AG2-152 Phase I Study Report

v1.00 released 2025-10-29 21:17

Banister-Bear Skin 138 kV

79.0 MW Capacity / 131.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Virginia Electric and Power Company (d/b/a) Dominion Energy Virginia, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is American Electric Power.

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed a Solar generating facility located in the American Electric Power zone — Pittsylvania County, Virginia. The installed facilities will have a total capability of 131.0 MW with 79.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-152
Project Name:
Banister-Bear Skin 138 kV
Project Developer Name:
Virginia Electric and Power Company (d/b/a) Dominion Energy Virginia
State:
Virginia
County:
Pittsylvania
Transmission Owner:
American Electric Power
MFO:
131.0
MWE:
131.0
MWC:
79.0
Fuel Type:
Solar
Basecase Study Year:
2028

Capacity Interconnection Rights (CIR) Transfer Details

This project intends to claim and transfer CIRs from the following Deactivation capacity generation resources. PJM performed a reliability analysis of the impacts to the system capability for the proposed transfer of CIRs from the Deactivation generation resources.

Unit NameStatusCIR ClaimedPOI Transfer
Chesterfield 6Deactivated Generator52.0Yes
Yorktown 3Deactivated Generator27.0Yes

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AG2-152 will interconnect on the American Electric Power  transmission system  tapping the Banister-Bear Skin 138 kV Line.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AG2-152 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-152Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$18,578,995$18,578,995
Network Upgrades$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$20,522,088$20,522,088
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$39,101,083$39,101,083

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AG2-152

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AG2-152 Project due at DP1
ABA - B
AG2-152$3,910,108$524,000$3,386,108

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Stand-Alone Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)AEP will construct a new breaker and a half station, initially populated with 3 breakers and operated as a ring bus as well as the associated facilities required to support the interconnection.$18,578,995 $18,578,995

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 24 to 30 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Transmission Owner Analysis

No Transmission Owner impacts identified.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-152 was evaluated as a 131.0 MW (79.0 MW Capacity) injection in the AEP area.

AG2-152 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 131.0 MW (131.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
AEP_P7-1_#10817___SRT-A
TowerAC120.87 %388.0B468.9780.42
GD2AEP
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
AEP_P4_#10213_05CLOVRD 138_A_SRT-A
BreakerAC113.77 %388.0B441.4378.33
GD2AEP
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
AEP_P4_#10210_05CLOVRD 138_A2_SRT-A
BreakerAC113.52 %388.0B440.4478.3
GD2AEP
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
AEP_P7-1_#10808___SRT-A
TowerAC110.55 %388.0B428.9480.44
GD2AEP
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
AEP_P2-2_#6213_05WLAKE 138_1_SRT-A
BusAC104.39 %388.0B405.0375.88
GD2AEP
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
AEP_P2-2_#6212_05WLAKE 138_2_SRT-A
BusAC102.03 %388.0B395.8975.88
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC121.06 %3393.4B4107.9712.36
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC117.02 %3610.0B4224.5517.64
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC116.77 %3610.0B4215.4317.63
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC116.68 %3610.0B4211.9817.62
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC116.36 %3610.0B4200.4317.63
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
DVP_P4-2: 151T1047_SRT-A
BreakerAC134.96 %245.0B330.656.6
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
DVP_P4-2: 104702_SRT-A
BreakerAC134.95 %245.0B330.636.6
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
DVP_P4-2: 1016T1047_SRT-A
BreakerAC128.07 %245.0B313.776.61
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
DVP_P4-2: 101672_SRT-A
BreakerAC128.05 %245.0B313.736.61
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
DVP_P4-2: 104772_SRT-A
BreakerAC126.62 %245.0B310.216.61
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
DVP_P1-2: LN 1047_SRT-A
SingleAC106.29 %245.0B260.44.63
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
DVP_P1-2: LN 1016_SRT-A-1
SingleAC101.51 %245.0B248.714.64
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
BusAC100.25 %245.0B245.6113.8
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
AEP_P7-1_#10778___SRT-A
TowerAC100.25 %245.0B245.613.8
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Base Case
SingleAC118.66 %192.7A228.666.85
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
BreakerAC117.03 %284.0B332.3629.76
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
BreakerAC116.49 %284.0B330.8229.65
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
BusAC115.7 %284.0B328.5829.65
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P7-1_#10778___SRT-A
TowerAC115.69 %284.0B328.5629.65
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P4_#10687_05EDAN 2 138_N_SRT-A
BreakerAC115.68 %284.0B328.5429.65
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P4_#8676_05EDANV2 230_S_SRT-A
BreakerAC115.67 %284.0B328.529.65
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P1-2_#5366_SRT-A-1
SingleAC110.86 %266.96B295.9520.77
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P1-3_#10688_05EDANV2 230_4_SRT-A
SingleAC110.35 %266.96B294.620.79
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P4_#10213_05CLOVRD 138_A_SRT-A
BreakerAC106.32 %284.0B301.9613.56
IPDAEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Base Case
SingleAC104.85 %192.7A202.0411.36
IPDAEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P1-2_#5366_SRT-A-1
SingleAC102.26 %266.96B272.9834.45
IPDAEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P1-3_#10688_05EDANV2 230_4_SRT-A
SingleAC101.72 %266.96B271.5634.48
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P7-1_#10781___SRT-A-1
TowerAC100.01 %284.0B284.0115.21
GD2AEP
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
BreakerAC112.15 %296.0B331.96112.58
GD2AEP
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
BreakerAC109.26 %296.0B323.4112.58
GD2AEP
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
AEP_P4_#8676_05EDANV2 230_S_SRT-A
BreakerAC109.26 %296.0B323.4112.58
GD2AEP
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
AEP_P4_#10687_05EDAN 2 138_N_SRT-A
BreakerAC109.26 %296.0B323.4112.58
GD2AEP
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
BusAC109.26 %296.0B323.4112.58
GD2AEP
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
AEP_P7-1_#10778___SRT-A
TowerAC109.26 %296.0B323.4112.58
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
DVP_P4-2: 151T1047_SRT-A
BreakerAC136.34 %245.0B334.026.6
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
DVP_P4-2: 104702_SRT-A
BreakerAC136.33 %245.0B334.06.6
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
DVP_P4-2: 1016T1047_SRT-A
BreakerAC129.43 %245.0B317.116.61
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
DVP_P4-2: 101672_SRT-A
BreakerAC129.42 %245.0B317.076.61
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
DVP_P4-2: 104772_SRT-A
BreakerAC127.97 %245.0B313.536.61
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
DVP_P1-2: LN 1047_SRT-A
SingleAC107.67 %245.0B263.784.63
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
DVP_P1-2: LN 1016_SRT-A-1
SingleAC102.87 %245.0B252.044.64
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
BusAC101.55 %245.0B248.813.8
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
AEP_P7-1_#10778___SRT-A
TowerAC101.55 %245.0B248.7913.8
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
DVP_P2-2: ALTAVISTA 115KV_SRT-A
BusAC100.37 %245.0B245.97.55
GD2AEP
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
BreakerAC113.61 %255.0B289.7129.79
GD2AEP
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
BreakerAC113.02 %255.0B288.229.68
GD2AEP
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
BusAC112.15 %255.0B285.9729.68
GD2AEP
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
AEP_P7-1_#10778___SRT-A
TowerAC112.13 %255.0B285.9429.68
GD2AEP
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
AEP_P4_#10687_05EDAN 2 138_N_SRT-A
BreakerAC112.13 %255.0B285.9229.68
GD2AEP
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
AEP_P4_#8676_05EDANV2 230_S_SRT-A
BreakerAC112.11 %255.0B285.8929.68
GD2AEP
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
AEP_P4_#10213_05CLOVRD 138_A_SRT-A
BreakerAC101.78 %255.0B259.5513.59
GD2DVP
3CRSTL HILL-AC1-222 TAP 115.0 kV Ckt 1 line
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
BreakerAC100.59 %350.0C352.0713.06
GD2DVP
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
BreakerAC111.45 %350.0C390.0813.03
GD2DVP
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
BreakerAC109.96 %350.0C384.8512.85
GD2DVP
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
BusAC109.7 %350.0C383.9412.85
GD2DVP
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
AEP_P7-1_#10778___SRT-A
TowerAC109.69 %350.0C383.9212.85
GD2DVP
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
AEP_P1-3_#10688_05EDANV2 230_4_SRT-A
SingleAC106.4 %285.76B304.059.01
GD2DVP
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
AEP_P1-2_#5366_SRT-A-1
SingleAC106.21 %285.76B303.58.98
GD2DVP
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
AEP_P7-1_#10781___SRT-A-1
TowerAC102.7 %350.0C359.467.33
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
DVP_P4-2: 151T1047_SRT-A
BreakerAC137.18 %245.0B336.086.6
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
DVP_P4-2: 104702_SRT-A
BreakerAC137.17 %245.0B336.066.6
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
DVP_P4-2: 1016T1047_SRT-A
BreakerAC130.26 %245.0B319.146.61
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
DVP_P4-2: 101672_SRT-A
BreakerAC130.24 %245.0B319.16.61
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
DVP_P4-2: 104772_SRT-A
BreakerAC128.8 %245.0B315.556.61
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
DVP_P1-2: LN 1047_SRT-A
SingleAC115.43 %230.3B265.844.63
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
DVP_P1-2: LN 1016_SRT-A-1
SingleAC110.32 %230.3B254.074.64
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
BusAC102.33 %245.0B250.7113.8
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
AEP_P7-1_#10778___SRT-A
TowerAC102.33 %245.0B250.713.8
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
DVP_P2-2: ALTAVISTA 115KV_SRT-A
BusAC101.22 %245.0B247.987.55
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC212.98 %699.0C1488.765.77
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC212.93 %699.0C1488.375.77
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC209.35 %699.0C1463.375.68
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC207.29 %571.52B1184.73.98
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC204.76 %571.52B1170.273.98
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC203.45 %699.0C1422.115.68
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC203.45 %699.0C1422.115.68
GD2DVP
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
DVP_P4-2: 509T570_SRT-A
BreakerAC114.83 %997.0C1144.913.36
GD2DVP
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-3
SingleAC108.64 %814.98B885.419.44
GD2DVP
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-2
SingleAC106.47 %814.98B867.679.44
GD2DVP
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
DVP_P4-2: 57062_SRT-S
BreakerAC100.2 %997.0C998.9713.46
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC201.24 %684.0C1376.515.79
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC201.19 %684.0C1376.135.79
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC197.56 %684.0C1351.345.7
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC195.93 %559.3B1095.864.0
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC193.37 %559.3B1081.514.0
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC191.54 %684.0C1310.125.7
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC191.54 %684.0C1310.125.7
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-3
SingleAC182.88 %508.54B930.038.89
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-2
SingleAC178.67 %508.54B908.598.89
GD2DVP
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line
DVP_P4-2: 509T570_SRT-A
BreakerAC109.79 %997.0C1094.5713.39
GD2DVP
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-3
SingleAC103.53 %814.98B843.759.46
GD2DVP
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-2
SingleAC101.35 %814.98B825.979.46
GD2DVP
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line
DVP_P1-2: LN 555_SRT-A
SingleAC112.33 %3220.44B3617.398.2
GD2DVP
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line
DVP_P7-1: LN 2168-555_SRT-A
TowerAC105.49 %3940.0C4156.412.91
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-1
SingleAC139.73 %4070.2B5687.3312.91
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-2
SingleAC133.78 %4070.2B5445.2812.91
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 58572_SRT-A
BreakerAC124.04 %4996.0C6196.9518.41
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-5: W72_SRT-A
BreakerAC123.43 %4996.0C6166.5618.35
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: XT585_SRT-S
BreakerAC114.16 %4996.0C5703.6618.41
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 54472_SRT-S
BreakerAC111.74 %2858.0C3193.4911.34
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC123.06 %4070.2B5008.6512.09
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51192_SRT-S
BreakerAC109.25 %4996.0C5458.0617.25
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51172_SRT-S
BreakerAC108.79 %4996.0C5435.0717.2
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P4-2: 511T544_SRT-S
BreakerAC107.19 %4996.0C5355.1917.06
GD2DVP
8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line
DVP_P1-2: LN 555_SRT-A
SingleAC112.01 %3220.44B3607.138.2
GD2DVP
8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line
DVP_P7-1: LN 2168-555_SRT-A
TowerAC105.23 %3940.0C4145.8812.91
GD2DVP
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
BreakerAC113.44 %350.0C397.0513.03
GD2DVP
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
BreakerAC111.95 %350.0C391.8312.85
GD2DVP
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
BusAC111.69 %350.0C390.9312.85
GD2DVP
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
AEP_P7-1_#10778___SRT-A
TowerAC111.69 %350.0C390.9112.85
GD2DVP
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
AEP_P1-3_#10688_05EDANV2 230_4_SRT-A
SingleAC108.84 %285.76B311.039.01
GD2DVP
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
AEP_P1-2_#5366_SRT-A-1
SingleAC108.65 %285.76B310.488.98
GD2DVP
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
AEP_P7-1_#10781___SRT-A-1
TowerAC104.72 %350.0C366.517.33
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC136.1 %4070.2B5539.4112.09
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 51192_SRT-S
BreakerAC120.36 %4996.0C6013.1117.25
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 51172_SRT-S
BreakerAC119.82 %4996.0C5986.2917.2
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 511T544_SRT-S
BreakerAC118.15 %4996.0C5902.917.06
GD2AEP
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
AEP_P7-1_#10817___SRT-A
TowerAC121.83 %392.0B477.5780.42
GD2AEP
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
AEP_P4_#10213_05CLOVRD 138_A_SRT-A
BreakerAC114.79 %392.0B450.078.33
GD2AEP
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
AEP_P4_#10210_05CLOVRD 138_A2_SRT-A
BreakerAC114.54 %392.0B449.0178.3
GD2AEP
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
AEP_P7-1_#10808___SRT-A
TowerAC111.62 %392.0B437.5480.44
GD2AEP
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
AEP_P2-2_#6213_05WLAKE 138_1_SRT-A
BusAC105.51 %392.0B413.675.88
GD2AEP
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
AEP_P2-2_#6212_05WLAKE 138_2_SRT-A
BusAC103.18 %392.0B404.4575.88
IPDAEP
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
AEP_P7-1_#10817___SRT-A
TowerAC100.63 %392.0B394.4593.51
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC211.67 %684.0C1447.795.79
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC211.61 %684.0C1447.45.79
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC207.99 %684.0C1422.625.7
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC206.17 %559.3B1153.124.0
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC203.59 %559.3B1138.684.0
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC201.95 %684.0C1381.355.7
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC201.95 %684.0C1381.355.7
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC129.2 %4070.2B5258.7212.09
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51192_SRT-S
BreakerAC114.25 %4996.0C5708.1217.25
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51172_SRT-S
BreakerAC113.76 %4996.0C5683.4417.2
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P4-2: 511T544_SRT-S
BreakerAC112.13 %4996.0C5601.817.06
GD2DVP
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
BreakerAC103.04 %350.0C360.6413.06
GD2DVP
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
BreakerAC101.53 %350.0C355.3712.87
GD2DVP
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
BusAC101.27 %350.0C354.4612.87
GD2DVP
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
AEP_P7-1_#10778___SRT-A
TowerAC101.27 %350.0C354.4412.87
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC218.2 %684.0C1492.55.79
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC218.14 %684.0C1492.115.79
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC214.52 %684.0C1467.345.7
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC212.24 %559.3B1187.044.0
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC209.65 %559.3B1172.594.0
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC208.48 %684.0C1426.035.7
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC208.48 %684.0C1426.035.7
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC219.98 %699.0C1537.655.77
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC219.92 %699.0C1537.265.77
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC216.35 %699.0C1512.315.68
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC213.74 %571.52B1221.63.98
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC211.19 %571.52B1206.973.98
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC210.43 %699.0C1470.95.68
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC210.43 %699.0C1470.95.68

Details for 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line l/o AEP_P7-1_#10817___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10817___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:120.87 %
Rating:388.0 MVA
Rating Type:B
MVA to Mitigate:468.97
MW Contribution:80.42
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
3.549
24684505SMG3
50/50
2.195
24684305SMG1
50/50
1.287
270013AE1-250 PV
Solar/Wind Harmer
12.954
270455AD2-022 GEN
Solar/Wind Helper
0.924
270457AD2-023 GEN
Solar/Wind Helper
0.609
24684705SMG5
50/50
1.367
970481AG2-311 GEN
50/50
19.048
24728405LEESVG
50/50
0.493
970223AG2-152 GEN
Solar/Wind Harmer
80.422
270016AE1-250 BESS
Solar/Wind Harmer
12.954
270574AD1-017 GEN2
Solar/Wind Harmer
23.549
270173AC1-122 GEN
Solar/Wind Harmer
4.971
24684605SMG4
50/50
3.572
24728405LEESVG
50/50
0.495
270197AD1-017 GEN1
Solar/Wind Harmer
7.076
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.014
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.058
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.099
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.315
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.611
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.571

Details for 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line l/o AEP_P4_#10213_05CLOVRD 138_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10213_05CLOVRD 138_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.77 %
Rating:388.0 MVA
Rating Type:B
MVA to Mitigate:441.43
MW Contribution:78.33
Bus #Bus NameTypeMW Contribution
24684705SMG5
50/50
1.198
970481AG2-311 GEN
50/50
16.703
24728405LEESVG
50/50
0.334
3151561HALLBR1
50/50
0.448
970223AG2-152 GEN
Solar/Wind Harmer
78.334
270016AE1-250 BESS
Solar/Wind Harmer
12.518
270574AD1-017 GEN2
Solar/Wind Harmer
22.147
270173AC1-122 GEN
Solar/Wind Harmer
3.243
3147312GRETNA
Solar/Wind Harmer
-0.017
3146802CHATHAM
Solar/Wind Harmer
-0.016
941801AE2-185 GEN
Solar/Wind Harmer
8.005
3147123OTTER R
Solar/Wind Harmer
-0.011
962751AG1-124 GEN
Solar/Wind Harmer
5.228
24684405SMG2
50/50
3.112
24684505SMG3
50/50
1.925
24684305SMG1
50/50
1.128
270013AE1-250 PV
Solar/Wind Harmer
12.518
316217AC1-145 GEN
Solar/Wind Harmer
3.465
316197AC1-042 GEN
Solar/Wind Harmer
2.627
942671AE2-283 GEN
Solar/Wind Harmer
7.071
942751AE2-291 GEN
Solar/Wind Harmer
7.417
316123AC1-075 GEN
Solar/Wind Harmer
1.01
970165AG2-112 GEN
Solar/Wind Harmer
0.889
970163AG2-111 GEN
Solar/Wind Harmer
0.849
270455AD2-022 GEN
Solar/Wind Helper
0.935
270457AD2-023 GEN
Solar/Wind Helper
0.616
24684605SMG4
50/50
3.133
24728405LEESVG
50/50
0.336
270197AD1-017 GEN1
Solar/Wind Harmer
6.655
3147312GRETNA
Solar/Wind Harmer
-0.004
941821AE2-187 GEN
Solar/Wind Harmer
8.005
958131AF2-107 GEN
Solar/Wind Harmer
2.397
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.068
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.225
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.079
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.234
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.589
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.768

Details for 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line l/o AEP_P4_#10210_05CLOVRD 138_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10210_05CLOVRD 138_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.52 %
Rating:388.0 MVA
Rating Type:B
MVA to Mitigate:440.44
MW Contribution:78.3
Bus #Bus NameTypeMW Contribution
24684705SMG5
50/50
1.197
970481AG2-311 GEN
50/50
16.68
24728405LEESVG
50/50
0.334
3151561HALLBR1
50/50
0.448
970223AG2-152 GEN
Solar/Wind Harmer
78.303
270016AE1-250 BESS
Solar/Wind Harmer
12.513
270574AD1-017 GEN2
Solar/Wind Harmer
22.132
270173AC1-122 GEN
Solar/Wind Harmer
3.239
3147312GRETNA
Solar/Wind Harmer
-0.017
3146802CHATHAM
Solar/Wind Harmer
-0.016
941801AE2-185 GEN
Solar/Wind Harmer
7.991
3147123OTTER R
Solar/Wind Harmer
-0.011
962751AG1-124 GEN
Solar/Wind Harmer
5.215
24684605SMG4
50/50
3.128
24728405LEESVG
50/50
0.335
270197AD1-017 GEN1
Solar/Wind Harmer
6.65
3147312GRETNA
Solar/Wind Harmer
-0.004
941821AE2-187 GEN
Solar/Wind Harmer
7.991
958131AF2-107 GEN
Solar/Wind Harmer
2.391
316123AC1-075 GEN
Solar/Wind Harmer
1.008
970165AG2-112 GEN
Solar/Wind Harmer
0.887
970163AG2-111 GEN
Solar/Wind Harmer
0.846
270455AD2-022 GEN
Solar/Wind Helper
0.937
270457AD2-023 GEN
Solar/Wind Helper
0.617
24684405SMG2
50/50
3.108
24684505SMG3
50/50
1.922
24684305SMG1
50/50
1.127
270013AE1-250 PV
Solar/Wind Harmer
12.513
316217AC1-145 GEN
Solar/Wind Harmer
3.459
316197AC1-042 GEN
Solar/Wind Harmer
2.622
942671AE2-283 GEN
Solar/Wind Harmer
7.059
942751AE2-291 GEN
Solar/Wind Harmer
7.401
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.068
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.226
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.078
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.237
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.59
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.771

Details for 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line l/o AEP_P7-1_#10808___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10808___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.55 %
Rating:388.0 MVA
Rating Type:B
MVA to Mitigate:428.94
MW Contribution:80.44
Bus #Bus NameTypeMW Contribution
24684605SMG4
50/50
3.574
270197AD1-017 GEN1
Solar/Wind Harmer
7.079
270455AD2-022 GEN
Solar/Wind Helper
0.921
270457AD2-023 GEN
Solar/Wind Helper
0.607
24684405SMG2
50/50
3.551
24684505SMG3
50/50
2.196
24684305SMG1
50/50
1.287
270013AE1-250 PV
Solar/Wind Harmer
12.958
24684705SMG5
50/50
1.367
970481AG2-311 GEN
50/50
19.058
970223AG2-152 GEN
Solar/Wind Harmer
80.445
270016AE1-250 BESS
Solar/Wind Harmer
12.958
270574AD1-017 GEN2
Solar/Wind Harmer
23.558
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.003
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.023
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.088
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.303
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.604
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.518

Details for 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line l/o AEP_P2-2_#6213_05WLAKE 138_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#6213_05WLAKE 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.39 %
Rating:388.0 MVA
Rating Type:B
MVA to Mitigate:405.03
MW Contribution:75.88
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
2.694
24684505SMG3
50/50
1.666
24684305SMG1
50/50
0.977
270013AE1-250 PV
Solar/Wind Harmer
12.034
316217AC1-145 GEN
Solar/Wind Harmer
3.013
316197AC1-042 GEN
Solar/Wind Harmer
2.284
942671AE2-283 GEN
Solar/Wind Harmer
6.149
942751AE2-291 GEN
Solar/Wind Harmer
6.246
316123AC1-075 GEN
Solar/Wind Harmer
0.835
970165AG2-112 GEN
Solar/Wind Harmer
0.735
970163AG2-111 GEN
Solar/Wind Harmer
0.701
270455AD2-022 GEN
Solar/Wind Helper
1.036
270457AD2-023 GEN
Solar/Wind Helper
0.682
24684705SMG5
50/50
1.038
970481AG2-311 GEN
50/50
14.46
24728405LEESVG
50/50
0.29
3151561HALLBR1
50/50
0.389
970223AG2-152 GEN
Solar/Wind Harmer
75.879
270016AE1-250 BESS
Solar/Wind Harmer
12.034
270574AD1-017 GEN2
Solar/Wind Harmer
20.72
270173AC1-122 GEN
Solar/Wind Harmer
2.826
3147312GRETNA
Solar/Wind Harmer
-0.015
3146802CHATHAM
Solar/Wind Harmer
-0.014
941801AE2-185 GEN
Solar/Wind Harmer
6.961
3147123OTTER R
Solar/Wind Harmer
-0.01
962751AG1-124 GEN
Solar/Wind Harmer
4.826
24684605SMG4
50/50
2.712
24728405LEESVG
50/50
0.291
270197AD1-017 GEN1
Solar/Wind Harmer
6.226
3147312GRETNA
Solar/Wind Harmer
-0.004
941821AE2-187 GEN
Solar/Wind Harmer
6.961
958131AF2-107 GEN
Solar/Wind Harmer
2.203
270018AE2-047 C O1
Solar/Wind Helper
0.451
943811AF1-049 GEN
Solar/Wind Helper
0.749
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.052
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.178
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.061
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.391
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.663
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.766

Details for 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line l/o AEP_P2-2_#6212_05WLAKE 138_2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#6212_05WLAKE 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.03 %
Rating:388.0 MVA
Rating Type:B
MVA to Mitigate:395.89
MW Contribution:75.88
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
2.694
24684505SMG3
50/50
1.666
24684305SMG1
50/50
0.977
270013AE1-250 PV
Solar/Wind Harmer
12.034
316217AC1-145 GEN
Solar/Wind Harmer
3.013
316197AC1-042 GEN
Solar/Wind Harmer
2.284
942671AE2-283 GEN
Solar/Wind Harmer
6.149
942751AE2-291 GEN
Solar/Wind Harmer
6.246
316123AC1-075 GEN
Solar/Wind Harmer
0.835
970165AG2-112 GEN
Solar/Wind Harmer
0.735
970163AG2-111 GEN
Solar/Wind Harmer
0.701
270455AD2-022 GEN
Solar/Wind Helper
1.036
270457AD2-023 GEN
Solar/Wind Helper
0.682
24684705SMG5
50/50
1.038
970481AG2-311 GEN
50/50
14.46
24728405LEESVG
50/50
0.29
3151561HALLBR1
50/50
0.389
970223AG2-152 GEN
Solar/Wind Harmer
75.879
270016AE1-250 BESS
Solar/Wind Harmer
12.034
270574AD1-017 GEN2
Solar/Wind Harmer
20.72
270173AC1-122 GEN
Solar/Wind Harmer
2.826
3147312GRETNA
Solar/Wind Harmer
-0.015
3146802CHATHAM
Solar/Wind Harmer
-0.014
941801AE2-185 GEN
Solar/Wind Harmer
6.961
3147123OTTER R
Solar/Wind Harmer
-0.01
962751AG1-124 GEN
Solar/Wind Harmer
4.826
24684605SMG4
50/50
2.712
24728405LEESVG
50/50
0.291
270197AD1-017 GEN1
Solar/Wind Harmer
6.226
3147312GRETNA
Solar/Wind Harmer
-0.004
941821AE2-187 GEN
Solar/Wind Harmer
6.961
958131AF2-107 GEN
Solar/Wind Harmer
2.203
270018AE2-047 C O1
Solar/Wind Helper
0.451
943811AF1-049 GEN
Solar/Wind Helper
0.749
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.052
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.178
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.061
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.391
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.663
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.766

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.06 %
Rating:3393.4 MVA
Rating Type:B
MVA to Mitigate:4107.97
MW Contribution:12.36
Bus #Bus NameTypeMW Contribution
971543AH1-269 GEN
50/50
12.247
966391AG1-508 GEN
Solar/Wind Harmer
1.993
270069AE2-166 C O1
Solar/Wind Harmer
0.008
971313AH1-133 GEN
Solar/Wind Harmer
10.952
24734705WLF1G3
Adder
8.194
24734805WLF1G4
Adder
8.194
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684405SMG2
50/50
2.224
24684505SMG3
50/50
1.376
24684305SMG1
50/50
0.806
270583AD2-179 GEN
Solar/Wind Harmer
14.457
971277AH1-098 GEN
Solar/Wind Harmer
5.177
316217AC1-145 GEN
Solar/Wind Harmer
0.003
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
5.796
24728205BUCHG1
Adder
6.75
270013AE1-250 PV
Solar/Wind Harmer
0.006
971225AH1-072 GEN
Solar/Wind Harmer
1.905
971227AH1-073 GEN
Solar/Wind Harmer
1.905
944971AF1-162 GEN
Solar/Wind Harmer
9.068
24723005RIVRG1
Adder
22.954
24723105RIVRG2
Adder
22.954
24685805CER G1
Adder
9.822
24685905CER G2
Adder
9.822
942751AE2-291 GEN
Solar/Wind Harmer
7.887
966021AG1-471 GEN
Solar/Wind Harmer
4.013
971485AH1-239 GEN
Solar/Wind Harmer
5.928
960161AF2-307 GEN
Solar/Wind Harmer
4.775
339255AE2-071 GEN
Solar/Wind Harmer
-0.119
964781AG1-341 GEN
Solar/Wind Harmer
7.653
971081AG2-670 GEN
Solar/Wind Harmer
5.396
942891AE2-308 GEN
Solar/Wind Harmer
7.099
970653AG2-424 GEN
Solar/Wind Harmer
3.405
970653AG2-424 GEN
Solar/Wind Harmer
1.764
964571AG1-320 GEN
Solar/Wind Harmer
6.361
971125AH1-004 GEN
Solar/Wind Harmer
2.777
970107AG2-081 GEN
Solar/Wind Harmer
2.083
972043AH1-570 GEN
Solar/Wind Harmer
1.796
972045AH1-571 GEN
Solar/Wind Harmer
1.439
339221AD2-048_GEN
Solar/Wind Harmer
0.004
970235AG2-159 GEN
Solar/Wind Harmer
4.126
970235AG2-159 GEN
Solar/Wind Harmer
2.367
270186AC1-089 GEN
Solar/Wind Harmer
0.004
970239AG2-162 GEN
Solar/Wind Harmer
1.663
962581AG1-107 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.8
252509AD1-136 GEN
Solar/Wind Harmer
0.033
25183208HLCRTG
Solar/Wind Harmer
0.01
252519AF1-045_GEN
Solar/Wind Harmer
5.589
252516AE2-318_GEN
Solar/Wind Harmer
4.958
25194408D.CRK1
Adder
6.938
25194508D.CRK3
Adder
1.297
971073AG2-665 GEN
Solar/Wind Harmer
5.761
945391AF1-204 GEN
Solar/Wind Harmer
6.765
276916AD2-100_GEN
Solar/Wind Harmer
13.364
276911AD2-131_GEN
Solar/Wind Harmer
0.88
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.651
24728805RICHG1
Adder
3.384
24728905RICHG2
Adder
3.384
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
960251AF2-316 GEN
Solar/Wind Harmer
8.583
960201AF2-311 GEN
Solar/Wind Harmer
5.708
960611AF2-352 GEN
Solar/Wind Harmer
2.073
966841AG1-555 GEN
Solar/Wind Harmer
0.701
276782AC1-033 GEN
Solar/Wind Harmer
0.001
276741O09 GEN1
Solar/Wind Harmer
0.22
276708O09 GEN2
Solar/Wind Harmer
0.22
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.243
276646AC1-214 GEN2
Solar/Wind Harmer
0.243
972267AH1-718 GEN
Adder
3.688
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
8.241
274765LEE CO EC;6U
Adder
8.241
274762LEE CO EC;3U
Adder
8.222
274763LEE CO EC;4U
Adder
8.144
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
3.491
274856ECOGROVE ;U1
Solar/Wind Harmer
0.145
276611AD2-172 GEN
Solar/Wind Harmer
0.002
270383AD1-128 GEN
Solar/Wind Harmer
0.004
971341AH1-150 GEN
Solar/Wind Harmer
12.273
971343AH1-151 GEN
Solar/Wind Harmer
12.273
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
971333AH1-146 GEN
Solar/Wind Harmer
12.256
971335AH1-147 GEN
Solar/Wind Harmer
12.256
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
942991AE2-321 GEN
Solar/Wind Harmer
6.834
971613AH1-306 GEN
Solar/Wind Harmer
2.937
274879MINONK ;1U
Solar/Wind Harmer
0.258
970921AG2-575 GEN
Solar/Wind Harmer
6.111
970921AG2-575 GEN
Solar/Wind Harmer
2.037
962691AG1-118 GEN
Solar/Wind Harmer
18.322
958491AF2-143 GEN
Solar/Wind Harmer
9.158
960441AF2-335 GEN
Solar/Wind Harmer
6.106
970825AG2-519 GEN
Solar/Wind Harmer
6.767
274683WAUKEGAN ;8U
Adder
18.419
274683WAUKEGAN ;8U
Adder
15.526
274696ROCKY RD ;4P
Adder
9.957
274695ROCKY RD ;2P
Adder
9.727
274693ROCKY RD ;1P
Adder
9.632
970823AG2-518 GEN
50/50
8.384
247619Y1-049
50/50
0.913
24684705SMG5
50/50
0.856
970481AG2-311 GEN
50/50
11.937
24728405LEESVG
50/50
0.295
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.829
962751AG1-124 GEN
Solar/Wind Harmer
12.893
958121AF2-106 GEN
Solar/Wind Harmer
0.001
270173AC1-122 GEN
Solar/Wind Harmer
0.677
971331AH1-145 GEN
Solar/Wind Harmer
18.361
943031AE2-326 GEN
Solar/Wind Harmer
6.784
3147312GRETNA
Solar/Wind Harmer
0.186
3146802CHATHAM
Solar/Wind Harmer
0.175
941801AE2-185 GEN
Solar/Wind Harmer
7.452
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147123OTTER R
Solar/Wind Harmer
0.13
270346AE1-212 GEN
Solar/Wind Harmer
9.542
270030AE2-140 GEN
Solar/Wind Harmer
21.578
960911AF2-382 GEN
Solar/Wind Harmer
7.638
270016AE1-250 BESS
Solar/Wind Harmer
0.006
970913AG2-568 GEN
Solar/Wind Harmer
7.677
971461AH1-227 GEN
Solar/Wind Harmer
4.886
970223AG2-152 GEN
Solar/Wind Harmer
12.358
270053AF1-130 C
Solar/Wind Harmer
2.047
972103AH1-617 GEN
Solar/Wind Harmer
18.024
24686205CER G4
Adder
9.835
24686405CER G5
Adder
9.796
972273AH1-721 GEN
Adder
89.316
24721905FLATG4
Adder
21.686
970273AG2-179 GEN
Solar/Wind Harmer
4.425
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
8.427
962251AG1-071 GEN
Solar/Wind Harmer
4.496
966571AG1-526 GEN
Solar/Wind Harmer
15.967
970093AG2-073 GEN
Solar/Wind Harmer
7.166
960741AF2-365 GEN
Solar/Wind Harmer
3.563
3429391JKCT 9G
Adder
8.402
971191AH1-055 GEN
Solar/Wind Harmer
18.055
972167AH1-666 GEN
Solar/Wind Harmer
5.419
958171AF2-111 GEN
Solar/Wind Harmer
16.681
970243AG2-164 GEN
Solar/Wind Harmer
3.891
970519AG2-331 GEN
Solar/Wind Harmer
17.292
970699AG2-449 GEN
Solar/Wind Harmer
1.663
25196008MFTGT1
Adder
1.252
252510AF1-249 C
Solar/Wind Harmer
0.05
25194608D.CRK4
Adder
1.508
25196608WSDLE5
Adder
7.849
970193AG2-126 GEN
Solar/Wind Harmer
9.55
942481AE2-261 GEN
Solar/Wind Harmer
18.997
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.231
24728705AND G3
Adder
7.277
24728505AND G1
Adder
3.48
276621W2-048 GEN
Solar/Wind Harmer
0.318
276838X2-022 GEN2
Solar/Wind Harmer
0.355
276686W4-005 GEN3
Solar/Wind Harmer
0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.229
971993AH1-541 GEN
Solar/Wind Harmer
2.905
270356AE2-297 GEN
Solar/Wind Harmer
0.008
253406AD2-031_GEN
Solar/Wind Harmer
0.467
270222AC2-111 GEN
Solar/Wind Harmer
3.158
965931AG1-462 GEN
Solar/Wind Harmer
15.879
270291AC1-194 GEN
Solar/Wind Harmer
4.924
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
18.654
959611AF2-252 GEN
Solar/Wind Harmer
2.073
942111AE2-223 GEN
Solar/Wind Harmer
2.013
274878BISHOP HL;2U
Solar/Wind Harmer
0.208
276157O29GEN1
Solar/Wind Harmer
0.999
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
8.222
274767LEE CO EC;8U
Adder
8.125
270437AC2-090 C
Solar/Wind Harmer
0.003
970571AG2-364 GEN
Solar/Wind Harmer
12.296
253415AE1-040 GEN
Solar/Wind Harmer
0.002
972236AH1-702 GEN2
Adder
1.93
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.144
959091AF2-200 GEN
Solar/Wind Harmer
12.273
276889AE2-281 GEN
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.225
274850MENDOTA H;RU
Solar/Wind Harmer
0.072
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.11
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.654
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.673
970291AG2-192 GEN
Solar/Wind Harmer
0.612
274872LEEDK;1U
Solar/Wind Harmer
0.224
958821AF2-173 GEN
Solar/Wind Harmer
8.556
270004AE1-209 GEN
Solar/Wind Harmer
1.324
276805AD2-038 GEN
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
15.703
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
946031AF1-268 GEN
Solar/Wind Harmer
5.79
943121AE2-341 GEN
Solar/Wind Harmer
10.192
943591AF1-030 GEN
Solar/Wind Harmer
6.778
274729ELWOOD EC;1P
Adder
13.481
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.838
3147666LOUISA
Solar/Wind Helper
1.088
316254AC1-120 GEN1
Solar/Wind Helper
1.159
316097T157 G90
Solar/Wind Helper
1.125
970479AG2-310 GEN
50/50
20.255
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
966251AG1-494 GEN
50/50
4.388
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
24734905WLF1G5
Adder
8.194
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.023
270399AC1-101 GEN
Solar/Wind Harmer
2.892
270400AC1-102 GEN
Solar/Wind Harmer
2.892
941621AE2-160 GEN
Adder
4.285
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
970281AG2-184 GEN
Solar/Wind Harmer
18.925
972143AH1-644 GEN
Solar/Wind Harmer
9.763
971981AH1-535 GEN
Solar/Wind Harmer
5.843
971061AG2-657 GEN
Solar/Wind Harmer
5.368
24477305BRIDGE
Adder
0.419
972203AH1-686 GEN
Adder
2.704
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
965401AG1-405 GEN
Solar/Wind Harmer
4.227
965411AG1-406 GEN
Solar/Wind Harmer
2.719
339211AE2-254 GEN
Solar/Wind Harmer
0.003
3429211JKCT 2G
Adder
11.873
970455AG2-298 GEN
Solar/Wind Harmer
4.677
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
972163AH1-664 GEN
Solar/Wind Harmer
7.568
972165AH1-665 GEN
Solar/Wind Harmer
6.061
971985AH1-537 GEN
Solar/Wind Harmer
2.011
270367AC2-061_GEN
Solar/Wind Harmer
0.005
316123AC1-075 GEN
Solar/Wind Harmer
0.168
970165AG2-112 GEN
Solar/Wind Harmer
0.998
970163AG2-111 GEN
Solar/Wind Harmer
0.952
25196108MFTGT2
Adder
1.425
25196108MFTGT2
Adder
1.324
970879AG2-548 GEN
Solar/Wind Harmer
5.761
944221AF1-090 GEN
Solar/Wind Harmer
3.754
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.08
25196308WSDLE2
Adder
8.01
25196208WSDLE1
Adder
7.99
25196708WSDLE6
Adder
7.97
25196508WSDLE4
Adder
7.769
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.229
276848AB2-070 GEN3
Solar/Wind Harmer
0.228
963841AG1-237 GEN
Solar/Wind Harmer
2.698
946321AF1-296 GEN
Solar/Wind Harmer
3.483
270340AC2-060 GEN
Solar/Wind Harmer
0.007
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.505
941731AE2-173 GEN
Solar/Wind Harmer
5.162
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.204
961011AF2-392 GEN
Solar/Wind Harmer
3.623
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270240V3-007_GEN2
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
9.917
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.045
970169AG2-114 GEN
Solar/Wind Harmer
6.149
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
17.15
971171AH1-044 GEN
Solar/Wind Harmer
12.273
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971675AH1-338 GEN
Solar/Wind Harmer
2.39
971411AH1-196 GEN
Solar/Wind Harmer
9.19
970289AG2-191 GEN
Solar/Wind Harmer
1.163
971177AH1-047 GEN
Solar/Wind Harmer
3.774
270594AE1-207 GEN
Solar/Wind Harmer
6.853
276868AE1-113 GEN
Solar/Wind Harmer
1.227
276882AE2-255 GEN
Solar/Wind Harmer
0.715
970115AG2-085 GEN
Solar/Wind Harmer
2.442
971673AH1-337 GEN
Solar/Wind Harmer
3.956
274746AC1-111 G10
Adder
4.87
274744AC1-111 GEN8
Adder
4.87
25306009OHH W.
Adder
2.505
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.313
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.078
316164AC1-076 GEN
Solar/Wind Helper
1.172
238152AF2-075_GEN
Solar/Wind Helper
0.602
971029AG2-637 GEN
Solar/Wind Harmer
2.803
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316336AC2-165 C
Solar/Wind Helper
1.285
316006AB2-029 C
Solar/Wind Helper
0.112
316045AC1-158 PL2
Solar/Wind Helper
4.023
971367AH1-164 GEN
Solar/Wind Harmer
4.886
971329AH1-144 GEN
Solar/Wind Harmer
11.568
3147312GRETNA
Solar/Wind Harmer
0.047
941821AE2-187 GEN
Solar/Wind Harmer
7.452
270197AD1-017 GEN1
Solar/Wind Harmer
1.429
270336AE1-100 GEN
Solar/Wind Harmer
0.006
943811AF1-049 GEN
Solar/Wind Harmer
-0.002
24728305BUCHG2
Adder
6.75
270018AE2-047 C O1
Solar/Wind Harmer
0.004
958131AF2-107 GEN
Solar/Wind Harmer
5.339
24735205WLF2G2
Adder
8.023
971687AH1-348 GEN
Solar/Wind Harmer
0.948
971403AH1-188 GEN
Solar/Wind Harmer
13.153
24723205RIVRG3
Adder
22.954
971315AH1-136 GEN
Solar/Wind Harmer
1.695
24686105CER G3
Adder
9.887
24686505CER G6
Adder
9.874
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
24721705FLATG2
Adder
21.686
970947AG2-589 GEN
Solar/Wind Harmer
0.249
970273AG2-179 GEN
Solar/Wind Harmer
2.581
971821AH1-427 GEN
Solar/Wind Harmer
7.218
964901AG1-354 GEN
Solar/Wind Harmer
10.814
962241AG1-070 GEN
Solar/Wind Harmer
3.92
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
12.029
3429421JKCT 10G
Adder
8.402
971565AH1-281 GEN
Solar/Wind Harmer
1.396
339216AC1-074 GEN
Solar/Wind Harmer
0.187
945681AF1-233 GEN
Solar/Wind Harmer
12.782
927014AC1-188 GEN
Solar/Wind Harmer
0.004
970091AG2-072 GEN
Adder
74.012
970333AG2-219 GEN
Solar/Wind Harmer
4.755
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
25196808ZIMRHP
Adder
70.616
252507AC2-088 GEN
Solar/Wind Harmer
0.295
25196008MFTGT1
Adder
1.293
25194608D.CRK4
Adder
1.508
965911AG1-460 GEN
Solar/Wind Harmer
1.271
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.331
24728605AND G2
Adder
3.48
276615X2-022 GEN
Solar/Wind Harmer
0.066
963831AG1-236 GEN
Solar/Wind Harmer
2.455
274880W4-005 GEN4
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.107
963741AG1-226 GEN
Solar/Wind Harmer
14.811
972175AH1-670 GEN
Solar/Wind Harmer
5.171
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
8.673
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
274877BISHOP HL;1U
Solar/Wind Harmer
0.208
276158O29GEN2
Solar/Wind Harmer
0.001
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
8.222
274766LEE CO EC;7U
Adder
8.125
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.519
276903AD2-071 C
Solar/Wind Harmer
6.874
971475AH1-234 GEN
Solar/Wind Harmer
2.986
970819AG2-516 GEN
Solar/Wind Harmer
7.379
970569AG2-363 GEN
Solar/Wind Harmer
18.444
972235AH1-702 GEN1
Adder
2.22
24791305MDL-5G
Solar/Wind Harmer
0.001
274822ROCKFORD ;11
Adder
17.275
957471AF2-041 GEN
Solar/Wind Harmer
18.409
959081AF2-199 GEN
Solar/Wind Harmer
6.136
971067AG2-660 GEN
Solar/Wind Harmer
2.045
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
276861AD2-134 GEN
Solar/Wind Harmer
0.11
970291AG2-192 GEN
Solar/Wind Harmer
0.796
971997AH1-543 GEN
Solar/Wind Harmer
3.211
270032AE2-172
Solar/Wind Harmer
4.079
270263AC1-001 GEN
Solar/Wind Harmer
0.614
274872LEEDK;1U
Solar/Wind Harmer
0.004
270005AE1-210 C O1
Solar/Wind Harmer
1.324
965031AG1-367 GEN
Solar/Wind Harmer
6.111
962781AG1-127 GEN
Solar/Wind Harmer
5.815
276901AD2-066 C O1
Solar/Wind Harmer
0.006
939401AE1-172 GEN
Solar/Wind Harmer
4.568
970825AG2-519 GEN
Solar/Wind Harmer
2.167
274828WAUKEGAN ;BP
Adder
9.655
274682WAUKEGAN ;7U
Adder
15.703
276691AA1-018 GEN1
Solar/Wind Harmer
0.737
274745AC1-111 GEN9
Adder
4.87
315616AA1-038_C
Solar/Wind Helper
3.293
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.725
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.625
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.386
23583801GRNGAP
Solar/Wind Helper
4.287
316095T157 G97
Solar/Wind Helper
1.125
238147AE2-230_GEN1
Solar/Wind Helper
0.421
238149AF1-291A_GEN
Solar/Wind Helper
0.12
316313AB2-026
Solar/Wind Helper
0.354
316258AE1-075 C
Solar/Wind Helper
0.319
316405AF2-144 C
Solar/Wind Helper
0.265
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.387
316044AC1-158 PL1
Solar/Wind Helper
1.257
316450AC1-158 RIC
Solar/Wind Helper
0.335
274697ROCKY RD ;3P
Adder
2.642
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.824
958481AF2-142 GEN
Solar/Wind Harmer
9.131
971573AH1-285 GEN
Solar/Wind Harmer
1.134
3132123MT JACKSON
Solar/Wind Helper
1.389
315821AE2-092 GEN
Solar/Wind Helper
3.216
966001AG1-469 GEN
Solar/Wind Helper
0.32
315651AD1-115 GEN
Solar/Wind Helper
0.837
966871AG1-558 GEN
Solar/Wind Helper
0.306
316447AC1-158 HLD
Solar/Wind Helper
2.766
316468AD1-105 GEN
Solar/Wind Helper
1.124
944201AF1-088_MTX
Adder
109.09
957141AF2-008_MTX
Adder
54.545
LAGNLTFEXP_LAGN->PJM
CLTF
20.28
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.555
TVALTFEXP_TVA->PJM
CLTF
10.606
CPLELTFEXP_CPLE->PJM
CLTF
6.226
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.111
NYPJM->LTFIMP_NY
CLTF
3.248
LGEELTFEXP_LGEE->PJM
CLTF
6.763
WECLTFEXP_WEC->PJM
CLTF
3.371
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.415
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.315
MECLTFEXP_MEC->PJM
CLTF
15.415
SIGELTFEXP_SIGE->PJM
CLTF
0.508

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-020_SRT-SL


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.02 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4224.55
MW Contribution:17.64
Bus #Bus NameTypeMW Contribution
971543AH1-269 GEN
50/50
12.267
966391AG1-508 GEN
Solar/Wind Harmer
6.388
270069AE2-166 C O1
Solar/Wind Harmer
4.514
971313AH1-133 GEN
Solar/Wind Harmer
15.745
24734705WLF1G3
Adder
8.22
24734805WLF1G4
Adder
8.22
24734905WLF1G5
Adder
8.22
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.049
270399AC1-101 GEN
Solar/Wind Harmer
5.58
270400AC1-102 GEN
Solar/Wind Harmer
5.58
941621AE2-160 GEN
Adder
4.308
957241AF2-018 GEN
Solar/Wind Harmer
5.782
970281AG2-184 GEN
Solar/Wind Harmer
27.237
972143AH1-644 GEN
Solar/Wind Harmer
12.97
971981AH1-535 GEN
Solar/Wind Harmer
12.604
962211AG1-066 GEN
Solar/Wind Harmer
3.014
971061AG2-657 GEN
Solar/Wind Harmer
11.059
24477305BRIDGE
Adder
0.422
972203AH1-686 GEN
Adder
2.718
270330AC1-082 GEN2
Solar/Wind Harmer
0.83
270329AC1-082 GEN1
Solar/Wind Harmer
0.489
965401AG1-405 GEN
Solar/Wind Harmer
6.089
965411AG1-406 GEN
Solar/Wind Harmer
2.733
339211AE2-254 GEN
Solar/Wind Harmer
1.572
3429211JKCT 2G
Adder
11.941
970455AG2-298 GEN
Solar/Wind Harmer
6.067
339243AC2-075 GEN1
Solar/Wind Harmer
0.449
972163AH1-664 GEN
Solar/Wind Harmer
9.805
972165AH1-665 GEN
Solar/Wind Harmer
7.844
971985AH1-537 GEN
Solar/Wind Harmer
17.415
270367AC2-061_GEN
Solar/Wind Harmer
3.029
316123AC1-075 GEN
Solar/Wind Harmer
1.494
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.255
25196108MFTGT2
Adder
1.435
25196108MFTGT2
Adder
1.332
970879AG2-548 GEN
Solar/Wind Harmer
3.978
944221AF1-090 GEN
Solar/Wind Harmer
10.083
252524AE2-267 GEN
Solar/Wind Harmer
1.454
25196408WSDLE3
Adder
8.135
25196308WSDLE2
Adder
8.064
25196208WSDLE1
Adder
8.044
25196708WSDLE6
Adder
8.024
25196508WSDLE4
Adder
7.822
276785W4-005 GEN1
Solar/Wind Harmer
2.743
276174W4-005 GEN2
Solar/Wind Harmer
2.743
276849AB2-070 GEN2
Solar/Wind Harmer
2.04
276848AB2-070 GEN3
Solar/Wind Harmer
2.04
274823ROCKFORD ;21
Adder
17.257
274746AC1-111 G10
Adder
4.901
274744AC1-111 GEN8
Adder
4.901
25306009OHH W.
Adder
2.523
253372AE2-315 SEC3
Adder
1.658
253372AE2-315 SEC3
Adder
1.658
3148463FAIRFLD
Solar/Wind Helper
0.727
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.301
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.079
316164AC1-076 GEN
Solar/Wind Helper
1.177
238152AF2-075_GEN
Solar/Wind Helper
0.605
316312AB1-027
Solar/Wind Helper
0.425
3141426STAFORD
Solar/Wind Helper
0.049
24290605CLAY-1
50/50
0.256
24290605CLAY-1
50/50
0.256
24290705CLAY-2
50/50
0.256
24290705CLAY-2
50/50
0.256
24684405SMG2
50/50
2.226
24684505SMG3
50/50
1.377
24684305SMG1
50/50
0.807
270583AD2-179 GEN
Solar/Wind Harmer
20.758
270214AC2-123 GEN
Solar/Wind Harmer
4.319
971277AH1-098 GEN
Solar/Wind Harmer
7.435
316217AC1-145 GEN
Solar/Wind Harmer
4.25
316197AC1-042 GEN
Solar/Wind Harmer
3.222
942671AE2-283 GEN
Solar/Wind Harmer
8.674
24728205BUCHG1
Adder
6.772
270013AE1-250 PV
Solar/Wind Harmer
3.259
971225AH1-072 GEN
Solar/Wind Harmer
2.74
971227AH1-073 GEN
Solar/Wind Harmer
2.74
944971AF1-162 GEN
Solar/Wind Harmer
9.108
24723005RIVRG1
Adder
23.068
24723105RIVRG2
Adder
23.068
24685805CER G1
Adder
9.875
24685905CER G2
Adder
9.875
942751AE2-291 GEN
Solar/Wind Harmer
10.391
966021AG1-471 GEN
Solar/Wind Harmer
5.779
971485AH1-239 GEN
Solar/Wind Harmer
8.537
339231AF1-038_GEN
Solar/Wind Harmer
1.927
960161AF2-307 GEN
Solar/Wind Harmer
6.695
339255AE2-071 GEN
Solar/Wind Harmer
1.104
964781AG1-341 GEN
Solar/Wind Harmer
11.023
339236AF1-050_GEN
Solar/Wind Harmer
1.882
971081AG2-670 GEN
Solar/Wind Harmer
7.773
942891AE2-308 GEN
Solar/Wind Harmer
10.233
970653AG2-424 GEN
Solar/Wind Harmer
4.906
970653AG2-424 GEN
Solar/Wind Harmer
1.774
964571AG1-320 GEN
Solar/Wind Harmer
8.231
971125AH1-004 GEN
Solar/Wind Harmer
4.003
970107AG2-081 GEN
Solar/Wind Harmer
3.003
972043AH1-570 GEN
Solar/Wind Harmer
2.49
972045AH1-571 GEN
Solar/Wind Harmer
1.992
339221AD2-048_GEN
Solar/Wind Harmer
1.523
970235AG2-159 GEN
Solar/Wind Harmer
3.901
970235AG2-159 GEN
Solar/Wind Harmer
2.382
270186AC1-089 GEN
Solar/Wind Harmer
5.863
970239AG2-162 GEN
Solar/Wind Harmer
10.536
962581AG1-107 GEN
Solar/Wind Harmer
4.763
961491AF2-440 GEN
Solar/Wind Harmer
1.98
270444AC2-157 GEN1
Solar/Wind Harmer
5.271
252509AD1-136 GEN
Solar/Wind Harmer
0.24
25183208HLCRTG
Solar/Wind Harmer
5.62
252519AF1-045_GEN
Solar/Wind Harmer
5.628
252516AE2-318_GEN
Solar/Wind Harmer
4.293
970879AG2-548 GEN
Solar/Wind Harmer
5.702
971073AG2-665 GEN
Solar/Wind Harmer
5.702
971073AG2-665 GEN
Solar/Wind Harmer
3.978
25194408D.CRK1
Adder
6.985
25194508D.CRK3
Adder
1.306
945391AF1-204 GEN
Solar/Wind Harmer
12.796
276916AD2-100_GEN
Solar/Wind Harmer
19.269
276911AD2-131_GEN
Solar/Wind Harmer
3.894
957381AF2-032 GEN
Solar/Wind Harmer
0.383
253317AC1-085 GEN4
Solar/Wind Harmer
7.655
276763AC1-053 GEN1
Solar/Wind Harmer
3.59
276764AC1-053 GEN2
Solar/Wind Harmer
3.59
970241AG2-163 GEN
Solar/Wind Harmer
22.567
24728805RICHG1
Adder
3.406
24728905RICHG2
Adder
3.406
972267AH1-718 GEN
Adder
3.711
274764LEE CO EC;5U
Adder
8.292
274765LEE CO EC;6U
Adder
8.292
274762LEE CO EC;3U
Adder
8.273
274763LEE CO EC;4U
Adder
8.195
274683WAUKEGAN ;8U
Adder
18.536
274683WAUKEGAN ;8U
Adder
15.625
274696ROCKY RD ;4P
Adder
10.02
274695ROCKY RD ;2P
Adder
9.789
274693ROCKY RD ;1P
Adder
9.693
274697ROCKY RD ;3P
Adder
2.659
253370AE2-315 SEC1
Adder
1.753
3132123MT JACKSON
Solar/Wind Helper
1.392
315821AE2-092 GEN
Solar/Wind Helper
3.222
966001AG1-469 GEN
Solar/Wind Helper
0.321
315651AD1-115 GEN
Solar/Wind Helper
0.841
316447AC1-158 HLD
Solar/Wind Helper
2.779
966871AG1-558 GEN
Solar/Wind Helper
0.307
316468AD1-105 GEN
Solar/Wind Helper
1.129
970823AG2-518 GEN
50/50
8.396
247619Y1-049
50/50
0.915
24684705SMG5
50/50
0.857
970481AG2-311 GEN
50/50
11.948
24728405LEESVG
50/50
0.296
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.959
962751AG1-124 GEN
Solar/Wind Harmer
18.84
958121AF2-106 GEN
Solar/Wind Harmer
9.423
270173AC1-122 GEN
Solar/Wind Harmer
3.281
971331AH1-145 GEN
Solar/Wind Harmer
18.398
943031AE2-326 GEN
Solar/Wind Harmer
6.798
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.82
270574AD1-017 GEN2
Solar/Wind Harmer
8.482
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.986
270030AE2-140 GEN
Solar/Wind Harmer
30.98
960911AF2-382 GEN
Solar/Wind Harmer
10.985
270016AE1-250 BESS
Solar/Wind Harmer
3.259
970913AG2-568 GEN
Solar/Wind Harmer
11.054
971461AH1-227 GEN
Solar/Wind Harmer
7.029
970223AG2-152 GEN
Solar/Wind Harmer
17.643
270053AF1-130 C
Solar/Wind Harmer
4.837
972103AH1-617 GEN
Solar/Wind Harmer
25.94
24686205CER G4
Adder
9.888
24686405CER G5
Adder
9.849
972273AH1-721 GEN
Adder
89.748
24721905FLATG4
Adder
21.813
970273AG2-179 GEN
Solar/Wind Harmer
4.143
339250AF1-203 GEN
Solar/Wind Harmer
0.631
971155AH1-034 GEN
Solar/Wind Harmer
10.404
966571AG1-526 GEN
Solar/Wind Harmer
23.009
962251AG1-071 GEN
Solar/Wind Harmer
5.699
970093AG2-073 GEN
Solar/Wind Harmer
10.328
960741AF2-365 GEN
Solar/Wind Harmer
5.133
971191AH1-055 GEN
Solar/Wind Harmer
22.339
3429391JKCT 9G
Adder
8.45
972167AH1-666 GEN
Solar/Wind Harmer
7.817
957541AF2-048 GEN
Solar/Wind Harmer
1.539
958171AF2-111 GEN
Solar/Wind Harmer
24.064
970243AG2-164 GEN
Solar/Wind Harmer
24.738
970519AG2-331 GEN
Solar/Wind Harmer
16.62
970699AG2-449 GEN
Solar/Wind Harmer
10.995
25196008MFTGT1
Adder
1.261
252510AF1-249 C
Solar/Wind Harmer
0.387
25194608D.CRK4
Adder
1.519
25196608WSDLE5
Adder
7.903
970193AG2-126 GEN
Solar/Wind Harmer
13.773
942481AE2-261 GEN
Solar/Wind Harmer
27.393
253316AC1-085 GEN3
Solar/Wind Harmer
7.655
253433AC1-085 GEN1
Solar/Wind Harmer
4.859
946181AF1-283 GEN
Solar/Wind Harmer
11.881
24728705AND G3
Adder
7.324
24728505AND G1
Adder
3.502
276621W2-048 GEN
Solar/Wind Harmer
5.679
276838X2-022 GEN2
Solar/Wind Harmer
0.212
276686W4-005 GEN3
Solar/Wind Harmer
2.743
276668AB2-070 GEN1
Solar/Wind Harmer
2.04
971993AH1-541 GEN
Solar/Wind Harmer
8.379
253406AD2-031_GEN
Solar/Wind Harmer
1.157
270356AE2-297 GEN
Solar/Wind Harmer
4.125
274760LEE CO EC;1U
Adder
8.273
274767LEE CO EC;8U
Adder
8.175
972236AH1-702 GEN2
Adder
1.942
274682WAUKEGAN ;7U
Adder
15.803
253370AE2-315 SEC1
Adder
1.753
253371AE2-315 SEC2
Adder
1.658
274729ELWOOD EC;1P
Adder
1.688
3147983MERCK5
Solar/Wind Helper
0.199
316192AB2-158 GEN
Solar/Wind Helper
1.845
3147666LOUISA
Solar/Wind Helper
1.091
316254AC1-120 GEN1
Solar/Wind Helper
1.164
316097T157 G90
Solar/Wind Helper
1.133
238148AE2-230_GEN2
Solar/Wind Helper
0.425
316336AC2-165 C
Solar/Wind Helper
1.289
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.042
3142416OLDCHRC
Solar/Wind Helper
0.58
3142416OLDCHRC
Solar/Wind Helper
0.222
970479AG2-310 GEN
50/50
20.278
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.241
966251AG1-494 GEN
50/50
4.391
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
7.012
971329AH1-144 GEN
Solar/Wind Harmer
23.734
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
9.82
270197AD1-017 GEN1
Solar/Wind Harmer
2.549
270336AE1-100 GEN
Solar/Wind Harmer
2.762
943811AF1-049 GEN
Solar/Wind Harmer
5.705
24728305BUCHG2
Adder
6.772
270018AE2-047 C O1
Solar/Wind Harmer
1.828
958131AF2-107 GEN
Solar/Wind Harmer
7.112
24735205WLF2G2
Adder
8.049
971687AH1-348 GEN
Solar/Wind Harmer
1.364
971403AH1-188 GEN
Solar/Wind Harmer
18.932
24723205RIVRG3
Adder
23.068
971315AH1-136 GEN
Solar/Wind Harmer
2.441
24686105CER G3
Adder
9.94
24686505CER G6
Adder
9.927
270331AC1-082 GEN3
Solar/Wind Harmer
0.49
970947AG2-589 GEN
Solar/Wind Harmer
2.153
24721705FLATG2
Adder
21.813
970273AG2-179 GEN
Solar/Wind Harmer
2.594
971821AH1-427 GEN
Solar/Wind Harmer
10.401
964901AG1-354 GEN
Solar/Wind Harmer
15.577
960001AF2-291 GEN
Solar/Wind Harmer
3.136
339241AF1-083 GEN
Solar/Wind Harmer
1.723
962241AG1-070 GEN
Solar/Wind Harmer
4.662
3429241JKCT 3G
Adder
12.097
3429421JKCT 10G
Adder
8.45
971565AH1-281 GEN
Solar/Wind Harmer
2.012
943111AE2-339 GEN
Solar/Wind Harmer
0.888
339216AC1-074 GEN
Solar/Wind Harmer
1.659
945681AF1-233 GEN
Solar/Wind Harmer
18.436
927014AC1-188 GEN
Solar/Wind Harmer
1.543
970091AG2-072 GEN
Adder
74.457
970333AG2-219 GEN
Solar/Wind Harmer
30.235
270445AC2-157 GEN2
Solar/Wind Harmer
5.271
25196808ZIMRHP
Adder
71.09
252507AC2-088 GEN
Solar/Wind Harmer
1.681
25196008MFTGT1
Adder
1.302
25194608D.CRK4
Adder
1.519
965911AG1-460 GEN
Solar/Wind Harmer
1.278
253432AC1-085 GEN2
Solar/Wind Harmer
0.245
946171AF1-282 GEN
Solar/Wind Harmer
9.139
24728605AND G2
Adder
3.502
276615X2-022 GEN
Solar/Wind Harmer
1.783
963831AG1-236 GEN
Solar/Wind Harmer
8.931
274880W4-005 GEN4
Solar/Wind Harmer
2.743
963741AG1-226 GEN
Solar/Wind Harmer
40.621
274761LEE CO EC;2U
Adder
8.273
274766LEE CO EC;7U
Adder
8.175
972235AH1-702 GEN1
Adder
2.234
274822ROCKFORD ;11
Adder
17.383
274828WAUKEGAN ;BP
Adder
9.716
274682WAUKEGAN ;7U
Adder
15.803
274745AC1-111 GEN9
Adder
4.901
253370AE2-315 SEC1
Adder
1.753
253371AE2-315 SEC2
Adder
1.658
315616AA1-038_C
Solar/Wind Helper
3.295
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.727
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.628
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.388
23583801GRNGAP
Solar/Wind Helper
4.315
316095T157 G97
Solar/Wind Helper
1.133
238147AE2-230_GEN1
Solar/Wind Helper
0.423
238149AF1-291A_GEN
Solar/Wind Helper
0.121
966881AG1-559 GEN
Solar/Wind Helper
0.314
316313AB2-026
Solar/Wind Helper
0.355
316258AE1-075 C
Solar/Wind Helper
0.319
316405AF2-144 C
Solar/Wind Helper
0.266
316044AC1-158 PL1
Solar/Wind Helper
1.263
316450AC1-158 RIC
Solar/Wind Helper
0.337
316473AC1-191 GEN
Solar/Wind Helper
1.391
972175AH1-670 GEN
Solar/Wind Harmer
4.749
944201AF1-088_MTX
Adder
109.749
957141AF2-008_MTX
Adder
54.874
LAGNLTFEXP_LAGN->PJM
CLTF
20.369
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.617
TVALTFEXP_TVA->PJM
CLTF
10.651
CPLELTFEXP_CPLE->PJM
CLTF
6.237
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.77
NYPJM->LTFIMP_NY
CLTF
3.272
LGEELTFEXP_LGEE->PJM
CLTF
6.802
WECLTFEXP_WEC->PJM
CLTF
3.393
AG2-052LTFEXP_AG2-052->PJM
LTF
0.203
AH1-155LTFEXP_AH1-155->PJM
LTF
0.304
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.199
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.491
MECLTFEXP_MEC->PJM
CLTF
15.504
SIGELTFEXP_SIGE->PJM
CLTF
0.511

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-021_SRT-SL


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.77 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4215.43
MW Contribution:17.63
Bus #Bus NameTypeMW Contribution
971543AH1-269 GEN
50/50
12.253
966391AG1-508 GEN
Solar/Wind Harmer
6.379
270069AE2-166 C O1
Solar/Wind Harmer
4.509
971313AH1-133 GEN
Solar/Wind Harmer
15.712
24734705WLF1G3
Adder
8.202
24734805WLF1G4
Adder
8.202
24734905WLF1G5
Adder
8.202
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.031
270399AC1-101 GEN
Solar/Wind Harmer
5.563
270400AC1-102 GEN
Solar/Wind Harmer
5.563
941621AE2-160 GEN
Adder
4.292
957241AF2-018 GEN
Solar/Wind Harmer
5.764
970281AG2-184 GEN
Solar/Wind Harmer
27.16
972143AH1-644 GEN
Solar/Wind Harmer
12.933
971981AH1-535 GEN
Solar/Wind Harmer
12.575
962211AG1-066 GEN
Solar/Wind Harmer
3.005
971061AG2-657 GEN
Solar/Wind Harmer
11.012
24477305BRIDGE
Adder
0.42
972203AH1-686 GEN
Adder
2.709
270330AC1-082 GEN2
Solar/Wind Harmer
0.826
270329AC1-082 GEN1
Solar/Wind Harmer
0.486
965401AG1-405 GEN
Solar/Wind Harmer
6.068
965411AG1-406 GEN
Solar/Wind Harmer
2.724
339211AE2-254 GEN
Solar/Wind Harmer
1.566
3429211JKCT 2G
Adder
11.894
970455AG2-298 GEN
Solar/Wind Harmer
6.044
339243AC2-075 GEN1
Solar/Wind Harmer
0.447
972163AH1-664 GEN
Solar/Wind Harmer
9.762
972165AH1-665 GEN
Solar/Wind Harmer
7.81
971985AH1-537 GEN
Solar/Wind Harmer
17.332
270367AC2-061_GEN
Solar/Wind Harmer
3.015
316123AC1-075 GEN
Solar/Wind Harmer
1.493
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.254
25196108MFTGT2
Adder
1.428
25196108MFTGT2
Adder
1.326
970879AG2-548 GEN
Solar/Wind Harmer
3.956
944221AF1-090 GEN
Solar/Wind Harmer
10.042
252524AE2-267 GEN
Solar/Wind Harmer
1.447
25196408WSDLE3
Adder
8.097
25196308WSDLE2
Adder
8.027
25196208WSDLE1
Adder
8.006
25196708WSDLE6
Adder
7.986
25196508WSDLE4
Adder
7.785
276849AB2-070 GEN2
Solar/Wind Harmer
2.031
276848AB2-070 GEN3
Solar/Wind Harmer
2.031
276785W4-005 GEN1
Solar/Wind Harmer
2.731
276174W4-005 GEN2
Solar/Wind Harmer
2.731
274823ROCKFORD ;21
Adder
17.182
274746AC1-111 G10
Adder
4.879
274744AC1-111 GEN8
Adder
4.879
25306009OHH W.
Adder
2.51
253372AE2-315 SEC3
Adder
1.649
253372AE2-315 SEC3
Adder
1.649
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.079
316164AC1-076 GEN
Solar/Wind Helper
1.173
238152AF2-075_GEN
Solar/Wind Helper
0.603
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684405SMG2
50/50
2.225
24684505SMG3
50/50
1.376
24684305SMG1
50/50
0.806
270583AD2-179 GEN
Solar/Wind Harmer
20.732
270214AC2-123 GEN
Solar/Wind Harmer
4.313
971277AH1-098 GEN
Solar/Wind Harmer
7.425
316217AC1-145 GEN
Solar/Wind Harmer
4.248
316197AC1-042 GEN
Solar/Wind Harmer
3.22
942671AE2-283 GEN
Solar/Wind Harmer
8.669
24728205BUCHG1
Adder
6.757
270013AE1-250 PV
Solar/Wind Harmer
3.257
971225AH1-072 GEN
Solar/Wind Harmer
2.733
971227AH1-073 GEN
Solar/Wind Harmer
2.733
944971AF1-162 GEN
Solar/Wind Harmer
9.08
24723005RIVRG1
Adder
22.989
24723105RIVRG2
Adder
22.989
24685805CER G1
Adder
9.838
24685905CER G2
Adder
9.838
942751AE2-291 GEN
Solar/Wind Harmer
10.387
966021AG1-471 GEN
Solar/Wind Harmer
5.761
971485AH1-239 GEN
Solar/Wind Harmer
8.509
339231AF1-038_GEN
Solar/Wind Harmer
1.921
960161AF2-307 GEN
Solar/Wind Harmer
6.669
339255AE2-071 GEN
Solar/Wind Harmer
1.1
964781AG1-341 GEN
Solar/Wind Harmer
10.986
339236AF1-050_GEN
Solar/Wind Harmer
1.875
971081AG2-670 GEN
Solar/Wind Harmer
7.746
942891AE2-308 GEN
Solar/Wind Harmer
10.193
970653AG2-424 GEN
Solar/Wind Harmer
4.888
970653AG2-424 GEN
Solar/Wind Harmer
1.767
964571AG1-320 GEN
Solar/Wind Harmer
8.199
971125AH1-004 GEN
Solar/Wind Harmer
3.987
970107AG2-081 GEN
Solar/Wind Harmer
2.99
972043AH1-570 GEN
Solar/Wind Harmer
2.479
972045AH1-571 GEN
Solar/Wind Harmer
1.983
339221AD2-048_GEN
Solar/Wind Harmer
1.517
970235AG2-159 GEN
Solar/Wind Harmer
3.885
970235AG2-159 GEN
Solar/Wind Harmer
2.372
270186AC1-089 GEN
Solar/Wind Harmer
5.836
970239AG2-162 GEN
Solar/Wind Harmer
10.492
962581AG1-107 GEN
Solar/Wind Harmer
4.741
961491AF2-440 GEN
Solar/Wind Harmer
1.97
270444AC2-157 GEN1
Solar/Wind Harmer
5.249
252509AD1-136 GEN
Solar/Wind Harmer
0.239
25183208HLCRTG
Solar/Wind Harmer
5.594
252519AF1-045_GEN
Solar/Wind Harmer
5.601
252516AE2-318_GEN
Solar/Wind Harmer
4.272
970879AG2-548 GEN
Solar/Wind Harmer
5.67
971073AG2-665 GEN
Solar/Wind Harmer
5.67
971073AG2-665 GEN
Solar/Wind Harmer
3.956
25194408D.CRK1
Adder
6.953
25194508D.CRK3
Adder
1.3
945391AF1-204 GEN
Solar/Wind Harmer
12.742
276916AD2-100_GEN
Solar/Wind Harmer
19.19
276911AD2-131_GEN
Solar/Wind Harmer
3.878
957381AF2-032 GEN
Solar/Wind Harmer
0.382
253317AC1-085 GEN4
Solar/Wind Harmer
7.618
276763AC1-053 GEN1
Solar/Wind Harmer
3.575
276764AC1-053 GEN2
Solar/Wind Harmer
3.575
970241AG2-163 GEN
Solar/Wind Harmer
22.469
24728805RICHG1
Adder
3.391
24728905RICHG2
Adder
3.391
972267AH1-718 GEN
Adder
3.695
274764LEE CO EC;5U
Adder
8.257
274765LEE CO EC;6U
Adder
8.257
274762LEE CO EC;3U
Adder
8.237
274763LEE CO EC;4U
Adder
8.16
274683WAUKEGAN ;8U
Adder
18.455
274683WAUKEGAN ;8U
Adder
15.556
274696ROCKY RD ;4P
Adder
9.976
274695ROCKY RD ;2P
Adder
9.746
274693ROCKY RD ;1P
Adder
9.65
274697ROCKY RD ;3P
Adder
2.648
253370AE2-315 SEC1
Adder
1.744
3132123MT JACKSON
Solar/Wind Helper
1.39
315821AE2-092 GEN
Solar/Wind Helper
3.218
966001AG1-469 GEN
Solar/Wind Helper
0.32
315651AD1-115 GEN
Solar/Wind Helper
0.839
966871AG1-558 GEN
Solar/Wind Helper
0.306
316447AC1-158 HLD
Solar/Wind Helper
2.77
316468AD1-105 GEN
Solar/Wind Helper
1.126
970823AG2-518 GEN
50/50
8.387
247619Y1-049
50/50
0.914
24684705SMG5
50/50
0.857
970481AG2-311 GEN
50/50
11.94
24728405LEESVG
50/50
0.296
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.869
962751AG1-124 GEN
Solar/Wind Harmer
18.829
958121AF2-106 GEN
Solar/Wind Harmer
9.412
270173AC1-122 GEN
Solar/Wind Harmer
3.279
971331AH1-145 GEN
Solar/Wind Harmer
18.373
943031AE2-326 GEN
Solar/Wind Harmer
6.789
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.814
270574AD1-017 GEN2
Solar/Wind Harmer
8.476
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.951
270030AE2-140 GEN
Solar/Wind Harmer
30.945
960911AF2-382 GEN
Solar/Wind Harmer
10.959
270016AE1-250 BESS
Solar/Wind Harmer
3.257
970913AG2-568 GEN
Solar/Wind Harmer
11.019
971461AH1-227 GEN
Solar/Wind Harmer
7.011
970223AG2-152 GEN
Solar/Wind Harmer
17.629
270053AF1-130 C
Solar/Wind Harmer
4.822
972103AH1-617 GEN
Solar/Wind Harmer
25.867
24686205CER G4
Adder
9.851
24686405CER G5
Adder
9.812
972273AH1-721 GEN
Adder
89.448
24721905FLATG4
Adder
21.725
970273AG2-179 GEN
Solar/Wind Harmer
4.129
339250AF1-203 GEN
Solar/Wind Harmer
0.629
971155AH1-034 GEN
Solar/Wind Harmer
10.369
966571AG1-526 GEN
Solar/Wind Harmer
22.923
962251AG1-071 GEN
Solar/Wind Harmer
5.679
970093AG2-073 GEN
Solar/Wind Harmer
10.289
960741AF2-365 GEN
Solar/Wind Harmer
5.115
3429391JKCT 9G
Adder
8.417
971191AH1-055 GEN
Solar/Wind Harmer
22.23
972167AH1-666 GEN
Solar/Wind Harmer
7.783
957541AF2-048 GEN
Solar/Wind Harmer
1.531
958171AF2-111 GEN
Solar/Wind Harmer
23.957
970243AG2-164 GEN
Solar/Wind Harmer
24.633
970519AG2-331 GEN
Solar/Wind Harmer
16.549
970699AG2-449 GEN
Solar/Wind Harmer
10.948
25196008MFTGT1
Adder
1.255
252510AF1-249 C
Solar/Wind Harmer
0.385
25194608D.CRK4
Adder
1.511
25196608WSDLE5
Adder
7.866
970193AG2-126 GEN
Solar/Wind Harmer
13.715
942481AE2-261 GEN
Solar/Wind Harmer
27.279
253316AC1-085 GEN3
Solar/Wind Harmer
7.618
253433AC1-085 GEN1
Solar/Wind Harmer
4.836
946181AF1-283 GEN
Solar/Wind Harmer
11.823
24728705AND G3
Adder
7.292
24728505AND G1
Adder
3.486
276621W2-048 GEN
Solar/Wind Harmer
5.656
276838X2-022 GEN2
Solar/Wind Harmer
0.211
276668AB2-070 GEN1
Solar/Wind Harmer
2.031
276686W4-005 GEN3
Solar/Wind Harmer
2.731
971993AH1-541 GEN
Solar/Wind Harmer
8.344
270356AE2-297 GEN
Solar/Wind Harmer
4.106
253406AD2-031_GEN
Solar/Wind Harmer
1.151
274760LEE CO EC;1U
Adder
8.237
274767LEE CO EC;8U
Adder
8.14
972236AH1-702 GEN2
Adder
1.934
274682WAUKEGAN ;7U
Adder
15.734
253370AE2-315 SEC1
Adder
1.744
253371AE2-315 SEC2
Adder
1.649
274729ELWOOD EC;1P
Adder
1.681
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.84
3147666LOUISA
Solar/Wind Helper
1.089
316254AC1-120 GEN1
Solar/Wind Helper
1.161
316097T157 G90
Solar/Wind Helper
1.128
238148AE2-230_GEN2
Solar/Wind Helper
0.424
316336AC2-165 C
Solar/Wind Helper
1.286
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.029
970479AG2-310 GEN
50/50
20.262
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
966251AG1-494 GEN
50/50
4.389
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
7.006
971329AH1-144 GEN
Solar/Wind Harmer
23.701
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
9.814
270197AD1-017 GEN1
Solar/Wind Harmer
2.547
270336AE1-100 GEN
Solar/Wind Harmer
2.759
943811AF1-049 GEN
Solar/Wind Harmer
5.698
24728305BUCHG2
Adder
6.757
270018AE2-047 C O1
Solar/Wind Harmer
1.826
958131AF2-107 GEN
Solar/Wind Harmer
7.109
24735205WLF2G2
Adder
8.031
971687AH1-348 GEN
Solar/Wind Harmer
1.36
971403AH1-188 GEN
Solar/Wind Harmer
18.877
24723205RIVRG3
Adder
22.989
971315AH1-136 GEN
Solar/Wind Harmer
2.433
24686105CER G3
Adder
9.903
24686505CER G6
Adder
9.89
270331AC1-082 GEN3
Solar/Wind Harmer
0.488
24721705FLATG2
Adder
21.725
970947AG2-589 GEN
Solar/Wind Harmer
2.143
970273AG2-179 GEN
Solar/Wind Harmer
2.585
971821AH1-427 GEN
Solar/Wind Harmer
10.363
964901AG1-354 GEN
Solar/Wind Harmer
15.523
339241AF1-083 GEN
Solar/Wind Harmer
1.717
962241AG1-070 GEN
Solar/Wind Harmer
4.647
960001AF2-291 GEN
Solar/Wind Harmer
3.12
3429241JKCT 3G
Adder
12.05
3429421JKCT 10G
Adder
8.417
971565AH1-281 GEN
Solar/Wind Harmer
2.004
943111AE2-339 GEN
Solar/Wind Harmer
0.884
339216AC1-074 GEN
Solar/Wind Harmer
1.652
945681AF1-233 GEN
Solar/Wind Harmer
18.356
927014AC1-188 GEN
Solar/Wind Harmer
1.535
970091AG2-072 GEN
Adder
74.149
970333AG2-219 GEN
Solar/Wind Harmer
30.107
270445AC2-157 GEN2
Solar/Wind Harmer
5.249
25196808ZIMRHP
Adder
70.761
252507AC2-088 GEN
Solar/Wind Harmer
1.673
25196008MFTGT1
Adder
1.296
25194608D.CRK4
Adder
1.511
965911AG1-460 GEN
Solar/Wind Harmer
1.273
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
946171AF1-282 GEN
Solar/Wind Harmer
9.095
24728605AND G2
Adder
3.486
276615X2-022 GEN
Solar/Wind Harmer
1.776
963831AG1-236 GEN
Solar/Wind Harmer
8.893
274880W4-005 GEN4
Solar/Wind Harmer
2.731
963741AG1-226 GEN
Solar/Wind Harmer
40.444
274761LEE CO EC;2U
Adder
8.237
274766LEE CO EC;7U
Adder
8.14
972235AH1-702 GEN1
Adder
2.224
274822ROCKFORD ;11
Adder
17.308
274828WAUKEGAN ;BP
Adder
9.674
274682WAUKEGAN ;7U
Adder
15.734
274745AC1-111 GEN9
Adder
4.879
253370AE2-315 SEC1
Adder
1.744
253371AE2-315 SEC2
Adder
1.649
315616AA1-038_C
Solar/Wind Helper
3.294
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.725
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.626
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.387
23583801GRNGAP
Solar/Wind Helper
4.296
316095T157 G97
Solar/Wind Helper
1.128
238147AE2-230_GEN1
Solar/Wind Helper
0.422
238149AF1-291A_GEN
Solar/Wind Helper
0.12
966881AG1-559 GEN
Solar/Wind Helper
0.314
316313AB2-026
Solar/Wind Helper
0.354
316258AE1-075 C
Solar/Wind Helper
0.319
316405AF2-144 C
Solar/Wind Helper
0.266
316473AC1-191 GEN
Solar/Wind Helper
1.388
316044AC1-158 PL1
Solar/Wind Helper
1.259
316450AC1-158 RIC
Solar/Wind Helper
0.336
972175AH1-670 GEN
Solar/Wind Harmer
4.729
944201AF1-088_MTX
Adder
109.291
957141AF2-008_MTX
Adder
54.646
LAGNLTFEXP_LAGN->PJM
CLTF
20.308
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.574
TVALTFEXP_TVA->PJM
CLTF
10.62
CPLELTFEXP_CPLE->PJM
CLTF
6.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.312
NYPJM->LTFIMP_NY
CLTF
3.255
LGEELTFEXP_LGEE->PJM
CLTF
6.775
WECLTFEXP_WEC->PJM
CLTF
3.378
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.655
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.369
MECLTFEXP_MEC->PJM
CLTF
15.442
SIGELTFEXP_SIGE->PJM
CLTF
0.509

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.68 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4211.98
MW Contribution:17.62
Bus #Bus NameTypeMW Contribution
971543AH1-269 GEN
50/50
12.247
966391AG1-508 GEN
Solar/Wind Harmer
6.374
270069AE2-166 C O1
Solar/Wind Harmer
4.507
971313AH1-133 GEN
Solar/Wind Harmer
15.698
24734705WLF1G3
Adder
8.194
24734805WLF1G4
Adder
8.194
24734905WLF1G5
Adder
8.194
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.023
270399AC1-101 GEN
Solar/Wind Harmer
5.556
270400AC1-102 GEN
Solar/Wind Harmer
5.556
941621AE2-160 GEN
Adder
4.285
957241AF2-018 GEN
Solar/Wind Harmer
5.757
970281AG2-184 GEN
Solar/Wind Harmer
27.126
972143AH1-644 GEN
Solar/Wind Harmer
12.917
971981AH1-535 GEN
Solar/Wind Harmer
12.563
962211AG1-066 GEN
Solar/Wind Harmer
3.001
971061AG2-657 GEN
Solar/Wind Harmer
10.991
24477305BRIDGE
Adder
0.419
972203AH1-686 GEN
Adder
2.704
270330AC1-082 GEN2
Solar/Wind Harmer
0.824
270329AC1-082 GEN1
Solar/Wind Harmer
0.485
965401AG1-405 GEN
Solar/Wind Harmer
6.059
965411AG1-406 GEN
Solar/Wind Harmer
2.719
339211AE2-254 GEN
Solar/Wind Harmer
1.563
3429211JKCT 2G
Adder
11.873
970455AG2-298 GEN
Solar/Wind Harmer
6.034
339243AC2-075 GEN1
Solar/Wind Harmer
0.446
972163AH1-664 GEN
Solar/Wind Harmer
9.743
972165AH1-665 GEN
Solar/Wind Harmer
7.794
971985AH1-537 GEN
Solar/Wind Harmer
17.295
270367AC2-061_GEN
Solar/Wind Harmer
3.009
316123AC1-075 GEN
Solar/Wind Harmer
1.493
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.254
25196108MFTGT2
Adder
1.425
25196108MFTGT2
Adder
1.324
970879AG2-548 GEN
Solar/Wind Harmer
3.946
944221AF1-090 GEN
Solar/Wind Harmer
10.024
252524AE2-267 GEN
Solar/Wind Harmer
1.444
25196408WSDLE3
Adder
8.08
25196308WSDLE2
Adder
8.01
25196208WSDLE1
Adder
7.99
25196708WSDLE6
Adder
7.97
25196508WSDLE4
Adder
7.769
276785W4-005 GEN1
Solar/Wind Harmer
2.726
276174W4-005 GEN2
Solar/Wind Harmer
2.726
276849AB2-070 GEN2
Solar/Wind Harmer
2.027
276848AB2-070 GEN3
Solar/Wind Harmer
2.027
274823ROCKFORD ;21
Adder
17.15
274746AC1-111 G10
Adder
4.87
274744AC1-111 GEN8
Adder
4.87
25306009OHH W.
Adder
2.505
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.313
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.078
316164AC1-076 GEN
Solar/Wind Helper
1.172
238152AF2-075_GEN
Solar/Wind Helper
0.602
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684405SMG2
50/50
2.224
24684505SMG3
50/50
1.376
24684305SMG1
50/50
0.806
270583AD2-179 GEN
Solar/Wind Harmer
20.721
270214AC2-123 GEN
Solar/Wind Harmer
4.311
971277AH1-098 GEN
Solar/Wind Harmer
7.42
316217AC1-145 GEN
Solar/Wind Harmer
4.247
316197AC1-042 GEN
Solar/Wind Harmer
3.219
942671AE2-283 GEN
Solar/Wind Harmer
8.667
24728205BUCHG1
Adder
6.75
270013AE1-250 PV
Solar/Wind Harmer
3.256
971225AH1-072 GEN
Solar/Wind Harmer
2.73
971227AH1-073 GEN
Solar/Wind Harmer
2.73
944971AF1-162 GEN
Solar/Wind Harmer
9.068
24723005RIVRG1
Adder
22.954
24723105RIVRG2
Adder
22.954
24685805CER G1
Adder
9.822
24685905CER G2
Adder
9.822
942751AE2-291 GEN
Solar/Wind Harmer
10.385
966021AG1-471 GEN
Solar/Wind Harmer
5.753
971485AH1-239 GEN
Solar/Wind Harmer
8.497
339231AF1-038_GEN
Solar/Wind Harmer
1.918
960161AF2-307 GEN
Solar/Wind Harmer
6.658
339255AE2-071 GEN
Solar/Wind Harmer
1.099
964781AG1-341 GEN
Solar/Wind Harmer
10.97
339236AF1-050_GEN
Solar/Wind Harmer
1.872
971081AG2-670 GEN
Solar/Wind Harmer
7.734
942891AE2-308 GEN
Solar/Wind Harmer
10.176
970653AG2-424 GEN
Solar/Wind Harmer
4.88
970653AG2-424 GEN
Solar/Wind Harmer
1.764
964571AG1-320 GEN
Solar/Wind Harmer
8.186
970823AG2-518 GEN
50/50
8.384
247619Y1-049
50/50
0.913
24684705SMG5
50/50
0.856
970481AG2-311 GEN
50/50
11.937
24728405LEESVG
50/50
0.295
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.829
962751AG1-124 GEN
Solar/Wind Harmer
18.825
958121AF2-106 GEN
Solar/Wind Harmer
9.407
270173AC1-122 GEN
Solar/Wind Harmer
3.278
971331AH1-145 GEN
Solar/Wind Harmer
18.361
943031AE2-326 GEN
Solar/Wind Harmer
6.784
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.812
270574AD1-017 GEN2
Solar/Wind Harmer
8.473
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.936
270030AE2-140 GEN
Solar/Wind Harmer
30.929
960911AF2-382 GEN
Solar/Wind Harmer
10.948
270016AE1-250 BESS
Solar/Wind Harmer
3.256
970913AG2-568 GEN
Solar/Wind Harmer
11.004
971461AH1-227 GEN
Solar/Wind Harmer
7.003
970223AG2-152 GEN
Solar/Wind Harmer
17.623
270053AF1-130 C
Solar/Wind Harmer
4.815
972103AH1-617 GEN
Solar/Wind Harmer
25.835
24686205CER G4
Adder
9.835
24686405CER G5
Adder
9.796
972273AH1-721 GEN
Adder
89.316
24721905FLATG4
Adder
21.686
970273AG2-179 GEN
Solar/Wind Harmer
4.123
339250AF1-203 GEN
Solar/Wind Harmer
0.628
971155AH1-034 GEN
Solar/Wind Harmer
10.354
962251AG1-071 GEN
Solar/Wind Harmer
5.671
966571AG1-526 GEN
Solar/Wind Harmer
22.886
970093AG2-073 GEN
Solar/Wind Harmer
10.271
960741AF2-365 GEN
Solar/Wind Harmer
5.107
3429391JKCT 9G
Adder
8.402
971191AH1-055 GEN
Solar/Wind Harmer
22.182
972167AH1-666 GEN
Solar/Wind Harmer
7.768
957541AF2-048 GEN
Solar/Wind Harmer
1.528
958171AF2-111 GEN
Solar/Wind Harmer
23.91
970243AG2-164 GEN
Solar/Wind Harmer
24.587
970519AG2-331 GEN
Solar/Wind Harmer
16.518
970699AG2-449 GEN
Solar/Wind Harmer
10.927
25196008MFTGT1
Adder
1.252
252510AF1-249 C
Solar/Wind Harmer
0.384
25194608D.CRK4
Adder
1.508
25196608WSDLE5
Adder
7.849
970193AG2-126 GEN
Solar/Wind Harmer
13.689
942481AE2-261 GEN
Solar/Wind Harmer
27.229
253316AC1-085 GEN3
Solar/Wind Harmer
7.601
253433AC1-085 GEN1
Solar/Wind Harmer
4.825
946181AF1-283 GEN
Solar/Wind Harmer
11.797
24728705AND G3
Adder
7.277
24728505AND G1
Adder
3.48
276621W2-048 GEN
Solar/Wind Harmer
5.645
276838X2-022 GEN2
Solar/Wind Harmer
0.211
276686W4-005 GEN3
Solar/Wind Harmer
2.726
276668AB2-070 GEN1
Solar/Wind Harmer
2.027
971993AH1-541 GEN
Solar/Wind Harmer
8.328
270356AE2-297 GEN
Solar/Wind Harmer
4.098
253406AD2-031_GEN
Solar/Wind Harmer
1.149
274760LEE CO EC;1U
Adder
8.222
274767LEE CO EC;8U
Adder
8.125
972236AH1-702 GEN2
Adder
1.93
274682WAUKEGAN ;7U
Adder
15.703
274729ELWOOD EC;1P
Adder
13.481
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.838
3147666LOUISA
Solar/Wind Helper
1.088
316254AC1-120 GEN1
Solar/Wind Helper
1.159
316097T157 G90
Solar/Wind Helper
1.125
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316336AC2-165 C
Solar/Wind Helper
1.285
316006AB2-029 C
Solar/Wind Helper
0.112
316045AC1-158 PL2
Solar/Wind Helper
4.023
971125AH1-004 GEN
Solar/Wind Harmer
3.98
970107AG2-081 GEN
Solar/Wind Harmer
2.985
972043AH1-570 GEN
Solar/Wind Harmer
2.475
972045AH1-571 GEN
Solar/Wind Harmer
1.98
339221AD2-048_GEN
Solar/Wind Harmer
1.514
970235AG2-159 GEN
Solar/Wind Harmer
3.878
970235AG2-159 GEN
Solar/Wind Harmer
2.367
270186AC1-089 GEN
Solar/Wind Harmer
5.824
970239AG2-162 GEN
Solar/Wind Harmer
10.472
962581AG1-107 GEN
Solar/Wind Harmer
4.731
961491AF2-440 GEN
Solar/Wind Harmer
1.966
270444AC2-157 GEN1
Solar/Wind Harmer
5.239
252509AD1-136 GEN
Solar/Wind Harmer
0.238
25183208HLCRTG
Solar/Wind Harmer
5.582
252519AF1-045_GEN
Solar/Wind Harmer
5.589
252516AE2-318_GEN
Solar/Wind Harmer
4.263
25194408D.CRK1
Adder
6.938
25194508D.CRK3
Adder
1.297
970879AG2-548 GEN
Solar/Wind Harmer
5.656
971073AG2-665 GEN
Solar/Wind Harmer
5.656
971073AG2-665 GEN
Solar/Wind Harmer
3.946
945391AF1-204 GEN
Solar/Wind Harmer
12.718
276916AD2-100_GEN
Solar/Wind Harmer
19.154
276911AD2-131_GEN
Solar/Wind Harmer
3.871
957381AF2-032 GEN
Solar/Wind Harmer
0.381
253317AC1-085 GEN4
Solar/Wind Harmer
7.601
276763AC1-053 GEN1
Solar/Wind Harmer
3.568
276764AC1-053 GEN2
Solar/Wind Harmer
3.568
970241AG2-163 GEN
Solar/Wind Harmer
22.426
24728805RICHG1
Adder
3.384
24728905RICHG2
Adder
3.384
972267AH1-718 GEN
Adder
3.688
274764LEE CO EC;5U
Adder
8.241
274765LEE CO EC;6U
Adder
8.241
274762LEE CO EC;3U
Adder
8.222
274763LEE CO EC;4U
Adder
8.144
274683WAUKEGAN ;8U
Adder
18.419
274683WAUKEGAN ;8U
Adder
15.526
274696ROCKY RD ;4P
Adder
9.957
274695ROCKY RD ;2P
Adder
9.727
274693ROCKY RD ;1P
Adder
9.632
274697ROCKY RD ;3P
Adder
2.642
3132123MT JACKSON
Solar/Wind Helper
1.389
315821AE2-092 GEN
Solar/Wind Helper
3.216
966001AG1-469 GEN
Solar/Wind Helper
0.32
315651AD1-115 GEN
Solar/Wind Helper
0.837
966871AG1-558 GEN
Solar/Wind Helper
0.306
316447AC1-158 HLD
Solar/Wind Helper
2.766
316468AD1-105 GEN
Solar/Wind Helper
1.124
970479AG2-310 GEN
50/50
20.255
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
966251AG1-494 GEN
50/50
4.388
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
7.003
971329AH1-144 GEN
Solar/Wind Harmer
23.686
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
9.812
270197AD1-017 GEN1
Solar/Wind Harmer
2.546
270336AE1-100 GEN
Solar/Wind Harmer
2.757
943811AF1-049 GEN
Solar/Wind Harmer
5.695
24728305BUCHG2
Adder
6.75
270018AE2-047 C O1
Solar/Wind Harmer
1.826
958131AF2-107 GEN
Solar/Wind Harmer
7.108
24735205WLF2G2
Adder
8.023
971687AH1-348 GEN
Solar/Wind Harmer
1.359
971403AH1-188 GEN
Solar/Wind Harmer
18.852
24723205RIVRG3
Adder
22.954
971315AH1-136 GEN
Solar/Wind Harmer
2.43
24686105CER G3
Adder
9.887
24686505CER G6
Adder
9.874
270331AC1-082 GEN3
Solar/Wind Harmer
0.487
24721705FLATG2
Adder
21.686
970947AG2-589 GEN
Solar/Wind Harmer
2.139
970273AG2-179 GEN
Solar/Wind Harmer
2.581
971821AH1-427 GEN
Solar/Wind Harmer
10.346
964901AG1-354 GEN
Solar/Wind Harmer
15.5
339241AF1-083 GEN
Solar/Wind Harmer
1.715
962241AG1-070 GEN
Solar/Wind Harmer
4.64
960001AF2-291 GEN
Solar/Wind Harmer
3.113
3429241JKCT 3G
Adder
12.029
3429421JKCT 10G
Adder
8.402
971565AH1-281 GEN
Solar/Wind Harmer
2.001
943111AE2-339 GEN
Solar/Wind Harmer
0.883
339216AC1-074 GEN
Solar/Wind Harmer
1.649
945681AF1-233 GEN
Solar/Wind Harmer
18.32
927014AC1-188 GEN
Solar/Wind Harmer
1.532
970091AG2-072 GEN
Adder
74.012
970333AG2-219 GEN
Solar/Wind Harmer
30.05
270445AC2-157 GEN2
Solar/Wind Harmer
5.239
25196808ZIMRHP
Adder
70.616
252507AC2-088 GEN
Solar/Wind Harmer
1.669
25196008MFTGT1
Adder
1.293
25194608D.CRK4
Adder
1.508
965911AG1-460 GEN
Solar/Wind Harmer
1.271
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
946171AF1-282 GEN
Solar/Wind Harmer
9.075
24728605AND G2
Adder
3.48
276615X2-022 GEN
Solar/Wind Harmer
1.772
963831AG1-236 GEN
Solar/Wind Harmer
8.877
274880W4-005 GEN4
Solar/Wind Harmer
2.726
963741AG1-226 GEN
Solar/Wind Harmer
40.366
274761LEE CO EC;2U
Adder
8.222
274766LEE CO EC;7U
Adder
8.125
972235AH1-702 GEN1
Adder
2.22
274822ROCKFORD ;11
Adder
17.275
274828WAUKEGAN ;BP
Adder
9.655
274682WAUKEGAN ;7U
Adder
15.703
274745AC1-111 GEN9
Adder
4.87
315616AA1-038_C
Solar/Wind Helper
3.293
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.725
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.625
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.386
23583801GRNGAP
Solar/Wind Helper
4.287
316095T157 G97
Solar/Wind Helper
1.125
238147AE2-230_GEN1
Solar/Wind Helper
0.421
238149AF1-291A_GEN
Solar/Wind Helper
0.12
316313AB2-026
Solar/Wind Helper
0.354
316258AE1-075 C
Solar/Wind Helper
0.319
316405AF2-144 C
Solar/Wind Helper
0.265
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.387
316044AC1-158 PL1
Solar/Wind Helper
1.257
316450AC1-158 RIC
Solar/Wind Helper
0.335
972175AH1-670 GEN
Solar/Wind Harmer
4.72
944201AF1-088_MTX
Adder
109.09
957141AF2-008_MTX
Adder
54.545
LAGNLTFEXP_LAGN->PJM
CLTF
20.28
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.555
TVALTFEXP_TVA->PJM
CLTF
10.606
CPLELTFEXP_CPLE->PJM
CLTF
6.226
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.111
NYPJM->LTFIMP_NY
CLTF
3.248
LGEELTFEXP_LGEE->PJM
CLTF
6.763
WECLTFEXP_WEC->PJM
CLTF
3.371
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.415
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.315
MECLTFEXP_MEC->PJM
CLTF
15.415
SIGELTFEXP_SIGE->PJM
CLTF
0.508

