160 GEN
Solar/Wind Harmer
0.248
316018AA1-139 ULT2
Solar/Wind Harmer
0.004
316017AA1-139 ULT1
Solar/Wind Harmer
0.085
3137176SLIGO L2192
Solar/Wind Harmer
0.608
3146456SLIGO L269
Solar/Wind Harmer
2.703
3130086AYDLETT
Solar/Wind Harmer
0.61
3145796HORNRTN
Solar/Wind Harmer
0.458
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.146
3146386ELIZ CT
Solar/Wind Harmer
0.152
315742AE1-103 GEN
Solar/Wind Harmer
0.002
3152261N ANNA2
50/50
36.457
3151771S ANNAG1
50/50
1.04
3151801S ANNAS2
50/50
0.534
3151761LOISA E
50/50
39.513
972183AH1-676 GEN
50/50
307.587
3151031BRUNSWICKG2
50/50
2.697
3147666LOUISA
Solar/Wind Harmer
1.117
316313AB2-026
Solar/Wind Harmer
0.125
316258AE1-075 C
Solar/Wind Harmer
0.15
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
3.006
970917AG2-570 GEN
Solar/Wind Harmer
17.445
316478AD1-087 GEN
Solar/Wind Harmer
0.619
316486AD2-202 GEN
Solar/Wind Harmer
0.182
970909AG2-566 GEN
Solar/Wind Harmer
1.827
3146926FARMVIL
Solar/Wind Harmer
0.098
316365GEN2_N
Solar/Wind Harmer
0.365
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3147133PAMPLIN
Solar/Wind Harmer
0.506
3152251N ANNA1
50/50
36.46
3151791S ANNAG2
50/50
1.04
3151781S ANNAS1
50/50
0.534
3151741LOISA C
50/50
1.06
3151751LOISA D
50/50
19.381
970119AG2-088 GEN
50/50
30.855
315243AE2-183_GT3
50/50
3.43
3151051BRUNSWICKS1
50/50
5.597
3151021BRUNSWICKG1
50/50
2.697
971451AH1-221 GEN
50/50
8.191
3147666LOUISA
Solar/Wind Harmer
1.943
316192AB2-158 GEN
Solar/Wind Harmer
2.682
3143226MDLTHAN
Solar/Wind Harmer
0.231
940641AE2-051 GEN
Solar/Wind Harmer
16.781
3143336POWHATN
Solar/Wind Harmer
3.536
970919AG2-571 GEN
Solar/Wind Harmer
6.978
939411AE1-173 GEN
Solar/Wind Harmer
83.474
970087AG2-069 GEN
Solar/Wind Harmer
15.624
316336AC2-165 C
Solar/Wind Harmer
0.007
3143526WINTERP
Solar/Wind Harmer
0.974
957481AF2-042 GEN
Solar/Wind Harmer
49.548
315693AD1-088 GEN
Solar/Wind Harmer
8.718
962491AG1-098 GEN
Solar/Wind Harmer
10.335
970937AG2-583 GEN
Solar/Wind Harmer
10.339
315687AD1-152 GEN
Solar/Wind Harmer
0.005
3146926FARMVIL
Solar/Wind Harmer
0.098
316023GEN1_S
Solar/Wind Harmer
0.365
963171AG1-166 GEN
Solar/Wind Harmer
0.858
971563AH1-280 GEN
Solar/Wind Harmer
1.716
3144293JTRSVLE
Adder
0.512
960081AF2-299 GEN
Solar/Wind Harmer
1.543
316303AF2-085
50/50
4.114
315244AE2-183_ST
50/50
5.93
963041AG1-153 GEN
50/50
5.461
3147346CASHSCORNER
Solar/Wind Harmer
0.597
941031AE2-094 GEN
Solar/Wind Harmer
39.425
944011AF1-069 GEN
Solar/Wind Harmer
12.882
970673AG2-436 GEN
Solar/Wind Harmer
44.756
970685AG2-442 GEN
Solar/Wind Harmer
11.971
971795AH1-408 GEN
Solar/Wind Harmer
10.682
3147043LAWRENC
Adder
1.448
316237AB2-079_GEN
Solar/Wind Harmer
0.001
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.063
971065AG2-659 GEN
Solar/Wind Harmer
6.688
316129AC1-054 GEN
Solar/Wind Harmer
0.589
316011AB1-132 GEN
Solar/Wind Harmer
2.809
962571AG1-106 GEN
Solar/Wind Harmer
2.198
944591AF1-124 GEN
Solar/Wind Harmer
34.895
316190AA2-174 GEN
Solar/Wind Harmer
0
3145783HORNRTN
Solar/Wind Harmer
0.153
316388AE2-253 GEN
Solar/Wind Harmer
0.479
316294AC1-161 GEN
Solar/Wind Harmer
2.649
3146456SLIGO L269
Solar/Wind Harmer
0.153
3145796HORNRTN
Solar/Wind Harmer
0.503
3145796HORNRTN
Solar/Wind Harmer
0.152
315683AE1-153 C
Solar/Wind Harmer
12.128
316246AF1-032 C
Solar/Wind Harmer
0.069
316093AE2-104_GEN
Solar/Wind Harmer
2.556
316375AC2-012 GEN
Solar/Wind Harmer
0.004
3150981CHESPKA
Adder
1.895
3145893MURPHYS
Solar/Wind Harmer
0.607
3145893MURPHYS
Solar/Wind Harmer
0.674
3146516WINFALL
Solar/Wind Harmer
0.491
3146516WINFALL
Solar/Wind Harmer
0.152
972003AH1-546 GEN
Solar/Wind Harmer
6.434
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3146263WOODLND
Solar/Wind Harmer
0.151
3146173TUNIS
Solar/Wind Harmer
0.151
3130156CHOWAN
Solar/Wind Harmer
0.151
970401AG2-262 GEN
Solar/Wind Harmer
0.884
970661AG2-428 GEN
Solar/Wind Harmer
14.943
3145683EARLEYS
Solar/Wind Harmer
0.15
3145663CRESWEL
Solar/Wind Harmer
0.42
971163AH1-040 GEN
Solar/Wind Harmer
11.998
316381AD1-082 GEN
Solar/Wind Harmer
0.156
970659AG2-427 GEN
Solar/Wind Harmer
7.24
3146206CASHIE
Solar/Wind Harmer
0.149
971547AH1-271 GEN
Solar/Wind Harmer
3.186
3145823KELFORD
Solar/Wind Harmer
0.149
316212AC1-099_GEN
Solar/Wind Harmer
0.765
316072AD1-144
Solar/Wind Harmer
0.053
315722AD1-056 GEN
Solar/Wind Harmer
0.927
3145963POPLR C
Solar/Wind Harmer
0.146
316174AB2-169 GEN
Solar/Wind Harmer
0.004
3146293MARTNCO
Solar/Wind Harmer
0.133
3146233WITAKRS
Solar/Wind Harmer
0.569
3145746EVERETS
Solar/Wind Harmer
0.142
3145746EVERETS
Solar/Wind Harmer
0.142
316494AC1-189 GEN
Solar/Wind Harmer
0.48
961671AG1-007 GEN
Solar/Wind Harmer
0.022
3146083TARBORO
Solar/Wind Harmer
0.142
3145493TOT1
Solar/Wind Harmer
0.63
3145336SMITFLD
Solar/Wind Harmer
0.565
3145543BTLEBRO
Solar/Wind Harmer
0.141
3145543BTLEBRO
Solar/Wind Harmer
0.113
316359AB2-059 GEN
Solar/Wind Harmer
0.508
316049AB1-081 GEN
Solar/Wind Harmer
0.809
3142053HEARTS
Solar/Wind Harmer
0.249
3150851SPRUNCC
Adder
0.645
316003AC1-222 GEN
Solar/Wind Harmer
0.004
971377AH1-170 GEN
Solar/Wind Harmer
1.465
3147623JAMES R
Solar/Wind Harmer
0.318
3151171GRAVELC
Adder
1.435
315671AE2-027_GEN
Solar/Wind Harmer
8.542
961611AG1-000B GEN
Solar/Wind Harmer
6.943
971647AH1-324 GEN
Solar/Wind Harmer
5.564
971069AG2-661 GEN
Solar/Wind Harmer
2.256
316458AB2-190 GEN2
Solar/Wind Harmer
0.669
970129AG2-093 GEN
Solar/Wind Harmer
3.534
3138126ROCKLANDING
Solar/Wind Harmer
0.055
3142543TWELFTH
Solar/Wind Harmer
0.011
970673AG2-436 GEN
Solar/Wind Harmer
29.837
971967AH1-528 GEN
Solar/Wind Harmer
33.079
970085AG2-068 GEN
Solar/Wind Harmer
10.416
970581AG2-369 GEN
Solar/Wind Harmer
8.958
316233AE1-074 FULL
Solar/Wind Harmer
0.15
971281AH1-106 GEN
Solar/Wind Harmer
2.6
971283AH1-107 GEN
Solar/Wind Harmer
2.6
316315AB2-025 C
Solar/Wind Harmer
0.143
315814AE2-033 C
Solar/Wind Harmer
13.959
315657AE1-056 GEN
Solar/Wind Harmer
5.562
946301AF1-294 GEN
Solar/Wind Harmer
3.175
961791AG1-021 GEN
Solar/Wind Harmer
1.544
3143316POE
Solar/Wind Harmer
0.635
970683AG2-441 GEN
Solar/Wind Harmer
10.688
970681AG2-440 GEN
Solar/Wind Harmer
8.55
3144303KENBRDG
Solar/Wind Harmer
0.128
971443AH1-215 GEN
Solar/Wind Harmer
2.682
970285AG2-188 GEN
Solar/Wind Harmer
12.58
316087AB2-174 GEN
Solar/Wind Harmer
0.005
971845AH1-439 GEN
Solar/Wind Harmer
7.164
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
970831AG2-522 GEN
Solar/Wind Harmer
6.67
3137643SOCKMAN
Solar/Wind Harmer
0.622
315652AC1-086 GEN
Solar/Wind Harmer
16.994
315607AA1-063A GEN
Solar/Wind Harmer
0.314
3146043SEABORD
Solar/Wind Harmer
0.153
957871AF2-081 GEN
Solar/Wind Harmer
7.61
319010AE1-072 C
Solar/Wind Harmer
0.769
3146406KITTY HAWK
Solar/Wind Harmer
0.019
3145796HORNRTN
Solar/Wind Harmer
0.488
3145796HORNRTN
Solar/Wind Harmer
0.061
965291AG1-394 GEN
Solar/Wind Harmer
0.678
313526AB2-022
Solar/Wind Harmer
0.082
316305AF2-043 C
Solar/Wind Harmer
0.001
3151081ELIZAR1
Adder
13.946
3151091ELIZAR2
Adder
13.704
316321Z2-027
Solar/Wind Harmer
0.028
3146396TANGLEW
Solar/Wind Harmer
0.419
3145176PASQUOTANK
Solar/Wind Harmer
0.094
315835AF2-110_GEN
Solar/Wind Harmer
1.043
3146486SUNBURY
Solar/Wind Harmer
0.152
3146486SUNBURY
Solar/Wind Harmer
0.152
3152611GOSPORTB
Adder
1.933
3152621GOSPORTC
Adder
1.641
3152601GOSPORTA
Adder
1.513
3145893MURPHYS
Solar/Wind Harmer
0.41
3145893MURPHYS
Solar/Wind Harmer
0.152
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
316311AC2-079 GEN
Solar/Wind Harmer
4.34
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.104
3130156CHOWAN
Solar/Wind Harmer
0.151
3130156CHOWAN
Solar/Wind Harmer
0.151
3145513AHOSKIE
Solar/Wind Harmer
0.314
3145513AHOSKIE
Solar/Wind Harmer
0.15
972205AH1-687 GEN
Adder
6.411
3145683EARLEYS
Solar/Wind Harmer
0.3
3145683EARLEYS
Solar/Wind Harmer
0.15
3145683EARLEYS
Solar/Wind Harmer
0.15
315816AE2-034 GEN
Solar/Wind Harmer
0.644
316036AC1-147 C
Solar/Wind Harmer
0.028
3150991CHESPKB
Adder
1.59
3150991CHESPKB
Adder
1.552
962561AG1-105 GEN
Solar/Wind Harmer
7.287
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3145893MURPHYS
Solar/Wind Harmer
1.015
3145893MURPHYS
Solar/Wind Harmer
0.273
3146516WINFALL
Solar/Wind Harmer
0.152
3146516WINFALL
Solar/Wind Harmer
0.152
3146516WINFALL
Solar/Wind Harmer
0.152
3146626S HERTFORD
Solar/Wind Harmer
0.151
3146626S HERTFORD
Solar/Wind Harmer
0.151
3146173TUNIS
Solar/Wind Harmer
0.151
3146173TUNIS
Solar/Wind Harmer
0.151
3146376EDENTON
Solar/Wind Harmer
0.67
3146376EDENTON
Solar/Wind Harmer
0.67
964791AG1-342 GEN
Solar/Wind Harmer
2.892
3146843MT LREL
Solar/Wind Harmer
0.15
3146843MT LREL
Solar/Wind Harmer
0.15
970657AG2-426 GEN
Solar/Wind Harmer
5.253
970657AG2-426 GEN
Solar/Wind Harmer
1.101
316065AD1-022 GEN
Solar/Wind Harmer
6.875
316274AC1-208 GEN
Solar/Wind Harmer
0.769
3145933PARMELE
Solar/Wind Harmer
0.287
3145933PARMELE
Solar/Wind Harmer
0.144
3145493TOT1
Solar/Wind Harmer
0.328
3145453TOT5
Solar/Wind Harmer
0.197
3145603CNETO
Solar/Wind Harmer
0.131
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316263AC1-034 GEN
Solar/Wind Harmer
5.37
961601AG1-000A GEN
Solar/Wind Harmer
2.512
971489AH1-241 GEN
Solar/Wind Harmer
7.325
316240AF1-291 C
Solar/Wind Harmer
0.001
316222AC1-221 GEN
Solar/Wind Harmer
0.537
316033AB2-134 GEN
Solar/Wind Harmer
0.008
315697AD1-025 GEN
Solar/Wind Harmer
0.144
944641AF1-129 GEN
Adder
60.502
3130546PLYMOUTH
Solar/Wind Harmer
0.149
3146206CASHIE
Solar/Wind Harmer
0.149
970601AG2-382 GEN
Solar/Wind Harmer
5.575
315732AD1-074 GEN1
Solar/Wind Harmer
0.858
315733AD1-074 GEN2
Solar/Wind Harmer
0.858
315735AD1-075 GEN1
Solar/Wind Harmer
0.429
3146033SCOT NK
Solar/Wind Harmer
0.593
316118AC1-105 GEN
Solar/Wind Harmer
0.382
3147173SINAI
Solar/Wind Harmer
0.145
3147243WELCO
Solar/Wind Harmer
0.091
316319Z2-044 C
Solar/Wind Harmer
0
316005AA1-067
Solar/Wind Harmer
0.153
3145746EVERETS
Solar/Wind Harmer
0.567
3145746EVERETS
Solar/Wind Harmer
0.142
3145746EVERETS
Solar/Wind Harmer
0.142
3145746EVERETS
Solar/Wind Harmer
0.142
970181AG2-120 GEN
Solar/Wind Harmer
1.773
957861AF2-080 GEN
Solar/Wind Harmer
6.125
316420AA1-050 GEN
Solar/Wind Harmer
0.005
3145573BETHELC
Solar/Wind Harmer
0.142
3145573BETHELC
Solar/Wind Harmer
0.142
971445AH1-216 GEN
Solar/Wind Harmer
9.913
971285AH1-108 GEN
Adder
1.055
972265AH1-717 GEN
Adder
10.474
3151201GRAVEL4
Adder
9.819
3151191GRAVEL3
Adder
9.695
3151211GRAVEL5
Adder
9.695
971447AH1-217 GEN
Solar/Wind Harmer
3.983
316369SG1_INVT
Solar/Wind Harmer
0.005
970865AG2-541 GEN
Solar/Wind Harmer
4.353
316132AB2-190 GEN1
Solar/Wind Harmer
0.669
270494AE1-108_GEN
Solar/Wind Harmer
1.404
316123AC1-075 GEN
Solar/Wind Harmer
0.154
970165AG2-112 GEN
Solar/Wind Harmer
0.913
970163AG2-111 GEN
Solar/Wind Harmer
0.871
971193AH1-056 GEN
Solar/Wind Harmer
9.82
963181AG1-167 GEN
Solar/Wind Harmer
0.644
3144293JTRSVLE
Adder
0.512
3147043LAWRENC
Solar/Wind Harmer
0.096
959311AF2-222 GEN
Solar/Wind Harmer
14.213
970257AG2-171 GEN
Solar/Wind Harmer
5.111
315785AD2-033 C
Solar/Wind Harmer
1.297
964241AG1-285 GEN
Solar/Wind Harmer
10.591
316131AB2-060 GEN
Solar/Wind Harmer
0.498
313506AB2-031 GEN
Solar/Wind Harmer
0.487
3146776BUCKING
Solar/Wind Harmer
0.057
944581AF1-123 GEN
Solar/Wind Harmer
34.771
944601AF1-125 GEN
Solar/Wind Harmer
34.236
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
3132273ORANGE
Solar/Wind Harmer
0.031
315773AC2-141 GEN
Solar/Wind Harmer
5.584
3146456SLIGO L269
Solar/Wind Harmer
0.153
971153AH1-033 GEN
Solar/Wind Harmer
1.766
3145796HORNRTN
Solar/Wind Harmer
0.61
3145796HORNRTN
Solar/Wind Harmer
0.152
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
316320Y1-086
Solar/Wind Harmer
0.001
3151101ELIZAR3
Adder
14.124
3145273HOLLAND
Solar/Wind Harmer
0.114
3144873MCLAUGH
Solar/Wind Harmer
0.004
316435W1029_GEN3
Solar/Wind Harmer
0.001
3145893MURPHYS
Solar/Wind Harmer
0.254
3145893MURPHYS
Solar/Wind Harmer
0.152
3146516WINFALL
Solar/Wind Harmer
0.152
3146626S HERTFORD
Solar/Wind Harmer
0.151
957521AF2-046 GEN
Solar/Wind Harmer
11.271
961681AG1-008 GEN
Solar/Wind Harmer
11.271
3146263WOODLND
Solar/Wind Harmer
0.151
3146173TUNIS
Solar/Wind Harmer
0.151
3146376EDENTON
Solar/Wind Harmer
0.151
316463AE2-346 GEN
Solar/Wind Harmer
0.129
316140AB2-099
Solar/Wind Harmer
0.054
962331AG1-082 GEN
Solar/Wind Harmer
1.604
970661AG2-428 GEN
Solar/Wind Harmer
3.178
315614AA2-178 GEN
Solar/Wind Harmer
0.858
316083AB2-161 GEN
Solar/Wind Harmer
0.002
970659AG2-427 GEN
Solar/Wind Harmer
1.584
3156021HOLLOMANSOL
Solar/Wind Harmer
0.678
971157AH1-035 GEN
Solar/Wind Harmer
1.793
3146206CASHIE
Solar/Wind Harmer
0.149
315737AD1-076 GEN
Solar/Wind Harmer
1.921
316317KELFORD C
Solar/Wind Harmer
0.014
3145823KELFORD
Solar/Wind Harmer
0.149
315813AE1-149 C
Solar/Wind Harmer
7.948
3144536CHRHLND
Solar/Wind Harmer
0.022
316210AC1-098 GEN
Solar/Wind Harmer
1.371
315724AD1-057 GEN
Solar/Wind Harmer
0.549
3145963POPLR C
Solar/Wind Harmer
0.146
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
6.188
316327AA2-057 GEN
Solar/Wind Harmer
0.219
3145933PARMELE
Solar/Wind Harmer
0.144
966801AG1-551 GEN
Solar/Wind Harmer
1.673
3146233WITAKRS
Solar/Wind Harmer
0.718
3146233WITAKRS
Solar/Wind Harmer
0.097
3138543CONSLDL
Solar/Wind Harmer
0.094
3145746EVERETS
Solar/Wind Harmer
0.142
3145746EVERETS
Solar/Wind Harmer
0.142
315839AE2-212 C
Solar/Wind Harmer
0.001
3146073TAR RVR
Solar/Wind Harmer
0.142
3146083TARBORO
Solar/Wind Harmer
0.142
3145336SMITFLD
Solar/Wind Harmer
0.057
3145543BTLEBRO
Solar/Wind Harmer
0.141
3145543BTLEBRO
Solar/Wind Harmer
0.141
971623AH1-311 GEN
Solar/Wind Harmer
0.283
961601AG1-000A GEN
Solar/Wind Harmer
10.046
3150861SPRUNCD
Adder
0.645
970221AG2-151 GEN
Solar/Wind Harmer
7.325
965281AG1-393 GEN
Solar/Wind Harmer
1.459
3151221GRAVEL6
Adder
9.808
3151171GRAVELC
Adder
1.887
961611AG1-000B GEN
Solar/Wind Harmer
3.53
971683AH1-343 GEN
Solar/Wind Harmer
4.854
316283AC2-100 C
Solar/Wind Harmer
0.252
315778AD1-151 GEN
Solar/Wind Harmer
10.15
970129AG2-093 GEN
Solar/Wind Harmer
7.509
3144216WINCHST
Adder
0.455
970133AG2-095 GEN
Solar/Wind Harmer
1.157
3150921YORKTN3
Adder
2.978
LAGNLTFEXP_LAGN->PJM
CLTF
6.172
CBM West 1LTFEXP_CBM-W1->PJM
CBM
14.582
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.459
MECLTFEXP_MEC->PJM
CLTF
2.598
SIGELTFEXP_SIGE->PJM
CLTF
0.077
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.668
TVALTFEXP_TVA->PJM
CLTF
3.105
NYPJM->LTFIMP_NY
CLTF
2.601
LGEELTFEXP_LGEE->PJM
CLTF
0.913
WECLTFEXP_WEC->PJM
CLTF
0.444
CPLELTFEXP_CPLE->PJM
CLTF
9.633
CBM West 2LTFEXP_CBM-W2->PJM
CBM
31.022

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:172.64 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5559.88
MW Contribution:8.42
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
20.321
970119AG2-088 GEN
50/50
35.422
3150851SPRUNCC
50/50
1.216
3143096IRON208
50/50
1.078
3152331SURRY 2
50/50
9.99
3150771HOPHCF1
50/50
0.977
3143226MDLTHAN
Solar/Wind Harmer
0.265
3143526WINTERP
Solar/Wind Harmer
1.342
3147666LOUISA
Solar/Wind Harmer
1.028
316192AB2-158 GEN
Solar/Wind Harmer
1.415
940641AE2-051 GEN
Solar/Wind Harmer
19.964
939411AE1-173 GEN
Solar/Wind Harmer
105.426
3142543TWELFTH
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
4.211
315671AE2-027_GEN
Solar/Wind Harmer
15.496
944591AF1-124 GEN
Solar/Wind Harmer
54.408
970129AG2-093 GEN
Solar/Wind Harmer
6.846
316458AB2-190 GEN2
Solar/Wind Harmer
1.291
971069AG2-661 GEN
Solar/Wind Harmer
4.274
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
3
970659AG2-427 GEN
Solar/Wind Harmer
11.613
971647AH1-324 GEN
Solar/Wind Harmer
10.242
3145336SMITFLD
Solar/Wind Harmer
0.959
316381AD1-082 GEN
Solar/Wind Harmer
0.25
944631AF1-128 GEN
Adder
114.357
961611AG1-000B GEN
Solar/Wind Harmer
12.579
3151171GRAVELC
Adder
2.549
970661AG2-428 GEN
Solar/Wind Harmer
23.801
316388AE2-253 GEN
Solar/Wind Harmer
0.747
3146456SLIGO L269
Solar/Wind Harmer
0.238
3142416OLDCHRC
Solar/Wind Harmer
0.618
3142416OLDCHRC
Solar/Wind Harmer
0.237
316072AD1-144
Solar/Wind Harmer
0.086
3138126ROCKLANDING
Solar/Wind Harmer
0.109
316246AF1-032 C
Solar/Wind Harmer
0.107
316159AE1-175 C
Solar/Wind Harmer
0.205
316093AE2-104_GEN
Solar/Wind Harmer
3.974
971317AH1-138 GEN
Solar/Wind Harmer
1.762
3146516WINFALL
Solar/Wind Harmer
0.754
3146516WINFALL
Solar/Wind Harmer
0.233
3142433PROV 92
Solar/Wind Harmer
0.928
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
971777AH1-397 GEN
Solar/Wind Harmer
0.6
3141843SHACKLE
Adder
1.16
3143336POWHATN
Solar/Wind Harmer
4.034
3130156CHOWAN
Solar/Wind Harmer
0.227
3141766HARMONY
Solar/Wind Harmer
0.045
970919AG2-571 GEN
Solar/Wind Harmer
8.004
966881AG1-559 GEN
Solar/Wind Harmer
0.26
970087AG2-069 GEN
Solar/Wind Harmer
17.934
3145663CRESWEL
Solar/Wind Harmer
0.622
971163AH1-040 GEN
Solar/Wind Harmer
17.772
3138133OCRAN
Solar/Wind Harmer
0.133
316023GEN1_S
Solar/Wind Harmer
0.489
972197AH1-683 GEN
Adder
4.553
972219AH1-694 GEN
Adder
3.278
316336AC2-165 C
Solar/Wind Harmer
0.008
3146206CASHIE
Solar/Wind Harmer
0.216
971547AH1-271 GEN
Solar/Wind Harmer
4.607
3145893MURPHYS
Solar/Wind Harmer
0.862
3145893MURPHYS
Solar/Wind Harmer
0.958
957481AF2-042 GEN
Solar/Wind Harmer
57.247
3146173TUNIS
Solar/Wind Harmer
0.213
960081AF2-299 GEN
Solar/Wind Harmer
2.041
962861AG1-135 GEN
Solar/Wind Harmer
6.774
3145683EARLEYS
Solar/Wind Harmer
0.211
3146263WOODLND
Solar/Wind Harmer
0.21
315693AD1-088 GEN
Solar/Wind Harmer
10.091
962491AG1-098 GEN
Solar/Wind Harmer
11.959
316011AB1-132 GEN
Solar/Wind Harmer
3.796
962571AG1-106 GEN
Solar/Wind Harmer
2.971
971795AH1-408 GEN
Solar/Wind Harmer
13.893
3145963POPLR C
Solar/Wind Harmer
0.208
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.208
3141726DUNNSVL
Solar/Wind Harmer
0.83
316174AB2-169 GEN
Solar/Wind Harmer
0.006
3147043LAWRENC
Adder
1.868
3145783HORNRTN
Solar/Wind Harmer
0.206
3145796HORNRTN
Solar/Wind Harmer
0.678
3145796HORNRTN
Solar/Wind Harmer
0.206
3150351NORNECKC2
Adder
2.04
316212AC1-099_GEN
Solar/Wind Harmer
1.038
3146293MARTNCO
Solar/Wind Harmer
0.185
316129AC1-054 GEN
Solar/Wind Harmer
0.746
971065AG2-659 GEN
Solar/Wind Harmer
8.434
3145746EVERETS
Solar/Wind Harmer
0.196
3145746EVERETS
Solar/Wind Harmer
0.196
315722AD1-056 GEN
Solar/Wind Harmer
1.237
316337AD2-073 GEN
Solar/Wind Harmer
0.169
315687AD1-152 GEN
Solar/Wind Harmer
0.006
316494AC1-189 GEN
Solar/Wind Harmer
0.651
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970937AG2-583 GEN
Solar/Wind Harmer
11.696
970685AG2-442 GEN
Solar/Wind Harmer
14.234
3146233WITAKRS
Solar/Wind Harmer
0.757
961671AG1-007 GEN
Solar/Wind Harmer
0.029
3146083TARBORO
Solar/Wind Harmer
0.19
3145493TOT1
Solar/Wind Harmer
0.845
963171AG1-166 GEN
Solar/Wind Harmer
1.014
971563AH1-280 GEN
Solar/Wind Harmer
2.028
3144293JTRSVLE
Adder
0.605
3146926FARMVIL
Solar/Wind Harmer
0.113
3145543BTLEBRO
Solar/Wind Harmer
0.187
3145543BTLEBRO
Solar/Wind Harmer
0.149
316359AB2-059 GEN
Solar/Wind Harmer
0.672
316049AB1-081 GEN
Solar/Wind Harmer
1.07
3142053HEARTS
Solar/Wind Harmer
0.329
970401AG2-262 GEN
Solar/Wind Harmer
1.071
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.072
972003AH1-546 GEN
Solar/Wind Harmer
7.247
316003AC1-222 GEN
Solar/Wind Harmer
0.004
972135AH1-637 GEN
Solar/Wind Harmer
1.431
971377AH1-170 GEN
Solar/Wind Harmer
1.683
3147623JAMES R
Solar/Wind Harmer
0.366
972277AH1-723 GEN
Adder
87.353
971133AH1-012 GEN
50/50
5.491
944641AF1-129 GEN
50/50
122.767
970533AG2-339 GEN
50/50
21.564
970531AG2-338 GEN
50/50
8.626
3142366NRTHEST
50/50
0.836
3150781HOPHCF2
50/50
0.977
3150791HOPHCF3
50/50
0.977
3150761HOPPOLC
50/50
0.62
971213AH1-066 GEN
50/50
0.857
971223AH1-071 GEN
Solar/Wind Harmer
2.834
3143526WINTERP
Solar/Wind Harmer
1.342
316240AF1-291 C
Solar/Wind Harmer
0.002
3150691DARBY 3
Adder
17.296
3150701DARBY 4
Adder
17.255
3150681DARBY 2
Adder
17.235
3150671DARBY 1
Adder
17.215
316036AC1-147 C
Solar/Wind Harmer
0.045
3150991CHESPKB
Adder
2.516
3150991CHESPKB
Adder
2.456
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.27
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.23
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316185AD1-033 GEN
Solar/Wind Harmer
0.007
970657AG2-426 GEN
Solar/Wind Harmer
8.395
970657AG2-426 GEN
Solar/Wind Harmer
1.76
3142296MT RD221
Adder
0.763
3145506HICKORY
Solar/Wind Harmer
0.957
3145506HICKORY
Solar/Wind Harmer
0.574
3145506HICKORY
Solar/Wind Harmer
0.144
3142946ENON
Solar/Wind Harmer
0.024
316339AD2-160 GEN
Solar/Wind Harmer
0.387
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.133
3137176SLIGO L2192
Solar/Wind Harmer
0.946
3146456SLIGO L269
Solar/Wind Harmer
4.208
3130086AYDLETT
Solar/Wind Harmer
0.95
316075AC2-137 C
Solar/Wind Harmer
0.065
972185AH1-677 GEN
Adder
13.26
3144356SAPONY
Solar/Wind Harmer
1.973
3146386ELIZ CT
Solar/Wind Harmer
0.235
972187AH1-678 GEN
Adder
6.65
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.233
3146516WINFALL
Solar/Wind Harmer
0.233
3146516WINFALL
Solar/Wind Harmer
0.233
3146626S HERTFORD
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
0.231
966871AG1-558 GEN
Solar/Wind Harmer
0.266
970933AG2-581 GEN
Solar/Wind Harmer
18.37
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
1.008
3146376EDENTON
Solar/Wind Harmer
1.008
957411AF2-035 GEN
Solar/Wind Harmer
9.597
970317AG2-208 GEN
Solar/Wind Harmer
8.892
315673AE1-157 GEN
Solar/Wind Harmer
15.364
3150391LDYSMT3
Adder
29.101
972195AH1-682 GEN
Adder
3.824
316065AD1-022 GEN
Solar/Wind Harmer
9.976
3145893MURPHYS
Solar/Wind Harmer
1.442
3145893MURPHYS
Solar/Wind Harmer
0.388
970099AG2-077 GEN
Solar/Wind Harmer
22.899
3146173TUNIS
Solar/Wind Harmer
0.213
3146173TUNIS
Solar/Wind Harmer
0.213
958261AF2-120 GEN
Solar/Wind Harmer
6.97
316181AB2-040 GEN
Solar/Wind Harmer
0.305
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.126
316426AA2-053 GEN
Solar/Wind Harmer
0.702
3145593CAROLNA
Solar/Wind Harmer
0.207
3145593CAROLNA
Solar/Wind Harmer
0.207
966811AG1-552 GEN
Solar/Wind Harmer
2.246
3145593CAROLNA
Solar/Wind Harmer
0.258
3145783HORNRTN
Solar/Wind Harmer
3.66
3145783HORNRTN
Solar/Wind Harmer
2.928
3145783HORNRTN
Solar/Wind Harmer
0.915
3145783HORNRTN
Solar/Wind Harmer
0.366
3145796HORNRTN
Solar/Wind Harmer
0.617
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.143
3150341NORNECKC1
Adder
2.126
971741AH1-377 GEN
Solar/Wind Harmer
19.869
3145933PARMELE
Solar/Wind Harmer
0.399
3145933PARMELE
Solar/Wind Harmer
0.2
316274AC1-208 GEN
Solar/Wind Harmer
1.034
316468AD1-105 GEN
Solar/Wind Harmer
-0.064
970301AG2-198 GEN
Solar/Wind Harmer
8.419
939181AE1-148 GEN
Solar/Wind Harmer
9.29
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.155
971775AH1-396 GEN
Solar/Wind Harmer
0.306
3145493TOT1
Solar/Wind Harmer
0.441
3145453TOT5
Solar/Wind Harmer
0.264
3145603CNETO
Solar/Wind Harmer
0.176
958211AF2-115 GEN
Solar/Wind Harmer
2.282
963191AG1-168 GEN
Solar/Wind Harmer
0.761
3144293JTRSVLE
Adder
0.605
3144293JTRSVLE
Adder
0.51
3147133PAMPLIN
Solar/Wind Harmer
0.19
3147133PAMPLIN
Solar/Wind Harmer
0.152
961601AG1-000A GEN
Solar/Wind Harmer
3.325
316263AC1-034 GEN
Solar/Wind Harmer
7.104
962561AG1-105 GEN
Solar/Wind Harmer
8.835
964791AG1-342 GEN
Solar/Wind Harmer
3.505
3146843MT LREL
Solar/Wind Harmer
0.182
3146843MT LREL
Solar/Wind Harmer
0.182
3146776BUCKING
Solar/Wind Harmer
0.716
3146776BUCKING
Solar/Wind Harmer
0.058
316222AC1-221 GEN
Solar/Wind Harmer
0.661
971489AH1-241 GEN
Solar/Wind Harmer
8.416
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
7.289
3151731LOISA B
Adder
8.676
3151721LOISA A
Adder
8.631
316447AC1-158 HLD
Solar/Wind Helper
11.481
3152261N ANNA2
50/50
20.32
3150861SPRUNCD
50/50
1.216
3143096IRON208
50/50
1.078
3143096IRON208
50/50
1.056
3150801HOPHCF4
50/50
1.421
971211AH1-065 GEN
50/50
1.714
3151101ELIZAR3
50/50
23.68
3151161SURRY 1
50/50
9.205
3147666LOUISA
Solar/Wind Harmer
0.591
315839AE2-212 C
Solar/Wind Harmer
0.002
315773AC2-141 GEN
Solar/Wind Harmer
8.876
965281AG1-393 GEN
Solar/Wind Harmer
2.585
315813AE1-149 C
Solar/Wind Harmer
12.873
970133AG2-095 GEN
Solar/Wind Harmer
2.314
944581AF1-123 GEN
Solar/Wind Harmer
54.216
944601AF1-125 GEN
Solar/Wind Harmer
53.381
970129AG2-093 GEN
Solar/Wind Harmer
14.547
315778AD1-151 GEN
Solar/Wind Harmer
19.233
3144536CHRHLND
Solar/Wind Harmer
0.036
3144873MCLAUGH
Solar/Wind Harmer
0.006
970659AG2-427 GEN
Solar/Wind Harmer
2.54
3145336SMITFLD
Solar/Wind Harmer
0.096
316083AB2-161 GEN
Solar/Wind Harmer
0.003
961611AG1-000B GEN
Solar/Wind Harmer
6.396
3151221GRAVEL6
Adder
17.422
3151171GRAVELC
Adder
3.352
970661AG2-428 GEN
Solar/Wind Harmer
5.062
970293AG2-193 GEN
Solar/Wind Harmer
2.548
3142946ENON
Solar/Wind Harmer
0.08
3146456SLIGO L269
Solar/Wind Harmer
0.238
971153AH1-033 GEN
Solar/Wind Harmer
2.749
3142416OLDCHRC
Solar/Wind Harmer
2.305
3144216WINCHST
Adder
0.896
3150921YORKTN3
Adder
5.966
316382AG1-145 C
Solar/Wind Harmer
0.002
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.233
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3146626S HERTFORD
Solar/Wind Harmer
0.231
3145273HOLLAND
Solar/Wind Harmer
0.173
316473AC1-191 GEN
Solar/Wind Harmer
0.778
3141843SHACKLE
Adder
1.16
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.143
316258AE1-075 C
Solar/Wind Harmer
0.171
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.429
3146376EDENTON
Solar/Wind Harmer
0.227
3141766HARMONY
Solar/Wind Harmer
3.024
316280AD1-041 GEN
Solar/Wind Harmer
0.005
316156AD2-030 GEN
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
4.011
970917AG2-570 GEN
Solar/Wind Harmer
20.009
315614AA2-178 GEN
Solar/Wind Harmer
1.271
971157AH1-035 GEN
Solar/Wind Harmer
2.623
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
316365GEN2_N
Solar/Wind Harmer
0.489
315737AD1-076 GEN
Solar/Wind Harmer
2.804
3150401LDYSMT4
Adder
29.156
3150371LDYSMT1
Adder
28.172
962971AG1-146 GEN
Solar/Wind Harmer
3.461
3146206CASHIE
Solar/Wind Harmer
0.216
3145893MURPHYS
Solar/Wind Harmer
0.361
3145893MURPHYS
Solar/Wind Harmer
0.215
957521AF2-046 GEN
Solar/Wind Harmer
15.996
961681AG1-008 GEN
Solar/Wind Harmer
15.996
970009AG2-005 GEN
Solar/Wind Harmer
1.599
3146173TUNIS
Solar/Wind Harmer
0.213
3156021HOLLOMANSOL
Solar/Wind Harmer
0.967
316463AE2-346 GEN
Solar/Wind Harmer
0.183
316140AB2-099
Solar/Wind Harmer
0.076
962331AG1-082 GEN
Solar/Wind Harmer
2.268
316404AE1-155 C
Solar/Wind Harmer
0.047
3146263WOODLND
Solar/Wind Harmer
0.21
313506AB2-031 GEN
Solar/Wind Harmer
0.649
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3145963POPLR C
Solar/Wind Harmer
0.208
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.208
316478AD1-087 GEN
Solar/Wind Harmer
0.721
316486AD2-202 GEN
Solar/Wind Harmer
0.212
3147043LAWRENC
Solar/Wind Harmer
0.124
3145796HORNRTN
Solar/Wind Harmer
0.822
3145796HORNRTN
Solar/Wind Harmer
0.206
3150351NORNECKC2
Adder
2.075
316210AC1-098 GEN
Solar/Wind Harmer
1.861
3145933PARMELE
Solar/Wind Harmer
0.2
966801AG1-551 GEN
Solar/Wind Harmer
2.326
971781AH1-399 GEN
Solar/Wind Harmer
0.26
970909AG2-566 GEN
Solar/Wind Harmer
2.105
3145746EVERETS
Solar/Wind Harmer
0.196
3145746EVERETS
Solar/Wind Harmer
0.196
315724AD1-057 GEN
Solar/Wind Harmer
0.733
316327AA2-057 GEN
Solar/Wind Harmer
0.292
316131AB2-060 GEN
Solar/Wind Harmer
0.604
964241AG1-285 GEN
Solar/Wind Harmer
12.793
315785AD2-033 C
Solar/Wind Harmer
1.556
970257AG2-171 GEN
Solar/Wind Harmer
6.117
959311AF2-222 GEN
Solar/Wind Harmer
16.978
3146233WITAKRS
Solar/Wind Harmer
0.955
3146233WITAKRS
Solar/Wind Harmer
0.129
3146073TAR RVR
Solar/Wind Harmer
0.19
3146083TARBORO
Solar/Wind Harmer
0.19
963181AG1-167 GEN
Solar/Wind Harmer
0.761
3144293JTRSVLE
Adder
0.605
3138543CONSLDL
Solar/Wind Harmer
0.125
3147133PAMPLIN
Solar/Wind Harmer
0.596
971193AH1-056 GEN
Solar/Wind Harmer
11.558
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.113
961601AG1-000A GEN
Solar/Wind Harmer
13.299
3145543BTLEBRO
Solar/Wind Harmer
0.187
3145543BTLEBRO
Solar/Wind Harmer
0.187
971623AH1-311 GEN
Solar/Wind Harmer
0.374
3141906WESTMOR
Solar/Wind Harmer
0.074
3146776BUCKING
Solar/Wind Harmer
0.064
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.491
970737AG2-469 GEN
Solar/Wind Harmer
7.435
971683AH1-343 GEN
Solar/Wind Harmer
5.965
316283AC2-100 C
Solar/Wind Harmer
0.31
970221AG2-151 GEN
Solar/Wind Harmer
8.416
972255AH1-712 GEN
Adder
74.962
3151761LOISA E
Adder
17.688
972183AH1-676 GEN
Adder
136.298
316303AF2-085
50/50
4.723
971285AH1-108 GEN
50/50
1.99
970603AG2-384 GEN
50/50
5.178
972263AH1-716 GEN
50/50
139.063
316233AE1-074 FULL
Solar/Wind Harmer
0.207
971281AH1-106 GEN
Solar/Wind Harmer
3.58
971283AH1-107 GEN
Solar/Wind Harmer
3.58
3143316POE
Solar/Wind Harmer
0.964
941031AE2-094 GEN
Solar/Wind Harmer
44.68
944011AF1-069 GEN
Solar/Wind Harmer
14.599
316132AB2-190 GEN1
Solar/Wind Harmer
1.291
3151081ELIZAR1
Adder
22.034
3151091ELIZAR2
Adder
21.652
3152611GOSPORTB
Adder
3.059
3152621GOSPORTC
Adder
2.596
3152601GOSPORTA
Adder
2.395
316369SG1_INVT
Solar/Wind Harmer
0.009
971445AH1-216 GEN
Solar/Wind Harmer
16.89
972265AH1-717 GEN
Adder
18.606
3151201GRAVEL4
Adder
17.442
3151191GRAVEL3
Adder
17.221
3151211GRAVEL5
Adder
17.221
970673AG2-436 GEN
Solar/Wind Harmer
50.858
970673AG2-436 GEN
Solar/Wind Harmer
33.905
957871AF2-081 GEN
Solar/Wind Harmer
11.862
316312AB1-027
Solar/Wind Harmer
0.425
319010AE1-072 C
Solar/Wind Harmer
1.197
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.163
316311AC2-079 GEN
Solar/Wind Harmer
6.823
3146406KITTY HAWK
Solar/Wind Harmer
0.03
316305AF2-043 C
Solar/Wind Harmer
0.002
315835AF2-110_GEN
Solar/Wind Harmer
1.621
316315AB2-025 C
Solar/Wind Harmer
0.191
315976AC1-164 GENA
Solar/Wind Harmer
24.444
316169AC1-164_GENC
Solar/Wind Harmer
21.117
315975AC1-164 GENB
Solar/Wind Harmer
0.723
313526AB2-022
Solar/Wind Harmer
0.128
971967AH1-528 GEN
Solar/Wind Harmer
37.658
315814AE2-033 C
Solar/Wind Harmer
18.587
3146486SUNBURY
Solar/Wind Harmer
0.235
3146486SUNBURY
Solar/Wind Harmer
0.235
316321Z2-027
Solar/Wind Harmer
0.044
3146396TANGLEW
Solar/Wind Harmer
0.646
3145176PASQUOTANK
Solar/Wind Harmer
0.145
972189AH1-679 GEN
Adder
3.913
971167AH1-042 GEN
Solar/Wind Harmer
20.686
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3138283WHITEMARSH
Solar/Wind Harmer
0.054
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3143873LANEXA
Solar/Wind Harmer
0.137
316314AB2-024 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.729
3130156CHOWAN
Solar/Wind Harmer
0.227
3130156CHOWAN
Solar/Wind Harmer
0.227
316059AD1-063 C
Solar/Wind Harmer
0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.045
970085AG2-068 GEN
Solar/Wind Harmer
11.956
970581AG2-369 GEN
Solar/Wind Harmer
10.282
3141913WHIT STONE
Solar/Wind Harmer
0.222
315816AE2-034 GEN
Solar/Wind Harmer
0.953
3138133OCRAN
Solar/Wind Harmer
0.066
3141783LANCAST
Solar/Wind Harmer
0.132
3141783LANCAST
Solar/Wind Harmer
0.088
3130546PLYMOUTH
Solar/Wind Harmer
0.218
315732AD1-074 GEN1
Solar/Wind Harmer
1.252
315733AD1-074 GEN2
Solar/Wind Harmer
1.252
315735AD1-075 GEN1
Solar/Wind Harmer
0.627
965291AG1-394 GEN
Solar/Wind Harmer
0.966
3150411LDYSMT5
Adder
29.247
3150381LDYSMT2
Adder
27.99
972213AH1-691 GEN
Adder
4.735
972215AH1-692 GEN
Adder
4.735
962981AG1-147 GEN
Solar/Wind Harmer
8.075
3146206CASHIE
Solar/Wind Harmer
0.216
970601AG2-382 GEN
Solar/Wind Harmer
8.061
3145893MURPHYS
Solar/Wind Harmer
0.582
3145893MURPHYS
Solar/Wind Harmer
0.215
970327AG2-215 GEN
Solar/Wind Harmer
7.029
3145513AHOSKIE
Solar/Wind Harmer
0.444
3145513AHOSKIE
Solar/Wind Harmer
0.212
3146043SEABORD
Solar/Wind Harmer
0.212
3145683EARLEYS
Solar/Wind Harmer
0.423
3145683EARLEYS
Solar/Wind Harmer
0.211
3145683EARLEYS
Solar/Wind Harmer
0.211
315607AA1-063A GEN
Solar/Wind Harmer
0.431
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
22.967
3137643SOCKMAN
Solar/Wind Harmer
0.832
3145796HORNRTN
Solar/Wind Harmer
0.658
3145796HORNRTN
Solar/Wind Harmer
0.082
3141813NORNECK
Solar/Wind Harmer
0.205
3146033SCOT NK
Solar/Wind Harmer
0.815
970831AG2-522 GEN
Solar/Wind Harmer
8.503
316005AA1-067
Solar/Wind Harmer
0.21
3145746EVERETS
Solar/Wind Harmer
0.779
3145746EVERETS
Solar/Wind Harmer
0.196
3145746EVERETS
Solar/Wind Harmer
0.196
3145746EVERETS
Solar/Wind Harmer
0.196
970181AG2-120 GEN
Solar/Wind Harmer
2.436
957861AF2-080 GEN
Solar/Wind Harmer
8.31
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316420AA1-050 GEN
Solar/Wind Harmer
0.006
971443AH1-215 GEN
Solar/Wind Harmer
3.212
3144303KENBRDG
Solar/Wind Harmer
0.153
970683AG2-441 GEN
Solar/Wind Harmer
12.709
970681AG2-440 GEN
Solar/Wind Harmer
10.167
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.19
3145573BETHELC
Solar/Wind Harmer
0.19
946301AF1-294 GEN
Solar/Wind Harmer
3.752
961791AG1-021 GEN
Solar/Wind Harmer
1.825
315657AE1-056 GEN
Solar/Wind Harmer
6.547
316223AC1-118
Solar/Wind Harmer
0.132
970285AG2-188 GEN
Solar/Wind Harmer
14.341
971845AH1-439 GEN
Solar/Wind Harmer
8.154
316118AC1-105 GEN
Solar/Wind Harmer
0.462
3147173SINAI
Solar/Wind Harmer
0.175
3147243WELCO
Solar/Wind Harmer
0.11
972205AH1-687 GEN
Adder
7.204
944491AF1-114 GEN
Solar/Wind Harmer
0.001
970865AG2-541 GEN
Solar/Wind Harmer
5.394
971447AH1-217 GEN
Solar/Wind Harmer
4.654
972193AH1-681 GEN
Adder
3.349
316123AC1-075 GEN
Solar/Wind Harmer
0.195
970165AG2-112 GEN
Solar/Wind Harmer
1.154
970163AG2-111 GEN
Solar/Wind Harmer
1.101
3141316ARNOLDS
Adder
0.29
316044AC1-158 PL1
Solar/Wind Helper
5.216
316450AC1-158 RIC
Solar/Wind Helper
1.391
3141196NOKESVL
Solar/Wind Helper
1.131
3151751LOISA D
Adder
8.676
970223AG2-152 GEN
Solar/Wind Harmer
7.908
316045AC1-158 PL2
Solar/Wind Helper
16.699
316006AB2-029 C
Solar/Wind Helper
0.14
270494AE1-108_GEN
Solar/Wind Harmer
1.672
3147346CASHSCORNER
Solar/Wind Harmer
0.293
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316164AC1-076 GEN
Solar/Wind Helper
1.38
316411AF1-147_GEN1
Solar/Wind Helper
0.79
316415AF1-147_GEN2
Solar/Wind Helper
0.79
3138216PACIFIC
Solar/Wind Helper
0.038
LAGNLTFEXP_LAGN->PJM
CLTF
8.398
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.027
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.441
MECLTFEXP_MEC->PJM
CLTF
3.751
SIGELTFEXP_SIGE->PJM
CLTF
0.114
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.505
TVALTFEXP_TVA->PJM
CLTF
4.252
NYPJM->LTFIMP_NY
CLTF
3.266
LGEELTFEXP_LGEE->PJM
CLTF
1.371
WECLTFEXP_WEC->PJM
CLTF
0.662
CPLELTFEXP_CPLE->PJM
CLTF
12.136
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.163

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:171.66 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5528.27
MW Contribution:8.48
Bus #Bus NameTypeMW Contribution
971133AH1-012 GEN
50/50
5.467
944641AF1-129 GEN
50/50
125.042
3142366NRTHEST
50/50
0.853
970533AG2-339 GEN
50/50
21.877
970531AG2-338 GEN
50/50
8.751
3150781HOPHCF2
50/50
0.996
3150791HOPHCF3
50/50
0.996
3150761HOPPOLC
50/50
0.631
971213AH1-066 GEN
50/50
0.873
3150691DARBY 3
50/50
18.729
3150701DARBY 4
50/50
18.685
971223AH1-071 GEN
Solar/Wind Harmer
2.875
3143526WINTERP
Solar/Wind Harmer
1.363
316240AF1-291 C
Solar/Wind Harmer
0.002
3150681DARBY 2
Adder
17.588
3150671DARBY 1
Adder
17.568
3142296MT RD221
Adder
0.779
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.275
316036AC1-147 C
Solar/Wind Harmer
0.045
3150991CHESPKB
Adder
2.56
3150991CHESPKB
Adder
2.499
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.234
316185AD1-033 GEN
Solar/Wind Harmer
0.007
970657AG2-426 GEN
Solar/Wind Harmer
8.541
970657AG2-426 GEN
Solar/Wind Harmer
1.79
3142946ENON
Solar/Wind Harmer
0.024
3145506HICKORY
Solar/Wind Harmer
0.973
3145506HICKORY
Solar/Wind Harmer
0.584
3145506HICKORY
Solar/Wind Harmer
0.146
316339AD2-160 GEN
Solar/Wind Harmer
0.393
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.135
316075AC2-137 C
Solar/Wind Harmer
0.066
3137176SLIGO L2192
Solar/Wind Harmer
0.963
3146456SLIGO L269
Solar/Wind Harmer
4.28
3130086AYDLETT
Solar/Wind Harmer
0.966
972185AH1-677 GEN
Adder
13.452
3144356SAPONY
Solar/Wind Harmer
2.004
3146386ELIZ CT
Solar/Wind Harmer
0.239
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
972187AH1-678 GEN
Adder
6.746
3146516WINFALL
Solar/Wind Harmer
0.236
3146516WINFALL
Solar/Wind Harmer
0.236
3146516WINFALL
Solar/Wind Harmer
0.236
966871AG1-558 GEN
Solar/Wind Harmer
0.272
3146626S HERTFORD
Solar/Wind Harmer
0.235
3146626S HERTFORD
Solar/Wind Harmer
0.235
970933AG2-581 GEN
Solar/Wind Harmer
18.633
316303AF2-085
50/50
4.791
971285AH1-108 GEN
50/50
2.026
970603AG2-384 GEN
50/50
5.274
316233AE1-074 FULL
Solar/Wind Harmer
0.21
971281AH1-106 GEN
Solar/Wind Harmer
3.638
971283AH1-107 GEN
Solar/Wind Harmer
3.638
3143316POE
Solar/Wind Harmer
0.98
941031AE2-094 GEN
Solar/Wind Harmer
45.33
944011AF1-069 GEN
Solar/Wind Harmer
14.811
316132AB2-190 GEN1
Solar/Wind Harmer
1.315
316369SG1_INVT
Solar/Wind Harmer
0.009
3151081ELIZAR1
Adder
22.416
3151091ELIZAR2
Adder
22.027
3152611GOSPORTB
Adder
3.112
3152621GOSPORTC
Adder
2.641
3152601GOSPORTA
Adder
2.437
971445AH1-216 GEN
Solar/Wind Harmer
17.191
972265AH1-717 GEN
Adder
18.943
3151201GRAVEL4
Adder
17.758
3151191GRAVEL3
Adder
17.533
3151211GRAVEL5
Adder
17.533
316312AB1-027
Solar/Wind Harmer
0.435
957871AF2-081 GEN
Solar/Wind Harmer
12.066
970673AG2-436 GEN
Solar/Wind Harmer
51.597
970673AG2-436 GEN
Solar/Wind Harmer
34.398
319010AE1-072 C
Solar/Wind Harmer
1.218
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.166
316311AC2-079 GEN
Solar/Wind Harmer
6.941
3146406KITTY HAWK
Solar/Wind Harmer
0.03
316305AF2-043 C
Solar/Wind Harmer
0.002
315976AC1-164 GENA
Solar/Wind Harmer
24.95
316169AC1-164_GENC
Solar/Wind Harmer
21.555
315975AC1-164 GENB
Solar/Wind Harmer
0.738
315835AF2-110_GEN
Solar/Wind Harmer
1.649
316315AB2-025 C
Solar/Wind Harmer
0.194
313526AB2-022
Solar/Wind Harmer
0.13
972189AH1-679 GEN
Adder
4.009
3146486SUNBURY
Solar/Wind Harmer
0.239
3146486SUNBURY
Solar/Wind Harmer
0.239
971967AH1-528 GEN
Solar/Wind Harmer
38.202
315814AE2-033 C
Solar/Wind Harmer
18.884
316321Z2-027
Solar/Wind Harmer
0.044
3146396TANGLEW
Solar/Wind Harmer
0.658
3145176PASQUOTANK
Solar/Wind Harmer
0.148
971167AH1-042 GEN
Solar/Wind Harmer
21.1
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
3138283WHITEMARSH
Solar/Wind Harmer
0.055
3143873LANEXA
Solar/Wind Harmer
0.14
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
316314AB2-024 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.866
316059AD1-063 C
Solar/Wind Harmer
0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.008
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.23
3130156CHOWAN
Solar/Wind Harmer
0.23
3141873WAN 176
Solar/Wind Harmer
0.046
970085AG2-068 GEN
Solar/Wind Harmer
12.13
970581AG2-369 GEN
Solar/Wind Harmer
10.432
3141913WHIT STONE
Solar/Wind Harmer
0.227
3138133OCRAN
Solar/Wind Harmer
0.068
315816AE2-034 GEN
Solar/Wind Harmer
0.969
3141783LANCAST
Solar/Wind Harmer
0.135
3141783LANCAST
Solar/Wind Harmer
0.09
3150411LDYSMT5
Adder
30.153
3150381LDYSMT2
Adder
28.858
972213AH1-691 GEN
Adder
4.882
972215AH1-692 GEN
Adder
4.882
3130546PLYMOUTH
Solar/Wind Harmer
0.222
315732AD1-074 GEN1
Solar/Wind Harmer
1.273
315733AD1-074 GEN2
Solar/Wind Harmer
1.273
315735AD1-075 GEN1
Solar/Wind Harmer
0.637
965291AG1-394 GEN
Solar/Wind Harmer
0.982
962981AG1-147 GEN
Solar/Wind Harmer
8.243
3146206CASHIE
Solar/Wind Harmer
0.219
970601AG2-382 GEN
Solar/Wind Harmer
8.195
3145893MURPHYS
Solar/Wind Harmer
0.591
3145893MURPHYS
Solar/Wind Harmer
0.219
970327AG2-215 GEN
Solar/Wind Harmer
7.177
3145513AHOSKIE
Solar/Wind Harmer
0.452
3145513AHOSKIE
Solar/Wind Harmer
0.216
3146043SEABORD
Solar/Wind Harmer
0.215
3145683EARLEYS
Solar/Wind Harmer
0.43
3145683EARLEYS
Solar/Wind Harmer
0.215
3145683EARLEYS
Solar/Wind Harmer
0.215
315607AA1-063A GEN
Solar/Wind Harmer
0.438
3152251N ANNA1
50/50
20.435
970119AG2-088 GEN
50/50
35.934
3150851SPRUNCC
50/50
1.238
3143096IRON208
50/50
1.099
3152331SURRY 2
50/50
10.173
3150771HOPHCF1
50/50
0.996
3143226MDLTHAN
Solar/Wind Harmer
0.269
3143526WINTERP
Solar/Wind Harmer
1.363
3147666LOUISA
Solar/Wind Harmer
1.017
940641AE2-051 GEN
Solar/Wind Harmer
20.264
939411AE1-173 GEN
Solar/Wind Harmer
107.071
3142543TWELFTH
Solar/Wind Harmer
0.024
316192AB2-158 GEN
Solar/Wind Harmer
1.397
316294AC1-161 GEN
Solar/Wind Harmer
4.284
315671AE2-027_GEN
Solar/Wind Harmer
15.779
970129AG2-093 GEN
Solar/Wind Harmer
6.973
316458AB2-190 GEN2
Solar/Wind Harmer
1.315
944591AF1-124 GEN
Solar/Wind Harmer
55.346
971069AG2-661 GEN
Solar/Wind Harmer
4.353
944631AF1-128 GEN
Adder
116.602
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
3.052
971647AH1-324 GEN
Solar/Wind Harmer
10.43
970659AG2-427 GEN
Solar/Wind Harmer
11.815
3145336SMITFLD
Solar/Wind Harmer
0.976
961611AG1-000B GEN
Solar/Wind Harmer
12.808
316381AD1-082 GEN
Solar/Wind Harmer
0.254
3151171GRAVELC
Adder
2.595
970661AG2-428 GEN
Solar/Wind Harmer
24.214
3142416OLDCHRC
Solar/Wind Harmer
0.631
3142416OLDCHRC
Solar/Wind Harmer
0.242
316388AE2-253 GEN
Solar/Wind Harmer
0.76
3138126ROCKLANDING
Solar/Wind Harmer
0.111
3146456SLIGO L269
Solar/Wind Harmer
0.242
316072AD1-144
Solar/Wind Harmer
0.088
316159AE1-175 C
Solar/Wind Harmer
0.209
316246AF1-032 C
Solar/Wind Harmer
0.109
971317AH1-138 GEN
Solar/Wind Harmer
1.796
316093AE2-104_GEN
Solar/Wind Harmer
4.042
3142433PROV 92
Solar/Wind Harmer
0.947
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
3146516WINFALL
Solar/Wind Harmer
0.766
3146516WINFALL
Solar/Wind Harmer
0.236
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
971777AH1-397 GEN
Solar/Wind Harmer
0.612
3141843SHACKLE
Adder
1.184
3141766HARMONY
Solar/Wind Harmer
0.046
966881AG1-559 GEN
Solar/Wind Harmer
0.267
3130156CHOWAN
Solar/Wind Harmer
0.23
3143336POWHATN
Solar/Wind Harmer
4.084
970919AG2-571 GEN
Solar/Wind Harmer
8.12
970087AG2-069 GEN
Solar/Wind Harmer
18.195
3138133OCRAN
Solar/Wind Harmer
0.136
3145663CRESWEL
Solar/Wind Harmer
0.632
971163AH1-040 GEN
Solar/Wind Harmer
18.07
972197AH1-683 GEN
Adder
4.694
972219AH1-694 GEN
Adder
3.38
316023GEN1_S
Solar/Wind Harmer
0.497
3146206CASHIE
Solar/Wind Harmer
0.219
971547AH1-271 GEN
Solar/Wind Harmer
4.683
316336AC2-165 C
Solar/Wind Harmer
0.009
3145893MURPHYS
Solar/Wind Harmer
0.876
3145893MURPHYS
Solar/Wind Harmer
0.974
957481AF2-042 GEN
Solar/Wind Harmer
58.056
3146173TUNIS
Solar/Wind Harmer
0.217
962861AG1-135 GEN
Solar/Wind Harmer
6.917
960081AF2-299 GEN
Solar/Wind Harmer
2.073
3145683EARLEYS
Solar/Wind Harmer
0.215
3146263WOODLND
Solar/Wind Harmer
0.214
315693AD1-088 GEN
Solar/Wind Harmer
10.231
962491AG1-098 GEN
Solar/Wind Harmer
12.124
316011AB1-132 GEN
Solar/Wind Harmer
3.856
962571AG1-106 GEN
Solar/Wind Harmer
3.018
3141726DUNNSVL
Solar/Wind Harmer
0.847
3145963POPLR C
Solar/Wind Harmer
0.211
971795AH1-408 GEN
Solar/Wind Harmer
14.105
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.211
316174AB2-169 GEN
Solar/Wind Harmer
0.006
3147043LAWRENC
Adder
1.896
3145783HORNRTN
Solar/Wind Harmer
0.209
3150351NORNECKC2
Adder
2.084
3145796HORNRTN
Solar/Wind Harmer
0.689
3145796HORNRTN
Solar/Wind Harmer
0.209
316212AC1-099_GEN
Solar/Wind Harmer
1.054
3146293MARTNCO
Solar/Wind Harmer
0.188
316129AC1-054 GEN
Solar/Wind Harmer
0.758
971065AG2-659 GEN
Solar/Wind Harmer
8.56
316337AD2-073 GEN
Solar/Wind Harmer
0.173
3145746EVERETS
Solar/Wind Harmer
0.199
3145746EVERETS
Solar/Wind Harmer
0.199
315722AD1-056 GEN
Solar/Wind Harmer
1.256
315687AD1-152 GEN
Solar/Wind Harmer
0.006
316494AC1-189 GEN
Solar/Wind Harmer
0.661
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3146233WITAKRS
Solar/Wind Harmer
0.769
961671AG1-007 GEN
Solar/Wind Harmer
0.03
3146083TARBORO
Solar/Wind Harmer
0.193
3145493TOT1
Solar/Wind Harmer
0.859
970685AG2-442 GEN
Solar/Wind Harmer
14.419
970937AG2-583 GEN
Solar/Wind Harmer
11.813
963171AG1-166 GEN
Solar/Wind Harmer
1.027
971563AH1-280 GEN
Solar/Wind Harmer
2.054
3144293JTRSVLE
Adder
0.613
3146926FARMVIL
Solar/Wind Harmer
0.114
3145543BTLEBRO
Solar/Wind Harmer
0.19
3145543BTLEBRO
Solar/Wind Harmer
0.152
316359AB2-059 GEN
Solar/Wind Harmer
0.682
316049AB1-081 GEN
Solar/Wind Harmer
1.086
3142053HEARTS
Solar/Wind Harmer
0.334
970401AG2-262 GEN
Solar/Wind Harmer
1.086
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.072
972003AH1-546 GEN
Solar/Wind Harmer
7.307
972135AH1-637 GEN
Solar/Wind Harmer
1.466
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971377AH1-170 GEN
Solar/Wind Harmer
1.697
3147623JAMES R
Solar/Wind Harmer
0.369
972277AH1-723 GEN
Adder
89.316
3151751LOISA D
Adder
8.255
970223AG2-152 GEN
Solar/Wind Harmer
8.023
316045AC1-158 PL2
Solar/Wind Helper
16.818
3152261N ANNA2
50/50
20.433
3150861SPRUNCD
50/50
1.238
3143096IRON208
50/50
1.099
3143096IRON208
50/50
1.077
3150801HOPHCF4
50/50
1.448
971211AH1-065 GEN
50/50
1.746
3151161SURRY 1
50/50
9.371
3147666LOUISA
Solar/Wind Harmer
0.585
315839AE2-212 C
Solar/Wind Harmer
0.002
315773AC2-141 GEN
Solar/Wind Harmer
9.03
965281AG1-393 GEN
Solar/Wind Harmer
2.631
315813AE1-149 C
Solar/Wind Harmer
13.098
970133AG2-095 GEN
Solar/Wind Harmer
2.358
970129AG2-093 GEN
Solar/Wind Harmer
14.818
944581AF1-123 GEN
Solar/Wind Harmer
55.15
315742AE1-103 GEN
Solar/Wind Harmer
0.003
957411AF2-035 GEN
Solar/Wind Harmer
9.864
970317AG2-208 GEN
Solar/Wind Harmer
9.139
3146376EDENTON
Solar/Wind Harmer
1.025
3146376EDENTON
Solar/Wind Harmer
1.025
315673AE1-157 GEN
Solar/Wind Harmer
15.809
3150391LDYSMT3
Adder
30.003
972195AH1-682 GEN
Adder
3.943
316065AD1-022 GEN
Solar/Wind Harmer
10.141
3145893MURPHYS
Solar/Wind Harmer
1.466
3145893MURPHYS
Solar/Wind Harmer
0.394
970099AG2-077 GEN
Solar/Wind Harmer
23.222
3146173TUNIS
Solar/Wind Harmer
0.217
3146173TUNIS
Solar/Wind Harmer
0.217
958261AF2-120 GEN
Solar/Wind Harmer
7.118
316181AB2-040 GEN
Solar/Wind Harmer
0.309
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3142666NORTHAMPTON
Solar/Wind Harmer
0.128
316426AA2-053 GEN
Solar/Wind Harmer
0.713
3145593CAROLNA
Solar/Wind Harmer
0.21
3145593CAROLNA
Solar/Wind Harmer
0.21
966811AG1-552 GEN
Solar/Wind Harmer
2.282
3145593CAROLNA
Solar/Wind Harmer
0.262
3145783HORNRTN
Solar/Wind Harmer
3.718
3145783HORNRTN
Solar/Wind Harmer
2.974
3145783HORNRTN
Solar/Wind Harmer
0.93
3145783HORNRTN
Solar/Wind Harmer
0.372
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.19
3150341NORNECKC1
Adder
2.172
3145796HORNRTN
Solar/Wind Harmer
0.626
3145933PARMELE
Solar/Wind Harmer
0.406
3145933PARMELE
Solar/Wind Harmer
0.203
971741AH1-377 GEN
Solar/Wind Harmer
20.122
316274AC1-208 GEN
Solar/Wind Harmer
1.051
316468AD1-105 GEN
Solar/Wind Harmer
-0.066
970301AG2-198 GEN
Solar/Wind Harmer
8.524
939181AE1-148 GEN
Solar/Wind Harmer
9.423
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.264
971775AH1-396 GEN
Solar/Wind Harmer
0.31
3145493TOT1
Solar/Wind Harmer
0.448
3145453TOT5
Solar/Wind Harmer
0.269
3145603CNETO
Solar/Wind Harmer
0.179
958211AF2-115 GEN
Solar/Wind Harmer
2.311
963191AG1-168 GEN
Solar/Wind Harmer
0.77
3144293JTRSVLE
Adder
0.613
3144293JTRSVLE
Adder
0.516
3147133PAMPLIN
Solar/Wind Harmer
0.192
3147133PAMPLIN
Solar/Wind Harmer
0.154
961601AG1-000A GEN
Solar/Wind Harmer
3.377
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
23.331
3137643SOCKMAN
Solar/Wind Harmer
0.845
3141813NORNECK
Solar/Wind Harmer
0.209
3145796HORNRTN
Solar/Wind Harmer
0.668
3145796HORNRTN
Solar/Wind Harmer
0.084
3146033SCOT NK
Solar/Wind Harmer
0.828
970831AG2-522 GEN
Solar/Wind Harmer
8.631
316005AA1-067
Solar/Wind Harmer
0.213
3145746EVERETS
Solar/Wind Harmer
0.791
3145746EVERETS
Solar/Wind Harmer
0.199
3145746EVERETS
Solar/Wind Harmer
0.199
3145746EVERETS
Solar/Wind Harmer
0.199
970181AG2-120 GEN
Solar/Wind Harmer
2.475
957861AF2-080 GEN
Solar/Wind Harmer
8.442
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316420AA1-050 GEN
Solar/Wind Harmer
0.006
971443AH1-215 GEN
Solar/Wind Harmer
3.255
3144303KENBRDG
Solar/Wind Harmer
0.155
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.193
3145573BETHELC
Solar/Wind Harmer
0.193
970683AG2-441 GEN
Solar/Wind Harmer
12.874
970681AG2-440 GEN
Solar/Wind Harmer
10.299
946301AF1-294 GEN
Solar/Wind Harmer
3.8
961791AG1-021 GEN
Solar/Wind Harmer
1.849
315657AE1-056 GEN
Solar/Wind Harmer
6.628
316223AC1-118
Solar/Wind Harmer
0.135
970285AG2-188 GEN
Solar/Wind Harmer
14.487
971845AH1-439 GEN
Solar/Wind Harmer
8.236
316118AC1-105 GEN
Solar/Wind Harmer
0.469
3147173SINAI
Solar/Wind Harmer
0.178
3147243WELCO
Solar/Wind Harmer
0.111
972205AH1-687 GEN
Adder
7.261
944491AF1-114 GEN
Solar/Wind Harmer
0.001
970865AG2-541 GEN
Solar/Wind Harmer
5.471
971447AH1-217 GEN
Solar/Wind Harmer
4.69
972193AH1-681 GEN
Adder
3.425
316123AC1-075 GEN
Solar/Wind Harmer
0.197
970165AG2-112 GEN
Solar/Wind Harmer
1.171
970163AG2-111 GEN
Solar/Wind Harmer
1.117
270494AE1-108_GEN
Solar/Wind Harmer
1.686
3147346CASHSCORNER
Solar/Wind Harmer
0.279
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316164AC1-076 GEN
Solar/Wind Helper
2.196
316411AF1-147_GEN1
Solar/Wind Helper
0.801
316415AF1-147_GEN2
Solar/Wind Helper
0.801
3138216PACIFIC
Solar/Wind Helper
0.039
316263AC1-034 GEN
Solar/Wind Harmer
7.215
962561AG1-105 GEN
Solar/Wind Harmer
8.959
964791AG1-342 GEN
Solar/Wind Harmer
3.555
3146843MT LREL
Solar/Wind Harmer
0.185
3146843MT LREL
Solar/Wind Harmer
0.185
3146776BUCKING
Solar/Wind Harmer
0.723
3146776BUCKING
Solar/Wind Harmer
0.059
316222AC1-221 GEN
Solar/Wind Harmer
0.67
971489AH1-241 GEN
Solar/Wind Harmer
8.483
942751AE2-291 GEN
Solar/Wind Harmer
7.393
315821AE2-092 GEN
Solar/Wind Harmer
0.008
3151731LOISA B
Adder
8.255
3151721LOISA A
Adder
8.212
316447AC1-158 HLD
Solar/Wind Helper
11.564
315651AD1-115 GEN
Solar/Wind Helper
1.026
944601AF1-125 GEN
Solar/Wind Harmer
54.301
315778AD1-151 GEN
Solar/Wind Harmer
19.588
3151101ELIZAR3
Adder
22.703
3144536CHRHLND
Solar/Wind Harmer
0.037
3144873MCLAUGH
Solar/Wind Harmer
0.006
970659AG2-427 GEN
Solar/Wind Harmer
2.585
3145336SMITFLD
Solar/Wind Harmer
0.098
961611AG1-000B GEN
Solar/Wind Harmer
6.513
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3151221GRAVEL6
Adder
17.737
3151171GRAVELC
Adder
3.413
970293AG2-193 GEN
Solar/Wind Harmer
2.6
3142946ENON
Solar/Wind Harmer
0.081
970661AG2-428 GEN
Solar/Wind Harmer
5.15
3142416OLDCHRC
Solar/Wind Harmer
2.354
3144216WINCHST
Adder
0.913
3146456SLIGO L269
Solar/Wind Harmer
0.242
971153AH1-033 GEN
Solar/Wind Harmer
2.796
3150921YORKTN3
Adder
6.079
316382AG1-145 C
Solar/Wind Harmer
0.002
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
3146516WINFALL
Solar/Wind Harmer
0.236
316473AC1-191 GEN
Solar/Wind Harmer
0.795
3146626S HERTFORD
Solar/Wind Harmer
0.235
3145273HOLLAND
Solar/Wind Harmer
0.176
3141843SHACKLE
Adder
1.184
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
3.085
316280AD1-041 GEN
Solar/Wind Harmer
0.005
3146376EDENTON
Solar/Wind Harmer
0.23
316156AD2-030 GEN
Solar/Wind Harmer
0.17
3141873WAN 176
Solar/Wind Harmer
4.092
316313AB2-026
Solar/Wind Harmer
0.145
316258AE1-075 C
Solar/Wind Harmer
0.173
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.472
970917AG2-570 GEN
Solar/Wind Harmer
20.3
315614AA2-178 GEN
Solar/Wind Harmer
1.293
3150401LDYSMT4
Adder
30.059
3150371LDYSMT1
Adder
29.045
971157AH1-035 GEN
Solar/Wind Harmer
2.667
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
315737AD1-076 GEN
Solar/Wind Harmer
2.851
316365GEN2_N
Solar/Wind Harmer
0.497
962971AG1-146 GEN
Solar/Wind Harmer
3.533
3146206CASHIE
Solar/Wind Harmer
0.219
3145893MURPHYS
Solar/Wind Harmer
0.367
3145893MURPHYS
Solar/Wind Harmer
0.219
970009AG2-005 GEN
Solar/Wind Harmer
1.633
957521AF2-046 GEN
Solar/Wind Harmer
16.257
961681AG1-008 GEN
Solar/Wind Harmer
16.257
3146173TUNIS
Solar/Wind Harmer
0.217
3156021HOLLOMANSOL
Solar/Wind Harmer
0.983
316463AE2-346 GEN
Solar/Wind Harmer
0.186
316140AB2-099
Solar/Wind Harmer
0.077
962331AG1-082 GEN
Solar/Wind Harmer
2.305
316404AE1-155 C
Solar/Wind Harmer
0.048
3146263WOODLND
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.659
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3145963POPLR C
Solar/Wind Harmer
0.211
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.211
3147043LAWRENC
Solar/Wind Harmer
0.126
316478AD1-087 GEN
Solar/Wind Harmer
0.731
316486AD2-202 GEN
Solar/Wind Harmer
0.215
3150351NORNECKC2
Adder
2.12
3145796HORNRTN
Solar/Wind Harmer
0.835
3145796HORNRTN
Solar/Wind Harmer
0.209
316210AC1-098 GEN
Solar/Wind Harmer
1.891
3145933PARMELE
Solar/Wind Harmer
0.203
966801AG1-551 GEN
Solar/Wind Harmer
2.363
971781AH1-399 GEN
Solar/Wind Harmer
0.266
970909AG2-566 GEN
Solar/Wind Harmer
2.131
3145746EVERETS
Solar/Wind Harmer
0.199
3145746EVERETS
Solar/Wind Harmer
0.199
315724AD1-057 GEN
Solar/Wind Harmer
0.745
316327AA2-057 GEN
Solar/Wind Harmer
0.297
316131AB2-060 GEN
Solar/Wind Harmer
0.613
964241AG1-285 GEN
Solar/Wind Harmer
12.969
315785AD2-033 C
Solar/Wind Harmer
1.576
970257AG2-171 GEN
Solar/Wind Harmer
6.198
959311AF2-222 GEN
Solar/Wind Harmer
17.202
3146233WITAKRS
Solar/Wind Harmer
0.97
3146233WITAKRS
Solar/Wind Harmer
0.131
3146073TAR RVR
Solar/Wind Harmer
0.193
3146083TARBORO
Solar/Wind Harmer
0.193
3138543CONSLDL
Solar/Wind Harmer
0.127
963181AG1-167 GEN
Solar/Wind Harmer
0.77
3144293JTRSVLE
Adder
0.613
3147133PAMPLIN
Solar/Wind Harmer
0.603
971193AH1-056 GEN
Solar/Wind Harmer
11.702
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
961601AG1-000A GEN
Solar/Wind Harmer
13.507
3146926FARMVIL
Solar/Wind Harmer
0.114
3145543BTLEBRO
Solar/Wind Harmer
0.19
3145543BTLEBRO
Solar/Wind Harmer
0.19
971623AH1-311 GEN
Solar/Wind Harmer
0.38
3141906WESTMOR
Solar/Wind Harmer
0.075
3146776BUCKING
Solar/Wind Harmer
0.065
970737AG2-469 GEN
Solar/Wind Harmer
7.61
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.598
971683AH1-343 GEN
Solar/Wind Harmer
6.05
316283AC2-100 C
Solar/Wind Harmer
0.314
970221AG2-151 GEN
Solar/Wind Harmer
8.483
972255AH1-712 GEN
Adder
76.646
3151761LOISA E
Adder
16.829
3141316ARNOLDS
Adder
0.299
972183AH1-676 GEN
Adder
129.168
3150331BIRCHWDA
Adder
19.249
316044AC1-158 PL1
Solar/Wind Helper
5.254
316450AC1-158 RIC
Solar/Wind Helper
1.401
316170AC1-121 GEN2
Solar/Wind Helper
0.463
3141196NOKESVL
Solar/Wind Helper
1.151
316006AB2-029 C
Solar/Wind Helper
0.152
316254AC1-120 GEN1
Solar/Wind Helper
1.388
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.369
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.657
MECLTFEXP_MEC->PJM
CLTF
3.808
LAGNLTFEXP_LAGN->PJM
CLTF
8.524
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.899
TVALTFEXP_TVA->PJM
CLTF
4.316
SIGELTFEXP_SIGE->PJM
CLTF
0.116
CPLELTFEXP_CPLE->PJM
CLTF
12.317
NYPJM->LTFIMP_NY
CLTF
3.309
LGEELTFEXP_LGEE->PJM
CLTF
1.392
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.813
WECLTFEXP_WEC->PJM
CLTF
0.673

