AG2-152 Phase I Study Report
v1.00 released 2025-10-29 21:17
Banister-Bear Skin 138 kV
79.0 MW Capacity / 131.0 MW Energy
Introduction
This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Virginia Electric and Power Company (d/b/a) Dominion Energy Virginia, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is American Electric Power.
Preface
The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.
In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
- PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
- PJM will only perform load flow analysis during the Phase I System Impact Study.
- In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
- PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
- The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
- Identify required Interconnection Facilities to accommodate the New Service Request.
- Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
- Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.
Decision Point I Requirements
At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.
Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.
General
The Project Developer has proposed a Solar generating facility located in the American Electric Power zone — Pittsylvania County, Virginia. The installed facilities will have a total capability of 131.0 MW with 79.0 MW of this output being recognized by PJM as Capacity.Project Information
Capacity Interconnection Rights (CIR) Transfer Details
This project intends to claim and transfer CIRs from the following Deactivation capacity generation resources. PJM performed a reliability analysis of the impacts to the system capability for the proposed transfer of CIRs from the Deactivation generation resources.
| Unit Name | Status | CIR Claimed | POI Transfer |
|---|---|---|---|
| Chesterfield 6 | Deactivated Generator | 52.0 | Yes |
| Yorktown 3 | Deactivated Generator | 27.0 | Yes |
Physical Interconnection Facility Study
Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.
Point of Interconnection
AG2-152 will interconnect on the American Electric Power transmission system tapping the Banister-Bear Skin 138 kV Line.
Cost Summary
The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.
Based on the Phase I SIS results, the AG2-152 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.
| Cost Summary | |||
|---|---|---|---|
| Description | Cost Allocated to AG2-152 | Cost Subject to Readiness* | |
| Transmission Owner Interconnection Facilities (TOIF) | $0 | $0 | |
| Other Scope | $0 | $0 | |
| Option To Build Oversight | $0 | $0 | |
| Physical Interconnection Network Upgrades | |||
| Stand Alone Network Upgrades | $18,578,995 | $18,578,995 | |
| Network Upgrades | $0 | $0 | |
| System Reliability Network Upgrades | |||
| Steady State Thermal & Voltage (SP & LL) | $20,522,088 | $20,522,088 | |
| Transient Stability | $0 | $0 | |
| Short Circuit | $0 | $0 | |
| Transmission Owner Analysis | |||
| SubRegional | $0 | $0 | |
| Distribution | $0 | $0 | |
| Affected System Reinforcements | |||
| AFS - PJM Violatons | $0 | $0 | |
| AFS - Non-PJM Violations | $0 | $0 | |
| Total | $39,101,083 | $39,101,083 | |
* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.
Definitions
Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.
Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.
Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.
Notes
Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.
Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.
Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.
Readiness Deposit
Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.
During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.
Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.
Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))
Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.
Readiness Deposit #2 Due for Project AG2-152
Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.
| Readiness Deposit | |||
|---|---|---|---|
| Project ID | 10% of cost allocation for Phase I Network Upgrades | Readiness Deposit #1 Received (RD1) | Readiness Deposit #2 (RD2) for AG2-152 Project due at DP1 |
| A | B | A - B | |
| AG2-152 | $3,910,108 | $524,000 | $3,386,108 |
Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.
For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.
Transmission Owner Scope of Work
The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.
| Stand-Alone Network Upgrades | |||
|---|---|---|---|
| RTEP ID | Description | Total Cost ($USD) | Allocated Cost ($USD) |
| (Pending) | AEP will construct a new breaker and a half station, initially populated with 3 breakers and operated as a ring bus as well as the associated facilities required to support the interconnection. | $18,578,995 | $18,578,995 |
Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 24 to 30 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.
The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.
Transmission Owner Analysis
No Transmission Owner impacts identified.
Developer Requirements
The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.
To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.
Revenue Metering and SCADA Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:Transmission Owner Requirements
- Temperature (degrees Fahrenheit)
- Atmospheric Pressure (hectopascals)
- Irradiance
- Forced outage data
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.
Summer Peak Analysis
The New Service Request AG2-152 was evaluated as a 131.0 MW (79.0 MW Capacity) injection in the AEP area.
AG2-152 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 131.0 MW (131.0 MW under study).
Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.
| Study | Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Final Cycle Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
|---|---|---|---|---|---|---|---|---|---|---|---|
| GD2 | AEP | 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line | AEP_P7-1_#10817___SRT-A | Tower | AC | 120.87 % | 388.0 | B | 468.97 | 80.42 | |
| GD2 | AEP | 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line | AEP_P4_#10213_05CLOVRD 138_A_SRT-A | Breaker | AC | 113.77 % | 388.0 | B | 441.43 | 78.33 | |
| GD2 | AEP | 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line | AEP_P4_#10210_05CLOVRD 138_A2_SRT-A | Breaker | AC | 113.52 % | 388.0 | B | 440.44 | 78.3 | |
| GD2 | AEP | 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line | AEP_P7-1_#10808___SRT-A | Tower | AC | 110.55 % | 388.0 | B | 428.94 | 80.44 | |
| GD2 | AEP | 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line | AEP_P2-2_#6213_05WLAKE 138_1_SRT-A | Bus | AC | 104.39 % | 388.0 | B | 405.03 | 75.88 | |
| GD2 | AEP | 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line | AEP_P2-2_#6212_05WLAKE 138_2_SRT-A | Bus | AC | 102.03 % | 388.0 | B | 395.89 | 75.88 | |
| GD2 | AEP/DVP | 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | AP_P1-3_MP-765-501T_SRT-A | Single | AC | 121.06 % | 3393.4 | B | 4107.97 | 12.36 | |
| GD2 | AEP/DVP | 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | AP_P2-3_MP-500-020_SRT-SL | Breaker | AC | 117.02 % | 3610.0 | B | 4224.55 | 17.64 | |
| GD2 | AEP/DVP | 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | AP_P2-3_MP-500-021_SRT-SL | Breaker | AC | 116.77 % | 3610.0 | B | 4215.43 | 17.63 | |
| GD2 | AEP/DVP | 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | AEP_P4_#37_05MOUNTN 765_B1_SRT-A | Breaker | AC | 116.68 % | 3610.0 | B | 4211.98 | 17.62 | |
| GD2 | AEP/DVP | 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | AEP_P4_#2942_05KAMMER 765_PP_SRT-A | Breaker | AC | 116.36 % | 3610.0 | B | 4200.43 | 17.63 | |
| GD2 | AEP | 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line | DVP_P4-2: 151T1047_SRT-A | Breaker | AC | 134.96 % | 245.0 | B | 330.65 | 6.6 | |
| GD2 | AEP | 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line | DVP_P4-2: 104702_SRT-A | Breaker | AC | 134.95 % | 245.0 | B | 330.63 | 6.6 | |
| GD2 | AEP | 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line | DVP_P4-2: 1016T1047_SRT-A | Breaker | AC | 128.07 % | 245.0 | B | 313.77 | 6.61 | |
| GD2 | AEP | 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line | DVP_P4-2: 101672_SRT-A | Breaker | AC | 128.05 % | 245.0 | B | 313.73 | 6.61 | |
| GD2 | AEP | 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line | DVP_P4-2: 104772_SRT-A | Breaker | AC | 126.62 % | 245.0 | B | 310.21 | 6.61 | |
| GD2 | AEP | 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line | DVP_P1-2: LN 1047_SRT-A | Single | AC | 106.29 % | 245.0 | B | 260.4 | 4.63 | |
| GD2 | AEP | 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line | DVP_P1-2: LN 1016_SRT-A-1 | Single | AC | 101.51 % | 245.0 | B | 248.71 | 4.64 | |
| GD2 | AEP | 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line | AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A | Bus | AC | 100.25 % | 245.0 | B | 245.61 | 13.8 | |
| GD2 | AEP | 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line | AEP_P7-1_#10778___SRT-A | Tower | AC | 100.25 % | 245.0 | B | 245.6 | 13.8 | |
| GD2 | AEP/DVP | 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | Base Case | Single | AC | 118.66 % | 192.7 | A | 228.66 | 6.85 | |
| GD2 | AEP/DVP | 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | AEP_P4_#10162_05EDAN 1 138_P_SRT-A | Breaker | AC | 117.03 % | 284.0 | B | 332.36 | 29.76 | |
| GD2 | AEP/DVP | 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | AEP_P4_#10164_05EDAN 2 138_M_SRT-A | Breaker | AC | 116.49 % | 284.0 | B | 330.82 | 29.65 | |
| GD2 | AEP/DVP | 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A | Bus | AC | 115.7 % | 284.0 | B | 328.58 | 29.65 | |
| GD2 | AEP/DVP | 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | AEP_P7-1_#10778___SRT-A | Tower | AC | 115.69 % | 284.0 | B | 328.56 | 29.65 | |
| GD2 | AEP/DVP | 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | AEP_P4_#10687_05EDAN 2 138_N_SRT-A | Breaker | AC | 115.68 % | 284.0 | B | 328.54 | 29.65 | |
| GD2 | AEP/DVP | 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | AEP_P4_#8676_05EDANV2 230_S_SRT-A | Breaker | AC | 115.67 % | 284.0 | B | 328.5 | 29.65 | |
| GD2 | AEP/DVP | 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | AEP_P1-2_#5366_SRT-A-1 | Single | AC | 110.86 % | 266.96 | B | 295.95 | 20.77 | |
| GD2 | AEP/DVP | 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | AEP_P1-3_#10688_05EDANV2 230_4_SRT-A | Single | AC | 110.35 % | 266.96 | B | 294.6 | 20.79 | |
| GD2 | AEP/DVP | 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | AEP_P4_#10213_05CLOVRD 138_A_SRT-A | Breaker | AC | 106.32 % | 284.0 | B | 301.96 | 13.56 | |
| IPD | AEP/DVP | 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | Base Case | Single | AC | 104.85 % | 192.7 | A | 202.04 | 11.36 | |
| IPD | AEP/DVP | 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | AEP_P1-2_#5366_SRT-A-1 | Single | AC | 102.26 % | 266.96 | B | 272.98 | 34.45 | |
| IPD | AEP/DVP | 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | AEP_P1-3_#10688_05EDANV2 230_4_SRT-A | Single | AC | 101.72 % | 266.96 | B | 271.56 | 34.48 | |
| GD2 | AEP/DVP | 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | AEP_P7-1_#10781___SRT-A-1 | Tower | AC | 100.01 % | 284.0 | B | 284.01 | 15.21 | |
| GD2 | AEP | 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line | AEP_P4_#10164_05EDAN 2 138_M_SRT-A | Breaker | AC | 112.15 % | 296.0 | B | 331.96 | 112.58 | |
| GD2 | AEP | 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line | AEP_P4_#10162_05EDAN 1 138_P_SRT-A | Breaker | AC | 109.26 % | 296.0 | B | 323.4 | 112.58 | |
| GD2 | AEP | 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line | AEP_P4_#8676_05EDANV2 230_S_SRT-A | Breaker | AC | 109.26 % | 296.0 | B | 323.4 | 112.58 | |
| GD2 | AEP | 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line | AEP_P4_#10687_05EDAN 2 138_N_SRT-A | Breaker | AC | 109.26 % | 296.0 | B | 323.4 | 112.58 | |
| GD2 | AEP | 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line | AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A | Bus | AC | 109.26 % | 296.0 | B | 323.4 | 112.58 | |
| GD2 | AEP | 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line | AEP_P7-1_#10778___SRT-A | Tower | AC | 109.26 % | 296.0 | B | 323.4 | 112.58 | |
| GD2 | AEP | 05OTTER-05JOHNMT 138.0 kV Ckt 1 line | DVP_P4-2: 151T1047_SRT-A | Breaker | AC | 136.34 % | 245.0 | B | 334.02 | 6.6 | |
| GD2 | AEP | 05OTTER-05JOHNMT 138.0 kV Ckt 1 line | DVP_P4-2: 104702_SRT-A | Breaker | AC | 136.33 % | 245.0 | B | 334.0 | 6.6 | |
| GD2 | AEP | 05OTTER-05JOHNMT 138.0 kV Ckt 1 line | DVP_P4-2: 1016T1047_SRT-A | Breaker | AC | 129.43 % | 245.0 | B | 317.11 | 6.61 | |
| GD2 | AEP | 05OTTER-05JOHNMT 138.0 kV Ckt 1 line | DVP_P4-2: 101672_SRT-A | Breaker | AC | 129.42 % | 245.0 | B | 317.07 | 6.61 | |
| GD2 | AEP | 05OTTER-05JOHNMT 138.0 kV Ckt 1 line | DVP_P4-2: 104772_SRT-A | Breaker | AC | 127.97 % | 245.0 | B | 313.53 | 6.61 | |
| GD2 | AEP | 05OTTER-05JOHNMT 138.0 kV Ckt 1 line | DVP_P1-2: LN 1047_SRT-A | Single | AC | 107.67 % | 245.0 | B | 263.78 | 4.63 | |
| GD2 | AEP | 05OTTER-05JOHNMT 138.0 kV Ckt 1 line | DVP_P1-2: LN 1016_SRT-A-1 | Single | AC | 102.87 % | 245.0 | B | 252.04 | 4.64 | |
| GD2 | AEP | 05OTTER-05JOHNMT 138.0 kV Ckt 1 line | AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A | Bus | AC | 101.55 % | 245.0 | B | 248.8 | 13.8 | |
| GD2 | AEP | 05OTTER-05JOHNMT 138.0 kV Ckt 1 line | AEP_P7-1_#10778___SRT-A | Tower | AC | 101.55 % | 245.0 | B | 248.79 | 13.8 | |
| GD2 | AEP | 05OTTER-05JOHNMT 138.0 kV Ckt 1 line | DVP_P2-2: ALTAVISTA 115KV_SRT-A | Bus | AC | 100.37 % | 245.0 | B | 245.9 | 7.55 | |
| GD2 | AEP | 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line | AEP_P4_#10162_05EDAN 1 138_P_SRT-A | Breaker | AC | 113.61 % | 255.0 | B | 289.71 | 29.79 | |
| GD2 | AEP | 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line | AEP_P4_#10164_05EDAN 2 138_M_SRT-A | Breaker | AC | 113.02 % | 255.0 | B | 288.2 | 29.68 | |
| GD2 | AEP | 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line | AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A | Bus | AC | 112.15 % | 255.0 | B | 285.97 | 29.68 | |
| GD2 | AEP | 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line | AEP_P7-1_#10778___SRT-A | Tower | AC | 112.13 % | 255.0 | B | 285.94 | 29.68 | |
| GD2 | AEP | 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line | AEP_P4_#10687_05EDAN 2 138_N_SRT-A | Breaker | AC | 112.13 % | 255.0 | B | 285.92 | 29.68 | |
| GD2 | AEP | 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line | AEP_P4_#8676_05EDANV2 230_S_SRT-A | Breaker | AC | 112.11 % | 255.0 | B | 285.89 | 29.68 | |
| GD2 | AEP | 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line | AEP_P4_#10213_05CLOVRD 138_A_SRT-A | Breaker | AC | 101.78 % | 255.0 | B | 259.55 | 13.59 | |
| GD2 | DVP | 3CRSTL HILL-AC1-222 TAP 115.0 kV Ckt 1 line | AEP_P4_#10162_05EDAN 1 138_P_SRT-A | Breaker | AC | 100.59 % | 350.0 | C | 352.07 | 13.06 | |
| GD2 | DVP | 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line | AEP_P4_#10162_05EDAN 1 138_P_SRT-A | Breaker | AC | 111.45 % | 350.0 | C | 390.08 | 13.03 | |
| GD2 | DVP | 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line | AEP_P4_#10164_05EDAN 2 138_M_SRT-A | Breaker | AC | 109.96 % | 350.0 | C | 384.85 | 12.85 | |
| GD2 | DVP | 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line | AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A | Bus | AC | 109.7 % | 350.0 | C | 383.94 | 12.85 | |