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.36 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4200.43
MW Contribution:17.63
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
8.386
247619Y1-049
50/50
0.913
24684705SMG5
50/50
0.857
970481AG2-311 GEN
50/50
11.941
24728405LEESVG
50/50
0.296
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.847
962751AG1-124 GEN
Solar/Wind Harmer
18.831
958121AF2-106 GEN
Solar/Wind Harmer
9.409
270173AC1-122 GEN
Solar/Wind Harmer
3.279
971331AH1-145 GEN
Solar/Wind Harmer
18.367
943031AE2-326 GEN
Solar/Wind Harmer
6.787
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.815
270574AD1-017 GEN2
Solar/Wind Harmer
8.476
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.941
270030AE2-140 GEN
Solar/Wind Harmer
30.942
960911AF2-382 GEN
Solar/Wind Harmer
10.952
270016AE1-250 BESS
Solar/Wind Harmer
3.257
970913AG2-568 GEN
Solar/Wind Harmer
11.009
971461AH1-227 GEN
Solar/Wind Harmer
7.007
970223AG2-152 GEN
Solar/Wind Harmer
17.631
270053AF1-130 C
Solar/Wind Harmer
4.818
972103AH1-617 GEN
Solar/Wind Harmer
25.847
24686205CER G4
Adder
9.841
24686405CER G5
Adder
9.802
972273AH1-721 GEN
Adder
89.369
24721905FLATG4
Adder
21.699
970273AG2-179 GEN
Solar/Wind Harmer
4.125
339250AF1-203 GEN
Solar/Wind Harmer
0.628
971155AH1-034 GEN
Solar/Wind Harmer
10.36
962251AG1-071 GEN
Solar/Wind Harmer
5.674
966571AG1-526 GEN
Solar/Wind Harmer
22.9
970093AG2-073 GEN
Solar/Wind Harmer
10.278
960741AF2-365 GEN
Solar/Wind Harmer
5.111
3429391JKCT 9G
Adder
8.407
971191AH1-055 GEN
Solar/Wind Harmer
22.196
972167AH1-666 GEN
Solar/Wind Harmer
7.773
957541AF2-048 GEN
Solar/Wind Harmer
1.529
958171AF2-111 GEN
Solar/Wind Harmer
23.926
970243AG2-164 GEN
Solar/Wind Harmer
24.603
970519AG2-331 GEN
Solar/Wind Harmer
16.529
970699AG2-449 GEN
Solar/Wind Harmer
10.935
25196008MFTGT1
Adder
1.253
971543AH1-269 GEN
50/50
12.251
966391AG1-508 GEN
Solar/Wind Harmer
6.377
270069AE2-166 C O1
Solar/Wind Harmer
4.508
971313AH1-133 GEN
Solar/Wind Harmer
15.705
24734705WLF1G3
Adder
8.198
24734805WLF1G4
Adder
8.198
24734905WLF1G5
Adder
8.198
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.027
270399AC1-101 GEN
Solar/Wind Harmer
5.558
270400AC1-102 GEN
Solar/Wind Harmer
5.558
941621AE2-160 GEN
Adder
4.287
957241AF2-018 GEN
Solar/Wind Harmer
5.759
970281AG2-184 GEN
Solar/Wind Harmer
27.14
972143AH1-644 GEN
Solar/Wind Harmer
12.924
971981AH1-535 GEN
Solar/Wind Harmer
12.569
962211AG1-066 GEN
Solar/Wind Harmer
3.003
971061AG2-657 GEN
Solar/Wind Harmer
10.996
24477305BRIDGE
Adder
0.419
972203AH1-686 GEN
Adder
2.706
270330AC1-082 GEN2
Solar/Wind Harmer
0.824
270329AC1-082 GEN1
Solar/Wind Harmer
0.486
965401AG1-405 GEN
Solar/Wind Harmer
6.063
965411AG1-406 GEN
Solar/Wind Harmer
2.721
339211AE2-254 GEN
Solar/Wind Harmer
1.564
3429211JKCT 2G
Adder
11.881
970455AG2-298 GEN
Solar/Wind Harmer
6.038
339243AC2-075 GEN1
Solar/Wind Harmer
0.447
972163AH1-664 GEN
Solar/Wind Harmer
9.749
972165AH1-665 GEN
Solar/Wind Harmer
7.8
971985AH1-537 GEN
Solar/Wind Harmer
17.306
270367AC2-061_GEN
Solar/Wind Harmer
3.011
316123AC1-075 GEN
Solar/Wind Harmer
1.494
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.255
25196108MFTGT2
Adder
1.426
25196108MFTGT2
Adder
1.325
970879AG2-548 GEN
Solar/Wind Harmer
3.949
944221AF1-090 GEN
Solar/Wind Harmer
10.031
252524AE2-267 GEN
Solar/Wind Harmer
1.445
25196408WSDLE3
Adder
8.086
25196308WSDLE2
Adder
8.015
25196208WSDLE1
Adder
7.995
25196708WSDLE6
Adder
7.975
25196508WSDLE4
Adder
7.774
276849AB2-070 GEN2
Solar/Wind Harmer
2.029
276848AB2-070 GEN3
Solar/Wind Harmer
2.029
276785W4-005 GEN1
Solar/Wind Harmer
2.728
276174W4-005 GEN2
Solar/Wind Harmer
2.728
274823ROCKFORD ;21
Adder
17.162
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684405SMG2
50/50
2.225
24684505SMG3
50/50
1.376
24684305SMG1
50/50
0.806
270583AD2-179 GEN
Solar/Wind Harmer
20.728
270214AC2-123 GEN
Solar/Wind Harmer
4.312
971277AH1-098 GEN
Solar/Wind Harmer
7.423
316217AC1-145 GEN
Solar/Wind Harmer
4.248
316197AC1-042 GEN
Solar/Wind Harmer
3.22
942671AE2-283 GEN
Solar/Wind Harmer
8.67
24728205BUCHG1
Adder
6.753
270013AE1-250 PV
Solar/Wind Harmer
3.257
971225AH1-072 GEN
Solar/Wind Harmer
2.732
971227AH1-073 GEN
Solar/Wind Harmer
2.732
944971AF1-162 GEN
Solar/Wind Harmer
9.072
24723005RIVRG1
Adder
22.966
24723105RIVRG2
Adder
22.966
24685805CER G1
Adder
9.828
24685905CER G2
Adder
9.828
942751AE2-291 GEN
Solar/Wind Harmer
10.391
966021AG1-471 GEN
Solar/Wind Harmer
5.756
971485AH1-239 GEN
Solar/Wind Harmer
8.502
339231AF1-038_GEN
Solar/Wind Harmer
1.919
960161AF2-307 GEN
Solar/Wind Harmer
6.662
339255AE2-071 GEN
Solar/Wind Harmer
1.099
964781AG1-341 GEN
Solar/Wind Harmer
10.976
339236AF1-050_GEN
Solar/Wind Harmer
1.873
971081AG2-670 GEN
Solar/Wind Harmer
7.739
942891AE2-308 GEN
Solar/Wind Harmer
10.182
970653AG2-424 GEN
Solar/Wind Harmer
4.883
970653AG2-424 GEN
Solar/Wind Harmer
1.765
964571AG1-320 GEN
Solar/Wind Harmer
8.191
971125AH1-004 GEN
Solar/Wind Harmer
3.983
970107AG2-081 GEN
Solar/Wind Harmer
2.987
972043AH1-570 GEN
Solar/Wind Harmer
2.476
972045AH1-571 GEN
Solar/Wind Harmer
1.981
339221AD2-048_GEN
Solar/Wind Harmer
1.515
970235AG2-159 GEN
Solar/Wind Harmer
3.88
970235AG2-159 GEN
Solar/Wind Harmer
2.369
270186AC1-089 GEN
Solar/Wind Harmer
5.828
970239AG2-162 GEN
Solar/Wind Harmer
10.479
962581AG1-107 GEN
Solar/Wind Harmer
4.734
961491AF2-440 GEN
Solar/Wind Harmer
1.967
270444AC2-157 GEN1
Solar/Wind Harmer
5.243
252509AD1-136 GEN
Solar/Wind Harmer
0.239
25183208HLCRTG
Solar/Wind Harmer
5.586
252519AF1-045_GEN
Solar/Wind Harmer
5.593
252516AE2-318_GEN
Solar/Wind Harmer
4.266
25194408D.CRK1
Adder
6.943
25194508D.CRK3
Adder
1.298
970879AG2-548 GEN
Solar/Wind Harmer
5.66
971073AG2-665 GEN
Solar/Wind Harmer
5.66
971073AG2-665 GEN
Solar/Wind Harmer
3.949
945391AF1-204 GEN
Solar/Wind Harmer
12.727
276916AD2-100_GEN
Solar/Wind Harmer
19.168
276911AD2-131_GEN
Solar/Wind Harmer
3.874
957381AF2-032 GEN
Solar/Wind Harmer
0.381
253317AC1-085 GEN4
Solar/Wind Harmer
7.607
276763AC1-053 GEN1
Solar/Wind Harmer
3.571
276764AC1-053 GEN2
Solar/Wind Harmer
3.571
970241AG2-163 GEN
Solar/Wind Harmer
22.442
24728805RICHG1
Adder
3.386
24728905RICHG2
Adder
3.386
972267AH1-718 GEN
Adder
3.691
274764LEE CO EC;5U
Adder
8.247
274765LEE CO EC;6U
Adder
8.247
274762LEE CO EC;3U
Adder
8.227
274763LEE CO EC;4U
Adder
8.15
274683WAUKEGAN ;8U
Adder
18.432
274683WAUKEGAN ;8U
Adder
15.538
274696ROCKY RD ;4P
Adder
9.964
274695ROCKY RD ;2P
Adder
9.734
252510AF1-249 C
Solar/Wind Harmer
0.385
25194608D.CRK4
Adder
1.509
25196608WSDLE5
Adder
7.855
970193AG2-126 GEN
Solar/Wind Harmer
13.698
942481AE2-261 GEN
Solar/Wind Harmer
27.248
253316AC1-085 GEN3
Solar/Wind Harmer
7.607
253433AC1-085 GEN1
Solar/Wind Harmer
4.829
946181AF1-283 GEN
Solar/Wind Harmer
11.806
24728705AND G3
Adder
7.283
24728505AND G1
Adder
3.482
276621W2-048 GEN
Solar/Wind Harmer
5.649
276838X2-022 GEN2
Solar/Wind Harmer
0.211
276668AB2-070 GEN1
Solar/Wind Harmer
2.029
276686W4-005 GEN3
Solar/Wind Harmer
2.728
971993AH1-541 GEN
Solar/Wind Harmer
8.334
270356AE2-297 GEN
Solar/Wind Harmer
4.101
253406AD2-031_GEN
Solar/Wind Harmer
1.149
274760LEE CO EC;1U
Adder
8.227
274767LEE CO EC;8U
Adder
8.131
972236AH1-702 GEN2
Adder
1.932
970479AG2-310 GEN
50/50
20.26
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
966251AG1-494 GEN
50/50
4.39
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
7.005
971329AH1-144 GEN
Solar/Wind Harmer
23.694
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
9.815
270197AD1-017 GEN1
Solar/Wind Harmer
2.547
270336AE1-100 GEN
Solar/Wind Harmer
2.758
943811AF1-049 GEN
Solar/Wind Harmer
5.698
24728305BUCHG2
Adder
6.753
270018AE2-047 C O1
Solar/Wind Harmer
1.826
958131AF2-107 GEN
Solar/Wind Harmer
7.111
24735205WLF2G2
Adder
8.027
971687AH1-348 GEN
Solar/Wind Harmer
1.359
971403AH1-188 GEN
Solar/Wind Harmer
18.861
24723205RIVRG3
Adder
22.966
971315AH1-136 GEN
Solar/Wind Harmer
2.431
24686105CER G3
Adder
9.893
24686505CER G6
Adder
9.88
270331AC1-082 GEN3
Solar/Wind Harmer
0.487
24721705FLATG2
Adder
21.699
970947AG2-589 GEN
Solar/Wind Harmer
2.14
970273AG2-179 GEN
Solar/Wind Harmer
2.583
971821AH1-427 GEN
Solar/Wind Harmer
10.353
964901AG1-354 GEN
Solar/Wind Harmer
15.509
339241AF1-083 GEN
Solar/Wind Harmer
1.716
962241AG1-070 GEN
Solar/Wind Harmer
4.643
960001AF2-291 GEN
Solar/Wind Harmer
3.115
3429241JKCT 3G
Adder
12.037
3429421JKCT 10G
Adder
8.407
971565AH1-281 GEN
Solar/Wind Harmer
2.002
943111AE2-339 GEN
Solar/Wind Harmer
0.883
339216AC1-074 GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
18.332
927014AC1-188 GEN
Solar/Wind Harmer
1.533
970091AG2-072 GEN
Adder
74.061
970333AG2-219 GEN
Solar/Wind Harmer
30.071
270445AC2-157 GEN2
Solar/Wind Harmer
5.243
25196808ZIMRHP
Adder
70.665
252507AC2-088 GEN
Solar/Wind Harmer
1.671
25196008MFTGT1
Adder
1.294
25194608D.CRK4
Adder
1.509
965911AG1-460 GEN
Solar/Wind Harmer
1.272
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
946171AF1-282 GEN
Solar/Wind Harmer
9.081
24728605AND G2
Adder
3.482
276615X2-022 GEN
Solar/Wind Harmer
1.774
963831AG1-236 GEN
Solar/Wind Harmer
8.883
274880W4-005 GEN4
Solar/Wind Harmer
2.728
963741AG1-226 GEN
Solar/Wind Harmer
40.395
274761LEE CO EC;2U
Adder
8.227
274766LEE CO EC;7U
Adder
8.131
972235AH1-702 GEN1
Adder
2.221
274822ROCKFORD ;11
Adder
17.288
274828WAUKEGAN ;BP
Adder
9.662
274682WAUKEGAN ;7U
Adder
15.715
274745AC1-111 GEN9
Adder
4.873
315616AA1-038_C
Solar/Wind Helper
3.292
3148013FISHERV
Solar/Wind Helper
0.522
316499AE2-029_GEN
Solar/Wind Helper
1.724
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.625
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.386
23583801GRNGAP
Solar/Wind Helper
4.284
316095T157 G97
Solar/Wind Helper
1.124
238147AE2-230_GEN1
Solar/Wind Helper
0.421
238149AF1-291A_GEN
Solar/Wind Helper
0.12
316313AB2-026
Solar/Wind Helper
0.354
316258AE1-075 C
Solar/Wind Helper
0.318
316405AF2-144 C
Solar/Wind Helper
0.265
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.386
316044AC1-158 PL1
Solar/Wind Helper
1.256
316450AC1-158 RIC
Solar/Wind Helper
0.335
972175AH1-670 GEN
Solar/Wind Harmer
4.723
274682WAUKEGAN ;7U
Adder
15.715
274729ELWOOD EC;1P
Adder
13.491
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.837
3147666LOUISA
Solar/Wind Helper
1.087
316254AC1-120 GEN1
Solar/Wind Helper
1.158
316097T157 G90
Solar/Wind Helper
1.124
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316336AC2-165 C
Solar/Wind Helper
1.284
316006AB2-029 C
Solar/Wind Helper
0.112
316045AC1-158 PL2
Solar/Wind Helper
4.02
274693ROCKY RD ;1P
Adder
9.639
274697ROCKY RD ;3P
Adder
2.644
3132123MT JACKSON
Solar/Wind Helper
1.388
315821AE2-092 GEN
Solar/Wind Helper
3.215
966001AG1-469 GEN
Solar/Wind Helper
0.32
315651AD1-115 GEN
Solar/Wind Helper
0.837
966871AG1-558 GEN
Solar/Wind Helper
0.306
316447AC1-158 HLD
Solar/Wind Helper
2.764
316468AD1-105 GEN
Solar/Wind Helper
1.124
274746AC1-111 G10
Adder
4.873
274744AC1-111 GEN8
Adder
4.873
25306009OHH W.
Adder
2.506
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.313
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.078
316164AC1-076 GEN
Solar/Wind Helper
1.171
238152AF2-075_GEN
Solar/Wind Helper
0.601
944201AF1-088_MTX
Adder
109.164
957141AF2-008_MTX
Adder
54.582
LAGNLTFEXP_LAGN->PJM
CLTF
20.293
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.574
TVALTFEXP_TVA->PJM
CLTF
10.613
CPLELTFEXP_CPLE->PJM
CLTF
6.233
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.197
NYPJM->LTFIMP_NY
CLTF
3.243
LGEELTFEXP_LGEE->PJM
CLTF
6.767
WECLTFEXP_WEC->PJM
CLTF
3.374
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.508
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.339
MECLTFEXP_MEC->PJM
CLTF
15.425
SIGELTFEXP_SIGE->PJM
CLTF
0.508

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o DVP_P4-2: 151T1047_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 151T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.96 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:330.65
MW Contribution:6.6
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
1.184
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.484
970481AG2-311 GEN
50/50
6.751
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.139
316003AC1-222 GEN
Solar/Wind Harmer
5.036
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.147
270016AE1-250 BESS
Solar/Wind Harmer
1.342
270173AC1-122 GEN
Solar/Wind Harmer
0.85
970223AG2-152 GEN
Solar/Wind Harmer
6.601
24684405SMG2
50/50
1.258
24684505SMG3
50/50
0.778
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.716
316197AC1-042 GEN
Solar/Wind Harmer
6.608
942671AE2-283 GEN
Solar/Wind Harmer
17.789
942751AE2-291 GEN
Solar/Wind Harmer
32.874
270013AE1-250 PV
Solar/Wind Harmer
1.342
316123AC1-075 GEN
Solar/Wind Harmer
5.564
970865AG2-541 GEN
Solar/Wind Harmer
20.949
970165AG2-112 GEN
Solar/Wind Harmer
4.899
970163AG2-111 GEN
Solar/Wind Harmer
4.673
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.266
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.139
971683AH1-343 GEN
Solar/Wind Harmer
22.238
270197AD1-017 GEN1
Solar/Wind Harmer
1.246
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.061
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
0.013
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.831
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.484
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.065
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.177

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o DVP_P4-2: 104702_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104702_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.95 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:330.63
MW Contribution:6.6
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.266
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.139
971683AH1-343 GEN
Solar/Wind Harmer
22.238
270197AD1-017 GEN1
Solar/Wind Harmer
1.246
316123AC1-075 GEN
Solar/Wind Harmer
5.564
970865AG2-541 GEN
Solar/Wind Harmer
20.949
970165AG2-112 GEN
Solar/Wind Harmer
4.899
970163AG2-111 GEN
Solar/Wind Harmer
4.673
3151561HALLBR1
50/50
1.184
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.484
970481AG2-311 GEN
50/50
6.751
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.139
316003AC1-222 GEN
Solar/Wind Harmer
5.035
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.147
270016AE1-250 BESS
Solar/Wind Harmer
1.342
270173AC1-122 GEN
Solar/Wind Harmer
0.85
970223AG2-152 GEN
Solar/Wind Harmer
6.6
24684405SMG2
50/50
1.258
24684505SMG3
50/50
0.778
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.716
316197AC1-042 GEN
Solar/Wind Harmer
6.608
942671AE2-283 GEN
Solar/Wind Harmer
17.789
942751AE2-291 GEN
Solar/Wind Harmer
32.874
270013AE1-250 PV
Solar/Wind Harmer
1.342
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.061
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
0.012
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.829
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.484
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.065
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.178

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o DVP_P4-2: 1016T1047_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 1016T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.07 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:313.77
MW Contribution:6.61
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Harmer
5.565
970865AG2-541 GEN
Solar/Wind Harmer
20.954
970165AG2-112 GEN
Solar/Wind Harmer
4.9
970163AG2-111 GEN
Solar/Wind Harmer
4.674
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.143
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.151
270016AE1-250 BESS
Solar/Wind Harmer
1.344
270173AC1-122 GEN
Solar/Wind Harmer
0.851
970223AG2-152 GEN
Solar/Wind Harmer
6.611
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.718
316197AC1-042 GEN
Solar/Wind Harmer
6.609
942671AE2-283 GEN
Solar/Wind Harmer
17.793
942751AE2-291 GEN
Solar/Wind Harmer
32.881
270013AE1-250 PV
Solar/Wind Harmer
1.344
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.143
971683AH1-343 GEN
Solar/Wind Harmer
22.243
270197AD1-017 GEN1
Solar/Wind Harmer
1.247
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.029
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007
CPLELTFEXP_CPLE->PJM
CLTF
0.492
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.06
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.153

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o DVP_P4-2: 101672_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 101672_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.05 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:313.73
MW Contribution:6.61
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.143
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.151
270016AE1-250 BESS
Solar/Wind Harmer
1.344
270173AC1-122 GEN
Solar/Wind Harmer
0.851
970223AG2-152 GEN
Solar/Wind Harmer
6.611
316123AC1-075 GEN
Solar/Wind Harmer
5.565
970865AG2-541 GEN
Solar/Wind Harmer
20.954
970165AG2-112 GEN
Solar/Wind Harmer
4.9
970163AG2-111 GEN
Solar/Wind Harmer
4.674
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.718
316197AC1-042 GEN
Solar/Wind Harmer
6.609
942671AE2-283 GEN
Solar/Wind Harmer
17.793
942751AE2-291 GEN
Solar/Wind Harmer
32.881
270013AE1-250 PV
Solar/Wind Harmer
1.344
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.143
971683AH1-343 GEN
Solar/Wind Harmer
22.243
270197AD1-017 GEN1
Solar/Wind Harmer
1.247
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.029
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007
CPLELTFEXP_CPLE->PJM
CLTF
0.492
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.06
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.153

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o DVP_P4-2: 104772_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104772_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.62 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:310.21
MW Contribution:6.61
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Harmer
5.565
970865AG2-541 GEN
Solar/Wind Harmer
20.954
970165AG2-112 GEN
Solar/Wind Harmer
4.9
970163AG2-111 GEN
Solar/Wind Harmer
4.674
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.143
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.151
270016AE1-250 BESS
Solar/Wind Harmer
1.344
270173AC1-122 GEN
Solar/Wind Harmer
0.851
970223AG2-152 GEN
Solar/Wind Harmer
6.611
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.718
316197AC1-042 GEN
Solar/Wind Harmer
6.609
942671AE2-283 GEN
Solar/Wind Harmer
17.793
942751AE2-291 GEN
Solar/Wind Harmer
32.881
270013AE1-250 PV
Solar/Wind Harmer
1.344
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.143
971683AH1-343 GEN
Solar/Wind Harmer
22.243
270197AD1-017 GEN1
Solar/Wind Harmer
1.247
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.029
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007
CPLELTFEXP_CPLE->PJM
CLTF
0.492
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.06
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.153

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 1047_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1047_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.29 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:260.4
MW Contribution:4.63
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
1.184
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.484
970481AG2-311 GEN
50/50
6.751
3147312GRETNA
Solar/Wind Harmer
0.382
3146802CHATHAM
Solar/Wind Harmer
0.358
941801AE2-185 GEN
Solar/Wind Harmer
15.295
316003AC1-222 GEN
Solar/Wind Harmer
0.012
3147123OTTER R
Solar/Wind Harmer
0.275
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.002
270173AC1-122 GEN
Solar/Wind Harmer
0.175
970223AG2-152 GEN
Solar/Wind Harmer
4.628
316123AC1-075 GEN
Solar/Wind Harmer
0.627
970865AG2-541 GEN
Solar/Wind Harmer
15.911
970165AG2-112 GEN
Solar/Wind Harmer
3.721
970163AG2-111 GEN
Solar/Wind Harmer
3.549
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.266
3147312GRETNA
Solar/Wind Harmer
0.096
941821AE2-187 GEN
Solar/Wind Harmer
15.295
971683AH1-343 GEN
Solar/Wind Harmer
16.89
270197AD1-017 GEN1
Solar/Wind Harmer
0.699
24684405SMG2
50/50
1.258
24684505SMG3
50/50
0.778
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
0.006
316197AC1-042 GEN
Solar/Wind Harmer
0.005
942671AE2-283 GEN
Solar/Wind Harmer
11.896
942751AE2-291 GEN
Solar/Wind Harmer
24.967
270013AE1-250 PV
Solar/Wind Harmer
0.002
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.061
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
0.012
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.829
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.484
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.065
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.178

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 1016_SRT-A-1


Base Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1016_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.51 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:248.71
MW Contribution:4.64
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Harmer
0.628
970865AG2-541 GEN
Solar/Wind Harmer
15.914
970165AG2-112 GEN
Solar/Wind Harmer
3.721
970163AG2-111 GEN
Solar/Wind Harmer
3.55
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
0.382
3146802CHATHAM
Solar/Wind Harmer
0.358
941801AE2-185 GEN
Solar/Wind Harmer
15.299
3147123OTTER R
Solar/Wind Harmer
0.275
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.002
270173AC1-122 GEN
Solar/Wind Harmer
0.176
970223AG2-152 GEN
Solar/Wind Harmer
4.636
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
0.096
941821AE2-187 GEN
Solar/Wind Harmer
15.299
971683AH1-343 GEN
Solar/Wind Harmer
16.893
270197AD1-017 GEN1
Solar/Wind Harmer
0.7
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
0.006
316197AC1-042 GEN
Solar/Wind Harmer
0.005
942671AE2-283 GEN
Solar/Wind Harmer
11.899
942751AE2-291 GEN
Solar/Wind Harmer
24.973
270013AE1-250 PV
Solar/Wind Harmer
0.002
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.028
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007
CPLELTFEXP_CPLE->PJM
CLTF
0.492
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.06
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.154

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.25 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:245.61
MW Contribution:13.8
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Harmer
2.482
970165AG2-112 GEN
Solar/Wind Harmer
2.186
970163AG2-111 GEN
Solar/Wind Harmer
2.085
970865AG2-541 GEN
Solar/Wind Harmer
6.833
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.005
316118AC1-105 GEN
Solar/Wind Harmer
0.454
24684405SMG2
50/50
1.198
24684505SMG3
50/50
0.741
24684305SMG1
50/50
0.434
316217AC1-145 GEN
Solar/Wind Harmer
7.301
316197AC1-042 GEN
Solar/Wind Harmer
5.534
942671AE2-283 GEN
Solar/Wind Harmer
14.9
942751AE2-291 GEN
Solar/Wind Harmer
17.168
270013AE1-250 PV
Solar/Wind Harmer
2.392
24728405LEESVG
50/50
0.32
24684605SMG4
50/50
1.206
3147312GRETNA
Solar/Wind Harmer
-0.009
941821AE2-187 GEN
Solar/Wind Harmer
16.868
270197AD1-017 GEN1
Solar/Wind Harmer
1.62
971683AH1-343 GEN
Solar/Wind Harmer
5.942
316248AF1-058 C
Solar/Wind Harmer
0.225
960061AF2-297 GEN
Solar/Wind Harmer
3.734
3151561HALLBR1
50/50
0.931
24728405LEESVG
50/50
0.319
24684705SMG5
50/50
0.461
970481AG2-311 GEN
50/50
6.43
3147312GRETNA
Solar/Wind Harmer
-0.036
3146802CHATHAM
Solar/Wind Harmer
-0.034
941801AE2-185 GEN
Solar/Wind Harmer
16.868
3147123OTTER R
Solar/Wind Harmer
-0.024
270574AD1-017 GEN2
Solar/Wind Harmer
5.39
270016AE1-250 BESS
Solar/Wind Harmer
2.392
970223AG2-152 GEN
Solar/Wind Harmer
13.798
316003AC1-222 GEN
Solar/Wind Harmer
1.06
270173AC1-122 GEN
Solar/Wind Harmer
0.706
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.153
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.471
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.072
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.729
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.033
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.539

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o AEP_P7-1_#10778___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10778___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.25 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:245.6
MW Contribution:13.8
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.198
24684505SMG3
50/50
0.741
24684305SMG1
50/50
0.434
316217AC1-145 GEN
Solar/Wind Harmer
7.301
316197AC1-042 GEN
Solar/Wind Harmer
5.534
942671AE2-283 GEN
Solar/Wind Harmer
14.9
942751AE2-291 GEN
Solar/Wind Harmer
17.168
270013AE1-250 PV
Solar/Wind Harmer
2.392
316123AC1-075 GEN
Solar/Wind Harmer
2.482
970165AG2-112 GEN
Solar/Wind Harmer
2.186
970163AG2-111 GEN
Solar/Wind Harmer
2.085
970865AG2-541 GEN
Solar/Wind Harmer
6.833
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.005
316118AC1-105 GEN
Solar/Wind Harmer
0.454
3151561HALLBR1
50/50
0.931
24728405LEESVG
50/50
0.319
24684705SMG5
50/50
0.461
970481AG2-311 GEN
50/50
6.43
3147312GRETNA
Solar/Wind Harmer
-0.036
3146802CHATHAM
Solar/Wind Harmer
-0.034
941801AE2-185 GEN
Solar/Wind Harmer
16.868
3147123OTTER R
Solar/Wind Harmer
-0.024
270574AD1-017 GEN2
Solar/Wind Harmer
5.39
270016AE1-250 BESS
Solar/Wind Harmer
2.392
970223AG2-152 GEN
Solar/Wind Harmer
13.798
316003AC1-222 GEN
Solar/Wind Harmer
1.06
270173AC1-122 GEN
Solar/Wind Harmer
0.706
24728405LEESVG
50/50
0.32
24684605SMG4
50/50
1.206
3147312GRETNA
Solar/Wind Harmer
-0.009
941821AE2-187 GEN
Solar/Wind Harmer
16.868
270197AD1-017 GEN1
Solar/Wind Harmer
1.62
971683AH1-343 GEN
Solar/Wind Harmer
5.942
316248AF1-058 C
Solar/Wind Harmer
0.225
960061AF2-297 GEN
Solar/Wind Harmer
3.734
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.153
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.471
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.072
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.729
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.033
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.539

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.66 %
Rating:192.7 MVA
Rating Type:A
MVA to Mitigate:228.66
MW Contribution:6.85
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Helper
2.591
3147173SINAI
Solar/Wind Helper
0.126
3147243WELCO
Solar/Wind Helper
0.079
24684405SMG2
50/50
1.947
24684505SMG3
50/50
1.204
24684305SMG1
50/50
0.706
270013AE1-250 PV
Solar/Wind Harmer
0.004
316197AC1-042 GEN
Solar/Wind Helper
0.783
24728405LEESVG
50/50
0.549
24684705SMG5
50/50
0.75
970481AG2-311 GEN
50/50
10.451
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270173AC1-122 GEN
Solar/Wind Harmer
0.32
270016AE1-250 BESS
Solar/Wind Harmer
0.004
970223AG2-152 GEN
Solar/Wind Harmer
6.853
3147312GRETNA
Solar/Wind Helper
0.668
3146802CHATHAM
Solar/Wind Helper
0.626
3147123OTTER R
Solar/Wind Helper
0.448
316003AC1-222 GEN
Solar/Wind Helper
0.83
24728405LEESVG
50/50
0.551
24684605SMG4
50/50
1.96
270197AD1-017 GEN1
Solar/Wind Harmer
1.068
3147312GRETNA
Solar/Wind Helper
0.167
316248AF1-058 C
Solar/Wind Helper
0.17
LAGNLTFEXP_LAGN->PJM
CLTF
0.265
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.314
TVALTFEXP_TVA->PJM
CLTF
0.14
CPLELTFEXP_CPLE->PJM
CLTF
0.047
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.737
NYPJM->LTFIMP_NY
CLTF
0.068
LGEELTFEXP_LGEE->PJM
CLTF
0.091
WECLTFEXP_WEC->PJM
CLTF
0.046
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.65
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.52
MECLTFEXP_MEC->PJM
CLTF
0.207
SIGELTFEXP_SIGE->PJM
CLTF
0.007

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#10162_05EDAN 1 138_P_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.03 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:332.36
MW Contribution:29.76
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.617
24684705SMG5
50/50
0.995
970481AG2-311 GEN
50/50
13.869
270574AD1-017 GEN2
Solar/Wind Harmer
11.625
270016AE1-250 BESS
Solar/Wind Harmer
5.16
970223AG2-152 GEN
Solar/Wind Harmer
29.761
270173AC1-122 GEN
Solar/Wind Harmer
2.227
3147312GRETNA
Solar/Wind Helper
0.606
3146802CHATHAM
Solar/Wind Helper
0.568
3147123OTTER R
Solar/Wind Helper
0.407
316003AC1-222 GEN
Solar/Wind Helper
0.836
316123AC1-075 GEN
Solar/Wind Helper
2.422
3147173SINAI
Solar/Wind Helper
0.136
3147243WELCO
Solar/Wind Helper
0.085
316118AC1-105 GEN
Solar/Wind Helper
0.472
24684405SMG2
50/50
2.584
24684505SMG3
50/50
1.598
24684305SMG1
50/50
0.937
270013AE1-250 PV
Solar/Wind Harmer
5.16
316197AC1-042 GEN
Solar/Wind Helper
0.711
24728405LEESVG
50/50
0.619
24684605SMG4
50/50
2.601
270197AD1-017 GEN1
Solar/Wind Harmer
3.493
3147312GRETNA
Solar/Wind Helper
0.151
316248AF1-058 C
Solar/Wind Helper
0.182
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.53
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.09
LGEELTFEXP_LGEE->PJM
CLTF
0.102
WECLTFEXP_WEC->PJM
CLTF
0.047
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.462
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.176
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.725
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.075
MECLTFEXP_MEC->PJM
CLTF
0.162
SIGELTFEXP_SIGE->PJM
CLTF
0.007

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.49 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:330.82
MW Contribution:29.65
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Helper
2.409
3147173SINAI
Solar/Wind Helper
0.131
3147243WELCO
Solar/Wind Helper
0.082
316118AC1-105 GEN
Solar/Wind Helper
0.455
24684405SMG2
50/50
2.574
24684505SMG3
50/50
1.592
24684305SMG1
50/50
0.933
270013AE1-250 PV
Solar/Wind Harmer
5.141
316197AC1-042 GEN
Solar/Wind Helper
0.712
24728405LEESVG
50/50
0.616
24684705SMG5
50/50
0.991
970481AG2-311 GEN
50/50
13.817
270574AD1-017 GEN2
Solar/Wind Harmer
11.581
270016AE1-250 BESS
Solar/Wind Harmer
5.141
970223AG2-152 GEN
Solar/Wind Harmer
29.649
270173AC1-122 GEN
Solar/Wind Harmer
2.215
3147312GRETNA
Solar/Wind Helper
0.607
3146802CHATHAM
Solar/Wind Helper
0.569
3147123OTTER R
Solar/Wind Helper
0.407
316003AC1-222 GEN
Solar/Wind Helper
0.819
24728405LEESVG
50/50
0.619
24684605SMG4
50/50
2.591
270197AD1-017 GEN1
Solar/Wind Harmer
3.48
3147312GRETNA
Solar/Wind Helper
0.152
316248AF1-058 C
Solar/Wind Helper
0.177
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.474
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.085
LGEELTFEXP_LGEE->PJM
CLTF
0.084
WECLTFEXP_WEC->PJM
CLTF
0.038
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.368
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.414
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.075
MECLTFEXP_MEC->PJM
CLTF
0.135
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:115.7 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:328.58
MW Contribution:29.65
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Helper
2.409
3147173SINAI
Solar/Wind Helper
0.131
3147243WELCO
Solar/Wind Helper
0.082
316118AC1-105 GEN
Solar/Wind Helper
0.455
24684405SMG2
50/50
2.574
24684505SMG3
50/50
1.592
24684305SMG1
50/50
0.933
270013AE1-250 PV
Solar/Wind Harmer
5.141
316197AC1-042 GEN
Solar/Wind Helper
0.712
24728405LEESVG
50/50
0.616
24684705SMG5
50/50
0.991
970481AG2-311 GEN
50/50
13.817
270574AD1-017 GEN2
Solar/Wind Harmer
11.581
270016AE1-250 BESS
Solar/Wind Harmer
5.141
970223AG2-152 GEN
Solar/Wind Harmer
29.649
270173AC1-122 GEN
Solar/Wind Harmer
2.215
3147312GRETNA
Solar/Wind Helper
0.607
3146802CHATHAM
Solar/Wind Helper
0.569
3147123OTTER R
Solar/Wind Helper
0.407
316003AC1-222 GEN
Solar/Wind Helper
0.819
24728405LEESVG
50/50
0.619
24684605SMG4
50/50
2.591
270197AD1-017 GEN1
Solar/Wind Harmer
3.48
3147312GRETNA
Solar/Wind Helper
0.152
316248AF1-058 C
Solar/Wind Helper
0.177
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.474
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.085
LGEELTFEXP_LGEE->PJM
CLTF
0.084
WECLTFEXP_WEC->PJM
CLTF
0.038
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.368
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.414
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.075
MECLTFEXP_MEC->PJM
CLTF
0.135
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P7-1_#10778___SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10778___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:115.69 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:328.56
MW Contribution:29.65
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
2.574
24684505SMG3
50/50
1.592
24684305SMG1
50/50
0.933
270013AE1-250 PV
Solar/Wind Harmer
5.141
316197AC1-042 GEN
Solar/Wind Helper
0.712
316123AC1-075 GEN
Solar/Wind Helper
2.409
3147173SINAI
Solar/Wind Helper
0.131
3147243WELCO
Solar/Wind Helper
0.082
316118AC1-105 GEN
Solar/Wind Helper
0.455
24728405LEESVG
50/50
0.616
24684705SMG5
50/50
0.991
970481AG2-311 GEN
50/50
13.817
270574AD1-017 GEN2
Solar/Wind Harmer
11.582
270016AE1-250 BESS
Solar/Wind Harmer
5.141
970223AG2-152 GEN
Solar/Wind Harmer
29.65
270173AC1-122 GEN
Solar/Wind Harmer
2.215
3147312GRETNA
Solar/Wind Helper
0.607
3146802CHATHAM
Solar/Wind Helper
0.569
3147123OTTER R
Solar/Wind Helper
0.407
316003AC1-222 GEN
Solar/Wind Helper
0.819
24728405LEESVG
50/50
0.619
24684605SMG4
50/50
2.591
270197AD1-017 GEN1
Solar/Wind Harmer
3.48
3147312GRETNA
Solar/Wind Helper
0.152
316248AF1-058 C
Solar/Wind Helper
0.177
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.474
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.085
LGEELTFEXP_LGEE->PJM
CLTF
0.084
WECLTFEXP_WEC->PJM
CLTF
0.038
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.368
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.414
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.075
MECLTFEXP_MEC->PJM
CLTF
0.135
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#10687_05EDAN 2 138_N_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10687_05EDAN 2 138_N_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.68 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:328.54
MW Contribution:29.65
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.616
24684705SMG5
50/50
0.991
970481AG2-311 GEN
50/50
13.817
270574AD1-017 GEN2
Solar/Wind Harmer
11.582
270016AE1-250 BESS
Solar/Wind Harmer
5.141
970223AG2-152 GEN
Solar/Wind Harmer
29.65
270173AC1-122 GEN
Solar/Wind Harmer
2.215
3147312GRETNA
Solar/Wind Helper
0.607
3146802CHATHAM
Solar/Wind Helper
0.569
3147123OTTER R
Solar/Wind Helper
0.407
316003AC1-222 GEN
Solar/Wind Helper
0.819
316123AC1-075 GEN
Solar/Wind Helper
2.409
3147173SINAI
Solar/Wind Helper
0.131
3147243WELCO
Solar/Wind Helper
0.082
316118AC1-105 GEN
Solar/Wind Helper
0.455
24684405SMG2
50/50
2.574
24684505SMG3
50/50
1.592
24684305SMG1
50/50
0.933
270013AE1-250 PV
Solar/Wind Harmer
5.141
316197AC1-042 GEN
Solar/Wind Helper
0.712
24728405LEESVG
50/50
0.619
24684605SMG4
50/50
2.591
270197AD1-017 GEN1
Solar/Wind Harmer
3.48
3147312GRETNA
Solar/Wind Helper
0.152
316248AF1-058 C
Solar/Wind Helper
0.177
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.474
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.085
LGEELTFEXP_LGEE->PJM
CLTF
0.084
WECLTFEXP_WEC->PJM
CLTF
0.038
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.368
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.414
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.075
MECLTFEXP_MEC->PJM
CLTF
0.135
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#8676_05EDANV2 230_S_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8676_05EDANV2 230_S_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.67 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:328.5
MW Contribution:29.65
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.619
24684605SMG4
50/50
2.591
270197AD1-017 GEN1
Solar/Wind Harmer
3.48
3147312GRETNA
Solar/Wind Helper
0.152
316248AF1-058 C
Solar/Wind Helper
0.177
24728405LEESVG
50/50
0.616
24684705SMG5
50/50
0.991
970481AG2-311 GEN
50/50
13.817
270574AD1-017 GEN2
Solar/Wind Harmer
11.581
270016AE1-250 BESS
Solar/Wind Harmer
5.141
970223AG2-152 GEN
Solar/Wind Harmer
29.649
270173AC1-122 GEN
Solar/Wind Harmer
2.215
3147312GRETNA
Solar/Wind Helper
0.607
3146802CHATHAM
Solar/Wind Helper
0.569
3147123OTTER R
Solar/Wind Helper
0.407
316003AC1-222 GEN
Solar/Wind Helper
0.819
24684405SMG2
50/50
2.574
24684505SMG3
50/50
1.592
24684305SMG1
50/50
0.933
270013AE1-250 PV
Solar/Wind Harmer
5.141
316197AC1-042 GEN
Solar/Wind Helper
0.712
316123AC1-075 GEN
Solar/Wind Helper
2.409
3147173SINAI
Solar/Wind Helper
0.131
3147243WELCO
Solar/Wind Helper
0.082
316118AC1-105 GEN
Solar/Wind Helper
0.455
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.474
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.085
LGEELTFEXP_LGEE->PJM
CLTF
0.084
WECLTFEXP_WEC->PJM
CLTF
0.038
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.368
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.414
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.075
MECLTFEXP_MEC->PJM
CLTF
0.135
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P1-2_#5366_SRT-A-1


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#5366_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.86 %
Rating:266.96 MVA
Rating Type:B
MVA to Mitigate:295.95
MW Contribution:20.77
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
2.572
24684505SMG3
50/50
1.591
24684305SMG1
50/50
0.933
270013AE1-250 PV
Solar/Wind Harmer
0.009
316197AC1-042 GEN
Solar/Wind Helper
0.712
24728405LEESVG
50/50
0.616
24684705SMG5
50/50
0.991
970481AG2-311 GEN
50/50
13.806
270574AD1-017 GEN2
Solar/Wind Harmer
0.002
270016AE1-250 BESS
Solar/Wind Harmer
0.009
970223AG2-152 GEN
Solar/Wind Harmer
20.775
270173AC1-122 GEN
Solar/Wind Harmer
0.457
3147312GRETNA
Solar/Wind Helper
0.607
3146802CHATHAM
Solar/Wind Helper
0.569
3147123OTTER R
Solar/Wind Helper
0.407
316003AC1-222 GEN
Solar/Wind Helper
0.816
316123AC1-075 GEN
Solar/Wind Helper
2.407
3147173SINAI
Solar/Wind Helper
0.13
3147243WELCO
Solar/Wind Helper
0.082
316118AC1-105 GEN
Solar/Wind Helper
0.452
24728405LEESVG
50/50
0.618
24684605SMG4
50/50
2.589
270197AD1-017 GEN1
Solar/Wind Harmer
1.952
3147312GRETNA
Solar/Wind Helper
0.152
316248AF1-058 C
Solar/Wind Helper
0.175
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.464
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.084
LGEELTFEXP_LGEE->PJM
CLTF
0.081
WECLTFEXP_WEC->PJM
CLTF
0.037
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.349
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.131
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.352
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.076
MECLTFEXP_MEC->PJM
CLTF
0.129
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P1-3_#10688_05EDANV2 230_4_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-3_#10688_05EDANV2 230_4_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.35 %
Rating:266.96 MVA
Rating Type:B
MVA to Mitigate:294.6
MW Contribution:20.79
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.616
24684705SMG5
50/50
0.991
970481AG2-311 GEN
50/50
13.817
270574AD1-017 GEN2
Solar/Wind Harmer
0.002
270016AE1-250 BESS
Solar/Wind Harmer
0.009
970223AG2-152 GEN
Solar/Wind Harmer
20.791
270173AC1-122 GEN
Solar/Wind Harmer
0.457
3147312GRETNA
Solar/Wind Helper
0.607
3146802CHATHAM
Solar/Wind Helper
0.569
3147123OTTER R
Solar/Wind Helper
0.407
316003AC1-222 GEN
Solar/Wind Helper
0.819
316123AC1-075 GEN
Solar/Wind Helper
2.409
3147173SINAI
Solar/Wind Helper
0.131
3147243WELCO
Solar/Wind Helper
0.082
316118AC1-105 GEN
Solar/Wind Helper
0.455
24728405LEESVG
50/50
0.619
24684605SMG4
50/50
2.591
270197AD1-017 GEN1
Solar/Wind Harmer
1.954
3147312GRETNA
Solar/Wind Helper
0.152
316248AF1-058 C
Solar/Wind Helper
0.177
24684405SMG2
50/50
2.574
24684505SMG3
50/50
1.592
24684305SMG1
50/50
0.933
270013AE1-250 PV
Solar/Wind Harmer
0.009
316197AC1-042 GEN
Solar/Wind Helper
0.712
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.474
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.085
LGEELTFEXP_LGEE->PJM
CLTF
0.084
WECLTFEXP_WEC->PJM
CLTF
0.038
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.368
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.414
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.075
MECLTFEXP_MEC->PJM
CLTF
0.135
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#10213_05CLOVRD 138_A_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10213_05CLOVRD 138_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.32 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:301.96
MW Contribution:13.56
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Helper
2.304
24728405LEESVG
50/50
0.627
24684405SMG2
50/50
2.657
24684505SMG3
50/50
1.644
24684305SMG1
50/50
0.963
270013AE1-250 PV
Solar/Wind Harmer
2.778
316197AC1-042 GEN
Solar/Wind Helper
0.705
24728405LEESVG
50/50
0.624
24684705SMG5
50/50
1.023
970481AG2-311 GEN
50/50
14.263
270574AD1-017 GEN2
Solar/Wind Harmer
8.687
270173AC1-122 GEN
Solar/Wind Harmer
2.265
270016AE1-250 BESS
Solar/Wind Harmer
2.778
970223AG2-152 GEN
Solar/Wind Harmer
13.563
3147312GRETNA
Solar/Wind Helper
0.601
3146802CHATHAM
Solar/Wind Helper
0.564
3147123OTTER R
Solar/Wind Helper
0.402
316003AC1-222 GEN
Solar/Wind Helper
0.716
24684605SMG4
50/50
2.675
270197AD1-017 GEN1
Solar/Wind Harmer
2.61
3147312GRETNA
Solar/Wind Helper
0.15
LAGNLTFEXP_LAGN->PJM
CLTF
0.303
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.003
TVALTFEXP_TVA->PJM
CLTF
0.153
CPLELTFEXP_CPLE->PJM
CLTF
0.438
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.568
NYPJM->LTFIMP_NY
CLTF
0.088
LGEELTFEXP_LGEE->PJM
CLTF
0.05
WECLTFEXP_WEC->PJM
CLTF
0.025
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.842
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.522
MECLTFEXP_MEC->PJM
CLTF
0.138
SIGELTFEXP_SIGE->PJM
CLTF
0.004

Details for [AG2-152] 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.85 %
Rating:192.7 MVA
Rating Type:A
MVA to Mitigate:202.04
MW Contribution:11.36
IPD Plant:AG2-152
Bus #Bus NameTypeMW Contribution
970223AG2-152 GEN
PJM_IPD
11.363

Details for [AG2-152] 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P1-2_#5366_SRT-A-1


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#5366_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.26 %
Rating:266.96 MVA
Rating Type:B
MVA to Mitigate:272.98
MW Contribution:34.45
IPD Plant:AG2-152
Bus #Bus NameTypeMW Contribution
970223AG2-152 GEN
PJM_IPD
34.449

Details for [AG2-152] 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P1-3_#10688_05EDANV2 230_4_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-3_#10688_05EDANV2 230_4_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.72 %
Rating:266.96 MVA
Rating Type:B
MVA to Mitigate:271.56
MW Contribution:34.48
IPD Plant:AG2-152
Bus #Bus NameTypeMW Contribution
970223AG2-152 GEN
PJM_IPD
34.476

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P7-1_#10781___SRT-A-1


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10781___SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.01 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:284.01
MW Contribution:15.21
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
2.143
24684505SMG3
50/50
1.326
24684305SMG1
50/50
0.777
270013AE1-250 PV
Solar/Wind Harmer
2.875
316197AC1-042 GEN
Solar/Wind Helper
0.762
3146843MT LREL
Solar/Wind Helper
0.114
3146843MT LREL
Solar/Wind Helper
0.114
316123AC1-075 GEN
Solar/Wind Helper
2.596
3147173SINAI
Solar/Wind Helper
0.145
3147243WELCO
Solar/Wind Helper
0.091
316118AC1-105 GEN
Solar/Wind Helper
0.504
24728405LEESVG
50/50
0.569
24684705SMG5
50/50
0.825
970481AG2-311 GEN
50/50
11.504
270574AD1-017 GEN2
Solar/Wind Harmer
7.826
270016AE1-250 BESS
Solar/Wind Harmer
2.875
970223AG2-152 GEN
Solar/Wind Harmer
15.211
270173AC1-122 GEN
Solar/Wind Harmer
1.769
3147312GRETNA
Solar/Wind Helper
0.65
3146802CHATHAM
Solar/Wind Helper
0.609
3147123OTTER R
Solar/Wind Helper
0.437
316003AC1-222 GEN
Solar/Wind Helper
0.895
24728405LEESVG
50/50
0.572
24684605SMG4
50/50
2.158
270197AD1-017 GEN1
Solar/Wind Harmer
2.352
270018AE2-047 C O1
Solar/Wind Harmer
0.617
943811AF1-049 GEN
Solar/Wind Harmer
1.677
3147312GRETNA
Solar/Wind Helper
0.162
316248AF1-058 C
Solar/Wind Helper
0.195
LAGNLTFEXP_LAGN->PJM
CLTF
0.11
TVALTFEXP_TVA->PJM
CLTF
0.08
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.64
NYPJM->LTFIMP_NY
CLTF
0.092
LGEELTFEXP_LGEE->PJM
CLTF
0.16
WECLTFEXP_WEC->PJM
CLTF
0.077
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.442
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.149
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.826
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.405
MECLTFEXP_MEC->PJM
CLTF
0.296
SIGELTFEXP_SIGE->PJM
CLTF
0.011

Details for 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.15 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:331.96
MW Contribution:112.58
Bus #Bus NameTypeMW Contribution
270574AD1-017 GEN2
Solar/Wind Harmer
43.973
270016AE1-250 BESS
Solar/Wind Harmer
19.519
970223AG2-152 GEN
Solar/Wind Harmer
112.575
270197AD1-017 GEN1
Solar/Wind Harmer
13.213
270013AE1-250 PV
Solar/Wind Harmer
19.519
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.042
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.131
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.042
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.044
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.027
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.196

Details for 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line l/o AEP_P4_#10162_05EDAN 1 138_P_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.26 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:323.4
MW Contribution:112.58
Bus #Bus NameTypeMW Contribution
270197AD1-017 GEN1
Solar/Wind Harmer
13.213
270013AE1-250 PV
Solar/Wind Harmer
19.519
270574AD1-017 GEN2
Solar/Wind Harmer
43.973
270016AE1-250 BESS
Solar/Wind Harmer
19.519
970223AG2-152 GEN
Solar/Wind Harmer
112.575
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.042
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.131
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.042
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.044
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.027
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.196

Details for 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line l/o AEP_P4_#8676_05EDANV2 230_S_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8676_05EDANV2 230_S_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.26 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:323.4
MW Contribution:112.58
Bus #Bus NameTypeMW Contribution
270013AE1-250 PV
Solar/Wind Harmer
19.519
270574AD1-017 GEN2
Solar/Wind Harmer
43.973
270016AE1-250 BESS
Solar/Wind Harmer
19.519
970223AG2-152 GEN
Solar/Wind Harmer
112.575
270197AD1-017 GEN1
Solar/Wind Harmer
13.213
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.042
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.131
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.042
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.044
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.027
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.196

Details for 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line l/o AEP_P4_#10687_05EDAN 2 138_N_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10687_05EDAN 2 138_N_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.26 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:323.4
MW Contribution:112.58
Bus #Bus NameTypeMW Contribution
270574AD1-017 GEN2
Solar/Wind Harmer
43.973
270016AE1-250 BESS
Solar/Wind Harmer
19.519
970223AG2-152 GEN
Solar/Wind Harmer
112.575
270197AD1-017 GEN1
Solar/Wind Harmer
13.213
270013AE1-250 PV
Solar/Wind Harmer
19.519
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.042
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.131
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.042
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.044
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.027
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.196

Details for 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line l/o AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:109.26 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:323.4
MW Contribution:112.58
Bus #Bus NameTypeMW Contribution
270197AD1-017 GEN1
Solar/Wind Harmer
13.213
270013AE1-250 PV
Solar/Wind Harmer
19.519
270574AD1-017 GEN2
Solar/Wind Harmer
43.973
270016AE1-250 BESS
Solar/Wind Harmer
19.519
970223AG2-152 GEN
Solar/Wind Harmer
112.575
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.042
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.131
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.042
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.044
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.027
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.196

Details for 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line l/o AEP_P7-1_#10778___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10778___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:109.26 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:323.4
MW Contribution:112.58
Bus #Bus NameTypeMW Contribution
270013AE1-250 PV
Solar/Wind Harmer
19.519
270197AD1-017 GEN1
Solar/Wind Harmer
13.213
270574AD1-017 GEN2
Solar/Wind Harmer
43.973
270016AE1-250 BESS
Solar/Wind Harmer
19.519
970223AG2-152 GEN
Solar/Wind Harmer
112.575
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.042
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.131
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.042
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.044
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.027
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.196

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o DVP_P4-2: 151T1047_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 151T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:136.34 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:334.02
MW Contribution:6.6
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.266
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.139
971683AH1-343 GEN
Solar/Wind Harmer
22.238
270197AD1-017 GEN1
Solar/Wind Harmer
1.246
316123AC1-075 GEN
Solar/Wind Harmer
5.564
970865AG2-541 GEN
Solar/Wind Harmer
20.949
970165AG2-112 GEN
Solar/Wind Harmer
4.899
970163AG2-111 GEN
Solar/Wind Harmer
4.673
3151561HALLBR1
50/50
1.184
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.484
970481AG2-311 GEN
50/50
6.751
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.139
316003AC1-222 GEN
Solar/Wind Harmer
5.036
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.147
270016AE1-250 BESS
Solar/Wind Harmer
1.342
270173AC1-122 GEN
Solar/Wind Harmer
0.85
970223AG2-152 GEN
Solar/Wind Harmer
6.601
24684405SMG2
50/50
1.258
24684505SMG3
50/50
0.778
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.716
316197AC1-042 GEN
Solar/Wind Harmer
6.608
942671AE2-283 GEN
Solar/Wind Harmer
17.789
942751AE2-291 GEN
Solar/Wind Harmer
32.874
270013AE1-250 PV
Solar/Wind Harmer
1.342
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.061
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
0.013
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.831
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.484
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.065
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.177

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o DVP_P4-2: 104702_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104702_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:136.33 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:334.0
MW Contribution:6.6
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Harmer
5.564
970865AG2-541 GEN
Solar/Wind Harmer
20.949
970165AG2-112 GEN
Solar/Wind Harmer
4.899
970163AG2-111 GEN
Solar/Wind Harmer
4.673
24684405SMG2
50/50
1.258
24684505SMG3
50/50
0.778
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.716
316197AC1-042 GEN
Solar/Wind Harmer
6.608
942671AE2-283 GEN
Solar/Wind Harmer
17.789
942751AE2-291 GEN
Solar/Wind Harmer
32.874
270013AE1-250 PV
Solar/Wind Harmer
1.342
3151561HALLBR1
50/50
1.184
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.484
970481AG2-311 GEN
50/50
6.751
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.139
316003AC1-222 GEN
Solar/Wind Harmer
5.035
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.147
270016AE1-250 BESS
Solar/Wind Harmer
1.342
270173AC1-122 GEN
Solar/Wind Harmer
0.85
970223AG2-152 GEN
Solar/Wind Harmer
6.6
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.266
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.139
971683AH1-343 GEN
Solar/Wind Harmer
22.238
270197AD1-017 GEN1
Solar/Wind Harmer
1.246
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.061
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
0.012
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.829
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.484
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.065
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.178

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o DVP_P4-2: 1016T1047_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 1016T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:129.43 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:317.11
MW Contribution:6.61
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.143
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.151
270016AE1-250 BESS
Solar/Wind Harmer
1.344
270173AC1-122 GEN
Solar/Wind Harmer
0.851
970223AG2-152 GEN
Solar/Wind Harmer
6.611
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.718
316197AC1-042 GEN
Solar/Wind Harmer
6.609
942671AE2-283 GEN
Solar/Wind Harmer
17.793
942751AE2-291 GEN
Solar/Wind Harmer
32.881
270013AE1-250 PV
Solar/Wind Harmer
1.344
316123AC1-075 GEN
Solar/Wind Harmer
5.565
970865AG2-541 GEN
Solar/Wind Harmer
20.954
970165AG2-112 GEN
Solar/Wind Harmer
4.9
970163AG2-111 GEN
Solar/Wind Harmer
4.674
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.143
971683AH1-343 GEN
Solar/Wind Harmer
22.243
270197AD1-017 GEN1
Solar/Wind Harmer
1.247
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.029
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007
CPLELTFEXP_CPLE->PJM
CLTF
0.492
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.06
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.153

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o DVP_P4-2: 101672_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 101672_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:129.42 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:317.07
MW Contribution:6.61
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Harmer
5.565
970865AG2-541 GEN
Solar/Wind Harmer
20.954
970165AG2-112 GEN
Solar/Wind Harmer
4.9
970163AG2-111 GEN
Solar/Wind Harmer
4.674
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.143
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.151
270016AE1-250 BESS
Solar/Wind Harmer
1.344
270173AC1-122 GEN
Solar/Wind Harmer
0.851
970223AG2-152 GEN
Solar/Wind Harmer
6.611
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.718
316197AC1-042 GEN
Solar/Wind Harmer
6.609
942671AE2-283 GEN
Solar/Wind Harmer
17.793
942751AE2-291 GEN
Solar/Wind Harmer
32.881
270013AE1-250 PV
Solar/Wind Harmer
1.344
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.143
971683AH1-343 GEN
Solar/Wind Harmer
22.243
270197AD1-017 GEN1
Solar/Wind Harmer
1.247
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.029
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007
CPLELTFEXP_CPLE->PJM
CLTF
0.492
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.06
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.153

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o DVP_P4-2: 104772_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104772_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.97 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:313.53
MW Contribution:6.61
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Harmer
5.565
970865AG2-541 GEN
Solar/Wind Harmer
20.954
970165AG2-112 GEN
Solar/Wind Harmer
4.9
970163AG2-111 GEN
Solar/Wind Harmer
4.674
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.718
316197AC1-042 GEN
Solar/Wind Harmer
6.609
942671AE2-283 GEN
Solar/Wind Harmer
17.793
942751AE2-291 GEN
Solar/Wind Harmer
32.881
270013AE1-250 PV
Solar/Wind Harmer
1.344
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.143
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.151
270016AE1-250 BESS
Solar/Wind Harmer
1.344
270173AC1-122 GEN
Solar/Wind Harmer
0.851
970223AG2-152 GEN
Solar/Wind Harmer
6.611
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.143
971683AH1-343 GEN
Solar/Wind Harmer
22.243
270197AD1-017 GEN1
Solar/Wind Harmer
1.247
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.029
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007
CPLELTFEXP_CPLE->PJM
CLTF
0.492
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.06
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.153

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 1047_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1047_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.67 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:263.78
MW Contribution:4.63
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.266
3147312GRETNA
Solar/Wind Harmer
0.096
941821AE2-187 GEN
Solar/Wind Harmer
15.295
971683AH1-343 GEN
Solar/Wind Harmer
16.89
270197AD1-017 GEN1
Solar/Wind Harmer
0.699
316123AC1-075 GEN
Solar/Wind Harmer
0.627
970865AG2-541 GEN
Solar/Wind Harmer
15.911
970165AG2-112 GEN
Solar/Wind Harmer
3.721
970163AG2-111 GEN
Solar/Wind Harmer
3.549
3151561HALLBR1
50/50
1.184
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.484
970481AG2-311 GEN
50/50
6.751
3147312GRETNA
Solar/Wind Harmer
0.382
3146802CHATHAM
Solar/Wind Harmer
0.358
941801AE2-185 GEN
Solar/Wind Harmer
15.295
316003AC1-222 GEN
Solar/Wind Harmer
0.012
3147123OTTER R
Solar/Wind Harmer
0.275
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.002
270173AC1-122 GEN
Solar/Wind Harmer
0.175
970223AG2-152 GEN
Solar/Wind Harmer
4.628
24684405SMG2
50/50
1.258
24684505SMG3
50/50
0.778
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
0.006
316197AC1-042 GEN
Solar/Wind Harmer
0.005
942671AE2-283 GEN
Solar/Wind Harmer
11.896
942751AE2-291 GEN
Solar/Wind Harmer
24.967
270013AE1-250 PV
Solar/Wind Harmer
0.002
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.061
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
0.012
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.829
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.484
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.065
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.178

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 1016_SRT-A-1


Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1016_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.87 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:252.04
MW Contribution:4.64
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
0.006
316197AC1-042 GEN
Solar/Wind Harmer
0.005
942671AE2-283 GEN
Solar/Wind Harmer
11.899
942751AE2-291 GEN
Solar/Wind Harmer
24.973
270013AE1-250 PV
Solar/Wind Harmer
0.002
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
0.382
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
0.096
941821AE2-187 GEN
Solar/Wind Harmer
15.299
971683AH1-343 GEN
Solar/Wind Harmer
16.893
270197AD1-017 GEN1
Solar/Wind Harmer
0.7
3146802CHATHAM
Solar/Wind Harmer
0.358
941801AE2-185 GEN
Solar/Wind Harmer
15.299
3147123OTTER R
Solar/Wind Harmer
0.275
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.002
270173AC1-122 GEN
Solar/Wind Harmer
0.176
970223AG2-152 GEN
Solar/Wind Harmer
4.636
316123AC1-075 GEN
Solar/Wind Harmer
0.628
970865AG2-541 GEN
Solar/Wind Harmer
15.914
970165AG2-112 GEN
Solar/Wind Harmer
3.721
970163AG2-111 GEN
Solar/Wind Harmer
3.55
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.028
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007
CPLELTFEXP_CPLE->PJM
CLTF
0.492
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.06
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.154

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.55 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:248.8
MW Contribution:13.8
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.32
24684605SMG4
50/50
1.206
3147312GRETNA
Solar/Wind Harmer
-0.009
941821AE2-187 GEN
Solar/Wind Harmer
16.868
270197AD1-017 GEN1
Solar/Wind Harmer
1.62
971683AH1-343 GEN
Solar/Wind Harmer
5.942
316248AF1-058 C
Solar/Wind Harmer
0.225
960061AF2-297 GEN
Solar/Wind Harmer
3.734
316123AC1-075 GEN
Solar/Wind Harmer
2.482
970165AG2-112 GEN
Solar/Wind Harmer
2.186
970163AG2-111 GEN
Solar/Wind Harmer
2.085
970865AG2-541 GEN
Solar/Wind Harmer
6.833
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.005
316118AC1-105 GEN
Solar/Wind Harmer
0.454
24684405SMG2
50/50
1.198
24684505SMG3
50/50
0.741
24684305SMG1
50/50
0.434
316217AC1-145 GEN
Solar/Wind Harmer
7.301
316197AC1-042 GEN
Solar/Wind Harmer
5.534
942671AE2-283 GEN
Solar/Wind Harmer
14.9
942751AE2-291 GEN
Solar/Wind Harmer
17.168
270013AE1-250 PV
Solar/Wind Harmer
2.392
3151561HALLBR1
50/50
0.931
24728405LEESVG
50/50
0.319
24684705SMG5
50/50
0.461
970481AG2-311 GEN
50/50
6.43
3147312GRETNA
Solar/Wind Harmer
-0.036
3146802CHATHAM
Solar/Wind Harmer
-0.034
941801AE2-185 GEN
Solar/Wind Harmer
16.868
3147123OTTER R
Solar/Wind Harmer
-0.024
270574AD1-017 GEN2
Solar/Wind Harmer
5.39
270016AE1-250 BESS
Solar/Wind Harmer
2.392
970223AG2-152 GEN
Solar/Wind Harmer
13.798
316003AC1-222 GEN
Solar/Wind Harmer
1.06
270173AC1-122 GEN
Solar/Wind Harmer
0.706
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.153
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.471
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.072
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.729
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.033
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.539

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o AEP_P7-1_#10778___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10778___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.55 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:248.79
MW Contribution:13.8
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.198
24684505SMG3
50/50
0.741
24684305SMG1
50/50
0.434
316217AC1-145 GEN
Solar/Wind Harmer
7.301
316197AC1-042 GEN
Solar/Wind Harmer
5.534
942671AE2-283 GEN
Solar/Wind Harmer
14.9
942751AE2-291 GEN
Solar/Wind Harmer
17.168
270013AE1-250 PV
Solar/Wind Harmer
2.392
316123AC1-075 GEN
Solar/Wind Harmer
2.482
970165AG2-112 GEN
Solar/Wind Harmer
2.186
970163AG2-111 GEN
Solar/Wind Harmer
2.085
970865AG2-541 GEN
Solar/Wind Harmer
6.833
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.005
316118AC1-105 GEN
Solar/Wind Harmer
0.454
3151561HALLBR1
50/50
0.931
24728405LEESVG
50/50
0.319
24684705SMG5
50/50
0.461
970481AG2-311 GEN
50/50
6.43
3147312GRETNA
Solar/Wind Harmer
-0.036
3146802CHATHAM
Solar/Wind Harmer
-0.034
941801AE2-185 GEN
Solar/Wind Harmer
16.868
3147123OTTER R
Solar/Wind Harmer
-0.024
270574AD1-017 GEN2
Solar/Wind Harmer
5.39
270016AE1-250 BESS
Solar/Wind Harmer
2.392
970223AG2-152 GEN
Solar/Wind Harmer
13.798
316003AC1-222 GEN
Solar/Wind Harmer
1.06
270173AC1-122 GEN
Solar/Wind Harmer
0.706
24728405LEESVG
50/50
0.32
24684605SMG4
50/50
1.206
3147312GRETNA
Solar/Wind Harmer
-0.009
941821AE2-187 GEN
Solar/Wind Harmer
16.868
270197AD1-017 GEN1
Solar/Wind Harmer
1.62
971683AH1-343 GEN
Solar/Wind Harmer
5.942
316248AF1-058 C
Solar/Wind Harmer
0.225
960061AF2-297 GEN
Solar/Wind Harmer
3.734
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.153
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.471
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.072
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.729
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.033
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.539

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o DVP_P2-2: ALTAVISTA 115KV_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: ALTAVISTA 115KV_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.37 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:245.9
MW Contribution:7.55
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.434
24684505SMG3
50/50
0.887
24684305SMG1
50/50
0.52
316217AC1-145 GEN
Solar/Wind Harmer
9.919
316197AC1-042 GEN
Solar/Wind Harmer
7.519
942671AE2-283 GEN
Solar/Wind Harmer
20.244
270013AE1-250 PV
Solar/Wind Harmer
1.533
24728405LEESVG
50/50
0.419
24684705SMG5
50/50
0.552
970481AG2-311 GEN
50/50
7.695
3147312GRETNA
Solar/Wind Harmer
-0.049
3146802CHATHAM
Solar/Wind Harmer
-0.046
941801AE2-185 GEN
Solar/Wind Harmer
22.918
270574AD1-017 GEN2
Solar/Wind Harmer
4.731
270016AE1-250 BESS
Solar/Wind Harmer
1.533
270173AC1-122 GEN
Solar/Wind Harmer
0.968
970223AG2-152 GEN
Solar/Wind Harmer
7.548
24728405LEESVG
50/50
0.421
24684605SMG4
50/50
1.443
3147312GRETNA
Solar/Wind Harmer
-0.012
941821AE2-187 GEN
Solar/Wind Harmer
22.918
270197AD1-017 GEN1
Solar/Wind Harmer
1.422
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.047
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.144
LAGNLTFEXP_LAGN->PJM
CLTF
0.083
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.044
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.034
CPLELTFEXP_CPLE->PJM
CLTF
0.586
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.054
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.099
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.056

Details for 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#10162_05EDAN 1 138_P_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.61 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:289.71
MW Contribution:29.79
Bus #Bus NameTypeMW Contribution
24684705SMG5
50/50
0.996
970481AG2-311 GEN
50/50
13.884
270574AD1-017 GEN2
Solar/Wind Harmer
11.637
270016AE1-250 BESS
Solar/Wind Harmer
5.166
970223AG2-152 GEN
Solar/Wind Harmer
29.792
270173AC1-122 GEN
Solar/Wind Harmer
2.231
3147312GRETNA
Solar/Wind Helper
0.606
3146802CHATHAM
Solar/Wind Helper
0.568
3147123OTTER R
Solar/Wind Helper
0.407
316003AC1-222 GEN
Solar/Wind Helper
0.834
24684605SMG4
50/50
2.604
270197AD1-017 GEN1
Solar/Wind Harmer
3.497
3147312GRETNA
Solar/Wind Helper
0.151
316248AF1-058 C
Solar/Wind Helper
0.182
316123AC1-075 GEN
Solar/Wind Helper
2.418
3147173SINAI
Solar/Wind Helper
0.135
3147243WELCO
Solar/Wind Helper
0.084
316118AC1-105 GEN
Solar/Wind Helper
0.469
24684405SMG2
50/50
2.587
24684505SMG3
50/50
1.6
24684305SMG1
50/50
0.938
270013AE1-250 PV
Solar/Wind Harmer
5.166
316197AC1-042 GEN
Solar/Wind Helper
0.71
TVALTFEXP_TVA->PJM
CLTF
0.016
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.849
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.074
LGEELTFEXP_LGEE->PJM
CLTF
0.118
WECLTFEXP_WEC->PJM
CLTF
0.056
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.446
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.167
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.07
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.165
MECLTFEXP_MEC->PJM
CLTF
0.201
SIGELTFEXP_SIGE->PJM
CLTF
0.008

Details for 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.02 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:288.2
MW Contribution:29.68
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Helper
2.405
3147173SINAI
Solar/Wind Helper
0.131
3147243WELCO
Solar/Wind Helper
0.082
316118AC1-105 GEN
Solar/Wind Helper
0.453
24684705SMG5
50/50
0.992
970481AG2-311 GEN
50/50
13.831
270574AD1-017 GEN2
Solar/Wind Harmer
11.593
270016AE1-250 BESS
Solar/Wind Harmer
5.146
970223AG2-152 GEN
Solar/Wind Harmer
29.68
270173AC1-122 GEN
Solar/Wind Harmer
2.218
3147312GRETNA
Solar/Wind Helper
0.606
3146802CHATHAM
Solar/Wind Helper
0.568
3147123OTTER R
Solar/Wind Helper
0.407
316003AC1-222 GEN
Solar/Wind Helper
0.817
24684405SMG2
50/50
2.577
24684505SMG3
50/50
1.594
24684305SMG1
50/50
0.934
270013AE1-250 PV
Solar/Wind Harmer
5.146
316197AC1-042 GEN
Solar/Wind Helper
0.711
24684605SMG4
50/50
2.594
270197AD1-017 GEN1
Solar/Wind Harmer
3.484
3147312GRETNA
Solar/Wind Helper
0.152
316248AF1-058 C
Solar/Wind Helper
0.176
LAGNLTFEXP_LAGN->PJM
CLTF
0.01
TVALTFEXP_TVA->PJM
CLTF
0.021
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.792
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.07
LGEELTFEXP_LGEE->PJM
CLTF
0.101
WECLTFEXP_WEC->PJM
CLTF
0.047
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.352
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.129
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.759
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.165
MECLTFEXP_MEC->PJM
CLTF
0.174
SIGELTFEXP_SIGE->PJM
CLTF
0.007

Details for 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:112.15 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:285.97
MW Contribution:29.68
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
2.577
24684505SMG3
50/50
1.594
24684305SMG1
50/50
0.934
270013AE1-250 PV
Solar/Wind Harmer
5.146
316197AC1-042 GEN
Solar/Wind Helper
0.711
316123AC1-075 GEN
Solar/Wind Helper
2.405
3147173SINAI
Solar/Wind Helper
0.131
3147243WELCO
Solar/Wind Helper
0.082
316118AC1-105 GEN
Solar/Wind Helper
0.453
24684705SMG5
50/50
0.992
970481AG2-311 GEN
50/50
13.831
270574AD1-017 GEN2
Solar/Wind Harmer
11.593
270016AE1-250 BESS
Solar/Wind Harmer
5.146
970223AG2-152 GEN
Solar/Wind Harmer
29.68
270173AC1-122 GEN
Solar/Wind Harmer
2.218
3147312GRETNA
Solar/Wind Helper
0.606
3146802CHATHAM
Solar/Wind Helper
0.568
3147123OTTER R
Solar/Wind Helper
0.407
316003AC1-222 GEN
Solar/Wind Helper
0.817
24684605SMG4
50/50
2.594
270197AD1-017 GEN1
Solar/Wind Harmer
3.484
3147312GRETNA
Solar/Wind Helper
0.152
316248AF1-058 C
Solar/Wind Helper
0.176
LAGNLTFEXP_LAGN->PJM
CLTF
0.01
TVALTFEXP_TVA->PJM
CLTF
0.021
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.792
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.07
LGEELTFEXP_LGEE->PJM
CLTF
0.101
WECLTFEXP_WEC->PJM
CLTF
0.047
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.352
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.129
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.759
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.165
MECLTFEXP_MEC->PJM
CLTF
0.174
SIGELTFEXP_SIGE->PJM
CLTF
0.007

Details for 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P7-1_#10778___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10778___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:112.13 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:285.94
MW Contribution:29.68
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Helper
2.405
3147173SINAI
Solar/Wind Helper
0.131
3147243WELCO
Solar/Wind Helper
0.082
316118AC1-105 GEN
Solar/Wind Helper
0.453
24684405SMG2
50/50
2.577
24684505SMG3
50/50
1.594
24684305SMG1
50/50
0.934
270013AE1-250 PV
Solar/Wind Harmer
5.146
316197AC1-042 GEN
Solar/Wind Helper
0.711
24684605SMG4
50/50
2.594
270197AD1-017 GEN1
Solar/Wind Harmer
3.484
3147312GRETNA
Solar/Wind Helper
0.152
316248AF1-058 C
Solar/Wind Helper
0.176
24684705SMG5
50/50
0.992
970481AG2-311 GEN
50/50
13.832
270574AD1-017 GEN2
Solar/Wind Harmer
11.594
270016AE1-250 BESS
Solar/Wind Harmer
5.146
970223AG2-152 GEN
Solar/Wind Harmer
29.681
270173AC1-122 GEN
Solar/Wind Harmer
2.219
3147312GRETNA
Solar/Wind Helper
0.606
3146802CHATHAM
Solar/Wind Helper
0.568
3147123OTTER R
Solar/Wind Helper
0.407
316003AC1-222 GEN
Solar/Wind Helper
0.817
LAGNLTFEXP_LAGN->PJM
CLTF
0.01
TVALTFEXP_TVA->PJM
CLTF
0.021
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.792
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.07
LGEELTFEXP_LGEE->PJM
CLTF
0.101
WECLTFEXP_WEC->PJM
CLTF
0.047
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.353
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.129
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.759
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.165
MECLTFEXP_MEC->PJM
CLTF
0.174
SIGELTFEXP_SIGE->PJM
CLTF
0.007

Details for 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#10687_05EDAN 2 138_N_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10687_05EDAN 2 138_N_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.13 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:285.92
MW Contribution:29.68
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Helper
2.405
3147173SINAI
Solar/Wind Helper
0.131
3147243WELCO
Solar/Wind Helper
0.082
316118AC1-105 GEN
Solar/Wind Helper
0.453
24684705SMG5
50/50
0.992
970481AG2-311 GEN
50/50
13.832
270574AD1-017 GEN2
Solar/Wind Harmer
11.594
270016AE1-250 BESS
Solar/Wind Harmer
5.146
970223AG2-152 GEN
Solar/Wind Harmer
29.681
270173AC1-122 GEN
Solar/Wind Harmer
2.219
3147312GRETNA
Solar/Wind Helper
0.606
3146802CHATHAM
Solar/Wind Helper
0.568
3147123OTTER R
Solar/Wind Helper
0.407
316003AC1-222 GEN
Solar/Wind Helper
0.817
24684405SMG2
50/50
2.577
24684505SMG3
50/50
1.594
24684305SMG1
50/50
0.934
270013AE1-250 PV
Solar/Wind Harmer
5.146
316197AC1-042 GEN
Solar/Wind Helper
0.711
24684605SMG4
50/50
2.594
270197AD1-017 GEN1
Solar/Wind Harmer
3.484
3147312GRETNA
Solar/Wind Helper
0.152
316248AF1-058 C
Solar/Wind Helper
0.176
LAGNLTFEXP_LAGN->PJM
CLTF
0.01
TVALTFEXP_TVA->PJM
CLTF
0.021
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.792
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.07
LGEELTFEXP_LGEE->PJM
CLTF
0.101
WECLTFEXP_WEC->PJM
CLTF
0.047
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.353
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.129
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.759
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.165
MECLTFEXP_MEC->PJM
CLTF
0.174
SIGELTFEXP_SIGE->PJM
CLTF
0.007

Details for 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#8676_05EDANV2 230_S_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8676_05EDANV2 230_S_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.11 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:285.89
MW Contribution:29.68
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Helper
2.405
3147173SINAI
Solar/Wind Helper
0.131
3147243WELCO
Solar/Wind Helper
0.082
316118AC1-105 GEN
Solar/Wind Helper
0.453
24684405SMG2
50/50
2.577
24684505SMG3
50/50
1.594
24684305SMG1
50/50
0.934
270013AE1-250 PV
Solar/Wind Harmer
5.146
316197AC1-042 GEN
Solar/Wind Helper
0.711
24684705SMG5
50/50
0.992
970481AG2-311 GEN
50/50
13.831
270574AD1-017 GEN2
Solar/Wind Harmer
11.593
270016AE1-250 BESS
Solar/Wind Harmer
5.146
970223AG2-152 GEN
Solar/Wind Harmer
29.68
270173AC1-122 GEN
Solar/Wind Harmer
2.218
3147312GRETNA
Solar/Wind Helper
0.606
3146802CHATHAM
Solar/Wind Helper
0.568
3147123OTTER R
Solar/Wind Helper
0.407
316003AC1-222 GEN
Solar/Wind Helper
0.817
24684605SMG4
50/50
2.594
270197AD1-017 GEN1
Solar/Wind Harmer
3.484
3147312GRETNA
Solar/Wind Helper
0.152
316248AF1-058 C
Solar/Wind Helper
0.176
LAGNLTFEXP_LAGN->PJM
CLTF
0.01
TVALTFEXP_TVA->PJM
CLTF
0.021
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.792
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.07
LGEELTFEXP_LGEE->PJM
CLTF
0.101
WECLTFEXP_WEC->PJM
CLTF
0.047
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.352
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.129
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.759
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.165
MECLTFEXP_MEC->PJM
CLTF
0.174
SIGELTFEXP_SIGE->PJM
CLTF
0.007

Details for 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#10213_05CLOVRD 138_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10213_05CLOVRD 138_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.78 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:259.55
MW Contribution:13.59
Bus #Bus NameTypeMW Contribution
24684705SMG5
50/50
1.024
970481AG2-311 GEN
50/50
14.277
270574AD1-017 GEN2
Solar/Wind Harmer
8.699
270173AC1-122 GEN
Solar/Wind Harmer
2.269
270016AE1-250 BESS
Solar/Wind Harmer
2.784
970223AG2-152 GEN
Solar/Wind Harmer
13.594
3147312GRETNA
Solar/Wind Helper
0.601
3146802CHATHAM
Solar/Wind Helper
0.563
3147123OTTER R
Solar/Wind Helper
0.402
316003AC1-222 GEN
Solar/Wind Helper
0.713
24684605SMG4
50/50
2.678
270197AD1-017 GEN1
Solar/Wind Harmer
2.614
3147312GRETNA
Solar/Wind Helper
0.15
24684405SMG2
50/50
2.66
24684505SMG3
50/50
1.645
24684305SMG1
50/50
0.964
270013AE1-250 PV
Solar/Wind Harmer
2.784
316197AC1-042 GEN
Solar/Wind Helper
0.705
316123AC1-075 GEN
Solar/Wind Helper
2.3
LAGNLTFEXP_LAGN->PJM
CLTF
0.351
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.075
TVALTFEXP_TVA->PJM
CLTF
0.177
CPLELTFEXP_CPLE->PJM
CLTF
0.464
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.887
NYPJM->LTFIMP_NY
CLTF
0.072
LGEELTFEXP_LGEE->PJM
CLTF
0.066
WECLTFEXP_WEC->PJM
CLTF
0.034
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.187
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.612
MECLTFEXP_MEC->PJM
CLTF
0.178
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for 3CRSTL HILL-AC1-222 TAP 115.0 kV Ckt 1 line l/o AEP_P4_#10162_05EDAN 1 138_P_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3CRSTL HILL-AC1-222 TAP 115.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.59 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:352.07
MW Contribution:13.06
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
0.769
24728405LEESVG
50/50
0.229
24684705SMG5
50/50
0.437
970481AG2-311 GEN
50/50
6.086
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
24728405LEESVG
50/50
0.23
24684605SMG4
50/50
1.141
971683AH1-343 GEN
Solar/Wind Harmer
40.643
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.665
270197AD1-017 GEN1
Solar/Wind Harmer
1.533
958131AF2-107 GEN
Solar/Wind Harmer
2.307
316248AF1-058 C
Solar/Wind Helper
0.422
316131AB2-060 GEN
Solar/Wind Helper
0.886
315785AD2-033 C
Solar/Wind Helper
1.508
970865AG2-541 GEN
Solar/Wind Harmer
35.485
316123AC1-075 GEN
Solar/Wind Harmer
7.909
970165AG2-112 GEN
Solar/Wind Harmer
6.964
970163AG2-111 GEN
Solar/Wind Harmer
6.643
3147173SINAI
Solar/Wind Helper
0.314
3147243WELCO
Solar/Wind Helper
0.196
316118AC1-105 GEN
Solar/Wind Helper
1.086
316239AB2-077_GEN
Solar/Wind Helper
0.202
316238AB2-078_GEN
Solar/Wind Helper
0.202
3144303KENBRDG
Solar/Wind Helper
0.1
24684405SMG2
50/50
1.134
24684505SMG3
50/50
0.701
24684305SMG1
50/50
0.411
942751AE2-291 GEN
Solar/Wind Harmer
41.056
316217AC1-145 GEN
Solar/Wind Harmer
4.616
316197AC1-042 GEN
Solar/Wind Harmer
3.499
942671AE2-283 GEN
Solar/Wind Harmer
9.42
270013AE1-250 PV
Solar/Wind Harmer
2.264
3146843MT LREL
Solar/Wind Helper
0.245
3146843MT LREL
Solar/Wind Helper
0.245
316034AC1-036 C
Solar/Wind Helper
0.131
941801AE2-185 GEN
Solar/Wind Harmer
10.665
270574AD1-017 GEN2
Solar/Wind Harmer
5.101
270016AE1-250 BESS
Solar/Wind Harmer
2.264
970223AG2-152 GEN
Solar/Wind Harmer
13.058
270173AC1-122 GEN
Solar/Wind Harmer
1.401
962751AG1-124 GEN
Solar/Wind Harmer
5.108
316003AC1-222 GEN
Solar/Wind Helper
1.949
316237AB2-079_GEN
Solar/Wind Helper
0.202
315687AD1-152 GEN
Solar/Wind Helper
0.724
TVALTFEXP_TVA->PJM
CLTF
0.041
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.996
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.1
LGEELTFEXP_LGEE->PJM
CLTF
0.269
WECLTFEXP_WEC->PJM
CLTF
0.129
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.998
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.376
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.824
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.391
MECLTFEXP_MEC->PJM
CLTF
0.467
SIGELTFEXP_SIGE->PJM
CLTF
0.018

Details for 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line l/o AEP_P4_#10162_05EDAN 1 138_P_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.45 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:390.08
MW Contribution:13.03
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.132
24684505SMG3
50/50
0.7
24684305SMG1
50/50
0.41
942751AE2-291 GEN
Solar/Wind Harmer
41.038
316217AC1-145 GEN
Solar/Wind Harmer
4.611
316197AC1-042 GEN
Solar/Wind Harmer
3.495
942671AE2-283 GEN
Solar/Wind Harmer
9.411
270013AE1-250 PV
Solar/Wind Harmer
2.26
3146843MT LREL
Solar/Wind Helper
0.245
3146843MT LREL
Solar/Wind Helper
0.245
316034AC1-036 C
Solar/Wind Helper
0.132
3151561HALLBR1
50/50
0.769
24728405LEESVG
50/50
0.228
24684705SMG5
50/50
0.436
970481AG2-311 GEN
50/50
6.074
316003AC1-222 GEN
Solar/Wind Harmer
9.848
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.654
270574AD1-017 GEN2
Solar/Wind Harmer
5.091
270016AE1-250 BESS
Solar/Wind Harmer
2.26
970223AG2-152 GEN
Solar/Wind Harmer
13.033
270173AC1-122 GEN
Solar/Wind Harmer
1.398
962751AG1-124 GEN
Solar/Wind Harmer
5.091
316237AB2-079_GEN
Solar/Wind Helper
0.203
315687AD1-152 GEN
Solar/Wind Helper
0.727
970865AG2-541 GEN
Solar/Wind Harmer
35.473
316123AC1-075 GEN
Solar/Wind Harmer
7.906
970165AG2-112 GEN
Solar/Wind Harmer
6.961
970163AG2-111 GEN
Solar/Wind Harmer
6.641
3147173SINAI
Solar/Wind Helper
0.315
3147243WELCO
Solar/Wind Helper
0.197
316118AC1-105 GEN
Solar/Wind Helper
1.088
316239AB2-077_GEN
Solar/Wind Helper
0.203
316238AB2-078_GEN
Solar/Wind Helper
0.203
3144303KENBRDG
Solar/Wind Helper
0.101
24728405LEESVG
50/50
0.229
24684605SMG4
50/50
1.139
971683AH1-343 GEN
Solar/Wind Harmer
40.631
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.654
270197AD1-017 GEN1
Solar/Wind Harmer
1.53
958131AF2-107 GEN
Solar/Wind Harmer
2.297
316248AF1-058 C
Solar/Wind Helper
0.423
316131AB2-060 GEN
Solar/Wind Helper
0.889
315785AD2-033 C
Solar/Wind Helper
1.513
TVALTFEXP_TVA->PJM
CLTF
0.021
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.729
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.113
LGEELTFEXP_LGEE->PJM
CLTF
0.256
WECLTFEXP_WEC->PJM
CLTF
0.121
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.011
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.384
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.535
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.316
MECLTFEXP_MEC->PJM
CLTF
0.433
SIGELTFEXP_SIGE->PJM
CLTF
0.017

Details for 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.96 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:384.85
MW Contribution:12.85
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
0.767
24728405LEESVG
50/50
0.227
24684705SMG5
50/50
0.43
970481AG2-311 GEN
50/50
5.987
316003AC1-222 GEN
Solar/Wind Harmer
9.884
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.622
270574AD1-017 GEN2
Solar/Wind Harmer
5.018
270016AE1-250 BESS
Solar/Wind Harmer
2.228
970223AG2-152 GEN
Solar/Wind Harmer
12.847
270173AC1-122 GEN
Solar/Wind Harmer
1.377
962751AG1-124 GEN
Solar/Wind Harmer
5
316237AB2-079_GEN
Solar/Wind Helper
0.194
315687AD1-152 GEN
Solar/Wind Helper
0.686
24728405LEESVG
50/50
0.228
24684605SMG4
50/50
1.123
971683AH1-343 GEN
Solar/Wind Harmer
40.772
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.622
270197AD1-017 GEN1
Solar/Wind Harmer
1.508
958131AF2-107 GEN
Solar/Wind Harmer
2.266
316248AF1-058 C
Solar/Wind Helper
0.413
316131AB2-060 GEN
Solar/Wind Helper
0.85
315785AD2-033 C
Solar/Wind Helper
1.444
970865AG2-541 GEN
Solar/Wind Harmer
35.588
316123AC1-075 GEN
Solar/Wind Harmer
7.927
970165AG2-112 GEN
Solar/Wind Harmer
6.98
970163AG2-111 GEN
Solar/Wind Harmer
6.658
3147173SINAI
Solar/Wind Helper
0.307
3147243WELCO
Solar/Wind Helper
0.192
316118AC1-105 GEN
Solar/Wind Helper
1.06
316239AB2-077_GEN
Solar/Wind Helper
0.194
316238AB2-078_GEN
Solar/Wind Helper
0.194
3144303KENBRDG
Solar/Wind Helper
0.096
24684405SMG2
50/50
1.115
24684505SMG3
50/50
0.69
24684305SMG1
50/50
0.404
942751AE2-291 GEN
Solar/Wind Harmer
41.127
316217AC1-145 GEN
Solar/Wind Harmer
4.597
316197AC1-042 GEN
Solar/Wind Harmer
3.485
942671AE2-283 GEN
Solar/Wind Harmer
9.382
270013AE1-250 PV
Solar/Wind Harmer
2.228
3146843MT LREL
Solar/Wind Helper
0.238
3146843MT LREL
Solar/Wind Helper
0.238
316034AC1-036 C
Solar/Wind Helper
0.126
TVALTFEXP_TVA->PJM
CLTF
0.03
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.635
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.104
LGEELTFEXP_LGEE->PJM
CLTF
0.226
WECLTFEXP_WEC->PJM
CLTF
0.108
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.855
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.321
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.018
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.317
MECLTFEXP_MEC->PJM
CLTF
0.388
SIGELTFEXP_SIGE->PJM
CLTF
0.015

Details for 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line l/o AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:109.7 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:383.94
MW Contribution:12.85
Bus #Bus NameTypeMW Contribution
970865AG2-541 GEN
Solar/Wind Harmer
35.588
316123AC1-075 GEN
Solar/Wind Harmer
7.927
970165AG2-112 GEN
Solar/Wind Harmer
6.98
970163AG2-111 GEN
Solar/Wind Harmer
6.658
3147173SINAI
Solar/Wind Helper
0.307
3147243WELCO
Solar/Wind Helper
0.192
316118AC1-105 GEN
Solar/Wind Helper
1.06
316239AB2-077_GEN
Solar/Wind Helper
0.194
316238AB2-078_GEN
Solar/Wind Helper
0.194
3144303KENBRDG
Solar/Wind Helper
0.096
24684405SMG2
50/50
1.115
24684505SMG3
50/50
0.69
24684305SMG1
50/50
0.404
942751AE2-291 GEN
Solar/Wind Harmer
41.127
316217AC1-145 GEN
Solar/Wind Harmer
4.597
316197AC1-042 GEN
Solar/Wind Harmer
3.485
942671AE2-283 GEN
Solar/Wind Harmer
9.382
270013AE1-250 PV
Solar/Wind Harmer
2.228
3146843MT LREL
Solar/Wind Helper
0.238
3146843MT LREL
Solar/Wind Helper
0.238
316034AC1-036 C
Solar/Wind Helper
0.126
3151561HALLBR1
50/50
0.767
24728405LEESVG
50/50
0.227
24684705SMG5
50/50
0.43
970481AG2-311 GEN
50/50
5.987
316003AC1-222 GEN
Solar/Wind Harmer
9.884
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.622
270574AD1-017 GEN2
Solar/Wind Harmer
5.018
24728405LEESVG
50/50
0.228
24684605SMG4
50/50
1.123
971683AH1-343 GEN
Solar/Wind Harmer
40.772
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.622
270197AD1-017 GEN1
Solar/Wind Harmer
1.508
958131AF2-107 GEN
Solar/Wind Harmer
2.266
316248AF1-058 C
Solar/Wind Helper
0.413
316131AB2-060 GEN
Solar/Wind Helper
0.85
315785AD2-033 C
Solar/Wind Helper
1.444
270016AE1-250 BESS
Solar/Wind Harmer
2.228
970223AG2-152 GEN
Solar/Wind Harmer
12.847
270173AC1-122 GEN
Solar/Wind Harmer
1.377
962751AG1-124 GEN
Solar/Wind Harmer
5
316237AB2-079_GEN
Solar/Wind Helper
0.194
315687AD1-152 GEN
Solar/Wind Helper
0.686
TVALTFEXP_TVA->PJM
CLTF
0.03
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.635
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.104
LGEELTFEXP_LGEE->PJM
CLTF
0.226
WECLTFEXP_WEC->PJM
CLTF
0.108
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.855
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.321
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.018
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.317
MECLTFEXP_MEC->PJM
CLTF
0.388
SIGELTFEXP_SIGE->PJM
CLTF
0.015

Details for 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line l/o AEP_P7-1_#10778___SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10778___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:109.69 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:383.92
MW Contribution:12.85
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.116
24684505SMG3
50/50
0.69
24684305SMG1
50/50
0.404
942751AE2-291 GEN
Solar/Wind Harmer
41.127
316217AC1-145 GEN
Solar/Wind Harmer
4.597
316197AC1-042 GEN
Solar/Wind Harmer
3.485
942671AE2-283 GEN
Solar/Wind Harmer
9.383
270013AE1-250 PV
Solar/Wind Harmer
2.228
3146843MT LREL
Solar/Wind Helper
0.238
3146843MT LREL
Solar/Wind Helper
0.238
316034AC1-036 C
Solar/Wind Helper
0.126
970865AG2-541 GEN
Solar/Wind Harmer
35.588
316123AC1-075 GEN
Solar/Wind Harmer
7.927
970165AG2-112 GEN
Solar/Wind Harmer
6.98
970163AG2-111 GEN
Solar/Wind Harmer
6.658
3147173SINAI
Solar/Wind Helper
0.307
3147243WELCO
Solar/Wind Helper
0.192
316118AC1-105 GEN
Solar/Wind Helper
1.06
316239AB2-077_GEN
Solar/Wind Helper
0.194
316238AB2-078_GEN
Solar/Wind Helper
0.194
3144303KENBRDG
Solar/Wind Helper
0.096
3151561HALLBR1
50/50
0.767
24728405LEESVG
50/50
0.227
24684705SMG5
50/50
0.43
970481AG2-311 GEN
50/50
5.987
316003AC1-222 GEN
Solar/Wind Harmer
9.884
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.622
270574AD1-017 GEN2
Solar/Wind Harmer
5.018
270016AE1-250 BESS
Solar/Wind Harmer
2.228
970223AG2-152 GEN
Solar/Wind Harmer
12.847
270173AC1-122 GEN
Solar/Wind Harmer
1.377
962751AG1-124 GEN
Solar/Wind Harmer
5
316237AB2-079_GEN
Solar/Wind Helper
0.194
315687AD1-152 GEN
Solar/Wind Helper
0.686
24728405LEESVG
50/50
0.228
24684605SMG4
50/50
1.123
971683AH1-343 GEN
Solar/Wind Harmer
40.772
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.622
270197AD1-017 GEN1
Solar/Wind Harmer
1.508
958131AF2-107 GEN
Solar/Wind Harmer
2.266
316248AF1-058 C
Solar/Wind Helper
0.413
316131AB2-060 GEN
Solar/Wind Helper
0.85
315785AD2-033 C
Solar/Wind Helper
1.445
TVALTFEXP_TVA->PJM
CLTF
0.03
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.635
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.104
LGEELTFEXP_LGEE->PJM
CLTF
0.226
WECLTFEXP_WEC->PJM
CLTF
0.108
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.855
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.321
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.019
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.317
MECLTFEXP_MEC->PJM
CLTF
0.388
SIGELTFEXP_SIGE->PJM
CLTF
0.015

Details for 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line l/o AEP_P1-3_#10688_05EDANV2 230_4_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P1-3_#10688_05EDANV2 230_4_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.4 %
Rating:285.76 MVA
Rating Type:B
MVA to Mitigate:304.05
MW Contribution:9.01
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.115
24684505SMG3
50/50
0.69
24684305SMG1
50/50
0.404
942751AE2-291 GEN
Solar/Wind Harmer
31.236
316217AC1-145 GEN
Solar/Wind Harmer
0.003
316197AC1-042 GEN
Solar/Wind Harmer
0.003
942671AE2-283 GEN
Solar/Wind Harmer
6.274
270013AE1-250 PV
Solar/Wind Harmer
0.004
3146843MT LREL
Solar/Wind Helper
0.238
3146843MT LREL
Solar/Wind Helper
0.238
316034AC1-036 C
Solar/Wind Helper
0.126
3151561HALLBR1
50/50
0.767
24728405LEESVG
50/50
0.227
24684705SMG5
50/50
0.43
970481AG2-311 GEN
50/50
5.987
316003AC1-222 GEN
Solar/Wind Harmer
0.024
3147123OTTER R
Solar/Wind Harmer
0.189
3147312GRETNA
Solar/Wind Harmer
0.201
3146802CHATHAM
Solar/Wind Harmer
0.189
941801AE2-185 GEN
Solar/Wind Harmer
8.067
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.004
970223AG2-152 GEN
Solar/Wind Harmer
9.008
270173AC1-122 GEN
Solar/Wind Harmer
0.284
962751AG1-124 GEN
Solar/Wind Harmer
3.424
316237AB2-079_GEN
Solar/Wind Helper
0.194
315687AD1-152 GEN
Solar/Wind Helper
0.686
970865AG2-541 GEN
Solar/Wind Harmer
27.029
316123AC1-075 GEN
Solar/Wind Harmer
0.894
970165AG2-112 GEN
Solar/Wind Harmer
5.301
970163AG2-111 GEN
Solar/Wind Harmer
5.057
3147173SINAI
Solar/Wind Helper
0.307
3147243WELCO
Solar/Wind Helper
0.192
316118AC1-105 GEN
Solar/Wind Helper
1.06
316239AB2-077_GEN
Solar/Wind Helper
0.194
316238AB2-078_GEN
Solar/Wind Helper
0.194
3144303KENBRDG
Solar/Wind Helper
0.096
24728405LEESVG
50/50
0.228
24684605SMG4
50/50
1.123
24288905REUSENS
50/50
0.018
966251AG1-494 GEN
50/50
1.276
971683AH1-343 GEN
Solar/Wind Harmer
30.966
3147312GRETNA
Solar/Wind Harmer
0.05
941821AE2-187 GEN
Solar/Wind Harmer
8.067
270197AD1-017 GEN1
Solar/Wind Harmer
0.846
958131AF2-107 GEN
Solar/Wind Harmer
1.702
316248AF1-058 C
Solar/Wind Helper
0.413
316131AB2-060 GEN
Solar/Wind Helper
0.85
315785AD2-033 C
Solar/Wind Helper
1.444
TVALTFEXP_TVA->PJM
CLTF
0.03
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.635
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.104
LGEELTFEXP_LGEE->PJM
CLTF
0.226
WECLTFEXP_WEC->PJM
CLTF
0.108
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.855
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.321
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.018
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.317
MECLTFEXP_MEC->PJM
CLTF
0.388
SIGELTFEXP_SIGE->PJM
CLTF
0.015

Details for 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line l/o AEP_P1-2_#5366_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#5366_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.21 %
Rating:285.76 MVA
Rating Type:B
MVA to Mitigate:303.5
MW Contribution:8.98
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
0.767
24728405LEESVG
50/50
0.226
24684705SMG5
50/50
0.428
970481AG2-311 GEN
50/50
5.969
316003AC1-222 GEN
Solar/Wind Harmer
0.024
3147123OTTER R
Solar/Wind Harmer
0.189
3147312GRETNA
Solar/Wind Harmer
0.201
3146802CHATHAM
Solar/Wind Harmer
0.189
941801AE2-185 GEN
Solar/Wind Harmer
8.062
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.004
970223AG2-152 GEN
Solar/Wind Harmer
8.982
270173AC1-122 GEN
Solar/Wind Harmer
0.283
962751AG1-124 GEN
Solar/Wind Harmer
3.412
316237AB2-079_GEN
Solar/Wind Helper
0.192
315687AD1-152 GEN
Solar/Wind Helper
0.678
970865AG2-541 GEN
Solar/Wind Harmer
27.047
316123AC1-075 GEN
Solar/Wind Harmer
0.894
970165AG2-112 GEN
Solar/Wind Harmer
5.304
970163AG2-111 GEN
Solar/Wind Harmer
5.06
3147173SINAI
Solar/Wind Helper
0.306
3147243WELCO
Solar/Wind Helper
0.191
316118AC1-105 GEN
Solar/Wind Helper
1.054
316239AB2-077_GEN
Solar/Wind Helper
0.192
316238AB2-078_GEN
Solar/Wind Helper
0.192
3144303KENBRDG
Solar/Wind Helper
0.095
24728405LEESVG
50/50
0.227
24684605SMG4
50/50
1.12
24288905REUSENS
50/50
0.018
966251AG1-494 GEN
50/50
1.272
971683AH1-343 GEN
Solar/Wind Harmer
30.988
3147312GRETNA
Solar/Wind Harmer
0.05
941821AE2-187 GEN
Solar/Wind Harmer
8.062
270197AD1-017 GEN1
Solar/Wind Harmer
0.844
958131AF2-107 GEN
Solar/Wind Harmer
1.697
316248AF1-058 C
Solar/Wind Helper
0.411
316131AB2-060 GEN
Solar/Wind Helper
0.842
315785AD2-033 C
Solar/Wind Helper
1.43
24684405SMG2
50/50
1.112
24684505SMG3
50/50
0.688
24684305SMG1
50/50
0.403
942751AE2-291 GEN
Solar/Wind Harmer
31.25
316217AC1-145 GEN
Solar/Wind Harmer
0.003
316197AC1-042 GEN
Solar/Wind Harmer
0.003
942671AE2-283 GEN
Solar/Wind Harmer
6.271
270013AE1-250 PV
Solar/Wind Harmer
0.004
3146843MT LREL
Solar/Wind Helper
0.237
3146843MT LREL
Solar/Wind Helper
0.237
316034AC1-036 C
Solar/Wind Helper
0.124
TVALTFEXP_TVA->PJM
CLTF
0.033
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.619
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.103
LGEELTFEXP_LGEE->PJM
CLTF
0.22
WECLTFEXP_WEC->PJM
CLTF
0.105
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.823
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.308
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.917
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.318
MECLTFEXP_MEC->PJM
CLTF
0.38
SIGELTFEXP_SIGE->PJM
CLTF
0.015

Details for 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line l/o AEP_P7-1_#10781___SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10781___SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.7 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:359.46
MW Contribution:7.33
Bus #Bus NameTypeMW Contribution
942751AE2-291 GEN
Solar/Wind Harmer
40.562
316217AC1-145 GEN
Solar/Wind Harmer
4.414
316197AC1-042 GEN
Solar/Wind Harmer
3.346
942671AE2-283 GEN
Solar/Wind Harmer
9.009
270013AE1-250 PV
Solar/Wind Harmer
1.363
3146843MT LREL
Solar/Wind Helper
0.248
3146843MT LREL
Solar/Wind Helper
0.248
316034AC1-036 C
Solar/Wind Helper
0.133
970865AG2-541 GEN
Solar/Wind Harmer
35.284
316123AC1-075 GEN
Solar/Wind Harmer
7.837
970165AG2-112 GEN
Solar/Wind Harmer
6.901
970163AG2-111 GEN
Solar/Wind Harmer
6.583
3147173SINAI
Solar/Wind Helper
0.318
3147243WELCO
Solar/Wind Helper
0.199
316118AC1-105 GEN
Solar/Wind Helper
1.1
316239AB2-077_GEN
Solar/Wind Helper
0.205
316238AB2-078_GEN
Solar/Wind Helper
0.205
3144303KENBRDG
Solar/Wind Helper
0.102
3151561HALLBR1
50/50
0.743
24728405LEESVG
50/50
0.21
316003AC1-222 GEN
Solar/Wind Harmer
9.819
3147123OTTER R
Solar/Wind Harmer
-0.02
3147312GRETNA
Solar/Wind Harmer
-0.022
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
10.198
270173AC1-122 GEN
Solar/Wind Harmer
1.218
270574AD1-017 GEN2
Solar/Wind Harmer
3.601
270016AE1-250 BESS
Solar/Wind Harmer
1.363
970223AG2-152 GEN
Solar/Wind Harmer
7.327
962751AG1-124 GEN
Solar/Wind Harmer
4.804
316237AB2-079_GEN
Solar/Wind Helper
0.205
315687AD1-152 GEN
Solar/Wind Helper
0.735
24728405LEESVG
50/50
0.21
971683AH1-343 GEN
Solar/Wind Harmer
40.466
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
10.198
270197AD1-017 GEN1
Solar/Wind Harmer
1.082
958131AF2-107 GEN
Solar/Wind Harmer
2.161
316248AF1-058 C
Solar/Wind Helper
0.428
316131AB2-060 GEN
Solar/Wind Helper
0.9
315785AD2-033 C
Solar/Wind Helper
1.533
LAGNLTFEXP_LAGN->PJM
CLTF
0.016
TVALTFEXP_TVA->PJM
CLTF
0.056
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.165
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.114
LGEELTFEXP_LGEE->PJM
CLTF
0.278
WECLTFEXP_WEC->PJM
CLTF
0.133
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.003
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.373
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.967
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.446
MECLTFEXP_MEC->PJM
CLTF
0.486
SIGELTFEXP_SIGE->PJM
CLTF
0.019

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o DVP_P4-2: 151T1047_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 151T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:137.18 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:336.08
MW Contribution:6.6
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Harmer
5.564
970865AG2-541 GEN
Solar/Wind Harmer
20.949
970165AG2-112 GEN
Solar/Wind Harmer
4.899
970163AG2-111 GEN
Solar/Wind Harmer
4.673
24684405SMG2
50/50
1.258
24684505SMG3
50/50
0.778
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.716
316197AC1-042 GEN
Solar/Wind Harmer
6.608
942671AE2-283 GEN
Solar/Wind Harmer
17.789
942751AE2-291 GEN
Solar/Wind Harmer
32.874
270013AE1-250 PV
Solar/Wind Harmer
1.342
3151561HALLBR1
50/50
1.184
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.484
970481AG2-311 GEN
50/50
6.751
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.139
316003AC1-222 GEN
Solar/Wind Harmer
5.036
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.147
270016AE1-250 BESS
Solar/Wind Harmer
1.342
270173AC1-122 GEN
Solar/Wind Harmer
0.85
970223AG2-152 GEN
Solar/Wind Harmer
6.601
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.266
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.139
971683AH1-343 GEN
Solar/Wind Harmer
22.238
270197AD1-017 GEN1
Solar/Wind Harmer
1.246
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.061
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
0.013
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.831
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.484
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.065
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.177

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o DVP_P4-2: 104702_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104702_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:137.17 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:336.06
MW Contribution:6.6
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Harmer
5.564
970865AG2-541 GEN
Solar/Wind Harmer
20.949
970165AG2-112 GEN
Solar/Wind Harmer
4.899
970163AG2-111 GEN
Solar/Wind Harmer
4.673
24684405SMG2
50/50
1.258
24684505SMG3
50/50
0.778
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.716
316197AC1-042 GEN
Solar/Wind Harmer
6.608
942671AE2-283 GEN
Solar/Wind Harmer
17.789
942751AE2-291 GEN
Solar/Wind Harmer
32.874
270013AE1-250 PV
Solar/Wind Harmer
1.342
3151561HALLBR1
50/50
1.184
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.484
970481AG2-311 GEN
50/50
6.751
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.139
316003AC1-222 GEN
Solar/Wind Harmer
5.035
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.147
270016AE1-250 BESS
Solar/Wind Harmer
1.342
270173AC1-122 GEN
Solar/Wind Harmer
0.85
970223AG2-152 GEN
Solar/Wind Harmer
6.6
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.266
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.139
971683AH1-343 GEN
Solar/Wind Harmer
22.238
270197AD1-017 GEN1
Solar/Wind Harmer
1.246
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.061
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
0.012
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.829
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.484
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.065
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.178

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o DVP_P4-2: 1016T1047_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 1016T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.26 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:319.14
MW Contribution:6.61
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Harmer
5.565
970865AG2-541 GEN
Solar/Wind Harmer
20.954
970165AG2-112 GEN
Solar/Wind Harmer
4.9
970163AG2-111 GEN
Solar/Wind Harmer
4.674
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.718
316197AC1-042 GEN
Solar/Wind Harmer
6.609
942671AE2-283 GEN
Solar/Wind Harmer
17.793
942751AE2-291 GEN
Solar/Wind Harmer
32.881
270013AE1-250 PV
Solar/Wind Harmer
1.344
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.143
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.151
270016AE1-250 BESS
Solar/Wind Harmer
1.344
270173AC1-122 GEN
Solar/Wind Harmer
0.851
970223AG2-152 GEN
Solar/Wind Harmer
6.611
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.143
971683AH1-343 GEN
Solar/Wind Harmer
22.243
270197AD1-017 GEN1
Solar/Wind Harmer
1.247
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.029
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007
CPLELTFEXP_CPLE->PJM
CLTF
0.492
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.06
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.153

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o DVP_P4-2: 101672_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 101672_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.24 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:319.1
MW Contribution:6.61
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.143
971683AH1-343 GEN
Solar/Wind Harmer
22.243
316123AC1-075 GEN
Solar/Wind Harmer
5.565
970865AG2-541 GEN
Solar/Wind Harmer
20.954
970165AG2-112 GEN
Solar/Wind Harmer
4.9
970163AG2-111 GEN
Solar/Wind Harmer
4.674
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.143
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.151
270016AE1-250 BESS
Solar/Wind Harmer
1.344
270173AC1-122 GEN
Solar/Wind Harmer
0.851
970223AG2-152 GEN
Solar/Wind Harmer
6.611
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.718
316197AC1-042 GEN
Solar/Wind Harmer
6.609
942671AE2-283 GEN
Solar/Wind Harmer
17.793
942751AE2-291 GEN
Solar/Wind Harmer
32.881
270013AE1-250 PV
Solar/Wind Harmer
1.344
270197AD1-017 GEN1
Solar/Wind Harmer
1.247
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.029
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007
CPLELTFEXP_CPLE->PJM
CLTF
0.492
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.06
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.153

