AG2-215 Phase I Study Report

v1.00 released 2025-10-29 21:49

Garner DP-Lancaster 115 kV

36.92 MW Capacity / 0.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Waller Solar I, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed an uprate to a planned/existing Solar facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — Lancaster County, Virginia. This project is an increase to the developer’s AD2-074/AF1-042/AG1-038/AG2-005 project(s), which will share the same Point of Interconnection. The AG2-215 project is a 36.92 MW Capacity only uprate to the previous project(s). The total installed facilities will have a capability of 196.0 MW with 114.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-215
Project Name:
Garner DP-Lancaster 115 kV
Project Developer Name:
Waller Solar I, LLC
State:
Virginia
County:
Lancaster
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
196.0
MWE:
0.0
MWC:
36.92
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AG2-215 will interconnect on the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) transmission system as an uprate to AD2-074, AF1-042 & AG1-038, sharing the POI and Attachment Facilities.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AG2-215 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-215Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$48,047,118$48,047,118
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$48,047,118$48,047,118

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AG2-215

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AG2-215 Project due at DP1
ABA - B
AG2-215$4,804,712$147,680$4,657,032

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Interconnection Facilities
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)AG2-005/AG2-215 will be sharing a POI and the TOIF with AD2-074, AF1-042, and AG1-038, so there are no associated interconnection costs for this project. Should the previous project(s) AD2-074, AF1-042, and AG1-038 withdraw from the Interconnection Queue, AG2-005 will assume responsibility of the TOIF, SANU, and Network Upgrade costs identified in the AD2-074, AF1-042, and AG1-038 study report(s) for interconnection to the Dominion System. AG2-005 and AG2-215 will also be sharing a POI and the TOIF.$0 $0 (See Note 1)

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 36 to 40 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Note 1: A Common Use Upgrade is a Network Upgrade that is needed for the interconnection of Generating Facilities or Merchant Transmission Facilities of more than one Project Developer or Eligible Customer and which is the shared responsibility of each Project Developer or Eligible Customer. If multiple Project Developers request to connect to the same interconnection substation, the Transmission Owner will determine the cost to accommodate all the requests at the substation. The cost for the interconnection will be allocated in proportion to the number of required terminations into the substation.

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2028 load flow model and the results were verified by Dominion.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-215 was evaluated as a 0.0 MW (36.92 MW Capacity) injection in the Dominion area.

AG2-215 was evaluated as part of a plant. The plant consists of AG2-215, AG2-005. The total Energy output of the plant was evaluated at its maximum seasonal capability of 196.0 MW (20.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
3GARNER-AE1-155 TAP 115.0 kV Ckt 1 line
DVP_P1-2: LN 65_SRT-A-1
SingleAC107.61 %203.98B219.536.91
GD2DVP
3GREYSPT-3HARMONY 115.0 kV Ckt 1 line
DVP_P1-2: LN 1059_SRT-A
SingleAC116.8 %269.78B315.0936.89
GD2DVP
3LANCAST-3OCRAN 115.0 kV Ckt 1 line
DVP_P1-2: LN 1059_SRT-A
SingleAC145.78 %219.96B320.6736.89
GD2DVP
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer
DVP_P1-3: 6NORNECK-TX#6_SRT-A
SingleAC118.91 %190.54B226.5717.34
GD2DVP
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
DVP_P1-3: 6NORNECK-TX#4_SRT-A
SingleAC133.22 %177.38B236.3117.98
GD2DVP
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
DVP_P1-2: LN 65_SRT-A-1
SingleAC121.19 %177.38B214.9720.14
GD2DVP
3OCRAN-3WHIT STONE 115.0 kV Ckt 1 line
DVP_P1-2: LN 1059_SRT-A
SingleAC142.85 %219.96B314.2236.89
GD2DVP
3RAPP TR-3GREYSPT 115.0 kV Ckt 1 line
DVP_P1-2: LN 1059_SRT-A
SingleAC114.8 %139.12B159.7118.44
GD2DVP
3RAPP TR-3GREYSPT 115.0 kV Ckt 2 line
DVP_P1-2: LN 1059_SRT-A
SingleAC114.8 %139.12B159.7118.44
GD2DVP
6AQUI_HARB_B-6GARSVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 2157_SRT-A
SingleAC125.38 %717.22B899.284.01
GD2DVP
6AQUI_HARB_B-6GARSVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 2104_SRT-A
SingleAC119.53 %717.22B857.314.01
GD2DVP
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC122.85 %559.3B687.097.19
GD2DVP
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC103.79 %559.3B580.477.23
GD2DVP
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC138.81 %548.02B760.687.19
GD2DVP
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC119.94 %548.02B657.287.23
GD2DVP
6CHCKAHM-6ELKO 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC110.39 %678.68B749.184.7
GD2DVP
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
DVP_P1-2: LN 567_SRT-A
SingleAC119.77 %935.39B1120.317.08
GD2DVP
6CHESTF A-6IRON208 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC111.61 %663.64B740.712.82
GD2DVP
6CHESTF A-6IRON208 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC108.5 %663.64B720.052.22
GD2DVP
6COMORN-6BIRCHWD 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC124.42 %548.02B681.857.19
GD2DVP
6COMORN-6BIRCHWD 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC104.98 %548.02B575.37.23
GD2DVP
6CRANES-6SPARTAN 230.0 kV Ckt 1 line
DVP_P1-2: LN 9296_SRT-A
SingleAC105.06 %984.18B1033.934.38
GD2DVP
6CRANES-6SPARTAN 230.0 kV Ckt 1 line
DVP_P1-2: LN 2119_SRT-A
SingleAC105.03 %984.18B1033.724.38
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
PEPCO_P1_5070_SRT-A
SingleAC152.59 %1331.98B2032.492.82
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
AP_P1-2_PE-500-406T_SRT-A
SingleAC109.83 %1331.98B1462.932.04
GD2DVP
6ELMONT-6HANOVER 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC105.87 %1123.3B1189.213.02
GD2DVP
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
DVP_P1-2: LN 557_SRT-S
SingleAC126.74 %888.3B1125.814.48
GD2DVP
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
DVP_P1-2: LN 576_SRT-S
SingleAC112.65 %888.3B1000.693.01
GD2DVP
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer
DVP_P1-2: LN 557_SRT-S
SingleAC127.13 %879.84B1118.554.46
GD2DVP
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer
DVP_P1-2: LN 576_SRT-S
SingleAC113.21 %879.84B996.082.99
GD2DVP
6FINES-6FREDBRG 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC138.73 %548.02B760.247.19
GD2DVP
6FINES-6FREDBRG 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC119.84 %548.02B656.737.23
GD2DVP
6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC178.97 %1123.3B2010.342.8
GD2DVP
6FREDBRG-6CRANES 230.0 kV Ckt 1 line
DVP_P1-2: LN 9296_SRT-A
SingleAC113.91 %984.18B1121.114.38
GD2DVP
6FREDBRG-6CRANES 230.0 kV Ckt 1 line
DVP_P1-2: LN 2119_SRT-A
SingleAC113.9 %984.18B1120.954.38
GD2DVP
6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line
DVP_P1-2: LN 2157_SRT-A
SingleAC116.81 %717.22B837.814.01
GD2DVP
6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line
DVP_P1-2: LN 2104_SRT-A
SingleAC110.78 %717.22B794.574.01
GD2DVP
6HANOVER-6FOUR RIVERS 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC100.18 %1123.3B1125.323.02
GD2DVP
6IRON208-6SOUWEST 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC103.96 %663.64B689.922.82
GD2DVP
6IRON208-6SOUWEST 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC100.72 %663.64B668.442.22
GD2DVP
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
DVP_P1-2: LN 563_SRT-S
SingleAC137.15 %1057.5B1450.332.71
GD2DVP
6NORNECK-6SANDERS 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC115.31 %571.52B659.047.21
GD2DVP
6NRTHEST-6ELMONT 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC106.04 %678.68B719.663.29
GD2DVP
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC111.12 %571.52B635.057.21
GD2DVP
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC113.11 %571.52B646.447.21
GD2DVP
6SPARTAN-6STAFORD 230.0 kV Ckt 1 line
DVP_P1-2: LN 9296_SRT-A
SingleAC105.01 %984.18B1033.524.38
GD2DVP
6SPARTAN-6STAFORD 230.0 kV Ckt 1 line
DVP_P1-2: LN 2119_SRT-A
SingleAC104.99 %984.18B1033.324.38
GD2DVP
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC134.25 %1478.62B1985.012.79
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
PEPCO_P1_5070_SRT-A
SingleAC140.61 %1478.62B2079.092.82
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
AP_P1-2_PE-500-406T_SRT-A
SingleAC102.09 %1478.62B1509.532.04
GD2DVP
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC111.62 %571.52B637.967.21
GD2DVP
8BRAMBLETON-AH1-727 TP 500.0 kV Ckt 1 line
DVP_P1-2: LN 9344_SRT-A
SingleAC106.63 %3256.16B3472.076.95
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC139.66 %3220.44B4497.834.29
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC127.51 %3220.44B4106.244.67
GD2DVP
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
SingleAC132.78 %4070.2B5404.527.22
GD2DVP
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-S
SingleAC123.02 %4070.2B5007.087.14
GD2DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC146.98 %2442.12B3589.459.5
GD2DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC145.46 %2442.12B3552.39.0
GD2DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Base Case
SingleAC102.62 %2442.12A2506.28.24
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC173.01 %4070.2B7041.7810.07
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC153.9 %4070.2B6264.08.61
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Base Case
SingleAC118.98 %4070.2A4842.757.79
GD2DVP
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-S
SingleAC126.22 %4070.2B5137.227.39
GD2DVP
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
SingleAC124.64 %4070.2B5073.157.14
GD2DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC130.67 %3220.44B4208.15.25
GD2DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC130.56 %3220.44B4204.635.23
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC175.45 %3220.44B5650.147.02
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC136.69 %3220.44B4402.076.31
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Base Case
SingleAC113.34 %3193.18A3619.134.3
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC172.64 %3220.44B5559.887.03
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC171.66 %3220.44B5528.277.18
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Base Case
SingleAC118.49 %3193.18A3783.565.03
GD2DVP/PJM
8POSSUM-BURCHES 500.0 kV Ckt 1 line
AP_P1-2_PE-500-406T_SRT-A
SingleAC105.05 %2913.06B3060.214.57
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC179.85 %3220.44B5791.827.03
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC175.06 %3220.44B5637.76.92
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Base Case
SingleAC129.41 %3220.44A4167.614.94
GD2DVP
AD2-074 TAP-AG1-146 TP 115.0 kV Ckt 1 line
DVP_P1-2: LN 1059_SRT-A
SingleAC135.42 %203.98B276.2436.89
GD2DVP
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
DVP_P1-2: LN 65_SRT-A-1
SingleAC175.73 %203.98B358.4636.89
GD2DVP
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
DVP_P1-2: LN 1021_SRT-A
SingleAC155.02 %203.98B316.2136.89
GD2DVP
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
Base Case
SingleAC113.07 %203.98A230.6519.59
GD2DVP
AE1-157 TAP-6LDYSMITH CT 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC137.7 %1478.62B2036.012.79
GD2DVP
AF1-114 TP-6DAHLGREN 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC118.84 %571.52B679.27.19
GD2DVP
AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC127.21 %559.3B711.497.19
GD2DVP
AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC108.1 %559.3B604.67.23
GD2DVP
AG1-135 TP-3GARNER 115.0 kV Ckt 1 line
DVP_P1-2: LN 65_SRT-A-1
SingleAC115.34 %203.98B235.2736.91
GD2DVP
AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
DVP_P1-2: LN 1059_SRT-A
SingleAC174.07 %203.98B355.0636.89
GD2DVP
AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
DVP_P1-2: LN 65_SRT-A-4
SingleAC114.08 %203.98B232.736.91
GD2DVP
AG2-469 TP-6OAKGROV 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC115.13 %571.52B657.977.21

Details for 3GARNER-AE1-155 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
3GARNER-AE1-155 TAP 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 65_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.61 %
Rating:203.98 MVA
Rating Type:B
MVA to Mitigate:219.5
MW Contribution:36.91
Bus #Bus NameTypeMW Contribution
970575AG2-366 GEN
50/50
19.992
962971AG1-146 GEN
Solar/Wind Harmer
17.993
962981AG1-147 GEN
Solar/Wind Harmer
41.983
970327AG2-215 GEN
Solar/Wind Harmer
36.905
962861AG1-135 GEN
Solar/Wind Harmer
35.985
970009AG2-005 GEN
Solar/Wind Harmer
8.397
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.023
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.07
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.022
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.023
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.014
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.105
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3GREYSPT-3HARMONY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1059_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3GREYSPT-3HARMONY 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1059_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.8 %
Rating:269.78 MVA
Rating Type:B
MVA to Mitigate:315.09
MW Contribution:36.89
Bus #Bus NameTypeMW Contribution
958261AF2-120 GEN
Solar/Wind Harmer
37.166
3141913WHIT STONE
Solar/Wind Harmer
1.123
3141783LANCAST
Solar/Wind Harmer
0.674
3141783LANCAST
Solar/Wind Harmer
0.45
3138133OCRAN
Solar/Wind Harmer
0.337
962981AG1-147 GEN
Solar/Wind Harmer
41.961
970327AG2-215 GEN
Solar/Wind Harmer
36.886
970575AG2-366 GEN
50/50
19.982
316404AE1-155 C
Solar/Wind Harmer
0.253
962971AG1-146 GEN
Solar/Wind Harmer
17.983
970009AG2-005 GEN
Solar/Wind Harmer
8.392
966661AG1-536 GEN
50/50
31.97
3138133OCRAN
Solar/Wind Harmer
0.674
962861AG1-135 GEN
Solar/Wind Harmer
35.967
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.051
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.16
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.051
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.053
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.032
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.238
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3LANCAST-3OCRAN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1059_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3LANCAST-3OCRAN 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1059_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:145.78 %
Rating:219.96 MVA
Rating Type:B
MVA to Mitigate:320.67
MW Contribution:36.89
Bus #Bus NameTypeMW Contribution
3141783LANCAST
Solar/Wind Harmer
0.674
3141783LANCAST
Solar/Wind Harmer
0.45
962981AG1-147 GEN
Solar/Wind Harmer
41.963
970327AG2-215 GEN
Solar/Wind Harmer
36.888
966661AG1-536 GEN
50/50
31.972
962861AG1-135 GEN
Solar/Wind Harmer
35.968
970575AG2-366 GEN
50/50
19.982
316404AE1-155 C
Solar/Wind Harmer
0.253
962971AG1-146 GEN
Solar/Wind Harmer
17.984
970009AG2-005 GEN
Solar/Wind Harmer
8.393
958261AF2-120 GEN
Solar/Wind Harmer
37.167
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.049
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.152
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.049
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.051
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.031
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.227
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6NORNECK-TX#6_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-3: 6NORNECK-TX#6_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.91 %
Rating:190.54 MVA
Rating Type:B
MVA to Mitigate:226.57
MW Contribution:17.34
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
8.785
966661AG1-536 GEN
50/50
18.112
3141843SHACKLE
50/50
0.568
962861AG1-135 GEN
Solar/Wind Harmer
19.459
3138133OCRAN
Solar/Wind Harmer
0.174
971777AH1-397 GEN
Solar/Wind Harmer
0.277
3141766HARMONY
Solar/Wind Harmer
0.014
315759AF1-018 GEN
50/50
2.541
3141813NORNECK
Solar/Wind Harmer
0.83
970327AG2-215 GEN
Solar/Wind Harmer
17.344
962981AG1-147 GEN
Solar/Wind Harmer
17.234
3141783LANCAST
Solar/Wind Harmer
0.208
3141783LANCAST
Solar/Wind Harmer
0.139
3138133OCRAN
Solar/Wind Harmer
0.087
3141913WHIT STONE
Solar/Wind Harmer
0.265
3141873WAN 176
Solar/Wind Harmer
0.033
315662AE1-191 GEN
Solar/Wind Harmer
0.004
315666AE1-190 GEN
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
3.127
3138283WHITEMARSH
Solar/Wind Harmer
0.02
316059AD1-063 C
Solar/Wind Harmer
0
3150351NORNECKC2
50/50
8.933
970575AG2-366 GEN
50/50
8.207
3141843SHACKLE
50/50
0.568
315749AE2-041 GEN
50/50
2.541
316404AE1-155 C
Solar/Wind Harmer
0.143
970009AG2-005 GEN
Solar/Wind Harmer
3.946
962971AG1-146 GEN
Solar/Wind Harmer
7.386
316156AD2-030 GEN
Solar/Wind Harmer
0.123
3141873WAN 176
Solar/Wind Harmer
2.946
316280AD1-041 GEN
Solar/Wind Harmer
0.003
316203AE2-005 GEN
Solar/Wind Harmer
0
3141766HARMONY
Solar/Wind Harmer
0.953
3150341NORNECKC1
50/50
9.228
3150341NORNECKC1
50/50
9.154
963611AG1-210 GEN
50/50
2.953
316077AC2-138 C
Solar/Wind Harmer
0.004
958261AF2-120 GEN
Solar/Wind Harmer
21.056
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.021
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.063
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.119
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.063
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.074
CPLELTFEXP_CPLE->PJM
CLTF
0.072
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6NORNECK-TX#4_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-3: 6NORNECK-TX#4_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.22 %
Rating:177.38 MVA
Rating Type:B
MVA to Mitigate:236.31
MW Contribution:17.98
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
9.26
970575AG2-366 GEN
50/50
8.507
3141843SHACKLE
50/50
0.589
315749AE2-041 GEN
50/50
2.634
316404AE1-155 C
Solar/Wind Harmer
0.149
970009AG2-005 GEN
Solar/Wind Harmer
4.091
962971AG1-146 GEN
Solar/Wind Harmer
7.656
316156AD2-030 GEN
Solar/Wind Harmer
0.127
3141873WAN 176
Solar/Wind Harmer
3.054
316280AD1-041 GEN
Solar/Wind Harmer
0.003
316203AE2-005 GEN
Solar/Wind Harmer
0
3141766HARMONY
Solar/Wind Harmer
0.988
3150341NORNECKC1
50/50
9.566
3150341NORNECKC1
50/50
9.49
963611AG1-210 GEN
50/50
3.061
316077AC2-138 C
Solar/Wind Harmer
0.005
958261AF2-120 GEN
Solar/Wind Harmer
21.826
315759AF1-018 GEN
50/50
2.634
3141813NORNECK
Solar/Wind Harmer
0.86
970327AG2-215 GEN
Solar/Wind Harmer
17.979
962981AG1-147 GEN
Solar/Wind Harmer
17.865
3141783LANCAST
Solar/Wind Harmer
0.216
3141783LANCAST
Solar/Wind Harmer
0.144
3138133OCRAN
Solar/Wind Harmer
0.09
3141913WHIT STONE
Solar/Wind Harmer
0.274
3141873WAN 176
Solar/Wind Harmer
0.034
315662AE1-191 GEN
Solar/Wind Harmer
0.004
315666AE1-190 GEN
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
3.241
3138283WHITEMARSH
Solar/Wind Harmer
0.02
316059AD1-063 C
Solar/Wind Harmer
0
3150351NORNECKC2
50/50
9.107
966661AG1-536 GEN
50/50
18.775
3141843SHACKLE
50/50
0.589
962861AG1-135 GEN
Solar/Wind Harmer
20.171
3138133OCRAN
Solar/Wind Harmer
0.18
971777AH1-397 GEN
Solar/Wind Harmer
0.287
3141766HARMONY
Solar/Wind Harmer
0.015
316337AD2-073 GEN
Solar/Wind Helper
0.174
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.021
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.066
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.123
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.065
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.077
CPLELTFEXP_CPLE->PJM
CLTF
0.075
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 65_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-2: LN 65_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.19 %
Rating:177.38 MVA
Rating Type:B
MVA to Mitigate:214.97
MW Contribution:20.14
Bus #Bus NameTypeMW Contribution
3141813NORNECK
Solar/Wind Harmer
0.613
962981AG1-147 GEN
Solar/Wind Harmer
22.913
970327AG2-215 GEN
Solar/Wind Harmer
20.142
970575AG2-366 GEN
50/50
10.911
3150351NORNECKC2
50/50
6.601
316404AE1-155 C
Solar/Wind Harmer
0.138
962971AG1-146 GEN
Solar/Wind Harmer
9.82
970009AG2-005 GEN
Solar/Wind Harmer
4.583
966661AG1-536 GEN
50/50
17.458
3150351NORNECKC2
50/50
6.492
962861AG1-135 GEN
Solar/Wind Harmer
19.64
3150341NORNECKC1
50/50
6.819
3150341NORNECKC1
50/50
6.765
963611AG1-210 GEN
50/50
2.182
316077AC2-138 C
Solar/Wind Harmer
0.003
958261AF2-120 GEN
Solar/Wind Harmer
20.295
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.028
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.088
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.028
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.029
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.018
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.131
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3OCRAN-3WHIT STONE 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1059_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3OCRAN-3WHIT STONE 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1059_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:142.85 %
Rating:219.96 MVA
Rating Type:B
MVA to Mitigate:314.22
MW Contribution:36.89
Bus #Bus NameTypeMW Contribution
3141783LANCAST
Solar/Wind Harmer
0.674
3141783LANCAST
Solar/Wind Harmer
0.45
3138133OCRAN
Solar/Wind Harmer
0.337
962981AG1-147 GEN
Solar/Wind Harmer
41.962
970327AG2-215 GEN
Solar/Wind Harmer
36.887
958261AF2-120 GEN
Solar/Wind Harmer
37.167
966661AG1-536 GEN
50/50
31.971
3138133OCRAN
Solar/Wind Harmer
0.674
962861AG1-135 GEN
Solar/Wind Harmer
35.968
970575AG2-366 GEN
50/50
19.982
316404AE1-155 C
Solar/Wind Harmer
0.253
962971AG1-146 GEN
Solar/Wind Harmer
17.984
970009AG2-005 GEN
Solar/Wind Harmer
8.392
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.05
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.156
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.05
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.052
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.031
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.232
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3RAPP TR-3GREYSPT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1059_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3RAPP TR-3GREYSPT 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1059_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.8 %
Rating:139.12 MVA
Rating Type:B
MVA to Mitigate:159.71
MW Contribution:18.44
Bus #Bus NameTypeMW Contribution
3141913WHIT STONE
Solar/Wind Harmer
0.561
3141783LANCAST
Solar/Wind Harmer
0.337
3141783LANCAST
Solar/Wind Harmer
0.225
3138133OCRAN
Solar/Wind Harmer
0.168
962981AG1-147 GEN
Solar/Wind Harmer
20.981
970327AG2-215 GEN
Solar/Wind Harmer
18.443
966661AG1-536 GEN
50/50
15.985
3138133OCRAN
Solar/Wind Harmer
0.337
962861AG1-135 GEN
Solar/Wind Harmer
17.983
970575AG2-366 GEN
50/50
9.991
316404AE1-155 C
Solar/Wind Harmer
0.127
962971AG1-146 GEN
Solar/Wind Harmer
8.992
970009AG2-005 GEN
Solar/Wind Harmer
4.196
958261AF2-120 GEN
Solar/Wind Harmer
18.583
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.026
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.08
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.025
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.027
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.016
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.119
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3RAPP TR-3GREYSPT 115.0 kV Ckt 2 line l/o DVP_P1-2: LN 1059_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3RAPP TR-3GREYSPT 115.0 kV Ckt 2 line
Contingency Name:
DVP_P1-2: LN 1059_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.8 %
Rating:139.12 MVA
Rating Type:B
MVA to Mitigate:159.71
MW Contribution:18.44
Bus #Bus NameTypeMW Contribution
3141913WHIT STONE
Solar/Wind Harmer
0.561
3141783LANCAST
Solar/Wind Harmer
0.337
3141783LANCAST
Solar/Wind Harmer
0.225
3138133OCRAN
Solar/Wind Harmer
0.168
962981AG1-147 GEN
Solar/Wind Harmer
20.981
970327AG2-215 GEN
Solar/Wind Harmer
18.443
966661AG1-536 GEN
50/50
15.985
3138133OCRAN
Solar/Wind Harmer
0.337
962861AG1-135 GEN
Solar/Wind Harmer
17.983
970575AG2-366 GEN
50/50
9.991
316404AE1-155 C
Solar/Wind Harmer
0.127
962971AG1-146 GEN
Solar/Wind Harmer
8.992
970009AG2-005 GEN
Solar/Wind Harmer
4.196
958261AF2-120 GEN
Solar/Wind Harmer
18.583
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.026
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.08
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.025
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.027
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.016
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.119
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 6AQUI_HARB_B-6GARSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2157_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6AQUI_HARB_B-6GARSVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2157_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.38 %
Rating:717.22 MVA
Rating Type:B
MVA to Mitigate:899.28
MW Contribution:4.01
Bus #Bus NameTypeMW Contribution
3150331BIRCHWDA
50/50
68.134
3141316ARNOLDS
50/50
0.877
3150401LDYSMT4
50/50
22.339
3150371LDYSMT1
50/50
21.586
3150501FRIVERG
50/50
1.254
3150351NORNECKC2
50/50
1.568
970737AG2-469 GEN
Solar/Wind Harmer
9.422
3141906WESTMOR
Solar/Wind Harmer
0.079
971781AH1-399 GEN
Solar/Wind Harmer
0.219
316404AE1-155 C
Solar/Wind Harmer
0.029
970009AG2-005 GEN
Solar/Wind Harmer
0.913
962971AG1-146 GEN
Solar/Wind Harmer
1.872
316156AD2-030 GEN
Solar/Wind Harmer
0.07
3141873WAN 176
Solar/Wind Harmer
1.67
316280AD1-041 GEN
Solar/Wind Harmer
0.002
3141766HARMONY
Solar/Wind Harmer
1.216
316203AE2-005 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
0.464
316473AC1-191 GEN
Solar/Wind Harmer
0.294
3142433PROV 92
Adder
0.157
3142433PROV 92
Adder
0.157
3142416OLDCHRC
Solar/Wind Harmer
0.648
970293AG2-193 GEN
Solar/Wind Harmer
0.709
3142946ENON
Solar/Wind Harmer
0.022
316382AG1-145 C
Solar/Wind Harmer
0.001
3143096IRON208
Adder
0.264
3143096IRON208
Adder
0.259
3150921YORKTN3
Adder
1.572
3144216WINCHST
Adder
0.232
970133AG2-095 GEN
Solar/Wind Harmer
0.577
970129AG2-093 GEN
Solar/Wind Harmer
3.58
315778AD1-151 GEN
Solar/Wind Harmer
4.691
3150861SPRUNCD
Adder
0.269
965281AG1-393 GEN
Solar/Wind Harmer
0.619
961611AG1-000B GEN
Solar/Wind Harmer
1.53
3151221GRAVEL6
Adder
4.131
3151171GRAVELC
Adder
0.795
315839AE2-212 C
Solar/Wind Harmer
0
972197AH1-683 GEN
50/50
3.488
972219AH1-694 GEN
50/50
2.512
3150351NORNECKC2
50/50
1.542
966661AG1-536 GEN
50/50
3.716
972135AH1-637 GEN
Solar/Wind Harmer
2.022
316337AD2-073 GEN
Solar/Wind Harmer
0.148
3141726DUNNSVL
Solar/Wind Harmer
0.555
962861AG1-135 GEN
Solar/Wind Harmer
4.109
966881AG1-559 GEN
Solar/Wind Harmer
0.144
3138133OCRAN
Solar/Wind Harmer
0.062
3141766HARMONY
Solar/Wind Harmer
0.018
971777AH1-397 GEN
Solar/Wind Harmer
0.24
3141843SHACKLE
Adder
0.464
3142433PROV 92
Solar/Wind Harmer
0.322
3142433PROV 92
Adder
0.157
3142433PROV 92
Adder
0.157
3142416OLDCHRC
Solar/Wind Harmer
0.174
3142416OLDCHRC
Solar/Wind Harmer
0.067
971317AH1-138 GEN
Solar/Wind Harmer
0.499
316159AE1-175 C
Solar/Wind Harmer
0.056
944631AF1-128 GEN
Adder
30.632
3143096IRON208
Adder
0.264
3138126ROCKLANDING
Solar/Wind Harmer
0.028
3142543TWELFTH
Solar/Wind Harmer
0.006
970129AG2-093 GEN
Solar/Wind Harmer
1.685
316458AB2-190 GEN2
Solar/Wind Harmer
0.317
315671AE2-027_GEN
Solar/Wind Harmer
3.762
971069AG2-661 GEN
Solar/Wind Harmer
1.042
3150851SPRUNCC
Adder
0.269
971647AH1-324 GEN
Solar/Wind Harmer
2.468
961611AG1-000B GEN
Solar/Wind Harmer
3.01
3151171GRAVELC
Adder
0.604
3150411LDYSMT5
50/50
22.409
3150381LDYSMT2
50/50
21.446
972213AH1-691 GEN
50/50
3.628
972215AH1-692 GEN
50/50
3.628
963051AG1-154 GEN
50/50
2.791
944491AF1-114 GEN
Solar/Wind Harmer
0.001
316223AC1-118
Solar/Wind Harmer
0.142
3141813NORNECK
Solar/Wind Harmer
0.146
970327AG2-215 GEN
Solar/Wind Harmer
4.011
962981AG1-147 GEN
Solar/Wind Harmer
4.368
3141783LANCAST
Solar/Wind Harmer
0.065
3141783LANCAST
Solar/Wind Harmer
0.043
3138133OCRAN
Solar/Wind Harmer
0.031
3141913WHIT STONE
Solar/Wind Harmer
0.102
3141873WAN 176
Solar/Wind Harmer
0.019
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
2.692
316314AB2-024 C
Solar/Wind Harmer
0
972189AH1-679 GEN
Adder
1.471
3143873LANEXA
Solar/Wind Harmer
0.052
3142433PROV 92
Adder
0.157
3142433PROV 92
Adder
0.157
971167AH1-042 GEN
Solar/Wind Harmer
7.034
3138283WHITEMARSH
Solar/Wind Harmer
0.018
315976AC1-164 GENA
Solar/Wind Harmer
7.205
316169AC1-164_GENC
Solar/Wind Harmer
6.225
315975AC1-164 GENB
Solar/Wind Harmer
0.213
316312AB1-027
Solar/Wind Harmer
0.12
316132AB2-190 GEN1
Solar/Wind Harmer
0.317
971285AH1-108 GEN
Adder
0.441
316369SG1_INVT
Solar/Wind Harmer
0.002
972265AH1-717 GEN
Adder
4.412
3151201GRAVEL4
Adder
4.136
3151191GRAVEL3
Adder
4.084
3151211GRAVEL5
Adder
4.084
3141426STAFORD
Solar/Wind Helper
0.047
957191AF2-013 GEN
50/50
28.808
3150391LDYSMT3
50/50
22.297
972195AH1-682 GEN
50/50
2.93
3150341NORNECKC1
50/50
1.62
3150341NORNECKC1
50/50
1.607
963611AG1-210 GEN
50/50
0.518
316468AD1-105 GEN
Solar/Wind Harmer
-0.054
316077AC2-138 C
Solar/Wind Harmer
0.001
315673AE1-157 GEN
Solar/Wind Harmer
9.444
958261AF2-120 GEN
Solar/Wind Harmer
4.32
957411AF2-035 GEN
Solar/Wind Harmer
5.322
970317AG2-208 GEN
Solar/Wind Harmer
4.93
966871AG1-558 GEN
Solar/Wind Harmer
0.101
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.007
3142296MT RD221
Adder
0.208
3150691DARBY 3
Adder
4.672
3150701DARBY 4
Adder
4.661
3150681DARBY 2
Adder
4.655
3150671DARBY 1
Adder
4.65
3142366NRTHEST
Adder
0.209
944641AF1-129 GEN
Adder
27.858
316033AB2-134 GEN
Solar/Wind Harmer
0.003
315697AD1-025 GEN
Solar/Wind Harmer
0.066
316240AF1-291 C
Solar/Wind Harmer
0
LAGNLTFEXP_LAGN->PJM
CLTF
1.844
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.3
TVALTFEXP_TVA->PJM
CLTF
0.932
NYPJM->LTFIMP_NY
CLTF
0.726
LGEELTFEXP_LGEE->PJM
CLTF
0.356
WECLTFEXP_WEC->PJM
CLTF
0.179
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.206
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.222
MECLTFEXP_MEC->PJM
CLTF
0.941
SIGELTFEXP_SIGE->PJM
CLTF
0.029
CPLELTFEXP_CPLE->PJM
CLTF
2.387
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.943

Details for 6AQUI_HARB_B-6GARSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2104_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6AQUI_HARB_B-6GARSVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2104_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.53 %
Rating:717.22 MVA
Rating Type:B
MVA to Mitigate:857.31
MW Contribution:4.01
Bus #Bus NameTypeMW Contribution
3150331BIRCHWDA
50/50
68.134
3141316ARNOLDS
50/50
0.877
3150401LDYSMT4
50/50
22.339
3150371LDYSMT1
50/50
21.586
3150501FRIVERG
50/50
1.254
3150351NORNECKC2
50/50
1.568
970737AG2-469 GEN
Solar/Wind Harmer
9.422
3141906WESTMOR
Solar/Wind Harmer
0.079
971781AH1-399 GEN
Solar/Wind Harmer
0.219
316404AE1-155 C
Solar/Wind Harmer
0.029
970009AG2-005 GEN
Solar/Wind Harmer
0.913
962971AG1-146 GEN
Solar/Wind Harmer
1.872
316156AD2-030 GEN
Solar/Wind Harmer
0.07
3141873WAN 176
Solar/Wind Harmer
1.67
316280AD1-041 GEN
Solar/Wind Harmer
0.002
3141766HARMONY
Solar/Wind Harmer
1.216
316203AE2-005 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
0.464
316473AC1-191 GEN
Solar/Wind Harmer
0.294
3142433PROV 92
Adder
0.157
3142433PROV 92
Adder
0.157
3142416OLDCHRC
Solar/Wind Harmer
0.648
970293AG2-193 GEN
Solar/Wind Harmer
0.709
3142946ENON
Solar/Wind Harmer
0.022
316382AG1-145 C
Solar/Wind Harmer
0.001
3143096IRON208
Adder
0.264
3143096IRON208
Adder
0.259
3150921YORKTN3
Adder
1.572
3144216WINCHST
Adder
0.232
970133AG2-095 GEN
Solar/Wind Harmer
0.577
970129AG2-093 GEN
Solar/Wind Harmer
3.58
315778AD1-151 GEN
Solar/Wind Harmer
4.691
3150861SPRUNCD
Adder
0.269
965281AG1-393 GEN
Solar/Wind Harmer
0.619
961611AG1-000B GEN
Solar/Wind Harmer
1.53
3151221GRAVEL6
Adder
4.131
3151171GRAVELC
Adder
0.795
315839AE2-212 C
Solar/Wind Harmer
0
957191AF2-013 GEN
50/50
28.808
3150391LDYSMT3
50/50
22.297
972195AH1-682 GEN
50/50
2.93
3150341NORNECKC1
50/50
1.62
3150341NORNECKC1
50/50
1.607
963611AG1-210 GEN
50/50
0.518
316468AD1-105 GEN
Solar/Wind Harmer
-0.054
316077AC2-138 C
Solar/Wind Harmer
0.001
315673AE1-157 GEN
Solar/Wind Harmer
9.444
958261AF2-120 GEN
Solar/Wind Harmer
4.32
957411AF2-035 GEN
Solar/Wind Harmer
5.322
970317AG2-208 GEN
Solar/Wind Harmer
4.93
966871AG1-558 GEN
Solar/Wind Harmer
0.101
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.007
3142296MT RD221
Adder
0.208
3150691DARBY 3
Adder
4.672
3150701DARBY 4
Adder
4.661
3150681DARBY 2
Adder
4.655
3150671DARBY 1
Adder
4.65
3142366NRTHEST
Adder
0.209
944641AF1-129 GEN
Adder
27.858
316033AB2-134 GEN
Solar/Wind Harmer
0.003
315697AD1-025 GEN
Solar/Wind Harmer
0.066
316240AF1-291 C
Solar/Wind Harmer
0
3141346CRANES
50/50
0.542
972197AH1-683 GEN
50/50
3.488
972219AH1-694 GEN
50/50
2.512
3150351NORNECKC2
50/50
1.542
966661AG1-536 GEN
50/50
3.716
972135AH1-637 GEN
Solar/Wind Harmer
2.022
316337AD2-073 GEN
Solar/Wind Harmer
0.148
3141726DUNNSVL
Solar/Wind Harmer
0.555
962861AG1-135 GEN
Solar/Wind Harmer
4.109
966881AG1-559 GEN
Solar/Wind Harmer
0.144
3138133OCRAN
Solar/Wind Harmer
0.062
3141766HARMONY
Solar/Wind Harmer
0.018
971777AH1-397 GEN
Solar/Wind Harmer
0.24
3141843SHACKLE
Adder
0.464
3142433PROV 92
Solar/Wind Harmer
0.322
3142433PROV 92
Adder
0.157
3142433PROV 92
Adder
0.157
3142416OLDCHRC
Solar/Wind Harmer
0.174
3142416OLDCHRC
Solar/Wind Harmer
0.067
971317AH1-138 GEN
Solar/Wind Harmer
0.499
316159AE1-175 C
Solar/Wind Harmer
0.056
944631AF1-128 GEN
Adder
30.632
3143096IRON208
Adder
0.264
3138126ROCKLANDING
Solar/Wind Harmer
0.028
3142543TWELFTH
Solar/Wind Harmer
0.006
970129AG2-093 GEN
Solar/Wind Harmer
1.685
316458AB2-190 GEN2
Solar/Wind Harmer
0.317
315671AE2-027_GEN
Solar/Wind Harmer
3.762
971069AG2-661 GEN
Solar/Wind Harmer
1.042
3150851SPRUNCC
Adder
0.269
971647AH1-324 GEN
Solar/Wind Harmer
2.468
961611AG1-000B GEN
Solar/Wind Harmer
3.01
3151171GRAVELC
Adder
0.604
3150411LDYSMT5
50/50
22.409
3150381LDYSMT2
50/50
21.446
972213AH1-691 GEN
50/50
3.628
972215AH1-692 GEN
50/50
3.628
963051AG1-154 GEN
50/50
2.791
944491AF1-114 GEN
Solar/Wind Harmer
0.001
316223AC1-118
Solar/Wind Harmer
0.142
3141813NORNECK
Solar/Wind Harmer
0.146
970327AG2-215 GEN
Solar/Wind Harmer
4.011
962981AG1-147 GEN
Solar/Wind Harmer
4.368
3141783LANCAST
Solar/Wind Harmer
0.065
3141783LANCAST
Solar/Wind Harmer
0.043
3138133OCRAN
Solar/Wind Harmer
0.031
3141913WHIT STONE
Solar/Wind Harmer
0.102
3141873WAN 176
Solar/Wind Harmer
0.019
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
2.692
316314AB2-024 C
Solar/Wind Harmer
0
972189AH1-679 GEN
Adder
1.471
3143873LANEXA
Solar/Wind Harmer
0.052
3142433PROV 92
Adder
0.157
3142433PROV 92
Adder
0.157
971167AH1-042 GEN
Solar/Wind Harmer
7.034
3138283WHITEMARSH
Solar/Wind Harmer
0.018
315976AC1-164 GENA
Solar/Wind Harmer
7.205
316169AC1-164_GENC
Solar/Wind Harmer
6.225
315975AC1-164 GENB
Solar/Wind Harmer
0.213
316312AB1-027
Solar/Wind Harmer
0.12
316132AB2-190 GEN1
Solar/Wind Harmer
0.317
971285AH1-108 GEN
Adder
0.441
316369SG1_INVT
Solar/Wind Harmer
0.002
972265AH1-717 GEN
Adder
4.412
3151201GRAVEL4
Adder
4.136
3151191GRAVEL3
Adder
4.084
3151211GRAVEL5
Adder
4.084
3141426STAFORD
Solar/Wind Helper
0.047
LAGNLTFEXP_LAGN->PJM
CLTF
1.844
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.3
TVALTFEXP_TVA->PJM
CLTF
0.932
NYPJM->LTFIMP_NY
CLTF
0.726
LGEELTFEXP_LGEE->PJM
CLTF
0.356
WECLTFEXP_WEC->PJM
CLTF
0.179
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.206
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.222
MECLTFEXP_MEC->PJM
CLTF
0.941
SIGELTFEXP_SIGE->PJM
CLTF
0.029
CPLELTFEXP_CPLE->PJM
CLTF
2.387
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.943

Details for 6ARNOLDS-6COMORN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.85 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:687.09
MW Contribution:7.19
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
2.956
966661AG1-536 GEN
50/50
6.849
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
971353AH1-157 GEN
50/50
7.408
970017AG2-010 GEN
50/50
4.699
3150641CHESTS8
50/50
0.203
944631AF1-128 GEN
50/50
31.925
972135AH1-637 GEN
Solar/Wind Harmer
4.389
316337AD2-073 GEN
Solar/Wind Harmer
0.299
3141726DUNNSVL
Solar/Wind Harmer
1.044
962861AG1-135 GEN
Solar/Wind Harmer
7.523
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
971317AH1-138 GEN
Solar/Wind Harmer
0.613
316159AE1-175 C
Solar/Wind Harmer
0.065
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3142416OLDCHRC
Solar/Wind Harmer
0.149
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.6
315759AF1-018 GEN
50/50
4.946
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150611CHESTG7
50/50
0.401
3150631CHESTG8
50/50
0.394
971047AG2-646 GEN
50/50
11.221
972263AH1-716 GEN
50/50
32.871
944491AF1-114 GEN
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Harmer
0.296
3141813NORNECK
Solar/Wind Harmer
0.279
970327AG2-215 GEN
Solar/Wind Harmer
7.194
962981AG1-147 GEN
Solar/Wind Harmer
7.685
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.051
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
0.029
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.081
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
9.122
315976AC1-164 GENA
Solar/Wind Harmer
8.292
316169AC1-164_GENC
Solar/Wind Harmer
7.163
315975AC1-164 GENB
Solar/Wind Harmer
0.245
316312AB1-027
Solar/Wind Harmer
0.102
972265AH1-717 GEN
Adder
4.377
3151201GRAVEL4
Adder
4.104
3151191GRAVEL3
Adder
4.052
3151211GRAVEL5
Adder
4.052
3141426STAFORD
Solar/Wind Helper
0.031
3141316ARNOLDS
50/50
2.018
3150351NORNECKC2
50/50
3.006
970575AG2-366 GEN
50/50
3.66
315749AE2-041 GEN
50/50
4.946
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150921YORKTN3
50/50
1.929
3144216WINCHST
50/50
0.279
3151161SURRY 1
50/50
2.166
970737AG2-469 GEN
Solar/Wind Harmer
20.178
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.637
962971AG1-146 GEN
Solar/Wind Harmer
3.294
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.61
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.855
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.668
3142416OLDCHRC
Solar/Wind Harmer
0.555
3151221GRAVEL6
Adder
4.099
3151171GRAVELC
Adder
0.789
957191AF2-013 GEN
50/50
65.713
3150341NORNECKC1
50/50
3.105
3150341NORNECKC1
50/50
3.08
963611AG1-210 GEN
50/50
0.994
3150621CHESTS7
50/50
0.184
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
7.962
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.007
LAGNLTFEXP_LAGN->PJM
CLTF
1.483
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.388
TVALTFEXP_TVA->PJM
CLTF
0.749
NYPJM->LTFIMP_NY
CLTF
0.564
LGEELTFEXP_LGEE->PJM
CLTF
0.274
WECLTFEXP_WEC->PJM
CLTF
0.137
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.711
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.577
MECLTFEXP_MEC->PJM
CLTF
0.732
SIGELTFEXP_SIGE->PJM
CLTF
0.022
CPLELTFEXP_CPLE->PJM
CLTF
1.997
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.895

Details for 6ARNOLDS-6COMORN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.79 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:580.47
MW Contribution:7.23
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
4.976
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
972263AH1-716 GEN
50/50
35.649
3150611CHESTG7
50/50
0.379
3150631CHESTG8
50/50
0.372
971047AG2-646 GEN
50/50
10.599
944491AF1-114 GEN
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Harmer
0.297
3141813NORNECK
Solar/Wind Harmer
0.28
970327AG2-215 GEN
Solar/Wind Harmer
7.232
962981AG1-147 GEN
Solar/Wind Harmer
7.729
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.074
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.168
3141873WAN 176
Solar/Wind Harmer
0.03
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.097
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
8.942
315976AC1-164 GENA
Solar/Wind Harmer
8.275
316169AC1-164_GENC
Solar/Wind Harmer
7.149
315975AC1-164 GENB
Solar/Wind Harmer
0.245
972265AH1-717 GEN
Adder
4.429
3151201GRAVEL4
Adder
4.152
3151191GRAVEL3
Adder
4.099
3151211GRAVEL5
Adder
4.099
3141426STAFORD
Solar/Wind Helper
0.029
957191AF2-013 GEN
50/50
65.968
3150341NORNECKC1
50/50
3.119
3150341NORNECKC1
50/50
3.094
963611AG1-210 GEN
50/50
0.998
3150621CHESTS7
50/50
0.174
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
8.003
316075AC2-137 C
Solar/Wind Harmer
0.018
3142946ENON
Solar/Wind Harmer
0.007
3141316ARNOLDS
50/50
2.026
3150351NORNECKC2
50/50
3.02
970575AG2-366 GEN
50/50
3.68
315749AE2-041 GEN
50/50
4.976
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
3150921YORKTN3
50/50
2.003
3144216WINCHST
50/50
0.289
3151161SURRY 1
50/50
2.191
970737AG2-469 GEN
Solar/Wind Harmer
20.26
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.646
962971AG1-146 GEN
Solar/Wind Harmer
3.312
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.629
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.866
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.022
3151221GRAVEL6
Adder
4.147
3151171GRAVELC
Adder
0.798
970293AG2-193 GEN
Solar/Wind Harmer
0.603
3150351NORNECKC2
50/50
2.97
966661AG1-536 GEN
50/50
6.884
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
971353AH1-157 GEN
50/50
7.642
970017AG2-010 GEN
50/50
4.875
3150641CHESTS8
50/50
0.192
944631AF1-128 GEN
50/50
30.156
3152331SURRY 2
50/50
2.455
972135AH1-637 GEN
Solar/Wind Harmer
4.407
316337AD2-073 GEN
Solar/Wind Harmer
0.3
3141726DUNNSVL
Solar/Wind Harmer
1.049
962861AG1-135 GEN
Solar/Wind Harmer
7.561
3138133OCRAN
Solar/Wind Harmer
0.104
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.365
3142433PROV 92
Solar/Wind Harmer
0.422
971317AH1-138 GEN
Solar/Wind Harmer
0.633
316159AE1-175 C
Solar/Wind Harmer
0.067
3138126ROCKLANDING
Solar/Wind Harmer
0.034
3151171GRAVELC
Adder
0.607
LAGNLTFEXP_LAGN->PJM
CLTF
1.213
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.047
TVALTFEXP_TVA->PJM
CLTF
0.609
NYPJM->LTFIMP_NY
CLTF
0.465
LGEELTFEXP_LGEE->PJM
CLTF
0.185
WECLTFEXP_WEC->PJM
CLTF
0.092
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.061
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.057
MECLTFEXP_MEC->PJM
CLTF
0.525
SIGELTFEXP_SIGE->PJM
CLTF
0.016
CPLELTFEXP_CPLE->PJM
CLTF
1.912
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.152

Details for 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.81 %
Rating:548.02 MVA
Rating Type:B
MVA to Mitigate:760.68
MW Contribution:7.19
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
2.956
966661AG1-536 GEN
50/50
6.849
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
971353AH1-157 GEN
50/50
7.408
970017AG2-010 GEN
50/50
4.699
3150641CHESTS8
50/50
0.203
944631AF1-128 GEN
50/50
31.925
972135AH1-637 GEN
Solar/Wind Harmer
4.389
316337AD2-073 GEN
Solar/Wind Harmer
0.299
3141726DUNNSVL
Solar/Wind Harmer
1.044
962861AG1-135 GEN
Solar/Wind Harmer
7.523
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
971317AH1-138 GEN
Solar/Wind Harmer
0.613
316159AE1-175 C
Solar/Wind Harmer
0.065
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3142416OLDCHRC
Solar/Wind Harmer
0.149
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.6
957191AF2-013 GEN
50/50
65.713
3150341NORNECKC1
50/50
3.105
3150341NORNECKC1
50/50
3.08
963611AG1-210 GEN
50/50
0.994
3150621CHESTS7
50/50
0.184
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
7.962
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.007
315759AF1-018 GEN
50/50
4.946
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150611CHESTG7
50/50
0.401
3150631CHESTG8
50/50
0.394
971047AG2-646 GEN
50/50
11.221
972263AH1-716 GEN
50/50
32.871
944491AF1-114 GEN
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Harmer
0.296
3141813NORNECK
Solar/Wind Harmer
0.279
970327AG2-215 GEN
Solar/Wind Harmer
7.194
962981AG1-147 GEN
Solar/Wind Harmer
7.685
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.051
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
0.029
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.081
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
9.122
315976AC1-164 GENA
Solar/Wind Harmer
8.292
316169AC1-164_GENC
Solar/Wind Harmer
7.163
315975AC1-164 GENB
Solar/Wind Harmer
0.245
316312AB1-027
Solar/Wind Harmer
0.102
972265AH1-717 GEN
Adder
4.377
3151201GRAVEL4
Adder
4.104
3151191GRAVEL3
Adder
4.052
3151211GRAVEL5
Adder
4.052
3141426STAFORD
Solar/Wind Helper
0.031
3150331BIRCHWDA
50/50
158.356
3141316ARNOLDS
50/50
2.018
3150351NORNECKC2
50/50
3.006
970575AG2-366 GEN
50/50
3.66
315749AE2-041 GEN
50/50
4.946
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150921YORKTN3
50/50
1.929
3144216WINCHST
50/50
0.279
3151161SURRY 1
50/50
2.166
970737AG2-469 GEN
Solar/Wind Harmer
20.178
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.637
962971AG1-146 GEN
Solar/Wind Harmer
3.294
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.61
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.855
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.668
3142416OLDCHRC
Solar/Wind Harmer
0.555
3151221GRAVEL6
Adder
4.099
3151171GRAVELC
Adder
0.789
LAGNLTFEXP_LAGN->PJM
CLTF
1.483
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.388
TVALTFEXP_TVA->PJM
CLTF
0.749
NYPJM->LTFIMP_NY
CLTF
0.564
LGEELTFEXP_LGEE->PJM
CLTF
0.274
WECLTFEXP_WEC->PJM
CLTF
0.137
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.711
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.577
MECLTFEXP_MEC->PJM
CLTF
0.732
SIGELTFEXP_SIGE->PJM
CLTF
0.022
CPLELTFEXP_CPLE->PJM
CLTF
1.997
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.895

Details for 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.94 %
Rating:548.02 MVA
Rating Type:B
MVA to Mitigate:657.28
MW Contribution:7.23
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
4.976
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
972263AH1-716 GEN
50/50
35.649
3150611CHESTG7
50/50
0.379
3150631CHESTG8
50/50
0.372
971047AG2-646 GEN
50/50
10.599
944491AF1-114 GEN
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Harmer
0.297
3141813NORNECK
Solar/Wind Harmer
0.28
970327AG2-215 GEN
Solar/Wind Harmer
7.232
962981AG1-147 GEN
Solar/Wind Harmer
7.729
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.074
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.168
3141873WAN 176
Solar/Wind Harmer
0.03
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.097
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
8.942
315976AC1-164 GENA
Solar/Wind Harmer
8.275
316169AC1-164_GENC
Solar/Wind Harmer
7.149
315975AC1-164 GENB
Solar/Wind Harmer
0.245
972265AH1-717 GEN
Adder
4.429
3151201GRAVEL4
Adder
4.152
3151191GRAVEL3
Adder
4.099
3151211GRAVEL5
Adder
4.099
3141426STAFORD
Solar/Wind Helper
0.029
3150331BIRCHWDA
50/50
158.961
3141316ARNOLDS
50/50
2.026
3150351NORNECKC2
50/50
3.02
970575AG2-366 GEN
50/50
3.68
315749AE2-041 GEN
50/50
4.976
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
3150921YORKTN3
50/50
2.003
3144216WINCHST
50/50
0.289
3151161SURRY 1
50/50
2.191
970737AG2-469 GEN
Solar/Wind Harmer
20.26
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.646
962971AG1-146 GEN
Solar/Wind Harmer
3.312
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.629
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.866
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.022
3151221GRAVEL6
Adder
4.147
3151171GRAVELC
Adder
0.798
970293AG2-193 GEN
Solar/Wind Harmer
0.603
3150351NORNECKC2
50/50
2.97
966661AG1-536 GEN
50/50
6.884
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
971353AH1-157 GEN
50/50
7.642
970017AG2-010 GEN
50/50
4.875
3150641CHESTS8
50/50
0.192
944631AF1-128 GEN
50/50
30.156
3152331SURRY 2
50/50
2.455
972135AH1-637 GEN
Solar/Wind Harmer
4.407
316337AD2-073 GEN
Solar/Wind Harmer
0.3
3141726DUNNSVL
Solar/Wind Harmer
1.049
962861AG1-135 GEN
Solar/Wind Harmer
7.561
3138133OCRAN
Solar/Wind Harmer
0.104
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.365
3142433PROV 92
Solar/Wind Harmer
0.422
971317AH1-138 GEN
Solar/Wind Harmer
0.633
316159AE1-175 C
Solar/Wind Harmer
0.067
3138126ROCKLANDING
Solar/Wind Harmer
0.034
3151171GRAVELC
Adder
0.607
957191AF2-013 GEN
50/50
65.968
3150341NORNECKC1
50/50
3.119
3150341NORNECKC1
50/50
3.094
963611AG1-210 GEN
50/50
0.998
3150621CHESTS7
50/50
0.174
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
8.003
316075AC2-137 C
Solar/Wind Harmer
0.018
3142946ENON
Solar/Wind Harmer
0.007
LAGNLTFEXP_LAGN->PJM
CLTF
1.213
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.047
TVALTFEXP_TVA->PJM
CLTF
0.609
NYPJM->LTFIMP_NY
CLTF
0.465
LGEELTFEXP_LGEE->PJM
CLTF
0.185
WECLTFEXP_WEC->PJM
CLTF
0.092
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.061
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.057
MECLTFEXP_MEC->PJM
CLTF
0.525
SIGELTFEXP_SIGE->PJM
CLTF
0.016
CPLELTFEXP_CPLE->PJM
CLTF
1.912
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.152

Details for 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHCKAHM-6ELKO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.39 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:749.18
MW Contribution:4.7
Bus #Bus NameTypeMW Contribution
315749AE2-041 GEN
50/50
5.733
3141843SHACKLE
50/50
0.805
970575AG2-366 GEN
50/50
2.564
3150351NORNECKC2
50/50
1.491
3150921YORKTN3
50/50
3.133
3142433PROV 92
50/50
0.237
3142433PROV 92
50/50
0.237
3144216WINCHST
50/50
0.45
3151161SURRY 1
50/50
3.05
3141766HARMONY
Solar/Wind Harmer
2.15
316382AG1-145 C
Solar/Wind Harmer
0.001
316156AD2-030 GEN
Solar/Wind Harmer
0.11
3141873WAN 176
Solar/Wind Harmer
2.643
316280AD1-041 GEN
Solar/Wind Harmer
0.003
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
962971AG1-146 GEN
Solar/Wind Harmer
2.307
970009AG2-005 GEN
Solar/Wind Harmer
1.069
316404AE1-155 C
Solar/Wind Harmer
0.032
3142946ENON
Solar/Wind Harmer
0.045
3141906WESTMOR
Solar/Wind Harmer
0.046
970737AG2-469 GEN
Solar/Wind Harmer
4.442
315773AC2-141 GEN
Solar/Wind Harmer
3.089
3151221GRAVEL6
Adder
5.773
3151171GRAVELC
Adder
1.111
3145336SMITFLD
Solar/Wind Harmer
0.032
944581AF1-123 GEN
Solar/Wind Harmer
17.807
944601AF1-125 GEN
Solar/Wind Harmer
17.533
3144536CHRHLND
Solar/Wind Harmer
0.012
3151101ELIZAR3
Adder
7.322
3144873MCLAUGH
Solar/Wind Harmer
0.002
3146456SLIGO L269
Solar/Wind Harmer
0.077
971153AH1-033 GEN
Solar/Wind Harmer
0.886
961611AG1-000B GEN
Solar/Wind Harmer
2.019
316320Y1-086
Solar/Wind Harmer
0
316435W1029_GEN3
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.072
3146626S HERTFORD
Solar/Wind Harmer
0.071
315778AD1-151 GEN
Solar/Wind Harmer
5.404
3146376EDENTON
Solar/Wind Harmer
0.067
3145273HOLLAND
Solar/Wind Harmer
0.05
970129AG2-093 GEN
Solar/Wind Harmer
3.847
315614AA2-178 GEN
Solar/Wind Harmer
0.363
971157AH1-035 GEN
Solar/Wind Harmer
0.726
315737AD1-076 GEN
Solar/Wind Harmer
0.771
970133AG2-095 GEN
Solar/Wind Harmer
0.559
3146206CASHIE
Solar/Wind Harmer
0.058
3150341NORNECKC1
50/50
1.541
3150341NORNECKC1
50/50
1.528
963611AG1-210 GEN
50/50
0.493
3150621CHESTS7
50/50
0.297
958261AF2-120 GEN
Solar/Wind Harmer
4.681
316077AC2-138 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.013
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.015
3150991CHESPKB
Adder
0.825
3150991CHESPKB
Adder
0.805
316316AC1-027 C
Solar/Wind Harmer
0.075
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3145506HICKORY
Solar/Wind Harmer
0.311
3145506HICKORY
Solar/Wind Harmer
0.187
3145506HICKORY
Solar/Wind Harmer
0.047
316339AD2-160 GEN
Solar/Wind Harmer
0.125
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.043
3137176SLIGO L2192
Solar/Wind Harmer
0.305
3146456SLIGO L269
Solar/Wind Harmer
1.356
3130086AYDLETT
Solar/Wind Harmer
0.305
3146386ELIZ CT
Solar/Wind Harmer
0.075
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.072
3146516WINFALL
Solar/Wind Harmer
0.072
3146516WINFALL
Solar/Wind Harmer
0.072
3146626S HERTFORD
Solar/Wind Harmer
0.071
3146626S HERTFORD
Solar/Wind Harmer
0.071
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.079
3146376EDENTON
Solar/Wind Harmer
0.299
3146376EDENTON
Solar/Wind Harmer
0.299
315742AE1-103 GEN
Solar/Wind Harmer
0.001
316065AD1-022 GEN
Solar/Wind Harmer
2.693
316075AC2-137 C
Solar/Wind Helper
1.022
315759AF1-018 GEN
50/50
5.733
3142433PROV 92
50/50
0.237
3142433PROV 92
50/50
0.237
3150611CHESTG7
50/50
0.647
3150631CHESTG8
50/50
0.636
971047AG2-646 GEN
50/50
18.112
972263AH1-716 GEN
50/50
58.57
315976AC1-164 GENA
Solar/Wind Harmer
22.099
316169AC1-164_GENC
Solar/Wind Harmer
19.091
315975AC1-164 GENB
Solar/Wind Harmer
0.654
316314AB2-024 C
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.03
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.4
3143873LANEXA
Solar/Wind Harmer
0.089
3141913WHIT STONE
Solar/Wind Harmer
0.147
3138133OCRAN
Solar/Wind Harmer
0.044
3141783LANCAST
Solar/Wind Harmer
0.088
3141783LANCAST
Solar/Wind Harmer
0.058
962981AG1-147 GEN
Solar/Wind Harmer
5.383
970327AG2-215 GEN
Solar/Wind Harmer
4.699
3141813NORNECK
Solar/Wind Harmer
0.139
3138283WHITEMARSH
Solar/Wind Harmer
0.031
316223AC1-118
Solar/Wind Harmer
0.083
971167AH1-042 GEN
Solar/Wind Harmer
9.459
944491AF1-114 GEN
Solar/Wind Harmer
0
972265AH1-717 GEN
Adder
6.165
3151201GRAVEL4
Adder
5.779
3151191GRAVEL3
Adder
5.706
3151211GRAVEL5
Adder
5.706
971445AH1-216 GEN
Solar/Wind Harmer
5.578
3151081ELIZAR1
Adder
7.23
3151091ELIZAR2
Adder
7.104
3152611GOSPORTB
Adder
1.003
3152621GOSPORTC
Adder
0.851
3152601GOSPORTA
Adder
0.785
957871AF2-081 GEN
Solar/Wind Harmer
3.833
319010AE1-072 C
Solar/Wind Harmer
0.385
3146406KITTY HAWK
Solar/Wind Harmer
0.01
316305AF2-043 C
Solar/Wind Harmer
0.001
313526AB2-022
Solar/Wind Harmer
0.04
3146486SUNBURY
Solar/Wind Harmer
0.074
3146486SUNBURY
Solar/Wind Harmer
0.074
316321Z2-027
Solar/Wind Harmer
0.014
3146396TANGLEW
Solar/Wind Harmer
0.204
3145176PASQUOTANK
Solar/Wind Harmer
0.046
315835AF2-110_GEN
Solar/Wind Harmer
0.491
316369SG1_INVT
Solar/Wind Harmer
0.003
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.067
3130156CHOWAN
Solar/Wind Harmer
0.067
316132AB2-190 GEN1
Solar/Wind Harmer
0.345
316311AC2-079 GEN
Solar/Wind Harmer
1.828
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.044
315816AE2-034 GEN
Solar/Wind Harmer
0.272
3130546PLYMOUTH
Solar/Wind Harmer
0.06
315732AD1-074 GEN1
Solar/Wind Harmer
0.344
315733AD1-074 GEN2
Solar/Wind Harmer
0.344
315735AD1-075 GEN1
Solar/Wind Harmer
0.172
3146206CASHIE
Solar/Wind Harmer
0.058
970601AG2-382 GEN
Solar/Wind Harmer
2.153
316312AB1-027
Solar/Wind Helper
0.774
3141843SHACKLE
50/50
0.805
966661AG1-536 GEN
50/50
4.027
3150351NORNECKC2
50/50
1.467
971353AH1-157 GEN
50/50
11.629
3142433PROV 92
50/50
0.237
3142433PROV 92
50/50
0.237
970017AG2-010 GEN
50/50
7.587
3150641CHESTS8
50/50
0.328
944631AF1-128 GEN
50/50
51.528
3152331SURRY 2
50/50
4.05
3141766HARMONY
Solar/Wind Harmer
0.032
316159AE1-175 C
Solar/Wind Harmer
0.131
971777AH1-397 GEN
Solar/Wind Harmer
0.392
3138133OCRAN
Solar/Wind Harmer
0.088
3141726DUNNSVL
Solar/Wind Harmer
0.58
962861AG1-135 GEN
Solar/Wind Harmer
4.544
971317AH1-138 GEN
Solar/Wind Harmer
0.97
316337AD2-073 GEN
Solar/Wind Harmer
0.112
3142433PROV 92
Solar/Wind Harmer
0.459
3138126ROCKLANDING
Solar/Wind Harmer
0.052
972135AH1-637 GEN
Solar/Wind Harmer
0.821
316294AC1-161 GEN
Solar/Wind Harmer
1.466
316072AD1-144
Solar/Wind Harmer
0.029
3151171GRAVELC
Adder
0.845
3145336SMITFLD
Solar/Wind Harmer
0.317
944591AF1-124 GEN
Solar/Wind Harmer
17.87
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.984
316388AE2-253 GEN
Solar/Wind Harmer
0.242
3146456SLIGO L269
Solar/Wind Harmer
0.077
316246AF1-032 C
Solar/Wind Harmer
0.034
961611AG1-000B GEN
Solar/Wind Harmer
3.97
971647AH1-324 GEN
Solar/Wind Harmer
3.105
3146516WINFALL
Solar/Wind Harmer
0.234
3146516WINFALL
Solar/Wind Harmer
0.072
316093AE2-104_GEN
Solar/Wind Harmer
1.204
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
971069AG2-661 GEN
Solar/Wind Harmer
1.201
3130156CHOWAN
Solar/Wind Harmer
0.067
316458AB2-190 GEN2
Solar/Wind Harmer
0.345
970129AG2-093 GEN
Solar/Wind Harmer
1.811
3145663CRESWEL
Solar/Wind Harmer
0.178
971163AH1-040 GEN
Solar/Wind Harmer
5.075
939411AE1-173 GEN
Solar/Wind Harmer
25.398
3146206CASHIE
Solar/Wind Harmer
0.058
971547AH1-271 GEN
Solar/Wind Harmer
1.231
3142416OLDCHRC
Solar/Wind Helper
1.057
3142416OLDCHRC
Solar/Wind Helper
0.405
LAGNLTFEXP_LAGN->PJM
CLTF
1.093
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.265
TVALTFEXP_TVA->PJM
CLTF
0.541
NYPJM->LTFIMP_NY
CLTF
0.351
LGEELTFEXP_LGEE->PJM
CLTF
0.115
WECLTFEXP_WEC->PJM
CLTF
0.057
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.783
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.778
MECLTFEXP_MEC->PJM
CLTF
0.38
SIGELTFEXP_SIGE->PJM
CLTF
0.011
CPLELTFEXP_CPLE->PJM
CLTF
2.113
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.142

Details for 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 567_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 567_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.77 %
Rating:935.39 MVA
Rating Type:B
MVA to Mitigate:1120.31
MW Contribution:7.08
Bus #Bus NameTypeMW Contribution
315749AE2-041 GEN
50/50
8.574
3141843SHACKLE
50/50
1.242
970575AG2-366 GEN
50/50
3.862
3142433PROV 92
50/50
0.435
3142433PROV 92
50/50
0.435
3150351NORNECKC2
50/50
2.24
3150921YORKTN3
50/50
4.627
3144216WINCHST
50/50
0.678
3143096IRON208
50/50
0.7
3143096IRON208
50/50
0.686
3150801HOPHCF4
50/50
0.906
971211AH1-065 GEN
50/50
1.092
3141766HARMONY
Solar/Wind Harmer
3.215
3142946ENON
Solar/Wind Harmer
0.078
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.005
316156AD2-030 GEN
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
3.99
316382AG1-145 C
Solar/Wind Harmer
0.002
962971AG1-146 GEN
Solar/Wind Harmer
3.476
970009AG2-005 GEN
Solar/Wind Harmer
1.61
316404AE1-155 C
Solar/Wind Harmer
0.048
970293AG2-193 GEN
Solar/Wind Harmer
2.101
3141906WESTMOR
Solar/Wind Harmer
0.07
970737AG2-469 GEN
Solar/Wind Harmer
6.757
3142416OLDCHRC
Solar/Wind Harmer
1.491
3150341NORNECKC1
50/50
2.314
3150341NORNECKC1
50/50
2.295
963611AG1-210 GEN
50/50
0.74
3150621CHESTS7
50/50
0.591
3150781HOPHCF2
50/50
0.623
3150791HOPHCF3
50/50
0.623
3150761HOPPOLC
50/50
0.395
971213AH1-066 GEN
50/50
0.546
316075AC2-137 C
Solar/Wind Harmer
0.069
3142946ENON
Solar/Wind Harmer
0.023
958261AF2-120 GEN
Solar/Wind Harmer
7.042
315759AF1-018 GEN
50/50
8.574
3142433PROV 92
50/50
0.435
3142433PROV 92
50/50
0.435
3150611CHESTG7
50/50
1.286
3150631CHESTG8
50/50
1.265
971047AG2-646 GEN
50/50
36.002
315976AC1-164 GENA
Solar/Wind Harmer
32.344
316169AC1-164_GENC
Solar/Wind Harmer
27.943
315975AC1-164 GENB
Solar/Wind Harmer
0.957
316314AB2-024 C
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.002
3143873LANEXA
Solar/Wind Harmer
0.141
970189AG2-124 GEN
Solar/Wind Harmer
6.788
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.045
3141913WHIT STONE
Solar/Wind Harmer
0.222
3138133OCRAN
Solar/Wind Harmer
0.066
3141783LANCAST
Solar/Wind Harmer
0.132
3141783LANCAST
Solar/Wind Harmer
0.088
962981AG1-147 GEN
Solar/Wind Harmer
8.11
970327AG2-215 GEN
Solar/Wind Harmer
7.076
3141813NORNECK
Solar/Wind Harmer
0.208
971167AH1-042 GEN
Solar/Wind Harmer
18.214
3138283WHITEMARSH
Solar/Wind Harmer
0.046
316223AC1-118
Solar/Wind Harmer
0.126
316312AB1-027
Solar/Wind Harmer
0.275
316132AB2-190 GEN1
Solar/Wind Harmer
0.809
316369SG1_INVT
Solar/Wind Harmer
0.006
972265AH1-717 GEN
Adder
11.153
3151201GRAVEL4
Adder
10.455
3151191GRAVEL3
Adder
10.323
3151211GRAVEL5
Adder
10.323
971445AH1-216 GEN
Solar/Wind Harmer
9.647
944491AF1-114 GEN
Solar/Wind Harmer
0
3152611GOSPORTB
Adder
1.587
3152621GOSPORTC
Adder
1.347
3152601GOSPORTA
Adder
1.242
3151081ELIZAR1
Adder
11.396
3151091ELIZAR2
Adder
11.198
316305AF2-043 C
Solar/Wind Harmer
0.001
957871AF2-081 GEN
Solar/Wind Harmer
6.034
319010AE1-072 C
Solar/Wind Harmer
0.608
3146406KITTY HAWK
Solar/Wind Harmer
0.015
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.082
316311AC2-079 GEN
Solar/Wind Harmer
3.454
315835AF2-110_GEN
Solar/Wind Harmer
0.824
3146486SUNBURY
Solar/Wind Harmer
0.119
3146486SUNBURY
Solar/Wind Harmer
0.119
313526AB2-022
Solar/Wind Harmer
0.064
316321Z2-027
Solar/Wind Harmer
0.022
3146396TANGLEW
Solar/Wind Harmer
0.325
3145176PASQUOTANK
Solar/Wind Harmer
0.073
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.111
3130156CHOWAN
Solar/Wind Harmer
0.111
3143316POE
Solar/Wind Harmer
0.433
315816AE2-034 GEN
Solar/Wind Harmer
0.455
971285AH1-108 GEN
Adder
0.794
3130546PLYMOUTH
Solar/Wind Harmer
0.102
315732AD1-074 GEN1
Solar/Wind Harmer
0.585
315733AD1-074 GEN2
Solar/Wind Harmer
0.585
315735AD1-075 GEN1
Solar/Wind Harmer
0.293
3146206CASHIE
Solar/Wind Harmer
0.099
970601AG2-382 GEN
Solar/Wind Harmer
3.715
965291AG1-394 GEN
Solar/Wind Harmer
0.437
3145893MURPHYS
Solar/Wind Harmer
0.261
3145893MURPHYS
Solar/Wind Harmer
0.097
316315AB2-025 C
Solar/Wind Harmer
0.078
315814AE2-033 C
Solar/Wind Harmer
7.609
3145513AHOSKIE
Solar/Wind Harmer
0.198
3145513AHOSKIE
Solar/Wind Harmer
0.095
3145683EARLEYS
Solar/Wind Harmer
0.188
3145683EARLEYS
Solar/Wind Harmer
0.094
3145683EARLEYS
Solar/Wind Harmer
0.094
3146043SEABORD
Solar/Wind Harmer
0.091
315607AA1-063A GEN
Solar/Wind Harmer
0.184
315652AC1-086 GEN
Solar/Wind Harmer
9.519
3146033SCOT NK
Solar/Wind Harmer
0.346
941031AE2-094 GEN
Solar/Wind Harmer
15.83
944011AF1-069 GEN
Solar/Wind Harmer
5.172
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.34
3145796HORNRTN
Solar/Wind Harmer
0.271
3145796HORNRTN
Solar/Wind Harmer
0.034
316233AE1-074 FULL
Solar/Wind Harmer
0.068
971281AH1-106 GEN
Solar/Wind Harmer
1.171
971283AH1-107 GEN
Solar/Wind Harmer
1.171
970673AG2-436 GEN
Solar/Wind Harmer
17.959
970673AG2-436 GEN
Solar/Wind Harmer
11.973
316005AA1-067
Solar/Wind Harmer
0.089
3145746EVERETS
Solar/Wind Harmer
0.329
3145746EVERETS
Solar/Wind Harmer
0.083
3145746EVERETS
Solar/Wind Harmer
0.083
3145746EVERETS
Solar/Wind Harmer
0.083
970181AG2-120 GEN
Solar/Wind Harmer
1.028
971967AH1-528 GEN
Solar/Wind Harmer
13.196
957861AF2-080 GEN
Solar/Wind Harmer
3.428
970085AG2-068 GEN
Solar/Wind Harmer
4.189
970581AG2-369 GEN
Solar/Wind Harmer
3.603
316420AA1-050 GEN
Solar/Wind Harmer
0.003
3145573BETHELC
Solar/Wind Harmer
0.077
3145573BETHELC
Solar/Wind Harmer
0.077
316319Z2-044 C
Solar/Wind Harmer
0
970831AG2-522 GEN
Solar/Wind Harmer
3.188
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
0.999
3144303KENBRDG
Solar/Wind Harmer
0.047
3141843SHACKLE
50/50
1.242
966661AG1-536 GEN
50/50
6.058
3142433PROV 92
50/50
0.435
3142433PROV 92
50/50
0.435
3150351NORNECKC2
50/50
2.203
3150641CHESTS8
50/50
0.652
944631AF1-128 GEN
50/50
102.426
971353AH1-157 GEN
50/50
16.966
970017AG2-010 GEN
50/50
11.364
3143096IRON208
50/50
0.7
3150771HOPHCF1
50/50
0.623
3141766HARMONY
Solar/Wind Harmer
0.048
971777AH1-397 GEN
Solar/Wind Harmer
0.605
3138133OCRAN
Solar/Wind Harmer
0.133
316159AE1-175 C
Solar/Wind Harmer
0.19
3141726DUNNSVL
Solar/Wind Harmer
0.868
962861AG1-135 GEN
Solar/Wind Harmer
6.837
3142433PROV 92
Solar/Wind Harmer
0.844
316337AD2-073 GEN
Solar/Wind Harmer
0.169
971317AH1-138 GEN
Solar/Wind Harmer
1.414
3138126ROCKLANDING
Solar/Wind Harmer
0.078
3142416OLDCHRC
Solar/Wind Harmer
0.4
3142416OLDCHRC
Solar/Wind Harmer
0.153
970129AG2-093 GEN
Solar/Wind Harmer
4.296
316458AB2-190 GEN2
Solar/Wind Harmer
0.809
971069AG2-661 GEN
Solar/Wind Harmer
2.652
972135AH1-637 GEN
Solar/Wind Harmer
1.254
971647AH1-324 GEN
Solar/Wind Harmer
6.261
961611AG1-000B GEN
Solar/Wind Harmer
7.623
3151171GRAVELC
Adder
1.528
3145336SMITFLD
Solar/Wind Harmer
0.545
316072AD1-144
Solar/Wind Harmer
0.047
315671AE2-027_GEN
Solar/Wind Harmer
8.084
316375AC2-012 GEN
Solar/Wind Harmer
0.003
3150981CHESPKA
Adder
1.556
316294AC1-161 GEN
Solar/Wind Harmer
2.12
944591AF1-124 GEN
Solar/Wind Harmer
27.57
3142543TWELFTH
Solar/Wind Harmer
0.012
316246AF1-032 C
Solar/Wind Harmer
0.055
316388AE2-253 GEN
Solar/Wind Harmer
0.38
3146456SLIGO L269
Solar/Wind Harmer
0.121
970659AG2-427 GEN
Solar/Wind Harmer
5.84
316381AD1-082 GEN
Solar/Wind Harmer
0.126
970661AG2-428 GEN
Solar/Wind Harmer
11.997
316093AE2-104_GEN
Solar/Wind Harmer
2.019
3146516WINFALL
Solar/Wind Harmer
0.377
3146516WINFALL
Solar/Wind Harmer
0.116
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.111
3145663CRESWEL
Solar/Wind Harmer
0.297
971163AH1-040 GEN
Solar/Wind Harmer
8.478
3150851SPRUNCC
Adder
0.485
939411AE1-173 GEN
Solar/Wind Harmer
43.623
3146206CASHIE
Solar/Wind Harmer
0.099
971547AH1-271 GEN
Solar/Wind Harmer
2.123
3145893MURPHYS
Solar/Wind Harmer
0.387
3145893MURPHYS
Solar/Wind Harmer
0.431
940641AE2-051 GEN
Solar/Wind Harmer
7.644
3146173TUNIS
Solar/Wind Harmer
0.095
3145683EARLEYS
Solar/Wind Harmer
0.094
3145963POPLR C
Solar/Wind Harmer
0.093
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.091
3145823KELFORD
Solar/Wind Harmer
0.09
970133AG2-095 GEN
Solar/Wind Harmer
1.475
970129AG2-093 GEN
Solar/Wind Harmer
9.13
315778AD1-151 GEN
Solar/Wind Harmer
11.936
961611AG1-000B GEN
Solar/Wind Harmer
3.876
3151221GRAVEL6
Adder
10.443
3151171GRAVELC
Adder
2.009
3145336SMITFLD
Solar/Wind Harmer
0.055
3144536CHRHLND
Solar/Wind Harmer
0.019
3144873MCLAUGH
Solar/Wind Harmer
0.003
3151101ELIZAR3
Adder
11.542
965281AG1-393 GEN
Solar/Wind Harmer
1.324
315773AC2-141 GEN
Solar/Wind Harmer
4.468
944581AF1-123 GEN
Solar/Wind Harmer
27.472
944601AF1-125 GEN
Solar/Wind Harmer
27.049
315813AE1-149 C
Solar/Wind Harmer
6.453
3146456SLIGO L269
Solar/Wind Harmer
0.121
971153AH1-033 GEN
Solar/Wind Harmer
1.397
970659AG2-427 GEN
Solar/Wind Harmer
1.277
316083AB2-161 GEN
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
2.552
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.116
3146626S HERTFORD
Solar/Wind Harmer
0.115
3145273HOLLAND
Solar/Wind Harmer
0.085
315839AE2-212 C
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.11
315614AA2-178 GEN
Solar/Wind Harmer
0.606
3150861SPRUNCD
Adder
0.485
971157AH1-035 GEN
Solar/Wind Harmer
1.23
315737AD1-076 GEN
Solar/Wind Harmer
1.31
3146206CASHIE
Solar/Wind Harmer
0.099
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3145893MURPHYS
Solar/Wind Harmer
0.162
3145893MURPHYS
Solar/Wind Harmer
0.097
957521AF2-046 GEN
Solar/Wind Harmer
7.177
961681AG1-008 GEN
Solar/Wind Harmer
7.177
3156021HOLLOMANSOL
Solar/Wind Harmer
0.437
3146173TUNIS
Solar/Wind Harmer
0.095
316463AE2-346 GEN
Solar/Wind Harmer
0.081
316140AB2-099
Solar/Wind Harmer
0.034
962331AG1-082 GEN
Solar/Wind Harmer
1.01
3145963POPLR C
Solar/Wind Harmer
0.093
3146263WOODLND
Solar/Wind Harmer
0.091
316317KELFORD C
Solar/Wind Harmer
0.009
3145823KELFORD
Solar/Wind Harmer
0.09
316365GEN2_N
Solar/Wind Harmer
0.201
3142666NORTHAMPTON
Solar/Wind Harmer
0.088
3145933PARMELE
Solar/Wind Harmer
0.086
966801AG1-551 GEN
Solar/Wind Harmer
1.002
313506AB2-031 GEN
Solar/Wind Harmer
0.263
3145796HORNRTN
Solar/Wind Harmer
0.338
3145796HORNRTN
Solar/Wind Harmer
0.085
316210AC1-098 GEN
Solar/Wind Harmer
0.773
3145746EVERETS
Solar/Wind Harmer
0.083
3145746EVERETS
Solar/Wind Harmer
0.083
970917AG2-570 GEN
Solar/Wind Harmer
7.013
3147043LAWRENC
Solar/Wind Harmer
0.047
315724AD1-057 GEN
Solar/Wind Harmer
0.295
316327AA2-057 GEN
Solar/Wind Harmer
0.118
3146073TAR RVR
Solar/Wind Harmer
0.077
3146083TARBORO
Solar/Wind Harmer
0.077
3146233WITAKRS
Solar/Wind Harmer
0.38
3146233WITAKRS
Solar/Wind Harmer
0.052
3138543CONSLDL
Solar/Wind Harmer
0.05
961601AG1-000A GEN
Solar/Wind Harmer
5.236
3145543BTLEBRO
Solar/Wind Harmer
0.073
3145543BTLEBRO
Solar/Wind Harmer
0.073
971623AH1-311 GEN
Solar/Wind Harmer
0.147
316478AD1-087 GEN
Solar/Wind Harmer
0.24
316486AD2-202 GEN
Solar/Wind Harmer
0.07
3141316ARNOLDS
Adder
0.161
316131AB2-060 GEN
Solar/Wind Harmer
0.199
964241AG1-285 GEN
Solar/Wind Harmer
4.14
315785AD2-033 C
Solar/Wind Harmer
0.488
970257AG2-171 GEN
Solar/Wind Harmer
1.897
959311AF2-222 GEN
Solar/Wind Harmer
5.222
316473AC1-191 GEN
Solar/Wind Harmer
0.191
316248AF1-058 C
Solar/Wind Harmer
0
960061AF2-297 GEN
Solar/Wind Harmer
2.402
316077AC2-138 C
Solar/Wind Harmer
0.001
3150691DARBY 3
Adder
10.705
3150701DARBY 4
Adder
10.68
3150681DARBY 2
Adder
10.668
3150671DARBY 1
Adder
10.655
316033AB2-134 GEN
Solar/Wind Harmer
0.009
315697AD1-025 GEN
Solar/Wind Harmer
0.167
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.023
3150991CHESPKB
Adder
1.305
3150991CHESPKB
Adder
1.274
316316AC1-027 C
Solar/Wind Harmer
0.119
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.003
3145506HICKORY
Solar/Wind Harmer
0.488
3145506HICKORY
Solar/Wind Harmer
0.293
3145506HICKORY
Solar/Wind Harmer
0.073
3142366NRTHEST
Adder
0.397
316339AD2-160 GEN
Solar/Wind Harmer
0.197
316018AA1-139 ULT2
Solar/Wind Harmer
0.003
316017AA1-139 ULT1
Solar/Wind Harmer
0.068
3137176SLIGO L2192
Solar/Wind Harmer
0.481
3146456SLIGO L269
Solar/Wind Harmer
2.138
970657AG2-426 GEN
Solar/Wind Harmer
4.227
970657AG2-426 GEN
Solar/Wind Harmer
0.886
3130086AYDLETT
Solar/Wind Harmer
0.482
3146386ELIZ CT
Solar/Wind Harmer
0.119
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.116
3146516WINFALL
Solar/Wind Harmer
0.116
3146516WINFALL
Solar/Wind Harmer
0.116
944641AF1-129 GEN
Adder
55.399
316240AF1-291 C
Solar/Wind Harmer
0.001
3146626S HERTFORD
Solar/Wind Harmer
0.115
3146626S HERTFORD
Solar/Wind Harmer
0.115
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.491
3146376EDENTON
Solar/Wind Harmer
0.491
316065AD1-022 GEN
Solar/Wind Harmer
4.62
3145893MURPHYS
Solar/Wind Harmer
0.648
3145893MURPHYS
Solar/Wind Harmer
0.174
3144356SAPONY
Solar/Wind Harmer
0.808
3146173TUNIS
Solar/Wind Harmer
0.095
3146173TUNIS
Solar/Wind Harmer
0.095
3142666NORTHAMPTON
Solar/Wind Harmer
0.088
3142666NORTHAMPTON
Solar/Wind Harmer
0.088
3142666NORTHAMPTON
Solar/Wind Harmer
0.088
3142666NORTHAMPTON
Solar/Wind Harmer
0.053
316426AA2-053 GEN
Solar/Wind Harmer
0.293
3145933PARMELE
Solar/Wind Harmer
0.172
3145933PARMELE
Solar/Wind Harmer
0.086
316181AB2-040 GEN
Solar/Wind Harmer
0.123
3145593CAROLNA
Solar/Wind Harmer
0.085
3145593CAROLNA
Solar/Wind Harmer
0.085
966811AG1-552 GEN
Solar/Wind Harmer
0.922
3145593CAROLNA
Solar/Wind Harmer
0.106
3145796HORNRTN
Solar/Wind Harmer
0.254
3145783HORNRTN
Solar/Wind Harmer
1.502
3145783HORNRTN
Solar/Wind Harmer
1.202
3145783HORNRTN
Solar/Wind Harmer
0.376
3145783HORNRTN
Solar/Wind Harmer
0.15
3143526WINTERP
Solar/Wind Harmer
0.439
972185AH1-677 GEN
Adder
4.674
972187AH1-678 GEN
Adder
2.339
316274AC1-208 GEN
Solar/Wind Harmer
0.423
970933AG2-581 GEN
Solar/Wind Harmer
6.363
3145493TOT1
Solar/Wind Harmer
0.178
3145453TOT5
Solar/Wind Harmer
0.107
3145603CNETO
Solar/Wind Harmer
0.071
961601AG1-000A GEN
Solar/Wind Harmer
1.309
316263AC1-034 GEN
Solar/Wind Harmer
2.793
970099AG2-077 GEN
Solar/Wind Harmer
7.694
971223AH1-071 GEN
Solar/Wind Harmer
0.72
939181AE1-148 GEN
Solar/Wind Harmer
3.206
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
2.881
964791AG1-342 GEN
Solar/Wind Harmer
1.14
3146843MT LREL
Solar/Wind Harmer
0.059
3146843MT LREL
Solar/Wind Harmer
0.059
970323AG2-213 GEN
Solar/Wind Harmer
2.53
971775AH1-396 GEN
Solar/Wind Harmer
0.095
316034AC1-036 C
Solar/Wind Harmer
0.004
971741AH1-377 GEN
Solar/Wind Harmer
5.844
966871AG1-558 GEN
Solar/Wind Harmer
0.065
316023GEN1_S
Solar/Wind Harmer
0.201
316190AA2-174 GEN
Solar/Wind Harmer
0
316011AB1-132 GEN
Solar/Wind Harmer
1.573
962571AG1-106 GEN
Solar/Wind Harmer
1.231
3146293MARTNCO
Solar/Wind Harmer
0.08
960081AF2-299 GEN
Solar/Wind Harmer
0.817
3145796HORNRTN
Solar/Wind Harmer
0.279
3145796HORNRTN
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
0.084
3143526WINTERP
Solar/Wind Harmer
0.439
316212AC1-099_GEN
Solar/Wind Harmer
0.431
3145746EVERETS
Solar/Wind Harmer
0.083
3145746EVERETS
Solar/Wind Harmer
0.083
971795AH1-408 GEN
Solar/Wind Harmer
5.378
316494AC1-189 GEN
Solar/Wind Harmer
0.269
970919AG2-571 GEN
Solar/Wind Harmer
2.805
3147043LAWRENC
Adder
0.711
970087AG2-069 GEN
Solar/Wind Harmer
6.284
315722AD1-056 GEN
Solar/Wind Harmer
0.497
961671AG1-007 GEN
Solar/Wind Harmer
0.012
3146083TARBORO
Solar/Wind Harmer
0.077
3145493TOT1
Solar/Wind Harmer
0.342
3146233WITAKRS
Solar/Wind Harmer
0.302
316129AC1-054 GEN
Solar/Wind Harmer
0.277
316359AB2-059 GEN
Solar/Wind Harmer
0.264
316049AB1-081 GEN
Solar/Wind Harmer
0.421
3145543BTLEBRO
Solar/Wind Harmer
0.073
3145543BTLEBRO
Solar/Wind Harmer
0.059
3142053HEARTS
Solar/Wind Harmer
0.129
971065AG2-659 GEN
Solar/Wind Harmer
3.097
957481AF2-042 GEN
Solar/Wind Harmer
19.236
315693AD1-088 GEN
Solar/Wind Harmer
3.297
962491AG1-098 GEN
Solar/Wind Harmer
3.883
3143226MDLTHAN
Solar/Wind Harmer
0.067
315687AD1-152 GEN
Solar/Wind Harmer
0.002
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970401AG2-262 GEN
Solar/Wind Harmer
0.348
970685AG2-442 GEN
Solar/Wind Harmer
4.283
316118AC1-105 GEN
Solar/Wind Harmer
0.149
970683AG2-441 GEN
Solar/Wind Harmer
3.824
970681AG2-440 GEN
Solar/Wind Harmer
3.059
3147173SINAI
Solar/Wind Harmer
0.056
3147243WELCO
Solar/Wind Harmer
0.035
LAGNLTFEXP_LAGN->PJM
CLTF
1.924
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.054
TVALTFEXP_TVA->PJM
CLTF
0.95
NYPJM->LTFIMP_NY
CLTF
0.699
LGEELTFEXP_LGEE->PJM
CLTF
0.151
WECLTFEXP_WEC->PJM
CLTF
0.071
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.999
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.074
MECLTFEXP_MEC->PJM
CLTF
0.569
SIGELTFEXP_SIGE->PJM
CLTF
0.015
CPLELTFEXP_CPLE->PJM
CLTF
4.035
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.643

Details for 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF A-6IRON208 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.61 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:740.71
MW Contribution:2.82
Bus #Bus NameTypeMW Contribution
3150801HOPHCF4
50/50
0.81
971211AH1-065 GEN
50/50
0.977
315749AE2-041 GEN
50/50
3.414
3151161SURRY 1
50/50
3.592
3142946ENON
Solar/Wind Harmer
0.072
970133AG2-095 GEN
Solar/Wind Harmer
1.318
970129AG2-093 GEN
Solar/Wind Harmer
7.619
315778AD1-151 GEN
Solar/Wind Harmer
9.439
961611AG1-000B GEN
Solar/Wind Harmer
2.697
3141766HARMONY
Solar/Wind Harmer
1.28
316382AG1-145 C
Solar/Wind Harmer
0.001
3151221GRAVEL6
Adder
6.799
3151171GRAVELC
Adder
1.308
3141843SHACKLE
Adder
0.471
316203AE2-005 GEN
Solar/Wind Harmer
0
316280AD1-041 GEN
Solar/Wind Harmer
0.002
316156AD2-030 GEN
Solar/Wind Harmer
0.068
3141873WAN 176
Solar/Wind Harmer
1.624
962971AG1-146 GEN
Solar/Wind Harmer
1.39
970009AG2-005 GEN
Solar/Wind Harmer
0.641
3142433PROV 92
Adder
0.165
3142433PROV 92
Adder
0.165
3144216WINCHST
Adder
0.319
316404AE1-155 C
Solar/Wind Harmer
0.019
3145336SMITFLD
Solar/Wind Harmer
0.033
3150921YORKTN3
Adder
2.093
3150351NORNECKC2
Adder
0.824
3144536CHRHLND
Solar/Wind Harmer
0.011
315813AE1-149 C
Solar/Wind Harmer
3.817
970659AG2-427 GEN
Solar/Wind Harmer
0.738
316083AB2-161 GEN
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.45
3144873MCLAUGH
Solar/Wind Harmer
0.002
3151101ELIZAR3
Adder
6.266
3141906WESTMOR
Solar/Wind Harmer
0.027
944581AF1-123 GEN
Solar/Wind Harmer
14.477
944601AF1-125 GEN
Solar/Wind Harmer
14.254
3146456SLIGO L269
Solar/Wind Harmer
0.064
971153AH1-033 GEN
Solar/Wind Harmer
0.742
316320Y1-086
Solar/Wind Harmer
0
315773AC2-141 GEN
Solar/Wind Harmer
2.272
316435W1029_GEN3
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.061
965281AG1-393 GEN
Solar/Wind Harmer
0.649
3146626S HERTFORD
Solar/Wind Harmer
0.06
970737AG2-469 GEN
Solar/Wind Harmer
2.555
3145273HOLLAND
Solar/Wind Harmer
0.045
3146376EDENTON
Solar/Wind Harmer
0.057
3150621CHESTS7
50/50
0.75
3150781HOPHCF2
50/50
0.557
3150791HOPHCF3
50/50
0.557
3150761HOPPOLC
50/50
0.353
971213AH1-066 GEN
50/50
0.488
3142946ENON
Solar/Wind Harmer
0.022
316033AB2-134 GEN
Solar/Wind Harmer
0.007
315697AD1-025 GEN
Solar/Wind Harmer
0.127
958261AF2-120 GEN
Solar/Wind Harmer
2.785
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316075AC2-137 C
Solar/Wind Harmer
0.023
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.851
3150341NORNECKC1
Adder
0.845
970657AG2-426 GEN
Solar/Wind Harmer
2.421
970657AG2-426 GEN
Solar/Wind Harmer
0.507
316036AC1-147 C
Solar/Wind Harmer
0.013
3150991CHESPKB
Adder
0.712
3150991CHESPKB
Adder
0.694
316316AC1-027 C
Solar/Wind Harmer
0.064
3142956BIRDNECK
Solar/Wind Harmer
0
3150641CHESTS8
50/50
0.828
944631AF1-128 GEN
50/50
130.091
3150771HOPHCF1
50/50
0.557
3152331SURRY 2
50/50
2.862
970129AG2-093 GEN
Solar/Wind Harmer
3.585
316458AB2-190 GEN2
Solar/Wind Harmer
0.67
971069AG2-661 GEN
Solar/Wind Harmer
2.098
971647AH1-324 GEN
Solar/Wind Harmer
4.574
961611AG1-000B GEN
Solar/Wind Harmer
5.304
3141766HARMONY
Solar/Wind Harmer
0.019
316159AE1-175 C
Solar/Wind Harmer
0.081
3151171GRAVELC
Adder
0.995
971777AH1-397 GEN
Solar/Wind Harmer
0.243
3141843SHACKLE
Adder
0.471
3138133OCRAN
Solar/Wind Harmer
0.054
971317AH1-138 GEN
Solar/Wind Harmer
0.639
3142433PROV 92
Solar/Wind Harmer
0.34
3142433PROV 92
Adder
0.165
3142433PROV 92
Adder
0.165
962861AG1-135 GEN
Solar/Wind Harmer
2.709
3141726DUNNSVL
Solar/Wind Harmer
0.337
3138126ROCKLANDING
Solar/Wind Harmer
0.039
3145336SMITFLD
Solar/Wind Harmer
0.335
3150351NORNECKC2
Adder
0.811
316337AD2-073 GEN
Solar/Wind Harmer
0.065
316072AD1-144
Solar/Wind Harmer
0.026
970659AG2-427 GEN
Solar/Wind Harmer
3.376
316381AD1-082 GEN
Solar/Wind Harmer
0.072
970661AG2-428 GEN
Solar/Wind Harmer
6.816
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.848
316246AF1-032 C
Solar/Wind Harmer
0.029
316388AE2-253 GEN
Solar/Wind Harmer
0.202
944591AF1-124 GEN
Solar/Wind Harmer
14.529
3146456SLIGO L269
Solar/Wind Harmer
0.064
316093AE2-104_GEN
Solar/Wind Harmer
1.078
316294AC1-161 GEN
Solar/Wind Harmer
1.078
3146516WINFALL
Solar/Wind Harmer
0.198
3146516WINFALL
Solar/Wind Harmer
0.061
315671AE2-027_GEN
Solar/Wind Harmer
3.892
315800Z1-036_GEN1
Solar/Wind Harmer
0
3130156CHOWAN
Solar/Wind Harmer
0.057
3143526WINTERP
Solar/Wind Helper
1.618
3143226MDLTHAN
Solar/Wind Helper
0.118
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3145506HICKORY
Solar/Wind Harmer
0.26
3145506HICKORY
Solar/Wind Harmer
0.156
3145506HICKORY
Solar/Wind Harmer
0.039
316339AD2-160 GEN
Solar/Wind Harmer
0.105
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.036
3137176SLIGO L2192
Solar/Wind Harmer
0.256
3146456SLIGO L269
Solar/Wind Harmer
1.137
3130086AYDLETT
Solar/Wind Harmer
0.256
3146386ELIZ CT
Solar/Wind Harmer
0.063
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.061
3146516WINFALL
Solar/Wind Harmer
0.061
3146516WINFALL
Solar/Wind Harmer
0.061
3146626S HERTFORD
Solar/Wind Harmer
0.06
3146626S HERTFORD
Solar/Wind Harmer
0.06
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.255
3146376EDENTON
Solar/Wind Harmer
0.255
3143526WINTERP
Solar/Wind Helper
1.618
3150611CHESTG7
50/50
1.633
3150631CHESTG8
50/50
1.607
971047AG2-646 GEN
50/50
45.726
315759AF1-018 GEN
50/50
3.414
316132AB2-190 GEN1
Solar/Wind Harmer
0.67
315976AC1-164 GENA
Solar/Wind Harmer
12.162
316169AC1-164_GENC
Solar/Wind Harmer
10.507
315975AC1-164 GENB
Solar/Wind Harmer
0.36
316369SG1_INVT
Solar/Wind Harmer
0.004
316314AB2-024 C
Solar/Wind Harmer
0
316059AD1-063 C
Solar/Wind Harmer
0.001
972265AH1-717 GEN
Adder
7.261
3151201GRAVEL4
Adder
6.807
3151191GRAVEL3
Adder
6.721
3151211GRAVEL5
Adder
6.721
3143873LANEXA
Solar/Wind Harmer
0.056
970189AG2-124 GEN
Solar/Wind Harmer
2.733
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.018
3141913WHIT STONE
Solar/Wind Harmer
0.09
3138133OCRAN
Solar/Wind Harmer
0.027
3141783LANCAST
Solar/Wind Harmer
0.053
3141783LANCAST
Solar/Wind Harmer
0.035
3138283WHITEMARSH
Solar/Wind Harmer
0.02
962981AG1-147 GEN
Solar/Wind Harmer
3.244
970327AG2-215 GEN
Solar/Wind Harmer
2.818
3142433PROV 92
Adder
0.165
3142433PROV 92
Adder
0.165
971445AH1-216 GEN
Solar/Wind Harmer
5.957
971167AH1-042 GEN
Solar/Wind Harmer
7.355
3141813NORNECK
Solar/Wind Harmer
0.081
3152611GOSPORTB
Adder
0.865
3152621GOSPORTC
Adder
0.734
3152601GOSPORTA
Adder
0.677
3151081ELIZAR1
Adder
6.186
3151091ELIZAR2
Adder
6.079
316223AC1-118
Solar/Wind Harmer
0.048
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.045
316311AC2-079 GEN
Solar/Wind Harmer
1.899
316305AF2-043 C
Solar/Wind Harmer
0.001
957871AF2-081 GEN
Solar/Wind Harmer
3.21
319010AE1-072 C
Solar/Wind Harmer
0.323
315835AF2-110_GEN
Solar/Wind Harmer
0.44
3146406KITTY HAWK
Solar/Wind Harmer
0.008
313526AB2-022
Solar/Wind Harmer
0.034
3146486SUNBURY
Solar/Wind Harmer
0.063
3146486SUNBURY
Solar/Wind Harmer
0.063
316321Z2-027
Solar/Wind Harmer
0.012
3146396TANGLEW
Solar/Wind Harmer
0.172
3145176PASQUOTANK
Solar/Wind Harmer
0.039
315611Z1-036_GEN2
Solar/Wind Harmer
0
3130156CHOWAN
Solar/Wind Harmer
0.057
3130156CHOWAN
Solar/Wind Harmer
0.057
316233AE1-074 FULL
Solar/Wind Helper
0.475
LAGNLTFEXP_LAGN->PJM
CLTF
0.804
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.434
TVALTFEXP_TVA->PJM
CLTF
0.397
NYPJM->LTFIMP_NY
CLTF
0.33
LGEELTFEXP_LGEE->PJM
CLTF
0.057
WECLTFEXP_WEC->PJM
CLTF
0.026
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.657
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.279
MECLTFEXP_MEC->PJM
CLTF
0.223
SIGELTFEXP_SIGE->PJM
CLTF
0.006
CPLELTFEXP_CPLE->PJM
CLTF
1.734
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.554

Details for 6CHESTF A-6IRON208 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF A-6IRON208 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.5 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:720.05
MW Contribution:2.22
Bus #Bus NameTypeMW Contribution
3150801HOPHCF4
50/50
0.746
971211AH1-065 GEN
50/50
0.9
3151161SURRY 1
50/50
3.123
3142946ENON
Solar/Wind Harmer
0.066
970133AG2-095 GEN
Solar/Wind Harmer
1.215
970129AG2-093 GEN
Solar/Wind Harmer
6.944
315778AD1-151 GEN
Solar/Wind Harmer
8.525
961611AG1-000B GEN
Solar/Wind Harmer
2.377
3151221GRAVEL6
Adder
5.91
3151171GRAVELC
Adder
1.137
3141766HARMONY
Solar/Wind Harmer
1.013
316382AG1-145 C
Solar/Wind Harmer
0.001
3141843SHACKLE
Adder
0.374
316203AE2-005 GEN
Solar/Wind Harmer
0
316280AD1-041 GEN
Solar/Wind Harmer
0.001
316156AD2-030 GEN
Solar/Wind Harmer
0.053
3141873WAN 176
Solar/Wind Harmer
1.283
3145336SMITFLD
Solar/Wind Harmer
0.029
962971AG1-146 GEN
Solar/Wind Harmer
1.096
3142433PROV 92
Adder
0.133
3142433PROV 92
Adder
0.133
970009AG2-005 GEN
Solar/Wind Harmer
0.505
3144216WINCHST
Adder
0.253
316404AE1-155 C
Solar/Wind Harmer
0.015
315813AE1-149 C
Solar/Wind Harmer
3.52
3150921YORKTN3
Adder
1.637
3150351NORNECKC2
Adder
0.647
970659AG2-427 GEN
Solar/Wind Harmer
0.67
316083AB2-161 GEN
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.3
3144536CHRHLND
Solar/Wind Harmer
0.009
3144873MCLAUGH
Solar/Wind Harmer
0.001
3151101ELIZAR3
Adder
5.246
3150621CHESTS7
50/50
0.705
3150781HOPHCF2
50/50
0.513
3150791HOPHCF3
50/50
0.513
3150761HOPPOLC
50/50
0.325
971213AH1-066 GEN
50/50
0.45
3142946ENON
Solar/Wind Harmer
0.02
316033AB2-134 GEN
Solar/Wind Harmer
0.006
315697AD1-025 GEN
Solar/Wind Harmer
0.114
316236AE1-162_GEN
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
2.192
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.669
3150341NORNECKC1
Adder
0.663
316075AC2-137 C
Solar/Wind Harmer
0.018
3150611CHESTG7
50/50
1.535
3150631CHESTG8
50/50
1.511
971047AG2-646 GEN
50/50
42.989
316132AB2-190 GEN1
Solar/Wind Harmer
0.61
316369SG1_INVT
Solar/Wind Harmer
0.004
315976AC1-164 GENA
Solar/Wind Harmer
9.735
316169AC1-164_GENC
Solar/Wind Harmer
8.41
315975AC1-164 GENB
Solar/Wind Harmer
0.288
972265AH1-717 GEN
Adder
6.312
3151201GRAVEL4
Adder
5.917
3151191GRAVEL3
Adder
5.842
3151211GRAVEL5
Adder
5.842
316314AB2-024 C
Solar/Wind Harmer
0
316059AD1-063 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.045
970189AG2-124 GEN
Solar/Wind Harmer
2.166
971445AH1-216 GEN
Solar/Wind Harmer
5.125
315662AE1-191 GEN
Solar/Wind Harmer
0.002
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.014
3141913WHIT STONE
Solar/Wind Harmer
0.071
3138133OCRAN
Solar/Wind Harmer
0.021
3141783LANCAST
Solar/Wind Harmer
0.042
3141783LANCAST
Solar/Wind Harmer
0.028
3138283WHITEMARSH
Solar/Wind Harmer
0.016
962981AG1-147 GEN
Solar/Wind Harmer
2.557
3142433PROV 92
Adder
0.133
3142433PROV 92
Adder
0.133
970327AG2-215 GEN
Solar/Wind Harmer
2.22
971167AH1-042 GEN
Solar/Wind Harmer
5.919
3141813NORNECK
Solar/Wind Harmer
0.064
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.04
316311AC2-079 GEN
Solar/Wind Harmer
1.663
3152611GOSPORTB
Adder
0.725
3152621GOSPORTC
Adder
0.615
3152601GOSPORTA
Adder
0.568
3151081ELIZAR1
Adder
5.179
3151091ELIZAR2
Adder
5.089
316233AE1-074 FULL
Solar/Wind Helper
0.525
3150641CHESTS8
50/50
0.778
944631AF1-128 GEN
50/50
122.303
3150771HOPHCF1
50/50
0.513
970129AG2-093 GEN
Solar/Wind Harmer
3.268
316458AB2-190 GEN2
Solar/Wind Harmer
0.61
971069AG2-661 GEN
Solar/Wind Harmer
1.894
971647AH1-324 GEN
Solar/Wind Harmer
4.071
961611AG1-000B GEN
Solar/Wind Harmer
4.675
3151171GRAVELC
Adder
0.865
3141766HARMONY
Solar/Wind Harmer
0.015
316159AE1-175 C
Solar/Wind Harmer
0.063
971777AH1-397 GEN
Solar/Wind Harmer
0.193
3141843SHACKLE
Adder
0.374
3145336SMITFLD
Solar/Wind Harmer
0.288
3138133OCRAN
Solar/Wind Harmer
0.042
3142433PROV 92
Solar/Wind Harmer
0.273
3142433PROV 92
Adder
0.133
3142433PROV 92
Adder
0.133
962861AG1-135 GEN
Solar/Wind Harmer
2.133
3138126ROCKLANDING
Solar/Wind Harmer
0.03
3141726DUNNSVL
Solar/Wind Harmer
0.265
971317AH1-138 GEN
Solar/Wind Harmer
0.495
3150351NORNECKC2
Adder
0.637
970659AG2-427 GEN
Solar/Wind Harmer
3.065
316381AD1-082 GEN
Solar/Wind Harmer
0.066
970661AG2-428 GEN
Solar/Wind Harmer
6.114
316072AD1-144
Solar/Wind Harmer
0.022
316337AD2-073 GEN
Solar/Wind Harmer
0.051
316375AC2-012 GEN
Solar/Wind Harmer
0.001
3150981CHESPKA
Adder
0.711
3143526WINTERP
Solar/Wind Helper
1.788
3143226MDLTHAN
Solar/Wind Helper
0.157
970657AG2-426 GEN
Solar/Wind Harmer
2.184
970657AG2-426 GEN
Solar/Wind Harmer
0.458
316036AC1-147 C
Solar/Wind Harmer
0.011
3150991CHESPKB
Adder
0.596
3150991CHESPKB
Adder
0.582
3143526WINTERP
Solar/Wind Helper
1.788
LAGNLTFEXP_LAGN->PJM
CLTF
1.059
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.936
TVALTFEXP_TVA->PJM
CLTF
0.526
NYPJM->LTFIMP_NY
CLTF
0.354
LGEELTFEXP_LGEE->PJM
CLTF
0.127
WECLTFEXP_WEC->PJM
CLTF
0.063
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.024
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.746
MECLTFEXP_MEC->PJM
CLTF
0.397
SIGELTFEXP_SIGE->PJM
CLTF
0.011
CPLELTFEXP_CPLE->PJM
CLTF
1.919
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.103

Details for 6COMORN-6BIRCHWD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6COMORN-6BIRCHWD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.42 %
Rating:548.02 MVA
Rating Type:B
MVA to Mitigate:681.85
MW Contribution:7.19
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
2.956
966661AG1-536 GEN
50/50
6.849
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
971353AH1-157 GEN
50/50
7.408
970017AG2-010 GEN
50/50
4.699
3150641CHESTS8
50/50
0.203
944631AF1-128 GEN
50/50
31.925
972135AH1-637 GEN
Solar/Wind Harmer
4.389
316337AD2-073 GEN
Solar/Wind Harmer
0.299
3141726DUNNSVL
Solar/Wind Harmer
1.044
962861AG1-135 GEN
Solar/Wind Harmer
7.523
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
3141316ARNOLDS
50/50
2.018
3150351NORNECKC2
50/50
3.006
970575AG2-366 GEN
50/50
3.66
315749AE2-041 GEN
50/50
4.946
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150921YORKTN3
50/50
1.929
3144216WINCHST
50/50
0.279
3151161SURRY 1
50/50
2.166
970737AG2-469 GEN
Solar/Wind Harmer
20.178
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.637
962971AG1-146 GEN
Solar/Wind Harmer
3.294
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.61
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.855
971317AH1-138 GEN
Solar/Wind Harmer
0.613
316159AE1-175 C
Solar/Wind Harmer
0.065
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3142416OLDCHRC
Solar/Wind Harmer
0.149
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.6
315759AF1-018 GEN
50/50
4.946
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150611CHESTG7
50/50
0.401
3150631CHESTG8
50/50
0.394
971047AG2-646 GEN
50/50
11.221
972263AH1-716 GEN
50/50
32.871
944491AF1-114 GEN
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Harmer
0.296
3141813NORNECK
Solar/Wind Harmer
0.279
970327AG2-215 GEN
Solar/Wind Harmer
7.194
962981AG1-147 GEN
Solar/Wind Harmer
7.685
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.051
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
0.029
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.081
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
9.122
315976AC1-164 GENA
Solar/Wind Harmer
8.292
316169AC1-164_GENC
Solar/Wind Harmer
7.163
315975AC1-164 GENB
Solar/Wind Harmer
0.245
316312AB1-027
Solar/Wind Harmer
0.102
972265AH1-717 GEN
Adder
4.377
3151201GRAVEL4
Adder
4.104
3151191GRAVEL3
Adder
4.052
3151211GRAVEL5
Adder
4.052
3141426STAFORD
Solar/Wind Helper
0.031
957191AF2-013 GEN
50/50
65.713
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.668
3142416OLDCHRC
Solar/Wind Harmer
0.555
3151221GRAVEL6
Adder
4.099
3151171GRAVELC
Adder
0.789
3150341NORNECKC1
50/50
3.105
3150341NORNECKC1
50/50
3.08
963611AG1-210 GEN
50/50
0.994
3150621CHESTS7
50/50
0.184
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
7.962
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.007
LAGNLTFEXP_LAGN->PJM
CLTF
1.483
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.388
TVALTFEXP_TVA->PJM
CLTF
0.749
NYPJM->LTFIMP_NY
CLTF
0.564
LGEELTFEXP_LGEE->PJM
CLTF
0.274
WECLTFEXP_WEC->PJM
CLTF
0.137
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.711
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.577
MECLTFEXP_MEC->PJM
CLTF
0.732
SIGELTFEXP_SIGE->PJM
CLTF
0.022
CPLELTFEXP_CPLE->PJM
CLTF
1.997
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.895

Details for 6COMORN-6BIRCHWD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6COMORN-6BIRCHWD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.98 %
Rating:548.02 MVA
Rating Type:B
MVA to Mitigate:575.3
MW Contribution:7.23
Bus #Bus NameTypeMW Contribution
3141316ARNOLDS
50/50
2.026
3150351NORNECKC2
50/50
3.02
970575AG2-366 GEN
50/50
3.68
315749AE2-041 GEN
50/50
4.976
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
3150921YORKTN3
50/50
2.003
3144216WINCHST
50/50
0.289
3151161SURRY 1
50/50
2.191
970737AG2-469 GEN
Solar/Wind Harmer
20.26
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.646
962971AG1-146 GEN
Solar/Wind Harmer
3.312
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.629
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.866
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.022
3151221GRAVEL6
Adder
4.147
3151171GRAVELC
Adder
0.798
970293AG2-193 GEN
Solar/Wind Harmer
0.603
315759AF1-018 GEN
50/50
4.976
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
972263AH1-716 GEN
50/50
35.649
3150611CHESTG7
50/50
0.379
3150631CHESTG8
50/50
0.372
971047AG2-646 GEN
50/50
10.599
944491AF1-114 GEN
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Harmer
0.297
3141813NORNECK
Solar/Wind Harmer
0.28
970327AG2-215 GEN
Solar/Wind Harmer
7.232
962981AG1-147 GEN
Solar/Wind Harmer
7.729
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.074
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.168
3141873WAN 176
Solar/Wind Harmer
0.03
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.097
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
8.942
315976AC1-164 GENA
Solar/Wind Harmer
8.275
316169AC1-164_GENC
Solar/Wind Harmer
7.149
315975AC1-164 GENB
Solar/Wind Harmer
0.245
972265AH1-717 GEN
Adder
4.429
3151201GRAVEL4
Adder
4.152
3151191GRAVEL3
Adder
4.099
3151211GRAVEL5
Adder
4.099
3141426STAFORD
Solar/Wind Helper
0.029
3150351NORNECKC2
50/50
2.97
966661AG1-536 GEN
50/50
6.884
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
971353AH1-157 GEN
50/50
7.642
970017AG2-010 GEN
50/50
4.875
3150641CHESTS8
50/50
0.192
944631AF1-128 GEN
50/50
30.156
3152331SURRY 2
50/50
2.455
972135AH1-637 GEN
Solar/Wind Harmer
4.407
316337AD2-073 GEN
Solar/Wind Harmer
0.3
3141726DUNNSVL
Solar/Wind Harmer
1.049
962861AG1-135 GEN
Solar/Wind Harmer
7.561
3138133OCRAN
Solar/Wind Harmer
0.104
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.365
3142433PROV 92
Solar/Wind Harmer
0.422
971317AH1-138 GEN
Solar/Wind Harmer
0.633
316159AE1-175 C
Solar/Wind Harmer
0.067
3138126ROCKLANDING
Solar/Wind Harmer
0.034
3151171GRAVELC
Adder
0.607
957191AF2-013 GEN
50/50
65.968
3150341NORNECKC1
50/50
3.119
3150341NORNECKC1
50/50
3.094
963611AG1-210 GEN
50/50
0.998
3150621CHESTS7
50/50
0.174
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
8.003
316075AC2-137 C
Solar/Wind Harmer
0.018
3142946ENON
Solar/Wind Harmer
0.007
LAGNLTFEXP_LAGN->PJM
CLTF
1.213
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.047
TVALTFEXP_TVA->PJM
CLTF
0.609
NYPJM->LTFIMP_NY
CLTF
0.465
LGEELTFEXP_LGEE->PJM
CLTF
0.185
WECLTFEXP_WEC->PJM
CLTF
0.092
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.061
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.057
MECLTFEXP_MEC->PJM
CLTF
0.525
SIGELTFEXP_SIGE->PJM
CLTF
0.016
CPLELTFEXP_CPLE->PJM
CLTF
1.912
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.152

Details for 6CRANES-6SPARTAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9296_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CRANES-6SPARTAN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 9296_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.06 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1033.93
MW Contribution:4.38
Bus #Bus NameTypeMW Contribution
3150331BIRCHWDA
50/50
74.484
3141316ARNOLDS
50/50
0.959
3150401LDYSMT4
50/50
24.421
3150371LDYSMT1
50/50
23.598
3150501FRIVERG
50/50
1.371
3150351NORNECKC2
50/50
1.714
970737AG2-469 GEN
Solar/Wind Harmer
10.3
3141906WESTMOR
Solar/Wind Harmer
0.086
971781AH1-399 GEN
Solar/Wind Harmer
0.24
316404AE1-155 C
Solar/Wind Harmer
0.032
970009AG2-005 GEN
Solar/Wind Harmer
0.998
962971AG1-146 GEN
Solar/Wind Harmer
2.046
316156AD2-030 GEN
Solar/Wind Harmer
0.076
3141873WAN 176
Solar/Wind Harmer
1.826
316280AD1-041 GEN
Solar/Wind Harmer
0.002
3141766HARMONY
Solar/Wind Harmer
1.33
316203AE2-005 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
0.507
316473AC1-191 GEN
Solar/Wind Harmer
0.322
3142433PROV 92
Adder
0.171
3142433PROV 92
Adder
0.171
3142416OLDCHRC
Solar/Wind Harmer
0.709
970293AG2-193 GEN
Solar/Wind Harmer
0.775
3142946ENON
Solar/Wind Harmer
0.024
316382AG1-145 C
Solar/Wind Harmer
0.001
3143096IRON208
Adder
0.289
3143096IRON208
Adder
0.283
3150921YORKTN3
Adder
1.719
3144216WINCHST
Adder
0.254
970133AG2-095 GEN
Solar/Wind Harmer
0.63
970129AG2-093 GEN
Solar/Wind Harmer
3.914
315778AD1-151 GEN
Solar/Wind Harmer
5.128
3150861SPRUNCD
Adder
0.294
965281AG1-393 GEN
Solar/Wind Harmer
0.677
961611AG1-000B GEN
Solar/Wind Harmer
1.673
3151221GRAVEL6
Adder
4.517
3151171GRAVELC
Adder
0.869
315839AE2-212 C
Solar/Wind Harmer
0
3145336SMITFLD
Solar/Wind Harmer
0.024
315813AE1-149 C
Solar/Wind Harmer
3.187
970659AG2-427 GEN
Solar/Wind Harmer
0.623
316083AB2-161 GEN
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.234
3144536CHRHLND
Solar/Wind Harmer
0.009
3144873MCLAUGH
Solar/Wind Harmer
0.001
3151101ELIZAR3
Adder
5.306
315773AC2-141 GEN
Solar/Wind Harmer
2.068
944581AF1-123 GEN
Solar/Wind Harmer
12.738
944601AF1-125 GEN
Solar/Wind Harmer
12.541
3150411LDYSMT5
50/50
24.498
3150381LDYSMT2
50/50
23.445
972213AH1-691 GEN
50/50
3.966
972215AH1-692 GEN
50/50
3.966
963051AG1-154 GEN
50/50
3.051
944491AF1-114 GEN
Solar/Wind Harmer
0.001
316223AC1-118
Solar/Wind Harmer
0.155
3141813NORNECK
Solar/Wind Harmer
0.159
970327AG2-215 GEN
Solar/Wind Harmer
4.385
962981AG1-147 GEN
Solar/Wind Harmer
4.775
3141783LANCAST
Solar/Wind Harmer
0.071
3141783LANCAST
Solar/Wind Harmer
0.047
3138133OCRAN
Solar/Wind Harmer
0.034
3141913WHIT STONE
Solar/Wind Harmer
0.111
3141873WAN 176
Solar/Wind Harmer
0.021
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
2.943
316314AB2-024 C
Solar/Wind Harmer
0
972189AH1-679 GEN
Adder
1.608
3143873LANEXA
Solar/Wind Harmer
0.057
3142433PROV 92
Adder
0.171
3142433PROV 92
Adder
0.171
971167AH1-042 GEN
Solar/Wind Harmer
7.69
3138283WHITEMARSH
Solar/Wind Harmer
0.02
315976AC1-164 GENA
Solar/Wind Harmer
7.877
316169AC1-164_GENC
Solar/Wind Harmer
6.805
315975AC1-164 GENB
Solar/Wind Harmer
0.233
316312AB1-027
Solar/Wind Harmer
0.131
316132AB2-190 GEN1
Solar/Wind Harmer
0.347
971285AH1-108 GEN
Adder
0.482
316369SG1_INVT
Solar/Wind Harmer
0.002
972265AH1-717 GEN
Adder
4.824
3151201GRAVEL4
Adder
4.522
3151191GRAVEL3
Adder
4.465
3151211GRAVEL5
Adder
4.465
971445AH1-216 GEN
Solar/Wind Harmer
4.254
316233AE1-074 FULL
Solar/Wind Harmer
0.047
971281AH1-106 GEN
Solar/Wind Harmer
0.819
971283AH1-107 GEN
Solar/Wind Harmer
0.819
3143316POE
Solar/Wind Harmer
0.231
3152611GOSPORTB
Adder
0.729
3152621GOSPORTC
Adder
0.618
3152601GOSPORTA
Adder
0.571
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.039
316311AC2-079 GEN
Solar/Wind Harmer
1.643
3151081ELIZAR1
Adder
5.239
3151091ELIZAR2
Adder
5.148
316305AF2-043 C
Solar/Wind Harmer
0
957871AF2-081 GEN
Solar/Wind Harmer
2.801
315835AF2-110_GEN
Solar/Wind Harmer
0.386
3141426STAFORD
Solar/Wind Helper
0.174
3141346CRANES
50/50
0.721
972197AH1-683 GEN
50/50
3.813
972219AH1-694 GEN
50/50
2.746
3150351NORNECKC2
50/50
1.686
966661AG1-536 GEN
50/50
4.063
972135AH1-637 GEN
Solar/Wind Harmer
2.21
316337AD2-073 GEN
Solar/Wind Harmer
0.162
3141726DUNNSVL
Solar/Wind Harmer
0.606
962861AG1-135 GEN
Solar/Wind Harmer
4.492
966881AG1-559 GEN
Solar/Wind Harmer
0.158
3138133OCRAN
Solar/Wind Harmer
0.068
3141766HARMONY
Solar/Wind Harmer
0.02
971777AH1-397 GEN
Solar/Wind Harmer
0.262
3141843SHACKLE
Adder
0.507
3142433PROV 92
Solar/Wind Harmer
0.352
3142433PROV 92
Adder
0.171
3142433PROV 92
Adder
0.171
3142416OLDCHRC
Solar/Wind Harmer
0.19
3142416OLDCHRC
Solar/Wind Harmer
0.073
971317AH1-138 GEN
Solar/Wind Harmer
0.545
316159AE1-175 C
Solar/Wind Harmer
0.061
944631AF1-128 GEN
Adder
33.488
3143096IRON208
Adder
0.289
3138126ROCKLANDING
Solar/Wind Harmer
0.031
3142543TWELFTH
Solar/Wind Harmer
0.006
970129AG2-093 GEN
Solar/Wind Harmer
1.842
316458AB2-190 GEN2
Solar/Wind Harmer
0.347
315671AE2-027_GEN
Solar/Wind Harmer
4.113
971069AG2-661 GEN
Solar/Wind Harmer
1.14
3150851SPRUNCC
Adder
0.294
971647AH1-324 GEN
Solar/Wind Harmer
2.698
961611AG1-000B GEN
Solar/Wind Harmer
3.29
3151171GRAVELC
Adder
0.661
3145336SMITFLD
Solar/Wind Harmer
0.241
3143526WINTERP
Solar/Wind Harmer
0.307
970659AG2-427 GEN
Solar/Wind Harmer
2.85
316381AD1-082 GEN
Solar/Wind Harmer
0.061
316072AD1-144
Solar/Wind Harmer
0.021
970661AG2-428 GEN
Solar/Wind Harmer
5.802
316375AC2-012 GEN
Solar/Wind Harmer
0.001
3150981CHESPKA
Adder
0.715
316294AC1-161 GEN
Solar/Wind Harmer
0.981
944591AF1-124 GEN
Solar/Wind Harmer
12.783
316246AF1-032 C
Solar/Wind Harmer
0.025
316388AE2-253 GEN
Solar/Wind Harmer
0.176
316093AE2-104_GEN
Solar/Wind Harmer
0.946
957191AF2-013 GEN
50/50
31.493
3150391LDYSMT3
50/50
24.376
972195AH1-682 GEN
50/50
3.203
3150341NORNECKC1
50/50
1.771
3150341NORNECKC1
50/50
1.756
963611AG1-210 GEN
50/50
0.567
316468AD1-105 GEN
Solar/Wind Harmer
-0.059
316077AC2-138 C
Solar/Wind Harmer
0.001
315673AE1-157 GEN
Solar/Wind Harmer
10.324
958261AF2-120 GEN
Solar/Wind Harmer
4.723
957411AF2-035 GEN
Solar/Wind Harmer
5.818
970317AG2-208 GEN
Solar/Wind Harmer
5.39
966871AG1-558 GEN
Solar/Wind Harmer
0.11
316075AC2-137 C
Solar/Wind Harmer
0.02
3142946ENON
Solar/Wind Harmer
0.007
3142296MT RD221
Adder
0.227
3150691DARBY 3
Adder
5.107
3150701DARBY 4
Adder
5.095
3150681DARBY 2
Adder
5.089
3150671DARBY 1
Adder
5.083
3142366NRTHEST
Adder
0.229
944641AF1-129 GEN
Adder
30.454
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.072
316240AF1-291 C
Solar/Wind Harmer
0.001
316236AE1-162_GEN
Solar/Wind Harmer
0
3143526WINTERP
Solar/Wind Harmer
0.307
970657AG2-426 GEN
Solar/Wind Harmer
2.053
970657AG2-426 GEN
Solar/Wind Harmer
0.43
316036AC1-147 C
Solar/Wind Harmer
0.011
3150991CHESPKB
Adder
0.599
3150991CHESPKB
Adder
0.585
316316AC1-027 C
Solar/Wind Harmer
0.055
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3145506HICKORY
Solar/Wind Harmer
0.226
3145506HICKORY
Solar/Wind Harmer
0.136
3145506HICKORY
Solar/Wind Harmer
0.034
316339AD2-160 GEN
Solar/Wind Harmer
0.091
316018AA1-139 ULT2
Solar/Wind Harmer
0.001
316017AA1-139 ULT1
Solar/Wind Harmer
0.031
LAGNLTFEXP_LAGN->PJM
CLTF
2.016
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.794
TVALTFEXP_TVA->PJM
CLTF
1.019
NYPJM->LTFIMP_NY
CLTF
0.793
LGEELTFEXP_LGEE->PJM
CLTF
0.39
WECLTFEXP_WEC->PJM
CLTF
0.196
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.786
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.522
MECLTFEXP_MEC->PJM
CLTF
1.029
SIGELTFEXP_SIGE->PJM
CLTF
0.032
CPLELTFEXP_CPLE->PJM
CLTF
2.609
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.871

Details for 6CRANES-6SPARTAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2119_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CRANES-6SPARTAN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2119_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.03 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1033.72
MW Contribution:4.38
Bus #Bus NameTypeMW Contribution
3150411LDYSMT5
50/50
24.498
3150381LDYSMT2
50/50
23.445
972213AH1-691 GEN
50/50
3.966
972215AH1-692 GEN
50/50
3.966
963051AG1-154 GEN
50/50
3.051
944491AF1-114 GEN
Solar/Wind Harmer
0.001
316223AC1-118
Solar/Wind Harmer
0.155
3141813NORNECK
Solar/Wind Harmer
0.159
970327AG2-215 GEN
Solar/Wind Harmer
4.385
962981AG1-147 GEN
Solar/Wind Harmer
4.775
3141783LANCAST
Solar/Wind Harmer
0.071
3141783LANCAST
Solar/Wind Harmer
0.047
3138133OCRAN
Solar/Wind Harmer
0.034
3141913WHIT STONE
Solar/Wind Harmer
0.111
3141873WAN 176
Solar/Wind Harmer
0.021
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
2.943
316314AB2-024 C
Solar/Wind Harmer
0
972189AH1-679 GEN
Adder
1.608
3143873LANEXA
Solar/Wind Harmer
0.057
3142433PROV 92
Adder
0.171
3142433PROV 92
Adder
0.171
971167AH1-042 GEN
Solar/Wind Harmer
7.69
3138283WHITEMARSH
Solar/Wind Harmer
0.02
315976AC1-164 GENA
Solar/Wind Harmer
7.877
316169AC1-164_GENC
Solar/Wind Harmer
6.805
315975AC1-164 GENB
Solar/Wind Harmer
0.233
316312AB1-027
Solar/Wind Harmer
0.131
316132AB2-190 GEN1
Solar/Wind Harmer
0.347
971285AH1-108 GEN
Adder
0.482
316369SG1_INVT
Solar/Wind Harmer
0.002
972265AH1-717 GEN
Adder
4.824
3151201GRAVEL4
Adder
4.522
3151191GRAVEL3
Adder
4.465
3151211GRAVEL5
Adder
4.465
971445AH1-216 GEN
Solar/Wind Harmer
4.254
316233AE1-074 FULL
Solar/Wind Harmer
0.047
971281AH1-106 GEN
Solar/Wind Harmer
0.819
971283AH1-107 GEN
Solar/Wind Harmer
0.819
3143316POE
Solar/Wind Harmer
0.231
3152611GOSPORTB
Adder
0.729
3152621GOSPORTC
Adder
0.618
3152601GOSPORTA
Adder
0.571
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.039
316311AC2-079 GEN
Solar/Wind Harmer
1.643
3151081ELIZAR1
Adder
5.239
3151091ELIZAR2
Adder
5.148
316305AF2-043 C
Solar/Wind Harmer
0
957871AF2-081 GEN
Solar/Wind Harmer
2.801
315835AF2-110_GEN
Solar/Wind Harmer
0.386
3141426STAFORD
Solar/Wind Helper
0.174
957191AF2-013 GEN
50/50
31.493
3150391LDYSMT3
50/50
24.376
972195AH1-682 GEN
50/50
3.203
3150341NORNECKC1
50/50
1.771
3150341NORNECKC1
50/50
1.756
963611AG1-210 GEN
50/50
0.567
316468AD1-105 GEN
Solar/Wind Harmer
-0.059
316077AC2-138 C
Solar/Wind Harmer
0.001
315673AE1-157 GEN
Solar/Wind Harmer
10.324
958261AF2-120 GEN
Solar/Wind Harmer
4.723
957411AF2-035 GEN
Solar/Wind Harmer
5.818
970317AG2-208 GEN
Solar/Wind Harmer
5.39
966871AG1-558 GEN
Solar/Wind Harmer
0.11
316075AC2-137 C
Solar/Wind Harmer
0.02
3142946ENON
Solar/Wind Harmer
0.007
3142296MT RD221
Adder
0.227
3150691DARBY 3
Adder
5.107
3150701DARBY 4
Adder
5.095
3150681DARBY 2
Adder
5.089
3150671DARBY 1
Adder
5.083
3142366NRTHEST
Adder
0.229
944641AF1-129 GEN
Adder
30.454
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.072
316240AF1-291 C
Solar/Wind Harmer
0.001
316236AE1-162_GEN
Solar/Wind Harmer
0
3143526WINTERP
Solar/Wind Harmer
0.307
970657AG2-426 GEN
Solar/Wind Harmer
2.053
970657AG2-426 GEN
Solar/Wind Harmer
0.43
316036AC1-147 C
Solar/Wind Harmer
0.011
3150991CHESPKB
Adder
0.599
3150991CHESPKB
Adder
0.585
316316AC1-027 C
Solar/Wind Harmer
0.055
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3145506HICKORY
Solar/Wind Harmer
0.226
3145506HICKORY
Solar/Wind Harmer
0.136
3145506HICKORY
Solar/Wind Harmer
0.034
316339AD2-160 GEN
Solar/Wind Harmer
0.091
316018AA1-139 ULT2
Solar/Wind Harmer
0.001
316017AA1-139 ULT1
Solar/Wind Harmer
0.031
3141346CRANES
50/50
0.721
972197AH1-683 GEN
50/50
3.813
972219AH1-694 GEN
50/50
2.746
3150351NORNECKC2
50/50
1.686
966661AG1-536 GEN
50/50
4.063
972135AH1-637 GEN
Solar/Wind Harmer
2.21
316337AD2-073 GEN
Solar/Wind Harmer
0.162
3141726DUNNSVL
Solar/Wind Harmer
0.606
962861AG1-135 GEN
Solar/Wind Harmer
4.492
966881AG1-559 GEN
Solar/Wind Harmer
0.158
3138133OCRAN
Solar/Wind Harmer
0.068
3141766HARMONY
Solar/Wind Harmer
0.02
971777AH1-397 GEN
Solar/Wind Harmer
0.262
3141843SHACKLE
Adder
0.507
3142433PROV 92
Solar/Wind Harmer
0.352
3142433PROV 92
Adder
0.171
3142433PROV 92
Adder
0.171
3142416OLDCHRC
Solar/Wind Harmer
0.19
3142416OLDCHRC
Solar/Wind Harmer
0.073
971317AH1-138 GEN
Solar/Wind Harmer
0.545
316159AE1-175 C
Solar/Wind Harmer
0.061
944631AF1-128 GEN
Adder
33.488
3150331BIRCHWDA
50/50
74.484
3141316ARNOLDS
50/50
0.959
3150401LDYSMT4
50/50
24.421
3150371LDYSMT1
50/50
23.598
3150501FRIVERG
50/50
1.371
3150351NORNECKC2
50/50
1.714
970737AG2-469 GEN
Solar/Wind Harmer
10.3
3141906WESTMOR
Solar/Wind Harmer
0.086
971781AH1-399 GEN
Solar/Wind Harmer
0.24
316404AE1-155 C
Solar/Wind Harmer
0.032
970009AG2-005 GEN
Solar/Wind Harmer
0.998
962971AG1-146 GEN
Solar/Wind Harmer
2.046
316156AD2-030 GEN
Solar/Wind Harmer
0.076
3141873WAN 176
Solar/Wind Harmer
1.826
316280AD1-041 GEN
Solar/Wind Harmer
0.002
3141766HARMONY
Solar/Wind Harmer
1.33
316203AE2-005 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
0.507
316473AC1-191 GEN
Solar/Wind Harmer
0.322
3142433PROV 92
Adder
0.171
3142433PROV 92
Adder
0.171
3142416OLDCHRC
Solar/Wind Harmer
0.709
970293AG2-193 GEN
Solar/Wind Harmer
0.775
3142946ENON
Solar/Wind Harmer
0.024
316382AG1-145 C
Solar/Wind Harmer
0.001
3143096IRON208
Adder
0.289
3143096IRON208
Adder
0.283
3150921YORKTN3
Adder
1.719
3144216WINCHST
Adder
0.254
970133AG2-095 GEN
Solar/Wind Harmer
0.63
970129AG2-093 GEN
Solar/Wind Harmer
3.914
315778AD1-151 GEN
Solar/Wind Harmer
5.128
3150861SPRUNCD
Adder
0.294
965281AG1-393 GEN
Solar/Wind Harmer
0.677
961611AG1-000B GEN
Solar/Wind Harmer
1.673
3151221GRAVEL6
Adder
4.517
3151171GRAVELC
Adder
0.869
315839AE2-212 C
Solar/Wind Harmer
0
3145336SMITFLD
Solar/Wind Harmer
0.024
315813AE1-149 C
Solar/Wind Harmer
3.187
970659AG2-427 GEN
Solar/Wind Harmer
0.623
316083AB2-161 GEN
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.234
3144536CHRHLND
Solar/Wind Harmer
0.009
3144873MCLAUGH
Solar/Wind Harmer
0.001
3151101ELIZAR3
Adder
5.306
315773AC2-141 GEN
Solar/Wind Harmer
2.068
944581AF1-123 GEN
Solar/Wind Harmer
12.738
944601AF1-125 GEN
Solar/Wind Harmer
12.541
3143096IRON208
Adder
0.289
3138126ROCKLANDING
Solar/Wind Harmer
0.031
3142543TWELFTH
Solar/Wind Harmer
0.006
970129AG2-093 GEN
Solar/Wind Harmer
1.842
316458AB2-190 GEN2
Solar/Wind Harmer
0.347
315671AE2-027_GEN
Solar/Wind Harmer
4.113
971069AG2-661 GEN
Solar/Wind Harmer
1.14
3150851SPRUNCC
Adder
0.294
971647AH1-324 GEN
Solar/Wind Harmer
2.698
961611AG1-000B GEN
Solar/Wind Harmer
3.29
3151171GRAVELC
Adder
0.661
3145336SMITFLD
Solar/Wind Harmer
0.241
3143526WINTERP
Solar/Wind Harmer
0.307
970659AG2-427 GEN
Solar/Wind Harmer
2.85
316381AD1-082 GEN
Solar/Wind Harmer
0.061
316072AD1-144
Solar/Wind Harmer
0.021
970661AG2-428 GEN
Solar/Wind Harmer
5.802
316375AC2-012 GEN
Solar/Wind Harmer
0.001
3150981CHESPKA
Adder
0.715
316294AC1-161 GEN
Solar/Wind Harmer
0.981
944591AF1-124 GEN
Solar/Wind Harmer
12.783
316246AF1-032 C
Solar/Wind Harmer
0.025
316388AE2-253 GEN
Solar/Wind Harmer
0.176
316093AE2-104_GEN
Solar/Wind Harmer
0.946
LAGNLTFEXP_LAGN->PJM
CLTF
2.016
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.794
TVALTFEXP_TVA->PJM
CLTF
1.019
NYPJM->LTFIMP_NY
CLTF
0.793
LGEELTFEXP_LGEE->PJM
CLTF
0.39
WECLTFEXP_WEC->PJM
CLTF
0.196
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.786
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.522
MECLTFEXP_MEC->PJM
CLTF
1.029
SIGELTFEXP_SIGE->PJM
CLTF
0.032
CPLELTFEXP_CPLE->PJM
CLTF
2.609
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.871

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o PEPCO_P1_5070_SRT-A


Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
PEPCO_P1_5070_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:152.59 %
Rating:1331.98 MVA
Rating Type:B
MVA to Mitigate:2032.49
MW Contribution:2.82
Bus #Bus NameTypeMW Contribution
972289AH1-729 GEN
50/50
13.249
3150091POSSM6B
50/50
0.848
3150071POSSM 5
50/50
52.224
3150181POSSMC2
50/50
1.152
3150181POSSMC2
50/50
1.143
3150181POSSMC2
50/50
1.143
316447AC1-158 HLD
Solar/Wind Harmer
1.014
3150391LDYSMT3
Adder
12.655
972195AH1-682 GEN
Adder
1.663
315651AD1-115 GEN
Solar/Wind Harmer
0.003
315673AE1-157 GEN
Solar/Wind Harmer
6.396
957411AF2-035 GEN
Solar/Wind Harmer
3.895
970317AG2-208 GEN
Solar/Wind Harmer
3.609
316468AD1-105 GEN
Solar/Wind Harmer
-0.029
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.913
3150341NORNECKC1
Adder
0.906
966001AG1-469 GEN
Solar/Wind Harmer
0.051
958261AF2-120 GEN
Solar/Wind Harmer
2.86
3151731LOISA B
Adder
5.599
3151721LOISA A
Adder
5.57
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.271
3142366NRTHEST
Adder
0.276
3150691DARBY 3
Adder
6.069
3150701DARBY 4
Adder
6.055
3150681DARBY 2
Adder
6.048
3150671DARBY 1
Adder
6.041
316075AC2-137 C
Solar/Wind Harmer
0.023
3142946ENON
Solar/Wind Harmer
0.008
3143526WINTERP
Solar/Wind Harmer
0.435
971223AH1-071 GEN
Solar/Wind Harmer
0.89
944641AF1-129 GEN
Adder
39.415
316240AF1-291 C
Solar/Wind Harmer
0.001
316033AB2-134 GEN
Solar/Wind Harmer
0.005
315697AD1-025 GEN
Solar/Wind Harmer
0.092
316236AE1-162_GEN
Solar/Wind Harmer
0.001
970657AG2-426 GEN
Solar/Wind Harmer
2.829
970657AG2-426 GEN
Solar/Wind Harmer
0.593
316036AC1-147 C
Solar/Wind Harmer
0.015
3150991CHESPKB
Adder
0.845
3150991CHESPKB
Adder
0.825
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.077
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3145506HICKORY
Solar/Wind Harmer
0.321
3145506HICKORY
Solar/Wind Harmer
0.193
3145506HICKORY
Solar/Wind Harmer
0.048
316339AD2-160 GEN
Solar/Wind Harmer
0.13
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
3152131X4-039 ST
50/50
2.892
3152121X4-039 GT2
50/50
1.833
3150011OMF A
50/50
0.216
3140676OCCOQUN
50/50
0.286
970467AG2-304 GEN
50/50
14.788
972223AH1-696 GEN
50/50
9.026
3150151POSSMC1
50/50
1.143
3141346CRANES
50/50
0.127
3150221REMNGT2
50/50
13.228
972201AH1-685 GEN
50/50
2.282
3150211REMNGT1
Adder
12.383
3150281M RUN A
Adder
13.357
316006AB2-029 C
Solar/Wind Harmer
0.001
971685AH1-345 GEN
Solar/Wind Harmer
0.73
316045AC1-158 PL2
Solar/Wind Harmer
1.475
972197AH1-683 GEN
Adder
1.98
972219AH1-694 GEN
Adder
1.425
316254AC1-120 GEN1
Solar/Wind Harmer
0.2
972135AH1-637 GEN
Solar/Wind Harmer
0.781
966881AG1-559 GEN
Solar/Wind Harmer
0.105
315683AE1-153 C
Solar/Wind Harmer
7.218
3147666LOUISA
Solar/Wind Harmer
0.355
316192AB2-158 GEN
Solar/Wind Harmer
0.501
970053AG2-049 GEN
50/50
2.022
3138216PACIFIC
Solar/Wind Harmer
0.025
316411AF1-147_GEN1
Solar/Wind Harmer
0.003
316415AF1-147_GEN2
Solar/Wind Harmer
0.003
3141426STAFORD
Solar/Wind Harmer
0.023
3150411LDYSMT5
Adder
12.718
3150381LDYSMT2
Adder
12.172
972213AH1-691 GEN
Adder
2.059
972215AH1-692 GEN
Adder
2.059
316164AC1-076 GEN
Solar/Wind Harmer
0.132
944491AF1-114 GEN
Solar/Wind Harmer
0
316223AC1-118
Solar/Wind Harmer
0.064
972189AH1-679 GEN
Adder
1.467
3141813NORNECK
Solar/Wind Harmer
0.087
970327AG2-215 GEN
Solar/Wind Harmer
2.824
962981AG1-147 GEN
Solar/Wind Harmer
3.203
3141783LANCAST
Solar/Wind Harmer
0.051
3141783LANCAST
Solar/Wind Harmer
0.034
3138133OCRAN
Solar/Wind Harmer
0.025
3141913WHIT STONE
Solar/Wind Harmer
0.085
3147346CASHSCORNER
Solar/Wind Harmer
0.196
316312AB1-027
Solar/Wind Harmer
0.152
316314AB2-024 C
Solar/Wind Harmer
0
316059AD1-063 C
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.017
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
2.507
3143873LANEXA
Solar/Wind Harmer
0.051
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
971167AH1-042 GEN
Solar/Wind Harmer
7.477
315976AC1-164 GENA
Solar/Wind Harmer
8.72
316169AC1-164_GENC
Solar/Wind Harmer
7.533
315975AC1-164 GENB
Solar/Wind Harmer
0.258
316233AE1-074 FULL
Solar/Wind Harmer
0.067
971281AH1-106 GEN
Solar/Wind Harmer
1.161
971283AH1-107 GEN
Solar/Wind Harmer
1.161
971285AH1-108 GEN
Adder
0.631
3138283WHITEMARSH
Solar/Wind Harmer
0.019
316132AB2-190 GEN1
Solar/Wind Harmer
0.442
316369SG1_INVT
Solar/Wind Harmer
0.003
972265AH1-717 GEN
Adder
6.337
3151201GRAVEL4
Adder
5.94
3151191GRAVEL3
Adder
5.865
3151211GRAVEL5
Adder
5.865
971445AH1-216 GEN
Solar/Wind Harmer
5.723
3143316POE
Solar/Wind Harmer
0.321
3151081ELIZAR1
Adder
7.394
3151091ELIZAR2
Adder
7.266
3152611GOSPORTB
Adder
1.027
3152621GOSPORTC
Adder
0.872
3152601GOSPORTA
Adder
0.804
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.055
316311AC2-079 GEN
Solar/Wind Harmer
2.303
957871AF2-081 GEN
Solar/Wind Harmer
3.99
316305AF2-043 C
Solar/Wind Harmer
0.001
319010AE1-072 C
Solar/Wind Harmer
0.403
3146406KITTY HAWK
Solar/Wind Harmer
0.01
315835AF2-110_GEN
Solar/Wind Harmer
0.548
313526AB2-022
Solar/Wind Harmer
0.043
3146486SUNBURY
Solar/Wind Harmer
0.079
3146486SUNBURY
Solar/Wind Harmer
0.079
316321Z2-027
Solar/Wind Harmer
0.015
3146396TANGLEW
Solar/Wind Harmer
0.219
3145176PASQUOTANK
Solar/Wind Harmer
0.049
316315AB2-025 C
Solar/Wind Harmer
0.064
315814AE2-033 C
Solar/Wind Harmer
6.204
941031AE2-094 GEN
Solar/Wind Harmer
14.412
944011AF1-069 GEN
Solar/Wind Harmer
4.709
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.078
3130156CHOWAN
Solar/Wind Harmer
0.078
970673AG2-436 GEN
Solar/Wind Harmer
16.54
970673AG2-436 GEN
Solar/Wind Harmer
11.027
971967AH1-528 GEN
Solar/Wind Harmer
12.344
315816AE2-034 GEN
Solar/Wind Harmer
0.329
3130546PLYMOUTH
Solar/Wind Harmer
0.076
315732AD1-074 GEN1
Solar/Wind Harmer
0.435
315733AD1-074 GEN2
Solar/Wind Harmer
0.435
315735AD1-075 GEN1
Solar/Wind Harmer
0.218
965291AG1-394 GEN
Solar/Wind Harmer
0.336
3146206CASHIE
Solar/Wind Harmer
0.075
970601AG2-382 GEN
Solar/Wind Harmer
2.811
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
970085AG2-068 GEN
Solar/Wind Harmer
4
970581AG2-369 GEN
Solar/Wind Harmer
3.44
3145513AHOSKIE
Solar/Wind Harmer
0.156
3145513AHOSKIE
Solar/Wind Harmer
0.074
3146043SEABORD
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.149
3145683EARLEYS
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.074
315607AA1-063A GEN
Solar/Wind Harmer
0.152
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.294
315652AC1-086 GEN
Solar/Wind Harmer
8.087
972205AH1-687 GEN
Adder
3.134
970285AG2-188 GEN
Solar/Wind Harmer
5.802
971845AH1-439 GEN
Solar/Wind Harmer
3.325
3145796HORNRTN
Solar/Wind Harmer
0.233
3145796HORNRTN
Solar/Wind Harmer
0.029
3146033SCOT NK
Solar/Wind Harmer
0.29
315657AE1-056 GEN
Solar/Wind Harmer
2.494
946301AF1-294 GEN
Solar/Wind Harmer
1.424
961791AG1-021 GEN
Solar/Wind Harmer
0.693
970683AG2-441 GEN
Solar/Wind Harmer
4.794
970681AG2-440 GEN
Solar/Wind Harmer
3.836
970831AG2-522 GEN
Solar/Wind Harmer
3.066
972193AH1-681 GEN
Adder
1.643
3144303KENBRDG
Solar/Wind Harmer
0.057
971443AH1-215 GEN
Solar/Wind Harmer
1.204
971447AH1-217 GEN
Solar/Wind Harmer
2.163
316005AA1-067
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.282
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
970181AG2-120 GEN
Solar/Wind Harmer
0.883
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3138266HYDRAULIC
Solar/Wind Harmer
0.003
3138266HYDRAULIC
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
3.032
316420AA1-050 GEN
Solar/Wind Harmer
0.002
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.07
3145573BETHELC
Solar/Wind Harmer
0.07
316118AC1-105 GEN
Solar/Wind Harmer
0.176
3147173SINAI
Solar/Wind Harmer
0.067
3147243WELCO
Solar/Wind Harmer
0.042
270494AE1-108_GEN
Solar/Wind Harmer
0.802
3148133STUARTS
Solar/Wind Harmer
0.039
3148013FISHERV
Solar/Wind Harmer
0.037
970865AG2-541 GEN
Solar/Wind Harmer
2.214
316123AC1-075 GEN
Solar/Wind Harmer
0.084
970165AG2-112 GEN
Solar/Wind Harmer
0.5
970163AG2-111 GEN
Solar/Wind Harmer
0.477
3148463FAIRFLD
Solar/Wind Harmer
0.06
3151881LOWMORC
Adder
0.64
3151881LOWMORC
Adder
0.63
3151861LOWMORA
Adder
0.62
960921AF2-383 GEN
Solar/Wind Helper
0.279
205943AE1-185 GEN
Solar/Wind Helper
0.387
205956AE1-196_GEN
Solar/Wind Helper
0.385
205932AD2-116_GEN
Solar/Wind Helper
0.385
959381AF2-229 GEN
Solar/Wind Helper
0.257
237085AD2-009_GEN
Solar/Wind Helper
0.97
203975AE1-071-GEN
Solar/Wind Helper
1.713
233935AB2-179 C
Solar/Wind Helper
0.772
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.575
233990AG1-397 GEN
Solar/Wind Helper
0.162
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.208
964001AG1-254 GEN
Solar/Wind Helper
0.565
219914AD2-027 C
Solar/Wind Helper
0.068
227927V4-067C
Solar/Wind Helper
0.006
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
219607WPEMNERT C
Solar/Wind Helper
0.047
214067T20SOLAR
Solar/Wind Helper
0.007
20715728PEM_W1-119
Solar/Wind Helper
0.056
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
966261AG1-495 GEN
Solar/Wind Helper
0.047
20675928HOL_W4-097
Solar/Wind Helper
0.029
207530AG1-191 GEN
Solar/Wind Helper
0.038
207484AF2-139 C O1
Solar/Wind Helper
0.048
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
20675128HRM_W1-127
Solar/Wind Helper
0.017
209116AE2-175 GEN
Solar/Wind Helper
1.004
961261AF2-417 GEN
Solar/Wind Helper
0.241
959431AF2-234 GEN
Solar/Wind Helper
0.466
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
959421AF2-233 GEN
Solar/Wind Helper
0.233
238208AF1-136 C
Solar/Wind Helper
0.089
316017AA1-139 ULT1
Solar/Wind Harmer
0.045
3137176SLIGO L2192
Solar/Wind Harmer
0.319
3146456SLIGO L269
Solar/Wind Harmer
1.416
3130086AYDLETT
Solar/Wind Harmer
0.32
3146386ELIZ CT
Solar/Wind Harmer
0.08
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.079
3144356SAPONY
Solar/Wind Harmer
0.657
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.345
3146376EDENTON
Solar/Wind Harmer
0.345
972185AH1-677 GEN
Adder
4.331
972187AH1-678 GEN
Adder
2.184
970933AG2-581 GEN
Solar/Wind Harmer
6.107
316065AD1-022 GEN
Solar/Wind Harmer
3.475
3145893MURPHYS
Solar/Wind Harmer
0.503
3145893MURPHYS
Solar/Wind Harmer
0.135
3146173TUNIS
Solar/Wind Harmer
0.075
3146173TUNIS
Solar/Wind Harmer
0.075
970099AG2-077 GEN
Solar/Wind Harmer
7.908
316181AB2-040 GEN
Solar/Wind Harmer
0.107
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.044
971741AH1-377 GEN
Solar/Wind Harmer
7.304
970301AG2-198 GEN
Solar/Wind Harmer
3.138
316426AA2-053 GEN
Solar/Wind Harmer
0.248
3146776BUCKING
Solar/Wind Harmer
0.293
3145593CAROLNA
Solar/Wind Harmer
0.073
3145593CAROLNA
Solar/Wind Harmer
0.073
3146776BUCKING
Solar/Wind Harmer
0.024
966811AG1-552 GEN
Solar/Wind Harmer
0.795
3145593CAROLNA
Solar/Wind Harmer
0.091
3145783HORNRTN
Solar/Wind Harmer
1.299
3145783HORNRTN
Solar/Wind Harmer
1.039
3145783HORNRTN
Solar/Wind Harmer
0.325
3145783HORNRTN
Solar/Wind Harmer
0.13
3145796HORNRTN
Solar/Wind Harmer
0.219
3147133PAMPLIN
Solar/Wind Harmer
0.072
3147133PAMPLIN
Solar/Wind Harmer
0.058
958211AF2-115 GEN
Solar/Wind Harmer
0.866
963191AG1-168 GEN
Solar/Wind Harmer
0.289
3144293JTRSVLE
Adder
0.23
3144293JTRSVLE
Adder
0.193
3145933PARMELE
Solar/Wind Harmer
0.144
3145933PARMELE
Solar/Wind Harmer
0.072
316274AC1-208 GEN
Solar/Wind Harmer
0.372
316034AC1-036 C
Solar/Wind Harmer
0.005
970323AG2-213 GEN
Solar/Wind Harmer
3.057
971775AH1-396 GEN
Solar/Wind Harmer
0.115
971489AH1-241 GEN
Solar/Wind Harmer
3.817
313527AB2-043 GEN
Solar/Wind Harmer
0.001
939181AE1-148 GEN
Solar/Wind Harmer
3.402
3145493TOT1
Solar/Wind Harmer
0.162
3145453TOT5
Solar/Wind Harmer
0.097
3145603CNETO
Solar/Wind Harmer
0.065
315821AE2-092 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
3.322
961601AG1-000A GEN
Solar/Wind Harmer
1.228
316263AC1-034 GEN
Solar/Wind Harmer
2.624
964791AG1-342 GEN
Solar/Wind Harmer
1.322
3146843MT LREL
Solar/Wind Harmer
0.069
3146843MT LREL
Solar/Wind Harmer
0.069
316222AC1-221 GEN
Solar/Wind Harmer
0.264
971761AH1-387 GEN
Solar/Wind Harmer
1.238
942751AE2-291 GEN
Solar/Wind Harmer
3.276
3132123MT JACKSON
Solar/Wind Harmer
0.183
970117AG2-086 GEN
Solar/Wind Harmer
1.401
970117AG2-086 GEN
Solar/Wind Harmer
0.934
226929AD2-058 GEN
Solar/Wind Helper
0.143
237025AB1-124 C
Solar/Wind Helper
0.193
237006AB1-125 GEN
Solar/Wind Helper
0.145
23777801MSM_W1-116
Solar/Wind Helper
0.13
237034AC2-136 C
Solar/Wind Helper
0.205
205916AD1-020 GEN
Solar/Wind Helper
1.48
208835TUHI V3-051
Solar/Wind Helper
0.019
208835TUHI V3-051
Solar/Wind Helper
0.019
237001AB1-127_GEN
Solar/Wind Helper
0.307
237002AB1-128_GEN
Solar/Wind Helper
0.298
235063AE1-101 C2
Solar/Wind Helper
1.064
20390526W1-045 C
Solar/Wind Helper
0.252
23777901MDS_W4-102
Solar/Wind Helper
0.105
235020AA1-095 C
Solar/Wind Helper
0.029
233933AB2-153 GEN
Solar/Wind Helper
0.14
233944AB2-135 GEN
Solar/Wind Helper
0.355
232424Y1-079 C
Solar/Wind Helper
0.07
233987AB2-037 GEN
Solar/Wind Helper
1.406
233946AB2-136 GEN
Solar/Wind Helper
0.341
234036AF2-325 C
Solar/Wind Helper
0.025
233901CHERRYDALE C
Solar/Wind Helper
0.139
232408W1-005 C
Solar/Wind Helper
0.304
232410W1-006 C
Solar/Wind Helper
0.304
233939AC1-091 C
Solar/Wind Helper
0.209
233970AC1-092 C
Solar/Wind Helper
0.209
230433AD2-135 GEN
Solar/Wind Helper
0.01
219921AF1-264
Solar/Wind Helper
0.03
230407AD2-065 C
Solar/Wind Helper
0.024
219615MILLCREEK C
Solar/Wind Helper
0.016
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20714928UPF_X1-085
Solar/Wind Helper
0.003
20720628TIN_W1-124
Solar/Wind Helper
0.11
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.009
207442AE1-156 GEN
Solar/Wind Helper
0.188
20676128MHD_W3-029
Solar/Wind Helper
0.055
20671828STAW2-080
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
207471AF2-354 C
Solar/Wind Helper
0.097
20674928WA_W3-044
Solar/Wind Helper
0.056
964851AG1-348 GEN
Solar/Wind Helper
0.046
20674128FR_U2-059
Solar/Wind Helper
0.002
20676228FRD_X1-012
Solar/Wind Helper
0.052
966111AG1-480 GEN
Solar/Wind Helper
0.042
211065PSPA IPP
Solar/Wind Helper
0.085
211065PSPA IPP
Solar/Wind Helper
0.085
208972BECR K09
Solar/Wind Helper
0.178
961431AF2-434 GEN
Solar/Wind Helper
0.236
209029WAYMART-WD
Solar/Wind Helper
0.443
209054AE2-059 GEN
Solar/Wind Helper
0.042
946751AF1-339 GEN
Solar/Wind Helper
0.233
209137AF2-361 C
Solar/Wind Helper
0.708
3152111X4-039 GT1
50/50
1.838
315747AE2-019 GEN
50/50
13.176
3150021OMF B
50/50
0.216
3150101POSSM6S
50/50
1.296
3150081POSSM6A
50/50
0.848
3150151POSSMC1
50/50
1.143
3150151POSSMC1
50/50
1.143
3150231REMNGT3
50/50
14.281
3150241REMNGT4
50/50
13.316
972217AH1-693 GEN
50/50
1.756
963691AG1-221 GEN
Solar/Wind Harmer
2.312
971455AH1-223 GEN
Solar/Wind Harmer
2.312
3141196NOKESVL
Solar/Wind Harmer
0.429
972199AH1-684 GEN
Adder
1.903
3150301M RUN C
Adder
13.349
3150291M RUN B
Adder
13.25
3150331BIRCHWDA
Adder
16.626
3141316ARNOLDS
Adder
0.229
316044AC1-158 PL1
Solar/Wind Harmer
0.461
316450AC1-158 RIC
Solar/Wind Harmer
0.123
3150401LDYSMT4
Adder
12.678
3150371LDYSMT1
Adder
12.251
316170AC1-121 GEN2
Solar/Wind Harmer
0.1
970737AG2-469 GEN
Solar/Wind Harmer
3.872
3141906WESTMOR
Solar/Wind Harmer
0.036
3132273ORANGE
Solar/Wind Harmer
0.018
971781AH1-399 GEN
Solar/Wind Harmer
0.118
3147666LOUISA
Solar/Wind Harmer
0.204
3150351NORNECKC2
Adder
0.884
316404AE1-155 C
Solar/Wind Harmer
0.019
3151761LOISA E
Adder
11.415
972183AH1-676 GEN
Adder
92.045
970009AG2-005 GEN
Solar/Wind Harmer
0.643
316473AC1-191 GEN
Solar/Wind Harmer
0.29
962971AG1-146 GEN
Solar/Wind Harmer
1.373
3142416OLDCHRC
Solar/Wind Harmer
0.821
3141766HARMONY
Solar/Wind Harmer
1.129
316156AD2-030 GEN
Solar/Wind Harmer
0.063
3141873WAN 176
Solar/Wind Harmer
1.505
316280AD1-041 GEN
Solar/Wind Harmer
0.002
316203AE2-005 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
0.432
970293AG2-193 GEN
Solar/Wind Harmer
0.899
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3142946ENON
Solar/Wind Harmer
0.028
3150861SPRUNCD
Adder
0.385
316382AG1-145 C
Solar/Wind Harmer
0.001
970133AG2-095 GEN
Solar/Wind Harmer
0.794
970129AG2-093 GEN
Solar/Wind Harmer
4.984
3150921YORKTN3
Adder
2.069
315778AD1-151 GEN
Solar/Wind Harmer
6.579
965281AG1-393 GEN
Solar/Wind Harmer
0.877
3144216WINCHST
Adder
0.31
315839AE2-212 C
Solar/Wind Harmer
0.001
961611AG1-000B GEN
Solar/Wind Harmer
2.181
3151221GRAVEL6
Adder
5.934
3151171GRAVELC
Adder
1.142
3145336SMITFLD
Solar/Wind Harmer
0.033
315813AE1-149 C
Solar/Wind Harmer
4.334
315773AC2-141 GEN
Solar/Wind Harmer
2.962
970659AG2-427 GEN
Solar/Wind Harmer
0.856
316083AB2-161 GEN
Solar/Wind Harmer
0.001
3144536CHRHLND
Solar/Wind Harmer
0.012
3151101ELIZAR3
Adder
7.489
970661AG2-428 GEN
Solar/Wind Harmer
1.707
3144873MCLAUGH
Solar/Wind Harmer
0.002
944581AF1-123 GEN
Solar/Wind Harmer
18.149
944601AF1-125 GEN
Solar/Wind Harmer
17.869
3146456SLIGO L269
Solar/Wind Harmer
0.08
971153AH1-033 GEN
Solar/Wind Harmer
0.925
316320Y1-086
Solar/Wind Harmer
0
316313AB2-026
Solar/Wind Harmer
0.05
316258AE1-075 C
Solar/Wind Harmer
0.06
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
1.2
316435W1029_GEN3
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.079
3145273HOLLAND
Solar/Wind Harmer
0.059
3146376EDENTON
Solar/Wind Harmer
0.078
315614AA2-178 GEN
Solar/Wind Harmer
0.439
971157AH1-035 GEN
Solar/Wind Harmer
0.911
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
315737AD1-076 GEN
Solar/Wind Harmer
0.975
3146206CASHIE
Solar/Wind Harmer
0.075
316365GEN2_N
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
970917AG2-570 GEN
Solar/Wind Harmer
6.681
957521AF2-046 GEN
Solar/Wind Harmer
5.587
961681AG1-008 GEN
Solar/Wind Harmer
5.587
3146173TUNIS
Solar/Wind Harmer
0.075
3156021HOLLOMANSOL
Solar/Wind Harmer
0.339
316463AE2-346 GEN
Solar/Wind Harmer
0.064
316140AB2-099
Solar/Wind Harmer
0.027
962331AG1-082 GEN
Solar/Wind Harmer
0.795
3146263WOODLND
Solar/Wind Harmer
0.074
313506AB2-031 GEN
Solar/Wind Harmer
0.228
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3145963POPLR C
Solar/Wind Harmer
0.074
970909AG2-566 GEN
Solar/Wind Harmer
0.785
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.073
3147043LAWRENC
Solar/Wind Harmer
0.044
3146776BUCKING
Solar/Wind Harmer
0.026
3146926FARMVIL
Solar/Wind Harmer
0.044
3145796HORNRTN
Solar/Wind Harmer
0.291
3145796HORNRTN
Solar/Wind Harmer
0.073
942461AE2-259 GEN
Solar/Wind Harmer
0
316478AD1-087 GEN
Solar/Wind Harmer
0.254
316486AD2-202 GEN
Solar/Wind Harmer
0.075
3147133PAMPLIN
Solar/Wind Harmer
0.227
971193AH1-056 GEN
Solar/Wind Harmer
4.404
963181AG1-167 GEN
Solar/Wind Harmer
0.289
3144293JTRSVLE
Adder
0.23
316210AC1-098 GEN
Solar/Wind Harmer
0.668
972255AH1-712 GEN
Adder
36.775
3145933PARMELE
Solar/Wind Harmer
0.072
966801AG1-551 GEN
Solar/Wind Harmer
0.836
959311AF2-222 GEN
Solar/Wind Harmer
6.376
970257AG2-171 GEN
Solar/Wind Harmer
2.293
970221AG2-151 GEN
Solar/Wind Harmer
3.817
315785AD2-033 C
Solar/Wind Harmer
0.582
964241AG1-285 GEN
Solar/Wind Harmer
4.753
316131AB2-060 GEN
Solar/Wind Harmer
0.224
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
315724AD1-057 GEN
Solar/Wind Harmer
0.266
316327AA2-057 GEN
Solar/Wind Harmer
0.106
3146233WITAKRS
Solar/Wind Harmer
0.35
3146233WITAKRS
Solar/Wind Harmer
0.047
3146073TAR RVR
Solar/Wind Harmer
0.07
3146083TARBORO
Solar/Wind Harmer
0.07
3138543CONSLDL
Solar/Wind Harmer
0.046
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.069
961601AG1-000A GEN
Solar/Wind Harmer
4.912
971623AH1-311 GEN
Solar/Wind Harmer
0.138
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.87
971683AH1-343 GEN
Solar/Wind Harmer
2.391
3148013FISHERV
Solar/Wind Harmer
0.065
316283AC2-100 C
Solar/Wind Harmer
0.124
315616AA1-038_C
Solar/Wind Harmer
0
3151861LOWMORA
Adder
0.645
958131AF2-107 GEN
Solar/Wind Harmer
1.618
226910AB2-157 C
Solar/Wind Helper
0.02
227287AC2-120 GEN
Solar/Wind Helper
0.49
237030AB1-096 C
Solar/Wind Helper
0.083
223402AF1-300 C
Solar/Wind Helper
0.397
205917AD1-020 ES
Solar/Wind Helper
0.318
238221AF1-254 C O1
Solar/Wind Helper
0.179
235067AD1-061 GEN
Solar/Wind Helper
0.312
233982AB2-133 GEN
Solar/Wind Helper
0.216
233918AB1-142 GEN
Solar/Wind Helper
0.303
233994AC2-023 GEN
Solar/Wind Helper
0.577
233996TM1833_GEN
Solar/Wind Helper
0.157
233997TMININ_4.2
Solar/Wind Helper
0.157
233940AF2-379 C
Solar/Wind Helper
0.037
234015AF2-250 C
Solar/Wind Helper
0.023
233952AC2-187 GEN
Solar/Wind Helper
0.139
232406W1-004 FULL
Solar/Wind Helper
0.304
233971AC1-093 C
Solar/Wind Helper
0.214
230430AE1-229_GEN
Solar/Wind Helper
1.995
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.089
228729W2-030 C
Solar/Wind Helper
0.065
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20716028EGP_W2-019
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.037
20715028HAN_X4-015
Solar/Wind Helper
0.033
219276PARKLANDSO C
Solar/Wind Helper
0.052
20714528FRN_Y2-051
Solar/Wind Helper
0.033
20720528MAN_W1-024
Solar/Wind Helper
0.016
219612MATRIX C
Solar/Wind Helper
0.014
218438BLK ROCK C
Solar/Wind Helper
0.016
20673728F2S_V4-070
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
219919AE1-041 FULL
Solar/Wind Helper
0.002
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
207510AF2-138 C
Solar/Wind Helper
0.046
20674628WNG_W3-110
Solar/Wind Helper
0.051
963161AG1-165 GEN
Solar/Wind Helper
0.242
963071AG1-156 GEN
Solar/Wind Helper
0.783
209027LOR2_Q27
Solar/Wind Helper
0.557
961331AF2-424 GEN
Solar/Wind Helper
0.237
961421AF2-433 GEN
Solar/Wind Helper
0.236
957921AF2-086 GEN
Solar/Wind Helper
0.234
946691AF1-333 GEN
Solar/Wind Helper
0.233
946741AF1-338 GEN
Solar/Wind Helper
0.233
209067AE2-060 GEN
Solar/Wind Helper
0.042
316337AD2-073 GEN
Solar/Wind Harmer
0.077
3150351NORNECKC2
Adder
0.87
3141726DUNNSVL
Solar/Wind Harmer
0.348
962861AG1-135 GEN
Solar/Wind Harmer
2.764
3151751LOISA D
Adder
5.599
3138133OCRAN
Solar/Wind Harmer
0.051
3142416OLDCHRC
Solar/Wind Harmer
0.22
3142416OLDCHRC
Solar/Wind Harmer
0.084
3141766HARMONY
Solar/Wind Harmer
0.017
971777AH1-397 GEN
Solar/Wind Harmer
0.223
3141843SHACKLE
Adder
0.432
3142433PROV 92
Solar/Wind Harmer
0.337
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143526WINTERP
Solar/Wind Harmer
0.435
3142543TWELFTH
Solar/Wind Harmer
0.008
3150851SPRUNCC
Adder
0.385
944631AF1-128 GEN
Adder
39.853
3143226MDLTHAN
Solar/Wind Harmer
0.083
316159AE1-175 C
Solar/Wind Harmer
0.072
971317AH1-138 GEN
Solar/Wind Harmer
0.618
970129AG2-093 GEN
Solar/Wind Harmer
2.345
316458AB2-190 GEN2
Solar/Wind Harmer
0.442
315671AE2-027_GEN
Solar/Wind Harmer
5.273
3138126ROCKLANDING
Solar/Wind Harmer
0.038
971069AG2-661 GEN
Solar/Wind Harmer
1.462
971647AH1-324 GEN
Solar/Wind Harmer
3.497
961611AG1-000B GEN
Solar/Wind Harmer
4.29
3151171GRAVELC
Adder
0.868
3145336SMITFLD
Solar/Wind Harmer
0.325
316294AC1-161 GEN
Solar/Wind Harmer
1.405
970659AG2-427 GEN
Solar/Wind Harmer
3.913
316381AD1-082 GEN
Solar/Wind Harmer
0.084
316375AC2-012 GEN
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
8.025
3150981CHESPKA
Adder
1.007
944591AF1-124 GEN
Solar/Wind Harmer
18.213
316072AD1-144
Solar/Wind Harmer
0.029
316388AE2-253 GEN
Solar/Wind Harmer
0.251
3146456SLIGO L269
Solar/Wind Harmer
0.08
939411AE1-173 GEN
Solar/Wind Harmer
34.166
316246AF1-032 C
Solar/Wind Harmer
0.036
940641AE2-051 GEN
Solar/Wind Harmer
6.396
316093AE2-104_GEN
Solar/Wind Harmer
1.342
3143336POWHATN
Solar/Wind Harmer
1.412
3146516WINFALL
Solar/Wind Harmer
0.256
3146516WINFALL
Solar/Wind Harmer
0.079
316336AC2-165 C
Solar/Wind Harmer
0.003
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.078
3145663CRESWEL
Solar/Wind Harmer
0.215
971163AH1-040 GEN
Solar/Wind Harmer
6.133
970937AG2-583 GEN
Solar/Wind Harmer
4.64
3146206CASHIE
Solar/Wind Harmer
0.075
971547AH1-271 GEN
Solar/Wind Harmer
1.606
316023GEN1_S
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
0.301
3145893MURPHYS
Solar/Wind Harmer
0.334
970919AG2-571 GEN
Solar/Wind Harmer
2.672
970087AG2-069 GEN
Solar/Wind Harmer
5.999
3146173TUNIS
Solar/Wind Harmer
0.075
960081AF2-299 GEN
Solar/Wind Harmer
0.714
3145683EARLEYS
Solar/Wind Harmer
0.074
957481AF2-042 GEN
Solar/Wind Harmer
19.771
3146263WOODLND
Solar/Wind Harmer
0.074
315693AD1-088 GEN
Solar/Wind Harmer
3.545
962491AG1-098 GEN
Solar/Wind Harmer
4.214
971795AH1-408 GEN
Solar/Wind Harmer
4.913
3145963POPLR C
Solar/Wind Harmer
0.074
316011AB1-132 GEN
Solar/Wind Harmer
1.337
962571AG1-106 GEN
Solar/Wind Harmer
1.046
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.073
3147043LAWRENC
Adder
0.664
972003AH1-546 GEN
Solar/Wind Harmer
3.117
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.029
3146926FARMVIL
Solar/Wind Harmer
0.044
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145783HORNRTN
Solar/Wind Harmer
0.073
3145796HORNRTN
Solar/Wind Harmer
0.24
3145796HORNRTN
Solar/Wind Harmer
0.073
963171AG1-166 GEN
Solar/Wind Harmer
0.385
971563AH1-280 GEN
Solar/Wind Harmer
0.77
3144293JTRSVLE
Adder
0.23
316212AC1-099_GEN
Solar/Wind Harmer
0.372
970685AG2-442 GEN
Solar/Wind Harmer
5.37
972277AH1-723 GEN
Adder
42.854
3146293MARTNCO
Solar/Wind Harmer
0.067
316129AC1-054 GEN
Solar/Wind Harmer
0.27
971377AH1-170 GEN
Solar/Wind Harmer
0.763
3147623JAMES R
Solar/Wind Harmer
0.166
971065AG2-659 GEN
Solar/Wind Harmer
3.053
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315722AD1-056 GEN
Solar/Wind Harmer
0.448
315687AD1-152 GEN
Solar/Wind Harmer
0.002
316494AC1-189 GEN
Solar/Wind Harmer
0.238
3146233WITAKRS
Solar/Wind Harmer
0.278
961671AG1-007 GEN
Solar/Wind Harmer
0.011
3146083TARBORO
Solar/Wind Harmer
0.07
3145493TOT1
Solar/Wind Harmer
0.31
316359AB2-059 GEN
Solar/Wind Harmer
0.248
316049AB1-081 GEN
Solar/Wind Harmer
0.395
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.055
3142053HEARTS
Solar/Wind Harmer
0.122
970401AG2-262 GEN
Solar/Wind Harmer
0.404
316003AC1-222 GEN
Solar/Wind Harmer
0.002
315705AF1-075 GEN
Solar/Wind Harmer
2.472
3147983MERCK5
Solar/Wind Harmer
0.024
23779801AA1-109
Solar/Wind Helper
0.218
223401AF1-299 GEN
Solar/Wind Helper
0.397
966131AG1-482 GEN
Solar/Wind Helper
0.111
237080AD1-060 GEN
Solar/Wind Helper
0.221
235062AE1-101 C1
Solar/Wind Helper
1.064
237038AE2-054 C
Solar/Wind Helper
0.173
233930AB2-032 GEN
Solar/Wind Helper
0.23
233915AB1-141 GEN
Solar/Wind Helper
0.303
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
233998TM1NIN_3.36
Solar/Wind Helper
0.157
232428Y3-058 C
Solar/Wind Helper
0.203
233954AC2-188 GEN
Solar/Wind Helper
0.139
232404W1-003 C
Solar/Wind Helper
0.304
233950AC2-186 GEN
Solar/Wind Helper
0.07
232434Z2-077 GEN
Solar/Wind Helper
0.076
233972AC1-094 C
Solar/Wind Helper
0.181
205941AD2-115 GEN
Solar/Wind Helper
0.302
230434AG1-499 GEN
Solar/Wind Helper
0.136
230511AF1-262
Solar/Wind Helper
0.009
219258KINSLEYDEP C
Solar/Wind Helper
0.045
228728W1-130C
Solar/Wind Helper
0.032
219904AC1-010 C
Solar/Wind Helper
0.036
219907AC1-030 C
Solar/Wind Helper
0.02
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
20720728JCB_W1-129
Solar/Wind Helper
0.033
207445AB1-138_GEN
Solar/Wind Helper
0.061
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
207454AA2-184 E
Solar/Wind Helper
0.18
20715228NPK_W1-113
Solar/Wind Helper
0.045
20742028HF_AC1-207
Solar/Wind Helper
0.082
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
20675428EAM_W2-061
Solar/Wind Helper
0.009
218428ETC SOLAR C
Solar/Wind Helper
0.003
20676428JCR_X2-075
Solar/Wind Helper
0.039
217213AMBOY SO C
Solar/Wind Helper
0.017
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.013
207437AD2-070 GEN
Solar/Wind Helper
0.079
207439AE1-081 C O1
Solar/Wind Helper
0.011
207518AF1-320_GEN
Solar/Wind Helper
0.9
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
212266LOR1
Solar/Wind Helper
0.026
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.829
946731AF1-337 GEN
Solar/Wind Helper
0.233
209071AE2-133 GEN
Solar/Wind Helper
0.042
LAGNLTFEXP_LAGN->PJM
CLTF
6.324
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.565
TVALTFEXP_TVA->PJM
CLTF
3.188
NYPJM->LTFIMP_NY
CLTF
2.575
LGEELTFEXP_LGEE->PJM
CLTF
1.805
WECLTFEXP_WEC->PJM
CLTF
0.962
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.485
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.592
MECLTFEXP_MEC->PJM
CLTF
4.449
SIGELTFEXP_SIGE->PJM
CLTF
0.14
CPLELTFEXP_CPLE->PJM
CLTF
5.065
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.965