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.49 %
Rating:3193.18 MVA
Rating Type:A
MVA to Mitigate:3783.56
MW Contribution:6.39
Bus #Bus NameTypeMW Contribution
971133AH1-012 GEN
50/50
4.727
970533AG2-339 GEN
50/50
16.617
970531AG2-338 GEN
50/50
6.647
315242AE2-183_GT2
50/50
3.006
315241AE2-183_GT1
50/50
2.987
972185AH1-677 GEN
50/50
10.835
3151041BRUNSWICKG3
50/50
2.367
972187AH1-678 GEN
50/50
5.432
3150991CHESPKB
50/50
1.99
3150991CHESPKB
50/50
1.942
971223AH1-071 GEN
Solar/Wind Harmer
2.18
3143526WINTERP
Solar/Wind Harmer
1.012
316036AC1-147 C
Solar/Wind Harmer
0.033
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.172
316185AD1-033 GEN
Solar/Wind Harmer
0.005
316240AF1-291 C
Solar/Wind Harmer
0.001
3144356SAPONY
Solar/Wind Harmer
1.494
3145506HICKORY
Solar/Wind Harmer
0.714
3145506HICKORY
Solar/Wind Harmer
0.428
3145506HICKORY
Solar/Wind Harmer
0.107
970657AG2-426 GEN
Solar/Wind Harmer
6.25
970657AG2-426 GEN
Solar/Wind Harmer
1.31
944641AF1-129 GEN
Adder
84.93
316339AD2-160 GEN
Solar/Wind Harmer
0.288
316018AA1-139 ULT2
Solar/Wind Harmer
0.004
316017AA1-139 ULT1
Solar/Wind Harmer
0.099
316236AE1-162_GEN
Solar/Wind Harmer
0.001
3137176SLIGO L2192
Solar/Wind Harmer
0.706
3146456SLIGO L269
Solar/Wind Harmer
3.14
3130086AYDLETT
Solar/Wind Harmer
0.709
970933AG2-581 GEN
Solar/Wind Harmer
14.133
316033AB2-134 GEN
Solar/Wind Harmer
0.01
315697AD1-025 GEN
Solar/Wind Harmer
0.199
3146386ELIZ CT
Solar/Wind Harmer
0.176
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.174
3146516WINFALL
Solar/Wind Harmer
0.174
3146516WINFALL
Solar/Wind Harmer
0.174
3142366NRTHEST
Adder
0.565
3146626S HERTFORD
Solar/Wind Harmer
0.173
3152261N ANNA2
50/50
17.597
3150861SPRUNCD
50/50
0.898
3151031BRUNSWICKG2
50/50
2.367
3151101ELIZAR3
50/50
17.646
3147666LOUISA
Solar/Wind Harmer
0.507
315773AC2-141 GEN
Solar/Wind Harmer
6.611
315839AE2-212 C
Solar/Wind Harmer
0.001
944581AF1-123 GEN
Solar/Wind Harmer
40.447
944601AF1-125 GEN
Solar/Wind Harmer
39.824
315813AE1-149 C
Solar/Wind Harmer
9.573
3144873MCLAUGH
Solar/Wind Harmer
0.004
965281AG1-393 GEN
Solar/Wind Harmer
1.908
970659AG2-427 GEN
Solar/Wind Harmer
1.891
3144536CHRHLND
Solar/Wind Harmer
0.027
316083AB2-161 GEN
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
3.77
3145336SMITFLD
Solar/Wind Harmer
0.071
3146456SLIGO L269
Solar/Wind Harmer
0.177
971153AH1-033 GEN
Solar/Wind Harmer
2.051
3151221GRAVEL6
Adder
12.86
3151171GRAVELC
Adder
2.474
961611AG1-000B GEN
Solar/Wind Harmer
4.714
315778AD1-151 GEN
Solar/Wind Harmer
14.128
970129AG2-093 GEN
Solar/Wind Harmer
10.67
970133AG2-095 GEN
Solar/Wind Harmer
1.693
3143096IRON208
Adder
0.737
3143096IRON208
Adder
0.722
316320Y1-086
Solar/Wind Harmer
0.001
3144216WINCHST
Adder
0.657
316435W1029_GEN3
Solar/Wind Harmer
0.001
316313AB2-026
Solar/Wind Harmer
0.11
316258AE1-075 C
Solar/Wind Harmer
0.131
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.631
3146516WINFALL
Solar/Wind Harmer
0.174
3152251N ANNA1
50/50
17.599
970119AG2-088 GEN
50/50
27.254
3150851SPRUNCC
50/50
0.898
315243AE2-183_GT3
50/50
3.006
3151051BRUNSWICKS1
50/50
4.913
3151021BRUNSWICKG1
50/50
2.367
971451AH1-221 GEN
50/50
7.19
3150981CHESPKA
50/50
2.372
3147666LOUISA
Solar/Wind Harmer
0.882
316192AB2-158 GEN
Solar/Wind Harmer
1.212
3143226MDLTHAN
Solar/Wind Harmer
0.204
3143526WINTERP
Solar/Wind Harmer
1.012
940641AE2-051 GEN
Solar/Wind Harmer
15.302
939411AE1-173 GEN
Solar/Wind Harmer
80.278
316294AC1-161 GEN
Solar/Wind Harmer
3.136
944591AF1-124 GEN
Solar/Wind Harmer
40.591
316375AC2-012 GEN
Solar/Wind Harmer
0.005
970659AG2-427 GEN
Solar/Wind Harmer
8.643
316381AD1-082 GEN
Solar/Wind Harmer
0.186
315671AE2-027_GEN
Solar/Wind Harmer
11.421
970661AG2-428 GEN
Solar/Wind Harmer
17.724
3142543TWELFTH
Solar/Wind Harmer
0.017
316388AE2-253 GEN
Solar/Wind Harmer
0.557
3145336SMITFLD
Solar/Wind Harmer
0.711
3146456SLIGO L269
Solar/Wind Harmer
0.177
316246AF1-032 C
Solar/Wind Harmer
0.08
3151171GRAVELC
Adder
1.882
316072AD1-144
Solar/Wind Harmer
0.064
961611AG1-000B GEN
Solar/Wind Harmer
9.271
971647AH1-324 GEN
Solar/Wind Harmer
7.54
971069AG2-661 GEN
Solar/Wind Harmer
3.14
316458AB2-190 GEN2
Solar/Wind Harmer
0.947
970129AG2-093 GEN
Solar/Wind Harmer
5.021
316093AE2-104_GEN
Solar/Wind Harmer
2.965
3143096IRON208
Adder
0.737
3143336POWHATN
Solar/Wind Harmer
3.095
3138126ROCKLANDING
Solar/Wind Harmer
0.08
3146516WINFALL
Solar/Wind Harmer
0.563
3146516WINFALL
Solar/Wind Harmer
0.174
944631AF1-128 GEN
Adder
82.804
970919AG2-571 GEN
Solar/Wind Harmer
6.156
970087AG2-069 GEN
Solar/Wind Harmer
13.793
971317AH1-138 GEN
Solar/Wind Harmer
1.284
316159AE1-175 C
Solar/Wind Harmer
0.148
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.17
3142416OLDCHRC
Solar/Wind Harmer
0.437
3142416OLDCHRC
Solar/Wind Harmer
0.167
3142433PROV 92
Solar/Wind Harmer
0.669
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
3145663CRESWEL
Solar/Wind Harmer
0.466
971163AH1-040 GEN
Solar/Wind Harmer
13.314
316336AC2-165 C
Solar/Wind Harmer
0.006
316023GEN1_S
Solar/Wind Harmer
0.37
957481AF2-042 GEN
Solar/Wind Harmer
43.952
971777AH1-397 GEN
Solar/Wind Harmer
0.431
3141843SHACKLE
Adder
0.835
3141766HARMONY
Solar/Wind Harmer
0.033
3146206CASHIE
Solar/Wind Harmer
0.162
971547AH1-271 GEN
Solar/Wind Harmer
3.458
3145893MURPHYS
Solar/Wind Harmer
0.648
3145893MURPHYS
Solar/Wind Harmer
0.72
315693AD1-088 GEN
Solar/Wind Harmer
7.741
960081AF2-299 GEN
Solar/Wind Harmer
1.545
962491AG1-098 GEN
Solar/Wind Harmer
9.173
3146173TUNIS
Solar/Wind Harmer
0.161
3138133OCRAN
Solar/Wind Harmer
0.096
3145683EARLEYS
Solar/Wind Harmer
0.159
3146263WOODLND
Solar/Wind Harmer
0.158
971795AH1-408 GEN
Solar/Wind Harmer
10.53
316011AB1-132 GEN
Solar/Wind Harmer
2.868
962571AG1-106 GEN
Solar/Wind Harmer
2.244
316190AA2-174 GEN
Solar/Wind Harmer
0
3147043LAWRENC
Adder
1.417
3145963POPLR C
Solar/Wind Harmer
0.156
3145823KELFORD
Solar/Wind Harmer
0.156
3145783HORNRTN
Solar/Wind Harmer
0.155
3145796HORNRTN
Solar/Wind Harmer
0.512
3145796HORNRTN
Solar/Wind Harmer
0.155
316174AB2-169 GEN
Solar/Wind Harmer
0.004
316212AC1-099_GEN
Solar/Wind Harmer
0.783
962861AG1-135 GEN
Solar/Wind Harmer
4.841
316129AC1-054 GEN
Solar/Wind Harmer
0.567
3146293MARTNCO
Solar/Wind Harmer
0.139
971065AG2-659 GEN
Solar/Wind Harmer
6.41
315687AD1-152 GEN
Solar/Wind Harmer
0.005
3141726DUNNSVL
Solar/Wind Harmer
0.591
315722AD1-056 GEN
Solar/Wind Harmer
0.935
3145746EVERETS
Solar/Wind Harmer
0.147
3145746EVERETS
Solar/Wind Harmer
0.147
966881AG1-559 GEN
Solar/Wind Harmer
0.17
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970937AG2-583 GEN
Solar/Wind Harmer
8.939
3150351NORNECKC2
Adder
1.452
316494AC1-189 GEN
Solar/Wind Harmer
0.491
970685AG2-442 GEN
Solar/Wind Harmer
10.862
963171AG1-166 GEN
Solar/Wind Harmer
0.774
971563AH1-280 GEN
Solar/Wind Harmer
1.548
3144293JTRSVLE
Adder
0.462
3146233WITAKRS
Solar/Wind Harmer
0.573
961671AG1-007 GEN
Solar/Wind Harmer
0.022
3146083TARBORO
Solar/Wind Harmer
0.144
3145493TOT1
Solar/Wind Harmer
0.639
3146926FARMVIL
Solar/Wind Harmer
0.086
3145543BTLEBRO
Solar/Wind Harmer
0.141
3145543BTLEBRO
Solar/Wind Harmer
0.113
316359AB2-059 GEN
Solar/Wind Harmer
0.508
316049AB1-081 GEN
Solar/Wind Harmer
0.809
3142053HEARTS
Solar/Wind Harmer
0.249
970401AG2-262 GEN
Solar/Wind Harmer
0.817
316337AD2-073 GEN
Solar/Wind Harmer
0.12
972197AH1-683 GEN
Adder
2.865
972219AH1-694 GEN
Adder
2.063
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.055
972003AH1-546 GEN
Solar/Wind Harmer
5.523
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971377AH1-170 GEN
Solar/Wind Harmer
1.278
3147623JAMES R
Solar/Wind Harmer
0.278
972135AH1-637 GEN
Solar/Wind Harmer
0.998
316045AC1-158 PL2
Solar/Wind Helper
17.173
316006AB2-029 C
Solar/Wind Helper
0.112
316303AF2-085
50/50
3.634
971285AH1-108 GEN
50/50
1.469
315244AE2-183_ST
50/50
5.196
963041AG1-153 GEN
50/50
4.793
3151081ELIZAR1
50/50
17.423
3151091ELIZAR2
50/50
17.121
941591AE2-156 GEN
50/50
15.921
3152611GOSPORTB
50/50
2.419
3152621GOSPORTC
50/50
2.053
3152601GOSPORTA
50/50
1.894
315779AE2-040
50/50
2.493
316233AE1-074 FULL
Solar/Wind Harmer
0.156
971281AH1-106 GEN
Solar/Wind Harmer
2.702
971283AH1-107 GEN
Solar/Wind Harmer
2.702
941031AE2-094 GEN
Solar/Wind Harmer
34.43
944011AF1-069 GEN
Solar/Wind Harmer
11.25
970673AG2-436 GEN
Solar/Wind Harmer
39.174
970673AG2-436 GEN
Solar/Wind Harmer
26.116
3143316POE
Solar/Wind Harmer
0.721
971967AH1-528 GEN
Solar/Wind Harmer
28.994
316315AB2-025 C
Solar/Wind Harmer
0.144
315814AE2-033 C
Solar/Wind Harmer
14.072
957871AF2-081 GEN
Solar/Wind Harmer
8.849
971445AH1-216 GEN
Solar/Wind Harmer
12.508
319010AE1-072 C
Solar/Wind Harmer
0.893
3146406KITTY HAWK
Solar/Wind Harmer
0.022
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.121
316311AC2-079 GEN
Solar/Wind Harmer
5.087
316305AF2-043 C
Solar/Wind Harmer
0.001
972265AH1-717 GEN
Adder
13.734
3151201GRAVEL4
Adder
12.875
3151191GRAVEL3
Adder
12.712
3151211GRAVEL5
Adder
12.712
316369SG1_INVT
Solar/Wind Harmer
0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.947
315835AF2-110_GEN
Solar/Wind Harmer
1.21
313526AB2-022
Solar/Wind Harmer
0.095
3146486SUNBURY
Solar/Wind Harmer
0.175
3146486SUNBURY
Solar/Wind Harmer
0.175
316321Z2-027
Solar/Wind Harmer
0.033
3146396TANGLEW
Solar/Wind Harmer
0.483
3145176PASQUOTANK
Solar/Wind Harmer
0.109
970085AG2-068 GEN
Solar/Wind Harmer
9.195
970581AG2-369 GEN
Solar/Wind Harmer
7.908
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.17
3130156CHOWAN
Solar/Wind Harmer
0.17
315976AC1-164 GENA
Solar/Wind Harmer
17.467
316169AC1-164_GENC
Solar/Wind Harmer
15.09
315975AC1-164 GENB
Solar/Wind Harmer
0.517
3138283WHITEMARSH
Solar/Wind Harmer
0.039
971167AH1-042 GEN
Solar/Wind Harmer
14.927
316312AB1-027
Solar/Wind Harmer
0.3
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
315816AE2-034 GEN
Solar/Wind Harmer
0.714
3143873LANEXA
Solar/Wind Harmer
0.099
3130546PLYMOUTH
Solar/Wind Harmer
0.164
315732AD1-074 GEN1
Solar/Wind Harmer
0.939
315733AD1-074 GEN2
Solar/Wind Harmer
0.939
315735AD1-075 GEN1
Solar/Wind Harmer
0.47
965291AG1-394 GEN
Solar/Wind Harmer
0.726
970189AG2-124 GEN
Solar/Wind Harmer
4.842
316314AB2-024 C
Solar/Wind Harmer
0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.032
3146206CASHIE
Solar/Wind Harmer
0.162
970601AG2-382 GEN
Solar/Wind Harmer
6.052
3145893MURPHYS
Solar/Wind Harmer
0.437
3145893MURPHYS
Solar/Wind Harmer
0.162
3145513AHOSKIE
Solar/Wind Harmer
0.334
3145513AHOSKIE
Solar/Wind Harmer
0.16
3141913WHIT STONE
Solar/Wind Harmer
0.16
3146043SEABORD
Solar/Wind Harmer
0.16
316087AB2-174 GEN
Solar/Wind Harmer
0.005
972189AH1-679 GEN
Adder
2.672
3138133OCRAN
Solar/Wind Harmer
0.048
315607AA1-063A GEN
Solar/Wind Harmer
0.325
3145683EARLEYS
Solar/Wind Harmer
0.318
3145683EARLEYS
Solar/Wind Harmer
0.159
3145683EARLEYS
Solar/Wind Harmer
0.159
3141783LANCAST
Solar/Wind Harmer
0.095
3141783LANCAST
Solar/Wind Harmer
0.063
315652AC1-086 GEN
Solar/Wind Harmer
17.349
3137643SOCKMAN
Solar/Wind Harmer
0.629
3145796HORNRTN
Solar/Wind Harmer
0.497
3145796HORNRTN
Solar/Wind Harmer
0.062
962981AG1-147 GEN
Solar/Wind Harmer
5.785
3146033SCOT NK
Solar/Wind Harmer
0.614
970327AG2-215 GEN
Solar/Wind Harmer
5.03
970831AG2-522 GEN
Solar/Wind Harmer
6.456
316005AA1-067
Solar/Wind Harmer
0.158
3145746EVERETS
Solar/Wind Harmer
0.587
3145746EVERETS
Solar/Wind Harmer
0.147
3145746EVERETS
Solar/Wind Harmer
0.147
3145746EVERETS
Solar/Wind Harmer
0.147
970181AG2-120 GEN
Solar/Wind Harmer
1.837
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
2.45
3144303KENBRDG
Solar/Wind Harmer
0.117
3141813NORNECK
Solar/Wind Harmer
0.146
957861AF2-080 GEN
Solar/Wind Harmer
6.272
970683AG2-441 GEN
Solar/Wind Harmer
9.698
970681AG2-440 GEN
Solar/Wind Harmer
7.758
946301AF1-294 GEN
Solar/Wind Harmer
2.864
961791AG1-021 GEN
Solar/Wind Harmer
1.393
315657AE1-056 GEN
Solar/Wind Harmer
4.998
316420AA1-050 GEN
Solar/Wind Harmer
0.005
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.144
3145573BETHELC
Solar/Wind Harmer
0.144
970285AG2-188 GEN
Solar/Wind Harmer
10.95
971845AH1-439 GEN
Solar/Wind Harmer
6.225
3150411LDYSMT5
Adder
18.406
3150381LDYSMT2
Adder
17.615
972213AH1-691 GEN
Adder
2.98
972215AH1-692 GEN
Adder
2.98
316118AC1-105 GEN
Solar/Wind Harmer
0.352
3147173SINAI
Solar/Wind Harmer
0.134
3147243WELCO
Solar/Wind Harmer
0.084
316223AC1-118
Solar/Wind Harmer
0.093
972205AH1-687 GEN
Adder
5.489
970865AG2-541 GEN
Solar/Wind Harmer
4.099
971447AH1-217 GEN
Solar/Wind Harmer
3.524
316164AC1-076 GEN
Solar/Wind Helper
1.636
3150921YORKTN3
Adder
4.366
970917AG2-570 GEN
Solar/Wind Harmer
15.39
3146626S HERTFORD
Solar/Wind Harmer
0.173
3145273HOLLAND
Solar/Wind Harmer
0.129
3142946ENON
Solar/Wind Harmer
0.058
316382AG1-145 C
Solar/Wind Harmer
0.001
970293AG2-193 GEN
Solar/Wind Harmer
1.821
3146376EDENTON
Solar/Wind Harmer
0.17
3142416OLDCHRC
Solar/Wind Harmer
1.628
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
315614AA2-178 GEN
Solar/Wind Harmer
0.952
316365GEN2_N
Solar/Wind Harmer
0.37
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
971157AH1-035 GEN
Solar/Wind Harmer
1.967
315737AD1-076 GEN
Solar/Wind Harmer
2.103
3141843SHACKLE
Adder
0.835
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
2.172
316156AD2-030 GEN
Solar/Wind Harmer
0.12
3141873WAN 176
Solar/Wind Harmer
2.887
3146206CASHIE
Solar/Wind Harmer
0.162
3145893MURPHYS
Solar/Wind Harmer
0.271
3145893MURPHYS
Solar/Wind Harmer
0.162
316473AC1-191 GEN
Solar/Wind Harmer
0.547
957521AF2-046 GEN
Solar/Wind Harmer
12.028
961681AG1-008 GEN
Solar/Wind Harmer
12.028
3146173TUNIS
Solar/Wind Harmer
0.161
3156021HOLLOMANSOL
Solar/Wind Harmer
0.727
316463AE2-346 GEN
Solar/Wind Harmer
0.137
316140AB2-099
Solar/Wind Harmer
0.057
962331AG1-082 GEN
Solar/Wind Harmer
1.706
313506AB2-031 GEN
Solar/Wind Harmer
0.491
3146263WOODLND
Solar/Wind Harmer
0.158
316478AD1-087 GEN
Solar/Wind Harmer
0.553
316486AD2-202 GEN
Solar/Wind Harmer
0.162
3142666NORTHAMPTON
Solar/Wind Harmer
0.158
3147043LAWRENC
Solar/Wind Harmer
0.094
3145963POPLR C
Solar/Wind Harmer
0.156
316317KELFORD C
Solar/Wind Harmer
0.015
3145823KELFORD
Solar/Wind Harmer
0.156
3145796HORNRTN
Solar/Wind Harmer
0.621
3145796HORNRTN
Solar/Wind Harmer
0.155
962971AG1-146 GEN
Solar/Wind Harmer
2.479
970009AG2-005 GEN
Solar/Wind Harmer
1.144
316210AC1-098 GEN
Solar/Wind Harmer
1.405
970909AG2-566 GEN
Solar/Wind Harmer
1.611
316404AE1-155 C
Solar/Wind Harmer
0.034
3145933PARMELE
Solar/Wind Harmer
0.15
966801AG1-551 GEN
Solar/Wind Harmer
1.752
315724AD1-057 GEN
Solar/Wind Harmer
0.554
3145746EVERETS
Solar/Wind Harmer
0.147
3145746EVERETS
Solar/Wind Harmer
0.147
316131AB2-060 GEN
Solar/Wind Harmer
0.461
316327AA2-057 GEN
Solar/Wind Harmer
0.221
964241AG1-285 GEN
Solar/Wind Harmer
9.755
315785AD2-033 C
Solar/Wind Harmer
1.187
970257AG2-171 GEN
Solar/Wind Harmer
4.666
959311AF2-222 GEN
Solar/Wind Harmer
12.953
3150351NORNECKC2
Adder
1.476
963181AG1-167 GEN
Solar/Wind Harmer
0.581
3144293JTRSVLE
Adder
0.462
3147133PAMPLIN
Solar/Wind Harmer
0.455
971193AH1-056 GEN
Solar/Wind Harmer
8.824
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146233WITAKRS
Solar/Wind Harmer
0.722
3146233WITAKRS
Solar/Wind Harmer
0.098
3146073TAR RVR
Solar/Wind Harmer
0.144
3146083TARBORO
Solar/Wind Harmer
0.144
3138543CONSLDL
Solar/Wind Harmer
0.095
3146926FARMVIL
Solar/Wind Harmer
0.086
961601AG1-000A GEN
Solar/Wind Harmer
10.061
3145543BTLEBRO
Solar/Wind Harmer
0.141
3145543BTLEBRO
Solar/Wind Harmer
0.141
971623AH1-311 GEN
Solar/Wind Harmer
0.283
971781AH1-399 GEN
Solar/Wind Harmer
0.181
3150401LDYSMT4
Adder
18.348
3150371LDYSMT1
Adder
17.729
3146776BUCKING
Solar/Wind Harmer
0.049
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.713
3141906WESTMOR
Solar/Wind Harmer
0.052
971683AH1-343 GEN
Solar/Wind Harmer
4.538
970737AG2-469 GEN
Solar/Wind Harmer
5.206
316283AC2-100 C
Solar/Wind Harmer
0.236
970221AG2-151 GEN
Solar/Wind Harmer
6.389
316044AC1-158 PL1
Solar/Wind Helper
5.365
316450AC1-158 RIC
Solar/Wind Helper
1.431
3146626S HERTFORD
Solar/Wind Harmer
0.173
3142946ENON
Solar/Wind Harmer
0.017
3150691DARBY 3
Adder
12.388
3150701DARBY 4
Adder
12.359
3150681DARBY 2
Adder
12.344
3150671DARBY 1
Adder
12.33
315742AE1-103 GEN
Solar/Wind Harmer
0.002
3146376EDENTON
Solar/Wind Harmer
0.754
3146376EDENTON
Solar/Wind Harmer
0.754
316075AC2-137 C
Solar/Wind Harmer
0.046
3142296MT RD221
Adder
0.537
970099AG2-077 GEN
Solar/Wind Harmer
17.581
316065AD1-022 GEN
Solar/Wind Harmer
7.487
3145893MURPHYS
Solar/Wind Harmer
1.084
3145893MURPHYS
Solar/Wind Harmer
0.291
966871AG1-558 GEN
Solar/Wind Harmer
0.187
3146173TUNIS
Solar/Wind Harmer
0.161
3146173TUNIS
Solar/Wind Harmer
0.161
316181AB2-040 GEN
Solar/Wind Harmer
0.23
3142666NORTHAMPTON
Solar/Wind Harmer
0.158
3142666NORTHAMPTON
Solar/Wind Harmer
0.158
3142666NORTHAMPTON
Solar/Wind Harmer
0.158
3142666NORTHAMPTON
Solar/Wind Harmer
0.095
316426AA2-053 GEN
Solar/Wind Harmer
0.53
3145593CAROLNA
Solar/Wind Harmer
0.156
3145593CAROLNA
Solar/Wind Harmer
0.156
966811AG1-552 GEN
Solar/Wind Harmer
1.698
3145593CAROLNA
Solar/Wind Harmer
0.195
3145783HORNRTN
Solar/Wind Harmer
2.766
3145783HORNRTN
Solar/Wind Harmer
2.213
3145783HORNRTN
Solar/Wind Harmer
0.692
3145783HORNRTN
Solar/Wind Harmer
0.277
3145796HORNRTN
Solar/Wind Harmer
0.466
971741AH1-377 GEN
Solar/Wind Harmer
15.218
970301AG2-198 GEN
Solar/Wind Harmer
6.446
316274AC1-208 GEN
Solar/Wind Harmer
0.781
958261AF2-120 GEN
Solar/Wind Harmer
4.978
3145933PARMELE
Solar/Wind Harmer
0.301
3145933PARMELE
Solar/Wind Harmer
0.15
939181AE1-148 GEN
Solar/Wind Harmer
7.079
957411AF2-035 GEN
Solar/Wind Harmer
6.288
970317AG2-208 GEN
Solar/Wind Harmer
5.826
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.011
970323AG2-213 GEN
Solar/Wind Harmer
6.221
971775AH1-396 GEN
Solar/Wind Harmer
0.233
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.525
3150341NORNECKC1
Adder
1.513
958211AF2-115 GEN
Solar/Wind Harmer
1.742
963191AG1-168 GEN
Solar/Wind Harmer
0.581
3144293JTRSVLE
Adder
0.462
3144293JTRSVLE
Adder
0.389
3147133PAMPLIN
Solar/Wind Harmer
0.145
3147133PAMPLIN
Solar/Wind Harmer
0.116
3145493TOT1
Solar/Wind Harmer
0.333
3145453TOT5
Solar/Wind Harmer
0.2
3145603CNETO
Solar/Wind Harmer
0.133
315673AE1-157 GEN
Solar/Wind Harmer
9.924
961601AG1-000A GEN
Solar/Wind Harmer
2.515
316263AC1-034 GEN
Solar/Wind Harmer
5.374
962561AG1-105 GEN
Solar/Wind Harmer
6.736
964791AG1-342 GEN
Solar/Wind Harmer
2.673
3146843MT LREL
Solar/Wind Harmer
0.139
3146843MT LREL
Solar/Wind Harmer
0.139
316468AD1-105 GEN
Solar/Wind Harmer
-0.045
3150391LDYSMT3
Adder
18.314
972195AH1-682 GEN
Adder
2.407
3146776BUCKING
Solar/Wind Harmer
0.547
3146776BUCKING
Solar/Wind Harmer
0.044
316222AC1-221 GEN
Solar/Wind Harmer
0.503
971489AH1-241 GEN
Solar/Wind Harmer
6.389
316447AC1-158 HLD
Solar/Wind Helper
11.807
LAGNLTFEXP_LAGN->PJM
CLTF
6.271
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.977
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.753
MECLTFEXP_MEC->PJM
CLTF
2.757
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.05
TVALTFEXP_TVA->PJM
CLTF
3.173
SIGELTFEXP_SIGE->PJM
CLTF
0.083
NYPJM->LTFIMP_NY
CLTF
2.427
LGEELTFEXP_LGEE->PJM
CLTF
1
WECLTFEXP_WEC->PJM
CLTF
0.483
CPLELTFEXP_CPLE->PJM
CLTF
9.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.048

Details for 8POSSUM-BURCHES 500.0 kV Ckt 1 line l/o AP_P1-2_PE-500-406T_SRT-A


Base Case Flowgate

Area:DVP/PJM
Facility Description:
8POSSUM-BURCHES 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-406T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.05 %
Rating:2913.06 MVA
Rating Type:B
MVA to Mitigate:3060.21
MW Contribution:6.0
Bus #Bus NameTypeMW Contribution
972223AH1-696 GEN
50/50
15.369
3150151POSSMC1
50/50
1.946
3141346CRANES
50/50
0.214
3150011OMF A
50/50
0.313
3140676OCCOQUN
50/50
0.415
972197AH1-683 GEN
50/50
3.446
972219AH1-694 GEN
50/50
2.481
972135AH1-637 GEN
Solar/Wind Harmer
1.281
966881AG1-559 GEN
Solar/Wind Harmer
0.172
316337AD2-073 GEN
Solar/Wind Harmer
0.125
3150351NORNECKC2
Adder
1.412
3141726DUNNSVL
Solar/Wind Harmer
0.564
962861AG1-135 GEN
Solar/Wind Harmer
4.477
3138133OCRAN
Solar/Wind Harmer
0.082
3141766HARMONY
Solar/Wind Harmer
0.027
3142416OLDCHRC
Solar/Wind Harmer
0.355
3142416OLDCHRC
Solar/Wind Harmer
0.136
971777AH1-397 GEN
Solar/Wind Harmer
0.36
3141843SHACKLE
Adder
0.697
3142433PROV 92
Solar/Wind Harmer
0.542
3142433PROV 92
Adder
0.264
3142433PROV 92
Adder
0.264
3143096IRON208
Adder
0.563
316045AC1-158 PL2
Solar/Wind Harmer
2.091
944631AF1-128 GEN
Adder
63.967
3142543TWELFTH
Solar/Wind Harmer
0.013
3150851SPRUNCC
Adder
0.616
316159AE1-175 C
Solar/Wind Harmer
0.115
3143526WINTERP
Solar/Wind Harmer
0.692
971317AH1-138 GEN
Solar/Wind Harmer
0.993
3143226MDLTHAN
Solar/Wind Harmer
0.132
970129AG2-093 GEN
Solar/Wind Harmer
3.759
316458AB2-190 GEN2
Solar/Wind Harmer
0.709
315671AE2-027_GEN
Solar/Wind Harmer
8.445
3138126ROCKLANDING
Solar/Wind Harmer
0.061
971069AG2-661 GEN
Solar/Wind Harmer
2.343
971647AH1-324 GEN
Solar/Wind Harmer
5.603
3147666LOUISA
Solar/Wind Harmer
0.525
961611AG1-000B GEN
Solar/Wind Harmer
6.873
316192AB2-158 GEN
Solar/Wind Harmer
0.74
3151171GRAVELC
Adder
1.391
3145336SMITFLD
Solar/Wind Harmer
0.52
316294AC1-161 GEN
Solar/Wind Harmer
2.247
970659AG2-427 GEN
Solar/Wind Harmer
6.262
316381AD1-082 GEN
Solar/Wind Harmer
0.135
970661AG2-428 GEN
Solar/Wind Harmer
12.841
316375AC2-012 GEN
Solar/Wind Harmer
0.003
3150981CHESPKA
Adder
1.611
944591AF1-124 GEN
Solar/Wind Harmer
29.132
316072AD1-144
Solar/Wind Harmer
0.047
316254AC1-120 GEN1
Solar/Wind Harmer
0.274
316388AE2-253 GEN
Solar/Wind Harmer
0.402
3146456SLIGO L269
Solar/Wind Harmer
0.128
316246AF1-032 C
Solar/Wind Harmer
0.058
316093AE2-104_GEN
Solar/Wind Harmer
2.148
939411AE1-173 GEN
Solar/Wind Harmer
54.47
940641AE2-051 GEN
Solar/Wind Harmer
10.185
3146516WINFALL
Solar/Wind Harmer
0.409
3146516WINFALL
Solar/Wind Harmer
0.126
3143336POWHATN
Solar/Wind Harmer
2.23
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.124
3151751LOISA D
Adder
8.077
316006AB2-029 C
Solar/Wind Harmer
0.001
971685AH1-345 GEN
Solar/Wind Harmer
0.923
316336AC2-165 C
Solar/Wind Harmer
0.005
315683AE1-153 C
Solar/Wind Harmer
9.818
3145663CRESWEL
Solar/Wind Harmer
0.344
971163AH1-040 GEN
Solar/Wind Harmer
9.834
3150281M RUN A
Adder
16.653
3150221REMNGT2
Adder
15.477
3150211REMNGT1
Adder
15.375
972201AH1-685 GEN
Adder
2.67
3146206CASHIE
Solar/Wind Harmer
0.121
971547AH1-271 GEN
Solar/Wind Harmer
2.578
3145893MURPHYS
Solar/Wind Harmer
0.482
3145893MURPHYS
Solar/Wind Harmer
0.536
316023GEN1_S
Solar/Wind Harmer
0.271
970919AG2-571 GEN
Solar/Wind Harmer
4.269
3146173TUNIS
Solar/Wind Harmer
0.12
970087AG2-069 GEN
Solar/Wind Harmer
9.586
3145683EARLEYS
Solar/Wind Harmer
0.119
960081AF2-299 GEN
Solar/Wind Harmer
1.144
970937AG2-583 GEN
Solar/Wind Harmer
7.301
3146263WOODLND
Solar/Wind Harmer
0.119
957481AF2-042 GEN
Solar/Wind Harmer
31.564
3145963POPLR C
Solar/Wind Harmer
0.118
3145823KELFORD
Solar/Wind Harmer
0.118
316011AB1-132 GEN
Solar/Wind Harmer
2.146
971795AH1-408 GEN
Solar/Wind Harmer
7.87
962571AG1-106 GEN
Solar/Wind Harmer
1.679
316190AA2-174 GEN
Solar/Wind Harmer
0
315693AD1-088 GEN
Solar/Wind Harmer
5.655
316174AB2-169 GEN
Solar/Wind Harmer
0.003
962491AG1-098 GEN
Solar/Wind Harmer
6.721
3147043LAWRENC
Adder
1.063
3145783HORNRTN
Solar/Wind Harmer
0.117
3145796HORNRTN
Solar/Wind Harmer
0.386
3145796HORNRTN
Solar/Wind Harmer
0.117
3146926FARMVIL
Solar/Wind Harmer
0.07
316212AC1-099_GEN
Solar/Wind Harmer
0.599
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.046
3146293MARTNCO
Solar/Wind Harmer
0.107
972003AH1-546 GEN
Solar/Wind Harmer
4.897
972277AH1-723 GEN
Adder
68.708
316129AC1-054 GEN
Solar/Wind Harmer
0.433
963171AG1-166 GEN
Solar/Wind Harmer
0.613
971563AH1-280 GEN
Solar/Wind Harmer
1.225
3144293JTRSVLE
Adder
0.366
971065AG2-659 GEN
Solar/Wind Harmer
4.897
970685AG2-442 GEN
Solar/Wind Harmer
8.558
3145746EVERETS
Solar/Wind Harmer
0.114
3145746EVERETS
Solar/Wind Harmer
0.114
315722AD1-056 GEN
Solar/Wind Harmer
0.721
316237AB2-079_GEN
Solar/Wind Harmer
0.001
316494AC1-189 GEN
Solar/Wind Harmer
0.383
315687AD1-152 GEN
Solar/Wind Harmer
0.004
971377AH1-170 GEN
Solar/Wind Harmer
1.2
3147623JAMES R
Solar/Wind Harmer
0.261
223401AF1-299 GEN
Solar/Wind Helper
0.698
233930AB2-032 GEN
Solar/Wind Helper
0.368
233915AB1-141 GEN
Solar/Wind Helper
0.486
232422X3-066 FULL
Solar/Wind Helper
0.11
233964AF2-378 GEN
Solar/Wind Helper
0.04
232426Y1-080 FULL
Solar/Wind Helper
0.037
232428Y3-058 C
Solar/Wind Helper
0.325
233998TM1NIN_3.36
Solar/Wind Helper
0.251
232404W1-003 C
Solar/Wind Helper
0.487
233954AC2-188 GEN
Solar/Wind Helper
0.223
233950AC2-186 GEN
Solar/Wind Helper
0.111
232434Z2-077 GEN
Solar/Wind Helper
0.122
233972AC1-094 C
Solar/Wind Helper
0.289
3150091POSSM6B
50/50
1.444
3150071POSSM 5
50/50
88.927
3150181POSSMC2
50/50
1.962
3150181POSSMC2
50/50
1.946
3150181POSSMC2
50/50
1.946
957191AF2-013 GEN
50/50
14.065
3150391LDYSMT3
50/50
22.026
972195AH1-682 GEN
50/50
2.894
315673AE1-157 GEN
Solar/Wind Harmer
10.452
957411AF2-035 GEN
Solar/Wind Harmer
6.351
970317AG2-208 GEN
Solar/Wind Harmer
5.884
316468AD1-105 GEN
Solar/Wind Harmer
-0.047
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.483
3150341NORNECKC1
Adder
1.471
958261AF2-120 GEN
Solar/Wind Harmer
4.633
966871AG1-558 GEN
Solar/Wind Harmer
0.16
3142296MT RD221
Adder
0.436
316075AC2-137 C
Solar/Wind Harmer
0.037
3150691DARBY 3
Adder
9.75
3150701DARBY 4
Adder
9.728
3150681DARBY 2
Adder
9.716
3150671DARBY 1
Adder
9.705
3142366NRTHEST
Adder
0.443
3142946ENON
Solar/Wind Harmer
0.013
316447AC1-158 HLD
Solar/Wind Harmer
1.437
3143526WINTERP
Solar/Wind Harmer
0.692
944641AF1-129 GEN
Adder
63.136
971223AH1-071 GEN
Solar/Wind Harmer
1.411
316240AF1-291 C
Solar/Wind Harmer
0.001
316033AB2-134 GEN
Solar/Wind Harmer
0.008
315697AD1-025 GEN
Solar/Wind Harmer
0.148
316236AE1-162_GEN
Solar/Wind Harmer
0.001
970657AG2-426 GEN
Solar/Wind Harmer
4.528
970657AG2-426 GEN
Solar/Wind Harmer
0.949
316036AC1-147 C
Solar/Wind Harmer
0.024
3150991CHESPKB
Adder
1.352
3150991CHESPKB
Adder
1.319
316316AC1-027 C
Solar/Wind Harmer
0.124
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.004
3145506HICKORY
Solar/Wind Harmer
0.514
3145506HICKORY
Solar/Wind Harmer
0.308
3145506HICKORY
Solar/Wind Harmer
0.077
316339AD2-160 GEN
Solar/Wind Harmer
0.208
316018AA1-139 ULT2
Solar/Wind Harmer
0.003
316017AA1-139 ULT1
Solar/Wind Harmer
0.072
3137176SLIGO L2192
Solar/Wind Harmer
0.51
3146456SLIGO L269
Solar/Wind Harmer
2.267
3130086AYDLETT
Solar/Wind Harmer
0.512
315651AD1-115 GEN
Solar/Wind Harmer
0.004
3146386ELIZ CT
Solar/Wind Harmer
0.127
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.126
3146516WINFALL
Solar/Wind Harmer
0.126
3146516WINFALL
Solar/Wind Harmer
0.126
3146626S HERTFORD
Solar/Wind Harmer
0.126
3146626S HERTFORD
Solar/Wind Harmer
0.126
3144356SAPONY
Solar/Wind Harmer
1.05
315742AE1-103 GEN
Solar/Wind Harmer
0.001
966001AG1-469 GEN
Solar/Wind Harmer
0.073
3146376EDENTON
Solar/Wind Harmer
0.553
3146376EDENTON
Solar/Wind Harmer
0.553
3151731LOISA B
Adder
8.077
3151721LOISA A
Adder
8.035
972185AH1-677 GEN
Adder
6.905
972187AH1-678 GEN
Adder
3.484
970933AG2-581 GEN
Solar/Wind Harmer
9.737
316065AD1-022 GEN
Solar/Wind Harmer
5.575
3145893MURPHYS
Solar/Wind Harmer
0.807
3145893MURPHYS
Solar/Wind Harmer
0.217
3146173TUNIS
Solar/Wind Harmer
0.12
3146173TUNIS
Solar/Wind Harmer
0.12
316181AB2-040 GEN
Solar/Wind Harmer
0.172
970099AG2-077 GEN
Solar/Wind Harmer
12.626
3142666NORTHAMPTON
Solar/Wind Harmer
0.118
3142666NORTHAMPTON
Solar/Wind Harmer
0.118
3142666NORTHAMPTON
Solar/Wind Harmer
0.118
3142666NORTHAMPTON
Solar/Wind Harmer
0.071
316426AA2-053 GEN
Solar/Wind Harmer
0.398
3145593CAROLNA
Solar/Wind Harmer
0.118
3145593CAROLNA
Solar/Wind Harmer
0.118
966811AG1-552 GEN
Solar/Wind Harmer
1.276
3145593CAROLNA
Solar/Wind Harmer
0.146
3145783HORNRTN
Solar/Wind Harmer
2.085
3145783HORNRTN
Solar/Wind Harmer
1.668
3145783HORNRTN
Solar/Wind Harmer
0.521
3145783HORNRTN
Solar/Wind Harmer
0.209
3145796HORNRTN
Solar/Wind Harmer
0.351
971741AH1-377 GEN
Solar/Wind Harmer
11.611
970301AG2-198 GEN
Solar/Wind Harmer
4.984
3146776BUCKING
Solar/Wind Harmer
0.462
3146776BUCKING
Solar/Wind Harmer
0.037
3145933PARMELE
Solar/Wind Harmer
0.231
3145933PARMELE
Solar/Wind Harmer
0.115
316274AC1-208 GEN
Solar/Wind Harmer
0.598
3147133PAMPLIN
Solar/Wind Harmer
0.115
3147133PAMPLIN
Solar/Wind Harmer
0.092
958211AF2-115 GEN
Solar/Wind Harmer
1.378
963191AG1-168 GEN
Solar/Wind Harmer
0.459
3144293JTRSVLE
Adder
0.366
3144293JTRSVLE
Adder
0.308
316034AC1-036 C
Solar/Wind Harmer
0.008
970323AG2-213 GEN
Solar/Wind Harmer
4.879
971775AH1-396 GEN
Solar/Wind Harmer
0.183
313527AB2-043 GEN
Solar/Wind Harmer
0.001
939181AE1-148 GEN
Solar/Wind Harmer
5.453
971489AH1-241 GEN
Solar/Wind Harmer
6.002
226929AD2-058 GEN
Solar/Wind Helper
0.401
208835TUHI V3-051
Solar/Wind Helper
0.03
208835TUHI V3-051
Solar/Wind Helper
0.03
233933AB2-153 GEN
Solar/Wind Helper
0.225
233944AB2-135 GEN
Solar/Wind Helper
0.569
232424Y1-079 C
Solar/Wind Helper
0.112
233987AB2-037 GEN
Solar/Wind Helper
2.251
234036AF2-325 C
Solar/Wind Helper
0.04
233946AB2-136 GEN
Solar/Wind Helper
0.546
233901CHERRYDALE C
Solar/Wind Helper
0.223
232408W1-005 C
Solar/Wind Helper
0.487
232410W1-006 C
Solar/Wind Helper
0.487
233939AC1-091 C
Solar/Wind Helper
0.335
233970AC1-092 C
Solar/Wind Helper
0.335
970053AG2-049 GEN
50/50
2.771
3150411LDYSMT5
50/50
22.136
3150381LDYSMT2
50/50
21.185
972213AH1-691 GEN
50/50
3.584
972215AH1-692 GEN
50/50
3.584
963051AG1-154 GEN
50/50
2.757
3141426STAFORD
Solar/Wind Harmer
0.039
944491AF1-114 GEN
Solar/Wind Harmer
0
316223AC1-118
Solar/Wind Harmer
0.105
972189AH1-679 GEN
Adder
2.375
3141813NORNECK
Solar/Wind Harmer
0.141
970327AG2-215 GEN
Solar/Wind Harmer
4.571
962981AG1-147 GEN
Solar/Wind Harmer
5.181
3141783LANCAST
Solar/Wind Harmer
0.083
3141783LANCAST
Solar/Wind Harmer
0.055
3138133OCRAN
Solar/Wind Harmer
0.041
3141913WHIT STONE
Solar/Wind Harmer
0.137
3141873WAN 176
Solar/Wind Harmer
0.027
316059AD1-063 C
Solar/Wind Harmer
0.001
316314AB2-024 C
Solar/Wind Harmer
0
316312AB1-027
Solar/Wind Harmer
0.244
315662AE1-191 GEN
Solar/Wind Harmer
0.004
315666AE1-190 GEN
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.04
3143873LANEXA
Solar/Wind Harmer
0.082
3142433PROV 92
Adder
0.264
3142433PROV 92
Adder
0.264
971167AH1-042 GEN
Solar/Wind Harmer
12.03
315976AC1-164 GENA
Solar/Wind Harmer
14.027
316169AC1-164_GENC
Solar/Wind Harmer
12.118
315975AC1-164 GENB
Solar/Wind Harmer
0.415
3138283WHITEMARSH
Solar/Wind Harmer
0.031
971285AH1-108 GEN
Adder
1.008
316233AE1-074 FULL
Solar/Wind Harmer
0.107
971281AH1-106 GEN
Solar/Wind Harmer
1.847
971283AH1-107 GEN
Solar/Wind Harmer
1.847
316164AC1-076 GEN
Solar/Wind Harmer
0.186
316132AB2-190 GEN1
Solar/Wind Harmer
0.709
316369SG1_INVT
Solar/Wind Harmer
0.005
972265AH1-717 GEN
Adder
10.151
3151201GRAVEL4
Adder
9.516
3151191GRAVEL3
Adder
9.395
3151211GRAVEL5
Adder
9.395
971445AH1-216 GEN
Solar/Wind Harmer
9.164
3143316POE
Solar/Wind Harmer
0.514
3151081ELIZAR1
Adder
11.83
3151091ELIZAR2
Adder
11.624
3152611GOSPORTB
Adder
1.643
3152621GOSPORTC
Adder
1.395
3152601GOSPORTA
Adder
1.287
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.088
316311AC2-079 GEN
Solar/Wind Harmer
3.686
957871AF2-081 GEN
Solar/Wind Harmer
6.385
316305AF2-043 C
Solar/Wind Harmer
0.001
319010AE1-072 C
Solar/Wind Harmer
0.645
3146406KITTY HAWK
Solar/Wind Harmer
0.016
315835AF2-110_GEN
Solar/Wind Harmer
0.877
313526AB2-022
Solar/Wind Harmer
0.069
3146486SUNBURY
Solar/Wind Harmer
0.127
3146486SUNBURY
Solar/Wind Harmer
0.127
316321Z2-027
Solar/Wind Harmer
0.024
3146396TANGLEW
Solar/Wind Harmer
0.35
3145176PASQUOTANK
Solar/Wind Harmer
0.079
316315AB2-025 C
Solar/Wind Harmer
0.101
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
315814AE2-033 C
Solar/Wind Harmer
9.914
941031AE2-094 GEN
Solar/Wind Harmer
22.955
944011AF1-069 GEN
Solar/Wind Harmer
7.5
3130156CHOWAN
Solar/Wind Harmer
0.124
3130156CHOWAN
Solar/Wind Harmer
0.124
970673AG2-436 GEN
Solar/Wind Harmer
26.361
970673AG2-436 GEN
Solar/Wind Harmer
17.574
971967AH1-528 GEN
Solar/Wind Harmer
19.675
315816AE2-034 GEN
Solar/Wind Harmer
0.528
3147346CASHSCORNER
Solar/Wind Harmer
0.285
3130546PLYMOUTH
Solar/Wind Harmer
0.122
315732AD1-074 GEN1
Solar/Wind Harmer
0.698
315733AD1-074 GEN2
Solar/Wind Harmer
0.698
315735AD1-075 GEN1
Solar/Wind Harmer
0.35
965291AG1-394 GEN
Solar/Wind Harmer
0.539
3146206CASHIE
Solar/Wind Harmer
0.121
970601AG2-382 GEN
Solar/Wind Harmer
4.511
3145893MURPHYS
Solar/Wind Harmer
0.326
3145893MURPHYS
Solar/Wind Harmer
0.121
970085AG2-068 GEN
Solar/Wind Harmer
6.391
970581AG2-369 GEN
Solar/Wind Harmer
5.496
3145513AHOSKIE
Solar/Wind Harmer
0.25
3145513AHOSKIE
Solar/Wind Harmer
0.12
3145683EARLEYS
Solar/Wind Harmer
0.239
3145683EARLEYS
Solar/Wind Harmer
0.119
3145683EARLEYS
Solar/Wind Harmer
0.119
3146043SEABORD
Solar/Wind Harmer
0.119
315607AA1-063A GEN
Solar/Wind Harmer
0.243
316087AB2-174 GEN
Solar/Wind Harmer
0.003
315652AC1-086 GEN
Solar/Wind Harmer
12.981
3137643SOCKMAN
Solar/Wind Harmer
0.471
3145796HORNRTN
Solar/Wind Harmer
0.374
3145796HORNRTN
Solar/Wind Harmer
0.047
3146033SCOT NK
Solar/Wind Harmer
0.467
970285AG2-188 GEN
Solar/Wind Harmer
9.159
971845AH1-439 GEN
Solar/Wind Harmer
5.245
970831AG2-522 GEN
Solar/Wind Harmer
4.918
972193AH1-681 GEN
Adder
2.634
972205AH1-687 GEN
Adder
4.919
315657AE1-056 GEN
Solar/Wind Harmer
3.968
946301AF1-294 GEN
Solar/Wind Harmer
2.267
961791AG1-021 GEN
Solar/Wind Harmer
1.103
970683AG2-441 GEN
Solar/Wind Harmer
7.642
970681AG2-440 GEN
Solar/Wind Harmer
6.113
3144303KENBRDG
Solar/Wind Harmer
0.091
971443AH1-215 GEN
Solar/Wind Harmer
1.921
316005AA1-067
Solar/Wind Harmer
0.123
3145746EVERETS
Solar/Wind Harmer
0.455
3145746EVERETS
Solar/Wind Harmer
0.114
3145746EVERETS
Solar/Wind Harmer
0.114
3145746EVERETS
Solar/Wind Harmer
0.114
970181AG2-120 GEN
Solar/Wind Harmer
1.422
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
957861AF2-080 GEN
Solar/Wind Harmer
4.883
316420AA1-050 GEN
Solar/Wind Harmer
0.004
233935AB2-179 C
Solar/Wind Helper
1.237
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.92
233990AG1-397 GEN
Solar/Wind Helper
0.259
232432Z2-076 GEN
Solar/Wind Helper
0.064
234033AF1-007_GEN
Solar/Wind Helper
6.733
3150101POSSM6S
50/50
2.207
3150081POSSM6A
50/50
1.444
3150151POSSMC1
50/50
1.946
3150151POSSMC1
50/50
1.946
3150331BIRCHWDA
50/50
29.368
3150021OMF B
50/50
0.313
3141316ARNOLDS
50/50
0.404
3150401LDYSMT4
50/50
22.067
3150371LDYSMT1
50/50
21.323
970497AG2-320 GEN
50/50
14.416
970737AG2-469 GEN
Solar/Wind Harmer
6.342
3141906WESTMOR
Solar/Wind Harmer
0.059
971781AH1-399 GEN
Solar/Wind Harmer
0.191
3150351NORNECKC2
Adder
1.435
316404AE1-155 C
Solar/Wind Harmer
0.032
970009AG2-005 GEN
Solar/Wind Harmer
1.04
962971AG1-146 GEN
Solar/Wind Harmer
2.22
316473AC1-191 GEN
Solar/Wind Harmer
0.469
316156AD2-030 GEN
Solar/Wind Harmer
0.101
3141873WAN 176
Solar/Wind Harmer
2.426
3141766HARMONY
Solar/Wind Harmer
1.82
3142416OLDCHRC
Solar/Wind Harmer
1.322
316280AD1-041 GEN
Solar/Wind Harmer
0.003
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141843SHACKLE
Adder
0.697
3142433PROV 92
Adder
0.264
3142433PROV 92
Adder
0.264
970293AG2-193 GEN
Solar/Wind Harmer
1.446
3142946ENON
Solar/Wind Harmer
0.045
3143096IRON208
Adder
0.563
3143096IRON208
Adder
0.552
316044AC1-158 PL1
Solar/Wind Harmer
0.654
316450AC1-158 RIC
Solar/Wind Harmer
0.174
3150861SPRUNCD
Adder
0.616
316382AG1-145 C
Solar/Wind Harmer
0.001
970133AG2-095 GEN
Solar/Wind Harmer
1.273
970129AG2-093 GEN
Solar/Wind Harmer
7.987
3150921YORKTN3
Adder
3.319
3144216WINCHST
Adder
0.497
315778AD1-151 GEN
Solar/Wind Harmer
10.543
965281AG1-393 GEN
Solar/Wind Harmer
1.404
315839AE2-212 C
Solar/Wind Harmer
0.001
3147666LOUISA
Solar/Wind Harmer
0.302
961611AG1-000B GEN
Solar/Wind Harmer
3.495
3151221GRAVEL6
Adder
9.505
3151171GRAVELC
Adder
1.829
3145336SMITFLD
Solar/Wind Harmer
0.052
315813AE1-149 C
Solar/Wind Harmer
6.935
315773AC2-141 GEN
Solar/Wind Harmer
4.737
970659AG2-427 GEN
Solar/Wind Harmer
1.37
3144536CHRHLND
Solar/Wind Harmer
0.019
316083AB2-161 GEN
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
2.731
3151101ELIZAR3
Adder
11.981
3144873MCLAUGH
Solar/Wind Harmer
0.003
944581AF1-123 GEN
Solar/Wind Harmer
29.029
944601AF1-125 GEN
Solar/Wind Harmer
28.582
316170AC1-121 GEN2
Solar/Wind Harmer
0.137
3146456SLIGO L269
Solar/Wind Harmer
0.128
971153AH1-033 GEN
Solar/Wind Harmer
1.481
316320Y1-086
Solar/Wind Harmer
0.001
3132273ORANGE
Solar/Wind Harmer
0.025
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.126
3146626S HERTFORD
Solar/Wind Harmer
0.126
3145273HOLLAND
Solar/Wind Harmer
0.094
316313AB2-026
Solar/Wind Harmer
0.079
316258AE1-075 C
Solar/Wind Harmer
0.095
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
1.895
3146376EDENTON
Solar/Wind Harmer
0.124
3151761LOISA E
Adder
16.466
972183AH1-676 GEN
Adder
132.605
315614AA2-178 GEN
Solar/Wind Harmer
0.703
3150301M RUN C
Adder
16.643
3150291M RUN B
Adder
16.52
3150231REMNGT3
Adder
16.71
3150241REMNGT4
Adder
15.58
972199AH1-684 GEN
Adder
2.362
972217AH1-693 GEN
Adder
2.054
971157AH1-035 GEN
Solar/Wind Harmer
1.461
3156081AA2-088 GEN
Solar/Wind Harmer
0.003
315737AD1-076 GEN
Solar/Wind Harmer
1.564
3146206CASHIE
Solar/Wind Harmer
0.121
3145893MURPHYS
Solar/Wind Harmer
0.202
3145893MURPHYS
Solar/Wind Harmer
0.121
316365GEN2_N
Solar/Wind Harmer
0.271
957521AF2-046 GEN
Solar/Wind Harmer
8.962
961681AG1-008 GEN
Solar/Wind Harmer
8.962
970917AG2-570 GEN
Solar/Wind Harmer
10.673
3146173TUNIS
Solar/Wind Harmer
0.12
3156021HOLLOMANSOL
Solar/Wind Harmer
0.544
316463AE2-346 GEN
Solar/Wind Harmer
0.103
316140AB2-099
Solar/Wind Harmer
0.043
962331AG1-082 GEN
Solar/Wind Harmer
1.276
3141196NOKESVL
Solar/Wind Harmer
0.475
3146263WOODLND
Solar/Wind Harmer
0.119
313506AB2-031 GEN
Solar/Wind Harmer
0.366
3145963POPLR C
Solar/Wind Harmer
0.118
3142666NORTHAMPTON
Solar/Wind Harmer
0.118
316317KELFORD C
Solar/Wind Harmer
0.011
3145823KELFORD
Solar/Wind Harmer
0.118
3147043LAWRENC
Solar/Wind Harmer
0.071
3145796HORNRTN
Solar/Wind Harmer
0.468
3145796HORNRTN
Solar/Wind Harmer
0.117
970909AG2-566 GEN
Solar/Wind Harmer
1.246
316478AD1-087 GEN
Solar/Wind Harmer
0.406
316486AD2-202 GEN
Solar/Wind Harmer
0.119
3146926FARMVIL
Solar/Wind Harmer
0.07
316210AC1-098 GEN
Solar/Wind Harmer
1.074
3146776BUCKING
Solar/Wind Harmer
0.042
3145933PARMELE
Solar/Wind Harmer
0.115
966801AG1-551 GEN
Solar/Wind Harmer
1.346
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
972255AH1-712 GEN
Adder
58.961
3147133PAMPLIN
Solar/Wind Harmer
0.361
971193AH1-056 GEN
Solar/Wind Harmer
7.005
963181AG1-167 GEN
Solar/Wind Harmer
0.459
3144293JTRSVLE
Adder
0.366
959311AF2-222 GEN
Solar/Wind Harmer
10.172
970257AG2-171 GEN
Solar/Wind Harmer
3.659
3145746EVERETS
Solar/Wind Harmer
0.114
3145746EVERETS
Solar/Wind Harmer
0.114
315785AD2-033 C
Solar/Wind Harmer
0.929
964241AG1-285 GEN
Solar/Wind Harmer
7.598
315724AD1-057 GEN
Solar/Wind Harmer
0.428
316131AB2-060 GEN
Solar/Wind Harmer
0.358
316327AA2-057 GEN
Solar/Wind Harmer
0.171
970221AG2-151 GEN
Solar/Wind Harmer
6.002
227287AC2-120 GEN
Solar/Wind Helper
1.283
226910AB2-157 C
Solar/Wind Helper
0.05
223402AF1-300 C
Solar/Wind Helper
0.698
233918AB1-142 GEN
Solar/Wind Helper
0.486
233982AB2-133 GEN
Solar/Wind Helper
0.346
233994AC2-023 GEN
Solar/Wind Helper
0.923
233996TM1833_GEN
Solar/Wind Helper
0.251
233997TMININ_4.2
Solar/Wind Helper
0.251
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.036
232406W1-004 FULL
Solar/Wind Helper
0.487
233952AC2-187 GEN
Solar/Wind Helper
0.223
233971AC1-093 C
Solar/Wind Helper
0.342
LAGNLTFEXP_LAGN->PJM
CLTF
10.825
CBM West 1LTFEXP_CBM-W1->PJM
CBM
63.366
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.907
MECLTFEXP_MEC->PJM
CLTF
7.822
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.705
TVALTFEXP_TVA->PJM
CLTF
5.449
SIGELTFEXP_SIGE->PJM
CLTF
0.246
NYPJM->LTFIMP_NY
CLTF
3.769
LGEELTFEXP_LGEE->PJM
CLTF
3.18
WECLTFEXP_WEC->PJM
CLTF
1.706
CPLELTFEXP_CPLE->PJM
CLTF
8.254
CBM West 2LTFEXP_CBM-W2->PJM
CBM
67.489
AG2-052LTFEXP_AG2-052->PJM
LTF
0.101
AH1-155LTFEXP_AH1-155->PJM
LTF
0.152

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:179.85 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5791.82
MW Contribution:8.67
Bus #Bus NameTypeMW Contribution
971133AH1-012 GEN
50/50
5.665
944641AF1-129 GEN
50/50
122.768
3142366NRTHEST
50/50
0.838
970533AG2-339 GEN
50/50
21.472
970531AG2-338 GEN
50/50
8.589
3150781HOPHCF2
50/50
0.977
3150791HOPHCF3
50/50
0.977
3150761HOPPOLC
50/50
0.62
971213AH1-066 GEN
50/50
0.857
3150691DARBY 3
50/50
18.39
316447AC1-158 HLD
Solar/Wind Harmer
6.696
971223AH1-071 GEN
Solar/Wind Harmer
2.827
3143526WINTERP
Solar/Wind Harmer
1.34
316240AF1-291 C
Solar/Wind Harmer
0.002
3150701DARBY 4
Adder
17.29
3150681DARBY 2
Adder
17.27
3150671DARBY 1
Adder
17.25
3142296MT RD221
Adder
0.765
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.27
316036AC1-147 C
Solar/Wind Harmer
0.045
3150991CHESPKB
Adder
2.513
3150991CHESPKB
Adder
2.452
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.23
316185AD1-033 GEN
Solar/Wind Harmer
0.007
970657AG2-426 GEN
Solar/Wind Harmer
8.383
970657AG2-426 GEN
Solar/Wind Harmer
1.758
3142946ENON
Solar/Wind Harmer
0.024
3145506HICKORY
Solar/Wind Harmer
0.955
3145506HICKORY
Solar/Wind Harmer
0.573
3145506HICKORY
Solar/Wind Harmer
0.143
316339AD2-160 GEN
Solar/Wind Harmer
0.386
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.133
316075AC2-137 C
Solar/Wind Harmer
0.065
3137176SLIGO L2192
Solar/Wind Harmer
0.945
3146456SLIGO L269
Solar/Wind Harmer
4.201
3130086AYDLETT
Solar/Wind Harmer
0.948
972185AH1-677 GEN
Adder
13.205
3144356SAPONY
Solar/Wind Harmer
1.967
3146386ELIZ CT
Solar/Wind Harmer
0.235
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
972187AH1-678 GEN
Adder
6.623
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
966871AG1-558 GEN
Solar/Wind Harmer
0.267
3146626S HERTFORD
Solar/Wind Harmer
0.231
3152251N ANNA1
50/50
19.951
971507AH1-251 GEN
50/50
16.627
970119AG2-088 GEN
50/50
35.342
3150851SPRUNCC
50/50
1.216
3143096IRON208
50/50
1.079
3152331SURRY 2
50/50
9.986
3150771HOPHCF1
50/50
0.977
316045AC1-158 PL2
Solar/Wind Harmer
9.742
3147666LOUISA
Solar/Wind Harmer
1.096
316192AB2-158 GEN
Solar/Wind Harmer
1.516
3143226MDLTHAN
Solar/Wind Harmer
0.265
3143526WINTERP
Solar/Wind Harmer
1.34
3152261N ANNA2
50/50
19.95
3150861SPRUNCD
50/50
1.216
3143096IRON208
50/50
1.079
3143096IRON208
50/50
1.057
3150801HOPHCF4
50/50
1.421
971211AH1-065 GEN
50/50
1.714
3151161SURRY 1
50/50
9.199
316044AC1-158 PL1
Solar/Wind Harmer
3.047
316450AC1-158 RIC
Solar/Wind Harmer
0.812
3147666LOUISA
Solar/Wind Harmer
0.63
315839AE2-212 C
Solar/Wind Harmer
0.002
315773AC2-141 GEN
Solar/Wind Harmer
8.863
965281AG1-393 GEN
Solar/Wind Harmer
2.583
970133AG2-095 GEN
Solar/Wind Harmer
2.314
315813AE1-149 C
Solar/Wind Harmer
12.857
970129AG2-093 GEN
Solar/Wind Harmer
14.547
944581AF1-123 GEN
Solar/Wind Harmer
54.129
944601AF1-125 GEN
Solar/Wind Harmer
53.295
315778AD1-151 GEN
Solar/Wind Harmer
19.229
3151101ELIZAR3
Adder
22.283
3144536CHRHLND
Solar/Wind Harmer
0.036
3144873MCLAUGH
Solar/Wind Harmer
0.006
970659AG2-427 GEN
Solar/Wind Harmer
2.537
961611AG1-000B GEN
Solar/Wind Harmer
6.393
3145336SMITFLD
Solar/Wind Harmer
0.096
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3151221GRAVEL6
Adder
17.41
3151171GRAVELC
Adder
3.35
970293AG2-193 GEN
Solar/Wind Harmer
2.553
3142946ENON
Solar/Wind Harmer
0.08
970661AG2-428 GEN
Solar/Wind Harmer
5.055
3142416OLDCHRC
Solar/Wind Harmer
2.311
3144216WINCHST
Adder
0.896
3146456SLIGO L269
Solar/Wind Harmer
0.237
971153AH1-033 GEN
Solar/Wind Harmer
2.744
3150921YORKTN3
Adder
5.966
316382AG1-145 C
Solar/Wind Harmer
0.002
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
3146516WINFALL
Solar/Wind Harmer
0.232
316473AC1-191 GEN
Solar/Wind Harmer
0.781
3146626S HERTFORD
Solar/Wind Harmer
0.231
3145273HOLLAND
Solar/Wind Harmer
0.173
316313AB2-026
Solar/Wind Harmer
0.144
316258AE1-075 C
Solar/Wind Harmer
0.172
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.453
3141843SHACKLE
Adder
1.161
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
3.026
316280AD1-041 GEN
Solar/Wind Harmer
0.005
3146376EDENTON
Solar/Wind Harmer
0.226
316156AD2-030 GEN
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
4.013
970917AG2-570 GEN
Solar/Wind Harmer
19.927
315614AA2-178 GEN
Solar/Wind Harmer
1.269
3150401LDYSMT4
Adder
29.389
3150371LDYSMT1
Adder
28.398
971157AH1-035 GEN
Solar/Wind Harmer
2.618
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
316365GEN2_N
Solar/Wind Harmer
0.488
315737AD1-076 GEN
Solar/Wind Harmer
2.798
962971AG1-146 GEN
Solar/Wind Harmer
3.462
3146206CASHIE
Solar/Wind Harmer
0.215
3145893MURPHYS
Solar/Wind Harmer
0.36
3145893MURPHYS
Solar/Wind Harmer
0.215
957521AF2-046 GEN
Solar/Wind Harmer
15.963
961681AG1-008 GEN
Solar/Wind Harmer
15.963
970009AG2-005 GEN
Solar/Wind Harmer
1.6
3146173TUNIS
Solar/Wind Harmer
0.213
3156021HOLLOMANSOL
Solar/Wind Harmer
0.965
316463AE2-346 GEN
Solar/Wind Harmer
0.182
316140AB2-099
Solar/Wind Harmer
0.076
962331AG1-082 GEN
Solar/Wind Harmer
2.263
316404AE1-155 C
Solar/Wind Harmer
0.047
3146263WOODLND
Solar/Wind Harmer
0.21
313506AB2-031 GEN
Solar/Wind Harmer
0.648
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3145963POPLR C
Solar/Wind Harmer
0.207
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.207
316478AD1-087 GEN
Solar/Wind Harmer
0.72
316486AD2-202 GEN
Solar/Wind Harmer
0.211
3147043LAWRENC
Solar/Wind Harmer
0.124
3145796HORNRTN
Solar/Wind Harmer
0.82
3145796HORNRTN
Solar/Wind Harmer
0.205
3150351NORNECKC2
Adder
2.075
316210AC1-098 GEN
Solar/Wind Harmer
1.857
3145933PARMELE
Solar/Wind Harmer
0.199
966801AG1-551 GEN
Solar/Wind Harmer
2.319
970909AG2-566 GEN
Solar/Wind Harmer
2.12
971781AH1-399 GEN
Solar/Wind Harmer
0.26
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
315724AD1-057 GEN
Solar/Wind Harmer
0.731
316327AA2-057 GEN
Solar/Wind Harmer
0.292
316131AB2-060 GEN
Solar/Wind Harmer
0.605
964241AG1-285 GEN
Solar/Wind Harmer
12.823
315785AD2-033 C
Solar/Wind Harmer
1.561
970257AG2-171 GEN
Solar/Wind Harmer
6.143
959311AF2-222 GEN
Solar/Wind Harmer
17.057
963181AG1-167 GEN
Solar/Wind Harmer
0.766
3144293JTRSVLE
Adder
0.609
3147133PAMPLIN
Solar/Wind Harmer
0.6
971193AH1-056 GEN
Solar/Wind Harmer
11.648
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.114
3146233WITAKRS
Solar/Wind Harmer
0.953
3146233WITAKRS
Solar/Wind Harmer
0.129
3146073TAR RVR
Solar/Wind Harmer
0.189
3146083TARBORO
Solar/Wind Harmer
0.189
3138543CONSLDL
Solar/Wind Harmer
0.125
3132273ORANGE
Solar/Wind Harmer
0.038
961601AG1-000A GEN
Solar/Wind Harmer
13.257
3145543BTLEBRO
Solar/Wind Harmer
0.186
3145543BTLEBRO
Solar/Wind Harmer
0.186
971623AH1-311 GEN
Solar/Wind Harmer
0.373
3141906WESTMOR
Solar/Wind Harmer
0.074
3146776BUCKING
Solar/Wind Harmer
0.066
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.481
970737AG2-469 GEN
Solar/Wind Harmer
7.427
316170AC1-121 GEN2
Solar/Wind Harmer
0.183
3151761LOISA E
Adder
22.218
972183AH1-676 GEN
Adder
173.787
970221AG2-151 GEN
Solar/Wind Harmer
8.67
971683AH1-343 GEN
Solar/Wind Harmer
5.958
316283AC2-100 C
Solar/Wind Harmer
0.309
972255AH1-712 GEN
Adder
76.037
3141316ARNOLDS
Adder
0.289
3141196NOKESVL
Solar/Wind Helper
1.164
940641AE2-051 GEN
Solar/Wind Harmer
19.885
939411AE1-173 GEN
Solar/Wind Harmer
105.071
3142543TWELFTH
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
4.205
315671AE2-027_GEN
Solar/Wind Harmer
15.49
970129AG2-093 GEN
Solar/Wind Harmer
6.846
316458AB2-190 GEN2
Solar/Wind Harmer
1.291
944591AF1-124 GEN
Solar/Wind Harmer
54.321
971069AG2-661 GEN
Solar/Wind Harmer
4.273
944631AF1-128 GEN
Adder
114.478
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.995
971647AH1-324 GEN
Solar/Wind Harmer
10.238
970659AG2-427 GEN
Solar/Wind Harmer
11.598
961611AG1-000B GEN
Solar/Wind Harmer
12.573
3145336SMITFLD
Solar/Wind Harmer
0.958
316381AD1-082 GEN
Solar/Wind Harmer
0.25
3151171GRAVELC
Adder
2.547
970661AG2-428 GEN
Solar/Wind Harmer
23.769
3142416OLDCHRC
Solar/Wind Harmer
0.62
3142416OLDCHRC
Solar/Wind Harmer
0.237
316388AE2-253 GEN
Solar/Wind Harmer
0.746
3138126ROCKLANDING
Solar/Wind Harmer
0.109
3146456SLIGO L269
Solar/Wind Harmer
0.237
316072AD1-144
Solar/Wind Harmer
0.086
316159AE1-175 C
Solar/Wind Harmer
0.205
316246AF1-032 C
Solar/Wind Harmer
0.107
971317AH1-138 GEN
Solar/Wind Harmer
1.763
316093AE2-104_GEN
Solar/Wind Harmer
3.967
3142433PROV 92
Solar/Wind Harmer
0.929
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
3146516WINFALL
Solar/Wind Harmer
0.752
3146516WINFALL
Solar/Wind Harmer
0.232
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.063
971777AH1-397 GEN
Solar/Wind Harmer
0.6
3141843SHACKLE
Adder
1.161
3141766HARMONY
Solar/Wind Harmer
0.045
3130156CHOWAN
Solar/Wind Harmer
0.226
966881AG1-559 GEN
Solar/Wind Harmer
0.262
970919AG2-571 GEN
Solar/Wind Harmer
7.971
970087AG2-069 GEN
Solar/Wind Harmer
17.86
3138133OCRAN
Solar/Wind Harmer
0.133
3145663CRESWEL
Solar/Wind Harmer
0.62
971163AH1-040 GEN
Solar/Wind Harmer
17.736
972197AH1-683 GEN
Adder
4.589
972219AH1-694 GEN
Adder
3.304
316336AC2-165 C
Solar/Wind Harmer
0.009
316023GEN1_S
Solar/Wind Harmer
0.488
3146206CASHIE
Solar/Wind Harmer
0.215
971547AH1-271 GEN
Solar/Wind Harmer
4.597
3145893MURPHYS
Solar/Wind Harmer
0.86
3145893MURPHYS
Solar/Wind Harmer
0.956
957481AF2-042 GEN
Solar/Wind Harmer
57.154
3146173TUNIS
Solar/Wind Harmer
0.213
960081AF2-299 GEN
Solar/Wind Harmer
2.037
962861AG1-135 GEN
Solar/Wind Harmer
6.776
3145683EARLEYS
Solar/Wind Harmer
0.211
315693AD1-088 GEN
Solar/Wind Harmer
10.092
3146263WOODLND
Solar/Wind Harmer
0.21
962491AG1-098 GEN
Solar/Wind Harmer
11.964
3146626S HERTFORD
Solar/Wind Harmer
0.231
970933AG2-581 GEN
Solar/Wind Harmer
18.312
315742AE1-103 GEN
Solar/Wind Harmer
0.003
957411AF2-035 GEN
Solar/Wind Harmer
9.66
970317AG2-208 GEN
Solar/Wind Harmer
8.949
3146376EDENTON
Solar/Wind Harmer
1.006
3146376EDENTON
Solar/Wind Harmer
1.006
315673AE1-157 GEN
Solar/Wind Harmer
15.472
3150391LDYSMT3
Adder
29.334
972195AH1-682 GEN
Adder
3.855
316065AD1-022 GEN
Solar/Wind Harmer
9.955
3145893MURPHYS
Solar/Wind Harmer
1.439
3145893MURPHYS
Solar/Wind Harmer
0.387
970099AG2-077 GEN
Solar/Wind Harmer
22.861
3146173TUNIS
Solar/Wind Harmer
0.213
3146173TUNIS
Solar/Wind Harmer
0.213
958261AF2-120 GEN
Solar/Wind Harmer
6.972
316181AB2-040 GEN
Solar/Wind Harmer
0.304
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.125
316426AA2-053 GEN
Solar/Wind Harmer
0.701
3145593CAROLNA
Solar/Wind Harmer
0.207
3145593CAROLNA
Solar/Wind Harmer
0.207
966811AG1-552 GEN
Solar/Wind Harmer
2.242
3145593CAROLNA
Solar/Wind Harmer
0.257
3145783HORNRTN
Solar/Wind Harmer
3.653
3145783HORNRTN
Solar/Wind Harmer
2.922
3145783HORNRTN
Solar/Wind Harmer
0.913
3145783HORNRTN
Solar/Wind Harmer
0.365
3145796HORNRTN
Solar/Wind Harmer
0.615
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.144
3150341NORNECKC1
Adder
2.127
971741AH1-377 GEN
Solar/Wind Harmer
19.978
3145933PARMELE
Solar/Wind Harmer
0.398
3145933PARMELE
Solar/Wind Harmer
0.199
316274AC1-208 GEN
Solar/Wind Harmer
1.032
970301AG2-198 GEN
Solar/Wind Harmer
8.48
316468AD1-105 GEN
Solar/Wind Harmer
-0.064
939181AE1-148 GEN
Solar/Wind Harmer
9.287
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.19
971775AH1-396 GEN
Solar/Wind Harmer
0.307
958211AF2-115 GEN
Solar/Wind Harmer
2.298
963191AG1-168 GEN
Solar/Wind Harmer
0.766
3144293JTRSVLE
Adder
0.609
3144293JTRSVLE
Adder
0.513
3147133PAMPLIN
Solar/Wind Harmer
0.191
3147133PAMPLIN
Solar/Wind Harmer
0.153
3145493TOT1
Solar/Wind Harmer
0.439
3145453TOT5
Solar/Wind Harmer
0.264
3145603CNETO
Solar/Wind Harmer
0.176
961601AG1-000A GEN
Solar/Wind Harmer
3.314
316263AC1-034 GEN
Solar/Wind Harmer
7.082
962561AG1-105 GEN
Solar/Wind Harmer
8.835
3146776BUCKING
Solar/Wind Harmer
0.73
3146776BUCKING
Solar/Wind Harmer
0.059
964791AG1-342 GEN
Solar/Wind Harmer
3.505
3146843MT LREL
Solar/Wind Harmer
0.182
3146843MT LREL
Solar/Wind Harmer
0.182
316011AB1-132 GEN
Solar/Wind Harmer
3.787
962571AG1-106 GEN
Solar/Wind Harmer
2.963
971795AH1-408 GEN
Solar/Wind Harmer
13.875
3145963POPLR C
Solar/Wind Harmer
0.207
3141726DUNNSVL
Solar/Wind Harmer
0.83
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.207
3147043LAWRENC
Adder
1.866
316174AB2-169 GEN
Solar/Wind Harmer
0.005
3145783HORNRTN
Solar/Wind Harmer
0.205
3145796HORNRTN
Solar/Wind Harmer
0.677
3145796HORNRTN
Solar/Wind Harmer
0.205
3150351NORNECKC2
Adder
2.041
316212AC1-099_GEN
Solar/Wind Harmer
1.035
3146293MARTNCO
Solar/Wind Harmer
0.185
316129AC1-054 GEN
Solar/Wind Harmer
0.746
971065AG2-659 GEN
Solar/Wind Harmer
8.425
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
315722AD1-056 GEN
Solar/Wind Harmer
1.233
316337AD2-073 GEN
Solar/Wind Harmer
0.169
970937AG2-583 GEN
Solar/Wind Harmer
11.922
315687AD1-152 GEN
Solar/Wind Harmer
0.006
316494AC1-189 GEN
Solar/Wind Harmer
0.649
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
14.314
963171AG1-166 GEN
Solar/Wind Harmer
1.021
971563AH1-280 GEN
Solar/Wind Harmer
2.042
3144293JTRSVLE
Adder
0.609
3146926FARMVIL
Solar/Wind Harmer
0.114
3146233WITAKRS
Solar/Wind Harmer
0.755
961671AG1-007 GEN
Solar/Wind Harmer
0.029
3146083TARBORO
Solar/Wind Harmer
0.189
3145493TOT1
Solar/Wind Harmer
0.843
3145543BTLEBRO
Solar/Wind Harmer
0.186
3145543BTLEBRO
Solar/Wind Harmer
0.149
316359AB2-059 GEN
Solar/Wind Harmer
0.669
316049AB1-081 GEN
Solar/Wind Harmer
1.066
3142053HEARTS
Solar/Wind Harmer
0.328
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.073
970401AG2-262 GEN
Solar/Wind Harmer
1.071
972003AH1-546 GEN
Solar/Wind Harmer
7.446
316254AC1-120 GEN1
Solar/Wind Harmer
0.366
316003AC1-222 GEN
Solar/Wind Harmer
0.004
3151751LOISA D
Adder
10.898
972135AH1-637 GEN
Solar/Wind Harmer
1.429
971377AH1-170 GEN
Solar/Wind Harmer
1.734
3147623JAMES R
Solar/Wind Harmer
0.377
972277AH1-723 GEN
Adder
88.606
966001AG1-469 GEN
Solar/Wind Harmer
0.098
3151731LOISA B
Adder
10.898
3151721LOISA A
Adder
10.842
971489AH1-241 GEN
Solar/Wind Harmer
8.67
316222AC1-221 GEN
Solar/Wind Harmer
0.658
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
7.283
315651AD1-115 GEN
Solar/Wind Harmer
0.004
971531AH1-263 GEN
50/50
60.398
316303AF2-085
50/50
4.712
971285AH1-108 GEN
50/50
1.991
970603AG2-384 GEN
50/50
5.178
316164AC1-076 GEN
Solar/Wind Harmer
0.448
316233AE1-074 FULL
Solar/Wind Harmer
0.206
971281AH1-106 GEN
Solar/Wind Harmer
3.576
971283AH1-107 GEN
Solar/Wind Harmer
3.576
3143316POE
Solar/Wind Harmer
0.962
941031AE2-094 GEN
Solar/Wind Harmer
44.489
944011AF1-069 GEN
Solar/Wind Harmer
14.536
316132AB2-190 GEN1
Solar/Wind Harmer
1.291
316369SG1_INVT
Solar/Wind Harmer
0.009
3151081ELIZAR1
Adder
22.001
3151091ELIZAR2
Adder
21.619
3152611GOSPORTB
Adder
3.055
3152621GOSPORTC
Adder
2.593
3152601GOSPORTA
Adder
2.392
971445AH1-216 GEN
Solar/Wind Harmer
16.874
972265AH1-717 GEN
Adder
18.594
3151201GRAVEL4
Adder
17.43
3151191GRAVEL3
Adder
17.21
3151211GRAVEL5
Adder
17.21
316312AB1-027
Solar/Wind Harmer
0.427
957871AF2-081 GEN
Solar/Wind Harmer
11.843
970673AG2-436 GEN
Solar/Wind Harmer
50.646
970673AG2-436 GEN
Solar/Wind Harmer
33.764
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.163
319010AE1-072 C
Solar/Wind Harmer
1.195
316311AC2-079 GEN
Solar/Wind Harmer
6.813
3146406KITTY HAWK
Solar/Wind Harmer
0.03
316305AF2-043 C
Solar/Wind Harmer
0.002
315976AC1-164 GENA
Solar/Wind Harmer
24.491
316169AC1-164_GENC
Solar/Wind Harmer
21.158
315975AC1-164 GENB
Solar/Wind Harmer
0.725
315835AF2-110_GEN
Solar/Wind Harmer
1.619
316315AB2-025 C
Solar/Wind Harmer
0.19
313526AB2-022
Solar/Wind Harmer
0.127
972189AH1-679 GEN
Adder
3.932
3146486SUNBURY
Solar/Wind Harmer
0.234
3146486SUNBURY
Solar/Wind Harmer
0.234
971967AH1-528 GEN
Solar/Wind Harmer
37.517
315814AE2-033 C
Solar/Wind Harmer
18.537
316321Z2-027
Solar/Wind Harmer
0.044
3146396TANGLEW
Solar/Wind Harmer
0.645
3145176PASQUOTANK
Solar/Wind Harmer
0.145
971167AH1-042 GEN
Solar/Wind Harmer
20.705
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
3138283WHITEMARSH
Solar/Wind Harmer
0.054
3143873LANEXA
Solar/Wind Harmer
0.138
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
316314AB2-024 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.735
316059AD1-063 C
Solar/Wind Harmer
0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.226
3130156CHOWAN
Solar/Wind Harmer
0.226
3141873WAN 176
Solar/Wind Harmer
0.045
970085AG2-068 GEN
Solar/Wind Harmer
11.907
970581AG2-369 GEN
Solar/Wind Harmer
10.24
3141913WHIT STONE
Solar/Wind Harmer
0.222
3138133OCRAN
Solar/Wind Harmer
0.066
315816AE2-034 GEN
Solar/Wind Harmer
0.951
3141783LANCAST
Solar/Wind Harmer
0.132
3141783LANCAST
Solar/Wind Harmer
0.088
3150411LDYSMT5
Adder
29.481
3150381LDYSMT2
Adder
28.214
972213AH1-691 GEN
Adder
4.773
972215AH1-692 GEN
Adder
4.773
3130546PLYMOUTH
Solar/Wind Harmer
0.218
315732AD1-074 GEN1
Solar/Wind Harmer
1.25
315733AD1-074 GEN2
Solar/Wind Harmer
1.25
315735AD1-075 GEN1
Solar/Wind Harmer
0.626
965291AG1-394 GEN
Solar/Wind Harmer
0.964
962981AG1-147 GEN
Solar/Wind Harmer
8.079
3146206CASHIE
Solar/Wind Harmer
0.215
970601AG2-382 GEN
Solar/Wind Harmer
8.044
3145893MURPHYS
Solar/Wind Harmer
0.581
3145893MURPHYS
Solar/Wind Harmer
0.215
970327AG2-215 GEN
Solar/Wind Harmer
7.032
3145513AHOSKIE
Solar/Wind Harmer
0.443
3145513AHOSKIE
Solar/Wind Harmer
0.212
3146043SEABORD
Solar/Wind Harmer
0.211
3145683EARLEYS
Solar/Wind Harmer
0.422
3145683EARLEYS
Solar/Wind Harmer
0.211
3145683EARLEYS
Solar/Wind Harmer
0.211
315607AA1-063A GEN
Solar/Wind Harmer
0.431
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
22.91
3137643SOCKMAN
Solar/Wind Harmer
0.831
3145796HORNRTN
Solar/Wind Harmer
0.656
3145796HORNRTN
Solar/Wind Harmer
0.082
3141813NORNECK
Solar/Wind Harmer
0.205
3146033SCOT NK
Solar/Wind Harmer
0.813
970831AG2-522 GEN
Solar/Wind Harmer
8.493
316005AA1-067
Solar/Wind Harmer
0.209
3145746EVERETS
Solar/Wind Harmer
0.776
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
970181AG2-120 GEN
Solar/Wind Harmer
2.429
957861AF2-080 GEN
Solar/Wind Harmer
8.286
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
3.225
3144303KENBRDG
Solar/Wind Harmer
0.153
970683AG2-441 GEN
Solar/Wind Harmer
12.781
970681AG2-440 GEN
Solar/Wind Harmer
10.225
946301AF1-294 GEN
Solar/Wind Harmer
3.778
961791AG1-021 GEN
Solar/Wind Harmer
1.838
315657AE1-056 GEN
Solar/Wind Harmer
6.598
316420AA1-050 GEN
Solar/Wind Harmer
0.006
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.189
3145573BETHELC
Solar/Wind Harmer
0.189
970285AG2-188 GEN
Solar/Wind Harmer
14.603
316223AC1-118
Solar/Wind Harmer
0.132
971845AH1-439 GEN
Solar/Wind Harmer
8.313
316118AC1-105 GEN
Solar/Wind Harmer
0.462
3147173SINAI
Solar/Wind Harmer
0.175
3147243WELCO
Solar/Wind Harmer
0.11
972205AH1-687 GEN
Adder
7.416
3147346CASHSCORNER
Solar/Wind Harmer
0.37
944491AF1-114 GEN
Solar/Wind Harmer
0.001
971447AH1-217 GEN
Solar/Wind Harmer
4.798
970865AG2-541 GEN
Solar/Wind Harmer
5.388
972193AH1-681 GEN
Adder
3.397
270494AE1-108_GEN
Solar/Wind Harmer
1.716
316123AC1-075 GEN
Solar/Wind Harmer
0.194
970165AG2-112 GEN
Solar/Wind Harmer
1.153
970163AG2-111 GEN
Solar/Wind Harmer
1.1
3138266HYDRAULIC
Solar/Wind Harmer
0.006
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316411AF1-147_GEN1
Solar/Wind Helper
0.82
316415AF1-147_GEN2
Solar/Wind Helper
0.82
3138216PACIFIC
Solar/Wind Helper
0.04
LAGNLTFEXP_LAGN->PJM
CLTF
8.202
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.192
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.068
MECLTFEXP_MEC->PJM
CLTF
3.555
SIGELTFEXP_SIGE->PJM
CLTF
0.108
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.311
TVALTFEXP_TVA->PJM
CLTF
4.157
NYPJM->LTFIMP_NY
CLTF
3.433
LGEELTFEXP_LGEE->PJM
CLTF
1.291
WECLTFEXP_WEC->PJM
CLTF
0.616
CPLELTFEXP_CPLE->PJM
CLTF
12.074
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.739