| GD2 | DVP | 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line | AEP_P7-1_#10778___SRT-A | Tower | AC | 109.69 % | 350.0 | C | 383.92 | 12.85 | |
| GD2 | DVP | 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line | AEP_P1-3_#10688_05EDANV2 230_4_SRT-A | Single | AC | 106.4 % | 285.76 | B | 304.05 | 9.01 | |
| GD2 | DVP | 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line | AEP_P1-2_#5366_SRT-A-1 | Single | AC | 106.21 % | 285.76 | B | 303.5 | 8.98 | |
| GD2 | DVP | 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line | AEP_P7-1_#10781___SRT-A-1 | Tower | AC | 102.7 % | 350.0 | C | 359.46 | 7.33 | |
| GD2 | AEP/DVP | 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line | DVP_P4-2: 151T1047_SRT-A | Breaker | AC | 137.18 % | 245.0 | B | 336.08 | 6.6 | |
| GD2 | AEP/DVP | 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line | DVP_P4-2: 104702_SRT-A | Breaker | AC | 137.17 % | 245.0 | B | 336.06 | 6.6 | |
| GD2 | AEP/DVP | 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line | DVP_P4-2: 1016T1047_SRT-A | Breaker | AC | 130.26 % | 245.0 | B | 319.14 | 6.61 | |
| GD2 | AEP/DVP | 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line | DVP_P4-2: 101672_SRT-A | Breaker | AC | 130.24 % | 245.0 | B | 319.1 | 6.61 | |
| GD2 | AEP/DVP | 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line | DVP_P4-2: 104772_SRT-A | Breaker | AC | 128.8 % | 245.0 | B | 315.55 | 6.61 | |
| GD2 | AEP/DVP | 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line | DVP_P1-2: LN 1047_SRT-A | Single | AC | 115.43 % | 230.3 | B | 265.84 | 4.63 | |
| GD2 | AEP/DVP | 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line | DVP_P1-2: LN 1016_SRT-A-1 | Single | AC | 110.32 % | 230.3 | B | 254.07 | 4.64 | |
| GD2 | AEP/DVP | 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line | AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A | Bus | AC | 102.33 % | 245.0 | B | 250.71 | 13.8 | |
| GD2 | AEP/DVP | 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line | AEP_P7-1_#10778___SRT-A | Tower | AC | 102.33 % | 245.0 | B | 250.7 | 13.8 | |
| GD2 | AEP/DVP | 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line | DVP_P2-2: ALTAVISTA 115KV_SRT-A | Bus | AC | 101.22 % | 245.0 | B | 247.98 | 7.55 | |
| GD2 | DVP | 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line | DVP_P4-2: 511T556_SRT-S | Breaker | AC | 212.98 % | 699.0 | C | 1488.76 | 5.77 | |
| GD2 | DVP | 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line | DVP_P4-2: 587T591_SRT-S | Breaker | AC | 212.93 % | 699.0 | C | 1488.37 | 5.77 | |
| GD2 | DVP | 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line | DVP_P4-2: 55692_SRT-S | Breaker | AC | 209.35 % | 699.0 | C | 1463.37 | 5.68 | |
| GD2 | DVP | 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line | DVP_P1-2: LN 587_SRT-A-3 | Single | AC | 207.29 % | 571.52 | B | 1184.7 | 3.98 | |
| GD2 | DVP | 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line | DVP_P1-2: LN 593_SRT-A | Single | AC | 204.76 % | 571.52 | B | 1170.27 | 3.98 | |
| GD2 | DVP | 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line | DVP_P4-2: H2T593_SRT-A | Breaker | AC | 203.45 % | 699.0 | C | 1422.11 | 5.68 | |
| GD2 | DVP | 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line | DVP_P4-2: H1T593_SRT-A | Breaker | AC | 203.45 % | 699.0 | C | 1422.11 | 5.68 | |
| GD2 | DVP | 6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line | DVP_P4-2: 509T570_SRT-A | Breaker | AC | 114.83 % | 997.0 | C | 1144.9 | 13.36 | |
| GD2 | DVP | 6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line | DVP_P1-2: LN 570_SRT-A-3 | Single | AC | 108.64 % | 814.98 | B | 885.41 | 9.44 | |
| GD2 | DVP | 6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line | DVP_P1-2: LN 570_SRT-A-2 | Single | AC | 106.47 % | 814.98 | B | 867.67 | 9.44 | |
| GD2 | DVP | 6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line | DVP_P4-2: 57062_SRT-S | Breaker | AC | 100.2 % | 997.0 | C | 998.97 | 13.46 | |
| GD2 | DVP | 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line | DVP_P4-2: 511T556_SRT-S | Breaker | AC | 201.24 % | 684.0 | C | 1376.51 | 5.79 | |
| GD2 | DVP | 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line | DVP_P4-2: 587T591_SRT-S | Breaker | AC | 201.19 % | 684.0 | C | 1376.13 | 5.79 | |
| GD2 | DVP | 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line | DVP_P4-2: 55692_SRT-S | Breaker | AC | 197.56 % | 684.0 | C | 1351.34 | 5.7 | |
| GD2 | DVP | 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line | DVP_P1-2: LN 587_SRT-A-3 | Single | AC | 195.93 % | 559.3 | B | 1095.86 | 4.0 | |
| GD2 | DVP | 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line | DVP_P1-2: LN 593_SRT-A | Single | AC | 193.37 % | 559.3 | B | 1081.51 | 4.0 | |
| GD2 | DVP | 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line | DVP_P4-2: H2T593_SRT-A | Breaker | AC | 191.54 % | 684.0 | C | 1310.12 | 5.7 | |
| GD2 | DVP | 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line | DVP_P4-2: H1T593_SRT-A | Breaker | AC | 191.54 % | 684.0 | C | 1310.12 | 5.7 | |
| GD2 | CPLE/DVP | 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line | DVP_P1-2: LN 570_SRT-A-3 | Single | AC | 182.88 % | 508.54 | B | 930.03 | 8.89 | |
| GD2 | CPLE/DVP | 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line | DVP_P1-2: LN 570_SRT-A-2 | Single | AC | 178.67 % | 508.54 | B | 908.59 | 8.89 | |
| GD2 | DVP | 6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line | DVP_P4-2: 509T570_SRT-A | Breaker | AC | 109.79 % | 997.0 | C | 1094.57 | 13.39 | |
| GD2 | DVP | 6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line | DVP_P1-2: LN 570_SRT-A-3 | Single | AC | 103.53 % | 814.98 | B | 843.75 | 9.46 | |
| GD2 | DVP | 6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line | DVP_P1-2: LN 570_SRT-A-2 | Single | AC | 101.35 % | 814.98 | B | 825.97 | 9.46 | |
| GD2 | DVP | 8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line | DVP_P1-2: LN 555_SRT-A | Single | AC | 112.33 % | 3220.44 | B | 3617.39 | 8.2 | |
| GD2 | DVP | 8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line | DVP_P7-1: LN 2168-555_SRT-A | Tower | AC | 105.49 % | 3940.0 | C | 4156.4 | 12.91 | |
| GD2 | DVP | 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line | DVP_P1-2: LN 585_SRT-A-1 | Single | AC | 139.73 % | 4070.2 | B | 5687.33 | 12.91 | |
| GD2 | DVP | 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line | DVP_P1-2: LN 585_SRT-A-2 | Single | AC | 133.78 % | 4070.2 | B | 5445.28 | 12.91 | |
| GD2 | DVP | 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line | DVP_P4-2: 58572_SRT-A | Breaker | AC | 124.04 % | 4996.0 | C | 6196.95 | 18.41 | |
| GD2 | DVP | 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line | DVP_P4-5: W72_SRT-A | Breaker | AC | 123.43 % | 4996.0 | C | 6166.56 | 18.35 | |
| GD2 | DVP | 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line | DVP_P4-2: XT585_SRT-S | Breaker | AC | 114.16 % | 4996.0 | C | 5703.66 | 18.41 | |
| GD2 | DVP | 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line | DVP_P4-2: 54472_SRT-S | Breaker | AC | 111.74 % | 2858.0 | C | 3193.49 | 11.34 | |
| GD2 | DVP | 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line | DVP_P1-2: LN 511_SRT-S | Single | AC | 123.06 % | 4070.2 | B | 5008.65 | 12.09 | |
| GD2 | DVP | 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line | DVP_P4-2: 51192_SRT-S | Breaker | AC | 109.25 % | 4996.0 | C | 5458.06 | 17.25 | |
| GD2 | DVP | 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line | DVP_P4-2: 51172_SRT-S | Breaker | AC | 108.79 % | 4996.0 | C | 5435.07 | 17.2 | |
| GD2 | DVP | 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line | DVP_P4-2: 511T544_SRT-S | Breaker | AC | 107.19 % | 4996.0 | C | 5355.19 | 17.06 | |
| GD2 | DVP | 8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line | DVP_P1-2: LN 555_SRT-A | Single | AC | 112.01 % | 3220.44 | B | 3607.13 | 8.2 | |
| GD2 | DVP | 8VALLEY SC-8VALLEY 500.0 kV Ckt 1 line | DVP_P7-1: LN 2168-555_SRT-A | Tower | AC | 105.23 % | 3940.0 | C | 4145.88 | 12.91 | |
| GD2 | DVP | AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line | AEP_P4_#10162_05EDAN 1 138_P_SRT-A | Breaker | AC | 113.44 % | 350.0 | C | 397.05 | 13.03 | |
| GD2 | DVP | AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line | AEP_P4_#10164_05EDAN 2 138_M_SRT-A | Breaker | AC | 111.95 % | 350.0 | C | 391.83 | 12.85 | |
| GD2 | DVP | AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line | AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A | Bus | AC | 111.69 % | 350.0 | C | 390.93 | 12.85 | |
| GD2 | DVP | AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line | AEP_P7-1_#10778___SRT-A | Tower | AC | 111.69 % | 350.0 | C | 390.91 | 12.85 | |
| GD2 | DVP | AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line | AEP_P1-3_#10688_05EDANV2 230_4_SRT-A | Single | AC | 108.84 % | 285.76 | B | 311.03 | 9.01 | |
| GD2 | DVP | AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line | AEP_P1-2_#5366_SRT-A-1 | Single | AC | 108.65 % | 285.76 | B | 310.48 | 8.98 | |
| GD2 | DVP | AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line | AEP_P7-1_#10781___SRT-A-1 | Tower | AC | 104.72 % | 350.0 | C | 366.51 | 7.33 | |
| GD2 | DVP | AE2-094 TP-8CARSON 500.0 kV Ckt 1 line | DVP_P1-2: LN 511_SRT-S | Single | AC | 136.1 % | 4070.2 | B | 5539.41 | 12.09 | |
| GD2 | DVP | AE2-094 TP-8CARSON 500.0 kV Ckt 1 line | DVP_P4-2: 51192_SRT-S | Breaker | AC | 120.36 % | 4996.0 | C | 6013.11 | 17.25 | |
| GD2 | DVP | AE2-094 TP-8CARSON 500.0 kV Ckt 1 line | DVP_P4-2: 51172_SRT-S | Breaker | AC | 119.82 % | 4996.0 | C | 5986.29 | 17.2 | |
| GD2 | DVP | AE2-094 TP-8CARSON 500.0 kV Ckt 1 line | DVP_P4-2: 511T544_SRT-S | Breaker | AC | 118.15 % | 4996.0 | C | 5902.9 | 17.06 | |
| GD2 | AEP | AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line | AEP_P7-1_#10817___SRT-A | Tower | AC | 121.83 % | 392.0 | B | 477.57 | 80.42 | |
| GD2 | AEP | AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line | AEP_P4_#10213_05CLOVRD 138_A_SRT-A | Breaker | AC | 114.79 % | 392.0 | B | 450.0 | 78.33 | |
| GD2 | AEP | AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line | AEP_P4_#10210_05CLOVRD 138_A2_SRT-A | Breaker | AC | 114.54 % | 392.0 | B | 449.01 | 78.3 | |
| GD2 | AEP | AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line | AEP_P7-1_#10808___SRT-A | Tower | AC | 111.62 % | 392.0 | B | 437.54 | 80.44 | |
| GD2 | AEP | AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line | AEP_P2-2_#6213_05WLAKE 138_1_SRT-A | Bus | AC | 105.51 % | 392.0 | B | 413.6 | 75.88 | |
| GD2 | AEP | AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line | AEP_P2-2_#6212_05WLAKE 138_2_SRT-A | Bus | AC | 103.18 % | 392.0 | B | 404.45 | 75.88 | |
| IPD | AEP | AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line | AEP_P7-1_#10817___SRT-A | Tower | AC | 100.63 % | 392.0 | B | 394.45 | 93.51 | |
| GD2 | DVP | AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line | DVP_P4-2: 511T556_SRT-S | Breaker | AC | 211.67 % | 684.0 | C | 1447.79 | 5.79 | |
| GD2 | DVP | AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line | DVP_P4-2: 587T591_SRT-S | Breaker | AC | 211.61 % | 684.0 | C | 1447.4 | 5.79 | |
| GD2 | DVP | AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line | DVP_P4-2: 55692_SRT-S | Breaker | AC | 207.99 % | 684.0 | C | 1422.62 | 5.7 | |
| GD2 | DVP | AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line | DVP_P1-2: LN 587_SRT-A-3 | Single | AC | 206.17 % | 559.3 | B | 1153.12 | 4.0 | |
| GD2 | DVP | AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line | DVP_P1-2: LN 593_SRT-A | Single | AC | 203.59 % | 559.3 | B | 1138.68 | 4.0 | |
| GD2 | DVP | AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line | DVP_P4-2: H2T593_SRT-A | Breaker | AC | 201.95 % | 684.0 | C | 1381.35 | 5.7 | |
| GD2 | DVP | AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line | DVP_P4-2: H1T593_SRT-A | Breaker | AC | 201.95 % | 684.0 | C | 1381.35 | 5.7 | |
| GD2 | DVP | AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P1-2: LN 511_SRT-S | Single | AC | 129.2 % | 4070.2 | B | 5258.72 | 12.09 | |
| GD2 | DVP | AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P4-2: 51192_SRT-S | Breaker | AC | 114.25 % | 4996.0 | C | 5708.12 | 17.25 | |
| GD2 | DVP | AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P4-2: 51172_SRT-S | Breaker | AC | 113.76 % | 4996.0 | C | 5683.44 | 17.2 | |
| GD2 | DVP | AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P4-2: 511T544_SRT-S | Breaker | AC | 112.13 % | 4996.0 | C | 5601.8 | 17.06 | |
| GD2 | DVP | AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line | AEP_P4_#10162_05EDAN 1 138_P_SRT-A | Breaker | AC | 103.04 % | 350.0 | C | 360.64 | 13.06 | |
| GD2 | DVP | AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line | AEP_P4_#10164_05EDAN 2 138_M_SRT-A | Breaker | AC | 101.53 % | 350.0 | C | 355.37 | 12.87 | |
| GD2 | DVP | AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line | AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A | Bus | AC | 101.27 % | 350.0 | C | 354.46 | 12.87 | |
| GD2 | DVP | AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line | AEP_P7-1_#10778___SRT-A | Tower | AC | 101.27 % | 350.0 | C | 354.44 | 12.87 | |
| GD2 | DVP | AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line | DVP_P4-2: 511T556_SRT-S | Breaker | AC | 218.2 % | 684.0 | C | 1492.5 | 5.79 | |
| GD2 | DVP | AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line | DVP_P4-2: 587T591_SRT-S | Breaker | AC | 218.14 % | 684.0 | C | 1492.11 | 5.79 | |
| GD2 | DVP | AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line | DVP_P4-2: 55692_SRT-S | Breaker | AC | 214.52 % | 684.0 | C | 1467.34 | 5.7 | |
| GD2 | DVP | AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line | DVP_P1-2: LN 587_SRT-A-3 | Single | AC | 212.24 % | 559.3 | B | 1187.04 | 4.0 | |
| GD2 | DVP | AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line | DVP_P1-2: LN 593_SRT-A | Single | AC | 209.65 % | 559.3 | B | 1172.59 | 4.0 | |
| GD2 | DVP | AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line | DVP_P4-2: H2T593_SRT-A | Breaker | AC | 208.48 % | 684.0 | C | 1426.03 | 5.7 | |
| GD2 | DVP | AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line | DVP_P4-2: H1T593_SRT-A | Breaker | AC | 208.48 % | 684.0 | C | 1426.03 | 5.7 | |
| GD2 | DVP | AH1-546 TP-6BREMO 230.0 kV Ckt 1 line | DVP_P4-2: 511T556_SRT-S | Breaker | AC | 219.98 % | 699.0 | C | 1537.65 | 5.77 | |
| GD2 | DVP | AH1-546 TP-6BREMO 230.0 kV Ckt 1 line | DVP_P4-2: 587T591_SRT-S | Breaker | AC | 219.92 % | 699.0 | C | 1537.26 | 5.77 | |
| GD2 | DVP | AH1-546 TP-6BREMO 230.0 kV Ckt 1 line | DVP_P4-2: 55692_SRT-S | Breaker | AC | 216.35 % | 699.0 | C | 1512.31 | 5.68 | |
| GD2 | DVP | AH1-546 TP-6BREMO 230.0 kV Ckt 1 line | DVP_P1-2: LN 587_SRT-A-3 | Single | AC | 213.74 % | 571.52 | B | 1221.6 | 3.98 | |
| GD2 | DVP | AH1-546 TP-6BREMO 230.0 kV Ckt 1 line | DVP_P1-2: LN 593_SRT-A | Single | AC | 211.19 % | 571.52 | B | 1206.97 | 3.98 | |
| GD2 | DVP | AH1-546 TP-6BREMO 230.0 kV Ckt 1 line | DVP_P4-2: H1T593_SRT-A | Breaker | AC | 210.43 % | 699.0 | C | 1470.9 | 5.68 | |
| GD2 | DVP | AH1-546 TP-6BREMO 230.0 kV Ckt 1 line | DVP_P4-2: H2T593_SRT-A | Breaker | AC | 210.43 % | 699.0 | C | 1470.9 | 5.68 |
Winter Peak Analysis
The New Service Request AG2-152 was evaluated as a 131.0 MW (79.0 MW Capacity) injection in the AEP area.