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o AP_P1-2_PE-500-406T_SRT-A


Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-406T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.83 %
Rating:1331.98 MVA
Rating Type:B
MVA to Mitigate:1462.93
MW Contribution:2.04
Bus #Bus NameTypeMW Contribution
970053AG2-049 GEN
50/50
1.525
3138216PACIFIC
Solar/Wind Harmer
0.024
316411AF1-147_GEN1
Solar/Wind Harmer
0.003
316415AF1-147_GEN2
Solar/Wind Harmer
0.003
316164AC1-076 GEN
Solar/Wind Harmer
0.104
3141426STAFORD
Solar/Wind Harmer
0.015
3147346CASHSCORNER
Solar/Wind Harmer
0.156
3150411LDYSMT5
Adder
8.881
3150381LDYSMT2
Adder
8.499
972213AH1-691 GEN
Adder
1.438
972215AH1-692 GEN
Adder
1.438
944491AF1-114 GEN
Solar/Wind Harmer
0
316223AC1-118
Solar/Wind Harmer
0.046
972189AH1-679 GEN
Adder
1.058
3141813NORNECK
Solar/Wind Harmer
0.063
970327AG2-215 GEN
Solar/Wind Harmer
2.041
962981AG1-147 GEN
Solar/Wind Harmer
2.318
316312AB1-027
Solar/Wind Harmer
0.111
316233AE1-074 FULL
Solar/Wind Harmer
0.05
3141783LANCAST
Solar/Wind Harmer
0.037
3141783LANCAST
Solar/Wind Harmer
0.025
971281AH1-106 GEN
Solar/Wind Harmer
0.859
971283AH1-107 GEN
Solar/Wind Harmer
0.859
3138133OCRAN
Solar/Wind Harmer
0.019
3141913WHIT STONE
Solar/Wind Harmer
0.062
316314AB2-024 C
Solar/Wind Harmer
0
316059AD1-063 C
Solar/Wind Harmer
0
315662AE1-191 GEN
Solar/Wind Harmer
0.002
315666AE1-190 GEN
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.037
3141873WAN 176
Solar/Wind Harmer
0.012
970189AG2-124 GEN
Solar/Wind Harmer
1.827
971285AH1-108 GEN
Adder
0.465
3142433PROV 92
Adder
0.12
3142433PROV 92
Adder
0.12
315976AC1-164 GENA
Solar/Wind Harmer
6.381
971167AH1-042 GEN
Solar/Wind Harmer
5.466
316169AC1-164_GENC
Solar/Wind Harmer
5.512
315975AC1-164 GENB
Solar/Wind Harmer
0.189
3138283WHITEMARSH
Solar/Wind Harmer
0.014
316132AB2-190 GEN1
Solar/Wind Harmer
0.326
316369SG1_INVT
Solar/Wind Harmer
0.002
972265AH1-717 GEN
Adder
4.684
3151201GRAVEL4
Adder
4.391
3151191GRAVEL3
Adder
4.336
3151211GRAVEL5
Adder
4.336
3143316POE
Solar/Wind Harmer
0.238
971445AH1-216 GEN
Solar/Wind Harmer
4.236
3151081ELIZAR1
Adder
5.485
3151091ELIZAR2
Adder
5.39
3152611GOSPORTB
Adder
0.762
3152621GOSPORTC
Adder
0.647
3152601GOSPORTA
Adder
0.597
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.041
316311AC2-079 GEN
Solar/Wind Harmer
1.71
957871AF2-081 GEN
Solar/Wind Harmer
2.964
319010AE1-072 C
Solar/Wind Harmer
0.299
316305AF2-043 C
Solar/Wind Harmer
0
3146406KITTY HAWK
Solar/Wind Harmer
0.007
315835AF2-110_GEN
Solar/Wind Harmer
0.407
313526AB2-022
Solar/Wind Harmer
0.032
3146486SUNBURY
Solar/Wind Harmer
0.059
3146486SUNBURY
Solar/Wind Harmer
0.059
316321Z2-027
Solar/Wind Harmer
0.011
3146396TANGLEW
Solar/Wind Harmer
0.163
3145176PASQUOTANK
Solar/Wind Harmer
0.037
316315AB2-025 C
Solar/Wind Harmer
0.047
941031AE2-094 GEN
Solar/Wind Harmer
10.802
944011AF1-069 GEN
Solar/Wind Harmer
3.529
315814AE2-033 C
Solar/Wind Harmer
4.636
315611Z1-036_GEN2
Solar/Wind Harmer
0
970673AG2-436 GEN
Solar/Wind Harmer
12.417
970673AG2-436 GEN
Solar/Wind Harmer
8.278
3130156CHOWAN
Solar/Wind Harmer
0.058
3130156CHOWAN
Solar/Wind Harmer
0.058
971967AH1-528 GEN
Solar/Wind Harmer
9.279
315816AE2-034 GEN
Solar/Wind Harmer
0.246
972205AH1-687 GEN
Adder
2.436
3130546PLYMOUTH
Solar/Wind Harmer
0.057
315732AD1-074 GEN1
Solar/Wind Harmer
0.327
315733AD1-074 GEN2
Solar/Wind Harmer
0.327
315735AD1-075 GEN1
Solar/Wind Harmer
0.164
965291AG1-394 GEN
Solar/Wind Harmer
0.253
971845AH1-439 GEN
Solar/Wind Harmer
2.569
970285AG2-188 GEN
Solar/Wind Harmer
4.479
970085AG2-068 GEN
Solar/Wind Harmer
3.019
970581AG2-369 GEN
Solar/Wind Harmer
2.597
3146206CASHIE
Solar/Wind Harmer
0.057
970601AG2-382 GEN
Solar/Wind Harmer
2.113
3145893MURPHYS
Solar/Wind Harmer
0.153
3145893MURPHYS
Solar/Wind Harmer
0.057
3138266HYDRAULIC
Solar/Wind Harmer
0.003
3138266HYDRAULIC
Solar/Wind Harmer
0.002
960921AF2-383 GEN
Solar/Wind Helper
0.255
205943AE1-185 GEN
Solar/Wind Helper
0.354
205956AE1-196_GEN
Solar/Wind Helper
0.352
205932AD2-116_GEN
Solar/Wind Helper
0.352
959381AF2-229 GEN
Solar/Wind Helper
0.226
203975AE1-071-GEN
Solar/Wind Helper
1.507
237085AD2-009_GEN
Solar/Wind Helper
0.799
233935AB2-179 C
Solar/Wind Helper
0.72
232436AB1-176 C
Solar/Wind Helper
0.025
233923SMA
Solar/Wind Helper
0.537
233990AG1-397 GEN
Solar/Wind Helper
0.151
232432Z2-076 GEN
Solar/Wind Helper
0.038
234033AF1-007_GEN
Solar/Wind Helper
3.932
964001AG1-254 GEN
Solar/Wind Helper
0.525
219914AD2-027 C
Solar/Wind Helper
0.063
227927V4-067C
Solar/Wind Helper
0.006
228754AB1-001 C
Solar/Wind Helper
0.014
219272CLEANLIGHT C
Solar/Wind Helper
0.014
219688LUMSOLAR_S C
Solar/Wind Helper
0.022
219607WPEMNERT C
Solar/Wind Helper
0.044
214067T20SOLAR
Solar/Wind Helper
0.006
20715728PEM_W1-119
Solar/Wind Helper
0.052
20715828PEM_W1-120
Solar/Wind Helper
0.052
207459AE1-142 C O1
Solar/Wind Helper
0.157
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.046
218526CNTRALGAS2 C
Solar/Wind Helper
0.086
218524CNTRALGAS1 C
Solar/Wind Helper
0.086
966261AG1-495 GEN
Solar/Wind Helper
0.043
207530AG1-191 GEN
Solar/Wind Helper
0.035
20675928HOL_W4-097
Solar/Wind Helper
0.026
20676328BVR_Y1-020
Solar/Wind Helper
0.014
207484AF2-139 C O1
Solar/Wind Helper
0.044
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.044
20675728RH_W2-091
Solar/Wind Helper
0.072
20675128HRM_W1-127
Solar/Wind Helper
0.016
209116AE2-175 GEN
Solar/Wind Helper
0.921
961261AF2-417 GEN
Solar/Wind Helper
0.221
972289AH1-729 GEN
50/50
12.961
315651AD1-115 GEN
Solar/Wind Harmer
0.002
316447AC1-158 HLD
Solar/Wind Harmer
0.794
3150071POSSM 5
Adder
31.816
3150181POSSMC2
Adder
0.702
3150181POSSMC2
Adder
0.696
3150181POSSMC2
Adder
0.696
966001AG1-469 GEN
Solar/Wind Harmer
0.04
3151731LOISA B
Adder
4.435
3151721LOISA A
Adder
4.412
3150391LDYSMT3
Adder
8.836
972195AH1-682 GEN
Adder
1.161
315673AE1-157 GEN
Solar/Wind Harmer
4.506
957411AF2-035 GEN
Solar/Wind Harmer
2.759
970317AG2-208 GEN
Solar/Wind Harmer
2.556
316468AD1-105 GEN
Solar/Wind Harmer
-0.021
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.656
3150341NORNECKC1
Adder
0.651
966871AG1-558 GEN
Solar/Wind Harmer
0.072
958261AF2-120 GEN
Solar/Wind Harmer
2.062
3142296MT RD221
Adder
0.198
971223AH1-071 GEN
Solar/Wind Harmer
0.661
3143526WINTERP
Solar/Wind Harmer
0.322
3142366NRTHEST
Adder
0.202
3150691DARBY 3
Adder
4.444
3150701DARBY 4
Adder
4.434
3150681DARBY 2
Adder
4.428
3150671DARBY 1
Adder
4.423
316075AC2-137 C
Solar/Wind Harmer
0.017
3142946ENON
Solar/Wind Harmer
0.006
944641AF1-129 GEN
Adder
29.055
316240AF1-291 C
Solar/Wind Harmer
0
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.068
316236AE1-162_GEN
Solar/Wind Harmer
0
970657AG2-426 GEN
Solar/Wind Harmer
2.098
970657AG2-426 GEN
Solar/Wind Harmer
0.44
316036AC1-147 C
Solar/Wind Harmer
0.011
3150991CHESPKB
Adder
0.627
3150991CHESPKB
Adder
0.612
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.057
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3145506HICKORY
Solar/Wind Harmer
0.239
3145506HICKORY
Solar/Wind Harmer
0.143
3145506HICKORY
Solar/Wind Harmer
0.036
316339AD2-160 GEN
Solar/Wind Harmer
0.097
316018AA1-139 ULT2
Solar/Wind Harmer
0.001
316017AA1-139 ULT1
Solar/Wind Harmer
0.033
3137176SLIGO L2192
Solar/Wind Harmer
0.237
3146456SLIGO L269
Solar/Wind Harmer
1.052
3130086AYDLETT
Solar/Wind Harmer
0.238
3146386ELIZ CT
Solar/Wind Harmer
0.059
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.059
3146516WINFALL
Solar/Wind Harmer
0.059
3146516WINFALL
Solar/Wind Harmer
0.059
3144356SAPONY
Solar/Wind Harmer
0.491
3146626S HERTFORD
Solar/Wind Harmer
0.059
3146626S HERTFORD
Solar/Wind Harmer
0.059
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.258
3146376EDENTON
Solar/Wind Harmer
0.258
972185AH1-677 GEN
Adder
3.254
971761AH1-387 GEN
Solar/Wind Harmer
1.133
972187AH1-678 GEN
Adder
1.643
970933AG2-581 GEN
Solar/Wind Harmer
4.601
316065AD1-022 GEN
Solar/Wind Harmer
2.61
3146776BUCKING
Solar/Wind Harmer
0.227
3146776BUCKING
Solar/Wind Harmer
0.018
3145893MURPHYS
Solar/Wind Harmer
0.379
3145893MURPHYS
Solar/Wind Harmer
0.102
3146173TUNIS
Solar/Wind Harmer
0.056
3146173TUNIS
Solar/Wind Harmer
0.056
970301AG2-198 GEN
Solar/Wind Harmer
2.401
237025AB1-124 C
Solar/Wind Helper
0.177
237006AB1-125 GEN
Solar/Wind Helper
0.132
23777801MSM_W1-116
Solar/Wind Helper
0.118
237034AC2-136 C
Solar/Wind Helper
0.179
205916AD1-020 GEN
Solar/Wind Helper
1.359
226929AD2-058 GEN
Solar/Wind Helper
0.07
208835TUHI V3-051
Solar/Wind Helper
0.018
208835TUHI V3-051
Solar/Wind Helper
0.018
237001AB1-127_GEN
Solar/Wind Helper
0.259
237002AB1-128_GEN
Solar/Wind Helper
0.251
20390526W1-045 C
Solar/Wind Helper
0.222
235063AE1-101 C2
Solar/Wind Helper
0.889
23777901MDS_W4-102
Solar/Wind Helper
0.085
233933AB2-153 GEN
Solar/Wind Helper
0.131
233944AB2-135 GEN
Solar/Wind Helper
0.332
232424Y1-079 C
Solar/Wind Helper
0.065
233987AB2-037 GEN
Solar/Wind Helper
1.314
234036AF2-325 C
Solar/Wind Helper
0.024
233946AB2-136 GEN
Solar/Wind Helper
0.319
233901CHERRYDALE C
Solar/Wind Helper
0.13
232408W1-005 C
Solar/Wind Helper
0.284
232410W1-006 C
Solar/Wind Helper
0.284
233939AC1-091 C
Solar/Wind Helper
0.196
233970AC1-092 C
Solar/Wind Helper
0.196
230433AD2-135 GEN
Solar/Wind Helper
0.009
230407AD2-065 C
Solar/Wind Helper
0.022
219921AF1-264
Solar/Wind Helper
0.028
219615MILLCREEK C
Solar/Wind Helper
0.014
963401AG1-189 GEN
Solar/Wind Helper
0.03
963391AG1-188 GEN
Solar/Wind Helper
0.044
20714928UPF_X1-085
Solar/Wind Helper
0.003
20720628TIN_W1-124
Solar/Wind Helper
0.102
235020AA1-095 C
Solar/Wind Helper
0.023
20716928W4-060COL
Solar/Wind Helper
0.028
20673828FLE_V3-070
Solar/Wind Helper
0.048
218440SUMMTASSOC C
Solar/Wind Helper
0.009
207442AE1-156 GEN
Solar/Wind Helper
0.174
20676128MHD_W3-029
Solar/Wind Helper
0.051
20671828STAW2-080
Solar/Wind Helper
0.014
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.003
217204WCALDSOLAR C
Solar/Wind Helper
0.002
207471AF2-354 C
Solar/Wind Helper
0.089
20674928WA_W3-044
Solar/Wind Helper
0.052
964851AG1-348 GEN
Solar/Wind Helper
0.043
20676228FRD_X1-012
Solar/Wind Helper
0.048
20674128FR_U2-059
Solar/Wind Helper
0.002
966111AG1-480 GEN
Solar/Wind Helper
0.039
211065PSPA IPP
Solar/Wind Helper
0.078
211065PSPA IPP
Solar/Wind Helper
0.078
3152111X4-039 GT1
50/50
1.827
315747AE2-019 GEN
50/50
12.182
972285AH1-727 GEN
50/50
35.211
3150231REMNGT3
50/50
11.996
3150241REMNGT4
50/50
11.185
972217AH1-693 GEN
50/50
1.475
963691AG1-221 GEN
Solar/Wind Harmer
2.201
971455AH1-223 GEN
Solar/Wind Harmer
2.201
3141196NOKESVL
Solar/Wind Harmer
0.372
972199AH1-684 GEN
Adder
1.598
3150301M RUN C
Adder
11.196
3150291M RUN B
Adder
11.113
316170AC1-121 GEN2
Solar/Wind Harmer
0.08
316044AC1-158 PL1
Solar/Wind Harmer
0.361
316450AC1-158 RIC
Solar/Wind Harmer
0.096
3132273ORANGE
Solar/Wind Harmer
0.014
3150151POSSMC1
Adder
0.696
3150151POSSMC1
Adder
0.696
3147666LOUISA
Solar/Wind Harmer
0.158
3151761LOISA E
Adder
9.041
972183AH1-676 GEN
Adder
72.988
3150331BIRCHWDA
Adder
11.297
3141316ARNOLDS
Adder
0.157
3150401LDYSMT4
Adder
8.853
3150371LDYSMT1
Adder
8.554
970737AG2-469 GEN
Solar/Wind Harmer
2.728
971781AH1-399 GEN
Solar/Wind Harmer
0.084
3141906WESTMOR
Solar/Wind Harmer
0.025
3150351NORNECKC2
Adder
0.635
316473AC1-191 GEN
Solar/Wind Harmer
0.211
316404AE1-155 C
Solar/Wind Harmer
0.014
970009AG2-005 GEN
Solar/Wind Harmer
0.464
962971AG1-146 GEN
Solar/Wind Harmer
0.993
3142416OLDCHRC
Solar/Wind Harmer
0.6
970293AG2-193 GEN
Solar/Wind Harmer
0.658
3141766HARMONY
Solar/Wind Harmer
0.822
316203AE2-005 GEN
Solar/Wind Harmer
0
316280AD1-041 GEN
Solar/Wind Harmer
0.001
316156AD2-030 GEN
Solar/Wind Harmer
0.046
3141873WAN 176
Solar/Wind Harmer
1.096
3141843SHACKLE
Adder
0.315
3150861SPRUNCD
Adder
0.284
3143096IRON208
Adder
0.258
3143096IRON208
Adder
0.253
3142433PROV 92
Adder
0.12
3142433PROV 92
Adder
0.12
3142946ENON
Solar/Wind Harmer
0.021
316382AG1-145 C
Solar/Wind Harmer
0
970133AG2-095 GEN
Solar/Wind Harmer
0.585
970129AG2-093 GEN
Solar/Wind Harmer
3.674
965281AG1-393 GEN
Solar/Wind Harmer
0.648
315778AD1-151 GEN
Solar/Wind Harmer
4.854
3150921YORKTN3
Adder
1.524
315839AE2-212 C
Solar/Wind Harmer
0
3144216WINCHST
Adder
0.228
961611AG1-000B GEN
Solar/Wind Harmer
1.611
3151221GRAVEL6
Adder
4.386
3151171GRAVELC
Adder
0.844
315813AE1-149 C
Solar/Wind Harmer
3.21
3145336SMITFLD
Solar/Wind Harmer
0.024
315773AC2-141 GEN
Solar/Wind Harmer
2.196
316313AB2-026
Solar/Wind Harmer
0.038
316258AE1-075 C
Solar/Wind Harmer
0.045
316405AF2-144 C
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
0.907
970659AG2-427 GEN
Solar/Wind Harmer
0.635
316083AB2-161 GEN
Solar/Wind Harmer
0.001
3144536CHRHLND
Solar/Wind Harmer
0.009
3151101ELIZAR3
Adder
5.556
3144873MCLAUGH
Solar/Wind Harmer
0.001
944581AF1-123 GEN
Solar/Wind Harmer
13.468
944601AF1-125 GEN
Solar/Wind Harmer
13.26
970661AG2-428 GEN
Solar/Wind Harmer
1.266
3146456SLIGO L269
Solar/Wind Harmer
0.059
971153AH1-033 GEN
Solar/Wind Harmer
0.687
316320Y1-086
Solar/Wind Harmer
0
316435W1029_GEN3
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.059
3146626S HERTFORD
Solar/Wind Harmer
0.059
3145273HOLLAND
Solar/Wind Harmer
0.044
3146376EDENTON
Solar/Wind Harmer
0.058
315614AA2-178 GEN
Solar/Wind Harmer
0.329
3156081AA2-088 GEN
Solar/Wind Harmer
0.001
971157AH1-035 GEN
Solar/Wind Harmer
0.683
315737AD1-076 GEN
Solar/Wind Harmer
0.732
970917AG2-570 GEN
Solar/Wind Harmer
5.042
3146776BUCKING
Solar/Wind Harmer
0.02
316365GEN2_N
Solar/Wind Harmer
0.127
3146206CASHIE
Solar/Wind Harmer
0.057
3145893MURPHYS
Solar/Wind Harmer
0.095
3145893MURPHYS
Solar/Wind Harmer
0.057
957521AF2-046 GEN
Solar/Wind Harmer
4.204
961681AG1-008 GEN
Solar/Wind Harmer
4.204
3146926FARMVIL
Solar/Wind Harmer
0.034
3146173TUNIS
Solar/Wind Harmer
0.056
970909AG2-566 GEN
Solar/Wind Harmer
0.6
237030AB1-096 C
Solar/Wind Helper
0.076
223402AF1-300 C
Solar/Wind Helper
0.351
226910AB2-157 C
Solar/Wind Helper
0.013
227287AC2-120 GEN
Solar/Wind Helper
0.279
205917AD1-020 ES
Solar/Wind Helper
0.292
238221AF1-254 C O1
Solar/Wind Helper
0.149
235067AD1-061 GEN
Solar/Wind Helper
0.259
233982AB2-133 GEN
Solar/Wind Helper
0.202
233918AB1-142 GEN
Solar/Wind Helper
0.283
233994AC2-023 GEN
Solar/Wind Helper
0.539
233996TM1833_GEN
Solar/Wind Helper
0.146
233997TMININ_4.2
Solar/Wind Helper
0.146
233940AF2-379 C
Solar/Wind Helper
0.035
234015AF2-250 C
Solar/Wind Helper
0.021
233952AC2-187 GEN
Solar/Wind Helper
0.13
232406W1-004 FULL
Solar/Wind Helper
0.284
233971AC1-093 C
Solar/Wind Helper
0.2
230430AE1-229_GEN
Solar/Wind Helper
1.854
230415AB2-049 C
Solar/Wind Helper
0.017
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.03
219912AD2-042 GEN
Solar/Wind Helper
0.082
228729W2-030 C
Solar/Wind Helper
0.061
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.006
219906AC1-017 C
Solar/Wind Helper
0.023
219348LDSOLAR C
Solar/Wind Helper
0.062
959561AF2-247 GEN
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.034
20716028EGP_W2-019
Solar/Wind Helper
0.01
20715028HAN_X4-015
Solar/Wind Helper
0.031
219276PARKLANDSO C
Solar/Wind Helper
0.048
20714528FRN_Y2-051
Solar/Wind Helper
0.031
20720528MAN_W1-024
Solar/Wind Helper
0.015
219612MATRIX C
Solar/Wind Helper
0.013
218438BLK ROCK C
Solar/Wind Helper
0.015
219908AB1-139 C
Solar/Wind Helper
0.039
219919AE1-041 FULL
Solar/Wind Helper
0.002
20673728F2S_V4-070
Solar/Wind Helper
0.016
219249CENTRALDIV C
Solar/Wind Helper
0.005
217211CAMDEN ST C
Solar/Wind Helper
0.002
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.016
207510AF2-138 C
Solar/Wind Helper
0.043
20674628WNG_W3-110
Solar/Wind Helper
0.047
963161AG1-165 GEN
Solar/Wind Helper
0.221
3152131X4-039 ST
50/50
2.874
3152121X4-039 GT2
50/50
1.821
970467AG2-304 GEN
50/50
12.983
3150221REMNGT2
50/50
11.111
972201AH1-685 GEN
50/50
1.917
3150211REMNGT1
Adder
10.402
3150281M RUN A
Adder
11.203
316006AB2-029 C
Solar/Wind Harmer
0
971685AH1-345 GEN
Solar/Wind Harmer
0.609
3140676OCCOQUN
Adder
0.198
316254AC1-120 GEN1
Solar/Wind Harmer
0.16
316045AC1-158 PL2
Solar/Wind Harmer
1.156
315683AE1-153 C
Solar/Wind Harmer
5.861
972223AH1-696 GEN
Adder
5.499
3150151POSSMC1
Adder
0.696
3147666LOUISA
Solar/Wind Harmer
0.275
316192AB2-158 GEN
Solar/Wind Harmer
0.388
3151751LOISA D
Adder
4.435
3141346CRANES
Adder
0.08
972197AH1-683 GEN
Adder
1.382
972219AH1-694 GEN
Adder
0.995
966881AG1-559 GEN
Solar/Wind Harmer
0.075
972135AH1-637 GEN
Solar/Wind Harmer
0.548
316337AD2-073 GEN
Solar/Wind Harmer
0.055
3150351NORNECKC2
Adder
0.624
3141726DUNNSVL
Solar/Wind Harmer
0.25
962861AG1-135 GEN
Solar/Wind Harmer
1.994
3143226MDLTHAN
Solar/Wind Harmer
0.062
3143526WINTERP
Solar/Wind Harmer
0.322
3142416OLDCHRC
Solar/Wind Harmer
0.161
3142416OLDCHRC
Solar/Wind Harmer
0.062
3138133OCRAN
Solar/Wind Harmer
0.037
3141766HARMONY
Solar/Wind Harmer
0.012
971777AH1-397 GEN
Solar/Wind Harmer
0.163
3141843SHACKLE
Adder
0.315
3150851SPRUNCC
Adder
0.284
3143096IRON208
Adder
0.258
3142433PROV 92
Solar/Wind Harmer
0.246
3142433PROV 92
Adder
0.12
3142433PROV 92
Adder
0.12
3142543TWELFTH
Solar/Wind Harmer
0.006
944631AF1-128 GEN
Adder
29.257
316159AE1-175 C
Solar/Wind Harmer
0.053
971317AH1-138 GEN
Solar/Wind Harmer
0.454
315671AE2-027_GEN
Solar/Wind Harmer
3.891
970129AG2-093 GEN
Solar/Wind Harmer
1.729
316458AB2-190 GEN2
Solar/Wind Harmer
0.326
971069AG2-661 GEN
Solar/Wind Harmer
1.079
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971647AH1-324 GEN
Solar/Wind Harmer
2.582
961611AG1-000B GEN
Solar/Wind Harmer
3.169
3151171GRAVELC
Adder
0.642
3145336SMITFLD
Solar/Wind Harmer
0.24
316294AC1-161 GEN
Solar/Wind Harmer
1.042
3143336POWHATN
Solar/Wind Harmer
1.067
970659AG2-427 GEN
Solar/Wind Harmer
2.901
316381AD1-082 GEN
Solar/Wind Harmer
0.062
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.747
944591AF1-124 GEN
Solar/Wind Harmer
13.516
970661AG2-428 GEN
Solar/Wind Harmer
5.952
316072AD1-144
Solar/Wind Harmer
0.022
939411AE1-173 GEN
Solar/Wind Harmer
25.458
940641AE2-051 GEN
Solar/Wind Harmer
4.772
316388AE2-253 GEN
Solar/Wind Harmer
0.187
316336AC2-165 C
Solar/Wind Harmer
0.002
3146456SLIGO L269
Solar/Wind Harmer
0.059
316246AF1-032 C
Solar/Wind Harmer
0.027
316093AE2-104_GEN
Solar/Wind Harmer
0.998
3146516WINFALL
Solar/Wind Harmer
0.19
3146516WINFALL
Solar/Wind Harmer
0.059
315800Z1-036_GEN1
Solar/Wind Harmer
0
970937AG2-583 GEN
Solar/Wind Harmer
3.567
3130156CHOWAN
Solar/Wind Harmer
0.058
3145663CRESWEL
Solar/Wind Harmer
0.161
971163AH1-040 GEN
Solar/Wind Harmer
4.594
972003AH1-546 GEN
Solar/Wind Harmer
2.42
970919AG2-571 GEN
Solar/Wind Harmer
2.017
316322AB2-045
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.023
316023GEN1_S
Solar/Wind Harmer
0.127
970087AG2-069 GEN
Solar/Wind Harmer
4.529
3146206CASHIE
Solar/Wind Harmer
0.057
971547AH1-271 GEN
Solar/Wind Harmer
1.207
3145893MURPHYS
Solar/Wind Harmer
0.226
3145893MURPHYS
Solar/Wind Harmer
0.251
3146926FARMVIL
Solar/Wind Harmer
0.034
3146173TUNIS
Solar/Wind Harmer
0.056
23779801AA1-109
Solar/Wind Helper
0.196
223401AF1-299 GEN
Solar/Wind Helper
0.351
966131AG1-482 GEN
Solar/Wind Helper
0.102
237080AD1-060 GEN
Solar/Wind Helper
0.184
235062AE1-101 C1
Solar/Wind Helper
0.889
237038AE2-054 C
Solar/Wind Helper
0.144
233930AB2-032 GEN
Solar/Wind Helper
0.215
233915AB1-141 GEN
Solar/Wind Helper
0.283
232422X3-066 FULL
Solar/Wind Helper
0.064
233964AF2-378 GEN
Solar/Wind Helper
0.023
232426Y1-080 FULL
Solar/Wind Helper
0.022
232428Y3-058 C
Solar/Wind Helper
0.19
233998TM1NIN_3.36
Solar/Wind Helper
0.146
233954AC2-188 GEN
Solar/Wind Helper
0.13
232404W1-003 C
Solar/Wind Helper
0.284
233950AC2-186 GEN
Solar/Wind Helper
0.065
232434Z2-077 GEN
Solar/Wind Helper
0.071
233972AC1-094 C
Solar/Wind Helper
0.169
205941AD2-115 GEN
Solar/Wind Helper
0.276
230511AF1-262
Solar/Wind Helper
0.008
230434AG1-499 GEN
Solar/Wind Helper
0.126
228728W1-130C
Solar/Wind Helper
0.03
219258KINSLEYDEP C
Solar/Wind Helper
0.042
219904AC1-010 C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.019
218660EHAMPSOLAR C
Solar/Wind Helper
0.018
219686LUMSOLAR_N C
Solar/Wind Helper
0.022
219304NAMERICA C
Solar/Wind Helper
0.072
20720728JCB_W1-129
Solar/Wind Helper
0.031
207445AB1-138_GEN
Solar/Wind Helper
0.056
963711AG1-223 GEN
Solar/Wind Helper
0.035
20714828MDF_W3-079
Solar/Wind Helper
0.07
219680HOPEWELLV C1
Solar/Wind Helper
0.002
207454AA2-184 E
Solar/Wind Helper
0.166
20715228NPK_W1-113
Solar/Wind Helper
0.042
20742028HF_AC1-207
Solar/Wind Helper
0.075
218428ETC SOLAR C
Solar/Wind Helper
0.003
207528AF2-192 GEN
Solar/Wind Helper
0.04
20673628F1S_V4-069
Solar/Wind Helper
0.016
20675428EAM_W2-061
Solar/Wind Helper
0.008
217213AMBOY SO C
Solar/Wind Helper
0.015
20676428JCR_X2-075
Solar/Wind Helper
0.036
217209CENTRL HS C
Solar/Wind Helper
0.004
217208PARK ELE C
Solar/Wind Helper
0.002
20674328GAR_V4-001
Solar/Wind Helper
0.012
207439AE1-081 C O1
Solar/Wind Helper
0.01
207437AD2-070 GEN
Solar/Wind Helper
0.073
207518AF1-320_GEN
Solar/Wind Helper
0.827
20671928W4-073
Solar/Wind Helper
0.047
20675828AU_W4-064
Solar/Wind Helper
0.015
961301AF2-421 GEN
Solar/Wind Helper
0.221
963151AG1-164 GEN
Solar/Wind Helper
0.221
LAGNLTFEXP_LAGN->PJM
CLTF
5.367
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.069
TVALTFEXP_TVA->PJM
CLTF
2.703
NYPJM->LTFIMP_NY
CLTF
2.351
LGEELTFEXP_LGEE->PJM
CLTF
1.596
WECLTFEXP_WEC->PJM
CLTF
0.855
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.688
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.895
MECLTFEXP_MEC->PJM
CLTF
3.911
SIGELTFEXP_SIGE->PJM
CLTF
0.123
CPLELTFEXP_CPLE->PJM
CLTF
3.974
CBM West 2LTFEXP_CBM-W2->PJM
CBM
33.607

Details for 6ELMONT-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6ELMONT-6HANOVER 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.87 %
Rating:1123.3 MVA
Rating Type:B
MVA to Mitigate:1189.21
MW Contribution:3.02
Bus #Bus NameTypeMW Contribution
3142296MT RD221
50/50
0.632
3142366NRTHEST
50/50
0.551
3150691DARBY 3
50/50
11.896
3150701DARBY 4
50/50
11.869
3150681DARBY 2
50/50
11.855
3150671DARBY 1
50/50
11.841
3150621CHESTS7
50/50
0.394
966871AG1-558 GEN
Solar/Wind Harmer
0.195
316075AC2-137 C
Solar/Wind Harmer
0.04
3142946ENON
Solar/Wind Harmer
0.013
944641AF1-129 GEN
Adder
63.125
316240AF1-291 C
Solar/Wind Harmer
0.001
3143526WINTERP
Solar/Wind Harmer
0.621
316033AB2-134 GEN
Solar/Wind Harmer
0.007
315697AD1-025 GEN
Solar/Wind Harmer
0.134
316468AD1-105 GEN
Solar/Wind Harmer
-0.035
970657AG2-426 GEN
Solar/Wind Harmer
3.808
970657AG2-426 GEN
Solar/Wind Harmer
0.798
316236AE1-162_GEN
Solar/Wind Harmer
0.001
971223AH1-071 GEN
Solar/Wind Harmer
1.1
316036AC1-147 C
Solar/Wind Harmer
0.019
3150991CHESPKB
Adder
1.057
3150991CHESPKB
Adder
1.031
316316AC1-027 C
Solar/Wind Harmer
0.096
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.003
3145506HICKORY
Solar/Wind Harmer
0.398
3145506HICKORY
Solar/Wind Harmer
0.239
3145506HICKORY
Solar/Wind Harmer
0.06
316339AD2-160 GEN
Solar/Wind Harmer
0.161
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.055
3137176SLIGO L2192
Solar/Wind Harmer
0.393
3146456SLIGO L269
Solar/Wind Harmer
1.748
3130086AYDLETT
Solar/Wind Harmer
0.394
971645AH1-323 GEN
50/50
17.435
3143096IRON208
50/50
0.63
3143096IRON208
50/50
0.617
316473AC1-191 GEN
Solar/Wind Harmer
0.571
3142416OLDCHRC
Solar/Wind Harmer
1.631
970293AG2-193 GEN
Solar/Wind Harmer
1.601
3150861SPRUNCD
Adder
0.622
3142946ENON
Solar/Wind Harmer
0.045
970133AG2-095 GEN
Solar/Wind Harmer
1.231
970129AG2-093 GEN
Solar/Wind Harmer
7.489
965281AG1-393 GEN
Solar/Wind Harmer
1.32
315839AE2-212 C
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.237
3142433PROV 92
Adder
0.237
315778AD1-151 GEN
Solar/Wind Harmer
9.667
316382AG1-145 C
Solar/Wind Harmer
0.001
961611AG1-000B GEN
Solar/Wind Harmer
3.052
315813AE1-149 C
Solar/Wind Harmer
6.039
3151221GRAVEL6
Adder
8.11
3151171GRAVELC
Adder
1.56
3141766HARMONY
Solar/Wind Harmer
1.48
3141843SHACKLE
Adder
0.567
316203AE2-005 GEN
Solar/Wind Harmer
0
3144216WINCHST
Adder
0.416
3150921YORKTN3
Adder
2.767
970659AG2-427 GEN
Solar/Wind Harmer
1.163
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.002
971781AH1-399 GEN
Solar/Wind Harmer
0.143
970661AG2-428 GEN
Solar/Wind Harmer
2.277
3145336SMITFLD
Solar/Wind Harmer
0.043
316156AD2-030 GEN
Solar/Wind Harmer
0.079
3141873WAN 176
Solar/Wind Harmer
1.904
3144536CHRHLND
Solar/Wind Harmer
0.015
3144873MCLAUGH
Solar/Wind Harmer
0.003
3151101ELIZAR3
Adder
9.352
315773AC2-141 GEN
Solar/Wind Harmer
3.646
944581AF1-123 GEN
Solar/Wind Harmer
22.395
944601AF1-125 GEN
Solar/Wind Harmer
22.05
3146456SLIGO L269
Solar/Wind Harmer
0.099
971153AH1-033 GEN
Solar/Wind Harmer
1.142
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.096
3145273HOLLAND
Solar/Wind Harmer
0.072
3146626S HERTFORD
Solar/Wind Harmer
0.096
962971AG1-146 GEN
Solar/Wind Harmer
1.516
3146376EDENTON
Solar/Wind Harmer
0.093
970009AG2-005 GEN
Solar/Wind Harmer
0.687
315614AA2-178 GEN
Solar/Wind Harmer
0.521
971157AH1-035 GEN
Solar/Wind Harmer
1.07
315737AD1-076 GEN
Solar/Wind Harmer
1.143
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146206CASHIE
Solar/Wind Harmer
0.088
972255AH1-712 GEN
Adder
44.866
316404AE1-155 C
Solar/Wind Harmer
0.02
3145893MURPHYS
Solar/Wind Harmer
0.146
3145893MURPHYS
Solar/Wind Harmer
0.087
957521AF2-046 GEN
Solar/Wind Harmer
6.466
961681AG1-008 GEN
Solar/Wind Harmer
6.466
316365GEN2_N
Solar/Wind Harmer
0.195
316313AB2-026
Solar/Wind Harmer
0.055
316258AE1-075 C
Solar/Wind Harmer
0.065
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
1.308
3146173TUNIS
Solar/Wind Harmer
0.086
3156021HOLLOMANSOL
Solar/Wind Harmer
0.391
316463AE2-346 GEN
Solar/Wind Harmer
0.074
316140AB2-099
Solar/Wind Harmer
0.031
962331AG1-082 GEN
Solar/Wind Harmer
0.914
3146263WOODLND
Solar/Wind Harmer
0.084
3145963POPLR C
Solar/Wind Harmer
0.084
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
316317KELFORD C
Solar/Wind Harmer
0.008
3145823KELFORD
Solar/Wind Harmer
0.083
313506AB2-031 GEN
Solar/Wind Harmer
0.255
3145796HORNRTN
Solar/Wind Harmer
0.326
3145796HORNRTN
Solar/Wind Harmer
0.082
3145933PARMELE
Solar/Wind Harmer
0.08
966801AG1-551 GEN
Solar/Wind Harmer
0.93
3147043LAWRENC
Solar/Wind Harmer
0.048
316210AC1-098 GEN
Solar/Wind Harmer
0.737
3150351NORNECKC2
Adder
0.804
3145746EVERETS
Solar/Wind Harmer
0.078
3145746EVERETS
Solar/Wind Harmer
0.078
315724AD1-057 GEN
Solar/Wind Harmer
0.289
316327AA2-057 GEN
Solar/Wind Harmer
0.115
970917AG2-570 GEN
Solar/Wind Harmer
6.696
3146073TAR RVR
Solar/Wind Harmer
0.075
3146083TARBORO
Solar/Wind Harmer
0.075
3146233WITAKRS
Solar/Wind Harmer
0.375
3146233WITAKRS
Solar/Wind Harmer
0.051
3138543CONSLDL
Solar/Wind Harmer
0.049
961601AG1-000A GEN
Solar/Wind Harmer
5.215
3145543BTLEBRO
Solar/Wind Harmer
0.073
3145543BTLEBRO
Solar/Wind Harmer
0.073
971623AH1-311 GEN
Solar/Wind Harmer
0.147
316478AD1-087 GEN
Solar/Wind Harmer
0.249
316486AD2-202 GEN
Solar/Wind Harmer
0.073
316131AB2-060 GEN
Solar/Wind Harmer
0.221
964241AG1-285 GEN
Solar/Wind Harmer
4.675
315785AD2-033 C
Solar/Wind Harmer
0.567
970257AG2-171 GEN
Solar/Wind Harmer
2.225
959311AF2-222 GEN
Solar/Wind Harmer
6.171
970909AG2-566 GEN
Solar/Wind Harmer
0.738
963181AG1-167 GEN
Solar/Wind Harmer
0.275
3144293JTRSVLE
Adder
0.219
3147133PAMPLIN
Solar/Wind Harmer
0.215
971193AH1-056 GEN
Solar/Wind Harmer
4.17
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.04
3146776BUCKING
Solar/Wind Harmer
0.023
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.742
971683AH1-343 GEN
Solar/Wind Harmer
2.232
316283AC2-100 C
Solar/Wind Harmer
0.116
970221AG2-151 GEN
Solar/Wind Harmer
3.149
966881AG1-559 GEN
Solar/Wind Helper
1.213
3150611CHESTG7
50/50
0.857
3150631CHESTG8
50/50
0.843
316312AB1-027
Solar/Wind Harmer
0.301
971285AH1-108 GEN
Adder
1.017
315976AC1-164 GENA
Solar/Wind Harmer
13.778
316169AC1-164_GENC
Solar/Wind Harmer
11.903
315975AC1-164 GENB
Solar/Wind Harmer
0.408
971167AH1-042 GEN
Solar/Wind Harmer
10.969
316132AB2-190 GEN1
Solar/Wind Harmer
0.662
3142433PROV 92
Adder
0.237
3142433PROV 92
Adder
0.237
316233AE1-074 FULL
Solar/Wind Harmer
0.096
971281AH1-106 GEN
Solar/Wind Harmer
1.657
971283AH1-107 GEN
Solar/Wind Harmer
1.657
316369SG1_INVT
Solar/Wind Harmer
0.004
3143873LANEXA
Solar/Wind Harmer
0.07
316314AB2-024 C
Solar/Wind Harmer
0
3143316POE
Solar/Wind Harmer
0.442
972265AH1-717 GEN
Adder
8.661
3151201GRAVEL4
Adder
8.12
3151191GRAVEL3
Adder
8.017
3151211GRAVEL5
Adder
8.017
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
3.288
315662AE1-191 GEN
Solar/Wind Harmer
0.004
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971445AH1-216 GEN
Solar/Wind Harmer
7.593
3141873WAN 176
Solar/Wind Harmer
0.021
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.071
316311AC2-079 GEN
Solar/Wind Harmer
2.965
3141913WHIT STONE
Solar/Wind Harmer
0.103
3138133OCRAN
Solar/Wind Harmer
0.031
3152611GOSPORTB
Adder
1.285
3152621GOSPORTC
Adder
1.09
3152601GOSPORTA
Adder
1.006
3151081ELIZAR1
Adder
9.234
3151091ELIZAR2
Adder
9.074
3141783LANCAST
Solar/Wind Harmer
0.06
3141783LANCAST
Solar/Wind Harmer
0.04
315835AF2-110_GEN
Solar/Wind Harmer
0.683
316305AF2-043 C
Solar/Wind Harmer
0.001
957871AF2-081 GEN
Solar/Wind Harmer
4.929
319010AE1-072 C
Solar/Wind Harmer
0.497
3146406KITTY HAWK
Solar/Wind Harmer
0.012
313526AB2-022
Solar/Wind Harmer
0.053
3146486SUNBURY
Solar/Wind Harmer
0.098
3146486SUNBURY
Solar/Wind Harmer
0.098
316321Z2-027
Solar/Wind Harmer
0.018
3146396TANGLEW
Solar/Wind Harmer
0.268
3145176PASQUOTANK
Solar/Wind Harmer
0.06
962981AG1-147 GEN
Solar/Wind Harmer
3.537
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
316315AB2-025 C
Solar/Wind Harmer
0.076
315814AE2-033 C
Solar/Wind Harmer
7.456
3130156CHOWAN
Solar/Wind Harmer
0.093
3130156CHOWAN
Solar/Wind Harmer
0.093
970327AG2-215 GEN
Solar/Wind Harmer
3.018
315816AE2-034 GEN
Solar/Wind Harmer
0.39
3130546PLYMOUTH
Solar/Wind Harmer
0.089
315732AD1-074 GEN1
Solar/Wind Harmer
0.51
315733AD1-074 GEN2
Solar/Wind Harmer
0.51
315735AD1-075 GEN1
Solar/Wind Harmer
0.255
965291AG1-394 GEN
Solar/Wind Harmer
0.392
3146206CASHIE
Solar/Wind Harmer
0.088
970601AG2-382 GEN
Solar/Wind Harmer
3.275
972193AH1-681 GEN
Adder
2.005
3145893MURPHYS
Solar/Wind Harmer
0.235
3145893MURPHYS
Solar/Wind Harmer
0.087
3145513AHOSKIE
Solar/Wind Harmer
0.179
3145513AHOSKIE
Solar/Wind Harmer
0.086
3145683EARLEYS
Solar/Wind Harmer
0.17
3145683EARLEYS
Solar/Wind Harmer
0.085
3145683EARLEYS
Solar/Wind Harmer
0.085
3146043SEABORD
Solar/Wind Harmer
0.084
315607AA1-063A GEN
Solar/Wind Harmer
0.172
315652AC1-086 GEN
Solar/Wind Harmer
9.127
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.328
3145796HORNRTN
Solar/Wind Harmer
0.261
3145796HORNRTN
Solar/Wind Harmer
0.033
3146033SCOT NK
Solar/Wind Harmer
0.324
941031AE2-094 GEN
Solar/Wind Harmer
14.626
944011AF1-069 GEN
Solar/Wind Harmer
4.779
3141813NORNECK
Solar/Wind Harmer
0.079
970673AG2-436 GEN
Solar/Wind Harmer
16.734
970673AG2-436 GEN
Solar/Wind Harmer
11.156
316005AA1-067
Solar/Wind Harmer
0.084
3145746EVERETS
Solar/Wind Harmer
0.31
3145746EVERETS
Solar/Wind Harmer
0.078
3145746EVERETS
Solar/Wind Harmer
0.078
3145746EVERETS
Solar/Wind Harmer
0.078
970181AG2-120 GEN
Solar/Wind Harmer
0.97
971967AH1-528 GEN
Solar/Wind Harmer
12.447
957861AF2-080 GEN
Solar/Wind Harmer
3.293
316420AA1-050 GEN
Solar/Wind Harmer
0.002
970831AG2-522 GEN
Solar/Wind Harmer
3.224
970085AG2-068 GEN
Solar/Wind Harmer
4.006
970581AG2-369 GEN
Solar/Wind Harmer
3.445
3145573BETHELC
Solar/Wind Harmer
0.075
3145573BETHELC
Solar/Wind Harmer
0.075
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
1.169
3144303KENBRDG
Solar/Wind Harmer
0.056
970683AG2-441 GEN
Solar/Wind Harmer
4.609
970681AG2-440 GEN
Solar/Wind Harmer
3.687
946301AF1-294 GEN
Solar/Wind Harmer
1.357
961791AG1-021 GEN
Solar/Wind Harmer
0.66
315657AE1-056 GEN
Solar/Wind Harmer
2.362
316118AC1-105 GEN
Solar/Wind Harmer
0.169
970285AG2-188 GEN
Solar/Wind Harmer
5.153
971845AH1-439 GEN
Solar/Wind Harmer
2.936
3147173SINAI
Solar/Wind Harmer
0.064
3147243WELCO
Solar/Wind Harmer
0.04
972205AH1-687 GEN
Adder
2.638
970865AG2-541 GEN
Solar/Wind Harmer
2.043
971447AH1-217 GEN
Solar/Wind Harmer
1.766
3141426STAFORD
Solar/Wind Helper
0.033
3143096IRON208
50/50
0.63
3150641CHESTS8
50/50
0.434
3142416OLDCHRC
Solar/Wind Harmer
0.437
3142416OLDCHRC
Solar/Wind Harmer
0.168
3142543TWELFTH
Solar/Wind Harmer
0.014
944631AF1-128 GEN
Adder
64.319
3150851SPRUNCC
Adder
0.622
315671AE2-027_GEN
Solar/Wind Harmer
8.029
970129AG2-093 GEN
Solar/Wind Harmer
3.524
316458AB2-190 GEN2
Solar/Wind Harmer
0.662
3142433PROV 92
Solar/Wind Harmer
0.488
3142433PROV 92
Adder
0.237
3142433PROV 92
Adder
0.237
971069AG2-661 GEN
Solar/Wind Harmer
2.148
3143526WINTERP
Solar/Wind Harmer
0.621
316159AE1-175 C
Solar/Wind Harmer
0.102
971647AH1-324 GEN
Solar/Wind Harmer
4.981
961611AG1-000B GEN
Solar/Wind Harmer
6.001
3151171GRAVELC
Adder
1.187
971317AH1-138 GEN
Solar/Wind Harmer
0.83
3141766HARMONY
Solar/Wind Harmer
0.022
971777AH1-397 GEN
Solar/Wind Harmer
0.293
3141843SHACKLE
Adder
0.567
3138126ROCKLANDING
Solar/Wind Harmer
0.051
970659AG2-427 GEN
Solar/Wind Harmer
5.319
316381AD1-082 GEN
Solar/Wind Harmer
0.114
970661AG2-428 GEN
Solar/Wind Harmer
10.707
3145336SMITFLD
Solar/Wind Harmer
0.43
3143226MDLTHAN
Solar/Wind Harmer
0.103
316072AD1-144
Solar/Wind Harmer
0.037
3138133OCRAN
Solar/Wind Harmer
0.061
316375AC2-012 GEN
Solar/Wind Harmer
0.003
3150981CHESPKA
Adder
1.26
316294AC1-161 GEN
Solar/Wind Harmer
1.73
316093AE2-104_GEN
Solar/Wind Harmer
1.674
944591AF1-124 GEN
Solar/Wind Harmer
22.475
316388AE2-253 GEN
Solar/Wind Harmer
0.31
316246AF1-032 C
Solar/Wind Harmer
0.045
3146456SLIGO L269
Solar/Wind Harmer
0.099
3146516WINFALL
Solar/Wind Harmer
0.312
3146516WINFALL
Solar/Wind Harmer
0.096
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.093
3145663CRESWEL
Solar/Wind Harmer
0.255
971163AH1-040 GEN
Solar/Wind Harmer
7.278
962861AG1-135 GEN
Solar/Wind Harmer
2.836
939411AE1-173 GEN
Solar/Wind Harmer
37.741
3146206CASHIE
Solar/Wind Harmer
0.088
971547AH1-271 GEN
Solar/Wind Harmer
1.872
972277AH1-723 GEN
Adder
52.282
3145893MURPHYS
Solar/Wind Harmer
0.349
3145893MURPHYS
Solar/Wind Harmer
0.388
316023GEN1_S
Solar/Wind Harmer
0.195
3143336POWHATN
Solar/Wind Harmer
1.539
3146173TUNIS
Solar/Wind Harmer
0.086
3145683EARLEYS
Solar/Wind Harmer
0.085
940641AE2-051 GEN
Solar/Wind Harmer
6.781
3146263WOODLND
Solar/Wind Harmer
0.084
3141726DUNNSVL
Solar/Wind Harmer
0.336
3145963POPLR C
Solar/Wind Harmer
0.084
960081AF2-299 GEN
Solar/Wind Harmer
0.803
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145823KELFORD
Solar/Wind Harmer
0.083
316011AB1-132 GEN
Solar/Wind Harmer
1.509
962571AG1-106 GEN
Solar/Wind Harmer
1.181
316336AC2-165 C
Solar/Wind Harmer
0.003
316190AA2-174 GEN
Solar/Wind Harmer
0
3145796HORNRTN
Solar/Wind Harmer
0.269
3145796HORNRTN
Solar/Wind Harmer
0.082
3145783HORNRTN
Solar/Wind Harmer
0.081
971795AH1-408 GEN
Solar/Wind Harmer
5.392
3146293MARTNCO
Solar/Wind Harmer
0.074
3147043LAWRENC
Adder
0.72
316212AC1-099_GEN
Solar/Wind Harmer
0.411
3150351NORNECKC2
Adder
0.791
3145746EVERETS
Solar/Wind Harmer
0.078
3145746EVERETS
Solar/Wind Harmer
0.078
315722AD1-056 GEN
Solar/Wind Harmer
0.488
316494AC1-189 GEN
Solar/Wind Harmer
0.258
970919AG2-571 GEN
Solar/Wind Harmer
2.678
970087AG2-069 GEN
Solar/Wind Harmer
6.009
961671AG1-007 GEN
Solar/Wind Harmer
0.011
3146083TARBORO
Solar/Wind Harmer
0.075
3145493TOT1
Solar/Wind Harmer
0.333
316129AC1-054 GEN
Solar/Wind Harmer
0.282
3146233WITAKRS
Solar/Wind Harmer
0.297
971065AG2-659 GEN
Solar/Wind Harmer
3.171
316359AB2-059 GEN
Solar/Wind Harmer
0.263
316049AB1-081 GEN
Solar/Wind Harmer
0.419
3145543BTLEBRO
Solar/Wind Harmer
0.073
3145543BTLEBRO
Solar/Wind Harmer
0.059
3142053HEARTS
Solar/Wind Harmer
0.129
957481AF2-042 GEN
Solar/Wind Harmer
19.524
315693AD1-088 GEN
Solar/Wind Harmer
3.47
962491AG1-098 GEN
Solar/Wind Harmer
4.117
970937AG2-583 GEN
Solar/Wind Harmer
4.364
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970685AG2-442 GEN
Solar/Wind Harmer
5.162
963171AG1-166 GEN
Solar/Wind Harmer
0.367
971563AH1-280 GEN
Solar/Wind Harmer
0.733
3144293JTRSVLE
Adder
0.219
315687AD1-152 GEN
Solar/Wind Harmer
0.002
3146926FARMVIL
Solar/Wind Harmer
0.04
970401AG2-262 GEN
Solar/Wind Harmer
0.392
316337AD2-073 GEN
Solar/Wind Harmer
0.057
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.026
316003AC1-222 GEN
Solar/Wind Harmer
0.002
972003AH1-546 GEN
Solar/Wind Harmer
2.646
971377AH1-170 GEN
Solar/Wind Harmer
0.63
3147623JAMES R
Solar/Wind Harmer
0.137
3146386ELIZ CT
Solar/Wind Harmer
0.098
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.096
3146516WINFALL
Solar/Wind Harmer
0.096
3146516WINFALL
Solar/Wind Harmer
0.096
3146626S HERTFORD
Solar/Wind Harmer
0.096
3146626S HERTFORD
Solar/Wind Harmer
0.096
3144356SAPONY
Solar/Wind Harmer
0.792
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.415
3146376EDENTON
Solar/Wind Harmer
0.415
316065AD1-022 GEN
Solar/Wind Harmer
4.058
958261AF2-120 GEN
Solar/Wind Harmer
2.891
3145893MURPHYS
Solar/Wind Harmer
0.583
3145893MURPHYS
Solar/Wind Harmer
0.157
3146173TUNIS
Solar/Wind Harmer
0.086
3146173TUNIS
Solar/Wind Harmer
0.086
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.05
316181AB2-040 GEN
Solar/Wind Harmer
0.12
316426AA2-053 GEN
Solar/Wind Harmer
0.278
3145796HORNRTN
Solar/Wind Harmer
0.245
3145593CAROLNA
Solar/Wind Harmer
0.082
3145593CAROLNA
Solar/Wind Harmer
0.082
966811AG1-552 GEN
Solar/Wind Harmer
0.885
3145593CAROLNA
Solar/Wind Harmer
0.102
3145783HORNRTN
Solar/Wind Harmer
1.442
3145783HORNRTN
Solar/Wind Harmer
1.154
3145783HORNRTN
Solar/Wind Harmer
0.361
3145783HORNRTN
Solar/Wind Harmer
0.144
3145933PARMELE
Solar/Wind Harmer
0.16
3145933PARMELE
Solar/Wind Harmer
0.08
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.831
3150341NORNECKC1
Adder
0.824
316274AC1-208 GEN
Solar/Wind Harmer
0.408
972185AH1-677 GEN
Adder
4.375
972187AH1-678 GEN
Adder
2.202
970933AG2-581 GEN
Solar/Wind Harmer
6.122
3145493TOT1
Solar/Wind Harmer
0.174
3145453TOT5
Solar/Wind Harmer
0.104
3145603CNETO
Solar/Wind Harmer
0.07
961601AG1-000A GEN
Solar/Wind Harmer
1.304
316263AC1-034 GEN
Solar/Wind Harmer
2.784
970099AG2-077 GEN
Solar/Wind Harmer
7.81
939181AE1-148 GEN
Solar/Wind Harmer
3.417
313527AB2-043 GEN
Solar/Wind Harmer
0.001
971741AH1-377 GEN
Solar/Wind Harmer
6.934
316034AC1-036 C
Solar/Wind Harmer
0.005
970323AG2-213 GEN
Solar/Wind Harmer
2.967
971775AH1-396 GEN
Solar/Wind Harmer
0.111
970301AG2-198 GEN
Solar/Wind Harmer
2.952
958211AF2-115 GEN
Solar/Wind Harmer
0.825
963191AG1-168 GEN
Solar/Wind Harmer
0.275
3144293JTRSVLE
Adder
0.219
3144293JTRSVLE
Adder
0.184
3147133PAMPLIN
Solar/Wind Harmer
0.068
3147133PAMPLIN
Solar/Wind Harmer
0.055
962561AG1-105 GEN
Solar/Wind Harmer
3.235
964791AG1-342 GEN
Solar/Wind Harmer
1.284
3146843MT LREL
Solar/Wind Harmer
0.067
3146843MT LREL
Solar/Wind Harmer
0.067
3146776BUCKING
Solar/Wind Harmer
0.258
3146776BUCKING
Solar/Wind Harmer
0.021
316222AC1-221 GEN
Solar/Wind Harmer
0.248
971489AH1-241 GEN
Solar/Wind Harmer
3.149
LAGNLTFEXP_LAGN->PJM
CLTF
4.321
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.837
TVALTFEXP_TVA->PJM
CLTF
2.185
NYPJM->LTFIMP_NY
CLTF
0.971
LGEELTFEXP_LGEE->PJM
CLTF
0.994
WECLTFEXP_WEC->PJM
CLTF
0.514
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.477
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.705
MECLTFEXP_MEC->PJM
CLTF
2.537
SIGELTFEXP_SIGE->PJM
CLTF
0.079
CPLELTFEXP_CPLE->PJM
CLTF
4.707
CBM West 2LTFEXP_CBM-W2->PJM
CBM
24.626

Details for 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:126.74 %
Rating:888.3 MVA
Rating Type:B
MVA to Mitigate:1125.81
MW Contribution:4.48
Bus #Bus NameTypeMW Contribution
316312AB1-027
Solar/Wind Harmer
0.395
972189AH1-679 GEN
Adder
3.384
971285AH1-108 GEN
Adder
1.332
315976AC1-164 GENA
Solar/Wind Harmer
17.534
316169AC1-164_GENC
Solar/Wind Harmer
15.148
315975AC1-164 GENB
Solar/Wind Harmer
0.519
971167AH1-042 GEN
Solar/Wind Harmer
14.525
3142433PROV 92
Adder
0.315
3142433PROV 92
Adder
0.315
316132AB2-190 GEN1
Solar/Wind Harmer
0.845
316233AE1-074 FULL
Solar/Wind Harmer
0.126
971281AH1-106 GEN
Solar/Wind Harmer
2.178
971283AH1-107 GEN
Solar/Wind Harmer
2.178
3143873LANEXA
Solar/Wind Harmer
0.093
316314AB2-024 C
Solar/Wind Harmer
0.001
316369SG1_INVT
Solar/Wind Harmer
0.006
970189AG2-124 GEN
Solar/Wind Harmer
4.432
316059AD1-063 C
Solar/Wind Harmer
0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.029
3141913WHIT STONE
Solar/Wind Harmer
0.143
3138133OCRAN
Solar/Wind Harmer
0.043
3143316POE
Solar/Wind Harmer
0.563
3138283WHITEMARSH
Solar/Wind Harmer
0.033
3141783LANCAST
Solar/Wind Harmer
0.085
3141783LANCAST
Solar/Wind Harmer
0.056
972265AH1-717 GEN
Adder
10.823
3151201GRAVEL4
Adder
10.146
3151191GRAVEL3
Adder
10.018
3151211GRAVEL5
Adder
10.018
962981AG1-147 GEN
Solar/Wind Harmer
5.162
970327AG2-215 GEN
Solar/Wind Harmer
4.484
971445AH1-216 GEN
Solar/Wind Harmer
9.42
3141813NORNECK
Solar/Wind Harmer
0.129
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.087
316311AC2-079 GEN
Solar/Wind Harmer
3.662
3152611GOSPORTB
Adder
1.57
3152621GOSPORTC
Adder
1.332
3152601GOSPORTA
Adder
1.229
3151081ELIZAR1
Adder
11.278
3151091ELIZAR2
Adder
11.082
315835AF2-110_GEN
Solar/Wind Harmer
0.834
316305AF2-043 C
Solar/Wind Harmer
0.001
957871AF2-081 GEN
Solar/Wind Harmer
5.996
319010AE1-072 C
Solar/Wind Harmer
0.604
3146406KITTY HAWK
Solar/Wind Harmer
0.015
313526AB2-022
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.118
3146486SUNBURY
Solar/Wind Harmer
0.118
316321Z2-027
Solar/Wind Harmer
0.022
3146396TANGLEW
Solar/Wind Harmer
0.325
3145176PASQUOTANK
Solar/Wind Harmer
0.073
316315AB2-025 C
Solar/Wind Harmer
0.095
315814AE2-033 C
Solar/Wind Harmer
9.24
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.112
3130156CHOWAN
Solar/Wind Harmer
0.112
316223AC1-118
Solar/Wind Harmer
0.079
315816AE2-034 GEN
Solar/Wind Harmer
0.465
3130546PLYMOUTH
Solar/Wind Harmer
0.105
315732AD1-074 GEN1
Solar/Wind Harmer
0.603
315733AD1-074 GEN2
Solar/Wind Harmer
0.603
315735AD1-075 GEN1
Solar/Wind Harmer
0.302
965291AG1-394 GEN
Solar/Wind Harmer
0.463
3146206CASHIE
Solar/Wind Harmer
0.103
970601AG2-382 GEN
Solar/Wind Harmer
3.859
3145893MURPHYS
Solar/Wind Harmer
0.277
3145893MURPHYS
Solar/Wind Harmer
0.103
3145513AHOSKIE
Solar/Wind Harmer
0.21
3145513AHOSKIE
Solar/Wind Harmer
0.1
3145683EARLEYS
Solar/Wind Harmer
0.199
3145683EARLEYS
Solar/Wind Harmer
0.1
3145683EARLEYS
Solar/Wind Harmer
0.1
3146043SEABORD
Solar/Wind Harmer
0.099
315607AA1-063A GEN
Solar/Wind Harmer
0.2
941031AE2-094 GEN
Solar/Wind Harmer
17.955
944011AF1-069 GEN
Solar/Wind Harmer
5.867
315652AC1-086 GEN
Solar/Wind Harmer
10.647
316087AB2-174 GEN
Solar/Wind Harmer
0.003
970673AG2-436 GEN
Solar/Wind Harmer
20.374
970673AG2-436 GEN
Solar/Wind Harmer
13.582
3137643SOCKMAN
Solar/Wind Harmer
0.379
3145796HORNRTN
Solar/Wind Harmer
0.302
3145796HORNRTN
Solar/Wind Harmer
0.038
971967AH1-528 GEN
Solar/Wind Harmer
15.01
3146033SCOT NK
Solar/Wind Harmer
0.373
970085AG2-068 GEN
Solar/Wind Harmer
4.745
970581AG2-369 GEN
Solar/Wind Harmer
4.081
316005AA1-067
Solar/Wind Harmer
0.095
3145746EVERETS
Solar/Wind Harmer
0.35
3145746EVERETS
Solar/Wind Harmer
0.088
3145746EVERETS
Solar/Wind Harmer
0.088
3145746EVERETS
Solar/Wind Harmer
0.088
970181AG2-120 GEN
Solar/Wind Harmer
1.097
944491AF1-114 GEN
Solar/Wind Harmer
0
957861AF2-080 GEN
Solar/Wind Harmer
3.693
316420AA1-050 GEN
Solar/Wind Harmer
0.003
970831AG2-522 GEN
Solar/Wind Harmer
3.589
3145573BETHELC
Solar/Wind Harmer
0.083
3145573BETHELC
Solar/Wind Harmer
0.083
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
1.197
3144303KENBRDG
Solar/Wind Harmer
0.057
970683AG2-441 GEN
Solar/Wind Harmer
4.648
970681AG2-440 GEN
Solar/Wind Harmer
3.718
946301AF1-294 GEN
Solar/Wind Harmer
1.349
961791AG1-021 GEN
Solar/Wind Harmer
0.656
315657AE1-056 GEN
Solar/Wind Harmer
2.326
316118AC1-105 GEN
Solar/Wind Harmer
0.171
3147173SINAI
Solar/Wind Harmer
0.064
3147243WELCO
Solar/Wind Harmer
0.04
971645AH1-323 GEN
50/50
23.176
315051AA1-145 CT1
50/50
1.602
316473AC1-191 GEN
Solar/Wind Harmer
0.785
3142416OLDCHRC
Solar/Wind Harmer
2.137
970293AG2-193 GEN
Solar/Wind Harmer
2.08
3143096IRON208
Adder
0.772
3143096IRON208
Adder
0.757
971781AH1-399 GEN
Solar/Wind Harmer
0.241
3150861SPRUNCD
Adder
0.814
3142946ENON
Solar/Wind Harmer
0.058
970133AG2-095 GEN
Solar/Wind Harmer
1.58
3142433PROV 92
Adder
0.315
3142433PROV 92
Adder
0.315
965281AG1-393 GEN
Solar/Wind Harmer
1.703
315839AE2-212 C
Solar/Wind Harmer
0.001
970129AG2-093 GEN
Solar/Wind Harmer
9.555
315778AD1-151 GEN
Solar/Wind Harmer
12.276
3141843SHACKLE
Adder
0.764
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
1.992
316280AD1-041 GEN
Solar/Wind Harmer
0.003
316382AG1-145 C
Solar/Wind Harmer
0.001
316156AD2-030 GEN
Solar/Wind Harmer
0.108
3141873WAN 176
Solar/Wind Harmer
2.586
961611AG1-000B GEN
Solar/Wind Harmer
3.834
315813AE1-149 C
Solar/Wind Harmer
7.663
3151221GRAVEL6
Adder
10.135
3151171GRAVELC
Adder
1.95
970659AG2-427 GEN
Solar/Wind Harmer
1.465
962971AG1-146 GEN
Solar/Wind Harmer
2.212
316083AB2-161 GEN
Solar/Wind Harmer
0.002
3144216WINCHST
Adder
0.518
3150921YORKTN3
Adder
3.447
970009AG2-005 GEN
Solar/Wind Harmer
1.02
970661AG2-428 GEN
Solar/Wind Harmer
2.849
316404AE1-155 C
Solar/Wind Harmer
0.03
3145336SMITFLD
Solar/Wind Harmer
0.053
3150351NORNECKC2
Adder
1.311
3144536CHRHLND
Solar/Wind Harmer
0.019
3144873MCLAUGH
Solar/Wind Harmer
0.003
3151101ELIZAR3
Adder
11.422
944581AF1-123 GEN
Solar/Wind Harmer
27.265
944601AF1-125 GEN
Solar/Wind Harmer
26.845
315773AC2-141 GEN
Solar/Wind Harmer
4.411
3146456SLIGO L269
Solar/Wind Harmer
0.12
971153AH1-033 GEN
Solar/Wind Harmer
1.388
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.116
3145273HOLLAND
Solar/Wind Harmer
0.087
3146626S HERTFORD
Solar/Wind Harmer
0.115
3146376EDENTON
Solar/Wind Harmer
0.112
3141906WESTMOR
Solar/Wind Harmer
0.044
315614AA2-178 GEN
Solar/Wind Harmer
0.62
971157AH1-035 GEN
Solar/Wind Harmer
1.266
315737AD1-076 GEN
Solar/Wind Harmer
1.351
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
316365GEN2_N
Solar/Wind Harmer
0.232
3146206CASHIE
Solar/Wind Harmer
0.103
3145893MURPHYS
Solar/Wind Harmer
0.172
3145893MURPHYS
Solar/Wind Harmer
0.103
957521AF2-046 GEN
Solar/Wind Harmer
7.604
961681AG1-008 GEN
Solar/Wind Harmer
7.604
3146173TUNIS
Solar/Wind Harmer
0.101
3156021HOLLOMANSOL
Solar/Wind Harmer
0.459
970737AG2-469 GEN
Solar/Wind Harmer
4.296
316463AE2-346 GEN
Solar/Wind Harmer
0.086
316140AB2-099
Solar/Wind Harmer
0.036
962331AG1-082 GEN
Solar/Wind Harmer
1.07
316313AB2-026
Solar/Wind Harmer
0.063
316258AE1-075 C
Solar/Wind Harmer
0.075
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
1.5
3146263WOODLND
Solar/Wind Harmer
0.098
3145963POPLR C
Solar/Wind Harmer
0.097
3142666NORTHAMPTON
Solar/Wind Harmer
0.097
316317KELFORD C
Solar/Wind Harmer
0.009
3145823KELFORD
Solar/Wind Harmer
0.096
313506AB2-031 GEN
Solar/Wind Harmer
0.297
3145796HORNRTN
Solar/Wind Harmer
0.378
3145796HORNRTN
Solar/Wind Harmer
0.094
3145933PARMELE
Solar/Wind Harmer
0.091
966801AG1-551 GEN
Solar/Wind Harmer
1.061
3147043LAWRENC
Solar/Wind Harmer
0.054
316210AC1-098 GEN
Solar/Wind Harmer
0.841
970917AG2-570 GEN
Solar/Wind Harmer
7.946
3145746EVERETS
Solar/Wind Harmer
0.088
3145746EVERETS
Solar/Wind Harmer
0.088
315724AD1-057 GEN
Solar/Wind Harmer
0.326
316327AA2-057 GEN
Solar/Wind Harmer
0.129
3146073TAR RVR
Solar/Wind Harmer
0.083
3146083TARBORO
Solar/Wind Harmer
0.083
3146233WITAKRS
Solar/Wind Harmer
0.418
3146233WITAKRS
Solar/Wind Harmer
0.057
3138543CONSLDL
Solar/Wind Harmer
0.055
961601AG1-000A GEN
Solar/Wind Harmer
5.758
3145543BTLEBRO
Solar/Wind Harmer
0.081
3145543BTLEBRO
Solar/Wind Harmer
0.081
971623AH1-311 GEN
Solar/Wind Harmer
0.162
316478AD1-087 GEN
Solar/Wind Harmer
0.276
316486AD2-202 GEN
Solar/Wind Harmer
0.081
316131AB2-060 GEN
Solar/Wind Harmer
0.233
964241AG1-285 GEN
Solar/Wind Harmer
4.88
315785AD2-033 C
Solar/Wind Harmer
0.583
970257AG2-171 GEN
Solar/Wind Harmer
2.276
959311AF2-222 GEN
Solar/Wind Harmer
6.287
970909AG2-566 GEN
Solar/Wind Harmer
0.742
963181AG1-167 GEN
Solar/Wind Harmer
0.273
3144293JTRSVLE
Adder
0.218
3147133PAMPLIN
Solar/Wind Harmer
0.212
971193AH1-056 GEN
Solar/Wind Harmer
4.107
942461AE2-259 GEN
Solar/Wind Harmer
0
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.746
3146926FARMVIL
Solar/Wind Harmer
0.037
316283AC2-100 C
Solar/Wind Harmer
0.113
971683AH1-343 GEN
Solar/Wind Harmer
2.074
3142296MT RD221
50/50
0.838
3142366NRTHEST
50/50
0.724
3150691DARBY 3
50/50
15.566
3150701DARBY 4
50/50
15.53
3150681DARBY 2
50/50
15.512
3150671DARBY 1
50/50
15.494
966871AG1-558 GEN
Solar/Wind Harmer
0.269
316075AC2-137 C
Solar/Wind Harmer
0.051
316468AD1-105 GEN
Solar/Wind Harmer
-0.06
3142946ENON
Solar/Wind Harmer
0.017
944641AF1-129 GEN
Adder
81.784
316240AF1-291 C
Solar/Wind Harmer
0.001
3143526WINTERP
Solar/Wind Harmer
0.816
316033AB2-134 GEN
Solar/Wind Harmer
0.009
315697AD1-025 GEN
Solar/Wind Harmer
0.169
970657AG2-426 GEN
Solar/Wind Harmer
4.777
970657AG2-426 GEN
Solar/Wind Harmer
1.002
971223AH1-071 GEN
Solar/Wind Harmer
1.448
958261AF2-120 GEN
Solar/Wind Harmer
4.431
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.354
3150341NORNECKC1
Adder
1.343
316036AC1-147 C
Solar/Wind Harmer
0.023
3150991CHESPKB
Adder
1.291
3150991CHESPKB
Adder
1.26
316316AC1-027 C
Solar/Wind Harmer
0.117
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.003
3145506HICKORY
Solar/Wind Harmer
0.484
3145506HICKORY
Solar/Wind Harmer
0.291
3145506HICKORY
Solar/Wind Harmer
0.073
316339AD2-160 GEN
Solar/Wind Harmer
0.196
316018AA1-139 ULT2
Solar/Wind Harmer
0.003
316017AA1-139 ULT1
Solar/Wind Harmer
0.067
3137176SLIGO L2192
Solar/Wind Harmer
0.478
3146456SLIGO L269
Solar/Wind Harmer
2.125
3130086AYDLETT
Solar/Wind Harmer
0.479
3146386ELIZ CT
Solar/Wind Harmer
0.118
3144356SAPONY
Solar/Wind Harmer
0.983
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.116
3146516WINFALL
Solar/Wind Harmer
0.116
3146516WINFALL
Solar/Wind Harmer
0.116
3146626S HERTFORD
Solar/Wind Harmer
0.115
3146626S HERTFORD
Solar/Wind Harmer
0.115
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.497
3146376EDENTON
Solar/Wind Harmer
0.497
957411AF2-035 GEN
Solar/Wind Harmer
4.469
970317AG2-208 GEN
Solar/Wind Harmer
4.14
316065AD1-022 GEN
Solar/Wind Harmer
4.786
3145893MURPHYS
Solar/Wind Harmer
0.687
3145893MURPHYS
Solar/Wind Harmer
0.185
3146173TUNIS
Solar/Wind Harmer
0.101
3146173TUNIS
Solar/Wind Harmer
0.101
3142666NORTHAMPTON
Solar/Wind Harmer
0.097
3142666NORTHAMPTON
Solar/Wind Harmer
0.097
3142666NORTHAMPTON
Solar/Wind Harmer
0.097
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
316181AB2-040 GEN
Solar/Wind Harmer
0.139
316426AA2-053 GEN
Solar/Wind Harmer
0.321
3145796HORNRTN
Solar/Wind Harmer
0.283
972185AH1-677 GEN
Adder
5.303
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.094
966811AG1-552 GEN
Solar/Wind Harmer
1.021
3145593CAROLNA
Solar/Wind Harmer
0.117
3145783HORNRTN
Solar/Wind Harmer
1.66
3145783HORNRTN
Solar/Wind Harmer
1.328
3145783HORNRTN
Solar/Wind Harmer
0.415
3145783HORNRTN
Solar/Wind Harmer
0.166
972187AH1-678 GEN
Adder
2.654
3145933PARMELE
Solar/Wind Harmer
0.182
3145933PARMELE
Solar/Wind Harmer
0.091
970933AG2-581 GEN
Solar/Wind Harmer
7.263
316274AC1-208 GEN
Solar/Wind Harmer
0.464
3145493TOT1
Solar/Wind Harmer
0.194
3145453TOT5
Solar/Wind Harmer
0.116
3145603CNETO
Solar/Wind Harmer
0.077
970099AG2-077 GEN
Solar/Wind Harmer
8.86
961601AG1-000A GEN
Solar/Wind Harmer
1.439
316263AC1-034 GEN
Solar/Wind Harmer
3.071
939181AE1-148 GEN
Solar/Wind Harmer
3.678
313527AB2-043 GEN
Solar/Wind Harmer
0.001
315673AE1-157 GEN
Solar/Wind Harmer
5.089
971741AH1-377 GEN
Solar/Wind Harmer
7.141
970323AG2-213 GEN
Solar/Wind Harmer
3.035
971775AH1-396 GEN
Solar/Wind Harmer
0.114
316034AC1-036 C
Solar/Wind Harmer
0.005
970301AG2-198 GEN
Solar/Wind Harmer
2.969
962561AG1-105 GEN
Solar/Wind Harmer
3.332
964791AG1-342 GEN
Solar/Wind Harmer
1.316
3146843MT LREL
Solar/Wind Harmer
0.068
3146843MT LREL
Solar/Wind Harmer
0.068
958211AF2-115 GEN
Solar/Wind Harmer
0.82
963191AG1-168 GEN
Solar/Wind Harmer
0.273
3144293JTRSVLE
Adder
0.218
3144293JTRSVLE
Adder
0.183
3147133PAMPLIN
Solar/Wind Harmer
0.067
3147133PAMPLIN
Solar/Wind Harmer
0.054
316222AC1-221 GEN
Solar/Wind Harmer
0.241
315052AA1-145 CT2
50/50
1.609
3142416OLDCHRC
Solar/Wind Harmer
0.573
3142416OLDCHRC
Solar/Wind Harmer
0.22
3143096IRON208
Adder
0.772
3142543TWELFTH
Solar/Wind Harmer
0.018
3150851SPRUNCC
Adder
0.814
944631AF1-128 GEN
Adder
82.869
315671AE2-027_GEN
Solar/Wind Harmer
10.376
3142433PROV 92
Solar/Wind Harmer
0.647
3142433PROV 92
Adder
0.315
3142433PROV 92
Adder
0.315
970129AG2-093 GEN
Solar/Wind Harmer
4.497
316458AB2-190 GEN2
Solar/Wind Harmer
0.845
3143526WINTERP
Solar/Wind Harmer
0.816
971069AG2-661 GEN
Solar/Wind Harmer
2.728
971777AH1-397 GEN
Solar/Wind Harmer
0.395
3141843SHACKLE
Adder
0.764
3141766HARMONY
Solar/Wind Harmer
0.03
316159AE1-175 C
Solar/Wind Harmer
0.127
971647AH1-324 GEN
Solar/Wind Harmer
6.283
961611AG1-000B GEN
Solar/Wind Harmer
7.539
3138133OCRAN
Solar/Wind Harmer
0.085
971317AH1-138 GEN
Solar/Wind Harmer
1.044
3151171GRAVELC
Adder
1.483
970659AG2-427 GEN
Solar/Wind Harmer
6.695
316381AD1-082 GEN
Solar/Wind Harmer
0.143
3138126ROCKLANDING
Solar/Wind Harmer
0.063
3143226MDLTHAN
Solar/Wind Harmer
0.136
962861AG1-135 GEN
Solar/Wind Harmer
4.311
970661AG2-428 GEN
Solar/Wind Harmer
13.393
3145336SMITFLD
Solar/Wind Harmer
0.533
3141726DUNNSVL
Solar/Wind Harmer
0.531
3150351NORNECKC2
Adder
1.289
316072AD1-144
Solar/Wind Harmer
0.045
316375AC2-012 GEN
Solar/Wind Harmer
0.003
3150981CHESPKA
Adder
1.539
316093AE2-104_GEN
Solar/Wind Harmer
2.044
944591AF1-124 GEN
Solar/Wind Harmer
27.362
316294AC1-161 GEN
Solar/Wind Harmer
2.092
316246AF1-032 C
Solar/Wind Harmer
0.054
316388AE2-253 GEN
Solar/Wind Harmer
0.378
316337AD2-073 GEN
Solar/Wind Harmer
0.105
3146456SLIGO L269
Solar/Wind Harmer
0.12
3146516WINFALL
Solar/Wind Harmer
0.377
3146516WINFALL
Solar/Wind Harmer
0.116
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.112
939411AE1-173 GEN
Solar/Wind Harmer
46.536
3145663CRESWEL
Solar/Wind Harmer
0.303
971163AH1-040 GEN
Solar/Wind Harmer
8.662
940641AE2-051 GEN
Solar/Wind Harmer
8.402
966881AG1-559 GEN
Solar/Wind Harmer
0.121
316023GEN1_S
Solar/Wind Harmer
0.232
3146206CASHIE
Solar/Wind Harmer
0.103
971547AH1-271 GEN
Solar/Wind Harmer
2.205
3145893MURPHYS
Solar/Wind Harmer
0.41
3145893MURPHYS
Solar/Wind Harmer
0.456
3146173TUNIS
Solar/Wind Harmer
0.101
3145683EARLEYS
Solar/Wind Harmer
0.1
3143336POWHATN
Solar/Wind Harmer
1.765
3146263WOODLND
Solar/Wind Harmer
0.098
960081AF2-299 GEN
Solar/Wind Harmer
0.939
3145963POPLR C
Solar/Wind Harmer
0.097
316011AB1-132 GEN
Solar/Wind Harmer
1.76
962571AG1-106 GEN
Solar/Wind Harmer
1.377
3145823KELFORD
Solar/Wind Harmer
0.096
316174AB2-169 GEN
Solar/Wind Harmer
0.003
316190AA2-174 GEN
Solar/Wind Harmer
0
3145796HORNRTN
Solar/Wind Harmer
0.312
3145796HORNRTN
Solar/Wind Harmer
0.094
972135AH1-637 GEN
Solar/Wind Harmer
0.806
3145783HORNRTN
Solar/Wind Harmer
0.093
971795AH1-408 GEN
Solar/Wind Harmer
6.196
3146293MARTNCO
Solar/Wind Harmer
0.084
3147043LAWRENC
Adder
0.82
316212AC1-099_GEN
Solar/Wind Harmer
0.469
316336AC2-165 C
Solar/Wind Harmer
0.004
970919AG2-571 GEN
Solar/Wind Harmer
3.178
970087AG2-069 GEN
Solar/Wind Harmer
7.118
3145746EVERETS
Solar/Wind Harmer
0.088
3145746EVERETS
Solar/Wind Harmer
0.088
315722AD1-056 GEN
Solar/Wind Harmer
0.551
316494AC1-189 GEN
Solar/Wind Harmer
0.289
961671AG1-007 GEN
Solar/Wind Harmer
0.013
3146083TARBORO
Solar/Wind Harmer
0.083
3145493TOT1
Solar/Wind Harmer
0.371
3146233WITAKRS
Solar/Wind Harmer
0.331
957481AF2-042 GEN
Solar/Wind Harmer
22.149
316129AC1-054 GEN
Solar/Wind Harmer
0.312
971065AG2-659 GEN
Solar/Wind Harmer
3.501
316359AB2-059 GEN
Solar/Wind Harmer
0.29
316049AB1-081 GEN
Solar/Wind Harmer
0.462
3145543BTLEBRO
Solar/Wind Harmer
0.081
3145543BTLEBRO
Solar/Wind Harmer
0.065
3142053HEARTS
Solar/Wind Harmer
0.142
315693AD1-088 GEN
Solar/Wind Harmer
3.844
962491AG1-098 GEN
Solar/Wind Harmer
4.539
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
5.205
970401AG2-262 GEN
Solar/Wind Harmer
0.402
963171AG1-166 GEN
Solar/Wind Harmer
0.365
971563AH1-280 GEN
Solar/Wind Harmer
0.729
3144293JTRSVLE
Adder
0.218
970937AG2-583 GEN
Solar/Wind Harmer
4.001
3146926FARMVIL
Solar/Wind Harmer
0.037
316003AC1-222 GEN
Solar/Wind Harmer
0.002
LAGNLTFEXP_LAGN->PJM
CLTF
1.967
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.801
TVALTFEXP_TVA->PJM
CLTF
0.968
NYPJM->LTFIMP_NY
CLTF
0.78
LGEELTFEXP_LGEE->PJM
CLTF
0.102
WECLTFEXP_WEC->PJM
CLTF
0.044
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.893
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.08
MECLTFEXP_MEC->PJM
CLTF
0.479
SIGELTFEXP_SIGE->PJM
CLTF
0.012
CPLELTFEXP_CPLE->PJM
CLTF
4.454
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.414

Details for 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.65 %
Rating:888.3 MVA
Rating Type:B
MVA to Mitigate:1000.69
MW Contribution:3.01
Bus #Bus NameTypeMW Contribution
3142296MT RD221
50/50
0.865
3142366NRTHEST
50/50
0.696
3150691DARBY 3
50/50
14.433
3150701DARBY 4
50/50
14.399
966871AG1-558 GEN
Solar/Wind Harmer
0.275
3150681DARBY 2
Adder
13.554
3150671DARBY 1
Adder
13.538
316468AD1-105 GEN
Solar/Wind Harmer
-0.061
3143526WINTERP
Solar/Wind Harmer
0.869
944641AF1-129 GEN
Adder
75.958
316240AF1-291 C
Solar/Wind Harmer
0.001
971223AH1-071 GEN
Solar/Wind Harmer
1.648
316075AC2-137 C
Solar/Wind Harmer
0.04
3142946ENON
Solar/Wind Harmer
0.013
316033AB2-134 GEN
Solar/Wind Harmer
0.007
315697AD1-025 GEN
Solar/Wind Harmer
0.133
957411AF2-035 GEN
Solar/Wind Harmer
4.74
970317AG2-208 GEN
Solar/Wind Harmer
4.392
970657AG2-426 GEN
Solar/Wind Harmer
3.866
970657AG2-426 GEN
Solar/Wind Harmer
0.81
3144356SAPONY
Solar/Wind Harmer
0.871
972189AH1-679 GEN
50/50
3.754
316312AB1-027
Solar/Wind Harmer
0.366
971285AH1-108 GEN
Adder
1.32
316233AE1-074 FULL
Solar/Wind Harmer
0.134
971281AH1-106 GEN
Solar/Wind Harmer
2.319
971283AH1-107 GEN
Solar/Wind Harmer
2.319
316132AB2-190 GEN1
Solar/Wind Harmer
0.692
3143316POE
Solar/Wind Harmer
0.509
971167AH1-042 GEN
Solar/Wind Harmer
11.321
3142433PROV 92
Adder
0.241
3142433PROV 92
Adder
0.241
316369SG1_INVT
Solar/Wind Harmer
0.004
315976AC1-164 GENA
Solar/Wind Harmer
11.881
316169AC1-164_GENC
Solar/Wind Harmer
10.264
315975AC1-164 GENB
Solar/Wind Harmer
0.352
3143873LANEXA
Solar/Wind Harmer
0.066
316315AB2-025 C
Solar/Wind Harmer
0.084
315814AE2-033 C
Solar/Wind Harmer
8.168
970189AG2-124 GEN
Solar/Wind Harmer
3.032
316314AB2-024 C
Solar/Wind Harmer
0
972265AH1-717 GEN
Adder
7.859
3151201GRAVEL4
Adder
7.367
3151191GRAVEL3
Adder
7.274
3151211GRAVEL5
Adder
7.274
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.019
3141913WHIT STONE
Solar/Wind Harmer
0.096
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.065
3138133OCRAN
Solar/Wind Harmer
0.029
316311AC2-079 GEN
Solar/Wind Harmer
2.73
3141783LANCAST
Solar/Wind Harmer
0.057
3141783LANCAST
Solar/Wind Harmer
0.038
971445AH1-216 GEN
Solar/Wind Harmer
6.635
962981AG1-147 GEN
Solar/Wind Harmer
3.458
970327AG2-215 GEN
Solar/Wind Harmer
3.007
3138283WHITEMARSH
Solar/Wind Harmer
0.021
941031AE2-094 GEN
Solar/Wind Harmer
16.062
944011AF1-069 GEN
Solar/Wind Harmer
5.248
3141813NORNECK
Solar/Wind Harmer
0.087
971645AH1-323 GEN
50/50
24.148
315051AA1-145 CT1
50/50
1.675
3150501FRIVERG
50/50
1.618
316473AC1-191 GEN
Solar/Wind Harmer
0.805
3142416OLDCHRC
Solar/Wind Harmer
1.98
971781AH1-399 GEN
Solar/Wind Harmer
0.246
3150861SPRUNCD
Adder
0.807
970293AG2-193 GEN
Solar/Wind Harmer
1.797
3143096IRON208
Adder
0.699
3143096IRON208
Adder
0.685
315839AE2-212 C
Solar/Wind Harmer
0.001
965281AG1-393 GEN
Solar/Wind Harmer
1.542
970133AG2-095 GEN
Solar/Wind Harmer
1.345
3142946ENON
Solar/Wind Harmer
0.045
970129AG2-093 GEN
Solar/Wind Harmer
7.862
3142433PROV 92
Adder
0.241
3142433PROV 92
Adder
0.241
315813AE1-149 C
Solar/Wind Harmer
6.558
315778AD1-151 GEN
Solar/Wind Harmer
9.834
970659AG2-427 GEN
Solar/Wind Harmer
1.205
316313AB2-026
Solar/Wind Harmer
0.072
316258AE1-075 C
Solar/Wind Harmer
0.086
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
1.719
316083AB2-161 GEN
Solar/Wind Harmer
0.001
961611AG1-000B GEN
Solar/Wind Harmer
2.879
970661AG2-428 GEN
Solar/Wind Harmer
2.271
3141843SHACKLE
Adder
0.523
316203AE2-005 GEN
Solar/Wind Harmer
0
3151221GRAVEL6
Adder
7.359
3151171GRAVELC
Adder
1.416
316280AD1-041 GEN
Solar/Wind Harmer
0.002
3141766HARMONY
Solar/Wind Harmer
1.332
316156AD2-030 GEN
Solar/Wind Harmer
0.072
3141873WAN 176
Solar/Wind Harmer
1.726
3145336SMITFLD
Solar/Wind Harmer
0.037
962971AG1-146 GEN
Solar/Wind Harmer
1.482
316382AG1-145 C
Solar/Wind Harmer
0.001
970009AG2-005 GEN
Solar/Wind Harmer
0.684
316404AE1-155 C
Solar/Wind Harmer
0.02
316365GEN2_N
Solar/Wind Harmer
0.197
3150351NORNECKC2
Adder
0.883
3144216WINCHST
Adder
0.324
3144536CHRHLND
Solar/Wind Harmer
0.013
3150921YORKTN3
Adder
2.109
3145273HOLLAND
Solar/Wind Harmer
0.062
3144873MCLAUGH
Solar/Wind Harmer
0.002
3151101ELIZAR3
Adder
7.508
313506AB2-031 GEN
Solar/Wind Harmer
0.248
970917AG2-570 GEN
Solar/Wind Harmer
7.106
3146456SLIGO L269
Solar/Wind Harmer
0.079
971153AH1-033 GEN
Solar/Wind Harmer
0.918
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
316435W1029_GEN3
Solar/Wind Harmer
0
316320Y1-086
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.079
3142666NORTHAMPTON
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.079
3147043LAWRENC
Solar/Wind Harmer
0.047
944581AF1-123 GEN
Solar/Wind Harmer
17.595
944601AF1-125 GEN
Solar/Wind Harmer
17.324
3145893MURPHYS
Solar/Wind Harmer
0.131
3145893MURPHYS
Solar/Wind Harmer
0.078
3146376EDENTON
Solar/Wind Harmer
0.078
957521AF2-046 GEN
Solar/Wind Harmer
5.788
961681AG1-008 GEN
Solar/Wind Harmer
5.788
3145796HORNRTN
Solar/Wind Harmer
0.311
3145796HORNRTN
Solar/Wind Harmer
0.078
3146173TUNIS
Solar/Wind Harmer
0.077
315614AA2-178 GEN
Solar/Wind Harmer
0.44
316463AE2-346 GEN
Solar/Wind Harmer
0.066
316140AB2-099
Solar/Wind Harmer
0.027
962331AG1-082 GEN
Solar/Wind Harmer
0.816
971157AH1-035 GEN
Solar/Wind Harmer
0.915
3146263WOODLND
Solar/Wind Harmer
0.076
315737AD1-076 GEN
Solar/Wind Harmer
0.979
3146206CASHIE
Solar/Wind Harmer
0.076
3156021HOLLOMANSOL
Solar/Wind Harmer
0.345
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.075
3141906WESTMOR
Solar/Wind Harmer
0.03
3145963POPLR C
Solar/Wind Harmer
0.073
316210AC1-098 GEN
Solar/Wind Harmer
0.673
316478AD1-087 GEN
Solar/Wind Harmer
0.251
316486AD2-202 GEN
Solar/Wind Harmer
0.074
315724AD1-057 GEN
Solar/Wind Harmer
0.269
315773AC2-141 GEN
Solar/Wind Harmer
2.612
3145933PARMELE
Solar/Wind Harmer
0.07
966801AG1-551 GEN
Solar/Wind Harmer
0.817
316327AA2-057 GEN
Solar/Wind Harmer
0.105
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
970737AG2-469 GEN
Solar/Wind Harmer
2.935
3146233WITAKRS
Solar/Wind Harmer
0.342
3146233WITAKRS
Solar/Wind Harmer
0.046
3138543CONSLDL
Solar/Wind Harmer
0.045
3146073TAR RVR
Solar/Wind Harmer
0.067
3146083TARBORO
Solar/Wind Harmer
0.067
970909AG2-566 GEN
Solar/Wind Harmer
0.714
316131AB2-060 GEN
Solar/Wind Harmer
0.211
961601AG1-000A GEN
Solar/Wind Harmer
4.75
971623AH1-311 GEN
Solar/Wind Harmer
0.133
3145543BTLEBRO
Solar/Wind Harmer
0.067
3145543BTLEBRO
Solar/Wind Harmer
0.067
964241AG1-285 GEN
Solar/Wind Harmer
4.442
316236AE1-162_GEN
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
2.976
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.912
3150341NORNECKC1
Adder
0.905
972185AH1-677 GEN
Adder
4.746
972187AH1-678 GEN
Adder
2.375
315742AE1-103 GEN
Solar/Wind Harmer
0.001
970933AG2-581 GEN
Solar/Wind Harmer
6.534
316036AC1-147 C
Solar/Wind Harmer
0.015
3150991CHESPKB
Adder
0.851
3150991CHESPKB
Adder
0.831
316316AC1-027 C
Solar/Wind Harmer
0.077
3142956BIRDNECK
Solar/Wind Harmer
0
316181AB2-040 GEN
Solar/Wind Harmer
0.116
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3145506HICKORY
Solar/Wind Harmer
0.318
3145506HICKORY
Solar/Wind Harmer
0.191
3145506HICKORY
Solar/Wind Harmer
0.048
316339AD2-160 GEN
Solar/Wind Harmer
0.129
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.044
3137176SLIGO L2192
Solar/Wind Harmer
0.316
3146456SLIGO L269
Solar/Wind Harmer
1.405
3130086AYDLETT
Solar/Wind Harmer
0.317
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146386ELIZ CT
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3142666NORTHAMPTON
Solar/Wind Harmer
0.079
3142666NORTHAMPTON
Solar/Wind Harmer
0.079
3142666NORTHAMPTON
Solar/Wind Harmer
0.079
3142666NORTHAMPTON
Solar/Wind Harmer
0.047
315673AE1-157 GEN
Solar/Wind Harmer
5.466
3146626S HERTFORD
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.079
3145893MURPHYS
Solar/Wind Harmer
0.523
3145893MURPHYS
Solar/Wind Harmer
0.14
3146376EDENTON
Solar/Wind Harmer
0.346
3146376EDENTON
Solar/Wind Harmer
0.346
3145796HORNRTN
Solar/Wind Harmer
0.233
3146173TUNIS
Solar/Wind Harmer
0.077
3146173TUNIS
Solar/Wind Harmer
0.077
970673AG2-436 GEN
Solar/Wind Harmer
18.231
970673AG2-436 GEN
Solar/Wind Harmer
12.154
315835AF2-110_GEN
Solar/Wind Harmer
0.581
971967AH1-528 GEN
Solar/Wind Harmer
13.462
3152611GOSPORTB
Adder
1.035
3152621GOSPORTC
Adder
0.879
3152601GOSPORTA
Adder
0.81
316305AF2-043 C
Solar/Wind Harmer
0.001
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3151081ELIZAR1
Adder
7.413
3151091ELIZAR2
Adder
7.284
3146486SUNBURY
Solar/Wind Harmer
0.08
3146486SUNBURY
Solar/Wind Harmer
0.08
315652AC1-086 GEN
Solar/Wind Harmer
8.756
970085AG2-068 GEN
Solar/Wind Harmer
4.243
970581AG2-369 GEN
Solar/Wind Harmer
3.649
957871AF2-081 GEN
Solar/Wind Harmer
3.955
319010AE1-072 C
Solar/Wind Harmer
0.4
3146406KITTY HAWK
Solar/Wind Harmer
0.01
313526AB2-022
Solar/Wind Harmer
0.043
316321Z2-027
Solar/Wind Harmer
0.015
3145176PASQUOTANK
Solar/Wind Harmer
0.049
3146396TANGLEW
Solar/Wind Harmer
0.218
965291AG1-394 GEN
Solar/Wind Harmer
0.352
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3137643SOCKMAN
Solar/Wind Harmer
0.313
3145893MURPHYS
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
0.078
3130156CHOWAN
Solar/Wind Harmer
0.078
3130156CHOWAN
Solar/Wind Harmer
0.078
3146043SEABORD
Solar/Wind Harmer
0.078
3145796HORNRTN
Solar/Wind Harmer
0.249
3145796HORNRTN
Solar/Wind Harmer
0.031
315607AA1-063A GEN
Solar/Wind Harmer
0.159
315816AE2-034 GEN
Solar/Wind Harmer
0.33
3145513AHOSKIE
Solar/Wind Harmer
0.16
3145513AHOSKIE
Solar/Wind Harmer
0.076
3130546PLYMOUTH
Solar/Wind Harmer
0.076
315732AD1-074 GEN1
Solar/Wind Harmer
0.437
315733AD1-074 GEN2
Solar/Wind Harmer
0.437
315735AD1-075 GEN1
Solar/Wind Harmer
0.219
3146206CASHIE
Solar/Wind Harmer
0.076
970601AG2-382 GEN
Solar/Wind Harmer
2.838
3145683EARLEYS
Solar/Wind Harmer
0.152
3145683EARLEYS
Solar/Wind Harmer
0.076
3145683EARLEYS
Solar/Wind Harmer
0.076
316223AC1-118
Solar/Wind Harmer
0.054
3146033SCOT NK
Solar/Wind Harmer
0.294
970831AG2-522 GEN
Solar/Wind Harmer
3.055
316005AA1-067
Solar/Wind Harmer
0.074
3145746EVERETS
Solar/Wind Harmer
0.274
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
970181AG2-120 GEN
Solar/Wind Harmer
0.858
316319Z2-044 C
Solar/Wind Harmer
0
957861AF2-080 GEN
Solar/Wind Harmer
2.939
316420AA1-050 GEN
Solar/Wind Harmer
0.002
3145573BETHELC
Solar/Wind Harmer
0.067
3145573BETHELC
Solar/Wind Harmer
0.067
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
1.107
3144303KENBRDG
Solar/Wind Harmer
0.053
970683AG2-441 GEN
Solar/Wind Harmer
4.354
970681AG2-440 GEN
Solar/Wind Harmer
3.483
946301AF1-294 GEN
Solar/Wind Harmer
1.279
961791AG1-021 GEN
Solar/Wind Harmer
0.622
315657AE1-056 GEN
Solar/Wind Harmer
2.223
316118AC1-105 GEN
Solar/Wind Harmer
0.155
944491AF1-114 GEN
Solar/Wind Harmer
0
970285AG2-188 GEN
Solar/Wind Harmer
4.666
3147173SINAI
Solar/Wind Harmer
0.058
3147243WELCO
Solar/Wind Harmer
0.037
971845AH1-439 GEN
Solar/Wind Harmer
2.641
315785AD2-033 C
Solar/Wind Harmer
0.537
970257AG2-171 GEN
Solar/Wind Harmer
2.107
959311AF2-222 GEN
Solar/Wind Harmer
5.84
963181AG1-167 GEN
Solar/Wind Harmer
0.259
3144293JTRSVLE
Adder
0.206
3147133PAMPLIN
Solar/Wind Harmer
0.202
971193AH1-056 GEN
Solar/Wind Harmer
3.925
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.037
316248AF1-058 C
Solar/Wind Harmer
0
960061AF2-297 GEN
Solar/Wind Harmer
2.493
3146776BUCKING
Solar/Wind Harmer
0.021
3145593CAROLNA
Solar/Wind Harmer
0.077
3145593CAROLNA
Solar/Wind Harmer
0.077
966811AG1-552 GEN
Solar/Wind Harmer
0.833
3145593CAROLNA
Solar/Wind Harmer
0.096
316426AA2-053 GEN
Solar/Wind Harmer
0.259
3145783HORNRTN
Solar/Wind Harmer
1.353
3145783HORNRTN
Solar/Wind Harmer
1.083
3145783HORNRTN
Solar/Wind Harmer
0.338
3145783HORNRTN
Solar/Wind Harmer
0.135
316065AD1-022 GEN
Solar/Wind Harmer
3.502
970099AG2-077 GEN
Solar/Wind Harmer
8.029
316274AC1-208 GEN
Solar/Wind Harmer
0.376
3145933PARMELE
Solar/Wind Harmer
0.14
3145933PARMELE
Solar/Wind Harmer
0.07
971741AH1-377 GEN
Solar/Wind Harmer
6.787
939181AE1-148 GEN
Solar/Wind Harmer
3.254
3145493TOT1
Solar/Wind Harmer
0.157
3145453TOT5
Solar/Wind Harmer
0.094
3145603CNETO
Solar/Wind Harmer
0.063
313527AB2-043 GEN
Solar/Wind Harmer
0.001
970301AG2-198 GEN
Solar/Wind Harmer
2.858
961601AG1-000A GEN
Solar/Wind Harmer
1.187
316263AC1-034 GEN
Solar/Wind Harmer
2.534
970323AG2-213 GEN
Solar/Wind Harmer
2.809
971775AH1-396 GEN
Solar/Wind Harmer
0.105
316034AC1-036 C
Solar/Wind Harmer
0.005
958211AF2-115 GEN
Solar/Wind Harmer
0.778
963191AG1-168 GEN
Solar/Wind Harmer
0.259
3144293JTRSVLE
Adder
0.206
3144293JTRSVLE
Adder
0.174
3147133PAMPLIN
Solar/Wind Harmer
0.064
3147133PAMPLIN
Solar/Wind Harmer
0.052
962561AG1-105 GEN
Solar/Wind Harmer
3.015
964791AG1-342 GEN
Solar/Wind Harmer
1.191
3146843MT LREL
Solar/Wind Harmer
0.062
3146843MT LREL
Solar/Wind Harmer
0.062
3146776BUCKING
Solar/Wind Harmer
0.231
3146776BUCKING
Solar/Wind Harmer
0.019
315052AA1-145 CT2
50/50
1.682
3142416OLDCHRC
Solar/Wind Harmer
0.531
3142416OLDCHRC
Solar/Wind Harmer
0.203
3142543TWELFTH
Solar/Wind Harmer
0.017
3150851SPRUNCC
Adder
0.807
3143526WINTERP
Solar/Wind Harmer
0.869
3143096IRON208
Adder
0.699
3143226MDLTHAN
Solar/Wind Harmer
0.154
315671AE2-027_GEN
Solar/Wind Harmer
9.4
944631AF1-128 GEN
Adder
68.219
970129AG2-093 GEN
Solar/Wind Harmer
3.7
316458AB2-190 GEN2
Solar/Wind Harmer
0.692
3142433PROV 92
Solar/Wind Harmer
0.495
3142433PROV 92
Adder
0.241
3142433PROV 92
Adder
0.241
971069AG2-661 GEN
Solar/Wind Harmer
2.185
970659AG2-427 GEN
Solar/Wind Harmer
5.509
3143336POWHATN
Solar/Wind Harmer
2.022
971647AH1-324 GEN
Solar/Wind Harmer
4.837
316381AD1-082 GEN
Solar/Wind Harmer
0.117
966881AG1-559 GEN
Solar/Wind Harmer
0.128
961611AG1-000B GEN
Solar/Wind Harmer
5.662
970661AG2-428 GEN
Solar/Wind Harmer
10.677
316336AC2-165 C
Solar/Wind Harmer
0.004
971777AH1-397 GEN
Solar/Wind Harmer
0.27
3141843SHACKLE
Adder
0.523
3151171GRAVELC
Adder
1.077
3141766HARMONY
Solar/Wind Harmer
0.02
3138133OCRAN
Solar/Wind Harmer
0.057
3145336SMITFLD
Solar/Wind Harmer
0.374
316159AE1-175 C
Solar/Wind Harmer
0.08
962861AG1-135 GEN
Solar/Wind Harmer
2.894
3141726DUNNSVL
Solar/Wind Harmer
0.357
316023GEN1_S
Solar/Wind Harmer
0.197
940641AE2-051 GEN
Solar/Wind Harmer
6.975
3150351NORNECKC2
Adder
0.868
3138126ROCKLANDING
Solar/Wind Harmer
0.039
939411AE1-173 GEN
Solar/Wind Harmer
36.329
971317AH1-138 GEN
Solar/Wind Harmer
0.635
316093AE2-104_GEN
Solar/Wind Harmer
1.424
316072AD1-144
Solar/Wind Harmer
0.031
960081AF2-299 GEN
Solar/Wind Harmer
0.797
316337AD2-073 GEN
Solar/Wind Harmer
0.071
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
1.015
316246AF1-032 C
Solar/Wind Harmer
0.037
970919AG2-571 GEN
Solar/Wind Harmer
2.843
971795AH1-408 GEN
Solar/Wind Harmer
5.315
316011AB1-132 GEN
Solar/Wind Harmer
1.447
962571AG1-106 GEN
Solar/Wind Harmer
1.133
970087AG2-069 GEN
Solar/Wind Harmer
6.365
316388AE2-253 GEN
Solar/Wind Harmer
0.249
3146456SLIGO L269
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.256
3146516WINFALL
Solar/Wind Harmer
0.079
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3147043LAWRENC
Adder
0.707
944591AF1-124 GEN
Solar/Wind Harmer
17.658
3145893MURPHYS
Solar/Wind Harmer
0.312
3145893MURPHYS
Solar/Wind Harmer
0.347
3130156CHOWAN
Solar/Wind Harmer
0.078
3145796HORNRTN
Solar/Wind Harmer
0.256
3145796HORNRTN
Solar/Wind Harmer
0.078
3146173TUNIS
Solar/Wind Harmer
0.077
3145663CRESWEL
Solar/Wind Harmer
0.215
971163AH1-040 GEN
Solar/Wind Harmer
6.157
316190AA2-174 GEN
Solar/Wind Harmer
0
3146263WOODLND
Solar/Wind Harmer
0.076
3145783HORNRTN
Solar/Wind Harmer
0.076
3146206CASHIE
Solar/Wind Harmer
0.076
971547AH1-271 GEN
Solar/Wind Harmer
1.622
3145683EARLEYS
Solar/Wind Harmer
0.076
970937AG2-583 GEN
Solar/Wind Harmer
4.642
957481AF2-042 GEN
Solar/Wind Harmer
20.073
3145823KELFORD
Solar/Wind Harmer
0.075
315693AD1-088 GEN
Solar/Wind Harmer
3.517
3145963POPLR C
Solar/Wind Harmer
0.073
962491AG1-098 GEN
Solar/Wind Harmer
4.163
316212AC1-099_GEN
Solar/Wind Harmer
0.375
316174AB2-169 GEN
Solar/Wind Harmer
0.002
315722AD1-056 GEN
Solar/Wind Harmer
0.454
316294AC1-161 GEN
Solar/Wind Harmer
1.239
316129AC1-054 GEN
Solar/Wind Harmer
0.267
971065AG2-659 GEN
Solar/Wind Harmer
3.009
3146293MARTNCO
Solar/Wind Harmer
0.065
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
3146233WITAKRS
Solar/Wind Harmer
0.271
316494AC1-189 GEN
Solar/Wind Harmer
0.23
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.067
3145493TOT1
Solar/Wind Harmer
0.3
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.002
316359AB2-059 GEN
Solar/Wind Harmer
0.24
316049AB1-081 GEN
Solar/Wind Harmer
0.382
3142053HEARTS
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.067
3145543BTLEBRO
Solar/Wind Harmer
0.053
970685AG2-442 GEN
Solar/Wind Harmer
4.877
963171AG1-166 GEN
Solar/Wind Harmer
0.346
971563AH1-280 GEN
Solar/Wind Harmer
0.691
3144293JTRSVLE
Adder
0.206
972135AH1-637 GEN
Solar/Wind Harmer
0.553
3146926FARMVIL
Solar/Wind Harmer
0.037
970401AG2-262 GEN
Solar/Wind Harmer
0.364
316322AB2-045
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.023
LAGNLTFEXP_LAGN->PJM
CLTF
1.99
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.971
TVALTFEXP_TVA->PJM
CLTF
0.987
NYPJM->LTFIMP_NY
CLTF
0.729
LGEELTFEXP_LGEE->PJM
CLTF
0.185
WECLTFEXP_WEC->PJM
CLTF
0.088
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.615
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.22
MECLTFEXP_MEC->PJM
CLTF
0.64
SIGELTFEXP_SIGE->PJM
CLTF
0.018
CPLELTFEXP_CPLE->PJM
CLTF
3.927
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.16

Details for 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.13 %
Rating:879.84 MVA
Rating Type:B
MVA to Mitigate:1118.55
MW Contribution:4.46
Bus #Bus NameTypeMW Contribution
316312AB1-027
Solar/Wind Harmer
0.393
972189AH1-679 GEN
Adder
3.368
971285AH1-108 GEN
Adder
1.326
315976AC1-164 GENA
Solar/Wind Harmer
17.453
316169AC1-164_GENC
Solar/Wind Harmer
15.078
315975AC1-164 GENB
Solar/Wind Harmer
0.516
971167AH1-042 GEN
Solar/Wind Harmer
14.458
3142433PROV 92
Adder
0.313
3142433PROV 92
Adder
0.313
316132AB2-190 GEN1
Solar/Wind Harmer
0.841
316233AE1-074 FULL
Solar/Wind Harmer
0.125
971281AH1-106 GEN
Solar/Wind Harmer
2.168
971283AH1-107 GEN
Solar/Wind Harmer
2.168
3143873LANEXA
Solar/Wind Harmer
0.093
316314AB2-024 C
Solar/Wind Harmer
0.001
316369SG1_INVT
Solar/Wind Harmer
0.006
970189AG2-124 GEN
Solar/Wind Harmer
4.412
316059AD1-063 C
Solar/Wind Harmer
0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.029
3141913WHIT STONE
Solar/Wind Harmer
0.142
3138133OCRAN
Solar/Wind Harmer
0.042
3143316POE
Solar/Wind Harmer
0.561
3138283WHITEMARSH
Solar/Wind Harmer
0.033
3141783LANCAST
Solar/Wind Harmer
0.084
3141783LANCAST
Solar/Wind Harmer
0.056
972265AH1-717 GEN
Adder
10.773
3151201GRAVEL4
Adder
10.099
3151191GRAVEL3
Adder
9.972
3151211GRAVEL5
Adder
9.972
962981AG1-147 GEN
Solar/Wind Harmer
5.138
970327AG2-215 GEN
Solar/Wind Harmer
4.464
971445AH1-216 GEN
Solar/Wind Harmer
9.376
3141813NORNECK
Solar/Wind Harmer
0.129
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.087
316311AC2-079 GEN
Solar/Wind Harmer
3.645
3152611GOSPORTB
Adder
1.562
3152621GOSPORTC
Adder
1.326
3152601GOSPORTA
Adder
1.223
3151081ELIZAR1
Adder
11.226
3151091ELIZAR2
Adder
11.031
315835AF2-110_GEN
Solar/Wind Harmer
0.83
316305AF2-043 C
Solar/Wind Harmer
0.001
957871AF2-081 GEN
Solar/Wind Harmer
5.968
319010AE1-072 C
Solar/Wind Harmer
0.602
3146406KITTY HAWK
Solar/Wind Harmer
0.015
313526AB2-022
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.118
3146486SUNBURY
Solar/Wind Harmer
0.118
316321Z2-027
Solar/Wind Harmer
0.022
3146396TANGLEW
Solar/Wind Harmer
0.323
3145176PASQUOTANK
Solar/Wind Harmer
0.073
316315AB2-025 C
Solar/Wind Harmer
0.095
315814AE2-033 C
Solar/Wind Harmer
9.198
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.111
3130156CHOWAN
Solar/Wind Harmer
0.111
316223AC1-118
Solar/Wind Harmer
0.079
315816AE2-034 GEN
Solar/Wind Harmer
0.463
3130546PLYMOUTH
Solar/Wind Harmer
0.105
315732AD1-074 GEN1
Solar/Wind Harmer
0.6
315733AD1-074 GEN2
Solar/Wind Harmer
0.6
315735AD1-075 GEN1
Solar/Wind Harmer
0.301
965291AG1-394 GEN
Solar/Wind Harmer
0.46
3146206CASHIE
Solar/Wind Harmer
0.103
970601AG2-382 GEN
Solar/Wind Harmer
3.841
3145893MURPHYS
Solar/Wind Harmer
0.276
3145893MURPHYS
Solar/Wind Harmer
0.102
3145513AHOSKIE
Solar/Wind Harmer
0.209
3145513AHOSKIE
Solar/Wind Harmer
0.1
3145683EARLEYS
Solar/Wind Harmer
0.198
3145683EARLEYS
Solar/Wind Harmer
0.099
3145683EARLEYS
Solar/Wind Harmer
0.099
3146043SEABORD
Solar/Wind Harmer
0.098
315607AA1-063A GEN
Solar/Wind Harmer
0.199
941031AE2-094 GEN
Solar/Wind Harmer
17.872
944011AF1-069 GEN
Solar/Wind Harmer
5.839
315652AC1-086 GEN
Solar/Wind Harmer
10.598
316087AB2-174 GEN
Solar/Wind Harmer
0.003
970673AG2-436 GEN
Solar/Wind Harmer
20.28
970673AG2-436 GEN
Solar/Wind Harmer
13.52
3137643SOCKMAN
Solar/Wind Harmer
0.378
3145796HORNRTN
Solar/Wind Harmer
0.301
3145796HORNRTN
Solar/Wind Harmer
0.038
971967AH1-528 GEN
Solar/Wind Harmer
14.941
3146033SCOT NK
Solar/Wind Harmer
0.371
970085AG2-068 GEN
Solar/Wind Harmer
4.723
970581AG2-369 GEN
Solar/Wind Harmer
4.062
316005AA1-067
Solar/Wind Harmer
0.094
3145746EVERETS
Solar/Wind Harmer
0.349
3145746EVERETS
Solar/Wind Harmer
0.088
3145746EVERETS
Solar/Wind Harmer
0.088
3145746EVERETS
Solar/Wind Harmer
0.088
970181AG2-120 GEN
Solar/Wind Harmer
1.091
944491AF1-114 GEN
Solar/Wind Harmer
0
957861AF2-080 GEN
Solar/Wind Harmer
3.676
316420AA1-050 GEN
Solar/Wind Harmer
0.003
970831AG2-522 GEN
Solar/Wind Harmer
3.573
3145573BETHELC
Solar/Wind Harmer
0.083
3145573BETHELC
Solar/Wind Harmer
0.083
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
1.192
3144303KENBRDG
Solar/Wind Harmer
0.057
970683AG2-441 GEN
Solar/Wind Harmer
4.626
971645AH1-323 GEN
50/50
23.069
315051AA1-145 CT1
50/50
1.594
316473AC1-191 GEN
Solar/Wind Harmer
0.781
3142416OLDCHRC
Solar/Wind Harmer
2.127
970293AG2-193 GEN
Solar/Wind Harmer
2.071
3143096IRON208
Adder
0.769
3143096IRON208
Adder
0.754
971781AH1-399 GEN
Solar/Wind Harmer
0.24
3150861SPRUNCD
Adder
0.81
3142946ENON
Solar/Wind Harmer
0.057
970133AG2-095 GEN
Solar/Wind Harmer
1.573
3142433PROV 92
Adder
0.313
3142433PROV 92
Adder
0.313
965281AG1-393 GEN
Solar/Wind Harmer
1.695
315839AE2-212 C
Solar/Wind Harmer
0.001
970129AG2-093 GEN
Solar/Wind Harmer
9.511
315778AD1-151 GEN
Solar/Wind Harmer
12.22
3141843SHACKLE
Adder
0.761
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
1.983
316280AD1-041 GEN
Solar/Wind Harmer
0.003
316382AG1-145 C
Solar/Wind Harmer
0.001
316156AD2-030 GEN
Solar/Wind Harmer
0.107
3141873WAN 176
Solar/Wind Harmer
2.574
961611AG1-000B GEN
Solar/Wind Harmer
3.816
315813AE1-149 C
Solar/Wind Harmer
7.628
3151221GRAVEL6
Adder
10.088
3151171GRAVELC
Adder
1.941
970659AG2-427 GEN
Solar/Wind Harmer
1.458
962971AG1-146 GEN
Solar/Wind Harmer
2.202
316083AB2-161 GEN
Solar/Wind Harmer
0.002
3144216WINCHST
Adder
0.516
3150921YORKTN3
Adder
3.431
970009AG2-005 GEN
Solar/Wind Harmer
1.016
970661AG2-428 GEN
Solar/Wind Harmer
2.835
316404AE1-155 C
Solar/Wind Harmer
0.03
3145336SMITFLD
Solar/Wind Harmer
0.053
3150351NORNECKC2
Adder
1.304
3144536CHRHLND
Solar/Wind Harmer
0.019
3144873MCLAUGH
Solar/Wind Harmer
0.003
3151101ELIZAR3
Adder
11.37
944581AF1-123 GEN
Solar/Wind Harmer
27.14
944601AF1-125 GEN
Solar/Wind Harmer
26.722
315773AC2-141 GEN
Solar/Wind Harmer
4.39
3146456SLIGO L269
Solar/Wind Harmer
0.119
971153AH1-033 GEN
Solar/Wind Harmer
1.382
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.116
3145273HOLLAND
Solar/Wind Harmer
0.087
3146626S HERTFORD
Solar/Wind Harmer
0.115
3146376EDENTON
Solar/Wind Harmer
0.111
3141906WESTMOR
Solar/Wind Harmer
0.044
315614AA2-178 GEN
Solar/Wind Harmer
0.617
971157AH1-035 GEN
Solar/Wind Harmer
1.26
315737AD1-076 GEN
Solar/Wind Harmer
1.344
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
316365GEN2_N
Solar/Wind Harmer
0.231
3146206CASHIE
Solar/Wind Harmer
0.103
3145893MURPHYS
Solar/Wind Harmer
0.171
3145893MURPHYS
Solar/Wind Harmer
0.102
957521AF2-046 GEN
Solar/Wind Harmer
7.569
961681AG1-008 GEN
Solar/Wind Harmer
7.569
3146173TUNIS
Solar/Wind Harmer
0.101
3156021HOLLOMANSOL
Solar/Wind Harmer
0.457
970737AG2-469 GEN
Solar/Wind Harmer
4.276
316463AE2-346 GEN
Solar/Wind Harmer
0.086
316140AB2-099
Solar/Wind Harmer
0.036
962331AG1-082 GEN
Solar/Wind Harmer
1.065
316313AB2-026
Solar/Wind Harmer
0.062
316258AE1-075 C
Solar/Wind Harmer
0.075
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
1.493
3146263WOODLND
Solar/Wind Harmer
0.098
3145963POPLR C
Solar/Wind Harmer
0.097
3142666NORTHAMPTON
Solar/Wind Harmer
0.097
316317KELFORD C
Solar/Wind Harmer
0.009
3145823KELFORD
Solar/Wind Harmer
0.096
313506AB2-031 GEN
Solar/Wind Harmer
0.296
3145796HORNRTN
Solar/Wind Harmer
0.376
3145796HORNRTN
Solar/Wind Harmer
0.094
3145933PARMELE
Solar/Wind Harmer
0.091
966801AG1-551 GEN
Solar/Wind Harmer
1.056
3147043LAWRENC
Solar/Wind Harmer
0.054
316210AC1-098 GEN
Solar/Wind Harmer
0.837
970917AG2-570 GEN
Solar/Wind Harmer
7.909
3145746EVERETS
Solar/Wind Harmer
0.088
3145746EVERETS
Solar/Wind Harmer
0.088
315724AD1-057 GEN
Solar/Wind Harmer
0.325
316327AA2-057 GEN
Solar/Wind Harmer
0.128
3146073TAR RVR
Solar/Wind Harmer
0.083
3146083TARBORO
Solar/Wind Harmer
0.083
3146233WITAKRS
Solar/Wind Harmer
0.416
3146233WITAKRS
Solar/Wind Harmer
0.056
3138543CONSLDL
Solar/Wind Harmer
0.054
961601AG1-000A GEN
Solar/Wind Harmer
5.731
971623AH1-311 GEN
Solar/Wind Harmer
0.161
3145543BTLEBRO
Solar/Wind Harmer
0.08
3145543BTLEBRO
Solar/Wind Harmer
0.08
316478AD1-087 GEN
Solar/Wind Harmer
0.275
316486AD2-202 GEN
Solar/Wind Harmer
0.081
316131AB2-060 GEN
Solar/Wind Harmer
0.232
964241AG1-285 GEN
Solar/Wind Harmer
4.857
315785AD2-033 C
Solar/Wind Harmer
0.58
970257AG2-171 GEN
Solar/Wind Harmer
2.266
959311AF2-222 GEN
Solar/Wind Harmer
6.258
970909AG2-566 GEN
Solar/Wind Harmer
0.739
963181AG1-167 GEN
Solar/Wind Harmer
0.272
3144293JTRSVLE
Adder
0.217
3147133PAMPLIN
Solar/Wind Harmer
0.211
971193AH1-056 GEN
Solar/Wind Harmer
4.088
942461AE2-259 GEN
Solar/Wind Harmer
0
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.734
3146926FARMVIL
Solar/Wind Harmer
0.037
316283AC2-100 C
Solar/Wind Harmer
0.113
3142296MT RD221
50/50
0.835
3142366NRTHEST
50/50
0.721
3150691DARBY 3
50/50
15.494
3150701DARBY 4
50/50
15.458
3150681DARBY 2
50/50
15.44
3150671DARBY 1
50/50
15.422
966871AG1-558 GEN
Solar/Wind Harmer
0.267
316075AC2-137 C
Solar/Wind Harmer
0.051
316468AD1-105 GEN
Solar/Wind Harmer
-0.059
3142946ENON
Solar/Wind Harmer
0.017
944641AF1-129 GEN
Adder
81.407
316240AF1-291 C
Solar/Wind Harmer
0.001
3143526WINTERP
Solar/Wind Harmer
0.813
316033AB2-134 GEN
Solar/Wind Harmer
0.009
315697AD1-025 GEN
Solar/Wind Harmer
0.169
970657AG2-426 GEN
Solar/Wind Harmer
4.755
970657AG2-426 GEN
Solar/Wind Harmer
0.997
971223AH1-071 GEN
Solar/Wind Harmer
1.441
958261AF2-120 GEN
Solar/Wind Harmer
4.411
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.348
3150341NORNECKC1
Adder
1.337
316036AC1-147 C
Solar/Wind Harmer
0.023
3150991CHESPKB
Adder
1.285
3150991CHESPKB
Adder
1.254
316316AC1-027 C
Solar/Wind Harmer
0.117
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.003
3145506HICKORY
Solar/Wind Harmer
0.482
3145506HICKORY
Solar/Wind Harmer
0.289
3145506HICKORY
Solar/Wind Harmer
0.072
316339AD2-160 GEN
Solar/Wind Harmer
0.195
316018AA1-139 ULT2
Solar/Wind Harmer
0.003
316017AA1-139 ULT1
Solar/Wind Harmer
0.067
3137176SLIGO L2192
Solar/Wind Harmer
0.476
3146456SLIGO L269
Solar/Wind Harmer
2.116
3130086AYDLETT
Solar/Wind Harmer
0.477
3146386ELIZ CT
Solar/Wind Harmer
0.118
3144356SAPONY
Solar/Wind Harmer
0.978
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.116
3146516WINFALL
Solar/Wind Harmer
0.116
3146516WINFALL
Solar/Wind Harmer
0.116
3146626S HERTFORD
Solar/Wind Harmer
0.115
3146626S HERTFORD
Solar/Wind Harmer
0.115
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.495
3146376EDENTON
Solar/Wind Harmer
0.495
957411AF2-035 GEN
Solar/Wind Harmer
4.448
970317AG2-208 GEN
Solar/Wind Harmer
4.121
316065AD1-022 GEN
Solar/Wind Harmer
4.764
3145893MURPHYS
Solar/Wind Harmer
0.684
3145893MURPHYS
Solar/Wind Harmer
0.184
3146173TUNIS
Solar/Wind Harmer
0.101
3146173TUNIS
Solar/Wind Harmer
0.101
3142666NORTHAMPTON
Solar/Wind Harmer
0.097
3142666NORTHAMPTON
Solar/Wind Harmer
0.097
3142666NORTHAMPTON
Solar/Wind Harmer
0.097
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
316181AB2-040 GEN
Solar/Wind Harmer
0.139
316426AA2-053 GEN
Solar/Wind Harmer
0.32
3145796HORNRTN
Solar/Wind Harmer
0.282
972185AH1-677 GEN
Adder
5.279
3145593CAROLNA
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.094
966811AG1-552 GEN
Solar/Wind Harmer
1.016
3145593CAROLNA
Solar/Wind Harmer
0.117
3145783HORNRTN
Solar/Wind Harmer
1.652
3145783HORNRTN
Solar/Wind Harmer
1.322
3145783HORNRTN
Solar/Wind Harmer
0.413
3145783HORNRTN
Solar/Wind Harmer
0.165
972187AH1-678 GEN
Adder
2.641
3145933PARMELE
Solar/Wind Harmer
0.181
3145933PARMELE
Solar/Wind Harmer
0.091
970933AG2-581 GEN
Solar/Wind Harmer
7.23
316274AC1-208 GEN
Solar/Wind Harmer
0.462
3145493TOT1
Solar/Wind Harmer
0.193
3145453TOT5
Solar/Wind Harmer
0.116
3145603CNETO
Solar/Wind Harmer
0.077
970099AG2-077 GEN
Solar/Wind Harmer
8.819
961601AG1-000A GEN
Solar/Wind Harmer
1.433
316263AC1-034 GEN
Solar/Wind Harmer
3.057
939181AE1-148 GEN
Solar/Wind Harmer
3.661
313527AB2-043 GEN
Solar/Wind Harmer
0.001
315673AE1-157 GEN
Solar/Wind Harmer
5.065
971741AH1-377 GEN
Solar/Wind Harmer
7.108
970323AG2-213 GEN
Solar/Wind Harmer
3.021
315052AA1-145 CT2
50/50
1.601
3142416OLDCHRC
Solar/Wind Harmer
0.57
3142416OLDCHRC
Solar/Wind Harmer
0.219
3143096IRON208
Adder
0.769
3142543TWELFTH
Solar/Wind Harmer
0.018
3150851SPRUNCC
Adder
0.81
944631AF1-128 GEN
Adder
82.486
315671AE2-027_GEN
Solar/Wind Harmer
10.328
3142433PROV 92
Solar/Wind Harmer
0.644
3142433PROV 92
Adder
0.313
3142433PROV 92
Adder
0.313
970129AG2-093 GEN
Solar/Wind Harmer
4.476
316458AB2-190 GEN2
Solar/Wind Harmer
0.841
3143526WINTERP
Solar/Wind Harmer
0.813
971069AG2-661 GEN
Solar/Wind Harmer
2.715
971777AH1-397 GEN
Solar/Wind Harmer
0.393
3141843SHACKLE
Adder
0.761
3141766HARMONY
Solar/Wind Harmer
0.03
316159AE1-175 C
Solar/Wind Harmer
0.127
971647AH1-324 GEN
Solar/Wind Harmer
6.254
961611AG1-000B GEN
Solar/Wind Harmer
7.505
3138133OCRAN
Solar/Wind Harmer
0.085
971317AH1-138 GEN
Solar/Wind Harmer
1.04
3151171GRAVELC
Adder
1.476
970659AG2-427 GEN
Solar/Wind Harmer
6.664
316381AD1-082 GEN
Solar/Wind Harmer
0.143
3138126ROCKLANDING
Solar/Wind Harmer
0.063
3143226MDLTHAN
Solar/Wind Harmer
0.135
962861AG1-135 GEN
Solar/Wind Harmer
4.291
970661AG2-428 GEN
Solar/Wind Harmer
13.331
3145336SMITFLD
Solar/Wind Harmer
0.53
3141726DUNNSVL
Solar/Wind Harmer
0.528
3150351NORNECKC2
Adder
1.283
316072AD1-144
Solar/Wind Harmer
0.045
316375AC2-012 GEN
Solar/Wind Harmer
0.003
3150981CHESPKA
Adder
1.532
316093AE2-104_GEN
Solar/Wind Harmer
2.034
944591AF1-124 GEN
Solar/Wind Harmer
27.236
316294AC1-161 GEN
Solar/Wind Harmer
2.083
316246AF1-032 C
Solar/Wind Harmer
0.054
316388AE2-253 GEN
Solar/Wind Harmer
0.376
316337AD2-073 GEN
Solar/Wind Harmer
0.104
3146456SLIGO L269
Solar/Wind Harmer
0.119
3146516WINFALL
Solar/Wind Harmer
0.376
3146516WINFALL
Solar/Wind Harmer
0.116
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.111
939411AE1-173 GEN
Solar/Wind Harmer
46.322
3145663CRESWEL
Solar/Wind Harmer
0.302
971163AH1-040 GEN
Solar/Wind Harmer
8.622
940641AE2-051 GEN
Solar/Wind Harmer
8.364
966881AG1-559 GEN
Solar/Wind Harmer
0.12
316023GEN1_S
Solar/Wind Harmer
0.231
3146206CASHIE
Solar/Wind Harmer
0.103
971547AH1-271 GEN
Solar/Wind Harmer
2.195
3145893MURPHYS
Solar/Wind Harmer
0.408
3145893MURPHYS
Solar/Wind Harmer
0.454
3146173TUNIS
Solar/Wind Harmer
0.101
3145683EARLEYS
Solar/Wind Harmer
0.099
3143336POWHATN
Solar/Wind Harmer
1.757
3146263WOODLND
Solar/Wind Harmer
0.098
960081AF2-299 GEN
Solar/Wind Harmer
0.935
3145963POPLR C
Solar/Wind Harmer
0.097
316011AB1-132 GEN
Solar/Wind Harmer
1.752
962571AG1-106 GEN
Solar/Wind Harmer
1.371
3145823KELFORD
Solar/Wind Harmer
0.096
316174AB2-169 GEN
Solar/Wind Harmer
0.003
316190AA2-174 GEN
Solar/Wind Harmer
0
3145796HORNRTN
Solar/Wind Harmer
0.31
3145796HORNRTN
Solar/Wind Harmer
0.094
972135AH1-637 GEN
Solar/Wind Harmer
0.802
3145783HORNRTN
Solar/Wind Harmer
0.093
971795AH1-408 GEN
Solar/Wind Harmer
6.167
3146293MARTNCO
Solar/Wind Harmer
0.084
3147043LAWRENC
Adder
0.817
316212AC1-099_GEN
Solar/Wind Harmer
0.467
316336AC2-165 C
Solar/Wind Harmer
0.003
970919AG2-571 GEN
Solar/Wind Harmer
3.164
970087AG2-069 GEN
Solar/Wind Harmer
7.085
3145746EVERETS
Solar/Wind Harmer
0.088
3145746EVERETS
Solar/Wind Harmer
0.088
315722AD1-056 GEN
Solar/Wind Harmer
0.548
316494AC1-189 GEN
Solar/Wind Harmer
0.288
961671AG1-007 GEN
Solar/Wind Harmer
0.013
3146083TARBORO
Solar/Wind Harmer
0.083
3145493TOT1
Solar/Wind Harmer
0.37
3146233WITAKRS
Solar/Wind Harmer
0.329
957481AF2-042 GEN
Solar/Wind Harmer
22.047
316129AC1-054 GEN
Solar/Wind Harmer
0.311
971065AG2-659 GEN
Solar/Wind Harmer
3.485
316359AB2-059 GEN
Solar/Wind Harmer
0.289
316049AB1-081 GEN
Solar/Wind Harmer
0.46
3142053HEARTS
Solar/Wind Harmer
0.142
3145543BTLEBRO
Solar/Wind Harmer
0.08
3145543BTLEBRO
Solar/Wind Harmer
0.064
315693AD1-088 GEN
Solar/Wind Harmer
3.826
962491AG1-098 GEN
Solar/Wind Harmer
4.518
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
5.181
970401AG2-262 GEN
Solar/Wind Harmer
0.4
963171AG1-166 GEN
Solar/Wind Harmer
0.363
971563AH1-280 GEN
Solar/Wind Harmer
0.726
3144293JTRSVLE
Adder
0.217
970937AG2-583 GEN
Solar/Wind Harmer
3.982
3146926FARMVIL
Solar/Wind Harmer
0.037
316003AC1-222 GEN
Solar/Wind Harmer
0.002
970681AG2-440 GEN
Solar/Wind Harmer
3.701
946301AF1-294 GEN
Solar/Wind Harmer
1.343
961791AG1-021 GEN
Solar/Wind Harmer
0.653
315657AE1-056 GEN
Solar/Wind Harmer
2.315
316118AC1-105 GEN
Solar/Wind Harmer
0.171
3147173SINAI
Solar/Wind Harmer
0.064
3147243WELCO
Solar/Wind Harmer
0.04
971775AH1-396 GEN
Solar/Wind Harmer
0.113
316034AC1-036 C
Solar/Wind Harmer
0.005
970301AG2-198 GEN
Solar/Wind Harmer
2.955
962561AG1-105 GEN
Solar/Wind Harmer
3.316
964791AG1-342 GEN
Solar/Wind Harmer
1.31
3146843MT LREL
Solar/Wind Harmer
0.068
3146843MT LREL
Solar/Wind Harmer
0.068
958211AF2-115 GEN
Solar/Wind Harmer
0.817
963191AG1-168 GEN
Solar/Wind Harmer
0.272
3144293JTRSVLE
Adder
0.217
3144293JTRSVLE
Adder
0.182
3147133PAMPLIN
Solar/Wind Harmer
0.067
3147133PAMPLIN
Solar/Wind Harmer
0.054
316222AC1-221 GEN
Solar/Wind Harmer
0.24
LAGNLTFEXP_LAGN->PJM
CLTF
1.958
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.761
TVALTFEXP_TVA->PJM
CLTF
0.963
NYPJM->LTFIMP_NY
CLTF
0.776
LGEELTFEXP_LGEE->PJM
CLTF
0.102
WECLTFEXP_WEC->PJM
CLTF
0.044
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.889
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.066
MECLTFEXP_MEC->PJM
CLTF
0.477
SIGELTFEXP_SIGE->PJM
CLTF
0.012
CPLELTFEXP_CPLE->PJM
CLTF
4.434
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.375

Details for 6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.21 %
Rating:879.84 MVA
Rating Type:B
MVA to Mitigate:996.08
MW Contribution:2.99
Bus #Bus NameTypeMW Contribution
315052AA1-145 CT2
50/50
1.674
3142416OLDCHRC
Solar/Wind Harmer
0.529
3142416OLDCHRC
Solar/Wind Harmer
0.203
3142543TWELFTH
Solar/Wind Harmer
0.017
3150851SPRUNCC
Adder
0.803
3143526WINTERP
Solar/Wind Harmer
0.865
3143096IRON208
Adder
0.696
3143226MDLTHAN
Solar/Wind Harmer
0.154
315671AE2-027_GEN
Solar/Wind Harmer
9.357
944631AF1-128 GEN
Adder
67.904
970129AG2-093 GEN
Solar/Wind Harmer
3.683
316458AB2-190 GEN2
Solar/Wind Harmer
0.689
3142433PROV 92
Solar/Wind Harmer
0.493
3142433PROV 92
Adder
0.24
3142433PROV 92
Adder
0.24
971069AG2-661 GEN
Solar/Wind Harmer
2.175
970659AG2-427 GEN
Solar/Wind Harmer
5.483
3143336POWHATN
Solar/Wind Harmer
2.013
971647AH1-324 GEN
Solar/Wind Harmer
4.814
316381AD1-082 GEN
Solar/Wind Harmer
0.116
966881AG1-559 GEN
Solar/Wind Harmer
0.128
961611AG1-000B GEN
Solar/Wind Harmer
5.636
970661AG2-428 GEN
Solar/Wind Harmer
10.628
316336AC2-165 C
Solar/Wind Harmer
0.004
971777AH1-397 GEN
Solar/Wind Harmer
0.269
3141843SHACKLE
Adder
0.521
3151171GRAVELC
Adder
1.072
3141766HARMONY
Solar/Wind Harmer
0.02
3138133OCRAN
Solar/Wind Harmer
0.057
3145336SMITFLD
Solar/Wind Harmer
0.372
316159AE1-175 C
Solar/Wind Harmer
0.079
962861AG1-135 GEN
Solar/Wind Harmer
2.88
971645AH1-323 GEN
50/50
24.037
315051AA1-145 CT1
50/50
1.667
3150501FRIVERG
50/50
1.611
316473AC1-191 GEN
Solar/Wind Harmer
0.801
3142416OLDCHRC
Solar/Wind Harmer
1.971
971781AH1-399 GEN
Solar/Wind Harmer
0.245
3150861SPRUNCD
Adder
0.803
970293AG2-193 GEN
Solar/Wind Harmer
1.789
3143096IRON208
Adder
0.696
3143096IRON208
Adder
0.682
315839AE2-212 C
Solar/Wind Harmer
0.001
965281AG1-393 GEN
Solar/Wind Harmer
1.535
970133AG2-095 GEN
Solar/Wind Harmer
1.339
3142946ENON
Solar/Wind Harmer
0.045
970129AG2-093 GEN
Solar/Wind Harmer
7.826
3142433PROV 92
Adder
0.24
3142433PROV 92
Adder
0.24
315813AE1-149 C
Solar/Wind Harmer
6.527
315778AD1-151 GEN
Solar/Wind Harmer
9.789
970659AG2-427 GEN
Solar/Wind Harmer
1.199
316313AB2-026
Solar/Wind Harmer
0.071
316258AE1-075 C
Solar/Wind Harmer
0.085
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
1.711
316083AB2-161 GEN
Solar/Wind Harmer
0.001
961611AG1-000B GEN
Solar/Wind Harmer
2.866
970661AG2-428 GEN
Solar/Wind Harmer
2.26
3141843SHACKLE
Adder
0.521
316203AE2-005 GEN
Solar/Wind Harmer
0
3151221GRAVEL6
Adder
7.325
3151171GRAVELC
Adder
1.409
316280AD1-041 GEN
Solar/Wind Harmer
0.002
3141766HARMONY
Solar/Wind Harmer
1.326
316156AD2-030 GEN
Solar/Wind Harmer
0.072
3141873WAN 176
Solar/Wind Harmer
1.718
3145336SMITFLD
Solar/Wind Harmer
0.037
962971AG1-146 GEN
Solar/Wind Harmer
1.475
316382AG1-145 C
Solar/Wind Harmer
0.001
970009AG2-005 GEN
Solar/Wind Harmer
0.681
316404AE1-155 C
Solar/Wind Harmer
0.02
316365GEN2_N
Solar/Wind Harmer
0.196
3150351NORNECKC2
Adder
0.879
3144216WINCHST
Adder
0.323
3144536CHRHLND
Solar/Wind Harmer
0.013
3150921YORKTN3
Adder
2.099
3145273HOLLAND
Solar/Wind Harmer
0.062
3144873MCLAUGH
Solar/Wind Harmer
0.002
3151101ELIZAR3
Adder
7.473
313506AB2-031 GEN
Solar/Wind Harmer
0.246
970917AG2-570 GEN
Solar/Wind Harmer
7.074
3146456SLIGO L269
Solar/Wind Harmer
0.079
971153AH1-033 GEN
Solar/Wind Harmer
0.914
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
316435W1029_GEN3
Solar/Wind Harmer
0
316320Y1-086
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.079
3142666NORTHAMPTON
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.078
3147043LAWRENC
Solar/Wind Harmer
0.047
944581AF1-123 GEN
Solar/Wind Harmer
17.514
944601AF1-125 GEN
Solar/Wind Harmer
17.244
3145893MURPHYS
Solar/Wind Harmer
0.13
3145893MURPHYS
Solar/Wind Harmer
0.078
3146376EDENTON
Solar/Wind Harmer
0.077
957521AF2-046 GEN
Solar/Wind Harmer
5.761
961681AG1-008 GEN
Solar/Wind Harmer
5.761
3145796HORNRTN
Solar/Wind Harmer
0.309
3145796HORNRTN
Solar/Wind Harmer
0.077
3146173TUNIS
Solar/Wind Harmer
0.077
315614AA2-178 GEN
Solar/Wind Harmer
0.438
316463AE2-346 GEN
Solar/Wind Harmer
0.065
316140AB2-099
Solar/Wind Harmer
0.027
962331AG1-082 GEN
Solar/Wind Harmer
0.812
971157AH1-035 GEN
Solar/Wind Harmer
0.911
3146263WOODLND
Solar/Wind Harmer
0.076
315737AD1-076 GEN
Solar/Wind Harmer
0.975
3146206CASHIE
Solar/Wind Harmer
0.076
3156021HOLLOMANSOL
Solar/Wind Harmer
0.343
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.074
3141906WESTMOR
Solar/Wind Harmer
0.03
3145963POPLR C
Solar/Wind Harmer
0.073
316210AC1-098 GEN
Solar/Wind Harmer
0.67
316478AD1-087 GEN
Solar/Wind Harmer
0.25
316486AD2-202 GEN
Solar/Wind Harmer
0.073
315724AD1-057 GEN
Solar/Wind Harmer
0.268
315773AC2-141 GEN
Solar/Wind Harmer
2.6
3145933PARMELE
Solar/Wind Harmer
0.07
966801AG1-551 GEN
Solar/Wind Harmer
0.814
316327AA2-057 GEN
Solar/Wind Harmer
0.105
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
970737AG2-469 GEN
Solar/Wind Harmer
2.922
3146233WITAKRS
Solar/Wind Harmer
0.341
3146233WITAKRS
Solar/Wind Harmer
0.046
3138543CONSLDL
Solar/Wind Harmer
0.045
3146073TAR RVR
Solar/Wind Harmer
0.067
3146083TARBORO
Solar/Wind Harmer
0.067
970909AG2-566 GEN
Solar/Wind Harmer
0.711
316131AB2-060 GEN
Solar/Wind Harmer
0.21
961601AG1-000A GEN
Solar/Wind Harmer
4.728
971623AH1-311 GEN
Solar/Wind Harmer
0.133
3145543BTLEBRO
Solar/Wind Harmer
0.066
3145543BTLEBRO
Solar/Wind Harmer
0.066
964241AG1-285 GEN
Solar/Wind Harmer
4.421
315785AD2-033 C
Solar/Wind Harmer
0.535
970257AG2-171 GEN
Solar/Wind Harmer
2.097
959311AF2-222 GEN
Solar/Wind Harmer
5.813
963181AG1-167 GEN
Solar/Wind Harmer
0.258
3144293JTRSVLE
Adder
0.205
3147133PAMPLIN
Solar/Wind Harmer
0.201
971193AH1-056 GEN
Solar/Wind Harmer
3.907
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.037
316248AF1-058 C
Solar/Wind Harmer
0
960061AF2-297 GEN
Solar/Wind Harmer
2.481
3146776BUCKING
Solar/Wind Harmer
0.021
3142296MT RD221
50/50
0.861
3142366NRTHEST
50/50
0.692
3150691DARBY 3
50/50
14.366
3150701DARBY 4
50/50
14.333
966871AG1-558 GEN
Solar/Wind Harmer
0.274
3150681DARBY 2
Adder
13.492
3150671DARBY 1
Adder
13.476
316468AD1-105 GEN
Solar/Wind Harmer
-0.061
3143526WINTERP
Solar/Wind Harmer
0.865
944641AF1-129 GEN
Adder
75.607
316240AF1-291 C
Solar/Wind Harmer
0.001
971223AH1-071 GEN
Solar/Wind Harmer
1.64
316075AC2-137 C
Solar/Wind Harmer
0.04
3142946ENON
Solar/Wind Harmer
0.013
316033AB2-134 GEN
Solar/Wind Harmer
0.007
315697AD1-025 GEN
Solar/Wind Harmer
0.133
957411AF2-035 GEN
Solar/Wind Harmer
4.718
970317AG2-208 GEN
Solar/Wind Harmer
4.371
970657AG2-426 GEN
Solar/Wind Harmer
3.848
970657AG2-426 GEN
Solar/Wind Harmer
0.807
3144356SAPONY
Solar/Wind Harmer
0.867
316236AE1-162_GEN
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
2.962
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.908
3150341NORNECKC1
Adder
0.9
972185AH1-677 GEN
Adder
4.724
972187AH1-678 GEN
Adder
2.364
315742AE1-103 GEN
Solar/Wind Harmer
0.001
970933AG2-581 GEN
Solar/Wind Harmer
6.503
316036AC1-147 C
Solar/Wind Harmer
0.015
3150991CHESPKB
Adder
0.847
3150991CHESPKB
Adder
0.827
316316AC1-027 C
Solar/Wind Harmer
0.077
3142956BIRDNECK
Solar/Wind Harmer
0
316181AB2-040 GEN
Solar/Wind Harmer
0.116
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3145506HICKORY
Solar/Wind Harmer
0.316
3145506HICKORY
Solar/Wind Harmer
0.19
3145506HICKORY
Solar/Wind Harmer
0.047
3141726DUNNSVL
Solar/Wind Harmer
0.356
316023GEN1_S
Solar/Wind Harmer
0.196
940641AE2-051 GEN
Solar/Wind Harmer
6.943
3150351NORNECKC2
Adder
0.864
3138126ROCKLANDING
Solar/Wind Harmer
0.039
939411AE1-173 GEN
Solar/Wind Harmer
36.161
971317AH1-138 GEN
Solar/Wind Harmer
0.632
316093AE2-104_GEN
Solar/Wind Harmer
1.417
316072AD1-144
Solar/Wind Harmer
0.03
960081AF2-299 GEN
Solar/Wind Harmer
0.794
316337AD2-073 GEN
Solar/Wind Harmer
0.07
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
1.01
316246AF1-032 C
Solar/Wind Harmer
0.036
970919AG2-571 GEN
Solar/Wind Harmer
2.829
971795AH1-408 GEN
Solar/Wind Harmer
5.291
316011AB1-132 GEN
Solar/Wind Harmer
1.441
962571AG1-106 GEN
Solar/Wind Harmer
1.127
970087AG2-069 GEN
Solar/Wind Harmer
6.336
316388AE2-253 GEN
Solar/Wind Harmer
0.248
3146456SLIGO L269
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.255
3146516WINFALL
Solar/Wind Harmer
0.079
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3147043LAWRENC
Adder
0.704
944591AF1-124 GEN
Solar/Wind Harmer
17.577
3145893MURPHYS
Solar/Wind Harmer
0.311
3145893MURPHYS
Solar/Wind Harmer
0.346
3130156CHOWAN
Solar/Wind Harmer
0.077
3145796HORNRTN
Solar/Wind Harmer
0.255
3145796HORNRTN
Solar/Wind Harmer
0.077
3146173TUNIS
Solar/Wind Harmer
0.077
3145663CRESWEL
Solar/Wind Harmer
0.214
971163AH1-040 GEN
Solar/Wind Harmer
6.129
316190AA2-174 GEN
Solar/Wind Harmer
0
3146263WOODLND
Solar/Wind Harmer
0.076
3145783HORNRTN
Solar/Wind Harmer
0.076
3146206CASHIE
Solar/Wind Harmer
0.076
971547AH1-271 GEN
Solar/Wind Harmer
1.615
3145683EARLEYS
Solar/Wind Harmer
0.076
970937AG2-583 GEN
Solar/Wind Harmer
4.62
957481AF2-042 GEN
Solar/Wind Harmer
19.981
3145823KELFORD
Solar/Wind Harmer
0.074
315693AD1-088 GEN
Solar/Wind Harmer
3.501
3145963POPLR C
Solar/Wind Harmer
0.073
962491AG1-098 GEN
Solar/Wind Harmer
4.143
316212AC1-099_GEN
Solar/Wind Harmer
0.374
316174AB2-169 GEN
Solar/Wind Harmer
0.002
315722AD1-056 GEN
Solar/Wind Harmer
0.452
316294AC1-161 GEN
Solar/Wind Harmer
1.233
316129AC1-054 GEN
Solar/Wind Harmer
0.266
971065AG2-659 GEN
Solar/Wind Harmer
2.995
3146293MARTNCO
Solar/Wind Harmer
0.065
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
3146233WITAKRS
Solar/Wind Harmer
0.27
316494AC1-189 GEN
Solar/Wind Harmer
0.229
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.067
3145493TOT1
Solar/Wind Harmer
0.299
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.002
316359AB2-059 GEN
Solar/Wind Harmer
0.238
316049AB1-081 GEN
Solar/Wind Harmer
0.38
3142053HEARTS
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.066
3145543BTLEBRO
Solar/Wind Harmer
0.053
970685AG2-442 GEN
Solar/Wind Harmer
4.854
963171AG1-166 GEN
Solar/Wind Harmer
0.344
971563AH1-280 GEN
Solar/Wind Harmer
0.688
3144293JTRSVLE
Adder
0.205
972135AH1-637 GEN
Solar/Wind Harmer
0.55
3146926FARMVIL
Solar/Wind Harmer
0.037
970401AG2-262 GEN
Solar/Wind Harmer
0.362
316322AB2-045
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.023
316339AD2-160 GEN
Solar/Wind Harmer
0.128
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.044
3137176SLIGO L2192
Solar/Wind Harmer
0.314
3146456SLIGO L269
Solar/Wind Harmer
1.398
3130086AYDLETT
Solar/Wind Harmer
0.316
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146386ELIZ CT
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3142666NORTHAMPTON
Solar/Wind Harmer
0.079
3142666NORTHAMPTON
Solar/Wind Harmer
0.079
3142666NORTHAMPTON
Solar/Wind Harmer
0.079
3142666NORTHAMPTON
Solar/Wind Harmer
0.047
315673AE1-157 GEN
Solar/Wind Harmer
5.44
3146626S HERTFORD
Solar/Wind Harmer
0.078
3146626S HERTFORD
Solar/Wind Harmer
0.078
3145893MURPHYS
Solar/Wind Harmer
0.52
3145893MURPHYS
Solar/Wind Harmer
0.14
3146376EDENTON
Solar/Wind Harmer
0.345
3146376EDENTON
Solar/Wind Harmer
0.345
3145796HORNRTN
Solar/Wind Harmer
0.232
3146173TUNIS
Solar/Wind Harmer
0.077
3146173TUNIS
Solar/Wind Harmer
0.077
3145593CAROLNA
Solar/Wind Harmer
0.076
3145593CAROLNA
Solar/Wind Harmer
0.076
966811AG1-552 GEN
Solar/Wind Harmer
0.829
3145593CAROLNA
Solar/Wind Harmer
0.095
316426AA2-053 GEN
Solar/Wind Harmer
0.258
3145783HORNRTN
Solar/Wind Harmer
1.347
3145783HORNRTN
Solar/Wind Harmer
1.078
3145783HORNRTN
Solar/Wind Harmer
0.337
3145783HORNRTN
Solar/Wind Harmer
0.135
316065AD1-022 GEN
Solar/Wind Harmer
3.486
970099AG2-077 GEN
Solar/Wind Harmer
7.992
316274AC1-208 GEN
Solar/Wind Harmer
0.374
3145933PARMELE
Solar/Wind Harmer
0.14
3145933PARMELE
Solar/Wind Harmer
0.07
971741AH1-377 GEN
Solar/Wind Harmer
6.756
939181AE1-148 GEN
Solar/Wind Harmer
3.239
3145493TOT1
Solar/Wind Harmer
0.156
3145453TOT5
Solar/Wind Harmer
0.093
3145603CNETO
Solar/Wind Harmer
0.062
313527AB2-043 GEN
Solar/Wind Harmer
0.001
970301AG2-198 GEN
Solar/Wind Harmer
2.845
961601AG1-000A GEN
Solar/Wind Harmer
1.182
316263AC1-034 GEN
Solar/Wind Harmer
2.522
970323AG2-213 GEN
Solar/Wind Harmer
2.797
971775AH1-396 GEN
Solar/Wind Harmer
0.105
316034AC1-036 C
Solar/Wind Harmer
0.005
958211AF2-115 GEN
Solar/Wind Harmer
0.774
963191AG1-168 GEN
Solar/Wind Harmer
0.258
3144293JTRSVLE
Adder
0.205
3144293JTRSVLE
Adder
0.173
3147133PAMPLIN
Solar/Wind Harmer
0.064
3147133PAMPLIN
Solar/Wind Harmer
0.051
962561AG1-105 GEN
Solar/Wind Harmer
3.001
964791AG1-342 GEN
Solar/Wind Harmer
1.186
3146843MT LREL
Solar/Wind Harmer
0.062
3146843MT LREL
Solar/Wind Harmer
0.062
3146776BUCKING
Solar/Wind Harmer
0.23
3146776BUCKING
Solar/Wind Harmer
0.019
972189AH1-679 GEN
50/50
3.737
316312AB1-027
Solar/Wind Harmer
0.364
971285AH1-108 GEN
Adder
1.314
316233AE1-074 FULL
Solar/Wind Harmer
0.133
971281AH1-106 GEN
Solar/Wind Harmer
2.308
971283AH1-107 GEN
Solar/Wind Harmer
2.308
316132AB2-190 GEN1
Solar/Wind Harmer
0.689
3143316POE
Solar/Wind Harmer
0.507
971167AH1-042 GEN
Solar/Wind Harmer
11.268
3142433PROV 92
Adder
0.24
3142433PROV 92
Adder
0.24
316369SG1_INVT
Solar/Wind Harmer
0.004
315976AC1-164 GENA
Solar/Wind Harmer
11.827
316169AC1-164_GENC
Solar/Wind Harmer
10.217
315975AC1-164 GENB
Solar/Wind Harmer
0.35
3143873LANEXA
Solar/Wind Harmer
0.065
316315AB2-025 C
Solar/Wind Harmer
0.084
315814AE2-033 C
Solar/Wind Harmer
8.13
970189AG2-124 GEN
Solar/Wind Harmer
3.018
316314AB2-024 C
Solar/Wind Harmer
0
972265AH1-717 GEN
Adder
7.823
3151201GRAVEL4
Adder
7.333
3151191GRAVEL3
Adder
7.241
3151211GRAVEL5
Adder
7.241
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.019
3141913WHIT STONE
Solar/Wind Harmer
0.095
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.065
3138133OCRAN
Solar/Wind Harmer
0.028
316311AC2-079 GEN
Solar/Wind Harmer
2.717
3141783LANCAST
Solar/Wind Harmer
0.056
3141783LANCAST
Solar/Wind Harmer
0.038
971445AH1-216 GEN
Solar/Wind Harmer
6.604
962981AG1-147 GEN
Solar/Wind Harmer
3.442
970327AG2-215 GEN
Solar/Wind Harmer
2.993
3138283WHITEMARSH
Solar/Wind Harmer
0.021
941031AE2-094 GEN
Solar/Wind Harmer
15.988
944011AF1-069 GEN
Solar/Wind Harmer
5.224
3141813NORNECK
Solar/Wind Harmer
0.087
970673AG2-436 GEN
Solar/Wind Harmer
18.147
970673AG2-436 GEN
Solar/Wind Harmer
12.098
315835AF2-110_GEN
Solar/Wind Harmer
0.578
971967AH1-528 GEN
Solar/Wind Harmer
13.399
3152611GOSPORTB
Adder
1.03
3152621GOSPORTC
Adder
0.874
3152601GOSPORTA
Adder
0.807
316305AF2-043 C
Solar/Wind Harmer
0.001
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3151081ELIZAR1
Adder
7.379
3151091ELIZAR2
Adder
7.251
3146486SUNBURY
Solar/Wind Harmer
0.08
3146486SUNBURY
Solar/Wind Harmer
0.08
315652AC1-086 GEN
Solar/Wind Harmer
8.716
970085AG2-068 GEN
Solar/Wind Harmer
4.224
970581AG2-369 GEN
Solar/Wind Harmer
3.632
957871AF2-081 GEN
Solar/Wind Harmer
3.937
319010AE1-072 C
Solar/Wind Harmer
0.398
3146406KITTY HAWK
Solar/Wind Harmer
0.01
313526AB2-022
Solar/Wind Harmer
0.043
316321Z2-027
Solar/Wind Harmer
0.015
3145176PASQUOTANK
Solar/Wind Harmer
0.049
3146396TANGLEW
Solar/Wind Harmer
0.217
965291AG1-394 GEN
Solar/Wind Harmer
0.35
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3137643SOCKMAN
Solar/Wind Harmer
0.311
3145893MURPHYS
Solar/Wind Harmer
0.21
3145893MURPHYS
Solar/Wind Harmer
0.078
3130156CHOWAN
Solar/Wind Harmer
0.077
3130156CHOWAN
Solar/Wind Harmer
0.077
3146043SEABORD
Solar/Wind Harmer
0.077
3145796HORNRTN
Solar/Wind Harmer
0.248
3145796HORNRTN
Solar/Wind Harmer
0.031
315607AA1-063A GEN
Solar/Wind Harmer
0.158
315816AE2-034 GEN
Solar/Wind Harmer
0.329
3145513AHOSKIE
Solar/Wind Harmer
0.159
3145513AHOSKIE
Solar/Wind Harmer
0.076
3130546PLYMOUTH
Solar/Wind Harmer
0.076
315732AD1-074 GEN1
Solar/Wind Harmer
0.435
315733AD1-074 GEN2
Solar/Wind Harmer
0.435
315735AD1-075 GEN1
Solar/Wind Harmer
0.218
3146206CASHIE
Solar/Wind Harmer
0.076
970601AG2-382 GEN
Solar/Wind Harmer
2.825
3145683EARLEYS
Solar/Wind Harmer
0.151
3145683EARLEYS
Solar/Wind Harmer
0.076
3145683EARLEYS
Solar/Wind Harmer
0.076
316223AC1-118
Solar/Wind Harmer
0.054
3146033SCOT NK
Solar/Wind Harmer
0.293
970831AG2-522 GEN
Solar/Wind Harmer
3.041
316005AA1-067
Solar/Wind Harmer
0.074
3145746EVERETS
Solar/Wind Harmer
0.273
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
970181AG2-120 GEN
Solar/Wind Harmer
0.854
316319Z2-044 C
Solar/Wind Harmer
0
957861AF2-080 GEN
Solar/Wind Harmer
2.926
316420AA1-050 GEN
Solar/Wind Harmer
0.002
3145573BETHELC
Solar/Wind Harmer
0.067
3145573BETHELC
Solar/Wind Harmer
0.067
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
1.102
3144303KENBRDG
Solar/Wind Harmer
0.052
970683AG2-441 GEN
Solar/Wind Harmer
4.334
970681AG2-440 GEN
Solar/Wind Harmer
3.467
946301AF1-294 GEN
Solar/Wind Harmer
1.273
961791AG1-021 GEN
Solar/Wind Harmer
0.619
315657AE1-056 GEN
Solar/Wind Harmer
2.213
316118AC1-105 GEN
Solar/Wind Harmer
0.155
944491AF1-114 GEN
Solar/Wind Harmer
0
970285AG2-188 GEN
Solar/Wind Harmer
4.645
3147173SINAI
Solar/Wind Harmer
0.058
3147243WELCO
Solar/Wind Harmer
0.036
971845AH1-439 GEN
Solar/Wind Harmer
2.629
LAGNLTFEXP_LAGN->PJM
CLTF
1.981
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.934
TVALTFEXP_TVA->PJM
CLTF
0.982
NYPJM->LTFIMP_NY
CLTF
0.725
LGEELTFEXP_LGEE->PJM
CLTF
0.184
WECLTFEXP_WEC->PJM
CLTF
0.088
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.603
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.205
MECLTFEXP_MEC->PJM
CLTF
0.637
SIGELTFEXP_SIGE->PJM
CLTF
0.018
CPLELTFEXP_CPLE->PJM
CLTF
3.909
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.118

Details for 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FINES-6FREDBRG 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.73 %
Rating:548.02 MVA
Rating Type:B
MVA to Mitigate:760.24
MW Contribution:7.19
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
2.956
966661AG1-536 GEN
50/50
6.849
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
971353AH1-157 GEN
50/50
7.408
970017AG2-010 GEN
50/50
4.699
3150641CHESTS8
50/50
0.203
944631AF1-128 GEN
50/50
31.925
972135AH1-637 GEN
Solar/Wind Harmer
4.389
316337AD2-073 GEN
Solar/Wind Harmer
0.299
3141726DUNNSVL
Solar/Wind Harmer
1.044
962861AG1-135 GEN
Solar/Wind Harmer
7.523
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
971317AH1-138 GEN
Solar/Wind Harmer
0.613
316159AE1-175 C
Solar/Wind Harmer
0.065
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3142416OLDCHRC
Solar/Wind Harmer
0.149
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.6
957191AF2-013 GEN
50/50
65.713
3150341NORNECKC1
50/50
3.105
3150341NORNECKC1
50/50
3.08
963611AG1-210 GEN
50/50
0.994
3150621CHESTS7
50/50
0.184
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
7.962
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.007
315759AF1-018 GEN
50/50
4.946
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150611CHESTG7
50/50
0.401
3150631CHESTG8
50/50
0.394
971047AG2-646 GEN
50/50
11.221
972263AH1-716 GEN
50/50
32.871
944491AF1-114 GEN
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Harmer
0.296
3141813NORNECK
Solar/Wind Harmer
0.279
970327AG2-215 GEN
Solar/Wind Harmer
7.194
962981AG1-147 GEN
Solar/Wind Harmer
7.685
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.051
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
0.029
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.081
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
9.122
315976AC1-164 GENA
Solar/Wind Harmer
8.292
316169AC1-164_GENC
Solar/Wind Harmer
7.163
315975AC1-164 GENB
Solar/Wind Harmer
0.245
316312AB1-027
Solar/Wind Harmer
0.102
972265AH1-717 GEN
Adder
4.377
3151201GRAVEL4
Adder
4.104
3151191GRAVEL3
Adder
4.052
3151211GRAVEL5
Adder
4.052
3141426STAFORD
Solar/Wind Helper
0.031
3150331BIRCHWDA
50/50
158.356
3141316ARNOLDS
50/50
2.018
3150351NORNECKC2
50/50
3.006
970575AG2-366 GEN
50/50
3.66
315749AE2-041 GEN
50/50
4.946
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150921YORKTN3
50/50
1.929
3144216WINCHST
50/50
0.279
3151161SURRY 1
50/50
2.166
970737AG2-469 GEN
Solar/Wind Harmer
20.178
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.637
962971AG1-146 GEN
Solar/Wind Harmer
3.294
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.61
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.855
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.668
3142416OLDCHRC
Solar/Wind Harmer
0.555
3151221GRAVEL6
Adder
4.099
3151171GRAVELC
Adder
0.789
LAGNLTFEXP_LAGN->PJM
CLTF
1.483
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.388
TVALTFEXP_TVA->PJM
CLTF
0.749
NYPJM->LTFIMP_NY
CLTF
0.564
LGEELTFEXP_LGEE->PJM
CLTF
0.274
WECLTFEXP_WEC->PJM
CLTF
0.137
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.711
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.577
MECLTFEXP_MEC->PJM
CLTF
0.732
SIGELTFEXP_SIGE->PJM
CLTF
0.022
CPLELTFEXP_CPLE->PJM
CLTF
1.997
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.895

Details for 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FINES-6FREDBRG 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.84 %
Rating:548.02 MVA
Rating Type:B
MVA to Mitigate:656.73
MW Contribution:7.23
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
4.976
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
972263AH1-716 GEN
50/50
35.649
3150611CHESTG7
50/50
0.379
3150631CHESTG8
50/50
0.372
971047AG2-646 GEN
50/50
10.599
944491AF1-114 GEN
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Harmer
0.297
3141813NORNECK
Solar/Wind Harmer
0.28
970327AG2-215 GEN
Solar/Wind Harmer
7.232
962981AG1-147 GEN
Solar/Wind Harmer
7.729
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.074
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.168
3141873WAN 176
Solar/Wind Harmer
0.03
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.097
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
8.942
315976AC1-164 GENA
Solar/Wind Harmer
8.275
316169AC1-164_GENC
Solar/Wind Harmer
7.149
315975AC1-164 GENB
Solar/Wind Harmer
0.245
972265AH1-717 GEN
Adder
4.429
3151201GRAVEL4
Adder
4.152
3151191GRAVEL3
Adder
4.099
3151211GRAVEL5
Adder
4.099
3141426STAFORD
Solar/Wind Helper
0.029
3150331BIRCHWDA
50/50
158.961
3141316ARNOLDS
50/50
2.026
3150351NORNECKC2
50/50
3.02
970575AG2-366 GEN
50/50
3.68
315749AE2-041 GEN
50/50
4.976
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
3150921YORKTN3
50/50
2.003
3144216WINCHST
50/50
0.289
3151161SURRY 1
50/50
2.191
970737AG2-469 GEN
Solar/Wind Harmer
20.26
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.646
962971AG1-146 GEN
Solar/Wind Harmer
3.312
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.629
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.866
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.022
3151221GRAVEL6
Adder
4.147
3151171GRAVELC
Adder
0.798
970293AG2-193 GEN
Solar/Wind Harmer
0.603
3150351NORNECKC2
50/50
2.97
966661AG1-536 GEN
50/50
6.884
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
971353AH1-157 GEN
50/50
7.642
970017AG2-010 GEN
50/50
4.875
3150641CHESTS8
50/50
0.192
944631AF1-128 GEN
50/50
30.156
3152331SURRY 2
50/50
2.455
972135AH1-637 GEN
Solar/Wind Harmer
4.407
316337AD2-073 GEN
Solar/Wind Harmer
0.3
3141726DUNNSVL
Solar/Wind Harmer
1.049
962861AG1-135 GEN
Solar/Wind Harmer
7.561
3138133OCRAN
Solar/Wind Harmer
0.104
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.365
3142433PROV 92
Solar/Wind Harmer
0.422
971317AH1-138 GEN
Solar/Wind Harmer
0.633
316159AE1-175 C
Solar/Wind Harmer
0.067
3138126ROCKLANDING
Solar/Wind Harmer
0.034
3151171GRAVELC
Adder
0.607
957191AF2-013 GEN
50/50
65.968
3150341NORNECKC1
50/50
3.119
3150341NORNECKC1
50/50
3.094
963611AG1-210 GEN
50/50
0.998
3150621CHESTS7
50/50
0.174
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
8.003
316075AC2-137 C
Solar/Wind Harmer
0.018
3142946ENON
Solar/Wind Harmer
0.007
LAGNLTFEXP_LAGN->PJM
CLTF
1.213
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.047
TVALTFEXP_TVA->PJM
CLTF
0.609
NYPJM->LTFIMP_NY
CLTF
0.465
LGEELTFEXP_LGEE->PJM
CLTF
0.185
WECLTFEXP_WEC->PJM
CLTF
0.092
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.061
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.057
MECLTFEXP_MEC->PJM
CLTF
0.525
SIGELTFEXP_SIGE->PJM
CLTF
0.016
CPLELTFEXP_CPLE->PJM
CLTF
1.912
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.152