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:175.06 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5637.7
MW Contribution:8.48
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
19.717
3150861SPRUNCD
50/50
1.197
3143096IRON208
50/50
1.062
3143096IRON208
50/50
1.041
3150801HOPHCF4
50/50
1.399
971211AH1-065 GEN
50/50
1.687
3151161SURRY 1
50/50
9.055
316044AC1-158 PL1
Solar/Wind Harmer
3.023
316450AC1-158 RIC
Solar/Wind Harmer
0.806
3147666LOUISA
Solar/Wind Harmer
0.614
315839AE2-212 C
Solar/Wind Harmer
0.002
315773AC2-141 GEN
Solar/Wind Harmer
8.726
965281AG1-393 GEN
Solar/Wind Harmer
2.543
315813AE1-149 C
Solar/Wind Harmer
12.658
970133AG2-095 GEN
Solar/Wind Harmer
2.278
970129AG2-093 GEN
Solar/Wind Harmer
14.319
944581AF1-123 GEN
Solar/Wind Harmer
53.293
944601AF1-125 GEN
Solar/Wind Harmer
52.472
315778AD1-151 GEN
Solar/Wind Harmer
18.928
3151101ELIZAR3
Adder
21.938
971133AH1-012 GEN
50/50
5.548
944641AF1-129 GEN
50/50
120.841
970533AG2-339 GEN
50/50
21.15
3152251N ANNA1
50/50
19.719
970119AG2-088 GEN
50/50
34.806
3150851SPRUNCC
50/50
1.197
3143096IRON208
50/50
1.062
3152331SURRY 2
50/50
9.829
3150771HOPHCF1
50/50
0.962
316045AC1-158 PL2
Solar/Wind Harmer
9.665
3147666LOUISA
Solar/Wind Harmer
1.067
3143226MDLTHAN
Solar/Wind Harmer
0.261
316192AB2-158 GEN
Solar/Wind Harmer
1.475
3143526WINTERP
Solar/Wind Harmer
1.319
940641AE2-051 GEN
Solar/Wind Harmer
19.587
939411AE1-173 GEN
Solar/Wind Harmer
103.486
3142543TWELFTH
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
4.14
315671AE2-027_GEN
Solar/Wind Harmer
15.248
970129AG2-093 GEN
Solar/Wind Harmer
6.738
316458AB2-190 GEN2
Solar/Wind Harmer
1.271
944591AF1-124 GEN
Solar/Wind Harmer
53.482
971069AG2-661 GEN
Solar/Wind Harmer
4.206
944631AF1-128 GEN
Adder
112.66
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.949
971647AH1-324 GEN
Solar/Wind Harmer
10.078
970659AG2-427 GEN
Solar/Wind Harmer
11.419
3145336SMITFLD
Solar/Wind Harmer
0.943
961611AG1-000B GEN
Solar/Wind Harmer
12.376
970531AG2-338 GEN
50/50
8.46
3142366NRTHEST
50/50
0.824
3150781HOPHCF2
50/50
0.962
3150791HOPHCF3
50/50
0.962
3150761HOPPOLC
50/50
0.61
971213AH1-066 GEN
50/50
0.844
3150691DARBY 3
50/50
18.094
3150701DARBY 4
50/50
18.052
316447AC1-158 HLD
Solar/Wind Harmer
6.644
971223AH1-071 GEN
Solar/Wind Harmer
2.784
3143526WINTERP
Solar/Wind Harmer
1.319
316240AF1-291 C
Solar/Wind Harmer
0.002
3150681DARBY 2
Adder
16.992
3150671DARBY 1
Adder
16.973
3142296MT RD221
Adder
0.753
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.266
316036AC1-147 C
Solar/Wind Harmer
0.044
3150991CHESPKB
Adder
2.474
3150991CHESPKB
Adder
2.414
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.226
316185AD1-033 GEN
Solar/Wind Harmer
0.007
970657AG2-426 GEN
Solar/Wind Harmer
8.254
970657AG2-426 GEN
Solar/Wind Harmer
1.73
3145506HICKORY
Solar/Wind Harmer
0.94
3145506HICKORY
Solar/Wind Harmer
0.564
3145506HICKORY
Solar/Wind Harmer
0.141
3142946ENON
Solar/Wind Harmer
0.023
316339AD2-160 GEN
Solar/Wind Harmer
0.38
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.131
3137176SLIGO L2192
Solar/Wind Harmer
0.93
316075AC2-137 C
Solar/Wind Harmer
0.064
3146456SLIGO L269
Solar/Wind Harmer
4.136
3130086AYDLETT
Solar/Wind Harmer
0.933
972185AH1-677 GEN
Adder
13.007
3144356SAPONY
Solar/Wind Harmer
1.937
3146386ELIZ CT
Solar/Wind Harmer
0.231
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
972187AH1-678 GEN
Adder
6.523
3146516WINFALL
Solar/Wind Harmer
0.229
316303AF2-085
50/50
4.641
971285AH1-108 GEN
50/50
1.959
970603AG2-384 GEN
50/50
5.097
316233AE1-074 FULL
Solar/Wind Harmer
0.203
971281AH1-106 GEN
Solar/Wind Harmer
3.521
971283AH1-107 GEN
Solar/Wind Harmer
3.521
3143316POE
Solar/Wind Harmer
0.947
941031AE2-094 GEN
Solar/Wind Harmer
43.824
944011AF1-069 GEN
Solar/Wind Harmer
14.319
316132AB2-190 GEN1
Solar/Wind Harmer
1.271
316369SG1_INVT
Solar/Wind Harmer
0.009
3151081ELIZAR1
Adder
21.661
3151091ELIZAR2
Adder
21.285
3152611GOSPORTB
Adder
3.008
3144536CHRHLND
Solar/Wind Harmer
0.035
3144873MCLAUGH
Solar/Wind Harmer
0.006
970659AG2-427 GEN
Solar/Wind Harmer
2.498
3145336SMITFLD
Solar/Wind Harmer
0.094
961611AG1-000B GEN
Solar/Wind Harmer
6.293
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3151221GRAVEL6
Adder
17.139
3151171GRAVELC
Adder
3.297
970293AG2-193 GEN
Solar/Wind Harmer
2.512
970661AG2-428 GEN
Solar/Wind Harmer
4.977
3142946ENON
Solar/Wind Harmer
0.079
3142416OLDCHRC
Solar/Wind Harmer
2.274
3144216WINCHST
Adder
0.882
3146456SLIGO L269
Solar/Wind Harmer
0.234
971153AH1-033 GEN
Solar/Wind Harmer
2.702
3150921YORKTN3
Adder
5.872
316382AG1-145 C
Solar/Wind Harmer
0.002
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.445
3142433PROV 92
Adder
0.445
3146516WINFALL
Solar/Wind Harmer
0.229
316473AC1-191 GEN
Solar/Wind Harmer
0.768
3146626S HERTFORD
Solar/Wind Harmer
0.227
3145273HOLLAND
Solar/Wind Harmer
0.17
316313AB2-026
Solar/Wind Harmer
0.142
316258AE1-075 C
Solar/Wind Harmer
0.17
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.394
3141843SHACKLE
Adder
1.143
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
2.978
316280AD1-041 GEN
Solar/Wind Harmer
0.005
3146376EDENTON
Solar/Wind Harmer
0.223
316156AD2-030 GEN
Solar/Wind Harmer
0.165
3141873WAN 176
Solar/Wind Harmer
3.95
970917AG2-570 GEN
Solar/Wind Harmer
19.626
315614AA2-178 GEN
Solar/Wind Harmer
1.249
3150401LDYSMT4
Adder
28.893
3150371LDYSMT1
Adder
27.918
971157AH1-035 GEN
Solar/Wind Harmer
2.577
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
316365GEN2_N
Solar/Wind Harmer
0.481
315737AD1-076 GEN
Solar/Wind Harmer
2.755
962971AG1-146 GEN
Solar/Wind Harmer
3.408
3146206CASHIE
Solar/Wind Harmer
0.212
3145893MURPHYS
Solar/Wind Harmer
0.354
3145893MURPHYS
Solar/Wind Harmer
0.212
957521AF2-046 GEN
Solar/Wind Harmer
15.715
961681AG1-008 GEN
Solar/Wind Harmer
15.715
970009AG2-005 GEN
Solar/Wind Harmer
1.575
3146173TUNIS
Solar/Wind Harmer
0.21
3156021HOLLOMANSOL
Solar/Wind Harmer
0.95
316463AE2-346 GEN
Solar/Wind Harmer
0.179
316140AB2-099
Solar/Wind Harmer
0.075
962331AG1-082 GEN
Solar/Wind Harmer
2.227
316404AE1-155 C
Solar/Wind Harmer
0.047
3146263WOODLND
Solar/Wind Harmer
0.207
313506AB2-031 GEN
Solar/Wind Harmer
0.638
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3145963POPLR C
Solar/Wind Harmer
0.204
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.204
316478AD1-087 GEN
Solar/Wind Harmer
0.708
316486AD2-202 GEN
Solar/Wind Harmer
0.208
3147043LAWRENC
Solar/Wind Harmer
0.122
3145796HORNRTN
Solar/Wind Harmer
0.807
3145796HORNRTN
Solar/Wind Harmer
0.202
3150351NORNECKC2
Adder
2.043
316210AC1-098 GEN
Solar/Wind Harmer
1.828
3145933PARMELE
Solar/Wind Harmer
0.196
966801AG1-551 GEN
Solar/Wind Harmer
2.283
970909AG2-566 GEN
Solar/Wind Harmer
2.083
971781AH1-399 GEN
Solar/Wind Harmer
0.256
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
315724AD1-057 GEN
Solar/Wind Harmer
0.72
316327AA2-057 GEN
Solar/Wind Harmer
0.287
316131AB2-060 GEN
Solar/Wind Harmer
0.595
964241AG1-285 GEN
Solar/Wind Harmer
12.61
315785AD2-033 C
Solar/Wind Harmer
1.535
970257AG2-171 GEN
Solar/Wind Harmer
6.039
959311AF2-222 GEN
Solar/Wind Harmer
16.767
963181AG1-167 GEN
Solar/Wind Harmer
0.752
3144293JTRSVLE
Adder
0.599
3147133PAMPLIN
Solar/Wind Harmer
0.59
971193AH1-056 GEN
Solar/Wind Harmer
11.443
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146233WITAKRS
Solar/Wind Harmer
0.938
3146233WITAKRS
Solar/Wind Harmer
0.127
3146926FARMVIL
Solar/Wind Harmer
0.112
3146073TAR RVR
Solar/Wind Harmer
0.186
3146083TARBORO
Solar/Wind Harmer
0.186
3138543CONSLDL
Solar/Wind Harmer
0.123
961601AG1-000A GEN
Solar/Wind Harmer
13.049
3145543BTLEBRO
Solar/Wind Harmer
0.183
3145543BTLEBRO
Solar/Wind Harmer
0.183
971623AH1-311 GEN
Solar/Wind Harmer
0.367
3141906WESTMOR
Solar/Wind Harmer
0.072
3146776BUCKING
Solar/Wind Harmer
0.064
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.36
970737AG2-469 GEN
Solar/Wind Harmer
7.314
971683AH1-343 GEN
Solar/Wind Harmer
5.86
3151761LOISA E
Adder
21.054
970221AG2-151 GEN
Solar/Wind Harmer
8.48
3132273ORANGE
Solar/Wind Harmer
0.031
316283AC2-100 C
Solar/Wind Harmer
0.304
972183AH1-676 GEN
Adder
164.313
972255AH1-712 GEN
Adder
74.545
316170AC1-121 GEN2
Solar/Wind Harmer
0.13
3141316ARNOLDS
Adder
0.285
3141196NOKESVL
Solar/Wind Helper
1.139
3152621GOSPORTC
Adder
2.552
3152601GOSPORTA
Adder
2.355
971445AH1-216 GEN
Solar/Wind Harmer
16.611
972265AH1-717 GEN
Adder
18.304
3151201GRAVEL4
Adder
17.158
3151191GRAVEL3
Adder
16.941
3151211GRAVEL5
Adder
16.941
316312AB1-027
Solar/Wind Harmer
0.42
957871AF2-081 GEN
Solar/Wind Harmer
11.66
316164AC1-076 GEN
Solar/Wind Harmer
0.329
970673AG2-436 GEN
Solar/Wind Harmer
49.886
970673AG2-436 GEN
Solar/Wind Harmer
33.257
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.16
319010AE1-072 C
Solar/Wind Harmer
1.177
316311AC2-079 GEN
Solar/Wind Harmer
6.708
3146406KITTY HAWK
Solar/Wind Harmer
0.029
316305AF2-043 C
Solar/Wind Harmer
0.002
315976AC1-164 GENA
Solar/Wind Harmer
24.098
316169AC1-164_GENC
Solar/Wind Harmer
20.818
315975AC1-164 GENB
Solar/Wind Harmer
0.713
315835AF2-110_GEN
Solar/Wind Harmer
1.594
316315AB2-025 C
Solar/Wind Harmer
0.187
313526AB2-022
Solar/Wind Harmer
0.125
971967AH1-528 GEN
Solar/Wind Harmer
36.95
3146486SUNBURY
Solar/Wind Harmer
0.231
3146486SUNBURY
Solar/Wind Harmer
0.231
972189AH1-679 GEN
Adder
3.867
315814AE2-033 C
Solar/Wind Harmer
18.254
316321Z2-027
Solar/Wind Harmer
0.043
3146396TANGLEW
Solar/Wind Harmer
0.635
3145176PASQUOTANK
Solar/Wind Harmer
0.143
971167AH1-042 GEN
Solar/Wind Harmer
20.377
3142433PROV 92
Adder
0.445
3142433PROV 92
Adder
0.445
3138283WHITEMARSH
Solar/Wind Harmer
0.053
3143873LANEXA
Solar/Wind Harmer
0.135
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
316314AB2-024 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.628
316059AD1-063 C
Solar/Wind Harmer
0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.223
3130156CHOWAN
Solar/Wind Harmer
0.223
3141873WAN 176
Solar/Wind Harmer
0.044
970085AG2-068 GEN
Solar/Wind Harmer
11.727
970581AG2-369 GEN
Solar/Wind Harmer
10.085
3141913WHIT STONE
Solar/Wind Harmer
0.219
3138133OCRAN
Solar/Wind Harmer
0.065
315816AE2-034 GEN
Solar/Wind Harmer
0.937
3141783LANCAST
Solar/Wind Harmer
0.13
3141783LANCAST
Solar/Wind Harmer
0.087
3150411LDYSMT5
Adder
28.983
3150381LDYSMT2
Adder
27.738
972213AH1-691 GEN
Adder
4.692
972215AH1-692 GEN
Adder
4.692
3130546PLYMOUTH
Solar/Wind Harmer
0.215
315732AD1-074 GEN1
Solar/Wind Harmer
1.23
315733AD1-074 GEN2
Solar/Wind Harmer
1.23
315735AD1-075 GEN1
Solar/Wind Harmer
0.616
965291AG1-394 GEN
Solar/Wind Harmer
0.949
962981AG1-147 GEN
Solar/Wind Harmer
7.952
3146206CASHIE
Solar/Wind Harmer
0.212
970601AG2-382 GEN
Solar/Wind Harmer
7.919
3145893MURPHYS
Solar/Wind Harmer
0.572
3145893MURPHYS
Solar/Wind Harmer
0.212
970327AG2-215 GEN
Solar/Wind Harmer
6.922
3145513AHOSKIE
Solar/Wind Harmer
0.437
3145513AHOSKIE
Solar/Wind Harmer
0.209
3146043SEABORD
Solar/Wind Harmer
0.208
3145683EARLEYS
Solar/Wind Harmer
0.416
3145683EARLEYS
Solar/Wind Harmer
0.208
3145683EARLEYS
Solar/Wind Harmer
0.208
315607AA1-063A GEN
Solar/Wind Harmer
0.424
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
22.553
3137643SOCKMAN
Solar/Wind Harmer
0.818
3145796HORNRTN
Solar/Wind Harmer
0.646
3145796HORNRTN
Solar/Wind Harmer
0.081
3141813NORNECK
Solar/Wind Harmer
0.201
3146033SCOT NK
Solar/Wind Harmer
0.8
970831AG2-522 GEN
Solar/Wind Harmer
8.358
316005AA1-067
Solar/Wind Harmer
0.206
3145746EVERETS
Solar/Wind Harmer
0.764
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
970181AG2-120 GEN
Solar/Wind Harmer
2.391
957861AF2-080 GEN
Solar/Wind Harmer
8.156
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
3.171
3144303KENBRDG
Solar/Wind Harmer
0.151
970683AG2-441 GEN
Solar/Wind Harmer
12.561
970681AG2-440 GEN
Solar/Wind Harmer
10.049
946301AF1-294 GEN
Solar/Wind Harmer
3.712
961791AG1-021 GEN
Solar/Wind Harmer
1.806
315657AE1-056 GEN
Solar/Wind Harmer
6.482
316420AA1-050 GEN
Solar/Wind Harmer
0.006
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.186
3145573BETHELC
Solar/Wind Harmer
0.186
970285AG2-188 GEN
Solar/Wind Harmer
14.319
316223AC1-118
Solar/Wind Harmer
0.13
971845AH1-439 GEN
Solar/Wind Harmer
8.149
316118AC1-105 GEN
Solar/Wind Harmer
0.454
3147173SINAI
Solar/Wind Harmer
0.172
3147243WELCO
Solar/Wind Harmer
0.108
972205AH1-687 GEN
Adder
7.256
944491AF1-114 GEN
Solar/Wind Harmer
0.001
971447AH1-217 GEN
Solar/Wind Harmer
4.692
970865AG2-541 GEN
Solar/Wind Harmer
5.299
3147346CASHSCORNER
Solar/Wind Harmer
0.35
972193AH1-681 GEN
Adder
3.331
316123AC1-075 GEN
Solar/Wind Harmer
0.191
970165AG2-112 GEN
Solar/Wind Harmer
1.134
970163AG2-111 GEN
Solar/Wind Harmer
1.081
270494AE1-108_GEN
Solar/Wind Harmer
1.679
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316411AF1-147_GEN1
Solar/Wind Helper
0.804
316415AF1-147_GEN2
Solar/Wind Helper
0.804
3138216PACIFIC
Solar/Wind Helper
0.039
316381AD1-082 GEN
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
2.508
970661AG2-428 GEN
Solar/Wind Harmer
23.401
3142416OLDCHRC
Solar/Wind Harmer
0.61
3142416OLDCHRC
Solar/Wind Harmer
0.234
316388AE2-253 GEN
Solar/Wind Harmer
0.734
3138126ROCKLANDING
Solar/Wind Harmer
0.107
3146456SLIGO L269
Solar/Wind Harmer
0.234
316072AD1-144
Solar/Wind Harmer
0.085
316159AE1-175 C
Solar/Wind Harmer
0.201
316246AF1-032 C
Solar/Wind Harmer
0.105
971317AH1-138 GEN
Solar/Wind Harmer
1.735
316093AE2-104_GEN
Solar/Wind Harmer
3.906
3142433PROV 92
Solar/Wind Harmer
0.914
3142433PROV 92
Adder
0.445
3142433PROV 92
Adder
0.445
3146516WINFALL
Solar/Wind Harmer
0.741
3146516WINFALL
Solar/Wind Harmer
0.229
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.993
971777AH1-397 GEN
Solar/Wind Harmer
0.591
3141843SHACKLE
Adder
1.143
3141766HARMONY
Solar/Wind Harmer
0.045
3130156CHOWAN
Solar/Wind Harmer
0.223
966881AG1-559 GEN
Solar/Wind Harmer
0.257
970919AG2-571 GEN
Solar/Wind Harmer
7.85
970087AG2-069 GEN
Solar/Wind Harmer
17.59
3138133OCRAN
Solar/Wind Harmer
0.131
3145663CRESWEL
Solar/Wind Harmer
0.611
971163AH1-040 GEN
Solar/Wind Harmer
17.461
972197AH1-683 GEN
Adder
4.512
972219AH1-694 GEN
Adder
3.248
316336AC2-165 C
Solar/Wind Harmer
0.008
316023GEN1_S
Solar/Wind Harmer
0.481
3146206CASHIE
Solar/Wind Harmer
0.212
971547AH1-271 GEN
Solar/Wind Harmer
4.525
3145893MURPHYS
Solar/Wind Harmer
0.847
3145893MURPHYS
Solar/Wind Harmer
0.941
957481AF2-042 GEN
Solar/Wind Harmer
56.258
3146173TUNIS
Solar/Wind Harmer
0.21
960081AF2-299 GEN
Solar/Wind Harmer
2.005
962861AG1-135 GEN
Solar/Wind Harmer
6.67
3145683EARLEYS
Solar/Wind Harmer
0.208
315693AD1-088 GEN
Solar/Wind Harmer
9.93
3146516WINFALL
Solar/Wind Harmer
0.229
3146516WINFALL
Solar/Wind Harmer
0.229
966871AG1-558 GEN
Solar/Wind Harmer
0.263
3146626S HERTFORD
Solar/Wind Harmer
0.227
3146626S HERTFORD
Solar/Wind Harmer
0.227
970933AG2-581 GEN
Solar/Wind Harmer
18.033
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
0.99
3146376EDENTON
Solar/Wind Harmer
0.99
957411AF2-035 GEN
Solar/Wind Harmer
9.498
970317AG2-208 GEN
Solar/Wind Harmer
8.8
315673AE1-157 GEN
Solar/Wind Harmer
15.213
3150391LDYSMT3
Adder
28.839
972195AH1-682 GEN
Adder
3.79
316065AD1-022 GEN
Solar/Wind Harmer
9.8
3145893MURPHYS
Solar/Wind Harmer
1.417
3145893MURPHYS
Solar/Wind Harmer
0.381
970099AG2-077 GEN
Solar/Wind Harmer
22.503
3146173TUNIS
Solar/Wind Harmer
0.21
3146173TUNIS
Solar/Wind Harmer
0.21
958261AF2-120 GEN
Solar/Wind Harmer
6.863
316181AB2-040 GEN
Solar/Wind Harmer
0.299
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3142666NORTHAMPTON
Solar/Wind Harmer
0.123
316426AA2-053 GEN
Solar/Wind Harmer
0.69
3145593CAROLNA
Solar/Wind Harmer
0.203
3145593CAROLNA
Solar/Wind Harmer
0.203
966811AG1-552 GEN
Solar/Wind Harmer
2.207
3145593CAROLNA
Solar/Wind Harmer
0.253
3145783HORNRTN
Solar/Wind Harmer
3.596
3145783HORNRTN
Solar/Wind Harmer
2.876
3145783HORNRTN
Solar/Wind Harmer
0.899
3145783HORNRTN
Solar/Wind Harmer
0.36
3145796HORNRTN
Solar/Wind Harmer
0.606
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.11
3150341NORNECKC1
Adder
2.093
971741AH1-377 GEN
Solar/Wind Harmer
19.637
3145933PARMELE
Solar/Wind Harmer
0.392
3145933PARMELE
Solar/Wind Harmer
0.196
316274AC1-208 GEN
Solar/Wind Harmer
1.016
970301AG2-198 GEN
Solar/Wind Harmer
8.333
316468AD1-105 GEN
Solar/Wind Harmer
-0.063
939181AE1-148 GEN
Solar/Wind Harmer
9.137
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.051
971775AH1-396 GEN
Solar/Wind Harmer
0.302
958211AF2-115 GEN
Solar/Wind Harmer
2.257
963191AG1-168 GEN
Solar/Wind Harmer
0.752
3144293JTRSVLE
Adder
0.599
3144293JTRSVLE
Adder
0.504
3147133PAMPLIN
Solar/Wind Harmer
0.188
3147133PAMPLIN
Solar/Wind Harmer
0.15
3145493TOT1
Solar/Wind Harmer
0.432
3145453TOT5
Solar/Wind Harmer
0.259
3145603CNETO
Solar/Wind Harmer
0.173
961601AG1-000A GEN
Solar/Wind Harmer
3.262
316263AC1-034 GEN
Solar/Wind Harmer
6.97
962561AG1-105 GEN
Solar/Wind Harmer
8.691
964791AG1-342 GEN
Solar/Wind Harmer
3.448
3146843MT LREL
Solar/Wind Harmer
0.179
3146843MT LREL
Solar/Wind Harmer
0.179
3146776BUCKING
Solar/Wind Harmer
0.716
3146776BUCKING
Solar/Wind Harmer
0.058
3151731LOISA B
Adder
10.327
3151721LOISA A
Adder
10.274
971489AH1-241 GEN
Solar/Wind Harmer
8.48
316222AC1-221 GEN
Solar/Wind Harmer
0.648
966001AG1-469 GEN
Solar/Wind Harmer
0.09
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
7.158
3146263WOODLND
Solar/Wind Harmer
0.207
962491AG1-098 GEN
Solar/Wind Harmer
11.772
316011AB1-132 GEN
Solar/Wind Harmer
3.728
962571AG1-106 GEN
Solar/Wind Harmer
2.917
971795AH1-408 GEN
Solar/Wind Harmer
13.656
3145963POPLR C
Solar/Wind Harmer
0.204
3141726DUNNSVL
Solar/Wind Harmer
0.817
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.204
3147043LAWRENC
Adder
1.836
316174AB2-169 GEN
Solar/Wind Harmer
0.005
3145783HORNRTN
Solar/Wind Harmer
0.202
3145796HORNRTN
Solar/Wind Harmer
0.666
3145796HORNRTN
Solar/Wind Harmer
0.202
3150351NORNECKC2
Adder
2.009
316212AC1-099_GEN
Solar/Wind Harmer
1.019
3146293MARTNCO
Solar/Wind Harmer
0.182
316129AC1-054 GEN
Solar/Wind Harmer
0.734
971065AG2-659 GEN
Solar/Wind Harmer
8.291
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
315722AD1-056 GEN
Solar/Wind Harmer
1.214
316337AD2-073 GEN
Solar/Wind Harmer
0.167
315687AD1-152 GEN
Solar/Wind Harmer
0.006
970937AG2-583 GEN
Solar/Wind Harmer
11.689
316494AC1-189 GEN
Solar/Wind Harmer
0.639
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
14.068
963171AG1-166 GEN
Solar/Wind Harmer
1.003
971563AH1-280 GEN
Solar/Wind Harmer
2.007
3144293JTRSVLE
Adder
0.599
3146233WITAKRS
Solar/Wind Harmer
0.743
3146926FARMVIL
Solar/Wind Harmer
0.112
961671AG1-007 GEN
Solar/Wind Harmer
0.029
3146083TARBORO
Solar/Wind Harmer
0.186
3145493TOT1
Solar/Wind Harmer
0.829
3145543BTLEBRO
Solar/Wind Harmer
0.183
3145543BTLEBRO
Solar/Wind Harmer
0.147
316359AB2-059 GEN
Solar/Wind Harmer
0.659
316049AB1-081 GEN
Solar/Wind Harmer
1.05
3142053HEARTS
Solar/Wind Harmer
0.323
970401AG2-262 GEN
Solar/Wind Harmer
1.053
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.072
972003AH1-546 GEN
Solar/Wind Harmer
7.289
316003AC1-222 GEN
Solar/Wind Harmer
0.004
972135AH1-637 GEN
Solar/Wind Harmer
1.408
3151751LOISA D
Adder
10.327
971377AH1-170 GEN
Solar/Wind Harmer
1.696
3147623JAMES R
Solar/Wind Harmer
0.368
972277AH1-723 GEN
Adder
86.868
316254AC1-120 GEN1
Solar/Wind Harmer
0.26
LAGNLTFEXP_LAGN->PJM
CLTF
8.056
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.76
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.813
MECLTFEXP_MEC->PJM
CLTF
3.485
SIGELTFEXP_SIGE->PJM
CLTF
0.106
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.878
TVALTFEXP_TVA->PJM
CLTF
4.082
NYPJM->LTFIMP_NY
CLTF
3.369
LGEELTFEXP_LGEE->PJM
CLTF
1.264
WECLTFEXP_WEC->PJM
CLTF
0.603
CPLELTFEXP_CPLE->PJM
CLTF
11.88
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.966

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:129.41 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:4167.61
MW Contribution:6.52
Bus #Bus NameTypeMW Contribution
971133AH1-012 GEN
50/50
4.837
970533AG2-339 GEN
50/50
16.271
970531AG2-338 GEN
50/50
6.508
315242AE2-183_GT2
50/50
2.943
315241AE2-183_GT1
50/50
2.925
972185AH1-677 GEN
50/50
10.611
3151041BRUNSWICKG3
50/50
2.318
972187AH1-678 GEN
50/50
5.32
316447AC1-158 HLD
Solar/Wind Harmer
6.529
971223AH1-071 GEN
Solar/Wind Harmer
2.14
3143526WINTERP
Solar/Wind Harmer
0.994
316036AC1-147 C
Solar/Wind Harmer
0.033
3150991CHESPKB
Adder
1.839
3150991CHESPKB
Adder
1.795
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.168
316185AD1-033 GEN
Solar/Wind Harmer
0.005
316240AF1-291 C
Solar/Wind Harmer
0.001
3145506HICKORY
Solar/Wind Harmer
0.7
3145506HICKORY
Solar/Wind Harmer
0.42
3145506HICKORY
Solar/Wind Harmer
0.105
970657AG2-426 GEN
Solar/Wind Harmer
6.132
970657AG2-426 GEN
Solar/Wind Harmer
1.286
3144356SAPONY
Solar/Wind Harmer
1.464
944641AF1-129 GEN
Adder
83.418
316339AD2-160 GEN
Solar/Wind Harmer
0.283
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316018AA1-139 ULT2
Solar/Wind Harmer
0.004
316017AA1-139 ULT1
Solar/Wind Harmer
0.097
3137176SLIGO L2192
Solar/Wind Harmer
0.693
3146456SLIGO L269
Solar/Wind Harmer
3.08
3130086AYDLETT
Solar/Wind Harmer
0.695
316033AB2-134 GEN
Solar/Wind Harmer
0.01
315697AD1-025 GEN
Solar/Wind Harmer
0.195
970933AG2-581 GEN
Solar/Wind Harmer
13.857
3146386ELIZ CT
Solar/Wind Harmer
0.172
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.17
3146516WINFALL
Solar/Wind Harmer
0.17
3146516WINFALL
Solar/Wind Harmer
0.17
3142366NRTHEST
Adder
0.556
3146626S HERTFORD
Solar/Wind Harmer
0.169
3146626S HERTFORD
Solar/Wind Harmer
0.169
3150691DARBY 3
Adder
12.185
3150701DARBY 4
Adder
12.157
3150681DARBY 2
Adder
12.142
3150671DARBY 1
Adder
12.128
3142946ENON
Solar/Wind Harmer
0.017
315742AE1-103 GEN
Solar/Wind Harmer
0.002
316075AC2-137 C
Solar/Wind Harmer
0.046
3146376EDENTON
Solar/Wind Harmer
0.74
3146376EDENTON
Solar/Wind Harmer
0.74
3142296MT RD221
Adder
0.528
970099AG2-077 GEN
Solar/Wind Harmer
17.266
316065AD1-022 GEN
Solar/Wind Harmer
7.34
966871AG1-558 GEN
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
1.063
3145893MURPHYS
Solar/Wind Harmer
0.286
3146173TUNIS
Solar/Wind Harmer
0.157
3146173TUNIS
Solar/Wind Harmer
0.157
316181AB2-040 GEN
Solar/Wind Harmer
0.226
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
3142666NORTHAMPTON
Solar/Wind Harmer
0.093
316426AA2-053 GEN
Solar/Wind Harmer
0.52
3145593CAROLNA
Solar/Wind Harmer
0.153
3145593CAROLNA
Solar/Wind Harmer
0.153
966811AG1-552 GEN
Solar/Wind Harmer
1.665
3145593CAROLNA
Solar/Wind Harmer
0.191
3145783HORNRTN
Solar/Wind Harmer
2.713
3145783HORNRTN
Solar/Wind Harmer
2.17
3145783HORNRTN
Solar/Wind Harmer
0.678
3145783HORNRTN
Solar/Wind Harmer
0.271
3145796HORNRTN
Solar/Wind Harmer
0.457
971741AH1-377 GEN
Solar/Wind Harmer
15.076
970301AG2-198 GEN
Solar/Wind Harmer
6.399
958261AF2-120 GEN
Solar/Wind Harmer
4.886
316274AC1-208 GEN
Solar/Wind Harmer
0.766
3145933PARMELE
Solar/Wind Harmer
0.295
3145933PARMELE
Solar/Wind Harmer
0.147
957411AF2-035 GEN
Solar/Wind Harmer
6.2
970317AG2-208 GEN
Solar/Wind Harmer
5.744
939181AE1-148 GEN
Solar/Wind Harmer
6.96
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.011
316303AF2-085
50/50
3.567
971285AH1-108 GEN
50/50
1.443
315244AE2-183_ST
50/50
5.089
963041AG1-153 GEN
50/50
4.694
3151081ELIZAR1
50/50
17.092
3151091ELIZAR2
50/50
16.795
316164AC1-076 GEN
Solar/Wind Harmer
0.366
316233AE1-074 FULL
Solar/Wind Harmer
0.153
971281AH1-106 GEN
Solar/Wind Harmer
2.654
971283AH1-107 GEN
Solar/Wind Harmer
2.654
941031AE2-094 GEN
Solar/Wind Harmer
33.713
944011AF1-069 GEN
Solar/Wind Harmer
11.015
970673AG2-436 GEN
Solar/Wind Harmer
38.362
970673AG2-436 GEN
Solar/Wind Harmer
25.574
3143316POE
Solar/Wind Harmer
0.707
971967AH1-528 GEN
Solar/Wind Harmer
28.408
3152611GOSPORTB
Adder
2.236
3152621GOSPORTC
Adder
1.898
3152601GOSPORTA
Adder
1.751
316315AB2-025 C
Solar/Wind Harmer
0.141
957871AF2-081 GEN
Solar/Wind Harmer
8.68
315814AE2-033 C
Solar/Wind Harmer
13.794
971445AH1-216 GEN
Solar/Wind Harmer
12.275
319010AE1-072 C
Solar/Wind Harmer
0.876
3146406KITTY HAWK
Solar/Wind Harmer
0.022
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.119
316311AC2-079 GEN
Solar/Wind Harmer
4.99
316305AF2-043 C
Solar/Wind Harmer
0.001
972265AH1-717 GEN
Adder
13.481
3151201GRAVEL4
Adder
12.638
3151191GRAVEL3
Adder
12.478
3151211GRAVEL5
Adder
12.478
316369SG1_INVT
Solar/Wind Harmer
0.006
316132AB2-190 GEN1
Solar/Wind Harmer
0.93
315835AF2-110_GEN
Solar/Wind Harmer
1.187
313526AB2-022
Solar/Wind Harmer
0.093
3146486SUNBURY
Solar/Wind Harmer
0.172
3146486SUNBURY
Solar/Wind Harmer
0.172
316321Z2-027
Solar/Wind Harmer
0.032
3146396TANGLEW
Solar/Wind Harmer
0.473
3145176PASQUOTANK
Solar/Wind Harmer
0.106
970085AG2-068 GEN
Solar/Wind Harmer
9.004
970581AG2-369 GEN
Solar/Wind Harmer
7.744
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.166
3130156CHOWAN
Solar/Wind Harmer
0.166
315976AC1-164 GENA
Solar/Wind Harmer
17.177
316169AC1-164_GENC
Solar/Wind Harmer
14.839
315975AC1-164 GENB
Solar/Wind Harmer
0.508
316312AB1-027
Solar/Wind Harmer
0.296
3138283WHITEMARSH
Solar/Wind Harmer
0.038
971167AH1-042 GEN
Solar/Wind Harmer
14.667
3142433PROV 92
Adder
0.32
3142433PROV 92
Adder
0.32
315816AE2-034 GEN
Solar/Wind Harmer
0.7
3143873LANEXA
Solar/Wind Harmer
0.097
3130546PLYMOUTH
Solar/Wind Harmer
0.161
970189AG2-124 GEN
Solar/Wind Harmer
4.756
316314AB2-024 C
Solar/Wind Harmer
0.001
965291AG1-394 GEN
Solar/Wind Harmer
0.712
315732AD1-074 GEN1
Solar/Wind Harmer
0.921
315733AD1-074 GEN2
Solar/Wind Harmer
0.921
315735AD1-075 GEN1
Solar/Wind Harmer
0.461
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.032
3145893MURPHYS
Solar/Wind Harmer
0.429
3145893MURPHYS
Solar/Wind Harmer
0.159
3146206CASHIE
Solar/Wind Harmer
0.159
970601AG2-382 GEN
Solar/Wind Harmer
5.933
972189AH1-679 GEN
Adder
2.633
3141913WHIT STONE
Solar/Wind Harmer
0.157
3145513AHOSKIE
Solar/Wind Harmer
0.328
3145513AHOSKIE
Solar/Wind Harmer
0.157
3146043SEABORD
Solar/Wind Harmer
0.156
316087AB2-174 GEN
Solar/Wind Harmer
0.004
3138133OCRAN
Solar/Wind Harmer
0.047
315607AA1-063A GEN
Solar/Wind Harmer
0.319
3145683EARLEYS
Solar/Wind Harmer
0.312
3145683EARLEYS
Solar/Wind Harmer
0.156
3145683EARLEYS
Solar/Wind Harmer
0.156
3141783LANCAST
Solar/Wind Harmer
0.093
3141783LANCAST
Solar/Wind Harmer
0.062
315652AC1-086 GEN
Solar/Wind Harmer
17.007
3137643SOCKMAN
Solar/Wind Harmer
0.617
3145796HORNRTN
Solar/Wind Harmer
0.487
3145796HORNRTN
Solar/Wind Harmer
0.061
962981AG1-147 GEN
Solar/Wind Harmer
5.679
3146033SCOT NK
Solar/Wind Harmer
0.602
970327AG2-215 GEN
Solar/Wind Harmer
4.937
970831AG2-522 GEN
Solar/Wind Harmer
6.34
316005AA1-067
Solar/Wind Harmer
0.155
3145746EVERETS
Solar/Wind Harmer
0.575
3145746EVERETS
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
0.144
970181AG2-120 GEN
Solar/Wind Harmer
1.799
971443AH1-215 GEN
Solar/Wind Harmer
2.423
3144303KENBRDG
Solar/Wind Harmer
0.115
970683AG2-441 GEN
Solar/Wind Harmer
9.607
970681AG2-440 GEN
Solar/Wind Harmer
7.685
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
946301AF1-294 GEN
Solar/Wind Harmer
2.841
961791AG1-021 GEN
Solar/Wind Harmer
1.382
315657AE1-056 GEN
Solar/Wind Harmer
4.964
3141813NORNECK
Solar/Wind Harmer
0.143
957861AF2-080 GEN
Solar/Wind Harmer
6.144
316420AA1-050 GEN
Solar/Wind Harmer
0.005
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.141
3145573BETHELC
Solar/Wind Harmer
0.141
970285AG2-188 GEN
Solar/Wind Harmer
11.015
971845AH1-439 GEN
Solar/Wind Harmer
6.271
3150411LDYSMT5
Adder
18.158
3150381LDYSMT2
Adder
17.377
972213AH1-691 GEN
Adder
2.94
972215AH1-692 GEN
Adder
2.94
3147346CASHSCORNER
Solar/Wind Harmer
0.311
316118AC1-105 GEN
Solar/Wind Harmer
0.346
3147173SINAI
Solar/Wind Harmer
0.131
3147243WELCO
Solar/Wind Harmer
0.082
972205AH1-687 GEN
Adder
5.595
316223AC1-118
Solar/Wind Harmer
0.091
971447AH1-217 GEN
Solar/Wind Harmer
3.599
970865AG2-541 GEN
Solar/Wind Harmer
4.024
3152251N ANNA1
50/50
17.069
971507AH1-251 GEN
50/50
10.56
970119AG2-088 GEN
50/50
26.753
3150851SPRUNCC
50/50
0.882
315243AE2-183_GT3
50/50
2.943
3151051BRUNSWICKS1
50/50
4.812
3151021BRUNSWICKG1
50/50
2.318
971451AH1-221 GEN
50/50
7.041
316045AC1-158 PL2
Solar/Wind Harmer
9.498
3147666LOUISA
Solar/Wind Harmer
0.935
316192AB2-158 GEN
Solar/Wind Harmer
1.293
3143226MDLTHAN
Solar/Wind Harmer
0.2
3143526WINTERP
Solar/Wind Harmer
0.994
940641AE2-051 GEN
Solar/Wind Harmer
14.986
939411AE1-173 GEN
Solar/Wind Harmer
78.651
316294AC1-161 GEN
Solar/Wind Harmer
3.077
944591AF1-124 GEN
Solar/Wind Harmer
39.816
316375AC2-012 GEN
Solar/Wind Harmer
0.004
3150981CHESPKA
Adder
2.192
970659AG2-427 GEN
Solar/Wind Harmer
8.481
316381AD1-082 GEN
Solar/Wind Harmer
0.183
315671AE2-027_GEN
Solar/Wind Harmer
11.214
3142543TWELFTH
Solar/Wind Harmer
0.017
970661AG2-428 GEN
Solar/Wind Harmer
17.39
316388AE2-253 GEN
Solar/Wind Harmer
0.547
3145336SMITFLD
Solar/Wind Harmer
0.697
3146456SLIGO L269
Solar/Wind Harmer
0.174
316246AF1-032 C
Solar/Wind Harmer
0.078
3151171GRAVELC
Adder
1.847
961611AG1-000B GEN
Solar/Wind Harmer
9.102
971647AH1-324 GEN
Solar/Wind Harmer
7.403
316072AD1-144
Solar/Wind Harmer
0.063
971069AG2-661 GEN
Solar/Wind Harmer
3.083
316458AB2-190 GEN2
Solar/Wind Harmer
0.93
970129AG2-093 GEN
Solar/Wind Harmer
4.931
3143096IRON208
Adder
0.724
316093AE2-104_GEN
Solar/Wind Harmer
2.908
3143336POWHATN
Solar/Wind Harmer
3.072
3138126ROCKLANDING
Solar/Wind Harmer
0.078
944631AF1-128 GEN
Adder
81.389
3146516WINFALL
Solar/Wind Harmer
0.552
3146516WINFALL
Solar/Wind Harmer
0.17
970919AG2-571 GEN
Solar/Wind Harmer
6.028
316159AE1-175 C
Solar/Wind Harmer
0.146
971317AH1-138 GEN
Solar/Wind Harmer
1.261
970087AG2-069 GEN
Solar/Wind Harmer
13.506
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.166
316336AC2-165 C
Solar/Wind Harmer
0.006
3142416OLDCHRC
Solar/Wind Harmer
0.43
3142416OLDCHRC
Solar/Wind Harmer
0.165
3142433PROV 92
Solar/Wind Harmer
0.658
3142433PROV 92
Adder
0.32
3142433PROV 92
Adder
0.32
3145663CRESWEL
Solar/Wind Harmer
0.457
971163AH1-040 GEN
Solar/Wind Harmer
13.055
957481AF2-042 GEN
Solar/Wind Harmer
43.165
316023GEN1_S
Solar/Wind Harmer
0.363
971777AH1-397 GEN
Solar/Wind Harmer
0.424
3141843SHACKLE
Adder
0.82
3141766HARMONY
Solar/Wind Harmer
0.032
3145893MURPHYS
Solar/Wind Harmer
0.635
3145893MURPHYS
Solar/Wind Harmer
0.706
3146206CASHIE
Solar/Wind Harmer
0.159
971547AH1-271 GEN
Solar/Wind Harmer
3.39
315693AD1-088 GEN
Solar/Wind Harmer
7.618
962491AG1-098 GEN
Solar/Wind Harmer
9.031
960081AF2-299 GEN
Solar/Wind Harmer
1.516
3146173TUNIS
Solar/Wind Harmer
0.157
3138133OCRAN
Solar/Wind Harmer
0.094
3145683EARLEYS
Solar/Wind Harmer
0.156
3146263WOODLND
Solar/Wind Harmer
0.155
971795AH1-408 GEN
Solar/Wind Harmer
10.34
316011AB1-132 GEN
Solar/Wind Harmer
2.811
962571AG1-106 GEN
Solar/Wind Harmer
2.2
316190AA2-174 GEN
Solar/Wind Harmer
0
3147043LAWRENC
Adder
1.392
3145823KELFORD
Solar/Wind Harmer
0.153
3145963POPLR C
Solar/Wind Harmer
0.153
3145783HORNRTN
Solar/Wind Harmer
0.152
3145796HORNRTN
Solar/Wind Harmer
0.502
3145796HORNRTN
Solar/Wind Harmer
0.152
316174AB2-169 GEN
Solar/Wind Harmer
0.004
962861AG1-135 GEN
Solar/Wind Harmer
4.751
316212AC1-099_GEN
Solar/Wind Harmer
0.768
316129AC1-054 GEN
Solar/Wind Harmer
0.557
971065AG2-659 GEN
Solar/Wind Harmer
6.296
3146293MARTNCO
Solar/Wind Harmer
0.137
970937AG2-583 GEN
Solar/Wind Harmer
9.004
315687AD1-152 GEN
Solar/Wind Harmer
0.005
966881AG1-559 GEN
Solar/Wind Harmer
0.168
3141726DUNNSVL
Solar/Wind Harmer
0.58
315722AD1-056 GEN
Solar/Wind Harmer
0.916
3145746EVERETS
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
0.144
970685AG2-442 GEN
Solar/Wind Harmer
10.759
316254AC1-120 GEN1
Solar/Wind Harmer
0.307
316237AB2-079_GEN
Solar/Wind Harmer
0.001
963171AG1-166 GEN
Solar/Wind Harmer
0.768
971563AH1-280 GEN
Solar/Wind Harmer
1.536
3152261N ANNA2
50/50
17.068
3150861SPRUNCD
50/50
0.882
3151031BRUNSWICKG2
50/50
2.318
3151101ELIZAR3
50/50
17.311
316044AC1-158 PL1
Solar/Wind Harmer
2.971
316450AC1-158 RIC
Solar/Wind Harmer
0.792
3147666LOUISA
Solar/Wind Harmer
0.538
315773AC2-141 GEN
Solar/Wind Harmer
6.485
315839AE2-212 C
Solar/Wind Harmer
0.001
944581AF1-123 GEN
Solar/Wind Harmer
39.675
944601AF1-125 GEN
Solar/Wind Harmer
39.064
315813AE1-149 C
Solar/Wind Harmer
9.394
965281AG1-393 GEN
Solar/Wind Harmer
1.874
3144873MCLAUGH
Solar/Wind Harmer
0.004
970659AG2-427 GEN
Solar/Wind Harmer
1.855
3144536CHRHLND
Solar/Wind Harmer
0.026
316083AB2-161 GEN
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
3.699
3145336SMITFLD
Solar/Wind Harmer
0.07
3146456SLIGO L269
Solar/Wind Harmer
0.174
971153AH1-033 GEN
Solar/Wind Harmer
2.012
3151221GRAVEL6
Adder
12.623
3151171GRAVELC
Adder
2.429
961611AG1-000B GEN
Solar/Wind Harmer
4.628
315778AD1-151 GEN
Solar/Wind Harmer
13.874
970129AG2-093 GEN
Solar/Wind Harmer
10.479
970133AG2-095 GEN
Solar/Wind Harmer
1.663
3143096IRON208
Adder
0.724
3143096IRON208
Adder
0.71
316313AB2-026
Solar/Wind Harmer
0.109
316258AE1-075 C
Solar/Wind Harmer
0.13
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.611
316320Y1-086
Solar/Wind Harmer
0.001
3144216WINCHST
Adder
0.645
316435W1029_GEN3
Solar/Wind Harmer
0.001
3150921YORKTN3
Adder
4.287
3146516WINFALL
Solar/Wind Harmer
0.17
970917AG2-570 GEN
Solar/Wind Harmer
15.071
3146626S HERTFORD
Solar/Wind Harmer
0.169
3142946ENON
Solar/Wind Harmer
0.057
3145273HOLLAND
Solar/Wind Harmer
0.127
316382AG1-145 C
Solar/Wind Harmer
0.001
970293AG2-193 GEN
Solar/Wind Harmer
1.792
3146376EDENTON
Solar/Wind Harmer
0.166
3142416OLDCHRC
Solar/Wind Harmer
1.602
3142433PROV 92
Adder
0.32
3142433PROV 92
Adder
0.32
315614AA2-178 GEN
Solar/Wind Harmer
0.934
316365GEN2_N
Solar/Wind Harmer
0.363
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
971157AH1-035 GEN
Solar/Wind Harmer
1.929
3141843SHACKLE
Adder
0.82
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
315737AD1-076 GEN
Solar/Wind Harmer
2.062
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
2.134
316156AD2-030 GEN
Solar/Wind Harmer
0.118
3141873WAN 176
Solar/Wind Harmer
2.836
316473AC1-191 GEN
Solar/Wind Harmer
0.538
3145893MURPHYS
Solar/Wind Harmer
0.266
3145893MURPHYS
Solar/Wind Harmer
0.159
3146206CASHIE
Solar/Wind Harmer
0.159
957521AF2-046 GEN
Solar/Wind Harmer
11.795
961681AG1-008 GEN
Solar/Wind Harmer
11.795
3132273ORANGE
Solar/Wind Harmer
0.032
3146173TUNIS
Solar/Wind Harmer
0.157
3156021HOLLOMANSOL
Solar/Wind Harmer
0.713
316463AE2-346 GEN
Solar/Wind Harmer
0.135
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.672
313506AB2-031 GEN
Solar/Wind Harmer
0.482
316478AD1-087 GEN
Solar/Wind Harmer
0.543
316486AD2-202 GEN
Solar/Wind Harmer
0.159
3146263WOODLND
Solar/Wind Harmer
0.155
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
3147043LAWRENC
Solar/Wind Harmer
0.092
316317KELFORD C
Solar/Wind Harmer
0.015
3145823KELFORD
Solar/Wind Harmer
0.153
3145963POPLR C
Solar/Wind Harmer
0.153
3145796HORNRTN
Solar/Wind Harmer
0.609
3145796HORNRTN
Solar/Wind Harmer
0.152
962971AG1-146 GEN
Solar/Wind Harmer
2.434
970009AG2-005 GEN
Solar/Wind Harmer
1.123
970909AG2-566 GEN
Solar/Wind Harmer
1.6
316210AC1-098 GEN
Solar/Wind Harmer
1.377
316404AE1-155 C
Solar/Wind Harmer
0.033
3145933PARMELE
Solar/Wind Harmer
0.147
966801AG1-551 GEN
Solar/Wind Harmer
1.716
315724AD1-057 GEN
Solar/Wind Harmer
0.543
3145746EVERETS
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
0.144
316131AB2-060 GEN
Solar/Wind Harmer
0.454
964241AG1-285 GEN
Solar/Wind Harmer
9.624
315785AD2-033 C
Solar/Wind Harmer
1.173
970257AG2-171 GEN
Solar/Wind Harmer
4.614
959311AF2-222 GEN
Solar/Wind Harmer
12.815
316170AC1-121 GEN2
Solar/Wind Harmer
0.154
963181AG1-167 GEN
Solar/Wind Harmer
0.576
3144293JTRSVLE
Adder
0.458
3147133PAMPLIN
Solar/Wind Harmer
0.452
971193AH1-056 GEN
Solar/Wind Harmer
8.764
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.086
316327AA2-057 GEN
Solar/Wind Harmer
0.217
3150351NORNECKC2
Adder
1.449
3151761LOISA E
Adder
18.847
3146233WITAKRS
Solar/Wind Harmer
0.708
3146233WITAKRS
Solar/Wind Harmer
0.096
3138543CONSLDL
Solar/Wind Harmer
0.093
3146073TAR RVR
Solar/Wind Harmer
0.141
3146083TARBORO
Solar/Wind Harmer
0.141
961601AG1-000A GEN
Solar/Wind Harmer
9.854
3145543BTLEBRO
Solar/Wind Harmer
0.138
3145543BTLEBRO
Solar/Wind Harmer
0.138
971623AH1-311 GEN
Solar/Wind Harmer
0.277
972183AH1-676 GEN
Adder
147.354
3146776BUCKING
Solar/Wind Harmer
0.05
3150401LDYSMT4
Adder
18.101
3150371LDYSMT1
Adder
17.49
971781AH1-399 GEN
Solar/Wind Harmer
0.177
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.61
3141906WESTMOR
Solar/Wind Harmer
0.051
970221AG2-151 GEN
Solar/Wind Harmer
6.519
971683AH1-343 GEN
Solar/Wind Harmer
4.456
970737AG2-469 GEN
Solar/Wind Harmer
5.095
316283AC2-100 C
Solar/Wind Harmer
0.231
970323AG2-213 GEN
Solar/Wind Harmer
6.152
971775AH1-396 GEN
Solar/Wind Harmer
0.231
958211AF2-115 GEN
Solar/Wind Harmer
1.728
963191AG1-168 GEN
Solar/Wind Harmer
0.576
3144293JTRSVLE
Adder
0.458
3144293JTRSVLE
Adder
0.386
3147133PAMPLIN
Solar/Wind Harmer
0.144
3147133PAMPLIN
Solar/Wind Harmer
0.115
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.496
3150341NORNECKC1
Adder
1.484
966001AG1-469 GEN
Solar/Wind Harmer
0.083
3151731LOISA B
Adder
9.244
3151721LOISA A
Adder
9.197
315673AE1-157 GEN
Solar/Wind Harmer
9.786
3145493TOT1
Solar/Wind Harmer
0.326
3145453TOT5
Solar/Wind Harmer
0.196
3145603CNETO
Solar/Wind Harmer
0.13
961601AG1-000A GEN
Solar/Wind Harmer
2.463
316263AC1-034 GEN
Solar/Wind Harmer
5.264
962561AG1-105 GEN
Solar/Wind Harmer
6.627
3146776BUCKING
Solar/Wind Harmer
0.551
3146776BUCKING
Solar/Wind Harmer
0.045
964791AG1-342 GEN
Solar/Wind Harmer
2.629
3146843MT LREL
Solar/Wind Harmer
0.137
3146843MT LREL
Solar/Wind Harmer
0.137
3150391LDYSMT3
Adder
18.067
972195AH1-682 GEN
Adder
2.374
316468AD1-105 GEN
Solar/Wind Harmer
-0.044
971489AH1-241 GEN
Solar/Wind Harmer
6.519
316222AC1-221 GEN
Solar/Wind Harmer
0.492
3144293JTRSVLE
Adder
0.458
3146926FARMVIL
Solar/Wind Harmer
0.086
3150351NORNECKC2
Adder
1.425
316494AC1-189 GEN
Solar/Wind Harmer
0.481
3151751LOISA D
Adder
9.244
3146233WITAKRS
Solar/Wind Harmer
0.561
961671AG1-007 GEN
Solar/Wind Harmer
0.022
3146083TARBORO
Solar/Wind Harmer
0.141
3145493TOT1
Solar/Wind Harmer
0.626
3145543BTLEBRO
Solar/Wind Harmer
0.138
3145543BTLEBRO
Solar/Wind Harmer
0.111
316359AB2-059 GEN
Solar/Wind Harmer
0.498
316049AB1-081 GEN
Solar/Wind Harmer
0.793
3142053HEARTS
Solar/Wind Harmer
0.244
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.055
970401AG2-262 GEN
Solar/Wind Harmer
0.803
316337AD2-073 GEN
Solar/Wind Harmer
0.118
972197AH1-683 GEN
Adder
2.827
972219AH1-694 GEN
Adder
2.035
972003AH1-546 GEN
Solar/Wind Harmer
5.618
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971377AH1-170 GEN
Solar/Wind Harmer
1.304
3147623JAMES R
Solar/Wind Harmer
0.283
972135AH1-637 GEN
Solar/Wind Harmer
0.976
LAGNLTFEXP_LAGN->PJM
CLTF
5.963
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.817
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.186
MECLTFEXP_MEC->PJM
CLTF
2.509
CBM South 2LTFEXP_CBM-S2->PJM
CBM
19.52
TVALTFEXP_TVA->PJM
CLTF
3.02
SIGELTFEXP_SIGE->PJM
CLTF
0.076
NYPJM->LTFIMP_NY
CLTF
2.547
LGEELTFEXP_LGEE->PJM
CLTF
0.9
WECLTFEXP_WEC->PJM
CLTF
0.426
CPLELTFEXP_CPLE->PJM
CLTF
9
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.036

Details for AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.0 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1248.61
MW Contribution:7.26
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
1.086
3144293JTRSVLE
50/50
1.009
3144293JTRSVLE
50/50
0.85
970535AG2-341 GEN
50/50
5.15
316222AC1-221 GEN
Solar/Wind Harmer
10.229
970099AG2-077 GEN
Solar/Wind Harmer
67.902
970933AG2-581 GEN
Solar/Wind Harmer
50.214
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.644
962561AG1-105 GEN
Solar/Wind Harmer
26.877
971741AH1-377 GEN
Solar/Wind Harmer
48.375
970301AG2-198 GEN
Solar/Wind Harmer
19.484
313527AB2-043 GEN
Solar/Wind Harmer
5.914
970323AG2-213 GEN
Solar/Wind Harmer
17.447
971775AH1-396 GEN
Solar/Wind Harmer
2.485
316034AC1-036 C
Solar/Wind Harmer
0.647
958211AF2-115 GEN
Solar/Wind Harmer
5.246
963191AG1-168 GEN
Solar/Wind Harmer
3.148
942751AE2-291 GEN
Solar/Wind Harmer
21.29
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.128
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.959
316197AC1-042 GEN
Solar/Wind Harmer
1.485
942671AE2-283 GEN
Solar/Wind Harmer
3.997
971489AH1-241 GEN
Solar/Wind Harmer
6.897
315821AE2-092 GEN
Solar/Wind Harmer
1.796
316181AB2-040 GEN
Solar/Wind Harmer
1.066
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.786
3151531CLOVER1
50/50
10.81
3144293JTRSVLE
50/50
1.009
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3147043LAWRENC
50/50
1.435
3151561HALLBR1
50/50
0.347
3151931BEARGRDN S1
50/50
1.382
3151911BEARGRDN G1
50/50
1.071
315687AD1-152 GEN
Solar/Wind Harmer
7.754
316003AC1-222 GEN
Solar/Wind Harmer
5.366
957481AF2-042 GEN
Solar/Wind Harmer
169.755
315693AD1-088 GEN
Solar/Wind Harmer
25.249
962491AG1-098 GEN
Solar/Wind Harmer
33.372
970401AG2-262 GEN
Solar/Wind Harmer
3.252
316237AB2-079_GEN
Solar/Wind Harmer
1.108
970685AG2-442 GEN
Solar/Wind Harmer
29.934
963171AG1-166 GEN
Solar/Wind Harmer
4.197
971563AH1-280 GEN
Solar/Wind Harmer
4.197
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.353
316322AB2-045
Solar/Wind Harmer
0.758
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.877
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.335
971795AH1-408 GEN
Solar/Wind Harmer
10.57
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.525
971377AH1-170 GEN
Solar/Wind Harmer
1.453
3147623JAMES R
Solar/Wind Harmer
0.18
970937AG2-583 GEN
Solar/Wind Harmer
7.555
970413AG2-270 GEN
50/50
47.174
3144293JTRSVLE
50/50
1.009
3151591KERR 2
50/50
0.537
3151921BEARGRDN G2
50/50
1.071
316248AF1-058 C
Solar/Wind Harmer
1.793
960061AF2-297 GEN
Solar/Wind Harmer
29.749
316478AD1-087 GEN
Solar/Wind Harmer
4.929
316486AD2-202 GEN
Solar/Wind Harmer
1.444
971683AH1-343 GEN
Solar/Wind Harmer
22.008
970909AG2-566 GEN
Solar/Wind Harmer
3.699
316131AB2-060 GEN
Solar/Wind Harmer
3.917
964241AG1-285 GEN
Solar/Wind Harmer
28.021
315785AD2-033 C
Solar/Wind Harmer
7.969
970257AG2-171 GEN
Solar/Wind Harmer
13.085
959311AF2-222 GEN
Solar/Wind Harmer
36.211
963181AG1-167 GEN
Solar/Wind Harmer
3.148
3147133PAMPLIN
Solar/Wind Harmer
-0.104
971193AH1-056 GEN
Solar/Wind Harmer
20.705
942461AE2-259 GEN
Solar/Wind Harmer
4.788
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.525
970221AG2-151 GEN
Solar/Wind Harmer
7.265
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.614
316313AB2-026
Solar/Wind Harmer
0.176
316258AE1-075 C
Solar/Wind Harmer
0.158
316405AF2-144 C
Solar/Wind Harmer
0.167
3143336POWHATN
Solar/Wind Harmer
0.657
316283AC2-100 C
Solar/Wind Helper
2.324
960081AF2-299 GEN
Solar/Wind Harmer
0.925
316336AC2-165 C
Solar/Wind Harmer
1.327
3143336POWHATN
Solar/Wind Harmer
0.773
3151541CLOVER2
50/50
10.758
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
972205AH1-687 GEN
50/50
5.223
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.765
971967AH1-528 GEN
Solar/Wind Harmer
100.698
970865AG2-541 GEN
Solar/Wind Harmer
19.076
316123AC1-075 GEN
Solar/Wind Harmer
4.171
970165AG2-112 GEN
Solar/Wind Harmer
3.672
970163AG2-111 GEN
Solar/Wind Harmer
3.503
316239AB2-077_GEN
Solar/Wind Harmer
1.108
316238AB2-078_GEN
Solar/Wind Harmer
1.108
971443AH1-215 GEN
Solar/Wind Harmer
6.88
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.727
970681AG2-440 GEN
Solar/Wind Harmer
21.381
946301AF1-294 GEN
Solar/Wind Harmer
8.604
961791AG1-021 GEN
Solar/Wind Harmer
4.197
315657AE1-056 GEN
Solar/Wind Harmer
12.423
970285AG2-188 GEN
Solar/Wind Harmer
21.434
971845AH1-439 GEN
Solar/Wind Harmer
12.337
970831AG2-522 GEN
Solar/Wind Harmer
10.013
971447AH1-217 GEN
Solar/Wind Harmer
3.92
270494AE1-108_GEN
Solar/Wind Harmer
2.506
946281AF1-292 GEN
Solar/Wind Harmer
0.184
316087AB2-174 GEN
Solar/Wind Harmer
1.115
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.376
270457AD2-023 GEN
Solar/Wind Helper
0.907
3145593CAROLNA
Solar/Wind Harmer
0.058
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.85
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.677
VTFLTFEXP_VFT->PJM
CMTX
1.127
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.809
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.962
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.429
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.343
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.375

Details for AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.45 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1220.46
MW Contribution:7.28
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
1.084
3144293JTRSVLE
50/50
1.008
3144293JTRSVLE
50/50
0.849
970535AG2-341 GEN
50/50
5.137
316222AC1-221 GEN
Solar/Wind Harmer
10.209
970099AG2-077 GEN
Solar/Wind Harmer
67.776
970933AG2-581 GEN
Solar/Wind Harmer
50.121
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.622
962561AG1-105 GEN
Solar/Wind Harmer
26.822
971741AH1-377 GEN
Solar/Wind Harmer
48.301
970301AG2-198 GEN
Solar/Wind Harmer
19.456
313527AB2-043 GEN
Solar/Wind Harmer
5.902
970323AG2-213 GEN
Solar/Wind Harmer
17.415
971775AH1-396 GEN
Solar/Wind Harmer
2.48
316034AC1-036 C
Solar/Wind Harmer
0.646
958211AF2-115 GEN
Solar/Wind Harmer
5.238
963191AG1-168 GEN
Solar/Wind Harmer
3.143
942751AE2-291 GEN
Solar/Wind Harmer
21.229
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.08
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.947
316197AC1-042 GEN
Solar/Wind Harmer
1.476
942671AE2-283 GEN
Solar/Wind Harmer
3.973
971489AH1-241 GEN
Solar/Wind Harmer
6.915
315821AE2-092 GEN
Solar/Wind Harmer
1.803
316181AB2-040 GEN
Solar/Wind Harmer
1.066
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.785
3145593CAROLNA
Solar/Wind Harmer
0.058
3151531CLOVER1
50/50
10.79
3144293JTRSVLE
50/50
1.008
3151601KERR 3
50/50
0.535
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.434
3151561HALLBR1
50/50
0.346
3151931BEARGRDN S1
50/50
1.386
3151911BEARGRDN G1
50/50
1.074
315687AD1-152 GEN
Solar/Wind Harmer
7.739
316003AC1-222 GEN
Solar/Wind Harmer
5.355
957481AF2-042 GEN
Solar/Wind Harmer
169.439
315693AD1-088 GEN
Solar/Wind Harmer
25.203
962491AG1-098 GEN
Solar/Wind Harmer
33.312
970401AG2-262 GEN
Solar/Wind Harmer
3.246
316237AB2-079_GEN
Solar/Wind Harmer
1.105
970685AG2-442 GEN
Solar/Wind Harmer
29.883
963171AG1-166 GEN
Solar/Wind Harmer
4.19
971563AH1-280 GEN
Solar/Wind Harmer
4.19
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.32
316322AB2-045
Solar/Wind Harmer
0.758
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.872
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.349
971795AH1-408 GEN
Solar/Wind Harmer
10.568
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.498
971377AH1-170 GEN
Solar/Wind Harmer
1.457
3147623JAMES R
Solar/Wind Harmer
0.18
970937AG2-583 GEN
Solar/Wind Harmer
7.594
960081AF2-299 GEN
Solar/Wind Harmer
0.927
316336AC2-165 C
Solar/Wind Harmer
1.341
3143336POWHATN
Solar/Wind Harmer
0.784
970413AG2-270 GEN
50/50
47.085
3144293JTRSVLE
50/50
1.008
3151591KERR 2
50/50
0.535
3151921BEARGRDN G2
50/50
1.074
316248AF1-058 C
Solar/Wind Harmer
1.789
960061AF2-297 GEN
Solar/Wind Harmer
29.687
316478AD1-087 GEN
Solar/Wind Harmer
4.92
316486AD2-202 GEN
Solar/Wind Harmer
1.441
971683AH1-343 GEN
Solar/Wind Harmer
21.959
970909AG2-566 GEN
Solar/Wind Harmer
3.694
316131AB2-060 GEN
Solar/Wind Harmer
3.909
964241AG1-285 GEN
Solar/Wind Harmer
27.966
315785AD2-033 C
Solar/Wind Harmer
7.954
970257AG2-171 GEN
Solar/Wind Harmer
13.061
959311AF2-222 GEN
Solar/Wind Harmer
36.146
963181AG1-167 GEN
Solar/Wind Harmer
3.143
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.674
942461AE2-259 GEN
Solar/Wind Harmer
4.782
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.498
970221AG2-151 GEN
Solar/Wind Harmer
7.284
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.615
316313AB2-026
Solar/Wind Harmer
0.178
316258AE1-075 C
Solar/Wind Harmer
0.16
316405AF2-144 C
Solar/Wind Harmer
0.169
3143336POWHATN
Solar/Wind Harmer
0.666
316283AC2-100 C
Solar/Wind Helper
2.343
270018AE2-047 C O1
Solar/Wind Helper
0.4
3151541CLOVER2
50/50
10.738
3151611KERR 4
50/50
0.535
3151621KERR 5
50/50
0.535
3151631KERR 6
50/50
0.535
3151641KERR 7
50/50
0.535
972205AH1-687 GEN
50/50
5.237
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.757
971967AH1-528 GEN
Solar/Wind Harmer
100.512
970865AG2-541 GEN
Solar/Wind Harmer
19.031
316123AC1-075 GEN
Solar/Wind Harmer
4.16
970165AG2-112 GEN
Solar/Wind Harmer
3.663
970163AG2-111 GEN
Solar/Wind Harmer
3.494
316239AB2-077_GEN
Solar/Wind Harmer
1.105
316238AB2-078_GEN
Solar/Wind Harmer
1.105
971443AH1-215 GEN
Solar/Wind Harmer
6.867
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.682
970681AG2-440 GEN
Solar/Wind Harmer
21.345
946301AF1-294 GEN
Solar/Wind Harmer
8.59
961791AG1-021 GEN
Solar/Wind Harmer
4.19
315657AE1-056 GEN
Solar/Wind Harmer
12.405
970285AG2-188 GEN
Solar/Wind Harmer
21.428
971845AH1-439 GEN
Solar/Wind Harmer
12.335
970831AG2-522 GEN
Solar/Wind Harmer
9.984
971447AH1-217 GEN
Solar/Wind Harmer
3.931
270494AE1-108_GEN
Solar/Wind Harmer
2.509
946281AF1-292 GEN
Solar/Wind Harmer
0.185
316087AB2-174 GEN
Solar/Wind Harmer
1.116
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.395
270457AD2-023 GEN
Solar/Wind Helper
0.919
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.869
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.738
VTFLTFEXP_VFT->PJM
CMTX
1.375
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.857
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.08
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.522
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.505
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.476

Details for AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.42 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1220.19
MW Contribution:7.28
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
1.084
3144293JTRSVLE
50/50
1.008
3144293JTRSVLE
50/50
0.849
970535AG2-341 GEN
50/50
5.137
316222AC1-221 GEN
Solar/Wind Harmer
10.209
970099AG2-077 GEN
Solar/Wind Harmer
67.776
970933AG2-581 GEN
Solar/Wind Harmer
50.121
3151531CLOVER1
50/50
10.79
3144293JTRSVLE
50/50
1.008
3151601KERR 3
50/50
0.535
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.434
3151561HALLBR1
50/50
0.346
3151931BEARGRDN S1
50/50
1.386
3151911BEARGRDN G1
50/50
1.074
315687AD1-152 GEN
Solar/Wind Harmer
7.739
316003AC1-222 GEN
Solar/Wind Harmer
5.355
957481AF2-042 GEN
Solar/Wind Harmer
169.439
315693AD1-088 GEN
Solar/Wind Harmer
25.203
962491AG1-098 GEN
Solar/Wind Harmer
33.312
970401AG2-262 GEN
Solar/Wind Harmer
3.246
316237AB2-079_GEN
Solar/Wind Harmer
1.105
970685AG2-442 GEN
Solar/Wind Harmer
29.883
963171AG1-166 GEN
Solar/Wind Harmer
4.19
971563AH1-280 GEN
Solar/Wind Harmer
4.19
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.32
970413AG2-270 GEN
50/50
47.085
3144293JTRSVLE
50/50
1.008
3151591KERR 2
50/50
0.535
3151921BEARGRDN G2
50/50
1.074
316248AF1-058 C
Solar/Wind Harmer
1.789
960061AF2-297 GEN
Solar/Wind Harmer
29.687
316478AD1-087 GEN
Solar/Wind Harmer
4.92
316486AD2-202 GEN
Solar/Wind Harmer
1.441
971683AH1-343 GEN
Solar/Wind Harmer
21.959
970909AG2-566 GEN
Solar/Wind Harmer
3.694
316131AB2-060 GEN
Solar/Wind Harmer
3.909
964241AG1-285 GEN
Solar/Wind Harmer
27.966
315785AD2-033 C
Solar/Wind Harmer
7.954
970257AG2-171 GEN
Solar/Wind Harmer
13.061
959311AF2-222 GEN
Solar/Wind Harmer
36.146
963181AG1-167 GEN
Solar/Wind Harmer
3.143
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.674
942461AE2-259 GEN
Solar/Wind Harmer
4.782
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.498
970221AG2-151 GEN
Solar/Wind Harmer
7.284
966621AG1-532 GEN
Solar/Wind Harmer
0.167
316322AB2-045
Solar/Wind Harmer
0.758
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.872
3147123OTTER R
Solar/Wind Harmer
-0.01
3151541CLOVER2
50/50
10.738
3151611KERR 4
50/50
0.535
3151621KERR 5
50/50
0.535
3151631KERR 6
50/50
0.535
3151641KERR 7
50/50
0.535
972205AH1-687 GEN
50/50
5.237
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.757
971967AH1-528 GEN
Solar/Wind Harmer
100.512
970865AG2-541 GEN
Solar/Wind Harmer
19.031
316123AC1-075 GEN
Solar/Wind Harmer
4.16
970165AG2-112 GEN
Solar/Wind Harmer
3.663
970163AG2-111 GEN
Solar/Wind Harmer
3.494
316239AB2-077_GEN
Solar/Wind Harmer
1.105
316238AB2-078_GEN
Solar/Wind Harmer
1.105
971443AH1-215 GEN
Solar/Wind Harmer
6.867
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.682
970681AG2-440 GEN
Solar/Wind Harmer
21.345
946301AF1-294 GEN
Solar/Wind Harmer
8.59
961791AG1-021 GEN
Solar/Wind Harmer
4.19
315657AE1-056 GEN
Solar/Wind Harmer
12.405
970285AG2-188 GEN
Solar/Wind Harmer
21.428
971845AH1-439 GEN
Solar/Wind Harmer
12.335
970831AG2-522 GEN
Solar/Wind Harmer
9.984
971447AH1-217 GEN
Solar/Wind Harmer
3.931
270494AE1-108_GEN
Solar/Wind Harmer
2.509
946281AF1-292 GEN
Solar/Wind Harmer
0.185
316087AB2-174 GEN
Solar/Wind Harmer
1.116
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.395
270457AD2-023 GEN
Solar/Wind Helper
0.919
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.622
962561AG1-105 GEN
Solar/Wind Harmer
26.822
971741AH1-377 GEN
Solar/Wind Harmer
48.301
970301AG2-198 GEN
Solar/Wind Harmer
19.456
313527AB2-043 GEN
Solar/Wind Harmer
5.902
970323AG2-213 GEN
Solar/Wind Harmer
17.415
971775AH1-396 GEN
Solar/Wind Harmer
2.48
316034AC1-036 C
Solar/Wind Harmer
0.646
958211AF2-115 GEN
Solar/Wind Harmer
5.238
963191AG1-168 GEN
Solar/Wind Harmer
3.143
942751AE2-291 GEN
Solar/Wind Harmer
21.229
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.08
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.947
316197AC1-042 GEN
Solar/Wind Harmer
1.476
942671AE2-283 GEN
Solar/Wind Harmer
3.973
971489AH1-241 GEN
Solar/Wind Harmer
6.915
315821AE2-092 GEN
Solar/Wind Harmer
1.803
316181AB2-040 GEN
Solar/Wind Harmer
1.066
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.785
3145593CAROLNA
Solar/Wind Harmer
0.058
972003AH1-546 GEN
Solar/Wind Harmer
7.349
971795AH1-408 GEN
Solar/Wind Harmer
10.568
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.498
971377AH1-170 GEN
Solar/Wind Harmer
1.457
3147623JAMES R
Solar/Wind Harmer
0.18
970937AG2-583 GEN
Solar/Wind Harmer
7.594
960081AF2-299 GEN
Solar/Wind Harmer
0.927
316336AC2-165 C
Solar/Wind Harmer
1.341
3143336POWHATN
Solar/Wind Harmer
0.784
313506AB2-031 GEN
Solar/Wind Harmer
0.615
316313AB2-026
Solar/Wind Harmer
0.178
316258AE1-075 C
Solar/Wind Harmer
0.16
316405AF2-144 C
Solar/Wind Harmer
0.169
3143336POWHATN
Solar/Wind Harmer
0.666
316283AC2-100 C
Solar/Wind Helper
2.343
270018AE2-047 C O1
Solar/Wind Helper
0.4
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.869
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.738
VTFLTFEXP_VFT->PJM
CMTX
1.375
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.857
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.08
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.522
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.505
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.476

Details for AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.84 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1202.69
MW Contribution:7.17
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
10.912
3144293JTRSVLE
50/50
1.003
3151601KERR 3
50/50
0.535
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.433
3151561HALLBR1
50/50
0.349
3151931BEARGRDN S1
50/50
1.364
3151911BEARGRDN G1
50/50
1.057
315687AD1-152 GEN
Solar/Wind Harmer
7.805
957481AF2-042 GEN
Solar/Wind Harmer
172.899
316003AC1-222 GEN
Solar/Wind Harmer
5.386
970401AG2-262 GEN
Solar/Wind Harmer
3.259
315693AD1-088 GEN
Solar/Wind Harmer
24.873
962491AG1-098 GEN
Solar/Wind Harmer
32.876
316237AB2-079_GEN
Solar/Wind Harmer
1.106
970685AG2-442 GEN
Solar/Wind Harmer
29.769
963171AG1-166 GEN
Solar/Wind Harmer
4.169
971563AH1-280 GEN
Solar/Wind Harmer
4.169
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.328
316322AB2-045
Solar/Wind Harmer
0.749
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.873
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.24
971795AH1-408 GEN
Solar/Wind Harmer
10.551
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.548
971377AH1-170 GEN
Solar/Wind Harmer
1.434
3147623JAMES R
Solar/Wind Harmer
0.178
970937AG2-583 GEN
Solar/Wind Harmer
7.455
960081AF2-299 GEN
Solar/Wind Harmer
0.924
316336AC2-165 C
Solar/Wind Harmer
1.309
3143336POWHATN
Solar/Wind Harmer
0.763
3151541CLOVER2
50/50
10.86
3151611KERR 4
50/50
0.535
3151621KERR 5
50/50
0.535
3151631KERR 6
50/50
0.535
3151641KERR 7
50/50
0.535
972205AH1-687 GEN
50/50
5.155
3147173SINAI
Solar/Wind Harmer
-0.06
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.776
970865AG2-541 GEN
Solar/Wind Harmer
19.147
316123AC1-075 GEN
Solar/Wind Harmer
4.187
970165AG2-112 GEN
Solar/Wind Harmer
3.686
970163AG2-111 GEN
Solar/Wind Harmer
3.517
316239AB2-077_GEN
Solar/Wind Harmer
1.106
316238AB2-078_GEN
Solar/Wind Harmer
1.106
971443AH1-215 GEN
Solar/Wind Harmer
6.851
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.58
970681AG2-440 GEN
Solar/Wind Harmer
21.264
946301AF1-294 GEN
Solar/Wind Harmer
8.547
961791AG1-021 GEN
Solar/Wind Harmer
4.169
315657AE1-056 GEN
Solar/Wind Harmer
12.33
970285AG2-188 GEN
Solar/Wind Harmer
21.156
971845AH1-439 GEN
Solar/Wind Harmer
12.177
970831AG2-522 GEN
Solar/Wind Harmer
9.991
971447AH1-217 GEN
Solar/Wind Harmer
3.869
270494AE1-108_GEN
Solar/Wind Harmer
2.477
946281AF1-292 GEN
Solar/Wind Harmer
0.184
316087AB2-174 GEN
Solar/Wind Harmer
1.113
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.367
270457AD2-023 GEN
Solar/Wind Helper
0.901
3152661PLYWOOD A
50/50
1.089
3144293JTRSVLE
50/50
1.003
3144293JTRSVLE
50/50
0.844
970535AG2-341 GEN
50/50
5.14
316222AC1-221 GEN
Solar/Wind Harmer
10.244
970099AG2-077 GEN
Solar/Wind Harmer
69.159
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.665
962561AG1-105 GEN
Solar/Wind Harmer
26.917
971741AH1-377 GEN
Solar/Wind Harmer
47.685
970301AG2-198 GEN
Solar/Wind Harmer
19.211
313527AB2-043 GEN
Solar/Wind Harmer
5.903
970323AG2-213 GEN
Solar/Wind Harmer
17.371
971775AH1-396 GEN
Solar/Wind Harmer
2.474
316034AC1-036 C
Solar/Wind Harmer
0.644
942751AE2-291 GEN
Solar/Wind Harmer
21.373
958211AF2-115 GEN
Solar/Wind Harmer
5.211
963191AG1-168 GEN
Solar/Wind Harmer
3.127
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.09
3146776BUCKING
Solar/Wind Harmer
-0.089
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.968
316197AC1-042 GEN
Solar/Wind Harmer
1.492
942671AE2-283 GEN
Solar/Wind Harmer
4.017
971489AH1-241 GEN
Solar/Wind Harmer
6.809
315821AE2-092 GEN
Solar/Wind Harmer
1.772
316181AB2-040 GEN
Solar/Wind Harmer
1.064
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.785
3145593CAROLNA
Solar/Wind Harmer
0.058
970413AG2-270 GEN
50/50
47.618
3144293JTRSVLE
50/50
1.003
3151591KERR 2
50/50
0.535
3151921BEARGRDN G2
50/50
1.057
316248AF1-058 C
Solar/Wind Harmer
1.799
960061AF2-297 GEN
Solar/Wind Harmer
29.857
316478AD1-087 GEN
Solar/Wind Harmer
4.976
316486AD2-202 GEN
Solar/Wind Harmer
1.457
971683AH1-343 GEN
Solar/Wind Harmer
22.089
970909AG2-566 GEN
Solar/Wind Harmer
3.648
316131AB2-060 GEN
Solar/Wind Harmer
3.91
964241AG1-285 GEN
Solar/Wind Harmer
27.945
315785AD2-033 C
Solar/Wind Harmer
7.938
970257AG2-171 GEN
Solar/Wind Harmer
13.028
959311AF2-222 GEN
Solar/Wind Harmer
36.042
963181AG1-167 GEN
Solar/Wind Harmer
3.127
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.55
942461AE2-259 GEN
Solar/Wind Harmer
4.741
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.548
970221AG2-151 GEN
Solar/Wind Harmer
7.172
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.613
316313AB2-026
Solar/Wind Harmer
0.173
316258AE1-075 C
Solar/Wind Harmer
0.156
316405AF2-144 C
Solar/Wind Harmer
0.165
3143336POWHATN
Solar/Wind Harmer
0.648
316283AC2-100 C
Solar/Wind Helper
2.31
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.845
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.662
VTFLTFEXP_VFT->PJM
CMTX
1.071
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.798
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.933
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.408
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.306
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.353

Details for AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.84 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1202.63
MW Contribution:7.17
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.859
3151611KERR 4
50/50
0.535
3151621KERR 5
50/50
0.535
3151631KERR 6
50/50
0.535
3151641KERR 7
50/50
0.535
972205AH1-687 GEN
50/50
5.156
3147173SINAI
Solar/Wind Harmer
-0.06
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.775
970865AG2-541 GEN
Solar/Wind Harmer
19.147
316123AC1-075 GEN
Solar/Wind Harmer
4.187
970165AG2-112 GEN
Solar/Wind Harmer
3.686
970163AG2-111 GEN
Solar/Wind Harmer
3.517
316239AB2-077_GEN
Solar/Wind Harmer
1.106
316238AB2-078_GEN
Solar/Wind Harmer
1.106
971443AH1-215 GEN
Solar/Wind Harmer
6.851
3152661PLYWOOD A
50/50
1.089
3144293JTRSVLE
50/50
1.003
3144293JTRSVLE
50/50
0.844
970535AG2-341 GEN
50/50
5.14
316222AC1-221 GEN
Solar/Wind Harmer
10.244
970099AG2-077 GEN
Solar/Wind Harmer
69.15
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.664
962561AG1-105 GEN
Solar/Wind Harmer
26.917
971741AH1-377 GEN
Solar/Wind Harmer
47.691
970301AG2-198 GEN
Solar/Wind Harmer
19.213
313527AB2-043 GEN
Solar/Wind Harmer
5.903
970323AG2-213 GEN
Solar/Wind Harmer
17.372
971775AH1-396 GEN
Solar/Wind Harmer
2.474
316034AC1-036 C
Solar/Wind Harmer
0.644
942751AE2-291 GEN
Solar/Wind Harmer
21.372
958211AF2-115 GEN
Solar/Wind Harmer
5.212
963191AG1-168 GEN
Solar/Wind Harmer
3.127
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.09
3146776BUCKING
Solar/Wind Harmer
-0.089
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.968
316197AC1-042 GEN
Solar/Wind Harmer
1.492
942671AE2-283 GEN
Solar/Wind Harmer
4.017
971489AH1-241 GEN
Solar/Wind Harmer
6.81
315821AE2-092 GEN
Solar/Wind Harmer
1.772
316181AB2-040 GEN
Solar/Wind Harmer
1.064
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.785
3145593CAROLNA
Solar/Wind Harmer
0.058
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.581
970681AG2-440 GEN
Solar/Wind Harmer
21.265
946301AF1-294 GEN
Solar/Wind Harmer
8.547
961791AG1-021 GEN
Solar/Wind Harmer
4.169
315657AE1-056 GEN
Solar/Wind Harmer
12.331
970285AG2-188 GEN
Solar/Wind Harmer
21.159
971845AH1-439 GEN
Solar/Wind Harmer
12.178
970831AG2-522 GEN
Solar/Wind Harmer
9.991
971447AH1-217 GEN
Solar/Wind Harmer
3.87
270494AE1-108_GEN
Solar/Wind Harmer
2.477
3151531CLOVER1
50/50
10.911
3144293JTRSVLE
50/50
1.003
3151601KERR 3
50/50
0.535
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.433
3151561HALLBR1
50/50
0.349
3151931BEARGRDN S1
50/50
1.364
3151911BEARGRDN G1
50/50
1.057
315687AD1-152 GEN
Solar/Wind Harmer
7.805
957481AF2-042 GEN
Solar/Wind Harmer
172.875
316003AC1-222 GEN
Solar/Wind Harmer
5.386
970401AG2-262 GEN
Solar/Wind Harmer
3.259
315693AD1-088 GEN
Solar/Wind Harmer
24.876
962491AG1-098 GEN
Solar/Wind Harmer
32.88
316237AB2-079_GEN
Solar/Wind Harmer
1.106
970685AG2-442 GEN
Solar/Wind Harmer
29.77
963171AG1-166 GEN
Solar/Wind Harmer
4.169
971563AH1-280 GEN
Solar/Wind Harmer
4.169
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.328
316322AB2-045
Solar/Wind Harmer
0.749
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.873
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.24
971795AH1-408 GEN
Solar/Wind Harmer
10.551
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.548
971377AH1-170 GEN
Solar/Wind Harmer
1.435
3147623JAMES R
Solar/Wind Harmer
0.178
970937AG2-583 GEN
Solar/Wind Harmer
7.456
960081AF2-299 GEN
Solar/Wind Harmer
0.924
316336AC2-165 C
Solar/Wind Harmer
1.309
3143336POWHATN
Solar/Wind Harmer
0.763
970413AG2-270 GEN
50/50
47.615
3144293JTRSVLE
50/50
1.003
3151591KERR 2
50/50
0.535
3151921BEARGRDN G2
50/50
1.057
316248AF1-058 C
Solar/Wind Harmer
1.799
960061AF2-297 GEN
Solar/Wind Harmer
29.856
316478AD1-087 GEN
Solar/Wind Harmer
4.975
316486AD2-202 GEN
Solar/Wind Harmer
1.457
971683AH1-343 GEN
Solar/Wind Harmer
22.089
970909AG2-566 GEN
Solar/Wind Harmer
3.648
316131AB2-060 GEN
Solar/Wind Harmer
3.91
964241AG1-285 GEN
Solar/Wind Harmer
27.945
315785AD2-033 C
Solar/Wind Harmer
7.938
970257AG2-171 GEN
Solar/Wind Harmer
13.029
959311AF2-222 GEN
Solar/Wind Harmer
36.043
963181AG1-167 GEN
Solar/Wind Harmer
3.127
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.551
942461AE2-259 GEN
Solar/Wind Harmer
4.741
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.548
970221AG2-151 GEN
Solar/Wind Harmer
7.173
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.613
316313AB2-026
Solar/Wind Harmer
0.173
316258AE1-075 C
Solar/Wind Harmer
0.156
316405AF2-144 C
Solar/Wind Harmer
0.165
3143336POWHATN
Solar/Wind Harmer
0.648
316283AC2-100 C
Solar/Wind Helper
2.31
946281AF1-292 GEN
Solar/Wind Harmer
0.184
316087AB2-174 GEN
Solar/Wind Harmer
1.113
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.367
270457AD2-023 GEN
Solar/Wind Helper
0.901
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.845
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.662
VTFLTFEXP_VFT->PJM
CMTX
1.071
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.798
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.933
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.409
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.307
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.353

Details for AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.96 %
Rating:903.34 MVA
Rating Type:B
MVA to Mitigate:939.11
MW Contribution:5.52
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
10.81
3144293JTRSVLE
50/50
1.009
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3147043LAWRENC
50/50
1.435
3151561HALLBR1
50/50
0.347
3151931BEARGRDN S1
50/50
1.382
3151911BEARGRDN G1
50/50
1.071
3151261ROARAP2
50/50
0.077
24728405LEESVG
50/50
0.073
315687AD1-152 GEN
Solar/Wind Harmer
0.019
316003AC1-222 GEN
Solar/Wind Harmer
0.013
957481AF2-042 GEN
Solar/Wind Harmer
128.928
315693AD1-088 GEN
Solar/Wind Harmer
21.573
962491AG1-098 GEN
Solar/Wind Harmer
25.346
970401AG2-262 GEN
Solar/Wind Harmer
2.602
316237AB2-079_GEN
Solar/Wind Harmer
0.003
970685AG2-442 GEN
Solar/Wind Harmer
22.735
963171AG1-166 GEN
Solar/Wind Harmer
1.594
971563AH1-280 GEN
Solar/Wind Harmer
3.188
3146926FARMVIL
Solar/Wind Harmer
0.163
971065AG2-659 GEN
Solar/Wind Harmer
8.623
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.08
316129AC1-054 GEN
Solar/Wind Harmer
0.717
3147123OTTER R
Solar/Wind Harmer
0.087
972003AH1-546 GEN
Solar/Wind Harmer
5.562
971795AH1-408 GEN
Solar/Wind Harmer
8.362
3147312GRETNA
Solar/Wind Harmer
0.086
3146802CHATHAM
Solar/Wind Harmer
0.08
941801AE2-185 GEN
Solar/Wind Harmer
3.437
971377AH1-170 GEN
Solar/Wind Harmer
1.104
3147623JAMES R
Solar/Wind Harmer
0.24
970937AG2-583 GEN
Solar/Wind Harmer
5.738
960081AF2-299 GEN
Solar/Wind Harmer
0.703
316336AC2-165 C
Solar/Wind Harmer
0.003
3143336POWHATN
Solar/Wind Harmer
1.031
3151541CLOVER2
50/50
10.758
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
972205AH1-687 GEN
50/50
5.223
3151281ROARAP4
50/50
0.075
3151281ROARAP4
50/50
0.07
3147173SINAI
Solar/Wind Harmer
0.529
3147243WELCO
Solar/Wind Harmer
0.331
316118AC1-105 GEN
Solar/Wind Harmer
1.258
971967AH1-528 GEN
Solar/Wind Harmer
76.276
970865AG2-541 GEN
Solar/Wind Harmer
14.488
316123AC1-075 GEN
Solar/Wind Harmer
0.47
970165AG2-112 GEN
Solar/Wind Harmer
2.789
970163AG2-111 GEN
Solar/Wind Harmer
2.661
316239AB2-077_GEN
Solar/Wind Harmer
0.003
316238AB2-078_GEN
Solar/Wind Harmer
0.003
971443AH1-215 GEN
Solar/Wind Harmer
5.225
3144303KENBRDG
Solar/Wind Harmer
0.248
970683AG2-441 GEN
Solar/Wind Harmer
20.299
970681AG2-440 GEN
Solar/Wind Harmer
16.239
946301AF1-294 GEN
Solar/Wind Harmer
5.897
961791AG1-021 GEN
Solar/Wind Harmer
2.869
315657AE1-056 GEN
Solar/Wind Harmer
10.169
970285AG2-188 GEN
Solar/Wind Harmer
17.248
971845AH1-439 GEN
Solar/Wind Harmer
9.37
970831AG2-522 GEN
Solar/Wind Harmer
7.605
971447AH1-217 GEN
Solar/Wind Harmer
2.977
270494AE1-108_GEN
Solar/Wind Harmer
1.028
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.259
270455AD2-022 GEN
Solar/Wind Helper
1.376
270457AD2-023 GEN
Solar/Wind Helper
0.907
970413AG2-270 GEN
50/50
47.174
3144293JTRSVLE
50/50
1.009
3151591KERR 2
50/50
0.537
3151921BEARGRDN G2
50/50
1.071
3151261ROARAP2
50/50
0.076
24728405LEESVG
50/50
0.073
316248AF1-058 C
Solar/Wind Harmer
0.004
960061AF2-297 GEN
Solar/Wind Harmer
22.594
316478AD1-087 GEN
Solar/Wind Harmer
1.768
316486AD2-202 GEN
Solar/Wind Harmer
0.519
971683AH1-343 GEN
Solar/Wind Harmer
16.715
970909AG2-566 GEN
Solar/Wind Harmer
3.699
316131AB2-060 GEN
Solar/Wind Harmer
1.016
964241AG1-285 GEN
Solar/Wind Harmer
21.282
315785AD2-033 C
Solar/Wind Harmer
2.544
970257AG2-171 GEN
Solar/Wind Harmer
9.938
959311AF2-222 GEN
Solar/Wind Harmer
27.447
963181AG1-167 GEN
Solar/Wind Harmer
1.195
3147133PAMPLIN
Solar/Wind Harmer
0.925
971193AH1-056 GEN
Solar/Wind Harmer
17.953
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
3146926FARMVIL
Solar/Wind Harmer
0.163
3146776BUCKING
Solar/Wind Harmer
0.072
3147043LAWRENC
Solar/Wind Harmer
0.09
3147312GRETNA
Solar/Wind Harmer
0.021
941821AE2-187 GEN
Solar/Wind Harmer
3.437
970221AG2-151 GEN
Solar/Wind Harmer
5.518
313506AB2-031 GEN
Solar/Wind Harmer
0.21
316313AB2-026
Solar/Wind Harmer
0.037
316258AE1-075 C
Solar/Wind Harmer
0.044
316405AF2-144 C
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
0.876
316283AC2-100 C
Solar/Wind Helper
2.324
3152661PLYWOOD A
50/50
1.086
3144293JTRSVLE
50/50
1.009
3144293JTRSVLE
50/50
0.85
970535AG2-341 GEN
50/50
5.15
316222AC1-221 GEN
Solar/Wind Harmer
3.734
970099AG2-077 GEN
Solar/Wind Harmer
51.571
970933AG2-581 GEN
Solar/Wind Harmer
38.137
3146843MT LREL
Solar/Wind Harmer
0.444
3146843MT LREL
Solar/Wind Harmer
0.444
964791AG1-342 GEN
Solar/Wind Harmer
8.515
962561AG1-105 GEN
Solar/Wind Harmer
20.413
971741AH1-377 GEN
Solar/Wind Harmer
36.74
970301AG2-198 GEN
Solar/Wind Harmer
14.798
313527AB2-043 GEN
Solar/Wind Harmer
0.004
970323AG2-213 GEN
Solar/Wind Harmer
13.251
971775AH1-396 GEN
Solar/Wind Harmer
0.497
316034AC1-036 C
Solar/Wind Harmer
0.023
958211AF2-115 GEN
Solar/Wind Harmer
3.586
963191AG1-168 GEN
Solar/Wind Harmer
1.195
942751AE2-291 GEN
Solar/Wind Harmer
16.169
3147133PAMPLIN
Solar/Wind Harmer
0.295
3147133PAMPLIN
Solar/Wind Harmer
0.236
939181AE1-148 GEN
Solar/Wind Harmer
13.009
3146776BUCKING
Solar/Wind Harmer
0.802
3146776BUCKING
Solar/Wind Harmer
0.065
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
2.673
971489AH1-241 GEN
Solar/Wind Harmer
5.518
315821AE2-092 GEN
Solar/Wind Harmer
0.005
316181AB2-040 GEN
Solar/Wind Harmer
0.099
3145593CAROLNA
Solar/Wind Harmer
0.062
3145593CAROLNA
Solar/Wind Harmer
0.062
966811AG1-552 GEN
Solar/Wind Harmer
0.675
3145593CAROLNA
Solar/Wind Harmer
0.077
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.85
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.677
VTFLTFEXP_VFT->PJM
CMTX
1.127
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.809
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.962
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.429
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.343
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.375