AG2-152 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 131.0 MW (131.0 MW under study).
Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.
| Study | Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Final Cycle Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
|---|---|---|---|---|---|---|---|---|---|---|---|
| GD2 | AEP/DVP | 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | AEP_P1-2_#3174_6_SRT-A | Single | AC | 101.09 % | 304.56 | B | 307.89 | 0.49 | |
| GD2 | AEP/DVP | 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | AEP_P1-3_#1372_05JOSHUA 765_1_SRT-A | Single | AC | 100.99 % | 304.56 | B | 307.57 | 0.49 | |
| GD2 | CPLE/DVP | 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line | DVP_P4-2: 509T570_SRT-A | Breaker | AC | 143.28 % | 694.0 | B | 994.38 | 0.73 | |
| GD2 | CPLE/DVP | 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line | DVP_P1-2: LN 570_SRT-A-3 | Single | AC | 136.4 % | 652.36 | B | 889.84 | 0.74 | |
| GD2 | CPLE/DVP | 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line | DVP_P1-2: LN 570_SRT-A-2 | Single | AC | 134.99 % | 652.36 | B | 880.62 | 0.74 | |
| GD2 | CPLE/DVP | 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line | DVP_P4-2: 57062_SRT-W | Breaker | AC | 130.48 % | 694.0 | B | 905.5 | 0.74 | |
| IPD | CPLE/DVP | 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line | DVP_P4-2: 509T570_SRT-A | Breaker | AC | 107.4 % | 694.0 | B | 745.32 | 14.7 | |
| GD2 | CPLE/DVP | 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line | DVP_P4-2: 59162_SRT-W | Breaker | AC | 104.06 % | 694.0 | B | 722.2 | 0.56 | |
| GD2 | CPLE/DVP | 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line | DVP_P4-2: XT591_SRT-W | Breaker | AC | 104.06 % | 694.0 | B | 722.2 | 0.56 | |
| GD2 | CPLE/DVP | 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line | DVP_P4-2: 59192-1_SRT-W | Breaker | AC | 104.05 % | 694.0 | B | 722.14 | 0.56 |
Light Load Analysis
The New Service Request AG2-152 was evaluated as a 131.0 MW injection
AG2-152 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 131.0 MW (131.0 MW under study).
Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.
| Study | Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Final Cycle Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
|---|---|---|---|---|---|---|---|---|---|---|---|
| GD2 | AEP | 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line | AEP_P1-2_#311_5_SRT-A | Single | AC | 125.64 % | 296.0 | B | 371.9 | 24.01 | |
| GD2 | AEP | 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line | AEP_P4_#7587_05J.FERR 765_B_SRT-A | Breaker | AC | 123.54 % | 296.0 | B | 365.69 | 24.0 | |
| GD2 | AEP | 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line | AEP_P4_#2914_05J.FERR 765_B2_SRT-A | Breaker | AC | 123.21 % | 296.0 | B | 364.71 | 24.01 | |
| GD2 | AEP | 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line | AEP_P7-1_#10781___SRT-A-3 | Tower | AC | 103.45 % | 296.0 | B | 306.2 | 34.32 | |
| IPD | AEP | 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line | AEP_P4_#7587_05J.FERR 765_B_SRT-A | Breaker | AC | 103.11 % | 296.0 | B | 305.2 | 43.64 | |
| IPD | AEP | 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line | AEP_P4_#2914_05J.FERR 765_B2_SRT-A | Breaker | AC | 102.86 % | 296.0 | B | 304.46 | 43.65 | |
| IPD | AEP | 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line | AEP_P1-2_#311_5_SRT-A | Single | AC | 102.85 % | 296.0 | B | 304.45 | 43.65 | |
| IPD | AEP | 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line | AEP_P4_#311_05CLOVRD 765_CC2_SRT-A | Breaker | AC | 102.85 % | 296.0 | B | 304.45 | 43.65 | |
| GD2 | CPLE/DVP | 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line | DVP_P4-2: 509T570_SRT-A | Breaker | AC | 109.87 % | 541.0 | B | 594.42 | 8.16 |
Short Circuit Analysis
Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.
Stability Analysis
Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.
Reactive Power Analysis
Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.
Steady-State Voltage Analysis
Steady State Voltage Analysis is Not Required.
New Service Request Dependencies
The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.
| New Service Requests Dependencies | ||
|---|---|---|
| Project ID | Project Name | Status |
| AA1-018 | Powerton-Goodings Grove | In Service |
| AA1-038 | Lexington-Low Moor 230kV | Under Construction |
| AA1-050 | Tarboro-Everetts 230kV | In Service |
| AA1-063A | Carolina–Seaboard 115kV | In Service |
| AA1-067 | Everetts 34.5kV | In Service |
| AA1-095 | Halfway-Marlowe 34.5kV | In Service |
| AA1-139 | Hickory-Shawboro 230kV | In Service |
| AA2-053 | Carolina-Jackson 115kV | In Service |
| AA2-057 | Hornertown-Whitakers 115kV | In Service |
| AA2-174 | Carolina-Jackson 115kV | In Service |
| AA2-178 | Mackeys 230kV | In Service |
| AB1-001 | Absecon 12 kV | In Service |
| AB1-006 | Meadow Lake 345kV | In Service |
| AB1-027 | Old Church 34.5 KV | In Service |
| AB1-081 | Anaconda-Mayo Dunbar 115kV | In Service |
| AB1-096 | Carroll-Mt. Airy 34.5kV | In Service |
| AB1-124 | Carroll-Monocacy 34.5kV | Partially in Service - Under Construction |
| AB1-125 | Carroll-Monocacy 34.5kV | In Service |
| AB1-127 | St. Thomas-Guilford 34.5kV | In Service |
| AB1-128 | St. Thomas-Mercersburg 34.5kV | In Service |
| AB1-132 | Thelma 230kV | In Service |
| AB1-141 | Church-Wye Mills 138 kV I | In Service |
| AB1-142 | Church-Wye Mills 138 kV II | In Service |
| AB1-176 | Price 25kV II | Engineering & Procurement |
| AB1-180 | Pine View 12kV | In Service |
| AB2-022 | Elizabeth City 34.5kV | In Service |
| AB2-024 | Correctional 34.5kV | In Service |
| AB2-025 | Sapony 34.5kV | In Service |
| AB2-026 | Powhatan 34.5kV | In Service |
| AB2-029 | Remington 34.5kV | In Service |
| AB2-031 | Brink-Trego 115kV | In Service |
| AB2-032 | Church-Wye Mills 138 kV | In Service |
| AB2-037 | Keeney-Steele 230kV | Under Construction |
| AB2-040 | Brink 115kV | In Service |
| AB2-043 | Chase City 115kV | In Service |
| AB2-045 | Buckingham 34.5kV | In Service |
| AB2-049 | Gloucester Township 12kV | In Service |
| AB2-059 | Benson-Dunbar 115kV | In Service |
| AB2-060 | Chase City-Lunenburg 115kV | In Service |
| AB2-070 | Mt. Pulaski-Brokaw | In Service |
| AB2-077 | Buggs Island-Chase City 115kV | In Service |
| AB2-078 | Buggs Island-Chase City 115kV | In Service |
| AB2-079 | Buggs Island-Chase City 115kV | In Service |
| AB2-099 | Ahoskie 34.5kV | In Service |
| AB2-133 | Chestertown 69kV | Under Construction |
| AB2-134 | Hopewell-Surry 230kV | In Service |
| AB2-135 | Church-Kent 69kV | In Service |
| AB2-136 | Cambridge-West Cambridge 69kV | Under Construction |
| AB2-153 | Church-Wye Mills 138 kV | In Service |
| AB2-157 | Prince George's County 12kV | In Service |
| AB2-158 | Louisa-South Anna 230kV | In Service |
| AB2-161 | Waverly #2 DP 115kV | In Service |
| AB2-169 | Pantago-Five Points 115kV | In Service |
| AB2-174 | Emporia-Trego 115kV | In Service |
| AB2-179 | Townsend 138kV | In Service |
| AB2-190 | Hopewell-Surry 230kV | In Service |
| AC1-001 | Delano 138kV | In Service |
| AC1-010 | Gloucester 26kV | Under Construction |
| AC1-027 | Pendleton 34.5kV | In Service |
| AC1-030 | Cinnaminson 13kV | In Service |
| AC1-033 | Kewanee 138 kV | In Service |
| AC1-034 | Heartsease DP - Mayo Dunbar 115kV | Suspended |
| AC1-036 | Twittys Creek 34.5kV | In Service |
| AC1-042 | Altavista-Mt. Airy 69kV | In Service |
| AC1-053 | Lanesville-Brokaw | Partially in Service - Under Construction |
| AC1-054 | Kerr Dam–Eatons Ferry 115 kV | In Service |
| AC1-074 | Jacksonville-Renaker 138kV I | In Service |
| AC1-075 | Perth-Hickory Grove 115kV | In Service |
| AC1-076 | Locust Grove-Paytes 115kV | In Service |
| AC1-082 | Ravenswood-Hemlock 69kV | Under Construction |
| AC1-085 | Stuart-Clinton 345kV | In Service |
| AC1-086 | Thelma 230kV | Suspended |
| AC1-089 | Hillsboro-Wildcat 138kV | In Service |
| AC1-091 | Cedar Creek 138kV I | Engineering & Procurement |
| AC1-092 | Cedar Creek 138kV II | Engineering & Procurement |
| AC1-093 | Cedar Creek 138kV III | Engineering & Procurement |
| AC1-094 | Cedar Creek 138kV IV | Engineering & Procurement |
| AC1-098 | Dawson-South Justice 115kV | Partially in Service - Under Construction |
| AC1-099 | Dawson-South Justice 115kV | Partially in Service - Under Construction |
| AC1-101 | Johns Creek-Excel 138kV I | Suspended |
| AC1-102 | Johns Creek-Excel 138kV II | Suspended |
| AC1-105 | Halifax-Mt. Laurel 115kV | In Service |
| AC1-111 | Aurora 138kV | In Service |
| AC1-118 | Westmoreland 34.5kV | In Service |
| AC1-120 | Mitchell-Mountain Run 115kV | Engineering & Procurement |
| AC1-121 | Mitchell-Mountain Run 115kV | Engineering & Procurement |
| AC1-122 | Smith Mountain-Candler's Mountain 138kV | In Service |
| AC1-145 | Gretna DP 69 kV | In Service |
| AC1-147 | Grassfield 34.5kV | In Service |
| AC1-158 | Spotsylvania 500kV | In Service |
| AC1-161 | Septa 500kV | In Service |
| AC1-164 | Chickahominy 230kV | Partially in Service - Under Construction |
| AC1-168 | Kewanee-Streator | Suspended |
| AC1-174 | Losantville 345kV | In Service |
| AC1-175 | Losantville 345kV | In Service |
| AC1-188 | Rio-Lick 138kV | Engineering & Procurement |
| AC1-189 | Chinquapin-Everetts 230kV | Under Construction |
| AC1-191 | Elmont 115kV | Engineering & Procurement |
| AC1-194 | Elk 138kV | Active |
| AC1-208 | Cox-Whitakers 115kV | Under Construction |
| AC1-214 | Crescent Ridge | In Service |
| AC1-221 | Halifax-Person 230kV | In Service |
| AC1-222 | Crystal Hill-Halifax 115kV | In Service |
| AC2-012 | Grassfield-Great Bridge 115kV | In Service |
| AC2-023 | Hebron 69kV | Engineering & Procurement |
| AC2-060 | Buckskin 69kV | In Service |
| AC2-061 | Hillsboro-Clinton 138kV | In Service |
| AC2-075 | Jacksonville-Renaker 138 kV | In Service |
| AC2-079 | Ivor-Oak Ridge 115kV | Suspended |
| AC2-088 | S. Bethel-Brown 69kV | In Service |
| AC2-090 | Losantville 345kV | In Service |
| AC2-100 | Halifax-Person 230kV | In Service |
| AC2-111 | College Corner 138kV | Engineering & Procurement |
| AC2-120 | Ripley 69kV | In Service |
| AC2-123 | Jacksons Ferry 138kV | In Service |
| AC2-136 | East Hagerstown 12kV | Under Construction |
| AC2-137 | Elko 34.5kV | In Service |
| AC2-138 | Northern Neck 34.5kV | In Service |
| AC2-141 | Septa 500kV | Engineering & Procurement |
| AC2-157 | Sullivan 345 kV | Under Construction |
| AC2-165 | Bremo-Powhatan 230kV | Suspended |
| AC2-186 | Harrington 25kV | Under Construction |
| AC2-187 | Harrington 69kV | Under Construction |
| AC2-188 | Harrington 69 kV | Under Construction |
| AD1-013 | Twombly Road 138kV | Engineering & Procurement |
| AD1-017 | Smith Mountain-Bearskin 138 kV | In Service |
| AD1-020 | Hunterstown-Lincoln 115 kV | In Service |
| AD1-022 | Cashie-Trowbridge 230 kV | Engineering & Procurement |
| AD1-025 | Hopewell-Surry 230 kV | Under Construction |
| AD1-033 | Fentress-Landstown 230 kV | In Service |
| AD1-041 | Harmony Village-Shackleford 115 kV | In Service |