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o DVP_P4-2: 104772_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104772_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.8 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:315.55
MW Contribution:6.61
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.143
971683AH1-343 GEN
Solar/Wind Harmer
22.243
270197AD1-017 GEN1
Solar/Wind Harmer
1.247
316123AC1-075 GEN
Solar/Wind Harmer
5.565
970865AG2-541 GEN
Solar/Wind Harmer
20.954
970165AG2-112 GEN
Solar/Wind Harmer
4.9
970163AG2-111 GEN
Solar/Wind Harmer
4.674
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.718
316197AC1-042 GEN
Solar/Wind Harmer
6.609
942671AE2-283 GEN
Solar/Wind Harmer
17.793
942751AE2-291 GEN
Solar/Wind Harmer
32.881
270013AE1-250 PV
Solar/Wind Harmer
1.344
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.143
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.151
270016AE1-250 BESS
Solar/Wind Harmer
1.344
270173AC1-122 GEN
Solar/Wind Harmer
0.851
970223AG2-152 GEN
Solar/Wind Harmer
6.611
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.029
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007
CPLELTFEXP_CPLE->PJM
CLTF
0.492
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.06
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.153

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 1047_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1047_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.43 %
Rating:230.3 MVA
Rating Type:B
MVA to Mitigate:265.84
MW Contribution:4.63
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Harmer
0.627
970865AG2-541 GEN
Solar/Wind Harmer
15.911
970165AG2-112 GEN
Solar/Wind Harmer
3.721
970163AG2-111 GEN
Solar/Wind Harmer
3.549
3151561HALLBR1
50/50
1.184
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.484
970481AG2-311 GEN
50/50
6.751
3147312GRETNA
Solar/Wind Harmer
0.382
3146802CHATHAM
Solar/Wind Harmer
0.358
941801AE2-185 GEN
Solar/Wind Harmer
15.295
316003AC1-222 GEN
Solar/Wind Harmer
0.012
3147123OTTER R
Solar/Wind Harmer
0.275
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.002
270173AC1-122 GEN
Solar/Wind Harmer
0.175
970223AG2-152 GEN
Solar/Wind Harmer
4.628
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.266
3147312GRETNA
Solar/Wind Harmer
0.096
941821AE2-187 GEN
Solar/Wind Harmer
15.295
971683AH1-343 GEN
Solar/Wind Harmer
16.89
270197AD1-017 GEN1
Solar/Wind Harmer
0.699
24684405SMG2
50/50
1.258
24684505SMG3
50/50
0.778
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
0.006
316197AC1-042 GEN
Solar/Wind Harmer
0.005
942671AE2-283 GEN
Solar/Wind Harmer
11.896
942751AE2-291 GEN
Solar/Wind Harmer
24.967
270013AE1-250 PV
Solar/Wind Harmer
0.002
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.061
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
0.012
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.829
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.484
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.065
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.178

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 1016_SRT-A-1


Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1016_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.32 %
Rating:230.3 MVA
Rating Type:B
MVA to Mitigate:254.07
MW Contribution:4.64
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
0.382
3146802CHATHAM
Solar/Wind Harmer
0.358
941801AE2-185 GEN
Solar/Wind Harmer
15.299
3147123OTTER R
Solar/Wind Harmer
0.275
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.002
270173AC1-122 GEN
Solar/Wind Harmer
0.176
970223AG2-152 GEN
Solar/Wind Harmer
4.636
316123AC1-075 GEN
Solar/Wind Harmer
0.628
970865AG2-541 GEN
Solar/Wind Harmer
15.914
970165AG2-112 GEN
Solar/Wind Harmer
3.721
970163AG2-111 GEN
Solar/Wind Harmer
3.55
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
0.096
941821AE2-187 GEN
Solar/Wind Harmer
15.299
971683AH1-343 GEN
Solar/Wind Harmer
16.893
270197AD1-017 GEN1
Solar/Wind Harmer
0.7
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
0.006
316197AC1-042 GEN
Solar/Wind Harmer
0.005
942671AE2-283 GEN
Solar/Wind Harmer
11.899
942751AE2-291 GEN
Solar/Wind Harmer
24.973
270013AE1-250 PV
Solar/Wind Harmer
0.002
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.028
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007
CPLELTFEXP_CPLE->PJM
CLTF
0.492
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.06
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.154

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.33 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:250.71
MW Contribution:13.8
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.198
24684505SMG3
50/50
0.741
24684305SMG1
50/50
0.434
316217AC1-145 GEN
Solar/Wind Harmer
7.301
316197AC1-042 GEN
Solar/Wind Harmer
5.534
942671AE2-283 GEN
Solar/Wind Harmer
14.9
942751AE2-291 GEN
Solar/Wind Harmer
17.168
270013AE1-250 PV
Solar/Wind Harmer
2.392
316123AC1-075 GEN
Solar/Wind Harmer
2.482
970165AG2-112 GEN
Solar/Wind Harmer
2.186
970163AG2-111 GEN
Solar/Wind Harmer
2.085
970865AG2-541 GEN
Solar/Wind Harmer
6.833
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.005
316118AC1-105 GEN
Solar/Wind Harmer
0.454
3151561HALLBR1
50/50
0.931
24728405LEESVG
50/50
0.319
24684705SMG5
50/50
0.461
970481AG2-311 GEN
50/50
6.43
3147312GRETNA
Solar/Wind Harmer
-0.036
3146802CHATHAM
Solar/Wind Harmer
-0.034
941801AE2-185 GEN
Solar/Wind Harmer
16.868
3147123OTTER R
Solar/Wind Harmer
-0.024
270574AD1-017 GEN2
Solar/Wind Harmer
5.39
270016AE1-250 BESS
Solar/Wind Harmer
2.392
970223AG2-152 GEN
Solar/Wind Harmer
13.798
316003AC1-222 GEN
Solar/Wind Harmer
1.06
270173AC1-122 GEN
Solar/Wind Harmer
0.706
24728405LEESVG
50/50
0.32
24684605SMG4
50/50
1.206
3147312GRETNA
Solar/Wind Harmer
-0.009
941821AE2-187 GEN
Solar/Wind Harmer
16.868
270197AD1-017 GEN1
Solar/Wind Harmer
1.62
971683AH1-343 GEN
Solar/Wind Harmer
5.942
316248AF1-058 C
Solar/Wind Harmer
0.225
960061AF2-297 GEN
Solar/Wind Harmer
3.734
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.153
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.471
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.072
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.729
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.033
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.539

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o AEP_P7-1_#10778___SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10778___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.33 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:250.7
MW Contribution:13.8
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.198
24684505SMG3
50/50
0.741
24684305SMG1
50/50
0.434
316217AC1-145 GEN
Solar/Wind Harmer
7.301
316197AC1-042 GEN
Solar/Wind Harmer
5.534
942671AE2-283 GEN
Solar/Wind Harmer
14.9
942751AE2-291 GEN
Solar/Wind Harmer
17.168
270013AE1-250 PV
Solar/Wind Harmer
2.392
316123AC1-075 GEN
Solar/Wind Harmer
2.482
970165AG2-112 GEN
Solar/Wind Harmer
2.186
970163AG2-111 GEN
Solar/Wind Harmer
2.085
970865AG2-541 GEN
Solar/Wind Harmer
6.833
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.005
316118AC1-105 GEN
Solar/Wind Harmer
0.454
3151561HALLBR1
50/50
0.931
24728405LEESVG
50/50
0.319
24684705SMG5
50/50
0.461
970481AG2-311 GEN
50/50
6.43
3147312GRETNA
Solar/Wind Harmer
-0.036
3146802CHATHAM
Solar/Wind Harmer
-0.034
941801AE2-185 GEN
Solar/Wind Harmer
16.868
3147123OTTER R
Solar/Wind Harmer
-0.024
270574AD1-017 GEN2
Solar/Wind Harmer
5.39
270016AE1-250 BESS
Solar/Wind Harmer
2.392
970223AG2-152 GEN
Solar/Wind Harmer
13.798
316003AC1-222 GEN
Solar/Wind Harmer
1.06
270173AC1-122 GEN
Solar/Wind Harmer
0.706
24728405LEESVG
50/50
0.32
24684605SMG4
50/50
1.206
3147312GRETNA
Solar/Wind Harmer
-0.009
941821AE2-187 GEN
Solar/Wind Harmer
16.868
270197AD1-017 GEN1
Solar/Wind Harmer
1.62
971683AH1-343 GEN
Solar/Wind Harmer
5.942
316248AF1-058 C
Solar/Wind Harmer
0.225
960061AF2-297 GEN
Solar/Wind Harmer
3.734
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.153
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.471
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.072
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CPLELTFEXP_CPLE->PJM
CLTF
0.729
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.033
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.539

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o DVP_P2-2: ALTAVISTA 115KV_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: ALTAVISTA 115KV_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.22 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:247.98
MW Contribution:7.55
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.434
24684505SMG3
50/50
0.887
24684305SMG1
50/50
0.52
316217AC1-145 GEN
Solar/Wind Harmer
9.919
316197AC1-042 GEN
Solar/Wind Harmer
7.519
942671AE2-283 GEN
Solar/Wind Harmer
20.244
270013AE1-250 PV
Solar/Wind Harmer
1.533
24728405LEESVG
50/50
0.421
24684605SMG4
50/50
1.443
3147312GRETNA
Solar/Wind Harmer
-0.012
941821AE2-187 GEN
Solar/Wind Harmer
22.918
270197AD1-017 GEN1
Solar/Wind Harmer
1.422
24728405LEESVG
50/50
0.419
24684705SMG5
50/50
0.552
970481AG2-311 GEN
50/50
7.695
3147312GRETNA
Solar/Wind Harmer
-0.049
3146802CHATHAM
Solar/Wind Harmer
-0.046
941801AE2-185 GEN
Solar/Wind Harmer
22.918
270574AD1-017 GEN2
Solar/Wind Harmer
4.731
270016AE1-250 BESS
Solar/Wind Harmer
1.533
270173AC1-122 GEN
Solar/Wind Harmer
0.968
970223AG2-152 GEN
Solar/Wind Harmer
7.548
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.047
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.144
LAGNLTFEXP_LAGN->PJM
CLTF
0.083
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.044
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.034
CPLELTFEXP_CPLE->PJM
CLTF
0.586
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.054
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.099
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.056

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:212.98 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1488.76
MW Contribution:5.77
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.863
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.477
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.384
971563AH1-280 GEN
Solar/Wind Harmer
6.384
970685AG2-442 GEN
Solar/Wind Harmer
41.078
962491AG1-098 GEN
Solar/Wind Harmer
28.511
315693AD1-088 GEN
Solar/Wind Harmer
20.878
957481AF2-042 GEN
Solar/Wind Harmer
119.657
316237AB2-079_GEN
Solar/Wind Harmer
0.969
315687AD1-152 GEN
Solar/Wind Harmer
3.719
970401AG2-262 GEN
Solar/Wind Harmer
1.826
316003AC1-222 GEN
Solar/Wind Harmer
2.228
971065AG2-659 GEN
Solar/Wind Harmer
10.772
316129AC1-054 GEN
Solar/Wind Harmer
1.807
971795AH1-408 GEN
Solar/Wind Harmer
11.365
960081AF2-299 GEN
Solar/Wind Harmer
1.184
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.962
316049AB1-081 GEN
Solar/Wind Harmer
0.77
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.712
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
970223AG2-152 GEN
Solar/Wind Harmer
5.769
3151541CLOVER2
50/50
6.83
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
971845AH1-439 GEN
Solar/Wind Harmer
44.827
970285AG2-188 GEN
Solar/Wind Harmer
71.81
315657AE1-056 GEN
Solar/Wind Harmer
20.233
946301AF1-294 GEN
Solar/Wind Harmer
13.088
961791AG1-021 GEN
Solar/Wind Harmer
6.384
970683AG2-441 GEN
Solar/Wind Harmer
36.677
970681AG2-440 GEN
Solar/Wind Harmer
29.342
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.305
971967AH1-528 GEN
Solar/Wind Harmer
73.277
316239AB2-077_GEN
Solar/Wind Harmer
0.969
316238AB2-078_GEN
Solar/Wind Harmer
0.969
316118AC1-105 GEN
Solar/Wind Harmer
1.805
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.02
970831AG2-522 GEN
Solar/Wind Harmer
9.81
316123AC1-075 GEN
Solar/Wind Harmer
1.786
970165AG2-112 GEN
Solar/Wind Harmer
1.573
970163AG2-111 GEN
Solar/Wind Harmer
1.5
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.951
3151591KERR 2
50/50
0.482
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.336
970909AG2-566 GEN
Solar/Wind Harmer
5.575
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.627
3152661PLYWOOD A
50/50
0.509
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.363
971741AH1-377 GEN
Solar/Wind Harmer
63.743
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.98
963191AG1-168 GEN
Solar/Wind Harmer
4.788
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.282
971775AH1-396 GEN
Solar/Wind Harmer
3.031
970933AG2-581 GEN
Solar/Wind Harmer
36.542
970099AG2-077 GEN
Solar/Wind Harmer
47.863
313527AB2-043 GEN
Solar/Wind Harmer
5.319
962561AG1-105 GEN
Solar/Wind Harmer
16.15
964791AG1-342 GEN
Solar/Wind Harmer
5.978
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.382
942751AE2-291 GEN
Solar/Wind Harmer
9.268
316222AC1-221 GEN
Solar/Wind Harmer
1.428
316181AB2-040 GEN
Solar/Wind Harmer
1.451
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.155
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.18
3145783HORNRTN
Solar/Wind Harmer
0.944
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.888
316263AC1-034 GEN
Solar/Wind Harmer
3.343
961601AG1-000A GEN
Solar/Wind Harmer
2.724
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.489
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.631
270457AD2-023 GEN
Solar/Wind Harmer
0.827
315607AA1-063A GEN
Solar/Wind Harmer
0.88
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.41
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.561
270494AE1-108_GEN
Solar/Wind Helper
3.67
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.067
3148013FISHERV
Solar/Wind Helper
0.064
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.721
963181AG1-167 GEN
Solar/Wind Harmer
4.788
959311AF2-222 GEN
Solar/Wind Harmer
45.74
970257AG2-171 GEN
Solar/Wind Harmer
15.961
315785AD2-033 C
Solar/Wind Harmer
9.254
964241AG1-285 GEN
Solar/Wind Harmer
28.298
316478AD1-087 GEN
Solar/Wind Harmer
3.113
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.606
316248AF1-058 C
Solar/Wind Harmer
0.74
960061AF2-297 GEN
Solar/Wind Harmer
12.278
971683AH1-343 GEN
Solar/Wind Harmer
9.189
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.301
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.773
316210AC1-098 GEN
Solar/Wind Harmer
1.19
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.758
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.392
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.405
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.318
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
3148013FISHERV
Solar/Wind Helper
0.111
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.041
316197AC1-042 GEN
Solar/Wind Harmer
0.789
942671AE2-283 GEN
Solar/Wind Harmer
2.125
315821AE2-092 GEN
Solar/Wind Helper
2.535
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.191
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.405
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.316
LAGNLTFEXP_LAGN->PJM
CLTF
3.179
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.848
TVALTFEXP_TVA->PJM
CLTF
1.583
CPLELTFEXP_CPLE->PJM
CLTF
5.212
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.402
NYPJM->LTFIMP_NY
CLTF
0.53
LGEELTFEXP_LGEE->PJM
CLTF
0.51
WECLTFEXP_WEC->PJM
CLTF
0.265
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.278
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.374
MECLTFEXP_MEC->PJM
CLTF
1.462
SIGELTFEXP_SIGE->PJM
CLTF
0.043

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:212.93 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1488.37
MW Contribution:5.77
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.951
3151591KERR 2
50/50
0.482
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.336
970909AG2-566 GEN
Solar/Wind Harmer
5.575
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.721
963181AG1-167 GEN
Solar/Wind Harmer
4.788
959311AF2-222 GEN
Solar/Wind Harmer
45.74
970257AG2-171 GEN
Solar/Wind Harmer
15.961
315785AD2-033 C
Solar/Wind Harmer
9.254
964241AG1-285 GEN
Solar/Wind Harmer
28.298
316478AD1-087 GEN
Solar/Wind Harmer
3.113
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.606
316248AF1-058 C
Solar/Wind Harmer
0.74
960061AF2-297 GEN
Solar/Wind Harmer
12.278
971683AH1-343 GEN
Solar/Wind Harmer
9.189
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.301
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.773
316210AC1-098 GEN
Solar/Wind Harmer
1.19
3146233WITAKRS
Solar/Wind Harmer
0.155
3151541CLOVER2
50/50
6.83
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
971845AH1-439 GEN
Solar/Wind Harmer
44.827
970285AG2-188 GEN
Solar/Wind Harmer
71.81
315657AE1-056 GEN
Solar/Wind Harmer
20.233
946301AF1-294 GEN
Solar/Wind Harmer
13.088
961791AG1-021 GEN
Solar/Wind Harmer
6.384
970683AG2-441 GEN
Solar/Wind Harmer
36.677
970681AG2-440 GEN
Solar/Wind Harmer
29.342
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.305
971967AH1-528 GEN
Solar/Wind Harmer
73.277
316239AB2-077_GEN
Solar/Wind Harmer
0.969
316238AB2-078_GEN
Solar/Wind Harmer
0.969
316118AC1-105 GEN
Solar/Wind Harmer
1.805
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.02
970831AG2-522 GEN
Solar/Wind Harmer
9.81
316123AC1-075 GEN
Solar/Wind Harmer
1.786
970165AG2-112 GEN
Solar/Wind Harmer
1.573
970163AG2-111 GEN
Solar/Wind Harmer
1.5
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.489
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.631
270457AD2-023 GEN
Solar/Wind Harmer
0.827
315607AA1-063A GEN
Solar/Wind Harmer
0.88
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.41
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.561
270494AE1-108_GEN
Solar/Wind Helper
3.67
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.067
3148013FISHERV
Solar/Wind Helper
0.064
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.863
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.477
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.384
971563AH1-280 GEN
Solar/Wind Harmer
6.384
970685AG2-442 GEN
Solar/Wind Harmer
41.078
962491AG1-098 GEN
Solar/Wind Harmer
28.511
315693AD1-088 GEN
Solar/Wind Harmer
20.878
957481AF2-042 GEN
Solar/Wind Harmer
119.657
316237AB2-079_GEN
Solar/Wind Harmer
0.969
315687AD1-152 GEN
Solar/Wind Harmer
3.719
970401AG2-262 GEN
Solar/Wind Harmer
1.826
316003AC1-222 GEN
Solar/Wind Harmer
2.228
971065AG2-659 GEN
Solar/Wind Harmer
10.772
316129AC1-054 GEN
Solar/Wind Harmer
1.807
971795AH1-408 GEN
Solar/Wind Harmer
11.365
960081AF2-299 GEN
Solar/Wind Harmer
1.184
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.962
316049AB1-081 GEN
Solar/Wind Harmer
0.77
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.712
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
970223AG2-152 GEN
Solar/Wind Harmer
5.769
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.191
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.405
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.316
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.627
3152661PLYWOOD A
50/50
0.509
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.363
971741AH1-377 GEN
Solar/Wind Harmer
63.743
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.98
963191AG1-168 GEN
Solar/Wind Harmer
4.788
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.282
971775AH1-396 GEN
Solar/Wind Harmer
3.031
970933AG2-581 GEN
Solar/Wind Harmer
36.542
970099AG2-077 GEN
Solar/Wind Harmer
47.863
313527AB2-043 GEN
Solar/Wind Harmer
5.319
962561AG1-105 GEN
Solar/Wind Harmer
16.15
964791AG1-342 GEN
Solar/Wind Harmer
5.978
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.382
942751AE2-291 GEN
Solar/Wind Harmer
9.268
316222AC1-221 GEN
Solar/Wind Harmer
1.428
316181AB2-040 GEN
Solar/Wind Harmer
1.451
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.155
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.18
3145783HORNRTN
Solar/Wind Harmer
0.944
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.888
316263AC1-034 GEN
Solar/Wind Harmer
3.343
961601AG1-000A GEN
Solar/Wind Harmer
2.724
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.041
316197AC1-042 GEN
Solar/Wind Harmer
0.789
942671AE2-283 GEN
Solar/Wind Harmer
2.125
315821AE2-092 GEN
Solar/Wind Helper
2.535
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.758
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.392
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.405
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.318
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
3148013FISHERV
Solar/Wind Helper
0.111
LAGNLTFEXP_LAGN->PJM
CLTF
3.179
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.848
TVALTFEXP_TVA->PJM
CLTF
1.583
CPLELTFEXP_CPLE->PJM
CLTF
5.212
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.402
NYPJM->LTFIMP_NY
CLTF
0.53
LGEELTFEXP_LGEE->PJM
CLTF
0.51
WECLTFEXP_WEC->PJM
CLTF
0.265
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.278
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.374
MECLTFEXP_MEC->PJM
CLTF
1.462
SIGELTFEXP_SIGE->PJM
CLTF
0.043

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:209.35 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1463.37
MW Contribution:5.68
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.826
970285AG2-188 GEN
Solar/Wind Harmer
71.806
315657AE1-056 GEN
Solar/Wind Harmer
20.219
946301AF1-294 GEN
Solar/Wind Harmer
13.078
961791AG1-021 GEN
Solar/Wind Harmer
6.379
970683AG2-441 GEN
Solar/Wind Harmer
36.643
970681AG2-440 GEN
Solar/Wind Harmer
29.315
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.296
971967AH1-528 GEN
Solar/Wind Harmer
73.139
316239AB2-077_GEN
Solar/Wind Harmer
0.967
316238AB2-078_GEN
Solar/Wind Harmer
0.967
316118AC1-105 GEN
Solar/Wind Harmer
1.799
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.987
970831AG2-522 GEN
Solar/Wind Harmer
9.789
316123AC1-075 GEN
Solar/Wind Harmer
1.778
970165AG2-112 GEN
Solar/Wind Harmer
1.566
970163AG2-111 GEN
Solar/Wind Harmer
1.494
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.49
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.605
270457AD2-023 GEN
Solar/Wind Harmer
0.814
315607AA1-063A GEN
Solar/Wind Harmer
0.881
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.406
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.564
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.331
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
-0.168
971193AH1-056 GEN
Solar/Wind Harmer
33.698
963181AG1-167 GEN
Solar/Wind Harmer
4.785
959311AF2-222 GEN
Solar/Wind Harmer
45.693
970257AG2-171 GEN
Solar/Wind Harmer
15.944
315785AD2-033 C
Solar/Wind Harmer
9.243
964241AG1-285 GEN
Solar/Wind Harmer
28.257
316478AD1-087 GEN
Solar/Wind Harmer
3.106
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.6
316248AF1-058 C
Solar/Wind Harmer
0.737
960061AF2-297 GEN
Solar/Wind Harmer
12.232
971683AH1-343 GEN
Solar/Wind Harmer
9.152
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.287
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.767
316210AC1-098 GEN
Solar/Wind Harmer
1.185
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.727
315724AD1-057 GEN
Solar/Wind Harmer
0.389
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.343
971741AH1-377 GEN
Solar/Wind Harmer
63.689
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.974
963191AG1-168 GEN
Solar/Wind Harmer
4.785
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.258
971775AH1-396 GEN
Solar/Wind Harmer
3.027
970933AG2-581 GEN
Solar/Wind Harmer
36.473
970099AG2-077 GEN
Solar/Wind Harmer
47.77
313527AB2-043 GEN
Solar/Wind Harmer
5.31
962561AG1-105 GEN
Solar/Wind Harmer
16.108
964791AG1-342 GEN
Solar/Wind Harmer
5.961
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.346
942751AE2-291 GEN
Solar/Wind Harmer
9.222
316222AC1-221 GEN
Solar/Wind Harmer
1.414
316181AB2-040 GEN
Solar/Wind Harmer
1.452
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.154
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.178
3145783HORNRTN
Solar/Wind Harmer
0.943
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.884
316263AC1-034 GEN
Solar/Wind Harmer
3.306
961601AG1-000A GEN
Solar/Wind Harmer
2.693
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
316217AC1-145 GEN
Solar/Wind Harmer
1.032
316197AC1-042 GEN
Solar/Wind Harmer
0.782
942671AE2-283 GEN
Solar/Wind Harmer
2.107
315821AE2-092 GEN
Solar/Wind Helper
2.531
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.379
971563AH1-280 GEN
Solar/Wind Harmer
6.379
970685AG2-442 GEN
Solar/Wind Harmer
41.041
962491AG1-098 GEN
Solar/Wind Harmer
28.467
315693AD1-088 GEN
Solar/Wind Harmer
20.844
957481AF2-042 GEN
Solar/Wind Harmer
119.424
316237AB2-079_GEN
Solar/Wind Harmer
0.967
315687AD1-152 GEN
Solar/Wind Harmer
3.708
970401AG2-262 GEN
Solar/Wind Harmer
1.822
316003AC1-222 GEN
Solar/Wind Harmer
2.219
971065AG2-659 GEN
Solar/Wind Harmer
10.747
316129AC1-054 GEN
Solar/Wind Harmer
1.803
971795AH1-408 GEN
Solar/Wind Harmer
11.364
960081AF2-299 GEN
Solar/Wind Harmer
1.186
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.658
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.951
316049AB1-081 GEN
Solar/Wind Harmer
0.761
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.707
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
970223AG2-152 GEN
Solar/Wind Harmer
5.68
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.385
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.31
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.385
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:207.29 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:1184.7
MW Contribution:3.98
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.952
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.158
3151411GASTONB
50/50
0.158
316322AB2-045
Solar/Wind Harmer
0.006
3146776BUCKING
Solar/Wind Harmer
0.305
3146926FARMVIL
Solar/Wind Harmer
0.38
963171AG1-166 GEN
Solar/Wind Harmer
2.423
971563AH1-280 GEN
Solar/Wind Harmer
4.845
970685AG2-442 GEN
Solar/Wind Harmer
31.17
962491AG1-098 GEN
Solar/Wind Harmer
21.62
315693AD1-088 GEN
Solar/Wind Harmer
17.81
957481AF2-042 GEN
Solar/Wind Harmer
90.702
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.457
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.163
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
8.991
960081AF2-299 GEN
Solar/Wind Harmer
0.901
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.348
3146233WITAKRS
Solar/Wind Harmer
0.26
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
316359AB2-059 GEN
Solar/Wind Harmer
0.225
316049AB1-081 GEN
Solar/Wind Harmer
0.359
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.061
315722AD1-056 GEN
Solar/Wind Harmer
0.381
3145796HORNRTN
Solar/Wind Harmer
0.194
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.064
962571AG1-106 GEN
Solar/Wind Harmer
0.833
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.252
970223AG2-152 GEN
Solar/Wind Harmer
3.983
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.042
941801AE2-185 GEN
Solar/Wind Harmer
1.811
3145823KELFORD
Solar/Wind Harmer
0.056
316336AC2-165 C
Solar/Wind Helper
1.31
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.158
3151411GASTONB
50/50
0.158
3146776BUCKING
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Harmer
0.38
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.219
963181AG1-167 GEN
Solar/Wind Harmer
1.817
959311AF2-222 GEN
Solar/Wind Harmer
34.634
970257AG2-171 GEN
Solar/Wind Harmer
12.109
315785AD2-033 C
Solar/Wind Harmer
2.951
964241AG1-285 GEN
Solar/Wind Harmer
21.461
316478AD1-087 GEN
Solar/Wind Harmer
1.114
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.934
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.29
971683AH1-343 GEN
Solar/Wind Harmer
6.951
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.286
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.624
3146233WITAKRS
Solar/Wind Harmer
0.328
3146233WITAKRS
Solar/Wind Harmer
0.044
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.061
961601AG1-000A GEN
Solar/Wind Harmer
4.335
315724AD1-057 GEN
Solar/Wind Harmer
0.226
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.811
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.103
971845AH1-439 GEN
Solar/Wind Harmer
34.045
970285AG2-188 GEN
Solar/Wind Harmer
57.782
315657AE1-056 GEN
Solar/Wind Harmer
16.55
946301AF1-294 GEN
Solar/Wind Harmer
8.963
961791AG1-021 GEN
Solar/Wind Harmer
4.361
970683AG2-441 GEN
Solar/Wind Harmer
27.831
970681AG2-440 GEN
Solar/Wind Harmer
22.264
3144303KENBRDG
Solar/Wind Harmer
0.302
971443AH1-215 GEN
Solar/Wind Harmer
6.301
971967AH1-528 GEN
Solar/Wind Harmer
55.401
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.601
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.066
970831AG2-522 GEN
Solar/Wind Harmer
7.435
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.134
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.367
315607AA1-063A GEN
Solar/Wind Harmer
0.158
3146043SEABORD
Solar/Wind Harmer
0.075
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.249
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.44
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.251
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.212
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.099
3146776BUCKING
Solar/Wind Harmer
3.045
3146776BUCKING
Solar/Wind Harmer
0.247
970301AG2-198 GEN
Solar/Wind Harmer
22.286
971741AH1-377 GEN
Solar/Wind Harmer
48.371
3147133PAMPLIN
Solar/Wind Harmer
0.479
3147133PAMPLIN
Solar/Wind Harmer
0.383
958211AF2-115 GEN
Solar/Wind Harmer
5.451
963191AG1-168 GEN
Solar/Wind Harmer
1.817
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.146
971775AH1-396 GEN
Solar/Wind Harmer
0.605
970933AG2-581 GEN
Solar/Wind Harmer
27.701
970099AG2-077 GEN
Solar/Wind Harmer
36.281
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.234
964791AG1-342 GEN
Solar/Wind Harmer
4.769
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.655
942751AE2-291 GEN
Solar/Wind Harmer
7.004
316222AC1-221 GEN
Solar/Wind Harmer
0.516
316181AB2-040 GEN
Solar/Wind Harmer
0.134
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.99
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.571
3145783HORNRTN
Solar/Wind Harmer
1.257
3145783HORNRTN
Solar/Wind Harmer
0.393
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.283
316274AC1-208 GEN
Solar/Wind Harmer
0.379
316263AC1-034 GEN
Solar/Wind Harmer
2.385
961601AG1-000A GEN
Solar/Wind Harmer
1.084
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.131
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.409
315821AE2-092 GEN
Solar/Wind Helper
2.531
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:204.76 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:1170.27
MW Contribution:3.98
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.158
3151411GASTONB
50/50
0.158
3146776BUCKING
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Harmer
0.38
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.219
963181AG1-167 GEN
Solar/Wind Harmer
1.817
959311AF2-222 GEN
Solar/Wind Harmer
34.634
970257AG2-171 GEN
Solar/Wind Harmer
12.109
315785AD2-033 C
Solar/Wind Harmer
2.951
964241AG1-285 GEN
Solar/Wind Harmer
21.461
316478AD1-087 GEN
Solar/Wind Harmer
1.114
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.934
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.29
971683AH1-343 GEN
Solar/Wind Harmer
6.951
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.286
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.624
3146233WITAKRS
Solar/Wind Harmer
0.328
3146233WITAKRS
Solar/Wind Harmer
0.044
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.061
961601AG1-000A GEN
Solar/Wind Harmer
4.335
315724AD1-057 GEN
Solar/Wind Harmer
0.226
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.811
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.212
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.099
3146776BUCKING
Solar/Wind Harmer
3.045
3146776BUCKING
Solar/Wind Harmer
0.247
970301AG2-198 GEN
Solar/Wind Harmer
22.286
971741AH1-377 GEN
Solar/Wind Harmer
48.371
3147133PAMPLIN
Solar/Wind Harmer
0.479
3147133PAMPLIN
Solar/Wind Harmer
0.383
958211AF2-115 GEN
Solar/Wind Harmer
5.451
963191AG1-168 GEN
Solar/Wind Harmer
1.817
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.146
971775AH1-396 GEN
Solar/Wind Harmer
0.605
970099AG2-077 GEN
Solar/Wind Harmer
36.281
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.234
964791AG1-342 GEN
Solar/Wind Harmer
4.769
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.655
942751AE2-291 GEN
Solar/Wind Harmer
7.004
316222AC1-221 GEN
Solar/Wind Harmer
0.516
316181AB2-040 GEN
Solar/Wind Harmer
0.134
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.99
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.571
3145783HORNRTN
Solar/Wind Harmer
1.257
3145783HORNRTN
Solar/Wind Harmer
0.393
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.283
316274AC1-208 GEN
Solar/Wind Harmer
0.379
316263AC1-034 GEN
Solar/Wind Harmer
2.385
961601AG1-000A GEN
Solar/Wind Harmer
1.084
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.131
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.409
315821AE2-092 GEN
Solar/Wind Helper
2.531
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.952
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.158
3151411GASTONB
50/50
0.158
316322AB2-045
Solar/Wind Harmer
0.006
3146776BUCKING
Solar/Wind Harmer
0.305
3146926FARMVIL
Solar/Wind Harmer
0.38
963171AG1-166 GEN
Solar/Wind Harmer
2.423
971563AH1-280 GEN
Solar/Wind Harmer
4.845
970685AG2-442 GEN
Solar/Wind Harmer
31.17
962491AG1-098 GEN
Solar/Wind Harmer
21.62
315693AD1-088 GEN
Solar/Wind Harmer
17.81
957481AF2-042 GEN
Solar/Wind Harmer
90.702
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.457
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.163
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
8.991
960081AF2-299 GEN
Solar/Wind Harmer
0.901
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.348
3146233WITAKRS
Solar/Wind Harmer
0.26
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
316359AB2-059 GEN
Solar/Wind Harmer
0.225
316049AB1-081 GEN
Solar/Wind Harmer
0.359
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.061
315722AD1-056 GEN
Solar/Wind Harmer
0.381
3145796HORNRTN
Solar/Wind Harmer
0.194
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.064
962571AG1-106 GEN
Solar/Wind Harmer
0.833
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.252
970223AG2-152 GEN
Solar/Wind Harmer
3.983
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.042
941801AE2-185 GEN
Solar/Wind Harmer
1.811
3145823KELFORD
Solar/Wind Harmer
0.056
316336AC2-165 C
Solar/Wind Helper
1.31
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.103
971845AH1-439 GEN
Solar/Wind Harmer
34.045
970285AG2-188 GEN
Solar/Wind Harmer
57.782
315657AE1-056 GEN
Solar/Wind Harmer
16.55
946301AF1-294 GEN
Solar/Wind Harmer
8.963
961791AG1-021 GEN
Solar/Wind Harmer
4.361
970683AG2-441 GEN
Solar/Wind Harmer
27.831
970681AG2-440 GEN
Solar/Wind Harmer
22.264
3144303KENBRDG
Solar/Wind Harmer
0.302
971443AH1-215 GEN
Solar/Wind Harmer
6.301
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.601
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.066
970831AG2-522 GEN
Solar/Wind Harmer
7.435
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.134
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.367
315607AA1-063A GEN
Solar/Wind Harmer
0.158
3146043SEABORD
Solar/Wind Harmer
0.075
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.249
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.44
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.251
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:203.45 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1422.11
MW Contribution:5.68
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.826
970285AG2-188 GEN
Solar/Wind Harmer
71.806
315657AE1-056 GEN
Solar/Wind Harmer
20.219
946301AF1-294 GEN
Solar/Wind Harmer
13.078
961791AG1-021 GEN
Solar/Wind Harmer
6.379
970683AG2-441 GEN
Solar/Wind Harmer
36.643
970681AG2-440 GEN
Solar/Wind Harmer
29.315
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.296
316239AB2-077_GEN
Solar/Wind Harmer
0.967
316238AB2-078_GEN
Solar/Wind Harmer
0.967
316118AC1-105 GEN
Solar/Wind Harmer
1.799
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.987
970831AG2-522 GEN
Solar/Wind Harmer
9.789
316123AC1-075 GEN
Solar/Wind Harmer
1.778
970165AG2-112 GEN
Solar/Wind Harmer
1.566
970163AG2-111 GEN
Solar/Wind Harmer
1.494
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.49
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.605
270457AD2-023 GEN
Solar/Wind Harmer
0.814
315607AA1-063A GEN
Solar/Wind Harmer
0.881
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.406
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.564
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.331
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
-0.168
971193AH1-056 GEN
Solar/Wind Harmer
33.698
963181AG1-167 GEN
Solar/Wind Harmer
4.785
959311AF2-222 GEN
Solar/Wind Harmer
45.693
970257AG2-171 GEN
Solar/Wind Harmer
15.944
315785AD2-033 C
Solar/Wind Harmer
9.243
964241AG1-285 GEN
Solar/Wind Harmer
28.257
316478AD1-087 GEN
Solar/Wind Harmer
3.106
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.6
316248AF1-058 C
Solar/Wind Harmer
0.737
960061AF2-297 GEN
Solar/Wind Harmer
12.232
971683AH1-343 GEN
Solar/Wind Harmer
9.152
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.287
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.767
316210AC1-098 GEN
Solar/Wind Harmer
1.185
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.727
315724AD1-057 GEN
Solar/Wind Harmer
0.389
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.385
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.343
971741AH1-377 GEN
Solar/Wind Harmer
63.689
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.974
963191AG1-168 GEN
Solar/Wind Harmer
4.785
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.258
971775AH1-396 GEN
Solar/Wind Harmer
3.027
970099AG2-077 GEN
Solar/Wind Harmer
47.77
313527AB2-043 GEN
Solar/Wind Harmer
5.31
962561AG1-105 GEN
Solar/Wind Harmer
16.108
964791AG1-342 GEN
Solar/Wind Harmer
5.961
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.346
942751AE2-291 GEN
Solar/Wind Harmer
9.222
316222AC1-221 GEN
Solar/Wind Harmer
1.414
316181AB2-040 GEN
Solar/Wind Harmer
1.452
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.154
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.178
3145783HORNRTN
Solar/Wind Harmer
0.943
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.884
316263AC1-034 GEN
Solar/Wind Harmer
3.306
961601AG1-000A GEN
Solar/Wind Harmer
2.693
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
316217AC1-145 GEN
Solar/Wind Harmer
1.032
316197AC1-042 GEN
Solar/Wind Harmer
0.782
942671AE2-283 GEN
Solar/Wind Harmer
2.107
315821AE2-092 GEN
Solar/Wind Helper
2.531
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.379
971563AH1-280 GEN
Solar/Wind Harmer
6.379
970685AG2-442 GEN
Solar/Wind Harmer
41.041
962491AG1-098 GEN
Solar/Wind Harmer
28.467
315693AD1-088 GEN
Solar/Wind Harmer
20.844
957481AF2-042 GEN
Solar/Wind Harmer
119.424
316237AB2-079_GEN
Solar/Wind Harmer
0.967
315687AD1-152 GEN
Solar/Wind Harmer
3.708
970401AG2-262 GEN
Solar/Wind Harmer
1.822
316003AC1-222 GEN
Solar/Wind Harmer
2.219
971065AG2-659 GEN
Solar/Wind Harmer
10.747
316129AC1-054 GEN
Solar/Wind Harmer
1.803
971795AH1-408 GEN
Solar/Wind Harmer
11.364
960081AF2-299 GEN
Solar/Wind Harmer
1.186
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.658
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.951
316049AB1-081 GEN
Solar/Wind Harmer
0.761
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.707
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
970223AG2-152 GEN
Solar/Wind Harmer
5.68
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.385
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.31
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:203.45 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1422.11
MW Contribution:5.68
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.826
970285AG2-188 GEN
Solar/Wind Harmer
71.806
315657AE1-056 GEN
Solar/Wind Harmer
20.219
946301AF1-294 GEN
Solar/Wind Harmer
13.078
961791AG1-021 GEN
Solar/Wind Harmer
6.379
970683AG2-441 GEN
Solar/Wind Harmer
36.643
970681AG2-440 GEN
Solar/Wind Harmer
29.315
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.296
316239AB2-077_GEN
Solar/Wind Harmer
0.967
316238AB2-078_GEN
Solar/Wind Harmer
0.967
316118AC1-105 GEN
Solar/Wind Harmer
1.799
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.987
970831AG2-522 GEN
Solar/Wind Harmer
9.789
316123AC1-075 GEN
Solar/Wind Harmer
1.778
970165AG2-112 GEN
Solar/Wind Harmer
1.566
970163AG2-111 GEN
Solar/Wind Harmer
1.494
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.49
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.605
270457AD2-023 GEN
Solar/Wind Harmer
0.814
315607AA1-063A GEN
Solar/Wind Harmer
0.881
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.406
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.564
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.331
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
-0.168
971193AH1-056 GEN
Solar/Wind Harmer
33.698
963181AG1-167 GEN
Solar/Wind Harmer
4.785
959311AF2-222 GEN
Solar/Wind Harmer
45.693
970257AG2-171 GEN
Solar/Wind Harmer
15.944
315785AD2-033 C
Solar/Wind Harmer
9.243
964241AG1-285 GEN
Solar/Wind Harmer
28.257
316478AD1-087 GEN
Solar/Wind Harmer
3.106
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.6
316248AF1-058 C
Solar/Wind Harmer
0.737
960061AF2-297 GEN
Solar/Wind Harmer
12.232
971683AH1-343 GEN
Solar/Wind Harmer
9.152
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.287
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.767
316210AC1-098 GEN
Solar/Wind Harmer
1.185
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.727
315724AD1-057 GEN
Solar/Wind Harmer
0.389
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.385
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.343
971741AH1-377 GEN
Solar/Wind Harmer
63.689
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.974
963191AG1-168 GEN
Solar/Wind Harmer
4.785
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.258
971775AH1-396 GEN
Solar/Wind Harmer
3.027
970099AG2-077 GEN
Solar/Wind Harmer
47.77
313527AB2-043 GEN
Solar/Wind Harmer
5.31
962561AG1-105 GEN
Solar/Wind Harmer
16.108
964791AG1-342 GEN
Solar/Wind Harmer
5.961
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.346
942751AE2-291 GEN
Solar/Wind Harmer
9.222
316222AC1-221 GEN
Solar/Wind Harmer
1.414
316181AB2-040 GEN
Solar/Wind Harmer
1.452
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.154
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.178
3145783HORNRTN
Solar/Wind Harmer
0.943
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.884
316263AC1-034 GEN
Solar/Wind Harmer
3.306
961601AG1-000A GEN
Solar/Wind Harmer
2.693
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
316217AC1-145 GEN
Solar/Wind Harmer
1.032
316197AC1-042 GEN
Solar/Wind Harmer
0.782
942671AE2-283 GEN
Solar/Wind Harmer
2.107
315821AE2-092 GEN
Solar/Wind Helper
2.531
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.379
971563AH1-280 GEN
Solar/Wind Harmer
6.379
970685AG2-442 GEN
Solar/Wind Harmer
41.041
962491AG1-098 GEN
Solar/Wind Harmer
28.467
315693AD1-088 GEN
Solar/Wind Harmer
20.844
957481AF2-042 GEN
Solar/Wind Harmer
119.424
316237AB2-079_GEN
Solar/Wind Harmer
0.967
315687AD1-152 GEN
Solar/Wind Harmer
3.708
970401AG2-262 GEN
Solar/Wind Harmer
1.822
316003AC1-222 GEN
Solar/Wind Harmer
2.219
971065AG2-659 GEN
Solar/Wind Harmer
10.747
316129AC1-054 GEN
Solar/Wind Harmer
1.803
971795AH1-408 GEN
Solar/Wind Harmer
11.364
960081AF2-299 GEN
Solar/Wind Harmer
1.186
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.658
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.951
316049AB1-081 GEN
Solar/Wind Harmer
0.761
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.707
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
970223AG2-152 GEN
Solar/Wind Harmer
5.68
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.385
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.31
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042

Details for 6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line l/o DVP_P4-2: 509T570_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.83 %
Rating:997.0 MVA
Rating Type:C
MVA to Mitigate:1144.9
MW Contribution:13.36
Bus #Bus NameTypeMW Contribution
3147173SINAI
Solar/Wind Harmer
-0.042
3147243WELCO
Solar/Wind Harmer
-0.026
970865AG2-541 GEN
Solar/Wind Harmer
14.146
316118AC1-105 GEN
Solar/Wind Harmer
2.355
316123AC1-075 GEN
Solar/Wind Harmer
3.235
970165AG2-112 GEN
Solar/Wind Harmer
2.848
970163AG2-111 GEN
Solar/Wind Harmer
2.717
270455AD2-022 GEN
Solar/Wind Harmer
3.531
270457AD2-023 GEN
Solar/Wind Harmer
1.791
970085AG2-068 GEN
Solar/Wind Harmer
9.94
970581AG2-369 GEN
Solar/Wind Harmer
8.549
270069AE2-166 C O1
Solar/Wind Harmer
1.803
971981AH1-535 GEN
Solar/Wind Harmer
4.605
3143316POE
Solar/Wind Helper
0.634
316369SG1_INVT
Solar/Wind Helper
0.701
316132AB2-190 GEN1
Solar/Wind Helper
0.826
957831AF2-077 GEN
Solar/Wind Helper
0.192
319010AE1-072 C
Solar/Wind Helper
1.62
316305AF2-043 C
Solar/Wind Helper
0.189
316349AD2-085 GEN
Solar/Wind Helper
0.637
316233AE1-074 FULL
Solar/Wind Helper
0.211
957601AF2-054 GEN
Solar/Wind Helper
0.183
3141873WAN 176
Solar/Wind Helper
0.027
315662AE1-191 GEN
Solar/Wind Helper
0.732
315666AE1-190 GEN
Solar/Wind Helper
0.183
3143873LANEXA
Solar/Wind Helper
0.081
316059AD1-063 C
Solar/Wind Helper
0.137
3141913WHIT STONE
Solar/Wind Helper
0.135
3138133OCRAN
Solar/Wind Helper
0.04
3141783LANCAST
Solar/Wind Helper
0.08
3141783LANCAST
Solar/Wind Helper
0.054
313526AB2-022
Solar/Wind Helper
0.2
316315AB2-025 C
Solar/Wind Helper
0.199
3146486SUNBURY
Solar/Wind Helper
0.128
3146486SUNBURY
Solar/Wind Helper
0.128
3141813NORNECK
Solar/Wind Helper
0.128
316312AB1-027
Solar/Wind Helper
0.241
316321Z2-027
Solar/Wind Helper
0.193
3145176PASQUOTANK
Solar/Wind Helper
0.078
316223AC1-118
Solar/Wind Helper
0.184
971629AH1-314 GEN
50/50
13.489
3151561HALLBR1
50/50
0.374
24728405LEESVG
50/50
0.136
315687AD1-152 GEN
Solar/Wind Harmer
8.943
316003AC1-222 GEN
Solar/Wind Harmer
3.856
970401AG2-262 GEN
Solar/Wind Harmer
1.705
3147123OTTER R
Solar/Wind Harmer
-0.01
970087AG2-069 GEN
Solar/Wind Harmer
14.91
970919AG2-571 GEN
Solar/Wind Harmer
5.033
970223AG2-152 GEN
Solar/Wind Harmer
13.358
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.461
270016AE1-250 BESS
Solar/Wind Harmer
2.226
270574AD1-017 GEN2
Solar/Wind Harmer
4.502
270030AE2-140 GEN
Solar/Wind Harmer
14.747
270173AC1-122 GEN
Solar/Wind Harmer
1.038
316359AB2-059 GEN
Solar/Wind Harmer
0.937
316049AB1-081 GEN
Solar/Wind Harmer
0.75
3142053HEARTS
Solar/Wind Harmer
0.082
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146926FARMVIL
Solar/Wind Helper
0.145
316322AB2-045
Solar/Wind Helper
0.217
3146776BUCKING
Solar/Wind Helper
0.078
316294AC1-161 GEN
Solar/Wind Helper
3.077
316375AC2-012 GEN
Solar/Wind Helper
0.404
3145336SMITFLD
Solar/Wind Helper
0.602
316381AD1-082 GEN
Solar/Wind Helper
0.757
316388AE2-253 GEN
Solar/Wind Helper
0.555
316458AB2-190 GEN2
Solar/Wind Helper
0.826
316159AE1-175 C
Solar/Wind Helper
0.218
3146456SLIGO L269
Solar/Wind Helper
0.143
316072AD1-144
Solar/Wind Helper
0.163
3143226MDLTHAN
Solar/Wind Helper
0.141
316246AF1-032 C
Solar/Wind Helper
0.161
316336AC2-165 C
Solar/Wind Helper
0.752
3143526WINTERP
Solar/Wind Helper
0.718
3142543TWELFTH
Solar/Wind Helper
0.013
3142433PROV 92
Solar/Wind Helper
0.545
3141766HARMONY
Solar/Wind Helper
0.027
3138133OCRAN
Solar/Wind Helper
0.081
964211AG1-282 GEN
Solar/Wind Helper
0.173
3141726DUNNSVL
Solar/Wind Helper
0.513
3142416OLDCHRC
Solar/Wind Helper
0.33
3142416OLDCHRC
Solar/Wind Helper
0.126
316337AD2-073 GEN
Solar/Wind Helper
0.188
3146516WINFALL
Solar/Wind Helper
0.38
3146516WINFALL
Solar/Wind Helper
0.117
3152661PLYWOOD A
50/50
0.685
316222AC1-221 GEN
Solar/Wind Harmer
3.1
942751AE2-291 GEN
Solar/Wind Harmer
17.158
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
964791AG1-342 GEN
Solar/Wind Harmer
5.579
962561AG1-105 GEN
Solar/Wind Harmer
12.783
316217AC1-145 GEN
Solar/Wind Harmer
2.364
316197AC1-042 GEN
Solar/Wind Harmer
1.792
942671AE2-283 GEN
Solar/Wind Harmer
4.824
270013AE1-250 PV
Solar/Wind Harmer
2.226
961601AG1-000A GEN
Solar/Wind Harmer
2.749
316263AC1-034 GEN
Solar/Wind Harmer
3.259
3146776BUCKING
Solar/Wind Helper
0.779
3146776BUCKING
Solar/Wind Helper
0.063
316036AC1-147 C
Solar/Wind Helper
0.235
316316AC1-027 C
Solar/Wind Helper
0.241
3142956BIRDNECK
Solar/Wind Helper
0.103
316185AD1-033 GEN
Solar/Wind Helper
0.715
316236AE1-162_GEN
Solar/Wind Helper
0.202
3145506HICKORY
Solar/Wind Helper
0.599
3145506HICKORY
Solar/Wind Helper
0.359
3145506HICKORY
Solar/Wind Helper
0.09
316240AF1-291 C
Solar/Wind Helper
0.198
316339AD2-160 GEN
Solar/Wind Helper
0.555
316033AB2-134 GEN
Solar/Wind Helper
0.501
315697AD1-025 GEN
Solar/Wind Helper
1.666
316018AA1-139 ULT2
Solar/Wind Helper
0.622
316017AA1-139 ULT1
Solar/Wind Helper
0.661
3137176SLIGO L2192
Solar/Wind Helper
0.569
3130086AYDLETT
Solar/Wind Helper
0.564
3143526WINTERP
Solar/Wind Helper
0.718
3142946ENON
Solar/Wind Helper
0.014
316075AC2-137 C
Solar/Wind Helper
0.201
316487AF1-042 GEN
Solar/Wind Helper
0.133
3146386ELIZ CT
Solar/Wind Helper
0.131
3144356SAPONY
Solar/Wind Helper
0.234
316077AC2-138 C
Solar/Wind Helper
0.12
966871AG1-558 GEN
Solar/Wind Helper
0.165
316431W1029_GEN1
Solar/Wind Helper
0.485
316433W1029_GEN2
Solar/Wind Helper
0.485
3146516WINFALL
Solar/Wind Helper
0.117
3146516WINFALL
Solar/Wind Helper
0.117
3146516WINFALL
Solar/Wind Helper
0.117
316468AD1-105 GEN
Solar/Wind Helper
0.568
24728405LEESVG
50/50
0.137
316248AF1-058 C
Solar/Wind Harmer
1.27
960061AF2-297 GEN
Solar/Wind Harmer
21.067
971683AH1-343 GEN
Solar/Wind Harmer
16.042
316283AC2-100 C
Solar/Wind Harmer
2.82
970917AG2-570 GEN
Solar/Wind Harmer
39.759
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.461
270197AD1-017 GEN1
Solar/Wind Harmer
1.353
270018AE2-047 C O1
Solar/Wind Harmer
1.019
943811AF1-049 GEN
Solar/Wind Harmer
2.868
270336AE1-100 GEN
Solar/Wind Harmer
1.167
971367AH1-164 GEN
Solar/Wind Harmer
1.912
961601AG1-000A GEN
Solar/Wind Harmer
2.784
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316478AD1-087 GEN
Solar/Wind Helper
3.08
316486AD2-202 GEN
Solar/Wind Helper
0.902
3146926FARMVIL
Solar/Wind Helper
0.145
3146776BUCKING
Solar/Wind Helper
0.07
315773AC2-141 GEN
Solar/Wind Helper
3.622
942461AE2-259 GEN
Solar/Wind Helper
1.133
3144873MCLAUGH
Solar/Wind Helper
0.004
3144536CHRHLND
Solar/Wind Helper
0.023
315839AE2-212 C
Solar/Wind Helper
0.205
3145336SMITFLD
Solar/Wind Helper
0.06
316382AG1-145 C
Solar/Wind Helper
0.193
3146456SLIGO L269
Solar/Wind Helper
0.143
316313AB2-026
Solar/Wind Helper
0.213
316258AE1-075 C
Solar/Wind Helper
0.192
316405AF2-144 C
Solar/Wind Helper
0.16
316156AD2-030 GEN
Solar/Wind Helper
0.206
316280AD1-041 GEN
Solar/Wind Helper
0.457
3142946ENON
Solar/Wind Helper
0.045
316484AD2-074 GEN
Solar/Wind Helper
0.254
316320Y1-086
Solar/Wind Helper
0.059
316404AE1-155 C
Solar/Wind Helper
1.1
316473AC1-191 GEN
Solar/Wind Helper
0.746
3141906WESTMOR
Solar/Wind Helper
0.048
316435W1029_GEN3
Solar/Wind Helper
0.485
3146516WINFALL
Solar/Wind Helper
0.117
LAGNLTFEXP_LAGN->PJM
CLTF
9.202
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.294
TVALTFEXP_TVA->PJM
CLTF
4.607
CPLELTFEXP_CPLE->PJM
CLTF
11.151
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.541
NYPJM->LTFIMP_NY
CLTF
0.755
LGEELTFEXP_LGEE->PJM
CLTF
1.98
WECLTFEXP_WEC->PJM
CLTF
1.048
CBM West 1LTFEXP_CBM-W1->PJM
CBM
38.067
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.134
MECLTFEXP_MEC->PJM
CLTF
5.224
SIGELTFEXP_SIGE->PJM
CLTF
0.159

Details for 6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.64 %
Rating:814.98 MVA
Rating Type:B
MVA to Mitigate:885.41
MW Contribution:9.44
Bus #Bus NameTypeMW Contribution
971629AH1-314 GEN
50/50
13.578
3151561HALLBR1
50/50
0.376
24728405LEESVG
50/50
0.138
970417AG2-272 GEN
50/50
1.899
24684705SMG5
50/50
0.33
970481AG2-311 GEN
50/50
4.594
315687AD1-152 GEN
Solar/Wind Harmer
0.022
316003AC1-222 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.37
3147123OTTER R
Solar/Wind Harmer
0.091
970087AG2-069 GEN
Solar/Wind Harmer
11.404
970919AG2-571 GEN
Solar/Wind Harmer
5.068
3147173SINAI
Solar/Wind Harmer
0.376
3147243WELCO
Solar/Wind Harmer
0.235
970865AG2-541 GEN
Solar/Wind Harmer
10.778
316118AC1-105 GEN
Solar/Wind Harmer
0.789
316123AC1-075 GEN
Solar/Wind Harmer
0.366
970223AG2-152 GEN
Solar/Wind Harmer
9.437
3147312GRETNA
Solar/Wind Harmer
0.104
3146802CHATHAM
Solar/Wind Harmer
0.098
941801AE2-185 GEN
Solar/Wind Harmer
4.18
270016AE1-250 BESS
Solar/Wind Harmer
0.004
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270030AE2-140 GEN
Solar/Wind Harmer
10.396
270173AC1-122 GEN
Solar/Wind Harmer
0.217
316359AB2-059 GEN
Solar/Wind Harmer
0.226
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3142053HEARTS
Solar/Wind Harmer
0.111
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
3146926FARMVIL
Solar/Wind Helper
0.144
316322AB2-045
Solar/Wind Helper
0.215
3146776BUCKING
Solar/Wind Helper
0.077
316294AC1-161 GEN
Solar/Wind Helper
3.041
316375AC2-012 GEN
Solar/Wind Helper
0.399
3145336SMITFLD
Solar/Wind Helper
0.594
316381AD1-082 GEN
Solar/Wind Helper
0.747
316388AE2-253 GEN
Solar/Wind Helper
0.548
316458AB2-190 GEN2
Solar/Wind Helper
0.815
316159AE1-175 C
Solar/Wind Helper
0.215
3146456SLIGO L269
Solar/Wind Helper
0.141
316072AD1-144
Solar/Wind Helper
0.16
3143226MDLTHAN
Solar/Wind Helper
0.139
316246AF1-032 C
Solar/Wind Helper
0.159
316336AC2-165 C
Solar/Wind Helper
0.741
3143526WINTERP
Solar/Wind Helper
0.708
3142543TWELFTH
Solar/Wind Helper
0.013
3142433PROV 92
Solar/Wind Helper
0.538
3141766HARMONY
Solar/Wind Helper
0.027
3138133OCRAN
Solar/Wind Helper
0.08
964211AG1-282 GEN
Solar/Wind Helper
0.17
3141726DUNNSVL
Solar/Wind Helper
0.505
3142416OLDCHRC
Solar/Wind Helper
0.325
3142416OLDCHRC
Solar/Wind Helper
0.124
316337AD2-073 GEN
Solar/Wind Helper
0.185
3146516WINFALL
Solar/Wind Helper
0.373
24728405LEESVG
50/50
0.138
24684605SMG4
50/50
0.862
24288905REUSENS
50/50
0.013
316248AF1-058 C
Solar/Wind Harmer
0.003
960061AF2-297 GEN
Solar/Wind Harmer
16.042
971683AH1-343 GEN
Solar/Wind Harmer
12.22
316283AC2-100 C
Solar/Wind Harmer
0.523
970917AG2-570 GEN
Solar/Wind Harmer
12.67
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.18
270197AD1-017 GEN1
Solar/Wind Harmer
0.766
270018AE2-047 C O1
Solar/Wind Harmer
0.002
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.003
971367AH1-164 GEN
Solar/Wind Harmer
1.353
961601AG1-000A GEN
Solar/Wind Harmer
4.498
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
316478AD1-087 GEN
Solar/Wind Helper
3.07
316486AD2-202 GEN
Solar/Wind Helper
0.899
3146926FARMVIL
Solar/Wind Helper
0.144
3146776BUCKING
Solar/Wind Helper
0.069
315773AC2-141 GEN
Solar/Wind Helper
3.58
942461AE2-259 GEN
Solar/Wind Helper
1.12
3144873MCLAUGH
Solar/Wind Helper
0.004
3144536CHRHLND
Solar/Wind Helper
0.023
315839AE2-212 C
Solar/Wind Helper
0.202
3145336SMITFLD
Solar/Wind Helper
0.059
316382AG1-145 C
Solar/Wind Helper
0.191
3146456SLIGO L269
Solar/Wind Helper
0.141
316313AB2-026
Solar/Wind Helper
0.21
316258AE1-075 C
Solar/Wind Helper
0.189
316405AF2-144 C
Solar/Wind Helper
0.157
316156AD2-030 GEN
Solar/Wind Helper
0.203
316280AD1-041 GEN
Solar/Wind Helper
0.451
3142946ENON
Solar/Wind Helper
0.045
316484AD2-074 GEN
Solar/Wind Helper
0.25
316320Y1-086
Solar/Wind Helper
0.058
316404AE1-155 C
Solar/Wind Helper
1.083
316473AC1-191 GEN
Solar/Wind Helper
0.734
3141906WESTMOR
Solar/Wind Helper
0.047
316435W1029_GEN3
Solar/Wind Helper
0.477
3146516WINFALL
Solar/Wind Helper
0.115
970165AG2-112 GEN
Solar/Wind Harmer
2.171
970163AG2-111 GEN
Solar/Wind Harmer
2.071
970085AG2-068 GEN
Solar/Wind Harmer
7.603
970581AG2-369 GEN
Solar/Wind Harmer
6.538
270069AE2-166 C O1
Solar/Wind Harmer
0.003
971981AH1-535 GEN
Solar/Wind Harmer
2.177
3143316POE
Solar/Wind Helper
0.626
316369SG1_INVT
Solar/Wind Helper
0.691
316132AB2-190 GEN1
Solar/Wind Helper
0.815
957831AF2-077 GEN
Solar/Wind Helper
0.189
319010AE1-072 C
Solar/Wind Helper
1.597
316305AF2-043 C
Solar/Wind Helper
0.186
316349AD2-085 GEN
Solar/Wind Helper
0.628
316233AE1-074 FULL
Solar/Wind Helper
0.208
957601AF2-054 GEN
Solar/Wind Helper
0.18
3141873WAN 176
Solar/Wind Helper
0.027
315662AE1-191 GEN
Solar/Wind Helper
0.721
315666AE1-190 GEN
Solar/Wind Helper
0.18
3143873LANEXA
Solar/Wind Helper
0.08
316059AD1-063 C
Solar/Wind Helper
0.135
3141913WHIT STONE
Solar/Wind Helper
0.133
3138133OCRAN
Solar/Wind Helper
0.04
3141783LANCAST
Solar/Wind Helper
0.079
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.196
3146486SUNBURY
Solar/Wind Helper
0.126
3146486SUNBURY
Solar/Wind Helper
0.126
3141813NORNECK
Solar/Wind Helper
0.126
316312AB1-027
Solar/Wind Helper
0.238
316321Z2-027
Solar/Wind Helper
0.19
3145176PASQUOTANK
Solar/Wind Helper
0.077
316223AC1-118
Solar/Wind Helper
0.181
3146516WINFALL
Solar/Wind Helper
0.115
3152661PLYWOOD A
50/50
0.687
24684405SMG2
50/50
0.856
24684505SMG3
50/50
0.529
24684305SMG1
50/50
0.31
316222AC1-221 GEN
Solar/Wind Harmer
1.136
942751AE2-291 GEN
Solar/Wind Harmer
13.086
3146843MT LREL
Solar/Wind Harmer
0.235
3146843MT LREL
Solar/Wind Harmer
0.235
964791AG1-342 GEN
Solar/Wind Harmer
4.482
962561AG1-105 GEN
Solar/Wind Harmer
9.757
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.251
270013AE1-250 PV
Solar/Wind Harmer
0.004
961601AG1-000A GEN
Solar/Wind Harmer
1.124
316263AC1-034 GEN
Solar/Wind Harmer
2.389
3146776BUCKING
Solar/Wind Helper
0.771
3146776BUCKING
Solar/Wind Helper
0.062
316036AC1-147 C
Solar/Wind Helper
0.232
3142956BIRDNECK
Solar/Wind Helper
0.102
316316AC1-027 C
Solar/Wind Helper
0.238
316185AD1-033 GEN
Solar/Wind Helper
0.706
316236AE1-162_GEN
Solar/Wind Helper
0.2
3145506HICKORY
Solar/Wind Helper
0.591
3145506HICKORY
Solar/Wind Helper
0.355
3145506HICKORY
Solar/Wind Helper
0.089
316240AF1-291 C
Solar/Wind Helper
0.195
316339AD2-160 GEN
Solar/Wind Helper
0.548
316033AB2-134 GEN
Solar/Wind Helper
0.494
315697AD1-025 GEN
Solar/Wind Helper
1.643
316018AA1-139 ULT2
Solar/Wind Helper
0.614
316017AA1-139 ULT1
Solar/Wind Helper
0.652
3137176SLIGO L2192
Solar/Wind Helper
0.561
3130086AYDLETT
Solar/Wind Helper
0.556
3143526WINTERP
Solar/Wind Helper
0.708
3142946ENON
Solar/Wind Helper
0.013
316075AC2-137 C
Solar/Wind Helper
0.198
316487AF1-042 GEN
Solar/Wind Helper
0.131
3146386ELIZ CT
Solar/Wind Helper
0.129
3144356SAPONY
Solar/Wind Helper
0.23
316077AC2-138 C
Solar/Wind Helper
0.118
966871AG1-558 GEN
Solar/Wind Helper
0.162
316431W1029_GEN1
Solar/Wind Helper
0.477
316433W1029_GEN2
Solar/Wind Helper
0.477
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
316468AD1-105 GEN
Solar/Wind Helper
0.559
LAGNLTFEXP_LAGN->PJM
CLTF
9.357
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.525
TVALTFEXP_TVA->PJM
CLTF
4.684
CPLELTFEXP_CPLE->PJM
CLTF
11.235
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.568
NYPJM->LTFIMP_NY
CLTF
0.706
LGEELTFEXP_LGEE->PJM
CLTF
2.033
WECLTFEXP_WEC->PJM
CLTF
1.077
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.091
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.18
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.424
MECLTFEXP_MEC->PJM
CLTF
5.352
SIGELTFEXP_SIGE->PJM
CLTF
0.163

Details for 6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.47 %
Rating:814.98 MVA
Rating Type:B
MVA to Mitigate:867.67
MW Contribution:9.44
Bus #Bus NameTypeMW Contribution
3147173SINAI
Solar/Wind Harmer
0.376
3147243WELCO
Solar/Wind Harmer
0.235
970865AG2-541 GEN
Solar/Wind Harmer
10.778
316118AC1-105 GEN
Solar/Wind Harmer
0.789
316123AC1-075 GEN
Solar/Wind Harmer
0.366
970165AG2-112 GEN
Solar/Wind Harmer
2.171
970163AG2-111 GEN
Solar/Wind Harmer
2.071
970085AG2-068 GEN
Solar/Wind Harmer
7.603
970581AG2-369 GEN
Solar/Wind Harmer
6.538
270069AE2-166 C O1
Solar/Wind Harmer
0.003
971981AH1-535 GEN
Solar/Wind Harmer
2.177
3143316POE
Solar/Wind Helper
0.626
3152661PLYWOOD A
50/50
0.687
24684405SMG2
50/50
0.856
24684505SMG3
50/50
0.529
24684305SMG1
50/50
0.31
316222AC1-221 GEN
Solar/Wind Harmer
1.136
942751AE2-291 GEN
Solar/Wind Harmer
13.086
3146843MT LREL
Solar/Wind Harmer
0.235
3146843MT LREL
Solar/Wind Harmer
0.235
964791AG1-342 GEN
Solar/Wind Harmer
4.482
962561AG1-105 GEN
Solar/Wind Harmer
9.757
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.251
270013AE1-250 PV
Solar/Wind Harmer
0.004
961601AG1-000A GEN
Solar/Wind Harmer
1.124
316263AC1-034 GEN
Solar/Wind Harmer
2.389
3146776BUCKING
Solar/Wind Helper
0.771
3146776BUCKING
Solar/Wind Helper
0.062
316036AC1-147 C
Solar/Wind Helper
0.232
3142956BIRDNECK
Solar/Wind Helper
0.102
316316AC1-027 C
Solar/Wind Helper
0.238
316185AD1-033 GEN
Solar/Wind Helper
0.706
316236AE1-162_GEN
Solar/Wind Helper
0.2
3145506HICKORY
Solar/Wind Helper
0.591
3145506HICKORY
Solar/Wind Helper
0.355
3145506HICKORY
Solar/Wind Helper
0.089
316240AF1-291 C
Solar/Wind Helper
0.195
316339AD2-160 GEN
Solar/Wind Helper
0.548
316033AB2-134 GEN
Solar/Wind Helper
0.494
315697AD1-025 GEN
Solar/Wind Helper
1.643
316018AA1-139 ULT2
Solar/Wind Helper
0.614
316017AA1-139 ULT1
Solar/Wind Helper
0.652
3137176SLIGO L2192
Solar/Wind Helper
0.561
3130086AYDLETT
Solar/Wind Helper
0.556
3143526WINTERP
Solar/Wind Helper
0.708
3142946ENON
Solar/Wind Helper
0.013
316075AC2-137 C
Solar/Wind Helper
0.198
316487AF1-042 GEN
Solar/Wind Helper
0.131
3146386ELIZ CT
Solar/Wind Helper
0.129
3144356SAPONY
Solar/Wind Helper
0.23
316077AC2-138 C
Solar/Wind Helper
0.118
966871AG1-558 GEN
Solar/Wind Helper
0.162
316431W1029_GEN1
Solar/Wind Helper
0.477
316433W1029_GEN2
Solar/Wind Helper
0.477
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
316468AD1-105 GEN
Solar/Wind Helper
0.559
971629AH1-314 GEN
50/50
13.578
3151561HALLBR1
50/50
0.376
24728405LEESVG
50/50
0.138
970417AG2-272 GEN
50/50
1.899
24684705SMG5
50/50
0.33
970481AG2-311 GEN
50/50
4.594
315687AD1-152 GEN
Solar/Wind Harmer
0.022
316003AC1-222 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.37
3147123OTTER R
Solar/Wind Harmer
0.091
970087AG2-069 GEN
Solar/Wind Harmer
11.404
970223AG2-152 GEN
Solar/Wind Harmer
9.437
3147312GRETNA
Solar/Wind Harmer
0.104
3146802CHATHAM
Solar/Wind Harmer
0.098
941801AE2-185 GEN
Solar/Wind Harmer
4.18
270016AE1-250 BESS
Solar/Wind Harmer
0.004
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270030AE2-140 GEN
Solar/Wind Harmer
10.396
270173AC1-122 GEN
Solar/Wind Harmer
0.217
316359AB2-059 GEN
Solar/Wind Harmer
0.226
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3142053HEARTS
Solar/Wind Harmer
0.111
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
3146926FARMVIL
Solar/Wind Helper
0.144
316322AB2-045
Solar/Wind Helper
0.215
3146776BUCKING
Solar/Wind Helper
0.077
316294AC1-161 GEN
Solar/Wind Helper
3.041
316375AC2-012 GEN
Solar/Wind Helper
0.399
3145336SMITFLD
Solar/Wind Helper
0.594
316381AD1-082 GEN
Solar/Wind Helper
0.747
316388AE2-253 GEN
Solar/Wind Helper
0.548
316458AB2-190 GEN2
Solar/Wind Helper
0.815
316159AE1-175 C
Solar/Wind Helper
0.215
3146456SLIGO L269
Solar/Wind Helper
0.141
316072AD1-144
Solar/Wind Helper
0.16
3143226MDLTHAN
Solar/Wind Helper
0.139
316246AF1-032 C
Solar/Wind Helper
0.159
316336AC2-165 C
Solar/Wind Helper
0.741
3143526WINTERP
Solar/Wind Helper
0.708
3142543TWELFTH
Solar/Wind Helper
0.013
3142433PROV 92
Solar/Wind Helper
0.538
3141766HARMONY
Solar/Wind Helper
0.027
3138133OCRAN
Solar/Wind Helper
0.08
964211AG1-282 GEN
Solar/Wind Helper
0.17
3141726DUNNSVL
Solar/Wind Helper
0.505
3142416OLDCHRC
Solar/Wind Helper
0.325
3142416OLDCHRC
Solar/Wind Helper
0.124
316337AD2-073 GEN
Solar/Wind Helper
0.185
3146516WINFALL
Solar/Wind Helper
0.373
3146516WINFALL
Solar/Wind Helper
0.115
316369SG1_INVT
Solar/Wind Helper
0.691
316132AB2-190 GEN1
Solar/Wind Helper
0.815
957831AF2-077 GEN
Solar/Wind Helper
0.189
319010AE1-072 C
Solar/Wind Helper
1.597
316305AF2-043 C
Solar/Wind Helper
0.186
316349AD2-085 GEN
Solar/Wind Helper
0.628
316233AE1-074 FULL
Solar/Wind Helper
0.208
957601AF2-054 GEN
Solar/Wind Helper
0.18
3141873WAN 176
Solar/Wind Helper
0.027
315662AE1-191 GEN
Solar/Wind Helper
0.721
315666AE1-190 GEN
Solar/Wind Helper
0.18
3143873LANEXA
Solar/Wind Helper
0.08
316059AD1-063 C
Solar/Wind Helper
0.135
3141913WHIT STONE
Solar/Wind Helper
0.133
3138133OCRAN
Solar/Wind Helper
0.04
3141783LANCAST
Solar/Wind Helper
0.079
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.196
3146486SUNBURY
Solar/Wind Helper
0.126
3146486SUNBURY
Solar/Wind Helper
0.126
3141813NORNECK
Solar/Wind Helper
0.126
316312AB1-027
Solar/Wind Helper
0.238
316321Z2-027
Solar/Wind Helper
0.19
3145176PASQUOTANK
Solar/Wind Helper
0.077
316223AC1-118
Solar/Wind Helper
0.181
24728405LEESVG
50/50
0.138
24684605SMG4
50/50
0.862
24288905REUSENS
50/50
0.013
316248AF1-058 C
Solar/Wind Harmer
0.003
960061AF2-297 GEN
Solar/Wind Harmer
16.042
971683AH1-343 GEN
Solar/Wind Harmer
12.22
316283AC2-100 C
Solar/Wind Harmer
0.523
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.18
270197AD1-017 GEN1
Solar/Wind Harmer
0.766
270018AE2-047 C O1
Solar/Wind Harmer
0.002
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.003
971367AH1-164 GEN
Solar/Wind Harmer
1.353
961601AG1-000A GEN
Solar/Wind Harmer
4.498
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
316478AD1-087 GEN
Solar/Wind Helper
3.07
316486AD2-202 GEN
Solar/Wind Helper
0.899
3146926FARMVIL
Solar/Wind Helper
0.144
3146776BUCKING
Solar/Wind Helper
0.069
315773AC2-141 GEN
Solar/Wind Helper
3.58
942461AE2-259 GEN
Solar/Wind Helper
1.12
3144873MCLAUGH
Solar/Wind Helper
0.004
3144536CHRHLND
Solar/Wind Helper
0.023
315839AE2-212 C
Solar/Wind Helper
0.202
3145336SMITFLD
Solar/Wind Helper
0.059
316382AG1-145 C
Solar/Wind Helper
0.191
3146456SLIGO L269
Solar/Wind Helper
0.141
316313AB2-026
Solar/Wind Helper
0.21
316258AE1-075 C
Solar/Wind Helper
0.189
316405AF2-144 C
Solar/Wind Helper
0.157
316156AD2-030 GEN
Solar/Wind Helper
0.203
316280AD1-041 GEN
Solar/Wind Helper
0.451
3142946ENON
Solar/Wind Helper
0.045
316484AD2-074 GEN
Solar/Wind Helper
0.25
316320Y1-086
Solar/Wind Helper
0.058
316404AE1-155 C
Solar/Wind Helper
1.083
316473AC1-191 GEN
Solar/Wind Helper
0.734
3141906WESTMOR
Solar/Wind Helper
0.047
316435W1029_GEN3
Solar/Wind Helper
0.477
3146516WINFALL
Solar/Wind Helper
0.115
LAGNLTFEXP_LAGN->PJM
CLTF
9.357
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.525
TVALTFEXP_TVA->PJM
CLTF
4.684
CPLELTFEXP_CPLE->PJM
CLTF
11.235
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.568
NYPJM->LTFIMP_NY
CLTF
0.706
LGEELTFEXP_LGEE->PJM
CLTF
2.033
WECLTFEXP_WEC->PJM
CLTF
1.077
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.091
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.18
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.424
MECLTFEXP_MEC->PJM
CLTF
5.352
SIGELTFEXP_SIGE->PJM
CLTF
0.163

Details for 6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line l/o DVP_P4-2: 57062_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57062_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.2 %
Rating:997.0 MVA
Rating Type:C
MVA to Mitigate:998.97
MW Contribution:13.46
Bus #Bus NameTypeMW Contribution
971629AH1-314 GEN
50/50
13.578
3151561HALLBR1
50/50
0.376
24728405LEESVG
50/50
0.138
315687AD1-152 GEN
Solar/Wind Harmer
8.957
316003AC1-222 GEN
Solar/Wind Harmer
3.867
970401AG2-262 GEN
Solar/Wind Harmer
1.712
3147123OTTER R
Solar/Wind Harmer
-0.01
970087AG2-069 GEN
Solar/Wind Harmer
15.015
970919AG2-571 GEN
Solar/Wind Harmer
5.068
970223AG2-152 GEN
Solar/Wind Harmer
13.457
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.503
270016AE1-250 BESS
Solar/Wind Harmer
2.243
270574AD1-017 GEN2
Solar/Wind Harmer
4.541
270030AE2-140 GEN
Solar/Wind Harmer
14.9
270173AC1-122 GEN
Solar/Wind Harmer
1.05
316359AB2-059 GEN
Solar/Wind Harmer
0.952
316049AB1-081 GEN
Solar/Wind Harmer
0.762
3142053HEARTS
Solar/Wind Harmer
0.083
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
24728405LEESVG
50/50
0.138
316248AF1-058 C
Solar/Wind Harmer
1.273
3152661PLYWOOD A
50/50
0.687
316222AC1-221 GEN
Solar/Wind Harmer
3.111
942751AE2-291 GEN
Solar/Wind Harmer
17.229
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
964791AG1-342 GEN
Solar/Wind Harmer
5.603
962561AG1-105 GEN
Solar/Wind Harmer
12.846
316217AC1-145 GEN
Solar/Wind Harmer
2.382
3147173SINAI
Solar/Wind Harmer
-0.042
3147243WELCO
Solar/Wind Harmer
-0.026
970865AG2-541 GEN
Solar/Wind Harmer
14.192
316118AC1-105 GEN
Solar/Wind Harmer
2.363
316123AC1-075 GEN
Solar/Wind Harmer
3.247
970165AG2-112 GEN
Solar/Wind Harmer
2.859
970163AG2-111 GEN
Solar/Wind Harmer
2.727
270455AD2-022 GEN
Solar/Wind Harmer
3.551
270457AD2-023 GEN
Solar/Wind Harmer
1.801
970085AG2-068 GEN
Solar/Wind Harmer
10.01
970581AG2-369 GEN
Solar/Wind Harmer
8.609
270069AE2-166 C O1
Solar/Wind Harmer
1.824
971981AH1-535 GEN
Solar/Wind Harmer
4.681
3143316POE
Solar/Wind Helper
0.626
316369SG1_INVT
Solar/Wind Helper
0.691
316132AB2-190 GEN1
Solar/Wind Helper
0.815
957831AF2-077 GEN
Solar/Wind Helper
0.189
316197AC1-042 GEN
Solar/Wind Harmer
1.806
942671AE2-283 GEN
Solar/Wind Harmer
4.861
270013AE1-250 PV
Solar/Wind Harmer
2.243
961601AG1-000A GEN
Solar/Wind Harmer
2.793
316263AC1-034 GEN
Solar/Wind Harmer
3.311
3146776BUCKING
Solar/Wind Helper
0.771
3146776BUCKING
Solar/Wind Helper
0.062
316036AC1-147 C
Solar/Wind Helper
0.232
3142956BIRDNECK
Solar/Wind Helper
0.102
316316AC1-027 C
Solar/Wind Helper
0.238
316185AD1-033 GEN
Solar/Wind Helper
0.706
316236AE1-162_GEN
Solar/Wind Helper
0.2
3145506HICKORY
Solar/Wind Helper
0.591
3145506HICKORY
Solar/Wind Helper
0.355
3145506HICKORY
Solar/Wind Helper
0.089
316240AF1-291 C
Solar/Wind Helper
0.195
316339AD2-160 GEN
Solar/Wind Helper
0.548
316033AB2-134 GEN
Solar/Wind Helper
0.494
315697AD1-025 GEN
Solar/Wind Helper
1.643
316018AA1-139 ULT2
Solar/Wind Helper
0.614
316017AA1-139 ULT1
Solar/Wind Helper
0.652
3137176SLIGO L2192
Solar/Wind Helper
0.561
3130086AYDLETT
Solar/Wind Helper
0.556
3143526WINTERP
Solar/Wind Helper
0.708
3142946ENON
Solar/Wind Helper
0.013
316075AC2-137 C
Solar/Wind Helper
0.198
316487AF1-042 GEN
Solar/Wind Helper
0.131
3146386ELIZ CT
Solar/Wind Helper
0.129
3144356SAPONY
Solar/Wind Helper
0.23
316077AC2-138 C
Solar/Wind Helper
0.118
966871AG1-558 GEN
Solar/Wind Helper
0.162
316431W1029_GEN1
Solar/Wind Helper
0.477
316433W1029_GEN2
Solar/Wind Helper
0.477
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
316468AD1-105 GEN
Solar/Wind Helper
0.559
319010AE1-072 C
Solar/Wind Helper
1.597
316305AF2-043 C
Solar/Wind Helper
0.186
316349AD2-085 GEN
Solar/Wind Helper
0.628
316233AE1-074 FULL
Solar/Wind Helper
0.208
957601AF2-054 GEN
Solar/Wind Helper
0.18
3141873WAN 176
Solar/Wind Helper
0.027
315662AE1-191 GEN
Solar/Wind Helper
0.721
315666AE1-190 GEN
Solar/Wind Helper
0.18
3143873LANEXA
Solar/Wind Helper
0.08
316059AD1-063 C
Solar/Wind Helper
0.135
3141913WHIT STONE
Solar/Wind Helper
0.133
3138133OCRAN
Solar/Wind Helper
0.04
3141783LANCAST
Solar/Wind Helper
0.079
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.196
3146486SUNBURY
Solar/Wind Helper
0.126
3146486SUNBURY
Solar/Wind Helper
0.126
3141813NORNECK
Solar/Wind Helper
0.126
316312AB1-027
Solar/Wind Helper
0.238
316321Z2-027
Solar/Wind Helper
0.19
3145176PASQUOTANK
Solar/Wind Helper
0.077
316223AC1-118
Solar/Wind Helper
0.181
3146926FARMVIL
Solar/Wind Helper
0.144
316322AB2-045
Solar/Wind Helper
0.215
3146776BUCKING
Solar/Wind Helper
0.077
316294AC1-161 GEN
Solar/Wind Helper
3.041
316375AC2-012 GEN
Solar/Wind Helper
0.399
3145336SMITFLD
Solar/Wind Helper
0.594
316381AD1-082 GEN
Solar/Wind Helper
0.747
316388AE2-253 GEN
Solar/Wind Helper
0.548
316458AB2-190 GEN2
Solar/Wind Helper
0.815
316159AE1-175 C
Solar/Wind Helper
0.215
3146456SLIGO L269
Solar/Wind Helper
0.141
316072AD1-144
Solar/Wind Helper
0.16
3143226MDLTHAN
Solar/Wind Helper
0.139
316246AF1-032 C
Solar/Wind Helper
0.159
316336AC2-165 C
Solar/Wind Helper
0.741
3143526WINTERP
Solar/Wind Helper
0.708
3142543TWELFTH
Solar/Wind Helper
0.013
3142433PROV 92
Solar/Wind Helper
0.538
3141766HARMONY
Solar/Wind Helper
0.027
3138133OCRAN
Solar/Wind Helper
0.08
964211AG1-282 GEN
Solar/Wind Helper
0.17
3141726DUNNSVL
Solar/Wind Helper
0.505
3142416OLDCHRC
Solar/Wind Helper
0.325
3142416OLDCHRC
Solar/Wind Helper
0.124
316337AD2-073 GEN
Solar/Wind Helper
0.185
3146516WINFALL
Solar/Wind Helper
0.373
3146516WINFALL
Solar/Wind Helper
0.115
960061AF2-297 GEN
Solar/Wind Harmer
21.123
971683AH1-343 GEN
Solar/Wind Harmer
16.09
316283AC2-100 C
Solar/Wind Harmer
2.83
970917AG2-570 GEN
Solar/Wind Harmer
40.038
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.503
270197AD1-017 GEN1
Solar/Wind Harmer
1.364
270018AE2-047 C O1
Solar/Wind Harmer
1.028
943811AF1-049 GEN
Solar/Wind Harmer
2.896
270336AE1-100 GEN
Solar/Wind Harmer
1.18
971367AH1-164 GEN
Solar/Wind Harmer
1.939
961601AG1-000A GEN
Solar/Wind Harmer
2.829
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316478AD1-087 GEN
Solar/Wind Helper
3.07
316486AD2-202 GEN
Solar/Wind Helper
0.899
3146926FARMVIL
Solar/Wind Helper
0.144
3146776BUCKING
Solar/Wind Helper
0.069
315773AC2-141 GEN
Solar/Wind Helper
3.58
942461AE2-259 GEN
Solar/Wind Helper
1.12
3144873MCLAUGH
Solar/Wind Helper
0.004
3144536CHRHLND
Solar/Wind Helper
0.023
315839AE2-212 C
Solar/Wind Helper
0.202
3145336SMITFLD
Solar/Wind Helper
0.059
316382AG1-145 C
Solar/Wind Helper
0.191
3146456SLIGO L269
Solar/Wind Helper
0.141
316313AB2-026
Solar/Wind Helper
0.21
316258AE1-075 C
Solar/Wind Helper
0.189
316405AF2-144 C
Solar/Wind Helper
0.157
316156AD2-030 GEN
Solar/Wind Helper
0.203
316280AD1-041 GEN
Solar/Wind Helper
0.451
3142946ENON
Solar/Wind Helper
0.045
316484AD2-074 GEN
Solar/Wind Helper
0.25
316320Y1-086
Solar/Wind Helper
0.058
316404AE1-155 C
Solar/Wind Helper
1.083
316473AC1-191 GEN
Solar/Wind Helper
0.734
3141906WESTMOR
Solar/Wind Helper
0.047
316435W1029_GEN3
Solar/Wind Helper
0.477
3146516WINFALL
Solar/Wind Helper
0.115
LAGNLTFEXP_LAGN->PJM
CLTF
9.357
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.525
TVALTFEXP_TVA->PJM
CLTF
4.684
CPLELTFEXP_CPLE->PJM
CLTF
11.235
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.568
NYPJM->LTFIMP_NY
CLTF
0.706
LGEELTFEXP_LGEE->PJM
CLTF
2.033
WECLTFEXP_WEC->PJM
CLTF
1.077
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.091
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.18
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.424
MECLTFEXP_MEC->PJM
CLTF
5.352
SIGELTFEXP_SIGE->PJM
CLTF
0.163

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:201.24 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1376.51
MW Contribution:5.79
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.835
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
315657AE1-056 GEN
Solar/Wind Harmer
20.241
946301AF1-294 GEN
Solar/Wind Harmer
13.094
961791AG1-021 GEN
Solar/Wind Harmer
6.387
970683AG2-441 GEN
Solar/Wind Harmer
36.695
970681AG2-440 GEN
Solar/Wind Harmer
29.356
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.31
971967AH1-528 GEN
Solar/Wind Harmer
73.321
316239AB2-077_GEN
Solar/Wind Harmer
0.97
316238AB2-078_GEN
Solar/Wind Harmer
0.97
316118AC1-105 GEN
Solar/Wind Harmer
1.807
3147173SINAI
Solar/Wind Harmer
-0.025
3144293JTRSVLE
50/50
1.536
3144293JTRSVLE
50/50
1.294
970535AG2-341 GEN
50/50
4.631
3152661PLYWOOD A
50/50
0.509
970301AG2-198 GEN
Solar/Wind Harmer
29.375
971741AH1-377 GEN
Solar/Wind Harmer
63.77
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.984
963191AG1-168 GEN
Solar/Wind Harmer
4.79
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.293
971775AH1-396 GEN
Solar/Wind Harmer
3.032
970933AG2-581 GEN
Solar/Wind Harmer
36.564
970099AG2-077 GEN
Solar/Wind Harmer
47.892
313527AB2-043 GEN
Solar/Wind Harmer
5.323
962561AG1-105 GEN
Solar/Wind Harmer
16.163
964791AG1-342 GEN
Solar/Wind Harmer
5.983
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.395
942751AE2-291 GEN
Solar/Wind Harmer
9.282
316222AC1-221 GEN
Solar/Wind Harmer
1.431
316181AB2-040 GEN
Solar/Wind Harmer
1.454
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.157
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.182
3145783HORNRTN
Solar/Wind Harmer
0.946
3145783HORNRTN
Solar/Wind Harmer
0.296
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.956
316274AC1-208 GEN
Solar/Wind Harmer
0.891
316263AC1-034 GEN
Solar/Wind Harmer
3.354
961601AG1-000A GEN
Solar/Wind Harmer
2.733
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.045
316197AC1-042 GEN
Solar/Wind Harmer
0.792
942671AE2-283 GEN
Solar/Wind Harmer
2.132
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.531
3144293JTRSVLE
50/50
1.536
3151531CLOVER1
50/50
6.868
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.479
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.387
971563AH1-280 GEN
Solar/Wind Harmer
6.387
970685AG2-442 GEN
Solar/Wind Harmer
41.098
962491AG1-098 GEN
Solar/Wind Harmer
28.527
315693AD1-088 GEN
Solar/Wind Harmer
20.89
957481AF2-042 GEN
Solar/Wind Harmer
119.73
316237AB2-079_GEN
Solar/Wind Harmer
0.97
315687AD1-152 GEN
Solar/Wind Harmer
3.722
970401AG2-262 GEN
Solar/Wind Harmer
1.828
316003AC1-222 GEN
Solar/Wind Harmer
2.23
971065AG2-659 GEN
Solar/Wind Harmer
10.784
316129AC1-054 GEN
Solar/Wind Harmer
1.809
971795AH1-408 GEN
Solar/Wind Harmer
11.382
960081AF2-299 GEN
Solar/Wind Harmer
1.187
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.663
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.965
316049AB1-081 GEN
Solar/Wind Harmer
0.772
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.715
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
970223AG2-152 GEN
Solar/Wind Harmer
5.79
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.192
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.414
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.314
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.03
970831AG2-522 GEN
Solar/Wind Harmer
9.822
316123AC1-075 GEN
Solar/Wind Harmer
1.789
970165AG2-112 GEN
Solar/Wind Harmer
1.575
970163AG2-111 GEN
Solar/Wind Harmer
1.503
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.493
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.635
270457AD2-023 GEN
Solar/Wind Harmer
0.829
315607AA1-063A GEN
Solar/Wind Harmer
0.882
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.411
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.563
270494AE1-108_GEN
Solar/Wind Helper
3.665
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.536
970413AG2-270 GEN
50/50
29.97
3151591KERR 2
50/50
0.482
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.339
970909AG2-566 GEN
Solar/Wind Harmer
5.578
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.735
963181AG1-167 GEN
Solar/Wind Harmer
4.79
959311AF2-222 GEN
Solar/Wind Harmer
45.765
970257AG2-171 GEN
Solar/Wind Harmer
15.97
315785AD2-033 C
Solar/Wind Harmer
9.259
964241AG1-285 GEN
Solar/Wind Harmer
28.316
316478AD1-087 GEN
Solar/Wind Harmer
3.115
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.609
316248AF1-058 C
Solar/Wind Harmer
0.741
960061AF2-297 GEN
Solar/Wind Harmer
12.289
971683AH1-343 GEN
Solar/Wind Harmer
9.199
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.303
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.775
316210AC1-098 GEN
Solar/Wind Harmer
1.194
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.767
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.393
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.414
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.317
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
LAGNLTFEXP_LAGN->PJM
CLTF
3.212
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.896
TVALTFEXP_TVA->PJM
CLTF
1.599
CPLELTFEXP_CPLE->PJM
CLTF
5.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.616
NYPJM->LTFIMP_NY
CLTF
0.52
LGEELTFEXP_LGEE->PJM
CLTF
0.521
WECLTFEXP_WEC->PJM
CLTF
0.271
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.51
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.435
MECLTFEXP_MEC->PJM
CLTF
1.488
SIGELTFEXP_SIGE->PJM
CLTF
0.044

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:201.19 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1376.13
MW Contribution:5.79
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.536
3151531CLOVER1
50/50
6.868
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.479
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.387
971563AH1-280 GEN
Solar/Wind Harmer
6.387
970685AG2-442 GEN
Solar/Wind Harmer
41.098
962491AG1-098 GEN
Solar/Wind Harmer
28.527
315693AD1-088 GEN
Solar/Wind Harmer
20.89
957481AF2-042 GEN
Solar/Wind Harmer
119.73
316237AB2-079_GEN
Solar/Wind Harmer
0.97
315687AD1-152 GEN
Solar/Wind Harmer
3.722
970401AG2-262 GEN
Solar/Wind Harmer
1.828
316003AC1-222 GEN
Solar/Wind Harmer
2.23
971065AG2-659 GEN
Solar/Wind Harmer
10.784
316129AC1-054 GEN
Solar/Wind Harmer
1.809
971795AH1-408 GEN
Solar/Wind Harmer
11.382
960081AF2-299 GEN
Solar/Wind Harmer
1.187
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3151541CLOVER2
50/50
6.835
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
315657AE1-056 GEN
Solar/Wind Harmer
20.241
946301AF1-294 GEN
Solar/Wind Harmer
13.094
961791AG1-021 GEN
Solar/Wind Harmer
6.387
970683AG2-441 GEN
Solar/Wind Harmer
36.695
970681AG2-440 GEN
Solar/Wind Harmer
29.356
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.31
971967AH1-528 GEN
Solar/Wind Harmer
73.321
316239AB2-077_GEN
Solar/Wind Harmer
0.97
316238AB2-078_GEN
Solar/Wind Harmer
0.97
316118AC1-105 GEN
Solar/Wind Harmer
1.807
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.03
970831AG2-522 GEN
Solar/Wind Harmer
9.822
316123AC1-075 GEN
Solar/Wind Harmer
1.789
3144293JTRSVLE
50/50
1.536
970413AG2-270 GEN
50/50
29.97
3151591KERR 2
50/50
0.482
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.339
970909AG2-566 GEN
Solar/Wind Harmer
5.578
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.735
963181AG1-167 GEN
Solar/Wind Harmer
4.79
959311AF2-222 GEN
Solar/Wind Harmer
45.765
970257AG2-171 GEN
Solar/Wind Harmer
15.97
315785AD2-033 C
Solar/Wind Harmer
9.259
964241AG1-285 GEN
Solar/Wind Harmer
28.316
316478AD1-087 GEN
Solar/Wind Harmer
3.115
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.609
316248AF1-058 C
Solar/Wind Harmer
0.741
960061AF2-297 GEN
Solar/Wind Harmer
12.289
971683AH1-343 GEN
Solar/Wind Harmer
9.199
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.303
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.775
316210AC1-098 GEN
Solar/Wind Harmer
1.194
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.767
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.393
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.414
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.317
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
3144293JTRSVLE
50/50
1.536
3144293JTRSVLE
50/50
1.294
970535AG2-341 GEN
50/50
4.631
3152661PLYWOOD A
50/50
0.509
970301AG2-198 GEN
Solar/Wind Harmer
29.375
971741AH1-377 GEN
Solar/Wind Harmer
63.77
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.984
963191AG1-168 GEN
Solar/Wind Harmer
4.79
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.293
971775AH1-396 GEN
Solar/Wind Harmer
3.032
970933AG2-581 GEN
Solar/Wind Harmer
36.564
970099AG2-077 GEN
Solar/Wind Harmer
47.892
313527AB2-043 GEN
Solar/Wind Harmer
5.323
962561AG1-105 GEN
Solar/Wind Harmer
16.163
964791AG1-342 GEN
Solar/Wind Harmer
5.983
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.395
942751AE2-291 GEN
Solar/Wind Harmer
9.282
316222AC1-221 GEN
Solar/Wind Harmer
1.431
316181AB2-040 GEN
Solar/Wind Harmer
1.454
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.157
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.182
3145783HORNRTN
Solar/Wind Harmer
0.946
3145783HORNRTN
Solar/Wind Harmer
0.296
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.956
316274AC1-208 GEN
Solar/Wind Harmer
0.891
316263AC1-034 GEN
Solar/Wind Harmer
3.354
961601AG1-000A GEN
Solar/Wind Harmer
2.733
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
970165AG2-112 GEN
Solar/Wind Harmer
1.575
970163AG2-111 GEN
Solar/Wind Harmer
1.503
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.493
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.635
270457AD2-023 GEN
Solar/Wind Harmer
0.829
315607AA1-063A GEN
Solar/Wind Harmer
0.882
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.411
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.563
270494AE1-108_GEN
Solar/Wind Helper
3.665
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.663
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.965
316049AB1-081 GEN
Solar/Wind Harmer
0.772
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.715
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
970223AG2-152 GEN
Solar/Wind Harmer
5.79
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.192
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.414
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.314
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.045
316197AC1-042 GEN
Solar/Wind Harmer
0.792
942671AE2-283 GEN
Solar/Wind Harmer
2.132
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.531
LAGNLTFEXP_LAGN->PJM
CLTF
3.212
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.896
TVALTFEXP_TVA->PJM
CLTF
1.599
CPLELTFEXP_CPLE->PJM
CLTF
5.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.616
NYPJM->LTFIMP_NY
CLTF
0.52
LGEELTFEXP_LGEE->PJM
CLTF
0.521
WECLTFEXP_WEC->PJM
CLTF
0.271
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.51
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.435
MECLTFEXP_MEC->PJM
CLTF
1.488
SIGELTFEXP_SIGE->PJM
CLTF
0.044

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:197.56 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1351.34
MW Contribution:5.7
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970933AG2-581 GEN
Solar/Wind Harmer
36.495
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
971967AH1-528 GEN
Solar/Wind Harmer
73.183
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:195.93 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:1095.86
MW Contribution:4.0
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.104
315657AE1-056 GEN
Solar/Wind Harmer
16.558
946301AF1-294 GEN
Solar/Wind Harmer
8.968
961791AG1-021 GEN
Solar/Wind Harmer
4.363
970683AG2-441 GEN
Solar/Wind Harmer
27.844
970681AG2-440 GEN
Solar/Wind Harmer
22.275
3144303KENBRDG
Solar/Wind Harmer
0.303
971443AH1-215 GEN
Solar/Wind Harmer
6.304
971967AH1-528 GEN
Solar/Wind Harmer
55.434
316239AB2-077_GEN
Solar/Wind Harmer
0.002
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.213
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.1
970301AG2-198 GEN
Solar/Wind Harmer
22.295
971741AH1-377 GEN
Solar/Wind Harmer
48.392
3147133PAMPLIN
Solar/Wind Harmer
0.48
3147133PAMPLIN
Solar/Wind Harmer
0.384
958211AF2-115 GEN
Solar/Wind Harmer
5.453
963191AG1-168 GEN
Solar/Wind Harmer
1.818
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.154
971775AH1-396 GEN
Solar/Wind Harmer
0.606
970933AG2-581 GEN
Solar/Wind Harmer
27.718
970099AG2-077 GEN
Solar/Wind Harmer
36.303
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.244
964791AG1-342 GEN
Solar/Wind Harmer
4.773
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.665
942751AE2-291 GEN
Solar/Wind Harmer
7.016
316222AC1-221 GEN
Solar/Wind Harmer
0.517
316181AB2-040 GEN
Solar/Wind Harmer
0.135
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.992
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.575
3145783HORNRTN
Solar/Wind Harmer
1.26
3145783HORNRTN
Solar/Wind Harmer
0.394
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.38
316263AC1-034 GEN
Solar/Wind Harmer
2.393
961601AG1-000A GEN
Solar/Wind Harmer
1.088
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.132
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.414
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.97
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
963171AG1-166 GEN
Solar/Wind Harmer
2.424
971563AH1-280 GEN
Solar/Wind Harmer
4.847
970685AG2-442 GEN
Solar/Wind Harmer
31.186
962491AG1-098 GEN
Solar/Wind Harmer
21.632
315693AD1-088 GEN
Solar/Wind Harmer
17.82
957481AF2-042 GEN
Solar/Wind Harmer
90.757
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.458
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.171
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
9.004
960081AF2-299 GEN
Solar/Wind Harmer
0.903
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.349
3146233WITAKRS
Solar/Wind Harmer
0.261
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.051
316359AB2-059 GEN
Solar/Wind Harmer
0.226
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.062
315722AD1-056 GEN
Solar/Wind Harmer
0.382
3145796HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.068
962571AG1-106 GEN
Solar/Wind Harmer
0.836
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.253
970223AG2-152 GEN
Solar/Wind Harmer
3.997
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.043
941801AE2-185 GEN
Solar/Wind Harmer
1.818
3145823KELFORD
Solar/Wind Harmer
0.056
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.602
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.073
970831AG2-522 GEN
Solar/Wind Harmer
7.443
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.191
970163AG2-111 GEN
Solar/Wind Harmer
1.136
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.368
315607AA1-063A GEN
Solar/Wind Harmer
0.159
3146043SEABORD
Solar/Wind Harmer
0.076
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.25
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.462
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.252
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.232
963181AG1-167 GEN
Solar/Wind Harmer
1.818
959311AF2-222 GEN
Solar/Wind Harmer
34.653
970257AG2-171 GEN
Solar/Wind Harmer
12.116
315785AD2-033 C
Solar/Wind Harmer
2.953
964241AG1-285 GEN
Solar/Wind Harmer
21.475
316478AD1-087 GEN
Solar/Wind Harmer
1.115
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.935
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.299
971683AH1-343 GEN
Solar/Wind Harmer
6.959
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.287
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.626
3146233WITAKRS
Solar/Wind Harmer
0.329
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.062
961601AG1-000A GEN
Solar/Wind Harmer
4.35
315724AD1-057 GEN
Solar/Wind Harmer
0.227
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.818
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:193.37 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:1081.51
MW Contribution:4.0
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.104
315657AE1-056 GEN
Solar/Wind Harmer
16.558
946301AF1-294 GEN
Solar/Wind Harmer
8.968
961791AG1-021 GEN
Solar/Wind Harmer
4.363
970683AG2-441 GEN
Solar/Wind Harmer
27.844
970681AG2-440 GEN
Solar/Wind Harmer
22.275
3144303KENBRDG
Solar/Wind Harmer
0.303
971443AH1-215 GEN
Solar/Wind Harmer
6.304
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.602
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.073
970831AG2-522 GEN
Solar/Wind Harmer
7.443
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.191
970163AG2-111 GEN
Solar/Wind Harmer
1.136
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.368
315607AA1-063A GEN
Solar/Wind Harmer
0.159
3146043SEABORD
Solar/Wind Harmer
0.076
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.25
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.462
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.252
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.213
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.1
970301AG2-198 GEN
Solar/Wind Harmer
22.295
971741AH1-377 GEN
Solar/Wind Harmer
48.392
3147133PAMPLIN
Solar/Wind Harmer
0.48
3147133PAMPLIN
Solar/Wind Harmer
0.384
958211AF2-115 GEN
Solar/Wind Harmer
5.453
963191AG1-168 GEN
Solar/Wind Harmer
1.818
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.154
971775AH1-396 GEN
Solar/Wind Harmer
0.606
970099AG2-077 GEN
Solar/Wind Harmer
36.303
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.244
964791AG1-342 GEN
Solar/Wind Harmer
4.773
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.665
942751AE2-291 GEN
Solar/Wind Harmer
7.016
316222AC1-221 GEN
Solar/Wind Harmer
0.517
316181AB2-040 GEN
Solar/Wind Harmer
0.135
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.992
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.575
3145783HORNRTN
Solar/Wind Harmer
1.26
3145783HORNRTN
Solar/Wind Harmer
0.394
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.38
316263AC1-034 GEN
Solar/Wind Harmer
2.393
961601AG1-000A GEN
Solar/Wind Harmer
1.088
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.132
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.414
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.97
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
963171AG1-166 GEN
Solar/Wind Harmer
2.424
971563AH1-280 GEN
Solar/Wind Harmer
4.847
970685AG2-442 GEN
Solar/Wind Harmer
31.186
962491AG1-098 GEN
Solar/Wind Harmer
21.632
315693AD1-088 GEN
Solar/Wind Harmer
17.82
957481AF2-042 GEN
Solar/Wind Harmer
90.757
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.458
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.171
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
9.004
960081AF2-299 GEN
Solar/Wind Harmer
0.903
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.349
3146233WITAKRS
Solar/Wind Harmer
0.261
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.051
316359AB2-059 GEN
Solar/Wind Harmer
0.226
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.062
315722AD1-056 GEN
Solar/Wind Harmer
0.382
3145796HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.068
962571AG1-106 GEN
Solar/Wind Harmer
0.836
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.253
970223AG2-152 GEN
Solar/Wind Harmer
3.997
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.043
941801AE2-185 GEN
Solar/Wind Harmer
1.818
3145823KELFORD
Solar/Wind Harmer
0.056
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.232
963181AG1-167 GEN
Solar/Wind Harmer
1.818
959311AF2-222 GEN
Solar/Wind Harmer
34.653
970257AG2-171 GEN
Solar/Wind Harmer
12.116
315785AD2-033 C
Solar/Wind Harmer
2.953
964241AG1-285 GEN
Solar/Wind Harmer
21.475
316478AD1-087 GEN
Solar/Wind Harmer
1.115
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.935
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.299
971683AH1-343 GEN
Solar/Wind Harmer
6.959
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.287
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.626
3146233WITAKRS
Solar/Wind Harmer
0.329
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.062
961601AG1-000A GEN
Solar/Wind Harmer
4.35
315724AD1-057 GEN
Solar/Wind Harmer
0.227
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.818
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:191.54 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1310.12
MW Contribution:5.7
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970099AG2-077 GEN
Solar/Wind Harmer
47.799
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:191.54 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1310.12
MW Contribution:5.7
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-3