Details for AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.05 %
Rating:903.34 MVA
Rating Type:B
MVA to Mitigate:921.89
MW Contribution:5.52
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
10.81
3144293JTRSVLE
50/50
1.009
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3147043LAWRENC
50/50
1.435
3151561HALLBR1
50/50
0.347
3151931BEARGRDN S1
50/50
1.382
3151911BEARGRDN G1
50/50
1.071
3151261ROARAP2
50/50
0.077
24728405LEESVG
50/50
0.073
315687AD1-152 GEN
Solar/Wind Harmer
0.019
316003AC1-222 GEN
Solar/Wind Harmer
0.013
3152661PLYWOOD A
50/50
1.086
3144293JTRSVLE
50/50
1.009
3144293JTRSVLE
50/50
0.85
970535AG2-341 GEN
50/50
5.15
316222AC1-221 GEN
Solar/Wind Harmer
3.734
970099AG2-077 GEN
Solar/Wind Harmer
51.571
3146843MT LREL
Solar/Wind Harmer
0.444
3146843MT LREL
Solar/Wind Harmer
0.444
964791AG1-342 GEN
Solar/Wind Harmer
8.515
962561AG1-105 GEN
Solar/Wind Harmer
20.413
971741AH1-377 GEN
Solar/Wind Harmer
36.74
970301AG2-198 GEN
Solar/Wind Harmer
14.798
313527AB2-043 GEN
Solar/Wind Harmer
0.004
970323AG2-213 GEN
Solar/Wind Harmer
13.251
971775AH1-396 GEN
Solar/Wind Harmer
0.497
316034AC1-036 C
Solar/Wind Harmer
0.023
958211AF2-115 GEN
Solar/Wind Harmer
3.586
963191AG1-168 GEN
Solar/Wind Harmer
1.195
942751AE2-291 GEN
Solar/Wind Harmer
16.169
3147133PAMPLIN
Solar/Wind Harmer
0.295
3147133PAMPLIN
Solar/Wind Harmer
0.236
939181AE1-148 GEN
Solar/Wind Harmer
13.009
3146776BUCKING
Solar/Wind Harmer
0.802
3146776BUCKING
Solar/Wind Harmer
0.065
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
2.673
971489AH1-241 GEN
Solar/Wind Harmer
5.518
315821AE2-092 GEN
Solar/Wind Harmer
0.005
316181AB2-040 GEN
Solar/Wind Harmer
0.099
3145593CAROLNA
Solar/Wind Harmer
0.062
3145593CAROLNA
Solar/Wind Harmer
0.062
966811AG1-552 GEN
Solar/Wind Harmer
0.675
957481AF2-042 GEN
Solar/Wind Harmer
128.928
315693AD1-088 GEN
Solar/Wind Harmer
21.573
962491AG1-098 GEN
Solar/Wind Harmer
25.346
970401AG2-262 GEN
Solar/Wind Harmer
2.602
316237AB2-079_GEN
Solar/Wind Harmer
0.003
970685AG2-442 GEN
Solar/Wind Harmer
22.735
963171AG1-166 GEN
Solar/Wind Harmer
1.594
971563AH1-280 GEN
Solar/Wind Harmer
3.188
3146926FARMVIL
Solar/Wind Harmer
0.163
971065AG2-659 GEN
Solar/Wind Harmer
8.623
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.08
316129AC1-054 GEN
Solar/Wind Harmer
0.717
3147123OTTER R
Solar/Wind Harmer
0.087
972003AH1-546 GEN
Solar/Wind Harmer
5.562
971795AH1-408 GEN
Solar/Wind Harmer
8.362
3147312GRETNA
Solar/Wind Harmer
0.086
3146802CHATHAM
Solar/Wind Harmer
0.08
941801AE2-185 GEN
Solar/Wind Harmer
3.437
971377AH1-170 GEN
Solar/Wind Harmer
1.104
3147623JAMES R
Solar/Wind Harmer
0.24
970937AG2-583 GEN
Solar/Wind Harmer
5.738
960081AF2-299 GEN
Solar/Wind Harmer
0.703
316336AC2-165 C
Solar/Wind Harmer
0.003
3143336POWHATN
Solar/Wind Harmer
1.031
3151541CLOVER2
50/50
10.758
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
972205AH1-687 GEN
50/50
5.223
3151281ROARAP4
50/50
0.075
3151281ROARAP4
50/50
0.07
3147173SINAI
Solar/Wind Harmer
0.529
3147243WELCO
Solar/Wind Harmer
0.331
316118AC1-105 GEN
Solar/Wind Harmer
1.258
970865AG2-541 GEN
Solar/Wind Harmer
14.488
316123AC1-075 GEN
Solar/Wind Harmer
0.47
970165AG2-112 GEN
Solar/Wind Harmer
2.789
970163AG2-111 GEN
Solar/Wind Harmer
2.661
316239AB2-077_GEN
Solar/Wind Harmer
0.003
316238AB2-078_GEN
Solar/Wind Harmer
0.003
971443AH1-215 GEN
Solar/Wind Harmer
5.225
3144303KENBRDG
Solar/Wind Harmer
0.248
970683AG2-441 GEN
Solar/Wind Harmer
20.299
970681AG2-440 GEN
Solar/Wind Harmer
16.239
946301AF1-294 GEN
Solar/Wind Harmer
5.897
961791AG1-021 GEN
Solar/Wind Harmer
2.869
315657AE1-056 GEN
Solar/Wind Harmer
10.169
970285AG2-188 GEN
Solar/Wind Harmer
17.248
971845AH1-439 GEN
Solar/Wind Harmer
9.37
970831AG2-522 GEN
Solar/Wind Harmer
7.605
971447AH1-217 GEN
Solar/Wind Harmer
2.977
270494AE1-108_GEN
Solar/Wind Harmer
1.028
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.259
270455AD2-022 GEN
Solar/Wind Helper
1.376
270457AD2-023 GEN
Solar/Wind Helper
0.907
970413AG2-270 GEN
50/50
47.174
3144293JTRSVLE
50/50
1.009
3151591KERR 2
50/50
0.537
3151921BEARGRDN G2
50/50
1.071
3151261ROARAP2
50/50
0.076
24728405LEESVG
50/50
0.073
316248AF1-058 C
Solar/Wind Harmer
0.004
960061AF2-297 GEN
Solar/Wind Harmer
22.594
316478AD1-087 GEN
Solar/Wind Harmer
1.768
316486AD2-202 GEN
Solar/Wind Harmer
0.519
971683AH1-343 GEN
Solar/Wind Harmer
16.715
970909AG2-566 GEN
Solar/Wind Harmer
3.699
316131AB2-060 GEN
Solar/Wind Harmer
1.016
964241AG1-285 GEN
Solar/Wind Harmer
21.282
315785AD2-033 C
Solar/Wind Harmer
2.544
970257AG2-171 GEN
Solar/Wind Harmer
9.938
959311AF2-222 GEN
Solar/Wind Harmer
27.447
963181AG1-167 GEN
Solar/Wind Harmer
1.195
3147133PAMPLIN
Solar/Wind Harmer
0.925
971193AH1-056 GEN
Solar/Wind Harmer
17.953
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
3146926FARMVIL
Solar/Wind Harmer
0.163
3146776BUCKING
Solar/Wind Harmer
0.072
3147043LAWRENC
Solar/Wind Harmer
0.09
3147312GRETNA
Solar/Wind Harmer
0.021
941821AE2-187 GEN
Solar/Wind Harmer
3.437
970221AG2-151 GEN
Solar/Wind Harmer
5.518
313506AB2-031 GEN
Solar/Wind Harmer
0.21
316313AB2-026
Solar/Wind Harmer
0.037
316258AE1-075 C
Solar/Wind Harmer
0.044
316405AF2-144 C
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
0.876
316283AC2-100 C
Solar/Wind Helper
2.324
3145593CAROLNA
Solar/Wind Harmer
0.077
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.85
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.677
VTFLTFEXP_VFT->PJM
CMTX
1.127
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.809
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.962
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.429
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.343
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.375

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:239.46 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1295.46
MW Contribution:7.25
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
10.804
3144293JTRSVLE
50/50
1.008
3151601KERR 3
50/50
0.536
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.432
3151561HALLBR1
50/50
0.347
3151931BEARGRDN S1
50/50
1.379
3151911BEARGRDN G1
50/50
1.068
315687AD1-152 GEN
Solar/Wind Harmer
7.75
316003AC1-222 GEN
Solar/Wind Harmer
5.363
957481AF2-042 GEN
Solar/Wind Harmer
169.654
315693AD1-088 GEN
Solar/Wind Harmer
25.233
962491AG1-098 GEN
Solar/Wind Harmer
33.35
970401AG2-262 GEN
Solar/Wind Harmer
3.25
316237AB2-079_GEN
Solar/Wind Harmer
1.107
970685AG2-442 GEN
Solar/Wind Harmer
29.906
963171AG1-166 GEN
Solar/Wind Harmer
4.193
971563AH1-280 GEN
Solar/Wind Harmer
4.193
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.337
316322AB2-045
Solar/Wind Harmer
0.757
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.874
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.319
971795AH1-408 GEN
Solar/Wind Harmer
10.545
3147312GRETNA
Solar/Wind Harmer
-0.01
3151541CLOVER2
50/50
10.752
3151611KERR 4
50/50
0.536
3151621KERR 5
50/50
0.536
3151631KERR 6
50/50
0.536
3151641KERR 7
50/50
0.536
972205AH1-687 GEN
50/50
5.21
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.763
971967AH1-528 GEN
Solar/Wind Harmer
100.637
970865AG2-541 GEN
Solar/Wind Harmer
19.063
316123AC1-075 GEN
Solar/Wind Harmer
4.167
970165AG2-112 GEN
Solar/Wind Harmer
3.669
970163AG2-111 GEN
Solar/Wind Harmer
3.5
316239AB2-077_GEN
Solar/Wind Harmer
1.107
316238AB2-078_GEN
Solar/Wind Harmer
1.107
971443AH1-215 GEN
Solar/Wind Harmer
6.874
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.701
970681AG2-440 GEN
Solar/Wind Harmer
21.361
946301AF1-294 GEN
Solar/Wind Harmer
8.596
961791AG1-021 GEN
Solar/Wind Harmer
4.193
315657AE1-056 GEN
Solar/Wind Harmer
12.411
970285AG2-188 GEN
Solar/Wind Harmer
21.406
971845AH1-439 GEN
Solar/Wind Harmer
12.319
970831AG2-522 GEN
Solar/Wind Harmer
9.997
971447AH1-217 GEN
Solar/Wind Harmer
3.908
270494AE1-108_GEN
Solar/Wind Harmer
2.497
946281AF1-292 GEN
Solar/Wind Harmer
0.183
316087AB2-174 GEN
Solar/Wind Harmer
1.111
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.379
270457AD2-023 GEN
Solar/Wind Helper
0.909
970413AG2-270 GEN
50/50
47.147
3144293JTRSVLE
50/50
1.008
3151591KERR 2
50/50
0.536
3151921BEARGRDN G2
50/50
1.068
316283AC2-100 C
Solar/Wind Harmer
9.573
316248AF1-058 C
Solar/Wind Harmer
1.792
960061AF2-297 GEN
Solar/Wind Harmer
29.732
316478AD1-087 GEN
Solar/Wind Harmer
4.927
316486AD2-202 GEN
Solar/Wind Harmer
1.443
971683AH1-343 GEN
Solar/Wind Harmer
21.994
970909AG2-566 GEN
Solar/Wind Harmer
3.696
316131AB2-060 GEN
Solar/Wind Harmer
3.914
964241AG1-285 GEN
Solar/Wind Harmer
27.996
315785AD2-033 C
Solar/Wind Harmer
7.961
970257AG2-171 GEN
Solar/Wind Harmer
13.073
959311AF2-222 GEN
Solar/Wind Harmer
36.177
963181AG1-167 GEN
Solar/Wind Harmer
3.145
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.685
942461AE2-259 GEN
Solar/Wind Harmer
4.783
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.513
970221AG2-151 GEN
Solar/Wind Harmer
7.245
966621AG1-532 GEN
Solar/Wind Harmer
0.166
313506AB2-031 GEN
Solar/Wind Harmer
0.612
316313AB2-026
Solar/Wind Harmer
0.175
316258AE1-075 C
Solar/Wind Harmer
0.157
3152661PLYWOOD A
50/50
1.085
3144293JTRSVLE
50/50
1.008
3144293JTRSVLE
50/50
0.849
970535AG2-341 GEN
50/50
5.145
316222AC1-221 GEN
Solar/Wind Harmer
10.226
970099AG2-077 GEN
Solar/Wind Harmer
67.861
970933AG2-581 GEN
Solar/Wind Harmer
50.184
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.637
962561AG1-105 GEN
Solar/Wind Harmer
26.859
971741AH1-377 GEN
Solar/Wind Harmer
48.337
970301AG2-198 GEN
Solar/Wind Harmer
19.467
313527AB2-043 GEN
Solar/Wind Harmer
5.909
970323AG2-213 GEN
Solar/Wind Harmer
17.431
971775AH1-396 GEN
Solar/Wind Harmer
2.482
316034AC1-036 C
Solar/Wind Harmer
0.646
958211AF2-115 GEN
Solar/Wind Harmer
5.241
963191AG1-168 GEN
Solar/Wind Harmer
3.145
942751AE2-291 GEN
Solar/Wind Harmer
21.269
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.11
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.953
316197AC1-042 GEN
Solar/Wind Harmer
1.481
942671AE2-283 GEN
Solar/Wind Harmer
3.987
971489AH1-241 GEN
Solar/Wind Harmer
6.878
315821AE2-092 GEN
Solar/Wind Harmer
1.789
316181AB2-040 GEN
Solar/Wind Harmer
1.061
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.783
3145593CAROLNA
Solar/Wind Harmer
0.058
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.513
971377AH1-170 GEN
Solar/Wind Harmer
1.449
3147623JAMES R
Solar/Wind Harmer
0.179
970937AG2-583 GEN
Solar/Wind Harmer
7.531
960081AF2-299 GEN
Solar/Wind Harmer
0.921
316336AC2-165 C
Solar/Wind Harmer
1.321
3143336POWHATN
Solar/Wind Harmer
0.769
316405AF2-144 C
Solar/Wind Harmer
0.166
3143336POWHATN
Solar/Wind Harmer
0.654
270018AE2-047 C O1
Solar/Wind Helper
0.395
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.864
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.722
VTFLTFEXP_VFT->PJM
CMTX
0.961
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.818
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.028
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.368
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.218
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.39

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:234.05 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1266.23
MW Contribution:7.26
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
10.784
3144293JTRSVLE
50/50
1.007
3151601KERR 3
50/50
0.534
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.431
3151561HALLBR1
50/50
0.345
3151931BEARGRDN S1
50/50
1.382
3151911BEARGRDN G1
50/50
1.071
315687AD1-152 GEN
Solar/Wind Harmer
7.735
316003AC1-222 GEN
Solar/Wind Harmer
5.352
957481AF2-042 GEN
Solar/Wind Harmer
169.338
315693AD1-088 GEN
Solar/Wind Harmer
25.187
962491AG1-098 GEN
Solar/Wind Harmer
33.29
3151541CLOVER2
50/50
10.732
3151611KERR 4
50/50
0.534
3151621KERR 5
50/50
0.534
3151631KERR 6
50/50
0.534
3151641KERR 7
50/50
0.534
972205AH1-687 GEN
50/50
5.224
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.755
971967AH1-528 GEN
Solar/Wind Harmer
100.451
970865AG2-541 GEN
Solar/Wind Harmer
19.018
316123AC1-075 GEN
Solar/Wind Harmer
4.156
970165AG2-112 GEN
Solar/Wind Harmer
3.66
970163AG2-111 GEN
Solar/Wind Harmer
3.491
316239AB2-077_GEN
Solar/Wind Harmer
1.104
316238AB2-078_GEN
Solar/Wind Harmer
1.104
971443AH1-215 GEN
Solar/Wind Harmer
6.861
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.656
970681AG2-440 GEN
Solar/Wind Harmer
21.325
946301AF1-294 GEN
Solar/Wind Harmer
8.582
961791AG1-021 GEN
Solar/Wind Harmer
4.186
315657AE1-056 GEN
Solar/Wind Harmer
12.392
970285AG2-188 GEN
Solar/Wind Harmer
21.4
971845AH1-439 GEN
Solar/Wind Harmer
12.318
970831AG2-522 GEN
Solar/Wind Harmer
9.968
971447AH1-217 GEN
Solar/Wind Harmer
3.919
270494AE1-108_GEN
Solar/Wind Harmer
2.5
946281AF1-292 GEN
Solar/Wind Harmer
0.184
316087AB2-174 GEN
Solar/Wind Harmer
1.112
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.399
270457AD2-023 GEN
Solar/Wind Helper
0.922
970413AG2-270 GEN
50/50
47.058
3144293JTRSVLE
50/50
1.007
3151591KERR 2
50/50
0.534
3151921BEARGRDN G2
50/50
1.071
316283AC2-100 C
Solar/Wind Harmer
9.554
316248AF1-058 C
Solar/Wind Harmer
1.788
960061AF2-297 GEN
Solar/Wind Harmer
29.671
316478AD1-087 GEN
Solar/Wind Harmer
4.917
316486AD2-202 GEN
Solar/Wind Harmer
1.44
971683AH1-343 GEN
Solar/Wind Harmer
21.945
970909AG2-566 GEN
Solar/Wind Harmer
3.691
316131AB2-060 GEN
Solar/Wind Harmer
3.906
964241AG1-285 GEN
Solar/Wind Harmer
27.94
315785AD2-033 C
Solar/Wind Harmer
7.947
970257AG2-171 GEN
Solar/Wind Harmer
13.049
959311AF2-222 GEN
Solar/Wind Harmer
36.112
963181AG1-167 GEN
Solar/Wind Harmer
3.14
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.654
942461AE2-259 GEN
Solar/Wind Harmer
4.777
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.485
970221AG2-151 GEN
Solar/Wind Harmer
7.264
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.612
316313AB2-026
Solar/Wind Harmer
0.177
316258AE1-075 C
Solar/Wind Harmer
0.16
316405AF2-144 C
Solar/Wind Harmer
0.168
3143336POWHATN
Solar/Wind Harmer
0.663
270018AE2-047 C O1
Solar/Wind Helper
0.402
3152661PLYWOOD A
50/50
1.083
3144293JTRSVLE
50/50
1.007
3144293JTRSVLE
50/50
0.848
970535AG2-341 GEN
50/50
5.132
316222AC1-221 GEN
Solar/Wind Harmer
10.206
970099AG2-077 GEN
Solar/Wind Harmer
67.735
970933AG2-581 GEN
Solar/Wind Harmer
50.091
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.615
962561AG1-105 GEN
Solar/Wind Harmer
26.803
971741AH1-377 GEN
Solar/Wind Harmer
48.264
970301AG2-198 GEN
Solar/Wind Harmer
19.44
313527AB2-043 GEN
Solar/Wind Harmer
5.897
970323AG2-213 GEN
Solar/Wind Harmer
17.399
971775AH1-396 GEN
Solar/Wind Harmer
2.478
316034AC1-036 C
Solar/Wind Harmer
0.645
958211AF2-115 GEN
Solar/Wind Harmer
5.233
963191AG1-168 GEN
Solar/Wind Harmer
3.14
942751AE2-291 GEN
Solar/Wind Harmer
21.208
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.061
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.941
316197AC1-042 GEN
Solar/Wind Harmer
1.472
942671AE2-283 GEN
Solar/Wind Harmer
3.962
971489AH1-241 GEN
Solar/Wind Harmer
6.896
315821AE2-092 GEN
Solar/Wind Harmer
1.796
316181AB2-040 GEN
Solar/Wind Harmer
1.062
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.781
3145593CAROLNA
Solar/Wind Harmer
0.058
970401AG2-262 GEN
Solar/Wind Harmer
3.243
316237AB2-079_GEN
Solar/Wind Harmer
1.104
970685AG2-442 GEN
Solar/Wind Harmer
29.855
963171AG1-166 GEN
Solar/Wind Harmer
4.186
971563AH1-280 GEN
Solar/Wind Harmer
4.186
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.304
316322AB2-045
Solar/Wind Harmer
0.757
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.869
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.333
971795AH1-408 GEN
Solar/Wind Harmer
10.544
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.485
971377AH1-170 GEN
Solar/Wind Harmer
1.453
3147623JAMES R
Solar/Wind Harmer
0.18
970937AG2-583 GEN
Solar/Wind Harmer
7.571
960081AF2-299 GEN
Solar/Wind Harmer
0.923
316336AC2-165 C
Solar/Wind Harmer
1.335
3143336POWHATN
Solar/Wind Harmer
0.78
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.883
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.782
VTFLTFEXP_VFT->PJM
CMTX
1.209
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.866
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.147
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.461
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.38
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.491

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:234.0 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1265.96
MW Contribution:7.26
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.732
3151611KERR 4
50/50
0.534
3151621KERR 5
50/50
0.534
3151631KERR 6
50/50
0.534
3151641KERR 7
50/50
0.534
972205AH1-687 GEN
50/50
5.224
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.755
971967AH1-528 GEN
Solar/Wind Harmer
100.451
970865AG2-541 GEN
Solar/Wind Harmer
19.018
316123AC1-075 GEN
Solar/Wind Harmer
4.156
970165AG2-112 GEN
Solar/Wind Harmer
3.66
970163AG2-111 GEN
Solar/Wind Harmer
3.491
316239AB2-077_GEN
Solar/Wind Harmer
1.104
316238AB2-078_GEN
Solar/Wind Harmer
1.104
971443AH1-215 GEN
Solar/Wind Harmer
6.861
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.656
970681AG2-440 GEN
Solar/Wind Harmer
21.325
946301AF1-294 GEN
Solar/Wind Harmer
8.582
961791AG1-021 GEN
Solar/Wind Harmer
4.186
315657AE1-056 GEN
Solar/Wind Harmer
12.392
970285AG2-188 GEN
Solar/Wind Harmer
21.4
971845AH1-439 GEN
Solar/Wind Harmer
12.318
970831AG2-522 GEN
Solar/Wind Harmer
9.968
971447AH1-217 GEN
Solar/Wind Harmer
3.919
270494AE1-108_GEN
Solar/Wind Harmer
2.5
946281AF1-292 GEN
Solar/Wind Harmer
0.184
316087AB2-174 GEN
Solar/Wind Harmer
1.112
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.399
270457AD2-023 GEN
Solar/Wind Helper
0.922
3152661PLYWOOD A
50/50
1.083
3144293JTRSVLE
50/50
1.007
3144293JTRSVLE
50/50
0.848
970535AG2-341 GEN
50/50
5.132
316222AC1-221 GEN
Solar/Wind Harmer
10.206
970099AG2-077 GEN
Solar/Wind Harmer
67.735
970933AG2-581 GEN
Solar/Wind Harmer
50.091
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.615
962561AG1-105 GEN
Solar/Wind Harmer
26.803
971741AH1-377 GEN
Solar/Wind Harmer
48.264
970301AG2-198 GEN
Solar/Wind Harmer
19.44
313527AB2-043 GEN
Solar/Wind Harmer
5.897
970323AG2-213 GEN
Solar/Wind Harmer
17.399
971775AH1-396 GEN
Solar/Wind Harmer
2.478
316034AC1-036 C
Solar/Wind Harmer
0.645
958211AF2-115 GEN
Solar/Wind Harmer
5.233
963191AG1-168 GEN
Solar/Wind Harmer
3.14
942751AE2-291 GEN
Solar/Wind Harmer
21.208
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.061
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.941
316197AC1-042 GEN
Solar/Wind Harmer
1.472
942671AE2-283 GEN
Solar/Wind Harmer
3.962
971489AH1-241 GEN
Solar/Wind Harmer
6.896
315821AE2-092 GEN
Solar/Wind Harmer
1.796
316181AB2-040 GEN
Solar/Wind Harmer
1.062
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.781
3145593CAROLNA
Solar/Wind Harmer
0.058
3151531CLOVER1
50/50
10.784
3144293JTRSVLE
50/50
1.007
3151601KERR 3
50/50
0.534
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.431
3151561HALLBR1
50/50
0.345
3151931BEARGRDN S1
50/50
1.382
3151911BEARGRDN G1
50/50
1.071
315687AD1-152 GEN
Solar/Wind Harmer
7.735
316003AC1-222 GEN
Solar/Wind Harmer
5.352
957481AF2-042 GEN
Solar/Wind Harmer
169.338
315693AD1-088 GEN
Solar/Wind Harmer
25.187
962491AG1-098 GEN
Solar/Wind Harmer
33.29
970401AG2-262 GEN
Solar/Wind Harmer
3.243
316237AB2-079_GEN
Solar/Wind Harmer
1.104
970685AG2-442 GEN
Solar/Wind Harmer
29.855
963171AG1-166 GEN
Solar/Wind Harmer
4.186
971563AH1-280 GEN
Solar/Wind Harmer
4.186
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.304
316322AB2-045
Solar/Wind Harmer
0.757
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.869
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.333
971795AH1-408 GEN
Solar/Wind Harmer
10.544
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.485
971377AH1-170 GEN
Solar/Wind Harmer
1.453
3147623JAMES R
Solar/Wind Harmer
0.18
970937AG2-583 GEN
Solar/Wind Harmer
7.571
960081AF2-299 GEN
Solar/Wind Harmer
0.923
316336AC2-165 C
Solar/Wind Harmer
1.335
3143336POWHATN
Solar/Wind Harmer
0.78
970413AG2-270 GEN
50/50
47.058
3144293JTRSVLE
50/50
1.007
3151591KERR 2
50/50
0.534
3151921BEARGRDN G2
50/50
1.071
316283AC2-100 C
Solar/Wind Harmer
9.554
316248AF1-058 C
Solar/Wind Harmer
1.788
960061AF2-297 GEN
Solar/Wind Harmer
29.671
316478AD1-087 GEN
Solar/Wind Harmer
4.917
316486AD2-202 GEN
Solar/Wind Harmer
1.44
971683AH1-343 GEN
Solar/Wind Harmer
21.945
970909AG2-566 GEN
Solar/Wind Harmer
3.691
316131AB2-060 GEN
Solar/Wind Harmer
3.906
964241AG1-285 GEN
Solar/Wind Harmer
27.94
315785AD2-033 C
Solar/Wind Harmer
7.947
970257AG2-171 GEN
Solar/Wind Harmer
13.049
959311AF2-222 GEN
Solar/Wind Harmer
36.112
963181AG1-167 GEN
Solar/Wind Harmer
3.14
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.654
942461AE2-259 GEN
Solar/Wind Harmer
4.777
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.485
970221AG2-151 GEN
Solar/Wind Harmer
7.264
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.612
316313AB2-026
Solar/Wind Harmer
0.177
316258AE1-075 C
Solar/Wind Harmer
0.16
316405AF2-144 C
Solar/Wind Harmer
0.168
3143336POWHATN
Solar/Wind Harmer
0.663
270018AE2-047 C O1
Solar/Wind Helper
0.402
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.883
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.782
VTFLTFEXP_VFT->PJM
CMTX
1.209
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.866
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.147
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.461
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.38
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.491

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X1_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:231.01 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1249.79
MW Contribution:7.15
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
10.906
3144293JTRSVLE
50/50
1.002
3151601KERR 3
50/50
0.535
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.43
3151561HALLBR1
50/50
0.348
3151931BEARGRDN S1
50/50
1.361
3151911BEARGRDN G1
50/50
1.054
315687AD1-152 GEN
Solar/Wind Harmer
7.801
957481AF2-042 GEN
Solar/Wind Harmer
172.797
316003AC1-222 GEN
Solar/Wind Harmer
5.383
970401AG2-262 GEN
Solar/Wind Harmer
3.256
315693AD1-088 GEN
Solar/Wind Harmer
24.857
962491AG1-098 GEN
Solar/Wind Harmer
32.854
316237AB2-079_GEN
Solar/Wind Harmer
1.105
970685AG2-442 GEN
Solar/Wind Harmer
29.741
963171AG1-166 GEN
Solar/Wind Harmer
4.165
971563AH1-280 GEN
Solar/Wind Harmer
4.165
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.312
316322AB2-045
Solar/Wind Harmer
0.748
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.87
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.224
971795AH1-408 GEN
Solar/Wind Harmer
10.527
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.536
971377AH1-170 GEN
Solar/Wind Harmer
1.43
3147623JAMES R
Solar/Wind Harmer
0.177
970937AG2-583 GEN
Solar/Wind Harmer
7.432
960081AF2-299 GEN
Solar/Wind Harmer
0.92
316336AC2-165 C
Solar/Wind Harmer
1.303
3143336POWHATN
Solar/Wind Harmer
0.759
970413AG2-270 GEN
50/50
47.591
3144293JTRSVLE
50/50
1.002
3151591KERR 2
50/50
0.535
3151921BEARGRDN G2
50/50
1.054
316283AC2-100 C
Solar/Wind Harmer
9.587
316248AF1-058 C
Solar/Wind Harmer
1.798
960061AF2-297 GEN
Solar/Wind Harmer
29.84
316478AD1-087 GEN
Solar/Wind Harmer
4.973
316486AD2-202 GEN
Solar/Wind Harmer
1.456
971683AH1-343 GEN
Solar/Wind Harmer
22.075
970909AG2-566 GEN
Solar/Wind Harmer
3.645
316131AB2-060 GEN
Solar/Wind Harmer
3.906
964241AG1-285 GEN
Solar/Wind Harmer
27.919
315785AD2-033 C
Solar/Wind Harmer
7.93
970257AG2-171 GEN
Solar/Wind Harmer
13.016
959311AF2-222 GEN
Solar/Wind Harmer
36.008
963181AG1-167 GEN
Solar/Wind Harmer
3.124
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.53
942461AE2-259 GEN
Solar/Wind Harmer
4.736
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.536
970221AG2-151 GEN
Solar/Wind Harmer
7.152
966621AG1-532 GEN
Solar/Wind Harmer
0.166
313506AB2-031 GEN
Solar/Wind Harmer
0.611
316313AB2-026
Solar/Wind Harmer
0.172
316258AE1-075 C
Solar/Wind Harmer
0.155
316405AF2-144 C
Solar/Wind Harmer
0.164
3143336POWHATN
Solar/Wind Harmer
0.645
3151541CLOVER2
50/50
10.854
3151611KERR 4
50/50
0.535
3151621KERR 5
50/50
0.535
3151631KERR 6
50/50
0.535
3151641KERR 7
50/50
0.535
972205AH1-687 GEN
50/50
5.142
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.773
970865AG2-541 GEN
Solar/Wind Harmer
19.134
316123AC1-075 GEN
Solar/Wind Harmer
4.183
970165AG2-112 GEN
Solar/Wind Harmer
3.683
970163AG2-111 GEN
Solar/Wind Harmer
3.514
316239AB2-077_GEN
Solar/Wind Harmer
1.105
316238AB2-078_GEN
Solar/Wind Harmer
1.105
971443AH1-215 GEN
Solar/Wind Harmer
6.844
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.554
970681AG2-440 GEN
Solar/Wind Harmer
21.243
946301AF1-294 GEN
Solar/Wind Harmer
8.538
961791AG1-021 GEN
Solar/Wind Harmer
4.165
315657AE1-056 GEN
Solar/Wind Harmer
12.318
970285AG2-188 GEN
Solar/Wind Harmer
21.128
971845AH1-439 GEN
Solar/Wind Harmer
12.16
970831AG2-522 GEN
Solar/Wind Harmer
9.974
971447AH1-217 GEN
Solar/Wind Harmer
3.858
270494AE1-108_GEN
Solar/Wind Harmer
2.469
946281AF1-292 GEN
Solar/Wind Harmer
0.183
316087AB2-174 GEN
Solar/Wind Harmer
1.109
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.37
270457AD2-023 GEN
Solar/Wind Helper
0.903
3152661PLYWOOD A
50/50
1.089
3144293JTRSVLE
50/50
1.002
3144293JTRSVLE
50/50
0.844
970535AG2-341 GEN
50/50
5.134
316222AC1-221 GEN
Solar/Wind Harmer
10.241
970099AG2-077 GEN
Solar/Wind Harmer
69.119
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.658
962561AG1-105 GEN
Solar/Wind Harmer
26.899
971741AH1-377 GEN
Solar/Wind Harmer
47.648
970301AG2-198 GEN
Solar/Wind Harmer
19.194
313527AB2-043 GEN
Solar/Wind Harmer
5.898
970323AG2-213 GEN
Solar/Wind Harmer
17.355
971775AH1-396 GEN
Solar/Wind Harmer
2.471
316034AC1-036 C
Solar/Wind Harmer
0.643
942751AE2-291 GEN
Solar/Wind Harmer
21.352
958211AF2-115 GEN
Solar/Wind Harmer
5.206
963191AG1-168 GEN
Solar/Wind Harmer
3.124
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.072
3146776BUCKING
Solar/Wind Harmer
-0.088
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.963
316197AC1-042 GEN
Solar/Wind Harmer
1.488
942671AE2-283 GEN
Solar/Wind Harmer
4.007
971489AH1-241 GEN
Solar/Wind Harmer
6.79
315821AE2-092 GEN
Solar/Wind Harmer
1.766
316181AB2-040 GEN
Solar/Wind Harmer
1.06
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.781
3145593CAROLNA
Solar/Wind Harmer
0.058
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.859
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.707
VTFLTFEXP_VFT->PJM
CMTX
0.905
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.807
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.999
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.347
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.181
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.368

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X2_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:231.0 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1249.74
MW Contribution:7.15
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.853
3151611KERR 4
50/50
0.535
3151621KERR 5
50/50
0.535
3151631KERR 6
50/50
0.535
3151641KERR 7
50/50
0.535
972205AH1-687 GEN
50/50
5.143
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.773
970865AG2-541 GEN
Solar/Wind Harmer
19.133
316123AC1-075 GEN
Solar/Wind Harmer
4.183
970165AG2-112 GEN
Solar/Wind Harmer
3.683
970163AG2-111 GEN
Solar/Wind Harmer
3.514
316239AB2-077_GEN
Solar/Wind Harmer
1.105
316238AB2-078_GEN
Solar/Wind Harmer
1.105
971443AH1-215 GEN
Solar/Wind Harmer
6.845
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.555
970681AG2-440 GEN
Solar/Wind Harmer
21.244
946301AF1-294 GEN
Solar/Wind Harmer
8.539
961791AG1-021 GEN
Solar/Wind Harmer
4.165
315657AE1-056 GEN
Solar/Wind Harmer
12.319
970285AG2-188 GEN
Solar/Wind Harmer
21.13
971845AH1-439 GEN
Solar/Wind Harmer
12.161
970831AG2-522 GEN
Solar/Wind Harmer
9.975
971447AH1-217 GEN
Solar/Wind Harmer
3.858
270494AE1-108_GEN
Solar/Wind Harmer
2.469
946281AF1-292 GEN
Solar/Wind Harmer
0.183
316087AB2-174 GEN
Solar/Wind Harmer
1.109
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.37
270457AD2-023 GEN
Solar/Wind Helper
0.903
970413AG2-270 GEN
50/50
47.588
3144293JTRSVLE
50/50
1.002
3151591KERR 2
50/50
0.535
3151921BEARGRDN G2
50/50
1.054
316283AC2-100 C
Solar/Wind Harmer
9.586
316248AF1-058 C
Solar/Wind Harmer
1.798
960061AF2-297 GEN
Solar/Wind Harmer
29.84
316478AD1-087 GEN
Solar/Wind Harmer
4.972
316486AD2-202 GEN
Solar/Wind Harmer
1.456
971683AH1-343 GEN
Solar/Wind Harmer
22.075
970909AG2-566 GEN
Solar/Wind Harmer
3.645
316131AB2-060 GEN
Solar/Wind Harmer
3.906
964241AG1-285 GEN
Solar/Wind Harmer
27.92
315785AD2-033 C
Solar/Wind Harmer
7.931
970257AG2-171 GEN
Solar/Wind Harmer
13.017
959311AF2-222 GEN
Solar/Wind Harmer
36.009
963181AG1-167 GEN
Solar/Wind Harmer
3.124
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.531
942461AE2-259 GEN
Solar/Wind Harmer
4.736
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.536
970221AG2-151 GEN
Solar/Wind Harmer
7.153
966621AG1-532 GEN
Solar/Wind Harmer
0.166
313506AB2-031 GEN
Solar/Wind Harmer
0.611
316313AB2-026
Solar/Wind Harmer
0.173
316258AE1-075 C
Solar/Wind Harmer
0.155
316405AF2-144 C
Solar/Wind Harmer
0.164
3143336POWHATN
Solar/Wind Harmer
0.645
3152661PLYWOOD A
50/50
1.089
3144293JTRSVLE
50/50
1.002
3144293JTRSVLE
50/50
0.844
970535AG2-341 GEN
50/50
5.134
316222AC1-221 GEN
Solar/Wind Harmer
10.241
970099AG2-077 GEN
Solar/Wind Harmer
69.109
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.657
962561AG1-105 GEN
Solar/Wind Harmer
26.899
971741AH1-377 GEN
Solar/Wind Harmer
47.653
970301AG2-198 GEN
Solar/Wind Harmer
19.197
313527AB2-043 GEN
Solar/Wind Harmer
5.898
970323AG2-213 GEN
Solar/Wind Harmer
17.355
971775AH1-396 GEN
Solar/Wind Harmer
2.471
316034AC1-036 C
Solar/Wind Harmer
0.644
942751AE2-291 GEN
Solar/Wind Harmer
21.351
958211AF2-115 GEN
Solar/Wind Harmer
5.207
963191AG1-168 GEN
Solar/Wind Harmer
3.124
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.072
3146776BUCKING
Solar/Wind Harmer
-0.088
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.963
316197AC1-042 GEN
Solar/Wind Harmer
1.488
942671AE2-283 GEN
Solar/Wind Harmer
4.007
971489AH1-241 GEN
Solar/Wind Harmer
6.79
315821AE2-092 GEN
Solar/Wind Harmer
1.766
316181AB2-040 GEN
Solar/Wind Harmer
1.06
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
3151531CLOVER1
50/50
10.905
3144293JTRSVLE
50/50
1.002
3151601KERR 3
50/50
0.535
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.43
3151561HALLBR1
50/50
0.348
3151931BEARGRDN S1
50/50
1.361
3151911BEARGRDN G1
50/50
1.054
315687AD1-152 GEN
Solar/Wind Harmer
7.801
957481AF2-042 GEN
Solar/Wind Harmer
172.774
316003AC1-222 GEN
Solar/Wind Harmer
5.383
970401AG2-262 GEN
Solar/Wind Harmer
3.256
315693AD1-088 GEN
Solar/Wind Harmer
24.86
962491AG1-098 GEN
Solar/Wind Harmer
32.858
316237AB2-079_GEN
Solar/Wind Harmer
1.105
970685AG2-442 GEN
Solar/Wind Harmer
29.742
963171AG1-166 GEN
Solar/Wind Harmer
4.165
971563AH1-280 GEN
Solar/Wind Harmer
4.165
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.312
316322AB2-045
Solar/Wind Harmer
0.748
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.87
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.224
971795AH1-408 GEN
Solar/Wind Harmer
10.527
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.536
971377AH1-170 GEN
Solar/Wind Harmer
1.431
3147623JAMES R
Solar/Wind Harmer
0.177
970937AG2-583 GEN
Solar/Wind Harmer
7.433
960081AF2-299 GEN
Solar/Wind Harmer
0.92
316336AC2-165 C
Solar/Wind Harmer
1.304
3143336POWHATN
Solar/Wind Harmer
0.759
966811AG1-552 GEN
Solar/Wind Harmer
0.781
3145593CAROLNA
Solar/Wind Harmer
0.058
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.859
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.707
VTFLTFEXP_VFT->PJM
CMTX
0.906
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.807
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.999
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.347
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.181
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.368

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:192.41 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:978.46
MW Contribution:5.5
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
1.085
3144293JTRSVLE
50/50
1.008
3144293JTRSVLE
50/50
0.849
970535AG2-341 GEN
50/50
5.145
316222AC1-221 GEN
Solar/Wind Harmer
3.733
970099AG2-077 GEN
Solar/Wind Harmer
51.54
970933AG2-581 GEN
Solar/Wind Harmer
38.114
3146843MT LREL
Solar/Wind Harmer
0.444
3146843MT LREL
Solar/Wind Harmer
0.444
964791AG1-342 GEN
Solar/Wind Harmer
8.51
962561AG1-105 GEN
Solar/Wind Harmer
20.399
971741AH1-377 GEN
Solar/Wind Harmer
36.712
970301AG2-198 GEN
Solar/Wind Harmer
14.785
313527AB2-043 GEN
Solar/Wind Harmer
0.004
970323AG2-213 GEN
Solar/Wind Harmer
13.238
971775AH1-396 GEN
Solar/Wind Harmer
0.496
316034AC1-036 C
Solar/Wind Harmer
0.023
958211AF2-115 GEN
Solar/Wind Harmer
3.583
963191AG1-168 GEN
Solar/Wind Harmer
1.194
942751AE2-291 GEN
Solar/Wind Harmer
16.154
3147133PAMPLIN
Solar/Wind Harmer
0.294
3147133PAMPLIN
Solar/Wind Harmer
0.235
939181AE1-148 GEN
Solar/Wind Harmer
12.995
3146776BUCKING
Solar/Wind Harmer
0.801
3146776BUCKING
Solar/Wind Harmer
0.065
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
2.666
971489AH1-241 GEN
Solar/Wind Harmer
5.502
315821AE2-092 GEN
Solar/Wind Harmer
0.005
316181AB2-040 GEN
Solar/Wind Harmer
0.098
3145593CAROLNA
Solar/Wind Harmer
0.062
3145593CAROLNA
Solar/Wind Harmer
0.062
966811AG1-552 GEN
Solar/Wind Harmer
0.671
3145593CAROLNA
Solar/Wind Harmer
0.077
3151531CLOVER1
50/50
10.804
3144293JTRSVLE
50/50
1.008
3151601KERR 3
50/50
0.536
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.432
3151561HALLBR1
50/50
0.347
3151931BEARGRDN S1
50/50
1.379
3151911BEARGRDN G1
50/50
1.068
3151261ROARAP2
50/50
0.077
24728405LEESVG
50/50
0.072
315687AD1-152 GEN
Solar/Wind Harmer
0.019
316003AC1-222 GEN
Solar/Wind Harmer
0.013
957481AF2-042 GEN
Solar/Wind Harmer
128.851
315693AD1-088 GEN
Solar/Wind Harmer
21.559
962491AG1-098 GEN
Solar/Wind Harmer
25.329
970401AG2-262 GEN
Solar/Wind Harmer
2.6
316237AB2-079_GEN
Solar/Wind Harmer
0.003
970685AG2-442 GEN
Solar/Wind Harmer
22.713
963171AG1-166 GEN
Solar/Wind Harmer
1.592
971563AH1-280 GEN
Solar/Wind Harmer
3.185
3146926FARMVIL
Solar/Wind Harmer
0.162
971065AG2-659 GEN
Solar/Wind Harmer
8.611
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.08
316129AC1-054 GEN
Solar/Wind Harmer
0.716
3147123OTTER R
Solar/Wind Harmer
0.087
972003AH1-546 GEN
Solar/Wind Harmer
5.549
971795AH1-408 GEN
Solar/Wind Harmer
8.343
3147312GRETNA
Solar/Wind Harmer
0.086
3146802CHATHAM
Solar/Wind Harmer
0.08
941801AE2-185 GEN
Solar/Wind Harmer
3.428
971377AH1-170 GEN
Solar/Wind Harmer
1.1
3147623JAMES R
Solar/Wind Harmer
0.239
970937AG2-583 GEN
Solar/Wind Harmer
5.72
960081AF2-299 GEN
Solar/Wind Harmer
0.7
316336AC2-165 C
Solar/Wind Harmer
0.003
3143336POWHATN
Solar/Wind Harmer
1.026
970413AG2-270 GEN
50/50
47.147
3144293JTRSVLE
50/50
1.008
3151591KERR 2
50/50
0.536
3151921BEARGRDN G2
50/50
1.068
3151261ROARAP2
50/50
0.075
24728405LEESVG
50/50
0.073
316283AC2-100 C
Solar/Wind Harmer
1.77
316248AF1-058 C
Solar/Wind Harmer
0.004
960061AF2-297 GEN
Solar/Wind Harmer
22.582
316478AD1-087 GEN
Solar/Wind Harmer
1.767
316486AD2-202 GEN
Solar/Wind Harmer
0.519
971683AH1-343 GEN
Solar/Wind Harmer
16.704
970909AG2-566 GEN
Solar/Wind Harmer
3.696
316131AB2-060 GEN
Solar/Wind Harmer
1.015
964241AG1-285 GEN
Solar/Wind Harmer
21.263
315785AD2-033 C
Solar/Wind Harmer
2.542
970257AG2-171 GEN
Solar/Wind Harmer
9.929
959311AF2-222 GEN
Solar/Wind Harmer
27.421
963181AG1-167 GEN
Solar/Wind Harmer
1.194
3147133PAMPLIN
Solar/Wind Harmer
0.924
971193AH1-056 GEN
Solar/Wind Harmer
17.935
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
3146926FARMVIL
Solar/Wind Harmer
0.162
3146776BUCKING
Solar/Wind Harmer
0.072
3147043LAWRENC
Solar/Wind Harmer
0.09
3147312GRETNA
Solar/Wind Harmer
0.021
941821AE2-187 GEN
Solar/Wind Harmer
3.428
970221AG2-151 GEN
Solar/Wind Harmer
5.502
313506AB2-031 GEN
Solar/Wind Harmer
0.209
316313AB2-026
Solar/Wind Harmer
0.036
316258AE1-075 C
Solar/Wind Harmer
0.044
316405AF2-144 C
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
0.872
270018AE2-047 C O1
Solar/Wind Helper
0.395
3151541CLOVER2
50/50
10.752
3151611KERR 4
50/50
0.536
3151621KERR 5
50/50
0.536
3151631KERR 6
50/50
0.536
3151641KERR 7
50/50
0.536
972205AH1-687 GEN
50/50
5.21
3151281ROARAP4
50/50
0.075
3151281ROARAP4
50/50
0.07
3147173SINAI
Solar/Wind Harmer
0.529
3147243WELCO
Solar/Wind Harmer
0.331
316118AC1-105 GEN
Solar/Wind Harmer
1.257
971967AH1-528 GEN
Solar/Wind Harmer
76.23
970865AG2-541 GEN
Solar/Wind Harmer
14.478
316123AC1-075 GEN
Solar/Wind Harmer
0.47
970165AG2-112 GEN
Solar/Wind Harmer
2.787
970163AG2-111 GEN
Solar/Wind Harmer
2.658
316239AB2-077_GEN
Solar/Wind Harmer
0.003
316238AB2-078_GEN
Solar/Wind Harmer
0.003
971443AH1-215 GEN
Solar/Wind Harmer
5.22
3144303KENBRDG
Solar/Wind Harmer
0.248
970683AG2-441 GEN
Solar/Wind Harmer
20.28
970681AG2-440 GEN
Solar/Wind Harmer
16.224
946301AF1-294 GEN
Solar/Wind Harmer
5.891
961791AG1-021 GEN
Solar/Wind Harmer
2.866
315657AE1-056 GEN
Solar/Wind Harmer
10.159
970285AG2-188 GEN
Solar/Wind Harmer
17.225
971845AH1-439 GEN
Solar/Wind Harmer
9.357
970831AG2-522 GEN
Solar/Wind Harmer
7.592
971447AH1-217 GEN
Solar/Wind Harmer
2.968
270494AE1-108_GEN
Solar/Wind Harmer
1.024
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.258
270455AD2-022 GEN
Solar/Wind Helper
1.379
270457AD2-023 GEN
Solar/Wind Helper
0.909
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.864
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.722
VTFLTFEXP_VFT->PJM
CMTX
0.961
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.818
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.028
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.368
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.218
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.39

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:189.13 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:961.81
MW Contribution:5.5
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
1.085
3144293JTRSVLE
50/50
1.008
3144293JTRSVLE
50/50
0.849
970535AG2-341 GEN
50/50
5.145
316222AC1-221 GEN
Solar/Wind Harmer
3.733
970099AG2-077 GEN
Solar/Wind Harmer
51.54
3146843MT LREL
Solar/Wind Harmer
0.444
3146843MT LREL
Solar/Wind Harmer
0.444
964791AG1-342 GEN
Solar/Wind Harmer
8.51
962561AG1-105 GEN
Solar/Wind Harmer
20.399
971741AH1-377 GEN
Solar/Wind Harmer
36.712
970301AG2-198 GEN
Solar/Wind Harmer
14.785
313527AB2-043 GEN
Solar/Wind Harmer
0.004
970323AG2-213 GEN
Solar/Wind Harmer
13.238
971775AH1-396 GEN
Solar/Wind Harmer
0.496
316034AC1-036 C
Solar/Wind Harmer
0.023
958211AF2-115 GEN
Solar/Wind Harmer
3.583
963191AG1-168 GEN
Solar/Wind Harmer
1.194
942751AE2-291 GEN
Solar/Wind Harmer
16.154
3147133PAMPLIN
Solar/Wind Harmer
0.294
3147133PAMPLIN
Solar/Wind Harmer
0.235
939181AE1-148 GEN
Solar/Wind Harmer
12.995
3146776BUCKING
Solar/Wind Harmer
0.801
3146776BUCKING
Solar/Wind Harmer
0.065
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
2.666
971489AH1-241 GEN
Solar/Wind Harmer
5.502
315821AE2-092 GEN
Solar/Wind Harmer
0.005
316181AB2-040 GEN
Solar/Wind Harmer
0.098
3145593CAROLNA
Solar/Wind Harmer
0.062
3145593CAROLNA
Solar/Wind Harmer
0.062
966811AG1-552 GEN
Solar/Wind Harmer
0.671
3145593CAROLNA
Solar/Wind Harmer
0.077
3151531CLOVER1
50/50
10.804
3144293JTRSVLE
50/50
1.008
3151601KERR 3
50/50
0.536
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.432
3151561HALLBR1
50/50
0.347
3151931BEARGRDN S1
50/50
1.379
3151911BEARGRDN G1
50/50
1.068
3151261ROARAP2
50/50
0.077
24728405LEESVG
50/50
0.072
315687AD1-152 GEN
Solar/Wind Harmer
0.019
316003AC1-222 GEN
Solar/Wind Harmer
0.013
957481AF2-042 GEN
Solar/Wind Harmer
128.851
315693AD1-088 GEN
Solar/Wind Harmer
21.559
962491AG1-098 GEN
Solar/Wind Harmer
25.329
970401AG2-262 GEN
Solar/Wind Harmer
2.6
316237AB2-079_GEN
Solar/Wind Harmer
0.003
970685AG2-442 GEN
Solar/Wind Harmer
22.713
963171AG1-166 GEN
Solar/Wind Harmer
1.592
971563AH1-280 GEN
Solar/Wind Harmer
3.185
3146926FARMVIL
Solar/Wind Harmer
0.162
971065AG2-659 GEN
Solar/Wind Harmer
8.611
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.08
316129AC1-054 GEN
Solar/Wind Harmer
0.716
3147123OTTER R
Solar/Wind Harmer
0.087
972003AH1-546 GEN
Solar/Wind Harmer
5.549
971795AH1-408 GEN
Solar/Wind Harmer
8.343
3147312GRETNA
Solar/Wind Harmer
0.086
3146802CHATHAM
Solar/Wind Harmer
0.08
941801AE2-185 GEN
Solar/Wind Harmer
3.428
971377AH1-170 GEN
Solar/Wind Harmer
1.1
3147623JAMES R
Solar/Wind Harmer
0.239
970937AG2-583 GEN
Solar/Wind Harmer
5.72
960081AF2-299 GEN
Solar/Wind Harmer
0.7
316336AC2-165 C
Solar/Wind Harmer
0.003
3143336POWHATN
Solar/Wind Harmer
1.026
970413AG2-270 GEN
50/50
47.147
3144293JTRSVLE
50/50
1.008
3151591KERR 2
50/50
0.536
3151921BEARGRDN G2
50/50
1.068
3151261ROARAP2
50/50
0.075
24728405LEESVG
50/50
0.073
316283AC2-100 C
Solar/Wind Harmer
1.77
316248AF1-058 C
Solar/Wind Harmer
0.004
960061AF2-297 GEN
Solar/Wind Harmer
22.582
316478AD1-087 GEN
Solar/Wind Harmer
1.767
316486AD2-202 GEN
Solar/Wind Harmer
0.519
971683AH1-343 GEN
Solar/Wind Harmer
16.704
970909AG2-566 GEN
Solar/Wind Harmer
3.696
316131AB2-060 GEN
Solar/Wind Harmer
1.015
964241AG1-285 GEN
Solar/Wind Harmer
21.263
315785AD2-033 C
Solar/Wind Harmer
2.542
970257AG2-171 GEN
Solar/Wind Harmer
9.929
959311AF2-222 GEN
Solar/Wind Harmer
27.421
963181AG1-167 GEN
Solar/Wind Harmer
1.194
3147133PAMPLIN
Solar/Wind Harmer
0.924
971193AH1-056 GEN
Solar/Wind Harmer
17.935
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
3146926FARMVIL
Solar/Wind Harmer
0.162
3146776BUCKING
Solar/Wind Harmer
0.072
3147043LAWRENC
Solar/Wind Harmer
0.09
3147312GRETNA
Solar/Wind Harmer
0.021
941821AE2-187 GEN
Solar/Wind Harmer
3.428
970221AG2-151 GEN
Solar/Wind Harmer
5.502
313506AB2-031 GEN
Solar/Wind Harmer
0.209
316313AB2-026
Solar/Wind Harmer
0.036
316258AE1-075 C
Solar/Wind Harmer
0.044
316405AF2-144 C
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
0.872
270018AE2-047 C O1
Solar/Wind Helper
0.395
3151541CLOVER2
50/50
10.752
3151611KERR 4
50/50
0.536
3151621KERR 5
50/50
0.536
3151631KERR 6
50/50
0.536
3151641KERR 7
50/50
0.536
972205AH1-687 GEN
50/50
5.21
3151281ROARAP4
50/50
0.075
3151281ROARAP4
50/50
0.07
3147173SINAI
Solar/Wind Harmer
0.529
3147243WELCO
Solar/Wind Harmer
0.331
316118AC1-105 GEN
Solar/Wind Harmer
1.257
970865AG2-541 GEN
Solar/Wind Harmer
14.478
316123AC1-075 GEN
Solar/Wind Harmer
0.47
970165AG2-112 GEN
Solar/Wind Harmer
2.787
970163AG2-111 GEN
Solar/Wind Harmer
2.658
316239AB2-077_GEN
Solar/Wind Harmer
0.003
316238AB2-078_GEN
Solar/Wind Harmer
0.003
971443AH1-215 GEN
Solar/Wind Harmer
5.22
3144303KENBRDG
Solar/Wind Harmer
0.248
970683AG2-441 GEN
Solar/Wind Harmer
20.28
970681AG2-440 GEN
Solar/Wind Harmer
16.224
946301AF1-294 GEN
Solar/Wind Harmer
5.891
961791AG1-021 GEN
Solar/Wind Harmer
2.866
315657AE1-056 GEN
Solar/Wind Harmer
10.159
970285AG2-188 GEN
Solar/Wind Harmer
17.225
971845AH1-439 GEN
Solar/Wind Harmer
9.357
970831AG2-522 GEN
Solar/Wind Harmer
7.592
971447AH1-217 GEN
Solar/Wind Harmer
2.968
270494AE1-108_GEN
Solar/Wind Harmer
1.024
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.258
270455AD2-022 GEN
Solar/Wind Helper
1.379
270457AD2-023 GEN
Solar/Wind Helper
0.909
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.864
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.722
VTFLTFEXP_VFT->PJM
CMTX
0.961
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.818
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.028
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.368
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.218
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.39

Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.59 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:1021.82
MW Contribution:23.29
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.272
3151611KERR 4
50/50
0.119
3151621KERR 5
50/50
0.119
3151631KERR 6
50/50
0.119
3151641KERR 7
50/50
0.119
971447AH1-217 GEN
Solar/Wind Harmer
12.405
971845AH1-439 GEN
Solar/Wind Harmer
16.776
970285AG2-188 GEN
Solar/Wind Harmer
28.087
270494AE1-108_GEN
Solar/Wind Harmer
4.136
315657AE1-056 GEN
Solar/Wind Harmer
6.8
946301AF1-294 GEN
Solar/Wind Harmer
3.603
961791AG1-021 GEN
Solar/Wind Harmer
1.753
970683AG2-441 GEN
Solar/Wind Harmer
10.781
970681AG2-440 GEN
Solar/Wind Harmer
8.625
3144303KENBRDG
Solar/Wind Harmer
0.112
971443AH1-215 GEN
Solar/Wind Harmer
2.312
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.152
316233AE1-074 FULL
Solar/Wind Helper
0.267
3151921BEARGRDN G2
50/50
4.566
3144293JTRSVLE
50/50
0.617
966251AG1-494 GEN
50/50
1.538
3151591KERR 2
50/50
0.119
970221AG2-151 GEN
Solar/Wind Harmer
23.288
3146776BUCKING
Solar/Wind Harmer
0.136
3146926FARMVIL
Solar/Wind Harmer
0.171
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
2.106
3147133PAMPLIN
Solar/Wind Harmer
0.619
971193AH1-056 GEN
Solar/Wind Harmer
12.006
963181AG1-167 GEN
Solar/Wind Harmer
0.73
959311AF2-222 GEN
Solar/Wind Harmer
12.97
958131AF2-107 GEN
Solar/Wind Harmer
4.134
970257AG2-171 GEN
Solar/Wind Harmer
4.465
315785AD2-033 C
Solar/Wind Harmer
1.063
964241AG1-285 GEN
Solar/Wind Harmer
7.162
316131AB2-060 GEN
Solar/Wind Harmer
0.293
316313AB2-026
Solar/Wind Helper
0.96
316258AE1-075 C
Solar/Wind Helper
0.863
316405AF2-144 C
Solar/Wind Helper
0.719
3144293JTRSVLE
50/50
0.617
3144293JTRSVLE
50/50
0.519
970535AG2-341 GEN
50/50
1.291
971489AH1-241 GEN
Solar/Wind Harmer
23.288
3146776BUCKING
Solar/Wind Harmer
1.511
3146776BUCKING
Solar/Wind Harmer
0.122
315821AE2-092 GEN
Solar/Wind Harmer
0.018
970301AG2-198 GEN
Solar/Wind Harmer
8.425
3147133PAMPLIN
Solar/Wind Harmer
0.197
3147133PAMPLIN
Solar/Wind Harmer
0.158
958211AF2-115 GEN
Solar/Wind Harmer
2.191
963191AG1-168 GEN
Solar/Wind Harmer
0.73
971741AH1-377 GEN
Solar/Wind Harmer
16.896
3151931BEARGRDN S1
50/50
5.893
3151911BEARGRDN G1
50/50
4.566
3144293JTRSVLE
50/50
0.617
3151601KERR 3
50/50
0.119
3151581KERR 1
50/50
0.042
316336AC2-165 C
Solar/Wind Harmer
0.029
970937AG2-583 GEN
Solar/Wind Harmer
37.457
972003AH1-546 GEN
Solar/Wind Harmer
19.992
971377AH1-170 GEN
Solar/Wind Harmer
4.658
3147623JAMES R
Solar/Wind Harmer
1.012
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.151
3146926FARMVIL
Solar/Wind Harmer
0.171
963171AG1-166 GEN
Solar/Wind Harmer
0.974
971563AH1-280 GEN
Solar/Wind Harmer
1.948
970685AG2-442 GEN
Solar/Wind Harmer
12.075
316237AB2-079_GEN
Solar/Wind Harmer
0.001
962491AG1-098 GEN
Solar/Wind Harmer
4.869
315693AD1-088 GEN
Solar/Wind Harmer
3.802
970401AG2-262 GEN
Solar/Wind Harmer
0.394
962751AG1-124 GEN
Solar/Wind Harmer
2.965
3143226MDLTHAN
Solar/Wind Helper
0.215
3143526WINTERP
Solar/Wind Helper
0.908
316034AC1-036 C
Solar/Wind Harmer
0.01
970323AG2-213 GEN
Solar/Wind Harmer
5.954
971775AH1-396 GEN
Solar/Wind Harmer
0.223
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.389
964791AG1-342 GEN
Solar/Wind Harmer
1.289
3146843MT LREL
Solar/Wind Harmer
0.067
3146843MT LREL
Solar/Wind Harmer
0.067
939181AE1-148 GEN
Solar/Wind Harmer
3.035
3143526WINTERP
Solar/Wind Helper
0.908
LAGNLTFEXP_LAGN->PJM
CLTF
1.304
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.417
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.366
MECLTFEXP_MEC->PJM
CLTF
0.764
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.091
TVALTFEXP_TVA->PJM
CLTF
0.67
NYPJM->LTFIMP_NY
CLTF
0.423
LGEELTFEXP_LGEE->PJM
CLTF
0.308
WECLTFEXP_WEC->PJM
CLTF
0.154
CPLELTFEXP_CPLE->PJM
CLTF
1.26
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.459

Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.65 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:1006.31
MW Contribution:15.12
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
2.963
3144293JTRSVLE
50/50
0.501
970413AG2-270 GEN
50/50
9.511
966251AG1-494 GEN
50/50
1.191
3151591KERR 2
50/50
0.134
970221AG2-151 GEN
Solar/Wind Harmer
15.115
3146776BUCKING
Solar/Wind Harmer
0.094
3146926FARMVIL
Solar/Wind Harmer
0.129
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
1.865
3147133PAMPLIN
Solar/Wind Harmer
0.496
971193AH1-056 GEN
Solar/Wind Harmer
9.619
963181AG1-167 GEN
Solar/Wind Harmer
0.594
972205AH1-687 GEN
50/50
14.45
3151541CLOVER2
50/50
2.169
3151611KERR 4
50/50
0.134
3151621KERR 5
50/50
0.134
3151631KERR 6
50/50
0.134
3151641KERR 7
50/50
0.134
971447AH1-217 GEN
Solar/Wind Harmer
8.134
971845AH1-439 GEN
Solar/Wind Harmer
11.699
970285AG2-188 GEN
Solar/Wind Harmer
19.821
270494AE1-108_GEN
Solar/Wind Harmer
2.719
315657AE1-056 GEN
Solar/Wind Harmer
5.448
946301AF1-294 GEN
Solar/Wind Harmer
2.929
961791AG1-021 GEN
Solar/Wind Harmer
1.425
970683AG2-441 GEN
Solar/Wind Harmer
8.983
970681AG2-440 GEN
Solar/Wind Harmer
7.186
3144303KENBRDG
Solar/Wind Harmer
0.096
971443AH1-215 GEN
Solar/Wind Harmer
1.998
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.187
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.068
3147243WELCO
Solar/Wind Harmer
0.043
970865AG2-541 GEN
Solar/Wind Harmer
2.117
316123AC1-075 GEN
Solar/Wind Harmer
0.077
970165AG2-112 GEN
Solar/Wind Harmer
0.456
970163AG2-111 GEN
Solar/Wind Harmer
0.435
316233AE1-074 FULL
Solar/Wind Helper
0.381
316312AB1-027
Solar/Wind Helper
0.218
316132AB2-190 GEN1
Solar/Wind Helper
0.644
3151931BEARGRDN S1
50/50
3.824
3151911BEARGRDN G1
50/50
2.963
3144293JTRSVLE
50/50
0.501
3151531CLOVER1
50/50
2.179
3151601KERR 3
50/50
0.134
3151581KERR 1
50/50
0.048
316336AC2-165 C
Solar/Wind Harmer
0.025
970937AG2-583 GEN
Solar/Wind Harmer
28.676
972003AH1-546 GEN
Solar/Wind Harmer
13.102
971377AH1-170 GEN
Solar/Wind Harmer
3.023
3147623JAMES R
Solar/Wind Harmer
0.657
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
963171AG1-166 GEN
Solar/Wind Harmer
0.792
971563AH1-280 GEN
Solar/Wind Harmer
1.583
970685AG2-442 GEN
Solar/Wind Harmer
10.06
962491AG1-098 GEN
Solar/Wind Harmer
7.008
315693AD1-088 GEN
Solar/Wind Harmer
5.758
957481AF2-042 GEN
Solar/Wind Harmer
29.062
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.003
970401AG2-262 GEN
Solar/Wind Harmer
0.448
316003AC1-222 GEN
Solar/Wind Harmer
0.002
3143226MDLTHAN
Solar/Wind Helper
0.301
3143526WINTERP
Solar/Wind Helper
1.298
3142543TWELFTH
Solar/Wind Helper
0.014
3142416OLDCHRC
Solar/Wind Helper
0.298
3142416OLDCHRC
Solar/Wind Helper
0.114
316458AB2-190 GEN2
Solar/Wind Helper
0.644
3142433PROV 92
Solar/Wind Helper
0.447
959311AF2-222 GEN
Solar/Wind Harmer
11.056
970257AG2-171 GEN
Solar/Wind Harmer
3.847
315785AD2-033 C
Solar/Wind Harmer
0.931
958131AF2-107 GEN
Solar/Wind Harmer
2.944
316478AD1-087 GEN
Solar/Wind Harmer
0.355
316486AD2-202 GEN
Solar/Wind Harmer
0.104
964241AG1-285 GEN
Solar/Wind Harmer
6.611
316131AB2-060 GEN
Solar/Wind Harmer
0.283
3148013FISHERV
Solar/Wind Harmer
0.07
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.916
971683AH1-343 GEN
Solar/Wind Harmer
2.335
316313AB2-026
Solar/Wind Helper
1.246
316258AE1-075 C
Solar/Wind Helper
1.121
316405AF2-144 C
Solar/Wind Helper
0.934
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.714
315839AE2-212 C
Solar/Wind Helper
0.156
3144293JTRSVLE
50/50
0.501
3144293JTRSVLE
50/50
0.422
970535AG2-341 GEN
50/50
1.342
3152661PLYWOOD A
50/50
0.157
971489AH1-241 GEN
Solar/Wind Harmer
15.115
3146776BUCKING
Solar/Wind Harmer
1.047
3146776BUCKING
Solar/Wind Harmer
0.085
315821AE2-092 GEN
Solar/Wind Harmer
0.012
970301AG2-198 GEN
Solar/Wind Harmer
7.46
971741AH1-377 GEN
Solar/Wind Harmer
16.096
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.126
958211AF2-115 GEN
Solar/Wind Harmer
1.781
963191AG1-168 GEN
Solar/Wind Harmer
0.594
316034AC1-036 C
Solar/Wind Harmer
0.009
970323AG2-213 GEN
Solar/Wind Harmer
5.129
971775AH1-396 GEN
Solar/Wind Harmer
0.192
970099AG2-077 GEN
Solar/Wind Harmer
11.625
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.75
964791AG1-342 GEN
Solar/Wind Harmer
1.467
3146843MT LREL
Solar/Wind Harmer
0.076
3146843MT LREL
Solar/Wind Harmer
0.076
939181AE1-148 GEN
Solar/Wind Harmer
3.307
3143526WINTERP
Solar/Wind Helper
1.298
316240AF1-291 C
Solar/Wind Helper
0.163
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.157
316075AC2-137 C
Solar/Wind Helper
0.174
LAGNLTFEXP_LAGN->PJM
CLTF
1.347
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.157
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.592
MECLTFEXP_MEC->PJM
CLTF
1.02
SIGELTFEXP_SIGE->PJM
CLTF
0.033
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.952
TVALTFEXP_TVA->PJM
CLTF
0.702
NYPJM->LTFIMP_NY
CLTF
0.35
LGEELTFEXP_LGEE->PJM
CLTF
0.439
WECLTFEXP_WEC->PJM
CLTF
0.224
CPLELTFEXP_CPLE->PJM
CLTF
0.579
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.662

Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2028T2054_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.54 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1171.53
MW Contribution:30.7
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.569
3144293JTRSVLE
50/50
0.617
970221AG2-151 GEN
Solar/Wind Harmer
30.705
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.028
970909AG2-566 GEN
Solar/Wind Harmer
2.106
3147133PAMPLIN
Solar/Wind Harmer
-0.069
971193AH1-056 GEN
Solar/Wind Harmer
13.849
963181AG1-167 GEN
Solar/Wind Harmer
1.924
959311AF2-222 GEN
Solar/Wind Harmer
17.112
958131AF2-107 GEN
Solar/Wind Harmer
5.537
970257AG2-171 GEN
Solar/Wind Harmer
5.879
315785AD2-033 C
Solar/Wind Harmer
3.33
964241AG1-285 GEN
Solar/Wind Harmer
9.43
316131AB2-060 GEN
Solar/Wind Harmer
1.13
316313AB2-026
Solar/Wind Helper
0.96
316258AE1-075 C
Solar/Wind Helper
0.864
316405AF2-144 C
Solar/Wind Helper
0.72
3151931BEARGRDN S1
50/50
5.897
3151911BEARGRDN G1
50/50
4.569
3144293JTRSVLE
50/50
0.617
316336AC2-165 C
Solar/Wind Harmer
14.675
970937AG2-583 GEN
Solar/Wind Harmer
49.327
972003AH1-546 GEN
Solar/Wind Harmer
26.381
971377AH1-170 GEN
Solar/Wind Harmer
6.141
3147623JAMES R
Solar/Wind Harmer
0.76
316322AB2-045
Solar/Wind Harmer
1.429
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
963171AG1-166 GEN
Solar/Wind Harmer
2.565
971563AH1-280 GEN
Solar/Wind Harmer
2.565
970685AG2-442 GEN
Solar/Wind Harmer
15.9
316237AB2-079_GEN
Solar/Wind Harmer
0.294
962491AG1-098 GEN
Solar/Wind Harmer
6.402
315693AD1-088 GEN
Solar/Wind Harmer
4.443
970401AG2-262 GEN
Solar/Wind Harmer
0.493
962751AG1-124 GEN
Solar/Wind Harmer
4.397
3143226MDLTHAN
Solar/Wind Helper
0.216
3143526WINTERP
Solar/Wind Helper
0.913
3144293JTRSVLE
50/50
0.617
3144293JTRSVLE
50/50
0.52
971489AH1-241 GEN
Solar/Wind Harmer
29.15
3146776BUCKING
Solar/Wind Harmer
-0.169
3146776BUCKING
Solar/Wind Harmer
-0.014
315821AE2-092 GEN
Solar/Wind Harmer
6.923
970301AG2-198 GEN
Solar/Wind Harmer
11.092
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.206
963191AG1-168 GEN
Solar/Wind Harmer
1.924
971741AH1-377 GEN
Solar/Wind Harmer
22.241
316034AC1-036 C
Solar/Wind Harmer
0.291
970323AG2-213 GEN
Solar/Wind Harmer
7.839
971775AH1-396 GEN
Solar/Wind Harmer
1.116
313527AB2-043 GEN
Solar/Wind Harmer
1.639
962561AG1-105 GEN
Solar/Wind Harmer
4.465
964791AG1-342 GEN
Solar/Wind Harmer
1.613
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
939181AE1-148 GEN
Solar/Wind Harmer
3.994
3143526WINTERP
Solar/Wind Helper
0.913
972205AH1-687 GEN
50/50
22.285
971447AH1-217 GEN
Solar/Wind Harmer
16.368
971845AH1-439 GEN
Solar/Wind Harmer
22.098
970285AG2-188 GEN
Solar/Wind Harmer
34.919
270494AE1-108_GEN
Solar/Wind Harmer
10.102
315657AE1-056 GEN
Solar/Wind Harmer
8.309
946301AF1-294 GEN
Solar/Wind Harmer
5.258
961791AG1-021 GEN
Solar/Wind Harmer
2.565
970683AG2-441 GEN
Solar/Wind Harmer
14.197
970681AG2-440 GEN
Solar/Wind Harmer
11.357
3144303KENBRDG
Solar/Wind Harmer
-0.013
971443AH1-215 GEN
Solar/Wind Harmer
3.044
316239AB2-077_GEN
Solar/Wind Harmer
0.294
316238AB2-078_GEN
Solar/Wind Harmer
0.294
316118AC1-105 GEN
Solar/Wind Harmer
0.455
316233AE1-074 FULL
Solar/Wind Helper
0.268
LAGNLTFEXP_LAGN->PJM
CLTF
1.37
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.853
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.493
MECLTFEXP_MEC->PJM
CLTF
0.817
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.164
TVALTFEXP_TVA->PJM
CLTF
0.704
SIGELTFEXP_SIGE->PJM
CLTF
0.026
CPLELTFEXP_CPLE->PJM
CLTF
1.275
NYPJM->LTFIMP_NY
CLTF
0.44
LGEELTFEXP_LGEE->PJM
CLTF
0.331
WECLTFEXP_WEC->PJM
CLTF
0.165
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.894

Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 233T2028_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.8 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1154.42
MW Contribution:30.67
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.567
3144293JTRSVLE
50/50
0.617
970221AG2-151 GEN
Solar/Wind Harmer
30.668
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.028
970909AG2-566 GEN
Solar/Wind Harmer
2.106
3147133PAMPLIN
Solar/Wind Harmer
-0.069
971193AH1-056 GEN
Solar/Wind Harmer
13.847
963181AG1-167 GEN
Solar/Wind Harmer
1.923
959311AF2-222 GEN
Solar/Wind Harmer
17.111
958131AF2-107 GEN
Solar/Wind Harmer
5.507
970257AG2-171 GEN
Solar/Wind Harmer
5.879
315785AD2-033 C
Solar/Wind Harmer
3.33
964241AG1-285 GEN
Solar/Wind Harmer
9.43
316131AB2-060 GEN
Solar/Wind Harmer
1.131
316313AB2-026
Solar/Wind Helper
0.96
316258AE1-075 C
Solar/Wind Helper
0.863
316405AF2-144 C
Solar/Wind Helper
0.719
3151931BEARGRDN S1
50/50
5.894
3151911BEARGRDN G1
50/50
4.567
3144293JTRSVLE
50/50
0.617
316336AC2-165 C
Solar/Wind Harmer
14.677
970937AG2-583 GEN
Solar/Wind Harmer
49.32
972003AH1-546 GEN
Solar/Wind Harmer
26.368
971377AH1-170 GEN
Solar/Wind Harmer
6.134
3147623JAMES R
Solar/Wind Harmer
0.759
316322AB2-045
Solar/Wind Harmer
1.428
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
963171AG1-166 GEN
Solar/Wind Harmer
2.565
971563AH1-280 GEN
Solar/Wind Harmer
2.565
970685AG2-442 GEN
Solar/Wind Harmer
15.899
316237AB2-079_GEN
Solar/Wind Harmer
0.294
962491AG1-098 GEN
Solar/Wind Harmer
6.41
315693AD1-088 GEN
Solar/Wind Harmer
4.449
970401AG2-262 GEN
Solar/Wind Harmer
0.492
962751AG1-124 GEN
Solar/Wind Harmer
4.338
3143226MDLTHAN
Solar/Wind Helper
0.215
3143526WINTERP
Solar/Wind Helper
0.908
3144293JTRSVLE
50/50
0.617
3144293JTRSVLE
50/50
0.519
971489AH1-241 GEN
Solar/Wind Harmer
29.115
3146776BUCKING
Solar/Wind Harmer
-0.169
3146776BUCKING
Solar/Wind Harmer
-0.014
315821AE2-092 GEN
Solar/Wind Harmer
6.883
970301AG2-198 GEN
Solar/Wind Harmer
11.092
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.206
963191AG1-168 GEN
Solar/Wind Harmer
1.923
971741AH1-377 GEN
Solar/Wind Harmer
22.246
316034AC1-036 C
Solar/Wind Harmer
0.291
970323AG2-213 GEN
Solar/Wind Harmer
7.839
971775AH1-396 GEN
Solar/Wind Harmer
1.116
313527AB2-043 GEN
Solar/Wind Harmer
1.639
962561AG1-105 GEN
Solar/Wind Harmer
4.463
964791AG1-342 GEN
Solar/Wind Harmer
1.612
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
939181AE1-148 GEN
Solar/Wind Harmer
3.996
3143526WINTERP
Solar/Wind Helper
0.908
972205AH1-687 GEN
50/50
22.273
971447AH1-217 GEN
Solar/Wind Harmer
16.337
971845AH1-439 GEN
Solar/Wind Harmer
22.09
970285AG2-188 GEN
Solar/Wind Harmer
34.906
270494AE1-108_GEN
Solar/Wind Harmer
10.084
315657AE1-056 GEN
Solar/Wind Harmer
8.308
946301AF1-294 GEN
Solar/Wind Harmer
5.258
961791AG1-021 GEN
Solar/Wind Harmer
2.565
970683AG2-441 GEN
Solar/Wind Harmer
14.195
970681AG2-440 GEN
Solar/Wind Harmer
11.356
3144303KENBRDG
Solar/Wind Harmer
-0.013
971443AH1-215 GEN
Solar/Wind Harmer
3.044
316239AB2-077_GEN
Solar/Wind Harmer
0.294
316238AB2-078_GEN
Solar/Wind Harmer
0.294
316118AC1-105 GEN
Solar/Wind Harmer
0.455
316233AE1-074 FULL
Solar/Wind Helper
0.267
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.473
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.382
MECLTFEXP_MEC->PJM
CLTF
0.771
LAGNLTFEXP_LAGN->PJM
CLTF
1.312
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.1
TVALTFEXP_TVA->PJM
CLTF
0.674
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CPLELTFEXP_CPLE->PJM
CLTF
1.262
NYPJM->LTFIMP_NY
CLTF
0.425
LGEELTFEXP_LGEE->PJM
CLTF
0.311
WECLTFEXP_WEC->PJM
CLTF
0.155
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.514

Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2193_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2028T2193_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.69 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1153.32
MW Contribution:29.4
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.624
3144293JTRSVLE
50/50
0.626
970221AG2-151 GEN
Solar/Wind Harmer
29.396
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.083
970909AG2-566 GEN
Solar/Wind Harmer
2.137
3147133PAMPLIN
Solar/Wind Harmer
-0.07
971193AH1-056 GEN
Solar/Wind Harmer
14.042
963181AG1-167 GEN
Solar/Wind Harmer
1.951
959311AF2-222 GEN
Solar/Wind Harmer
17.366
970257AG2-171 GEN
Solar/Wind Harmer
5.968
958131AF2-107 GEN
Solar/Wind Harmer
5.285
315785AD2-033 C
Solar/Wind Harmer
3.381
964241AG1-285 GEN
Solar/Wind Harmer
9.581
316131AB2-060 GEN
Solar/Wind Harmer
1.149
316313AB2-026
Solar/Wind Helper
0.95
316258AE1-075 C
Solar/Wind Helper
0.855
316405AF2-144 C
Solar/Wind Helper
0.712
3151931BEARGRDN S1
50/50
5.967
3151911BEARGRDN G1
50/50
4.624
3144293JTRSVLE
50/50
0.626
316336AC2-165 C
Solar/Wind Harmer
14.751
970937AG2-583 GEN
Solar/Wind Harmer
49.728
972003AH1-546 GEN
Solar/Wind Harmer
26.698
971377AH1-170 GEN
Solar/Wind Harmer
5.879
3147623JAMES R
Solar/Wind Harmer
0.728
316322AB2-045
Solar/Wind Harmer
1.447
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
3144293JTRSVLE
50/50
0.626
3144293JTRSVLE
50/50
0.527
971489AH1-241 GEN
Solar/Wind Harmer
27.908
3146776BUCKING
Solar/Wind Harmer
-0.171
3146776BUCKING
Solar/Wind Harmer
-0.014
315821AE2-092 GEN
Solar/Wind Harmer
6.517
970301AG2-198 GEN
Solar/Wind Harmer
11.252
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.252
963191AG1-168 GEN
Solar/Wind Harmer
1.951
971741AH1-377 GEN
Solar/Wind Harmer
22.579
316034AC1-036 C
Solar/Wind Harmer
0.296
970323AG2-213 GEN
Solar/Wind Harmer
7.957
971775AH1-396 GEN
Solar/Wind Harmer
1.133
313527AB2-043 GEN
Solar/Wind Harmer
1.667
962561AG1-105 GEN
Solar/Wind Harmer
4.537
964791AG1-342 GEN
Solar/Wind Harmer
1.638
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
939181AE1-148 GEN
Solar/Wind Harmer
4.074
3143526WINTERP
Solar/Wind Helper
0.896
963171AG1-166 GEN
Solar/Wind Harmer
2.601
971563AH1-280 GEN
Solar/Wind Harmer
2.601
970685AG2-442 GEN
Solar/Wind Harmer
16.131
316237AB2-079_GEN
Solar/Wind Harmer
0.299
962491AG1-098 GEN
Solar/Wind Harmer
6.532
315693AD1-088 GEN
Solar/Wind Harmer
4.536
970401AG2-262 GEN
Solar/Wind Harmer
0.501
962751AG1-124 GEN
Solar/Wind Harmer
4.17
3143226MDLTHAN
Solar/Wind Helper
0.212
3143526WINTERP
Solar/Wind Helper
0.896
972205AH1-687 GEN
50/50
22.551
971447AH1-217 GEN
Solar/Wind Harmer
15.483
971845AH1-439 GEN
Solar/Wind Harmer
22.374
970285AG2-188 GEN
Solar/Wind Harmer
35.358
270494AE1-108_GEN
Solar/Wind Harmer
9.667
315657AE1-056 GEN
Solar/Wind Harmer
8.425
946301AF1-294 GEN
Solar/Wind Harmer
5.333
961791AG1-021 GEN
Solar/Wind Harmer
2.601
970683AG2-441 GEN
Solar/Wind Harmer
14.402
970681AG2-440 GEN
Solar/Wind Harmer
11.522
3144303KENBRDG
Solar/Wind Harmer
-0.013
971443AH1-215 GEN
Solar/Wind Harmer
3.09
316239AB2-077_GEN
Solar/Wind Harmer
0.299
316238AB2-078_GEN
Solar/Wind Harmer
0.299
316118AC1-105 GEN
Solar/Wind Harmer
0.462
316233AE1-074 FULL
Solar/Wind Helper
0.263
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.273
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.343
MECLTFEXP_MEC->PJM
CLTF
0.749
LAGNLTFEXP_LAGN->PJM
CLTF
1.296
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.136
TVALTFEXP_TVA->PJM
CLTF
0.665
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CPLELTFEXP_CPLE->PJM
CLTF
1.291
NYPJM->LTFIMP_NY
CLTF
0.422
LGEELTFEXP_LGEE->PJM
CLTF
0.301
WECLTFEXP_WEC->PJM
CLTF
0.15
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.369

Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: WT2193_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT2193_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.66 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1153.09
MW Contribution:29.4
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.967
3151911BEARGRDN G1
50/50
4.624
3144293JTRSVLE
50/50
0.626
316336AC2-165 C
Solar/Wind Harmer
14.751
970937AG2-583 GEN
Solar/Wind Harmer
49.728
3144293JTRSVLE
50/50
0.626
3144293JTRSVLE
50/50
0.527
971489AH1-241 GEN
Solar/Wind Harmer
27.908
3146776BUCKING
Solar/Wind Harmer
-0.171
3146776BUCKING
Solar/Wind Harmer
-0.014
315821AE2-092 GEN
Solar/Wind Harmer
6.517
970301AG2-198 GEN
Solar/Wind Harmer
11.252
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.252
963191AG1-168 GEN
Solar/Wind Harmer
1.951
971741AH1-377 GEN
Solar/Wind Harmer
22.579
316034AC1-036 C
Solar/Wind Harmer
0.296
970323AG2-213 GEN
Solar/Wind Harmer
7.957
971775AH1-396 GEN
Solar/Wind Harmer
1.133
313527AB2-043 GEN
Solar/Wind Harmer
1.667
962561AG1-105 GEN
Solar/Wind Harmer
4.537
964791AG1-342 GEN
Solar/Wind Harmer
1.638
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
939181AE1-148 GEN
Solar/Wind Harmer
4.074
3143526WINTERP
Solar/Wind Helper
0.896
972003AH1-546 GEN
Solar/Wind Harmer
26.698
971377AH1-170 GEN
Solar/Wind Harmer
5.879
3147623JAMES R
Solar/Wind Harmer
0.728
316322AB2-045
Solar/Wind Harmer
1.447
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
963171AG1-166 GEN
Solar/Wind Harmer
2.601
971563AH1-280 GEN
Solar/Wind Harmer
2.601
970685AG2-442 GEN
Solar/Wind Harmer
16.131
316237AB2-079_GEN
Solar/Wind Harmer
0.299
962491AG1-098 GEN
Solar/Wind Harmer
6.532
315693AD1-088 GEN
Solar/Wind Harmer
4.536
970401AG2-262 GEN
Solar/Wind Harmer
0.501
962751AG1-124 GEN
Solar/Wind Harmer
4.17
3143226MDLTHAN
Solar/Wind Helper
0.212
3143526WINTERP
Solar/Wind Helper
0.896
3151921BEARGRDN G2
50/50
4.624
3144293JTRSVLE
50/50
0.626
970221AG2-151 GEN
Solar/Wind Harmer
29.396
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.083
970909AG2-566 GEN
Solar/Wind Harmer
2.137
3147133PAMPLIN
Solar/Wind Harmer
-0.07
971193AH1-056 GEN
Solar/Wind Harmer
14.042
963181AG1-167 GEN
Solar/Wind Harmer
1.951
959311AF2-222 GEN
Solar/Wind Harmer
17.366
970257AG2-171 GEN
Solar/Wind Harmer
5.968
958131AF2-107 GEN
Solar/Wind Harmer
5.285
315785AD2-033 C
Solar/Wind Harmer
3.381
964241AG1-285 GEN
Solar/Wind Harmer
9.581
316131AB2-060 GEN
Solar/Wind Harmer
1.149
316313AB2-026
Solar/Wind Helper
0.95
316258AE1-075 C
Solar/Wind Helper
0.855
316405AF2-144 C
Solar/Wind Helper
0.712
972205AH1-687 GEN
50/50
22.551
971447AH1-217 GEN
Solar/Wind Harmer
15.483
971845AH1-439 GEN
Solar/Wind Harmer
22.374
970285AG2-188 GEN
Solar/Wind Harmer
35.358
270494AE1-108_GEN
Solar/Wind Harmer
9.667
315657AE1-056 GEN
Solar/Wind Harmer
8.425
946301AF1-294 GEN
Solar/Wind Harmer
5.333
961791AG1-021 GEN
Solar/Wind Harmer
2.601
970683AG2-441 GEN
Solar/Wind Harmer
14.402
970681AG2-440 GEN
Solar/Wind Harmer
11.522
3144303KENBRDG
Solar/Wind Harmer
-0.013
971443AH1-215 GEN
Solar/Wind Harmer
3.09
316239AB2-077_GEN
Solar/Wind Harmer
0.299
316238AB2-078_GEN
Solar/Wind Harmer
0.299
316118AC1-105 GEN
Solar/Wind Harmer
0.462
316233AE1-074 FULL
Solar/Wind Helper
0.263
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.273
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.343
MECLTFEXP_MEC->PJM
CLTF
0.749
LAGNLTFEXP_LAGN->PJM
CLTF
1.296
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.136
TVALTFEXP_TVA->PJM
CLTF
0.665
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CPLELTFEXP_CPLE->PJM
CLTF
1.291
NYPJM->LTFIMP_NY
CLTF
0.422
LGEELTFEXP_LGEE->PJM
CLTF
0.301
WECLTFEXP_WEC->PJM
CLTF
0.15
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.369

Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 202872_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 202872_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.34 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1149.95
MW Contribution:29.4
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.624
3144293JTRSVLE
50/50
0.626
970221AG2-151 GEN
Solar/Wind Harmer
29.396
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.083
3144293JTRSVLE
50/50
0.626
3144293JTRSVLE
50/50
0.527
971489AH1-241 GEN
Solar/Wind Harmer
27.908
3146776BUCKING
Solar/Wind Harmer
-0.171
3146776BUCKING
Solar/Wind Harmer
-0.014
315821AE2-092 GEN
Solar/Wind Harmer
6.517
970301AG2-198 GEN
Solar/Wind Harmer
11.252
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3151931BEARGRDN S1
50/50
5.967
3151911BEARGRDN G1
50/50
4.624
3144293JTRSVLE
50/50
0.626
316336AC2-165 C
Solar/Wind Harmer
14.751
970937AG2-583 GEN
Solar/Wind Harmer
49.728
972003AH1-546 GEN
Solar/Wind Harmer
26.698
971377AH1-170 GEN
Solar/Wind Harmer
5.879
3147623JAMES R
Solar/Wind Harmer
0.728
316322AB2-045
Solar/Wind Harmer
1.447
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
963171AG1-166 GEN
Solar/Wind Harmer
2.601
971563AH1-280 GEN
Solar/Wind Harmer
2.601
970685AG2-442 GEN
Solar/Wind Harmer
16.131
316237AB2-079_GEN
Solar/Wind Harmer
0.299
962491AG1-098 GEN
Solar/Wind Harmer
6.532
315693AD1-088 GEN
Solar/Wind Harmer
4.536
970401AG2-262 GEN
Solar/Wind Harmer
0.501
962751AG1-124 GEN
Solar/Wind Harmer
4.17
3143226MDLTHAN
Solar/Wind Helper
0.212
3143526WINTERP
Solar/Wind Helper
0.896
970909AG2-566 GEN
Solar/Wind Harmer
2.137
3147133PAMPLIN
Solar/Wind Harmer
-0.07
971193AH1-056 GEN
Solar/Wind Harmer
14.042
963181AG1-167 GEN
Solar/Wind Harmer
1.951
959311AF2-222 GEN
Solar/Wind Harmer
17.366
970257AG2-171 GEN
Solar/Wind Harmer
5.968
958131AF2-107 GEN
Solar/Wind Harmer
5.285
315785AD2-033 C
Solar/Wind Harmer
3.381
964241AG1-285 GEN
Solar/Wind Harmer
9.581
316131AB2-060 GEN
Solar/Wind Harmer
1.149
316313AB2-026
Solar/Wind Helper
0.95
316258AE1-075 C
Solar/Wind Helper
0.855
316405AF2-144 C
Solar/Wind Helper
0.712
972205AH1-687 GEN
50/50
22.551
971447AH1-217 GEN
Solar/Wind Harmer
15.483
971845AH1-439 GEN
Solar/Wind Harmer
22.374
970285AG2-188 GEN
Solar/Wind Harmer
35.358
270494AE1-108_GEN
Solar/Wind Harmer
9.667
315657AE1-056 GEN
Solar/Wind Harmer
8.425
946301AF1-294 GEN
Solar/Wind Harmer
5.333
961791AG1-021 GEN
Solar/Wind Harmer
2.601
970683AG2-441 GEN
Solar/Wind Harmer
14.402
970681AG2-440 GEN
Solar/Wind Harmer
11.522
3144303KENBRDG
Solar/Wind Harmer
-0.013
971443AH1-215 GEN
Solar/Wind Harmer
3.09
316239AB2-077_GEN
Solar/Wind Harmer
0.299
316238AB2-078_GEN
Solar/Wind Harmer
0.299
316118AC1-105 GEN
Solar/Wind Harmer
0.462
316233AE1-074 FULL
Solar/Wind Helper
0.263
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.252
963191AG1-168 GEN
Solar/Wind Harmer
1.951
971741AH1-377 GEN
Solar/Wind Harmer
22.579
316034AC1-036 C
Solar/Wind Harmer
0.296
970323AG2-213 GEN
Solar/Wind Harmer
7.957
971775AH1-396 GEN
Solar/Wind Harmer
1.133
313527AB2-043 GEN
Solar/Wind Harmer
1.667
962561AG1-105 GEN
Solar/Wind Harmer
4.537
964791AG1-342 GEN
Solar/Wind Harmer
1.638
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
939181AE1-148 GEN
Solar/Wind Harmer
4.074
3143526WINTERP
Solar/Wind Helper
0.896
LAGNLTFEXP_LAGN->PJM
CLTF
1.296
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.273
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.343
MECLTFEXP_MEC->PJM
CLTF
0.749
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.136
TVALTFEXP_TVA->PJM
CLTF
0.665
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CPLELTFEXP_CPLE->PJM
CLTF
1.291
NYPJM->LTFIMP_NY
CLTF
0.422
LGEELTFEXP_LGEE->PJM
CLTF
0.301
WECLTFEXP_WEC->PJM
CLTF
0.15
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.369