Details for 6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FOUR RIVERS-6STJOHN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:178.97 %
Rating:1123.3 MVA
Rating Type:B
MVA to Mitigate:2010.34
MW Contribution:2.8
Bus #Bus NameTypeMW Contribution
315052AA1-145 CT2
50/50
2.931
3142416OLDCHRC
Solar/Wind Harmer
0.42
3142416OLDCHRC
Solar/Wind Harmer
0.161
3143096IRON208
Adder
0.565
3142543TWELFTH
Solar/Wind Harmer
0.013
944631AF1-128 GEN
Adder
61.103
3150851SPRUNCC
Adder
0.591
315671AE2-027_GEN
Solar/Wind Harmer
7.597
970129AG2-093 GEN
Solar/Wind Harmer
3.332
316458AB2-190 GEN2
Solar/Wind Harmer
0.626
3142433PROV 92
Solar/Wind Harmer
0.461
3142433PROV 92
Adder
0.224
3142433PROV 92
Adder
0.224
971069AG2-661 GEN
Solar/Wind Harmer
2.028
3143526WINTERP
Solar/Wind Harmer
0.586
316159AE1-175 C
Solar/Wind Harmer
0.096
971647AH1-324 GEN
Solar/Wind Harmer
4.693
961611AG1-000B GEN
Solar/Wind Harmer
5.648
3151171GRAVELC
Adder
1.115
971317AH1-138 GEN
Solar/Wind Harmer
0.78
3141766HARMONY
Solar/Wind Harmer
0.021
971777AH1-397 GEN
Solar/Wind Harmer
0.275
3141843SHACKLE
Adder
0.533
3138126ROCKLANDING
Solar/Wind Harmer
0.047
970659AG2-427 GEN
Solar/Wind Harmer
4.993
316381AD1-082 GEN
Solar/Wind Harmer
0.107
970661AG2-428 GEN
Solar/Wind Harmer
10.035
3145336SMITFLD
Solar/Wind Harmer
0.403
3143226MDLTHAN
Solar/Wind Harmer
0.096
316072AD1-144
Solar/Wind Harmer
0.034
3138133OCRAN
Solar/Wind Harmer
0.057
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
1.175
316294AC1-161 GEN
Solar/Wind Harmer
1.613
316093AE2-104_GEN
Solar/Wind Harmer
1.56
944591AF1-124 GEN
Solar/Wind Harmer
20.951
316388AE2-253 GEN
Solar/Wind Harmer
0.289
316246AF1-032 C
Solar/Wind Harmer
0.042
3146456SLIGO L269
Solar/Wind Harmer
0.092
3146516WINFALL
Solar/Wind Harmer
0.29
3146516WINFALL
Solar/Wind Harmer
0.09
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.087
3145663CRESWEL
Solar/Wind Harmer
0.236
971163AH1-040 GEN
Solar/Wind Harmer
6.739
962861AG1-135 GEN
Solar/Wind Harmer
2.62
939411AE1-173 GEN
Solar/Wind Harmer
34.862
3146206CASHIE
Solar/Wind Harmer
0.081
971547AH1-271 GEN
Solar/Wind Harmer
1.728
972277AH1-723 GEN
Adder
48.257
3145893MURPHYS
Solar/Wind Harmer
0.322
3145893MURPHYS
Solar/Wind Harmer
0.358
316023GEN1_S
Solar/Wind Harmer
0.18
3143336POWHATN
Solar/Wind Harmer
1.419
3146173TUNIS
Solar/Wind Harmer
0.079
3145683EARLEYS
Solar/Wind Harmer
0.078
940641AE2-051 GEN
Solar/Wind Harmer
6.242
3146263WOODLND
Solar/Wind Harmer
0.077
3141726DUNNSVL
Solar/Wind Harmer
0.309
3145963POPLR C
Solar/Wind Harmer
0.077
960081AF2-299 GEN
Solar/Wind Harmer
0.738
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145823KELFORD
Solar/Wind Harmer
0.076
316011AB1-132 GEN
Solar/Wind Harmer
1.386
962571AG1-106 GEN
Solar/Wind Harmer
1.085
316336AC2-165 C
Solar/Wind Harmer
0.003
316190AA2-174 GEN
Solar/Wind Harmer
0
3145796HORNRTN
Solar/Wind Harmer
0.247
3145796HORNRTN
Solar/Wind Harmer
0.075
3145783HORNRTN
Solar/Wind Harmer
0.074
971795AH1-408 GEN
Solar/Wind Harmer
4.942
3146293MARTNCO
Solar/Wind Harmer
0.068
3147043LAWRENC
Adder
0.659
316212AC1-099_GEN
Solar/Wind Harmer
0.376
3150351NORNECKC2
Adder
0.724
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
315722AD1-056 GEN
Solar/Wind Harmer
0.445
316494AC1-189 GEN
Solar/Wind Harmer
0.235
970919AG2-571 GEN
Solar/Wind Harmer
2.438
970087AG2-069 GEN
Solar/Wind Harmer
5.469
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.068
3145493TOT1
Solar/Wind Harmer
0.303
316129AC1-054 GEN
Solar/Wind Harmer
0.256
3146233WITAKRS
Solar/Wind Harmer
0.271
971065AG2-659 GEN
Solar/Wind Harmer
2.883
316359AB2-059 GEN
Solar/Wind Harmer
0.239
316049AB1-081 GEN
Solar/Wind Harmer
0.381
3145543BTLEBRO
Solar/Wind Harmer
0.066
3145543BTLEBRO
Solar/Wind Harmer
0.053
3142053HEARTS
Solar/Wind Harmer
0.117
957481AF2-042 GEN
Solar/Wind Harmer
17.725
315693AD1-088 GEN
Solar/Wind Harmer
3.146
962491AG1-098 GEN
Solar/Wind Harmer
3.732
970937AG2-583 GEN
Solar/Wind Harmer
3.951
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970685AG2-442 GEN
Solar/Wind Harmer
4.658
963171AG1-166 GEN
Solar/Wind Harmer
0.331
971563AH1-280 GEN
Solar/Wind Harmer
0.661
3144293JTRSVLE
Adder
0.197
315687AD1-152 GEN
Solar/Wind Harmer
0.002
3146926FARMVIL
Solar/Wind Harmer
0.036
970401AG2-262 GEN
Solar/Wind Harmer
0.353
316337AD2-073 GEN
Solar/Wind Harmer
0.051
316322AB2-045
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.023
3142296MT RD221
50/50
0.609
3142366NRTHEST
50/50
0.528
3150691DARBY 3
50/50
11.381
3150701DARBY 4
50/50
11.355
3150681DARBY 2
50/50
11.341
966871AG1-558 GEN
Solar/Wind Harmer
0.187
3150671DARBY 1
Adder
10.676
316075AC2-137 C
Solar/Wind Harmer
0.038
3142946ENON
Solar/Wind Harmer
0.013
944641AF1-129 GEN
Adder
59.909
316240AF1-291 C
Solar/Wind Harmer
0.001
3143526WINTERP
Solar/Wind Harmer
0.586
316033AB2-134 GEN
Solar/Wind Harmer
0.007
315697AD1-025 GEN
Solar/Wind Harmer
0.126
316468AD1-105 GEN
Solar/Wind Harmer
-0.033
970657AG2-426 GEN
Solar/Wind Harmer
3.572
970657AG2-426 GEN
Solar/Wind Harmer
0.749
316236AE1-162_GEN
Solar/Wind Harmer
0.001
971223AH1-071 GEN
Solar/Wind Harmer
1.028
316036AC1-147 C
Solar/Wind Harmer
0.017
3150991CHESPKB
Adder
0.986
3150991CHESPKB
Adder
0.962
316316AC1-027 C
Solar/Wind Harmer
0.09
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.003
3145506HICKORY
Solar/Wind Harmer
0.371
3145506HICKORY
Solar/Wind Harmer
0.222
3145506HICKORY
Solar/Wind Harmer
0.056
316339AD2-160 GEN
Solar/Wind Harmer
0.15
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.052
3137176SLIGO L2192
Solar/Wind Harmer
0.366
3146456SLIGO L269
Solar/Wind Harmer
1.629
3130086AYDLETT
Solar/Wind Harmer
0.367
3146386ELIZ CT
Solar/Wind Harmer
0.091
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.09
3146516WINFALL
Solar/Wind Harmer
0.09
3146516WINFALL
Solar/Wind Harmer
0.09
3146626S HERTFORD
Solar/Wind Harmer
0.089
3146626S HERTFORD
Solar/Wind Harmer
0.089
3144356SAPONY
Solar/Wind Harmer
0.735
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.385
3146376EDENTON
Solar/Wind Harmer
0.385
316065AD1-022 GEN
Solar/Wind Harmer
3.747
958261AF2-120 GEN
Solar/Wind Harmer
2.668
3145893MURPHYS
Solar/Wind Harmer
0.538
3145893MURPHYS
Solar/Wind Harmer
0.145
3146173TUNIS
Solar/Wind Harmer
0.079
3146173TUNIS
Solar/Wind Harmer
0.079
3142666NORTHAMPTON
Solar/Wind Harmer
0.077
3142666NORTHAMPTON
Solar/Wind Harmer
0.077
3142666NORTHAMPTON
Solar/Wind Harmer
0.077
3142666NORTHAMPTON
Solar/Wind Harmer
0.046
316181AB2-040 GEN
Solar/Wind Harmer
0.11
316426AA2-053 GEN
Solar/Wind Harmer
0.255
3145796HORNRTN
Solar/Wind Harmer
0.224
3145593CAROLNA
Solar/Wind Harmer
0.075
3145593CAROLNA
Solar/Wind Harmer
0.075
966811AG1-552 GEN
Solar/Wind Harmer
0.812
3145593CAROLNA
Solar/Wind Harmer
0.093
3145783HORNRTN
Solar/Wind Harmer
1.322
3145783HORNRTN
Solar/Wind Harmer
1.058
3145783HORNRTN
Solar/Wind Harmer
0.331
3145783HORNRTN
Solar/Wind Harmer
0.132
3145933PARMELE
Solar/Wind Harmer
0.146
3145933PARMELE
Solar/Wind Harmer
0.073
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.76
3150341NORNECKC1
Adder
0.754
316274AC1-208 GEN
Solar/Wind Harmer
0.373
972185AH1-677 GEN
Adder
3.996
972187AH1-678 GEN
Adder
2.009
970933AG2-581 GEN
Solar/Wind Harmer
5.582
3145493TOT1
Solar/Wind Harmer
0.158
3145453TOT5
Solar/Wind Harmer
0.095
3145603CNETO
Solar/Wind Harmer
0.063
961601AG1-000A GEN
Solar/Wind Harmer
1.184
316263AC1-034 GEN
Solar/Wind Harmer
2.527
970099AG2-077 GEN
Solar/Wind Harmer
7.09
972189AH1-679 GEN
50/50
6.542
316312AB1-027
Solar/Wind Harmer
0.289
971285AH1-108 GEN
Adder
0.966
315976AC1-164 GENA
Solar/Wind Harmer
13.079
316169AC1-164_GENC
Solar/Wind Harmer
11.299
315975AC1-164 GENB
Solar/Wind Harmer
0.387
971167AH1-042 GEN
Solar/Wind Harmer
10.37
316132AB2-190 GEN1
Solar/Wind Harmer
0.626
3142433PROV 92
Adder
0.224
3142433PROV 92
Adder
0.224
316233AE1-074 FULL
Solar/Wind Harmer
0.09
971281AH1-106 GEN
Solar/Wind Harmer
1.563
971283AH1-107 GEN
Solar/Wind Harmer
1.563
316369SG1_INVT
Solar/Wind Harmer
0.004
3143873LANEXA
Solar/Wind Harmer
0.066
316314AB2-024 C
Solar/Wind Harmer
0
3143316POE
Solar/Wind Harmer
0.415
972265AH1-717 GEN
Adder
8.137
3151201GRAVEL4
Adder
7.628
3151191GRAVEL3
Adder
7.532
3151211GRAVEL5
Adder
7.532
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
3.088
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3138283WHITEMARSH
Solar/Wind Harmer
0.024
971445AH1-216 GEN
Solar/Wind Harmer
7.118
3141873WAN 176
Solar/Wind Harmer
0.02
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.066
316311AC2-079 GEN
Solar/Wind Harmer
2.771
3141913WHIT STONE
Solar/Wind Harmer
0.096
3138133OCRAN
Solar/Wind Harmer
0.029
3152611GOSPORTB
Adder
1.199
3152621GOSPORTC
Adder
1.017
3152601GOSPORTA
Adder
0.939
3151081ELIZAR1
Adder
8.616
3151091ELIZAR2
Adder
8.466
3141783LANCAST
Solar/Wind Harmer
0.056
3141783LANCAST
Solar/Wind Harmer
0.037
315835AF2-110_GEN
Solar/Wind Harmer
0.637
316305AF2-043 C
Solar/Wind Harmer
0.001
957871AF2-081 GEN
Solar/Wind Harmer
4.593
319010AE1-072 C
Solar/Wind Harmer
0.463
3146406KITTY HAWK
Solar/Wind Harmer
0.011
313526AB2-022
Solar/Wind Harmer
0.049
3146486SUNBURY
Solar/Wind Harmer
0.091
3146486SUNBURY
Solar/Wind Harmer
0.091
316321Z2-027
Solar/Wind Harmer
0.017
3145176PASQUOTANK
Solar/Wind Harmer
0.056
3146396TANGLEW
Solar/Wind Harmer
0.249
962981AG1-147 GEN
Solar/Wind Harmer
3.285
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
316315AB2-025 C
Solar/Wind Harmer
0.071
315814AE2-033 C
Solar/Wind Harmer
6.922
3130156CHOWAN
Solar/Wind Harmer
0.087
3130156CHOWAN
Solar/Wind Harmer
0.087
970327AG2-215 GEN
Solar/Wind Harmer
2.796
315816AE2-034 GEN
Solar/Wind Harmer
0.361
3130546PLYMOUTH
Solar/Wind Harmer
0.082
315732AD1-074 GEN1
Solar/Wind Harmer
0.472
315733AD1-074 GEN2
Solar/Wind Harmer
0.472
315735AD1-075 GEN1
Solar/Wind Harmer
0.236
965291AG1-394 GEN
Solar/Wind Harmer
0.362
3146206CASHIE
Solar/Wind Harmer
0.081
970601AG2-382 GEN
Solar/Wind Harmer
3.023
972193AH1-681 GEN
Adder
1.85
3145893MURPHYS
Solar/Wind Harmer
0.217
3145893MURPHYS
Solar/Wind Harmer
0.08
3145513AHOSKIE
Solar/Wind Harmer
0.165
3145513AHOSKIE
Solar/Wind Harmer
0.079
3145683EARLEYS
Solar/Wind Harmer
0.157
3145683EARLEYS
Solar/Wind Harmer
0.078
3145683EARLEYS
Solar/Wind Harmer
0.078
3146043SEABORD
Solar/Wind Harmer
0.078
315607AA1-063A GEN
Solar/Wind Harmer
0.158
315652AC1-086 GEN
Solar/Wind Harmer
8.385
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.301
3145796HORNRTN
Solar/Wind Harmer
0.239
3145796HORNRTN
Solar/Wind Harmer
0.03
3146033SCOT NK
Solar/Wind Harmer
0.297
941031AE2-094 GEN
Solar/Wind Harmer
13.383
944011AF1-069 GEN
Solar/Wind Harmer
4.373
3141813NORNECK
Solar/Wind Harmer
0.073
970673AG2-436 GEN
Solar/Wind Harmer
15.295
970673AG2-436 GEN
Solar/Wind Harmer
10.197
316005AA1-067
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.283
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
970181AG2-120 GEN
Solar/Wind Harmer
0.886
971967AH1-528 GEN
Solar/Wind Harmer
11.367
957861AF2-080 GEN
Solar/Wind Harmer
3.002
316420AA1-050 GEN
Solar/Wind Harmer
0.002
970831AG2-522 GEN
Solar/Wind Harmer
2.936
970085AG2-068 GEN
Solar/Wind Harmer
3.646
970581AG2-369 GEN
Solar/Wind Harmer
3.135
3145573BETHELC
Solar/Wind Harmer
0.068
3145573BETHELC
Solar/Wind Harmer
0.068
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
1.056
3144303KENBRDG
Solar/Wind Harmer
0.05
970683AG2-441 GEN
Solar/Wind Harmer
4.159
970681AG2-440 GEN
Solar/Wind Harmer
3.327
946301AF1-294 GEN
Solar/Wind Harmer
1.224
961791AG1-021 GEN
Solar/Wind Harmer
0.595
315657AE1-056 GEN
Solar/Wind Harmer
2.129
316118AC1-105 GEN
Solar/Wind Harmer
0.152
970285AG2-188 GEN
Solar/Wind Harmer
4.619
971845AH1-439 GEN
Solar/Wind Harmer
2.63
3147173SINAI
Solar/Wind Harmer
0.057
3147243WELCO
Solar/Wind Harmer
0.036
3141426STAFORD
Solar/Wind Helper
0.036
315051AA1-145 CT1
50/50
2.918
971645AH1-323 GEN
50/50
16.835
316473AC1-191 GEN
Solar/Wind Harmer
0.548
3142416OLDCHRC
Solar/Wind Harmer
1.565
970293AG2-193 GEN
Solar/Wind Harmer
1.529
3143096IRON208
Adder
0.565
3143096IRON208
Adder
0.554
3150861SPRUNCD
Adder
0.591
3142946ENON
Solar/Wind Harmer
0.043
970133AG2-095 GEN
Solar/Wind Harmer
1.166
970129AG2-093 GEN
Solar/Wind Harmer
7.081
965281AG1-393 GEN
Solar/Wind Harmer
1.248
315839AE2-212 C
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.224
3142433PROV 92
Adder
0.224
315778AD1-151 GEN
Solar/Wind Harmer
9.127
316382AG1-145 C
Solar/Wind Harmer
0.001
961611AG1-000B GEN
Solar/Wind Harmer
2.872
315813AE1-149 C
Solar/Wind Harmer
5.679
3151221GRAVEL6
Adder
7.62
3151171GRAVELC
Adder
1.466
3141766HARMONY
Solar/Wind Harmer
1.39
3141843SHACKLE
Adder
0.533
316203AE2-005 GEN
Solar/Wind Harmer
0
3144216WINCHST
Adder
0.391
3150921YORKTN3
Adder
2.597
970659AG2-427 GEN
Solar/Wind Harmer
1.092
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.002
971781AH1-399 GEN
Solar/Wind Harmer
0.134
970661AG2-428 GEN
Solar/Wind Harmer
2.134
3145336SMITFLD
Solar/Wind Harmer
0.04
316156AD2-030 GEN
Solar/Wind Harmer
0.074
3141873WAN 176
Solar/Wind Harmer
1.784
3144536CHRHLND
Solar/Wind Harmer
0.014
3144873MCLAUGH
Solar/Wind Harmer
0.002
3151101ELIZAR3
Adder
8.726
315773AC2-141 GEN
Solar/Wind Harmer
3.399
944581AF1-123 GEN
Solar/Wind Harmer
20.877
944601AF1-125 GEN
Solar/Wind Harmer
20.555
3146456SLIGO L269
Solar/Wind Harmer
0.092
971153AH1-033 GEN
Solar/Wind Harmer
1.064
316320Y1-086
Solar/Wind Harmer
0
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.09
3145273HOLLAND
Solar/Wind Harmer
0.067
3146626S HERTFORD
Solar/Wind Harmer
0.089
962971AG1-146 GEN
Solar/Wind Harmer
1.408
3146376EDENTON
Solar/Wind Harmer
0.087
970009AG2-005 GEN
Solar/Wind Harmer
0.636
315614AA2-178 GEN
Solar/Wind Harmer
0.482
971157AH1-035 GEN
Solar/Wind Harmer
0.989
315737AD1-076 GEN
Solar/Wind Harmer
1.056
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146206CASHIE
Solar/Wind Harmer
0.081
972255AH1-712 GEN
Adder
41.412
316404AE1-155 C
Solar/Wind Harmer
0.018
3145893MURPHYS
Solar/Wind Harmer
0.135
3145893MURPHYS
Solar/Wind Harmer
0.08
957521AF2-046 GEN
Solar/Wind Harmer
5.964
961681AG1-008 GEN
Solar/Wind Harmer
5.964
316365GEN2_N
Solar/Wind Harmer
0.18
316313AB2-026
Solar/Wind Harmer
0.05
316258AE1-075 C
Solar/Wind Harmer
0.06
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
1.206
3146173TUNIS
Solar/Wind Harmer
0.079
3156021HOLLOMANSOL
Solar/Wind Harmer
0.361
316463AE2-346 GEN
Solar/Wind Harmer
0.068
316140AB2-099
Solar/Wind Harmer
0.028
962331AG1-082 GEN
Solar/Wind Harmer
0.842
3146263WOODLND
Solar/Wind Harmer
0.077
3145963POPLR C
Solar/Wind Harmer
0.077
3142666NORTHAMPTON
Solar/Wind Harmer
0.077
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.076
313506AB2-031 GEN
Solar/Wind Harmer
0.235
3145796HORNRTN
Solar/Wind Harmer
0.299
3145796HORNRTN
Solar/Wind Harmer
0.075
3145933PARMELE
Solar/Wind Harmer
0.073
966801AG1-551 GEN
Solar/Wind Harmer
0.852
3147043LAWRENC
Solar/Wind Harmer
0.044
316210AC1-098 GEN
Solar/Wind Harmer
0.675
3150351NORNECKC2
Adder
0.736
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
315724AD1-057 GEN
Solar/Wind Harmer
0.264
316327AA2-057 GEN
Solar/Wind Harmer
0.105
970917AG2-570 GEN
Solar/Wind Harmer
6.096
3146073TAR RVR
Solar/Wind Harmer
0.068
3146083TARBORO
Solar/Wind Harmer
0.068
3146233WITAKRS
Solar/Wind Harmer
0.341
3146233WITAKRS
Solar/Wind Harmer
0.046
3138543CONSLDL
Solar/Wind Harmer
0.045
961601AG1-000A GEN
Solar/Wind Harmer
4.735
3145543BTLEBRO
Solar/Wind Harmer
0.066
3145543BTLEBRO
Solar/Wind Harmer
0.066
971623AH1-311 GEN
Solar/Wind Harmer
0.133
316478AD1-087 GEN
Solar/Wind Harmer
0.226
316486AD2-202 GEN
Solar/Wind Harmer
0.066
316131AB2-060 GEN
Solar/Wind Harmer
0.2
964241AG1-285 GEN
Solar/Wind Harmer
4.226
315785AD2-033 C
Solar/Wind Harmer
0.512
970257AG2-171 GEN
Solar/Wind Harmer
2.009
959311AF2-222 GEN
Solar/Wind Harmer
5.571
970909AG2-566 GEN
Solar/Wind Harmer
0.666
963181AG1-167 GEN
Solar/Wind Harmer
0.248
3144293JTRSVLE
Adder
0.197
3147133PAMPLIN
Solar/Wind Harmer
0.194
971193AH1-056 GEN
Solar/Wind Harmer
3.759
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.036
3146776BUCKING
Solar/Wind Harmer
0.021
316248AF1-058 C
Solar/Wind Harmer
0
960061AF2-297 GEN
Solar/Wind Harmer
2.454
966881AG1-559 GEN
Solar/Wind Helper
1.231
939181AE1-148 GEN
Solar/Wind Harmer
3.093
313527AB2-043 GEN
Solar/Wind Harmer
0.001
971741AH1-377 GEN
Solar/Wind Harmer
6.264
316034AC1-036 C
Solar/Wind Harmer
0.005
970323AG2-213 GEN
Solar/Wind Harmer
2.679
971775AH1-396 GEN
Solar/Wind Harmer
0.1
970301AG2-198 GEN
Solar/Wind Harmer
2.664
958211AF2-115 GEN
Solar/Wind Harmer
0.744
963191AG1-168 GEN
Solar/Wind Harmer
0.248
3144293JTRSVLE
Adder
0.197
3144293JTRSVLE
Adder
0.166
3147133PAMPLIN
Solar/Wind Harmer
0.062
3147133PAMPLIN
Solar/Wind Harmer
0.049
962561AG1-105 GEN
Solar/Wind Harmer
2.911
964791AG1-342 GEN
Solar/Wind Harmer
1.154
3146843MT LREL
Solar/Wind Harmer
0.06
3146843MT LREL
Solar/Wind Harmer
0.06
3146776BUCKING
Solar/Wind Harmer
0.231
3146776BUCKING
Solar/Wind Harmer
0.019
LAGNLTFEXP_LAGN->PJM
CLTF
3.272
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.272
TVALTFEXP_TVA->PJM
CLTF
1.66
NYPJM->LTFIMP_NY
CLTF
1.302
LGEELTFEXP_LGEE->PJM
CLTF
0.637
WECLTFEXP_WEC->PJM
CLTF
0.317
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.925
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.738
MECLTFEXP_MEC->PJM
CLTF
1.668
SIGELTFEXP_SIGE->PJM
CLTF
0.052
CPLELTFEXP_CPLE->PJM
CLTF
4.14
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.656

Details for 6FREDBRG-6CRANES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9296_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FREDBRG-6CRANES 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 9296_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.91 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1121.11
MW Contribution:4.38
Bus #Bus NameTypeMW Contribution
3150411LDYSMT5
50/50
24.498
3150381LDYSMT2
50/50
23.445
972213AH1-691 GEN
50/50
3.966
972215AH1-692 GEN
50/50
3.966
963051AG1-154 GEN
50/50
3.051
944491AF1-114 GEN
Solar/Wind Harmer
0.001
316223AC1-118
Solar/Wind Harmer
0.155
3141813NORNECK
Solar/Wind Harmer
0.159
970327AG2-215 GEN
Solar/Wind Harmer
4.385
962981AG1-147 GEN
Solar/Wind Harmer
4.775
3141783LANCAST
Solar/Wind Harmer
0.071
3141783LANCAST
Solar/Wind Harmer
0.047
3138133OCRAN
Solar/Wind Harmer
0.034
3141913WHIT STONE
Solar/Wind Harmer
0.111
3141873WAN 176
Solar/Wind Harmer
0.021
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
2.943
316314AB2-024 C
Solar/Wind Harmer
0
972189AH1-679 GEN
Adder
1.608
3143873LANEXA
Solar/Wind Harmer
0.057
3142433PROV 92
Adder
0.171
3142433PROV 92
Adder
0.171
971167AH1-042 GEN
Solar/Wind Harmer
7.69
3138283WHITEMARSH
Solar/Wind Harmer
0.02
315976AC1-164 GENA
Solar/Wind Harmer
7.877
316169AC1-164_GENC
Solar/Wind Harmer
6.805
315975AC1-164 GENB
Solar/Wind Harmer
0.233
316312AB1-027
Solar/Wind Harmer
0.131
316132AB2-190 GEN1
Solar/Wind Harmer
0.347
971285AH1-108 GEN
Adder
0.482
316369SG1_INVT
Solar/Wind Harmer
0.002
972265AH1-717 GEN
Adder
4.824
3151201GRAVEL4
Adder
4.522
3151191GRAVEL3
Adder
4.465
3151211GRAVEL5
Adder
4.465
971445AH1-216 GEN
Solar/Wind Harmer
4.254
316233AE1-074 FULL
Solar/Wind Harmer
0.047
971281AH1-106 GEN
Solar/Wind Harmer
0.819
971283AH1-107 GEN
Solar/Wind Harmer
0.819
3143316POE
Solar/Wind Harmer
0.231
3152611GOSPORTB
Adder
0.729
3152621GOSPORTC
Adder
0.618
3152601GOSPORTA
Adder
0.571
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.039
316311AC2-079 GEN
Solar/Wind Harmer
1.643
972197AH1-683 GEN
50/50
3.813
972219AH1-694 GEN
50/50
2.746
3150351NORNECKC2
50/50
1.686
966661AG1-536 GEN
50/50
4.063
972135AH1-637 GEN
Solar/Wind Harmer
2.21
316337AD2-073 GEN
Solar/Wind Harmer
0.162
3141726DUNNSVL
Solar/Wind Harmer
0.606
962861AG1-135 GEN
Solar/Wind Harmer
4.492
966881AG1-559 GEN
Solar/Wind Harmer
0.158
3138133OCRAN
Solar/Wind Harmer
0.068
3141766HARMONY
Solar/Wind Harmer
0.02
971777AH1-397 GEN
Solar/Wind Harmer
0.262
3141843SHACKLE
Adder
0.507
3142433PROV 92
Solar/Wind Harmer
0.352
3142433PROV 92
Adder
0.171
3142433PROV 92
Adder
0.171
3142416OLDCHRC
Solar/Wind Harmer
0.19
3142416OLDCHRC
Solar/Wind Harmer
0.073
971317AH1-138 GEN
Solar/Wind Harmer
0.545
316159AE1-175 C
Solar/Wind Harmer
0.061
944631AF1-128 GEN
Adder
33.488
3143096IRON208
Adder
0.289
3138126ROCKLANDING
Solar/Wind Harmer
0.031
3142543TWELFTH
Solar/Wind Harmer
0.006
970129AG2-093 GEN
Solar/Wind Harmer
1.842
316458AB2-190 GEN2
Solar/Wind Harmer
0.347
315671AE2-027_GEN
Solar/Wind Harmer
4.113
971069AG2-661 GEN
Solar/Wind Harmer
1.14
3150851SPRUNCC
Adder
0.294
971647AH1-324 GEN
Solar/Wind Harmer
2.698
961611AG1-000B GEN
Solar/Wind Harmer
3.29
3151171GRAVELC
Adder
0.661
3145336SMITFLD
Solar/Wind Harmer
0.241
3143526WINTERP
Solar/Wind Harmer
0.307
970659AG2-427 GEN
Solar/Wind Harmer
2.85
316381AD1-082 GEN
Solar/Wind Harmer
0.061
316072AD1-144
Solar/Wind Harmer
0.021
970661AG2-428 GEN
Solar/Wind Harmer
5.802
316375AC2-012 GEN
Solar/Wind Harmer
0.001
3150981CHESPKA
Adder
0.715
316294AC1-161 GEN
Solar/Wind Harmer
0.981
944591AF1-124 GEN
Solar/Wind Harmer
12.783
316246AF1-032 C
Solar/Wind Harmer
0.025
316388AE2-253 GEN
Solar/Wind Harmer
0.176
316093AE2-104_GEN
Solar/Wind Harmer
0.946
3150331BIRCHWDA
50/50
74.484
3141316ARNOLDS
50/50
0.959
3150401LDYSMT4
50/50
24.421
3150371LDYSMT1
50/50
23.598
3150501FRIVERG
50/50
1.371
3150351NORNECKC2
50/50
1.714
970737AG2-469 GEN
Solar/Wind Harmer
10.3
3141906WESTMOR
Solar/Wind Harmer
0.086
971781AH1-399 GEN
Solar/Wind Harmer
0.24
316404AE1-155 C
Solar/Wind Harmer
0.032
970009AG2-005 GEN
Solar/Wind Harmer
0.998
962971AG1-146 GEN
Solar/Wind Harmer
2.047
316156AD2-030 GEN
Solar/Wind Harmer
0.076
3141873WAN 176
Solar/Wind Harmer
1.826
316280AD1-041 GEN
Solar/Wind Harmer
0.002
3141766HARMONY
Solar/Wind Harmer
1.33
316203AE2-005 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
0.507
316473AC1-191 GEN
Solar/Wind Harmer
0.322
3142433PROV 92
Adder
0.171
3142433PROV 92
Adder
0.171
3142416OLDCHRC
Solar/Wind Harmer
0.709
970293AG2-193 GEN
Solar/Wind Harmer
0.775
3142946ENON
Solar/Wind Harmer
0.024
316382AG1-145 C
Solar/Wind Harmer
0.001
3143096IRON208
Adder
0.289
3143096IRON208
Adder
0.283
3150921YORKTN3
Adder
1.719
3144216WINCHST
Adder
0.254
970133AG2-095 GEN
Solar/Wind Harmer
0.63
970129AG2-093 GEN
Solar/Wind Harmer
3.914
315778AD1-151 GEN
Solar/Wind Harmer
5.128
3150861SPRUNCD
Adder
0.294
965281AG1-393 GEN
Solar/Wind Harmer
0.677
961611AG1-000B GEN
Solar/Wind Harmer
1.673
3151221GRAVEL6
Adder
4.517
3151171GRAVELC
Adder
0.869
315839AE2-212 C
Solar/Wind Harmer
0
3145336SMITFLD
Solar/Wind Harmer
0.024
315813AE1-149 C
Solar/Wind Harmer
3.187
970659AG2-427 GEN
Solar/Wind Harmer
0.623
316083AB2-161 GEN
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.234
3144536CHRHLND
Solar/Wind Harmer
0.009
3144873MCLAUGH
Solar/Wind Harmer
0.001
3151101ELIZAR3
Adder
5.306
315773AC2-141 GEN
Solar/Wind Harmer
2.068
944581AF1-123 GEN
Solar/Wind Harmer
12.738
944601AF1-125 GEN
Solar/Wind Harmer
12.541
957191AF2-013 GEN
50/50
31.493
3150391LDYSMT3
50/50
24.376
972195AH1-682 GEN
50/50
3.203
3150341NORNECKC1
50/50
1.771
3150341NORNECKC1
50/50
1.756
963611AG1-210 GEN
50/50
0.567
316468AD1-105 GEN
Solar/Wind Harmer
-0.059
316077AC2-138 C
Solar/Wind Harmer
0.001
315673AE1-157 GEN
Solar/Wind Harmer
10.324
958261AF2-120 GEN
Solar/Wind Harmer
4.723
957411AF2-035 GEN
Solar/Wind Harmer
5.818
970317AG2-208 GEN
Solar/Wind Harmer
5.39
966871AG1-558 GEN
Solar/Wind Harmer
0.11
316075AC2-137 C
Solar/Wind Harmer
0.02
3142946ENON
Solar/Wind Harmer
0.007
3142296MT RD221
Adder
0.227
3150691DARBY 3
Adder
5.107
3150701DARBY 4
Adder
5.095
3150681DARBY 2
Adder
5.089
3150671DARBY 1
Adder
5.083
3142366NRTHEST
Adder
0.229
944641AF1-129 GEN
Adder
30.454
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.072
316240AF1-291 C
Solar/Wind Harmer
0.001
316236AE1-162_GEN
Solar/Wind Harmer
0
3143526WINTERP
Solar/Wind Harmer
0.307
970657AG2-426 GEN
Solar/Wind Harmer
2.053
970657AG2-426 GEN
Solar/Wind Harmer
0.43
316036AC1-147 C
Solar/Wind Harmer
0.011
3150991CHESPKB
Adder
0.599
3150991CHESPKB
Adder
0.585
316316AC1-027 C
Solar/Wind Harmer
0.055
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3145506HICKORY
Solar/Wind Harmer
0.226
3145506HICKORY
Solar/Wind Harmer
0.136
3145506HICKORY
Solar/Wind Harmer
0.034
316339AD2-160 GEN
Solar/Wind Harmer
0.091
316018AA1-139 ULT2
Solar/Wind Harmer
0.001
316017AA1-139 ULT1
Solar/Wind Harmer
0.031
3151081ELIZAR1
Adder
5.239
3151091ELIZAR2
Adder
5.148
316305AF2-043 C
Solar/Wind Harmer
0
957871AF2-081 GEN
Solar/Wind Harmer
2.801
315835AF2-110_GEN
Solar/Wind Harmer
0.386
3141426STAFORD
Solar/Wind Helper
0.174
LAGNLTFEXP_LAGN->PJM
CLTF
2.016
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.794
TVALTFEXP_TVA->PJM
CLTF
1.019
NYPJM->LTFIMP_NY
CLTF
0.793
LGEELTFEXP_LGEE->PJM
CLTF
0.39
WECLTFEXP_WEC->PJM
CLTF
0.196
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.786
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.522
MECLTFEXP_MEC->PJM
CLTF
1.029
SIGELTFEXP_SIGE->PJM
CLTF
0.032
CPLELTFEXP_CPLE->PJM
CLTF
2.609
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.872

Details for 6FREDBRG-6CRANES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2119_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FREDBRG-6CRANES 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2119_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.9 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1120.95
MW Contribution:4.38
Bus #Bus NameTypeMW Contribution
972197AH1-683 GEN
50/50
3.813
972219AH1-694 GEN
50/50
2.746
3150351NORNECKC2
50/50
1.686
966661AG1-536 GEN
50/50
4.063
972135AH1-637 GEN
Solar/Wind Harmer
2.21
316337AD2-073 GEN
Solar/Wind Harmer
0.162
3141726DUNNSVL
Solar/Wind Harmer
0.606
962861AG1-135 GEN
Solar/Wind Harmer
4.492
966881AG1-559 GEN
Solar/Wind Harmer
0.158
3138133OCRAN
Solar/Wind Harmer
0.068
3141766HARMONY
Solar/Wind Harmer
0.02
971777AH1-397 GEN
Solar/Wind Harmer
0.262
3141843SHACKLE
Adder
0.507
3142433PROV 92
Solar/Wind Harmer
0.352
3142433PROV 92
Adder
0.171
3142433PROV 92
Adder
0.171
3142416OLDCHRC
Solar/Wind Harmer
0.19
3142416OLDCHRC
Solar/Wind Harmer
0.073
971317AH1-138 GEN
Solar/Wind Harmer
0.545
316159AE1-175 C
Solar/Wind Harmer
0.061
944631AF1-128 GEN
Adder
33.488
3143096IRON208
Adder
0.289
3138126ROCKLANDING
Solar/Wind Harmer
0.031
3142543TWELFTH
Solar/Wind Harmer
0.006
970129AG2-093 GEN
Solar/Wind Harmer
1.842
316458AB2-190 GEN2
Solar/Wind Harmer
0.347
315671AE2-027_GEN
Solar/Wind Harmer
4.113
971069AG2-661 GEN
Solar/Wind Harmer
1.14
3150851SPRUNCC
Adder
0.294
971647AH1-324 GEN
Solar/Wind Harmer
2.698
961611AG1-000B GEN
Solar/Wind Harmer
3.29
3151171GRAVELC
Adder
0.661
3145336SMITFLD
Solar/Wind Harmer
0.241
3143526WINTERP
Solar/Wind Harmer
0.307
970659AG2-427 GEN
Solar/Wind Harmer
2.85
316381AD1-082 GEN
Solar/Wind Harmer
0.061
316072AD1-144
Solar/Wind Harmer
0.021
970661AG2-428 GEN
Solar/Wind Harmer
5.802
316375AC2-012 GEN
Solar/Wind Harmer
0.001
3150981CHESPKA
Adder
0.715
316294AC1-161 GEN
Solar/Wind Harmer
0.981
944591AF1-124 GEN
Solar/Wind Harmer
12.783
316246AF1-032 C
Solar/Wind Harmer
0.025
316388AE2-253 GEN
Solar/Wind Harmer
0.176
316093AE2-104_GEN
Solar/Wind Harmer
0.946
3150331BIRCHWDA
50/50
74.484
3141316ARNOLDS
50/50
0.959
3150401LDYSMT4
50/50
24.421
3150371LDYSMT1
50/50
23.598
3150501FRIVERG
50/50
1.371
3150351NORNECKC2
50/50
1.714
970737AG2-469 GEN
Solar/Wind Harmer
10.3
3141906WESTMOR
Solar/Wind Harmer
0.086
971781AH1-399 GEN
Solar/Wind Harmer
0.24
316404AE1-155 C
Solar/Wind Harmer
0.032
970009AG2-005 GEN
Solar/Wind Harmer
0.998
962971AG1-146 GEN
Solar/Wind Harmer
2.047
316156AD2-030 GEN
Solar/Wind Harmer
0.076
3141873WAN 176
Solar/Wind Harmer
1.826
316280AD1-041 GEN
Solar/Wind Harmer
0.002
3141766HARMONY
Solar/Wind Harmer
1.33
316203AE2-005 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
0.507
316473AC1-191 GEN
Solar/Wind Harmer
0.322
3142433PROV 92
Adder
0.171
3142433PROV 92
Adder
0.171
3142416OLDCHRC
Solar/Wind Harmer
0.709
970293AG2-193 GEN
Solar/Wind Harmer
0.775
3142946ENON
Solar/Wind Harmer
0.024
316382AG1-145 C
Solar/Wind Harmer
0.001
3143096IRON208
Adder
0.289
3143096IRON208
Adder
0.283
3150921YORKTN3
Adder
1.719
3144216WINCHST
Adder
0.254
970133AG2-095 GEN
Solar/Wind Harmer
0.63
970129AG2-093 GEN
Solar/Wind Harmer
3.914
315778AD1-151 GEN
Solar/Wind Harmer
5.128
3150861SPRUNCD
Adder
0.294
965281AG1-393 GEN
Solar/Wind Harmer
0.677
961611AG1-000B GEN
Solar/Wind Harmer
1.673
3151221GRAVEL6
Adder
4.517
3151171GRAVELC
Adder
0.869
315839AE2-212 C
Solar/Wind Harmer
0
3145336SMITFLD
Solar/Wind Harmer
0.024
315813AE1-149 C
Solar/Wind Harmer
3.187
970659AG2-427 GEN
Solar/Wind Harmer
0.623
316083AB2-161 GEN
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.234
3144536CHRHLND
Solar/Wind Harmer
0.009
3144873MCLAUGH
Solar/Wind Harmer
0.001
3151101ELIZAR3
Adder
5.306
315773AC2-141 GEN
Solar/Wind Harmer
2.068
944581AF1-123 GEN
Solar/Wind Harmer
12.738
944601AF1-125 GEN
Solar/Wind Harmer
12.541
957191AF2-013 GEN
50/50
31.493
3150391LDYSMT3
50/50
24.376
972195AH1-682 GEN
50/50
3.203
3150341NORNECKC1
50/50
1.771
3150341NORNECKC1
50/50
1.756
963611AG1-210 GEN
50/50
0.567
316468AD1-105 GEN
Solar/Wind Harmer
-0.059
316077AC2-138 C
Solar/Wind Harmer
0.001
315673AE1-157 GEN
Solar/Wind Harmer
10.324
958261AF2-120 GEN
Solar/Wind Harmer
4.723
957411AF2-035 GEN
Solar/Wind Harmer
5.818
970317AG2-208 GEN
Solar/Wind Harmer
5.39
966871AG1-558 GEN
Solar/Wind Harmer
0.11
316075AC2-137 C
Solar/Wind Harmer
0.02
3142946ENON
Solar/Wind Harmer
0.007
3142296MT RD221
Adder
0.227
3150691DARBY 3
Adder
5.107
3150701DARBY 4
Adder
5.095
3150681DARBY 2
Adder
5.089
3150671DARBY 1
Adder
5.083
3142366NRTHEST
Adder
0.229
944641AF1-129 GEN
Adder
30.454
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.072
316240AF1-291 C
Solar/Wind Harmer
0.001
316236AE1-162_GEN
Solar/Wind Harmer
0
3143526WINTERP
Solar/Wind Harmer
0.307
970657AG2-426 GEN
Solar/Wind Harmer
2.053
970657AG2-426 GEN
Solar/Wind Harmer
0.43
316036AC1-147 C
Solar/Wind Harmer
0.011
3150991CHESPKB
Adder
0.599
3150991CHESPKB
Adder
0.585
316316AC1-027 C
Solar/Wind Harmer
0.055
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3145506HICKORY
Solar/Wind Harmer
0.226
3145506HICKORY
Solar/Wind Harmer
0.136
3145506HICKORY
Solar/Wind Harmer
0.034
316339AD2-160 GEN
Solar/Wind Harmer
0.091
316018AA1-139 ULT2
Solar/Wind Harmer
0.001
316017AA1-139 ULT1
Solar/Wind Harmer
0.031
3150411LDYSMT5
50/50
24.498
3150381LDYSMT2
50/50
23.445
972213AH1-691 GEN
50/50
3.966
972215AH1-692 GEN
50/50
3.966
963051AG1-154 GEN
50/50
3.051
944491AF1-114 GEN
Solar/Wind Harmer
0.001
316223AC1-118
Solar/Wind Harmer
0.155
3141813NORNECK
Solar/Wind Harmer
0.159
970327AG2-215 GEN
Solar/Wind Harmer
4.385
962981AG1-147 GEN
Solar/Wind Harmer
4.775
3141783LANCAST
Solar/Wind Harmer
0.071
3141783LANCAST
Solar/Wind Harmer
0.047
3138133OCRAN
Solar/Wind Harmer
0.034
3141913WHIT STONE
Solar/Wind Harmer
0.111
3141873WAN 176
Solar/Wind Harmer
0.021
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
2.943
316314AB2-024 C
Solar/Wind Harmer
0
972189AH1-679 GEN
Adder
1.608
3143873LANEXA
Solar/Wind Harmer
0.057
3142433PROV 92
Adder
0.171
3142433PROV 92
Adder
0.171
971167AH1-042 GEN
Solar/Wind Harmer
7.69
3138283WHITEMARSH
Solar/Wind Harmer
0.02
315976AC1-164 GENA
Solar/Wind Harmer
7.877
316169AC1-164_GENC
Solar/Wind Harmer
6.805
315975AC1-164 GENB
Solar/Wind Harmer
0.233
316312AB1-027
Solar/Wind Harmer
0.131
316132AB2-190 GEN1
Solar/Wind Harmer
0.347
971285AH1-108 GEN
Adder
0.482
316369SG1_INVT
Solar/Wind Harmer
0.002
972265AH1-717 GEN
Adder
4.824
3151201GRAVEL4
Adder
4.522
3151191GRAVEL3
Adder
4.465
3151211GRAVEL5
Adder
4.465
971445AH1-216 GEN
Solar/Wind Harmer
4.254
316233AE1-074 FULL
Solar/Wind Harmer
0.047
971281AH1-106 GEN
Solar/Wind Harmer
0.819
971283AH1-107 GEN
Solar/Wind Harmer
0.819
3143316POE
Solar/Wind Harmer
0.231
3152611GOSPORTB
Adder
0.729
3152621GOSPORTC
Adder
0.618
3152601GOSPORTA
Adder
0.571
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.039
316311AC2-079 GEN
Solar/Wind Harmer
1.643
3151081ELIZAR1
Adder
5.239
3151091ELIZAR2
Adder
5.148
316305AF2-043 C
Solar/Wind Harmer
0
957871AF2-081 GEN
Solar/Wind Harmer
2.801
315835AF2-110_GEN
Solar/Wind Harmer
0.386
3141426STAFORD
Solar/Wind Helper
0.174
LAGNLTFEXP_LAGN->PJM
CLTF
2.016
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.794
TVALTFEXP_TVA->PJM
CLTF
1.019
NYPJM->LTFIMP_NY
CLTF
0.793
LGEELTFEXP_LGEE->PJM
CLTF
0.39
WECLTFEXP_WEC->PJM
CLTF
0.196
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.786
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.522
MECLTFEXP_MEC->PJM
CLTF
1.029
SIGELTFEXP_SIGE->PJM
CLTF
0.032
CPLELTFEXP_CPLE->PJM
CLTF
2.609
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.872

Details for 6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2157_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2157_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.81 %
Rating:717.22 MVA
Rating Type:B
MVA to Mitigate:837.81
MW Contribution:4.01
Bus #Bus NameTypeMW Contribution
957191AF2-013 GEN
50/50
28.808
3150391LDYSMT3
50/50
22.297
972195AH1-682 GEN
50/50
2.93
3150341NORNECKC1
50/50
1.62
3150341NORNECKC1
50/50
1.607
963611AG1-210 GEN
50/50
0.518
316468AD1-105 GEN
Solar/Wind Harmer
-0.054
316077AC2-138 C
Solar/Wind Harmer
0.001
315673AE1-157 GEN
Solar/Wind Harmer
9.444
958261AF2-120 GEN
Solar/Wind Harmer
4.32
957411AF2-035 GEN
Solar/Wind Harmer
5.322
970317AG2-208 GEN
Solar/Wind Harmer
4.93
966871AG1-558 GEN
Solar/Wind Harmer
0.101
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.007
3142296MT RD221
Adder
0.208
3150691DARBY 3
Adder
4.672
3150701DARBY 4
Adder
4.661
3150681DARBY 2
Adder
4.655
3150671DARBY 1
Adder
4.65
3142366NRTHEST
Adder
0.209
944641AF1-129 GEN
Adder
27.858
316033AB2-134 GEN
Solar/Wind Harmer
0.003
315697AD1-025 GEN
Solar/Wind Harmer
0.066
316240AF1-291 C
Solar/Wind Harmer
0
3150331BIRCHWDA
50/50
68.134
3141316ARNOLDS
50/50
0.877
3150401LDYSMT4
50/50
22.339
3150371LDYSMT1
50/50
21.586
3150501FRIVERG
50/50
1.254
3150351NORNECKC2
50/50
1.568
970737AG2-469 GEN
Solar/Wind Harmer
9.422
3141906WESTMOR
Solar/Wind Harmer
0.079
971781AH1-399 GEN
Solar/Wind Harmer
0.219
316404AE1-155 C
Solar/Wind Harmer
0.029
970009AG2-005 GEN
Solar/Wind Harmer
0.913
962971AG1-146 GEN
Solar/Wind Harmer
1.872
316156AD2-030 GEN
Solar/Wind Harmer
0.07
3141873WAN 176
Solar/Wind Harmer
1.67
316280AD1-041 GEN
Solar/Wind Harmer
0.002
3150411LDYSMT5
50/50
22.409
3150381LDYSMT2
50/50
21.446
972213AH1-691 GEN
50/50
3.628
972215AH1-692 GEN
50/50
3.628
963051AG1-154 GEN
50/50
2.791
944491AF1-114 GEN
Solar/Wind Harmer
0.001
316223AC1-118
Solar/Wind Harmer
0.142
3141813NORNECK
Solar/Wind Harmer
0.146
970327AG2-215 GEN
Solar/Wind Harmer
4.011
962981AG1-147 GEN
Solar/Wind Harmer
4.368
3141783LANCAST
Solar/Wind Harmer
0.065
3141783LANCAST
Solar/Wind Harmer
0.043
3138133OCRAN
Solar/Wind Harmer
0.031
3141913WHIT STONE
Solar/Wind Harmer
0.102
3141873WAN 176
Solar/Wind Harmer
0.019
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
2.692
316314AB2-024 C
Solar/Wind Harmer
0
972189AH1-679 GEN
Adder
1.471
3143873LANEXA
Solar/Wind Harmer
0.052
3142433PROV 92
Adder
0.157
3142433PROV 92
Adder
0.157
971167AH1-042 GEN
Solar/Wind Harmer
7.034
3138283WHITEMARSH
Solar/Wind Harmer
0.018
315976AC1-164 GENA
Solar/Wind Harmer
7.205
316169AC1-164_GENC
Solar/Wind Harmer
6.225
315975AC1-164 GENB
Solar/Wind Harmer
0.213
316312AB1-027
Solar/Wind Harmer
0.12
316132AB2-190 GEN1
Solar/Wind Harmer
0.317
971285AH1-108 GEN
Adder
0.441
316369SG1_INVT
Solar/Wind Harmer
0.002
972265AH1-717 GEN
Adder
4.412
3151201GRAVEL4
Adder
4.136
3151191GRAVEL3
Adder
4.084
3151211GRAVEL5
Adder
4.084
3141426STAFORD
Solar/Wind Helper
0.047
3141766HARMONY
Solar/Wind Harmer
1.216
316203AE2-005 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
0.464
316473AC1-191 GEN
Solar/Wind Harmer
0.294
3142433PROV 92
Adder
0.157
3142433PROV 92
Adder
0.157
3142416OLDCHRC
Solar/Wind Harmer
0.648
970293AG2-193 GEN
Solar/Wind Harmer
0.709
3142946ENON
Solar/Wind Harmer
0.022
316382AG1-145 C
Solar/Wind Harmer
0.001
3143096IRON208
Adder
0.264
3143096IRON208
Adder
0.259
3150921YORKTN3
Adder
1.572
3144216WINCHST
Adder
0.232
970133AG2-095 GEN
Solar/Wind Harmer
0.577
970129AG2-093 GEN
Solar/Wind Harmer
3.58
315778AD1-151 GEN
Solar/Wind Harmer
4.691
3150861SPRUNCD
Adder
0.269
965281AG1-393 GEN
Solar/Wind Harmer
0.619
961611AG1-000B GEN
Solar/Wind Harmer
1.53
3151221GRAVEL6
Adder
4.131
3151171GRAVELC
Adder
0.795
315839AE2-212 C
Solar/Wind Harmer
0
972197AH1-683 GEN
50/50
3.488
972219AH1-694 GEN
50/50
2.512
3150351NORNECKC2
50/50
1.542
966661AG1-536 GEN
50/50
3.716
972135AH1-637 GEN
Solar/Wind Harmer
2.022
316337AD2-073 GEN
Solar/Wind Harmer
0.148
3141726DUNNSVL
Solar/Wind Harmer
0.555
962861AG1-135 GEN
Solar/Wind Harmer
4.109
966881AG1-559 GEN
Solar/Wind Harmer
0.144
3138133OCRAN
Solar/Wind Harmer
0.062
3141766HARMONY
Solar/Wind Harmer
0.018
971777AH1-397 GEN
Solar/Wind Harmer
0.24
3141843SHACKLE
Adder
0.464
3142433PROV 92
Solar/Wind Harmer
0.322
3142433PROV 92
Adder
0.157
3142433PROV 92
Adder
0.157
3142416OLDCHRC
Solar/Wind Harmer
0.174
3142416OLDCHRC
Solar/Wind Harmer
0.067
971317AH1-138 GEN
Solar/Wind Harmer
0.499
316159AE1-175 C
Solar/Wind Harmer
0.056
944631AF1-128 GEN
Adder
30.632
3143096IRON208
Adder
0.264
3138126ROCKLANDING
Solar/Wind Harmer
0.028
3142543TWELFTH
Solar/Wind Harmer
0.006
970129AG2-093 GEN
Solar/Wind Harmer
1.685
316458AB2-190 GEN2
Solar/Wind Harmer
0.317
315671AE2-027_GEN
Solar/Wind Harmer
3.762
971069AG2-661 GEN
Solar/Wind Harmer
1.042
3150851SPRUNCC
Adder
0.269
971647AH1-324 GEN
Solar/Wind Harmer
2.468
961611AG1-000B GEN
Solar/Wind Harmer
3.01
3151171GRAVELC
Adder
0.604
LAGNLTFEXP_LAGN->PJM
CLTF
1.844
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.3
TVALTFEXP_TVA->PJM
CLTF
0.932
NYPJM->LTFIMP_NY
CLTF
0.726
LGEELTFEXP_LGEE->PJM
CLTF
0.356
WECLTFEXP_WEC->PJM
CLTF
0.179
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.206
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.222
MECLTFEXP_MEC->PJM
CLTF
0.941
SIGELTFEXP_SIGE->PJM
CLTF
0.029
CPLELTFEXP_CPLE->PJM
CLTF
2.387
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.943

Details for 6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2104_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2104_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.78 %
Rating:717.22 MVA
Rating Type:B
MVA to Mitigate:794.57
MW Contribution:4.01
Bus #Bus NameTypeMW Contribution
3150331BIRCHWDA
50/50
68.134
3141316ARNOLDS
50/50
0.877
3150401LDYSMT4
50/50
22.339
3150371LDYSMT1
50/50
21.586
3150501FRIVERG
50/50
1.254
3150351NORNECKC2
50/50
1.568
970737AG2-469 GEN
Solar/Wind Harmer
9.422
3141906WESTMOR
Solar/Wind Harmer
0.079
971781AH1-399 GEN
Solar/Wind Harmer
0.219
316404AE1-155 C
Solar/Wind Harmer
0.029
970009AG2-005 GEN
Solar/Wind Harmer
0.913
962971AG1-146 GEN
Solar/Wind Harmer
1.872
316156AD2-030 GEN
Solar/Wind Harmer
0.07
3141873WAN 176
Solar/Wind Harmer
1.67
316280AD1-041 GEN
Solar/Wind Harmer
0.002
3141766HARMONY
Solar/Wind Harmer
1.216
316203AE2-005 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
0.464
316473AC1-191 GEN
Solar/Wind Harmer
0.294
3142433PROV 92
Adder
0.157
3142433PROV 92
Adder
0.157
3142416OLDCHRC
Solar/Wind Harmer
0.648
970293AG2-193 GEN
Solar/Wind Harmer
0.709
3142946ENON
Solar/Wind Harmer
0.022
316382AG1-145 C
Solar/Wind Harmer
0.001
3143096IRON208
Adder
0.264
3143096IRON208
Adder
0.259
3150921YORKTN3
Adder
1.572
3144216WINCHST
Adder
0.232
970133AG2-095 GEN
Solar/Wind Harmer
0.577
970129AG2-093 GEN
Solar/Wind Harmer
3.58
315778AD1-151 GEN
Solar/Wind Harmer
4.691
3150861SPRUNCD
Adder
0.269
965281AG1-393 GEN
Solar/Wind Harmer
0.619
961611AG1-000B GEN
Solar/Wind Harmer
1.53
3151221GRAVEL6
Adder
4.131
3151171GRAVELC
Adder
0.795
315839AE2-212 C
Solar/Wind Harmer
0
3141346CRANES
50/50
0.542
972197AH1-683 GEN
50/50
3.488
972219AH1-694 GEN
50/50
2.512
3150351NORNECKC2
50/50
1.542
966661AG1-536 GEN
50/50
3.716
972135AH1-637 GEN
Solar/Wind Harmer
2.022
316337AD2-073 GEN
Solar/Wind Harmer
0.148
3141726DUNNSVL
Solar/Wind Harmer
0.555
962861AG1-135 GEN
Solar/Wind Harmer
4.109
966881AG1-559 GEN
Solar/Wind Harmer
0.144
3138133OCRAN
Solar/Wind Harmer
0.062
3141766HARMONY
Solar/Wind Harmer
0.018
971777AH1-397 GEN
Solar/Wind Harmer
0.24
3141843SHACKLE
Adder
0.464
957191AF2-013 GEN
50/50
28.808
3150391LDYSMT3
50/50
22.297
972195AH1-682 GEN
50/50
2.93
3150341NORNECKC1
50/50
1.62
3150341NORNECKC1
50/50
1.607
963611AG1-210 GEN
50/50
0.518
316468AD1-105 GEN
Solar/Wind Harmer
-0.054
316077AC2-138 C
Solar/Wind Harmer
0.001
315673AE1-157 GEN
Solar/Wind Harmer
9.444
958261AF2-120 GEN
Solar/Wind Harmer
4.32
957411AF2-035 GEN
Solar/Wind Harmer
5.322
970317AG2-208 GEN
Solar/Wind Harmer
4.93
966871AG1-558 GEN
Solar/Wind Harmer
0.101
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.007
3142296MT RD221
Adder
0.208
3150691DARBY 3
Adder
4.672
3150701DARBY 4
Adder
4.661
3150681DARBY 2
Adder
4.655
3150671DARBY 1
Adder
4.65
3142366NRTHEST
Adder
0.209
944641AF1-129 GEN
Adder
27.858
316033AB2-134 GEN
Solar/Wind Harmer
0.003
315697AD1-025 GEN
Solar/Wind Harmer
0.066
316240AF1-291 C
Solar/Wind Harmer
0
3150411LDYSMT5
50/50
22.409
3150381LDYSMT2
50/50
21.446
972213AH1-691 GEN
50/50
3.628
972215AH1-692 GEN
50/50
3.628
963051AG1-154 GEN
50/50
2.791
944491AF1-114 GEN
Solar/Wind Harmer
0.001
316223AC1-118
Solar/Wind Harmer
0.142
3141813NORNECK
Solar/Wind Harmer
0.146
970327AG2-215 GEN
Solar/Wind Harmer
4.011
962981AG1-147 GEN
Solar/Wind Harmer
4.368
3141783LANCAST
Solar/Wind Harmer
0.065
3141783LANCAST
Solar/Wind Harmer
0.043
3138133OCRAN
Solar/Wind Harmer
0.031
3141913WHIT STONE
Solar/Wind Harmer
0.102
3141873WAN 176
Solar/Wind Harmer
0.019
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
2.692
316314AB2-024 C
Solar/Wind Harmer
0
972189AH1-679 GEN
Adder
1.471
3143873LANEXA
Solar/Wind Harmer
0.052
3142433PROV 92
Adder
0.157
3142433PROV 92
Adder
0.157
971167AH1-042 GEN
Solar/Wind Harmer
7.034
3138283WHITEMARSH
Solar/Wind Harmer
0.018
315976AC1-164 GENA
Solar/Wind Harmer
7.205
316169AC1-164_GENC
Solar/Wind Harmer
6.225
315975AC1-164 GENB
Solar/Wind Harmer
0.213
316312AB1-027
Solar/Wind Harmer
0.12
316132AB2-190 GEN1
Solar/Wind Harmer
0.317
971285AH1-108 GEN
Adder
0.441
316369SG1_INVT
Solar/Wind Harmer
0.002
972265AH1-717 GEN
Adder
4.412
3151201GRAVEL4
Adder
4.136
3151191GRAVEL3
Adder
4.084
3151211GRAVEL5
Adder
4.084
3141426STAFORD
Solar/Wind Helper
0.047
3142433PROV 92
Solar/Wind Harmer
0.322
3142433PROV 92
Adder
0.157
3142433PROV 92
Adder
0.157
3142416OLDCHRC
Solar/Wind Harmer
0.174
3142416OLDCHRC
Solar/Wind Harmer
0.067
971317AH1-138 GEN
Solar/Wind Harmer
0.499
316159AE1-175 C
Solar/Wind Harmer
0.056
944631AF1-128 GEN
Adder
30.632
3143096IRON208
Adder
0.264
3138126ROCKLANDING
Solar/Wind Harmer
0.028
3142543TWELFTH
Solar/Wind Harmer
0.006
970129AG2-093 GEN
Solar/Wind Harmer
1.685
316458AB2-190 GEN2
Solar/Wind Harmer
0.317
315671AE2-027_GEN
Solar/Wind Harmer
3.762
971069AG2-661 GEN
Solar/Wind Harmer
1.042
3150851SPRUNCC
Adder
0.269
971647AH1-324 GEN
Solar/Wind Harmer
2.468
961611AG1-000B GEN
Solar/Wind Harmer
3.01
3151171GRAVELC
Adder
0.604
LAGNLTFEXP_LAGN->PJM
CLTF
1.844
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.3
TVALTFEXP_TVA->PJM
CLTF
0.932
NYPJM->LTFIMP_NY
CLTF
0.726
LGEELTFEXP_LGEE->PJM
CLTF
0.356
WECLTFEXP_WEC->PJM
CLTF
0.179
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.206
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.222
MECLTFEXP_MEC->PJM
CLTF
0.941
SIGELTFEXP_SIGE->PJM
CLTF
0.029
CPLELTFEXP_CPLE->PJM
CLTF
2.387
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.943

Details for 6HANOVER-6FOUR RIVERS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6HANOVER-6FOUR RIVERS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.18 %
Rating:1123.3 MVA
Rating Type:B
MVA to Mitigate:1125.32
MW Contribution:3.02
Bus #Bus NameTypeMW Contribution
3150611CHESTG7
50/50
0.857
3150631CHESTG8
50/50
0.843
316312AB1-027
Solar/Wind Harmer
0.301
971285AH1-108 GEN
Adder
1.017
315976AC1-164 GENA
Solar/Wind Harmer
13.778
316169AC1-164_GENC
Solar/Wind Harmer
11.903
315975AC1-164 GENB
Solar/Wind Harmer
0.408
971167AH1-042 GEN
Solar/Wind Harmer
10.969
316132AB2-190 GEN1
Solar/Wind Harmer
0.662
3142433PROV 92
Adder
0.237
3142433PROV 92
Adder
0.237
316233AE1-074 FULL
Solar/Wind Harmer
0.096
971281AH1-106 GEN
Solar/Wind Harmer
1.657
971283AH1-107 GEN
Solar/Wind Harmer
1.657
316369SG1_INVT
Solar/Wind Harmer
0.004
3143873LANEXA
Solar/Wind Harmer
0.07
316314AB2-024 C
Solar/Wind Harmer
0
3143316POE
Solar/Wind Harmer
0.442
972265AH1-717 GEN
Adder
8.661
3151201GRAVEL4
Adder
8.12
3151191GRAVEL3
Adder
8.017
3151211GRAVEL5
Adder
8.017
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
3.288
315662AE1-191 GEN
Solar/Wind Harmer
0.004
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971445AH1-216 GEN
Solar/Wind Harmer
7.593
3141873WAN 176
Solar/Wind Harmer
0.021
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.071
316311AC2-079 GEN
Solar/Wind Harmer
2.965
3141913WHIT STONE
Solar/Wind Harmer
0.103
3138133OCRAN
Solar/Wind Harmer
0.031
3152611GOSPORTB
Adder
1.285
3152621GOSPORTC
Adder
1.09
3152601GOSPORTA
Adder
1.006
3151081ELIZAR1
Adder
9.234
3151091ELIZAR2
Adder
9.074
3141783LANCAST
Solar/Wind Harmer
0.06
3141783LANCAST
Solar/Wind Harmer
0.04
315835AF2-110_GEN
Solar/Wind Harmer
0.683
316305AF2-043 C
Solar/Wind Harmer
0.001
957871AF2-081 GEN
Solar/Wind Harmer
4.929
319010AE1-072 C
Solar/Wind Harmer
0.497
3146406KITTY HAWK
Solar/Wind Harmer
0.012
313526AB2-022
Solar/Wind Harmer
0.053
3146486SUNBURY
Solar/Wind Harmer
0.098
3146486SUNBURY
Solar/Wind Harmer
0.098
316321Z2-027
Solar/Wind Harmer
0.018
3146396TANGLEW
Solar/Wind Harmer
0.268
3145176PASQUOTANK
Solar/Wind Harmer
0.06
962981AG1-147 GEN
Solar/Wind Harmer
3.537
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
316315AB2-025 C
Solar/Wind Harmer
0.076
315814AE2-033 C
Solar/Wind Harmer
7.456
3130156CHOWAN
Solar/Wind Harmer
0.093
3130156CHOWAN
Solar/Wind Harmer
0.093
970327AG2-215 GEN
Solar/Wind Harmer
3.018
315816AE2-034 GEN
Solar/Wind Harmer
0.39
3130546PLYMOUTH
Solar/Wind Harmer
0.089
315732AD1-074 GEN1
Solar/Wind Harmer
0.51
315733AD1-074 GEN2
Solar/Wind Harmer
0.51
315735AD1-075 GEN1
Solar/Wind Harmer
0.255
965291AG1-394 GEN
Solar/Wind Harmer
0.392
3146206CASHIE
Solar/Wind Harmer
0.088
970601AG2-382 GEN
Solar/Wind Harmer
3.275
972193AH1-681 GEN
Adder
2.005
3145893MURPHYS
Solar/Wind Harmer
0.235
3145893MURPHYS
Solar/Wind Harmer
0.087
3145513AHOSKIE
Solar/Wind Harmer
0.179
3145513AHOSKIE
Solar/Wind Harmer
0.086
3145683EARLEYS
Solar/Wind Harmer
0.17
3145683EARLEYS
Solar/Wind Harmer
0.085
3145683EARLEYS
Solar/Wind Harmer
0.085
3146043SEABORD
Solar/Wind Harmer
0.084
315607AA1-063A GEN
Solar/Wind Harmer
0.172
315652AC1-086 GEN
Solar/Wind Harmer
9.127
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.328
3145796HORNRTN
Solar/Wind Harmer
0.261
3145796HORNRTN
Solar/Wind Harmer
0.033
3146033SCOT NK
Solar/Wind Harmer
0.324
941031AE2-094 GEN
Solar/Wind Harmer
14.626
944011AF1-069 GEN
Solar/Wind Harmer
4.779
3141813NORNECK
Solar/Wind Harmer
0.079
970673AG2-436 GEN
Solar/Wind Harmer
16.734
970673AG2-436 GEN
Solar/Wind Harmer
11.156
316005AA1-067
Solar/Wind Harmer
0.084
3145746EVERETS
Solar/Wind Harmer
0.31
3145746EVERETS
Solar/Wind Harmer
0.078
3145746EVERETS
Solar/Wind Harmer
0.078
3145746EVERETS
Solar/Wind Harmer
0.078
970181AG2-120 GEN
Solar/Wind Harmer
0.97
971967AH1-528 GEN
Solar/Wind Harmer
12.447
957861AF2-080 GEN
Solar/Wind Harmer
3.293
316420AA1-050 GEN
Solar/Wind Harmer
0.002
970831AG2-522 GEN
Solar/Wind Harmer
3.224
970085AG2-068 GEN
Solar/Wind Harmer
4.006
970581AG2-369 GEN
Solar/Wind Harmer
3.445
3145573BETHELC
Solar/Wind Harmer
0.075
3145573BETHELC
Solar/Wind Harmer
0.075
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
1.169
3144303KENBRDG
Solar/Wind Harmer
0.056
970683AG2-441 GEN
Solar/Wind Harmer
4.609
970681AG2-440 GEN
Solar/Wind Harmer
3.687
946301AF1-294 GEN
Solar/Wind Harmer
1.357
961791AG1-021 GEN
Solar/Wind Harmer
0.66
315657AE1-056 GEN
Solar/Wind Harmer
2.362
316118AC1-105 GEN
Solar/Wind Harmer
0.169
970285AG2-188 GEN
Solar/Wind Harmer
5.153
971845AH1-439 GEN
Solar/Wind Harmer
2.936
3147173SINAI
Solar/Wind Harmer
0.064
3147243WELCO
Solar/Wind Harmer
0.04
972205AH1-687 GEN
Adder
2.638
970865AG2-541 GEN
Solar/Wind Harmer
2.043
971447AH1-217 GEN
Solar/Wind Harmer
1.766
3141426STAFORD
Solar/Wind Helper
0.033
3143096IRON208
50/50
0.63
3150641CHESTS8
50/50
0.434
3142416OLDCHRC
Solar/Wind Harmer
0.437
3142416OLDCHRC
Solar/Wind Harmer
0.168
3142543TWELFTH
Solar/Wind Harmer
0.014
944631AF1-128 GEN
Adder
64.319
3150851SPRUNCC
Adder
0.622
315671AE2-027_GEN
Solar/Wind Harmer
8.029
970129AG2-093 GEN
Solar/Wind Harmer
3.524
316458AB2-190 GEN2
Solar/Wind Harmer
0.662
3142433PROV 92
Solar/Wind Harmer
0.488
3142433PROV 92
Adder
0.237
3142433PROV 92
Adder
0.237
971069AG2-661 GEN
Solar/Wind Harmer
2.148
3143526WINTERP
Solar/Wind Harmer
0.621
316159AE1-175 C
Solar/Wind Harmer
0.102
971647AH1-324 GEN
Solar/Wind Harmer
4.981
961611AG1-000B GEN
Solar/Wind Harmer
6.001
3151171GRAVELC
Adder
1.187
971317AH1-138 GEN
Solar/Wind Harmer
0.83
3141766HARMONY
Solar/Wind Harmer
0.022
971777AH1-397 GEN
Solar/Wind Harmer
0.293
3141843SHACKLE
Adder
0.567
3138126ROCKLANDING
Solar/Wind Harmer
0.051
970659AG2-427 GEN
Solar/Wind Harmer
5.319
316381AD1-082 GEN
Solar/Wind Harmer
0.114
970661AG2-428 GEN
Solar/Wind Harmer
10.707
971645AH1-323 GEN
50/50
17.435
3143096IRON208
50/50
0.63
3143096IRON208
50/50
0.617
316473AC1-191 GEN
Solar/Wind Harmer
0.571
3142416OLDCHRC
Solar/Wind Harmer
1.631
970293AG2-193 GEN
Solar/Wind Harmer
1.601
3150861SPRUNCD
Adder
0.622
3142946ENON
Solar/Wind Harmer
0.045
970133AG2-095 GEN
Solar/Wind Harmer
1.231
970129AG2-093 GEN
Solar/Wind Harmer
7.489
965281AG1-393 GEN
Solar/Wind Harmer
1.32
315839AE2-212 C
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.237
3142433PROV 92
Adder
0.237
315778AD1-151 GEN
Solar/Wind Harmer
9.667
316382AG1-145 C
Solar/Wind Harmer
0.001
961611AG1-000B GEN
Solar/Wind Harmer
3.052
315813AE1-149 C
Solar/Wind Harmer
6.039
3151221GRAVEL6
Adder
8.11
3151171GRAVELC
Adder
1.56
3141766HARMONY
Solar/Wind Harmer
1.48
3141843SHACKLE
Adder
0.567
316203AE2-005 GEN
Solar/Wind Harmer
0
3144216WINCHST
Adder
0.416
3150921YORKTN3
Adder
2.767
970659AG2-427 GEN
Solar/Wind Harmer
1.163
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.002
971781AH1-399 GEN
Solar/Wind Harmer
0.143
970661AG2-428 GEN
Solar/Wind Harmer
2.277
3145336SMITFLD
Solar/Wind Harmer
0.043
316156AD2-030 GEN
Solar/Wind Harmer
0.079
3141873WAN 176
Solar/Wind Harmer
1.904
3144536CHRHLND
Solar/Wind Harmer
0.015
3144873MCLAUGH
Solar/Wind Harmer
0.003
3151101ELIZAR3
Adder
9.352
315773AC2-141 GEN
Solar/Wind Harmer
3.646
944581AF1-123 GEN
Solar/Wind Harmer
22.395
944601AF1-125 GEN
Solar/Wind Harmer
22.05
3146456SLIGO L269
Solar/Wind Harmer
0.099
971153AH1-033 GEN
Solar/Wind Harmer
1.142
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.096
3145273HOLLAND
Solar/Wind Harmer
0.072
3146626S HERTFORD
Solar/Wind Harmer
0.096
962971AG1-146 GEN
Solar/Wind Harmer
1.516
3146376EDENTON
Solar/Wind Harmer
0.093
970009AG2-005 GEN
Solar/Wind Harmer
0.687
315614AA2-178 GEN
Solar/Wind Harmer
0.521
971157AH1-035 GEN
Solar/Wind Harmer
1.07
315737AD1-076 GEN
Solar/Wind Harmer
1.143
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146206CASHIE
Solar/Wind Harmer
0.088
972255AH1-712 GEN
Adder
44.865
316404AE1-155 C
Solar/Wind Harmer
0.02
3145893MURPHYS
Solar/Wind Harmer
0.146
3145893MURPHYS
Solar/Wind Harmer
0.087
957521AF2-046 GEN
Solar/Wind Harmer
6.466
961681AG1-008 GEN
Solar/Wind Harmer
6.466
316365GEN2_N
Solar/Wind Harmer
0.195
316313AB2-026
Solar/Wind Harmer
0.055
316258AE1-075 C
Solar/Wind Harmer
0.065
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
1.308
3146173TUNIS
Solar/Wind Harmer
0.086
3156021HOLLOMANSOL
Solar/Wind Harmer
0.391
316463AE2-346 GEN
Solar/Wind Harmer
0.074
316140AB2-099
Solar/Wind Harmer
0.031
962331AG1-082 GEN
Solar/Wind Harmer
0.914
3146263WOODLND
Solar/Wind Harmer
0.084
3145963POPLR C
Solar/Wind Harmer
0.084
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
316317KELFORD C
Solar/Wind Harmer
0.008
3145823KELFORD
Solar/Wind Harmer
0.083
313506AB2-031 GEN
Solar/Wind Harmer
0.255
3145796HORNRTN
Solar/Wind Harmer
0.326
3145796HORNRTN
Solar/Wind Harmer
0.082
3145933PARMELE
Solar/Wind Harmer
0.08
966801AG1-551 GEN
Solar/Wind Harmer
0.93
3147043LAWRENC
Solar/Wind Harmer
0.048
316210AC1-098 GEN
Solar/Wind Harmer
0.737
3150351NORNECKC2
Adder
0.804
3145746EVERETS
Solar/Wind Harmer
0.078
3145746EVERETS
Solar/Wind Harmer
0.078
315724AD1-057 GEN
Solar/Wind Harmer
0.289
316327AA2-057 GEN
Solar/Wind Harmer
0.115
970917AG2-570 GEN
Solar/Wind Harmer
6.696
3146073TAR RVR
Solar/Wind Harmer
0.075
3146083TARBORO
Solar/Wind Harmer
0.075
3146233WITAKRS
Solar/Wind Harmer
0.375
3146233WITAKRS
Solar/Wind Harmer
0.051
3138543CONSLDL
Solar/Wind Harmer
0.049
961601AG1-000A GEN
Solar/Wind Harmer
5.215
3145543BTLEBRO
Solar/Wind Harmer
0.073
3145543BTLEBRO
Solar/Wind Harmer
0.073
971623AH1-311 GEN
Solar/Wind Harmer
0.147
316478AD1-087 GEN
Solar/Wind Harmer
0.249
316486AD2-202 GEN
Solar/Wind Harmer
0.073
316131AB2-060 GEN
Solar/Wind Harmer
0.221
964241AG1-285 GEN
Solar/Wind Harmer
4.675
315785AD2-033 C
Solar/Wind Harmer
0.567
970257AG2-171 GEN
Solar/Wind Harmer
2.225
959311AF2-222 GEN
Solar/Wind Harmer
6.171
970909AG2-566 GEN
Solar/Wind Harmer
0.738
963181AG1-167 GEN
Solar/Wind Harmer
0.275
3144293JTRSVLE
Adder
0.219
3147133PAMPLIN
Solar/Wind Harmer
0.215
971193AH1-056 GEN
Solar/Wind Harmer
4.17
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.04
3146776BUCKING
Solar/Wind Harmer
0.023
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.742
971683AH1-343 GEN
Solar/Wind Harmer
2.232
316283AC2-100 C
Solar/Wind Harmer
0.116
970221AG2-151 GEN
Solar/Wind Harmer
3.149
966881AG1-559 GEN
Solar/Wind Helper
1.213
3142296MT RD221
50/50
0.632
3142366NRTHEST
50/50
0.551
3150691DARBY 3
50/50
11.896
3150701DARBY 4
50/50
11.869
3150681DARBY 2
50/50
11.855
3150671DARBY 1
50/50
11.841
3150621CHESTS7
50/50
0.394
966871AG1-558 GEN
Solar/Wind Harmer
0.195
316075AC2-137 C
Solar/Wind Harmer
0.04
3142946ENON
Solar/Wind Harmer
0.013
944641AF1-129 GEN
Adder
63.125
316240AF1-291 C
Solar/Wind Harmer
0.001
3143526WINTERP
Solar/Wind Harmer
0.621
316033AB2-134 GEN
Solar/Wind Harmer
0.007
315697AD1-025 GEN
Solar/Wind Harmer
0.134
316468AD1-105 GEN
Solar/Wind Harmer
-0.035
970657AG2-426 GEN
Solar/Wind Harmer
3.808
970657AG2-426 GEN
Solar/Wind Harmer
0.798
316236AE1-162_GEN
Solar/Wind Harmer
0.001
971223AH1-071 GEN
Solar/Wind Harmer
1.1
316036AC1-147 C
Solar/Wind Harmer
0.019
3150991CHESPKB
Adder
1.057
3150991CHESPKB
Adder
1.031
316316AC1-027 C
Solar/Wind Harmer
0.096
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.003
3145506HICKORY
Solar/Wind Harmer
0.398
3145506HICKORY
Solar/Wind Harmer
0.239
3145506HICKORY
Solar/Wind Harmer
0.06
316339AD2-160 GEN
Solar/Wind Harmer
0.161
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.055
3137176SLIGO L2192
Solar/Wind Harmer
0.393
3146456SLIGO L269
Solar/Wind Harmer
1.748
3130086AYDLETT
Solar/Wind Harmer
0.394
3146386ELIZ CT
Solar/Wind Harmer
0.098
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.096
3146516WINFALL
Solar/Wind Harmer
0.096
3146516WINFALL
Solar/Wind Harmer
0.096
3146626S HERTFORD
Solar/Wind Harmer
0.096
3146626S HERTFORD
Solar/Wind Harmer
0.096
3144356SAPONY
Solar/Wind Harmer
0.792
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.415
3146376EDENTON
Solar/Wind Harmer
0.415
316065AD1-022 GEN
Solar/Wind Harmer
4.058
958261AF2-120 GEN
Solar/Wind Harmer
2.891
3145893MURPHYS
Solar/Wind Harmer
0.583
3145893MURPHYS
Solar/Wind Harmer
0.157
3146173TUNIS
Solar/Wind Harmer
0.086
3146173TUNIS
Solar/Wind Harmer
0.086
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.05
316181AB2-040 GEN
Solar/Wind Harmer
0.12
316426AA2-053 GEN
Solar/Wind Harmer
0.278
3145796HORNRTN
Solar/Wind Harmer
0.245
3145593CAROLNA
Solar/Wind Harmer
0.082
3145593CAROLNA
Solar/Wind Harmer
0.082
966811AG1-552 GEN
Solar/Wind Harmer
0.885
3145593CAROLNA
Solar/Wind Harmer
0.102
3145783HORNRTN
Solar/Wind Harmer
1.442
3145783HORNRTN
Solar/Wind Harmer
1.154
3145783HORNRTN
Solar/Wind Harmer
0.361
3145783HORNRTN
Solar/Wind Harmer
0.144
3145933PARMELE
Solar/Wind Harmer
0.16
3145933PARMELE
Solar/Wind Harmer
0.08
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.831
3150341NORNECKC1
Adder
0.824
316274AC1-208 GEN
Solar/Wind Harmer
0.408
972185AH1-677 GEN
Adder
4.375
972187AH1-678 GEN
Adder
2.202
970933AG2-581 GEN
Solar/Wind Harmer
6.122
3145493TOT1
Solar/Wind Harmer
0.174
3145453TOT5
Solar/Wind Harmer
0.104
3145603CNETO
Solar/Wind Harmer
0.07
961601AG1-000A GEN
Solar/Wind Harmer
1.304
316263AC1-034 GEN
Solar/Wind Harmer
2.784
970099AG2-077 GEN
Solar/Wind Harmer
7.81
939181AE1-148 GEN
Solar/Wind Harmer
3.417
313527AB2-043 GEN
Solar/Wind Harmer
0.001
971741AH1-377 GEN
Solar/Wind Harmer
6.934
316034AC1-036 C
Solar/Wind Harmer
0.005
970323AG2-213 GEN
Solar/Wind Harmer
2.967
971775AH1-396 GEN
Solar/Wind Harmer
0.111
970301AG2-198 GEN
Solar/Wind Harmer
2.952
958211AF2-115 GEN
Solar/Wind Harmer
0.825
963191AG1-168 GEN
Solar/Wind Harmer
0.275
3144293JTRSVLE
Adder
0.219
3144293JTRSVLE
Adder
0.184
3147133PAMPLIN
Solar/Wind Harmer
0.068
3147133PAMPLIN
Solar/Wind Harmer
0.055
962561AG1-105 GEN
Solar/Wind Harmer
3.235
964791AG1-342 GEN
Solar/Wind Harmer
1.284
3146843MT LREL
Solar/Wind Harmer
0.067
3146843MT LREL
Solar/Wind Harmer
0.067
3146776BUCKING
Solar/Wind Harmer
0.258
3146776BUCKING
Solar/Wind Harmer
0.021
316222AC1-221 GEN
Solar/Wind Harmer
0.248
971489AH1-241 GEN
Solar/Wind Harmer
3.149
3145336SMITFLD
Solar/Wind Harmer
0.43
3143226MDLTHAN
Solar/Wind Harmer
0.103
316072AD1-144
Solar/Wind Harmer
0.037
3138133OCRAN
Solar/Wind Harmer
0.061
316375AC2-012 GEN
Solar/Wind Harmer
0.003
3150981CHESPKA
Adder
1.26
316294AC1-161 GEN
Solar/Wind Harmer
1.73
316093AE2-104_GEN
Solar/Wind Harmer
1.674
944591AF1-124 GEN
Solar/Wind Harmer
22.475
316388AE2-253 GEN
Solar/Wind Harmer
0.31
316246AF1-032 C
Solar/Wind Harmer
0.045
3146456SLIGO L269
Solar/Wind Harmer
0.099
3146516WINFALL
Solar/Wind Harmer
0.312
3146516WINFALL
Solar/Wind Harmer
0.096
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.093
3145663CRESWEL
Solar/Wind Harmer
0.255
971163AH1-040 GEN
Solar/Wind Harmer
7.278
962861AG1-135 GEN
Solar/Wind Harmer
2.836
939411AE1-173 GEN
Solar/Wind Harmer
37.741
3146206CASHIE
Solar/Wind Harmer
0.088
971547AH1-271 GEN
Solar/Wind Harmer
1.872
972277AH1-723 GEN
Adder
52.282
3145893MURPHYS
Solar/Wind Harmer
0.349
3145893MURPHYS
Solar/Wind Harmer
0.388
316023GEN1_S
Solar/Wind Harmer
0.195
3143336POWHATN
Solar/Wind Harmer
1.539
3146173TUNIS
Solar/Wind Harmer
0.086
3145683EARLEYS
Solar/Wind Harmer
0.085
940641AE2-051 GEN
Solar/Wind Harmer
6.781
3146263WOODLND
Solar/Wind Harmer
0.084
3141726DUNNSVL
Solar/Wind Harmer
0.336
3145963POPLR C
Solar/Wind Harmer
0.084
960081AF2-299 GEN
Solar/Wind Harmer
0.803
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145823KELFORD
Solar/Wind Harmer
0.083
316011AB1-132 GEN
Solar/Wind Harmer
1.509
962571AG1-106 GEN
Solar/Wind Harmer
1.181
316336AC2-165 C
Solar/Wind Harmer
0.003
316190AA2-174 GEN
Solar/Wind Harmer
0
3145796HORNRTN
Solar/Wind Harmer
0.269
3145796HORNRTN
Solar/Wind Harmer
0.082
3145783HORNRTN
Solar/Wind Harmer
0.081
971795AH1-408 GEN
Solar/Wind Harmer
5.392
3146293MARTNCO
Solar/Wind Harmer
0.074
3147043LAWRENC
Adder
0.72
316212AC1-099_GEN
Solar/Wind Harmer
0.411
3150351NORNECKC2
Adder
0.791
3145746EVERETS
Solar/Wind Harmer
0.078
3145746EVERETS
Solar/Wind Harmer
0.078
315722AD1-056 GEN
Solar/Wind Harmer
0.488
316494AC1-189 GEN
Solar/Wind Harmer
0.258
970919AG2-571 GEN
Solar/Wind Harmer
2.678
970087AG2-069 GEN
Solar/Wind Harmer
6.009
961671AG1-007 GEN
Solar/Wind Harmer
0.011
3146083TARBORO
Solar/Wind Harmer
0.075
3145493TOT1
Solar/Wind Harmer
0.333
316129AC1-054 GEN
Solar/Wind Harmer
0.282
3146233WITAKRS
Solar/Wind Harmer
0.297
971065AG2-659 GEN
Solar/Wind Harmer
3.171
316359AB2-059 GEN
Solar/Wind Harmer
0.263
316049AB1-081 GEN
Solar/Wind Harmer
0.419
3145543BTLEBRO
Solar/Wind Harmer
0.073
3145543BTLEBRO
Solar/Wind Harmer
0.059
3142053HEARTS
Solar/Wind Harmer
0.129
957481AF2-042 GEN
Solar/Wind Harmer
19.524
315693AD1-088 GEN
Solar/Wind Harmer
3.47
962491AG1-098 GEN
Solar/Wind Harmer
4.117
970937AG2-583 GEN
Solar/Wind Harmer
4.364
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970685AG2-442 GEN
Solar/Wind Harmer
5.162
963171AG1-166 GEN
Solar/Wind Harmer
0.367
971563AH1-280 GEN
Solar/Wind Harmer
0.733
3144293JTRSVLE
Adder
0.219
315687AD1-152 GEN
Solar/Wind Harmer
0.002
3146926FARMVIL
Solar/Wind Harmer
0.04
970401AG2-262 GEN
Solar/Wind Harmer
0.392
316337AD2-073 GEN
Solar/Wind Harmer
0.057
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.026
316003AC1-222 GEN
Solar/Wind Harmer
0.002
972003AH1-546 GEN
Solar/Wind Harmer
2.646
971377AH1-170 GEN
Solar/Wind Harmer
0.63
3147623JAMES R
Solar/Wind Harmer
0.137
LAGNLTFEXP_LAGN->PJM
CLTF
4.321
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.837
TVALTFEXP_TVA->PJM
CLTF
2.185
NYPJM->LTFIMP_NY
CLTF
0.971
LGEELTFEXP_LGEE->PJM
CLTF
0.994
WECLTFEXP_WEC->PJM
CLTF
0.514
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.476
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.705
MECLTFEXP_MEC->PJM
CLTF
2.537
SIGELTFEXP_SIGE->PJM
CLTF
0.079
CPLELTFEXP_CPLE->PJM
CLTF
4.707
CBM West 2LTFEXP_CBM-W2->PJM
CBM
24.626

Details for 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6IRON208-6SOUWEST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.96 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:689.92
MW Contribution:2.82
Bus #Bus NameTypeMW Contribution
3143096IRON208
50/50
2.365
3143096IRON208
50/50
2.318
3150801HOPHCF4
50/50
0.81
971211AH1-065 GEN
50/50
0.977
315749AE2-041 GEN
50/50
3.414
3151161SURRY 1
50/50
3.592
3142946ENON
Solar/Wind Harmer
0.072
970133AG2-095 GEN
Solar/Wind Harmer
1.318
970129AG2-093 GEN
Solar/Wind Harmer
7.619
315778AD1-151 GEN
Solar/Wind Harmer
9.439
961611AG1-000B GEN
Solar/Wind Harmer
2.697
3141766HARMONY
Solar/Wind Harmer
1.28
316382AG1-145 C
Solar/Wind Harmer
0.001
3151221GRAVEL6
Adder
6.799
3151171GRAVELC
Adder
1.308
3141843SHACKLE
Adder
0.471
316203AE2-005 GEN
Solar/Wind Harmer
0
316280AD1-041 GEN
Solar/Wind Harmer
0.002
316156AD2-030 GEN
Solar/Wind Harmer
0.068
3141873WAN 176
Solar/Wind Harmer
1.624
962971AG1-146 GEN
Solar/Wind Harmer
1.39
970009AG2-005 GEN
Solar/Wind Harmer
0.641
3142433PROV 92
Adder
0.165
3142433PROV 92
Adder
0.165
3144216WINCHST
Adder
0.319
316404AE1-155 C
Solar/Wind Harmer
0.019
3145336SMITFLD
Solar/Wind Harmer
0.033
3150921YORKTN3
Adder
2.093
3150351NORNECKC2
Adder
0.824
3144536CHRHLND
Solar/Wind Harmer
0.011
315813AE1-149 C
Solar/Wind Harmer
3.817
970659AG2-427 GEN
Solar/Wind Harmer
0.738
316083AB2-161 GEN
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.45
3144873MCLAUGH
Solar/Wind Harmer
0.002
3151101ELIZAR3
Adder
6.266
3141906WESTMOR
Solar/Wind Harmer
0.027
944581AF1-123 GEN
Solar/Wind Harmer
14.477
944601AF1-125 GEN
Solar/Wind Harmer
14.254
3146456SLIGO L269
Solar/Wind Harmer
0.064
971153AH1-033 GEN
Solar/Wind Harmer
0.742
316320Y1-086
Solar/Wind Harmer
0
315773AC2-141 GEN
Solar/Wind Harmer
2.272
316435W1029_GEN3
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.061
965281AG1-393 GEN
Solar/Wind Harmer
0.649
3146626S HERTFORD
Solar/Wind Harmer
0.06
970737AG2-469 GEN
Solar/Wind Harmer
2.555
3145273HOLLAND
Solar/Wind Harmer
0.045
3146376EDENTON
Solar/Wind Harmer
0.057
3150611CHESTG7
50/50
1.633
3150631CHESTG8
50/50
1.607
971047AG2-646 GEN
50/50
45.726
315759AF1-018 GEN
50/50
3.414
316132AB2-190 GEN1
Solar/Wind Harmer
0.67
315976AC1-164 GENA
Solar/Wind Harmer
12.162
316169AC1-164_GENC
Solar/Wind Harmer
10.507
315975AC1-164 GENB
Solar/Wind Harmer
0.36
316369SG1_INVT
Solar/Wind Harmer
0.004
316314AB2-024 C
Solar/Wind Harmer
0
316059AD1-063 C
Solar/Wind Harmer
0.001
972265AH1-717 GEN
Adder
7.261
3151201GRAVEL4
Adder
6.807
3151191GRAVEL3
Adder
6.721
3151211GRAVEL5
Adder
6.721
3143873LANEXA
Solar/Wind Harmer
0.056
970189AG2-124 GEN
Solar/Wind Harmer
2.733
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.018
3141913WHIT STONE
Solar/Wind Harmer
0.09
3138133OCRAN
Solar/Wind Harmer
0.027
3141783LANCAST
Solar/Wind Harmer
0.053
3141783LANCAST
Solar/Wind Harmer
0.035
3138283WHITEMARSH
Solar/Wind Harmer
0.02
962981AG1-147 GEN
Solar/Wind Harmer
3.244
970327AG2-215 GEN
Solar/Wind Harmer
2.818
3142433PROV 92
Adder
0.165
3142433PROV 92
Adder
0.165
971445AH1-216 GEN
Solar/Wind Harmer
5.957
971167AH1-042 GEN
Solar/Wind Harmer
7.355
3141813NORNECK
Solar/Wind Harmer
0.081
3152611GOSPORTB
Adder
0.865
3152621GOSPORTC
Adder
0.734
3152601GOSPORTA
Adder
0.677
3151081ELIZAR1
Adder
6.186
3151091ELIZAR2
Adder
6.079
316223AC1-118
Solar/Wind Harmer
0.048
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.045
316311AC2-079 GEN
Solar/Wind Harmer
1.899
316305AF2-043 C
Solar/Wind Harmer
0.001
957871AF2-081 GEN
Solar/Wind Harmer
3.21
319010AE1-072 C
Solar/Wind Harmer
0.323
315835AF2-110_GEN
Solar/Wind Harmer
0.44
3146406KITTY HAWK
Solar/Wind Harmer
0.008
313526AB2-022
Solar/Wind Harmer
0.034
3146486SUNBURY
Solar/Wind Harmer
0.063
3146486SUNBURY
Solar/Wind Harmer
0.063
316321Z2-027
Solar/Wind Harmer
0.012
3146396TANGLEW
Solar/Wind Harmer
0.172
3145176PASQUOTANK
Solar/Wind Harmer
0.039
315611Z1-036_GEN2
Solar/Wind Harmer
0
3130156CHOWAN
Solar/Wind Harmer
0.057
3130156CHOWAN
Solar/Wind Harmer
0.057
316233AE1-074 FULL
Solar/Wind Helper
0.475
3143096IRON208
50/50
2.365
3150641CHESTS8
50/50
0.828
944631AF1-128 GEN
50/50
130.091
3150771HOPHCF1
50/50
0.557
3152331SURRY 2
50/50
2.862
970129AG2-093 GEN
Solar/Wind Harmer
3.585
316458AB2-190 GEN2
Solar/Wind Harmer
0.67
971069AG2-661 GEN
Solar/Wind Harmer
2.098
971647AH1-324 GEN
Solar/Wind Harmer
4.574
961611AG1-000B GEN
Solar/Wind Harmer
5.304
3141766HARMONY
Solar/Wind Harmer
0.019
316159AE1-175 C
Solar/Wind Harmer
0.081
3151171GRAVELC
Adder
0.995
971777AH1-397 GEN
Solar/Wind Harmer
0.243
3141843SHACKLE
Adder
0.471
3138133OCRAN
Solar/Wind Harmer
0.054
971317AH1-138 GEN
Solar/Wind Harmer
0.639
3142433PROV 92
Solar/Wind Harmer
0.34
3142433PROV 92
Adder
0.165
3142433PROV 92
Adder
0.165
962861AG1-135 GEN
Solar/Wind Harmer
2.709
3141726DUNNSVL
Solar/Wind Harmer
0.337
3138126ROCKLANDING
Solar/Wind Harmer
0.039
3145336SMITFLD
Solar/Wind Harmer
0.335
3150351NORNECKC2
Adder
0.811
316337AD2-073 GEN
Solar/Wind Harmer
0.065
316072AD1-144
Solar/Wind Harmer
0.026
970659AG2-427 GEN
Solar/Wind Harmer
3.376
316381AD1-082 GEN
Solar/Wind Harmer
0.072
970661AG2-428 GEN
Solar/Wind Harmer
6.816
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.848
316246AF1-032 C
Solar/Wind Harmer
0.029
316388AE2-253 GEN
Solar/Wind Harmer
0.202
944591AF1-124 GEN
Solar/Wind Harmer
14.529
3146456SLIGO L269
Solar/Wind Harmer
0.064
316093AE2-104_GEN
Solar/Wind Harmer
1.078
316294AC1-161 GEN
Solar/Wind Harmer
1.078
3146516WINFALL
Solar/Wind Harmer
0.198
3146516WINFALL
Solar/Wind Harmer
0.061
315671AE2-027_GEN
Solar/Wind Harmer
3.892
315800Z1-036_GEN1
Solar/Wind Harmer
0
3130156CHOWAN
Solar/Wind Harmer
0.057
3143526WINTERP
Solar/Wind Helper
1.618
3143226MDLTHAN
Solar/Wind Helper
0.118
3150621CHESTS7
50/50
0.75
3150781HOPHCF2
50/50
0.557
3150791HOPHCF3
50/50
0.557
3150761HOPPOLC
50/50
0.353
971213AH1-066 GEN
50/50
0.488
3142946ENON
Solar/Wind Harmer
0.022
316033AB2-134 GEN
Solar/Wind Harmer
0.007
315697AD1-025 GEN
Solar/Wind Harmer
0.127
958261AF2-120 GEN
Solar/Wind Harmer
2.785
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316075AC2-137 C
Solar/Wind Harmer
0.023
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.851
3150341NORNECKC1
Adder
0.845
970657AG2-426 GEN
Solar/Wind Harmer
2.421
970657AG2-426 GEN
Solar/Wind Harmer
0.507
316036AC1-147 C
Solar/Wind Harmer
0.013
3150991CHESPKB
Adder
0.712
3150991CHESPKB
Adder
0.694
316316AC1-027 C
Solar/Wind Harmer
0.064
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3145506HICKORY
Solar/Wind Harmer
0.26
3145506HICKORY
Solar/Wind Harmer
0.156
3145506HICKORY
Solar/Wind Harmer
0.039
316339AD2-160 GEN
Solar/Wind Harmer
0.105
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.036
3137176SLIGO L2192
Solar/Wind Harmer
0.256
3146456SLIGO L269
Solar/Wind Harmer
1.137
3130086AYDLETT
Solar/Wind Harmer
0.256
3146386ELIZ CT
Solar/Wind Harmer
0.063
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.061
3146516WINFALL
Solar/Wind Harmer
0.061
3146516WINFALL
Solar/Wind Harmer
0.061
3146626S HERTFORD
Solar/Wind Harmer
0.06
3146626S HERTFORD
Solar/Wind Harmer
0.06
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.255
3146376EDENTON
Solar/Wind Harmer
0.255
3143526WINTERP
Solar/Wind Helper
1.618
LAGNLTFEXP_LAGN->PJM
CLTF
0.804
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.434
TVALTFEXP_TVA->PJM
CLTF
0.397
NYPJM->LTFIMP_NY
CLTF
0.33
LGEELTFEXP_LGEE->PJM
CLTF
0.057
WECLTFEXP_WEC->PJM
CLTF
0.026
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.657
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.279
MECLTFEXP_MEC->PJM
CLTF
0.223
SIGELTFEXP_SIGE->PJM
CLTF
0.006
CPLELTFEXP_CPLE->PJM
CLTF
1.734
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.554

Details for 6IRON208-6SOUWEST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6IRON208-6SOUWEST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.72 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:668.44
MW Contribution:2.22
Bus #Bus NameTypeMW Contribution
3150611CHESTG7
50/50
1.535
3150631CHESTG8
50/50
1.511
971047AG2-646 GEN
50/50
42.989
316132AB2-190 GEN1
Solar/Wind Harmer
0.61
316369SG1_INVT
Solar/Wind Harmer
0.004
315976AC1-164 GENA
Solar/Wind Harmer
9.735
316169AC1-164_GENC
Solar/Wind Harmer
8.41
315975AC1-164 GENB
Solar/Wind Harmer
0.288
972265AH1-717 GEN
Adder
6.312
3151201GRAVEL4
Adder
5.917
3151191GRAVEL3
Adder
5.842
3151211GRAVEL5
Adder
5.842
316314AB2-024 C
Solar/Wind Harmer
0
316059AD1-063 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.045
970189AG2-124 GEN
Solar/Wind Harmer
2.166
971445AH1-216 GEN
Solar/Wind Harmer
5.125
315662AE1-191 GEN
Solar/Wind Harmer
0.002
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.014
3141913WHIT STONE
Solar/Wind Harmer
0.071
3138133OCRAN
Solar/Wind Harmer
0.021
3141783LANCAST
Solar/Wind Harmer
0.042
3141783LANCAST
Solar/Wind Harmer
0.028
3138283WHITEMARSH
Solar/Wind Harmer
0.016
962981AG1-147 GEN
Solar/Wind Harmer
2.557
3142433PROV 92
Adder
0.133
3142433PROV 92
Adder
0.133
970327AG2-215 GEN
Solar/Wind Harmer
2.22
971167AH1-042 GEN
Solar/Wind Harmer
5.919
3141813NORNECK
Solar/Wind Harmer
0.064
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.04
316311AC2-079 GEN
Solar/Wind Harmer
1.663
3152611GOSPORTB
Adder
0.725
3152621GOSPORTC
Adder
0.615
3152601GOSPORTA
Adder
0.568
3151081ELIZAR1
Adder
5.179
3151091ELIZAR2
Adder
5.089
316233AE1-074 FULL
Solar/Wind Helper
0.525
3150621CHESTS7
50/50
0.705
3150781HOPHCF2
50/50
0.513
3150791HOPHCF3
50/50
0.513
3150761HOPPOLC
50/50
0.325
971213AH1-066 GEN
50/50
0.45
3142946ENON
Solar/Wind Harmer
0.02
316033AB2-134 GEN
Solar/Wind Harmer
0.006
315697AD1-025 GEN
Solar/Wind Harmer
0.114
316236AE1-162_GEN
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
2.192
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.669
3150341NORNECKC1
Adder
0.663
316075AC2-137 C
Solar/Wind Harmer
0.018
970657AG2-426 GEN
Solar/Wind Harmer
2.184
970657AG2-426 GEN
Solar/Wind Harmer
0.458
316036AC1-147 C
Solar/Wind Harmer
0.011
3150991CHESPKB
Adder
0.596
3150991CHESPKB
Adder
0.582
3143526WINTERP
Solar/Wind Helper
1.788
3143096IRON208
50/50
2.307
3143096IRON208
50/50
2.26
3150801HOPHCF4
50/50
0.746
971211AH1-065 GEN
50/50
0.9
3151161SURRY 1
50/50
3.123
3142946ENON
Solar/Wind Harmer
0.066
970133AG2-095 GEN
Solar/Wind Harmer
1.215
970129AG2-093 GEN
Solar/Wind Harmer
6.944
315778AD1-151 GEN
Solar/Wind Harmer
8.525
961611AG1-000B GEN
Solar/Wind Harmer
2.377
3151221GRAVEL6
Adder
5.91
3151171GRAVELC
Adder
1.137
3141766HARMONY
Solar/Wind Harmer
1.013
316382AG1-145 C
Solar/Wind Harmer
0.001
3141843SHACKLE
Adder
0.374
316203AE2-005 GEN
Solar/Wind Harmer
0
316280AD1-041 GEN
Solar/Wind Harmer
0.001
316156AD2-030 GEN
Solar/Wind Harmer
0.053
3141873WAN 176
Solar/Wind Harmer
1.283
3145336SMITFLD
Solar/Wind Harmer
0.029
962971AG1-146 GEN
Solar/Wind Harmer
1.096
3142433PROV 92
Adder
0.133
3142433PROV 92
Adder
0.133
970009AG2-005 GEN
Solar/Wind Harmer
0.505
3144216WINCHST
Adder
0.253
316404AE1-155 C
Solar/Wind Harmer
0.015
315813AE1-149 C
Solar/Wind Harmer
3.52
3150921YORKTN3
Adder
1.637
3150351NORNECKC2
Adder
0.647
970659AG2-427 GEN
Solar/Wind Harmer
0.67
316083AB2-161 GEN
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.3
3144536CHRHLND
Solar/Wind Harmer
0.009
3144873MCLAUGH
Solar/Wind Harmer
0.001
3151101ELIZAR3
Adder
5.246
3143096IRON208
50/50
2.307
3150641CHESTS8
50/50
0.778
944631AF1-128 GEN
50/50
122.303
3150771HOPHCF1
50/50
0.513
970129AG2-093 GEN
Solar/Wind Harmer
3.268
316458AB2-190 GEN2
Solar/Wind Harmer
0.61
971069AG2-661 GEN
Solar/Wind Harmer
1.894
971647AH1-324 GEN
Solar/Wind Harmer
4.071
961611AG1-000B GEN
Solar/Wind Harmer
4.675
3151171GRAVELC
Adder
0.865
3141766HARMONY
Solar/Wind Harmer
0.015
316159AE1-175 C
Solar/Wind Harmer
0.063
971777AH1-397 GEN
Solar/Wind Harmer
0.193
3141843SHACKLE
Adder
0.374
3145336SMITFLD
Solar/Wind Harmer
0.288
3138133OCRAN
Solar/Wind Harmer
0.042
3142433PROV 92
Solar/Wind Harmer
0.273
3142433PROV 92
Adder
0.133
3142433PROV 92
Adder
0.133
962861AG1-135 GEN
Solar/Wind Harmer
2.133
3138126ROCKLANDING
Solar/Wind Harmer
0.03
3141726DUNNSVL
Solar/Wind Harmer
0.265
971317AH1-138 GEN
Solar/Wind Harmer
0.495
3150351NORNECKC2
Adder
0.637
970659AG2-427 GEN
Solar/Wind Harmer
3.065
316381AD1-082 GEN
Solar/Wind Harmer
0.066
970661AG2-428 GEN
Solar/Wind Harmer
6.114
316072AD1-144
Solar/Wind Harmer
0.022
316337AD2-073 GEN
Solar/Wind Harmer
0.051
316375AC2-012 GEN
Solar/Wind Harmer
0.001
3150981CHESPKA
Adder
0.711
3143526WINTERP
Solar/Wind Helper
1.788
3143226MDLTHAN
Solar/Wind Helper
0.157
LAGNLTFEXP_LAGN->PJM
CLTF
1.059
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.936
TVALTFEXP_TVA->PJM
CLTF
0.526
NYPJM->LTFIMP_NY
CLTF
0.354
LGEELTFEXP_LGEE->PJM
CLTF
0.127
WECLTFEXP_WEC->PJM
CLTF
0.063
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.024
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.746
MECLTFEXP_MEC->PJM
CLTF
0.397
SIGELTFEXP_SIGE->PJM
CLTF
0.011
CPLELTFEXP_CPLE->PJM
CLTF
1.919
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.103

Details for 6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:137.15 %
Rating:1057.5 MVA
Rating Type:B
MVA to Mitigate:1450.33
MW Contribution:2.71
Bus #Bus NameTypeMW Contribution
970119AG2-088 GEN
50/50
52.941
3150851SPRUNCC
50/50
1.044
316303AF2-085
50/50
7.059
971285AH1-108 GEN
50/50
1.708
972205AH1-687 GEN
50/50
6.267
316233AE1-074 FULL
Solar/Wind Harmer
0.255
971281AH1-106 GEN
Solar/Wind Harmer
4.412
971283AH1-107 GEN
Solar/Wind Harmer
4.412
971845AH1-439 GEN
Solar/Wind Harmer
5.597
970285AG2-188 GEN
Solar/Wind Harmer
9.622
971447AH1-217 GEN
Solar/Wind Harmer
3.562
316132AB2-190 GEN1
Solar/Wind Harmer
0.626
3143316POE
Solar/Wind Harmer
0.447
971167AH1-042 GEN
Solar/Wind Harmer
9.861
316369SG1_INVT
Solar/Wind Harmer
0.004
316312AB1-027
Solar/Wind Harmer
0.195
3142433PROV 92
Adder
0.211
3142433PROV 92
Adder
0.211
270494AE1-108_GEN
Solar/Wind Harmer
1.234
315976AC1-164 GENA
Solar/Wind Harmer
10.641
316169AC1-164_GENC
Solar/Wind Harmer
9.193
315975AC1-164 GENB
Solar/Wind Harmer
0.315
315657AE1-056 GEN
Solar/Wind Harmer
3.476
972265AH1-717 GEN
Adder
7.802
3151201GRAVEL4
Adder
7.314
3151191GRAVEL3
Adder
7.221
3151211GRAVEL5
Adder
7.221
3143873LANEXA
Solar/Wind Harmer
0.059
946301AF1-294 GEN
Solar/Wind Harmer
1.948
961791AG1-021 GEN
Solar/Wind Harmer
0.948
316315AB2-025 C
Solar/Wind Harmer
0.079
315814AE2-033 C
Solar/Wind Harmer
7.71
971445AH1-216 GEN
Solar/Wind Harmer
6.794
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.066
316311AC2-079 GEN
Solar/Wind Harmer
2.751
970683AG2-441 GEN
Solar/Wind Harmer
6.388
970681AG2-440 GEN
Solar/Wind Harmer
5.11
970189AG2-124 GEN
Solar/Wind Harmer
2.786
316314AB2-024 C
Solar/Wind Harmer
0
3144303KENBRDG
Solar/Wind Harmer
0.074
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
1.553
316059AD1-063 C
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.018
3138283WHITEMARSH
Solar/Wind Harmer
0.021
315835AF2-110_GEN
Solar/Wind Harmer
0.619
3152611GOSPORTB
Adder
1.135
3152621GOSPORTC
Adder
0.963
3152601GOSPORTA
Adder
0.888
3151081ELIZAR1
Adder
8.147
3151091ELIZAR2
Adder
8.006
3141913WHIT STONE
Solar/Wind Harmer
0.088
316305AF2-043 C
Solar/Wind Harmer
0.001
3138133OCRAN
Solar/Wind Harmer
0.026
957871AF2-081 GEN
Solar/Wind Harmer
4.367
319010AE1-072 C
Solar/Wind Harmer
0.441
3146406KITTY HAWK
Solar/Wind Harmer
0.011
3146486SUNBURY
Solar/Wind Harmer
0.087
3146486SUNBURY
Solar/Wind Harmer
0.087
313526AB2-022
Solar/Wind Harmer
0.047
941031AE2-094 GEN
Solar/Wind Harmer
16.035
944011AF1-069 GEN
Solar/Wind Harmer
5.239
316321Z2-027
Solar/Wind Harmer
0.016
3145176PASQUOTANK
Solar/Wind Harmer
0.054
3146396TANGLEW
Solar/Wind Harmer
0.24
3141783LANCAST
Solar/Wind Harmer
0.052
3141783LANCAST
Solar/Wind Harmer
0.035
971967AH1-528 GEN
Solar/Wind Harmer
13.837
970673AG2-436 GEN
Solar/Wind Harmer
18.368
970673AG2-436 GEN
Solar/Wind Harmer
12.246
316087AB2-174 GEN
Solar/Wind Harmer
0.002
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
0.085
965291AG1-394 GEN
Solar/Wind Harmer
0.378
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3145893MURPHYS
Solar/Wind Harmer
0.227
3145893MURPHYS
Solar/Wind Harmer
0.084
3137643SOCKMAN
Solar/Wind Harmer
0.336
962981AG1-147 GEN
Solar/Wind Harmer
3.138
3146043SEABORD
Solar/Wind Harmer
0.084
315816AE2-034 GEN
Solar/Wind Harmer
0.36
315607AA1-063A GEN
Solar/Wind Harmer
0.171
315652AC1-086 GEN
Solar/Wind Harmer
9.169
3130546PLYMOUTH
Solar/Wind Harmer
0.083
315732AD1-074 GEN1
Solar/Wind Harmer
0.476
315733AD1-074 GEN2
Solar/Wind Harmer
0.476
315735AD1-075 GEN1
Solar/Wind Harmer
0.238
3145513AHOSKIE
Solar/Wind Harmer
0.173
3145513AHOSKIE
Solar/Wind Harmer
0.083
3150861SPRUNCD
50/50
1.044
3143096IRON208
50/50
0.687
3143096IRON208
50/50
0.673
3151921BEARGRDN G2
50/50
1.285
316313AB2-026
Solar/Wind Harmer
0.185
316258AE1-075 C
Solar/Wind Harmer
0.222
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.438
3146776BUCKING
Solar/Wind Harmer
0.045
970221AG2-151 GEN
Solar/Wind Harmer
6.608
965281AG1-393 GEN
Solar/Wind Harmer
1.316
315839AE2-212 C
Solar/Wind Harmer
0.001
970133AG2-095 GEN
Solar/Wind Harmer
1.182
970293AG2-193 GEN
Solar/Wind Harmer
1.304
3142946ENON
Solar/Wind Harmer
0.04
970129AG2-093 GEN
Solar/Wind Harmer
7.091
315778AD1-151 GEN
Solar/Wind Harmer
9.051
3146926FARMVIL
Solar/Wind Harmer
0.068
315813AE1-149 C
Solar/Wind Harmer
5.92
316473AC1-191 GEN
Solar/Wind Harmer
0.369
3142416OLDCHRC
Solar/Wind Harmer
1.056
3142433PROV 92
Adder
0.211
3142433PROV 92
Adder
0.211
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970659AG2-427 GEN
Solar/Wind Harmer
1.122
316083AB2-161 GEN
Solar/Wind Harmer
0.001
961611AG1-000B GEN
Solar/Wind Harmer
2.784
970909AG2-566 GEN
Solar/Wind Harmer
1.096
970661AG2-428 GEN
Solar/Wind Harmer
2.168
3147133PAMPLIN
Solar/Wind Harmer
0.316
971193AH1-056 GEN
Solar/Wind Harmer
6.137
3151221GRAVEL6
Adder
7.305
3151171GRAVELC
Adder
1.406
963181AG1-167 GEN
Solar/Wind Harmer
0.395
3144293JTRSVLE
Adder
0.314
3145336SMITFLD
Solar/Wind Harmer
0.038
3141843SHACKLE
Adder
0.481
316203AE2-005 GEN
Solar/Wind Harmer
0
959311AF2-222 GEN
Solar/Wind Harmer
8.32
316382AG1-145 C
Solar/Wind Harmer
0.001
970257AG2-171 GEN
Solar/Wind Harmer
2.966
316280AD1-041 GEN
Solar/Wind Harmer
0.002
3141766HARMONY
Solar/Wind Harmer
1.23
315785AD2-033 C
Solar/Wind Harmer
0.744
3144216WINCHST
Adder
0.345
3144536CHRHLND
Solar/Wind Harmer
0.014
316156AD2-030 GEN
Solar/Wind Harmer
0.067
3141873WAN 176
Solar/Wind Harmer
1.611
3150921YORKTN3
Adder
2.265
3144873MCLAUGH
Solar/Wind Harmer
0.002
3151101ELIZAR3
Adder
8.251
3145273HOLLAND
Solar/Wind Harmer
0.066
316365GEN2_N
Solar/Wind Harmer
0.199
964241AG1-285 GEN
Solar/Wind Harmer
5.88
3146456SLIGO L269
Solar/Wind Harmer
0.088
971153AH1-033 GEN
Solar/Wind Harmer
1.013
944581AF1-123 GEN
Solar/Wind Harmer
19.675
944601AF1-125 GEN
Solar/Wind Harmer
19.372
316320Y1-086
Solar/Wind Harmer
0
316435W1029_GEN3
Solar/Wind Harmer
0.001
3147043LAWRENC
Solar/Wind Harmer
0.052
3146516WINFALL
Solar/Wind Harmer
0.087
3146626S HERTFORD
Solar/Wind Harmer
0.086
316131AB2-060 GEN
Solar/Wind Harmer
0.271
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
313506AB2-031 GEN
Solar/Wind Harmer
0.264
3146376EDENTON
Solar/Wind Harmer
0.085
315773AC2-141 GEN
Solar/Wind Harmer
3.093
3145893MURPHYS
Solar/Wind Harmer
0.141
3145893MURPHYS
Solar/Wind Harmer
0.084
962971AG1-146 GEN
Solar/Wind Harmer
1.345
315614AA2-178 GEN
Solar/Wind Harmer
0.481
957521AF2-046 GEN
Solar/Wind Harmer
6.241
961681AG1-008 GEN
Solar/Wind Harmer
6.241
316478AD1-087 GEN
Solar/Wind Harmer
0.292
316486AD2-202 GEN
Solar/Wind Harmer
0.086
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3146173TUNIS
Solar/Wind Harmer
0.083
971157AH1-035 GEN
Solar/Wind Harmer
0.997
315737AD1-076 GEN
Solar/Wind Harmer
1.067
316463AE2-346 GEN
Solar/Wind Harmer
0.071
316140AB2-099
Solar/Wind Harmer
0.03
962331AG1-082 GEN
Solar/Wind Harmer
0.882
3146206CASHIE
Solar/Wind Harmer
0.083
970009AG2-005 GEN
Solar/Wind Harmer
0.617
3146263WOODLND
Solar/Wind Harmer
0.082
970917AG2-570 GEN
Solar/Wind Harmer
7.314
3156021HOLLOMANSOL
Solar/Wind Harmer
0.373
3145796HORNRTN
Solar/Wind Harmer
0.327
3145796HORNRTN
Solar/Wind Harmer
0.082
971781AH1-399 GEN
Solar/Wind Harmer
0.107
316317KELFORD C
Solar/Wind Harmer
0.008
3145823KELFORD
Solar/Wind Harmer
0.081
316404AE1-155 C
Solar/Wind Harmer
0.018
3145963POPLR C
Solar/Wind Harmer
0.08
316210AC1-098 GEN
Solar/Wind Harmer
0.732
315724AD1-057 GEN
Solar/Wind Harmer
0.29
3145933PARMELE
Solar/Wind Harmer
0.077
966801AG1-551 GEN
Solar/Wind Harmer
0.897
316327AA2-057 GEN
Solar/Wind Harmer
0.115
3150351NORNECKC2
Adder
0.769
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
3146233WITAKRS
Solar/Wind Harmer
0.375
3146233WITAKRS
Solar/Wind Harmer
0.051
3138543CONSLDL
Solar/Wind Harmer
0.049
3143096IRON208
50/50
0.687
3151931BEARGRDN S1
50/50
1.658
3151911BEARGRDN G1
50/50
1.285
3143226MDLTHAN
Solar/Wind Harmer
0.397
3143526WINTERP
Solar/Wind Harmer
1.653
3143336POWHATN
Solar/Wind Harmer
5.221
316336AC2-165 C
Solar/Wind Harmer
0.01
970937AG2-583 GEN
Solar/Wind Harmer
12.089
3142543TWELFTH
Solar/Wind Harmer
0.016
972003AH1-546 GEN
Solar/Wind Harmer
5.766
944631AF1-128 GEN
Adder
61.208
315671AE2-027_GEN
Solar/Wind Harmer
7.993
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.05
971377AH1-170 GEN
Solar/Wind Harmer
1.322
3147623JAMES R
Solar/Wind Harmer
0.287
970129AG2-093 GEN
Solar/Wind Harmer
3.337
316458AB2-190 GEN2
Solar/Wind Harmer
0.626
971069AG2-661 GEN
Solar/Wind Harmer
2.011
3146926FARMVIL
Solar/Wind Harmer
0.068
3142416OLDCHRC
Solar/Wind Harmer
0.283
3142416OLDCHRC
Solar/Wind Harmer
0.109
3142433PROV 92
Solar/Wind Harmer
0.434
3142433PROV 92
Adder
0.211
3142433PROV 92
Adder
0.211
971647AH1-324 GEN
Solar/Wind Harmer
4.589
970659AG2-427 GEN
Solar/Wind Harmer
5.129
316381AD1-082 GEN
Solar/Wind Harmer
0.11
961611AG1-000B GEN
Solar/Wind Harmer
5.476
970661AG2-428 GEN
Solar/Wind Harmer
10.195
3151171GRAVELC
Adder
1.069
963171AG1-166 GEN
Solar/Wind Harmer
0.527
971563AH1-280 GEN
Solar/Wind Harmer
1.053
3144293JTRSVLE
Adder
0.314
3145336SMITFLD
Solar/Wind Harmer
0.384
970685AG2-442 GEN
Solar/Wind Harmer
7.154
971777AH1-397 GEN
Solar/Wind Harmer
0.248
3141843SHACKLE
Adder
0.481
316159AE1-175 C
Solar/Wind Harmer
0.081
3141766HARMONY
Solar/Wind Harmer
0.018
3138126ROCKLANDING
Solar/Wind Harmer
0.042
316072AD1-144
Solar/Wind Harmer
0.033
316093AE2-104_GEN
Solar/Wind Harmer
1.516
971317AH1-138 GEN
Solar/Wind Harmer
0.671
962491AG1-098 GEN
Solar/Wind Harmer
5.114
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
1.112
315693AD1-088 GEN
Solar/Wind Harmer
4.267
316023GEN1_S
Solar/Wind Harmer
0.199
316246AF1-032 C
Solar/Wind Harmer
0.04
940641AE2-051 GEN
Solar/Wind Harmer
7.055
939411AE1-173 GEN
Solar/Wind Harmer
37.578
3138133OCRAN
Solar/Wind Harmer
0.053
316388AE2-253 GEN
Solar/Wind Harmer
0.275
3146456SLIGO L269
Solar/Wind Harmer
0.088
944591AF1-124 GEN
Solar/Wind Harmer
19.745
960081AF2-299 GEN
Solar/Wind Harmer
0.838
971795AH1-408 GEN
Solar/Wind Harmer
5.798
3147043LAWRENC
Adder
0.785
3146516WINFALL
Solar/Wind Harmer
0.281
3146516WINFALL
Solar/Wind Harmer
0.087
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
957481AF2-042 GEN
Solar/Wind Harmer
22.879
3130156CHOWAN
Solar/Wind Harmer
0.085
316237AB2-079_GEN
Solar/Wind Harmer
0.001
316294AC1-161 GEN
Solar/Wind Harmer
1.467
3145893MURPHYS
Solar/Wind Harmer
0.336
3145893MURPHYS
Solar/Wind Harmer
0.374
3145663CRESWEL
Solar/Wind Harmer
0.235
971163AH1-040 GEN
Solar/Wind Harmer
6.72
316011AB1-132 GEN
Solar/Wind Harmer
1.515
962571AG1-106 GEN
Solar/Wind Harmer
1.186
3146173TUNIS
Solar/Wind Harmer
0.083
316190AA2-174 GEN
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.083
971547AH1-271 GEN
Solar/Wind Harmer
1.762
3146263WOODLND
Solar/Wind Harmer
0.082
3145783HORNRTN
Solar/Wind Harmer
0.082
970919AG2-571 GEN
Solar/Wind Harmer
2.926
3145683EARLEYS
Solar/Wind Harmer
0.082
970087AG2-069 GEN
Solar/Wind Harmer
6.559
316129AC1-054 GEN
Solar/Wind Harmer
0.308
3145796HORNRTN
Solar/Wind Harmer
0.27
3145796HORNRTN
Solar/Wind Harmer
0.082
971065AG2-659 GEN
Solar/Wind Harmer
3.493
3145823KELFORD
Solar/Wind Harmer
0.081
962861AG1-135 GEN
Solar/Wind Harmer
2.586
3145963POPLR C
Solar/Wind Harmer
0.08
316174AB2-169 GEN
Solar/Wind Harmer
0.002
316212AC1-099_GEN
Solar/Wind Harmer
0.408
315687AD1-152 GEN
Solar/Wind Harmer
0.003
3141726DUNNSVL
Solar/Wind Harmer
0.313
970401AG2-262 GEN
Solar/Wind Harmer
0.457
315722AD1-056 GEN
Solar/Wind Harmer
0.488
3146293MARTNCO
Solar/Wind Harmer
0.071
3150351NORNECKC2
Adder
0.757
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
316494AC1-189 GEN
Solar/Wind Harmer
0.253
3146233WITAKRS
Solar/Wind Harmer
0.298
961671AG1-007 GEN
Solar/Wind Harmer
0.011
3146083TARBORO
Solar/Wind Harmer
0.074
3145493TOT1
Solar/Wind Harmer
0.33
3145543BTLEBRO
Solar/Wind Harmer
0.073
3145543BTLEBRO
Solar/Wind Harmer
0.059
316359AB2-059 GEN
Solar/Wind Harmer
0.263
316049AB1-081 GEN
Solar/Wind Harmer
0.42
3142053HEARTS
Solar/Wind Harmer
0.129
316003AC1-222 GEN
Solar/Wind Harmer
0.002
316337AD2-073 GEN
Solar/Wind Harmer
0.06
316045AC1-158 PL2
Solar/Wind Helper
2.716
3147666LOUISA
Solar/Wind Helper
0.467
316192AB2-158 GEN
Solar/Wind Helper
0.764
3142366NRTHEST
50/50
0.483
3150691DARBY 3
50/50
10.163
3150701DARBY 4
50/50
10.139
3150681DARBY 2
50/50
10.127
3150671DARBY 1
50/50
10.115
944641AF1-129 GEN
50/50
66.432
971223AH1-071 GEN
Solar/Wind Harmer
4.235
3143526WINTERP
Solar/Wind Harmer
1.653
316240AF1-291 C
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.497
3146776BUCKING
Solar/Wind Harmer
0.04
971489AH1-241 GEN
Solar/Wind Harmer
6.608
3142946ENON
Solar/Wind Harmer
0.012
3142296MT RD221
Adder
0.38
316033AB2-134 GEN
Solar/Wind Harmer
0.006
315697AD1-025 GEN
Solar/Wind Harmer
0.124
316075AC2-137 C
Solar/Wind Harmer
0.03
966871AG1-558 GEN
Solar/Wind Harmer
0.126
970657AG2-426 GEN
Solar/Wind Harmer
3.648
970657AG2-426 GEN
Solar/Wind Harmer
0.765
970301AG2-198 GEN
Solar/Wind Harmer
4.386
3147133PAMPLIN
Solar/Wind Harmer
0.101
3147133PAMPLIN
Solar/Wind Harmer
0.081
971741AH1-377 GEN
Solar/Wind Harmer
9.881
958211AF2-115 GEN
Solar/Wind Harmer
1.185
963191AG1-168 GEN
Solar/Wind Harmer
0.395
3144293JTRSVLE
Adder
0.314
3144293JTRSVLE
Adder
0.265
3144356SAPONY
Solar/Wind Harmer
0.819
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316034AC1-036 C
Solar/Wind Harmer
0.007
970323AG2-213 GEN
Solar/Wind Harmer
3.955
971775AH1-396 GEN
Solar/Wind Harmer
0.148
315821AE2-092 GEN
Solar/Wind Harmer
0.006
316036AC1-147 C
Solar/Wind Harmer
0.017
3150991CHESPKB
Adder
0.933
3150991CHESPKB
Adder
0.911
316316AC1-027 C
Solar/Wind Harmer
0.085
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.003
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3145506HICKORY
Solar/Wind Harmer
0.351
3145506HICKORY
Solar/Wind Harmer
0.211
3145506HICKORY
Solar/Wind Harmer
0.053
3146073TAR RVR
Solar/Wind Harmer
0.074
3146083TARBORO
Solar/Wind Harmer
0.074
3145543BTLEBRO
Solar/Wind Harmer
0.073
3145543BTLEBRO
Solar/Wind Harmer
0.073
961601AG1-000A GEN
Solar/Wind Harmer
5.213
971623AH1-311 GEN
Solar/Wind Harmer
0.147
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.088
971683AH1-343 GEN
Solar/Wind Harmer
2.46
316283AC2-100 C
Solar/Wind Harmer
0.122
3141906WESTMOR
Solar/Wind Harmer
0.024
958131AF2-107 GEN
Solar/Wind Harmer
1.633
316044AC1-158 PL1
Solar/Wind Helper
0.848
316450AC1-158 RIC
Solar/Wind Helper
0.226
3147666LOUISA
Solar/Wind Helper
0.269
3146206CASHIE
Solar/Wind Harmer
0.083
970601AG2-382 GEN
Solar/Wind Harmer
3.084
970327AG2-215 GEN
Solar/Wind Harmer
2.71
3145683EARLEYS
Solar/Wind Harmer
0.164
3145683EARLEYS
Solar/Wind Harmer
0.082
3145683EARLEYS
Solar/Wind Harmer
0.082
970831AG2-522 GEN
Solar/Wind Harmer
3.502
970085AG2-068 GEN
Solar/Wind Harmer
4.372
970581AG2-369 GEN
Solar/Wind Harmer
3.76
3145796HORNRTN
Solar/Wind Harmer
0.262
3145796HORNRTN
Solar/Wind Harmer
0.033
3146033SCOT NK
Solar/Wind Harmer
0.319
972189AH1-679 GEN
Adder
1.329
3141813NORNECK
Solar/Wind Harmer
0.076
316005AA1-067
Solar/Wind Harmer
0.081
3145746EVERETS
Solar/Wind Harmer
0.301
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
970181AG2-120 GEN
Solar/Wind Harmer
0.942
316118AC1-105 GEN
Solar/Wind Harmer
0.194
957861AF2-080 GEN
Solar/Wind Harmer
3.228
316319Z2-044 C
Solar/Wind Harmer
0
316420AA1-050 GEN
Solar/Wind Harmer
0.002
3145573BETHELC
Solar/Wind Harmer
0.074
3145573BETHELC
Solar/Wind Harmer
0.074
3147173SINAI
Solar/Wind Harmer
0.072
3147243WELCO
Solar/Wind Harmer
0.045
970865AG2-541 GEN
Solar/Wind Harmer
2.225
316223AC1-118
Solar/Wind Harmer
0.043
316123AC1-075 GEN
Solar/Wind Harmer
0.08
970165AG2-112 GEN
Solar/Wind Harmer
0.477
970163AG2-111 GEN
Solar/Wind Harmer
0.455
316339AD2-160 GEN
Solar/Wind Harmer
0.142
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.049
3137176SLIGO L2192
Solar/Wind Harmer
0.349
3146456SLIGO L269
Solar/Wind Harmer
1.551
3130086AYDLETT
Solar/Wind Harmer
0.35
3146386ELIZ CT
Solar/Wind Harmer
0.087
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.087
3146516WINFALL
Solar/Wind Harmer
0.087
3146516WINFALL
Solar/Wind Harmer
0.087
970933AG2-581 GEN
Solar/Wind Harmer
6.917
3146626S HERTFORD
Solar/Wind Harmer
0.086
3146626S HERTFORD
Solar/Wind Harmer
0.086
970099AG2-077 GEN
Solar/Wind Harmer
9.151
313527AB2-043 GEN
Solar/Wind Harmer
0.001
972185AH1-677 GEN
Adder
4.805
316181AB2-040 GEN
Solar/Wind Harmer
0.124
3146376EDENTON
Solar/Wind Harmer
0.379
3146376EDENTON
Solar/Wind Harmer
0.379
972187AH1-678 GEN
Adder
2.42
3145893MURPHYS
Solar/Wind Harmer
0.563
3145893MURPHYS
Solar/Wind Harmer
0.151
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.083
3142666NORTHAMPTON
Solar/Wind Harmer
0.05
3146173TUNIS
Solar/Wind Harmer
0.083
3146173TUNIS
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.083
966811AG1-552 GEN
Solar/Wind Harmer
0.901
3145593CAROLNA
Solar/Wind Harmer
0.103
316426AA2-053 GEN
Solar/Wind Harmer
0.28
316065AD1-022 GEN
Solar/Wind Harmer
3.808
3145783HORNRTN
Solar/Wind Harmer
1.465
3145783HORNRTN
Solar/Wind Harmer
1.172
3145783HORNRTN
Solar/Wind Harmer
0.366
3145783HORNRTN
Solar/Wind Harmer
0.146
939181AE1-148 GEN
Solar/Wind Harmer
3.944
3145796HORNRTN
Solar/Wind Harmer
0.246
316468AD1-105 GEN
Solar/Wind Harmer
-0.026
958261AF2-120 GEN
Solar/Wind Harmer
2.652
962561AG1-105 GEN
Solar/Wind Harmer
3.799
316274AC1-208 GEN
Solar/Wind Harmer
0.409
964791AG1-342 GEN
Solar/Wind Harmer
1.497
3146843MT LREL
Solar/Wind Harmer
0.078
3146843MT LREL
Solar/Wind Harmer
0.078
3145933PARMELE
Solar/Wind Harmer
0.154
3145933PARMELE
Solar/Wind Harmer
0.077
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.795
3150341NORNECKC1
Adder
0.788
3145493TOT1
Solar/Wind Harmer
0.172
3145453TOT5
Solar/Wind Harmer
0.103
3145603CNETO
Solar/Wind Harmer
0.069
961601AG1-000A GEN
Solar/Wind Harmer
1.303
316263AC1-034 GEN
Solar/Wind Harmer
2.786
316222AC1-221 GEN
Solar/Wind Harmer
0.261
316447AC1-158 HLD
Solar/Wind Helper
1.867
LAGNLTFEXP_LAGN->PJM
CLTF
3.494
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.348
TVALTFEXP_TVA->PJM
CLTF
1.763
NYPJM->LTFIMP_NY
CLTF
1.086
LGEELTFEXP_LGEE->PJM
CLTF
0.65
WECLTFEXP_WEC->PJM
CLTF
0.327
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.354
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.067
MECLTFEXP_MEC->PJM
CLTF
1.74
SIGELTFEXP_SIGE->PJM
CLTF
0.053
CPLELTFEXP_CPLE->PJM
CLTF
4.706
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.653

Details for 6NORNECK-6SANDERS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6NORNECK-6SANDERS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.31 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:659.04
MW Contribution:7.21
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
4.965
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150611CHESTG7
50/50
0.404
3150631CHESTG8
50/50
0.398
971047AG2-646 GEN
50/50
11.319
972263AH1-716 GEN
50/50
33.189
3141813NORNECK
Solar/Wind Harmer
0.28
970327AG2-215 GEN
Solar/Wind Harmer
7.212
962981AG1-147 GEN
Solar/Wind Harmer
7.706
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
0.029
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.097
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3150351NORNECKC2
50/50
3.012
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
9.171
315976AC1-164 GENA
Solar/Wind Harmer
8.348
316169AC1-164_GENC
Solar/Wind Harmer
7.212
315975AC1-164 GENB
Solar/Wind Harmer
0.247
316312AB1-027
Solar/Wind Harmer
0.103
972265AH1-717 GEN
Adder
4.42
3151201GRAVEL4
Adder
4.144
3151191GRAVEL3
Adder
4.091
3151211GRAVEL5
Adder
4.091
316369SG1_INVT
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Helper
2.149
3141426STAFORD
Solar/Wind Helper
0.031
3150351NORNECKC2
50/50
2.962
966661AG1-536 GEN
50/50
6.865
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
971353AH1-157 GEN
50/50
7.457
970017AG2-010 GEN
50/50
4.736
3150641CHESTS8
50/50
0.205
944631AF1-128 GEN
50/50
32.202
3141726DUNNSVL
Solar/Wind Harmer
1.046
962861AG1-135 GEN
Solar/Wind Harmer
7.54
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.365
3142433PROV 92
Solar/Wind Harmer
0.43
971317AH1-138 GEN
Solar/Wind Harmer
0.617
316159AE1-175 C
Solar/Wind Harmer
0.065
3138126ROCKLANDING
Solar/Wind Harmer
0.033
3142416OLDCHRC
Solar/Wind Harmer
0.15
3142416OLDCHRC
Solar/Wind Harmer
0.058
3151171GRAVELC
Adder
0.606
961611AG1-000B GEN
Solar/Wind Harmer
2.976
971647AH1-324 GEN
Solar/Wind Harmer
2.415
971069AG2-661 GEN
Solar/Wind Harmer
1.002
316337AD2-073 GEN
Solar/Wind Helper
2.345
970575AG2-366 GEN
50/50
3.67
315749AE2-041 GEN
50/50
4.965
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150921YORKTN3
50/50
1.944
3144216WINCHST
50/50
0.281
3151161SURRY 1
50/50
2.187
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.641
962971AG1-146 GEN
Solar/Wind Harmer
3.303
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.62
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.862
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.674
3142416OLDCHRC
Solar/Wind Harmer
0.56
3151221GRAVEL6
Adder
4.139
3151171GRAVELC
Adder
0.796
961611AG1-000B GEN
Solar/Wind Harmer
1.513
315778AD1-151 GEN
Solar/Wind Harmer
4.508
3141906WESTMOR
Solar/Wind Helper
0.564
3150341NORNECKC1
50/50
3.111
3150341NORNECKC1
50/50
3.086
963611AG1-210 GEN
50/50
0.996
3150621CHESTS7
50/50
0.186
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
7.981
316075AC2-137 C
Solar/Wind Harmer
0.02
3142946ENON
Solar/Wind Harmer
0.007
316033AB2-134 GEN
Solar/Wind Harmer
0.003
315697AD1-025 GEN
Solar/Wind Harmer
0.063
LAGNLTFEXP_LAGN->PJM
CLTF
1.568
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.516
TVALTFEXP_TVA->PJM
CLTF
0.792
NYPJM->LTFIMP_NY
CLTF
0.537
LGEELTFEXP_LGEE->PJM
CLTF
0.304
WECLTFEXP_WEC->PJM
CLTF
0.153
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.326
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.737
MECLTFEXP_MEC->PJM
CLTF
0.803
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
2.043
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.462

Details for 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6NRTHEST-6ELMONT 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.04 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:719.66
MW Contribution:3.29
Bus #Bus NameTypeMW Contribution
971285AH1-108 GEN
50/50
1.812
3142433PROV 92
50/50
0.256
3142433PROV 92
50/50
0.256
970603AG2-384 GEN
50/50
2.487
315759AF1-018 GEN
50/50
4.011
315976AC1-164 GENA
Solar/Wind Harmer
13.74
316169AC1-164_GENC
Solar/Wind Harmer
11.87
315975AC1-164 GENB
Solar/Wind Harmer
0.407
971167AH1-042 GEN
Solar/Wind Harmer
11.132
3143873LANEXA
Solar/Wind Harmer
0.071
316314AB2-024 C
Solar/Wind Harmer
0
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
3.339
315662AE1-191 GEN
Solar/Wind Harmer
0.004
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.022
3141913WHIT STONE
Solar/Wind Harmer
0.106
3138133OCRAN
Solar/Wind Harmer
0.032
3141783LANCAST
Solar/Wind Harmer
0.063
3141783LANCAST
Solar/Wind Harmer
0.042
3138283WHITEMARSH
Solar/Wind Harmer
0.024
316132AB2-190 GEN1
Solar/Wind Harmer
0.558
962981AG1-147 GEN
Solar/Wind Harmer
3.806
316369SG1_INVT
Solar/Wind Harmer
0.004
970327AG2-215 GEN
Solar/Wind Harmer
3.295
3143316POE
Solar/Wind Harmer
0.383
972265AH1-717 GEN
Adder
7.425
3151201GRAVEL4
Adder
6.96
3151191GRAVEL3
Adder
6.872
3151211GRAVEL5
Adder
6.872
3141813NORNECK
Solar/Wind Harmer
0.093
971445AH1-216 GEN
Solar/Wind Harmer
6.5
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.061
316311AC2-079 GEN
Solar/Wind Harmer
2.536
3152611GOSPORTB
Adder
1.096
3152621GOSPORTC
Adder
0.93
3152601GOSPORTA
Adder
0.858
3151081ELIZAR1
Adder
7.878
3151091ELIZAR2
Adder
7.741
315835AF2-110_GEN
Solar/Wind Harmer
0.581
316305AF2-043 C
Solar/Wind Harmer
0.001
957871AF2-081 GEN
Solar/Wind Harmer
4.193
319010AE1-072 C
Solar/Wind Harmer
0.423
3146406KITTY HAWK
Solar/Wind Harmer
0.01
313526AB2-022
Solar/Wind Harmer
0.045
3146486SUNBURY
Solar/Wind Harmer
0.083
3146486SUNBURY
Solar/Wind Harmer
0.083
316321Z2-027
Solar/Wind Harmer
0.015
3146396TANGLEW
Solar/Wind Harmer
0.227
3145176PASQUOTANK
Solar/Wind Harmer
0.051
316315AB2-025 C
Solar/Wind Harmer
0.065
315814AE2-033 C
Solar/Wind Harmer
6.307
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.078
3130156CHOWAN
Solar/Wind Harmer
0.078
315816AE2-034 GEN
Solar/Wind Harmer
0.324
316223AC1-118
Solar/Wind Harmer
0.054
3130546PLYMOUTH
Solar/Wind Harmer
0.074
315732AD1-074 GEN1
Solar/Wind Harmer
0.421
315733AD1-074 GEN2
Solar/Wind Harmer
0.421
315735AD1-075 GEN1
Solar/Wind Harmer
0.211
965291AG1-394 GEN
Solar/Wind Harmer
0.321
3146206CASHIE
Solar/Wind Harmer
0.072
970601AG2-382 GEN
Solar/Wind Harmer
2.689
3145893MURPHYS
Solar/Wind Harmer
0.192
3145893MURPHYS
Solar/Wind Harmer
0.071
3145513AHOSKIE
Solar/Wind Harmer
0.146
3145513AHOSKIE
Solar/Wind Harmer
0.07
3145683EARLEYS
Solar/Wind Harmer
0.138
3145683EARLEYS
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.069
3146043SEABORD
Solar/Wind Harmer
0.068
315607AA1-063A GEN
Solar/Wind Harmer
0.139
315652AC1-086 GEN
Solar/Wind Harmer
7.356
316087AB2-174 GEN
Solar/Wind Harmer
0.002
941031AE2-094 GEN
Solar/Wind Harmer
12.088
944011AF1-069 GEN
Solar/Wind Harmer
3.95
3137643SOCKMAN
Solar/Wind Harmer
0.262
3145796HORNRTN
Solar/Wind Harmer
0.209
3145796HORNRTN
Solar/Wind Harmer
0.026
3146033SCOT NK
Solar/Wind Harmer
0.259
970673AG2-436 GEN
Solar/Wind Harmer
13.729
970673AG2-436 GEN
Solar/Wind Harmer
9.153
971967AH1-528 GEN
Solar/Wind Harmer
10.107
316005AA1-067
Solar/Wind Harmer
0.066
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.061
3145746EVERETS
Solar/Wind Harmer
0.061
3145746EVERETS
Solar/Wind Harmer
0.061
970181AG2-120 GEN
Solar/Wind Harmer
0.765
970085AG2-068 GEN
Solar/Wind Harmer
3.212
970581AG2-369 GEN
Solar/Wind Harmer
2.763
957861AF2-080 GEN
Solar/Wind Harmer
2.574
316420AA1-050 GEN
Solar/Wind Harmer
0.002
3145573BETHELC
Solar/Wind Harmer
0.058
3145573BETHELC
Solar/Wind Harmer
0.058
316319Z2-044 C
Solar/Wind Harmer
0
970831AG2-522 GEN
Solar/Wind Harmer
2.461
3142366NRTHEST
50/50
1.511
3150691DARBY 3
50/50
28.96
3150701DARBY 4
50/50
28.893
3150681DARBY 2
50/50
28.859
3150671DARBY 1
50/50
28.825
944641AF1-129 GEN
50/50
58.962
3150781HOPHCF2
50/50
0.435
3150791HOPHCF3
50/50
0.435
316075AC2-137 C
Solar/Wind Harmer
0.047
316240AF1-291 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.011
316033AB2-134 GEN
Solar/Wind Harmer
0.006
315697AD1-025 GEN
Solar/Wind Harmer
0.113
958261AF2-120 GEN
Solar/Wind Harmer
3.238
970657AG2-426 GEN
Solar/Wind Harmer
3.279
970657AG2-426 GEN
Solar/Wind Harmer
0.687
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.979
3150341NORNECKC1
Adder
0.971
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.016
3150991CHESPKB
Adder
0.902
3150991CHESPKB
Adder
0.88
316316AC1-027 C
Solar/Wind Harmer
0.082
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3145506HICKORY
Solar/Wind Harmer
0.339
3145506HICKORY
Solar/Wind Harmer
0.203
3145506HICKORY
Solar/Wind Harmer
0.051
316339AD2-160 GEN
Solar/Wind Harmer
0.137
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.047
3137176SLIGO L2192
Solar/Wind Harmer
0.334
3146456SLIGO L269
Solar/Wind Harmer
1.486
3130086AYDLETT
Solar/Wind Harmer
0.335
3146386ELIZ CT
Solar/Wind Harmer
0.083
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.081
3146516WINFALL
Solar/Wind Harmer
0.081
3146516WINFALL
Solar/Wind Harmer
0.081
3146626S HERTFORD
Solar/Wind Harmer
0.081
3146626S HERTFORD
Solar/Wind Harmer
0.081
3144356SAPONY
Solar/Wind Harmer
0.671
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.347
3146376EDENTON
Solar/Wind Harmer
0.347
316065AD1-022 GEN
Solar/Wind Harmer
3.336
3145893MURPHYS
Solar/Wind Harmer
0.477
3145893MURPHYS
Solar/Wind Harmer
0.128
3146173TUNIS
Solar/Wind Harmer
0.07
3146173TUNIS
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.067
3142666NORTHAMPTON
Solar/Wind Harmer
0.067
3142666NORTHAMPTON
Solar/Wind Harmer
0.067
3142666NORTHAMPTON
Solar/Wind Harmer
0.04
316181AB2-040 GEN
Solar/Wind Harmer
0.096
316426AA2-053 GEN
Solar/Wind Harmer
0.222
3145796HORNRTN
Solar/Wind Harmer
0.196
3145593CAROLNA
Solar/Wind Harmer
0.065
3145593CAROLNA
Solar/Wind Harmer
0.065
966811AG1-552 GEN
Solar/Wind Harmer
0.705
3145593CAROLNA
Solar/Wind Harmer
0.081
3145783HORNRTN
Solar/Wind Harmer
1.147
3145783HORNRTN
Solar/Wind Harmer
0.917
3145783HORNRTN
Solar/Wind Harmer
0.287
3145783HORNRTN
Solar/Wind Harmer
0.115
972185AH1-677 GEN
Adder
3.575
3145933PARMELE
Solar/Wind Harmer
0.127
3145933PARMELE
Solar/Wind Harmer
0.064
972187AH1-678 GEN
Adder
1.79
316274AC1-208 GEN
Solar/Wind Harmer
0.322
970933AG2-581 GEN
Solar/Wind Harmer
4.888
971223AH1-071 GEN
Solar/Wind Harmer
0.633
3145493TOT1
Solar/Wind Harmer
0.135
3145453TOT5
Solar/Wind Harmer
0.081
3145603CNETO
Solar/Wind Harmer
0.054
961601AG1-000A GEN
Solar/Wind Harmer
1.002
316263AC1-034 GEN
Solar/Wind Harmer
2.138
3150851SPRUNCC
50/50
1.107
3142433PROV 92
50/50
0.256
3142433PROV 92
50/50
0.256
3141843SHACKLE
50/50
0.611
3150771HOPHCF1
50/50
0.435
3142543TWELFTH
Solar/Wind Harmer
0.019
3142433PROV 92
Solar/Wind Harmer
0.495
315671AE2-027_GEN
Solar/Wind Harmer
7.528
3141766HARMONY
Solar/Wind Harmer
0.023
971777AH1-397 GEN
Solar/Wind Harmer
0.298
316159AE1-175 C
Solar/Wind Harmer
0.096
3138133OCRAN
Solar/Wind Harmer
0.064
944631AF1-128 GEN
Adder
50.091
970129AG2-093 GEN
Solar/Wind Harmer
2.967
316458AB2-190 GEN2
Solar/Wind Harmer
0.558
971317AH1-138 GEN
Solar/Wind Harmer
0.769
971069AG2-661 GEN
Solar/Wind Harmer
1.816
3138126ROCKLANDING
Solar/Wind Harmer
0.046
971647AH1-324 GEN
Solar/Wind Harmer
4.236
962861AG1-135 GEN
Solar/Wind Harmer
3.155
961611AG1-000B GEN
Solar/Wind Harmer
5.121
3141726DUNNSVL
Solar/Wind Harmer
0.387
3151171GRAVELC
Adder
1.017
970659AG2-427 GEN
Solar/Wind Harmer
4.587
316381AD1-082 GEN
Solar/Wind Harmer
0.098
3150351NORNECKC2
Adder
0.932
970661AG2-428 GEN
Solar/Wind Harmer
9.208
3145336SMITFLD
Solar/Wind Harmer
0.368
316072AD1-144
Solar/Wind Harmer
0.032
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
1.075
316294AC1-161 GEN
Solar/Wind Harmer
1.478
944591AF1-124 GEN
Solar/Wind Harmer
19.166
316337AD2-073 GEN
Solar/Wind Harmer
0.074
316093AE2-104_GEN
Solar/Wind Harmer
1.425
316246AF1-032 C
Solar/Wind Harmer
0.038
316388AE2-253 GEN
Solar/Wind Harmer
0.264
3146456SLIGO L269
Solar/Wind Harmer
0.084
3146516WINFALL
Solar/Wind Harmer
0.264
3146516WINFALL
Solar/Wind Harmer
0.081
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.078
3145663CRESWEL
Solar/Wind Harmer
0.211
971163AH1-040 GEN
Solar/Wind Harmer
6.044
939411AE1-173 GEN
Solar/Wind Harmer
31.884
3146206CASHIE
Solar/Wind Harmer
0.072
971547AH1-271 GEN
Solar/Wind Harmer
1.537
940641AE2-051 GEN
Solar/Wind Harmer
5.708
3145893MURPHYS
Solar/Wind Harmer
0.285
3145893MURPHYS
Solar/Wind Harmer
0.317
316023GEN1_S
Solar/Wind Harmer
0.16
3146173TUNIS
Solar/Wind Harmer
0.07
3143096IRON208
Adder
0.293
3145683EARLEYS
Solar/Wind Harmer
0.069
3146263WOODLND
Solar/Wind Harmer
0.068
3145963POPLR C
Solar/Wind Harmer
0.068
960081AF2-299 GEN
Solar/Wind Harmer
0.645
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145823KELFORD
Solar/Wind Harmer
0.067
316011AB1-132 GEN
Solar/Wind Harmer
1.216
962571AG1-106 GEN
Solar/Wind Harmer
0.951
316190AA2-174 GEN
Solar/Wind Harmer
0
3145796HORNRTN
Solar/Wind Harmer
0.216
3145796HORNRTN
Solar/Wind Harmer
0.065
3145783HORNRTN
Solar/Wind Harmer
0.064
971795AH1-408 GEN
Solar/Wind Harmer
4.241
3146293MARTNCO
Solar/Wind Harmer
0.059
316212AC1-099_GEN
Solar/Wind Harmer
0.325
3147043LAWRENC
Adder
0.561
3145746EVERETS
Solar/Wind Harmer
0.061
3145746EVERETS
Solar/Wind Harmer
0.061
970919AG2-571 GEN
Solar/Wind Harmer
2.151
315722AD1-056 GEN
Solar/Wind Harmer
0.382
970087AG2-069 GEN
Solar/Wind Harmer
4.819
972135AH1-637 GEN
Solar/Wind Harmer
0.511
316494AC1-189 GEN
Solar/Wind Harmer
0.202
3143226MDLTHAN
Solar/Wind Harmer
0.059
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.058
3145493TOT1
Solar/Wind Harmer
0.259
3146233WITAKRS
Solar/Wind Harmer
0.23
316129AC1-054 GEN
Solar/Wind Harmer
0.214
316359AB2-059 GEN
Solar/Wind Harmer
0.202
316049AB1-081 GEN
Solar/Wind Harmer
0.322
3145543BTLEBRO
Solar/Wind Harmer
0.056
3145543BTLEBRO
Solar/Wind Harmer
0.045
3142053HEARTS
Solar/Wind Harmer
0.099
3150861SPRUNCD
50/50
1.107
3142433PROV 92
50/50
0.256
3142433PROV 92
50/50
0.256
315749AE2-041 GEN
50/50
4.011
3141843SHACKLE
50/50
0.611
3150801HOPHCF4
50/50
0.633
970293AG2-193 GEN
Solar/Wind Harmer
2.979
965281AG1-393 GEN
Solar/Wind Harmer
1.223
3142946ENON
Solar/Wind Harmer
0.038
3141766HARMONY
Solar/Wind Harmer
1.504
316203AE2-005 GEN
Solar/Wind Harmer
0
316280AD1-041 GEN
Solar/Wind Harmer
0.002
316382AG1-145 C
Solar/Wind Harmer
0.001
316156AD2-030 GEN
Solar/Wind Harmer
0.081
3141873WAN 176
Solar/Wind Harmer
1.933
315839AE2-212 C
Solar/Wind Harmer
0.001
970133AG2-095 GEN
Solar/Wind Harmer
1.03
970129AG2-093 GEN
Solar/Wind Harmer
6.305
315778AD1-151 GEN
Solar/Wind Harmer
8.173
962971AG1-146 GEN
Solar/Wind Harmer
1.631
970009AG2-005 GEN
Solar/Wind Harmer
0.75
3150921YORKTN3
Adder
2.505
3144216WINCHST
Adder
0.374
315813AE1-149 C
Solar/Wind Harmer
5.226
316404AE1-155 C
Solar/Wind Harmer
0.022
961611AG1-000B GEN
Solar/Wind Harmer
2.604
3151221GRAVEL6
Adder
6.952
3151171GRAVELC
Adder
1.338
970659AG2-427 GEN
Solar/Wind Harmer
1.003
316083AB2-161 GEN
Solar/Wind Harmer
0.001
3150351NORNECKC2
Adder
0.947
970661AG2-428 GEN
Solar/Wind Harmer
1.959
3145336SMITFLD
Solar/Wind Harmer
0.037
3144536CHRHLND
Solar/Wind Harmer
0.013
3144873MCLAUGH
Solar/Wind Harmer
0.002
3151101ELIZAR3
Adder
7.979
315773AC2-141 GEN
Solar/Wind Harmer
3.115
944581AF1-123 GEN
Solar/Wind Harmer
19.098
944601AF1-125 GEN
Solar/Wind Harmer
18.804
3146456SLIGO L269
Solar/Wind Harmer
0.084
971153AH1-033 GEN
Solar/Wind Harmer
0.971
316320Y1-086
Solar/Wind Harmer
0
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.081
3145273HOLLAND
Solar/Wind Harmer
0.061
3146626S HERTFORD
Solar/Wind Harmer
0.081
3146376EDENTON
Solar/Wind Harmer
0.078
315614AA2-178 GEN
Solar/Wind Harmer
0.432
3141906WESTMOR
Solar/Wind Harmer
0.03
971157AH1-035 GEN
Solar/Wind Harmer
0.883
315737AD1-076 GEN
Solar/Wind Harmer
0.942
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146206CASHIE
Solar/Wind Harmer
0.072
3145893MURPHYS
Solar/Wind Harmer
0.119
3145893MURPHYS
Solar/Wind Harmer
0.071
316365GEN2_N
Solar/Wind Harmer
0.16
957521AF2-046 GEN
Solar/Wind Harmer
5.28
961681AG1-008 GEN
Solar/Wind Harmer
5.28
3156021HOLLOMANSOL
Solar/Wind Harmer
0.319
3146173TUNIS
Solar/Wind Harmer
0.07
3143096IRON208
Adder
0.293
3143096IRON208
Adder
0.287
316463AE2-346 GEN
Solar/Wind Harmer
0.06
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.744
3146263WOODLND
Solar/Wind Harmer
0.068
3145963POPLR C
Solar/Wind Harmer
0.068
3142666NORTHAMPTON
Solar/Wind Harmer
0.067
316317KELFORD C
Solar/Wind Harmer
0.006
3145823KELFORD
Solar/Wind Harmer
0.067
313506AB2-031 GEN
Solar/Wind Harmer
0.204
970737AG2-469 GEN
Solar/Wind Harmer
2.813
3145796HORNRTN
Solar/Wind Harmer
0.261
3145796HORNRTN
Solar/Wind Harmer
0.065
3145933PARMELE
Solar/Wind Harmer
0.064
966801AG1-551 GEN
Solar/Wind Harmer
0.74
316210AC1-098 GEN
Solar/Wind Harmer
0.583
3147043LAWRENC
Solar/Wind Harmer
0.037
3145746EVERETS
Solar/Wind Harmer
0.061
3145746EVERETS
Solar/Wind Harmer
0.061
970917AG2-570 GEN
Solar/Wind Harmer
5.377
315724AD1-057 GEN
Solar/Wind Harmer
0.227
316327AA2-057 GEN
Solar/Wind Harmer
0.09
3146073TAR RVR
Solar/Wind Harmer
0.058
3146083TARBORO
Solar/Wind Harmer
0.058
3146233WITAKRS
Solar/Wind Harmer
0.29
3146233WITAKRS
Solar/Wind Harmer
0.039
3138543CONSLDL
Solar/Wind Harmer
0.038
961601AG1-000A GEN
Solar/Wind Harmer
4.009
3145543BTLEBRO
Solar/Wind Harmer
0.056
3145543BTLEBRO
Solar/Wind Harmer
0.056
971623AH1-311 GEN
Solar/Wind Harmer
0.113
966881AG1-559 GEN
Solar/Wind Helper
0.162
LAGNLTFEXP_LAGN->PJM
CLTF
1.779
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.508
TVALTFEXP_TVA->PJM
CLTF
0.883
NYPJM->LTFIMP_NY
CLTF
0.509
LGEELTFEXP_LGEE->PJM
CLTF
0.227
WECLTFEXP_WEC->PJM
CLTF
0.114
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.784
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.942
MECLTFEXP_MEC->PJM
CLTF
0.697
SIGELTFEXP_SIGE->PJM
CLTF
0.02
CPLELTFEXP_CPLE->PJM
CLTF
3.173
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.691

Details for 6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.12 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:635.05
MW Contribution:7.21
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
3.01
970575AG2-366 GEN
50/50
3.666
315749AE2-041 GEN
50/50
4.959
3141843SHACKLE
50/50
0.748
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150921YORKTN3
50/50
1.939
3144216WINCHST
50/50
0.281
3151161SURRY 1
50/50
2.18
970737AG2-469 GEN
Solar/Wind Harmer
20.194
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.64
962971AG1-146 GEN
Solar/Wind Harmer
3.3
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.617
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.86
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.672
3142416OLDCHRC
Solar/Wind Harmer
0.558
3151221GRAVEL6
Adder
4.126
3151171GRAVELC
Adder
0.794
961611AG1-000B GEN
Solar/Wind Harmer
1.508
3150351NORNECKC2
50/50
2.96
966661AG1-536 GEN
50/50
6.86
3141843SHACKLE
50/50
0.748
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
971353AH1-157 GEN
50/50
7.442
970017AG2-010 GEN
50/50
4.725
3150641CHESTS8
50/50
0.204
944631AF1-128 GEN
50/50
32.114
972135AH1-637 GEN
Solar/Wind Harmer
4.393
316337AD2-073 GEN
Solar/Wind Harmer
0.299
3141726DUNNSVL
Solar/Wind Harmer
1.045
962861AG1-135 GEN
Solar/Wind Harmer
7.535
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.364
3142433PROV 92
Solar/Wind Harmer
0.43
971317AH1-138 GEN
Solar/Wind Harmer
0.616
316159AE1-175 C
Solar/Wind Harmer
0.065
3138126ROCKLANDING
Solar/Wind Harmer
0.033
3142416OLDCHRC
Solar/Wind Harmer
0.15
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.604
961611AG1-000B GEN
Solar/Wind Harmer
2.967
971647AH1-324 GEN
Solar/Wind Harmer
2.407
3150341NORNECKC1
50/50
3.109
3150341NORNECKC1
50/50
3.084
963611AG1-210 GEN
50/50
0.995
3150621CHESTS7
50/50
0.185
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
7.975
316075AC2-137 C
Solar/Wind Harmer
0.02
3142946ENON
Solar/Wind Harmer
0.007
316033AB2-134 GEN
Solar/Wind Harmer
0.003
315697AD1-025 GEN
Solar/Wind Harmer
0.063
315759AF1-018 GEN
50/50
4.959
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150611CHESTG7
50/50
0.403
3150631CHESTG8
50/50
0.397
971047AG2-646 GEN
50/50
11.288
972263AH1-716 GEN
50/50
33.088
316223AC1-118
Solar/Wind Harmer
0.296
3141813NORNECK
Solar/Wind Harmer
0.28
970327AG2-215 GEN
Solar/Wind Harmer
7.206
962981AG1-147 GEN
Solar/Wind Harmer
7.699
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
0.029
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.092
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
9.155
315976AC1-164 GENA
Solar/Wind Harmer
8.33
316169AC1-164_GENC
Solar/Wind Harmer
7.197
315975AC1-164 GENB
Solar/Wind Harmer
0.246
316312AB1-027
Solar/Wind Harmer
0.103
972265AH1-717 GEN
Adder
4.406
3151201GRAVEL4
Adder
4.131
3151191GRAVEL3
Adder
4.078
3151211GRAVEL5
Adder
4.078
316369SG1_INVT
Solar/Wind Harmer
0.002
3141426STAFORD
Solar/Wind Helper
0.031
LAGNLTFEXP_LAGN->PJM
CLTF
1.541
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.475
TVALTFEXP_TVA->PJM
CLTF
0.778
NYPJM->LTFIMP_NY
CLTF
0.546
LGEELTFEXP_LGEE->PJM
CLTF
0.294
WECLTFEXP_WEC->PJM
CLTF
0.148
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.13
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.686
MECLTFEXP_MEC->PJM
CLTF
0.78
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CPLELTFEXP_CPLE->PJM
CLTF
2.028
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.282

Details for 6SANDERS-6WESTMOR 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.11 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:646.44
MW Contribution:7.21
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
3.011
970575AG2-366 GEN
50/50
3.668
315749AE2-041 GEN
50/50
4.962
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150921YORKTN3
50/50
1.942
3144216WINCHST
50/50
0.281
3151161SURRY 1
50/50
2.184
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.64
962971AG1-146 GEN
Solar/Wind Harmer
3.301
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.619
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.861
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.673
3142416OLDCHRC
Solar/Wind Harmer
0.559
3151221GRAVEL6
Adder
4.133
3151171GRAVELC
Adder
0.795
961611AG1-000B GEN
Solar/Wind Harmer
1.511
315778AD1-151 GEN
Solar/Wind Harmer
4.501
3141906WESTMOR
Solar/Wind Helper
0.564
3150351NORNECKC2
50/50
2.961
966661AG1-536 GEN
50/50
6.863
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
971353AH1-157 GEN
50/50
7.45
970017AG2-010 GEN
50/50
4.731
3150641CHESTS8
50/50
0.205
944631AF1-128 GEN
50/50
32.161
316337AD2-073 GEN
Solar/Wind Harmer
0.299
3141726DUNNSVL
Solar/Wind Harmer
1.046
962861AG1-135 GEN
Solar/Wind Harmer
7.538
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.364
3142433PROV 92
Solar/Wind Harmer
0.43
971317AH1-138 GEN
Solar/Wind Harmer
0.617
316159AE1-175 C
Solar/Wind Harmer
0.065
3138126ROCKLANDING
Solar/Wind Harmer
0.033
3142416OLDCHRC
Solar/Wind Harmer
0.15
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.605
961611AG1-000B GEN
Solar/Wind Harmer
2.971
971647AH1-324 GEN
Solar/Wind Harmer
2.411
971069AG2-661 GEN
Solar/Wind Harmer
1
3150341NORNECKC1
50/50
3.11
3150341NORNECKC1
50/50
3.085
963611AG1-210 GEN
50/50
0.995
3150621CHESTS7
50/50
0.185
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
7.978
316075AC2-137 C
Solar/Wind Harmer
0.02
3142946ENON
Solar/Wind Harmer
0.007
316033AB2-134 GEN
Solar/Wind Harmer
0.003
315697AD1-025 GEN
Solar/Wind Harmer
0.063
315759AF1-018 GEN
50/50
4.962
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150611CHESTG7
50/50
0.404
3150631CHESTG8
50/50
0.397
971047AG2-646 GEN
50/50
11.304
972263AH1-716 GEN
50/50
33.141
3141813NORNECK
Solar/Wind Harmer
0.28
970327AG2-215 GEN
Solar/Wind Harmer
7.209
962981AG1-147 GEN
Solar/Wind Harmer
7.703
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
0.029
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.094
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
9.163
315976AC1-164 GENA
Solar/Wind Harmer
8.34
316169AC1-164_GENC
Solar/Wind Harmer
7.205
315975AC1-164 GENB
Solar/Wind Harmer
0.247
316312AB1-027
Solar/Wind Harmer
0.103
972265AH1-717 GEN
Adder
4.414
3151201GRAVEL4
Adder
4.138
3151191GRAVEL3
Adder
4.085
3151211GRAVEL5
Adder
4.085
316369SG1_INVT
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Helper
2.149
3141426STAFORD
Solar/Wind Helper
0.031
LAGNLTFEXP_LAGN->PJM
CLTF
1.555
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.497
TVALTFEXP_TVA->PJM
CLTF
0.786
NYPJM->LTFIMP_NY
CLTF
0.541
LGEELTFEXP_LGEE->PJM
CLTF
0.299
WECLTFEXP_WEC->PJM
CLTF
0.151
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.234
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.714
MECLTFEXP_MEC->PJM
CLTF
0.792
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CPLELTFEXP_CPLE->PJM
CLTF
2.036
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.378

Details for 6SPARTAN-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9296_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6SPARTAN-6STAFORD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 9296_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.01 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1033.52
MW Contribution:4.38
Bus #Bus NameTypeMW Contribution
3150411LDYSMT5
50/50
24.498
3150381LDYSMT2
50/50
23.445
972213AH1-691 GEN
50/50
3.966
972215AH1-692 GEN
50/50
3.966
963051AG1-154 GEN
50/50
3.051
944491AF1-114 GEN
Solar/Wind Harmer
0.001
316223AC1-118
Solar/Wind Harmer
0.155
3141813NORNECK
Solar/Wind Harmer
0.159
970327AG2-215 GEN
Solar/Wind Harmer
4.385
962981AG1-147 GEN
Solar/Wind Harmer
4.775
3141783LANCAST
Solar/Wind Harmer
0.071
3141783LANCAST
Solar/Wind Harmer
0.047
3138133OCRAN
Solar/Wind Harmer
0.034
3141913WHIT STONE
Solar/Wind Harmer
0.111
3141873WAN 176
Solar/Wind Harmer
0.021
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
957191AF2-013 GEN
50/50
31.493
3150391LDYSMT3
50/50
24.376
972195AH1-682 GEN
50/50
3.203
3150341NORNECKC1
50/50
1.771
3150341NORNECKC1
50/50
1.756
963611AG1-210 GEN
50/50
0.567
316468AD1-105 GEN
Solar/Wind Harmer
-0.059
316077AC2-138 C
Solar/Wind Harmer
0.001
315673AE1-157 GEN
Solar/Wind Harmer
10.324
958261AF2-120 GEN
Solar/Wind Harmer
4.723
957411AF2-035 GEN
Solar/Wind Harmer
5.818
970317AG2-208 GEN
Solar/Wind Harmer
5.39
966871AG1-558 GEN
Solar/Wind Harmer
0.11
316075AC2-137 C
Solar/Wind Harmer
0.02
3142946ENON
Solar/Wind Harmer
0.007
3142296MT RD221
Adder
0.227
3150691DARBY 3
Adder
5.107
3150701DARBY 4
Adder
5.095
3150681DARBY 2
Adder
5.089
3150671DARBY 1
Adder
5.083
3142366NRTHEST
Adder
0.229
944641AF1-129 GEN
Adder
30.454
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.072
316240AF1-291 C
Solar/Wind Harmer
0.001
316236AE1-162_GEN
Solar/Wind Harmer
0
3143526WINTERP
Solar/Wind Harmer
0.307
970657AG2-426 GEN
Solar/Wind Harmer
2.053
970657AG2-426 GEN
Solar/Wind Harmer
0.43
316036AC1-147 C
Solar/Wind Harmer
0.011
3150991CHESPKB
Adder
0.599
3150991CHESPKB
Adder
0.585
316316AC1-027 C
Solar/Wind Harmer
0.055
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3145506HICKORY
Solar/Wind Harmer
0.226
3145506HICKORY
Solar/Wind Harmer
0.136
3145506HICKORY
Solar/Wind Harmer
0.034
316339AD2-160 GEN
Solar/Wind Harmer
0.091
316018AA1-139 ULT2
Solar/Wind Harmer
0.001
316017AA1-139 ULT1
Solar/Wind Harmer
0.031
3150331BIRCHWDA
50/50
74.484
3141316ARNOLDS
50/50
0.959
3150401LDYSMT4
50/50
24.421
3150371LDYSMT1
50/50
23.598
3150501FRIVERG
50/50
1.371
3150351NORNECKC2
50/50
1.714
970737AG2-469 GEN
Solar/Wind Harmer
10.3
3141906WESTMOR
Solar/Wind Harmer
0.086
971781AH1-399 GEN
Solar/Wind Harmer
0.24
316404AE1-155 C
Solar/Wind Harmer
0.032
970009AG2-005 GEN
Solar/Wind Harmer
0.998
962971AG1-146 GEN
Solar/Wind Harmer
2.046
316156AD2-030 GEN
Solar/Wind Harmer
0.076
3141873WAN 176
Solar/Wind Harmer
1.826
316280AD1-041 GEN
Solar/Wind Harmer
0.002
3141766HARMONY
Solar/Wind Harmer
1.33
316203AE2-005 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
0.507
316473AC1-191 GEN
Solar/Wind Harmer
0.322
3142433PROV 92
Adder
0.171
3142433PROV 92
Adder
0.171
3142416OLDCHRC
Solar/Wind Harmer
0.709
970293AG2-193 GEN
Solar/Wind Harmer
0.775
3142946ENON
Solar/Wind Harmer
0.024
316382AG1-145 C
Solar/Wind Harmer
0.001
3143096IRON208
Adder
0.289
3143096IRON208
Adder
0.283
3150921YORKTN3
Adder
1.719
3144216WINCHST
Adder
0.254
970133AG2-095 GEN
Solar/Wind Harmer
0.63
970129AG2-093 GEN
Solar/Wind Harmer
3.914
315778AD1-151 GEN
Solar/Wind Harmer
5.128
3150861SPRUNCD
Adder
0.294
965281AG1-393 GEN
Solar/Wind Harmer
0.677
961611AG1-000B GEN
Solar/Wind Harmer
1.673
3151221GRAVEL6
Adder
4.517
3151171GRAVELC
Adder
0.869
315839AE2-212 C
Solar/Wind Harmer
0
3145336SMITFLD
Solar/Wind Harmer
0.024
315813AE1-149 C
Solar/Wind Harmer
3.187
970659AG2-427 GEN
Solar/Wind Harmer
0.623
316083AB2-161 GEN
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.234
3144536CHRHLND
Solar/Wind Harmer
0.009
3144873MCLAUGH
Solar/Wind Harmer
0.001
3151101ELIZAR3
Adder
5.306
315773AC2-141 GEN
Solar/Wind Harmer
2.068
944581AF1-123 GEN
Solar/Wind Harmer
12.738
944601AF1-125 GEN
Solar/Wind Harmer
12.541
3141346CRANES
50/50
0.721
972197AH1-683 GEN
50/50
3.813
972219AH1-694 GEN
50/50
2.746
3150351NORNECKC2
50/50
1.686
966661AG1-536 GEN
50/50
4.063
972135AH1-637 GEN
Solar/Wind Harmer
2.21
316337AD2-073 GEN
Solar/Wind Harmer
0.162
3141726DUNNSVL
Solar/Wind Harmer
0.606
962861AG1-135 GEN
Solar/Wind Harmer
4.492
966881AG1-559 GEN
Solar/Wind Harmer
0.158
3138133OCRAN
Solar/Wind Harmer
0.068
3141766HARMONY
Solar/Wind Harmer
0.02
971777AH1-397 GEN
Solar/Wind Harmer
0.262
3141843SHACKLE
Adder
0.507
3142433PROV 92
Solar/Wind Harmer
0.352
3142433PROV 92
Adder
0.171
3142433PROV 92
Adder
0.171
3142416OLDCHRC
Solar/Wind Harmer
0.19
3142416OLDCHRC
Solar/Wind Harmer
0.073
971317AH1-138 GEN
Solar/Wind Harmer
0.545
316159AE1-175 C
Solar/Wind Harmer
0.061
944631AF1-128 GEN
Adder
33.488
3143096IRON208
Adder
0.289
3138126ROCKLANDING
Solar/Wind Harmer
0.031
3142543TWELFTH
Solar/Wind Harmer
0.006
970129AG2-093 GEN
Solar/Wind Harmer
1.842
316458AB2-190 GEN2
Solar/Wind Harmer
0.347
315671AE2-027_GEN
Solar/Wind Harmer
4.113
971069AG2-661 GEN
Solar/Wind Harmer
1.14
3150851SPRUNCC
Adder
0.294
971647AH1-324 GEN
Solar/Wind Harmer
2.698
961611AG1-000B GEN
Solar/Wind Harmer
3.29
3151171GRAVELC
Adder
0.661
3145336SMITFLD
Solar/Wind Harmer
0.241
3143526WINTERP
Solar/Wind Harmer
0.307
970659AG2-427 GEN
Solar/Wind Harmer
2.85
316381AD1-082 GEN
Solar/Wind Harmer
0.061
316072AD1-144
Solar/Wind Harmer
0.021
970661AG2-428 GEN
Solar/Wind Harmer
5.802
316375AC2-012 GEN
Solar/Wind Harmer
0.001
3150981CHESPKA
Adder
0.715
316294AC1-161 GEN
Solar/Wind Harmer
0.981
944591AF1-124 GEN
Solar/Wind Harmer
12.783
316246AF1-032 C
Solar/Wind Harmer
0.025
316388AE2-253 GEN
Solar/Wind Harmer
0.176
316093AE2-104_GEN
Solar/Wind Harmer
0.946
970189AG2-124 GEN
Solar/Wind Harmer
2.943
316314AB2-024 C
Solar/Wind Harmer
0
972189AH1-679 GEN
Adder
1.608
3143873LANEXA
Solar/Wind Harmer
0.057
3142433PROV 92
Adder
0.171
3142433PROV 92
Adder
0.171
971167AH1-042 GEN
Solar/Wind Harmer
7.69
3138283WHITEMARSH
Solar/Wind Harmer
0.02
315976AC1-164 GENA
Solar/Wind Harmer
7.877
316169AC1-164_GENC
Solar/Wind Harmer
6.805
315975AC1-164 GENB
Solar/Wind Harmer
0.233
316312AB1-027
Solar/Wind Harmer
0.131
316132AB2-190 GEN1
Solar/Wind Harmer
0.347
971285AH1-108 GEN
Adder
0.482
316369SG1_INVT
Solar/Wind Harmer
0.002
972265AH1-717 GEN
Adder
4.824
3151201GRAVEL4
Adder
4.522
3151191GRAVEL3
Adder
4.465
3151211GRAVEL5
Adder
4.465
971445AH1-216 GEN
Solar/Wind Harmer
4.254
316233AE1-074 FULL
Solar/Wind Harmer
0.047
971281AH1-106 GEN
Solar/Wind Harmer
0.819
971283AH1-107 GEN
Solar/Wind Harmer
0.819
3143316POE
Solar/Wind Harmer
0.231
3152611GOSPORTB
Adder
0.729
3152621GOSPORTC
Adder
0.618
3152601GOSPORTA
Adder
0.571
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.039
316311AC2-079 GEN
Solar/Wind Harmer
1.643
3151081ELIZAR1
Adder
5.239
3151091ELIZAR2
Adder
5.148
316305AF2-043 C
Solar/Wind Harmer
0
957871AF2-081 GEN
Solar/Wind Harmer
2.801
315835AF2-110_GEN
Solar/Wind Harmer
0.386
3141426STAFORD
Solar/Wind Helper
0.174
LAGNLTFEXP_LAGN->PJM
CLTF
2.016
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.794
TVALTFEXP_TVA->PJM
CLTF
1.019
NYPJM->LTFIMP_NY
CLTF
0.793
LGEELTFEXP_LGEE->PJM
CLTF
0.39
WECLTFEXP_WEC->PJM
CLTF
0.196
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.786
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.522
MECLTFEXP_MEC->PJM
CLTF
1.029
SIGELTFEXP_SIGE->PJM
CLTF
0.032
CPLELTFEXP_CPLE->PJM
CLTF
2.609
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.871