| AD1-056 | Hornertown-Hathaway 230 kV | Suspended |
| AD1-057 | Hornertown-Hathaway 230 kV | Suspended |
| AD1-060 | Mercersburg-Milnor 34.5 kV | In Service |
| AD1-061 | McConnelsburg-Mercersburg 34 kV | In Service |
| AD1-063 | Harmony Village 34.5 kV | In Service |
| AD1-074 | Trowbridge 230 kV | Engineering & Procurement |
| AD1-075 | Trowbridge 230 kV | Engineering & Procurement |
| AD1-076 | Trowbridge 230 kV | Engineering & Procurement |
| AD1-082 | Bakers Pond-Ivor 115kV | In Service |
| AD1-087 | Clover-Sedge Hill 230 kV | In Service |
| AD1-088 | Briery-Clover 230 kV | Suspended |
| AD1-105 | Kings Dominion DP 115 kV | Under Construction |
| AD1-115 | Mountain Run-Mitchell 115 kV | Engineering & Procurement |
| AD1-128 | Modoc-Delaware 138 kV | Partially in Service - Under Construction |
| AD1-136 | South Bethel-Brown 69 kV | In Service |
| AD1-144 | Kings Fork 34.5 kV | In Service |
| AD1-151 | Hopewell-Surry 230 kV | Suspended |
| AD1-152 | Clover-Sedge Hill 230 kV | In Service |
| AD1-155 | Meadow Brook-Strasburg 138 kV | In Service |
| AD2-009 | McConnellsburg 138 kV | In Service |
| AD2-022 | East Danville - Roxborough 230 kV | Engineering & Procurement |
| AD2-023 | East Danville - Roxborough 230 kV | Engineering & Procurement |
| AD2-027 | Camden Switch 26 kV | In Service |
| AD2-030 | Wan 34.5 kV | In Service |
| AD2-031 | Martinsville-Wilmington 69 kV | In Service |
| AD2-033 | Chase City-Lunenburg 115 kV | Under Construction |
| AD2-038 | Powerton-Nevada 345 kV | Under Construction |
| AD2-042 | Camden Switch 26 kV II | In Service |
| AD2-048 | Cynthia-Headquarters 69 kV | Under Construction |
| AD2-058 | St. Barnabas 13 kV | In Service |
| AD2-065 | Atco 12 kV | In Service |
| AD2-066 | Mazon-Crescent Ridge 138 kV | Engineering & Procurement |
| AD2-071 | Strawton-Deer Creek 138 kV | Suspended |
| AD2-073 | Sanders DP 230 kV | In Service |
| AD2-074 | Garner DP-Lancaster 115 kV | Engineering & Procurement |
| AD2-085 | Myrtle-Windsor DP 115kV | Engineering & Procurement |
| AD2-100 | Kincaid-Pana 345 kV | Suspended |
| AD2-116 | Hokes-Grantley 69 kV | In Service |
| AD2-131 | Kincaid-Pana 345kV | Suspended |
| AD2-134 | Shady Oaks | Partially in Service - Under Construction |
| AD2-135 | Williamstown 12kV | Partially in Service - Under Construction |
| AD2-160 | Hickory-Moyock 230kV | In Service |
| AD2-172 | Lena 138kV | In Service |
| AD2-179 | Morgans Cut-Glen Lyn 138kV | Suspended |
| AD2-202 | Clover-Sedge Hill 230kV | In Service |
| AE1-040 | Greenfield 69 kV | In Service |
| AE1-056 | Red House-South Creek 115 kV | Withdrawn |
| AE1-072 | Shawboro-Sligo 230 kV | Under Construction |
| AE1-074 | Winterpock 34.5 kV | Under Construction |
| AE1-075 | Powhatan 34.5 kV | In Service |
| AE1-100 | Axton 138 kV | In Service |
| AE1-101 | McConnellsburg-Texas Eastern 138 kV | In Service |
| AE1-103 | Holland-Union Camp 115 kV | Under Construction |
| AE1-108 | Bremo-Scottsville 138 kV | Engineering & Procurement |
| AE1-113 | Mole Creek 345 kV | Engineering & Procurement |
| AE1-114 | Maryland-Lancaster 138 kV | Active |
| AE1-148 | Kerr Dam-Ridge Rd 115 kV | Active |
| AE1-149 | Disputanta-Poe 115 kV | Suspended |
| AE1-155 | Garner-Northern Neck 115 kV | In Service |
| AE1-157 | Ladysmith CT-St. Johns 230 kV | Suspended |
| AE1-162 | Smithfield 34.5 kV | In Service |
| AE1-163 | Powerton-Nevada 345 kV | Engineering & Procurement |
| AE1-172 | Loretto-Wilton Center | Active |
| AE1-173 | Carson-Suffolk 500 kV | Under Construction |
| AE1-175 | Light Foot 34.5 kV | In Service |
| AE1-176 | Roanoke-Vinton 12 kV (Niagara Hydro) | In Service |
| AE1-185 | Hokes-Jackson 69 kV | In Service |
| AE1-190 | Harmony Village-Shackleford 115 kV | Partially in Service - Under Construction |
| AE1-191 | Harmony Village-Shackleford 115 kV | Partially in Service - Under Construction |
| AE1-196 | Hokes-Jackson 69 kV II | In Service |
| AE1-205 | McLean 345 kV | Engineering & Procurement |
| AE1-207 | Mississinewa-Gaston 138 kV | Suspended |
| AE1-209 | Desoto 345 kV | Suspended |
| AE1-210 | Desoto 345 kV | Suspended |
| AE1-212 | Grandview-Clifftop 138 kV | Suspended |
| AE1-229 | Deepwater-Upper Pittsgrove 138 kV | Suspended |
| AE1-250 | Smith Mountain-E. Danville 138 kV | Engineering & Procurement |
| AE2-005 | Harmony Village-Shackleford 115 kV | Under Construction |
| AE2-027 | Harrowgate-Locks 115kV | Under Construction |
| AE2-029 | Grottoes-Merck 115kV | Under Construction |
| AE2-033 | Clubhouse-Sapony 230 kV | Suspended |
| AE2-034 | Mackeys 230 kV | Partially in Service - Under Construction |
| AE2-035 | Lena 138 kV | In Service |
| AE2-040 | Sapony 34.5 kV | Partially in Service - Under Construction |
| AE2-047 | Ridgeway-Solite 69 kV | Engineering & Procurement |
| AE2-051 | Carson-Septa 500 kV | Engineering & Procurement |
| AE2-054 | Warfordsburg 34 kV | In Service |
| AE2-071 | Patton Rd-Summer Shade 69 kV | In Service |
| AE2-092 | Kidds Store-Sherwood 115 kV | Engineering & Procurement |
| AE2-094 | Carson-Rogers Road 500 kV | Engineering & Procurement |
| AE2-104 | Suffolk 115 kV | Suspended |
| AE2-140 | Axton-Danville 138 kV | Suspended |
| AE2-156 | Yadkin 115 kV | Active |
| AE2-160 | Kanawha River 138 kV | Engineering & Procurement |
| AE2-166 | Stockton 138 kV | Suspended |
| AE2-172 | Mississinewa-Gaston 138 kV | Suspended |
| AE2-173 | McLean 345 kV | Active |
| AE2-183 | Rogers Road 500 kV | In Service |
| AE2-185 | Gladys DP-Stonemill Switching Station 69 kV | Active |
| AE2-187 | Shockoe DP-Chatham 69 kV | Active |
| AE2-212 | Harrowgate 34 kV | Engineering & Procurement |
| AE2-220 | Losantville 345 kV | Engineering & Procurement |
| AE2-221 | Clinton-Stuart 345 kV | Under Construction |
| AE2-223 | McLean 345 kV | Active |
| AE2-230 | Bartonsville-Meadow Brook 138 kV | In Service |
| AE2-253 | Hickory-Moyock 230 kV | In Service |
| AE2-254 | Garrard County-Tommy-Gooch 69 kV | In Service |
| AE2-255 | Molecreek 345 kV | Engineering & Procurement |
| AE2-259 | Curdsville-Willis Mtn 115 kV | Engineering & Procurement |
| AE2-261 | Kincaid-Pana 345 kV | Active |
| AE2-267 | Woodsdale 345 kV | Engineering & Procurement |
| AE2-281 | Powerton-Nevada 345 kV | Engineering & Procurement |
| AE2-283 | Gladys-Stone Mill 69 kV | Active |
| AE2-291 | Grit DP-Perth 115 kV | Active |
| AE2-297 | Madison-Tanners Creek 138 kV | In Service |
| AE2-308 | Three Forks-Dale 138 kV | Active |
| AE2-315 | Yankee Tap 69 kV | In Service |
| AE2-318 | Ford-Cedarville 138 kV | Suspended |
| AE2-321 | Belvidere-Marengo 138 kV | Active |
| AE2-326 | Jacksons Ferry 138 kV | Engineering & Procurement |
| AE2-339 | Avon 138 kV | Engineering & Procurement |
| AE2-341 | Sandwich-Plano 138 kV | Active |
| AE2-346 | Ahoskie 34.5 kV | In Service |
| AF1-007 | Indian River 230 kV I | Suspended |
| AF1-014 | Harmony Village-Shackleford 115 kV | Under Construction |
| AF1-017 | Myrtle-Windsor 115 kV | Engineering & Procurement |
| AF1-030 | Sandwich-Plano 138 kV | Active |
| AF1-032 | Suffolk 34.5 kV | In Service |
| AF1-038 | Sewellton Jct-Webbs Crossroads 69 kV | Engineering & Procurement |
| AF1-042 | Garner DP-Lancaster 115 kV | Engineering & Procurement |
| AF1-045 | Cedarville-Ford 138 kV | Suspended |
| AF1-049 | Berry Hill 138 kV | Under Construction |
| AF1-050 | Summer Shade - Green County 161 kV | Engineering & Procurement |
| AF1-058 | Welco 34.5 kV | In Service |
| AF1-069 | Carson-Rogers Rd 500 kV | Engineering & Procurement |
| AF1-075 | Harrisburg-Endless Caverns 230 kV | Suspended |
| AF1-083 | Green County-Saloma 161 kV | Engineering & Procurement |
| AF1-088 | Sullivan 345 kV | Active |
| AF1-090 | Kincaid-Pana | Engineering & Procurement |
| AF1-114 | Oak Grove-Dahlgren 230 kV | Engineering & Procurement |
| AF1-123 | Harper 230 kV | Active |
| AF1-124 | Harper 230 kV | Active |
| AF1-125 | Harper 230 kV | Active |
| AF1-128 | Chesterfield 230 kV | Active |
| AF1-129 | Chesterfield 230 kV | Engineering & Procurement |
| AF1-130 | Inez 138 kV | Suspended |
| AF1-136 | Warfordsburg-Purcell Junction 34.5 kV | Engineering & Procurement |
| AF1-147 | Poland Rd-Runway DP 230kV | Under Construction |
| AF1-162 | Inez 138 kV | Engineering & Procurement |
| AF1-203 | Patton Rd-Summer Shade 69 kV | In Service |
| AF1-204 | Eugene 345 kV | Active |
| AF1-207 | Reynolds-Olive #1 345 kV | Engineering & Procurement |
| AF1-233 | Flemingsburg – Spurlock 138kV | Active |
| AF1-249 | Nickel 12.47 kV | In Service |
| AF1-254 | Milnor-Huyetts 34.5 kV | Under Construction |
| AF1-262 | Upper Pittsgrove 12 kV | In Service |
| AF1-264 | Runnemede 13 kV | In Service |
| AF1-268 | Desoto-Jay 138 kV | Engineering & Procurement |
| AF1-282 | Stuart-Clinton 345 kV | Engineering & Procurement |
| AF1-283 | Stuart-Clinton 345 kV | Engineering & Procurement |
| AF1-290 | Feagans Mill-Millville 138 kV | In Service |
| AF1-291 | Tyler 34.5 kV | Engineering & Procurement |
| AF1-291A | Bartonsville-Meadow Brook 138 kV | In Service |
| AF1-292 | Fields 34.5kV | Engineering & Procurement |
| AF1-294 | Jetersville-Ponton 115 kV | Active |
| AF1-296 | Garden Plain 138 kV | Active |
| AF1-299 | Otter Point 34.5 kV I | In Service |
| AF1-300 | Otter Point 34.5 kV II | In Service |
| AF1-322 | Meadow Lake 345 kV | Engineering & Procurement |
| AF1-331 | Twombley Road | Engineering & Procurement |
| AF2-008 | Sullivan 345 kV | Active |
| AF2-018 | Inez 138 kV | Engineering & Procurement |
| AF2-032 | Kincaid 345 kV | Engineering & Procurement |
| AF2-035 | St. Johns 115 kV | Active |
| AF2-041 | Nelson-Electric Junction 345 kV | Active |
| AF2-042 | Clover-Rawlings 500 kV | Active |
| AF2-043 | Suffolk 34.5 kV | In Service |
| AF2-046 | Tunis-Mapleton 115 kV | Active |
| AF2-048 | Rio-Lick 138 kV | Engineering & Procurement |
| AF2-054 | Wan 34.5 kV | In Service |
| AF2-069 | Crescent Ridge 138 kV | Active |
| AF2-075 | Bartonsville-Meadow Brook 138 kV III | In Service |
| AF2-077 | White Marsh 34.5 kV | In Service |
| AF2-078 | Reynolds-Olive #1 345 kV | Engineering & Procurement |
| AF2-080 | Chinquapin-Everetts 230 kV | Active |
| AF2-081 | Moyock 230 kV | Active |
| AF2-085 | Midlothian 34.5 kV | In Service |
| AF2-106 | Hazel Hollow-Glen Lyn #1 138 kV | Engineering & Procurement |
| AF2-107 | Clifford 138 kV | Engineering & Procurement |
| AF2-110 | Suffolk 115 kV | Suspended |
| AF2-111 | North Clark-Spurlock 345 kV | Active |
| AF2-115 | Jetersville-Ponton 115 kV | Active |
| AF2-120 | Garner-Northern Neck 115 kV | Active |
| AF2-142 | Nevada 345 kV | Active |
| AF2-143 | Powerton-Nevada 345 kV | Active |
| AF2-144 | Powhatan 34.5 kV | In Service |
| AF2-173 | Desoto 345 kV | Active |
| AF2-199 | Nelson-Electric Junction 345 kV | Active |
| AF2-200 | Nelson-Electric Junction 345 kV | Active |
| AF2-222 | Madisonville DP-Twitty's Creek 115 kV | Active |
| AF2-225 | McLean 345 kV | Active |
| AF2-250 | Edgewood 12 kV III | In Service |
| AF2-252 | Blue Mound 345 kV | Engineering & Procurement |
| AF2-291 | Sporn South-Leon 138 kV | Engineering & Procurement |