Details for AG1-098 TP-6FINNEYWOOD 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG1-098 TP-6FINNEYWOOD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-6: CHASE C T342_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.09 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:853.39
MW Contribution:13.93
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.843
3151931BEARGRDN S1
50/50
2.684
3151911BEARGRDN G1
50/50
2.08
962491AG1-098 GEN
Solar/Wind Harmer
69.83
3146926FARMVIL
Solar/Wind Harmer
-0.036
970685AG2-442 GEN
Solar/Wind Harmer
53.632
963171AG1-166 GEN
Solar/Wind Harmer
7.662
971563AH1-280 GEN
Solar/Wind Harmer
7.662
316322AB2-045
Solar/Wind Harmer
1.513
3146776BUCKING
Solar/Wind Harmer
-0.018
972003AH1-546 GEN
Solar/Wind Harmer
14.352
971377AH1-170 GEN
Solar/Wind Harmer
2.786
3147623JAMES R
Solar/Wind Harmer
0.345
970937AG2-583 GEN
Solar/Wind Harmer
14.305
316336AC2-165 C
Solar/Wind Harmer
2.384
3143336POWHATN
Solar/Wind Harmer
1.342
315687AD1-152 GEN
Solar/Wind Helper
1.215
316237AB2-079_GEN
Solar/Wind Helper
0.255
316129AC1-054 GEN
Solar/Wind Helper
0.83
3144293JTRSVLE
50/50
1.843
3151921BEARGRDN G2
50/50
2.08
970909AG2-566 GEN
Solar/Wind Harmer
7.611
942461AE2-259 GEN
Solar/Wind Harmer
9.211
3146926FARMVIL
Solar/Wind Harmer
-0.036
3147133PAMPLIN
Solar/Wind Harmer
-0.192
959311AF2-222 GEN
Solar/Wind Harmer
63.976
971193AH1-056 GEN
Solar/Wind Harmer
38.309
970257AG2-171 GEN
Solar/Wind Harmer
22.985
963181AG1-167 GEN
Solar/Wind Harmer
5.746
315785AD2-033 C
Solar/Wind Harmer
13.891
316131AB2-060 GEN
Solar/Wind Harmer
6.613
964241AG1-285 GEN
Solar/Wind Harmer
47.885
3146776BUCKING
Solar/Wind Harmer
-0.016
970221AG2-151 GEN
Solar/Wind Harmer
13.931
316313AB2-026
Solar/Wind Harmer
0.305
316258AE1-075 C
Solar/Wind Harmer
0.275
316405AF2-144 C
Solar/Wind Harmer
0.29
3143336POWHATN
Solar/Wind Harmer
1.141
972183AH1-676 GEN
Adder
39.209
316478AD1-087 GEN
Solar/Wind Helper
1.275
316486AD2-202 GEN
Solar/Wind Helper
0.373
316248AF1-058 C
Solar/Wind Helper
0.23
316283AC2-100 C
Solar/Wind Helper
0.644
316003AC1-222 GEN
Solar/Wind Helper
0.686
3144293JTRSVLE
50/50
1.843
3144293JTRSVLE
50/50
1.552
971741AH1-377 GEN
Solar/Wind Harmer
100.021
970301AG2-198 GEN
Solar/Wind Harmer
40.087
316034AC1-036 C
Solar/Wind Harmer
1.137
3147133PAMPLIN
Solar/Wind Harmer
-0.061
3147133PAMPLIN
Solar/Wind Harmer
-0.049
970323AG2-213 GEN
Solar/Wind Harmer
30.647
958211AF2-115 GEN
Solar/Wind Harmer
9.577
963191AG1-168 GEN
Solar/Wind Harmer
5.746
971775AH1-396 GEN
Solar/Wind Harmer
4.364
3146776BUCKING
Solar/Wind Harmer
-0.179
3146776BUCKING
Solar/Wind Harmer
-0.015
971489AH1-241 GEN
Solar/Wind Harmer
13.226
315821AE2-092 GEN
Solar/Wind Harmer
3.439
3146843MT LREL
Solar/Wind Helper
0.172
3146843MT LREL
Solar/Wind Helper
0.172
316222AC1-221 GEN
Solar/Wind Helper
0.699
972205AH1-687 GEN
50/50
10.143
3144303KENBRDG
Solar/Wind Harmer
-0.049
970683AG2-441 GEN
Solar/Wind Harmer
47.886
970681AG2-440 GEN
Solar/Wind Harmer
38.309
315657AE1-056 GEN
Solar/Wind Harmer
22.986
946301AF1-294 GEN
Solar/Wind Harmer
15.707
961791AG1-021 GEN
Solar/Wind Harmer
7.662
971443AH1-215 GEN
Solar/Wind Harmer
12.067
970285AG2-188 GEN
Solar/Wind Harmer
42.868
971845AH1-439 GEN
Solar/Wind Harmer
24.629
971447AH1-217 GEN
Solar/Wind Harmer
7.521
270494AE1-108_GEN
Solar/Wind Harmer
4.495
3138266HYDRAULIC
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Helper
0.255
316238AB2-078_GEN
Solar/Wind Helper
0.255
3147173SINAI
Solar/Wind Helper
0.172
3147243WELCO
Solar/Wind Helper
0.107
316118AC1-105 GEN
Solar/Wind Helper
0.666
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.216
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.69
VTFLTFEXP_VFT->PJM
CMTX
2.578
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.855
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.599
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.961
CBM NorthLTFEXP_CBM-N->PJM
CBM
1.806
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.805

Details for AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.8 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:983.47
MW Contribution:23.31
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.57
3144293JTRSVLE
50/50
0.618
966251AG1-494 GEN
50/50
1.545
3151591KERR 2
50/50
0.12
970221AG2-151 GEN
Solar/Wind Harmer
23.308
3146776BUCKING
Solar/Wind Harmer
0.136
3146926FARMVIL
Solar/Wind Harmer
0.171
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
2.11
3147133PAMPLIN
Solar/Wind Harmer
0.62
971193AH1-056 GEN
Solar/Wind Harmer
12.029
963181AG1-167 GEN
Solar/Wind Harmer
0.732
3144293JTRSVLE
50/50
0.618
3144293JTRSVLE
50/50
0.52
970535AG2-341 GEN
50/50
1.297
971489AH1-241 GEN
Solar/Wind Harmer
23.308
3146776BUCKING
Solar/Wind Harmer
1.512
3146776BUCKING
Solar/Wind Harmer
0.122
315821AE2-092 GEN
Solar/Wind Harmer
0.018
970301AG2-198 GEN
Solar/Wind Harmer
8.441
3147133PAMPLIN
Solar/Wind Harmer
0.197
3147133PAMPLIN
Solar/Wind Harmer
0.158
958211AF2-115 GEN
Solar/Wind Harmer
2.196
963191AG1-168 GEN
Solar/Wind Harmer
0.732
971741AH1-377 GEN
Solar/Wind Harmer
16.934
316034AC1-036 C
Solar/Wind Harmer
0.01
970323AG2-213 GEN
Solar/Wind Harmer
5.97
971775AH1-396 GEN
Solar/Wind Harmer
0.224
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.408
964791AG1-342 GEN
Solar/Wind Harmer
1.297
3146843MT LREL
Solar/Wind Harmer
0.067
3146843MT LREL
Solar/Wind Harmer
0.067
939181AE1-148 GEN
Solar/Wind Harmer
3.054
3143526WINTERP
Solar/Wind Helper
0.904
972205AH1-687 GEN
50/50
22.289
3151931BEARGRDN S1
50/50
5.898
3151911BEARGRDN G1
50/50
4.57
3144293JTRSVLE
50/50
0.618
3151601KERR 3
50/50
0.12
3151581KERR 1
50/50
0.043
970937AG2-583 GEN
Solar/Wind Harmer
37.481
972003AH1-546 GEN
Solar/Wind Harmer
20.008
971377AH1-170 GEN
Solar/Wind Harmer
4.662
3147623JAMES R
Solar/Wind Harmer
1.013
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.151
3146926FARMVIL
Solar/Wind Harmer
0.171
963171AG1-166 GEN
Solar/Wind Harmer
0.976
971563AH1-280 GEN
Solar/Wind Harmer
1.952
970685AG2-442 GEN
Solar/Wind Harmer
12.103
316237AB2-079_GEN
Solar/Wind Harmer
0.001
962491AG1-098 GEN
Solar/Wind Harmer
4.891
315693AD1-088 GEN
Solar/Wind Harmer
3.821
970401AG2-262 GEN
Solar/Wind Harmer
0.396
962751AG1-124 GEN
Solar/Wind Harmer
2.983
316336AC2-165 C
Solar/Wind Helper
3.978
3143226MDLTHAN
Solar/Wind Helper
0.214
3143526WINTERP
Solar/Wind Helper
0.904
3151611KERR 4
50/50
0.12
3151621KERR 5
50/50
0.12
3151631KERR 6
50/50
0.12
3151641KERR 7
50/50
0.12
971447AH1-217 GEN
Solar/Wind Harmer
12.416
971845AH1-439 GEN
Solar/Wind Harmer
16.793
970285AG2-188 GEN
Solar/Wind Harmer
28.117
270494AE1-108_GEN
Solar/Wind Harmer
4.14
315657AE1-056 GEN
Solar/Wind Harmer
6.813
946301AF1-294 GEN
Solar/Wind Harmer
3.611
961791AG1-021 GEN
Solar/Wind Harmer
1.757
970683AG2-441 GEN
Solar/Wind Harmer
10.806
970681AG2-440 GEN
Solar/Wind Harmer
8.645
3144303KENBRDG
Solar/Wind Harmer
0.112
971443AH1-215 GEN
Solar/Wind Harmer
2.318
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.153
316233AE1-074 FULL
Solar/Wind Helper
0.266
959311AF2-222 GEN
Solar/Wind Harmer
13.003
958131AF2-107 GEN
Solar/Wind Harmer
4.145
970257AG2-171 GEN
Solar/Wind Harmer
4.477
315785AD2-033 C
Solar/Wind Harmer
1.066
964241AG1-285 GEN
Solar/Wind Harmer
7.188
316131AB2-060 GEN
Solar/Wind Harmer
0.295
316313AB2-026
Solar/Wind Helper
0.958
316258AE1-075 C
Solar/Wind Helper
0.862
316405AF2-144 C
Solar/Wind Helper
0.719
LAGNLTFEXP_LAGN->PJM
CLTF
1.363
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.841
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.476
MECLTFEXP_MEC->PJM
CLTF
0.813
SIGELTFEXP_SIGE->PJM
CLTF
0.026
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.179
TVALTFEXP_TVA->PJM
CLTF
0.699
NYPJM->LTFIMP_NY
CLTF
0.404
LGEELTFEXP_LGEE->PJM
CLTF
0.328
WECLTFEXP_WEC->PJM
CLTF
0.165
CPLELTFEXP_CPLE->PJM
CLTF
1.292
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.85

Details for AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.99 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:969.01
MW Contribution:15.13
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.503
3144293JTRSVLE
50/50
0.423
970535AG2-341 GEN
50/50
1.349
3152661PLYWOOD A
50/50
0.157
971489AH1-241 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
1.049
3146776BUCKING
Solar/Wind Harmer
0.085
315821AE2-092 GEN
Solar/Wind Harmer
0.013
970301AG2-198 GEN
Solar/Wind Harmer
7.476
971741AH1-377 GEN
Solar/Wind Harmer
16.133
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.127
958211AF2-115 GEN
Solar/Wind Harmer
1.786
963191AG1-168 GEN
Solar/Wind Harmer
0.595
316034AC1-036 C
Solar/Wind Harmer
0.009
970323AG2-213 GEN
Solar/Wind Harmer
5.145
971775AH1-396 GEN
Solar/Wind Harmer
0.193
970099AG2-077 GEN
Solar/Wind Harmer
11.665
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.768
964791AG1-342 GEN
Solar/Wind Harmer
1.475
3146843MT LREL
Solar/Wind Harmer
0.077
3146843MT LREL
Solar/Wind Harmer
0.077
939181AE1-148 GEN
Solar/Wind Harmer
3.325
3143526WINTERP
Solar/Wind Helper
1.294
316240AF1-291 C
Solar/Wind Helper
0.162
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.156
316075AC2-137 C
Solar/Wind Helper
0.172
3151921BEARGRDN G2
50/50
2.966
3144293JTRSVLE
50/50
0.503
970413AG2-270 GEN
50/50
9.546
966251AG1-494 GEN
50/50
1.198
3151591KERR 2
50/50
0.135
970221AG2-151 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
0.094
3146926FARMVIL
Solar/Wind Harmer
0.129
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
1.869
3147133PAMPLIN
Solar/Wind Harmer
0.497
971193AH1-056 GEN
Solar/Wind Harmer
9.642
963181AG1-167 GEN
Solar/Wind Harmer
0.595
959311AF2-222 GEN
Solar/Wind Harmer
11.09
970257AG2-171 GEN
Solar/Wind Harmer
3.859
315785AD2-033 C
Solar/Wind Harmer
0.934
958131AF2-107 GEN
Solar/Wind Harmer
2.955
316478AD1-087 GEN
Solar/Wind Harmer
0.356
316486AD2-202 GEN
Solar/Wind Harmer
0.105
964241AG1-285 GEN
Solar/Wind Harmer
6.636
316131AB2-060 GEN
Solar/Wind Harmer
0.284
3148013FISHERV
Solar/Wind Harmer
0.071
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.932
971683AH1-343 GEN
Solar/Wind Harmer
2.348
316313AB2-026
Solar/Wind Helper
1.245
316258AE1-075 C
Solar/Wind Helper
1.12
316405AF2-144 C
Solar/Wind Helper
0.933
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.709
315839AE2-212 C
Solar/Wind Helper
0.155
972205AH1-687 GEN
50/50
14.467
3151541CLOVER2
50/50
2.177
3151611KERR 4
50/50
0.135
3151621KERR 5
50/50
0.135
3151631KERR 6
50/50
0.135
3151641KERR 7
50/50
0.135
971447AH1-217 GEN
Solar/Wind Harmer
8.145
971845AH1-439 GEN
Solar/Wind Harmer
11.716
970285AG2-188 GEN
Solar/Wind Harmer
19.851
270494AE1-108_GEN
Solar/Wind Harmer
2.723
315657AE1-056 GEN
Solar/Wind Harmer
5.462
946301AF1-294 GEN
Solar/Wind Harmer
2.936
961791AG1-021 GEN
Solar/Wind Harmer
1.429
970683AG2-441 GEN
Solar/Wind Harmer
9.008
970681AG2-440 GEN
Solar/Wind Harmer
7.206
3144303KENBRDG
Solar/Wind Harmer
0.096
971443AH1-215 GEN
Solar/Wind Harmer
2.005
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.188
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.069
3147243WELCO
Solar/Wind Harmer
0.043
970865AG2-541 GEN
Solar/Wind Harmer
2.13
316123AC1-075 GEN
Solar/Wind Harmer
0.077
970165AG2-112 GEN
Solar/Wind Harmer
0.459
970163AG2-111 GEN
Solar/Wind Harmer
0.438
316233AE1-074 FULL
Solar/Wind Helper
0.38
316312AB1-027
Solar/Wind Helper
0.217
316132AB2-190 GEN1
Solar/Wind Helper
0.639
3151931BEARGRDN S1
50/50
3.828
3151911BEARGRDN G1
50/50
2.966
3144293JTRSVLE
50/50
0.503
3151531CLOVER1
50/50
2.188
3151601KERR 3
50/50
0.135
3151581KERR 1
50/50
0.048
970937AG2-583 GEN
Solar/Wind Harmer
28.699
972003AH1-546 GEN
Solar/Wind Harmer
13.118
971377AH1-170 GEN
Solar/Wind Harmer
3.027
3147623JAMES R
Solar/Wind Harmer
0.658
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
963171AG1-166 GEN
Solar/Wind Harmer
0.794
971563AH1-280 GEN
Solar/Wind Harmer
1.587
970685AG2-442 GEN
Solar/Wind Harmer
10.089
962491AG1-098 GEN
Solar/Wind Harmer
7.03
315693AD1-088 GEN
Solar/Wind Harmer
5.777
957481AF2-042 GEN
Solar/Wind Harmer
29.163
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.003
970401AG2-262 GEN
Solar/Wind Harmer
0.451
316003AC1-222 GEN
Solar/Wind Harmer
0.002
316336AC2-165 C
Solar/Wind Helper
5.135
3143226MDLTHAN
Solar/Wind Helper
0.3
3143526WINTERP
Solar/Wind Helper
1.294
3142543TWELFTH
Solar/Wind Helper
0.014
3142416OLDCHRC
Solar/Wind Helper
0.296
3142416OLDCHRC
Solar/Wind Helper
0.113
316458AB2-190 GEN2
Solar/Wind Helper
0.639
LAGNLTFEXP_LAGN->PJM
CLTF
1.406
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.581
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
1.069
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.04
TVALTFEXP_TVA->PJM
CLTF
0.731
SIGELTFEXP_SIGE->PJM
CLTF
0.035
NYPJM->LTFIMP_NY
CLTF
0.331
LGEELTFEXP_LGEE->PJM
CLTF
0.459
WECLTFEXP_WEC->PJM
CLTF
0.235
CPLELTFEXP_CPLE->PJM
CLTF
0.611
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.053

Details for AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2028T2054_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.14 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1118.59
MW Contribution:30.73
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.901
3151911BEARGRDN G1
50/50
4.573
3144293JTRSVLE
50/50
0.618
970937AG2-583 GEN
Solar/Wind Harmer
49.358
972003AH1-546 GEN
Solar/Wind Harmer
26.402
971377AH1-170 GEN
Solar/Wind Harmer
6.146
3147623JAMES R
Solar/Wind Harmer
0.761
316322AB2-045
Solar/Wind Harmer
1.43
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
963171AG1-166 GEN
Solar/Wind Harmer
2.57
971563AH1-280 GEN
Solar/Wind Harmer
2.57
970685AG2-442 GEN
Solar/Wind Harmer
15.938
316237AB2-079_GEN
Solar/Wind Harmer
0.296
962491AG1-098 GEN
Solar/Wind Harmer
6.43
315693AD1-088 GEN
Solar/Wind Harmer
4.464
970401AG2-262 GEN
Solar/Wind Harmer
0.496
962751AG1-124 GEN
Solar/Wind Harmer
4.423
316336AC2-165 C
Solar/Wind Helper
3.979
3143226MDLTHAN
Solar/Wind Helper
0.215
3143526WINTERP
Solar/Wind Helper
0.909
3151921BEARGRDN G2
50/50
4.573
3144293JTRSVLE
50/50
0.618
970221AG2-151 GEN
Solar/Wind Harmer
30.731
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.035
970909AG2-566 GEN
Solar/Wind Harmer
2.11
3147133PAMPLIN
Solar/Wind Harmer
-0.069
971193AH1-056 GEN
Solar/Wind Harmer
13.876
963181AG1-167 GEN
Solar/Wind Harmer
1.928
959311AF2-222 GEN
Solar/Wind Harmer
17.157
958131AF2-107 GEN
Solar/Wind Harmer
5.552
970257AG2-171 GEN
Solar/Wind Harmer
5.895
315785AD2-033 C
Solar/Wind Harmer
3.34
964241AG1-285 GEN
Solar/Wind Harmer
9.463
316131AB2-060 GEN
Solar/Wind Harmer
1.135
316313AB2-026
Solar/Wind Helper
0.959
316258AE1-075 C
Solar/Wind Helper
0.863
316405AF2-144 C
Solar/Wind Helper
0.719
972205AH1-687 GEN
50/50
22.302
971447AH1-217 GEN
Solar/Wind Harmer
16.384
971845AH1-439 GEN
Solar/Wind Harmer
22.121
970285AG2-188 GEN
Solar/Wind Harmer
34.956
270494AE1-108_GEN
Solar/Wind Harmer
10.113
315657AE1-056 GEN
Solar/Wind Harmer
8.325
946301AF1-294 GEN
Solar/Wind Harmer
5.269
961791AG1-021 GEN
Solar/Wind Harmer
2.57
970683AG2-441 GEN
Solar/Wind Harmer
14.23
970681AG2-440 GEN
Solar/Wind Harmer
11.384
3144303KENBRDG
Solar/Wind Harmer
-0.013
971443AH1-215 GEN
Solar/Wind Harmer
3.053
316239AB2-077_GEN
Solar/Wind Harmer
0.296
316238AB2-078_GEN
Solar/Wind Harmer
0.296
316118AC1-105 GEN
Solar/Wind Harmer
0.458
316233AE1-074 FULL
Solar/Wind Helper
0.267
3144293JTRSVLE
50/50
0.618
3144293JTRSVLE
50/50
0.521
971489AH1-241 GEN
Solar/Wind Harmer
29.175
3146776BUCKING
Solar/Wind Harmer
-0.169
3146776BUCKING
Solar/Wind Harmer
-0.014
315821AE2-092 GEN
Solar/Wind Harmer
6.931
970301AG2-198 GEN
Solar/Wind Harmer
11.113
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.213
963191AG1-168 GEN
Solar/Wind Harmer
1.928
971741AH1-377 GEN
Solar/Wind Harmer
22.291
316034AC1-036 C
Solar/Wind Harmer
0.292
970323AG2-213 GEN
Solar/Wind Harmer
7.861
971775AH1-396 GEN
Solar/Wind Harmer
1.119
313527AB2-043 GEN
Solar/Wind Harmer
1.646
962561AG1-105 GEN
Solar/Wind Harmer
4.489
964791AG1-342 GEN
Solar/Wind Harmer
1.622
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
939181AE1-148 GEN
Solar/Wind Harmer
4.018
3143526WINTERP
Solar/Wind Helper
0.909
LAGNLTFEXP_LAGN->PJM
CLTF
1.429
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.277
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.604
MECLTFEXP_MEC->PJM
CLTF
0.866
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.252
TVALTFEXP_TVA->PJM
CLTF
0.733
SIGELTFEXP_SIGE->PJM
CLTF
0.027
CPLELTFEXP_CPLE->PJM
CLTF
1.307
NYPJM->LTFIMP_NY
CLTF
0.421
LGEELTFEXP_LGEE->PJM
CLTF
0.351
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.286
WECLTFEXP_WEC->PJM
CLTF
0.177

Details for AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 233T2028_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.41 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1101.63
MW Contribution:30.69
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.898
3151911BEARGRDN G1
50/50
4.57
3144293JTRSVLE
50/50
0.618
970937AG2-583 GEN
Solar/Wind Harmer
49.351
972003AH1-546 GEN
Solar/Wind Harmer
26.389
971377AH1-170 GEN
Solar/Wind Harmer
6.139
3147623JAMES R
Solar/Wind Harmer
0.76
316322AB2-045
Solar/Wind Harmer
1.43
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
963171AG1-166 GEN
Solar/Wind Harmer
2.57
971563AH1-280 GEN
Solar/Wind Harmer
2.57
970685AG2-442 GEN
Solar/Wind Harmer
15.936
316237AB2-079_GEN
Solar/Wind Harmer
0.296
962491AG1-098 GEN
Solar/Wind Harmer
6.439
315693AD1-088 GEN
Solar/Wind Harmer
4.471
970401AG2-262 GEN
Solar/Wind Harmer
0.495
962751AG1-124 GEN
Solar/Wind Harmer
4.364
316336AC2-165 C
Solar/Wind Helper
3.978
3143226MDLTHAN
Solar/Wind Helper
0.214
3143526WINTERP
Solar/Wind Helper
0.905
3151921BEARGRDN G2
50/50
4.57
3144293JTRSVLE
50/50
0.618
970221AG2-151 GEN
Solar/Wind Harmer
30.694
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.034
970909AG2-566 GEN
Solar/Wind Harmer
2.11
3147133PAMPLIN
Solar/Wind Harmer
-0.069
971193AH1-056 GEN
Solar/Wind Harmer
13.873
963181AG1-167 GEN
Solar/Wind Harmer
1.927
959311AF2-222 GEN
Solar/Wind Harmer
17.156
958131AF2-107 GEN
Solar/Wind Harmer
5.522
970257AG2-171 GEN
Solar/Wind Harmer
5.895
315785AD2-033 C
Solar/Wind Harmer
3.339
964241AG1-285 GEN
Solar/Wind Harmer
9.464
316131AB2-060 GEN
Solar/Wind Harmer
1.135
316313AB2-026
Solar/Wind Helper
0.959
316258AE1-075 C
Solar/Wind Helper
0.862
316405AF2-144 C
Solar/Wind Helper
0.719
972205AH1-687 GEN
50/50
22.291
971447AH1-217 GEN
Solar/Wind Harmer
16.353
971845AH1-439 GEN
Solar/Wind Harmer
22.112
970285AG2-188 GEN
Solar/Wind Harmer
34.943
270494AE1-108_GEN
Solar/Wind Harmer
10.095
315657AE1-056 GEN
Solar/Wind Harmer
8.324
946301AF1-294 GEN
Solar/Wind Harmer
5.268
961791AG1-021 GEN
Solar/Wind Harmer
2.57
970683AG2-441 GEN
Solar/Wind Harmer
14.229
970681AG2-440 GEN
Solar/Wind Harmer
11.383
3144303KENBRDG
Solar/Wind Harmer
-0.013
971443AH1-215 GEN
Solar/Wind Harmer
3.053
316239AB2-077_GEN
Solar/Wind Harmer
0.296
316238AB2-078_GEN
Solar/Wind Harmer
0.296
316118AC1-105 GEN
Solar/Wind Harmer
0.458
316233AE1-074 FULL
Solar/Wind Helper
0.266
3144293JTRSVLE
50/50
0.618
3144293JTRSVLE
50/50
0.521
971489AH1-241 GEN
Solar/Wind Harmer
29.14
3146776BUCKING
Solar/Wind Harmer
-0.169
3146776BUCKING
Solar/Wind Harmer
-0.014
315821AE2-092 GEN
Solar/Wind Harmer
6.892
970301AG2-198 GEN
Solar/Wind Harmer
11.114
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.212
963191AG1-168 GEN
Solar/Wind Harmer
1.927
971741AH1-377 GEN
Solar/Wind Harmer
22.295
316034AC1-036 C
Solar/Wind Harmer
0.292
970323AG2-213 GEN
Solar/Wind Harmer
7.86
971775AH1-396 GEN
Solar/Wind Harmer
1.119
313527AB2-043 GEN
Solar/Wind Harmer
1.646
962561AG1-105 GEN
Solar/Wind Harmer
4.487
964791AG1-342 GEN
Solar/Wind Harmer
1.621
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
939181AE1-148 GEN
Solar/Wind Harmer
4.02
3143526WINTERP
Solar/Wind Helper
0.905
LAGNLTFEXP_LAGN->PJM
CLTF
1.371
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.897
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.492
MECLTFEXP_MEC->PJM
CLTF
0.819
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.188
TVALTFEXP_TVA->PJM
CLTF
0.704
SIGELTFEXP_SIGE->PJM
CLTF
0.026
CPLELTFEXP_CPLE->PJM
CLTF
1.294
NYPJM->LTFIMP_NY
CLTF
0.406
LGEELTFEXP_LGEE->PJM
CLTF
0.331
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.906
WECLTFEXP_WEC->PJM
CLTF
0.166

Details for AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2193_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2028T2193_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.29 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1100.44
MW Contribution:29.42
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.972
3151911BEARGRDN G1
50/50
4.627
3144293JTRSVLE
50/50
0.627
970937AG2-583 GEN
Solar/Wind Harmer
49.759
972003AH1-546 GEN
Solar/Wind Harmer
26.719
971377AH1-170 GEN
Solar/Wind Harmer
5.885
3147623JAMES R
Solar/Wind Harmer
0.728
316322AB2-045
Solar/Wind Harmer
1.448
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
963171AG1-166 GEN
Solar/Wind Harmer
2.607
971563AH1-280 GEN
Solar/Wind Harmer
2.607
970685AG2-442 GEN
Solar/Wind Harmer
16.168
316237AB2-079_GEN
Solar/Wind Harmer
0.301
962491AG1-098 GEN
Solar/Wind Harmer
6.56
315693AD1-088 GEN
Solar/Wind Harmer
4.557
970401AG2-262 GEN
Solar/Wind Harmer
0.503
962751AG1-124 GEN
Solar/Wind Harmer
4.196
316336AC2-165 C
Solar/Wind Helper
3.937
3143226MDLTHAN
Solar/Wind Helper
0.212
3143526WINTERP
Solar/Wind Helper
0.892
3151921BEARGRDN G2
50/50
4.627
3144293JTRSVLE
50/50
0.627
970221AG2-151 GEN
Solar/Wind Harmer
29.423
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.089
970909AG2-566 GEN
Solar/Wind Harmer
2.141
3147133PAMPLIN
Solar/Wind Harmer
-0.07
971193AH1-056 GEN
Solar/Wind Harmer
14.068
963181AG1-167 GEN
Solar/Wind Harmer
1.955
959311AF2-222 GEN
Solar/Wind Harmer
17.41
970257AG2-171 GEN
Solar/Wind Harmer
5.984
958131AF2-107 GEN
Solar/Wind Harmer
5.299
315785AD2-033 C
Solar/Wind Harmer
3.39
964241AG1-285 GEN
Solar/Wind Harmer
9.615
316131AB2-060 GEN
Solar/Wind Harmer
1.154
316313AB2-026
Solar/Wind Helper
0.949
316258AE1-075 C
Solar/Wind Helper
0.854
316405AF2-144 C
Solar/Wind Helper
0.711
972205AH1-687 GEN
50/50
22.568
971447AH1-217 GEN
Solar/Wind Harmer
15.499
971845AH1-439 GEN
Solar/Wind Harmer
22.397
970285AG2-188 GEN
Solar/Wind Harmer
35.395
270494AE1-108_GEN
Solar/Wind Harmer
9.679
315657AE1-056 GEN
Solar/Wind Harmer
8.441
946301AF1-294 GEN
Solar/Wind Harmer
5.344
961791AG1-021 GEN
Solar/Wind Harmer
2.607
970683AG2-441 GEN
Solar/Wind Harmer
14.436
970681AG2-440 GEN
Solar/Wind Harmer
11.549
3144303KENBRDG
Solar/Wind Harmer
-0.013
971443AH1-215 GEN
Solar/Wind Harmer
3.098
316239AB2-077_GEN
Solar/Wind Harmer
0.301
316238AB2-078_GEN
Solar/Wind Harmer
0.301
316118AC1-105 GEN
Solar/Wind Harmer
0.465
316233AE1-074 FULL
Solar/Wind Helper
0.262
3144293JTRSVLE
50/50
0.627
3144293JTRSVLE
50/50
0.528
971489AH1-241 GEN
Solar/Wind Harmer
27.933
3146776BUCKING
Solar/Wind Harmer
-0.171
3146776BUCKING
Solar/Wind Harmer
-0.014
315821AE2-092 GEN
Solar/Wind Harmer
6.525
970301AG2-198 GEN
Solar/Wind Harmer
11.274
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.258
963191AG1-168 GEN
Solar/Wind Harmer
1.955
971741AH1-377 GEN
Solar/Wind Harmer
22.629
316034AC1-036 C
Solar/Wind Harmer
0.297
970323AG2-213 GEN
Solar/Wind Harmer
7.978
971775AH1-396 GEN
Solar/Wind Harmer
1.136
313527AB2-043 GEN
Solar/Wind Harmer
1.674
962561AG1-105 GEN
Solar/Wind Harmer
4.561
964791AG1-342 GEN
Solar/Wind Harmer
1.647
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
939181AE1-148 GEN
Solar/Wind Harmer
4.097
3143526WINTERP
Solar/Wind Helper
0.892
LAGNLTFEXP_LAGN->PJM
CLTF
1.355
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.454
MECLTFEXP_MEC->PJM
CLTF
0.798
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.224
TVALTFEXP_TVA->PJM
CLTF
0.694
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
1.323
NYPJM->LTFIMP_NY
CLTF
0.404
LGEELTFEXP_LGEE->PJM
CLTF
0.321
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.76
WECLTFEXP_WEC->PJM
CLTF
0.161

Details for AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: WT2193_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT2193_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.27 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1100.22
MW Contribution:29.42
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.627
3144293JTRSVLE
50/50
0.528
971489AH1-241 GEN
Solar/Wind Harmer
27.933
3146776BUCKING
Solar/Wind Harmer
-0.171
3146776BUCKING
Solar/Wind Harmer
-0.014
315821AE2-092 GEN
Solar/Wind Harmer
6.525
970301AG2-198 GEN
Solar/Wind Harmer
11.274
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.258
963191AG1-168 GEN
Solar/Wind Harmer
1.955
971741AH1-377 GEN
Solar/Wind Harmer
22.629
316034AC1-036 C
Solar/Wind Harmer
0.297
970323AG2-213 GEN
Solar/Wind Harmer
7.978
971775AH1-396 GEN
Solar/Wind Harmer
1.136
313527AB2-043 GEN
Solar/Wind Harmer
1.674
962561AG1-105 GEN
Solar/Wind Harmer
4.561
964791AG1-342 GEN
Solar/Wind Harmer
1.647
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
939181AE1-148 GEN
Solar/Wind Harmer
4.097
3143526WINTERP
Solar/Wind Helper
0.892
3151921BEARGRDN G2
50/50
4.627
3144293JTRSVLE
50/50
0.627
970221AG2-151 GEN
Solar/Wind Harmer
29.423
3146776BUCKING
Solar/Wind Harmer
-0.015
3151931BEARGRDN S1
50/50
5.972
3151911BEARGRDN G1
50/50
4.627
3144293JTRSVLE
50/50
0.627
970937AG2-583 GEN
Solar/Wind Harmer
49.759
972003AH1-546 GEN
Solar/Wind Harmer
26.719
971377AH1-170 GEN
Solar/Wind Harmer
5.885
3147623JAMES R
Solar/Wind Harmer
0.728
316322AB2-045
Solar/Wind Harmer
1.448
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
963171AG1-166 GEN
Solar/Wind Harmer
2.607
971563AH1-280 GEN
Solar/Wind Harmer
2.607
970685AG2-442 GEN
Solar/Wind Harmer
16.168
316237AB2-079_GEN
Solar/Wind Harmer
0.301
962491AG1-098 GEN
Solar/Wind Harmer
6.56
315693AD1-088 GEN
Solar/Wind Harmer
4.557
970401AG2-262 GEN
Solar/Wind Harmer
0.503
962751AG1-124 GEN
Solar/Wind Harmer
4.196
316336AC2-165 C
Solar/Wind Helper
3.937
3143226MDLTHAN
Solar/Wind Helper
0.212
3143526WINTERP
Solar/Wind Helper
0.892
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.089
970909AG2-566 GEN
Solar/Wind Harmer
2.141
3147133PAMPLIN
Solar/Wind Harmer
-0.07
971193AH1-056 GEN
Solar/Wind Harmer
14.068
963181AG1-167 GEN
Solar/Wind Harmer
1.955
959311AF2-222 GEN
Solar/Wind Harmer
17.41
970257AG2-171 GEN
Solar/Wind Harmer
5.984
958131AF2-107 GEN
Solar/Wind Harmer
5.299
315785AD2-033 C
Solar/Wind Harmer
3.39
964241AG1-285 GEN
Solar/Wind Harmer
9.615
316131AB2-060 GEN
Solar/Wind Harmer
1.154
316313AB2-026
Solar/Wind Helper
0.949
316258AE1-075 C
Solar/Wind Helper
0.854
316405AF2-144 C
Solar/Wind Helper
0.711
972205AH1-687 GEN
50/50
22.568
971447AH1-217 GEN
Solar/Wind Harmer
15.499
971845AH1-439 GEN
Solar/Wind Harmer
22.397
970285AG2-188 GEN
Solar/Wind Harmer
35.395
270494AE1-108_GEN
Solar/Wind Harmer
9.679
315657AE1-056 GEN
Solar/Wind Harmer
8.441
946301AF1-294 GEN
Solar/Wind Harmer
5.344
961791AG1-021 GEN
Solar/Wind Harmer
2.607
970683AG2-441 GEN
Solar/Wind Harmer
14.436
970681AG2-440 GEN
Solar/Wind Harmer
11.549
3144303KENBRDG
Solar/Wind Harmer
-0.013
971443AH1-215 GEN
Solar/Wind Harmer
3.098
316239AB2-077_GEN
Solar/Wind Harmer
0.301
316238AB2-078_GEN
Solar/Wind Harmer
0.301
316118AC1-105 GEN
Solar/Wind Harmer
0.465
316233AE1-074 FULL
Solar/Wind Helper
0.262
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.454
MECLTFEXP_MEC->PJM
CLTF
0.798
LAGNLTFEXP_LAGN->PJM
CLTF
1.355
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.224
TVALTFEXP_TVA->PJM
CLTF
0.694
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
1.323
NYPJM->LTFIMP_NY
CLTF
0.404
LGEELTFEXP_LGEE->PJM
CLTF
0.321
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.76
WECLTFEXP_WEC->PJM
CLTF
0.161

Details for AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 202872_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 202872_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.95 %
Rating:980.0 MVA
Rating Type:C
MVA to Mitigate:1097.1
MW Contribution:29.42
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.972
3151911BEARGRDN G1
50/50
4.627
3144293JTRSVLE
50/50
0.627
970937AG2-583 GEN
Solar/Wind Harmer
49.759
972003AH1-546 GEN
Solar/Wind Harmer
26.719
971377AH1-170 GEN
Solar/Wind Harmer
5.885
3147623JAMES R
Solar/Wind Harmer
0.728
316322AB2-045
Solar/Wind Harmer
1.448
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.019
963171AG1-166 GEN
Solar/Wind Harmer
2.607
971563AH1-280 GEN
Solar/Wind Harmer
2.607
970685AG2-442 GEN
Solar/Wind Harmer
16.168
316237AB2-079_GEN
Solar/Wind Harmer
0.301
962491AG1-098 GEN
Solar/Wind Harmer
6.56
315693AD1-088 GEN
Solar/Wind Harmer
4.557
970401AG2-262 GEN
Solar/Wind Harmer
0.503
962751AG1-124 GEN
Solar/Wind Harmer
4.196
316336AC2-165 C
Solar/Wind Helper
3.937
3143226MDLTHAN
Solar/Wind Helper
0.212
3143526WINTERP
Solar/Wind Helper
0.892
3151921BEARGRDN G2
50/50
4.627
3144293JTRSVLE
50/50
0.627
970221AG2-151 GEN
Solar/Wind Harmer
29.423
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.089
970909AG2-566 GEN
Solar/Wind Harmer
2.141
3147133PAMPLIN
Solar/Wind Harmer
-0.07
971193AH1-056 GEN
Solar/Wind Harmer
14.068
963181AG1-167 GEN
Solar/Wind Harmer
1.955
959311AF2-222 GEN
Solar/Wind Harmer
17.41
970257AG2-171 GEN
Solar/Wind Harmer
5.984
958131AF2-107 GEN
Solar/Wind Harmer
5.299
315785AD2-033 C
Solar/Wind Harmer
3.39
964241AG1-285 GEN
Solar/Wind Harmer
9.615
316131AB2-060 GEN
Solar/Wind Harmer
1.154
316313AB2-026
Solar/Wind Helper
0.949
972205AH1-687 GEN
50/50
22.568
971447AH1-217 GEN
Solar/Wind Harmer
15.499
971845AH1-439 GEN
Solar/Wind Harmer
22.397
970285AG2-188 GEN
Solar/Wind Harmer
35.395
270494AE1-108_GEN
Solar/Wind Harmer
9.679
315657AE1-056 GEN
Solar/Wind Harmer
8.441
946301AF1-294 GEN
Solar/Wind Harmer
5.344
961791AG1-021 GEN
Solar/Wind Harmer
2.607
970683AG2-441 GEN
Solar/Wind Harmer
14.436
970681AG2-440 GEN
Solar/Wind Harmer
11.549
3144303KENBRDG
Solar/Wind Harmer
-0.013
971443AH1-215 GEN
Solar/Wind Harmer
3.098
316239AB2-077_GEN
Solar/Wind Harmer
0.301
316238AB2-078_GEN
Solar/Wind Harmer
0.301
316118AC1-105 GEN
Solar/Wind Harmer
0.465
316233AE1-074 FULL
Solar/Wind Helper
0.262
3144293JTRSVLE
50/50
0.627
3144293JTRSVLE
50/50
0.528
971489AH1-241 GEN
Solar/Wind Harmer
27.933
3146776BUCKING
Solar/Wind Harmer
-0.171
3146776BUCKING
Solar/Wind Harmer
-0.014
315821AE2-092 GEN
Solar/Wind Harmer
6.525
970301AG2-198 GEN
Solar/Wind Harmer
11.274
3147133PAMPLIN
Solar/Wind Harmer
-0.022
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.258
963191AG1-168 GEN
Solar/Wind Harmer
1.955
971741AH1-377 GEN
Solar/Wind Harmer
22.629
316034AC1-036 C
Solar/Wind Harmer
0.297
970323AG2-213 GEN
Solar/Wind Harmer
7.978
971775AH1-396 GEN
Solar/Wind Harmer
1.136
313527AB2-043 GEN
Solar/Wind Harmer
1.674
962561AG1-105 GEN
Solar/Wind Harmer
4.561
964791AG1-342 GEN
Solar/Wind Harmer
1.647
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
939181AE1-148 GEN
Solar/Wind Harmer
4.097
3143526WINTERP
Solar/Wind Helper
0.892
316258AE1-075 C
Solar/Wind Helper
0.854
316405AF2-144 C
Solar/Wind Helper
0.711
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.454
MECLTFEXP_MEC->PJM
CLTF
0.798
LAGNLTFEXP_LAGN->PJM
CLTF
1.355
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.224
TVALTFEXP_TVA->PJM
CLTF
0.694
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
1.323
NYPJM->LTFIMP_NY
CLTF
0.404
LGEELTFEXP_LGEE->PJM
CLTF
0.321
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.76
WECLTFEXP_WEC->PJM
CLTF
0.161

Details for AH1-012 TP-6SOUTH HALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2199_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
AH1-012 TP-6SOUTH HALL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2199_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:147.17 %
Rating:819.68 MVA
Rating Type:B
MVA to Mitigate:1206.36
MW Contribution:4.15
Bus #Bus NameTypeMW Contribution
3151791S ANNAG2
50/50
1.911
3151781S ANNAS1
50/50
0.982
3151741LOISA C
50/50
1.992
3151751LOISA D
50/50
36.435
3151931BEARGRDN S1
50/50
0.956
3151911BEARGRDN G1
50/50
0.741
3147666LOUISA
Solar/Wind Harmer
3.006
316192AB2-158 GEN
Solar/Wind Harmer
4.18
971133AH1-012 GEN
50/50
15.027
3151731LOISA B
50/50
36.435
3151721LOISA A
50/50
36.247
966001AG1-469 GEN
Solar/Wind Harmer
0.277
315651AD1-115 GEN
Solar/Wind Harmer
0.004
971489AH1-241 GEN
Solar/Wind Harmer
4.148
315821AE2-092 GEN
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.24
3146776BUCKING
Solar/Wind Harmer
0.019
972205AH1-687 GEN
50/50
3.614
3147346CASHSCORNER
Solar/Wind Harmer
1.128
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3138266HYDRAULIC
Solar/Wind Harmer
0.004
316164AC1-076 GEN
Solar/Wind Harmer
0.13
971447AH1-217 GEN
Solar/Wind Harmer
2.371
3148133STUARTS
Solar/Wind Harmer
0.044
3148013FISHERV
Solar/Wind Harmer
0.042
270494AE1-108_GEN
Solar/Wind Harmer
0.774
971845AH1-439 GEN
Solar/Wind Harmer
2.662
315683AE1-153 C
Solar/Wind Harmer
41.15
316254AC1-120 GEN1
Solar/Wind Harmer
0.299
971377AH1-170 GEN
Solar/Wind Harmer
0.83
3147623JAMES R
Solar/Wind Harmer
0.18
972003AH1-546 GEN
Solar/Wind Harmer
3.234
970937AG2-583 GEN
Solar/Wind Harmer
3.695
316322AB2-045
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.024
3151771S ANNAG1
50/50
1.911
3151801S ANNAS2
50/50
0.982
3151761LOISA E
50/50
74.281
972183AH1-676 GEN
50/50
587.315
3151921BEARGRDN G2
50/50
0.741
3147666LOUISA
Solar/Wind Harmer
1.729
3132273ORANGE
Solar/Wind Harmer
0.067
316170AC1-121 GEN2
Solar/Wind Harmer
0.15
970221AG2-151 GEN
Solar/Wind Harmer
4.148
3148013FISHERV
Solar/Wind Harmer
0.074
3146776BUCKING
Solar/Wind Harmer
0.022
LAGNLTFEXP_LAGN->PJM
CLTF
0.977
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.963
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.899
MECLTFEXP_MEC->PJM
CLTF
0.75
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.184
TVALTFEXP_TVA->PJM
CLTF
0.512
NYPJM->LTFIMP_NY
CLTF
0.406
LGEELTFEXP_LGEE->PJM
CLTF
0.327
WECLTFEXP_WEC->PJM
CLTF
0.165
CPLELTFEXP_CPLE->PJM
CLTF
0.264
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.337

Details for AH1-012 TP-6SOUTH HALL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
AH1-012 TP-6SOUTH HALL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:143.81 %
Rating:1003.0 MVA
Rating Type:C
MVA to Mitigate:1442.37
MW Contribution:6.3
Bus #Bus NameTypeMW Contribution
971133AH1-012 GEN
50/50
15.525
3151731LOISA B
50/50
41
3151721LOISA A
50/50
40.788
966001AG1-469 GEN
Solar/Wind Harmer
1.242
971489AH1-241 GEN
Solar/Wind Harmer
5.982
315821AE2-092 GEN
Solar/Wind Harmer
2.06
3147346CASHSCORNER
Solar/Wind Harmer
0.957
3151791S ANNAG2
50/50
2.136
3151781S ANNAS1
50/50
1.098
3151741LOISA C
50/50
2.242
3151751LOISA D
50/50
41
3147666LOUISA
Solar/Wind Harmer
-0.354
316192AB2-158 GEN
Solar/Wind Harmer
10.429
315683AE1-153 C
Solar/Wind Harmer
61.252
971377AH1-170 GEN
Solar/Wind Harmer
1.26
3147623JAMES R
Solar/Wind Harmer
0.156
972003AH1-546 GEN
Solar/Wind Harmer
4.933
970937AG2-583 GEN
Solar/Wind Harmer
5.684
316322AB2-045
Solar/Wind Harmer
0.265
3146776BUCKING
Solar/Wind Harmer
-0.003
315705AF1-075 GEN
Solar/Wind Harmer
2.892
3151771S ANNAG1
50/50
2.136
3151801S ANNAS2
50/50
1.098
3151761LOISA E
50/50
83.586
972183AH1-676 GEN
50/50
663.972
3147666LOUISA
Solar/Wind Harmer
-0.203
970221AG2-151 GEN
Solar/Wind Harmer
6.301
3148013FISHERV
Solar/Wind Harmer
-0.009
3146776BUCKING
Solar/Wind Harmer
-0.003
316499AE2-029_GEN
Solar/Wind Harmer
0.518
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
972205AH1-687 GEN
Adder
3.933
971447AH1-217 GEN
Solar/Wind Harmer
3.598
3148133STUARTS
Solar/Wind Harmer
-0.006
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
2.18
971845AH1-439 GEN
Solar/Wind Harmer
4.09
970285AG2-188 GEN
Solar/Wind Harmer
6.451
3146776BUCKING
Solar/Wind Harmer
-0.031
3146776BUCKING
Solar/Wind Harmer
-0.003
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.172
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.363
MECLTFEXP_MEC->PJM
CLTF
0.912
LAGNLTFEXP_LAGN->PJM
CLTF
1.228
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.694
TVALTFEXP_TVA->PJM
CLTF
0.641
SIGELTFEXP_SIGE->PJM
CLTF
0.03
CPLELTFEXP_CPLE->PJM
CLTF
0.459
NYPJM->LTFIMP_NY
CLTF
0.489
LGEELTFEXP_LGEE->PJM
CLTF
0.394
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.833
WECLTFEXP_WEC->PJM
CLTF
0.198

Details for AH1-012 TP-6SOUTH HALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2331_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-012 TP-6SOUTH HALL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2331_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:142.44 %
Rating:819.68 MVA
Rating Type:B
MVA to Mitigate:1167.53
MW Contribution:4.15
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
3.614
3147346CASHSCORNER
Solar/Wind Harmer
1.128
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3138266HYDRAULIC
Solar/Wind Harmer
0.004
316164AC1-076 GEN
Solar/Wind Harmer
0.13
971447AH1-217 GEN
Solar/Wind Harmer
2.371
3148133STUARTS
Solar/Wind Harmer
0.044
3148013FISHERV
Solar/Wind Harmer
0.042
270494AE1-108_GEN
Solar/Wind Harmer
0.774
971845AH1-439 GEN
Solar/Wind Harmer
2.662
971133AH1-012 GEN
50/50
15.027
3151731LOISA B
50/50
36.435
3151721LOISA A
50/50
36.247
966001AG1-469 GEN
Solar/Wind Harmer
0.277
315651AD1-115 GEN
Solar/Wind Harmer
0.004
971489AH1-241 GEN
Solar/Wind Harmer
4.148
315821AE2-092 GEN
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.24
3146776BUCKING
Solar/Wind Harmer
0.019
3151771S ANNAG1
50/50
1.911
3151801S ANNAS2
50/50
0.982
3151761LOISA E
50/50
74.281
972183AH1-676 GEN
50/50
587.315
3151921BEARGRDN G2
50/50
0.741
3147666LOUISA
Solar/Wind Harmer
1.729
3132273ORANGE
Solar/Wind Harmer
0.067
316170AC1-121 GEN2
Solar/Wind Harmer
0.15
970221AG2-151 GEN
Solar/Wind Harmer
4.148
3148013FISHERV
Solar/Wind Harmer
0.074
3146776BUCKING
Solar/Wind Harmer
0.022
3151791S ANNAG2
50/50
1.911
3151781S ANNAS1
50/50
0.982
3151741LOISA C
50/50
1.992
3151751LOISA D
50/50
36.435
3151931BEARGRDN S1
50/50
0.956
3151911BEARGRDN G1
50/50
0.741
3147666LOUISA
Solar/Wind Harmer
3.006
316192AB2-158 GEN
Solar/Wind Harmer
4.18
315683AE1-153 C
Solar/Wind Harmer
41.15
316254AC1-120 GEN1
Solar/Wind Harmer
0.299
971377AH1-170 GEN
Solar/Wind Harmer
0.83
3147623JAMES R
Solar/Wind Harmer
0.18
972003AH1-546 GEN
Solar/Wind Harmer
3.234
970937AG2-583 GEN
Solar/Wind Harmer
3.695
316322AB2-045
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.024
LAGNLTFEXP_LAGN->PJM
CLTF
0.977
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.963
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.899
MECLTFEXP_MEC->PJM
CLTF
0.75
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.184
TVALTFEXP_TVA->PJM
CLTF
0.512
NYPJM->LTFIMP_NY
CLTF
0.406
LGEELTFEXP_LGEE->PJM
CLTF
0.327
WECLTFEXP_WEC->PJM
CLTF
0.165
CPLELTFEXP_CPLE->PJM
CLTF
0.264
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.337

Details for AH1-012 TP-6SOUTH HALL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
AH1-012 TP-6SOUTH HALL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:137.71 %
Rating:1003.0 MVA
Rating Type:C
MVA to Mitigate:1381.19
MW Contribution:6.3
Bus #Bus NameTypeMW Contribution
3151771S ANNAG1
50/50
2.136
3151801S ANNAS2
50/50
1.098
3151761LOISA E
50/50
83.586
972183AH1-676 GEN
50/50
663.972
3147666LOUISA
Solar/Wind Harmer
-0.203
970221AG2-151 GEN
Solar/Wind Harmer
6.301
3148013FISHERV
Solar/Wind Harmer
-0.009
3146776BUCKING
Solar/Wind Harmer
-0.003
316499AE2-029_GEN
Solar/Wind Harmer
0.518
971133AH1-012 GEN
50/50
15.525
3151731LOISA B
50/50
41
3151721LOISA A
50/50
40.788
966001AG1-469 GEN
Solar/Wind Harmer
1.242
971489AH1-241 GEN
Solar/Wind Harmer
5.982
315821AE2-092 GEN
Solar/Wind Harmer
2.06
3146776BUCKING
Solar/Wind Harmer
-0.031
3146776BUCKING
Solar/Wind Harmer
-0.003
3147346CASHSCORNER
Solar/Wind Harmer
0.957
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
972205AH1-687 GEN
Adder
3.933
971447AH1-217 GEN
Solar/Wind Harmer
3.598
3148133STUARTS
Solar/Wind Harmer
-0.006
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
2.18
971845AH1-439 GEN
Solar/Wind Harmer
4.09
970285AG2-188 GEN
Solar/Wind Harmer
6.451
3151791S ANNAG2
50/50
2.136
3151781S ANNAS1
50/50
1.098
3151741LOISA C
50/50
2.242
3151751LOISA D
50/50
41
3147666LOUISA
Solar/Wind Harmer
-0.354
316192AB2-158 GEN
Solar/Wind Harmer
10.429
971377AH1-170 GEN
Solar/Wind Harmer
1.26
3147623JAMES R
Solar/Wind Harmer
0.156
972003AH1-546 GEN
Solar/Wind Harmer
4.933
970937AG2-583 GEN
Solar/Wind Harmer
5.684
316322AB2-045
Solar/Wind Harmer
0.265
3146776BUCKING
Solar/Wind Harmer
-0.003
315705AF1-075 GEN
Solar/Wind Harmer
2.892
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.172
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.363
MECLTFEXP_MEC->PJM
CLTF
0.912
LAGNLTFEXP_LAGN->PJM
CLTF
1.228
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.694
TVALTFEXP_TVA->PJM
CLTF
0.641
SIGELTFEXP_SIGE->PJM
CLTF
0.03
CPLELTFEXP_CPLE->PJM
CLTF
0.459
NYPJM->LTFIMP_NY
CLTF
0.489
LGEELTFEXP_LGEE->PJM
CLTF
0.394
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.833
WECLTFEXP_WEC->PJM
CLTF
0.198

Details for AH1-012 TP-6SOUTH HALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 2199T2331_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-012 TP-6SOUTH HALL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2199T2331_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.9 %
Rating:1003.0 MVA
Rating Type:C
MVA to Mitigate:1232.7
MW Contribution:5.46
Bus #Bus NameTypeMW Contribution
3151771S ANNAG1
50/50
1.911
3151801S ANNAS2
50/50
0.982
3151761LOISA E
50/50
74.281
972183AH1-676 GEN
50/50
587.315
3147666LOUISA
Solar/Wind Harmer
-0.193
3132273ORANGE
Solar/Wind Harmer
-0.007
316170AC1-121 GEN2
Solar/Wind Harmer
0.424
970221AG2-151 GEN
Solar/Wind Harmer
5.462
3148013FISHERV
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Harmer
-0.002
3151791S ANNAG2
50/50
1.911
3151781S ANNAS1
50/50
0.982
3151741LOISA C
50/50
1.992
3151751LOISA D
50/50
36.435
3147666LOUISA
Solar/Wind Harmer
-0.336
316192AB2-158 GEN
Solar/Wind Harmer
9.884
315683AE1-153 C
Solar/Wind Harmer
54.18
316254AC1-120 GEN1
Solar/Wind Harmer
1.271
971377AH1-170 GEN
Solar/Wind Harmer
1.092
3147623JAMES R
Solar/Wind Harmer
0.135
972003AH1-546 GEN
Solar/Wind Harmer
4.266
970937AG2-583 GEN
Solar/Wind Harmer
4.865
316322AB2-045
Solar/Wind Harmer
0.227
3146776BUCKING
Solar/Wind Harmer
-0.003
971133AH1-012 GEN
50/50
15.027
3151731LOISA B
50/50
36.435
3151721LOISA A
50/50
36.247
966001AG1-469 GEN
Solar/Wind Harmer
1.01
315651AD1-115 GEN
Solar/Wind Harmer
5.72
971489AH1-241 GEN
Solar/Wind Harmer
5.185
315821AE2-092 GEN
Solar/Wind Harmer
1.791
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
3147346CASHSCORNER
Solar/Wind Harmer
0.846
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
316164AC1-076 GEN
Solar/Wind Harmer
0.879
972205AH1-687 GEN
Adder
3.406
971447AH1-217 GEN
Solar/Wind Harmer
3.122
3148133STUARTS
Solar/Wind Harmer
-0.005
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
1.886
971845AH1-439 GEN
Solar/Wind Harmer
3.505
LAGNLTFEXP_LAGN->PJM
CLTF
0.977
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.963
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.899
MECLTFEXP_MEC->PJM
CLTF
0.75
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.184
TVALTFEXP_TVA->PJM
CLTF
0.512
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
0.264
NYPJM->LTFIMP_NY
CLTF
0.406
LGEELTFEXP_LGEE->PJM
CLTF
0.327
WECLTFEXP_WEC->PJM
CLTF
0.165
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.337

Details for AH1-012 TP-6SOUTH HALL 230.0 kV Ckt 1 line l/o DVP_P4-2: 2278T2331_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-012 TP-6SOUTH HALL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2278T2331_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.93 %
Rating:1003.0 MVA
Rating Type:C
MVA to Mitigate:1192.89
MW Contribution:5.46
Bus #Bus NameTypeMW Contribution
3151791S ANNAG2
50/50
1.911
3151781S ANNAS1
50/50
0.982
3151741LOISA C
50/50
1.992
3151751LOISA D
50/50
36.435
3147666LOUISA
Solar/Wind Harmer
-0.336
316192AB2-158 GEN
Solar/Wind Harmer
9.884
315683AE1-153 C
Solar/Wind Harmer
54.18
316254AC1-120 GEN1
Solar/Wind Harmer
1.271
971377AH1-170 GEN
Solar/Wind Harmer
1.092
3147623JAMES R
Solar/Wind Harmer
0.135
972003AH1-546 GEN
Solar/Wind Harmer
4.266
970937AG2-583 GEN
Solar/Wind Harmer
4.865
316322AB2-045
Solar/Wind Harmer
0.227
3146776BUCKING
Solar/Wind Harmer
-0.003
3151771S ANNAG1
50/50
1.911
3151801S ANNAS2
50/50
0.982
3151761LOISA E
50/50
74.281
972183AH1-676 GEN
50/50
587.315
3147666LOUISA
Solar/Wind Harmer
-0.193
3132273ORANGE
Solar/Wind Harmer
-0.007
316170AC1-121 GEN2
Solar/Wind Harmer
0.424
970221AG2-151 GEN
Solar/Wind Harmer
5.462
3148013FISHERV
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Harmer
-0.002
3147346CASHSCORNER
Solar/Wind Harmer
0.846
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
316164AC1-076 GEN
Solar/Wind Harmer
0.879
972205AH1-687 GEN
Adder
3.406
971447AH1-217 GEN
Solar/Wind Harmer
3.122
3148133STUARTS
Solar/Wind Harmer
-0.005
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
1.886
971845AH1-439 GEN
Solar/Wind Harmer
3.505
971133AH1-012 GEN
50/50
15.027
3151731LOISA B
50/50
36.435
3151721LOISA A
50/50
36.247
966001AG1-469 GEN
Solar/Wind Harmer
1.01
315651AD1-115 GEN
Solar/Wind Harmer
5.72
971489AH1-241 GEN
Solar/Wind Harmer
5.185
315821AE2-092 GEN
Solar/Wind Harmer
1.791
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
LAGNLTFEXP_LAGN->PJM
CLTF
0.977
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.963
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.899
MECLTFEXP_MEC->PJM
CLTF
0.75
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.184
TVALTFEXP_TVA->PJM
CLTF
0.512
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
0.264
NYPJM->LTFIMP_NY
CLTF
0.406
LGEELTFEXP_LGEE->PJM
CLTF
0.327
WECLTFEXP_WEC->PJM
CLTF
0.165
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.337

Details for AH1-012 TP-6SOUTH HALL 230.0 kV Ckt 1 line l/o DVP_P2-2: GERMANNA_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-012 TP-6SOUTH HALL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: GERMANNA_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:117.52 %
Rating:1003.0 MVA
Rating Type:C
MVA to Mitigate:1178.69
MW Contribution:5.46
Bus #Bus NameTypeMW Contribution
971133AH1-012 GEN
50/50
15.027
3151731LOISA B
50/50
36.435
3151721LOISA A
50/50
36.247
966001AG1-469 GEN
Solar/Wind Harmer
1.01
315651AD1-115 GEN
Solar/Wind Harmer
5.72
971489AH1-241 GEN
Solar/Wind Harmer
5.185
315821AE2-092 GEN
Solar/Wind Harmer
1.791
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
3147346CASHSCORNER
Solar/Wind Harmer
0.846
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
3138266HYDRAULIC
Solar/Wind Harmer
-0.001
316164AC1-076 GEN
Solar/Wind Harmer
0.879
972205AH1-687 GEN
Adder
3.406
971447AH1-217 GEN
Solar/Wind Harmer
3.122
3148133STUARTS
Solar/Wind Harmer
-0.005
3148013FISHERV
Solar/Wind Harmer
-0.005
270494AE1-108_GEN
Solar/Wind Harmer
1.886
971845AH1-439 GEN
Solar/Wind Harmer
3.505
3151791S ANNAG2
50/50
1.911
3151781S ANNAS1
50/50
0.982
3151741LOISA C
50/50
1.992
3151751LOISA D
50/50
36.435
3147666LOUISA
Solar/Wind Harmer
-0.336
316192AB2-158 GEN
Solar/Wind Harmer
9.884
316254AC1-120 GEN1
Solar/Wind Harmer
1.271
971377AH1-170 GEN
Solar/Wind Harmer
1.092
3147623JAMES R
Solar/Wind Harmer
0.135
972003AH1-546 GEN
Solar/Wind Harmer
4.266
970937AG2-583 GEN
Solar/Wind Harmer
4.865
316322AB2-045
Solar/Wind Harmer
0.227
3146776BUCKING
Solar/Wind Harmer
-0.003
3151771S ANNAG1
50/50
1.911
3151801S ANNAS2
50/50
0.982
3151761LOISA E
50/50
74.281
972183AH1-676 GEN
50/50
587.315
3147666LOUISA
Solar/Wind Harmer
-0.193
3132273ORANGE
Solar/Wind Harmer
-0.007
316170AC1-121 GEN2
Solar/Wind Harmer
0.424
970221AG2-151 GEN
Solar/Wind Harmer
5.462
3148013FISHERV
Solar/Wind Harmer
-0.008
3146776BUCKING
Solar/Wind Harmer
-0.002
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.963
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.899
MECLTFEXP_MEC->PJM
CLTF
0.75
LAGNLTFEXP_LAGN->PJM
CLTF
0.977
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.184
TVALTFEXP_TVA->PJM
CLTF
0.512
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
0.264
NYPJM->LTFIMP_NY
CLTF
0.406
LGEELTFEXP_LGEE->PJM
CLTF
0.327
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.337
WECLTFEXP_WEC->PJM
CLTF
0.165

Details for AH1-377 TP-AG1-098 TP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-377 TP-AG1-098 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-6: CHASE C T342_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.73 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:780.97
MW Contribution:13.93
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.843
3151931BEARGRDN S1
50/50
2.684
3151911BEARGRDN G1
50/50
2.08
3146926FARMVIL
Solar/Wind Harmer
-0.036
970685AG2-442 GEN
Solar/Wind Harmer
53.632
963171AG1-166 GEN
Solar/Wind Harmer
7.662
971563AH1-280 GEN
Solar/Wind Harmer
7.662
316322AB2-045
Solar/Wind Harmer
1.513
3146776BUCKING
Solar/Wind Harmer
-0.018
972003AH1-546 GEN
Solar/Wind Harmer
14.352
971377AH1-170 GEN
Solar/Wind Harmer
2.786
3147623JAMES R
Solar/Wind Harmer
0.345
970937AG2-583 GEN
Solar/Wind Harmer
14.305
316336AC2-165 C
Solar/Wind Harmer
2.384
3143336POWHATN
Solar/Wind Harmer
1.342
315687AD1-152 GEN
Solar/Wind Helper
1.215
316237AB2-079_GEN
Solar/Wind Helper
0.255
316129AC1-054 GEN
Solar/Wind Helper
0.83
316003AC1-222 GEN
Solar/Wind Helper
0.686
972205AH1-687 GEN
50/50
10.143
3144303KENBRDG
Solar/Wind Harmer
-0.049
970683AG2-441 GEN
Solar/Wind Harmer
47.886
970681AG2-440 GEN
Solar/Wind Harmer
38.309
315657AE1-056 GEN
Solar/Wind Harmer
22.986
946301AF1-294 GEN
Solar/Wind Harmer
15.707
961791AG1-021 GEN
Solar/Wind Harmer
7.662
971443AH1-215 GEN
Solar/Wind Harmer
12.067
970285AG2-188 GEN
Solar/Wind Harmer
42.868
971845AH1-439 GEN
Solar/Wind Harmer
24.629
971447AH1-217 GEN
Solar/Wind Harmer
7.521
270494AE1-108_GEN
Solar/Wind Harmer
4.495
3138266HYDRAULIC
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Helper
0.255
316238AB2-078_GEN
Solar/Wind Helper
0.255
3147173SINAI
Solar/Wind Helper
0.172
3147243WELCO
Solar/Wind Helper
0.107
316118AC1-105 GEN
Solar/Wind Helper
0.666
3144293JTRSVLE
50/50
1.843
3144293JTRSVLE
50/50
1.552
971741AH1-377 GEN
Solar/Wind Harmer
100.021
970301AG2-198 GEN
Solar/Wind Harmer
40.087
316034AC1-036 C
Solar/Wind Harmer
1.137
3147133PAMPLIN
Solar/Wind Harmer
-0.061
3147133PAMPLIN
Solar/Wind Harmer
-0.049
970323AG2-213 GEN
Solar/Wind Harmer
30.647
958211AF2-115 GEN
Solar/Wind Harmer
9.577
963191AG1-168 GEN
Solar/Wind Harmer
5.746
971775AH1-396 GEN
Solar/Wind Harmer
4.364
3146776BUCKING
Solar/Wind Harmer
-0.179
3146776BUCKING
Solar/Wind Harmer
-0.015
971489AH1-241 GEN
Solar/Wind Harmer
13.226
315821AE2-092 GEN
Solar/Wind Harmer
3.439
3146843MT LREL
Solar/Wind Helper
0.172
3146843MT LREL
Solar/Wind Helper
0.172
316222AC1-221 GEN
Solar/Wind Helper
0.699
3144293JTRSVLE
50/50
1.843
3151921BEARGRDN G2
50/50
2.08
970909AG2-566 GEN
Solar/Wind Harmer
7.611
942461AE2-259 GEN
Solar/Wind Harmer
9.211
3146926FARMVIL
Solar/Wind Harmer
-0.036
3147133PAMPLIN
Solar/Wind Harmer
-0.192
959311AF2-222 GEN
Solar/Wind Harmer
63.976
971193AH1-056 GEN
Solar/Wind Harmer
38.309
970257AG2-171 GEN
Solar/Wind Harmer
22.985
963181AG1-167 GEN
Solar/Wind Harmer
5.746
315785AD2-033 C
Solar/Wind Harmer
13.891
316131AB2-060 GEN
Solar/Wind Harmer
6.613
964241AG1-285 GEN
Solar/Wind Harmer
47.885
3146776BUCKING
Solar/Wind Harmer
-0.016
970221AG2-151 GEN
Solar/Wind Harmer
13.931
316313AB2-026
Solar/Wind Harmer
0.305
316258AE1-075 C
Solar/Wind Harmer
0.275
316405AF2-144 C
Solar/Wind Harmer
0.29
3143336POWHATN
Solar/Wind Harmer
1.141
972183AH1-676 GEN
Adder
39.209
316478AD1-087 GEN
Solar/Wind Helper
1.275
316486AD2-202 GEN
Solar/Wind Helper
0.373
316248AF1-058 C
Solar/Wind Helper
0.23
316283AC2-100 C
Solar/Wind Helper
0.644
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.216
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.69
VTFLTFEXP_VFT->PJM
CMTX
2.578
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.855
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.599
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.961
CBM NorthLTFEXP_CBM-N->PJM
CBM
1.806
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.805
CONTINGENCY 'DVP_P1-2: LN 2193_SRT-A'
 OPEN BRANCH FROM BUS 313707 TO BUS 313867 CKT 1   /*6FORK UNION  230.0 - 6BREMODIST   230.0
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BUS 313867                                   /*6BREMODIST   230.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-S'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: WT576_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 2                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: 57602_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 1                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: H6T563_SRT-S'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1                /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: H6T576_SRT-A'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1   /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1   /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 2027_SRT-A-3'
 OPEN BRANCH FROM BUS 314322 TO BUS 314333 CKT 1   /*6MDLTHAN     230.0 - 6POWHATN     230.0
 OPEN BRANCH FROM BUS 314333 TO BUS 316335 CKT 1   /*6POWHATN     230.0 - AC2-165 TAP  230.0
 OPEN BUS 314333                                   /*6POWHATN     230.0
 OPEN BUS 316258                                   /*AE1-075 C    230.0
 OPEN BUS 316313                                   /*AB2-026      230.0
 OPEN BUS 316405                                   /*AF2-144 C    230.0
END
CONTINGENCY 'DVP_P4-2: 242T2027_SRT-A'
 OPEN BRANCH FROM BUS 314322 TO BUS 314333 CKT 1   /*6MDLTHAN     230.0 - 6POWHATN     230.0
 OPEN BRANCH FROM BUS 314333 TO BUS 316335 CKT 1   /*6POWHATN     230.0 - AC2-165 TAP  230.0
 OPEN BUS 314333                                   /*6POWHATN     230.0
 OPEN BUS 316258                                   /*AE1-075 C    230.0
 OPEN BUS 316313                                   /*AB2-026      230.0
 OPEN BUS 316405                                   /*AF2-144 C    230.0
END
CONTINGENCY 'AEP_P2-2_#1377_05J.FERR 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242514 TO BUS 290022 CKT 1   /*05J.FERR     765.0 - 05J.FERR 1EQ   1.0
 OPEN BRANCH FROM BUS 242520 TO BUS 290022 CKT 1   /*05J.FERR     500.0 - 05J.FERR 1EQ   1.0
 OPEN BRANCH FROM BUS 242520 TO BUS 306719 CKT 1   /*05J.FERR     500.0 - 8ANTIOCH     500.0
 OPEN BRANCH FROM BUS 290022 TO BUS 290023 CKT 1   /*05J.FERR 1EQ   1.0 - 05J.FERR T1   13.8
END
CONTINGENCY 'DVP_P7-1: LN 2066-282_SRT-S'
 OPEN BRANCH FROM BUS 313740 TO BUS 314322 CKT 1                /*6GENITO      230.0 - 6MDLTHAN     230.0
 OPEN BRANCH FROM BUS 313740 TO BUS 314352 CKT 1                /*6GENITO      230.0 - 6WINTERP     230.0
 OPEN BRANCH FROM BUS 314307 TO BUS 314311 CKT 1                /*6HULL282     230.0 - 6IRON282     230.0
 OPEN BRANCH FROM BUS 314307 TO BUS 314322 CKT 1                /*6HULL282     230.0 - 6MDLTHAN     230.0
 OPEN BRANCH FROM BUS 314311 TO BUS 314339 CKT 1                /*6IRON282     230.0 - 6SPRUNCE     230.0
 OPEN BRANCH FROM BUS 314339 TO BUS 315083 CKT 1                /*6SPRUNCE     230.0 - 1SPRUNCA      13.8
 OPEN BRANCH FROM BUS 314339 TO BUS 315084 CKT 1                /*6SPRUNCE     230.0 - 1SPRUNCB      13.8
 OPEN BUS 313740                                                /*6GENITO      230.0
 OPEN BUS 314307                                                /*6HULL282     230.0
 OPEN BUS 314311                                                /*6IRON282     230.0
 OPEN BUS 315083                                                /*1SPRUNCA      13.8
 OPEN BUS 315084                                                /*1SPRUNCB      13.8
 SET POSTCONTRATING 876 BRANCH FROM BUS 314233 TO BUS 314322 CKT 1 /*6N POLE      230.0 - 6MDLTHAN     230.0
 SET PRECONTRATING 813 BRANCH FROM BUS 314233 TO BUS 314322 CKT 1 /*6N POLE      230.0 - 6MDLTHAN     230.0
END
CONTINGENCY 'DVP_P7-1: LN 219-282_SRT-A'
 OPEN BRANCH FROM BUS 314306 TO BUS 314338 CKT 1   /*6HULL219     230.0 - 6SOUWEST     230.0
 OPEN BRANCH FROM BUS 314306 TO BUS 314352 CKT 1   /*6HULL219     230.0 - 6WINTERP     230.0
 OPEN BRANCH FROM BUS 314307 TO BUS 314311 CKT 1   /*6HULL282     230.0 - 6IRON282     230.0
 OPEN BRANCH FROM BUS 314307 TO BUS 314322 CKT 1   /*6HULL282     230.0 - 6MDLTHAN     230.0
 OPEN BRANCH FROM BUS 314311 TO BUS 314339 CKT 1   /*6IRON282     230.0 - 6SPRUNCE     230.0
 OPEN BRANCH FROM BUS 314339 TO BUS 315083 CKT 1   /*6SPRUNCE     230.0 - 1SPRUNCA      13.8
 OPEN BRANCH FROM BUS 314339 TO BUS 315084 CKT 1   /*6SPRUNCE     230.0 - 1SPRUNCB      13.8
 OPEN BUS 314306                                   /*6HULL219     230.0
 OPEN BUS 314307                                   /*6HULL282     230.0
 OPEN BUS 314311                                   /*6IRON282     230.0
 OPEN BUS 315083                                   /*1SPRUNCA      13.8
 OPEN BUS 315084                                   /*1SPRUNCB      13.8
END
CONTINGENCY 'DVP_P2-2: DOOMS B2_SRT-A'
 OPEN BRANCH FROM BUS 313286 TO BUS 314793 CKT 1   /*3WAYNESBORO  115.0 - 3DOOMS       115.0
 OPEN BRANCH FROM BUS 314767 TO BUS 314793 CKT 1   /*3MIDWAY      115.0 - 3DOOMS       115.0
 OPEN BRANCH FROM BUS 314791 TO BUS 314793 CKT 1   /*3BRAND TAP   115.0 - 3DOOMS       115.0
END
CONTINGENCY 'DVP_P1-2: LN 2028_SRT-A'
 OPEN BRANCH FROM BUS 313373 TO BUS 313707 CKT 1   /*6GRAPEVINE   230.0 - 6FORK UNION  230.0
 OPEN BRANCH FROM BUS 313373 TO BUS 314765 CKT 1   /*6GRAPEVINE   230.0 - 6MTEAGLE     230.0
 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1   /*6CHARLVL     230.0 - 6MTEAGLE     230.0
 OPEN BUS 313373                                   /*6GRAPEVINE   230.0
 OPEN BUS 313493                                   /*3GRAPEVINE   115.0
 OPEN BUS 314754                                   /*3CUNNING     115.0
 OPEN BUS 314765                                   /*6MTEAGLE     230.0
END
CONTINGENCY 'DVP_P1-2: LN 593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P4-2: 2028T2054_SRT-A'
 OPEN BRANCH FROM BUS 313373 TO BUS 313707 CKT 1   /*6GRAPEVINE   230.0 - 6FORK UNION  230.0
 OPEN BRANCH FROM BUS 313373 TO BUS 314765 CKT 1   /*6GRAPEVINE   230.0 - 6MTEAGLE     230.0
 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1   /*6CHARLVL     230.0 - 6MTEAGLE     230.0
 OPEN BRANCH FROM BUS 314749 TO BUS 314772 CKT 1   /*6CHARLVL     230.0 - 6PROFFIT     230.0
 OPEN BRANCH FROM BUS 314759 TO BUS 314772 CKT 1   /*6HOLLYMD     230.0 - 6PROFFIT     230.0
 OPEN BUS 313373                                   /*6GRAPEVINE   230.0
 OPEN BUS 313493                                   /*3GRAPEVINE   115.0
 OPEN BUS 314754                                   /*3CUNNING     115.0
 OPEN BUS 314765                                   /*6MTEAGLE     230.0
 OPEN BUS 314772                                   /*6PROFFIT     230.0
END
CONTINGENCY 'DVP_P4-2: 233T2028_SRT-A'
 OPEN BRANCH FROM BUS 313373 TO BUS 313707 CKT 1   /*6GRAPEVINE   230.0 - 6FORK UNION  230.0
 OPEN BRANCH FROM BUS 313373 TO BUS 314765 CKT 1   /*6GRAPEVINE   230.0 - 6MTEAGLE     230.0
 OPEN BRANCH FROM BUS 313826 TO BUS 314742 CKT 1   /*6HYDRAULIC   230.0 - 6BARRCK2     230.0
 OPEN BRANCH FROM BUS 313826 TO BUS 314749 CKT 1   /*6HYDRAULIC   230.0 - 6CHARLVL     230.0
 OPEN BRANCH FROM BUS 314742 TO BUS 314751 CKT 1   /*6BARRCK2     230.0 - 6CROZET1     230.0
 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1   /*6CHARLVL     230.0 - 6MTEAGLE     230.0
 OPEN BRANCH FROM BUS 314751 TO BUS 314794 CKT 1   /*6CROZET1     230.0 - 6DOOMS       230.0
 OPEN BUS 313373                                   /*6GRAPEVINE   230.0
 OPEN BUS 313493                                   /*3GRAPEVINE   115.0
 OPEN BUS 313826                                   /*6HYDRAULIC   230.0
 OPEN BUS 314742                                   /*6BARRCK2     230.0
 OPEN BUS 314751                                   /*6CROZET1     230.0
 OPEN BUS 314754                                   /*3CUNNING     115.0
 OPEN BUS 314765                                   /*6MTEAGLE     230.0
END
CONTINGENCY 'DVP_P4-2: 587T591_SRT-S'
 OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1                /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 OPEN BRANCH FROM BUS 971966 TO BUS 314936 CKT 1                /*AH1-528 TP   500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 511T556_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 OPEN BRANCH FROM BUS 971966 TO BUS 314936 CKT 1                /*AH1-528 TP   500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 2028T2193_SRT-A'
 OPEN BRANCH FROM BUS 313373 TO BUS 313707 CKT 1   /*6GRAPEVINE   230.0 - 6FORK UNION  230.0
 OPEN BRANCH FROM BUS 313373 TO BUS 314765 CKT 1   /*6GRAPEVINE   230.0 - 6MTEAGLE     230.0
 OPEN BRANCH FROM BUS 313707 TO BUS 313867 CKT 1   /*6FORK UNION  230.0 - 6BREMODIST   230.0
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1   /*6CHARLVL     230.0 - 6MTEAGLE     230.0
 OPEN BUS 313373                                   /*6GRAPEVINE   230.0
 OPEN BUS 313493                                   /*3GRAPEVINE   115.0
 OPEN BUS 313867                                   /*6BREMODIST   230.0
 OPEN BUS 314754                                   /*3CUNNING     115.0
 OPEN BUS 314765                                   /*6MTEAGLE     230.0
END
CONTINGENCY 'DVP_P4-2: 202712_SRT-S'
 OPEN BRANCH FROM BUS 314322 TO BUS 314333 CKT 1                /*6MDLTHAN     230.0 - 6POWHATN     230.0
 OPEN BRANCH FROM BUS 314333 TO BUS 316335 CKT 1                /*6POWHATN     230.0 - AC2-165 TAP  230.0
 OPEN BUS 314333                                                /*6POWHATN     230.0
 OPEN BUS 316258                                                /*AE1-075 C    230.0
 OPEN BUS 316313                                                /*AB2-026      230.0
 OPEN BUS 316405                                                /*AF2-144 C    230.0
 SET POSTCONTRATING 876 BRANCH FROM BUS 314233 TO BUS 314322 CKT 1 /*6N POLE      230.0 - 6MDLTHAN     230.0
 SET PRECONTRATING 813 BRANCH FROM BUS 314233 TO BUS 314322 CKT 1 /*6N POLE      230.0 - 6MDLTHAN     230.0
END
CONTINGENCY 'DVP_P4-2: WT2193_SRT-A'
 OPEN BRANCH FROM BUS 313707 TO BUS 313708 CKT 1   /*6FORK UNION  230.0 - 3FORK UNION  115.0
 OPEN BRANCH FROM BUS 313707 TO BUS 313867 CKT 1   /*6FORK UNION  230.0 - 6BREMODIST   230.0
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BUS 313867                                   /*6BREMODIST   230.0
END
CONTINGENCY 'DVP_P4-2: 202872_SRT-A'
 OPEN BRANCH FROM BUS 313373 TO BUS 313707 CKT 1   /*6GRAPEVINE   230.0 - 6FORK UNION  230.0
 OPEN BRANCH FROM BUS 313373 TO BUS 314765 CKT 1   /*6GRAPEVINE   230.0 - 6MTEAGLE     230.0
 OPEN BRANCH FROM BUS 313707 TO BUS 313708 CKT 1   /*6FORK UNION  230.0 - 3FORK UNION  115.0
 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1   /*6CHARLVL     230.0 - 6MTEAGLE     230.0
 OPEN BUS 313373                                   /*6GRAPEVINE   230.0
 OPEN BUS 313493                                   /*3GRAPEVINE   115.0
 OPEN BUS 314754                                   /*3CUNNING     115.0
 OPEN BUS 314765                                   /*6MTEAGLE     230.0
END
CONTINGENCY 'DVP_P1-2: LN 553_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314910 CKT 1                /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 2199_SRT-A-1'
 OPEN BRANCH FROM BUS 313671 TO BUS 315678 CKT 1   /*6GERMANNA    230.0 - AE1-153 TAP  230.0
END
CONTINGENCY 'DVP_P1-2: LN 2331_SRT-A'
 OPEN BRANCH FROM BUS 313671 TO BUS 313679 CKT 1   /*6GERMANNA    230.0 - 6CIRRUS      230.0
END
CONTINGENCY 'DVP_P7-1: LN 11-2199_SRT-A-1'
 OPEN BRANCH FROM BUS 313227 TO BUS 314769 CKT 1   /*3ORANGE      115.0 - 3ORANGE TAP  115.0
 OPEN BRANCH FROM BUS 313671 TO BUS 315678 CKT 1   /*6GERMANNA    230.0 - AE1-153 TAP  230.0
 OPEN BRANCH FROM BUS 314756 TO BUS 314769 CKT 1   /*3DOUBLDY     115.0 - 3ORANGE TAP  115.0
 OPEN BRANCH FROM BUS 314756 TO BUS 314776 CKT 1   /*3DOUBLDY     115.0 - 3SOMRSET     115.0
 OPEN BRANCH FROM BUS 314757 TO BUS 314776 CKT 1   /*3GORDNVL     115.0 - 3SOMRSET     115.0
 OPEN BRANCH FROM BUS 314769 TO BUS 314815 CKT 1   /*3ORANGE TAP  115.0 - 3OAK GRE     115.0
 OPEN BRANCH FROM BUS 314776 TO BUS 314884 CKT 1   /*3SOMRSET     115.0 - 3SOMRS_1     115.0
 OPEN BUS 313227                                   /*3ORANGE      115.0
 OPEN BUS 314756                                   /*3DOUBLDY     115.0
 OPEN BUS 314769                                   /*3ORANGE TAP  115.0
 OPEN BUS 314776                                   /*3SOMRSET     115.0
 OPEN BUS 314884                                   /*3SOMRS_1     115.0
END
CONTINGENCY 'DVP_P7-1: LN 11-2199_SRT-A-2'
 OPEN BRANCH FROM BUS 313227 TO BUS 314769 CKT 1   /*3ORANGE      115.0 - 3ORANGE TAP  115.0
 OPEN BRANCH FROM BUS 314756 TO BUS 314769 CKT 1   /*3DOUBLDY     115.0 - 3ORANGE TAP  115.0
 OPEN BRANCH FROM BUS 314756 TO BUS 314776 CKT 1   /*3DOUBLDY     115.0 - 3SOMRSET     115.0
 OPEN BRANCH FROM BUS 314757 TO BUS 314776 CKT 1   /*3GORDNVL     115.0 - 3SOMRSET     115.0
 OPEN BRANCH FROM BUS 314758 TO BUS 315678 CKT 1   /*6GORDNVL     230.0 - AE1-153 TAP  230.0
 OPEN BRANCH FROM BUS 314769 TO BUS 314815 CKT 1   /*3ORANGE TAP  115.0 - 3OAK GRE     115.0
 OPEN BRANCH FROM BUS 314776 TO BUS 314884 CKT 1   /*3SOMRSET     115.0 - 3SOMRS_1     115.0
 OPEN BUS 313227                                   /*3ORANGE      115.0
 OPEN BUS 314756                                   /*3DOUBLDY     115.0
 OPEN BUS 314769                                   /*3ORANGE TAP  115.0
 OPEN BUS 314776                                   /*3SOMRSET     115.0
 OPEN BUS 314884                                   /*3SOMRS_1     115.0
END
CONTINGENCY 'DVP_P4-2: 2199T2331_SRT-A'
 OPEN BRANCH FROM BUS 313671 TO BUS 313679 CKT 1   /*6GERMANNA    230.0 - 6CIRRUS      230.0
 OPEN BRANCH FROM BUS 313671 TO BUS 315678 CKT 1   /*6GERMANNA    230.0 - AE1-153 TAP  230.0
END
CONTINGENCY 'DVP_P4-2: 2278T2331_SRT-A'
 OPEN BRANCH FROM BUS 313671 TO BUS 313679 CKT 1   /*6GERMANNA    230.0 - 6CIRRUS      230.0
 OPEN BRANCH FROM BUS 313678 TO BUS 313679 CKT 1   /*6KYSER       230.0 - 6CIRRUS      230.0
END
CONTINGENCY 'DVP_P2-2: GERMANNA_SRT-A'
 OPEN BRANCH FROM BUS 313671 TO BUS 313679 CKT 1   /*6GERMANNA    230.0 - 6CIRRUS      230.0
 OPEN BRANCH FROM BUS 313671 TO BUS 315678 CKT 1   /*6GERMANNA    230.0 - AE1-153 TAP  230.0
 OPEN BRANCH FROM BUS 314758 TO BUS 315678 CKT 1   /*6GORDNVL     230.0 - AE1-153 TAP  230.0
 OPEN BUS 315678                                   /*AE1-153 TAP  230.0
 OPEN BUS 315679                                   /*AE1-153 MAIN 230.0
 OPEN BUS 315680                                   /*AE1-153 COL1  34.5
 OPEN BUS 315681                                   /*AE1-153 COL2  34.5
 OPEN BUS 315682                                   /*AE1-153 TER   13.8
 OPEN BUS 315683                                   /*AE1-153 C      0.6
END
CONTINGENCY 'PEPCO_P1_5070_SRT-A'
 OPEN BRANCH FROM BUS 200019 TO BUS 314922 CKT 1   /*BURCHES      500.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P4-2: 55692_SRT-S'
 OPEN BRANCH FROM BUS 314936 TO BUS 971966 CKT 1                /*8RAWLINGS    500.0 - AH1-528 TP   500.0
 OPEN BUS 314920                                                /*8RAWLIN_STC1 500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-5: 556X2_SRT-S'
 OPEN BRANCH FROM BUS 313995 TO BUS 313996 CKT 2   /*8FINNEYWOOD  500.0 - 6FINNEYWOOD  230.0
 OPEN BRANCH FROM BUS 313995 TO BUS 957480 CKT 1   /*8FINNEYWOOD  500.0 - AF2-042 TP   500.0
END
CONTINGENCY 'DVP_P4-5: 556X1_SRT-S'
 OPEN BRANCH FROM BUS 313995 TO BUS 313996 CKT 1   /*8FINNEYWOOD  500.0 - 6FINNEYWOOD  230.0
 OPEN BRANCH FROM BUS 313995 TO BUS 957480 CKT 1   /*8FINNEYWOOD  500.0 - AF2-042 TP   500.0
END
CONTINGENCY 'DVP_P7-1: LN 39-91_SRT-A-2'
 OPEN BRANCH FROM BUS 313179 TO BUS 313271 CKT 1   /*3TURKEYRUN   115.0 - 3TRANSCO TAP 115.0
 OPEN BRANCH FROM BUS 313179 TO BUS 313783 CKT 1   /*3TURKEYRUN   115.0 - 3WALNUT CRK  115.0
 OPEN BRANCH FROM BUS 313270 TO BUS 313271 CKT 1   /*3TRANSCO DP  115.0 - 3TRANSCO TAP 115.0
 OPEN BRANCH FROM BUS 313271 TO BUS 314763 CKT 1   /*3TRANSCO TAP 115.0 - 3KIDDSTO     115.0
 OPEN BRANCH FROM BUS 313783 TO BUS 314773 CKT 1   /*3WALNUT CRK  115.0 - 3RED HIL     115.0
 OPEN BRANCH FROM BUS 314767 TO BUS 314773 CKT 1   /*3MIDWAY      115.0 - 3RED HIL     115.0
 OPEN BRANCH FROM BUS 314767 TO BUS 314793 CKT 1   /*3MIDWAY      115.0 - 3DOOMS       115.0
 OPEN BRANCH FROM BUS 971446 TO BUS 314763 CKT 1   /*AH1-217 TP   115.0 - 3KIDDSTO     115.0
 OPEN BUS 247086                                   /*05REDHIL     115.0
 OPEN BUS 313179                                   /*3TURKEYRUN   115.0
 OPEN BUS 313270                                   /*3TRANSCO DP  115.0
 OPEN BUS 313271                                   /*3TRANSCO TAP 115.0
 OPEN BUS 314763                                   /*3KIDDSTO     115.0
 OPEN BUS 314767                                   /*3MIDWAY      115.0
 OPEN BUS 314773                                   /*3RED HIL     115.0
 OPEN BUS 315817                                   /*AE2-092 MAIN 115.0
 OPEN BUS 315818                                   /*AE2-092 COL   34.5
 OPEN BUS 315819                                   /*AE2-092 TER   13.8
 OPEN BUS 315820                                   /*AE2-092 GSU   34.5
 OPEN BUS 315821                                   /*AE2-092 GEN    0.6
END
CONTINGENCY 'DVP_P1-2: LN 2304_SRT-A-2'
 OPEN BRANCH FROM BUS 313046 TO BUS 313052 CKT 1   /*6LOUISA PUMP 230.0 - 6DESPER      230.0
 OPEN BRANCH FROM BUS 313046 TO BUS 314766 CKT 1   /*6LOUISA PUMP 230.0 - 6LOUISA      230.0
 OPEN BRANCH FROM BUS 971132 TO BUS 314766 CKT 1   /*AH1-012 TP   230.0 - 6LOUISA      230.0
 OPEN BUS 313046                                   /*6LOUISA PUMP 230.0
 OPEN BUS 314766                                   /*6LOUISA      230.0
END
CONTINGENCY 'DVP_P1-2: LN 2202_SRT-A'
 OPEN BRANCH FROM BUS 313052 TO BUS 314777 CKT 1   /*6DESPER      230.0 - 6S ANNA      230.0
END
CONTINGENCY 'DVP_P4-2: 220232_SRT-A'
 OPEN BRANCH FROM BUS 313052 TO BUS 314777 CKT 1   /*6DESPER      230.0 - 6S ANNA      230.0
END
CONTINGENCY 'DVP_P4-2: 2304T2202_SRT-A'
 OPEN BRANCH FROM BUS 313046 TO BUS 313052 CKT 1   /*6LOUISA PUMP 230.0 - 6DESPER      230.0
 OPEN BRANCH FROM BUS 313046 TO BUS 314766 CKT 1   /*6LOUISA PUMP 230.0 - 6LOUISA      230.0
 OPEN BRANCH FROM BUS 313052 TO BUS 314777 CKT 1   /*6DESPER      230.0 - 6S ANNA      230.0
 OPEN BRANCH FROM BUS 971132 TO BUS 314766 CKT 1   /*AH1-012 TP   230.0 - 6LOUISA      230.0
 OPEN BUS 313046                                   /*6LOUISA PUMP 230.0
 OPEN BUS 314766                                   /*6LOUISA      230.0
END
CONTINGENCY 'DVP_P4-2: G2T2202_SRT-A'
 OPEN BRANCH FROM BUS 313052 TO BUS 314777 CKT 1                /*6DESPER      230.0 - 6S ANNA      230.0
 OPEN BRANCH FROM BUS 314777 TO BUS 315179 TO BUS 315180 CKT 1  /*6S ANNA      230.0 - 1S ANNAG2     13.8 - 1S ANNAS2     13.8
 OPEN BUS 315179                                                /*1S ANNAG2     13.8
 OPEN BUS 315180                                                /*1S ANNAS2     13.8
END
CONTINGENCY 'DVP_P4-2: H3T255_SRT-A'
 OPEN BRANCH FROM BUS 313930 TO BUS 314232 CKT 1                /*6SOUTH HALL  230.0 - 6NO ANNA     230.0
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 2                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314777 TO BUS 315179 TO BUS 315180 CKT 1  /*6S ANNA      230.0 - 1S ANNAG2     13.8 - 1S ANNAS2     13.8
 OPEN BUS 315179                                                /*1S ANNAG2     13.8
 OPEN BUS 315180                                                /*1S ANNAS2     13.8
END
CONTINGENCY 'DVP_P4-2: 25532_SRT-A'
 OPEN BRANCH FROM BUS 313930 TO BUS 314232 CKT 1                /*6SOUTH HALL  230.0 - 6NO ANNA     230.0
 OPEN BRANCH FROM BUS 314777 TO BUS 315179 TO BUS 315180 CKT 1  /*6S ANNA      230.0 - 1S ANNAG2     13.8 - 1S ANNAS2     13.8
 OPEN BUS 315179                                                /*1S ANNAG2     13.8
 OPEN BUS 315180                                                /*1S ANNAS2     13.8
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 562T563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1   /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1   /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 56372_SRT-S'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1                /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-5: 593X1_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
 OPEN BRANCH FROM BUS 313995 TO BUS 313996 CKT 1   /*8FINNEYWOOD  500.0 - 6FINNEYWOOD  230.0
END
CONTINGENCY 'DVP_P4-5: 593X2_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
 OPEN BRANCH FROM BUS 313995 TO BUS 313996 CKT 2   /*8FINNEYWOOD  500.0 - 6FINNEYWOOD  230.0
END
CONTINGENCY 'DVP_P1-2: LN 9344_SRT-A'
 OPEN BRANCH FROM BUS 313393 TO BUS 313905 CKT 1   /*8MARS        500.0 - 8WSHNGSTAR   500.0
END
CONTINGENCY 'DVP_P1-2: LN 594_SRT-S'
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 573_SRT-S'
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1                /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
END
CONTINGENCY 'DVP_P7-1: LN 2054-2135_SRT-A'
 OPEN BRANCH FROM BUS 314734 TO BUS 314758 CKT 1   /*6CASHSCORNER 230.0 - 6GORDNVL     230.0
 OPEN BRANCH FROM BUS 314734 TO BUS 314759 CKT 1   /*6CASHSCORNER 230.0 - 6HOLLYMD     230.0
 OPEN BRANCH FROM BUS 314749 TO BUS 314772 CKT 1   /*6CHARLVL     230.0 - 6PROFFIT     230.0
 OPEN BRANCH FROM BUS 314759 TO BUS 314772 CKT 1   /*6HOLLYMD     230.0 - 6PROFFIT     230.0
 OPEN BUS 314734                                   /*6CASHSCORNER 230.0
 OPEN BUS 314772                                   /*6PROFFIT     230.0
END
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2913 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'AP_P1-2_PE-500-406T_SRT-A'
 DISCONNECT BRANCH FROM BUS 200003 TO BUS 235105 CKT 1   /*BRIGHTON     500.0 - 01DOUBS      500.0
END
CONTINGENCY 'DVP_P1-2: LN 587_SRT-A-3'
 OPEN BRANCH FROM BUS 971966 TO BUS 314936 CKT 1   /*AH1-528 TP   500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-6: CHASE C T342_SRT-A'
 OPEN BUS 313527   /*AB2-043 GEN    0.6
 OPEN BUS 313528   /*AB2-043 COL   34.5
 OPEN BUS 313529   /*3BLUESTONE   115.0
 OPEN BUS 314267   /*3CHASCTY2    115.0
 OPEN BUS 314518   /*3CHASC_1     115.0
 OPEN BUS 314681   /*3CHASCTY     115.0
END
314744 to 313708 ckt 2
313708 to 313707 ckt 1
314747 to 313867 ckt 1
314747 to 970936 ckt 1
313867 to 313707 ckt 1
313868 to 316335 ckt 1
314749 to 314772 ckt 1
313052 to 313046 ckt 1
314290 to 223938 ckt 1
315684 to 314697 ckt 1
314218 to 314222 ckt 1
313996 to 313995 ckt 1
313996 to 313995 ckt 2
313707 to 313373 ckt 1
313671 to 313679 ckt 1
313373 to 314765 ckt 1
314222 to 314212 ckt 1
314759 to 314734 ckt 1
313678 to 313897 ckt 1
314745 to 314777 ckt 1
313046 to 314766 ckt 1
314766 to 971132 ckt 1
313897 to 314080 ckt 1
314322 to 314914 ckt 1
314765 to 314749 ckt 1
314333 to 314322 ckt 1
314772 to 314759 ckt 1
314777 to 313052 ckt 1
314697 to 316218 ckt 1
313930 to 314232 ckt 1
313911 to 314290 ckt 1
314933 to 972284 ckt 1
314905 to 314900 ckt 1
314908 to 314911 ckt 1
314911 to 314905 ckt 1
314911 to 314922 ckt 1
314914 to 314918 ckt 1
314918 to 314911 ckt 1
314918 to 314934 ckt 1
314922 to 200019 ckt 1
314934 to 314916 ckt 1
316218 to 316281 ckt 1
316281 to 304070 ckt 1
316335 to 314333 ckt 1
962490 to 313996 ckt 1
970936 to 313868 ckt 1
971132 to 313930 ckt 1
971740 to 962490 ckt 1

Winter Peak Analysis

The New Service Request AG2-151 was evaluated as a 100.0 MW (60.0 MW Capacity) injection in the Dominion area.