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:182.88 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:930.03
MW Contribution:8.89
Bus #Bus NameTypeMW Contribution
270013AE1-250 PV
Solar/Wind Harmer
0.003
961601AG1-000A GEN
Solar/Wind Harmer
1.322
316263AC1-034 GEN
Solar/Wind Harmer
2.764
3145493TOT1
Solar/Wind Harmer
0.148
3145453TOT5
Solar/Wind Harmer
0.089
3145603CNETO
Solar/Wind Harmer
0.059
971341AH1-150 GEN
Solar/Wind Harmer
4.143
971343AH1-151 GEN
Solar/Wind Harmer
4.143
316222AC1-221 GEN
Solar/Wind Helper
8.797
3146843MT LREL
Solar/Wind Helper
0.574
3146843MT LREL
Solar/Wind Helper
0.574
316034AC1-036 C
Solar/Wind Helper
0.351
3147133PAMPLIN
Solar/Wind Helper
0.308
3147133PAMPLIN
Solar/Wind Helper
0.247
3146776BUCKING
Solar/Wind Helper
0.854
3146776BUCKING
Solar/Wind Helper
0.069
316036AC1-147 C
Solar/Wind Helper
0.204
3142956BIRDNECK
Solar/Wind Helper
0.089
316316AC1-027 C
Solar/Wind Helper
0.209
316185AD1-033 GEN
Solar/Wind Helper
0.62
316236AE1-162_GEN
Solar/Wind Helper
0.176
316240AF1-291 C
Solar/Wind Helper
0.176
3145506HICKORY
Solar/Wind Helper
0.519
3145506HICKORY
Solar/Wind Helper
0.311
3145506HICKORY
Solar/Wind Helper
0.078
316033AB2-134 GEN
Solar/Wind Helper
0.44
315697AD1-025 GEN
Solar/Wind Helper
1.464
316339AD2-160 GEN
Solar/Wind Helper
0.48
316018AA1-139 ULT2
Solar/Wind Helper
0.537
316017AA1-139 ULT1
Solar/Wind Helper
0.571
3143526WINTERP
Solar/Wind Helper
0.647
3137176SLIGO L2192
Solar/Wind Helper
0.49
3144356SAPONY
Solar/Wind Helper
0.22
3130086AYDLETT
Solar/Wind Helper
0.486
3142946ENON
Solar/Wind Helper
0.012
316075AC2-137 C
Solar/Wind Helper
0.178
316487AF1-042 GEN
Solar/Wind Helper
0.117
3146386ELIZ CT
Solar/Wind Helper
0.113
316077AC2-138 C
Solar/Wind Helper
0.106
971629AH1-314 GEN
50/50
15.388
970417AG2-272 GEN
50/50
2.023
970087AG2-069 GEN
Solar/Wind Harmer
13.785
970919AG2-571 GEN
Solar/Wind Harmer
6.126
970223AG2-152 GEN
Solar/Wind Harmer
8.891
270016AE1-250 BESS
Solar/Wind Harmer
0.003
270030AE2-140 GEN
Solar/Wind Harmer
11.004
270574AD1-017 GEN2
Solar/Wind Harmer
0
316359AB2-059 GEN
Solar/Wind Harmer
0.261
316049AB1-081 GEN
Solar/Wind Harmer
0.416
3142053HEARTS
Solar/Wind Harmer
0.128
3145543BTLEBRO
Solar/Wind Harmer
0.072
3145543BTLEBRO
Solar/Wind Harmer
0.058
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.283
3146233WITAKRS
Solar/Wind Harmer
0.227
972273AH1-721 GEN
Adder
31.464
959091AF2-200 GEN
Solar/Wind Harmer
4.143
274729ELWOOD EC;1P
Adder
4.672
274730ELWOOD EC;6P
Adder
4.672
274734ELWOOD EC;8P
Adder
4.672
274736ELWOOD EC;9P
Adder
4.672
274676JOLIET 29;8U
Adder
8.408
315687AD1-152 GEN
Solar/Wind Helper
3.789
316003AC1-222 GEN
Solar/Wind Helper
2.887
316237AB2-079_GEN
Solar/Wind Helper
0.489
3146926FARMVIL
Solar/Wind Helper
0.16
316322AB2-045
Solar/Wind Helper
0.238
3146776BUCKING
Solar/Wind Helper
0.085
316129AC1-054 GEN
Solar/Wind Helper
0.854
316294AC1-161 GEN
Solar/Wind Helper
2.674
3147123OTTER R
Solar/Wind Helper
0.085
316336AC2-165 C
Solar/Wind Helper
0.744
316375AC2-012 GEN
Solar/Wind Helper
0.351
3145336SMITFLD
Solar/Wind Helper
0.525
316381AD1-082 GEN
Solar/Wind Helper
0.67
3143226MDLTHAN
Solar/Wind Helper
0.128
316458AB2-190 GEN2
Solar/Wind Helper
0.728
316159AE1-175 C
Solar/Wind Helper
0.191
316388AE2-253 GEN
Solar/Wind Helper
0.48
3143526WINTERP
Solar/Wind Helper
0.647
316072AD1-144
Solar/Wind Helper
0.141
3146456SLIGO L269
Solar/Wind Helper
0.123
3142543TWELFTH
Solar/Wind Helper
0.012
316246AF1-032 C
Solar/Wind Helper
0.14
3142433PROV 92
Solar/Wind Helper
0.482
3141766HARMONY
Solar/Wind Helper
0.024
3138133OCRAN
Solar/Wind Helper
0.071
964211AG1-282 GEN
Solar/Wind Helper
0.152
3141726DUNNSVL
Solar/Wind Helper
0.452
3142416OLDCHRC
Solar/Wind Helper
0.293
3142416OLDCHRC
Solar/Wind Helper
0.112
970085AG2-068 GEN
Solar/Wind Harmer
9.19
970581AG2-369 GEN
Solar/Wind Harmer
7.903
270069AE2-166 C O1
Solar/Wind Harmer
0.003
971981AH1-535 GEN
Solar/Wind Harmer
2.359
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
316420AA1-050 GEN
Solar/Wind Harmer
0.002
316319Z2-044 C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
4.143
274731ELWOOD EC;2P
Adder
4.672
274733ELWOOD EC;3P
Adder
4.672
274735ELWOOD EC;4P
Adder
4.672
274728ELWOOD EC;5P
Adder
4.672
274675JOLIET 29;7U
Adder
8.719
274675JOLIET 29;7U
Adder
8.408
972211AH1-690 GEN
Adder
28.667
3147173SINAI
Solar/Wind Helper
0.727
3147243WELCO
Solar/Wind Helper
0.454
316118AC1-105 GEN
Solar/Wind Helper
2.53
316123AC1-075 GEN
Solar/Wind Helper
2.71
316239AB2-077_GEN
Solar/Wind Helper
0.489
316238AB2-078_GEN
Solar/Wind Helper
0.489
3144303KENBRDG
Solar/Wind Helper
0.269
3143316POE
Solar/Wind Helper
0.561
316369SG1_INVT
Solar/Wind Helper
0.616
316132AB2-190 GEN1
Solar/Wind Helper
0.728
957831AF2-077 GEN
Solar/Wind Helper
0.168
316233AE1-074 FULL
Solar/Wind Helper
0.19
316349AD2-085 GEN
Solar/Wind Helper
0.563
316315AB2-025 C
Solar/Wind Helper
0.187
319010AE1-072 C
Solar/Wind Helper
1.397
316305AF2-043 C
Solar/Wind Helper
0.164
957601AF2-054 GEN
Solar/Wind Helper
0.161
3141873WAN 176
Solar/Wind Helper
0.024
315662AE1-191 GEN
Solar/Wind Helper
0.644
315666AE1-190 GEN
Solar/Wind Helper
0.161
3143873LANEXA
Solar/Wind Helper
0.072
316059AD1-063 C
Solar/Wind Helper
0.12
3141913WHIT STONE
Solar/Wind Helper
0.119
3138133OCRAN
Solar/Wind Helper
0.036
3141783LANCAST
Solar/Wind Helper
0.071
3141783LANCAST
Solar/Wind Helper
0.047
316312AB1-027
Solar/Wind Helper
0.214
313526AB2-022
Solar/Wind Helper
0.171
3141813NORNECK
Solar/Wind Helper
0.112
970917AG2-570 GEN
Solar/Wind Harmer
15.316
270018AE2-047 C O1
Solar/Wind Harmer
0.003
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
0.53
961601AG1-000A GEN
Solar/Wind Harmer
5.289
971623AH1-311 GEN
Solar/Wind Harmer
0.145
3145543BTLEBRO
Solar/Wind Harmer
0.072
3145543BTLEBRO
Solar/Wind Harmer
0.072
971367AH1-164 GEN
Solar/Wind Harmer
1.205
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
3138543CONSLDL
Solar/Wind Harmer
0.039
3146233WITAKRS
Solar/Wind Harmer
0.287
3146233WITAKRS
Solar/Wind Harmer
0.039
957471AF2-041 GEN
Solar/Wind Harmer
6.215
959081AF2-199 GEN
Solar/Wind Harmer
2.072
971067AG2-660 GEN
Solar/Wind Harmer
0.691
274732ELWOOD EC;7P
Adder
4.672
274676JOLIET 29;8U
Adder
8.719
316283AC2-100 C
Solar/Wind Helper
8.307
316248AF1-058 C
Solar/Wind Helper
0.977
316478AD1-087 GEN
Solar/Wind Helper
2.495
316486AD2-202 GEN
Solar/Wind Helper
0.731
316131AB2-060 GEN
Solar/Wind Helper
2.179
315785AD2-033 C
Solar/Wind Helper
3.963
3147133PAMPLIN
Solar/Wind Helper
0.969
942461AE2-259 GEN
Solar/Wind Helper
1.948
3146926FARMVIL
Solar/Wind Helper
0.16
3146776BUCKING
Solar/Wind Helper
0.077
3147043LAWRENC
Solar/Wind Helper
0.109
315773AC2-141 GEN
Solar/Wind Helper
3.147
316313AB2-026
Solar/Wind Helper
0.207
316258AE1-075 C
Solar/Wind Helper
0.186
316405AF2-144 C
Solar/Wind Helper
0.155
315839AE2-212 C
Solar/Wind Helper
0.182
3144873MCLAUGH
Solar/Wind Helper
0.003
3144536CHRHLND
Solar/Wind Helper
0.02
3145336SMITFLD
Solar/Wind Helper
0.053
316382AG1-145 C
Solar/Wind Helper
0.17
3146456SLIGO L269
Solar/Wind Helper
0.123
3142946ENON
Solar/Wind Helper
0.04
316156AD2-030 GEN
Solar/Wind Helper
0.181
316280AD1-041 GEN
Solar/Wind Helper
0.403
316484AD2-074 GEN
Solar/Wind Helper
0.224
316404AE1-155 C
Solar/Wind Helper
0.968
316320Y1-086
Solar/Wind Helper
0.05
944201AF1-088_MTX
Adder
34.575
900033ID_568986
External Queue
3.919766426086426
LAGNLTFEXP_LAGN->PJM
CLTF
10.425
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.051
TVALTFEXP_TVA->PJM
CLTF
5.193
CPLELTFEXP_CPLE->PJM
CLTF
13.504
CBM West 2LTFEXP_CBM-W2->PJM
CBM
57.694
NYPJM->LTFIMP_NY
CLTF
0.599
LGEELTFEXP_LGEE->PJM
CLTF
2.145
WECLTFEXP_WEC->PJM
CLTF
1.147
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.096
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.755
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.101
MECLTFEXP_MEC->PJM
CLTF
5.768
SIGELTFEXP_SIGE->PJM
CLTF
0.174

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-2


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:178.67 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:908.59
MW Contribution:8.89
Bus #Bus NameTypeMW Contribution
970085AG2-068 GEN
Solar/Wind Harmer
9.19
970581AG2-369 GEN
Solar/Wind Harmer
7.903
270069AE2-166 C O1
Solar/Wind Harmer
0.003
971981AH1-535 GEN
Solar/Wind Harmer
2.359
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
316420AA1-050 GEN
Solar/Wind Harmer
0.002
316319Z2-044 C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
4.143
274731ELWOOD EC;2P
Adder
4.672
274733ELWOOD EC;3P
Adder
4.672
274735ELWOOD EC;4P
Adder
4.672
274728ELWOOD EC;5P
Adder
4.672
274675JOLIET 29;7U
Adder
8.719
274675JOLIET 29;7U
Adder
8.408
972211AH1-690 GEN
Adder
28.667
3147173SINAI
Solar/Wind Helper
0.727
3147243WELCO
Solar/Wind Helper
0.454
316118AC1-105 GEN
Solar/Wind Helper
2.53
316123AC1-075 GEN
Solar/Wind Helper
2.71
316239AB2-077_GEN
Solar/Wind Helper
0.489
316238AB2-078_GEN
Solar/Wind Helper
0.489
3144303KENBRDG
Solar/Wind Helper
0.269
3143316POE
Solar/Wind Helper
0.561
316369SG1_INVT
Solar/Wind Helper
0.616
316132AB2-190 GEN1
Solar/Wind Helper
0.728
957831AF2-077 GEN
Solar/Wind Helper
0.168
316233AE1-074 FULL
Solar/Wind Helper
0.19
316349AD2-085 GEN
Solar/Wind Helper
0.563
316315AB2-025 C
Solar/Wind Helper
0.187
319010AE1-072 C
Solar/Wind Helper
1.397
316305AF2-043 C
Solar/Wind Helper
0.164
957601AF2-054 GEN
Solar/Wind Helper
0.161
3141873WAN 176
Solar/Wind Helper
0.024
315662AE1-191 GEN
Solar/Wind Helper
0.644
315666AE1-190 GEN
Solar/Wind Helper
0.161
3143873LANEXA
Solar/Wind Helper
0.072
316059AD1-063 C
Solar/Wind Helper
0.12
3141913WHIT STONE
Solar/Wind Helper
0.119
3138133OCRAN
Solar/Wind Helper
0.036
3141783LANCAST
Solar/Wind Helper
0.071
3141783LANCAST
Solar/Wind Helper
0.047
316312AB1-027
Solar/Wind Helper
0.214
313526AB2-022
Solar/Wind Helper
0.171
3141813NORNECK
Solar/Wind Helper
0.112
270013AE1-250 PV
Solar/Wind Harmer
0.003
961601AG1-000A GEN
Solar/Wind Harmer
1.322
316263AC1-034 GEN
Solar/Wind Harmer
2.764
3145493TOT1
Solar/Wind Harmer
0.148
3145453TOT5
Solar/Wind Harmer
0.089
3145603CNETO
Solar/Wind Harmer
0.059
971341AH1-150 GEN
Solar/Wind Harmer
4.143
971343AH1-151 GEN
Solar/Wind Harmer
4.143
316222AC1-221 GEN
Solar/Wind Helper
8.797
3146843MT LREL
Solar/Wind Helper
0.574
3146843MT LREL
Solar/Wind Helper
0.574
316034AC1-036 C
Solar/Wind Helper
0.351
3147133PAMPLIN
Solar/Wind Helper
0.308
3147133PAMPLIN
Solar/Wind Helper
0.247
3146776BUCKING
Solar/Wind Helper
0.854
3146776BUCKING
Solar/Wind Helper
0.069
316036AC1-147 C
Solar/Wind Helper
0.204
3142956BIRDNECK
Solar/Wind Helper
0.089
316316AC1-027 C
Solar/Wind Helper
0.209
316185AD1-033 GEN
Solar/Wind Helper
0.62
316236AE1-162_GEN
Solar/Wind Helper
0.176
316240AF1-291 C
Solar/Wind Helper
0.176
3145506HICKORY
Solar/Wind Helper
0.519
3145506HICKORY
Solar/Wind Helper
0.311
3145506HICKORY
Solar/Wind Helper
0.078
316033AB2-134 GEN
Solar/Wind Helper
0.44
315697AD1-025 GEN
Solar/Wind Helper
1.464
316339AD2-160 GEN
Solar/Wind Helper
0.48
316018AA1-139 ULT2
Solar/Wind Helper
0.537
316017AA1-139 ULT1
Solar/Wind Helper
0.571
3143526WINTERP
Solar/Wind Helper
0.647
3137176SLIGO L2192
Solar/Wind Helper
0.49
3144356SAPONY
Solar/Wind Helper
0.22
3130086AYDLETT
Solar/Wind Helper
0.486
3142946ENON
Solar/Wind Helper
0.012
316075AC2-137 C
Solar/Wind Helper
0.178
316487AF1-042 GEN
Solar/Wind Helper
0.117
3146386ELIZ CT
Solar/Wind Helper
0.113
316077AC2-138 C
Solar/Wind Helper
0.106
971629AH1-314 GEN
50/50
15.388
970417AG2-272 GEN
50/50
2.023
970087AG2-069 GEN
Solar/Wind Harmer
13.785
970223AG2-152 GEN
Solar/Wind Harmer
8.891
270016AE1-250 BESS
Solar/Wind Harmer
0.003
270030AE2-140 GEN
Solar/Wind Harmer
11.004
270574AD1-017 GEN2
Solar/Wind Harmer
0
316359AB2-059 GEN
Solar/Wind Harmer
0.261
316049AB1-081 GEN
Solar/Wind Harmer
0.416
3142053HEARTS
Solar/Wind Harmer
0.128
3145543BTLEBRO
Solar/Wind Harmer
0.072
3145543BTLEBRO
Solar/Wind Harmer
0.058
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.283
3146233WITAKRS
Solar/Wind Harmer
0.227
972273AH1-721 GEN
Adder
31.464
959091AF2-200 GEN
Solar/Wind Harmer
4.143
274729ELWOOD EC;1P
Adder
4.672
274730ELWOOD EC;6P
Adder
4.672
274734ELWOOD EC;8P
Adder
4.672
274736ELWOOD EC;9P
Adder
4.672
274676JOLIET 29;8U
Adder
8.408
315687AD1-152 GEN
Solar/Wind Helper
3.789
316003AC1-222 GEN
Solar/Wind Helper
2.887
316237AB2-079_GEN
Solar/Wind Helper
0.489
3146926FARMVIL
Solar/Wind Helper
0.16
316322AB2-045
Solar/Wind Helper
0.238
3146776BUCKING
Solar/Wind Helper
0.085
316129AC1-054 GEN
Solar/Wind Helper
0.854
316294AC1-161 GEN
Solar/Wind Helper
2.674
3147123OTTER R
Solar/Wind Helper
0.085
316336AC2-165 C
Solar/Wind Helper
0.744
316375AC2-012 GEN
Solar/Wind Helper
0.351
3145336SMITFLD
Solar/Wind Helper
0.525
316381AD1-082 GEN
Solar/Wind Helper
0.67
3143226MDLTHAN
Solar/Wind Helper
0.128
316458AB2-190 GEN2
Solar/Wind Helper
0.728
316159AE1-175 C
Solar/Wind Helper
0.191
316388AE2-253 GEN
Solar/Wind Helper
0.48
3143526WINTERP
Solar/Wind Helper
0.647
316072AD1-144
Solar/Wind Helper
0.141
3146456SLIGO L269
Solar/Wind Helper
0.123
3142543TWELFTH
Solar/Wind Helper
0.012
316246AF1-032 C
Solar/Wind Helper
0.14
3142433PROV 92
Solar/Wind Helper
0.482
3141766HARMONY
Solar/Wind Helper
0.024
3138133OCRAN
Solar/Wind Helper
0.071
964211AG1-282 GEN
Solar/Wind Helper
0.152
3141726DUNNSVL
Solar/Wind Helper
0.452
3142416OLDCHRC
Solar/Wind Helper
0.293
3142416OLDCHRC
Solar/Wind Helper
0.112
270018AE2-047 C O1
Solar/Wind Harmer
0.003
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
0.53
961601AG1-000A GEN
Solar/Wind Harmer
5.289
971623AH1-311 GEN
Solar/Wind Harmer
0.145
3145543BTLEBRO
Solar/Wind Harmer
0.072
3145543BTLEBRO
Solar/Wind Harmer
0.072
971367AH1-164 GEN
Solar/Wind Harmer
1.205
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
3138543CONSLDL
Solar/Wind Harmer
0.039
3146233WITAKRS
Solar/Wind Harmer
0.287
3146233WITAKRS
Solar/Wind Harmer
0.039
957471AF2-041 GEN
Solar/Wind Harmer
6.215
959081AF2-199 GEN
Solar/Wind Harmer
2.072
971067AG2-660 GEN
Solar/Wind Harmer
0.691
274732ELWOOD EC;7P
Adder
4.672
274676JOLIET 29;8U
Adder
8.719
316283AC2-100 C
Solar/Wind Helper
8.307
316248AF1-058 C
Solar/Wind Helper
0.977
316478AD1-087 GEN
Solar/Wind Helper
2.495
316486AD2-202 GEN
Solar/Wind Helper
0.731
316131AB2-060 GEN
Solar/Wind Helper
2.179
315785AD2-033 C
Solar/Wind Helper
3.963
3147133PAMPLIN
Solar/Wind Helper
0.969
942461AE2-259 GEN
Solar/Wind Helper
1.948
3146926FARMVIL
Solar/Wind Helper
0.16
3146776BUCKING
Solar/Wind Helper
0.077
3147043LAWRENC
Solar/Wind Helper
0.109
315773AC2-141 GEN
Solar/Wind Helper
3.147
316313AB2-026
Solar/Wind Helper
0.207
316258AE1-075 C
Solar/Wind Helper
0.186
316405AF2-144 C
Solar/Wind Helper
0.155
315839AE2-212 C
Solar/Wind Helper
0.182
3144873MCLAUGH
Solar/Wind Helper
0.003
3144536CHRHLND
Solar/Wind Helper
0.02
3145336SMITFLD
Solar/Wind Helper
0.053
316382AG1-145 C
Solar/Wind Helper
0.17
3146456SLIGO L269
Solar/Wind Helper
0.123
3142946ENON
Solar/Wind Helper
0.04
316156AD2-030 GEN
Solar/Wind Helper
0.181
316280AD1-041 GEN
Solar/Wind Helper
0.403
316484AD2-074 GEN
Solar/Wind Helper
0.224
316404AE1-155 C
Solar/Wind Helper
0.968
316320Y1-086
Solar/Wind Helper
0.05
944201AF1-088_MTX
Adder
34.575
900033ID_568986
External Queue
3.919766426086426
LAGNLTFEXP_LAGN->PJM
CLTF
10.425
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.051
TVALTFEXP_TVA->PJM
CLTF
5.193
CPLELTFEXP_CPLE->PJM
CLTF
13.504
CBM West 2LTFEXP_CBM-W2->PJM
CBM
57.694
NYPJM->LTFIMP_NY
CLTF
0.599
LGEELTFEXP_LGEE->PJM
CLTF
2.145
WECLTFEXP_WEC->PJM
CLTF
1.147
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.096
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.755
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.101
MECLTFEXP_MEC->PJM
CLTF
5.768
SIGELTFEXP_SIGE->PJM
CLTF
0.174

Details for 6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line l/o DVP_P4-2: 509T570_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.79 %
Rating:997.0 MVA
Rating Type:C
MVA to Mitigate:1094.57
MW Contribution:13.39
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
0.686
971629AH1-314 GEN
50/50
13.518
3151561HALLBR1
50/50
0.374
24728405LEESVG
50/50
0.137
316003AC1-222 GEN
Solar/Wind Harmer
3.859
970401AG2-262 GEN
Solar/Wind Harmer
1.707
3147123OTTER R
Solar/Wind Harmer
-0.01
970087AG2-069 GEN
Solar/Wind Harmer
14.944
970919AG2-571 GEN
Solar/Wind Harmer
5.044
970223AG2-152 GEN
Solar/Wind Harmer
13.39
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.475
270016AE1-250 BESS
Solar/Wind Harmer
2.232
270574AD1-017 GEN2
Solar/Wind Harmer
4.514
270030AE2-140 GEN
Solar/Wind Harmer
14.796
3147173SINAI
Solar/Wind Harmer
-0.042
3147243WELCO
Solar/Wind Harmer
-0.026
970865AG2-541 GEN
Solar/Wind Harmer
14.161
316118AC1-105 GEN
Solar/Wind Harmer
2.358
316123AC1-075 GEN
Solar/Wind Harmer
3.239
970165AG2-112 GEN
Solar/Wind Harmer
2.852
970163AG2-111 GEN
Solar/Wind Harmer
2.72
270455AD2-022 GEN
Solar/Wind Harmer
3.538
270457AD2-023 GEN
Solar/Wind Harmer
1.794
970085AG2-068 GEN
Solar/Wind Harmer
9.963
970581AG2-369 GEN
Solar/Wind Harmer
8.568
270069AE2-166 C O1
Solar/Wind Harmer
1.81
971981AH1-535 GEN
Solar/Wind Harmer
4.63
3143316POE
Solar/Wind Helper
0.631
316369SG1_INVT
Solar/Wind Helper
0.698
316132AB2-190 GEN1
Solar/Wind Helper
0.823
957831AF2-077 GEN
Solar/Wind Helper
0.191
319010AE1-072 C
Solar/Wind Helper
1.613
316305AF2-043 C
Solar/Wind Helper
0.188
316349AD2-085 GEN
Solar/Wind Helper
0.634
316233AE1-074 FULL
Solar/Wind Helper
0.21
957601AF2-054 GEN
Solar/Wind Helper
0.182
3141873WAN 176
Solar/Wind Helper
0.027
315662AE1-191 GEN
Solar/Wind Helper
0.728
315666AE1-190 GEN
Solar/Wind Helper
0.182
3143873LANEXA
Solar/Wind Helper
0.081
316059AD1-063 C
Solar/Wind Helper
0.136
3141913WHIT STONE
Solar/Wind Helper
0.134
3138133OCRAN
Solar/Wind Helper
0.04
3141783LANCAST
Solar/Wind Helper
0.08
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.199
316315AB2-025 C
Solar/Wind Helper
0.198
3146486SUNBURY
Solar/Wind Helper
0.128
3146486SUNBURY
Solar/Wind Helper
0.128
3141813NORNECK
Solar/Wind Helper
0.127
316312AB1-027
Solar/Wind Helper
0.24
316321Z2-027
Solar/Wind Helper
0.192
3145176PASQUOTANK
Solar/Wind Helper
0.078
316223AC1-118
Solar/Wind Helper
0.183
24728405LEESVG
50/50
0.137
316248AF1-058 C
Solar/Wind Harmer
1.271
960061AF2-297 GEN
Solar/Wind Harmer
21.085
971683AH1-343 GEN
Solar/Wind Harmer
16.057
316283AC2-100 C
Solar/Wind Harmer
2.823
970917AG2-570 GEN
Solar/Wind Harmer
39.848
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.475
270197AD1-017 GEN1
Solar/Wind Harmer
1.356
270018AE2-047 C O1
Solar/Wind Harmer
1.022
943811AF1-049 GEN
Solar/Wind Harmer
2.877
270336AE1-100 GEN
Solar/Wind Harmer
1.171
971367AH1-164 GEN
Solar/Wind Harmer
1.921
961601AG1-000A GEN
Solar/Wind Harmer
2.799
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316478AD1-087 GEN
Solar/Wind Helper
3.077
316486AD2-202 GEN
Solar/Wind Helper
0.901
3146926FARMVIL
Solar/Wind Helper
0.145
3146776BUCKING
Solar/Wind Helper
0.07
315773AC2-141 GEN
Solar/Wind Helper
3.608
942461AE2-259 GEN
Solar/Wind Helper
1.129
3144873MCLAUGH
Solar/Wind Helper
0.004
3144536CHRHLND
Solar/Wind Helper
0.023
315839AE2-212 C
Solar/Wind Helper
0.204
3145336SMITFLD
Solar/Wind Helper
0.06
316382AG1-145 C
Solar/Wind Helper
0.193
3146456SLIGO L269
Solar/Wind Helper
0.142
316313AB2-026
Solar/Wind Helper
0.212
316258AE1-075 C
Solar/Wind Helper
0.191
316405AF2-144 C
Solar/Wind Helper
0.159
316156AD2-030 GEN
Solar/Wind Helper
0.205
316280AD1-041 GEN
Solar/Wind Helper
0.455
3142946ENON
Solar/Wind Helper
0.045
316484AD2-074 GEN
Solar/Wind Helper
0.253
316320Y1-086
Solar/Wind Helper
0.058
316404AE1-155 C
Solar/Wind Helper
1.094
316473AC1-191 GEN
Solar/Wind Helper
0.742
3141906WESTMOR
Solar/Wind Helper
0.048
316435W1029_GEN3
Solar/Wind Helper
0.482
3146516WINFALL
Solar/Wind Helper
0.117
316222AC1-221 GEN
Solar/Wind Harmer
3.103
942751AE2-291 GEN
Solar/Wind Harmer
17.181
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
964791AG1-342 GEN
Solar/Wind Harmer
5.586
962561AG1-105 GEN
Solar/Wind Harmer
12.803
316217AC1-145 GEN
Solar/Wind Harmer
2.369
316197AC1-042 GEN
Solar/Wind Harmer
1.796
942671AE2-283 GEN
Solar/Wind Harmer
4.836
270013AE1-250 PV
Solar/Wind Harmer
2.232
961601AG1-000A GEN
Solar/Wind Harmer
2.764
316263AC1-034 GEN
Solar/Wind Harmer
3.276
3146776BUCKING
Solar/Wind Helper
0.776
3146776BUCKING
Solar/Wind Helper
0.063
316036AC1-147 C
Solar/Wind Helper
0.234
3142956BIRDNECK
Solar/Wind Helper
0.103
316316AC1-027 C
Solar/Wind Helper
0.24
316185AD1-033 GEN
Solar/Wind Helper
0.713
316236AE1-162_GEN
Solar/Wind Helper
0.201
3145506HICKORY
Solar/Wind Helper
0.597
3145506HICKORY
Solar/Wind Helper
0.358
3145506HICKORY
Solar/Wind Helper
0.089
316240AF1-291 C
Solar/Wind Helper
0.197
316339AD2-160 GEN
Solar/Wind Helper
0.553
316033AB2-134 GEN
Solar/Wind Helper
0.499
315697AD1-025 GEN
Solar/Wind Helper
1.658
316018AA1-139 ULT2
Solar/Wind Helper
0.62
316017AA1-139 ULT1
Solar/Wind Helper
0.658
3137176SLIGO L2192
Solar/Wind Helper
0.566
3130086AYDLETT
Solar/Wind Helper
0.562
3143526WINTERP
Solar/Wind Helper
0.715
3142946ENON
Solar/Wind Helper
0.014
316075AC2-137 C
Solar/Wind Helper
0.2
316487AF1-042 GEN
Solar/Wind Helper
0.132
3146386ELIZ CT
Solar/Wind Helper
0.131
3144356SAPONY
Solar/Wind Helper
0.233
316077AC2-138 C
Solar/Wind Helper
0.12
966871AG1-558 GEN
Solar/Wind Helper
0.164
316431W1029_GEN1
Solar/Wind Helper
0.482
316433W1029_GEN2
Solar/Wind Helper
0.482
3146516WINFALL
Solar/Wind Helper
0.117
3146516WINFALL
Solar/Wind Helper
0.117
3146516WINFALL
Solar/Wind Helper
0.117
316468AD1-105 GEN
Solar/Wind Helper
0.565
270173AC1-122 GEN
Solar/Wind Harmer
1.042
316359AB2-059 GEN
Solar/Wind Harmer
0.942
316049AB1-081 GEN
Solar/Wind Harmer
0.754
3142053HEARTS
Solar/Wind Harmer
0.082
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
315687AD1-152 GEN
Solar/Wind Helper
4.938
3146926FARMVIL
Solar/Wind Helper
0.145
316322AB2-045
Solar/Wind Helper
0.216
3146776BUCKING
Solar/Wind Helper
0.078
316294AC1-161 GEN
Solar/Wind Helper
3.066
316375AC2-012 GEN
Solar/Wind Helper
0.403
3145336SMITFLD
Solar/Wind Helper
0.6
316381AD1-082 GEN
Solar/Wind Helper
0.754
316388AE2-253 GEN
Solar/Wind Helper
0.553
316458AB2-190 GEN2
Solar/Wind Helper
0.823
316159AE1-175 C
Solar/Wind Helper
0.217
3146456SLIGO L269
Solar/Wind Helper
0.142
316072AD1-144
Solar/Wind Helper
0.162
3143226MDLTHAN
Solar/Wind Helper
0.14
316246AF1-032 C
Solar/Wind Helper
0.16
316336AC2-165 C
Solar/Wind Helper
0.748
3143526WINTERP
Solar/Wind Helper
0.715
3142543TWELFTH
Solar/Wind Helper
0.013
3142433PROV 92
Solar/Wind Helper
0.543
3141766HARMONY
Solar/Wind Helper
0.027
3138133OCRAN
Solar/Wind Helper
0.08
964211AG1-282 GEN
Solar/Wind Helper
0.172
3141726DUNNSVL
Solar/Wind Helper
0.511
3142416OLDCHRC
Solar/Wind Helper
0.328
3142416OLDCHRC
Solar/Wind Helper
0.126
316337AD2-073 GEN
Solar/Wind Helper
0.187
3146516WINFALL
Solar/Wind Helper
0.378
3146516WINFALL
Solar/Wind Helper
0.117
LAGNLTFEXP_LAGN->PJM
CLTF
9.252
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.368
TVALTFEXP_TVA->PJM
CLTF
4.632
CPLELTFEXP_CPLE->PJM
CLTF
11.178
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.871
NYPJM->LTFIMP_NY
CLTF
0.739
LGEELTFEXP_LGEE->PJM
CLTF
1.997
WECLTFEXP_WEC->PJM
CLTF
1.057
CBM West 1LTFEXP_CBM-W1->PJM
CBM
38.424
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.227
MECLTFEXP_MEC->PJM
CLTF
5.265
SIGELTFEXP_SIGE->PJM
CLTF
0.161

Details for 6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.53 %
Rating:814.98 MVA
Rating Type:B
MVA to Mitigate:843.75
MW Contribution:9.46
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
0.688
24684405SMG2
50/50
0.859
24684505SMG3
50/50
0.531
24684305SMG1
50/50
0.311
316222AC1-221 GEN
Solar/Wind Harmer
1.137
942751AE2-291 GEN
Solar/Wind Harmer
13.103
3146843MT LREL
Solar/Wind Harmer
0.235
3146843MT LREL
Solar/Wind Harmer
0.235
964791AG1-342 GEN
Solar/Wind Harmer
4.488
962561AG1-105 GEN
Solar/Wind Harmer
9.772
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.259
270013AE1-250 PV
Solar/Wind Harmer
0.004
961601AG1-000A GEN
Solar/Wind Harmer
1.13
316263AC1-034 GEN
Solar/Wind Harmer
2.401
3146776BUCKING
Solar/Wind Helper
0.769
3146776BUCKING
Solar/Wind Helper
0.062
316036AC1-147 C
Solar/Wind Helper
0.231
316316AC1-027 C
Solar/Wind Helper
0.237
3142956BIRDNECK
Solar/Wind Helper
0.101
316185AD1-033 GEN
Solar/Wind Helper
0.703
316236AE1-162_GEN
Solar/Wind Helper
0.199
3145506HICKORY
Solar/Wind Helper
0.589
3145506HICKORY
Solar/Wind Helper
0.353
3145506HICKORY
Solar/Wind Helper
0.088
316240AF1-291 C
Solar/Wind Helper
0.194
316339AD2-160 GEN
Solar/Wind Helper
0.545
316033AB2-134 GEN
Solar/Wind Helper
0.492
315697AD1-025 GEN
Solar/Wind Helper
1.636
316018AA1-139 ULT2
Solar/Wind Helper
0.611
316017AA1-139 ULT1
Solar/Wind Helper
0.649
3137176SLIGO L2192
Solar/Wind Helper
0.558
3130086AYDLETT
Solar/Wind Helper
0.554
3143526WINTERP
Solar/Wind Helper
0.705
3142946ENON
Solar/Wind Helper
0.013
316075AC2-137 C
Solar/Wind Helper
0.197
316487AF1-042 GEN
Solar/Wind Helper
0.13
3146386ELIZ CT
Solar/Wind Helper
0.129
3144356SAPONY
Solar/Wind Helper
0.229
316077AC2-138 C
Solar/Wind Helper
0.118
966871AG1-558 GEN
Solar/Wind Helper
0.161
316431W1029_GEN1
Solar/Wind Helper
0.474
316433W1029_GEN2
Solar/Wind Helper
0.474
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
316468AD1-105 GEN
Solar/Wind Helper
0.556
971629AH1-314 GEN
50/50
13.606
3151561HALLBR1
50/50
0.377
24728405LEESVG
50/50
0.138
970417AG2-272 GEN
50/50
1.905
24684705SMG5
50/50
0.331
970481AG2-311 GEN
50/50
4.609
316003AC1-222 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.371
3147123OTTER R
Solar/Wind Harmer
0.091
970087AG2-069 GEN
Solar/Wind Harmer
11.429
970919AG2-571 GEN
Solar/Wind Harmer
5.079
970223AG2-152 GEN
Solar/Wind Harmer
9.459
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.098
941801AE2-185 GEN
Solar/Wind Harmer
4.19
270016AE1-250 BESS
Solar/Wind Harmer
0.004
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270030AE2-140 GEN
Solar/Wind Harmer
10.43
270173AC1-122 GEN
Solar/Wind Harmer
0.218
316359AB2-059 GEN
Solar/Wind Harmer
0.227
316049AB1-081 GEN
Solar/Wind Harmer
0.362
3142053HEARTS
Solar/Wind Harmer
0.111
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
315687AD1-152 GEN
Solar/Wind Helper
4.927
3146926FARMVIL
Solar/Wind Helper
0.143
316322AB2-045
Solar/Wind Helper
0.214
3146776BUCKING
Solar/Wind Helper
0.077
316294AC1-161 GEN
Solar/Wind Helper
3.03
316375AC2-012 GEN
Solar/Wind Helper
0.398
3145336SMITFLD
Solar/Wind Helper
0.592
316381AD1-082 GEN
Solar/Wind Helper
0.744
316388AE2-253 GEN
Solar/Wind Helper
0.545
316458AB2-190 GEN2
Solar/Wind Helper
0.811
316159AE1-175 C
Solar/Wind Helper
0.214
3146456SLIGO L269
Solar/Wind Helper
0.14
316072AD1-144
Solar/Wind Helper
0.16
3143226MDLTHAN
Solar/Wind Helper
0.138
316246AF1-032 C
Solar/Wind Helper
0.158
316336AC2-165 C
Solar/Wind Helper
0.738
3143526WINTERP
Solar/Wind Helper
0.705
3147173SINAI
Solar/Wind Harmer
0.376
3147243WELCO
Solar/Wind Harmer
0.235
970865AG2-541 GEN
Solar/Wind Harmer
10.789
3142543TWELFTH
Solar/Wind Helper
0.013
3142433PROV 92
Solar/Wind Helper
0.535
3141766HARMONY
Solar/Wind Helper
0.027
3138133OCRAN
Solar/Wind Helper
0.079
964211AG1-282 GEN
Solar/Wind Helper
0.169
3141726DUNNSVL
Solar/Wind Helper
0.503
3142416OLDCHRC
Solar/Wind Helper
0.323
3142416OLDCHRC
Solar/Wind Helper
0.124
316337AD2-073 GEN
Solar/Wind Helper
0.184
3146516WINFALL
Solar/Wind Helper
0.371
3146516WINFALL
Solar/Wind Helper
0.115
24728405LEESVG
50/50
0.138
24684605SMG4
50/50
0.864
24288905REUSENS
50/50
0.013
316248AF1-058 C
Solar/Wind Harmer
0.003
960061AF2-297 GEN
Solar/Wind Harmer
16.056
971683AH1-343 GEN
Solar/Wind Harmer
12.232
316283AC2-100 C
Solar/Wind Harmer
0.524
970917AG2-570 GEN
Solar/Wind Harmer
12.699
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.19
270197AD1-017 GEN1
Solar/Wind Harmer
0.768
270018AE2-047 C O1
Solar/Wind Harmer
0.002
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.003
971367AH1-164 GEN
Solar/Wind Harmer
1.359
961601AG1-000A GEN
Solar/Wind Harmer
4.52
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
316478AD1-087 GEN
Solar/Wind Helper
3.067
316486AD2-202 GEN
Solar/Wind Helper
0.898
3146926FARMVIL
Solar/Wind Helper
0.143
3146776BUCKING
Solar/Wind Helper
0.069
315773AC2-141 GEN
Solar/Wind Helper
3.566
942461AE2-259 GEN
Solar/Wind Helper
1.116
3144873MCLAUGH
Solar/Wind Helper
0.004
3144536CHRHLND
Solar/Wind Helper
0.023
315839AE2-212 C
Solar/Wind Helper
0.201
3145336SMITFLD
Solar/Wind Helper
0.059
316382AG1-145 C
Solar/Wind Helper
0.19
3146456SLIGO L269
Solar/Wind Helper
0.14
316313AB2-026
Solar/Wind Helper
0.209
316258AE1-075 C
Solar/Wind Helper
0.188
316405AF2-144 C
Solar/Wind Helper
0.157
316156AD2-030 GEN
Solar/Wind Helper
0.202
316280AD1-041 GEN
Solar/Wind Helper
0.449
3142946ENON
Solar/Wind Helper
0.045
316484AD2-074 GEN
Solar/Wind Helper
0.249
316320Y1-086
Solar/Wind Helper
0.057
316404AE1-155 C
Solar/Wind Helper
1.078
316473AC1-191 GEN
Solar/Wind Helper
0.73
3141906WESTMOR
Solar/Wind Helper
0.047
316435W1029_GEN3
Solar/Wind Helper
0.474
3146516WINFALL
Solar/Wind Helper
0.115
316118AC1-105 GEN
Solar/Wind Harmer
0.79
316123AC1-075 GEN
Solar/Wind Harmer
0.367
970165AG2-112 GEN
Solar/Wind Harmer
2.174
970163AG2-111 GEN
Solar/Wind Harmer
2.074
970085AG2-068 GEN
Solar/Wind Harmer
7.62
970581AG2-369 GEN
Solar/Wind Harmer
6.553
270069AE2-166 C O1
Solar/Wind Harmer
0.003
971981AH1-535 GEN
Solar/Wind Harmer
2.189
3143316POE
Solar/Wind Helper
0.623
316369SG1_INVT
Solar/Wind Helper
0.688
316132AB2-190 GEN1
Solar/Wind Helper
0.811
957831AF2-077 GEN
Solar/Wind Helper
0.188
319010AE1-072 C
Solar/Wind Helper
1.59
316305AF2-043 C
Solar/Wind Helper
0.186
316349AD2-085 GEN
Solar/Wind Helper
0.625
316233AE1-074 FULL
Solar/Wind Helper
0.207
957601AF2-054 GEN
Solar/Wind Helper
0.179
3141873WAN 176
Solar/Wind Helper
0.027
315662AE1-191 GEN
Solar/Wind Helper
0.718
315666AE1-190 GEN
Solar/Wind Helper
0.179
3143873LANEXA
Solar/Wind Helper
0.08
316059AD1-063 C
Solar/Wind Helper
0.134
3141913WHIT STONE
Solar/Wind Helper
0.132
3138133OCRAN
Solar/Wind Helper
0.04
3141783LANCAST
Solar/Wind Helper
0.079
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.196
316315AB2-025 C
Solar/Wind Helper
0.195
3146486SUNBURY
Solar/Wind Helper
0.126
3146486SUNBURY
Solar/Wind Helper
0.126
3141813NORNECK
Solar/Wind Helper
0.125
316312AB1-027
Solar/Wind Helper
0.236
316321Z2-027
Solar/Wind Helper
0.189
3145176PASQUOTANK
Solar/Wind Helper
0.077
316223AC1-118
Solar/Wind Helper
0.18
LAGNLTFEXP_LAGN->PJM
CLTF
9.406
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.599
TVALTFEXP_TVA->PJM
CLTF
4.709
CPLELTFEXP_CPLE->PJM
CLTF
11.262
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.898
NYPJM->LTFIMP_NY
CLTF
0.69
LGEELTFEXP_LGEE->PJM
CLTF
2.05
WECLTFEXP_WEC->PJM
CLTF
1.087
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.092
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.537
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.517
MECLTFEXP_MEC->PJM
CLTF
5.393
SIGELTFEXP_SIGE->PJM
CLTF
0.165

Details for 6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.35 %
Rating:814.98 MVA
Rating Type:B
MVA to Mitigate:825.97
MW Contribution:9.46
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
0.688
24684405SMG2
50/50
0.859
24684505SMG3
50/50
0.531
24684305SMG1
50/50
0.311
316222AC1-221 GEN
Solar/Wind Harmer
1.137
942751AE2-291 GEN
Solar/Wind Harmer
13.103
3146843MT LREL
Solar/Wind Harmer
0.235
3146843MT LREL
Solar/Wind Harmer
0.235
964791AG1-342 GEN
Solar/Wind Harmer
4.488
962561AG1-105 GEN
Solar/Wind Harmer
9.772
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.259
270013AE1-250 PV
Solar/Wind Harmer
0.004
24728405LEESVG
50/50
0.138
24684605SMG4
50/50
0.864
24288905REUSENS
50/50
0.013
316248AF1-058 C
Solar/Wind Harmer
0.003
960061AF2-297 GEN
Solar/Wind Harmer
16.056
971683AH1-343 GEN
Solar/Wind Harmer
12.232
316283AC2-100 C
Solar/Wind Harmer
0.524
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.19
270197AD1-017 GEN1
Solar/Wind Harmer
0.768
270018AE2-047 C O1
Solar/Wind Harmer
0.002
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.003
971367AH1-164 GEN
Solar/Wind Harmer
1.359
961601AG1-000A GEN
Solar/Wind Harmer
4.52
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
316478AD1-087 GEN
Solar/Wind Helper
3.067
316486AD2-202 GEN
Solar/Wind Helper
0.898
3146926FARMVIL
Solar/Wind Helper
0.143
3146776BUCKING
Solar/Wind Helper
0.069
315773AC2-141 GEN
Solar/Wind Helper
3.566
942461AE2-259 GEN
Solar/Wind Helper
1.116
3144873MCLAUGH
Solar/Wind Helper
0.004
3144536CHRHLND
Solar/Wind Helper
0.023
315839AE2-212 C
Solar/Wind Helper
0.201
3145336SMITFLD
Solar/Wind Helper
0.059
316382AG1-145 C
Solar/Wind Helper
0.19
3146456SLIGO L269
Solar/Wind Helper
0.14
316313AB2-026
Solar/Wind Helper
0.209
316258AE1-075 C
Solar/Wind Helper
0.188
316405AF2-144 C
Solar/Wind Helper
0.157
316156AD2-030 GEN
Solar/Wind Helper
0.202
316280AD1-041 GEN
Solar/Wind Helper
0.449
3142946ENON
Solar/Wind Helper
0.045
316484AD2-074 GEN
Solar/Wind Helper
0.249
316320Y1-086
Solar/Wind Helper
0.057
316404AE1-155 C
Solar/Wind Helper
1.078
316473AC1-191 GEN
Solar/Wind Helper
0.73
3141906WESTMOR
Solar/Wind Helper
0.047
316435W1029_GEN3
Solar/Wind Helper
0.474
3146516WINFALL
Solar/Wind Helper
0.115
971629AH1-314 GEN
50/50
13.606
3151561HALLBR1
50/50
0.377
24728405LEESVG
50/50
0.138
970417AG2-272 GEN
50/50
1.905
24684705SMG5
50/50
0.331
970481AG2-311 GEN
50/50
4.609
316003AC1-222 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.371
3147123OTTER R
Solar/Wind Harmer
0.091
970087AG2-069 GEN
Solar/Wind Harmer
11.429
970223AG2-152 GEN
Solar/Wind Harmer
9.459
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.098
941801AE2-185 GEN
Solar/Wind Harmer
4.19
270016AE1-250 BESS
Solar/Wind Harmer
0.004
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270030AE2-140 GEN
Solar/Wind Harmer
10.43
270173AC1-122 GEN
Solar/Wind Harmer
0.218
316359AB2-059 GEN
Solar/Wind Harmer
0.227
316049AB1-081 GEN
Solar/Wind Harmer
0.362
3142053HEARTS
Solar/Wind Harmer
0.111
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
315687AD1-152 GEN
Solar/Wind Helper
4.927
3146926FARMVIL
Solar/Wind Helper
0.143
316322AB2-045
Solar/Wind Helper
0.214
3146776BUCKING
Solar/Wind Helper
0.077
316294AC1-161 GEN
Solar/Wind Helper
3.03
316375AC2-012 GEN
Solar/Wind Helper
0.398
3145336SMITFLD
Solar/Wind Helper
0.592
316381AD1-082 GEN
Solar/Wind Helper
0.744
316388AE2-253 GEN
Solar/Wind Helper
0.545
316458AB2-190 GEN2
Solar/Wind Helper
0.811
316159AE1-175 C
Solar/Wind Helper
0.214
3146456SLIGO L269
Solar/Wind Helper
0.14
316072AD1-144
Solar/Wind Helper
0.16
3143226MDLTHAN
Solar/Wind Helper
0.138
316246AF1-032 C
Solar/Wind Helper
0.158
316336AC2-165 C
Solar/Wind Helper
0.738
3143526WINTERP
Solar/Wind Helper
0.705
3142543TWELFTH
Solar/Wind Helper
0.013
3142433PROV 92
Solar/Wind Helper
0.535
3141766HARMONY
Solar/Wind Helper
0.027
3138133OCRAN
Solar/Wind Helper
0.079
964211AG1-282 GEN
Solar/Wind Helper
0.169
3141726DUNNSVL
Solar/Wind Helper
0.503
3142416OLDCHRC
Solar/Wind Helper
0.323
3142416OLDCHRC
Solar/Wind Helper
0.124
316337AD2-073 GEN
Solar/Wind Helper
0.184
3146516WINFALL
Solar/Wind Helper
0.371
3146516WINFALL
Solar/Wind Helper
0.115
3147173SINAI
Solar/Wind Harmer
0.376
3147243WELCO
Solar/Wind Harmer
0.235
970865AG2-541 GEN
Solar/Wind Harmer
10.789
316118AC1-105 GEN
Solar/Wind Harmer
0.79
316123AC1-075 GEN
Solar/Wind Harmer
0.367
970165AG2-112 GEN
Solar/Wind Harmer
2.174
970163AG2-111 GEN
Solar/Wind Harmer
2.074
970085AG2-068 GEN
Solar/Wind Harmer
7.62
970581AG2-369 GEN
Solar/Wind Harmer
6.553
270069AE2-166 C O1
Solar/Wind Harmer
0.003
971981AH1-535 GEN
Solar/Wind Harmer
2.189
3143316POE
Solar/Wind Helper
0.623
316369SG1_INVT
Solar/Wind Helper
0.688
316132AB2-190 GEN1
Solar/Wind Helper
0.811
957831AF2-077 GEN
Solar/Wind Helper
0.188
319010AE1-072 C
Solar/Wind Helper
1.59
316305AF2-043 C
Solar/Wind Helper
0.186
316349AD2-085 GEN
Solar/Wind Helper
0.625
316233AE1-074 FULL
Solar/Wind Helper
0.207
957601AF2-054 GEN
Solar/Wind Helper
0.179
3141873WAN 176
Solar/Wind Helper
0.027
315662AE1-191 GEN
Solar/Wind Helper
0.718
315666AE1-190 GEN
Solar/Wind Helper
0.179
3143873LANEXA
Solar/Wind Helper
0.08
316059AD1-063 C
Solar/Wind Helper
0.134
3141913WHIT STONE
Solar/Wind Helper
0.132
3138133OCRAN
Solar/Wind Helper
0.04
3141783LANCAST
Solar/Wind Helper
0.079
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.196
316315AB2-025 C
Solar/Wind Helper
0.195
3146486SUNBURY
Solar/Wind Helper
0.126
3146486SUNBURY
Solar/Wind Helper
0.126
3141813NORNECK
Solar/Wind Helper
0.125
316312AB1-027
Solar/Wind Helper
0.236
316321Z2-027
Solar/Wind Helper
0.189
3145176PASQUOTANK
Solar/Wind Helper
0.077
316223AC1-118
Solar/Wind Helper
0.18
961601AG1-000A GEN
Solar/Wind Harmer
1.13
316263AC1-034 GEN
Solar/Wind Harmer
2.401
3146776BUCKING
Solar/Wind Helper
0.769
3146776BUCKING
Solar/Wind Helper
0.062
316036AC1-147 C
Solar/Wind Helper
0.231
316316AC1-027 C
Solar/Wind Helper
0.237
3142956BIRDNECK
Solar/Wind Helper
0.101
316185AD1-033 GEN
Solar/Wind Helper
0.703
316236AE1-162_GEN
Solar/Wind Helper
0.199
3145506HICKORY
Solar/Wind Helper
0.589
3145506HICKORY
Solar/Wind Helper
0.353
3145506HICKORY
Solar/Wind Helper
0.088
316240AF1-291 C
Solar/Wind Helper
0.194
316339AD2-160 GEN
Solar/Wind Helper
0.545
316033AB2-134 GEN
Solar/Wind Helper
0.492
315697AD1-025 GEN
Solar/Wind Helper
1.636
316018AA1-139 ULT2
Solar/Wind Helper
0.611
316017AA1-139 ULT1
Solar/Wind Helper
0.649
3137176SLIGO L2192
Solar/Wind Helper
0.558
3130086AYDLETT
Solar/Wind Helper
0.554
3143526WINTERP
Solar/Wind Helper
0.705
3142946ENON
Solar/Wind Helper
0.013
316075AC2-137 C
Solar/Wind Helper
0.197
316487AF1-042 GEN
Solar/Wind Helper
0.13
3146386ELIZ CT
Solar/Wind Helper
0.129
3144356SAPONY
Solar/Wind Helper
0.229
316077AC2-138 C
Solar/Wind Helper
0.118
966871AG1-558 GEN
Solar/Wind Helper
0.161
316431W1029_GEN1
Solar/Wind Helper
0.474
316433W1029_GEN2
Solar/Wind Helper
0.474
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
316468AD1-105 GEN
Solar/Wind Helper
0.556
LAGNLTFEXP_LAGN->PJM
CLTF
9.406
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.599
TVALTFEXP_TVA->PJM
CLTF
4.709
CPLELTFEXP_CPLE->PJM
CLTF
11.262
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.898
NYPJM->LTFIMP_NY
CLTF
0.69
LGEELTFEXP_LGEE->PJM
CLTF
2.05
WECLTFEXP_WEC->PJM
CLTF
1.087
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.092
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.537
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.517
MECLTFEXP_MEC->PJM
CLTF
5.393
SIGELTFEXP_SIGE->PJM
CLTF
0.165

Details for 8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 555_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 555_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.33 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3617.39
MW Contribution:8.2
Bus #Bus NameTypeMW Contribution
24290605CLAY-1
50/50
0.172
24290605CLAY-1
50/50
0.172
24290705CLAY-2
50/50
0.172
24290705CLAY-2
50/50
0.172
270583AD2-179 GEN
Solar/Wind Harmer
9.708
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
4.021
971277AH1-098 GEN
Solar/Wind Harmer
3.383
270013AE1-250 PV
Solar/Wind Harmer
0.004
24728205BUCHG1
Adder
4.101
3132123MT JACKSON
Solar/Wind Helper
1.116
3152061BATH 6F
50/50
16.44
970823AG2-518 GEN
50/50
5.734
962751AG1-124 GEN
Solar/Wind Harmer
9.115
270173AC1-122 GEN
Solar/Wind Harmer
0.472
958121AF2-106 GEN
Solar/Wind Harmer
0.001
247619Y1-049
Adder
0.574
971331AH1-145 GEN
Solar/Wind Harmer
12.171
3147312GRETNA
Solar/Wind Harmer
0.129
3146802CHATHAM
Solar/Wind Harmer
0.121
941801AE2-185 GEN
Solar/Wind Harmer
5.17
943031AE2-326 GEN
Solar/Wind Harmer
4.43
3147123OTTER R
Solar/Wind Harmer
0.09
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270030AE2-140 GEN
Solar/Wind Harmer
14.108
270346AE1-212 GEN
Solar/Wind Harmer
5.915
270016AE1-250 BESS
Solar/Wind Harmer
0.004
970223AG2-152 GEN
Solar/Wind Harmer
8.195
960911AF2-382 GEN
Solar/Wind Harmer
4.593
3147983MERCK5
Solar/Wind Helper
0.146
3152011BATH 1A
50/50
16.383
3152021BATH 2B
50/50
16.383
3152031BATH 3C
50/50
16.378
3152041BATH 4D
50/50
16.352
3151881LOWMORC
50/50
4.046
3151881LOWMORC
50/50
3.982
3151861LOWMORA
50/50
3.918
971543AH1-269 GEN
50/50
8.257
3148463FAIRFLD
Solar/Wind Harmer
0.358
966391AG1-508 GEN
Solar/Wind Harmer
1.299
270069AE2-166 C O1
Solar/Wind Harmer
0.005
971313AH1-133 GEN
Solar/Wind Harmer
6.761
24734705WLF1G3
Adder
4.975
24734805WLF1G4
Adder
4.975
24734905WLF1G5
Adder
4.975
3148133STUARTS
Solar/Wind Helper
0.182
3148013FISHERV
Solar/Wind Helper
0.175
3138266HYDRAULIC
Solar/Wind Helper
0.012
3138266HYDRAULIC
Solar/Wind Helper
0.007
3152051BATH 5E
50/50
16.369
3151861LOWMORA
50/50
4.078
3137383CUSHAW
50/50
0.078
270205AE1-176
50/50
0.004
970479AG2-310 GEN
50/50
14.12
24288905REUSENS
50/50
0.04
315616AA1-038_C
Solar/Wind Harmer
0.003
971367AH1-164 GEN
Solar/Wind Harmer
3.331
971329AH1-144 GEN
Solar/Wind Harmer
7.668
3147312GRETNA
Solar/Wind Harmer
0.032
941821AE2-187 GEN
Solar/Wind Harmer
5.17
270197AD1-017 GEN1
Solar/Wind Harmer
0.974
270336AE1-100 GEN
Solar/Wind Harmer
0.004
958131AF2-107 GEN
Solar/Wind Harmer
3.843
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270018AE2-047 C O1
Solar/Wind Harmer
0.003
24728305BUCHG2
Adder
4.101
316499AE2-029_GEN
Solar/Wind Helper
1.225
3148013FISHERV
Solar/Wind Helper
0.304
23583801GRNGAP
Solar/Wind Helper
3.885
237061AD1-155 GEN
Solar/Wind Helper
0.042
LAGNLTFEXP_LAGN->PJM
CLTF
11.387
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.911
TVALTFEXP_TVA->PJM
CLTF
6.03
CPLELTFEXP_CPLE->PJM
CLTF
3.393
CBM West 2LTFEXP_CBM-W2->PJM
CBM
71.784
NYPJM->LTFIMP_NY
CLTF
2.909
LGEELTFEXP_LGEE->PJM
CLTF
3.588
WECLTFEXP_WEC->PJM
CLTF
1.753
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155
CBM West 1LTFEXP_CBM-W1->PJM
CBM
62.503
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.099
MECLTFEXP_MEC->PJM
CLTF
8.174
SIGELTFEXP_SIGE->PJM
CLTF
0.27

Details for 8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2168-555_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2168-555_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.49 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4156.4
MW Contribution:12.91
Bus #Bus NameTypeMW Contribution
3152011BATH 1A
50/50
17.37
3152021BATH 2B
50/50
17.37
3152031BATH 3C
50/50
17.364
3152041BATH 4D
50/50
17.337
3151881LOWMORC
50/50
6.984
3151881LOWMORC
50/50
6.875
24290605CLAY-1
50/50
0.194
24290605CLAY-1
50/50
0.194
24290705CLAY-2
50/50
0.194
24290705CLAY-2
50/50
0.194
270583AD2-179 GEN
Solar/Wind Harmer
15.671
270214AC2-123 GEN
Solar/Wind Harmer
3.17
316217AC1-145 GEN
Solar/Wind Harmer
3.265
316197AC1-042 GEN
Solar/Wind Harmer
2.475
942671AE2-283 GEN
Solar/Wind Harmer
6.664
971277AH1-098 GEN
Solar/Wind Harmer
5.461
270013AE1-250 PV
Solar/Wind Harmer
2.411
24728205BUCHG1
Adder
4.634
971225AH1-072 GEN
Solar/Wind Harmer
1.824
971227AH1-073 GEN
Solar/Wind Harmer
1.824
3132123MT JACKSON
Solar/Wind Helper
1.31
315821AE2-092 GEN
Solar/Wind Helper
2.895
3152051BATH 5E
50/50
17.355
3137383CUSHAW
50/50
0.134
3151861LOWMORA
50/50
7.039
270205AE1-176
50/50
0.005
970479AG2-310 GEN
50/50
15.892
24288905REUSENS
50/50
0.045
315616AA1-038_C
Solar/Wind Harmer
14.233
3151861LOWMORA
50/50
6.765
971543AH1-269 GEN
50/50
9.298
3148463FAIRFLD
Solar/Wind Harmer
-0.069
966391AG1-508 GEN
Solar/Wind Harmer
4.68
270069AE2-166 C O1
Solar/Wind Harmer
3.325
971313AH1-133 GEN
Solar/Wind Harmer
10.943
966001AG1-469 GEN
Solar/Wind Helper
0.292
315651AD1-115 GEN
Solar/Wind Helper
0.781
24734705WLF1G3
Adder
5.613
24734805WLF1G4
Adder
5.613
24734905WLF1G5
Adder
5.613
24735105WLF2G1
Adder
5.48
270132AB1-180 C
Adder
0.114
3148133STUARTS
Solar/Wind Helper
0.274
3148013FISHERV
Solar/Wind Helper
0.263
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.011
23546401DTGZ2-030
Solar/Wind Helper
0.075
238152AF2-075_GEN
Solar/Wind Helper
0.572
316164AC1-076 GEN
Solar/Wind Helper
1.095
3152061BATH 6F
50/50
17.43
970823AG2-518 GEN
50/50
6.455
962751AG1-124 GEN
Solar/Wind Harmer
14.726
270173AC1-122 GEN
Solar/Wind Harmer
2.55
958121AF2-106 GEN
Solar/Wind Harmer
7.115
247619Y1-049
Adder
0.646
971331AH1-145 GEN
Solar/Wind Harmer
13.718
943031AE2-326 GEN
Solar/Wind Harmer
4.99
3147312GRETNA
Solar/Wind Harmer
-0.016
3146802CHATHAM
Solar/Wind Harmer
-0.015
941801AE2-185 GEN
Solar/Wind Harmer
7.544
3147123OTTER R
Solar/Wind Harmer
-0.011
270574AD1-017 GEN2
Solar/Wind Harmer
6.414
270030AE2-140 GEN
Solar/Wind Harmer
22.569
270346AE1-212 GEN
Solar/Wind Harmer
9.778
270016AE1-250 BESS
Solar/Wind Harmer
2.411
960911AF2-382 GEN
Solar/Wind Harmer
7.443
970223AG2-152 GEN
Solar/Wind Harmer
12.909
971461AH1-227 GEN
Solar/Wind Harmer
4.678
970913AG2-568 GEN
Solar/Wind Harmer
7.285
3147983MERCK5
Solar/Wind Helper
0.183
316192AB2-158 GEN
Solar/Wind Helper
1.696
3147666LOUISA
Solar/Wind Helper
1.004
316254AC1-120 GEN1
Solar/Wind Helper
1.079
316097T157 G90
Solar/Wind Helper
1.082
238148AE2-230_GEN2
Solar/Wind Helper
0.402
316336AC2-165 C
Solar/Wind Helper
1.208
971367AH1-164 GEN
Solar/Wind Harmer
5.352
971329AH1-144 GEN
Solar/Wind Harmer
17.696
3147312GRETNA
Solar/Wind Harmer
-0.004
941821AE2-187 GEN
Solar/Wind Harmer
7.544
270197AD1-017 GEN1
Solar/Wind Harmer
1.927
270336AE1-100 GEN
Solar/Wind Harmer
2.02
943811AF1-049 GEN
Solar/Wind Harmer
4.147
270018AE2-047 C O1
Solar/Wind Harmer
1.338
958131AF2-107 GEN
Solar/Wind Harmer
5.403
24728305BUCHG2
Adder
4.634
24735205WLF2G2
Adder
5.48
971687AH1-348 GEN
Solar/Wind Harmer
0.906
971403AH1-188 GEN
Solar/Wind Harmer
12.187
316499AE2-029_GEN
Solar/Wind Helper
1.577
3148013FISHERV
Solar/Wind Helper
0.457
3132273ORANGE
Solar/Wind Helper
0.051
3147666LOUISA
Solar/Wind Helper
0.577
237061AD1-155 GEN
Solar/Wind Helper
0.047
23583801GRNGAP
Solar/Wind Helper
4.125
316170AC1-121 GEN2
Solar/Wind Helper
0.36
316095T157 G97
Solar/Wind Helper
1.082
238147AE2-230_GEN1
Solar/Wind Helper
0.401
238149AF1-291A_GEN
Solar/Wind Helper
0.114
LAGNLTFEXP_LAGN->PJM
CLTF
12.827
CBM South 2LTFEXP_CBM-S2->PJM
CBM
16.289
TVALTFEXP_TVA->PJM
CLTF
6.791
CPLELTFEXP_CPLE->PJM
CLTF
3.547
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.312
NYPJM->LTFIMP_NY
CLTF
3.2
LGEELTFEXP_LGEE->PJM
CLTF
4.095
WECLTFEXP_WEC->PJM
CLTF
2.007
AG2-052LTFEXP_AG2-052->PJM
LTF
0.119
AH1-155LTFEXP_AH1-155->PJM
LTF
0.178
CBM West 1LTFEXP_CBM-W1->PJM
CBM
71.759
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.94
MECLTFEXP_MEC->PJM
CLTF
9.322
SIGELTFEXP_SIGE->PJM
CLTF
0.308

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.73 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5687.33
MW Contribution:12.91
Bus #Bus NameTypeMW Contribution
3151041BRUNSWICKG3
50/50
8.505
972187AH1-678 GEN
50/50
19.517
315242AE2-183_GT2
50/50
10.667
315241AE2-183_GT1
50/50
10.602
972185AH1-677 GEN
50/50
38.457
970533AG2-339 GEN
50/50
57.391
970531AG2-338 GEN
50/50
22.956
3152661PLYWOOD A
50/50
0.751
970535AG2-341 GEN
50/50
5.149
3144293JTRSVLE
50/50
0.914
3144293JTRSVLE
50/50
0.769
970933AG2-581 GEN
Solar/Wind Harmer
51.542
970099AG2-077 GEN
Solar/Wind Harmer
57.884
971741AH1-377 GEN
Solar/Wind Harmer
38.437
970301AG2-198 GEN
Solar/Wind Harmer
15.165
3146843MT LREL
Solar/Wind Harmer
0.321
3146843MT LREL
Solar/Wind Harmer
0.321
3151051BRUNSWICKS1
50/50
17.651
3151021BRUNSWICKG1
50/50
8.505
971451AH1-221 GEN
50/50
25.831
315243AE2-183_GT3
50/50
10.667
963041AG1-153 GEN
50/50
17.22
315244AE2-183_ST
50/50
18.443
3151541CLOVER2
50/50
10.593
3151611KERR 4
50/50
0.604
3151621KERR 5
50/50
0.604
964791AG1-342 GEN
Solar/Wind Harmer
6.159
962561AG1-105 GEN
Solar/Wind Harmer
15.15
316222AC1-221 GEN
Solar/Wind Harmer
1.267
939181AE1-148 GEN
Solar/Wind Harmer
13.97
313527AB2-043 GEN
Solar/Wind Harmer
0.004
970323AG2-213 GEN
Solar/Wind Harmer
11.867
971775AH1-396 GEN
Solar/Wind Harmer
0.445
316034AC1-036 C
Solar/Wind Harmer
0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.246
963191AG1-168 GEN
Solar/Wind Harmer
1.082
3147133PAMPLIN
Solar/Wind Harmer
0.268
3147133PAMPLIN
Solar/Wind Harmer
0.214
942751AE2-291 GEN
Solar/Wind Harmer
12.744
270013AE1-250 PV
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.64
3146776BUCKING
Solar/Wind Harmer
0.052
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
3.595
316263AC1-034 GEN
Solar/Wind Harmer
4.676
961601AG1-000A GEN
Solar/Wind Harmer
2.136
316036AC1-147 C
Solar/Wind Helper
0.621
3142956BIRDNECK
Solar/Wind Helper
0.272
316316AC1-027 C
Solar/Wind Helper
0.638
316185AD1-033 GEN
Solar/Wind Helper
1.893
3145506HICKORY
Solar/Wind Helper
1.587
3145506HICKORY
Solar/Wind Helper
0.952
3145506HICKORY
Solar/Wind Helper
0.238
316236AE1-162_GEN
Solar/Wind Helper
0.529
316339AD2-160 GEN
Solar/Wind Helper
1.472
316018AA1-139 ULT2
Solar/Wind Helper
1.65
316017AA1-139 ULT1
Solar/Wind Helper
1.754
3137176SLIGO L2192
Solar/Wind Helper
1.508
3130086AYDLETT
Solar/Wind Helper
1.498
316033AB2-134 GEN
Solar/Wind Helper
1.287
315697AD1-025 GEN
Solar/Wind Helper
4.277
316240AF1-291 C
Solar/Wind Helper
0.501
3146386ELIZ CT
Solar/Wind Helper
0.35
3142946ENON
Solar/Wind Helper
0.034
316487AF1-042 GEN
Solar/Wind Helper
0.339
3144356SAPONY
Solar/Wind Helper
0.597
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.305
316431W1029_GEN1
Solar/Wind Helper
1.295
316433W1029_GEN2
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
966871AG1-558 GEN
Solar/Wind Helper
0.403
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
316468AD1-105 GEN
Solar/Wind Helper
1.402
315742AE1-103 GEN
Solar/Wind Helper
0.368
3151531CLOVER1
50/50
10.644
3151601KERR 3
50/50
0.604
3151581KERR 1
50/50
0.216
3144293JTRSVLE
50/50
0.914
971629AH1-314 GEN
50/50
19.06
3151561HALLBR1
50/50
0.404
970919AG2-571 GEN
Solar/Wind Harmer
21.586
970087AG2-069 GEN
Solar/Wind Harmer
48.225
957481AF2-042 GEN
Solar/Wind Harmer
144.711
315693AD1-088 GEN
Solar/Wind Harmer
23.762
962491AG1-098 GEN
Solar/Wind Harmer
27.839
315687AD1-152 GEN
Solar/Wind Harmer
0.015
316003AC1-222 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.882
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
20.472
963171AG1-166 GEN
Solar/Wind Harmer
1.443
971563AH1-280 GEN
Solar/Wind Harmer
2.885
3146926FARMVIL
Solar/Wind Harmer
0.151
971065AG2-659 GEN
Solar/Wind Harmer
9.511
316129AC1-054 GEN
Solar/Wind Harmer
0.786
970223AG2-152 GEN
Solar/Wind Harmer
12.908
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.097
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.064
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.115
3146802CHATHAM
Solar/Wind Harmer
0.108
941801AE2-185 GEN
Solar/Wind Harmer
4.622
270030AE2-140 GEN
Solar/Wind Harmer
14.688
3145543BTLEBRO
Solar/Wind Harmer
0.123
3145543BTLEBRO
Solar/Wind Harmer
0.099
316359AB2-059 GEN
Solar/Wind Harmer
0.442
316049AB1-081 GEN
Solar/Wind Harmer
0.704
3142053HEARTS
Solar/Wind Harmer
0.217
316294AC1-161 GEN
Solar/Wind Helper
8.153
316375AC2-012 GEN
Solar/Wind Helper
1.068
3145336SMITFLD
Solar/Wind Helper
1.575
316388AE2-253 GEN
Solar/Wind Helper
1.472
3146456SLIGO L269
Solar/Wind Helper
0.379
316381AD1-082 GEN
Solar/Wind Helper
1.955
316072AD1-144
Solar/Wind Helper
0.428
316246AF1-032 C
Solar/Wind Helper
0.424
316159AE1-175 C
Solar/Wind Helper
0.562
316458AB2-190 GEN2
Solar/Wind Helper
2.107
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.376
3138133OCRAN
Solar/Wind Helper
0.206
3142543TWELFTH
Solar/Wind Helper
0.032
964211AG1-282 GEN
Solar/Wind Helper
0.439
3141726DUNNSVL
Solar/Wind Helper
1.304
316337AD2-073 GEN
Solar/Wind Helper
0.478
3142416OLDCHRC
Solar/Wind Helper
0.816
3142416OLDCHRC
Solar/Wind Helper
0.312
3146516WINFALL
Solar/Wind Helper
1.016
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
3143226MDLTHAN
Solar/Wind Helper
0.3
315800Z1-036_GEN1
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3151631KERR 6
50/50
0.604
3151641KERR 7
50/50
0.604
971967AH1-528 GEN
Solar/Wind Harmer
109.53
970673AG2-436 GEN
Solar/Wind Harmer
137.75
970673AG2-436 GEN
Solar/Wind Harmer
91.833
941031AE2-094 GEN
Solar/Wind Harmer
118.914
944011AF1-069 GEN
Solar/Wind Harmer
38.854
970085AG2-068 GEN
Solar/Wind Harmer
32.15
970581AG2-369 GEN
Solar/Wind Harmer
27.649
3147173SINAI
Solar/Wind Harmer
0.345
3147243WELCO
Solar/Wind Harmer
0.216
316118AC1-105 GEN
Solar/Wind Harmer
0.86
970865AG2-541 GEN
Solar/Wind Harmer
10.119
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.678
3144303KENBRDG
Solar/Wind Harmer
0.222
970683AG2-441 GEN
Solar/Wind Harmer
18.278
970681AG2-440 GEN
Solar/Wind Harmer
14.623
946301AF1-294 GEN
Solar/Wind Harmer
5.338
961791AG1-021 GEN
Solar/Wind Harmer
2.597
315657AE1-056 GEN
Solar/Wind Harmer
9.239
316123AC1-075 GEN
Solar/Wind Harmer
0.351
970165AG2-112 GEN
Solar/Wind Harmer
2.08
970163AG2-111 GEN
Solar/Wind Harmer
1.985
970831AG2-522 GEN
Solar/Wind Harmer
8.286
970285AG2-188 GEN
Solar/Wind Harmer
14.461
971845AH1-439 GEN
Solar/Wind Harmer
7.612
270069AE2-166 C O1
Solar/Wind Harmer
0.005
3143316POE
Solar/Wind Helper
1.64
319010AE1-072 C
Solar/Wind Helper
4.299
316369SG1_INVT
Solar/Wind Helper
1.8
316305AF2-043 C
Solar/Wind Helper
0.499
316132AB2-190 GEN1
Solar/Wind Helper
2.107
957831AF2-077 GEN
Solar/Wind Helper
0.495
316349AD2-085 GEN
Solar/Wind Helper
1.649
313526AB2-022
Solar/Wind Helper
0.533
957601AF2-054 GEN
Solar/Wind Helper
0.467
3141873WAN 176
Solar/Wind Helper
0.07
315662AE1-191 GEN
Solar/Wind Helper
1.865
315666AE1-190 GEN
Solar/Wind Helper
0.466
316059AD1-063 C
Solar/Wind Helper
0.348
3141913WHIT STONE
Solar/Wind Helper
0.345
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.137
3146486SUNBURY
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.341
316321Z2-027
Solar/Wind Helper
0.514
3145176PASQUOTANK
Solar/Wind Helper
0.209
316315AB2-025 C
Solar/Wind Helper
0.507
3141813NORNECK
Solar/Wind Helper
0.325
316312AB1-027
Solar/Wind Helper
0.597
316233AE1-074 FULL
Solar/Wind Helper
0.469
316223AC1-118
Solar/Wind Helper
0.466
315611Z1-036_GEN2
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
3151031BRUNSWICKG2
50/50
8.505
970413AG2-270 GEN
50/50
46.449
3151591KERR 2
50/50
0.604
3144293JTRSVLE
50/50
0.914
970917AG2-570 GEN
Solar/Wind Harmer
53.965
316478AD1-087 GEN
Solar/Wind Harmer
1.733
316486AD2-202 GEN
Solar/Wind Harmer
0.509
970909AG2-566 GEN
Solar/Wind Harmer
3.791
316248AF1-058 C
Solar/Wind Harmer
0.003
960061AF2-297 GEN
Solar/Wind Harmer
14.727
971683AH1-343 GEN
Solar/Wind Harmer
11.379
316283AC2-100 C
Solar/Wind Harmer
0.592
316131AB2-060 GEN
Solar/Wind Harmer
0.901
964241AG1-285 GEN
Solar/Wind Harmer
18.92
315785AD2-033 C
Solar/Wind Harmer
2.274
970257AG2-171 GEN
Solar/Wind Harmer
8.9
959311AF2-222 GEN
Solar/Wind Harmer
24.62
963181AG1-167 GEN
Solar/Wind Harmer
1.082
3147133PAMPLIN
Solar/Wind Harmer
0.841
971193AH1-056 GEN
Solar/Wind Harmer
16.311
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
3146926FARMVIL
Solar/Wind Harmer
0.151
3146776BUCKING
Solar/Wind Harmer
0.058
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
1.012
3147312GRETNA
Solar/Wind Harmer
0.029
941821AE2-187 GEN
Solar/Wind Harmer
4.622
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.004
3145543BTLEBRO
Solar/Wind Harmer
0.123
3145543BTLEBRO
Solar/Wind Harmer
0.123
971623AH1-311 GEN
Solar/Wind Harmer
0.246
961601AG1-000A GEN
Solar/Wind Harmer
8.544
315773AC2-141 GEN
Solar/Wind Helper
9.595
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3145336SMITFLD
Solar/Wind Helper
0.157
315839AE2-212 C
Solar/Wind Helper
0.523
3146456SLIGO L269
Solar/Wind Helper
0.379
316382AG1-145 C
Solar/Wind Helper
0.498
316320Y1-086
Solar/Wind Helper
0.156
316156AD2-030 GEN
Solar/Wind Helper
0.525
316280AD1-041 GEN
Solar/Wind Helper
1.166
3142946ENON
Solar/Wind Helper
0.114
316484AD2-074 GEN
Solar/Wind Helper
0.648
316404AE1-155 C
Solar/Wind Helper
2.8
316435W1029_GEN3
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3141906WESTMOR
Solar/Wind Helper
0.122
316473AC1-191 GEN
Solar/Wind Helper
1.829
3146626S HERTFORD
Solar/Wind Helper
0.296
3145273HOLLAND
Solar/Wind Helper
0.201
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.24
LAGNLTFEXP_LAGN->PJM
CLTF
15.403
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.288
TVALTFEXP_TVA->PJM
CLTF
7.684
CPLELTFEXP_CPLE->PJM
CLTF
20.639
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.343
NYPJM->LTFIMP_NY
CLTF
2.484
LGEELTFEXP_LGEE->PJM
CLTF
2.833
WECLTFEXP_WEC->PJM
CLTF
1.482
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.447
MECLTFEXP_MEC->PJM
CLTF
7.78
SIGELTFEXP_SIGE->PJM
CLTF
0.233

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.78 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5445.28
MW Contribution:12.91
Bus #Bus NameTypeMW Contribution
3151051BRUNSWICKS1
50/50
17.651
3151021BRUNSWICKG1
50/50
8.505
971451AH1-221 GEN
50/50
25.831
315243AE2-183_GT3
50/50
10.667
3151531CLOVER1
50/50
10.644
3151601KERR 3
50/50
0.604
3151581KERR 1
50/50
0.216
3144293JTRSVLE
50/50
0.914
971629AH1-314 GEN
50/50
19.06
3151561HALLBR1
50/50
0.404
970919AG2-571 GEN
Solar/Wind Harmer
21.586
970087AG2-069 GEN
Solar/Wind Harmer
48.225
957481AF2-042 GEN
Solar/Wind Harmer
144.711
315693AD1-088 GEN
Solar/Wind Harmer
23.762
962491AG1-098 GEN
Solar/Wind Harmer
27.839
315687AD1-152 GEN
Solar/Wind Harmer
0.015
316003AC1-222 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.882
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
20.472
963171AG1-166 GEN
Solar/Wind Harmer
1.443
971563AH1-280 GEN
Solar/Wind Harmer
2.885
3146926FARMVIL
Solar/Wind Harmer
0.151
971065AG2-659 GEN
Solar/Wind Harmer
9.511
316129AC1-054 GEN
Solar/Wind Harmer
0.786
970223AG2-152 GEN
Solar/Wind Harmer
12.908
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.097
3151031BRUNSWICKG2
50/50
8.505
970413AG2-270 GEN
50/50
46.449
3151591KERR 2
50/50
0.604
3144293JTRSVLE
50/50
0.914
970917AG2-570 GEN
Solar/Wind Harmer
53.965
316478AD1-087 GEN
Solar/Wind Harmer
1.733
316486AD2-202 GEN
Solar/Wind Harmer
0.509
970909AG2-566 GEN
Solar/Wind Harmer
3.791
316248AF1-058 C
Solar/Wind Harmer
0.003
960061AF2-297 GEN
Solar/Wind Harmer
14.727
971683AH1-343 GEN
Solar/Wind Harmer
11.379
316283AC2-100 C
Solar/Wind Harmer
0.592
316131AB2-060 GEN
Solar/Wind Harmer
0.901
964241AG1-285 GEN
Solar/Wind Harmer
18.92
315785AD2-033 C
Solar/Wind Harmer
2.274
970257AG2-171 GEN
Solar/Wind Harmer
8.9
959311AF2-222 GEN
Solar/Wind Harmer
24.62
963181AG1-167 GEN
Solar/Wind Harmer
1.082
3147133PAMPLIN
Solar/Wind Harmer
0.841
971193AH1-056 GEN
Solar/Wind Harmer
16.311
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
3146926FARMVIL
Solar/Wind Harmer
0.151
3146776BUCKING
Solar/Wind Harmer
0.058
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
1.012
3147312GRETNA
Solar/Wind Harmer
0.029
941821AE2-187 GEN
Solar/Wind Harmer
4.622
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.004
3145543BTLEBRO
Solar/Wind Harmer
0.123
3145543BTLEBRO
Solar/Wind Harmer
0.123
971623AH1-311 GEN
Solar/Wind Harmer
0.246
963041AG1-153 GEN
50/50
17.22
315244AE2-183_ST
50/50
18.443
3151541CLOVER2
50/50
10.593
3151611KERR 4
50/50
0.604
3151621KERR 5
50/50
0.604
3151631KERR 6
50/50
0.604
3151641KERR 7
50/50
0.604
971967AH1-528 GEN
Solar/Wind Harmer
109.53
970673AG2-436 GEN
Solar/Wind Harmer
137.75
970673AG2-436 GEN
Solar/Wind Harmer
91.833
970085AG2-068 GEN
Solar/Wind Harmer
32.15
970581AG2-369 GEN
Solar/Wind Harmer
27.649
3147173SINAI
Solar/Wind Harmer
0.345
3147243WELCO
Solar/Wind Harmer
0.216
316118AC1-105 GEN
Solar/Wind Harmer
0.86
970865AG2-541 GEN
Solar/Wind Harmer
10.119
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.678
3144303KENBRDG
Solar/Wind Harmer
0.222
970683AG2-441 GEN
Solar/Wind Harmer
18.278
970681AG2-440 GEN
Solar/Wind Harmer
14.623
946301AF1-294 GEN
Solar/Wind Harmer
5.338
961791AG1-021 GEN
Solar/Wind Harmer
2.597
315657AE1-056 GEN
Solar/Wind Harmer
9.239
316123AC1-075 GEN
Solar/Wind Harmer
0.351
970165AG2-112 GEN
Solar/Wind Harmer
2.08
970163AG2-111 GEN
Solar/Wind Harmer
1.985
970831AG2-522 GEN
Solar/Wind Harmer
8.286
970285AG2-188 GEN
Solar/Wind Harmer
14.461
971845AH1-439 GEN
Solar/Wind Harmer
7.612
270069AE2-166 C O1
Solar/Wind Harmer
0.005
3143316POE
Solar/Wind Helper
1.64
319010AE1-072 C
Solar/Wind Helper
4.299
316369SG1_INVT
Solar/Wind Helper
1.8
316305AF2-043 C
Solar/Wind Helper
0.499
316132AB2-190 GEN1
Solar/Wind Helper
2.107
957831AF2-077 GEN
Solar/Wind Helper
0.495
316349AD2-085 GEN
Solar/Wind Helper
1.649
313526AB2-022
Solar/Wind Helper
0.533
957601AF2-054 GEN
Solar/Wind Helper
0.467
3141873WAN 176
Solar/Wind Helper
0.07
315662AE1-191 GEN
Solar/Wind Helper
1.865
315666AE1-190 GEN
Solar/Wind Helper
0.466
316059AD1-063 C
Solar/Wind Helper
0.348
3141913WHIT STONE
Solar/Wind Helper
0.345
3138133OCRAN
Solar/Wind Helper
0.103
3151041BRUNSWICKG3
50/50
8.505
972187AH1-678 GEN
50/50
19.517
315242AE2-183_GT2
50/50
10.667
315241AE2-183_GT1
50/50
10.602
972185AH1-677 GEN
50/50
38.457
3152661PLYWOOD A
50/50
0.751
970535AG2-341 GEN
50/50
5.149
3144293JTRSVLE
50/50
0.914
3144293JTRSVLE
50/50
0.769
970933AG2-581 GEN
Solar/Wind Harmer
51.542
970099AG2-077 GEN
Solar/Wind Harmer
57.884
971741AH1-377 GEN
Solar/Wind Harmer
38.437
970301AG2-198 GEN
Solar/Wind Harmer
15.165
3146843MT LREL
Solar/Wind Harmer
0.321
3146843MT LREL
Solar/Wind Harmer
0.321
964791AG1-342 GEN
Solar/Wind Harmer
6.159
962561AG1-105 GEN
Solar/Wind Harmer
15.15
316222AC1-221 GEN
Solar/Wind Harmer
1.267
939181AE1-148 GEN
Solar/Wind Harmer
13.97
313527AB2-043 GEN
Solar/Wind Harmer
0.004
970323AG2-213 GEN
Solar/Wind Harmer
11.867
971775AH1-396 GEN
Solar/Wind Harmer
0.445
316034AC1-036 C
Solar/Wind Harmer
0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.246
963191AG1-168 GEN
Solar/Wind Harmer
1.082
3147133PAMPLIN
Solar/Wind Harmer
0.268
3147133PAMPLIN
Solar/Wind Harmer
0.214
942751AE2-291 GEN
Solar/Wind Harmer
12.744
270013AE1-250 PV
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.64
3146776BUCKING
Solar/Wind Harmer
0.052
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
3.595
316263AC1-034 GEN
Solar/Wind Harmer
4.676
961601AG1-000A GEN
Solar/Wind Harmer
2.136
316036AC1-147 C
Solar/Wind Helper
0.621
3142956BIRDNECK
Solar/Wind Helper
0.272
316316AC1-027 C
Solar/Wind Helper
0.638
316185AD1-033 GEN
Solar/Wind Helper
1.893
3145506HICKORY
Solar/Wind Helper
1.587
3145506HICKORY
Solar/Wind Helper
0.952
3145506HICKORY
Solar/Wind Helper
0.238
316236AE1-162_GEN
Solar/Wind Helper
0.529
316339AD2-160 GEN
Solar/Wind Helper
1.472
316018AA1-139 ULT2
Solar/Wind Helper
1.65
316017AA1-139 ULT1
Solar/Wind Helper
1.754
3137176SLIGO L2192
Solar/Wind Helper
1.508
3130086AYDLETT
Solar/Wind Helper
1.498
316033AB2-134 GEN
Solar/Wind Helper
1.287
315697AD1-025 GEN
Solar/Wind Helper
4.277
316240AF1-291 C
Solar/Wind Helper
0.501
3146386ELIZ CT
Solar/Wind Helper
0.35
3142946ENON
Solar/Wind Helper
0.034
316487AF1-042 GEN
Solar/Wind Helper
0.339
3144356SAPONY
Solar/Wind Helper
0.597
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.305
316431W1029_GEN1
Solar/Wind Helper
1.295
316433W1029_GEN2
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
966871AG1-558 GEN
Solar/Wind Helper
0.403
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
316468AD1-105 GEN
Solar/Wind Helper
1.402
315742AE1-103 GEN
Solar/Wind Helper
0.368
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.064
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.115
3146802CHATHAM
Solar/Wind Harmer
0.108
941801AE2-185 GEN
Solar/Wind Harmer
4.622
270030AE2-140 GEN
Solar/Wind Harmer
14.688
3145543BTLEBRO
Solar/Wind Harmer
0.123
3145543BTLEBRO
Solar/Wind Harmer
0.099
316359AB2-059 GEN
Solar/Wind Harmer
0.442
316049AB1-081 GEN
Solar/Wind Harmer
0.704
3142053HEARTS
Solar/Wind Harmer
0.217
316294AC1-161 GEN
Solar/Wind Helper
8.153
316375AC2-012 GEN
Solar/Wind Helper
1.068
3145336SMITFLD
Solar/Wind Helper
1.575
316388AE2-253 GEN
Solar/Wind Helper
1.472
3146456SLIGO L269
Solar/Wind Helper
0.379
316381AD1-082 GEN
Solar/Wind Helper
1.955
316072AD1-144
Solar/Wind Helper
0.428
316246AF1-032 C
Solar/Wind Helper
0.424
316159AE1-175 C
Solar/Wind Helper
0.562
316458AB2-190 GEN2
Solar/Wind Helper
2.107
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.376
3138133OCRAN
Solar/Wind Helper
0.206
3142543TWELFTH
Solar/Wind Helper
0.032
964211AG1-282 GEN
Solar/Wind Helper
0.439
3141726DUNNSVL
Solar/Wind Helper
1.304
316337AD2-073 GEN
Solar/Wind Helper
0.478
3142416OLDCHRC
Solar/Wind Helper
0.816
3142416OLDCHRC
Solar/Wind Helper
0.312
3146516WINFALL
Solar/Wind Helper
1.016
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
3143226MDLTHAN
Solar/Wind Helper
0.3
315800Z1-036_GEN1
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3143873LANEXA
Solar/Wind Helper
0.206
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.137
3146486SUNBURY
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.341
316321Z2-027
Solar/Wind Helper
0.514
3145176PASQUOTANK
Solar/Wind Helper
0.209
316315AB2-025 C
Solar/Wind Helper
0.507
3141813NORNECK
Solar/Wind Helper
0.325
316312AB1-027
Solar/Wind Helper
0.597
316233AE1-074 FULL
Solar/Wind Helper
0.469
316223AC1-118
Solar/Wind Helper
0.466
315611Z1-036_GEN2
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
961601AG1-000A GEN
Solar/Wind Harmer
8.544
315773AC2-141 GEN
Solar/Wind Helper
9.595
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3145336SMITFLD
Solar/Wind Helper
0.157
315839AE2-212 C
Solar/Wind Helper
0.523
3146456SLIGO L269
Solar/Wind Helper
0.379
316382AG1-145 C
Solar/Wind Helper
0.498
316320Y1-086
Solar/Wind Helper
0.156
316156AD2-030 GEN
Solar/Wind Helper
0.525
316280AD1-041 GEN
Solar/Wind Helper
1.166
3142946ENON
Solar/Wind Helper
0.114
316484AD2-074 GEN
Solar/Wind Helper
0.648
316404AE1-155 C
Solar/Wind Helper
2.8
316435W1029_GEN3
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3141906WESTMOR
Solar/Wind Helper
0.122
316473AC1-191 GEN
Solar/Wind Helper
1.829
3146626S HERTFORD
Solar/Wind Helper
0.296
3145273HOLLAND
Solar/Wind Helper
0.201
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.24
LAGNLTFEXP_LAGN->PJM
CLTF
15.403
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.288
TVALTFEXP_TVA->PJM
CLTF
7.684
CPLELTFEXP_CPLE->PJM
CLTF
20.639
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.343
NYPJM->LTFIMP_NY
CLTF
2.484
LGEELTFEXP_LGEE->PJM
CLTF
2.833
WECLTFEXP_WEC->PJM
CLTF
1.482
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.447
MECLTFEXP_MEC->PJM
CLTF
7.78
SIGELTFEXP_SIGE->PJM
CLTF
0.233

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 58572_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 58572_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.04 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:6196.95
MW Contribution:18.41
Bus #Bus NameTypeMW Contribution
963041AG1-153 GEN
50/50
17.22
315244AE2-183_ST
50/50
18.443
3151541CLOVER2
50/50
10.593
3151611KERR 4
50/50
0.604
3151621KERR 5
50/50
0.604
3151631KERR 6
50/50
0.604
3151641KERR 7
50/50
0.604
971967AH1-528 GEN
Solar/Wind Harmer
144.6
970673AG2-436 GEN
Solar/Wind Harmer
152.413
970673AG2-436 GEN
Solar/Wind Harmer
77.171
941031AE2-094 GEN
Solar/Wind Harmer
136.017
944011AF1-069 GEN
Solar/Wind Harmer
42.619
970085AG2-068 GEN
Solar/Wind Harmer
42.331
970581AG2-369 GEN
Solar/Wind Harmer
36.404
3147173SINAI
Solar/Wind Harmer
-0.039
3147243WELCO
Solar/Wind Harmer
-0.024
316118AC1-105 GEN
Solar/Wind Harmer
2.575
970865AG2-541 GEN
Solar/Wind Harmer
13.323
316239AB2-077_GEN
Solar/Wind Harmer
0.978
316238AB2-078_GEN
Solar/Wind Harmer
0.978
971443AH1-215 GEN
Solar/Wind Harmer
6.159
3144303KENBRDG
Solar/Wind Harmer
-0.025
970683AG2-441 GEN
Solar/Wind Harmer
24.066
970681AG2-440 GEN
Solar/Wind Harmer
19.253
946301AF1-294 GEN
Solar/Wind Harmer
7.788
961791AG1-021 GEN
Solar/Wind Harmer
3.799
315657AE1-056 GEN
Solar/Wind Harmer
11.287
316123AC1-075 GEN
Solar/Wind Harmer
3.111
970165AG2-112 GEN
Solar/Wind Harmer
2.739
970163AG2-111 GEN
Solar/Wind Harmer
2.613
270455AD2-022 GEN
Solar/Wind Harmer
5.008
270457AD2-023 GEN
Solar/Wind Harmer
2.539
970831AG2-522 GEN
Solar/Wind Harmer
10.909
970285AG2-188 GEN
Solar/Wind Harmer
17.971
971845AH1-439 GEN
Solar/Wind Harmer
10.023
270069AE2-166 C O1
Solar/Wind Harmer
2.578
3143316POE
Solar/Wind Helper
1.64
319010AE1-072 C
Solar/Wind Helper
4.299
316369SG1_INVT
Solar/Wind Helper
1.8
316305AF2-043 C
Solar/Wind Helper
0.499
316132AB2-190 GEN1
Solar/Wind Helper
2.107
957831AF2-077 GEN
Solar/Wind Helper
0.495
316349AD2-085 GEN
Solar/Wind Helper
1.649
313526AB2-022
Solar/Wind Helper
0.533
957601AF2-054 GEN
Solar/Wind Helper
0.467
3141873WAN 176
Solar/Wind Helper
0.07
315662AE1-191 GEN
Solar/Wind Helper
1.865
315666AE1-190 GEN
Solar/Wind Helper
0.466
316059AD1-063 C
Solar/Wind Helper
0.348
3141913WHIT STONE
Solar/Wind Helper
0.345
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.137
3146486SUNBURY
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.341
316321Z2-027
Solar/Wind Helper
0.514
3145176PASQUOTANK
Solar/Wind Helper
0.209
316315AB2-025 C
Solar/Wind Helper
0.507
3141813NORNECK
Solar/Wind Helper
0.325
3151051BRUNSWICKS1
50/50
17.651
3151021BRUNSWICKG1
50/50
8.505
971451AH1-221 GEN
50/50
25.831
315243AE2-183_GT3
50/50
10.667
3151531CLOVER1
50/50
10.644
3151601KERR 3
50/50
0.604
3151581KERR 1
50/50
0.216
3144293JTRSVLE
50/50
0.914
971629AH1-314 GEN
50/50
19.06
3151561HALLBR1
50/50
0.404
970919AG2-571 GEN
Solar/Wind Harmer
21.586
970087AG2-069 GEN
Solar/Wind Harmer
63.496
957481AF2-042 GEN
Solar/Wind Harmer
190.536
315693AD1-088 GEN
Solar/Wind Harmer
27.811
962491AG1-098 GEN
Solar/Wind Harmer
36.654
315687AD1-152 GEN
Solar/Wind Harmer
6.022
316003AC1-222 GEN
Solar/Wind Harmer
3.575
970401AG2-262 GEN
Solar/Wind Harmer
2.352
316237AB2-079_GEN
Solar/Wind Harmer
0.978
970685AG2-442 GEN
Solar/Wind Harmer
26.954
963171AG1-166 GEN
Solar/Wind Harmer
3.799
971563AH1-280 GEN
Solar/Wind Harmer
3.799
3146926FARMVIL
Solar/Wind Harmer
-0.017
971065AG2-659 GEN
Solar/Wind Harmer
12.523
316129AC1-054 GEN
Solar/Wind Harmer
2.059
970223AG2-152 GEN
Solar/Wind Harmer
18.408
270016AE1-250 BESS
Solar/Wind Harmer
3.042
3147123OTTER R
Solar/Wind Harmer
-0.011
316322AB2-045
Solar/Wind Harmer
0.605
3146776BUCKING
Solar/Wind Harmer
-0.007
270574AD1-017 GEN2
Solar/Wind Harmer
5.998
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
941801AE2-185 GEN
Solar/Wind Harmer
6.086
270030AE2-140 GEN
Solar/Wind Harmer
21.053
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.864
316049AB1-081 GEN
Solar/Wind Harmer
1.492
3142053HEARTS
Solar/Wind Harmer
0.163
316294AC1-161 GEN
Solar/Wind Helper
8.153
316375AC2-012 GEN
Solar/Wind Helper
1.068
3145336SMITFLD
Solar/Wind Helper
1.575
316388AE2-253 GEN
Solar/Wind Helper
1.472
3146456SLIGO L269
Solar/Wind Helper
0.379
316381AD1-082 GEN
Solar/Wind Helper
1.955
316072AD1-144
Solar/Wind Helper
0.428
316246AF1-032 C
Solar/Wind Helper
0.424
316159AE1-175 C
Solar/Wind Helper
0.562
316458AB2-190 GEN2
Solar/Wind Helper
2.107
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.376
3138133OCRAN
Solar/Wind Helper
0.206
3142543TWELFTH
Solar/Wind Helper
0.032
964211AG1-282 GEN
Solar/Wind Helper
0.439
3141726DUNNSVL
Solar/Wind Helper
1.304
316337AD2-073 GEN
Solar/Wind Helper
0.478
3142416OLDCHRC
Solar/Wind Helper
0.816
3142416OLDCHRC
Solar/Wind Helper
0.312
3146516WINFALL
Solar/Wind Helper
1.016
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
3143226MDLTHAN
Solar/Wind Helper
0.3
315800Z1-036_GEN1
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3151041BRUNSWICKG3
50/50
8.505
972187AH1-678 GEN
50/50
19.517
315242AE2-183_GT2
50/50
10.667
315241AE2-183_GT1
50/50
10.602
972185AH1-677 GEN
50/50
38.457
970533AG2-339 GEN
50/50
57.391
970531AG2-338 GEN
50/50
22.956
3152661PLYWOOD A
50/50
0.751
970535AG2-341 GEN
50/50
5.149
3144293JTRSVLE
50/50
0.914
3144293JTRSVLE
50/50
0.769
970933AG2-581 GEN
Solar/Wind Harmer
67.863
970099AG2-077 GEN
Solar/Wind Harmer
76.214
971741AH1-377 GEN
Solar/Wind Harmer
50.609
970301AG2-198 GEN
Solar/Wind Harmer
19.968
3146843MT LREL
Solar/Wind Harmer
-0.036
3146843MT LREL
Solar/Wind Harmer
-0.036
964791AG1-342 GEN
Solar/Wind Harmer
7.699
962561AG1-105 GEN
Solar/Wind Harmer
19.948
316222AC1-221 GEN
Solar/Wind Harmer
3.472
939181AE1-148 GEN
Solar/Wind Harmer
18.394
313527AB2-043 GEN
Solar/Wind Harmer
5.237
970323AG2-213 GEN
Solar/Wind Harmer
15.625
971775AH1-396 GEN
Solar/Wind Harmer
2.225
316034AC1-036 C
Solar/Wind Harmer
0.579
958211AF2-115 GEN
Solar/Wind Harmer
4.748
963191AG1-168 GEN
Solar/Wind Harmer
2.849
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
942751AE2-291 GEN
Solar/Wind Harmer
16.78
270013AE1-250 PV
Solar/Wind Harmer
3.042
3146776BUCKING
Solar/Wind Harmer
-0.072
3146776BUCKING
Solar/Wind Harmer
-0.006
316217AC1-145 GEN
Solar/Wind Harmer
2.634
316197AC1-042 GEN
Solar/Wind Harmer
1.997
942671AE2-283 GEN
Solar/Wind Harmer
5.376
316263AC1-034 GEN
Solar/Wind Harmer
6.481
961601AG1-000A GEN
Solar/Wind Harmer
5.306
316036AC1-147 C
Solar/Wind Helper
0.621
3142956BIRDNECK
Solar/Wind Helper
0.272
316316AC1-027 C
Solar/Wind Helper
0.638
316185AD1-033 GEN
Solar/Wind Helper
1.893
3145506HICKORY
Solar/Wind Helper
1.587
3145506HICKORY
Solar/Wind Helper
0.952
3145506HICKORY
Solar/Wind Helper
0.238
316236AE1-162_GEN
Solar/Wind Helper
0.529
316339AD2-160 GEN
Solar/Wind Helper
1.472
316018AA1-139 ULT2
Solar/Wind Helper
1.65
316017AA1-139 ULT1
Solar/Wind Helper
1.754
3137176SLIGO L2192
Solar/Wind Helper
1.508
3130086AYDLETT
Solar/Wind Helper
1.498
316033AB2-134 GEN
Solar/Wind Helper
1.287
315697AD1-025 GEN
Solar/Wind Helper
4.277
316240AF1-291 C
Solar/Wind Helper
0.501
3146386ELIZ CT
Solar/Wind Helper
0.35
3142946ENON
Solar/Wind Helper
0.034
316487AF1-042 GEN
Solar/Wind Helper
0.339
3144356SAPONY
Solar/Wind Helper
0.597
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.305
316431W1029_GEN1
Solar/Wind Helper
1.295
316433W1029_GEN2
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
966871AG1-558 GEN
Solar/Wind Helper
0.403
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
316468AD1-105 GEN
Solar/Wind Helper
1.402
315742AE1-103 GEN
Solar/Wind Helper
0.368
3151031BRUNSWICKG2
50/50
8.505
970413AG2-270 GEN
50/50
46.449
3151591KERR 2
50/50
0.604
3144293JTRSVLE
50/50
0.914
970917AG2-570 GEN
Solar/Wind Harmer
170.53
316478AD1-087 GEN
Solar/Wind Harmer
4.831
316486AD2-202 GEN
Solar/Wind Harmer
1.415
970909AG2-566 GEN
Solar/Wind Harmer
3.791
316248AF1-058 C
Solar/Wind Harmer
1.169
960061AF2-297 GEN
Solar/Wind Harmer
19.391
971683AH1-343 GEN
Solar/Wind Harmer
14.982
316283AC2-100 C
Solar/Wind Harmer
3.205
316131AB2-060 GEN
Solar/Wind Harmer
3.471
964241AG1-285 GEN
Solar/Wind Harmer
24.911
315785AD2-033 C
Solar/Wind Harmer
7.122
970257AG2-171 GEN
Solar/Wind Harmer
11.718
959311AF2-222 GEN
Solar/Wind Harmer
32.481
963181AG1-167 GEN
Solar/Wind Harmer
2.849
3147133PAMPLIN
Solar/Wind Harmer
-0.094
971193AH1-056 GEN
Solar/Wind Harmer
18.811
942461AE2-259 GEN
Solar/Wind Harmer
4.399
3146926FARMVIL
Solar/Wind Harmer
-0.017
3146776BUCKING
Solar/Wind Harmer
-0.006
270018AE2-047 C O1
Solar/Wind Harmer
1.466
270197AD1-017 GEN1
Solar/Wind Harmer
1.802
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
6.086
943811AF1-049 GEN
Solar/Wind Harmer
4.09
270336AE1-100 GEN
Solar/Wind Harmer
1.669
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
5.373
315773AC2-141 GEN
Solar/Wind Helper
9.595
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3145336SMITFLD
Solar/Wind Helper
0.157
315839AE2-212 C
Solar/Wind Helper
0.523
3146456SLIGO L269
Solar/Wind Helper
0.379
316382AG1-145 C
Solar/Wind Helper
0.498
316320Y1-086
Solar/Wind Helper
0.156
316156AD2-030 GEN
Solar/Wind Helper
0.525
316280AD1-041 GEN
Solar/Wind Helper
1.166
3142946ENON
Solar/Wind Helper
0.114
316484AD2-074 GEN
Solar/Wind Helper
0.648
316404AE1-155 C
Solar/Wind Helper
2.8
316435W1029_GEN3
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3141906WESTMOR
Solar/Wind Helper
0.122
316473AC1-191 GEN
Solar/Wind Helper
1.829
3146626S HERTFORD
Solar/Wind Helper
0.296
3145273HOLLAND
Solar/Wind Helper
0.201
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.24
316312AB1-027
Solar/Wind Helper
0.597
316233AE1-074 FULL
Solar/Wind Helper
0.469
316223AC1-118
Solar/Wind Helper
0.466
315611Z1-036_GEN2
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
LAGNLTFEXP_LAGN->PJM
CLTF
15.403
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.288
TVALTFEXP_TVA->PJM
CLTF
7.684
CPLELTFEXP_CPLE->PJM
CLTF
20.639
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.343
NYPJM->LTFIMP_NY
CLTF
2.484
LGEELTFEXP_LGEE->PJM
CLTF
2.833
WECLTFEXP_WEC->PJM
CLTF
1.482
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.447
MECLTFEXP_MEC->PJM
CLTF
7.78
SIGELTFEXP_SIGE->PJM
CLTF
0.233