| AF2-297 | Sedge Hill 115 kV | Active |
| AF2-299 | Fields 34.5 kV | Active |
| AF2-307 | Hope-Belvins Valley Tap 69 kV | Active |
| AF2-311 | Gilboa-Jones Branch 138 kV | Engineering & Procurement |
| AF2-316 | Gilboa-Jones Branch 138 kV II | Engineering & Procurement |
| AF2-325 | Jacktown 12 kV | Engineering & Procurement |
| AF2-335 | Delaware-Royerton 138 kV | Active |
| AF2-352 | Blue Mound 345 kV | Engineering & Procurement |
| AF2-365 | Munfordville KU Tap-Horse Cave Jct. 69 kV | Active |
| AF2-378 | Cambridge 12 kV | Engineering & Procurement |
| AF2-379 | Princess Anne 25 kV | Under Construction |
| AF2-382 | Hurley 69 kV | Engineering & Procurement |
| AF2-383 | Tolna 115 kV | Withdrawn |
| AF2-392 | Nelson-Dixon 138 kV | Active |
| AF2-404 | Gladys DP-Stonemill 69 kV | Active |
| AF2-440 | Hillsboro-Middleboro 138 kV | Engineering & Procurement |
| AG1-007 | Tar River 12.5 kV | Engineering & Procurement |
| AG1-008 | Tunis-Mapleton 115 kV | Active |
| AG1-021 | Jetersville-Ponton 115 kV | Active |
| AG1-038 | Garner DP-Lancaster 115 kV | Engineering & Procurement |
| AG1-066 | Bonnyman 69 kV | Engineering & Procurement |
| AG1-070 | Bon Ayr 69 kV | Active |
| AG1-071 | Bon Ayr 69 kV | Active |
| AG1-082 | Ahoskie 34.5 kV | Active |
| AG1-098 | Briery-Clover 230 kV | Active |
| AG1-105 | Mount Laurel-Barnes Junction 115 kV | Active |
| AG1-106 | Thelma 230 kV | Active |
| AG1-107 | Hillsboro-Middleboro 138 kV | Engineering & Procurement |
| AG1-118 | Sugar Grove-Waterman 138kV | Active |
| AG1-124 | Gladstone 138 kV | Active |
| AG1-127 | Crego Rd 138 kV | Active |
| AG1-135 | Garner-Lancaster 115 kV | Active |
| AG1-145 | Lightfoot 34.5 kV | In Service |
| AG1-146 | Garner DP-Lancaster 115 kV | Active |
| AG1-147 | Garner DP-Lancaster 115 kV | Active |
| AG1-153 | Heritage 500 kV | Active |
| AG1-166 | Lone Pine 115 kV | Active |
| AG1-167 | Lone Pine 115 kV | Active |
| AG1-168 | Lone Pine 115 kV | Active |
| AG1-226 | Dequine-Eugene 345 kV | Active |
| AG1-236 | Lanesville-Brokaw 345 kV | Active |
| AG1-237 | Dequine-Eugene 345 kV | Engineering & Procurement |
| AG1-254 | Salem-Woodstown 69 kV | Engineering & Procurement |
| AG1-282 | Dunnsville 34.5 kV | Engineering & Procurement |
| AG1-285 | Chase City-Central 115 kV | Active |
| AG1-320 | Glendale-Stephensburg 69 kV | Active |
| AG1-341 | Summer Shade 161 kV | Active |
| AG1-342 | Dryburg 115 kV | Active |
| AG1-354 | Summershade-Green County 161 kV | Active |
| AG1-367 | DeSoto 345 kV | Active |
| AG1-374 | Blue Mound 345 kV | Active |
| AG1-393 | Sapony 34.5 kV | Active |
| AG1-394 | Boykins 34.5 kV | Active |
| AG1-397 | Walston 12 kV | Withdrawn |
| AG1-405 | Walnut Grove-Asahi 69 kV | Active |
| AG1-406 | Walnut Grove-Asahi 69 kV | Active |
| AG1-460 | Kincaid-Pana 345 kV | Active |
| AG1-462 | Cordova 345 kV | Active |
| AG1-469 | Gordonsville 34.5 kV | Engineering & Procurement |
| AG1-471 | Up Church-Wayne County 69 kV | Active |
| AG1-482 | Hamilton 115 kV | Withdrawn |
| AG1-494 | Boxwood-Riverville 138 kV | Active |
| AG1-499 | Lambs 12.47 kV | Under Construction |
| AG1-508 | Point Lookout 69 kV | Engineering & Procurement |
| AG1-526 | West Garrard 345 kV | Active |
| AG1-532 | Fields 34.5 kV | Engineering & Procurement |
| AG1-551 | Parmele 34.5 kV | Active |
| AG1-552 | Carolina 34.5 kV | Active |
| AG1-555 | Dequine 345 kV | Engineering & Procurement |
| AG1-558 | Buckner 34.5 kV | Engineering & Procurement |
| AG1-559 | Caroline Pines 22 kV | Engineering & Procurement |
| AG2-005 | Garner DP-Lancaster 115 kV | Active |
| AG2-010 | Peninsula-Whealton 115 kV | Active |
| AG2-068 | Heritage - Wake 500 kV | Active |
| AG2-069 | Heritage - Wake 500 kV | Active |
| AG2-072 | Rockport 765 kV | Active |
| AG2-073 | Crooksville 69 kV | Active |
| AG2-077 | Clover-Rawlings 500 kV | Active |
| AG2-081 | Mt. Sterling-Fogg Pike 69 kV | Active |
| AG2-085 | Delaware-Royerton 138 kV | Active |
| AG2-088 | Midlothian 230 kV | Active |
| AG2-093 | Colonial Trail-Hopewell 230 kV | Active |
| AG2-095 | Hopewell 34.5 kV (Circuit 313) | Active |
| AG2-111 | Perth 34.5 kV Substation (Circuit 408) | Active |
| AG2-112 | Perth 34.5 kV Substation (Circuit 404) | Active |
| AG2-114 | Dresden-Pontiac Midpoint 345 kV | Active |
| AG2-120 | Everetts 34.5 kV | Active |
| AG2-124 | Shackleford-Harmony 115 kV | Active |
| AG2-126 | Eugene 345 kV | Active |
| AG2-151 | Trices Lake - James River Tap 115 kV | Active |
| AG2-159 | Williamstown 69 kV | Active |
| AG2-162 | Jefferson-Greentown 765 kV | Active |
| AG2-163 | Dequine-Eugene 345 kV | Active |
| AG2-164 | Jefferson-Greentown 765 kV | Active |
| AG2-171 | Lunenburg-Nutbush 115 kV | Active |
| AG2-179 | Sewellton Junction 69 kV | Active |
| AG2-184 | Harbert Metering 138 kV | Active |
| AG2-188 | Farmville - Buckingham 230 kV | Active |
| AG2-191 | Mississinewa 138 kV | Active |
| AG2-192 | Mississinewa 138 kV | Active |
| AG2-193 | Turner 34.5 kV | Active |
| AG2-198 | Briery - Finneywood 230 kV | Active |
| AG2-208 | Greenwood DP - St. Johns DP 115 kV | Active |
| AG2-213 | Gary D.P Tap - Gary D.P 115 kV | Active |
| AG2-215 | Garner DP-Lancaster 115 kV | Active |
| AG2-219 | Jefferson-Greentown 765 kV | Active |
| AG2-262 | Dryburg 115 kV | Active |
| AG2-270 | Clover 230 kV | Active |
| AG2-272 | Berry Hill 138 kV | Active |
| AG2-298 | Sulphur Creek-Loretto 69 kV | Active |
| AG2-310 | Matt Funk 138 kV | Active |
| AG2-311 | Smith Mountain 138 kV | Active |
| AG2-331 | Jefferson-Greentown 765 kV | Active |
| AG2-338 | Rogers Road - Carson 500 kV | Active |
| AG2-339 | Rogers Road - Carson 500 kV | Active |
| AG2-341 | Ridge Road 115 kV | Active |
| AG2-360 | Broadford 138 kV | Active |
| AG2-363 | Powerton 345 kV | Active |
| AG2-364 | Powerton 345 kV | Active |
| AG2-369 | Heritage - Wake 500 kV | Active |
| AG2-382 | Cashie 230 kV | Active |
| AG2-384 | Chesterfield 230 kV | Active |
| AG2-401 | Losantville 345 kV | Active |
| AG2-424 | Magnolia - Summersville 69 kV | Active |
| AG2-426 | Wakefield - Waverly 115 kV | Active |
| AG2-427 | Waverly 115 kV | Active |
| AG2-428 | Wakefield 115 kV | Active |
| AG2-436 | Carson - Rogers Road 500 kV | Active |
| AG2-440 | Twittys Creek - Madisonville 115 kV | Active |
| AG2-441 | Twittys Creek - Madisonville 115 kV | Active |
| AG2-442 | Twittys Creek - Madisonville 115 kV | Active |
| AG2-449 | Jefferson-Greentown 765 kV | Active |
| AG2-469 | Westmoreland – Oak Grove 230 kV | Active |
| AG2-487 | Madison - Tanners Creek 138 kV | Active |
| AG2-491 | Meadow Lake 345 kV | Active |
| AG2-516 | Pecatonica 138kV | Active |
| AG2-518 | Tech Drive 138 kV | Active |
| AG2-519 | Royerton - Desoto 138 kV | Active |
| AG2-522 | Five Forks DP 115 kV | Active |
| AG2-541 | Perth - Crystal Hill 115 kV | Active |
| AG2-548 | Corwin - Elk 138 kV | Active |
| AG2-566 | Briery - Finneywood 230 kV | Active |
| AG2-568 | Stink Run – Sundial 138 kV | Active |
| AG2-570 | Heritage - Wake 500 kV | Active |
| AG2-571 | Heritage - Wake 500 kV | Active |
| AG2-575 | Crego Rd. 138 kV | Active |
| AG2-581 | Rawlings-Clover 500 kV | Active |
| AG2-583 | Bremo - Cartersville 230 kV | Active |
| AG2-589 | Ravenswood - Hemlock 69 kV | Active |
| AG2-637 | Randolph - Hodgin 138 kV | Active |
| AG2-657 | Kanawha River - Carbondale 138 kV | Active |
| AG2-659 | Kerr Dam – Hawtree 115 kV | Active |
| AG2-660 | Nelson-Electric Junction 345 kV | Active |
| AG2-661 | Hopewell - Colonial Trail 230 kV | Active |
| AG2-665 | Corwin - Elk 138 kV | Active |
| AG2-670 | Green County -Taylor County Junction 161 kV | Active |
| AH1-004 | Avon - Renaker 138 kV | Active |
| AH1-012 | Louisa - North Anna 230 kV | Active |
| AH1-033 | Sligo 34.5 kV | Active |
| AH1-034 | Patton Road Junction - Summer Shade 69 kV | Active |
| AH1-035 | Plymouth 34.5 kV | Active |
| AH1-040 | Mackeys - Creswell 115 kV | Active |
| AH1-042 | Providence Forge-Turner 115kV | Active |
| AH1-044 | Nelson - Electric Junction 345 kV | Active |
| AH1-047 | Marengo - Belvidere 138 kV | Active |
| AH1-055 | Kyger Creek - Don Marquis 345 kV | Active |
| AH1-056 | Red House DP 115kV | Active |
| AH1-065 | Hopewell 34.5kV | Active |
| AH1-066 | Hopewell 34.5kV | Active |
| AH1-071 | Midlothian 34.5 kV | Active |
| AH1-072 | Red Onion - VC5 69 kV | Active |
| AH1-073 | Red Onion - VC5 69 kV | Active |
| AH1-098 | Wolf Glade-West Carroll 138 kV | Active |
| AH1-106 | Winterpock 34.5kV | Active |
| AH1-107 | Winterpock 34.5kV | Active |
| AH1-108 | Spruance NUG 230 kV | Active |
| AH1-133 | Saltville - Tazewell 138 kV | Active |
| AH1-136 | Falcon - Middle Creek 46 kV | Active |
| AH1-138 | Penniman 34.5 kV | Active |
| AH1-144 | Peter's Mountain 138 kV | Active |
| AH1-145 | Peter's Mountain 138 kV | Active |
| AH1-146 | White Rock - Wayne 345 kV | Active |
| AH1-147 | White Rock - Wayne 345 kV | Active |
| AH1-150 | Nelson-Electric Junction 345 kV | Active |
| AH1-151 | Nelson-Electric Junction 345 kV | Active |
| AH1-157 | Penniman - Waller 230 kV | Active |
| AH1-164 | Oak Level - Tank Hill 138 kV | Active |
| AH1-170 | Columbia DP 115kV | Active |
| AH1-188 | Pigeon Creek 138 kV | Active |
| AH1-196 | Prairie 345 kV | Active |
| AH1-215 | Central VA-Twitty 115 kV | Active |
| AH1-216 | Smithfield-Surry 230 kV | Active |
| AH1-217 | Kidds Store - Fork Union 115 kV II | Active |
| AH1-221 | Heritage 500 kV | Active |
| AH1-227 | Flemming - Fremont 69 kV | Active |
| AH1-234 | Wempletown - Paddock 345 kV | Active |
| AH1-239 | Upchurch - Zula 69 kV | Active |
| AH1-241 | Cobbs Creek - James River Industrial 115kV | Active |
| AH1-269 | Claytor 138 kV | Active |
| AH1-271 | Cashie 230 kV | Active |
| AH1-280 | Jetersville-Ponton 115 kV | Active |
| AH1-281 | Bluegrass Parkway Tap - Woodlawn 69 kV | Active |
| AH1-285 | Sandwich 138 kV | Active |
| AH1-292 | Sullivan 345 kV | Active |
| AH1-306 | Mississinewa-Gaston 138 kV | Active |
| AH1-311 | Heartsease DP - Mayo Dunbar 115kV | Active |
| AH1-314 | East Danville 138 kV | Active |
| AH1-323 | Elmont 230 kV | Active |
| AH1-324 | Colonial Trail – Surry 230 kV | Active |
| AH1-337 | Randolph - Hodgin 138 kV | Active |
| AH1-338 | McGirr Rd - Ritchie Road 138kV | Active |
| AH1-341 | Stillman - Dixon 138KV | Active |
| AH1-343 | Crystal Hill DP- Perth 115kV | Active |
| AH1-348 | Pound 34.5 kV | Active |
| AH1-377 | Clover- Farmville 230kV | Active |
| AH1-396 | Gary 24.94 kV | Active |
| AH1-397 | Shacklesford 34.5 kV | Active |
| AH1-399 | North Doswell 12.5 kV | Active |
| AH1-408 | Freeman DP – Lawrenceville 115 kV | Active |
| AH1-427 | Tommy Gooch - Garrard County 69 kV | Active |
| AH1-439 | Buckingham- Farmville 230kV | Active |
| AH1-528 | Rawlings - Unity 500 kV | Active |
| AH1-535 | Nagel - Cane River 230 kV | Active |
| AH1-537 | Pierce - Kyger Creek 345 kV | Active |
| AH1-541 | Chestnut 345 kV | Active |
| AH1-543 | Mulberry – Tazewell 345 kV | Active |
| AH1-546 | Bremo - Buckingham 230 kV | Active |
| AH1-570 | Headquarters - Millersburg Junction 69 kV | Active |
| AH1-571 | Headquarters - Millersburg Junction 69 kV | Active |