Details for 6SPARTAN-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2119_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6SPARTAN-6STAFORD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2119_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.99 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1033.32
MW Contribution:4.38
Bus #Bus NameTypeMW Contribution
3150331BIRCHWDA
50/50
74.484
3141316ARNOLDS
50/50
0.959
3150401LDYSMT4
50/50
24.421
3150371LDYSMT1
50/50
23.598
3150501FRIVERG
50/50
1.371
3150351NORNECKC2
50/50
1.714
970737AG2-469 GEN
Solar/Wind Harmer
10.3
3141906WESTMOR
Solar/Wind Harmer
0.086
971781AH1-399 GEN
Solar/Wind Harmer
0.24
316404AE1-155 C
Solar/Wind Harmer
0.032
970009AG2-005 GEN
Solar/Wind Harmer
0.998
962971AG1-146 GEN
Solar/Wind Harmer
2.046
316156AD2-030 GEN
Solar/Wind Harmer
0.076
3141873WAN 176
Solar/Wind Harmer
1.826
316280AD1-041 GEN
Solar/Wind Harmer
0.002
3141766HARMONY
Solar/Wind Harmer
1.33
316203AE2-005 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
0.507
316473AC1-191 GEN
Solar/Wind Harmer
0.322
3142433PROV 92
Adder
0.171
3142433PROV 92
Adder
0.171
3142416OLDCHRC
Solar/Wind Harmer
0.709
970293AG2-193 GEN
Solar/Wind Harmer
0.775
3142946ENON
Solar/Wind Harmer
0.024
316382AG1-145 C
Solar/Wind Harmer
0.001
3143096IRON208
Adder
0.289
3143096IRON208
Adder
0.283
3150921YORKTN3
Adder
1.719
3144216WINCHST
Adder
0.254
970133AG2-095 GEN
Solar/Wind Harmer
0.63
970129AG2-093 GEN
Solar/Wind Harmer
3.914
315778AD1-151 GEN
Solar/Wind Harmer
5.128
3150861SPRUNCD
Adder
0.294
965281AG1-393 GEN
Solar/Wind Harmer
0.677
961611AG1-000B GEN
Solar/Wind Harmer
1.673
3151221GRAVEL6
Adder
4.517
3151171GRAVELC
Adder
0.869
315839AE2-212 C
Solar/Wind Harmer
0
3145336SMITFLD
Solar/Wind Harmer
0.024
315813AE1-149 C
Solar/Wind Harmer
3.187
970659AG2-427 GEN
Solar/Wind Harmer
0.623
316083AB2-161 GEN
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.234
3144536CHRHLND
Solar/Wind Harmer
0.009
3144873MCLAUGH
Solar/Wind Harmer
0.001
3151101ELIZAR3
Adder
5.306
315773AC2-141 GEN
Solar/Wind Harmer
2.068
944581AF1-123 GEN
Solar/Wind Harmer
12.738
944601AF1-125 GEN
Solar/Wind Harmer
12.541
3150411LDYSMT5
50/50
24.498
3150381LDYSMT2
50/50
23.445
972213AH1-691 GEN
50/50
3.966
972215AH1-692 GEN
50/50
3.966
963051AG1-154 GEN
50/50
3.051
944491AF1-114 GEN
Solar/Wind Harmer
0.001
316223AC1-118
Solar/Wind Harmer
0.155
3141813NORNECK
Solar/Wind Harmer
0.159
970327AG2-215 GEN
Solar/Wind Harmer
4.385
962981AG1-147 GEN
Solar/Wind Harmer
4.775
3141783LANCAST
Solar/Wind Harmer
0.071
3141783LANCAST
Solar/Wind Harmer
0.047
3138133OCRAN
Solar/Wind Harmer
0.034
3141913WHIT STONE
Solar/Wind Harmer
0.111
3141873WAN 176
Solar/Wind Harmer
0.021
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
2.943
316314AB2-024 C
Solar/Wind Harmer
0
972189AH1-679 GEN
Adder
1.608
3143873LANEXA
Solar/Wind Harmer
0.057
3142433PROV 92
Adder
0.171
3142433PROV 92
Adder
0.171
971167AH1-042 GEN
Solar/Wind Harmer
7.69
3138283WHITEMARSH
Solar/Wind Harmer
0.02
315976AC1-164 GENA
Solar/Wind Harmer
7.877
316169AC1-164_GENC
Solar/Wind Harmer
6.805
315975AC1-164 GENB
Solar/Wind Harmer
0.233
316312AB1-027
Solar/Wind Harmer
0.131
316132AB2-190 GEN1
Solar/Wind Harmer
0.347
971285AH1-108 GEN
Adder
0.482
316369SG1_INVT
Solar/Wind Harmer
0.002
972265AH1-717 GEN
Adder
4.824
3151201GRAVEL4
Adder
4.522
3151191GRAVEL3
Adder
4.465
3151211GRAVEL5
Adder
4.465
971445AH1-216 GEN
Solar/Wind Harmer
4.254
316233AE1-074 FULL
Solar/Wind Harmer
0.047
971281AH1-106 GEN
Solar/Wind Harmer
0.819
971283AH1-107 GEN
Solar/Wind Harmer
0.819
3143316POE
Solar/Wind Harmer
0.231
3152611GOSPORTB
Adder
0.729
3152621GOSPORTC
Adder
0.618
3152601GOSPORTA
Adder
0.571
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.039
316311AC2-079 GEN
Solar/Wind Harmer
1.643
3151081ELIZAR1
Adder
5.239
3151091ELIZAR2
Adder
5.148
316305AF2-043 C
Solar/Wind Harmer
0
957871AF2-081 GEN
Solar/Wind Harmer
2.801
315835AF2-110_GEN
Solar/Wind Harmer
0.386
3141426STAFORD
Solar/Wind Helper
0.174
3141346CRANES
50/50
0.721
972197AH1-683 GEN
50/50
3.813
972219AH1-694 GEN
50/50
2.746
3150351NORNECKC2
50/50
1.686
966661AG1-536 GEN
50/50
4.063
972135AH1-637 GEN
Solar/Wind Harmer
2.21
316337AD2-073 GEN
Solar/Wind Harmer
0.162
3141726DUNNSVL
Solar/Wind Harmer
0.606
962861AG1-135 GEN
Solar/Wind Harmer
4.492
966881AG1-559 GEN
Solar/Wind Harmer
0.158
3138133OCRAN
Solar/Wind Harmer
0.068
3141766HARMONY
Solar/Wind Harmer
0.02
971777AH1-397 GEN
Solar/Wind Harmer
0.262
3141843SHACKLE
Adder
0.507
3142433PROV 92
Solar/Wind Harmer
0.352
3142433PROV 92
Adder
0.171
3142433PROV 92
Adder
0.171
3142416OLDCHRC
Solar/Wind Harmer
0.19
3142416OLDCHRC
Solar/Wind Harmer
0.073
971317AH1-138 GEN
Solar/Wind Harmer
0.545
316159AE1-175 C
Solar/Wind Harmer
0.061
944631AF1-128 GEN
Adder
33.488
3143096IRON208
Adder
0.289
3138126ROCKLANDING
Solar/Wind Harmer
0.031
3142543TWELFTH
Solar/Wind Harmer
0.006
970129AG2-093 GEN
Solar/Wind Harmer
1.842
316458AB2-190 GEN2
Solar/Wind Harmer
0.347
315671AE2-027_GEN
Solar/Wind Harmer
4.113
971069AG2-661 GEN
Solar/Wind Harmer
1.14
3150851SPRUNCC
Adder
0.294
971647AH1-324 GEN
Solar/Wind Harmer
2.698
961611AG1-000B GEN
Solar/Wind Harmer
3.29
3151171GRAVELC
Adder
0.661
3145336SMITFLD
Solar/Wind Harmer
0.241
3143526WINTERP
Solar/Wind Harmer
0.307
970659AG2-427 GEN
Solar/Wind Harmer
2.85
316381AD1-082 GEN
Solar/Wind Harmer
0.061
316072AD1-144
Solar/Wind Harmer
0.021
970661AG2-428 GEN
Solar/Wind Harmer
5.802
316375AC2-012 GEN
Solar/Wind Harmer
0.001
3150981CHESPKA
Adder
0.715
316294AC1-161 GEN
Solar/Wind Harmer
0.981
944591AF1-124 GEN
Solar/Wind Harmer
12.783
316246AF1-032 C
Solar/Wind Harmer
0.025
316388AE2-253 GEN
Solar/Wind Harmer
0.176
316093AE2-104_GEN
Solar/Wind Harmer
0.946
957191AF2-013 GEN
50/50
31.493
3150391LDYSMT3
50/50
24.376
972195AH1-682 GEN
50/50
3.203
3150341NORNECKC1
50/50
1.771
3150341NORNECKC1
50/50
1.756
963611AG1-210 GEN
50/50
0.567
316468AD1-105 GEN
Solar/Wind Harmer
-0.059
316077AC2-138 C
Solar/Wind Harmer
0.001
315673AE1-157 GEN
Solar/Wind Harmer
10.324
958261AF2-120 GEN
Solar/Wind Harmer
4.723
957411AF2-035 GEN
Solar/Wind Harmer
5.818
970317AG2-208 GEN
Solar/Wind Harmer
5.39
966871AG1-558 GEN
Solar/Wind Harmer
0.11
316075AC2-137 C
Solar/Wind Harmer
0.02
3142946ENON
Solar/Wind Harmer
0.007
3142296MT RD221
Adder
0.227
3150691DARBY 3
Adder
5.107
3150701DARBY 4
Adder
5.095
3150681DARBY 2
Adder
5.089
3150671DARBY 1
Adder
5.083
3142366NRTHEST
Adder
0.229
944641AF1-129 GEN
Adder
30.454
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.072
316240AF1-291 C
Solar/Wind Harmer
0.001
316236AE1-162_GEN
Solar/Wind Harmer
0
3143526WINTERP
Solar/Wind Harmer
0.307
970657AG2-426 GEN
Solar/Wind Harmer
2.053
970657AG2-426 GEN
Solar/Wind Harmer
0.43
316036AC1-147 C
Solar/Wind Harmer
0.011
3150991CHESPKB
Adder
0.599
3150991CHESPKB
Adder
0.585
316316AC1-027 C
Solar/Wind Harmer
0.055
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3145506HICKORY
Solar/Wind Harmer
0.226
3145506HICKORY
Solar/Wind Harmer
0.136
3145506HICKORY
Solar/Wind Harmer
0.034
316339AD2-160 GEN
Solar/Wind Harmer
0.091
316018AA1-139 ULT2
Solar/Wind Harmer
0.001
316017AA1-139 ULT1
Solar/Wind Harmer
0.031
LAGNLTFEXP_LAGN->PJM
CLTF
2.016
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.794
TVALTFEXP_TVA->PJM
CLTF
1.019
NYPJM->LTFIMP_NY
CLTF
0.793
LGEELTFEXP_LGEE->PJM
CLTF
0.39
WECLTFEXP_WEC->PJM
CLTF
0.196
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.786
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.522
MECLTFEXP_MEC->PJM
CLTF
1.029
SIGELTFEXP_SIGE->PJM
CLTF
0.032
CPLELTFEXP_CPLE->PJM
CLTF
2.609
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.871

Details for 6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:134.25 %
Rating:1478.62 MVA
Rating Type:B
MVA to Mitigate:1985.01
MW Contribution:2.79
Bus #Bus NameTypeMW Contribution
315051AA1-145 CT1
50/50
2.918
971645AH1-323 GEN
50/50
16.828
316473AC1-191 GEN
Solar/Wind Harmer
0.547
3142416OLDCHRC
Solar/Wind Harmer
1.565
970293AG2-193 GEN
Solar/Wind Harmer
1.528
3143096IRON208
Adder
0.565
3143096IRON208
Adder
0.554
3150861SPRUNCD
Adder
0.59
3142946ENON
Solar/Wind Harmer
0.043
970133AG2-095 GEN
Solar/Wind Harmer
1.165
970129AG2-093 GEN
Solar/Wind Harmer
7.076
965281AG1-393 GEN
Solar/Wind Harmer
1.247
315839AE2-212 C
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.224
3142433PROV 92
Adder
0.224
315052AA1-145 CT2
50/50
2.93
966881AG1-559 GEN
Solar/Wind Harmer
0.767
3142416OLDCHRC
Solar/Wind Harmer
0.42
3142416OLDCHRC
Solar/Wind Harmer
0.161
3143096IRON208
Adder
0.565
3142543TWELFTH
Solar/Wind Harmer
0.013
944631AF1-128 GEN
Adder
61.065
3150851SPRUNCC
Adder
0.59
315671AE2-027_GEN
Solar/Wind Harmer
7.592
970129AG2-093 GEN
Solar/Wind Harmer
3.33
316458AB2-190 GEN2
Solar/Wind Harmer
0.626
3142433PROV 92
Solar/Wind Harmer
0.461
3142433PROV 92
Adder
0.224
3142433PROV 92
Adder
0.224
971069AG2-661 GEN
Solar/Wind Harmer
2.027
3143526WINTERP
Solar/Wind Harmer
0.585
316159AE1-175 C
Solar/Wind Harmer
0.096
971647AH1-324 GEN
Solar/Wind Harmer
4.69
961611AG1-000B GEN
Solar/Wind Harmer
5.643
3151171GRAVELC
Adder
1.114
971317AH1-138 GEN
Solar/Wind Harmer
0.779
3141766HARMONY
Solar/Wind Harmer
0.021
971777AH1-397 GEN
Solar/Wind Harmer
0.275
3141843SHACKLE
Adder
0.532
3138126ROCKLANDING
Solar/Wind Harmer
0.047
970659AG2-427 GEN
Solar/Wind Harmer
4.989
316381AD1-082 GEN
Solar/Wind Harmer
0.107
970661AG2-428 GEN
Solar/Wind Harmer
10.027
3145336SMITFLD
Solar/Wind Harmer
0.402
3143226MDLTHAN
Solar/Wind Harmer
0.096
316072AD1-144
Solar/Wind Harmer
0.034
972189AH1-679 GEN
50/50
6.54
316312AB1-027
Solar/Wind Harmer
0.289
315778AD1-151 GEN
Solar/Wind Harmer
9.121
316382AG1-145 C
Solar/Wind Harmer
0.001
961611AG1-000B GEN
Solar/Wind Harmer
2.869
315813AE1-149 C
Solar/Wind Harmer
5.675
3151221GRAVEL6
Adder
7.614
3151171GRAVELC
Adder
1.465
3141766HARMONY
Solar/Wind Harmer
1.389
3141843SHACKLE
Adder
0.532
316203AE2-005 GEN
Solar/Wind Harmer
0
3144216WINCHST
Adder
0.39
3150921YORKTN3
Adder
2.595
970659AG2-427 GEN
Solar/Wind Harmer
1.091
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.002
971781AH1-399 GEN
Solar/Wind Harmer
0.134
970661AG2-428 GEN
Solar/Wind Harmer
2.133
3145336SMITFLD
Solar/Wind Harmer
0.04
316156AD2-030 GEN
Solar/Wind Harmer
0.074
3141873WAN 176
Solar/Wind Harmer
1.782
3144536CHRHLND
Solar/Wind Harmer
0.014
3144873MCLAUGH
Solar/Wind Harmer
0.002
3151101ELIZAR3
Adder
8.719
315773AC2-141 GEN
Solar/Wind Harmer
3.396
944581AF1-123 GEN
Solar/Wind Harmer
20.859
944601AF1-125 GEN
Solar/Wind Harmer
20.537
3146456SLIGO L269
Solar/Wind Harmer
0.092
971153AH1-033 GEN
Solar/Wind Harmer
1.063
316320Y1-086
Solar/Wind Harmer
0
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.089
3145273HOLLAND
Solar/Wind Harmer
0.067
3146626S HERTFORD
Solar/Wind Harmer
0.089
962971AG1-146 GEN
Solar/Wind Harmer
1.407
3146376EDENTON
Solar/Wind Harmer
0.086
970009AG2-005 GEN
Solar/Wind Harmer
0.636
315614AA2-178 GEN
Solar/Wind Harmer
0.482
971157AH1-035 GEN
Solar/Wind Harmer
0.988
315737AD1-076 GEN
Solar/Wind Harmer
1.055
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146206CASHIE
Solar/Wind Harmer
0.081
972255AH1-712 GEN
Adder
41.371
316404AE1-155 C
Solar/Wind Harmer
0.018
3145893MURPHYS
Solar/Wind Harmer
0.134
3145893MURPHYS
Solar/Wind Harmer
0.08
957521AF2-046 GEN
Solar/Wind Harmer
5.958
961681AG1-008 GEN
Solar/Wind Harmer
5.958
316365GEN2_N
Solar/Wind Harmer
0.179
316313AB2-026
Solar/Wind Harmer
0.05
316258AE1-075 C
Solar/Wind Harmer
0.06
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
1.205
3146173TUNIS
Solar/Wind Harmer
0.079
3156021HOLLOMANSOL
Solar/Wind Harmer
0.36
316463AE2-346 GEN
Solar/Wind Harmer
0.068
316140AB2-099
Solar/Wind Harmer
0.028
962331AG1-082 GEN
Solar/Wind Harmer
0.841
3146263WOODLND
Solar/Wind Harmer
0.077
3145963POPLR C
Solar/Wind Harmer
0.077
3142666NORTHAMPTON
Solar/Wind Harmer
0.076
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.076
313506AB2-031 GEN
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
0.299
3145796HORNRTN
Solar/Wind Harmer
0.075
3145933PARMELE
Solar/Wind Harmer
0.073
966801AG1-551 GEN
Solar/Wind Harmer
0.851
3147043LAWRENC
Solar/Wind Harmer
0.044
316210AC1-098 GEN
Solar/Wind Harmer
0.674
3150351NORNECKC2
Adder
0.735
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
315724AD1-057 GEN
Solar/Wind Harmer
0.263
316327AA2-057 GEN
Solar/Wind Harmer
0.105
970917AG2-570 GEN
Solar/Wind Harmer
6.089
3146073TAR RVR
Solar/Wind Harmer
0.068
3146083TARBORO
Solar/Wind Harmer
0.068
3146233WITAKRS
Solar/Wind Harmer
0.341
3146233WITAKRS
Solar/Wind Harmer
0.046
3138543CONSLDL
Solar/Wind Harmer
0.045
961601AG1-000A GEN
Solar/Wind Harmer
4.729
3145543BTLEBRO
Solar/Wind Harmer
0.066
3145543BTLEBRO
Solar/Wind Harmer
0.066
971623AH1-311 GEN
Solar/Wind Harmer
0.133
316478AD1-087 GEN
Solar/Wind Harmer
0.225
316486AD2-202 GEN
Solar/Wind Harmer
0.066
316131AB2-060 GEN
Solar/Wind Harmer
0.2
964241AG1-285 GEN
Solar/Wind Harmer
4.22
315785AD2-033 C
Solar/Wind Harmer
0.511
970257AG2-171 GEN
Solar/Wind Harmer
2.007
959311AF2-222 GEN
Solar/Wind Harmer
5.564
970909AG2-566 GEN
Solar/Wind Harmer
0.665
963181AG1-167 GEN
Solar/Wind Harmer
0.248
3144293JTRSVLE
Adder
0.197
3147133PAMPLIN
Solar/Wind Harmer
0.193
971193AH1-056 GEN
Solar/Wind Harmer
3.754
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.036
3146776BUCKING
Solar/Wind Harmer
0.021
316248AF1-058 C
Solar/Wind Harmer
0
960061AF2-297 GEN
Solar/Wind Harmer
2.45
3142296MT RD221
50/50
0.608
3142366NRTHEST
50/50
0.528
3150691DARBY 3
50/50
11.375
3150701DARBY 4
50/50
11.349
3150681DARBY 2
50/50
11.335
957411AF2-035 GEN
Solar/Wind Harmer
28.305
970317AG2-208 GEN
Solar/Wind Harmer
26.223
966871AG1-558 GEN
Solar/Wind Harmer
0.187
3150671DARBY 1
Adder
10.67
316075AC2-137 C
Solar/Wind Harmer
0.038
3142946ENON
Solar/Wind Harmer
0.013
944641AF1-129 GEN
Adder
59.87
316240AF1-291 C
Solar/Wind Harmer
0.001
3143526WINTERP
Solar/Wind Harmer
0.585
316033AB2-134 GEN
Solar/Wind Harmer
0.007
315697AD1-025 GEN
Solar/Wind Harmer
0.126
316468AD1-105 GEN
Solar/Wind Harmer
-0.033
970657AG2-426 GEN
Solar/Wind Harmer
3.569
970657AG2-426 GEN
Solar/Wind Harmer
0.748
316236AE1-162_GEN
Solar/Wind Harmer
0.001
971223AH1-071 GEN
Solar/Wind Harmer
1.027
316036AC1-147 C
Solar/Wind Harmer
0.017
3150991CHESPKB
Adder
0.985
3150991CHESPKB
Adder
0.962
316316AC1-027 C
Solar/Wind Harmer
0.09
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.003
3145506HICKORY
Solar/Wind Harmer
0.37
3145506HICKORY
Solar/Wind Harmer
0.222
3145506HICKORY
Solar/Wind Harmer
0.056
316339AD2-160 GEN
Solar/Wind Harmer
0.15
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.051
3137176SLIGO L2192
Solar/Wind Harmer
0.366
3146456SLIGO L269
Solar/Wind Harmer
1.627
3130086AYDLETT
Solar/Wind Harmer
0.367
3146386ELIZ CT
Solar/Wind Harmer
0.091
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.089
3146516WINFALL
Solar/Wind Harmer
0.089
3146516WINFALL
Solar/Wind Harmer
0.089
3146626S HERTFORD
Solar/Wind Harmer
0.089
3146626S HERTFORD
Solar/Wind Harmer
0.089
3144356SAPONY
Solar/Wind Harmer
0.735
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.385
3146376EDENTON
Solar/Wind Harmer
0.385
316065AD1-022 GEN
Solar/Wind Harmer
3.744
958261AF2-120 GEN
Solar/Wind Harmer
2.666
3145893MURPHYS
Solar/Wind Harmer
0.538
3145893MURPHYS
Solar/Wind Harmer
0.145
3146173TUNIS
Solar/Wind Harmer
0.079
3146173TUNIS
Solar/Wind Harmer
0.079
3142666NORTHAMPTON
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.046
316181AB2-040 GEN
Solar/Wind Harmer
0.11
316426AA2-053 GEN
Solar/Wind Harmer
0.255
3145796HORNRTN
Solar/Wind Harmer
0.224
3145593CAROLNA
Solar/Wind Harmer
0.075
3145593CAROLNA
Solar/Wind Harmer
0.075
966811AG1-552 GEN
Solar/Wind Harmer
0.811
3145593CAROLNA
Solar/Wind Harmer
0.093
3145783HORNRTN
Solar/Wind Harmer
1.321
3145783HORNRTN
Solar/Wind Harmer
1.057
3145783HORNRTN
Solar/Wind Harmer
0.33
3145783HORNRTN
Solar/Wind Harmer
0.132
3145933PARMELE
Solar/Wind Harmer
0.146
3145933PARMELE
Solar/Wind Harmer
0.073
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.759
3150341NORNECKC1
Adder
0.753
316274AC1-208 GEN
Solar/Wind Harmer
0.373
972185AH1-677 GEN
Adder
3.992
972187AH1-678 GEN
Adder
2.007
970933AG2-581 GEN
Solar/Wind Harmer
5.576
3145493TOT1
Solar/Wind Harmer
0.158
3145453TOT5
Solar/Wind Harmer
0.095
3145603CNETO
Solar/Wind Harmer
0.063
961601AG1-000A GEN
Solar/Wind Harmer
1.182
316263AC1-034 GEN
Solar/Wind Harmer
2.524
970099AG2-077 GEN
Solar/Wind Harmer
7.081
939181AE1-148 GEN
Solar/Wind Harmer
3.089
313527AB2-043 GEN
Solar/Wind Harmer
0.001
971741AH1-377 GEN
Solar/Wind Harmer
6.257
316034AC1-036 C
Solar/Wind Harmer
0.005
970323AG2-213 GEN
Solar/Wind Harmer
2.676
971775AH1-396 GEN
Solar/Wind Harmer
0.1
970301AG2-198 GEN
Solar/Wind Harmer
2.661
958211AF2-115 GEN
Solar/Wind Harmer
0.743
963191AG1-168 GEN
Solar/Wind Harmer
0.248
3144293JTRSVLE
Adder
0.197
3144293JTRSVLE
Adder
0.166
3147133PAMPLIN
Solar/Wind Harmer
0.062
3147133PAMPLIN
Solar/Wind Harmer
0.049
962561AG1-105 GEN
Solar/Wind Harmer
2.907
964791AG1-342 GEN
Solar/Wind Harmer
1.152
3146843MT LREL
Solar/Wind Harmer
0.06
3146843MT LREL
Solar/Wind Harmer
0.06
3146776BUCKING
Solar/Wind Harmer
0.231
3146776BUCKING
Solar/Wind Harmer
0.019
971285AH1-108 GEN
Adder
0.966
315976AC1-164 GENA
Solar/Wind Harmer
13.07
316169AC1-164_GENC
Solar/Wind Harmer
11.292
315975AC1-164 GENB
Solar/Wind Harmer
0.387
971167AH1-042 GEN
Solar/Wind Harmer
10.363
316132AB2-190 GEN1
Solar/Wind Harmer
0.626
3142433PROV 92
Adder
0.224
3142433PROV 92
Adder
0.224
316233AE1-074 FULL
Solar/Wind Harmer
0.09
971281AH1-106 GEN
Solar/Wind Harmer
1.562
971283AH1-107 GEN
Solar/Wind Harmer
1.562
316369SG1_INVT
Solar/Wind Harmer
0.004
3143873LANEXA
Solar/Wind Harmer
0.066
316314AB2-024 C
Solar/Wind Harmer
0
3143316POE
Solar/Wind Harmer
0.414
972265AH1-717 GEN
Adder
8.131
3151201GRAVEL4
Adder
7.623
3151191GRAVEL3
Adder
7.526
3151211GRAVEL5
Adder
7.526
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
3.086
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3138283WHITEMARSH
Solar/Wind Harmer
0.024
971445AH1-216 GEN
Solar/Wind Harmer
7.113
3141873WAN 176
Solar/Wind Harmer
0.02
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.066
316311AC2-079 GEN
Solar/Wind Harmer
2.768
3141913WHIT STONE
Solar/Wind Harmer
0.096
3138133OCRAN
Solar/Wind Harmer
0.028
3152611GOSPORTB
Adder
1.198
3152621GOSPORTC
Adder
1.017
3152601GOSPORTA
Adder
0.938
3151081ELIZAR1
Adder
8.608
3151091ELIZAR2
Adder
8.459
3141783LANCAST
Solar/Wind Harmer
0.056
3141783LANCAST
Solar/Wind Harmer
0.037
315835AF2-110_GEN
Solar/Wind Harmer
0.636
316305AF2-043 C
Solar/Wind Harmer
0.001
957871AF2-081 GEN
Solar/Wind Harmer
4.589
319010AE1-072 C
Solar/Wind Harmer
0.463
3146406KITTY HAWK
Solar/Wind Harmer
0.011
313526AB2-022
Solar/Wind Harmer
0.049
3146486SUNBURY
Solar/Wind Harmer
0.091
3146486SUNBURY
Solar/Wind Harmer
0.091
316321Z2-027
Solar/Wind Harmer
0.017
3146396TANGLEW
Solar/Wind Harmer
0.249
3145176PASQUOTANK
Solar/Wind Harmer
0.056
962981AG1-147 GEN
Solar/Wind Harmer
3.282
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
316315AB2-025 C
Solar/Wind Harmer
0.071
315814AE2-033 C
Solar/Wind Harmer
6.916
3130156CHOWAN
Solar/Wind Harmer
0.086
3130156CHOWAN
Solar/Wind Harmer
0.086
970327AG2-215 GEN
Solar/Wind Harmer
2.794
315816AE2-034 GEN
Solar/Wind Harmer
0.361
3130546PLYMOUTH
Solar/Wind Harmer
0.082
315732AD1-074 GEN1
Solar/Wind Harmer
0.471
315733AD1-074 GEN2
Solar/Wind Harmer
0.471
315735AD1-075 GEN1
Solar/Wind Harmer
0.236
965291AG1-394 GEN
Solar/Wind Harmer
0.361
3146206CASHIE
Solar/Wind Harmer
0.081
970601AG2-382 GEN
Solar/Wind Harmer
3.02
972193AH1-681 GEN
Adder
1.848
3145893MURPHYS
Solar/Wind Harmer
0.217
3145893MURPHYS
Solar/Wind Harmer
0.08
3145513AHOSKIE
Solar/Wind Harmer
0.165
3145513AHOSKIE
Solar/Wind Harmer
0.079
3145683EARLEYS
Solar/Wind Harmer
0.157
3145683EARLEYS
Solar/Wind Harmer
0.078
3145683EARLEYS
Solar/Wind Harmer
0.078
3146043SEABORD
Solar/Wind Harmer
0.078
315607AA1-063A GEN
Solar/Wind Harmer
0.158
315652AC1-086 GEN
Solar/Wind Harmer
8.376
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.3
3145796HORNRTN
Solar/Wind Harmer
0.239
3145796HORNRTN
Solar/Wind Harmer
0.03
3146033SCOT NK
Solar/Wind Harmer
0.297
941031AE2-094 GEN
Solar/Wind Harmer
13.369
944011AF1-069 GEN
Solar/Wind Harmer
4.368
3141813NORNECK
Solar/Wind Harmer
0.072
970673AG2-436 GEN
Solar/Wind Harmer
15.278
970673AG2-436 GEN
Solar/Wind Harmer
10.185
316005AA1-067
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.283
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
970181AG2-120 GEN
Solar/Wind Harmer
0.885
971967AH1-528 GEN
Solar/Wind Harmer
11.354
957861AF2-080 GEN
Solar/Wind Harmer
2.998
316420AA1-050 GEN
Solar/Wind Harmer
0.002
970831AG2-522 GEN
Solar/Wind Harmer
2.933
970085AG2-068 GEN
Solar/Wind Harmer
3.642
970581AG2-369 GEN
Solar/Wind Harmer
3.132
3145573BETHELC
Solar/Wind Harmer
0.068
3145573BETHELC
Solar/Wind Harmer
0.068
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
1.054
3144303KENBRDG
Solar/Wind Harmer
0.05
970683AG2-441 GEN
Solar/Wind Harmer
4.154
970681AG2-440 GEN
Solar/Wind Harmer
3.323
946301AF1-294 GEN
Solar/Wind Harmer
1.222
961791AG1-021 GEN
Solar/Wind Harmer
0.594
315657AE1-056 GEN
Solar/Wind Harmer
2.127
316118AC1-105 GEN
Solar/Wind Harmer
0.152
970285AG2-188 GEN
Solar/Wind Harmer
4.613
971845AH1-439 GEN
Solar/Wind Harmer
2.627
3147173SINAI
Solar/Wind Harmer
0.057
3147243WELCO
Solar/Wind Harmer
0.036
3141426STAFORD
Solar/Wind Helper
0.036
3138133OCRAN
Solar/Wind Harmer
0.057
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
1.175
316294AC1-161 GEN
Solar/Wind Harmer
1.611
316093AE2-104_GEN
Solar/Wind Harmer
1.559
944591AF1-124 GEN
Solar/Wind Harmer
20.933
316388AE2-253 GEN
Solar/Wind Harmer
0.289
316246AF1-032 C
Solar/Wind Harmer
0.042
3146456SLIGO L269
Solar/Wind Harmer
0.092
3146516WINFALL
Solar/Wind Harmer
0.29
3146516WINFALL
Solar/Wind Harmer
0.089
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.086
3145663CRESWEL
Solar/Wind Harmer
0.235
971163AH1-040 GEN
Solar/Wind Harmer
6.732
962861AG1-135 GEN
Solar/Wind Harmer
2.618
939411AE1-173 GEN
Solar/Wind Harmer
34.828
3146206CASHIE
Solar/Wind Harmer
0.081
971547AH1-271 GEN
Solar/Wind Harmer
1.726
972277AH1-723 GEN
Adder
48.21
3145893MURPHYS
Solar/Wind Harmer
0.321
3145893MURPHYS
Solar/Wind Harmer
0.357
316023GEN1_S
Solar/Wind Harmer
0.179
3143336POWHATN
Solar/Wind Harmer
1.418
3146173TUNIS
Solar/Wind Harmer
0.079
3145683EARLEYS
Solar/Wind Harmer
0.078
940641AE2-051 GEN
Solar/Wind Harmer
6.235
3146263WOODLND
Solar/Wind Harmer
0.077
3141726DUNNSVL
Solar/Wind Harmer
0.309
3145963POPLR C
Solar/Wind Harmer
0.077
960081AF2-299 GEN
Solar/Wind Harmer
0.737
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145823KELFORD
Solar/Wind Harmer
0.076
316011AB1-132 GEN
Solar/Wind Harmer
1.384
962571AG1-106 GEN
Solar/Wind Harmer
1.083
316336AC2-165 C
Solar/Wind Harmer
0.003
316190AA2-174 GEN
Solar/Wind Harmer
0
3145796HORNRTN
Solar/Wind Harmer
0.247
3145796HORNRTN
Solar/Wind Harmer
0.075
3145783HORNRTN
Solar/Wind Harmer
0.074
971795AH1-408 GEN
Solar/Wind Harmer
4.936
3146293MARTNCO
Solar/Wind Harmer
0.068
3147043LAWRENC
Adder
0.658
316212AC1-099_GEN
Solar/Wind Harmer
0.376
3150351NORNECKC2
Adder
0.723
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
315722AD1-056 GEN
Solar/Wind Harmer
0.444
316494AC1-189 GEN
Solar/Wind Harmer
0.235
970919AG2-571 GEN
Solar/Wind Harmer
2.436
970087AG2-069 GEN
Solar/Wind Harmer
5.462
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.068
3145493TOT1
Solar/Wind Harmer
0.303
316129AC1-054 GEN
Solar/Wind Harmer
0.256
3146233WITAKRS
Solar/Wind Harmer
0.27
971065AG2-659 GEN
Solar/Wind Harmer
2.88
316359AB2-059 GEN
Solar/Wind Harmer
0.239
316049AB1-081 GEN
Solar/Wind Harmer
0.38
3145543BTLEBRO
Solar/Wind Harmer
0.066
3145543BTLEBRO
Solar/Wind Harmer
0.053
3142053HEARTS
Solar/Wind Harmer
0.117
957481AF2-042 GEN
Solar/Wind Harmer
17.703
315693AD1-088 GEN
Solar/Wind Harmer
3.143
962491AG1-098 GEN
Solar/Wind Harmer
3.727
970937AG2-583 GEN
Solar/Wind Harmer
3.946
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970685AG2-442 GEN
Solar/Wind Harmer
4.652
963171AG1-166 GEN
Solar/Wind Harmer
0.33
971563AH1-280 GEN
Solar/Wind Harmer
0.661
3144293JTRSVLE
Adder
0.197
315687AD1-152 GEN
Solar/Wind Harmer
0.002
3146926FARMVIL
Solar/Wind Harmer
0.036
970401AG2-262 GEN
Solar/Wind Harmer
0.352
316337AD2-073 GEN
Solar/Wind Harmer
0.051
316322AB2-045
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.023
LAGNLTFEXP_LAGN->PJM
CLTF
3.259
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.253
TVALTFEXP_TVA->PJM
CLTF
1.654
NYPJM->LTFIMP_NY
CLTF
1.306
LGEELTFEXP_LGEE->PJM
CLTF
0.633
WECLTFEXP_WEC->PJM
CLTF
0.314
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.836
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.715
MECLTFEXP_MEC->PJM
CLTF
1.658
SIGELTFEXP_SIGE->PJM
CLTF
0.051
CPLELTFEXP_CPLE->PJM
CLTF
4.134
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.574

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o PEPCO_P1_5070_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
PEPCO_P1_5070_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:140.61 %
Rating:1478.62 MVA
Rating Type:B
MVA to Mitigate:2079.09
MW Contribution:2.82
Bus #Bus NameTypeMW Contribution
972289AH1-729 GEN
50/50
13.249
3150091POSSM6B
50/50
0.848
3150071POSSM 5
50/50
52.224
3150181POSSMC2
50/50
1.152
3150181POSSMC2
50/50
1.143
3150181POSSMC2
50/50
1.143
316447AC1-158 HLD
Solar/Wind Harmer
1.014
3150391LDYSMT3
Adder
12.655
972195AH1-682 GEN
Adder
1.663
315651AD1-115 GEN
Solar/Wind Harmer
0.003
315673AE1-157 GEN
Solar/Wind Harmer
6.396
957411AF2-035 GEN
Solar/Wind Harmer
3.895
970317AG2-208 GEN
Solar/Wind Harmer
3.609
316468AD1-105 GEN
Solar/Wind Harmer
-0.029
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.913
3150341NORNECKC1
Adder
0.906
966001AG1-469 GEN
Solar/Wind Harmer
0.051
958261AF2-120 GEN
Solar/Wind Harmer
2.86
3151731LOISA B
Adder
5.599
3151721LOISA A
Adder
5.57
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.271
3142366NRTHEST
Adder
0.276
3150691DARBY 3
Adder
6.069
3150701DARBY 4
Adder
6.055
3150681DARBY 2
Adder
6.048
3150671DARBY 1
Adder
6.041
316075AC2-137 C
Solar/Wind Harmer
0.023
3142946ENON
Solar/Wind Harmer
0.008
3143526WINTERP
Solar/Wind Harmer
0.435
971223AH1-071 GEN
Solar/Wind Harmer
0.89
944641AF1-129 GEN
Adder
39.415
316240AF1-291 C
Solar/Wind Harmer
0.001
316033AB2-134 GEN
Solar/Wind Harmer
0.005
315697AD1-025 GEN
Solar/Wind Harmer
0.092
316236AE1-162_GEN
Solar/Wind Harmer
0.001
970657AG2-426 GEN
Solar/Wind Harmer
2.829
970657AG2-426 GEN
Solar/Wind Harmer
0.593
316036AC1-147 C
Solar/Wind Harmer
0.015
3150991CHESPKB
Adder
0.845
3150991CHESPKB
Adder
0.825
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.077
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3145506HICKORY
Solar/Wind Harmer
0.321
3145506HICKORY
Solar/Wind Harmer
0.193
3145506HICKORY
Solar/Wind Harmer
0.048
316339AD2-160 GEN
Solar/Wind Harmer
0.13
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.045
3137176SLIGO L2192
Solar/Wind Harmer
0.319
3146456SLIGO L269
Solar/Wind Harmer
1.416
3130086AYDLETT
Solar/Wind Harmer
0.32
3146386ELIZ CT
Solar/Wind Harmer
0.08
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.079
3144356SAPONY
Solar/Wind Harmer
0.657
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.345
3146376EDENTON
Solar/Wind Harmer
0.345
972185AH1-677 GEN
Adder
4.331
972187AH1-678 GEN
Adder
2.184
970933AG2-581 GEN
Solar/Wind Harmer
6.107
316065AD1-022 GEN
Solar/Wind Harmer
3.475
3145893MURPHYS
Solar/Wind Harmer
0.503
3145893MURPHYS
Solar/Wind Harmer
0.135
3146173TUNIS
Solar/Wind Harmer
0.075
3146173TUNIS
Solar/Wind Harmer
0.075
970099AG2-077 GEN
Solar/Wind Harmer
7.908
316181AB2-040 GEN
Solar/Wind Harmer
0.107
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.044
971741AH1-377 GEN
Solar/Wind Harmer
7.304
970301AG2-198 GEN
Solar/Wind Harmer
3.138
316426AA2-053 GEN
Solar/Wind Harmer
0.248
3146776BUCKING
Solar/Wind Harmer
0.293
3145593CAROLNA
Solar/Wind Harmer
0.073
3145593CAROLNA
Solar/Wind Harmer
0.073
3146776BUCKING
Solar/Wind Harmer
0.024
966811AG1-552 GEN
Solar/Wind Harmer
0.795
3145593CAROLNA
Solar/Wind Harmer
0.091
3145783HORNRTN
Solar/Wind Harmer
1.299
3145783HORNRTN
Solar/Wind Harmer
1.039
3145783HORNRTN
Solar/Wind Harmer
0.325
3145783HORNRTN
Solar/Wind Harmer
0.13
3145796HORNRTN
Solar/Wind Harmer
0.219
3147133PAMPLIN
Solar/Wind Harmer
0.072
3147133PAMPLIN
Solar/Wind Harmer
0.058
958211AF2-115 GEN
Solar/Wind Harmer
0.866
963191AG1-168 GEN
Solar/Wind Harmer
0.289
3144293JTRSVLE
Adder
0.23
3144293JTRSVLE
Adder
0.193
3145933PARMELE
Solar/Wind Harmer
0.144
3145933PARMELE
Solar/Wind Harmer
0.072
316274AC1-208 GEN
Solar/Wind Harmer
0.372
316034AC1-036 C
Solar/Wind Harmer
0.005
970323AG2-213 GEN
Solar/Wind Harmer
3.057
971775AH1-396 GEN
Solar/Wind Harmer
0.115
971489AH1-241 GEN
Solar/Wind Harmer
3.817
313527AB2-043 GEN
Solar/Wind Harmer
0.001
939181AE1-148 GEN
Solar/Wind Harmer
3.402
3145493TOT1
Solar/Wind Harmer
0.162
3145453TOT5
Solar/Wind Harmer
0.097
3145603CNETO
Solar/Wind Harmer
0.065
315821AE2-092 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
3.322
961601AG1-000A GEN
Solar/Wind Harmer
1.228
316263AC1-034 GEN
Solar/Wind Harmer
2.624
964791AG1-342 GEN
Solar/Wind Harmer
1.322
3146843MT LREL
Solar/Wind Harmer
0.069
3146843MT LREL
Solar/Wind Harmer
0.069
316222AC1-221 GEN
Solar/Wind Harmer
0.264
971761AH1-387 GEN
Solar/Wind Harmer
1.238
942751AE2-291 GEN
Solar/Wind Harmer
3.276
3132123MT JACKSON
Solar/Wind Harmer
0.183
970117AG2-086 GEN
Solar/Wind Harmer
1.401
970117AG2-086 GEN
Solar/Wind Harmer
0.934
226929AD2-058 GEN
Solar/Wind Helper
0.143
237025AB1-124 C
Solar/Wind Helper
0.193
237006AB1-125 GEN
Solar/Wind Helper
0.145
23777801MSM_W1-116
Solar/Wind Helper
0.13
237034AC2-136 C
Solar/Wind Helper
0.205
205916AD1-020 GEN
Solar/Wind Helper
1.48
208835TUHI V3-051
Solar/Wind Helper
0.019
208835TUHI V3-051
Solar/Wind Helper
0.019
237001AB1-127_GEN
Solar/Wind Helper
0.307
237002AB1-128_GEN
Solar/Wind Helper
0.298
235063AE1-101 C2
Solar/Wind Helper
1.064
20390526W1-045 C
Solar/Wind Helper
0.252
23777901MDS_W4-102
Solar/Wind Helper
0.105
235020AA1-095 C
Solar/Wind Helper
0.029
233933AB2-153 GEN
Solar/Wind Helper
0.14
233944AB2-135 GEN
Solar/Wind Helper
0.355
232424Y1-079 C
Solar/Wind Helper
0.07
233987AB2-037 GEN
Solar/Wind Helper
1.406
233946AB2-136 GEN
Solar/Wind Helper
0.341
234036AF2-325 C
Solar/Wind Helper
0.025
970053AG2-049 GEN
50/50
2.022
3138216PACIFIC
Solar/Wind Harmer
0.025
316411AF1-147_GEN1
Solar/Wind Harmer
0.003
316415AF1-147_GEN2
Solar/Wind Harmer
0.003
3141426STAFORD
Solar/Wind Harmer
0.023
3150411LDYSMT5
Adder
12.718
3150381LDYSMT2
Adder
12.172
972213AH1-691 GEN
Adder
2.059
972215AH1-692 GEN
Adder
2.059
316164AC1-076 GEN
Solar/Wind Harmer
0.132
944491AF1-114 GEN
Solar/Wind Harmer
0
316223AC1-118
Solar/Wind Harmer
0.064
972189AH1-679 GEN
Adder
1.467
3141813NORNECK
Solar/Wind Harmer
0.087
970327AG2-215 GEN
Solar/Wind Harmer
2.824
962981AG1-147 GEN
Solar/Wind Harmer
3.203
3141783LANCAST
Solar/Wind Harmer
0.051
3141783LANCAST
Solar/Wind Harmer
0.034
3138133OCRAN
Solar/Wind Harmer
0.025
3141913WHIT STONE
Solar/Wind Harmer
0.085
3147346CASHSCORNER
Solar/Wind Harmer
0.196
316312AB1-027
Solar/Wind Harmer
0.152
316314AB2-024 C
Solar/Wind Harmer
0
316059AD1-063 C
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.017
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
2.507
3143873LANEXA
Solar/Wind Harmer
0.051
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
971167AH1-042 GEN
Solar/Wind Harmer
7.477
315976AC1-164 GENA
Solar/Wind Harmer
8.72
316169AC1-164_GENC
Solar/Wind Harmer
7.533
315975AC1-164 GENB
Solar/Wind Harmer
0.258
316233AE1-074 FULL
Solar/Wind Harmer
0.067
971281AH1-106 GEN
Solar/Wind Harmer
1.161
971283AH1-107 GEN
Solar/Wind Harmer
1.161
971285AH1-108 GEN
Adder
0.631
3138283WHITEMARSH
Solar/Wind Harmer
0.019
316132AB2-190 GEN1
Solar/Wind Harmer
0.442
316369SG1_INVT
Solar/Wind Harmer
0.003
972265AH1-717 GEN
Adder
6.337
3151201GRAVEL4
Adder
5.94
3151191GRAVEL3
Adder
5.865
3151211GRAVEL5
Adder
5.865
971445AH1-216 GEN
Solar/Wind Harmer
5.723
3143316POE
Solar/Wind Harmer
0.321
3151081ELIZAR1
Adder
7.394
3151091ELIZAR2
Adder
7.266
3152611GOSPORTB
Adder
1.027
3152621GOSPORTC
Adder
0.872
3152601GOSPORTA
Adder
0.804
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.055
316311AC2-079 GEN
Solar/Wind Harmer
2.303
957871AF2-081 GEN
Solar/Wind Harmer
3.99
316305AF2-043 C
Solar/Wind Harmer
0.001
319010AE1-072 C
Solar/Wind Harmer
0.403
3146406KITTY HAWK
Solar/Wind Harmer
0.01
315835AF2-110_GEN
Solar/Wind Harmer
0.548
313526AB2-022
Solar/Wind Harmer
0.043
3146486SUNBURY
Solar/Wind Harmer
0.079
3146486SUNBURY
Solar/Wind Harmer
0.079
316321Z2-027
Solar/Wind Harmer
0.015
3146396TANGLEW
Solar/Wind Harmer
0.219
3145176PASQUOTANK
Solar/Wind Harmer
0.049
316315AB2-025 C
Solar/Wind Harmer
0.064
315814AE2-033 C
Solar/Wind Harmer
6.204
941031AE2-094 GEN
Solar/Wind Harmer
14.412
944011AF1-069 GEN
Solar/Wind Harmer
4.709
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.078
3130156CHOWAN
Solar/Wind Harmer
0.078
970673AG2-436 GEN
Solar/Wind Harmer
16.54
970673AG2-436 GEN
Solar/Wind Harmer
11.027
971967AH1-528 GEN
Solar/Wind Harmer
12.344
315816AE2-034 GEN
Solar/Wind Harmer
0.329
3130546PLYMOUTH
Solar/Wind Harmer
0.076
315732AD1-074 GEN1
Solar/Wind Harmer
0.435
315733AD1-074 GEN2
Solar/Wind Harmer
0.435
315735AD1-075 GEN1
Solar/Wind Harmer
0.218
965291AG1-394 GEN
Solar/Wind Harmer
0.336
3146206CASHIE
Solar/Wind Harmer
0.075
970601AG2-382 GEN
Solar/Wind Harmer
2.811
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
970085AG2-068 GEN
Solar/Wind Harmer
4
970581AG2-369 GEN
Solar/Wind Harmer
3.44
3145513AHOSKIE
Solar/Wind Harmer
0.156
3145513AHOSKIE
Solar/Wind Harmer
0.074
3146043SEABORD
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.149
3145683EARLEYS
Solar/Wind Harmer
0.074
3145683EARLEYS
Solar/Wind Harmer
0.074
315607AA1-063A GEN
Solar/Wind Harmer
0.152
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.294
315652AC1-086 GEN
Solar/Wind Harmer
8.087
972205AH1-687 GEN
Adder
3.134
970285AG2-188 GEN
Solar/Wind Harmer
5.802
971845AH1-439 GEN
Solar/Wind Harmer
3.325
3145796HORNRTN
Solar/Wind Harmer
0.233
3145796HORNRTN
Solar/Wind Harmer
0.029
3146033SCOT NK
Solar/Wind Harmer
0.29
315657AE1-056 GEN
Solar/Wind Harmer
2.494
946301AF1-294 GEN
Solar/Wind Harmer
1.424
961791AG1-021 GEN
Solar/Wind Harmer
0.693
970683AG2-441 GEN
Solar/Wind Harmer
4.794
970681AG2-440 GEN
Solar/Wind Harmer
3.836
970831AG2-522 GEN
Solar/Wind Harmer
3.066
972193AH1-681 GEN
Adder
1.643
3144303KENBRDG
Solar/Wind Harmer
0.057
971443AH1-215 GEN
Solar/Wind Harmer
1.204
971447AH1-217 GEN
Solar/Wind Harmer
2.163
316005AA1-067
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.282
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
970181AG2-120 GEN
Solar/Wind Harmer
0.883
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3138266HYDRAULIC
Solar/Wind Harmer
0.003
3138266HYDRAULIC
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
3.032
316420AA1-050 GEN
Solar/Wind Harmer
0.002
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.07
3145573BETHELC
Solar/Wind Harmer
0.07
316118AC1-105 GEN
Solar/Wind Harmer
0.176
3147173SINAI
Solar/Wind Harmer
0.067
3147243WELCO
Solar/Wind Harmer
0.042
270494AE1-108_GEN
Solar/Wind Harmer
0.802
3148133STUARTS
Solar/Wind Harmer
0.039
3148013FISHERV
Solar/Wind Harmer
0.037
970865AG2-541 GEN
Solar/Wind Harmer
2.214
316123AC1-075 GEN
Solar/Wind Harmer
0.084
970165AG2-112 GEN
Solar/Wind Harmer
0.5
970163AG2-111 GEN
Solar/Wind Harmer
0.477
3148463FAIRFLD
Solar/Wind Harmer
0.06
3151881LOWMORC
Adder
0.64
3151881LOWMORC
Adder
0.63
3151861LOWMORA
Adder
0.62
960921AF2-383 GEN
Solar/Wind Helper
0.279
205943AE1-185 GEN
Solar/Wind Helper
0.387
205956AE1-196_GEN
Solar/Wind Helper
0.385
205932AD2-116_GEN
Solar/Wind Helper
0.385
959381AF2-229 GEN
Solar/Wind Helper
0.257
237085AD2-009_GEN
Solar/Wind Helper
0.97
203975AE1-071-GEN
Solar/Wind Helper
1.713
233935AB2-179 C
Solar/Wind Helper
0.772
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.575
233990AG1-397 GEN
Solar/Wind Helper
0.162
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.208
964001AG1-254 GEN
Solar/Wind Helper
0.565
219914AD2-027 C
Solar/Wind Helper
0.068
227927V4-067C
Solar/Wind Helper
0.006
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
219607WPEMNERT C
Solar/Wind Helper
0.047
214067T20SOLAR
Solar/Wind Helper
0.007
20715728PEM_W1-119
Solar/Wind Helper
0.056
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
966261AG1-495 GEN
Solar/Wind Helper
0.047
20675928HOL_W4-097
Solar/Wind Helper
0.029
207530AG1-191 GEN
Solar/Wind Helper
0.038
3152111X4-039 GT1
50/50
1.838
315747AE2-019 GEN
50/50
13.176
3150021OMF B
50/50
0.216
3150101POSSM6S
50/50
1.296
3150081POSSM6A
50/50
0.848
3150151POSSMC1
50/50
1.143
3150151POSSMC1
50/50
1.143
3150231REMNGT3
50/50
14.281
3150241REMNGT4
50/50
13.316
972217AH1-693 GEN
50/50
1.756
963691AG1-221 GEN
Solar/Wind Harmer
2.312
971455AH1-223 GEN
Solar/Wind Harmer
2.312
3141196NOKESVL
Solar/Wind Harmer
0.429
972199AH1-684 GEN
Adder
1.903
3150301M RUN C
Adder
13.349
3150291M RUN B
Adder
13.25
3150331BIRCHWDA
Adder
16.626
3141316ARNOLDS
Adder
0.229
316044AC1-158 PL1
Solar/Wind Harmer
0.461
316450AC1-158 RIC
Solar/Wind Harmer
0.123
3150401LDYSMT4
Adder
12.678
3150371LDYSMT1
Adder
12.251
316170AC1-121 GEN2
Solar/Wind Harmer
0.1
970737AG2-469 GEN
Solar/Wind Harmer
3.872
3141906WESTMOR
Solar/Wind Harmer
0.036
3132273ORANGE
Solar/Wind Harmer
0.018
971781AH1-399 GEN
Solar/Wind Harmer
0.118
3147666LOUISA
Solar/Wind Harmer
0.204
3150351NORNECKC2
Adder
0.884
316404AE1-155 C
Solar/Wind Harmer
0.019
3151761LOISA E
Adder
11.415
972183AH1-676 GEN
Adder
92.045
970009AG2-005 GEN
Solar/Wind Harmer
0.643
316473AC1-191 GEN
Solar/Wind Harmer
0.29
962971AG1-146 GEN
Solar/Wind Harmer
1.373
3142416OLDCHRC
Solar/Wind Harmer
0.821
3141766HARMONY
Solar/Wind Harmer
1.129
316156AD2-030 GEN
Solar/Wind Harmer
0.063
3141873WAN 176
Solar/Wind Harmer
1.505
316280AD1-041 GEN
Solar/Wind Harmer
0.002
316203AE2-005 GEN
Solar/Wind Harmer
0
3141843SHACKLE
Adder
0.432
970293AG2-193 GEN
Solar/Wind Harmer
0.899
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3142946ENON
Solar/Wind Harmer
0.028
3150861SPRUNCD
Adder
0.385
316382AG1-145 C
Solar/Wind Harmer
0.001
970133AG2-095 GEN
Solar/Wind Harmer
0.794
970129AG2-093 GEN
Solar/Wind Harmer
4.984
3150921YORKTN3
Adder
2.069
315778AD1-151 GEN
Solar/Wind Harmer
6.579
965281AG1-393 GEN
Solar/Wind Harmer
0.877
3144216WINCHST
Adder
0.31
315839AE2-212 C
Solar/Wind Harmer
0.001
961611AG1-000B GEN
Solar/Wind Harmer
2.181
3151221GRAVEL6
Adder
5.934
3151171GRAVELC
Adder
1.142
3145336SMITFLD
Solar/Wind Harmer
0.033
315813AE1-149 C
Solar/Wind Harmer
4.334
315773AC2-141 GEN
Solar/Wind Harmer
2.962
970659AG2-427 GEN
Solar/Wind Harmer
0.856
316083AB2-161 GEN
Solar/Wind Harmer
0.001
3144536CHRHLND
Solar/Wind Harmer
0.012
3151101ELIZAR3
Adder
7.489
970661AG2-428 GEN
Solar/Wind Harmer
1.707
3144873MCLAUGH
Solar/Wind Harmer
0.002
944581AF1-123 GEN
Solar/Wind Harmer
18.149
944601AF1-125 GEN
Solar/Wind Harmer
17.869
3146456SLIGO L269
Solar/Wind Harmer
0.08
971153AH1-033 GEN
Solar/Wind Harmer
0.925
316320Y1-086
Solar/Wind Harmer
0
316313AB2-026
Solar/Wind Harmer
0.05
316258AE1-075 C
Solar/Wind Harmer
0.06
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
1.2
316435W1029_GEN3
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.079
3145273HOLLAND
Solar/Wind Harmer
0.059
3146376EDENTON
Solar/Wind Harmer
0.078
315614AA2-178 GEN
Solar/Wind Harmer
0.439
971157AH1-035 GEN
Solar/Wind Harmer
0.911
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
315737AD1-076 GEN
Solar/Wind Harmer
0.975
3146206CASHIE
Solar/Wind Harmer
0.075
316365GEN2_N
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
970917AG2-570 GEN
Solar/Wind Harmer
6.681
957521AF2-046 GEN
Solar/Wind Harmer
5.587
961681AG1-008 GEN
Solar/Wind Harmer
5.587
3146173TUNIS
Solar/Wind Harmer
0.075
3156021HOLLOMANSOL
Solar/Wind Harmer
0.339
316463AE2-346 GEN
Solar/Wind Harmer
0.064
316140AB2-099
Solar/Wind Harmer
0.027
3152131X4-039 ST
50/50
2.892
3152121X4-039 GT2
50/50
1.833
3150011OMF A
50/50
0.216
3140676OCCOQUN
50/50
0.286
970467AG2-304 GEN
50/50
14.788
972223AH1-696 GEN
50/50
9.026
3150151POSSMC1
50/50
1.143
3141346CRANES
50/50
0.127
3150221REMNGT2
50/50
13.228
972201AH1-685 GEN
50/50
2.282
3150211REMNGT1
Adder
12.383
3150281M RUN A
Adder
13.357
316006AB2-029 C
Solar/Wind Harmer
0.001
971685AH1-345 GEN
Solar/Wind Harmer
0.73
316045AC1-158 PL2
Solar/Wind Harmer
1.475
972197AH1-683 GEN
Adder
1.98
972219AH1-694 GEN
Adder
1.425
316254AC1-120 GEN1
Solar/Wind Harmer
0.2
972135AH1-637 GEN
Solar/Wind Harmer
0.781
966881AG1-559 GEN
Solar/Wind Harmer
0.105
315683AE1-153 C
Solar/Wind Harmer
7.218
3147666LOUISA
Solar/Wind Harmer
0.355
316192AB2-158 GEN
Solar/Wind Harmer
0.501
316337AD2-073 GEN
Solar/Wind Harmer
0.077
3150351NORNECKC2
Adder
0.87
3141726DUNNSVL
Solar/Wind Harmer
0.348
962861AG1-135 GEN
Solar/Wind Harmer
2.764
3151751LOISA D
Adder
5.599
3138133OCRAN
Solar/Wind Harmer
0.051
3142416OLDCHRC
Solar/Wind Harmer
0.22
3142416OLDCHRC
Solar/Wind Harmer
0.084
3141766HARMONY
Solar/Wind Harmer
0.017
971777AH1-397 GEN
Solar/Wind Harmer
0.223
3141843SHACKLE
Adder
0.432
3142433PROV 92
Solar/Wind Harmer
0.337
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143526WINTERP
Solar/Wind Harmer
0.435
3142543TWELFTH
Solar/Wind Harmer
0.008
3150851SPRUNCC
Adder
0.385
944631AF1-128 GEN
Adder
39.853
3143226MDLTHAN
Solar/Wind Harmer
0.083
316159AE1-175 C
Solar/Wind Harmer
0.072
971317AH1-138 GEN
Solar/Wind Harmer
0.618
970129AG2-093 GEN
Solar/Wind Harmer
2.345
316458AB2-190 GEN2
Solar/Wind Harmer
0.442
315671AE2-027_GEN
Solar/Wind Harmer
5.273
3138126ROCKLANDING
Solar/Wind Harmer
0.038
971069AG2-661 GEN
Solar/Wind Harmer
1.462
971647AH1-324 GEN
Solar/Wind Harmer
3.497
961611AG1-000B GEN
Solar/Wind Harmer
4.29
3151171GRAVELC
Adder
0.868
3145336SMITFLD
Solar/Wind Harmer
0.325
316294AC1-161 GEN
Solar/Wind Harmer
1.405
970659AG2-427 GEN
Solar/Wind Harmer
3.913
316381AD1-082 GEN
Solar/Wind Harmer
0.084
316375AC2-012 GEN
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
8.025
3150981CHESPKA
Adder
1.007
944591AF1-124 GEN
Solar/Wind Harmer
18.213
316072AD1-144
Solar/Wind Harmer
0.029
316388AE2-253 GEN
Solar/Wind Harmer
0.251
3146456SLIGO L269
Solar/Wind Harmer
0.08
939411AE1-173 GEN
Solar/Wind Harmer
34.166
316246AF1-032 C
Solar/Wind Harmer
0.036
940641AE2-051 GEN
Solar/Wind Harmer
6.396
316093AE2-104_GEN
Solar/Wind Harmer
1.342
3143336POWHATN
Solar/Wind Harmer
1.412
3146516WINFALL
Solar/Wind Harmer
0.256
3146516WINFALL
Solar/Wind Harmer
0.079
962331AG1-082 GEN
Solar/Wind Harmer
0.795
3146263WOODLND
Solar/Wind Harmer
0.074
313506AB2-031 GEN
Solar/Wind Harmer
0.228
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3145963POPLR C
Solar/Wind Harmer
0.074
970909AG2-566 GEN
Solar/Wind Harmer
0.785
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.073
3147043LAWRENC
Solar/Wind Harmer
0.044
3146776BUCKING
Solar/Wind Harmer
0.026
3146926FARMVIL
Solar/Wind Harmer
0.044
3145796HORNRTN
Solar/Wind Harmer
0.291
3145796HORNRTN
Solar/Wind Harmer
0.073
942461AE2-259 GEN
Solar/Wind Harmer
0
316478AD1-087 GEN
Solar/Wind Harmer
0.254
316486AD2-202 GEN
Solar/Wind Harmer
0.075
3147133PAMPLIN
Solar/Wind Harmer
0.227
971193AH1-056 GEN
Solar/Wind Harmer
4.404
963181AG1-167 GEN
Solar/Wind Harmer
0.289
3144293JTRSVLE
Adder
0.23
316210AC1-098 GEN
Solar/Wind Harmer
0.668
972255AH1-712 GEN
Adder
36.775
3145933PARMELE
Solar/Wind Harmer
0.072
966801AG1-551 GEN
Solar/Wind Harmer
0.836
959311AF2-222 GEN
Solar/Wind Harmer
6.376
970257AG2-171 GEN
Solar/Wind Harmer
2.293
970221AG2-151 GEN
Solar/Wind Harmer
3.817
315785AD2-033 C
Solar/Wind Harmer
0.582
964241AG1-285 GEN
Solar/Wind Harmer
4.753
316131AB2-060 GEN
Solar/Wind Harmer
0.224
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
315724AD1-057 GEN
Solar/Wind Harmer
0.266
316327AA2-057 GEN
Solar/Wind Harmer
0.106
3146233WITAKRS
Solar/Wind Harmer
0.35
3146233WITAKRS
Solar/Wind Harmer
0.047
3146073TAR RVR
Solar/Wind Harmer
0.07
3146083TARBORO
Solar/Wind Harmer
0.07
3138543CONSLDL
Solar/Wind Harmer
0.046
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.069
961601AG1-000A GEN
Solar/Wind Harmer
4.912
971623AH1-311 GEN
Solar/Wind Harmer
0.138
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.87
971683AH1-343 GEN
Solar/Wind Harmer
2.391
3148013FISHERV
Solar/Wind Harmer
0.065
316283AC2-100 C
Solar/Wind Harmer
0.124
315616AA1-038_C
Solar/Wind Harmer
0
3151861LOWMORA
Adder
0.645
958131AF2-107 GEN
Solar/Wind Harmer
1.618
226910AB2-157 C
Solar/Wind Helper
0.02
227287AC2-120 GEN
Solar/Wind Helper
0.49
237030AB1-096 C
Solar/Wind Helper
0.083
223402AF1-300 C
Solar/Wind Helper
0.397
205917AD1-020 ES
Solar/Wind Helper
0.318
238221AF1-254 C O1
Solar/Wind Helper
0.179
235067AD1-061 GEN
Solar/Wind Helper
0.312
233982AB2-133 GEN
Solar/Wind Helper
0.216
233918AB1-142 GEN
Solar/Wind Helper
0.303
233994AC2-023 GEN
Solar/Wind Helper
0.577
233996TM1833_GEN
Solar/Wind Helper
0.157
233997TMININ_4.2
Solar/Wind Helper
0.157
233940AF2-379 C
Solar/Wind Helper
0.037
234015AF2-250 C
Solar/Wind Helper
0.023
233952AC2-187 GEN
Solar/Wind Helper
0.139
232406W1-004 FULL
Solar/Wind Helper
0.304
233971AC1-093 C
Solar/Wind Helper
0.214
230430AE1-229_GEN
Solar/Wind Helper
1.995
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.089
228729W2-030 C
Solar/Wind Helper
0.065
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20716028EGP_W2-019
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.037
20715028HAN_X4-015
Solar/Wind Helper
0.033
219276PARKLANDSO C
Solar/Wind Helper
0.052
20714528FRN_Y2-051
Solar/Wind Helper
0.033
20720528MAN_W1-024
Solar/Wind Helper
0.016
219612MATRIX C
Solar/Wind Helper
0.014
218438BLK ROCK C
Solar/Wind Helper
0.016
20673728F2S_V4-070
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
219919AE1-041 FULL
Solar/Wind Helper
0.002
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
207510AF2-138 C
Solar/Wind Helper
0.046
20674628WNG_W3-110
Solar/Wind Helper
0.051
963161AG1-165 GEN
Solar/Wind Helper
0.242
963071AG1-156 GEN
Solar/Wind Helper
0.783
209027LOR2_Q27
Solar/Wind Helper
0.557
961331AF2-424 GEN
Solar/Wind Helper
0.237
961421AF2-433 GEN
Solar/Wind Helper
0.236
957921AF2-086 GEN
Solar/Wind Helper
0.234
946691AF1-333 GEN
Solar/Wind Helper
0.233
946741AF1-338 GEN
Solar/Wind Helper
0.233
209067AE2-060 GEN
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.139
232408W1-005 C
Solar/Wind Helper
0.304
232410W1-006 C
Solar/Wind Helper
0.304
233939AC1-091 C
Solar/Wind Helper
0.209
233970AC1-092 C
Solar/Wind Helper
0.209
230433AD2-135 GEN
Solar/Wind Helper
0.01
219921AF1-264
Solar/Wind Helper
0.03
230407AD2-065 C
Solar/Wind Helper
0.024
219615MILLCREEK C
Solar/Wind Helper
0.016
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20714928UPF_X1-085
Solar/Wind Helper
0.003
20720628TIN_W1-124
Solar/Wind Helper
0.11
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.009
207442AE1-156 GEN
Solar/Wind Helper
0.188
20676128MHD_W3-029
Solar/Wind Helper
0.055
20671828STAW2-080
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
207471AF2-354 C
Solar/Wind Helper
0.097
20674928WA_W3-044
Solar/Wind Helper
0.056
964851AG1-348 GEN
Solar/Wind Helper
0.046
20674128FR_U2-059
Solar/Wind Helper
0.002
20676228FRD_X1-012
Solar/Wind Helper
0.052
966111AG1-480 GEN
Solar/Wind Helper
0.042
211065PSPA IPP
Solar/Wind Helper
0.085
211065PSPA IPP
Solar/Wind Helper
0.085
208972BECR K09
Solar/Wind Helper
0.178
961431AF2-434 GEN
Solar/Wind Helper
0.236
209029WAYMART-WD
Solar/Wind Helper
0.443
209054AE2-059 GEN
Solar/Wind Helper
0.042
946751AF1-339 GEN
Solar/Wind Helper
0.233
209137AF2-361 C
Solar/Wind Helper
0.708
207484AF2-139 C O1
Solar/Wind Helper
0.048
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
20675128HRM_W1-127
Solar/Wind Helper
0.017
209116AE2-175 GEN
Solar/Wind Helper
1.004
961261AF2-417 GEN
Solar/Wind Helper
0.241
959431AF2-234 GEN
Solar/Wind Helper
0.466
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
959421AF2-233 GEN
Solar/Wind Helper
0.233
238208AF1-136 C
Solar/Wind Helper
0.089
316336AC2-165 C
Solar/Wind Harmer
0.003
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.078
3145663CRESWEL
Solar/Wind Harmer
0.215
971163AH1-040 GEN
Solar/Wind Harmer
6.133
970937AG2-583 GEN
Solar/Wind Harmer
4.64
3146206CASHIE
Solar/Wind Harmer
0.075
971547AH1-271 GEN
Solar/Wind Harmer
1.606
316023GEN1_S
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
0.301
3145893MURPHYS
Solar/Wind Harmer
0.334
970919AG2-571 GEN
Solar/Wind Harmer
2.672
970087AG2-069 GEN
Solar/Wind Harmer
5.999
3146173TUNIS
Solar/Wind Harmer
0.075
960081AF2-299 GEN
Solar/Wind Harmer
0.714
3145683EARLEYS
Solar/Wind Harmer
0.074
957481AF2-042 GEN
Solar/Wind Harmer
19.771
3146263WOODLND
Solar/Wind Harmer
0.074
315693AD1-088 GEN
Solar/Wind Harmer
3.545
962491AG1-098 GEN
Solar/Wind Harmer
4.214
971795AH1-408 GEN
Solar/Wind Harmer
4.913
3145963POPLR C
Solar/Wind Harmer
0.074
316011AB1-132 GEN
Solar/Wind Harmer
1.337
962571AG1-106 GEN
Solar/Wind Harmer
1.046
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.073
3147043LAWRENC
Adder
0.664
972003AH1-546 GEN
Solar/Wind Harmer
3.117
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.029
3146926FARMVIL
Solar/Wind Harmer
0.044
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145783HORNRTN
Solar/Wind Harmer
0.073
3145796HORNRTN
Solar/Wind Harmer
0.24
3145796HORNRTN
Solar/Wind Harmer
0.073
963171AG1-166 GEN
Solar/Wind Harmer
0.385
971563AH1-280 GEN
Solar/Wind Harmer
0.77
3144293JTRSVLE
Adder
0.23
316212AC1-099_GEN
Solar/Wind Harmer
0.372
970685AG2-442 GEN
Solar/Wind Harmer
5.37
972277AH1-723 GEN
Adder
42.854
3146293MARTNCO
Solar/Wind Harmer
0.067
316129AC1-054 GEN
Solar/Wind Harmer
0.27
971377AH1-170 GEN
Solar/Wind Harmer
0.763
3147623JAMES R
Solar/Wind Harmer
0.166
971065AG2-659 GEN
Solar/Wind Harmer
3.053
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315722AD1-056 GEN
Solar/Wind Harmer
0.448
315687AD1-152 GEN
Solar/Wind Harmer
0.002
316494AC1-189 GEN
Solar/Wind Harmer
0.238
3146233WITAKRS
Solar/Wind Harmer
0.278
961671AG1-007 GEN
Solar/Wind Harmer
0.011
3146083TARBORO
Solar/Wind Harmer
0.07
3145493TOT1
Solar/Wind Harmer
0.31
316359AB2-059 GEN
Solar/Wind Harmer
0.248
316049AB1-081 GEN
Solar/Wind Harmer
0.395
3145543BTLEBRO
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.055
3142053HEARTS
Solar/Wind Harmer
0.122
970401AG2-262 GEN
Solar/Wind Harmer
0.404
316003AC1-222 GEN
Solar/Wind Harmer
0.002
315705AF1-075 GEN
Solar/Wind Harmer
2.472
3147983MERCK5
Solar/Wind Harmer
0.024
23779801AA1-109
Solar/Wind Helper
0.218
223401AF1-299 GEN
Solar/Wind Helper
0.397
966131AG1-482 GEN
Solar/Wind Helper
0.111
237080AD1-060 GEN
Solar/Wind Helper
0.221
235062AE1-101 C1
Solar/Wind Helper
1.064
237038AE2-054 C
Solar/Wind Helper
0.173
233930AB2-032 GEN
Solar/Wind Helper
0.23
233915AB1-141 GEN
Solar/Wind Helper
0.303
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
233998TM1NIN_3.36
Solar/Wind Helper
0.157
232428Y3-058 C
Solar/Wind Helper
0.203
233954AC2-188 GEN
Solar/Wind Helper
0.139
232404W1-003 C
Solar/Wind Helper
0.304
233950AC2-186 GEN
Solar/Wind Helper
0.07
232434Z2-077 GEN
Solar/Wind Helper
0.076
233972AC1-094 C
Solar/Wind Helper
0.181
205941AD2-115 GEN
Solar/Wind Helper
0.302
230434AG1-499 GEN
Solar/Wind Helper
0.136
230511AF1-262
Solar/Wind Helper
0.009
219258KINSLEYDEP C
Solar/Wind Helper
0.045
228728W1-130C
Solar/Wind Helper
0.032
219904AC1-010 C
Solar/Wind Helper
0.036
219907AC1-030 C
Solar/Wind Helper
0.02
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
20720728JCB_W1-129
Solar/Wind Helper
0.033
207445AB1-138_GEN
Solar/Wind Helper
0.061
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
207454AA2-184 E
Solar/Wind Helper
0.18
20715228NPK_W1-113
Solar/Wind Helper
0.045
20742028HF_AC1-207
Solar/Wind Helper
0.082
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
20675428EAM_W2-061
Solar/Wind Helper
0.009
218428ETC SOLAR C
Solar/Wind Helper
0.003
20676428JCR_X2-075
Solar/Wind Helper
0.039
217213AMBOY SO C
Solar/Wind Helper
0.017
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.013
207437AD2-070 GEN
Solar/Wind Helper
0.079
207439AE1-081 C O1
Solar/Wind Helper
0.011
207518AF1-320_GEN
Solar/Wind Helper
0.9
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
212266LOR1
Solar/Wind Helper
0.026
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.829
946731AF1-337 GEN
Solar/Wind Helper
0.233
209071AE2-133 GEN
Solar/Wind Helper
0.042
LAGNLTFEXP_LAGN->PJM
CLTF
6.324
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.565
TVALTFEXP_TVA->PJM
CLTF
3.188
NYPJM->LTFIMP_NY
CLTF
2.575
LGEELTFEXP_LGEE->PJM
CLTF
1.805
WECLTFEXP_WEC->PJM
CLTF
0.962
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.485
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.592
MECLTFEXP_MEC->PJM
CLTF
4.449
SIGELTFEXP_SIGE->PJM
CLTF
0.14
CPLELTFEXP_CPLE->PJM
CLTF
5.065
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.965

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o AP_P1-2_PE-500-406T_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-406T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.09 %
Rating:1478.62 MVA
Rating Type:B
MVA to Mitigate:1509.53
MW Contribution:2.04
Bus #Bus NameTypeMW Contribution
3152111X4-039 GT1
50/50
1.827
315747AE2-019 GEN
50/50
12.182
972285AH1-727 GEN
50/50
35.211
3150231REMNGT3
50/50
11.996
3150241REMNGT4
50/50
11.185
972217AH1-693 GEN
50/50
1.475
963691AG1-221 GEN
Solar/Wind Harmer
2.201
971455AH1-223 GEN
Solar/Wind Harmer
2.201
3141196NOKESVL
Solar/Wind Harmer
0.372
972199AH1-684 GEN
Adder
1.598
3150301M RUN C
Adder
11.196
3150291M RUN B
Adder
11.113
316170AC1-121 GEN2
Solar/Wind Harmer
0.08
316044AC1-158 PL1
Solar/Wind Harmer
0.361
316450AC1-158 RIC
Solar/Wind Harmer
0.096
3132273ORANGE
Solar/Wind Harmer
0.014
3150151POSSMC1
Adder
0.696
3150151POSSMC1
Adder
0.696
3147666LOUISA
Solar/Wind Harmer
0.158
3151761LOISA E
Adder
9.041
972183AH1-676 GEN
Adder
72.988
3150331BIRCHWDA
Adder
11.297
3141316ARNOLDS
Adder
0.157
3150401LDYSMT4
Adder
8.853
3150371LDYSMT1
Adder
8.554
970737AG2-469 GEN
Solar/Wind Harmer
2.728
971781AH1-399 GEN
Solar/Wind Harmer
0.084
970053AG2-049 GEN
50/50
1.525
3138216PACIFIC
Solar/Wind Harmer
0.024
316411AF1-147_GEN1
Solar/Wind Harmer
0.003
316415AF1-147_GEN2
Solar/Wind Harmer
0.003
316164AC1-076 GEN
Solar/Wind Harmer
0.104
3141426STAFORD
Solar/Wind Harmer
0.015
3147346CASHSCORNER
Solar/Wind Harmer
0.156
3150411LDYSMT5
Adder
8.881
3150381LDYSMT2
Adder
8.499
972213AH1-691 GEN
Adder
1.438
972215AH1-692 GEN
Adder
1.438
944491AF1-114 GEN
Solar/Wind Harmer
0
316223AC1-118
Solar/Wind Harmer
0.046
972189AH1-679 GEN
Adder
1.058
3141813NORNECK
Solar/Wind Harmer
0.063
970327AG2-215 GEN
Solar/Wind Harmer
2.041
962981AG1-147 GEN
Solar/Wind Harmer
2.318
316312AB1-027
Solar/Wind Harmer
0.111
316233AE1-074 FULL
Solar/Wind Harmer
0.05
3141783LANCAST
Solar/Wind Harmer
0.037
3141783LANCAST
Solar/Wind Harmer
0.025
971281AH1-106 GEN
Solar/Wind Harmer
0.859
971283AH1-107 GEN
Solar/Wind Harmer
0.859
3138133OCRAN
Solar/Wind Harmer
0.019
3141913WHIT STONE
Solar/Wind Harmer
0.062
316314AB2-024 C
Solar/Wind Harmer
0
316059AD1-063 C
Solar/Wind Harmer
0
315662AE1-191 GEN
Solar/Wind Harmer
0.002
315666AE1-190 GEN
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.037
3141873WAN 176
Solar/Wind Harmer
0.012
970189AG2-124 GEN
Solar/Wind Harmer
1.827
971285AH1-108 GEN
Adder
0.465
3142433PROV 92
Adder
0.12
3142433PROV 92
Adder
0.12
315976AC1-164 GENA
Solar/Wind Harmer
6.381
971167AH1-042 GEN
Solar/Wind Harmer
5.466
316169AC1-164_GENC
Solar/Wind Harmer
5.512
315975AC1-164 GENB
Solar/Wind Harmer
0.189
3138283WHITEMARSH
Solar/Wind Harmer
0.014
316132AB2-190 GEN1
Solar/Wind Harmer
0.326
3152131X4-039 ST
50/50
2.874
3152121X4-039 GT2
50/50
1.821
970467AG2-304 GEN
50/50
12.983
3150221REMNGT2
50/50
11.111
972201AH1-685 GEN
50/50
1.917
3150211REMNGT1
Adder
10.402
3150281M RUN A
Adder
11.203
316006AB2-029 C
Solar/Wind Harmer
0
971685AH1-345 GEN
Solar/Wind Harmer
0.609
3140676OCCOQUN
Adder
0.198
316254AC1-120 GEN1
Solar/Wind Harmer
0.16
316045AC1-158 PL2
Solar/Wind Harmer
1.156
315683AE1-153 C
Solar/Wind Harmer
5.861
972223AH1-696 GEN
Adder
5.499
3150151POSSMC1
Adder
0.696
3147666LOUISA
Solar/Wind Harmer
0.275
316192AB2-158 GEN
Solar/Wind Harmer
0.388
3151751LOISA D
Adder
4.435
3141346CRANES
Adder
0.08
972197AH1-683 GEN
Adder
1.382
972219AH1-694 GEN
Adder
0.995
966881AG1-559 GEN
Solar/Wind Harmer
0.075
972135AH1-637 GEN
Solar/Wind Harmer
0.548
316337AD2-073 GEN
Solar/Wind Harmer
0.055
3150351NORNECKC2
Adder
0.624
3141726DUNNSVL
Solar/Wind Harmer
0.25
962861AG1-135 GEN
Solar/Wind Harmer
1.994
3143226MDLTHAN
Solar/Wind Harmer
0.062
3143526WINTERP
Solar/Wind Harmer
0.322
3142416OLDCHRC
Solar/Wind Harmer
0.161
3142416OLDCHRC
Solar/Wind Harmer
0.062
3138133OCRAN
Solar/Wind Harmer
0.037
3141766HARMONY
Solar/Wind Harmer
0.012
971777AH1-397 GEN
Solar/Wind Harmer
0.163
3141843SHACKLE
Adder
0.315
3150851SPRUNCC
Adder
0.284
3143096IRON208
Adder
0.258
3142433PROV 92
Solar/Wind Harmer
0.246
3142433PROV 92
Adder
0.12
3142433PROV 92
Adder
0.12
3142543TWELFTH
Solar/Wind Harmer
0.006
944631AF1-128 GEN
Adder
29.257
316159AE1-175 C
Solar/Wind Harmer
0.053
971317AH1-138 GEN
Solar/Wind Harmer
0.454
315671AE2-027_GEN
Solar/Wind Harmer
3.891
970129AG2-093 GEN
Solar/Wind Harmer
1.729
316458AB2-190 GEN2
Solar/Wind Harmer
0.326
971069AG2-661 GEN
Solar/Wind Harmer
1.079
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971647AH1-324 GEN
Solar/Wind Harmer
2.582
961611AG1-000B GEN
Solar/Wind Harmer
3.169
3151171GRAVELC
Adder
0.642
3145336SMITFLD
Solar/Wind Harmer
0.24
316294AC1-161 GEN
Solar/Wind Harmer
1.042
3143336POWHATN
Solar/Wind Harmer
1.067
970659AG2-427 GEN
Solar/Wind Harmer
2.901
316381AD1-082 GEN
Solar/Wind Harmer
0.062
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.747
944591AF1-124 GEN
Solar/Wind Harmer
13.516
970661AG2-428 GEN
Solar/Wind Harmer
5.952
316072AD1-144
Solar/Wind Harmer
0.022
939411AE1-173 GEN
Solar/Wind Harmer
25.458
316369SG1_INVT
Solar/Wind Harmer
0.002
972265AH1-717 GEN
Adder
4.684
3151201GRAVEL4
Adder
4.391
3151191GRAVEL3
Adder
4.336
3151211GRAVEL5
Adder
4.336
3143316POE
Solar/Wind Harmer
0.238
971445AH1-216 GEN
Solar/Wind Harmer
4.236
3151081ELIZAR1
Adder
5.485
3151091ELIZAR2
Adder
5.39
3152611GOSPORTB
Adder
0.762
3152621GOSPORTC
Adder
0.647
3152601GOSPORTA
Adder
0.597
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.041
316311AC2-079 GEN
Solar/Wind Harmer
1.71
957871AF2-081 GEN
Solar/Wind Harmer
2.964
319010AE1-072 C
Solar/Wind Harmer
0.299
316305AF2-043 C
Solar/Wind Harmer
0
3146406KITTY HAWK
Solar/Wind Harmer
0.007
315835AF2-110_GEN
Solar/Wind Harmer
0.407
313526AB2-022
Solar/Wind Harmer
0.032
3146486SUNBURY
Solar/Wind Harmer
0.059
3146486SUNBURY
Solar/Wind Harmer
0.059
316321Z2-027
Solar/Wind Harmer
0.011
3146396TANGLEW
Solar/Wind Harmer
0.163
3145176PASQUOTANK
Solar/Wind Harmer
0.037
316315AB2-025 C
Solar/Wind Harmer
0.047
941031AE2-094 GEN
Solar/Wind Harmer
10.802
944011AF1-069 GEN
Solar/Wind Harmer
3.529
315814AE2-033 C
Solar/Wind Harmer
4.636
315611Z1-036_GEN2
Solar/Wind Harmer
0
970673AG2-436 GEN
Solar/Wind Harmer
12.417
970673AG2-436 GEN
Solar/Wind Harmer
8.278
3130156CHOWAN
Solar/Wind Harmer
0.058
3130156CHOWAN
Solar/Wind Harmer
0.058
971967AH1-528 GEN
Solar/Wind Harmer
9.279
315816AE2-034 GEN
Solar/Wind Harmer
0.246
972205AH1-687 GEN
Adder
2.436
3130546PLYMOUTH
Solar/Wind Harmer
0.057
315732AD1-074 GEN1
Solar/Wind Harmer
0.327
315733AD1-074 GEN2
Solar/Wind Harmer
0.327
315735AD1-075 GEN1
Solar/Wind Harmer
0.164
965291AG1-394 GEN
Solar/Wind Harmer
0.253
971845AH1-439 GEN
Solar/Wind Harmer
2.569
970285AG2-188 GEN
Solar/Wind Harmer
4.479
970085AG2-068 GEN
Solar/Wind Harmer
3.019
970581AG2-369 GEN
Solar/Wind Harmer
2.597
3146206CASHIE
Solar/Wind Harmer
0.057
970601AG2-382 GEN
Solar/Wind Harmer
2.113
3145893MURPHYS
Solar/Wind Harmer
0.153
3145893MURPHYS
Solar/Wind Harmer
0.057
3138266HYDRAULIC
Solar/Wind Harmer
0.003
3138266HYDRAULIC
Solar/Wind Harmer
0.002
960921AF2-383 GEN
Solar/Wind Helper
0.255
205943AE1-185 GEN
Solar/Wind Helper
0.354
205956AE1-196_GEN
Solar/Wind Helper
0.352
205932AD2-116_GEN
Solar/Wind Helper
0.352
959381AF2-229 GEN
Solar/Wind Helper
0.226
203975AE1-071-GEN
Solar/Wind Helper
1.507
237085AD2-009_GEN
Solar/Wind Helper
0.799
233935AB2-179 C
Solar/Wind Helper
0.72
232436AB1-176 C
Solar/Wind Helper
0.025
233923SMA
Solar/Wind Helper
0.537
233990AG1-397 GEN
Solar/Wind Helper
0.151
232432Z2-076 GEN
Solar/Wind Helper
0.038
234033AF1-007_GEN
Solar/Wind Helper
3.932
964001AG1-254 GEN
Solar/Wind Helper
0.525
219914AD2-027 C
Solar/Wind Helper
0.063
227927V4-067C
Solar/Wind Helper
0.006
228754AB1-001 C
Solar/Wind Helper
0.014
219272CLEANLIGHT C
Solar/Wind Helper
0.014
219688LUMSOLAR_S C
Solar/Wind Helper
0.022
219607WPEMNERT C
Solar/Wind Helper
0.044
214067T20SOLAR
Solar/Wind Helper
0.006
20715728PEM_W1-119
Solar/Wind Helper
0.052
20715828PEM_W1-120
Solar/Wind Helper
0.052
207459AE1-142 C O1
Solar/Wind Helper
0.157
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.046
218526CNTRALGAS2 C
Solar/Wind Helper
0.086
218524CNTRALGAS1 C
Solar/Wind Helper
0.086
966261AG1-495 GEN
Solar/Wind Helper
0.043
207530AG1-191 GEN
Solar/Wind Helper
0.035
20675928HOL_W4-097
Solar/Wind Helper
0.026
20676328BVR_Y1-020
Solar/Wind Helper
0.014
207484AF2-139 C O1
Solar/Wind Helper
0.044
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.044
20675728RH_W2-091
Solar/Wind Helper
0.072
20675128HRM_W1-127
Solar/Wind Helper
0.016
209116AE2-175 GEN
Solar/Wind Helper
0.921
961261AF2-417 GEN
Solar/Wind Helper
0.221
972289AH1-729 GEN
50/50
12.961
315651AD1-115 GEN
Solar/Wind Harmer
0.002
316447AC1-158 HLD
Solar/Wind Harmer
0.794
3150071POSSM 5
Adder
31.816
3150181POSSMC2
Adder
0.702
3150181POSSMC2
Adder
0.696
3150181POSSMC2
Adder
0.696
966001AG1-469 GEN
Solar/Wind Harmer
0.04
3151731LOISA B
Adder
4.435
3151721LOISA A
Adder
4.412
3150391LDYSMT3
Adder
8.836
972195AH1-682 GEN
Adder
1.161
315673AE1-157 GEN
Solar/Wind Harmer
4.506
957411AF2-035 GEN
Solar/Wind Harmer
2.759
970317AG2-208 GEN
Solar/Wind Harmer
2.556
316468AD1-105 GEN
Solar/Wind Harmer
-0.021
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.656
3150341NORNECKC1
Adder
0.651
966871AG1-558 GEN
Solar/Wind Harmer
0.072
958261AF2-120 GEN
Solar/Wind Harmer
2.062
3142296MT RD221
Adder
0.198
971223AH1-071 GEN
Solar/Wind Harmer
0.661
3143526WINTERP
Solar/Wind Harmer
0.322
3142366NRTHEST
Adder
0.202
3150691DARBY 3
Adder
4.444
3150701DARBY 4
Adder
4.434
3150681DARBY 2
Adder
4.428
3150671DARBY 1
Adder
4.423
316075AC2-137 C
Solar/Wind Harmer
0.017
3142946ENON
Solar/Wind Harmer
0.006
944641AF1-129 GEN
Adder
29.055
316240AF1-291 C
Solar/Wind Harmer
0
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.068
316236AE1-162_GEN
Solar/Wind Harmer
0
970657AG2-426 GEN
Solar/Wind Harmer
2.098
970657AG2-426 GEN
Solar/Wind Harmer
0.44
316036AC1-147 C
Solar/Wind Harmer
0.011
3150991CHESPKB
Adder
0.627
3150991CHESPKB
Adder
0.612
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.057
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3145506HICKORY
Solar/Wind Harmer
0.239
3145506HICKORY
Solar/Wind Harmer
0.143
3145506HICKORY
Solar/Wind Harmer
0.036
316339AD2-160 GEN
Solar/Wind Harmer
0.097
316018AA1-139 ULT2
Solar/Wind Harmer
0.001
316017AA1-139 ULT1
Solar/Wind Harmer
0.033
3137176SLIGO L2192
Solar/Wind Harmer
0.237
3146456SLIGO L269
Solar/Wind Harmer
1.052
3130086AYDLETT
Solar/Wind Harmer
0.238
3146386ELIZ CT
Solar/Wind Harmer
0.059
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.059
3146516WINFALL
Solar/Wind Harmer
0.059
3146516WINFALL
Solar/Wind Harmer
0.059
3144356SAPONY
Solar/Wind Harmer
0.491
3146626S HERTFORD
Solar/Wind Harmer
0.059
3146626S HERTFORD
Solar/Wind Harmer
0.059
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.258
3146376EDENTON
Solar/Wind Harmer
0.258
972185AH1-677 GEN
Adder
3.254
971761AH1-387 GEN
Solar/Wind Harmer
1.133
972187AH1-678 GEN
Adder
1.643
970933AG2-581 GEN
Solar/Wind Harmer
4.601
316065AD1-022 GEN
Solar/Wind Harmer
2.61
3146776BUCKING
Solar/Wind Harmer
0.227
3146776BUCKING
Solar/Wind Harmer
0.018
3145893MURPHYS
Solar/Wind Harmer
0.379
3145893MURPHYS
Solar/Wind Harmer
0.102
3146173TUNIS
Solar/Wind Harmer
0.056
3146173TUNIS
Solar/Wind Harmer
0.056
970301AG2-198 GEN
Solar/Wind Harmer
2.401
237025AB1-124 C
Solar/Wind Helper
0.177
237006AB1-125 GEN
Solar/Wind Helper
0.132
23777801MSM_W1-116
Solar/Wind Helper
0.118
237034AC2-136 C
Solar/Wind Helper
0.179
205916AD1-020 GEN
Solar/Wind Helper
1.359
226929AD2-058 GEN
Solar/Wind Helper
0.07
208835TUHI V3-051
Solar/Wind Helper
0.018
208835TUHI V3-051
Solar/Wind Helper
0.018
237001AB1-127_GEN
Solar/Wind Helper
0.259
237002AB1-128_GEN
Solar/Wind Helper
0.251
20390526W1-045 C
Solar/Wind Helper
0.222
235063AE1-101 C2
Solar/Wind Helper
0.889
23777901MDS_W4-102
Solar/Wind Helper
0.085
233933AB2-153 GEN
Solar/Wind Helper
0.131
233944AB2-135 GEN
Solar/Wind Helper
0.332
232424Y1-079 C
Solar/Wind Helper
0.065
233987AB2-037 GEN
Solar/Wind Helper
1.314
234036AF2-325 C
Solar/Wind Helper
0.024
233946AB2-136 GEN
Solar/Wind Helper
0.319
233901CHERRYDALE C
Solar/Wind Helper
0.13
232408W1-005 C
Solar/Wind Helper
0.284
232410W1-006 C
Solar/Wind Helper
0.284
233939AC1-091 C
Solar/Wind Helper
0.196
233970AC1-092 C
Solar/Wind Helper
0.196
230433AD2-135 GEN
Solar/Wind Helper
0.009
230407AD2-065 C
Solar/Wind Helper
0.022
219921AF1-264
Solar/Wind Helper
0.028
940641AE2-051 GEN
Solar/Wind Harmer
4.772
316388AE2-253 GEN
Solar/Wind Harmer
0.187
316336AC2-165 C
Solar/Wind Harmer
0.002
3146456SLIGO L269
Solar/Wind Harmer
0.059
316246AF1-032 C
Solar/Wind Harmer
0.027
316093AE2-104_GEN
Solar/Wind Harmer
0.998
3146516WINFALL
Solar/Wind Harmer
0.19
3146516WINFALL
Solar/Wind Harmer
0.059
315800Z1-036_GEN1
Solar/Wind Harmer
0
970937AG2-583 GEN
Solar/Wind Harmer
3.567
3130156CHOWAN
Solar/Wind Harmer
0.058
3145663CRESWEL
Solar/Wind Harmer
0.161
971163AH1-040 GEN
Solar/Wind Harmer
4.594
972003AH1-546 GEN
Solar/Wind Harmer
2.42
970919AG2-571 GEN
Solar/Wind Harmer
2.017
316322AB2-045
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.023
316023GEN1_S
Solar/Wind Harmer
0.127
970087AG2-069 GEN
Solar/Wind Harmer
4.529
3146206CASHIE
Solar/Wind Harmer
0.057
971547AH1-271 GEN
Solar/Wind Harmer
1.207
3145893MURPHYS
Solar/Wind Harmer
0.226
3145893MURPHYS
Solar/Wind Harmer
0.251
3146926FARMVIL
Solar/Wind Harmer
0.034
3146173TUNIS
Solar/Wind Harmer
0.056
23779801AA1-109
Solar/Wind Helper
0.196
223401AF1-299 GEN
Solar/Wind Helper
0.351
966131AG1-482 GEN
Solar/Wind Helper
0.102
237080AD1-060 GEN
Solar/Wind Helper
0.184
235062AE1-101 C1
Solar/Wind Helper
0.889
237038AE2-054 C
Solar/Wind Helper
0.144
233930AB2-032 GEN
Solar/Wind Helper
0.215
233915AB1-141 GEN
Solar/Wind Helper
0.283
232422X3-066 FULL
Solar/Wind Helper
0.064
233964AF2-378 GEN
Solar/Wind Helper
0.023
232426Y1-080 FULL
Solar/Wind Helper
0.022
232428Y3-058 C
Solar/Wind Helper
0.19
233998TM1NIN_3.36
Solar/Wind Helper
0.146
233954AC2-188 GEN
Solar/Wind Helper
0.13
232404W1-003 C
Solar/Wind Helper
0.284
233950AC2-186 GEN
Solar/Wind Helper
0.065
232434Z2-077 GEN
Solar/Wind Helper
0.071
233972AC1-094 C
Solar/Wind Helper
0.169
205941AD2-115 GEN
Solar/Wind Helper
0.276
230511AF1-262
Solar/Wind Helper
0.008
230434AG1-499 GEN
Solar/Wind Helper
0.126
228728W1-130C
Solar/Wind Helper
0.03
219258KINSLEYDEP C
Solar/Wind Helper
0.042
219904AC1-010 C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.019
218660EHAMPSOLAR C
Solar/Wind Helper
0.018
219686LUMSOLAR_N C
Solar/Wind Helper
0.022
219304NAMERICA C
Solar/Wind Helper
0.072
20720728JCB_W1-129
Solar/Wind Helper
0.031
207445AB1-138_GEN
Solar/Wind Helper
0.056
963711AG1-223 GEN
Solar/Wind Helper
0.035
20714828MDF_W3-079
Solar/Wind Helper
0.07
219680HOPEWELLV C1
Solar/Wind Helper
0.002
207454AA2-184 E
Solar/Wind Helper
0.166
20715228NPK_W1-113
Solar/Wind Helper
0.042
20742028HF_AC1-207
Solar/Wind Helper
0.075
218428ETC SOLAR C
Solar/Wind Helper
0.003
207528AF2-192 GEN
Solar/Wind Helper
0.04
20673628F1S_V4-069
Solar/Wind Helper
0.016
20675428EAM_W2-061
Solar/Wind Helper
0.008
217213AMBOY SO C
Solar/Wind Helper
0.015
20676428JCR_X2-075
Solar/Wind Helper
0.036
217209CENTRL HS C
Solar/Wind Helper
0.004
217208PARK ELE C
Solar/Wind Helper
0.002
20674328GAR_V4-001
Solar/Wind Helper
0.012
207439AE1-081 C O1
Solar/Wind Helper
0.01
207437AD2-070 GEN
Solar/Wind Helper
0.073
207518AF1-320_GEN
Solar/Wind Helper
0.827
20671928W4-073
Solar/Wind Helper
0.047
20675828AU_W4-064
Solar/Wind Helper
0.015
961301AF2-421 GEN
Solar/Wind Helper
0.221
963151AG1-164 GEN
Solar/Wind Helper
0.221
3141906WESTMOR
Solar/Wind Harmer
0.025
3150351NORNECKC2
Adder
0.635
316473AC1-191 GEN
Solar/Wind Harmer
0.211
316404AE1-155 C
Solar/Wind Harmer
0.014
970009AG2-005 GEN
Solar/Wind Harmer
0.464
962971AG1-146 GEN
Solar/Wind Harmer
0.993
3142416OLDCHRC
Solar/Wind Harmer
0.6
970293AG2-193 GEN
Solar/Wind Harmer
0.658
3141766HARMONY
Solar/Wind Harmer
0.822
316203AE2-005 GEN
Solar/Wind Harmer
0
316280AD1-041 GEN
Solar/Wind Harmer
0.001
316156AD2-030 GEN
Solar/Wind Harmer
0.046
3141873WAN 176
Solar/Wind Harmer
1.096
3141843SHACKLE
Adder
0.315
3150861SPRUNCD
Adder
0.284
3143096IRON208
Adder
0.258
3143096IRON208
Adder
0.253
3142433PROV 92
Adder
0.12
3142433PROV 92
Adder
0.12
3142946ENON
Solar/Wind Harmer
0.021
316382AG1-145 C
Solar/Wind Harmer
0
970133AG2-095 GEN
Solar/Wind Harmer
0.585
970129AG2-093 GEN
Solar/Wind Harmer
3.674
965281AG1-393 GEN
Solar/Wind Harmer
0.648
315778AD1-151 GEN
Solar/Wind Harmer
4.854
3150921YORKTN3
Adder
1.524
315839AE2-212 C
Solar/Wind Harmer
0
3144216WINCHST
Adder
0.228
961611AG1-000B GEN
Solar/Wind Harmer
1.611
3151221GRAVEL6
Adder
4.386
3151171GRAVELC
Adder
0.844
315813AE1-149 C
Solar/Wind Harmer
3.21
3145336SMITFLD
Solar/Wind Harmer
0.024
315773AC2-141 GEN
Solar/Wind Harmer
2.196
316313AB2-026
Solar/Wind Harmer
0.038
316258AE1-075 C
Solar/Wind Harmer
0.045
316405AF2-144 C
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
0.907
970659AG2-427 GEN
Solar/Wind Harmer
0.635
316083AB2-161 GEN
Solar/Wind Harmer
0.001
3144536CHRHLND
Solar/Wind Harmer
0.009
3151101ELIZAR3
Adder
5.556
3144873MCLAUGH
Solar/Wind Harmer
0.001
944581AF1-123 GEN
Solar/Wind Harmer
13.468
944601AF1-125 GEN
Solar/Wind Harmer
13.26
970661AG2-428 GEN
Solar/Wind Harmer
1.266
3146456SLIGO L269
Solar/Wind Harmer
0.059
971153AH1-033 GEN
Solar/Wind Harmer
0.687
316320Y1-086
Solar/Wind Harmer
0
316435W1029_GEN3
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.059
3146626S HERTFORD
Solar/Wind Harmer
0.059
3145273HOLLAND
Solar/Wind Harmer
0.044
3146376EDENTON
Solar/Wind Harmer
0.058
315614AA2-178 GEN
Solar/Wind Harmer
0.329
3156081AA2-088 GEN
Solar/Wind Harmer
0.001
971157AH1-035 GEN
Solar/Wind Harmer
0.683
315737AD1-076 GEN
Solar/Wind Harmer
0.732
970917AG2-570 GEN
Solar/Wind Harmer
5.042
3146776BUCKING
Solar/Wind Harmer
0.02
316365GEN2_N
Solar/Wind Harmer
0.127
3146206CASHIE
Solar/Wind Harmer
0.057
3145893MURPHYS
Solar/Wind Harmer
0.095
3145893MURPHYS
Solar/Wind Harmer
0.057
957521AF2-046 GEN
Solar/Wind Harmer
4.204
961681AG1-008 GEN
Solar/Wind Harmer
4.204
3146926FARMVIL
Solar/Wind Harmer
0.034
3146173TUNIS
Solar/Wind Harmer
0.056
970909AG2-566 GEN
Solar/Wind Harmer
0.6
237030AB1-096 C
Solar/Wind Helper
0.076
223402AF1-300 C
Solar/Wind Helper
0.351
226910AB2-157 C
Solar/Wind Helper
0.013
227287AC2-120 GEN
Solar/Wind Helper
0.279
205917AD1-020 ES
Solar/Wind Helper
0.292
238221AF1-254 C O1
Solar/Wind Helper
0.149
235067AD1-061 GEN
Solar/Wind Helper
0.259
233982AB2-133 GEN
Solar/Wind Helper
0.202
233918AB1-142 GEN
Solar/Wind Helper
0.283
233994AC2-023 GEN
Solar/Wind Helper
0.539
233996TM1833_GEN
Solar/Wind Helper
0.146
233997TMININ_4.2
Solar/Wind Helper
0.146
233940AF2-379 C
Solar/Wind Helper
0.035
234015AF2-250 C
Solar/Wind Helper
0.021
233952AC2-187 GEN
Solar/Wind Helper
0.13
232406W1-004 FULL
Solar/Wind Helper
0.284
233971AC1-093 C
Solar/Wind Helper
0.2
230430AE1-229_GEN
Solar/Wind Helper
1.854
230415AB2-049 C
Solar/Wind Helper
0.017
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.03
219912AD2-042 GEN
Solar/Wind Helper
0.082
228729W2-030 C
Solar/Wind Helper
0.061
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.006
219906AC1-017 C
Solar/Wind Helper
0.023
219348LDSOLAR C
Solar/Wind Helper
0.062
959561AF2-247 GEN
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.034
20716028EGP_W2-019
Solar/Wind Helper
0.01
20715028HAN_X4-015
Solar/Wind Helper
0.031
219276PARKLANDSO C
Solar/Wind Helper
0.048
20714528FRN_Y2-051
Solar/Wind Helper
0.031
20720528MAN_W1-024
Solar/Wind Helper
0.015
219612MATRIX C
Solar/Wind Helper
0.013
218438BLK ROCK C
Solar/Wind Helper
0.015
219908AB1-139 C
Solar/Wind Helper
0.039
219919AE1-041 FULL
Solar/Wind Helper
0.002
20673728F2S_V4-070
Solar/Wind Helper
0.016
219249CENTRALDIV C
Solar/Wind Helper
0.005
217211CAMDEN ST C
Solar/Wind Helper
0.002
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.016
207510AF2-138 C
Solar/Wind Helper
0.043
20674628WNG_W3-110
Solar/Wind Helper
0.047
963161AG1-165 GEN
Solar/Wind Helper
0.221
219615MILLCREEK C
Solar/Wind Helper
0.014
963401AG1-189 GEN
Solar/Wind Helper
0.03
963391AG1-188 GEN
Solar/Wind Helper
0.044
20714928UPF_X1-085
Solar/Wind Helper
0.003
20720628TIN_W1-124
Solar/Wind Helper
0.102
235020AA1-095 C
Solar/Wind Helper
0.023
20716928W4-060COL
Solar/Wind Helper
0.028
20673828FLE_V3-070
Solar/Wind Helper
0.048
218440SUMMTASSOC C
Solar/Wind Helper
0.009
207442AE1-156 GEN
Solar/Wind Helper
0.174
20676128MHD_W3-029
Solar/Wind Helper
0.051
20671828STAW2-080
Solar/Wind Helper
0.014
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.003
217204WCALDSOLAR C
Solar/Wind Helper
0.002
207471AF2-354 C
Solar/Wind Helper
0.089
20674928WA_W3-044
Solar/Wind Helper
0.052
964851AG1-348 GEN
Solar/Wind Helper
0.043
20676228FRD_X1-012
Solar/Wind Helper
0.048
20674128FR_U2-059
Solar/Wind Helper
0.002
966111AG1-480 GEN
Solar/Wind Helper
0.039
211065PSPA IPP
Solar/Wind Helper
0.078
211065PSPA IPP
Solar/Wind Helper
0.078
LAGNLTFEXP_LAGN->PJM
CLTF
5.367
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.069
TVALTFEXP_TVA->PJM
CLTF
2.703
NYPJM->LTFIMP_NY
CLTF
2.351
LGEELTFEXP_LGEE->PJM
CLTF
1.596
WECLTFEXP_WEC->PJM
CLTF
0.855
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.688
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.895
MECLTFEXP_MEC->PJM
CLTF
3.911
SIGELTFEXP_SIGE->PJM
CLTF
0.123
CPLELTFEXP_CPLE->PJM
CLTF
3.974
CBM West 2LTFEXP_CBM-W2->PJM
CBM
33.607

Details for 6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.62 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:637.96
MW Contribution:7.21
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
3.01
970575AG2-366 GEN
50/50
3.666
315749AE2-041 GEN
50/50
4.959
3141843SHACKLE
50/50
0.748
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150921YORKTN3
50/50
1.939
3144216WINCHST
50/50
0.281
3151161SURRY 1
50/50
2.18
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.64
962971AG1-146 GEN
Solar/Wind Harmer
3.3
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.617
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.86
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.672
3142416OLDCHRC
Solar/Wind Harmer
0.558
3151221GRAVEL6
Adder
4.126
3151171GRAVELC
Adder
0.794
961611AG1-000B GEN
Solar/Wind Harmer
1.508
3150341NORNECKC1
50/50
3.109
3150341NORNECKC1
50/50
3.084
963611AG1-210 GEN
50/50
0.995
3150621CHESTS7
50/50
0.185
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
7.975
316075AC2-137 C
Solar/Wind Harmer
0.02
3142946ENON
Solar/Wind Harmer
0.007
316033AB2-134 GEN
Solar/Wind Harmer
0.003
315697AD1-025 GEN
Solar/Wind Harmer
0.063
3150351NORNECKC2
50/50
2.96
966661AG1-536 GEN
50/50
6.86
3141843SHACKLE
50/50
0.748
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
971353AH1-157 GEN
50/50
7.442
970017AG2-010 GEN
50/50
4.725
3150641CHESTS8
50/50
0.204
944631AF1-128 GEN
50/50
32.114
316337AD2-073 GEN
Solar/Wind Harmer
0.299
3141726DUNNSVL
Solar/Wind Harmer
1.045
962861AG1-135 GEN
Solar/Wind Harmer
7.535
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.364
3142433PROV 92
Solar/Wind Harmer
0.43
971317AH1-138 GEN
Solar/Wind Harmer
0.616
316159AE1-175 C
Solar/Wind Harmer
0.065
3138126ROCKLANDING
Solar/Wind Harmer
0.033
3142416OLDCHRC
Solar/Wind Harmer
0.15
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.604
961611AG1-000B GEN
Solar/Wind Harmer
2.967
971647AH1-324 GEN
Solar/Wind Harmer
2.407
315759AF1-018 GEN
50/50
4.959
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150611CHESTG7
50/50
0.403
3150631CHESTG8
50/50
0.397
971047AG2-646 GEN
50/50
11.288
972263AH1-716 GEN
50/50
33.088
316223AC1-118
Solar/Wind Harmer
0.296
3141813NORNECK
Solar/Wind Harmer
0.28
970327AG2-215 GEN
Solar/Wind Harmer
7.206
962981AG1-147 GEN
Solar/Wind Harmer
7.699
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
0.029
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.092
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
9.155
315976AC1-164 GENA
Solar/Wind Harmer
8.33
316169AC1-164_GENC
Solar/Wind Harmer
7.197
315975AC1-164 GENB
Solar/Wind Harmer
0.246
316312AB1-027
Solar/Wind Harmer
0.103
972265AH1-717 GEN
Adder
4.406
3151201GRAVEL4
Adder
4.131
3151191GRAVEL3
Adder
4.078
3151211GRAVEL5
Adder
4.078
316369SG1_INVT
Solar/Wind Harmer
0.002
3141426STAFORD
Solar/Wind Helper
0.031
LAGNLTFEXP_LAGN->PJM
CLTF
1.541
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.475
TVALTFEXP_TVA->PJM
CLTF
0.778
NYPJM->LTFIMP_NY
CLTF
0.546
LGEELTFEXP_LGEE->PJM
CLTF
0.294
WECLTFEXP_WEC->PJM
CLTF
0.148
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.13
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.686
MECLTFEXP_MEC->PJM
CLTF
0.78
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CPLELTFEXP_CPLE->PJM
CLTF
2.028
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.282

Details for 8BRAMBLETON-AH1-727 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 9344_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8BRAMBLETON-AH1-727 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 9344_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.63 %
Rating:3256.16 MVA
Rating Type:B
MVA to Mitigate:3472.07
MW Contribution:6.95
Bus #Bus NameTypeMW Contribution
316164AC1-076 GEN
Solar/Wind Harmer
0.382
3150411LDYSMT5
Adder
31.941
3150381LDYSMT2
Adder
30.569
972213AH1-691 GEN
Adder
5.171
972215AH1-692 GEN
Adder
5.171
3147346CASHSCORNER
Solar/Wind Harmer
0.532
3141426STAFORD
Solar/Wind Harmer
0.05
972189AH1-679 GEN
Adder
3.695
944491AF1-114 GEN
Solar/Wind Harmer
0.001
316223AC1-118
Solar/Wind Harmer
0.155
316312AB1-027
Solar/Wind Harmer
0.381
3141813NORNECK
Solar/Wind Harmer
0.213
316233AE1-074 FULL
Solar/Wind Harmer
0.17
971281AH1-106 GEN
Solar/Wind Harmer
2.946
971283AH1-107 GEN
Solar/Wind Harmer
2.946
970053AG2-049 GEN
Adder
3.548
970327AG2-215 GEN
Solar/Wind Harmer
6.945
962981AG1-147 GEN
Solar/Wind Harmer
7.889
971285AH1-108 GEN
Adder
1.591
3141783LANCAST
Solar/Wind Harmer
0.126
3141783LANCAST
Solar/Wind Harmer
0.084
315976AC1-164 GENA
Solar/Wind Harmer
21.836
316169AC1-164_GENC
Solar/Wind Harmer
18.864
315975AC1-164 GENB
Solar/Wind Harmer
0.646
3138133OCRAN
Solar/Wind Harmer
0.063
316314AB2-024 C
Solar/Wind Harmer
0.001
971255AH1-087 GEN
50/50
5.432
971259AH1-089 GEN
50/50
5.432
3150281M RUN A
50/50
43.576
3150221REMNGT2
50/50
40.487
972201AH1-685 GEN
50/50
6.985
3150211REMNGT1
Adder
37.902
316006AB2-029 C
Solar/Wind Harmer
0.002
971685AH1-345 GEN
Solar/Wind Harmer
2.219
316045AC1-158 PL2
Solar/Wind Harmer
4.376
316447AC1-158 HLD
Solar/Wind Harmer
3.008
315651AD1-115 GEN
Solar/Wind Harmer
0.009
966001AG1-469 GEN
Solar/Wind Harmer
0.139
3150391LDYSMT3
Adder
31.782
972195AH1-682 GEN
Adder
4.177
3151731LOISA B
Adder
15.317
3151721LOISA A
Adder
15.238
315673AE1-157 GEN
Solar/Wind Harmer
16.074
957411AF2-035 GEN
Solar/Wind Harmer
9.794
970317AG2-208 GEN
Solar/Wind Harmer
9.074
3150071POSSM 5
Adder
101.873
3150181POSSMC2
Adder
2.248
3150181POSSMC2
Adder
2.229
3150181POSSMC2
Adder
2.229
316468AD1-105 GEN
Solar/Wind Harmer
-0.071
966871AG1-558 GEN
Solar/Wind Harmer
0.248
3142296MT RD221
Adder
0.683
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.231
3150341NORNECKC1
Adder
2.213
971223AH1-071 GEN
Solar/Wind Harmer
2.268
3143526WINTERP
Solar/Wind Harmer
1.104
3142366NRTHEST
Adder
0.693
958261AF2-120 GEN
Solar/Wind Harmer
7.015
3150691DARBY 3
Adder
15.26
3150701DARBY 4
Adder
15.225
3150681DARBY 2
Adder
15.207
3150671DARBY 1
Adder
15.189
316075AC2-137 C
Solar/Wind Harmer
0.058
3142946ENON
Solar/Wind Harmer
0.021
944641AF1-129 GEN
Adder
98.867
316240AF1-291 C
Solar/Wind Harmer
0.002
316033AB2-134 GEN
Solar/Wind Harmer
0.012
315697AD1-025 GEN
Solar/Wind Harmer
0.231
316236AE1-162_GEN
Solar/Wind Harmer
0.002
970657AG2-426 GEN
Solar/Wind Harmer
7.052
970657AG2-426 GEN
Solar/Wind Harmer
1.478
316036AC1-147 C
Solar/Wind Harmer
0.037
3150991CHESPKB
Adder
2.106
3150991CHESPKB
Adder
2.056
316316AC1-027 C
Solar/Wind Harmer
0.193
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.006
3145506HICKORY
Solar/Wind Harmer
0.8
3145506HICKORY
Solar/Wind Harmer
0.48
3145506HICKORY
Solar/Wind Harmer
0.12
316339AD2-160 GEN
Solar/Wind Harmer
0.323
316018AA1-139 ULT2
Solar/Wind Harmer
0.005
316017AA1-139 ULT1
Solar/Wind Harmer
0.111
3137176SLIGO L2192
Solar/Wind Harmer
0.792
3146456SLIGO L269
Solar/Wind Harmer
3.521
3130086AYDLETT
Solar/Wind Harmer
0.795
3146386ELIZ CT
Solar/Wind Harmer
0.197
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.195
3146516WINFALL
Solar/Wind Harmer
0.195
3146516WINFALL
Solar/Wind Harmer
0.195
3144356SAPONY
Solar/Wind Harmer
1.625
3146626S HERTFORD
Solar/Wind Harmer
0.194
3146626S HERTFORD
Solar/Wind Harmer
0.194
315742AE1-103 GEN
Solar/Wind Harmer
0.002
3146376EDENTON
Solar/Wind Harmer
0.847
3146376EDENTON
Solar/Wind Harmer
0.847
972185AH1-677 GEN
Adder
10.672
972187AH1-678 GEN
Adder
5.366
970933AG2-581 GEN
Solar/Wind Harmer
14.962
316065AD1-022 GEN
Solar/Wind Harmer
8.417
3145893MURPHYS
Solar/Wind Harmer
1.217
3145893MURPHYS
Solar/Wind Harmer
0.327
3146173TUNIS
Solar/Wind Harmer
0.18
3146173TUNIS
Solar/Wind Harmer
0.18
970099AG2-077 GEN
Solar/Wind Harmer
19.085
316181AB2-040 GEN
Solar/Wind Harmer
0.257
971741AH1-377 GEN
Solar/Wind Harmer
17.523
3142666NORTHAMPTON
Solar/Wind Harmer
0.176
3142666NORTHAMPTON
Solar/Wind Harmer
0.176
3142666NORTHAMPTON
Solar/Wind Harmer
0.176
3142666NORTHAMPTON
Solar/Wind Harmer
0.106
970301AG2-198 GEN
Solar/Wind Harmer
7.522
316426AA2-053 GEN
Solar/Wind Harmer
0.594
3145593CAROLNA
Solar/Wind Harmer
0.175
3145593CAROLNA
Solar/Wind Harmer
0.175
966811AG1-552 GEN
Solar/Wind Harmer
1.903
3145593CAROLNA
Solar/Wind Harmer
0.218
3146776BUCKING
Solar/Wind Harmer
0.699
3146776BUCKING
Solar/Wind Harmer
0.057
3145783HORNRTN
Solar/Wind Harmer
3.102
3145783HORNRTN
Solar/Wind Harmer
2.482
3145783HORNRTN
Solar/Wind Harmer
0.776
3145783HORNRTN
Solar/Wind Harmer
0.31
3145796HORNRTN
Solar/Wind Harmer
0.521
3147133PAMPLIN
Solar/Wind Harmer
0.172
3147133PAMPLIN
Solar/Wind Harmer
0.137
958211AF2-115 GEN
Solar/Wind Harmer
2.054
963191AG1-168 GEN
Solar/Wind Harmer
0.685
3144293JTRSVLE
Adder
0.545
3144293JTRSVLE
Adder
0.459
3145933PARMELE
Solar/Wind Harmer
0.34
3145933PARMELE
Solar/Wind Harmer
0.17
316274AC1-208 GEN
Solar/Wind Harmer
0.88
316034AC1-036 C
Solar/Wind Harmer
0.012
970323AG2-213 GEN
Solar/Wind Harmer
7.229
971775AH1-396 GEN
Solar/Wind Harmer
0.271
971489AH1-241 GEN
Solar/Wind Harmer
8.948
313527AB2-043 GEN
Solar/Wind Harmer
0.002
939181AE1-148 GEN
Solar/Wind Harmer
8.005
3145493TOT1
Solar/Wind Harmer
0.377
3145453TOT5
Solar/Wind Harmer
0.226
3145603CNETO
Solar/Wind Harmer
0.151
962561AG1-105 GEN
Solar/Wind Harmer
7.712
961601AG1-000A GEN
Solar/Wind Harmer
2.849
316263AC1-034 GEN
Solar/Wind Harmer
6.088
964791AG1-342 GEN
Solar/Wind Harmer
3.061
3146843MT LREL
Solar/Wind Harmer
0.159
3146843MT LREL
Solar/Wind Harmer
0.159
315821AE2-092 GEN
Solar/Wind Harmer
0.01
971761AH1-387 GEN
Solar/Wind Harmer
2.843
316222AC1-221 GEN
Solar/Wind Harmer
0.583
942751AE2-291 GEN
Solar/Wind Harmer
6.934
3132123MT JACKSON
Solar/Wind Harmer
0.381
970117AG2-086 GEN
Solar/Wind Harmer
2.919
970117AG2-086 GEN
Solar/Wind Harmer
1.946
235020AA1-095 C
Solar/Wind Helper
0.059
23777901MDS_W4-102
Solar/Wind Helper
0.197
237034AC2-136 C
Solar/Wind Helper
0.259
23777801MSM_W1-116
Solar/Wind Helper
0.131
237001AB1-127_GEN
Solar/Wind Helper
0.481
237025AB1-124 C
Solar/Wind Helper
0.187
237006AB1-125 GEN
Solar/Wind Helper
0.14
237002AB1-128_GEN
Solar/Wind Helper
0.48
235063AE1-101 C2
Solar/Wind Helper
1.773
20390526W1-045 C
Solar/Wind Helper
0.368
205916AD1-020 GEN
Solar/Wind Helper
1.767
233987AB2-037 GEN
Solar/Wind Helper
2.414
233901CHERRYDALE C
Solar/Wind Helper
0.239
233939AC1-091 C
Solar/Wind Helper
0.361
233970AC1-092 C
Solar/Wind Helper
0.361
232408W1-005 C
Solar/Wind Helper
0.523
232410W1-006 C
Solar/Wind Helper
0.523
233946AB2-136 GEN
Solar/Wind Helper
0.585
234036AF2-325 C
Solar/Wind Helper
0.043
232424Y1-079 C
Solar/Wind Helper
0.12
233944AB2-135 GEN
Solar/Wind Helper
0.605
233933AB2-153 GEN
Solar/Wind Helper
0.239
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.041
219921AF1-264
Solar/Wind Helper
0.052
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.057
963391AG1-188 GEN
Solar/Wind Helper
0.084
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.192
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.017
20673828FLE_V3-070
Solar/Wind Helper
0.092
207442AE1-156 GEN
Solar/Wind Helper
0.329
20676128MHD_W3-029
Solar/Wind Helper
0.097
217081WEATEXAS C
Solar/Wind Helper
0.013
20671828STAW2-080
Solar/Wind Helper
0.027
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
20676228FRD_X1-012
Solar/Wind Helper
0.092
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.099
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.074
211065PSPA IPP
Solar/Wind Helper
0.151
211065PSPA IPP
Solar/Wind Helper
0.151
971253AH1-086 GEN
50/50
24.442
971257AH1-088 GEN
50/50
5.432
3150301M RUN C
50/50
43.549
3150291M RUN B
50/50
43.226
3150231REMNGT3
50/50
43.711
3150241REMNGT4
50/50
40.756
972217AH1-693 GEN
50/50
5.373
972199AH1-684 GEN
Adder
5.823
3141196NOKESVL
Solar/Wind Harmer
1.195
316044AC1-158 PL1
Solar/Wind Harmer
1.369
316450AC1-158 RIC
Solar/Wind Harmer
0.365
316170AC1-121 GEN2
Solar/Wind Harmer
0.291
3132273ORANGE
Solar/Wind Harmer
0.051
3147666LOUISA
Solar/Wind Harmer
0.563
3150401LDYSMT4
Adder
31.841
3150371LDYSMT1
Adder
30.767
3151761LOISA E
Adder
31.228
972183AH1-676 GEN
Adder
251.695
3150331BIRCHWDA
Adder
38.122
3150151POSSMC1
Adder
2.229
3150151POSSMC1
Adder
2.229
3141316ARNOLDS
Adder
0.53
971781AH1-399 GEN
Solar/Wind Harmer
0.287
970737AG2-469 GEN
Solar/Wind Harmer
9.258
3141906WESTMOR
Solar/Wind Harmer
0.086
316473AC1-191 GEN
Solar/Wind Harmer
0.726
3142416OLDCHRC
Solar/Wind Harmer
2.065
3150351NORNECKC2
Adder
2.16
316404AE1-155 C
Solar/Wind Harmer
0.048
970293AG2-193 GEN
Solar/Wind Harmer
2.259
970009AG2-005 GEN
Solar/Wind Harmer
1.58
962971AG1-146 GEN
Solar/Wind Harmer
3.381
3150861SPRUNCD
Adder
0.972
3143096IRON208
Adder
0.883
3143096IRON208
Adder
0.866
3141766HARMONY
Solar/Wind Harmer
2.802
3142433PROV 92
Adder
0.408
3142433PROV 92
Adder
0.408
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141843SHACKLE
Adder
1.073
3142946ENON
Solar/Wind Harmer
0.07
316280AD1-041 GEN
Solar/Wind Harmer
0.004
316156AD2-030 GEN
Solar/Wind Harmer
0.155
3141873WAN 176
Solar/Wind Harmer
3.731
316382AG1-145 C
Solar/Wind Harmer
0.002
970133AG2-095 GEN
Solar/Wind Harmer
1.99
970129AG2-093 GEN
Solar/Wind Harmer
12.476
965281AG1-393 GEN
Solar/Wind Harmer
2.197
315778AD1-151 GEN
Solar/Wind Harmer
16.459
3150921YORKTN3
Adder
5.164
315839AE2-212 C
Solar/Wind Harmer
0.002
3144216WINCHST
Adder
0.774
961611AG1-000B GEN
Solar/Wind Harmer
5.45
3151221GRAVEL6
Adder
14.814
3151171GRAVELC
Adder
2.85
315813AE1-149 C
Solar/Wind Harmer
10.825
3145336SMITFLD
Solar/Wind Harmer
0.081
315773AC2-141 GEN
Solar/Wind Harmer
7.404
970659AG2-427 GEN
Solar/Wind Harmer
2.135
3144536CHRHLND
Solar/Wind Harmer
0.03
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3151101ELIZAR3
Adder
18.67
3144873MCLAUGH
Solar/Wind Harmer
0.005
944581AF1-123 GEN
Solar/Wind Harmer
45.254
944601AF1-125 GEN
Solar/Wind Harmer
44.557
970661AG2-428 GEN
Solar/Wind Harmer
4.252
3146456SLIGO L269
Solar/Wind Harmer
0.199
971153AH1-033 GEN
Solar/Wind Harmer
2.3
316313AB2-026
Solar/Wind Harmer
0.124
316258AE1-075 C
Solar/Wind Harmer
0.149
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.984
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.195
3146626S HERTFORD
Solar/Wind Harmer
0.194
3145273HOLLAND
Solar/Wind Harmer
0.145
3146376EDENTON
Solar/Wind Harmer
0.19
315614AA2-178 GEN
Solar/Wind Harmer
1.07
971157AH1-035 GEN
Solar/Wind Harmer
2.212
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
315737AD1-076 GEN
Solar/Wind Harmer
2.365
970917AG2-570 GEN
Solar/Wind Harmer
16.254
316365GEN2_N
Solar/Wind Harmer
0.409
3146206CASHIE
Solar/Wind Harmer
0.182
3145893MURPHYS
Solar/Wind Harmer
0.304
3145893MURPHYS
Solar/Wind Harmer
0.182
957521AF2-046 GEN
Solar/Wind Harmer
13.506
961681AG1-008 GEN
Solar/Wind Harmer
13.506
3146173TUNIS
Solar/Wind Harmer
0.18
3156021HOLLOMANSOL
Solar/Wind Harmer
0.817
316463AE2-346 GEN
Solar/Wind Harmer
0.154
316140AB2-099
Solar/Wind Harmer
0.064
962331AG1-082 GEN
Solar/Wind Harmer
1.916
3146263WOODLND
Solar/Wind Harmer
0.178
313506AB2-031 GEN
Solar/Wind Harmer
0.548
3142666NORTHAMPTON
Solar/Wind Harmer
0.176
3145963POPLR C
Solar/Wind Harmer
0.176
970909AG2-566 GEN
Solar/Wind Harmer
1.881
316317KELFORD C
Solar/Wind Harmer
0.017
3145823KELFORD
Solar/Wind Harmer
0.176
3147043LAWRENC
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.105
3146776BUCKING
Solar/Wind Harmer
0.063
3145796HORNRTN
Solar/Wind Harmer
0.695
3145796HORNRTN
Solar/Wind Harmer
0.174
316478AD1-087 GEN
Solar/Wind Harmer
0.607
316486AD2-202 GEN
Solar/Wind Harmer
0.178
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3147133PAMPLIN
Solar/Wind Harmer
0.539
971193AH1-056 GEN
Solar/Wind Harmer
10.456
963181AG1-167 GEN
Solar/Wind Harmer
0.685
3144293JTRSVLE
Adder
0.545
316210AC1-098 GEN
Solar/Wind Harmer
1.582
3145933PARMELE
Solar/Wind Harmer
0.17
966801AG1-551 GEN
Solar/Wind Harmer
1.979
959311AF2-222 GEN
Solar/Wind Harmer
15.084
970257AG2-171 GEN
Solar/Wind Harmer
5.422
315785AD2-033 C
Solar/Wind Harmer
1.375
964241AG1-285 GEN
Solar/Wind Harmer
11.211
970221AG2-151 GEN
Solar/Wind Harmer
8.948
316131AB2-060 GEN
Solar/Wind Harmer
0.527
3145746EVERETS
Solar/Wind Harmer
0.167
3145746EVERETS
Solar/Wind Harmer
0.167
315724AD1-057 GEN
Solar/Wind Harmer
0.624
316327AA2-057 GEN
Solar/Wind Harmer
0.25
972255AH1-712 GEN
Adder
83.534
3146233WITAKRS
Solar/Wind Harmer
0.817
3146233WITAKRS
Solar/Wind Harmer
0.111
3146073TAR RVR
Solar/Wind Harmer
0.163
3146083TARBORO
Solar/Wind Harmer
0.163
3138543CONSLDL
Solar/Wind Harmer
0.107
961601AG1-000A GEN
Solar/Wind Harmer
11.396
3145543BTLEBRO
Solar/Wind Harmer
0.16
3145543BTLEBRO
Solar/Wind Harmer
0.16
971623AH1-311 GEN
Solar/Wind Harmer
0.32
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
6.556
971683AH1-343 GEN
Solar/Wind Harmer
5.342
316283AC2-100 C
Solar/Wind Harmer
0.274
3148013FISHERV
Solar/Wind Harmer
0.138
315616AA1-038_C
Solar/Wind Harmer
0.001
3151861LOWMORA
Adder
1.283
237061AD1-155 GEN
Solar/Wind Harmer
0.003
238221AF1-254 C O1
Solar/Wind Helper
0.304
237030AB1-096 C
Solar/Wind Helper
0.08
235067AD1-061 GEN
Solar/Wind Helper
0.532
205917AD1-020 ES
Solar/Wind Helper
0.38
233994AC2-023 GEN
Solar/Wind Helper
0.99
233996TM1833_GEN
Solar/Wind Helper
0.269
233997TMININ_4.2
Solar/Wind Helper
0.269
233971AC1-093 C
Solar/Wind Helper
0.369
232406W1-004 FULL
Solar/Wind Helper
0.523
233940AF2-379 C
Solar/Wind Helper
0.064
234015AF2-250 C
Solar/Wind Helper
0.039
233952AC2-187 GEN
Solar/Wind Helper
0.239
233918AB1-142 GEN
Solar/Wind Helper
0.516
233982AB2-133 GEN
Solar/Wind Helper
0.368
230430AE1-229_GEN
Solar/Wind Helper
3.449
230415AB2-049 C
Solar/Wind Helper
0.031
228729W2-030 C
Solar/Wind Helper
0.113
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.056
219291REEVESSOUT C
Solar/Wind Helper
0.012
219912AD2-042 GEN
Solar/Wind Helper
0.153
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.043
219348LDSOLAR C
Solar/Wind Helper
0.117
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.064
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.058
20714528FRN_Y2-051
Solar/Wind Helper
0.058
219276PARKLANDSO C
Solar/Wind Helper
0.091
20720528MAN_W1-024
Solar/Wind Helper
0.029
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.028
219908AB1-139 C
Solar/Wind Helper
0.075
219249CENTRALDIV C
Solar/Wind Helper
0.01
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.09
316254AC1-120 GEN1
Solar/Wind Harmer
0.583
315683AE1-153 C
Solar/Wind Harmer
20.71
3147666LOUISA
Solar/Wind Harmer
0.979
316192AB2-158 GEN
Solar/Wind Harmer
1.381
972197AH1-683 GEN
Adder
4.972
972219AH1-694 GEN
Adder
3.58
3151751LOISA D
Adder
15.317
3140676OCCOQUN
Adder
0.566
966881AG1-559 GEN
Solar/Wind Harmer
0.265
3141346CRANES
Adder
0.266
972223AH1-696 GEN
Adder
17.606
3150151POSSMC1
Adder
2.229
972135AH1-637 GEN
Solar/Wind Harmer
1.858
316337AD2-073 GEN
Solar/Wind Harmer
0.187
3142416OLDCHRC
Solar/Wind Harmer
0.554
3142416OLDCHRC
Solar/Wind Harmer
0.212
3150351NORNECKC2
Adder
2.124
3141726DUNNSVL
Solar/Wind Harmer
0.851
3143226MDLTHAN
Solar/Wind Harmer
0.212
3143526WINTERP
Solar/Wind Harmer
1.104
962861AG1-135 GEN
Solar/Wind Harmer
6.784
3150851SPRUNCC
Adder
0.972
3143096IRON208
Adder
0.883
3142543TWELFTH
Solar/Wind Harmer
0.02
3138133OCRAN
Solar/Wind Harmer
0.126
3141766HARMONY
Solar/Wind Harmer
0.042
3142433PROV 92
Solar/Wind Harmer
0.84
3142433PROV 92
Adder
0.408
3142433PROV 92
Adder
0.408
971777AH1-397 GEN
Solar/Wind Harmer
0.554
3141843SHACKLE
Adder
1.073
944631AF1-128 GEN
Adder
99.968
316159AE1-175 C
Solar/Wind Harmer
0.179
971317AH1-138 GEN
Solar/Wind Harmer
1.542
970129AG2-093 GEN
Solar/Wind Harmer
5.871
315671AE2-027_GEN
Solar/Wind Harmer
13.209
316458AB2-190 GEN2
Solar/Wind Harmer
1.107
971069AG2-661 GEN
Solar/Wind Harmer
3.658
3138126ROCKLANDING
Solar/Wind Harmer
0.094
971647AH1-324 GEN
Solar/Wind Harmer
8.741
961611AG1-000B GEN
Solar/Wind Harmer
10.718
3151171GRAVELC
Adder
2.168
3145336SMITFLD
Solar/Wind Harmer
0.811
316294AC1-161 GEN
Solar/Wind Harmer
3.512
970659AG2-427 GEN
Solar/Wind Harmer
9.759
316381AD1-082 GEN
Solar/Wind Harmer
0.21
316375AC2-012 GEN
Solar/Wind Harmer
0.005
3150981CHESPKA
Adder
2.51
944591AF1-124 GEN
Solar/Wind Harmer
45.415
970661AG2-428 GEN
Solar/Wind Harmer
19.99
316072AD1-144
Solar/Wind Harmer
0.072
939411AE1-173 GEN
Solar/Wind Harmer
85.364
940641AE2-051 GEN
Solar/Wind Harmer
15.997
316388AE2-253 GEN
Solar/Wind Harmer
0.625
3146456SLIGO L269
Solar/Wind Harmer
0.199
316246AF1-032 C
Solar/Wind Harmer
0.09
316093AE2-104_GEN
Solar/Wind Harmer
3.331
3143336POWHATN
Solar/Wind Harmer
3.511
3146516WINFALL
Solar/Wind Harmer
0.632
3146516WINFALL
Solar/Wind Harmer
0.195
316336AC2-165 C
Solar/Wind Harmer
0.008
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.19
3145663CRESWEL
Solar/Wind Harmer
0.523
971163AH1-040 GEN
Solar/Wind Harmer
14.962
970937AG2-583 GEN
Solar/Wind Harmer
11.244
970919AG2-571 GEN
Solar/Wind Harmer
6.502
316023GEN1_S
Solar/Wind Harmer
0.409
970087AG2-069 GEN
Solar/Wind Harmer
14.579
3146206CASHIE
Solar/Wind Harmer
0.182
971547AH1-271 GEN
Solar/Wind Harmer
3.887
3145893MURPHYS
Solar/Wind Harmer
0.727
3145893MURPHYS
Solar/Wind Harmer
0.809
3146173TUNIS
Solar/Wind Harmer
0.18
960081AF2-299 GEN
Solar/Wind Harmer
1.72
3145683EARLEYS
Solar/Wind Harmer
0.179
957481AF2-042 GEN
Solar/Wind Harmer
47.712
3146263WOODLND
Solar/Wind Harmer
0.178
315693AD1-088 GEN
Solar/Wind Harmer
8.533
962491AG1-098 GEN
Solar/Wind Harmer
10.141
971795AH1-408 GEN
Solar/Wind Harmer
11.784
3145963POPLR C
Solar/Wind Harmer
0.176
316011AB1-132 GEN
Solar/Wind Harmer
3.202
962571AG1-106 GEN
Solar/Wind Harmer
2.506
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.176
3147043LAWRENC
Adder
1.589
3146926FARMVIL
Solar/Wind Harmer
0.105
316174AB2-169 GEN
Solar/Wind Harmer
0.005
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.07
972003AH1-546 GEN
Solar/Wind Harmer
7.424
3145783HORNRTN
Solar/Wind Harmer
0.174
3145796HORNRTN
Solar/Wind Harmer
0.573
3145796HORNRTN
Solar/Wind Harmer
0.174
963171AG1-166 GEN
Solar/Wind Harmer
0.913
971563AH1-280 GEN
Solar/Wind Harmer
1.826
3144293JTRSVLE
Adder
0.545
316212AC1-099_GEN
Solar/Wind Harmer
0.882
970685AG2-442 GEN
Solar/Wind Harmer
12.717
3146293MARTNCO
Solar/Wind Harmer
0.158
316129AC1-054 GEN
Solar/Wind Harmer
0.638
971065AG2-659 GEN
Solar/Wind Harmer
7.218
971377AH1-170 GEN
Solar/Wind Harmer
1.79
3147623JAMES R
Solar/Wind Harmer
0.389
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3141913WHIT STONE
Solar/Wind Harmer
0.21
3143873LANEXA
Solar/Wind Harmer
0.126
316059AD1-063 C
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.408
3142433PROV 92
Adder
0.408
971167AH1-042 GEN
Solar/Wind Harmer
18.654
970189AG2-124 GEN
Solar/Wind Harmer
6.224
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.042
3138283WHITEMARSH
Solar/Wind Harmer
0.048
316132AB2-190 GEN1
Solar/Wind Harmer
1.107
316369SG1_INVT
Solar/Wind Harmer
0.008
972265AH1-717 GEN
Adder
15.821
3151201GRAVEL4
Adder
14.831
3151191GRAVEL3
Adder
14.643
3151211GRAVEL5
Adder
14.643
3143316POE
Solar/Wind Harmer
0.803
971445AH1-216 GEN
Solar/Wind Harmer
14.282
3151081ELIZAR1
Adder
18.434
3151091ELIZAR2
Adder
18.114
3152611GOSPORTB
Adder
2.56
3152621GOSPORTC
Adder
2.173
3152601GOSPORTA
Adder
2.005
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.137
316311AC2-079 GEN
Solar/Wind Harmer
5.725
957871AF2-081 GEN
Solar/Wind Harmer
9.922
319010AE1-072 C
Solar/Wind Harmer
1.001
316305AF2-043 C
Solar/Wind Harmer
0.002
3146406KITTY HAWK
Solar/Wind Harmer
0.025
315835AF2-110_GEN
Solar/Wind Harmer
1.359
313526AB2-022
Solar/Wind Harmer
0.107
3146486SUNBURY
Solar/Wind Harmer
0.197
3146486SUNBURY
Solar/Wind Harmer
0.197
316321Z2-027
Solar/Wind Harmer
0.037
3146396TANGLEW
Solar/Wind Harmer
0.542
3145176PASQUOTANK
Solar/Wind Harmer
0.122
316315AB2-025 C
Solar/Wind Harmer
0.157
941031AE2-094 GEN
Solar/Wind Harmer
35.747
944011AF1-069 GEN
Solar/Wind Harmer
11.68
315814AE2-033 C
Solar/Wind Harmer
15.327
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
40.848
970673AG2-436 GEN
Solar/Wind Harmer
27.232
3130156CHOWAN
Solar/Wind Harmer
0.19
3130156CHOWAN
Solar/Wind Harmer
0.19
971967AH1-528 GEN
Solar/Wind Harmer
30.407
315816AE2-034 GEN
Solar/Wind Harmer
0.803
3130546PLYMOUTH
Solar/Wind Harmer
0.184
315732AD1-074 GEN1
Solar/Wind Harmer
1.056
315733AD1-074 GEN2
Solar/Wind Harmer
1.056
315735AD1-075 GEN1
Solar/Wind Harmer
0.529
965291AG1-394 GEN
Solar/Wind Harmer
0.815
970085AG2-068 GEN
Solar/Wind Harmer
9.72
970581AG2-369 GEN
Solar/Wind Harmer
8.359
3146206CASHIE
Solar/Wind Harmer
0.182
970601AG2-382 GEN
Solar/Wind Harmer
6.803
3145893MURPHYS
Solar/Wind Harmer
0.491
3145893MURPHYS
Solar/Wind Harmer
0.182
3145513AHOSKIE
Solar/Wind Harmer
0.376
3145513AHOSKIE
Solar/Wind Harmer
0.179
3146043SEABORD
Solar/Wind Harmer
0.179
3145683EARLEYS
Solar/Wind Harmer
0.358
3145683EARLEYS
Solar/Wind Harmer
0.179
3145683EARLEYS
Solar/Wind Harmer
0.179
315607AA1-063A GEN
Solar/Wind Harmer
0.365
316087AB2-174 GEN
Solar/Wind Harmer
0.005
3137643SOCKMAN
Solar/Wind Harmer
0.704
315652AC1-086 GEN
Solar/Wind Harmer
19.374
970285AG2-188 GEN
Solar/Wind Harmer
13.847
971845AH1-439 GEN
Solar/Wind Harmer
7.933
972205AH1-687 GEN
Adder
7.463
3145796HORNRTN
Solar/Wind Harmer
0.556
3145796HORNRTN
Solar/Wind Harmer
0.07
3146033SCOT NK
Solar/Wind Harmer
0.691
315657AE1-056 GEN
Solar/Wind Harmer
5.923
946301AF1-294 GEN
Solar/Wind Harmer
3.377
961791AG1-021 GEN
Solar/Wind Harmer
1.643
970683AG2-441 GEN
Solar/Wind Harmer
11.355
970681AG2-440 GEN
Solar/Wind Harmer
9.084
970831AG2-522 GEN
Solar/Wind Harmer
7.264
3144303KENBRDG
Solar/Wind Harmer
0.135
971443AH1-215 GEN
Solar/Wind Harmer
2.845
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316005AA1-067
Solar/Wind Harmer
0.179
3145746EVERETS
Solar/Wind Harmer
0.664
3145746EVERETS
Solar/Wind Harmer
0.167
3145746EVERETS
Solar/Wind Harmer
0.167
3145746EVERETS
Solar/Wind Harmer
0.167
970181AG2-120 GEN
Solar/Wind Harmer
2.078
971447AH1-217 GEN
Solar/Wind Harmer
5.04
957861AF2-080 GEN
Solar/Wind Harmer
7.098
316420AA1-050 GEN
Solar/Wind Harmer
0.005
972193AH1-681 GEN
Adder
3.732
316319Z2-044 C
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0.007
3138266HYDRAULIC
Solar/Wind Harmer
0.004
3145573BETHELC
Solar/Wind Harmer
0.163
3145573BETHELC
Solar/Wind Harmer
0.163
316118AC1-105 GEN
Solar/Wind Harmer
0.404
3147173SINAI
Solar/Wind Harmer
0.154
3147243WELCO
Solar/Wind Harmer
0.096
270494AE1-108_GEN
Solar/Wind Harmer
1.806
970865AG2-541 GEN
Solar/Wind Harmer
4.891
3148133STUARTS
Solar/Wind Harmer
0.083
3148013FISHERV
Solar/Wind Harmer
0.079
316123AC1-075 GEN
Solar/Wind Harmer
0.181
970165AG2-112 GEN
Solar/Wind Harmer
1.076
970163AG2-111 GEN
Solar/Wind Harmer
1.027
3148463FAIRFLD
Solar/Wind Harmer
0.12
3151881LOWMORC
Adder
1.273
3151881LOWMORC
Adder
1.253
3151861LOWMORA
Adder
1.233
237085AD2-009_GEN
Solar/Wind Helper
1.73
238208AF1-136 C
Solar/Wind Helper
0.215
959381AF2-229 GEN
Solar/Wind Helper
0.375
234033AF1-007_GEN
Solar/Wind Helper
7.236
233923SMA
Solar/Wind Helper
0.988
233990AG1-397 GEN
Solar/Wind Helper
0.278
232432Z2-076 GEN
Solar/Wind Helper
0.069
232436AB1-176 C
Solar/Wind Helper
0.046
233935AB2-179 C
Solar/Wind Helper
1.3
203975AE1-071-GEN
Solar/Wind Helper
2.597
964001AG1-254 GEN
Solar/Wind Helper
0.977
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.027
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.117
219688LUMSOLAR_S C
Solar/Wind Helper
0.041
219607WPEMNERT C
Solar/Wind Helper
0.082
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.097
20715828PEM_W1-120
Solar/Wind Helper
0.097
207459AE1-142 C O1
Solar/Wind Helper
0.295
219620RIDERU C
Solar/Wind Helper
0.001
205943AE1-185 GEN
Solar/Wind Helper
0.503
205956AE1-196_GEN
Solar/Wind Helper
0.502
205932AD2-116_GEN
Solar/Wind Helper
0.502
960921AF2-383 GEN
Solar/Wind Helper
0.358
218526CNTRALGAS2 C
Solar/Wind Helper
0.163
20675528CPH_W2-050
Solar/Wind Helper
0.088
218524CNTRALGAS1 C
Solar/Wind Helper
0.162
966261AG1-495 GEN
Solar/Wind Helper
0.082
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20674828DL_W4-046
Solar/Wind Helper
0.008
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.78
3145746EVERETS
Solar/Wind Harmer
0.167
3145746EVERETS
Solar/Wind Harmer
0.167
315722AD1-056 GEN
Solar/Wind Harmer
1.053
315687AD1-152 GEN
Solar/Wind Harmer
0.005
316494AC1-189 GEN
Solar/Wind Harmer
0.556
972277AH1-723 GEN
Adder
97.342
3146233WITAKRS
Solar/Wind Harmer
0.648
961671AG1-007 GEN
Solar/Wind Harmer
0.025
3146083TARBORO
Solar/Wind Harmer
0.163
3145493TOT1
Solar/Wind Harmer
0.723
3145543BTLEBRO
Solar/Wind Harmer
0.16
3145543BTLEBRO
Solar/Wind Harmer
0.128
316359AB2-059 GEN
Solar/Wind Harmer
0.576
316049AB1-081 GEN
Solar/Wind Harmer
0.917
3142053HEARTS
Solar/Wind Harmer
0.282
970401AG2-262 GEN
Solar/Wind Harmer
0.935
316003AC1-222 GEN
Solar/Wind Harmer
0.004
3147983MERCK5
Solar/Wind Harmer
0.05
315705AF1-075 GEN
Solar/Wind Harmer
4.991
23779801AA1-109
Solar/Wind Helper
0.222
237080AD1-060 GEN
Solar/Wind Helper
0.373
237038AE2-054 C
Solar/Wind Helper
0.293
235062AE1-101 C1
Solar/Wind Helper
1.773
233998TM1NIN_3.36
Solar/Wind Helper
0.269
233972AC1-094 C
Solar/Wind Helper
0.312
232404W1-003 C
Solar/Wind Helper
0.523
232428Y3-058 C
Solar/Wind Helper
0.348
232434Z2-077 GEN
Solar/Wind Helper
0.131
232426Y1-080 FULL
Solar/Wind Helper
0.04
233964AF2-378 GEN
Solar/Wind Helper
0.043
233954AC2-188 GEN
Solar/Wind Helper
0.239
233950AC2-186 GEN
Solar/Wind Helper
0.12
232422X3-066 FULL
Solar/Wind Helper
0.117
233930AB2-032 GEN
Solar/Wind Helper
0.391
233915AB1-141 GEN
Solar/Wind Helper
0.516
966131AG1-482 GEN
Solar/Wind Helper
0.138
230511AF1-262
Solar/Wind Helper
0.015
228728W1-130C
Solar/Wind Helper
0.055
230434AG1-499 GEN
Solar/Wind Helper
0.235
219258KINSLEYDEP C
Solar/Wind Helper
0.078
219904AC1-010 C
Solar/Wind Helper
0.062
218660EHAMPSOLAR C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.041
219907AC1-030 C
Solar/Wind Helper
0.035
219304NAMERICA C
Solar/Wind Helper
0.134
20720728JCB_W1-129
Solar/Wind Helper
0.058
207445AB1-138_GEN
Solar/Wind Helper
0.106
963711AG1-223 GEN
Solar/Wind Helper
0.065
20714828MDF_W3-079
Solar/Wind Helper
0.132
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.079
207454AA2-184 E
Solar/Wind Helper
0.315
20742028HF_AC1-207
Solar/Wind Helper
0.143
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.077
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.023
205941AD2-115 GEN
Solar/Wind Helper
0.494
207439AE1-081 C O1
Solar/Wind Helper
0.019
20675828AU_W4-064
Solar/Wind Helper
0.03
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.579
20671928W4-073
Solar/Wind Helper
0.09
LAGNLTFEXP_LAGN->PJM
CLTF
9.398
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.867
TVALTFEXP_TVA->PJM
CLTF
4.772
NYPJM->LTFIMP_NY
CLTF
4.891
LGEELTFEXP_LGEE->PJM
CLTF
2.004
WECLTFEXP_WEC->PJM
CLTF
1.006
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.101
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.667
MECLTFEXP_MEC->PJM
CLTF
5.134
SIGELTFEXP_SIGE->PJM
CLTF
0.16
CPLELTFEXP_CPLE->PJM
CLTF
10.838
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.117

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.66 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4497.83
MW Contribution:4.29
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
5.789
3151051BRUNSWICKS1
50/50
9.423
3151021BRUNSWICKG1
50/50
4.54
971451AH1-221 GEN
50/50
13.79
3151531CLOVER1
50/50
5.905
940641AE2-051 GEN
Solar/Wind Harmer
28.987
939411AE1-173 GEN
Solar/Wind Harmer
145.254
970919AG2-571 GEN
Solar/Wind Harmer
11.736
970087AG2-069 GEN
Solar/Wind Harmer
26.275
957481AF2-042 GEN
Solar/Wind Harmer
77.806
316294AC1-161 GEN
Solar/Wind Harmer
4.901
944591AF1-124 GEN
Solar/Wind Harmer
62.818
316388AE2-253 GEN
Solar/Wind Harmer
0.855
3146456SLIGO L269
Solar/Wind Harmer
0.272
315693AD1-088 GEN
Solar/Wind Harmer
13.02
316375AC2-012 GEN
Solar/Wind Harmer
0.007
3150981CHESPKA
Adder
3.38
316246AF1-032 C
Solar/Wind Harmer
0.122
3146516WINFALL
Solar/Wind Harmer
0.867
3146516WINFALL
Solar/Wind Harmer
0.268
962491AG1-098 GEN
Solar/Wind Harmer
15.268
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
316093AE2-104_GEN
Solar/Wind Harmer
4.461
316023GEN1_S
Solar/Wind Harmer
0.594
3130156CHOWAN
Solar/Wind Harmer
0.263
3145663CRESWEL
Solar/Wind Harmer
0.728
971163AH1-040 GEN
Solar/Wind Harmer
20.811
316072AD1-144
Solar/Wind Harmer
0.094
315687AD1-152 GEN
Solar/Wind Harmer
0.008
960081AF2-299 GEN
Solar/Wind Harmer
2.469
3146206CASHIE
Solar/Wind Harmer
0.256
971547AH1-271 GEN
Solar/Wind Harmer
5.457
3145893MURPHYS
Solar/Wind Harmer
1.02
3145893MURPHYS
Solar/Wind Harmer
1.134
316011AB1-132 GEN
Solar/Wind Harmer
4.622
962571AG1-106 GEN
Solar/Wind Harmer
3.617
3146173TUNIS
Solar/Wind Harmer
0.254
3145683EARLEYS
Solar/Wind Harmer
0.253
3146263WOODLND
Solar/Wind Harmer
0.252
316190AA2-174 GEN
Solar/Wind Harmer
0
3145796HORNRTN
Solar/Wind Harmer
0.829
3145796HORNRTN
Solar/Wind Harmer
0.251
971795AH1-408 GEN
Solar/Wind Harmer
16.715
3145823KELFORD
Solar/Wind Harmer
0.25
3145783HORNRTN
Solar/Wind Harmer
0.25
3145963POPLR C
Solar/Wind Harmer
0.249
316174AB2-169 GEN
Solar/Wind Harmer
0.007
3147043LAWRENC
Adder
2.242
316212AC1-099_GEN
Solar/Wind Harmer
1.268
316129AC1-054 GEN
Solar/Wind Harmer
0.918
970661AG2-428 GEN
Solar/Wind Harmer
24.263
971065AG2-659 GEN
Solar/Wind Harmer
10.39
3145336SMITFLD
Solar/Wind Harmer
0.973
3146293MARTNCO
Solar/Wind Harmer
0.225
315722AD1-056 GEN
Solar/Wind Harmer
1.532
3145746EVERETS
Solar/Wind Harmer
0.24
3145746EVERETS
Solar/Wind Harmer
0.24
316381AD1-082 GEN
Solar/Wind Harmer
0.249
316494AC1-189 GEN
Solar/Wind Harmer
0.804
970659AG2-427 GEN
Solar/Wind Harmer
11.496
3146233WITAKRS
Solar/Wind Harmer
0.942
961671AG1-007 GEN
Solar/Wind Harmer
0.036
3146083TARBORO
Solar/Wind Harmer
0.236
3145493TOT1
Solar/Wind Harmer
1.05
316359AB2-059 GEN
Solar/Wind Harmer
0.841
316049AB1-081 GEN
Solar/Wind Harmer
1.34
3145543BTLEBRO
Solar/Wind Harmer
0.234
3145543BTLEBRO
Solar/Wind Harmer
0.187
3142053HEARTS
Solar/Wind Harmer
0.412
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3151171GRAVELC
Adder
2.407
970401AG2-262 GEN
Solar/Wind Harmer
1.317
3138126ROCKLANDING
Solar/Wind Harmer
0.101
961611AG1-000B GEN
Solar/Wind Harmer
11.332
316003AC1-222 GEN
Solar/Wind Harmer
0.006
971647AH1-324 GEN
Solar/Wind Harmer
8.873
971317AH1-138 GEN
Solar/Wind Harmer
1.539
970685AG2-442 GEN
Solar/Wind Harmer
14.697
971069AG2-661 GEN
Solar/Wind Harmer
3.441
316159AE1-175 C
Solar/Wind Harmer
0.165
963171AG1-166 GEN
Solar/Wind Harmer
1.004
971563AH1-280 GEN
Solar/Wind Harmer
2.008
3144293JTRSVLE
Adder
0.599
316458AB2-190 GEN2
Solar/Wind Harmer
0.989
315671AE2-027_GEN
Solar/Wind Harmer
11.755
970129AG2-093 GEN
Solar/Wind Harmer
5.199
971777AH1-397 GEN
Solar/Wind Harmer
0.395
3141843SHACKLE
Adder
0.764
3141766HARMONY
Solar/Wind Harmer
0.03
3146926FARMVIL
Solar/Wind Harmer
0.088
3138133OCRAN
Solar/Wind Harmer
0.087
3142433PROV 92
Solar/Wind Harmer
0.557
3142433PROV 92
Adder
0.271
3142433PROV 92
Adder
0.271
970223AG2-152 GEN
Solar/Wind Harmer
9.565
944631AF1-128 GEN
Adder
62.411
270016AE1-250 BESS
Solar/Wind Harmer
0.004
962861AG1-135 GEN
Solar/Wind Harmer
4.023
3147123OTTER R
Solar/Wind Harmer
0.07
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3141726DUNNSVL
Solar/Wind Harmer
0.457
316045AC1-158 PL2
Solar/Wind Helper
5.221
3147666LOUISA
Solar/Wind Helper
1.002
316192AB2-158 GEN
Solar/Wind Helper
1.658
316254AC1-120 GEN1
Solar/Wind Helper
1.035
970533AG2-339 GEN
50/50
32.288
970531AG2-338 GEN
50/50
12.915
315242AE2-183_GT2
50/50
5.789
315241AE2-183_GT1
50/50
5.753
972185AH1-677 GEN
50/50
20.868
3151041BRUNSWICKG3
50/50
4.54
972187AH1-678 GEN
50/50
10.419
970933AG2-581 GEN
Solar/Wind Harmer
26.407
970099AG2-077 GEN
Solar/Wind Harmer
31.122
3144356SAPONY
Solar/Wind Harmer
2.393
316185AD1-033 GEN
Solar/Wind Harmer
0.008
3145506HICKORY
Solar/Wind Harmer
1.094
3145506HICKORY
Solar/Wind Harmer
0.657
3145506HICKORY
Solar/Wind Harmer
0.164
316339AD2-160 GEN
Solar/Wind Harmer
0.443
316018AA1-139 ULT2
Solar/Wind Harmer
0.007
316017AA1-139 ULT1
Solar/Wind Harmer
0.152
3142956BIRDNECK
Solar/Wind Harmer
0
3137176SLIGO L2192
Solar/Wind Harmer
1.084
3146456SLIGO L269
Solar/Wind Harmer
4.819
316316AC1-027 C
Solar/Wind Harmer
0.261
3130086AYDLETT
Solar/Wind Harmer
1.088
316036AC1-147 C
Solar/Wind Harmer
0.05
3150991CHESPKB
Adder
2.836
3150991CHESPKB
Adder
2.768
3146386ELIZ CT
Solar/Wind Harmer
0.27
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.268
3146516WINFALL
Solar/Wind Harmer
0.268
3146516WINFALL
Solar/Wind Harmer
0.268
3146626S HERTFORD
Solar/Wind Harmer
0.267
3146626S HERTFORD
Solar/Wind Harmer
0.267
3146376EDENTON
Solar/Wind Harmer
1.171
3146376EDENTON
Solar/Wind Harmer
1.171
315742AE1-103 GEN
Solar/Wind Harmer
0.003
316065AD1-022 GEN
Solar/Wind Harmer
11.799
3145893MURPHYS
Solar/Wind Harmer
1.706
3145893MURPHYS
Solar/Wind Harmer
0.459
316181AB2-040 GEN
Solar/Wind Harmer
0.369
3142666NORTHAMPTON
Solar/Wind Harmer
0.254
3142666NORTHAMPTON
Solar/Wind Harmer
0.254
3142666NORTHAMPTON
Solar/Wind Harmer
0.254
3142666NORTHAMPTON
Solar/Wind Harmer
0.153
3146173TUNIS
Solar/Wind Harmer
0.254
3146173TUNIS
Solar/Wind Harmer
0.254
316426AA2-053 GEN
Solar/Wind Harmer
0.849
3145796HORNRTN
Solar/Wind Harmer
0.754
3145593CAROLNA
Solar/Wind Harmer
0.251
3145593CAROLNA
Solar/Wind Harmer
0.251
966811AG1-552 GEN
Solar/Wind Harmer
2.724
3145593CAROLNA
Solar/Wind Harmer
0.313
3145783HORNRTN
Solar/Wind Harmer
4.447
3145783HORNRTN
Solar/Wind Harmer
3.557
3145783HORNRTN
Solar/Wind Harmer
1.112
3145783HORNRTN
Solar/Wind Harmer
0.445
316274AC1-208 GEN
Solar/Wind Harmer
1.268
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3145933PARMELE
Solar/Wind Harmer
0.486
3145933PARMELE
Solar/Wind Harmer
0.243
970657AG2-426 GEN
Solar/Wind Harmer
8.443
970657AG2-426 GEN
Solar/Wind Harmer
1.77
939181AE1-148 GEN
Solar/Wind Harmer
11.415
3145493TOT1
Solar/Wind Harmer
0.548
3145453TOT5
Solar/Wind Harmer
0.329
3145603CNETO
Solar/Wind Harmer
0.219
961601AG1-000A GEN
Solar/Wind Harmer
4.164
316263AC1-034 GEN
Solar/Wind Harmer
8.897
313527AB2-043 GEN
Solar/Wind Harmer
0.003
962561AG1-105 GEN
Solar/Wind Harmer
10.79
964791AG1-342 GEN
Solar/Wind Harmer
4.311
3146843MT LREL
Solar/Wind Harmer
0.224
3146843MT LREL
Solar/Wind Harmer
0.224
971741AH1-377 GEN
Solar/Wind Harmer
21.422
316222AC1-221 GEN
Solar/Wind Harmer
0.867
970323AG2-213 GEN
Solar/Wind Harmer
8.785
971775AH1-396 GEN
Solar/Wind Harmer
0.329
316034AC1-036 C
Solar/Wind Harmer
0.015
316033AB2-134 GEN
Solar/Wind Harmer
0.012
315697AD1-025 GEN
Solar/Wind Harmer
0.225
970301AG2-198 GEN
Solar/Wind Harmer
8.511
958211AF2-115 GEN
Solar/Wind Harmer
2.259
963191AG1-168 GEN
Solar/Wind Harmer
0.753
3144293JTRSVLE
Adder
0.599
3144293JTRSVLE
Adder
0.505
3147133PAMPLIN
Solar/Wind Harmer
0.182
3147133PAMPLIN
Solar/Wind Harmer
0.146
316240AF1-291 C
Solar/Wind Harmer
0.001
944641AF1-129 GEN
Adder
78.098
942751AE2-291 GEN
Solar/Wind Harmer
8.652
3142946ENON
Solar/Wind Harmer
0.013
270013AE1-250 PV
Solar/Wind Harmer
0.004
958261AF2-120 GEN
Solar/Wind Harmer
4.097
316075AC2-137 C
Solar/Wind Harmer
0.033
316447AC1-158 HLD
Solar/Wind Helper
3.59
315651AD1-115 GEN
Solar/Wind Helper
0.751
315244AE2-183_ST
50/50
10.008
963041AG1-153 GEN
50/50
9.194
315779AE2-040
50/50
3.994
3151541CLOVER2
50/50
5.877
3151081ELIZAR1
50/50
26.432
941031AE2-094 GEN
Solar/Wind Harmer
66.901
944011AF1-069 GEN
Solar/Wind Harmer
21.859
970673AG2-436 GEN
Solar/Wind Harmer
75.678
970673AG2-436 GEN
Solar/Wind Harmer
50.452
971967AH1-528 GEN
Solar/Wind Harmer
55.275
970085AG2-068 GEN
Solar/Wind Harmer
17.517
970581AG2-369 GEN
Solar/Wind Harmer
15.064
316315AB2-025 C
Solar/Wind Harmer
0.231
315814AE2-033 C
Solar/Wind Harmer
22.552
957871AF2-081 GEN
Solar/Wind Harmer
13.58
319010AE1-072 C
Solar/Wind Harmer
1.371
3146406KITTY HAWK
Solar/Wind Harmer
0.034
3151091ELIZAR2
Adder
24.477
3152611GOSPORTB
Adder
3.448
3152621GOSPORTC
Adder
2.926
3152601GOSPORTA
Adder
2.699
313526AB2-022
Solar/Wind Harmer
0.146
316305AF2-043 C
Solar/Wind Harmer
0.002
316321Z2-027
Solar/Wind Harmer
0.05
3146396TANGLEW
Solar/Wind Harmer
0.743
3145176PASQUOTANK
Solar/Wind Harmer
0.167
3146486SUNBURY
Solar/Wind Harmer
0.269
3146486SUNBURY
Solar/Wind Harmer
0.269
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
315835AF2-110_GEN
Solar/Wind Harmer
1.82
3130156CHOWAN
Solar/Wind Harmer
0.263
3130156CHOWAN
Solar/Wind Harmer
0.263
315816AE2-034 GEN
Solar/Wind Harmer
1.116
3130546PLYMOUTH
Solar/Wind Harmer
0.257
315732AD1-074 GEN1
Solar/Wind Harmer
1.477
315733AD1-074 GEN2
Solar/Wind Harmer
1.477
315735AD1-075 GEN1
Solar/Wind Harmer
0.74
965291AG1-394 GEN
Solar/Wind Harmer
1.138
3146206CASHIE
Solar/Wind Harmer
0.256
970601AG2-382 GEN
Solar/Wind Harmer
9.549
316311AC2-079 GEN
Solar/Wind Harmer
7.334
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.175
316087AB2-174 GEN
Solar/Wind Harmer
0.007
3145893MURPHYS
Solar/Wind Harmer
0.688
3145893MURPHYS
Solar/Wind Harmer
0.255
315652AC1-086 GEN
Solar/Wind Harmer
27.966
3145513AHOSKIE
Solar/Wind Harmer
0.53
3145513AHOSKIE
Solar/Wind Harmer
0.253
3146043SEABORD
Solar/Wind Harmer
0.253
315607AA1-063A GEN
Solar/Wind Harmer
0.517
3145683EARLEYS
Solar/Wind Harmer
0.506
3145683EARLEYS
Solar/Wind Harmer
0.253
3145683EARLEYS
Solar/Wind Harmer
0.253
3137643SOCKMAN
Solar/Wind Harmer
1.009
3145796HORNRTN
Solar/Wind Harmer
0.804
3145796HORNRTN
Solar/Wind Harmer
0.101
3146033SCOT NK
Solar/Wind Harmer
0.989
970831AG2-522 GEN
Solar/Wind Harmer
10.446
3143316POE
Solar/Wind Harmer
0.965
971445AH1-216 GEN
Solar/Wind Harmer
17.029
316005AA1-067
Solar/Wind Harmer
0.257
3145746EVERETS
Solar/Wind Harmer
0.955
3145746EVERETS
Solar/Wind Harmer
0.24
3145746EVERETS
Solar/Wind Harmer
0.24
3145746EVERETS
Solar/Wind Harmer
0.24
970181AG2-120 GEN
Solar/Wind Harmer
2.987
957861AF2-080 GEN
Solar/Wind Harmer
10.262
316420AA1-050 GEN
Solar/Wind Harmer
0.008
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.236
3145573BETHELC
Solar/Wind Harmer
0.236
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
972265AH1-717 GEN
Adder
17.569
3151201GRAVEL4
Adder
16.47
3151191GRAVEL3
Adder
16.261
3151211GRAVEL5
Adder
16.261
316118AC1-105 GEN
Solar/Wind Harmer
0.578
3147173SINAI
Solar/Wind Harmer
0.223
3147243WELCO
Solar/Wind Harmer
0.14
971443AH1-215 GEN
Solar/Wind Harmer
3.472
3144303KENBRDG
Solar/Wind Harmer
0.165
316369SG1_INVT
Solar/Wind Harmer
0.007
970683AG2-441 GEN
Solar/Wind Harmer
13.122
970681AG2-440 GEN
Solar/Wind Harmer
10.498
970865AG2-541 GEN
Solar/Wind Harmer
6.671
946301AF1-294 GEN
Solar/Wind Harmer
3.715
961791AG1-021 GEN
Solar/Wind Harmer
1.807
3138283WHITEMARSH
Solar/Wind Harmer
0.044
316132AB2-190 GEN1
Solar/Wind Harmer
0.989
315657AE1-056 GEN
Solar/Wind Harmer
6.288
316123AC1-075 GEN
Solar/Wind Harmer
0.235
970165AG2-112 GEN
Solar/Wind Harmer
1.394
970163AG2-111 GEN
Solar/Wind Harmer
1.33
3141873WAN 176
Solar/Wind Harmer
0.031
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.431
316059AD1-063 C
Solar/Wind Harmer
0.001
3141913WHIT STONE
Solar/Wind Harmer
0.147
316314AB2-024 C
Solar/Wind Harmer
0.001
3138133OCRAN
Solar/Wind Harmer
0.044
3143873LANEXA
Solar/Wind Harmer
0.086
3141783LANCAST
Solar/Wind Harmer
0.085
3141783LANCAST
Solar/Wind Harmer
0.057
3142433PROV 92
Adder
0.271
3142433PROV 92
Adder
0.271
971167AH1-042 GEN
Solar/Wind Harmer
12.277
315976AC1-164 GENA
Solar/Wind Harmer
14.222
316169AC1-164_GENC
Solar/Wind Harmer
12.287
315975AC1-164 GENB
Solar/Wind Harmer
0.421
962981AG1-147 GEN
Solar/Wind Harmer
5.038
970327AG2-215 GEN
Solar/Wind Harmer
4.29
316164AC1-076 GEN
Solar/Wind Helper
1.17
3151031BRUNSWICKG2
50/50
4.54
970413AG2-270 GEN
50/50
25.77
3151101ELIZAR3
50/50
26.77
970917AG2-570 GEN
Solar/Wind Harmer
29.34
315773AC2-141 GEN
Solar/Wind Harmer
10.33
944581AF1-123 GEN
Solar/Wind Harmer
62.596
944601AF1-125 GEN
Solar/Wind Harmer
61.631
316478AD1-087 GEN
Solar/Wind Harmer
0.962
316486AD2-202 GEN
Solar/Wind Harmer
0.283
3146456SLIGO L269
Solar/Wind Harmer
0.272
971153AH1-033 GEN
Solar/Wind Harmer
3.148
3144873MCLAUGH
Solar/Wind Harmer
0.007
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.268
3146626S HERTFORD
Solar/Wind Harmer
0.267
316365GEN2_N
Solar/Wind Harmer
0.594
3146376EDENTON
Solar/Wind Harmer
0.263
3144536CHRHLND
Solar/Wind Harmer
0.039
3145273HOLLAND
Solar/Wind Harmer
0.197
315614AA2-178 GEN
Solar/Wind Harmer
1.489
971157AH1-035 GEN
Solar/Wind Harmer
3.091
315737AD1-076 GEN
Solar/Wind Harmer
3.308
3156081AA2-088 GEN
Solar/Wind Harmer
0.006
3146206CASHIE
Solar/Wind Harmer
0.256
3145893MURPHYS
Solar/Wind Harmer
0.427
3145893MURPHYS
Solar/Wind Harmer
0.255
957521AF2-046 GEN
Solar/Wind Harmer
18.955
961681AG1-008 GEN
Solar/Wind Harmer
18.955
313506AB2-031 GEN
Solar/Wind Harmer
0.786
3142666NORTHAMPTON
Solar/Wind Harmer
0.254
3146173TUNIS
Solar/Wind Harmer
0.254
3156021HOLLOMANSOL
Solar/Wind Harmer
1.153
316463AE2-346 GEN
Solar/Wind Harmer
0.218
316140AB2-099
Solar/Wind Harmer
0.091
962331AG1-082 GEN
Solar/Wind Harmer
2.704
3146263WOODLND
Solar/Wind Harmer
0.252
3145796HORNRTN
Solar/Wind Harmer
1.005
3145796HORNRTN
Solar/Wind Harmer
0.251
316317KELFORD C
Solar/Wind Harmer
0.024
3145823KELFORD
Solar/Wind Harmer
0.25
3145963POPLR C
Solar/Wind Harmer
0.249
3147043LAWRENC
Solar/Wind Harmer
0.149
316210AC1-098 GEN
Solar/Wind Harmer
2.273
970661AG2-428 GEN
Solar/Wind Harmer
5.16
3145336SMITFLD
Solar/Wind Harmer
0.097
3145933PARMELE
Solar/Wind Harmer
0.243
966801AG1-551 GEN
Solar/Wind Harmer
2.83
315724AD1-057 GEN
Solar/Wind Harmer
0.908
3145746EVERETS
Solar/Wind Harmer
0.24
3145746EVERETS
Solar/Wind Harmer
0.24
316327AA2-057 GEN
Solar/Wind Harmer
0.362
316083AB2-161 GEN
Solar/Wind Harmer
0.003
970659AG2-427 GEN
Solar/Wind Harmer
2.515
3146233WITAKRS
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.161
3138543CONSLDL
Solar/Wind Harmer
0.156
3146073TAR RVR
Solar/Wind Harmer
0.236
3146083TARBORO
Solar/Wind Harmer
0.236
961601AG1-000A GEN
Solar/Wind Harmer
16.657
3145543BTLEBRO
Solar/Wind Harmer
0.234
3145543BTLEBRO
Solar/Wind Harmer
0.234
971623AH1-311 GEN
Solar/Wind Harmer
0.468
315813AE1-149 C
Solar/Wind Harmer
12.227
3151221GRAVEL6
Adder
16.451
3151171GRAVELC
Adder
3.165
316131AB2-060 GEN
Solar/Wind Harmer
0.707
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.527
3144216WINCHST
Adder
0.83
964241AG1-285 GEN
Solar/Wind Harmer
14.603
3150921YORKTN3
Adder
5.498
961611AG1-000B GEN
Solar/Wind Harmer
5.762
315785AD2-033 C
Solar/Wind Harmer
1.703
316283AC2-100 C
Solar/Wind Harmer
0.406
970257AG2-171 GEN
Solar/Wind Harmer
6.589
959311AF2-222 GEN
Solar/Wind Harmer
18.071
971683AH1-343 GEN
Solar/Wind Harmer
7.451
315839AE2-212 C
Solar/Wind Harmer
0.002
970909AG2-566 GEN
Solar/Wind Harmer
2.128
315778AD1-151 GEN
Solar/Wind Harmer
15.484
316382AG1-145 C
Solar/Wind Harmer
0.002
965281AG1-393 GEN
Solar/Wind Harmer
2.04
963181AG1-167 GEN
Solar/Wind Harmer
0.753
3144293JTRSVLE
Adder
0.599
970129AG2-093 GEN
Solar/Wind Harmer
11.049
3147133PAMPLIN
Solar/Wind Harmer
0.572
971193AH1-056 GEN
Solar/Wind Harmer
11.101
970133AG2-095 GEN
Solar/Wind Harmer
1.61
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316156AD2-030 GEN
Solar/Wind Harmer
0.114
3141873WAN 176
Solar/Wind Harmer
2.731
316280AD1-041 GEN
Solar/Wind Harmer
0.003
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141843SHACKLE
Adder
0.764
3141766HARMONY
Solar/Wind Harmer
1.984
3146926FARMVIL
Solar/Wind Harmer
0.088
3142433PROV 92
Adder
0.271
3142433PROV 92
Adder
0.271
962971AG1-146 GEN
Solar/Wind Harmer
2.159
3142946ENON
Solar/Wind Harmer
0.044
970009AG2-005 GEN
Solar/Wind Harmer
0.976
316404AE1-155 C
Solar/Wind Harmer
0.028
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
0.766
316044AC1-158 PL1
Solar/Wind Helper
1.631
316450AC1-158 RIC
Solar/Wind Helper
0.435
3147666LOUISA
Solar/Wind Helper
0.576
316170AC1-121 GEN2
Solar/Wind Helper
0.345
LAGNLTFEXP_LAGN->PJM
CLTF
11.265
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.702
TVALTFEXP_TVA->PJM
CLTF
5.645
NYPJM->LTFIMP_NY
CLTF
2.873
LGEELTFEXP_LGEE->PJM
CLTF
2
WECLTFEXP_WEC->PJM
CLTF
1.023
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.7
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.348
MECLTFEXP_MEC->PJM
CLTF
5.484
SIGELTFEXP_SIGE->PJM
CLTF
0.165
CPLELTFEXP_CPLE->PJM
CLTF
15.998
CBM West 2LTFEXP_CBM-W2->PJM
CBM
59.498