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-5: W72_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: W72_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.43 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:6166.56
MW Contribution:18.35
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
8.442
970413AG2-270 GEN
50/50
46.159
3151591KERR 2
50/50
0.604
3144293JTRSVLE
50/50
0.912
963041AG1-153 GEN
50/50
17.095
315244AE2-183_ST
50/50
18.308
3151541CLOVER2
50/50
10.527
3151611KERR 4
50/50
0.604
3151621KERR 5
50/50
0.604
3151631KERR 6
50/50
0.604
3151641KERR 7
50/50
0.604
971967AH1-528 GEN
Solar/Wind Harmer
143.519
970673AG2-436 GEN
Solar/Wind Harmer
151.3
970673AG2-436 GEN
Solar/Wind Harmer
76.608
941031AE2-094 GEN
Solar/Wind Harmer
135.024
944011AF1-069 GEN
Solar/Wind Harmer
42.308
970085AG2-068 GEN
Solar/Wind Harmer
42.031
970581AG2-369 GEN
Solar/Wind Harmer
36.147
3147173SINAI
Solar/Wind Harmer
-0.039
3147243WELCO
Solar/Wind Harmer
-0.024
316118AC1-105 GEN
Solar/Wind Harmer
2.567
970865AG2-541 GEN
Solar/Wind Harmer
13.271
316239AB2-077_GEN
Solar/Wind Harmer
0.98
316238AB2-078_GEN
Solar/Wind Harmer
0.98
971443AH1-215 GEN
Solar/Wind Harmer
6.158
3144303KENBRDG
Solar/Wind Harmer
-0.025
970683AG2-441 GEN
Solar/Wind Harmer
24.044
970681AG2-440 GEN
Solar/Wind Harmer
19.235
946301AF1-294 GEN
Solar/Wind Harmer
7.775
961791AG1-021 GEN
Solar/Wind Harmer
3.793
315657AE1-056 GEN
Solar/Wind Harmer
11.263
316123AC1-075 GEN
Solar/Wind Harmer
3.099
970165AG2-112 GEN
Solar/Wind Harmer
2.728
970163AG2-111 GEN
Solar/Wind Harmer
2.603
270455AD2-022 GEN
Solar/Wind Harmer
4.991
270457AD2-023 GEN
Solar/Wind Harmer
2.531
970831AG2-522 GEN
Solar/Wind Harmer
11.041
970285AG2-188 GEN
Solar/Wind Harmer
17.881
971845AH1-439 GEN
Solar/Wind Harmer
9.974
270069AE2-166 C O1
Solar/Wind Harmer
2.569
319010AE1-072 C
Solar/Wind Helper
4.32
3143316POE
Solar/Wind Helper
1.486
316305AF2-043 C
Solar/Wind Helper
0.5
316369SG1_INVT
Solar/Wind Helper
1.758
957831AF2-077 GEN
Solar/Wind Helper
0.492
316132AB2-190 GEN1
Solar/Wind Helper
2.041
316349AD2-085 GEN
Solar/Wind Helper
1.61
313526AB2-022
Solar/Wind Helper
0.535
957601AF2-054 GEN
Solar/Wind Helper
0.462
3141873WAN 176
Solar/Wind Helper
0.069
315662AE1-191 GEN
Solar/Wind Helper
1.844
315666AE1-190 GEN
Solar/Wind Helper
0.461
3146486SUNBURY
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.341
316059AD1-063 C
Solar/Wind Helper
0.344
3141913WHIT STONE
Solar/Wind Helper
0.341
3138133OCRAN
Solar/Wind Helper
0.102
3143873LANEXA
Solar/Wind Helper
0.203
3141783LANCAST
Solar/Wind Helper
0.203
3141783LANCAST
Solar/Wind Helper
0.135
316321Z2-027
Solar/Wind Helper
0.515
3145176PASQUOTANK
Solar/Wind Helper
0.209
3141813NORNECK
Solar/Wind Helper
0.321
316312AB1-027
Solar/Wind Helper
0.585
316223AC1-118
Solar/Wind Helper
0.461
316233AE1-074 FULL
Solar/Wind Helper
0.462
316315AB2-025 C
Solar/Wind Helper
0.44
315611Z1-036_GEN2
Solar/Wind Helper
1.494
3130156CHOWAN
Solar/Wind Helper
0.24
3130156CHOWAN
Solar/Wind Helper
0.24
3151041BRUNSWICKG3
50/50
8.442
972187AH1-678 GEN
50/50
19.374
315242AE2-183_GT2
50/50
10.589
315241AE2-183_GT1
50/50
10.524
972185AH1-677 GEN
50/50
38.176
970533AG2-339 GEN
50/50
56.972
970531AG2-338 GEN
50/50
22.789
3152661PLYWOOD A
50/50
0.749
970535AG2-341 GEN
50/50
5.154
3144293JTRSVLE
50/50
0.912
3144293JTRSVLE
50/50
0.768
970933AG2-581 GEN
Solar/Wind Harmer
67.369
970099AG2-077 GEN
Solar/Wind Harmer
75.708
971741AH1-377 GEN
Solar/Wind Harmer
50.305
970301AG2-198 GEN
Solar/Wind Harmer
19.85
3146843MT LREL
Solar/Wind Harmer
-0.036
3146843MT LREL
Solar/Wind Harmer
-0.036
964791AG1-342 GEN
Solar/Wind Harmer
7.683
962561AG1-105 GEN
Solar/Wind Harmer
19.916
316222AC1-221 GEN
Solar/Wind Harmer
3.458
939181AE1-148 GEN
Solar/Wind Harmer
18.413
313527AB2-043 GEN
Solar/Wind Harmer
5.244
970323AG2-213 GEN
Solar/Wind Harmer
15.621
971775AH1-396 GEN
Solar/Wind Harmer
2.225
316034AC1-036 C
Solar/Wind Harmer
0.579
958211AF2-115 GEN
Solar/Wind Harmer
4.741
963191AG1-168 GEN
Solar/Wind Harmer
2.845
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
942751AE2-291 GEN
Solar/Wind Harmer
16.715
270013AE1-250 PV
Solar/Wind Harmer
3.032
3146776BUCKING
Solar/Wind Harmer
-0.071
3146776BUCKING
Solar/Wind Harmer
-0.006
316217AC1-145 GEN
Solar/Wind Harmer
2.625
316197AC1-042 GEN
Solar/Wind Harmer
1.99
942671AE2-283 GEN
Solar/Wind Harmer
5.357
316263AC1-034 GEN
Solar/Wind Harmer
6.638
961601AG1-000A GEN
Solar/Wind Harmer
5.443
316036AC1-147 C
Solar/Wind Helper
0.624
3142956BIRDNECK
Solar/Wind Helper
0.274
316316AC1-027 C
Solar/Wind Helper
0.642
316185AD1-033 GEN
Solar/Wind Helper
1.905
3145506HICKORY
Solar/Wind Helper
1.596
3145506HICKORY
Solar/Wind Helper
0.958
3145506HICKORY
Solar/Wind Helper
0.239
316236AE1-162_GEN
Solar/Wind Helper
0.527
316339AD2-160 GEN
Solar/Wind Helper
1.48
316018AA1-139 ULT2
Solar/Wind Helper
1.659
316017AA1-139 ULT1
Solar/Wind Helper
1.763
3137176SLIGO L2192
Solar/Wind Helper
1.516
3130086AYDLETT
Solar/Wind Helper
1.505
316033AB2-134 GEN
Solar/Wind Helper
1.257
315697AD1-025 GEN
Solar/Wind Helper
4.177
3146386ELIZ CT
Solar/Wind Helper
0.351
316240AF1-291 C
Solar/Wind Helper
0.468
3142946ENON
Solar/Wind Helper
0.033
316487AF1-042 GEN
Solar/Wind Helper
0.335
316075AC2-137 C
Solar/Wind Helper
0.492
316077AC2-138 C
Solar/Wind Helper
0.302
316431W1029_GEN1
Solar/Wind Helper
1.297
316433W1029_GEN2
Solar/Wind Helper
1.297
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.573
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
966871AG1-558 GEN
Solar/Wind Helper
0.394
3144356SAPONY
Solar/Wind Helper
0.518
316468AD1-105 GEN
Solar/Wind Helper
1.373
315742AE1-103 GEN
Solar/Wind Helper
0.362
3151051BRUNSWICKS1
50/50
17.522
3151021BRUNSWICKG1
50/50
8.442
971451AH1-221 GEN
50/50
25.642
315243AE2-183_GT3
50/50
10.589
3151531CLOVER1
50/50
10.578
3151601KERR 3
50/50
0.604
3151581KERR 1
50/50
0.216
3144293JTRSVLE
50/50
0.912
971629AH1-314 GEN
50/50
18.997
3151561HALLBR1
50/50
0.403
970919AG2-571 GEN
Solar/Wind Harmer
21.433
970087AG2-069 GEN
Solar/Wind Harmer
63.047
957481AF2-042 GEN
Solar/Wind Harmer
189.269
315693AD1-088 GEN
Solar/Wind Harmer
27.634
962491AG1-098 GEN
Solar/Wind Harmer
36.422
315687AD1-152 GEN
Solar/Wind Harmer
5.988
316003AC1-222 GEN
Solar/Wind Harmer
3.561
970401AG2-262 GEN
Solar/Wind Harmer
2.348
316237AB2-079_GEN
Solar/Wind Harmer
0.98
970685AG2-442 GEN
Solar/Wind Harmer
26.929
963171AG1-166 GEN
Solar/Wind Harmer
3.793
971563AH1-280 GEN
Solar/Wind Harmer
3.793
3146926FARMVIL
Solar/Wind Harmer
-0.017
971065AG2-659 GEN
Solar/Wind Harmer
12.621
316129AC1-054 GEN
Solar/Wind Harmer
2.079
970223AG2-152 GEN
Solar/Wind Harmer
18.347
270016AE1-250 BESS
Solar/Wind Harmer
3.032
3147123OTTER R
Solar/Wind Harmer
-0.011
316322AB2-045
Solar/Wind Harmer
0.602
3146776BUCKING
Solar/Wind Harmer
-0.007
270574AD1-017 GEN2
Solar/Wind Harmer
5.978
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
941801AE2-185 GEN
Solar/Wind Harmer
6.064
270030AE2-140 GEN
Solar/Wind Harmer
20.984
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.909
316049AB1-081 GEN
Solar/Wind Harmer
1.528
3142053HEARTS
Solar/Wind Harmer
0.166
316294AC1-161 GEN
Solar/Wind Helper
8.246
316375AC2-012 GEN
Solar/Wind Helper
1.074
3145336SMITFLD
Solar/Wind Helper
1.568
316388AE2-253 GEN
Solar/Wind Helper
1.48
3146456SLIGO L269
Solar/Wind Helper
0.38
316072AD1-144
Solar/Wind Helper
0.428
316246AF1-032 C
Solar/Wind Helper
0.426
316159AE1-175 C
Solar/Wind Helper
0.559
316381AD1-082 GEN
Solar/Wind Helper
1.857
316458AB2-190 GEN2
Solar/Wind Helper
2.041
3141766HARMONY
Solar/Wind Helper
0.068
3138133OCRAN
Solar/Wind Helper
0.204
3142433PROV 92
Solar/Wind Helper
1.345
3142543TWELFTH
Solar/Wind Helper
0.031
964211AG1-282 GEN
Solar/Wind Helper
0.434
3141726DUNNSVL
Solar/Wind Helper
1.289
3146516WINFALL
Solar/Wind Helper
1.017
3146516WINFALL
Solar/Wind Helper
0.314
316337AD2-073 GEN
Solar/Wind Helper
0.473
3142416OLDCHRC
Solar/Wind Helper
0.799
3142416OLDCHRC
Solar/Wind Helper
0.306
3143526WINTERP
Solar/Wind Helper
1.573
3143226MDLTHAN
Solar/Wind Helper
0.298
315800Z1-036_GEN1
Solar/Wind Helper
1.494
3130156CHOWAN
Solar/Wind Helper
0.24
970917AG2-570 GEN
Solar/Wind Harmer
169.32
316478AD1-087 GEN
Solar/Wind Harmer
4.801
316486AD2-202 GEN
Solar/Wind Harmer
1.406
970909AG2-566 GEN
Solar/Wind Harmer
3.769
316248AF1-058 C
Solar/Wind Harmer
1.164
960061AF2-297 GEN
Solar/Wind Harmer
19.314
971683AH1-343 GEN
Solar/Wind Harmer
14.923
316283AC2-100 C
Solar/Wind Harmer
3.192
316131AB2-060 GEN
Solar/Wind Harmer
3.475
964241AG1-285 GEN
Solar/Wind Harmer
24.93
315785AD2-033 C
Solar/Wind Harmer
7.122
970257AG2-171 GEN
Solar/Wind Harmer
11.716
959311AF2-222 GEN
Solar/Wind Harmer
32.468
963181AG1-167 GEN
Solar/Wind Harmer
2.845
3147133PAMPLIN
Solar/Wind Harmer
-0.094
971193AH1-056 GEN
Solar/Wind Harmer
18.772
942461AE2-259 GEN
Solar/Wind Harmer
4.384
3146926FARMVIL
Solar/Wind Harmer
-0.017
3146776BUCKING
Solar/Wind Harmer
-0.006
270018AE2-047 C O1
Solar/Wind Harmer
1.461
270197AD1-017 GEN1
Solar/Wind Harmer
1.796
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
6.064
943811AF1-049 GEN
Solar/Wind Harmer
4.077
270336AE1-100 GEN
Solar/Wind Harmer
1.664
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
5.512
3138543CONSLDL
Solar/Wind Harmer
-0.008
315773AC2-141 GEN
Solar/Wind Helper
9.706
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3145336SMITFLD
Solar/Wind Helper
0.157
3146456SLIGO L269
Solar/Wind Helper
0.38
316382AG1-145 C
Solar/Wind Helper
0.496
315839AE2-212 C
Solar/Wind Helper
0.483
316320Y1-086
Solar/Wind Helper
0.157
316156AD2-030 GEN
Solar/Wind Helper
0.52
316280AD1-041 GEN
Solar/Wind Helper
1.152
3142946ENON
Solar/Wind Helper
0.111
316484AD2-074 GEN
Solar/Wind Helper
0.641
316404AE1-155 C
Solar/Wind Helper
2.769
316435W1029_GEN3
Solar/Wind Helper
1.297
3146516WINFALL
Solar/Wind Helper
0.314
3141906WESTMOR
Solar/Wind Helper
0.121
3146626S HERTFORD
Solar/Wind Helper
0.296
316473AC1-191 GEN
Solar/Wind Helper
1.785
3145273HOLLAND
Solar/Wind Helper
0.198
966881AG1-559 GEN
Solar/Wind Helper
0.346
3146376EDENTON
Solar/Wind Helper
0.239
LAGNLTFEXP_LAGN->PJM
CLTF
15.349
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.145
TVALTFEXP_TVA->PJM
CLTF
7.657
CPLELTFEXP_CPLE->PJM
CLTF
20.587
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.048
NYPJM->LTFIMP_NY
CLTF
2.481
LGEELTFEXP_LGEE->PJM
CLTF
2.822
WECLTFEXP_WEC->PJM
CLTF
1.476
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.486
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.354
MECLTFEXP_MEC->PJM
CLTF
7.751
SIGELTFEXP_SIGE->PJM
CLTF
0.232

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: XT585_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: XT585_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.16 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5703.66
MW Contribution:18.41
Bus #Bus NameTypeMW Contribution
3151051BRUNSWICKS1
50/50
17.651
3151021BRUNSWICKG1
50/50
8.505
971451AH1-221 GEN
50/50
25.831
315243AE2-183_GT3
50/50
10.667
3151531CLOVER1
50/50
10.644
3151601KERR 3
50/50
0.604
3151581KERR 1
50/50
0.216
3144293JTRSVLE
50/50
0.914
971629AH1-314 GEN
50/50
19.06
3151561HALLBR1
50/50
0.404
970919AG2-571 GEN
Solar/Wind Harmer
21.586
970087AG2-069 GEN
Solar/Wind Harmer
63.496
957481AF2-042 GEN
Solar/Wind Harmer
190.536
315693AD1-088 GEN
Solar/Wind Harmer
27.811
962491AG1-098 GEN
Solar/Wind Harmer
36.654
315687AD1-152 GEN
Solar/Wind Harmer
6.022
316003AC1-222 GEN
Solar/Wind Harmer
3.575
970401AG2-262 GEN
Solar/Wind Harmer
2.352
316237AB2-079_GEN
Solar/Wind Harmer
0.978
970685AG2-442 GEN
Solar/Wind Harmer
26.954
963171AG1-166 GEN
Solar/Wind Harmer
3.799
971563AH1-280 GEN
Solar/Wind Harmer
3.799
3146926FARMVIL
Solar/Wind Harmer
-0.017
971065AG2-659 GEN
Solar/Wind Harmer
12.523
316129AC1-054 GEN
Solar/Wind Harmer
2.059
963041AG1-153 GEN
50/50
17.22
315244AE2-183_ST
50/50
18.443
3151541CLOVER2
50/50
10.593
3151611KERR 4
50/50
0.604
3151621KERR 5
50/50
0.604
3151631KERR 6
50/50
0.604
3151641KERR 7
50/50
0.604
971967AH1-528 GEN
Solar/Wind Harmer
144.6
970085AG2-068 GEN
Solar/Wind Harmer
42.331
970581AG2-369 GEN
Solar/Wind Harmer
36.404
3147173SINAI
Solar/Wind Harmer
-0.039
3147243WELCO
Solar/Wind Harmer
-0.024
316118AC1-105 GEN
Solar/Wind Harmer
2.575
970865AG2-541 GEN
Solar/Wind Harmer
13.323
316239AB2-077_GEN
Solar/Wind Harmer
0.978
316238AB2-078_GEN
Solar/Wind Harmer
0.978
971443AH1-215 GEN
Solar/Wind Harmer
6.159
3144303KENBRDG
Solar/Wind Harmer
-0.025
970683AG2-441 GEN
Solar/Wind Harmer
24.066
970681AG2-440 GEN
Solar/Wind Harmer
19.253
946301AF1-294 GEN
Solar/Wind Harmer
7.788
961791AG1-021 GEN
Solar/Wind Harmer
3.799
315657AE1-056 GEN
Solar/Wind Harmer
11.287
970223AG2-152 GEN
Solar/Wind Harmer
18.408
270016AE1-250 BESS
Solar/Wind Harmer
3.042
3147123OTTER R
Solar/Wind Harmer
-0.011
316322AB2-045
Solar/Wind Harmer
0.605
3146776BUCKING
Solar/Wind Harmer
-0.007
270574AD1-017 GEN2
Solar/Wind Harmer
5.998
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
941801AE2-185 GEN
Solar/Wind Harmer
6.086
270030AE2-140 GEN
Solar/Wind Harmer
21.053
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.864
316049AB1-081 GEN
Solar/Wind Harmer
1.492
3142053HEARTS
Solar/Wind Harmer
0.163
316294AC1-161 GEN
Solar/Wind Helper
8.153
316375AC2-012 GEN
Solar/Wind Helper
1.068
3145336SMITFLD
Solar/Wind Helper
1.575
316388AE2-253 GEN
Solar/Wind Helper
1.472
3146456SLIGO L269
Solar/Wind Helper
0.379
316381AD1-082 GEN
Solar/Wind Helper
1.955
316072AD1-144
Solar/Wind Helper
0.428
316246AF1-032 C
Solar/Wind Helper
0.424
316159AE1-175 C
Solar/Wind Helper
0.562
316458AB2-190 GEN2
Solar/Wind Helper
2.107
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.376
3138133OCRAN
Solar/Wind Helper
0.206
3142543TWELFTH
Solar/Wind Helper
0.032
964211AG1-282 GEN
Solar/Wind Helper
0.439
3141726DUNNSVL
Solar/Wind Helper
1.304
316337AD2-073 GEN
Solar/Wind Helper
0.478
3142416OLDCHRC
Solar/Wind Helper
0.816
3142416OLDCHRC
Solar/Wind Helper
0.312
3146516WINFALL
Solar/Wind Helper
1.016
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
3143226MDLTHAN
Solar/Wind Helper
0.3
315800Z1-036_GEN1
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3151041BRUNSWICKG3
50/50
8.505
972187AH1-678 GEN
50/50
19.517
315242AE2-183_GT2
50/50
10.667
315241AE2-183_GT1
50/50
10.602
972185AH1-677 GEN
50/50
38.457
3152661PLYWOOD A
50/50
0.751
970535AG2-341 GEN
50/50
5.149
3144293JTRSVLE
50/50
0.914
3144293JTRSVLE
50/50
0.769
970933AG2-581 GEN
Solar/Wind Harmer
67.863
970099AG2-077 GEN
Solar/Wind Harmer
76.214
971741AH1-377 GEN
Solar/Wind Harmer
50.609
970301AG2-198 GEN
Solar/Wind Harmer
19.968
3146843MT LREL
Solar/Wind Harmer
-0.036
3146843MT LREL
Solar/Wind Harmer
-0.036
964791AG1-342 GEN
Solar/Wind Harmer
7.699
962561AG1-105 GEN
Solar/Wind Harmer
19.948
316222AC1-221 GEN
Solar/Wind Harmer
3.472
939181AE1-148 GEN
Solar/Wind Harmer
18.394
313527AB2-043 GEN
Solar/Wind Harmer
5.237
970323AG2-213 GEN
Solar/Wind Harmer
15.625
971775AH1-396 GEN
Solar/Wind Harmer
2.225
316034AC1-036 C
Solar/Wind Harmer
0.579
958211AF2-115 GEN
Solar/Wind Harmer
4.748
963191AG1-168 GEN
Solar/Wind Harmer
2.849
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
942751AE2-291 GEN
Solar/Wind Harmer
16.78
270013AE1-250 PV
Solar/Wind Harmer
3.042
3146776BUCKING
Solar/Wind Harmer
-0.072
3146776BUCKING
Solar/Wind Harmer
-0.006
316217AC1-145 GEN
Solar/Wind Harmer
2.634
316197AC1-042 GEN
Solar/Wind Harmer
1.997
942671AE2-283 GEN
Solar/Wind Harmer
5.376
316263AC1-034 GEN
Solar/Wind Harmer
6.481
961601AG1-000A GEN
Solar/Wind Harmer
5.306
316036AC1-147 C
Solar/Wind Helper
0.621
3142956BIRDNECK
Solar/Wind Helper
0.272
316316AC1-027 C
Solar/Wind Helper
0.638
316185AD1-033 GEN
Solar/Wind Helper
1.893
3145506HICKORY
Solar/Wind Helper
1.587
3145506HICKORY
Solar/Wind Helper
0.952
3145506HICKORY
Solar/Wind Helper
0.238
316236AE1-162_GEN
Solar/Wind Helper
0.529
316339AD2-160 GEN
Solar/Wind Helper
1.472
316018AA1-139 ULT2
Solar/Wind Helper
1.65
316017AA1-139 ULT1
Solar/Wind Helper
1.754
3137176SLIGO L2192
Solar/Wind Helper
1.508
3130086AYDLETT
Solar/Wind Helper
1.498
316033AB2-134 GEN
Solar/Wind Helper
1.287
315697AD1-025 GEN
Solar/Wind Helper
4.277
316240AF1-291 C
Solar/Wind Helper
0.501
3146386ELIZ CT
Solar/Wind Helper
0.35
3142946ENON
Solar/Wind Helper
0.034
316487AF1-042 GEN
Solar/Wind Helper
0.339
3144356SAPONY
Solar/Wind Helper
0.597
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.305
316431W1029_GEN1
Solar/Wind Helper
1.295
316433W1029_GEN2
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
966871AG1-558 GEN
Solar/Wind Helper
0.403
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
316468AD1-105 GEN
Solar/Wind Helper
1.402
315742AE1-103 GEN
Solar/Wind Helper
0.368
316123AC1-075 GEN
Solar/Wind Harmer
3.111
970165AG2-112 GEN
Solar/Wind Harmer
2.739
970163AG2-111 GEN
Solar/Wind Harmer
2.613
270455AD2-022 GEN
Solar/Wind Harmer
5.008
270457AD2-023 GEN
Solar/Wind Harmer
2.539
970831AG2-522 GEN
Solar/Wind Harmer
10.909
970285AG2-188 GEN
Solar/Wind Harmer
17.971
971845AH1-439 GEN
Solar/Wind Harmer
10.023
270069AE2-166 C O1
Solar/Wind Harmer
2.578
3143316POE
Solar/Wind Helper
1.64
319010AE1-072 C
Solar/Wind Helper
4.299
316369SG1_INVT
Solar/Wind Helper
1.8
316305AF2-043 C
Solar/Wind Helper
0.499
316132AB2-190 GEN1
Solar/Wind Helper
2.107
957831AF2-077 GEN
Solar/Wind Helper
0.495
316349AD2-085 GEN
Solar/Wind Helper
1.649
313526AB2-022
Solar/Wind Helper
0.533
957601AF2-054 GEN
Solar/Wind Helper
0.467
3141873WAN 176
Solar/Wind Helper
0.07
315662AE1-191 GEN
Solar/Wind Helper
1.865
315666AE1-190 GEN
Solar/Wind Helper
0.466
316059AD1-063 C
Solar/Wind Helper
0.348
3141913WHIT STONE
Solar/Wind Helper
0.345
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.137
3146486SUNBURY
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.341
316321Z2-027
Solar/Wind Helper
0.514
3145176PASQUOTANK
Solar/Wind Helper
0.209
316315AB2-025 C
Solar/Wind Helper
0.507
3141813NORNECK
Solar/Wind Helper
0.325
316312AB1-027
Solar/Wind Helper
0.597
316233AE1-074 FULL
Solar/Wind Helper
0.469
316223AC1-118
Solar/Wind Helper
0.466
315611Z1-036_GEN2
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
3151031BRUNSWICKG2
50/50
8.505
970413AG2-270 GEN
50/50
46.449
3151591KERR 2
50/50
0.604
3144293JTRSVLE
50/50
0.914
970917AG2-570 GEN
Solar/Wind Harmer
170.53
316478AD1-087 GEN
Solar/Wind Harmer
4.831
316486AD2-202 GEN
Solar/Wind Harmer
1.415
970909AG2-566 GEN
Solar/Wind Harmer
3.791
316248AF1-058 C
Solar/Wind Harmer
1.169
960061AF2-297 GEN
Solar/Wind Harmer
19.391
971683AH1-343 GEN
Solar/Wind Harmer
14.982
316283AC2-100 C
Solar/Wind Harmer
3.205
316131AB2-060 GEN
Solar/Wind Harmer
3.471
964241AG1-285 GEN
Solar/Wind Harmer
24.911
315785AD2-033 C
Solar/Wind Harmer
7.122
970257AG2-171 GEN
Solar/Wind Harmer
11.718
959311AF2-222 GEN
Solar/Wind Harmer
32.481
963181AG1-167 GEN
Solar/Wind Harmer
2.849
3147133PAMPLIN
Solar/Wind Harmer
-0.094
971193AH1-056 GEN
Solar/Wind Harmer
18.811
942461AE2-259 GEN
Solar/Wind Harmer
4.399
3146926FARMVIL
Solar/Wind Harmer
-0.017
3146776BUCKING
Solar/Wind Harmer
-0.006
270018AE2-047 C O1
Solar/Wind Harmer
1.466
270197AD1-017 GEN1
Solar/Wind Harmer
1.802
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
6.086
943811AF1-049 GEN
Solar/Wind Harmer
4.09
270336AE1-100 GEN
Solar/Wind Harmer
1.669
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
5.373
315773AC2-141 GEN
Solar/Wind Helper
9.595
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3145336SMITFLD
Solar/Wind Helper
0.157
315839AE2-212 C
Solar/Wind Helper
0.523
3146456SLIGO L269
Solar/Wind Helper
0.379
316382AG1-145 C
Solar/Wind Helper
0.498
316320Y1-086
Solar/Wind Helper
0.156
316156AD2-030 GEN
Solar/Wind Helper
0.525
316280AD1-041 GEN
Solar/Wind Helper
1.166
3142946ENON
Solar/Wind Helper
0.114
316484AD2-074 GEN
Solar/Wind Helper
0.648
316404AE1-155 C
Solar/Wind Helper
2.8
316435W1029_GEN3
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3141906WESTMOR
Solar/Wind Helper
0.122
316473AC1-191 GEN
Solar/Wind Helper
1.829
3146626S HERTFORD
Solar/Wind Helper
0.296
3145273HOLLAND
Solar/Wind Helper
0.201
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.24
LAGNLTFEXP_LAGN->PJM
CLTF
15.403
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.288
TVALTFEXP_TVA->PJM
CLTF
7.684
CPLELTFEXP_CPLE->PJM
CLTF
20.639
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.343
NYPJM->LTFIMP_NY
CLTF
2.484
LGEELTFEXP_LGEE->PJM
CLTF
2.833
WECLTFEXP_WEC->PJM
CLTF
1.482
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.447
MECLTFEXP_MEC->PJM
CLTF
7.78
SIGELTFEXP_SIGE->PJM
CLTF
0.233

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 54472_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 54472_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.74 %
Rating:2858.0 MVA
Rating Type:C
MVA to Mitigate:3193.49
MW Contribution:11.34
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
7.968
3151051BRUNSWICKS1
50/50
8.574
3151021BRUNSWICKG1
50/50
4.131
971451AH1-221 GEN
50/50
12.548
315243AE2-183_GT3
50/50
3.874
3151601KERR 3
50/50
0.44
3151581KERR 1
50/50
0.157
3144293JTRSVLE
50/50
0.691
971629AH1-314 GEN
50/50
11.594
957481AF2-042 GEN
Solar/Wind Harmer
144.035
315693AD1-088 GEN
Solar/Wind Harmer
21.036
962491AG1-098 GEN
Solar/Wind Harmer
27.737
315687AD1-152 GEN
Solar/Wind Harmer
4.411
3151041BRUNSWICKG3
50/50
4.131
972187AH1-678 GEN
50/50
9.481
3152661PLYWOOD A
50/50
0.538
315242AE2-183_GT2
50/50
3.874
315241AE2-183_GT1
50/50
3.85
972185AH1-677 GEN
50/50
13.967
970535AG2-341 GEN
50/50
3.778
3144293JTRSVLE
50/50
0.691
3144293JTRSVLE
50/50
0.582
970933AG2-581 GEN
Solar/Wind Harmer
51.852
970099AG2-077 GEN
Solar/Wind Harmer
57.614
971741AH1-377 GEN
Solar/Wind Harmer
38.586
970301AG2-198 GEN
Solar/Wind Harmer
15.274
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
964791AG1-342 GEN
Solar/Wind Harmer
5.564
962561AG1-105 GEN
Solar/Wind Harmer
14.462
939181AE1-148 GEN
Solar/Wind Harmer
13.444
313527AB2-043 GEN
Solar/Wind Harmer
3.87
970323AG2-213 GEN
Solar/Wind Harmer
11.685
971775AH1-396 GEN
Solar/Wind Harmer
1.664
316034AC1-036 C
Solar/Wind Harmer
0.433
958211AF2-115 GEN
Solar/Wind Harmer
3.59
963191AG1-168 GEN
Solar/Wind Harmer
2.154
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
316222AC1-221 GEN
Solar/Wind Harmer
2.218
942751AE2-291 GEN
Solar/Wind Harmer
11.754
3146776BUCKING
Solar/Wind Harmer
-0.058
3146776BUCKING
Solar/Wind Harmer
-0.005
316240AF1-291 C
Solar/Wind Helper
0.299
3151541CLOVER2
50/50
7.93
963041AG1-153 GEN
50/50
8.365
315244AE2-183_ST
50/50
6.698
3151611KERR 4
50/50
0.44
3151621KERR 5
50/50
0.44
3151631KERR 6
50/50
0.44
3151641KERR 7
50/50
0.44
971967AH1-528 GEN
Solar/Wind Harmer
110.812
970085AG2-068 GEN
Solar/Wind Harmer
20.738
970581AG2-369 GEN
Solar/Wind Harmer
17.835
3147173SINAI
Solar/Wind Harmer
-0.028
3147243WELCO
Solar/Wind Harmer
-0.017
316118AC1-105 GEN
Solar/Wind Harmer
1.848
316239AB2-077_GEN
Solar/Wind Harmer
0.722
316238AB2-078_GEN
Solar/Wind Harmer
0.722
971443AH1-215 GEN
Solar/Wind Harmer
4.604
3144303KENBRDG
Solar/Wind Harmer
-0.019
970865AG2-541 GEN
Solar/Wind Harmer
9.435
970683AG2-441 GEN
Solar/Wind Harmer
18.098
970919AG2-571 GEN
Solar/Wind Harmer
10.566
970087AG2-069 GEN
Solar/Wind Harmer
31.107
970401AG2-262 GEN
Solar/Wind Harmer
1.7
316003AC1-222 GEN
Solar/Wind Harmer
2.544
316237AB2-079_GEN
Solar/Wind Harmer
0.722
970685AG2-442 GEN
Solar/Wind Harmer
20.27
963171AG1-166 GEN
Solar/Wind Harmer
2.872
971563AH1-280 GEN
Solar/Wind Harmer
2.872
3146926FARMVIL
Solar/Wind Harmer
-0.013
971065AG2-659 GEN
Solar/Wind Harmer
9.218
316129AC1-054 GEN
Solar/Wind Harmer
1.52
316322AB2-045
Solar/Wind Harmer
0.488
3146776BUCKING
Solar/Wind Harmer
-0.006
970223AG2-152 GEN
Solar/Wind Harmer
11.343
316294AC1-161 GEN
Solar/Wind Helper
4.653
970413AG2-270 GEN
50/50
34.77
3151031BRUNSWICKG2
50/50
4.131
3151591KERR 2
50/50
0.44
3144293JTRSVLE
50/50
0.691
316478AD1-087 GEN
Solar/Wind Harmer
3.615
316486AD2-202 GEN
Solar/Wind Harmer
1.059
970917AG2-570 GEN
Solar/Wind Harmer
83.468
970909AG2-566 GEN
Solar/Wind Harmer
2.9
316248AF1-058 C
Solar/Wind Harmer
0.833
960061AF2-297 GEN
Solar/Wind Harmer
13.826
971683AH1-343 GEN
Solar/Wind Harmer
10.636
316131AB2-060 GEN
Solar/Wind Harmer
2.567
964241AG1-285 GEN
Solar/Wind Harmer
18.486
315785AD2-033 C
Solar/Wind Harmer
5.315
970257AG2-171 GEN
Solar/Wind Harmer
8.764
959311AF2-222 GEN
Solar/Wind Harmer
24.33
963181AG1-167 GEN
Solar/Wind Harmer
2.154
970681AG2-440 GEN
Solar/Wind Harmer
14.478
946301AF1-294 GEN
Solar/Wind Harmer
5.887
961791AG1-021 GEN
Solar/Wind Harmer
2.872
315657AE1-056 GEN
Solar/Wind Harmer
8.565
316123AC1-075 GEN
Solar/Wind Harmer
2.19
970165AG2-112 GEN
Solar/Wind Harmer
1.928
970163AG2-111 GEN
Solar/Wind Harmer
1.839
970673AG2-436 GEN
Solar/Wind Harmer
40.956
970673AG2-436 GEN
Solar/Wind Harmer
20.737
270455AD2-022 GEN
Solar/Wind Harmer
3.036
270457AD2-023 GEN
Solar/Wind Harmer
1.539
970285AG2-188 GEN
Solar/Wind Harmer
14.324
970831AG2-522 GEN
Solar/Wind Harmer
8.077
971845AH1-439 GEN
Solar/Wind Harmer
8.053
3143316POE
Solar/Wind Helper
1.004
3147133PAMPLIN
Solar/Wind Harmer
-0.071
971193AH1-056 GEN
Solar/Wind Harmer
14.275
942461AE2-259 GEN
Solar/Wind Harmer
3.375
3146926FARMVIL
Solar/Wind Harmer
-0.013
316283AC2-100 C
Solar/Wind Harmer
2.04
3146776BUCKING
Solar/Wind Harmer
-0.005
315773AC2-141 GEN
Solar/Wind Helper
5.476
315839AE2-212 C
Solar/Wind Helper
0.317
LAGNLTFEXP_LAGN->PJM
CLTF
8.928
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.434
TVALTFEXP_TVA->PJM
CLTF
4.461
CPLELTFEXP_CPLE->PJM
CLTF
11.786
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.116
NYPJM->LTFIMP_NY
CLTF
1.417
LGEELTFEXP_LGEE->PJM
CLTF
1.692
WECLTFEXP_WEC->PJM
CLTF
0.884
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.523
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.401
MECLTFEXP_MEC->PJM
CLTF
4.601
SIGELTFEXP_SIGE->PJM
CLTF
0.139

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.06 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5008.65
MW Contribution:12.09
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
44.982
970099AG2-077 GEN
Solar/Wind Harmer
50.723
971741AH1-377 GEN
Solar/Wind Harmer
33.569
970301AG2-198 GEN
Solar/Wind Harmer
13.228
3146843MT LREL
Solar/Wind Harmer
0.286
3146843MT LREL
Solar/Wind Harmer
0.286
964791AG1-342 GEN
Solar/Wind Harmer
5.488
316222AC1-221 GEN
Solar/Wind Harmer
1.175
962561AG1-105 GEN
Solar/Wind Harmer
13.485
939181AE1-148 GEN
Solar/Wind Harmer
12.41
313527AB2-043 GEN
Solar/Wind Harmer
0.003
970323AG2-213 GEN
Solar/Wind Harmer
10.445
971775AH1-396 GEN
Solar/Wind Harmer
0.392
316034AC1-036 C
Solar/Wind Harmer
0.018
958211AF2-115 GEN
Solar/Wind Harmer
2.845
963191AG1-168 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.234
3147133PAMPLIN
Solar/Wind Harmer
0.187
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
47.73
957481AF2-042 GEN
Solar/Wind Harmer
126.807
315693AD1-088 GEN
Solar/Wind Harmer
20.818
962491AG1-098 GEN
Solar/Wind Harmer
24.385
315687AD1-152 GEN
Solar/Wind Harmer
0.013
316003AC1-222 GEN
Solar/Wind Harmer
0.008
970401AG2-262 GEN
Solar/Wind Harmer
1.677
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
17.979
963171AG1-166 GEN
Solar/Wind Harmer
1.264
971563AH1-280 GEN
Solar/Wind Harmer
2.529
3146926FARMVIL
Solar/Wind Harmer
0.131
971065AG2-659 GEN
Solar/Wind Harmer
8.445
316129AC1-054 GEN
Solar/Wind Harmer
0.698
970223AG2-152 GEN
Solar/Wind Harmer
12.094
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.088
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
971967AH1-528 GEN
Solar/Wind Harmer
95.481
970085AG2-068 GEN
Solar/Wind Harmer
31.82
970581AG2-369 GEN
Solar/Wind Harmer
27.365
3147173SINAI
Solar/Wind Harmer
0.309
3147243WELCO
Solar/Wind Harmer
0.193
316118AC1-105 GEN
Solar/Wind Harmer
0.768
970865AG2-541 GEN
Solar/Wind Harmer
9.078
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.118
3144303KENBRDG
Solar/Wind Harmer
0.196
970683AG2-441 GEN
Solar/Wind Harmer
16.053
970681AG2-440 GEN
Solar/Wind Harmer
12.842
946301AF1-294 GEN
Solar/Wind Harmer
4.678
961791AG1-021 GEN
Solar/Wind Harmer
2.276
315657AE1-056 GEN
Solar/Wind Harmer
8.085
316123AC1-075 GEN
Solar/Wind Harmer
0.315
970165AG2-112 GEN
Solar/Wind Harmer
1.87
970163AG2-111 GEN
Solar/Wind Harmer
1.784
970831AG2-522 GEN
Solar/Wind Harmer
7.35
970285AG2-188 GEN
Solar/Wind Harmer
12.402
971845AH1-439 GEN
Solar/Wind Harmer
6.507
270069AE2-166 C O1
Solar/Wind Harmer
0.004
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
53.421
316478AD1-087 GEN
Solar/Wind Harmer
1.525
316486AD2-202 GEN
Solar/Wind Harmer
0.448
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
13.182
316283AC2-100 C
Solar/Wind Harmer
0.55
971683AH1-343 GEN
Solar/Wind Harmer
10.2
316131AB2-060 GEN
Solar/Wind Harmer
0.796
964241AG1-285 GEN
Solar/Wind Harmer
16.703
315785AD2-033 C
Solar/Wind Harmer
2.003
970257AG2-171 GEN
Solar/Wind Harmer
7.834
959311AF2-222 GEN
Solar/Wind Harmer
21.656
963181AG1-167 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.736
971193AH1-056 GEN
Solar/Wind Harmer
14.274
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.131
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
0.943
3146776BUCKING
Solar/Wind Harmer
0.049
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.212
270336AE1-100 GEN
Solar/Wind Harmer
0.003
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.117
971623AH1-311 GEN
Solar/Wind Harmer
0.234
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.055
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.099
941801AE2-185 GEN
Solar/Wind Harmer
4.212
270030AE2-140 GEN
Solar/Wind Harmer
13.804
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.094
316359AB2-059 GEN
Solar/Wind Harmer
0.421
316049AB1-081 GEN
Solar/Wind Harmer
0.67
3142053HEARTS
Solar/Wind Harmer
0.206
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
961601AG1-000A GEN
Solar/Wind Harmer
8.141
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
942751AE2-291 GEN
Solar/Wind Harmer
11.476
270013AE1-250 PV
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.546
3146776BUCKING
Solar/Wind Harmer
0.044
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.276
316263AC1-034 GEN
Solar/Wind Harmer
4.449
961601AG1-000A GEN
Solar/Wind Harmer
2.035
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
NYPJM->LTFIMP_NY
CLTF
2.382
LGEELTFEXP_LGEE->PJM
CLTF
2.675
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51192_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51192_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.25 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5458.06
MW Contribution:17.25
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
62.844
957481AF2-042 GEN
Solar/Wind Harmer
166.962
315693AD1-088 GEN
Solar/Wind Harmer
24.364
962491AG1-098 GEN
Solar/Wind Harmer
32.107
315687AD1-152 GEN
Solar/Wind Harmer
5.339
316003AC1-222 GEN
Solar/Wind Harmer
3.203
970401AG2-262 GEN
Solar/Wind Harmer
2.096
316237AB2-079_GEN
Solar/Wind Harmer
0.866
970685AG2-442 GEN
Solar/Wind Harmer
23.673
963171AG1-166 GEN
Solar/Wind Harmer
3.329
971563AH1-280 GEN
Solar/Wind Harmer
3.329
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.119
316129AC1-054 GEN
Solar/Wind Harmer
1.828
970223AG2-152 GEN
Solar/Wind Harmer
17.247
270016AE1-250 BESS
Solar/Wind Harmer
2.846
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.591
316322AB2-045
Solar/Wind Harmer
0.516
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.545
270030AE2-140 GEN
Solar/Wind Harmer
19.786
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.774
316049AB1-081 GEN
Solar/Wind Harmer
1.419
3142053HEARTS
Solar/Wind Harmer
0.155
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
168.81
316478AD1-087 GEN
Solar/Wind Harmer
4.25
316486AD2-202 GEN
Solar/Wind Harmer
1.245
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
1.046
960061AF2-297 GEN
Solar/Wind Harmer
17.357
316283AC2-100 C
Solar/Wind Harmer
2.974
971683AH1-343 GEN
Solar/Wind Harmer
13.43
316131AB2-060 GEN
Solar/Wind Harmer
3.068
964241AG1-285 GEN
Solar/Wind Harmer
21.992
315785AD2-033 C
Solar/Wind Harmer
6.274
970257AG2-171 GEN
Solar/Wind Harmer
10.314
959311AF2-222 GEN
Solar/Wind Harmer
28.571
963181AG1-167 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.462
942461AE2-259 GEN
Solar/Wind Harmer
3.832
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.378
270197AD1-017 GEN1
Solar/Wind Harmer
1.68
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.844
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.545
270336AE1-100 GEN
Solar/Wind Harmer
1.569
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
5.12
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
971967AH1-528 GEN
Solar/Wind Harmer
126.052
970085AG2-068 GEN
Solar/Wind Harmer
41.896
970581AG2-369 GEN
Solar/Wind Harmer
36.031
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.3
970865AG2-541 GEN
Solar/Wind Harmer
11.953
316239AB2-077_GEN
Solar/Wind Harmer
0.866
316238AB2-078_GEN
Solar/Wind Harmer
0.866
971443AH1-215 GEN
Solar/Wind Harmer
5.422
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.136
970681AG2-440 GEN
Solar/Wind Harmer
16.909
946301AF1-294 GEN
Solar/Wind Harmer
6.825
961791AG1-021 GEN
Solar/Wind Harmer
3.329
270455AD2-022 GEN
Solar/Wind Harmer
4.714
270457AD2-023 GEN
Solar/Wind Harmer
2.39
315657AE1-056 GEN
Solar/Wind Harmer
9.877
316123AC1-075 GEN
Solar/Wind Harmer
2.797
970165AG2-112 GEN
Solar/Wind Harmer
2.462
970163AG2-111 GEN
Solar/Wind Harmer
2.349
970831AG2-522 GEN
Solar/Wind Harmer
9.678
970285AG2-188 GEN
Solar/Wind Harmer
15.412
971845AH1-439 GEN
Solar/Wind Harmer
8.567
270069AE2-166 C O1
Solar/Wind Harmer
2.422
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
59.226
970099AG2-077 GEN
Solar/Wind Harmer
66.785
971741AH1-377 GEN
Solar/Wind Harmer
44.199
970301AG2-198 GEN
Solar/Wind Harmer
17.416
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.86
316222AC1-221 GEN
Solar/Wind Harmer
3.218
962561AG1-105 GEN
Solar/Wind Harmer
17.755
939181AE1-148 GEN
Solar/Wind Harmer
16.34
313527AB2-043 GEN
Solar/Wind Harmer
4.631
970323AG2-213 GEN
Solar/Wind Harmer
13.752
971775AH1-396 GEN
Solar/Wind Harmer
1.958
316034AC1-036 C
Solar/Wind Harmer
0.51
958211AF2-115 GEN
Solar/Wind Harmer
4.162
963191AG1-168 GEN
Solar/Wind Harmer
2.497
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.11
270013AE1-250 PV
Solar/Wind Harmer
2.846
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.4
316197AC1-042 GEN
Solar/Wind Harmer
1.819
942671AE2-283 GEN
Solar/Wind Harmer
4.898
316263AC1-034 GEN
Solar/Wind Harmer
6.166
961601AG1-000A GEN
Solar/Wind Harmer
5.056
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
NYPJM->LTFIMP_NY
CLTF
2.382
LGEELTFEXP_LGEE->PJM
CLTF
2.675
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51172_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51172_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.79 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5435.07
MW Contribution:17.2
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
11.056
3151051BRUNSWICKS1
50/50
17.38
3151021BRUNSWICKG1
50/50
8.374
971451AH1-221 GEN
50/50
25.435
3151531CLOVER1
50/50
9.312
3151601KERR 3
50/50
0.538
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.8
971629AH1-314 GEN
50/50
17.875
3151561HALLBR1
50/50
0.366
970919AG2-571 GEN
Solar/Wind Harmer
21.227
970087AG2-069 GEN
Solar/Wind Harmer
62.431
957481AF2-042 GEN
Solar/Wind Harmer
166.01
315693AD1-088 GEN
Solar/Wind Harmer
24.233
962491AG1-098 GEN
Solar/Wind Harmer
31.935
315687AD1-152 GEN
Solar/Wind Harmer
5.313
316003AC1-222 GEN
Solar/Wind Harmer
3.193
970401AG2-262 GEN
Solar/Wind Harmer
2.094
316237AB2-079_GEN
Solar/Wind Harmer
0.868
970685AG2-442 GEN
Solar/Wind Harmer
23.682
963171AG1-166 GEN
Solar/Wind Harmer
3.328
971563AH1-280 GEN
Solar/Wind Harmer
3.328
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.224
316129AC1-054 GEN
Solar/Wind Harmer
1.849
970223AG2-152 GEN
Solar/Wind Harmer
17.201
270016AE1-250 BESS
Solar/Wind Harmer
2.839
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.577
316322AB2-045
Solar/Wind Harmer
0.514
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.53
270030AE2-140 GEN
Solar/Wind Harmer
19.734
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.817
316049AB1-081 GEN
Solar/Wind Harmer
1.454
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.785
316375AC2-012 GEN
Solar/Wind Helper
1.014
3145336SMITFLD
Solar/Wind Helper
1.482
316388AE2-253 GEN
Solar/Wind Helper
1.397
3146456SLIGO L269
Solar/Wind Helper
0.359
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.402
316159AE1-175 C
Solar/Wind Helper
0.529
316381AD1-082 GEN
Solar/Wind Helper
1.758
316458AB2-190 GEN2
Solar/Wind Helper
1.933
3141766HARMONY
Solar/Wind Helper
0.065
3138133OCRAN
Solar/Wind Helper
0.193
3142433PROV 92
Solar/Wind Helper
1.275
3142543TWELFTH
Solar/Wind Helper
0.029
964211AG1-282 GEN
Solar/Wind Helper
0.412
3141726DUNNSVL
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.961
3146516WINFALL
Solar/Wind Helper
0.297
316337AD2-073 GEN
Solar/Wind Helper
0.448
3142416OLDCHRC
Solar/Wind Helper
0.759
3142416OLDCHRC
Solar/Wind Helper
0.291
3143526WINTERP
Solar/Wind Helper
1.499
3143226MDLTHAN
Solar/Wind Helper
0.284
315800Z1-036_GEN1
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
3151031BRUNSWICKG2
50/50
8.374
970413AG2-270 GEN
50/50
40.637
3151591KERR 2
50/50
0.538
3144293JTRSVLE
50/50
0.8
970917AG2-570 GEN
Solar/Wind Harmer
167.695
316478AD1-087 GEN
Solar/Wind Harmer
4.227
316486AD2-202 GEN
Solar/Wind Harmer
1.238
970909AG2-566 GEN
Solar/Wind Harmer
3.291
316248AF1-058 C
Solar/Wind Harmer
1.043
960061AF2-297 GEN
Solar/Wind Harmer
17.305
316283AC2-100 C
Solar/Wind Harmer
2.965
971683AH1-343 GEN
Solar/Wind Harmer
13.39
316131AB2-060 GEN
Solar/Wind Harmer
3.076
964241AG1-285 GEN
Solar/Wind Harmer
22.038
315785AD2-033 C
Solar/Wind Harmer
6.282
970257AG2-171 GEN
Solar/Wind Harmer
10.326
959311AF2-222 GEN
Solar/Wind Harmer
28.597
963181AG1-167 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.449
942461AE2-259 GEN
Solar/Wind Harmer
3.824
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.375
270197AD1-017 GEN1
Solar/Wind Harmer
1.676
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.834
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.53
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.564
961601AG1-000A GEN
Solar/Wind Harmer
5.252
315773AC2-141 GEN
Solar/Wind Helper
9.163
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.058
3145336SMITFLD
Solar/Wind Helper
0.148
3146456SLIGO L269
Solar/Wind Helper
0.359
316382AG1-145 C
Solar/Wind Helper
0.469
315839AE2-212 C
Solar/Wind Helper
0.457
316320Y1-086
Solar/Wind Helper
0.148
316156AD2-030 GEN
Solar/Wind Helper
0.492
316280AD1-041 GEN
Solar/Wind Helper
1.092
3142946ENON
Solar/Wind Helper
0.105
316484AD2-074 GEN
Solar/Wind Helper
0.607
316404AE1-155 C
Solar/Wind Helper
2.624
316435W1029_GEN3
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3141906WESTMOR
Solar/Wind Helper
0.115
3146626S HERTFORD
Solar/Wind Helper
0.28
316473AC1-191 GEN
Solar/Wind Helper
1.696
3145273HOLLAND
Solar/Wind Helper
0.188
966881AG1-559 GEN
Solar/Wind Helper
0.329
3146376EDENTON
Solar/Wind Helper
0.226
315244AE2-183_ST
50/50
19.115
963041AG1-153 GEN
50/50
16.957
3151541CLOVER2
50/50
9.268
3151611KERR 4
50/50
0.538
3151621KERR 5
50/50
0.538
3151631KERR 6
50/50
0.538
3151641KERR 7
50/50
0.538
971967AH1-528 GEN
Solar/Wind Harmer
125.223
970085AG2-068 GEN
Solar/Wind Harmer
41.62
970581AG2-369 GEN
Solar/Wind Harmer
35.794
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.295
970865AG2-541 GEN
Solar/Wind Harmer
11.917
316239AB2-077_GEN
Solar/Wind Harmer
0.868
316238AB2-078_GEN
Solar/Wind Harmer
0.868
971443AH1-215 GEN
Solar/Wind Harmer
5.428
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.145
970681AG2-440 GEN
Solar/Wind Harmer
16.916
946301AF1-294 GEN
Solar/Wind Harmer
6.823
961791AG1-021 GEN
Solar/Wind Harmer
3.328
270455AD2-022 GEN
Solar/Wind Harmer
4.701
270457AD2-023 GEN
Solar/Wind Harmer
2.384
315657AE1-056 GEN
Solar/Wind Harmer
9.869
316123AC1-075 GEN
Solar/Wind Harmer
2.789
970165AG2-112 GEN
Solar/Wind Harmer
2.455
970163AG2-111 GEN
Solar/Wind Harmer
2.342
970831AG2-522 GEN
Solar/Wind Harmer
9.813
970285AG2-188 GEN
Solar/Wind Harmer
15.354
971845AH1-439 GEN
Solar/Wind Harmer
8.535
270069AE2-166 C O1
Solar/Wind Harmer
2.415
319010AE1-072 C
Solar/Wind Helper
4.079
3143316POE
Solar/Wind Helper
1.407
316305AF2-043 C
Solar/Wind Helper
0.473
316369SG1_INVT
Solar/Wind Helper
1.664
957831AF2-077 GEN
Solar/Wind Helper
0.466
316132AB2-190 GEN1
Solar/Wind Helper
1.933
316349AD2-085 GEN
Solar/Wind Helper
1.523
313526AB2-022
Solar/Wind Helper
0.505
957601AF2-054 GEN
Solar/Wind Helper
0.438
3141873WAN 176
Solar/Wind Helper
0.065
315662AE1-191 GEN
Solar/Wind Helper
1.747
315666AE1-190 GEN
Solar/Wind Helper
0.437
316059AD1-063 C
Solar/Wind Helper
0.326
3141913WHIT STONE
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3138133OCRAN
Solar/Wind Helper
0.097
3143873LANEXA
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.128
316321Z2-027
Solar/Wind Helper
0.487
3145176PASQUOTANK
Solar/Wind Helper
0.198
3141813NORNECK
Solar/Wind Helper
0.304
316312AB1-027
Solar/Wind Helper
0.556
316233AE1-074 FULL
Solar/Wind Helper
0.44
316223AC1-118
Solar/Wind Helper
0.438
316315AB2-025 C
Solar/Wind Helper
0.418
315611Z1-036_GEN2
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
3130156CHOWAN
Solar/Wind Helper
0.226
315242AE2-183_GT2
50/50
11.056
315241AE2-183_GT1
50/50
10.988
972185AH1-677 GEN
50/50
39.858
3151041BRUNSWICKG3
50/50
8.374
972187AH1-678 GEN
50/50
19.217
3152661PLYWOOD A
50/50
0.67
970535AG2-341 GEN
50/50
4.577
3144293JTRSVLE
50/50
0.8
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
58.849
970099AG2-077 GEN
Solar/Wind Harmer
66.404
971741AH1-377 GEN
Solar/Wind Harmer
43.978
970301AG2-198 GEN
Solar/Wind Harmer
17.332
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.854
316222AC1-221 GEN
Solar/Wind Harmer
3.208
962561AG1-105 GEN
Solar/Wind Harmer
17.747
939181AE1-148 GEN
Solar/Wind Harmer
16.378
313527AB2-043 GEN
Solar/Wind Harmer
4.643
970323AG2-213 GEN
Solar/Wind Harmer
13.768
971775AH1-396 GEN
Solar/Wind Harmer
1.961
316034AC1-036 C
Solar/Wind Harmer
0.511
958211AF2-115 GEN
Solar/Wind Harmer
4.16
963191AG1-168 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.066
270013AE1-250 PV
Solar/Wind Harmer
2.839
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.394
316197AC1-042 GEN
Solar/Wind Harmer
1.815
942671AE2-283 GEN
Solar/Wind Harmer
4.885
316263AC1-034 GEN
Solar/Wind Harmer
6.316
961601AG1-000A GEN
Solar/Wind Harmer
5.186
316036AC1-147 C
Solar/Wind Helper
0.59
3142956BIRDNECK
Solar/Wind Helper
0.259
316316AC1-027 C
Solar/Wind Helper
0.606
316185AD1-033 GEN
Solar/Wind Helper
1.799
3145506HICKORY
Solar/Wind Helper
1.507
3145506HICKORY
Solar/Wind Helper
0.904
3145506HICKORY
Solar/Wind Helper
0.226
316236AE1-162_GEN
Solar/Wind Helper
0.498
316339AD2-160 GEN
Solar/Wind Helper
1.397
316018AA1-139 ULT2
Solar/Wind Helper
1.567
316017AA1-139 ULT1
Solar/Wind Helper
1.665
3137176SLIGO L2192
Solar/Wind Helper
1.432
3130086AYDLETT
Solar/Wind Helper
1.421
316033AB2-134 GEN
Solar/Wind Helper
1.19
315697AD1-025 GEN
Solar/Wind Helper
3.953
3146386ELIZ CT
Solar/Wind Helper
0.331
316240AF1-291 C
Solar/Wind Helper
0.444
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.318
316075AC2-137 C
Solar/Wind Helper
0.467
316077AC2-138 C
Solar/Wind Helper
0.286
316431W1029_GEN1
Solar/Wind Helper
1.225
316433W1029_GEN2
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3143526WINTERP
Solar/Wind Helper
1.499
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
966871AG1-558 GEN
Solar/Wind Helper
0.374
3144356SAPONY
Solar/Wind Helper
0.492
316468AD1-105 GEN
Solar/Wind Helper
1.305
LAGNLTFEXP_LAGN->PJM
CLTF
14.626
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.161
TVALTFEXP_TVA->PJM
CLTF
7.294
CPLELTFEXP_CPLE->PJM
CLTF
19.708
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.004
NYPJM->LTFIMP_NY
CLTF
2.38
LGEELTFEXP_LGEE->PJM
CLTF
2.666
WECLTFEXP_WEC->PJM
CLTF
1.395
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.554
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.081
MECLTFEXP_MEC->PJM
CLTF
7.343
SIGELTFEXP_SIGE->PJM
CLTF
0.22

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 511T544_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T544_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.19 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5355.19
MW Contribution:17.06
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
18.952
963041AG1-153 GEN
50/50
16.812
3151541CLOVER2
50/50
9.183
3151611KERR 4
50/50
0.532
3151621KERR 5
50/50
0.532
3151631KERR 6
50/50
0.532
3151641KERR 7
50/50
0.532
971967AH1-528 GEN
Solar/Wind Harmer
124.141
970085AG2-068 GEN
Solar/Wind Harmer
41.268
970581AG2-369 GEN
Solar/Wind Harmer
35.491
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.271
970865AG2-541 GEN
Solar/Wind Harmer
11.801
316239AB2-077_GEN
Solar/Wind Harmer
0.856
316238AB2-078_GEN
Solar/Wind Harmer
0.856
971443AH1-215 GEN
Solar/Wind Harmer
5.352
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
20.851
970681AG2-440 GEN
Solar/Wind Harmer
16.681
946301AF1-294 GEN
Solar/Wind Harmer
6.73
961791AG1-021 GEN
Solar/Wind Harmer
3.283
315242AE2-183_GT2
50/50
10.962
315241AE2-183_GT1
50/50
10.894
972185AH1-677 GEN
50/50
39.518
3151041BRUNSWICKG3
50/50
8.303
972187AH1-678 GEN
50/50
19.053
3152661PLYWOOD A
50/50
0.663
970535AG2-341 GEN
50/50
4.519
3144293JTRSVLE
50/50
0.79
3144293JTRSVLE
50/50
0.665
970933AG2-581 GEN
Solar/Wind Harmer
58.334
970099AG2-077 GEN
Solar/Wind Harmer
65.804
971741AH1-377 GEN
Solar/Wind Harmer
43.523
970301AG2-198 GEN
Solar/Wind Harmer
17.145
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.775
316222AC1-221 GEN
Solar/Wind Harmer
3.182
315243AE2-183_GT3
50/50
10.962
3151051BRUNSWICKS1
50/50
17.232
3151021BRUNSWICKG1
50/50
8.303
971451AH1-221 GEN
50/50
25.218
3151531CLOVER1
50/50
9.227
3151601KERR 3
50/50
0.532
3151581KERR 1
50/50
0.19
3144293JTRSVLE
50/50
0.79
971629AH1-314 GEN
50/50
17.731
3151561HALLBR1
50/50
0.363
970919AG2-571 GEN
Solar/Wind Harmer
21.047
970087AG2-069 GEN
Solar/Wind Harmer
61.902
957481AF2-042 GEN
Solar/Wind Harmer
164.509
315693AD1-088 GEN
Solar/Wind Harmer
24.007
962491AG1-098 GEN
Solar/Wind Harmer
31.634
315687AD1-152 GEN
Solar/Wind Harmer
5.265
316003AC1-222 GEN
Solar/Wind Harmer
3.162
970401AG2-262 GEN
Solar/Wind Harmer
2.07
316237AB2-079_GEN
Solar/Wind Harmer
0.856
970685AG2-442 GEN
Solar/Wind Harmer
23.354
963171AG1-166 GEN
Solar/Wind Harmer
3.283
971563AH1-280 GEN
Solar/Wind Harmer
3.283
3146926FARMVIL
Solar/Wind Harmer
-0.014
971065AG2-659 GEN
Solar/Wind Harmer
11.094
316129AC1-054 GEN
Solar/Wind Harmer
1.827
970223AG2-152 GEN
Solar/Wind Harmer
17.059
270016AE1-250 BESS
Solar/Wind Harmer
2.815
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.528
316322AB2-045
Solar/Wind Harmer
0.506
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.477
270030AE2-140 GEN
Solar/Wind Harmer
19.567
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.809
316049AB1-081 GEN
Solar/Wind Harmer
1.448
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.244
962561AG1-105 GEN
Solar/Wind Harmer
17.536
939181AE1-148 GEN
Solar/Wind Harmer
16.186
313527AB2-043 GEN
Solar/Wind Harmer
4.576
970323AG2-213 GEN
Solar/Wind Harmer
13.574
971775AH1-396 GEN
Solar/Wind Harmer
1.933
316034AC1-036 C
Solar/Wind Harmer
0.503
958211AF2-115 GEN
Solar/Wind Harmer
4.103
963191AG1-168 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
14.918
270013AE1-250 PV
Solar/Wind Harmer
2.815
3146776BUCKING
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.37
316197AC1-042 GEN
Solar/Wind Harmer
1.797
942671AE2-283 GEN
Solar/Wind Harmer
4.838
316263AC1-034 GEN
Solar/Wind Harmer
6.29
961601AG1-000A GEN
Solar/Wind Harmer
5.16
316240AF1-291 C
Solar/Wind Helper
0.471
316036AC1-147 C
Solar/Wind Helper
0.511
316236AE1-162_GEN
Solar/Wind Helper
0.447
316316AC1-027 C
Solar/Wind Helper
0.524
3142956BIRDNECK
Solar/Wind Helper
0.223
316033AB2-134 GEN
Solar/Wind Helper
1.137
315697AD1-025 GEN
Solar/Wind Helper
3.779
316185AD1-033 GEN
Solar/Wind Helper
1.551
3145506HICKORY
Solar/Wind Helper
1.298
3145506HICKORY
Solar/Wind Helper
0.779
3145506HICKORY
Solar/Wind Helper
0.195
3144356SAPONY
Solar/Wind Helper
0.581
316339AD2-160 GEN
Solar/Wind Helper
1.201
316018AA1-139 ULT2
Solar/Wind Helper
1.346
316017AA1-139 ULT1
Solar/Wind Helper
1.43
3142946ENON
Solar/Wind Helper
0.031
3137176SLIGO L2192
Solar/Wind Helper
1.229
3130086AYDLETT
Solar/Wind Helper
1.219
316487AF1-042 GEN
Solar/Wind Helper
0.305
316075AC2-137 C
Solar/Wind Helper
0.459
316077AC2-138 C
Solar/Wind Helper
0.276
3143526WINTERP
Solar/Wind Helper
1.519
3146386ELIZ CT
Solar/Wind Helper
0.283
966871AG1-558 GEN
Solar/Wind Helper
0.376
316468AD1-105 GEN
Solar/Wind Helper
1.308
316431W1029_GEN1
Solar/Wind Helper
1.037
316433W1029_GEN2
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3151031BRUNSWICKG2
50/50
8.303
970413AG2-270 GEN
50/50
40.265
3151591KERR 2
50/50
0.532
3144293JTRSVLE
50/50
0.79
970917AG2-570 GEN
Solar/Wind Harmer
166.275
316478AD1-087 GEN
Solar/Wind Harmer
4.189
316486AD2-202 GEN
Solar/Wind Harmer
1.227
970909AG2-566 GEN
Solar/Wind Harmer
3.255
316248AF1-058 C
Solar/Wind Harmer
1.033
960061AF2-297 GEN
Solar/Wind Harmer
17.135
316283AC2-100 C
Solar/Wind Harmer
2.94
971683AH1-343 GEN
Solar/Wind Harmer
13.259
316131AB2-060 GEN
Solar/Wind Harmer
3.032
964241AG1-285 GEN
Solar/Wind Harmer
21.724
315785AD2-033 C
Solar/Wind Harmer
6.194
970257AG2-171 GEN
Solar/Wind Harmer
10.181
959311AF2-222 GEN
Solar/Wind Harmer
28.197
963181AG1-167 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.081
971193AH1-056 GEN
Solar/Wind Harmer
16.225
942461AE2-259 GEN
Solar/Wind Harmer
3.773
3146926FARMVIL
Solar/Wind Harmer
-0.014
270018AE2-047 C O1
Solar/Wind Harmer
1.363
270197AD1-017 GEN1
Solar/Wind Harmer
1.661
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.802
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.477
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.551
961601AG1-000A GEN
Solar/Wind Harmer
5.225
315773AC2-141 GEN
Solar/Wind Helper
8.525
315839AE2-212 C
Solar/Wind Helper
0.497
3144536CHRHLND
Solar/Wind Helper
0.05
3144873MCLAUGH
Solar/Wind Helper
0.008
3145336SMITFLD
Solar/Wind Helper
0.133
316382AG1-145 C
Solar/Wind Helper
0.441
316156AD2-030 GEN
Solar/Wind Helper
0.47
3142946ENON
Solar/Wind Helper
0.104
316280AD1-041 GEN
Solar/Wind Helper
1.046
3146456SLIGO L269
Solar/Wind Helper
0.308
316484AD2-074 GEN
Solar/Wind Helper
0.583
316404AE1-155 C
Solar/Wind Helper
2.523
316320Y1-086
Solar/Wind Helper
0.126
316473AC1-191 GEN
Solar/Wind Helper
1.704
3141906WESTMOR
Solar/Wind Helper
0.111
316435W1029_GEN3
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
966881AG1-559 GEN
Solar/Wind Helper
0.328
3146626S HERTFORD
Solar/Wind Helper
0.236
3146626S HERTFORD
Solar/Wind Helper
0.236
3146626S HERTFORD
Solar/Wind Helper
0.236
270455AD2-022 GEN
Solar/Wind Harmer
4.664
270457AD2-023 GEN
Solar/Wind Harmer
2.365
315657AE1-056 GEN
Solar/Wind Harmer
9.735
316123AC1-075 GEN
Solar/Wind Harmer
2.761
970165AG2-112 GEN
Solar/Wind Harmer
2.431
970163AG2-111 GEN
Solar/Wind Harmer
2.319
970831AG2-522 GEN
Solar/Wind Harmer
9.696
970285AG2-188 GEN
Solar/Wind Harmer
15.118
971845AH1-439 GEN
Solar/Wind Harmer
8.397
270069AE2-166 C O1
Solar/Wind Harmer
2.394
3143316POE
Solar/Wind Helper
1.57
316132AB2-190 GEN1
Solar/Wind Helper
1.893
316369SG1_INVT
Solar/Wind Helper
1.59
957831AF2-077 GEN
Solar/Wind Helper
0.437
316315AB2-025 C
Solar/Wind Helper
0.494
957601AF2-054 GEN
Solar/Wind Helper
0.418
3141873WAN 176
Solar/Wind Helper
0.062
315662AE1-191 GEN
Solar/Wind Helper
1.674
315666AE1-190 GEN
Solar/Wind Helper
0.419
3143873LANEXA
Solar/Wind Helper
0.186
316059AD1-063 C
Solar/Wind Helper
0.312
3141913WHIT STONE
Solar/Wind Helper
0.309
3138133OCRAN
Solar/Wind Helper
0.093
3141783LANCAST
Solar/Wind Helper
0.184
3141783LANCAST
Solar/Wind Helper
0.123
319010AE1-072 C
Solar/Wind Helper
3.5
316349AD2-085 GEN
Solar/Wind Helper
1.396
316305AF2-043 C
Solar/Wind Helper
0.402
3141813NORNECK
Solar/Wind Helper
0.293
316233AE1-074 FULL
Solar/Wind Helper
0.446
316312AB1-027
Solar/Wind Helper
0.55
313526AB2-022
Solar/Wind Helper
0.431
316223AC1-118
Solar/Wind Helper
0.424
3146486SUNBURY
Solar/Wind Helper
0.274
3146486SUNBURY
Solar/Wind Helper
0.274
316321Z2-027
Solar/Wind Helper
0.414
3145176PASQUOTANK
Solar/Wind Helper
0.168
316381AD1-082 GEN
Solar/Wind Helper
1.747
316375AC2-012 GEN
Solar/Wind Helper
0.879
3145336SMITFLD
Solar/Wind Helper
1.331
316458AB2-190 GEN2
Solar/Wind Helper
1.893
316159AE1-175 C
Solar/Wind Helper
0.497
316388AE2-253 GEN
Solar/Wind Helper
1.201
3142433PROV 92
Solar/Wind Helper
1.254
3142543TWELFTH
Solar/Wind Helper
0.03
3141766HARMONY
Solar/Wind Helper
0.062
3146456SLIGO L269
Solar/Wind Helper
0.308
3138133OCRAN
Solar/Wind Helper
0.185
316072AD1-144
Solar/Wind Helper
0.35
316246AF1-032 C
Solar/Wind Helper
0.342
964211AG1-282 GEN
Solar/Wind Helper
0.397
3141726DUNNSVL
Solar/Wind Helper
1.179
3143526WINTERP
Solar/Wind Helper
1.519
3142416OLDCHRC
Solar/Wind Helper
0.752
3143226MDLTHAN
Solar/Wind Helper
0.289
3142416OLDCHRC
Solar/Wind Helper
0.288
316337AD2-073 GEN
Solar/Wind Helper
0.434
3146516WINFALL
Solar/Wind Helper
0.813
3146516WINFALL
Solar/Wind Helper
0.251
LAGNLTFEXP_LAGN->PJM
CLTF
14.499
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.842
TVALTFEXP_TVA->PJM
CLTF
7.231
CPLELTFEXP_CPLE->PJM
CLTF
19.58
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.279
NYPJM->LTFIMP_NY
CLTF
2.38
LGEELTFEXP_LGEE->PJM
CLTF
2.637
WECLTFEXP_WEC->PJM
CLTF
1.38
AG2-052LTFEXP_AG2-052->PJM
LTF
0.074
AH1-155LTFEXP_AH1-155->PJM
LTF
0.111
CBM West 1LTFEXP_CBM-W1->PJM
CBM
48.979
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.858
MECLTFEXP_MEC->PJM
CLTF
7.267
SIGELTFEXP_SIGE->PJM
CLTF
0.218

Details for 8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 555_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 555_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.01 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3607.13
MW Contribution:8.2
Bus #Bus NameTypeMW Contribution
3152061BATH 6F
50/50
16.44
970823AG2-518 GEN
50/50
5.734
962751AG1-124 GEN
Solar/Wind Harmer
9.115
270173AC1-122 GEN
Solar/Wind Harmer
0.472
958121AF2-106 GEN
Solar/Wind Harmer
0.001
247619Y1-049
Adder
0.574
971331AH1-145 GEN
Solar/Wind Harmer
12.171
3147312GRETNA
Solar/Wind Harmer
0.129
3146802CHATHAM
Solar/Wind Harmer
0.121
941801AE2-185 GEN
Solar/Wind Harmer
5.17
943031AE2-326 GEN
Solar/Wind Harmer
4.43
3147123OTTER R
Solar/Wind Harmer
0.09
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270030AE2-140 GEN
Solar/Wind Harmer
14.108
270346AE1-212 GEN
Solar/Wind Harmer
5.915
270016AE1-250 BESS
Solar/Wind Harmer
0.004
970223AG2-152 GEN
Solar/Wind Harmer
8.195
960911AF2-382 GEN
Solar/Wind Harmer
4.593
3147983MERCK5
Solar/Wind Helper
0.146
3152011BATH 1A
50/50
16.383
3152021BATH 2B
50/50
16.383
3152031BATH 3C
50/50
16.378
3152041BATH 4D
50/50
16.352
3151881LOWMORC
50/50
4.046
3151881LOWMORC
50/50
3.982
3151861LOWMORA
50/50
3.918
971543AH1-269 GEN
50/50
8.257
3148463FAIRFLD
Solar/Wind Harmer
0.358
966391AG1-508 GEN
Solar/Wind Harmer
1.299
270069AE2-166 C O1
Solar/Wind Harmer
0.005
971313AH1-133 GEN
Solar/Wind Harmer
6.761
24734705WLF1G3
Adder
4.975
24734805WLF1G4
Adder
4.975
24734905WLF1G5
Adder
4.975
3148133STUARTS
Solar/Wind Helper
0.182
3148013FISHERV
Solar/Wind Helper
0.175
3138266HYDRAULIC
Solar/Wind Helper
0.012
3138266HYDRAULIC
Solar/Wind Helper
0.007
3152051BATH 5E
50/50
16.369
3151861LOWMORA
50/50
4.078
3137383CUSHAW
50/50
0.078
270205AE1-176
50/50
0.004
970479AG2-310 GEN
50/50
14.12
24288905REUSENS
50/50
0.04
315616AA1-038_C
Solar/Wind Harmer
0.003
971367AH1-164 GEN
Solar/Wind Harmer
3.331
971329AH1-144 GEN
Solar/Wind Harmer
7.668
3147312GRETNA
Solar/Wind Harmer
0.032
941821AE2-187 GEN
Solar/Wind Harmer
5.17
270197AD1-017 GEN1
Solar/Wind Harmer
0.974
270336AE1-100 GEN
Solar/Wind Harmer
0.004
958131AF2-107 GEN
Solar/Wind Harmer
3.843
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270018AE2-047 C O1
Solar/Wind Harmer
0.003
24728305BUCHG2
Adder
4.101
316499AE2-029_GEN
Solar/Wind Helper
1.225
3148013FISHERV
Solar/Wind Helper
0.304
23583801GRNGAP
Solar/Wind Helper
3.885
237061AD1-155 GEN
Solar/Wind Helper
0.042
24290605CLAY-1
50/50
0.172
24290605CLAY-1
50/50
0.172
24290705CLAY-2
50/50
0.172
24290705CLAY-2
50/50
0.172
270583AD2-179 GEN
Solar/Wind Harmer
9.708
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
4.021
971277AH1-098 GEN
Solar/Wind Harmer
3.383
270013AE1-250 PV
Solar/Wind Harmer
0.004
24728205BUCHG1
Adder
4.101
3132123MT JACKSON
Solar/Wind Helper
1.116
LAGNLTFEXP_LAGN->PJM
CLTF
11.387
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.911
TVALTFEXP_TVA->PJM
CLTF
6.03
CPLELTFEXP_CPLE->PJM
CLTF
3.393
CBM West 2LTFEXP_CBM-W2->PJM
CBM
71.784
NYPJM->LTFIMP_NY
CLTF
2.909
LGEELTFEXP_LGEE->PJM
CLTF
3.588
WECLTFEXP_WEC->PJM
CLTF
1.753
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155
CBM West 1LTFEXP_CBM-W1->PJM
CBM
62.503
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.099
MECLTFEXP_MEC->PJM
CLTF
8.174
SIGELTFEXP_SIGE->PJM
CLTF
0.27

Details for 8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2168-555_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2168-555_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.23 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4145.88
MW Contribution:12.91
Bus #Bus NameTypeMW Contribution
24290605CLAY-1
50/50
0.194
24290605CLAY-1
50/50
0.194
24290705CLAY-2
50/50
0.194
24290705CLAY-2
50/50
0.194
270583AD2-179 GEN
Solar/Wind Harmer
15.671
270214AC2-123 GEN
Solar/Wind Harmer
3.17
316217AC1-145 GEN
Solar/Wind Harmer
3.265
316197AC1-042 GEN
Solar/Wind Harmer
2.475
942671AE2-283 GEN
Solar/Wind Harmer
6.664
971277AH1-098 GEN
Solar/Wind Harmer
5.461
270013AE1-250 PV
Solar/Wind Harmer
2.411
24728205BUCHG1
Adder
4.634
971225AH1-072 GEN
Solar/Wind Harmer
1.824
971227AH1-073 GEN
Solar/Wind Harmer
1.824
3132123MT JACKSON
Solar/Wind Helper
1.31
315821AE2-092 GEN
Solar/Wind Helper
2.895
966001AG1-469 GEN
Solar/Wind Helper
0.292
315651AD1-115 GEN
Solar/Wind Helper
0.781
3152011BATH 1A
50/50
17.37
3152021BATH 2B
50/50
17.37
3152031BATH 3C
50/50
17.364
3152041BATH 4D
50/50
17.337
3151881LOWMORC
50/50
6.984
3151881LOWMORC
50/50
6.875
3151861LOWMORA
50/50
6.765
971543AH1-269 GEN
50/50
9.298
3148463FAIRFLD
Solar/Wind Harmer
-0.069
966391AG1-508 GEN
Solar/Wind Harmer
4.68
270069AE2-166 C O1
Solar/Wind Harmer
3.325
971313AH1-133 GEN
Solar/Wind Harmer
10.943
24734705WLF1G3
Adder
5.613
24734805WLF1G4
Adder
5.613
24734905WLF1G5
Adder
5.613
24735105WLF2G1
Adder
5.48
270132AB1-180 C
Adder
0.114
3148133STUARTS
Solar/Wind Helper
0.274
3148013FISHERV
Solar/Wind Helper
0.263
3138266HYDRAULIC
Solar/Wind Helper
0.017
3138266HYDRAULIC
Solar/Wind Helper
0.011
23546401DTGZ2-030
Solar/Wind Helper
0.075
238152AF2-075_GEN
Solar/Wind Helper
0.572
316164AC1-076 GEN
Solar/Wind Helper
1.095
3152061BATH 6F
50/50
17.43
970823AG2-518 GEN
50/50
6.455
962751AG1-124 GEN
Solar/Wind Harmer
14.726
270173AC1-122 GEN
Solar/Wind Harmer
2.55
958121AF2-106 GEN
Solar/Wind Harmer
7.115
247619Y1-049
Adder
0.646
971331AH1-145 GEN
Solar/Wind Harmer
13.718
943031AE2-326 GEN
Solar/Wind Harmer
4.99
3147312GRETNA
Solar/Wind Harmer
-0.016
3146802CHATHAM
Solar/Wind Harmer
-0.015
941801AE2-185 GEN
Solar/Wind Harmer
7.544
3147123OTTER R
Solar/Wind Harmer
-0.011
270574AD1-017 GEN2
Solar/Wind Harmer
6.414
270030AE2-140 GEN
Solar/Wind Harmer
22.569
270346AE1-212 GEN
Solar/Wind Harmer
9.778
270016AE1-250 BESS
Solar/Wind Harmer
2.411
960911AF2-382 GEN
Solar/Wind Harmer
7.443
970223AG2-152 GEN
Solar/Wind Harmer
12.909
971461AH1-227 GEN
Solar/Wind Harmer
4.678
970913AG2-568 GEN
Solar/Wind Harmer
7.285
3147983MERCK5
Solar/Wind Helper
0.183
316192AB2-158 GEN
Solar/Wind Helper
1.696
3147666LOUISA
Solar/Wind Helper
1.004
316254AC1-120 GEN1
Solar/Wind Helper
1.079
316097T157 G90
Solar/Wind Helper
1.082
238148AE2-230_GEN2
Solar/Wind Helper
0.402
316336AC2-165 C
Solar/Wind Helper
1.208
3152051BATH 5E
50/50
17.355
3137383CUSHAW
50/50
0.134
3151861LOWMORA
50/50
7.039
270205AE1-176
50/50
0.005
970479AG2-310 GEN
50/50
15.892
24288905REUSENS
50/50
0.045
315616AA1-038_C
Solar/Wind Harmer
14.233
971367AH1-164 GEN
Solar/Wind Harmer
5.352
971329AH1-144 GEN
Solar/Wind Harmer
17.696
3147312GRETNA
Solar/Wind Harmer
-0.004
941821AE2-187 GEN
Solar/Wind Harmer
7.544
270197AD1-017 GEN1
Solar/Wind Harmer
1.927
270336AE1-100 GEN
Solar/Wind Harmer
2.02
943811AF1-049 GEN
Solar/Wind Harmer
4.147
270018AE2-047 C O1
Solar/Wind Harmer
1.338
958131AF2-107 GEN
Solar/Wind Harmer
5.403
24728305BUCHG2
Adder
4.634
24735205WLF2G2
Adder
5.48
971687AH1-348 GEN
Solar/Wind Harmer
0.906
971403AH1-188 GEN
Solar/Wind Harmer
12.187
316499AE2-029_GEN
Solar/Wind Helper
1.577
3148013FISHERV
Solar/Wind Helper
0.457
3132273ORANGE
Solar/Wind Helper
0.051
3147666LOUISA
Solar/Wind Helper
0.577
237061AD1-155 GEN
Solar/Wind Helper
0.047
23583801GRNGAP
Solar/Wind Helper
4.125
316170AC1-121 GEN2
Solar/Wind Helper
0.36
316095T157 G97
Solar/Wind Helper
1.082
238147AE2-230_GEN1
Solar/Wind Helper
0.401
238149AF1-291A_GEN
Solar/Wind Helper
0.114
LAGNLTFEXP_LAGN->PJM
CLTF
12.827
CBM South 2LTFEXP_CBM-S2->PJM
CBM
16.289
TVALTFEXP_TVA->PJM
CLTF
6.791
CPLELTFEXP_CPLE->PJM
CLTF
3.547
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.312
NYPJM->LTFIMP_NY
CLTF
3.2
LGEELTFEXP_LGEE->PJM
CLTF
4.095
WECLTFEXP_WEC->PJM
CLTF
2.007
AG2-052LTFEXP_AG2-052->PJM
LTF
0.119
AH1-155LTFEXP_AH1-155->PJM
LTF
0.178
CBM West 1LTFEXP_CBM-W1->PJM
CBM
71.759
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.94
MECLTFEXP_MEC->PJM
CLTF
9.322
SIGELTFEXP_SIGE->PJM
CLTF
0.308

Details for AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line l/o AEP_P4_#10162_05EDAN 1 138_P_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.44 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:397.05
MW Contribution:13.03
Bus #Bus NameTypeMW Contribution
970865AG2-541 GEN
Solar/Wind Harmer
35.473
316123AC1-075 GEN
Solar/Wind Harmer
7.906
970165AG2-112 GEN
Solar/Wind Harmer
6.961
970163AG2-111 GEN
Solar/Wind Harmer
6.641
3147173SINAI
Solar/Wind Helper
0.315
3147243WELCO
Solar/Wind Helper
0.197
316118AC1-105 GEN
Solar/Wind Helper
1.088
316239AB2-077_GEN
Solar/Wind Helper
0.203
316238AB2-078_GEN
Solar/Wind Helper
0.203
3144303KENBRDG
Solar/Wind Helper
0.101
3151561HALLBR1
50/50
0.769
24728405LEESVG
50/50
0.228
24684705SMG5
50/50
0.436
970481AG2-311 GEN
50/50
6.074
316003AC1-222 GEN
Solar/Wind Harmer
9.848
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.654
270574AD1-017 GEN2
Solar/Wind Harmer
5.091
270016AE1-250 BESS
Solar/Wind Harmer
2.26
970223AG2-152 GEN
Solar/Wind Harmer
13.033
270173AC1-122 GEN
Solar/Wind Harmer
1.398
962751AG1-124 GEN
Solar/Wind Harmer
5.091
316237AB2-079_GEN
Solar/Wind Helper
0.203
315687AD1-152 GEN
Solar/Wind Helper
0.727
24684405SMG2
50/50
1.132
24684505SMG3
50/50
0.7
24684305SMG1
50/50
0.41
942751AE2-291 GEN
Solar/Wind Harmer
41.038
316217AC1-145 GEN
Solar/Wind Harmer
4.611
316197AC1-042 GEN
Solar/Wind Harmer
3.495
942671AE2-283 GEN
Solar/Wind Harmer
9.411
270013AE1-250 PV
Solar/Wind Harmer
2.26
3146843MT LREL
Solar/Wind Helper
0.245
3146843MT LREL
Solar/Wind Helper
0.245
316034AC1-036 C
Solar/Wind Helper
0.132
24728405LEESVG
50/50
0.229
24684605SMG4
50/50
1.139
971683AH1-343 GEN
Solar/Wind Harmer
40.631
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.654
270197AD1-017 GEN1
Solar/Wind Harmer
1.53
958131AF2-107 GEN
Solar/Wind Harmer
2.297
316248AF1-058 C
Solar/Wind Helper
0.423
316131AB2-060 GEN
Solar/Wind Helper
0.889
315785AD2-033 C
Solar/Wind Helper
1.513
TVALTFEXP_TVA->PJM
CLTF
0.021
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.729
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.113
LGEELTFEXP_LGEE->PJM
CLTF
0.256
WECLTFEXP_WEC->PJM
CLTF
0.121
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.011
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.384
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.535
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.316
MECLTFEXP_MEC->PJM
CLTF
0.433
SIGELTFEXP_SIGE->PJM
CLTF
0.017

Details for AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.95 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:391.83
MW Contribution:12.85
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
0.767
24728405LEESVG
50/50
0.227
24684705SMG5
50/50
0.43
970481AG2-311 GEN
50/50
5.987
316003AC1-222 GEN
Solar/Wind Harmer
9.884
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.622
270574AD1-017 GEN2
Solar/Wind Harmer
5.018
270016AE1-250 BESS
Solar/Wind Harmer
2.228
970223AG2-152 GEN
Solar/Wind Harmer
12.847
270173AC1-122 GEN
Solar/Wind Harmer
1.377
962751AG1-124 GEN
Solar/Wind Harmer
5
316237AB2-079_GEN
Solar/Wind Helper
0.194
315687AD1-152 GEN
Solar/Wind Helper
0.686
24728405LEESVG
50/50
0.228
24684605SMG4
50/50
1.123
971683AH1-343 GEN
Solar/Wind Harmer
40.772
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.622
270197AD1-017 GEN1
Solar/Wind Harmer
1.508
958131AF2-107 GEN
Solar/Wind Harmer
2.266
316248AF1-058 C
Solar/Wind Helper
0.413
316131AB2-060 GEN
Solar/Wind Helper
0.85
315785AD2-033 C
Solar/Wind Helper
1.444
24684405SMG2
50/50
1.115
24684505SMG3
50/50
0.69
24684305SMG1
50/50
0.404
942751AE2-291 GEN
Solar/Wind Harmer
41.127
316217AC1-145 GEN
Solar/Wind Harmer
4.597
316197AC1-042 GEN
Solar/Wind Harmer
3.485
942671AE2-283 GEN
Solar/Wind Harmer
9.382
270013AE1-250 PV
Solar/Wind Harmer
2.228
3146843MT LREL
Solar/Wind Helper
0.238
3146843MT LREL
Solar/Wind Helper
0.238
316034AC1-036 C
Solar/Wind Helper
0.126
970865AG2-541 GEN
Solar/Wind Harmer
35.588
316123AC1-075 GEN
Solar/Wind Harmer
7.927
970165AG2-112 GEN
Solar/Wind Harmer
6.98
970163AG2-111 GEN
Solar/Wind Harmer
6.658
3147173SINAI
Solar/Wind Helper
0.307
3147243WELCO
Solar/Wind Helper
0.192
316118AC1-105 GEN
Solar/Wind Helper
1.06
316239AB2-077_GEN
Solar/Wind Helper
0.194
316238AB2-078_GEN
Solar/Wind Helper
0.194
3144303KENBRDG
Solar/Wind Helper
0.096
TVALTFEXP_TVA->PJM
CLTF
0.03
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.635
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.104
LGEELTFEXP_LGEE->PJM
CLTF
0.226
WECLTFEXP_WEC->PJM
CLTF
0.108
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.855
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.321
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.018
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.317
MECLTFEXP_MEC->PJM
CLTF
0.388
SIGELTFEXP_SIGE->PJM
CLTF
0.015

Details for AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line l/o AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:111.69 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:390.93
MW Contribution:12.85
Bus #Bus NameTypeMW Contribution
970865AG2-541 GEN
Solar/Wind Harmer
35.588
316123AC1-075 GEN
Solar/Wind Harmer
7.927
970165AG2-112 GEN
Solar/Wind Harmer
6.98
970163AG2-111 GEN
Solar/Wind Harmer
6.658
3147173SINAI
Solar/Wind Helper
0.307
3147243WELCO
Solar/Wind Helper
0.192
316118AC1-105 GEN
Solar/Wind Helper
1.06
316239AB2-077_GEN
Solar/Wind Helper
0.194
316238AB2-078_GEN
Solar/Wind Helper
0.194
3144303KENBRDG
Solar/Wind Helper
0.096
24684405SMG2
50/50
1.115
24684505SMG3
50/50
0.69
24684305SMG1
50/50
0.404
942751AE2-291 GEN
Solar/Wind Harmer
41.127
316217AC1-145 GEN
Solar/Wind Harmer
4.597
316197AC1-042 GEN
Solar/Wind Harmer
3.485
942671AE2-283 GEN
Solar/Wind Harmer
9.382
270013AE1-250 PV
Solar/Wind Harmer
2.228
3146843MT LREL
Solar/Wind Helper
0.238
3146843MT LREL
Solar/Wind Helper
0.238
316034AC1-036 C
Solar/Wind Helper
0.126
3151561HALLBR1
50/50
0.767
24728405LEESVG
50/50
0.227
24684705SMG5
50/50
0.43
970481AG2-311 GEN
50/50
5.987
316003AC1-222 GEN
Solar/Wind Harmer
9.884
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.622
270574AD1-017 GEN2
Solar/Wind Harmer
5.018
270016AE1-250 BESS
Solar/Wind Harmer
2.228
970223AG2-152 GEN
Solar/Wind Harmer
12.847
270173AC1-122 GEN
Solar/Wind Harmer
1.377
962751AG1-124 GEN
Solar/Wind Harmer
5
316237AB2-079_GEN
Solar/Wind Helper
0.194
315687AD1-152 GEN
Solar/Wind Helper
0.686
24728405LEESVG
50/50
0.228
24684605SMG4
50/50
1.123
971683AH1-343 GEN
Solar/Wind Harmer
40.772
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.622
270197AD1-017 GEN1
Solar/Wind Harmer
1.508
958131AF2-107 GEN
Solar/Wind Harmer
2.266
316248AF1-058 C
Solar/Wind Helper
0.413
316131AB2-060 GEN
Solar/Wind Helper
0.85
315785AD2-033 C
Solar/Wind Helper
1.444
TVALTFEXP_TVA->PJM
CLTF
0.03
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.635
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.104
LGEELTFEXP_LGEE->PJM
CLTF
0.226
WECLTFEXP_WEC->PJM
CLTF
0.108
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.855
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.321
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.018
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.317
MECLTFEXP_MEC->PJM
CLTF
0.388
SIGELTFEXP_SIGE->PJM
CLTF
0.015

Details for AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line l/o AEP_P7-1_#10778___SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10778___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:111.69 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:390.91
MW Contribution:12.85
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.116
24684505SMG3
50/50
0.69
24684305SMG1
50/50
0.404
942751AE2-291 GEN
Solar/Wind Harmer
41.127
316217AC1-145 GEN
Solar/Wind Harmer
4.597
316197AC1-042 GEN
Solar/Wind Harmer
3.485
942671AE2-283 GEN
Solar/Wind Harmer
9.383
270013AE1-250 PV
Solar/Wind Harmer
2.228
3146843MT LREL
Solar/Wind Helper
0.238
3146843MT LREL
Solar/Wind Helper
0.238
316034AC1-036 C
Solar/Wind Helper
0.126
970865AG2-541 GEN
Solar/Wind Harmer
35.588
316123AC1-075 GEN
Solar/Wind Harmer
7.927
970165AG2-112 GEN
Solar/Wind Harmer
6.98
970163AG2-111 GEN
Solar/Wind Harmer
6.658
3147173SINAI
Solar/Wind Helper
0.307
3147243WELCO
Solar/Wind Helper
0.192
316118AC1-105 GEN
Solar/Wind Helper
1.06
316239AB2-077_GEN
Solar/Wind Helper
0.194
316238AB2-078_GEN
Solar/Wind Helper
0.194
3144303KENBRDG
Solar/Wind Helper
0.096
3151561HALLBR1
50/50
0.767
24728405LEESVG
50/50
0.227
24684705SMG5
50/50
0.43
970481AG2-311 GEN
50/50
5.987
316003AC1-222 GEN
Solar/Wind Harmer
9.884
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.622
270574AD1-017 GEN2
Solar/Wind Harmer
5.018
270016AE1-250 BESS
Solar/Wind Harmer
2.228
970223AG2-152 GEN
Solar/Wind Harmer
12.847
270173AC1-122 GEN
Solar/Wind Harmer
1.377
962751AG1-124 GEN
Solar/Wind Harmer
5
316237AB2-079_GEN
Solar/Wind Helper
0.194
315687AD1-152 GEN
Solar/Wind Helper
0.686
24728405LEESVG
50/50
0.228
24684605SMG4
50/50
1.123
971683AH1-343 GEN
Solar/Wind Harmer
40.772
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.622
270197AD1-017 GEN1
Solar/Wind Harmer
1.508
958131AF2-107 GEN
Solar/Wind Harmer
2.266
316248AF1-058 C
Solar/Wind Helper
0.413
316131AB2-060 GEN
Solar/Wind Helper
0.85
315785AD2-033 C
Solar/Wind Helper
1.445
TVALTFEXP_TVA->PJM
CLTF
0.03
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.635
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.104
LGEELTFEXP_LGEE->PJM
CLTF
0.226
WECLTFEXP_WEC->PJM
CLTF
0.108
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.855
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.321
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.019
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.317
MECLTFEXP_MEC->PJM
CLTF
0.388
SIGELTFEXP_SIGE->PJM
CLTF
0.015

Details for AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line l/o AEP_P1-3_#10688_05EDANV2 230_4_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
Contingency Name:
AEP_P1-3_#10688_05EDANV2 230_4_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.84 %
Rating:285.76 MVA
Rating Type:B
MVA to Mitigate:311.03
MW Contribution:9.01
Bus #Bus NameTypeMW Contribution
970865AG2-541 GEN
Solar/Wind Harmer
27.029
316123AC1-075 GEN
Solar/Wind Harmer
0.894
970165AG2-112 GEN
Solar/Wind Harmer
5.301
970163AG2-111 GEN
Solar/Wind Harmer
5.057
3147173SINAI
Solar/Wind Helper
0.307
3147243WELCO
Solar/Wind Helper
0.192
316118AC1-105 GEN
Solar/Wind Helper
1.06
316239AB2-077_GEN
Solar/Wind Helper
0.194
316238AB2-078_GEN
Solar/Wind Helper
0.194
3144303KENBRDG
Solar/Wind Helper
0.096
3151561HALLBR1
50/50
0.767
24728405LEESVG
50/50
0.227
24684705SMG5
50/50
0.43
970481AG2-311 GEN
50/50
5.987
316003AC1-222 GEN
Solar/Wind Harmer
0.024
3147123OTTER R
Solar/Wind Harmer
0.189
3147312GRETNA
Solar/Wind Harmer
0.201
3146802CHATHAM
Solar/Wind Harmer
0.189
941801AE2-185 GEN
Solar/Wind Harmer
8.067
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.004
970223AG2-152 GEN
Solar/Wind Harmer
9.008
270173AC1-122 GEN
Solar/Wind Harmer
0.284
962751AG1-124 GEN
Solar/Wind Harmer
3.424
316237AB2-079_GEN
Solar/Wind Helper
0.194
315687AD1-152 GEN
Solar/Wind Helper
0.686
24728405LEESVG
50/50
0.228
24684605SMG4
50/50
1.123
24288905REUSENS
50/50
0.018
966251AG1-494 GEN
50/50
1.276
971683AH1-343 GEN
Solar/Wind Harmer
30.966
3147312GRETNA
Solar/Wind Harmer
0.05
941821AE2-187 GEN
Solar/Wind Harmer
8.067
270197AD1-017 GEN1
Solar/Wind Harmer
0.846
958131AF2-107 GEN
Solar/Wind Harmer
1.702
316248AF1-058 C
Solar/Wind Helper
0.413
316131AB2-060 GEN
Solar/Wind Helper
0.85
315785AD2-033 C
Solar/Wind Helper
1.444
24684405SMG2
50/50
1.115
24684505SMG3
50/50
0.69
24684305SMG1
50/50
0.404
942751AE2-291 GEN
Solar/Wind Harmer
31.236
316217AC1-145 GEN
Solar/Wind Harmer
0.003
316197AC1-042 GEN
Solar/Wind Harmer
0.003
942671AE2-283 GEN
Solar/Wind Harmer
6.274
270013AE1-250 PV
Solar/Wind Harmer
0.004
3146843MT LREL
Solar/Wind Helper
0.238
3146843MT LREL
Solar/Wind Helper
0.238
316034AC1-036 C
Solar/Wind Helper
0.126
TVALTFEXP_TVA->PJM
CLTF
0.03
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.635
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.104
LGEELTFEXP_LGEE->PJM
CLTF
0.226
WECLTFEXP_WEC->PJM
CLTF
0.108
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.855
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.321
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.018
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.317
MECLTFEXP_MEC->PJM
CLTF
0.388
SIGELTFEXP_SIGE->PJM
CLTF
0.015

Details for AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line l/o AEP_P1-2_#5366_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#5366_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.65 %
Rating:285.76 MVA
Rating Type:B
MVA to Mitigate:310.48
MW Contribution:8.98
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.112
3151561HALLBR1
50/50
0.767
24728405LEESVG
50/50
0.226
24684705SMG5
50/50
0.428
970481AG2-311 GEN
50/50
5.969
316003AC1-222 GEN
Solar/Wind Harmer
0.024
3147123OTTER R
Solar/Wind Harmer
0.189
3147312GRETNA
Solar/Wind Harmer
0.201
3146802CHATHAM
Solar/Wind Harmer
0.189
941801AE2-185 GEN
Solar/Wind Harmer
8.062
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.004
970223AG2-152 GEN
Solar/Wind Harmer
8.982
270173AC1-122 GEN
Solar/Wind Harmer
0.283
962751AG1-124 GEN
Solar/Wind Harmer
3.412
316237AB2-079_GEN
Solar/Wind Helper
0.192
315687AD1-152 GEN
Solar/Wind Helper
0.678
970865AG2-541 GEN
Solar/Wind Harmer
27.047
316123AC1-075 GEN
Solar/Wind Harmer
0.894
970165AG2-112 GEN
Solar/Wind Harmer
5.304
970163AG2-111 GEN
Solar/Wind Harmer
5.06
3147173SINAI
Solar/Wind Helper
0.306
3147243WELCO
Solar/Wind Helper
0.191
316118AC1-105 GEN
Solar/Wind Helper
1.054
316239AB2-077_GEN
Solar/Wind Helper
0.192
316238AB2-078_GEN
Solar/Wind Helper
0.192
3144303KENBRDG
Solar/Wind Helper
0.095
24728405LEESVG
50/50
0.227
24684605SMG4
50/50
1.12
24288905REUSENS
50/50
0.018
966251AG1-494 GEN
50/50
1.272
971683AH1-343 GEN
Solar/Wind Harmer
30.988
3147312GRETNA
Solar/Wind Harmer
0.05
941821AE2-187 GEN
Solar/Wind Harmer
8.062
270197AD1-017 GEN1
Solar/Wind Harmer
0.844
958131AF2-107 GEN
Solar/Wind Harmer
1.697
316248AF1-058 C
Solar/Wind Helper
0.411
316131AB2-060 GEN
Solar/Wind Helper
0.842
315785AD2-033 C
Solar/Wind Helper
1.43
24684505SMG3
50/50
0.688
24684305SMG1
50/50
0.403
942751AE2-291 GEN
Solar/Wind Harmer
31.25
316217AC1-145 GEN
Solar/Wind Harmer
0.003
316197AC1-042 GEN
Solar/Wind Harmer
0.003
942671AE2-283 GEN
Solar/Wind Harmer
6.271
270013AE1-250 PV
Solar/Wind Harmer
0.004
3146843MT LREL
Solar/Wind Helper
0.237
3146843MT LREL
Solar/Wind Helper
0.237
316034AC1-036 C
Solar/Wind Helper
0.124
TVALTFEXP_TVA->PJM
CLTF
0.033
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.619
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.103
LGEELTFEXP_LGEE->PJM
CLTF
0.22
WECLTFEXP_WEC->PJM
CLTF
0.105
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.823
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.308
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.917
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.318
MECLTFEXP_MEC->PJM
CLTF
0.38
SIGELTFEXP_SIGE->PJM
CLTF
0.015