| AH1-617 | Harbert Metering 138 kV | Active |
| AH1-637 | Oak Grove 34.5 kV | Active |
| AH1-644 | Spicewood Metering 138 kV | Active |
| AH1-664 | Goddard-Plumville 138 kV | Active |
| AH1-665 | Goddard-Plumsville 138 kV II | Active |
| AH1-666 | Flemingsburg - Spurlock 138 kV | Active |
| AH1-670 | Blue Mound-Chestnut 345 kV | Active |
| AH1-676 | Gordonsville 230 kV | Active |
| AH1-677 | Rogers Road 500 kV | Active |
| AH1-678 | Heritage 500 kV | Active |
| AH1-679 | Four Rivers 230 kV | Active |
| AH1-681 | Cunningham 500 kV | Active |
| AH1-682 | Ladysmith CT 230 kV | Active |
| AH1-683 | Ladysmith CT 230 kV | Active |
| AH1-686 | Hanging Rock 765 kV | Active |
| AH1-687 | Bear Garden 230kV | Active |
| AH1-690 | Bay Shore - Lallendorf 345 kV | Active |
| AH1-691 | Ladysmith CT 230 kV | Active |
| AH1-692 | Ladysmith CT 230 kV | Active |
| AH1-694 | Ladysmith CT 230 kV | Active |
| AH1-702 | Byron 345 kV | Active |
| AH1-712 | Cunningham 500 kV | Active |
| AH1-716 | Surry-Skiffes Creek 500kV | Active |
| AH1-717 | Surry 230kV | Active |
| AH1-718 | Nelson 345 kV | Active |
| AH1-721 | Laurel-Cooper 161 kV | Active |
| AH1-723 | Cunningham 500 kV | Active |
| V3-007 | Desoto-Tanners Creek #1 345kV | In Service |
| V4-067 | Cates Road Egg Harbor Township 12kV | Deactivated |
| W1-003 | Oak Hall | In Service |
| W1-004 | Oak Hall | In Service |
| W1-005 | Oak Hall | In Service |
| W1-006 | Oak Hall | In Service |
| W1-130 | Vine Road 12kV | In Service |
| W2-030 | Egg Harbor Township | In Service |
| W2-048 | Brokaw-Lanesville | In Service |
| W4-005 | Blue Mound-Latham | In Service |
| X2-022 | Brokaw-Lanesville | In Service |
| X3-066 | Church Hill 69kV | In Service |
| Y1-049 | Wurno 34.5kV | In Service |
| Y1-079 | Wye Mills 69kV | In Service |
| Y1-080 | Dorchester 12kV | In Service |
| Y1-086 | Morgans Corner | In Service |
| Y3-058 | Rockawalkin 69kV | In Service |
| Z1-036 | WinFall-Chowan 230kV | In Service |
| Z2-027 | Pasquotank 34.5kV | In Service |
| Z2-044 | Whitakers 34.5kV | In Service |
| Z2-076 | Worcester South 25kV | In Service |
| Z2-077 | Worcester North 25kV | In Service |
| Z2-087 | Pontiac MidPoint-Brokaw 345kV | In Service |
| Z2-115 | Deer Creek 12.47kV | In Service |
Affected System - PJM Identified Violations
As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.
No cost allocated AFS Tie Line reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.
System Reinforcement
- Type
- Load Flow
- TO
- CPLE
- RTEP ID / TO ID
- (Pending) / TC2-CPLE-0001
- Title
- Person - VP Hendrick 230kV Line (Existing Line Uprate)
- Description
- Currently no costs since there is already a DEP project to reconductor to upgrade this line. This is the estimated ISD for the current project CPLE is developing. The Person - Hendrick 230 kV line will be reconductored with bundled 795 ACSS/TW and will have a rating 1195MVA.
- Total Cost ($USD)
- $0
- Allocated Cost ($USD)
- $0
- Time Estimate
- 0 to 48 Months
Info Note: AG2-152 contributes to the loading of an overloaded tie line facility between PJM and an affected system entity, which was identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line and will be confirmed in subsequent study phases, along with cost allocation of such upgrade if applicable, in coordination with the affected system.
| Facility | Contingency | |
|---|---|---|
| 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line | (Any) |
Affected System - Non-PJM Identified Violations
In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:
System Reinforcements
Based on the Phase I analysis results, this project may have a cost responsibility for the following System Reinforcements:
| TO | RTEP ID | Title | Allocated Cost ($USD) |
|---|---|---|---|
| AEP | (Pending) / AEP-TC2-18704 | 05SMITHMTN 138.0 kV to 05LEESVI 138.0 kV ckt 1 - Rebuild | $13,245,672 |
| Dominion | (Pending) / TC2-PH1-DOM-0044 | Wreck and rebuild 4.5 miles of 230 kV Line 2204 between Black Walnut and Edmonson with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. | $1,689,186 |
| Dominion | (Pending) / TC1-PH1-DOM-096 | Wreck and rebuild 2.8 mi of 115 kV Line 15 between Huber DP and Sedgehill with (1) 768,2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C | $1,335,495 |
| Dominion | (Pending) / TC2-PH1-DOM-2001 | Wreck and rebuild 2.66 miles of 115 kV line 1016 between Crystal Hill DP and AH1-343 with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. | $1,270,297 |
| AEP | (Pending) / AEP-TC2-18717 | 05BANSTR 138.0 kV to 05EDAN 2 138.0 kV ckt 1 - Sag Study and Replace Equipment | $1,167,298 |
| Dominion | (Pending) / TC2-PH1-DOM-0045 | Wreck and rebuild 8.3 miles of 230 kV Line 2250 between Edmonson and Sedge Hill with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. | $670,515 |
| Dominion | (Pending) / dom-184 | Wreck and rebuild 0.97 mi of 115 kV Line 15 between Woodchuck Trail and Huber DP with (1) 768,2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C | $462,654 |
| AEP | (Pending) / AEP-TC2-18655 | 05MUSEVILLE 138.0 kV to 05SMITHMTN 138.0 kV ckt 1 - Replace Switch | $370,179 |
| Dominion | (Pending) / TC2-PH1-DOM-2002 | Replace 556.6 ACSR line lead on line 104 at AltaVista 138 kV | $158,414 |
| Dominion | (Pending) / TC2-PH1-DOM-2043 | Wreck and rebuild 0.93 miles of 230 kV Line 2241 between Hendrick and Persons with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Dominion portion of line only. | $63,434 |
| AEP | (Pending) / AEP-TC2-18709 | AG2-152 TP 138.0 kV to 05BANSTR 138.0 kV ckt 1 - Sag Study and Upgrade Equipment | $34,332 |
| Dominion | n8423 / dom-119 | Wreck and rebuild 0.06 miles of 115 kV line 1016 between Woodchuck Trail and Crystal Hill DP with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. | $28,653 |
| AEP | (Pending) / AEPAPRJV004 | Replace wavetrap @ New London | $25,960 |
| Grand Total: | $20,522,089 | ||
Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.
System Reinforcement
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- (Pending) / AEP-TC2-18704
- Title
- 05SMITHMTN 138.0 kV to 05LEESVI 138.0 kV ckt 1 - Rebuild
- Description
- Rebuild ~8.2 miles of 138 kV line between Smith Mountain and Leesville, upgrade 795 AAC station conductor at Smith Mountain and Leesville.
- Total Cost ($USD)
- $32,000,000
- Allocated Cost ($USD)
- $13,245,672
- Time Estimate
- 36 to 48 Months
Contributor
| Facility | Contingency | |
|---|---|---|
| 05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line | (Any) |
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
AG2-111 | 3.8 MW | 5.3% | $1,710,840 |
AG2-112 | 4.0 MW | 5.6% | $1,793,537 |
AG2-152 | 29.8 MW | 41.4% | $13,245,672 |
AG2-311 | 13.9 MW | 19.3% | $6,172,896 |
AG2-541 | 13.6 MW | 18.9% | $6,049,740 |
AH1-343 | 6.8 MW | 9.5% | $3,027,315 |
System Reinforcement
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- (Pending) / TC2-PH1-DOM-0044
- Title
- Wreck and rebuild 4.5 miles of 230 kV Line 2204 between Black Walnut and Edmonson with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
- Description
- Wreck and rebuild 4.5 miles of 230 kV Line 2204 between Black Walnut and Edmonson with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
- Total Cost ($USD)
- $17,100,000
- Allocated Cost ($USD)
- $1,689,186
- Time Estimate
- 36 to 42 Months
Contributor
| Facility | Contingency | |
|---|---|---|
| 6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line | (Any) |
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
AG2-068 | 9.9 MW | 7.4% | $1,256,962 |
AG2-069 | 14.9 MW | 11.0% | $1,885,444 |
AG2-152 | 13.4 MW | 9.9% | $1,689,186 |
AG2-369 | 8.5 MW | 6.3% | $1,081,064 |
AG2-541 | 14.1 MW | 10.5% | $1,788,832 |
AG2-570 | 39.8 MW | 29.4% | $5,027,723 |
AG2-571 | 5.0 MW | 3.7% | $636,448 |
AH1-314 | 13.5 MW | 10.0% | $1,705,751 |
AH1-343 | 16.0 MW | 11.9% | $2,028,591 |
System Reinforcement
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- (Pending) / TC1-PH1-DOM-096
- Title
- Wreck and rebuild 2.8 mi of 115 kV Line 15 between Huber DP and Sedgehill with (1) 768,2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C
- Description
- Wreck and rebuild 2.8 mi of 115 kV Line 15 between Huber DP and Sedgehill with (1) 768,2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C
- Total Cost ($USD)
- $8,960,000
- Allocated Cost ($USD)
- $1,335,495
- Time Estimate
- 30 to 36 Months
Contributor
| Facility | Contingency | |
|---|---|---|
| 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line | (Any) |
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
AG2-111 | 5.0 MW | 5.8% | $516,143 |
AG2-112 | 5.3 MW | 6.0% | $541,145 |
AG2-152 | 13.0 MW | 14.9% | $1,335,495 |
AG2-311 | 6.1 MW | 6.9% | $622,404 |
AG2-541 | 27.0 MW | 30.9% | $2,768,644 |
AH1-343 | 31.0 MW | 35.4% | $3,176,168 |
System Reinforcement
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- (Pending) / TC2-PH1-DOM-2001
- Title
- Wreck and rebuild 2.66 miles of 115 kV line 1016 between Crystal Hill DP and AH1-343 with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
- Description
- Wreck and rebuild 2.66 miles of 115 kV line 1016 between Crystal Hill DP and AH1-343 with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
- Total Cost ($USD)
- $8,512,000
- Allocated Cost ($USD)
- $1,270,297
- Time Estimate
- 30 to 36 Months
Contributor
| Facility | Contingency | |
|---|---|---|
| 3CRSTL HILL-AH1-343 TP 115.0 kV Ckt 1 line | (Any) |
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
AG2-111 | 5.0 MW | 5.8% | $490,200 |
AG2-112 | 5.3 MW | 6.0% | $513,936 |
AG2-152 | 13.1 MW | 14.9% | $1,270,297 |
AG2-311 | 6.1 MW | 7.0% | $592,053 |
AG2-541 | 27.0 MW | 30.9% | $2,629,314 |
AH1-343 | 31.0 MW | 35.4% | $3,016,201 |
System Reinforcement
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- (Pending) / AEP-TC2-18717
- Title
- 05BANSTR 138.0 kV to 05EDAN 2 138.0 kV ckt 1 - Sag Study and Replace Equipment
- Description
- Replace first overhead conductor span from East Danville to Structure 18-135 (1033 ACSR); Conduct sag clearance study on 10.7 miles between Structure 18-135 and Banister; Replace 1590 AAC station conductor at Banister; Replace 2000 AAC station conductor at East Danville
- Total Cost ($USD)
- $1,700,000
- Allocated Cost ($USD)
- $1,167,298
- Time Estimate
- 36 to 48 Months
Contributor
| Facility | Contingency | |
|---|---|---|
| 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line | (Any) |
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
AG2-152 | 80.4 MW | 68.7% | $1,167,298 |
AG2-311 | 19.0 MW | 16.3% | $276,475 |
AG2-541 | 8.6 MW | 7.3% | $124,289 |
AH1-343 | 9.1 MW | 7.8% | $131,938 |
System Reinforcement
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- (Pending) / TC2-PH1-DOM-0045
- Title
- Wreck and rebuild 8.3 miles of 230 kV Line 2250 between Edmonson and Sedge Hill with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
- Description
- Wreck and rebuild 8.3 miles of 230 kV Line 2250 between Edmonson and Sedge Hill with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
- Total Cost ($USD)