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.51 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4106.24
MW Contribution:4.67
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
4.652
3151101ELIZAR3
50/50
28.63
3151161SURRY 1
50/50
9.069
970917AG2-570 GEN
Solar/Wind Harmer
30.012
315773AC2-141 GEN
Solar/Wind Harmer
11.237
944581AF1-123 GEN
Solar/Wind Harmer
67.152
944601AF1-125 GEN
Solar/Wind Harmer
66.117
3146456SLIGO L269
Solar/Wind Harmer
0.291
971153AH1-033 GEN
Solar/Wind Harmer
3.361
3144873MCLAUGH
Solar/Wind Harmer
0.007
316320Y1-086
Solar/Wind Harmer
0.002
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.284
3146626S HERTFORD
Solar/Wind Harmer
0.282
3144536CHRHLND
Solar/Wind Harmer
0.042
316478AD1-087 GEN
Solar/Wind Harmer
0.973
316486AD2-202 GEN
Solar/Wind Harmer
0.286
3146376EDENTON
Solar/Wind Harmer
0.278
3145273HOLLAND
Solar/Wind Harmer
0.207
315614AA2-178 GEN
Solar/Wind Harmer
1.563
971157AH1-035 GEN
Solar/Wind Harmer
3.233
315737AD1-076 GEN
Solar/Wind Harmer
3.457
316365GEN2_N
Solar/Wind Harmer
0.603
3146206CASHIE
Solar/Wind Harmer
0.266
3156081AA2-088 GEN
Solar/Wind Harmer
0.006
3145893MURPHYS
Solar/Wind Harmer
0.442
3145893MURPHYS
Solar/Wind Harmer
0.264
957521AF2-046 GEN
Solar/Wind Harmer
19.615
961681AG1-008 GEN
Solar/Wind Harmer
19.615
3156021HOLLOMANSOL
Solar/Wind Harmer
1.195
3146173TUNIS
Solar/Wind Harmer
0.263
316463AE2-346 GEN
Solar/Wind Harmer
0.225
316140AB2-099
Solar/Wind Harmer
0.094
962331AG1-082 GEN
Solar/Wind Harmer
2.796
3146263WOODLND
Solar/Wind Harmer
0.26
3142666NORTHAMPTON
Solar/Wind Harmer
0.259
3145963POPLR C
Solar/Wind Harmer
0.259
313506AB2-031 GEN
Solar/Wind Harmer
0.799
316317KELFORD C
Solar/Wind Harmer
0.025
3145823KELFORD
Solar/Wind Harmer
0.257
3145336SMITFLD
Solar/Wind Harmer
0.103
3145796HORNRTN
Solar/Wind Harmer
1.024
3145796HORNRTN
Solar/Wind Harmer
0.256
316210AC1-098 GEN
Solar/Wind Harmer
2.325
3145933PARMELE
Solar/Wind Harmer
0.25
966801AG1-551 GEN
Solar/Wind Harmer
2.914
3147043LAWRENC
Solar/Wind Harmer
0.15
970661AG2-428 GEN
Solar/Wind Harmer
5.262
3145746EVERETS
Solar/Wind Harmer
0.246
3145746EVERETS
Solar/Wind Harmer
0.246
315724AD1-057 GEN
Solar/Wind Harmer
0.923
316327AA2-057 GEN
Solar/Wind Harmer
0.368
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3146233WITAKRS
Solar/Wind Harmer
1.209
3146233WITAKRS
Solar/Wind Harmer
0.164
3146073TAR RVR
Solar/Wind Harmer
0.241
3146083TARBORO
Solar/Wind Harmer
0.241
3138543CONSLDL
Solar/Wind Harmer
0.159
970659AG2-427 GEN
Solar/Wind Harmer
2.534
3144216WINCHST
Adder
0.899
3150921YORKTN3
Adder
5.993
961601AG1-000A GEN
Solar/Wind Harmer
16.907
3145543BTLEBRO
Solar/Wind Harmer
0.237
3145543BTLEBRO
Solar/Wind Harmer
0.237
971623AH1-311 GEN
Solar/Wind Harmer
0.475
3151221GRAVEL6
Adder
17.166
3151171GRAVELC
Adder
3.303
315813AE1-149 C
Solar/Wind Harmer
12.107
316131AB2-060 GEN
Solar/Wind Harmer
0.706
961611AG1-000B GEN
Solar/Wind Harmer
5.941
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.493
964241AG1-285 GEN
Solar/Wind Harmer
14.533
316382AG1-145 C
Solar/Wind Harmer
0.002
315785AD2-033 C
Solar/Wind Harmer
1.686
316283AC2-100 C
Solar/Wind Harmer
0.405
970257AG2-171 GEN
Solar/Wind Harmer
6.511
959311AF2-222 GEN
Solar/Wind Harmer
17.832
971683AH1-343 GEN
Solar/Wind Harmer
7.341
970909AG2-566 GEN
Solar/Wind Harmer
2.087
315778AD1-151 GEN
Solar/Wind Harmer
15.465
315839AE2-212 C
Solar/Wind Harmer
0.001
963181AG1-167 GEN
Solar/Wind Harmer
0.736
3144293JTRSVLE
Adder
0.586
965281AG1-393 GEN
Solar/Wind Harmer
1.915
970129AG2-093 GEN
Solar/Wind Harmer
10.834
3147133PAMPLIN
Solar/Wind Harmer
0.557
971193AH1-056 GEN
Solar/Wind Harmer
10.805
316156AD2-030 GEN
Solar/Wind Harmer
0.122
3141873WAN 176
Solar/Wind Harmer
2.94
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
2.131
970133AG2-095 GEN
Solar/Wind Harmer
1.531
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141843SHACKLE
Adder
0.813
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
962971AG1-146 GEN
Solar/Wind Harmer
2.345
970009AG2-005 GEN
Solar/Wind Harmer
1.063
3142433PROV 92
Adder
0.27
3142433PROV 92
Adder
0.27
3146926FARMVIL
Solar/Wind Harmer
0.083
316404AE1-155 C
Solar/Wind Harmer
0.031
3142946ENON
Solar/Wind Harmer
0.043
3150351NORNECKC2
Adder
1.248
316044AC1-158 PL1
Solar/Wind Helper
1.377
316450AC1-158 RIC
Solar/Wind Helper
0.367
3147666LOUISA
Solar/Wind Helper
0.517
315244AE2-183_ST
50/50
10.261
963041AG1-153 GEN
50/50
9.42
3151081ELIZAR1
50/50
28.268
3151091ELIZAR2
50/50
27.777
941591AE2-156 GEN
50/50
25.77
3152611GOSPORTB
50/50
3.91
3152621GOSPORTC
50/50
3.319
3152601GOSPORTA
50/50
3.061
315779AE2-040
50/50
4.021
941031AE2-094 GEN
Solar/Wind Harmer
68.698
944011AF1-069 GEN
Solar/Wind Harmer
22.446
970673AG2-436 GEN
Solar/Wind Harmer
77.635
970673AG2-436 GEN
Solar/Wind Harmer
51.757
971967AH1-528 GEN
Solar/Wind Harmer
56.624
970085AG2-068 GEN
Solar/Wind Harmer
17.915
970581AG2-369 GEN
Solar/Wind Harmer
15.406
957871AF2-081 GEN
Solar/Wind Harmer
14.506
319010AE1-072 C
Solar/Wind Harmer
1.463
3146406KITTY HAWK
Solar/Wind Harmer
0.036
316315AB2-025 C
Solar/Wind Harmer
0.233
313526AB2-022
Solar/Wind Harmer
0.156
316305AF2-043 C
Solar/Wind Harmer
0.002
315814AE2-033 C
Solar/Wind Harmer
22.713
316321Z2-027
Solar/Wind Harmer
0.053
3146396TANGLEW
Solar/Wind Harmer
0.79
3145176PASQUOTANK
Solar/Wind Harmer
0.178
3146486SUNBURY
Solar/Wind Harmer
0.285
3146486SUNBURY
Solar/Wind Harmer
0.285
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
315835AF2-110_GEN
Solar/Wind Harmer
1.923
3130156CHOWAN
Solar/Wind Harmer
0.278
3130156CHOWAN
Solar/Wind Harmer
0.278
315816AE2-034 GEN
Solar/Wind Harmer
1.172
3130546PLYMOUTH
Solar/Wind Harmer
0.269
315732AD1-074 GEN1
Solar/Wind Harmer
1.544
315733AD1-074 GEN2
Solar/Wind Harmer
1.544
315735AD1-075 GEN1
Solar/Wind Harmer
0.773
3146206CASHIE
Solar/Wind Harmer
0.266
970601AG2-382 GEN
Solar/Wind Harmer
9.949
316311AC2-079 GEN
Solar/Wind Harmer
7.631
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.182
970533AG2-339 GEN
50/50
33.155
970531AG2-338 GEN
50/50
13.262
315242AE2-183_GT2
50/50
5.935
315241AE2-183_GT1
50/50
5.899
972185AH1-677 GEN
50/50
21.397
3151041BRUNSWICKG3
50/50
4.652
972187AH1-678 GEN
50/50
10.676
3150991CHESPKB
50/50
3.216
3150991CHESPKB
50/50
3.139
970933AG2-581 GEN
Solar/Wind Harmer
26.986
970099AG2-077 GEN
Solar/Wind Harmer
31.582
316185AD1-033 GEN
Solar/Wind Harmer
0.008
3145506HICKORY
Solar/Wind Harmer
1.17
3145506HICKORY
Solar/Wind Harmer
0.702
3145506HICKORY
Solar/Wind Harmer
0.176
316339AD2-160 GEN
Solar/Wind Harmer
0.473
3142956BIRDNECK
Solar/Wind Harmer
0
316018AA1-139 ULT2
Solar/Wind Harmer
0.007
316017AA1-139 ULT1
Solar/Wind Harmer
0.163
316316AC1-027 C
Solar/Wind Harmer
0.279
3137176SLIGO L2192
Solar/Wind Harmer
1.157
3146456SLIGO L269
Solar/Wind Harmer
5.145
3130086AYDLETT
Solar/Wind Harmer
1.161
316036AC1-147 C
Solar/Wind Harmer
0.054
3144356SAPONY
Solar/Wind Harmer
2.41
3146386ELIZ CT
Solar/Wind Harmer
0.288
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.284
3146516WINFALL
Solar/Wind Harmer
0.284
3146516WINFALL
Solar/Wind Harmer
0.284
3146626S HERTFORD
Solar/Wind Harmer
0.282
3146626S HERTFORD
Solar/Wind Harmer
0.282
3146376EDENTON
Solar/Wind Harmer
1.235
3146376EDENTON
Solar/Wind Harmer
1.235
315742AE1-103 GEN
Solar/Wind Harmer
0.003
316065AD1-022 GEN
Solar/Wind Harmer
12.307
3145893MURPHYS
Solar/Wind Harmer
1.766
3145893MURPHYS
Solar/Wind Harmer
0.475
3146173TUNIS
Solar/Wind Harmer
0.263
3146173TUNIS
Solar/Wind Harmer
0.263
3142666NORTHAMPTON
Solar/Wind Harmer
0.259
3142666NORTHAMPTON
Solar/Wind Harmer
0.259
3142666NORTHAMPTON
Solar/Wind Harmer
0.259
3142666NORTHAMPTON
Solar/Wind Harmer
0.156
316181AB2-040 GEN
Solar/Wind Harmer
0.375
316426AA2-053 GEN
Solar/Wind Harmer
0.869
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3145593CAROLNA
Solar/Wind Harmer
0.256
3145593CAROLNA
Solar/Wind Harmer
0.256
966811AG1-552 GEN
Solar/Wind Harmer
2.78
3145593CAROLNA
Solar/Wind Harmer
0.319
3145796HORNRTN
Solar/Wind Harmer
0.768
3145783HORNRTN
Solar/Wind Harmer
4.537
3145783HORNRTN
Solar/Wind Harmer
3.63
3145783HORNRTN
Solar/Wind Harmer
1.134
3145783HORNRTN
Solar/Wind Harmer
0.454
3145933PARMELE
Solar/Wind Harmer
0.5
3145933PARMELE
Solar/Wind Harmer
0.25
316274AC1-208 GEN
Solar/Wind Harmer
1.294
970657AG2-426 GEN
Solar/Wind Harmer
8.563
970657AG2-426 GEN
Solar/Wind Harmer
1.795
3145493TOT1
Solar/Wind Harmer
0.558
3145453TOT5
Solar/Wind Harmer
0.335
3145603CNETO
Solar/Wind Harmer
0.223
939181AE1-148 GEN
Solar/Wind Harmer
11.474
961601AG1-000A GEN
Solar/Wind Harmer
4.227
316263AC1-034 GEN
Solar/Wind Harmer
9.031
313527AB2-043 GEN
Solar/Wind Harmer
0.003
962561AG1-105 GEN
Solar/Wind Harmer
10.764
964791AG1-342 GEN
Solar/Wind Harmer
4.3
3146843MT LREL
Solar/Wind Harmer
0.224
3146843MT LREL
Solar/Wind Harmer
0.224
971741AH1-377 GEN
Solar/Wind Harmer
21.186
316222AC1-221 GEN
Solar/Wind Harmer
0.863
970323AG2-213 GEN
Solar/Wind Harmer
8.682
971775AH1-396 GEN
Solar/Wind Harmer
0.326
316034AC1-036 C
Solar/Wind Harmer
0.015
316033AB2-134 GEN
Solar/Wind Harmer
0.012
315697AD1-025 GEN
Solar/Wind Harmer
0.227
970301AG2-198 GEN
Solar/Wind Harmer
8.347
958211AF2-115 GEN
Solar/Wind Harmer
2.208
963191AG1-168 GEN
Solar/Wind Harmer
0.736
3144293JTRSVLE
Adder
0.586
3144293JTRSVLE
Adder
0.493
3147133PAMPLIN
Solar/Wind Harmer
0.177
3147133PAMPLIN
Solar/Wind Harmer
0.142
316240AF1-291 C
Solar/Wind Harmer
0.001
942751AE2-291 GEN
Solar/Wind Harmer
8.242
944641AF1-129 GEN
Adder
69.44
958261AF2-120 GEN
Solar/Wind Harmer
4.48
3142946ENON
Solar/Wind Harmer
0.013
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.29
3150341NORNECKC1
Adder
1.279
270013AE1-250 PV
Solar/Wind Harmer
0.004
316075AC2-137 C
Solar/Wind Harmer
0.031
316447AC1-158 HLD
Solar/Wind Helper
3.03
965291AG1-394 GEN
Solar/Wind Harmer
1.178
3145893MURPHYS
Solar/Wind Harmer
0.712
3145893MURPHYS
Solar/Wind Harmer
0.264
3145513AHOSKIE
Solar/Wind Harmer
0.548
3145513AHOSKIE
Solar/Wind Harmer
0.262
3145683EARLEYS
Solar/Wind Harmer
0.523
3145683EARLEYS
Solar/Wind Harmer
0.261
3145683EARLEYS
Solar/Wind Harmer
0.261
3146043SEABORD
Solar/Wind Harmer
0.26
315607AA1-063A GEN
Solar/Wind Harmer
0.531
315652AC1-086 GEN
Solar/Wind Harmer
28.501
316087AB2-174 GEN
Solar/Wind Harmer
0.007
3137643SOCKMAN
Solar/Wind Harmer
1.028
3145796HORNRTN
Solar/Wind Harmer
0.819
3145796HORNRTN
Solar/Wind Harmer
0.102
971445AH1-216 GEN
Solar/Wind Harmer
17.94
3146033SCOT NK
Solar/Wind Harmer
1.015
970831AG2-522 GEN
Solar/Wind Harmer
10.575
316005AA1-067
Solar/Wind Harmer
0.264
3145746EVERETS
Solar/Wind Harmer
0.98
3145746EVERETS
Solar/Wind Harmer
0.246
3145746EVERETS
Solar/Wind Harmer
0.246
3145746EVERETS
Solar/Wind Harmer
0.246
970181AG2-120 GEN
Solar/Wind Harmer
3.065
957861AF2-080 GEN
Solar/Wind Harmer
10.491
316420AA1-050 GEN
Solar/Wind Harmer
0.008
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.241
3145573BETHELC
Solar/Wind Harmer
0.241
3143316POE
Solar/Wind Harmer
0.943
972265AH1-717 GEN
Adder
18.333
3151201GRAVEL4
Adder
17.186
3151191GRAVEL3
Adder
16.968
3151211GRAVEL5
Adder
16.968
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.576
3147173SINAI
Solar/Wind Harmer
0.222
3147243WELCO
Solar/Wind Harmer
0.139
971443AH1-215 GEN
Solar/Wind Harmer
3.433
3138283WHITEMARSH
Solar/Wind Harmer
0.047
3144303KENBRDG
Solar/Wind Harmer
0.163
316369SG1_INVT
Solar/Wind Harmer
0.008
970683AG2-441 GEN
Solar/Wind Harmer
12.898
970681AG2-440 GEN
Solar/Wind Harmer
10.318
970865AG2-541 GEN
Solar/Wind Harmer
6.531
946301AF1-294 GEN
Solar/Wind Harmer
3.631
961791AG1-021 GEN
Solar/Wind Harmer
1.767
316132AB2-190 GEN1
Solar/Wind Harmer
0.972
315657AE1-056 GEN
Solar/Wind Harmer
6.12
316123AC1-075 GEN
Solar/Wind Harmer
0.227
970165AG2-112 GEN
Solar/Wind Harmer
1.344
970163AG2-111 GEN
Solar/Wind Harmer
1.282
3141873WAN 176
Solar/Wind Harmer
0.033
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.717
3141913WHIT STONE
Solar/Wind Harmer
0.159
3138133OCRAN
Solar/Wind Harmer
0.047
316314AB2-024 C
Solar/Wind Harmer
0.001
3141783LANCAST
Solar/Wind Harmer
0.092
3141783LANCAST
Solar/Wind Harmer
0.062
3143873LANEXA
Solar/Wind Harmer
0.09
962981AG1-147 GEN
Solar/Wind Harmer
5.473
315976AC1-164 GENA
Solar/Wind Harmer
14.998
316169AC1-164_GENC
Solar/Wind Harmer
12.957
315975AC1-164 GENB
Solar/Wind Harmer
0.444
970327AG2-215 GEN
Solar/Wind Harmer
4.671
3142433PROV 92
Adder
0.27
3142433PROV 92
Adder
0.27
971167AH1-042 GEN
Solar/Wind Harmer
12.111
3141813NORNECK
Solar/Wind Harmer
0.123
315243AE2-183_GT3
50/50
5.935
3151051BRUNSWICKS1
50/50
9.655
3151021BRUNSWICKG1
50/50
4.652
971451AH1-221 GEN
50/50
14.13
3150981CHESPKA
50/50
3.834
3152331SURRY 2
50/50
11.817
940641AE2-051 GEN
Solar/Wind Harmer
30.066
939411AE1-173 GEN
Solar/Wind Harmer
151.643
970919AG2-571 GEN
Solar/Wind Harmer
12.005
970087AG2-069 GEN
Solar/Wind Harmer
26.872
316294AC1-161 GEN
Solar/Wind Harmer
5.331
944591AF1-124 GEN
Solar/Wind Harmer
67.391
957481AF2-042 GEN
Solar/Wind Harmer
78.955
316388AE2-253 GEN
Solar/Wind Harmer
0.914
3146456SLIGO L269
Solar/Wind Harmer
0.291
316375AC2-012 GEN
Solar/Wind Harmer
0.007
316246AF1-032 C
Solar/Wind Harmer
0.129
3146516WINFALL
Solar/Wind Harmer
0.92
3146516WINFALL
Solar/Wind Harmer
0.284
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
316093AE2-104_GEN
Solar/Wind Harmer
4.713
3130156CHOWAN
Solar/Wind Harmer
0.278
316072AD1-144
Solar/Wind Harmer
0.1
315693AD1-088 GEN
Solar/Wind Harmer
13.144
3145663CRESWEL
Solar/Wind Harmer
0.764
971163AH1-040 GEN
Solar/Wind Harmer
21.847
962491AG1-098 GEN
Solar/Wind Harmer
15.396
316023GEN1_S
Solar/Wind Harmer
0.603
3146206CASHIE
Solar/Wind Harmer
0.266
971547AH1-271 GEN
Solar/Wind Harmer
5.685
3145893MURPHYS
Solar/Wind Harmer
1.055
3145893MURPHYS
Solar/Wind Harmer
1.173
3146173TUNIS
Solar/Wind Harmer
0.263
3145683EARLEYS
Solar/Wind Harmer
0.261
960081AF2-299 GEN
Solar/Wind Harmer
2.502
3146263WOODLND
Solar/Wind Harmer
0.26
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316011AB1-132 GEN
Solar/Wind Harmer
4.711
962571AG1-106 GEN
Solar/Wind Harmer
3.686
3145963POPLR C
Solar/Wind Harmer
0.259
3145823KELFORD
Solar/Wind Harmer
0.257
316190AA2-174 GEN
Solar/Wind Harmer
0
316174AB2-169 GEN
Solar/Wind Harmer
0.007
3145336SMITFLD
Solar/Wind Harmer
1.026
3145796HORNRTN
Solar/Wind Harmer
0.844
3145796HORNRTN
Solar/Wind Harmer
0.256
3145783HORNRTN
Solar/Wind Harmer
0.255
971795AH1-408 GEN
Solar/Wind Harmer
16.891
316212AC1-099_GEN
Solar/Wind Harmer
1.297
3146293MARTNCO
Solar/Wind Harmer
0.232
3147043LAWRENC
Adder
2.262
970661AG2-428 GEN
Solar/Wind Harmer
24.74
316129AC1-054 GEN
Solar/Wind Harmer
0.929
3145746EVERETS
Solar/Wind Harmer
0.246
3145746EVERETS
Solar/Wind Harmer
0.246
971065AG2-659 GEN
Solar/Wind Harmer
10.5
315722AD1-056 GEN
Solar/Wind Harmer
1.557
316494AC1-189 GEN
Solar/Wind Harmer
0.822
316381AD1-082 GEN
Solar/Wind Harmer
0.252
3146233WITAKRS
Solar/Wind Harmer
0.958
961671AG1-007 GEN
Solar/Wind Harmer
0.037
3146083TARBORO
Solar/Wind Harmer
0.241
3145493TOT1
Solar/Wind Harmer
1.07
970659AG2-427 GEN
Solar/Wind Harmer
11.585
3138126ROCKLANDING
Solar/Wind Harmer
0.109
316359AB2-059 GEN
Solar/Wind Harmer
0.854
316049AB1-081 GEN
Solar/Wind Harmer
1.36
3145543BTLEBRO
Solar/Wind Harmer
0.237
3145543BTLEBRO
Solar/Wind Harmer
0.19
3142053HEARTS
Solar/Wind Harmer
0.418
3151171GRAVELC
Adder
2.512
316237AB2-079_GEN
Solar/Wind Harmer
0.002
971317AH1-138 GEN
Solar/Wind Harmer
1.684
970401AG2-262 GEN
Solar/Wind Harmer
1.314
961611AG1-000B GEN
Solar/Wind Harmer
11.683
971647AH1-324 GEN
Solar/Wind Harmer
9.052
316003AC1-222 GEN
Solar/Wind Harmer
0.006
316159AE1-175 C
Solar/Wind Harmer
0.18
970685AG2-442 GEN
Solar/Wind Harmer
14.446
971069AG2-661 GEN
Solar/Wind Harmer
3.437
963171AG1-166 GEN
Solar/Wind Harmer
0.981
971563AH1-280 GEN
Solar/Wind Harmer
1.963
3144293JTRSVLE
Adder
0.586
316458AB2-190 GEN2
Solar/Wind Harmer
0.972
970129AG2-093 GEN
Solar/Wind Harmer
5.098
315671AE2-027_GEN
Solar/Wind Harmer
10.946
3141766HARMONY
Solar/Wind Harmer
0.032
971777AH1-397 GEN
Solar/Wind Harmer
0.42
3141843SHACKLE
Adder
0.813
3138133OCRAN
Solar/Wind Harmer
0.094
3142433PROV 92
Solar/Wind Harmer
0.556
3142433PROV 92
Adder
0.27
3142433PROV 92
Adder
0.27
3146926FARMVIL
Solar/Wind Harmer
0.083
962861AG1-135 GEN
Solar/Wind Harmer
4.393
970223AG2-152 GEN
Solar/Wind Harmer
8.982
3141726DUNNSVL
Solar/Wind Harmer
0.502
3150351NORNECKC2
Adder
1.228
944631AF1-128 GEN
Adder
58.491
270016AE1-250 BESS
Solar/Wind Harmer
0.004
3143226MDLTHAN
Solar/Wind Helper
0.258
316045AC1-158 PL2
Solar/Wind Helper
4.407
3147666LOUISA
Solar/Wind Helper
0.898
LAGNLTFEXP_LAGN->PJM
CLTF
10.308
CBM South 2LTFEXP_CBM-S2->PJM
CBM
33.823
TVALTFEXP_TVA->PJM
CLTF
5.142
NYPJM->LTFIMP_NY
CLTF
2.512
LGEELTFEXP_LGEE->PJM
CLTF
1.654
WECLTFEXP_WEC->PJM
CLTF
0.847
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.267
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.46
MECLTFEXP_MEC->PJM
CLTF
4.698
SIGELTFEXP_SIGE->PJM
CLTF
0.139
CPLELTFEXP_CPLE->PJM
CLTF
15.903
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.081

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:132.78 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5404.52
MW Contribution:7.22
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
14.578
970497AG2-320 GEN
50/50
26.215
3150401LDYSMT4
50/50
37.246
3150371LDYSMT1
50/50
35.99
315051AA1-145 CT1
50/50
2.03
316044AC1-158 PL1
Solar/Wind Harmer
1.523
316450AC1-158 RIC
Solar/Wind Harmer
0.406
3142416OLDCHRC
Solar/Wind Harmer
2.415
970293AG2-193 GEN
Solar/Wind Harmer
2.624
3143096IRON208
Adder
1.025
3143096IRON208
Adder
1.004
3150861SPRUNCD
Adder
1.127
316473AC1-191 GEN
Solar/Wind Harmer
0.822
3142946ENON
Solar/Wind Harmer
0.081
970133AG2-095 GEN
Solar/Wind Harmer
2.304
316382AG1-145 C
Solar/Wind Harmer
0.002
970129AG2-093 GEN
Solar/Wind Harmer
14.433
315778AD1-151 GEN
Solar/Wind Harmer
19.035
965281AG1-393 GEN
Solar/Wind Harmer
2.538
315839AE2-212 C
Solar/Wind Harmer
0.002
3150921YORKTN3
Adder
5.938
3144216WINCHST
Adder
0.891
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
961611AG1-000B GEN
Solar/Wind Harmer
6.298
315773AC2-141 GEN
Solar/Wind Harmer
8.598
3151221GRAVEL6
Adder
17.114
3151171GRAVELC
Adder
3.293
3145336SMITFLD
Solar/Wind Harmer
0.094
315813AE1-149 C
Solar/Wind Harmer
12.5
3144536CHRHLND
Solar/Wind Harmer
0.035
970659AG2-427 GEN
Solar/Wind Harmer
2.464
944581AF1-123 GEN
Solar/Wind Harmer
52.379
944601AF1-125 GEN
Solar/Wind Harmer
51.572
3151101ELIZAR3
Adder
21.599
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3144873MCLAUGH
Solar/Wind Harmer
0.006
3141766HARMONY
Solar/Wind Harmer
3.092
970661AG2-428 GEN
Solar/Wind Harmer
4.905
3141843SHACKLE
Adder
1.184
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.005
316156AD2-030 GEN
Solar/Wind Harmer
0.17
3141873WAN 176
Solar/Wind Harmer
4.089
3146456SLIGO L269
Solar/Wind Harmer
0.23
971153AH1-033 GEN
Solar/Wind Harmer
2.655
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.224
3146626S HERTFORD
Solar/Wind Harmer
0.223
3145273HOLLAND
Solar/Wind Harmer
0.166
962971AG1-146 GEN
Solar/Wind Harmer
3.551
970009AG2-005 GEN
Solar/Wind Harmer
1.644
3146376EDENTON
Solar/Wind Harmer
0.218
316404AE1-155 C
Solar/Wind Harmer
0.049
315614AA2-178 GEN
Solar/Wind Harmer
1.22
3150351NORNECKC2
Adder
2.148
971781AH1-399 GEN
Solar/Wind Harmer
0.278
316313AB2-026
Solar/Wind Harmer
0.133
316258AE1-075 C
Solar/Wind Harmer
0.159
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
3.185
971157AH1-035 GEN
Solar/Wind Harmer
2.514
315737AD1-076 GEN
Solar/Wind Harmer
2.686
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
970917AG2-570 GEN
Solar/Wind Harmer
18.383
3146206CASHIE
Solar/Wind Harmer
0.206
316365GEN2_N
Solar/Wind Harmer
0.463
3145893MURPHYS
Solar/Wind Harmer
0.344
3145893MURPHYS
Solar/Wind Harmer
0.206
957521AF2-046 GEN
Solar/Wind Harmer
15.264
961681AG1-008 GEN
Solar/Wind Harmer
15.264
3146173TUNIS
Solar/Wind Harmer
0.204
3156021HOLLOMANSOL
Solar/Wind Harmer
0.924
316463AE2-346 GEN
Solar/Wind Harmer
0.174
316140AB2-099
Solar/Wind Harmer
0.072
962331AG1-082 GEN
Solar/Wind Harmer
2.163
3147666LOUISA
Solar/Wind Harmer
0.462
3146263WOODLND
Solar/Wind Harmer
0.2
3145963POPLR C
Solar/Wind Harmer
0.199
313506AB2-031 GEN
Solar/Wind Harmer
0.614
3142666NORTHAMPTON
Solar/Wind Harmer
0.198
316317KELFORD C
Solar/Wind Harmer
0.019
3145823KELFORD
Solar/Wind Harmer
0.198
3145796HORNRTN
Solar/Wind Harmer
0.778
3145796HORNRTN
Solar/Wind Harmer
0.195
3147043LAWRENC
Solar/Wind Harmer
0.117
3141906WESTMOR
Solar/Wind Harmer
0.077
316478AD1-087 GEN
Solar/Wind Harmer
0.667
316486AD2-202 GEN
Solar/Wind Harmer
0.196
316210AC1-098 GEN
Solar/Wind Harmer
1.765
3145933PARMELE
Solar/Wind Harmer
0.19
966801AG1-551 GEN
Solar/Wind Harmer
2.213
3145746EVERETS
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
0.186
315724AD1-057 GEN
Solar/Wind Harmer
0.693
970737AG2-469 GEN
Solar/Wind Harmer
7.863
970909AG2-566 GEN
Solar/Wind Harmer
1.962
316327AA2-057 GEN
Solar/Wind Harmer
0.277
3146073TAR RVR
Solar/Wind Harmer
0.18
3146083TARBORO
Solar/Wind Harmer
0.18
3146233WITAKRS
Solar/Wind Harmer
0.903
3146233WITAKRS
Solar/Wind Harmer
0.122
316131AB2-060 GEN
Solar/Wind Harmer
0.565
3138543CONSLDL
Solar/Wind Harmer
0.118
964241AG1-285 GEN
Solar/Wind Harmer
11.97
315785AD2-033 C
Solar/Wind Harmer
1.456
970257AG2-171 GEN
Solar/Wind Harmer
5.726
959311AF2-222 GEN
Solar/Wind Harmer
15.895
963181AG1-167 GEN
Solar/Wind Harmer
0.712
3144293JTRSVLE
Adder
0.567
3147133PAMPLIN
Solar/Wind Harmer
0.558
971193AH1-056 GEN
Solar/Wind Harmer
10.829
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
961601AG1-000A GEN
Solar/Wind Harmer
12.564
3145543BTLEBRO
Solar/Wind Harmer
0.176
3145543BTLEBRO
Solar/Wind Harmer
0.176
971623AH1-311 GEN
Solar/Wind Harmer
0.353
3146926FARMVIL
Solar/Wind Harmer
0.106
3146776BUCKING
Solar/Wind Harmer
0.061
972255AH1-712 GEN
Adder
84.412
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
6.993
971683AH1-343 GEN
Solar/Wind Harmer
5.591
970221AG2-151 GEN
Solar/Wind Harmer
8.062
316283AC2-100 C
Solar/Wind Harmer
0.29
3132273ORANGE
Solar/Wind Harmer
0.028
3141316ARNOLDS
Adder
0.324
3150331BIRCHWDA
Adder
21.287
3151761LOISA E
Adder
16.391
316170AC1-121 GEN2
Solar/Wind Harmer
0.131
972183AH1-676 GEN
Adder
128.276
3141196NOKESVL
Solar/Wind Helper
1.252
3150391LDYSMT3
50/50
37.176
972195AH1-682 GEN
50/50
4.885
316447AC1-158 HLD
Solar/Wind Harmer
3.348
315673AE1-157 GEN
Solar/Wind Harmer
17.981
957411AF2-035 GEN
Solar/Wind Harmer
11.052
970317AG2-208 GEN
Solar/Wind Harmer
10.239
3142296MT RD221
Adder
0.803
3142366NRTHEST
Adder
0.809
3150691DARBY 3
Adder
17.772
3150701DARBY 4
Adder
17.73
3150681DARBY 2
Adder
17.71
3150671DARBY 1
Adder
17.689
3143526WINTERP
Solar/Wind Harmer
1.273
316075AC2-137 C
Solar/Wind Harmer
0.067
971223AH1-071 GEN
Solar/Wind Harmer
2.604
966871AG1-558 GEN
Solar/Wind Harmer
0.281
3142946ENON
Solar/Wind Harmer
0.024
944641AF1-129 GEN
Adder
114.635
316240AF1-291 C
Solar/Wind Harmer
0.002
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.267
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316036AC1-147 C
Solar/Wind Harmer
0.043
3150991CHESPKB
Adder
2.436
3150991CHESPKB
Adder
2.378
970657AG2-426 GEN
Solar/Wind Harmer
8.137
970657AG2-426 GEN
Solar/Wind Harmer
1.706
316316AC1-027 C
Solar/Wind Harmer
0.223
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.007
3145506HICKORY
Solar/Wind Harmer
0.925
3145506HICKORY
Solar/Wind Harmer
0.555
3145506HICKORY
Solar/Wind Harmer
0.139
316339AD2-160 GEN
Solar/Wind Harmer
0.374
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.129
3137176SLIGO L2192
Solar/Wind Harmer
0.914
3146456SLIGO L269
Solar/Wind Harmer
4.065
3130086AYDLETT
Solar/Wind Harmer
0.917
3146386ELIZ CT
Solar/Wind Harmer
0.227
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.224
3146516WINFALL
Solar/Wind Harmer
0.224
3146516WINFALL
Solar/Wind Harmer
0.224
3146626S HERTFORD
Solar/Wind Harmer
0.223
3146626S HERTFORD
Solar/Wind Harmer
0.223
3144356SAPONY
Solar/Wind Harmer
1.861
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
0.969
3146376EDENTON
Solar/Wind Harmer
0.969
958261AF2-120 GEN
Solar/Wind Harmer
7.183
972185AH1-677 GEN
Adder
12.157
972187AH1-678 GEN
Adder
6.1
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.219
3150341NORNECKC1
Adder
2.202
316468AD1-105 GEN
Solar/Wind Harmer
-0.069
970933AG2-581 GEN
Solar/Wind Harmer
16.879
316065AD1-022 GEN
Solar/Wind Harmer
9.548
3145893MURPHYS
Solar/Wind Harmer
1.376
3145893MURPHYS
Solar/Wind Harmer
0.37
3146173TUNIS
Solar/Wind Harmer
0.204
3146173TUNIS
Solar/Wind Harmer
0.204
316181AB2-040 GEN
Solar/Wind Harmer
0.288
3142666NORTHAMPTON
Solar/Wind Harmer
0.198
3142666NORTHAMPTON
Solar/Wind Harmer
0.198
3142666NORTHAMPTON
Solar/Wind Harmer
0.198
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
970099AG2-077 GEN
Solar/Wind Harmer
21.134
316426AA2-053 GEN
Solar/Wind Harmer
0.666
3145593CAROLNA
Solar/Wind Harmer
0.196
3145593CAROLNA
Solar/Wind Harmer
0.196
966811AG1-552 GEN
Solar/Wind Harmer
2.127
3145593CAROLNA
Solar/Wind Harmer
0.244
3145783HORNRTN
Solar/Wind Harmer
3.466
3145783HORNRTN
Solar/Wind Harmer
2.773
3145783HORNRTN
Solar/Wind Harmer
0.866
3145783HORNRTN
Solar/Wind Harmer
0.347
3145796HORNRTN
Solar/Wind Harmer
0.584
3145933PARMELE
Solar/Wind Harmer
0.38
3145933PARMELE
Solar/Wind Harmer
0.19
316274AC1-208 GEN
Solar/Wind Harmer
0.98
971741AH1-377 GEN
Solar/Wind Harmer
18.489
970301AG2-198 GEN
Solar/Wind Harmer
7.849
939181AE1-148 GEN
Solar/Wind Harmer
8.688
3145493TOT1
Solar/Wind Harmer
0.417
3145453TOT5
Solar/Wind Harmer
0.25
3145603CNETO
Solar/Wind Harmer
0.167
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.634
971775AH1-396 GEN
Solar/Wind Harmer
0.286
958211AF2-115 GEN
Solar/Wind Harmer
2.137
963191AG1-168 GEN
Solar/Wind Harmer
0.712
3144293JTRSVLE
Adder
0.567
3144293JTRSVLE
Adder
0.477
3147133PAMPLIN
Solar/Wind Harmer
0.178
3147133PAMPLIN
Solar/Wind Harmer
0.142
961601AG1-000A GEN
Solar/Wind Harmer
3.141
316263AC1-034 GEN
Solar/Wind Harmer
6.71
962561AG1-105 GEN
Solar/Wind Harmer
8.256
964791AG1-342 GEN
Solar/Wind Harmer
3.275
3146843MT LREL
Solar/Wind Harmer
0.17
3146843MT LREL
Solar/Wind Harmer
0.17
3146776BUCKING
Solar/Wind Harmer
0.676
3146776BUCKING
Solar/Wind Harmer
0.055
971489AH1-241 GEN
Solar/Wind Harmer
8.062
316222AC1-221 GEN
Solar/Wind Harmer
0.618
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
6.907
966001AG1-469 GEN
Solar/Wind Harmer
0.072
3151731LOISA B
Adder
8.04
3151721LOISA A
Adder
7.998
971531AH1-263 GEN
50/50
86.379
3150411LDYSMT5
50/50
37.362
3150381LDYSMT2
50/50
35.757
972213AH1-691 GEN
50/50
6.049
972215AH1-692 GEN
50/50
6.049
963051AG1-154 GEN
50/50
4.653
972189AH1-679 GEN
Adder
4.288
316312AB1-027
Solar/Wind Harmer
0.446
316233AE1-074 FULL
Solar/Wind Harmer
0.196
971281AH1-106 GEN
Solar/Wind Harmer
3.397
971283AH1-107 GEN
Solar/Wind Harmer
3.397
971285AH1-108 GEN
Adder
1.844
315976AC1-164 GENA
Solar/Wind Harmer
25.197
316169AC1-164_GENC
Solar/Wind Harmer
21.768
315975AC1-164 GENB
Solar/Wind Harmer
0.745
316164AC1-076 GEN
Solar/Wind Harmer
0.34
316132AB2-190 GEN1
Solar/Wind Harmer
1.28
316369SG1_INVT
Solar/Wind Harmer
0.009
971167AH1-042 GEN
Solar/Wind Harmer
21.021
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
972265AH1-717 GEN
Adder
18.278
3151201GRAVEL4
Adder
17.134
3151191GRAVEL3
Adder
16.917
3151211GRAVEL5
Adder
16.917
971445AH1-216 GEN
Solar/Wind Harmer
16.508
3143316POE
Solar/Wind Harmer
0.927
3143873LANEXA
Solar/Wind Harmer
0.14
3138283WHITEMARSH
Solar/Wind Harmer
0.054
316314AB2-024 C
Solar/Wind Harmer
0.001
3151081ELIZAR1
Adder
21.327
3151091ELIZAR2
Adder
20.956
3152611GOSPORTB
Adder
2.962
3152621GOSPORTC
Adder
2.514
3152601GOSPORTA
Adder
2.319
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.866
315662AE1-191 GEN
Solar/Wind Harmer
0.008
315666AE1-190 GEN
Solar/Wind Harmer
0.002
957871AF2-081 GEN
Solar/Wind Harmer
11.461
3141873WAN 176
Solar/Wind Harmer
0.046
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.158
316311AC2-079 GEN
Solar/Wind Harmer
6.6
319010AE1-072 C
Solar/Wind Harmer
1.156
3146406KITTY HAWK
Solar/Wind Harmer
0.029
316305AF2-043 C
Solar/Wind Harmer
0.002
315835AF2-110_GEN
Solar/Wind Harmer
1.566
313526AB2-022
Solar/Wind Harmer
0.123
3141913WHIT STONE
Solar/Wind Harmer
0.227
3146486SUNBURY
Solar/Wind Harmer
0.227
3146486SUNBURY
Solar/Wind Harmer
0.227
3138133OCRAN
Solar/Wind Harmer
0.068
316321Z2-027
Solar/Wind Harmer
0.042
3146396TANGLEW
Solar/Wind Harmer
0.624
3145176PASQUOTANK
Solar/Wind Harmer
0.14
3141783LANCAST
Solar/Wind Harmer
0.135
3141783LANCAST
Solar/Wind Harmer
0.09
316315AB2-025 C
Solar/Wind Harmer
0.18
941031AE2-094 GEN
Solar/Wind Harmer
40.915
944011AF1-069 GEN
Solar/Wind Harmer
13.368
962981AG1-147 GEN
Solar/Wind Harmer
8.287
315814AE2-033 C
Solar/Wind Harmer
17.537
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
970327AG2-215 GEN
Solar/Wind Harmer
7.225
970673AG2-436 GEN
Solar/Wind Harmer
46.61
970673AG2-436 GEN
Solar/Wind Harmer
31.073
3130156CHOWAN
Solar/Wind Harmer
0.218
3130156CHOWAN
Solar/Wind Harmer
0.218
971967AH1-528 GEN
Solar/Wind Harmer
34.545
315816AE2-034 GEN
Solar/Wind Harmer
0.915
3141813NORNECK
Solar/Wind Harmer
0.212
3130546PLYMOUTH
Solar/Wind Harmer
0.209
315732AD1-074 GEN1
Solar/Wind Harmer
1.2
315733AD1-074 GEN2
Solar/Wind Harmer
1.2
315735AD1-075 GEN1
Solar/Wind Harmer
0.6
965291AG1-394 GEN
Solar/Wind Harmer
0.923
3146206CASHIE
Solar/Wind Harmer
0.206
970601AG2-382 GEN
Solar/Wind Harmer
7.712
970085AG2-068 GEN
Solar/Wind Harmer
10.986
970581AG2-369 GEN
Solar/Wind Harmer
9.448
3145893MURPHYS
Solar/Wind Harmer
0.555
3145893MURPHYS
Solar/Wind Harmer
0.206
3145513AHOSKIE
Solar/Wind Harmer
0.424
3145513AHOSKIE
Solar/Wind Harmer
0.203
3145683EARLEYS
Solar/Wind Harmer
0.403
3145683EARLEYS
Solar/Wind Harmer
0.202
3145683EARLEYS
Solar/Wind Harmer
0.202
3146043SEABORD
Solar/Wind Harmer
0.201
315607AA1-063A GEN
Solar/Wind Harmer
0.41
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
21.753
3137643SOCKMAN
Solar/Wind Harmer
0.788
3145796HORNRTN
Solar/Wind Harmer
0.623
3145796HORNRTN
Solar/Wind Harmer
0.078
3146033SCOT NK
Solar/Wind Harmer
0.774
316223AC1-118
Solar/Wind Harmer
0.139
970831AG2-522 GEN
Solar/Wind Harmer
7.995
316005AA1-067
Solar/Wind Harmer
0.2
3145746EVERETS
Solar/Wind Harmer
0.74
3145746EVERETS
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
0.186
970181AG2-120 GEN
Solar/Wind Harmer
2.314
957861AF2-080 GEN
Solar/Wind Harmer
7.879
316420AA1-050 GEN
Solar/Wind Harmer
0.006
3145573BETHELC
Solar/Wind Harmer
0.18
3145573BETHELC
Solar/Wind Harmer
0.18
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
3.007
3144303KENBRDG
Solar/Wind Harmer
0.143
970683AG2-441 GEN
Solar/Wind Harmer
11.901
970681AG2-440 GEN
Solar/Wind Harmer
9.521
946301AF1-294 GEN
Solar/Wind Harmer
3.515
961791AG1-021 GEN
Solar/Wind Harmer
1.71
315657AE1-056 GEN
Solar/Wind Harmer
6.134
970285AG2-188 GEN
Solar/Wind Harmer
13.517
944491AF1-114 GEN
Solar/Wind Harmer
0.001
971845AH1-439 GEN
Solar/Wind Harmer
7.694
316118AC1-105 GEN
Solar/Wind Harmer
0.432
972193AH1-681 GEN
Adder
3.772
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.102
972205AH1-687 GEN
Adder
6.859
971447AH1-217 GEN
Solar/Wind Harmer
4.479
970865AG2-541 GEN
Solar/Wind Harmer
5.067
316123AC1-075 GEN
Solar/Wind Harmer
0.184
970165AG2-112 GEN
Solar/Wind Harmer
1.09
970163AG2-111 GEN
Solar/Wind Harmer
1.039
270494AE1-108_GEN
Solar/Wind Harmer
1.609
3147346CASHSCORNER
Solar/Wind Harmer
0.278
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316411AF1-147_GEN1
Solar/Wind Helper
0.807
316415AF1-147_GEN2
Solar/Wind Helper
0.807
3138216PACIFIC
Solar/Wind Helper
0.039
971507AH1-251 GEN
50/50
17.73
3152251N ANNA1
50/50
14.579
972197AH1-683 GEN
50/50
5.816
972219AH1-694 GEN
50/50
4.188
315052AA1-145 CT2
50/50
2.039
316045AC1-158 PL2
Solar/Wind Harmer
4.87
966881AG1-559 GEN
Solar/Wind Harmer
0.299
3142416OLDCHRC
Solar/Wind Harmer
0.648
3142416OLDCHRC
Solar/Wind Harmer
0.248
3143526WINTERP
Solar/Wind Harmer
1.273
3143096IRON208
Adder
1.025
3150851SPRUNCC
Adder
1.127
3143226MDLTHAN
Solar/Wind Harmer
0.244
3142543TWELFTH
Solar/Wind Harmer
0.023
944631AF1-128 GEN
Adder
115.654
316159AE1-175 C
Solar/Wind Harmer
0.206
970129AG2-093 GEN
Solar/Wind Harmer
6.792
316458AB2-190 GEN2
Solar/Wind Harmer
1.28
315671AE2-027_GEN
Solar/Wind Harmer
15.26
971069AG2-661 GEN
Solar/Wind Harmer
4.23
971647AH1-324 GEN
Solar/Wind Harmer
10.104
971317AH1-138 GEN
Solar/Wind Harmer
1.765
3138126ROCKLANDING
Solar/Wind Harmer
0.108
3142433PROV 92
Solar/Wind Harmer
0.944
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
961611AG1-000B GEN
Solar/Wind Harmer
12.386
316294AC1-161 GEN
Solar/Wind Harmer
4.079
3151171GRAVELC
Adder
2.504
3145336SMITFLD
Solar/Wind Harmer
0.937
970659AG2-427 GEN
Solar/Wind Harmer
11.263
944591AF1-124 GEN
Solar/Wind Harmer
52.565
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.904
316381AD1-082 GEN
Solar/Wind Harmer
0.242
3141766HARMONY
Solar/Wind Harmer
0.046
970661AG2-428 GEN
Solar/Wind Harmer
23.062
971777AH1-397 GEN
Solar/Wind Harmer
0.612
3141843SHACKLE
Adder
1.184
316072AD1-144
Solar/Wind Harmer
0.084
939411AE1-173 GEN
Solar/Wind Harmer
98.509
940641AE2-051 GEN
Solar/Wind Harmer
18.448
316388AE2-253 GEN
Solar/Wind Harmer
0.722
3146456SLIGO L269
Solar/Wind Harmer
0.23
316246AF1-032 C
Solar/Wind Harmer
0.103
316093AE2-104_GEN
Solar/Wind Harmer
3.838
3138133OCRAN
Solar/Wind Harmer
0.136
3146516WINFALL
Solar/Wind Harmer
0.727
3146516WINFALL
Solar/Wind Harmer
0.224
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.218
962861AG1-135 GEN
Solar/Wind Harmer
6.976
3141726DUNNSVL
Solar/Wind Harmer
0.859
3145663CRESWEL
Solar/Wind Harmer
0.597
971163AH1-040 GEN
Solar/Wind Harmer
17.057
3150351NORNECKC2
Adder
2.113
3143336POWHATN
Solar/Wind Harmer
3.747
970919AG2-571 GEN
Solar/Wind Harmer
7.353
3146206CASHIE
Solar/Wind Harmer
0.206
971547AH1-271 GEN
Solar/Wind Harmer
4.407
316023GEN1_S
Solar/Wind Harmer
0.463
970087AG2-069 GEN
Solar/Wind Harmer
16.479
3145893MURPHYS
Solar/Wind Harmer
0.822
3145893MURPHYS
Solar/Wind Harmer
0.914
3146173TUNIS
Solar/Wind Harmer
0.204
316337AD2-073 GEN
Solar/Wind Harmer
0.177
316336AC2-165 C
Solar/Wind Harmer
0.008
3145683EARLEYS
Solar/Wind Harmer
0.202
3147666LOUISA
Solar/Wind Harmer
0.804
960081AF2-299 GEN
Solar/Wind Harmer
1.928
3146263WOODLND
Solar/Wind Harmer
0.2
3145963POPLR C
Solar/Wind Harmer
0.199
957481AF2-042 GEN
Solar/Wind Harmer
52.836
316011AB1-132 GEN
Solar/Wind Harmer
3.595
962571AG1-106 GEN
Solar/Wind Harmer
2.814
3145823KELFORD
Solar/Wind Harmer
0.198
316190AA2-174 GEN
Solar/Wind Harmer
0
316174AB2-169 GEN
Solar/Wind Harmer
0.005
316192AB2-158 GEN
Solar/Wind Harmer
1.112
971795AH1-408 GEN
Solar/Wind Harmer
13.096
3145783HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.642
3145796HORNRTN
Solar/Wind Harmer
0.195
315693AD1-088 GEN
Solar/Wind Harmer
9.336
3147043LAWRENC
Adder
1.759
962491AG1-098 GEN
Solar/Wind Harmer
11.068
316212AC1-099_GEN
Solar/Wind Harmer
0.984
3146293MARTNCO
Solar/Wind Harmer
0.176
316129AC1-054 GEN
Solar/Wind Harmer
0.701
3145746EVERETS
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
0.186
971065AG2-659 GEN
Solar/Wind Harmer
7.918
315722AD1-056 GEN
Solar/Wind Harmer
1.169
316494AC1-189 GEN
Solar/Wind Harmer
0.617
315687AD1-152 GEN
Solar/Wind Harmer
0.006
961671AG1-007 GEN
Solar/Wind Harmer
0.028
3146083TARBORO
Solar/Wind Harmer
0.18
3145493TOT1
Solar/Wind Harmer
0.8
3146233WITAKRS
Solar/Wind Harmer
0.716
970937AG2-583 GEN
Solar/Wind Harmer
11.013
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970685AG2-442 GEN
Solar/Wind Harmer
13.329
972135AH1-637 GEN
Solar/Wind Harmer
1.522
963171AG1-166 GEN
Solar/Wind Harmer
0.95
971563AH1-280 GEN
Solar/Wind Harmer
1.9
3144293JTRSVLE
Adder
0.567
3145543BTLEBRO
Solar/Wind Harmer
0.176
3145543BTLEBRO
Solar/Wind Harmer
0.141
316359AB2-059 GEN
Solar/Wind Harmer
0.634
316049AB1-081 GEN
Solar/Wind Harmer
1.011
3142053HEARTS
Solar/Wind Harmer
0.311
3146926FARMVIL
Solar/Wind Harmer
0.106
970401AG2-262 GEN
Solar/Wind Harmer
1.001
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.068
972277AH1-723 GEN
Adder
98.366
972003AH1-546 GEN
Solar/Wind Harmer
6.888
316003AC1-222 GEN
Solar/Wind Harmer
0.004
971377AH1-170 GEN
Solar/Wind Harmer
1.612
3147623JAMES R
Solar/Wind Harmer
0.35
3151751LOISA D
Adder
8.04
316254AC1-120 GEN1
Solar/Wind Harmer
0.262
LAGNLTFEXP_LAGN->PJM
CLTF
8.029
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.001
TVALTFEXP_TVA->PJM
CLTF
4.071
NYPJM->LTFIMP_NY
CLTF
3.261
LGEELTFEXP_LGEE->PJM
CLTF
1.336
WECLTFEXP_WEC->PJM
CLTF
0.644
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.423
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.85
MECLTFEXP_MEC->PJM
CLTF
3.626
SIGELTFEXP_SIGE->PJM
CLTF
0.111
CPLELTFEXP_CPLE->PJM
CLTF
11.392
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.447

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.02 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5007.08
MW Contribution:7.14
Bus #Bus NameTypeMW Contribution
971531AH1-263 GEN
50/50
73.177
3150411LDYSMT5
50/50
36.98
3150381LDYSMT2
50/50
35.391
972213AH1-691 GEN
50/50
5.987
972215AH1-692 GEN
50/50
5.987
963051AG1-154 GEN
50/50
4.605
972189AH1-679 GEN
Adder
4.237
316312AB1-027
Solar/Wind Harmer
0.44
316233AE1-074 FULL
Solar/Wind Harmer
0.193
971281AH1-106 GEN
Solar/Wind Harmer
3.35
971283AH1-107 GEN
Solar/Wind Harmer
3.35
971285AH1-108 GEN
Adder
1.819
315976AC1-164 GENA
Solar/Wind Harmer
24.88
316169AC1-164_GENC
Solar/Wind Harmer
21.494
315975AC1-164 GENB
Solar/Wind Harmer
0.736
316132AB2-190 GEN1
Solar/Wind Harmer
1.264
316369SG1_INVT
Solar/Wind Harmer
0.009
971167AH1-042 GEN
Solar/Wind Harmer
20.755
3142433PROV 92
Adder
0.453
3142433PROV 92
Adder
0.453
972265AH1-717 GEN
Adder
18.039
3151201GRAVEL4
Adder
16.911
3151191GRAVEL3
Adder
16.697
3151211GRAVEL5
Adder
16.697
971445AH1-216 GEN
Solar/Wind Harmer
16.292
3143316POE
Solar/Wind Harmer
0.915
3143873LANEXA
Solar/Wind Harmer
0.139
3138283WHITEMARSH
Solar/Wind Harmer
0.053
316314AB2-024 C
Solar/Wind Harmer
0.001
3151081ELIZAR1
Adder
21.046
3151091ELIZAR2
Adder
20.681
3152611GOSPORTB
Adder
2.923
3152621GOSPORTC
Adder
2.481
3152601GOSPORTA
Adder
2.288
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.781
315662AE1-191 GEN
Solar/Wind Harmer
0.008
315666AE1-190 GEN
Solar/Wind Harmer
0.002
957871AF2-081 GEN
Solar/Wind Harmer
11.31
3141873WAN 176
Solar/Wind Harmer
0.045
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.155
316311AC2-079 GEN
Solar/Wind Harmer
6.513
319010AE1-072 C
Solar/Wind Harmer
1.141
3146406KITTY HAWK
Solar/Wind Harmer
0.028
316305AF2-043 C
Solar/Wind Harmer
0.002
315835AF2-110_GEN
Solar/Wind Harmer
1.545
3141913WHIT STONE
Solar/Wind Harmer
0.224
313526AB2-022
Solar/Wind Harmer
0.121
3138133OCRAN
Solar/Wind Harmer
0.067
3146486SUNBURY
Solar/Wind Harmer
0.224
3146486SUNBURY
Solar/Wind Harmer
0.224
316321Z2-027
Solar/Wind Harmer
0.041
3146396TANGLEW
Solar/Wind Harmer
0.616
3145176PASQUOTANK
Solar/Wind Harmer
0.138
3141783LANCAST
Solar/Wind Harmer
0.133
3141783LANCAST
Solar/Wind Harmer
0.089
316315AB2-025 C
Solar/Wind Harmer
0.177
962981AG1-147 GEN
Solar/Wind Harmer
8.186
941031AE2-094 GEN
Solar/Wind Harmer
40.356
944011AF1-069 GEN
Solar/Wind Harmer
13.186
315814AE2-033 C
Solar/Wind Harmer
17.302
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
970327AG2-215 GEN
Solar/Wind Harmer
7.138
970673AG2-436 GEN
Solar/Wind Harmer
45.972
970673AG2-436 GEN
Solar/Wind Harmer
30.648
3130156CHOWAN
Solar/Wind Harmer
0.215
3130156CHOWAN
Solar/Wind Harmer
0.215
971967AH1-528 GEN
Solar/Wind Harmer
34.067
315816AE2-034 GEN
Solar/Wind Harmer
0.903
3141813NORNECK
Solar/Wind Harmer
0.209
3130546PLYMOUTH
Solar/Wind Harmer
0.207
315732AD1-074 GEN1
Solar/Wind Harmer
1.184
315733AD1-074 GEN2
Solar/Wind Harmer
1.184
315735AD1-075 GEN1
Solar/Wind Harmer
0.593
965291AG1-394 GEN
Solar/Wind Harmer
0.91
3146206CASHIE
Solar/Wind Harmer
0.204
970601AG2-382 GEN
Solar/Wind Harmer
7.61
970085AG2-068 GEN
Solar/Wind Harmer
10.836
970581AG2-369 GEN
Solar/Wind Harmer
9.319
3145893MURPHYS
Solar/Wind Harmer
0.548
3145893MURPHYS
Solar/Wind Harmer
0.203
3145513AHOSKIE
Solar/Wind Harmer
0.418
3145513AHOSKIE
Solar/Wind Harmer
0.2
3145683EARLEYS
Solar/Wind Harmer
0.398
3145683EARLEYS
Solar/Wind Harmer
0.199
3145683EARLEYS
Solar/Wind Harmer
0.199
3146043SEABORD
Solar/Wind Harmer
0.198
315607AA1-063A GEN
Solar/Wind Harmer
0.404
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
21.462
3137643SOCKMAN
Solar/Wind Harmer
0.777
3145796HORNRTN
Solar/Wind Harmer
0.615
3145796HORNRTN
Solar/Wind Harmer
0.077
3146033SCOT NK
Solar/Wind Harmer
0.764
316223AC1-118
Solar/Wind Harmer
0.137
970831AG2-522 GEN
Solar/Wind Harmer
7.881
316005AA1-067
Solar/Wind Harmer
0.197
3145746EVERETS
Solar/Wind Harmer
0.73
3145746EVERETS
Solar/Wind Harmer
0.183
3145746EVERETS
Solar/Wind Harmer
0.183
3145746EVERETS
Solar/Wind Harmer
0.183
970181AG2-120 GEN
Solar/Wind Harmer
2.284
957861AF2-080 GEN
Solar/Wind Harmer
7.776
316420AA1-050 GEN
Solar/Wind Harmer
0.006
3145573BETHELC
Solar/Wind Harmer
0.178
3145573BETHELC
Solar/Wind Harmer
0.178
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
2.956
3144303KENBRDG
Solar/Wind Harmer
0.141
970683AG2-441 GEN
Solar/Wind Harmer
11.694
970681AG2-440 GEN
Solar/Wind Harmer
9.355
946301AF1-294 GEN
Solar/Wind Harmer
3.451
961791AG1-021 GEN
Solar/Wind Harmer
1.679
315657AE1-056 GEN
Solar/Wind Harmer
6.021
944491AF1-114 GEN
Solar/Wind Harmer
0.001
970285AG2-188 GEN
Solar/Wind Harmer
13.206
971845AH1-439 GEN
Solar/Wind Harmer
7.514
316118AC1-105 GEN
Solar/Wind Harmer
0.425
972193AH1-681 GEN
Adder
3.717
3147173SINAI
Solar/Wind Harmer
0.161
3147243WELCO
Solar/Wind Harmer
0.101
972205AH1-687 GEN
Adder
6.67
970865AG2-541 GEN
Solar/Wind Harmer
4.995
971447AH1-217 GEN
Solar/Wind Harmer
4.355
316123AC1-075 GEN
Solar/Wind Harmer
0.181
970165AG2-112 GEN
Solar/Wind Harmer
1.074
970163AG2-111 GEN
Solar/Wind Harmer
1.025
270494AE1-108_GEN
Solar/Wind Harmer
1.568
316411AF1-147_GEN1
Solar/Wind Helper
0.784
316415AF1-147_GEN2
Solar/Wind Helper
0.784
3138216PACIFIC
Solar/Wind Helper
0.038
3152261N ANNA2
50/50
14.366
970497AG2-320 GEN
50/50
25.942
3150401LDYSMT4
50/50
36.865
3150371LDYSMT1
50/50
35.621
315051AA1-145 CT1
50/50
2.006
3142416OLDCHRC
Solar/Wind Harmer
2.384
970293AG2-193 GEN
Solar/Wind Harmer
2.591
3143096IRON208
Adder
1.011
3143096IRON208
Adder
0.991
3150861SPRUNCD
Adder
1.112
316473AC1-191 GEN
Solar/Wind Harmer
0.812
3142946ENON
Solar/Wind Harmer
0.08
970133AG2-095 GEN
Solar/Wind Harmer
2.274
316382AG1-145 C
Solar/Wind Harmer
0.002
970129AG2-093 GEN
Solar/Wind Harmer
14.245
315778AD1-151 GEN
Solar/Wind Harmer
18.787
965281AG1-393 GEN
Solar/Wind Harmer
2.505
315839AE2-212 C
Solar/Wind Harmer
0.002
3150921YORKTN3
Adder
5.862
3144216WINCHST
Adder
0.879
3142433PROV 92
Adder
0.453
3142433PROV 92
Adder
0.453
961611AG1-000B GEN
Solar/Wind Harmer
6.216
315773AC2-141 GEN
Solar/Wind Harmer
8.485
3151221GRAVEL6
Adder
16.891
3151171GRAVELC
Adder
3.25
3145336SMITFLD
Solar/Wind Harmer
0.093
315813AE1-149 C
Solar/Wind Harmer
12.335
3144536CHRHLND
Solar/Wind Harmer
0.034
970659AG2-427 GEN
Solar/Wind Harmer
2.431
944581AF1-123 GEN
Solar/Wind Harmer
51.69
944601AF1-125 GEN
Solar/Wind Harmer
50.894
3151101ELIZAR3
Adder
21.316
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3144873MCLAUGH
Solar/Wind Harmer
0.006
3141766HARMONY
Solar/Wind Harmer
3.053
3141843SHACKLE
Adder
1.169
970661AG2-428 GEN
Solar/Wind Harmer
4.841
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.005
316156AD2-030 GEN
Solar/Wind Harmer
0.168
3141873WAN 176
Solar/Wind Harmer
4.038
3146456SLIGO L269
Solar/Wind Harmer
0.227
971153AH1-033 GEN
Solar/Wind Harmer
2.621
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.221
3146626S HERTFORD
Solar/Wind Harmer
0.22
962971AG1-146 GEN
Solar/Wind Harmer
3.508
3145273HOLLAND
Solar/Wind Harmer
0.164
970009AG2-005 GEN
Solar/Wind Harmer
1.624
3146376EDENTON
Solar/Wind Harmer
0.215
316404AE1-155 C
Solar/Wind Harmer
0.048
315614AA2-178 GEN
Solar/Wind Harmer
1.204
3150351NORNECKC2
Adder
2.123
971781AH1-399 GEN
Solar/Wind Harmer
0.275
316313AB2-026
Solar/Wind Harmer
0.13
316258AE1-075 C
Solar/Wind Harmer
0.156
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
3.126
971157AH1-035 GEN
Solar/Wind Harmer
2.481
315737AD1-076 GEN
Solar/Wind Harmer
2.651
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
970917AG2-570 GEN
Solar/Wind Harmer
18.132
3146206CASHIE
Solar/Wind Harmer
0.204
316365GEN2_N
Solar/Wind Harmer
0.456
3145893MURPHYS
Solar/Wind Harmer
0.34
3145893MURPHYS
Solar/Wind Harmer
0.203
957521AF2-046 GEN
Solar/Wind Harmer
15.061
961681AG1-008 GEN
Solar/Wind Harmer
15.061
3146173TUNIS
Solar/Wind Harmer
0.201
3156021HOLLOMANSOL
Solar/Wind Harmer
0.911
316463AE2-346 GEN
Solar/Wind Harmer
0.172
316140AB2-099
Solar/Wind Harmer
0.071
962331AG1-082 GEN
Solar/Wind Harmer
2.134
3146263WOODLND
Solar/Wind Harmer
0.197
3145963POPLR C
Solar/Wind Harmer
0.196
313506AB2-031 GEN
Solar/Wind Harmer
0.605
3142666NORTHAMPTON
Solar/Wind Harmer
0.196
316317KELFORD C
Solar/Wind Harmer
0.019
3145823KELFORD
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.768
3145796HORNRTN
Solar/Wind Harmer
0.192
3147043LAWRENC
Solar/Wind Harmer
0.115
3141906WESTMOR
Solar/Wind Harmer
0.076
3147666LOUISA
Solar/Wind Harmer
0.435
316478AD1-087 GEN
Solar/Wind Harmer
0.657
316486AD2-202 GEN
Solar/Wind Harmer
0.193
316210AC1-098 GEN
Solar/Wind Harmer
1.741
3145933PARMELE
Solar/Wind Harmer
0.187
966801AG1-551 GEN
Solar/Wind Harmer
2.184
3145746EVERETS
Solar/Wind Harmer
0.183
3145746EVERETS
Solar/Wind Harmer
0.183
970737AG2-469 GEN
Solar/Wind Harmer
7.78
315724AD1-057 GEN
Solar/Wind Harmer
0.684
316327AA2-057 GEN
Solar/Wind Harmer
0.273
970909AG2-566 GEN
Solar/Wind Harmer
1.926
3146073TAR RVR
Solar/Wind Harmer
0.178
3146083TARBORO
Solar/Wind Harmer
0.178
3146233WITAKRS
Solar/Wind Harmer
0.891
3146233WITAKRS
Solar/Wind Harmer
0.121
3138543CONSLDL
Solar/Wind Harmer
0.117
316131AB2-060 GEN
Solar/Wind Harmer
0.557
964241AG1-285 GEN
Solar/Wind Harmer
11.779
315785AD2-033 C
Solar/Wind Harmer
1.432
970257AG2-171 GEN
Solar/Wind Harmer
5.629
959311AF2-222 GEN
Solar/Wind Harmer
15.624
963181AG1-167 GEN
Solar/Wind Harmer
0.7
3144293JTRSVLE
Adder
0.557
3147133PAMPLIN
Solar/Wind Harmer
0.548
971193AH1-056 GEN
Solar/Wind Harmer
10.629
961601AG1-000A GEN
Solar/Wind Harmer
12.399
3145543BTLEBRO
Solar/Wind Harmer
0.174
3145543BTLEBRO
Solar/Wind Harmer
0.174
971623AH1-311 GEN
Solar/Wind Harmer
0.349
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.104
3146776BUCKING
Solar/Wind Harmer
0.059
972255AH1-712 GEN
Adder
83.19
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
6.893
971683AH1-343 GEN
Solar/Wind Harmer
5.511
970221AG2-151 GEN
Solar/Wind Harmer
7.84
316283AC2-100 C
Solar/Wind Harmer
0.286
3141316ARNOLDS
Adder
0.322
3150331BIRCHWDA
Adder
21.148
316044AC1-158 PL1
Solar/Wind Helper
1.891
316450AC1-158 RIC
Solar/Wind Helper
0.504
3141196NOKESVL
Solar/Wind Helper
1.226
3150391LDYSMT3
50/50
36.796
972195AH1-682 GEN
50/50
4.835
315673AE1-157 GEN
Solar/Wind Harmer
17.789
957411AF2-035 GEN
Solar/Wind Harmer
10.93
970317AG2-208 GEN
Solar/Wind Harmer
10.126
3142296MT RD221
Adder
0.793
3142366NRTHEST
Adder
0.798
3150691DARBY 3
Adder
17.545
3150701DARBY 4
Adder
17.505
3150681DARBY 2
Adder
17.484
3150671DARBY 1
Adder
17.464
316075AC2-137 C
Solar/Wind Harmer
0.066
3143526WINTERP
Solar/Wind Harmer
1.255
971223AH1-071 GEN
Solar/Wind Harmer
2.567
966871AG1-558 GEN
Solar/Wind Harmer
0.278
3142946ENON
Solar/Wind Harmer
0.024
944641AF1-129 GEN
Adder
113.139
316240AF1-291 C
Solar/Wind Harmer
0.002
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.263
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316036AC1-147 C
Solar/Wind Harmer
0.043
3150991CHESPKB
Adder
2.404
3150991CHESPKB
Adder
2.347
970657AG2-426 GEN
Solar/Wind Harmer
8.03
970657AG2-426 GEN
Solar/Wind Harmer
1.684
316316AC1-027 C
Solar/Wind Harmer
0.22
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.007
3145506HICKORY
Solar/Wind Harmer
0.912
3145506HICKORY
Solar/Wind Harmer
0.547
3145506HICKORY
Solar/Wind Harmer
0.137
316339AD2-160 GEN
Solar/Wind Harmer
0.369
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.127
3137176SLIGO L2192
Solar/Wind Harmer
0.902
3146456SLIGO L269
Solar/Wind Harmer
4.012
3130086AYDLETT
Solar/Wind Harmer
0.905
3146386ELIZ CT
Solar/Wind Harmer
0.224
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.221
3146516WINFALL
Solar/Wind Harmer
0.221
3146516WINFALL
Solar/Wind Harmer
0.221
3146626S HERTFORD
Solar/Wind Harmer
0.22
3146626S HERTFORD
Solar/Wind Harmer
0.22
3144356SAPONY
Solar/Wind Harmer
1.836
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
0.957
3146376EDENTON
Solar/Wind Harmer
0.957
958261AF2-120 GEN
Solar/Wind Harmer
7.097
972185AH1-677 GEN
Adder
11.991
972187AH1-678 GEN
Adder
6.016
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.193
3150341NORNECKC1
Adder
2.176
316468AD1-105 GEN
Solar/Wind Harmer
-0.068
970933AG2-581 GEN
Solar/Wind Harmer
16.641
316065AD1-022 GEN
Solar/Wind Harmer
9.423
3145893MURPHYS
Solar/Wind Harmer
1.358
3145893MURPHYS
Solar/Wind Harmer
0.365
3146173TUNIS
Solar/Wind Harmer
0.201
3152251N ANNA1
50/50
14.367
972197AH1-683 GEN
50/50
5.757
972219AH1-694 GEN
50/50
4.145
315052AA1-145 CT2
50/50
2.014
966881AG1-559 GEN
Solar/Wind Harmer
0.296
3142416OLDCHRC
Solar/Wind Harmer
0.639
3142416OLDCHRC
Solar/Wind Harmer
0.245
3143526WINTERP
Solar/Wind Harmer
1.255
3143096IRON208
Adder
1.011
3150851SPRUNCC
Adder
1.112
3142543TWELFTH
Solar/Wind Harmer
0.023
3143226MDLTHAN
Solar/Wind Harmer
0.24
944631AF1-128 GEN
Adder
114.169
316159AE1-175 C
Solar/Wind Harmer
0.204
970129AG2-093 GEN
Solar/Wind Harmer
6.704
316458AB2-190 GEN2
Solar/Wind Harmer
1.264
315671AE2-027_GEN
Solar/Wind Harmer
15.06
971069AG2-661 GEN
Solar/Wind Harmer
4.175
971647AH1-324 GEN
Solar/Wind Harmer
9.972
971317AH1-138 GEN
Solar/Wind Harmer
1.742
3138126ROCKLANDING
Solar/Wind Harmer
0.107
3142433PROV 92
Solar/Wind Harmer
0.932
3142433PROV 92
Adder
0.453
3142433PROV 92
Adder
0.453
961611AG1-000B GEN
Solar/Wind Harmer
12.225
316294AC1-161 GEN
Solar/Wind Harmer
4.025
3151171GRAVELC
Adder
2.471
3145336SMITFLD
Solar/Wind Harmer
0.925
970659AG2-427 GEN
Solar/Wind Harmer
11.115
944591AF1-124 GEN
Solar/Wind Harmer
51.874
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.866
316381AD1-082 GEN
Solar/Wind Harmer
0.239
3141766HARMONY
Solar/Wind Harmer
0.046
971777AH1-397 GEN
Solar/Wind Harmer
0.604
3141843SHACKLE
Adder
1.169
970661AG2-428 GEN
Solar/Wind Harmer
22.759
316072AD1-144
Solar/Wind Harmer
0.082
939411AE1-173 GEN
Solar/Wind Harmer
97.185
940641AE2-051 GEN
Solar/Wind Harmer
18.198
316388AE2-253 GEN
Solar/Wind Harmer
0.712
3146456SLIGO L269
Solar/Wind Harmer
0.227
316246AF1-032 C
Solar/Wind Harmer
0.102
316093AE2-104_GEN
Solar/Wind Harmer
3.787
3138133OCRAN
Solar/Wind Harmer
0.134
3146516WINFALL
Solar/Wind Harmer
0.717
3146516WINFALL
Solar/Wind Harmer
0.221
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
962861AG1-135 GEN
Solar/Wind Harmer
6.892
3130156CHOWAN
Solar/Wind Harmer
0.215
3141726DUNNSVL
Solar/Wind Harmer
0.848
3145663CRESWEL
Solar/Wind Harmer
0.589
971163AH1-040 GEN
Solar/Wind Harmer
16.833
3150351NORNECKC2
Adder
2.088
3143336POWHATN
Solar/Wind Harmer
3.678
970919AG2-571 GEN
Solar/Wind Harmer
7.253
3146206CASHIE
Solar/Wind Harmer
0.204
971547AH1-271 GEN
Solar/Wind Harmer
4.349
316023GEN1_S
Solar/Wind Harmer
0.456
970087AG2-069 GEN
Solar/Wind Harmer
16.254
3145893MURPHYS
Solar/Wind Harmer
0.811
3145893MURPHYS
Solar/Wind Harmer
0.902
3146173TUNIS
Solar/Wind Harmer
0.201
316337AD2-073 GEN
Solar/Wind Harmer
0.175
3145683EARLEYS
Solar/Wind Harmer
0.199
316336AC2-165 C
Solar/Wind Harmer
0.008
960081AF2-299 GEN
Solar/Wind Harmer
1.901
3146263WOODLND
Solar/Wind Harmer
0.197
3145963POPLR C
Solar/Wind Harmer
0.196
957481AF2-042 GEN
Solar/Wind Harmer
52.064
316011AB1-132 GEN
Solar/Wind Harmer
3.547
962571AG1-106 GEN
Solar/Wind Harmer
2.776
3145823KELFORD
Solar/Wind Harmer
0.195
316190AA2-174 GEN
Solar/Wind Harmer
0
316174AB2-169 GEN
Solar/Wind Harmer
0.005
971795AH1-408 GEN
Solar/Wind Harmer
12.912
3145783HORNRTN
Solar/Wind Harmer
0.192
3145796HORNRTN
Solar/Wind Harmer
0.634
3145796HORNRTN
Solar/Wind Harmer
0.192
3147043LAWRENC
Adder
1.734
315693AD1-088 GEN
Solar/Wind Harmer
9.193
962491AG1-098 GEN
Solar/Wind Harmer
10.897
3147666LOUISA
Solar/Wind Harmer
0.757
316212AC1-099_GEN
Solar/Wind Harmer
0.971
3146293MARTNCO
Solar/Wind Harmer
0.174
316192AB2-158 GEN
Solar/Wind Harmer
1.044
316129AC1-054 GEN
Solar/Wind Harmer
0.691
3145746EVERETS
Solar/Wind Harmer
0.183
3145746EVERETS
Solar/Wind Harmer
0.183
971065AG2-659 GEN
Solar/Wind Harmer
7.805
315722AD1-056 GEN
Solar/Wind Harmer
1.154
316494AC1-189 GEN
Solar/Wind Harmer
0.609
315687AD1-152 GEN
Solar/Wind Harmer
0.006
961671AG1-007 GEN
Solar/Wind Harmer
0.027
3146083TARBORO
Solar/Wind Harmer
0.178
3145493TOT1
Solar/Wind Harmer
0.79
3146233WITAKRS
Solar/Wind Harmer
0.707
316237AB2-079_GEN
Solar/Wind Harmer
0.001
972135AH1-637 GEN
Solar/Wind Harmer
1.506
970685AG2-442 GEN
Solar/Wind Harmer
13.097
970937AG2-583 GEN
Solar/Wind Harmer
10.754
963171AG1-166 GEN
Solar/Wind Harmer
0.933
971563AH1-280 GEN
Solar/Wind Harmer
1.866
3144293JTRSVLE
Adder
0.557
3145543BTLEBRO
Solar/Wind Harmer
0.174
3145543BTLEBRO
Solar/Wind Harmer
0.139
316359AB2-059 GEN
Solar/Wind Harmer
0.626
316049AB1-081 GEN
Solar/Wind Harmer
0.997
3142053HEARTS
Solar/Wind Harmer
0.307
3146926FARMVIL
Solar/Wind Harmer
0.104
970401AG2-262 GEN
Solar/Wind Harmer
0.986
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.066
972277AH1-723 GEN
Adder
96.942
972003AH1-546 GEN
Solar/Wind Harmer
6.703
316003AC1-222 GEN
Solar/Wind Harmer
0.004
971377AH1-170 GEN
Solar/Wind Harmer
1.568
3147623JAMES R
Solar/Wind Harmer
0.341
316045AC1-158 PL2
Solar/Wind Helper
6.052
316006AB2-029 C
Solar/Wind Helper
0.11
3146173TUNIS
Solar/Wind Harmer
0.201
316181AB2-040 GEN
Solar/Wind Harmer
0.284
3142666NORTHAMPTON
Solar/Wind Harmer
0.196
3142666NORTHAMPTON
Solar/Wind Harmer
0.196
3142666NORTHAMPTON
Solar/Wind Harmer
0.196
3142666NORTHAMPTON
Solar/Wind Harmer
0.117
970099AG2-077 GEN
Solar/Wind Harmer
20.826
316426AA2-053 GEN
Solar/Wind Harmer
0.657
3145593CAROLNA
Solar/Wind Harmer
0.193
3145593CAROLNA
Solar/Wind Harmer
0.193
966811AG1-552 GEN
Solar/Wind Harmer
2.098
3145593CAROLNA
Solar/Wind Harmer
0.241
3145783HORNRTN
Solar/Wind Harmer
3.419
3145783HORNRTN
Solar/Wind Harmer
2.735
3145783HORNRTN
Solar/Wind Harmer
0.855
3145783HORNRTN
Solar/Wind Harmer
0.342
3145796HORNRTN
Solar/Wind Harmer
0.576
3145933PARMELE
Solar/Wind Harmer
0.375
3145933PARMELE
Solar/Wind Harmer
0.187
316274AC1-208 GEN
Solar/Wind Harmer
0.967
971741AH1-377 GEN
Solar/Wind Harmer
18.163
970301AG2-198 GEN
Solar/Wind Harmer
7.705
939181AE1-148 GEN
Solar/Wind Harmer
8.56
3145493TOT1
Solar/Wind Harmer
0.412
3145453TOT5
Solar/Wind Harmer
0.247
3145603CNETO
Solar/Wind Harmer
0.165
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.506
971775AH1-396 GEN
Solar/Wind Harmer
0.281
958211AF2-115 GEN
Solar/Wind Harmer
2.099
963191AG1-168 GEN
Solar/Wind Harmer
0.7
3144293JTRSVLE
Adder
0.557
3144293JTRSVLE
Adder
0.469
3147133PAMPLIN
Solar/Wind Harmer
0.174
3147133PAMPLIN
Solar/Wind Harmer
0.139
961601AG1-000A GEN
Solar/Wind Harmer
3.1
316263AC1-034 GEN
Solar/Wind Harmer
6.622
962561AG1-105 GEN
Solar/Wind Harmer
8.133
964791AG1-342 GEN
Solar/Wind Harmer
3.227
3146843MT LREL
Solar/Wind Harmer
0.168
3146843MT LREL
Solar/Wind Harmer
0.168
3146776BUCKING
Solar/Wind Harmer
0.66
3146776BUCKING
Solar/Wind Harmer
0.053
971489AH1-241 GEN
Solar/Wind Harmer
7.84
316222AC1-221 GEN
Solar/Wind Harmer
0.61
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
6.812
316447AC1-158 HLD
Solar/Wind Helper
4.161
LAGNLTFEXP_LAGN->PJM
CLTF
8.007
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.726
TVALTFEXP_TVA->PJM
CLTF
4.059
NYPJM->LTFIMP_NY
CLTF
3.144
LGEELTFEXP_LGEE->PJM
CLTF
1.356
WECLTFEXP_WEC->PJM
CLTF
0.657
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.991
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.831
MECLTFEXP_MEC->PJM
CLTF
3.667
SIGELTFEXP_SIGE->PJM
CLTF
0.112
CPLELTFEXP_CPLE->PJM
CLTF
11.252
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.535

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:146.98 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:3589.45
MW Contribution:9.5
Bus #Bus NameTypeMW Contribution
972263AH1-716 GEN
50/50
238.379
3151081ELIZAR1
50/50
34.239
3151091ELIZAR2
50/50
33.645
941591AE2-156 GEN
50/50
31.25
3152611GOSPORTB
50/50
4.742
3152621GOSPORTC
50/50
4.025
3152601GOSPORTA
50/50
3.713
957871AF2-081 GEN
Solar/Wind Harmer
17.29
319010AE1-072 C
Solar/Wind Harmer
1.74
3146406KITTY HAWK
Solar/Wind Harmer
0.043
3138283WHITEMARSH
Solar/Wind Harmer
0.08
316305AF2-043 C
Solar/Wind Harmer
0.003
315976AC1-164 GENA
Solar/Wind Harmer
35.232
316169AC1-164_GENC
Solar/Wind Harmer
30.437
315975AC1-164 GENB
Solar/Wind Harmer
1.042
313526AB2-022
Solar/Wind Harmer
0.184
316321Z2-027
Solar/Wind Harmer
0.062
3146396TANGLEW
Solar/Wind Harmer
0.926
3145176PASQUOTANK
Solar/Wind Harmer
0.208
3146486SUNBURY
Solar/Wind Harmer
0.335
3146486SUNBURY
Solar/Wind Harmer
0.335
971445AH1-216 GEN
Solar/Wind Harmer
23.372
315835AF2-110_GEN
Solar/Wind Harmer
2.259
316314AB2-024 C
Solar/Wind Harmer
0.001
972265AH1-717 GEN
Adder
24.957
3151201GRAVEL4
Adder
23.396
3151191GRAVEL3
Adder
23.099
3151211GRAVEL5
Adder
23.099
315611Z1-036_GEN2
Solar/Wind Harmer
0.003
316059AD1-063 C
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.064
315662AE1-191 GEN
Solar/Wind Harmer
0.01
315666AE1-190 GEN
Solar/Wind Harmer
0.003
3130156CHOWAN
Solar/Wind Harmer
0.314
3130156CHOWAN
Solar/Wind Harmer
0.314
970189AG2-124 GEN
Solar/Wind Harmer
9.301
316311AC2-079 GEN
Solar/Wind Harmer
8.93
315833AF1-017_GEN
Solar/Wind Harmer
0.002
316349AD2-085 GEN
Solar/Wind Harmer
0.213
3141913WHIT STONE
Solar/Wind Harmer
0.31
3138133OCRAN
Solar/Wind Harmer
0.092
3143873LANEXA
Solar/Wind Harmer
0.185
3141783LANCAST
Solar/Wind Harmer
0.182
3141783LANCAST
Solar/Wind Harmer
0.122
315816AE2-034 GEN
Solar/Wind Harmer
1.293
962981AG1-147 GEN
Solar/Wind Harmer
11.004
3130546PLYMOUTH
Solar/Wind Harmer
0.291
316369SG1_INVT
Solar/Wind Harmer
0.011
315732AD1-074 GEN1
Solar/Wind Harmer
1.665
315733AD1-074 GEN2
Solar/Wind Harmer
1.665
315735AD1-075 GEN1
Solar/Wind Harmer
0.833
970327AG2-215 GEN
Solar/Wind Harmer
9.499
3146206CASHIE
Solar/Wind Harmer
0.283
970601AG2-382 GEN
Solar/Wind Harmer
10.56
3142433PROV 92
Adder
0.549
3142433PROV 92
Adder
0.549
971167AH1-042 GEN
Solar/Wind Harmer
24.515
965291AG1-394 GEN
Solar/Wind Harmer
1.225
941031AE2-094 GEN
Solar/Wind Harmer
50.437
944011AF1-069 GEN
Solar/Wind Harmer
16.48
316132AB2-190 GEN1
Solar/Wind Harmer
1.466
3145893MURPHYS
Solar/Wind Harmer
0.736
3145893MURPHYS
Solar/Wind Harmer
0.273
3145513AHOSKIE
Solar/Wind Harmer
0.561
3145513AHOSKIE
Solar/Wind Harmer
0.268
970673AG2-436 GEN
Solar/Wind Harmer
57.198
970673AG2-436 GEN
Solar/Wind Harmer
38.132
3145683EARLEYS
Solar/Wind Harmer
0.534
3145683EARLEYS
Solar/Wind Harmer
0.267
3145683EARLEYS
Solar/Wind Harmer
0.267
3141813NORNECK
Solar/Wind Harmer
0.265
971967AH1-528 GEN
Solar/Wind Harmer
41.999
3146043SEABORD
Solar/Wind Harmer
0.257
315607AA1-063A GEN
Solar/Wind Harmer
0.522
316315AB2-025 C
Solar/Wind Harmer
0.206
315814AE2-033 C
Solar/Wind Harmer
20.097
970085AG2-068 GEN
Solar/Wind Harmer
13.326
970581AG2-369 GEN
Solar/Wind Harmer
11.461
3146033SCOT NK
Solar/Wind Harmer
0.989
3143316POE
Solar/Wind Harmer
0.966
315652AC1-086 GEN
Solar/Wind Harmer
26.799
3137643SOCKMAN
Solar/Wind Harmer
0.964
316087AB2-174 GEN
Solar/Wind Harmer
0.007
3145796HORNRTN
Solar/Wind Harmer
0.766
3145796HORNRTN
Solar/Wind Harmer
0.096
316005AA1-067
Solar/Wind Harmer
0.257
3145746EVERETS
Solar/Wind Harmer
0.951
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
970181AG2-120 GEN
Solar/Wind Harmer
2.976
957861AF2-080 GEN
Solar/Wind Harmer
9.959
316420AA1-050 GEN
Solar/Wind Harmer
0.007
3145573BETHELC
Solar/Wind Harmer
0.224
3145573BETHELC
Solar/Wind Harmer
0.224
316319Z2-044 C
Solar/Wind Harmer
0
970831AG2-522 GEN
Solar/Wind Harmer
9.415
316223AC1-118
Solar/Wind Harmer
0.153
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
3.071
3144303KENBRDG
Solar/Wind Harmer
0.146
316118AC1-105 GEN
Solar/Wind Harmer
0.468
3147173SINAI
Solar/Wind Harmer
0.178
3147243WELCO
Solar/Wind Harmer
0.111
971285AH1-108 GEN
Adder
1.342
970683AG2-441 GEN
Solar/Wind Harmer
11.794
970681AG2-440 GEN
Solar/Wind Harmer
9.435
946301AF1-294 GEN
Solar/Wind Harmer
3.39
961791AG1-021 GEN
Solar/Wind Harmer
1.649
316233AE1-074 FULL
Solar/Wind Harmer
0.136
971281AH1-106 GEN
Solar/Wind Harmer
2.362
3150991CHESPKB
50/50
3.902
3150991CHESPKB
50/50
3.808
316185AD1-033 GEN
Solar/Wind Harmer
0.01
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.337
316036AC1-147 C
Solar/Wind Harmer
0.065
3145506HICKORY
Solar/Wind Harmer
1.401
3145506HICKORY
Solar/Wind Harmer
0.841
3145506HICKORY
Solar/Wind Harmer
0.21
316339AD2-160 GEN
Solar/Wind Harmer
0.564
316018AA1-139 ULT2
Solar/Wind Harmer
0.009
316017AA1-139 ULT1
Solar/Wind Harmer
0.194
3137176SLIGO L2192
Solar/Wind Harmer
1.377
3146456SLIGO L269
Solar/Wind Harmer
6.122
3130086AYDLETT
Solar/Wind Harmer
1.379
3146386ELIZ CT
Solar/Wind Harmer
0.339
316236AE1-162_GEN
Solar/Wind Harmer
0.003
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.33
3146516WINFALL
Solar/Wind Harmer
0.33
3146516WINFALL
Solar/Wind Harmer
0.33
3146626S HERTFORD
Solar/Wind Harmer
0.326
3146626S HERTFORD
Solar/Wind Harmer
0.326
3146376EDENTON
Solar/Wind Harmer
1.396
3146376EDENTON
Solar/Wind Harmer
1.396
315742AE1-103 GEN
Solar/Wind Harmer
0.004
316033AB2-134 GEN
Solar/Wind Harmer
0.017
315697AD1-025 GEN
Solar/Wind Harmer
0.327
3142946ENON
Solar/Wind Harmer
0.028
316065AD1-022 GEN
Solar/Wind Harmer
13.139
970657AG2-426 GEN
Solar/Wind Harmer
9.959
970657AG2-426 GEN
Solar/Wind Harmer
2.088
958261AF2-120 GEN
Solar/Wind Harmer
9.287
316075AC2-137 C
Solar/Wind Harmer
0.076
3145893MURPHYS
Solar/Wind Harmer
1.826
3145893MURPHYS
Solar/Wind Harmer
0.491
3146173TUNIS
Solar/Wind Harmer
0.27
3146173TUNIS
Solar/Wind Harmer
0.27
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.78
3150341NORNECKC1
Adder
2.758
972185AH1-677 GEN
Adder
14.884
972187AH1-678 GEN
Adder
7.445
3144356SAPONY
Solar/Wind Harmer
2.128
970933AG2-581 GEN
Solar/Wind Harmer
20.23
3145933PARMELE
Solar/Wind Harmer
0.496
3145933PARMELE
Solar/Wind Harmer
0.248
3142666NORTHAMPTON
Solar/Wind Harmer
0.247
3142666NORTHAMPTON
Solar/Wind Harmer
0.247
3142666NORTHAMPTON
Solar/Wind Harmer
0.247
3142666NORTHAMPTON
Solar/Wind Harmer
0.148
316426AA2-053 GEN
Solar/Wind Harmer
0.834
3145593CAROLNA
Solar/Wind Harmer
0.242
3145593CAROLNA
Solar/Wind Harmer
0.242
966811AG1-552 GEN
Solar/Wind Harmer
2.63
3145593CAROLNA
Solar/Wind Harmer
0.302
3145783HORNRTN
Solar/Wind Harmer
4.289
3145783HORNRTN
Solar/Wind Harmer
3.432
3145783HORNRTN
Solar/Wind Harmer
1.072
3145783HORNRTN
Solar/Wind Harmer
0.429
316181AB2-040 GEN
Solar/Wind Harmer
0.349
3145796HORNRTN
Solar/Wind Harmer
0.718
316274AC1-208 GEN
Solar/Wind Harmer
1.219
970099AG2-077 GEN
Solar/Wind Harmer
24.387
3145493TOT1
Solar/Wind Harmer
0.519
3145453TOT5
Solar/Wind Harmer
0.311
3145603CNETO
Solar/Wind Harmer
0.208
961601AG1-000A GEN
Solar/Wind Harmer
3.829
316263AC1-034 GEN
Solar/Wind Harmer
8.179
316240AF1-291 C
Solar/Wind Harmer
0.002
944641AF1-129 GEN
Adder
100.049
939181AE1-148 GEN
Solar/Wind Harmer
9.766
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
8.948
971741AH1-377 GEN
Solar/Wind Harmer
18.452
964791AG1-342 GEN
Solar/Wind Harmer
3.551
3146843MT LREL
Solar/Wind Harmer
0.185
3146843MT LREL
Solar/Wind Harmer
0.185
3150691DARBY 3
Adder
13.256
3150701DARBY 4
Adder
13.225
3150681DARBY 2
Adder
13.21
3150671DARBY 1
Adder
13.194
970323AG2-213 GEN
Solar/Wind Harmer
7.78
971775AH1-396 GEN
Solar/Wind Harmer
0.292
316034AC1-036 C
Solar/Wind Harmer
0.013
970301AG2-198 GEN
Solar/Wind Harmer
7.54
971223AH1-071 GEN
Solar/Wind Harmer
1.839
958211AF2-115 GEN
Solar/Wind Harmer
2.062
963191AG1-168 GEN
Solar/Wind Harmer
0.687
3144293JTRSVLE
Adder
0.547
3144293JTRSVLE
Adder
0.461
3143526WINTERP
Solar/Wind Harmer
0.885
3147133PAMPLIN
Solar/Wind Harmer
0.168
3147133PAMPLIN
Solar/Wind Harmer
0.134
316222AC1-221 GEN
Solar/Wind Harmer
0.683
3142366NRTHEST
Adder
0.52
942751AE2-291 GEN
Solar/Wind Harmer
6.426
3146776BUCKING
Solar/Wind Harmer
0.466
3146776BUCKING
Solar/Wind Harmer
0.038
971283AH1-107 GEN
Solar/Wind Harmer
2.362
316312AB1-027
Solar/Wind Harmer
0.304
315657AE1-056 GEN
Solar/Wind Harmer
5.802
944491AF1-114 GEN
Solar/Wind Harmer
0
970865AG2-541 GEN
Solar/Wind Harmer
5.175
316123AC1-075 GEN
Solar/Wind Harmer
0.178
970165AG2-112 GEN
Solar/Wind Harmer
1.056
970163AG2-111 GEN
Solar/Wind Harmer
1.007
970285AG2-188 GEN
Solar/Wind Harmer
9.811
971845AH1-439 GEN
Solar/Wind Harmer
5.401
3150921YORKTN3
50/50
9.838
3144216WINCHST
50/50
1.454
3151101ELIZAR3
50/50
34.678
3151161SURRY 1
50/50
12.347
315773AC2-141 GEN
Solar/Wind Harmer
13.957
316382AG1-145 C
Solar/Wind Harmer
0.003
944581AF1-123 GEN
Solar/Wind Harmer
80.429
944601AF1-125 GEN
Solar/Wind Harmer
79.19
3144873MCLAUGH
Solar/Wind Harmer
0.009
3144536CHRHLND
Solar/Wind Harmer
0.052
3146456SLIGO L269
Solar/Wind Harmer
0.346
971153AH1-033 GEN
Solar/Wind Harmer
3.999
316320Y1-086
Solar/Wind Harmer
0.002
3145336SMITFLD
Solar/Wind Harmer
0.133
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.33
3146626S HERTFORD
Solar/Wind Harmer
0.326
3151221GRAVEL6
Adder
23.369
3151171GRAVELC
Adder
4.496
3141766HARMONY
Solar/Wind Harmer
4.28
316156AD2-030 GEN
Solar/Wind Harmer
0.236
3141873WAN 176
Solar/Wind Harmer
5.657
316280AD1-041 GEN
Solar/Wind Harmer
0.006
3146376EDENTON
Solar/Wind Harmer
0.314
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141843SHACKLE
Adder
1.603
3145273HOLLAND
Solar/Wind Harmer
0.235
961611AG1-000B GEN
Solar/Wind Harmer
8.258
315614AA2-178 GEN
Solar/Wind Harmer
1.724
962971AG1-146 GEN
Solar/Wind Harmer
4.716
971157AH1-035 GEN
Solar/Wind Harmer
3.498
315737AD1-076 GEN
Solar/Wind Harmer
3.727
970661AG2-428 GEN
Solar/Wind Harmer
6.128
970009AG2-005 GEN
Solar/Wind Harmer
2.161
3142946ENON
Solar/Wind Harmer
0.096
315778AD1-151 GEN
Solar/Wind Harmer
22.705
3146206CASHIE
Solar/Wind Harmer
0.283
3142433PROV 92
Adder
0.549
3142433PROV 92
Adder
0.549
316083AB2-161 GEN
Solar/Wind Harmer
0.004
316404AE1-155 C
Solar/Wind Harmer
0.063
970659AG2-427 GEN
Solar/Wind Harmer
2.943
3156081AA2-088 GEN
Solar/Wind Harmer
0.007
3156021HOLLOMANSOL
Solar/Wind Harmer
1.24
3145893MURPHYS
Solar/Wind Harmer
0.457
3145893MURPHYS
Solar/Wind Harmer
0.273
957521AF2-046 GEN
Solar/Wind Harmer
20.241
961681AG1-008 GEN
Solar/Wind Harmer
20.241
970129AG2-093 GEN
Solar/Wind Harmer
16.408
3146173TUNIS
Solar/Wind Harmer
0.27
316463AE2-346 GEN
Solar/Wind Harmer
0.231
316140AB2-099
Solar/Wind Harmer
0.096
962331AG1-082 GEN
Solar/Wind Harmer
2.864
3145963POPLR C
Solar/Wind Harmer
0.267
3150351NORNECKC2
Adder
2.691
315813AE1-149 C
Solar/Wind Harmer
13.997
3146263WOODLND
Solar/Wind Harmer
0.26
316317KELFORD C
Solar/Wind Harmer
0.025
3145823KELFORD
Solar/Wind Harmer
0.257
970133AG2-095 GEN
Solar/Wind Harmer
2.439
970917AG2-570 GEN
Solar/Wind Harmer
22.313
3145933PARMELE
Solar/Wind Harmer
0.248
966801AG1-551 GEN
Solar/Wind Harmer
2.89
3142666NORTHAMPTON
Solar/Wind Harmer
0.247
316365GEN2_N
Solar/Wind Harmer
0.553
313506AB2-031 GEN
Solar/Wind Harmer
0.743
3145796HORNRTN
Solar/Wind Harmer
0.958
3145796HORNRTN
Solar/Wind Harmer
0.239
316210AC1-098 GEN
Solar/Wind Harmer
2.222
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
965281AG1-393 GEN
Solar/Wind Harmer
2.451
970293AG2-193 GEN
Solar/Wind Harmer
2.439
316327AA2-057 GEN
Solar/Wind Harmer
0.342
315724AD1-057 GEN
Solar/Wind Harmer
0.848
3147043LAWRENC
Solar/Wind Harmer
0.135
315839AE2-212 C
Solar/Wind Harmer
0.002
3146073TAR RVR
Solar/Wind Harmer
0.224
3146083TARBORO
Solar/Wind Harmer
0.224
3146233WITAKRS
Solar/Wind Harmer
1.108
3146233WITAKRS
Solar/Wind Harmer
0.15
3138543CONSLDL
Solar/Wind Harmer
0.145
316478AD1-087 GEN
Solar/Wind Harmer
0.759
316486AD2-202 GEN
Solar/Wind Harmer
0.223
961601AG1-000A GEN
Solar/Wind Harmer
15.318
3145543BTLEBRO
Solar/Wind Harmer
0.215
3145543BTLEBRO
Solar/Wind Harmer
0.215
971623AH1-311 GEN
Solar/Wind Harmer
0.43
3143096IRON208
Adder
0.898
3143096IRON208
Adder
0.88
3141906WESTMOR
Solar/Wind Harmer
0.085
316131AB2-060 GEN
Solar/Wind Harmer
0.609
964241AG1-285 GEN
Solar/Wind Harmer
12.68
970737AG2-469 GEN
Solar/Wind Harmer
8.068
315785AD2-033 C
Solar/Wind Harmer
1.5
970257AG2-171 GEN
Solar/Wind Harmer
5.835
959311AF2-222 GEN
Solar/Wind Harmer
16.07
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.598
3150861SPRUNCD
Adder
0.82
970909AG2-566 GEN
Solar/Wind Harmer
1.885
963181AG1-167 GEN
Solar/Wind Harmer
0.687
3144293JTRSVLE
Adder
0.547
3142416OLDCHRC
Solar/Wind Harmer
1.645
3147133PAMPLIN
Solar/Wind Harmer
0.528
971193AH1-056 GEN
Solar/Wind Harmer
10.243
316283AC2-100 C
Solar/Wind Harmer
0.32
971683AH1-343 GEN
Solar/Wind Harmer
5.838
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.088
316313AB2-026
Solar/Wind Harmer
0.085
316258AE1-075 C
Solar/Wind Harmer
0.102
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.047
3146776BUCKING
Solar/Wind Harmer
0.042
3152331SURRY 2
50/50
17.341
971353AH1-157 GEN
50/50
32.652
970017AG2-010 GEN
50/50
24.601
3150981CHESPKA
50/50
4.651
316294AC1-161 GEN
Solar/Wind Harmer
6.621
971317AH1-138 GEN
Solar/Wind Harmer
2.751
3138126ROCKLANDING
Solar/Wind Harmer
0.168
316159AE1-175 C
Solar/Wind Harmer
0.315
944591AF1-124 GEN
Solar/Wind Harmer
80.715
316375AC2-012 GEN
Solar/Wind Harmer
0.009
316388AE2-253 GEN
Solar/Wind Harmer
1.09
3146456SLIGO L269
Solar/Wind Harmer
0.346
316246AF1-032 C
Solar/Wind Harmer
0.154
316072AD1-144
Solar/Wind Harmer
0.123
3145336SMITFLD
Solar/Wind Harmer
1.331
3146516WINFALL
Solar/Wind Harmer
1.07
3146516WINFALL
Solar/Wind Harmer
0.33
316093AE2-104_GEN
Solar/Wind Harmer
5.536
3151171GRAVELC
Adder
3.419
315800Z1-036_GEN1
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
0.064
939411AE1-173 GEN
Solar/Wind Harmer
134.654
3130156CHOWAN
Solar/Wind Harmer
0.314
971777AH1-397 GEN
Solar/Wind Harmer
0.828
3141843SHACKLE
Adder
1.603
961611AG1-000B GEN
Solar/Wind Harmer
16.242
3138133OCRAN
Solar/Wind Harmer
0.185
940641AE2-051 GEN
Solar/Wind Harmer
24.257
3145663CRESWEL
Solar/Wind Harmer
0.843
971163AH1-040 GEN
Solar/Wind Harmer
24.101
971647AH1-324 GEN
Solar/Wind Harmer
12.816
970661AG2-428 GEN
Solar/Wind Harmer
28.811
971069AG2-661 GEN
Solar/Wind Harmer
5.046
962861AG1-135 GEN
Solar/Wind Harmer
9.061
3146206CASHIE
Solar/Wind Harmer
0.283
971547AH1-271 GEN
Solar/Wind Harmer
6.034
3142433PROV 92
Solar/Wind Harmer
1.129
3142433PROV 92
Adder
0.549
3142433PROV 92
Adder
0.549
316381AD1-082 GEN
Solar/Wind Harmer
0.293
970659AG2-427 GEN
Solar/Wind Harmer
13.452
316458AB2-190 GEN2
Solar/Wind Harmer
1.466
3145893MURPHYS
Solar/Wind Harmer
1.091
3145893MURPHYS
Solar/Wind Harmer
1.213
3141726DUNNSVL
Solar/Wind Harmer
1.09
970129AG2-093 GEN
Solar/Wind Harmer
7.721
3146173TUNIS
Solar/Wind Harmer
0.27
3145963POPLR C
Solar/Wind Harmer
0.267
3145683EARLEYS
Solar/Wind Harmer
0.267
3150351NORNECKC2
Adder
2.647
944631AF1-128 GEN
Adder
125.685
316174AB2-169 GEN
Solar/Wind Harmer
0.007
3146263WOODLND
Solar/Wind Harmer
0.26
3145823KELFORD
Solar/Wind Harmer
0.257
970919AG2-571 GEN
Solar/Wind Harmer
8.925
970087AG2-069 GEN
Solar/Wind Harmer
19.989
3146293MARTNCO
Solar/Wind Harmer
0.23
316190AA2-174 GEN
Solar/Wind Harmer
0
316023GEN1_S
Solar/Wind Harmer
0.553
316011AB1-132 GEN
Solar/Wind Harmer
4.429
962571AG1-106 GEN
Solar/Wind Harmer
3.466
3145783HORNRTN
Solar/Wind Harmer
0.241
316337AD2-073 GEN
Solar/Wind Harmer
0.209
3145796HORNRTN
Solar/Wind Harmer
0.79
3145796HORNRTN
Solar/Wind Harmer
0.239
316212AC1-099_GEN
Solar/Wind Harmer
1.239
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
960081AF2-299 GEN
Solar/Wind Harmer
2.29
316494AC1-189 GEN
Solar/Wind Harmer
0.78
971795AH1-408 GEN
Solar/Wind Harmer
15.293
957481AF2-042 GEN
Solar/Wind Harmer
60.968
315671AE2-027_GEN
Solar/Wind Harmer
14.563
315722AD1-056 GEN
Solar/Wind Harmer
1.431
3147043LAWRENC
Adder
2.037
961671AG1-007 GEN
Solar/Wind Harmer
0.034
3146083TARBORO
Solar/Wind Harmer
0.224
3145493TOT1
Solar/Wind Harmer
0.996
3146233WITAKRS
Solar/Wind Harmer
0.879
316129AC1-054 GEN
Solar/Wind Harmer
0.821
315693AD1-088 GEN
Solar/Wind Harmer
10.427
971065AG2-659 GEN
Solar/Wind Harmer
9.224
3145543BTLEBRO
Solar/Wind Harmer
0.215
3145543BTLEBRO
Solar/Wind Harmer
0.172
316359AB2-059 GEN
Solar/Wind Harmer
0.773
316049AB1-081 GEN
Solar/Wind Harmer
1.232
3142053HEARTS
Solar/Wind Harmer
0.379
962491AG1-098 GEN
Solar/Wind Harmer
12.277
3143096IRON208
Adder
0.898
315687AD1-152 GEN
Solar/Wind Harmer
0.007
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3142543TWELFTH
Solar/Wind Harmer
0.018
970401AG2-262 GEN
Solar/Wind Harmer
1.085
3150851SPRUNCC
Adder
0.82
970685AG2-442 GEN
Solar/Wind Harmer
13.21
972135AH1-637 GEN
Solar/Wind Harmer
1.474
3143226MDLTHAN
Solar/Wind Harmer
0.172
963171AG1-166 GEN
Solar/Wind Harmer
0.916
971563AH1-280 GEN
Solar/Wind Harmer
1.832
3144293JTRSVLE
Adder
0.547
3143526WINTERP
Solar/Wind Harmer
0.885
3142416OLDCHRC
Solar/Wind Harmer
0.441
3142416OLDCHRC
Solar/Wind Harmer
0.169
316003AC1-222 GEN
Solar/Wind Harmer
0.004
3146926FARMVIL
Solar/Wind Harmer
0.088
3143336POWHATN
Solar/Wind Harmer
2.408
316336AC2-165 C
Solar/Wind Harmer
0.005
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.047
LAGNLTFEXP_LAGN->PJM
CLTF
7.286
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.32
TVALTFEXP_TVA->PJM
CLTF
3.623
NYPJM->LTFIMP_NY
CLTF
2.157
LGEELTFEXP_LGEE->PJM
CLTF
0.951
WECLTFEXP_WEC->PJM
CLTF
0.477
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.81
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.09
MECLTFEXP_MEC->PJM
CLTF
2.89
SIGELTFEXP_SIGE->PJM
CLTF
0.083
CPLELTFEXP_CPLE->PJM
CLTF
12.747
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.757

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:145.46 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:3552.3
MW Contribution:9.0
Bus #Bus NameTypeMW Contribution
972263AH1-716 GEN
50/50
236.435
3151081ELIZAR1
50/50
34.071
3151091ELIZAR2
50/50
33.48
941591AE2-156 GEN
50/50
31.086
3152611GOSPORTB
50/50
4.716
3152621GOSPORTC
50/50
4.003
3152601GOSPORTA
50/50
3.692
957871AF2-081 GEN
Solar/Wind Harmer
17.231
319010AE1-072 C
Solar/Wind Harmer
1.734
3146406KITTY HAWK
Solar/Wind Harmer
0.043
316305AF2-043 C
Solar/Wind Harmer
0.003
313526AB2-022
Solar/Wind Harmer
0.183
316321Z2-027
Solar/Wind Harmer
0.062
3146396TANGLEW
Solar/Wind Harmer
0.923
3145176PASQUOTANK
Solar/Wind Harmer
0.207
3146486SUNBURY
Solar/Wind Harmer
0.334
3146486SUNBURY
Solar/Wind Harmer
0.334
3138283WHITEMARSH
Solar/Wind Harmer
0.077
315835AF2-110_GEN
Solar/Wind Harmer
2.241
971445AH1-216 GEN
Solar/Wind Harmer
22.847
315611Z1-036_GEN2
Solar/Wind Harmer
0.003
315976AC1-164 GENA
Solar/Wind Harmer
32.93
316169AC1-164_GENC
Solar/Wind Harmer
28.449
315975AC1-164 GENB
Solar/Wind Harmer
0.974
3130156CHOWAN
Solar/Wind Harmer
0.313
3130156CHOWAN
Solar/Wind Harmer
0.313
972265AH1-717 GEN
Adder
24.145
3151201GRAVEL4
Adder
22.635
3151191GRAVEL3
Adder
22.348
3151211GRAVEL5
Adder
22.348
316311AC2-079 GEN
Solar/Wind Harmer
8.775
315833AF1-017_GEN
Solar/Wind Harmer
0.002
316349AD2-085 GEN
Solar/Wind Harmer
0.209
316314AB2-024 C
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.06
315816AE2-034 GEN
Solar/Wind Harmer
1.289
315662AE1-191 GEN
Solar/Wind Harmer
0.01
315666AE1-190 GEN
Solar/Wind Harmer
0.002
970189AG2-124 GEN
Solar/Wind Harmer
8.787
3141913WHIT STONE
Solar/Wind Harmer
0.294
3138133OCRAN
Solar/Wind Harmer
0.088
3130546PLYMOUTH
Solar/Wind Harmer
0.29
315732AD1-074 GEN1
Solar/Wind Harmer
1.66
315733AD1-074 GEN2
Solar/Wind Harmer
1.66
315735AD1-075 GEN1
Solar/Wind Harmer
0.831
3141783LANCAST
Solar/Wind Harmer
0.173
3141783LANCAST
Solar/Wind Harmer
0.115
3143873LANEXA
Solar/Wind Harmer
0.173
941031AE2-094 GEN
Solar/Wind Harmer
52.388
944011AF1-069 GEN
Solar/Wind Harmer
17.117
3146206CASHIE
Solar/Wind Harmer
0.282
970601AG2-382 GEN
Solar/Wind Harmer
10.532
962981AG1-147 GEN
Solar/Wind Harmer
10.429
970673AG2-436 GEN
Solar/Wind Harmer
59.327
970673AG2-436 GEN
Solar/Wind Harmer
39.552
316369SG1_INVT
Solar/Wind Harmer
0.01
965291AG1-394 GEN
Solar/Wind Harmer
1.219
970327AG2-215 GEN
Solar/Wind Harmer
8.996
3145893MURPHYS
Solar/Wind Harmer
0.733
3145893MURPHYS
Solar/Wind Harmer
0.271
971967AH1-528 GEN
Solar/Wind Harmer
43.419
3145513AHOSKIE
Solar/Wind Harmer
0.56
3145513AHOSKIE
Solar/Wind Harmer
0.267
3145683EARLEYS
Solar/Wind Harmer
0.533
3145683EARLEYS
Solar/Wind Harmer
0.266
3145683EARLEYS
Solar/Wind Harmer
0.266
3142433PROV 92
Adder
0.504
3142433PROV 92
Adder
0.504
970085AG2-068 GEN
Solar/Wind Harmer
13.776
970581AG2-369 GEN
Solar/Wind Harmer
11.847
3146043SEABORD
Solar/Wind Harmer
0.256
315607AA1-063A GEN
Solar/Wind Harmer
0.52
316132AB2-190 GEN1
Solar/Wind Harmer
1.358
316315AB2-025 C
Solar/Wind Harmer
0.204
971167AH1-042 GEN
Solar/Wind Harmer
22.411
315814AE2-033 C
Solar/Wind Harmer
19.96
3141813NORNECK
Solar/Wind Harmer
0.25
3146033SCOT NK
Solar/Wind Harmer
0.988
315652AC1-086 GEN
Solar/Wind Harmer
26.724
3137643SOCKMAN
Solar/Wind Harmer
0.96
316005AA1-067
Solar/Wind Harmer
0.257
3145746EVERETS
Solar/Wind Harmer
0.952
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
970181AG2-120 GEN
Solar/Wind Harmer
2.978
3145796HORNRTN
Solar/Wind Harmer
0.765
3145796HORNRTN
Solar/Wind Harmer
0.096
316087AB2-174 GEN
Solar/Wind Harmer
0.007
3143316POE
Solar/Wind Harmer
0.921
957861AF2-080 GEN
Solar/Wind Harmer
9.971
316420AA1-050 GEN
Solar/Wind Harmer
0.007
3145573BETHELC
Solar/Wind Harmer
0.224
3145573BETHELC
Solar/Wind Harmer
0.224
316319Z2-044 C
Solar/Wind Harmer
0
970831AG2-522 GEN
Solar/Wind Harmer
9.375
316223AC1-118
Solar/Wind Harmer
0.144
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.467
3147173SINAI
Solar/Wind Harmer
0.178
3147243WELCO
Solar/Wind Harmer
0.111
971443AH1-215 GEN
Solar/Wind Harmer
2.94
3144303KENBRDG
Solar/Wind Harmer
0.139
970683AG2-441 GEN
Solar/Wind Harmer
11.135
970681AG2-440 GEN
Solar/Wind Harmer
8.908
946301AF1-294 GEN
Solar/Wind Harmer
3.16
961791AG1-021 GEN
Solar/Wind Harmer
1.537
315657AE1-056 GEN
Solar/Wind Harmer
5.357
970865AG2-541 GEN
Solar/Wind Harmer
5.15
3152331SURRY 2
50/50
17.238
971353AH1-157 GEN
50/50
31.744
970017AG2-010 GEN
50/50
24.039
3150981CHESPKA
50/50
4.626
316294AC1-161 GEN
Solar/Wind Harmer
6.631
971317AH1-138 GEN
Solar/Wind Harmer
2.676
944591AF1-124 GEN
Solar/Wind Harmer
80.586
3138126ROCKLANDING
Solar/Wind Harmer
0.164
316159AE1-175 C
Solar/Wind Harmer
0.304
316375AC2-012 GEN
Solar/Wind Harmer
0.009
316388AE2-253 GEN
Solar/Wind Harmer
1.086
3146456SLIGO L269
Solar/Wind Harmer
0.345
316246AF1-032 C
Solar/Wind Harmer
0.153
316072AD1-144
Solar/Wind Harmer
0.122
3146516WINFALL
Solar/Wind Harmer
1.066
3146516WINFALL
Solar/Wind Harmer
0.329
316093AE2-104_GEN
Solar/Wind Harmer
5.492
3145336SMITFLD
Solar/Wind Harmer
1.303
939411AE1-173 GEN
Solar/Wind Harmer
137.667
315800Z1-036_GEN1
Solar/Wind Harmer
0.003
3130156CHOWAN
Solar/Wind Harmer
0.313
940641AE2-051 GEN
Solar/Wind Harmer
25.037
3151171GRAVELC
Adder
3.308
3141766HARMONY
Solar/Wind Harmer
0.061
3145663CRESWEL
Solar/Wind Harmer
0.84
971163AH1-040 GEN
Solar/Wind Harmer
24.028
961611AG1-000B GEN
Solar/Wind Harmer
15.572
971777AH1-397 GEN
Solar/Wind Harmer
0.783
3141843SHACKLE
Adder
1.515
3138133OCRAN
Solar/Wind Harmer
0.176
971647AH1-324 GEN
Solar/Wind Harmer
12.191
3146206CASHIE
Solar/Wind Harmer
0.282
971547AH1-271 GEN
Solar/Wind Harmer
6.019
970661AG2-428 GEN
Solar/Wind Harmer
27.952
3145893MURPHYS
Solar/Wind Harmer
1.086
3145893MURPHYS
Solar/Wind Harmer
1.208
316381AD1-082 GEN
Solar/Wind Harmer
0.283
3146173TUNIS
Solar/Wind Harmer
0.269
962861AG1-135 GEN
Solar/Wind Harmer
8.574
970659AG2-427 GEN
Solar/Wind Harmer
12.95
3145963POPLR C
Solar/Wind Harmer
0.267
3145683EARLEYS
Solar/Wind Harmer
0.266
971069AG2-661 GEN
Solar/Wind Harmer
4.727
3150921YORKTN3
50/50
9.609
3144216WINCHST
50/50
1.419
3151101ELIZAR3
50/50
34.507
3151161SURRY 1
50/50
11.945
315773AC2-141 GEN
Solar/Wind Harmer
13.978
944581AF1-123 GEN
Solar/Wind Harmer
80.3
944601AF1-125 GEN
Solar/Wind Harmer
79.064
316382AG1-145 C
Solar/Wind Harmer
0.003
3144873MCLAUGH
Solar/Wind Harmer
0.009
3146456SLIGO L269
Solar/Wind Harmer
0.345
971153AH1-033 GEN
Solar/Wind Harmer
3.986
3144536CHRHLND
Solar/Wind Harmer
0.051
316320Y1-086
Solar/Wind Harmer
0.002
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.329
3145336SMITFLD
Solar/Wind Harmer
0.13
3146626S HERTFORD
Solar/Wind Harmer
0.325
3146376EDENTON
Solar/Wind Harmer
0.313
3145273HOLLAND
Solar/Wind Harmer
0.233
3151221GRAVEL6
Adder
22.609
3151171GRAVELC
Adder
4.35
3141766HARMONY
Solar/Wind Harmer
4.054
316156AD2-030 GEN
Solar/Wind Harmer
0.224
3141873WAN 176
Solar/Wind Harmer
5.376
315614AA2-178 GEN
Solar/Wind Harmer
1.719
316280AD1-041 GEN
Solar/Wind Harmer
0.006
961611AG1-000B GEN
Solar/Wind Harmer
7.918
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141843SHACKLE
Adder
1.515
971157AH1-035 GEN
Solar/Wind Harmer
3.489
315737AD1-076 GEN
Solar/Wind Harmer
3.717
3146206CASHIE
Solar/Wind Harmer
0.282
970661AG2-428 GEN
Solar/Wind Harmer
5.945
962971AG1-146 GEN
Solar/Wind Harmer
4.47
3156081AA2-088 GEN
Solar/Wind Harmer
0.007
970009AG2-005 GEN
Solar/Wind Harmer
2.047
3156021HOLLOMANSOL
Solar/Wind Harmer
1.237
3145893MURPHYS
Solar/Wind Harmer
0.455
3145893MURPHYS
Solar/Wind Harmer
0.271
316083AB2-161 GEN
Solar/Wind Harmer
0.004
957521AF2-046 GEN
Solar/Wind Harmer
20.157
961681AG1-008 GEN
Solar/Wind Harmer
20.157
3146173TUNIS
Solar/Wind Harmer
0.269
970659AG2-427 GEN
Solar/Wind Harmer
2.833
316463AE2-346 GEN
Solar/Wind Harmer
0.23
316140AB2-099
Solar/Wind Harmer
0.096
962331AG1-082 GEN
Solar/Wind Harmer
2.855
3145963POPLR C
Solar/Wind Harmer
0.267
315778AD1-151 GEN
Solar/Wind Harmer
21.272
316404AE1-155 C
Solar/Wind Harmer
0.06
3146263WOODLND
Solar/Wind Harmer
0.259
970917AG2-570 GEN
Solar/Wind Harmer
23.07
3142433PROV 92
Adder
0.504
3142433PROV 92
Adder
0.504
3142946ENON
Solar/Wind Harmer
0.086
316317KELFORD C
Solar/Wind Harmer
0.025
3145823KELFORD
Solar/Wind Harmer
0.257
970129AG2-093 GEN
Solar/Wind Harmer
15.176
3150351NORNECKC2
Adder
2.54
315813AE1-149 C
Solar/Wind Harmer
13.315
3145933PARMELE
Solar/Wind Harmer
0.248
966801AG1-551 GEN
Solar/Wind Harmer
2.89
3142666NORTHAMPTON
Solar/Wind Harmer
0.246
316365GEN2_N
Solar/Wind Harmer
0.55
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
316210AC1-098 GEN
Solar/Wind Harmer
2.22
313506AB2-031 GEN
Solar/Wind Harmer
0.739
3145796HORNRTN
Solar/Wind Harmer
0.956
3145796HORNRTN
Solar/Wind Harmer
0.239
970133AG2-095 GEN
Solar/Wind Harmer
2.211
316327AA2-057 GEN
Solar/Wind Harmer
0.342
315724AD1-057 GEN
Solar/Wind Harmer
0.849
3146073TAR RVR
Solar/Wind Harmer
0.224
3146083TARBORO
Solar/Wind Harmer
0.224
3147043LAWRENC
Solar/Wind Harmer
0.134
3146233WITAKRS
Solar/Wind Harmer
1.11
3146233WITAKRS
Solar/Wind Harmer
0.15
3138543CONSLDL
Solar/Wind Harmer
0.145
316478AD1-087 GEN
Solar/Wind Harmer
0.767
316486AD2-202 GEN
Solar/Wind Harmer
0.225
961601AG1-000A GEN
Solar/Wind Harmer
15.354
3145543BTLEBRO
Solar/Wind Harmer
0.216
3145543BTLEBRO
Solar/Wind Harmer
0.216
971623AH1-311 GEN
Solar/Wind Harmer
0.431
965281AG1-393 GEN
Solar/Wind Harmer
2.229
315839AE2-212 C
Solar/Wind Harmer
0.002
3141906WESTMOR
Solar/Wind Harmer
0.08
970293AG2-193 GEN
Solar/Wind Harmer
2.109
316131AB2-060 GEN
Solar/Wind Harmer
0.596
964241AG1-285 GEN
Solar/Wind Harmer
12.329
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.602
315785AD2-033 C
Solar/Wind Harmer
1.441
970737AG2-469 GEN
Solar/Wind Harmer
7.562
970257AG2-171 GEN
Solar/Wind Harmer
5.579
3143096IRON208
Adder
0.724
3143096IRON208
Adder
0.71
959311AF2-222 GEN
Solar/Wind Harmer
15.31
316283AC2-100 C
Solar/Wind Harmer
0.323
970909AG2-566 GEN
Solar/Wind Harmer
1.761
963181AG1-167 GEN
Solar/Wind Harmer
0.641
3144293JTRSVLE
Adder
0.51
971683AH1-343 GEN
Solar/Wind Harmer
5.822
3147133PAMPLIN
Solar/Wind Harmer
0.487
971193AH1-056 GEN
Solar/Wind Harmer
9.458
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3142416OLDCHRC
Solar/Wind Harmer
1.369
3146926FARMVIL
Solar/Wind Harmer
0.076
3150861SPRUNCD
Adder
0.53
316174AB2-169 GEN
Solar/Wind Harmer
0.007
3146263WOODLND
Solar/Wind Harmer
0.259
970919AG2-571 GEN
Solar/Wind Harmer
9.228
3142433PROV 92
Solar/Wind Harmer
1.037
3142433PROV 92
Adder
0.504
3142433PROV 92
Adder
0.504
970087AG2-069 GEN
Solar/Wind Harmer
20.664
3141726DUNNSVL
Solar/Wind Harmer
1.028
3145823KELFORD
Solar/Wind Harmer
0.257
316458AB2-190 GEN2
Solar/Wind Harmer
1.358
970129AG2-093 GEN
Solar/Wind Harmer
7.142
3150351NORNECKC2
Adder
2.498
3146293MARTNCO
Solar/Wind Harmer
0.23
316190AA2-174 GEN
Solar/Wind Harmer
0
316023GEN1_S
Solar/Wind Harmer
0.55
316011AB1-132 GEN
Solar/Wind Harmer
4.417
962571AG1-106 GEN
Solar/Wind Harmer
3.457
3145783HORNRTN
Solar/Wind Harmer
0.24
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
316212AC1-099_GEN
Solar/Wind Harmer
1.238
3145796HORNRTN
Solar/Wind Harmer
0.788
3145796HORNRTN
Solar/Wind Harmer
0.239
960081AF2-299 GEN
Solar/Wind Harmer
2.276
944631AF1-128 GEN
Adder
111.457
957481AF2-042 GEN
Solar/Wind Harmer
61.861
316494AC1-189 GEN
Solar/Wind Harmer
0.781
971795AH1-408 GEN
Solar/Wind Harmer
15.163
316337AD2-073 GEN
Solar/Wind Harmer
0.197
315722AD1-056 GEN
Solar/Wind Harmer
1.431
961671AG1-007 GEN
Solar/Wind Harmer
0.034
3146083TARBORO
Solar/Wind Harmer
0.224
3145493TOT1
Solar/Wind Harmer
0.997
3147043LAWRENC
Adder
2.017
3146233WITAKRS
Solar/Wind Harmer
0.88
315693AD1-088 GEN
Solar/Wind Harmer
10.438
316129AC1-054 GEN
Solar/Wind Harmer
0.818
3145543BTLEBRO
Solar/Wind Harmer
0.216
3145543BTLEBRO
Solar/Wind Harmer
0.172
316359AB2-059 GEN
Solar/Wind Harmer
0.775
316049AB1-081 GEN
Solar/Wind Harmer
1.235
3142053HEARTS
Solar/Wind Harmer
0.38
971065AG2-659 GEN
Solar/Wind Harmer
9.183
962491AG1-098 GEN
Solar/Wind Harmer
12.255
315687AD1-152 GEN
Solar/Wind Harmer
0.007
315671AE2-027_GEN
Solar/Wind Harmer
13.142
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970401AG2-262 GEN
Solar/Wind Harmer
1.076
3143096IRON208
Adder
0.724
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970685AG2-442 GEN
Solar/Wind Harmer
12.471
972135AH1-637 GEN
Solar/Wind Harmer
1.379
963171AG1-166 GEN
Solar/Wind Harmer
0.854
971563AH1-280 GEN
Solar/Wind Harmer
1.708
3144293JTRSVLE
Adder
0.51
3142543TWELFTH
Solar/Wind Harmer
0.014
3142416OLDCHRC
Solar/Wind Harmer
0.367
3142416OLDCHRC
Solar/Wind Harmer
0.141
3146926FARMVIL
Solar/Wind Harmer
0.076
3150851SPRUNCC
Adder
0.53
3150991CHESPKB
50/50
3.881
3150991CHESPKB
50/50
3.787
316185AD1-033 GEN
Solar/Wind Harmer
0.01
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.335
3145506HICKORY
Solar/Wind Harmer
1.396
3145506HICKORY
Solar/Wind Harmer
0.838
3145506HICKORY
Solar/Wind Harmer
0.21
316036AC1-147 C
Solar/Wind Harmer
0.065
316339AD2-160 GEN
Solar/Wind Harmer
0.562
316312AB1-027
Solar/Wind Harmer
0.253
944491AF1-114 GEN
Solar/Wind Harmer
0
316123AC1-075 GEN
Solar/Wind Harmer
0.176
970165AG2-112 GEN
Solar/Wind Harmer
1.046
970163AG2-111 GEN
Solar/Wind Harmer
0.997
971285AH1-108 GEN
Adder
0.868
316018AA1-139 ULT2
Solar/Wind Harmer
0.009
316017AA1-139 ULT1
Solar/Wind Harmer
0.193
3137176SLIGO L2192
Solar/Wind Harmer
1.372
3146456SLIGO L269
Solar/Wind Harmer
6.101
3130086AYDLETT
Solar/Wind Harmer
1.375
3146386ELIZ CT
Solar/Wind Harmer
0.338
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.329
3146516WINFALL
Solar/Wind Harmer
0.329
3146516WINFALL
Solar/Wind Harmer
0.329
316236AE1-162_GEN
Solar/Wind Harmer
0.003
3146626S HERTFORD
Solar/Wind Harmer
0.325
3146626S HERTFORD
Solar/Wind Harmer
0.325
3146376EDENTON
Solar/Wind Harmer
1.391
3146376EDENTON
Solar/Wind Harmer
1.391
315742AE1-103 GEN
Solar/Wind Harmer
0.004
316065AD1-022 GEN
Solar/Wind Harmer
13.104
970657AG2-426 GEN
Solar/Wind Harmer
9.628
970657AG2-426 GEN
Solar/Wind Harmer
2.018
972185AH1-677 GEN
Adder
15.426
316033AB2-134 GEN
Solar/Wind Harmer
0.016
315697AD1-025 GEN
Solar/Wind Harmer
0.309
3145893MURPHYS
Solar/Wind Harmer
1.818
3145893MURPHYS
Solar/Wind Harmer
0.489
972187AH1-678 GEN
Adder
7.708
3146173TUNIS
Solar/Wind Harmer
0.269
3146173TUNIS
Solar/Wind Harmer
0.269
958261AF2-120 GEN
Solar/Wind Harmer
8.785
970933AG2-581 GEN
Solar/Wind Harmer
20.809
3142946ENON
Solar/Wind Harmer
0.026
3144356SAPONY
Solar/Wind Harmer
2.113
316075AC2-137 C
Solar/Wind Harmer
0.069
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.624
3150341NORNECKC1
Adder
2.603
3145933PARMELE
Solar/Wind Harmer
0.496
3145933PARMELE
Solar/Wind Harmer
0.248
3142666NORTHAMPTON
Solar/Wind Harmer
0.246
3142666NORTHAMPTON
Solar/Wind Harmer
0.246
3142666NORTHAMPTON
Solar/Wind Harmer
0.246
3142666NORTHAMPTON
Solar/Wind Harmer
0.148
316426AA2-053 GEN
Solar/Wind Harmer
0.831
3145593CAROLNA
Solar/Wind Harmer
0.241
3145593CAROLNA
Solar/Wind Harmer
0.241
966811AG1-552 GEN
Solar/Wind Harmer
2.62
3145593CAROLNA
Solar/Wind Harmer
0.301
3145783HORNRTN
Solar/Wind Harmer
4.275
3145783HORNRTN
Solar/Wind Harmer
3.42
3145783HORNRTN
Solar/Wind Harmer
1.069
3145783HORNRTN
Solar/Wind Harmer
0.428
316181AB2-040 GEN
Solar/Wind Harmer
0.347
3145796HORNRTN
Solar/Wind Harmer
0.717
316274AC1-208 GEN
Solar/Wind Harmer
1.217
970099AG2-077 GEN
Solar/Wind Harmer
24.744
3145493TOT1
Solar/Wind Harmer
0.52
3145453TOT5
Solar/Wind Harmer
0.312
3145603CNETO
Solar/Wind Harmer
0.208
961601AG1-000A GEN
Solar/Wind Harmer
3.839
316263AC1-034 GEN
Solar/Wind Harmer
8.198
939181AE1-148 GEN
Solar/Wind Harmer
9.694
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316240AF1-291 C
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
8.858
944641AF1-129 GEN
Adder
87.436
964791AG1-342 GEN
Solar/Wind Harmer
3.522
3146843MT LREL
Solar/Wind Harmer
0.183
3146843MT LREL
Solar/Wind Harmer
0.183
971741AH1-377 GEN
Solar/Wind Harmer
17.569
970323AG2-213 GEN
Solar/Wind Harmer
7.438
971775AH1-396 GEN
Solar/Wind Harmer
0.279
316034AC1-036 C
Solar/Wind Harmer
0.013
316222AC1-221 GEN
Solar/Wind Harmer
0.689
970301AG2-198 GEN
Solar/Wind Harmer
7.044
958211AF2-115 GEN
Solar/Wind Harmer
1.922
963191AG1-168 GEN
Solar/Wind Harmer
0.641
3144293JTRSVLE
Adder
0.51
3144293JTRSVLE
Adder
0.429
3147133PAMPLIN
Solar/Wind Harmer
0.155
3147133PAMPLIN
Solar/Wind Harmer
0.124
3150691DARBY 3
Adder
10.708
3150701DARBY 4
Adder
10.683
3150681DARBY 2
Adder
10.671
3150671DARBY 1
Adder
10.658
3142366NRTHEST
Adder
0.396
942751AE2-291 GEN
Solar/Wind Harmer
6.34
LAGNLTFEXP_LAGN->PJM
CLTF
7.278
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.541
TVALTFEXP_TVA->PJM
CLTF
3.613
NYPJM->LTFIMP_NY
CLTF
2.077
LGEELTFEXP_LGEE->PJM
CLTF
0.931
WECLTFEXP_WEC->PJM
CLTF
0.469
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.522
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.042
MECLTFEXP_MEC->PJM
CLTF
2.857
SIGELTFEXP_SIGE->PJM
CLTF
0.082
CPLELTFEXP_CPLE->PJM
CLTF
12.886
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.58

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.62 %
Rating:2442.12 MVA
Rating Type:A
MVA to Mitigate:2506.2
MW Contribution:8.24
Bus #Bus NameTypeMW Contribution
972263AH1-716 GEN
50/50
204.764
3151081ELIZAR1
50/50
27.927
3151091ELIZAR2
50/50
27.442
941591AE2-156 GEN
50/50
25.486
3152611GOSPORTB
50/50
3.867
3152621GOSPORTC
50/50
3.282
3152601GOSPORTA
50/50
3.027
315759AF1-018 GEN
50/50
9.884
315976AC1-164 GENA
Solar/Wind Harmer
30.824
316169AC1-164_GENC
Solar/Wind Harmer
26.629
315975AC1-164 GENB
Solar/Wind Harmer
0.912
3138283WHITEMARSH
Solar/Wind Harmer
0.068
957871AF2-081 GEN
Solar/Wind Harmer
14.058
319010AE1-072 C
Solar/Wind Harmer
1.413
3146406KITTY HAWK
Solar/Wind Harmer
0.035
316314AB2-024 C
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.002
316305AF2-043 C
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.149
3141873WAN 176
Solar/Wind Harmer
0.055
315662AE1-191 GEN
Solar/Wind Harmer
0.009
315666AE1-190 GEN
Solar/Wind Harmer
0.002
316321Z2-027
Solar/Wind Harmer
0.05
3146396TANGLEW
Solar/Wind Harmer
0.749
3145176PASQUOTANK
Solar/Wind Harmer
0.168
3146486SUNBURY
Solar/Wind Harmer
0.271
3146486SUNBURY
Solar/Wind Harmer
0.271
971445AH1-216 GEN
Solar/Wind Harmer
19.042
970189AG2-124 GEN
Solar/Wind Harmer
8.003
3141913WHIT STONE
Solar/Wind Harmer
0.268
3138133OCRAN
Solar/Wind Harmer
0.08
315835AF2-110_GEN
Solar/Wind Harmer
1.817
3143873LANEXA
Solar/Wind Harmer
0.158
3141783LANCAST
Solar/Wind Harmer
0.158
3141783LANCAST
Solar/Wind Harmer
0.105
972265AH1-717 GEN
Adder
20.32
3151201GRAVEL4
Adder
19.048
3151191GRAVEL3
Adder
18.807
3151211GRAVEL5
Adder
18.807
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
962981AG1-147 GEN
Solar/Wind Harmer
9.537
970327AG2-215 GEN
Solar/Wind Harmer
8.242
3130156CHOWAN
Solar/Wind Harmer
0.251
3130156CHOWAN
Solar/Wind Harmer
0.251
316311AC2-079 GEN
Solar/Wind Harmer
7.083
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.169
315816AE2-034 GEN
Solar/Wind Harmer
1.025
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
316369SG1_INVT
Solar/Wind Harmer
0.009
3141813NORNECK
Solar/Wind Harmer
0.232
971167AH1-042 GEN
Solar/Wind Harmer
20.385
3130546PLYMOUTH
Solar/Wind Harmer
0.229
315732AD1-074 GEN1
Solar/Wind Harmer
1.309
315733AD1-074 GEN2
Solar/Wind Harmer
1.309
315735AD1-075 GEN1
Solar/Wind Harmer
0.655
3146206CASHIE
Solar/Wind Harmer
0.221
970601AG2-382 GEN
Solar/Wind Harmer
8.257
316132AB2-190 GEN1
Solar/Wind Harmer
1.162
965291AG1-394 GEN
Solar/Wind Harmer
0.947
3145893MURPHYS
Solar/Wind Harmer
0.569
3145893MURPHYS
Solar/Wind Harmer
0.211
3145513AHOSKIE
Solar/Wind Harmer
0.433
3145513AHOSKIE
Solar/Wind Harmer
0.207
3145683EARLEYS
Solar/Wind Harmer
0.411
3145683EARLEYS
Solar/Wind Harmer
0.206
3145683EARLEYS
Solar/Wind Harmer
0.206
3146043SEABORD
Solar/Wind Harmer
0.195
315607AA1-063A GEN
Solar/Wind Harmer
0.395
941031AE2-094 GEN
Solar/Wind Harmer
35.093
944011AF1-069 GEN
Solar/Wind Harmer
11.466
316223AC1-118
Solar/Wind Harmer
0.135
3146033SCOT NK
Solar/Wind Harmer
0.749
970673AG2-436 GEN
Solar/Wind Harmer
39.792
970673AG2-436 GEN
Solar/Wind Harmer
26.528
316315AB2-025 C
Solar/Wind Harmer
0.148
315814AE2-033 C
Solar/Wind Harmer
14.447
971967AH1-528 GEN
Solar/Wind Harmer
29.182
316005AA1-067
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.721
3145746EVERETS
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
315652AC1-086 GEN
Solar/Wind Harmer
19.936
970181AG2-120 GEN
Solar/Wind Harmer
2.256
3137643SOCKMAN
Solar/Wind Harmer
0.715
3145796HORNRTN
Solar/Wind Harmer
0.569
3145796HORNRTN
Solar/Wind Harmer
0.071
3143316POE
Solar/Wind Harmer
0.699
316087AB2-174 GEN
Solar/Wind Harmer
0.005
970085AG2-068 GEN
Solar/Wind Harmer
9.275
970581AG2-369 GEN
Solar/Wind Harmer
7.976
957861AF2-080 GEN
Solar/Wind Harmer
7.482
316420AA1-050 GEN
Solar/Wind Harmer
0.006
3145573BETHELC
Solar/Wind Harmer
0.167
3145573BETHELC
Solar/Wind Harmer
0.167
316319Z2-044 C
Solar/Wind Harmer
0
970831AG2-522 GEN
Solar/Wind Harmer
6.814
944491AF1-114 GEN
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316312AB1-027
Solar/Wind Harmer
0.237
316118AC1-105 GEN
Solar/Wind Harmer
0.324
971443AH1-215 GEN
Solar/Wind Harmer
2.1
3144303KENBRDG
Solar/Wind Harmer
0.1
3147173SINAI
Solar/Wind Harmer
0.123
3147243WELCO
Solar/Wind Harmer
0.077
970683AG2-441 GEN
Solar/Wind Harmer
7.989
970681AG2-440 GEN
Solar/Wind Harmer
6.391
971285AH1-108 GEN
Adder
0.879
946301AF1-294 GEN
Solar/Wind Harmer
2.276
961791AG1-021 GEN
Solar/Wind Harmer
1.107
3150991CHESPKB
50/50
3.182
3150991CHESPKB
50/50
3.105
316185AD1-033 GEN
Solar/Wind Harmer
0.008
3142956BIRDNECK
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.053
316316AC1-027 C
Solar/Wind Harmer
0.275
3145506HICKORY
Solar/Wind Harmer
1.141
3145506HICKORY
Solar/Wind Harmer
0.684
3145506HICKORY
Solar/Wind Harmer
0.171
316339AD2-160 GEN
Solar/Wind Harmer
0.459
316018AA1-139 ULT2
Solar/Wind Harmer
0.007
316017AA1-139 ULT1
Solar/Wind Harmer
0.158
3137176SLIGO L2192
Solar/Wind Harmer
1.119
3146456SLIGO L269
Solar/Wind Harmer
4.975
3130086AYDLETT
Solar/Wind Harmer
1.12
3146386ELIZ CT
Solar/Wind Harmer
0.274
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.266
3146516WINFALL
Solar/Wind Harmer
0.266
3146516WINFALL
Solar/Wind Harmer
0.266
3146626S HERTFORD
Solar/Wind Harmer
0.262
3146626S HERTFORD
Solar/Wind Harmer
0.262
3146376EDENTON
Solar/Wind Harmer
1.115
3146376EDENTON
Solar/Wind Harmer
1.115
958261AF2-120 GEN
Solar/Wind Harmer
8.075
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3142946ENON
Solar/Wind Harmer
0.024
316075AC2-137 C
Solar/Wind Harmer
0.065
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.262
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.426
3150341NORNECKC1
Adder
2.407
316065AD1-022 GEN
Solar/Wind Harmer
10.294
970657AG2-426 GEN
Solar/Wind Harmer
7.712
970657AG2-426 GEN
Solar/Wind Harmer
1.617
3145893MURPHYS
Solar/Wind Harmer
1.41
3145893MURPHYS
Solar/Wind Harmer
0.379
3146173TUNIS
Solar/Wind Harmer
0.208
3146173TUNIS
Solar/Wind Harmer
0.208
3145933PARMELE
Solar/Wind Harmer
0.379
3145933PARMELE
Solar/Wind Harmer
0.189
316426AA2-053 GEN
Solar/Wind Harmer
0.625
3142666NORTHAMPTON
Solar/Wind Harmer
0.185
3142666NORTHAMPTON
Solar/Wind Harmer
0.185
3142666NORTHAMPTON
Solar/Wind Harmer
0.185
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
972185AH1-677 GEN
Adder
10.353
3144356SAPONY
Solar/Wind Harmer
1.528
972187AH1-678 GEN
Adder
5.178
3145593CAROLNA
Solar/Wind Harmer
0.18
3145593CAROLNA
Solar/Wind Harmer
0.18
966811AG1-552 GEN
Solar/Wind Harmer
1.959
3145593CAROLNA
Solar/Wind Harmer
0.225
3145783HORNRTN
Solar/Wind Harmer
3.196
3145783HORNRTN
Solar/Wind Harmer
2.557
3145783HORNRTN
Solar/Wind Harmer
0.799
3145783HORNRTN
Solar/Wind Harmer
0.32
3145796HORNRTN
Solar/Wind Harmer
0.534
316181AB2-040 GEN
Solar/Wind Harmer
0.257
970933AG2-581 GEN
Solar/Wind Harmer
14.033
316274AC1-208 GEN
Solar/Wind Harmer
0.91
3145493TOT1
Solar/Wind Harmer
0.387
3145453TOT5
Solar/Wind Harmer
0.232
3145603CNETO
Solar/Wind Harmer
0.155
961601AG1-000A GEN
Solar/Wind Harmer
2.822
316263AC1-034 GEN
Solar/Wind Harmer
6.026
970099AG2-077 GEN
Solar/Wind Harmer
16.845
316240AF1-291 C
Solar/Wind Harmer
0.001
944641AF1-129 GEN
Adder
72.632
939181AE1-148 GEN
Solar/Wind Harmer
6.878
3150691DARBY 3
Adder
10.054
3150701DARBY 4
Adder
10.031
3150681DARBY 2
Adder
10.019
3150671DARBY 1
Adder
10.008
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
6.199
964791AG1-342 GEN
Solar/Wind Harmer
2.458
3146843MT LREL
Solar/Wind Harmer
0.128
3146843MT LREL
Solar/Wind Harmer
0.128
970323AG2-213 GEN
Solar/Wind Harmer
5.316
971775AH1-396 GEN
Solar/Wind Harmer
0.199
316034AC1-036 C
Solar/Wind Harmer
0.009
971741AH1-377 GEN
Solar/Wind Harmer
12.345
970301AG2-198 GEN
Solar/Wind Harmer
4.996
958211AF2-115 GEN
Solar/Wind Harmer
1.384
963191AG1-168 GEN
Solar/Wind Harmer
0.461
3144293JTRSVLE
Adder
0.367
3144293JTRSVLE
Adder
0.309
316222AC1-221 GEN
Solar/Wind Harmer
0.474
3142366NRTHEST
Adder
0.372
3150921YORKTN3
50/50
8.377
3144216WINCHST
50/50
1.232
3151101ELIZAR3
50/50
28.284
315749AE2-041 GEN
50/50
9.884
3141843SHACKLE
50/50
1.464
3151161SURRY 1
50/50
10.052
315773AC2-141 GEN
Solar/Wind Harmer
11.569
316382AG1-145 C
Solar/Wind Harmer
0.003
944581AF1-123 GEN
Solar/Wind Harmer
65.654
944601AF1-125 GEN
Solar/Wind Harmer
64.643
3144873MCLAUGH
Solar/Wind Harmer
0.007
3144536CHRHLND
Solar/Wind Harmer
0.042
3146456SLIGO L269
Solar/Wind Harmer
0.281
971153AH1-033 GEN
Solar/Wind Harmer
3.25
3141766HARMONY
Solar/Wind Harmer
3.707
316320Y1-086
Solar/Wind Harmer
0.001
316156AD2-030 GEN
Solar/Wind Harmer
0.203
3141873WAN 176
Solar/Wind Harmer
4.88
316280AD1-041 GEN
Solar/Wind Harmer
0.006
3145336SMITFLD
Solar/Wind Harmer
0.109
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.266
3146626S HERTFORD
Solar/Wind Harmer
0.262
3151221GRAVEL6
Adder
19.026
3151171GRAVELC
Adder
3.661
962971AG1-146 GEN
Solar/Wind Harmer
4.087
970009AG2-005 GEN
Solar/Wind Harmer
1.875
3146376EDENTON
Solar/Wind Harmer
0.251
961611AG1-000B GEN
Solar/Wind Harmer
6.685
3145273HOLLAND
Solar/Wind Harmer
0.187
316404AE1-155 C
Solar/Wind Harmer
0.055
315614AA2-178 GEN
Solar/Wind Harmer
1.366
3142946ENON
Solar/Wind Harmer
0.08
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
3150351NORNECKC2
Adder
2.349
971157AH1-035 GEN
Solar/Wind Harmer
2.754
315737AD1-076 GEN
Solar/Wind Harmer
2.931
315778AD1-151 GEN
Solar/Wind Harmer
18.115
970661AG2-428 GEN
Solar/Wind Harmer
4.77
3146206CASHIE
Solar/Wind Harmer
0.221
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
970129AG2-093 GEN
Solar/Wind Harmer
12.986
970659AG2-427 GEN
Solar/Wind Harmer
2.265
3156021HOLLOMANSOL
Solar/Wind Harmer
0.961
3145893MURPHYS
Solar/Wind Harmer
0.353
3145893MURPHYS
Solar/Wind Harmer
0.211
957521AF2-046 GEN
Solar/Wind Harmer
15.623
961681AG1-008 GEN
Solar/Wind Harmer
15.623
3146173TUNIS
Solar/Wind Harmer
0.208
3145963POPLR C
Solar/Wind Harmer
0.207
316463AE2-346 GEN
Solar/Wind Harmer
0.178
316140AB2-099
Solar/Wind Harmer
0.074
962331AG1-082 GEN
Solar/Wind Harmer
2.207
3146263WOODLND
Solar/Wind Harmer
0.199
970133AG2-095 GEN
Solar/Wind Harmer
1.906
315813AE1-149 C
Solar/Wind Harmer
10.584
316317KELFORD C
Solar/Wind Harmer
0.019
3145823KELFORD
Solar/Wind Harmer
0.196
3145933PARMELE
Solar/Wind Harmer
0.189
966801AG1-551 GEN
Solar/Wind Harmer
2.208
3141906WESTMOR
Solar/Wind Harmer
0.075
970293AG2-193 GEN
Solar/Wind Harmer
1.977
3142666NORTHAMPTON
Solar/Wind Harmer
0.185
3145746EVERETS
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
316365GEN2_N
Solar/Wind Harmer
0.405
316210AC1-098 GEN
Solar/Wind Harmer
1.669
3145796HORNRTN
Solar/Wind Harmer
0.711
3145796HORNRTN
Solar/Wind Harmer
0.178
313506AB2-031 GEN
Solar/Wind Harmer
0.548
970917AG2-570 GEN
Solar/Wind Harmer
15.528
965281AG1-393 GEN
Solar/Wind Harmer
1.806
316327AA2-057 GEN
Solar/Wind Harmer
0.254
970737AG2-469 GEN
Solar/Wind Harmer
7.154
315724AD1-057 GEN
Solar/Wind Harmer
0.627
3146073TAR RVR
Solar/Wind Harmer
0.167
3146083TARBORO
Solar/Wind Harmer
0.167
3146233WITAKRS
Solar/Wind Harmer
0.82
3146233WITAKRS
Solar/Wind Harmer
0.111
3143096IRON208
Adder
0.683
3143096IRON208
Adder
0.669
3138543CONSLDL
Solar/Wind Harmer
0.107
3147043LAWRENC
Solar/Wind Harmer
0.098
315839AE2-212 C
Solar/Wind Harmer
0.001
961601AG1-000A GEN
Solar/Wind Harmer
11.289
3145543BTLEBRO
Solar/Wind Harmer
0.158
3145543BTLEBRO
Solar/Wind Harmer
0.158
971623AH1-311 GEN
Solar/Wind Harmer
0.317
316478AD1-087 GEN
Solar/Wind Harmer
0.524
316486AD2-202 GEN
Solar/Wind Harmer
0.154
316131AB2-060 GEN
Solar/Wind Harmer
0.423
3142416OLDCHRC
Solar/Wind Harmer
1.283
964241AG1-285 GEN
Solar/Wind Harmer
8.767
315785AD2-033 C
Solar/Wind Harmer
1.028
970257AG2-171 GEN
Solar/Wind Harmer
3.987
959311AF2-222 GEN
Solar/Wind Harmer
10.954
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.24
970909AG2-566 GEN
Solar/Wind Harmer
1.249
3150861SPRUNCD
Adder
0.537
963181AG1-167 GEN
Solar/Wind Harmer
0.461
3144293JTRSVLE
Adder
0.367
316283AC2-100 C
Solar/Wind Harmer
0.223
3152331SURRY 2
50/50
14.903
971353AH1-157 GEN
50/50
28.02
970017AG2-010 GEN
50/50
20.837
3150981CHESPKA
50/50
3.793
3141843SHACKLE
50/50
1.464
316294AC1-161 GEN
Solar/Wind Harmer
5.488
971317AH1-138 GEN
Solar/Wind Harmer
2.36
316159AE1-175 C
Solar/Wind Harmer
0.271
3138126ROCKLANDING
Solar/Wind Harmer
0.142
944591AF1-124 GEN
Solar/Wind Harmer
65.888
316375AC2-012 GEN
Solar/Wind Harmer
0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.887
3146456SLIGO L269
Solar/Wind Harmer
0.281
3141766HARMONY
Solar/Wind Harmer
0.056
316072AD1-144
Solar/Wind Harmer
0.1
316246AF1-032 C
Solar/Wind Harmer
0.125
3145336SMITFLD
Solar/Wind Harmer
1.085
971777AH1-397 GEN
Solar/Wind Harmer
0.713
3138133OCRAN
Solar/Wind Harmer
0.16
3146516WINFALL
Solar/Wind Harmer
0.862
3146516WINFALL
Solar/Wind Harmer
0.266
316093AE2-104_GEN
Solar/Wind Harmer
4.453
3151171GRAVELC
Adder
2.784
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.251
961611AG1-000B GEN
Solar/Wind Harmer
13.148
962861AG1-135 GEN
Solar/Wind Harmer
7.873
971647AH1-324 GEN
Solar/Wind Harmer
10.323
3145663CRESWEL
Solar/Wind Harmer
0.668
971163AH1-040 GEN
Solar/Wind Harmer
19.1
3141726DUNNSVL
Solar/Wind Harmer
0.952
939411AE1-173 GEN
Solar/Wind Harmer
101.201
3142433PROV 92
Solar/Wind Harmer
0.945
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
3150351NORNECKC2
Adder
2.31
971069AG2-661 GEN
Solar/Wind Harmer
4.025
970661AG2-428 GEN
Solar/Wind Harmer
22.429
3146206CASHIE
Solar/Wind Harmer
0.221
971547AH1-271 GEN
Solar/Wind Harmer
4.718
940641AE2-051 GEN
Solar/Wind Harmer
17.631
316381AD1-082 GEN
Solar/Wind Harmer
0.226
316458AB2-190 GEN2
Solar/Wind Harmer
1.162
970129AG2-093 GEN
Solar/Wind Harmer
6.111
970659AG2-427 GEN
Solar/Wind Harmer
10.353
944631AF1-128 GEN
Adder
101.924
316337AD2-073 GEN
Solar/Wind Harmer
0.183
3145893MURPHYS
Solar/Wind Harmer
0.842
3145893MURPHYS
Solar/Wind Harmer
0.937
3146173TUNIS
Solar/Wind Harmer
0.208
3145963POPLR C
Solar/Wind Harmer
0.207
3145683EARLEYS
Solar/Wind Harmer
0.206
316174AB2-169 GEN
Solar/Wind Harmer
0.005
3146263WOODLND
Solar/Wind Harmer
0.199
3145823KELFORD
Solar/Wind Harmer
0.196
3146293MARTNCO
Solar/Wind Harmer
0.176
316190AA2-174 GEN
Solar/Wind Harmer
0
316011AB1-132 GEN
Solar/Wind Harmer
3.295
3145746EVERETS
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
962571AG1-106 GEN
Solar/Wind Harmer
2.579
316023GEN1_S
Solar/Wind Harmer
0.405
316212AC1-099_GEN
Solar/Wind Harmer
0.931
3145783HORNRTN
Solar/Wind Harmer
0.18
3145796HORNRTN
Solar/Wind Harmer
0.587
3145796HORNRTN
Solar/Wind Harmer
0.178
970919AG2-571 GEN
Solar/Wind Harmer
6.211
960081AF2-299 GEN
Solar/Wind Harmer
1.675
970087AG2-069 GEN
Solar/Wind Harmer
13.912
316494AC1-189 GEN
Solar/Wind Harmer
0.586
315671AE2-027_GEN
Solar/Wind Harmer
10.758
315722AD1-056 GEN
Solar/Wind Harmer
1.058
961671AG1-007 GEN
Solar/Wind Harmer
0.026
3146083TARBORO
Solar/Wind Harmer
0.167
3145493TOT1
Solar/Wind Harmer
0.742
971795AH1-408 GEN
Solar/Wind Harmer
11.088
3146233WITAKRS
Solar/Wind Harmer
0.65
3143096IRON208
Adder
0.683
3147043LAWRENC
Adder
1.471
3145543BTLEBRO
Solar/Wind Harmer
0.158
3145543BTLEBRO
Solar/Wind Harmer
0.127
316359AB2-059 GEN
Solar/Wind Harmer
0.57
316049AB1-081 GEN
Solar/Wind Harmer
0.908
3142053HEARTS
Solar/Wind Harmer
0.279
957481AF2-042 GEN
Solar/Wind Harmer
42.112
316129AC1-054 GEN
Solar/Wind Harmer
0.592
971065AG2-659 GEN
Solar/Wind Harmer
6.63
972135AH1-637 GEN
Solar/Wind Harmer
1.313
315693AD1-088 GEN
Solar/Wind Harmer
7.161
962491AG1-098 GEN
Solar/Wind Harmer
8.419
315687AD1-152 GEN
Solar/Wind Harmer
0.005
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3142543TWELFTH
Solar/Wind Harmer
0.013
3142416OLDCHRC
Solar/Wind Harmer
0.344
3142416OLDCHRC
Solar/Wind Harmer
0.132
970401AG2-262 GEN
Solar/Wind Harmer
0.751
970685AG2-442 GEN
Solar/Wind Harmer
8.947
3150851SPRUNCC
Adder
0.537
963171AG1-166 GEN
Solar/Wind Harmer
0.615
971563AH1-280 GEN
Solar/Wind Harmer
1.23
3144293JTRSVLE
Adder
0.367
316003AC1-222 GEN
Solar/Wind Harmer
0.003
LAGNLTFEXP_LAGN->PJM
CLTF
4.637
CBM South 2LTFEXP_CBM-S2->PJM
CBM
18.084
TVALTFEXP_TVA->PJM
CLTF
2.295
NYPJM->LTFIMP_NY
CLTF
1.457
LGEELTFEXP_LGEE->PJM
CLTF
0.489
WECLTFEXP_WEC->PJM
CLTF
0.242
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.626
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.547
MECLTFEXP_MEC->PJM
CLTF
1.618
SIGELTFEXP_SIGE->PJM
CLTF
0.045
CPLELTFEXP_CPLE->PJM
CLTF
8.941
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.836

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:173.01 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:7041.78
MW Contribution:10.07
Bus #Bus NameTypeMW Contribution
3152331SURRY 2
50/50
15.859
3142416OLDCHRC
Solar/Wind Harmer
1.011
3142416OLDCHRC
Solar/Wind Harmer
0.387
316159AE1-175 C
Solar/Wind Harmer
0.327
944631AF1-128 GEN
Adder
179.515
3143096IRON208
Adder
1.57
3138126ROCKLANDING
Solar/Wind Harmer
0.171
971317AH1-138 GEN
Solar/Wind Harmer
2.773
316294AC1-161 GEN
Solar/Wind Harmer
6.422
3142543TWELFTH
Solar/Wind Harmer
0.035
970129AG2-093 GEN
Solar/Wind Harmer
10.478
316458AB2-190 GEN2
Solar/Wind Harmer
1.976
971069AG2-661 GEN
Solar/Wind Harmer
6.539
971647AH1-324 GEN
Solar/Wind Harmer
15.662
961611AG1-000B GEN
Solar/Wind Harmer
19.23
3151171GRAVELC
Adder
3.895
3150851SPRUNCC
Adder
1.682
3145336SMITFLD
Solar/Wind Harmer
1.459
944591AF1-124 GEN
Solar/Wind Harmer
82.083
316375AC2-012 GEN
Solar/Wind Harmer
0.009
3150981CHESPKA
Adder
4.531
315671AE2-027_GEN
Solar/Wind Harmer
23.135
316072AD1-144
Solar/Wind Harmer
0.13
316388AE2-253 GEN
Solar/Wind Harmer
1.126
972263AH1-716 GEN
50/50
220.54
316312AB1-027
Solar/Wind Harmer
0.696
315976AC1-164 GENA
Solar/Wind Harmer
40.142
316169AC1-164_GENC
Solar/Wind Harmer
34.679
315975AC1-164 GENB
Solar/Wind Harmer
1.188
316132AB2-190 GEN1
Solar/Wind Harmer
1.976
316369SG1_INVT
Solar/Wind Harmer
0.014
972265AH1-717 GEN
Adder
28.433
3151201GRAVEL4
Adder
26.654
3151191GRAVEL3
Adder
26.317
3151211GRAVEL5
Adder
26.317
971445AH1-216 GEN
Solar/Wind Harmer
25.708
971285AH1-108 GEN
Adder
2.752
3151081ELIZAR1
Adder
33.28
3151091ELIZAR2
Adder
32.702
3152611GOSPORTB
Adder
4.621
3152621GOSPORTC
Adder
3.922
3152601GOSPORTA
Adder
3.618
971167AH1-042 GEN
Solar/Wind Harmer
31.907
957871AF2-081 GEN
Solar/Wind Harmer
17.869
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
3138283WHITEMARSH
Solar/Wind Harmer
0.083
319010AE1-072 C
Solar/Wind Harmer
1.802
3146406KITTY HAWK
Solar/Wind Harmer
0.045
316305AF2-043 C
Solar/Wind Harmer
0.003
315833AF1-017_GEN
Solar/Wind Harmer
0.002
316349AD2-085 GEN
Solar/Wind Harmer
0.243
316311AC2-079 GEN
Solar/Wind Harmer
10.187
3143873LANEXA
Solar/Wind Harmer
0.213
316233AE1-074 FULL
Solar/Wind Harmer
0.283
971281AH1-106 GEN
Solar/Wind Harmer
4.913
971283AH1-107 GEN
Solar/Wind Harmer
4.913
315835AF2-110_GEN
Solar/Wind Harmer
2.43
313526AB2-022
Solar/Wind Harmer
0.192
316314AB2-024 C
Solar/Wind Harmer
0.001
3146486SUNBURY
Solar/Wind Harmer
0.352
3146486SUNBURY
Solar/Wind Harmer
0.352
3143316POE
Solar/Wind Harmer
1.396
316321Z2-027
Solar/Wind Harmer
0.065
3146396TANGLEW
Solar/Wind Harmer
0.971
3145176PASQUOTANK
Solar/Wind Harmer
0.218
316059AD1-063 C
Solar/Wind Harmer
0.002
970189AG2-124 GEN
Solar/Wind Harmer
10.307
315662AE1-191 GEN
Solar/Wind Harmer
0.011
315666AE1-190 GEN
Solar/Wind Harmer
0.003
3141873WAN 176
Solar/Wind Harmer
0.069
315611Z1-036_GEN2
Solar/Wind Harmer
0.003
3130156CHOWAN
Solar/Wind Harmer
0.338
3130156CHOWAN
Solar/Wind Harmer
0.338
3141913WHIT STONE
Solar/Wind Harmer
0.333
316315AB2-025 C
Solar/Wind Harmer
0.269
315814AE2-033 C
Solar/Wind Harmer
26.26
3138133OCRAN
Solar/Wind Harmer
0.099
315816AE2-034 GEN
Solar/Wind Harmer
1.417
941031AE2-094 GEN
Solar/Wind Harmer
60.194
944011AF1-069 GEN
Solar/Wind Harmer
19.668
3141783LANCAST
Solar/Wind Harmer
0.195
3141783LANCAST
Solar/Wind Harmer
0.13
3130546PLYMOUTH
Solar/Wind Harmer
0.324
315732AD1-074 GEN1
Solar/Wind Harmer
1.854
315733AD1-074 GEN2
Solar/Wind Harmer
1.854
315735AD1-075 GEN1
Solar/Wind Harmer
0.928
972193AH1-681 GEN
Adder
7.36
970673AG2-436 GEN
Solar/Wind Harmer
68.642
970673AG2-436 GEN
Solar/Wind Harmer
45.761
3146206CASHIE
Solar/Wind Harmer
0.318
970601AG2-382 GEN
Solar/Wind Harmer
11.901
965291AG1-394 GEN
Solar/Wind Harmer
1.416
971967AH1-528 GEN
Solar/Wind Harmer
50.838
3145893MURPHYS
Solar/Wind Harmer
0.852
3145893MURPHYS
Solar/Wind Harmer
0.316
962981AG1-147 GEN
Solar/Wind Harmer
11.703
3145513AHOSKIE
Solar/Wind Harmer
0.651
3145513AHOSKIE
Solar/Wind Harmer
0.311
3145683EARLEYS
Solar/Wind Harmer
0.62
3145683EARLEYS
Solar/Wind Harmer
0.31
3145683EARLEYS
Solar/Wind Harmer
0.31
3146043SEABORD
Solar/Wind Harmer
0.307
970327AG2-215 GEN
Solar/Wind Harmer
10.069
315607AA1-063A GEN
Solar/Wind Harmer
0.625
970085AG2-068 GEN
Solar/Wind Harmer
16.26
970581AG2-369 GEN
Solar/Wind Harmer
13.984
316087AB2-174 GEN
Solar/Wind Harmer
0.009
315652AC1-086 GEN
Solar/Wind Harmer
33.087
3137643SOCKMAN
Solar/Wind Harmer
1.194
3145796HORNRTN
Solar/Wind Harmer
0.948
3145796HORNRTN
Solar/Wind Harmer
0.119
3146033SCOT NK
Solar/Wind Harmer
1.185
316005AA1-067
Solar/Wind Harmer
0.307
3145746EVERETS
Solar/Wind Harmer
1.138
3145746EVERETS
Solar/Wind Harmer
0.286
3145746EVERETS
Solar/Wind Harmer
0.286
3145746EVERETS
Solar/Wind Harmer
0.286
970181AG2-120 GEN
Solar/Wind Harmer
3.56
970831AG2-522 GEN
Solar/Wind Harmer
12.024
957861AF2-080 GEN
Solar/Wind Harmer
12.104
316420AA1-050 GEN
Solar/Wind Harmer
0.009
3141813NORNECK
Solar/Wind Harmer
0.276
3145573BETHELC
Solar/Wind Harmer
0.276
3145573BETHELC
Solar/Wind Harmer
0.276
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.38
3144303KENBRDG
Solar/Wind Harmer
0.208
972189AH1-679 GEN
Adder
4.36
970683AG2-441 GEN
Solar/Wind Harmer
17.21
970681AG2-440 GEN
Solar/Wind Harmer
13.768
946301AF1-294 GEN
Solar/Wind Harmer
5.05
961791AG1-021 GEN
Solar/Wind Harmer
2.457
315657AE1-056 GEN
Solar/Wind Harmer
8.773
316118AC1-105 GEN
Solar/Wind Harmer
0.646
3147173SINAI
Solar/Wind Harmer
0.246
3147243WELCO
Solar/Wind Harmer
0.154
970285AG2-188 GEN
Solar/Wind Harmer
18.408
971845AH1-439 GEN
Solar/Wind Harmer
10.428
970865AG2-541 GEN
Solar/Wind Harmer
7.734
972205AH1-687 GEN
Adder
8.917
316223AC1-118
Solar/Wind Harmer
0.15
316123AC1-075 GEN
Solar/Wind Harmer
0.284
970165AG2-112 GEN
Solar/Wind Harmer
1.683
970163AG2-111 GEN
Solar/Wind Harmer
1.606
971447AH1-217 GEN
Solar/Wind Harmer
5.953
270494AE1-108_GEN
Solar/Wind Harmer
2.206
3148133STUARTS
Solar/Wind Harmer
0.092
3148013FISHERV
Solar/Wind Harmer
0.088
3148463FAIRFLD
Solar/Wind Harmer
0.15
3151881LOWMORC
Adder
1.595
3151881LOWMORC
Adder
1.57
3151861LOWMORA
Adder
1.545
270069AE2-166 C O1
Solar/Wind Harmer
0.005
944491AF1-114 GEN
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316164AC1-076 GEN
Solar/Wind Helper
1.845
316411AF1-147_GEN1
Solar/Wind Helper
1.079
316415AF1-147_GEN2
Solar/Wind Helper
1.079
3138216PACIFIC
Solar/Wind Helper
0.053
3141426STAFORD
Solar/Wind Helper
0.061
237085AD2-009_GEN
Solar/Wind Helper
1.388
960921AF2-383 GEN
Solar/Wind Helper
0.352
233935AB2-179 C
Solar/Wind Helper
1.229
3142433PROV 92
Solar/Wind Harmer
1.432
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
3146456SLIGO L269
Solar/Wind Harmer
0.358
316246AF1-032 C
Solar/Wind Harmer
0.161
970659AG2-427 GEN
Solar/Wind Harmer
17.218
316381AD1-082 GEN
Solar/Wind Harmer
0.371
971645AH1-323 GEN
50/50
34.852
3151161SURRY 1
50/50
14.066
3142416OLDCHRC
Solar/Wind Harmer
3.771
970293AG2-193 GEN
Solar/Wind Harmer
4.092
3142946ENON
Solar/Wind Harmer
0.127
316382AG1-145 C
Solar/Wind Harmer
0.003
3143096IRON208
Adder
1.57
3143096IRON208
Adder
1.539
3150921YORKTN3
Adder
9.356
3144216WINCHST
Adder
1.402
315773AC2-141 GEN
Solar/Wind Harmer
13.538
970133AG2-095 GEN
Solar/Wind Harmer
3.544
970129AG2-093 GEN
Solar/Wind Harmer
22.266
315778AD1-151 GEN
Solar/Wind Harmer
29.426
961611AG1-000B GEN
Solar/Wind Harmer
9.778
970661AG2-428 GEN
Solar/Wind Harmer
35.374
3143526WINTERP
Solar/Wind Harmer
1.841
316093AE2-104_GEN
Solar/Wind Harmer
5.955
3141766HARMONY
Solar/Wind Harmer
0.07
3146516WINFALL
Solar/Wind Harmer
1.13
3146516WINFALL
Solar/Wind Harmer
0.349
971777AH1-397 GEN
Solar/Wind Harmer
0.918
3141843SHACKLE
Adder
1.778
939411AE1-173 GEN
Solar/Wind Harmer
148.397
3143226MDLTHAN
Solar/Wind Harmer
0.343
940641AE2-051 GEN
Solar/Wind Harmer
27.456
315800Z1-036_GEN1
Solar/Wind Harmer
0.003
3130156CHOWAN
Solar/Wind Harmer
0.338
3138133OCRAN
Solar/Wind Harmer
0.198
3145663CRESWEL
Solar/Wind Harmer
0.924
971163AH1-040 GEN
Solar/Wind Harmer
26.412
972277AH1-723 GEN
Adder
191.941
3146206CASHIE
Solar/Wind Harmer
0.318
971547AH1-271 GEN
Solar/Wind Harmer
6.801
3145893MURPHYS
Solar/Wind Harmer
1.262
3145893MURPHYS
Solar/Wind Harmer
1.404
3146173TUNIS
Solar/Wind Harmer
0.313
316023GEN1_S
Solar/Wind Harmer
0.699
3145683EARLEYS
Solar/Wind Harmer
0.31
3146263WOODLND
Solar/Wind Harmer
0.306
3145963POPLR C
Solar/Wind Harmer
0.306
970919AG2-571 GEN
Solar/Wind Harmer
10.879
970087AG2-069 GEN
Solar/Wind Harmer
24.391
316174AB2-169 GEN
Solar/Wind Harmer
0.008
3145823KELFORD
Solar/Wind Harmer
0.303
960081AF2-299 GEN
Solar/Wind Harmer
2.907
316011AB1-132 GEN
Solar/Wind Harmer
5.469
962571AG1-106 GEN
Solar/Wind Harmer
4.28
316190AA2-174 GEN
Solar/Wind Harmer
0.001
962861AG1-135 GEN
Solar/Wind Harmer
9.564
3145796HORNRTN
Solar/Wind Harmer
0.978
3145796HORNRTN
Solar/Wind Harmer
0.296
3145783HORNRTN
Solar/Wind Harmer
0.296
971795AH1-408 GEN
Solar/Wind Harmer
19.673
3146293MARTNCO
Solar/Wind Harmer
0.271
3147043LAWRENC
Adder
2.638
957481AF2-042 GEN
Solar/Wind Harmer
77.718
316212AC1-099_GEN
Solar/Wind Harmer
1.505
3143336POWHATN
Solar/Wind Harmer
5.15
3141726DUNNSVL
Solar/Wind Harmer
1.146
3145746EVERETS
Solar/Wind Harmer
0.286
3145746EVERETS
Solar/Wind Harmer
0.286
315693AD1-088 GEN
Solar/Wind Harmer
13.658
962491AG1-098 GEN
Solar/Wind Harmer
16.171
315722AD1-056 GEN
Solar/Wind Harmer
1.786
316494AC1-189 GEN
Solar/Wind Harmer
0.948
316129AC1-054 GEN
Solar/Wind Harmer
1.053
971065AG2-659 GEN
Solar/Wind Harmer
11.883
3150351NORNECKC2
Adder
2.758
961671AG1-007 GEN
Solar/Wind Harmer
0.042
3146083TARBORO
Solar/Wind Harmer
0.276
3145493TOT1
Solar/Wind Harmer
1.227
316336AC2-165 C
Solar/Wind Harmer
0.011
3146233WITAKRS
Solar/Wind Harmer
1.096
3145543BTLEBRO
Solar/Wind Harmer
0.27
3145543BTLEBRO
Solar/Wind Harmer
0.216
316359AB2-059 GEN
Solar/Wind Harmer
0.971
316049AB1-081 GEN
Solar/Wind Harmer
1.547
3142053HEARTS
Solar/Wind Harmer
0.476
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
19.275
963171AG1-166 GEN
Solar/Wind Harmer
1.365
971563AH1-280 GEN
Solar/Wind Harmer
2.73
3144293JTRSVLE
Adder
0.815
970401AG2-262 GEN
Solar/Wind Harmer
1.493
3146926FARMVIL
Solar/Wind Harmer
0.147
316337AD2-073 GEN
Solar/Wind Harmer
0.212
970937AG2-583 GEN
Solar/Wind Harmer
14.682
316003AC1-222 GEN
Solar/Wind Harmer
0.006
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.091
972003AH1-546 GEN
Solar/Wind Harmer
9.023
971377AH1-170 GEN
Solar/Wind Harmer
2.126
3147623JAMES R
Solar/Wind Harmer
0.462
970223AG2-152 GEN
Solar/Wind Harmer
12.134
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.1
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.127
3146802CHATHAM
Solar/Wind Harmer
0.119
941801AE2-185 GEN
Solar/Wind Harmer
5.072
972135AH1-637 GEN
Solar/Wind Harmer
1.317
270173AC1-122 GEN
Solar/Wind Harmer
0.358
270030AE2-140 GEN
Solar/Wind Harmer
15.132
962751AG1-124 GEN
Solar/Wind Harmer
6.367
315705AF1-075 GEN
Solar/Wind Harmer
5.115
316045AC1-158 PL2
Solar/Wind Helper
8.011
316006AB2-029 C
Solar/Wind Helper
0.164
316254AC1-120 GEN1
Solar/Wind Helper
1.563
3147666LOUISA
Solar/Wind Helper
1.282
316192AB2-158 GEN
Solar/Wind Helper
2.104
223401AF1-299 GEN
Solar/Wind Helper
0.393
23779801AA1-109
Solar/Wind Helper
0.185
237080AD1-060 GEN
Solar/Wind Helper
0.295
237038AE2-054 C
Solar/Wind Helper
0.233
235062AE1-101 C1
Solar/Wind Helper
1.423
966131AG1-482 GEN
Solar/Wind Helper
0.131
233930AB2-032 GEN
Solar/Wind Helper
0.368
3151221GRAVEL6
Adder
26.624
3151171GRAVELC
Adder
5.122
3150861SPRUNCD
Adder
1.682
3145336SMITFLD
Solar/Wind Harmer
0.146
3144536CHRHLND
Solar/Wind Harmer
0.054
944581AF1-123 GEN
Solar/Wind Harmer
81.792
944601AF1-125 GEN
Solar/Wind Harmer
80.532
3151101ELIZAR3
Adder
33.706
3144873MCLAUGH
Solar/Wind Harmer
0.009
965281AG1-393 GEN
Solar/Wind Harmer
3.845
315839AE2-212 C
Solar/Wind Harmer
0.003
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
3146456SLIGO L269
Solar/Wind Harmer
0.358
971153AH1-033 GEN
Solar/Wind Harmer
4.14
316473AC1-191 GEN
Solar/Wind Harmer
1.209
315813AE1-149 C
Solar/Wind Harmer
19.023
970659AG2-427 GEN
Solar/Wind Harmer
3.767
316083AB2-161 GEN
Solar/Wind Harmer
0.005
970661AG2-428 GEN
Solar/Wind Harmer
7.524
316320Y1-086
Solar/Wind Harmer
0.002
316435W1029_GEN3
Solar/Wind Harmer
0.002
3141766HARMONY
Solar/Wind Harmer
4.656
3146516WINFALL
Solar/Wind Harmer
0.349
3141843SHACKLE
Adder
1.778
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3146626S HERTFORD
Solar/Wind Harmer
0.346
316280AD1-041 GEN
Solar/Wind Harmer
0.007
3145273HOLLAND
Solar/Wind Harmer
0.258
316156AD2-030 GEN
Solar/Wind Harmer
0.254
3141873WAN 176
Solar/Wind Harmer
6.098
3146376EDENTON
Solar/Wind Harmer
0.338
315614AA2-178 GEN
Solar/Wind Harmer
1.889
971157AH1-035 GEN
Solar/Wind Harmer
3.886
315737AD1-076 GEN
Solar/Wind Harmer
4.152
972255AH1-712 GEN
Adder
164.714
3156081AA2-088 GEN
Solar/Wind Harmer
0.008
3146206CASHIE
Solar/Wind Harmer
0.318
3145893MURPHYS
Solar/Wind Harmer
0.528
3145893MURPHYS
Solar/Wind Harmer
0.316
957521AF2-046 GEN
Solar/Wind Harmer
23.434
961681AG1-008 GEN
Solar/Wind Harmer
23.434
962971AG1-146 GEN
Solar/Wind Harmer
5.016
3156021HOLLOMANSOL
Solar/Wind Harmer
1.422
3146173TUNIS
Solar/Wind Harmer
0.313
316365GEN2_N
Solar/Wind Harmer
0.699
316463AE2-346 GEN
Solar/Wind Harmer
0.267
316140AB2-099
Solar/Wind Harmer
0.111
962331AG1-082 GEN
Solar/Wind Harmer
3.322
970009AG2-005 GEN
Solar/Wind Harmer
2.291
3146263WOODLND
Solar/Wind Harmer
0.306
3145963POPLR C
Solar/Wind Harmer
0.306
970917AG2-570 GEN
Solar/Wind Harmer
27.198
316317KELFORD C
Solar/Wind Harmer
0.029
3145823KELFORD
Solar/Wind Harmer
0.303
3142666NORTHAMPTON
Solar/Wind Harmer
0.302
313506AB2-031 GEN
Solar/Wind Harmer
0.929
3145796HORNRTN
Solar/Wind Harmer
1.185
3145796HORNRTN
Solar/Wind Harmer
0.296
316404AE1-155 C
Solar/Wind Harmer
0.067
3145933PARMELE
Solar/Wind Harmer
0.292
966801AG1-551 GEN
Solar/Wind Harmer
3.408
3147043LAWRENC
Solar/Wind Harmer
0.175
316210AC1-098 GEN
Solar/Wind Harmer
2.699
316313AB2-026
Solar/Wind Harmer
0.183
316258AE1-075 C
Solar/Wind Harmer
0.219
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.377
3145746EVERETS
Solar/Wind Harmer
0.286
3145746EVERETS
Solar/Wind Harmer
0.286
315724AD1-057 GEN
Solar/Wind Harmer
1.059
316478AD1-087 GEN
Solar/Wind Harmer
0.983
316486AD2-202 GEN
Solar/Wind Harmer
0.289
316327AA2-057 GEN
Solar/Wind Harmer
0.423
3150351NORNECKC2
Adder
2.804
3146073TAR RVR
Solar/Wind Harmer
0.276
3146083TARBORO
Solar/Wind Harmer
0.276
3146233WITAKRS
Solar/Wind Harmer
1.382
3146233WITAKRS
Solar/Wind Harmer
0.187
3138543CONSLDL
Solar/Wind Harmer
0.181
961601AG1-000A GEN
Solar/Wind Harmer
19.24
3145543BTLEBRO
Solar/Wind Harmer
0.27
3145543BTLEBRO
Solar/Wind Harmer
0.27
971623AH1-311 GEN
Solar/Wind Harmer
0.541
316131AB2-060 GEN
Solar/Wind Harmer
0.835
964241AG1-285 GEN
Solar/Wind Harmer
17.596
970909AG2-566 GEN
Solar/Wind Harmer
2.793
315785AD2-033 C
Solar/Wind Harmer
2.125
970257AG2-171 GEN
Solar/Wind Harmer
8.336
959311AF2-222 GEN
Solar/Wind Harmer
23.097
963181AG1-167 GEN
Solar/Wind Harmer
1.024
3144293JTRSVLE
Adder
0.815
3147133PAMPLIN
Solar/Wind Harmer
0.798
971193AH1-056 GEN
Solar/Wind Harmer
15.489
971781AH1-399 GEN
Solar/Wind Harmer
0.329
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
10.514
3146926FARMVIL
Solar/Wind Harmer
0.147
971683AH1-343 GEN
Solar/Wind Harmer
8.489
3146776BUCKING
Solar/Wind Harmer
0.082
316283AC2-100 C
Solar/Wind Harmer
0.444
3141906WESTMOR
Solar/Wind Harmer
0.083
970221AG2-151 GEN
Solar/Wind Harmer
10.629
970737AG2-469 GEN
Solar/Wind Harmer
7.511
270197AD1-017 GEN1
Solar/Wind Harmer
1.056
3147312GRETNA
Solar/Wind Harmer
0.032
941821AE2-187 GEN
Solar/Wind Harmer
5.072
270018AE2-047 C O1
Solar/Wind Harmer
0.003
3148013FISHERV
Solar/Wind Harmer
0.154
315616AA1-038_C
Solar/Wind Harmer
0.001
3151861LOWMORA
Adder
1.607
958131AF2-107 GEN
Solar/Wind Harmer
4.297
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.004
971367AH1-164 GEN
Solar/Wind Harmer
2.405
316044AC1-158 PL1
Solar/Wind Helper
2.503
316450AC1-158 RIC
Solar/Wind Helper
0.667
3141196NOKESVL
Solar/Wind Helper
1.389
316170AC1-121 GEN2
Solar/Wind Helper
0.521
3147666LOUISA
Solar/Wind Helper
0.737
227287AC2-120 GEN
Solar/Wind Helper
0.432
226910AB2-157 C
Solar/Wind Helper
0.018
223402AF1-300 C
Solar/Wind Helper
0.393
3132273ORANGE
Solar/Wind Helper
0.053
237030AB1-096 C
Solar/Wind Helper
0.069
238221AF1-254 C O1
Solar/Wind Helper
0.238
235067AD1-061 GEN
Solar/Wind Helper
0.424
205917AD1-020 ES
Solar/Wind Helper
0.354
233915AB1-141 GEN
Solar/Wind Helper
0.486
232422X3-066 FULL
Solar/Wind Helper
0.11
233964AF2-378 GEN
Solar/Wind Helper
0.04
232426Y1-080 FULL
Solar/Wind Helper
0.038
232428Y3-058 C
Solar/Wind Helper
0.327
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.491
232434Z2-077 GEN
Solar/Wind Helper
0.123
233954AC2-188 GEN
Solar/Wind Helper
0.225
233950AC2-186 GEN
Solar/Wind Helper
0.112
233972AC1-094 C
Solar/Wind Helper
0.292
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.221
228728W1-130C
Solar/Wind Helper
0.052
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219904AC1-010 C
Solar/Wind Helper
0.058
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
3142296MT RD221
50/50
1.311
3150691DARBY 3
50/50
29.113
3150701DARBY 4
50/50
29.046
3150681DARBY 2
50/50
29.012
3150671DARBY 1
50/50
28.978
3142366NRTHEST
50/50
1.317
316075AC2-137 C
Solar/Wind Harmer
0.106
3142946ENON
Solar/Wind Harmer
0.038
316033AB2-134 GEN
Solar/Wind Harmer
0.022
315697AD1-025 GEN
Solar/Wind Harmer
0.413
944641AF1-129 GEN
Adder
174.18
316236AE1-162_GEN
Solar/Wind Harmer
0.003
316240AF1-291 C
Solar/Wind Harmer
0.003
316036AC1-147 C
Solar/Wind Harmer
0.067
3150991CHESPKB
Adder
3.801
3150991CHESPKB
Adder
3.71
316316AC1-027 C
Solar/Wind Harmer
0.347
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.01
3145506HICKORY
Solar/Wind Harmer
1.442
3145506HICKORY
Solar/Wind Harmer
0.865
3145506HICKORY
Solar/Wind Harmer
0.217
316339AD2-160 GEN
Solar/Wind Harmer
0.583
316018AA1-139 ULT2
Solar/Wind Harmer
0.009
316017AA1-139 ULT1
Solar/Wind Harmer
0.2
3137176SLIGO L2192
Solar/Wind Harmer
1.425
3146456SLIGO L269
Solar/Wind Harmer
6.337
966871AG1-558 GEN
Solar/Wind Harmer
0.414
3130086AYDLETT
Solar/Wind Harmer
1.43
970657AG2-426 GEN
Solar/Wind Harmer
12.462
970657AG2-426 GEN
Solar/Wind Harmer
2.613
3143526WINTERP
Solar/Wind Harmer
1.841
3146386ELIZ CT
Solar/Wind Harmer
0.354
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.349
3146516WINFALL
Solar/Wind Harmer
0.349
3146516WINFALL
Solar/Wind Harmer
0.349
3146626S HERTFORD
Solar/Wind Harmer
0.346
3146626S HERTFORD
Solar/Wind Harmer
0.346
971223AH1-071 GEN
Solar/Wind Harmer
3.664
315742AE1-103 GEN
Solar/Wind Harmer
0.004
3146376EDENTON
Solar/Wind Harmer
1.504
3146376EDENTON
Solar/Wind Harmer
1.504
3144356SAPONY
Solar/Wind Harmer
2.786
316065AD1-022 GEN
Solar/Wind Harmer
14.743
972185AH1-677 GEN
Adder
17.914
3145893MURPHYS
Solar/Wind Harmer
2.113
3145893MURPHYS
Solar/Wind Harmer
0.568
972187AH1-678 GEN
Adder
8.995
3146173TUNIS
Solar/Wind Harmer
0.313
3146173TUNIS
Solar/Wind Harmer
0.313
970933AG2-581 GEN
Solar/Wind Harmer
24.83
3142666NORTHAMPTON
Solar/Wind Harmer
0.302
3142666NORTHAMPTON
Solar/Wind Harmer
0.302
3142666NORTHAMPTON
Solar/Wind Harmer
0.302
3142666NORTHAMPTON
Solar/Wind Harmer
0.181
316181AB2-040 GEN
Solar/Wind Harmer
0.436
316426AA2-053 GEN
Solar/Wind Harmer
1.013
3145593CAROLNA
Solar/Wind Harmer
0.298
3145593CAROLNA
Solar/Wind Harmer
0.298
966811AG1-552 GEN
Solar/Wind Harmer
3.231
3145593CAROLNA
Solar/Wind Harmer
0.371
3145796HORNRTN
Solar/Wind Harmer
0.889
3145783HORNRTN
Solar/Wind Harmer
5.27
3145783HORNRTN
Solar/Wind Harmer
4.216
3145783HORNRTN
Solar/Wind Harmer
1.317
3145783HORNRTN
Solar/Wind Harmer
0.527
958261AF2-120 GEN
Solar/Wind Harmer
9.788
3145933PARMELE
Solar/Wind Harmer
0.585
3145933PARMELE
Solar/Wind Harmer
0.292
970099AG2-077 GEN
Solar/Wind Harmer
31.087
316274AC1-208 GEN
Solar/Wind Harmer
1.496
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.897
3150341NORNECKC1
Adder
2.874
3145493TOT1
Solar/Wind Harmer
0.64
3145453TOT5
Solar/Wind Harmer
0.384
3145603CNETO
Solar/Wind Harmer
0.256
961601AG1-000A GEN
Solar/Wind Harmer
4.81
316263AC1-034 GEN
Solar/Wind Harmer
10.275
939181AE1-148 GEN
Solar/Wind Harmer
12.944
971741AH1-377 GEN
Solar/Wind Harmer
26.49
313527AB2-043 GEN
Solar/Wind Harmer
0.003
970301AG2-198 GEN
Solar/Wind Harmer
11.171
970323AG2-213 GEN
Solar/Wind Harmer
11.115
971775AH1-396 GEN
Solar/Wind Harmer
0.417
316034AC1-036 C
Solar/Wind Harmer
0.019
962561AG1-105 GEN
Solar/Wind Harmer
12.3
958211AF2-115 GEN
Solar/Wind Harmer
3.071
963191AG1-168 GEN
Solar/Wind Harmer
1.024
3144293JTRSVLE
Adder
0.815
3144293JTRSVLE
Adder
0.686
964791AG1-342 GEN
Solar/Wind Harmer
4.887
3146843MT LREL
Solar/Wind Harmer
0.254
3146843MT LREL
Solar/Wind Harmer
0.254
3147133PAMPLIN
Solar/Wind Harmer
0.254
3147133PAMPLIN
Solar/Wind Harmer
0.203
316468AD1-105 GEN
Solar/Wind Harmer
-0.081
3146776BUCKING
Solar/Wind Harmer
0.914
3146776BUCKING
Solar/Wind Harmer
0.074
316222AC1-221 GEN
Solar/Wind Harmer
0.945
971489AH1-241 GEN
Solar/Wind Harmer
10.629
942751AE2-291 GEN
Solar/Wind Harmer
10.765
315821AE2-092 GEN
Solar/Wind Harmer
0.011
270013AE1-250 PV
Solar/Wind Harmer
0.005
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
3.945
316447AC1-158 HLD
Solar/Wind Helper
5.508
315651AD1-115 GEN
Solar/Wind Helper
1.146
226929AD2-058 GEN
Solar/Wind Helper
0.127
23777801MSM_W1-116
Solar/Wind Helper
0.11
237025AB1-124 C
Solar/Wind Helper
0.159
237006AB1-125 GEN
Solar/Wind Helper
0.12
237034AC2-136 C
Solar/Wind Helper
0.207
23777901MDS_W4-102
Solar/Wind Helper
0.152
235020AA1-095 C
Solar/Wind Helper
0.045
237001AB1-127_GEN
Solar/Wind Helper
0.385
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
237002AB1-128_GEN
Solar/Wind Helper
0.384
235063AE1-101 C2
Solar/Wind Helper
1.423
205916AD1-020 GEN
Solar/Wind Helper
1.645
233933AB2-153 GEN
Solar/Wind Helper
0.225
233944AB2-135 GEN
Solar/Wind Helper
0.569
232424Y1-079 C
Solar/Wind Helper
0.112
233987AB2-037 GEN
Solar/Wind Helper
2.265
233946AB2-136 GEN
Solar/Wind Helper
0.549
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
232408W1-005 C
Solar/Wind Helper
0.491
232410W1-006 C
Solar/Wind Helper
0.491
233939AC1-091 C
Solar/Wind Helper
0.338
233970AC1-092 C
Solar/Wind Helper
0.338
238175AF1-290_GEN
Solar/Wind Helper
0.118
230433AD2-135 GEN
Solar/Wind Helper
0.016
230407AD2-065 C
Solar/Wind Helper
0.039
219921AF1-264
Solar/Wind Helper
0.049
233918AB1-142 GEN
Solar/Wind Helper
0.486
233982AB2-133 GEN
Solar/Wind Helper
0.346
233994AC2-023 GEN
Solar/Wind Helper
0.929
233996TM1833_GEN
Solar/Wind Helper
0.253
233997TMININ_4.2
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.491
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.225
233971AC1-093 C
Solar/Wind Helper
0.346
230430AE1-229_GEN
Solar/Wind Helper
3.238
230415AB2-049 C
Solar/Wind Helper
0.029
228729W2-030 C
Solar/Wind Helper
0.106
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.052
219912AD2-042 GEN
Solar/Wind Helper
0.144
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
205943AE1-185 GEN
Solar/Wind Helper
0.491
232436AB1-176 C
Solar/Wind Helper
0.043
205932AD2-116_GEN
Solar/Wind Helper
0.491
205956AE1-196_GEN
Solar/Wind Helper
0.491
233923SMA
Solar/Wind Helper
0.927
233990AG1-397 GEN
Solar/Wind Helper
0.261
232432Z2-076 GEN
Solar/Wind Helper
0.065
234033AF1-007_GEN
Solar/Wind Helper
6.788
238208AF1-136 C
Solar/Wind Helper
0.173
964001AG1-254 GEN
Solar/Wind Helper
0.917
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.025
219914AD2-027 C
Solar/Wind Helper
0.11
219272CLEANLIGHT C
Solar/Wind Helper
0.024
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
219907AC1-030 C
Solar/Wind Helper
0.032
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
LAGNLTFEXP_LAGN->PJM
CLTF
14.625
CBM South 2LTFEXP_CBM-S2->PJM
CBM
39.998
TVALTFEXP_TVA->PJM
CLTF
7.404
NYPJM->LTFIMP_NY
CLTF
4.634
LGEELTFEXP_LGEE->PJM
CLTF
3.014
WECLTFEXP_WEC->PJM
CLTF
1.525
AG2-052LTFEXP_AG2-052->PJM
LTF
0.084
AH1-155LTFEXP_AH1-155->PJM
LTF
0.126
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.563
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.762
MECLTFEXP_MEC->PJM
CLTF
7.835
SIGELTFEXP_SIGE->PJM
CLTF
0.242
CPLELTFEXP_CPLE->PJM
CLTF
17.713
CBM West 2LTFEXP_CBM-W2->PJM
CBM
80.377