Details for AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line l/o AEP_P7-1_#10781___SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10781___SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.72 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:366.51
MW Contribution:7.33
Bus #Bus NameTypeMW Contribution
942751AE2-291 GEN
Solar/Wind Harmer
40.562
316217AC1-145 GEN
Solar/Wind Harmer
4.414
316197AC1-042 GEN
Solar/Wind Harmer
3.346
942671AE2-283 GEN
Solar/Wind Harmer
9.009
270013AE1-250 PV
Solar/Wind Harmer
1.363
3146843MT LREL
Solar/Wind Helper
0.248
3146843MT LREL
Solar/Wind Helper
0.248
316034AC1-036 C
Solar/Wind Helper
0.133
970865AG2-541 GEN
Solar/Wind Harmer
35.284
316123AC1-075 GEN
Solar/Wind Harmer
7.837
970165AG2-112 GEN
Solar/Wind Harmer
6.901
970163AG2-111 GEN
Solar/Wind Harmer
6.583
3147173SINAI
Solar/Wind Helper
0.318
3147243WELCO
Solar/Wind Helper
0.199
316118AC1-105 GEN
Solar/Wind Helper
1.1
316239AB2-077_GEN
Solar/Wind Helper
0.205
316238AB2-078_GEN
Solar/Wind Helper
0.205
3144303KENBRDG
Solar/Wind Helper
0.102
3151561HALLBR1
50/50
0.743
24728405LEESVG
50/50
0.21
316003AC1-222 GEN
Solar/Wind Harmer
9.819
3147123OTTER R
Solar/Wind Harmer
-0.02
3147312GRETNA
Solar/Wind Harmer
-0.022
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
10.198
270173AC1-122 GEN
Solar/Wind Harmer
1.218
270574AD1-017 GEN2
Solar/Wind Harmer
3.601
270016AE1-250 BESS
Solar/Wind Harmer
1.363
970223AG2-152 GEN
Solar/Wind Harmer
7.327
962751AG1-124 GEN
Solar/Wind Harmer
4.804
316237AB2-079_GEN
Solar/Wind Helper
0.205
315687AD1-152 GEN
Solar/Wind Helper
0.735
24728405LEESVG
50/50
0.21
971683AH1-343 GEN
Solar/Wind Harmer
40.466
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
10.198
270197AD1-017 GEN1
Solar/Wind Harmer
1.082
958131AF2-107 GEN
Solar/Wind Harmer
2.161
316248AF1-058 C
Solar/Wind Helper
0.428
316131AB2-060 GEN
Solar/Wind Helper
0.9
315785AD2-033 C
Solar/Wind Helper
1.533
LAGNLTFEXP_LAGN->PJM
CLTF
0.016
TVALTFEXP_TVA->PJM
CLTF
0.056
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.165
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.114
LGEELTFEXP_LGEE->PJM
CLTF
0.278
WECLTFEXP_WEC->PJM
CLTF
0.133
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.003
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.373
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.967
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.446
MECLTFEXP_MEC->PJM
CLTF
0.486
SIGELTFEXP_SIGE->PJM
CLTF
0.019

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.1 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5539.41
MW Contribution:12.09
Bus #Bus NameTypeMW Contribution
970533AG2-339 GEN
50/50
66.733
970531AG2-338 GEN
50/50
26.693
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
44.982
970099AG2-077 GEN
Solar/Wind Harmer
50.723
971741AH1-377 GEN
Solar/Wind Harmer
33.569
970301AG2-198 GEN
Solar/Wind Harmer
13.228
3146843MT LREL
Solar/Wind Harmer
0.286
3146843MT LREL
Solar/Wind Harmer
0.286
964791AG1-342 GEN
Solar/Wind Harmer
5.488
316222AC1-221 GEN
Solar/Wind Harmer
1.175
962561AG1-105 GEN
Solar/Wind Harmer
13.485
939181AE1-148 GEN
Solar/Wind Harmer
12.41
313527AB2-043 GEN
Solar/Wind Harmer
0.003
970323AG2-213 GEN
Solar/Wind Harmer
10.445
971775AH1-396 GEN
Solar/Wind Harmer
0.392
316034AC1-036 C
Solar/Wind Harmer
0.018
958211AF2-115 GEN
Solar/Wind Harmer
2.845
963191AG1-168 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.234
3147133PAMPLIN
Solar/Wind Harmer
0.187
942751AE2-291 GEN
Solar/Wind Harmer
11.476
270013AE1-250 PV
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.546
3146776BUCKING
Solar/Wind Harmer
0.044
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.276
316263AC1-034 GEN
Solar/Wind Harmer
4.449
961601AG1-000A GEN
Solar/Wind Harmer
2.035
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
47.73
957481AF2-042 GEN
Solar/Wind Harmer
126.807
315693AD1-088 GEN
Solar/Wind Harmer
20.818
962491AG1-098 GEN
Solar/Wind Harmer
24.385
315687AD1-152 GEN
Solar/Wind Harmer
0.013
316003AC1-222 GEN
Solar/Wind Harmer
0.008
970401AG2-262 GEN
Solar/Wind Harmer
1.677
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
17.979
963171AG1-166 GEN
Solar/Wind Harmer
1.264
971563AH1-280 GEN
Solar/Wind Harmer
2.529
3146926FARMVIL
Solar/Wind Harmer
0.131
971065AG2-659 GEN
Solar/Wind Harmer
8.445
316129AC1-054 GEN
Solar/Wind Harmer
0.698
970223AG2-152 GEN
Solar/Wind Harmer
12.094
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.088
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.055
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.099
941801AE2-185 GEN
Solar/Wind Harmer
4.212
270030AE2-140 GEN
Solar/Wind Harmer
13.804
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.094
316359AB2-059 GEN
Solar/Wind Harmer
0.421
316049AB1-081 GEN
Solar/Wind Harmer
0.67
3142053HEARTS
Solar/Wind Harmer
0.206
316294AC1-161 GEN
Solar/Wind Helper
7.693
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
941031AE2-094 GEN
Solar/Wind Harmer
138.271
944011AF1-069 GEN
Solar/Wind Harmer
45.178
970673AG2-436 GEN
Solar/Wind Harmer
149.315
970673AG2-436 GEN
Solar/Wind Harmer
99.544
971967AH1-528 GEN
Solar/Wind Harmer
95.481
970085AG2-068 GEN
Solar/Wind Harmer
31.82
970581AG2-369 GEN
Solar/Wind Harmer
27.365
3147173SINAI
Solar/Wind Harmer
0.309
3147243WELCO
Solar/Wind Harmer
0.193
316118AC1-105 GEN
Solar/Wind Harmer
0.768
970865AG2-541 GEN
Solar/Wind Harmer
9.078
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.118
3144303KENBRDG
Solar/Wind Harmer
0.196
970683AG2-441 GEN
Solar/Wind Harmer
16.053
970681AG2-440 GEN
Solar/Wind Harmer
12.842
946301AF1-294 GEN
Solar/Wind Harmer
4.678
961791AG1-021 GEN
Solar/Wind Harmer
2.276
315657AE1-056 GEN
Solar/Wind Harmer
8.085
316123AC1-075 GEN
Solar/Wind Harmer
0.315
970165AG2-112 GEN
Solar/Wind Harmer
1.87
970163AG2-111 GEN
Solar/Wind Harmer
1.784
970831AG2-522 GEN
Solar/Wind Harmer
7.35
970285AG2-188 GEN
Solar/Wind Harmer
12.402
971845AH1-439 GEN
Solar/Wind Harmer
6.507
270069AE2-166 C O1
Solar/Wind Harmer
0.004
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
53.421
316478AD1-087 GEN
Solar/Wind Harmer
1.525
316486AD2-202 GEN
Solar/Wind Harmer
0.448
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
13.182
316283AC2-100 C
Solar/Wind Harmer
0.55
971683AH1-343 GEN
Solar/Wind Harmer
10.2
316131AB2-060 GEN
Solar/Wind Harmer
0.796
964241AG1-285 GEN
Solar/Wind Harmer
16.703
315785AD2-033 C
Solar/Wind Harmer
2.003
970257AG2-171 GEN
Solar/Wind Harmer
7.834
959311AF2-222 GEN
Solar/Wind Harmer
21.656
963181AG1-167 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.736
971193AH1-056 GEN
Solar/Wind Harmer
14.274
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.131
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
0.943
3146776BUCKING
Solar/Wind Harmer
0.049
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.212
270336AE1-100 GEN
Solar/Wind Harmer
0.003
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.117
971623AH1-311 GEN
Solar/Wind Harmer
0.234
961601AG1-000A GEN
Solar/Wind Harmer
8.141
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
NYPJM->LTFIMP_NY
CLTF
2.382
LGEELTFEXP_LGEE->PJM
CLTF
2.675
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 51192_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51192_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.36 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:6013.11
MW Contribution:17.25
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
62.844
957481AF2-042 GEN
Solar/Wind Harmer
166.962
315693AD1-088 GEN
Solar/Wind Harmer
24.364
962491AG1-098 GEN
Solar/Wind Harmer
32.107
315687AD1-152 GEN
Solar/Wind Harmer
5.339
316003AC1-222 GEN
Solar/Wind Harmer
3.203
970401AG2-262 GEN
Solar/Wind Harmer
2.096
316237AB2-079_GEN
Solar/Wind Harmer
0.866
970685AG2-442 GEN
Solar/Wind Harmer
23.673
963171AG1-166 GEN
Solar/Wind Harmer
3.329
971563AH1-280 GEN
Solar/Wind Harmer
3.329
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.119
316129AC1-054 GEN
Solar/Wind Harmer
1.828
970223AG2-152 GEN
Solar/Wind Harmer
17.247
270016AE1-250 BESS
Solar/Wind Harmer
2.846
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.591
316322AB2-045
Solar/Wind Harmer
0.516
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.545
270030AE2-140 GEN
Solar/Wind Harmer
19.786
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.774
316049AB1-081 GEN
Solar/Wind Harmer
1.419
3142053HEARTS
Solar/Wind Harmer
0.155
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
970533AG2-339 GEN
50/50
66.733
970531AG2-338 GEN
50/50
26.693
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
168.81
316478AD1-087 GEN
Solar/Wind Harmer
4.25
316486AD2-202 GEN
Solar/Wind Harmer
1.245
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
1.046
960061AF2-297 GEN
Solar/Wind Harmer
17.357
316283AC2-100 C
Solar/Wind Harmer
2.974
971683AH1-343 GEN
Solar/Wind Harmer
13.43
316131AB2-060 GEN
Solar/Wind Harmer
3.068
964241AG1-285 GEN
Solar/Wind Harmer
21.992
315785AD2-033 C
Solar/Wind Harmer
6.274
970257AG2-171 GEN
Solar/Wind Harmer
10.314
959311AF2-222 GEN
Solar/Wind Harmer
28.571
963181AG1-167 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.462
942461AE2-259 GEN
Solar/Wind Harmer
3.832
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.378
270197AD1-017 GEN1
Solar/Wind Harmer
1.68
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
941031AE2-094 GEN
Solar/Wind Harmer
158.157
944011AF1-069 GEN
Solar/Wind Harmer
49.556
970673AG2-436 GEN
Solar/Wind Harmer
165.209
970673AG2-436 GEN
Solar/Wind Harmer
83.65
971967AH1-528 GEN
Solar/Wind Harmer
126.052
970085AG2-068 GEN
Solar/Wind Harmer
41.896
970581AG2-369 GEN
Solar/Wind Harmer
36.031
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.3
970865AG2-541 GEN
Solar/Wind Harmer
11.953
316239AB2-077_GEN
Solar/Wind Harmer
0.866
316238AB2-078_GEN
Solar/Wind Harmer
0.866
971443AH1-215 GEN
Solar/Wind Harmer
5.422
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.136
970681AG2-440 GEN
Solar/Wind Harmer
16.909
946301AF1-294 GEN
Solar/Wind Harmer
6.825
961791AG1-021 GEN
Solar/Wind Harmer
3.329
270455AD2-022 GEN
Solar/Wind Harmer
4.714
270457AD2-023 GEN
Solar/Wind Harmer
2.39
315657AE1-056 GEN
Solar/Wind Harmer
9.877
316123AC1-075 GEN
Solar/Wind Harmer
2.797
970165AG2-112 GEN
Solar/Wind Harmer
2.462
970163AG2-111 GEN
Solar/Wind Harmer
2.349
970831AG2-522 GEN
Solar/Wind Harmer
9.678
970285AG2-188 GEN
Solar/Wind Harmer
15.412
971845AH1-439 GEN
Solar/Wind Harmer
8.567
270069AE2-166 C O1
Solar/Wind Harmer
2.422
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
59.226
970099AG2-077 GEN
Solar/Wind Harmer
66.785
971741AH1-377 GEN
Solar/Wind Harmer
44.199
970301AG2-198 GEN
Solar/Wind Harmer
17.416
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.86
316222AC1-221 GEN
Solar/Wind Harmer
3.218
962561AG1-105 GEN
Solar/Wind Harmer
17.755
939181AE1-148 GEN
Solar/Wind Harmer
16.34
313527AB2-043 GEN
Solar/Wind Harmer
4.631
970323AG2-213 GEN
Solar/Wind Harmer
13.752
971775AH1-396 GEN
Solar/Wind Harmer
1.958
316034AC1-036 C
Solar/Wind Harmer
0.51
958211AF2-115 GEN
Solar/Wind Harmer
4.162
963191AG1-168 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.11
270013AE1-250 PV
Solar/Wind Harmer
2.846
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.4
316197AC1-042 GEN
Solar/Wind Harmer
1.819
942671AE2-283 GEN
Solar/Wind Harmer
4.898
316263AC1-034 GEN
Solar/Wind Harmer
6.166
961601AG1-000A GEN
Solar/Wind Harmer
5.056
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.844
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.545
270336AE1-100 GEN
Solar/Wind Harmer
1.569
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
5.12
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
NYPJM->LTFIMP_NY
CLTF
2.382
LGEELTFEXP_LGEE->PJM
CLTF
2.675
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 51172_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51172_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.82 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5986.29
MW Contribution:17.2
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
11.056
3151051BRUNSWICKS1
50/50
17.38
3151021BRUNSWICKG1
50/50
8.374
971451AH1-221 GEN
50/50
25.435
3151531CLOVER1
50/50
9.312
3151601KERR 3
50/50
0.538
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.8
971629AH1-314 GEN
50/50
17.875
3151561HALLBR1
50/50
0.366
970919AG2-571 GEN
Solar/Wind Harmer
21.227
970087AG2-069 GEN
Solar/Wind Harmer
62.431
957481AF2-042 GEN
Solar/Wind Harmer
166.01
315693AD1-088 GEN
Solar/Wind Harmer
24.233
962491AG1-098 GEN
Solar/Wind Harmer
31.935
315687AD1-152 GEN
Solar/Wind Harmer
5.313
316003AC1-222 GEN
Solar/Wind Harmer
3.193
970401AG2-262 GEN
Solar/Wind Harmer
2.094
316237AB2-079_GEN
Solar/Wind Harmer
0.868
970685AG2-442 GEN
Solar/Wind Harmer
23.682
963171AG1-166 GEN
Solar/Wind Harmer
3.328
971563AH1-280 GEN
Solar/Wind Harmer
3.328
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.224
316129AC1-054 GEN
Solar/Wind Harmer
1.849
970223AG2-152 GEN
Solar/Wind Harmer
17.201
270016AE1-250 BESS
Solar/Wind Harmer
2.839
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.577
316322AB2-045
Solar/Wind Harmer
0.514
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.53
270030AE2-140 GEN
Solar/Wind Harmer
19.734
315244AE2-183_ST
50/50
19.115
963041AG1-153 GEN
50/50
16.957
3151541CLOVER2
50/50
9.268
3151611KERR 4
50/50
0.538
3151621KERR 5
50/50
0.538
3151631KERR 6
50/50
0.538
3151641KERR 7
50/50
0.538
941031AE2-094 GEN
Solar/Wind Harmer
157.012
944011AF1-069 GEN
Solar/Wind Harmer
49.197
970673AG2-436 GEN
Solar/Wind Harmer
164.043
970673AG2-436 GEN
Solar/Wind Harmer
83.06
971967AH1-528 GEN
Solar/Wind Harmer
125.223
970085AG2-068 GEN
Solar/Wind Harmer
41.62
970581AG2-369 GEN
Solar/Wind Harmer
35.794
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.295
970865AG2-541 GEN
Solar/Wind Harmer
11.917
316239AB2-077_GEN
Solar/Wind Harmer
0.868
316238AB2-078_GEN
Solar/Wind Harmer
0.868
971443AH1-215 GEN
Solar/Wind Harmer
5.428
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.145
970681AG2-440 GEN
Solar/Wind Harmer
16.916
946301AF1-294 GEN
Solar/Wind Harmer
6.823
961791AG1-021 GEN
Solar/Wind Harmer
3.328
970533AG2-339 GEN
50/50
66.25
970531AG2-338 GEN
50/50
26.5
315242AE2-183_GT2
50/50
11.056
315241AE2-183_GT1
50/50
10.988
972185AH1-677 GEN
50/50
39.858
3151041BRUNSWICKG3
50/50
8.374
972187AH1-678 GEN
50/50
19.217
3152661PLYWOOD A
50/50
0.67
970535AG2-341 GEN
50/50
4.577
3144293JTRSVLE
50/50
0.8
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
58.849
970099AG2-077 GEN
Solar/Wind Harmer
66.404
971741AH1-377 GEN
Solar/Wind Harmer
43.978
970301AG2-198 GEN
Solar/Wind Harmer
17.332
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.854
316222AC1-221 GEN
Solar/Wind Harmer
3.208
962561AG1-105 GEN
Solar/Wind Harmer
17.747
939181AE1-148 GEN
Solar/Wind Harmer
16.378
313527AB2-043 GEN
Solar/Wind Harmer
4.643
970323AG2-213 GEN
Solar/Wind Harmer
13.768
971775AH1-396 GEN
Solar/Wind Harmer
1.961
316034AC1-036 C
Solar/Wind Harmer
0.511
958211AF2-115 GEN
Solar/Wind Harmer
4.16
963191AG1-168 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.066
270013AE1-250 PV
Solar/Wind Harmer
2.839
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.394
316197AC1-042 GEN
Solar/Wind Harmer
1.815
942671AE2-283 GEN
Solar/Wind Harmer
4.885
316263AC1-034 GEN
Solar/Wind Harmer
6.316
961601AG1-000A GEN
Solar/Wind Harmer
5.186
316036AC1-147 C
Solar/Wind Helper
0.59
3142956BIRDNECK
Solar/Wind Helper
0.259
316316AC1-027 C
Solar/Wind Helper
0.606
316185AD1-033 GEN
Solar/Wind Helper
1.799
3145506HICKORY
Solar/Wind Helper
1.507
3145506HICKORY
Solar/Wind Helper
0.904
3145506HICKORY
Solar/Wind Helper
0.226
316236AE1-162_GEN
Solar/Wind Helper
0.498
316339AD2-160 GEN
Solar/Wind Helper
1.397
316018AA1-139 ULT2
Solar/Wind Helper
1.567
316017AA1-139 ULT1
Solar/Wind Helper
1.665
3137176SLIGO L2192
Solar/Wind Helper
1.432
3130086AYDLETT
Solar/Wind Helper
1.421
316033AB2-134 GEN
Solar/Wind Helper
1.19
315697AD1-025 GEN
Solar/Wind Helper
3.953
3146386ELIZ CT
Solar/Wind Helper
0.331
316240AF1-291 C
Solar/Wind Helper
0.444
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.318
316075AC2-137 C
Solar/Wind Helper
0.467
316077AC2-138 C
Solar/Wind Helper
0.286
316431W1029_GEN1
Solar/Wind Helper
1.225
316433W1029_GEN2
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.817
316049AB1-081 GEN
Solar/Wind Harmer
1.454
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.785
316375AC2-012 GEN
Solar/Wind Helper
1.014
3145336SMITFLD
Solar/Wind Helper
1.482
316388AE2-253 GEN
Solar/Wind Helper
1.397
3146456SLIGO L269
Solar/Wind Helper
0.359
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.402
316159AE1-175 C
Solar/Wind Helper
0.529
316381AD1-082 GEN
Solar/Wind Helper
1.758
316458AB2-190 GEN2
Solar/Wind Helper
1.933
3141766HARMONY
Solar/Wind Helper
0.065
3138133OCRAN
Solar/Wind Helper
0.193
3142433PROV 92
Solar/Wind Helper
1.275
3142543TWELFTH
Solar/Wind Helper
0.029
964211AG1-282 GEN
Solar/Wind Helper
0.412
3141726DUNNSVL
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.961
3146516WINFALL
Solar/Wind Helper
0.297
316337AD2-073 GEN
Solar/Wind Helper
0.448
3142416OLDCHRC
Solar/Wind Helper
0.759
3142416OLDCHRC
Solar/Wind Helper
0.291
3143526WINTERP
Solar/Wind Helper
1.499
3143226MDLTHAN
Solar/Wind Helper
0.284
315800Z1-036_GEN1
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
270455AD2-022 GEN
Solar/Wind Harmer
4.701
270457AD2-023 GEN
Solar/Wind Harmer
2.384
315657AE1-056 GEN
Solar/Wind Harmer
9.869
316123AC1-075 GEN
Solar/Wind Harmer
2.789
970165AG2-112 GEN
Solar/Wind Harmer
2.455
970163AG2-111 GEN
Solar/Wind Harmer
2.342
970831AG2-522 GEN
Solar/Wind Harmer
9.813
970285AG2-188 GEN
Solar/Wind Harmer
15.354
971845AH1-439 GEN
Solar/Wind Harmer
8.535
270069AE2-166 C O1
Solar/Wind Harmer
2.415
319010AE1-072 C
Solar/Wind Helper
4.079
3143316POE
Solar/Wind Helper
1.407
316305AF2-043 C
Solar/Wind Helper
0.473
316369SG1_INVT
Solar/Wind Helper
1.664
957831AF2-077 GEN
Solar/Wind Helper
0.466
316132AB2-190 GEN1
Solar/Wind Helper
1.933
316349AD2-085 GEN
Solar/Wind Helper
1.523
313526AB2-022
Solar/Wind Helper
0.505
957601AF2-054 GEN
Solar/Wind Helper
0.438
3141873WAN 176
Solar/Wind Helper
0.065
315662AE1-191 GEN
Solar/Wind Helper
1.747
315666AE1-190 GEN
Solar/Wind Helper
0.437
316059AD1-063 C
Solar/Wind Helper
0.326
3141913WHIT STONE
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3138133OCRAN
Solar/Wind Helper
0.097
3143873LANEXA
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.128
316321Z2-027
Solar/Wind Helper
0.487
3145176PASQUOTANK
Solar/Wind Helper
0.198
3141813NORNECK
Solar/Wind Helper
0.304
316312AB1-027
Solar/Wind Helper
0.556
316233AE1-074 FULL
Solar/Wind Helper
0.44
316223AC1-118
Solar/Wind Helper
0.438
316315AB2-025 C
Solar/Wind Helper
0.418
315611Z1-036_GEN2
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
3130156CHOWAN
Solar/Wind Helper
0.226
3151031BRUNSWICKG2
50/50
8.374
970413AG2-270 GEN
50/50
40.637
3151591KERR 2
50/50
0.538
3144293JTRSVLE
50/50
0.8
970917AG2-570 GEN
Solar/Wind Harmer
167.695
3146516WINFALL
Solar/Wind Helper
0.297
3143526WINTERP
Solar/Wind Helper
1.499
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
966871AG1-558 GEN
Solar/Wind Helper
0.374
3144356SAPONY
Solar/Wind Helper
0.492
316468AD1-105 GEN
Solar/Wind Helper
1.305
316478AD1-087 GEN
Solar/Wind Harmer
4.227
316486AD2-202 GEN
Solar/Wind Harmer
1.238
970909AG2-566 GEN
Solar/Wind Harmer
3.291
316248AF1-058 C
Solar/Wind Harmer
1.043
960061AF2-297 GEN
Solar/Wind Harmer
17.305
316283AC2-100 C
Solar/Wind Harmer
2.965
971683AH1-343 GEN
Solar/Wind Harmer
13.39
316131AB2-060 GEN
Solar/Wind Harmer
3.076
964241AG1-285 GEN
Solar/Wind Harmer
22.038
315785AD2-033 C
Solar/Wind Harmer
6.282
970257AG2-171 GEN
Solar/Wind Harmer
10.326
959311AF2-222 GEN
Solar/Wind Harmer
28.597
963181AG1-167 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.449
942461AE2-259 GEN
Solar/Wind Harmer
3.824
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.375
270197AD1-017 GEN1
Solar/Wind Harmer
1.676
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.834
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.53
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.564
961601AG1-000A GEN
Solar/Wind Harmer
5.252
315773AC2-141 GEN
Solar/Wind Helper
9.163
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.058
3145336SMITFLD
Solar/Wind Helper
0.148
3146456SLIGO L269
Solar/Wind Helper
0.359
316382AG1-145 C
Solar/Wind Helper
0.469
315839AE2-212 C
Solar/Wind Helper
0.457
316320Y1-086
Solar/Wind Helper
0.148
316156AD2-030 GEN
Solar/Wind Helper
0.492
316280AD1-041 GEN
Solar/Wind Helper
1.092
3142946ENON
Solar/Wind Helper
0.105
316484AD2-074 GEN
Solar/Wind Helper
0.607
316404AE1-155 C
Solar/Wind Helper
2.624
316435W1029_GEN3
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3141906WESTMOR
Solar/Wind Helper
0.115
3146626S HERTFORD
Solar/Wind Helper
0.28
316473AC1-191 GEN
Solar/Wind Helper
1.696
3145273HOLLAND
Solar/Wind Helper
0.188
966881AG1-559 GEN
Solar/Wind Helper
0.329
3146376EDENTON
Solar/Wind Helper
0.226
LAGNLTFEXP_LAGN->PJM
CLTF
14.626
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.161
TVALTFEXP_TVA->PJM
CLTF
7.294
CPLELTFEXP_CPLE->PJM
CLTF
19.708
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.004
NYPJM->LTFIMP_NY
CLTF
2.38
LGEELTFEXP_LGEE->PJM
CLTF
2.666
WECLTFEXP_WEC->PJM
CLTF
1.395
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.554
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.081
MECLTFEXP_MEC->PJM
CLTF
7.343
SIGELTFEXP_SIGE->PJM
CLTF
0.22

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 511T544_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T544_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.15 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5902.9
MW Contribution:17.06
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
18.952
963041AG1-153 GEN
50/50
16.812
3151541CLOVER2
50/50
9.183
3151611KERR 4
50/50
0.532
3151621KERR 5
50/50
0.532
3151631KERR 6
50/50
0.532
3151641KERR 7
50/50
0.532
941031AE2-094 GEN
Solar/Wind Harmer
155.676
944011AF1-069 GEN
Solar/Wind Harmer
48.778
970673AG2-436 GEN
Solar/Wind Harmer
162.646
970673AG2-436 GEN
Solar/Wind Harmer
82.352
971967AH1-528 GEN
Solar/Wind Harmer
124.141
970085AG2-068 GEN
Solar/Wind Harmer
41.268
970581AG2-369 GEN
Solar/Wind Harmer
35.491
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.271
970865AG2-541 GEN
Solar/Wind Harmer
11.801
316239AB2-077_GEN
Solar/Wind Harmer
0.856
316238AB2-078_GEN
Solar/Wind Harmer
0.856
971443AH1-215 GEN
Solar/Wind Harmer
5.352
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
20.851
970681AG2-440 GEN
Solar/Wind Harmer
16.681
946301AF1-294 GEN
Solar/Wind Harmer
6.73
961791AG1-021 GEN
Solar/Wind Harmer
3.283
270455AD2-022 GEN
Solar/Wind Harmer
4.664
270457AD2-023 GEN
Solar/Wind Harmer
2.365
315657AE1-056 GEN
Solar/Wind Harmer
9.735
316123AC1-075 GEN
Solar/Wind Harmer
2.761
970165AG2-112 GEN
Solar/Wind Harmer
2.431
970163AG2-111 GEN
Solar/Wind Harmer
2.319
970831AG2-522 GEN
Solar/Wind Harmer
9.696
970285AG2-188 GEN
Solar/Wind Harmer
15.118
971845AH1-439 GEN
Solar/Wind Harmer
8.397
270069AE2-166 C O1
Solar/Wind Harmer
2.394
3143316POE
Solar/Wind Helper
1.57
316132AB2-190 GEN1
Solar/Wind Helper
1.893
316369SG1_INVT
Solar/Wind Helper
1.59
957831AF2-077 GEN
Solar/Wind Helper
0.437
316315AB2-025 C
Solar/Wind Helper
0.494
957601AF2-054 GEN
Solar/Wind Helper
0.418
3141873WAN 176
Solar/Wind Helper
0.062
315662AE1-191 GEN
Solar/Wind Helper
1.674
315666AE1-190 GEN
Solar/Wind Helper
0.419
3143873LANEXA
Solar/Wind Helper
0.186
316059AD1-063 C
Solar/Wind Helper
0.312
3141913WHIT STONE
Solar/Wind Helper
0.309
3138133OCRAN
Solar/Wind Helper
0.093
3141783LANCAST
Solar/Wind Helper
0.184
3141783LANCAST
Solar/Wind Helper
0.123
319010AE1-072 C
Solar/Wind Helper
3.5
316349AD2-085 GEN
Solar/Wind Helper
1.396
316305AF2-043 C
Solar/Wind Helper
0.402
3141813NORNECK
Solar/Wind Helper
0.293
316233AE1-074 FULL
Solar/Wind Helper
0.446
316312AB1-027
Solar/Wind Helper
0.55
313526AB2-022
Solar/Wind Helper
0.431
316223AC1-118
Solar/Wind Helper
0.424
3146486SUNBURY
Solar/Wind Helper
0.274
3146486SUNBURY
Solar/Wind Helper
0.274
316321Z2-027
Solar/Wind Helper
0.414
3145176PASQUOTANK
Solar/Wind Helper
0.168
970533AG2-339 GEN
50/50
65.686
970531AG2-338 GEN
50/50
26.274
315242AE2-183_GT2
50/50
10.962
315241AE2-183_GT1
50/50
10.894
972185AH1-677 GEN
50/50
39.518
3151041BRUNSWICKG3
50/50
8.303
972187AH1-678 GEN
50/50
19.053
3152661PLYWOOD A
50/50
0.663
970535AG2-341 GEN
50/50
4.519
3144293JTRSVLE
50/50
0.79
3144293JTRSVLE
50/50
0.665
970933AG2-581 GEN
Solar/Wind Harmer
58.334
970099AG2-077 GEN
Solar/Wind Harmer
65.804
971741AH1-377 GEN
Solar/Wind Harmer
43.523
970301AG2-198 GEN
Solar/Wind Harmer
17.145
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.775
316222AC1-221 GEN
Solar/Wind Harmer
3.182
962561AG1-105 GEN
Solar/Wind Harmer
17.536
939181AE1-148 GEN
Solar/Wind Harmer
16.186
313527AB2-043 GEN
Solar/Wind Harmer
4.576
970323AG2-213 GEN
Solar/Wind Harmer
13.574
971775AH1-396 GEN
Solar/Wind Harmer
1.933
316034AC1-036 C
Solar/Wind Harmer
0.503
958211AF2-115 GEN
Solar/Wind Harmer
4.103
963191AG1-168 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
14.918
270013AE1-250 PV
Solar/Wind Harmer
2.815
3146776BUCKING
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.37
316197AC1-042 GEN
Solar/Wind Harmer
1.797
942671AE2-283 GEN
Solar/Wind Harmer
4.838
316263AC1-034 GEN
Solar/Wind Harmer
6.29
961601AG1-000A GEN
Solar/Wind Harmer
5.16
316240AF1-291 C
Solar/Wind Helper
0.471
316036AC1-147 C
Solar/Wind Helper
0.511
316236AE1-162_GEN
Solar/Wind Helper
0.447
316316AC1-027 C
Solar/Wind Helper
0.524
3142956BIRDNECK
Solar/Wind Helper
0.223
316033AB2-134 GEN
Solar/Wind Helper
1.137
315697AD1-025 GEN
Solar/Wind Helper
3.779
316185AD1-033 GEN
Solar/Wind Helper
1.551
3145506HICKORY
Solar/Wind Helper
1.298
3145506HICKORY
Solar/Wind Helper
0.779
3145506HICKORY
Solar/Wind Helper
0.195
3144356SAPONY
Solar/Wind Helper
0.581
316339AD2-160 GEN
Solar/Wind Helper
1.201
316018AA1-139 ULT2
Solar/Wind Helper
1.346
316017AA1-139 ULT1
Solar/Wind Helper
1.43
3142946ENON
Solar/Wind Helper
0.031
3137176SLIGO L2192
Solar/Wind Helper
1.229
3130086AYDLETT
Solar/Wind Helper
1.219
316487AF1-042 GEN
Solar/Wind Helper
0.305
316075AC2-137 C
Solar/Wind Helper
0.459
316077AC2-138 C
Solar/Wind Helper
0.276
3143526WINTERP
Solar/Wind Helper
1.519
3146386ELIZ CT
Solar/Wind Helper
0.283
966871AG1-558 GEN
Solar/Wind Helper
0.376
316468AD1-105 GEN
Solar/Wind Helper
1.308
316431W1029_GEN1
Solar/Wind Helper
1.037
316433W1029_GEN2
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146626S HERTFORD
Solar/Wind Helper
0.236
3146626S HERTFORD
Solar/Wind Helper
0.236
315243AE2-183_GT3
50/50
10.962
3151051BRUNSWICKS1
50/50
17.232
3151021BRUNSWICKG1
50/50
8.303
971451AH1-221 GEN
50/50
25.218
3151531CLOVER1
50/50
9.227
3151601KERR 3
50/50
0.532
3151581KERR 1
50/50
0.19
3144293JTRSVLE
50/50
0.79
971629AH1-314 GEN
50/50
17.731
3151561HALLBR1
50/50
0.363
970919AG2-571 GEN
Solar/Wind Harmer
21.047
970087AG2-069 GEN
Solar/Wind Harmer
61.902
957481AF2-042 GEN
Solar/Wind Harmer
164.509
315693AD1-088 GEN
Solar/Wind Harmer
24.007
962491AG1-098 GEN
Solar/Wind Harmer
31.634
315687AD1-152 GEN
Solar/Wind Harmer
5.265
316003AC1-222 GEN
Solar/Wind Harmer
3.162
970401AG2-262 GEN
Solar/Wind Harmer
2.07
316237AB2-079_GEN
Solar/Wind Harmer
0.856
970685AG2-442 GEN
Solar/Wind Harmer
23.354
963171AG1-166 GEN
Solar/Wind Harmer
3.283
971563AH1-280 GEN
Solar/Wind Harmer
3.283
3146926FARMVIL
Solar/Wind Harmer
-0.014
971065AG2-659 GEN
Solar/Wind Harmer
11.094
316129AC1-054 GEN
Solar/Wind Harmer
1.827
970223AG2-152 GEN
Solar/Wind Harmer
17.059
270016AE1-250 BESS
Solar/Wind Harmer
2.815
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.528
316322AB2-045
Solar/Wind Harmer
0.506
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.477
270030AE2-140 GEN
Solar/Wind Harmer
19.567
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.809
316049AB1-081 GEN
Solar/Wind Harmer
1.448
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.244
316381AD1-082 GEN
Solar/Wind Helper
1.747
316375AC2-012 GEN
Solar/Wind Helper
0.879
3145336SMITFLD
Solar/Wind Helper
1.331
316458AB2-190 GEN2
Solar/Wind Helper
1.893
316159AE1-175 C
Solar/Wind Helper
0.497
316388AE2-253 GEN
Solar/Wind Helper
1.201
3142433PROV 92
Solar/Wind Helper
1.254
3142543TWELFTH
Solar/Wind Helper
0.03
3141766HARMONY
Solar/Wind Helper
0.062
3146456SLIGO L269
Solar/Wind Helper
0.308
3138133OCRAN
Solar/Wind Helper
0.185
316072AD1-144
Solar/Wind Helper
0.35
316246AF1-032 C
Solar/Wind Helper
0.342
964211AG1-282 GEN
Solar/Wind Helper
0.397
3141726DUNNSVL
Solar/Wind Helper
1.179
3143526WINTERP
Solar/Wind Helper
1.519
3142416OLDCHRC
Solar/Wind Helper
0.752
3143226MDLTHAN
Solar/Wind Helper
0.289
3142416OLDCHRC
Solar/Wind Helper
0.288
316337AD2-073 GEN
Solar/Wind Helper
0.434
3146516WINFALL
Solar/Wind Helper
0.813
3146516WINFALL
Solar/Wind Helper
0.251
3151031BRUNSWICKG2
50/50
8.303
970413AG2-270 GEN
50/50
40.265
3151591KERR 2
50/50
0.532
3144293JTRSVLE
50/50
0.79
970917AG2-570 GEN
Solar/Wind Harmer
166.275
316478AD1-087 GEN
Solar/Wind Harmer
4.189
316486AD2-202 GEN
Solar/Wind Harmer
1.227
970909AG2-566 GEN
Solar/Wind Harmer
3.255
316248AF1-058 C
Solar/Wind Harmer
1.033
960061AF2-297 GEN
Solar/Wind Harmer
17.135
316283AC2-100 C
Solar/Wind Harmer
2.94
971683AH1-343 GEN
Solar/Wind Harmer
13.259
316131AB2-060 GEN
Solar/Wind Harmer
3.032
964241AG1-285 GEN
Solar/Wind Harmer
21.724
315785AD2-033 C
Solar/Wind Harmer
6.194
970257AG2-171 GEN
Solar/Wind Harmer
10.181
959311AF2-222 GEN
Solar/Wind Harmer
28.197
963181AG1-167 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.081
971193AH1-056 GEN
Solar/Wind Harmer
16.225
942461AE2-259 GEN
Solar/Wind Harmer
3.773
3146926FARMVIL
Solar/Wind Harmer
-0.014
270018AE2-047 C O1
Solar/Wind Harmer
1.363
270197AD1-017 GEN1
Solar/Wind Harmer
1.661
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.802
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.477
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.551
961601AG1-000A GEN
Solar/Wind Harmer
5.225
315773AC2-141 GEN
Solar/Wind Helper
8.525
315839AE2-212 C
Solar/Wind Helper
0.497
3144536CHRHLND
Solar/Wind Helper
0.05
3144873MCLAUGH
Solar/Wind Helper
0.008
3145336SMITFLD
Solar/Wind Helper
0.133
316382AG1-145 C
Solar/Wind Helper
0.441
316156AD2-030 GEN
Solar/Wind Helper
0.47
3142946ENON
Solar/Wind Helper
0.104
316280AD1-041 GEN
Solar/Wind Helper
1.046
3146456SLIGO L269
Solar/Wind Helper
0.308
316484AD2-074 GEN
Solar/Wind Helper
0.583
316404AE1-155 C
Solar/Wind Helper
2.523
316320Y1-086
Solar/Wind Helper
0.126
316473AC1-191 GEN
Solar/Wind Helper
1.704
3141906WESTMOR
Solar/Wind Helper
0.111
316435W1029_GEN3
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
966881AG1-559 GEN
Solar/Wind Helper
0.328
3146626S HERTFORD
Solar/Wind Helper
0.236
LAGNLTFEXP_LAGN->PJM
CLTF
14.499
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.842
TVALTFEXP_TVA->PJM
CLTF
7.231
CPLELTFEXP_CPLE->PJM
CLTF
19.58
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.279
NYPJM->LTFIMP_NY
CLTF
2.38
LGEELTFEXP_LGEE->PJM
CLTF
2.637
WECLTFEXP_WEC->PJM
CLTF
1.38
AG2-052LTFEXP_AG2-052->PJM
LTF
0.074
AH1-155LTFEXP_AH1-155->PJM
LTF
0.111
CBM West 1LTFEXP_CBM-W1->PJM
CBM
48.979
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.858
MECLTFEXP_MEC->PJM
CLTF
7.267
SIGELTFEXP_SIGE->PJM
CLTF
0.218

Details for AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line l/o AEP_P7-1_#10817___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10817___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:121.83 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:477.57
MW Contribution:80.42
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
3.549
24684505SMG3
50/50
2.195
24684305SMG1
50/50
1.287
270013AE1-250 PV
Solar/Wind Harmer
12.954
270455AD2-022 GEN
Solar/Wind Helper
0.924
270457AD2-023 GEN
Solar/Wind Helper
0.609
24684705SMG5
50/50
1.367
970481AG2-311 GEN
50/50
19.048
24728405LEESVG
50/50
0.493
970223AG2-152 GEN
Solar/Wind Harmer
80.422
270016AE1-250 BESS
Solar/Wind Harmer
12.954
270574AD1-017 GEN2
Solar/Wind Harmer
23.549
270173AC1-122 GEN
Solar/Wind Harmer
4.971
24684605SMG4
50/50
3.572
24728405LEESVG
50/50
0.495
270197AD1-017 GEN1
Solar/Wind Harmer
7.076
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.014
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.058
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.099
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.315
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.611
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.571

Details for AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line l/o AEP_P4_#10213_05CLOVRD 138_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10213_05CLOVRD 138_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.79 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:450.0
MW Contribution:78.33
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Harmer
1.01
970165AG2-112 GEN
Solar/Wind Harmer
0.889
970163AG2-111 GEN
Solar/Wind Harmer
0.849
270455AD2-022 GEN
Solar/Wind Helper
0.935
270457AD2-023 GEN
Solar/Wind Helper
0.616
24684705SMG5
50/50
1.198
970481AG2-311 GEN
50/50
16.703
24728405LEESVG
50/50
0.334
3151561HALLBR1
50/50
0.448
970223AG2-152 GEN
Solar/Wind Harmer
78.334
270016AE1-250 BESS
Solar/Wind Harmer
12.518
270574AD1-017 GEN2
Solar/Wind Harmer
22.147
270173AC1-122 GEN
Solar/Wind Harmer
3.243
3147312GRETNA
Solar/Wind Harmer
-0.017
3146802CHATHAM
Solar/Wind Harmer
-0.016
941801AE2-185 GEN
Solar/Wind Harmer
8.005
3147123OTTER R
Solar/Wind Harmer
-0.011
962751AG1-124 GEN
Solar/Wind Harmer
5.228
24684405SMG2
50/50
3.112
24684505SMG3
50/50
1.925
24684305SMG1
50/50
1.128
270013AE1-250 PV
Solar/Wind Harmer
12.518
316217AC1-145 GEN
Solar/Wind Harmer
3.465
316197AC1-042 GEN
Solar/Wind Harmer
2.627
942671AE2-283 GEN
Solar/Wind Harmer
7.071
942751AE2-291 GEN
Solar/Wind Harmer
7.417
24684605SMG4
50/50
3.133
24728405LEESVG
50/50
0.336
270197AD1-017 GEN1
Solar/Wind Harmer
6.655
3147312GRETNA
Solar/Wind Harmer
-0.004
941821AE2-187 GEN
Solar/Wind Harmer
8.005
958131AF2-107 GEN
Solar/Wind Harmer
2.397
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.068
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.225
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.079
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.234
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.589
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.768

Details for AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line l/o AEP_P4_#10210_05CLOVRD 138_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10210_05CLOVRD 138_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.54 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:449.01
MW Contribution:78.3
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Harmer
1.008
970165AG2-112 GEN
Solar/Wind Harmer
0.887
970163AG2-111 GEN
Solar/Wind Harmer
0.846
270455AD2-022 GEN
Solar/Wind Helper
0.937
270457AD2-023 GEN
Solar/Wind Helper
0.617
24684405SMG2
50/50
3.108
24684505SMG3
50/50
1.922
24684305SMG1
50/50
1.127
270013AE1-250 PV
Solar/Wind Harmer
12.513
316217AC1-145 GEN
Solar/Wind Harmer
3.459
316197AC1-042 GEN
Solar/Wind Harmer
2.622
942671AE2-283 GEN
Solar/Wind Harmer
7.059
942751AE2-291 GEN
Solar/Wind Harmer
7.401
24684705SMG5
50/50
1.197
970481AG2-311 GEN
50/50
16.68
24728405LEESVG
50/50
0.334
3151561HALLBR1
50/50
0.448
970223AG2-152 GEN
Solar/Wind Harmer
78.303
270016AE1-250 BESS
Solar/Wind Harmer
12.513
270574AD1-017 GEN2
Solar/Wind Harmer
22.132
270173AC1-122 GEN
Solar/Wind Harmer
3.239
3147312GRETNA
Solar/Wind Harmer
-0.017
3146802CHATHAM
Solar/Wind Harmer
-0.016
941801AE2-185 GEN
Solar/Wind Harmer
7.991
3147123OTTER R
Solar/Wind Harmer
-0.011
962751AG1-124 GEN
Solar/Wind Harmer
5.215
24684605SMG4
50/50
3.128
24728405LEESVG
50/50
0.335
270197AD1-017 GEN1
Solar/Wind Harmer
6.65
3147312GRETNA
Solar/Wind Harmer
-0.004
941821AE2-187 GEN
Solar/Wind Harmer
7.991
958131AF2-107 GEN
Solar/Wind Harmer
2.391
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.068
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.226
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.078
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.237
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.59
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.771

Details for AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line l/o AEP_P7-1_#10808___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10808___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:111.62 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:437.54
MW Contribution:80.44
Bus #Bus NameTypeMW Contribution
24684605SMG4
50/50
3.574
270197AD1-017 GEN1
Solar/Wind Harmer
7.079
270455AD2-022 GEN
Solar/Wind Helper
0.921
270457AD2-023 GEN
Solar/Wind Helper
0.607
24684405SMG2
50/50
3.551
24684505SMG3
50/50
2.196
24684305SMG1
50/50
1.287
270013AE1-250 PV
Solar/Wind Harmer
12.958
24684705SMG5
50/50
1.367
970481AG2-311 GEN
50/50
19.058
970223AG2-152 GEN
Solar/Wind Harmer
80.445
270016AE1-250 BESS
Solar/Wind Harmer
12.958
270574AD1-017 GEN2
Solar/Wind Harmer
23.558
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.003
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.023
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.088
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.303
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.604
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.518

Details for AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line l/o AEP_P2-2_#6213_05WLAKE 138_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#6213_05WLAKE 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:105.51 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:413.6
MW Contribution:75.88
Bus #Bus NameTypeMW Contribution
24684605SMG4
50/50
2.712
24728405LEESVG
50/50
0.291
270197AD1-017 GEN1
Solar/Wind Harmer
6.226
3147312GRETNA
Solar/Wind Harmer
-0.004
941821AE2-187 GEN
Solar/Wind Harmer
6.961
958131AF2-107 GEN
Solar/Wind Harmer
2.203
270018AE2-047 C O1
Solar/Wind Helper
0.451
943811AF1-049 GEN
Solar/Wind Helper
0.749
316123AC1-075 GEN
Solar/Wind Harmer
0.835
970165AG2-112 GEN
Solar/Wind Harmer
0.735
970163AG2-111 GEN
Solar/Wind Harmer
0.701
270455AD2-022 GEN
Solar/Wind Helper
1.036
270457AD2-023 GEN
Solar/Wind Helper
0.682
24684405SMG2
50/50
2.694
24684505SMG3
50/50
1.666
24684305SMG1
50/50
0.977
270013AE1-250 PV
Solar/Wind Harmer
12.034
316217AC1-145 GEN
Solar/Wind Harmer
3.013
316197AC1-042 GEN
Solar/Wind Harmer
2.284
942671AE2-283 GEN
Solar/Wind Harmer
6.149
942751AE2-291 GEN
Solar/Wind Harmer
6.246
24684705SMG5
50/50
1.038
970481AG2-311 GEN
50/50
14.46
24728405LEESVG
50/50
0.29
3151561HALLBR1
50/50
0.389
970223AG2-152 GEN
Solar/Wind Harmer
75.879
270016AE1-250 BESS
Solar/Wind Harmer
12.034
270574AD1-017 GEN2
Solar/Wind Harmer
20.72
270173AC1-122 GEN
Solar/Wind Harmer
2.826
3147312GRETNA
Solar/Wind Harmer
-0.015
3146802CHATHAM
Solar/Wind Harmer
-0.014
941801AE2-185 GEN
Solar/Wind Harmer
6.961
3147123OTTER R
Solar/Wind Harmer
-0.01
962751AG1-124 GEN
Solar/Wind Harmer
4.826
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.052
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.178
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.061
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.391
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.663
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.766

Details for AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line l/o AEP_P2-2_#6212_05WLAKE 138_2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#6212_05WLAKE 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:103.18 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:404.45
MW Contribution:75.88
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Harmer
0.835
970165AG2-112 GEN
Solar/Wind Harmer
0.735
970163AG2-111 GEN
Solar/Wind Harmer
0.701
270455AD2-022 GEN
Solar/Wind Helper
1.036
270457AD2-023 GEN
Solar/Wind Helper
0.682
24684405SMG2
50/50
2.694
24684505SMG3
50/50
1.666
24684305SMG1
50/50
0.977
270013AE1-250 PV
Solar/Wind Harmer
12.034
316217AC1-145 GEN
Solar/Wind Harmer
3.013
316197AC1-042 GEN
Solar/Wind Harmer
2.284
942671AE2-283 GEN
Solar/Wind Harmer
6.149
942751AE2-291 GEN
Solar/Wind Harmer
6.246
24684605SMG4
50/50
2.712
24728405LEESVG
50/50
0.291
270197AD1-017 GEN1
Solar/Wind Harmer
6.226
3147312GRETNA
Solar/Wind Harmer
-0.004
941821AE2-187 GEN
Solar/Wind Harmer
6.961
958131AF2-107 GEN
Solar/Wind Harmer
2.203
270018AE2-047 C O1
Solar/Wind Helper
0.451
943811AF1-049 GEN
Solar/Wind Helper
0.749
24684705SMG5
50/50
1.038
970481AG2-311 GEN
50/50
14.46
24728405LEESVG
50/50
0.29
3151561HALLBR1
50/50
0.389
970223AG2-152 GEN
Solar/Wind Harmer
75.879
270016AE1-250 BESS
Solar/Wind Harmer
12.034
270574AD1-017 GEN2
Solar/Wind Harmer
20.72
270173AC1-122 GEN
Solar/Wind Harmer
2.826
3147312GRETNA
Solar/Wind Harmer
-0.015
3146802CHATHAM
Solar/Wind Harmer
-0.014
941801AE2-185 GEN
Solar/Wind Harmer
6.961
3147123OTTER R
Solar/Wind Harmer
-0.01
962751AG1-124 GEN
Solar/Wind Harmer
4.826
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.052
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.178
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.061
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.391
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.663
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.766

Details for [AG2-152] AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line l/o AEP_P7-1_#10817___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10817___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.63 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:394.45
MW Contribution:93.51
IPD Plant:AG2-152
Bus #Bus NameTypeMW Contribution
970223AG2-152 GEN
PJM_IPD
93.514

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:211.67 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1447.79
MW Contribution:5.79
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.536
3151531CLOVER1
50/50
6.868
3151541CLOVER2
50/50
6.835
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
970285AG2-188 GEN
Solar/Wind Harmer
71.83
315657AE1-056 GEN
Solar/Wind Harmer
20.241
946301AF1-294 GEN
Solar/Wind Harmer
13.094
961791AG1-021 GEN
Solar/Wind Harmer
6.387
970683AG2-441 GEN
Solar/Wind Harmer
36.695
970681AG2-440 GEN
Solar/Wind Harmer
29.356
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.31
971967AH1-528 GEN
Solar/Wind Harmer
73.321
316239AB2-077_GEN
Solar/Wind Harmer
0.97
316238AB2-078_GEN
Solar/Wind Harmer
0.97
316118AC1-105 GEN
Solar/Wind Harmer
1.807
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.03
970831AG2-522 GEN
Solar/Wind Harmer
9.822
316123AC1-075 GEN
Solar/Wind Harmer
1.789
970165AG2-112 GEN
Solar/Wind Harmer
1.575
970163AG2-111 GEN
Solar/Wind Harmer
1.503
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.493
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.635
270457AD2-023 GEN
Solar/Wind Harmer
0.829
315607AA1-063A GEN
Solar/Wind Harmer
0.882
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.411
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.563
270494AE1-108_GEN
Solar/Wind Helper
3.665
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.536
970413AG2-270 GEN
50/50
29.97
3151591KERR 2
50/50
0.482
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.339
970909AG2-566 GEN
Solar/Wind Harmer
5.578
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.735
963181AG1-167 GEN
Solar/Wind Harmer
4.79
959311AF2-222 GEN
Solar/Wind Harmer
45.765
970257AG2-171 GEN
Solar/Wind Harmer
15.97
315785AD2-033 C
Solar/Wind Harmer
9.259
964241AG1-285 GEN
Solar/Wind Harmer
28.316
316478AD1-087 GEN
Solar/Wind Harmer
3.115
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.609
316248AF1-058 C
Solar/Wind Harmer
0.741
960061AF2-297 GEN
Solar/Wind Harmer
12.289
971683AH1-343 GEN
Solar/Wind Harmer
9.199
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.303
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.775
316210AC1-098 GEN
Solar/Wind Harmer
1.194
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.767
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.393
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.414
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.317
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
3144293JTRSVLE
50/50
1.536
3144293JTRSVLE
50/50
1.294
970535AG2-341 GEN
50/50
4.631
3152661PLYWOOD A
50/50
0.509
970301AG2-198 GEN
Solar/Wind Harmer
29.375
971741AH1-377 GEN
Solar/Wind Harmer
63.77
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.984
963191AG1-168 GEN
Solar/Wind Harmer
4.79
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.293
971775AH1-396 GEN
Solar/Wind Harmer
3.032
970933AG2-581 GEN
Solar/Wind Harmer
36.564
970099AG2-077 GEN
Solar/Wind Harmer
47.892
313527AB2-043 GEN
Solar/Wind Harmer
5.323
962561AG1-105 GEN
Solar/Wind Harmer
16.163
964791AG1-342 GEN
Solar/Wind Harmer
5.983
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.395
942751AE2-291 GEN
Solar/Wind Harmer
9.282
316222AC1-221 GEN
Solar/Wind Harmer
1.431
316181AB2-040 GEN
Solar/Wind Harmer
1.454
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.157
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.182
3145783HORNRTN
Solar/Wind Harmer
0.946
3145783HORNRTN
Solar/Wind Harmer
0.296
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.956
316274AC1-208 GEN
Solar/Wind Harmer
0.891
316263AC1-034 GEN
Solar/Wind Harmer
3.354
961601AG1-000A GEN
Solar/Wind Harmer
2.733
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.045
316197AC1-042 GEN
Solar/Wind Harmer
0.792
942671AE2-283 GEN
Solar/Wind Harmer
2.132
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.531
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.479
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.387
971563AH1-280 GEN
Solar/Wind Harmer
6.387
970685AG2-442 GEN
Solar/Wind Harmer
41.098
962491AG1-098 GEN
Solar/Wind Harmer
28.527
315693AD1-088 GEN
Solar/Wind Harmer
20.89
957481AF2-042 GEN
Solar/Wind Harmer
119.73
316237AB2-079_GEN
Solar/Wind Harmer
0.97
315687AD1-152 GEN
Solar/Wind Harmer
3.722
970401AG2-262 GEN
Solar/Wind Harmer
1.828
316003AC1-222 GEN
Solar/Wind Harmer
2.23
971065AG2-659 GEN
Solar/Wind Harmer
10.784
316129AC1-054 GEN
Solar/Wind Harmer
1.809
971795AH1-408 GEN
Solar/Wind Harmer
11.382
960081AF2-299 GEN
Solar/Wind Harmer
1.187
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.663
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.965
316049AB1-081 GEN
Solar/Wind Harmer
0.772
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.715
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
970223AG2-152 GEN
Solar/Wind Harmer
5.79
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.192
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.414
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.314
LAGNLTFEXP_LAGN->PJM
CLTF
3.212
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.896
TVALTFEXP_TVA->PJM
CLTF
1.599
CPLELTFEXP_CPLE->PJM
CLTF
5.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.616
NYPJM->LTFIMP_NY
CLTF
0.52
LGEELTFEXP_LGEE->PJM
CLTF
0.521
WECLTFEXP_WEC->PJM
CLTF
0.271
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.51
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.435
MECLTFEXP_MEC->PJM
CLTF
1.488
SIGELTFEXP_SIGE->PJM
CLTF
0.044

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:211.61 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1447.4
MW Contribution:5.79
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.835
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
970285AG2-188 GEN
Solar/Wind Harmer
71.83
315657AE1-056 GEN
Solar/Wind Harmer
20.241
946301AF1-294 GEN
Solar/Wind Harmer
13.094
961791AG1-021 GEN
Solar/Wind Harmer
6.387
970683AG2-441 GEN
Solar/Wind Harmer
36.695
970681AG2-440 GEN
Solar/Wind Harmer
29.356
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.31
971967AH1-528 GEN
Solar/Wind Harmer
73.321
316239AB2-077_GEN
Solar/Wind Harmer
0.97
316238AB2-078_GEN
Solar/Wind Harmer
0.97
316118AC1-105 GEN
Solar/Wind Harmer
1.807
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.03
970831AG2-522 GEN
Solar/Wind Harmer
9.822
316123AC1-075 GEN
Solar/Wind Harmer
1.789
970165AG2-112 GEN
Solar/Wind Harmer
1.575
970163AG2-111 GEN
Solar/Wind Harmer
1.503
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.493
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.635
270457AD2-023 GEN
Solar/Wind Harmer
0.829
315607AA1-063A GEN
Solar/Wind Harmer
0.882
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.411
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.563
270494AE1-108_GEN
Solar/Wind Helper
3.665
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.536
970413AG2-270 GEN
50/50
29.97
3151591KERR 2
50/50
0.482
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.339
970909AG2-566 GEN
Solar/Wind Harmer
5.578
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.735
963181AG1-167 GEN
Solar/Wind Harmer
4.79
959311AF2-222 GEN
Solar/Wind Harmer
45.765
970257AG2-171 GEN
Solar/Wind Harmer
15.97
315785AD2-033 C
Solar/Wind Harmer
9.259
964241AG1-285 GEN
Solar/Wind Harmer
28.316
316478AD1-087 GEN
Solar/Wind Harmer
3.115
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.609
316248AF1-058 C
Solar/Wind Harmer
0.741
960061AF2-297 GEN
Solar/Wind Harmer
12.289
971683AH1-343 GEN
Solar/Wind Harmer
9.199
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.303
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.775
316210AC1-098 GEN
Solar/Wind Harmer
1.194
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.767
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.393
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.414
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.317
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
3144293JTRSVLE
50/50
1.536
3144293JTRSVLE
50/50
1.294
970535AG2-341 GEN
50/50
4.631
3152661PLYWOOD A
50/50
0.509
970301AG2-198 GEN
Solar/Wind Harmer
29.375
971741AH1-377 GEN
Solar/Wind Harmer
63.77
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.984
963191AG1-168 GEN
Solar/Wind Harmer
4.79
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.293
971775AH1-396 GEN
Solar/Wind Harmer
3.032
970933AG2-581 GEN
Solar/Wind Harmer
36.564
970099AG2-077 GEN
Solar/Wind Harmer
47.892
313527AB2-043 GEN
Solar/Wind Harmer
5.323
962561AG1-105 GEN
Solar/Wind Harmer
16.163
964791AG1-342 GEN
Solar/Wind Harmer
5.983
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.395
942751AE2-291 GEN
Solar/Wind Harmer
9.282
316222AC1-221 GEN
Solar/Wind Harmer
1.431
316181AB2-040 GEN
Solar/Wind Harmer
1.454
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.157
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.182
3145783HORNRTN
Solar/Wind Harmer
0.946
3145783HORNRTN
Solar/Wind Harmer
0.296
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.956
316274AC1-208 GEN
Solar/Wind Harmer
0.891
316263AC1-034 GEN
Solar/Wind Harmer
3.354
961601AG1-000A GEN
Solar/Wind Harmer
2.733
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.045
316197AC1-042 GEN
Solar/Wind Harmer
0.792
942671AE2-283 GEN
Solar/Wind Harmer
2.132
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.531
3144293JTRSVLE
50/50
1.536
3151531CLOVER1
50/50
6.868
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.479
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.387
971563AH1-280 GEN
Solar/Wind Harmer
6.387
970685AG2-442 GEN
Solar/Wind Harmer
41.098
962491AG1-098 GEN
Solar/Wind Harmer
28.527
315693AD1-088 GEN
Solar/Wind Harmer
20.89
957481AF2-042 GEN
Solar/Wind Harmer
119.73
316237AB2-079_GEN
Solar/Wind Harmer
0.97
315687AD1-152 GEN
Solar/Wind Harmer
3.722
970401AG2-262 GEN
Solar/Wind Harmer
1.828
316003AC1-222 GEN
Solar/Wind Harmer
2.23
971065AG2-659 GEN
Solar/Wind Harmer
10.784
316129AC1-054 GEN
Solar/Wind Harmer
1.809
971795AH1-408 GEN
Solar/Wind Harmer
11.382
960081AF2-299 GEN
Solar/Wind Harmer
1.187
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.663
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.965
316049AB1-081 GEN
Solar/Wind Harmer
0.772
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.715
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
970223AG2-152 GEN
Solar/Wind Harmer
5.79
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.192
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.414
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.314
LAGNLTFEXP_LAGN->PJM
CLTF
3.212
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.896
TVALTFEXP_TVA->PJM
CLTF
1.599
CPLELTFEXP_CPLE->PJM
CLTF
5.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.616
NYPJM->LTFIMP_NY
CLTF
0.52
LGEELTFEXP_LGEE->PJM
CLTF
0.521
WECLTFEXP_WEC->PJM
CLTF
0.271
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.51
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.435
MECLTFEXP_MEC->PJM
CLTF
1.488
SIGELTFEXP_SIGE->PJM
CLTF
0.044

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:207.99 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1422.62
MW Contribution:5.7
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
970285AG2-188 GEN
Solar/Wind Harmer
71.826
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
971967AH1-528 GEN
Solar/Wind Harmer
73.183
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
970933AG2-581 GEN
Solar/Wind Harmer
36.495
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:206.17 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:1153.12
MW Contribution:4.0
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.232
963181AG1-167 GEN
Solar/Wind Harmer
1.818
959311AF2-222 GEN
Solar/Wind Harmer
34.653
970257AG2-171 GEN
Solar/Wind Harmer
12.116
315785AD2-033 C
Solar/Wind Harmer
2.953
964241AG1-285 GEN
Solar/Wind Harmer
21.475
316478AD1-087 GEN
Solar/Wind Harmer
1.115
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.935
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.299
971683AH1-343 GEN
Solar/Wind Harmer
6.959
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.287
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.626
3146233WITAKRS
Solar/Wind Harmer
0.329
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.062
961601AG1-000A GEN
Solar/Wind Harmer
4.35
315724AD1-057 GEN
Solar/Wind Harmer
0.227
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.818
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.213
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.1
970301AG2-198 GEN
Solar/Wind Harmer
22.295
971741AH1-377 GEN
Solar/Wind Harmer
48.392
3147133PAMPLIN
Solar/Wind Harmer
0.48
3147133PAMPLIN
Solar/Wind Harmer
0.384
958211AF2-115 GEN
Solar/Wind Harmer
5.453
963191AG1-168 GEN
Solar/Wind Harmer
1.818
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.154
971775AH1-396 GEN
Solar/Wind Harmer
0.606
970933AG2-581 GEN
Solar/Wind Harmer
27.718
970099AG2-077 GEN
Solar/Wind Harmer
36.303
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.244
964791AG1-342 GEN
Solar/Wind Harmer
4.773
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.665
942751AE2-291 GEN
Solar/Wind Harmer
7.016
316222AC1-221 GEN
Solar/Wind Harmer
0.517
316181AB2-040 GEN
Solar/Wind Harmer
0.135
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.992
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.575
3145783HORNRTN
Solar/Wind Harmer
1.26
3145783HORNRTN
Solar/Wind Harmer
0.394
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.38
316263AC1-034 GEN
Solar/Wind Harmer
2.393
961601AG1-000A GEN
Solar/Wind Harmer
1.088
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.132
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.414
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.97
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
963171AG1-166 GEN
Solar/Wind Harmer
2.424
971563AH1-280 GEN
Solar/Wind Harmer
4.847
970685AG2-442 GEN
Solar/Wind Harmer
31.186
962491AG1-098 GEN
Solar/Wind Harmer
21.632
315693AD1-088 GEN
Solar/Wind Harmer
17.82
957481AF2-042 GEN
Solar/Wind Harmer
90.757
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.458
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.171
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
9.004
960081AF2-299 GEN
Solar/Wind Harmer
0.903
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.349
3146233WITAKRS
Solar/Wind Harmer
0.261
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.051
316359AB2-059 GEN
Solar/Wind Harmer
0.226
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.062
315722AD1-056 GEN
Solar/Wind Harmer
0.382
3145796HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.068
962571AG1-106 GEN
Solar/Wind Harmer
0.836
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.253
970223AG2-152 GEN
Solar/Wind Harmer
3.997
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.043
941801AE2-185 GEN
Solar/Wind Harmer
1.818
3145823KELFORD
Solar/Wind Harmer
0.056
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.104
970285AG2-188 GEN
Solar/Wind Harmer
57.798
315657AE1-056 GEN
Solar/Wind Harmer
16.558
946301AF1-294 GEN
Solar/Wind Harmer
8.968
961791AG1-021 GEN
Solar/Wind Harmer
4.363
970683AG2-441 GEN
Solar/Wind Harmer
27.844
970681AG2-440 GEN
Solar/Wind Harmer
22.275
3144303KENBRDG
Solar/Wind Harmer
0.303
971443AH1-215 GEN
Solar/Wind Harmer
6.304
971967AH1-528 GEN
Solar/Wind Harmer
55.434
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.602
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.073
970831AG2-522 GEN
Solar/Wind Harmer
7.443
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.191
970163AG2-111 GEN
Solar/Wind Harmer
1.136
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.368
315607AA1-063A GEN
Solar/Wind Harmer
0.159
3146043SEABORD
Solar/Wind Harmer
0.076
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.25
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.462
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.252
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:203.59 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:1138.68
MW Contribution:4.0
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.213
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.1
970301AG2-198 GEN
Solar/Wind Harmer
22.295
971741AH1-377 GEN
Solar/Wind Harmer
48.392
3147133PAMPLIN
Solar/Wind Harmer
0.48
3147133PAMPLIN
Solar/Wind Harmer
0.384
958211AF2-115 GEN
Solar/Wind Harmer
5.453
963191AG1-168 GEN
Solar/Wind Harmer
1.818
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.154
971775AH1-396 GEN
Solar/Wind Harmer
0.606
970099AG2-077 GEN
Solar/Wind Harmer
36.303
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.244
964791AG1-342 GEN
Solar/Wind Harmer
4.773
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.665
942751AE2-291 GEN
Solar/Wind Harmer
7.016
316222AC1-221 GEN
Solar/Wind Harmer
0.517
316181AB2-040 GEN
Solar/Wind Harmer
0.135
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.97
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
963171AG1-166 GEN
Solar/Wind Harmer
2.424
971563AH1-280 GEN
Solar/Wind Harmer
4.847
970685AG2-442 GEN
Solar/Wind Harmer
31.186
962491AG1-098 GEN
Solar/Wind Harmer
21.632
315693AD1-088 GEN
Solar/Wind Harmer
17.82
957481AF2-042 GEN
Solar/Wind Harmer
90.757
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.458
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.171
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
9.004
960081AF2-299 GEN
Solar/Wind Harmer
0.903
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.349
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.232
963181AG1-167 GEN
Solar/Wind Harmer
1.818
959311AF2-222 GEN
Solar/Wind Harmer
34.653
970257AG2-171 GEN
Solar/Wind Harmer
12.116
315785AD2-033 C
Solar/Wind Harmer
2.953
964241AG1-285 GEN
Solar/Wind Harmer
21.475
316478AD1-087 GEN
Solar/Wind Harmer
1.115
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.935
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.299
971683AH1-343 GEN
Solar/Wind Harmer
6.959
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.287
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.626
3146233WITAKRS
Solar/Wind Harmer
0.329
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.104
970285AG2-188 GEN
Solar/Wind Harmer
57.798
315657AE1-056 GEN
Solar/Wind Harmer
16.558
946301AF1-294 GEN
Solar/Wind Harmer
8.968
961791AG1-021 GEN
Solar/Wind Harmer
4.363
970683AG2-441 GEN
Solar/Wind Harmer
27.844
970681AG2-440 GEN
Solar/Wind Harmer
22.275
3144303KENBRDG
Solar/Wind Harmer
0.303
971443AH1-215 GEN
Solar/Wind Harmer
6.304
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.602
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.073
970831AG2-522 GEN
Solar/Wind Harmer
7.443
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.191
970163AG2-111 GEN
Solar/Wind Harmer
1.136
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.368
315607AA1-063A GEN
Solar/Wind Harmer
0.159
3146043SEABORD
Solar/Wind Harmer
0.076
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.25
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.462
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.252
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.992
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.575
3145783HORNRTN
Solar/Wind Harmer
1.26
3145783HORNRTN
Solar/Wind Harmer
0.394
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.38
316263AC1-034 GEN
Solar/Wind Harmer
2.393
961601AG1-000A GEN
Solar/Wind Harmer
1.088
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.132
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.414
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
3146233WITAKRS
Solar/Wind Harmer
0.261
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.051
316359AB2-059 GEN
Solar/Wind Harmer
0.226
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.062
315722AD1-056 GEN
Solar/Wind Harmer
0.382
3145796HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.068
962571AG1-106 GEN
Solar/Wind Harmer
0.836
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.253
970223AG2-152 GEN
Solar/Wind Harmer
3.997
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.043
941801AE2-185 GEN
Solar/Wind Harmer
1.818
3145823KELFORD
Solar/Wind Harmer
0.056
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.062
961601AG1-000A GEN
Solar/Wind Harmer
4.35
315724AD1-057 GEN
Solar/Wind Harmer
0.227
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.818
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:201.95 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1381.35
MW Contribution:5.7
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
970285AG2-188 GEN
Solar/Wind Harmer
71.826
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:201.95 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1381.35
MW Contribution:5.7
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
970285AG2-188 GEN
Solar/Wind Harmer
71.826
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:129.2 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5258.72
MW Contribution:12.09
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
44.982
970099AG2-077 GEN
Solar/Wind Harmer
50.723
971741AH1-377 GEN
Solar/Wind Harmer
33.569
970301AG2-198 GEN
Solar/Wind Harmer
13.228
3146843MT LREL
Solar/Wind Harmer
0.286
3146843MT LREL
Solar/Wind Harmer
0.286
964791AG1-342 GEN
Solar/Wind Harmer
5.488
316222AC1-221 GEN
Solar/Wind Harmer
1.175
962561AG1-105 GEN
Solar/Wind Harmer
13.485
939181AE1-148 GEN
Solar/Wind Harmer
12.41
313527AB2-043 GEN
Solar/Wind Harmer
0.003
970323AG2-213 GEN
Solar/Wind Harmer
10.445
971775AH1-396 GEN
Solar/Wind Harmer
0.392
316034AC1-036 C
Solar/Wind Harmer
0.018
958211AF2-115 GEN
Solar/Wind Harmer
2.845
963191AG1-168 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.234
3147133PAMPLIN
Solar/Wind Harmer
0.187
942751AE2-291 GEN
Solar/Wind Harmer
11.476
270013AE1-250 PV
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.546
3146776BUCKING
Solar/Wind Harmer
0.044
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.276
316263AC1-034 GEN
Solar/Wind Harmer
4.449
961601AG1-000A GEN
Solar/Wind Harmer
2.035
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
47.73
957481AF2-042 GEN
Solar/Wind Harmer
126.807
315693AD1-088 GEN
Solar/Wind Harmer
20.818
962491AG1-098 GEN
Solar/Wind Harmer
24.385
315687AD1-152 GEN
Solar/Wind Harmer
0.013
316003AC1-222 GEN
Solar/Wind Harmer
0.008
970401AG2-262 GEN
Solar/Wind Harmer
1.677
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
17.979
963171AG1-166 GEN
Solar/Wind Harmer
1.264
971563AH1-280 GEN
Solar/Wind Harmer
2.529
3146926FARMVIL
Solar/Wind Harmer
0.131
971065AG2-659 GEN
Solar/Wind Harmer
8.445
316129AC1-054 GEN
Solar/Wind Harmer
0.698
970223AG2-152 GEN
Solar/Wind Harmer
12.094
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.088
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.055
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.099
941801AE2-185 GEN
Solar/Wind Harmer
4.212
270030AE2-140 GEN
Solar/Wind Harmer
13.804
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.094
316359AB2-059 GEN
Solar/Wind Harmer
0.421
316049AB1-081 GEN
Solar/Wind Harmer
0.67
3142053HEARTS
Solar/Wind Harmer
0.206
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
970673AG2-436 GEN
Solar/Wind Harmer
149.315
970673AG2-436 GEN
Solar/Wind Harmer
99.544
971967AH1-528 GEN
Solar/Wind Harmer
95.481
970085AG2-068 GEN
Solar/Wind Harmer
31.82
970581AG2-369 GEN
Solar/Wind Harmer
27.365
3147173SINAI
Solar/Wind Harmer
0.309
3147243WELCO
Solar/Wind Harmer
0.193
316118AC1-105 GEN
Solar/Wind Harmer
0.768
970865AG2-541 GEN
Solar/Wind Harmer
9.078
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.118
3144303KENBRDG
Solar/Wind Harmer
0.196
970683AG2-441 GEN
Solar/Wind Harmer
16.053
970681AG2-440 GEN
Solar/Wind Harmer
12.842
946301AF1-294 GEN
Solar/Wind Harmer
4.678
961791AG1-021 GEN
Solar/Wind Harmer
2.276
315657AE1-056 GEN
Solar/Wind Harmer
8.085
316123AC1-075 GEN
Solar/Wind Harmer
0.315
970165AG2-112 GEN
Solar/Wind Harmer
1.87
970163AG2-111 GEN
Solar/Wind Harmer
1.784
970831AG2-522 GEN
Solar/Wind Harmer
7.35
970285AG2-188 GEN
Solar/Wind Harmer
12.402
971845AH1-439 GEN
Solar/Wind Harmer
6.507
270069AE2-166 C O1
Solar/Wind Harmer
0.004
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
53.421
316478AD1-087 GEN
Solar/Wind Harmer
1.525
316486AD2-202 GEN
Solar/Wind Harmer
0.448
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
13.182
316283AC2-100 C
Solar/Wind Harmer
0.55
971683AH1-343 GEN
Solar/Wind Harmer
10.2
316131AB2-060 GEN
Solar/Wind Harmer
0.796
964241AG1-285 GEN
Solar/Wind Harmer
16.703
315785AD2-033 C
Solar/Wind Harmer
2.003
970257AG2-171 GEN
Solar/Wind Harmer
7.834
959311AF2-222 GEN
Solar/Wind Harmer
21.656
963181AG1-167 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.736
971193AH1-056 GEN
Solar/Wind Harmer
14.274
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.131
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
0.943
3146776BUCKING
Solar/Wind Harmer
0.049
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.212
270336AE1-100 GEN
Solar/Wind Harmer
0.003
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.117
971623AH1-311 GEN
Solar/Wind Harmer
0.234
961601AG1-000A GEN
Solar/Wind Harmer
8.141
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
NYPJM->LTFIMP_NY
CLTF
2.382
LGEELTFEXP_LGEE->PJM
CLTF
2.675
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51192_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51192_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.25 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5708.12
MW Contribution:17.25
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
62.844
957481AF2-042 GEN
Solar/Wind Harmer
166.962
315693AD1-088 GEN
Solar/Wind Harmer
24.364
962491AG1-098 GEN
Solar/Wind Harmer
32.107
315687AD1-152 GEN
Solar/Wind Harmer
5.339
316003AC1-222 GEN
Solar/Wind Harmer
3.203
970401AG2-262 GEN
Solar/Wind Harmer
2.096
316237AB2-079_GEN
Solar/Wind Harmer
0.866
970685AG2-442 GEN
Solar/Wind Harmer
23.673
963171AG1-166 GEN
Solar/Wind Harmer
3.329
971563AH1-280 GEN
Solar/Wind Harmer
3.329
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.119
316129AC1-054 GEN
Solar/Wind Harmer
1.828
970223AG2-152 GEN
Solar/Wind Harmer
17.247
270016AE1-250 BESS
Solar/Wind Harmer
2.846
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.591
316322AB2-045
Solar/Wind Harmer
0.516
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.545
270030AE2-140 GEN
Solar/Wind Harmer
19.786
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.774
316049AB1-081 GEN
Solar/Wind Harmer
1.419
3142053HEARTS
Solar/Wind Harmer
0.155
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
59.226
970099AG2-077 GEN
Solar/Wind Harmer
66.785
971741AH1-377 GEN
Solar/Wind Harmer
44.199
970301AG2-198 GEN
Solar/Wind Harmer
17.416
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.86
316222AC1-221 GEN
Solar/Wind Harmer
3.218
962561AG1-105 GEN
Solar/Wind Harmer
17.755
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
970673AG2-436 GEN
Solar/Wind Harmer
165.209
970673AG2-436 GEN
Solar/Wind Harmer
83.65
971967AH1-528 GEN
Solar/Wind Harmer
126.052
970085AG2-068 GEN
Solar/Wind Harmer
41.896
970581AG2-369 GEN
Solar/Wind Harmer
36.031
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.3
970865AG2-541 GEN
Solar/Wind Harmer
11.953
316239AB2-077_GEN
Solar/Wind Harmer
0.866
316238AB2-078_GEN
Solar/Wind Harmer
0.866
971443AH1-215 GEN
Solar/Wind Harmer
5.422
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.136
970681AG2-440 GEN
Solar/Wind Harmer
16.909
946301AF1-294 GEN
Solar/Wind Harmer
6.825
961791AG1-021 GEN
Solar/Wind Harmer
3.329
270455AD2-022 GEN
Solar/Wind Harmer
4.714
270457AD2-023 GEN
Solar/Wind Harmer
2.39
315657AE1-056 GEN
Solar/Wind Harmer
9.877
316123AC1-075 GEN
Solar/Wind Harmer
2.797
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
168.81
316478AD1-087 GEN
Solar/Wind Harmer
4.25
316486AD2-202 GEN
Solar/Wind Harmer
1.245
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
1.046
960061AF2-297 GEN
Solar/Wind Harmer
17.357
316283AC2-100 C
Solar/Wind Harmer
2.974
971683AH1-343 GEN
Solar/Wind Harmer
13.43
316131AB2-060 GEN
Solar/Wind Harmer
3.068
964241AG1-285 GEN
Solar/Wind Harmer
21.992
315785AD2-033 C
Solar/Wind Harmer
6.274
970257AG2-171 GEN
Solar/Wind Harmer
10.314
959311AF2-222 GEN
Solar/Wind Harmer
28.571
963181AG1-167 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.462
942461AE2-259 GEN
Solar/Wind Harmer
3.832
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.378
270197AD1-017 GEN1
Solar/Wind Harmer
1.68
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.844
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.545
270336AE1-100 GEN
Solar/Wind Harmer
1.569
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
5.12
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
970165AG2-112 GEN
Solar/Wind Harmer
2.462
970163AG2-111 GEN
Solar/Wind Harmer
2.349
970831AG2-522 GEN
Solar/Wind Harmer
9.678
970285AG2-188 GEN
Solar/Wind Harmer
15.412
971845AH1-439 GEN
Solar/Wind Harmer
8.567
270069AE2-166 C O1
Solar/Wind Harmer
2.422
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
939181AE1-148 GEN
Solar/Wind Harmer
16.34
313527AB2-043 GEN
Solar/Wind Harmer
4.631
970323AG2-213 GEN
Solar/Wind Harmer
13.752
971775AH1-396 GEN
Solar/Wind Harmer
1.958
316034AC1-036 C
Solar/Wind Harmer
0.51
958211AF2-115 GEN
Solar/Wind Harmer
4.162
963191AG1-168 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.11
270013AE1-250 PV
Solar/Wind Harmer
2.846
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.4
316197AC1-042 GEN
Solar/Wind Harmer
1.819
942671AE2-283 GEN
Solar/Wind Harmer
4.898
316263AC1-034 GEN
Solar/Wind Harmer
6.166
961601AG1-000A GEN
Solar/Wind Harmer
5.056
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
NYPJM->LTFIMP_NY
CLTF
2.382
LGEELTFEXP_LGEE->PJM
CLTF
2.675
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51172_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51172_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.76 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5683.44
MW Contribution:17.2
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
19.115
963041AG1-153 GEN
50/50
16.957
3151541CLOVER2
50/50
9.268
3151611KERR 4
50/50
0.538
315242AE2-183_GT2
50/50
11.056
315241AE2-183_GT1
50/50
10.988
3151621KERR 5
50/50
0.538
3151631KERR 6
50/50
0.538
3151641KERR 7
50/50
0.538
970673AG2-436 GEN
Solar/Wind Harmer
164.043
970673AG2-436 GEN
Solar/Wind Harmer
83.06
971967AH1-528 GEN
Solar/Wind Harmer
125.223
970085AG2-068 GEN
Solar/Wind Harmer
41.62
970581AG2-369 GEN
Solar/Wind Harmer
35.794
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.295
970865AG2-541 GEN
Solar/Wind Harmer
11.917
316239AB2-077_GEN
Solar/Wind Harmer
0.868
316238AB2-078_GEN
Solar/Wind Harmer
0.868
315243AE2-183_GT3
50/50
11.056
3151051BRUNSWICKS1
50/50
17.38
3151021BRUNSWICKG1
50/50
8.374
971451AH1-221 GEN
50/50
25.435
3151531CLOVER1
50/50
9.312
3151601KERR 3
50/50
0.538
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.8
971629AH1-314 GEN
50/50
17.875
3151561HALLBR1
50/50
0.366
970919AG2-571 GEN
Solar/Wind Harmer
21.227
970087AG2-069 GEN
Solar/Wind Harmer
62.431
957481AF2-042 GEN
Solar/Wind Harmer
166.01
315693AD1-088 GEN
Solar/Wind Harmer
24.233
962491AG1-098 GEN
Solar/Wind Harmer
31.935
315687AD1-152 GEN
Solar/Wind Harmer
5.313
316003AC1-222 GEN
Solar/Wind Harmer
3.193
970401AG2-262 GEN
Solar/Wind Harmer
2.094
316237AB2-079_GEN
Solar/Wind Harmer
0.868
970685AG2-442 GEN
Solar/Wind Harmer
23.682
963171AG1-166 GEN
Solar/Wind Harmer
3.328
971563AH1-280 GEN
Solar/Wind Harmer
3.328
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.224
316129AC1-054 GEN
Solar/Wind Harmer
1.849
970223AG2-152 GEN
Solar/Wind Harmer
17.201
270016AE1-250 BESS
Solar/Wind Harmer
2.839
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.577
316322AB2-045
Solar/Wind Harmer
0.514
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.53
270030AE2-140 GEN
Solar/Wind Harmer
19.734
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.817
316049AB1-081 GEN
Solar/Wind Harmer
1.454
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.785
316375AC2-012 GEN
Solar/Wind Helper
1.014
3145336SMITFLD
Solar/Wind Helper
1.482
316388AE2-253 GEN
Solar/Wind Helper
1.397
3146456SLIGO L269
Solar/Wind Helper
0.359
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.402
316159AE1-175 C
Solar/Wind Helper
0.529
316381AD1-082 GEN
Solar/Wind Helper
1.758
316458AB2-190 GEN2
Solar/Wind Helper
1.933
3141766HARMONY
Solar/Wind Helper
0.065
3138133OCRAN
Solar/Wind Helper
0.193
3142433PROV 92
Solar/Wind Helper
1.275
3142543TWELFTH
Solar/Wind Helper
0.029
964211AG1-282 GEN
Solar/Wind Helper
0.412
3141726DUNNSVL
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.961
3146516WINFALL
Solar/Wind Helper
0.297
316337AD2-073 GEN
Solar/Wind Helper
0.448
3142416OLDCHRC
Solar/Wind Helper
0.759
3142416OLDCHRC
Solar/Wind Helper
0.291
3143526WINTERP
Solar/Wind Helper
1.499
3143226MDLTHAN
Solar/Wind Helper
0.284
315800Z1-036_GEN1
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
3151031BRUNSWICKG2
50/50
8.374
970413AG2-270 GEN
50/50
40.637
3151591KERR 2
50/50
0.538
3144293JTRSVLE
50/50
0.8
970917AG2-570 GEN
Solar/Wind Harmer
167.695
316478AD1-087 GEN
Solar/Wind Harmer
4.227
316486AD2-202 GEN
Solar/Wind Harmer
1.238
970909AG2-566 GEN
Solar/Wind Harmer
3.291
316248AF1-058 C
Solar/Wind Harmer
1.043
960061AF2-297 GEN
Solar/Wind Harmer
17.305
316283AC2-100 C
Solar/Wind Harmer
2.965
971683AH1-343 GEN
Solar/Wind Harmer
13.39
316131AB2-060 GEN
Solar/Wind Harmer
3.076
964241AG1-285 GEN
Solar/Wind Harmer
22.038
315785AD2-033 C
Solar/Wind Harmer
6.282
970257AG2-171 GEN
Solar/Wind Harmer
10.326
959311AF2-222 GEN
Solar/Wind Harmer
28.597
963181AG1-167 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.449
942461AE2-259 GEN
Solar/Wind Harmer
3.824
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.375
270197AD1-017 GEN1
Solar/Wind Harmer
1.676
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.834
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.53
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.564
961601AG1-000A GEN
Solar/Wind Harmer
5.252
315773AC2-141 GEN
Solar/Wind Helper
9.163
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.058
3145336SMITFLD
Solar/Wind Helper
0.148
3146456SLIGO L269
Solar/Wind Helper
0.359
316382AG1-145 C
Solar/Wind Helper
0.469
315839AE2-212 C
Solar/Wind Helper
0.457
316320Y1-086
Solar/Wind Helper
0.148
316156AD2-030 GEN
Solar/Wind Helper
0.492
316280AD1-041 GEN
Solar/Wind Helper
1.092
3142946ENON
Solar/Wind Helper
0.105
316484AD2-074 GEN
Solar/Wind Helper
0.607
316404AE1-155 C
Solar/Wind Helper
2.624
316435W1029_GEN3
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3141906WESTMOR
Solar/Wind Helper
0.115
3146626S HERTFORD
Solar/Wind Helper
0.28
316473AC1-191 GEN
Solar/Wind Helper
1.696
3145273HOLLAND
Solar/Wind Helper
0.188
966881AG1-559 GEN
Solar/Wind Helper
0.329
3146376EDENTON
Solar/Wind Helper
0.226
972185AH1-677 GEN
50/50
39.858
3151041BRUNSWICKG3
50/50
8.374
972187AH1-678 GEN
50/50
19.217
3152661PLYWOOD A
50/50
0.67
970535AG2-341 GEN
50/50
4.577
3144293JTRSVLE
50/50
0.8
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
58.849
970099AG2-077 GEN
Solar/Wind Harmer
66.404
971741AH1-377 GEN
Solar/Wind Harmer
43.978
970301AG2-198 GEN
Solar/Wind Harmer
17.332
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.854
316222AC1-221 GEN
Solar/Wind Harmer
3.208
962561AG1-105 GEN
Solar/Wind Harmer
17.747
939181AE1-148 GEN
Solar/Wind Harmer
16.378
313527AB2-043 GEN
Solar/Wind Harmer
4.643
970323AG2-213 GEN
Solar/Wind Harmer
13.768
971775AH1-396 GEN
Solar/Wind Harmer
1.961
316034AC1-036 C
Solar/Wind Harmer
0.511
958211AF2-115 GEN
Solar/Wind Harmer
4.16
963191AG1-168 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.066
270013AE1-250 PV
Solar/Wind Harmer
2.839
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.394
316197AC1-042 GEN
Solar/Wind Harmer
1.815
942671AE2-283 GEN
Solar/Wind Harmer
4.885
316263AC1-034 GEN
Solar/Wind Harmer
6.316
961601AG1-000A GEN
Solar/Wind Harmer
5.186
316036AC1-147 C
Solar/Wind Helper
0.59
3142956BIRDNECK
Solar/Wind Helper
0.259
316316AC1-027 C
Solar/Wind Helper
0.606
316185AD1-033 GEN
Solar/Wind Helper
1.799
3145506HICKORY
Solar/Wind Helper
1.507
3145506HICKORY
Solar/Wind Helper
0.904
3145506HICKORY
Solar/Wind Helper
0.226
316236AE1-162_GEN
Solar/Wind Helper
0.498
316339AD2-160 GEN
Solar/Wind Helper
1.397
316018AA1-139 ULT2
Solar/Wind Helper
1.567
316017AA1-139 ULT1
Solar/Wind Helper
1.665
3137176SLIGO L2192
Solar/Wind Helper
1.432
3130086AYDLETT
Solar/Wind Helper
1.421
316033AB2-134 GEN
Solar/Wind Helper
1.19
315697AD1-025 GEN
Solar/Wind Helper
3.953
3146386ELIZ CT
Solar/Wind Helper
0.331
316240AF1-291 C
Solar/Wind Helper
0.444
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.318
316075AC2-137 C
Solar/Wind Helper
0.467
316077AC2-138 C
Solar/Wind Helper
0.286
316431W1029_GEN1
Solar/Wind Helper
1.225
316433W1029_GEN2
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3143526WINTERP
Solar/Wind Helper
1.499
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
966871AG1-558 GEN
Solar/Wind Helper
0.374
3144356SAPONY
Solar/Wind Helper
0.492
316468AD1-105 GEN
Solar/Wind Helper
1.305
971443AH1-215 GEN
Solar/Wind Harmer
5.428
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.145
970681AG2-440 GEN
Solar/Wind Harmer
16.916
946301AF1-294 GEN
Solar/Wind Harmer
6.823
961791AG1-021 GEN
Solar/Wind Harmer
3.328
270455AD2-022 GEN
Solar/Wind Harmer
4.701
270457AD2-023 GEN
Solar/Wind Harmer
2.384
315657AE1-056 GEN
Solar/Wind Harmer
9.869
316123AC1-075 GEN
Solar/Wind Harmer
2.789
970165AG2-112 GEN
Solar/Wind Harmer
2.455
970163AG2-111 GEN
Solar/Wind Harmer
2.342
970831AG2-522 GEN
Solar/Wind Harmer
9.813
970285AG2-188 GEN
Solar/Wind Harmer
15.354
971845AH1-439 GEN
Solar/Wind Harmer
8.535
270069AE2-166 C O1
Solar/Wind Harmer
2.415
319010AE1-072 C
Solar/Wind Helper
4.079
3143316POE
Solar/Wind Helper
1.407
316305AF2-043 C
Solar/Wind Helper
0.473
316369SG1_INVT
Solar/Wind Helper
1.664
957831AF2-077 GEN
Solar/Wind Helper
0.466
316132AB2-190 GEN1
Solar/Wind Helper
1.933
316349AD2-085 GEN
Solar/Wind Helper
1.523
313526AB2-022
Solar/Wind Helper
0.505
957601AF2-054 GEN
Solar/Wind Helper
0.438
3141873WAN 176
Solar/Wind Helper
0.065
315662AE1-191 GEN
Solar/Wind Helper
1.747
315666AE1-190 GEN
Solar/Wind Helper
0.437
316059AD1-063 C
Solar/Wind Helper
0.326
3141913WHIT STONE
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3138133OCRAN
Solar/Wind Helper
0.097
3143873LANEXA
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.128
316321Z2-027
Solar/Wind Helper
0.487
3145176PASQUOTANK
Solar/Wind Helper
0.198
3141813NORNECK
Solar/Wind Helper
0.304
316312AB1-027
Solar/Wind Helper
0.556
316233AE1-074 FULL
Solar/Wind Helper
0.44
316223AC1-118
Solar/Wind Helper
0.438
316315AB2-025 C
Solar/Wind Helper
0.418
315611Z1-036_GEN2
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
3130156CHOWAN
Solar/Wind Helper
0.226
LAGNLTFEXP_LAGN->PJM
CLTF
14.626
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.161
TVALTFEXP_TVA->PJM
CLTF
7.294
CPLELTFEXP_CPLE->PJM
CLTF
19.708
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.004
NYPJM->LTFIMP_NY
CLTF
2.38
LGEELTFEXP_LGEE->PJM
CLTF
2.666
WECLTFEXP_WEC->PJM
CLTF
1.395
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.554
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.081
MECLTFEXP_MEC->PJM
CLTF
7.343
SIGELTFEXP_SIGE->PJM
CLTF
0.22

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 511T544_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T544_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.13 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5601.8
MW Contribution:17.06
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
18.952
963041AG1-153 GEN
50/50
16.812
3151541CLOVER2
50/50
9.183
3151611KERR 4
50/50
0.532
3151621KERR 5
50/50
0.532
3151631KERR 6
50/50
0.532
3151641KERR 7
50/50
0.532
970673AG2-436 GEN
Solar/Wind Harmer
162.646
970673AG2-436 GEN
Solar/Wind Harmer
82.352
971967AH1-528 GEN
Solar/Wind Harmer
124.141
970085AG2-068 GEN
Solar/Wind Harmer
41.268
970581AG2-369 GEN
Solar/Wind Harmer
35.491
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.271
970865AG2-541 GEN
Solar/Wind Harmer
11.801
316239AB2-077_GEN
Solar/Wind Harmer
0.856
316238AB2-078_GEN
Solar/Wind Harmer
0.856
971443AH1-215 GEN
Solar/Wind Harmer
5.352
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
20.851
970681AG2-440 GEN
Solar/Wind Harmer
16.681
946301AF1-294 GEN
Solar/Wind Harmer
6.73
961791AG1-021 GEN
Solar/Wind Harmer
3.283
270455AD2-022 GEN
Solar/Wind Harmer
4.664
270457AD2-023 GEN
Solar/Wind Harmer
2.365
315657AE1-056 GEN
Solar/Wind Harmer
9.735
316123AC1-075 GEN
Solar/Wind Harmer
2.761
970165AG2-112 GEN
Solar/Wind Harmer
2.431
970163AG2-111 GEN
Solar/Wind Harmer
2.319
970831AG2-522 GEN
Solar/Wind Harmer
9.696
970285AG2-188 GEN
Solar/Wind Harmer
15.118
971845AH1-439 GEN
Solar/Wind Harmer
8.397
270069AE2-166 C O1
Solar/Wind Harmer
2.394
3143316POE
Solar/Wind Helper
1.57
316132AB2-190 GEN1
Solar/Wind Helper
1.893
316369SG1_INVT
Solar/Wind Helper
1.59
957831AF2-077 GEN
Solar/Wind Helper
0.437
316315AB2-025 C
Solar/Wind Helper
0.494
957601AF2-054 GEN
Solar/Wind Helper
0.418
3141873WAN 176
Solar/Wind Helper
0.062
315662AE1-191 GEN
Solar/Wind Helper
1.674
315666AE1-190 GEN
Solar/Wind Helper
0.419
3143873LANEXA
Solar/Wind Helper
0.186
316059AD1-063 C
Solar/Wind Helper
0.312
3141913WHIT STONE
Solar/Wind Helper
0.309
3138133OCRAN
Solar/Wind Helper
0.093
3141783LANCAST
Solar/Wind Helper
0.184
3141783LANCAST
Solar/Wind Helper
0.123
319010AE1-072 C
Solar/Wind Helper
3.5
316349AD2-085 GEN
Solar/Wind Helper
1.396
316305AF2-043 C
Solar/Wind Helper
0.402
3141813NORNECK
Solar/Wind Helper
0.293
316233AE1-074 FULL
Solar/Wind Helper
0.446
316312AB1-027
Solar/Wind Helper
0.55
313526AB2-022
Solar/Wind Helper
0.431
316223AC1-118
Solar/Wind Helper
0.424
3146486SUNBURY
Solar/Wind Helper
0.274
3146486SUNBURY
Solar/Wind Helper
0.274
316321Z2-027
Solar/Wind Helper
0.414
3145176PASQUOTANK
Solar/Wind Helper
0.168
315243AE2-183_GT3
50/50
10.962
3151051BRUNSWICKS1
50/50
17.232
3151021BRUNSWICKG1
50/50
8.303
971451AH1-221 GEN
50/50
25.218
3151531CLOVER1
50/50
9.227
3151601KERR 3
50/50
0.532
3151581KERR 1
50/50
0.19
3144293JTRSVLE
50/50
0.79
971629AH1-314 GEN
50/50
17.731
3151561HALLBR1
50/50
0.363
970919AG2-571 GEN
Solar/Wind Harmer
21.047
970087AG2-069 GEN
Solar/Wind Harmer
61.902
957481AF2-042 GEN
Solar/Wind Harmer
164.509
315693AD1-088 GEN
Solar/Wind Harmer
24.007
962491AG1-098 GEN
Solar/Wind Harmer
31.634
315687AD1-152 GEN
Solar/Wind Harmer
5.265
316003AC1-222 GEN
Solar/Wind Harmer
3.162
970401AG2-262 GEN
Solar/Wind Harmer
2.07
316237AB2-079_GEN
Solar/Wind Harmer
0.856
970685AG2-442 GEN
Solar/Wind Harmer
23.354
963171AG1-166 GEN
Solar/Wind Harmer
3.283
971563AH1-280 GEN
Solar/Wind Harmer
3.283
3146926FARMVIL
Solar/Wind Harmer
-0.014
971065AG2-659 GEN
Solar/Wind Harmer
11.094
316129AC1-054 GEN
Solar/Wind Harmer
1.827
970223AG2-152 GEN
Solar/Wind Harmer
17.059
270016AE1-250 BESS
Solar/Wind Harmer
2.815
315242AE2-183_GT2
50/50
10.962
315241AE2-183_GT1
50/50
10.894
972185AH1-677 GEN
50/50
39.518
3151041BRUNSWICKG3
50/50
8.303
972187AH1-678 GEN
50/50
19.053
3152661PLYWOOD A
50/50
0.663
970535AG2-341 GEN
50/50
4.519
3144293JTRSVLE
50/50
0.79
3144293JTRSVLE
50/50
0.665
970933AG2-581 GEN
Solar/Wind Harmer
58.334
970099AG2-077 GEN
Solar/Wind Harmer
65.804
971741AH1-377 GEN
Solar/Wind Harmer
43.523
970301AG2-198 GEN
Solar/Wind Harmer
17.145
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.775
316222AC1-221 GEN
Solar/Wind Harmer
3.182
962561AG1-105 GEN
Solar/Wind Harmer
17.536
939181AE1-148 GEN
Solar/Wind Harmer
16.186
313527AB2-043 GEN
Solar/Wind Harmer
4.576
970323AG2-213 GEN
Solar/Wind Harmer
13.574
971775AH1-396 GEN
Solar/Wind Harmer
1.933
316034AC1-036 C
Solar/Wind Harmer
0.503
958211AF2-115 GEN
Solar/Wind Harmer
4.103
963191AG1-168 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
14.918
270013AE1-250 PV
Solar/Wind Harmer
2.815
3146776BUCKING
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.37
316197AC1-042 GEN
Solar/Wind Harmer
1.797
942671AE2-283 GEN
Solar/Wind Harmer
4.838
316263AC1-034 GEN
Solar/Wind Harmer
6.29
961601AG1-000A GEN
Solar/Wind Harmer
5.16
316240AF1-291 C
Solar/Wind Helper
0.471
316036AC1-147 C
Solar/Wind Helper
0.511
316236AE1-162_GEN
Solar/Wind Helper
0.447
316316AC1-027 C
Solar/Wind Helper
0.524
3142956BIRDNECK
Solar/Wind Helper
0.223
316033AB2-134 GEN
Solar/Wind Helper
1.137
315697AD1-025 GEN
Solar/Wind Helper
3.779
316185AD1-033 GEN
Solar/Wind Helper
1.551
3145506HICKORY
Solar/Wind Helper
1.298
3145506HICKORY
Solar/Wind Helper
0.779
3145506HICKORY
Solar/Wind Helper
0.195
3144356SAPONY
Solar/Wind Helper
0.581
316339AD2-160 GEN
Solar/Wind Helper
1.201
316018AA1-139 ULT2
Solar/Wind Helper
1.346
316017AA1-139 ULT1
Solar/Wind Helper
1.43
3142946ENON
Solar/Wind Helper
0.031
3137176SLIGO L2192
Solar/Wind Helper
1.229
3130086AYDLETT
Solar/Wind Helper
1.219
316487AF1-042 GEN
Solar/Wind Helper
0.305
316075AC2-137 C
Solar/Wind Helper
0.459
316077AC2-138 C
Solar/Wind Helper
0.276
3143526WINTERP
Solar/Wind Helper
1.519
3146386ELIZ CT
Solar/Wind Helper
0.283
966871AG1-558 GEN
Solar/Wind Helper
0.376
316468AD1-105 GEN
Solar/Wind Helper
1.308
316431W1029_GEN1
Solar/Wind Helper
1.037
316433W1029_GEN2
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146626S HERTFORD
Solar/Wind Helper
0.236
3146626S HERTFORD
Solar/Wind Helper
0.236
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.528
316322AB2-045
Solar/Wind Harmer
0.506
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.477
270030AE2-140 GEN
Solar/Wind Harmer
19.567
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.809
316049AB1-081 GEN
Solar/Wind Harmer
1.448
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.244
316381AD1-082 GEN
Solar/Wind Helper
1.747
316375AC2-012 GEN
Solar/Wind Helper
0.879
3145336SMITFLD
Solar/Wind Helper
1.331
316458AB2-190 GEN2
Solar/Wind Helper
1.893
316159AE1-175 C
Solar/Wind Helper
0.497
316388AE2-253 GEN
Solar/Wind Helper
1.201
3142433PROV 92
Solar/Wind Helper
1.254
3142543TWELFTH
Solar/Wind Helper
0.03
3141766HARMONY
Solar/Wind Helper
0.062
3146456SLIGO L269
Solar/Wind Helper
0.308
3138133OCRAN
Solar/Wind Helper
0.185
316072AD1-144
Solar/Wind Helper
0.35
316246AF1-032 C
Solar/Wind Helper
0.342
964211AG1-282 GEN
Solar/Wind Helper
0.397
3141726DUNNSVL
Solar/Wind Helper
1.179
3143526WINTERP
Solar/Wind Helper
1.519
3142416OLDCHRC
Solar/Wind Helper
0.752
3143226MDLTHAN
Solar/Wind Helper
0.289
3142416OLDCHRC
Solar/Wind Helper
0.288
316337AD2-073 GEN
Solar/Wind Helper
0.434
3146516WINFALL
Solar/Wind Helper
0.813
3146516WINFALL
Solar/Wind Helper
0.251
3151031BRUNSWICKG2
50/50
8.303
970413AG2-270 GEN
50/50
40.265
3151591KERR 2
50/50
0.532
3144293JTRSVLE
50/50
0.79
970917AG2-570 GEN
Solar/Wind Harmer
166.275
316478AD1-087 GEN
Solar/Wind Harmer
4.189
316486AD2-202 GEN
Solar/Wind Harmer
1.227
970909AG2-566 GEN
Solar/Wind Harmer
3.255
316248AF1-058 C
Solar/Wind Harmer
1.033
960061AF2-297 GEN
Solar/Wind Harmer
17.135
316283AC2-100 C
Solar/Wind Harmer
2.94
971683AH1-343 GEN
Solar/Wind Harmer
13.259
316131AB2-060 GEN
Solar/Wind Harmer
3.032
964241AG1-285 GEN
Solar/Wind Harmer
21.724
315785AD2-033 C
Solar/Wind Harmer
6.194
970257AG2-171 GEN
Solar/Wind Harmer
10.181
959311AF2-222 GEN
Solar/Wind Harmer
28.197
963181AG1-167 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.081
971193AH1-056 GEN
Solar/Wind Harmer
16.225
942461AE2-259 GEN
Solar/Wind Harmer
3.773
3146926FARMVIL
Solar/Wind Harmer
-0.014
270018AE2-047 C O1
Solar/Wind Harmer
1.363
270197AD1-017 GEN1
Solar/Wind Harmer
1.661
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.802
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.477
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.551
961601AG1-000A GEN
Solar/Wind Harmer
5.225
315773AC2-141 GEN
Solar/Wind Helper
8.525
315839AE2-212 C
Solar/Wind Helper
0.497
3144536CHRHLND
Solar/Wind Helper
0.05
3144873MCLAUGH
Solar/Wind Helper
0.008
3145336SMITFLD
Solar/Wind Helper
0.133
316382AG1-145 C
Solar/Wind Helper
0.441
316156AD2-030 GEN
Solar/Wind Helper
0.47
3142946ENON
Solar/Wind Helper
0.104
316280AD1-041 GEN
Solar/Wind Helper
1.046
3146456SLIGO L269
Solar/Wind Helper
0.308
316484AD2-074 GEN
Solar/Wind Helper
0.583
316404AE1-155 C
Solar/Wind Helper
2.523
316320Y1-086
Solar/Wind Helper
0.126
316473AC1-191 GEN
Solar/Wind Helper
1.704
3141906WESTMOR
Solar/Wind Helper
0.111
316435W1029_GEN3
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
966881AG1-559 GEN
Solar/Wind Helper
0.328
3146626S HERTFORD
Solar/Wind Helper
0.236
LAGNLTFEXP_LAGN->PJM
CLTF
14.499
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.842
TVALTFEXP_TVA->PJM
CLTF
7.231
CPLELTFEXP_CPLE->PJM
CLTF
19.58
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.279
NYPJM->LTFIMP_NY
CLTF
2.38
LGEELTFEXP_LGEE->PJM
CLTF
2.637
WECLTFEXP_WEC->PJM
CLTF
1.38
AG2-052LTFEXP_AG2-052->PJM
LTF
0.074
AH1-155LTFEXP_AH1-155->PJM
LTF
0.111
CBM West 1LTFEXP_CBM-W1->PJM
CBM
48.979
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.858
MECLTFEXP_MEC->PJM
CLTF
7.267
SIGELTFEXP_SIGE->PJM
CLTF
0.218