AG2-151 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 100.0 MW (100.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line
DVP_P1-2: LN 2199_SRT-A-1
SingleAC134.88 %909.92B1227.270.35
GD2DVP
6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line
DVP_P1-2: LN 2199_SRT-A-2
SingleAC134.51 %909.92B1223.940.35
GD2DVP
6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-1
TowerAC127.82 %1113.0C1422.590.4
GD2DVP
6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-2
TowerAC127.48 %1113.0C1418.820.4
GD2DVP
6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line
DVP_P4-2: H3T2199_SRT-A
BreakerAC110.3 %1113.0C1227.60.35
GD2DVP
6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line
DVP_P4-2: 2199T2331_SRT-A
BreakerAC109.86 %1113.0C1222.790.35
GD2DVP
6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line
DVP_P2-2: GERMANNA_SRT-A
BusAC109.56 %1113.0C1219.440.35
GD2DVP
6LOISACT-6S ANNA 230.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-1
TowerAC108.34 %1061.0C1149.540.41
GD2DVP
6LOISACT-6S ANNA 230.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-2
TowerAC107.99 %1061.0C1145.720.41
GD2DVP
6LOISACT-6S ANNA 230.0 kV Ckt 1 line
DVP_P1-2: LN 2199_SRT-A-1
SingleAC105.03 %909.92B955.680.36
GD2DVP
6LOISACT-6S ANNA 230.0 kV Ckt 1 line
DVP_P1-2: LN 2199_SRT-A-2
SingleAC104.66 %909.92B952.30.36
GD2DVP
6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line
DVP_P1-2: LN 2199_SRT-A-1
SingleAC134.87 %909.92B1227.240.35
GD2DVP
6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line
DVP_P1-2: LN 2199_SRT-A-2
SingleAC134.51 %909.92B1223.90.35
GD2DVP
6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-1
TowerAC127.81 %1113.0C1422.560.4
GD2DVP
6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-2
TowerAC127.47 %1113.0C1418.790.4
GD2DVP
6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line
DVP_P4-2: H3T2199_SRT-A
BreakerAC110.29 %1113.0C1227.560.35
GD2DVP
6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line
DVP_P4-2: 2199T2331_SRT-A
BreakerAC109.86 %1113.0C1222.750.35
GD2DVP
6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line
DVP_P2-2: GERMANNA_SRT-A
BusAC109.56 %1113.0C1219.410.35
GD2DVP
6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 2199_SRT-A-1
SingleAC111.18 %909.92B1011.630.35
GD2DVP
6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 2199_SRT-A-2
SingleAC110.81 %909.92B1008.310.35
GD2DVP
6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-1
TowerAC108.1 %1113.0C1203.180.4
GD2DVP
6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-2
TowerAC107.76 %1113.0C1199.410.4
GD2DVP
6S ANNA-6DESPER 230.0 kV Ckt 1 line
DVP_P1-2: LN 2199_SRT-A-1
SingleAC134.81 %909.92B1226.660.35
GD2DVP
6S ANNA-6DESPER 230.0 kV Ckt 1 line
DVP_P1-2: LN 2199_SRT-A-2
SingleAC134.44 %909.92B1223.330.35
GD2DVP
6S ANNA-6DESPER 230.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-1
TowerAC127.77 %1113.0C1422.070.4
GD2DVP
6S ANNA-6DESPER 230.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-2
TowerAC127.43 %1113.0C1418.310.4
GD2DVP
6S ANNA-6DESPER 230.0 kV Ckt 1 line
DVP_P4-2: H3T2199_SRT-A
BreakerAC110.24 %1113.0C1227.00.35
GD2DVP
6S ANNA-6DESPER 230.0 kV Ckt 1 line
DVP_P4-2: 2199T2331_SRT-A
BreakerAC109.81 %1113.0C1222.170.35
GD2DVP
6S ANNA-6DESPER 230.0 kV Ckt 1 line
DVP_P2-2: GERMANNA_SRT-A
BusAC109.51 %1113.0C1218.830.35
GD2DVP
6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line
DVP_P1-2: LN 2199_SRT-A-1
SingleAC112.28 %909.92B1021.640.35
GD2DVP
6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line
DVP_P1-2: LN 2199_SRT-A-2
SingleAC111.91 %909.92B1018.310.35
GD2DVP
6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-1
TowerAC109.04 %1113.0C1213.620.4
GD2DVP
6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-2
TowerAC108.7 %1113.0C1209.840.4
GD2DVP
AH1-012 TP-6SOUTH HALL 230.0 kV Ckt 1 line
DVP_P1-2: LN 2199_SRT-A-1
SingleAC112.38 %909.92B1022.60.35
GD2DVP
AH1-012 TP-6SOUTH HALL 230.0 kV Ckt 1 line
DVP_P1-2: LN 2199_SRT-A-2
SingleAC112.02 %909.92B1019.270.35
GD2DVP
AH1-012 TP-6SOUTH HALL 230.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-1
TowerAC109.13 %1113.0C1214.570.4
GD2DVP
AH1-012 TP-6SOUTH HALL 230.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-2
TowerAC108.79 %1113.0C1210.80.4

Details for 6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2199_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2199_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:134.88 %
Rating:909.92 MVA
Rating Type:B
MVA to Mitigate:1227.27
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
3151721LOISA A
50/50
41.896
3151911BEARGRDN G1
50/50
0.691
3132273ORANGE
Solar/Wind Harmer
-0.171
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.062
3146776BUCKING
Solar/Wind Harmer
-0.056
3146776BUCKING
Solar/Wind Harmer
-0.05
3151731LOISA B
50/50
41.896
3151751LOISA D
50/50
41.896
3151921BEARGRDN G2
50/50
0.725
3148013FISHERV
Solar/Wind Harmer
-0.189
3148013FISHERV
Solar/Wind Harmer
-0.109
3147666LOUISA
Solar/Wind Helper
2.368
3151771S ANNAG1
50/50
2.477
971447AH1-217 GEN
Solar/Wind Harmer
0.199
3147623JAMES R
Solar/Wind Harmer
0.009
972003AH1-546 GEN
Solar/Wind Harmer
0.272
3148133STUARTS
Solar/Wind Harmer
-0.113
3147346CASHSCORNER
Solar/Wind Harmer
0.056
3151801S ANNAS2
50/50
1.35
971377AH1-170 GEN
Solar/Wind Harmer
0.07
3147666LOUISA
Solar/Wind Helper
4.119
3151791S ANNAG2
50/50
2.477
3151761LOISA E
50/50
95.09
315821AE2-092 GEN
Solar/Wind Harmer
0
3151931BEARGRDN S1
50/50
1.249
316164AC1-076 GEN
Solar/Wind Harmer
0
970285AG2-188 GEN
Solar/Wind Harmer
0.353
315651AD1-115 GEN
Solar/Wind Harmer
0
971489AH1-241 GEN
Solar/Wind Harmer
0.349
3151741LOISA C
50/50
41.896
3146776BUCKING
Solar/Wind Harmer
-0.619
970221AG2-151 GEN
Solar/Wind Harmer
0.349
3151781S ANNAS1
50/50
1.35
972183AH1-676 GEN
50/50
596.715
3138266HYDRAULIC
Solar/Wind Harmer
-0.018
3138266HYDRAULIC
Solar/Wind Harmer
-0.011
315683AE1-153 C
Solar/Wind Harmer
3.434
970937AG2-583 GEN
Solar/Wind Harmer
0.311
971845AH1-439 GEN
Solar/Wind Harmer
0.224
CPLELTFEXP_CPLE->PJM
CLTF
0.327
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.033
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.162
LAGNLTFEXP_LAGN->PJM
CLTF
1.083
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.328
TVALTFEXP_TVA->PJM
CLTF
0.566
NYPJM->LTFIMP_NY
CLTF
0.372
LGEELTFEXP_LGEE->PJM
CLTF
0.363
WECLTFEXP_WEC->PJM
CLTF
0.184
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.821
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.1
MECLTFEXP_MEC->PJM
CLTF
0.838
SIGELTFEXP_SIGE->PJM
CLTF
0.027

Details for 6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2199_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2199_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:134.51 %
Rating:909.92 MVA
Rating Type:B
MVA to Mitigate:1223.94
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
3151721LOISA A
50/50
41.896
3151911BEARGRDN G1
50/50
0.691
3132273ORANGE
Solar/Wind Harmer
-0.171
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.062
3146776BUCKING
Solar/Wind Harmer
-0.056
3146776BUCKING
Solar/Wind Harmer
-0.05
3151731LOISA B
50/50
41.896
3151751LOISA D
50/50
41.896
3151921BEARGRDN G2
50/50
0.725
3148013FISHERV
Solar/Wind Harmer
-0.189
3148013FISHERV
Solar/Wind Harmer
-0.109
3147666LOUISA
Solar/Wind Helper
2.368
3151771S ANNAG1
50/50
2.477
971447AH1-217 GEN
Solar/Wind Harmer
0.199
3147623JAMES R
Solar/Wind Harmer
0.009
972003AH1-546 GEN
Solar/Wind Harmer
0.272
3148133STUARTS
Solar/Wind Harmer
-0.113
3147346CASHSCORNER
Solar/Wind Harmer
0.056
3151801S ANNAS2
50/50
1.35
971377AH1-170 GEN
Solar/Wind Harmer
0.07
3147666LOUISA
Solar/Wind Helper
4.119
3151791S ANNAG2
50/50
2.477
3151931BEARGRDN S1
50/50
1.249
316164AC1-076 GEN
Solar/Wind Harmer
0
970285AG2-188 GEN
Solar/Wind Harmer
0.353
315651AD1-115 GEN
Solar/Wind Harmer
0
971489AH1-241 GEN
Solar/Wind Harmer
0.349
3151741LOISA C
50/50
41.896
3146776BUCKING
Solar/Wind Harmer
-0.619
970221AG2-151 GEN
Solar/Wind Harmer
0.349
3151761LOISA E
50/50
95.09
315821AE2-092 GEN
Solar/Wind Harmer
0
3151781S ANNAS1
50/50
1.35
972183AH1-676 GEN
50/50
596.715
3138266HYDRAULIC
Solar/Wind Harmer
-0.018
3138266HYDRAULIC
Solar/Wind Harmer
-0.011
970937AG2-583 GEN
Solar/Wind Harmer
0.311
971845AH1-439 GEN
Solar/Wind Harmer
0.224
CPLELTFEXP_CPLE->PJM
CLTF
0.327
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.033
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.162
LAGNLTFEXP_LAGN->PJM
CLTF
1.083
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.328
TVALTFEXP_TVA->PJM
CLTF
0.566
NYPJM->LTFIMP_NY
CLTF
0.372
LGEELTFEXP_LGEE->PJM
CLTF
0.363
WECLTFEXP_WEC->PJM
CLTF
0.184
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.821
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.1
MECLTFEXP_MEC->PJM
CLTF
0.838
SIGELTFEXP_SIGE->PJM
CLTF
0.027

Details for 6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:127.82 %
Rating:1113.0 MVA
Rating Type:C
MVA to Mitigate:1422.59
MW Contribution:0.4
Bus #Bus NameTypeMW Contribution
3151731LOISA B
50/50
47.136
3151751LOISA D
50/50
47.136
3148013FISHERV
Solar/Wind Harmer
-0.216
3148013FISHERV
Solar/Wind Harmer
-0.124
3147666LOUISA
Solar/Wind Helper
2.119
3147346CASHSCORNER
Solar/Wind Harmer
0.064
3151801S ANNAS2
50/50
1.509
971377AH1-170 GEN
Solar/Wind Harmer
0.08
3147666LOUISA
Solar/Wind Helper
3.685
3151771S ANNAG1
50/50
2.768
971447AH1-217 GEN
Solar/Wind Harmer
0.229
3147623JAMES R
Solar/Wind Harmer
0.01
972003AH1-546 GEN
Solar/Wind Harmer
0.315
3148133STUARTS
Solar/Wind Harmer
-0.13
3151791S ANNAG2
50/50
2.768
970285AG2-188 GEN
Solar/Wind Harmer
0.412
971489AH1-241 GEN
Solar/Wind Harmer
0.402
3151741LOISA C
50/50
47.136
3146776BUCKING
Solar/Wind Harmer
-0.72
3151721LOISA A
50/50
47.136
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.072
3146776BUCKING
Solar/Wind Harmer
-0.065
3146776BUCKING
Solar/Wind Harmer
-0.058
970221AG2-151 GEN
Solar/Wind Harmer
0.402
3151761LOISA E
50/50
106.982
315821AE2-092 GEN
Solar/Wind Harmer
0
3151781S ANNAS1
50/50
1.509
972183AH1-676 GEN
50/50
674.465
3138266HYDRAULIC
Solar/Wind Harmer
-0.02
3138266HYDRAULIC
Solar/Wind Harmer
-0.012
315705AF1-075 GEN
Solar/Wind Harmer
0.185
315683AE1-153 C
Solar/Wind Harmer
3.881
970937AG2-583 GEN
Solar/Wind Harmer
0.363
971845AH1-439 GEN
Solar/Wind Harmer
0.261
CPLELTFEXP_CPLE->PJM
CLTF
0.52
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.499
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.246
LAGNLTFEXP_LAGN->PJM
CLTF
1.331
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.833
TVALTFEXP_TVA->PJM
CLTF
0.693
NYPJM->LTFIMP_NY
CLTF
0.456
LGEELTFEXP_LGEE->PJM
CLTF
0.427
WECLTFEXP_WEC->PJM
CLTF
0.217
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.028
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.556
MECLTFEXP_MEC->PJM
CLTF
0.997
SIGELTFEXP_SIGE->PJM
CLTF
0.032

Details for 6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:127.48 %
Rating:1113.0 MVA
Rating Type:C
MVA to Mitigate:1418.82
MW Contribution:0.4
Bus #Bus NameTypeMW Contribution
3147346CASHSCORNER
Solar/Wind Harmer
0.064
3151801S ANNAS2
50/50
1.509
971377AH1-170 GEN
Solar/Wind Harmer
0.08
3147666LOUISA
Solar/Wind Helper
3.685
3151731LOISA B
50/50
47.136
3151751LOISA D
50/50
47.136
3148013FISHERV
Solar/Wind Harmer
-0.216
3148013FISHERV
Solar/Wind Harmer
-0.124
3147666LOUISA
Solar/Wind Helper
2.119
3151771S ANNAG1
50/50
2.768
971447AH1-217 GEN
Solar/Wind Harmer
0.229
3147623JAMES R
Solar/Wind Harmer
0.01
972003AH1-546 GEN
Solar/Wind Harmer
0.315
3148133STUARTS
Solar/Wind Harmer
-0.13
3151791S ANNAG2
50/50
2.768
970285AG2-188 GEN
Solar/Wind Harmer
0.412
971489AH1-241 GEN
Solar/Wind Harmer
0.402
3151741LOISA C
50/50
47.136
3146776BUCKING
Solar/Wind Harmer
-0.72
3151721LOISA A
50/50
47.136
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.072
3146776BUCKING
Solar/Wind Harmer
-0.065
3146776BUCKING
Solar/Wind Harmer
-0.058
970221AG2-151 GEN
Solar/Wind Harmer
0.402
3151761LOISA E
50/50
106.982
315821AE2-092 GEN
Solar/Wind Harmer
0
3151781S ANNAS1
50/50
1.509
972183AH1-676 GEN
50/50
674.465
3138266HYDRAULIC
Solar/Wind Harmer
-0.02
3138266HYDRAULIC
Solar/Wind Harmer
-0.012
315705AF1-075 GEN
Solar/Wind Harmer
0.185
970937AG2-583 GEN
Solar/Wind Harmer
0.363
971845AH1-439 GEN
Solar/Wind Harmer
0.261
CPLELTFEXP_CPLE->PJM
CLTF
0.52
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.499
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.246
LAGNLTFEXP_LAGN->PJM
CLTF
1.331
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.833
TVALTFEXP_TVA->PJM
CLTF
0.693
NYPJM->LTFIMP_NY
CLTF
0.456
LGEELTFEXP_LGEE->PJM
CLTF
0.427
WECLTFEXP_WEC->PJM
CLTF
0.217
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.028
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.556
MECLTFEXP_MEC->PJM
CLTF
0.997
SIGELTFEXP_SIGE->PJM
CLTF
0.032

Details for 6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line l/o DVP_P4-2: H3T2199_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H3T2199_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.3 %
Rating:1113.0 MVA
Rating Type:C
MVA to Mitigate:1227.6
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
3151721LOISA A
50/50
42.068
3132273ORANGE
Solar/Wind Harmer
-0.165
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.062
3146776BUCKING
Solar/Wind Harmer
-0.056
3146776BUCKING
Solar/Wind Harmer
-0.05
3151731LOISA B
50/50
42.068
3151751LOISA D
50/50
42.068
3148013FISHERV
Solar/Wind Harmer
-0.19
3148013FISHERV
Solar/Wind Harmer
-0.109
3147666LOUISA
Solar/Wind Helper
2.36
3151771S ANNAG1
50/50
2.487
971447AH1-217 GEN
Solar/Wind Harmer
0.2
3147623JAMES R
Solar/Wind Harmer
0.009
972003AH1-546 GEN
Solar/Wind Harmer
0.274
3148133STUARTS
Solar/Wind Harmer
-0.114
3147346CASHSCORNER
Solar/Wind Harmer
0.057
3151801S ANNAS2
50/50
1.356
971377AH1-170 GEN
Solar/Wind Harmer
0.07
3147666LOUISA
Solar/Wind Helper
4.105
3151791S ANNAG2
50/50
2.487
316164AC1-076 GEN
Solar/Wind Harmer
0
970285AG2-188 GEN
Solar/Wind Harmer
0.355
315651AD1-115 GEN
Solar/Wind Harmer
0
971489AH1-241 GEN
Solar/Wind Harmer
0.351
3151741LOISA C
50/50
42.068
3146776BUCKING
Solar/Wind Harmer
-0.622
970221AG2-151 GEN
Solar/Wind Harmer
0.351
3151761LOISA E
50/50
95.481
315821AE2-092 GEN
Solar/Wind Harmer
0
3151781S ANNAS1
50/50
1.356
972183AH1-676 GEN
50/50
599.271
3138266HYDRAULIC
Solar/Wind Harmer
-0.018
3138266HYDRAULIC
Solar/Wind Harmer
-0.011
970937AG2-583 GEN
Solar/Wind Harmer
0.313
971845AH1-439 GEN
Solar/Wind Harmer
0.226
CPLELTFEXP_CPLE->PJM
CLTF
0.333
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.081
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.165
LAGNLTFEXP_LAGN->PJM
CLTF
1.091
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.345
TVALTFEXP_TVA->PJM
CLTF
0.57
NYPJM->LTFIMP_NY
CLTF
0.375
LGEELTFEXP_LGEE->PJM
CLTF
0.365
WECLTFEXP_WEC->PJM
CLTF
0.186
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.861
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.115
MECLTFEXP_MEC->PJM
CLTF
0.843
SIGELTFEXP_SIGE->PJM
CLTF
0.028

Details for 6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2199T2331_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2199T2331_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.86 %
Rating:1113.0 MVA
Rating Type:C
MVA to Mitigate:1222.79
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
3151731LOISA B
50/50
41.896
3151751LOISA D
50/50
41.896
3148013FISHERV
Solar/Wind Harmer
-0.189
3148013FISHERV
Solar/Wind Harmer
-0.109
3147666LOUISA
Solar/Wind Helper
2.368
3151771S ANNAG1
50/50
2.477
971447AH1-217 GEN
Solar/Wind Harmer
0.199
3147623JAMES R
Solar/Wind Harmer
0.009
972003AH1-546 GEN
Solar/Wind Harmer
0.272
3148133STUARTS
Solar/Wind Harmer
-0.113
3147346CASHSCORNER
Solar/Wind Harmer
0.056
3151801S ANNAS2
50/50
1.35
971377AH1-170 GEN
Solar/Wind Harmer
0.07
3147666LOUISA
Solar/Wind Helper
4.119
3151791S ANNAG2
50/50
2.477
316164AC1-076 GEN
Solar/Wind Harmer
0
970285AG2-188 GEN
Solar/Wind Harmer
0.353
315651AD1-115 GEN
Solar/Wind Harmer
0
3151721LOISA A
50/50
41.896
3132273ORANGE
Solar/Wind Harmer
-0.171
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.062
3146776BUCKING
Solar/Wind Harmer
-0.056
3146776BUCKING
Solar/Wind Harmer
-0.05
971489AH1-241 GEN
Solar/Wind Harmer
0.349
3151741LOISA C
50/50
41.896
3146776BUCKING
Solar/Wind Harmer
-0.619
970221AG2-151 GEN
Solar/Wind Harmer
0.349
3151761LOISA E
50/50
95.09
315821AE2-092 GEN
Solar/Wind Harmer
0
3151781S ANNAS1
50/50
1.35
972183AH1-676 GEN
50/50
596.715
3138266HYDRAULIC
Solar/Wind Harmer
-0.018
3138266HYDRAULIC
Solar/Wind Harmer
-0.011
315683AE1-153 C
Solar/Wind Harmer
3.434
970937AG2-583 GEN
Solar/Wind Harmer
0.311
971845AH1-439 GEN
Solar/Wind Harmer
0.224
CPLELTFEXP_CPLE->PJM
CLTF
0.327
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.033
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.162
LAGNLTFEXP_LAGN->PJM
CLTF
1.083
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.328
TVALTFEXP_TVA->PJM
CLTF
0.566
NYPJM->LTFIMP_NY
CLTF
0.372
LGEELTFEXP_LGEE->PJM
CLTF
0.363
WECLTFEXP_WEC->PJM
CLTF
0.184
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.821
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.1
MECLTFEXP_MEC->PJM
CLTF
0.838
SIGELTFEXP_SIGE->PJM
CLTF
0.027

Details for 6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line l/o DVP_P2-2: GERMANNA_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6DESPER-6LOUISA PUMP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: GERMANNA_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:109.56 %
Rating:1113.0 MVA
Rating Type:C
MVA to Mitigate:1219.44
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
3151771S ANNAG1
50/50
2.477
971447AH1-217 GEN
Solar/Wind Harmer
0.199
3147623JAMES R
Solar/Wind Harmer
0.009
972003AH1-546 GEN
Solar/Wind Harmer
0.272
3148133STUARTS
Solar/Wind Harmer
-0.113
3151731LOISA B
50/50
41.896
3151751LOISA D
50/50
41.896
3148013FISHERV
Solar/Wind Harmer
-0.189
3148013FISHERV
Solar/Wind Harmer
-0.109
3147666LOUISA
Solar/Wind Helper
2.368
3147346CASHSCORNER
Solar/Wind Harmer
0.056
3151801S ANNAS2
50/50
1.35
971377AH1-170 GEN
Solar/Wind Harmer
0.07
3147666LOUISA
Solar/Wind Helper
4.119
3151791S ANNAG2
50/50
2.477
316164AC1-076 GEN
Solar/Wind Harmer
0
970285AG2-188 GEN
Solar/Wind Harmer
0.353
315651AD1-115 GEN
Solar/Wind Harmer
0
971489AH1-241 GEN
Solar/Wind Harmer
0.349
3151741LOISA C
50/50
41.896
3146776BUCKING
Solar/Wind Harmer
-0.619
3151721LOISA A
50/50
41.896
3132273ORANGE
Solar/Wind Harmer
-0.171
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.062
3146776BUCKING
Solar/Wind Harmer
-0.056
3146776BUCKING
Solar/Wind Harmer
-0.05
970221AG2-151 GEN
Solar/Wind Harmer
0.349
3151761LOISA E
50/50
95.09
315821AE2-092 GEN
Solar/Wind Harmer
0
3151781S ANNAS1
50/50
1.35
972183AH1-676 GEN
50/50
596.715
3138266HYDRAULIC
Solar/Wind Harmer
-0.018
3138266HYDRAULIC
Solar/Wind Harmer
-0.011
970937AG2-583 GEN
Solar/Wind Harmer
0.311
971845AH1-439 GEN
Solar/Wind Harmer
0.224
CPLELTFEXP_CPLE->PJM
CLTF
0.327
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.033
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.162
LAGNLTFEXP_LAGN->PJM
CLTF
1.083
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.328
TVALTFEXP_TVA->PJM
CLTF
0.566
NYPJM->LTFIMP_NY
CLTF
0.372
LGEELTFEXP_LGEE->PJM
CLTF
0.363
WECLTFEXP_WEC->PJM
CLTF
0.184
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.821
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.1
MECLTFEXP_MEC->PJM
CLTF
0.838
SIGELTFEXP_SIGE->PJM
CLTF
0.027

Details for 6LOISACT-6S ANNA 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
6LOISACT-6S ANNA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.34 %
Rating:1061.0 MVA
Rating Type:C
MVA to Mitigate:1149.54
MW Contribution:0.41
Bus #Bus NameTypeMW Contribution
3147346CASHSCORNER
Solar/Wind Harmer
0.064
971377AH1-170 GEN
Solar/Wind Harmer
0.082
3147666LOUISA
Solar/Wind Helper
3.661
3151731LOISA B
50/50
47.304
3151751LOISA D
50/50
47.304
3148013FISHERV
Solar/Wind Harmer
-0.221
3148013FISHERV
Solar/Wind Harmer
-0.127
3147666LOUISA
Solar/Wind Helper
2.105
971447AH1-217 GEN
Solar/Wind Harmer
0.235
3147623JAMES R
Solar/Wind Harmer
0.011
972003AH1-546 GEN
Solar/Wind Harmer
0.322
3148133STUARTS
Solar/Wind Harmer
-0.133
3147983MERCK5
Solar/Wind Harmer
-0.059
970285AG2-188 GEN
Solar/Wind Harmer
0.426
971489AH1-241 GEN
Solar/Wind Harmer
0.411
3151741LOISA C
50/50
47.304
3146776BUCKING
Solar/Wind Harmer
-0.741
3151721LOISA A
50/50
47.304
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.074
3146776BUCKING
Solar/Wind Harmer
-0.067
3146776BUCKING
Solar/Wind Harmer
-0.06
970221AG2-151 GEN
Solar/Wind Harmer
0.411
3151761LOISA E
50/50
107.364
315821AE2-092 GEN
Solar/Wind Harmer
0
972183AH1-676 GEN
50/50
676.911
3138266HYDRAULIC
Solar/Wind Harmer
-0.02
3138266HYDRAULIC
Solar/Wind Harmer
-0.013
315705AF1-075 GEN
Solar/Wind Harmer
0.192
316192AB2-158 GEN
Solar/Wind Helper
1.34
315683AE1-153 C
Solar/Wind Harmer
3.895
970937AG2-583 GEN
Solar/Wind Harmer
0.374
971845AH1-439 GEN
Solar/Wind Harmer
0.269
CPLELTFEXP_CPLE->PJM
CLTF
0.699
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.693
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.246
LAGNLTFEXP_LAGN->PJM
CLTF
1.661
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.326
TVALTFEXP_TVA->PJM
CLTF
0.859
NYPJM->LTFIMP_NY
CLTF
0.352
LGEELTFEXP_LGEE->PJM
CLTF
0.54
WECLTFEXP_WEC->PJM
CLTF
0.279
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.406
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.175
MECLTFEXP_MEC->PJM
CLTF
1.27
SIGELTFEXP_SIGE->PJM
CLTF
0.041

Details for 6LOISACT-6S ANNA 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6LOISACT-6S ANNA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:107.99 %
Rating:1061.0 MVA
Rating Type:C
MVA to Mitigate:1145.72
MW Contribution:0.41
Bus #Bus NameTypeMW Contribution
3147346CASHSCORNER
Solar/Wind Harmer
0.064
971377AH1-170 GEN
Solar/Wind Harmer
0.082
3147666LOUISA
Solar/Wind Helper
3.661
971447AH1-217 GEN
Solar/Wind Harmer
0.235
3147623JAMES R
Solar/Wind Harmer
0.011
972003AH1-546 GEN
Solar/Wind Harmer
0.322
3148133STUARTS
Solar/Wind Harmer
-0.133
3147983MERCK5
Solar/Wind Harmer
-0.059
970285AG2-188 GEN
Solar/Wind Harmer
0.426
971489AH1-241 GEN
Solar/Wind Harmer
0.411
3151741LOISA C
50/50
47.304
3146776BUCKING
Solar/Wind Harmer
-0.741
3151721LOISA A
50/50
47.304
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.074
3146776BUCKING
Solar/Wind Harmer
-0.067
3146776BUCKING
Solar/Wind Harmer
-0.06
970221AG2-151 GEN
Solar/Wind Harmer
0.411
3151731LOISA B
50/50
47.304
3151751LOISA D
50/50
47.304
3148013FISHERV
Solar/Wind Harmer
-0.221
3148013FISHERV
Solar/Wind Harmer
-0.127
3147666LOUISA
Solar/Wind Helper
2.105
3151761LOISA E
50/50
107.364
315821AE2-092 GEN
Solar/Wind Harmer
0
972183AH1-676 GEN
50/50
676.911
3138266HYDRAULIC
Solar/Wind Harmer
-0.02
3138266HYDRAULIC
Solar/Wind Harmer
-0.013
315705AF1-075 GEN
Solar/Wind Harmer
0.192
316192AB2-158 GEN
Solar/Wind Helper
1.34
970937AG2-583 GEN
Solar/Wind Harmer
0.374
971845AH1-439 GEN
Solar/Wind Harmer
0.269
CPLELTFEXP_CPLE->PJM
CLTF
0.699
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.693
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.246
LAGNLTFEXP_LAGN->PJM
CLTF
1.661
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.326
TVALTFEXP_TVA->PJM
CLTF
0.859
NYPJM->LTFIMP_NY
CLTF
0.352
LGEELTFEXP_LGEE->PJM
CLTF
0.54
WECLTFEXP_WEC->PJM
CLTF
0.279
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.406
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.175
MECLTFEXP_MEC->PJM
CLTF
1.27
SIGELTFEXP_SIGE->PJM
CLTF
0.041

Details for 6LOISACT-6S ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2199_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
6LOISACT-6S ANNA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2199_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.03 %
Rating:909.92 MVA
Rating Type:B
MVA to Mitigate:955.68
MW Contribution:0.36
Bus #Bus NameTypeMW Contribution
3151721LOISA A
50/50
42.064
3151911BEARGRDN G1
50/50
0.71
3132273ORANGE
Solar/Wind Harmer
-0.172
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.064
3146776BUCKING
Solar/Wind Harmer
-0.058
3146776BUCKING
Solar/Wind Harmer
-0.052
3151731LOISA B
50/50
42.064
3151751LOISA D
50/50
42.064
3151921BEARGRDN G2
50/50
0.744
3148013FISHERV
Solar/Wind Harmer
-0.194
3148013FISHERV
Solar/Wind Harmer
-0.112
3147666LOUISA
Solar/Wind Helper
2.355
971447AH1-217 GEN
Solar/Wind Harmer
0.205
3147623JAMES R
Solar/Wind Harmer
0.009
972003AH1-546 GEN
Solar/Wind Harmer
0.28
3148133STUARTS
Solar/Wind Harmer
-0.117
3147346CASHSCORNER
Solar/Wind Harmer
0.057
971377AH1-170 GEN
Solar/Wind Harmer
0.072
3147666LOUISA
Solar/Wind Helper
4.095
3151931BEARGRDN S1
50/50
1.282
316164AC1-076 GEN
Solar/Wind Harmer
0
970285AG2-188 GEN
Solar/Wind Harmer
0.367
315651AD1-115 GEN
Solar/Wind Harmer
0
971489AH1-241 GEN
Solar/Wind Harmer
0.358
3151741LOISA C
50/50
42.064
3146776BUCKING
Solar/Wind Harmer
-0.64
970221AG2-151 GEN
Solar/Wind Harmer
0.358
3151761LOISA E
50/50
95.472
315821AE2-092 GEN
Solar/Wind Harmer
0
972183AH1-676 GEN
50/50
599.161
3138266HYDRAULIC
Solar/Wind Harmer
-0.018
3138266HYDRAULIC
Solar/Wind Harmer
-0.011
316192AB2-158 GEN
Solar/Wind Helper
1.5
315683AE1-153 C
Solar/Wind Harmer
3.448
970937AG2-583 GEN
Solar/Wind Harmer
0.322
971845AH1-439 GEN
Solar/Wind Harmer
0.232
CPLELTFEXP_CPLE->PJM
CLTF
0.506
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.228
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.162
LAGNLTFEXP_LAGN->PJM
CLTF
1.414
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.821
TVALTFEXP_TVA->PJM
CLTF
0.731
NYPJM->LTFIMP_NY
CLTF
0.267
LGEELTFEXP_LGEE->PJM
CLTF
0.475
WECLTFEXP_WEC->PJM
CLTF
0.247
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.199
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.719
MECLTFEXP_MEC->PJM
CLTF
1.112
SIGELTFEXP_SIGE->PJM
CLTF
0.036

Details for 6LOISACT-6S ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2199_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6LOISACT-6S ANNA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2199_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.66 %
Rating:909.92 MVA
Rating Type:B
MVA to Mitigate:952.3
MW Contribution:0.36
Bus #Bus NameTypeMW Contribution
3151721LOISA A
50/50
42.064
3151911BEARGRDN G1
50/50
0.71
3132273ORANGE
Solar/Wind Harmer
-0.172
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.064
3146776BUCKING
Solar/Wind Harmer
-0.058
3146776BUCKING
Solar/Wind Harmer
-0.052
3151731LOISA B
50/50
42.064
3151751LOISA D
50/50
42.064
3151921BEARGRDN G2
50/50
0.744
3148013FISHERV
Solar/Wind Harmer
-0.194
3148013FISHERV
Solar/Wind Harmer
-0.112
3147666LOUISA
Solar/Wind Helper
2.355
971447AH1-217 GEN
Solar/Wind Harmer
0.205
3147623JAMES R
Solar/Wind Harmer
0.009
972003AH1-546 GEN
Solar/Wind Harmer
0.28
3148133STUARTS
Solar/Wind Harmer
-0.117
3147346CASHSCORNER
Solar/Wind Harmer
0.057
971377AH1-170 GEN
Solar/Wind Harmer
0.072
3147666LOUISA
Solar/Wind Helper
4.095
3151931BEARGRDN S1
50/50
1.282
316164AC1-076 GEN
Solar/Wind Harmer
0
970285AG2-188 GEN
Solar/Wind Harmer
0.367
315651AD1-115 GEN
Solar/Wind Harmer
0
971489AH1-241 GEN
Solar/Wind Harmer
0.358
3151741LOISA C
50/50
42.064
3146776BUCKING
Solar/Wind Harmer
-0.64
970221AG2-151 GEN
Solar/Wind Harmer
0.358
3151761LOISA E
50/50
95.472
315821AE2-092 GEN
Solar/Wind Harmer
0
972183AH1-676 GEN
50/50
599.161
3138266HYDRAULIC
Solar/Wind Harmer
-0.018
3138266HYDRAULIC
Solar/Wind Harmer
-0.011
316192AB2-158 GEN
Solar/Wind Helper
1.5
970937AG2-583 GEN
Solar/Wind Harmer
0.322
971845AH1-439 GEN
Solar/Wind Harmer
0.232
CPLELTFEXP_CPLE->PJM
CLTF
0.506
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.228
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.162
LAGNLTFEXP_LAGN->PJM
CLTF
1.414
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.821
TVALTFEXP_TVA->PJM
CLTF
0.731
NYPJM->LTFIMP_NY
CLTF
0.267
LGEELTFEXP_LGEE->PJM
CLTF
0.475
WECLTFEXP_WEC->PJM
CLTF
0.247
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.199
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.719
MECLTFEXP_MEC->PJM
CLTF
1.112
SIGELTFEXP_SIGE->PJM
CLTF
0.036

Details for 6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2199_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2199_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:134.87 %
Rating:909.92 MVA
Rating Type:B
MVA to Mitigate:1227.24
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
3151721LOISA A
50/50
41.896
3151911BEARGRDN G1
50/50
0.691
3132273ORANGE
Solar/Wind Harmer
-0.171
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.062
3146776BUCKING
Solar/Wind Harmer
-0.056
3146776BUCKING
Solar/Wind Harmer
-0.05
3151731LOISA B
50/50
41.896
3151751LOISA D
50/50
41.896
3151921BEARGRDN G2
50/50
0.725
3148013FISHERV
Solar/Wind Harmer
-0.189
3148013FISHERV
Solar/Wind Harmer
-0.109
3147666LOUISA
Solar/Wind Helper
2.368
3151771S ANNAG1
50/50
2.477
971447AH1-217 GEN
Solar/Wind Harmer
0.199
3147623JAMES R
Solar/Wind Harmer
0.009
972003AH1-546 GEN
Solar/Wind Harmer
0.272
3148133STUARTS
Solar/Wind Harmer
-0.113
3147346CASHSCORNER
Solar/Wind Harmer
0.056
3151801S ANNAS2
50/50
1.35
971377AH1-170 GEN
Solar/Wind Harmer
0.07
3147666LOUISA
Solar/Wind Helper
4.119
3151791S ANNAG2
50/50
2.477
3151761LOISA E
50/50
95.09
3151931BEARGRDN S1
50/50
1.249
316164AC1-076 GEN
Solar/Wind Harmer
0
970285AG2-188 GEN
Solar/Wind Harmer
0.353
315651AD1-115 GEN
Solar/Wind Harmer
0
971489AH1-241 GEN
Solar/Wind Harmer
0.349
3151741LOISA C
50/50
41.896
3146776BUCKING
Solar/Wind Harmer
-0.619
970221AG2-151 GEN
Solar/Wind Harmer
0.349
315821AE2-092 GEN
Solar/Wind Harmer
0
3151781S ANNAS1
50/50
1.35
972183AH1-676 GEN
50/50
596.715
3138266HYDRAULIC
Solar/Wind Harmer
-0.018
3138266HYDRAULIC
Solar/Wind Harmer
-0.011
315683AE1-153 C
Solar/Wind Harmer
3.434
970937AG2-583 GEN
Solar/Wind Harmer
0.311
971845AH1-439 GEN
Solar/Wind Harmer
0.224
CPLELTFEXP_CPLE->PJM
CLTF
0.327
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.033
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.162
LAGNLTFEXP_LAGN->PJM
CLTF
1.083
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.328
TVALTFEXP_TVA->PJM
CLTF
0.566
NYPJM->LTFIMP_NY
CLTF
0.372
LGEELTFEXP_LGEE->PJM
CLTF
0.363
WECLTFEXP_WEC->PJM
CLTF
0.184
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.821
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.1
MECLTFEXP_MEC->PJM
CLTF
0.838
SIGELTFEXP_SIGE->PJM
CLTF
0.027

Details for 6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2199_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2199_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:134.51 %
Rating:909.92 MVA
Rating Type:B
MVA to Mitigate:1223.9
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
3151721LOISA A
50/50
41.896
3151911BEARGRDN G1
50/50
0.691
3132273ORANGE
Solar/Wind Harmer
-0.171
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.062
3146776BUCKING
Solar/Wind Harmer
-0.056
3146776BUCKING
Solar/Wind Harmer
-0.05
3151731LOISA B
50/50
41.896
3151751LOISA D
50/50
41.896
3151921BEARGRDN G2
50/50
0.725
3148013FISHERV
Solar/Wind Harmer
-0.189
3148013FISHERV
Solar/Wind Harmer
-0.109
3147666LOUISA
Solar/Wind Helper
2.368
3151771S ANNAG1
50/50
2.477
971447AH1-217 GEN
Solar/Wind Harmer
0.199
3147623JAMES R
Solar/Wind Harmer
0.009
972003AH1-546 GEN
Solar/Wind Harmer
0.272
3148133STUARTS
Solar/Wind Harmer
-0.113
3147346CASHSCORNER
Solar/Wind Harmer
0.056
3151801S ANNAS2
50/50
1.35
971377AH1-170 GEN
Solar/Wind Harmer
0.07
3147666LOUISA
Solar/Wind Helper
4.119
3151791S ANNAG2
50/50
2.477
3151931BEARGRDN S1
50/50
1.249
316164AC1-076 GEN
Solar/Wind Harmer
0
970285AG2-188 GEN
Solar/Wind Harmer
0.353
315651AD1-115 GEN
Solar/Wind Harmer
0
971489AH1-241 GEN
Solar/Wind Harmer
0.349
3151741LOISA C
50/50
41.896
3146776BUCKING
Solar/Wind Harmer
-0.619
970221AG2-151 GEN
Solar/Wind Harmer
0.349
3151761LOISA E
50/50
95.09
315821AE2-092 GEN
Solar/Wind Harmer
0
3151781S ANNAS1
50/50
1.35
972183AH1-676 GEN
50/50
596.715
3138266HYDRAULIC
Solar/Wind Harmer
-0.018
3138266HYDRAULIC
Solar/Wind Harmer
-0.011
970937AG2-583 GEN
Solar/Wind Harmer
0.311
971845AH1-439 GEN
Solar/Wind Harmer
0.224
CPLELTFEXP_CPLE->PJM
CLTF
0.327
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.033
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.162
LAGNLTFEXP_LAGN->PJM
CLTF
1.083
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.328
TVALTFEXP_TVA->PJM
CLTF
0.566
NYPJM->LTFIMP_NY
CLTF
0.372
LGEELTFEXP_LGEE->PJM
CLTF
0.363
WECLTFEXP_WEC->PJM
CLTF
0.184
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.821
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.1
MECLTFEXP_MEC->PJM
CLTF
0.838
SIGELTFEXP_SIGE->PJM
CLTF
0.027

Details for 6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:127.81 %
Rating:1113.0 MVA
Rating Type:C
MVA to Mitigate:1422.56
MW Contribution:0.4
Bus #Bus NameTypeMW Contribution
3151731LOISA B
50/50
47.136
3151751LOISA D
50/50
47.136
3148013FISHERV
Solar/Wind Harmer
-0.216
3148013FISHERV
Solar/Wind Harmer
-0.124
3147666LOUISA
Solar/Wind Helper
2.119
3147346CASHSCORNER
Solar/Wind Harmer
0.064
3151801S ANNAS2
50/50
1.509
971377AH1-170 GEN
Solar/Wind Harmer
0.08
3147666LOUISA
Solar/Wind Helper
3.685
3151771S ANNAG1
50/50
2.768
971447AH1-217 GEN
Solar/Wind Harmer
0.229
3147623JAMES R
Solar/Wind Harmer
0.01
972003AH1-546 GEN
Solar/Wind Harmer
0.315
3148133STUARTS
Solar/Wind Harmer
-0.13
3151791S ANNAG2
50/50
2.768
970285AG2-188 GEN
Solar/Wind Harmer
0.412
971489AH1-241 GEN
Solar/Wind Harmer
0.402
3151741LOISA C
50/50
47.136
3146776BUCKING
Solar/Wind Harmer
-0.72
3151721LOISA A
50/50
47.136
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.072
3146776BUCKING
Solar/Wind Harmer
-0.065
3146776BUCKING
Solar/Wind Harmer
-0.058
970221AG2-151 GEN
Solar/Wind Harmer
0.402
3151761LOISA E
50/50
106.982
315821AE2-092 GEN
Solar/Wind Harmer
0
3151781S ANNAS1
50/50
1.509
972183AH1-676 GEN
50/50
674.465
3138266HYDRAULIC
Solar/Wind Harmer
-0.02
3138266HYDRAULIC
Solar/Wind Harmer
-0.012
315705AF1-075 GEN
Solar/Wind Harmer
0.185
315683AE1-153 C
Solar/Wind Harmer
3.881
970937AG2-583 GEN
Solar/Wind Harmer
0.363
971845AH1-439 GEN
Solar/Wind Harmer
0.261
CPLELTFEXP_CPLE->PJM
CLTF
0.52
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.499
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.246
LAGNLTFEXP_LAGN->PJM
CLTF
1.331
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.833
TVALTFEXP_TVA->PJM
CLTF
0.693
NYPJM->LTFIMP_NY
CLTF
0.456
LGEELTFEXP_LGEE->PJM
CLTF
0.427
WECLTFEXP_WEC->PJM
CLTF
0.217
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.028
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.556
MECLTFEXP_MEC->PJM
CLTF
0.997
SIGELTFEXP_SIGE->PJM
CLTF
0.032

Details for 6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:127.47 %
Rating:1113.0 MVA
Rating Type:C
MVA to Mitigate:1418.79
MW Contribution:0.4
Bus #Bus NameTypeMW Contribution
3147346CASHSCORNER
Solar/Wind Harmer
0.064
3151801S ANNAS2
50/50
1.509
971377AH1-170 GEN
Solar/Wind Harmer
0.08
3147666LOUISA
Solar/Wind Helper
3.685
3151731LOISA B
50/50
47.136
3151751LOISA D
50/50
47.136
3148013FISHERV
Solar/Wind Harmer
-0.216
3148013FISHERV
Solar/Wind Harmer
-0.124
3147666LOUISA
Solar/Wind Helper
2.119
3151771S ANNAG1
50/50
2.768
971447AH1-217 GEN
Solar/Wind Harmer
0.229
3147623JAMES R
Solar/Wind Harmer
0.01
972003AH1-546 GEN
Solar/Wind Harmer
0.315
3148133STUARTS
Solar/Wind Harmer
-0.13
3151791S ANNAG2
50/50
2.768
970285AG2-188 GEN
Solar/Wind Harmer
0.412
971489AH1-241 GEN
Solar/Wind Harmer
0.402
3151741LOISA C
50/50
47.136
3146776BUCKING
Solar/Wind Harmer
-0.72
3151721LOISA A
50/50
47.136
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.072
3146776BUCKING
Solar/Wind Harmer
-0.065
3146776BUCKING
Solar/Wind Harmer
-0.058
970221AG2-151 GEN
Solar/Wind Harmer
0.402
3151761LOISA E
50/50
106.982
315821AE2-092 GEN
Solar/Wind Harmer
0
3151781S ANNAS1
50/50
1.509
972183AH1-676 GEN
50/50
674.465
3138266HYDRAULIC
Solar/Wind Harmer
-0.02
3138266HYDRAULIC
Solar/Wind Harmer
-0.012
315705AF1-075 GEN
Solar/Wind Harmer
0.185
970937AG2-583 GEN
Solar/Wind Harmer
0.363
971845AH1-439 GEN
Solar/Wind Harmer
0.261
CPLELTFEXP_CPLE->PJM
CLTF
0.52
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.499
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.246
LAGNLTFEXP_LAGN->PJM
CLTF
1.331
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.833
TVALTFEXP_TVA->PJM
CLTF
0.693
NYPJM->LTFIMP_NY
CLTF
0.456
LGEELTFEXP_LGEE->PJM
CLTF
0.427
WECLTFEXP_WEC->PJM
CLTF
0.217
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.028
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.556
MECLTFEXP_MEC->PJM
CLTF
0.997
SIGELTFEXP_SIGE->PJM
CLTF
0.032

Details for 6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line l/o DVP_P4-2: H3T2199_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H3T2199_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.29 %
Rating:1113.0 MVA
Rating Type:C
MVA to Mitigate:1227.56
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
3151721LOISA A
50/50
42.068
3132273ORANGE
Solar/Wind Harmer
-0.165
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.062
3146776BUCKING
Solar/Wind Harmer
-0.056
3151731LOISA B
50/50
42.068
3151751LOISA D
50/50
42.068
3148013FISHERV
Solar/Wind Harmer
-0.19
3148013FISHERV
Solar/Wind Harmer
-0.109
3147666LOUISA
Solar/Wind Helper
2.36
3151771S ANNAG1
50/50
2.487
971447AH1-217 GEN
Solar/Wind Harmer
0.2
3147623JAMES R
Solar/Wind Harmer
0.009
972003AH1-546 GEN
Solar/Wind Harmer
0.274
3148133STUARTS
Solar/Wind Harmer
-0.114
3147346CASHSCORNER
Solar/Wind Harmer
0.057
3151801S ANNAS2
50/50
1.356
971377AH1-170 GEN
Solar/Wind Harmer
0.07
3147666LOUISA
Solar/Wind Helper
4.105
3151791S ANNAG2
50/50
2.487
316164AC1-076 GEN
Solar/Wind Harmer
0
970285AG2-188 GEN
Solar/Wind Harmer
0.355
315651AD1-115 GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.05
971489AH1-241 GEN
Solar/Wind Harmer
0.351
3151741LOISA C
50/50
42.068
3146776BUCKING
Solar/Wind Harmer
-0.622
970221AG2-151 GEN
Solar/Wind Harmer
0.351
3151761LOISA E
50/50
95.481
315821AE2-092 GEN
Solar/Wind Harmer
0
3151781S ANNAS1
50/50
1.356
972183AH1-676 GEN
50/50
599.271
3138266HYDRAULIC
Solar/Wind Harmer
-0.018
3138266HYDRAULIC
Solar/Wind Harmer
-0.011
970937AG2-583 GEN
Solar/Wind Harmer
0.313
971845AH1-439 GEN
Solar/Wind Harmer
0.226
CPLELTFEXP_CPLE->PJM
CLTF
0.333
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.081
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.165
LAGNLTFEXP_LAGN->PJM
CLTF
1.091
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.345
TVALTFEXP_TVA->PJM
CLTF
0.57
NYPJM->LTFIMP_NY
CLTF
0.375
LGEELTFEXP_LGEE->PJM
CLTF
0.365
WECLTFEXP_WEC->PJM
CLTF
0.186
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.861
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.115
MECLTFEXP_MEC->PJM
CLTF
0.843
SIGELTFEXP_SIGE->PJM
CLTF
0.028

Details for 6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line l/o DVP_P4-2: 2199T2331_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2199T2331_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.86 %
Rating:1113.0 MVA
Rating Type:C
MVA to Mitigate:1222.75
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
3151731LOISA B
50/50
41.896
3151751LOISA D
50/50
41.896
3148013FISHERV
Solar/Wind Harmer
-0.189
3148013FISHERV
Solar/Wind Harmer
-0.109
3147666LOUISA
Solar/Wind Helper
2.368
3151771S ANNAG1
50/50
2.477
971447AH1-217 GEN
Solar/Wind Harmer
0.199
3147623JAMES R
Solar/Wind Harmer
0.009
972003AH1-546 GEN
Solar/Wind Harmer
0.272
3148133STUARTS
Solar/Wind Harmer
-0.113
3147346CASHSCORNER
Solar/Wind Harmer
0.056
3151801S ANNAS2
50/50
1.35
971377AH1-170 GEN
Solar/Wind Harmer
0.07
3147666LOUISA
Solar/Wind Helper
4.119
3151791S ANNAG2
50/50
2.477
316164AC1-076 GEN
Solar/Wind Harmer
0
970285AG2-188 GEN
Solar/Wind Harmer
0.353
315651AD1-115 GEN
Solar/Wind Harmer
0
3151721LOISA A
50/50
41.896
3132273ORANGE
Solar/Wind Harmer
-0.171
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.062
3146776BUCKING
Solar/Wind Harmer
-0.056
3146776BUCKING
Solar/Wind Harmer
-0.05
971489AH1-241 GEN
Solar/Wind Harmer
0.349
3151741LOISA C
50/50
41.896
3146776BUCKING
Solar/Wind Harmer
-0.619
970221AG2-151 GEN
Solar/Wind Harmer
0.349
3151761LOISA E
50/50
95.09
315821AE2-092 GEN
Solar/Wind Harmer
0
3151781S ANNAS1
50/50
1.35
972183AH1-676 GEN
50/50
596.715
3138266HYDRAULIC
Solar/Wind Harmer
-0.018
3138266HYDRAULIC
Solar/Wind Harmer
-0.011
315683AE1-153 C
Solar/Wind Harmer
3.434
970937AG2-583 GEN
Solar/Wind Harmer
0.311
971845AH1-439 GEN
Solar/Wind Harmer
0.224
CPLELTFEXP_CPLE->PJM
CLTF
0.327
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.033
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.162
LAGNLTFEXP_LAGN->PJM
CLTF
1.083
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.328
TVALTFEXP_TVA->PJM
CLTF
0.566
NYPJM->LTFIMP_NY
CLTF
0.372
LGEELTFEXP_LGEE->PJM
CLTF
0.363
WECLTFEXP_WEC->PJM
CLTF
0.184
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.821
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.1
MECLTFEXP_MEC->PJM
CLTF
0.838
SIGELTFEXP_SIGE->PJM
CLTF
0.027

Details for 6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line l/o DVP_P2-2: GERMANNA_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: GERMANNA_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:109.56 %
Rating:1113.0 MVA
Rating Type:C
MVA to Mitigate:1219.41
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
3151771S ANNAG1
50/50
2.477
971447AH1-217 GEN
Solar/Wind Harmer
0.199
3147623JAMES R
Solar/Wind Harmer
0.009
972003AH1-546 GEN
Solar/Wind Harmer
0.272
3151731LOISA B
50/50
41.896
3151751LOISA D
50/50
41.896
3148013FISHERV
Solar/Wind Harmer
-0.189
3148013FISHERV
Solar/Wind Harmer
-0.109
3147666LOUISA
Solar/Wind Helper
2.368
3147346CASHSCORNER
Solar/Wind Harmer
0.056
3151801S ANNAS2
50/50
1.35
971377AH1-170 GEN
Solar/Wind Harmer
0.07
3147666LOUISA
Solar/Wind Helper
4.119
3148133STUARTS
Solar/Wind Harmer
-0.113
3151791S ANNAG2
50/50
2.477
316164AC1-076 GEN
Solar/Wind Harmer
0
970285AG2-188 GEN
Solar/Wind Harmer
0.353
315651AD1-115 GEN
Solar/Wind Harmer
0
971489AH1-241 GEN
Solar/Wind Harmer
0.349
3151741LOISA C
50/50
41.896
3146776BUCKING
Solar/Wind Harmer
-0.619
3151721LOISA A
50/50
41.896
3132273ORANGE
Solar/Wind Harmer
-0.171
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.062
3146776BUCKING
Solar/Wind Harmer
-0.056
3146776BUCKING
Solar/Wind Harmer
-0.05
970221AG2-151 GEN
Solar/Wind Harmer
0.349
3151761LOISA E
50/50
95.09
315821AE2-092 GEN
Solar/Wind Harmer
0
3151781S ANNAS1
50/50
1.35
972183AH1-676 GEN
50/50
596.715
3138266HYDRAULIC
Solar/Wind Harmer
-0.018
3138266HYDRAULIC
Solar/Wind Harmer
-0.011
970937AG2-583 GEN
Solar/Wind Harmer
0.311
971845AH1-439 GEN
Solar/Wind Harmer
0.224
CPLELTFEXP_CPLE->PJM
CLTF
0.327
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.033
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.162
LAGNLTFEXP_LAGN->PJM
CLTF
1.083
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.328
TVALTFEXP_TVA->PJM
CLTF
0.566
NYPJM->LTFIMP_NY
CLTF
0.372
LGEELTFEXP_LGEE->PJM
CLTF
0.363
WECLTFEXP_WEC->PJM
CLTF
0.184
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.821
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.1
MECLTFEXP_MEC->PJM
CLTF
0.838
SIGELTFEXP_SIGE->PJM
CLTF
0.027

Details for 6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2199_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2199_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.18 %
Rating:909.92 MVA
Rating Type:B
MVA to Mitigate:1011.63
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
3151721LOISA A
50/50
41.884
3151911BEARGRDN G1
50/50
0.69
3132273ORANGE
Solar/Wind Harmer
-0.171
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.062
3146776BUCKING
Solar/Wind Harmer
-0.056
3146776BUCKING
Solar/Wind Harmer
-0.05
3151731LOISA B
50/50
41.884
3151751LOISA D
50/50
41.884
3151921BEARGRDN G2
50/50
0.724
3147666LOUISA
Solar/Wind Harmer
-4.404
3148013FISHERV
Solar/Wind Harmer
-0.189
3148013FISHERV
Solar/Wind Harmer
-0.108
3151771S ANNAG1
50/50
2.477
971447AH1-217 GEN
Solar/Wind Harmer
0.199
3147623JAMES R
Solar/Wind Harmer
0.009
972003AH1-546 GEN
Solar/Wind Harmer
0.272
3148133STUARTS
Solar/Wind Harmer
-0.113
3147346CASHSCORNER
Solar/Wind Harmer
0.056
3151801S ANNAS2
50/50
1.35
3147666LOUISA
Solar/Wind Harmer
-7.659
971377AH1-170 GEN
Solar/Wind Harmer
0.07
3151791S ANNAG2
50/50
2.477
3151931BEARGRDN S1
50/50
1.247
316164AC1-076 GEN
Solar/Wind Harmer
0
970285AG2-188 GEN
Solar/Wind Harmer
0.353
315651AD1-115 GEN
Solar/Wind Harmer
0
971489AH1-241 GEN
Solar/Wind Harmer
0.348
3151741LOISA C
50/50
41.884
3146776BUCKING
Solar/Wind Harmer
-0.617
970221AG2-151 GEN
Solar/Wind Harmer
0.348
3151761LOISA E
50/50
95.063
315821AE2-092 GEN
Solar/Wind Harmer
0
3151781S ANNAS1
50/50
1.35
972183AH1-676 GEN
50/50
596.542
3138266HYDRAULIC
Solar/Wind Harmer
-0.018
3138266HYDRAULIC
Solar/Wind Harmer
-0.011
315683AE1-153 C
Solar/Wind Harmer
3.433
970937AG2-583 GEN
Solar/Wind Harmer
0.311
971845AH1-439 GEN
Solar/Wind Harmer
0.224
CPLELTFEXP_CPLE->PJM
CLTF
0.314
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.877
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.162
LAGNLTFEXP_LAGN->PJM
CLTF
1.06
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.293
TVALTFEXP_TVA->PJM
CLTF
0.554
NYPJM->LTFIMP_NY
CLTF
0.379
LGEELTFEXP_LGEE->PJM
CLTF
0.355
WECLTFEXP_WEC->PJM
CLTF
0.18
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.652
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.056
MECLTFEXP_MEC->PJM
CLTF
0.819
SIGELTFEXP_SIGE->PJM
CLTF
0.027

Details for 6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2199_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2199_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.81 %
Rating:909.92 MVA
Rating Type:B
MVA to Mitigate:1008.31
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
3151721LOISA A
50/50
41.884
3151911BEARGRDN G1
50/50
0.69
3132273ORANGE
Solar/Wind Harmer
-0.171
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.062
3146776BUCKING
Solar/Wind Harmer
-0.056
3146776BUCKING
Solar/Wind Harmer
-0.05
3151731LOISA B
50/50
41.884
3151751LOISA D
50/50
41.884
3151921BEARGRDN G2
50/50
0.724
3147666LOUISA
Solar/Wind Harmer
-4.404
3148013FISHERV
Solar/Wind Harmer
-0.189
3148013FISHERV
Solar/Wind Harmer
-0.108
3151771S ANNAG1
50/50
2.477
971447AH1-217 GEN
Solar/Wind Harmer
0.199
3147623JAMES R
Solar/Wind Harmer
0.009
972003AH1-546 GEN
Solar/Wind Harmer
0.272
3148133STUARTS
Solar/Wind Harmer
-0.113
3147346CASHSCORNER
Solar/Wind Harmer
0.056
3151801S ANNAS2
50/50
1.35
3147666LOUISA
Solar/Wind Harmer
-7.659
971377AH1-170 GEN
Solar/Wind Harmer
0.07
3151791S ANNAG2
50/50
2.477
3151931BEARGRDN S1
50/50
1.247
316164AC1-076 GEN
Solar/Wind Harmer
0
970285AG2-188 GEN
Solar/Wind Harmer
0.353
315651AD1-115 GEN
Solar/Wind Harmer
0
971489AH1-241 GEN
Solar/Wind Harmer
0.348
3151741LOISA C
50/50
41.884
3146776BUCKING
Solar/Wind Harmer
-0.617
970221AG2-151 GEN
Solar/Wind Harmer
0.348
3151761LOISA E
50/50
95.063
315821AE2-092 GEN
Solar/Wind Harmer
0
3151781S ANNAS1
50/50
1.35
972183AH1-676 GEN
50/50
596.542
3138266HYDRAULIC
Solar/Wind Harmer
-0.018
3138266HYDRAULIC
Solar/Wind Harmer
-0.011
970937AG2-583 GEN
Solar/Wind Harmer
0.311
971845AH1-439 GEN
Solar/Wind Harmer
0.224
CPLELTFEXP_CPLE->PJM
CLTF
0.314
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.877
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.162
LAGNLTFEXP_LAGN->PJM
CLTF
1.06
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.293
TVALTFEXP_TVA->PJM
CLTF
0.554
NYPJM->LTFIMP_NY
CLTF
0.379
LGEELTFEXP_LGEE->PJM
CLTF
0.355
WECLTFEXP_WEC->PJM
CLTF
0.18
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.652
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.056
MECLTFEXP_MEC->PJM
CLTF
0.819
SIGELTFEXP_SIGE->PJM
CLTF
0.027

Details for 6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.1 %
Rating:1113.0 MVA
Rating Type:C
MVA to Mitigate:1203.18
MW Contribution:0.4
Bus #Bus NameTypeMW Contribution
3147346CASHSCORNER
Solar/Wind Harmer
0.064
3151801S ANNAS2
50/50
1.508
3147666LOUISA
Solar/Wind Harmer
-8.059
971377AH1-170 GEN
Solar/Wind Harmer
0.08
3151731LOISA B
50/50
47.124
3151751LOISA D
50/50
47.124
3147666LOUISA
Solar/Wind Harmer
-4.634
3148013FISHERV
Solar/Wind Harmer
-0.215
3151771S ANNAG1
50/50
2.767
971447AH1-217 GEN
Solar/Wind Harmer
0.229
3147623JAMES R
Solar/Wind Harmer
0.01
972003AH1-546 GEN
Solar/Wind Harmer
0.314
3148133STUARTS
Solar/Wind Harmer
-0.129
3151791S ANNAG2
50/50
2.767
970285AG2-188 GEN
Solar/Wind Harmer
0.411
971489AH1-241 GEN
Solar/Wind Harmer
0.401
3151741LOISA C
50/50
47.124
3146776BUCKING
Solar/Wind Harmer
-0.718
3151721LOISA A
50/50
47.124
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.072
3146776BUCKING
Solar/Wind Harmer
-0.065
3146776BUCKING
Solar/Wind Harmer
-0.058
970221AG2-151 GEN
Solar/Wind Harmer
0.401
3148013FISHERV
Solar/Wind Harmer
-0.124
3151761LOISA E
50/50
106.955
315821AE2-092 GEN
Solar/Wind Harmer
0
3151781S ANNAS1
50/50
1.508
972183AH1-676 GEN
50/50
674.292
3138266HYDRAULIC
Solar/Wind Harmer
-0.02
3138266HYDRAULIC
Solar/Wind Harmer
-0.012
315705AF1-075 GEN
Solar/Wind Harmer
0.185
315683AE1-153 C
Solar/Wind Harmer
3.88
970937AG2-583 GEN
Solar/Wind Harmer
0.362
971845AH1-439 GEN
Solar/Wind Harmer
0.261
CPLELTFEXP_CPLE->PJM
CLTF
0.507
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.343
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.246
LAGNLTFEXP_LAGN->PJM
CLTF
1.307
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.798
TVALTFEXP_TVA->PJM
CLTF
0.682
NYPJM->LTFIMP_NY
CLTF
0.464
LGEELTFEXP_LGEE->PJM
CLTF
0.419
WECLTFEXP_WEC->PJM
CLTF
0.213
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.859
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.512
MECLTFEXP_MEC->PJM
CLTF
0.977
SIGELTFEXP_SIGE->PJM
CLTF
0.032

Details for 6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:107.76 %
Rating:1113.0 MVA
Rating Type:C
MVA to Mitigate:1199.41
MW Contribution:0.4
Bus #Bus NameTypeMW Contribution
3147346CASHSCORNER
Solar/Wind Harmer
0.064
3151801S ANNAS2
50/50
1.508
3147666LOUISA
Solar/Wind Harmer
-8.059
971377AH1-170 GEN
Solar/Wind Harmer
0.08
3151771S ANNAG1
50/50
2.767
971447AH1-217 GEN
Solar/Wind Harmer
0.229
3147623JAMES R
Solar/Wind Harmer
0.01
972003AH1-546 GEN
Solar/Wind Harmer
0.314
3148133STUARTS
Solar/Wind Harmer
-0.129
3151791S ANNAG2
50/50
2.767
970285AG2-188 GEN
Solar/Wind Harmer
0.411
971489AH1-241 GEN
Solar/Wind Harmer
0.401
3151741LOISA C
50/50
47.124
3146776BUCKING
Solar/Wind Harmer
-0.718
3151721LOISA A
50/50
47.124
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.072
3146776BUCKING
Solar/Wind Harmer
-0.065
3146776BUCKING
Solar/Wind Harmer
-0.058
970221AG2-151 GEN
Solar/Wind Harmer
0.401
3151731LOISA B
50/50
47.124
3151751LOISA D
50/50
47.124
3147666LOUISA
Solar/Wind Harmer
-4.634
3148013FISHERV
Solar/Wind Harmer
-0.215
3148013FISHERV
Solar/Wind Harmer
-0.124
3151761LOISA E
50/50
106.955
315821AE2-092 GEN
Solar/Wind Harmer
0
3151781S ANNAS1
50/50
1.508
972183AH1-676 GEN
50/50
674.292
3138266HYDRAULIC
Solar/Wind Harmer
-0.02
3138266HYDRAULIC
Solar/Wind Harmer
-0.012
315705AF1-075 GEN
Solar/Wind Harmer
0.185
970937AG2-583 GEN
Solar/Wind Harmer
0.362
971845AH1-439 GEN
Solar/Wind Harmer
0.261
CPLELTFEXP_CPLE->PJM
CLTF
0.507
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.343
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.246
LAGNLTFEXP_LAGN->PJM
CLTF
1.307
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.798
TVALTFEXP_TVA->PJM
CLTF
0.682
NYPJM->LTFIMP_NY
CLTF
0.464
LGEELTFEXP_LGEE->PJM
CLTF
0.419
WECLTFEXP_WEC->PJM
CLTF
0.213
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.859
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.512
MECLTFEXP_MEC->PJM
CLTF
0.977
SIGELTFEXP_SIGE->PJM
CLTF
0.032

Details for 6S ANNA-6DESPER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2199_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
6S ANNA-6DESPER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2199_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:134.81 %
Rating:909.92 MVA
Rating Type:B
MVA to Mitigate:1226.66
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
3151721LOISA A
50/50
41.899
3151911BEARGRDN G1
50/50
0.692
3132273ORANGE
Solar/Wind Harmer
-0.171
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.062
3146776BUCKING
Solar/Wind Harmer
-0.056
3146776BUCKING
Solar/Wind Harmer
-0.05
3151731LOISA B
50/50
41.899
3151751LOISA D
50/50
41.899
3151921BEARGRDN G2
50/50
0.726
3148013FISHERV
Solar/Wind Harmer
-0.189
3148013FISHERV
Solar/Wind Harmer
-0.109
3147666LOUISA
Solar/Wind Helper
2.368
3151771S ANNAG1
50/50
2.477
971447AH1-217 GEN
Solar/Wind Harmer
0.199
3147623JAMES R
Solar/Wind Harmer
0.009
972003AH1-546 GEN
Solar/Wind Harmer
0.273
3148133STUARTS
Solar/Wind Harmer
-0.113
3147346CASHSCORNER
Solar/Wind Harmer
0.056
3151801S ANNAS2
50/50
1.35
971377AH1-170 GEN
Solar/Wind Harmer
0.07
3147666LOUISA
Solar/Wind Helper
4.119
3151791S ANNAG2
50/50
2.477
3151931BEARGRDN S1
50/50
1.25
316164AC1-076 GEN
Solar/Wind Harmer
0
970285AG2-188 GEN
Solar/Wind Harmer
0.354
315651AD1-115 GEN
Solar/Wind Harmer
0
971489AH1-241 GEN
Solar/Wind Harmer
0.349
3151741LOISA C
50/50
41.899
3146776BUCKING
Solar/Wind Harmer
-0.619
970221AG2-151 GEN
Solar/Wind Harmer
0.349
3151761LOISA E
50/50
95.097
315821AE2-092 GEN
Solar/Wind Harmer
0
3151781S ANNAS1
50/50
1.35
972183AH1-676 GEN
50/50
596.754
3138266HYDRAULIC
Solar/Wind Harmer
-0.018
3138266HYDRAULIC
Solar/Wind Harmer
-0.011
316192AB2-158 GEN
Solar/Wind Helper
1.508
315683AE1-153 C
Solar/Wind Harmer
3.434
970937AG2-583 GEN
Solar/Wind Harmer
0.312
971845AH1-439 GEN
Solar/Wind Harmer
0.225
CPLELTFEXP_CPLE->PJM
CLTF
0.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.068
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.162
LAGNLTFEXP_LAGN->PJM
CLTF
1.088
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.336
TVALTFEXP_TVA->PJM
CLTF
0.569
NYPJM->LTFIMP_NY
CLTF
0.37
LGEELTFEXP_LGEE->PJM
CLTF
0.364
WECLTFEXP_WEC->PJM
CLTF
0.185
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.859
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.11
MECLTFEXP_MEC->PJM
CLTF
0.843
SIGELTFEXP_SIGE->PJM
CLTF
0.027

Details for 6S ANNA-6DESPER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2199_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6S ANNA-6DESPER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2199_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:134.44 %
Rating:909.92 MVA
Rating Type:B
MVA to Mitigate:1223.33
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
3151721LOISA A
50/50
41.899
3151911BEARGRDN G1
50/50
0.692
3132273ORANGE
Solar/Wind Harmer
-0.171
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.062
3146776BUCKING
Solar/Wind Harmer
-0.056
3146776BUCKING
Solar/Wind Harmer
-0.05
3151731LOISA B
50/50
41.899
3151751LOISA D
50/50
41.899
3151921BEARGRDN G2
50/50
0.726
3148013FISHERV
Solar/Wind Harmer
-0.189
3148013FISHERV
Solar/Wind Harmer
-0.109
3147666LOUISA
Solar/Wind Helper
2.368
3151771S ANNAG1
50/50
2.477
971447AH1-217 GEN
Solar/Wind Harmer
0.199
3147623JAMES R
Solar/Wind Harmer
0.009
972003AH1-546 GEN
Solar/Wind Harmer
0.273
3148133STUARTS
Solar/Wind Harmer
-0.113
3147346CASHSCORNER
Solar/Wind Harmer
0.056
3151801S ANNAS2
50/50
1.35
971377AH1-170 GEN
Solar/Wind Harmer
0.07
3147666LOUISA
Solar/Wind Helper
4.119
3151791S ANNAG2
50/50
2.477
3151931BEARGRDN S1
50/50
1.25
316164AC1-076 GEN
Solar/Wind Harmer
0
970285AG2-188 GEN
Solar/Wind Harmer
0.354
315651AD1-115 GEN
Solar/Wind Harmer
0
971489AH1-241 GEN
Solar/Wind Harmer
0.349
3151741LOISA C
50/50
41.899
3146776BUCKING
Solar/Wind Harmer
-0.619
970221AG2-151 GEN
Solar/Wind Harmer
0.349
3151761LOISA E
50/50
95.097
315821AE2-092 GEN
Solar/Wind Harmer
0
3151781S ANNAS1
50/50
1.35
972183AH1-676 GEN
50/50
596.754
3138266HYDRAULIC
Solar/Wind Harmer
-0.018
3138266HYDRAULIC
Solar/Wind Harmer
-0.011
316192AB2-158 GEN
Solar/Wind Helper
1.508
970937AG2-583 GEN
Solar/Wind Harmer
0.312
971845AH1-439 GEN
Solar/Wind Harmer
0.225
CPLELTFEXP_CPLE->PJM
CLTF
0.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.068
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.162
LAGNLTFEXP_LAGN->PJM
CLTF
1.088
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.336
TVALTFEXP_TVA->PJM
CLTF
0.569
NYPJM->LTFIMP_NY
CLTF
0.37
LGEELTFEXP_LGEE->PJM
CLTF
0.364
WECLTFEXP_WEC->PJM
CLTF
0.185
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.859
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.11
MECLTFEXP_MEC->PJM
CLTF
0.843
SIGELTFEXP_SIGE->PJM
CLTF
0.027

Details for 6S ANNA-6DESPER 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
6S ANNA-6DESPER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:127.77 %
Rating:1113.0 MVA
Rating Type:C
MVA to Mitigate:1422.07
MW Contribution:0.4
Bus #Bus NameTypeMW Contribution
3147346CASHSCORNER
Solar/Wind Harmer
0.064
3151801S ANNAS2
50/50
1.509
971377AH1-170 GEN
Solar/Wind Harmer
0.08
3147666LOUISA
Solar/Wind Helper
3.684
3151731LOISA B
50/50
47.138
3151751LOISA D
50/50
47.138
3148013FISHERV
Solar/Wind Harmer
-0.216
3148013FISHERV
Solar/Wind Harmer
-0.124
3147666LOUISA
Solar/Wind Helper
2.118
3151771S ANNAG1
50/50
2.768
971447AH1-217 GEN
Solar/Wind Harmer
0.23
3147623JAMES R
Solar/Wind Harmer
0.01
972003AH1-546 GEN
Solar/Wind Harmer
0.315
3148133STUARTS
Solar/Wind Harmer
-0.13
3151791S ANNAG2
50/50
2.768
970285AG2-188 GEN
Solar/Wind Harmer
0.413
971489AH1-241 GEN
Solar/Wind Harmer
0.402
3151741LOISA C
50/50
47.138
3146776BUCKING
Solar/Wind Harmer
-0.72
3151721LOISA A
50/50
47.138
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.072
3146776BUCKING
Solar/Wind Harmer
-0.065
3146776BUCKING
Solar/Wind Harmer
-0.058
970221AG2-151 GEN
Solar/Wind Harmer
0.402
3151761LOISA E
50/50
106.988
315821AE2-092 GEN
Solar/Wind Harmer
0
3151781S ANNAS1
50/50
1.509
972183AH1-676 GEN
50/50
674.504
3138266HYDRAULIC
Solar/Wind Harmer
-0.02
3138266HYDRAULIC
Solar/Wind Harmer
-0.012
315705AF1-075 GEN
Solar/Wind Harmer
0.185
316192AB2-158 GEN
Solar/Wind Helper
1.348
315683AE1-153 C
Solar/Wind Harmer
3.881
970937AG2-583 GEN
Solar/Wind Harmer
0.363
971845AH1-439 GEN
Solar/Wind Harmer
0.262
CPLELTFEXP_CPLE->PJM
CLTF
0.523
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.534
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.246
LAGNLTFEXP_LAGN->PJM
CLTF
1.336
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.84
TVALTFEXP_TVA->PJM
CLTF
0.696
NYPJM->LTFIMP_NY
CLTF
0.455
LGEELTFEXP_LGEE->PJM
CLTF
0.429
WECLTFEXP_WEC->PJM
CLTF
0.218
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.066
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.566
MECLTFEXP_MEC->PJM
CLTF
1.001
SIGELTFEXP_SIGE->PJM
CLTF
0.033