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:153.9 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:6264.0
MW Contribution:8.61
Bus #Bus NameTypeMW Contribution
3142296MT RD221
50/50
1.096
3150991CHESPKB
50/50
3.492
3150991CHESPKB
50/50
3.408
316075AC2-137 C
Solar/Wind Harmer
0.09
3142946ENON
Solar/Wind Harmer
0.031
316036AC1-147 C
Solar/Wind Harmer
0.058
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.301
316185AD1-033 GEN
Solar/Wind Harmer
0.009
316236AE1-162_GEN
Solar/Wind Harmer
0.003
3145506HICKORY
Solar/Wind Harmer
1.25
3145506HICKORY
Solar/Wind Harmer
0.75
3145506HICKORY
Solar/Wind Harmer
0.188
316339AD2-160 GEN
Solar/Wind Harmer
0.505
316018AA1-139 ULT2
Solar/Wind Harmer
0.008
316017AA1-139 ULT1
Solar/Wind Harmer
0.174
3150691DARBY 3
Adder
22.343
3150701DARBY 4
Adder
22.291
3150681DARBY 2
Adder
22.265
971645AH1-323 GEN
50/50
29.723
3150921YORKTN3
50/50
8.624
3144216WINCHST
50/50
1.289
3151101ELIZAR3
50/50
30.975
3151161SURRY 1
50/50
11.975
3142416OLDCHRC
Solar/Wind Harmer
3.208
316382AG1-145 C
Solar/Wind Harmer
0.003
315773AC2-141 GEN
Solar/Wind Harmer
11.84
970293AG2-193 GEN
Solar/Wind Harmer
3.398
944581AF1-123 GEN
Solar/Wind Harmer
71.01
944601AF1-125 GEN
Solar/Wind Harmer
69.916
3142946ENON
Solar/Wind Harmer
0.105
3144873MCLAUGH
Solar/Wind Harmer
0.008
3144536CHRHLND
Solar/Wind Harmer
0.047
3145336SMITFLD
Solar/Wind Harmer
0.125
3151221GRAVEL6
Adder
22.664
3151171GRAVELC
Adder
4.361
3146456SLIGO L269
Solar/Wind Harmer
0.31
971153AH1-033 GEN
Solar/Wind Harmer
3.585
961611AG1-000B GEN
Solar/Wind Harmer
8.272
972255AH1-712 GEN
Adder
157.541
315778AD1-151 GEN
Solar/Wind Harmer
24.551
316320Y1-086
Solar/Wind Harmer
0.002
970129AG2-093 GEN
Solar/Wind Harmer
18.454
970133AG2-095 GEN
Solar/Wind Harmer
2.91
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.301
3142433PROV 92
Adder
0.583
3142433PROV 92
Adder
0.583
316473AC1-191 GEN
Solar/Wind Harmer
1.014
970661AG2-428 GEN
Solar/Wind Harmer
6.346
3141766HARMONY
Solar/Wind Harmer
3.995
3146626S HERTFORD
Solar/Wind Harmer
0.299
316083AB2-161 GEN
Solar/Wind Harmer
0.004
970659AG2-427 GEN
Solar/Wind Harmer
3.158
3141843SHACKLE
Adder
1.519
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
315813AE1-149 C
Solar/Wind Harmer
15.819
316280AD1-041 GEN
Solar/Wind Harmer
0.006
3145273HOLLAND
Solar/Wind Harmer
0.221
316156AD2-030 GEN
Solar/Wind Harmer
0.218
3141873WAN 176
Solar/Wind Harmer
5.232
965281AG1-393 GEN
Solar/Wind Harmer
3.137
315839AE2-212 C
Solar/Wind Harmer
0.002
3143096IRON208
Adder
1.226
3143096IRON208
Adder
1.201
3146376EDENTON
Solar/Wind Harmer
0.291
315614AA2-178 GEN
Solar/Wind Harmer
1.626
971157AH1-035 GEN
Solar/Wind Harmer
3.34
315737AD1-076 GEN
Solar/Wind Harmer
3.567
3146206CASHIE
Solar/Wind Harmer
0.273
3156081AA2-088 GEN
Solar/Wind Harmer
0.006
3145893MURPHYS
Solar/Wind Harmer
0.451
3145893MURPHYS
Solar/Wind Harmer
0.269
957521AF2-046 GEN
Solar/Wind Harmer
20.016
961681AG1-008 GEN
Solar/Wind Harmer
20.016
962971AG1-146 GEN
Solar/Wind Harmer
4.293
3156021HOLLOMANSOL
Solar/Wind Harmer
1.218
3146173TUNIS
Solar/Wind Harmer
0.267
316463AE2-346 GEN
Solar/Wind Harmer
0.229
316140AB2-099
Solar/Wind Harmer
0.095
962331AG1-082 GEN
Solar/Wind Harmer
2.839
316365GEN2_N
Solar/Wind Harmer
0.59
3145963POPLR C
Solar/Wind Harmer
0.263
972263AH1-716 GEN
50/50
194.204
3151081ELIZAR1
50/50
30.584
3151091ELIZAR2
50/50
30.053
941591AE2-156 GEN
50/50
27.947
3152611GOSPORTB
50/50
4.245
3152621GOSPORTC
50/50
3.603
3152601GOSPORTA
50/50
3.323
315976AC1-164 GENA
Solar/Wind Harmer
34.449
316169AC1-164_GENC
Solar/Wind Harmer
29.761
315975AC1-164 GENB
Solar/Wind Harmer
1.019
316312AB1-027
Solar/Wind Harmer
0.592
971445AH1-216 GEN
Solar/Wind Harmer
22.015
972265AH1-717 GEN
Adder
24.205
3151201GRAVEL4
Adder
22.69
3151191GRAVEL3
Adder
22.403
3151211GRAVEL5
Adder
22.403
957871AF2-081 GEN
Solar/Wind Harmer
15.477
319010AE1-072 C
Solar/Wind Harmer
1.561
3146406KITTY HAWK
Solar/Wind Harmer
0.039
3138283WHITEMARSH
Solar/Wind Harmer
0.072
316305AF2-043 C
Solar/Wind Harmer
0.002
316369SG1_INVT
Solar/Wind Harmer
0.011
972193AH1-681 GEN
Adder
7.039
313526AB2-022
Solar/Wind Harmer
0.166
316132AB2-190 GEN1
Solar/Wind Harmer
1.639
3146486SUNBURY
Solar/Wind Harmer
0.305
3146486SUNBURY
Solar/Wind Harmer
0.305
315835AF2-110_GEN
Solar/Wind Harmer
2.092
316321Z2-027
Solar/Wind Harmer
0.057
3146396TANGLEW
Solar/Wind Harmer
0.839
3145176PASQUOTANK
Solar/Wind Harmer
0.189
316314AB2-024 C
Solar/Wind Harmer
0.001
316311AC2-079 GEN
Solar/Wind Harmer
8.688
315833AF1-017_GEN
Solar/Wind Harmer
0.002
316349AD2-085 GEN
Solar/Wind Harmer
0.207
3143873LANEXA
Solar/Wind Harmer
0.181
3142433PROV 92
Adder
0.583
3142433PROV 92
Adder
0.583
971167AH1-042 GEN
Solar/Wind Harmer
26.63
316059AD1-063 C
Solar/Wind Harmer
0.002
970189AG2-124 GEN
Solar/Wind Harmer
8.811
315662AE1-191 GEN
Solar/Wind Harmer
0.01
315666AE1-190 GEN
Solar/Wind Harmer
0.002
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.059
3130156CHOWAN
Solar/Wind Harmer
0.292
3130156CHOWAN
Solar/Wind Harmer
0.292
3143316POE
Solar/Wind Harmer
1.153
3141913WHIT STONE
Solar/Wind Harmer
0.285
315816AE2-034 GEN
Solar/Wind Harmer
1.219
3138133OCRAN
Solar/Wind Harmer
0.085
316315AB2-025 C
Solar/Wind Harmer
0.226
315814AE2-033 C
Solar/Wind Harmer
22.041
941031AE2-094 GEN
Solar/Wind Harmer
51.279
944011AF1-069 GEN
Solar/Wind Harmer
16.755
3141783LANCAST
Solar/Wind Harmer
0.167
3141783LANCAST
Solar/Wind Harmer
0.111
3130546PLYMOUTH
Solar/Wind Harmer
0.278
315732AD1-074 GEN1
Solar/Wind Harmer
1.593
315733AD1-074 GEN2
Solar/Wind Harmer
1.593
315735AD1-075 GEN1
Solar/Wind Harmer
0.797
970673AG2-436 GEN
Solar/Wind Harmer
58.436
970673AG2-436 GEN
Solar/Wind Harmer
38.957
3146206CASHIE
Solar/Wind Harmer
0.273
970601AG2-382 GEN
Solar/Wind Harmer
10.212
965291AG1-394 GEN
Solar/Wind Harmer
1.209
971967AH1-528 GEN
Solar/Wind Harmer
43.16
3145893MURPHYS
Solar/Wind Harmer
0.728
3145893MURPHYS
Solar/Wind Harmer
0.269
962981AG1-147 GEN
Solar/Wind Harmer
10.018
3145513AHOSKIE
Solar/Wind Harmer
0.556
3145513AHOSKIE
Solar/Wind Harmer
0.266
3145683EARLEYS
Solar/Wind Harmer
0.53
3145683EARLEYS
Solar/Wind Harmer
0.265
3145683EARLEYS
Solar/Wind Harmer
0.265
970327AG2-215 GEN
Solar/Wind Harmer
8.614
3146043SEABORD
Solar/Wind Harmer
0.261
315607AA1-063A GEN
Solar/Wind Harmer
0.531
970085AG2-068 GEN
Solar/Wind Harmer
13.834
970581AG2-369 GEN
Solar/Wind Harmer
11.898
315652AC1-086 GEN
Solar/Wind Harmer
28.063
316087AB2-174 GEN
Solar/Wind Harmer
0.007
3137643SOCKMAN
Solar/Wind Harmer
1.011
3146033SCOT NK
Solar/Wind Harmer
1.01
971285AH1-108 GEN
Adder
1.899
3145796HORNRTN
Solar/Wind Harmer
0.805
3145796HORNRTN
Solar/Wind Harmer
0.101
316005AA1-067
Solar/Wind Harmer
0.262
3145746EVERETS
Solar/Wind Harmer
0.973
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
970181AG2-120 GEN
Solar/Wind Harmer
3.044
957861AF2-080 GEN
Solar/Wind Harmer
10.333
316420AA1-050 GEN
Solar/Wind Harmer
0.008
970831AG2-522 GEN
Solar/Wind Harmer
10.106
3141813NORNECK
Solar/Wind Harmer
0.236
3145573BETHELC
Solar/Wind Harmer
0.235
3145573BETHELC
Solar/Wind Harmer
0.235
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
972189AH1-679 GEN
Adder
3.657
971443AH1-215 GEN
Solar/Wind Harmer
3.537
3144303KENBRDG
Solar/Wind Harmer
0.168
316118AC1-105 GEN
Solar/Wind Harmer
0.54
3147173SINAI
Solar/Wind Harmer
0.207
3147243WELCO
Solar/Wind Harmer
0.129
970683AG2-441 GEN
Solar/Wind Harmer
13.748
3152331SURRY 2
50/50
13.991
971353AH1-157 GEN
50/50
28.65
970017AG2-010 GEN
50/50
21.737
3150981CHESPKA
50/50
4.162
3142416OLDCHRC
Solar/Wind Harmer
0.86
3142416OLDCHRC
Solar/Wind Harmer
0.33
316159AE1-175 C
Solar/Wind Harmer
0.283
316294AC1-161 GEN
Solar/Wind Harmer
5.617
971317AH1-138 GEN
Solar/Wind Harmer
2.41
3138126ROCKLANDING
Solar/Wind Harmer
0.148
944591AF1-124 GEN
Solar/Wind Harmer
71.262
316375AC2-012 GEN
Solar/Wind Harmer
0.008
3145336SMITFLD
Solar/Wind Harmer
1.25
3151171GRAVELC
Adder
3.316
316388AE2-253 GEN
Solar/Wind Harmer
0.975
316072AD1-144
Solar/Wind Harmer
0.112
3146456SLIGO L269
Solar/Wind Harmer
0.31
961611AG1-000B GEN
Solar/Wind Harmer
16.269
971647AH1-324 GEN
Solar/Wind Harmer
13.184
316246AF1-032 C
Solar/Wind Harmer
0.139
944631AF1-128 GEN
Adder
146.833
972277AH1-723 GEN
Adder
183.583
971069AG2-661 GEN
Solar/Wind Harmer
5.456
316458AB2-190 GEN2
Solar/Wind Harmer
1.639
970129AG2-093 GEN
Solar/Wind Harmer
8.684
316093AE2-104_GEN
Solar/Wind Harmer
5.127
3146516WINFALL
Solar/Wind Harmer
0.976
3146516WINFALL
Solar/Wind Harmer
0.301
3142433PROV 92
Solar/Wind Harmer
1.2
3142433PROV 92
Adder
0.583
3142433PROV 92
Adder
0.583
970661AG2-428 GEN
Solar/Wind Harmer
29.836
3141766HARMONY
Solar/Wind Harmer
0.06
939411AE1-173 GEN
Solar/Wind Harmer
127.601
316381AD1-082 GEN
Solar/Wind Harmer
0.311
970659AG2-427 GEN
Solar/Wind Harmer
14.437
971777AH1-397 GEN
Solar/Wind Harmer
0.785
3141843SHACKLE
Adder
1.519
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
315671AE2-027_GEN
Solar/Wind Harmer
18.84
940641AE2-051 GEN
Solar/Wind Harmer
23.538
3143096IRON208
Adder
1.226
3130156CHOWAN
Solar/Wind Harmer
0.292
3145663CRESWEL
Solar/Wind Harmer
0.795
971163AH1-040 GEN
Solar/Wind Harmer
22.732
3138133OCRAN
Solar/Wind Harmer
0.17
3142543TWELFTH
Solar/Wind Harmer
0.027
3146206CASHIE
Solar/Wind Harmer
0.273
971547AH1-271 GEN
Solar/Wind Harmer
5.835
3145893MURPHYS
Solar/Wind Harmer
1.078
3145893MURPHYS
Solar/Wind Harmer
1.199
3146173TUNIS
Solar/Wind Harmer
0.267
3145683EARLEYS
Solar/Wind Harmer
0.265
316023GEN1_S
Solar/Wind Harmer
0.59
3145963POPLR C
Solar/Wind Harmer
0.263
3146263WOODLND
Solar/Wind Harmer
0.261
316174AB2-169 GEN
Solar/Wind Harmer
0.007
970919AG2-571 GEN
Solar/Wind Harmer
9.256
970087AG2-069 GEN
Solar/Wind Harmer
20.752
3145823KELFORD
Solar/Wind Harmer
0.259
962861AG1-135 GEN
Solar/Wind Harmer
8.175
316011AB1-132 GEN
Solar/Wind Harmer
4.638
962571AG1-106 GEN
Solar/Wind Harmer
3.63
960081AF2-299 GEN
Solar/Wind Harmer
2.448
316190AA2-174 GEN
Solar/Wind Harmer
0
3150851SPRUNCC
Adder
1.161
3145796HORNRTN
Solar/Wind Harmer
0.83
3145796HORNRTN
Solar/Wind Harmer
0.251
3145783HORNRTN
Solar/Wind Harmer
0.251
3146293MARTNCO
Solar/Wind Harmer
0.232
316212AC1-099_GEN
Solar/Wind Harmer
1.281
971795AH1-408 GEN
Solar/Wind Harmer
16.501
3141726DUNNSVL
Solar/Wind Harmer
0.979
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
970009AG2-005 GEN
Solar/Wind Harmer
1.96
3146263WOODLND
Solar/Wind Harmer
0.261
970917AG2-570 GEN
Solar/Wind Harmer
23.14
316317KELFORD C
Solar/Wind Harmer
0.025
3145823KELFORD
Solar/Wind Harmer
0.259
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
313506AB2-031 GEN
Solar/Wind Harmer
0.784
316404AE1-155 C
Solar/Wind Harmer
0.057
3150861SPRUNCD
Adder
1.161
3145796HORNRTN
Solar/Wind Harmer
1.006
3145796HORNRTN
Solar/Wind Harmer
0.251
3145933PARMELE
Solar/Wind Harmer
0.25
966801AG1-551 GEN
Solar/Wind Harmer
2.916
316210AC1-098 GEN
Solar/Wind Harmer
2.297
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
3147043LAWRENC
Solar/Wind Harmer
0.146
315724AD1-057 GEN
Solar/Wind Harmer
0.9
316327AA2-057 GEN
Solar/Wind Harmer
0.36
3150351NORNECKC2
Adder
2.392
316478AD1-087 GEN
Solar/Wind Harmer
0.823
316486AD2-202 GEN
Solar/Wind Harmer
0.242
3146073TAR RVR
Solar/Wind Harmer
0.235
3146083TARBORO
Solar/Wind Harmer
0.235
3146233WITAKRS
Solar/Wind Harmer
1.176
3146233WITAKRS
Solar/Wind Harmer
0.159
3138543CONSLDL
Solar/Wind Harmer
0.154
961601AG1-000A GEN
Solar/Wind Harmer
16.379
3145543BTLEBRO
Solar/Wind Harmer
0.23
3145543BTLEBRO
Solar/Wind Harmer
0.23
971623AH1-311 GEN
Solar/Wind Harmer
0.46
316131AB2-060 GEN
Solar/Wind Harmer
0.687
964241AG1-285 GEN
Solar/Wind Harmer
14.393
315785AD2-033 C
Solar/Wind Harmer
1.721
970257AG2-171 GEN
Solar/Wind Harmer
6.725
959311AF2-222 GEN
Solar/Wind Harmer
18.581
971781AH1-399 GEN
Solar/Wind Harmer
0.272
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
8.82
970909AG2-566 GEN
Solar/Wind Harmer
2.199
963181AG1-167 GEN
Solar/Wind Harmer
0.81
3144293JTRSVLE
Adder
0.645
3147133PAMPLIN
Solar/Wind Harmer
0.627
971193AH1-056 GEN
Solar/Wind Harmer
12.172
957481AF2-042 GEN
Solar/Wind Harmer
65.115
3147043LAWRENC
Adder
2.208
315722AD1-056 GEN
Solar/Wind Harmer
1.518
316494AC1-189 GEN
Solar/Wind Harmer
0.81
3150351NORNECKC2
Adder
2.352
315693AD1-088 GEN
Solar/Wind Harmer
11.318
961671AG1-007 GEN
Solar/Wind Harmer
0.036
3146083TARBORO
Solar/Wind Harmer
0.235
3145493TOT1
Solar/Wind Harmer
1.047
316129AC1-054 GEN
Solar/Wind Harmer
0.885
3146233WITAKRS
Solar/Wind Harmer
0.932
962491AG1-098 GEN
Solar/Wind Harmer
13.368
971065AG2-659 GEN
Solar/Wind Harmer
9.97
3145543BTLEBRO
Solar/Wind Harmer
0.23
3145543BTLEBRO
Solar/Wind Harmer
0.184
316359AB2-059 GEN
Solar/Wind Harmer
0.827
316049AB1-081 GEN
Solar/Wind Harmer
1.317
3142053HEARTS
Solar/Wind Harmer
0.405
315687AD1-152 GEN
Solar/Wind Harmer
0.007
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970401AG2-262 GEN
Solar/Wind Harmer
1.243
316337AD2-073 GEN
Solar/Wind Harmer
0.18
970685AG2-442 GEN
Solar/Wind Harmer
15.398
963171AG1-166 GEN
Solar/Wind Harmer
1.08
971563AH1-280 GEN
Solar/Wind Harmer
2.16
3144293JTRSVLE
Adder
0.645
316003AC1-222 GEN
Solar/Wind Harmer
0.005
3143526WINTERP
Solar/Wind Harmer
0.968
3146926FARMVIL
Solar/Wind Harmer
0.111
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.065
970223AG2-152 GEN
Solar/Wind Harmer
10.425
270016AE1-250 BESS
Solar/Wind Harmer
0.004
3147123OTTER R
Solar/Wind Harmer
0.085
972003AH1-546 GEN
Solar/Wind Harmer
5.963
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.109
3146802CHATHAM
Solar/Wind Harmer
0.102
941801AE2-185 GEN
Solar/Wind Harmer
4.349
970937AG2-583 GEN
Solar/Wind Harmer
8.286
316336AC2-165 C
Solar/Wind Harmer
0.005
3143336POWHATN
Solar/Wind Harmer
2.393
3143226MDLTHAN
Solar/Wind Harmer
0.134
971377AH1-170 GEN
Solar/Wind Harmer
1.425
3147623JAMES R
Solar/Wind Harmer
0.31
972135AH1-637 GEN
Solar/Wind Harmer
1.098
270173AC1-122 GEN
Solar/Wind Harmer
0.31
270030AE2-140 GEN
Solar/Wind Harmer
13.116
315705AF1-075 GEN
Solar/Wind Harmer
4.718
962751AG1-124 GEN
Solar/Wind Harmer
5.402
970681AG2-440 GEN
Solar/Wind Harmer
10.999
946301AF1-294 GEN
Solar/Wind Harmer
3.996
961791AG1-021 GEN
Solar/Wind Harmer
1.944
315657AE1-056 GEN
Solar/Wind Harmer
6.894
970865AG2-541 GEN
Solar/Wind Harmer
6.515
316233AE1-074 FULL
Solar/Wind Harmer
0.149
971281AH1-106 GEN
Solar/Wind Harmer
2.583
971283AH1-107 GEN
Solar/Wind Harmer
2.583
316223AC1-118
Solar/Wind Harmer
0.126
316123AC1-075 GEN
Solar/Wind Harmer
0.24
970165AG2-112 GEN
Solar/Wind Harmer
1.423
970163AG2-111 GEN
Solar/Wind Harmer
1.357
970285AG2-188 GEN
Solar/Wind Harmer
13.264
971845AH1-439 GEN
Solar/Wind Harmer
7.44
3148463FAIRFLD
Solar/Wind Harmer
0.138
3151881LOWMORC
Adder
1.466
3151881LOWMORC
Adder
1.443
3151861LOWMORA
Adder
1.42
3148133STUARTS
Solar/Wind Harmer
0.081
3148013FISHERV
Solar/Wind Harmer
0.078
972205AH1-687 GEN
Adder
5.785
971447AH1-217 GEN
Solar/Wind Harmer
4.064
270494AE1-108_GEN
Solar/Wind Harmer
1.551
270069AE2-166 C O1
Solar/Wind Harmer
0.004
316164AC1-076 GEN
Solar/Wind Helper
1.573
316411AF1-147_GEN1
Solar/Wind Helper
0.945
316415AF1-147_GEN2
Solar/Wind Helper
0.945
3138216PACIFIC
Solar/Wind Helper
0.046
3141426STAFORD
Solar/Wind Helper
0.055
3150671DARBY 1
Adder
22.239
3137176SLIGO L2192
Solar/Wind Harmer
1.234
3146456SLIGO L269
Solar/Wind Harmer
5.488
3130086AYDLETT
Solar/Wind Harmer
1.238
316033AB2-134 GEN
Solar/Wind Harmer
0.018
315697AD1-025 GEN
Solar/Wind Harmer
0.346
3146386ELIZ CT
Solar/Wind Harmer
0.306
3142366NRTHEST
Adder
1
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.301
3146516WINFALL
Solar/Wind Harmer
0.301
3146516WINFALL
Solar/Wind Harmer
0.301
966871AG1-558 GEN
Solar/Wind Harmer
0.347
970657AG2-426 GEN
Solar/Wind Harmer
10.482
970657AG2-426 GEN
Solar/Wind Harmer
2.198
3146626S HERTFORD
Solar/Wind Harmer
0.299
3146626S HERTFORD
Solar/Wind Harmer
0.299
944641AF1-129 GEN
Adder
140.632
316240AF1-291 C
Solar/Wind Harmer
0.002
3146376EDENTON
Solar/Wind Harmer
1.297
3146376EDENTON
Solar/Wind Harmer
1.297
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3144356SAPONY
Solar/Wind Harmer
2.337
316065AD1-022 GEN
Solar/Wind Harmer
12.657
972185AH1-677 GEN
Adder
15.245
3145893MURPHYS
Solar/Wind Harmer
1.804
3145893MURPHYS
Solar/Wind Harmer
0.485
972187AH1-678 GEN
Adder
7.651
3146173TUNIS
Solar/Wind Harmer
0.267
3146173TUNIS
Solar/Wind Harmer
0.267
970933AG2-581 GEN
Solar/Wind Harmer
21
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
316426AA2-053 GEN
Solar/Wind Harmer
0.86
316181AB2-040 GEN
Solar/Wind Harmer
0.368
958261AF2-120 GEN
Solar/Wind Harmer
8.365
3145593CAROLNA
Solar/Wind Harmer
0.252
3145593CAROLNA
Solar/Wind Harmer
0.252
966811AG1-552 GEN
Solar/Wind Harmer
2.738
3145593CAROLNA
Solar/Wind Harmer
0.314
3145796HORNRTN
Solar/Wind Harmer
0.754
3145783HORNRTN
Solar/Wind Harmer
4.467
3145783HORNRTN
Solar/Wind Harmer
3.574
3145783HORNRTN
Solar/Wind Harmer
1.117
3145783HORNRTN
Solar/Wind Harmer
0.447
3145933PARMELE
Solar/Wind Harmer
0.501
3145933PARMELE
Solar/Wind Harmer
0.25
316274AC1-208 GEN
Solar/Wind Harmer
1.272
970099AG2-077 GEN
Solar/Wind Harmer
26.046
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.471
3150341NORNECKC1
Adder
2.451
3145493TOT1
Solar/Wind Harmer
0.546
3145453TOT5
Solar/Wind Harmer
0.327
3145603CNETO
Solar/Wind Harmer
0.218
961601AG1-000A GEN
Solar/Wind Harmer
4.095
316263AC1-034 GEN
Solar/Wind Harmer
8.746
939181AE1-148 GEN
Solar/Wind Harmer
10.786
313527AB2-043 GEN
Solar/Wind Harmer
0.003
971741AH1-377 GEN
Solar/Wind Harmer
21.126
962561AG1-105 GEN
Solar/Wind Harmer
10.222
964791AG1-342 GEN
Solar/Wind Harmer
4.068
3146843MT LREL
Solar/Wind Harmer
0.212
3146843MT LREL
Solar/Wind Harmer
0.212
970323AG2-213 GEN
Solar/Wind Harmer
8.967
971775AH1-396 GEN
Solar/Wind Harmer
0.336
316034AC1-036 C
Solar/Wind Harmer
0.015
316468AD1-105 GEN
Solar/Wind Harmer
-0.067
970301AG2-198 GEN
Solar/Wind Harmer
8.797
958211AF2-115 GEN
Solar/Wind Harmer
2.43
963191AG1-168 GEN
Solar/Wind Harmer
0.81
3144293JTRSVLE
Adder
0.645
3144293JTRSVLE
Adder
0.543
3147133PAMPLIN
Solar/Wind Harmer
0.2
3147133PAMPLIN
Solar/Wind Harmer
0.16
316222AC1-221 GEN
Solar/Wind Harmer
0.802
3143526WINTERP
Solar/Wind Harmer
0.968
942751AE2-291 GEN
Solar/Wind Harmer
9.118
3146776BUCKING
Solar/Wind Harmer
0.649
3146776BUCKING
Solar/Wind Harmer
0.052
270013AE1-250 PV
Solar/Wind Harmer
0.004
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.383
315821AE2-092 GEN
Solar/Wind Harmer
0.008
971223AH1-071 GEN
Solar/Wind Harmer
1.43
971489AH1-241 GEN
Solar/Wind Harmer
7.125
316447AC1-158 HLD
Solar/Wind Helper
4.499
315651AD1-115 GEN
Solar/Wind Helper
0.98
226929AD2-058 GEN
Solar/Wind Helper
0.113
23777801MSM_W1-116
Solar/Wind Helper
0.096
237025AB1-124 C
Solar/Wind Helper
0.14
237006AB1-125 GEN
Solar/Wind Helper
0.105
316045AC1-158 PL2
Solar/Wind Helper
6.543
316006AB2-029 C
Solar/Wind Helper
0.142
316254AC1-120 GEN1
Solar/Wind Helper
1.333
3147666LOUISA
Solar/Wind Helper
1.029
316192AB2-158 GEN
Solar/Wind Helper
1.689
223401AF1-299 GEN
Solar/Wind Helper
0.346
23779801AA1-109
Solar/Wind Helper
0.161
971683AH1-343 GEN
Solar/Wind Harmer
7.141
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316283AC2-100 C
Solar/Wind Harmer
0.376
3146926FARMVIL
Solar/Wind Harmer
0.111
3141906WESTMOR
Solar/Wind Harmer
0.07
3146776BUCKING
Solar/Wind Harmer
0.058
970737AG2-469 GEN
Solar/Wind Harmer
6.299
270197AD1-017 GEN1
Solar/Wind Harmer
0.911
315616AA1-038_C
Solar/Wind Harmer
0.001
3151861LOWMORA
Adder
1.478
3147312GRETNA
Solar/Wind Harmer
0.027
941821AE2-187 GEN
Solar/Wind Harmer
4.349
3148013FISHERV
Solar/Wind Harmer
0.135
316313AB2-026
Solar/Wind Harmer
0.085
316258AE1-075 C
Solar/Wind Harmer
0.102
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.034
970221AG2-151 GEN
Solar/Wind Harmer
7.125
270018AE2-047 C O1
Solar/Wind Harmer
0.003
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
958131AF2-107 GEN
Solar/Wind Harmer
3.424
270336AE1-100 GEN
Solar/Wind Harmer
0.003
971367AH1-164 GEN
Solar/Wind Harmer
2.104
316044AC1-158 PL1
Solar/Wind Helper
2.044
316450AC1-158 RIC
Solar/Wind Helper
0.545
3141196NOKESVL
Solar/Wind Helper
1.216
316170AC1-121 GEN2
Solar/Wind Helper
0.444
227287AC2-120 GEN
Solar/Wind Helper
0.383
226910AB2-157 C
Solar/Wind Helper
0.016
3147666LOUISA
Solar/Wind Helper
0.591
223402AF1-300 C
Solar/Wind Helper
0.346
237030AB1-096 C
Solar/Wind Helper
0.06
LAGNLTFEXP_LAGN->PJM
CLTF
12.709
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.309
TVALTFEXP_TVA->PJM
CLTF
6.437
NYPJM->LTFIMP_NY
CLTF
4.044
LGEELTFEXP_LGEE->PJM
CLTF
2.658
WECLTFEXP_WEC->PJM
CLTF
1.346
AG2-052LTFEXP_AG2-052->PJM
LTF
0.074
AH1-155LTFEXP_AH1-155->PJM
LTF
0.112
CBM West 1LTFEXP_CBM-W1->PJM
CBM
47.354
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.437
MECLTFEXP_MEC->PJM
CLTF
6.883
SIGELTFEXP_SIGE->PJM
CLTF
0.213
CPLELTFEXP_CPLE->PJM
CLTF
15.123
CBM West 2LTFEXP_CBM-W2->PJM
CBM
70.159

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.98 %
Rating:4070.2 MVA
Rating Type:A
MVA to Mitigate:4842.75
MW Contribution:7.79
Bus #Bus NameTypeMW Contribution
971645AH1-323 GEN
50/50
29.668
3152191CUNINGD
50/50
5.586
3152171CUNINGB
50/50
2.411
972255AH1-712 GEN
50/50
168.86
3142416OLDCHRC
Solar/Wind Harmer
3.115
970293AG2-193 GEN
Solar/Wind Harmer
3.254
316473AC1-191 GEN
Solar/Wind Harmer
1.006
3142946ENON
Solar/Wind Harmer
0.098
316382AG1-145 C
Solar/Wind Harmer
0.002
3143096IRON208
Adder
1.181
3143096IRON208
Adder
1.157
3142433PROV 92
Adder
0.534
3142433PROV 92
Adder
0.534
3150921YORKTN3
Adder
6.858
3144216WINCHST
Adder
1.022
3142296MT RD221
50/50
1.091
3150691DARBY 3
50/50
22.95
3150701DARBY 4
50/50
22.896
3150681DARBY 2
50/50
22.869
3150671DARBY 1
50/50
22.843
3142366NRTHEST
50/50
1.033
316075AC2-137 C
Solar/Wind Harmer
0.085
966871AG1-558 GEN
Solar/Wind Harmer
0.344
3142946ENON
Solar/Wind Harmer
0.029
316033AB2-134 GEN
Solar/Wind Harmer
0.015
315697AD1-025 GEN
Solar/Wind Harmer
0.295
944641AF1-129 GEN
Adder
124.433
316240AF1-291 C
Solar/Wind Harmer
0.002
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316036AC1-147 C
Solar/Wind Harmer
0.046
3150991CHESPKB
Adder
2.57
3150991CHESPKB
Adder
2.508
316316AC1-027 C
Solar/Wind Harmer
0.234
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.007
3145506HICKORY
Solar/Wind Harmer
0.97
3145506HICKORY
Solar/Wind Harmer
0.582
3145506HICKORY
Solar/Wind Harmer
0.146
316339AD2-160 GEN
Solar/Wind Harmer
0.392
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.135
3137176SLIGO L2192
Solar/Wind Harmer
0.957
3146456SLIGO L269
Solar/Wind Harmer
4.255
3130086AYDLETT
Solar/Wind Harmer
0.96
970657AG2-426 GEN
Solar/Wind Harmer
8.387
970657AG2-426 GEN
Solar/Wind Harmer
1.758
3146386ELIZ CT
Solar/Wind Harmer
0.237
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
3146626S HERTFORD
Solar/Wind Harmer
0.23
3146626S HERTFORD
Solar/Wind Harmer
0.23
958261AF2-120 GEN
Solar/Wind Harmer
7.587
3146376EDENTON
Solar/Wind Harmer
0.994
3146376EDENTON
Solar/Wind Harmer
0.994
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3143526WINTERP
Solar/Wind Harmer
1.125
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.255
3150341NORNECKC1
Adder
2.237
316468AD1-105 GEN
Solar/Wind Harmer
-0.068
316065AD1-022 GEN
Solar/Wind Harmer
9.583
3145893MURPHYS
Solar/Wind Harmer
1.358
3145893MURPHYS
Solar/Wind Harmer
0.365
3144356SAPONY
Solar/Wind Harmer
1.697
3146173TUNIS
Solar/Wind Harmer
0.201
3146173TUNIS
Solar/Wind Harmer
0.201
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3142666NORTHAMPTON
Solar/Wind Harmer
0.114
316426AA2-053 GEN
Solar/Wind Harmer
0.635
3145933PARMELE
Solar/Wind Harmer
0.373
3145933PARMELE
Solar/Wind Harmer
0.186
316181AB2-040 GEN
Solar/Wind Harmer
0.27
3145593CAROLNA
Solar/Wind Harmer
0.186
3145593CAROLNA
Solar/Wind Harmer
0.186
966811AG1-552 GEN
Solar/Wind Harmer
2.014
3145593CAROLNA
Solar/Wind Harmer
0.231
3145783HORNRTN
Solar/Wind Harmer
3.287
3145783HORNRTN
Solar/Wind Harmer
2.629
3145783HORNRTN
Solar/Wind Harmer
0.822
3145783HORNRTN
Solar/Wind Harmer
0.329
3145796HORNRTN
Solar/Wind Harmer
0.554
971223AH1-071 GEN
Solar/Wind Harmer
1.938
316274AC1-208 GEN
Solar/Wind Harmer
0.935
972185AH1-677 GEN
Adder
9.694
3145493TOT1
Solar/Wind Harmer
0.4
3152161CUNINGA
50/50
2.401
972277AH1-723 GEN
50/50
196.773
3142416OLDCHRC
Solar/Wind Harmer
0.835
3142416OLDCHRC
Solar/Wind Harmer
0.32
316159AE1-175 C
Solar/Wind Harmer
0.248
944631AF1-128 GEN
Adder
136.402
3143096IRON208
Adder
1.181
971317AH1-138 GEN
Solar/Wind Harmer
2.064
3142433PROV 92
Solar/Wind Harmer
1.099
3142433PROV 92
Adder
0.534
3142433PROV 92
Adder
0.534
3138126ROCKLANDING
Solar/Wind Harmer
0.125
3141766HARMONY
Solar/Wind Harmer
0.054
3142543TWELFTH
Solar/Wind Harmer
0.026
971777AH1-397 GEN
Solar/Wind Harmer
0.709
3141843SHACKLE
Adder
1.372
970129AG2-093 GEN
Solar/Wind Harmer
7.556
316458AB2-190 GEN2
Solar/Wind Harmer
1.424
971069AG2-661 GEN
Solar/Wind Harmer
4.688
971647AH1-324 GEN
Solar/Wind Harmer
11.14
961611AG1-000B GEN
Solar/Wind Harmer
13.616
3151171GRAVELC
Adder
2.743
3138133OCRAN
Solar/Wind Harmer
0.153
315671AE2-027_GEN
Solar/Wind Harmer
16.232
3150851SPRUNCC
Adder
1.168
3145336SMITFLD
Solar/Wind Harmer
1.012
316294AC1-161 GEN
Solar/Wind Harmer
4.367
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
3.063
316072AD1-144
Solar/Wind Harmer
0.089
944591AF1-124 GEN
Solar/Wind Harmer
55.179
316388AE2-253 GEN
Solar/Wind Harmer
0.757
3146456SLIGO L269
Solar/Wind Harmer
0.24
970659AG2-427 GEN
Solar/Wind Harmer
11.595
316246AF1-032 C
Solar/Wind Harmer
0.108
316381AD1-082 GEN
Solar/Wind Harmer
0.25
970661AG2-428 GEN
Solar/Wind Harmer
23.793
316093AE2-104_GEN
Solar/Wind Harmer
3.989
3146516WINFALL
Solar/Wind Harmer
0.754
3146516WINFALL
Solar/Wind Harmer
0.232
962861AG1-135 GEN
Solar/Wind Harmer
7.409
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3141726DUNNSVL
Solar/Wind Harmer
0.895
3130156CHOWAN
Solar/Wind Harmer
0.224
3145663CRESWEL
Solar/Wind Harmer
0.606
971163AH1-040 GEN
Solar/Wind Harmer
17.339
3143526WINTERP
Solar/Wind Harmer
1.125
3150351NORNECKC2
Adder
2.147
3146206CASHIE
Solar/Wind Harmer
0.207
971547AH1-271 GEN
Solar/Wind Harmer
4.412
939411AE1-173 GEN
Solar/Wind Harmer
87.698
3145893MURPHYS
Solar/Wind Harmer
0.811
3145893MURPHYS
Solar/Wind Harmer
0.902
3146173TUNIS
Solar/Wind Harmer
0.201
3145683EARLEYS
Solar/Wind Harmer
0.198
3145963POPLR C
Solar/Wind Harmer
0.197
316174AB2-169 GEN
Solar/Wind Harmer
0.005
3146263WOODLND
Solar/Wind Harmer
0.195
3145823KELFORD
Solar/Wind Harmer
0.193
940641AE2-051 GEN
Solar/Wind Harmer
15.435
3141766HARMONY
Solar/Wind Harmer
3.615
3141843SHACKLE
Adder
1.372
970133AG2-095 GEN
Solar/Wind Harmer
2.576
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.005
970129AG2-093 GEN
Solar/Wind Harmer
16.057
316156AD2-030 GEN
Solar/Wind Harmer
0.195
3141873WAN 176
Solar/Wind Harmer
4.689
315778AD1-151 GEN
Solar/Wind Harmer
21.096
961611AG1-000B GEN
Solar/Wind Harmer
6.924
3151221GRAVEL6
Adder
18.744
3151171GRAVELC
Adder
3.606
3150861SPRUNCD
Adder
1.168
3145336SMITFLD
Solar/Wind Harmer
0.101
315773AC2-141 GEN
Solar/Wind Harmer
9.204
965281AG1-393 GEN
Solar/Wind Harmer
2.675
3144536CHRHLND
Solar/Wind Harmer
0.037
315839AE2-212 C
Solar/Wind Harmer
0.002
3151101ELIZAR3
Adder
22.773
3144873MCLAUGH
Solar/Wind Harmer
0.006
944581AF1-123 GEN
Solar/Wind Harmer
54.983
944601AF1-125 GEN
Solar/Wind Harmer
54.137
962971AG1-146 GEN
Solar/Wind Harmer
3.875
315813AE1-149 C
Solar/Wind Harmer
12.831
3146456SLIGO L269
Solar/Wind Harmer
0.24
971153AH1-033 GEN
Solar/Wind Harmer
2.78
970659AG2-427 GEN
Solar/Wind Harmer
2.536
316083AB2-161 GEN
Solar/Wind Harmer
0.003
970661AG2-428 GEN
Solar/Wind Harmer
5.061
970009AG2-005 GEN
Solar/Wind Harmer
1.772
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.232
3146626S HERTFORD
Solar/Wind Harmer
0.23
316404AE1-155 C
Solar/Wind Harmer
0.052
3145273HOLLAND
Solar/Wind Harmer
0.171
3146376EDENTON
Solar/Wind Harmer
0.224
315614AA2-178 GEN
Solar/Wind Harmer
1.24
3150351NORNECKC2
Adder
2.183
971157AH1-035 GEN
Solar/Wind Harmer
2.537
315737AD1-076 GEN
Solar/Wind Harmer
2.707
971781AH1-399 GEN
Solar/Wind Harmer
0.275
3146206CASHIE
Solar/Wind Harmer
0.207
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
3145893MURPHYS
Solar/Wind Harmer
0.34
3145893MURPHYS
Solar/Wind Harmer
0.203
957521AF2-046 GEN
Solar/Wind Harmer
15.055
961681AG1-008 GEN
Solar/Wind Harmer
15.055
3156021HOLLOMANSOL
Solar/Wind Harmer
0.916
3146173TUNIS
Solar/Wind Harmer
0.201
316463AE2-346 GEN
Solar/Wind Harmer
0.171
316140AB2-099
Solar/Wind Harmer
0.071
962331AG1-082 GEN
Solar/Wind Harmer
2.13
3145963POPLR C
Solar/Wind Harmer
0.197
3146263WOODLND
Solar/Wind Harmer
0.195
316317KELFORD C
Solar/Wind Harmer
0.019
3145823KELFORD
Solar/Wind Harmer
0.193
316365GEN2_N
Solar/Wind Harmer
0.432
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3145933PARMELE
Solar/Wind Harmer
0.186
966801AG1-551 GEN
Solar/Wind Harmer
2.17
313506AB2-031 GEN
Solar/Wind Harmer
0.575
3145796HORNRTN
Solar/Wind Harmer
0.739
3145796HORNRTN
Solar/Wind Harmer
0.185
316210AC1-098 GEN
Solar/Wind Harmer
1.695
3145746EVERETS
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
3147043LAWRENC
Solar/Wind Harmer
0.107
315724AD1-057 GEN
Solar/Wind Harmer
0.658
316327AA2-057 GEN
Solar/Wind Harmer
0.264
3146073TAR RVR
Solar/Wind Harmer
0.172
3146083TARBORO
Solar/Wind Harmer
0.172
3146233WITAKRS
Solar/Wind Harmer
0.859
3146233WITAKRS
Solar/Wind Harmer
0.116
3138543CONSLDL
Solar/Wind Harmer
0.113
961601AG1-000A GEN
Solar/Wind Harmer
11.93
3145543BTLEBRO
Solar/Wind Harmer
0.167
3145543BTLEBRO
Solar/Wind Harmer
0.167
971623AH1-311 GEN
Solar/Wind Harmer
0.335
970917AG2-570 GEN
Solar/Wind Harmer
14.887
316313AB2-026
Solar/Wind Harmer
0.103
316258AE1-075 C
Solar/Wind Harmer
0.123
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.467
3141906WESTMOR
Solar/Wind Harmer
0.065
316478AD1-087 GEN
Solar/Wind Harmer
0.557
316486AD2-202 GEN
Solar/Wind Harmer
0.164
316131AB2-060 GEN
Solar/Wind Harmer
0.497
964241AG1-285 GEN
Solar/Wind Harmer
10.495
315785AD2-033 C
Solar/Wind Harmer
1.27
3152181CUNINGC
50/50
2.565
972193AH1-681 GEN
50/50
7.545
316312AB1-027
Solar/Wind Harmer
0.575
315976AC1-164 GENA
Solar/Wind Harmer
32.144
316169AC1-164_GENC
Solar/Wind Harmer
27.769
315975AC1-164 GENB
Solar/Wind Harmer
0.951
316314AB2-024 C
Solar/Wind Harmer
0.001
971167AH1-042 GEN
Solar/Wind Harmer
24.413
3142433PROV 92
Adder
0.534
3142433PROV 92
Adder
0.534
3143873LANEXA
Solar/Wind Harmer
0.165
316059AD1-063 C
Solar/Wind Harmer
0.002
3138283WHITEMARSH
Solar/Wind Harmer
0.062
970189AG2-124 GEN
Solar/Wind Harmer
7.953
315662AE1-191 GEN
Solar/Wind Harmer
0.009
315666AE1-190 GEN
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
1.424
3141873WAN 176
Solar/Wind Harmer
0.053
316369SG1_INVT
Solar/Wind Harmer
0.01
972265AH1-717 GEN
Adder
20.019
3151201GRAVEL4
Adder
18.766
3151191GRAVEL3
Adder
18.528
3151211GRAVEL5
Adder
18.528
3141913WHIT STONE
Solar/Wind Harmer
0.256
3138133OCRAN
Solar/Wind Harmer
0.076
971445AH1-216 GEN
Solar/Wind Harmer
17.851
971285AH1-108 GEN
Adder
1.911
3141783LANCAST
Solar/Wind Harmer
0.15
3141783LANCAST
Solar/Wind Harmer
0.1
3151081ELIZAR1
Adder
22.486
3151091ELIZAR2
Adder
22.095
3152611GOSPORTB
Adder
3.124
3152621GOSPORTC
Adder
2.651
3152601GOSPORTA
Adder
2.446
962981AG1-147 GEN
Solar/Wind Harmer
9.042
957871AF2-081 GEN
Solar/Wind Harmer
12.005
319010AE1-072 C
Solar/Wind Harmer
1.21
3146406KITTY HAWK
Solar/Wind Harmer
0.03
316305AF2-043 C
Solar/Wind Harmer
0.002
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.163
316311AC2-079 GEN
Solar/Wind Harmer
6.837
970327AG2-215 GEN
Solar/Wind Harmer
7.789
315835AF2-110_GEN
Solar/Wind Harmer
1.628
313526AB2-022
Solar/Wind Harmer
0.128
3146486SUNBURY
Solar/Wind Harmer
0.236
3146486SUNBURY
Solar/Wind Harmer
0.236
316321Z2-027
Solar/Wind Harmer
0.044
3146396TANGLEW
Solar/Wind Harmer
0.649
3145176PASQUOTANK
Solar/Wind Harmer
0.146
3143316POE
Solar/Wind Harmer
0.911
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.224
3130156CHOWAN
Solar/Wind Harmer
0.224
972189AH1-679 GEN
Adder
3.73
315816AE2-034 GEN
Solar/Wind Harmer
0.93
316233AE1-074 FULL
Solar/Wind Harmer
0.173
971281AH1-106 GEN
Solar/Wind Harmer
3.003
971283AH1-107 GEN
Solar/Wind Harmer
3.003
3141813NORNECK
Solar/Wind Harmer
0.215
3130546PLYMOUTH
Solar/Wind Harmer
0.211
315732AD1-074 GEN1
Solar/Wind Harmer
1.209
315733AD1-074 GEN2
Solar/Wind Harmer
1.209
315735AD1-075 GEN1
Solar/Wind Harmer
0.605
3146206CASHIE
Solar/Wind Harmer
0.207
970601AG2-382 GEN
Solar/Wind Harmer
7.721
965291AG1-394 GEN
Solar/Wind Harmer
0.911
3145893MURPHYS
Solar/Wind Harmer
0.548
3145893MURPHYS
Solar/Wind Harmer
0.203
316315AB2-025 C
Solar/Wind Harmer
0.164
315814AE2-033 C
Solar/Wind Harmer
16.008
3145513AHOSKIE
Solar/Wind Harmer
0.417
3145513AHOSKIE
Solar/Wind Harmer
0.199
3145683EARLEYS
Solar/Wind Harmer
0.397
3145683EARLEYS
Solar/Wind Harmer
0.198
3145683EARLEYS
Solar/Wind Harmer
0.198
3146043SEABORD
Solar/Wind Harmer
0.194
315607AA1-063A GEN
Solar/Wind Harmer
0.395
315652AC1-086 GEN
Solar/Wind Harmer
20.636
3146033SCOT NK
Solar/Wind Harmer
0.749
316087AB2-174 GEN
Solar/Wind Harmer
0.005
3137643SOCKMAN
Solar/Wind Harmer
0.742
3145796HORNRTN
Solar/Wind Harmer
0.591
3145796HORNRTN
Solar/Wind Harmer
0.074
316005AA1-067
Solar/Wind Harmer
0.194
3145746EVERETS
Solar/Wind Harmer
0.72
3145746EVERETS
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
3145453TOT5
Solar/Wind Harmer
0.24
3145603CNETO
Solar/Wind Harmer
0.16
972187AH1-678 GEN
Adder
4.882
970933AG2-581 GEN
Solar/Wind Harmer
13.585
961601AG1-000A GEN
Solar/Wind Harmer
2.983
316263AC1-034 GEN
Solar/Wind Harmer
6.369
970099AG2-077 GEN
Solar/Wind Harmer
17.402
939181AE1-148 GEN
Solar/Wind Harmer
7.706
313527AB2-043 GEN
Solar/Wind Harmer
0.002
970323AG2-213 GEN
Solar/Wind Harmer
6.645
971775AH1-396 GEN
Solar/Wind Harmer
0.249
316034AC1-036 C
Solar/Wind Harmer
0.011
971741AH1-377 GEN
Solar/Wind Harmer
15.41
970301AG2-198 GEN
Solar/Wind Harmer
6.555
958211AF2-115 GEN
Solar/Wind Harmer
1.842
963191AG1-168 GEN
Solar/Wind Harmer
0.614
3144293JTRSVLE
Adder
0.489
3144293JTRSVLE
Adder
0.411
3147133PAMPLIN
Solar/Wind Harmer
0.153
3147133PAMPLIN
Solar/Wind Harmer
0.122
962561AG1-105 GEN
Solar/Wind Harmer
7.312
964791AG1-342 GEN
Solar/Wind Harmer
2.904
3146843MT LREL
Solar/Wind Harmer
0.151
3146843MT LREL
Solar/Wind Harmer
0.151
3146776BUCKING
Solar/Wind Harmer
0.569
3146776BUCKING
Solar/Wind Harmer
0.046
316222AC1-221 GEN
Solar/Wind Harmer
0.567
315821AE2-092 GEN
Solar/Wind Harmer
0.008
971489AH1-241 GEN
Solar/Wind Harmer
7.112
942751AE2-291 GEN
Solar/Wind Harmer
6.853
316447AC1-158 HLD
Solar/Wind Helper
3.611
226929AD2-058 GEN
Solar/Wind Helper
0.096
315651AD1-115 GEN
Solar/Wind Helper
0.797
970257AG2-171 GEN
Solar/Wind Harmer
4.984
959311AF2-222 GEN
Solar/Wind Harmer
13.814
970909AG2-566 GEN
Solar/Wind Harmer
1.639
963181AG1-167 GEN
Solar/Wind Harmer
0.614
3144293JTRSVLE
Adder
0.489
3147133PAMPLIN
Solar/Wind Harmer
0.479
971193AH1-056 GEN
Solar/Wind Harmer
9.299
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.089
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
6.236
3146776BUCKING
Solar/Wind Harmer
0.051
3148013FISHERV
Solar/Wind Harmer
0.14
971683AH1-343 GEN
Solar/Wind Harmer
5.137
315616AA1-038_C
Solar/Wind Harmer
0.001
3151861LOWMORA
Adder
1.496
970737AG2-469 GEN
Solar/Wind Harmer
5.853
316283AC2-100 C
Solar/Wind Harmer
0.266
970221AG2-151 GEN
Solar/Wind Harmer
7.112
316044AC1-158 PL1
Solar/Wind Helper
1.64
316450AC1-158 RIC
Solar/Wind Helper
0.438
3141196NOKESVL
Solar/Wind Helper
1.029
227287AC2-120 GEN
Solar/Wind Helper
0.327
226910AB2-157 C
Solar/Wind Helper
0.013
316170AC1-121 GEN2
Solar/Wind Helper
0.36
970181AG2-120 GEN
Solar/Wind Harmer
2.254
957861AF2-080 GEN
Solar/Wind Harmer
7.61
941031AE2-094 GEN
Solar/Wind Harmer
32.353
944011AF1-069 GEN
Solar/Wind Harmer
10.571
316420AA1-050 GEN
Solar/Wind Harmer
0.006
970673AG2-436 GEN
Solar/Wind Harmer
37.059
970673AG2-436 GEN
Solar/Wind Harmer
24.706
3145573BETHELC
Solar/Wind Harmer
0.172
3145573BETHELC
Solar/Wind Harmer
0.172
971967AH1-528 GEN
Solar/Wind Harmer
27.582
970831AG2-522 GEN
Solar/Wind Harmer
7.305
316319Z2-044 C
Solar/Wind Harmer
0
970085AG2-068 GEN
Solar/Wind Harmer
8.909
970581AG2-369 GEN
Solar/Wind Harmer
7.662
316223AC1-118
Solar/Wind Harmer
0.117
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
2.618
3144303KENBRDG
Solar/Wind Harmer
0.124
970683AG2-441 GEN
Solar/Wind Harmer
10.305
970681AG2-440 GEN
Solar/Wind Harmer
8.244
946301AF1-294 GEN
Solar/Wind Harmer
3.029
961791AG1-021 GEN
Solar/Wind Harmer
1.473
315657AE1-056 GEN
Solar/Wind Harmer
5.267
316118AC1-105 GEN
Solar/Wind Harmer
0.384
3147173SINAI
Solar/Wind Harmer
0.146
3147243WELCO
Solar/Wind Harmer
0.091
970285AG2-188 GEN
Solar/Wind Harmer
11.379
971845AH1-439 GEN
Solar/Wind Harmer
6.479
3148133STUARTS
Solar/Wind Harmer
0.084
3148013FISHERV
Solar/Wind Harmer
0.081
3148463FAIRFLD
Solar/Wind Harmer
0.139
3151881LOWMORC
Adder
1.484
3151881LOWMORC
Adder
1.461
3151861LOWMORA
Adder
1.437
970865AG2-541 GEN
Solar/Wind Harmer
4.73
972205AH1-687 GEN
Adder
5.79
971447AH1-217 GEN
Solar/Wind Harmer
4.07
316123AC1-075 GEN
Solar/Wind Harmer
0.178
970165AG2-112 GEN
Solar/Wind Harmer
1.054
970163AG2-111 GEN
Solar/Wind Harmer
1.006
270494AE1-108_GEN
Solar/Wind Harmer
1.506
316164AC1-076 GEN
Solar/Wind Helper
1.291
316411AF1-147_GEN1
Solar/Wind Helper
0.798
316415AF1-147_GEN2
Solar/Wind Helper
0.798
3138216PACIFIC
Solar/Wind Helper
0.039
316023GEN1_S
Solar/Wind Harmer
0.432
316337AD2-073 GEN
Solar/Wind Harmer
0.166
316190AA2-174 GEN
Solar/Wind Harmer
0
316011AB1-132 GEN
Solar/Wind Harmer
3.411
962571AG1-106 GEN
Solar/Wind Harmer
2.669
960081AF2-299 GEN
Solar/Wind Harmer
1.79
3146293MARTNCO
Solar/Wind Harmer
0.173
3145783HORNRTN
Solar/Wind Harmer
0.185
3145796HORNRTN
Solar/Wind Harmer
0.609
3145796HORNRTN
Solar/Wind Harmer
0.185
316212AC1-099_GEN
Solar/Wind Harmer
0.945
3143226MDLTHAN
Solar/Wind Harmer
0.182
3145746EVERETS
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
971795AH1-408 GEN
Solar/Wind Harmer
12.042
3147043LAWRENC
Adder
1.61
316494AC1-189 GEN
Solar/Wind Harmer
0.596
315722AD1-056 GEN
Solar/Wind Harmer
1.11
961671AG1-007 GEN
Solar/Wind Harmer
0.026
3146083TARBORO
Solar/Wind Harmer
0.172
3145493TOT1
Solar/Wind Harmer
0.767
3146233WITAKRS
Solar/Wind Harmer
0.681
316129AC1-054 GEN
Solar/Wind Harmer
0.638
971065AG2-659 GEN
Solar/Wind Harmer
7.177
3145543BTLEBRO
Solar/Wind Harmer
0.167
3145543BTLEBRO
Solar/Wind Harmer
0.134
316359AB2-059 GEN
Solar/Wind Harmer
0.602
316049AB1-081 GEN
Solar/Wind Harmer
0.959
3142053HEARTS
Solar/Wind Harmer
0.295
970919AG2-571 GEN
Solar/Wind Harmer
5.955
970087AG2-069 GEN
Solar/Wind Harmer
13.364
3143336POWHATN
Solar/Wind Harmer
2.903
957481AF2-042 GEN
Solar/Wind Harmer
43.505
315693AD1-088 GEN
Solar/Wind Harmer
7.732
962491AG1-098 GEN
Solar/Wind Harmer
9.171
316336AC2-165 C
Solar/Wind Harmer
0.006
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970685AG2-442 GEN
Solar/Wind Harmer
11.542
315687AD1-152 GEN
Solar/Wind Harmer
0.005
963171AG1-166 GEN
Solar/Wind Harmer
0.819
971563AH1-280 GEN
Solar/Wind Harmer
1.637
3144293JTRSVLE
Adder
0.489
970401AG2-262 GEN
Solar/Wind Harmer
0.887
3146926FARMVIL
Solar/Wind Harmer
0.089
970937AG2-583 GEN
Solar/Wind Harmer
8.957
316003AC1-222 GEN
Solar/Wind Harmer
0.004
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.057
972003AH1-546 GEN
Solar/Wind Harmer
5.812
971377AH1-170 GEN
Solar/Wind Harmer
1.422
3147623JAMES R
Solar/Wind Harmer
0.309
315705AF1-075 GEN
Solar/Wind Harmer
4.935
972135AH1-637 GEN
Solar/Wind Harmer
1.026
970223AG2-152 GEN
Solar/Wind Harmer
7.945
3147123OTTER R
Solar/Wind Harmer
0.068
316045AC1-158 PL2
Solar/Wind Helper
5.251
316006AB2-029 C
Solar/Wind Helper
0.117
316254AC1-120 GEN1
Solar/Wind Helper
1.08
LAGNLTFEXP_LAGN->PJM
CLTF
9.82
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.055
TVALTFEXP_TVA->PJM
CLTF
4.995
NYPJM->LTFIMP_NY
CLTF
3.366
LGEELTFEXP_LGEE->PJM
CLTF
2.175
WECLTFEXP_WEC->PJM
CLTF
1.097
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.092
CBM West 1LTFEXP_CBM-W1->PJM
CBM
38.714
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.519
MECLTFEXP_MEC->PJM
CLTF
5.527
SIGELTFEXP_SIGE->PJM
CLTF
0.173
CPLELTFEXP_CPLE->PJM
CLTF
10.807
CBM West 2LTFEXP_CBM-W2->PJM
CBM
55.119

Details for 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:126.22 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5137.22
MW Contribution:7.39
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
14.825
970497AG2-320 GEN
50/50
26.932
3150401LDYSMT4
50/50
38.285
3150371LDYSMT1
50/50
36.994
315051AA1-145 CT1
50/50
2.076
3142416OLDCHRC
Solar/Wind Harmer
2.465
970293AG2-193 GEN
Solar/Wind Harmer
2.678
3143096IRON208
Adder
1.045
3143096IRON208
Adder
1.024
3150861SPRUNCD
Adder
1.148
316473AC1-191 GEN
Solar/Wind Harmer
0.839
3142946ENON
Solar/Wind Harmer
0.083
970133AG2-095 GEN
Solar/Wind Harmer
2.349
316382AG1-145 C
Solar/Wind Harmer
0.002
970129AG2-093 GEN
Solar/Wind Harmer
14.714
315778AD1-151 GEN
Solar/Wind Harmer
19.405
965281AG1-393 GEN
Solar/Wind Harmer
2.587
315839AE2-212 C
Solar/Wind Harmer
0.002
3142433PROV 92
Adder
0.469
3142433PROV 92
Adder
0.469
3150921YORKTN3
Adder
6.055
3144216WINCHST
Adder
0.908
961611AG1-000B GEN
Solar/Wind Harmer
6.42
3151221GRAVEL6
Adder
17.444
3151171GRAVELC
Adder
3.356
315773AC2-141 GEN
Solar/Wind Harmer
8.761
3145336SMITFLD
Solar/Wind Harmer
0.096
315813AE1-149 C
Solar/Wind Harmer
12.736
3144536CHRHLND
Solar/Wind Harmer
0.035
970659AG2-427 GEN
Solar/Wind Harmer
2.51
944581AF1-123 GEN
Solar/Wind Harmer
53.367
944601AF1-125 GEN
Solar/Wind Harmer
52.545
3151101ELIZAR3
Adder
22.008
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3144873MCLAUGH
Solar/Wind Harmer
0.006
3141766HARMONY
Solar/Wind Harmer
3.157
3141843SHACKLE
Adder
1.209
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
970661AG2-428 GEN
Solar/Wind Harmer
4.998
316280AD1-041 GEN
Solar/Wind Harmer
0.005
316156AD2-030 GEN
Solar/Wind Harmer
0.174
3141873WAN 176
Solar/Wind Harmer
4.175
3146456SLIGO L269
Solar/Wind Harmer
0.234
971153AH1-033 GEN
Solar/Wind Harmer
2.705
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.228
3146626S HERTFORD
Solar/Wind Harmer
0.227
962971AG1-146 GEN
Solar/Wind Harmer
3.63
3145273HOLLAND
Solar/Wind Harmer
0.17
970009AG2-005 GEN
Solar/Wind Harmer
1.68
3146376EDENTON
Solar/Wind Harmer
0.222
316404AE1-155 C
Solar/Wind Harmer
0.05
315614AA2-178 GEN
Solar/Wind Harmer
1.242
3150351NORNECKC2
Adder
2.198
971781AH1-399 GEN
Solar/Wind Harmer
0.285
971157AH1-035 GEN
Solar/Wind Harmer
2.559
315737AD1-076 GEN
Solar/Wind Harmer
2.735
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
316313AB2-026
Solar/Wind Harmer
0.134
316258AE1-075 C
Solar/Wind Harmer
0.16
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.201
970917AG2-570 GEN
Solar/Wind Harmer
18.693
3146206CASHIE
Solar/Wind Harmer
0.21
316365GEN2_N
Solar/Wind Harmer
0.471
3145893MURPHYS
Solar/Wind Harmer
0.35
3145893MURPHYS
Solar/Wind Harmer
0.209
957521AF2-046 GEN
Solar/Wind Harmer
15.533
961681AG1-008 GEN
Solar/Wind Harmer
15.533
3146173TUNIS
Solar/Wind Harmer
0.207
3156021HOLLOMANSOL
Solar/Wind Harmer
0.94
316463AE2-346 GEN
Solar/Wind Harmer
0.177
316140AB2-099
Solar/Wind Harmer
0.074
962331AG1-082 GEN
Solar/Wind Harmer
2.201
3146263WOODLND
Solar/Wind Harmer
0.204
3145963POPLR C
Solar/Wind Harmer
0.202
313506AB2-031 GEN
Solar/Wind Harmer
0.624
3142666NORTHAMPTON
Solar/Wind Harmer
0.202
316317KELFORD C
Solar/Wind Harmer
0.019
3145823KELFORD
Solar/Wind Harmer
0.201
3145796HORNRTN
Solar/Wind Harmer
0.792
3145796HORNRTN
Solar/Wind Harmer
0.198
3141906WESTMOR
Solar/Wind Harmer
0.079
3147043LAWRENC
Solar/Wind Harmer
0.118
316478AD1-087 GEN
Solar/Wind Harmer
0.676
316486AD2-202 GEN
Solar/Wind Harmer
0.198
316210AC1-098 GEN
Solar/Wind Harmer
1.795
3145933PARMELE
Solar/Wind Harmer
0.193
966801AG1-551 GEN
Solar/Wind Harmer
2.252
970737AG2-469 GEN
Solar/Wind Harmer
8.074
3145746EVERETS
Solar/Wind Harmer
0.189
3145746EVERETS
Solar/Wind Harmer
0.189
315724AD1-057 GEN
Solar/Wind Harmer
0.705
316327AA2-057 GEN
Solar/Wind Harmer
0.281
970909AG2-566 GEN
Solar/Wind Harmer
1.971
3146073TAR RVR
Solar/Wind Harmer
0.183
3146083TARBORO
Solar/Wind Harmer
0.183
3146233WITAKRS
Solar/Wind Harmer
0.919
3146233WITAKRS
Solar/Wind Harmer
0.124
3138543CONSLDL
Solar/Wind Harmer
0.12
3147666LOUISA
Solar/Wind Harmer
0.42
316131AB2-060 GEN
Solar/Wind Harmer
0.572
964241AG1-285 GEN
Solar/Wind Harmer
12.091
315785AD2-033 C
Solar/Wind Harmer
1.468
970257AG2-171 GEN
Solar/Wind Harmer
5.771
959311AF2-222 GEN
Solar/Wind Harmer
16.014
961601AG1-000A GEN
Solar/Wind Harmer
12.778
3145543BTLEBRO
Solar/Wind Harmer
0.179
3145543BTLEBRO
Solar/Wind Harmer
0.179
971623AH1-311 GEN
Solar/Wind Harmer
0.359
963181AG1-167 GEN
Solar/Wind Harmer
0.716
3144293JTRSVLE
Adder
0.57
3147133PAMPLIN
Solar/Wind Harmer
0.56
971193AH1-056 GEN
Solar/Wind Harmer
10.872
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.105
3146776BUCKING
Solar/Wind Harmer
0.06
972255AH1-712 GEN
Adder
85.454
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.086
971683AH1-343 GEN
Solar/Wind Harmer
5.663
316283AC2-100 C
Solar/Wind Harmer
0.294
970221AG2-151 GEN
Solar/Wind Harmer
7.9
3141316ARNOLDS
Adder
0.336
3150331BIRCHWDA
Adder
22.127
316044AC1-158 PL1
Solar/Wind Helper
2.207
316450AC1-158 RIC
Solar/Wind Helper
0.589
3141196NOKESVL
Solar/Wind Helper
1.25
316170AC1-121 GEN2
Solar/Wind Helper
0.431
3150391LDYSMT3
50/50
38.213
972195AH1-682 GEN
50/50
5.022
315673AE1-157 GEN
Solar/Wind Harmer
18.457
957411AF2-035 GEN
Solar/Wind Harmer
11.334
970317AG2-208 GEN
Solar/Wind Harmer
10.501
3142296MT RD221
Adder
0.82
3142366NRTHEST
Adder
0.825
3150691DARBY 3
Adder
18.133
3150701DARBY 4
Adder
18.091
3150681DARBY 2
Adder
18.07
3150671DARBY 1
Adder
18.049
316075AC2-137 C
Solar/Wind Harmer
0.069
3143526WINTERP
Solar/Wind Harmer
1.295
966871AG1-558 GEN
Solar/Wind Harmer
0.287
971223AH1-071 GEN
Solar/Wind Harmer
2.646
3142946ENON
Solar/Wind Harmer
0.025
944641AF1-129 GEN
Adder
116.855
316240AF1-291 C
Solar/Wind Harmer
0.002
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.272
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316036AC1-147 C
Solar/Wind Harmer
0.044
3150991CHESPKB
Adder
2.482
3150991CHESPKB
Adder
2.423
970657AG2-426 GEN
Solar/Wind Harmer
8.291
970657AG2-426 GEN
Solar/Wind Harmer
1.738
316316AC1-027 C
Solar/Wind Harmer
0.227
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.007
3145506HICKORY
Solar/Wind Harmer
0.942
3145506HICKORY
Solar/Wind Harmer
0.565
3145506HICKORY
Solar/Wind Harmer
0.141
316339AD2-160 GEN
Solar/Wind Harmer
0.381
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.131
3137176SLIGO L2192
Solar/Wind Harmer
0.931
3146456SLIGO L269
Solar/Wind Harmer
4.141
3130086AYDLETT
Solar/Wind Harmer
0.934
3146386ELIZ CT
Solar/Wind Harmer
0.231
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.228
3146516WINFALL
Solar/Wind Harmer
0.228
3146516WINFALL
Solar/Wind Harmer
0.228
3146626S HERTFORD
Solar/Wind Harmer
0.227
3146626S HERTFORD
Solar/Wind Harmer
0.227
3144356SAPONY
Solar/Wind Harmer
1.894
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
0.987
3146376EDENTON
Solar/Wind Harmer
0.987
958261AF2-120 GEN
Solar/Wind Harmer
7.345
972185AH1-677 GEN
Adder
12.364
972187AH1-678 GEN
Adder
6.203
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.271
3150341NORNECKC1
Adder
2.253
316468AD1-105 GEN
Solar/Wind Harmer
-0.071
970933AG2-581 GEN
Solar/Wind Harmer
17.147
316065AD1-022 GEN
Solar/Wind Harmer
9.721
3145893MURPHYS
Solar/Wind Harmer
1.401
3145893MURPHYS
Solar/Wind Harmer
0.376
3146173TUNIS
Solar/Wind Harmer
0.207
3146173TUNIS
Solar/Wind Harmer
0.207
316181AB2-040 GEN
Solar/Wind Harmer
0.293
3142666NORTHAMPTON
Solar/Wind Harmer
0.202
3142666NORTHAMPTON
Solar/Wind Harmer
0.202
3142666NORTHAMPTON
Solar/Wind Harmer
0.202
3142666NORTHAMPTON
Solar/Wind Harmer
0.121
970099AG2-077 GEN
Solar/Wind Harmer
21.434
316426AA2-053 GEN
Solar/Wind Harmer
0.677
3145593CAROLNA
Solar/Wind Harmer
0.199
3145593CAROLNA
Solar/Wind Harmer
0.199
966811AG1-552 GEN
Solar/Wind Harmer
2.162
3145593CAROLNA
Solar/Wind Harmer
0.248
3145783HORNRTN
Solar/Wind Harmer
3.524
3145783HORNRTN
Solar/Wind Harmer
2.819
3145783HORNRTN
Solar/Wind Harmer
0.881
3145783HORNRTN
Solar/Wind Harmer
0.352
3145796HORNRTN
Solar/Wind Harmer
0.594
3145933PARMELE
Solar/Wind Harmer
0.387
3145933PARMELE
Solar/Wind Harmer
0.193
316274AC1-208 GEN
Solar/Wind Harmer
0.996
971741AH1-377 GEN
Solar/Wind Harmer
18.605
970301AG2-198 GEN
Solar/Wind Harmer
7.883
939181AE1-148 GEN
Solar/Wind Harmer
8.803
3145493TOT1
Solar/Wind Harmer
0.424
3145453TOT5
Solar/Wind Harmer
0.255
3145603CNETO
Solar/Wind Harmer
0.17
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.695
971775AH1-396 GEN
Solar/Wind Harmer
0.289
961601AG1-000A GEN
Solar/Wind Harmer
3.194
316263AC1-034 GEN
Solar/Wind Harmer
6.824
958211AF2-115 GEN
Solar/Wind Harmer
2.148
963191AG1-168 GEN
Solar/Wind Harmer
0.716
3144293JTRSVLE
Adder
0.57
3144293JTRSVLE
Adder
0.48
3147133PAMPLIN
Solar/Wind Harmer
0.178
3147133PAMPLIN
Solar/Wind Harmer
0.143
962561AG1-105 GEN
Solar/Wind Harmer
8.357
964791AG1-342 GEN
Solar/Wind Harmer
3.316
3146843MT LREL
Solar/Wind Harmer
0.172
3146843MT LREL
Solar/Wind Harmer
0.172
3146776BUCKING
Solar/Wind Harmer
0.67
3146776BUCKING
Solar/Wind Harmer
0.054
316222AC1-221 GEN
Solar/Wind Harmer
0.627
971489AH1-241 GEN
Solar/Wind Harmer
7.9
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
6.989
316447AC1-158 HLD
Solar/Wind Helper
4.858
315651AD1-115 GEN
Solar/Wind Helper
0.961
3150411LDYSMT5
50/50
38.405
3150381LDYSMT2
50/50
36.755
972213AH1-691 GEN
50/50
6.217
972215AH1-692 GEN
50/50
6.217
963051AG1-154 GEN
50/50
4.783
972189AH1-679 GEN
50/50
4.654
316312AB1-027
Solar/Wind Harmer
0.455
316233AE1-074 FULL
Solar/Wind Harmer
0.199
971281AH1-106 GEN
Solar/Wind Harmer
3.456
971283AH1-107 GEN
Solar/Wind Harmer
3.456
971285AH1-108 GEN
Adder
1.878
315976AC1-164 GENA
Solar/Wind Harmer
25.718
316169AC1-164_GENC
Solar/Wind Harmer
22.218
315975AC1-164 GENB
Solar/Wind Harmer
0.761
316132AB2-190 GEN1
Solar/Wind Harmer
1.305
316369SG1_INVT
Solar/Wind Harmer
0.009
971167AH1-042 GEN
Solar/Wind Harmer
21.453
3142433PROV 92
Adder
0.469
3142433PROV 92
Adder
0.469
972265AH1-717 GEN
Adder
18.63
3151201GRAVEL4
Adder
17.465
3151191GRAVEL3
Adder
17.243
3151211GRAVEL5
Adder
17.243
971445AH1-216 GEN
Solar/Wind Harmer
16.824
3143873LANEXA
Solar/Wind Harmer
0.143
3143316POE
Solar/Wind Harmer
0.945
3138283WHITEMARSH
Solar/Wind Harmer
0.055
316314AB2-024 C
Solar/Wind Harmer
0.001
3151081ELIZAR1
Adder
21.73
3151091ELIZAR2
Adder
21.353
3152611GOSPORTB
Adder
3.018
3152621GOSPORTC
Adder
2.561
3152601GOSPORTA
Adder
2.363
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
7.011
315662AE1-191 GEN
Solar/Wind Harmer
0.008
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.047
957871AF2-081 GEN
Solar/Wind Harmer
11.676
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.161
316311AC2-079 GEN
Solar/Wind Harmer
6.724
319010AE1-072 C
Solar/Wind Harmer
1.178
3146406KITTY HAWK
Solar/Wind Harmer
0.029
316305AF2-043 C
Solar/Wind Harmer
0.002
315835AF2-110_GEN
Solar/Wind Harmer
1.595
3141913WHIT STONE
Solar/Wind Harmer
0.232
313526AB2-022
Solar/Wind Harmer
0.125
3138133OCRAN
Solar/Wind Harmer
0.069
3146486SUNBURY
Solar/Wind Harmer
0.231
3146486SUNBURY
Solar/Wind Harmer
0.231
316321Z2-027
Solar/Wind Harmer
0.043
3146396TANGLEW
Solar/Wind Harmer
0.635
3145176PASQUOTANK
Solar/Wind Harmer
0.143
3141783LANCAST
Solar/Wind Harmer
0.138
3141783LANCAST
Solar/Wind Harmer
0.092
962981AG1-147 GEN
Solar/Wind Harmer
8.47
316315AB2-025 C
Solar/Wind Harmer
0.183
941031AE2-094 GEN
Solar/Wind Harmer
41.622
944011AF1-069 GEN
Solar/Wind Harmer
13.599
315814AE2-033 C
Solar/Wind Harmer
17.851
970327AG2-215 GEN
Solar/Wind Harmer
7.386
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
47.408
970673AG2-436 GEN
Solar/Wind Harmer
31.605
3130156CHOWAN
Solar/Wind Harmer
0.222
3130156CHOWAN
Solar/Wind Harmer
0.222
971967AH1-528 GEN
Solar/Wind Harmer
35.12
315816AE2-034 GEN
Solar/Wind Harmer
0.932
3141813NORNECK
Solar/Wind Harmer
0.217
3130546PLYMOUTH
Solar/Wind Harmer
0.213
315732AD1-074 GEN1
Solar/Wind Harmer
1.221
315733AD1-074 GEN2
Solar/Wind Harmer
1.221
315735AD1-075 GEN1
Solar/Wind Harmer
0.611
965291AG1-394 GEN
Solar/Wind Harmer
0.939
3146206CASHIE
Solar/Wind Harmer
0.21
970601AG2-382 GEN
Solar/Wind Harmer
7.851
970085AG2-068 GEN
Solar/Wind Harmer
11.171
970581AG2-369 GEN
Solar/Wind Harmer
9.607
3145893MURPHYS
Solar/Wind Harmer
0.565
3145893MURPHYS
Solar/Wind Harmer
0.209
3145513AHOSKIE
Solar/Wind Harmer
0.431
3145513AHOSKIE
Solar/Wind Harmer
0.206
3145683EARLEYS
Solar/Wind Harmer
0.411
3145683EARLEYS
Solar/Wind Harmer
0.205
3145683EARLEYS
Solar/Wind Harmer
0.205
3146043SEABORD
Solar/Wind Harmer
0.205
315607AA1-063A GEN
Solar/Wind Harmer
0.417
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
22.128
3137643SOCKMAN
Solar/Wind Harmer
0.801
3145796HORNRTN
Solar/Wind Harmer
0.634
3145796HORNRTN
Solar/Wind Harmer
0.079
316223AC1-118
Solar/Wind Harmer
0.142
3146033SCOT NK
Solar/Wind Harmer
0.787
970831AG2-522 GEN
Solar/Wind Harmer
8.114
316005AA1-067
Solar/Wind Harmer
0.203
3145746EVERETS
Solar/Wind Harmer
0.753
3145746EVERETS
Solar/Wind Harmer
0.189
3145746EVERETS
Solar/Wind Harmer
0.189
3145746EVERETS
Solar/Wind Harmer
0.189
970181AG2-120 GEN
Solar/Wind Harmer
2.355
957861AF2-080 GEN
Solar/Wind Harmer
8.016
316420AA1-050 GEN
Solar/Wind Harmer
0.006
3145573BETHELC
Solar/Wind Harmer
0.183
3145573BETHELC
Solar/Wind Harmer
0.183
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
3.031
3144303KENBRDG
Solar/Wind Harmer
0.144
970683AG2-441 GEN
Solar/Wind Harmer
11.977
970681AG2-440 GEN
Solar/Wind Harmer
9.582
946301AF1-294 GEN
Solar/Wind Harmer
3.532
961791AG1-021 GEN
Solar/Wind Harmer
1.718
315657AE1-056 GEN
Solar/Wind Harmer
6.158
944491AF1-114 GEN
Solar/Wind Harmer
0.001
970285AG2-188 GEN
Solar/Wind Harmer
13.414
316118AC1-105 GEN
Solar/Wind Harmer
0.437
971845AH1-439 GEN
Solar/Wind Harmer
7.626
972193AH1-681 GEN
Adder
3.818
3147173SINAI
Solar/Wind Harmer
0.166
3147243WELCO
Solar/Wind Harmer
0.104
972205AH1-687 GEN
Adder
6.726
970865AG2-541 GEN
Solar/Wind Harmer
5.131
971447AH1-217 GEN
Solar/Wind Harmer
4.386
316123AC1-075 GEN
Solar/Wind Harmer
0.186
970165AG2-112 GEN
Solar/Wind Harmer
1.103
970163AG2-111 GEN
Solar/Wind Harmer
1.052
270494AE1-108_GEN
Solar/Wind Harmer
1.582
316164AC1-076 GEN
Solar/Wind Helper
1.947
316411AF1-147_GEN1
Solar/Wind Helper
0.8
316415AF1-147_GEN2
Solar/Wind Helper
0.8
3138216PACIFIC
Solar/Wind Helper
0.039
3152251N ANNA1
50/50
14.826
972197AH1-683 GEN
50/50
5.978
972219AH1-694 GEN
50/50
4.304
315052AA1-145 CT2
50/50
2.085
966881AG1-559 GEN
Solar/Wind Harmer
0.307
3142416OLDCHRC
Solar/Wind Harmer
0.661
3142416OLDCHRC
Solar/Wind Harmer
0.253
3143096IRON208
Adder
1.045
3143526WINTERP
Solar/Wind Harmer
1.295
3150851SPRUNCC
Adder
1.148
3142543TWELFTH
Solar/Wind Harmer
0.024
3143226MDLTHAN
Solar/Wind Harmer
0.248
944631AF1-128 GEN
Adder
117.965
316159AE1-175 C
Solar/Wind Harmer
0.21
970129AG2-093 GEN
Solar/Wind Harmer
6.924
316458AB2-190 GEN2
Solar/Wind Harmer
1.305
315671AE2-027_GEN
Solar/Wind Harmer
15.554
971069AG2-661 GEN
Solar/Wind Harmer
4.312
971647AH1-324 GEN
Solar/Wind Harmer
10.299
971317AH1-138 GEN
Solar/Wind Harmer
1.8
3142433PROV 92
Solar/Wind Harmer
0.964
3142433PROV 92
Adder
0.469
3142433PROV 92
Adder
0.469
3138126ROCKLANDING
Solar/Wind Harmer
0.111
961611AG1-000B GEN
Solar/Wind Harmer
12.625
3151171GRAVELC
Adder
2.552
316294AC1-161 GEN
Solar/Wind Harmer
4.156
3145336SMITFLD
Solar/Wind Harmer
0.955
970659AG2-427 GEN
Solar/Wind Harmer
11.475
944591AF1-124 GEN
Solar/Wind Harmer
53.557
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.959
316381AD1-082 GEN
Solar/Wind Harmer
0.247
3141766HARMONY
Solar/Wind Harmer
0.047
971777AH1-397 GEN
Solar/Wind Harmer
0.625
3141843SHACKLE
Adder
1.209
970661AG2-428 GEN
Solar/Wind Harmer
23.497
316072AD1-144
Solar/Wind Harmer
0.085
939411AE1-173 GEN
Solar/Wind Harmer
100.291
316388AE2-253 GEN
Solar/Wind Harmer
0.736
940641AE2-051 GEN
Solar/Wind Harmer
18.777
3146456SLIGO L269
Solar/Wind Harmer
0.234
316246AF1-032 C
Solar/Wind Harmer
0.105
316093AE2-104_GEN
Solar/Wind Harmer
3.91
3138133OCRAN
Solar/Wind Harmer
0.139
3146516WINFALL
Solar/Wind Harmer
0.74
3146516WINFALL
Solar/Wind Harmer
0.228
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
962861AG1-135 GEN
Solar/Wind Harmer
7.133
3130156CHOWAN
Solar/Wind Harmer
0.222
3141726DUNNSVL
Solar/Wind Harmer
0.878
3145663CRESWEL
Solar/Wind Harmer
0.608
971163AH1-040 GEN
Solar/Wind Harmer
17.369
3150351NORNECKC2
Adder
2.162
3143336POWHATN
Solar/Wind Harmer
3.766
970919AG2-571 GEN
Solar/Wind Harmer
7.477
3146206CASHIE
Solar/Wind Harmer
0.21
971547AH1-271 GEN
Solar/Wind Harmer
4.486
316023GEN1_S
Solar/Wind Harmer
0.471
970087AG2-069 GEN
Solar/Wind Harmer
16.757
3145893MURPHYS
Solar/Wind Harmer
0.837
3145893MURPHYS
Solar/Wind Harmer
0.931
316337AD2-073 GEN
Solar/Wind Harmer
0.181
3146173TUNIS
Solar/Wind Harmer
0.207
3145683EARLEYS
Solar/Wind Harmer
0.205
960081AF2-299 GEN
Solar/Wind Harmer
1.959
3146263WOODLND
Solar/Wind Harmer
0.204
316336AC2-165 C
Solar/Wind Harmer
0.008
3145963POPLR C
Solar/Wind Harmer
0.202
316011AB1-132 GEN
Solar/Wind Harmer
3.658
962571AG1-106 GEN
Solar/Wind Harmer
2.862
3145823KELFORD
Solar/Wind Harmer
0.201
957481AF2-042 GEN
Solar/Wind Harmer
53.584
316174AB2-169 GEN
Solar/Wind Harmer
0.005
316190AA2-174 GEN
Solar/Wind Harmer
0
971795AH1-408 GEN
Solar/Wind Harmer
13.299
3145783HORNRTN
Solar/Wind Harmer
0.198
3145796HORNRTN
Solar/Wind Harmer
0.653
3145796HORNRTN
Solar/Wind Harmer
0.198
3147043LAWRENC
Adder
1.785
315693AD1-088 GEN
Solar/Wind Harmer
9.451
962491AG1-098 GEN
Solar/Wind Harmer
11.2
316212AC1-099_GEN
Solar/Wind Harmer
1.001
3146293MARTNCO
Solar/Wind Harmer
0.179
3145746EVERETS
Solar/Wind Harmer
0.189
3145746EVERETS
Solar/Wind Harmer
0.189
316129AC1-054 GEN
Solar/Wind Harmer
0.711
971065AG2-659 GEN
Solar/Wind Harmer
8.033
315722AD1-056 GEN
Solar/Wind Harmer
1.189
316494AC1-189 GEN
Solar/Wind Harmer
0.628
972135AH1-637 GEN
Solar/Wind Harmer
1.564
961671AG1-007 GEN
Solar/Wind Harmer
0.028
3146083TARBORO
Solar/Wind Harmer
0.183
3145493TOT1
Solar/Wind Harmer
0.814
3146233WITAKRS
Solar/Wind Harmer
0.728
315687AD1-152 GEN
Solar/Wind Harmer
0.006
3147666LOUISA
Solar/Wind Harmer
0.73
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970685AG2-442 GEN
Solar/Wind Harmer
13.415
3145543BTLEBRO
Solar/Wind Harmer
0.179
3145543BTLEBRO
Solar/Wind Harmer
0.144
316359AB2-059 GEN
Solar/Wind Harmer
0.645
316049AB1-081 GEN
Solar/Wind Harmer
1.028
3142053HEARTS
Solar/Wind Harmer
0.316
963171AG1-166 GEN
Solar/Wind Harmer
0.955
971563AH1-280 GEN
Solar/Wind Harmer
1.909
3144293JTRSVLE
Adder
0.57
970937AG2-583 GEN
Solar/Wind Harmer
10.92
316192AB2-158 GEN
Solar/Wind Harmer
1.002
3146926FARMVIL
Solar/Wind Harmer
0.105
970401AG2-262 GEN
Solar/Wind Harmer
1.013
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.067
972277AH1-723 GEN
Adder
99.579
316003AC1-222 GEN
Solar/Wind Harmer
0.004
972003AH1-546 GEN
Solar/Wind Harmer
6.768
971377AH1-170 GEN
Solar/Wind Harmer
1.58
3147623JAMES R
Solar/Wind Harmer
0.343
316045AC1-158 PL2
Solar/Wind Helper
7.066
316006AB2-029 C
Solar/Wind Helper
0.145
316254AC1-120 GEN1
Solar/Wind Helper
1.294
LAGNLTFEXP_LAGN->PJM
CLTF
8.214
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.425
TVALTFEXP_TVA->PJM
CLTF
4.163
NYPJM->LTFIMP_NY
CLTF
3.205
LGEELTFEXP_LGEE->PJM
CLTF
1.386
WECLTFEXP_WEC->PJM
CLTF
0.672
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.47
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.182
MECLTFEXP_MEC->PJM
CLTF
3.753
SIGELTFEXP_SIGE->PJM
CLTF
0.114
CPLELTFEXP_CPLE->PJM
CLTF
11.58
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.571

Details for 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.64 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5073.15
MW Contribution:7.14
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
13.89
970497AG2-320 GEN
50/50
26.316
3150401LDYSMT4
50/50
37.387
3150371LDYSMT1
50/50
36.126
315051AA1-145 CT1
50/50
2.017
316044AC1-158 PL1
Solar/Wind Harmer
1.37
316450AC1-158 RIC
Solar/Wind Harmer
0.365
3142416OLDCHRC
Solar/Wind Harmer
2.389
970293AG2-193 GEN
Solar/Wind Harmer
2.592
3143096IRON208
Adder
1.01
3143096IRON208
Adder
0.989
316473AC1-191 GEN
Solar/Wind Harmer
0.814
3150861SPRUNCD
Adder
1.107
3142946ENON
Solar/Wind Harmer
0.08
970133AG2-095 GEN
Solar/Wind Harmer
2.267
316382AG1-145 C
Solar/Wind Harmer
0.002
970129AG2-093 GEN
Solar/Wind Harmer
14.202
315778AD1-151 GEN
Solar/Wind Harmer
18.726
965281AG1-393 GEN
Solar/Wind Harmer
2.495
315839AE2-212 C
Solar/Wind Harmer
0.002
3142433PROV 92
Adder
0.453
3142433PROV 92
Adder
0.453
3150921YORKTN3
Adder
5.845
3144216WINCHST
Adder
0.877
961611AG1-000B GEN
Solar/Wind Harmer
6.193
3151221GRAVEL6
Adder
16.824
3151171GRAVELC
Adder
3.237
315773AC2-141 GEN
Solar/Wind Harmer
8.441
3145336SMITFLD
Solar/Wind Harmer
0.092
315813AE1-149 C
Solar/Wind Harmer
12.273
3144536CHRHLND
Solar/Wind Harmer
0.034
3141766HARMONY
Solar/Wind Harmer
3.053
3141843SHACKLE
Adder
1.169
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
970659AG2-427 GEN
Solar/Wind Harmer
2.419
3151101ELIZAR3
Adder
21.202
944581AF1-123 GEN
Solar/Wind Harmer
51.405
944601AF1-125 GEN
Solar/Wind Harmer
50.613
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3144873MCLAUGH
Solar/Wind Harmer
0.006
316280AD1-041 GEN
Solar/Wind Harmer
0.005
970661AG2-428 GEN
Solar/Wind Harmer
4.815
316156AD2-030 GEN
Solar/Wind Harmer
0.168
3141873WAN 176
Solar/Wind Harmer
4.037
3146456SLIGO L269
Solar/Wind Harmer
0.225
971153AH1-033 GEN
Solar/Wind Harmer
2.606
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.22
962971AG1-146 GEN
Solar/Wind Harmer
3.51
3146626S HERTFORD
Solar/Wind Harmer
0.218
3145273HOLLAND
Solar/Wind Harmer
0.163
970009AG2-005 GEN
Solar/Wind Harmer
1.625
316404AE1-155 C
Solar/Wind Harmer
0.048
3146376EDENTON
Solar/Wind Harmer
0.214
971781AH1-399 GEN
Solar/Wind Harmer
0.276
3150351NORNECKC2
Adder
2.127
315614AA2-178 GEN
Solar/Wind Harmer
1.196
971157AH1-035 GEN
Solar/Wind Harmer
2.463
315737AD1-076 GEN
Solar/Wind Harmer
2.632
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
316313AB2-026
Solar/Wind Harmer
0.129
316258AE1-075 C
Solar/Wind Harmer
0.154
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
3.087
3146206CASHIE
Solar/Wind Harmer
0.202
970917AG2-570 GEN
Solar/Wind Harmer
17.936
316365GEN2_N
Solar/Wind Harmer
0.453
3145893MURPHYS
Solar/Wind Harmer
0.337
3145893MURPHYS
Solar/Wind Harmer
0.201
957521AF2-046 GEN
Solar/Wind Harmer
14.949
961681AG1-008 GEN
Solar/Wind Harmer
14.949
3146173TUNIS
Solar/Wind Harmer
0.199
3156021HOLLOMANSOL
Solar/Wind Harmer
0.905
316463AE2-346 GEN
Solar/Wind Harmer
0.17
316140AB2-099
Solar/Wind Harmer
0.071
962331AG1-082 GEN
Solar/Wind Harmer
2.118
3146263WOODLND
Solar/Wind Harmer
0.196
3145963POPLR C
Solar/Wind Harmer
0.194
313506AB2-031 GEN
Solar/Wind Harmer
0.6
3142666NORTHAMPTON
Solar/Wind Harmer
0.194
316317KELFORD C
Solar/Wind Harmer
0.019
3145823KELFORD
Solar/Wind Harmer
0.193
3141906WESTMOR
Solar/Wind Harmer
0.077
3145796HORNRTN
Solar/Wind Harmer
0.762
3145796HORNRTN
Solar/Wind Harmer
0.19
3147043LAWRENC
Solar/Wind Harmer
0.114
316210AC1-098 GEN
Solar/Wind Harmer
1.726
316478AD1-087 GEN
Solar/Wind Harmer
0.649
316486AD2-202 GEN
Solar/Wind Harmer
0.191
3145933PARMELE
Solar/Wind Harmer
0.186
966801AG1-551 GEN
Solar/Wind Harmer
2.166
970737AG2-469 GEN
Solar/Wind Harmer
7.816
3145746EVERETS
Solar/Wind Harmer
0.182
3145746EVERETS
Solar/Wind Harmer
0.182
315724AD1-057 GEN
Solar/Wind Harmer
0.678
3147666LOUISA
Solar/Wind Harmer
0.412
316327AA2-057 GEN
Solar/Wind Harmer
0.27
970909AG2-566 GEN
Solar/Wind Harmer
1.901
3146073TAR RVR
Solar/Wind Harmer
0.176
3146083TARBORO
Solar/Wind Harmer
0.176
3146233WITAKRS
Solar/Wind Harmer
0.883
3146233WITAKRS
Solar/Wind Harmer
0.12
3138543CONSLDL
Solar/Wind Harmer
0.116
316131AB2-060 GEN
Solar/Wind Harmer
0.55
964241AG1-285 GEN
Solar/Wind Harmer
11.64
315785AD2-033 C
Solar/Wind Harmer
1.415
970257AG2-171 GEN
Solar/Wind Harmer
5.56
959311AF2-222 GEN
Solar/Wind Harmer
15.432
961601AG1-000A GEN
Solar/Wind Harmer
12.283
3145543BTLEBRO
Solar/Wind Harmer
0.172
3145543BTLEBRO
Solar/Wind Harmer
0.172
963181AG1-167 GEN
Solar/Wind Harmer
0.691
3144293JTRSVLE
Adder
0.55
971623AH1-311 GEN
Solar/Wind Harmer
0.345
3147133PAMPLIN
Solar/Wind Harmer
0.541
971193AH1-056 GEN
Solar/Wind Harmer
10.489
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.102
972255AH1-712 GEN
Adder
83.356
3146776BUCKING
Solar/Wind Harmer
0.058
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
6.812
971683AH1-343 GEN
Solar/Wind Harmer
5.445
3152251N ANNA1
50/50
13.891
972197AH1-683 GEN
50/50
5.838
972219AH1-694 GEN
50/50
4.203
315052AA1-145 CT2
50/50
2.026
316045AC1-158 PL2
Solar/Wind Harmer
4.381
966881AG1-559 GEN
Solar/Wind Harmer
0.299
3142416OLDCHRC
Solar/Wind Harmer
0.641
3142416OLDCHRC
Solar/Wind Harmer
0.245
3143096IRON208
Adder
1.01
3150851SPRUNCC
Adder
1.107
3142543TWELFTH
Solar/Wind Harmer
0.023
3143526WINTERP
Solar/Wind Harmer
1.246
944631AF1-128 GEN
Adder
114.018
3143226MDLTHAN
Solar/Wind Harmer
0.238
316159AE1-175 C
Solar/Wind Harmer
0.203
970129AG2-093 GEN
Solar/Wind Harmer
6.683
316458AB2-190 GEN2
Solar/Wind Harmer
1.26
315671AE2-027_GEN
Solar/Wind Harmer
15.005
971069AG2-661 GEN
Solar/Wind Harmer
4.161
3142433PROV 92
Solar/Wind Harmer
0.932
3142433PROV 92
Adder
0.453
3142433PROV 92
Adder
0.453
971647AH1-324 GEN
Solar/Wind Harmer
9.937
971317AH1-138 GEN
Solar/Wind Harmer
1.739
3138126ROCKLANDING
Solar/Wind Harmer
0.107
961611AG1-000B GEN
Solar/Wind Harmer
12.179
3151171GRAVELC
Adder
2.462
316294AC1-161 GEN
Solar/Wind Harmer
4.004
3145336SMITFLD
Solar/Wind Harmer
0.921
3141766HARMONY
Solar/Wind Harmer
0.046
971777AH1-397 GEN
Solar/Wind Harmer
0.604
3141843SHACKLE
Adder
1.169
970659AG2-427 GEN
Solar/Wind Harmer
11.057
944591AF1-124 GEN
Solar/Wind Harmer
51.588
316381AD1-082 GEN
Solar/Wind Harmer
0.238
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.851
970661AG2-428 GEN
Solar/Wind Harmer
22.639
316072AD1-144
Solar/Wind Harmer
0.082
316388AE2-253 GEN
Solar/Wind Harmer
0.708
939411AE1-173 GEN
Solar/Wind Harmer
96.357
3146456SLIGO L269
Solar/Wind Harmer
0.225
940641AE2-051 GEN
Solar/Wind Harmer
18.025
316246AF1-032 C
Solar/Wind Harmer
0.101
316093AE2-104_GEN
Solar/Wind Harmer
3.766
3138133OCRAN
Solar/Wind Harmer
0.134
3146516WINFALL
Solar/Wind Harmer
0.713
3146516WINFALL
Solar/Wind Harmer
0.22
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
962861AG1-135 GEN
Solar/Wind Harmer
6.899
3130156CHOWAN
Solar/Wind Harmer
0.214
3141726DUNNSVL
Solar/Wind Harmer
0.85
3150351NORNECKC2
Adder
2.092
3145663CRESWEL
Solar/Wind Harmer
0.585
971163AH1-040 GEN
Solar/Wind Harmer
16.721
3143336POWHATN
Solar/Wind Harmer
3.631
3146206CASHIE
Solar/Wind Harmer
0.202
971547AH1-271 GEN
Solar/Wind Harmer
4.318
970919AG2-571 GEN
Solar/Wind Harmer
7.174
316023GEN1_S
Solar/Wind Harmer
0.453
3145893MURPHYS
Solar/Wind Harmer
0.805
3145893MURPHYS
Solar/Wind Harmer
0.896
316337AD2-073 GEN
Solar/Wind Harmer
0.175
970087AG2-069 GEN
Solar/Wind Harmer
16.078
3146173TUNIS
Solar/Wind Harmer
0.199
3145683EARLEYS
Solar/Wind Harmer
0.197
960081AF2-299 GEN
Solar/Wind Harmer
1.885
3146263WOODLND
Solar/Wind Harmer
0.196
316336AC2-165 C
Solar/Wind Harmer
0.008
3145963POPLR C
Solar/Wind Harmer
0.194
316011AB1-132 GEN
Solar/Wind Harmer
3.518
962571AG1-106 GEN
Solar/Wind Harmer
2.753
3145823KELFORD
Solar/Wind Harmer
0.193
957481AF2-042 GEN
Solar/Wind Harmer
51.474
316174AB2-169 GEN
Solar/Wind Harmer
0.005
316190AA2-174 GEN
Solar/Wind Harmer
0
971795AH1-408 GEN
Solar/Wind Harmer
12.793
3145783HORNRTN
Solar/Wind Harmer
0.19
3145796HORNRTN
Solar/Wind Harmer
0.628
3145796HORNRTN
Solar/Wind Harmer
0.19
3147043LAWRENC
Adder
1.718
315693AD1-088 GEN
Solar/Wind Harmer
9.086
962491AG1-098 GEN
Solar/Wind Harmer
10.769
316212AC1-099_GEN
Solar/Wind Harmer
0.963
3146293MARTNCO
Solar/Wind Harmer
0.172
3145746EVERETS
Solar/Wind Harmer
0.182
3145746EVERETS
Solar/Wind Harmer
0.182
316129AC1-054 GEN
Solar/Wind Harmer
0.684
971065AG2-659 GEN
Solar/Wind Harmer
7.725
315722AD1-056 GEN
Solar/Wind Harmer
1.144
3147666LOUISA
Solar/Wind Harmer
0.717
316494AC1-189 GEN
Solar/Wind Harmer
0.604
972135AH1-637 GEN
Solar/Wind Harmer
1.514
961671AG1-007 GEN
Solar/Wind Harmer
0.027
3146083TARBORO
Solar/Wind Harmer
0.176
3145493TOT1
Solar/Wind Harmer
0.783
3146233WITAKRS
Solar/Wind Harmer
0.7
315687AD1-152 GEN
Solar/Wind Harmer
0.006
316237AB2-079_GEN
Solar/Wind Harmer
0.001
316192AB2-158 GEN
Solar/Wind Harmer
0.987
970685AG2-442 GEN
Solar/Wind Harmer
12.932
3145543BTLEBRO
Solar/Wind Harmer
0.172
3145543BTLEBRO
Solar/Wind Harmer
0.138
963171AG1-166 GEN
Solar/Wind Harmer
0.921
971563AH1-280 GEN
Solar/Wind Harmer
1.842
3144293JTRSVLE
Adder
0.55
316359AB2-059 GEN
Solar/Wind Harmer
0.62
316049AB1-081 GEN
Solar/Wind Harmer
0.988
3142053HEARTS
Solar/Wind Harmer
0.304
970937AG2-583 GEN
Solar/Wind Harmer
10.585
3146926FARMVIL
Solar/Wind Harmer
0.102
970401AG2-262 GEN
Solar/Wind Harmer
0.974
972277AH1-723 GEN
Adder
97.135
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.065
972003AH1-546 GEN
Solar/Wind Harmer
6.584
316003AC1-222 GEN
Solar/Wind Harmer
0.004
971377AH1-170 GEN
Solar/Wind Harmer
1.539
3147623JAMES R
Solar/Wind Harmer
0.334
316006AB2-029 C
Solar/Wind Helper
0.12
316283AC2-100 C
Solar/Wind Harmer
0.283
970221AG2-151 GEN
Solar/Wind Harmer
7.696
3141316ARNOLDS
Adder
0.326
3150331BIRCHWDA
Adder
21.467
3141196NOKESVL
Solar/Wind Helper
1.224
3150411LDYSMT5
50/50
37.503
3150381LDYSMT2
50/50
35.892
972213AH1-691 GEN
50/50
6.072
972215AH1-692 GEN
50/50
6.072
963051AG1-154 GEN
50/50
4.67
972189AH1-679 GEN
50/50
4.522
316312AB1-027
Solar/Wind Harmer
0.441
971285AH1-108 GEN
Adder
1.812
315976AC1-164 GENA
Solar/Wind Harmer
24.889
316169AC1-164_GENC
Solar/Wind Harmer
21.501
315975AC1-164 GENB
Solar/Wind Harmer
0.736
316233AE1-074 FULL
Solar/Wind Harmer
0.192
971281AH1-106 GEN
Solar/Wind Harmer
3.326
971283AH1-107 GEN
Solar/Wind Harmer
3.326
316132AB2-190 GEN1
Solar/Wind Harmer
1.26
971167AH1-042 GEN
Solar/Wind Harmer
20.74
316369SG1_INVT
Solar/Wind Harmer
0.009
3142433PROV 92
Adder
0.453
3142433PROV 92
Adder
0.453
972265AH1-717 GEN
Adder
17.968
3151201GRAVEL4
Adder
16.844
3151191GRAVEL3
Adder
16.63
3151211GRAVEL5
Adder
16.63
3143873LANEXA
Solar/Wind Harmer
0.139
971445AH1-216 GEN
Solar/Wind Harmer
16.22
316314AB2-024 C
Solar/Wind Harmer
0.001
3138283WHITEMARSH
Solar/Wind Harmer
0.053
3143316POE
Solar/Wind Harmer
0.91
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.779
3151081ELIZAR1
Adder
20.934
3151091ELIZAR2
Adder
20.57
3152611GOSPORTB
Adder
2.907
3152621GOSPORTC
Adder
2.467
3152601GOSPORTA
Adder
2.276
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.045
957871AF2-081 GEN
Solar/Wind Harmer
11.247
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.155
316311AC2-079 GEN
Solar/Wind Harmer
6.478
319010AE1-072 C
Solar/Wind Harmer
1.135
3146406KITTY HAWK
Solar/Wind Harmer
0.028
316305AF2-043 C
Solar/Wind Harmer
0.002
3141913WHIT STONE
Solar/Wind Harmer
0.224
315835AF2-110_GEN
Solar/Wind Harmer
1.537
3138133OCRAN
Solar/Wind Harmer
0.067
313526AB2-022
Solar/Wind Harmer
0.121
3146486SUNBURY
Solar/Wind Harmer
0.222
3146486SUNBURY
Solar/Wind Harmer
0.222
3141783LANCAST
Solar/Wind Harmer
0.133
3141783LANCAST
Solar/Wind Harmer
0.089
316321Z2-027
Solar/Wind Harmer
0.041
3146396TANGLEW
Solar/Wind Harmer
0.612
3145176PASQUOTANK
Solar/Wind Harmer
0.138
962981AG1-147 GEN
Solar/Wind Harmer
8.191
316315AB2-025 C
Solar/Wind Harmer
0.176
970327AG2-215 GEN
Solar/Wind Harmer
7.143
315814AE2-033 C
Solar/Wind Harmer
17.164
941031AE2-094 GEN
Solar/Wind Harmer
39.927
944011AF1-069 GEN
Solar/Wind Harmer
13.046
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.214
3130156CHOWAN
Solar/Wind Harmer
0.214
970673AG2-436 GEN
Solar/Wind Harmer
45.48
970673AG2-436 GEN
Solar/Wind Harmer
30.32
971967AH1-528 GEN
Solar/Wind Harmer
33.699
3141813NORNECK
Solar/Wind Harmer
0.21
315816AE2-034 GEN
Solar/Wind Harmer
0.897
3130546PLYMOUTH
Solar/Wind Harmer
0.205
315732AD1-074 GEN1
Solar/Wind Harmer
1.176
315733AD1-074 GEN2
Solar/Wind Harmer
1.176
315735AD1-075 GEN1
Solar/Wind Harmer
0.588
965291AG1-394 GEN
Solar/Wind Harmer
0.904
3146206CASHIE
Solar/Wind Harmer
0.202
970601AG2-382 GEN
Solar/Wind Harmer
7.556
3145893MURPHYS
Solar/Wind Harmer
0.544
3145893MURPHYS
Solar/Wind Harmer
0.201
970085AG2-068 GEN
Solar/Wind Harmer
10.719
970581AG2-369 GEN
Solar/Wind Harmer
9.218
3145513AHOSKIE
Solar/Wind Harmer
0.415
3145513AHOSKIE
Solar/Wind Harmer
0.198
3145683EARLEYS
Solar/Wind Harmer
0.395
3145683EARLEYS
Solar/Wind Harmer
0.197
3145683EARLEYS
Solar/Wind Harmer
0.197
3146043SEABORD
Solar/Wind Harmer
0.197
315607AA1-063A GEN
Solar/Wind Harmer
0.401
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
21.282
3137643SOCKMAN
Solar/Wind Harmer
0.77
316223AC1-118
Solar/Wind Harmer
0.138
3145796HORNRTN
Solar/Wind Harmer
0.609
3145796HORNRTN
Solar/Wind Harmer
0.076
3146033SCOT NK
Solar/Wind Harmer
0.757
970831AG2-522 GEN
Solar/Wind Harmer
7.803
316005AA1-067
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.724
3145746EVERETS
Solar/Wind Harmer
0.182
3145746EVERETS
Solar/Wind Harmer
0.182
3145746EVERETS
Solar/Wind Harmer
0.182
970181AG2-120 GEN
Solar/Wind Harmer
2.265
957861AF2-080 GEN
Solar/Wind Harmer
7.708
316420AA1-050 GEN
Solar/Wind Harmer
0.006
3145573BETHELC
Solar/Wind Harmer
0.176
3145573BETHELC
Solar/Wind Harmer
0.176
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
2.92
3144303KENBRDG
Solar/Wind Harmer
0.139
970683AG2-441 GEN
Solar/Wind Harmer
11.546
970681AG2-440 GEN
Solar/Wind Harmer
9.237
946301AF1-294 GEN
Solar/Wind Harmer
3.407
961791AG1-021 GEN
Solar/Wind Harmer
1.657
315657AE1-056 GEN
Solar/Wind Harmer
5.941
944491AF1-114 GEN
Solar/Wind Harmer
0.001
970285AG2-188 GEN
Solar/Wind Harmer
12.999
971845AH1-439 GEN
Solar/Wind Harmer
7.393
972193AH1-681 GEN
Adder
3.724
316118AC1-105 GEN
Solar/Wind Harmer
0.42
3147173SINAI
Solar/Wind Harmer
0.16
3147243WELCO
Solar/Wind Harmer
0.1
972205AH1-687 GEN
Adder
6.548
970865AG2-541 GEN
Solar/Wind Harmer
4.934
971447AH1-217 GEN
Solar/Wind Harmer
4.275
316123AC1-075 GEN
Solar/Wind Harmer
0.179
970165AG2-112 GEN
Solar/Wind Harmer
1.061
970163AG2-111 GEN
Solar/Wind Harmer
1.012
270494AE1-108_GEN
Solar/Wind Harmer
1.539
316411AF1-147_GEN1
Solar/Wind Helper
0.785
316415AF1-147_GEN2
Solar/Wind Helper
0.785
3138216PACIFIC
Solar/Wind Helper
0.038
3150391LDYSMT3
50/50
37.317
972195AH1-682 GEN
50/50
4.904
316447AC1-158 HLD
Solar/Wind Harmer
3.012
315673AE1-157 GEN
Solar/Wind Harmer
17.997
957411AF2-035 GEN
Solar/Wind Harmer
11.043
970317AG2-208 GEN
Solar/Wind Harmer
10.231
3142296MT RD221
Adder
0.795
3142366NRTHEST
Adder
0.798
3150691DARBY 3
Adder
17.546
3150701DARBY 4
Adder
17.506
3150681DARBY 2
Adder
17.485
3150671DARBY 1
Adder
17.465
316075AC2-137 C
Solar/Wind Harmer
0.066
966871AG1-558 GEN
Solar/Wind Harmer
0.278
3143526WINTERP
Solar/Wind Harmer
1.246
3142946ENON
Solar/Wind Harmer
0.024
971223AH1-071 GEN
Solar/Wind Harmer
2.54
944641AF1-129 GEN
Adder
112.782
316240AF1-291 C
Solar/Wind Harmer
0.002
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.263
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316036AC1-147 C
Solar/Wind Harmer
0.042
3150991CHESPKB
Adder
2.391
3150991CHESPKB
Adder
2.334
970657AG2-426 GEN
Solar/Wind Harmer
7.988
970657AG2-426 GEN
Solar/Wind Harmer
1.675
316316AC1-027 C
Solar/Wind Harmer
0.219
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.006
3145506HICKORY
Solar/Wind Harmer
0.907
3145506HICKORY
Solar/Wind Harmer
0.544
3145506HICKORY
Solar/Wind Harmer
0.136
316339AD2-160 GEN
Solar/Wind Harmer
0.367
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.126
3137176SLIGO L2192
Solar/Wind Harmer
0.897
3146456SLIGO L269
Solar/Wind Harmer
3.989
3130086AYDLETT
Solar/Wind Harmer
0.9
3146386ELIZ CT
Solar/Wind Harmer
0.223
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.22
3146516WINFALL
Solar/Wind Harmer
0.22
3146516WINFALL
Solar/Wind Harmer
0.22
3146626S HERTFORD
Solar/Wind Harmer
0.218
3146626S HERTFORD
Solar/Wind Harmer
0.218
3144356SAPONY
Solar/Wind Harmer
1.822
315742AE1-103 GEN
Solar/Wind Harmer
0.002
958261AF2-120 GEN
Solar/Wind Harmer
7.105
3146376EDENTON
Solar/Wind Harmer
0.951
3146376EDENTON
Solar/Wind Harmer
0.951
972185AH1-677 GEN
Adder
11.862
316468AD1-105 GEN
Solar/Wind Harmer
-0.068
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.197
3150341NORNECKC1
Adder
2.18
972187AH1-678 GEN
Adder
5.952
970933AG2-581 GEN
Solar/Wind Harmer
16.459
316065AD1-022 GEN
Solar/Wind Harmer
9.356
3145893MURPHYS
Solar/Wind Harmer
1.348
3145893MURPHYS
Solar/Wind Harmer
0.362
3146173TUNIS
Solar/Wind Harmer
0.199
3146173TUNIS
Solar/Wind Harmer
0.199
316181AB2-040 GEN
Solar/Wind Harmer
0.282
3142666NORTHAMPTON
Solar/Wind Harmer
0.194
3142666NORTHAMPTON
Solar/Wind Harmer
0.194
3142666NORTHAMPTON
Solar/Wind Harmer
0.194
3142666NORTHAMPTON
Solar/Wind Harmer
0.116
970099AG2-077 GEN
Solar/Wind Harmer
20.59
316426AA2-053 GEN
Solar/Wind Harmer
0.651
3145593CAROLNA
Solar/Wind Harmer
0.192
3145593CAROLNA
Solar/Wind Harmer
0.192
966811AG1-552 GEN
Solar/Wind Harmer
2.08
3145593CAROLNA
Solar/Wind Harmer
0.239
3145783HORNRTN
Solar/Wind Harmer
3.389
3145783HORNRTN
Solar/Wind Harmer
2.711
3145783HORNRTN
Solar/Wind Harmer
0.847
3145783HORNRTN
Solar/Wind Harmer
0.339
3145796HORNRTN
Solar/Wind Harmer
0.571
3145933PARMELE
Solar/Wind Harmer
0.372
3145933PARMELE
Solar/Wind Harmer
0.186
316274AC1-208 GEN
Solar/Wind Harmer
0.958
971741AH1-377 GEN
Solar/Wind Harmer
17.929
970301AG2-198 GEN
Solar/Wind Harmer
7.603
939181AE1-148 GEN
Solar/Wind Harmer
8.466
3145493TOT1
Solar/Wind Harmer
0.408
3145453TOT5
Solar/Wind Harmer
0.245
3145603CNETO
Solar/Wind Harmer
0.163
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.414
971775AH1-396 GEN
Solar/Wind Harmer
0.278
961601AG1-000A GEN
Solar/Wind Harmer
3.071
958211AF2-115 GEN
Solar/Wind Harmer
2.072
963191AG1-168 GEN
Solar/Wind Harmer
0.691
3144293JTRSVLE
Adder
0.55
3144293JTRSVLE
Adder
0.463
316263AC1-034 GEN
Solar/Wind Harmer
6.56
3147133PAMPLIN
Solar/Wind Harmer
0.172
3147133PAMPLIN
Solar/Wind Harmer
0.138
962561AG1-105 GEN
Solar/Wind Harmer
8.039
964791AG1-342 GEN
Solar/Wind Harmer
3.189
3146843MT LREL
Solar/Wind Harmer
0.166
3146843MT LREL
Solar/Wind Harmer
0.166
3146776BUCKING
Solar/Wind Harmer
0.649
3146776BUCKING
Solar/Wind Harmer
0.053
316222AC1-221 GEN
Solar/Wind Harmer
0.603
971489AH1-241 GEN
Solar/Wind Harmer
7.696
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
6.723
LAGNLTFEXP_LAGN->PJM
CLTF
7.83
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.391
TVALTFEXP_TVA->PJM
CLTF
3.97
NYPJM->LTFIMP_NY
CLTF
3.157
LGEELTFEXP_LGEE->PJM
CLTF
1.303
WECLTFEXP_WEC->PJM
CLTF
0.629
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.913
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.507
MECLTFEXP_MEC->PJM
CLTF
3.537
SIGELTFEXP_SIGE->PJM
CLTF
0.108
CPLELTFEXP_CPLE->PJM
CLTF
11.118
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.426

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.67 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4208.1
MW Contribution:5.25
Bus #Bus NameTypeMW Contribution
970497AG2-320 GEN
50/50
20.809
3150401LDYSMT4
50/50
28.767
3150371LDYSMT1
50/50
27.797
315051AA1-145 CT1
50/50
1.582
971645AH1-323 GEN
50/50
17.655
3142416OLDCHRC
Solar/Wind Harmer
1.87
970293AG2-193 GEN
Solar/Wind Harmer
2.014
3143096IRON208
Adder
0.779
3143096IRON208
Adder
0.764
316473AC1-191 GEN
Solar/Wind Harmer
0.628
3142946ENON
Solar/Wind Harmer
0.062
3150861SPRUNCD
Adder
0.847
970133AG2-095 GEN
Solar/Wind Harmer
1.744
316382AG1-145 C
Solar/Wind Harmer
0.001
970129AG2-093 GEN
Solar/Wind Harmer
10.911
315778AD1-151 GEN
Solar/Wind Harmer
14.378
965281AG1-393 GEN
Solar/Wind Harmer
1.909
315839AE2-212 C
Solar/Wind Harmer
0.001
3150921YORKTN3
Adder
4.486
3144216WINCHST
Adder
0.673
961611AG1-000B GEN
Solar/Wind Harmer
4.749
3142433PROV 92
Adder
0.346
3142433PROV 92
Adder
0.346
3151221GRAVEL6
Adder
12.894
3151171GRAVELC
Adder
2.481
315773AC2-141 GEN
Solar/Wind Harmer
6.451
3145336SMITFLD
Solar/Wind Harmer
0.071
315813AE1-149 C
Solar/Wind Harmer
9.37
3144536CHRHLND
Solar/Wind Harmer
0.026
970659AG2-427 GEN
Solar/Wind Harmer
1.847
3151101ELIZAR3
Adder
16.197
316083AB2-161 GEN
Solar/Wind Harmer
0.002
3144873MCLAUGH
Solar/Wind Harmer
0.004
944581AF1-123 GEN
Solar/Wind Harmer
39.252
944601AF1-125 GEN
Solar/Wind Harmer
38.647
970661AG2-428 GEN
Solar/Wind Harmer
3.678
3141766HARMONY
Solar/Wind Harmer
2.312
3141843SHACKLE
Adder
0.885
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.004
3146456SLIGO L269
Solar/Wind Harmer
0.172
971153AH1-033 GEN
Solar/Wind Harmer
1.991
316156AD2-030 GEN
Solar/Wind Harmer
0.127
3141873WAN 176
Solar/Wind Harmer
3.045
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.168
3146626S HERTFORD
Solar/Wind Harmer
0.167
3145273HOLLAND
Solar/Wind Harmer
0.125
3146376EDENTON
Solar/Wind Harmer
0.164
962971AG1-146 GEN
Solar/Wind Harmer
2.595
315614AA2-178 GEN
Solar/Wind Harmer
0.918
970009AG2-005 GEN
Solar/Wind Harmer
1.196
971157AH1-035 GEN
Solar/Wind Harmer
1.892
315737AD1-076 GEN
Solar/Wind Harmer
2.022
316404AE1-155 C
Solar/Wind Harmer
0.035
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
316313AB2-026
Solar/Wind Harmer
0.098
316258AE1-075 C
Solar/Wind Harmer
0.118
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.362
3146206CASHIE
Solar/Wind Harmer
0.155
3145893MURPHYS
Solar/Wind Harmer
0.259
3145893MURPHYS
Solar/Wind Harmer
0.155
957521AF2-046 GEN
Solar/Wind Harmer
11.485
961681AG1-008 GEN
Solar/Wind Harmer
11.485
316365GEN2_N
Solar/Wind Harmer
0.346
3146173TUNIS
Solar/Wind Harmer
0.153
3156021HOLLOMANSOL
Solar/Wind Harmer
0.696
316463AE2-346 GEN
Solar/Wind Harmer
0.131
316140AB2-099
Solar/Wind Harmer
0.055
962331AG1-082 GEN
Solar/Wind Harmer
1.628
970917AG2-570 GEN
Solar/Wind Harmer
13.535
3150351NORNECKC2
Adder
1.529
3146263WOODLND
Solar/Wind Harmer
0.151
971781AH1-399 GEN
Solar/Wind Harmer
0.197
3145963POPLR C
Solar/Wind Harmer
0.15
3142666NORTHAMPTON
Solar/Wind Harmer
0.149
313506AB2-031 GEN
Solar/Wind Harmer
0.461
316317KELFORD C
Solar/Wind Harmer
0.014
3145823KELFORD
Solar/Wind Harmer
0.149
3145796HORNRTN
Solar/Wind Harmer
0.586
3145796HORNRTN
Solar/Wind Harmer
0.146
3147043LAWRENC
Solar/Wind Harmer
0.088
3145933PARMELE
Solar/Wind Harmer
0.144
966801AG1-551 GEN
Solar/Wind Harmer
1.675
316210AC1-098 GEN
Solar/Wind Harmer
1.333
972255AH1-712 GEN
Adder
72.909
316478AD1-087 GEN
Solar/Wind Harmer
0.497
316486AD2-202 GEN
Solar/Wind Harmer
0.146
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
315724AD1-057 GEN
Solar/Wind Harmer
0.524
316327AA2-057 GEN
Solar/Wind Harmer
0.209
970909AG2-566 GEN
Solar/Wind Harmer
1.479
3146073TAR RVR
Solar/Wind Harmer
0.137
3146083TARBORO
Solar/Wind Harmer
0.137
3146233WITAKRS
Solar/Wind Harmer
0.685
3146233WITAKRS
Solar/Wind Harmer
0.093
3138543CONSLDL
Solar/Wind Harmer
0.09
316131AB2-060 GEN
Solar/Wind Harmer
0.427
964241AG1-285 GEN
Solar/Wind Harmer
9.049
315785AD2-033 C
Solar/Wind Harmer
1.102
970257AG2-171 GEN
Solar/Wind Harmer
4.334
959311AF2-222 GEN
Solar/Wind Harmer
12.033
963181AG1-167 GEN
Solar/Wind Harmer
0.54
3144293JTRSVLE
Adder
0.43
3147133PAMPLIN
Solar/Wind Harmer
0.423
971193AH1-056 GEN
Solar/Wind Harmer
8.213
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
961601AG1-000A GEN
Solar/Wind Harmer
9.544
3145543BTLEBRO
Solar/Wind Harmer
0.134
3145543BTLEBRO
Solar/Wind Harmer
0.134
971623AH1-311 GEN
Solar/Wind Harmer
0.268
3146926FARMVIL
Solar/Wind Harmer
0.08
3147666LOUISA
Solar/Wind Harmer
0.299
3146776BUCKING
Solar/Wind Harmer
0.047
3141906WESTMOR
Solar/Wind Harmer
0.052
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.333
970737AG2-469 GEN
Solar/Wind Harmer
5.097
970221AG2-151 GEN
Solar/Wind Harmer
6.355
971683AH1-343 GEN
Solar/Wind Harmer
4.317
316283AC2-100 C
Solar/Wind Harmer
0.224
227287AC2-120 GEN
Solar/Wind Helper
0.387
226910AB2-157 C
Solar/Wind Helper
0.015
3150391LDYSMT3
50/50
28.713
972195AH1-682 GEN
50/50
3.773
3142296MT RD221
50/50
0.663
3142366NRTHEST
50/50
0.658
315673AE1-157 GEN
Solar/Wind Harmer
13.925
957411AF2-035 GEN
Solar/Wind Harmer
8.572
970317AG2-208 GEN
Solar/Wind Harmer
7.941
3150691DARBY 3
Adder
13.639
3150701DARBY 4
Adder
13.607
3150681DARBY 2
Adder
13.591
3150671DARBY 1
Adder
13.575
316075AC2-137 C
Solar/Wind Harmer
0.052
966871AG1-558 GEN
Solar/Wind Harmer
0.215
3142946ENON
Solar/Wind Harmer
0.018
944641AF1-129 GEN
Adder
86.641
316240AF1-291 C
Solar/Wind Harmer
0.001
3143526WINTERP
Solar/Wind Harmer
0.94
316033AB2-134 GEN
Solar/Wind Harmer
0.011
315697AD1-025 GEN
Solar/Wind Harmer
0.202
971223AH1-071 GEN
Solar/Wind Harmer
1.89
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.032
3150991CHESPKB
Adder
1.827
3150991CHESPKB
Adder
1.783
970657AG2-426 GEN
Solar/Wind Harmer
6.101
970657AG2-426 GEN
Solar/Wind Harmer
1.279
316316AC1-027 C
Solar/Wind Harmer
0.167
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.005
3145506HICKORY
Solar/Wind Harmer
0.693
3145506HICKORY
Solar/Wind Harmer
0.416
3145506HICKORY
Solar/Wind Harmer
0.104
316339AD2-160 GEN
Solar/Wind Harmer
0.28
316018AA1-139 ULT2
Solar/Wind Harmer
0.004
316017AA1-139 ULT1
Solar/Wind Harmer
0.096
3137176SLIGO L2192
Solar/Wind Harmer
0.686
3146456SLIGO L269
Solar/Wind Harmer
3.048
3130086AYDLETT
Solar/Wind Harmer
0.688
3146386ELIZ CT
Solar/Wind Harmer
0.17
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.168
3146516WINFALL
Solar/Wind Harmer
0.168
3146516WINFALL
Solar/Wind Harmer
0.168
3146626S HERTFORD
Solar/Wind Harmer
0.167
3146626S HERTFORD
Solar/Wind Harmer
0.167
3144356SAPONY
Solar/Wind Harmer
1.381
315742AE1-103 GEN
Solar/Wind Harmer
0.002
3146376EDENTON
Solar/Wind Harmer
0.728
3146376EDENTON
Solar/Wind Harmer
0.728
972185AH1-677 GEN
Adder
8.902
972187AH1-678 GEN
Adder
4.473
958261AF2-120 GEN
Solar/Wind Harmer
5.185
316065AD1-022 GEN
Solar/Wind Harmer
7.188
970933AG2-581 GEN
Solar/Wind Harmer
12.41
3145893MURPHYS
Solar/Wind Harmer
1.035
3145893MURPHYS
Solar/Wind Harmer
0.278
3146173TUNIS
Solar/Wind Harmer
0.153
3146173TUNIS
Solar/Wind Harmer
0.153
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.579
3150341NORNECKC1
Adder
1.567
316468AD1-105 GEN
Solar/Wind Harmer
-0.049
3142666NORTHAMPTON
Solar/Wind Harmer
0.149
3142666NORTHAMPTON
Solar/Wind Harmer
0.149
3142666NORTHAMPTON
Solar/Wind Harmer
0.149
3142666NORTHAMPTON
Solar/Wind Harmer
0.09
316181AB2-040 GEN
Solar/Wind Harmer
0.216
316426AA2-053 GEN
Solar/Wind Harmer
0.501
3145593CAROLNA
Solar/Wind Harmer
0.147
3145593CAROLNA
Solar/Wind Harmer
0.147
966811AG1-552 GEN
Solar/Wind Harmer
1.6
3145593CAROLNA
Solar/Wind Harmer
0.184
970099AG2-077 GEN
Solar/Wind Harmer
15.68
3145783HORNRTN
Solar/Wind Harmer
2.61
3145783HORNRTN
Solar/Wind Harmer
2.088
3145783HORNRTN
Solar/Wind Harmer
0.652
3145783HORNRTN
Solar/Wind Harmer
0.261
3145796HORNRTN
Solar/Wind Harmer
0.44
3145933PARMELE
Solar/Wind Harmer
0.288
3145933PARMELE
Solar/Wind Harmer
0.144
316274AC1-208 GEN
Solar/Wind Harmer
0.74
971741AH1-377 GEN
Solar/Wind Harmer
13.893
970301AG2-198 GEN
Solar/Wind Harmer
5.915
3145493TOT1
Solar/Wind Harmer
0.317
3145453TOT5
Solar/Wind Harmer
0.19
3145603CNETO
Solar/Wind Harmer
0.127
939181AE1-148 GEN
Solar/Wind Harmer
6.556
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.01
970323AG2-213 GEN
Solar/Wind Harmer
5.778
971775AH1-396 GEN
Solar/Wind Harmer
0.217
958211AF2-115 GEN
Solar/Wind Harmer
1.62
963191AG1-168 GEN
Solar/Wind Harmer
0.54
3144293JTRSVLE
Adder
0.43
3144293JTRSVLE
Adder
0.362
3147133PAMPLIN
Solar/Wind Harmer
0.135
3147133PAMPLIN
Solar/Wind Harmer
0.108
961601AG1-000A GEN
Solar/Wind Harmer
2.386
316263AC1-034 GEN
Solar/Wind Harmer
5.098
962561AG1-105 GEN
Solar/Wind Harmer
6.266
3146776BUCKING
Solar/Wind Harmer
0.519
3150411LDYSMT5
50/50
28.857
3150381LDYSMT2
50/50
27.617
972213AH1-691 GEN
50/50
4.672
972215AH1-692 GEN
50/50
4.672
963051AG1-154 GEN
50/50
3.594
972189AH1-679 GEN
50/50
3.546
316312AB1-027
Solar/Wind Harmer
0.345
315976AC1-164 GENA
Solar/Wind Harmer
19.303
316169AC1-164_GENC
Solar/Wind Harmer
16.676
315975AC1-164 GENB
Solar/Wind Harmer
0.571
971285AH1-108 GEN
Adder
1.386
316233AE1-074 FULL
Solar/Wind Harmer
0.145
971281AH1-106 GEN
Solar/Wind Harmer
2.508
971283AH1-107 GEN
Solar/Wind Harmer
2.508
316132AB2-190 GEN1
Solar/Wind Harmer
0.968
316369SG1_INVT
Solar/Wind Harmer
0.007
971167AH1-042 GEN
Solar/Wind Harmer
15.837
3142433PROV 92
Adder
0.346
3142433PROV 92
Adder
0.346
972265AH1-717 GEN
Adder
13.77
3151201GRAVEL4
Adder
12.909
3151191GRAVEL3
Adder
12.745
3151211GRAVEL5
Adder
12.745
971445AH1-216 GEN
Solar/Wind Harmer
12.417
3143873LANEXA
Solar/Wind Harmer
0.105
3138283WHITEMARSH
Solar/Wind Harmer
0.041
3143316POE
Solar/Wind Harmer
0.692
316314AB2-024 C
Solar/Wind Harmer
0.001
3151081ELIZAR1
Adder
15.992
3151091ELIZAR2
Adder
15.714
3152611GOSPORTB
Adder
2.221
3152621GOSPORTC
Adder
1.885
3152601GOSPORTA
Adder
1.739
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
5.131
957871AF2-081 GEN
Solar/Wind Harmer
8.594
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.118
316311AC2-079 GEN
Solar/Wind Harmer
4.949
315662AE1-191 GEN
Solar/Wind Harmer
0.006
315666AE1-190 GEN
Solar/Wind Harmer
0.001
319010AE1-072 C
Solar/Wind Harmer
0.867
3146406KITTY HAWK
Solar/Wind Harmer
0.021
316305AF2-043 C
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.034
315835AF2-110_GEN
Solar/Wind Harmer
1.175
313526AB2-022
Solar/Wind Harmer
0.092
3146486SUNBURY
Solar/Wind Harmer
0.17
3146486SUNBURY
Solar/Wind Harmer
0.17
316321Z2-027
Solar/Wind Harmer
0.032
3146396TANGLEW
Solar/Wind Harmer
0.468
3145176PASQUOTANK
Solar/Wind Harmer
0.105
3141913WHIT STONE
Solar/Wind Harmer
0.168
3138133OCRAN
Solar/Wind Harmer
0.05
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3141783LANCAST
Solar/Wind Harmer
0.099
3141783LANCAST
Solar/Wind Harmer
0.066
316315AB2-025 C
Solar/Wind Harmer
0.133
315814AE2-033 C
Solar/Wind Harmer
13.015
3130156CHOWAN
Solar/Wind Harmer
0.164
3130156CHOWAN
Solar/Wind Harmer
0.164
941031AE2-094 GEN
Solar/Wind Harmer
29.871
944011AF1-069 GEN
Solar/Wind Harmer
9.76
962981AG1-147 GEN
Solar/Wind Harmer
6.055
315816AE2-034 GEN
Solar/Wind Harmer
0.688
970327AG2-215 GEN
Solar/Wind Harmer
5.255
970673AG2-436 GEN
Solar/Wind Harmer
34.096
970673AG2-436 GEN
Solar/Wind Harmer
22.731
971967AH1-528 GEN
Solar/Wind Harmer
25.316
3130546PLYMOUTH
Solar/Wind Harmer
0.158
315732AD1-074 GEN1
Solar/Wind Harmer
0.903
315733AD1-074 GEN2
Solar/Wind Harmer
0.903
315735AD1-075 GEN1
Solar/Wind Harmer
0.452
965291AG1-394 GEN
Solar/Wind Harmer
0.694
3146206CASHIE
Solar/Wind Harmer
0.155
970601AG2-382 GEN
Solar/Wind Harmer
5.807
3145893MURPHYS
Solar/Wind Harmer
0.418
3145893MURPHYS
Solar/Wind Harmer
0.155
3145513AHOSKIE
Solar/Wind Harmer
0.319
3145513AHOSKIE
Solar/Wind Harmer
0.153
3145683EARLEYS
Solar/Wind Harmer
0.304
3145683EARLEYS
Solar/Wind Harmer
0.152
3145683EARLEYS
Solar/Wind Harmer
0.152
970085AG2-068 GEN
Solar/Wind Harmer
8.093
970581AG2-369 GEN
Solar/Wind Harmer
6.96
3146043SEABORD
Solar/Wind Harmer
0.151
315607AA1-063A GEN
Solar/Wind Harmer
0.308
3141813NORNECK
Solar/Wind Harmer
0.151
316087AB2-174 GEN
Solar/Wind Harmer
0.004
315652AC1-086 GEN
Solar/Wind Harmer
16.356
3137643SOCKMAN
Solar/Wind Harmer
0.592
3145796HORNRTN
Solar/Wind Harmer
0.469
3145796HORNRTN
Solar/Wind Harmer
0.059
3146033SCOT NK
Solar/Wind Harmer
0.584
972193AH1-681 GEN
Adder
3.258
970831AG2-522 GEN
Solar/Wind Harmer
6.025
316005AA1-067
Solar/Wind Harmer
0.151
3145746EVERETS
Solar/Wind Harmer
0.561
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
970181AG2-120 GEN
Solar/Wind Harmer
1.754
957861AF2-080 GEN
Solar/Wind Harmer
5.976
316420AA1-050 GEN
Solar/Wind Harmer
0.005
3145573BETHELC
Solar/Wind Harmer
0.137
3145573BETHELC
Solar/Wind Harmer
0.137
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
2.276
3144303KENBRDG
Solar/Wind Harmer
0.108
970683AG2-441 GEN
Solar/Wind Harmer
9.015
970681AG2-440 GEN
Solar/Wind Harmer
7.212
946301AF1-294 GEN
Solar/Wind Harmer
2.664
961791AG1-021 GEN
Solar/Wind Harmer
1.296
315657AE1-056 GEN
Solar/Wind Harmer
4.652
970285AG2-188 GEN
Solar/Wind Harmer
10.359
971845AH1-439 GEN
Solar/Wind Harmer
5.906
316223AC1-118
Solar/Wind Harmer
0.093
316118AC1-105 GEN
Solar/Wind Harmer
0.328
3147173SINAI
Solar/Wind Harmer
0.125
3147243WELCO
Solar/Wind Harmer
0.078
972205AH1-687 GEN
Adder
5.337
971447AH1-217 GEN
Solar/Wind Harmer
3.558
970865AG2-541 GEN
Solar/Wind Harmer
3.939
972197AH1-683 GEN
50/50
4.492
972219AH1-694 GEN
50/50
3.234
315052AA1-145 CT2
50/50
1.589
966881AG1-559 GEN
Solar/Wind Harmer
0.232
3142416OLDCHRC
Solar/Wind Harmer
0.502
3142416OLDCHRC
Solar/Wind Harmer
0.192
3143096IRON208
Adder
0.779
3142543TWELFTH
Solar/Wind Harmer
0.018
944631AF1-128 GEN
Adder
88.024
3150851SPRUNCC
Adder
0.847
316159AE1-175 C
Solar/Wind Harmer
0.157
3143526WINTERP
Solar/Wind Harmer
0.94
970129AG2-093 GEN
Solar/Wind Harmer
5.135
316458AB2-190 GEN2
Solar/Wind Harmer
0.968
971069AG2-661 GEN
Solar/Wind Harmer
3.195
315671AE2-027_GEN
Solar/Wind Harmer
11.489
971647AH1-324 GEN
Solar/Wind Harmer
7.623
971317AH1-138 GEN
Solar/Wind Harmer
1.333
3138126ROCKLANDING
Solar/Wind Harmer
0.082
961611AG1-000B GEN
Solar/Wind Harmer
9.339
3142433PROV 92
Solar/Wind Harmer
0.711
3142433PROV 92
Adder
0.346
3142433PROV 92
Adder
0.346
3151171GRAVELC
Adder
1.887
3143226MDLTHAN
Solar/Wind Harmer
0.177
316294AC1-161 GEN
Solar/Wind Harmer
3.06
3145336SMITFLD
Solar/Wind Harmer
0.705
970659AG2-427 GEN
Solar/Wind Harmer
8.444
316375AC2-012 GEN
Solar/Wind Harmer
0.004
3150981CHESPKA
Adder
2.178
316381AD1-082 GEN
Solar/Wind Harmer
0.182
944591AF1-124 GEN
Solar/Wind Harmer
39.391
970661AG2-428 GEN
Solar/Wind Harmer
17.291
3141766HARMONY
Solar/Wind Harmer
0.035
316072AD1-144
Solar/Wind Harmer
0.063
971777AH1-397 GEN
Solar/Wind Harmer
0.457
3141843SHACKLE
Adder
0.885
316388AE2-253 GEN
Solar/Wind Harmer
0.541
3146456SLIGO L269
Solar/Wind Harmer
0.172
316246AF1-032 C
Solar/Wind Harmer
0.078
316093AE2-104_GEN
Solar/Wind Harmer
2.878
939411AE1-173 GEN
Solar/Wind Harmer
72.518
940641AE2-051 GEN
Solar/Wind Harmer
13.497
3146516WINFALL
Solar/Wind Harmer
0.545
3146516WINFALL
Solar/Wind Harmer
0.168
3138133OCRAN
Solar/Wind Harmer
0.1
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.164
3145663CRESWEL
Solar/Wind Harmer
0.449
971163AH1-040 GEN
Solar/Wind Harmer
12.829
962861AG1-135 GEN
Solar/Wind Harmer
5.046
3143336POWHATN
Solar/Wind Harmer
2.778
3146206CASHIE
Solar/Wind Harmer
0.155
971547AH1-271 GEN
Solar/Wind Harmer
3.318
3145893MURPHYS
Solar/Wind Harmer
0.619
3145893MURPHYS
Solar/Wind Harmer
0.688
316023GEN1_S
Solar/Wind Harmer
0.346
3141726DUNNSVL
Solar/Wind Harmer
0.616
3146173TUNIS
Solar/Wind Harmer
0.153
970919AG2-571 GEN
Solar/Wind Harmer
5.414
3145683EARLEYS
Solar/Wind Harmer
0.152
970087AG2-069 GEN
Solar/Wind Harmer
12.139
3150351NORNECKC2
Adder
1.504
316336AC2-165 C
Solar/Wind Harmer
0.006
3146263WOODLND
Solar/Wind Harmer
0.151
960081AF2-299 GEN
Solar/Wind Harmer
1.445
3145963POPLR C
Solar/Wind Harmer
0.15
3145823KELFORD
Solar/Wind Harmer
0.149
316011AB1-132 GEN
Solar/Wind Harmer
2.703
962571AG1-106 GEN
Solar/Wind Harmer
2.116
316174AB2-169 GEN
Solar/Wind Harmer
0.004
316190AA2-174 GEN
Solar/Wind Harmer
0
971795AH1-408 GEN
Solar/Wind Harmer
9.834
957481AF2-042 GEN
Solar/Wind Harmer
39.2
3145783HORNRTN
Solar/Wind Harmer
0.147
3145796HORNRTN
Solar/Wind Harmer
0.484
3145796HORNRTN
Solar/Wind Harmer
0.146
3147043LAWRENC
Adder
1.322
315693AD1-088 GEN
Solar/Wind Harmer
6.952
962491AG1-098 GEN
Solar/Wind Harmer
8.247
3146293MARTNCO
Solar/Wind Harmer
0.133
316212AC1-099_GEN
Solar/Wind Harmer
0.743
972277AH1-723 GEN
Adder
84.961
3145746EVERETS
Solar/Wind Harmer
0.141
3145746EVERETS
Solar/Wind Harmer
0.141
316337AD2-073 GEN
Solar/Wind Harmer
0.122
316129AC1-054 GEN
Solar/Wind Harmer
0.528
971065AG2-659 GEN
Solar/Wind Harmer
5.969
315722AD1-056 GEN
Solar/Wind Harmer
0.885
316494AC1-189 GEN
Solar/Wind Harmer
0.468
970937AG2-583 GEN
Solar/Wind Harmer
8.39
961671AG1-007 GEN
Solar/Wind Harmer
0.021
3146083TARBORO
Solar/Wind Harmer
0.137
3145493TOT1
Solar/Wind Harmer
0.607
3146233WITAKRS
Solar/Wind Harmer
0.543
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.004
970685AG2-442 GEN
Solar/Wind Harmer
10.097
963171AG1-166 GEN
Solar/Wind Harmer
0.72
971563AH1-280 GEN
Solar/Wind Harmer
1.44
3144293JTRSVLE
Adder
0.43
3145543BTLEBRO
Solar/Wind Harmer
0.134
3145543BTLEBRO
Solar/Wind Harmer
0.107
316359AB2-059 GEN
Solar/Wind Harmer
0.482
316049AB1-081 GEN
Solar/Wind Harmer
0.768
3142053HEARTS
Solar/Wind Harmer
0.236
3146926FARMVIL
Solar/Wind Harmer
0.08
3147666LOUISA
Solar/Wind Harmer
0.52
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.052
970401AG2-262 GEN
Solar/Wind Harmer
0.76
316192AB2-158 GEN
Solar/Wind Harmer
0.724
972003AH1-546 GEN
Solar/Wind Harmer
5.346
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971377AH1-170 GEN
Solar/Wind Harmer
1.271
3147623JAMES R
Solar/Wind Harmer
0.276
972135AH1-637 GEN
Solar/Wind Harmer
0.962
3146776BUCKING
Solar/Wind Harmer
0.042
964791AG1-342 GEN
Solar/Wind Harmer
2.488
3146843MT LREL
Solar/Wind Harmer
0.129
3146843MT LREL
Solar/Wind Harmer
0.129
971489AH1-241 GEN
Solar/Wind Harmer
6.355
316222AC1-221 GEN
Solar/Wind Harmer
0.477
226929AD2-058 GEN
Solar/Wind Helper
0.118
LAGNLTFEXP_LAGN->PJM
CLTF
7.584
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.244
TVALTFEXP_TVA->PJM
CLTF
3.839
NYPJM->LTFIMP_NY
CLTF
2.846
LGEELTFEXP_LGEE->PJM
CLTF
1.614
WECLTFEXP_WEC->PJM
CLTF
0.82
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.903
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.41
MECLTFEXP_MEC->PJM
CLTF
4.166
SIGELTFEXP_SIGE->PJM
CLTF
0.129
CPLELTFEXP_CPLE->PJM
CLTF
8.902
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.096

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.56 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4204.63
MW Contribution:5.23
Bus #Bus NameTypeMW Contribution
970497AG2-320 GEN
50/50
20.637
3150401LDYSMT4
50/50
28.522
3150371LDYSMT1
50/50
27.56
315051AA1-145 CT1
50/50
1.572
3142416OLDCHRC
Solar/Wind Harmer
1.861
970293AG2-193 GEN
Solar/Wind Harmer
2.005
3143096IRON208
Adder
0.776
3143096IRON208
Adder
0.76
316473AC1-191 GEN
Solar/Wind Harmer
0.625
3142946ENON
Solar/Wind Harmer
0.062
3150861SPRUNCD
Adder
0.844
970133AG2-095 GEN
Solar/Wind Harmer
1.736
316382AG1-145 C
Solar/Wind Harmer
0.001
970129AG2-093 GEN
Solar/Wind Harmer
10.867
315778AD1-151 GEN
Solar/Wind Harmer
14.321
965281AG1-393 GEN
Solar/Wind Harmer
1.902
315839AE2-212 C
Solar/Wind Harmer
0.001
3150921YORKTN3
Adder
4.467
3144216WINCHST
Adder
0.67
961611AG1-000B GEN
Solar/Wind Harmer
4.73
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
3151221GRAVEL6
Adder
12.845
3151171GRAVELC
Adder
2.471
315773AC2-141 GEN
Solar/Wind Harmer
6.428
3145336SMITFLD
Solar/Wind Harmer
0.07
315813AE1-149 C
Solar/Wind Harmer
9.336
3144536CHRHLND
Solar/Wind Harmer
0.026
970659AG2-427 GEN
Solar/Wind Harmer
1.84
3151101ELIZAR3
Adder
16.14
316083AB2-161 GEN
Solar/Wind Harmer
0.002
3144873MCLAUGH
Solar/Wind Harmer
0.004
944581AF1-123 GEN
Solar/Wind Harmer
39.115
944601AF1-125 GEN
Solar/Wind Harmer
38.512
970661AG2-428 GEN
Solar/Wind Harmer
3.665
971531AH1-263 GEN
50/50
38.605
3150411LDYSMT5
50/50
28.611
3150381LDYSMT2
50/50
27.382
972213AH1-691 GEN
50/50
4.632
972215AH1-692 GEN
50/50
4.632
963051AG1-154 GEN
50/50
3.563
972189AH1-679 GEN
50/50
3.525
316312AB1-027
Solar/Wind Harmer
0.343
315976AC1-164 GENA
Solar/Wind Harmer
19.21
316169AC1-164_GENC
Solar/Wind Harmer
16.596
315975AC1-164 GENB
Solar/Wind Harmer
0.568
971285AH1-108 GEN
Adder
1.381
316233AE1-074 FULL
Solar/Wind Harmer
0.144
971281AH1-106 GEN
Solar/Wind Harmer
2.501
971283AH1-107 GEN
Solar/Wind Harmer
2.501
316132AB2-190 GEN1
Solar/Wind Harmer
0.964
316369SG1_INVT
Solar/Wind Harmer
0.007
971167AH1-042 GEN
Solar/Wind Harmer
15.763
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
972265AH1-717 GEN
Adder
13.718
3151201GRAVEL4
Adder
12.859
3151191GRAVEL3
Adder
12.697
3151211GRAVEL5
Adder
12.697
971445AH1-216 GEN
Solar/Wind Harmer
12.371
3143873LANEXA
Solar/Wind Harmer
0.105
3138283WHITEMARSH
Solar/Wind Harmer
0.04
3143316POE
Solar/Wind Harmer
0.69
3151081ELIZAR1
Adder
15.936
3151091ELIZAR2
Adder
15.659
316314AB2-024 C
Solar/Wind Harmer
0.001
3152611GOSPORTB
Adder
2.213
3152621GOSPORTC
Adder
1.878
3152601GOSPORTA
Adder
1.733
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
5.106
957871AF2-081 GEN
Solar/Wind Harmer
8.564
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.118
316311AC2-079 GEN
Solar/Wind Harmer
4.932
319010AE1-072 C
Solar/Wind Harmer
0.864
315662AE1-191 GEN
Solar/Wind Harmer
0.006
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3146406KITTY HAWK
Solar/Wind Harmer
0.021
316305AF2-043 C
Solar/Wind Harmer
0.001
315835AF2-110_GEN
Solar/Wind Harmer
1.17
3141873WAN 176
Solar/Wind Harmer
0.034
313526AB2-022
Solar/Wind Harmer
0.092
3146486SUNBURY
Solar/Wind Harmer
0.169
3146486SUNBURY
Solar/Wind Harmer
0.169
316321Z2-027
Solar/Wind Harmer
0.031
3146396TANGLEW
Solar/Wind Harmer
0.466
3145176PASQUOTANK
Solar/Wind Harmer
0.105
3141913WHIT STONE
Solar/Wind Harmer
0.167
3138133OCRAN
Solar/Wind Harmer
0.05
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
972197AH1-683 GEN
50/50
4.454
972219AH1-694 GEN
50/50
3.207
315052AA1-145 CT2
50/50
1.579
966881AG1-559 GEN
Solar/Wind Harmer
0.23
3142416OLDCHRC
Solar/Wind Harmer
0.499
3142416OLDCHRC
Solar/Wind Harmer
0.191
3143096IRON208
Adder
0.776
3142543TWELFTH
Solar/Wind Harmer
0.018
944631AF1-128 GEN
Adder
87.636
3150851SPRUNCC
Adder
0.844
316159AE1-175 C
Solar/Wind Harmer
0.156
3143526WINTERP
Solar/Wind Harmer
0.937
970129AG2-093 GEN
Solar/Wind Harmer
5.114
316458AB2-190 GEN2
Solar/Wind Harmer
0.964
971069AG2-661 GEN
Solar/Wind Harmer
3.182
315671AE2-027_GEN
Solar/Wind Harmer
11.444
971647AH1-324 GEN
Solar/Wind Harmer
7.594
971317AH1-138 GEN
Solar/Wind Harmer
1.327
3138126ROCKLANDING
Solar/Wind Harmer
0.082
961611AG1-000B GEN
Solar/Wind Harmer
9.303
3142433PROV 92
Solar/Wind Harmer
0.707
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
3143226MDLTHAN
Solar/Wind Harmer
0.177
3151171GRAVELC
Adder
1.879
316294AC1-161 GEN
Solar/Wind Harmer
3.05
3145336SMITFLD
Solar/Wind Harmer
0.702
970659AG2-427 GEN
Solar/Wind Harmer
8.414
316375AC2-012 GEN
Solar/Wind Harmer
0.004
3150981CHESPKA
Adder
2.17
316381AD1-082 GEN
Solar/Wind Harmer
0.181
944591AF1-124 GEN
Solar/Wind Harmer
39.254
970661AG2-428 GEN
Solar/Wind Harmer
17.23
316072AD1-144
Solar/Wind Harmer
0.063
3141766HARMONY
Solar/Wind Harmer
0.035
971777AH1-397 GEN
Solar/Wind Harmer
0.455
3141843SHACKLE
Adder
0.88
316388AE2-253 GEN
Solar/Wind Harmer
0.539
3146456SLIGO L269
Solar/Wind Harmer
0.172
316246AF1-032 C
Solar/Wind Harmer
0.077
316093AE2-104_GEN
Solar/Wind Harmer
2.869
939411AE1-173 GEN
Solar/Wind Harmer
72.314
940641AE2-051 GEN
Solar/Wind Harmer
13.462
3146516WINFALL
Solar/Wind Harmer
0.544
3146516WINFALL
Solar/Wind Harmer
0.168
3138133OCRAN
Solar/Wind Harmer
0.1
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.163
3145663CRESWEL
Solar/Wind Harmer
0.447
971163AH1-040 GEN
Solar/Wind Harmer
12.788
962861AG1-135 GEN
Solar/Wind Harmer
5.018
3143336POWHATN
Solar/Wind Harmer
2.779
3146206CASHIE
Solar/Wind Harmer
0.155
971547AH1-271 GEN
Solar/Wind Harmer
3.308
3145893MURPHYS
Solar/Wind Harmer
0.617
3145893MURPHYS
Solar/Wind Harmer
0.686
316023GEN1_S
Solar/Wind Harmer
0.345
3141726DUNNSVL
Solar/Wind Harmer
0.612
3146173TUNIS
Solar/Wind Harmer
0.153
970919AG2-571 GEN
Solar/Wind Harmer
5.402
3145683EARLEYS
Solar/Wind Harmer
0.151
970087AG2-069 GEN
Solar/Wind Harmer
12.113
316336AC2-165 C
Solar/Wind Harmer
0.006
3146263WOODLND
Solar/Wind Harmer
0.15
960081AF2-299 GEN
Solar/Wind Harmer
1.442
3150351NORNECKC2
Adder
1.495
3141783LANCAST
Solar/Wind Harmer
0.099
3141783LANCAST
Solar/Wind Harmer
0.066
316315AB2-025 C
Solar/Wind Harmer
0.133
315814AE2-033 C
Solar/Wind Harmer
12.978
3130156CHOWAN
Solar/Wind Harmer
0.163
3130156CHOWAN
Solar/Wind Harmer
0.163
941031AE2-094 GEN
Solar/Wind Harmer
29.802
944011AF1-069 GEN
Solar/Wind Harmer
9.738
962981AG1-147 GEN
Solar/Wind Harmer
6.022
315816AE2-034 GEN
Solar/Wind Harmer
0.686
970673AG2-436 GEN
Solar/Wind Harmer
34.019
970673AG2-436 GEN
Solar/Wind Harmer
22.68
970327AG2-215 GEN
Solar/Wind Harmer
5.226
971967AH1-528 GEN
Solar/Wind Harmer
25.262
3130546PLYMOUTH
Solar/Wind Harmer
0.157
315732AD1-074 GEN1
Solar/Wind Harmer
0.9
315733AD1-074 GEN2
Solar/Wind Harmer
0.9
315735AD1-075 GEN1
Solar/Wind Harmer
0.451
965291AG1-394 GEN
Solar/Wind Harmer
0.692
3146206CASHIE
Solar/Wind Harmer
0.155
970601AG2-382 GEN
Solar/Wind Harmer
5.789
3145893MURPHYS
Solar/Wind Harmer
0.416
3145893MURPHYS
Solar/Wind Harmer
0.154
3145513AHOSKIE
Solar/Wind Harmer
0.318
3145513AHOSKIE
Solar/Wind Harmer
0.152
3145683EARLEYS
Solar/Wind Harmer
0.303
3145683EARLEYS
Solar/Wind Harmer
0.151
3145683EARLEYS
Solar/Wind Harmer
0.151
970085AG2-068 GEN
Solar/Wind Harmer
8.075
970581AG2-369 GEN
Solar/Wind Harmer
6.945
3146043SEABORD
Solar/Wind Harmer
0.151
315607AA1-063A GEN
Solar/Wind Harmer
0.307
3141813NORNECK
Solar/Wind Harmer
0.15
316087AB2-174 GEN
Solar/Wind Harmer
0.004
315652AC1-086 GEN
Solar/Wind Harmer
16.312
3137643SOCKMAN
Solar/Wind Harmer
0.591
3145796HORNRTN
Solar/Wind Harmer
0.468
3145796HORNRTN
Solar/Wind Harmer
0.058
3146033SCOT NK
Solar/Wind Harmer
0.582
972193AH1-681 GEN
Adder
3.246
970831AG2-522 GEN
Solar/Wind Harmer
6.013
316005AA1-067
Solar/Wind Harmer
0.151
3145746EVERETS
Solar/Wind Harmer
0.559
3145746EVERETS
Solar/Wind Harmer
0.14
3145746EVERETS
Solar/Wind Harmer
0.14
3145746EVERETS
Solar/Wind Harmer
0.14
970181AG2-120 GEN
Solar/Wind Harmer
1.749
957861AF2-080 GEN
Solar/Wind Harmer
5.96
316420AA1-050 GEN
Solar/Wind Harmer
0.005
3145573BETHELC
Solar/Wind Harmer
0.136
3145573BETHELC
Solar/Wind Harmer
0.136
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
2.275
3144303KENBRDG
Solar/Wind Harmer
0.108
970683AG2-441 GEN
Solar/Wind Harmer
9.014
970681AG2-440 GEN
Solar/Wind Harmer
7.211
946301AF1-294 GEN
Solar/Wind Harmer
2.665
961791AG1-021 GEN
Solar/Wind Harmer
1.296
315657AE1-056 GEN
Solar/Wind Harmer
4.654
970285AG2-188 GEN
Solar/Wind Harmer
10.387
971845AH1-439 GEN
Solar/Wind Harmer
5.923
316223AC1-118
Solar/Wind Harmer
0.092
316118AC1-105 GEN
Solar/Wind Harmer
0.328
972205AH1-687 GEN
Adder
5.363
3147173SINAI
Solar/Wind Harmer
0.125
3147243WELCO
Solar/Wind Harmer
0.078
971447AH1-217 GEN
Solar/Wind Harmer
3.576
970865AG2-541 GEN
Solar/Wind Harmer
3.934
3141766HARMONY
Solar/Wind Harmer
2.301
3141843SHACKLE
Adder
0.88
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
0.172
971153AH1-033 GEN
Solar/Wind Harmer
1.985
316280AD1-041 GEN
Solar/Wind Harmer
0.004
316156AD2-030 GEN
Solar/Wind Harmer
0.126
3141873WAN 176
Solar/Wind Harmer
3.03
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.168
3146626S HERTFORD
Solar/Wind Harmer
0.167
3145273HOLLAND
Solar/Wind Harmer
0.125
3146376EDENTON
Solar/Wind Harmer
0.163
962971AG1-146 GEN
Solar/Wind Harmer
2.581
315614AA2-178 GEN
Solar/Wind Harmer
0.915
970009AG2-005 GEN
Solar/Wind Harmer
1.189
971157AH1-035 GEN
Solar/Wind Harmer
1.886
315737AD1-076 GEN
Solar/Wind Harmer
2.016
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
316313AB2-026
Solar/Wind Harmer
0.099
316258AE1-075 C
Solar/Wind Harmer
0.118
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.362
316404AE1-155 C
Solar/Wind Harmer
0.035
3146206CASHIE
Solar/Wind Harmer
0.155
3145893MURPHYS
Solar/Wind Harmer
0.258
3145893MURPHYS
Solar/Wind Harmer
0.154
957521AF2-046 GEN
Solar/Wind Harmer
11.452
961681AG1-008 GEN
Solar/Wind Harmer
11.452
316365GEN2_N
Solar/Wind Harmer
0.345
3146173TUNIS
Solar/Wind Harmer
0.153
3156021HOLLOMANSOL
Solar/Wind Harmer
0.694
316463AE2-346 GEN
Solar/Wind Harmer
0.131
316140AB2-099
Solar/Wind Harmer
0.054
962331AG1-082 GEN
Solar/Wind Harmer
1.624
970917AG2-570 GEN
Solar/Wind Harmer
13.506
3146263WOODLND
Solar/Wind Harmer
0.15
3150351NORNECKC2
Adder
1.52
3145963POPLR C
Solar/Wind Harmer
0.149
971781AH1-399 GEN
Solar/Wind Harmer
0.196
3142666NORTHAMPTON
Solar/Wind Harmer
0.149
313506AB2-031 GEN
Solar/Wind Harmer
0.46
316317KELFORD C
Solar/Wind Harmer
0.014
3145823KELFORD
Solar/Wind Harmer
0.149
3145796HORNRTN
Solar/Wind Harmer
0.585
3145796HORNRTN
Solar/Wind Harmer
0.146
3147043LAWRENC
Solar/Wind Harmer
0.087
3145933PARMELE
Solar/Wind Harmer
0.143
966801AG1-551 GEN
Solar/Wind Harmer
1.67
316210AC1-098 GEN
Solar/Wind Harmer
1.33
316478AD1-087 GEN
Solar/Wind Harmer
0.496
316486AD2-202 GEN
Solar/Wind Harmer
0.146
972255AH1-712 GEN
Adder
72.658
3145746EVERETS
Solar/Wind Harmer
0.14
3145746EVERETS
Solar/Wind Harmer
0.14
315724AD1-057 GEN
Solar/Wind Harmer
0.523
970909AG2-566 GEN
Solar/Wind Harmer
1.479
316327AA2-057 GEN
Solar/Wind Harmer
0.209
3146073TAR RVR
Solar/Wind Harmer
0.136
3146083TARBORO
Solar/Wind Harmer
0.136
3146233WITAKRS
Solar/Wind Harmer
0.683
3146233WITAKRS
Solar/Wind Harmer
0.093
3138543CONSLDL
Solar/Wind Harmer
0.09
316131AB2-060 GEN
Solar/Wind Harmer
0.427
964241AG1-285 GEN
Solar/Wind Harmer
9.041
315785AD2-033 C
Solar/Wind Harmer
1.101
970257AG2-171 GEN
Solar/Wind Harmer
4.332
959311AF2-222 GEN
Solar/Wind Harmer
12.029
963181AG1-167 GEN
Solar/Wind Harmer
0.54
3144293JTRSVLE
Adder
0.43
3147133PAMPLIN
Solar/Wind Harmer
0.423
971193AH1-056 GEN
Solar/Wind Harmer
8.216
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.081
961601AG1-000A GEN
Solar/Wind Harmer
9.521
3145543BTLEBRO
Solar/Wind Harmer
0.134
3145543BTLEBRO
Solar/Wind Harmer
0.134
971623AH1-311 GEN
Solar/Wind Harmer
0.268
3147666LOUISA
Solar/Wind Harmer
0.307
3146776BUCKING
Solar/Wind Harmer
0.047
3141906WESTMOR
Solar/Wind Harmer
0.051
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.326
970221AG2-151 GEN
Solar/Wind Harmer
6.386
970737AG2-469 GEN
Solar/Wind Harmer
5.057
971683AH1-343 GEN
Solar/Wind Harmer
4.312
316283AC2-100 C
Solar/Wind Harmer
0.223
227287AC2-120 GEN
Solar/Wind Helper
0.388
226910AB2-157 C
Solar/Wind Helper
0.015
3150391LDYSMT3
50/50
28.468
972195AH1-682 GEN
50/50
3.741
315673AE1-157 GEN
Solar/Wind Harmer
13.816
957411AF2-035 GEN
Solar/Wind Harmer
8.508
970317AG2-208 GEN
Solar/Wind Harmer
7.883
3142296MT RD221
Adder
0.622
3142366NRTHEST
Adder
0.618
3150691DARBY 3
Adder
13.575
3150701DARBY 4
Adder
13.543
3150681DARBY 2
Adder
13.528
3150671DARBY 1
Adder
13.512
316075AC2-137 C
Solar/Wind Harmer
0.051
966871AG1-558 GEN
Solar/Wind Harmer
0.214
3142946ENON
Solar/Wind Harmer
0.018
944641AF1-129 GEN
Adder
86.296
3143526WINTERP
Solar/Wind Harmer
0.937
316240AF1-291 C
Solar/Wind Harmer
0.001
316033AB2-134 GEN
Solar/Wind Harmer
0.01
315697AD1-025 GEN
Solar/Wind Harmer
0.201
971223AH1-071 GEN
Solar/Wind Harmer
1.886
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.032
3150991CHESPKB
Adder
1.821
3150991CHESPKB
Adder
1.777
970657AG2-426 GEN
Solar/Wind Harmer
6.079
970657AG2-426 GEN
Solar/Wind Harmer
1.274
316316AC1-027 C
Solar/Wind Harmer
0.166
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.005
3145506HICKORY
Solar/Wind Harmer
0.691
3145506HICKORY
Solar/Wind Harmer
0.414
3145506HICKORY
Solar/Wind Harmer
0.104
316339AD2-160 GEN
Solar/Wind Harmer
0.279
316018AA1-139 ULT2
Solar/Wind Harmer
0.004
316017AA1-139 ULT1
Solar/Wind Harmer
0.096
3137176SLIGO L2192
Solar/Wind Harmer
0.683
3146456SLIGO L269
Solar/Wind Harmer
3.038
3130086AYDLETT
Solar/Wind Harmer
0.686
3146386ELIZ CT
Solar/Wind Harmer
0.17
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.168
3146516WINFALL
Solar/Wind Harmer
0.168
3146516WINFALL
Solar/Wind Harmer
0.168
3146626S HERTFORD
Solar/Wind Harmer
0.167
3146626S HERTFORD
Solar/Wind Harmer
0.167
3144356SAPONY
Solar/Wind Harmer
1.377
315742AE1-103 GEN
Solar/Wind Harmer
0.002
3146376EDENTON
Solar/Wind Harmer
0.726
3146376EDENTON
Solar/Wind Harmer
0.726
972185AH1-677 GEN
Adder
8.883
972187AH1-678 GEN
Adder
4.463
958261AF2-120 GEN
Solar/Wind Harmer
5.156
316065AD1-022 GEN
Solar/Wind Harmer
7.167
970933AG2-581 GEN
Solar/Wind Harmer
12.385
3145893MURPHYS
Solar/Wind Harmer
1.032
3145893MURPHYS
Solar/Wind Harmer
0.278
3146173TUNIS
Solar/Wind Harmer
0.153
3146173TUNIS
Solar/Wind Harmer
0.153
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.57
3150341NORNECKC1
Adder
1.558
316468AD1-105 GEN
Solar/Wind Harmer
-0.049
3142666NORTHAMPTON
Solar/Wind Harmer
0.149
3142666NORTHAMPTON
Solar/Wind Harmer
0.149
3142666NORTHAMPTON
Solar/Wind Harmer
0.149
3142666NORTHAMPTON
Solar/Wind Harmer
0.089
316181AB2-040 GEN
Solar/Wind Harmer
0.216
316426AA2-053 GEN
Solar/Wind Harmer
0.5
3145593CAROLNA
Solar/Wind Harmer
0.147
3145593CAROLNA
Solar/Wind Harmer
0.147
966811AG1-552 GEN
Solar/Wind Harmer
1.596
3145593CAROLNA
Solar/Wind Harmer
0.183
970099AG2-077 GEN
Solar/Wind Harmer
15.655
3145783HORNRTN
Solar/Wind Harmer
2.603
3145783HORNRTN
Solar/Wind Harmer
2.082
3145783HORNRTN
Solar/Wind Harmer
0.651
3145783HORNRTN
Solar/Wind Harmer
0.26
3145796HORNRTN
Solar/Wind Harmer
0.438
3145933PARMELE
Solar/Wind Harmer
0.287
3145933PARMELE
Solar/Wind Harmer
0.143
316274AC1-208 GEN
Solar/Wind Harmer
0.738
971741AH1-377 GEN
Solar/Wind Harmer
13.893
970301AG2-198 GEN
Solar/Wind Harmer
5.917
939181AE1-148 GEN
Solar/Wind Harmer
6.546
3145493TOT1
Solar/Wind Harmer
0.316
3145453TOT5
Solar/Wind Harmer
0.189
3145603CNETO
Solar/Wind Harmer
0.126
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.01
970323AG2-213 GEN
Solar/Wind Harmer
5.776
971775AH1-396 GEN
Solar/Wind Harmer
0.217
958211AF2-115 GEN
Solar/Wind Harmer
1.621
963191AG1-168 GEN
Solar/Wind Harmer
0.54
3144293JTRSVLE
Adder
0.43
3144293JTRSVLE
Adder
0.362
3147133PAMPLIN
Solar/Wind Harmer
0.135
3147133PAMPLIN
Solar/Wind Harmer
0.108
961601AG1-000A GEN
Solar/Wind Harmer
2.38
316263AC1-034 GEN
Solar/Wind Harmer
5.085
962561AG1-105 GEN
Solar/Wind Harmer
6.258
3146776BUCKING
Solar/Wind Harmer
0.521
3146776BUCKING
Solar/Wind Harmer
0.042
964791AG1-342 GEN
Solar/Wind Harmer
2.485
3146843MT LREL
Solar/Wind Harmer
0.129
3146843MT LREL
Solar/Wind Harmer
0.129
971489AH1-241 GEN
Solar/Wind Harmer
6.386
316222AC1-221 GEN
Solar/Wind Harmer
0.476
226929AD2-058 GEN
Solar/Wind Helper
0.118
3145963POPLR C
Solar/Wind Harmer
0.149
3145823KELFORD
Solar/Wind Harmer
0.149
316011AB1-132 GEN
Solar/Wind Harmer
2.696
962571AG1-106 GEN
Solar/Wind Harmer
2.11
316174AB2-169 GEN
Solar/Wind Harmer
0.004
316190AA2-174 GEN
Solar/Wind Harmer
0
971795AH1-408 GEN
Solar/Wind Harmer
9.812
957481AF2-042 GEN
Solar/Wind Harmer
39.137
3145783HORNRTN
Solar/Wind Harmer
0.146
3145796HORNRTN
Solar/Wind Harmer
0.482
3145796HORNRTN
Solar/Wind Harmer
0.146
3147043LAWRENC
Adder
1.319
315693AD1-088 GEN
Solar/Wind Harmer
6.943
962491AG1-098 GEN
Solar/Wind Harmer
8.237
3146293MARTNCO
Solar/Wind Harmer
0.133
316212AC1-099_GEN
Solar/Wind Harmer
0.741
972277AH1-723 GEN
Adder
84.669
3145746EVERETS
Solar/Wind Harmer
0.14
3145746EVERETS
Solar/Wind Harmer
0.14
316129AC1-054 GEN
Solar/Wind Harmer
0.527
316337AD2-073 GEN
Solar/Wind Harmer
0.122
971065AG2-659 GEN
Solar/Wind Harmer
5.957
315722AD1-056 GEN
Solar/Wind Harmer
0.882
316494AC1-189 GEN
Solar/Wind Harmer
0.467
970937AG2-583 GEN
Solar/Wind Harmer
8.414
961671AG1-007 GEN
Solar/Wind Harmer
0.021
3146083TARBORO
Solar/Wind Harmer
0.136
3145493TOT1
Solar/Wind Harmer
0.606
3146233WITAKRS
Solar/Wind Harmer
0.542
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.004
970685AG2-442 GEN
Solar/Wind Harmer
10.095
963171AG1-166 GEN
Solar/Wind Harmer
0.72
971563AH1-280 GEN
Solar/Wind Harmer
1.44
3144293JTRSVLE
Adder
0.43
3146926FARMVIL
Solar/Wind Harmer
0.081
3145543BTLEBRO
Solar/Wind Harmer
0.134
3145543BTLEBRO
Solar/Wind Harmer
0.107
316359AB2-059 GEN
Solar/Wind Harmer
0.481
316049AB1-081 GEN
Solar/Wind Harmer
0.766
3142053HEARTS
Solar/Wind Harmer
0.236
3147666LOUISA
Solar/Wind Harmer
0.534
316192AB2-158 GEN
Solar/Wind Harmer
0.744
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.052
970401AG2-262 GEN
Solar/Wind Harmer
0.759
972003AH1-546 GEN
Solar/Wind Harmer
5.371
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971377AH1-170 GEN
Solar/Wind Harmer
1.277
3147623JAMES R
Solar/Wind Harmer
0.277
LAGNLTFEXP_LAGN->PJM
CLTF
7.576
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.212
TVALTFEXP_TVA->PJM
CLTF
3.836
NYPJM->LTFIMP_NY
CLTF
2.848
LGEELTFEXP_LGEE->PJM
CLTF
1.613
WECLTFEXP_WEC->PJM
CLTF
0.819
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.893
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.398
MECLTFEXP_MEC->PJM
CLTF
4.164
SIGELTFEXP_SIGE->PJM
CLTF
0.129
CPLELTFEXP_CPLE->PJM
CLTF
8.886
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.062