- $31,540,000
- Allocated Cost ($USD)
- $670,515
- Time Estimate
- 36 to 42 Months
Contributor
| Facility | Contingency | |
|---|---|---|
| 6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line | (Any) |
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
AG2-068 | 10.0 MW | 1.6% | $498,905 |
AG2-069 | 14.9 MW | 2.4% | $748,333 |
AG2-077 | 80.7 MW | 12.8% | $4,042,771 |
AG2-152 | 13.4 MW | 2.1% | $670,515 |
AG2-188 | 22.3 MW | 3.5% | $1,116,290 |
AG2-198 | 21.6 MW | 3.4% | $1,082,038 |
AG2-270 | 56.8 MW | 9.0% | $2,844,056 |
AG2-369 | 8.6 MW | 1.4% | $429,050 |
AG2-440 | 13.1 MW | 2.1% | $656,895 |
AG2-441 | 16.4 MW | 2.6% | $821,143 |
AG2-442 | 18.4 MW | 2.9% | $919,642 |
AG2-541 | 14.2 MW | 2.2% | $709,124 |
AG2-566 | 4.1 MW | 0.7% | $205,461 |
AG2-570 | 39.8 MW | 6.3% | $1,995,421 |
AG2-571 | 5.0 MW | 0.8% | $252,582 |
AG2-581 | 59.5 MW | 9.4% | $2,977,307 |
AH1-056 | 15.1 MW | 2.4% | $754,092 |
AH1-314 | 13.5 MW | 2.1% | $676,925 |
AH1-343 | 16.1 MW | 2.5% | $804,067 |
AH1-377 | 54.4 MW | 8.6% | $2,722,822 |
AH1-439 | 12.8 MW | 2.0% | $641,972 |
AH1-528 | 119.2 MW | 18.9% | $5,970,589 |
System Reinforcement
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- (Pending) / dom-184
- Title
- Wreck and rebuild 0.97 mi of 115 kV Line 15 between Woodchuck Trail and Huber DP with (1) 768,2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C
- Description
- Wreck and rebuild 0.97 mi of 115 kV Line 15 between Woodchuck Trail and Huber DP with (1) 768,2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C
- Total Cost ($USD)
- $3,104,000
- Allocated Cost ($USD)
- $462,654
- Time Estimate
- 30 to 36 Months
Contributor
| Facility | Contingency | |
|---|---|---|
| 3HUBER DP-AC1-222 TAP 115.0 kV Ckt 1 line | (Any) |
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
AG2-111 | 5.0 MW | 5.8% | $178,807 |
AG2-112 | 5.3 MW | 6.0% | $187,468 |
AG2-152 | 13.0 MW | 14.9% | $462,654 |
AG2-311 | 6.1 MW | 6.9% | $215,619 |
AG2-541 | 27.0 MW | 30.9% | $959,137 |
AH1-343 | 31.0 MW | 35.4% | $1,100,315 |
System Reinforcement
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- (Pending) / AEP-TC2-18655
- Title
- 05MUSEVILLE 138.0 kV to 05SMITHMTN 138.0 kV ckt 1 - Replace Switch
- Description
- Replace 138 kV Switch at Smith Mountain "C1S2"
- Total Cost ($USD)
- $500,000
- Allocated Cost ($USD)
- $370,179
- Time Estimate
- 36 to 48 Months
Contributor
| Facility | Contingency | |
|---|---|---|
| 05SMITHMTN-05MUSEVILLE 138.0 kV Ckt 1 line | (Any) |
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
AG2-152 | 112.6 MW | 74.0% | $370,179 |
AG2-272 | 7.8 MW | 5.1% | $25,589 |
AG2-311 | 19.3 MW | 12.7% | $63,625 |
AH1-314 | 12.3 MW | 8.1% | $40,607 |
System Reinforcement
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- (Pending) / TC2-PH1-DOM-2002
- Title
- Replace 556.6 ACSR line lead on line 104 at AltaVista 138 kV
- Description
- Replace 556.6 ACSR line lead on line 104 at AltaVista 138 kV
- Total Cost ($USD)
- $400,000
- Allocated Cost ($USD)
- $158,414
- Time Estimate
- 12 to 18 Months
Contributor
| Facility | Contingency | |
|---|---|---|
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | (Any) |
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
AG2-152 | 6.9 MW | 39.6% | $158,414 |
AG2-311 | 10.5 MW | 60.4% | $241,586 |
System Reinforcement
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- (Pending) / TC2-PH1-DOM-2043
- Title
- Wreck and rebuild 0.93 miles of 230 kV Line 2241 between Hendrick and Persons with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Dominion portion of line only.
- Description
- Wreck and rebuild 0.93 miles of 230 kV Line 2241 between Hendrick and Persons with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Dominion portion of line only.
- Total Cost ($USD)
- $3,534,000
- Allocated Cost ($USD)
- $63,434
- Time Estimate
- 36 to 42 Months
Contributor
| Facility | Contingency | |
|---|---|---|
| 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line | (Any) |
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
AG2-068 | 9.2 MW | 1.1% | $39,652 |
AG2-069 | 13.8 MW | 1.7% | $59,477 |
AG2-077 | 67.9 MW | 8.3% | $292,796 |
AG2-111 | 3.5 MW | 0.4% | $15,101 |
AG2-112 | 3.7 MW | 0.4% | $15,830 |
AG2-151 | 7.2 MW | 0.9% | $31,260 |
AG2-152 | 14.7 MW | 1.8% | $63,434 |
AG2-171 | 13.1 MW | 1.6% | $56,405 |
AG2-188 | 21.4 MW | 2.6% | $92,359 |
AG2-198 | 19.5 MW | 2.4% | $83,993 |
AG2-213 | 17.4 MW | 2.1% | $75,209 |
AG2-270 | 47.1 MW | 5.8% | $203,423 |
AG2-272 | 5.3 MW | 0.7% | $23,062 |
AG2-341 | 6.5 MW | 0.8% | $27,834 |
AG2-369 | 7.9 MW | 1.0% | $34,099 |
AG2-440 | 21.4 MW | 2.6% | $92,165 |
AG2-441 | 26.7 MW | 3.3% | $115,205 |
AG2-442 | 29.9 MW | 3.7% | $129,034 |
AG2-522 | 10.0 MW | 1.2% | $43,134 |
AG2-541 | 19.1 MW | 2.3% | $82,250 |
AG2-566 | 9.3 MW | 1.1% | $39,936 |
AG2-570 | 35.7 MW | 4.4% | $154,059 |
AG2-571 | 15.5 MW | 1.9% | $67,037 |
AG2-581 | 50.2 MW | 6.1% | $216,526 |
AG2-583 | 7.5 MW | 0.9% | $32,494 |
AG2-659 | 11.3 MW | 1.4% | $48,915 |
AH1-056 | 20.7 MW | 2.5% | $89,249 |
AH1-215 | 8.7 MW | 1.1% | $37,455 |
AH1-241 | 6.9 MW | 0.8% | $29,676 |
AH1-314 | 15.6 MW | 1.9% | $67,343 |
AH1-343 | 22.0 MW | 2.7% | $94,896 |
AH1-377 | 48.3 MW | 5.9% | $208,557 |
AH1-408 | 10.5 MW | 1.3% | $45,498 |
AH1-439 | 12.3 MW | 1.5% | $53,152 |
AH1-528 | 100.6 MW | 12.3% | $434,213 |
AH1-535 | 6.0 MW | 0.7% | $25,767 |
AH1-546 | 7.3 MW | 0.9% | $31,579 |
AH1-687 | 5.2 MW | 0.6% | $22,479 |
AH1-690 | 28.7 MW | 3.5% | $123,688 |
AH1-721 | 31.5 MW | 3.8% | $135,756 |
System Reinforcement
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- (Pending) / AEP-TC2-18709
- Title
- AG2-152 TP 138.0 kV to 05BANSTR 138.0 kV ckt 1 - Sag Study and Upgrade Equipment
- Description
- Upgrade 1590 AAC station conductor at Banister. Perform sag clearance study for ~0.5 mile of 138 kV line between AG2-152 and Banister to determine any potential mitigation required to operate at a higher temperature.
- Total Cost ($USD)
- $50,000
- Allocated Cost ($USD)
- $34,332
- Time Estimate
- 36 to 48 Months
Contributor
| Facility | Contingency | |
|---|---|---|
| 05BANSTR-AG2-152 TP 138.0 kV Ckt 1 line | (Any) |
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
AG2-152 | 80.4 MW | 68.7% | $34,332 |
AG2-311 | 19.0 MW | 16.3% | $8,132 |
AG2-541 | 8.6 MW | 7.3% | $3,656 |
AH1-343 | 9.1 MW | 7.8% | $3,881 |
System Reinforcement: n8423
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- n8423 / dom-119
- Title
- Wreck and rebuild 0.06 miles of 115 kV line 1016 between Woodchuck Trail and Crystal Hill DP with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
- Description
- Wreck and rebuild 0.06 miles of 115 kV line 1016 between Woodchuck Trail and Crystal Hill DP with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
- Total Cost ($USD)
- $192,000
- Allocated Cost ($USD)
- $28,653
- Time Estimate
- 30 to 36 Months
Contributor
| Facility | Contingency | |
|---|---|---|
| 3CRSTL HILL-AC1-222 TAP 115.0 kV Ckt 1 line | (Any) |
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
AG2-111 | 5.0 MW | 5.8% | $11,057 |
AG2-112 | 5.3 MW | 6.0% | $11,593 |
AG2-152 | 13.1 MW | 14.9% | $28,653 |
AG2-311 | 6.1 MW | 7.0% | $13,355 |
AG2-541 | 27.0 MW | 30.9% | $59,308 |
AH1-343 | 31.0 MW | 35.4% | $68,035 |
System Reinforcement
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- (Pending) / AEPAPRJV004
- Title
- Replace wavetrap @ New London
- Description
- Replace wavetrap @ New London
- Total Cost ($USD)
- $260,000
- Allocated Cost ($USD)
- $25,960
- Time Estimate
- 18 to 24 Months
Contributor
| Facility | Contingency | |
|---|---|---|
| 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line | (Any) |
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
AG2-111 | 4.7 MW | 7.1% | $18,378 |
AG2-112 | 4.9 MW | 7.4% | $19,267 |
AG2-152 | 6.6 MW | 10.0% | $25,960 |
AG2-311 | 6.8 MW | 10.2% | $26,550 |
AG2-541 | 20.9 MW | 31.7% | $82,388 |
AH1-343 | 22.2 MW | 33.6% | $87,457 |
System Reinforcement: b4000.211
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- b4000.211
- Title
- Rebuild 6.5 miles of Johnson Mountain - New London 138 kV line
- Description
- Rebuild 6.5 miles of Johnson Mountain - New London 138 kV line Projected In Service Date: 06/01/2029
- Cost Information
- Time Estimate
- Jun 01 2029
Contingent Note: Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.
| Facility | Contingency | |
|---|---|---|
| 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.210
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- b4000.210
- Title
- Rebuild 7 miles of Otter - Johnson Mountain 138 kV line.
- Description
- Rebuild 7 miles of Otter - Johnson Mountain 138 kV line.
- Cost Information
- Time Estimate
- Jun 01 2029
Contingent Note: Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.
| Facility | Contingency | |
|---|---|---|
| 05JOHNMT-05OTTER 138.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.207
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- b4000.207
- Title
- Leesville Station Upgrade 138 kV
- Description
- Leesville Station Upgrade 138 kV: Replace 795 KCM AAC, 37-Str. IPS Sch. 40 1272 KCM AAC, 61-Str. 1272 KCM AAC, 61-Str. PH A,B,C ALTA VISTA CB-A BUS DISC ALTA VISTA CB-A LINE DISC Wavetrap (1200A) Relay Thermal Limit 1356 Amps
- Cost Information
- Time Estimate
- Jun 01 2029
Contingent Note: Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.
| Facility | Contingency | |
|---|---|---|
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | (Any) |
System Reinforcement: n6594.1
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- n6594.1 / AEPA0044a
- Title
- Rebuild 8.4 miles section of the Leesville - Alta Vista 138 kV line
- Description
- Rebuild 8.4 miles section of the Leesville - Alta Vista 138 kV line
- Total Cost ($USD)
- $23,571,948
- Allocated Cost ($USD)
- $0
- Time Estimate
- Nov 21 2027
Contingent Note: Based on PJM cost allocation criteria, AG2-152 does not receive cost allocation towards this upgrade which has been securitized by a prior Queue/Cycle. Although AG2-152 may not have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable for the reliability to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.
| Facility | Contingency | |
|---|---|---|
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | (Any) |
System Reinforcement
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- (Pending)
- Title
- Most limiting rating on the Dominion side is the Wave Trap and Lead at Altavista: 363 / 382 /420 MVA.
- Description
- Most limiting rating on the Dominion side is the Wave Trap and Lead at Altavista: 363 / 382 /420 MVA.
- Total Cost ($USD)
- $0
- Allocated Cost ($USD)
- $0
- Time Estimate
- 99 Months
Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.
| Facility | Contingency | |
|---|---|---|
| 05OTTER-4ALTVSTA 138.0 kV Ckt 1 line | (Any) |
System Reinforcement: n5613
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- n5613 / AEPA0014a
- Title
- Rebuild 0.9 miles of the Otter - Alta Vista 138 kV line.
- Description
- Rebuild 0.9 miles of the Otter - Alta Vista 138 kV line.