Details for AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line l/o AEP_P4_#10162_05EDAN 1 138_P_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.04 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:360.64
MW Contribution:13.06
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
0.769
24728405LEESVG
50/50
0.23
24684605SMG4
50/50
1.141
971683AH1-343 GEN
Solar/Wind Harmer
40.643
24728405LEESVG
50/50
0.229
24684705SMG5
50/50
0.437
970481AG2-311 GEN
50/50
6.086
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.665
270574AD1-017 GEN2
Solar/Wind Harmer
5.101
270016AE1-250 BESS
Solar/Wind Harmer
2.264
970223AG2-152 GEN
Solar/Wind Harmer
13.058
270173AC1-122 GEN
Solar/Wind Harmer
1.401
962751AG1-124 GEN
Solar/Wind Harmer
5.108
316003AC1-222 GEN
Solar/Wind Helper
1.949
316237AB2-079_GEN
Solar/Wind Helper
0.202
315687AD1-152 GEN
Solar/Wind Helper
0.724
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.665
270197AD1-017 GEN1
Solar/Wind Harmer
1.533
958131AF2-107 GEN
Solar/Wind Harmer
2.307
316248AF1-058 C
Solar/Wind Helper
0.422
316131AB2-060 GEN
Solar/Wind Helper
0.886
315785AD2-033 C
Solar/Wind Helper
1.508
970865AG2-541 GEN
Solar/Wind Harmer
35.485
316123AC1-075 GEN
Solar/Wind Harmer
7.909
970165AG2-112 GEN
Solar/Wind Harmer
6.964
970163AG2-111 GEN
Solar/Wind Harmer
6.643
3147173SINAI
Solar/Wind Helper
0.314
3147243WELCO
Solar/Wind Helper
0.196
316118AC1-105 GEN
Solar/Wind Helper
1.086
316239AB2-077_GEN
Solar/Wind Helper
0.202
316238AB2-078_GEN
Solar/Wind Helper
0.202
3144303KENBRDG
Solar/Wind Helper
0.1
24684405SMG2
50/50
1.134
24684505SMG3
50/50
0.701
24684305SMG1
50/50
0.411
942751AE2-291 GEN
Solar/Wind Harmer
41.056
316217AC1-145 GEN
Solar/Wind Harmer
4.616
316197AC1-042 GEN
Solar/Wind Harmer
3.499
942671AE2-283 GEN
Solar/Wind Harmer
9.42
270013AE1-250 PV
Solar/Wind Harmer
2.264
3146843MT LREL
Solar/Wind Helper
0.245
3146843MT LREL
Solar/Wind Helper
0.245
316034AC1-036 C
Solar/Wind Helper
0.131
TVALTFEXP_TVA->PJM
CLTF
0.041
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.996
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.1
LGEELTFEXP_LGEE->PJM
CLTF
0.269
WECLTFEXP_WEC->PJM
CLTF
0.129
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.998
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.376
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.824
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.391
MECLTFEXP_MEC->PJM
CLTF
0.467
SIGELTFEXP_SIGE->PJM
CLTF
0.018

Details for AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.53 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:355.37
MW Contribution:12.87
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.228
24684605SMG4
50/50
1.125
24684405SMG2
50/50
1.118
24684505SMG3
50/50
0.691
24684305SMG1
50/50
0.405
942751AE2-291 GEN
Solar/Wind Harmer
41.146
316217AC1-145 GEN
Solar/Wind Harmer
4.602
316197AC1-042 GEN
Solar/Wind Harmer
3.489
942671AE2-283 GEN
Solar/Wind Harmer
9.392
270013AE1-250 PV
Solar/Wind Harmer
2.232
3146843MT LREL
Solar/Wind Helper
0.238
3146843MT LREL
Solar/Wind Helper
0.238
316034AC1-036 C
Solar/Wind Helper
0.125
970865AG2-541 GEN
Solar/Wind Harmer
35.6
316123AC1-075 GEN
Solar/Wind Harmer
7.93
970165AG2-112 GEN
Solar/Wind Harmer
6.982
970163AG2-111 GEN
Solar/Wind Harmer
6.661
3147173SINAI
Solar/Wind Helper
0.307
3147243WELCO
Solar/Wind Helper
0.192
316118AC1-105 GEN
Solar/Wind Helper
1.058
316239AB2-077_GEN
Solar/Wind Helper
0.194
316238AB2-078_GEN
Solar/Wind Helper
0.194
3144303KENBRDG
Solar/Wind Helper
0.096
3151561HALLBR1
50/50
0.768
24728405LEESVG
50/50
0.227
24684705SMG5
50/50
0.43
970481AG2-311 GEN
50/50
5.999
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.632
270574AD1-017 GEN2
Solar/Wind Harmer
5.028
270016AE1-250 BESS
Solar/Wind Harmer
2.232
970223AG2-152 GEN
Solar/Wind Harmer
12.873
270173AC1-122 GEN
Solar/Wind Harmer
1.38
962751AG1-124 GEN
Solar/Wind Harmer
5.018
316003AC1-222 GEN
Solar/Wind Helper
1.921
316237AB2-079_GEN
Solar/Wind Helper
0.194
315687AD1-152 GEN
Solar/Wind Helper
0.683
971683AH1-343 GEN
Solar/Wind Harmer
40.784
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.632
270197AD1-017 GEN1
Solar/Wind Harmer
1.511
958131AF2-107 GEN
Solar/Wind Harmer
2.276
316248AF1-058 C
Solar/Wind Helper
0.412
316131AB2-060 GEN
Solar/Wind Helper
0.847
315785AD2-033 C
Solar/Wind Helper
1.439
LAGNLTFEXP_LAGN->PJM
CLTF
0.022
TVALTFEXP_TVA->PJM
CLTF
0.051
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.902
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.092
LGEELTFEXP_LGEE->PJM
CLTF
0.24
WECLTFEXP_WEC->PJM
CLTF
0.115
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.841
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.313
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.307
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.392
MECLTFEXP_MEC->PJM
CLTF
0.422
SIGELTFEXP_SIGE->PJM
CLTF
0.016

Details for AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line l/o AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.27 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:354.46
MW Contribution:12.87
Bus #Bus NameTypeMW Contribution
970865AG2-541 GEN
Solar/Wind Harmer
35.6
316123AC1-075 GEN
Solar/Wind Harmer
7.93
970165AG2-112 GEN
Solar/Wind Harmer
6.982
970163AG2-111 GEN
Solar/Wind Harmer
6.661
3147173SINAI
Solar/Wind Helper
0.307
3147243WELCO
Solar/Wind Helper
0.192
316118AC1-105 GEN
Solar/Wind Helper
1.058
316239AB2-077_GEN
Solar/Wind Helper
0.194
316238AB2-078_GEN
Solar/Wind Helper
0.194
3144303KENBRDG
Solar/Wind Helper
0.096
24684405SMG2
50/50
1.118
24684505SMG3
50/50
0.691
24684305SMG1
50/50
0.405
942751AE2-291 GEN
Solar/Wind Harmer
41.146
316217AC1-145 GEN
Solar/Wind Harmer
4.602
316197AC1-042 GEN
Solar/Wind Harmer
3.489
942671AE2-283 GEN
Solar/Wind Harmer
9.392
270013AE1-250 PV
Solar/Wind Harmer
2.232
3146843MT LREL
Solar/Wind Helper
0.238
3146843MT LREL
Solar/Wind Helper
0.238
316034AC1-036 C
Solar/Wind Helper
0.125
24728405LEESVG
50/50
0.228
24684605SMG4
50/50
1.125
971683AH1-343 GEN
Solar/Wind Harmer
40.784
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.632
270197AD1-017 GEN1
Solar/Wind Harmer
1.511
958131AF2-107 GEN
Solar/Wind Harmer
2.276
316248AF1-058 C
Solar/Wind Helper
0.412
316131AB2-060 GEN
Solar/Wind Helper
0.847
315785AD2-033 C
Solar/Wind Helper
1.439
3151561HALLBR1
50/50
0.768
24728405LEESVG
50/50
0.227
24684705SMG5
50/50
0.43
970481AG2-311 GEN
50/50
5.999
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.632
270574AD1-017 GEN2
Solar/Wind Harmer
5.028
270016AE1-250 BESS
Solar/Wind Harmer
2.232
970223AG2-152 GEN
Solar/Wind Harmer
12.873
270173AC1-122 GEN
Solar/Wind Harmer
1.38
962751AG1-124 GEN
Solar/Wind Harmer
5.018
316003AC1-222 GEN
Solar/Wind Helper
1.921
316237AB2-079_GEN
Solar/Wind Helper
0.194
315687AD1-152 GEN
Solar/Wind Helper
0.683
LAGNLTFEXP_LAGN->PJM
CLTF
0.022
TVALTFEXP_TVA->PJM
CLTF
0.051
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.902
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.092
LGEELTFEXP_LGEE->PJM
CLTF
0.24
WECLTFEXP_WEC->PJM
CLTF
0.115
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.841
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.313
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.307
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.392
MECLTFEXP_MEC->PJM
CLTF
0.422
SIGELTFEXP_SIGE->PJM
CLTF
0.016

Details for AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line l/o AEP_P7-1_#10778___SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10778___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.27 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:354.44
MW Contribution:12.87
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.118
24684505SMG3
50/50
0.691
24684305SMG1
50/50
0.405
942751AE2-291 GEN
Solar/Wind Harmer
41.146
316217AC1-145 GEN
Solar/Wind Harmer
4.602
316197AC1-042 GEN
Solar/Wind Harmer
3.489
942671AE2-283 GEN
Solar/Wind Harmer
9.392
270013AE1-250 PV
Solar/Wind Harmer
2.232
3146843MT LREL
Solar/Wind Helper
0.238
3146843MT LREL
Solar/Wind Helper
0.238
316034AC1-036 C
Solar/Wind Helper
0.125
970865AG2-541 GEN
Solar/Wind Harmer
35.6
316123AC1-075 GEN
Solar/Wind Harmer
7.93
970165AG2-112 GEN
Solar/Wind Harmer
6.982
970163AG2-111 GEN
Solar/Wind Harmer
6.661
3147173SINAI
Solar/Wind Helper
0.307
3147243WELCO
Solar/Wind Helper
0.192
316118AC1-105 GEN
Solar/Wind Helper
1.058
316239AB2-077_GEN
Solar/Wind Helper
0.194
316238AB2-078_GEN
Solar/Wind Helper
0.194
3144303KENBRDG
Solar/Wind Helper
0.096
3151561HALLBR1
50/50
0.768
24728405LEESVG
50/50
0.227
24684705SMG5
50/50
0.43
970481AG2-311 GEN
50/50
5.999
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.633
270574AD1-017 GEN2
Solar/Wind Harmer
5.028
270016AE1-250 BESS
Solar/Wind Harmer
2.232
970223AG2-152 GEN
Solar/Wind Harmer
12.873
270173AC1-122 GEN
Solar/Wind Harmer
1.38
962751AG1-124 GEN
Solar/Wind Harmer
5.018
316003AC1-222 GEN
Solar/Wind Helper
1.921
316237AB2-079_GEN
Solar/Wind Helper
0.194
315687AD1-152 GEN
Solar/Wind Helper
0.683
24728405LEESVG
50/50
0.228
24684605SMG4
50/50
1.125
971683AH1-343 GEN
Solar/Wind Harmer
40.784
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.633
270197AD1-017 GEN1
Solar/Wind Harmer
1.511
958131AF2-107 GEN
Solar/Wind Harmer
2.276
316248AF1-058 C
Solar/Wind Helper
0.412
316131AB2-060 GEN
Solar/Wind Helper
0.847
315785AD2-033 C
Solar/Wind Helper
1.439
LAGNLTFEXP_LAGN->PJM
CLTF
0.022
TVALTFEXP_TVA->PJM
CLTF
0.051
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.902
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.092
LGEELTFEXP_LGEE->PJM
CLTF
0.24
WECLTFEXP_WEC->PJM
CLTF
0.115
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.842
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.313
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.307
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.392
MECLTFEXP_MEC->PJM
CLTF
0.422
SIGELTFEXP_SIGE->PJM
CLTF
0.016

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:218.2 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1492.5
MW Contribution:5.79
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.536
3151531CLOVER1
50/50
6.868
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.479
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.387
971563AH1-280 GEN
Solar/Wind Harmer
6.387
970685AG2-442 GEN
Solar/Wind Harmer
41.098
962491AG1-098 GEN
Solar/Wind Harmer
28.527
315693AD1-088 GEN
Solar/Wind Harmer
20.89
957481AF2-042 GEN
Solar/Wind Harmer
119.73
316237AB2-079_GEN
Solar/Wind Harmer
0.97
315687AD1-152 GEN
Solar/Wind Harmer
3.722
970401AG2-262 GEN
Solar/Wind Harmer
1.828
316003AC1-222 GEN
Solar/Wind Harmer
2.23
971065AG2-659 GEN
Solar/Wind Harmer
10.784
316129AC1-054 GEN
Solar/Wind Harmer
1.809
971795AH1-408 GEN
Solar/Wind Harmer
11.382
960081AF2-299 GEN
Solar/Wind Harmer
1.187
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.663
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.965
316049AB1-081 GEN
Solar/Wind Harmer
0.772
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.715
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
970223AG2-152 GEN
Solar/Wind Harmer
5.79
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.192
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.414
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.314
3151541CLOVER2
50/50
6.835
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
971845AH1-439 GEN
Solar/Wind Harmer
44.839
970285AG2-188 GEN
Solar/Wind Harmer
71.83
315657AE1-056 GEN
Solar/Wind Harmer
20.241
946301AF1-294 GEN
Solar/Wind Harmer
13.094
961791AG1-021 GEN
Solar/Wind Harmer
6.387
970683AG2-441 GEN
Solar/Wind Harmer
36.695
970681AG2-440 GEN
Solar/Wind Harmer
29.356
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.31
971967AH1-528 GEN
Solar/Wind Harmer
73.321
316239AB2-077_GEN
Solar/Wind Harmer
0.97
316238AB2-078_GEN
Solar/Wind Harmer
0.97
316118AC1-105 GEN
Solar/Wind Harmer
1.807
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.03
970831AG2-522 GEN
Solar/Wind Harmer
9.822
316123AC1-075 GEN
Solar/Wind Harmer
1.789
970165AG2-112 GEN
Solar/Wind Harmer
1.575
970163AG2-111 GEN
Solar/Wind Harmer
1.503
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.493
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.635
270457AD2-023 GEN
Solar/Wind Harmer
0.829
315607AA1-063A GEN
Solar/Wind Harmer
0.882
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.411
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.563
270494AE1-108_GEN
Solar/Wind Helper
3.665
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.536
970413AG2-270 GEN
50/50
29.97
3151591KERR 2
50/50
0.482
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.339
970909AG2-566 GEN
Solar/Wind Harmer
5.578
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.735
963181AG1-167 GEN
Solar/Wind Harmer
4.79
959311AF2-222 GEN
Solar/Wind Harmer
45.765
970257AG2-171 GEN
Solar/Wind Harmer
15.97
315785AD2-033 C
Solar/Wind Harmer
9.259
964241AG1-285 GEN
Solar/Wind Harmer
28.316
316478AD1-087 GEN
Solar/Wind Harmer
3.115
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.609
316248AF1-058 C
Solar/Wind Harmer
0.741
960061AF2-297 GEN
Solar/Wind Harmer
12.289
971683AH1-343 GEN
Solar/Wind Harmer
9.199
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.303
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.775
316210AC1-098 GEN
Solar/Wind Harmer
1.194
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.767
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.393
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.414
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.317
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
3144293JTRSVLE
50/50
1.536
3144293JTRSVLE
50/50
1.294
970535AG2-341 GEN
50/50
4.631
3152661PLYWOOD A
50/50
0.509
970301AG2-198 GEN
Solar/Wind Harmer
29.375
971741AH1-377 GEN
Solar/Wind Harmer
63.77
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.984
963191AG1-168 GEN
Solar/Wind Harmer
4.79
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.293
971775AH1-396 GEN
Solar/Wind Harmer
3.032
970933AG2-581 GEN
Solar/Wind Harmer
36.564
970099AG2-077 GEN
Solar/Wind Harmer
47.892
313527AB2-043 GEN
Solar/Wind Harmer
5.323
962561AG1-105 GEN
Solar/Wind Harmer
16.163
964791AG1-342 GEN
Solar/Wind Harmer
5.983
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.395
942751AE2-291 GEN
Solar/Wind Harmer
9.282
316222AC1-221 GEN
Solar/Wind Harmer
1.431
316181AB2-040 GEN
Solar/Wind Harmer
1.454
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.157
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.182
3145783HORNRTN
Solar/Wind Harmer
0.946
3145783HORNRTN
Solar/Wind Harmer
0.296
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.956
316274AC1-208 GEN
Solar/Wind Harmer
0.891
316263AC1-034 GEN
Solar/Wind Harmer
3.354
961601AG1-000A GEN
Solar/Wind Harmer
2.733
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.045
316197AC1-042 GEN
Solar/Wind Harmer
0.792
942671AE2-283 GEN
Solar/Wind Harmer
2.132
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.531
LAGNLTFEXP_LAGN->PJM
CLTF
3.212
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.896
TVALTFEXP_TVA->PJM
CLTF
1.599
CPLELTFEXP_CPLE->PJM
CLTF
5.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.616
NYPJM->LTFIMP_NY
CLTF
0.52
LGEELTFEXP_LGEE->PJM
CLTF
0.521
WECLTFEXP_WEC->PJM
CLTF
0.271
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.51
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.435
MECLTFEXP_MEC->PJM
CLTF
1.488
SIGELTFEXP_SIGE->PJM
CLTF
0.044

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:218.14 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1492.11
MW Contribution:5.79
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.536
3151531CLOVER1
50/50
6.868
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.479
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.387
971563AH1-280 GEN
Solar/Wind Harmer
6.387
970685AG2-442 GEN
Solar/Wind Harmer
41.098
962491AG1-098 GEN
Solar/Wind Harmer
28.527
315693AD1-088 GEN
Solar/Wind Harmer
20.89
957481AF2-042 GEN
Solar/Wind Harmer
119.73
316237AB2-079_GEN
Solar/Wind Harmer
0.97
315687AD1-152 GEN
Solar/Wind Harmer
3.722
970401AG2-262 GEN
Solar/Wind Harmer
1.828
316003AC1-222 GEN
Solar/Wind Harmer
2.23
971065AG2-659 GEN
Solar/Wind Harmer
10.784
316129AC1-054 GEN
Solar/Wind Harmer
1.809
971795AH1-408 GEN
Solar/Wind Harmer
11.382
960081AF2-299 GEN
Solar/Wind Harmer
1.187
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.663
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.965
316049AB1-081 GEN
Solar/Wind Harmer
0.772
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.715
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
970223AG2-152 GEN
Solar/Wind Harmer
5.79
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.192
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.414
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.314
3151541CLOVER2
50/50
6.835
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
971845AH1-439 GEN
Solar/Wind Harmer
44.839
970285AG2-188 GEN
Solar/Wind Harmer
71.83
315657AE1-056 GEN
Solar/Wind Harmer
20.241
946301AF1-294 GEN
Solar/Wind Harmer
13.094
961791AG1-021 GEN
Solar/Wind Harmer
6.387
970683AG2-441 GEN
Solar/Wind Harmer
36.695
970681AG2-440 GEN
Solar/Wind Harmer
29.356
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.31
971967AH1-528 GEN
Solar/Wind Harmer
73.321
316239AB2-077_GEN
Solar/Wind Harmer
0.97
316238AB2-078_GEN
Solar/Wind Harmer
0.97
316118AC1-105 GEN
Solar/Wind Harmer
1.807
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.03
970831AG2-522 GEN
Solar/Wind Harmer
9.822
316123AC1-075 GEN
Solar/Wind Harmer
1.789
970165AG2-112 GEN
Solar/Wind Harmer
1.575
970163AG2-111 GEN
Solar/Wind Harmer
1.503
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.493
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.635
270457AD2-023 GEN
Solar/Wind Harmer
0.829
315607AA1-063A GEN
Solar/Wind Harmer
0.882
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.411
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.563
270494AE1-108_GEN
Solar/Wind Helper
3.665
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.536
970413AG2-270 GEN
50/50
29.97
3151591KERR 2
50/50
0.482
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.339
970909AG2-566 GEN
Solar/Wind Harmer
5.578
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.735
963181AG1-167 GEN
Solar/Wind Harmer
4.79
959311AF2-222 GEN
Solar/Wind Harmer
45.765
970257AG2-171 GEN
Solar/Wind Harmer
15.97
315785AD2-033 C
Solar/Wind Harmer
9.259
964241AG1-285 GEN
Solar/Wind Harmer
28.316
316478AD1-087 GEN
Solar/Wind Harmer
3.115
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.609
316248AF1-058 C
Solar/Wind Harmer
0.741
960061AF2-297 GEN
Solar/Wind Harmer
12.289
971683AH1-343 GEN
Solar/Wind Harmer
9.199
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.303
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.775
316210AC1-098 GEN
Solar/Wind Harmer
1.194
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.767
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.393
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.414
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.317
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
3144293JTRSVLE
50/50
1.536
3144293JTRSVLE
50/50
1.294
970535AG2-341 GEN
50/50
4.631
3152661PLYWOOD A
50/50
0.509
970301AG2-198 GEN
Solar/Wind Harmer
29.375
971741AH1-377 GEN
Solar/Wind Harmer
63.77
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.984
963191AG1-168 GEN
Solar/Wind Harmer
4.79
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.293
971775AH1-396 GEN
Solar/Wind Harmer
3.032
970933AG2-581 GEN
Solar/Wind Harmer
36.564
970099AG2-077 GEN
Solar/Wind Harmer
47.892
313527AB2-043 GEN
Solar/Wind Harmer
5.323
962561AG1-105 GEN
Solar/Wind Harmer
16.163
964791AG1-342 GEN
Solar/Wind Harmer
5.983
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.395
942751AE2-291 GEN
Solar/Wind Harmer
9.282
316222AC1-221 GEN
Solar/Wind Harmer
1.431
316181AB2-040 GEN
Solar/Wind Harmer
1.454
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.157
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.182
3145783HORNRTN
Solar/Wind Harmer
0.946
3145783HORNRTN
Solar/Wind Harmer
0.296
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.956
316274AC1-208 GEN
Solar/Wind Harmer
0.891
316263AC1-034 GEN
Solar/Wind Harmer
3.354
961601AG1-000A GEN
Solar/Wind Harmer
2.733
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.045
316197AC1-042 GEN
Solar/Wind Harmer
0.792
942671AE2-283 GEN
Solar/Wind Harmer
2.132
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.531
LAGNLTFEXP_LAGN->PJM
CLTF
3.212
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.896
TVALTFEXP_TVA->PJM
CLTF
1.599
CPLELTFEXP_CPLE->PJM
CLTF
5.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.616
NYPJM->LTFIMP_NY
CLTF
0.52
LGEELTFEXP_LGEE->PJM
CLTF
0.521
WECLTFEXP_WEC->PJM
CLTF
0.271
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.51
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.435
MECLTFEXP_MEC->PJM
CLTF
1.488
SIGELTFEXP_SIGE->PJM
CLTF
0.044

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:214.52 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1467.34
MW Contribution:5.7
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.838
970285AG2-188 GEN
Solar/Wind Harmer
71.826
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
971967AH1-528 GEN
Solar/Wind Harmer
73.183
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970933AG2-581 GEN
Solar/Wind Harmer
36.495
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:212.24 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:1187.04
MW Contribution:4.0
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.213
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.1
970301AG2-198 GEN
Solar/Wind Harmer
22.295
971741AH1-377 GEN
Solar/Wind Harmer
48.392
3147133PAMPLIN
Solar/Wind Harmer
0.48
3147133PAMPLIN
Solar/Wind Harmer
0.384
958211AF2-115 GEN
Solar/Wind Harmer
5.453
963191AG1-168 GEN
Solar/Wind Harmer
1.818
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.154
971775AH1-396 GEN
Solar/Wind Harmer
0.606
970933AG2-581 GEN
Solar/Wind Harmer
27.718
970099AG2-077 GEN
Solar/Wind Harmer
36.303
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.244
964791AG1-342 GEN
Solar/Wind Harmer
4.773
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.665
942751AE2-291 GEN
Solar/Wind Harmer
7.016
316222AC1-221 GEN
Solar/Wind Harmer
0.517
316181AB2-040 GEN
Solar/Wind Harmer
0.135
3145593CAROLNA
Solar/Wind Harmer
0.091
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.97
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
963171AG1-166 GEN
Solar/Wind Harmer
2.424
971563AH1-280 GEN
Solar/Wind Harmer
4.847
970685AG2-442 GEN
Solar/Wind Harmer
31.186
962491AG1-098 GEN
Solar/Wind Harmer
21.632
315693AD1-088 GEN
Solar/Wind Harmer
17.82
957481AF2-042 GEN
Solar/Wind Harmer
90.757
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.458
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.171
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
9.004
960081AF2-299 GEN
Solar/Wind Harmer
0.903
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.349
3146233WITAKRS
Solar/Wind Harmer
0.261
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.051
316359AB2-059 GEN
Solar/Wind Harmer
0.226
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.062
315722AD1-056 GEN
Solar/Wind Harmer
0.382
3145796HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.068
962571AG1-106 GEN
Solar/Wind Harmer
0.836
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.253
970223AG2-152 GEN
Solar/Wind Harmer
3.997
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.043
941801AE2-185 GEN
Solar/Wind Harmer
1.818
3145823KELFORD
Solar/Wind Harmer
0.056
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.232
963181AG1-167 GEN
Solar/Wind Harmer
1.818
959311AF2-222 GEN
Solar/Wind Harmer
34.653
970257AG2-171 GEN
Solar/Wind Harmer
12.116
315785AD2-033 C
Solar/Wind Harmer
2.953
964241AG1-285 GEN
Solar/Wind Harmer
21.475
316478AD1-087 GEN
Solar/Wind Harmer
1.115
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.935
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.299
971683AH1-343 GEN
Solar/Wind Harmer
6.959
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.287
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.626
3146233WITAKRS
Solar/Wind Harmer
0.329
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.062
961601AG1-000A GEN
Solar/Wind Harmer
4.35
315724AD1-057 GEN
Solar/Wind Harmer
0.227
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.818
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.104
971845AH1-439 GEN
Solar/Wind Harmer
34.055
970285AG2-188 GEN
Solar/Wind Harmer
57.798
315657AE1-056 GEN
Solar/Wind Harmer
16.558
946301AF1-294 GEN
Solar/Wind Harmer
8.968
961791AG1-021 GEN
Solar/Wind Harmer
4.363
970683AG2-441 GEN
Solar/Wind Harmer
27.844
970681AG2-440 GEN
Solar/Wind Harmer
22.275
3144303KENBRDG
Solar/Wind Harmer
0.303
971443AH1-215 GEN
Solar/Wind Harmer
6.304
971967AH1-528 GEN
Solar/Wind Harmer
55.434
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.602
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.073
970831AG2-522 GEN
Solar/Wind Harmer
7.443
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.191
970163AG2-111 GEN
Solar/Wind Harmer
1.136
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.368
315607AA1-063A GEN
Solar/Wind Harmer
0.159
3146043SEABORD
Solar/Wind Harmer
0.076
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.25
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.462
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.252
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.992
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.575
3145783HORNRTN
Solar/Wind Harmer
1.26
3145783HORNRTN
Solar/Wind Harmer
0.394
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.38
316263AC1-034 GEN
Solar/Wind Harmer
2.393
961601AG1-000A GEN
Solar/Wind Harmer
1.088
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.132
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.414
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:209.65 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:1172.59
MW Contribution:4.0
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.213
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.1
970301AG2-198 GEN
Solar/Wind Harmer
22.295
971741AH1-377 GEN
Solar/Wind Harmer
48.392
3147133PAMPLIN
Solar/Wind Harmer
0.48
3147133PAMPLIN
Solar/Wind Harmer
0.384
958211AF2-115 GEN
Solar/Wind Harmer
5.453
963191AG1-168 GEN
Solar/Wind Harmer
1.818
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.154
971775AH1-396 GEN
Solar/Wind Harmer
0.606
970099AG2-077 GEN
Solar/Wind Harmer
36.303
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.244
964791AG1-342 GEN
Solar/Wind Harmer
4.773
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.665
942751AE2-291 GEN
Solar/Wind Harmer
7.016
316222AC1-221 GEN
Solar/Wind Harmer
0.517
316181AB2-040 GEN
Solar/Wind Harmer
0.135
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.992
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.575
3145783HORNRTN
Solar/Wind Harmer
1.26
3145783HORNRTN
Solar/Wind Harmer
0.394
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.38
316263AC1-034 GEN
Solar/Wind Harmer
2.393
961601AG1-000A GEN
Solar/Wind Harmer
1.088
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.132
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.414
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.97
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
963171AG1-166 GEN
Solar/Wind Harmer
2.424
971563AH1-280 GEN
Solar/Wind Harmer
4.847
970685AG2-442 GEN
Solar/Wind Harmer
31.186
962491AG1-098 GEN
Solar/Wind Harmer
21.632
315693AD1-088 GEN
Solar/Wind Harmer
17.82
957481AF2-042 GEN
Solar/Wind Harmer
90.757
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.458
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.171
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
9.004
960081AF2-299 GEN
Solar/Wind Harmer
0.903
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.349
3146233WITAKRS
Solar/Wind Harmer
0.261
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.051
316359AB2-059 GEN
Solar/Wind Harmer
0.226
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.062
315722AD1-056 GEN
Solar/Wind Harmer
0.382
3145796HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.068
962571AG1-106 GEN
Solar/Wind Harmer
0.836
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.253
970223AG2-152 GEN
Solar/Wind Harmer
3.997
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.043
941801AE2-185 GEN
Solar/Wind Harmer
1.818
3145823KELFORD
Solar/Wind Harmer
0.056
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.104
971845AH1-439 GEN
Solar/Wind Harmer
34.055
970285AG2-188 GEN
Solar/Wind Harmer
57.798
315657AE1-056 GEN
Solar/Wind Harmer
16.558
946301AF1-294 GEN
Solar/Wind Harmer
8.968
961791AG1-021 GEN
Solar/Wind Harmer
4.363
970683AG2-441 GEN
Solar/Wind Harmer
27.844
970681AG2-440 GEN
Solar/Wind Harmer
22.275
3144303KENBRDG
Solar/Wind Harmer
0.303
971443AH1-215 GEN
Solar/Wind Harmer
6.304
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.602
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.073
970831AG2-522 GEN
Solar/Wind Harmer
7.443
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.191
970163AG2-111 GEN
Solar/Wind Harmer
1.136
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.368
315607AA1-063A GEN
Solar/Wind Harmer
0.159
3146043SEABORD
Solar/Wind Harmer
0.076
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.25
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.462
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.252
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.232
963181AG1-167 GEN
Solar/Wind Harmer
1.818
959311AF2-222 GEN
Solar/Wind Harmer
34.653
970257AG2-171 GEN
Solar/Wind Harmer
12.116
315785AD2-033 C
Solar/Wind Harmer
2.953
964241AG1-285 GEN
Solar/Wind Harmer
21.475
316478AD1-087 GEN
Solar/Wind Harmer
1.115
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.935
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.299
971683AH1-343 GEN
Solar/Wind Harmer
6.959
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.287
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.626
3146233WITAKRS
Solar/Wind Harmer
0.329
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.062
961601AG1-000A GEN
Solar/Wind Harmer
4.35
315724AD1-057 GEN
Solar/Wind Harmer
0.227
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.818
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:208.48 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1426.03
MW Contribution:5.7
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.838
970285AG2-188 GEN
Solar/Wind Harmer
71.826
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:208.48 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1426.03
MW Contribution:5.7
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.838
970285AG2-188 GEN
Solar/Wind Harmer
71.826
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
316336AC2-165 C
Solar/Wind Helper
1.308
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:219.98 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1537.65
MW Contribution:5.77
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.951
3151591KERR 2
50/50
0.482
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.336
970909AG2-566 GEN
Solar/Wind Harmer
5.575
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.721
963181AG1-167 GEN
Solar/Wind Harmer
4.788
959311AF2-222 GEN
Solar/Wind Harmer
45.74
970257AG2-171 GEN
Solar/Wind Harmer
15.961
315785AD2-033 C
Solar/Wind Harmer
9.254
964241AG1-285 GEN
Solar/Wind Harmer
28.298
316478AD1-087 GEN
Solar/Wind Harmer
3.113
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.606
316248AF1-058 C
Solar/Wind Harmer
0.74
960061AF2-297 GEN
Solar/Wind Harmer
12.278
971683AH1-343 GEN
Solar/Wind Harmer
9.189
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.301
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.773
316210AC1-098 GEN
Solar/Wind Harmer
1.19
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.758
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.392
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.405
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.318
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
3148013FISHERV
Solar/Wind Helper
0.111
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.863
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.477
972003AH1-546 GEN
Solar/Wind Harmer
49.791
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.384
971563AH1-280 GEN
Solar/Wind Harmer
6.384
970685AG2-442 GEN
Solar/Wind Harmer
41.078
962491AG1-098 GEN
Solar/Wind Harmer
28.511
315693AD1-088 GEN
Solar/Wind Harmer
20.878
957481AF2-042 GEN
Solar/Wind Harmer
119.657
316237AB2-079_GEN
Solar/Wind Harmer
0.969
315687AD1-152 GEN
Solar/Wind Harmer
3.719
970401AG2-262 GEN
Solar/Wind Harmer
1.826
316003AC1-222 GEN
Solar/Wind Harmer
2.228
971065AG2-659 GEN
Solar/Wind Harmer
10.772
316129AC1-054 GEN
Solar/Wind Harmer
1.807
971795AH1-408 GEN
Solar/Wind Harmer
11.365
960081AF2-299 GEN
Solar/Wind Harmer
1.184
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.962
316049AB1-081 GEN
Solar/Wind Harmer
0.77
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.712
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
970223AG2-152 GEN
Solar/Wind Harmer
5.769
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.191
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.405
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.316
3151541CLOVER2
50/50
6.83
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
971845AH1-439 GEN
Solar/Wind Harmer
44.827
970285AG2-188 GEN
Solar/Wind Harmer
71.81
315657AE1-056 GEN
Solar/Wind Harmer
20.233
946301AF1-294 GEN
Solar/Wind Harmer
13.088
961791AG1-021 GEN
Solar/Wind Harmer
6.384
970683AG2-441 GEN
Solar/Wind Harmer
36.677
970681AG2-440 GEN
Solar/Wind Harmer
29.342
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.305
971967AH1-528 GEN
Solar/Wind Harmer
73.277
316239AB2-077_GEN
Solar/Wind Harmer
0.969
316238AB2-078_GEN
Solar/Wind Harmer
0.969
316118AC1-105 GEN
Solar/Wind Harmer
1.805
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.02
970831AG2-522 GEN
Solar/Wind Harmer
9.81
316123AC1-075 GEN
Solar/Wind Harmer
1.786
970165AG2-112 GEN
Solar/Wind Harmer
1.573
970163AG2-111 GEN
Solar/Wind Harmer
1.5
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.489
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.631
270457AD2-023 GEN
Solar/Wind Harmer
0.827
315607AA1-063A GEN
Solar/Wind Harmer
0.88
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.41
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.561
270494AE1-108_GEN
Solar/Wind Helper
3.67
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.067
3148013FISHERV
Solar/Wind Helper
0.064
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.627
3152661PLYWOOD A
50/50
0.509
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.363
971741AH1-377 GEN
Solar/Wind Harmer
63.743
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.98
963191AG1-168 GEN
Solar/Wind Harmer
4.788
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.282
971775AH1-396 GEN
Solar/Wind Harmer
3.031
970933AG2-581 GEN
Solar/Wind Harmer
36.542
970099AG2-077 GEN
Solar/Wind Harmer
47.863
313527AB2-043 GEN
Solar/Wind Harmer
5.319
962561AG1-105 GEN
Solar/Wind Harmer
16.15
964791AG1-342 GEN
Solar/Wind Harmer
5.978
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.382
942751AE2-291 GEN
Solar/Wind Harmer
9.268
316222AC1-221 GEN
Solar/Wind Harmer
1.428
316181AB2-040 GEN
Solar/Wind Harmer
1.451
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.155
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.18
3145783HORNRTN
Solar/Wind Harmer
0.944
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.888
316263AC1-034 GEN
Solar/Wind Harmer
3.343
961601AG1-000A GEN
Solar/Wind Harmer
2.724
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.041
316197AC1-042 GEN
Solar/Wind Harmer
0.789
942671AE2-283 GEN
Solar/Wind Harmer
2.125
315821AE2-092 GEN
Solar/Wind Helper
2.535
LAGNLTFEXP_LAGN->PJM
CLTF
3.179
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.848
TVALTFEXP_TVA->PJM
CLTF
1.583
CPLELTFEXP_CPLE->PJM
CLTF
5.212
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.402
NYPJM->LTFIMP_NY
CLTF
0.53
LGEELTFEXP_LGEE->PJM
CLTF
0.51
WECLTFEXP_WEC->PJM
CLTF
0.265
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.278
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.374
MECLTFEXP_MEC->PJM
CLTF
1.462
SIGELTFEXP_SIGE->PJM
CLTF
0.043

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:219.92 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1537.26
MW Contribution:5.77
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.951
3151591KERR 2
50/50
0.482
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.336
970909AG2-566 GEN
Solar/Wind Harmer
5.575
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.721
963181AG1-167 GEN
Solar/Wind Harmer
4.788
959311AF2-222 GEN
Solar/Wind Harmer
45.74
970257AG2-171 GEN
Solar/Wind Harmer
15.961
315785AD2-033 C
Solar/Wind Harmer
9.254
964241AG1-285 GEN
Solar/Wind Harmer
28.298
316478AD1-087 GEN
Solar/Wind Harmer
3.113
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.606
316248AF1-058 C
Solar/Wind Harmer
0.74
960061AF2-297 GEN
Solar/Wind Harmer
12.278
971683AH1-343 GEN
Solar/Wind Harmer
9.189
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.301
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.773
316210AC1-098 GEN
Solar/Wind Harmer
1.19
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.758
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.392
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.405
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.318
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.863
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.477
972003AH1-546 GEN
Solar/Wind Harmer
49.791
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.384
971563AH1-280 GEN
Solar/Wind Harmer
6.384
970685AG2-442 GEN
Solar/Wind Harmer
41.078
962491AG1-098 GEN
Solar/Wind Harmer
28.511
315693AD1-088 GEN
Solar/Wind Harmer
20.878
957481AF2-042 GEN
Solar/Wind Harmer
119.657
316237AB2-079_GEN
Solar/Wind Harmer
0.969
315687AD1-152 GEN
Solar/Wind Harmer
3.719
970401AG2-262 GEN
Solar/Wind Harmer
1.826
316003AC1-222 GEN
Solar/Wind Harmer
2.228
971065AG2-659 GEN
Solar/Wind Harmer
10.772
316129AC1-054 GEN
Solar/Wind Harmer
1.807
971795AH1-408 GEN
Solar/Wind Harmer
11.365
960081AF2-299 GEN
Solar/Wind Harmer
1.184
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.962
316049AB1-081 GEN
Solar/Wind Harmer
0.77
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.712
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
970223AG2-152 GEN
Solar/Wind Harmer
5.769
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.191
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.405
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.316
3151541CLOVER2
50/50
6.83
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
971845AH1-439 GEN
Solar/Wind Harmer
44.827
970285AG2-188 GEN
Solar/Wind Harmer
71.81
315657AE1-056 GEN
Solar/Wind Harmer
20.233
946301AF1-294 GEN
Solar/Wind Harmer
13.088
961791AG1-021 GEN
Solar/Wind Harmer
6.384
970683AG2-441 GEN
Solar/Wind Harmer
36.677
970681AG2-440 GEN
Solar/Wind Harmer
29.342
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.305
971967AH1-528 GEN
Solar/Wind Harmer
73.277
316239AB2-077_GEN
Solar/Wind Harmer
0.969
316238AB2-078_GEN
Solar/Wind Harmer
0.969
316118AC1-105 GEN
Solar/Wind Harmer
1.805
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.02
970831AG2-522 GEN
Solar/Wind Harmer
9.81
316123AC1-075 GEN
Solar/Wind Harmer
1.786
970165AG2-112 GEN
Solar/Wind Harmer
1.573
970163AG2-111 GEN
Solar/Wind Harmer
1.5
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.489
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.631
270457AD2-023 GEN
Solar/Wind Harmer
0.827
315607AA1-063A GEN
Solar/Wind Harmer
0.88
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.41
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.561
270494AE1-108_GEN
Solar/Wind Helper
3.67
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.067
3148013FISHERV
Solar/Wind Helper
0.064
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
3148013FISHERV
Solar/Wind Helper
0.111
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.627
3152661PLYWOOD A
50/50
0.509
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.363
971741AH1-377 GEN
Solar/Wind Harmer
63.743
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.98
963191AG1-168 GEN
Solar/Wind Harmer
4.788
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.282
971775AH1-396 GEN
Solar/Wind Harmer
3.031
970933AG2-581 GEN
Solar/Wind Harmer
36.542
970099AG2-077 GEN
Solar/Wind Harmer
47.863
313527AB2-043 GEN
Solar/Wind Harmer
5.319
962561AG1-105 GEN
Solar/Wind Harmer
16.15
964791AG1-342 GEN
Solar/Wind Harmer
5.978
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.382
942751AE2-291 GEN
Solar/Wind Harmer
9.268
316222AC1-221 GEN
Solar/Wind Harmer
1.428
316181AB2-040 GEN
Solar/Wind Harmer
1.451
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.155
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.18
3145783HORNRTN
Solar/Wind Harmer
0.944
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.888
316263AC1-034 GEN
Solar/Wind Harmer
3.343
961601AG1-000A GEN
Solar/Wind Harmer
2.724
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.041
316197AC1-042 GEN
Solar/Wind Harmer
0.789
942671AE2-283 GEN
Solar/Wind Harmer
2.125
315821AE2-092 GEN
Solar/Wind Helper
2.535
LAGNLTFEXP_LAGN->PJM
CLTF
3.179
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.848
TVALTFEXP_TVA->PJM
CLTF
1.583
CPLELTFEXP_CPLE->PJM
CLTF
5.212
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.402
NYPJM->LTFIMP_NY
CLTF
0.53
LGEELTFEXP_LGEE->PJM
CLTF
0.51
WECLTFEXP_WEC->PJM
CLTF
0.265
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.278
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.374
MECLTFEXP_MEC->PJM
CLTF
1.462
SIGELTFEXP_SIGE->PJM
CLTF
0.043

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:216.35 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1512.31
MW Contribution:5.68
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
972003AH1-546 GEN
Solar/Wind Harmer
49.802
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.379
971563AH1-280 GEN
Solar/Wind Harmer
6.379
970685AG2-442 GEN
Solar/Wind Harmer
41.041
962491AG1-098 GEN
Solar/Wind Harmer
28.467
315693AD1-088 GEN
Solar/Wind Harmer
20.844
957481AF2-042 GEN
Solar/Wind Harmer
119.424
316237AB2-079_GEN
Solar/Wind Harmer
0.967
315687AD1-152 GEN
Solar/Wind Harmer
3.708
970401AG2-262 GEN
Solar/Wind Harmer
1.822
316003AC1-222 GEN
Solar/Wind Harmer
2.219
971065AG2-659 GEN
Solar/Wind Harmer
10.747
316129AC1-054 GEN
Solar/Wind Harmer
1.803
971795AH1-408 GEN
Solar/Wind Harmer
11.364
960081AF2-299 GEN
Solar/Wind Harmer
1.186
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.658
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.951
316049AB1-081 GEN
Solar/Wind Harmer
0.761
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.707
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
970223AG2-152 GEN
Solar/Wind Harmer
5.68
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.385
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.31
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.826
970285AG2-188 GEN
Solar/Wind Harmer
71.806
315657AE1-056 GEN
Solar/Wind Harmer
20.219
946301AF1-294 GEN
Solar/Wind Harmer
13.078
961791AG1-021 GEN
Solar/Wind Harmer
6.379
970683AG2-441 GEN
Solar/Wind Harmer
36.643
970681AG2-440 GEN
Solar/Wind Harmer
29.315
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.296
971967AH1-528 GEN
Solar/Wind Harmer
73.139
316239AB2-077_GEN
Solar/Wind Harmer
0.967
316238AB2-078_GEN
Solar/Wind Harmer
0.967
316118AC1-105 GEN
Solar/Wind Harmer
1.799
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.987
970831AG2-522 GEN
Solar/Wind Harmer
9.789
316123AC1-075 GEN
Solar/Wind Harmer
1.778
970165AG2-112 GEN
Solar/Wind Harmer
1.566
970163AG2-111 GEN
Solar/Wind Harmer
1.494
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.49
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.605
270457AD2-023 GEN
Solar/Wind Harmer
0.814
315607AA1-063A GEN
Solar/Wind Harmer
0.881
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.406
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.564
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.331
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
-0.168
971193AH1-056 GEN
Solar/Wind Harmer
33.698
963181AG1-167 GEN
Solar/Wind Harmer
4.785
959311AF2-222 GEN
Solar/Wind Harmer
45.693
970257AG2-171 GEN
Solar/Wind Harmer
15.944
315785AD2-033 C
Solar/Wind Harmer
9.243
964241AG1-285 GEN
Solar/Wind Harmer
28.257
316478AD1-087 GEN
Solar/Wind Harmer
3.106
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.6
316248AF1-058 C
Solar/Wind Harmer
0.737
960061AF2-297 GEN
Solar/Wind Harmer
12.232
971683AH1-343 GEN
Solar/Wind Harmer
9.152
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.287
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.767
316210AC1-098 GEN
Solar/Wind Harmer
1.185
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.727
315724AD1-057 GEN
Solar/Wind Harmer
0.389
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.385
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.343
971741AH1-377 GEN
Solar/Wind Harmer
63.689
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.974
963191AG1-168 GEN
Solar/Wind Harmer
4.785
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.258
971775AH1-396 GEN
Solar/Wind Harmer
3.027
970933AG2-581 GEN
Solar/Wind Harmer
36.473
970099AG2-077 GEN
Solar/Wind Harmer
47.77
313527AB2-043 GEN
Solar/Wind Harmer
5.31
962561AG1-105 GEN
Solar/Wind Harmer
16.108
964791AG1-342 GEN
Solar/Wind Harmer
5.961
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.346
942751AE2-291 GEN
Solar/Wind Harmer
9.222
316222AC1-221 GEN
Solar/Wind Harmer
1.414
316181AB2-040 GEN
Solar/Wind Harmer
1.452
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.154
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.178
3145783HORNRTN
Solar/Wind Harmer
0.943
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.884
316263AC1-034 GEN
Solar/Wind Harmer
3.306
961601AG1-000A GEN
Solar/Wind Harmer
2.693
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
316217AC1-145 GEN
Solar/Wind Harmer
1.032
316197AC1-042 GEN
Solar/Wind Harmer
0.782
942671AE2-283 GEN
Solar/Wind Harmer
2.107
315821AE2-092 GEN
Solar/Wind Helper
2.531
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:213.74 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:1221.6
MW Contribution:3.98
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.212
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.099
3146776BUCKING
Solar/Wind Harmer
3.045
3146776BUCKING
Solar/Wind Harmer
0.247
970301AG2-198 GEN
Solar/Wind Harmer
22.286
971741AH1-377 GEN
Solar/Wind Harmer
48.371
3147133PAMPLIN
Solar/Wind Harmer
0.479
3147133PAMPLIN
Solar/Wind Harmer
0.383
958211AF2-115 GEN
Solar/Wind Harmer
5.451
963191AG1-168 GEN
Solar/Wind Harmer
1.817
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.146
971775AH1-396 GEN
Solar/Wind Harmer
0.605
970933AG2-581 GEN
Solar/Wind Harmer
27.701
970099AG2-077 GEN
Solar/Wind Harmer
36.281
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.234
964791AG1-342 GEN
Solar/Wind Harmer
4.769
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.655
942751AE2-291 GEN
Solar/Wind Harmer
7.004
316222AC1-221 GEN
Solar/Wind Harmer
0.516
316181AB2-040 GEN
Solar/Wind Harmer
0.134
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.99
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.571
3145783HORNRTN
Solar/Wind Harmer
1.257
3145783HORNRTN
Solar/Wind Harmer
0.393
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.283
316274AC1-208 GEN
Solar/Wind Harmer
0.379
316263AC1-034 GEN
Solar/Wind Harmer
2.385
961601AG1-000A GEN
Solar/Wind Harmer
1.084
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.131
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.409
315821AE2-092 GEN
Solar/Wind Helper
2.531
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.952
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.158
3151411GASTONB
50/50
0.158
972003AH1-546 GEN
Solar/Wind Harmer
37.761
316322AB2-045
Solar/Wind Harmer
0.006
3146776BUCKING
Solar/Wind Harmer
0.305
3146926FARMVIL
Solar/Wind Harmer
0.38
963171AG1-166 GEN
Solar/Wind Harmer
2.423
971563AH1-280 GEN
Solar/Wind Harmer
4.845
970685AG2-442 GEN
Solar/Wind Harmer
31.17
962491AG1-098 GEN
Solar/Wind Harmer
21.62
315693AD1-088 GEN
Solar/Wind Harmer
17.81
957481AF2-042 GEN
Solar/Wind Harmer
90.702
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.457
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.163
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
8.991
960081AF2-299 GEN
Solar/Wind Harmer
0.901
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.348
3146233WITAKRS
Solar/Wind Harmer
0.26
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
316359AB2-059 GEN
Solar/Wind Harmer
0.225
316049AB1-081 GEN
Solar/Wind Harmer
0.359
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.061
315722AD1-056 GEN
Solar/Wind Harmer
0.381
3145796HORNRTN
Solar/Wind Harmer
0.194
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.064
962571AG1-106 GEN
Solar/Wind Harmer
0.833
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.252
970223AG2-152 GEN
Solar/Wind Harmer
3.983
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.042
941801AE2-185 GEN
Solar/Wind Harmer
1.811
3145823KELFORD
Solar/Wind Harmer
0.056
316336AC2-165 C
Solar/Wind Helper
1.31
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.158
3151411GASTONB
50/50
0.158
3146776BUCKING
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Harmer
0.38
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.219
963181AG1-167 GEN
Solar/Wind Harmer
1.817
959311AF2-222 GEN
Solar/Wind Harmer
34.634
970257AG2-171 GEN
Solar/Wind Harmer
12.109
315785AD2-033 C
Solar/Wind Harmer
2.951
964241AG1-285 GEN
Solar/Wind Harmer
21.461
316478AD1-087 GEN
Solar/Wind Harmer
1.114
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.934
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.29
971683AH1-343 GEN
Solar/Wind Harmer
6.951
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.286
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.624
3146233WITAKRS
Solar/Wind Harmer
0.328
3146233WITAKRS
Solar/Wind Harmer
0.044
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.061
961601AG1-000A GEN
Solar/Wind Harmer
4.335
315724AD1-057 GEN
Solar/Wind Harmer
0.226
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.811
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.103
971845AH1-439 GEN
Solar/Wind Harmer
34.045
970285AG2-188 GEN
Solar/Wind Harmer
57.782
315657AE1-056 GEN
Solar/Wind Harmer
16.55
946301AF1-294 GEN
Solar/Wind Harmer
8.963
961791AG1-021 GEN
Solar/Wind Harmer
4.361
970683AG2-441 GEN
Solar/Wind Harmer
27.831
970681AG2-440 GEN
Solar/Wind Harmer
22.264
3144303KENBRDG
Solar/Wind Harmer
0.302
971443AH1-215 GEN
Solar/Wind Harmer
6.301
971967AH1-528 GEN
Solar/Wind Harmer
55.401
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.601
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.066
970831AG2-522 GEN
Solar/Wind Harmer
7.435
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.134
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.367
315607AA1-063A GEN
Solar/Wind Harmer
0.158
3146043SEABORD
Solar/Wind Harmer
0.075
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.249
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.44
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.251
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:211.19 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:1206.97
MW Contribution:3.98
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.103
971845AH1-439 GEN
Solar/Wind Harmer
34.045
970285AG2-188 GEN
Solar/Wind Harmer
57.782
315657AE1-056 GEN
Solar/Wind Harmer
16.55
946301AF1-294 GEN
Solar/Wind Harmer
8.963
961791AG1-021 GEN
Solar/Wind Harmer
4.361
970683AG2-441 GEN
Solar/Wind Harmer
27.831
970681AG2-440 GEN
Solar/Wind Harmer
22.264
3144303KENBRDG
Solar/Wind Harmer
0.302
971443AH1-215 GEN
Solar/Wind Harmer
6.301
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.601
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.066
970831AG2-522 GEN
Solar/Wind Harmer
7.435
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.134
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.367
315607AA1-063A GEN
Solar/Wind Harmer
0.158
3146043SEABORD
Solar/Wind Harmer
0.075
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.249
3145796HORNRTN
Solar/Wind Harmer
0.189
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.212
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.099
3146776BUCKING
Solar/Wind Harmer
3.045
3146776BUCKING
Solar/Wind Harmer
0.247
970301AG2-198 GEN
Solar/Wind Harmer
22.286
971741AH1-377 GEN
Solar/Wind Harmer
48.371
3147133PAMPLIN
Solar/Wind Harmer
0.479
3147133PAMPLIN
Solar/Wind Harmer
0.383
958211AF2-115 GEN
Solar/Wind Harmer
5.451
963191AG1-168 GEN
Solar/Wind Harmer
1.817
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.146
971775AH1-396 GEN
Solar/Wind Harmer
0.605
970099AG2-077 GEN
Solar/Wind Harmer
36.281
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.234
964791AG1-342 GEN
Solar/Wind Harmer
4.769
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.655
942751AE2-291 GEN
Solar/Wind Harmer
7.004
316222AC1-221 GEN
Solar/Wind Harmer
0.516
316181AB2-040 GEN
Solar/Wind Harmer
0.134
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.99
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.571
3145783HORNRTN
Solar/Wind Harmer
1.257
3145783HORNRTN
Solar/Wind Harmer
0.393
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.283
316274AC1-208 GEN
Solar/Wind Harmer
0.379
316263AC1-034 GEN
Solar/Wind Harmer
2.385
961601AG1-000A GEN
Solar/Wind Harmer
1.084
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.131
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.409
315821AE2-092 GEN
Solar/Wind Helper
2.531
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.952
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.158
3151411GASTONB
50/50
0.158
972003AH1-546 GEN
Solar/Wind Harmer
37.761
316322AB2-045
Solar/Wind Harmer
0.006
3146776BUCKING
Solar/Wind Harmer
0.305
3146926FARMVIL
Solar/Wind Harmer
0.38
963171AG1-166 GEN
Solar/Wind Harmer
2.423
971563AH1-280 GEN
Solar/Wind Harmer
4.845
970685AG2-442 GEN
Solar/Wind Harmer
31.17
962491AG1-098 GEN
Solar/Wind Harmer
21.62
315693AD1-088 GEN
Solar/Wind Harmer
17.81
957481AF2-042 GEN
Solar/Wind Harmer
90.702
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.457
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.163
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
8.991
960081AF2-299 GEN
Solar/Wind Harmer
0.901
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.348
3146233WITAKRS
Solar/Wind Harmer
0.26
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
316359AB2-059 GEN
Solar/Wind Harmer
0.225
316049AB1-081 GEN
Solar/Wind Harmer
0.359
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.061
315722AD1-056 GEN
Solar/Wind Harmer
0.381
3145796HORNRTN
Solar/Wind Harmer
0.194
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.064
962571AG1-106 GEN
Solar/Wind Harmer
0.833
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.252
970223AG2-152 GEN
Solar/Wind Harmer
3.983
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.042
941801AE2-185 GEN
Solar/Wind Harmer
1.811
3145823KELFORD
Solar/Wind Harmer
0.056
316336AC2-165 C
Solar/Wind Helper
1.31
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.158
3151411GASTONB
50/50
0.158
3146776BUCKING
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Harmer
0.38
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.219
963181AG1-167 GEN
Solar/Wind Harmer
1.817
959311AF2-222 GEN
Solar/Wind Harmer
34.634
970257AG2-171 GEN
Solar/Wind Harmer
12.109
315785AD2-033 C
Solar/Wind Harmer
2.951
964241AG1-285 GEN
Solar/Wind Harmer
21.461
316478AD1-087 GEN
Solar/Wind Harmer
1.114
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.934
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.29
971683AH1-343 GEN
Solar/Wind Harmer
6.951
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.286
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.624
3146233WITAKRS
Solar/Wind Harmer
0.328
3146233WITAKRS
Solar/Wind Harmer
0.044
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.44
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.251
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.061
961601AG1-000A GEN
Solar/Wind Harmer
4.335
315724AD1-057 GEN
Solar/Wind Harmer
0.226
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.811
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:210.43 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1470.9
MW Contribution:5.68
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.826
970285AG2-188 GEN
Solar/Wind Harmer
71.806
315657AE1-056 GEN
Solar/Wind Harmer
20.219
946301AF1-294 GEN
Solar/Wind Harmer
13.078
961791AG1-021 GEN
Solar/Wind Harmer
6.379
970683AG2-441 GEN
Solar/Wind Harmer
36.643
970681AG2-440 GEN
Solar/Wind Harmer
29.315
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.296
316239AB2-077_GEN
Solar/Wind Harmer
0.967
316238AB2-078_GEN
Solar/Wind Harmer
0.967
316118AC1-105 GEN
Solar/Wind Harmer
1.799
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.987
970831AG2-522 GEN
Solar/Wind Harmer
9.789
316123AC1-075 GEN
Solar/Wind Harmer
1.778
970165AG2-112 GEN
Solar/Wind Harmer
1.566
970163AG2-111 GEN
Solar/Wind Harmer
1.494
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.49
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.605
270457AD2-023 GEN
Solar/Wind Harmer
0.814
315607AA1-063A GEN
Solar/Wind Harmer
0.881
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.406
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.564
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.331
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
-0.168
971193AH1-056 GEN
Solar/Wind Harmer
33.698
963181AG1-167 GEN
Solar/Wind Harmer
4.785
959311AF2-222 GEN
Solar/Wind Harmer
45.693
970257AG2-171 GEN
Solar/Wind Harmer
15.944
315785AD2-033 C
Solar/Wind Harmer
9.243
964241AG1-285 GEN
Solar/Wind Harmer
28.257
316478AD1-087 GEN
Solar/Wind Harmer
3.106
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.6
316248AF1-058 C
Solar/Wind Harmer
0.737
960061AF2-297 GEN
Solar/Wind Harmer
12.232
971683AH1-343 GEN
Solar/Wind Harmer
9.152
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.287
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.767
316210AC1-098 GEN
Solar/Wind Harmer
1.185
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.727
315724AD1-057 GEN
Solar/Wind Harmer
0.389
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.385
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.343
971741AH1-377 GEN
Solar/Wind Harmer
63.689
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.974
963191AG1-168 GEN
Solar/Wind Harmer
4.785
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.258
971775AH1-396 GEN
Solar/Wind Harmer
3.027
970099AG2-077 GEN
Solar/Wind Harmer
47.77
313527AB2-043 GEN
Solar/Wind Harmer
5.31
962561AG1-105 GEN
Solar/Wind Harmer
16.108
964791AG1-342 GEN
Solar/Wind Harmer
5.961
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.346
942751AE2-291 GEN
Solar/Wind Harmer
9.222
316222AC1-221 GEN
Solar/Wind Harmer
1.414
316181AB2-040 GEN
Solar/Wind Harmer
1.452
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.154
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.178
3145783HORNRTN
Solar/Wind Harmer
0.943
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.884
316263AC1-034 GEN
Solar/Wind Harmer
3.306
961601AG1-000A GEN
Solar/Wind Harmer
2.693
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
316217AC1-145 GEN
Solar/Wind Harmer
1.032
316197AC1-042 GEN
Solar/Wind Harmer
0.782
942671AE2-283 GEN
Solar/Wind Harmer
2.107
315821AE2-092 GEN
Solar/Wind Helper
2.531
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
972003AH1-546 GEN
Solar/Wind Harmer
49.802
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.379
971563AH1-280 GEN
Solar/Wind Harmer
6.379
970685AG2-442 GEN
Solar/Wind Harmer
41.041
962491AG1-098 GEN
Solar/Wind Harmer
28.467
315693AD1-088 GEN
Solar/Wind Harmer
20.844
957481AF2-042 GEN
Solar/Wind Harmer
119.424
316237AB2-079_GEN
Solar/Wind Harmer
0.967
315687AD1-152 GEN
Solar/Wind Harmer
3.708
970401AG2-262 GEN
Solar/Wind Harmer
1.822
316003AC1-222 GEN
Solar/Wind Harmer
2.219
971065AG2-659 GEN
Solar/Wind Harmer
10.747
316129AC1-054 GEN
Solar/Wind Harmer
1.803
971795AH1-408 GEN
Solar/Wind Harmer
11.364
960081AF2-299 GEN
Solar/Wind Harmer
1.186
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.658
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.951
316049AB1-081 GEN
Solar/Wind Harmer
0.761
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.707
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
970223AG2-152 GEN
Solar/Wind Harmer
5.68
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.385
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.31
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:210.43 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1470.9
MW Contribution:5.68
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.826
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
972003AH1-546 GEN
Solar/Wind Harmer
49.802
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.379
971563AH1-280 GEN
Solar/Wind Harmer
6.379
970685AG2-442 GEN
Solar/Wind Harmer
41.041
962491AG1-098 GEN
Solar/Wind Harmer
28.467
315693AD1-088 GEN
Solar/Wind Harmer
20.844
957481AF2-042 GEN
Solar/Wind Harmer
119.424
316237AB2-079_GEN
Solar/Wind Harmer
0.967
315687AD1-152 GEN
Solar/Wind Harmer
3.708
970401AG2-262 GEN
Solar/Wind Harmer
1.822
316003AC1-222 GEN
Solar/Wind Harmer
2.219
971065AG2-659 GEN
Solar/Wind Harmer
10.747
316129AC1-054 GEN
Solar/Wind Harmer
1.803
971795AH1-408 GEN
Solar/Wind Harmer
11.364
960081AF2-299 GEN
Solar/Wind Harmer
1.186
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.658
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.951
316049AB1-081 GEN
Solar/Wind Harmer
0.761
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.707
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
970223AG2-152 GEN
Solar/Wind Harmer
5.68
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.385
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.31
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.343
971741AH1-377 GEN
Solar/Wind Harmer
63.689
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.974
963191AG1-168 GEN
Solar/Wind Harmer
4.785
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.258
971775AH1-396 GEN
Solar/Wind Harmer
3.027
970099AG2-077 GEN
Solar/Wind Harmer
47.77
313527AB2-043 GEN
Solar/Wind Harmer
5.31
962561AG1-105 GEN
Solar/Wind Harmer
16.108
964791AG1-342 GEN
Solar/Wind Harmer
5.961
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.346
942751AE2-291 GEN
Solar/Wind Harmer
9.222
316222AC1-221 GEN
Solar/Wind Harmer
1.414
316181AB2-040 GEN
Solar/Wind Harmer
1.452
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.154
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.178
3145783HORNRTN
Solar/Wind Harmer
0.943
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.884
316263AC1-034 GEN
Solar/Wind Harmer
3.306
961601AG1-000A GEN
Solar/Wind Harmer
2.693
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
970285AG2-188 GEN
Solar/Wind Harmer
71.806
315657AE1-056 GEN
Solar/Wind Harmer
20.219
946301AF1-294 GEN
Solar/Wind Harmer
13.078
961791AG1-021 GEN
Solar/Wind Harmer
6.379
970683AG2-441 GEN
Solar/Wind Harmer
36.643
970681AG2-440 GEN
Solar/Wind Harmer
29.315
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.296
316239AB2-077_GEN
Solar/Wind Harmer
0.967
316238AB2-078_GEN
Solar/Wind Harmer
0.967
316118AC1-105 GEN
Solar/Wind Harmer
1.799
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.987
970831AG2-522 GEN
Solar/Wind Harmer
9.789
316123AC1-075 GEN
Solar/Wind Harmer
1.778
970165AG2-112 GEN
Solar/Wind Harmer
1.566
970163AG2-111 GEN
Solar/Wind Harmer
1.494
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.49
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.605
270457AD2-023 GEN
Solar/Wind Harmer
0.814
315607AA1-063A GEN
Solar/Wind Harmer
0.881
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.406
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.564
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.331
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
-0.168
971193AH1-056 GEN
Solar/Wind Harmer
33.698
963181AG1-167 GEN
Solar/Wind Harmer
4.785
959311AF2-222 GEN
Solar/Wind Harmer
45.693
970257AG2-171 GEN
Solar/Wind Harmer
15.944
315785AD2-033 C
Solar/Wind Harmer
9.243
964241AG1-285 GEN
Solar/Wind Harmer
28.257
316478AD1-087 GEN
Solar/Wind Harmer
3.106
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.6
316248AF1-058 C
Solar/Wind Harmer
0.737
960061AF2-297 GEN
Solar/Wind Harmer
12.232
971683AH1-343 GEN
Solar/Wind Harmer
9.152
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.287
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.767
316210AC1-098 GEN
Solar/Wind Harmer
1.185
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.727
315724AD1-057 GEN
Solar/Wind Harmer
0.389
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.385
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
316217AC1-145 GEN
Solar/Wind Harmer
1.032
316197AC1-042 GEN
Solar/Wind Harmer
0.782
942671AE2-283 GEN
Solar/Wind Harmer
2.107
315821AE2-092 GEN
Solar/Wind Helper
2.531
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042
CONTINGENCY 'AEP_P7-1_#10817___SRT-A'
 OPEN BRANCH FROM BUS 242575 TO BUS 242737 CKT 1   /*05CANDLER MT 138.0 - 05OPOSSUMCK  138.0
 OPEN BRANCH FROM BUS 242575 TO BUS 242781 CKT 1   /*05CANDLER MT 138.0 - 05RUSTBR     138.0
 OPEN BRANCH FROM BUS 242575 TO BUS 243814 CKT 1   /*05CANDLER MT 138.0 - 05REDEYE     138.0
 OPEN BRANCH FROM BUS 242701 TO BUS 314667 CKT 1   /*05LEESVI     138.0 - 4ALTVSTA     138.0
END
CONTINGENCY 'AEP_P4_#10213_05CLOVRD 138_A_SRT-A'
 OPEN BRANCH FROM BUS 242560 TO BUS 242607 CKT 1    /*05BONSCK     138.0 - 05CLOVRD     138.0
 OPEN BRANCH FROM BUS 242560 TO BUS 242840 CKT 1    /*05BONSCK     138.0 - 05VINTON     138.0
 OPEN BRANCH FROM BUS 242607 TO BUS 243892 CKT 1    /*05CLOVRD     138.0 - 05MEADSTORSS 138.0
 OPEN BRANCH FROM BUS 242720 TO BUS 242775 CKT 1    /*05MONETA     138.0 - 05ROCKCAS SS 138.0
 OPEN BRANCH FROM BUS 242720 TO BUS 243892 CKT 1    /*05MONETA     138.0 - 05MEADSTORSS 138.0
 OPEN BRANCH FROM BUS 242773 TO BUS 242840 CKT 1    /*05ROANO1     138.0 - 05VINTON     138.0
 OPEN BRANCH FROM BUS 242775 TO BUS 242802 CKT 1    /*05ROCKCAS SS 138.0 - 05SMITHMTN   138.0
 OPEN BRANCH FROM BUS 242775 TO BUS 245675 CKT Z1   /*05ROCKCAS SS 138.0 - 05WHITEHOUS8 138.0
 OPEN BRANCH FROM BUS 243892 TO BUS 290923 CKT Z1   /*05MEADSTORSS 138.0 - 05MEADSTOR8  138.0
END
CONTINGENCY 'AEP_P4_#10210_05CLOVRD 138_A2_SRT-A'
 OPEN BRANCH FROM BUS 242607 TO BUS 243892 CKT 1    /*05CLOVRD     138.0 - 05MEADSTORSS 138.0
 OPEN BRANCH FROM BUS 242720 TO BUS 242775 CKT 1    /*05MONETA     138.0 - 05ROCKCAS SS 138.0
 OPEN BRANCH FROM BUS 242720 TO BUS 243892 CKT 1    /*05MONETA     138.0 - 05MEADSTORSS 138.0
 OPEN BRANCH FROM BUS 242775 TO BUS 242802 CKT 1    /*05ROCKCAS SS 138.0 - 05SMITHMTN   138.0
 OPEN BRANCH FROM BUS 243892 TO BUS 290923 CKT Z1   /*05MEADSTORSS 138.0 - 05MEADSTOR8  138.0
 REMOVE LOAD D8 FROM BUS 242607                     /*05CLOVRD     138.0
END
CONTINGENCY 'AEP_P7-1_#10808___SRT-A'
 OPEN BRANCH FROM BUS 242701 TO BUS 242802 CKT 1   /*05LEESVI     138.0 - 05SMITHMTN   138.0
 OPEN BRANCH FROM BUS 242701 TO BUS 247284 CKT 1   /*05LEESVI     138.0 - 05LEESVG      13.8
 OPEN BRANCH FROM BUS 242701 TO BUS 314667 CKT 1   /*05LEESVI     138.0 - 4ALTVSTA     138.0
 OPEN BRANCH FROM BUS 242802 TO BUS 243814 CKT 1   /*05SMITHMTN   138.0 - 05REDEYE     138.0
END
CONTINGENCY 'AEP_P2-2_#6213_05WLAKE 138_1_SRT-A'
 OPEN BRANCH FROM BUS 242748 TO BUS 242802 CKT 1   /*05PENHOOK    138.0 - 05SMITHMTN   138.0
 OPEN BRANCH FROM BUS 242748 TO BUS 243951 CKT 1   /*05PENHOOK    138.0 - 05REDWOOD    138.0
 OPEN BRANCH FROM BUS 242843 TO BUS 243951 CKT 1   /*05WLAKE      138.0 - 05REDWOOD    138.0
END
CONTINGENCY 'AEP_P2-2_#6212_05WLAKE 138_2_SRT-A'
 OPEN BRANCH FROM BUS 242555 TO BUS 242843 CKT 1   /*05BLAINE     138.0 - 05WLAKE      138.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AP_P2-3_MP-500-020_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-021_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AEP_P4_#37_05MOUNTN 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
END
CONTINGENCY 'AEP_P4_#2942_05KAMMER 765_PP_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 OPEN BRANCH FROM BUS 242925 TO BUS 243188 CKT 1   /*05KAMMER     765.0 - 05MLG1        26.0
 REMOVE UNIT 1 FROM BUS 243188                     /*05MLG1        26.0
END
CONTINGENCY 'DVP_P4-2: 151T1047_SRT-A'
 OPEN BRANCH FROM BUS 313168 TO BUS 314696 CKT 1   /*3HUBER DP    115.0 - 3SEDGE HILL  115.0
 OPEN BRANCH FROM BUS 313168 TO BUS 316000 CKT 1   /*3HUBER DP    115.0 - AC1-222 TAP  115.0
 OPEN BRANCH FROM BUS 313825 TO BUS 314696 CKT 1   /*3PLYWOOD     115.0 - 3SEDGE HILL  115.0
 OPEN BUS 313168                                   /*3HUBER DP    115.0
END
CONTINGENCY 'DVP_P4-2: 104702_SRT-A'
 OPEN BRANCH FROM BUS 313168 TO BUS 314696 CKT 1   /*3HUBER DP    115.0 - 3SEDGE HILL  115.0
 OPEN BRANCH FROM BUS 313168 TO BUS 316000 CKT 1   /*3HUBER DP    115.0 - AC1-222 TAP  115.0
 OPEN BUS 313168                                   /*3HUBER DP    115.0
 OPEN BUS 314520                                   /*3SEDGE_1     115.0
END
CONTINGENCY 'DVP_P4-2: 1016T1047_SRT-A'
 OPEN BRANCH FROM BUS 313168 TO BUS 314696 CKT 1   /*3HUBER DP    115.0 - 3SEDGE HILL  115.0
 OPEN BRANCH FROM BUS 313168 TO BUS 316000 CKT 1   /*3HUBER DP    115.0 - AC1-222 TAP  115.0
 OPEN BRANCH FROM BUS 314688 TO BUS 316000 CKT 1   /*3CRSTL HILL  115.0 - AC1-222 TAP  115.0
 OPEN BRANCH FROM BUS 314688 TO BUS 971682 CKT 1   /*3CRSTL HILL  115.0 - AH1-343 TP   115.0
 OPEN BUS 313168                                   /*3HUBER DP    115.0
 OPEN BUS 314688                                   /*3CRSTL HILL  115.0
 OPEN BUS 316000                                   /*AC1-222 TAP  115.0
 OPEN BUS 316001                                   /*AC1-222 MAIN 115.0
 OPEN BUS 316002                                   /*AC1-222 COL   34.5
 OPEN BUS 316003                                   /*AC1-222 GEN    0.6
END
CONTINGENCY 'DVP_P4-2: 101672_SRT-A'
 OPEN BRANCH FROM BUS 314688 TO BUS 316000 CKT 1   /*3CRSTL HILL  115.0 - AC1-222 TAP  115.0
 OPEN BRANCH FROM BUS 314688 TO BUS 971682 CKT 1   /*3CRSTL HILL  115.0 - AH1-343 TP   115.0
 OPEN BUS 314688                                   /*3CRSTL HILL  115.0
 OPEN BUS 316000                                   /*AC1-222 TAP  115.0
 OPEN BUS 316001                                   /*AC1-222 MAIN 115.0
 OPEN BUS 316002                                   /*AC1-222 COL   34.5
 OPEN BUS 316003                                   /*AC1-222 GEN    0.6
END
CONTINGENCY 'DVP_P4-2: 104772_SRT-A'
 OPEN BRANCH FROM BUS 313168 TO BUS 314696 CKT 1   /*3HUBER DP    115.0 - 3SEDGE HILL  115.0
 OPEN BRANCH FROM BUS 313168 TO BUS 316000 CKT 1   /*3HUBER DP    115.0 - AC1-222 TAP  115.0
 OPEN BUS 313168                                   /*3HUBER DP    115.0
 OPEN BUS 316000                                   /*AC1-222 TAP  115.0
 OPEN BUS 316001                                   /*AC1-222 MAIN 115.0
 OPEN BUS 316002                                   /*AC1-222 COL   34.5
 OPEN BUS 316003                                   /*AC1-222 GEN    0.6
END
CONTINGENCY 'DVP_P1-2: LN 1047_SRT-A'
 OPEN BRANCH FROM BUS 313168 TO BUS 314696 CKT 1   /*3HUBER DP    115.0 - 3SEDGE HILL  115.0
 OPEN BRANCH FROM BUS 313168 TO BUS 316000 CKT 1   /*3HUBER DP    115.0 - AC1-222 TAP  115.0
 OPEN BUS 313168                                   /*3HUBER DP    115.0
END
CONTINGENCY 'DVP_P1-2: LN 1016_SRT-A-1'
 OPEN BRANCH FROM BUS 314688 TO BUS 316000 CKT 1   /*3CRSTL HILL  115.0 - AC1-222 TAP  115.0
 OPEN BRANCH FROM BUS 314688 TO BUS 971682 CKT 1   /*3CRSTL HILL  115.0 - AH1-343 TP   115.0
 OPEN BUS 314688                                   /*3CRSTL HILL  115.0
END
CONTINGENCY 'AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A'
 OPEN BRANCH FROM BUS 242531 TO BUS 242632 CKT 4    /*05EDANV2     230.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242531 TO BUS 304094 CKT 1    /*05EDANV2     230.0 - 6YANCY TAP   230.0
 OPEN BRANCH FROM BUS 242549 TO BUS 242632 CKT 1    /*05BANSTR     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 242632 CKT 1    /*05E.MONU     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242631 TO BUS 242632 CKT Z1   /*05EDAN 1     138.0 - 05EDAN 2     138.0
END
CONTINGENCY 'AEP_P7-1_#10778___SRT-A'
 OPEN BRANCH FROM BUS 242531 TO BUS 242632 CKT 4    /*05EDANV2     230.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242531 TO BUS 304094 CKT 1    /*05EDANV2     230.0 - 6YANCY TAP   230.0
 OPEN BRANCH FROM BUS 242549 TO BUS 242632 CKT 1    /*05BANSTR     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 242632 CKT 1    /*05E.MONU     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 242770 CKT 1    /*05E.MONU     138.0 - 05RIGIS      138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 243948 CKT 3    /*05E.MONU     138.0 - 05BRANTLY     69.0
 OPEN BRANCH FROM BUS 242631 TO BUS 242632 CKT Z1   /*05EDAN 1     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242770 TO BUS 243988 CKT 1    /*05RIGIS      138.0 - 05RIGIS       69.0
 OPEN BRANCH FROM BUS 243974 TO BUS 243988 CKT 1    /*05GOODYEAR1   69.0 - 05RIGIS       69.0
END
CONTINGENCY 'AEP_P4_#10162_05EDAN 1 138_P_SRT-A'
 OPEN BRANCH FROM BUS 242530 TO BUS 242631 CKT 5    /*05EDANV1     230.0 - 05EDAN 1     138.0
 OPEN BRANCH FROM BUS 242530 TO BUS 270450 CKT 1    /*05EDANV1     230.0 - AD2-022 TAP  230.0
 OPEN BRANCH FROM BUS 242531 TO BUS 304094 CKT 1    /*05EDANV2     230.0 - 6YANCY TAP   230.0
 OPEN BRANCH FROM BUS 242549 TO BUS 242632 CKT 1    /*05BANSTR     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242620 TO BUS 242631 CKT 1    /*05DANVL2     138.0 - 05EDAN 1     138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 242632 CKT 1    /*05E.MONU     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242631 TO BUS 242632 CKT Z1   /*05EDAN 1     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242631 TO BUS 243962 CKT 1    /*05EDAN 1     138.0 - 05EDANV1EQ     1.0
 OPEN BRANCH FROM BUS 242631 TO BUS 246972 CKT 1    /*05EDAN 1     138.0 - 05ROCKSP     138.0
 OPEN BRANCH FROM BUS 243960 TO BUS 243962 CKT 1    /*05E.DANVIL    69.0 - 05EDANV1EQ     1.0
 OPEN BRANCH FROM BUS 243961 TO BUS 243962 CKT 1    /*05EDANVILL    12.0 - 05EDANV1EQ     1.0
 REMOVE SWSHUNT FROM BUS 242631                     /*05EDAN 1     138.0
 REMOVE SWSHUNT FROM BUS 243960                     /*05E.DANVIL    69.0
END
CONTINGENCY 'AEP_P4_#10164_05EDAN 2 138_M_SRT-A'
 OPEN BRANCH FROM BUS 242531 TO BUS 242632 CKT 4    /*05EDANV2     230.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242531 TO BUS 304094 CKT 1    /*05EDANV2     230.0 - 6YANCY TAP   230.0
 OPEN BRANCH FROM BUS 242549 TO BUS 242632 CKT 1    /*05BANSTR     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242549 TO BUS 314668 CKT Z1   /*05BANSTR     138.0 - 4BANISTR     138.0
 OPEN BRANCH FROM BUS 242549 TO BUS 970222 CKT 1    /*05BANSTR     138.0 - AG2-152 TP   138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 242632 CKT 1    /*05E.MONU     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242631 TO BUS 242632 CKT Z1   /*05EDAN 1     138.0 - 05EDAN 2     138.0
END
CONTINGENCY 'AEP_P4_#10687_05EDAN 2 138_N_SRT-A'
 OPEN BRANCH FROM BUS 242531 TO BUS 242632 CKT 4    /*05EDANV2     230.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242531 TO BUS 304094 CKT 1    /*05EDANV2     230.0 - 6YANCY TAP   230.0
 OPEN BRANCH FROM BUS 242549 TO BUS 242632 CKT 1    /*05BANSTR     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 242632 CKT 1    /*05E.MONU     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 242770 CKT 1    /*05E.MONU     138.0 - 05RIGIS      138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 243948 CKT 3    /*05E.MONU     138.0 - 05BRANTLY     69.0
 OPEN BRANCH FROM BUS 242631 TO BUS 242632 CKT Z1   /*05EDAN 1     138.0 - 05EDAN 2     138.0
 REMOVE SWSHUNT FROM BUS 242629                     /*05E.MONU     138.0
END
CONTINGENCY 'AEP_P4_#8676_05EDANV2 230_S_SRT-A'
 OPEN BRANCH FROM BUS 242531 TO BUS 242632 CKT 4    /*05EDANV2     230.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242531 TO BUS 304094 CKT 1    /*05EDANV2     230.0 - 6YANCY TAP   230.0
 OPEN BRANCH FROM BUS 242549 TO BUS 242632 CKT 1    /*05BANSTR     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 242632 CKT 1    /*05E.MONU     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242631 TO BUS 242632 CKT Z1   /*05EDAN 1     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 304094 TO BUS 304095 CKT 1    /*6YANCY TAP   230.0 - 6YANCYVILLE  230.0
 OPEN BRANCH FROM BUS 304094 TO BUS 304097 CKT 1    /*6YANCY TAP   230.0 - 6CONCD2230TT 230.0
END
CONTINGENCY 'AEP_P1-2_#5366_SRT-A-1'
 OPEN BRANCH FROM BUS 242549 TO BUS 242632 CKT 1    /*05BANSTR     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242549 TO BUS 314668 CKT Z1   /*05BANSTR     138.0 - 4BANISTR     138.0
 OPEN BRANCH FROM BUS 242549 TO BUS 970222 CKT 1    /*05BANSTR     138.0 - AG2-152 TP   138.0
END
CONTINGENCY 'AEP_P1-3_#10688_05EDANV2 230_4_SRT-A'
 OPEN BRANCH FROM BUS 242531 TO BUS 242632 CKT 4    /*05EDANV2     230.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242531 TO BUS 304094 CKT 1    /*05EDANV2     230.0 - 6YANCY TAP   230.0
 OPEN BRANCH FROM BUS 242549 TO BUS 242632 CKT 1    /*05BANSTR     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 242632 CKT 1    /*05E.MONU     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242631 TO BUS 242632 CKT Z1   /*05EDAN 1     138.0 - 05EDAN 2     138.0
END
CONTINGENCY 'AEP_P7-1_#10781___SRT-A-1'
 OPEN BRANCH FROM BUS 242530 TO BUS 270450 CKT 1   /*05EDANV1     230.0 - AD2-022 TAP  230.0
 OPEN BRANCH FROM BUS 242531 TO BUS 304094 CKT 1   /*05EDANV2     230.0 - 6YANCY TAP   230.0
 OPEN BRANCH FROM BUS 304094 TO BUS 304095 CKT 1   /*6YANCY TAP   230.0 - 6YANCYVILLE  230.0
 OPEN BRANCH FROM BUS 304094 TO BUS 304097 CKT 1   /*6YANCY TAP   230.0 - 6CONCD2230TT 230.0
END
CONTINGENCY 'DVP_P2-2: ALTAVISTA 115KV_SRT-A'
 OPEN BUS 313162   /*3HALL BR TAP 115.0
 OPEN BUS 314515   /*3ALTVS_1     115.0
 OPEN BUS 314666   /*3ALTVSTA     115.0
 OPEN BUS 314700   /*3HALL BR     115.0
 OPEN BUS 314705   /*3HURT        115.0
 OPEN BUS 315156   /*1HALLBR1      13.8
END
CONTINGENCY 'DVP_P4-2: 511T556_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 OPEN BRANCH FROM BUS 971966 TO BUS 314936 CKT 1                /*AH1-528 TP   500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 587T591_SRT-S'
 OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1                /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 OPEN BRANCH FROM BUS 971966 TO BUS 314936 CKT 1                /*AH1-528 TP   500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 55692_SRT-S'
 OPEN BRANCH FROM BUS 314936 TO BUS 971966 CKT 1                /*8RAWLINGS    500.0 - AH1-528 TP   500.0
 OPEN BUS 314920                                                /*8RAWLIN_STC1 500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P1-2: LN 587_SRT-A-3'
 OPEN BRANCH FROM BUS 971966 TO BUS 314936 CKT 1   /*AH1-528 TP   500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P1-2: LN 593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P4-2: H2T593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313986 CKT 2   /*8UNITY       500.0 - 6UNITY       230.0
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P4-2: H1T593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313986 CKT 1   /*8UNITY       500.0 - 6UNITY       230.0
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P4-2: 509T570_SRT-A'
 OPEN BRANCH FROM BUS 314935 TO BUS 314945 CKT 1   /*8HERITAGE    500.0 - 8BRUNSWICK   500.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315102 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG1  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315103 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG2  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315104 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG3  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315105 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKS1  19.0
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 OPEN BUS 314945                                   /*8BRUNSWICK   500.0
 OPEN BUS 315102                                   /*1BRUNSWICKG1  21.0
 OPEN BUS 315103                                   /*1BRUNSWICKG2  21.0
 OPEN BUS 315104                                   /*1BRUNSWICKG3  21.0
 OPEN BUS 315105                                   /*1BRUNSWICKS1  19.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-3'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-2'
 OPEN BRANCH FROM BUS 970916 TO BUS 970084 CKT 1   /*AG2-570 TP   500.0 - AG2-068 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 57062_SRT-S'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1                /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 SET POSTCONTRATING 3464 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3464 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P1-2: LN 555_SRT-A'
 OPEN BRANCH FROM BUS 314907 TO BUS 314912 CKT 1   /*8DOOMS       500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P7-1: LN 2168-555_SRT-A'
 OPEN BRANCH FROM BUS 314794 TO BUS 314854 CKT 1   /*6DOOMS       230.0 - 6LEXNGT1     230.0
 OPEN BRANCH FROM BUS 314907 TO BUS 314912 CKT 1   /*8DOOMS       500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-2'
 OPEN BRANCH FROM BUS 941030 TO BUS 970672 CKT 1   /*AE2-094 TP   500.0 - AG2-436 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 58572_SRT-A'
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P4-5: W72_SRT-A'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1   /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P4-2: XT585_SRT-S'
 OPEN BRANCH FROM BUS 970672 TO BUS 314940 CKT 1                /*AG2-436 TP   500.0 - 8ROGERS RD   500.0
 SET POSTCONTRATING 3464 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET PRECONTRATING 3464 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
END
CONTINGENCY 'DVP_P4-2: 54472_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 939410 CKT 1                /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P1-2: LN 511_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 51192_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 OPEN BUS 314921                                                /*8RAWLIN_STC2 500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 51172_SRT-S'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1                /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 511T544_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 939410 CKT 1                /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
242549 to 242632 ckt 1
242519 to 314912 ckt 1
242687 to 242734 ckt 1
242701 to 314667 ckt 1
290234 to 242802 ckt 1
242741 to 242687 ckt 1
242802 to 242701 ckt 1
314688 to 316000 ckt 1
313168 to 314696 ckt 1
314667 to 242741 ckt 1
314677 to 972002 ckt 1
315684 to 314690 ckt 1
314692 to 970284 ckt 1
304070 to 316281 ckt 1
314697 to 315684 ckt 1
314901 to 314991 ckt 1
314936 to 314902 ckt 1
314940 to 970672 ckt 1
314991 to 314926 ckt 1
316000 to 313168 ckt 1
941030 to 314902 ckt 1
970222 to 242549 ckt 1
970284 to 971844 ckt 1
970672 to 941030 ckt 1
971682 to 314688 ckt 1
971844 to 314677 ckt 1
972002 to 314747 ckt 1

Winter Peak Analysis

The New Service Request AG2-152 was evaluated as a 131.0 MW (79.0 MW Capacity) injection in the AEP area.

AG2-152 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 131.0 MW (131.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P1-2_#3174_6_SRT-A
SingleAC101.09 %304.56B307.890.49
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P1-3_#1372_05JOSHUA 765_1_SRT-A
SingleAC100.99 %304.56B307.570.49
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 509T570_SRT-A
BreakerAC143.28 %694.0B994.380.73
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-3
SingleAC136.4 %652.36B889.840.74
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-2
SingleAC134.99 %652.36B880.620.74
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 57062_SRT-W
BreakerAC130.48 %694.0B905.50.74
IPDCPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 509T570_SRT-A
BreakerAC107.4 %694.0B745.3214.7
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 59162_SRT-W
BreakerAC104.06 %694.0B722.20.56
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: XT591_SRT-W
BreakerAC104.06 %694.0B722.20.56
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 59192-1_SRT-W
BreakerAC104.05 %694.0B722.140.56

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P1-2_#3174_6_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#3174_6_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.09 %
Rating:304.56 MVA
Rating Type:B
MVA to Mitigate:307.89
MW Contribution:0.49
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.51
24728405LEESVG
50/50
0.51
3146843MT LREL
Solar/Wind Helper
0.156
3146843MT LREL
Solar/Wind Helper
0.156
3147123OTTER R
Solar/Wind Helper
0.694
3147312GRETNA
Solar/Wind Helper
0.257
3147312GRETNA
Solar/Wind Helper
1.029
24684305SMG1
50/50
1.217
24684405SMG2
50/50
2.782
24684505SMG3
50/50
2.086
24684605SMG4
50/50
2.087
24684705SMG5
50/50
1.043
316248AF1-058 C
Solar/Wind Helper
0.065
3146802CHATHAM
Solar/Wind Helper
0.965
3147243WELCO
Solar/Wind Helper
0.127
3147173SINAI
Solar/Wind Helper
0.203
270173AC1-122 GEN
Solar/Wind Harmer
0
316123AC1-075 GEN
Solar/Wind Helper
0.852
316197AC1-042 GEN
Solar/Wind Helper
0.868
970223AG2-152 GEN
Solar/Wind Harmer
0.488
970481AG2-311 GEN
50/50
9.129
316003AC1-222 GEN
Solar/Wind Helper
0.316
316118AC1-105 GEN
Solar/Wind Helper
0.147
316217AC1-145 GEN
Solar/Wind Helper
1.033
NYPJM->LTFIMP_NY
CLTF
0.082
LGEELTFEXP_LGEE->PJM
CLTF
0.14
WECLTFEXP_WEC->PJM
CLTF
0.069
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.053
LAGNLTFEXP_LAGN->PJM
CLTF
0.33
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.554
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.36
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.69
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.024
TVALTFEXP_TVA->PJM
CLTF
0.18
MECLTFEXP_MEC->PJM
CLTF
0.303
SIGELTFEXP_SIGE->PJM
CLTF
0.01

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P1-3_#1372_05JOSHUA 765_1_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-3_#1372_05JOSHUA 765_1_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.99 %
Rating:304.56 MVA
Rating Type:B
MVA to Mitigate:307.57
MW Contribution:0.49
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.51
24728405LEESVG
50/50
0.51
3146843MT LREL
Solar/Wind Helper
0.156
3146843MT LREL
Solar/Wind Helper
0.156
3147123OTTER R
Solar/Wind Helper
0.694
3147312GRETNA
Solar/Wind Helper
0.257
3147312GRETNA
Solar/Wind Helper
1.029
24684305SMG1
50/50
1.217
24684405SMG2
50/50
2.782
24684505SMG3
50/50
2.086
24684605SMG4
50/50
2.087
24684705SMG5
50/50
1.043
316248AF1-058 C
Solar/Wind Helper
0.065
3146802CHATHAM
Solar/Wind Helper
0.965
3147243WELCO
Solar/Wind Helper
0.127
3147173SINAI
Solar/Wind Helper
0.203
270173AC1-122 GEN
Solar/Wind Harmer
0
316123AC1-075 GEN
Solar/Wind Helper
0.852
316197AC1-042 GEN
Solar/Wind Helper
0.868
970223AG2-152 GEN
Solar/Wind Harmer
0.488
970481AG2-311 GEN
50/50
9.129
316003AC1-222 GEN
Solar/Wind Helper
0.316
316118AC1-105 GEN
Solar/Wind Helper
0.147
316217AC1-145 GEN
Solar/Wind Helper
1.033
NYPJM->LTFIMP_NY
CLTF
0.082
LGEELTFEXP_LGEE->PJM
CLTF
0.14
WECLTFEXP_WEC->PJM
CLTF
0.069
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.053
LAGNLTFEXP_LAGN->PJM
CLTF
0.33
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.554
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.36
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.69
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.024
TVALTFEXP_TVA->PJM
CLTF
0.18
MECLTFEXP_MEC->PJM
CLTF
0.303
SIGELTFEXP_SIGE->PJM
CLTF
0.01

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 509T570_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:143.28 %
Rating:694.0 MVA
Rating Type:B
MVA to Mitigate:994.38
MW Contribution:0.73
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Helper
0.153
3147133PAMPLIN
Solar/Wind Helper
1.357
3147133PAMPLIN
Solar/Wind Helper
0.346
3147133PAMPLIN
Solar/Wind Helper
0.432
3143316POE
Solar/Wind Helper
0.789
3145506HICKORY
Solar/Wind Helper
0.729
3145506HICKORY
Solar/Wind Helper
0.438
3145506HICKORY
Solar/Wind Helper
0.109
3146776BUCKING
Solar/Wind Helper
1.198
3146776BUCKING
Solar/Wind Helper
0.097
3146776BUCKING
Solar/Wind Helper
0.108
3146776BUCKING
Solar/Wind Helper
0.12
3143226MDLTHAN
Solar/Wind Helper
0.18
3146843MT LREL
Solar/Wind Helper
0.804
3146843MT LREL
Solar/Wind Helper
0.804
3146926FARMVIL
Solar/Wind Helper
0.225
3146926FARMVIL
Solar/Wind Helper
0.225
3147123OTTER R
Solar/Wind Helper
0.119
316034AC1-036 C
Solar/Wind Helper
0.104
316036AC1-147 C
Solar/Wind Helper
0.061
316159AE1-175 C
Solar/Wind Helper
0.057
316240AF1-291 C
Solar/Wind Helper
0.059
316248AF1-058 C
Solar/Wind Helper
0.327
316258AE1-075 C
Solar/Wind Helper
0.055
316316AC1-027 C
Solar/Wind Helper
0.053
316336AC2-165 C
Solar/Wind Helper
0.312
316382AG1-145 C
Solar/Wind Helper
0.057
316405AF2-144 C
Solar/Wind Helper
0.052
3145336SMITFLD
Solar/Wind Helper
0.738
3145336SMITFLD
Solar/Wind Helper
0.074
3147243WELCO
Solar/Wind Helper
0.636
316017AA1-139 ULT1
Solar/Wind Helper
0.169
316018AA1-139 ULT2
Solar/Wind Helper
0.016
316033AB2-134 GEN
Solar/Wind Helper
0.412
316388AE2-253 GEN
Solar/Wind Helper
0.142
3144303KENBRDG
Solar/Wind Helper
0.376
3147173SINAI
Solar/Wind Helper
1.018
316369SG1_INVT
Solar/Wind Helper
0.284
315839AE2-212 C
Solar/Wind Helper
0.061
315697AD1-025 GEN
Solar/Wind Helper
0.434
316185AD1-033 GEN
Solar/Wind Helper
0.208
316478AD1-087 GEN
Solar/Wind Helper
0.737
316486AD2-202 GEN
Solar/Wind Helper
0.216
315687AD1-152 GEN
Solar/Wind Helper
1.268
315785AD2-033 C
Solar/Wind Helper
0.995
316313AB2-026
Solar/Wind Helper
0.061
270030AE2-140 GEN
Solar/Wind Harmer
0.914
313527AB2-043 GEN
Solar/Wind Helper
0.404
316322AB2-045
Solar/Wind Helper
0.095
316359AB2-059 GEN
Solar/Wind Harmer
0
316131AB2-060 GEN
Solar/Wind Helper
0.644
316083AB2-161 GEN
Solar/Wind Helper
0.146
316132AB2-190 GEN1
Solar/Wind Helper
0.216
316458AB2-190 GEN2
Solar/Wind Helper
0.216
316123AC1-075 GEN
Solar/Wind Helper
0.801
316375AC2-012 GEN
Solar/Wind Helper
0.357
316339AD2-160 GEN
Solar/Wind Helper
0.142
316239AB2-077_GEN
Solar/Wind Helper
0.164
316238AB2-078_GEN
Solar/Wind Helper
0.164
316237AB2-079_GEN
Solar/Wind Helper
0.164
316381AD1-082 GEN
Solar/Wind Helper
0.199
316236AE1-162_GEN
Solar/Wind Helper
0.059
3145543BTLEBRO
Solar/Wind Harmer
-0.146
3145543BTLEBRO
Solar/Wind Harmer
-0.183
3145543BTLEBRO
Solar/Wind Harmer
-0.183
3145543BTLEBRO
Solar/Wind Harmer
-0.183
3138543CONSLDL
Solar/Wind Harmer
-0.098
3142053HEARTS
Solar/Wind Harmer
0.006
3144536CHRHLND
Solar/Wind Helper
0.028
3144873MCLAUGH
Solar/Wind Helper
0.005
3145453TOT5
Solar/Wind Harmer
0.004
3145493TOT1
Solar/Wind Harmer
0.014
3145493TOT1
Solar/Wind Harmer
0.007
3145573BETHELC
Solar/Wind Harmer
-0.161
3145573BETHELC
Solar/Wind Harmer
-0.161
3145603CNETO
Solar/Wind Harmer
0.003
3146073TAR RVR
Solar/Wind Harmer
-0.161
3146083TARBORO
Solar/Wind Harmer
-0.161
3146083TARBORO
Solar/Wind Harmer
-0.161
3146233WITAKRS
Solar/Wind Harmer
0.03
3146233WITAKRS
Solar/Wind Harmer
-0.575
3146233WITAKRS
Solar/Wind Harmer
-0.098
942461AE2-259 GEN
Solar/Wind Helper
0.651
943811AF1-049 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
0.329
961601AG1-000A GEN
Solar/Wind Harmer
5.263
961611AG1-000B GEN
Solar/Wind Helper
0.259
970085AG2-068 GEN
Solar/Wind Harmer
0.764
970087AG2-069 GEN
Solar/Wind Harmer
1.146
970223AG2-152 GEN
Solar/Wind Harmer
0.735
970581AG2-369 GEN
Solar/Wind Harmer
0.657
970917AG2-570 GEN
Solar/Wind Harmer
3.057
970919AG2-571 GEN
Solar/Wind Harmer
6.113
971367AH1-164 GEN
Solar/Wind Harmer
0.1
971629AH1-314 GEN
50/50
15.356
971981AH1-535 GEN
Solar/Wind Harmer
0.293
315773AC2-141 GEN
Solar/Wind Helper
0.792
316003AC1-222 GEN
Solar/Wind Helper
0.97
316118AC1-105 GEN
Solar/Wind Helper
0.747
316129AC1-054 GEN
Solar/Wind Helper
0.253
316222AC1-221 GEN
Solar/Wind Helper
2.596
316263AC1-034 GEN
Solar/Wind Harmer
0.241
316283AC2-100 C
Solar/Wind Helper
2.444
316294AC1-161 GEN
Solar/Wind Helper
0.792
900033ID_568986
External Queue
0.2332763522863388
NYPJM->LTFIMP_NY
CLTF
0.617
LGEELTFEXP_LGEE->PJM
CLTF
2.103
WECLTFEXP_WEC->PJM
CLTF
1.136
CPLELTFEXP_CPLE->PJM
CLTF
13.823
LAGNLTFEXP_LAGN->PJM
CLTF
10.439
CBM West 1LTFEXP_CBM-W1->PJM
CBM
42.454
CBM West 2LTFEXP_CBM-W2->PJM
CBM
57.31
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.037
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.468
TVALTFEXP_TVA->PJM
CLTF
5.181
MECLTFEXP_MEC->PJM
CLTF
5.746
SIGELTFEXP_SIGE->PJM
CLTF
0.173
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.095
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.495