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:175.45 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5650.14
MW Contribution:7.02
Bus #Bus NameTypeMW Contribution
970119AG2-088 GEN
50/50
49.132
315243AE2-183_GT3
50/50
5.558
3151051BRUNSWICKS1
50/50
9.077
3151021BRUNSWICKG1
50/50
4.373
971451AH1-221 GEN
50/50
13.283
3150981CHESPKA
50/50
4.07
3151031BRUNSWICKG2
50/50
4.373
3151101ELIZAR3
50/50
30.305
3150861SPRUNCD
50/50
1.461
3151161SURRY 1
50/50
11.304
970917AG2-570 GEN
Solar/Wind Harmer
28.408
315773AC2-141 GEN
Solar/Wind Harmer
11.382
944581AF1-123 GEN
Solar/Wind Harmer
69.733
944601AF1-125 GEN
Solar/Wind Harmer
68.658
3144873MCLAUGH
Solar/Wind Harmer
0.008
3146456SLIGO L269
Solar/Wind Harmer
0.306
971153AH1-033 GEN
Solar/Wind Harmer
3.534
3144536CHRHLND
Solar/Wind Harmer
0.046
316320Y1-086
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
6.41
316083AB2-161 GEN
Solar/Wind Harmer
0.004
970659AG2-427 GEN
Solar/Wind Harmer
3.204
315813AE1-149 C
Solar/Wind Harmer
16.153
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.3
3145336SMITFLD
Solar/Wind Harmer
0.12
3146626S HERTFORD
Solar/Wind Harmer
0.299
315839AE2-212 C
Solar/Wind Harmer
0.002
3145273HOLLAND
Solar/Wind Harmer
0.223
316313AB2-026
Solar/Wind Harmer
0.186
316258AE1-075 C
Solar/Wind Harmer
0.223
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.463
965281AG1-393 GEN
Solar/Wind Harmer
3.139
3151221GRAVEL6
Adder
21.396
3151171GRAVELC
Adder
4.116
3146376EDENTON
Solar/Wind Harmer
0.294
961611AG1-000B GEN
Solar/Wind Harmer
7.797
316365GEN2_N
Solar/Wind Harmer
0.655
315614AA2-178 GEN
Solar/Wind Harmer
1.657
315778AD1-151 GEN
Solar/Wind Harmer
23.065
3156081AA2-088 GEN
Solar/Wind Harmer
0.007
970129AG2-093 GEN
Solar/Wind Harmer
17.309
316478AD1-087 GEN
Solar/Wind Harmer
0.999
316486AD2-202 GEN
Solar/Wind Harmer
0.293
971157AH1-035 GEN
Solar/Wind Harmer
3.43
315737AD1-076 GEN
Solar/Wind Harmer
3.669
3144216WINCHST
Adder
1.072
970133AG2-095 GEN
Solar/Wind Harmer
2.723
3145893MURPHYS
Solar/Wind Harmer
0.474
3145893MURPHYS
Solar/Wind Harmer
0.283
3146206CASHIE
Solar/Wind Harmer
0.283
957521AF2-046 GEN
Solar/Wind Harmer
21.052
961681AG1-008 GEN
Solar/Wind Harmer
21.052
3150921YORKTN3
Adder
7.103
3146173TUNIS
Solar/Wind Harmer
0.281
313506AB2-031 GEN
Solar/Wind Harmer
0.867
3156021HOLLOMANSOL
Solar/Wind Harmer
1.274
316463AE2-346 GEN
Solar/Wind Harmer
0.241
316140AB2-099
Solar/Wind Harmer
0.1
962331AG1-082 GEN
Solar/Wind Harmer
2.99
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3146263WOODLND
Solar/Wind Harmer
0.278
3147043LAWRENC
Solar/Wind Harmer
0.166
316317KELFORD C
Solar/Wind Harmer
0.027
3145823KELFORD
Solar/Wind Harmer
0.275
3145796HORNRTN
Solar/Wind Harmer
1.1
3145796HORNRTN
Solar/Wind Harmer
0.275
3145963POPLR C
Solar/Wind Harmer
0.274
3143096IRON208
Adder
1.147
3143096IRON208
Adder
1.124
316382AG1-145 C
Solar/Wind Harmer
0.002
316210AC1-098 GEN
Solar/Wind Harmer
2.485
3145933PARMELE
Solar/Wind Harmer
0.265
966801AG1-551 GEN
Solar/Wind Harmer
3.091
3142946ENON
Solar/Wind Harmer
0.089
315724AD1-057 GEN
Solar/Wind Harmer
0.985
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
316327AA2-057 GEN
Solar/Wind Harmer
0.393
970909AG2-566 GEN
Solar/Wind Harmer
2.748
316131AB2-060 GEN
Solar/Wind Harmer
0.81
3146233WITAKRS
Solar/Wind Harmer
1.286
3146233WITAKRS
Solar/Wind Harmer
0.174
3138543CONSLDL
Solar/Wind Harmer
0.169
964241AG1-285 GEN
Solar/Wind Harmer
17.051
3146073TAR RVR
Solar/Wind Harmer
0.255
3146083TARBORO
Solar/Wind Harmer
0.255
970293AG2-193 GEN
Solar/Wind Harmer
2.717
3142433PROV 92
Adder
0.492
3142433PROV 92
Adder
0.492
316303AF2-085
50/50
6.551
315244AE2-183_ST
50/50
9.609
963041AG1-153 GEN
50/50
8.856
315779AE2-040
50/50
4.414
3151081ELIZAR1
50/50
29.922
3151091ELIZAR2
50/50
29.403
941591AE2-156 GEN
50/50
27.332
3152611GOSPORTB
50/50
4.152
3152621GOSPORTC
50/50
3.523
3152601GOSPORTA
50/50
3.25
971285AH1-108 GEN
50/50
2.391
972263AH1-716 GEN
50/50
170.662
941031AE2-094 GEN
Solar/Wind Harmer
63.788
944011AF1-069 GEN
Solar/Wind Harmer
20.842
970673AG2-436 GEN
Solar/Wind Harmer
72.487
970673AG2-436 GEN
Solar/Wind Harmer
48.325
316233AE1-074 FULL
Solar/Wind Harmer
0.268
971281AH1-106 GEN
Solar/Wind Harmer
4.649
971283AH1-107 GEN
Solar/Wind Harmer
4.649
971967AH1-528 GEN
Solar/Wind Harmer
53.477
970085AG2-068 GEN
Solar/Wind Harmer
16.971
970581AG2-369 GEN
Solar/Wind Harmer
14.595
316315AB2-025 C
Solar/Wind Harmer
0.256
315814AE2-033 C
Solar/Wind Harmer
24.917
3143316POE
Solar/Wind Harmer
1.232
957871AF2-081 GEN
Solar/Wind Harmer
15.244
319010AE1-072 C
Solar/Wind Harmer
1.539
3146406KITTY HAWK
Solar/Wind Harmer
0.038
316305AF2-043 C
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.164
315835AF2-110_GEN
Solar/Wind Harmer
2.081
315833AF1-017_GEN
Solar/Wind Harmer
0.002
316349AD2-085 GEN
Solar/Wind Harmer
0.208
316311AC2-079 GEN
Solar/Wind Harmer
8.702
3146486SUNBURY
Solar/Wind Harmer
0.302
3146486SUNBURY
Solar/Wind Harmer
0.302
316321Z2-027
Solar/Wind Harmer
0.056
3146396TANGLEW
Solar/Wind Harmer
0.833
3145176PASQUOTANK
Solar/Wind Harmer
0.187
971445AH1-216 GEN
Solar/Wind Harmer
21.042
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.294
3130156CHOWAN
Solar/Wind Harmer
0.294
972265AH1-717 GEN
Adder
22.85
3151201GRAVEL4
Adder
21.42
3151191GRAVEL3
Adder
21.149
3151211GRAVEL5
Adder
21.149
316369SG1_INVT
Solar/Wind Harmer
0.011
315816AE2-034 GEN
Solar/Wind Harmer
1.242
316132AB2-190 GEN1
Solar/Wind Harmer
1.538
3130546PLYMOUTH
Solar/Wind Harmer
0.286
965291AG1-394 GEN
Solar/Wind Harmer
1.269
315732AD1-074 GEN1
Solar/Wind Harmer
1.639
315733AD1-074 GEN2
Solar/Wind Harmer
1.639
315735AD1-075 GEN1
Solar/Wind Harmer
0.82
3145893MURPHYS
Solar/Wind Harmer
0.765
3145893MURPHYS
Solar/Wind Harmer
0.283
3146206CASHIE
Solar/Wind Harmer
0.283
970601AG2-382 GEN
Solar/Wind Harmer
10.575
316087AB2-174 GEN
Solar/Wind Harmer
0.008
3146043SEABORD
Solar/Wind Harmer
0.28
3145513AHOSKIE
Solar/Wind Harmer
0.586
3145513AHOSKIE
Solar/Wind Harmer
0.28
315607AA1-063A GEN
Solar/Wind Harmer
0.572
3145683EARLEYS
Solar/Wind Harmer
0.558
3145683EARLEYS
Solar/Wind Harmer
0.279
3145683EARLEYS
Solar/Wind Harmer
0.279
315652AC1-086 GEN
Solar/Wind Harmer
30.678
3137643SOCKMAN
Solar/Wind Harmer
1.111
3145796HORNRTN
Solar/Wind Harmer
0.88
3145796HORNRTN
Solar/Wind Harmer
0.11
3146033SCOT NK
Solar/Wind Harmer
1.084
970831AG2-522 GEN
Solar/Wind Harmer
11.448
3138283WHITEMARSH
Solar/Wind Harmer
0.061
316005AA1-067
Solar/Wind Harmer
0.28
3145746EVERETS
Solar/Wind Harmer
1.039
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
970181AG2-120 GEN
Solar/Wind Harmer
3.25
957861AF2-080 GEN
Solar/Wind Harmer
11.129
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316420AA1-050 GEN
Solar/Wind Harmer
0.008
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.255
3145573BETHELC
Solar/Wind Harmer
0.255
971167AH1-042 GEN
Solar/Wind Harmer
22.645
315976AC1-164 GENA
Solar/Wind Harmer
26.291
316169AC1-164_GENC
Solar/Wind Harmer
22.713
315975AC1-164 GENB
Solar/Wind Harmer
0.778
3142433PROV 92
Adder
0.492
3142433PROV 92
Adder
0.492
971443AH1-215 GEN
Solar/Wind Harmer
4.236
3144303KENBRDG
Solar/Wind Harmer
0.201
970683AG2-441 GEN
Solar/Wind Harmer
16.616
970681AG2-440 GEN
Solar/Wind Harmer
13.292
946301AF1-294 GEN
Solar/Wind Harmer
4.868
961791AG1-021 GEN
Solar/Wind Harmer
2.368
3143873LANEXA
Solar/Wind Harmer
0.148
315657AE1-056 GEN
Solar/Wind Harmer
8.449
316118AC1-105 GEN
Solar/Wind Harmer
0.629
970189AG2-124 GEN
Solar/Wind Harmer
7.213
315662AE1-191 GEN
Solar/Wind Harmer
0.008
315666AE1-190 GEN
Solar/Wind Harmer
0.002
316314AB2-024 C
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.048
3147173SINAI
Solar/Wind Harmer
0.24
3147243WELCO
Solar/Wind Harmer
0.15
316312AB1-027
Solar/Wind Harmer
0.429
3141913WHIT STONE
Solar/Wind Harmer
0.234
3138133OCRAN
Solar/Wind Harmer
0.069
3141783LANCAST
Solar/Wind Harmer
0.137
3141783LANCAST
Solar/Wind Harmer
0.091
962981AG1-147 GEN
Solar/Wind Harmer
8.172
970285AG2-188 GEN
Solar/Wind Harmer
17.223
971845AH1-439 GEN
Solar/Wind Harmer
9.707
970327AG2-215 GEN
Solar/Wind Harmer
7.016
970865AG2-541 GEN
Solar/Wind Harmer
7.314
3150851SPRUNCC
50/50
1.461
3152331SURRY 2
50/50
12.331
3143226MDLTHAN
Solar/Wind Harmer
0.368
940641AE2-051 GEN
Solar/Wind Harmer
28.054
939411AE1-173 GEN
Solar/Wind Harmer
145.057
3143526WINTERP
Solar/Wind Harmer
1.742
970919AG2-571 GEN
Solar/Wind Harmer
11.363
970087AG2-069 GEN
Solar/Wind Harmer
25.456
316294AC1-161 GEN
Solar/Wind Harmer
5.4
944591AF1-124 GEN
Solar/Wind Harmer
69.98
316375AC2-012 GEN
Solar/Wind Harmer
0.008
316388AE2-253 GEN
Solar/Wind Harmer
0.96
3146456SLIGO L269
Solar/Wind Harmer
0.306
316246AF1-032 C
Solar/Wind Harmer
0.137
316093AE2-104_GEN
Solar/Wind Harmer
5.099
970661AG2-428 GEN
Solar/Wind Harmer
30.138
316381AD1-082 GEN
Solar/Wind Harmer
0.316
970659AG2-427 GEN
Solar/Wind Harmer
14.649
316072AD1-144
Solar/Wind Harmer
0.109
3146516WINFALL
Solar/Wind Harmer
0.972
3146516WINFALL
Solar/Wind Harmer
0.3
3145336SMITFLD
Solar/Wind Harmer
1.197
957481AF2-042 GEN
Solar/Wind Harmer
79.695
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
5.25
3130156CHOWAN
Solar/Wind Harmer
0.294
3151171GRAVELC
Adder
3.13
961611AG1-000B GEN
Solar/Wind Harmer
15.335
315671AE2-027_GEN
Solar/Wind Harmer
18.679
316023GEN1_S
Solar/Wind Harmer
0.655
971647AH1-324 GEN
Solar/Wind Harmer
12.413
3145663CRESWEL
Solar/Wind Harmer
0.81
971163AH1-040 GEN
Solar/Wind Harmer
23.157
315693AD1-088 GEN
Solar/Wind Harmer
13.873
971069AG2-661 GEN
Solar/Wind Harmer
5.126
962491AG1-098 GEN
Solar/Wind Harmer
16.401
316458AB2-190 GEN2
Solar/Wind Harmer
1.538
970129AG2-093 GEN
Solar/Wind Harmer
8.145
960081AF2-299 GEN
Solar/Wind Harmer
2.73
3138126ROCKLANDING
Solar/Wind Harmer
0.13
3145893MURPHYS
Solar/Wind Harmer
1.134
3145893MURPHYS
Solar/Wind Harmer
1.26
3146206CASHIE
Solar/Wind Harmer
0.283
971547AH1-271 GEN
Solar/Wind Harmer
6.043
3146173TUNIS
Solar/Wind Harmer
0.281
3142543TWELFTH
Solar/Wind Harmer
0.027
3145683EARLEYS
Solar/Wind Harmer
0.279
316011AB1-132 GEN
Solar/Wind Harmer
5.071
962571AG1-106 GEN
Solar/Wind Harmer
3.968
971795AH1-408 GEN
Solar/Wind Harmer
18.591
3146263WOODLND
Solar/Wind Harmer
0.278
316190AA2-174 GEN
Solar/Wind Harmer
0
3147043LAWRENC
Adder
2.5
316336AC2-165 C
Solar/Wind Harmer
0.011
971317AH1-138 GEN
Solar/Wind Harmer
2.057
3145823KELFORD
Solar/Wind Harmer
0.275
3145796HORNRTN
Solar/Wind Harmer
0.907
3145796HORNRTN
Solar/Wind Harmer
0.275
3145783HORNRTN
Solar/Wind Harmer
0.275
3145963POPLR C
Solar/Wind Harmer
0.274
3143096IRON208
Adder
1.147
316174AB2-169 GEN
Solar/Wind Harmer
0.007
316159AE1-175 C
Solar/Wind Harmer
0.235
944631AF1-128 GEN
Adder
128.871
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316212AC1-099_GEN
Solar/Wind Harmer
1.386
316129AC1-054 GEN
Solar/Wind Harmer
1.006
971065AG2-659 GEN
Solar/Wind Harmer
11.378
3146293MARTNCO
Solar/Wind Harmer
0.246
315722AD1-056 GEN
Solar/Wind Harmer
1.662
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
316494AC1-189 GEN
Solar/Wind Harmer
0.872
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3146233WITAKRS
Solar/Wind Harmer
1.019
961671AG1-007 GEN
Solar/Wind Harmer
0.039
3146083TARBORO
Solar/Wind Harmer
0.255
3145493TOT1
Solar/Wind Harmer
1.136
3142433PROV 92
Solar/Wind Harmer
1.012
3142433PROV 92
Adder
0.492
3142433PROV 92
Adder
0.492
316359AB2-059 GEN
Solar/Wind Harmer
0.906
316049AB1-081 GEN
Solar/Wind Harmer
1.444
3145543BTLEBRO
Solar/Wind Harmer
0.252
3145543BTLEBRO
Solar/Wind Harmer
0.202
3142053HEARTS
Solar/Wind Harmer
0.444
970685AG2-442 GEN
Solar/Wind Harmer
18.609
970401AG2-262 GEN
Solar/Wind Harmer
1.452
963171AG1-166 GEN
Solar/Wind Harmer
1.316
971563AH1-280 GEN
Solar/Wind Harmer
2.632
3144293JTRSVLE
Adder
0.785
971777AH1-397 GEN
Solar/Wind Harmer
0.643
3141843SHACKLE
Adder
1.244
3141766HARMONY
Solar/Wind Harmer
0.048
3142416OLDCHRC
Solar/Wind Harmer
0.623
3142416OLDCHRC
Solar/Wind Harmer
0.239
3146926FARMVIL
Solar/Wind Harmer
0.141
3138133OCRAN
Solar/Wind Harmer
0.139
316003AC1-222 GEN
Solar/Wind Harmer
0.006
970937AG2-583 GEN
Solar/Wind Harmer
13.92
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.085
962861AG1-135 GEN
Solar/Wind Harmer
6.647
3141726DUNNSVL
Solar/Wind Harmer
0.786
3150351NORNECKC2
Adder
1.901
972003AH1-546 GEN
Solar/Wind Harmer
8.083
971377AH1-170 GEN
Solar/Wind Harmer
1.823
3147623JAMES R
Solar/Wind Harmer
0.396
316337AD2-073 GEN
Solar/Wind Harmer
0.146
970223AG2-152 GEN
Solar/Wind Harmer
10.672
270016AE1-250 BESS
Solar/Wind Harmer
0.004
3147123OTTER R
Solar/Wind Harmer
0.084
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.104
3146802CHATHAM
Solar/Wind Harmer
0.098
941801AE2-185 GEN
Solar/Wind Harmer
4.176
972277AH1-723 GEN
Adder
76.921
270030AE2-140 GEN
Solar/Wind Harmer
12.711
316045AC1-158 PL2
Solar/Wind Helper
7.036
3147666LOUISA
Solar/Wind Helper
1.244
316192AB2-158 GEN
Solar/Wind Helper
2.045
316254AC1-120 GEN1
Solar/Wind Helper
1.287
316006AB2-029 C
Solar/Wind Helper
0.13
315785AD2-033 C
Solar/Wind Harmer
2.056
961601AG1-000A GEN
Solar/Wind Harmer
17.946
3145543BTLEBRO
Solar/Wind Harmer
0.252
3145543BTLEBRO
Solar/Wind Harmer
0.252
971623AH1-311 GEN
Solar/Wind Harmer
0.505
970257AG2-171 GEN
Solar/Wind Harmer
8.061
959311AF2-222 GEN
Solar/Wind Harmer
22.323
963181AG1-167 GEN
Solar/Wind Harmer
0.987
3144293JTRSVLE
Adder
0.785
3147133PAMPLIN
Solar/Wind Harmer
0.769
971193AH1-056 GEN
Solar/Wind Harmer
14.916
3141843SHACKLE
Adder
1.244
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.005
3141766HARMONY
Solar/Wind Harmer
3.224
316156AD2-030 GEN
Solar/Wind Harmer
0.179
3141873WAN 176
Solar/Wind Harmer
4.293
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
10.242
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3142416OLDCHRC
Solar/Wind Harmer
2.323
3146926FARMVIL
Solar/Wind Harmer
0.141
971683AH1-343 GEN
Solar/Wind Harmer
8.112
962971AG1-146 GEN
Solar/Wind Harmer
3.502
316283AC2-100 C
Solar/Wind Harmer
0.428
316473AC1-191 GEN
Solar/Wind Harmer
0.734
970009AG2-005 GEN
Solar/Wind Harmer
1.596
3146776BUCKING
Solar/Wind Harmer
0.076
316404AE1-155 C
Solar/Wind Harmer
0.046
3150351NORNECKC2
Adder
1.933
970221AG2-151 GEN
Solar/Wind Harmer
9.113
971781AH1-399 GEN
Solar/Wind Harmer
0.197
3141906WESTMOR
Solar/Wind Harmer
0.057
270197AD1-017 GEN1
Solar/Wind Harmer
0.888
270018AE2-047 C O1
Solar/Wind Harmer
0.003
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.176
972255AH1-712 GEN
Adder
66.009
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
970533AG2-339 GEN
50/50
30.786
970531AG2-338 GEN
50/50
12.314
315242AE2-183_GT2
50/50
5.558
315241AE2-183_GT1
50/50
5.524
972185AH1-677 GEN
50/50
20.036
3151041BRUNSWICKG3
50/50
4.373
972187AH1-678 GEN
50/50
10.036
3150991CHESPKB
50/50
3.415
3150991CHESPKB
50/50
3.333
971223AH1-071 GEN
Solar/Wind Harmer
3.931
3143526WINTERP
Solar/Wind Harmer
1.742
970933AG2-581 GEN
Solar/Wind Harmer
25.944
3144356SAPONY
Solar/Wind Harmer
2.645
316185AD1-033 GEN
Solar/Wind Harmer
0.009
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.295
3145506HICKORY
Solar/Wind Harmer
1.229
3145506HICKORY
Solar/Wind Harmer
0.737
3145506HICKORY
Solar/Wind Harmer
0.184
316036AC1-147 C
Solar/Wind Harmer
0.057
316339AD2-160 GEN
Solar/Wind Harmer
0.497
316018AA1-139 ULT2
Solar/Wind Harmer
0.008
316017AA1-139 ULT1
Solar/Wind Harmer
0.171
3137176SLIGO L2192
Solar/Wind Harmer
1.217
3146456SLIGO L269
Solar/Wind Harmer
5.409
3130086AYDLETT
Solar/Wind Harmer
1.221
3146386ELIZ CT
Solar/Wind Harmer
0.303
970657AG2-426 GEN
Solar/Wind Harmer
10.611
970657AG2-426 GEN
Solar/Wind Harmer
2.224
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.3
3146516WINFALL
Solar/Wind Harmer
0.3
3146516WINFALL
Solar/Wind Harmer
0.3
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3146626S HERTFORD
Solar/Wind Harmer
0.299
3146626S HERTFORD
Solar/Wind Harmer
0.299
970099AG2-077 GEN
Solar/Wind Harmer
31.878
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
1.308
3146376EDENTON
Solar/Wind Harmer
1.308
316240AF1-291 C
Solar/Wind Harmer
0.002
316033AB2-134 GEN
Solar/Wind Harmer
0.017
315697AD1-025 GEN
Solar/Wind Harmer
0.325
944641AF1-129 GEN
Adder
137.21
316065AD1-022 GEN
Solar/Wind Harmer
13.074
3145893MURPHYS
Solar/Wind Harmer
1.897
3145893MURPHYS
Solar/Wind Harmer
0.51
3146173TUNIS
Solar/Wind Harmer
0.281
3146173TUNIS
Solar/Wind Harmer
0.281
316181AB2-040 GEN
Solar/Wind Harmer
0.407
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3142666NORTHAMPTON
Solar/Wind Harmer
0.167
316426AA2-053 GEN
Solar/Wind Harmer
0.935
3145593CAROLNA
Solar/Wind Harmer
0.276
3145593CAROLNA
Solar/Wind Harmer
0.276
966811AG1-552 GEN
Solar/Wind Harmer
2.997
3145593CAROLNA
Solar/Wind Harmer
0.344
3145796HORNRTN
Solar/Wind Harmer
0.825
3145783HORNRTN
Solar/Wind Harmer
4.886
3145783HORNRTN
Solar/Wind Harmer
3.909
3145783HORNRTN
Solar/Wind Harmer
1.222
3145783HORNRTN
Solar/Wind Harmer
0.489
316274AC1-208 GEN
Solar/Wind Harmer
1.384
3145933PARMELE
Solar/Wind Harmer
0.531
3145933PARMELE
Solar/Wind Harmer
0.265
3142946ENON
Solar/Wind Harmer
0.026
971741AH1-377 GEN
Solar/Wind Harmer
26.27
939181AE1-148 GEN
Solar/Wind Harmer
12.567
3142366NRTHEST
Adder
0.844
313527AB2-043 GEN
Solar/Wind Harmer
0.003
970301AG2-198 GEN
Solar/Wind Harmer
10.992
3150691DARBY 3
Adder
18.496
3150701DARBY 4
Adder
18.453
3150681DARBY 2
Adder
18.432
3150671DARBY 1
Adder
18.41
3145493TOT1
Solar/Wind Harmer
0.592
3145453TOT5
Solar/Wind Harmer
0.355
3145603CNETO
Solar/Wind Harmer
0.237
961601AG1-000A GEN
Solar/Wind Harmer
4.486
316263AC1-034 GEN
Solar/Wind Harmer
9.586
316075AC2-137 C
Solar/Wind Harmer
0.069
970323AG2-213 GEN
Solar/Wind Harmer
10.747
971775AH1-396 GEN
Solar/Wind Harmer
0.403
316034AC1-036 C
Solar/Wind Harmer
0.018
962561AG1-105 GEN
Solar/Wind Harmer
11.957
964791AG1-342 GEN
Solar/Wind Harmer
4.752
3146843MT LREL
Solar/Wind Harmer
0.247
3146843MT LREL
Solar/Wind Harmer
0.247
958211AF2-115 GEN
Solar/Wind Harmer
2.961
963191AG1-168 GEN
Solar/Wind Harmer
0.987
3144293JTRSVLE
Adder
0.785
3144293JTRSVLE
Adder
0.661
3147133PAMPLIN
Solar/Wind Harmer
0.245
3147133PAMPLIN
Solar/Wind Harmer
0.196
3142296MT RD221
Adder
0.748
316222AC1-221 GEN
Solar/Wind Harmer
0.912
966871AG1-558 GEN
Solar/Wind Harmer
0.251
3146776BUCKING
Solar/Wind Harmer
0.848
3146776BUCKING
Solar/Wind Harmer
0.069
958261AF2-120 GEN
Solar/Wind Harmer
6.796
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.997
3150341NORNECKC1
Adder
1.981
942751AE2-291 GEN
Solar/Wind Harmer
9.768
971489AH1-241 GEN
Solar/Wind Harmer
9.113
316468AD1-105 GEN
Solar/Wind Harmer
-0.049
270013AE1-250 PV
Solar/Wind Harmer
0.004
315821AE2-092 GEN
Solar/Wind Harmer
0.008
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.248
316447AC1-158 HLD
Solar/Wind Helper
4.837
315651AD1-115 GEN
Solar/Wind Helper
0.937
226929AD2-058 GEN
Solar/Wind Helper
0.091
970737AG2-469 GEN
Solar/Wind Harmer
5.167
958131AF2-107 GEN
Solar/Wind Harmer
3.333
316044AC1-158 PL1
Solar/Wind Helper
2.198
316450AC1-158 RIC
Solar/Wind Helper
0.586
3147666LOUISA
Solar/Wind Helper
0.715
316170AC1-121 GEN2
Solar/Wind Helper
0.429
3141196NOKESVL
Solar/Wind Helper
1.038
3132273ORANGE
Solar/Wind Helper
0.047
227287AC2-120 GEN
Solar/Wind Helper
0.311
226910AB2-157 C
Solar/Wind Helper
0.013
316123AC1-075 GEN
Solar/Wind Harmer
0.262
970165AG2-112 GEN
Solar/Wind Harmer
1.554
970163AG2-111 GEN
Solar/Wind Harmer
1.483
3141813NORNECK
Solar/Wind Harmer
0.191
972205AH1-687 GEN
Adder
7.916
971447AH1-217 GEN
Solar/Wind Harmer
4.969
270494AE1-108_GEN
Solar/Wind Harmer
1.845
972189AH1-679 GEN
Adder
2.488
316223AC1-118
Solar/Wind Harmer
0.103
972193AH1-681 GEN
Adder
2.949
316164AC1-076 GEN
Solar/Wind Helper
1.496
316411AF1-147_GEN1
Solar/Wind Helper
0.807
316415AF1-147_GEN2
Solar/Wind Helper
0.807
3138216PACIFIC
Solar/Wind Helper
0.039
LAGNLTFEXP_LAGN->PJM
CLTF
12.487
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.918
TVALTFEXP_TVA->PJM
CLTF
6.285
NYPJM->LTFIMP_NY
CLTF
3.567
LGEELTFEXP_LGEE->PJM
CLTF
2.341
WECLTFEXP_WEC->PJM
CLTF
1.189
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.096
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.504
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.654
MECLTFEXP_MEC->PJM
CLTF
6.28
SIGELTFEXP_SIGE->PJM
CLTF
0.191
CPLELTFEXP_CPLE->PJM
CLTF
16.793
CBM West 2LTFEXP_CBM-W2->PJM
CBM
66.855

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.69 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4402.07
MW Contribution:6.31
Bus #Bus NameTypeMW Contribution
970119AG2-088 GEN
50/50
43.39
315243AE2-183_GT3
50/50
5.306
3151051BRUNSWICKS1
50/50
8.655
3151021BRUNSWICKG1
50/50
4.17
971451AH1-221 GEN
50/50
12.666
3150981CHESPKA
50/50
3.862
3152331SURRY 2
50/50
11.978
940641AE2-051 GEN
Solar/Wind Harmer
26.972
939411AE1-173 GEN
Solar/Wind Harmer
139.157
3143226MDLTHAN
Solar/Wind Harmer
0.325
970919AG2-571 GEN
Solar/Wind Harmer
10.802
970087AG2-069 GEN
Solar/Wind Harmer
24.19
316294AC1-161 GEN
Solar/Wind Harmer
5.215
944591AF1-124 GEN
Solar/Wind Harmer
66.808
316375AC2-012 GEN
Solar/Wind Harmer
0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.912
3146456SLIGO L269
Solar/Wind Harmer
0.29
316246AF1-032 C
Solar/Wind Harmer
0.13
316093AE2-104_GEN
Solar/Wind Harmer
4.794
3146516WINFALL
Solar/Wind Harmer
0.92
3146516WINFALL
Solar/Wind Harmer
0.284
316072AD1-144
Solar/Wind Harmer
0.103
3143526WINTERP
Solar/Wind Harmer
1.47
957481AF2-042 GEN
Solar/Wind Harmer
74.795
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.277
3145336SMITFLD
Solar/Wind Harmer
1.108
970661AG2-428 GEN
Solar/Wind Harmer
27.311
316381AD1-082 GEN
Solar/Wind Harmer
0.284
3145663CRESWEL
Solar/Wind Harmer
0.761
971163AH1-040 GEN
Solar/Wind Harmer
21.769
970659AG2-427 GEN
Solar/Wind Harmer
13.13
315693AD1-088 GEN
Solar/Wind Harmer
12.923
316023GEN1_S
Solar/Wind Harmer
0.603
3151171GRAVELC
Adder
2.853
962491AG1-098 GEN
Solar/Wind Harmer
15.256
3146206CASHIE
Solar/Wind Harmer
0.265
971547AH1-271 GEN
Solar/Wind Harmer
5.655
3138126ROCKLANDING
Solar/Wind Harmer
0.121
3145893MURPHYS
Solar/Wind Harmer
1.056
3145893MURPHYS
Solar/Wind Harmer
1.174
961611AG1-000B GEN
Solar/Wind Harmer
13.793
3146173TUNIS
Solar/Wind Harmer
0.262
960081AF2-299 GEN
Solar/Wind Harmer
2.514
3145683EARLEYS
Solar/Wind Harmer
0.26
3146263WOODLND
Solar/Wind Harmer
0.259
971647AH1-324 GEN
Solar/Wind Harmer
11.046
316011AB1-132 GEN
Solar/Wind Harmer
4.685
962571AG1-106 GEN
Solar/Wind Harmer
3.666
316190AA2-174 GEN
Solar/Wind Harmer
0
971795AH1-408 GEN
Solar/Wind Harmer
17.096
3145963POPLR C
Solar/Wind Harmer
0.256
971317AH1-138 GEN
Solar/Wind Harmer
1.913
3145823KELFORD
Solar/Wind Harmer
0.256
3143336POWHATN
Solar/Wind Harmer
4.523
316174AB2-169 GEN
Solar/Wind Harmer
0.007
3145783HORNRTN
Solar/Wind Harmer
0.254
3145796HORNRTN
Solar/Wind Harmer
0.838
3145796HORNRTN
Solar/Wind Harmer
0.254
3147043LAWRENC
Adder
2.297
971069AG2-661 GEN
Solar/Wind Harmer
4.473
315687AD1-152 GEN
Solar/Wind Harmer
0.008
316159AE1-175 C
Solar/Wind Harmer
0.215
316212AC1-099_GEN
Solar/Wind Harmer
1.283
316458AB2-190 GEN2
Solar/Wind Harmer
1.325
3146293MARTNCO
Solar/Wind Harmer
0.229
316129AC1-054 GEN
Solar/Wind Harmer
0.928
970129AG2-093 GEN
Solar/Wind Harmer
7.001
971065AG2-659 GEN
Solar/Wind Harmer
10.492
315671AE2-027_GEN
Solar/Wind Harmer
15.643
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
315722AD1-056 GEN
Solar/Wind Harmer
1.533
3150851SPRUNCC
Adder
1.101
316494AC1-189 GEN
Solar/Wind Harmer
0.807
3146233WITAKRS
Solar/Wind Harmer
0.94
961671AG1-007 GEN
Solar/Wind Harmer
0.036
3146083TARBORO
Solar/Wind Harmer
0.236
3145493TOT1
Solar/Wind Harmer
1.049
316336AC2-165 C
Solar/Wind Harmer
0.009
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3145543BTLEBRO
Solar/Wind Harmer
0.232
3145543BTLEBRO
Solar/Wind Harmer
0.186
316359AB2-059 GEN
Solar/Wind Harmer
0.835
316049AB1-081 GEN
Solar/Wind Harmer
1.331
3142053HEARTS
Solar/Wind Harmer
0.409
970401AG2-262 GEN
Solar/Wind Harmer
1.326
970685AG2-442 GEN
Solar/Wind Harmer
16.767
944631AF1-128 GEN
Adder
106.166
963171AG1-166 GEN
Solar/Wind Harmer
1.18
971563AH1-280 GEN
Solar/Wind Harmer
2.361
3144293JTRSVLE
Adder
0.705
3142543TWELFTH
Solar/Wind Harmer
0.021
971777AH1-397 GEN
Solar/Wind Harmer
0.569
3141843SHACKLE
Adder
1.102
3143096IRON208
Adder
0.902
3141766HARMONY
Solar/Wind Harmer
0.043
3142433PROV 92
Solar/Wind Harmer
0.86
3142433PROV 92
Adder
0.418
3142433PROV 92
Adder
0.418
3138133OCRAN
Solar/Wind Harmer
0.125
316003AC1-222 GEN
Solar/Wind Harmer
0.006
3146926FARMVIL
Solar/Wind Harmer
0.123
970937AG2-583 GEN
Solar/Wind Harmer
11.537
962861AG1-135 GEN
Solar/Wind Harmer
5.983
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.072
3141726DUNNSVL
Solar/Wind Harmer
0.706
3150351NORNECKC2
Adder
1.716
3142416OLDCHRC
Solar/Wind Harmer
0.416
3142416OLDCHRC
Solar/Wind Harmer
0.159
972003AH1-546 GEN
Solar/Wind Harmer
6.522
316337AD2-073 GEN
Solar/Wind Harmer
0.133
971377AH1-170 GEN
Solar/Wind Harmer
1.41
3151031BRUNSWICKG2
50/50
4.17
3151101ELIZAR3
50/50
28.777
3151161SURRY 1
50/50
10.302
970917AG2-570 GEN
Solar/Wind Harmer
27.004
315773AC2-141 GEN
Solar/Wind Harmer
10.994
944581AF1-123 GEN
Solar/Wind Harmer
66.571
944601AF1-125 GEN
Solar/Wind Harmer
65.546
3144873MCLAUGH
Solar/Wind Harmer
0.007
3146456SLIGO L269
Solar/Wind Harmer
0.29
971153AH1-033 GEN
Solar/Wind Harmer
3.357
316320Y1-086
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.043
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.284
3146626S HERTFORD
Solar/Wind Harmer
0.282
3145273HOLLAND
Solar/Wind Harmer
0.209
3146376EDENTON
Solar/Wind Harmer
0.277
3145336SMITFLD
Solar/Wind Harmer
0.111
970661AG2-428 GEN
Solar/Wind Harmer
5.809
316083AB2-161 GEN
Solar/Wind Harmer
0.004
315614AA2-178 GEN
Solar/Wind Harmer
1.557
970659AG2-427 GEN
Solar/Wind Harmer
2.872
316365GEN2_N
Solar/Wind Harmer
0.603
3151221GRAVEL6
Adder
19.5
3151171GRAVELC
Adder
3.752
971157AH1-035 GEN
Solar/Wind Harmer
3.217
315813AE1-149 C
Solar/Wind Harmer
14.26
315737AD1-076 GEN
Solar/Wind Harmer
3.44
316478AD1-087 GEN
Solar/Wind Harmer
0.932
316486AD2-202 GEN
Solar/Wind Harmer
0.274
3156081AA2-088 GEN
Solar/Wind Harmer
0.006
3146206CASHIE
Solar/Wind Harmer
0.265
3144216WINCHST
Adder
0.999
3145893MURPHYS
Solar/Wind Harmer
0.442
3145893MURPHYS
Solar/Wind Harmer
0.264
3150921YORKTN3
Adder
6.638
957521AF2-046 GEN
Solar/Wind Harmer
19.613
961681AG1-008 GEN
Solar/Wind Harmer
19.613
961611AG1-000B GEN
Solar/Wind Harmer
7.014
3146173TUNIS
Solar/Wind Harmer
0.262
3156021HOLLOMANSOL
Solar/Wind Harmer
1.189
316463AE2-346 GEN
Solar/Wind Harmer
0.224
316140AB2-099
Solar/Wind Harmer
0.093
962331AG1-082 GEN
Solar/Wind Harmer
2.786
3146263WOODLND
Solar/Wind Harmer
0.259
313506AB2-031 GEN
Solar/Wind Harmer
0.8
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
3145963POPLR C
Solar/Wind Harmer
0.256
316317KELFORD C
Solar/Wind Harmer
0.025
3145823KELFORD
Solar/Wind Harmer
0.256
316313AB2-026
Solar/Wind Harmer
0.16
316258AE1-075 C
Solar/Wind Harmer
0.192
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.845
3145796HORNRTN
Solar/Wind Harmer
1.016
3145796HORNRTN
Solar/Wind Harmer
0.254
3147043LAWRENC
Solar/Wind Harmer
0.152
315839AE2-212 C
Solar/Wind Harmer
0.002
315778AD1-151 GEN
Solar/Wind Harmer
20.127
316382AG1-145 C
Solar/Wind Harmer
0.002
965281AG1-393 GEN
Solar/Wind Harmer
2.647
316210AC1-098 GEN
Solar/Wind Harmer
2.301
3145933PARMELE
Solar/Wind Harmer
0.247
966801AG1-551 GEN
Solar/Wind Harmer
2.873
970129AG2-093 GEN
Solar/Wind Harmer
14.877
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
315724AD1-057 GEN
Solar/Wind Harmer
0.909
316327AA2-057 GEN
Solar/Wind Harmer
0.363
3150861SPRUNCD
Adder
1.101
970133AG2-095 GEN
Solar/Wind Harmer
2.289
3146233WITAKRS
Solar/Wind Harmer
1.186
3146233WITAKRS
Solar/Wind Harmer
0.161
3146073TAR RVR
Solar/Wind Harmer
0.236
3146083TARBORO
Solar/Wind Harmer
0.236
3138543CONSLDL
Solar/Wind Harmer
0.156
316131AB2-060 GEN
Solar/Wind Harmer
0.739
964241AG1-285 GEN
Solar/Wind Harmer
15.529
970909AG2-566 GEN
Solar/Wind Harmer
2.481
961601AG1-000A GEN
Solar/Wind Harmer
16.539
3145543BTLEBRO
Solar/Wind Harmer
0.232
3145543BTLEBRO
Solar/Wind Harmer
0.232
971623AH1-311 GEN
Solar/Wind Harmer
0.465
315785AD2-033 C
Solar/Wind Harmer
1.864
970257AG2-171 GEN
Solar/Wind Harmer
7.295
959311AF2-222 GEN
Solar/Wind Harmer
20.178
3142946ENON
Solar/Wind Harmer
0.074
963181AG1-167 GEN
Solar/Wind Harmer
0.885
3144293JTRSVLE
Adder
0.705
3147133PAMPLIN
Solar/Wind Harmer
0.687
316303AF2-085
50/50
5.785
315244AE2-183_ST
50/50
9.174
963041AG1-153 GEN
50/50
8.444
3151081ELIZAR1
50/50
28.413
3151091ELIZAR2
50/50
27.92
941591AE2-156 GEN
50/50
25.939
3152611GOSPORTB
50/50
3.939
3152621GOSPORTC
50/50
3.343
3152601GOSPORTA
50/50
3.084
315779AE2-040
50/50
4.048
972263AH1-716 GEN
50/50
164.964
941031AE2-094 GEN
Solar/Wind Harmer
61.065
944011AF1-069 GEN
Solar/Wind Harmer
19.952
970673AG2-436 GEN
Solar/Wind Harmer
69.269
970673AG2-436 GEN
Solar/Wind Harmer
46.179
971967AH1-528 GEN
Solar/Wind Harmer
50.977
970085AG2-068 GEN
Solar/Wind Harmer
16.126
970581AG2-369 GEN
Solar/Wind Harmer
13.869
957871AF2-081 GEN
Solar/Wind Harmer
14.487
319010AE1-072 C
Solar/Wind Harmer
1.462
3146406KITTY HAWK
Solar/Wind Harmer
0.036
316315AB2-025 C
Solar/Wind Harmer
0.234
315814AE2-033 C
Solar/Wind Harmer
22.859
316305AF2-043 C
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.156
316321Z2-027
Solar/Wind Harmer
0.053
3146396TANGLEW
Solar/Wind Harmer
0.789
3145176PASQUOTANK
Solar/Wind Harmer
0.177
3146486SUNBURY
Solar/Wind Harmer
0.286
3146486SUNBURY
Solar/Wind Harmer
0.286
315835AF2-110_GEN
Solar/Wind Harmer
1.956
316233AE1-074 FULL
Solar/Wind Harmer
0.226
971281AH1-106 GEN
Solar/Wind Harmer
3.922
971283AH1-107 GEN
Solar/Wind Harmer
3.922
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
316311AC2-079 GEN
Solar/Wind Harmer
8.046
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.192
3130156CHOWAN
Solar/Wind Harmer
0.277
3130156CHOWAN
Solar/Wind Harmer
0.277
971445AH1-216 GEN
Solar/Wind Harmer
19.461
3143316POE
Solar/Wind Harmer
1.085
315816AE2-034 GEN
Solar/Wind Harmer
1.168
972265AH1-717 GEN
Adder
20.825
3151201GRAVEL4
Adder
19.522
3151191GRAVEL3
Adder
19.275
3151211GRAVEL5
Adder
19.275
3130546PLYMOUTH
Solar/Wind Harmer
0.268
315732AD1-074 GEN1
Solar/Wind Harmer
1.536
315733AD1-074 GEN2
Solar/Wind Harmer
1.536
315735AD1-075 GEN1
Solar/Wind Harmer
0.769
965291AG1-394 GEN
Solar/Wind Harmer
1.182
3146206CASHIE
Solar/Wind Harmer
0.265
970601AG2-382 GEN
Solar/Wind Harmer
9.896
3145893MURPHYS
Solar/Wind Harmer
0.713
3145893MURPHYS
Solar/Wind Harmer
0.264
3145513AHOSKIE
Solar/Wind Harmer
0.546
3145513AHOSKIE
Solar/Wind Harmer
0.261
3146043SEABORD
Solar/Wind Harmer
0.26
3145683EARLEYS
Solar/Wind Harmer
0.52
3145683EARLEYS
Solar/Wind Harmer
0.26
3145683EARLEYS
Solar/Wind Harmer
0.26
316087AB2-174 GEN
Solar/Wind Harmer
0.007
315607AA1-063A GEN
Solar/Wind Harmer
0.531
315652AC1-086 GEN
Solar/Wind Harmer
28.344
3137643SOCKMAN
Solar/Wind Harmer
1.027
971193AH1-056 GEN
Solar/Wind Harmer
13.34
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.346
316156AD2-030 GEN
Solar/Wind Harmer
0.16
3141873WAN 176
Solar/Wind Harmer
3.848
316280AD1-041 GEN
Solar/Wind Harmer
0.004
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141843SHACKLE
Adder
1.102
3143096IRON208
Adder
0.902
3143096IRON208
Adder
0.884
3141766HARMONY
Solar/Wind Harmer
2.867
3142433PROV 92
Adder
0.418
3142433PROV 92
Adder
0.418
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.123
316283AC2-100 C
Solar/Wind Harmer
0.389
971683AH1-343 GEN
Solar/Wind Harmer
7.294
962971AG1-146 GEN
Solar/Wind Harmer
3.148
970293AG2-193 GEN
Solar/Wind Harmer
2.064
970009AG2-005 GEN
Solar/Wind Harmer
1.436
316404AE1-155 C
Solar/Wind Harmer
0.042
3146776BUCKING
Solar/Wind Harmer
0.065
3150351NORNECKC2
Adder
1.745
3142416OLDCHRC
Solar/Wind Harmer
1.55
3141906WESTMOR
Solar/Wind Harmer
0.053
970221AG2-151 GEN
Solar/Wind Harmer
7.048
316473AC1-191 GEN
Solar/Wind Harmer
0.412
970737AG2-469 GEN
Solar/Wind Harmer
4.87
316044AC1-158 PL1
Solar/Wind Helper
1.723
316450AC1-158 RIC
Solar/Wind Helper
0.459
3147666LOUISA
Solar/Wind Helper
0.596
316369SG1_INVT
Solar/Wind Harmer
0.01
3145796HORNRTN
Solar/Wind Harmer
0.813
3145796HORNRTN
Solar/Wind Harmer
0.102
3146033SCOT NK
Solar/Wind Harmer
1.006
970831AG2-522 GEN
Solar/Wind Harmer
10.563
316132AB2-190 GEN1
Solar/Wind Harmer
1.325
316005AA1-067
Solar/Wind Harmer
0.26
3145746EVERETS
Solar/Wind Harmer
0.964
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
970181AG2-120 GEN
Solar/Wind Harmer
3.014
3138283WHITEMARSH
Solar/Wind Harmer
0.056
971285AH1-108 GEN
Adder
1.802
957861AF2-080 GEN
Solar/Wind Harmer
10.3
316420AA1-050 GEN
Solar/Wind Harmer
0.008
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.236
3145573BETHELC
Solar/Wind Harmer
0.236
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
3.835
3144303KENBRDG
Solar/Wind Harmer
0.182
970683AG2-441 GEN
Solar/Wind Harmer
14.971
970681AG2-440 GEN
Solar/Wind Harmer
11.976
316118AC1-105 GEN
Solar/Wind Harmer
0.574
946301AF1-294 GEN
Solar/Wind Harmer
4.367
961791AG1-021 GEN
Solar/Wind Harmer
2.125
315657AE1-056 GEN
Solar/Wind Harmer
7.556
3147173SINAI
Solar/Wind Harmer
0.219
3147243WELCO
Solar/Wind Harmer
0.137
315976AC1-164 GENA
Solar/Wind Harmer
22.6
316169AC1-164_GENC
Solar/Wind Harmer
19.524
315975AC1-164 GENB
Solar/Wind Harmer
0.669
3141873WAN 176
Solar/Wind Harmer
0.043
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
970189AG2-124 GEN
Solar/Wind Harmer
6.392
971167AH1-042 GEN
Solar/Wind Harmer
19.104
316059AD1-063 C
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.418
3142433PROV 92
Adder
0.418
3143873LANEXA
Solar/Wind Harmer
0.129
316314AB2-024 C
Solar/Wind Harmer
0.001
3141913WHIT STONE
Solar/Wind Harmer
0.21
3138133OCRAN
Solar/Wind Harmer
0.062
3141783LANCAST
Solar/Wind Harmer
0.123
3141783LANCAST
Solar/Wind Harmer
0.082
962981AG1-147 GEN
Solar/Wind Harmer
7.345
970327AG2-215 GEN
Solar/Wind Harmer
6.31
970865AG2-541 GEN
Solar/Wind Harmer
6.523
970285AG2-188 GEN
Solar/Wind Harmer
14.703
971845AH1-439 GEN
Solar/Wind Harmer
8.235
3141813NORNECK
Solar/Wind Harmer
0.172
316123AC1-075 GEN
Solar/Wind Harmer
0.229
970165AG2-112 GEN
Solar/Wind Harmer
1.36
970163AG2-111 GEN
Solar/Wind Harmer
1.297
316312AB1-027
Solar/Wind Harmer
0.286
972205AH1-687 GEN
Adder
6.309
316223AC1-118
Solar/Wind Harmer
0.095
971447AH1-217 GEN
Solar/Wind Harmer
3.746
270494AE1-108_GEN
Solar/Wind Harmer
1.403
316164AC1-076 GEN
Solar/Wind Helper
1.139
970533AG2-339 GEN
50/50
29.471
970531AG2-338 GEN
50/50
11.789
315242AE2-183_GT2
50/50
5.306
315241AE2-183_GT1
50/50
5.273
972185AH1-677 GEN
50/50
19.129
3151041BRUNSWICKG3
50/50
4.17
972187AH1-678 GEN
50/50
9.57
3150991CHESPKB
50/50
3.24
3150991CHESPKB
50/50
3.162
971223AH1-071 GEN
Solar/Wind Harmer
3.471
970933AG2-581 GEN
Solar/Wind Harmer
24.629
316185AD1-033 GEN
Solar/Wind Harmer
0.008
3145506HICKORY
Solar/Wind Harmer
1.168
3145506HICKORY
Solar/Wind Harmer
0.701
3145506HICKORY
Solar/Wind Harmer
0.175
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.28
316036AC1-147 C
Solar/Wind Harmer
0.054
316339AD2-160 GEN
Solar/Wind Harmer
0.472
316018AA1-139 ULT2
Solar/Wind Harmer
0.007
316017AA1-139 ULT1
Solar/Wind Harmer
0.162
3137176SLIGO L2192
Solar/Wind Harmer
1.156
3146456SLIGO L269
Solar/Wind Harmer
5.139
3130086AYDLETT
Solar/Wind Harmer
1.16
3144356SAPONY
Solar/Wind Harmer
2.426
3146386ELIZ CT
Solar/Wind Harmer
0.287
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.284
3146516WINFALL
Solar/Wind Harmer
0.284
3146516WINFALL
Solar/Wind Harmer
0.284
3143526WINTERP
Solar/Wind Harmer
1.47
3146626S HERTFORD
Solar/Wind Harmer
0.282
3146626S HERTFORD
Solar/Wind Harmer
0.282
970099AG2-077 GEN
Solar/Wind Harmer
29.918
3146376EDENTON
Solar/Wind Harmer
1.233
3146376EDENTON
Solar/Wind Harmer
1.233
316236AE1-162_GEN
Solar/Wind Harmer
0.002
315742AE1-103 GEN
Solar/Wind Harmer
0.003
970657AG2-426 GEN
Solar/Wind Harmer
9.567
970657AG2-426 GEN
Solar/Wind Harmer
2.006
316065AD1-022 GEN
Solar/Wind Harmer
12.243
3145893MURPHYS
Solar/Wind Harmer
1.767
3145893MURPHYS
Solar/Wind Harmer
0.475
3146173TUNIS
Solar/Wind Harmer
0.262
3146173TUNIS
Solar/Wind Harmer
0.262
316181AB2-040 GEN
Solar/Wind Harmer
0.376
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
316426AA2-053 GEN
Solar/Wind Harmer
0.866
3145593CAROLNA
Solar/Wind Harmer
0.255
3145593CAROLNA
Solar/Wind Harmer
0.255
966811AG1-552 GEN
Solar/Wind Harmer
2.773
3145593CAROLNA
Solar/Wind Harmer
0.318
316033AB2-134 GEN
Solar/Wind Harmer
0.015
315697AD1-025 GEN
Solar/Wind Harmer
0.287
3145783HORNRTN
Solar/Wind Harmer
4.52
3145783HORNRTN
Solar/Wind Harmer
3.616
3145783HORNRTN
Solar/Wind Harmer
1.13
3145783HORNRTN
Solar/Wind Harmer
0.452
3145796HORNRTN
Solar/Wind Harmer
0.762
3145933PARMELE
Solar/Wind Harmer
0.493
3145933PARMELE
Solar/Wind Harmer
0.247
316274AC1-208 GEN
Solar/Wind Harmer
1.28
971741AH1-377 GEN
Solar/Wind Harmer
23.908
939181AE1-148 GEN
Solar/Wind Harmer
11.558
316240AF1-291 C
Solar/Wind Harmer
0.002
3145493TOT1
Solar/Wind Harmer
0.547
3145453TOT5
Solar/Wind Harmer
0.328
3145603CNETO
Solar/Wind Harmer
0.219
313527AB2-043 GEN
Solar/Wind Harmer
0.003
944641AF1-129 GEN
Adder
111.535
970301AG2-198 GEN
Solar/Wind Harmer
9.924
961601AG1-000A GEN
Solar/Wind Harmer
4.135
316263AC1-034 GEN
Solar/Wind Harmer
8.835
970323AG2-213 GEN
Solar/Wind Harmer
9.727
971775AH1-396 GEN
Solar/Wind Harmer
0.365
316034AC1-036 C
Solar/Wind Harmer
0.017
962561AG1-105 GEN
Solar/Wind Harmer
10.919
964791AG1-342 GEN
Solar/Wind Harmer
4.339
3146843MT LREL
Solar/Wind Harmer
0.226
3146843MT LREL
Solar/Wind Harmer
0.226
3142946ENON
Solar/Wind Harmer
0.022
958211AF2-115 GEN
Solar/Wind Harmer
2.656
963191AG1-168 GEN
Solar/Wind Harmer
0.885
3144293JTRSVLE
Adder
0.705
3144293JTRSVLE
Adder
0.593
3147133PAMPLIN
Solar/Wind Harmer
0.219
3147133PAMPLIN
Solar/Wind Harmer
0.175
316075AC2-137 C
Solar/Wind Harmer
0.055
316222AC1-221 GEN
Solar/Wind Harmer
0.83
3150691DARBY 3
Adder
13.407
3150701DARBY 4
Adder
13.376
3150681DARBY 2
Adder
13.36
3150671DARBY 1
Adder
13.345
958261AF2-120 GEN
Solar/Wind Harmer
6.119
3142366NRTHEST
Adder
0.595
3146776BUCKING
Solar/Wind Harmer
0.717
3146776BUCKING
Solar/Wind Harmer
0.058
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.803
3150341NORNECKC1
Adder
1.788
942751AE2-291 GEN
Solar/Wind Harmer
8.42
971489AH1-241 GEN
Solar/Wind Harmer
7.048
3142296MT RD221
Adder
0.414
270013AE1-250 PV
Solar/Wind Harmer
0.004
966871AG1-558 GEN
Solar/Wind Harmer
0.141
316447AC1-158 HLD
Solar/Wind Helper
3.792
3147623JAMES R
Solar/Wind Harmer
0.306
970223AG2-152 GEN
Solar/Wind Harmer
9.004
270016AE1-250 BESS
Solar/Wind Harmer
0.004
3147123OTTER R
Solar/Wind Harmer
0.068
316045AC1-158 PL2
Solar/Wind Helper
5.515
3147666LOUISA
Solar/Wind Helper
1.037
316192AB2-158 GEN
Solar/Wind Helper
1.708
LAGNLTFEXP_LAGN->PJM
CLTF
10.194
CBM South 2LTFEXP_CBM-S2->PJM
CBM
32.592
TVALTFEXP_TVA->PJM
CLTF
5.103
NYPJM->LTFIMP_NY
CLTF
2.749
LGEELTFEXP_LGEE->PJM
CLTF
1.702
WECLTFEXP_WEC->PJM
CLTF
0.865
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.866
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.385
MECLTFEXP_MEC->PJM
CLTF
4.747
SIGELTFEXP_SIGE->PJM
CLTF
0.142
CPLELTFEXP_CPLE->PJM
CLTF
15.205
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.962

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.34 %
Rating:3193.18 MVA
Rating Type:A
MVA to Mitigate:3619.13
MW Contribution:4.3
Bus #Bus NameTypeMW Contribution
970119AG2-088 GEN
50/50
40.684
315243AE2-183_GT3
50/50
4.563
3151051BRUNSWICKS1
50/50
7.443
3151021BRUNSWICKG1
50/50
3.586
971451AH1-221 GEN
50/50
10.893
3151531CLOVER1
50/50
4.938
3143226MDLTHAN
Solar/Wind Harmer
0.305
940641AE2-051 GEN
Solar/Wind Harmer
22.672
939411AE1-173 GEN
Solar/Wind Harmer
114.479
970919AG2-571 GEN
Solar/Wind Harmer
9.287
970087AG2-069 GEN
Solar/Wind Harmer
20.797
3143526WINTERP
Solar/Wind Harmer
1.35
957481AF2-042 GEN
Solar/Wind Harmer
64.526
3143336POWHATN
Solar/Wind Harmer
4.238
315693AD1-088 GEN
Solar/Wind Harmer
11.177
962491AG1-098 GEN
Solar/Wind Harmer
13.203
316023GEN1_S
Solar/Wind Harmer
0.504
944591AF1-124 GEN
Solar/Wind Harmer
50.741
316294AC1-161 GEN
Solar/Wind Harmer
3.877
316388AE2-253 GEN
Solar/Wind Harmer
0.696
3146456SLIGO L269
Solar/Wind Harmer
0.222
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.768
316246AF1-032 C
Solar/Wind Harmer
0.1
316336AC2-165 C
Solar/Wind Harmer
0.009
316093AE2-104_GEN
Solar/Wind Harmer
3.708
970661AG2-428 GEN
Solar/Wind Harmer
21.842
316381AD1-082 GEN
Solar/Wind Harmer
0.229
960081AF2-299 GEN
Solar/Wind Harmer
2.106
970659AG2-427 GEN
Solar/Wind Harmer
10.606
3146516WINFALL
Solar/Wind Harmer
0.71
3146516WINFALL
Solar/Wind Harmer
0.219
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.216
971795AH1-408 GEN
Solar/Wind Harmer
14.392
316072AD1-144
Solar/Wind Harmer
0.078
315687AD1-152 GEN
Solar/Wind Harmer
0.007
3147043LAWRENC
Adder
1.939
3145663CRESWEL
Solar/Wind Harmer
0.599
971163AH1-040 GEN
Solar/Wind Harmer
17.112
316011AB1-132 GEN
Solar/Wind Harmer
3.881
962571AG1-106 GEN
Solar/Wind Harmer
3.037
3145893MURPHYS
Solar/Wind Harmer
0.851
3145893MURPHYS
Solar/Wind Harmer
0.946
3146173TUNIS
Solar/Wind Harmer
0.211
316190AA2-174 GEN
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.211
971547AH1-271 GEN
Solar/Wind Harmer
4.504
3145336SMITFLD
Solar/Wind Harmer
0.844
3145796HORNRTN
Solar/Wind Harmer
0.695
3145796HORNRTN
Solar/Wind Harmer
0.211
3150851SPRUNCC
Adder
0.97
3146263WOODLND
Solar/Wind Harmer
0.21
3145783HORNRTN
Solar/Wind Harmer
0.21
3145683EARLEYS
Solar/Wind Harmer
0.21
316129AC1-054 GEN
Solar/Wind Harmer
0.783
971065AG2-659 GEN
Solar/Wind Harmer
8.875
3145823KELFORD
Solar/Wind Harmer
0.208
3145963POPLR C
Solar/Wind Harmer
0.206
316174AB2-169 GEN
Solar/Wind Harmer
0.005
3151171GRAVELC
Adder
2.174
316212AC1-099_GEN
Solar/Wind Harmer
1.056
315671AE2-027_GEN
Solar/Wind Harmer
13.019
316237AB2-079_GEN
Solar/Wind Harmer
0.002
961611AG1-000B GEN
Solar/Wind Harmer
10.587
315722AD1-056 GEN
Solar/Wind Harmer
1.275
3146293MARTNCO
Solar/Wind Harmer
0.186
971647AH1-324 GEN
Solar/Wind Harmer
8.529
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
316494AC1-189 GEN
Solar/Wind Harmer
0.664
3146233WITAKRS
Solar/Wind Harmer
0.782
971069AG2-661 GEN
Solar/Wind Harmer
3.491
961671AG1-007 GEN
Solar/Wind Harmer
0.03
3146083TARBORO
Solar/Wind Harmer
0.195
3145493TOT1
Solar/Wind Harmer
0.868
970685AG2-442 GEN
Solar/Wind Harmer
14.585
970401AG2-262 GEN
Solar/Wind Harmer
1.143
316458AB2-190 GEN2
Solar/Wind Harmer
1.041
316359AB2-059 GEN
Solar/Wind Harmer
0.696
316049AB1-081 GEN
Solar/Wind Harmer
1.109
3145543BTLEBRO
Solar/Wind Harmer
0.194
3145543BTLEBRO
Solar/Wind Harmer
0.155
3142053HEARTS
Solar/Wind Harmer
0.341
970129AG2-093 GEN
Solar/Wind Harmer
5.511
963171AG1-166 GEN
Solar/Wind Harmer
1.03
971563AH1-280 GEN
Solar/Wind Harmer
2.061
3144293JTRSVLE
Adder
0.615
3138126ROCKLANDING
Solar/Wind Harmer
0.087
3142543TWELFTH
Solar/Wind Harmer
0.018
3146926FARMVIL
Solar/Wind Harmer
0.11
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971317AH1-138 GEN
Solar/Wind Harmer
1.337
970937AG2-583 GEN
Solar/Wind Harmer
10.797
3143096IRON208
Adder
0.735
316159AE1-175 C
Solar/Wind Harmer
0.149
944631AF1-128 GEN
Adder
81.311
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.065
3142433PROV 92
Solar/Wind Harmer
0.629
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
971777AH1-397 GEN
Solar/Wind Harmer
0.396
3141843SHACKLE
Adder
0.766
3141766HARMONY
Solar/Wind Harmer
0.029
3138133OCRAN
Solar/Wind Harmer
0.086
972003AH1-546 GEN
Solar/Wind Harmer
6.056
3142416OLDCHRC
Solar/Wind Harmer
0.332
3142416OLDCHRC
Solar/Wind Harmer
0.127
962861AG1-135 GEN
Solar/Wind Harmer
4.063
971377AH1-170 GEN
Solar/Wind Harmer
1.327
3147623JAMES R
Solar/Wind Harmer
0.288
3141726DUNNSVL
Solar/Wind Harmer
0.474
3150351NORNECKC2
Adder
1.153
970223AG2-152 GEN
Solar/Wind Harmer
7.902
316045AC1-158 PL2
Solar/Wind Helper
5.205
3147666LOUISA
Solar/Wind Helper
0.977
316192AB2-158 GEN
Solar/Wind Helper
1.608
3151031BRUNSWICKG2
50/50
3.586
970413AG2-270 GEN
50/50
21.547
3151101ELIZAR3
50/50
21.88
970917AG2-570 GEN
Solar/Wind Harmer
23.218
316313AB2-026
Solar/Wind Harmer
0.15
316258AE1-075 C
Solar/Wind Harmer
0.18
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.602
316478AD1-087 GEN
Solar/Wind Harmer
0.805
316486AD2-202 GEN
Solar/Wind Harmer
0.236
316365GEN2_N
Solar/Wind Harmer
0.504
944581AF1-123 GEN
Solar/Wind Harmer
50.561
944601AF1-125 GEN
Solar/Wind Harmer
49.783
315773AC2-141 GEN
Solar/Wind Harmer
8.172
3146456SLIGO L269
Solar/Wind Harmer
0.222
971153AH1-033 GEN
Solar/Wind Harmer
2.565
3144873MCLAUGH
Solar/Wind Harmer
0.006
316320Y1-086
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
4.646
316435W1029_GEN3
Solar/Wind Harmer
0.001
316083AB2-161 GEN
Solar/Wind Harmer
0.003
970659AG2-427 GEN
Solar/Wind Harmer
2.32
3146516WINFALL
Solar/Wind Harmer
0.219
315813AE1-149 C
Solar/Wind Harmer
11.679
3144536CHRHLND
Solar/Wind Harmer
0.033
3145273HOLLAND
Solar/Wind Harmer
0.164
3146626S HERTFORD
Solar/Wind Harmer
0.218
3146376EDENTON
Solar/Wind Harmer
0.216
313506AB2-031 GEN
Solar/Wind Harmer
0.667
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
3147043LAWRENC
Solar/Wind Harmer
0.129
315614AA2-178 GEN
Solar/Wind Harmer
1.224
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3145893MURPHYS
Solar/Wind Harmer
0.356
3145893MURPHYS
Solar/Wind Harmer
0.213
315839AE2-212 C
Solar/Wind Harmer
0.002
957521AF2-046 GEN
Solar/Wind Harmer
15.803
961681AG1-008 GEN
Solar/Wind Harmer
15.803
971157AH1-035 GEN
Solar/Wind Harmer
2.546
315737AD1-076 GEN
Solar/Wind Harmer
2.725
3146173TUNIS
Solar/Wind Harmer
0.211
3146206CASHIE
Solar/Wind Harmer
0.211
3145336SMITFLD
Solar/Wind Harmer
0.084
316463AE2-346 GEN
Solar/Wind Harmer
0.181
316140AB2-099
Solar/Wind Harmer
0.075
962331AG1-082 GEN
Solar/Wind Harmer
2.248
3145796HORNRTN
Solar/Wind Harmer
0.842
3145796HORNRTN
Solar/Wind Harmer
0.211
3150861SPRUNCD
Adder
0.97
3146263WOODLND
Solar/Wind Harmer
0.21
3156021HOLLOMANSOL
Solar/Wind Harmer
0.954
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.208
965281AG1-393 GEN
Solar/Wind Harmer
2.207
3145963POPLR C
Solar/Wind Harmer
0.206
3151221GRAVEL6
Adder
14.86
3151171GRAVELC
Adder
2.859
316210AC1-098 GEN
Solar/Wind Harmer
1.894
970909AG2-566 GEN
Solar/Wind Harmer
2.177
316131AB2-060 GEN
Solar/Wind Harmer
0.636
961611AG1-000B GEN
Solar/Wind Harmer
5.383
315724AD1-057 GEN
Solar/Wind Harmer
0.756
964241AG1-285 GEN
Solar/Wind Harmer
13.392
3145933PARMELE
Solar/Wind Harmer
0.2
966801AG1-551 GEN
Solar/Wind Harmer
2.335
316327AA2-057 GEN
Solar/Wind Harmer
0.301
315785AD2-033 C
Solar/Wind Harmer
1.614
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
970257AG2-171 GEN
Solar/Wind Harmer
6.323
959311AF2-222 GEN
Solar/Wind Harmer
17.507
3146233WITAKRS
Solar/Wind Harmer
0.986
3146233WITAKRS
Solar/Wind Harmer
0.134
315778AD1-151 GEN
Solar/Wind Harmer
15.709
3138543CONSLDL
Solar/Wind Harmer
0.129
3146073TAR RVR
Solar/Wind Harmer
0.195
3146083TARBORO
Solar/Wind Harmer
0.195
961601AG1-000A GEN
Solar/Wind Harmer
13.786
3145543BTLEBRO
Solar/Wind Harmer
0.194
3145543BTLEBRO
Solar/Wind Harmer
0.194
971623AH1-311 GEN
Solar/Wind Harmer
0.388
970129AG2-093 GEN
Solar/Wind Harmer
11.71
963181AG1-167 GEN
Solar/Wind Harmer
0.773
3144293JTRSVLE
Adder
0.615
3147133PAMPLIN
Solar/Wind Harmer
0.602
971193AH1-056 GEN
Solar/Wind Harmer
11.673
970133AG2-095 GEN
Solar/Wind Harmer
1.824
3144216WINCHST
Adder
0.716
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
8.068
3150921YORKTN3
Adder
4.712
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.11
3143096IRON208
Adder
0.735
3143096IRON208
Adder
0.72
316382AG1-145 C
Solar/Wind Harmer
0.001
971683AH1-343 GEN
Solar/Wind Harmer
6.321
316283AC2-100 C
Solar/Wind Harmer
0.335
3142946ENON
Solar/Wind Harmer
0.055
3146776BUCKING
Solar/Wind Harmer
0.059
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3141843SHACKLE
Adder
0.766
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.003
316156AD2-030 GEN
Solar/Wind Harmer
0.111
3141873WAN 176
Solar/Wind Harmer
2.658
970293AG2-193 GEN
Solar/Wind Harmer
1.582
3141766HARMONY
Solar/Wind Harmer
1.964
962971AG1-146 GEN
Solar/Wind Harmer
2.151
970009AG2-005 GEN
Solar/Wind Harmer
0.978
3142416OLDCHRC
Solar/Wind Harmer
1.237
316404AE1-155 C
Solar/Wind Harmer
0.028
970221AG2-151 GEN
Solar/Wind Harmer
6.633
3150351NORNECKC2
Adder
1.172
316473AC1-191 GEN
Solar/Wind Harmer
0.383
316044AC1-158 PL1
Solar/Wind Helper
1.626
316450AC1-158 RIC
Solar/Wind Helper
0.434
3147666LOUISA
Solar/Wind Helper
0.562
970533AG2-339 GEN
50/50
25.341
970531AG2-338 GEN
50/50
10.136
315242AE2-183_GT2
50/50
4.563
315241AE2-183_GT1
50/50
4.535
972185AH1-677 GEN
50/50
16.45
3151041BRUNSWICKG3
50/50
3.586
972187AH1-678 GEN
50/50
8.23
971223AH1-071 GEN
Solar/Wind Harmer
3.255
970933AG2-581 GEN
Solar/Wind Harmer
21.207
3143526WINTERP
Solar/Wind Harmer
1.35
3144356SAPONY
Solar/Wind Harmer
2.053
970099AG2-077 GEN
Solar/Wind Harmer
25.81
316185AD1-033 GEN
Solar/Wind Harmer
0.006
3145506HICKORY
Solar/Wind Harmer
0.89
3145506HICKORY
Solar/Wind Harmer
0.534
3145506HICKORY
Solar/Wind Harmer
0.134
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.213
316339AD2-160 GEN
Solar/Wind Harmer
0.36
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.124
3137176SLIGO L2192
Solar/Wind Harmer
0.883
3146456SLIGO L269
Solar/Wind Harmer
3.926
316036AC1-147 C
Solar/Wind Harmer
0.041
3130086AYDLETT
Solar/Wind Harmer
0.886
3150991CHESPKB
Adder
2.322
3150991CHESPKB
Adder
2.266
3146386ELIZ CT
Solar/Wind Harmer
0.22
970657AG2-426 GEN
Solar/Wind Harmer
7.686
970657AG2-426 GEN
Solar/Wind Harmer
1.611
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.219
3146516WINFALL
Solar/Wind Harmer
0.219
3146516WINFALL
Solar/Wind Harmer
0.219
3146626S HERTFORD
Solar/Wind Harmer
0.218
3146626S HERTFORD
Solar/Wind Harmer
0.218
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
0.961
3146376EDENTON
Solar/Wind Harmer
0.961
316181AB2-040 GEN
Solar/Wind Harmer
0.313
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.128
3145893MURPHYS
Solar/Wind Harmer
1.424
3145893MURPHYS
Solar/Wind Harmer
0.383
3145593CAROLNA
Solar/Wind Harmer
0.211
3145593CAROLNA
Solar/Wind Harmer
0.211
966811AG1-552 GEN
Solar/Wind Harmer
2.295
3145593CAROLNA
Solar/Wind Harmer
0.263
3146173TUNIS
Solar/Wind Harmer
0.211
3146173TUNIS
Solar/Wind Harmer
0.211
316065AD1-022 GEN
Solar/Wind Harmer
9.733
316426AA2-053 GEN
Solar/Wind Harmer
0.714
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3145796HORNRTN
Solar/Wind Harmer
0.632
971741AH1-377 GEN
Solar/Wind Harmer
20.897
3145783HORNRTN
Solar/Wind Harmer
3.74
3145783HORNRTN
Solar/Wind Harmer
2.992
3145783HORNRTN
Solar/Wind Harmer
0.935
3145783HORNRTN
Solar/Wind Harmer
0.374
939181AE1-148 GEN
Solar/Wind Harmer
9.88
970301AG2-198 GEN
Solar/Wind Harmer
8.706
316274AC1-208 GEN
Solar/Wind Harmer
1.058
313527AB2-043 GEN
Solar/Wind Harmer
0.003
316240AF1-291 C
Solar/Wind Harmer
0.002
3145933PARMELE
Solar/Wind Harmer
0.401
3145933PARMELE
Solar/Wind Harmer
0.2
316033AB2-134 GEN
Solar/Wind Harmer
0.012
315697AD1-025 GEN
Solar/Wind Harmer
0.223
970323AG2-213 GEN
Solar/Wind Harmer
8.431
971775AH1-396 GEN
Solar/Wind Harmer
0.316
316034AC1-036 C
Solar/Wind Harmer
0.014
944641AF1-129 GEN
Adder
93.824
962561AG1-105 GEN
Solar/Wind Harmer
9.407
3145493TOT1
Solar/Wind Harmer
0.453
3145453TOT5
Solar/Wind Harmer
0.272
3145603CNETO
Solar/Wind Harmer
0.181
964791AG1-342 GEN
Solar/Wind Harmer
3.74
3146843MT LREL
Solar/Wind Harmer
0.195
3146843MT LREL
Solar/Wind Harmer
0.195
961601AG1-000A GEN
Solar/Wind Harmer
3.447
316263AC1-034 GEN
Solar/Wind Harmer
7.365
958211AF2-115 GEN
Solar/Wind Harmer
2.318
963191AG1-168 GEN
Solar/Wind Harmer
0.773
3144293JTRSVLE
Adder
0.615
3144293JTRSVLE
Adder
0.518
3147133PAMPLIN
Solar/Wind Harmer
0.192
3147133PAMPLIN
Solar/Wind Harmer
0.153
316222AC1-221 GEN
Solar/Wind Harmer
0.714
3142946ENON
Solar/Wind Harmer
0.016
3146776BUCKING
Solar/Wind Harmer
0.65
3146776BUCKING
Solar/Wind Harmer
0.053
3142366NRTHEST
Adder
0.505
3150691DARBY 3
Adder
10.955
3150701DARBY 4
Adder
10.93
3150681DARBY 2
Adder
10.917
3150671DARBY 1
Adder
10.904
316075AC2-137 C
Solar/Wind Harmer
0.04
942751AE2-291 GEN
Solar/Wind Harmer
7.378
958261AF2-120 GEN
Solar/Wind Harmer
4.15
971489AH1-241 GEN
Solar/Wind Harmer
6.633
3142296MT RD221
Adder
0.39
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.211
3150341NORNECKC1
Adder
1.201
966871AG1-558 GEN
Solar/Wind Harmer
0.131
316447AC1-158 HLD
Solar/Wind Helper
3.579
316303AF2-085
50/50
5.424
315244AE2-183_ST
50/50
7.889
963041AG1-153 GEN
50/50
7.262
315779AE2-040
50/50
3.426
3151541CLOVER2
50/50
4.914
941031AE2-094 GEN
Solar/Wind Harmer
52.507
944011AF1-069 GEN
Solar/Wind Harmer
17.156
970673AG2-436 GEN
Solar/Wind Harmer
59.565
970673AG2-436 GEN
Solar/Wind Harmer
39.71
971967AH1-528 GEN
Solar/Wind Harmer
43.86
970085AG2-068 GEN
Solar/Wind Harmer
13.865
970581AG2-369 GEN
Solar/Wind Harmer
11.924
316233AE1-074 FULL
Solar/Wind Harmer
0.208
971281AH1-106 GEN
Solar/Wind Harmer
3.602
971283AH1-107 GEN
Solar/Wind Harmer
3.602
316315AB2-025 C
Solar/Wind Harmer
0.198
315814AE2-033 C
Solar/Wind Harmer
19.336
3143316POE
Solar/Wind Harmer
0.915
957871AF2-081 GEN
Solar/Wind Harmer
11.058
3151081ELIZAR1
Adder
20.359
3151091ELIZAR2
Adder
20.005
319010AE1-072 C
Solar/Wind Harmer
1.117
3146406KITTY HAWK
Solar/Wind Harmer
0.028
3152611GOSPORTB
Adder
2.823
3152621GOSPORTC
Adder
2.396
3152601GOSPORTA
Adder
2.21
316305AF2-043 C
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.119
315835AF2-110_GEN
Solar/Wind Harmer
1.513
316321Z2-027
Solar/Wind Harmer
0.041
3146396TANGLEW
Solar/Wind Harmer
0.607
3145176PASQUOTANK
Solar/Wind Harmer
0.136
3146486SUNBURY
Solar/Wind Harmer
0.22
3146486SUNBURY
Solar/Wind Harmer
0.22
316311AC2-079 GEN
Solar/Wind Harmer
6.318
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.151
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
316087AB2-174 GEN
Solar/Wind Harmer
0.006
3130156CHOWAN
Solar/Wind Harmer
0.216
3130156CHOWAN
Solar/Wind Harmer
0.216
965291AG1-394 GEN
Solar/Wind Harmer
0.951
315816AE2-034 GEN
Solar/Wind Harmer
0.918
315652AC1-086 GEN
Solar/Wind Harmer
23.483
3137643SOCKMAN
Solar/Wind Harmer
0.852
3145893MURPHYS
Solar/Wind Harmer
0.574
3145893MURPHYS
Solar/Wind Harmer
0.213
3146043SEABORD
Solar/Wind Harmer
0.213
315607AA1-063A GEN
Solar/Wind Harmer
0.434
3130546PLYMOUTH
Solar/Wind Harmer
0.212
315732AD1-074 GEN1
Solar/Wind Harmer
1.217
315733AD1-074 GEN2
Solar/Wind Harmer
1.217
315735AD1-075 GEN1
Solar/Wind Harmer
0.609
3146206CASHIE
Solar/Wind Harmer
0.211
970601AG2-382 GEN
Solar/Wind Harmer
7.883
3145513AHOSKIE
Solar/Wind Harmer
0.441
3145513AHOSKIE
Solar/Wind Harmer
0.211
3145796HORNRTN
Solar/Wind Harmer
0.674
3145796HORNRTN
Solar/Wind Harmer
0.084
971285AH1-108 GEN
Adder
1.587
971445AH1-216 GEN
Solar/Wind Harmer
14.817
3145683EARLEYS
Solar/Wind Harmer
0.42
3145683EARLEYS
Solar/Wind Harmer
0.21
3145683EARLEYS
Solar/Wind Harmer
0.21
970831AG2-522 GEN
Solar/Wind Harmer
8.902
3146033SCOT NK
Solar/Wind Harmer
0.823
972265AH1-717 GEN
Adder
15.87
3151201GRAVEL4
Adder
14.877
3151191GRAVEL3
Adder
14.689
3151211GRAVEL5
Adder
14.689
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316005AA1-067
Solar/Wind Harmer
0.212
3145746EVERETS
Solar/Wind Harmer
0.788
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
970181AG2-120 GEN
Solar/Wind Harmer
2.464
316369SG1_INVT
Solar/Wind Harmer
0.007
971443AH1-215 GEN
Solar/Wind Harmer
3.323
3144303KENBRDG
Solar/Wind Harmer
0.158
957861AF2-080 GEN
Solar/Wind Harmer
8.475
316319Z2-044 C
Solar/Wind Harmer
0
316420AA1-050 GEN
Solar/Wind Harmer
0.006
3145573BETHELC
Solar/Wind Harmer
0.195
3145573BETHELC
Solar/Wind Harmer
0.195
970683AG2-441 GEN
Solar/Wind Harmer
13.022
970681AG2-440 GEN
Solar/Wind Harmer
10.418
316132AB2-190 GEN1
Solar/Wind Harmer
1.041
946301AF1-294 GEN
Solar/Wind Harmer
3.812
961791AG1-021 GEN
Solar/Wind Harmer
1.855
316118AC1-105 GEN
Solar/Wind Harmer
0.495
315657AE1-056 GEN
Solar/Wind Harmer
6.612
3147173SINAI
Solar/Wind Harmer
0.189
3147243WELCO
Solar/Wind Harmer
0.118
3138283WHITEMARSH
Solar/Wind Harmer
0.039
970285AG2-188 GEN
Solar/Wind Harmer
13.256
971845AH1-439 GEN
Solar/Wind Harmer
7.448
970865AG2-541 GEN
Solar/Wind Harmer
5.665
971167AH1-042 GEN
Solar/Wind Harmer
14.133
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3143873LANEXA
Solar/Wind Harmer
0.09
970189AG2-124 GEN
Solar/Wind Harmer
4.44
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.03
316059AD1-063 C
Solar/Wind Harmer
0.001
316123AC1-075 GEN
Solar/Wind Harmer
0.2
970165AG2-112 GEN
Solar/Wind Harmer
1.187
970163AG2-111 GEN
Solar/Wind Harmer
1.132
316314AB2-024 C
Solar/Wind Harmer
0.001
315976AC1-164 GENA
Solar/Wind Harmer
15.083
316169AC1-164_GENC
Solar/Wind Harmer
13.031
315975AC1-164 GENB
Solar/Wind Harmer
0.446
3141913WHIT STONE
Solar/Wind Harmer
0.144
3138133OCRAN
Solar/Wind Harmer
0.043
3141783LANCAST
Solar/Wind Harmer
0.084
3141783LANCAST
Solar/Wind Harmer
0.056
972205AH1-687 GEN
Adder
5.897
962981AG1-147 GEN
Solar/Wind Harmer
5.019
970327AG2-215 GEN
Solar/Wind Harmer
4.3
316312AB1-027
Solar/Wind Harmer
0.228
971447AH1-217 GEN
Solar/Wind Harmer
3.55
3141813NORNECK
Solar/Wind Harmer
0.116
LAGNLTFEXP_LAGN->PJM
CLTF
9.063
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.182
TVALTFEXP_TVA->PJM
CLTF
4.543
NYPJM->LTFIMP_NY
CLTF
2.393
LGEELTFEXP_LGEE->PJM
CLTF
1.582
WECLTFEXP_WEC->PJM
CLTF
0.806
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.006
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.545
MECLTFEXP_MEC->PJM
CLTF
4.353
SIGELTFEXP_SIGE->PJM
CLTF
0.131
CPLELTFEXP_CPLE->PJM
CLTF
13.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.637

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:172.64 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5559.88
MW Contribution:7.03
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
20.32
3150861SPRUNCD
50/50
1.216
3143096IRON208
50/50
1.078
3143096IRON208
50/50
1.056
3150801HOPHCF4
50/50
1.421
971211AH1-065 GEN
50/50
1.714
3151101ELIZAR3
50/50
23.68
3151161SURRY 1
50/50
9.205
3147666LOUISA
Solar/Wind Harmer
0.591
315839AE2-212 C
Solar/Wind Harmer
0.002
315773AC2-141 GEN
Solar/Wind Harmer
8.876
965281AG1-393 GEN
Solar/Wind Harmer
2.585
315813AE1-149 C
Solar/Wind Harmer
12.873
970133AG2-095 GEN
Solar/Wind Harmer
2.314
944581AF1-123 GEN
Solar/Wind Harmer
54.216
944601AF1-125 GEN
Solar/Wind Harmer
53.381
970129AG2-093 GEN
Solar/Wind Harmer
14.547
315778AD1-151 GEN
Solar/Wind Harmer
19.233
3144536CHRHLND
Solar/Wind Harmer
0.036
3144873MCLAUGH
Solar/Wind Harmer
0.006
970659AG2-427 GEN
Solar/Wind Harmer
2.54
3145336SMITFLD
Solar/Wind Harmer
0.096
316083AB2-161 GEN
Solar/Wind Harmer
0.003
961611AG1-000B GEN
Solar/Wind Harmer
6.396
3151221GRAVEL6
Adder
17.422
3151171GRAVELC
Adder
3.352
970661AG2-428 GEN
Solar/Wind Harmer
5.062
970293AG2-193 GEN
Solar/Wind Harmer
2.548
3142946ENON
Solar/Wind Harmer
0.08
3146456SLIGO L269
Solar/Wind Harmer
0.238
971153AH1-033 GEN
Solar/Wind Harmer
2.749
3142416OLDCHRC
Solar/Wind Harmer
2.305
3144216WINCHST
Adder
0.896
3150921YORKTN3
Adder
5.966
316382AG1-145 C
Solar/Wind Harmer
0.002
316320Y1-086
Solar/Wind Harmer
0.001
3152251N ANNA1
50/50
20.321
970119AG2-088 GEN
50/50
35.422
3150851SPRUNCC
50/50
1.216
3143096IRON208
50/50
1.078
3152331SURRY 2
50/50
9.99
3150771HOPHCF1
50/50
0.977
3143226MDLTHAN
Solar/Wind Harmer
0.265
3143526WINTERP
Solar/Wind Harmer
1.342
3147666LOUISA
Solar/Wind Harmer
1.028
316192AB2-158 GEN
Solar/Wind Harmer
1.415
940641AE2-051 GEN
Solar/Wind Harmer
19.964
939411AE1-173 GEN
Solar/Wind Harmer
105.426
3142543TWELFTH
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
4.211
315671AE2-027_GEN
Solar/Wind Harmer
15.496
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.233
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3146626S HERTFORD
Solar/Wind Harmer
0.231
3145273HOLLAND
Solar/Wind Harmer
0.173
316473AC1-191 GEN
Solar/Wind Harmer
0.778
3141843SHACKLE
Adder
1.16
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.143
316258AE1-075 C
Solar/Wind Harmer
0.171
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.429
3146376EDENTON
Solar/Wind Harmer
0.227
3141766HARMONY
Solar/Wind Harmer
3.024
316280AD1-041 GEN
Solar/Wind Harmer
0.005
316156AD2-030 GEN
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
4.011
970917AG2-570 GEN
Solar/Wind Harmer
20.009
315614AA2-178 GEN
Solar/Wind Harmer
1.271
971157AH1-035 GEN
Solar/Wind Harmer
2.623
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
316365GEN2_N
Solar/Wind Harmer
0.489
315737AD1-076 GEN
Solar/Wind Harmer
2.804
3150401LDYSMT4
Adder
29.156
3150371LDYSMT1
Adder
28.172
962971AG1-146 GEN
Solar/Wind Harmer
3.461
3146206CASHIE
Solar/Wind Harmer
0.216
3145893MURPHYS
Solar/Wind Harmer
0.361
3145893MURPHYS
Solar/Wind Harmer
0.215
957521AF2-046 GEN
Solar/Wind Harmer
15.996
961681AG1-008 GEN
Solar/Wind Harmer
15.996
970009AG2-005 GEN
Solar/Wind Harmer
1.599
3146173TUNIS
Solar/Wind Harmer
0.213
3156021HOLLOMANSOL
Solar/Wind Harmer
0.967
316463AE2-346 GEN
Solar/Wind Harmer
0.183
316140AB2-099
Solar/Wind Harmer
0.076
962331AG1-082 GEN
Solar/Wind Harmer
2.268
316404AE1-155 C
Solar/Wind Harmer
0.047
3146263WOODLND
Solar/Wind Harmer
0.21
313506AB2-031 GEN
Solar/Wind Harmer
0.649
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3145963POPLR C
Solar/Wind Harmer
0.208
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.208
316478AD1-087 GEN
Solar/Wind Harmer
0.721
316486AD2-202 GEN
Solar/Wind Harmer
0.212
3147043LAWRENC
Solar/Wind Harmer
0.124
3145796HORNRTN
Solar/Wind Harmer
0.822
3145796HORNRTN
Solar/Wind Harmer
0.206
3150351NORNECKC2
Adder
2.075
316210AC1-098 GEN
Solar/Wind Harmer
1.861
3145933PARMELE
Solar/Wind Harmer
0.2
966801AG1-551 GEN
Solar/Wind Harmer
2.326
971781AH1-399 GEN
Solar/Wind Harmer
0.26
970909AG2-566 GEN
Solar/Wind Harmer
2.105
3145746EVERETS
Solar/Wind Harmer
0.196
3145746EVERETS
Solar/Wind Harmer
0.196
315724AD1-057 GEN
Solar/Wind Harmer
0.733
316327AA2-057 GEN
Solar/Wind Harmer
0.292
316131AB2-060 GEN
Solar/Wind Harmer
0.604
964241AG1-285 GEN
Solar/Wind Harmer
12.793
315785AD2-033 C
Solar/Wind Harmer
1.556
970257AG2-171 GEN
Solar/Wind Harmer
6.117
959311AF2-222 GEN
Solar/Wind Harmer
16.978
3146233WITAKRS
Solar/Wind Harmer
0.955
3146233WITAKRS
Solar/Wind Harmer
0.129
3146073TAR RVR
Solar/Wind Harmer
0.19
3146083TARBORO
Solar/Wind Harmer
0.19
963181AG1-167 GEN
Solar/Wind Harmer
0.761
3144293JTRSVLE
Adder
0.605
3138543CONSLDL
Solar/Wind Harmer
0.125
3147133PAMPLIN
Solar/Wind Harmer
0.596
971193AH1-056 GEN
Solar/Wind Harmer
11.558
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.113
961601AG1-000A GEN
Solar/Wind Harmer
13.299
3145543BTLEBRO
Solar/Wind Harmer
0.187
3145543BTLEBRO
Solar/Wind Harmer
0.187
971623AH1-311 GEN
Solar/Wind Harmer
0.374
3141906WESTMOR
Solar/Wind Harmer
0.074
3146776BUCKING
Solar/Wind Harmer
0.064
316248AF1-058 C
Solar/Wind Harmer
0.001
944591AF1-124 GEN
Solar/Wind Harmer
54.408
970129AG2-093 GEN
Solar/Wind Harmer
6.846
316458AB2-190 GEN2
Solar/Wind Harmer
1.291
971069AG2-661 GEN
Solar/Wind Harmer
4.274
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
3
970659AG2-427 GEN
Solar/Wind Harmer
11.613
971647AH1-324 GEN
Solar/Wind Harmer
10.242
3145336SMITFLD
Solar/Wind Harmer
0.959
316381AD1-082 GEN
Solar/Wind Harmer
0.25
944631AF1-128 GEN
Adder
114.357
961611AG1-000B GEN
Solar/Wind Harmer
12.579
3151171GRAVELC
Adder
2.549
970661AG2-428 GEN
Solar/Wind Harmer
23.801
316388AE2-253 GEN
Solar/Wind Harmer
0.747
3146456SLIGO L269
Solar/Wind Harmer
0.238
3142416OLDCHRC
Solar/Wind Harmer
0.618
3142416OLDCHRC
Solar/Wind Harmer
0.237
316072AD1-144
Solar/Wind Harmer
0.086
3138126ROCKLANDING
Solar/Wind Harmer
0.109
316246AF1-032 C
Solar/Wind Harmer
0.107
316159AE1-175 C
Solar/Wind Harmer
0.205
316093AE2-104_GEN
Solar/Wind Harmer
3.974
971317AH1-138 GEN
Solar/Wind Harmer
1.762
3146516WINFALL
Solar/Wind Harmer
0.754
3146516WINFALL
Solar/Wind Harmer
0.233
3142433PROV 92
Solar/Wind Harmer
0.928
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
971777AH1-397 GEN
Solar/Wind Harmer
0.6
3141843SHACKLE
Adder
1.16
3143336POWHATN
Solar/Wind Harmer
4.034
3130156CHOWAN
Solar/Wind Harmer
0.227
3141766HARMONY
Solar/Wind Harmer
0.045
970919AG2-571 GEN
Solar/Wind Harmer
8.004
966881AG1-559 GEN
Solar/Wind Harmer
0.26
970087AG2-069 GEN
Solar/Wind Harmer
17.934
3145663CRESWEL
Solar/Wind Harmer
0.622
971163AH1-040 GEN
Solar/Wind Harmer
17.772
3138133OCRAN
Solar/Wind Harmer
0.133
316023GEN1_S
Solar/Wind Harmer
0.489
972197AH1-683 GEN
Adder
4.553
972219AH1-694 GEN
Adder
3.278
316336AC2-165 C
Solar/Wind Harmer
0.008
3146206CASHIE
Solar/Wind Harmer
0.216
971547AH1-271 GEN
Solar/Wind Harmer
4.607
3145893MURPHYS
Solar/Wind Harmer
0.862
3145893MURPHYS
Solar/Wind Harmer
0.958
957481AF2-042 GEN
Solar/Wind Harmer
57.247
3146173TUNIS
Solar/Wind Harmer
0.213
960081AF2-299 GEN
Solar/Wind Harmer
2.041
962861AG1-135 GEN
Solar/Wind Harmer
6.774
3145683EARLEYS
Solar/Wind Harmer
0.211
3146263WOODLND
Solar/Wind Harmer
0.21
315693AD1-088 GEN
Solar/Wind Harmer
10.091
962491AG1-098 GEN
Solar/Wind Harmer
11.959
316011AB1-132 GEN
Solar/Wind Harmer
3.796
962571AG1-106 GEN
Solar/Wind Harmer
2.971
971795AH1-408 GEN
Solar/Wind Harmer
13.893
3145963POPLR C
Solar/Wind Harmer
0.208
316303AF2-085
50/50
4.723
971285AH1-108 GEN
50/50
1.99
970603AG2-384 GEN
50/50
5.178
972263AH1-716 GEN
50/50
139.063
316233AE1-074 FULL
Solar/Wind Harmer
0.207
971281AH1-106 GEN
Solar/Wind Harmer
3.58
971283AH1-107 GEN
Solar/Wind Harmer
3.58
3143316POE
Solar/Wind Harmer
0.964
941031AE2-094 GEN
Solar/Wind Harmer
44.68
944011AF1-069 GEN
Solar/Wind Harmer
14.599
316132AB2-190 GEN1
Solar/Wind Harmer
1.291
3151081ELIZAR1
Adder
22.034
3151091ELIZAR2
Adder
21.652
3152611GOSPORTB
Adder
3.059
3152621GOSPORTC
Adder
2.596
3152601GOSPORTA
Adder
2.395
316369SG1_INVT
Solar/Wind Harmer
0.009
971445AH1-216 GEN
Solar/Wind Harmer
16.89
972265AH1-717 GEN
Adder
18.606
3151201GRAVEL4
Adder
17.442
3151191GRAVEL3
Adder
17.221
3151211GRAVEL5
Adder
17.221
970673AG2-436 GEN
Solar/Wind Harmer
50.858
970673AG2-436 GEN
Solar/Wind Harmer
33.905
957871AF2-081 GEN
Solar/Wind Harmer
11.862
316312AB1-027
Solar/Wind Harmer
0.425
319010AE1-072 C
Solar/Wind Harmer
1.197
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.163
316311AC2-079 GEN
Solar/Wind Harmer
6.823
3146406KITTY HAWK
Solar/Wind Harmer
0.03
316305AF2-043 C
Solar/Wind Harmer
0.002
315835AF2-110_GEN
Solar/Wind Harmer
1.621
316315AB2-025 C
Solar/Wind Harmer
0.191
315976AC1-164 GENA
Solar/Wind Harmer
24.444
316169AC1-164_GENC
Solar/Wind Harmer
21.117
315975AC1-164 GENB
Solar/Wind Harmer
0.723
313526AB2-022
Solar/Wind Harmer
0.128
971967AH1-528 GEN
Solar/Wind Harmer
37.658
315814AE2-033 C
Solar/Wind Harmer
18.587
3146486SUNBURY
Solar/Wind Harmer
0.235
3146486SUNBURY
Solar/Wind Harmer
0.235
316321Z2-027
Solar/Wind Harmer
0.044
3146396TANGLEW
Solar/Wind Harmer
0.646
3145176PASQUOTANK
Solar/Wind Harmer
0.145
972189AH1-679 GEN
Adder
3.913
971167AH1-042 GEN
Solar/Wind Harmer
20.686
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3138283WHITEMARSH
Solar/Wind Harmer
0.054
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3143873LANEXA
Solar/Wind Harmer
0.137
316314AB2-024 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.729
3130156CHOWAN
Solar/Wind Harmer
0.227
3130156CHOWAN
Solar/Wind Harmer
0.227
316059AD1-063 C
Solar/Wind Harmer
0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.045
970085AG2-068 GEN
Solar/Wind Harmer
11.956
970581AG2-369 GEN
Solar/Wind Harmer
10.282
3141913WHIT STONE
Solar/Wind Harmer
0.222
315816AE2-034 GEN
Solar/Wind Harmer
0.953
3138133OCRAN
Solar/Wind Harmer
0.066
3141783LANCAST
Solar/Wind Harmer
0.132
3141783LANCAST
Solar/Wind Harmer
0.088
3130546PLYMOUTH
Solar/Wind Harmer
0.218
315732AD1-074 GEN1
Solar/Wind Harmer
1.252
315733AD1-074 GEN2
Solar/Wind Harmer
1.252
315735AD1-075 GEN1
Solar/Wind Harmer
0.627
965291AG1-394 GEN
Solar/Wind Harmer
0.966
3150411LDYSMT5
Adder
29.247
3150381LDYSMT2
Adder
27.99
972213AH1-691 GEN
Adder
4.735
972215AH1-692 GEN
Adder
4.735
962981AG1-147 GEN
Solar/Wind Harmer
8.075
3146206CASHIE
Solar/Wind Harmer
0.216
970601AG2-382 GEN
Solar/Wind Harmer
8.061
3145893MURPHYS
Solar/Wind Harmer
0.582
3145893MURPHYS
Solar/Wind Harmer
0.215
970327AG2-215 GEN
Solar/Wind Harmer
7.029
3145513AHOSKIE
Solar/Wind Harmer
0.444
3145513AHOSKIE
Solar/Wind Harmer
0.212
3146043SEABORD
Solar/Wind Harmer
0.212
3145683EARLEYS
Solar/Wind Harmer
0.423
3145683EARLEYS
Solar/Wind Harmer
0.211
3145683EARLEYS
Solar/Wind Harmer
0.211
315607AA1-063A GEN
Solar/Wind Harmer
0.431
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
22.967
3137643SOCKMAN
Solar/Wind Harmer
0.832
3145796HORNRTN
Solar/Wind Harmer
0.658
3145796HORNRTN
Solar/Wind Harmer
0.082
3141813NORNECK
Solar/Wind Harmer
0.205
3146033SCOT NK
Solar/Wind Harmer
0.815
970831AG2-522 GEN
Solar/Wind Harmer
8.503
316005AA1-067
Solar/Wind Harmer
0.21
3145746EVERETS
Solar/Wind Harmer
0.779
3145746EVERETS
Solar/Wind Harmer
0.196
3145746EVERETS
Solar/Wind Harmer
0.196
3145746EVERETS
Solar/Wind Harmer
0.196
970181AG2-120 GEN
Solar/Wind Harmer
2.436
957861AF2-080 GEN
Solar/Wind Harmer
8.31
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316420AA1-050 GEN
Solar/Wind Harmer
0.006
971443AH1-215 GEN
Solar/Wind Harmer
3.212
3144303KENBRDG
Solar/Wind Harmer
0.153
970683AG2-441 GEN
Solar/Wind Harmer
12.709
971133AH1-012 GEN
50/50
5.491
944641AF1-129 GEN
50/50
122.767
970533AG2-339 GEN
50/50
21.564
970531AG2-338 GEN
50/50
8.626
3142366NRTHEST
50/50
0.836
3150781HOPHCF2
50/50
0.977
3150791HOPHCF3
50/50
0.977
3150761HOPPOLC
50/50
0.62
971213AH1-066 GEN
50/50
0.857
971223AH1-071 GEN
Solar/Wind Harmer
2.834
3143526WINTERP
Solar/Wind Harmer
1.342
316240AF1-291 C
Solar/Wind Harmer
0.002
3150691DARBY 3
Adder
17.296
3150701DARBY 4
Adder
17.255
3150681DARBY 2
Adder
17.235
3150671DARBY 1
Adder
17.215
316036AC1-147 C
Solar/Wind Harmer
0.045
3150991CHESPKB
Adder
2.516
3150991CHESPKB
Adder
2.456
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.27
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.23
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316185AD1-033 GEN
Solar/Wind Harmer
0.007
970657AG2-426 GEN
Solar/Wind Harmer
8.395
970657AG2-426 GEN
Solar/Wind Harmer
1.76
3142296MT RD221
Adder
0.763
3145506HICKORY
Solar/Wind Harmer
0.957
3145506HICKORY
Solar/Wind Harmer
0.574
3145506HICKORY
Solar/Wind Harmer
0.144
3142946ENON
Solar/Wind Harmer
0.024
316339AD2-160 GEN
Solar/Wind Harmer
0.387
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.133
3137176SLIGO L2192
Solar/Wind Harmer
0.946
3146456SLIGO L269
Solar/Wind Harmer
4.208
3130086AYDLETT
Solar/Wind Harmer
0.95
316075AC2-137 C
Solar/Wind Harmer
0.065
972185AH1-677 GEN
Adder
13.26
3144356SAPONY
Solar/Wind Harmer
1.973
3146386ELIZ CT
Solar/Wind Harmer
0.235
972187AH1-678 GEN
Adder
6.65
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.233
3146516WINFALL
Solar/Wind Harmer
0.233
3146516WINFALL
Solar/Wind Harmer
0.233
3146626S HERTFORD
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
0.231
966871AG1-558 GEN
Solar/Wind Harmer
0.266
970933AG2-581 GEN
Solar/Wind Harmer
18.37
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
1.008
3146376EDENTON
Solar/Wind Harmer
1.008
957411AF2-035 GEN
Solar/Wind Harmer
9.597
970317AG2-208 GEN
Solar/Wind Harmer
8.892
315673AE1-157 GEN
Solar/Wind Harmer
15.364
3150391LDYSMT3
Adder
29.101
972195AH1-682 GEN
Adder
3.824
316065AD1-022 GEN
Solar/Wind Harmer
9.976
3145893MURPHYS
Solar/Wind Harmer
1.442
3145893MURPHYS
Solar/Wind Harmer
0.388
970099AG2-077 GEN
Solar/Wind Harmer
22.899
3146173TUNIS
Solar/Wind Harmer
0.213
3146173TUNIS
Solar/Wind Harmer
0.213
958261AF2-120 GEN
Solar/Wind Harmer
6.97
316181AB2-040 GEN
Solar/Wind Harmer
0.305
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.126
316426AA2-053 GEN
Solar/Wind Harmer
0.702
3145593CAROLNA
Solar/Wind Harmer
0.207
3145593CAROLNA
Solar/Wind Harmer
0.207
966811AG1-552 GEN
Solar/Wind Harmer
2.246
3145593CAROLNA
Solar/Wind Harmer
0.258
3145783HORNRTN
Solar/Wind Harmer
3.66
3145783HORNRTN
Solar/Wind Harmer
2.928
3145783HORNRTN
Solar/Wind Harmer
0.915
3145783HORNRTN
Solar/Wind Harmer
0.366
3145796HORNRTN
Solar/Wind Harmer
0.617
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.143
3150341NORNECKC1
Adder
2.126
971741AH1-377 GEN
Solar/Wind Harmer
19.869
3145933PARMELE
Solar/Wind Harmer
0.399
3145933PARMELE
Solar/Wind Harmer
0.2
316274AC1-208 GEN
Solar/Wind Harmer
1.034
316468AD1-105 GEN
Solar/Wind Harmer
-0.064
970301AG2-198 GEN
Solar/Wind Harmer
8.419
939181AE1-148 GEN
Solar/Wind Harmer
9.29
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.155
971775AH1-396 GEN
Solar/Wind Harmer
0.306
3145493TOT1
Solar/Wind Harmer
0.441
3145453TOT5
Solar/Wind Harmer
0.264
3145603CNETO
Solar/Wind Harmer
0.176
958211AF2-115 GEN
Solar/Wind Harmer
2.282
963191AG1-168 GEN
Solar/Wind Harmer
0.761
3144293JTRSVLE
Adder
0.605
3144293JTRSVLE
Adder
0.51
3147133PAMPLIN
Solar/Wind Harmer
0.19
3147133PAMPLIN
Solar/Wind Harmer
0.152
961601AG1-000A GEN
Solar/Wind Harmer
3.325
316263AC1-034 GEN
Solar/Wind Harmer
7.104
962561AG1-105 GEN
Solar/Wind Harmer
8.835
964791AG1-342 GEN
Solar/Wind Harmer
3.505
3146843MT LREL
Solar/Wind Harmer
0.182
3146843MT LREL
Solar/Wind Harmer
0.182
3146776BUCKING
Solar/Wind Harmer
0.716
3146776BUCKING
Solar/Wind Harmer
0.058
316222AC1-221 GEN
Solar/Wind Harmer
0.661
971489AH1-241 GEN
Solar/Wind Harmer
8.416
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
7.289
3151731LOISA B
Adder
8.676
3151721LOISA A
Adder
8.631
316447AC1-158 HLD
Solar/Wind Helper
11.481
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.208
3141726DUNNSVL
Solar/Wind Harmer
0.83
316174AB2-169 GEN
Solar/Wind Harmer
0.006
3147043LAWRENC
Adder
1.868
3145783HORNRTN
Solar/Wind Harmer
0.206
3145796HORNRTN
Solar/Wind Harmer
0.678
3145796HORNRTN
Solar/Wind Harmer
0.206
3150351NORNECKC2
Adder
2.04
316212AC1-099_GEN
Solar/Wind Harmer
1.038
3146293MARTNCO
Solar/Wind Harmer
0.185
316129AC1-054 GEN
Solar/Wind Harmer
0.746
971065AG2-659 GEN
Solar/Wind Harmer
8.434
3145746EVERETS
Solar/Wind Harmer
0.196
3145746EVERETS
Solar/Wind Harmer
0.196
315722AD1-056 GEN
Solar/Wind Harmer
1.237
316337AD2-073 GEN
Solar/Wind Harmer
0.169
315687AD1-152 GEN
Solar/Wind Harmer
0.006
316494AC1-189 GEN
Solar/Wind Harmer
0.651
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970937AG2-583 GEN
Solar/Wind Harmer
11.696
970685AG2-442 GEN
Solar/Wind Harmer
14.234
3146233WITAKRS
Solar/Wind Harmer
0.757
961671AG1-007 GEN
Solar/Wind Harmer
0.029
3146083TARBORO
Solar/Wind Harmer
0.19
3145493TOT1
Solar/Wind Harmer
0.845
963171AG1-166 GEN
Solar/Wind Harmer
1.014
971563AH1-280 GEN
Solar/Wind Harmer
2.028
3144293JTRSVLE
Adder
0.605
3146926FARMVIL
Solar/Wind Harmer
0.113
3145543BTLEBRO
Solar/Wind Harmer
0.187
3145543BTLEBRO
Solar/Wind Harmer
0.149
316359AB2-059 GEN
Solar/Wind Harmer
0.672
316049AB1-081 GEN
Solar/Wind Harmer
1.07
3142053HEARTS
Solar/Wind Harmer
0.329
970401AG2-262 GEN
Solar/Wind Harmer
1.071
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.072
972003AH1-546 GEN
Solar/Wind Harmer
7.247
316003AC1-222 GEN
Solar/Wind Harmer
0.004
972135AH1-637 GEN
Solar/Wind Harmer
1.431
971377AH1-170 GEN
Solar/Wind Harmer
1.683
3147623JAMES R
Solar/Wind Harmer
0.366
972277AH1-723 GEN
Adder
87.353
3151751LOISA D
Adder
8.676
970223AG2-152 GEN
Solar/Wind Harmer
7.908
316045AC1-158 PL2
Solar/Wind Helper
16.699
316006AB2-029 C
Solar/Wind Helper
0.14
970681AG2-440 GEN
Solar/Wind Harmer
10.167
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.19
3145573BETHELC
Solar/Wind Harmer
0.19
946301AF1-294 GEN
Solar/Wind Harmer
3.752
961791AG1-021 GEN
Solar/Wind Harmer
1.825
315657AE1-056 GEN
Solar/Wind Harmer
6.547
316223AC1-118
Solar/Wind Harmer
0.132
970285AG2-188 GEN
Solar/Wind Harmer
14.341
971845AH1-439 GEN
Solar/Wind Harmer
8.154
316118AC1-105 GEN
Solar/Wind Harmer
0.462
3147173SINAI
Solar/Wind Harmer
0.175
3147243WELCO
Solar/Wind Harmer
0.11
972205AH1-687 GEN
Adder
7.204
944491AF1-114 GEN
Solar/Wind Harmer
0.001
970865AG2-541 GEN
Solar/Wind Harmer
5.394
971447AH1-217 GEN
Solar/Wind Harmer
4.654
972193AH1-681 GEN
Adder
3.349
316123AC1-075 GEN
Solar/Wind Harmer
0.195
970165AG2-112 GEN
Solar/Wind Harmer
1.154
970163AG2-111 GEN
Solar/Wind Harmer
1.101
270494AE1-108_GEN
Solar/Wind Harmer
1.672
3147346CASHSCORNER
Solar/Wind Harmer
0.293
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316164AC1-076 GEN
Solar/Wind Helper
1.38
316411AF1-147_GEN1
Solar/Wind Helper
0.79
316415AF1-147_GEN2
Solar/Wind Helper
0.79
3138216PACIFIC
Solar/Wind Helper
0.038
960061AF2-297 GEN
Solar/Wind Harmer
7.491
970737AG2-469 GEN
Solar/Wind Harmer
7.435
971683AH1-343 GEN
Solar/Wind Harmer
5.965
316283AC2-100 C
Solar/Wind Harmer
0.31
970221AG2-151 GEN
Solar/Wind Harmer
8.416
972255AH1-712 GEN
Adder
74.962
3151761LOISA E
Adder
17.688
972183AH1-676 GEN
Adder
136.298
3141316ARNOLDS
Adder
0.29
316044AC1-158 PL1
Solar/Wind Helper
5.216
316450AC1-158 RIC
Solar/Wind Helper
1.391
3141196NOKESVL
Solar/Wind Helper
1.131
LAGNLTFEXP_LAGN->PJM
CLTF
8.398
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.505
TVALTFEXP_TVA->PJM
CLTF
4.252
NYPJM->LTFIMP_NY
CLTF
3.266
LGEELTFEXP_LGEE->PJM
CLTF
1.371
WECLTFEXP_WEC->PJM
CLTF
0.662
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.027
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.441
MECLTFEXP_MEC->PJM
CLTF
3.751
SIGELTFEXP_SIGE->PJM
CLTF
0.114
CPLELTFEXP_CPLE->PJM
CLTF
12.136
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.163

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:171.66 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5528.27
MW Contribution:7.18
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
4.791
971285AH1-108 GEN
50/50
2.026
970603AG2-384 GEN
50/50
5.274
316233AE1-074 FULL
Solar/Wind Harmer
0.21
971281AH1-106 GEN
Solar/Wind Harmer
3.638
971283AH1-107 GEN
Solar/Wind Harmer
3.638
3143316POE
Solar/Wind Harmer
0.98
941031AE2-094 GEN
Solar/Wind Harmer
45.33
944011AF1-069 GEN
Solar/Wind Harmer
14.811
316132AB2-190 GEN1
Solar/Wind Harmer
1.315
316369SG1_INVT
Solar/Wind Harmer
0.009
3151081ELIZAR1
Adder
22.416
3151091ELIZAR2
Adder
22.027
3152611GOSPORTB
Adder
3.112
3152621GOSPORTC
Adder
2.641
3152601GOSPORTA
Adder
2.437
971445AH1-216 GEN
Solar/Wind Harmer
17.191
972265AH1-717 GEN
Adder
18.943
3151201GRAVEL4
Adder
17.758
3151191GRAVEL3
Adder
17.533
3151211GRAVEL5
Adder
17.533
316312AB1-027
Solar/Wind Harmer
0.435
957871AF2-081 GEN
Solar/Wind Harmer
12.066
970673AG2-436 GEN
Solar/Wind Harmer
51.597
970673AG2-436 GEN
Solar/Wind Harmer
34.398
319010AE1-072 C
Solar/Wind Harmer
1.218
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.166
316311AC2-079 GEN
Solar/Wind Harmer
6.941
3146406KITTY HAWK
Solar/Wind Harmer
0.03
316305AF2-043 C
Solar/Wind Harmer
0.002
315976AC1-164 GENA
Solar/Wind Harmer
24.95
316169AC1-164_GENC
Solar/Wind Harmer
21.555
315975AC1-164 GENB
Solar/Wind Harmer
0.738
315835AF2-110_GEN
Solar/Wind Harmer
1.649
316315AB2-025 C
Solar/Wind Harmer
0.194
313526AB2-022
Solar/Wind Harmer
0.13
972189AH1-679 GEN
Adder
4.009
3146486SUNBURY
Solar/Wind Harmer
0.239
3146486SUNBURY
Solar/Wind Harmer
0.239
971967AH1-528 GEN
Solar/Wind Harmer
38.202
315814AE2-033 C
Solar/Wind Harmer
18.884
316321Z2-027
Solar/Wind Harmer
0.044
3146396TANGLEW
Solar/Wind Harmer
0.658
3145176PASQUOTANK
Solar/Wind Harmer
0.148
971167AH1-042 GEN
Solar/Wind Harmer
21.1
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
3138283WHITEMARSH
Solar/Wind Harmer
0.055
3143873LANEXA
Solar/Wind Harmer
0.14
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
316314AB2-024 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.866
316059AD1-063 C
Solar/Wind Harmer
0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.008
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.23
3130156CHOWAN
Solar/Wind Harmer
0.23
3141873WAN 176
Solar/Wind Harmer
0.046
970085AG2-068 GEN
Solar/Wind Harmer
12.13
970581AG2-369 GEN
Solar/Wind Harmer
10.432
3141913WHIT STONE
Solar/Wind Harmer
0.227
3138133OCRAN
Solar/Wind Harmer
0.068
315816AE2-034 GEN
Solar/Wind Harmer
0.969
3141783LANCAST
Solar/Wind Harmer
0.135
3141783LANCAST
Solar/Wind Harmer
0.09
3150411LDYSMT5
Adder
30.153
3150381LDYSMT2
Adder
28.858
972213AH1-691 GEN
Adder
4.882
972215AH1-692 GEN
Adder
4.882
3130546PLYMOUTH
Solar/Wind Harmer
0.222
315732AD1-074 GEN1
Solar/Wind Harmer
1.273
315733AD1-074 GEN2
Solar/Wind Harmer
1.273
315735AD1-075 GEN1
Solar/Wind Harmer
0.637
965291AG1-394 GEN
Solar/Wind Harmer
0.982
962981AG1-147 GEN
Solar/Wind Harmer
8.243
3146206CASHIE
Solar/Wind Harmer
0.219
970601AG2-382 GEN
Solar/Wind Harmer
8.195
3145893MURPHYS
Solar/Wind Harmer
0.591
3145893MURPHYS
Solar/Wind Harmer
0.219
970327AG2-215 GEN
Solar/Wind Harmer
7.177
3145513AHOSKIE
Solar/Wind Harmer
0.452
3145513AHOSKIE
Solar/Wind Harmer
0.216
3146043SEABORD
Solar/Wind Harmer
0.215
3145683EARLEYS
Solar/Wind Harmer
0.43
3145683EARLEYS
Solar/Wind Harmer
0.215
3145683EARLEYS
Solar/Wind Harmer
0.215
315607AA1-063A GEN
Solar/Wind Harmer
0.438
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
23.331
3137643SOCKMAN
Solar/Wind Harmer
0.845
3141813NORNECK
Solar/Wind Harmer
0.209
3145796HORNRTN
Solar/Wind Harmer
0.668
3145796HORNRTN
Solar/Wind Harmer
0.084
3146033SCOT NK
Solar/Wind Harmer
0.828
970831AG2-522 GEN
Solar/Wind Harmer
8.631
316005AA1-067
Solar/Wind Harmer
0.213
3145746EVERETS
Solar/Wind Harmer
0.791
3145746EVERETS
Solar/Wind Harmer
0.199
3145746EVERETS
Solar/Wind Harmer
0.199
3145746EVERETS
Solar/Wind Harmer
0.199
970181AG2-120 GEN
Solar/Wind Harmer
2.475
957861AF2-080 GEN
Solar/Wind Harmer
8.442
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316420AA1-050 GEN
Solar/Wind Harmer
0.006
971443AH1-215 GEN
Solar/Wind Harmer
3.255
3144303KENBRDG
Solar/Wind Harmer
0.155
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.193
3145573BETHELC
Solar/Wind Harmer
0.193
970683AG2-441 GEN
Solar/Wind Harmer
12.874
970681AG2-440 GEN
Solar/Wind Harmer
10.299
946301AF1-294 GEN
Solar/Wind Harmer
3.8
961791AG1-021 GEN
Solar/Wind Harmer
1.849
315657AE1-056 GEN
Solar/Wind Harmer
6.628
316223AC1-118
Solar/Wind Harmer
0.135
970285AG2-188 GEN
Solar/Wind Harmer
14.487
971845AH1-439 GEN
Solar/Wind Harmer
8.236
316118AC1-105 GEN
Solar/Wind Harmer
0.469
3147173SINAI
Solar/Wind Harmer
0.178
3147243WELCO
Solar/Wind Harmer
0.111
972205AH1-687 GEN
Adder
7.261
944491AF1-114 GEN
Solar/Wind Harmer
0.001
970865AG2-541 GEN
Solar/Wind Harmer
5.471
971447AH1-217 GEN
Solar/Wind Harmer
4.69
972193AH1-681 GEN
Adder
3.425
316123AC1-075 GEN
Solar/Wind Harmer
0.197
970165AG2-112 GEN
Solar/Wind Harmer
1.171
970163AG2-111 GEN
Solar/Wind Harmer
1.117
270494AE1-108_GEN
Solar/Wind Harmer
1.686
3147346CASHSCORNER
Solar/Wind Harmer
0.279
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316164AC1-076 GEN
Solar/Wind Helper
2.196
316411AF1-147_GEN1
Solar/Wind Helper
0.801
316415AF1-147_GEN2
Solar/Wind Helper
0.801
3138216PACIFIC
Solar/Wind Helper
0.039
3152251N ANNA1
50/50
20.435
970119AG2-088 GEN
50/50
35.934
3150851SPRUNCC
50/50
1.238
3143096IRON208
50/50
1.099
3152331SURRY 2
50/50
10.173
3150771HOPHCF1
50/50
0.996
3143226MDLTHAN
Solar/Wind Harmer
0.269
3143526WINTERP
Solar/Wind Harmer
1.363
3147666LOUISA
Solar/Wind Harmer
1.017
940641AE2-051 GEN
Solar/Wind Harmer
20.264
939411AE1-173 GEN
Solar/Wind Harmer
107.071
3142543TWELFTH
Solar/Wind Harmer
0.024
316192AB2-158 GEN
Solar/Wind Harmer
1.397
316294AC1-161 GEN
Solar/Wind Harmer
4.284
315671AE2-027_GEN
Solar/Wind Harmer
15.779
970129AG2-093 GEN
Solar/Wind Harmer
6.973
316458AB2-190 GEN2
Solar/Wind Harmer
1.315
944591AF1-124 GEN
Solar/Wind Harmer
55.346
971069AG2-661 GEN
Solar/Wind Harmer
4.353
944631AF1-128 GEN
Adder
116.602
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
3.052
971647AH1-324 GEN
Solar/Wind Harmer
10.43
970659AG2-427 GEN
Solar/Wind Harmer
11.815
3145336SMITFLD
Solar/Wind Harmer
0.976
961611AG1-000B GEN
Solar/Wind Harmer
12.808
316381AD1-082 GEN
Solar/Wind Harmer
0.254
3151171GRAVELC
Adder
2.595
970661AG2-428 GEN
Solar/Wind Harmer
24.214
3142416OLDCHRC
Solar/Wind Harmer
0.631
3142416OLDCHRC
Solar/Wind Harmer
0.242
316388AE2-253 GEN
Solar/Wind Harmer
0.76
3138126ROCKLANDING
Solar/Wind Harmer
0.111
3146456SLIGO L269
Solar/Wind Harmer
0.242
316072AD1-144
Solar/Wind Harmer
0.088
316159AE1-175 C
Solar/Wind Harmer
0.209
316246AF1-032 C
Solar/Wind Harmer
0.109
971317AH1-138 GEN
Solar/Wind Harmer
1.796
316093AE2-104_GEN
Solar/Wind Harmer
4.042
3142433PROV 92
Solar/Wind Harmer
0.947
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
3146516WINFALL
Solar/Wind Harmer
0.766
3146516WINFALL
Solar/Wind Harmer
0.236
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
971777AH1-397 GEN
Solar/Wind Harmer
0.612
3141843SHACKLE
Adder
1.184
3141766HARMONY
Solar/Wind Harmer
0.046
966881AG1-559 GEN
Solar/Wind Harmer
0.267
3130156CHOWAN
Solar/Wind Harmer
0.23
3143336POWHATN
Solar/Wind Harmer
4.084
970919AG2-571 GEN
Solar/Wind Harmer
8.12
970087AG2-069 GEN
Solar/Wind Harmer
18.195
3138133OCRAN
Solar/Wind Harmer
0.136
3145663CRESWEL
Solar/Wind Harmer
0.632
971163AH1-040 GEN
Solar/Wind Harmer
18.07
972197AH1-683 GEN
Adder
4.694
972219AH1-694 GEN
Adder
3.38
316023GEN1_S
Solar/Wind Harmer
0.497
3146206CASHIE
Solar/Wind Harmer
0.219
971547AH1-271 GEN
Solar/Wind Harmer
4.683
316336AC2-165 C
Solar/Wind Harmer
0.009
3145893MURPHYS
Solar/Wind Harmer
0.876
3145893MURPHYS
Solar/Wind Harmer
0.974
957481AF2-042 GEN
Solar/Wind Harmer
58.056
3146173TUNIS
Solar/Wind Harmer
0.217
962861AG1-135 GEN
Solar/Wind Harmer
6.917
960081AF2-299 GEN
Solar/Wind Harmer
2.073
3145683EARLEYS
Solar/Wind Harmer
0.215
3146263WOODLND
Solar/Wind Harmer
0.214
315693AD1-088 GEN
Solar/Wind Harmer
10.231
962491AG1-098 GEN
Solar/Wind Harmer
12.124
316011AB1-132 GEN
Solar/Wind Harmer
3.856
962571AG1-106 GEN
Solar/Wind Harmer
3.018
3141726DUNNSVL
Solar/Wind Harmer
0.847
3145963POPLR C
Solar/Wind Harmer
0.211
971795AH1-408 GEN
Solar/Wind Harmer
14.105
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.211
316174AB2-169 GEN
Solar/Wind Harmer
0.006
3147043LAWRENC
Adder
1.896
3145783HORNRTN
Solar/Wind Harmer
0.209
3150351NORNECKC2
Adder
2.084
3145796HORNRTN
Solar/Wind Harmer
0.689
3145796HORNRTN
Solar/Wind Harmer
0.209
316212AC1-099_GEN
Solar/Wind Harmer
1.054
3146293MARTNCO
Solar/Wind Harmer
0.188
316129AC1-054 GEN
Solar/Wind Harmer
0.758
971065AG2-659 GEN
Solar/Wind Harmer
8.56
316337AD2-073 GEN
Solar/Wind Harmer
0.173
3145746EVERETS
Solar/Wind Harmer
0.199
3145746EVERETS
Solar/Wind Harmer
0.199
315722AD1-056 GEN
Solar/Wind Harmer
1.256
315687AD1-152 GEN
Solar/Wind Harmer
0.006
316494AC1-189 GEN
Solar/Wind Harmer
0.661
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3146233WITAKRS
Solar/Wind Harmer
0.769
961671AG1-007 GEN
Solar/Wind Harmer
0.03
3146083TARBORO
Solar/Wind Harmer
0.193
3145493TOT1
Solar/Wind Harmer
0.859
970685AG2-442 GEN
Solar/Wind Harmer
14.419
970937AG2-583 GEN
Solar/Wind Harmer
11.813
963171AG1-166 GEN
Solar/Wind Harmer
1.027
971563AH1-280 GEN
Solar/Wind Harmer
2.054
3144293JTRSVLE
Adder
0.613
3146926FARMVIL
Solar/Wind Harmer
0.114
3145543BTLEBRO
Solar/Wind Harmer
0.19
3145543BTLEBRO
Solar/Wind Harmer
0.152
316359AB2-059 GEN
Solar/Wind Harmer
0.682
316049AB1-081 GEN
Solar/Wind Harmer
1.086
3142053HEARTS
Solar/Wind Harmer
0.334
970401AG2-262 GEN
Solar/Wind Harmer
1.086
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.072
972003AH1-546 GEN
Solar/Wind Harmer
7.307
972135AH1-637 GEN
Solar/Wind Harmer
1.466
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971377AH1-170 GEN
Solar/Wind Harmer
1.697
3147623JAMES R
Solar/Wind Harmer
0.369
972277AH1-723 GEN
Adder
89.316
3151751LOISA D
Adder
8.255
970223AG2-152 GEN
Solar/Wind Harmer
8.023
316045AC1-158 PL2
Solar/Wind Helper
16.818
316006AB2-029 C
Solar/Wind Helper
0.152
316254AC1-120 GEN1
Solar/Wind Helper
1.388
3152261N ANNA2
50/50
20.433
3150861SPRUNCD
50/50
1.238
3143096IRON208
50/50
1.099
3143096IRON208
50/50
1.077
3150801HOPHCF4
50/50
1.448
971211AH1-065 GEN
50/50
1.746
3151161SURRY 1
50/50
9.371
3147666LOUISA
Solar/Wind Harmer
0.585
315839AE2-212 C
Solar/Wind Harmer
0.002
315773AC2-141 GEN
Solar/Wind Harmer
9.03
965281AG1-393 GEN
Solar/Wind Harmer
2.631
315813AE1-149 C
Solar/Wind Harmer
13.098
970133AG2-095 GEN
Solar/Wind Harmer
2.358
970129AG2-093 GEN
Solar/Wind Harmer
14.818
944581AF1-123 GEN
Solar/Wind Harmer
55.15
944601AF1-125 GEN
Solar/Wind Harmer
54.301
315778AD1-151 GEN
Solar/Wind Harmer
19.588
3151101ELIZAR3
Adder
22.703
3144536CHRHLND
Solar/Wind Harmer
0.037
3144873MCLAUGH
Solar/Wind Harmer
0.006
970659AG2-427 GEN
Solar/Wind Harmer
2.585
3145336SMITFLD
Solar/Wind Harmer
0.098
961611AG1-000B GEN
Solar/Wind Harmer
6.513
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3151221GRAVEL6
Adder
17.737
3151171GRAVELC
Adder
3.413
970293AG2-193 GEN
Solar/Wind Harmer
2.6
3142946ENON
Solar/Wind Harmer
0.081
970661AG2-428 GEN
Solar/Wind Harmer
5.15
3142416OLDCHRC
Solar/Wind Harmer
2.354
3144216WINCHST
Adder
0.913
3146456SLIGO L269
Solar/Wind Harmer
0.242
971153AH1-033 GEN
Solar/Wind Harmer
2.796
3150921YORKTN3
Adder
6.079
316382AG1-145 C
Solar/Wind Harmer
0.002
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
3146516WINFALL
Solar/Wind Harmer
0.236
316473AC1-191 GEN
Solar/Wind Harmer
0.795
3146626S HERTFORD
Solar/Wind Harmer
0.235
3145273HOLLAND
Solar/Wind Harmer
0.176
3141843SHACKLE
Adder
1.184
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
3.085
316280AD1-041 GEN
Solar/Wind Harmer
0.005
3146376EDENTON
Solar/Wind Harmer
0.23
316156AD2-030 GEN
Solar/Wind Harmer
0.17
3141873WAN 176
Solar/Wind Harmer
4.092
316313AB2-026
Solar/Wind Harmer
0.145
316258AE1-075 C
Solar/Wind Harmer
0.173
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.472
970917AG2-570 GEN
Solar/Wind Harmer
20.3
315614AA2-178 GEN
Solar/Wind Harmer
1.293
3150401LDYSMT4
Adder
30.059
3150371LDYSMT1
Adder
29.045
971157AH1-035 GEN
Solar/Wind Harmer
2.667
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
315737AD1-076 GEN
Solar/Wind Harmer
2.851
316365GEN2_N
Solar/Wind Harmer
0.497
962971AG1-146 GEN
Solar/Wind Harmer
3.533
3146206CASHIE
Solar/Wind Harmer
0.219
3145893MURPHYS
Solar/Wind Harmer
0.367
3145893MURPHYS
Solar/Wind Harmer
0.219
970009AG2-005 GEN
Solar/Wind Harmer
1.633
957521AF2-046 GEN
Solar/Wind Harmer
16.257
961681AG1-008 GEN
Solar/Wind Harmer
16.257
3146173TUNIS
Solar/Wind Harmer
0.217
3156021HOLLOMANSOL
Solar/Wind Harmer
0.983
316463AE2-346 GEN
Solar/Wind Harmer
0.186
316140AB2-099
Solar/Wind Harmer
0.077
962331AG1-082 GEN
Solar/Wind Harmer
2.305
316404AE1-155 C
Solar/Wind Harmer
0.048
3146263WOODLND
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.659
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3145963POPLR C
Solar/Wind Harmer
0.211
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.211
3147043LAWRENC
Solar/Wind Harmer
0.126
316478AD1-087 GEN
Solar/Wind Harmer
0.731
316486AD2-202 GEN
Solar/Wind Harmer
0.215
3150351NORNECKC2
Adder
2.12
3145796HORNRTN
Solar/Wind Harmer
0.835
3145796HORNRTN
Solar/Wind Harmer
0.209
316210AC1-098 GEN
Solar/Wind Harmer
1.891
3145933PARMELE
Solar/Wind Harmer
0.203
966801AG1-551 GEN
Solar/Wind Harmer
2.363
971781AH1-399 GEN
Solar/Wind Harmer
0.266
970909AG2-566 GEN
Solar/Wind Harmer
2.131
3145746EVERETS
Solar/Wind Harmer
0.199
3145746EVERETS
Solar/Wind Harmer
0.199
315724AD1-057 GEN
Solar/Wind Harmer
0.745
316327AA2-057 GEN
Solar/Wind Harmer
0.297
316131AB2-060 GEN
Solar/Wind Harmer
0.613
964241AG1-285 GEN
Solar/Wind Harmer
12.969
315785AD2-033 C
Solar/Wind Harmer
1.576
970257AG2-171 GEN
Solar/Wind Harmer
6.198
959311AF2-222 GEN
Solar/Wind Harmer
17.202
3146233WITAKRS
Solar/Wind Harmer
0.97
3146233WITAKRS
Solar/Wind Harmer
0.131
3146073TAR RVR
Solar/Wind Harmer
0.193
3146083TARBORO
Solar/Wind Harmer
0.193
3138543CONSLDL
Solar/Wind Harmer
0.127
963181AG1-167 GEN
Solar/Wind Harmer
0.77
3144293JTRSVLE
Adder
0.613
3147133PAMPLIN
Solar/Wind Harmer
0.603
971193AH1-056 GEN
Solar/Wind Harmer
11.702
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
961601AG1-000A GEN
Solar/Wind Harmer
13.507
3146926FARMVIL
Solar/Wind Harmer
0.114
3145543BTLEBRO
Solar/Wind Harmer
0.19
3145543BTLEBRO
Solar/Wind Harmer
0.19
971623AH1-311 GEN
Solar/Wind Harmer
0.38
3141906WESTMOR
Solar/Wind Harmer
0.075
3146776BUCKING
Solar/Wind Harmer
0.065
970737AG2-469 GEN
Solar/Wind Harmer
7.61
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.598
971683AH1-343 GEN
Solar/Wind Harmer
6.05
316283AC2-100 C
Solar/Wind Harmer
0.314
970221AG2-151 GEN
Solar/Wind Harmer
8.483
972255AH1-712 GEN
Adder
76.646
3151761LOISA E
Adder
16.829
3141316ARNOLDS
Adder
0.299
972183AH1-676 GEN
Adder
129.168
3150331BIRCHWDA
Adder
19.249
316044AC1-158 PL1
Solar/Wind Helper
5.254
316450AC1-158 RIC
Solar/Wind Helper
1.401
316170AC1-121 GEN2
Solar/Wind Helper
0.463
3141196NOKESVL
Solar/Wind Helper
1.151
971133AH1-012 GEN
50/50
5.467
944641AF1-129 GEN
50/50
125.042
3142366NRTHEST
50/50
0.853
970533AG2-339 GEN
50/50
21.877
970531AG2-338 GEN
50/50
8.751
3150781HOPHCF2
50/50
0.996
3150791HOPHCF3
50/50
0.996
3150761HOPPOLC
50/50
0.631
971213AH1-066 GEN
50/50
0.873
3150691DARBY 3
50/50
18.729
3150701DARBY 4
50/50
18.685
971223AH1-071 GEN
Solar/Wind Harmer
2.875
3143526WINTERP
Solar/Wind Harmer
1.363
316240AF1-291 C
Solar/Wind Harmer
0.002
3150681DARBY 2
Adder
17.588
3150671DARBY 1
Adder
17.568
3142296MT RD221
Adder
0.779
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.275
316036AC1-147 C
Solar/Wind Harmer
0.045
3150991CHESPKB
Adder
2.56
3150991CHESPKB
Adder
2.499
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.234
316185AD1-033 GEN
Solar/Wind Harmer
0.007
970657AG2-426 GEN
Solar/Wind Harmer
8.541
970657AG2-426 GEN
Solar/Wind Harmer
1.79
3142946ENON
Solar/Wind Harmer
0.024
3145506HICKORY
Solar/Wind Harmer
0.973
3145506HICKORY
Solar/Wind Harmer
0.584
3145506HICKORY
Solar/Wind Harmer
0.146
316339AD2-160 GEN
Solar/Wind Harmer
0.393
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.135
316075AC2-137 C
Solar/Wind Harmer
0.066
3137176SLIGO L2192
Solar/Wind Harmer
0.963
3146456SLIGO L269
Solar/Wind Harmer
4.28
3130086AYDLETT
Solar/Wind Harmer
0.966
972185AH1-677 GEN
Adder
13.452
3144356SAPONY
Solar/Wind Harmer
2.004
3146386ELIZ CT
Solar/Wind Harmer
0.239
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
972187AH1-678 GEN
Adder
6.746
3146516WINFALL
Solar/Wind Harmer
0.236
3146516WINFALL
Solar/Wind Harmer
0.236
3146516WINFALL
Solar/Wind Harmer
0.236
966871AG1-558 GEN
Solar/Wind Harmer
0.272
3146626S HERTFORD
Solar/Wind Harmer
0.235
3146626S HERTFORD
Solar/Wind Harmer
0.235
970933AG2-581 GEN
Solar/Wind Harmer
18.633
315742AE1-103 GEN
Solar/Wind Harmer
0.003
957411AF2-035 GEN
Solar/Wind Harmer
9.864
970317AG2-208 GEN
Solar/Wind Harmer
9.139
3146376EDENTON
Solar/Wind Harmer
1.025
3146376EDENTON
Solar/Wind Harmer
1.025
315673AE1-157 GEN
Solar/Wind Harmer
15.809
3150391LDYSMT3
Adder
30.003
972195AH1-682 GEN
Adder
3.943
316065AD1-022 GEN
Solar/Wind Harmer
10.141
3145893MURPHYS
Solar/Wind Harmer
1.466
3145893MURPHYS
Solar/Wind Harmer
0.394
970099AG2-077 GEN
Solar/Wind Harmer
23.222
3146173TUNIS
Solar/Wind Harmer
0.217
3146173TUNIS
Solar/Wind Harmer
0.217
958261AF2-120 GEN
Solar/Wind Harmer
7.118
316181AB2-040 GEN
Solar/Wind Harmer
0.309
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3142666NORTHAMPTON
Solar/Wind Harmer
0.128
316426AA2-053 GEN
Solar/Wind Harmer
0.713
3145593CAROLNA
Solar/Wind Harmer
0.21
3145593CAROLNA
Solar/Wind Harmer
0.21
966811AG1-552 GEN
Solar/Wind Harmer
2.282
3145593CAROLNA
Solar/Wind Harmer
0.262
3145783HORNRTN
Solar/Wind Harmer
3.718
3145783HORNRTN
Solar/Wind Harmer
2.974
3145783HORNRTN
Solar/Wind Harmer
0.93
3145783HORNRTN
Solar/Wind Harmer
0.372
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.19
3150341NORNECKC1
Adder
2.172
3145796HORNRTN
Solar/Wind Harmer
0.626
3145933PARMELE
Solar/Wind Harmer
0.406
3145933PARMELE
Solar/Wind Harmer
0.203
971741AH1-377 GEN
Solar/Wind Harmer
20.122
316274AC1-208 GEN
Solar/Wind Harmer
1.051
316468AD1-105 GEN
Solar/Wind Harmer
-0.066
970301AG2-198 GEN
Solar/Wind Harmer
8.524
939181AE1-148 GEN
Solar/Wind Harmer
9.423
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.264
971775AH1-396 GEN
Solar/Wind Harmer
0.31
3145493TOT1
Solar/Wind Harmer
0.448
3145453TOT5
Solar/Wind Harmer
0.269
3145603CNETO
Solar/Wind Harmer
0.179
958211AF2-115 GEN
Solar/Wind Harmer
2.311
963191AG1-168 GEN
Solar/Wind Harmer
0.77
3144293JTRSVLE
Adder
0.613
3144293JTRSVLE
Adder
0.516
3147133PAMPLIN
Solar/Wind Harmer
0.192
3147133PAMPLIN
Solar/Wind Harmer
0.154
961601AG1-000A GEN
Solar/Wind Harmer
3.377
316263AC1-034 GEN
Solar/Wind Harmer
7.215
962561AG1-105 GEN
Solar/Wind Harmer
8.959
964791AG1-342 GEN
Solar/Wind Harmer
3.555
3146843MT LREL
Solar/Wind Harmer
0.185
3146843MT LREL
Solar/Wind Harmer
0.185
3146776BUCKING
Solar/Wind Harmer
0.723
3146776BUCKING
Solar/Wind Harmer
0.059
316222AC1-221 GEN
Solar/Wind Harmer
0.67
971489AH1-241 GEN
Solar/Wind Harmer
8.483
942751AE2-291 GEN
Solar/Wind Harmer
7.393
315821AE2-092 GEN
Solar/Wind Harmer
0.008
3151731LOISA B
Adder
8.255
3151721LOISA A
Adder
8.212
316447AC1-158 HLD
Solar/Wind Helper
11.564
315651AD1-115 GEN
Solar/Wind Helper
1.026
LAGNLTFEXP_LAGN->PJM
CLTF
8.524
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.899
TVALTFEXP_TVA->PJM
CLTF
4.316
NYPJM->LTFIMP_NY
CLTF
3.309
LGEELTFEXP_LGEE->PJM
CLTF
1.392
WECLTFEXP_WEC->PJM
CLTF
0.673
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.369
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.657
MECLTFEXP_MEC->PJM
CLTF
3.808
SIGELTFEXP_SIGE->PJM
CLTF
0.116
CPLELTFEXP_CPLE->PJM
CLTF
12.317
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.813

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.49 %
Rating:3193.18 MVA
Rating Type:A
MVA to Mitigate:3783.56
MW Contribution:5.03
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
17.597
3150861SPRUNCD
50/50
0.898
3151031BRUNSWICKG2
50/50
2.367
3151101ELIZAR3
50/50
17.646
3147666LOUISA
Solar/Wind Harmer
0.507
315773AC2-141 GEN
Solar/Wind Harmer
6.611
315839AE2-212 C
Solar/Wind Harmer
0.001
944581AF1-123 GEN
Solar/Wind Harmer
40.447
944601AF1-125 GEN
Solar/Wind Harmer
39.824
315813AE1-149 C
Solar/Wind Harmer
9.573
3144873MCLAUGH
Solar/Wind Harmer
0.004
965281AG1-393 GEN
Solar/Wind Harmer
1.908
970659AG2-427 GEN
Solar/Wind Harmer
1.891
3144536CHRHLND
Solar/Wind Harmer
0.027
316083AB2-161 GEN
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
3.77
3145336SMITFLD
Solar/Wind Harmer
0.071
3146456SLIGO L269
Solar/Wind Harmer
0.177
971153AH1-033 GEN
Solar/Wind Harmer
2.051
3151221GRAVEL6
Adder
12.86
3151171GRAVELC
Adder
2.474
961611AG1-000B GEN
Solar/Wind Harmer
4.714
315778AD1-151 GEN
Solar/Wind Harmer
14.128
970129AG2-093 GEN
Solar/Wind Harmer
10.67
970133AG2-095 GEN
Solar/Wind Harmer
1.693
3143096IRON208
Adder
0.737
3143096IRON208
Adder
0.722
316320Y1-086
Solar/Wind Harmer
0.001
3144216WINCHST
Adder
0.657
316435W1029_GEN3
Solar/Wind Harmer
0.001
316313AB2-026
Solar/Wind Harmer
0.11
316258AE1-075 C
Solar/Wind Harmer
0.131
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.631
3146516WINFALL
Solar/Wind Harmer
0.174
3150921YORKTN3
Adder
4.366
970917AG2-570 GEN
Solar/Wind Harmer
15.39
3146626S HERTFORD
Solar/Wind Harmer
0.173
3145273HOLLAND
Solar/Wind Harmer
0.129
3142946ENON
Solar/Wind Harmer
0.058
316382AG1-145 C
Solar/Wind Harmer
0.001
970293AG2-193 GEN
Solar/Wind Harmer
1.821
3146376EDENTON
Solar/Wind Harmer
0.17
3152251N ANNA1
50/50
17.599
970119AG2-088 GEN
50/50
27.254
3150851SPRUNCC
50/50
0.898
315243AE2-183_GT3
50/50
3.006
3151051BRUNSWICKS1
50/50
4.913
3151021BRUNSWICKG1
50/50
2.367
971451AH1-221 GEN
50/50
7.19
3150981CHESPKA
50/50
2.372
3147666LOUISA
Solar/Wind Harmer
0.882
316192AB2-158 GEN
Solar/Wind Harmer
1.212
3143226MDLTHAN
Solar/Wind Harmer
0.204
3143526WINTERP
Solar/Wind Harmer
1.012
940641AE2-051 GEN
Solar/Wind Harmer
15.302
939411AE1-173 GEN
Solar/Wind Harmer
80.278
316294AC1-161 GEN
Solar/Wind Harmer
3.136
944591AF1-124 GEN
Solar/Wind Harmer
40.591
316375AC2-012 GEN
Solar/Wind Harmer
0.005
970659AG2-427 GEN
Solar/Wind Harmer
8.643
316381AD1-082 GEN
Solar/Wind Harmer
0.186
315671AE2-027_GEN
Solar/Wind Harmer
11.421
970661AG2-428 GEN
Solar/Wind Harmer
17.724
3142543TWELFTH
Solar/Wind Harmer
0.017
316388AE2-253 GEN
Solar/Wind Harmer
0.557
3145336SMITFLD
Solar/Wind Harmer
0.711
3146456SLIGO L269
Solar/Wind Harmer
0.177
316246AF1-032 C
Solar/Wind Harmer
0.08
316303AF2-085
50/50
3.634
971285AH1-108 GEN
50/50
1.469
315244AE2-183_ST
50/50
5.196
963041AG1-153 GEN
50/50
4.793
3151081ELIZAR1
50/50
17.423
3151091ELIZAR2
50/50
17.121
941591AE2-156 GEN
50/50
15.921
3152611GOSPORTB
50/50
2.419
3152621GOSPORTC
50/50
2.053
3152601GOSPORTA
50/50
1.894
315779AE2-040
50/50
2.493
316233AE1-074 FULL
Solar/Wind Harmer
0.156
971281AH1-106 GEN
Solar/Wind Harmer
2.702
971283AH1-107 GEN
Solar/Wind Harmer
2.702
941031AE2-094 GEN
Solar/Wind Harmer
34.43
944011AF1-069 GEN
Solar/Wind Harmer
11.25
970673AG2-436 GEN
Solar/Wind Harmer
39.174
970673AG2-436 GEN
Solar/Wind Harmer
26.116
3143316POE
Solar/Wind Harmer
0.721
971967AH1-528 GEN
Solar/Wind Harmer
28.994
316315AB2-025 C
Solar/Wind Harmer
0.144
315814AE2-033 C
Solar/Wind Harmer
14.072
957871AF2-081 GEN
Solar/Wind Harmer
8.849
971445AH1-216 GEN
Solar/Wind Harmer
12.508
319010AE1-072 C
Solar/Wind Harmer
0.893
3146406KITTY HAWK
Solar/Wind Harmer
0.022
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.121
316311AC2-079 GEN
Solar/Wind Harmer
5.087
316305AF2-043 C
Solar/Wind Harmer
0.001
972265AH1-717 GEN
Adder
13.734
3151201GRAVEL4
Adder
12.875
3151191GRAVEL3
Adder
12.712
3151211GRAVEL5
Adder
12.712
316369SG1_INVT
Solar/Wind Harmer
0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.947
315835AF2-110_GEN
Solar/Wind Harmer
1.21
313526AB2-022
Solar/Wind Harmer
0.095
3146486SUNBURY
Solar/Wind Harmer
0.175
3146486SUNBURY
Solar/Wind Harmer
0.175
316321Z2-027
Solar/Wind Harmer
0.033
3146396TANGLEW
Solar/Wind Harmer
0.483
3145176PASQUOTANK
Solar/Wind Harmer
0.109
970085AG2-068 GEN
Solar/Wind Harmer
9.195
970581AG2-369 GEN
Solar/Wind Harmer
7.908
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.17
3130156CHOWAN
Solar/Wind Harmer
0.17
315976AC1-164 GENA
Solar/Wind Harmer
17.467
316169AC1-164_GENC
Solar/Wind Harmer
15.09
315975AC1-164 GENB
Solar/Wind Harmer
0.517
3138283WHITEMARSH
Solar/Wind Harmer
0.039
971167AH1-042 GEN
Solar/Wind Harmer
14.927
316312AB1-027
Solar/Wind Harmer
0.3
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
315816AE2-034 GEN
Solar/Wind Harmer
0.714
3143873LANEXA
Solar/Wind Harmer
0.099
3130546PLYMOUTH
Solar/Wind Harmer
0.164
315732AD1-074 GEN1
Solar/Wind Harmer
0.939
315733AD1-074 GEN2
Solar/Wind Harmer
0.939
315735AD1-075 GEN1
Solar/Wind Harmer
0.47
965291AG1-394 GEN
Solar/Wind Harmer
0.726
970189AG2-124 GEN
Solar/Wind Harmer
4.842
316314AB2-024 C
Solar/Wind Harmer
0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.032
3146206CASHIE
Solar/Wind Harmer
0.162
970601AG2-382 GEN
Solar/Wind Harmer
6.052
3145893MURPHYS
Solar/Wind Harmer
0.437
3145893MURPHYS
Solar/Wind Harmer
0.162
3145513AHOSKIE
Solar/Wind Harmer
0.334
3145513AHOSKIE
Solar/Wind Harmer
0.16
3141913WHIT STONE
Solar/Wind Harmer
0.16
3146043SEABORD
Solar/Wind Harmer
0.16
316087AB2-174 GEN
Solar/Wind Harmer
0.005
972189AH1-679 GEN
Adder
2.672
3138133OCRAN
Solar/Wind Harmer
0.048
315607AA1-063A GEN
Solar/Wind Harmer
0.325
3145683EARLEYS
Solar/Wind Harmer
0.318
3145683EARLEYS
Solar/Wind Harmer
0.159
3145683EARLEYS
Solar/Wind Harmer
0.159
3141783LANCAST
Solar/Wind Harmer
0.095
3141783LANCAST
Solar/Wind Harmer
0.063
315652AC1-086 GEN
Solar/Wind Harmer
17.349
3137643SOCKMAN
Solar/Wind Harmer
0.629
3145796HORNRTN
Solar/Wind Harmer
0.497
3145796HORNRTN
Solar/Wind Harmer
0.062
962981AG1-147 GEN
Solar/Wind Harmer
5.785
3146033SCOT NK
Solar/Wind Harmer
0.614
970327AG2-215 GEN
Solar/Wind Harmer
5.03
970831AG2-522 GEN
Solar/Wind Harmer
6.456
316005AA1-067
Solar/Wind Harmer
0.158
3145746EVERETS
Solar/Wind Harmer
0.587
3145746EVERETS
Solar/Wind Harmer
0.147
3145746EVERETS
Solar/Wind Harmer
0.147
3145746EVERETS
Solar/Wind Harmer
0.147
970181AG2-120 GEN
Solar/Wind Harmer
1.837
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
2.45
3144303KENBRDG
Solar/Wind Harmer
0.117
3141813NORNECK
Solar/Wind Harmer
0.146
957861AF2-080 GEN
Solar/Wind Harmer
6.272
970683AG2-441 GEN
Solar/Wind Harmer
9.698
970681AG2-440 GEN
Solar/Wind Harmer
7.758
946301AF1-294 GEN
Solar/Wind Harmer
2.864
961791AG1-021 GEN
Solar/Wind Harmer
1.393
315657AE1-056 GEN
Solar/Wind Harmer
4.998
316420AA1-050 GEN
Solar/Wind Harmer
0.005
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.144
3145573BETHELC
Solar/Wind Harmer
0.144
970285AG2-188 GEN
Solar/Wind Harmer
10.95
971845AH1-439 GEN
Solar/Wind Harmer
6.225
3150411LDYSMT5
Adder
18.406
3150381LDYSMT2
Adder
17.615
972213AH1-691 GEN
Adder
2.98
972215AH1-692 GEN
Adder
2.98
316118AC1-105 GEN
Solar/Wind Harmer
0.352
3147173SINAI
Solar/Wind Harmer
0.134
3147243WELCO
Solar/Wind Harmer
0.084
316223AC1-118
Solar/Wind Harmer
0.093
972205AH1-687 GEN
Adder
5.489
970865AG2-541 GEN
Solar/Wind Harmer
4.099
971447AH1-217 GEN
Solar/Wind Harmer
3.524
316164AC1-076 GEN
Solar/Wind Helper
1.636
971133AH1-012 GEN
50/50
4.727
970533AG2-339 GEN
50/50
16.617
970531AG2-338 GEN
50/50
6.647
315242AE2-183_GT2
50/50
3.006
315241AE2-183_GT1
50/50
2.987
972185AH1-677 GEN
50/50
10.835
3151041BRUNSWICKG3
50/50
2.367
972187AH1-678 GEN
50/50
5.432
3150991CHESPKB
50/50
1.99
3150991CHESPKB
50/50
1.942
971223AH1-071 GEN
Solar/Wind Harmer
2.18
3143526WINTERP
Solar/Wind Harmer
1.012
316036AC1-147 C
Solar/Wind Harmer
0.033
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.172
316185AD1-033 GEN
Solar/Wind Harmer
0.005
316240AF1-291 C
Solar/Wind Harmer
0.001
3144356SAPONY
Solar/Wind Harmer
1.494
3145506HICKORY
Solar/Wind Harmer
0.714
3145506HICKORY
Solar/Wind Harmer
0.428
3145506HICKORY
Solar/Wind Harmer
0.107
970657AG2-426 GEN
Solar/Wind Harmer
6.25
970657AG2-426 GEN
Solar/Wind Harmer
1.31
944641AF1-129 GEN
Adder
84.93
316339AD2-160 GEN
Solar/Wind Harmer
0.288
316018AA1-139 ULT2
Solar/Wind Harmer
0.004
316017AA1-139 ULT1
Solar/Wind Harmer
0.099
316236AE1-162_GEN
Solar/Wind Harmer
0.001
3137176SLIGO L2192
Solar/Wind Harmer
0.706
3146456SLIGO L269
Solar/Wind Harmer
3.14
3130086AYDLETT
Solar/Wind Harmer
0.709
970933AG2-581 GEN
Solar/Wind Harmer
14.133
316033AB2-134 GEN
Solar/Wind Harmer
0.01
315697AD1-025 GEN
Solar/Wind Harmer
0.199
3146386ELIZ CT
Solar/Wind Harmer
0.176
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.174
3146516WINFALL
Solar/Wind Harmer
0.174
3146516WINFALL
Solar/Wind Harmer
0.174
3142366NRTHEST
Adder
0.565
3146626S HERTFORD
Solar/Wind Harmer
0.173
3146626S HERTFORD
Solar/Wind Harmer
0.173
3142946ENON
Solar/Wind Harmer
0.017
3150691DARBY 3
Adder
12.388
3150701DARBY 4
Adder
12.359
3150681DARBY 2
Adder
12.344
3150671DARBY 1
Adder
12.33
315742AE1-103 GEN
Solar/Wind Harmer
0.002
3146376EDENTON
Solar/Wind Harmer
0.754
3146376EDENTON
Solar/Wind Harmer
0.754
316075AC2-137 C
Solar/Wind Harmer
0.046
3142296MT RD221
Adder
0.537
970099AG2-077 GEN
Solar/Wind Harmer
17.581
316065AD1-022 GEN
Solar/Wind Harmer
7.487
3145893MURPHYS
Solar/Wind Harmer
1.084
3145893MURPHYS
Solar/Wind Harmer
0.291
966871AG1-558 GEN
Solar/Wind Harmer
0.187
3146173TUNIS
Solar/Wind Harmer
0.161
3146173TUNIS
Solar/Wind Harmer
0.161
316181AB2-040 GEN
Solar/Wind Harmer
0.23
3142666NORTHAMPTON
Solar/Wind Harmer
0.158
3142666NORTHAMPTON
Solar/Wind Harmer
0.158
3142666NORTHAMPTON
Solar/Wind Harmer
0.158
3142666NORTHAMPTON
Solar/Wind Harmer
0.095
316426AA2-053 GEN
Solar/Wind Harmer
0.53
3145593CAROLNA
Solar/Wind Harmer
0.156
3145593CAROLNA
Solar/Wind Harmer
0.156
966811AG1-552 GEN
Solar/Wind Harmer
1.698
3145593CAROLNA
Solar/Wind Harmer
0.195
3145783HORNRTN
Solar/Wind Harmer
2.766
3145783HORNRTN
Solar/Wind Harmer
2.213
3145783HORNRTN
Solar/Wind Harmer
0.692
3145783HORNRTN
Solar/Wind Harmer
0.277
3145796HORNRTN
Solar/Wind Harmer
0.466
971741AH1-377 GEN
Solar/Wind Harmer
15.218
970301AG2-198 GEN
Solar/Wind Harmer
6.446
316274AC1-208 GEN
Solar/Wind Harmer
0.781
958261AF2-120 GEN
Solar/Wind Harmer
4.978
3145933PARMELE
Solar/Wind Harmer
0.301
3145933PARMELE
Solar/Wind Harmer
0.15
939181AE1-148 GEN
Solar/Wind Harmer
7.079
957411AF2-035 GEN
Solar/Wind Harmer
6.288
970317AG2-208 GEN
Solar/Wind Harmer
5.826
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.011
970323AG2-213 GEN
Solar/Wind Harmer
6.221
971775AH1-396 GEN
Solar/Wind Harmer
0.233
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.525
3150341NORNECKC1
Adder
1.513
958211AF2-115 GEN
Solar/Wind Harmer
1.742
963191AG1-168 GEN
Solar/Wind Harmer
0.581
3144293JTRSVLE
Adder
0.462
3144293JTRSVLE
Adder
0.389
3147133PAMPLIN
Solar/Wind Harmer
0.145
3147133PAMPLIN
Solar/Wind Harmer
0.116
3145493TOT1
Solar/Wind Harmer
0.333
3145453TOT5
Solar/Wind Harmer
0.2
3145603CNETO
Solar/Wind Harmer
0.133
315673AE1-157 GEN
Solar/Wind Harmer
9.924
961601AG1-000A GEN
Solar/Wind Harmer
2.515
316263AC1-034 GEN
Solar/Wind Harmer
5.374
962561AG1-105 GEN
Solar/Wind Harmer
6.736
964791AG1-342 GEN
Solar/Wind Harmer
2.673
3146843MT LREL
Solar/Wind Harmer
0.139
3146843MT LREL
Solar/Wind Harmer
0.139
316468AD1-105 GEN
Solar/Wind Harmer
-0.045
3150391LDYSMT3
Adder
18.314
972195AH1-682 GEN
Adder
2.407
3146776BUCKING
Solar/Wind Harmer
0.547
3146776BUCKING
Solar/Wind Harmer
0.044
316222AC1-221 GEN
Solar/Wind Harmer
0.503
971489AH1-241 GEN
Solar/Wind Harmer
6.389
316447AC1-158 HLD
Solar/Wind Helper
11.807
3142416OLDCHRC
Solar/Wind Harmer
1.628
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
315614AA2-178 GEN
Solar/Wind Harmer
0.952
316365GEN2_N
Solar/Wind Harmer
0.37
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
971157AH1-035 GEN
Solar/Wind Harmer
1.967
315737AD1-076 GEN
Solar/Wind Harmer
2.103
3141843SHACKLE
Adder
0.835
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
2.172
316156AD2-030 GEN
Solar/Wind Harmer
0.12
3141873WAN 176
Solar/Wind Harmer
2.887
3146206CASHIE
Solar/Wind Harmer
0.162
3145893MURPHYS
Solar/Wind Harmer
0.271
3145893MURPHYS
Solar/Wind Harmer
0.162
316473AC1-191 GEN
Solar/Wind Harmer
0.547
957521AF2-046 GEN
Solar/Wind Harmer
12.028
961681AG1-008 GEN
Solar/Wind Harmer
12.028
3146173TUNIS
Solar/Wind Harmer
0.161
3156021HOLLOMANSOL
Solar/Wind Harmer
0.727
316463AE2-346 GEN
Solar/Wind Harmer
0.137
316140AB2-099
Solar/Wind Harmer
0.057
962331AG1-082 GEN
Solar/Wind Harmer
1.706
313506AB2-031 GEN
Solar/Wind Harmer
0.491
3146263WOODLND
Solar/Wind Harmer
0.158
316478AD1-087 GEN
Solar/Wind Harmer
0.553
316486AD2-202 GEN
Solar/Wind Harmer
0.162
3142666NORTHAMPTON
Solar/Wind Harmer
0.158
3147043LAWRENC
Solar/Wind Harmer
0.094
3145963POPLR C
Solar/Wind Harmer
0.156
316317KELFORD C
Solar/Wind Harmer
0.015
3145823KELFORD
Solar/Wind Harmer
0.156
3145796HORNRTN
Solar/Wind Harmer
0.621
3145796HORNRTN
Solar/Wind Harmer
0.155
962971AG1-146 GEN
Solar/Wind Harmer
2.479
970009AG2-005 GEN
Solar/Wind Harmer
1.144
316210AC1-098 GEN
Solar/Wind Harmer
1.405
970909AG2-566 GEN
Solar/Wind Harmer
1.611
316404AE1-155 C
Solar/Wind Harmer
0.034
3145933PARMELE
Solar/Wind Harmer
0.15
966801AG1-551 GEN
Solar/Wind Harmer
1.752
315724AD1-057 GEN
Solar/Wind Harmer
0.554
3145746EVERETS
Solar/Wind Harmer
0.147
3145746EVERETS
Solar/Wind Harmer
0.147
316131AB2-060 GEN
Solar/Wind Harmer
0.461
316327AA2-057 GEN
Solar/Wind Harmer
0.221
964241AG1-285 GEN
Solar/Wind Harmer
9.755
315785AD2-033 C
Solar/Wind Harmer
1.187
970257AG2-171 GEN
Solar/Wind Harmer
4.666
959311AF2-222 GEN
Solar/Wind Harmer
12.953
3150351NORNECKC2
Adder
1.476
963181AG1-167 GEN
Solar/Wind Harmer
0.581
3144293JTRSVLE
Adder
0.462
3147133PAMPLIN
Solar/Wind Harmer
0.455
971193AH1-056 GEN
Solar/Wind Harmer
8.824
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146233WITAKRS
Solar/Wind Harmer
0.722
3146233WITAKRS
Solar/Wind Harmer
0.098
3146073TAR RVR
Solar/Wind Harmer
0.144
3146083TARBORO
Solar/Wind Harmer
0.144
3138543CONSLDL
Solar/Wind Harmer
0.095
3146926FARMVIL
Solar/Wind Harmer
0.086
961601AG1-000A GEN
Solar/Wind Harmer
10.061
3145543BTLEBRO
Solar/Wind Harmer
0.141
3145543BTLEBRO
Solar/Wind Harmer
0.141
971623AH1-311 GEN
Solar/Wind Harmer
0.283
971781AH1-399 GEN
Solar/Wind Harmer
0.181
3150401LDYSMT4
Adder
18.348
3150371LDYSMT1
Adder
17.729
3146776BUCKING
Solar/Wind Harmer
0.049
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.713
3141906WESTMOR
Solar/Wind Harmer
0.052
971683AH1-343 GEN
Solar/Wind Harmer
4.538
970737AG2-469 GEN
Solar/Wind Harmer
5.206
316283AC2-100 C
Solar/Wind Harmer
0.236
970221AG2-151 GEN
Solar/Wind Harmer
6.389
316044AC1-158 PL1
Solar/Wind Helper
5.365
316450AC1-158 RIC
Solar/Wind Helper
1.431
3151171GRAVELC
Adder
1.882
316072AD1-144
Solar/Wind Harmer
0.064
961611AG1-000B GEN
Solar/Wind Harmer
9.271
971647AH1-324 GEN
Solar/Wind Harmer
7.54
971069AG2-661 GEN
Solar/Wind Harmer
3.14
316458AB2-190 GEN2
Solar/Wind Harmer
0.947
970129AG2-093 GEN
Solar/Wind Harmer
5.021
316093AE2-104_GEN
Solar/Wind Harmer
2.965
3143096IRON208
Adder
0.737
3143336POWHATN
Solar/Wind Harmer
3.095
3138126ROCKLANDING
Solar/Wind Harmer
0.08
3146516WINFALL
Solar/Wind Harmer
0.563
3146516WINFALL
Solar/Wind Harmer
0.174
944631AF1-128 GEN
Adder
82.804
970919AG2-571 GEN
Solar/Wind Harmer
6.156
970087AG2-069 GEN
Solar/Wind Harmer
13.793
971317AH1-138 GEN
Solar/Wind Harmer
1.284
316159AE1-175 C
Solar/Wind Harmer
0.148
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.17
3142416OLDCHRC
Solar/Wind Harmer
0.437
3142416OLDCHRC
Solar/Wind Harmer
0.167
3142433PROV 92
Solar/Wind Harmer
0.669
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
3145663CRESWEL
Solar/Wind Harmer
0.466
971163AH1-040 GEN
Solar/Wind Harmer
13.314
316336AC2-165 C
Solar/Wind Harmer
0.006
316023GEN1_S
Solar/Wind Harmer
0.37
957481AF2-042 GEN
Solar/Wind Harmer
43.952
971777AH1-397 GEN
Solar/Wind Harmer
0.431
3141843SHACKLE
Adder
0.835
3141766HARMONY
Solar/Wind Harmer
0.033
3146206CASHIE
Solar/Wind Harmer
0.162
971547AH1-271 GEN
Solar/Wind Harmer
3.458
3145893MURPHYS
Solar/Wind Harmer
0.648
3145893MURPHYS
Solar/Wind Harmer
0.72
315693AD1-088 GEN
Solar/Wind Harmer
7.741
960081AF2-299 GEN
Solar/Wind Harmer
1.545
962491AG1-098 GEN
Solar/Wind Harmer
9.173
3146173TUNIS
Solar/Wind Harmer
0.161
3138133OCRAN
Solar/Wind Harmer
0.096
3145683EARLEYS
Solar/Wind Harmer
0.159
3146263WOODLND
Solar/Wind Harmer
0.158
971795AH1-408 GEN
Solar/Wind Harmer
10.53
316011AB1-132 GEN
Solar/Wind Harmer
2.868
962571AG1-106 GEN
Solar/Wind Harmer
2.244
316190AA2-174 GEN
Solar/Wind Harmer
0
3147043LAWRENC
Adder
1.417
3145963POPLR C
Solar/Wind Harmer
0.156
3145823KELFORD
Solar/Wind Harmer
0.156
3145783HORNRTN
Solar/Wind Harmer
0.155
3145796HORNRTN
Solar/Wind Harmer
0.512
3145796HORNRTN
Solar/Wind Harmer
0.155
316174AB2-169 GEN
Solar/Wind Harmer
0.004
316212AC1-099_GEN
Solar/Wind Harmer
0.783
962861AG1-135 GEN
Solar/Wind Harmer
4.841
316129AC1-054 GEN
Solar/Wind Harmer
0.567
3146293MARTNCO
Solar/Wind Harmer
0.139
971065AG2-659 GEN
Solar/Wind Harmer
6.41
315687AD1-152 GEN
Solar/Wind Harmer
0.005
3141726DUNNSVL
Solar/Wind Harmer
0.591
315722AD1-056 GEN
Solar/Wind Harmer
0.935
3145746EVERETS
Solar/Wind Harmer
0.147
3145746EVERETS
Solar/Wind Harmer
0.147
966881AG1-559 GEN
Solar/Wind Harmer
0.17
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970937AG2-583 GEN
Solar/Wind Harmer
8.939
3150351NORNECKC2
Adder
1.452
316494AC1-189 GEN
Solar/Wind Harmer
0.491
970685AG2-442 GEN
Solar/Wind Harmer
10.862
963171AG1-166 GEN
Solar/Wind Harmer
0.774
971563AH1-280 GEN
Solar/Wind Harmer
1.548
3144293JTRSVLE
Adder
0.462
3146233WITAKRS
Solar/Wind Harmer
0.573
961671AG1-007 GEN
Solar/Wind Harmer
0.022
3146083TARBORO
Solar/Wind Harmer
0.144
3145493TOT1
Solar/Wind Harmer
0.639
3146926FARMVIL
Solar/Wind Harmer
0.086
3145543BTLEBRO
Solar/Wind Harmer
0.141
3145543BTLEBRO
Solar/Wind Harmer
0.113
316359AB2-059 GEN
Solar/Wind Harmer
0.508
316049AB1-081 GEN
Solar/Wind Harmer
0.809
3142053HEARTS
Solar/Wind Harmer
0.249
970401AG2-262 GEN
Solar/Wind Harmer
0.817
316337AD2-073 GEN
Solar/Wind Harmer
0.12
972197AH1-683 GEN
Adder
2.865
972219AH1-694 GEN
Adder
2.063
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.055
972003AH1-546 GEN
Solar/Wind Harmer
5.523
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971377AH1-170 GEN
Solar/Wind Harmer
1.278
3147623JAMES R
Solar/Wind Harmer
0.278
972135AH1-637 GEN
Solar/Wind Harmer
0.998
316045AC1-158 PL2
Solar/Wind Helper
17.173
316006AB2-029 C
Solar/Wind Helper
0.112
LAGNLTFEXP_LAGN->PJM
CLTF
6.271
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.05
TVALTFEXP_TVA->PJM
CLTF
3.173
NYPJM->LTFIMP_NY
CLTF
2.427
LGEELTFEXP_LGEE->PJM
CLTF
1
WECLTFEXP_WEC->PJM
CLTF
0.483
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.977
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.753
MECLTFEXP_MEC->PJM
CLTF
2.757
SIGELTFEXP_SIGE->PJM
CLTF
0.083
CPLELTFEXP_CPLE->PJM
CLTF
9.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.048