- Total Cost ($USD)
- $2,740,849
- Allocated Cost ($USD)
- $0
- Time Estimate
- Nov 21 2027
Contingent Note: Based on PJM cost allocation criteria, AG2-152 does not receive cost allocation towards this upgrade which has been securitized by a prior Queue/Cycle. Although AG2-152 may not have cost responsibility for this upgrade, AG2-152 may need this upgrade in-service to be deliverable for the reliability to the PJM system. If AG2-152 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.
| Facility | Contingency | |
|---|---|---|
| 05OTTER-4ALTVSTA 138.0 kV Ckt 1 line | (Any) |
System Reinforcement
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- (Pending) / TC2-PH1-DOM-2077
- Title
- Replace switches 29824 and 29825 at Bremo 230 kV
- Description
- Replace switches 29824 and 29825 at Bremo 230 kV
- Total Cost ($USD)
- $800,000
- Allocated Cost ($USD)
- $0
- Time Estimate
- 12 to 18 Months
Potential Aggregate Contributor Note: Based on PJM cost allocation criteria, AG2-152 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-152 could receive cost allocation. Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 is a potential Aggregate Pool Contributor.
| Facility | Contingency | |
|---|---|---|
| 6BREMO-AH1-546 TP 230.0 kV Ckt 1 line | (Any) |
System Reinforcement
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- (Pending) / TC2-PH1-DOM-2076
- Title
- Replace wave trap 298 WT at Bremo 230 kV
- Description
- Replace wave trap 298 WT at Bremo 230 kV
- Total Cost ($USD)
- $400,000
- Allocated Cost ($USD)
- $0
- Time Estimate
- 12 to 18 Months
Potential Aggregate Contributor Note: Based on PJM cost allocation criteria, AG2-152 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-152 could receive cost allocation. Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 is a potential Aggregate Pool Contributor.
| Facility | Contingency | |
|---|---|---|
| 6BREMO-AH1-546 TP 230.0 kV Ckt 1 line | (Any) |
System Reinforcement
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- (Pending) / TC2-PH1-DOM-2079
- Title
- Replace 3 1/2 " AL Pipe line lead on line 298 at Bremo 230 kV
- Description
- Replace 3 1/2 " AL Pipe line lead on line 298 at Bremo 230 kV
- Total Cost ($USD)
- $500,000
- Allocated Cost ($USD)
- $0
- Time Estimate
- 12 to 18 Months
Potential Aggregate Contributor Note: Based on PJM cost allocation criteria, AG2-152 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-152 could receive cost allocation. Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 is a potential Aggregate Pool Contributor.
| Facility | Contingency | |
|---|---|---|
| 6BREMO-AH1-546 TP 230.0 kV Ckt 1 line | (Any) |
System Reinforcement
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- (Pending) / TC2-PH1-DOM-2078
- Title
- Replace 2-636 ACSR line lead on line 298 at Bremo 230 kV
- Description
- Replace 2-636 ACSR line lead on line 298 at Bremo 230 kV
- Total Cost ($USD)
- $500,000
- Allocated Cost ($USD)
- $0
- Time Estimate
- 12 to 18 Months
Potential Aggregate Contributor Note: Based on PJM cost allocation criteria, AG2-152 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-152 could receive cost allocation. Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 is a potential Aggregate Pool Contributor.
| Facility | Contingency | |
|---|---|---|
| 6BREMO-AH1-546 TP 230.0 kV Ckt 1 line | (Any) |
System Reinforcement: n9220.0
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- n9220.0 / TC1-PH2-DOM-033
- Title
- Wreck and rebuild 15.42 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
- Description
- Wreck and rebuild 15.42 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
- Total Cost ($USD)
- $44,465,922
- Allocated Cost ($USD)
- $0
- Time Estimate
- 42 to 48 Months
Potential Aggregate Contributor Note: Based on PJM cost allocation criteria, AG2-152 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-152 could receive cost allocation. Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 is a potential Aggregate Pool Contributor.
| Facility | Contingency | |
|---|---|---|
| 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line | (Any) | |
| 6BREMO-AH1-546 TP 230.0 kV Ckt 1 line | (Any) |
System Reinforcement: n9221.0
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- n9221.0 / TC1-PH3-DOM-015-TC2
- Title
- Replace 230 kV Breaker 29822 at Bremo with a higher-rated device (Buckingham - Bremo).
- Description
- Replace 230 kV Breaker 29822 at Bremo with a higher-rated device (Buckingham - Bremo).
- Total Cost ($USD)
- $2,057,335
- Allocated Cost ($USD)
- $0
- Time Estimate
- 38 to 39 Months
Potential Aggregate Contributor Note: Based on PJM cost allocation criteria, AG2-152 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-152 could receive cost allocation. Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 is a potential Aggregate Pool Contributor.
| Facility | Contingency | |
|---|---|---|
| 6BREMO-AH1-546 TP 230.0 kV Ckt 1 line | (Any) |
System Reinforcement: n9217.0
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- n9217.0 / TC1-PH2-DOM-028
- Title
- Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.
- Description
- Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.
- Total Cost ($USD)
- $40,414,822
- Allocated Cost ($USD)
- $0
- Time Estimate
- 45 to 46 Months
Potential Aggregate Contributor Note: Based on PJM cost allocation criteria, AG2-152 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-152 could receive cost allocation. Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 is a potential Aggregate Pool Contributor.
| Facility | Contingency | |
|---|---|---|
| 6BUCKING-AH1-439 TP 230.0 kV Ckt 1 line | (Any) | |
| 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line | (Any) | |
| AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line | (Any) |
System Reinforcement
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- (Pending) / TC2-PH1-DOM-2086
- Title
- Replace 3 1/2' AL Pipe line lead on line 298 at Farmville 230 kV
- Description
- Replace 3 1/2' AL Pipe line lead on line 298 at Farmville 230 kV
- Total Cost ($USD)
- $500,000
- Allocated Cost ($USD)
- $0
- Time Estimate
- 12 to 18 Months
Potential Aggregate Contributor Note: Based on PJM cost allocation criteria, AG2-152 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-152 could receive cost allocation. Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 is a potential Aggregate Pool Contributor.
| Facility | Contingency | |
|---|---|---|
| 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line | (Any) |
System Reinforcement
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- (Pending) / TC2-PH1-DOM-2085
- Title
- Replace wavetrap 298WT at Farmville 230 kV
- Description
- Replace wavetrap 298WT at Farmville 230 kV
- Total Cost ($USD)
- $400,000
- Allocated Cost ($USD)
- $0
- Time Estimate
- 16 to 18 Months
Potential Aggregate Contributor Note: Based on PJM cost allocation criteria, AG2-152 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-152 could receive cost allocation. Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 is a potential Aggregate Pool Contributor.
| Facility | Contingency | |
|---|---|---|
| 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line | (Any) |
System Reinforcement
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- (Pending) / TC2-PH1-DOM-2087
- Title
- Replace 2-1590 AAC 61 line lead on line 298 at Farmville 230 kV
- Description
- Replace 2-1590 AAC 61 line lead on line 298 at Farmville 230 kV
- Total Cost ($USD)
- $500,000
- Allocated Cost ($USD)
- $0
- Time Estimate
- 12 to 18 Months
Potential Aggregate Contributor Note: Based on PJM cost allocation criteria, AG2-152 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-152 could receive cost allocation. Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 is a potential Aggregate Pool Contributor.
| Facility | Contingency | |
|---|---|---|
| 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.350
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.350
- Title
- Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
- Description
- Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
- Cost Information
- Time Estimate
- Sep 16 2030
Not Contingent Note: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line | (Any) | |
| 8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line | (Any) | |
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) | |
| 8CARSON-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P1-2: LN 591_SRT-S |
System Reinforcement: b4000.355
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.355
- Title
- Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
- Description
- Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
- Cost Information
- Time Estimate
- Jun 01 2029
Not Contingent Note: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line | (Any) | |
| 8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line | (Any) | |
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) | |
| 8CARSON-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P1-2: LN 591_SRT-S |
System Reinforcement: b4000.327
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.327
- Title
- Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
- Description
- Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
- Cost Information
- Time Estimate
- Feb 24 2029
Not Contingent Note: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line | (Any) | |
| 8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line | (Any) | |
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) | |
| 8CARSON-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P1-2: LN 591_SRT-S |
System Reinforcement: b4000.348
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.348
- Title
- Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
- Description
- Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
- Cost Information
- Time Estimate
- Jun 01 2029
Not Contingent Note: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line | (Any) | |
| 8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line | (Any) | |
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) | |
| 8CARSON-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P1-2: LN 591_SRT-S |
System Reinforcement: b4000.341
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.341
- Title
- Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
- Description
- Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
- Cost Information
- Time Estimate
- Jul 13 2029
Not Contingent Note: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line | (Any) | |
| 8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line | (Any) | |
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) | |
| 8CARSON-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P1-2: LN 591_SRT-S |
System Reinforcement: b4000.357
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.357
- Title
- Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
- Description
- Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
- Cost Information
- Time Estimate
- Jun 01 2029
Not Contingent Note: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line | (Any) | |
| 8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line | (Any) | |
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) | |
| 8CARSON-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P1-2: LN 591_SRT-S |
System Reinforcement: b4000.349
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.349
- Title
- Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
- Description
- Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
- Cost Information
- Time Estimate
- Sep 16 2030
Not Contingent Note: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line | (Any) | |
| 8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line | (Any) | |
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) | |
| 8CARSON-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P1-2: LN 591_SRT-S |
System Reinforcement: b4000.352
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.352
- Title
- Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
- Description
- Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
- Cost Information
- Time Estimate
- Sep 16 2030
Not Contingent Note: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line | (Any) | |
| 8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line | (Any) | |
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) | |
| 8CARSON-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P1-2: LN 591_SRT-S |
System Reinforcement: b4000.344
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.344
- Title
- Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
- Description
- Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
- Cost Information
- Time Estimate
- Sep 16 2030
Not Contingent Note: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line | (Any) | |
| 8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line | (Any) | |
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) | |
| 8CARSON-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P1-2: LN 591_SRT-S |
System Reinforcement: b4000.325
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.325
- Title
- Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
- Description
- Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
- Cost Information
- Time Estimate
- Feb 24 2029
Not Contingent Note: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line | (Any) | |
| 8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line | (Any) | |
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) | |
| 8CARSON-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P1-2: LN 591_SRT-S |
System Reinforcement: b4000.346
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.346
- Title
- Cut-in 500kV line from Kraken substation into Yeat substation
- Description
- Cut-in 500kV line from Kraken substation into Yeat substation
- Cost Information
- Time Estimate
- Jun 01 2029
Not Contingent Note: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line | (Any) | |
| 8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line | (Any) | |
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) | |
| 8CARSON-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P1-2: LN 591_SRT-S |
System Reinforcement: b4000.356
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.356
- Title
- Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
- Description
- Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
- Cost Information
- Time Estimate
- Jun 01 2029
Not Contingent Note: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line | (Any) | |
| 8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line | (Any) | |
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) | |
| 8CARSON-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P1-2: LN 591_SRT-S |
System Reinforcement: b4000.345
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.345
- Title
- Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
- Description
- Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
- Cost Information
- Time Estimate
- Sep 16 2030
Not Contingent Note: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line | (Any) | |
| 8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line | (Any) | |
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) | |
| 8CARSON-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P1-2: LN 591_SRT-S |
System Reinforcement: b4000.351
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.351
- Title
- Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
- Description
- Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
- Cost Information
- Time Estimate
- Sep 16 2030
Not Contingent Note: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line | (Any) | |
| 8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line | (Any) | |
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) | |
| 8CARSON-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P1-2: LN 591_SRT-S |
System Reinforcement: b4000.326
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.326
- Title
- At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
- Description
- At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
- Cost Information
- Time Estimate
- Feb 24 2029
Not Contingent Note: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line | (Any) | |
| 8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line | (Any) | |
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) | |
| 8CARSON-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P1-2: LN 591_SRT-S |
System Reinforcement: b4000.342
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.342
- Title
- Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
- Description
- Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
- Cost Information
- Time Estimate
- Jul 13 2029
Not Contingent Note: AG2-152 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-152 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 8VALLEY-8VALLEY SC 500.0 kV Ckt 1 line | (Any) | |
| 8BATH CO-8VALLEY SC 500.0 kV Ckt 1 line | (Any) | |
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) | |
| 8CARSON-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P1-2: LN 591_SRT-S |
System Reinforcement: n9138.0
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- n9138.0 / TC1-PH1-DOM-070
- Title
- Wreck and rebuild 22.59 miles of Line #511 between Carson and Rawlings Substations with three (3) 1351 ACSS/TW and associated substation work.
- Description
- Wreck and rebuild 22.59 miles of Line 511 between Carson and Rawlings with three (3) 1351 ACSS/TW and associated substation work.
- Total Cost ($USD)
- $111,130,292
- Allocated Cost ($USD)
- $0
- Time Estimate
- 60 to 61 Months
Potential Aggregate Contributor Note: Based on PJM cost allocation criteria, AG2-152 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-152 could receive cost allocation. Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 is a potential Aggregate Pool Contributor.
| Facility | Contingency | |
|---|---|---|
| 8CARSON-8RAWLINGS 500.0 kV Ckt 1 line | (Any) | |
| 8CARSON-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P1-2: LN 511_SRT-S-A | |
| 8CARSON-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P1-2: LN 511_SRT-S | |
| 8CARSON-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P1-2: LN 511_SRT-S-C | |
| 8CARSON-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P1-2: LN 511_SRT-S | |
| 8CARSON-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P4-2: 51192_SRT-S | |
| 8CARSON-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P4-2: 51172_SRT-S | |
| 8CARSON-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P4-2: 511T544_SRT-S | |
| 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line | DVP_P1-2: LN 511_SRT-S | |
| 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line | DVP_P4-2: 51192_SRT-S | |
| 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line | DVP_P4-2: 51172_SRT-S | |
| 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line | DVP_P4-2: 511T544_SRT-S | |
| AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line | DVP_P1-2: LN 511_SRT-S | |
| AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line | DVP_P4-2: 51192_SRT-S | |
| AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line | DVP_P4-2: 51172_SRT-S | |
| AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line | DVP_P4-2: 511T544_SRT-S |
System Reinforcement: n9250.0
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- n9250.0 / TC1-PH2-DOM-044
- Title
- Construct a new 22.59 mile line between Carson and Rawlings Substations.
- Description
- Construct a new 22.59 mile line between Carson and Rawlings Substations.
- Total Cost ($USD)
- $108,728,086
- Allocated Cost ($USD)
- $0
- Time Estimate
- 60 to 61 Months
Potential Aggregate Contributor Note: Based on PJM cost allocation criteria, AG2-152 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-152 could receive cost allocation. Although AG2-152 may not presently have cost responsibility for this upgrade, AG2-152 is a potential Aggregate Pool Contributor.
| Facility | Contingency | |
|---|---|---|
| 8CARSON-8RAWLINGS 500.0 kV Ckt 1 line | (Any) | |
| 8CARSON-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P1-2: LN 511_SRT-S-C | |
| 8CARSON-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P1-2: LN 511_SRT-S | |
| 8CARSON-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P4-2: 51192_SRT-S | |
| 8CARSON-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P4-2: 51172_SRT-S | |
| 8CARSON-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P4-2: 511T544_SRT-S | |
| 8CARSON-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P1-2: LN 511_SRT-S-A | |
| 8CARSON-AE2-094 TP 500.0 kV Ckt 1 line | DVP_P1-2: LN 511_SRT-S | |
| 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line | DVP_P1-2: LN 511_SRT-S | |
| 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line | DVP_P4-2: 51192_SRT-S | |
| 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line | DVP_P4-2: 51172_SRT-S | |
| 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line | DVP_P4-2: 511T544_SRT-S | |
| AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line | DVP_P1-2: LN 511_SRT-S | |
| AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line | DVP_P4-2: 51192_SRT-S | |
| AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line | DVP_P4-2: 51172_SRT-S | |
| AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 line | DVP_P4-2: 511T544_SRT-S |