Details for 6S ANNA-6DESPER 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6S ANNA-6DESPER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:127.43 %
Rating:1113.0 MVA
Rating Type:C
MVA to Mitigate:1418.31
MW Contribution:0.4
Bus #Bus NameTypeMW Contribution
3147346CASHSCORNER
Solar/Wind Harmer
0.064
3151801S ANNAS2
50/50
1.509
971377AH1-170 GEN
Solar/Wind Harmer
0.08
3147666LOUISA
Solar/Wind Helper
3.684
3151731LOISA B
50/50
47.138
3151751LOISA D
50/50
47.138
3148013FISHERV
Solar/Wind Harmer
-0.216
3148013FISHERV
Solar/Wind Harmer
-0.124
3147666LOUISA
Solar/Wind Helper
2.118
3151771S ANNAG1
50/50
2.768
971447AH1-217 GEN
Solar/Wind Harmer
0.23
3147623JAMES R
Solar/Wind Harmer
0.01
972003AH1-546 GEN
Solar/Wind Harmer
0.315
3148133STUARTS
Solar/Wind Harmer
-0.13
3151791S ANNAG2
50/50
2.768
970285AG2-188 GEN
Solar/Wind Harmer
0.413
971489AH1-241 GEN
Solar/Wind Harmer
0.402
3151741LOISA C
50/50
47.138
3146776BUCKING
Solar/Wind Harmer
-0.72
3151721LOISA A
50/50
47.138
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.072
3146776BUCKING
Solar/Wind Harmer
-0.065
3146776BUCKING
Solar/Wind Harmer
-0.058
970221AG2-151 GEN
Solar/Wind Harmer
0.402
3151761LOISA E
50/50
106.988
315821AE2-092 GEN
Solar/Wind Harmer
0
3151781S ANNAS1
50/50
1.509
972183AH1-676 GEN
50/50
674.504
3138266HYDRAULIC
Solar/Wind Harmer
-0.02
3138266HYDRAULIC
Solar/Wind Harmer
-0.012
315705AF1-075 GEN
Solar/Wind Harmer
0.185
316192AB2-158 GEN
Solar/Wind Helper
1.348
970937AG2-583 GEN
Solar/Wind Harmer
0.363
971845AH1-439 GEN
Solar/Wind Harmer
0.262
CPLELTFEXP_CPLE->PJM
CLTF
0.523
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.534
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.246
LAGNLTFEXP_LAGN->PJM
CLTF
1.336
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.84
TVALTFEXP_TVA->PJM
CLTF
0.696
NYPJM->LTFIMP_NY
CLTF
0.455
LGEELTFEXP_LGEE->PJM
CLTF
0.429
WECLTFEXP_WEC->PJM
CLTF
0.218
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.066
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.566
MECLTFEXP_MEC->PJM
CLTF
1.001
SIGELTFEXP_SIGE->PJM
CLTF
0.033

Details for 6S ANNA-6DESPER 230.0 kV Ckt 1 line l/o DVP_P4-2: H3T2199_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6S ANNA-6DESPER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H3T2199_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.24 %
Rating:1113.0 MVA
Rating Type:C
MVA to Mitigate:1227.0
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
3151731LOISA B
50/50
42.071
3151751LOISA D
50/50
42.071
3148013FISHERV
Solar/Wind Harmer
-0.19
3148013FISHERV
Solar/Wind Harmer
-0.109
3147666LOUISA
Solar/Wind Helper
2.36
3151771S ANNAG1
50/50
2.487
971447AH1-217 GEN
Solar/Wind Harmer
0.2
3147623JAMES R
Solar/Wind Harmer
0.009
972003AH1-546 GEN
Solar/Wind Harmer
0.274
3148133STUARTS
Solar/Wind Harmer
-0.114
3147346CASHSCORNER
Solar/Wind Harmer
0.057
3151801S ANNAS2
50/50
1.356
971377AH1-170 GEN
Solar/Wind Harmer
0.07
3147666LOUISA
Solar/Wind Helper
4.104
3151791S ANNAG2
50/50
2.487
316164AC1-076 GEN
Solar/Wind Harmer
0
970285AG2-188 GEN
Solar/Wind Harmer
0.356
315651AD1-115 GEN
Solar/Wind Harmer
0
3151721LOISA A
50/50
42.071
3132273ORANGE
Solar/Wind Harmer
-0.165
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.062
3146776BUCKING
Solar/Wind Harmer
-0.056
3146776BUCKING
Solar/Wind Harmer
-0.05
971489AH1-241 GEN
Solar/Wind Harmer
0.351
3151741LOISA C
50/50
42.071
3146776BUCKING
Solar/Wind Harmer
-0.622
970221AG2-151 GEN
Solar/Wind Harmer
0.351
3151761LOISA E
50/50
95.487
315821AE2-092 GEN
Solar/Wind Harmer
0
3151781S ANNAS1
50/50
1.356
972183AH1-676 GEN
50/50
599.31
3138266HYDRAULIC
Solar/Wind Harmer
-0.018
3138266HYDRAULIC
Solar/Wind Harmer
-0.011
316192AB2-158 GEN
Solar/Wind Helper
1.503
970937AG2-583 GEN
Solar/Wind Harmer
0.313
971845AH1-439 GEN
Solar/Wind Harmer
0.226
CPLELTFEXP_CPLE->PJM
CLTF
0.336
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.116
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.165
LAGNLTFEXP_LAGN->PJM
CLTF
1.097
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.353
TVALTFEXP_TVA->PJM
CLTF
0.573
NYPJM->LTFIMP_NY
CLTF
0.373
LGEELTFEXP_LGEE->PJM
CLTF
0.366
WECLTFEXP_WEC->PJM
CLTF
0.187
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.899
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.125
MECLTFEXP_MEC->PJM
CLTF
0.848
SIGELTFEXP_SIGE->PJM
CLTF
0.028

Details for 6S ANNA-6DESPER 230.0 kV Ckt 1 line l/o DVP_P4-2: 2199T2331_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6S ANNA-6DESPER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2199T2331_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.81 %
Rating:1113.0 MVA
Rating Type:C
MVA to Mitigate:1222.17
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
3151731LOISA B
50/50
41.899
3151751LOISA D
50/50
41.899
3148013FISHERV
Solar/Wind Harmer
-0.189
3148013FISHERV
Solar/Wind Harmer
-0.109
3147666LOUISA
Solar/Wind Helper
2.368
3151771S ANNAG1
50/50
2.477
971447AH1-217 GEN
Solar/Wind Harmer
0.199
3147623JAMES R
Solar/Wind Harmer
0.009
972003AH1-546 GEN
Solar/Wind Harmer
0.273
3148133STUARTS
Solar/Wind Harmer
-0.113
3147346CASHSCORNER
Solar/Wind Harmer
0.056
3151801S ANNAS2
50/50
1.35
971377AH1-170 GEN
Solar/Wind Harmer
0.07
3147666LOUISA
Solar/Wind Helper
4.119
3151791S ANNAG2
50/50
2.477
316164AC1-076 GEN
Solar/Wind Harmer
0
970285AG2-188 GEN
Solar/Wind Harmer
0.354
315651AD1-115 GEN
Solar/Wind Harmer
0
3151721LOISA A
50/50
41.899
3132273ORANGE
Solar/Wind Harmer
-0.171
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.062
3146776BUCKING
Solar/Wind Harmer
-0.056
971489AH1-241 GEN
Solar/Wind Harmer
0.349
3151741LOISA C
50/50
41.899
3146776BUCKING
Solar/Wind Harmer
-0.619
3146776BUCKING
Solar/Wind Harmer
-0.05
970221AG2-151 GEN
Solar/Wind Harmer
0.349
3151761LOISA E
50/50
95.097
315821AE2-092 GEN
Solar/Wind Harmer
0
3151781S ANNAS1
50/50
1.35
972183AH1-676 GEN
50/50
596.754
3138266HYDRAULIC
Solar/Wind Harmer
-0.018
3138266HYDRAULIC
Solar/Wind Harmer
-0.011
316192AB2-158 GEN
Solar/Wind Helper
1.508
315683AE1-153 C
Solar/Wind Harmer
3.434
970937AG2-583 GEN
Solar/Wind Harmer
0.312
971845AH1-439 GEN
Solar/Wind Harmer
0.225
CPLELTFEXP_CPLE->PJM
CLTF
0.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.068
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.162
LAGNLTFEXP_LAGN->PJM
CLTF
1.088
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.336
TVALTFEXP_TVA->PJM
CLTF
0.569
NYPJM->LTFIMP_NY
CLTF
0.37
LGEELTFEXP_LGEE->PJM
CLTF
0.364
WECLTFEXP_WEC->PJM
CLTF
0.185
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.859
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.11
MECLTFEXP_MEC->PJM
CLTF
0.843
SIGELTFEXP_SIGE->PJM
CLTF
0.027

Details for 6S ANNA-6DESPER 230.0 kV Ckt 1 line l/o DVP_P2-2: GERMANNA_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6S ANNA-6DESPER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: GERMANNA_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:109.51 %
Rating:1113.0 MVA
Rating Type:C
MVA to Mitigate:1218.83
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
3151731LOISA B
50/50
41.899
3151751LOISA D
50/50
41.899
3148013FISHERV
Solar/Wind Harmer
-0.189
3148013FISHERV
Solar/Wind Harmer
-0.109
3147666LOUISA
Solar/Wind Helper
2.368
3147346CASHSCORNER
Solar/Wind Harmer
0.056
3151801S ANNAS2
50/50
1.35
971377AH1-170 GEN
Solar/Wind Harmer
0.07
3147666LOUISA
Solar/Wind Helper
4.119
3151771S ANNAG1
50/50
2.477
971447AH1-217 GEN
Solar/Wind Harmer
0.199
3147623JAMES R
Solar/Wind Harmer
0.009
972003AH1-546 GEN
Solar/Wind Harmer
0.273
3148133STUARTS
Solar/Wind Harmer
-0.113
3151791S ANNAG2
50/50
2.477
316164AC1-076 GEN
Solar/Wind Harmer
0
970285AG2-188 GEN
Solar/Wind Harmer
0.354
315651AD1-115 GEN
Solar/Wind Harmer
0
971489AH1-241 GEN
Solar/Wind Harmer
0.349
3151741LOISA C
50/50
41.899
3146776BUCKING
Solar/Wind Harmer
-0.619
3151721LOISA A
50/50
41.899
3132273ORANGE
Solar/Wind Harmer
-0.171
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.062
3146776BUCKING
Solar/Wind Harmer
-0.056
3146776BUCKING
Solar/Wind Harmer
-0.05
970221AG2-151 GEN
Solar/Wind Harmer
0.349
3151761LOISA E
50/50
95.097
315821AE2-092 GEN
Solar/Wind Harmer
0
3151781S ANNAS1
50/50
1.35
972183AH1-676 GEN
50/50
596.754
3138266HYDRAULIC
Solar/Wind Harmer
-0.018
3138266HYDRAULIC
Solar/Wind Harmer
-0.011
316192AB2-158 GEN
Solar/Wind Helper
1.508
970937AG2-583 GEN
Solar/Wind Harmer
0.312
971845AH1-439 GEN
Solar/Wind Harmer
0.225
CPLELTFEXP_CPLE->PJM
CLTF
0.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.068
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.162
LAGNLTFEXP_LAGN->PJM
CLTF
1.088
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.336
TVALTFEXP_TVA->PJM
CLTF
0.569
NYPJM->LTFIMP_NY
CLTF
0.37
LGEELTFEXP_LGEE->PJM
CLTF
0.364
WECLTFEXP_WEC->PJM
CLTF
0.185
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.859
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.11
MECLTFEXP_MEC->PJM
CLTF
0.843
SIGELTFEXP_SIGE->PJM
CLTF
0.027

Details for 6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2199_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2199_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.28 %
Rating:909.92 MVA
Rating Type:B
MVA to Mitigate:1021.64
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
3151721LOISA A
50/50
41.884
3151911BEARGRDN G1
50/50
0.69
3132273ORANGE
Solar/Wind Harmer
-0.171
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.062
3146776BUCKING
Solar/Wind Harmer
-0.056
3146776BUCKING
Solar/Wind Harmer
-0.05
3151731LOISA B
50/50
41.884
3151751LOISA D
50/50
41.884
3151921BEARGRDN G2
50/50
0.724
3147666LOUISA
Solar/Wind Harmer
-4.404
3148013FISHERV
Solar/Wind Harmer
-0.189
3148013FISHERV
Solar/Wind Harmer
-0.108
3151771S ANNAG1
50/50
2.477
971447AH1-217 GEN
Solar/Wind Harmer
0.199
3147623JAMES R
Solar/Wind Harmer
0.009
972003AH1-546 GEN
Solar/Wind Harmer
0.272
3148133STUARTS
Solar/Wind Harmer
-0.113
3147346CASHSCORNER
Solar/Wind Harmer
0.056
3151801S ANNAS2
50/50
1.35
3147666LOUISA
Solar/Wind Harmer
-7.659
971377AH1-170 GEN
Solar/Wind Harmer
0.07
3151791S ANNAG2
50/50
2.477
3151931BEARGRDN S1
50/50
1.247
316164AC1-076 GEN
Solar/Wind Harmer
0
970285AG2-188 GEN
Solar/Wind Harmer
0.353
971133AH1-012 GEN
50/50
15.037
315651AD1-115 GEN
Solar/Wind Harmer
0
971489AH1-241 GEN
Solar/Wind Harmer
0.348
3151741LOISA C
50/50
41.884
3146776BUCKING
Solar/Wind Harmer
-0.617
970221AG2-151 GEN
Solar/Wind Harmer
0.348
3151761LOISA E
50/50
95.063
315821AE2-092 GEN
Solar/Wind Harmer
0
3151781S ANNAS1
50/50
1.35
972183AH1-676 GEN
50/50
596.542
3138266HYDRAULIC
Solar/Wind Harmer
-0.018
3138266HYDRAULIC
Solar/Wind Harmer
-0.011
315683AE1-153 C
Solar/Wind Harmer
3.433
970937AG2-583 GEN
Solar/Wind Harmer
0.311
971845AH1-439 GEN
Solar/Wind Harmer
0.224
CPLELTFEXP_CPLE->PJM
CLTF
0.314
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.877
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.162
LAGNLTFEXP_LAGN->PJM
CLTF
1.06
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.293
TVALTFEXP_TVA->PJM
CLTF
0.554
NYPJM->LTFIMP_NY
CLTF
0.379
LGEELTFEXP_LGEE->PJM
CLTF
0.355
WECLTFEXP_WEC->PJM
CLTF
0.18
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.652
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.056
MECLTFEXP_MEC->PJM
CLTF
0.819
SIGELTFEXP_SIGE->PJM
CLTF
0.027

Details for 6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2199_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2199_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.91 %
Rating:909.92 MVA
Rating Type:B
MVA to Mitigate:1018.31
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
3151721LOISA A
50/50
41.884
3151911BEARGRDN G1
50/50
0.69
3132273ORANGE
Solar/Wind Harmer
-0.171
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.062
3146776BUCKING
Solar/Wind Harmer
-0.056
3146776BUCKING
Solar/Wind Harmer
-0.05
3151731LOISA B
50/50
41.884
3151751LOISA D
50/50
41.884
3151921BEARGRDN G2
50/50
0.724
3147666LOUISA
Solar/Wind Harmer
-4.404
3148013FISHERV
Solar/Wind Harmer
-0.189
3148013FISHERV
Solar/Wind Harmer
-0.108
3151771S ANNAG1
50/50
2.477
971447AH1-217 GEN
Solar/Wind Harmer
0.199
3147623JAMES R
Solar/Wind Harmer
0.009
972003AH1-546 GEN
Solar/Wind Harmer
0.272
3148133STUARTS
Solar/Wind Harmer
-0.113
3147346CASHSCORNER
Solar/Wind Harmer
0.056
3151801S ANNAS2
50/50
1.35
3147666LOUISA
Solar/Wind Harmer
-7.659
971377AH1-170 GEN
Solar/Wind Harmer
0.07
3151791S ANNAG2
50/50
2.477
3151931BEARGRDN S1
50/50
1.247
316164AC1-076 GEN
Solar/Wind Harmer
0
970285AG2-188 GEN
Solar/Wind Harmer
0.353
971133AH1-012 GEN
50/50
15.037
315651AD1-115 GEN
Solar/Wind Harmer
0
971489AH1-241 GEN
Solar/Wind Harmer
0.348
3151741LOISA C
50/50
41.884
3146776BUCKING
Solar/Wind Harmer
-0.617
970221AG2-151 GEN
Solar/Wind Harmer
0.348
3151761LOISA E
50/50
95.063
315821AE2-092 GEN
Solar/Wind Harmer
0
3151781S ANNAS1
50/50
1.35
972183AH1-676 GEN
50/50
596.542
3138266HYDRAULIC
Solar/Wind Harmer
-0.018
3138266HYDRAULIC
Solar/Wind Harmer
-0.011
970937AG2-583 GEN
Solar/Wind Harmer
0.311
971845AH1-439 GEN
Solar/Wind Harmer
0.224
CPLELTFEXP_CPLE->PJM
CLTF
0.314
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.877
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.162
LAGNLTFEXP_LAGN->PJM
CLTF
1.06
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.293
TVALTFEXP_TVA->PJM
CLTF
0.554
NYPJM->LTFIMP_NY
CLTF
0.379
LGEELTFEXP_LGEE->PJM
CLTF
0.355
WECLTFEXP_WEC->PJM
CLTF
0.18
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.652
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.056
MECLTFEXP_MEC->PJM
CLTF
0.819
SIGELTFEXP_SIGE->PJM
CLTF
0.027

Details for 6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:109.04 %
Rating:1113.0 MVA
Rating Type:C
MVA to Mitigate:1213.62
MW Contribution:0.4
Bus #Bus NameTypeMW Contribution
3147346CASHSCORNER
Solar/Wind Harmer
0.064
3151801S ANNAS2
50/50
1.508
3147666LOUISA
Solar/Wind Harmer
-8.059
971377AH1-170 GEN
Solar/Wind Harmer
0.08
3151731LOISA B
50/50
47.124
3151751LOISA D
50/50
47.124
3147666LOUISA
Solar/Wind Harmer
-4.634
3148013FISHERV
Solar/Wind Harmer
-0.215
3148013FISHERV
Solar/Wind Harmer
-0.124
3151771S ANNAG1
50/50
2.767
971447AH1-217 GEN
Solar/Wind Harmer
0.229
3147623JAMES R
Solar/Wind Harmer
0.01
972003AH1-546 GEN
Solar/Wind Harmer
0.314
3148133STUARTS
Solar/Wind Harmer
-0.129
3151791S ANNAG2
50/50
2.767
970285AG2-188 GEN
Solar/Wind Harmer
0.411
971133AH1-012 GEN
50/50
15.534
971489AH1-241 GEN
Solar/Wind Harmer
0.401
3151741LOISA C
50/50
47.124
3146776BUCKING
Solar/Wind Harmer
-0.718
3151721LOISA A
50/50
47.124
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.072
3146776BUCKING
Solar/Wind Harmer
-0.065
3146776BUCKING
Solar/Wind Harmer
-0.058
970221AG2-151 GEN
Solar/Wind Harmer
0.401
3151761LOISA E
50/50
106.955
315821AE2-092 GEN
Solar/Wind Harmer
0
3151781S ANNAS1
50/50
1.508
972183AH1-676 GEN
50/50
674.292
3138266HYDRAULIC
Solar/Wind Harmer
-0.02
3138266HYDRAULIC
Solar/Wind Harmer
-0.012
315705AF1-075 GEN
Solar/Wind Harmer
0.185
315683AE1-153 C
Solar/Wind Harmer
3.88
970937AG2-583 GEN
Solar/Wind Harmer
0.362
971845AH1-439 GEN
Solar/Wind Harmer
0.261
CPLELTFEXP_CPLE->PJM
CLTF
0.507
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.343
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.246
LAGNLTFEXP_LAGN->PJM
CLTF
1.307
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.798
TVALTFEXP_TVA->PJM
CLTF
0.682
NYPJM->LTFIMP_NY
CLTF
0.464
LGEELTFEXP_LGEE->PJM
CLTF
0.419
WECLTFEXP_WEC->PJM
CLTF
0.213
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.859
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.512
MECLTFEXP_MEC->PJM
CLTF
0.977
SIGELTFEXP_SIGE->PJM
CLTF
0.032

Details for 6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.7 %
Rating:1113.0 MVA
Rating Type:C
MVA to Mitigate:1209.84
MW Contribution:0.4
Bus #Bus NameTypeMW Contribution
3147346CASHSCORNER
Solar/Wind Harmer
0.064
3151801S ANNAS2
50/50
1.508
3147666LOUISA
Solar/Wind Harmer
-8.059
971377AH1-170 GEN
Solar/Wind Harmer
0.08
3151731LOISA B
50/50
47.124
3151751LOISA D
50/50
47.124
3147666LOUISA
Solar/Wind Harmer
-4.634
3148013FISHERV
Solar/Wind Harmer
-0.215
3148013FISHERV
Solar/Wind Harmer
-0.124
3151771S ANNAG1
50/50
2.767
971447AH1-217 GEN
Solar/Wind Harmer
0.229
3147623JAMES R
Solar/Wind Harmer
0.01
972003AH1-546 GEN
Solar/Wind Harmer
0.314
3148133STUARTS
Solar/Wind Harmer
-0.129
3151791S ANNAG2
50/50
2.767
970285AG2-188 GEN
Solar/Wind Harmer
0.411
971489AH1-241 GEN
Solar/Wind Harmer
0.401
3151741LOISA C
50/50
47.124
3146776BUCKING
Solar/Wind Harmer
-0.718
3151721LOISA A
50/50
47.124
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.072
3146776BUCKING
Solar/Wind Harmer
-0.065
3146776BUCKING
Solar/Wind Harmer
-0.058
970221AG2-151 GEN
Solar/Wind Harmer
0.401
3151761LOISA E
50/50
106.955
315821AE2-092 GEN
Solar/Wind Harmer
0
3151781S ANNAS1
50/50
1.508
972183AH1-676 GEN
50/50
674.292
971133AH1-012 GEN
50/50
15.534
3138266HYDRAULIC
Solar/Wind Harmer
-0.02
3138266HYDRAULIC
Solar/Wind Harmer
-0.012
315705AF1-075 GEN
Solar/Wind Harmer
0.185
970937AG2-583 GEN
Solar/Wind Harmer
0.362
971845AH1-439 GEN
Solar/Wind Harmer
0.261
CPLELTFEXP_CPLE->PJM
CLTF
0.507
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.343
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.246
LAGNLTFEXP_LAGN->PJM
CLTF
1.307
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.798
TVALTFEXP_TVA->PJM
CLTF
0.682
NYPJM->LTFIMP_NY
CLTF
0.464
LGEELTFEXP_LGEE->PJM
CLTF
0.419
WECLTFEXP_WEC->PJM
CLTF
0.213
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.859
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.512
MECLTFEXP_MEC->PJM
CLTF
0.977
SIGELTFEXP_SIGE->PJM
CLTF
0.032

Details for AH1-012 TP-6SOUTH HALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2199_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
AH1-012 TP-6SOUTH HALL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2199_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.38 %
Rating:909.92 MVA
Rating Type:B
MVA to Mitigate:1022.6
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
3151721LOISA A
50/50
41.884
3151911BEARGRDN G1
50/50
0.69
3132273ORANGE
Solar/Wind Harmer
-0.171
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.062
3146776BUCKING
Solar/Wind Harmer
-0.056
3146776BUCKING
Solar/Wind Harmer
-0.05
3151731LOISA B
50/50
41.884
3151751LOISA D
50/50
41.884
3151921BEARGRDN G2
50/50
0.724
3147666LOUISA
Solar/Wind Harmer
-4.404
3148013FISHERV
Solar/Wind Harmer
-0.189
3148013FISHERV
Solar/Wind Harmer
-0.108
3151771S ANNAG1
50/50
2.477
971447AH1-217 GEN
Solar/Wind Harmer
0.199
3147623JAMES R
Solar/Wind Harmer
0.009
972003AH1-546 GEN
Solar/Wind Harmer
0.272
3148133STUARTS
Solar/Wind Harmer
-0.113
3147346CASHSCORNER
Solar/Wind Harmer
0.056
3151801S ANNAS2
50/50
1.35
3147666LOUISA
Solar/Wind Harmer
-7.659
971377AH1-170 GEN
Solar/Wind Harmer
0.07
3151791S ANNAG2
50/50
2.477
3151931BEARGRDN S1
50/50
1.247
316164AC1-076 GEN
Solar/Wind Harmer
0
970285AG2-188 GEN
Solar/Wind Harmer
0.353
971133AH1-012 GEN
50/50
15.037
315651AD1-115 GEN
Solar/Wind Harmer
0
971489AH1-241 GEN
Solar/Wind Harmer
0.348
3151741LOISA C
50/50
41.884
3146776BUCKING
Solar/Wind Harmer
-0.617
970221AG2-151 GEN
Solar/Wind Harmer
0.348
3151761LOISA E
50/50
95.063
315821AE2-092 GEN
Solar/Wind Harmer
0
3151781S ANNAS1
50/50
1.35
972183AH1-676 GEN
50/50
596.542
3138266HYDRAULIC
Solar/Wind Harmer
-0.018
3138266HYDRAULIC
Solar/Wind Harmer
-0.011
315683AE1-153 C
Solar/Wind Harmer
3.433
970937AG2-583 GEN
Solar/Wind Harmer
0.311
971845AH1-439 GEN
Solar/Wind Harmer
0.224
CPLELTFEXP_CPLE->PJM
CLTF
0.314
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.877
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.162
LAGNLTFEXP_LAGN->PJM
CLTF
1.06
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.293
TVALTFEXP_TVA->PJM
CLTF
0.554
NYPJM->LTFIMP_NY
CLTF
0.379
LGEELTFEXP_LGEE->PJM
CLTF
0.355
WECLTFEXP_WEC->PJM
CLTF
0.18
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.652
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.056
MECLTFEXP_MEC->PJM
CLTF
0.819
SIGELTFEXP_SIGE->PJM
CLTF
0.027

Details for AH1-012 TP-6SOUTH HALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2199_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
AH1-012 TP-6SOUTH HALL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2199_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.02 %
Rating:909.92 MVA
Rating Type:B
MVA to Mitigate:1019.27
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
3151721LOISA A
50/50
41.884
3151911BEARGRDN G1
50/50
0.69
3132273ORANGE
Solar/Wind Harmer
-0.171
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.062
3146776BUCKING
Solar/Wind Harmer
-0.056
3146776BUCKING
Solar/Wind Harmer
-0.05
3151731LOISA B
50/50
41.884
3151751LOISA D
50/50
41.884
3151921BEARGRDN G2
50/50
0.724
3147666LOUISA
Solar/Wind Harmer
-4.404
3148013FISHERV
Solar/Wind Harmer
-0.189
3148013FISHERV
Solar/Wind Harmer
-0.108
3151771S ANNAG1
50/50
2.477
971447AH1-217 GEN
Solar/Wind Harmer
0.199
3147623JAMES R
Solar/Wind Harmer
0.009
972003AH1-546 GEN
Solar/Wind Harmer
0.272
3148133STUARTS
Solar/Wind Harmer
-0.113
3147346CASHSCORNER
Solar/Wind Harmer
0.056
3151801S ANNAS2
50/50
1.35
3147666LOUISA
Solar/Wind Harmer
-7.659
971377AH1-170 GEN
Solar/Wind Harmer
0.07
3151791S ANNAG2
50/50
2.477
3151931BEARGRDN S1
50/50
1.247
316164AC1-076 GEN
Solar/Wind Harmer
0
970285AG2-188 GEN
Solar/Wind Harmer
0.353
971133AH1-012 GEN
50/50
15.037
315651AD1-115 GEN
Solar/Wind Harmer
0
971489AH1-241 GEN
Solar/Wind Harmer
0.348
3151741LOISA C
50/50
41.884
3146776BUCKING
Solar/Wind Harmer
-0.617
970221AG2-151 GEN
Solar/Wind Harmer
0.348
3151761LOISA E
50/50
95.063
315821AE2-092 GEN
Solar/Wind Harmer
0
3151781S ANNAS1
50/50
1.35
972183AH1-676 GEN
50/50
596.542
3138266HYDRAULIC
Solar/Wind Harmer
-0.018
3138266HYDRAULIC
Solar/Wind Harmer
-0.011
970937AG2-583 GEN
Solar/Wind Harmer
0.311
971845AH1-439 GEN
Solar/Wind Harmer
0.224
CPLELTFEXP_CPLE->PJM
CLTF
0.314
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.877
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.162
LAGNLTFEXP_LAGN->PJM
CLTF
1.06
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.293
TVALTFEXP_TVA->PJM
CLTF
0.554
NYPJM->LTFIMP_NY
CLTF
0.379
LGEELTFEXP_LGEE->PJM
CLTF
0.355
WECLTFEXP_WEC->PJM
CLTF
0.18
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.652
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.056
MECLTFEXP_MEC->PJM
CLTF
0.819
SIGELTFEXP_SIGE->PJM
CLTF
0.027

Details for AH1-012 TP-6SOUTH HALL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
AH1-012 TP-6SOUTH HALL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:109.13 %
Rating:1113.0 MVA
Rating Type:C
MVA to Mitigate:1214.57
MW Contribution:0.4
Bus #Bus NameTypeMW Contribution
3147346CASHSCORNER
Solar/Wind Harmer
0.064
3151801S ANNAS2
50/50
1.508
3147666LOUISA
Solar/Wind Harmer
-8.059
971377AH1-170 GEN
Solar/Wind Harmer
0.08
3151731LOISA B
50/50
47.124
3151751LOISA D
50/50
47.124
3147666LOUISA
Solar/Wind Harmer
-4.634
3148013FISHERV
Solar/Wind Harmer
-0.215
3148013FISHERV
Solar/Wind Harmer
-0.124
3151771S ANNAG1
50/50
2.767
971447AH1-217 GEN
Solar/Wind Harmer
0.229
3147623JAMES R
Solar/Wind Harmer
0.01
972003AH1-546 GEN
Solar/Wind Harmer
0.314
3148133STUARTS
Solar/Wind Harmer
-0.129
3151791S ANNAG2
50/50
2.767
970285AG2-188 GEN
Solar/Wind Harmer
0.411
971133AH1-012 GEN
50/50
15.534
971489AH1-241 GEN
Solar/Wind Harmer
0.401
3151741LOISA C
50/50
47.124
3146776BUCKING
Solar/Wind Harmer
-0.718
3151721LOISA A
50/50
47.124
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.072
3146776BUCKING
Solar/Wind Harmer
-0.065
3146776BUCKING
Solar/Wind Harmer
-0.058
970221AG2-151 GEN
Solar/Wind Harmer
0.401
3151761LOISA E
50/50
106.955
315821AE2-092 GEN
Solar/Wind Harmer
0
3151781S ANNAS1
50/50
1.508
972183AH1-676 GEN
50/50
674.292
3138266HYDRAULIC
Solar/Wind Harmer
-0.02
3138266HYDRAULIC
Solar/Wind Harmer
-0.012
315705AF1-075 GEN
Solar/Wind Harmer
0.185
315683AE1-153 C
Solar/Wind Harmer
3.88
970937AG2-583 GEN
Solar/Wind Harmer
0.362
971845AH1-439 GEN
Solar/Wind Harmer
0.261
CPLELTFEXP_CPLE->PJM
CLTF
0.507
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.343
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.246
LAGNLTFEXP_LAGN->PJM
CLTF
1.307
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.798
TVALTFEXP_TVA->PJM
CLTF
0.682
NYPJM->LTFIMP_NY
CLTF
0.464
LGEELTFEXP_LGEE->PJM
CLTF
0.419
WECLTFEXP_WEC->PJM
CLTF
0.213
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.859
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.512
MECLTFEXP_MEC->PJM
CLTF
0.977
SIGELTFEXP_SIGE->PJM
CLTF
0.032

Details for AH1-012 TP-6SOUTH HALL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
AH1-012 TP-6SOUTH HALL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.79 %
Rating:1113.0 MVA
Rating Type:C
MVA to Mitigate:1210.8
MW Contribution:0.4
Bus #Bus NameTypeMW Contribution
3147346CASHSCORNER
Solar/Wind Harmer
0.064
3151801S ANNAS2
50/50
1.508
3147666LOUISA
Solar/Wind Harmer
-8.059
971377AH1-170 GEN
Solar/Wind Harmer
0.08
3151731LOISA B
50/50
47.124
3151751LOISA D
50/50
47.124
3147666LOUISA
Solar/Wind Harmer
-4.634
3148013FISHERV
Solar/Wind Harmer
-0.215
3148013FISHERV
Solar/Wind Harmer
-0.124
3151771S ANNAG1
50/50
2.767
971447AH1-217 GEN
Solar/Wind Harmer
0.229
3147623JAMES R
Solar/Wind Harmer
0.01
972003AH1-546 GEN
Solar/Wind Harmer
0.314
3148133STUARTS
Solar/Wind Harmer
-0.129
3151791S ANNAG2
50/50
2.767
970285AG2-188 GEN
Solar/Wind Harmer
0.411
971133AH1-012 GEN
50/50
15.534
971489AH1-241 GEN
Solar/Wind Harmer
0.401
3151741LOISA C
50/50
47.124
3146776BUCKING
Solar/Wind Harmer
-0.718
3151721LOISA A
50/50
47.124
270494AE1-108_GEN
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
-0.072
3146776BUCKING
Solar/Wind Harmer
-0.065
3146776BUCKING
Solar/Wind Harmer
-0.058
970221AG2-151 GEN
Solar/Wind Harmer
0.401
3151761LOISA E
50/50
106.955
315821AE2-092 GEN
Solar/Wind Harmer
0
3151781S ANNAS1
50/50
1.508
972183AH1-676 GEN
50/50
674.292
3138266HYDRAULIC
Solar/Wind Harmer
-0.02
3138266HYDRAULIC
Solar/Wind Harmer
-0.012
315705AF1-075 GEN
Solar/Wind Harmer
0.185
970937AG2-583 GEN
Solar/Wind Harmer
0.362
971845AH1-439 GEN
Solar/Wind Harmer
0.261
CPLELTFEXP_CPLE->PJM
CLTF
0.507
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.343
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.246
LAGNLTFEXP_LAGN->PJM
CLTF
1.307
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.798
TVALTFEXP_TVA->PJM
CLTF
0.682
NYPJM->LTFIMP_NY
CLTF
0.464
LGEELTFEXP_LGEE->PJM
CLTF
0.419
WECLTFEXP_WEC->PJM
CLTF
0.213
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.859
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.512
MECLTFEXP_MEC->PJM
CLTF
0.977
SIGELTFEXP_SIGE->PJM
CLTF
0.032
CONTINGENCY 'DVP_P1-2: LN 2199_SRT-A-1'
 OPEN BRANCH FROM BUS 313671 TO BUS 315678 CKT 1   /*6GERMANNA    230.0 - AE1-153 TAP  230.0
END
CONTINGENCY 'DVP_P1-2: LN 2199_SRT-A-2'
 OPEN BRANCH FROM BUS 314758 TO BUS 315678 CKT 1   /*6GORDNVL     230.0 - AE1-153 TAP  230.0
END
CONTINGENCY 'DVP_P7-1: LN 11-2199_SRT-A-1'
 OPEN BRANCH FROM BUS 313227 TO BUS 314769 CKT 1   /*3ORANGE      115.0 - 3ORANGE TAP  115.0
 OPEN BRANCH FROM BUS 313671 TO BUS 315678 CKT 1   /*6GERMANNA    230.0 - AE1-153 TAP  230.0
 OPEN BRANCH FROM BUS 314756 TO BUS 314769 CKT 1   /*3DOUBLDY     115.0 - 3ORANGE TAP  115.0
 OPEN BRANCH FROM BUS 314756 TO BUS 314776 CKT 1   /*3DOUBLDY     115.0 - 3SOMRSET     115.0
 OPEN BRANCH FROM BUS 314757 TO BUS 314776 CKT 1   /*3GORDNVL     115.0 - 3SOMRSET     115.0
 OPEN BRANCH FROM BUS 314769 TO BUS 314815 CKT 1   /*3ORANGE TAP  115.0 - 3OAK GRE     115.0
 OPEN BRANCH FROM BUS 314776 TO BUS 314884 CKT 1   /*3SOMRSET     115.0 - 3SOMRS_1     115.0
 OPEN BUS 313227                                   /*3ORANGE      115.0
 OPEN BUS 314756                                   /*3DOUBLDY     115.0
 OPEN BUS 314769                                   /*3ORANGE TAP  115.0
 OPEN BUS 314776                                   /*3SOMRSET     115.0
 OPEN BUS 314884                                   /*3SOMRS_1     115.0
END
CONTINGENCY 'DVP_P7-1: LN 11-2199_SRT-A-2'
 OPEN BRANCH FROM BUS 313227 TO BUS 314769 CKT 1   /*3ORANGE      115.0 - 3ORANGE TAP  115.0
 OPEN BRANCH FROM BUS 314756 TO BUS 314769 CKT 1   /*3DOUBLDY     115.0 - 3ORANGE TAP  115.0
 OPEN BRANCH FROM BUS 314756 TO BUS 314776 CKT 1   /*3DOUBLDY     115.0 - 3SOMRSET     115.0
 OPEN BRANCH FROM BUS 314757 TO BUS 314776 CKT 1   /*3GORDNVL     115.0 - 3SOMRSET     115.0
 OPEN BRANCH FROM BUS 314758 TO BUS 315678 CKT 1   /*6GORDNVL     230.0 - AE1-153 TAP  230.0
 OPEN BRANCH FROM BUS 314769 TO BUS 314815 CKT 1   /*3ORANGE TAP  115.0 - 3OAK GRE     115.0
 OPEN BRANCH FROM BUS 314776 TO BUS 314884 CKT 1   /*3SOMRSET     115.0 - 3SOMRS_1     115.0
 OPEN BUS 313227                                   /*3ORANGE      115.0
 OPEN BUS 314756                                   /*3DOUBLDY     115.0
 OPEN BUS 314769                                   /*3ORANGE TAP  115.0
 OPEN BUS 314776                                   /*3SOMRSET     115.0
 OPEN BUS 314884                                   /*3SOMRS_1     115.0
END
CONTINGENCY 'DVP_P4-2: H3T2199_SRT-A'
 OPEN BRANCH FROM BUS 314757 TO BUS 314758 CKT 2   /*3GORDNVL     115.0 - 6GORDNVL     230.0
 OPEN BRANCH FROM BUS 314758 TO BUS 315678 CKT 1   /*6GORDNVL     230.0 - AE1-153 TAP  230.0
END
CONTINGENCY 'DVP_P4-2: 2199T2331_SRT-A'
 OPEN BRANCH FROM BUS 313671 TO BUS 313679 CKT 1   /*6GERMANNA    230.0 - 6CIRRUS      230.0
 OPEN BRANCH FROM BUS 313671 TO BUS 315678 CKT 1   /*6GERMANNA    230.0 - AE1-153 TAP  230.0
END
CONTINGENCY 'DVP_P2-2: GERMANNA_SRT-A'
 OPEN BRANCH FROM BUS 313671 TO BUS 313679 CKT 1   /*6GERMANNA    230.0 - 6CIRRUS      230.0
 OPEN BRANCH FROM BUS 313671 TO BUS 315678 CKT 1   /*6GERMANNA    230.0 - AE1-153 TAP  230.0
 OPEN BRANCH FROM BUS 314758 TO BUS 315678 CKT 1   /*6GORDNVL     230.0 - AE1-153 TAP  230.0
 OPEN BUS 315678                                   /*AE1-153 TAP  230.0
 OPEN BUS 315679                                   /*AE1-153 MAIN 230.0
 OPEN BUS 315680                                   /*AE1-153 COL1  34.5
 OPEN BUS 315681                                   /*AE1-153 COL2  34.5
 OPEN BUS 315682                                   /*AE1-153 TER   13.8
 OPEN BUS 315683                                   /*AE1-153 C      0.6
END
313052 to 313046 ckt 1
314745 to 314777 ckt 1
313046 to 314766 ckt 1
314766 to 971132 ckt 1
314777 to 313052 ckt 1
313930 to 314232 ckt 1
971132 to 313930 ckt 1

Light Load Analysis

The New Service Request AG2-151 was evaluated as a 100.0 MW injection

AG2-151 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 100.0 MW (100.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
3BREMO-3FORK UNION 115.0 kV Ckt 2 line
DVP_P1-2: LN 2193_SRT-A
SingleAC115.74 %179.54B207.7910.5
GD2DVP
3FORK UNION-6FORK UNION 115.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 2193_SRT-A
SingleAC119.19 %332.2B395.9317.15
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-3
SingleAC104.83 %830.96B871.0813.83
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-3
SingleAC104.65 %830.96B869.6113.83
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-L
SingleAC121.87 %830.96B1012.6820.81
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC117.54 %830.96B976.7419.57
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-L
SingleAC124.77 %808.4B1008.6120.81
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC120.34 %808.4B972.8319.57
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-L
SingleAC124.16 %808.4B1003.720.81
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC119.74 %808.4B967.9519.57

Details for 3BREMO-3FORK UNION 115.0 kV Ckt 2 line l/o DVP_P1-2: LN 2193_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3BREMO-3FORK UNION 115.0 kV Ckt 2 line
Contingency Name:
DVP_P1-2: LN 2193_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.74 %
Rating:179.54 MVA
Rating Type:B
MVA to Mitigate:207.79
MW Contribution:10.5
Bus #Bus NameTypeMW Contribution
3147133PAMPLIN
Solar/Wind Harmer
0.458
3147133PAMPLIN
Solar/Wind Harmer
0.146
3147133PAMPLIN
Solar/Wind Harmer
0.117
3143336POWHATN
Solar/Wind Harmer
0.656
3143336POWHATN
Solar/Wind Harmer
0.558
3146776BUCKING
Solar/Wind Harmer
1.01
3146776BUCKING
Solar/Wind Harmer
0.101
3146776BUCKING
Solar/Wind Harmer
0.091
3146776BUCKING
Solar/Wind Harmer
0.082
3146926FARMVIL
Solar/Wind Harmer
0.119
3146926FARMVIL
Solar/Wind Harmer
0.119
315821AE2-092 GEN
Solar/Wind Helper
6.339
315657AE1-056 GEN
Solar/Wind Harmer
1.751
270494AE1-108_GEN
Solar/Wind Harmer
0
3147623JAMES R
Solar/Wind Harmer
0.274
316322AB2-045
Solar/Wind Harmer
0.007
942461AE2-259 GEN
Solar/Wind Harmer
0
970221AG2-151 GEN
Solar/Wind Harmer
10.497
970285AG2-188 GEN
Solar/Wind Harmer
6.693
970301AG2-198 GEN
Solar/Wind Harmer
2.361
970909AG2-566 GEN
Solar/Wind Harmer
1.526
970937AG2-583 GEN
Solar/Wind Harmer
5.978
971193AH1-056 GEN
Solar/Wind Harmer
2.918
971377AH1-170 GEN
Solar/Wind Harmer
2.099
971489AH1-241 GEN
Solar/Wind Harmer
10.497
958131AF2-107 GEN
Solar/Wind Harmer
1.515
971845AH1-439 GEN
Solar/Wind Harmer
4.212
972003AH1-546 GEN
Solar/Wind Harmer
4.888
972205AH1-687 GEN
50/50
5.599
NYPJM->LTFIMP_NY
CLTF
0.138
CPLELTFEXP_CPLE->PJM
CLTF
0.776
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.017
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.047
LAGNLTFEXP_LAGN->PJM
CLTF
0.299
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.065
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.469
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.509
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.156
MECLTFEXP_MEC->PJM
CLTF
0.018
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.217

Details for 3FORK UNION-6FORK UNION 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3FORK UNION-6FORK UNION 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 2193_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.19 %
Rating:332.2 MVA
Rating Type:B
MVA to Mitigate:395.93
MW Contribution:17.15
Bus #Bus NameTypeMW Contribution
3147133PAMPLIN
Solar/Wind Harmer
0.744
3147133PAMPLIN
Solar/Wind Harmer
0.237
3147133PAMPLIN
Solar/Wind Harmer
0.19
3143336POWHATN
Solar/Wind Harmer
1.064
3143336POWHATN
Solar/Wind Harmer
0.904
3146776BUCKING
Solar/Wind Harmer
1.645
3146776BUCKING
Solar/Wind Harmer
0.164
3146776BUCKING
Solar/Wind Harmer
0.148
3146776BUCKING
Solar/Wind Harmer
0.133
3146926FARMVIL
Solar/Wind Harmer
0.193
3146926FARMVIL
Solar/Wind Harmer
0.193
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
315657AE1-056 GEN
Solar/Wind Harmer
2.844
270494AE1-108_GEN
Solar/Wind Harmer
0
3147623JAMES R
Solar/Wind Harmer
0.447
316322AB2-045
Solar/Wind Harmer
0.012
942461AE2-259 GEN
Solar/Wind Harmer
0
946301AF1-294 GEN
Solar/Wind Harmer
1.827
959311AF2-222 GEN
Solar/Wind Harmer
6.249
961791AG1-021 GEN
Solar/Wind Harmer
0.891
963171AG1-166 GEN
Solar/Wind Harmer
0.891
963181AG1-167 GEN
Solar/Wind Harmer
0.669
963191AG1-168 GEN
Solar/Wind Harmer
0.669
970221AG2-151 GEN
Solar/Wind Harmer
17.153
970285AG2-188 GEN
Solar/Wind Harmer
10.901
970301AG2-198 GEN
Solar/Wind Harmer
3.833
970323AG2-213 GEN
Solar/Wind Harmer
1.25
970681AG2-440 GEN
Solar/Wind Harmer
4.05
970683AG2-441 GEN
Solar/Wind Harmer
5.062
970685AG2-442 GEN
Solar/Wind Harmer
5.67
970909AG2-566 GEN
Solar/Wind Harmer
2.479
970937AG2-583 GEN
Solar/Wind Harmer
9.735
971193AH1-056 GEN
Solar/Wind Harmer
4.741
971377AH1-170 GEN
Solar/Wind Harmer
3.431
971447AH1-217 GEN
Solar/Wind Harmer
9.875
971489AH1-241 GEN
Solar/Wind Harmer
17.153
971563AH1-280 GEN
Solar/Wind Harmer
0.891
958131AF2-107 GEN
Solar/Wind Harmer
2.493
958211AF2-115 GEN
Solar/Wind Harmer
1.114
966251AG1-494 GEN
50/50
2.519
971741AH1-377 GEN
Solar/Wind Harmer
7.956
971845AH1-439 GEN
Solar/Wind Harmer
6.862
972003AH1-546 GEN
Solar/Wind Harmer
7.97
972205AH1-687 GEN
50/50
9.13
NYPJM->LTFIMP_NY
CLTF
0.264
CPLELTFEXP_CPLE->PJM
CLTF
1.255
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.017
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.042
LAGNLTFEXP_LAGN->PJM
CLTF
0.519
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.946
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.829
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.475
TVALTFEXP_TVA->PJM
CLTF
0.271
MECLTFEXP_MEC->PJM
CLTF
0.054
SIGELTFEXP_SIGE->PJM
CLTF
0.001
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
3.698

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.83 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:871.08
MW Contribution:13.83
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.822
3147133PAMPLIN
Solar/Wind Harmer
2.25
3147133PAMPLIN
Solar/Wind Harmer
0.717
3147133PAMPLIN
Solar/Wind Harmer
0.573
3146776BUCKING
Solar/Wind Harmer
5.191
3146776BUCKING
Solar/Wind Harmer
0.519
3146776BUCKING
Solar/Wind Harmer
0.467
3146776BUCKING
Solar/Wind Harmer
0.42
3146926FARMVIL
Solar/Wind Harmer
0.6
3146926FARMVIL
Solar/Wind Harmer
0.6
3144303KENBRDG
Solar/Wind Harmer
0.424
316499AE2-029_GEN
Solar/Wind Helper
0.68
315657AE1-056 GEN
Solar/Wind Harmer
8.599
315785AD2-033 C
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Harmer
0
3147623JAMES R
Solar/Wind Harmer
0.36
316322AB2-045
Solar/Wind Harmer
0.038
942461AE2-259 GEN
Solar/Wind Harmer
0
946301AF1-294 GEN
Solar/Wind Harmer
5.489
959311AF2-222 GEN
Solar/Wind Harmer
18.381
961791AG1-021 GEN
Solar/Wind Harmer
2.677
963171AG1-166 GEN
Solar/Wind Harmer
2.677
963181AG1-167 GEN
Solar/Wind Harmer
2.008
963191AG1-168 GEN
Solar/Wind Harmer
2.008
970221AG2-151 GEN
Solar/Wind Harmer
13.827
970257AG2-171 GEN
Solar/Wind Harmer
6.356
970285AG2-188 GEN
Solar/Wind Harmer
34.291
970301AG2-198 GEN
Solar/Wind Harmer
11.577
970323AG2-213 GEN
Solar/Wind Harmer
8.474
970413AG2-270 GEN
50/50
13.645
970535AG2-341 GEN
50/50
5.405
970681AG2-440 GEN
Solar/Wind Harmer
12.032
970683AG2-441 GEN
Solar/Wind Harmer
15.04
970685AG2-442 GEN
Solar/Wind Harmer
16.845
970909AG2-566 GEN
Solar/Wind Harmer
7.485
970937AG2-583 GEN
Solar/Wind Harmer
38.155
971193AH1-056 GEN
Solar/Wind Harmer
14.332
971377AH1-170 GEN
Solar/Wind Harmer
2.765
971447AH1-217 GEN
Solar/Wind Harmer
1.955
971489AH1-241 GEN
Solar/Wind Harmer
13.827
971563AH1-280 GEN
Solar/Wind Harmer
2.677
958211AF2-115 GEN
Solar/Wind Harmer
3.347
966001AG1-469 GEN
Solar/Wind Helper
0.227
971741AH1-377 GEN
Solar/Wind Harmer
23.714
971775AH1-396 GEN
Solar/Wind Harmer
1.271
971845AH1-439 GEN
Solar/Wind Harmer
21.634
972003AH1-546 GEN
Solar/Wind Harmer
25.42
972205AH1-687 GEN
50/50
29.175
NYPJM->LTFIMP_NY
CLTF
0.546
CPLELTFEXP_CPLE->PJM
CLTF
2.721
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.013
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.02
LAGNLTFEXP_LAGN->PJM
CLTF
1.172
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.609
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.883
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.397
TVALTFEXP_TVA->PJM
CLTF
0.608
MECLTFEXP_MEC->PJM
CLTF
0.18
SIGELTFEXP_SIGE->PJM
CLTF
0.003
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
7.713

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.65 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:869.61
MW Contribution:13.83
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.822
3147133PAMPLIN
Solar/Wind Harmer
2.25
3147133PAMPLIN
Solar/Wind Harmer
0.717
3147133PAMPLIN
Solar/Wind Harmer
0.573
3146776BUCKING
Solar/Wind Harmer
5.191
3146776BUCKING
Solar/Wind Harmer
0.519
3146776BUCKING
Solar/Wind Harmer
0.467
3146776BUCKING
Solar/Wind Harmer
0.42
3146926FARMVIL
Solar/Wind Harmer
0.6
3146926FARMVIL
Solar/Wind Harmer
0.6
3144303KENBRDG
Solar/Wind Harmer
0.424
316499AE2-029_GEN
Solar/Wind Helper
0.68
315657AE1-056 GEN
Solar/Wind Harmer
8.599
315785AD2-033 C
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Harmer
0
3147623JAMES R
Solar/Wind Harmer
0.36
316322AB2-045
Solar/Wind Harmer
0.038
942461AE2-259 GEN
Solar/Wind Harmer
0
946301AF1-294 GEN
Solar/Wind Harmer
5.489
959311AF2-222 GEN
Solar/Wind Harmer
18.381
961791AG1-021 GEN
Solar/Wind Harmer
2.677
963171AG1-166 GEN
Solar/Wind Harmer
2.677
963181AG1-167 GEN
Solar/Wind Harmer
2.008
963191AG1-168 GEN
Solar/Wind Harmer
2.008
970221AG2-151 GEN
Solar/Wind Harmer
13.827
970257AG2-171 GEN
Solar/Wind Harmer
6.356
970285AG2-188 GEN
Solar/Wind Harmer
34.291
970301AG2-198 GEN
Solar/Wind Harmer
11.577
970323AG2-213 GEN
Solar/Wind Harmer
8.474
970413AG2-270 GEN
50/50
13.645
970535AG2-341 GEN
50/50
5.405
970681AG2-440 GEN
Solar/Wind Harmer
12.032
970683AG2-441 GEN
Solar/Wind Harmer
15.04
970685AG2-442 GEN
Solar/Wind Harmer
16.845
970909AG2-566 GEN
Solar/Wind Harmer
7.485
970937AG2-583 GEN
Solar/Wind Harmer
38.155
971193AH1-056 GEN
Solar/Wind Harmer
14.332
971377AH1-170 GEN
Solar/Wind Harmer
2.765
971447AH1-217 GEN
Solar/Wind Harmer
1.955
971489AH1-241 GEN
Solar/Wind Harmer
13.827
971563AH1-280 GEN
Solar/Wind Harmer
2.677
958211AF2-115 GEN
Solar/Wind Harmer
3.347
966001AG1-469 GEN
Solar/Wind Helper
0.227
971741AH1-377 GEN
Solar/Wind Harmer
23.714
971775AH1-396 GEN
Solar/Wind Harmer
1.271
971845AH1-439 GEN
Solar/Wind Harmer
21.634
972003AH1-546 GEN
Solar/Wind Harmer
25.42
972205AH1-687 GEN
50/50
29.175
NYPJM->LTFIMP_NY
CLTF
0.546
CPLELTFEXP_CPLE->PJM
CLTF
2.721
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.013
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.02
LAGNLTFEXP_LAGN->PJM
CLTF
1.172
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.609
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.883
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.397
TVALTFEXP_TVA->PJM
CLTF
0.608
MECLTFEXP_MEC->PJM
CLTF
0.18
SIGELTFEXP_SIGE->PJM
CLTF
0.003
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
7.713

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.87 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:1012.68
MW Contribution:20.81
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.919
3147133PAMPLIN
Solar/Wind Harmer
1.771
3147133PAMPLIN
Solar/Wind Harmer
0.564
3147133PAMPLIN
Solar/Wind Harmer
0.451
3143336POWHATN
Solar/Wind Harmer
2.572
3143336POWHATN
Solar/Wind Harmer
2.186
3146776BUCKING
Solar/Wind Harmer
3.757
3146776BUCKING
Solar/Wind Harmer
0.376
3146776BUCKING
Solar/Wind Harmer
0.338
3146776BUCKING
Solar/Wind Harmer
0.304
3146926FARMVIL
Solar/Wind Harmer
0.45
3146926FARMVIL
Solar/Wind Harmer
0.45
316303AF2-085
50/50
2.018
315616AA1-038_C
Solar/Wind Helper
1.051
315760AF1-028 GEN
50/50
Charging
11.333
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
315779AE2-040
50/50
0.984
316499AE2-029_GEN
Solar/Wind Helper
0.927
315657AE1-056 GEN
Solar/Wind Harmer
6.767
270494AE1-108_GEN
Solar/Wind Harmer
0
3147623JAMES R
Solar/Wind Harmer
0.542
316322AB2-045
Solar/Wind Harmer
0.027
316192AB2-158 GEN
Solar/Wind Helper
1.482
942461AE2-259 GEN
Solar/Wind Harmer
0
944641AF1-129 GEN
50/50
25.205
946301AF1-294 GEN
Solar/Wind Harmer
4.371
959311AF2-222 GEN
Solar/Wind Harmer
15.206
961791AG1-021 GEN
Solar/Wind Harmer
2.132
963041AG1-153 GEN
50/50
5.221
963171AG1-166 GEN
Solar/Wind Harmer
2.132
963181AG1-167 GEN
Solar/Wind Harmer
1.599
963191AG1-168 GEN
Solar/Wind Harmer
1.599
970119AG2-088 GEN
50/50
15.136
970221AG2-151 GEN
Solar/Wind Harmer
20.807
970257AG2-171 GEN
Solar/Wind Harmer
0.174
970285AG2-188 GEN
Solar/Wind Harmer
24.994
970301AG2-198 GEN
Solar/Wind Harmer
9.178
970323AG2-213 GEN
Solar/Wind Harmer
7.068
970413AG2-270 GEN
50/50
14.358
970531AG2-338 GEN
50/50
2.734
970533AG2-339 GEN
50/50
6.834
970535AG2-341 GEN
50/50
5.181
970681AG2-440 GEN
Solar/Wind Harmer
9.775
970683AG2-441 GEN
Solar/Wind Harmer
12.219
970685AG2-442 GEN
Solar/Wind Harmer
13.686
970909AG2-566 GEN
Solar/Wind Harmer
5.934
970937AG2-583 GEN
Solar/Wind Harmer
22.319
971193AH1-056 GEN
Solar/Wind Harmer
11.279
971377AH1-170 GEN
Solar/Wind Harmer
4.161
971447AH1-217 GEN
Solar/Wind Harmer
10.898
971489AH1-241 GEN
Solar/Wind Harmer
20.807
971563AH1-280 GEN
Solar/Wind Harmer
2.132
941591AE2-156 GEN
50/50
5.412
958211AF2-115 GEN
Solar/Wind Harmer
2.665
966001AG1-469 GEN
Solar/Wind Helper
0.334
966251AG1-494 GEN
50/50
3.128
971741AH1-377 GEN
Solar/Wind Harmer
19.305
971845AH1-439 GEN
Solar/Wind Harmer
15.695
972003AH1-546 GEN
Solar/Wind Harmer
17.998
972185AH1-677 GEN
50/50
4.638
972187AH1-678 GEN
50/50
2.367
972205AH1-687 GEN
50/50
20.575
NYPJM->LTFIMP_NY
CLTF
0.718
LGEELTFEXP_LGEE->PJM
CLTF
0.016
WECLTFEXP_WEC->PJM
CLTF
0.003
CPLELTFEXP_CPLE->PJM
CLTF
3.782
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
1.646
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.617
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.656
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.434
TVALTFEXP_TVA->PJM
CLTF
0.852
MECLTFEXP_MEC->PJM
CLTF
0.289
SIGELTFEXP_SIGE->PJM
CLTF
0.006
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.463

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.54 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:976.74
MW Contribution:19.57
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.699
3147133PAMPLIN
Solar/Wind Harmer
1.582
3147133PAMPLIN
Solar/Wind Harmer
0.504
3147133PAMPLIN
Solar/Wind Harmer
0.403
3143336POWHATN
Solar/Wind Harmer
2.224
3143336POWHATN
Solar/Wind Harmer
1.89
3146776BUCKING
Solar/Wind Harmer
3.491
3146776BUCKING
Solar/Wind Harmer
0.349
3146776BUCKING
Solar/Wind Harmer
0.314
3146776BUCKING
Solar/Wind Harmer
0.283
3146926FARMVIL
Solar/Wind Harmer
0.41
3146926FARMVIL
Solar/Wind Harmer
0.41
316303AF2-085
50/50
1.328
315616AA1-038_C
Solar/Wind Helper
1.725
315760AF1-028 GEN
50/50
Charging
15.678
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
316499AE2-029_GEN
Solar/Wind Helper
1.242
315657AE1-056 GEN
Solar/Wind Harmer
6.045
270494AE1-108_GEN
Solar/Wind Harmer
0
3147623JAMES R
Solar/Wind Harmer
0.51
316322AB2-045
Solar/Wind Harmer
0.025
316192AB2-158 GEN
Solar/Wind Helper
1.52
942461AE2-259 GEN
Solar/Wind Harmer
0
946301AF1-294 GEN
Solar/Wind Harmer
3.885
959311AF2-222 GEN
Solar/Wind Harmer
13.304
961791AG1-021 GEN
Solar/Wind Harmer
1.895
963171AG1-166 GEN
Solar/Wind Harmer
1.895
963181AG1-167 GEN
Solar/Wind Harmer
1.421
963191AG1-168 GEN
Solar/Wind Harmer
1.421
970117AG2-086 GEN
50/50
Charging
1.272
970119AG2-088 GEN
50/50
9.961
970221AG2-151 GEN
Solar/Wind Harmer
19.574
970257AG2-171 GEN
Solar/Wind Harmer
0.152
970285AG2-188 GEN
Solar/Wind Harmer
23.134
970301AG2-198 GEN
Solar/Wind Harmer
8.122
970323AG2-213 GEN
Solar/Wind Harmer
6.163
970413AG2-270 GEN
50/50
11.154
970535AG2-341 GEN
50/50
4.269
970681AG2-440 GEN
Solar/Wind Harmer
8.617
970683AG2-441 GEN
Solar/Wind Harmer
10.771
970685AG2-442 GEN
Solar/Wind Harmer
12.063
970909AG2-566 GEN
Solar/Wind Harmer
5.252
970937AG2-583 GEN
Solar/Wind Harmer
20.592
971193AH1-056 GEN
Solar/Wind Harmer
10.075
971377AH1-170 GEN
Solar/Wind Harmer
3.915
971447AH1-217 GEN
Solar/Wind Harmer
10.18
971489AH1-241 GEN
Solar/Wind Harmer
19.574
971563AH1-280 GEN
Solar/Wind Harmer
1.895
958211AF2-115 GEN
Solar/Wind Harmer
2.369
966001AG1-469 GEN
Solar/Wind Helper
0.358
966251AG1-494 GEN
50/50
3.897
971741AH1-377 GEN
Solar/Wind Harmer
16.848
971845AH1-439 GEN
Solar/Wind Harmer
14.563
972003AH1-546 GEN
Solar/Wind Harmer
16.919
972205AH1-687 GEN
50/50
19.383
NYPJM->LTFIMP_NY
CLTF
0.753
LGEELTFEXP_LGEE->PJM
CLTF
0.45
WECLTFEXP_WEC->PJM
CLTF
0.221
CPLELTFEXP_CPLE->PJM
CLTF
3.191
LAGNLTFEXP_LAGN->PJM
CLTF
2.588
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.46
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.628
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.28
TVALTFEXP_TVA->PJM
CLTF
1.354
MECLTFEXP_MEC->PJM
CLTF
1.224
SIGELTFEXP_SIGE->PJM
CLTF
0.038
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.284

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.77 %
Rating:808.4 MVA
Rating Type:B
MVA to Mitigate:1008.61
MW Contribution:20.81
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.919
3147133PAMPLIN
Solar/Wind Harmer
1.771
3147133PAMPLIN
Solar/Wind Harmer
0.564
3147133PAMPLIN
Solar/Wind Harmer
0.451
3143336POWHATN
Solar/Wind Harmer
2.572
3143336POWHATN
Solar/Wind Harmer
2.186
3146776BUCKING
Solar/Wind Harmer
3.757
3146776BUCKING
Solar/Wind Harmer
0.376
3146776BUCKING
Solar/Wind Harmer
0.338
3146776BUCKING
Solar/Wind Harmer
0.304
3146926FARMVIL
Solar/Wind Harmer
0.45
3146926FARMVIL
Solar/Wind Harmer
0.45
316303AF2-085
50/50
2.018
315616AA1-038_C
Solar/Wind Helper
1.051
315760AF1-028 GEN
50/50
Charging
11.333
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
315779AE2-040
50/50
0.984
316499AE2-029_GEN
Solar/Wind Helper
0.927
315657AE1-056 GEN
Solar/Wind Harmer
6.767
270494AE1-108_GEN
Solar/Wind Harmer
0
3147623JAMES R
Solar/Wind Harmer
0.542
316322AB2-045
Solar/Wind Harmer
0.027
316192AB2-158 GEN
Solar/Wind Helper
1.482
942461AE2-259 GEN
Solar/Wind Harmer
0
944641AF1-129 GEN
50/50
25.205
946301AF1-294 GEN
Solar/Wind Harmer
4.371
959311AF2-222 GEN
Solar/Wind Harmer
15.206
961791AG1-021 GEN
Solar/Wind Harmer
2.132
963041AG1-153 GEN
50/50
5.221
963171AG1-166 GEN
Solar/Wind Harmer
2.132
963181AG1-167 GEN
Solar/Wind Harmer
1.599
963191AG1-168 GEN
Solar/Wind Harmer
1.599
970119AG2-088 GEN
50/50
15.136
970221AG2-151 GEN
Solar/Wind Harmer
20.807
970257AG2-171 GEN
Solar/Wind Harmer
0.174
970285AG2-188 GEN
Solar/Wind Harmer
24.994
970301AG2-198 GEN
Solar/Wind Harmer
9.178
970323AG2-213 GEN
Solar/Wind Harmer
7.068
970413AG2-270 GEN
50/50
14.358
970531AG2-338 GEN
50/50
2.734
970533AG2-339 GEN
50/50
6.834
970535AG2-341 GEN
50/50
5.181
970681AG2-440 GEN
Solar/Wind Harmer
9.775
970683AG2-441 GEN
Solar/Wind Harmer
12.219
970685AG2-442 GEN
Solar/Wind Harmer
13.686
970909AG2-566 GEN
Solar/Wind Harmer
5.934
970937AG2-583 GEN
Solar/Wind Harmer
22.319
971193AH1-056 GEN
Solar/Wind Harmer
11.279
971377AH1-170 GEN
Solar/Wind Harmer
4.161
971447AH1-217 GEN
Solar/Wind Harmer
10.898
971489AH1-241 GEN
Solar/Wind Harmer
20.807
971563AH1-280 GEN
Solar/Wind Harmer
2.132
941591AE2-156 GEN
50/50
5.412
958211AF2-115 GEN
Solar/Wind Harmer
2.665
966001AG1-469 GEN
Solar/Wind Helper
0.334
966251AG1-494 GEN
50/50
3.128
971741AH1-377 GEN
Solar/Wind Harmer
19.305
971845AH1-439 GEN
Solar/Wind Harmer
15.695
972003AH1-546 GEN
Solar/Wind Harmer
17.998
972185AH1-677 GEN
50/50
4.638
972187AH1-678 GEN
50/50
2.367
972205AH1-687 GEN
50/50
20.575
NYPJM->LTFIMP_NY
CLTF
0.718
LGEELTFEXP_LGEE->PJM
CLTF
0.016
WECLTFEXP_WEC->PJM
CLTF
0.003
CPLELTFEXP_CPLE->PJM
CLTF
3.782
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
1.646
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.617
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.656
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.434
TVALTFEXP_TVA->PJM
CLTF
0.852
MECLTFEXP_MEC->PJM
CLTF
0.289
SIGELTFEXP_SIGE->PJM
CLTF
0.006
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.463

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.34 %
Rating:808.4 MVA
Rating Type:B
MVA to Mitigate:972.83
MW Contribution:19.57
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.699
3147133PAMPLIN
Solar/Wind Harmer
1.582
3147133PAMPLIN
Solar/Wind Harmer
0.504
3147133PAMPLIN
Solar/Wind Harmer
0.403
3143336POWHATN
Solar/Wind Harmer
2.224
3143336POWHATN
Solar/Wind Harmer
1.89
3146776BUCKING
Solar/Wind Harmer
3.491
3146776BUCKING
Solar/Wind Harmer
0.349
3146776BUCKING
Solar/Wind Harmer
0.314
3146776BUCKING
Solar/Wind Harmer
0.283
3146926FARMVIL
Solar/Wind Harmer
0.41
3146926FARMVIL
Solar/Wind Harmer
0.41
316303AF2-085
50/50
1.328
315616AA1-038_C
Solar/Wind Helper
1.725
315760AF1-028 GEN
50/50
Charging
15.678
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
316499AE2-029_GEN
Solar/Wind Helper
1.242
315657AE1-056 GEN
Solar/Wind Harmer
6.045
270494AE1-108_GEN
Solar/Wind Harmer
0
3147623JAMES R
Solar/Wind Harmer
0.51
316322AB2-045
Solar/Wind Harmer
0.025
316192AB2-158 GEN
Solar/Wind Helper
1.52
942461AE2-259 GEN
Solar/Wind Harmer
0
946301AF1-294 GEN
Solar/Wind Harmer
3.885
959311AF2-222 GEN
Solar/Wind Harmer
13.304
961791AG1-021 GEN
Solar/Wind Harmer
1.895
963171AG1-166 GEN
Solar/Wind Harmer
1.895
963181AG1-167 GEN
Solar/Wind Harmer
1.421
963191AG1-168 GEN
Solar/Wind Harmer
1.421
970117AG2-086 GEN
50/50
Charging
1.272
970119AG2-088 GEN
50/50
9.961
970221AG2-151 GEN
Solar/Wind Harmer
19.574
970257AG2-171 GEN
Solar/Wind Harmer
0.152
970285AG2-188 GEN
Solar/Wind Harmer
23.134
970301AG2-198 GEN
Solar/Wind Harmer
8.122
970323AG2-213 GEN
Solar/Wind Harmer
6.163
970413AG2-270 GEN
50/50
11.154
970535AG2-341 GEN
50/50
4.269
970681AG2-440 GEN
Solar/Wind Harmer
8.617
970683AG2-441 GEN
Solar/Wind Harmer
10.771
970685AG2-442 GEN
Solar/Wind Harmer
12.063
970909AG2-566 GEN
Solar/Wind Harmer
5.252
970937AG2-583 GEN
Solar/Wind Harmer
20.592
971193AH1-056 GEN
Solar/Wind Harmer
10.075
971377AH1-170 GEN
Solar/Wind Harmer
3.915
971447AH1-217 GEN
Solar/Wind Harmer
10.18
971489AH1-241 GEN
Solar/Wind Harmer
19.574
971563AH1-280 GEN
Solar/Wind Harmer
1.895
958211AF2-115 GEN
Solar/Wind Harmer
2.369
966001AG1-469 GEN
Solar/Wind Helper
0.358
966251AG1-494 GEN
50/50
3.897
971741AH1-377 GEN
Solar/Wind Harmer
16.848
971845AH1-439 GEN
Solar/Wind Harmer
14.563
972003AH1-546 GEN
Solar/Wind Harmer
16.919
972205AH1-687 GEN
50/50
19.383
NYPJM->LTFIMP_NY
CLTF
0.753
LGEELTFEXP_LGEE->PJM
CLTF
0.45
WECLTFEXP_WEC->PJM
CLTF
0.221
CPLELTFEXP_CPLE->PJM
CLTF
3.191
LAGNLTFEXP_LAGN->PJM
CLTF
2.588
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.46
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.628
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.28
TVALTFEXP_TVA->PJM
CLTF
1.354
MECLTFEXP_MEC->PJM
CLTF
1.224
SIGELTFEXP_SIGE->PJM
CLTF
0.038
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.284

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.16 %
Rating:808.4 MVA
Rating Type:B
MVA to Mitigate:1003.7
MW Contribution:20.81
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.919
3147133PAMPLIN
Solar/Wind Harmer
1.771
3147133PAMPLIN
Solar/Wind Harmer
0.564
3147133PAMPLIN
Solar/Wind Harmer
0.451
3143336POWHATN
Solar/Wind Harmer
2.572
3143336POWHATN
Solar/Wind Harmer
2.186
3146776BUCKING
Solar/Wind Harmer
3.757
3146776BUCKING
Solar/Wind Harmer
0.376
3146776BUCKING
Solar/Wind Harmer
0.338
3146776BUCKING
Solar/Wind Harmer
0.304
3146926FARMVIL
Solar/Wind Harmer
0.45
3146926FARMVIL
Solar/Wind Harmer
0.45
316303AF2-085
50/50
2.018
315616AA1-038_C
Solar/Wind Helper
1.051
315760AF1-028 GEN
50/50
Charging
11.333
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
315779AE2-040
50/50
0.984
316499AE2-029_GEN
Solar/Wind Helper
0.927
315657AE1-056 GEN
Solar/Wind Harmer
6.767
270494AE1-108_GEN
Solar/Wind Harmer
0
3147623JAMES R
Solar/Wind Harmer
0.542
316322AB2-045
Solar/Wind Harmer
0.027
316192AB2-158 GEN
Solar/Wind Helper
1.482
942461AE2-259 GEN
Solar/Wind Harmer
0
944641AF1-129 GEN
50/50
25.205
946301AF1-294 GEN
Solar/Wind Harmer
4.371
959311AF2-222 GEN
Solar/Wind Harmer
15.206
961791AG1-021 GEN
Solar/Wind Harmer
2.132
963041AG1-153 GEN
50/50
5.221
963171AG1-166 GEN
Solar/Wind Harmer
2.132
963181AG1-167 GEN
Solar/Wind Harmer
1.599
963191AG1-168 GEN
Solar/Wind Harmer
1.599
970119AG2-088 GEN
50/50
15.136
970221AG2-151 GEN
Solar/Wind Harmer
20.807
970257AG2-171 GEN
Solar/Wind Harmer
0.174
970285AG2-188 GEN
Solar/Wind Harmer
24.994
970301AG2-198 GEN
Solar/Wind Harmer
9.178
970323AG2-213 GEN
Solar/Wind Harmer
7.068
970413AG2-270 GEN
50/50
14.358
970531AG2-338 GEN
50/50
2.734
970533AG2-339 GEN
50/50
6.834
970535AG2-341 GEN
50/50
5.181
970681AG2-440 GEN
Solar/Wind Harmer
9.775
970683AG2-441 GEN
Solar/Wind Harmer
12.219
970685AG2-442 GEN
Solar/Wind Harmer
13.686
970909AG2-566 GEN
Solar/Wind Harmer
5.934
970937AG2-583 GEN
Solar/Wind Harmer
22.319
971193AH1-056 GEN
Solar/Wind Harmer
11.279
971377AH1-170 GEN
Solar/Wind Harmer
4.161
971447AH1-217 GEN
Solar/Wind Harmer
10.898
971489AH1-241 GEN
Solar/Wind Harmer
20.807
971563AH1-280 GEN
Solar/Wind Harmer
2.132
941591AE2-156 GEN
50/50
5.412
958211AF2-115 GEN
Solar/Wind Harmer
2.665
966001AG1-469 GEN
Solar/Wind Helper
0.334
966251AG1-494 GEN
50/50
3.128
971741AH1-377 GEN
Solar/Wind Harmer
19.305
971845AH1-439 GEN
Solar/Wind Harmer
15.695
972003AH1-546 GEN
Solar/Wind Harmer
17.998
972185AH1-677 GEN
50/50
4.638
972187AH1-678 GEN
50/50
2.367
972205AH1-687 GEN
50/50
20.575
NYPJM->LTFIMP_NY
CLTF
0.718
LGEELTFEXP_LGEE->PJM
CLTF
0.016
WECLTFEXP_WEC->PJM
CLTF
0.003
CPLELTFEXP_CPLE->PJM
CLTF
3.782
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
1.646
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.617
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.656
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.434
TVALTFEXP_TVA->PJM
CLTF
0.852
MECLTFEXP_MEC->PJM
CLTF
0.289
SIGELTFEXP_SIGE->PJM
CLTF
0.006
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.463

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.74 %
Rating:808.4 MVA
Rating Type:B
MVA to Mitigate:967.95
MW Contribution:19.57
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.699
3147133PAMPLIN
Solar/Wind Harmer
1.582
3147133PAMPLIN
Solar/Wind Harmer
0.504
3147133PAMPLIN
Solar/Wind Harmer
0.403
3143336POWHATN
Solar/Wind Harmer
2.224
3143336POWHATN
Solar/Wind Harmer
1.89
3146776BUCKING
Solar/Wind Harmer
3.491
3146776BUCKING
Solar/Wind Harmer
0.349
3146776BUCKING
Solar/Wind Harmer
0.314
3146776BUCKING
Solar/Wind Harmer
0.283
3146926FARMVIL
Solar/Wind Harmer
0.41
3146926FARMVIL
Solar/Wind Harmer
0.41
316303AF2-085
50/50
1.328
315616AA1-038_C
Solar/Wind Helper
1.725
315760AF1-028 GEN
50/50
Charging
15.678
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
316499AE2-029_GEN
Solar/Wind Helper
1.242
315657AE1-056 GEN
Solar/Wind Harmer
6.045
270494AE1-108_GEN
Solar/Wind Harmer
0
3147623JAMES R
Solar/Wind Harmer
0.51
316322AB2-045
Solar/Wind Harmer
0.025
316192AB2-158 GEN
Solar/Wind Helper
1.52
942461AE2-259 GEN
Solar/Wind Harmer
0
946301AF1-294 GEN
Solar/Wind Harmer
3.885
959311AF2-222 GEN
Solar/Wind Harmer
13.304
961791AG1-021 GEN
Solar/Wind Harmer
1.895
963171AG1-166 GEN
Solar/Wind Harmer
1.895
963181AG1-167 GEN
Solar/Wind Harmer
1.421
963191AG1-168 GEN
Solar/Wind Harmer
1.421
970117AG2-086 GEN
50/50
Charging
1.272
970119AG2-088 GEN
50/50
9.961
970221AG2-151 GEN
Solar/Wind Harmer
19.574
970257AG2-171 GEN
Solar/Wind Harmer
0.152
970285AG2-188 GEN
Solar/Wind Harmer
23.134
970301AG2-198 GEN
Solar/Wind Harmer
8.122
970323AG2-213 GEN
Solar/Wind Harmer
6.163
970413AG2-270 GEN
50/50
11.154
970535AG2-341 GEN
50/50
4.269
970681AG2-440 GEN
Solar/Wind Harmer
8.617
970683AG2-441 GEN
Solar/Wind Harmer
10.771
970685AG2-442 GEN
Solar/Wind Harmer
12.063
970909AG2-566 GEN
Solar/Wind Harmer
5.252
970937AG2-583 GEN
Solar/Wind Harmer
20.592
971193AH1-056 GEN
Solar/Wind Harmer
10.075
971377AH1-170 GEN
Solar/Wind Harmer
3.915
971447AH1-217 GEN
Solar/Wind Harmer
10.18
971489AH1-241 GEN
Solar/Wind Harmer
19.574
971563AH1-280 GEN
Solar/Wind Harmer
1.895
958211AF2-115 GEN
Solar/Wind Harmer
2.369
966001AG1-469 GEN
Solar/Wind Helper
0.358
966251AG1-494 GEN
50/50
3.897
971741AH1-377 GEN
Solar/Wind Harmer
16.848
971845AH1-439 GEN
Solar/Wind Harmer
14.563
972003AH1-546 GEN
Solar/Wind Harmer
16.919
972205AH1-687 GEN
50/50
19.383
NYPJM->LTFIMP_NY
CLTF
0.753
LGEELTFEXP_LGEE->PJM
CLTF
0.45
WECLTFEXP_WEC->PJM
CLTF
0.221
CPLELTFEXP_CPLE->PJM
CLTF
3.191
LAGNLTFEXP_LAGN->PJM
CLTF
2.588
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.46
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.628
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.28
TVALTFEXP_TVA->PJM
CLTF
1.354
MECLTFEXP_MEC->PJM
CLTF
1.224
SIGELTFEXP_SIGE->PJM
CLTF
0.038
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.284
CONTINGENCY 'DVP_P1-2: LN 2193_SRT-A'
 OPEN BRANCH FROM BUS 313707 TO BUS 313867 CKT 1   /*6FORK UNION  230.0 - 6BREMODIST   230.0
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BUS 313867                                   /*6BREMODIST   230.0
END
CONTINGENCY 'DVP_P1-2: LN 2027_SRT-A-3'
 OPEN BRANCH FROM BUS 314322 TO BUS 314333 CKT 1   /*6MDLTHAN     230.0 - 6POWHATN     230.0
 OPEN BRANCH FROM BUS 314333 TO BUS 316335 CKT 1   /*6POWHATN     230.0 - AC2-165 TAP  230.0
 OPEN BUS 314333                                   /*6POWHATN     230.0
 OPEN BUS 316258                                   /*AE1-075 C    230.0
 OPEN BUS 316313                                   /*AB2-026      230.0
 OPEN BUS 316405                                   /*AF2-144 C    230.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-L'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3914 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET PRECONTRATING 3880 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON      500.0 - 8MDLTHAN     500.0
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
314744 to 313708 ckt 2
313708 to 313707 ckt 1
314747 to 313867 ckt 1
313867 to 313707 ckt 1
313707 to 313373 ckt 1
313373 to 314765 ckt 1
314765 to 314749 ckt 1

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-038Lexington-Low Moor 230kVUnder Construction
AA1-050Tarboro-Everetts 230kVIn Service
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-067Everetts 34.5kVIn Service
AA1-095Halfway-Marlowe 34.5kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA1-145Four Rivers 230kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-057Hornertown-Whitakers 115kVIn Service
AA2-174Carolina-Jackson 115kVIn Service
AA2-178Mackeys 230kVIn Service
AA2-184Atlantic-Red Bank 34kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-096Carroll-Mt. Airy 34.5kVIn Service
AB1-124Carroll-Monocacy 34.5kVPartially in Service - Under Construction
AB1-125Carroll-Monocacy 34.5kVIn Service
AB1-127St. Thomas-Guilford 34.5kVIn Service
AB1-128St. Thomas-Mercersburg 34.5kVIn Service
AB1-132Thelma 230kVIn Service
AB1-138Navy 34.5kVIn Service
AB1-139Metuchen 26kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB2-022Elizabeth City 34.5kVIn Service
AB2-024Correctional 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-031Brink-Trego 115kVIn Service
AB2-032Church-Wye Mills 138 kVIn Service
AB2-037Keeney-Steele 230kVUnder Construction
AB2-040Brink 115kVIn Service
AB2-043Chase City 115kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-049Gloucester Township 12kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-134Hopewell-Surry 230kVIn Service
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVUnder Construction
AB2-153Church-Wye Mills 138 kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-169Pantago-Five Points 115kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AB2-179Townsend 138kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-010Gloucester 26kVUnder Construction
AC1-017Levittown 13 kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVSuspended
AC1-036Twittys Creek 34.5kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-086Thelma 230kVSuspended
AC1-091Cedar Creek 138kV IEngineering & Procurement
AC1-092Cedar Creek 138kV IIEngineering & Procurement
AC1-093Cedar Creek 138kV IIIEngineering & Procurement
AC1-094Cedar Creek 138kV IVEngineering & Procurement
AC1-098Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-099Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-191Elmont 115kVEngineering & Procurement
AC1-208Cox-Whitakers 115kVUnder Construction
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-023Hebron 69kVEngineering & Procurement
AC2-079Ivor-Oak Ridge 115kVSuspended
AC2-100Halifax-Person 230kVIn Service
AC2-120Ripley 69kVIn Service
AC2-136East Hagerstown 12kVUnder Construction
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-165Bremo-Powhatan 230kVSuspended
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AD1-017Smith Mountain-Bearskin 138 kVIn Service
AD1-020Hunterstown-Lincoln 115 kVIn Service
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVUnder Construction
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-060Mercersburg-Milnor 34.5 kVIn Service
AD1-061McConnelsburg-Mercersburg 34 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-088Briery-Clover 230 kVSuspended
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-144Kings Fork 34.5 kVIn Service
AD1-151Hopewell-Surry 230 kVSuspended
AD1-152Clover-Sedge Hill 230 kVIn Service
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-009McConnellsburg 138 kVIn Service
AD2-022East Danville - Roxborough 230 kVEngineering & Procurement
AD2-023East Danville - Roxborough 230 kVEngineering & Procurement
AD2-027Camden Switch 26 kVIn Service
AD2-030Wan 34.5 kVIn Service
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-042Camden Switch 26 kV IIIn Service
AD2-058St. Barnabas 13 kVIn Service
AD2-065Atco 12 kVIn Service
AD2-070Gilbert-Morris Park 34.5kVIn Service
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVEngineering & Procurement
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-115Lyons-Moselem 69kVIn Service
AD2-116Hokes-Grantley 69 kVIn Service
AD2-135Williamstown 12kVPartially in Service - Under Construction
AD2-160Hickory-Moyock 230kVIn Service
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-041Edison 4kVIn Service
AE1-056Red House-South Creek 115 kVWithdrawn
AE1-071Shade Gap-Roxbury 115 kVIn Service
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-081Landing 12.47 kVIn Service
AE1-100Axton 138 kVIn Service
AE1-101McConnellsburg-Texas Eastern 138 kVIn Service
AE1-103Holland-Union Camp 115 kVUnder Construction
AE1-108Bremo-Scottsville 138 kVEngineering & Procurement
AE1-142Manitou-Pleasant Plains 34.5 kVIn Service
AE1-148Kerr Dam-Ridge Rd 115 kVActive
AE1-149Disputanta-Poe 115 kVSuspended
AE1-153Remington-Gordonsville 230 kVSuspended
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-156Quakertown Solar II 34.5 kVPartially in Service - Under Construction
AE1-157Ladysmith CT-St. Johns 230 kVSuspended
AE1-162Smithfield 34.5 kVIn Service
AE1-173Carson-Suffolk 500 kVUnder Construction
AE1-175Light Foot 34.5 kVIn Service
AE1-185Hokes-Jackson 69 kVIn Service
AE1-190Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-191Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-196Hokes-Jackson 69 kV IIIn Service
AE1-229Deepwater-Upper Pittsgrove 138 kVSuspended
AE1-250Smith Mountain-E. Danville 138 kVEngineering & Procurement
AE2-005Harmony Village-Shackleford 115 kVUnder Construction
AE2-019New Road 230 kVUnder Construction
AE2-027Harrowgate-Locks 115kVUnder Construction
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-033Clubhouse-Sapony 230 kVSuspended
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-040Sapony 34.5 kVPartially in Service - Under Construction
AE2-042Milton 69 kVIn Service
AE2-047Ridgeway-Solite 69 kVEngineering & Procurement
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-054Warfordsburg 34 kVIn Service
AE2-059Derry Tap-Derry Bus 69 kVIn Service
AE2-060Mifflintown Bus-Mifflintown Tap 69 kVIn Service
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-094Carson-Rogers Road 500 kVEngineering & Procurement
AE2-104Suffolk 115 kVSuspended
AE2-133Penns Tap-Richfield Tie 69 kVIn Service
AE2-140Axton-Danville 138 kVSuspended
AE2-156Yadkin 115 kVActive
AE2-166Stockton 138 kVSuspended
AE2-175Jackson-Long Pond 69 kVPartially in Service - Under Construction
AE2-183Rogers Road 500 kVIn Service
AE2-185Gladys DP-Stonemill Switching Station 69 kVActive
AE2-187Shockoe DP-Chatham 69 kVActive
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-253Hickory-Moyock 230 kVIn Service
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVActive
AE2-291Grit DP-Perth 115 kVActive
AE2-346Ahoskie 34.5 kVIn Service
AF1-007Indian River 230 kV ISuspended
AF1-014Harmony Village-Shackleford 115 kVUnder Construction
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-028Endless Caverns 115 kVUnder Construction
AF1-032Suffolk 34.5 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-049Berry Hill 138 kVUnder Construction
AF1-058Welco 34.5 kVIn Service
AF1-069Carson-Rogers Rd 500 kVEngineering & Procurement
AF1-075Harrisburg-Endless Caverns 230 kVSuspended
AF1-114Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF1-123Harper 230 kVActive
AF1-124Harper 230 kVActive
AF1-125Harper 230 kVActive
AF1-128Chesterfield 230 kVActive
AF1-129Chesterfield 230 kVEngineering & Procurement
AF1-136Warfordsburg-Purcell Junction 34.5 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVUnder Construction
AF1-254Milnor-Huyetts 34.5 kVUnder Construction
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF1-290Feagans Mill-Millville 138 kVIn Service
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-292Fields 34.5kVEngineering & Procurement
AF1-294Jetersville-Ponton 115 kVActive
AF1-299Otter Point 34.5 kV IIn Service
AF1-300Otter Point 34.5 kV IIIn Service
AF1-320Merrill Creek 115 kVEngineering & Procurement
AF1-333Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-337Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-338Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-339Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF2-013Arnold's Corner-Dahlgren 230 kVEngineering & Procurement
AF2-035St. Johns 115 kVActive
AF2-042Clover-Rawlings 500 kVActive
AF2-043Suffolk 34.5 kVIn Service
AF2-046Tunis-Mapleton 115 kVActive
AF2-054Wan 34.5 kVIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-080Chinquapin-Everetts 230 kVActive
AF2-081Moyock 230 kVActive
AF2-085Midlothian 34.5 kVIn Service
AF2-086Scott Tap-Bowmans Mill Tap 69 kVEngineering & Procurement
AF2-107Clifford 138 kVEngineering & Procurement
AF2-110Suffolk 115 kVSuspended
AF2-115Jetersville-Ponton 115 kVActive
AF2-120Garner-Northern Neck 115 kVActive
AF2-138Flanders-West Wharton 34.5 kVIn Service
AF2-139Gilbert-Warren Glen 34.5 kVIn Service
AF2-144Powhatan 34.5 kVIn Service
AF2-192Frenchtown Solar-West Flemington 34.5 kVSuspended
AF2-222Madisonville DP-Twitty's Creek 115 kVActive
AF2-229Roxbury 23 kVEngineering & Procurement
AF2-233Penns-Richfield Tie #1 69 kVEngineering & Procurement
AF2-234Sunbury Yard #1-Richfield Tie #2 69 kVEngineering & Procurement
AF2-247Bustleton 13.2 kVIn Service
AF2-250Edgewood 12 kV IIIIn Service
AF2-297Sedge Hill 115 kVActive
AF2-299Fields 34.5 kVActive
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-354Washington 34.5 kV IIEngineering & Procurement
AF2-361Mifflintown Tap 69 kVEngineering & Procurement
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AF2-383Tolna 115 kVWithdrawn
AF2-417West Damascus Tap-West Damascus 69 kVEngineering & Procurement
AF2-421East Hazelton-Weatherly Tap 69Engineering & Procurement
AF2-424Reed-Reed Tap #1 69 kVEngineering & Procurement
AF2-425Reed-Reed Tap#1 69 kVEngineering & Procurement
AF2-433Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AF2-434Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AG1-007Tar River 12.5 kVEngineering & Procurement
AG1-008Tunis-Mapleton 115 kVActive
AG1-021Jetersville-Ponton 115 kVActive
AG1-037Ahoskie 34.5 kVEngineering & Procurement
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-082Ahoskie 34.5 kVActive
AG1-098Briery-Clover 230 kVActive
AG1-105Mount Laurel-Barnes Junction 115 kVActive
AG1-106Thelma 230 kVActive
AG1-124Gladstone 138 kVActive
AG1-135Garner-Lancaster 115 kVActive
AG1-145Lightfoot 34.5 kVIn Service
AG1-146Garner DP-Lancaster 115 kVActive
AG1-147Garner DP-Lancaster 115 kVActive
AG1-153Heritage 500 kVActive
AG1-154Ladysmith CT 230 kVActive
AG1-156Jack Frost-Lake Harmony 69 kVEngineering & Procurement
AG1-164East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-165East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-166Lone Pine 115 kVActive
AG1-167Lone Pine 115 kVActive
AG1-168Lone Pine 115 kVActive
AG1-188Manitou-Oyster Creek 34.5 kVEngineering & Procurement
AG1-189Oyster Creek-Bamber Lake 34.5Engineering & Procurement
AG1-191Chester-Pohatcong Mountain 34.5 kVPartially in Service - Under Construction
AG1-221Poland Rd-Runway DP 230 kVUnder Construction
AG1-223Larrabee-Allaire 34.5 kVUnder Construction
AG1-254Salem-Woodstown 69 kVEngineering & Procurement
AG1-259Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-260Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVEngineering & Procurement
AG1-285Chase City-Central 115 kVActive
AG1-342Dryburg 115 kVActive
AG1-348Pequest River-Washington 34.5 kVIn Service
AG1-393Sapony 34.5 kVActive
AG1-394Boykins 34.5 kVActive
AG1-397Walston 12 kVWithdrawn
AG1-469Gordonsville 34.5 kVEngineering & Procurement
AG1-480Shawnee 34.5 kVEngineering & Procurement
AG1-482Hamilton 115 kVWithdrawn
AG1-494Boxwood-Riverville 138 kVActive
AG1-495Gilbert-Rocktown 34.5 kVEngineering & Procurement
AG1-499Lambs 12.47 kVUnder Construction
AG1-532Fields 34.5 kVEngineering & Procurement
AG1-551Parmele 34.5 kVActive
AG1-552Carolina 34.5 kVActive
AG1-558Buckner 34.5 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
AG2-005Garner DP-Lancaster 115 kVActive
AG2-010Peninsula-Whealton 115 kVActive
AG2-049Van Dorn 34.5 kVActive
AG2-068Heritage - Wake 500 kVActive
AG2-069Heritage - Wake 500 kVActive
AG2-077Clover-Rawlings 500 kVActive
AG2-086Mt. Jackson DP-Mt. Jackson 115 kVActive
AG2-088Midlothian 230 kVActive
AG2-093Colonial Trail-Hopewell 230 kVActive
AG2-095Hopewell 34.5 kV (Circuit 313)Active
AG2-111Perth 34.5 kV Substation (Circuit 408)Active
AG2-112Perth 34.5 kV Substation (Circuit 404)Active
AG2-120Everetts 34.5 kVActive
AG2-124Shackleford-Harmony 115 kVActive
AG2-152Banister-Bear Skin 138 kVActive
AG2-171Lunenburg-Nutbush 115 kVActive
AG2-188Farmville - Buckingham 230 kVActive
AG2-193Turner 34.5 kVActive
AG2-198Briery - Finneywood 230 kVActive
AG2-208Greenwood DP - St. Johns DP 115 kVActive
AG2-213Gary D.P Tap - Gary D.P 115 kVActive
AG2-215Garner DP-Lancaster 115 kVActive
AG2-262Dryburg 115 kVActive
AG2-270Clover 230 kVActive
AG2-304Liberty 230 kVActive
AG2-320Ladysmith 230 kVActive
AG2-338Rogers Road - Carson 500 kVActive
AG2-339Rogers Road - Carson 500 kVActive
AG2-341Ridge Road 115 kVActive
AG2-369Heritage - Wake 500 kVActive
AG2-382Cashie 230 kVActive
AG2-384Chesterfield 230 kVActive
AG2-426Wakefield - Waverly 115 kVActive
AG2-427Waverly 115 kVActive
AG2-428Wakefield 115 kVActive
AG2-436Carson - Rogers Road 500 kVActive
AG2-440Twittys Creek - Madisonville 115 kVActive
AG2-441Twittys Creek - Madisonville 115 kVActive
AG2-442Twittys Creek - Madisonville 115 kVActive
AG2-469Westmoreland – Oak Grove 230 kVActive
AG2-522Five Forks DP 115 kVActive
AG2-541Perth - Crystal Hill 115 kVActive
AG2-566Briery - Finneywood 230 kVActive
AG2-570Heritage - Wake 500 kVActive
AG2-571Heritage - Wake 500 kVActive
AG2-581Rawlings-Clover 500 kVActive
AG2-583Bremo - Cartersville 230 kVActive
AG2-659Kerr Dam – Hawtree 115 kVActive
AG2-661Hopewell - Colonial Trail 230 kVActive
AH1-012Louisa - North Anna 230 kVActive
AH1-033Sligo 34.5 kVActive
AH1-035Plymouth 34.5 kVActive
AH1-040Mackeys - Creswell 115 kVActive
AH1-042Providence Forge-Turner 115kVActive
AH1-056Red House DP 115kVActive
AH1-065Hopewell 34.5kVActive
AH1-066Hopewell 34.5kVActive
AH1-071Midlothian 34.5 kVActive
AH1-086Morrisville 230kVActive
AH1-087Morrisville 230kVActive
AH1-088Morrisville 230kVActive
AH1-089Morrisville 230kVActive
AH1-106Winterpock 34.5kVActive
AH1-107Winterpock 34.5kVActive
AH1-108Spruance NUG 230 kVActive
AH1-138Penniman 34.5 kVActive
AH1-157Penniman - Waller 230 kVActive
AH1-164Oak Level - Tank Hill 138 kVActive
AH1-170Columbia DP 115kVActive
AH1-215Central VA-Twitty 115 kVActive
AH1-216Smithfield-Surry 230 kVActive
AH1-217Kidds Store - Fork Union 115 kV IIActive
AH1-221Heritage 500 kVActive
AH1-223Poland Rd-Runway DP 230 kVActive
AH1-241Cobbs Creek - James River Industrial 115kVActive
AH1-251Todds Tavern- Spotsylvania/Goldsdale 115kVActive
AH1-263Chancellor 115 kVActive
AH1-271Cashie 230 kVActive
AH1-280Jetersville-Ponton 115 kVActive
AH1-311Heartsease DP - Mayo Dunbar 115kVActive
AH1-323Elmont 230 kVActive
AH1-324Colonial Trail – Surry 230 kVActive
AH1-343Crystal Hill DP- Perth 115kVActive
AH1-345Remington 324 34.5 kVActive
AH1-377Clover- Farmville 230kVActive
AH1-387Meadowbrook-Greenland Gap 500kVActive
AH1-396Gary 24.94 kVActive
AH1-397Shacklesford 34.5 kVActive
AH1-399North Doswell 12.5 kVActive
AH1-408Freeman DP – Lawrenceville 115 kVActive
AH1-439Buckingham- Farmville 230kVActive
AH1-528Rawlings - Unity 500 kVActive
AH1-546Bremo - Buckingham 230 kVActive
AH1-637Oak Grove 34.5 kVActive
AH1-676Gordonsville 230 kVActive
AH1-677Rogers Road 500 kVActive
AH1-678Heritage 500 kVActive
AH1-679Four Rivers 230 kVActive
AH1-681Cunningham 500 kVActive
AH1-682Ladysmith CT 230 kVActive
AH1-683Ladysmith CT 230 kVActive
AH1-684Remington CT 230 kVActive
AH1-685Remington CT 230 kVActive
AH1-687Bear Garden 230kVActive
AH1-691Ladysmith CT 230 kVActive
AH1-692Ladysmith CT 230 kVActive
AH1-693Remington CT 230 kVActive
AH1-694Ladysmith CT 230 kVActive
AH1-696Possum Point 230kVActive
AH1-712Cunningham 500 kVActive
AH1-716Surry-Skiffes Creek 500kVActive
AH1-717Surry 230kVActive
AH1-723Cunningham 500 kVActive
AH1-729Ocean Court 230 kVActive
V4-067Cates Road Egg Harbor Township 12kVDeactivated
V4-068Murphy's 34.5kVIn Service
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
W3-077Broadway-Stewartsville 34.5kVIn Service
X3-066Church Hill 69kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y1-086Morgans CornerIn Service
Y3-058Rockawalkin 69kVIn Service
Z1-036WinFall-Chowan 230kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-044Whitakers 34.5kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)Identified Impacts

No cost allocated AFS Tie Line reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.