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-3


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.4 %
Rating:652.36 MVA
Rating Type:B
MVA to Mitigate:889.84
MW Contribution:0.74
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Helper
0.151
3147133PAMPLIN
Solar/Wind Helper
1.348
3147133PAMPLIN
Solar/Wind Helper
0.343
3147133PAMPLIN
Solar/Wind Helper
0.429
3137176SLIGO L2192
Solar/Wind Helper
0.678
3142433PROV 92
Solar/Wind Helper
0.666
3143316POE
Solar/Wind Helper
0.777
3145506HICKORY
Solar/Wind Helper
0.717
3145506HICKORY
Solar/Wind Helper
0.43
3145506HICKORY
Solar/Wind Helper
0.108
3146776BUCKING
Solar/Wind Helper
1.185
3146776BUCKING
Solar/Wind Helper
0.096
3146776BUCKING
Solar/Wind Helper
0.107
3146776BUCKING
Solar/Wind Helper
0.119
316075AC2-137 C
Solar/Wind Helper
0.052
3138133OCRAN
Solar/Wind Helper
0.049
3138133OCRAN
Solar/Wind Helper
0.098
3141766HARMONY
Solar/Wind Helper
0.033
3141783LANCAST
Solar/Wind Helper
0.098
3141783LANCAST
Solar/Wind Helper
0.065
3141913WHIT STONE
Solar/Wind Helper
0.164
3143226MDLTHAN
Solar/Wind Helper
0.177
3143873LANEXA
Solar/Wind Helper
0.099
3146456SLIGO L269
Solar/Wind Helper
0.17
3146456SLIGO L269
Solar/Wind Helper
0.17
3146843MT LREL
Solar/Wind Helper
0.801
3146843MT LREL
Solar/Wind Helper
0.801
3146926FARMVIL
Solar/Wind Helper
0.223
3146926FARMVIL
Solar/Wind Helper
0.223
3147123OTTER R
Solar/Wind Helper
0.117
3141726DUNNSVL
Solar/Wind Helper
0.624
316034AC1-036 C
Solar/Wind Helper
0.104
316036AC1-147 C
Solar/Wind Helper
0.06
316059AD1-063 C
Solar/Wind Helper
0.04
316159AE1-175 C
Solar/Wind Helper
0.056
316240AF1-291 C
Solar/Wind Helper
0.058
316246AF1-032 C
Solar/Wind Helper
0.041
316248AF1-058 C
Solar/Wind Helper
0.326
316258AE1-075 C
Solar/Wind Helper
0.054
316305AF2-043 C
Solar/Wind Helper
0.054
316314AB2-024 C
Solar/Wind Helper
0.053
316315AB2-025 C
Solar/Wind Helper
0.055
316316AC1-027 C
Solar/Wind Helper
0.052
316336AC2-165 C
Solar/Wind Helper
0.307
316382AG1-145 C
Solar/Wind Helper
0.056
316405AF2-144 C
Solar/Wind Helper
0.051
3145336SMITFLD
Solar/Wind Helper
0.726
3145336SMITFLD
Solar/Wind Helper
0.073
3147243WELCO
Solar/Wind Helper
0.634
3141873WAN 176
Solar/Wind Helper
0.033
3143526WINTERP
Solar/Wind Helper
0.894
3143526WINTERP
Solar/Wind Helper
0.894
316404AE1-155 C
Solar/Wind Helper
0.323
316017AA1-139 ULT1
Solar/Wind Helper
0.166
316018AA1-139 ULT2
Solar/Wind Helper
0.166
316033AB2-134 GEN
Solar/Wind Helper
0.405
316388AE2-253 GEN
Solar/Wind Helper
0.14
3142543TWELFTH
Solar/Wind Helper
0.016
3144303KENBRDG
Solar/Wind Helper
0.374
3147173SINAI
Solar/Wind Helper
1.015
316203AE2-005 GEN
Solar/Wind Helper
0.345
316441AF1-014 GEN
Solar/Wind Helper
0.053
316484AD2-074 GEN
Solar/Wind Helper
0.221
315833AF1-017_GEN
Solar/Wind Helper
0.109
316369SG1_INVT
Solar/Wind Helper
0.279
316487AF1-042 GEN
Solar/Wind Helper
0.116
315839AE2-212 C
Solar/Wind Helper
0.06
315662AE1-191 GEN
Solar/Wind Helper
0.213
315666AE1-190 GEN
Solar/Wind Helper
0.053
319010AE1-072 C
Solar/Wind Helper
0.407
315697AD1-025 GEN
Solar/Wind Helper
0.427
316185AD1-033 GEN
Solar/Wind Helper
0.205
316280AD1-041 GEN
Solar/Wind Helper
0.133
316478AD1-087 GEN
Solar/Wind Helper
0.734
316486AD2-202 GEN
Solar/Wind Helper
0.215
316072AD1-144
Solar/Wind Helper
0.041
315687AD1-152 GEN
Solar/Wind Helper
1.264
316156AD2-030 GEN
Solar/Wind Helper
0.053
315785AD2-033 C
Solar/Wind Helper
0.988
316313AB2-026
Solar/Wind Helper
0.06
270030AE2-140 GEN
Solar/Wind Harmer
0.924
316349AD2-085 GEN
Solar/Wind Helper
0.139
313527AB2-043 GEN
Solar/Wind Helper
0.402
316322AB2-045
Solar/Wind Helper
0.094
316359AB2-059 GEN
Solar/Wind Harmer
0
316131AB2-060 GEN
Solar/Wind Helper
0.64
316083AB2-161 GEN
Solar/Wind Helper
0.144
316132AB2-190 GEN1
Solar/Wind Helper
0.212
316458AB2-190 GEN2
Solar/Wind Helper
0.212
316123AC1-075 GEN
Solar/Wind Helper
0.797
316375AC2-012 GEN
Solar/Wind Helper
0.351
316339AD2-160 GEN
Solar/Wind Helper
0.14
316239AB2-077_GEN
Solar/Wind Helper
0.163
316238AB2-078_GEN
Solar/Wind Helper
0.163
316237AB2-079_GEN
Solar/Wind Helper
0.163
316381AD1-082 GEN
Solar/Wind Helper
0.195
316233AE1-074 FULL
Solar/Wind Helper
0.055
316236AE1-162_GEN
Solar/Wind Helper
0.058
3145543BTLEBRO
Solar/Wind Harmer
-0.149
3145543BTLEBRO
Solar/Wind Harmer
-0.186
3145543BTLEBRO
Solar/Wind Harmer
-0.186
3145543BTLEBRO
Solar/Wind Harmer
-0.186
3130086AYDLETT
Solar/Wind Helper
0.672
3138543CONSLDL
Solar/Wind Harmer
-0.1
3142053HEARTS
Solar/Wind Harmer
0.006
3142946ENON
Solar/Wind Helper
0.017
3142946ENON
Solar/Wind Helper
0.056
3144536CHRHLND
Solar/Wind Helper
0.028
3144873MCLAUGH
Solar/Wind Helper
0.005
3145453TOT5
Solar/Wind Harmer
0.004
3145493TOT1
Solar/Wind Harmer
0.014
3145493TOT1
Solar/Wind Harmer
0.007
3145573BETHELC
Solar/Wind Harmer
-0.164
3145573BETHELC
Solar/Wind Harmer
-0.164
3145603CNETO
Solar/Wind Harmer
0.003
3146073TAR RVR
Solar/Wind Harmer
-0.164
3146083TARBORO
Solar/Wind Harmer
-0.164
3146083TARBORO
Solar/Wind Harmer
-0.164
3146233WITAKRS
Solar/Wind Harmer
0.031
3146233WITAKRS
Solar/Wind Harmer
-0.586
3146233WITAKRS
Solar/Wind Harmer
-0.1
942461AE2-259 GEN
Solar/Wind Helper
0.646
943811AF1-049 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
0.334
961601AG1-000A GEN
Solar/Wind Harmer
5.342
961611AG1-000B GEN
Solar/Wind Helper
0.254
961951AG1-038 GEN
Solar/Wind Helper
0.116
970085AG2-068 GEN
Solar/Wind Harmer
0.769
970087AG2-069 GEN
Solar/Wind Harmer
1.154
970223AG2-152 GEN
Solar/Wind Harmer
0.742
970417AG2-272 GEN
50/50
2.037
970581AG2-369 GEN
Solar/Wind Harmer
0.661
970917AG2-570 GEN
Solar/Wind Harmer
3.076
970919AG2-571 GEN
Solar/Wind Harmer
6.153
971367AH1-164 GEN
Solar/Wind Harmer
0.102
971629AH1-314 GEN
50/50
15.454
957601AF2-054 GEN
Solar/Wind Helper
0.053
957831AF2-077 GEN
Solar/Wind Helper
0.055
964211AG1-282 GEN
Solar/Wind Helper
0.05
971981AH1-535 GEN
Solar/Wind Harmer
0.298
315773AC2-141 GEN
Solar/Wind Helper
0.78
316003AC1-222 GEN
Solar/Wind Helper
0.967
316118AC1-105 GEN
Solar/Wind Helper
0.744
316129AC1-054 GEN
Solar/Wind Helper
0.25
316222AC1-221 GEN
Solar/Wind Helper
2.592
316263AC1-034 GEN
Solar/Wind Harmer
0.245
316283AC2-100 C
Solar/Wind Helper
2.441
316294AC1-161 GEN
Solar/Wind Helper
0.78
944201AF1-088_MTX
Adder
35.265
900033ID_568986
External Queue
0.2332763522863388
NYPJM->LTFIMP_NY
CLTF
0.562
LGEELTFEXP_LGEE->PJM
CLTF
2.162
WECLTFEXP_WEC->PJM
CLTF
1.169
CPLELTFEXP_CPLE->PJM
CLTF
13.916
LAGNLTFEXP_LAGN->PJM
CLTF
10.611
CBM West 1LTFEXP_CBM-W1->PJM
CBM
43.691
CBM West 2LTFEXP_CBM-W2->PJM
CBM
58.452
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.359
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.725
TVALTFEXP_TVA->PJM
CLTF
5.267
MECLTFEXP_MEC->PJM
CLTF
5.888
SIGELTFEXP_SIGE->PJM
CLTF
0.177
AG2-052LTFEXP_AG2-052->PJM
LTF
0.066
AH1-155LTFEXP_AH1-155->PJM
LTF
0.098
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.495

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-2


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:134.99 %
Rating:652.36 MVA
Rating Type:B
MVA to Mitigate:880.62
MW Contribution:0.74
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Helper
0.151
3147133PAMPLIN
Solar/Wind Helper
1.348
3147133PAMPLIN
Solar/Wind Helper
0.343
3147133PAMPLIN
Solar/Wind Helper
0.429
3137176SLIGO L2192
Solar/Wind Helper
0.678
3142433PROV 92
Solar/Wind Helper
0.666
3143316POE
Solar/Wind Helper
0.777
3145506HICKORY
Solar/Wind Helper
0.717
3145506HICKORY
Solar/Wind Helper
0.43
3145506HICKORY
Solar/Wind Helper
0.108
3146776BUCKING
Solar/Wind Helper
1.185
3146776BUCKING
Solar/Wind Helper
0.096
3146776BUCKING
Solar/Wind Helper
0.107
3146776BUCKING
Solar/Wind Helper
0.119
316075AC2-137 C
Solar/Wind Helper
0.052
3138133OCRAN
Solar/Wind Helper
0.049
3138133OCRAN
Solar/Wind Helper
0.098
3141766HARMONY
Solar/Wind Helper
0.033
3141783LANCAST
Solar/Wind Helper
0.098
3141783LANCAST
Solar/Wind Helper
0.065
3141913WHIT STONE
Solar/Wind Helper
0.164
3143226MDLTHAN
Solar/Wind Helper
0.177
3143873LANEXA
Solar/Wind Helper
0.099
3146456SLIGO L269
Solar/Wind Helper
0.17
3146456SLIGO L269
Solar/Wind Helper
0.17
3146843MT LREL
Solar/Wind Helper
0.801
3146843MT LREL
Solar/Wind Helper
0.801
3146926FARMVIL
Solar/Wind Helper
0.223
3146926FARMVIL
Solar/Wind Helper
0.223
3147123OTTER R
Solar/Wind Helper
0.117
3141726DUNNSVL
Solar/Wind Helper
0.624
316034AC1-036 C
Solar/Wind Helper
0.104
316036AC1-147 C
Solar/Wind Helper
0.06
316059AD1-063 C
Solar/Wind Helper
0.04
316159AE1-175 C
Solar/Wind Helper
0.056
316240AF1-291 C
Solar/Wind Helper
0.058
316246AF1-032 C
Solar/Wind Helper
0.041
316248AF1-058 C
Solar/Wind Helper
0.326
316258AE1-075 C
Solar/Wind Helper
0.054
316305AF2-043 C
Solar/Wind Helper
0.054
316314AB2-024 C
Solar/Wind Helper
0.053
316315AB2-025 C
Solar/Wind Helper
0.055
316316AC1-027 C
Solar/Wind Helper
0.052
316336AC2-165 C
Solar/Wind Helper
0.307
316382AG1-145 C
Solar/Wind Helper
0.056
316405AF2-144 C
Solar/Wind Helper
0.051
3145336SMITFLD
Solar/Wind Helper
0.726
3145336SMITFLD
Solar/Wind Helper
0.073
3147243WELCO
Solar/Wind Helper
0.634
3141873WAN 176
Solar/Wind Helper
0.033
3143526WINTERP
Solar/Wind Helper
0.894
3143526WINTERP
Solar/Wind Helper
0.894
316404AE1-155 C
Solar/Wind Helper
0.323
316017AA1-139 ULT1
Solar/Wind Helper
0.166
316018AA1-139 ULT2
Solar/Wind Helper
0.166
316033AB2-134 GEN
Solar/Wind Helper
0.405
316388AE2-253 GEN
Solar/Wind Helper
0.14
3142543TWELFTH
Solar/Wind Helper
0.016
3144303KENBRDG
Solar/Wind Helper
0.374
3147173SINAI
Solar/Wind Helper
1.015
316203AE2-005 GEN
Solar/Wind Helper
0.345
316441AF1-014 GEN
Solar/Wind Helper
0.053
316484AD2-074 GEN
Solar/Wind Helper
0.221
315833AF1-017_GEN
Solar/Wind Helper
0.109
316369SG1_INVT
Solar/Wind Helper
0.279
316487AF1-042 GEN
Solar/Wind Helper
0.116
315839AE2-212 C
Solar/Wind Helper
0.06
315662AE1-191 GEN
Solar/Wind Helper
0.213
315666AE1-190 GEN
Solar/Wind Helper
0.053
319010AE1-072 C
Solar/Wind Helper
0.407
315697AD1-025 GEN
Solar/Wind Helper
0.427
316185AD1-033 GEN
Solar/Wind Helper
0.205
316280AD1-041 GEN
Solar/Wind Helper
0.133
316478AD1-087 GEN
Solar/Wind Helper
0.734
316486AD2-202 GEN
Solar/Wind Helper
0.215
316072AD1-144
Solar/Wind Helper
0.041
315687AD1-152 GEN
Solar/Wind Helper
1.264
316156AD2-030 GEN
Solar/Wind Helper
0.053
315785AD2-033 C
Solar/Wind Helper
0.988
316313AB2-026
Solar/Wind Helper
0.06
270030AE2-140 GEN
Solar/Wind Harmer
0.924
316349AD2-085 GEN
Solar/Wind Helper
0.139
313527AB2-043 GEN
Solar/Wind Helper
0.402
316322AB2-045
Solar/Wind Helper
0.094
316359AB2-059 GEN
Solar/Wind Harmer
0
316131AB2-060 GEN
Solar/Wind Helper
0.64
316083AB2-161 GEN
Solar/Wind Helper
0.144
316132AB2-190 GEN1
Solar/Wind Helper
0.212
316458AB2-190 GEN2
Solar/Wind Helper
0.212
316123AC1-075 GEN
Solar/Wind Helper
0.797
316375AC2-012 GEN
Solar/Wind Helper
0.351
316339AD2-160 GEN
Solar/Wind Helper
0.14
316239AB2-077_GEN
Solar/Wind Helper
0.163
316238AB2-078_GEN
Solar/Wind Helper
0.163
316237AB2-079_GEN
Solar/Wind Helper
0.163
316381AD1-082 GEN
Solar/Wind Helper
0.195
316233AE1-074 FULL
Solar/Wind Helper
0.055
316236AE1-162_GEN
Solar/Wind Helper
0.058
3145543BTLEBRO
Solar/Wind Harmer
-0.149
3145543BTLEBRO
Solar/Wind Harmer
-0.186
3145543BTLEBRO
Solar/Wind Harmer
-0.186
3145543BTLEBRO
Solar/Wind Harmer
-0.186
3130086AYDLETT
Solar/Wind Helper
0.672
3138543CONSLDL
Solar/Wind Harmer
-0.1
3142053HEARTS
Solar/Wind Harmer
0.006
3142946ENON
Solar/Wind Helper
0.017
3142946ENON
Solar/Wind Helper
0.056
3144536CHRHLND
Solar/Wind Helper
0.028
3144873MCLAUGH
Solar/Wind Helper
0.005
3145453TOT5
Solar/Wind Harmer
0.004
3145493TOT1
Solar/Wind Harmer
0.014
3145493TOT1
Solar/Wind Harmer
0.007
3145573BETHELC
Solar/Wind Harmer
-0.164
3145573BETHELC
Solar/Wind Harmer
-0.164
3145603CNETO
Solar/Wind Harmer
0.003
3146073TAR RVR
Solar/Wind Harmer
-0.164
3146083TARBORO
Solar/Wind Harmer
-0.164
3146083TARBORO
Solar/Wind Harmer
-0.164
3146233WITAKRS
Solar/Wind Harmer
0.031
3146233WITAKRS
Solar/Wind Harmer
-0.586
3146233WITAKRS
Solar/Wind Harmer
-0.1
942461AE2-259 GEN
Solar/Wind Helper
0.646
943811AF1-049 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
0.334
961601AG1-000A GEN
Solar/Wind Harmer
5.342
961611AG1-000B GEN
Solar/Wind Helper
0.254
961951AG1-038 GEN
Solar/Wind Helper
0.116
970085AG2-068 GEN
Solar/Wind Harmer
0.769
970087AG2-069 GEN
Solar/Wind Harmer
1.154
970223AG2-152 GEN
Solar/Wind Harmer
0.742
970417AG2-272 GEN
50/50
2.037
970581AG2-369 GEN
Solar/Wind Harmer
0.661
971367AH1-164 GEN
Solar/Wind Harmer
0.102
971629AH1-314 GEN
50/50
15.454
957601AF2-054 GEN
Solar/Wind Helper
0.053
957831AF2-077 GEN
Solar/Wind Helper
0.055
964211AG1-282 GEN
Solar/Wind Helper
0.05
971981AH1-535 GEN
Solar/Wind Harmer
0.298
315773AC2-141 GEN
Solar/Wind Helper
0.78
316003AC1-222 GEN
Solar/Wind Helper
0.967
316118AC1-105 GEN
Solar/Wind Helper
0.744
316129AC1-054 GEN
Solar/Wind Helper
0.25
316222AC1-221 GEN
Solar/Wind Helper
2.592
316263AC1-034 GEN
Solar/Wind Harmer
0.245
316283AC2-100 C
Solar/Wind Helper
2.441
316294AC1-161 GEN
Solar/Wind Helper
0.78
944201AF1-088_MTX
Adder
35.265
900033ID_568986
External Queue
0.2332763522863388
NYPJM->LTFIMP_NY
CLTF
0.562
LGEELTFEXP_LGEE->PJM
CLTF
2.162
WECLTFEXP_WEC->PJM
CLTF
1.169
CPLELTFEXP_CPLE->PJM
CLTF
13.916
LAGNLTFEXP_LAGN->PJM
CLTF
10.611
CBM West 1LTFEXP_CBM-W1->PJM
CBM
43.691
CBM West 2LTFEXP_CBM-W2->PJM
CBM
58.452
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.359
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.725
TVALTFEXP_TVA->PJM
CLTF
5.267
MECLTFEXP_MEC->PJM
CLTF
5.888
SIGELTFEXP_SIGE->PJM
CLTF
0.177
AG2-052LTFEXP_AG2-052->PJM
LTF
0.066
AH1-155LTFEXP_AH1-155->PJM
LTF
0.098
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.495

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57062_SRT-W


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57062_SRT-W
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.48 %
Rating:694.0 MVA
Rating Type:B
MVA to Mitigate:905.5
MW Contribution:0.74
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Helper
0.151
3147133PAMPLIN
Solar/Wind Helper
1.348
3147133PAMPLIN
Solar/Wind Helper
0.343
3147133PAMPLIN
Solar/Wind Helper
0.429
3137176SLIGO L2192
Solar/Wind Helper
0.678
3142433PROV 92
Solar/Wind Helper
0.666
3143316POE
Solar/Wind Helper
0.777
3145506HICKORY
Solar/Wind Helper
0.717
3145506HICKORY
Solar/Wind Helper
0.43
3145506HICKORY
Solar/Wind Helper
0.108
3146776BUCKING
Solar/Wind Helper
1.185
3146776BUCKING
Solar/Wind Helper
0.096
3146776BUCKING
Solar/Wind Helper
0.107
3146776BUCKING
Solar/Wind Helper
0.119
316075AC2-137 C
Solar/Wind Helper
0.052
3138133OCRAN
Solar/Wind Helper
0.049
3138133OCRAN
Solar/Wind Helper
0.098
3141766HARMONY
Solar/Wind Helper
0.033
3141783LANCAST
Solar/Wind Helper
0.098
3141783LANCAST
Solar/Wind Helper
0.065
3141913WHIT STONE
Solar/Wind Helper
0.164
3143226MDLTHAN
Solar/Wind Helper
0.177
3143873LANEXA
Solar/Wind Helper
0.099
3146456SLIGO L269
Solar/Wind Helper
0.17
3146456SLIGO L269
Solar/Wind Helper
0.17
3146843MT LREL
Solar/Wind Helper
0.801
3146843MT LREL
Solar/Wind Helper
0.801
3146926FARMVIL
Solar/Wind Helper
0.223
3146926FARMVIL
Solar/Wind Helper
0.223
3147123OTTER R
Solar/Wind Helper
0.117
3141726DUNNSVL
Solar/Wind Helper
0.624
316034AC1-036 C
Solar/Wind Helper
0.104
316036AC1-147 C
Solar/Wind Helper
0.06
316059AD1-063 C
Solar/Wind Helper
0.04
316159AE1-175 C
Solar/Wind Helper
0.056
316240AF1-291 C
Solar/Wind Helper
0.058
316246AF1-032 C
Solar/Wind Helper
0.041
316248AF1-058 C
Solar/Wind Helper
0.326
316258AE1-075 C
Solar/Wind Helper
0.054
316305AF2-043 C
Solar/Wind Helper
0.054
316314AB2-024 C
Solar/Wind Helper
0.053
316315AB2-025 C
Solar/Wind Helper
0.055
316316AC1-027 C
Solar/Wind Helper
0.052
316336AC2-165 C
Solar/Wind Helper
0.307
316382AG1-145 C
Solar/Wind Helper
0.056
316405AF2-144 C
Solar/Wind Helper
0.051
3145336SMITFLD
Solar/Wind Helper
0.726
3145336SMITFLD
Solar/Wind Helper
0.073
3147243WELCO
Solar/Wind Helper
0.634
3141873WAN 176
Solar/Wind Helper
0.033
3143526WINTERP
Solar/Wind Helper
0.894
3143526WINTERP
Solar/Wind Helper
0.894
316404AE1-155 C
Solar/Wind Helper
0.323
316017AA1-139 ULT1
Solar/Wind Helper
0.166
316018AA1-139 ULT2
Solar/Wind Helper
0.166
316033AB2-134 GEN
Solar/Wind Helper
0.405
316388AE2-253 GEN
Solar/Wind Helper
0.14
3142543TWELFTH
Solar/Wind Helper
0.016
3144303KENBRDG
Solar/Wind Helper
0.374
3147173SINAI
Solar/Wind Helper
1.015
316203AE2-005 GEN
Solar/Wind Helper
0.345
316441AF1-014 GEN
Solar/Wind Helper
0.053
316484AD2-074 GEN
Solar/Wind Helper
0.221
315833AF1-017_GEN
Solar/Wind Helper
0.109
316369SG1_INVT
Solar/Wind Helper
0.279
316487AF1-042 GEN
Solar/Wind Helper
0.116
315839AE2-212 C
Solar/Wind Helper
0.06
315662AE1-191 GEN
Solar/Wind Helper
0.213
315666AE1-190 GEN
Solar/Wind Helper
0.053
319010AE1-072 C
Solar/Wind Helper
0.407
315697AD1-025 GEN
Solar/Wind Helper
0.427
316185AD1-033 GEN
Solar/Wind Helper
0.205
316280AD1-041 GEN
Solar/Wind Helper
0.133
316478AD1-087 GEN
Solar/Wind Helper
0.734
316486AD2-202 GEN
Solar/Wind Helper
0.215
316072AD1-144
Solar/Wind Helper
0.041
315687AD1-152 GEN
Solar/Wind Helper
1.264
316156AD2-030 GEN
Solar/Wind Helper
0.053
315785AD2-033 C
Solar/Wind Helper
0.988
316313AB2-026
Solar/Wind Helper
0.06
270030AE2-140 GEN
Solar/Wind Harmer
0.924
316349AD2-085 GEN
Solar/Wind Helper
0.139
313527AB2-043 GEN
Solar/Wind Helper
0.402
316322AB2-045
Solar/Wind Helper
0.094
316359AB2-059 GEN
Solar/Wind Harmer
0
316131AB2-060 GEN
Solar/Wind Helper
0.64
316083AB2-161 GEN
Solar/Wind Helper
0.144
316132AB2-190 GEN1
Solar/Wind Helper
0.212
316458AB2-190 GEN2
Solar/Wind Helper
0.212
316123AC1-075 GEN
Solar/Wind Helper
0.797
316375AC2-012 GEN
Solar/Wind Helper
0.351
316339AD2-160 GEN
Solar/Wind Helper
0.14
316239AB2-077_GEN
Solar/Wind Helper
0.163
316238AB2-078_GEN
Solar/Wind Helper
0.163
316237AB2-079_GEN
Solar/Wind Helper
0.163
316381AD1-082 GEN
Solar/Wind Helper
0.195
316233AE1-074 FULL
Solar/Wind Helper
0.055
316236AE1-162_GEN
Solar/Wind Helper
0.058
3145543BTLEBRO
Solar/Wind Harmer
-0.149
3145543BTLEBRO
Solar/Wind Harmer
-0.186
3145543BTLEBRO
Solar/Wind Harmer
-0.186
3145543BTLEBRO
Solar/Wind Harmer
-0.186
3130086AYDLETT
Solar/Wind Helper
0.672
3138543CONSLDL
Solar/Wind Harmer
-0.1
3142053HEARTS
Solar/Wind Harmer
0.006
3142946ENON
Solar/Wind Helper
0.017
3142946ENON
Solar/Wind Helper
0.056
3144536CHRHLND
Solar/Wind Helper
0.028
3144873MCLAUGH
Solar/Wind Helper
0.005
3145453TOT5
Solar/Wind Harmer
0.004
3145493TOT1
Solar/Wind Harmer
0.014
3145493TOT1
Solar/Wind Harmer
0.007
3145573BETHELC
Solar/Wind Harmer
-0.164
3145573BETHELC
Solar/Wind Harmer
-0.164
3145603CNETO
Solar/Wind Harmer
0.003
3146073TAR RVR
Solar/Wind Harmer
-0.164
3146083TARBORO
Solar/Wind Harmer
-0.164
3146083TARBORO
Solar/Wind Harmer
-0.164
3146233WITAKRS
Solar/Wind Harmer
0.031
3146233WITAKRS
Solar/Wind Harmer
-0.586
3146233WITAKRS
Solar/Wind Harmer
-0.1
942461AE2-259 GEN
Solar/Wind Helper
0.646
943811AF1-049 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
0.334
961601AG1-000A GEN
Solar/Wind Harmer
5.342
961611AG1-000B GEN
Solar/Wind Helper
0.254
961951AG1-038 GEN
Solar/Wind Helper
0.116
970085AG2-068 GEN
Solar/Wind Harmer
0.769
970087AG2-069 GEN
Solar/Wind Harmer
1.154
970223AG2-152 GEN
Solar/Wind Harmer
0.742
970581AG2-369 GEN
Solar/Wind Harmer
0.661
970917AG2-570 GEN
Solar/Wind Harmer
3.076
970919AG2-571 GEN
Solar/Wind Harmer
6.153
971367AH1-164 GEN
Solar/Wind Harmer
0.102
971629AH1-314 GEN
50/50
15.454
957601AF2-054 GEN
Solar/Wind Helper
0.053
957831AF2-077 GEN
Solar/Wind Helper
0.055
964211AG1-282 GEN
Solar/Wind Helper
0.05
971981AH1-535 GEN
Solar/Wind Harmer
0.298
315773AC2-141 GEN
Solar/Wind Helper
0.78
316003AC1-222 GEN
Solar/Wind Helper
0.967
316118AC1-105 GEN
Solar/Wind Helper
0.744
316129AC1-054 GEN
Solar/Wind Helper
0.25
316222AC1-221 GEN
Solar/Wind Helper
2.592
316263AC1-034 GEN
Solar/Wind Harmer
0.245
316283AC2-100 C
Solar/Wind Helper
2.441
316294AC1-161 GEN
Solar/Wind Helper
0.78
944201AF1-088_MTX
Adder
35.265
957141AF2-008_MTX
Adder
17.632
900033ID_568986
External Queue
0.2332763522863388
NYPJM->LTFIMP_NY
CLTF
0.562
LGEELTFEXP_LGEE->PJM
CLTF
2.162
WECLTFEXP_WEC->PJM
CLTF
1.169
CPLELTFEXP_CPLE->PJM
CLTF
13.916
LAGNLTFEXP_LAGN->PJM
CLTF
10.611
CBM West 1LTFEXP_CBM-W1->PJM
CBM
43.691
CBM West 2LTFEXP_CBM-W2->PJM
CBM
58.452
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.359
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.725
TVALTFEXP_TVA->PJM
CLTF
5.267
MECLTFEXP_MEC->PJM
CLTF
5.888
SIGELTFEXP_SIGE->PJM
CLTF
0.177
AG2-052LTFEXP_AG2-052->PJM
LTF
0.066
AH1-155LTFEXP_AH1-155->PJM
LTF
0.098
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.495

Details for [AG2-152] 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 509T570_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.4 %
Rating:694.0 MVA
Rating Type:B
MVA to Mitigate:745.32
MW Contribution:14.7
IPD Plant:AG2-152
Bus #Bus NameTypeMW Contribution
970223AG2-152 GEN
PJM_IPD
14.702

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 59162_SRT-W


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 59162_SRT-W
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.06 %
Rating:694.0 MVA
Rating Type:B
MVA to Mitigate:722.2
MW Contribution:0.56
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Helper
0.152
3147133PAMPLIN
Solar/Wind Helper
1.339
3147133PAMPLIN
Solar/Wind Helper
0.341
3147133PAMPLIN
Solar/Wind Helper
0.426
3146776BUCKING
Solar/Wind Helper
1.102
3146776BUCKING
Solar/Wind Helper
0.089
3146776BUCKING
Solar/Wind Helper
0.099
3146776BUCKING
Solar/Wind Helper
0.11
3146843MT LREL
Solar/Wind Helper
0.832
3146843MT LREL
Solar/Wind Helper
0.832
3146926FARMVIL
Solar/Wind Helper
0.212
3146926FARMVIL
Solar/Wind Helper
0.212
3147123OTTER R
Solar/Wind Helper
0.144
3147312GRETNA
Solar/Wind Helper
0.032
3147312GRETNA
Solar/Wind Helper
0.128
316034AC1-036 C
Solar/Wind Helper
0.105
316248AF1-058 C
Solar/Wind Helper
0.34
3146802CHATHAM
Solar/Wind Helper
0.12
3147243WELCO
Solar/Wind Helper
0.66
3144303KENBRDG
Solar/Wind Helper
0.379
3147173SINAI
Solar/Wind Helper
1.057
316478AD1-087 GEN
Solar/Wind Helper
0.73
316486AD2-202 GEN
Solar/Wind Helper
0.214
315687AD1-152 GEN
Solar/Wind Helper
1.291
315785AD2-033 C
Solar/Wind Helper
1.005
270030AE2-140 GEN
Solar/Wind Harmer
0.691
313527AB2-043 GEN
Solar/Wind Helper
0.414
316322AB2-045
Solar/Wind Helper
0.088
316131AB2-060 GEN
Solar/Wind Helper
0.659
316123AC1-075 GEN
Solar/Wind Helper
0.852
316239AB2-077_GEN
Solar/Wind Helper
0.168
316238AB2-078_GEN
Solar/Wind Helper
0.168
316237AB2-079_GEN
Solar/Wind Helper
0.168
316197AC1-042 GEN
Solar/Wind Helper
0.108
942461AE2-259 GEN
Solar/Wind Helper
0.63
943811AF1-049 GEN
Solar/Wind Harmer
0
970223AG2-152 GEN
Solar/Wind Harmer
0.558
971629AH1-314 GEN
50/50
12.109
316003AC1-222 GEN
Solar/Wind Helper
1.011
316118AC1-105 GEN
Solar/Wind Helper
0.774
316129AC1-054 GEN
Solar/Wind Helper
0.271
316217AC1-145 GEN
Solar/Wind Helper
0.129
316222AC1-221 GEN
Solar/Wind Helper
2.726
316283AC2-100 C
Solar/Wind Helper
2.567
900033ID_568986
External Queue
0.2580420970916748
NYPJM->LTFIMP_NY
CLTF
0.381
LGEELTFEXP_LGEE->PJM
CLTF
1.396
WECLTFEXP_WEC->PJM
CLTF
0.754
CPLELTFEXP_CPLE->PJM
CLTF
9.444
LAGNLTFEXP_LAGN->PJM
CLTF
6.871
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.178
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.819
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.897
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.425
TVALTFEXP_TVA->PJM
CLTF
3.415
MECLTFEXP_MEC->PJM
CLTF
3.804
SIGELTFEXP_SIGE->PJM
CLTF
0.115
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.926

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: XT591_SRT-W


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: XT591_SRT-W
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.06 %
Rating:694.0 MVA
Rating Type:B
MVA to Mitigate:722.2
MW Contribution:0.56
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Helper
0.152
3147133PAMPLIN
Solar/Wind Helper
1.339
3147133PAMPLIN
Solar/Wind Helper
0.341
3147133PAMPLIN
Solar/Wind Helper
0.426
3146776BUCKING
Solar/Wind Helper
1.102
3146776BUCKING
Solar/Wind Helper
0.089
3146776BUCKING
Solar/Wind Helper
0.099
3146776BUCKING
Solar/Wind Helper
0.11
3146843MT LREL
Solar/Wind Helper
0.832
3146843MT LREL
Solar/Wind Helper
0.832
3146926FARMVIL
Solar/Wind Helper
0.212
3146926FARMVIL
Solar/Wind Helper
0.212
3147123OTTER R
Solar/Wind Helper
0.144
3147312GRETNA
Solar/Wind Helper
0.032
3147312GRETNA
Solar/Wind Helper
0.128
316034AC1-036 C
Solar/Wind Helper
0.105
316248AF1-058 C
Solar/Wind Helper
0.34
3146802CHATHAM
Solar/Wind Helper
0.12
3147243WELCO
Solar/Wind Helper
0.66
3144303KENBRDG
Solar/Wind Helper
0.379
3147173SINAI
Solar/Wind Helper
1.057
316478AD1-087 GEN
Solar/Wind Helper
0.73
316486AD2-202 GEN
Solar/Wind Helper
0.214
315687AD1-152 GEN
Solar/Wind Helper
1.291
315785AD2-033 C
Solar/Wind Helper
1.005
270030AE2-140 GEN
Solar/Wind Harmer
0.691
313527AB2-043 GEN
Solar/Wind Helper
0.414
316322AB2-045
Solar/Wind Helper
0.088
316131AB2-060 GEN
Solar/Wind Helper
0.659
316123AC1-075 GEN
Solar/Wind Helper
0.852
316239AB2-077_GEN
Solar/Wind Helper
0.168
316238AB2-078_GEN
Solar/Wind Helper
0.168
316237AB2-079_GEN
Solar/Wind Helper
0.168
316197AC1-042 GEN
Solar/Wind Helper
0.108
942461AE2-259 GEN
Solar/Wind Helper
0.63
943811AF1-049 GEN
Solar/Wind Harmer
0
970223AG2-152 GEN
Solar/Wind Harmer
0.558
971629AH1-314 GEN
50/50
12.109
316003AC1-222 GEN
Solar/Wind Helper
1.011
316118AC1-105 GEN
Solar/Wind Helper
0.774
316129AC1-054 GEN
Solar/Wind Helper
0.271
316217AC1-145 GEN
Solar/Wind Helper
0.129
316222AC1-221 GEN
Solar/Wind Helper
2.726
316283AC2-100 C
Solar/Wind Helper
2.567
900033ID_568986
External Queue
0.2580420970916748
NYPJM->LTFIMP_NY
CLTF
0.381
LGEELTFEXP_LGEE->PJM
CLTF
1.396
WECLTFEXP_WEC->PJM
CLTF
0.754
CPLELTFEXP_CPLE->PJM
CLTF
9.444
LAGNLTFEXP_LAGN->PJM
CLTF
6.871
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.178
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.819
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.897
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.425
TVALTFEXP_TVA->PJM
CLTF
3.415
MECLTFEXP_MEC->PJM
CLTF
3.804
SIGELTFEXP_SIGE->PJM
CLTF
0.115
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.926

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 59192-1_SRT-W


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 59192-1_SRT-W
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.05 %
Rating:694.0 MVA
Rating Type:B
MVA to Mitigate:722.14
MW Contribution:0.56
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Helper
0.152
3147133PAMPLIN
Solar/Wind Helper
1.339
3147133PAMPLIN
Solar/Wind Helper
0.341
3147133PAMPLIN
Solar/Wind Helper
0.426
3146776BUCKING
Solar/Wind Helper
1.102
3146776BUCKING
Solar/Wind Helper
0.089
3146776BUCKING
Solar/Wind Helper
0.099
3146776BUCKING
Solar/Wind Helper
0.11
3146843MT LREL
Solar/Wind Helper
0.832
3146843MT LREL
Solar/Wind Helper
0.832
3146926FARMVIL
Solar/Wind Helper
0.212
3146926FARMVIL
Solar/Wind Helper
0.212
3147123OTTER R
Solar/Wind Helper
0.144
3147312GRETNA
Solar/Wind Helper
0.032
3147312GRETNA
Solar/Wind Helper
0.128
316034AC1-036 C
Solar/Wind Helper
0.105
316248AF1-058 C
Solar/Wind Helper
0.34
3146802CHATHAM
Solar/Wind Helper
0.12
3147243WELCO
Solar/Wind Helper
0.66
3144303KENBRDG
Solar/Wind Helper
0.379
3147173SINAI
Solar/Wind Helper
1.057
316478AD1-087 GEN
Solar/Wind Helper
0.73
316486AD2-202 GEN
Solar/Wind Helper
0.214
315687AD1-152 GEN
Solar/Wind Helper
1.291
315785AD2-033 C
Solar/Wind Helper
1.005
270030AE2-140 GEN
Solar/Wind Harmer
0.691
313527AB2-043 GEN
Solar/Wind Helper
0.414
316322AB2-045
Solar/Wind Helper
0.088
316131AB2-060 GEN
Solar/Wind Helper
0.659
316123AC1-075 GEN
Solar/Wind Helper
0.852
316239AB2-077_GEN
Solar/Wind Helper
0.168
316238AB2-078_GEN
Solar/Wind Helper
0.168
316237AB2-079_GEN
Solar/Wind Helper
0.168
316197AC1-042 GEN
Solar/Wind Helper
0.108
942461AE2-259 GEN
Solar/Wind Helper
0.63
943811AF1-049 GEN
Solar/Wind Harmer
0
970223AG2-152 GEN
Solar/Wind Harmer
0.558
971629AH1-314 GEN
50/50
12.109
316003AC1-222 GEN
Solar/Wind Helper
1.011
316118AC1-105 GEN
Solar/Wind Helper
0.774
316129AC1-054 GEN
Solar/Wind Helper
0.271
316217AC1-145 GEN
Solar/Wind Helper
0.129
316222AC1-221 GEN
Solar/Wind Helper
2.726
316283AC2-100 C
Solar/Wind Helper
2.567
900033ID_568986
External Queue
0.2580420970916748
NYPJM->LTFIMP_NY
CLTF
0.381
LGEELTFEXP_LGEE->PJM
CLTF
1.396
WECLTFEXP_WEC->PJM
CLTF
0.754
CPLELTFEXP_CPLE->PJM
CLTF
9.444
LAGNLTFEXP_LAGN->PJM
CLTF
6.871
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.178
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.819
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.897
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.425
TVALTFEXP_TVA->PJM
CLTF
3.415
MECLTFEXP_MEC->PJM
CLTF
3.804
SIGELTFEXP_SIGE->PJM
CLTF
0.115
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.926
CONTINGENCY 'AEP_P1-2_#3174_6_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 290614 CKT Z1   /*05CLOVRD     765.0 - 05CLOVRD_RJO 765.0
 OPEN BRANCH FROM BUS 242515 TO BUS 290614 CKT 1    /*05JOSHUA     765.0 - 05CLOVRD_RJO 765.0
END
CONTINGENCY 'AEP_P1-3_#1372_05JOSHUA 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242515 TO BUS 247669 CKT 1   /*05JOSHUA     765.0 - 05JOSHUA 1EQ   1.0
 OPEN BRANCH FROM BUS 242688 TO BUS 247670 CKT 1   /*05JOSHUA     138.0 - 05JOSHUA_XFL 138.0
 OPEN BRANCH FROM BUS 247669 TO BUS 247670 CKT 1   /*05JOSHUA 1EQ   1.0 - 05JOSHUA_XFL 138.0
END
CONTINGENCY 'DVP_P4-2: 509T570_SRT-A'
 OPEN BRANCH FROM BUS 314935 TO BUS 314945 CKT 1   /*8HERITAGE    500.0 - 8BRUNSWICK   500.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315102 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG1  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315103 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG2  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315104 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG3  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315105 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKS1  19.0
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 OPEN BUS 314945                                   /*8BRUNSWICK   500.0
 OPEN BUS 315102                                   /*1BRUNSWICKG1  21.0
 OPEN BUS 315103                                   /*1BRUNSWICKG2  21.0
 OPEN BUS 315104                                   /*1BRUNSWICKG3  21.0
 OPEN BUS 315105                                   /*1BRUNSWICKS1  19.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-3'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-2'
 OPEN BRANCH FROM BUS 970916 TO BUS 970084 CKT 1   /*AG2-570 TP   500.0 - AG2-068 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 57062_SRT-W'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1                /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 SET POSTCONTRATING 4018 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET POSTCONTRATING 4538 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3984 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET PRECONTRATING 4261 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 59162_SRT-W'
 OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1                /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 4018 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET POSTCONTRATING 4538 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3984 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET PRECONTRATING 4261 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: XT591_SRT-W'
 OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1                /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 4018 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET POSTCONTRATING 4018 BRANCH FROM BUS 970916 TO BUS 314935 CKT 1 /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 SET POSTCONTRATING 4538 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3984 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET PRECONTRATING 3984 BRANCH FROM BUS 970916 TO BUS 314935 CKT 1 /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 SET PRECONTRATING 4261 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 59192-1_SRT-W'
 OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1                /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 OPEN BUS 314920                                                /*8RAWLIN_STC1 500.0
 SET POSTCONTRATING 4538 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 4261 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
END
242701 to 314667 ckt 1
304070 to 316281 ckt 1

Light Load Analysis

The New Service Request AG2-152 was evaluated as a 131.0 MW injection

AG2-152 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 131.0 MW (131.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
AEP_P1-2_#311_5_SRT-A
SingleAC125.64 %296.0B371.924.01
GD2AEP
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
AEP_P4_#7587_05J.FERR 765_B_SRT-A
BreakerAC123.54 %296.0B365.6924.0
GD2AEP
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
AEP_P4_#2914_05J.FERR 765_B2_SRT-A
BreakerAC123.21 %296.0B364.7124.01
GD2AEP
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
AEP_P7-1_#10781___SRT-A-3
TowerAC103.45 %296.0B306.234.32
IPDAEP
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
AEP_P4_#7587_05J.FERR 765_B_SRT-A
BreakerAC103.11 %296.0B305.243.64
IPDAEP
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
AEP_P4_#2914_05J.FERR 765_B2_SRT-A
BreakerAC102.86 %296.0B304.4643.65
IPDAEP
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
AEP_P1-2_#311_5_SRT-A
SingleAC102.85 %296.0B304.4543.65
IPDAEP
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
AEP_P4_#311_05CLOVRD 765_CC2_SRT-A
BreakerAC102.85 %296.0B304.4543.65
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 509T570_SRT-A
BreakerAC109.87 %541.0B594.428.16

Details for 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line l/o AEP_P1-2_#311_5_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#311_5_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.64 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:371.9
MW Contribution:24.01
Bus #Bus NameTypeMW Contribution
270173AC1-122 GEN
Solar/Wind Helper
4.149
316123AC1-075 GEN
Solar/Wind Helper
1.385
316197AC1-042 GEN
Solar/Wind Helper
1.563
316217AC1-145 GEN
Solar/Wind Helper
2.009
943811AF1-049 GEN
Solar/Wind Harmer
0
970223AG2-152 GEN
Solar/Wind Harmer
24.008
970417AG2-272 GEN
50/50
2.951
970481AG2-311 GEN
50/50
Charging
19.349
971629AH1-314 GEN
50/50
12.349
966251AG1-494 GEN
50/50
Charging
4.126
961131AF2-404 GEN
50/50
Charging
2.977
NYPJM->LTFIMP_NY
CLTF
0.212
LGEELTFEXP_LGEE->PJM
CLTF
0.235
WECLTFEXP_WEC->PJM
CLTF
0.127
CPLELTFEXP_CPLE->PJM
CLTF
2.551
LAGNLTFEXP_LAGN->PJM
CLTF
1.775
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.483
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.879
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.066
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.755
TVALTFEXP_TVA->PJM
CLTF
0.917
MECLTFEXP_MEC->PJM
CLTF
0.746
SIGELTFEXP_SIGE->PJM
CLTF
0.021
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
6.913

Details for 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line l/o AEP_P4_#7587_05J.FERR 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7587_05J.FERR 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.54 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:365.69
MW Contribution:24.0
Bus #Bus NameTypeMW Contribution
270173AC1-122 GEN
Solar/Wind Helper
4.153
316123AC1-075 GEN
Solar/Wind Helper
1.387
316197AC1-042 GEN
Solar/Wind Helper
1.565
316217AC1-145 GEN
Solar/Wind Helper
2.012
943811AF1-049 GEN
Solar/Wind Harmer
0
970223AG2-152 GEN
Solar/Wind Harmer
24.003
970481AG2-311 GEN
50/50
Charging
19.362
971629AH1-314 GEN
50/50
12.348
961131AF2-404 GEN
50/50
Charging
2.98
NYPJM->LTFIMP_NY
CLTF
0.213
LGEELTFEXP_LGEE->PJM
CLTF
0.237
WECLTFEXP_WEC->PJM
CLTF
0.129
CPLELTFEXP_CPLE->PJM
CLTF
2.555
LAGNLTFEXP_LAGN->PJM
CLTF
1.785
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.537
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.941
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.085
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.773
TVALTFEXP_TVA->PJM
CLTF
0.922
MECLTFEXP_MEC->PJM
CLTF
0.753
SIGELTFEXP_SIGE->PJM
CLTF
0.022
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
6.935

Details for 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line l/o AEP_P4_#2914_05J.FERR 765_B2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2914_05J.FERR 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.21 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:364.71
MW Contribution:24.01
Bus #Bus NameTypeMW Contribution
270173AC1-122 GEN
Solar/Wind Helper
4.149
316123AC1-075 GEN
Solar/Wind Helper
1.385
316197AC1-042 GEN
Solar/Wind Helper
1.563
316217AC1-145 GEN
Solar/Wind Helper
2.009
943811AF1-049 GEN
Solar/Wind Harmer
0
970223AG2-152 GEN
Solar/Wind Harmer
24.008
970481AG2-311 GEN
50/50
Charging
19.349
971629AH1-314 GEN
50/50
12.349
961131AF2-404 GEN
50/50
Charging
2.977
NYPJM->LTFIMP_NY
CLTF
0.212
LGEELTFEXP_LGEE->PJM
CLTF
0.235
WECLTFEXP_WEC->PJM
CLTF
0.127
CPLELTFEXP_CPLE->PJM
CLTF
2.551
LAGNLTFEXP_LAGN->PJM
CLTF
1.775
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.483
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.879
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.066
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.755
TVALTFEXP_TVA->PJM
CLTF
0.917
MECLTFEXP_MEC->PJM
CLTF
0.746
SIGELTFEXP_SIGE->PJM
CLTF
0.021
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
6.913

Details for 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line l/o AEP_P7-1_#10781___SRT-A-3


Base Case Flowgate

Area:AEP
Facility Description:
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10781___SRT-A-3
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:103.45 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:306.2
MW Contribution:34.32
Bus #Bus NameTypeMW Contribution
270173AC1-122 GEN
Solar/Wind Helper
2.81
270030AE2-140 GEN
Solar/Wind Harmer
14.512
316123AC1-075 GEN
Solar/Wind Helper
1.165
316197AC1-042 GEN
Solar/Wind Helper
1.06
316217AC1-145 GEN
Solar/Wind Helper
1.363
943811AF1-049 GEN
Solar/Wind Harmer
0
970223AG2-152 GEN
Solar/Wind Harmer
34.319
970417AG2-272 GEN
50/50
7.782
970481AG2-311 GEN
50/50
Charging
13.795
971629AH1-314 GEN
50/50
30.189
961131AF2-404 GEN
50/50
Charging
2.019
900033ID_568986
External Queue
14.067867279052734
NYPJM->LTFIMP_NY
CLTF
0.121
LGEELTFEXP_LGEE->PJM
CLTF
0.115
WECLTFEXP_WEC->PJM
CLTF
0.055
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.033
LAGNLTFEXP_LAGN->PJM
CLTF
0.33
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.934
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.17
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.676
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.179
TVALTFEXP_TVA->PJM
CLTF
0.183
MECLTFEXP_MEC->PJM
CLTF
0.254
SIGELTFEXP_SIGE->PJM
CLTF
0.009
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.661

Details for [AG2-152] 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line l/o AEP_P4_#7587_05J.FERR 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7587_05J.FERR 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.11 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:305.2
MW Contribution:43.64
IPD Plant:AG2-152
Bus #Bus NameTypeMW Contribution
970223AG2-152 GEN
PJM_IPD
43.642

Details for [AG2-152] 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line l/o AEP_P4_#2914_05J.FERR 765_B2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2914_05J.FERR 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.86 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:304.46
MW Contribution:43.65
IPD Plant:AG2-152
Bus #Bus NameTypeMW Contribution
970223AG2-152 GEN
PJM_IPD
43.651

Details for [AG2-152] 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line l/o AEP_P1-2_#311_5_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#311_5_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.85 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:304.45
MW Contribution:43.65
IPD Plant:AG2-152
Bus #Bus NameTypeMW Contribution
970223AG2-152 GEN
PJM_IPD
43.651

Details for [AG2-152] 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line l/o AEP_P4_#311_05CLOVRD 765_CC2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#311_05CLOVRD 765_CC2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.85 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:304.45
MW Contribution:43.65
IPD Plant:AG2-152
Bus #Bus NameTypeMW Contribution
970223AG2-152 GEN
PJM_IPD
43.651

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 509T570_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.87 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:594.42
MW Contribution:8.16
Bus #Bus NameTypeMW Contribution
3142956BIRDNECK
Solar/Wind Helper
0.29
316075AC2-137 C
Solar/Wind Helper
0.279
316034AC1-036 C
Solar/Wind Helper
0.557
316036AC1-147 C
Solar/Wind Helper
0.321
316059AD1-063 C
Solar/Wind Helper
0.214
316159AE1-175 C
Solar/Wind Helper
0.301
316240AF1-291 C
Solar/Wind Helper
0.313
316246AF1-032 C
Solar/Wind Helper
0.219
316248AF1-058 C
Solar/Wind Helper
1.76
316258AE1-075 C
Solar/Wind Helper
0.293
316305AF2-043 C
Solar/Wind Helper
0.292
316314AB2-024 C
Solar/Wind Helper
0.285
316315AB2-025 C
Solar/Wind Helper
0.294
316316AC1-027 C
Solar/Wind Helper
0.259
316336AC2-165 C
Solar/Wind Helper
1.653
316382AG1-145 C
Solar/Wind Helper
0.302
316405AF2-144 C
Solar/Wind Helper
0.205
316404AE1-155 C
Solar/Wind Helper
1.741
316017AA1-139 ULT1
Solar/Wind Helper
0.898
316018AA1-139 ULT2
Solar/Wind Helper
0.898
316033AB2-134 GEN
Solar/Wind Helper
2.184
316388AE2-253 GEN
Solar/Wind Helper
0.754
316203AE2-005 GEN
Solar/Wind Helper
1.863
316441AF1-014 GEN
Solar/Wind Helper
0.285
316484AD2-074 GEN
Solar/Wind Helper
1.103
315833AF1-017_GEN
Solar/Wind Helper
0.589
316369SG1_INVT
Solar/Wind Helper
1.502
316487AF1-042 GEN
Solar/Wind Helper
0.577
315839AE2-212 C
Solar/Wind Helper
0.324
315662AE1-191 GEN
Solar/Wind Helper
1.147
315666AE1-190 GEN
Solar/Wind Helper
0.287
319010AE1-072 C
Solar/Wind Helper
2.194
315697AD1-025 GEN
Solar/Wind Helper
2.301
316185AD1-033 GEN
Solar/Wind Helper
1.106
315773AC2-141 GEN
Solar/Wind Helper
3.897
316280AD1-041 GEN
Solar/Wind Helper
0.717
316003AC1-222 GEN
Solar/Wind Helper
5.211
316478AD1-087 GEN
Solar/Wind Helper
3.961
316486AD2-202 GEN
Solar/Wind Helper
1.16
316072AD1-144
Solar/Wind Helper
0.222
315687AD1-152 GEN
Solar/Wind Helper
6.825
316156AD2-030 GEN
Solar/Wind Helper
0.284
315785AD2-033 C
Solar/Wind Helper
4.938
316313AB2-026
Solar/Wind Helper
0.326
270030AE2-140 GEN
Solar/Wind Harmer
10.168
316349AD2-085 GEN
Solar/Wind Helper
0.696
313527AB2-043 GEN
Solar/Wind Helper
2.164
316322AB2-045
Solar/Wind Helper
0.501
316359AB2-059 GEN
Solar/Wind Harmer
0
316131AB2-060 GEN
Solar/Wind Helper
3.454
316083AB2-161 GEN
Solar/Wind Helper
0.201
316132AB2-190 GEN1
Solar/Wind Helper
1.145
316458AB2-190 GEN2
Solar/Wind Helper
1.145
316263AC1-034 GEN
Solar/Wind Harmer
2.844
316129AC1-054 GEN
Solar/Wind Helper
1.347
316123AC1-075 GEN
Solar/Wind Helper
4.3
316118AC1-105 GEN
Solar/Wind Helper
4.018
316222AC1-221 GEN
Solar/Wind Helper
13.996
316375AC2-012 GEN
Solar/Wind Helper
1.755
316283AC2-100 C
Solar/Wind Helper
13.179
316339AD2-160 GEN
Solar/Wind Helper
0.754
316239AB2-077_GEN
Solar/Wind Helper
0.88
316238AB2-078_GEN
Solar/Wind Helper
0.88
316237AB2-079_GEN
Solar/Wind Helper
0.88
316294AC1-161 GEN
Solar/Wind Helper
4.209
316381AD1-082 GEN
Solar/Wind Helper
1.054
316233AE1-074 FULL
Solar/Wind Helper
0.298
316236AE1-162_GEN
Solar/Wind Helper
0.315
3145543BTLEBRO
Solar/Wind Harmer
0.188
3145543BTLEBRO
Solar/Wind Harmer
0.188
3145543BTLEBRO
Solar/Wind Harmer
0.188
3145543BTLEBRO
Solar/Wind Harmer
0.151
3138543CONSLDL
Solar/Wind Harmer
0.102
3142053HEARTS
Solar/Wind Harmer
0.075
3145453TOT5
Solar/Wind Harmer
0.052
3145493TOT1
Solar/Wind Harmer
0.166
3145493TOT1
Solar/Wind Harmer
0.087
3145573BETHELC
Solar/Wind Harmer
0.166
3145573BETHELC
Solar/Wind Harmer
0.166
3145603CNETO
Solar/Wind Harmer
0.035
3146073TAR RVR
Solar/Wind Harmer
0.166
3146083TARBORO
Solar/Wind Harmer
0.166
3146083TARBORO
Solar/Wind Harmer
0.166
3146233WITAKRS
Solar/Wind Harmer
0.595
3146233WITAKRS
Solar/Wind Harmer
0.359
3146233WITAKRS
Solar/Wind Harmer
0.102
942461AE2-259 GEN
Solar/Wind Helper
3.485
943811AF1-049 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
2.81
961601AG1-000A GEN
Solar/Wind Harmer
3.875
961671AG1-007 GEN
Solar/Wind Harmer
0.313
961951AG1-038 GEN
Solar/Wind Helper
0.624
970085AG2-068 GEN
Solar/Wind Harmer
8.927
970087AG2-069 GEN
Solar/Wind Harmer
13.39
970223AG2-152 GEN
Solar/Wind Harmer
8.162
970413AG2-270 GEN
50/50
Charging
34.023
970535AG2-341 GEN
50/50
Charging
6.525
970581AG2-369 GEN
Solar/Wind Harmer
7.677
970865AG2-541 GEN
50/50
Charging
16.223
970909AG2-566 GEN
50/50
Charging
4.285
970917AG2-570 GEN
Solar/Wind Harmer
35.706
970919AG2-571 GEN
Solar/Wind Harmer
15.391
971367AH1-164 GEN
Solar/Wind Harmer
1.119
971443AH1-215 GEN
50/50
Charging
2.844
971629AH1-314 GEN
50/50
15.462
957601AF2-054 GEN
Solar/Wind Helper
0.286
957831AF2-077 GEN
Solar/Wind Helper
0.299
964211AG1-282 GEN
Solar/Wind Helper
0.27
971981AH1-535 GEN
Solar/Wind Harmer
2.856
971981AH1-535 GEN
Solar/Wind Harmer
3.116
944201AF1-088_MTX
Adder
35.322
957141AF2-008_MTX
Adder
14.034
900033ID_568986
External Queue
3.5454747676849365
NYPJM->LTFIMP_NY
CLTF
0.559
LGEELTFEXP_LGEE->PJM
CLTF
2.162
WECLTFEXP_WEC->PJM
CLTF
1.175
CPLELTFEXP_CPLE->PJM
CLTF
12.214
LAGNLTFEXP_LAGN->PJM
CLTF
10.551
CBM West 1LTFEXP_CBM-W1->PJM
CBM
43.161
CBM West 2LTFEXP_CBM-W2->PJM
CBM
58.725
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.69
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.334
TVALTFEXP_TVA->PJM
CLTF
5.364
MECLTFEXP_MEC->PJM
CLTF
5.904
SIGELTFEXP_SIGE->PJM
CLTF
0.178
AG2-052LTFEXP_AG2-052->PJM
LTF
0.066
AH1-155LTFEXP_AH1-155->PJM
LTF
0.099
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
28.118
CONTINGENCY 'AEP_P1-2_#311_5_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 290610 CKT Z1   /*05CLOVRD     765.0 - 05CLOVRD_RJA 765.0
 OPEN BRANCH FROM BUS 242514 TO BUS 290610 CKT 1    /*05J.FERR     765.0 - 05CLOVRD_RJA 765.0
 OPEN BRANCH FROM BUS 242684 TO BUS 242685 CKT ZB   /*05J.FERR     138.0 - 05J.FERX     138.0
END
CONTINGENCY 'AEP_P4_#7587_05J.FERR 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 290610 CKT Z1   /*05CLOVRD     765.0 - 05CLOVRD_RJA 765.0
 OPEN BRANCH FROM BUS 242514 TO BUS 242684 CKT 2    /*05J.FERR     765.0 - 05J.FERR     138.0
 OPEN BRANCH FROM BUS 242514 TO BUS 290610 CKT 1    /*05J.FERR     765.0 - 05CLOVRD_RJA 765.0
 OPEN BRANCH FROM BUS 242684 TO BUS 242685 CKT ZB   /*05J.FERR     138.0 - 05J.FERX     138.0
END
CONTINGENCY 'AEP_P4_#2914_05J.FERR 765_B2_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 290610 CKT Z1   /*05CLOVRD     765.0 - 05CLOVRD_RJA 765.0
 OPEN BRANCH FROM BUS 242514 TO BUS 245993 CKT 4    /*05J.FERR     765.0 - 05J.FERR SVS  20.6
 OPEN BRANCH FROM BUS 242514 TO BUS 290610 CKT 1    /*05J.FERR     765.0 - 05CLOVRD_RJA 765.0
 OPEN BRANCH FROM BUS 242684 TO BUS 242685 CKT ZB   /*05J.FERR     138.0 - 05J.FERX     138.0
 REMOVE SWSHUNT FROM BUS 242514                     /*05J.FERR     765.0
END
CONTINGENCY 'AEP_P7-1_#10781___SRT-A-3'
 OPEN BRANCH FROM BUS 242531 TO BUS 304094 CKT 1   /*05EDANV2     230.0 - 6YANCY TAP   230.0
 OPEN BRANCH FROM BUS 304094 TO BUS 304095 CKT 1   /*6YANCY TAP   230.0 - 6YANCYVILLE  230.0
 OPEN BRANCH FROM BUS 304094 TO BUS 304097 CKT 1   /*6YANCY TAP   230.0 - 6CONCD2230TT 230.0
 OPEN BRANCH FROM BUS 900033 TO BUS 304024 CKT 1   /*ID_568986    230.0 - 6ROXSEP230 T 230.0
END
CONTINGENCY 'AEP_P4_#311_05CLOVRD 765_CC2_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 290610 CKT Z1   /*05CLOVRD     765.0 - 05CLOVRD_RJA 765.0
 OPEN BRANCH FROM BUS 242514 TO BUS 290610 CKT 1    /*05J.FERR     765.0 - 05CLOVRD_RJA 765.0
 OPEN BRANCH FROM BUS 242684 TO BUS 242685 CKT ZB   /*05J.FERR     138.0 - 05J.FERX     138.0
END
CONTINGENCY 'DVP_P4-2: 509T570_SRT-A'
 OPEN BRANCH FROM BUS 314935 TO BUS 314945 CKT 1   /*8HERITAGE    500.0 - 8BRUNSWICK   500.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315102 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG1  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315103 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG2  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315104 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG3  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315105 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKS1  19.0
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 OPEN BUS 314945                                   /*8BRUNSWICK   500.0
 OPEN BUS 315102                                   /*1BRUNSWICKG1  21.0
 OPEN BUS 315103                                   /*1BRUNSWICKG2  21.0
 OPEN BUS 315104                                   /*1BRUNSWICKG3  21.0
 OPEN BUS 315105                                   /*1BRUNSWICKS1  19.0
END
290234 to 242802 ckt 1
304070 to 316281 ckt 1

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-038Lexington-Low Moor 230kVUnder Construction
AA1-050Tarboro-Everetts 230kVIn Service
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-067Everetts 34.5kVIn Service
AA1-095Halfway-Marlowe 34.5kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-057Hornertown-Whitakers 115kVIn Service
AA2-174Carolina-Jackson 115kVIn Service
AA2-178Mackeys 230kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-006Meadow Lake 345kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-096Carroll-Mt. Airy 34.5kVIn Service
AB1-124Carroll-Monocacy 34.5kVPartially in Service - Under Construction
AB1-125Carroll-Monocacy 34.5kVIn Service
AB1-127St. Thomas-Guilford 34.5kVIn Service
AB1-128St. Thomas-Mercersburg 34.5kVIn Service
AB1-132Thelma 230kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB1-180Pine View 12kVIn Service
AB2-022Elizabeth City 34.5kVIn Service
AB2-024Correctional 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-031Brink-Trego 115kVIn Service
AB2-032Church-Wye Mills 138 kVIn Service
AB2-037Keeney-Steele 230kVUnder Construction
AB2-040Brink 115kVIn Service
AB2-043Chase City 115kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-049Gloucester Township 12kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-134Hopewell-Surry 230kVIn Service
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVUnder Construction
AB2-153Church-Wye Mills 138 kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-169Pantago-Five Points 115kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AB2-179Townsend 138kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-001Delano 138kVIn Service
AC1-010Gloucester 26kVUnder Construction
AC1-027Pendleton 34.5kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVSuspended
AC1-036Twittys Creek 34.5kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-053Lanesville-BrokawPartially in Service - Under Construction
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-074Jacksonville-Renaker 138kV IIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-082Ravenswood-Hemlock 69kVUnder Construction
AC1-085Stuart-Clinton 345kVIn Service
AC1-086Thelma 230kVSuspended
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-091Cedar Creek 138kV IEngineering & Procurement
AC1-092Cedar Creek 138kV IIEngineering & Procurement
AC1-093Cedar Creek 138kV IIIEngineering & Procurement
AC1-094Cedar Creek 138kV IVEngineering & Procurement
AC1-098Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-099Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-101Johns Creek-Excel 138kV ISuspended
AC1-102Johns Creek-Excel 138kV IISuspended
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-111Aurora 138kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-188Rio-Lick 138kVEngineering & Procurement
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-191Elmont 115kVEngineering & Procurement
AC1-194Elk 138kVActive
AC1-208Cox-Whitakers 115kVUnder Construction
AC1-214Crescent RidgeIn Service
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-023Hebron 69kVEngineering & Procurement
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-075Jacksonville-Renaker 138 kVIn Service
AC2-079Ivor-Oak Ridge 115kVSuspended
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-100Halifax-Person 230kVIn Service
AC2-111College Corner 138kVEngineering & Procurement
AC2-120Ripley 69kVIn Service
AC2-123Jacksons Ferry 138kVIn Service
AC2-136East Hagerstown 12kVUnder Construction
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-157Sullivan 345 kVUnder Construction
AC2-165Bremo-Powhatan 230kVSuspended
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AD1-013Twombly Road 138kVEngineering & Procurement
AD1-017Smith Mountain-Bearskin 138 kVIn Service
AD1-020Hunterstown-Lincoln 115 kVIn Service
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVUnder Construction
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-060Mercersburg-Milnor 34.5 kVIn Service
AD1-061McConnelsburg-Mercersburg 34 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-088Briery-Clover 230 kVSuspended
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-128Modoc-Delaware 138 kVPartially in Service - Under Construction
AD1-136South Bethel-Brown 69 kVIn Service
AD1-144Kings Fork 34.5 kVIn Service
AD1-151Hopewell-Surry 230 kVSuspended
AD1-152Clover-Sedge Hill 230 kVIn Service
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-009McConnellsburg 138 kVIn Service
AD2-022East Danville - Roxborough 230 kVEngineering & Procurement
AD2-023East Danville - Roxborough 230 kVEngineering & Procurement
AD2-027Camden Switch 26 kVIn Service
AD2-030Wan 34.5 kVIn Service
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-042Camden Switch 26 kV IIIn Service
AD2-048Cynthia-Headquarters 69 kVUnder Construction
AD2-058St. Barnabas 13 kVIn Service
AD2-065Atco 12 kVIn Service
AD2-066Mazon-Crescent Ridge 138 kVEngineering & Procurement
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVEngineering & Procurement
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-100Kincaid-Pana 345 kVSuspended
AD2-116Hokes-Grantley 69 kVIn Service
AD2-131Kincaid-Pana 345kVSuspended
AD2-134Shady OaksPartially in Service - Under Construction
AD2-135Williamstown 12kVPartially in Service - Under Construction
AD2-160Hickory-Moyock 230kVIn Service
AD2-172Lena 138kVIn Service
AD2-179Morgans Cut-Glen Lyn 138kVSuspended
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-040Greenfield 69 kVIn Service
AE1-056Red House-South Creek 115 kVWithdrawn
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-100Axton 138 kVIn Service
AE1-101McConnellsburg-Texas Eastern 138 kVIn Service
AE1-103Holland-Union Camp 115 kVUnder Construction
AE1-108Bremo-Scottsville 138 kVEngineering & Procurement
AE1-113Mole Creek 345 kVEngineering & Procurement
AE1-114Maryland-Lancaster 138 kVActive
AE1-148Kerr Dam-Ridge Rd 115 kVActive
AE1-149Disputanta-Poe 115 kVSuspended
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-157Ladysmith CT-St. Johns 230 kVSuspended
AE1-162Smithfield 34.5 kVIn Service
AE1-163Powerton-Nevada 345 kVEngineering & Procurement
AE1-172Loretto-Wilton CenterActive
AE1-173Carson-Suffolk 500 kVUnder Construction
AE1-175Light Foot 34.5 kVIn Service
AE1-176Roanoke-Vinton 12 kV (Niagara Hydro)In Service
AE1-185Hokes-Jackson 69 kVIn Service
AE1-190Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-191Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-196Hokes-Jackson 69 kV IIIn Service
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-212Grandview-Clifftop 138 kVSuspended
AE1-229Deepwater-Upper Pittsgrove 138 kVSuspended
AE1-250Smith Mountain-E. Danville 138 kVEngineering & Procurement
AE2-005Harmony Village-Shackleford 115 kVUnder Construction
AE2-027Harrowgate-Locks 115kVUnder Construction
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-033Clubhouse-Sapony 230 kVSuspended
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-035Lena 138 kVIn Service
AE2-040Sapony 34.5 kVPartially in Service - Under Construction
AE2-047Ridgeway-Solite 69 kVEngineering & Procurement
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-054Warfordsburg 34 kVIn Service
AE2-071Patton Rd-Summer Shade 69 kVIn Service
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-094Carson-Rogers Road 500 kVEngineering & Procurement
AE2-104Suffolk 115 kVSuspended
AE2-140Axton-Danville 138 kVSuspended
AE2-156Yadkin 115 kVActive
AE2-160Kanawha River 138 kVEngineering & Procurement
AE2-166Stockton 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-173McLean 345 kVActive
AE2-183Rogers Road 500 kVIn Service
AE2-185Gladys DP-Stonemill Switching Station 69 kVActive
AE2-187Shockoe DP-Chatham 69 kVActive
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVActive
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-253Hickory-Moyock 230 kVIn Service
AE2-254Garrard County-Tommy-Gooch 69 kVIn Service
AE2-255Molecreek 345 kVEngineering & Procurement
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-261Kincaid-Pana 345 kVActive
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-281Powerton-Nevada 345 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVActive
AE2-291Grit DP-Perth 115 kVActive
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-308Three Forks-Dale 138 kVActive
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-321Belvidere-Marengo 138 kVActive
AE2-326Jacksons Ferry 138 kVEngineering & Procurement
AE2-339Avon 138 kVEngineering & Procurement
AE2-341Sandwich-Plano 138 kVActive
AE2-346Ahoskie 34.5 kVIn Service
AF1-007Indian River 230 kV ISuspended
AF1-014Harmony Village-Shackleford 115 kVUnder Construction
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-030Sandwich-Plano 138 kVActive
AF1-032Suffolk 34.5 kVIn Service
AF1-038Sewellton Jct-Webbs Crossroads 69 kVEngineering & Procurement
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-045Cedarville-Ford 138 kVSuspended
AF1-049Berry Hill 138 kVUnder Construction
AF1-050Summer Shade - Green County 161 kVEngineering & Procurement
AF1-058Welco 34.5 kVIn Service
AF1-069Carson-Rogers Rd 500 kVEngineering & Procurement
AF1-075Harrisburg-Endless Caverns 230 kVSuspended
AF1-083Green County-Saloma 161 kVEngineering & Procurement
AF1-088Sullivan 345 kVActive
AF1-090Kincaid-PanaEngineering & Procurement
AF1-114Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF1-123Harper 230 kVActive
AF1-124Harper 230 kVActive
AF1-125Harper 230 kVActive
AF1-128Chesterfield 230 kVActive
AF1-129Chesterfield 230 kVEngineering & Procurement
AF1-130Inez 138 kVSuspended
AF1-136Warfordsburg-Purcell Junction 34.5 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVUnder Construction
AF1-162Inez 138 kVEngineering & Procurement
AF1-203Patton Rd-Summer Shade 69 kVIn Service
AF1-204Eugene 345 kVActive
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-233Flemingsburg – Spurlock 138kVActive
AF1-249Nickel 12.47 kVIn Service
AF1-254Milnor-Huyetts 34.5 kVUnder Construction
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-290Feagans Mill-Millville 138 kVIn Service
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-292Fields 34.5kVEngineering & Procurement
AF1-294Jetersville-Ponton 115 kVActive
AF1-296Garden Plain 138 kVActive
AF1-299Otter Point 34.5 kV IIn Service
AF1-300Otter Point 34.5 kV IIIn Service
AF1-322Meadow Lake 345 kVEngineering & Procurement
AF1-331Twombley RoadEngineering & Procurement
AF2-008Sullivan 345 kVActive
AF2-018Inez 138 kVEngineering & Procurement
AF2-032Kincaid 345 kVEngineering & Procurement
AF2-035St. Johns 115 kVActive
AF2-041Nelson-Electric Junction 345 kVActive
AF2-042Clover-Rawlings 500 kVActive
AF2-043Suffolk 34.5 kVIn Service
AF2-046Tunis-Mapleton 115 kVActive
AF2-048Rio-Lick 138 kVEngineering & Procurement
AF2-054Wan 34.5 kVIn Service
AF2-069Crescent Ridge 138 kVActive
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-080Chinquapin-Everetts 230 kVActive
AF2-081Moyock 230 kVActive
AF2-085Midlothian 34.5 kVIn Service
AF2-106Hazel Hollow-Glen Lyn #1 138 kVEngineering & Procurement
AF2-107Clifford 138 kVEngineering & Procurement
AF2-110Suffolk 115 kVSuspended
AF2-111North Clark-Spurlock 345 kVActive
AF2-115Jetersville-Ponton 115 kVActive
AF2-120Garner-Northern Neck 115 kVActive
AF2-142Nevada 345 kVActive
AF2-143Powerton-Nevada 345 kVActive
AF2-144Powhatan 34.5 kVIn Service
AF2-173Desoto 345 kVActive
AF2-199Nelson-Electric Junction 345 kVActive
AF2-200Nelson-Electric Junction 345 kVActive
AF2-222Madisonville DP-Twitty's Creek 115 kVActive
AF2-225McLean 345 kVActive
AF2-250Edgewood 12 kV IIIIn Service
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-297Sedge Hill 115 kVActive
AF2-299Fields 34.5 kVActive
AF2-307Hope-Belvins Valley Tap 69 kVActive
AF2-311Gilboa-Jones Branch 138 kVEngineering & Procurement
AF2-316Gilboa-Jones Branch 138 kV IIEngineering & Procurement
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-335Delaware-Royerton 138 kVActive
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-365Munfordville KU Tap-Horse Cave Jct. 69 kVActive
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AF2-382Hurley 69 kVEngineering & Procurement
AF2-383Tolna 115 kVWithdrawn
AF2-392Nelson-Dixon 138 kVActive
AF2-404Gladys DP-Stonemill 69 kVActive
AF2-440Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-007Tar River 12.5 kVEngineering & Procurement
AG1-008Tunis-Mapleton 115 kVActive
AG1-021Jetersville-Ponton 115 kVActive
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-066Bonnyman 69 kVEngineering & Procurement
AG1-070Bon Ayr 69 kVActive
AG1-071Bon Ayr 69 kVActive
AG1-082Ahoskie 34.5 kVActive
AG1-098Briery-Clover 230 kVActive
AG1-105Mount Laurel-Barnes Junction 115 kVActive
AG1-106Thelma 230 kVActive
AG1-107Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-118Sugar Grove-Waterman 138kVActive
AG1-124Gladstone 138 kVActive
AG1-127Crego Rd 138 kVActive
AG1-135Garner-Lancaster 115 kVActive
AG1-145Lightfoot 34.5 kVIn Service
AG1-146Garner DP-Lancaster 115 kVActive
AG1-147Garner DP-Lancaster 115 kVActive
AG1-153Heritage 500 kVActive
AG1-166Lone Pine 115 kVActive
AG1-167Lone Pine 115 kVActive
AG1-168Lone Pine 115 kVActive
AG1-226Dequine-Eugene 345 kVActive
AG1-236Lanesville-Brokaw 345 kVActive
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-254Salem-Woodstown 69 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVEngineering & Procurement
AG1-285Chase City-Central 115 kVActive
AG1-320Glendale-Stephensburg 69 kVActive
AG1-341Summer Shade 161 kVActive
AG1-342Dryburg 115 kVActive
AG1-354Summershade-Green County 161 kVActive
AG1-367DeSoto 345 kVActive
AG1-374Blue Mound 345 kVActive
AG1-393Sapony 34.5 kVActive
AG1-394Boykins 34.5 kVActive
AG1-397Walston 12 kVWithdrawn
AG1-405Walnut Grove-Asahi 69 kVActive
AG1-406Walnut Grove-Asahi 69 kVActive
AG1-460Kincaid-Pana 345 kVActive
AG1-462Cordova 345 kVActive
AG1-469Gordonsville 34.5 kVEngineering & Procurement
AG1-471Up Church-Wayne County 69 kVActive
AG1-482Hamilton 115 kVWithdrawn
AG1-494Boxwood-Riverville 138 kVActive
AG1-499Lambs 12.47 kVUnder Construction
AG1-508Point Lookout 69 kVEngineering & Procurement
AG1-526West Garrard 345 kVActive
AG1-532Fields 34.5 kVEngineering & Procurement
AG1-551Parmele 34.5 kVActive
AG1-552Carolina 34.5 kVActive
AG1-555Dequine 345 kVEngineering & Procurement
AG1-558Buckner 34.5 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
AG2-005Garner DP-Lancaster 115 kVActive
AG2-010Peninsula-Whealton 115 kVActive
AG2-068Heritage - Wake 500 kVActive
AG2-069Heritage - Wake 500 kVActive
AG2-072Rockport 765 kVActive
AG2-073Crooksville 69 kVActive
AG2-077Clover-Rawlings 500 kVActive
AG2-081Mt. Sterling-Fogg Pike 69 kVActive
AG2-085Delaware-Royerton 138 kVActive
AG2-088Midlothian 230 kVActive
AG2-093Colonial Trail-Hopewell 230 kVActive
AG2-095Hopewell 34.5 kV (Circuit 313)Active
AG2-111Perth 34.5 kV Substation (Circuit 408)Active
AG2-112Perth 34.5 kV Substation (Circuit 404)Active
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-120Everetts 34.5 kVActive
AG2-124Shackleford-Harmony 115 kVActive
AG2-126Eugene 345 kVActive
AG2-151Trices Lake - James River Tap 115 kVActive
AG2-159Williamstown 69 kVActive
AG2-162Jefferson-Greentown 765 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-164Jefferson-Greentown 765 kVActive
AG2-171Lunenburg-Nutbush 115 kVActive
AG2-179Sewellton Junction 69 kVActive
AG2-184Harbert Metering 138 kVActive
AG2-188Farmville - Buckingham 230 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-193Turner 34.5 kVActive
AG2-198Briery - Finneywood 230 kVActive
AG2-208Greenwood DP - St. Johns DP 115 kVActive
AG2-213Gary D.P Tap - Gary D.P 115 kVActive
AG2-215Garner DP-Lancaster 115 kVActive
AG2-219Jefferson-Greentown 765 kVActive
AG2-262Dryburg 115 kVActive
AG2-270Clover 230 kVActive
AG2-272Berry Hill 138 kVActive
AG2-298Sulphur Creek-Loretto 69 kVActive
AG2-310Matt Funk 138 kVActive
AG2-311Smith Mountain 138 kVActive
AG2-331Jefferson-Greentown 765 kVActive
AG2-338Rogers Road - Carson 500 kVActive
AG2-339Rogers Road - Carson 500 kVActive
AG2-341Ridge Road 115 kVActive
AG2-360Broadford 138 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-369Heritage - Wake 500 kVActive
AG2-382Cashie 230 kVActive
AG2-384Chesterfield 230 kVActive
AG2-401Losantville 345 kVActive
AG2-424Magnolia - Summersville 69 kVActive
AG2-426Wakefield - Waverly 115 kVActive
AG2-427Waverly 115 kVActive
AG2-428Wakefield 115 kVActive
AG2-436Carson - Rogers Road 500 kVActive
AG2-440Twittys Creek - Madisonville 115 kVActive
AG2-441Twittys Creek - Madisonville 115 kVActive
AG2-442Twittys Creek - Madisonville 115 kVActive
AG2-449Jefferson-Greentown 765 kVActive
AG2-469Westmoreland – Oak Grove 230 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-516Pecatonica 138kVActive
AG2-518Tech Drive 138 kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-522Five Forks DP 115 kVActive
AG2-541Perth - Crystal Hill 115 kVActive
AG2-548Corwin - Elk 138 kVActive
AG2-566Briery - Finneywood 230 kVActive
AG2-568Stink Run – Sundial 138 kVActive
AG2-570Heritage - Wake 500 kVActive
AG2-571Heritage - Wake 500 kVActive
AG2-575Crego Rd. 138 kVActive
AG2-581Rawlings-Clover 500 kVActive
AG2-583Bremo - Cartersville 230 kVActive
AG2-589Ravenswood - Hemlock 69 kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-657Kanawha River - Carbondale 138 kVActive
AG2-659Kerr Dam – Hawtree 115 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-661Hopewell - Colonial Trail 230 kVActive
AG2-665Corwin - Elk 138 kVActive
AG2-670Green County -Taylor County Junction 161 kVActive
AH1-004Avon - Renaker 138 kVActive
AH1-012Louisa - North Anna 230 kVActive
AH1-033Sligo 34.5 kVActive
AH1-034Patton Road Junction - Summer Shade 69 kVActive
AH1-035Plymouth 34.5 kVActive
AH1-040Mackeys - Creswell 115 kVActive
AH1-042Providence Forge-Turner 115kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-047Marengo - Belvidere 138 kVActive
AH1-055Kyger Creek - Don Marquis 345 kVActive
AH1-056Red House DP 115kVActive
AH1-065Hopewell 34.5kVActive
AH1-066Hopewell 34.5kVActive
AH1-071Midlothian 34.5 kVActive
AH1-072Red Onion - VC5 69 kVActive
AH1-073Red Onion - VC5 69 kVActive
AH1-098Wolf Glade-West Carroll 138 kVActive
AH1-106Winterpock 34.5kVActive
AH1-107Winterpock 34.5kVActive
AH1-108Spruance NUG 230 kVActive
AH1-133Saltville - Tazewell 138 kVActive
AH1-136Falcon - Middle Creek 46 kVActive
AH1-138Penniman 34.5 kVActive
AH1-144Peter's Mountain 138 kVActive
AH1-145Peter's Mountain 138 kVActive
AH1-146White Rock - Wayne 345 kVActive
AH1-147White Rock - Wayne 345 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-157Penniman - Waller 230 kVActive
AH1-164Oak Level - Tank Hill 138 kVActive
AH1-170Columbia DP 115kVActive
AH1-188Pigeon Creek 138 kVActive
AH1-196Prairie 345 kVActive
AH1-215Central VA-Twitty 115 kVActive
AH1-216Smithfield-Surry 230 kVActive
AH1-217Kidds Store - Fork Union 115 kV IIActive
AH1-221Heritage 500 kVActive
AH1-227Flemming - Fremont 69 kVActive
AH1-234Wempletown - Paddock 345 kVActive
AH1-239Upchurch - Zula 69 kVActive
AH1-241Cobbs Creek - James River Industrial 115kVActive
AH1-269Claytor 138 kVActive
AH1-271Cashie 230 kVActive
AH1-280Jetersville-Ponton 115 kVActive
AH1-281Bluegrass Parkway Tap - Woodlawn 69 kVActive
AH1-285Sandwich 138 kVActive
AH1-292Sullivan 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-311Heartsease DP - Mayo Dunbar 115kVActive
AH1-314East Danville 138 kVActive
AH1-323Elmont 230 kVActive
AH1-324Colonial Trail – Surry 230 kVActive
AH1-337Randolph - Hodgin 138 kVActive
AH1-338McGirr Rd - Ritchie Road 138kVActive
AH1-341Stillman - Dixon 138KVActive
AH1-343Crystal Hill DP- Perth 115kVActive
AH1-348Pound 34.5 kVActive
AH1-377Clover- Farmville 230kVActive
AH1-396Gary 24.94 kVActive
AH1-397Shacklesford 34.5 kVActive
AH1-399North Doswell 12.5 kVActive
AH1-408Freeman DP – Lawrenceville 115 kVActive
AH1-427Tommy Gooch - Garrard County 69 kVActive
AH1-439Buckingham- Farmville 230kVActive
AH1-528Rawlings - Unity 500 kVActive
AH1-535Nagel - Cane River 230 kVActive
AH1-537Pierce - Kyger Creek 345 kVActive
AH1-541Chestnut 345 kVActive
AH1-543Mulberry – Tazewell 345 kVActive
AH1-546Bremo - Buckingham 230 kVActive
AH1-570Headquarters - Millersburg Junction 69 kVActive
AH1-571Headquarters - Millersburg Junction 69 kVActive
AH1-617Harbert Metering 138 kVActive
AH1-637Oak Grove 34.5 kVActive
AH1-644Spicewood Metering 138 kVActive
AH1-664Goddard-Plumville 138 kVActive
AH1-665Goddard-Plumsville 138 kV IIActive
AH1-666Flemingsburg - Spurlock 138 kVActive
AH1-670Blue Mound-Chestnut 345 kVActive
AH1-676Gordonsville 230 kVActive
AH1-677Rogers Road 500 kVActive
AH1-678Heritage 500 kVActive
AH1-679Four Rivers 230 kVActive
AH1-681Cunningham 500 kVActive
AH1-682Ladysmith CT 230 kVActive
AH1-683Ladysmith CT 230 kVActive
AH1-686Hanging Rock 765 kVActive
AH1-687Bear Garden 230kVActive
AH1-690Bay Shore - Lallendorf 345 kVActive
AH1-691Ladysmith CT 230 kVActive
AH1-692Ladysmith CT 230 kVActive
AH1-694Ladysmith CT 230 kVActive
AH1-702Byron 345 kVActive
AH1-712Cunningham 500 kVActive
AH1-716Surry-Skiffes Creek 500kVActive
AH1-717Surry 230kVActive
AH1-718Nelson 345 kVActive
AH1-721Laurel-Cooper 161 kVActive
AH1-723Cunningham 500 kVActive
V3-007Desoto-Tanners Creek #1 345kVIn Service
V4-067Cates Road Egg Harbor Township 12kVDeactivated
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
W2-048Brokaw-LanesvilleIn Service
W4-005Blue Mound-LathamIn Service
X2-022Brokaw-LanesvilleIn Service
X3-066Church Hill 69kVIn Service
Y1-049Wurno 34.5kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y1-086Morgans CornerIn Service
Y3-058Rockawalkin 69kVIn Service
Z1-036WinFall-Chowan 230kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-044Whitakers 34.5kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)Identified Impacts

No cost allocated AFS Tie Line reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.


System Reinforcement
Type
Load Flow
TO
CPLE
RTEP ID / TO ID
(Pending) / TC2-CPLE-0001
Title
Person - VP Hendrick 230kV Line (Existing Line Uprate)
Description
Currently no costs since there is already a DEP project to reconductor to upgrade this line. This is the estimated ISD for the current project CPLE is developing. The Person - Hendrick 230 kV line will be reconductored with bundled 795 ACSS/TW and will have a rating 1195MVA.
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
0 to 48 Months

Info

Note: AG2-152 contributes to the loading of an overloaded tie line facility between PJM and an affected system entity, which was identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line and will be confirmed in subsequent study phases, along with cost allocation of such upgrade if applicable, in coordination with the affected system.

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)

Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Study Pending
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Study Pending
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase I analysis results, this project may have a cost responsibility for the following System Reinforcements:

AG2-152 System Reinforcements:
TORTEP IDTitleAllocated Cost ($USD)
AEP(Pending) / AEP-TC2-1870405SMITHMTN 138.0 kV to 05LEESVI 138.0 kV ckt 1 - Rebuild$13,245,672
Dominion(Pending) / TC2-PH1-DOM-0044Wreck and rebuild 4.5 miles of 230 kV Line 2204 between Black Walnut and Edmonson with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.$1,689,186
Dominion(Pending) / TC1-PH1-DOM-096Wreck and rebuild 2.8 mi of 115 kV Line 15 between Huber DP and Sedgehill with (1) 768,2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C$1,335,495
Dominion(Pending) / TC2-PH1-DOM-2001Wreck and rebuild 2.66 miles of 115 kV line 1016 between Crystal Hill DP and AH1-343 with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.$1,270,297
AEP(Pending) / AEP-TC2-1871705BANSTR 138.0 kV to 05EDAN 2 138.0 kV ckt 1 - Sag Study and Replace Equipment$1,167,298
Dominion(Pending) / TC2-PH1-DOM-0045Wreck and rebuild 8.3 miles of 230 kV Line 2250 between Edmonson and Sedge Hill with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.$670,515
Dominion(Pending) / dom-184Wreck and rebuild 0.97 mi of 115 kV Line 15 between Woodchuck Trail and Huber DP with (1) 768,2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C$462,654
AEP(Pending) / AEP-TC2-1865505MUSEVILLE 138.0 kV to 05SMITHMTN 138.0 kV ckt 1 - Replace Switch$370,179
Dominion(Pending) / TC2-PH1-DOM-2002Replace 556.6 ACSR line lead on line 104 at AltaVista 138 kV$158,414
Dominion(Pending) / TC2-PH1-DOM-2043Wreck and rebuild 0.93 miles of 230 kV Line 2241 between Hendrick and Persons with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Dominion portion of line only.$63,434
AEP(Pending) / AEP-TC2-18709AG2-152 TP 138.0 kV to 05BANSTR 138.0 kV ckt 1 - Sag Study and Upgrade Equipment$34,332
Dominionn8423 / dom-119Wreck and rebuild 0.06 miles of 115 kV line 1016 between Woodchuck Trail and Crystal Hill DP with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.$28,653
AEP(Pending) / AEPAPRJV004Replace wavetrap @ New London$25,960
Grand Total:$20,522,089

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18704
Title
05SMITHMTN 138.0 kV to 05LEESVI 138.0 kV ckt 1 - Rebuild
Description
Rebuild ~8.2 miles of 138 kV line between Smith Mountain and Leesville, upgrade 795 AAC station conductor at Smith Mountain and Leesville.
Total Cost ($USD)
$32,000,000
Allocated Cost ($USD)
$13,245,672
Time Estimate
36 to 48 Months

Contributor

FacilityContingency
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-111
3.8 MW5.3%$1,710,840
AG2-112
4.0 MW5.6%$1,793,537
AG2-152
29.8 MW41.4%$13,245,672
AG2-311
13.9 MW19.3%$6,172,896
AG2-541
13.6 MW18.9%$6,049,740
AH1-343
6.8 MW9.5%$3,027,315

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0044
Title
Wreck and rebuild 4.5 miles of 230 kV Line 2204 between Black Walnut and Edmonson with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 4.5 miles of 230 kV Line 2204 between Black Walnut and Edmonson with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$17,100,000
Allocated Cost ($USD)
$1,689,186
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
9.9 MW7.4%$1,256,962
AG2-069
14.9 MW11.0%$1,885,444
AG2-152
13.4 MW9.9%$1,689,186
AG2-369
8.5 MW6.3%$1,081,064
AG2-541
14.1 MW10.5%$1,788,832
AG2-570
39.8 MW29.4%$5,027,723
AG2-571
5.0 MW3.7%$636,448
AH1-314
13.5 MW10.0%$1,705,751
AH1-343
16.0 MW11.9%$2,028,591

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH1-DOM-096
Title
Wreck and rebuild 2.8 mi of 115 kV Line 15 between Huber DP and Sedgehill with (1) 768,2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C
Description
Wreck and rebuild 2.8 mi of 115 kV Line 15 between Huber DP and Sedgehill with (1) 768,2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C
Total Cost ($USD)
$8,960,000
Allocated Cost ($USD)
$1,335,495
Time Estimate
30 to 36 Months

Contributor

FacilityContingency
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-111
5.0 MW5.8%$516,143
AG2-112
5.3 MW6.0%$541,145
AG2-152
13.0 MW14.9%$1,335,495
AG2-311
6.1 MW6.9%$622,404
AG2-541
27.0 MW30.9%$2,768,644
AH1-343
31.0 MW35.4%$3,176,168

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2001
Title
Wreck and rebuild 2.66 miles of 115 kV line 1016 between Crystal Hill DP and AH1-343 with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 2.66 miles of 115 kV line 1016 between Crystal Hill DP and AH1-343 with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$8,512,000
Allocated Cost ($USD)
$1,270,297
Time Estimate
30 to 36 Months

Contributor

FacilityContingency
3CRSTL HILL-AH1-343 TP 115.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-111
5.0 MW5.8%$490,200
AG2-112
5.3 MW6.0%$513,936
AG2-152
13.1 MW14.9%$1,270,297
AG2-311
6.1 MW7.0%$592,053
AG2-541
27.0 MW30.9%$2,629,314
AH1-343
31.0 MW35.4%$3,016,201

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18717
Title
05BANSTR 138.0 kV to 05EDAN 2 138.0 kV ckt 1 - Sag Study and Replace Equipment
Description
Replace first overhead conductor span from East Danville to Structure 18-135 (1033 ACSR); Conduct sag clearance study on 10.7 miles between Structure 18-135 and Banister; Replace 1590 AAC station conductor at Banister; Replace 2000 AAC station conductor at East Danville
Total Cost ($USD)
$1,700,000
Allocated Cost ($USD)
$1,167,298
Time Estimate
36 to 48 Months

Contributor

FacilityContingency
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-152
80.4 MW68.7%$1,167,298
AG2-311
19.0 MW16.3%$276,475
AG2-541
8.6 MW7.3%$124,289
AH1-343
9.1 MW7.8%$131,938

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0045
Title
Wreck and rebuild 8.3 miles of 230 kV Line 2250 between Edmonson and Sedge Hill with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 8.3 miles of 230 kV Line 2250 between Edmonson and Sedge Hill with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$31,540,000
Allocated Cost ($USD)
$670,515
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
10.0 MW1.6%$498,905
AG2-069
14.9 MW2.4%$748,333
AG2-077
80.7 MW12.8%$4,042,771
AG2-152
13.4 MW2.1%$670,515
AG2-188
22.3 MW3.5%$1,116,290
AG2-198
21.6 MW3.4%$1,082,038
AG2-270
56.8 MW9.0%$2,844,056
AG2-369
8.6 MW1.4%$429,050
AG2-440
13.1 MW2.1%$656,895
AG2-441
16.4 MW2.6%$821,143
AG2-442
18.4 MW2.9%$919,642
AG2-541
14.2 MW2.2%$709,124
AG2-566
4.1 MW0.7%$205,461
AG2-570
39.8 MW6.3%$1,995,421
AG2-571
5.0 MW0.8%$252,582
AG2-581
59.5 MW9.4%$2,977,307
AH1-056
15.1 MW2.4%$754,092
AH1-314
13.5 MW2.1%$676,925
AH1-343
16.1 MW2.5%$804,067
AH1-377
54.4 MW8.6%$2,722,822
AH1-439
12.8 MW2.0%$641,972
AH1-528
119.2 MW18.9%$5,970,589

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / dom-184
Title
Wreck and rebuild 0.97 mi of 115 kV Line 15 between Woodchuck Trail and Huber DP with (1) 768,2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C
Description
Wreck and rebuild 0.97 mi of 115 kV Line 15 between Woodchuck Trail and Huber DP with (1) 768,2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C
Total Cost ($USD)
$3,104,000
Allocated Cost ($USD)
$462,654
Time Estimate
30 to 36 Months

Contributor

FacilityContingency
3HUBER DP-AC1-222 TAP 115.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-111
5.0 MW5.8%$178,807
AG2-112
5.3 MW6.0%$187,468
AG2-152
13.0 MW14.9%$462,654
AG2-311
6.1 MW6.9%$215,619
AG2-541
27.0 MW30.9%$959,137
AH1-343
31.0 MW35.4%$1,100,315

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18655
Title
05MUSEVILLE 138.0 kV to 05SMITHMTN 138.0 kV ckt 1 - Replace Switch
Description
Replace 138 kV Switch at Smith Mountain "C1S2"
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$370,179
Time Estimate
36 to 48 Months

Contributor

FacilityContingency
05SMITHMTN-05MUSEVILLE 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-152
112.6 MW74.0%$370,179
AG2-272
7.8 MW5.1%$25,589
AG2-311
19.3 MW12.7%$63,625
AH1-314
12.3 MW8.1%$40,607

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2002
Title
Replace 556.6 ACSR line lead on line 104 at AltaVista 138 kV
Description
Replace 556.6 ACSR line lead on line 104 at AltaVista 138 kV
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$158,414
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-152
6.9 MW39.6%$158,414
AG2-311
10.5 MW60.4%$241,586

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2043
Title
Wreck and rebuild 0.93 miles of 230 kV Line 2241 between Hendrick and Persons with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Dominion portion of line only.
Description
Wreck and rebuild 0.93 miles of 230 kV Line 2241 between Hendrick and Persons with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Dominion portion of line only.
Total Cost ($USD)
$3,534,000
Allocated Cost ($USD)
$63,434
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
9.2 MW1.1%$39,652
AG2-069
13.8 MW1.7%$59,477
AG2-077
67.9 MW8.3%$292,796
AG2-111
3.5 MW0.4%$15,101
AG2-112
3.7 MW0.4%$15,830
AG2-151
7.2 MW0.9%$31,260
AG2-152
14.7 MW1.8%$63,434
AG2-171
13.1 MW1.6%$56,405
AG2-188
21.4 MW2.6%$92,359
AG2-198
19.5 MW2.4%$83,993
AG2-213
17.4 MW2.1%$75,209
AG2-270
47.1 MW5.8%$203,423
AG2-272
5.3 MW0.7%$23,062
AG2-341
6.5 MW0.8%$27,834
AG2-369
7.9 MW1.0%$34,099
AG2-440
21.4 MW2.6%$92,165
AG2-441
26.7 MW3.3%$115,205
AG2-442
29.9 MW3.7%$129,034
AG2-522
10.0 MW1.2%$43,134
AG2-541
19.1 MW2.3%$82,250
AG2-566
9.3 MW1.1%$39,936
AG2-570
35.7 MW4.4%$154,059
AG2-571
15.5 MW1.9%$67,037
AG2-581
50.2 MW6.1%$216,526
AG2-583
7.5 MW0.9%$32,494
AG2-659
11.3 MW1.4%$48,915
AH1-056
20.7 MW2.5%$89,249
AH1-215
8.7 MW1.1%$37,455
AH1-241
6.9 MW0.8%$29,676
AH1-314
15.6 MW1.9%$67,343
AH1-343
22.0 MW2.7%$94,896
AH1-377
48.3 MW5.9%$208,557
AH1-408
10.5 MW1.3%$45,498
AH1-439
12.3 MW1.5%$53,152
AH1-528
100.6 MW12.3%$434,213
AH1-535
6.0 MW0.7%$25,767
AH1-546
7.3 MW0.9%$31,579
AH1-687
5.2 MW0.6%$22,479
AH1-690
28.7 MW3.5%$123,688
AH1-721
31.5 MW3.8%$135,756

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18709
Title
AG2-152 TP 138.0 kV to 05BANSTR 138.0 kV ckt 1 - Sag Study and Upgrade Equipment
Description
Upgrade 1590 AAC station conductor at Banister. Perform sag clearance study for ~0.5 mile of 138 kV line between AG2-152 and Banister to determine any potential mitigation required to operate at a higher temperature.
Total Cost ($USD)
$50,000
Allocated Cost ($USD)
$34,332
Time Estimate
36 to 48 Months

Contributor

FacilityContingency
05BANSTR-AG2-152 TP 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-152
80.4 MW68.7%$34,332
AG2-311
19.0 MW16.3%$8,132
AG2-541
8.6 MW7.3%$3,656
AH1-343
9.1 MW7.8%$3,881

System Reinforcement: n8423
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n8423 / dom-119
Title
Wreck and rebuild 0.06 miles of 115 kV line 1016 between Woodchuck Trail and Crystal Hill DP with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 0.06 miles of 115 kV line 1016 between Woodchuck Trail and Crystal Hill DP with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$192,000
Allocated Cost ($USD)
$28,653
Time Estimate
30 to 36 Months

Contributor

FacilityContingency
3CRSTL HILL-AC1-222 TAP 115.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-111
5.0 MW5.8%$11,057
AG2-112
5.3 MW6.0%$11,593
AG2-152
13.1 MW14.9%$28,653
AG2-311
6.1 MW7.0%$13,355
AG2-541
27.0 MW30.9%$59,308
AH1-343
31.0 MW35.4%$68,035

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEPAPRJV004
Title
Replace wavetrap @ New London
Description
Replace wavetrap @ New London
Total Cost ($USD)
$260,000
Allocated Cost ($USD)
$25,960
Time Estimate
18 to 24 Months

Contributor

FacilityContingency
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-111
4.7 MW7.1%$18,378
AG2-112
4.9 MW7.4%$19,267
AG2-152
6.6 MW10.0%$25,960
AG2-311
6.8 MW10.2%$26,550
AG2-541
20.9 MW31.7%$82,388
AH1-343
22.2 MW33.6%$87,457

System Reinforcement: b4000.211
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.211
Title
Rebuild 6.5 miles of Johnson Mountain - New London 138 kV line
Description
Rebuild 6.5 miles of Johnson Mountain - New London 138 kV line Projected In Service Date: 06/01/2029
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.210
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.210
Title
Rebuild 7 miles of Otter - Johnson Mountain 138 kV line.
Description
Rebuild 7 miles of Otter - Johnson Mountain 138 kV line.
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05JOHNMT-05OTTER 138.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.207
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.207
Title
Leesville Station Upgrade 138 kV
Description
Leesville Station Upgrade 138 kV: Replace 795 KCM AAC, 37-Str. IPS Sch. 40 1272 KCM AAC, 61-Str. 1272 KCM AAC, 61-Str. PH A,B,C ALTA VISTA CB-A BUS DISC ALTA VISTA CB-A LINE DISC Wavetrap (1200A) Relay Thermal Limit 1356 Amps
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line(Any)

System Reinforcement: n6594.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n6594.1 / AEPA0044a
Title
Rebuild 8.4 miles section of the Leesville - Alta Vista 138 kV line
Description
Rebuild 8.4 miles section of the Leesville - Alta Vista 138 kV line
Total Cost ($USD)
$23,571,948
Allocated Cost ($USD)
$0
Time Estimate
Nov 21 2027

Contingent

Note: Based on PJM cost allocation criteria, AG2-152 does not receive cost allocation towards this upgrade which has been securitized by a prior Queue/Cycle. Although AG2-152 may not have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable for the reliability to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending)
Title
Most limiting rating on the Dominion side is the Wave Trap and Lead at Altavista: 363 / 382 /420 MVA.
Description
Most limiting rating on the Dominion side is the Wave Trap and Lead at Altavista: 363 / 382 /420 MVA.
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
99 Months

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
05OTTER-4ALTVSTA 138.0 kV Ckt 1 line(Any)

System Reinforcement: n5613
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n5613 / AEPA0014a
Title
Rebuild 0.9 miles of the Otter - Alta Vista 138 kV line.
Description
Rebuild 0.9 miles of the Otter - Alta Vista 138 kV line.
Total Cost ($USD)
$2,740,849
Allocated Cost ($USD)
$0
Time Estimate
Nov 21 2027

Contingent

Note: Based on PJM cost allocation criteria, AG2-152 does not receive cost allocation towards this upgrade which has been securitized by a prior Queue/Cycle. Although AG2-152 may not have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable for the reliability to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05OTTER-4ALTVSTA 138.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2077
Title
Replace switches 29824 and 29825 at Bremo 230 kV
Description
Replace switches 29824 and 29825 at Bremo 230 kV
Total Cost ($USD)
$800,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-152 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-152 could receive cost allocation. Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 is a potential Aggregate Pool Contributor.

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2076
Title
Replace wave trap 298 WT at Bremo 230 kV
Description
Replace wave trap 298 WT at Bremo 230 kV
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-152 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-152 could receive cost allocation. Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 is a potential Aggregate Pool Contributor.

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2079
Title
Replace 3 1/2 " AL Pipe line lead on line 298 at Bremo 230 kV
Description
Replace 3 1/2 " AL Pipe line lead on line 298 at Bremo 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-152 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-152 could receive cost allocation. Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 is a potential Aggregate Pool Contributor.

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2078
Title
Replace 2-636 ACSR line lead on line 298 at Bremo 230 kV
Description
Replace 2-636 ACSR line lead on line 298 at Bremo 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-152 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-152 could receive cost allocation. Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 is a potential Aggregate Pool Contributor.

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9220.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9220.0 / TC1-PH2-DOM-033
Title
Wreck and rebuild 15.42 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 15.42 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Total Cost ($USD)
$44,465,922
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-152 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-152 could receive cost allocation. Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 is a potential Aggregate Pool Contributor.

FacilityContingency
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line(Any)
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9221.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9221.0 / TC1-PH3-DOM-015-TC2
Title
Replace 230 kV Breaker 29822 at Bremo with a higher-rated device (Buckingham - Bremo).
Description
Replace 230 kV Breaker 29822 at Bremo with a higher-rated device (Buckingham - Bremo).
Total Cost ($USD)
$2,057,335
Allocated Cost ($USD)
$0
Time Estimate
38 to 39 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-152 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-152 could receive cost allocation. Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 is a potential Aggregate Pool Contributor.

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9217.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9217.0 / TC1-PH2-DOM-028
Title
Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.
Total Cost ($USD)
$40,414,822
Allocated Cost ($USD)
$0
Time Estimate
45 to 46 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-152 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-152 could receive cost allocation. Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 is a potential Aggregate Pool Contributor.

FacilityContingency
6BUCKING-AH1-439 TP 230.0 kV Ckt 1 line(Any)
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line(Any)
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2086
Title
Replace 3 1/2' AL Pipe line lead on line 298 at Farmville 230 kV
Description
Replace 3 1/2' AL Pipe line lead on line 298 at Farmville 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-152 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-152 could receive cost allocation. Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 is a potential Aggregate Pool Contributor.

FacilityContingency
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2085
Title
Replace wavetrap 298WT at Farmville 230 kV
Description
Replace wavetrap 298WT at Farmville 230 kV
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$0
Time Estimate
16 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-152 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-152 could receive cost allocation. Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 is a potential Aggregate Pool Contributor.

FacilityContingency
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2087
Title
Replace 2-1590 AAC 61 line lead on line 298 at Farmville 230 kV
Description
Replace 2-1590 AAC 61 line lead on line 298 at Farmville 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-152 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-152 could receive cost allocation. Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 is a potential Aggregate Pool Contributor.

FacilityContingency
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.355
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line(Any)
8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line(Any)
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S

System Reinforcement: n9138.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9138.0 / TC1-PH1-DOM-070
Title
Wreck and rebuild 22.59 miles of Line #511 between Carson and Rawlings Substations with three (3) 1351 ACSS/TW and associated substation work.
Description
Wreck and rebuild 22.59 miles of Line 511 between Carson and Rawlings with three (3) 1351 ACSS/TW and associated substation work.
Total Cost ($USD)
$111,130,292
Allocated Cost ($USD)
$0
Time Estimate
60 to 61 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-152 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-152 could receive cost allocation. Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 is a potential Aggregate Pool Contributor.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S

System Reinforcement: n9250.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9250.0 / TC1-PH2-DOM-044
Title
Construct a new 22.59 mile line between Carson and Rawlings Substations.
Description
Construct a new 22.59 mile line between Carson and Rawlings Substations.
Total Cost ($USD)
$108,728,086
Allocated Cost ($USD)
$0
Time Estimate
60 to 61 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-152 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-152 could receive cost allocation. Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 is a potential Aggregate Pool Contributor.

FacilityContingency
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
          Perth 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-111, AG2-112
        
          AG2-068 500 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-068, AG2-069, AG2-369
        
          AG2-570 500 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-570, AG2-571
        
          AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-198, AG2-566
        
          AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-440, AG2-441, AG2-442
        

Attachments

AG2-152 One Line Diagram

AG2-152 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.