System Reinforcement
Type
Load Flow
TO
CPLE
RTEP ID / TO ID
(Pending) / TC2-CPLE-0001
Title
Person - VP Hendrick 230kV Line (Existing Line Uprate)
Description
Currently no costs since there is already a DEP project to reconductor to upgrade this line. This is the estimated ISD for the current project CPLE is developing. The Person - Hendrick 230 kV line will be reconductored with bundled 795 ACSS/TW and will have a rating 1195MVA.
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
0 to 48 Months

Info

Note: AG2-151 contributes to the loading of an overloaded tie line facility between PJM and an affected system entity, which was identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line and will be confirmed in subsequent study phases, along with cost allocation of such upgrade if applicable, in coordination with the affected system.

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
CPLE
RTEP ID / TO ID
(Pending) / TC2-CPLE-0002
Title
Person - VP Hendrick 230kV line (New Line)
Description
This project is to add second line that would be built to 1195MVA. Assumed ~5 mile 230kV line with bundled conductor and can utilize last remaining CB bay at Person (no fence expansion). Estimated ISD Assumed 5 years from Kick off to complete work (Site & acquire ROW, engineering, construction) and assuming no other outage constraints (DEP or PJM) from previous projects already planned. The new line will also be bundled 795 ACSS/TW.
Total Cost ($USD)
$28,300,000
Allocated Cost ($USD)
$0
Time Estimate
0 to 60 Months

Info

Note: AG2-151 contributes to the loading of an overloaded tie line facility between PJM and an affected system entity, which was identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line and will be confirmed in subsequent study phases, along with cost allocation of such upgrade if applicable, in coordination with the affected system.

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)

Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Study Pending
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase I analysis results, this project may have a cost responsibility for the following System Reinforcements:

AG2-151 System Reinforcements:
TORTEP IDTitleAllocated Cost ($USD)
Dominionn7796 / dom-302/3Wreck and rebuild 14.01 miles of 230 kV Line 2027 between Midlothian and Powhatan with (2) 768.2 ACSS/TW (20/7) "MAUMEE".$4,103,123
Dominion(Pending) / TC1-PH2-DOM-0012Wreck and rebuild 8.1 miles of 230 kV Line 2027 (future Line 2323) between Bremo and AG2-583 with (2) 768.2 ACSS/TW (20/7) "MAUMEE".$2,704,358
Dominionn8296 / dom-266Add a 2nd new 224 MVA 115/230 kV Transformer at Fork Union substation and add one (1) 115 kV breaker and one (1) 230 kV breaker$2,423,123
Dominionn7568 / dom-369-TC2Wreck and rebuild 6.47 miles of 230 kV transmission line 2028 between Charlottesville and Mt. Eagle with (2) 768.2 ACSS/TW (20/7) ""Maumee"" @ 250C and replace line lead at Mt. Eagle.$2,028,498
Dominionn8256 / dom-277Wreck and rebuild 5.9 miles of 230 kV Line 2027 (future Line 2323) between Cartersville and AC2-165 (Sallee Creek) with (2) 768.2 ACSS/TW (20/7) "MAUMEE".$1,725,982
Dominionn8243 / dom-389Wreck and rebuild 5.8 miles of 230 kV Line 2027 between AC2-165 (Sallee Creek) and Powhatan with (2) 768.2 ACSS/TW (20/7) "MAUMEE".$1,697,936
Dominionn9203.0 / TC1-PH2-DOM-008-TC2Wreck and rebuild 10.74 miles of line 2028 between Fork Union and Cunningham (Grape Vine) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C.$1,662,714
Dominionn9376.0 / TC1-PH3-DOM-003-TC2Wreck and Rebuild 22.98 miles of 230 kV Line 235 from Briery to AG1-098 with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"" at 250 C.$827,471
Dominionn7569 / dom-490-TC2Upgrade a 3.78 mile segment of 230kV transmission line 2028 between Mt. Eagle and Grape Vine Substations at structure 2080/73.$736,406
Dominionn9644.0 / TC1-PH3-DOM-006-TC2Upgrade a 2.73 mile segment of 230kV transmission line 2028 between Mt. Eagle and Grape Vine. This segment runs from Grape Vine substation to structure 2080/73.$463,849
Dominion(Pending) / TC2-PH1-DOM-0013Wreck and rebuild 1.51 miles of 230 kV Line 2027 (future Line 2323) between Cartersville and AG2-583 with (2) 768.2 ACSS/TW (20/7) "MAUMEE".$441,734
Dominionn9198.0 / TC1-PH2-DOM-003-TC2Replace Circuit Breaker 219322 and Circuit Breaker Lead at Bremo 230 kV (Bremo - Fork Union).$74,401
Dominion(Pending) / TC2-PH1-DOM-0014Wreck and rebuild 0.17 miles of 230 kV Line 2027 between Midlothian and Powhatan with (2) 768.2 ACSS/TW (20/7) "MAUMEE".$49,788
Dominion(Pending) / TC2-PH1-DOM-1032Wreck and rebuild 0.73 miles of 230 kV line 235 between AG1-098 and Finneywood with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C$44,900
Dominion(Pending) / TC2-PH1-DOM-2043Wreck and rebuild 0.93 miles of 230 kV Line 2241 between Hendrick and Persons with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Dominion portion of line only.$31,260
Dominion(Pending) / TC2-PH1-DOM-2069Replace 2-1590 AAC line lead on line 2028 at Fork Union 230 kV$29,526
Dominion(Pending) / TC2-PH1-DOM-2073Replace 2-1590 line lead on line 2028 at Charlottesville and Mt Eagle 230 kV$29,035
Dominion(Pending) / TC2-PH1-DOM-2071Replace 2-1590 line lead on line 2028 at Mt. Eagle 230 kV$29,035
Dominion(Pending) / TC2-PH1-DOM-2065Replace switches 219324 and 219325 at Bremo 230 kV$28,157
Dominion(Pending) / TC2-PH1-DOM-2072Replace 2500 ACAR line lead on line 2028 at Charlottesville 230 kV$27,560
Dominion(Pending) / TC2-PH1-DOM-2068Wreck and rebuild 0.12 miles of 230 kV line 2028 between Fork Union and Grape Vine with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C$25,667
Dominion(Pending) / TC2-PH1-DOM-2070Replace wave trap 2028WT at Fork Union 230 kV$22,515
Dominion(Pending) / TC1-PH3-DOM-007Replace Wave Trap 2028WT at Charlottesville$22,048
Dominion(Pending) / TC2-PH1-DOM-2066Replace 2-636 ACSR line lead on line 2193 at Bremo 230 kV$14,838
Dominion(Pending) / TC2-PH1-DOM-2067Replace 3 1/2" pipe line lead on line 2193 at Bremo 230 kV$14,838
Dominion(Pending) / TC2-PH1-DOM-2064Replace 2-1590 line lead on line 2193 at Fork Union 230 kV$14,838
Dominion(Pending) / TC2-PH1-DOM-2063Wreck and rebuild 0.11 miles of 230 kV line 2193 between Fork Union and Bremo Dist with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C$14,712
Dominion(Pending) / TC2-PH1-DOM-0080Replace switch 219326 at Bremo 230 kV$14,079
Grand Total:$19,302,391

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n7796
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7796 / dom-302/3
Title
Wreck and rebuild 14.01 miles of 230 kV Line 2027 between Midlothian and Powhatan with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Description
Wreck and rebuild 14.01 miles of 230 kV Line 2027 between Midlothian and Powhatan with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Total Cost ($USD)
$53,238,000
Allocated Cost ($USD)
$4,103,123
Time Estimate
42 to 48 Months

Contributor

FacilityContingency
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-077
11.6 MW3.8%$2,045,039
AG2-151
23.3 MW7.7%$4,103,123
AG2-188
28.1 MW9.3%$4,948,039
AG2-198
8.4 MW2.8%$1,483,407
AG2-270
9.5 MW3.1%$1,672,909
AG2-440
8.6 MW2.9%$1,518,311
AG2-441
10.8 MW3.6%$1,897,844
AG2-442
12.1 MW4.0%$2,125,600
AG2-566
2.1 MW0.7%$370,896
AG2-581
8.9 MW2.9%$1,564,320
AG2-583
37.4 MW12.4%$6,600,676
AH1-056
12.0 MW4.0%$2,113,965
AH1-217
12.4 MW4.1%$2,185,535
AH1-241
23.3 MW7.7%$4,103,123
AH1-377
16.9 MW5.6%$2,974,570
AH1-439
16.8 MW5.6%$2,955,532
AH1-528
17.7 MW5.9%$3,128,287
AH1-546
20.0 MW6.6%$3,522,452
AH1-687
22.3 MW7.4%$3,924,374

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH2-DOM-0012
Title
Wreck and rebuild 8.1 miles of 230 kV Line 2027 (future Line 2323) between Bremo and AG2-583 with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Description
Wreck and rebuild 8.1 miles of 230 kV Line 2027 (future Line 2323) between Bremo and AG2-583 with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Total Cost ($USD)
$30,780,000
Allocated Cost ($USD)
$2,704,358
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-077
11.7 MW4.4%$1,353,455
AG2-151
23.3 MW8.8%$2,704,358
AG2-188
28.1 MW10.6%$3,262,332
AG2-198
8.4 MW3.2%$979,384
AG2-270
9.5 MW3.6%$1,107,594
AG2-440
8.6 MW3.3%$1,003,054
AG2-441
10.8 MW4.1%$1,253,788
AG2-442
12.1 MW4.6%$1,404,275
AG2-566
2.1 MW0.8%$244,817
AG2-581
8.9 MW3.4%$1,035,193
AH1-056
12.0 MW4.5%$1,395,689
AH1-217
12.4 MW4.7%$1,440,592
AH1-241
23.3 MW8.8%$2,704,358
AH1-377
16.9 MW6.4%$1,964,802
AH1-439
16.8 MW6.3%$1,948,442
AH1-528
17.8 MW6.7%$2,070,270
AH1-546
20.0 MW7.5%$2,321,469
AH1-687
22.3 MW8.4%$2,586,127

System Reinforcement: n8296
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n8296 / dom-266
Title
Add a 2nd new 224 MVA 115/230 kV Transformer at Fork Union substation and add one (1) 115 kV breaker and one (1) 230 kV breaker
Description
Add a 2nd new 224 MVA 115/230 kV Transformer at Fork Union substation and add one (1) 115 kV breaker and one (1) 230 kV breaker
Total Cost ($USD)
$17,500,000
Allocated Cost ($USD)
$2,423,123
Time Estimate
42 to 48 Months

Contributor

FacilityContingency
6FORK UNION-3FORK UNION 230.0/115.0 kV Ckt 1 transformer(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-151
17.8 MW13.8%$2,423,123
AG2-188
12.0 MW9.4%$1,637,293
AG2-198
4.0 MW3.1%$545,492
AG2-440
4.2 MW3.3%$577,356
AG2-441
5.3 MW4.1%$721,694
AG2-442
5.9 MW4.6%$808,298
AG2-566
2.5 MW1.9%$337,562
AG2-583
10.1 MW7.9%$1,379,253
AH1-056
5.7 MW4.4%$770,307
AH1-217
10.2 MW8.0%$1,395,049
AH1-241
17.8 MW13.8%$2,423,123
AH1-377
8.3 MW6.5%$1,133,605
AH1-439
7.1 MW5.6%$972,517
AH1-546
8.3 MW6.4%$1,126,252
AH1-687
9.2 MW7.1%$1,249,076

System Reinforcement: n7568
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7568 / dom-369-TC2
Title
Wreck and rebuild 6.47 miles of 230 kV transmission line 2028 between Charlottesville and Mt. Eagle with (2) 768.2 ACSS/TW (20/7) ""Maumee"" @ 250C and replace line lead at Mt. Eagle.
Description
Wreck and rebuild 6.47 miles of 230 kV transmission line 2028 between Charlottesville and Mt. Eagle with (2) 768.2 ACSS/TW (20/7) ""Maumee"" @ 250C and replace line lead at Mt. Eagle.
Total Cost ($USD)
$36,802,018
Allocated Cost ($USD)
$2,028,498
Time Estimate
43 to 44 Months

Contributor

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.1 MW1.1%$386,666
AG2-069
6.2 MW1.6%$580,093
AG2-077
11.7 MW3.0%$1,098,680
AG2-088
15.4 MW3.9%$1,445,217
AG2-151
21.6 MW5.5%$2,028,498
AG2-171
8.1 MW2.1%$763,488
AG2-188
27.6 MW7.0%$2,583,932
AG2-198
9.6 MW2.4%$898,502
AG2-213
7.4 MW1.9%$693,918
AG2-270
14.4 MW3.7%$1,346,206
AG2-338
2.8 MW0.7%$263,278
AG2-339
7.0 MW1.8%$658,101
AG2-369
0.8 MW0.2%$79,602
AG2-428
7.8 MW2.0%$733,766
AG2-436
28.3 MW7.2%$2,654,439
AG2-440
10.2 MW2.6%$958,602
AG2-441
12.8 MW3.3%$1,198,253
AG2-442
14.3 MW3.6%$1,341,987
AG2-566
5.9 MW1.5%$556,372
AG2-570
6.9 MW1.8%$647,038
AG2-571
2.8 MW0.7%$258,778
AG2-581
7.5 MW1.9%$699,918
AG2-583
23.2 MW5.9%$2,176,826
AH1-056
13.4 MW3.4%$1,260,884
AH1-217
11.3 MW2.9%$1,062,957
AH1-241
21.6 MW5.5%$2,028,498
AH1-377
20.2 MW5.1%$1,891,795
AH1-439
16.3 MW4.2%$1,531,101
AH1-528
13.7 MW3.5%$1,285,543
AH1-546
18.7 MW4.8%$1,751,062
AH1-687
20.7 MW5.3%$1,938,019

System Reinforcement: n8256
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n8256 / dom-277
Title
Wreck and rebuild 5.9 miles of 230 kV Line 2027 (future Line 2323) between Cartersville and AC2-165 (Sallee Creek) with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Description
Wreck and rebuild 5.9 miles of 230 kV Line 2027 (future Line 2323) between Cartersville and AC2-165 (Sallee Creek) with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Total Cost ($USD)
$22,420,000
Allocated Cost ($USD)
$1,725,982
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-077
11.7 MW3.9%$863,806
AG2-151
23.3 MW7.7%$1,725,982
AG2-188
28.1 MW9.3%$2,082,094
AG2-198
8.4 MW2.8%$625,065
AG2-270
9.5 MW3.2%$706,892
AG2-440
8.6 MW2.9%$640,172
AG2-441
10.8 MW3.6%$800,196
AG2-442
12.1 MW4.0%$896,240
AG2-566
2.1 MW0.7%$156,248
AG2-581
8.9 MW2.9%$660,684
AG2-583
37.5 MW12.4%$2,775,508
AH1-056
12.0 MW4.0%$890,760
AH1-217
12.4 MW4.1%$919,418
AH1-241
23.3 MW7.7%$1,725,982
AH1-377
16.9 MW5.6%$1,253,981
AH1-439
16.8 MW5.5%$1,243,540
AH1-528
17.8 MW5.9%$1,321,293
AH1-546
20.0 MW6.6%$1,481,614
AH1-687
22.3 MW7.4%$1,650,524

System Reinforcement: n8243
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n8243 / dom-389
Title
Wreck and rebuild 5.8 miles of 230 kV Line 2027 between AC2-165 (Sallee Creek) and Powhatan with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Description
Wreck and rebuild 5.8 miles of 230 kV Line 2027 between AC2-165 (Sallee Creek) and Powhatan with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Total Cost ($USD)
$22,040,000
Allocated Cost ($USD)
$1,697,936
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-077
11.6 MW3.8%$847,583
AG2-151
23.3 MW7.7%$1,697,936
AG2-188
28.1 MW9.3%$2,047,833
AG2-198
8.4 MW2.8%$614,270
AG2-270
9.5 MW3.1%$693,450
AG2-440
8.6 MW2.9%$628,852
AG2-441
10.8 MW3.6%$786,047
AG2-442
12.1 MW4.0%$880,393
AG2-566
2.1 MW0.7%$153,549
AG2-581
8.9 MW2.9%$648,319
AG2-583
37.5 MW12.4%$2,731,003
AH1-056
12.0 MW4.0%$875,362
AH1-217
12.4 MW4.1%$904,453
AH1-241
23.3 MW7.7%$1,697,936
AH1-377
16.9 MW5.6%$1,231,893
AH1-439
16.8 MW5.5%$1,223,144
AH1-528
17.8 MW5.9%$1,296,492
AH1-546
20.0 MW6.6%$1,457,624
AH1-687
22.3 MW7.4%$1,623,860

System Reinforcement: n9203.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9203.0 / TC1-PH2-DOM-008-TC2
Title
Wreck and rebuild 10.74 miles of line 2028 between Fork Union and Cunningham (Grape Vine) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C.
Description
Wreck and rebuild 10.74 miles of line 2028 between Fork Union and Cunningham (Grape Vine) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C.
Total Cost ($USD)
$29,539,973
Allocated Cost ($USD)
$1,662,714
Time Estimate
45 to 46 Months

Contributor

FacilityContingency
6GRAPEVINE-6FORK UNION 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.1 MW1.1%$316,942
AG2-069
6.2 MW1.6%$475,489
AG2-077
11.7 MW3.0%$900,563
AG2-088
15.4 MW4.0%$1,184,612
AG2-151
21.6 MW5.6%$1,662,714
AG2-188
27.6 MW7.2%$2,117,991
AG2-198
9.6 MW2.5%$736,482
AG2-213
7.4 MW1.9%$568,789
AG2-270
14.4 MW3.7%$1,103,455
AG2-338
2.8 MW0.7%$215,803
AG2-339
7.0 MW1.8%$539,431
AG2-369
0.8 MW0.2%$65,248
AG2-428
7.8 MW2.0%$601,451
AG2-436
28.3 MW7.4%$2,175,784
AG2-440
10.2 MW2.7%$785,745
AG2-441
12.8 MW3.3%$982,181
AG2-442
14.3 MW3.7%$1,099,996
AG2-566
5.9 MW1.5%$456,045
AG2-570
6.9 MW1.8%$530,362
AG2-571
2.8 MW0.7%$212,114
AG2-581
7.5 MW1.9%$573,707
AG2-583
23.2 MW6.0%$1,784,295
AH1-056
13.4 MW3.5%$1,033,519
AH1-217
11.3 MW2.9%$871,282
AH1-241
21.6 MW5.6%$1,662,714
AH1-377
20.2 MW5.2%$1,550,662
AH1-439
16.3 MW4.2%$1,255,009
AH1-528
13.7 MW3.6%$1,053,731
AH1-546
18.7 MW4.9%$1,435,306
AH1-687
20.7 MW5.4%$1,588,551

System Reinforcement: n9376.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9376.0 / TC1-PH3-DOM-003-TC2
Title
Wreck and Rebuild 22.98 miles of 230 kV Line 235 from Briery to AG1-098 with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"" at 250 C.
Description
Wreck and Rebuild 22.98 miles of 230 kV Line 235 from Briery to AG1-098 with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"" at 250 C.
Total Cost ($USD)
$69,323,785
Allocated Cost ($USD)
$827,471
Time Estimate
Dec 31 2029

Contributor

FacilityContingency
AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-077
108.9 MW9.3%$6,468,244
AG2-151
13.9 MW1.2%$827,471
AG2-171
23.0 MW2.0%$1,365,259
AG2-188
42.9 MW3.7%$2,546,266
AG2-198
65.5 MW5.6%$3,889,072
AG2-213
30.6 MW2.6%$1,820,365
AG2-270
88.1 MW7.5%$5,231,403
AG2-440
38.3 MW3.3%$2,275,471
AG2-441
47.9 MW4.1%$2,844,324
AG2-442
53.6 MW4.6%$3,185,624
AG2-566
14.0 MW1.2%$829,075
AG2-581
83.6 MW7.2%$4,964,291
AG2-583
14.3 MW1.2%$849,686
AH1-056
38.3 MW3.3%$2,275,471
AH1-215
12.1 MW1.0%$716,753
AH1-217
7.5 MW0.6%$446,731
AH1-241
13.2 MW1.1%$785,596
AH1-280
7.7 MW0.7%$455,106
AH1-377
208.3 MW17.8%$12,372,387
AH1-439
24.6 MW2.1%$1,462,909
AH1-528
167.2 MW14.3%$9,928,404
AH1-546
14.4 MW1.2%$852,477
AH1-676
39.2 MW3.4%$2,328,929
AH1-687
10.1 MW0.9%$602,472

System Reinforcement: n7569
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7569 / dom-490-TC2
Title
Upgrade a 3.78 mile segment of 230kV transmission line 2028 between Mt. Eagle and Grape Vine Substations at structure 2080/73.
Description
Uograde 3.78 miles of transmission line 2028 between Mt. Eagle and Grape Vine with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"". The segment runs from Mt Eagle to structure 2080/73.
Total Cost ($USD)
$13,360,242
Allocated Cost ($USD)
$736,406
Time Estimate
43 to 44 Months

Contributor

FacilityContingency
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.1 MW1.1%$140,371
AG2-069
6.2 MW1.6%$210,591
AG2-077
11.7 MW3.0%$398,854
AG2-088
15.4 MW3.9%$524,657
AG2-151
21.6 MW5.5%$736,406
AG2-171
8.1 MW2.1%$277,169
AG2-188
27.6 MW7.0%$938,045
AG2-198
9.6 MW2.4%$326,183
AG2-213
7.4 MW1.9%$251,913
AG2-270
14.4 MW3.7%$488,713
AG2-338
2.8 MW0.7%$95,578
AG2-339
7.0 MW1.8%$238,911
AG2-369
0.8 MW0.2%$28,898
AG2-428
7.8 MW2.0%$266,379
AG2-436
28.3 MW7.2%$963,641
AG2-440
10.2 MW2.6%$348,002
AG2-441
12.8 MW3.3%$435,002
AG2-442
14.3 MW3.6%$487,182
AG2-566
5.9 MW1.5%$201,980
AG2-570
6.9 MW1.8%$234,894
AG2-571
2.8 MW0.7%$93,944
AG2-581
7.5 MW1.9%$254,091
AG2-583
23.2 MW5.9%$790,253
AH1-056
13.4 MW3.4%$457,739
AH1-217
11.3 MW2.9%$385,885
AH1-241
21.6 MW5.5%$736,406
AH1-377
20.2 MW5.1%$686,779
AH1-439
16.3 MW4.2%$555,836
AH1-528
13.7 MW3.5%$466,691
AH1-546
18.7 MW4.8%$635,688
AH1-687
20.7 MW5.3%$703,559

System Reinforcement: n9644.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9644.0 / TC1-PH3-DOM-006-TC2
Title
Upgrade a 2.73 mile segment of 230kV transmission line 2028 between Mt. Eagle and Grape Vine. This segment runs from Grape Vine substation to structure 2080/73.
Description
Rebuild a 2.73 mile segment of 230kV line 2028 between Mt. Eagle and Grape Vinew with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @250 degrees C.
Total Cost ($USD)
$8,415,380
Allocated Cost ($USD)
$463,849
Time Estimate
Mar 31 2029

Contributor

FacilityContingency
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.1 MW1.1%$88,418
AG2-069
6.2 MW1.6%$132,648
AG2-077
11.7 MW3.0%$251,231
AG2-088
15.4 MW3.9%$330,472
AG2-151
21.6 MW5.5%$463,849
AG2-171
8.1 MW2.1%$174,584
AG2-188
27.6 MW7.0%$590,858
AG2-198
9.6 MW2.4%$205,457
AG2-213
7.4 MW1.9%$158,676
AG2-270
14.4 MW3.7%$307,832
AG2-338
2.8 MW0.7%$60,203
AG2-339
7.0 MW1.8%$150,486
AG2-369
0.8 MW0.2%$18,202
AG2-428
7.8 MW2.0%$167,787
AG2-436
28.3 MW7.2%$606,981
AG2-440
10.2 MW2.6%$219,200
AG2-441
12.8 MW3.3%$274,000
AG2-442
14.3 MW3.6%$306,867
AG2-566
5.9 MW1.5%$127,223
AG2-570
6.9 MW1.8%$147,956
AG2-571
2.8 MW0.7%$59,174
AG2-581
7.5 MW1.9%$160,048
AG2-583
23.2 MW5.9%$497,767
AH1-056
13.4 MW3.4%$288,322
AH1-217
11.3 MW2.9%$243,062
AH1-241
21.6 MW5.5%$463,849
AH1-377
20.2 MW5.1%$432,590
AH1-439
16.3 MW4.2%$350,111
AH1-528
13.7 MW3.5%$293,960
AH1-546
18.7 MW4.8%$400,409
AH1-687
20.7 MW5.3%$443,160

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0013
Title
Wreck and rebuild 1.51 miles of 230 kV Line 2027 (future Line 2323) between Cartersville and AG2-583 with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Description
Wreck and rebuild 1.51 miles of 230 kV Line 2027 (future Line 2323) between Cartersville and AG2-583 with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Total Cost ($USD)
$5,738,000
Allocated Cost ($USD)
$441,734
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-077
11.7 MW3.9%$221,076
AG2-151
23.3 MW7.7%$441,734
AG2-188
28.1 MW9.3%$532,875
AG2-198
8.4 MW2.8%$159,974
AG2-270
9.5 MW3.2%$180,916
AG2-440
8.6 MW2.9%$163,841
AG2-441
10.8 MW3.6%$204,796
AG2-442
12.1 MW4.0%$229,377
AG2-566
2.1 MW0.7%$39,989
AG2-581
8.9 MW2.9%$169,090
AG2-583
37.5 MW12.4%$710,342
AH1-056
12.0 MW4.0%$227,974
AH1-217
12.4 MW4.1%$235,309
AH1-241
23.3 MW7.7%$441,734
AH1-377
16.9 MW5.6%$320,934
AH1-439
16.8 MW5.5%$318,262
AH1-528
17.8 MW5.9%$338,162
AH1-546
20.0 MW6.6%$379,193
AH1-687
22.3 MW7.4%$422,422

System Reinforcement: n9198.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9198.0 / TC1-PH2-DOM-003-TC2
Title
Replace Circuit Breaker 219322 and Circuit Breaker Lead at Bremo 230 kV (Bremo - Fork Union).
Description
Replace Circuit Breaker 219322 and Circuit Breaker Lead at Bremo 230 kV (Bremo - Fork Union).
Total Cost ($USD)
$2,113,879
Allocated Cost ($USD)
$74,401
Time Estimate
40 to 41 Months

Contributor

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
5.5 MW0.7%$14,813
AG2-069
8.3 MW1.1%$22,223
AG2-077
20.7 MW2.6%$55,670
AG2-088
33.4 MW4.2%$89,747
AG2-151
27.7 MW3.5%$74,401
AG2-171
17.4 MW2.2%$46,851
AG2-188
59.1 MW7.5%$159,015
AG2-198
20.5 MW2.6%$55,218
AG2-213
17.6 MW2.2%$47,443
AG2-270
30.6 MW3.9%$82,279
AG2-338
6.0 MW0.8%$16,245
AG2-339
15.1 MW1.9%$40,615
AG2-369
4.1 MW0.5%$10,993
AG2-428
17.0 MW2.2%$45,705
AG2-436
60.8 MW7.7%$163,599
AG2-440
20.9 MW2.7%$56,176
AG2-441
26.1 MW3.3%$70,215
AG2-442
30.6 MW3.9%$82,225
AG2-566
12.7 MW1.6%$34,201
AG2-570
14.8 MW1.9%$39,732
AG2-571
5.9 MW0.8%$15,890
AG2-581
16.0 MW2.0%$43,020
AG2-583
49.9 MW6.3%$134,134
AH1-056
28.8 MW3.7%$77,366
AH1-241
27.7 MW3.5%$74,401
AH1-377
43.2 MW5.5%$116,216
AH1-408
16.7 MW2.1%$44,930
AH1-439
35.0 MW4.5%$94,235
AH1-528
29.4 MW3.7%$79,147
AH1-546
40.1 MW5.1%$107,827
AH1-687
44.4 MW5.6%$119,347

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0014
Title
Wreck and rebuild 0.17 miles of 230 kV Line 2027 between Midlothian and Powhatan with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Description
Wreck and rebuild 0.17 miles of 230 kV Line 2027 between Midlothian and Powhatan with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Total Cost ($USD)
$646,000
Allocated Cost ($USD)
$49,788
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-077
11.6 MW3.8%$24,815
AG2-151
23.3 MW7.7%$49,788
AG2-188
28.1 MW9.3%$60,040
AG2-198
8.4 MW2.8%$18,000
AG2-270
9.5 MW3.1%$20,299
AG2-440
8.6 MW2.9%$18,423
AG2-441
10.8 MW3.6%$23,029
AG2-442
12.1 MW4.0%$25,792
AG2-566
2.1 MW0.7%$4,501
AG2-581
8.9 MW2.9%$18,982
AG2-583
37.4 MW12.4%$80,094
AH1-056
12.0 MW4.0%$25,651
AH1-217
12.4 MW4.1%$26,520
AH1-241
23.3 MW7.7%$49,788
AH1-377
16.9 MW5.6%$36,094
AH1-439
16.8 MW5.6%$35,863
AH1-528
17.7 MW5.9%$37,959
AH1-546
20.0 MW6.6%$42,742
AH1-687
22.3 MW7.4%$47,619

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-1032
Title
Wreck and rebuild 0.73 miles of 230 kV line 235 between AG1-098 and Finneywood with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C
Description
Wreck and rebuild 0.73 miles of 230 kV line 235 between AG1-098 and Finneywood with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C
Total Cost ($USD)
$2,774,000
Allocated Cost ($USD)
$44,900
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6FINNEYWOOD-AG1-098 TP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-077
36.3 MW4.2%$116,992
AG2-151
13.9 MW1.6%$44,900
AG2-171
15.4 MW1.8%$49,715
AG2-188
89.0 MW10.3%$286,703
AG2-198
55.1 MW6.4%$177,623
AG2-213
20.6 MW2.4%$66,284
AG2-270
29.4 MW3.4%$94,621
AG2-440
31.5 MW3.7%$101,480
AG2-441
39.4 MW4.6%$126,851
AG2-442
44.1 MW5.1%$142,074
AG2-566
26.1 MW3.0%$84,275
AG2-581
27.9 MW3.2%$89,790
AG2-583
14.3 MW1.7%$46,105
AH1-056
40.7 MW4.7%$131,257
AH1-215
7.9 MW0.9%$25,594
AH1-217
7.5 MW0.9%$24,240
AH1-241
13.2 MW1.5%$42,628
AH1-280
7.4 MW0.9%$23,805
AH1-377
131.2 MW15.2%$422,936
AH1-439
54.0 MW6.3%$174,068
AH1-528
55.7 MW6.5%$179,576
AH1-546
50.7 MW5.9%$163,420
AH1-676
39.2 MW4.6%$126,371
AH1-687
10.1 MW1.2%$32,691

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2043
Title
Wreck and rebuild 0.93 miles of 230 kV Line 2241 between Hendrick and Persons with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Dominion portion of line only.
Description
Wreck and rebuild 0.93 miles of 230 kV Line 2241 between Hendrick and Persons with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Dominion portion of line only.
Total Cost ($USD)
$3,534,000
Allocated Cost ($USD)
$31,260
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
9.2 MW1.1%$39,652
AG2-069
13.8 MW1.7%$59,477
AG2-077
67.9 MW8.3%$292,796
AG2-111
3.5 MW0.4%$15,101
AG2-112
3.7 MW0.4%$15,830
AG2-151
7.2 MW0.9%$31,260
AG2-152
14.7 MW1.8%$63,434
AG2-171
13.1 MW1.6%$56,405
AG2-188
21.4 MW2.6%$92,359
AG2-198
19.5 MW2.4%$83,993
AG2-213
17.4 MW2.1%$75,209
AG2-270
47.1 MW5.8%$203,423
AG2-272
5.3 MW0.7%$23,062
AG2-341
6.5 MW0.8%$27,834
AG2-369
7.9 MW1.0%$34,099
AG2-440
21.4 MW2.6%$92,165
AG2-441
26.7 MW3.3%$115,205
AG2-442
29.9 MW3.7%$129,034
AG2-522
10.0 MW1.2%$43,134
AG2-541
19.1 MW2.3%$82,250
AG2-566
9.3 MW1.1%$39,936
AG2-570
35.7 MW4.4%$154,059
AG2-571
15.5 MW1.9%$67,037
AG2-581
50.2 MW6.1%$216,526
AG2-583
7.5 MW0.9%$32,494
AG2-659
11.3 MW1.4%$48,915
AH1-056
20.7 MW2.5%$89,249
AH1-215
8.7 MW1.1%$37,455
AH1-241
6.9 MW0.8%$29,676
AH1-314
15.6 MW1.9%$67,343
AH1-343
22.0 MW2.7%$94,896
AH1-377
48.3 MW5.9%$208,557
AH1-408
10.5 MW1.3%$45,498
AH1-439
12.3 MW1.5%$53,152
AH1-528
100.6 MW12.3%$434,213
AH1-535
6.0 MW0.7%$25,767
AH1-546
7.3 MW0.9%$31,579
AH1-687
5.2 MW0.6%$22,479
AH1-690
28.7 MW3.5%$123,688
AH1-721
31.5 MW3.8%$135,756

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2069
Title
Replace 2-1590 AAC line lead on line 2028 at Fork Union 230 kV
Description
Replace 2-1590 AAC line lead on line 2028 at Fork Union 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$29,526
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6GRAPEVINE-6FORK UNION 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
5.4 MW1.1%$5,636
AG2-069
8.1 MW1.7%$8,454
AG2-077
15.4 MW3.2%$16,005
AG2-088
15.4 MW3.2%$15,999
AG2-151
28.4 MW5.9%$29,526
AG2-188
34.2 MW7.1%$35,506
AG2-198
12.6 MW2.6%$13,084
AG2-213
9.7 MW2.0%$10,104
AG2-270
14.4 MW3.0%$14,911
AG2-338
2.8 MW0.6%$2,916
AG2-339
7.0 MW1.5%$7,289
AG2-369
2.0 MW0.4%$2,042
AG2-428
9.1 MW1.9%$9,472
AG2-436
28.3 MW5.9%$29,388
AG2-440
13.4 MW2.8%$13,958
AG2-441
16.8 MW3.5%$17,448
AG2-442
18.8 MW3.9%$19,541
AG2-566
5.9 MW1.2%$6,162
AG2-570
21.8 MW4.5%$22,634
AG2-571
2.8 MW0.6%$2,865
AG2-581
9.8 MW2.0%$10,199
AG2-583
30.5 MW6.3%$31,692
AH1-056
15.5 MW3.2%$16,081
AH1-217
14.9 MW3.1%$15,470
AH1-241
27.0 MW5.6%$28,031
AH1-377
26.5 MW5.5%$27,548
AH1-439
21.5 MW4.5%$22,291
AH1-528
18.1 MW3.8%$18,786
AH1-546
24.6 MW5.1%$25,534
AH1-687
20.6 MW4.3%$21,427

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2073
Title
Replace 2-1590 line lead on line 2028 at Charlottesville and Mt Eagle 230 kV
Description
Replace 2-1590 line lead on line 2028 at Charlottesville and Mt Eagle 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$29,035
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
5.4 MW1.1%$5,542
AG2-069
8.1 MW1.7%$8,314
AG2-077
15.4 MW3.1%$15,739
AG2-088
15.4 MW3.1%$15,733
AG2-151
28.4 MW5.8%$29,035
AG2-171
8.1 MW1.7%$8,316
AG2-188
34.2 MW7.0%$34,915
AG2-198
12.6 MW2.6%$12,866
AG2-213
9.7 MW2.0%$9,936
AG2-270
14.4 MW2.9%$14,663
AG2-338
2.8 MW0.6%$2,868
AG2-339
7.0 MW1.4%$7,168
AG2-369
2.0 MW0.4%$2,008
AG2-428
9.1 MW1.9%$9,314
AG2-436
28.3 MW5.8%$28,899
AG2-440
13.4 MW2.7%$13,726
AG2-441
16.8 MW3.4%$17,157
AG2-442
18.8 MW3.8%$19,216
AG2-566
5.9 MW1.2%$6,060
AG2-570
21.8 MW4.5%$22,257
AG2-571
2.8 MW0.6%$2,818
AG2-581
9.8 MW2.0%$10,029
AG2-583
30.5 MW6.2%$31,165
AH1-056
15.5 MW3.2%$15,813
AH1-217
14.9 MW3.0%$15,213
AH1-241
27.0 MW5.5%$27,565
AH1-377
26.5 MW5.4%$27,090
AH1-439
21.5 MW4.4%$21,920
AH1-528
18.1 MW3.7%$18,474
AH1-546
24.6 MW5.0%$25,110
AH1-687
20.6 MW4.2%$21,071

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2071
Title
Replace 2-1590 line lead on line 2028 at Mt. Eagle 230 kV
Description
Replace 2-1590 line lead on line 2028 at Mt. Eagle 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$29,035
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
5.4 MW1.1%$5,542
AG2-069
8.1 MW1.7%$8,314
AG2-077
15.4 MW3.1%$15,739
AG2-088
15.4 MW3.1%$15,733
AG2-151
28.4 MW5.8%$29,035
AG2-171
8.1 MW1.7%$8,316
AG2-188
34.2 MW7.0%$34,915
AG2-198
12.6 MW2.6%$12,866
AG2-213
9.7 MW2.0%$9,936
AG2-270
14.4 MW2.9%$14,663
AG2-338
2.8 MW0.6%$2,868
AG2-339
7.0 MW1.4%$7,168
AG2-369
2.0 MW0.4%$2,008
AG2-428
9.1 MW1.9%$9,314
AG2-436
28.3 MW5.8%$28,899
AG2-440
13.4 MW2.7%$13,726
AG2-441
16.8 MW3.4%$17,157
AG2-442
18.8 MW3.8%$19,216
AG2-566
5.9 MW1.2%$6,060
AG2-570
21.8 MW4.5%$22,257
AG2-571
2.8 MW0.6%$2,818
AG2-581
9.8 MW2.0%$10,029
AG2-583
30.5 MW6.2%$31,165
AH1-056
15.5 MW3.2%$15,813
AH1-217
14.9 MW3.0%$15,213
AH1-241
27.0 MW5.5%$27,565
AH1-377
26.5 MW5.4%$27,090
AH1-439
21.5 MW4.4%$21,920
AH1-528
18.1 MW3.7%$18,474
AH1-546
24.6 MW5.0%$25,110
AH1-687
20.6 MW4.2%$21,071

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2065
Title
Replace switches 219324 and 219325 at Bremo 230 kV
Description
Replace switches 219324 and 219325 at Bremo 230 kV
Total Cost ($USD)
$800,000
Allocated Cost ($USD)
$28,157
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
2.8 MW0.7%$5,606
AG2-069
4.1 MW1.1%$8,410
AG2-077
10.3 MW2.6%$21,068
AG2-088
16.7 MW4.2%$33,965
AG2-151
13.8 MW3.5%$28,157
AG2-171
8.7 MW2.2%$17,731
AG2-188
29.6 MW7.5%$60,179
AG2-198
10.3 MW2.6%$20,897
AG2-213
8.8 MW2.2%$17,955
AG2-270
15.3 MW3.9%$31,138
AG2-338
3.0 MW0.8%$6,148
AG2-339
7.5 MW1.9%$15,371
AG2-369
2.0 MW0.5%$4,160
AG2-428
8.5 MW2.2%$17,297
AG2-436
30.4 MW7.7%$61,914
AG2-440
10.4 MW2.7%$21,260
AG2-441
13.0 MW3.3%$26,573
AG2-442
15.3 MW3.9%$31,118
AG2-566
6.4 MW1.6%$12,943
AG2-570
7.4 MW1.9%$15,037
AG2-571
3.0 MW0.8%$6,013
AG2-581
8.0 MW2.0%$16,281
AG2-583
24.9 MW6.3%$50,763
AH1-056
14.4 MW3.7%$29,279
AH1-241
13.8 MW3.5%$28,157
AH1-377
21.6 MW5.5%$43,982
AH1-408
8.3 MW2.1%$17,004
AH1-439
17.5 MW4.5%$35,663
AH1-528
14.7 MW3.7%$29,953
AH1-546
20.0 MW5.1%$40,807
AH1-687
22.2 MW5.6%$45,167

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2072
Title
Replace 2500 ACAR line lead on line 2028 at Charlottesville 230 kV
Description
Replace 2500 ACAR line lead on line 2028 at Charlottesville 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$27,560
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.1 MW1.1%$5,253
AG2-069
6.2 MW1.6%$7,881
AG2-077
11.7 MW3.0%$14,927
AG2-088
15.4 MW3.9%$19,635
AG2-151
21.6 MW5.5%$27,560
AG2-171
8.1 MW2.1%$10,373
AG2-188
27.6 MW7.0%$35,106
AG2-198
9.6 MW2.4%$12,207
AG2-213
7.4 MW1.9%$9,428
AG2-270
14.4 MW3.7%$18,290
AG2-338
2.8 MW0.7%$3,577
AG2-339
7.0 MW1.8%$8,941
AG2-369
0.8 MW0.2%$1,081
AG2-428
7.8 MW2.0%$9,969
AG2-436
28.3 MW7.2%$36,064
AG2-440
10.2 MW2.6%$13,024
AG2-441
12.8 MW3.3%$16,280
AG2-442
14.3 MW3.6%$18,233
AG2-566
5.9 MW1.5%$7,559
AG2-570
6.9 MW1.8%$8,791
AG2-571
2.8 MW0.7%$3,516
AG2-581
7.5 MW1.9%$9,509
AG2-583
23.2 MW5.9%$29,575
AH1-056
13.4 MW3.4%$17,131
AH1-217
11.3 MW2.9%$14,442
AH1-241
21.6 MW5.5%$27,560
AH1-377
20.2 MW5.1%$25,702
AH1-439
16.3 MW4.2%$20,802
AH1-528
13.7 MW3.5%$17,466
AH1-546
18.7 MW4.8%$23,790
AH1-687
20.7 MW5.3%$26,330

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2068
Title
Wreck and rebuild 0.12 miles of 230 kV line 2028 between Fork Union and Grape Vine with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Description
Wreck and rebuild 0.12 miles of 230 kV line 2028 between Fork Union and Grape Vine with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Total Cost ($USD)
$456,000
Allocated Cost ($USD)
$25,667
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6GRAPEVINE-6FORK UNION 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.1 MW1.1%$4,893
AG2-069
6.2 MW1.6%$7,340
AG2-077
11.7 MW3.0%$13,902
AG2-088
15.4 MW4.0%$18,287
AG2-151
21.6 MW5.6%$25,667
AG2-188
27.6 MW7.2%$32,695
AG2-198
9.6 MW2.5%$11,369
AG2-213
7.4 MW1.9%$8,780
AG2-270
14.4 MW3.7%$17,034
AG2-338
2.8 MW0.7%$3,331
AG2-339
7.0 MW1.8%$8,327
AG2-369
0.8 MW0.2%$1,007
AG2-428
7.8 MW2.0%$9,284
AG2-436
28.3 MW7.4%$33,587
AG2-440
10.2 MW2.7%$12,129
AG2-441
12.8 MW3.3%$15,162
AG2-442
14.3 MW3.7%$16,980
AG2-566
5.9 MW1.5%$7,040
AG2-570
6.9 MW1.8%$8,187
AG2-571
2.8 MW0.7%$3,274
AG2-581
7.5 MW1.9%$8,856
AG2-583
23.2 MW6.0%$27,544
AH1-056
13.4 MW3.5%$15,954
AH1-217
11.3 MW2.9%$13,450
AH1-241
21.6 MW5.6%$25,667
AH1-377
20.2 MW5.2%$23,937
AH1-439
16.3 MW4.2%$19,373
AH1-528
13.7 MW3.6%$16,266
AH1-546
18.7 MW4.9%$22,156
AH1-687
20.7 MW5.4%$24,522

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2070
Title
Replace wave trap 2028WT at Fork Union 230 kV
Description
Replace wave trap 2028WT at Fork Union 230 kV
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$22,515
Time Estimate
16 to 18 Months

Contributor

FacilityContingency
6GRAPEVINE-6FORK UNION 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.1 MW1.1%$4,292
AG2-069
6.2 MW1.6%$6,439
AG2-077
11.7 MW3.0%$12,195
AG2-088
15.4 MW4.0%$16,041
AG2-151
21.6 MW5.6%$22,515
AG2-188
27.6 MW7.2%$28,680
AG2-198
9.6 MW2.5%$9,973
AG2-213
7.4 MW1.9%$7,702
AG2-270
14.4 MW3.7%$14,942
AG2-338
2.8 MW0.7%$2,922
AG2-339
7.0 MW1.8%$7,304
AG2-369
0.8 MW0.2%$884
AG2-428
7.8 MW2.0%$8,144
AG2-436
28.3 MW7.4%$29,462
AG2-440
10.2 MW2.7%$10,640
AG2-441
12.8 MW3.3%$13,300
AG2-442
14.3 MW3.7%$14,895
AG2-566
5.9 MW1.5%$6,175
AG2-570
6.9 MW1.8%$7,182
AG2-571
2.8 MW0.7%$2,872
AG2-581
7.5 MW1.9%$7,769
AG2-583
23.2 MW6.0%$24,161
AH1-056
13.4 MW3.5%$13,995
AH1-217
11.3 MW2.9%$11,798
AH1-241
21.6 MW5.6%$22,515
AH1-377
20.2 MW5.2%$20,997
AH1-439
16.3 MW4.2%$16,994
AH1-528
13.7 MW3.6%$14,269
AH1-546
18.7 MW4.9%$19,435
AH1-687
20.7 MW5.4%$21,511

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH3-DOM-007
Title
Replace Wave Trap 2028WT at Charlottesville
Description
Replace Wave Trap 2028WT at Charlottesville
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$22,048
Time Estimate
16 to 18 Months

Contributor

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.1 MW1.1%$4,203
AG2-069
6.2 MW1.6%$6,305
AG2-077
11.7 MW3.0%$11,942
AG2-088
15.4 MW3.9%$15,708
AG2-151
21.6 MW5.5%$22,048
AG2-171
8.1 MW2.1%$8,298
AG2-188
27.6 MW7.0%$28,085
AG2-198
9.6 MW2.4%$9,766
AG2-213
7.4 MW1.9%$7,542
AG2-270
14.4 MW3.7%$14,632
AG2-338
2.8 MW0.7%$2,862
AG2-339
7.0 MW1.8%$7,153
AG2-369
0.8 MW0.2%$865
AG2-428
7.8 MW2.0%$7,975
AG2-436
28.3 MW7.2%$28,851
AG2-440
10.2 MW2.6%$10,419
AG2-441
12.8 MW3.3%$13,024
AG2-442
14.3 MW3.6%$14,586
AG2-566
5.9 MW1.5%$6,047
AG2-570
6.9 MW1.8%$7,033
AG2-571
2.8 MW0.7%$2,813
AG2-581
7.5 MW1.9%$7,607
AG2-583
23.2 MW5.9%$23,660
AH1-056
13.4 MW3.4%$13,705
AH1-217
11.3 MW2.9%$11,553
AH1-241
21.6 MW5.5%$22,048
AH1-377
20.2 MW5.1%$20,562
AH1-439
16.3 MW4.2%$16,641
AH1-528
13.7 MW3.5%$13,973
AH1-546
18.7 MW4.8%$19,032
AH1-687
20.7 MW5.3%$21,064

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2066
Title
Replace 2-636 ACSR line lead on line 2193 at Bremo 230 kV
Description
Replace 2-636 ACSR line lead on line 2193 at Bremo 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$14,838
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
2.8 MW0.6%$2,954
AG2-069
4.1 MW0.9%$4,432
AG2-077
10.3 MW2.2%$11,102
AG2-088
16.7 MW3.6%$17,891
AG2-151
13.8 MW3.0%$14,838
AG2-171
8.7 MW1.9%$9,343
AG2-188
36.7 MW7.9%$39,350
AG2-198
13.5 MW2.9%$14,479
AG2-213
11.6 MW2.5%$12,458
AG2-270
15.3 MW3.3%$16,409
AG2-338
3.0 MW0.6%$3,240
AG2-339
7.5 MW1.6%$8,100
AG2-369
2.0 MW0.4%$2,192
AG2-428
9.9 MW2.1%$10,624
AG2-436
30.4 MW6.5%$32,614
AG2-440
11.3 MW2.4%$12,126
AG2-441
14.1 MW3.0%$15,157
AG2-442
20.1 MW4.3%$21,562
AG2-566
6.4 MW1.4%$6,821
AG2-570
23.3 MW5.0%$25,024
AG2-571
3.0 MW0.6%$3,168
AG2-581
10.5 MW2.3%$11,289
AG2-583
32.8 MW7.0%$35,169
AH1-056
16.6 MW3.6%$17,769
AH1-241
13.8 MW3.0%$14,838
AH1-377
28.4 MW6.1%$30,476
AH1-408
8.3 MW1.8%$8,960
AH1-439
23.0 MW4.9%$24,707
AH1-528
19.4 MW4.2%$20,828
AH1-546
26.4 MW5.7%$28,317
AH1-687
22.1 MW4.8%$23,765

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2067
Title
Replace 3 1/2" pipe line lead on line 2193 at Bremo 230 kV
Description
Replace 3 1/2" pipe line lead on line 2193 at Bremo 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$14,838
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
2.8 MW0.6%$2,954
AG2-069
4.1 MW0.9%$4,432
AG2-077
10.3 MW2.2%$11,102
AG2-088
16.7 MW3.6%$17,891
AG2-151
13.8 MW3.0%$14,838
AG2-171
8.7 MW1.9%$9,343
AG2-188
36.7 MW7.9%$39,350
AG2-198
13.5 MW2.9%$14,479
AG2-213
11.6 MW2.5%$12,458
AG2-270
15.3 MW3.3%$16,409
AG2-338
3.0 MW0.6%$3,240
AG2-339
7.5 MW1.6%$8,100
AG2-369
2.0 MW0.4%$2,192
AG2-428
9.9 MW2.1%$10,624
AG2-436
30.4 MW6.5%$32,614
AG2-440
11.3 MW2.4%$12,126
AG2-441
14.1 MW3.0%$15,157
AG2-442
20.1 MW4.3%$21,562
AG2-566
6.4 MW1.4%$6,821
AG2-570
23.3 MW5.0%$25,024
AG2-571
3.0 MW0.6%$3,168
AG2-581
10.5 MW2.3%$11,289
AG2-583
32.8 MW7.0%$35,169
AH1-056
16.6 MW3.6%$17,769
AH1-241
13.8 MW3.0%$14,838
AH1-377
28.4 MW6.1%$30,476
AH1-408
8.3 MW1.8%$8,960
AH1-439
23.0 MW4.9%$24,707
AH1-528
19.4 MW4.2%$20,828
AH1-546
26.4 MW5.7%$28,317
AH1-687
22.1 MW4.8%$23,765

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2064
Title
Replace 2-1590 line lead on line 2193 at Fork Union 230 kV
Description
Replace 2-1590 line lead on line 2193 at Fork Union 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$14,838
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
2.8 MW0.6%$2,954
AG2-069
4.1 MW0.9%$4,432
AG2-077
10.3 MW2.2%$11,102
AG2-088
16.7 MW3.6%$17,891
AG2-151
13.8 MW3.0%$14,838
AG2-171
8.7 MW1.9%$9,343
AG2-188
36.7 MW7.9%$39,350
AG2-198
13.5 MW2.9%$14,479
AG2-213
11.6 MW2.5%$12,458
AG2-270
15.3 MW3.3%$16,409
AG2-338
3.0 MW0.6%$3,240
AG2-339
7.5 MW1.6%$8,100
AG2-369
2.0 MW0.4%$2,192
AG2-428
9.9 MW2.1%$10,624
AG2-436
30.4 MW6.5%$32,614
AG2-440
11.3 MW2.4%$12,126
AG2-441
14.1 MW3.0%$15,157
AG2-442
20.1 MW4.3%$21,562
AG2-566
6.4 MW1.4%$6,821
AG2-570
23.3 MW5.0%$25,024
AG2-571
3.0 MW0.6%$3,168
AG2-581
10.5 MW2.3%$11,289
AG2-583
32.8 MW7.0%$35,169
AH1-056
16.6 MW3.6%$17,769
AH1-241
13.8 MW3.0%$14,838
AH1-377
28.4 MW6.1%$30,476
AH1-408
8.3 MW1.8%$8,960
AH1-439
23.0 MW4.9%$24,707
AH1-528
19.4 MW4.2%$20,828
AH1-546
26.4 MW5.7%$28,317
AH1-687
22.1 MW4.8%$23,765

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2063
Title
Wreck and rebuild 0.11 miles of 230 kV line 2193 between Fork Union and Bremo Dist with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Description
Wreck and rebuild 0.11 miles of 230 kV line 2193 between Fork Union and Bremo Dist with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Total Cost ($USD)
$418,000
Allocated Cost ($USD)
$14,712
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
2.8 MW0.7%$2,929
AG2-069
4.1 MW1.1%$4,394
AG2-077
10.3 MW2.6%$11,008
AG2-088
16.7 MW4.2%$17,747
AG2-151
13.8 MW3.5%$14,712
AG2-171
8.7 MW2.2%$9,264
AG2-188
29.6 MW7.5%$31,444
AG2-198
10.3 MW2.6%$10,919
AG2-213
8.8 MW2.2%$9,381
AG2-270
15.3 MW3.9%$16,270
AG2-338
3.0 MW0.8%$3,212
AG2-339
7.5 MW1.9%$8,031
AG2-369
2.0 MW0.5%$2,174
AG2-428
8.5 MW2.2%$9,038
AG2-436
30.4 MW7.7%$32,350
AG2-440
10.4 MW2.7%$11,108
AG2-441
13.0 MW3.3%$13,884
AG2-442
15.3 MW3.9%$16,259
AG2-566
6.4 MW1.6%$6,763
AG2-570
7.4 MW1.9%$7,857
AG2-571
3.0 MW0.8%$3,142
AG2-581
8.0 MW2.0%$8,507
AG2-583
24.9 MW6.3%$26,524
AH1-056
14.4 MW3.7%$15,298
AH1-241
13.8 MW3.5%$14,712
AH1-377
21.6 MW5.5%$22,981
AH1-408
8.3 MW2.1%$8,885
AH1-439
17.5 MW4.5%$18,634
AH1-528
14.7 MW3.7%$15,651
AH1-546
20.0 MW5.1%$21,322
AH1-687
22.2 MW5.6%$23,600

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0080
Title
Replace switch 219326 at Bremo 230 kV
Description
Replace switch 219326 at Bremo 230 kV
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$14,079
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
2.8 MW0.7%$2,803
AG2-069
4.1 MW1.1%$4,205
AG2-077
10.3 MW2.6%$10,534
AG2-088
16.7 MW4.2%$16,982
AG2-151
13.8 MW3.5%$14,079
AG2-171
8.7 MW2.2%$8,865
AG2-188
29.6 MW7.5%$30,090
AG2-198
10.3 MW2.6%$10,449
AG2-213
8.8 MW2.2%$8,977
AG2-270
15.3 MW3.9%$15,569
AG2-338
3.0 MW0.8%$3,074
AG2-339
7.5 MW1.9%$7,685
AG2-369
2.0 MW0.5%$2,080
AG2-428
8.5 MW2.2%$8,649
AG2-436
30.4 MW7.7%$30,957
AG2-440
10.4 MW2.7%$10,630
AG2-441
13.0 MW3.3%$13,286
AG2-442
15.3 MW3.9%$15,559
AG2-566
6.4 MW1.6%$6,472
AG2-570
7.4 MW1.9%$7,518
AG2-571
3.0 MW0.8%$3,007
AG2-581
8.0 MW2.0%$8,140
AG2-583
24.9 MW6.3%$25,382
AH1-056
14.4 MW3.7%$14,640
AH1-241
13.8 MW3.5%$14,079
AH1-377
21.6 MW5.5%$21,991
AH1-408
8.3 MW2.1%$8,502
AH1-439
17.5 MW4.5%$17,832
AH1-528
14.7 MW3.7%$14,977
AH1-546
20.0 MW5.1%$20,404
AH1-687
22.2 MW5.6%$22,584

System Reinforcement: n9146.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9146.0 / TC1-PH1-DOM-004
Title
Wreck and rebuild 1.51 miles of 115 kV Line No. 5 between Bremo and Fork Union with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees Celsius. Replace line lead at Bremo.
Description
Wreck and rebuild 1.51 miles of 115 kV Line No. 5 between Bremo and Fork Union with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees Celsius. Replace line lead at Bremo.
Total Cost ($USD)
$7,535,533
Allocated Cost ($USD)
$0
Time Estimate
42 to 43 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 may need this upgrade in-service to be deliverable to the PJM system. If AG2-151 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
3FORK UNION-3BREMO 115.0 kV Ckt 2 line(Any)

System Reinforcement: b3800.300
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.300
Title
Wreck/Rebuild 230kV Line #2135 segment Hollymeade Junction – Cash’s Corner using double-circuit capable 230 kV poles. (The second 230kV circuit will be wired but not have terminal ends.)
Description
Wreck/Rebuild 230kV Line #2135 segment Hollymeade Junction – Cash’s Corner using double-circuit capable 230 kV poles. (The second 230kV circuit will be wired but not have terminal ends.)
Cost Information
Time Estimate
Jun 30 2028

Contingent

Note: Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 may need this upgrade in-service to be deliverable to the PJM system. If AG2-151 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6CASHSCORNER-6HOLLYMD 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.302
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.302
Title
Upgrade Cash's Corner switches 213576 and 213579 and line leads to 4000A continuous current rating of 230kV Line #2135.
Description
Upgrade Cash's Corner switches 213576 and 213579 and line leads to 4000A continuous current rating of 230kV Line #2135.
Cost Information
Time Estimate
Jun 30 2028

Contingent

Note: Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 may need this upgrade in-service to be deliverable to the PJM system. If AG2-151 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6CASHSCORNER-6HOLLYMD 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0027
Title
Wreck and rebuild 13.05 miles of 230 kV Line 2202 between Desper and South Anna with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 Degrees C.
Description
Wreck and rebuild 13.05 miles of 230 kV Line 2202 between Desper and South Anna with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 Degrees C.
Total Cost ($USD)
$49,590,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
6DESPER-6S ANNA 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0028
Title
Wreck and rebuild 0.63 miles of 230 kV Line 2202 between Desper and South Anna with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 Degrees C
Description
Wreck and rebuild 0.63 miles of 230 kV Line 2202 between Desper and South Anna with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 Degrees C
Total Cost ($USD)
$2,394,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
6DESPER-6S ANNA 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0029
Title
Replace Switch 220216 at South Anna 230 kV with a 4000A switch.
Description
Replace Switch 220216 at South Anna 230 kV with a 4000A switch.
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
6DESPER-6S ANNA 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0030
Title
Replace (2) 3-1/2" AL Pipe Line Leads on Line 2202 and Breaker Leads at South Anna 230 kV.
Description
Replace (2) 3-1/2" AL Pipe Line Leads on Line 2202 and Breaker Leads at South Anna 230 kV.
Total Cost ($USD)
$1,000,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
6DESPER-6S ANNA 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0031
Title
Replace 2-1590 AAC Line Lead on Line 2202 at Desper 230 kV.
Description
Replace 2-1590 AAC Line Lead on Line 2202 at Desper 230 kV.
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
6DESPER-6S ANNA 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0032
Title
Replace Wave Trap 2202WT at Desper 230 kV.
Description
Replace Wave Trap 2202WT at Desper 230 kV.
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$0
Time Estimate
16 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
6DESPER-6S ANNA 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0033
Title
Replace Wave Trap 2202WT at South Anna 230 kV.
Description
Replace Wave Trap 2202WT at South Anna 230 kV.
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$0
Time Estimate
16 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
6DESPER-6S ANNA 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0034
Title
Replace Breaker 2074T2202 at South Anna 230 kV.
Description
Replace Breaker 2074T2202 at South Anna 230 kV.
Total Cost ($USD)
$2,000,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
6DESPER-6S ANNA 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9199.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9199.0 / TC1-PH2-DOM-004
Title
Wreck and rebuild 1.63 miles of line 2193 between Fork Union and Bremo with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C and replace line lead at Bremo.
Description
Wreck and rebuild 1.63 miles of line 2193 between Fork Union and Bremo with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C and replace line lead at Bremo.
Total Cost ($USD)
$7,947,612
Allocated Cost ($USD)
$0
Time Estimate
42 to 43 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 may need this upgrade in-service to be deliverable to the PJM system. If AG2-151 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2004
Title
Replace 2-1590 AAC 61 line lead on line 2032 at Four Rivers 230 kV.
Description
Replace 2-1590 AAC 61 line lead on line 2032 at Four Rivers 230 kV.
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2005
Title
Wreck and rebuild 5.74 mi of 230 kV Line 230 between Four Rivers and Hanover with (2) 768.2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C
Description
Wreck and rebuild 5.74 mi of 230 kV Line 230 between Four Rivers and Hanover with (2) 768.2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C
Total Cost ($USD)
$21,812,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2095
Title
Wreck and rebuild 7.90 miles of 230 kV Line 2199 between Germanna and Cirrus with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 Deg. C.
Description
Wreck and rebuild 7.90 miles of 230 kV Line 2199 between Germanna and Cirrus with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 Deg. C.
Total Cost ($USD)
$30,020,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
6GERMANNA-6CIRRUS 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0018
Title
Replace 2-795 AAC line lead on Line 2074 at Lousia CT 230 kV.
Description
Replace 2-795 AAC line lead on Line 2074 at Lousia CT 230 kV.
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
6LOISACT-6S ANNA 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0019
Title
Wreck and rebuild 0.4 miles of 230 kV Line 2074 between Louisa CT and South Anna with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 0.4 miles of 230 kV Line 2074 between Louisa CT and South Anna with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$1,520,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
6LOISACT-6S ANNA 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0020
Title
Wreck and rebuild 0.63 miles of 230 kV Line 2074 between Louisa CT and South Anna with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 0.63 miles of 230 kV Line 2074 between Louisa CT and South Anna with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$2,394,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
6LOISACT-6S ANNA 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2052
Title
Wreck and rebuild 0.74 miles of 230 kV Line 2304 between Desper and Louisa Pumping Station with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 Deg. C
Description
Wreck and rebuild 0.74 miles of 230 kV Line 2304 between Desper and Louisa Pumping Station with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 Deg. C
Total Cost ($USD)
$2,812,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
6LOUISA PUMP-6DESPER 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2054
Title
Replace 2-1590 AAC 61 line lead on Line 2304 at Desper 230 kV
Description
Replace 2-1590 AAC 61 line lead on Line 2304 at Desper 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
6LOUISA PUMP-6DESPER 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2053
Title
Replace MAINLINE JUMPER 1590 ACSR (45/7) @150 Deg. C with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 Deg. C
Description
Replace MAINLINE JUMPER 1590 ACSR (45/7) @150 Deg. C with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 Deg. C
Total Cost ($USD)
$10,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
6LOUISA PUMP-6DESPER 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2055
Title
Replace wavetrap 255WT at Desper 230 kV
Description
Replace wavetrap 255WT at Desper 230 kV
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$0
Time Estimate
16 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
6LOUISA PUMP-6DESPER 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2056
Title
Replace switch 25599 at Louisa Pumping 230 kV
Description
Replace switch 25599 at Louisa Pumping 230 kV
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
6LOUISA PUMP-6DESPER 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2057
Title
Wreck and rebuild 0.25 miles of 230 kV Line 2304 between Louisa Pumping Station and Louisa with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 Deg. C
Description
Wreck and rebuild 0.25 miles of 230 kV Line 2304 between Louisa Pumping Station and Louisa with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 Deg. C
Total Cost ($USD)
$950,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2058
Title
Replace MAINLINE JUMPER 1590 ACSR (45/7) @150 Deg. C with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 Deg. C
Description
Replace MAINLINE JUMPER 1590 ACSR (45/7) @150 Deg. C with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 Deg. C
Total Cost ($USD)
$10,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
6LOUISA PUMP-6LOUISA 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2059
Title
Wreck and rebuild 7.57 miles of 230 kV Line 2304 between Louisa and AH1-012 with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 Deg. C
Description
Wreck and rebuild 7.57 miles of 230 kV Line 2304 between Louisa and AH1-012 with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 Deg. C
Total Cost ($USD)
$28,766,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
6LOUISA-AH1-012 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9379.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9379.0 / TC1-PH3-DOM-011
Title
Replace existing 230/500 kV Transformer 1 at Midlothian with (4)-480 MVA Single Phase transformers.
Description
Replace existing 230/500 kV Transformer 1 at Midlothian with (4)-480 MVA Single Phase 500/230 kV transformers.
Total Cost ($USD)
$37,836,293
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2029

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending)
Title
Dominion work to accomodate new Person - Hendrick 230 kV tie line
Description
Add a breaker to existing three-breaker ring bus at Hendrick and construct 0.93 miles of new 230 kV line between Pesrons - Hendrick
Total Cost ($USD)
$8,894,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 may need this upgrade in-service to be deliverable to the PJM system. If AG2-151 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0045
Title
Wreck and rebuild 8.3 miles of 230 kV Line 2250 between Edmonson and Sedge Hill with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 8.3 miles of 230 kV Line 2250 between Edmonson and Sedge Hill with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$31,540,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)

System Reinforcement: n6215
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n6215
Title
Wreck and rebuild 18.56 miles of 230 kV Line 296 between Sedge Hill and Alton Post (AC1-221) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 18.56 miles of 230 kV Line 296 between Sedge Hill and Alton Post (AC1-221) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$70,528,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0051
Title
Wreck and rebuild 0.003 miles of 230 kV Line 296 between Sedge Hill and Alton Post (AC1-221) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 0.003 miles of 230 kV Line 296 between Sedge Hill and Alton Post (AC1-221) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$11,400
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2061
Title
Wreck and rebuild 0.82 miles of 230 kV Line 255 between Southall and North Anna with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 Deg. C
Description
Wreck and rebuild 0.82 miles of 230 kV Line 255 between Southall and North Anna with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 Deg. C
Total Cost ($USD)
$3,116,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2062
Title
Replace 2-1590 AAC line lead on line 255 at North Anna 230 kV
Description
Replace 2-1590 AAC line lead on line 255 at North Anna 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
6SOUTH HALL-6NO ANNA 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2060
Title
Wreck and rebuild 7.83 miles of 230 kV Line 2304 between AH1-012 and Southall with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 Deg. C
Description
Wreck and rebuild 7.83 miles of 230 kV Line 2304 between AH1-012 and Southall with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 Deg. C
Total Cost ($USD)
$29,754,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
6SOUTH HALL-AH1-012 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 may need this upgrade in-service to be deliverable to the PJM system. If AG2-151 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6KYSER-6LUCKYHILL 230.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6LUCKYHILL-6REMNGTN 230.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Contingent

Note: Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 may need this upgrade in-service to be deliverable to the PJM system. If AG2-151 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6LUCKYHILL-6REMNGTN 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6KYSER-6LUCKYHILL 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Contingent

Note: Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 may need this upgrade in-service to be deliverable to the PJM system. If AG2-151 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6LUCKYHILL-6REMNGTN 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6KYSER-6LUCKYHILL 230.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.355
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 may need this upgrade in-service to be deliverable to the PJM system. If AG2-151 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6LUCKYHILL-6REMNGTN 230.0 kV Ckt 1 line(Any)
6KYSER-6LUCKYHILL 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2097
Title
Build a new 11.95 mile line from Aspen 230 kV to Dickerson 230 kV with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 degrees C.
Description
Build a new 11.95 mile line from Aspen 230 kV to Dickerson 230 kV with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 degrees C.
Total Cost ($USD)
$33,230,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 lineAP_P2-3_PE-500-019B_SRT-A
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 lineAP_P2-3_PE-500-019F_SRT-SL
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 lineAP_P1-2_PE-500-406T_SRT-A
DICKH230-6EDFERRY 230.0 kV Ckt 1 lineAP_P2-3_PE-500-019F_SRT-SL
DICKH230-6EDFERRY 230.0 kV Ckt 1 lineAP_P2-3_PE-500-019B_SRT-A
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 linePEPCO_P1_5070_SRT-A
DICKH230-6EDFERRY 230.0 kV Ckt 1 linePEPCO_P1_5070_SRT-A
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.343
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.343
Title
Uprate bus at Brambleton to support 500kV Line #558 (Aspen to Brambleton) uprate.
Description
Uprate bus at Brambleton to support 500kV Line #558 (Aspen to Brambleton) uprate.
Cost Information
Time Estimate
Nov 28 2025

Not Contingent

Note: AG2-151 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-151 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8BRAMBLETON-AH1-727 TP 500.0 kV Ckt 1 line(Any)

System Reinforcement: n9249.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9249.0 / TC1-PH2-DOM-043
Title
Construct new 37.26 mile line between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C. Station upgrades at Midlothian and Carson to accommodate new line.
Description
Construct new 37.26 mile line between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C. Station upgrades at Midlothian and Carson to accommodate new line. New Rating = 4356/4356/5009 MVA
Total Cost ($USD)
$231,012,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S

System Reinforcement: n9139.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9139.0 / TC1-PH1-DOM-073
Title
Wreck and rebuild 37.41 miles of 500kV line 563 between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" and associated substation work.
Description
Wreck and rebuild 37.41 miles of 500kV transmission line 563 between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA. Remove wave traps.
Total Cost ($USD)
$245,455,768
Allocated Cost ($USD)
$0
Time Estimate
69 to 70 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Feb 24 2029

Contingent

Note: Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 may need this upgrade in-service to be deliverable to the PJM system. If AG2-151 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6LUCKYHILL-6REMNGTN 230.0 kV Ckt 1 line(Any)
6KYSER-6LUCKYHILL 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029

Contingent

Note: Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 may need this upgrade in-service to be deliverable to the PJM system. If AG2-151 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
6LUCKYHILL-6REMNGTN 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6KYSER-6LUCKYHILL 230.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029

Contingent

Note: Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 may need this upgrade in-service to be deliverable to the PJM system. If AG2-151 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6KYSER-6LUCKYHILL 230.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6LUCKYHILL-6REMNGTN 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9191.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9191.0 / TC1-PH1-DOM-090
Title
Rebuild 41.13 miles of line 576 between North Anna and Midlothian with triple bundled (3) 1351.5 ACSR (45/7) "Dipper" conductor and associated substation work.
Description
Rebuild 41.13 miles of line 576 between North Anna and Midlothian with triple bundled (3) 1351.5 ACSR (45/7) "Dipper" conductor at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA.
Total Cost ($USD)
$256,706,175
Allocated Cost ($USD)
$0
Time Estimate
74 to 75 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P1-2: LN 576_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: WT576_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: 57602_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2091
Title
Replace the existing Finneywood 230/500 kV XFRM T1 with a 3-480 MVA rated device
Description
Replace the existing Finneywood 230/500 kV XFRM T1 with a 3-480 MVA rated device
Total Cost ($USD)
$40,000,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
8FINNEYWOOD-6FINNEYWOOD 500.0/230.0 kV Ckt 1 transformer(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2092
Title
Replace the existing Finneywood 230/500 kV XFRM T2 with a 3-480 MVA rated device
Description
Replace the existing Finneywood 230/500 kV XFRM T2 with a 3-480 MVA rated device
Total Cost ($USD)
$40,000,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
8FINNEYWOOD-6FINNEYWOOD 500.0/230.0 kV Ckt 2 transformer(Any)

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 may need this upgrade in-service to be deliverable to the PJM system. If AG2-151 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
6LUCKYHILL-6REMNGTN 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6KYSER-6LUCKYHILL 230.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 may need this upgrade in-service to be deliverable to the PJM system. If AG2-151 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
6KYSER-6LUCKYHILL 230.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6LUCKYHILL-6REMNGTN 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 may need this upgrade in-service to be deliverable to the PJM system. If AG2-151 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
6KYSER-6LUCKYHILL 230.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6LUCKYHILL-6REMNGTN 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 may need this upgrade in-service to be deliverable to the PJM system. If AG2-151 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6KYSER-6LUCKYHILL 230.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6LUCKYHILL-6REMNGTN 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 may need this upgrade in-service to be deliverable to the PJM system. If AG2-151 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
6LUCKYHILL-6REMNGTN 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6KYSER-6LUCKYHILL 230.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 may need this upgrade in-service to be deliverable to the PJM system. If AG2-151 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6LUCKYHILL-6REMNGTN 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6KYSER-6LUCKYHILL 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 may need this upgrade in-service to be deliverable to the PJM system. If AG2-151 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
6LUCKYHILL-6REMNGTN 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6KYSER-6LUCKYHILL 230.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)

System Reinforcement: n9248.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9248.0 / TC1-PH2-DOM-042
Title
Construct new 41.13 mile line between North Anna and Midlothian with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN" at 145 degrees C. Station upgrades at North Anna and Midlothian to accommodate new line.
Description
Construct new 41.13 mile line between North Anna and Midlothian with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN" at 145 degrees C. Station upgrades at North Anna and Midlothian to accommodate new line.
Total Cost ($USD)
$345,766,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P1-2: LN 576_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P1-2: LN 557_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: WT576_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: 57602_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P4-2: 557T574_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 may need this upgrade in-service to be deliverable to the PJM system. If AG2-151 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6LUCKYHILL-6REMNGTN 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6KYSER-6LUCKYHILL 230.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0075
Title
Wreck and rebuild 18.75 miles of 500 kV Line 594 between Spotsylvania and Morrisville with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN"
Description
Wreck and rebuild 18.75 miles of 500 kV Line 594 between Spotsylvania and Morrisville with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN"
Total Cost ($USD)
$110,625,000
Allocated Cost ($USD)
$0
Time Estimate
18 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P2-2: MORRISVILLE B1_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P4-2: 545T552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P4-2: H1T552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P4-2: H3T552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 550_SRT-A

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0076
Title
Replace Wave Trap 594WT at Morrisville 500 KV
Description
Replace Wave Trap 594WT at Morrisville 500 KV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$0
Time Estimate
16 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0077
Title
Replace Wave Trap 594WT at Spotsylvania 500 KV
Description
Replace Wave Trap 594WT at Spotsylvania 500 KV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$0
Time Estimate
16 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0078
Title
Replace 3-1590 AAC 61 line lead on Line 594 at Morrisville 500 kV
Description
Replace 3-1590 AAC 61 line lead on Line 594 at Morrisville 500 kV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 may need this upgrade in-service to be deliverable to the PJM system. If AG2-151 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
6HOLLYMD-6PROFFIT 230.0 kV Ckt 1 line(Any)
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line(Any)
6LUCKYHILL-6REMNGTN 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6KYSER-6LUCKYHILL 230.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0071
Title
Wreck and rebuild 14.02 miles of 500 kV Line 573 between Spotsylvania and North Anna with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN".
Description
Wreck and rebuild 14.02 miles of 500 kV Line 573 between Spotsylvania and North Anna with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN".
Total Cost ($USD)
$82,718,000
Allocated Cost ($USD)
$0
Time Estimate
18 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0072
Title
Replace 2-2500 ACAR 84/7 line lead on Line 573 at North Anna 500 kV
Description
Replace 2-2500 ACAR 84/7 line lead on Line 573 at North Anna 500 kV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0073
Title
Replace Wave Trap 573WT at Spotsylvania 500 KV
Description
Replace Wave Trap 573WT at Spotsylvania 500 KV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$0
Time Estimate
16 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2008
Title
Wreck and rebuild 0.47 miles of 230 kV Line 2241 between Hendrick and Alton Post with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 0.47 miles of 230 kV Line 2241 between Hendrick and Alton Post with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$1,786,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending)
Title
No overload on Dominion equipment for 8POSSUM - BURCHES (TC2)
Description
Dominion End Ratings Winter: 5414/5581/6107 Light Load: 5227/5388/5941 Summer: 4257/4388/5046
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
BURCHES-8POSSUM 500.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
(Pending) / (Pending)
Title
TC2 Upgrade for BURCHES 500.0 kV to 8POSSUM 500.0 kV ckt 1
Description
Replaces the terminal equipment at Burches Hill 500 kV station (breakers, switches, and stranded bus) that upgrades the ratings.
Total Cost ($USD)
$6,000,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
BURCHES-8POSSUM 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.242
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.242
Title
Upgrading switches 20366M and 20369M and line leads to 4000A continuous current rating of 230kV Line #203 at Edwards Ferry substation
Description
Upgrading switches 20366M and 20369M and line leads to 4000A continuous current rating of 230kV Line #203 at Edwards Ferry substation
Cost Information
Time Estimate
Sep 13 2030

Not Contingent

Note: AG2-151 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-151 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.244
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b3800.244
Title
Rebuild 7.26 miles of existing 230 kV circuit from Dickerson Station H to Ed's Ferry area to accommodate the new 500 kV circuit between Doubs and Aspen. (The 230kV portion of the project)
Description
Rebuild 7.26 miles of existing 230 kV circuit from Dickerson Station H to Ed's Ferry area to accommodate the new 500 kV circuit between Doubs and Aspen. (The 230kV portion of the project)
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AG2-151 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-151 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
(Pending) / (Pending)
Title
Additional Aspen to Dickerson H 230 kV line
Description
PEPCO’s substation cost to accommodate an additional circuit at Dickerson H to be approximately $7.86 million. The cost for the remaining 7.25 miles of 230 kV transmission line is estimated at $78.62 million.
Total Cost ($USD)
$86,480,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-151 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-151 could receive cost allocation. Although AG2-151 may not presently have cost responsibility for this upgrade, AG2-151 is a potential Aggregate Pool Contributor.

FacilityContingency
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
          AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-198, AG2-566
        
          AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-440, AG2-441, AG2-442
        
          AG2-068 500 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-068, AG2-069, AG2-369
        
          AE2-094 500 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-338, AG2-339
        
          AG2-570 500 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-570, AG2-571
        
          Perth 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-111, AG2-112
        

Attachments

AG2-151 One Line Diagram

AG2-151 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.