Details for 8POSSUM-BURCHES 500.0 kV Ckt 1 line l/o AP_P1-2_PE-500-406T_SRT-A


Base Case Flowgate

Area:DVP/PJM
Facility Description:
8POSSUM-BURCHES 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-406T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.05 %
Rating:2913.06 MVA
Rating Type:B
MVA to Mitigate:3060.21
MW Contribution:4.57
Bus #Bus NameTypeMW Contribution
3150101POSSM6S
50/50
2.207
3150081POSSM6A
50/50
1.444
3150151POSSMC1
50/50
1.946
3150151POSSMC1
50/50
1.946
3150331BIRCHWDA
50/50
29.368
3150021OMF B
50/50
0.313
3141316ARNOLDS
50/50
0.404
3150401LDYSMT4
50/50
22.067
3150371LDYSMT1
50/50
21.323
970497AG2-320 GEN
50/50
14.416
970737AG2-469 GEN
Solar/Wind Harmer
6.342
3141906WESTMOR
Solar/Wind Harmer
0.059
971781AH1-399 GEN
Solar/Wind Harmer
0.191
3150351NORNECKC2
Adder
1.435
316404AE1-155 C
Solar/Wind Harmer
0.032
970009AG2-005 GEN
Solar/Wind Harmer
1.04
962971AG1-146 GEN
Solar/Wind Harmer
2.22
316473AC1-191 GEN
Solar/Wind Harmer
0.469
316156AD2-030 GEN
Solar/Wind Harmer
0.101
3141873WAN 176
Solar/Wind Harmer
2.426
3141766HARMONY
Solar/Wind Harmer
1.82
3142416OLDCHRC
Solar/Wind Harmer
1.322
316280AD1-041 GEN
Solar/Wind Harmer
0.003
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141843SHACKLE
Adder
0.697
3142433PROV 92
Adder
0.264
3142433PROV 92
Adder
0.264
970293AG2-193 GEN
Solar/Wind Harmer
1.446
3142946ENON
Solar/Wind Harmer
0.045
3143096IRON208
Adder
0.563
3143096IRON208
Adder
0.552
316044AC1-158 PL1
Solar/Wind Harmer
0.654
316450AC1-158 RIC
Solar/Wind Harmer
0.174
3150861SPRUNCD
Adder
0.616
316382AG1-145 C
Solar/Wind Harmer
0.001
970133AG2-095 GEN
Solar/Wind Harmer
1.273
970129AG2-093 GEN
Solar/Wind Harmer
7.987
3150921YORKTN3
Adder
3.319
3144216WINCHST
Adder
0.497
315778AD1-151 GEN
Solar/Wind Harmer
10.543
965281AG1-393 GEN
Solar/Wind Harmer
1.404
315839AE2-212 C
Solar/Wind Harmer
0.001
3147666LOUISA
Solar/Wind Harmer
0.302
961611AG1-000B GEN
Solar/Wind Harmer
3.495
3151221GRAVEL6
Adder
9.505
3151171GRAVELC
Adder
1.829
3145336SMITFLD
Solar/Wind Harmer
0.052
315813AE1-149 C
Solar/Wind Harmer
6.935
315773AC2-141 GEN
Solar/Wind Harmer
4.737
970659AG2-427 GEN
Solar/Wind Harmer
1.37
3144536CHRHLND
Solar/Wind Harmer
0.019
316083AB2-161 GEN
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
2.731
3151101ELIZAR3
Adder
11.981
3144873MCLAUGH
Solar/Wind Harmer
0.003
944581AF1-123 GEN
Solar/Wind Harmer
29.029
944601AF1-125 GEN
Solar/Wind Harmer
28.582
316170AC1-121 GEN2
Solar/Wind Harmer
0.137
3146456SLIGO L269
Solar/Wind Harmer
0.128
971153AH1-033 GEN
Solar/Wind Harmer
1.481
316320Y1-086
Solar/Wind Harmer
0.001
3132273ORANGE
Solar/Wind Harmer
0.025
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.126
3146626S HERTFORD
Solar/Wind Harmer
0.126
3145273HOLLAND
Solar/Wind Harmer
0.094
316313AB2-026
Solar/Wind Harmer
0.079
316258AE1-075 C
Solar/Wind Harmer
0.095
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
1.895
3146376EDENTON
Solar/Wind Harmer
0.124
3151761LOISA E
Adder
16.466
972183AH1-676 GEN
Adder
132.605
315614AA2-178 GEN
Solar/Wind Harmer
0.703
3150301M RUN C
Adder
16.643
3150291M RUN B
Adder
16.52
3150231REMNGT3
Adder
16.71
3150241REMNGT4
Adder
15.58
972199AH1-684 GEN
Adder
2.362
972217AH1-693 GEN
Adder
2.054
971157AH1-035 GEN
Solar/Wind Harmer
1.461
3156081AA2-088 GEN
Solar/Wind Harmer
0.003
315737AD1-076 GEN
Solar/Wind Harmer
1.564
3146206CASHIE
Solar/Wind Harmer
0.121
3145893MURPHYS
Solar/Wind Harmer
0.202
3145893MURPHYS
Solar/Wind Harmer
0.121
316365GEN2_N
Solar/Wind Harmer
0.271
957521AF2-046 GEN
Solar/Wind Harmer
8.962
961681AG1-008 GEN
Solar/Wind Harmer
8.962
970917AG2-570 GEN
Solar/Wind Harmer
10.673
3146173TUNIS
Solar/Wind Harmer
0.12
3156021HOLLOMANSOL
Solar/Wind Harmer
0.544
316463AE2-346 GEN
Solar/Wind Harmer
0.103
316140AB2-099
Solar/Wind Harmer
0.043
962331AG1-082 GEN
Solar/Wind Harmer
1.276
3141196NOKESVL
Solar/Wind Harmer
0.475
3146263WOODLND
Solar/Wind Harmer
0.119
313506AB2-031 GEN
Solar/Wind Harmer
0.366
3145963POPLR C
Solar/Wind Harmer
0.118
3142666NORTHAMPTON
Solar/Wind Harmer
0.118
316317KELFORD C
Solar/Wind Harmer
0.011
3145823KELFORD
Solar/Wind Harmer
0.118
3147043LAWRENC
Solar/Wind Harmer
0.071
3145796HORNRTN
Solar/Wind Harmer
0.468
3145796HORNRTN
Solar/Wind Harmer
0.117
970909AG2-566 GEN
Solar/Wind Harmer
1.246
316478AD1-087 GEN
Solar/Wind Harmer
0.406
316486AD2-202 GEN
Solar/Wind Harmer
0.119
3146926FARMVIL
Solar/Wind Harmer
0.07
316210AC1-098 GEN
Solar/Wind Harmer
1.074
3146776BUCKING
Solar/Wind Harmer
0.042
3145933PARMELE
Solar/Wind Harmer
0.115
966801AG1-551 GEN
Solar/Wind Harmer
1.346
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
972255AH1-712 GEN
Adder
58.961
3147133PAMPLIN
Solar/Wind Harmer
0.361
971193AH1-056 GEN
Solar/Wind Harmer
7.005
963181AG1-167 GEN
Solar/Wind Harmer
0.459
3144293JTRSVLE
Adder
0.366
959311AF2-222 GEN
Solar/Wind Harmer
10.172
970257AG2-171 GEN
Solar/Wind Harmer
3.659
3145746EVERETS
Solar/Wind Harmer
0.114
3145746EVERETS
Solar/Wind Harmer
0.114
315785AD2-033 C
Solar/Wind Harmer
0.929
964241AG1-285 GEN
Solar/Wind Harmer
7.598
315724AD1-057 GEN
Solar/Wind Harmer
0.428
316131AB2-060 GEN
Solar/Wind Harmer
0.358
316327AA2-057 GEN
Solar/Wind Harmer
0.171
970221AG2-151 GEN
Solar/Wind Harmer
6.002
227287AC2-120 GEN
Solar/Wind Helper
1.283
226910AB2-157 C
Solar/Wind Helper
0.05
223402AF1-300 C
Solar/Wind Helper
0.698
233918AB1-142 GEN
Solar/Wind Helper
0.486
233982AB2-133 GEN
Solar/Wind Helper
0.346
233994AC2-023 GEN
Solar/Wind Helper
0.923
233996TM1833_GEN
Solar/Wind Helper
0.251
233997TMININ_4.2
Solar/Wind Helper
0.251
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.036
232406W1-004 FULL
Solar/Wind Helper
0.487
233952AC2-187 GEN
Solar/Wind Helper
0.223
233971AC1-093 C
Solar/Wind Helper
0.342
970053AG2-049 GEN
50/50
2.771
3150411LDYSMT5
50/50
22.136
3150381LDYSMT2
50/50
21.185
972213AH1-691 GEN
50/50
3.584
972215AH1-692 GEN
50/50
3.584
963051AG1-154 GEN
50/50
2.757
3141426STAFORD
Solar/Wind Harmer
0.039
944491AF1-114 GEN
Solar/Wind Harmer
0
316223AC1-118
Solar/Wind Harmer
0.105
972189AH1-679 GEN
Adder
2.375
3141813NORNECK
Solar/Wind Harmer
0.141
970327AG2-215 GEN
Solar/Wind Harmer
4.571
962981AG1-147 GEN
Solar/Wind Harmer
5.181
3141783LANCAST
Solar/Wind Harmer
0.083
3141783LANCAST
Solar/Wind Harmer
0.055
3138133OCRAN
Solar/Wind Harmer
0.041
3141913WHIT STONE
Solar/Wind Harmer
0.137
3141873WAN 176
Solar/Wind Harmer
0.027
316059AD1-063 C
Solar/Wind Harmer
0.001
316314AB2-024 C
Solar/Wind Harmer
0
316312AB1-027
Solar/Wind Harmer
0.244
315662AE1-191 GEN
Solar/Wind Harmer
0.004
315666AE1-190 GEN
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.04
3143873LANEXA
Solar/Wind Harmer
0.082
3142433PROV 92
Adder
0.264
3142433PROV 92
Adder
0.264
971167AH1-042 GEN
Solar/Wind Harmer
12.03
315976AC1-164 GENA
Solar/Wind Harmer
14.027
316169AC1-164_GENC
Solar/Wind Harmer
12.118
315975AC1-164 GENB
Solar/Wind Harmer
0.415
3138283WHITEMARSH
Solar/Wind Harmer
0.031
971285AH1-108 GEN
Adder
1.008
316233AE1-074 FULL
Solar/Wind Harmer
0.107
971281AH1-106 GEN
Solar/Wind Harmer
1.847
971283AH1-107 GEN
Solar/Wind Harmer
1.847
316164AC1-076 GEN
Solar/Wind Harmer
0.186
316132AB2-190 GEN1
Solar/Wind Harmer
0.709
316369SG1_INVT
Solar/Wind Harmer
0.005
972265AH1-717 GEN
Adder
10.151
3151201GRAVEL4
Adder
9.516
3151191GRAVEL3
Adder
9.395
3151211GRAVEL5
Adder
9.395
971445AH1-216 GEN
Solar/Wind Harmer
9.164
3143316POE
Solar/Wind Harmer
0.514
3151081ELIZAR1
Adder
11.83
3151091ELIZAR2
Adder
11.624
3152611GOSPORTB
Adder
1.643
3152621GOSPORTC
Adder
1.395
3152601GOSPORTA
Adder
1.287
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.088
316311AC2-079 GEN
Solar/Wind Harmer
3.686
957871AF2-081 GEN
Solar/Wind Harmer
6.385
316305AF2-043 C
Solar/Wind Harmer
0.001
319010AE1-072 C
Solar/Wind Harmer
0.645
3146406KITTY HAWK
Solar/Wind Harmer
0.016
315835AF2-110_GEN
Solar/Wind Harmer
0.877
313526AB2-022
Solar/Wind Harmer
0.069
3146486SUNBURY
Solar/Wind Harmer
0.127
3146486SUNBURY
Solar/Wind Harmer
0.127
316321Z2-027
Solar/Wind Harmer
0.024
3146396TANGLEW
Solar/Wind Harmer
0.35
3145176PASQUOTANK
Solar/Wind Harmer
0.079
316315AB2-025 C
Solar/Wind Harmer
0.101
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
315814AE2-033 C
Solar/Wind Harmer
9.914
941031AE2-094 GEN
Solar/Wind Harmer
22.955
944011AF1-069 GEN
Solar/Wind Harmer
7.5
3130156CHOWAN
Solar/Wind Harmer
0.124
3130156CHOWAN
Solar/Wind Harmer
0.124
970673AG2-436 GEN
Solar/Wind Harmer
26.361
970673AG2-436 GEN
Solar/Wind Harmer
17.574
971967AH1-528 GEN
Solar/Wind Harmer
19.675
315816AE2-034 GEN
Solar/Wind Harmer
0.528
3147346CASHSCORNER
Solar/Wind Harmer
0.285
3130546PLYMOUTH
Solar/Wind Harmer
0.122
315732AD1-074 GEN1
Solar/Wind Harmer
0.698
315733AD1-074 GEN2
Solar/Wind Harmer
0.698
315735AD1-075 GEN1
Solar/Wind Harmer
0.35
965291AG1-394 GEN
Solar/Wind Harmer
0.539
3146206CASHIE
Solar/Wind Harmer
0.121
970601AG2-382 GEN
Solar/Wind Harmer
4.511
3145893MURPHYS
Solar/Wind Harmer
0.326
3145893MURPHYS
Solar/Wind Harmer
0.121
970085AG2-068 GEN
Solar/Wind Harmer
6.391
970581AG2-369 GEN
Solar/Wind Harmer
5.496
3145513AHOSKIE
Solar/Wind Harmer
0.25
3145513AHOSKIE
Solar/Wind Harmer
0.12
3145683EARLEYS
Solar/Wind Harmer
0.239
3145683EARLEYS
Solar/Wind Harmer
0.119
3145683EARLEYS
Solar/Wind Harmer
0.119
3146043SEABORD
Solar/Wind Harmer
0.119
315607AA1-063A GEN
Solar/Wind Harmer
0.243
316087AB2-174 GEN
Solar/Wind Harmer
0.003
315652AC1-086 GEN
Solar/Wind Harmer
12.981
3137643SOCKMAN
Solar/Wind Harmer
0.471
3145796HORNRTN
Solar/Wind Harmer
0.374
3145796HORNRTN
Solar/Wind Harmer
0.047
3146033SCOT NK
Solar/Wind Harmer
0.467
970285AG2-188 GEN
Solar/Wind Harmer
9.159
971845AH1-439 GEN
Solar/Wind Harmer
5.245
970831AG2-522 GEN
Solar/Wind Harmer
4.918
972193AH1-681 GEN
Adder
2.634
972205AH1-687 GEN
Adder
4.919
315657AE1-056 GEN
Solar/Wind Harmer
3.968
946301AF1-294 GEN
Solar/Wind Harmer
2.267
961791AG1-021 GEN
Solar/Wind Harmer
1.103
970683AG2-441 GEN
Solar/Wind Harmer
7.642
970681AG2-440 GEN
Solar/Wind Harmer
6.113
3144303KENBRDG
Solar/Wind Harmer
0.091
971443AH1-215 GEN
Solar/Wind Harmer
1.921
316005AA1-067
Solar/Wind Harmer
0.123
3145746EVERETS
Solar/Wind Harmer
0.455
3145746EVERETS
Solar/Wind Harmer
0.114
3145746EVERETS
Solar/Wind Harmer
0.114
3145746EVERETS
Solar/Wind Harmer
0.114
970181AG2-120 GEN
Solar/Wind Harmer
1.422
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
957861AF2-080 GEN
Solar/Wind Harmer
4.883
316420AA1-050 GEN
Solar/Wind Harmer
0.004
233935AB2-179 C
Solar/Wind Helper
1.237
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.92
233990AG1-397 GEN
Solar/Wind Helper
0.259
232432Z2-076 GEN
Solar/Wind Helper
0.064
234033AF1-007_GEN
Solar/Wind Helper
6.733
972223AH1-696 GEN
50/50
15.369
3150151POSSMC1
50/50
1.946
3141346CRANES
50/50
0.214
3150011OMF A
50/50
0.313
3140676OCCOQUN
50/50
0.415
972197AH1-683 GEN
50/50
3.446
972219AH1-694 GEN
50/50
2.481
972135AH1-637 GEN
Solar/Wind Harmer
1.281
966881AG1-559 GEN
Solar/Wind Harmer
0.172
316337AD2-073 GEN
Solar/Wind Harmer
0.125
3150351NORNECKC2
Adder
1.412
3141726DUNNSVL
Solar/Wind Harmer
0.564
962861AG1-135 GEN
Solar/Wind Harmer
4.477
3138133OCRAN
Solar/Wind Harmer
0.082
3141766HARMONY
Solar/Wind Harmer
0.027
3142416OLDCHRC
Solar/Wind Harmer
0.355
3142416OLDCHRC
Solar/Wind Harmer
0.136
971777AH1-397 GEN
Solar/Wind Harmer
0.36
3141843SHACKLE
Adder
0.697
3142433PROV 92
Solar/Wind Harmer
0.542
3142433PROV 92
Adder
0.264
3142433PROV 92
Adder
0.264
3143096IRON208
Adder
0.563
316045AC1-158 PL2
Solar/Wind Harmer
2.091
944631AF1-128 GEN
Adder
63.967
3142543TWELFTH
Solar/Wind Harmer
0.013
3150851SPRUNCC
Adder
0.616
316159AE1-175 C
Solar/Wind Harmer
0.115
3143526WINTERP
Solar/Wind Harmer
0.692
971317AH1-138 GEN
Solar/Wind Harmer
0.993
3143226MDLTHAN
Solar/Wind Harmer
0.132
970129AG2-093 GEN
Solar/Wind Harmer
3.759
316458AB2-190 GEN2
Solar/Wind Harmer
0.709
315671AE2-027_GEN
Solar/Wind Harmer
8.445
3138126ROCKLANDING
Solar/Wind Harmer
0.061
971069AG2-661 GEN
Solar/Wind Harmer
2.343
971647AH1-324 GEN
Solar/Wind Harmer
5.603
3147666LOUISA
Solar/Wind Harmer
0.525
961611AG1-000B GEN
Solar/Wind Harmer
6.873
316192AB2-158 GEN
Solar/Wind Harmer
0.74
3151171GRAVELC
Adder
1.391
3145336SMITFLD
Solar/Wind Harmer
0.52
316294AC1-161 GEN
Solar/Wind Harmer
2.247
970659AG2-427 GEN
Solar/Wind Harmer
6.262
316381AD1-082 GEN
Solar/Wind Harmer
0.135
970661AG2-428 GEN
Solar/Wind Harmer
12.841
316375AC2-012 GEN
Solar/Wind Harmer
0.003
3150981CHESPKA
Adder
1.611
944591AF1-124 GEN
Solar/Wind Harmer
29.132
316072AD1-144
Solar/Wind Harmer
0.047
316254AC1-120 GEN1
Solar/Wind Harmer
0.274
316388AE2-253 GEN
Solar/Wind Harmer
0.402
3146456SLIGO L269
Solar/Wind Harmer
0.128
316246AF1-032 C
Solar/Wind Harmer
0.058
316093AE2-104_GEN
Solar/Wind Harmer
2.148
939411AE1-173 GEN
Solar/Wind Harmer
54.47
940641AE2-051 GEN
Solar/Wind Harmer
10.185
3146516WINFALL
Solar/Wind Harmer
0.409
3146516WINFALL
Solar/Wind Harmer
0.126
3143336POWHATN
Solar/Wind Harmer
2.23
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.124
3151751LOISA D
Adder
8.077
316006AB2-029 C
Solar/Wind Harmer
0.001
971685AH1-345 GEN
Solar/Wind Harmer
0.923
316336AC2-165 C
Solar/Wind Harmer
0.005
315683AE1-153 C
Solar/Wind Harmer
9.818
3145663CRESWEL
Solar/Wind Harmer
0.344
971163AH1-040 GEN
Solar/Wind Harmer
9.834
3150281M RUN A
Adder
16.653
3150221REMNGT2
Adder
15.477
3150211REMNGT1
Adder
15.375
972201AH1-685 GEN
Adder
2.67
3146206CASHIE
Solar/Wind Harmer
0.121
971547AH1-271 GEN
Solar/Wind Harmer
2.578
3145893MURPHYS
Solar/Wind Harmer
0.482
3145893MURPHYS
Solar/Wind Harmer
0.536
316023GEN1_S
Solar/Wind Harmer
0.271
970919AG2-571 GEN
Solar/Wind Harmer
4.269
3146173TUNIS
Solar/Wind Harmer
0.12
970087AG2-069 GEN
Solar/Wind Harmer
9.586
3145683EARLEYS
Solar/Wind Harmer
0.119
960081AF2-299 GEN
Solar/Wind Harmer
1.144
970937AG2-583 GEN
Solar/Wind Harmer
7.301
3146263WOODLND
Solar/Wind Harmer
0.119
957481AF2-042 GEN
Solar/Wind Harmer
31.564
3145963POPLR C
Solar/Wind Harmer
0.118
3145823KELFORD
Solar/Wind Harmer
0.118
316011AB1-132 GEN
Solar/Wind Harmer
2.146
971795AH1-408 GEN
Solar/Wind Harmer
7.87
962571AG1-106 GEN
Solar/Wind Harmer
1.679
316190AA2-174 GEN
Solar/Wind Harmer
0
315693AD1-088 GEN
Solar/Wind Harmer
5.655
316174AB2-169 GEN
Solar/Wind Harmer
0.003
962491AG1-098 GEN
Solar/Wind Harmer
6.721
3147043LAWRENC
Adder
1.063
3145783HORNRTN
Solar/Wind Harmer
0.117
3145796HORNRTN
Solar/Wind Harmer
0.386
3145796HORNRTN
Solar/Wind Harmer
0.117
3146926FARMVIL
Solar/Wind Harmer
0.07
316212AC1-099_GEN
Solar/Wind Harmer
0.599
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.046
3146293MARTNCO
Solar/Wind Harmer
0.107
972003AH1-546 GEN
Solar/Wind Harmer
4.897
972277AH1-723 GEN
Adder
68.708
316129AC1-054 GEN
Solar/Wind Harmer
0.433
963171AG1-166 GEN
Solar/Wind Harmer
0.613
971563AH1-280 GEN
Solar/Wind Harmer
1.225
3144293JTRSVLE
Adder
0.366
971065AG2-659 GEN
Solar/Wind Harmer
4.897
970685AG2-442 GEN
Solar/Wind Harmer
8.558
3145746EVERETS
Solar/Wind Harmer
0.114
3145746EVERETS
Solar/Wind Harmer
0.114
315722AD1-056 GEN
Solar/Wind Harmer
0.721
316237AB2-079_GEN
Solar/Wind Harmer
0.001
316494AC1-189 GEN
Solar/Wind Harmer
0.383
315687AD1-152 GEN
Solar/Wind Harmer
0.004
971377AH1-170 GEN
Solar/Wind Harmer
1.2
3147623JAMES R
Solar/Wind Harmer
0.261
223401AF1-299 GEN
Solar/Wind Helper
0.698
233930AB2-032 GEN
Solar/Wind Helper
0.368
233915AB1-141 GEN
Solar/Wind Helper
0.486
232422X3-066 FULL
Solar/Wind Helper
0.11
233964AF2-378 GEN
Solar/Wind Helper
0.04
232426Y1-080 FULL
Solar/Wind Helper
0.037
232428Y3-058 C
Solar/Wind Helper
0.325
233998TM1NIN_3.36
Solar/Wind Helper
0.251
232404W1-003 C
Solar/Wind Helper
0.487
233954AC2-188 GEN
Solar/Wind Helper
0.223
233950AC2-186 GEN
Solar/Wind Helper
0.111
232434Z2-077 GEN
Solar/Wind Helper
0.122
233972AC1-094 C
Solar/Wind Helper
0.289
3150091POSSM6B
50/50
1.444
3150071POSSM 5
50/50
88.927
3150181POSSMC2
50/50
1.962
3150181POSSMC2
50/50
1.946
3150181POSSMC2
50/50
1.946
957191AF2-013 GEN
50/50
14.065
3150391LDYSMT3
50/50
22.026
972195AH1-682 GEN
50/50
2.894
315673AE1-157 GEN
Solar/Wind Harmer
10.452
957411AF2-035 GEN
Solar/Wind Harmer
6.351
970317AG2-208 GEN
Solar/Wind Harmer
5.884
316468AD1-105 GEN
Solar/Wind Harmer
-0.047
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.483
3150341NORNECKC1
Adder
1.471
958261AF2-120 GEN
Solar/Wind Harmer
4.633
966871AG1-558 GEN
Solar/Wind Harmer
0.16
3142296MT RD221
Adder
0.436
316075AC2-137 C
Solar/Wind Harmer
0.037
3150691DARBY 3
Adder
9.75
3150701DARBY 4
Adder
9.728
3150681DARBY 2
Adder
9.716
3150671DARBY 1
Adder
9.705
3142366NRTHEST
Adder
0.443
3142946ENON
Solar/Wind Harmer
0.013
316447AC1-158 HLD
Solar/Wind Harmer
1.437
3143526WINTERP
Solar/Wind Harmer
0.692
944641AF1-129 GEN
Adder
63.136
971223AH1-071 GEN
Solar/Wind Harmer
1.411
316240AF1-291 C
Solar/Wind Harmer
0.001
316033AB2-134 GEN
Solar/Wind Harmer
0.008
315697AD1-025 GEN
Solar/Wind Harmer
0.148
316236AE1-162_GEN
Solar/Wind Harmer
0.001
970657AG2-426 GEN
Solar/Wind Harmer
4.528
970657AG2-426 GEN
Solar/Wind Harmer
0.949
316036AC1-147 C
Solar/Wind Harmer
0.024
3150991CHESPKB
Adder
1.352
3150991CHESPKB
Adder
1.319
316316AC1-027 C
Solar/Wind Harmer
0.124
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.004
3145506HICKORY
Solar/Wind Harmer
0.514
3145506HICKORY
Solar/Wind Harmer
0.308
3145506HICKORY
Solar/Wind Harmer
0.077
316339AD2-160 GEN
Solar/Wind Harmer
0.208
316018AA1-139 ULT2
Solar/Wind Harmer
0.003
316017AA1-139 ULT1
Solar/Wind Harmer
0.072
3137176SLIGO L2192
Solar/Wind Harmer
0.51
3146456SLIGO L269
Solar/Wind Harmer
2.267
3130086AYDLETT
Solar/Wind Harmer
0.512
315651AD1-115 GEN
Solar/Wind Harmer
0.004
3146386ELIZ CT
Solar/Wind Harmer
0.127
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.126
3146516WINFALL
Solar/Wind Harmer
0.126
3146516WINFALL
Solar/Wind Harmer
0.126
3146626S HERTFORD
Solar/Wind Harmer
0.126
3146626S HERTFORD
Solar/Wind Harmer
0.126
3144356SAPONY
Solar/Wind Harmer
1.05
315742AE1-103 GEN
Solar/Wind Harmer
0.001
966001AG1-469 GEN
Solar/Wind Harmer
0.073
3146376EDENTON
Solar/Wind Harmer
0.553
3146376EDENTON
Solar/Wind Harmer
0.553
3151731LOISA B
Adder
8.077
3151721LOISA A
Adder
8.035
972185AH1-677 GEN
Adder
6.905
972187AH1-678 GEN
Adder
3.484
970933AG2-581 GEN
Solar/Wind Harmer
9.737
316065AD1-022 GEN
Solar/Wind Harmer
5.575
3145893MURPHYS
Solar/Wind Harmer
0.807
3145893MURPHYS
Solar/Wind Harmer
0.217
3146173TUNIS
Solar/Wind Harmer
0.12
3146173TUNIS
Solar/Wind Harmer
0.12
316181AB2-040 GEN
Solar/Wind Harmer
0.172
970099AG2-077 GEN
Solar/Wind Harmer
12.626
3142666NORTHAMPTON
Solar/Wind Harmer
0.118
3142666NORTHAMPTON
Solar/Wind Harmer
0.118
3142666NORTHAMPTON
Solar/Wind Harmer
0.118
3142666NORTHAMPTON
Solar/Wind Harmer
0.071
316426AA2-053 GEN
Solar/Wind Harmer
0.398
3145593CAROLNA
Solar/Wind Harmer
0.118
3145593CAROLNA
Solar/Wind Harmer
0.118
966811AG1-552 GEN
Solar/Wind Harmer
1.276
3145593CAROLNA
Solar/Wind Harmer
0.146
3145783HORNRTN
Solar/Wind Harmer
2.085
3145783HORNRTN
Solar/Wind Harmer
1.668
3145783HORNRTN
Solar/Wind Harmer
0.521
3145783HORNRTN
Solar/Wind Harmer
0.209
3145796HORNRTN
Solar/Wind Harmer
0.351
971741AH1-377 GEN
Solar/Wind Harmer
11.611
970301AG2-198 GEN
Solar/Wind Harmer
4.984
3146776BUCKING
Solar/Wind Harmer
0.462
3146776BUCKING
Solar/Wind Harmer
0.037
3145933PARMELE
Solar/Wind Harmer
0.231
3145933PARMELE
Solar/Wind Harmer
0.115
316274AC1-208 GEN
Solar/Wind Harmer
0.598
3147133PAMPLIN
Solar/Wind Harmer
0.115
3147133PAMPLIN
Solar/Wind Harmer
0.092
958211AF2-115 GEN
Solar/Wind Harmer
1.378
963191AG1-168 GEN
Solar/Wind Harmer
0.459
3144293JTRSVLE
Adder
0.366
3144293JTRSVLE
Adder
0.308
316034AC1-036 C
Solar/Wind Harmer
0.008
970323AG2-213 GEN
Solar/Wind Harmer
4.879
971775AH1-396 GEN
Solar/Wind Harmer
0.183
313527AB2-043 GEN
Solar/Wind Harmer
0.001
939181AE1-148 GEN
Solar/Wind Harmer
5.453
971489AH1-241 GEN
Solar/Wind Harmer
6.002
226929AD2-058 GEN
Solar/Wind Helper
0.401
208835TUHI V3-051
Solar/Wind Helper
0.03
208835TUHI V3-051
Solar/Wind Helper
0.03
233933AB2-153 GEN
Solar/Wind Helper
0.225
233944AB2-135 GEN
Solar/Wind Helper
0.569
232424Y1-079 C
Solar/Wind Helper
0.112
233987AB2-037 GEN
Solar/Wind Helper
2.251
234036AF2-325 C
Solar/Wind Helper
0.04
233946AB2-136 GEN
Solar/Wind Helper
0.546
233901CHERRYDALE C
Solar/Wind Helper
0.223
232408W1-005 C
Solar/Wind Helper
0.487
232410W1-006 C
Solar/Wind Helper
0.487
233939AC1-091 C
Solar/Wind Helper
0.335
233970AC1-092 C
Solar/Wind Helper
0.335
LAGNLTFEXP_LAGN->PJM
CLTF
10.825
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.705
TVALTFEXP_TVA->PJM
CLTF
5.449
NYPJM->LTFIMP_NY
CLTF
3.769
LGEELTFEXP_LGEE->PJM
CLTF
3.18
WECLTFEXP_WEC->PJM
CLTF
1.706
AG2-052LTFEXP_AG2-052->PJM
LTF
0.101
AH1-155LTFEXP_AH1-155->PJM
LTF
0.152
CBM West 1LTFEXP_CBM-W1->PJM
CBM
63.366
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.907
MECLTFEXP_MEC->PJM
CLTF
7.822
SIGELTFEXP_SIGE->PJM
CLTF
0.246
CPLELTFEXP_CPLE->PJM
CLTF
8.254
CBM West 2LTFEXP_CBM-W2->PJM
CBM
67.489

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:179.85 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5791.82
MW Contribution:7.03
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
19.951
971507AH1-251 GEN
50/50
16.627
970119AG2-088 GEN
50/50
35.342
3150851SPRUNCC
50/50
1.216
3143096IRON208
50/50
1.079
3152331SURRY 2
50/50
9.986
3150771HOPHCF1
50/50
0.977
316045AC1-158 PL2
Solar/Wind Harmer
9.742
3147666LOUISA
Solar/Wind Harmer
1.096
316192AB2-158 GEN
Solar/Wind Harmer
1.516
3143226MDLTHAN
Solar/Wind Harmer
0.265
3143526WINTERP
Solar/Wind Harmer
1.34
940641AE2-051 GEN
Solar/Wind Harmer
19.885
939411AE1-173 GEN
Solar/Wind Harmer
105.071
3142543TWELFTH
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
4.205
315671AE2-027_GEN
Solar/Wind Harmer
15.49
970129AG2-093 GEN
Solar/Wind Harmer
6.846
316458AB2-190 GEN2
Solar/Wind Harmer
1.291
944591AF1-124 GEN
Solar/Wind Harmer
54.321
971069AG2-661 GEN
Solar/Wind Harmer
4.273
944631AF1-128 GEN
Adder
114.478
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.995
971647AH1-324 GEN
Solar/Wind Harmer
10.238
970659AG2-427 GEN
Solar/Wind Harmer
11.598
961611AG1-000B GEN
Solar/Wind Harmer
12.573
3145336SMITFLD
Solar/Wind Harmer
0.958
316381AD1-082 GEN
Solar/Wind Harmer
0.25
3151171GRAVELC
Adder
2.547
970661AG2-428 GEN
Solar/Wind Harmer
23.769
3142416OLDCHRC
Solar/Wind Harmer
0.62
971531AH1-263 GEN
50/50
60.398
316303AF2-085
50/50
4.712
971285AH1-108 GEN
50/50
1.991
970603AG2-384 GEN
50/50
5.178
316164AC1-076 GEN
Solar/Wind Harmer
0.448
316233AE1-074 FULL
Solar/Wind Harmer
0.206
971281AH1-106 GEN
Solar/Wind Harmer
3.576
971283AH1-107 GEN
Solar/Wind Harmer
3.576
3143316POE
Solar/Wind Harmer
0.962
941031AE2-094 GEN
Solar/Wind Harmer
44.489
944011AF1-069 GEN
Solar/Wind Harmer
14.536
316132AB2-190 GEN1
Solar/Wind Harmer
1.291
316369SG1_INVT
Solar/Wind Harmer
0.009
3151081ELIZAR1
Adder
22.001
3151091ELIZAR2
Adder
21.619
3152611GOSPORTB
Adder
3.055
3152621GOSPORTC
Adder
2.593
3152601GOSPORTA
Adder
2.392
971445AH1-216 GEN
Solar/Wind Harmer
16.874
972265AH1-717 GEN
Adder
18.594
3151201GRAVEL4
Adder
17.43
3151191GRAVEL3
Adder
17.21
3151211GRAVEL5
Adder
17.21
316312AB1-027
Solar/Wind Harmer
0.427
957871AF2-081 GEN
Solar/Wind Harmer
11.843
970673AG2-436 GEN
Solar/Wind Harmer
50.646
970673AG2-436 GEN
Solar/Wind Harmer
33.764
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.163
319010AE1-072 C
Solar/Wind Harmer
1.195
316311AC2-079 GEN
Solar/Wind Harmer
6.813
3146406KITTY HAWK
Solar/Wind Harmer
0.03
316305AF2-043 C
Solar/Wind Harmer
0.002
315976AC1-164 GENA
Solar/Wind Harmer
24.491
316169AC1-164_GENC
Solar/Wind Harmer
21.158
315975AC1-164 GENB
Solar/Wind Harmer
0.725
315835AF2-110_GEN
Solar/Wind Harmer
1.619
316315AB2-025 C
Solar/Wind Harmer
0.19
313526AB2-022
Solar/Wind Harmer
0.127
972189AH1-679 GEN
Adder
3.932
3146486SUNBURY
Solar/Wind Harmer
0.234
3146486SUNBURY
Solar/Wind Harmer
0.234
971967AH1-528 GEN
Solar/Wind Harmer
37.517
315814AE2-033 C
Solar/Wind Harmer
18.537
316321Z2-027
Solar/Wind Harmer
0.044
3146396TANGLEW
Solar/Wind Harmer
0.645
3145176PASQUOTANK
Solar/Wind Harmer
0.145
971167AH1-042 GEN
Solar/Wind Harmer
20.705
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
3138283WHITEMARSH
Solar/Wind Harmer
0.054
3143873LANEXA
Solar/Wind Harmer
0.138
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
316314AB2-024 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.735
316059AD1-063 C
Solar/Wind Harmer
0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.226
3130156CHOWAN
Solar/Wind Harmer
0.226
3141873WAN 176
Solar/Wind Harmer
0.045
970085AG2-068 GEN
Solar/Wind Harmer
11.907
970581AG2-369 GEN
Solar/Wind Harmer
10.24
3141913WHIT STONE
Solar/Wind Harmer
0.222
3138133OCRAN
Solar/Wind Harmer
0.066
315816AE2-034 GEN
Solar/Wind Harmer
0.951
3141783LANCAST
Solar/Wind Harmer
0.132
3141783LANCAST
Solar/Wind Harmer
0.088
3150411LDYSMT5
Adder
29.481
3150381LDYSMT2
Adder
28.214
972213AH1-691 GEN
Adder
4.773
972215AH1-692 GEN
Adder
4.773
3130546PLYMOUTH
Solar/Wind Harmer
0.218
315732AD1-074 GEN1
Solar/Wind Harmer
1.25
315733AD1-074 GEN2
Solar/Wind Harmer
1.25
315735AD1-075 GEN1
Solar/Wind Harmer
0.626
965291AG1-394 GEN
Solar/Wind Harmer
0.964
962981AG1-147 GEN
Solar/Wind Harmer
8.079
3146206CASHIE
Solar/Wind Harmer
0.215
970601AG2-382 GEN
Solar/Wind Harmer
8.044
3145893MURPHYS
Solar/Wind Harmer
0.581
3145893MURPHYS
Solar/Wind Harmer
0.215
970327AG2-215 GEN
Solar/Wind Harmer
7.032
3145513AHOSKIE
Solar/Wind Harmer
0.443
3145513AHOSKIE
Solar/Wind Harmer
0.212
3146043SEABORD
Solar/Wind Harmer
0.211
3145683EARLEYS
Solar/Wind Harmer
0.422
3145683EARLEYS
Solar/Wind Harmer
0.211
3145683EARLEYS
Solar/Wind Harmer
0.211
315607AA1-063A GEN
Solar/Wind Harmer
0.431
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
22.91
3137643SOCKMAN
Solar/Wind Harmer
0.831
3145796HORNRTN
Solar/Wind Harmer
0.656
3145796HORNRTN
Solar/Wind Harmer
0.082
3141813NORNECK
Solar/Wind Harmer
0.205
3146033SCOT NK
Solar/Wind Harmer
0.813
970831AG2-522 GEN
Solar/Wind Harmer
8.493
316005AA1-067
Solar/Wind Harmer
0.209
3145746EVERETS
Solar/Wind Harmer
0.776
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
970181AG2-120 GEN
Solar/Wind Harmer
2.429
957861AF2-080 GEN
Solar/Wind Harmer
8.286
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
3.225
3144303KENBRDG
Solar/Wind Harmer
0.153
970683AG2-441 GEN
Solar/Wind Harmer
12.781
970681AG2-440 GEN
Solar/Wind Harmer
10.225
946301AF1-294 GEN
Solar/Wind Harmer
3.778
961791AG1-021 GEN
Solar/Wind Harmer
1.838
315657AE1-056 GEN
Solar/Wind Harmer
6.598
316420AA1-050 GEN
Solar/Wind Harmer
0.006
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.189
3145573BETHELC
Solar/Wind Harmer
0.189
970285AG2-188 GEN
Solar/Wind Harmer
14.603
316223AC1-118
Solar/Wind Harmer
0.132
971845AH1-439 GEN
Solar/Wind Harmer
8.313
316118AC1-105 GEN
Solar/Wind Harmer
0.462
3147173SINAI
Solar/Wind Harmer
0.175
3147243WELCO
Solar/Wind Harmer
0.11
972205AH1-687 GEN
Adder
7.416
3147346CASHSCORNER
Solar/Wind Harmer
0.37
944491AF1-114 GEN
Solar/Wind Harmer
0.001
971447AH1-217 GEN
Solar/Wind Harmer
4.798
970865AG2-541 GEN
Solar/Wind Harmer
5.388
972193AH1-681 GEN
Adder
3.397
270494AE1-108_GEN
Solar/Wind Harmer
1.716
3142416OLDCHRC
Solar/Wind Harmer
0.237
316388AE2-253 GEN
Solar/Wind Harmer
0.746
3138126ROCKLANDING
Solar/Wind Harmer
0.109
3146456SLIGO L269
Solar/Wind Harmer
0.237
316072AD1-144
Solar/Wind Harmer
0.086
316159AE1-175 C
Solar/Wind Harmer
0.205
316246AF1-032 C
Solar/Wind Harmer
0.107
971317AH1-138 GEN
Solar/Wind Harmer
1.763
316093AE2-104_GEN
Solar/Wind Harmer
3.967
3142433PROV 92
Solar/Wind Harmer
0.929
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
3146516WINFALL
Solar/Wind Harmer
0.752
3146516WINFALL
Solar/Wind Harmer
0.232
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.063
971777AH1-397 GEN
Solar/Wind Harmer
0.6
3141843SHACKLE
Adder
1.161
3141766HARMONY
Solar/Wind Harmer
0.045
3130156CHOWAN
Solar/Wind Harmer
0.226
966881AG1-559 GEN
Solar/Wind Harmer
0.262
970919AG2-571 GEN
Solar/Wind Harmer
7.971
970087AG2-069 GEN
Solar/Wind Harmer
17.86
3138133OCRAN
Solar/Wind Harmer
0.133
3145663CRESWEL
Solar/Wind Harmer
0.62
971163AH1-040 GEN
Solar/Wind Harmer
17.736
972197AH1-683 GEN
Adder
4.589
972219AH1-694 GEN
Adder
3.304
316336AC2-165 C
Solar/Wind Harmer
0.009
316023GEN1_S
Solar/Wind Harmer
0.488
3146206CASHIE
Solar/Wind Harmer
0.215
971547AH1-271 GEN
Solar/Wind Harmer
4.597
3145893MURPHYS
Solar/Wind Harmer
0.86
3145893MURPHYS
Solar/Wind Harmer
0.956
957481AF2-042 GEN
Solar/Wind Harmer
57.154
3146173TUNIS
Solar/Wind Harmer
0.213
960081AF2-299 GEN
Solar/Wind Harmer
2.037
962861AG1-135 GEN
Solar/Wind Harmer
6.776
3145683EARLEYS
Solar/Wind Harmer
0.211
315693AD1-088 GEN
Solar/Wind Harmer
10.092
3146263WOODLND
Solar/Wind Harmer
0.21
962491AG1-098 GEN
Solar/Wind Harmer
11.964
316011AB1-132 GEN
Solar/Wind Harmer
3.787
962571AG1-106 GEN
Solar/Wind Harmer
2.963
971795AH1-408 GEN
Solar/Wind Harmer
13.875
3145963POPLR C
Solar/Wind Harmer
0.207
3141726DUNNSVL
Solar/Wind Harmer
0.83
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.207
3147043LAWRENC
Adder
1.866
316174AB2-169 GEN
Solar/Wind Harmer
0.005
3145783HORNRTN
Solar/Wind Harmer
0.205
3145796HORNRTN
Solar/Wind Harmer
0.677
3145796HORNRTN
Solar/Wind Harmer
0.205
3150351NORNECKC2
Adder
2.041
316212AC1-099_GEN
Solar/Wind Harmer
1.035
3146293MARTNCO
Solar/Wind Harmer
0.185
316129AC1-054 GEN
Solar/Wind Harmer
0.746
971065AG2-659 GEN
Solar/Wind Harmer
8.425
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
315722AD1-056 GEN
Solar/Wind Harmer
1.233
316337AD2-073 GEN
Solar/Wind Harmer
0.169
970937AG2-583 GEN
Solar/Wind Harmer
11.922
315687AD1-152 GEN
Solar/Wind Harmer
0.006
316494AC1-189 GEN
Solar/Wind Harmer
0.649
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
14.314
963171AG1-166 GEN
Solar/Wind Harmer
1.021
971563AH1-280 GEN
Solar/Wind Harmer
2.042
3144293JTRSVLE
Adder
0.609
3146926FARMVIL
Solar/Wind Harmer
0.114
3146233WITAKRS
Solar/Wind Harmer
0.755
961671AG1-007 GEN
Solar/Wind Harmer
0.029
3146083TARBORO
Solar/Wind Harmer
0.189
3145493TOT1
Solar/Wind Harmer
0.843
3145543BTLEBRO
Solar/Wind Harmer
0.186
3145543BTLEBRO
Solar/Wind Harmer
0.149
316359AB2-059 GEN
Solar/Wind Harmer
0.669
316049AB1-081 GEN
Solar/Wind Harmer
1.066
3142053HEARTS
Solar/Wind Harmer
0.328
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.073
970401AG2-262 GEN
Solar/Wind Harmer
1.071
972003AH1-546 GEN
Solar/Wind Harmer
7.446
316254AC1-120 GEN1
Solar/Wind Harmer
0.366
316003AC1-222 GEN
Solar/Wind Harmer
0.004
3151751LOISA D
Adder
10.898
972135AH1-637 GEN
Solar/Wind Harmer
1.429
971377AH1-170 GEN
Solar/Wind Harmer
1.734
3147623JAMES R
Solar/Wind Harmer
0.377
972277AH1-723 GEN
Adder
88.606
3152261N ANNA2
50/50
19.95
3150861SPRUNCD
50/50
1.216
3143096IRON208
50/50
1.079
3143096IRON208
50/50
1.057
3150801HOPHCF4
50/50
1.421
971211AH1-065 GEN
50/50
1.714
3151161SURRY 1
50/50
9.199
316044AC1-158 PL1
Solar/Wind Harmer
3.047
316450AC1-158 RIC
Solar/Wind Harmer
0.812
3147666LOUISA
Solar/Wind Harmer
0.63
315839AE2-212 C
Solar/Wind Harmer
0.002
315773AC2-141 GEN
Solar/Wind Harmer
8.863
965281AG1-393 GEN
Solar/Wind Harmer
2.583
970133AG2-095 GEN
Solar/Wind Harmer
2.314
315813AE1-149 C
Solar/Wind Harmer
12.857
970129AG2-093 GEN
Solar/Wind Harmer
14.547
944581AF1-123 GEN
Solar/Wind Harmer
54.129
944601AF1-125 GEN
Solar/Wind Harmer
53.295
315778AD1-151 GEN
Solar/Wind Harmer
19.229
3151101ELIZAR3
Adder
22.283
3144536CHRHLND
Solar/Wind Harmer
0.036
3144873MCLAUGH
Solar/Wind Harmer
0.006
970659AG2-427 GEN
Solar/Wind Harmer
2.537
961611AG1-000B GEN
Solar/Wind Harmer
6.393
3145336SMITFLD
Solar/Wind Harmer
0.096
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3151221GRAVEL6
Adder
17.41
3151171GRAVELC
Adder
3.35
970293AG2-193 GEN
Solar/Wind Harmer
2.553
3142946ENON
Solar/Wind Harmer
0.08
970661AG2-428 GEN
Solar/Wind Harmer
5.055
3142416OLDCHRC
Solar/Wind Harmer
2.311
3144216WINCHST
Adder
0.896
3146456SLIGO L269
Solar/Wind Harmer
0.237
971153AH1-033 GEN
Solar/Wind Harmer
2.744
3150921YORKTN3
Adder
5.966
316382AG1-145 C
Solar/Wind Harmer
0.002
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
3146516WINFALL
Solar/Wind Harmer
0.232
316473AC1-191 GEN
Solar/Wind Harmer
0.781
3146626S HERTFORD
Solar/Wind Harmer
0.231
3145273HOLLAND
Solar/Wind Harmer
0.173
316313AB2-026
Solar/Wind Harmer
0.144
316258AE1-075 C
Solar/Wind Harmer
0.172
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.453
3141843SHACKLE
Adder
1.161
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
3.026
316280AD1-041 GEN
Solar/Wind Harmer
0.005
3146376EDENTON
Solar/Wind Harmer
0.226
316156AD2-030 GEN
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
4.013
970917AG2-570 GEN
Solar/Wind Harmer
19.927
315614AA2-178 GEN
Solar/Wind Harmer
1.269
3150401LDYSMT4
Adder
29.389
3150371LDYSMT1
Adder
28.398
971157AH1-035 GEN
Solar/Wind Harmer
2.618
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
316365GEN2_N
Solar/Wind Harmer
0.488
315737AD1-076 GEN
Solar/Wind Harmer
2.798
962971AG1-146 GEN
Solar/Wind Harmer
3.462
3146206CASHIE
Solar/Wind Harmer
0.215
3145893MURPHYS
Solar/Wind Harmer
0.36
3145893MURPHYS
Solar/Wind Harmer
0.215
957521AF2-046 GEN
Solar/Wind Harmer
15.963
961681AG1-008 GEN
Solar/Wind Harmer
15.963
970009AG2-005 GEN
Solar/Wind Harmer
1.6
3146173TUNIS
Solar/Wind Harmer
0.213
3156021HOLLOMANSOL
Solar/Wind Harmer
0.965
316463AE2-346 GEN
Solar/Wind Harmer
0.182
316140AB2-099
Solar/Wind Harmer
0.076
962331AG1-082 GEN
Solar/Wind Harmer
2.263
316404AE1-155 C
Solar/Wind Harmer
0.047
3146263WOODLND
Solar/Wind Harmer
0.21
313506AB2-031 GEN
Solar/Wind Harmer
0.648
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3145963POPLR C
Solar/Wind Harmer
0.207
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.207
316478AD1-087 GEN
Solar/Wind Harmer
0.72
316486AD2-202 GEN
Solar/Wind Harmer
0.211
3147043LAWRENC
Solar/Wind Harmer
0.124
3145796HORNRTN
Solar/Wind Harmer
0.82
3145796HORNRTN
Solar/Wind Harmer
0.205
3150351NORNECKC2
Adder
2.075
316210AC1-098 GEN
Solar/Wind Harmer
1.857
3145933PARMELE
Solar/Wind Harmer
0.199
966801AG1-551 GEN
Solar/Wind Harmer
2.319
970909AG2-566 GEN
Solar/Wind Harmer
2.12
971781AH1-399 GEN
Solar/Wind Harmer
0.26
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
315724AD1-057 GEN
Solar/Wind Harmer
0.731
316327AA2-057 GEN
Solar/Wind Harmer
0.292
316131AB2-060 GEN
Solar/Wind Harmer
0.605
964241AG1-285 GEN
Solar/Wind Harmer
12.823
315785AD2-033 C
Solar/Wind Harmer
1.561
970257AG2-171 GEN
Solar/Wind Harmer
6.143
959311AF2-222 GEN
Solar/Wind Harmer
17.057
963181AG1-167 GEN
Solar/Wind Harmer
0.766
3144293JTRSVLE
Adder
0.609
3147133PAMPLIN
Solar/Wind Harmer
0.6
971193AH1-056 GEN
Solar/Wind Harmer
11.648
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.114
3146233WITAKRS
Solar/Wind Harmer
0.953
3146233WITAKRS
Solar/Wind Harmer
0.129
3146073TAR RVR
Solar/Wind Harmer
0.189
3146083TARBORO
Solar/Wind Harmer
0.189
3138543CONSLDL
Solar/Wind Harmer
0.125
3132273ORANGE
Solar/Wind Harmer
0.038
961601AG1-000A GEN
Solar/Wind Harmer
13.257
3145543BTLEBRO
Solar/Wind Harmer
0.186
3145543BTLEBRO
Solar/Wind Harmer
0.186
971623AH1-311 GEN
Solar/Wind Harmer
0.373
3141906WESTMOR
Solar/Wind Harmer
0.074
3146776BUCKING
Solar/Wind Harmer
0.066
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.481
970737AG2-469 GEN
Solar/Wind Harmer
7.427
316170AC1-121 GEN2
Solar/Wind Harmer
0.183
3151761LOISA E
Adder
22.218
972183AH1-676 GEN
Adder
173.787
970221AG2-151 GEN
Solar/Wind Harmer
8.67
971683AH1-343 GEN
Solar/Wind Harmer
5.958
316283AC2-100 C
Solar/Wind Harmer
0.309
972255AH1-712 GEN
Adder
76.037
3141316ARNOLDS
Adder
0.289
3141196NOKESVL
Solar/Wind Helper
1.164
316123AC1-075 GEN
Solar/Wind Harmer
0.194
970165AG2-112 GEN
Solar/Wind Harmer
1.153
970163AG2-111 GEN
Solar/Wind Harmer
1.1
3138266HYDRAULIC
Solar/Wind Harmer
0.006
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316411AF1-147_GEN1
Solar/Wind Helper
0.82
316415AF1-147_GEN2
Solar/Wind Helper
0.82
3138216PACIFIC
Solar/Wind Helper
0.04
971133AH1-012 GEN
50/50
5.665
944641AF1-129 GEN
50/50
122.768
3142366NRTHEST
50/50
0.838
970533AG2-339 GEN
50/50
21.472
970531AG2-338 GEN
50/50
8.589
3150781HOPHCF2
50/50
0.977
3150791HOPHCF3
50/50
0.977
3150761HOPPOLC
50/50
0.62
971213AH1-066 GEN
50/50
0.857
3150691DARBY 3
50/50
18.39
316447AC1-158 HLD
Solar/Wind Harmer
6.696
971223AH1-071 GEN
Solar/Wind Harmer
2.827
3143526WINTERP
Solar/Wind Harmer
1.34
316240AF1-291 C
Solar/Wind Harmer
0.002
3150701DARBY 4
Adder
17.29
3150681DARBY 2
Adder
17.27
3150671DARBY 1
Adder
17.25
3142296MT RD221
Adder
0.765
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.27
316036AC1-147 C
Solar/Wind Harmer
0.045
3150991CHESPKB
Adder
2.513
3150991CHESPKB
Adder
2.452
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.23
316185AD1-033 GEN
Solar/Wind Harmer
0.007
970657AG2-426 GEN
Solar/Wind Harmer
8.383
970657AG2-426 GEN
Solar/Wind Harmer
1.758
3142946ENON
Solar/Wind Harmer
0.024
3145506HICKORY
Solar/Wind Harmer
0.955
3145506HICKORY
Solar/Wind Harmer
0.573
3145506HICKORY
Solar/Wind Harmer
0.143
316339AD2-160 GEN
Solar/Wind Harmer
0.386
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.133
316075AC2-137 C
Solar/Wind Harmer
0.065
3137176SLIGO L2192
Solar/Wind Harmer
0.945
3146456SLIGO L269
Solar/Wind Harmer
4.201
3130086AYDLETT
Solar/Wind Harmer
0.948
972185AH1-677 GEN
Adder
13.205
3144356SAPONY
Solar/Wind Harmer
1.967
3146386ELIZ CT
Solar/Wind Harmer
0.235
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
972187AH1-678 GEN
Adder
6.623
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
966871AG1-558 GEN
Solar/Wind Harmer
0.267
3146626S HERTFORD
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
0.231
970933AG2-581 GEN
Solar/Wind Harmer
18.312
315742AE1-103 GEN
Solar/Wind Harmer
0.003
957411AF2-035 GEN
Solar/Wind Harmer
9.66
970317AG2-208 GEN
Solar/Wind Harmer
8.949
3146376EDENTON
Solar/Wind Harmer
1.006
3146376EDENTON
Solar/Wind Harmer
1.006
315673AE1-157 GEN
Solar/Wind Harmer
15.472
3150391LDYSMT3
Adder
29.334
972195AH1-682 GEN
Adder
3.855
316065AD1-022 GEN
Solar/Wind Harmer
9.955
3145893MURPHYS
Solar/Wind Harmer
1.439
3145893MURPHYS
Solar/Wind Harmer
0.387
970099AG2-077 GEN
Solar/Wind Harmer
22.861
3146173TUNIS
Solar/Wind Harmer
0.213
3146173TUNIS
Solar/Wind Harmer
0.213
958261AF2-120 GEN
Solar/Wind Harmer
6.972
316181AB2-040 GEN
Solar/Wind Harmer
0.304
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.125
316426AA2-053 GEN
Solar/Wind Harmer
0.701
3145593CAROLNA
Solar/Wind Harmer
0.207
3145593CAROLNA
Solar/Wind Harmer
0.207
966811AG1-552 GEN
Solar/Wind Harmer
2.242
3145593CAROLNA
Solar/Wind Harmer
0.257
3145783HORNRTN
Solar/Wind Harmer
3.653
3145783HORNRTN
Solar/Wind Harmer
2.922
3145783HORNRTN
Solar/Wind Harmer
0.913
3145783HORNRTN
Solar/Wind Harmer
0.365
3145796HORNRTN
Solar/Wind Harmer
0.615
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.144
3150341NORNECKC1
Adder
2.127
971741AH1-377 GEN
Solar/Wind Harmer
19.978
3145933PARMELE
Solar/Wind Harmer
0.398
3145933PARMELE
Solar/Wind Harmer
0.199
316274AC1-208 GEN
Solar/Wind Harmer
1.032
970301AG2-198 GEN
Solar/Wind Harmer
8.48
316468AD1-105 GEN
Solar/Wind Harmer
-0.064
939181AE1-148 GEN
Solar/Wind Harmer
9.287
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.19
971775AH1-396 GEN
Solar/Wind Harmer
0.307
958211AF2-115 GEN
Solar/Wind Harmer
2.298
963191AG1-168 GEN
Solar/Wind Harmer
0.766
3144293JTRSVLE
Adder
0.609
3144293JTRSVLE
Adder
0.513
3147133PAMPLIN
Solar/Wind Harmer
0.191
3147133PAMPLIN
Solar/Wind Harmer
0.153
3145493TOT1
Solar/Wind Harmer
0.439
3145453TOT5
Solar/Wind Harmer
0.264
3145603CNETO
Solar/Wind Harmer
0.176
961601AG1-000A GEN
Solar/Wind Harmer
3.314
316263AC1-034 GEN
Solar/Wind Harmer
7.082
962561AG1-105 GEN
Solar/Wind Harmer
8.835
3146776BUCKING
Solar/Wind Harmer
0.73
3146776BUCKING
Solar/Wind Harmer
0.059
964791AG1-342 GEN
Solar/Wind Harmer
3.505
3146843MT LREL
Solar/Wind Harmer
0.182
3146843MT LREL
Solar/Wind Harmer
0.182
966001AG1-469 GEN
Solar/Wind Harmer
0.098
3151731LOISA B
Adder
10.898
3151721LOISA A
Adder
10.842
971489AH1-241 GEN
Solar/Wind Harmer
8.67
316222AC1-221 GEN
Solar/Wind Harmer
0.658
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
7.283
315651AD1-115 GEN
Solar/Wind Harmer
0.004
LAGNLTFEXP_LAGN->PJM
CLTF
8.202
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.311
TVALTFEXP_TVA->PJM
CLTF
4.157
NYPJM->LTFIMP_NY
CLTF
3.433
LGEELTFEXP_LGEE->PJM
CLTF
1.291
WECLTFEXP_WEC->PJM
CLTF
0.616
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.192
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.068
MECLTFEXP_MEC->PJM
CLTF
3.555
SIGELTFEXP_SIGE->PJM
CLTF
0.108
CPLELTFEXP_CPLE->PJM
CLTF
12.074
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.739

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:175.06 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5637.7
MW Contribution:6.92
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
19.719
970119AG2-088 GEN
50/50
34.806
3150851SPRUNCC
50/50
1.197
3143096IRON208
50/50
1.062
3152331SURRY 2
50/50
9.829
3150771HOPHCF1
50/50
0.962
316045AC1-158 PL2
Solar/Wind Harmer
9.665
971133AH1-012 GEN
50/50
5.548
944641AF1-129 GEN
50/50
120.841
970533AG2-339 GEN
50/50
21.15
970531AG2-338 GEN
50/50
8.46
3142366NRTHEST
50/50
0.824
3150781HOPHCF2
50/50
0.962
3150791HOPHCF3
50/50
0.962
3150761HOPPOLC
50/50
0.61
971213AH1-066 GEN
50/50
0.844
3150691DARBY 3
50/50
18.094
3150701DARBY 4
50/50
18.052
316447AC1-158 HLD
Solar/Wind Harmer
6.644
971223AH1-071 GEN
Solar/Wind Harmer
2.784
3143526WINTERP
Solar/Wind Harmer
1.319
316240AF1-291 C
Solar/Wind Harmer
0.002
3150681DARBY 2
Adder
16.992
3150671DARBY 1
Adder
16.973
3142296MT RD221
Adder
0.753
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.266
316036AC1-147 C
Solar/Wind Harmer
0.044
3150991CHESPKB
Adder
2.474
3150991CHESPKB
Adder
2.414
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.226
3152261N ANNA2
50/50
19.717
3150861SPRUNCD
50/50
1.197
3143096IRON208
50/50
1.062
3143096IRON208
50/50
1.041
3150801HOPHCF4
50/50
1.399
971211AH1-065 GEN
50/50
1.687
3151161SURRY 1
50/50
9.055
316044AC1-158 PL1
Solar/Wind Harmer
3.023
316450AC1-158 RIC
Solar/Wind Harmer
0.806
3147666LOUISA
Solar/Wind Harmer
0.614
315839AE2-212 C
Solar/Wind Harmer
0.002
315773AC2-141 GEN
Solar/Wind Harmer
8.726
965281AG1-393 GEN
Solar/Wind Harmer
2.543
315813AE1-149 C
Solar/Wind Harmer
12.658
970133AG2-095 GEN
Solar/Wind Harmer
2.278
970129AG2-093 GEN
Solar/Wind Harmer
14.319
944581AF1-123 GEN
Solar/Wind Harmer
53.293
944601AF1-125 GEN
Solar/Wind Harmer
52.472
315778AD1-151 GEN
Solar/Wind Harmer
18.928
3151101ELIZAR3
Adder
21.938
3144536CHRHLND
Solar/Wind Harmer
0.035
3144873MCLAUGH
Solar/Wind Harmer
0.006
970659AG2-427 GEN
Solar/Wind Harmer
2.498
3145336SMITFLD
Solar/Wind Harmer
0.094
961611AG1-000B GEN
Solar/Wind Harmer
6.293
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3151221GRAVEL6
Adder
17.139
3151171GRAVELC
Adder
3.297
970293AG2-193 GEN
Solar/Wind Harmer
2.512
970661AG2-428 GEN
Solar/Wind Harmer
4.977
3142946ENON
Solar/Wind Harmer
0.079
3142416OLDCHRC
Solar/Wind Harmer
2.274
3144216WINCHST
Adder
0.882
3146456SLIGO L269
Solar/Wind Harmer
0.234
971153AH1-033 GEN
Solar/Wind Harmer
2.702
3150921YORKTN3
Adder
5.872
316382AG1-145 C
Solar/Wind Harmer
0.002
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.445
3142433PROV 92
Adder
0.445
3146516WINFALL
Solar/Wind Harmer
0.229
316473AC1-191 GEN
Solar/Wind Harmer
0.768
3146626S HERTFORD
Solar/Wind Harmer
0.227
3145273HOLLAND
Solar/Wind Harmer
0.17
316313AB2-026
Solar/Wind Harmer
0.142
316258AE1-075 C
Solar/Wind Harmer
0.17
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.394
3141843SHACKLE
Adder
1.143
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
2.978
316280AD1-041 GEN
Solar/Wind Harmer
0.005
3146376EDENTON
Solar/Wind Harmer
0.223
316156AD2-030 GEN
Solar/Wind Harmer
0.165
3141873WAN 176
Solar/Wind Harmer
3.95
970917AG2-570 GEN
Solar/Wind Harmer
19.626
315614AA2-178 GEN
Solar/Wind Harmer
1.249
3150401LDYSMT4
Adder
28.893
3150371LDYSMT1
Adder
27.918
971157AH1-035 GEN
Solar/Wind Harmer
2.577
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
316365GEN2_N
Solar/Wind Harmer
0.481
315737AD1-076 GEN
Solar/Wind Harmer
2.755
962971AG1-146 GEN
Solar/Wind Harmer
3.408
3146206CASHIE
Solar/Wind Harmer
0.212
3145893MURPHYS
Solar/Wind Harmer
0.354
3145893MURPHYS
Solar/Wind Harmer
0.212
957521AF2-046 GEN
Solar/Wind Harmer
15.715
961681AG1-008 GEN
Solar/Wind Harmer
15.715
970009AG2-005 GEN
Solar/Wind Harmer
1.575
3146173TUNIS
Solar/Wind Harmer
0.21
3156021HOLLOMANSOL
Solar/Wind Harmer
0.95
316463AE2-346 GEN
Solar/Wind Harmer
0.179
316140AB2-099
Solar/Wind Harmer
0.075
962331AG1-082 GEN
Solar/Wind Harmer
2.227
316404AE1-155 C
Solar/Wind Harmer
0.047
3146263WOODLND
Solar/Wind Harmer
0.207
313506AB2-031 GEN
Solar/Wind Harmer
0.638
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3145963POPLR C
Solar/Wind Harmer
0.204
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.204
316478AD1-087 GEN
Solar/Wind Harmer
0.708
316486AD2-202 GEN
Solar/Wind Harmer
0.208
3147043LAWRENC
Solar/Wind Harmer
0.122
3145796HORNRTN
Solar/Wind Harmer
0.807
3145796HORNRTN
Solar/Wind Harmer
0.202
3150351NORNECKC2
Adder
2.043
316210AC1-098 GEN
Solar/Wind Harmer
1.828
3145933PARMELE
Solar/Wind Harmer
0.196
966801AG1-551 GEN
Solar/Wind Harmer
2.283
970909AG2-566 GEN
Solar/Wind Harmer
2.083
971781AH1-399 GEN
Solar/Wind Harmer
0.256
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
315724AD1-057 GEN
Solar/Wind Harmer
0.72
316327AA2-057 GEN
Solar/Wind Harmer
0.287
316131AB2-060 GEN
Solar/Wind Harmer
0.595
964241AG1-285 GEN
Solar/Wind Harmer
12.61
315785AD2-033 C
Solar/Wind Harmer
1.535
970257AG2-171 GEN
Solar/Wind Harmer
6.039
959311AF2-222 GEN
Solar/Wind Harmer
16.767
963181AG1-167 GEN
Solar/Wind Harmer
0.752
3144293JTRSVLE
Adder
0.599
3147133PAMPLIN
Solar/Wind Harmer
0.59
971193AH1-056 GEN
Solar/Wind Harmer
11.443
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146233WITAKRS
Solar/Wind Harmer
0.938
3146233WITAKRS
Solar/Wind Harmer
0.127
3146926FARMVIL
Solar/Wind Harmer
0.112
3146073TAR RVR
Solar/Wind Harmer
0.186
3146083TARBORO
Solar/Wind Harmer
0.186
3138543CONSLDL
Solar/Wind Harmer
0.123
961601AG1-000A GEN
Solar/Wind Harmer
13.049
3145543BTLEBRO
Solar/Wind Harmer
0.183
3145543BTLEBRO
Solar/Wind Harmer
0.183
971623AH1-311 GEN
Solar/Wind Harmer
0.367
3141906WESTMOR
Solar/Wind Harmer
0.072
3146776BUCKING
Solar/Wind Harmer
0.064
316248AF1-058 C
Solar/Wind Harmer
0.001
3147666LOUISA
Solar/Wind Harmer
1.067
3143226MDLTHAN
Solar/Wind Harmer
0.261
316192AB2-158 GEN
Solar/Wind Harmer
1.475
3143526WINTERP
Solar/Wind Harmer
1.319
940641AE2-051 GEN
Solar/Wind Harmer
19.587
939411AE1-173 GEN
Solar/Wind Harmer
103.486
3142543TWELFTH
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
4.14
315671AE2-027_GEN
Solar/Wind Harmer
15.248
970129AG2-093 GEN
Solar/Wind Harmer
6.738
316458AB2-190 GEN2
Solar/Wind Harmer
1.271
944591AF1-124 GEN
Solar/Wind Harmer
53.482
971069AG2-661 GEN
Solar/Wind Harmer
4.206
944631AF1-128 GEN
Adder
112.66
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.949
971647AH1-324 GEN
Solar/Wind Harmer
10.078
970659AG2-427 GEN
Solar/Wind Harmer
11.419
3145336SMITFLD
Solar/Wind Harmer
0.943
961611AG1-000B GEN
Solar/Wind Harmer
12.376
316381AD1-082 GEN
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
2.508
970661AG2-428 GEN
Solar/Wind Harmer
23.401
3142416OLDCHRC
Solar/Wind Harmer
0.61
3142416OLDCHRC
Solar/Wind Harmer
0.234
316388AE2-253 GEN
Solar/Wind Harmer
0.734
3138126ROCKLANDING
Solar/Wind Harmer
0.107
3146456SLIGO L269
Solar/Wind Harmer
0.234
316072AD1-144
Solar/Wind Harmer
0.085
316159AE1-175 C
Solar/Wind Harmer
0.201
316246AF1-032 C
Solar/Wind Harmer
0.105
971317AH1-138 GEN
Solar/Wind Harmer
1.735
316093AE2-104_GEN
Solar/Wind Harmer
3.906
3142433PROV 92
Solar/Wind Harmer
0.914
3142433PROV 92
Adder
0.445
3142433PROV 92
Adder
0.445
3146516WINFALL
Solar/Wind Harmer
0.741
3146516WINFALL
Solar/Wind Harmer
0.229
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.993
971777AH1-397 GEN
Solar/Wind Harmer
0.591
3141843SHACKLE
Adder
1.143
3141766HARMONY
Solar/Wind Harmer
0.045
3130156CHOWAN
Solar/Wind Harmer
0.223
966881AG1-559 GEN
Solar/Wind Harmer
0.257
970919AG2-571 GEN
Solar/Wind Harmer
7.85
970087AG2-069 GEN
Solar/Wind Harmer
17.59
3138133OCRAN
Solar/Wind Harmer
0.131
3145663CRESWEL
Solar/Wind Harmer
0.611
971163AH1-040 GEN
Solar/Wind Harmer
17.461
972197AH1-683 GEN
Adder
4.512
972219AH1-694 GEN
Adder
3.248
316336AC2-165 C
Solar/Wind Harmer
0.008
316023GEN1_S
Solar/Wind Harmer
0.481
3146206CASHIE
Solar/Wind Harmer
0.212
971547AH1-271 GEN
Solar/Wind Harmer
4.525
3145893MURPHYS
Solar/Wind Harmer
0.847
3145893MURPHYS
Solar/Wind Harmer
0.941
957481AF2-042 GEN
Solar/Wind Harmer
56.258
3146173TUNIS
Solar/Wind Harmer
0.21
960081AF2-299 GEN
Solar/Wind Harmer
2.005
962861AG1-135 GEN
Solar/Wind Harmer
6.67
3145683EARLEYS
Solar/Wind Harmer
0.208
315693AD1-088 GEN
Solar/Wind Harmer
9.93
3146263WOODLND
Solar/Wind Harmer
0.207
962491AG1-098 GEN
Solar/Wind Harmer
11.772
316011AB1-132 GEN
Solar/Wind Harmer
3.728
962571AG1-106 GEN
Solar/Wind Harmer
2.917
971795AH1-408 GEN
Solar/Wind Harmer
13.656
3145963POPLR C
Solar/Wind Harmer
0.204
3141726DUNNSVL
Solar/Wind Harmer
0.817
316190AA2-174 GEN
Solar/Wind Harmer
0
3145823KELFORD
Solar/Wind Harmer
0.204
3147043LAWRENC
Adder
1.836
316174AB2-169 GEN
Solar/Wind Harmer
0.005
3145783HORNRTN
Solar/Wind Harmer
0.202
3145796HORNRTN
Solar/Wind Harmer
0.666
3145796HORNRTN
Solar/Wind Harmer
0.202
3150351NORNECKC2
Adder
2.009
316212AC1-099_GEN
Solar/Wind Harmer
1.019
3146293MARTNCO
Solar/Wind Harmer
0.182
316129AC1-054 GEN
Solar/Wind Harmer
0.734
971065AG2-659 GEN
Solar/Wind Harmer
8.291
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
315722AD1-056 GEN
Solar/Wind Harmer
1.214
316337AD2-073 GEN
Solar/Wind Harmer
0.167
315687AD1-152 GEN
Solar/Wind Harmer
0.006
970937AG2-583 GEN
Solar/Wind Harmer
11.689
316494AC1-189 GEN
Solar/Wind Harmer
0.639
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
14.068
963171AG1-166 GEN
Solar/Wind Harmer
1.003
971563AH1-280 GEN
Solar/Wind Harmer
2.007
3144293JTRSVLE
Adder
0.599
3146233WITAKRS
Solar/Wind Harmer
0.743
3146926FARMVIL
Solar/Wind Harmer
0.112
961671AG1-007 GEN
Solar/Wind Harmer
0.029
3146083TARBORO
Solar/Wind Harmer
0.186
3145493TOT1
Solar/Wind Harmer
0.829
3145543BTLEBRO
Solar/Wind Harmer
0.183
3145543BTLEBRO
Solar/Wind Harmer
0.147
316359AB2-059 GEN
Solar/Wind Harmer
0.659
316049AB1-081 GEN
Solar/Wind Harmer
1.05
3142053HEARTS
Solar/Wind Harmer
0.323
970401AG2-262 GEN
Solar/Wind Harmer
1.053
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.072
972003AH1-546 GEN
Solar/Wind Harmer
7.289
316003AC1-222 GEN
Solar/Wind Harmer
0.004
960061AF2-297 GEN
Solar/Wind Harmer
7.36
970737AG2-469 GEN
Solar/Wind Harmer
7.314
971683AH1-343 GEN
Solar/Wind Harmer
5.86
3151761LOISA E
Adder
21.054
970221AG2-151 GEN
Solar/Wind Harmer
8.48
3132273ORANGE
Solar/Wind Harmer
0.031
316283AC2-100 C
Solar/Wind Harmer
0.304
972183AH1-676 GEN
Adder
164.313
972255AH1-712 GEN
Adder
74.545
316170AC1-121 GEN2
Solar/Wind Harmer
0.13
3141316ARNOLDS
Adder
0.285
3141196NOKESVL
Solar/Wind Helper
1.139
972135AH1-637 GEN
Solar/Wind Harmer
1.408
3151751LOISA D
Adder
10.327
971377AH1-170 GEN
Solar/Wind Harmer
1.696
3147623JAMES R
Solar/Wind Harmer
0.368
972277AH1-723 GEN
Adder
86.868
316254AC1-120 GEN1
Solar/Wind Harmer
0.26
316303AF2-085
50/50
4.641
971285AH1-108 GEN
50/50
1.959
970603AG2-384 GEN
50/50
5.097
316233AE1-074 FULL
Solar/Wind Harmer
0.203
971281AH1-106 GEN
Solar/Wind Harmer
3.521
971283AH1-107 GEN
Solar/Wind Harmer
3.521
3143316POE
Solar/Wind Harmer
0.947
941031AE2-094 GEN
Solar/Wind Harmer
43.824
944011AF1-069 GEN
Solar/Wind Harmer
14.319
316132AB2-190 GEN1
Solar/Wind Harmer
1.271
316369SG1_INVT
Solar/Wind Harmer
0.009
3151081ELIZAR1
Adder
21.661
3151091ELIZAR2
Adder
21.285
3152611GOSPORTB
Adder
3.008
3152621GOSPORTC
Adder
2.552
3152601GOSPORTA
Adder
2.355
971445AH1-216 GEN
Solar/Wind Harmer
16.611
972265AH1-717 GEN
Adder
18.304
3151201GRAVEL4
Adder
17.158
3151191GRAVEL3
Adder
16.941
3151211GRAVEL5
Adder
16.941
316312AB1-027
Solar/Wind Harmer
0.42
957871AF2-081 GEN
Solar/Wind Harmer
11.66
316164AC1-076 GEN
Solar/Wind Harmer
0.329
970673AG2-436 GEN
Solar/Wind Harmer
49.886
970673AG2-436 GEN
Solar/Wind Harmer
33.257
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.16
319010AE1-072 C
Solar/Wind Harmer
1.177
316311AC2-079 GEN
Solar/Wind Harmer
6.708
3146406KITTY HAWK
Solar/Wind Harmer
0.029
316305AF2-043 C
Solar/Wind Harmer
0.002
315976AC1-164 GENA
Solar/Wind Harmer
24.098
316169AC1-164_GENC
Solar/Wind Harmer
20.818
315975AC1-164 GENB
Solar/Wind Harmer
0.713
315835AF2-110_GEN
Solar/Wind Harmer
1.594
316315AB2-025 C
Solar/Wind Harmer
0.187
313526AB2-022
Solar/Wind Harmer
0.125
971967AH1-528 GEN
Solar/Wind Harmer
36.95
3146486SUNBURY
Solar/Wind Harmer
0.231
3146486SUNBURY
Solar/Wind Harmer
0.231
972189AH1-679 GEN
Adder
3.867
315814AE2-033 C
Solar/Wind Harmer
18.254
316321Z2-027
Solar/Wind Harmer
0.043
3146396TANGLEW
Solar/Wind Harmer
0.635
3145176PASQUOTANK
Solar/Wind Harmer
0.143
971167AH1-042 GEN
Solar/Wind Harmer
20.377
3142433PROV 92
Adder
0.445
3142433PROV 92
Adder
0.445
3138283WHITEMARSH
Solar/Wind Harmer
0.053
3143873LANEXA
Solar/Wind Harmer
0.135
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
316314AB2-024 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
6.628
316059AD1-063 C
Solar/Wind Harmer
0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.223
3130156CHOWAN
Solar/Wind Harmer
0.223
3141873WAN 176
Solar/Wind Harmer
0.044
970085AG2-068 GEN
Solar/Wind Harmer
11.727
970581AG2-369 GEN
Solar/Wind Harmer
10.085
3141913WHIT STONE
Solar/Wind Harmer
0.219
3138133OCRAN
Solar/Wind Harmer
0.065
315816AE2-034 GEN
Solar/Wind Harmer
0.937
3141783LANCAST
Solar/Wind Harmer
0.13
3141783LANCAST
Solar/Wind Harmer
0.087
3150411LDYSMT5
Adder
28.983
3150381LDYSMT2
Adder
27.738
972213AH1-691 GEN
Adder
4.692
972215AH1-692 GEN
Adder
4.692
3130546PLYMOUTH
Solar/Wind Harmer
0.215
315732AD1-074 GEN1
Solar/Wind Harmer
1.23
315733AD1-074 GEN2
Solar/Wind Harmer
1.23
315735AD1-075 GEN1
Solar/Wind Harmer
0.616
965291AG1-394 GEN
Solar/Wind Harmer
0.949
962981AG1-147 GEN
Solar/Wind Harmer
7.952
3146206CASHIE
Solar/Wind Harmer
0.212
970601AG2-382 GEN
Solar/Wind Harmer
7.919
3145893MURPHYS
Solar/Wind Harmer
0.572
3145893MURPHYS
Solar/Wind Harmer
0.212
970327AG2-215 GEN
Solar/Wind Harmer
6.922
3145513AHOSKIE
Solar/Wind Harmer
0.437
3145513AHOSKIE
Solar/Wind Harmer
0.209
3146043SEABORD
Solar/Wind Harmer
0.208
3145683EARLEYS
Solar/Wind Harmer
0.416
3145683EARLEYS
Solar/Wind Harmer
0.208
3145683EARLEYS
Solar/Wind Harmer
0.208
315607AA1-063A GEN
Solar/Wind Harmer
0.424
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315652AC1-086 GEN
Solar/Wind Harmer
22.553
3137643SOCKMAN
Solar/Wind Harmer
0.818
3145796HORNRTN
Solar/Wind Harmer
0.646
3145796HORNRTN
Solar/Wind Harmer
0.081
3141813NORNECK
Solar/Wind Harmer
0.201
3146033SCOT NK
Solar/Wind Harmer
0.8
970831AG2-522 GEN
Solar/Wind Harmer
8.358
316005AA1-067
Solar/Wind Harmer
0.206
3145746EVERETS
Solar/Wind Harmer
0.764
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
970181AG2-120 GEN
Solar/Wind Harmer
2.391
957861AF2-080 GEN
Solar/Wind Harmer
8.156
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
3.171
3144303KENBRDG
Solar/Wind Harmer
0.151
970683AG2-441 GEN
Solar/Wind Harmer
12.561
970681AG2-440 GEN
Solar/Wind Harmer
10.049
946301AF1-294 GEN
Solar/Wind Harmer
3.712
961791AG1-021 GEN
Solar/Wind Harmer
1.806
315657AE1-056 GEN
Solar/Wind Harmer
6.482
316420AA1-050 GEN
Solar/Wind Harmer
0.006
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.186
3145573BETHELC
Solar/Wind Harmer
0.186
970285AG2-188 GEN
Solar/Wind Harmer
14.319
316223AC1-118
Solar/Wind Harmer
0.13
971845AH1-439 GEN
Solar/Wind Harmer
8.149
316118AC1-105 GEN
Solar/Wind Harmer
0.454
3147173SINAI
Solar/Wind Harmer
0.172
3147243WELCO
Solar/Wind Harmer
0.108
972205AH1-687 GEN
Adder
7.256
944491AF1-114 GEN
Solar/Wind Harmer
0.001
971447AH1-217 GEN
Solar/Wind Harmer
4.692
970865AG2-541 GEN
Solar/Wind Harmer
5.299
3147346CASHSCORNER
Solar/Wind Harmer
0.35
972193AH1-681 GEN
Adder
3.331
316123AC1-075 GEN
Solar/Wind Harmer
0.191
970165AG2-112 GEN
Solar/Wind Harmer
1.134
970163AG2-111 GEN
Solar/Wind Harmer
1.081
270494AE1-108_GEN
Solar/Wind Harmer
1.679
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316411AF1-147_GEN1
Solar/Wind Helper
0.804
316415AF1-147_GEN2
Solar/Wind Helper
0.804
3138216PACIFIC
Solar/Wind Helper
0.039
316185AD1-033 GEN
Solar/Wind Harmer
0.007
970657AG2-426 GEN
Solar/Wind Harmer
8.254
970657AG2-426 GEN
Solar/Wind Harmer
1.73
3145506HICKORY
Solar/Wind Harmer
0.94
3145506HICKORY
Solar/Wind Harmer
0.564
3145506HICKORY
Solar/Wind Harmer
0.141
3142946ENON
Solar/Wind Harmer
0.023
316339AD2-160 GEN
Solar/Wind Harmer
0.38
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.131
3137176SLIGO L2192
Solar/Wind Harmer
0.93
316075AC2-137 C
Solar/Wind Harmer
0.064
3146456SLIGO L269
Solar/Wind Harmer
4.136
3130086AYDLETT
Solar/Wind Harmer
0.933
972185AH1-677 GEN
Adder
13.007
3144356SAPONY
Solar/Wind Harmer
1.937
3146386ELIZ CT
Solar/Wind Harmer
0.231
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
972187AH1-678 GEN
Adder
6.523
3146516WINFALL
Solar/Wind Harmer
0.229
3146516WINFALL
Solar/Wind Harmer
0.229
3146516WINFALL
Solar/Wind Harmer
0.229
966871AG1-558 GEN
Solar/Wind Harmer
0.263
3146626S HERTFORD
Solar/Wind Harmer
0.227
3146626S HERTFORD
Solar/Wind Harmer
0.227
970933AG2-581 GEN
Solar/Wind Harmer
18.033
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
0.99
3146376EDENTON
Solar/Wind Harmer
0.99
957411AF2-035 GEN
Solar/Wind Harmer
9.498
970317AG2-208 GEN
Solar/Wind Harmer
8.8
315673AE1-157 GEN
Solar/Wind Harmer
15.213
3150391LDYSMT3
Adder
28.839
972195AH1-682 GEN
Adder
3.79
316065AD1-022 GEN
Solar/Wind Harmer
9.8
3145893MURPHYS
Solar/Wind Harmer
1.417
3145893MURPHYS
Solar/Wind Harmer
0.381
970099AG2-077 GEN
Solar/Wind Harmer
22.503
3146173TUNIS
Solar/Wind Harmer
0.21
3146173TUNIS
Solar/Wind Harmer
0.21
958261AF2-120 GEN
Solar/Wind Harmer
6.863
316181AB2-040 GEN
Solar/Wind Harmer
0.299
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3142666NORTHAMPTON
Solar/Wind Harmer
0.123
316426AA2-053 GEN
Solar/Wind Harmer
0.69
3145593CAROLNA
Solar/Wind Harmer
0.203
3145593CAROLNA
Solar/Wind Harmer
0.203
966811AG1-552 GEN
Solar/Wind Harmer
2.207
3145593CAROLNA
Solar/Wind Harmer
0.253
3145783HORNRTN
Solar/Wind Harmer
3.596
3145783HORNRTN
Solar/Wind Harmer
2.876
3145783HORNRTN
Solar/Wind Harmer
0.899
3145783HORNRTN
Solar/Wind Harmer
0.36
3145796HORNRTN
Solar/Wind Harmer
0.606
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.11
3150341NORNECKC1
Adder
2.093
971741AH1-377 GEN
Solar/Wind Harmer
19.637
3145933PARMELE
Solar/Wind Harmer
0.392
3145933PARMELE
Solar/Wind Harmer
0.196
316274AC1-208 GEN
Solar/Wind Harmer
1.016
970301AG2-198 GEN
Solar/Wind Harmer
8.333
316468AD1-105 GEN
Solar/Wind Harmer
-0.063
939181AE1-148 GEN
Solar/Wind Harmer
9.137
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.051
971775AH1-396 GEN
Solar/Wind Harmer
0.302
958211AF2-115 GEN
Solar/Wind Harmer
2.257
963191AG1-168 GEN
Solar/Wind Harmer
0.752
3144293JTRSVLE
Adder
0.599
3144293JTRSVLE
Adder
0.504
3147133PAMPLIN
Solar/Wind Harmer
0.188
3147133PAMPLIN
Solar/Wind Harmer
0.15
3145493TOT1
Solar/Wind Harmer
0.432
3145453TOT5
Solar/Wind Harmer
0.259
3145603CNETO
Solar/Wind Harmer
0.173
961601AG1-000A GEN
Solar/Wind Harmer
3.262
316263AC1-034 GEN
Solar/Wind Harmer
6.97
962561AG1-105 GEN
Solar/Wind Harmer
8.691
964791AG1-342 GEN
Solar/Wind Harmer
3.448
3146843MT LREL
Solar/Wind Harmer
0.179
3146843MT LREL
Solar/Wind Harmer
0.179
3146776BUCKING
Solar/Wind Harmer
0.716
3146776BUCKING
Solar/Wind Harmer
0.058
3151731LOISA B
Adder
10.327
3151721LOISA A
Adder
10.274
971489AH1-241 GEN
Solar/Wind Harmer
8.48
316222AC1-221 GEN
Solar/Wind Harmer
0.648
966001AG1-469 GEN
Solar/Wind Harmer
0.09
315821AE2-092 GEN
Solar/Wind Harmer
0.008
942751AE2-291 GEN
Solar/Wind Harmer
7.158
LAGNLTFEXP_LAGN->PJM
CLTF
8.056
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.878
TVALTFEXP_TVA->PJM
CLTF
4.082
NYPJM->LTFIMP_NY
CLTF
3.369
LGEELTFEXP_LGEE->PJM
CLTF
1.264
WECLTFEXP_WEC->PJM
CLTF
0.603
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.76
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.813
MECLTFEXP_MEC->PJM
CLTF
3.485
SIGELTFEXP_SIGE->PJM
CLTF
0.106
CPLELTFEXP_CPLE->PJM
CLTF
11.88
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.966

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:129.41 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:4167.61
MW Contribution:4.94
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
17.068
3150861SPRUNCD
50/50
0.882
3151031BRUNSWICKG2
50/50
2.318
3151101ELIZAR3
50/50
17.311
316044AC1-158 PL1
Solar/Wind Harmer
2.971
316450AC1-158 RIC
Solar/Wind Harmer
0.792
3147666LOUISA
Solar/Wind Harmer
0.538
315773AC2-141 GEN
Solar/Wind Harmer
6.485
315839AE2-212 C
Solar/Wind Harmer
0.001
944581AF1-123 GEN
Solar/Wind Harmer
39.675
944601AF1-125 GEN
Solar/Wind Harmer
39.064
315813AE1-149 C
Solar/Wind Harmer
9.394
965281AG1-393 GEN
Solar/Wind Harmer
1.874
3144873MCLAUGH
Solar/Wind Harmer
0.004
970659AG2-427 GEN
Solar/Wind Harmer
1.855
3144536CHRHLND
Solar/Wind Harmer
0.026
316083AB2-161 GEN
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
3.699
3145336SMITFLD
Solar/Wind Harmer
0.07
3146456SLIGO L269
Solar/Wind Harmer
0.174
971153AH1-033 GEN
Solar/Wind Harmer
2.012
3151221GRAVEL6
Adder
12.623
3151171GRAVELC
Adder
2.429
961611AG1-000B GEN
Solar/Wind Harmer
4.628
315778AD1-151 GEN
Solar/Wind Harmer
13.874
970129AG2-093 GEN
Solar/Wind Harmer
10.479
970133AG2-095 GEN
Solar/Wind Harmer
1.663
3143096IRON208
Adder
0.724
3143096IRON208
Adder
0.71
316313AB2-026
Solar/Wind Harmer
0.109
316258AE1-075 C
Solar/Wind Harmer
0.13
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.611
316320Y1-086
Solar/Wind Harmer
0.001
3144216WINCHST
Adder
0.645
316435W1029_GEN3
Solar/Wind Harmer
0.001
3150921YORKTN3
Adder
4.287
3146516WINFALL
Solar/Wind Harmer
0.17
970917AG2-570 GEN
Solar/Wind Harmer
15.071
3146626S HERTFORD
Solar/Wind Harmer
0.169
3142946ENON
Solar/Wind Harmer
0.057
971133AH1-012 GEN
50/50
4.837
970533AG2-339 GEN
50/50
16.271
970531AG2-338 GEN
50/50
6.508
315242AE2-183_GT2
50/50
2.943
315241AE2-183_GT1
50/50
2.925
972185AH1-677 GEN
50/50
10.611
3151041BRUNSWICKG3
50/50
2.318
972187AH1-678 GEN
50/50
5.32
316447AC1-158 HLD
Solar/Wind Harmer
6.529
971223AH1-071 GEN
Solar/Wind Harmer
2.14
3143526WINTERP
Solar/Wind Harmer
0.994
316036AC1-147 C
Solar/Wind Harmer
0.033
3150991CHESPKB
Adder
1.839
3150991CHESPKB
Adder
1.795
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.168
316185AD1-033 GEN
Solar/Wind Harmer
0.005
316240AF1-291 C
Solar/Wind Harmer
0.001
3145506HICKORY
Solar/Wind Harmer
0.7
3145506HICKORY
Solar/Wind Harmer
0.42
3145506HICKORY
Solar/Wind Harmer
0.105
970657AG2-426 GEN
Solar/Wind Harmer
6.132
970657AG2-426 GEN
Solar/Wind Harmer
1.286
3144356SAPONY
Solar/Wind Harmer
1.464
944641AF1-129 GEN
Adder
83.418
316339AD2-160 GEN
Solar/Wind Harmer
0.283
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316018AA1-139 ULT2
Solar/Wind Harmer
0.004
316017AA1-139 ULT1
Solar/Wind Harmer
0.097
3137176SLIGO L2192
Solar/Wind Harmer
0.693
3146456SLIGO L269
Solar/Wind Harmer
3.08
3130086AYDLETT
Solar/Wind Harmer
0.695
316033AB2-134 GEN
Solar/Wind Harmer
0.01
315697AD1-025 GEN
Solar/Wind Harmer
0.195
970933AG2-581 GEN
Solar/Wind Harmer
13.857
3146386ELIZ CT
Solar/Wind Harmer
0.172
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.17
3146516WINFALL
Solar/Wind Harmer
0.17
3146516WINFALL
Solar/Wind Harmer
0.17
3142366NRTHEST
Adder
0.556
3146626S HERTFORD
Solar/Wind Harmer
0.169
3146626S HERTFORD
Solar/Wind Harmer
0.169
3150691DARBY 3
Adder
12.185
3150701DARBY 4
Adder
12.157
3150681DARBY 2
Adder
12.142
3150671DARBY 1
Adder
12.128
3142946ENON
Solar/Wind Harmer
0.017
315742AE1-103 GEN
Solar/Wind Harmer
0.002
316075AC2-137 C
Solar/Wind Harmer
0.046
3146376EDENTON
Solar/Wind Harmer
0.74
3146376EDENTON
Solar/Wind Harmer
0.74
3142296MT RD221
Adder
0.528
970099AG2-077 GEN
Solar/Wind Harmer
17.266
316065AD1-022 GEN
Solar/Wind Harmer
7.34
966871AG1-558 GEN
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
1.063
3145893MURPHYS
Solar/Wind Harmer
0.286
3146173TUNIS
Solar/Wind Harmer
0.157
3146173TUNIS
Solar/Wind Harmer
0.157
316181AB2-040 GEN
Solar/Wind Harmer
0.226
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
3142666NORTHAMPTON
Solar/Wind Harmer
0.093
316426AA2-053 GEN
Solar/Wind Harmer
0.52
3145593CAROLNA
Solar/Wind Harmer
0.153
3145593CAROLNA
Solar/Wind Harmer
0.153
966811AG1-552 GEN
Solar/Wind Harmer
1.665
3145593CAROLNA
Solar/Wind Harmer
0.191
3145783HORNRTN
Solar/Wind Harmer
2.713
3145783HORNRTN
Solar/Wind Harmer
2.17
3145783HORNRTN
Solar/Wind Harmer
0.678
3145783HORNRTN
Solar/Wind Harmer
0.271
3145796HORNRTN
Solar/Wind Harmer
0.457
971741AH1-377 GEN
Solar/Wind Harmer
15.076
970301AG2-198 GEN
Solar/Wind Harmer
6.399
958261AF2-120 GEN
Solar/Wind Harmer
4.886
316274AC1-208 GEN
Solar/Wind Harmer
0.766
3145933PARMELE
Solar/Wind Harmer
0.295
3145933PARMELE
Solar/Wind Harmer
0.147
957411AF2-035 GEN
Solar/Wind Harmer
6.2
970317AG2-208 GEN
Solar/Wind Harmer
5.744
939181AE1-148 GEN
Solar/Wind Harmer
6.96
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.011
970323AG2-213 GEN
Solar/Wind Harmer
6.152
971775AH1-396 GEN
Solar/Wind Harmer
0.231
958211AF2-115 GEN
Solar/Wind Harmer
1.728
963191AG1-168 GEN
Solar/Wind Harmer
0.576
3144293JTRSVLE
Adder
0.458
3144293JTRSVLE
Adder
0.386
3147133PAMPLIN
Solar/Wind Harmer
0.144
3147133PAMPLIN
Solar/Wind Harmer
0.115
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.496
3150341NORNECKC1
Adder
1.484
966001AG1-469 GEN
Solar/Wind Harmer
0.083
3151731LOISA B
Adder
9.244
3151721LOISA A
Adder
9.197
315673AE1-157 GEN
Solar/Wind Harmer
9.786
3145493TOT1
Solar/Wind Harmer
0.326
3145453TOT5
Solar/Wind Harmer
0.196
3145603CNETO
Solar/Wind Harmer
0.13
961601AG1-000A GEN
Solar/Wind Harmer
2.463
316263AC1-034 GEN
Solar/Wind Harmer
5.264
962561AG1-105 GEN
Solar/Wind Harmer
6.627
3146776BUCKING
Solar/Wind Harmer
0.551
3146776BUCKING
Solar/Wind Harmer
0.045
964791AG1-342 GEN
Solar/Wind Harmer
2.629
3146843MT LREL
Solar/Wind Harmer
0.137
3146843MT LREL
Solar/Wind Harmer
0.137
3150391LDYSMT3
Adder
18.067
972195AH1-682 GEN
Adder
2.374
316468AD1-105 GEN
Solar/Wind Harmer
-0.044
316303AF2-085
50/50
3.567
971285AH1-108 GEN
50/50
1.443
315244AE2-183_ST
50/50
5.089
963041AG1-153 GEN
50/50
4.694
3151081ELIZAR1
50/50
17.092
3151091ELIZAR2
50/50
16.795
316164AC1-076 GEN
Solar/Wind Harmer
0.366
316233AE1-074 FULL
Solar/Wind Harmer
0.153
971281AH1-106 GEN
Solar/Wind Harmer
2.654
971283AH1-107 GEN
Solar/Wind Harmer
2.654
941031AE2-094 GEN
Solar/Wind Harmer
33.713
944011AF1-069 GEN
Solar/Wind Harmer
11.015
970673AG2-436 GEN
Solar/Wind Harmer
38.362
970673AG2-436 GEN
Solar/Wind Harmer
25.574
3143316POE
Solar/Wind Harmer
0.707
971967AH1-528 GEN
Solar/Wind Harmer
28.408
3152611GOSPORTB
Adder
2.236
3152621GOSPORTC
Adder
1.898
3152601GOSPORTA
Adder
1.751
316315AB2-025 C
Solar/Wind Harmer
0.141
957871AF2-081 GEN
Solar/Wind Harmer
8.68
315814AE2-033 C
Solar/Wind Harmer
13.794
971445AH1-216 GEN
Solar/Wind Harmer
12.275
319010AE1-072 C
Solar/Wind Harmer
0.876
3146406KITTY HAWK
Solar/Wind Harmer
0.022
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.119
316311AC2-079 GEN
Solar/Wind Harmer
4.99
316305AF2-043 C
Solar/Wind Harmer
0.001
972265AH1-717 GEN
Adder
13.481
3151201GRAVEL4
Adder
12.638
3151191GRAVEL3
Adder
12.478
3151211GRAVEL5
Adder
12.478
316369SG1_INVT
Solar/Wind Harmer
0.006
316132AB2-190 GEN1
Solar/Wind Harmer
0.93
315835AF2-110_GEN
Solar/Wind Harmer
1.187
313526AB2-022
Solar/Wind Harmer
0.093
3146486SUNBURY
Solar/Wind Harmer
0.172
3146486SUNBURY
Solar/Wind Harmer
0.172
316321Z2-027
Solar/Wind Harmer
0.032
3146396TANGLEW
Solar/Wind Harmer
0.473
3145176PASQUOTANK
Solar/Wind Harmer
0.106
970085AG2-068 GEN
Solar/Wind Harmer
9.004
970581AG2-369 GEN
Solar/Wind Harmer
7.744
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.166
3130156CHOWAN
Solar/Wind Harmer
0.166
315976AC1-164 GENA
Solar/Wind Harmer
17.177
316169AC1-164_GENC
Solar/Wind Harmer
14.839
315975AC1-164 GENB
Solar/Wind Harmer
0.508
316312AB1-027
Solar/Wind Harmer
0.296
3138283WHITEMARSH
Solar/Wind Harmer
0.038
971167AH1-042 GEN
Solar/Wind Harmer
14.667
3142433PROV 92
Adder
0.32
3142433PROV 92
Adder
0.32
315816AE2-034 GEN
Solar/Wind Harmer
0.7
3143873LANEXA
Solar/Wind Harmer
0.097
3130546PLYMOUTH
Solar/Wind Harmer
0.161
970189AG2-124 GEN
Solar/Wind Harmer
4.756
316314AB2-024 C
Solar/Wind Harmer
0.001
965291AG1-394 GEN
Solar/Wind Harmer
0.712
315732AD1-074 GEN1
Solar/Wind Harmer
0.921
315733AD1-074 GEN2
Solar/Wind Harmer
0.921
315735AD1-075 GEN1
Solar/Wind Harmer
0.461
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.032
3145893MURPHYS
Solar/Wind Harmer
0.429
3145893MURPHYS
Solar/Wind Harmer
0.159
3146206CASHIE
Solar/Wind Harmer
0.159
970601AG2-382 GEN
Solar/Wind Harmer
5.933
972189AH1-679 GEN
Adder
2.633
3141913WHIT STONE
Solar/Wind Harmer
0.157
3145513AHOSKIE
Solar/Wind Harmer
0.328
3145513AHOSKIE
Solar/Wind Harmer
0.157
3146043SEABORD
Solar/Wind Harmer
0.156
316087AB2-174 GEN
Solar/Wind Harmer
0.004
3138133OCRAN
Solar/Wind Harmer
0.047
315607AA1-063A GEN
Solar/Wind Harmer
0.319
3145683EARLEYS
Solar/Wind Harmer
0.312
3145683EARLEYS
Solar/Wind Harmer
0.156
3145683EARLEYS
Solar/Wind Harmer
0.156
3141783LANCAST
Solar/Wind Harmer
0.093
3141783LANCAST
Solar/Wind Harmer
0.062
315652AC1-086 GEN
Solar/Wind Harmer
17.007
3137643SOCKMAN
Solar/Wind Harmer
0.617
3145796HORNRTN
Solar/Wind Harmer
0.487
3145796HORNRTN
Solar/Wind Harmer
0.061
962981AG1-147 GEN
Solar/Wind Harmer
5.679
3146033SCOT NK
Solar/Wind Harmer
0.602
970327AG2-215 GEN
Solar/Wind Harmer
4.937
970831AG2-522 GEN
Solar/Wind Harmer
6.34
316005AA1-067
Solar/Wind Harmer
0.155
3145746EVERETS
Solar/Wind Harmer
0.575
3145746EVERETS
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
0.144
970181AG2-120 GEN
Solar/Wind Harmer
1.799
971443AH1-215 GEN
Solar/Wind Harmer
2.423
3144303KENBRDG
Solar/Wind Harmer
0.115
970683AG2-441 GEN
Solar/Wind Harmer
9.607
970681AG2-440 GEN
Solar/Wind Harmer
7.685
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
946301AF1-294 GEN
Solar/Wind Harmer
2.841
961791AG1-021 GEN
Solar/Wind Harmer
1.382
315657AE1-056 GEN
Solar/Wind Harmer
4.964
3141813NORNECK
Solar/Wind Harmer
0.143
957861AF2-080 GEN
Solar/Wind Harmer
6.144
316420AA1-050 GEN
Solar/Wind Harmer
0.005
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.141
3145573BETHELC
Solar/Wind Harmer
0.141
970285AG2-188 GEN
Solar/Wind Harmer
11.015
971845AH1-439 GEN
Solar/Wind Harmer
6.271
3150411LDYSMT5
Adder
18.158
3150381LDYSMT2
Adder
17.377
972213AH1-691 GEN
Adder
2.94
972215AH1-692 GEN
Adder
2.94
3147346CASHSCORNER
Solar/Wind Harmer
0.311
316118AC1-105 GEN
Solar/Wind Harmer
0.346
3147173SINAI
Solar/Wind Harmer
0.131
3147243WELCO
Solar/Wind Harmer
0.082
972205AH1-687 GEN
Adder
5.595
316223AC1-118
Solar/Wind Harmer
0.091
971447AH1-217 GEN
Solar/Wind Harmer
3.599
970865AG2-541 GEN
Solar/Wind Harmer
4.024
3145273HOLLAND
Solar/Wind Harmer
0.127
316382AG1-145 C
Solar/Wind Harmer
0.001
970293AG2-193 GEN
Solar/Wind Harmer
1.792
3146376EDENTON
Solar/Wind Harmer
0.166
3142416OLDCHRC
Solar/Wind Harmer
1.602
3142433PROV 92
Adder
0.32
3142433PROV 92
Adder
0.32
315614AA2-178 GEN
Solar/Wind Harmer
0.934
316365GEN2_N
Solar/Wind Harmer
0.363
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
971157AH1-035 GEN
Solar/Wind Harmer
1.929
3141843SHACKLE
Adder
0.82
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
315737AD1-076 GEN
Solar/Wind Harmer
2.062
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
2.134
316156AD2-030 GEN
Solar/Wind Harmer
0.118
3141873WAN 176
Solar/Wind Harmer
2.836
316473AC1-191 GEN
Solar/Wind Harmer
0.538
3145893MURPHYS
Solar/Wind Harmer
0.266
3145893MURPHYS
Solar/Wind Harmer
0.159
3146206CASHIE
Solar/Wind Harmer
0.159
957521AF2-046 GEN
Solar/Wind Harmer
11.795
961681AG1-008 GEN
Solar/Wind Harmer
11.795
3132273ORANGE
Solar/Wind Harmer
0.032
3146173TUNIS
Solar/Wind Harmer
0.157
3156021HOLLOMANSOL
Solar/Wind Harmer
0.713
316463AE2-346 GEN
Solar/Wind Harmer
0.135
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.672
313506AB2-031 GEN
Solar/Wind Harmer
0.482
316478AD1-087 GEN
Solar/Wind Harmer
0.543
316486AD2-202 GEN
Solar/Wind Harmer
0.159
3146263WOODLND
Solar/Wind Harmer
0.155
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
3147043LAWRENC
Solar/Wind Harmer
0.092
316317KELFORD C
Solar/Wind Harmer
0.015
3145823KELFORD
Solar/Wind Harmer
0.153
3145963POPLR C
Solar/Wind Harmer
0.153
3145796HORNRTN
Solar/Wind Harmer
0.609
3145796HORNRTN
Solar/Wind Harmer
0.152
962971AG1-146 GEN
Solar/Wind Harmer
2.434
970009AG2-005 GEN
Solar/Wind Harmer
1.123
970909AG2-566 GEN
Solar/Wind Harmer
1.6
316210AC1-098 GEN
Solar/Wind Harmer
1.377
316404AE1-155 C
Solar/Wind Harmer
0.033
3145933PARMELE
Solar/Wind Harmer
0.147
966801AG1-551 GEN
Solar/Wind Harmer
1.716
315724AD1-057 GEN
Solar/Wind Harmer
0.543
3145746EVERETS
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
0.144
316131AB2-060 GEN
Solar/Wind Harmer
0.454
964241AG1-285 GEN
Solar/Wind Harmer
9.624
315785AD2-033 C
Solar/Wind Harmer
1.173
970257AG2-171 GEN
Solar/Wind Harmer
4.614
959311AF2-222 GEN
Solar/Wind Harmer
12.815
316170AC1-121 GEN2
Solar/Wind Harmer
0.154
963181AG1-167 GEN
Solar/Wind Harmer
0.576
3144293JTRSVLE
Adder
0.458
3147133PAMPLIN
Solar/Wind Harmer
0.452
971193AH1-056 GEN
Solar/Wind Harmer
8.764
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.086
316327AA2-057 GEN
Solar/Wind Harmer
0.217
3150351NORNECKC2
Adder
1.449
3151761LOISA E
Adder
18.847
3146233WITAKRS
Solar/Wind Harmer
0.708
3146233WITAKRS
Solar/Wind Harmer
0.096
3138543CONSLDL
Solar/Wind Harmer
0.093
3146073TAR RVR
Solar/Wind Harmer
0.141
3146083TARBORO
Solar/Wind Harmer
0.141
961601AG1-000A GEN
Solar/Wind Harmer
9.854
3145543BTLEBRO
Solar/Wind Harmer
0.138
3145543BTLEBRO
Solar/Wind Harmer
0.138
971623AH1-311 GEN
Solar/Wind Harmer
0.277
972183AH1-676 GEN
Adder
147.354
3146776BUCKING
Solar/Wind Harmer
0.05
3150401LDYSMT4
Adder
18.101
3150371LDYSMT1
Adder
17.49
971781AH1-399 GEN
Solar/Wind Harmer
0.177
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.61
3141906WESTMOR
Solar/Wind Harmer
0.051
970221AG2-151 GEN
Solar/Wind Harmer
6.519
971683AH1-343 GEN
Solar/Wind Harmer
4.456
970737AG2-469 GEN
Solar/Wind Harmer
5.095
316283AC2-100 C
Solar/Wind Harmer
0.231
971489AH1-241 GEN
Solar/Wind Harmer
6.519
316222AC1-221 GEN
Solar/Wind Harmer
0.492
3152251N ANNA1
50/50
17.069
971507AH1-251 GEN
50/50
10.56
970119AG2-088 GEN
50/50
26.753
3150851SPRUNCC
50/50
0.882
315243AE2-183_GT3
50/50
2.943
3151051BRUNSWICKS1
50/50
4.812
3151021BRUNSWICKG1
50/50
2.318
971451AH1-221 GEN
50/50
7.041
316045AC1-158 PL2
Solar/Wind Harmer
9.498
3147666LOUISA
Solar/Wind Harmer
0.935
316192AB2-158 GEN
Solar/Wind Harmer
1.293
3143226MDLTHAN
Solar/Wind Harmer
0.2
3143526WINTERP
Solar/Wind Harmer
0.994
940641AE2-051 GEN
Solar/Wind Harmer
14.986
939411AE1-173 GEN
Solar/Wind Harmer
78.651
316294AC1-161 GEN
Solar/Wind Harmer
3.077
944591AF1-124 GEN
Solar/Wind Harmer
39.816
316375AC2-012 GEN
Solar/Wind Harmer
0.004
3150981CHESPKA
Adder
2.192
970659AG2-427 GEN
Solar/Wind Harmer
8.481
316381AD1-082 GEN
Solar/Wind Harmer
0.183
315671AE2-027_GEN
Solar/Wind Harmer
11.214
3142543TWELFTH
Solar/Wind Harmer
0.017
970661AG2-428 GEN
Solar/Wind Harmer
17.39
316388AE2-253 GEN
Solar/Wind Harmer
0.547
3145336SMITFLD
Solar/Wind Harmer
0.697
3146456SLIGO L269
Solar/Wind Harmer
0.174
316246AF1-032 C
Solar/Wind Harmer
0.078
3151171GRAVELC
Adder
1.847
961611AG1-000B GEN
Solar/Wind Harmer
9.102
971647AH1-324 GEN
Solar/Wind Harmer
7.403
316072AD1-144
Solar/Wind Harmer
0.063
971069AG2-661 GEN
Solar/Wind Harmer
3.083
316458AB2-190 GEN2
Solar/Wind Harmer
0.93
970129AG2-093 GEN
Solar/Wind Harmer
4.931
3143096IRON208
Adder
0.724
316093AE2-104_GEN
Solar/Wind Harmer
2.908
3143336POWHATN
Solar/Wind Harmer
3.072
3138126ROCKLANDING
Solar/Wind Harmer
0.078
944631AF1-128 GEN
Adder
81.389
3146516WINFALL
Solar/Wind Harmer
0.552
3146516WINFALL
Solar/Wind Harmer
0.17
970919AG2-571 GEN
Solar/Wind Harmer
6.028
316159AE1-175 C
Solar/Wind Harmer
0.146
971317AH1-138 GEN
Solar/Wind Harmer
1.261
970087AG2-069 GEN
Solar/Wind Harmer
13.506
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.166
316336AC2-165 C
Solar/Wind Harmer
0.006
3142416OLDCHRC
Solar/Wind Harmer
0.43
3142416OLDCHRC
Solar/Wind Harmer
0.165
3142433PROV 92
Solar/Wind Harmer
0.658
3142433PROV 92
Adder
0.32
3142433PROV 92
Adder
0.32
3145663CRESWEL
Solar/Wind Harmer
0.457
971163AH1-040 GEN
Solar/Wind Harmer
13.055
957481AF2-042 GEN
Solar/Wind Harmer
43.165
316023GEN1_S
Solar/Wind Harmer
0.363
971777AH1-397 GEN
Solar/Wind Harmer
0.424
3141843SHACKLE
Adder
0.82
3141766HARMONY
Solar/Wind Harmer
0.032
3145893MURPHYS
Solar/Wind Harmer
0.635
3145893MURPHYS
Solar/Wind Harmer
0.706
3146206CASHIE
Solar/Wind Harmer
0.159
971547AH1-271 GEN
Solar/Wind Harmer
3.39
315693AD1-088 GEN
Solar/Wind Harmer
7.618
962491AG1-098 GEN
Solar/Wind Harmer
9.031
960081AF2-299 GEN
Solar/Wind Harmer
1.516
3146173TUNIS
Solar/Wind Harmer
0.157
3138133OCRAN
Solar/Wind Harmer
0.094
3145683EARLEYS
Solar/Wind Harmer
0.156
3146263WOODLND
Solar/Wind Harmer
0.155
971795AH1-408 GEN
Solar/Wind Harmer
10.34
316011AB1-132 GEN
Solar/Wind Harmer
2.811
962571AG1-106 GEN
Solar/Wind Harmer
2.2
316190AA2-174 GEN
Solar/Wind Harmer
0
3147043LAWRENC
Adder
1.392
3145823KELFORD
Solar/Wind Harmer
0.153
3145963POPLR C
Solar/Wind Harmer
0.153
3145783HORNRTN
Solar/Wind Harmer
0.152
3145796HORNRTN
Solar/Wind Harmer
0.502
3145796HORNRTN
Solar/Wind Harmer
0.152
316174AB2-169 GEN
Solar/Wind Harmer
0.004
962861AG1-135 GEN
Solar/Wind Harmer
4.751
316212AC1-099_GEN
Solar/Wind Harmer
0.768
316129AC1-054 GEN
Solar/Wind Harmer
0.557
971065AG2-659 GEN
Solar/Wind Harmer
6.296
3146293MARTNCO
Solar/Wind Harmer
0.137
970937AG2-583 GEN
Solar/Wind Harmer
9.004
315687AD1-152 GEN
Solar/Wind Harmer
0.005
966881AG1-559 GEN
Solar/Wind Harmer
0.168
3141726DUNNSVL
Solar/Wind Harmer
0.58
315722AD1-056 GEN
Solar/Wind Harmer
0.916
3145746EVERETS
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
0.144
970685AG2-442 GEN
Solar/Wind Harmer
10.759
316254AC1-120 GEN1
Solar/Wind Harmer
0.307
316237AB2-079_GEN
Solar/Wind Harmer
0.001
963171AG1-166 GEN
Solar/Wind Harmer
0.768
971563AH1-280 GEN
Solar/Wind Harmer
1.536
3144293JTRSVLE
Adder
0.458
3146926FARMVIL
Solar/Wind Harmer
0.086
3150351NORNECKC2
Adder
1.425
316494AC1-189 GEN
Solar/Wind Harmer
0.481
3151751LOISA D
Adder
9.244
3146233WITAKRS
Solar/Wind Harmer
0.561
961671AG1-007 GEN
Solar/Wind Harmer
0.022
3146083TARBORO
Solar/Wind Harmer
0.141
3145493TOT1
Solar/Wind Harmer
0.626
3145543BTLEBRO
Solar/Wind Harmer
0.138
3145543BTLEBRO
Solar/Wind Harmer
0.111
316359AB2-059 GEN
Solar/Wind Harmer
0.498
316049AB1-081 GEN
Solar/Wind Harmer
0.793
3142053HEARTS
Solar/Wind Harmer
0.244
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.055
970401AG2-262 GEN
Solar/Wind Harmer
0.803
316337AD2-073 GEN
Solar/Wind Harmer
0.118
972197AH1-683 GEN
Adder
2.827
972219AH1-694 GEN
Adder
2.035
972003AH1-546 GEN
Solar/Wind Harmer
5.618
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971377AH1-170 GEN
Solar/Wind Harmer
1.304
3147623JAMES R
Solar/Wind Harmer
0.283
972135AH1-637 GEN
Solar/Wind Harmer
0.976
LAGNLTFEXP_LAGN->PJM
CLTF
5.963
CBM South 2LTFEXP_CBM-S2->PJM
CBM
19.52
TVALTFEXP_TVA->PJM
CLTF
3.02
NYPJM->LTFIMP_NY
CLTF
2.547
LGEELTFEXP_LGEE->PJM
CLTF
0.9
WECLTFEXP_WEC->PJM
CLTF
0.426
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.817
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.186
MECLTFEXP_MEC->PJM
CLTF
2.509
SIGELTFEXP_SIGE->PJM
CLTF
0.076
CPLELTFEXP_CPLE->PJM
CLTF
9
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.036

Details for AD2-074 TAP-AG1-146 TP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1059_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AD2-074 TAP-AG1-146 TP 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1059_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:135.42 %
Rating:203.98 MVA
Rating Type:B
MVA to Mitigate:276.24
MW Contribution:36.89
Bus #Bus NameTypeMW Contribution
316404AE1-155 C
Solar/Wind Harmer
0.253
970009AG2-005 GEN
Solar/Wind Harmer
8.393
958261AF2-120 GEN
Solar/Wind Harmer
37.168
970327AG2-215 GEN
Solar/Wind Harmer
36.888
966661AG1-536 GEN
50/50
31.973
962861AG1-135 GEN
Solar/Wind Harmer
35.969
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.048
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.148
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.047
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.049
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.03
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.221
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 65_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:175.73 %
Rating:203.98 MVA
Rating Type:B
MVA to Mitigate:358.46
MW Contribution:36.89
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
31.973
962861AG1-135 GEN
Solar/Wind Harmer
35.969
970575AG2-366 GEN
50/50
19.983
316404AE1-155 C
Solar/Wind Harmer
0.253
962971AG1-146 GEN
Solar/Wind Harmer
17.985
970009AG2-005 GEN
Solar/Wind Harmer
8.393
962981AG1-147 GEN
Solar/Wind Harmer
41.964
970327AG2-215 GEN
Solar/Wind Harmer
36.888
958261AF2-120 GEN
Solar/Wind Harmer
37.168
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.048
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.148
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.047
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.049
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.03
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.221
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1021_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1021_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:155.02 %
Rating:203.98 MVA
Rating Type:B
MVA to Mitigate:316.21
MW Contribution:36.89
Bus #Bus NameTypeMW Contribution
958261AF2-120 GEN
Solar/Wind Harmer
37.166
970575AG2-366 GEN
50/50
19.982
316404AE1-155 C
Solar/Wind Harmer
0.253
962971AG1-146 GEN
Solar/Wind Harmer
17.983
970009AG2-005 GEN
Solar/Wind Harmer
8.392
3141913WHIT STONE
Solar/Wind Harmer
1.123
3141783LANCAST
Solar/Wind Harmer
0.674
3141783LANCAST
Solar/Wind Harmer
0.45
3138133OCRAN
Solar/Wind Harmer
0.337
962981AG1-147 GEN
Solar/Wind Harmer
41.961
970327AG2-215 GEN
Solar/Wind Harmer
36.886
966661AG1-536 GEN
50/50
31.97
3138133OCRAN
Solar/Wind Harmer
0.674
962861AG1-135 GEN
Solar/Wind Harmer
35.967
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.051
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.16
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.051
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.053
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.032
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.238
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.07 %
Rating:203.98 MVA
Rating Type:A
MVA to Mitigate:230.65
MW Contribution:19.59
Bus #Bus NameTypeMW Contribution
970575AG2-366 GEN
50/50
9.267
3141843SHACKLE
50/50
0.642
315749AE2-041 GEN
50/50
2.872
316404AE1-155 C
Solar/Wind Harmer
0.162
970009AG2-005 GEN
Solar/Wind Harmer
4.456
962971AG1-146 GEN
Solar/Wind Harmer
8.34
316156AD2-030 GEN
Solar/Wind Harmer
0.139
3141873WAN 176
Solar/Wind Harmer
3.327
316280AD1-041 GEN
Solar/Wind Harmer
0.003
316203AE2-005 GEN
Solar/Wind Harmer
0
3141766HARMONY
Solar/Wind Harmer
1.077
3141906WESTMOR
Solar/Wind Helper
0.046
966661AG1-536 GEN
50/50
20.452
3141843SHACKLE
50/50
0.642
962861AG1-135 GEN
Solar/Wind Harmer
21.972
3138133OCRAN
Solar/Wind Harmer
0.197
971777AH1-397 GEN
Solar/Wind Harmer
0.313
958261AF2-120 GEN
Solar/Wind Harmer
23.775
316077AC2-138 C
Solar/Wind Helper
0.348
3141766HARMONY
Solar/Wind Harmer
0.016
316337AD2-073 GEN
Solar/Wind Helper
0.189
315759AF1-018 GEN
50/50
2.872
970327AG2-215 GEN
Solar/Wind Harmer
19.585
962981AG1-147 GEN
Solar/Wind Harmer
19.461
3141783LANCAST
Solar/Wind Harmer
0.235
3141783LANCAST
Solar/Wind Harmer
0.157
3138133OCRAN
Solar/Wind Harmer
0.098
3141913WHIT STONE
Solar/Wind Harmer
0.299
3141873WAN 176
Solar/Wind Harmer
0.037
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
3.533
3138283WHITEMARSH
Solar/Wind Harmer
0.022
316059AD1-063 C
Solar/Wind Harmer
0.001
3141813NORNECK
Solar/Wind Helper
0.37
316223AC1-118
Solar/Wind Helper
0.174
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.019
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.059
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.153
GibsonPJM->LTFIMP_GIBSON
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.067
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.065
CPLELTFEXP_CPLE->PJM
CLTF
0.088
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AE1-157 TAP-6LDYSMITH CT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AE1-157 TAP-6LDYSMITH CT 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:137.7 %
Rating:1478.62 MVA
Rating Type:B
MVA to Mitigate:2036.01
MW Contribution:2.79
Bus #Bus NameTypeMW Contribution
315052AA1-145 CT2
50/50
2.93
966881AG1-559 GEN
Solar/Wind Harmer
0.767
3142416OLDCHRC
Solar/Wind Harmer
0.42
3142416OLDCHRC
Solar/Wind Harmer
0.161
3143096IRON208
Adder
0.565
3142543TWELFTH
Solar/Wind Harmer
0.013
944631AF1-128 GEN
Adder
61.065
3150851SPRUNCC
Adder
0.59
315671AE2-027_GEN
Solar/Wind Harmer
7.592
970129AG2-093 GEN
Solar/Wind Harmer
3.33
316458AB2-190 GEN2
Solar/Wind Harmer
0.626
3142433PROV 92
Solar/Wind Harmer
0.461
3142433PROV 92
Adder
0.224
3142433PROV 92
Adder
0.224
971069AG2-661 GEN
Solar/Wind Harmer
2.027
3143526WINTERP
Solar/Wind Harmer
0.585
316159AE1-175 C
Solar/Wind Harmer
0.096
971647AH1-324 GEN
Solar/Wind Harmer
4.69
961611AG1-000B GEN
Solar/Wind Harmer
5.643
3151171GRAVELC
Adder
1.114
971317AH1-138 GEN
Solar/Wind Harmer
0.779
3141766HARMONY
Solar/Wind Harmer
0.021
971777AH1-397 GEN
Solar/Wind Harmer
0.275
3141843SHACKLE
Adder
0.532
3138126ROCKLANDING
Solar/Wind Harmer
0.047
970659AG2-427 GEN
Solar/Wind Harmer
4.989
316381AD1-082 GEN
Solar/Wind Harmer
0.107
970661AG2-428 GEN
Solar/Wind Harmer
10.027
3145336SMITFLD
Solar/Wind Harmer
0.402
3143226MDLTHAN
Solar/Wind Harmer
0.096
316072AD1-144
Solar/Wind Harmer
0.034
3138133OCRAN
Solar/Wind Harmer
0.057
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
1.175
316294AC1-161 GEN
Solar/Wind Harmer
1.611
316093AE2-104_GEN
Solar/Wind Harmer
1.559
944591AF1-124 GEN
Solar/Wind Harmer
20.933
316388AE2-253 GEN
Solar/Wind Harmer
0.289
316246AF1-032 C
Solar/Wind Harmer
0.042
3146456SLIGO L269
Solar/Wind Harmer
0.092
3146516WINFALL
Solar/Wind Harmer
0.29
3146516WINFALL
Solar/Wind Harmer
0.089
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.086
3145663CRESWEL
Solar/Wind Harmer
0.235
971163AH1-040 GEN
Solar/Wind Harmer
6.732
962861AG1-135 GEN
Solar/Wind Harmer
2.618
939411AE1-173 GEN
Solar/Wind Harmer
34.828
3146206CASHIE
Solar/Wind Harmer
0.081
971547AH1-271 GEN
Solar/Wind Harmer
1.726
972277AH1-723 GEN
Adder
48.21
3145893MURPHYS
Solar/Wind Harmer
0.321
3145893MURPHYS
Solar/Wind Harmer
0.357
316023GEN1_S
Solar/Wind Harmer
0.179
3143336POWHATN
Solar/Wind Harmer
1.418
3146173TUNIS
Solar/Wind Harmer
0.079
3145683EARLEYS
Solar/Wind Harmer
0.078
940641AE2-051 GEN
Solar/Wind Harmer
6.235
3146263WOODLND
Solar/Wind Harmer
0.077
3141726DUNNSVL
Solar/Wind Harmer
0.309
3145963POPLR C
Solar/Wind Harmer
0.077
960081AF2-299 GEN
Solar/Wind Harmer
0.737
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145823KELFORD
Solar/Wind Harmer
0.076
316011AB1-132 GEN
Solar/Wind Harmer
1.384
962571AG1-106 GEN
Solar/Wind Harmer
1.083
316336AC2-165 C
Solar/Wind Harmer
0.003
316190AA2-174 GEN
Solar/Wind Harmer
0
3145796HORNRTN
Solar/Wind Harmer
0.247
3145796HORNRTN
Solar/Wind Harmer
0.075
3145783HORNRTN
Solar/Wind Harmer
0.074
971795AH1-408 GEN
Solar/Wind Harmer
4.936
3146293MARTNCO
Solar/Wind Harmer
0.068
3147043LAWRENC
Adder
0.658
316212AC1-099_GEN
Solar/Wind Harmer
0.376
3150351NORNECKC2
Adder
0.723
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
315722AD1-056 GEN
Solar/Wind Harmer
0.444
316494AC1-189 GEN
Solar/Wind Harmer
0.235
970919AG2-571 GEN
Solar/Wind Harmer
2.436
970087AG2-069 GEN
Solar/Wind Harmer
5.462
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.068
3145493TOT1
Solar/Wind Harmer
0.303
316129AC1-054 GEN
Solar/Wind Harmer
0.256
3146233WITAKRS
Solar/Wind Harmer
0.27
971065AG2-659 GEN
Solar/Wind Harmer
2.88
316359AB2-059 GEN
Solar/Wind Harmer
0.239
316049AB1-081 GEN
Solar/Wind Harmer
0.38
3145543BTLEBRO
Solar/Wind Harmer
0.066
3145543BTLEBRO
Solar/Wind Harmer
0.053
3142053HEARTS
Solar/Wind Harmer
0.117
957481AF2-042 GEN
Solar/Wind Harmer
17.703
315693AD1-088 GEN
Solar/Wind Harmer
3.143
962491AG1-098 GEN
Solar/Wind Harmer
3.727
970937AG2-583 GEN
Solar/Wind Harmer
3.946
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970685AG2-442 GEN
Solar/Wind Harmer
4.652
963171AG1-166 GEN
Solar/Wind Harmer
0.33
971563AH1-280 GEN
Solar/Wind Harmer
0.661
3144293JTRSVLE
Adder
0.197
315687AD1-152 GEN
Solar/Wind Harmer
0.002
3146926FARMVIL
Solar/Wind Harmer
0.036
970401AG2-262 GEN
Solar/Wind Harmer
0.352
316337AD2-073 GEN
Solar/Wind Harmer
0.051
316322AB2-045
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
0.023
3142296MT RD221
50/50
0.608
3142366NRTHEST
50/50
0.528
3150691DARBY 3
50/50
11.375
3150701DARBY 4
50/50
11.349
3150681DARBY 2
50/50
11.335
315673AE1-157 GEN
Solar/Wind Harmer
52.424
957411AF2-035 GEN
Solar/Wind Harmer
28.305
970317AG2-208 GEN
Solar/Wind Harmer
26.223
966871AG1-558 GEN
Solar/Wind Harmer
0.187
3150671DARBY 1
Adder
10.67
316075AC2-137 C
Solar/Wind Harmer
0.038
3142946ENON
Solar/Wind Harmer
0.013
944641AF1-129 GEN
Adder
59.87
316240AF1-291 C
Solar/Wind Harmer
0.001
3143526WINTERP
Solar/Wind Harmer
0.585
316033AB2-134 GEN
Solar/Wind Harmer
0.007
315697AD1-025 GEN
Solar/Wind Harmer
0.126
972189AH1-679 GEN
50/50
6.54
316312AB1-027
Solar/Wind Harmer
0.289
971285AH1-108 GEN
Adder
0.966
315976AC1-164 GENA
Solar/Wind Harmer
13.07
316169AC1-164_GENC
Solar/Wind Harmer
11.292
315975AC1-164 GENB
Solar/Wind Harmer
0.387
971167AH1-042 GEN
Solar/Wind Harmer
10.363
316132AB2-190 GEN1
Solar/Wind Harmer
0.626
3142433PROV 92
Adder
0.224
3142433PROV 92
Adder
0.224
316233AE1-074 FULL
Solar/Wind Harmer
0.09
971281AH1-106 GEN
Solar/Wind Harmer
1.562
971283AH1-107 GEN
Solar/Wind Harmer
1.562
316369SG1_INVT
Solar/Wind Harmer
0.004
3143873LANEXA
Solar/Wind Harmer
0.066
316314AB2-024 C
Solar/Wind Harmer
0
3143316POE
Solar/Wind Harmer
0.414
972265AH1-717 GEN
Adder
8.131
3151201GRAVEL4
Adder
7.623
3151191GRAVEL3
Adder
7.526
3151211GRAVEL5
Adder
7.526
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
3.086
315662AE1-191 GEN
Solar/Wind Harmer
0.003
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3138283WHITEMARSH
Solar/Wind Harmer
0.024
971445AH1-216 GEN
Solar/Wind Harmer
7.113
3141873WAN 176
Solar/Wind Harmer
0.02
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.066
316311AC2-079 GEN
Solar/Wind Harmer
2.768
3141913WHIT STONE
Solar/Wind Harmer
0.096
3138133OCRAN
Solar/Wind Harmer
0.028
3152611GOSPORTB
Adder
1.198
3152621GOSPORTC
Adder
1.017
3152601GOSPORTA
Adder
0.938
3151081ELIZAR1
Adder
8.608
3151091ELIZAR2
Adder
8.459
3141783LANCAST
Solar/Wind Harmer
0.056
3141783LANCAST
Solar/Wind Harmer
0.037
315835AF2-110_GEN
Solar/Wind Harmer
0.636
316305AF2-043 C
Solar/Wind Harmer
0.001
957871AF2-081 GEN
Solar/Wind Harmer
4.589
319010AE1-072 C
Solar/Wind Harmer
0.463
3146406KITTY HAWK
Solar/Wind Harmer
0.011
313526AB2-022
Solar/Wind Harmer
0.049
3146486SUNBURY
Solar/Wind Harmer
0.091
3146486SUNBURY
Solar/Wind Harmer
0.091
316321Z2-027
Solar/Wind Harmer
0.017
3146396TANGLEW
Solar/Wind Harmer
0.249
3145176PASQUOTANK
Solar/Wind Harmer
0.056
962981AG1-147 GEN
Solar/Wind Harmer
3.282
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
316315AB2-025 C
Solar/Wind Harmer
0.071
315814AE2-033 C
Solar/Wind Harmer
6.916
3130156CHOWAN
Solar/Wind Harmer
0.086
3130156CHOWAN
Solar/Wind Harmer
0.086
970327AG2-215 GEN
Solar/Wind Harmer
2.794
315816AE2-034 GEN
Solar/Wind Harmer
0.361
3130546PLYMOUTH
Solar/Wind Harmer
0.082
315732AD1-074 GEN1
Solar/Wind Harmer
0.471
315733AD1-074 GEN2
Solar/Wind Harmer
0.471
315735AD1-075 GEN1
Solar/Wind Harmer
0.236
965291AG1-394 GEN
Solar/Wind Harmer
0.361
3146206CASHIE
Solar/Wind Harmer
0.081
970601AG2-382 GEN
Solar/Wind Harmer
3.02
972193AH1-681 GEN
Adder
1.848
3145893MURPHYS
Solar/Wind Harmer
0.217
3145893MURPHYS
Solar/Wind Harmer
0.08
3145513AHOSKIE
Solar/Wind Harmer
0.165
3145513AHOSKIE
Solar/Wind Harmer
0.079
3145683EARLEYS
Solar/Wind Harmer
0.157
3145683EARLEYS
Solar/Wind Harmer
0.078
3145683EARLEYS
Solar/Wind Harmer
0.078
3146043SEABORD
Solar/Wind Harmer
0.078
315607AA1-063A GEN
Solar/Wind Harmer
0.158
315652AC1-086 GEN
Solar/Wind Harmer
8.376
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.3
3145796HORNRTN
Solar/Wind Harmer
0.239
3145796HORNRTN
Solar/Wind Harmer
0.03
3146033SCOT NK
Solar/Wind Harmer
0.297
941031AE2-094 GEN
Solar/Wind Harmer
13.369
944011AF1-069 GEN
Solar/Wind Harmer
4.368
3141813NORNECK
Solar/Wind Harmer
0.072
970673AG2-436 GEN
Solar/Wind Harmer
15.278
970673AG2-436 GEN
Solar/Wind Harmer
10.185
316005AA1-067
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.283
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
970181AG2-120 GEN
Solar/Wind Harmer
0.885
971967AH1-528 GEN
Solar/Wind Harmer
11.354
957861AF2-080 GEN
Solar/Wind Harmer
2.998
316420AA1-050 GEN
Solar/Wind Harmer
0.002
970831AG2-522 GEN
Solar/Wind Harmer
2.933
970085AG2-068 GEN
Solar/Wind Harmer
3.642
970581AG2-369 GEN
Solar/Wind Harmer
3.132
3145573BETHELC
Solar/Wind Harmer
0.068
3145573BETHELC
Solar/Wind Harmer
0.068
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
1.054
3144303KENBRDG
Solar/Wind Harmer
0.05
970683AG2-441 GEN
Solar/Wind Harmer
4.154
970681AG2-440 GEN
Solar/Wind Harmer
3.323
946301AF1-294 GEN
Solar/Wind Harmer
1.222
961791AG1-021 GEN
Solar/Wind Harmer
0.594
315657AE1-056 GEN
Solar/Wind Harmer
2.127
316118AC1-105 GEN
Solar/Wind Harmer
0.152
970285AG2-188 GEN
Solar/Wind Harmer
4.613
971845AH1-439 GEN
Solar/Wind Harmer
2.627
3147173SINAI
Solar/Wind Harmer
0.057
3147243WELCO
Solar/Wind Harmer
0.036
3141426STAFORD
Solar/Wind Helper
0.036
315051AA1-145 CT1
50/50
2.918
971645AH1-323 GEN
50/50
16.828
316473AC1-191 GEN
Solar/Wind Harmer
0.547
3142416OLDCHRC
Solar/Wind Harmer
1.565
970293AG2-193 GEN
Solar/Wind Harmer
1.528
3143096IRON208
Adder
0.565
3143096IRON208
Adder
0.554
3150861SPRUNCD
Adder
0.59
3142946ENON
Solar/Wind Harmer
0.043
970133AG2-095 GEN
Solar/Wind Harmer
1.165
970129AG2-093 GEN
Solar/Wind Harmer
7.076
965281AG1-393 GEN
Solar/Wind Harmer
1.247
315839AE2-212 C
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.224
3142433PROV 92
Adder
0.224
315778AD1-151 GEN
Solar/Wind Harmer
9.121
316382AG1-145 C
Solar/Wind Harmer
0.001
961611AG1-000B GEN
Solar/Wind Harmer
2.869
315813AE1-149 C
Solar/Wind Harmer
5.675
3151221GRAVEL6
Adder
7.614
3151171GRAVELC
Adder
1.465
3141766HARMONY
Solar/Wind Harmer
1.389
3141843SHACKLE
Adder
0.532
316203AE2-005 GEN
Solar/Wind Harmer
0
3144216WINCHST
Adder
0.39
3150921YORKTN3
Adder
2.595
970659AG2-427 GEN
Solar/Wind Harmer
1.091
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.002
971781AH1-399 GEN
Solar/Wind Harmer
0.134
970661AG2-428 GEN
Solar/Wind Harmer
2.133
3145336SMITFLD
Solar/Wind Harmer
0.04
316156AD2-030 GEN
Solar/Wind Harmer
0.074
3141873WAN 176
Solar/Wind Harmer
1.782
3144536CHRHLND
Solar/Wind Harmer
0.014
3144873MCLAUGH
Solar/Wind Harmer
0.002
3151101ELIZAR3
Adder
8.719
315773AC2-141 GEN
Solar/Wind Harmer
3.396
944581AF1-123 GEN
Solar/Wind Harmer
20.859
944601AF1-125 GEN
Solar/Wind Harmer
20.537
3146456SLIGO L269
Solar/Wind Harmer
0.092
971153AH1-033 GEN
Solar/Wind Harmer
1.063
316320Y1-086
Solar/Wind Harmer
0
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.089
3145273HOLLAND
Solar/Wind Harmer
0.067
3146626S HERTFORD
Solar/Wind Harmer
0.089
962971AG1-146 GEN
Solar/Wind Harmer
1.407
3146376EDENTON
Solar/Wind Harmer
0.086
970009AG2-005 GEN
Solar/Wind Harmer
0.636
315614AA2-178 GEN
Solar/Wind Harmer
0.482
971157AH1-035 GEN
Solar/Wind Harmer
0.988
315737AD1-076 GEN
Solar/Wind Harmer
1.055
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146206CASHIE
Solar/Wind Harmer
0.081
972255AH1-712 GEN
Adder
41.371
316404AE1-155 C
Solar/Wind Harmer
0.018
3145893MURPHYS
Solar/Wind Harmer
0.134
3145893MURPHYS
Solar/Wind Harmer
0.08
957521AF2-046 GEN
Solar/Wind Harmer
5.958
961681AG1-008 GEN
Solar/Wind Harmer
5.958
316365GEN2_N
Solar/Wind Harmer
0.179
316313AB2-026
Solar/Wind Harmer
0.05
316258AE1-075 C
Solar/Wind Harmer
0.06
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
1.205
3146173TUNIS
Solar/Wind Harmer
0.079
3156021HOLLOMANSOL
Solar/Wind Harmer
0.36
316463AE2-346 GEN
Solar/Wind Harmer
0.068
316140AB2-099
Solar/Wind Harmer
0.028
962331AG1-082 GEN
Solar/Wind Harmer
0.841
3146263WOODLND
Solar/Wind Harmer
0.077
3145963POPLR C
Solar/Wind Harmer
0.077
3142666NORTHAMPTON
Solar/Wind Harmer
0.076
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.076
313506AB2-031 GEN
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
0.299
3145796HORNRTN
Solar/Wind Harmer
0.075
3145933PARMELE
Solar/Wind Harmer
0.073
966801AG1-551 GEN
Solar/Wind Harmer
0.851
3147043LAWRENC
Solar/Wind Harmer
0.044
316210AC1-098 GEN
Solar/Wind Harmer
0.674
3150351NORNECKC2
Adder
0.735
3145746EVERETS
Solar/Wind Harmer
0.071
3145746EVERETS
Solar/Wind Harmer
0.071
315724AD1-057 GEN
Solar/Wind Harmer
0.263
316327AA2-057 GEN
Solar/Wind Harmer
0.105
970917AG2-570 GEN
Solar/Wind Harmer
6.089
3146073TAR RVR
Solar/Wind Harmer
0.068
3146083TARBORO
Solar/Wind Harmer
0.068
3146233WITAKRS
Solar/Wind Harmer
0.341
3146233WITAKRS
Solar/Wind Harmer
0.046
3138543CONSLDL
Solar/Wind Harmer
0.045
961601AG1-000A GEN
Solar/Wind Harmer
4.729
3145543BTLEBRO
Solar/Wind Harmer
0.066
3145543BTLEBRO
Solar/Wind Harmer
0.066
971623AH1-311 GEN
Solar/Wind Harmer
0.133
316478AD1-087 GEN
Solar/Wind Harmer
0.225
316486AD2-202 GEN
Solar/Wind Harmer
0.066
316131AB2-060 GEN
Solar/Wind Harmer
0.2
964241AG1-285 GEN
Solar/Wind Harmer
4.22
315785AD2-033 C
Solar/Wind Harmer
0.511
970257AG2-171 GEN
Solar/Wind Harmer
2.007
959311AF2-222 GEN
Solar/Wind Harmer
5.564
970909AG2-566 GEN
Solar/Wind Harmer
0.665
963181AG1-167 GEN
Solar/Wind Harmer
0.248
3144293JTRSVLE
Adder
0.197
3147133PAMPLIN
Solar/Wind Harmer
0.193
971193AH1-056 GEN
Solar/Wind Harmer
3.754
942461AE2-259 GEN
Solar/Wind Harmer
0
3146926FARMVIL
Solar/Wind Harmer
0.036
3146776BUCKING
Solar/Wind Harmer
0.021
316248AF1-058 C
Solar/Wind Harmer
0
960061AF2-297 GEN
Solar/Wind Harmer
2.45
316468AD1-105 GEN
Solar/Wind Harmer
-0.033
970657AG2-426 GEN
Solar/Wind Harmer
3.569
970657AG2-426 GEN
Solar/Wind Harmer
0.748
316236AE1-162_GEN
Solar/Wind Harmer
0.001
971223AH1-071 GEN
Solar/Wind Harmer
1.027
316036AC1-147 C
Solar/Wind Harmer
0.017
3150991CHESPKB
Adder
0.985
3150991CHESPKB
Adder
0.962
316316AC1-027 C
Solar/Wind Harmer
0.09
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.003
3145506HICKORY
Solar/Wind Harmer
0.37
3145506HICKORY
Solar/Wind Harmer
0.222
3145506HICKORY
Solar/Wind Harmer
0.056
316339AD2-160 GEN
Solar/Wind Harmer
0.15
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.051
3137176SLIGO L2192
Solar/Wind Harmer
0.366
3146456SLIGO L269
Solar/Wind Harmer
1.627
3130086AYDLETT
Solar/Wind Harmer
0.367
3146386ELIZ CT
Solar/Wind Harmer
0.091
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.089
3146516WINFALL
Solar/Wind Harmer
0.089
3146516WINFALL
Solar/Wind Harmer
0.089
3146626S HERTFORD
Solar/Wind Harmer
0.089
3146626S HERTFORD
Solar/Wind Harmer
0.089
3144356SAPONY
Solar/Wind Harmer
0.735
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.385
3146376EDENTON
Solar/Wind Harmer
0.385
316065AD1-022 GEN
Solar/Wind Harmer
3.744
958261AF2-120 GEN
Solar/Wind Harmer
2.666
3145893MURPHYS
Solar/Wind Harmer
0.538
3145893MURPHYS
Solar/Wind Harmer
0.145
3146173TUNIS
Solar/Wind Harmer
0.079
3146173TUNIS
Solar/Wind Harmer
0.079
3142666NORTHAMPTON
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.046
316181AB2-040 GEN
Solar/Wind Harmer
0.11
316426AA2-053 GEN
Solar/Wind Harmer
0.255
3145796HORNRTN
Solar/Wind Harmer
0.224
3145593CAROLNA
Solar/Wind Harmer
0.075
3145593CAROLNA
Solar/Wind Harmer
0.075
966811AG1-552 GEN
Solar/Wind Harmer
0.811
3145593CAROLNA
Solar/Wind Harmer
0.093
3145783HORNRTN
Solar/Wind Harmer
1.321
3145783HORNRTN
Solar/Wind Harmer
1.057
3145783HORNRTN
Solar/Wind Harmer
0.33
3145783HORNRTN
Solar/Wind Harmer
0.132
3145933PARMELE
Solar/Wind Harmer
0.146
3145933PARMELE
Solar/Wind Harmer
0.073
316077AC2-138 C
Solar/Wind Harmer
0
3150341NORNECKC1
Adder
0.759
3150341NORNECKC1
Adder
0.753
316274AC1-208 GEN
Solar/Wind Harmer
0.373
972185AH1-677 GEN
Adder
3.992
972187AH1-678 GEN
Adder
2.007
970933AG2-581 GEN
Solar/Wind Harmer
5.576
3145493TOT1
Solar/Wind Harmer
0.158
3145453TOT5
Solar/Wind Harmer
0.095
3145603CNETO
Solar/Wind Harmer
0.063
961601AG1-000A GEN
Solar/Wind Harmer
1.182
316263AC1-034 GEN
Solar/Wind Harmer
2.524
970099AG2-077 GEN
Solar/Wind Harmer
7.081
939181AE1-148 GEN
Solar/Wind Harmer
3.089
313527AB2-043 GEN
Solar/Wind Harmer
0.001
971741AH1-377 GEN
Solar/Wind Harmer
6.257
316034AC1-036 C
Solar/Wind Harmer
0.005
970323AG2-213 GEN
Solar/Wind Harmer
2.676
971775AH1-396 GEN
Solar/Wind Harmer
0.1
970301AG2-198 GEN
Solar/Wind Harmer
2.661
958211AF2-115 GEN
Solar/Wind Harmer
0.743
963191AG1-168 GEN
Solar/Wind Harmer
0.248
3144293JTRSVLE
Adder
0.197
3144293JTRSVLE
Adder
0.166
3147133PAMPLIN
Solar/Wind Harmer
0.062
3147133PAMPLIN
Solar/Wind Harmer
0.049
962561AG1-105 GEN
Solar/Wind Harmer
2.907
964791AG1-342 GEN
Solar/Wind Harmer
1.152
3146843MT LREL
Solar/Wind Harmer
0.06
3146843MT LREL
Solar/Wind Harmer
0.06
3146776BUCKING
Solar/Wind Harmer
0.231
3146776BUCKING
Solar/Wind Harmer
0.019
LAGNLTFEXP_LAGN->PJM
CLTF
3.259
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.253
TVALTFEXP_TVA->PJM
CLTF
1.654
NYPJM->LTFIMP_NY
CLTF
1.306
LGEELTFEXP_LGEE->PJM
CLTF
0.633
WECLTFEXP_WEC->PJM
CLTF
0.314
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.836
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.715
MECLTFEXP_MEC->PJM
CLTF
1.658
SIGELTFEXP_SIGE->PJM
CLTF
0.051
CPLELTFEXP_CPLE->PJM
CLTF
4.134
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.574

Details for AF1-114 TP-6DAHLGREN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AF1-114 TP-6DAHLGREN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.84 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:679.2
MW Contribution:7.19
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
2.956
966661AG1-536 GEN
50/50
6.849
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
971353AH1-157 GEN
50/50
7.408
970017AG2-010 GEN
50/50
4.699
3150641CHESTS8
50/50
0.203
944631AF1-128 GEN
50/50
31.925
972135AH1-637 GEN
Solar/Wind Harmer
4.389
316337AD2-073 GEN
Solar/Wind Harmer
0.299
3141726DUNNSVL
Solar/Wind Harmer
1.044
315759AF1-018 GEN
50/50
4.946
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150611CHESTG7
50/50
0.401
3150631CHESTG8
50/50
0.394
971047AG2-646 GEN
50/50
11.221
972263AH1-716 GEN
50/50
32.871
944491AF1-114 GEN
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Harmer
0.296
3141813NORNECK
Solar/Wind Harmer
0.279
970327AG2-215 GEN
Solar/Wind Harmer
7.194
962981AG1-147 GEN
Solar/Wind Harmer
7.685
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.051
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
0.029
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.081
3150351NORNECKC2
50/50
3.006
970575AG2-366 GEN
50/50
3.66
315749AE2-041 GEN
50/50
4.946
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150921YORKTN3
50/50
1.929
3144216WINCHST
50/50
0.279
3151161SURRY 1
50/50
2.166
970737AG2-469 GEN
Solar/Wind Harmer
20.178
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.637
962971AG1-146 GEN
Solar/Wind Harmer
3.294
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.61
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.855
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.668
3142416OLDCHRC
Solar/Wind Harmer
0.555
3151221GRAVEL6
Adder
4.099
3151171GRAVELC
Adder
0.789
962861AG1-135 GEN
Solar/Wind Harmer
7.523
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
971317AH1-138 GEN
Solar/Wind Harmer
0.613
316159AE1-175 C
Solar/Wind Harmer
0.065
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3142416OLDCHRC
Solar/Wind Harmer
0.149
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.6
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
9.122
315976AC1-164 GENA
Solar/Wind Harmer
8.292
316169AC1-164_GENC
Solar/Wind Harmer
7.163
315975AC1-164 GENB
Solar/Wind Harmer
0.245
316312AB1-027
Solar/Wind Harmer
0.102
972265AH1-717 GEN
Adder
4.377
3151201GRAVEL4
Adder
4.104
3151191GRAVEL3
Adder
4.052
3151211GRAVEL5
Adder
4.052
3141426STAFORD
Solar/Wind Helper
0.031
3150341NORNECKC1
50/50
3.105
3150341NORNECKC1
50/50
3.08
963611AG1-210 GEN
50/50
0.994
3150621CHESTS7
50/50
0.184
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
7.962
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.007
LAGNLTFEXP_LAGN->PJM
CLTF
1.483
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.388
TVALTFEXP_TVA->PJM
CLTF
0.749
NYPJM->LTFIMP_NY
CLTF
0.564
LGEELTFEXP_LGEE->PJM
CLTF
0.274
WECLTFEXP_WEC->PJM
CLTF
0.137
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.711
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.577
MECLTFEXP_MEC->PJM
CLTF
0.732
SIGELTFEXP_SIGE->PJM
CLTF
0.022
CPLELTFEXP_CPLE->PJM
CLTF
1.997
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.895

Details for AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.21 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:711.49
MW Contribution:7.19
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
4.946
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150611CHESTG7
50/50
0.401
3150631CHESTG8
50/50
0.394
971047AG2-646 GEN
50/50
11.221
972263AH1-716 GEN
50/50
32.871
944491AF1-114 GEN
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Harmer
0.296
3141813NORNECK
Solar/Wind Harmer
0.279
970327AG2-215 GEN
Solar/Wind Harmer
7.194
962981AG1-147 GEN
Solar/Wind Harmer
7.685
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.051
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
0.029
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.081
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
9.122
315976AC1-164 GENA
Solar/Wind Harmer
8.292
316169AC1-164_GENC
Solar/Wind Harmer
7.163
315975AC1-164 GENB
Solar/Wind Harmer
0.245
316312AB1-027
Solar/Wind Harmer
0.102
972265AH1-717 GEN
Adder
4.377
3151201GRAVEL4
Adder
4.104
3151191GRAVEL3
Adder
4.052
3151211GRAVEL5
Adder
4.052
3141426STAFORD
Solar/Wind Helper
0.031
3150351NORNECKC2
50/50
3.006
970575AG2-366 GEN
50/50
3.66
315749AE2-041 GEN
50/50
4.946
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150921YORKTN3
50/50
1.929
3144216WINCHST
50/50
0.279
3151161SURRY 1
50/50
2.166
970737AG2-469 GEN
Solar/Wind Harmer
20.178
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.637
962971AG1-146 GEN
Solar/Wind Harmer
3.294
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.61
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.855
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.668
3142416OLDCHRC
Solar/Wind Harmer
0.555
3151221GRAVEL6
Adder
4.099
3151171GRAVELC
Adder
0.789
957191AF2-013 GEN
50/50
65.713
3150341NORNECKC1
50/50
3.105
3150341NORNECKC1
50/50
3.08
963611AG1-210 GEN
50/50
0.994
3150621CHESTS7
50/50
0.184
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
7.962
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.007
3150351NORNECKC2
50/50
2.956
966661AG1-536 GEN
50/50
6.849
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
971353AH1-157 GEN
50/50
7.408
970017AG2-010 GEN
50/50
4.699
3150641CHESTS8
50/50
0.203
944631AF1-128 GEN
50/50
31.925
972135AH1-637 GEN
Solar/Wind Harmer
4.389
316337AD2-073 GEN
Solar/Wind Harmer
0.299
3141726DUNNSVL
Solar/Wind Harmer
1.044
962861AG1-135 GEN
Solar/Wind Harmer
7.523
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
971317AH1-138 GEN
Solar/Wind Harmer
0.613
316159AE1-175 C
Solar/Wind Harmer
0.065
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3142416OLDCHRC
Solar/Wind Harmer
0.149
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.6
LAGNLTFEXP_LAGN->PJM
CLTF
1.483
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.388
TVALTFEXP_TVA->PJM
CLTF
0.749
NYPJM->LTFIMP_NY
CLTF
0.564
LGEELTFEXP_LGEE->PJM
CLTF
0.274
WECLTFEXP_WEC->PJM
CLTF
0.137
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.711
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.577
MECLTFEXP_MEC->PJM
CLTF
0.732
SIGELTFEXP_SIGE->PJM
CLTF
0.022
CPLELTFEXP_CPLE->PJM
CLTF
1.997
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.895

Details for AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.1 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:604.6
MW Contribution:7.23
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
4.976
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
972263AH1-716 GEN
50/50
35.649
3150611CHESTG7
50/50
0.379
3150631CHESTG8
50/50
0.372
971047AG2-646 GEN
50/50
10.599
944491AF1-114 GEN
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Harmer
0.297
3141813NORNECK
Solar/Wind Harmer
0.28
970327AG2-215 GEN
Solar/Wind Harmer
7.232
962981AG1-147 GEN
Solar/Wind Harmer
7.729
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.074
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.168
3141873WAN 176
Solar/Wind Harmer
0.03
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.097
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
8.942
315976AC1-164 GENA
Solar/Wind Harmer
8.275
316169AC1-164_GENC
Solar/Wind Harmer
7.149
315975AC1-164 GENB
Solar/Wind Harmer
0.245
972265AH1-717 GEN
Adder
4.429
3151201GRAVEL4
Adder
4.152
3151191GRAVEL3
Adder
4.099
3151211GRAVEL5
Adder
4.099
3141426STAFORD
Solar/Wind Helper
0.029
3150351NORNECKC2
50/50
3.02
970575AG2-366 GEN
50/50
3.68
315749AE2-041 GEN
50/50
4.976
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
3150921YORKTN3
50/50
2.003
3144216WINCHST
50/50
0.289
3151161SURRY 1
50/50
2.191
970737AG2-469 GEN
Solar/Wind Harmer
20.26
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.646
962971AG1-146 GEN
Solar/Wind Harmer
3.312
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.629
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.866
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.022
3151221GRAVEL6
Adder
4.147
3151171GRAVELC
Adder
0.798
970293AG2-193 GEN
Solar/Wind Harmer
0.603
957191AF2-013 GEN
50/50
65.968
3150341NORNECKC1
50/50
3.119
3150341NORNECKC1
50/50
3.094
963611AG1-210 GEN
50/50
0.998
3150621CHESTS7
50/50
0.174
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
8.003
316075AC2-137 C
Solar/Wind Harmer
0.018
3142946ENON
Solar/Wind Harmer
0.007
3150351NORNECKC2
50/50
2.97
966661AG1-536 GEN
50/50
6.884
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
971353AH1-157 GEN
50/50
7.642
970017AG2-010 GEN
50/50
4.875
3150641CHESTS8
50/50
0.192
944631AF1-128 GEN
50/50
30.156
3152331SURRY 2
50/50
2.455
972135AH1-637 GEN
Solar/Wind Harmer
4.407
316337AD2-073 GEN
Solar/Wind Harmer
0.3
3141726DUNNSVL
Solar/Wind Harmer
1.049
962861AG1-135 GEN
Solar/Wind Harmer
7.561
3138133OCRAN
Solar/Wind Harmer
0.104
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.365
3142433PROV 92
Solar/Wind Harmer
0.422
971317AH1-138 GEN
Solar/Wind Harmer
0.633
316159AE1-175 C
Solar/Wind Harmer
0.067
3138126ROCKLANDING
Solar/Wind Harmer
0.034
3151171GRAVELC
Adder
0.607
LAGNLTFEXP_LAGN->PJM
CLTF
1.213
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.047
TVALTFEXP_TVA->PJM
CLTF
0.609
NYPJM->LTFIMP_NY
CLTF
0.465
LGEELTFEXP_LGEE->PJM
CLTF
0.185
WECLTFEXP_WEC->PJM
CLTF
0.092
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.061
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.057
MECLTFEXP_MEC->PJM
CLTF
0.525
SIGELTFEXP_SIGE->PJM
CLTF
0.016
CPLELTFEXP_CPLE->PJM
CLTF
1.912
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.152

Details for AG1-135 TP-3GARNER 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
AG1-135 TP-3GARNER 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 65_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.34 %
Rating:203.98 MVA
Rating Type:B
MVA to Mitigate:235.27
MW Contribution:36.91
Bus #Bus NameTypeMW Contribution
962981AG1-147 GEN
Solar/Wind Harmer
41.983
970327AG2-215 GEN
Solar/Wind Harmer
36.905
970575AG2-366 GEN
50/50
19.992
962971AG1-146 GEN
Solar/Wind Harmer
17.993
970009AG2-005 GEN
Solar/Wind Harmer
8.397
962861AG1-135 GEN
Solar/Wind Harmer
35.985
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.023
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.07
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.022
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.023
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.014
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.105
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1059_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1059_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:174.07 %
Rating:203.98 MVA
Rating Type:B
MVA to Mitigate:355.06
MW Contribution:36.89
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
31.973
962861AG1-135 GEN
Solar/Wind Harmer
35.969
958261AF2-120 GEN
Solar/Wind Harmer
37.168
962981AG1-147 GEN
Solar/Wind Harmer
41.964
970327AG2-215 GEN
Solar/Wind Harmer
36.888
970575AG2-366 GEN
50/50
19.983
316404AE1-155 C
Solar/Wind Harmer
0.253
962971AG1-146 GEN
Solar/Wind Harmer
17.985
970009AG2-005 GEN
Solar/Wind Harmer
8.393
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.048
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.148
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.047
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.049
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.03
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.221
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65_SRT-A-4


Base Case Flowgate

Area:DVP
Facility Description:
AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 65_SRT-A-4
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.08 %
Rating:203.98 MVA
Rating Type:B
MVA to Mitigate:232.7
MW Contribution:36.91
Bus #Bus NameTypeMW Contribution
962981AG1-147 GEN
Solar/Wind Harmer
41.983
970327AG2-215 GEN
Solar/Wind Harmer
36.905
962861AG1-135 GEN
Solar/Wind Harmer
35.985
970575AG2-366 GEN
50/50
19.992
962971AG1-146 GEN
Solar/Wind Harmer
17.993
970009AG2-005 GEN
Solar/Wind Harmer
8.397
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.023
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.07
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.022
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.023
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.014
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.105
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AG2-469 TP-6OAKGROV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-469 TP-6OAKGROV 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.13 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:657.97
MW Contribution:7.21
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
4.959
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150611CHESTG7
50/50
0.403
3150631CHESTG8
50/50
0.397
971047AG2-646 GEN
50/50
11.288
972263AH1-716 GEN
50/50
33.088
316223AC1-118
Solar/Wind Harmer
0.296
3141813NORNECK
Solar/Wind Harmer
0.28
970327AG2-215 GEN
Solar/Wind Harmer
7.206
962981AG1-147 GEN
Solar/Wind Harmer
7.699
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
0.029
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.092
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
9.155
315976AC1-164 GENA
Solar/Wind Harmer
8.33
316169AC1-164_GENC
Solar/Wind Harmer
7.197
315975AC1-164 GENB
Solar/Wind Harmer
0.246
316312AB1-027
Solar/Wind Harmer
0.103
972265AH1-717 GEN
Adder
4.406
3151201GRAVEL4
Adder
4.131
3151191GRAVEL3
Adder
4.078
3151211GRAVEL5
Adder
4.078
316369SG1_INVT
Solar/Wind Harmer
0.002
3141426STAFORD
Solar/Wind Helper
0.031
3150351NORNECKC2
50/50
2.96
966661AG1-536 GEN
50/50
6.86
3141843SHACKLE
50/50
0.748
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
971353AH1-157 GEN
50/50
7.442
970017AG2-010 GEN
50/50
4.725
3150641CHESTS8
50/50
0.204
944631AF1-128 GEN
50/50
32.114
316337AD2-073 GEN
Solar/Wind Harmer
0.299
3141726DUNNSVL
Solar/Wind Harmer
1.045
962861AG1-135 GEN
Solar/Wind Harmer
7.535
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.364
3142433PROV 92
Solar/Wind Harmer
0.43
971317AH1-138 GEN
Solar/Wind Harmer
0.616
316159AE1-175 C
Solar/Wind Harmer
0.065
3138126ROCKLANDING
Solar/Wind Harmer
0.033
3142416OLDCHRC
Solar/Wind Harmer
0.15
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.604
961611AG1-000B GEN
Solar/Wind Harmer
2.967
971647AH1-324 GEN
Solar/Wind Harmer
2.407
3150351NORNECKC2
50/50
3.01
970575AG2-366 GEN
50/50
3.666
315749AE2-041 GEN
50/50
4.959
3141843SHACKLE
50/50
0.748
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150921YORKTN3
50/50
1.939
3144216WINCHST
50/50
0.281
3151161SURRY 1
50/50
2.18
970737AG2-469 GEN
Solar/Wind Harmer
20.194
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.64
962971AG1-146 GEN
Solar/Wind Harmer
3.3
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.617
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.86
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.672
3142416OLDCHRC
Solar/Wind Harmer
0.558
3151221GRAVEL6
Adder
4.126
3151171GRAVELC
Adder
0.794
961611AG1-000B GEN
Solar/Wind Harmer
1.508
3150341NORNECKC1
50/50
3.109
3150341NORNECKC1
50/50
3.084
963611AG1-210 GEN
50/50
0.995
3150621CHESTS7
50/50
0.185
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
7.975
316075AC2-137 C
Solar/Wind Harmer
0.02
3142946ENON
Solar/Wind Harmer
0.007
316033AB2-134 GEN
Solar/Wind Harmer
0.003
315697AD1-025 GEN
Solar/Wind Harmer
0.063
LAGNLTFEXP_LAGN->PJM
CLTF
1.541
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.475
TVALTFEXP_TVA->PJM
CLTF
0.778
NYPJM->LTFIMP_NY
CLTF
0.546
LGEELTFEXP_LGEE->PJM
CLTF
0.294
WECLTFEXP_WEC->PJM
CLTF
0.148
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.13
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.686
MECLTFEXP_MEC->PJM
CLTF
0.78
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CPLELTFEXP_CPLE->PJM
CLTF
2.028
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.282
CONTINGENCY 'DVP_P1-2: LN 65_SRT-A-1'
 OPEN BRANCH FROM BUS 313813 TO BUS 314178 CKT 1   /*3OCRAN       115.0 - 3LANCAST     115.0
 OPEN BRANCH FROM BUS 313813 TO BUS 314191 CKT 1   /*3OCRAN       115.0 - 3WHIT STONE  115.0
 OPEN BRANCH FROM BUS 313870 TO BUS 314191 CKT 1   /*3RAPPAHNCK   115.0 - 3WHIT STONE  115.0
 OPEN BRANCH FROM BUS 314178 TO BUS 314400 CKT 1   /*3LANCAST     115.0 - 3LANCA_1     115.0
 OPEN BRANCH FROM BUS 962970 TO BUS 314178 CKT 1   /*AG1-146 TP   115.0 - 3LANCAST     115.0
 OPEN BUS 313813                                   /*3OCRAN       115.0
 OPEN BUS 314178                                   /*3LANCAST     115.0
 OPEN BUS 314191                                   /*3WHIT STONE  115.0
 OPEN BUS 314400                                   /*3LANCA_1     115.0
END
CONTINGENCY 'DVP_P1-2: LN 1059_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
CONTINGENCY 'DVP_P1-3: 6NORNECK-TX#6_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 2   /*3NORNECK     115.0 - 6NORNECK     230.0
END
CONTINGENCY 'DVP_P1-3: 6NORNECK-TX#4_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 1   /*3NORNECK     115.0 - 6NORNECK     230.0
END
CONTINGENCY 'DVP_P1-2: LN 2157_SRT-A'
 OPEN BRANCH FROM BUS 314134 TO BUS 314137 CKT 1   /*6CRANES      230.0 - 6FREDBRG     230.0
END
CONTINGENCY 'DVP_P1-2: LN 2104_SRT-A'
 OPEN BRANCH FROM BUS 313421 TO BUS 314134 CKT 1   /*6SPARTAN     230.0 - 6CRANES      230.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 567_SRT-A'
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 9296_SRT-A'
 OPEN BRANCH FROM BUS 314137 TO BUS 314145 CKT 1   /*6FREDBRG     230.0 - 6AQUI_HARB_B 230.0
END
CONTINGENCY 'DVP_P1-2: LN 2119_SRT-A'
 OPEN BRANCH FROM BUS 314140 TO BUS 314145 CKT 1   /*6GARSVL      230.0 - 6AQUI_HARB_B 230.0
END
CONTINGENCY 'PEPCO_P1_5070_SRT-A'
 OPEN BRANCH FROM BUS 200019 TO BUS 314922 CKT 1   /*BURCHES      500.0 - 8POSSUM      500.0
END
CONTINGENCY 'AP_P1-2_PE-500-406T_SRT-A'
 DISCONNECT BRANCH FROM BUS 200003 TO BUS 235105 CKT 1   /*BRIGHTON     500.0 - 01DOUBS      500.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-S'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 9344_SRT-A'
 OPEN BRANCH FROM BUS 313393 TO BUS 313905 CKT 1   /*8MARS        500.0 - 8WSHNGSTAR   500.0
END
CONTINGENCY 'DVP_P1-2: LN 594_SRT-S'
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 573_SRT-S'
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1                /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
END
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2913 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 1021_SRT-A'
 OPEN BRANCH FROM BUS 313842 TO BUS 313870 CKT Z1   /*3RAPPAHNCK_1 115.0 - 3RAPPAHNCK   115.0
 OPEN BRANCH FROM BUS 313843 TO BUS 313870 CKT Z1   /*3RAPPAHNCK_2 115.0 - 3RAPPAHNCK   115.0
 OPEN BRANCH FROM BUS 313870 TO BUS 313900 CKT Z1   /*3RAPPAHNCK   115.0 - 3RAPP TR     115.0
 OPEN BRANCH FROM BUS 313886 TO BUS 313900 CKT 1    /*3GREYSPT     115.0 - 3RAPP TR     115.0
 OPEN BRANCH FROM BUS 313886 TO BUS 313900 CKT 2    /*3GREYSPT     115.0 - 3RAPP TR     115.0
 OPEN BRANCH FROM BUS 313886 TO BUS 314174 CKT 1    /*3GREYSPT     115.0 - 3HARMONY     115.0
 OPEN BUS 313842                                    /*3RAPPAHNCK_1 115.0
 OPEN BUS 313843                                    /*3RAPPAHNCK_2 115.0
 OPEN BUS 313886                                    /*3GREYSPT     115.0
 OPEN BUS 313900                                    /*3RAPP TR     115.0
END
CONTINGENCY 'DVP_P1-2: LN 65_SRT-A-4'
 OPEN BRANCH FROM BUS 314173 TO BUS 962860 CKT 1   /*3GARNER      115.0 - AG1-135 TP   115.0
 OPEN BRANCH FROM BUS 316399 TO BUS 314173 CKT 1   /*AE1-155 TAP  115.0 - 3GARNER      115.0
 OPEN BUS 314173                                   /*3GARNER      115.0
END
314173 to 316399 ckt 1
313886 to 314174 ckt 1
314178 to 313813 ckt 1
314181 to 314182 ckt 1
314181 to 314182 ckt 2
313813 to 314191 ckt 1
313900 to 313886 ckt 1
313900 to 313886 ckt 2
314145 to 314140 ckt 1
314131 to 314175 ckt 1
314132 to 314163 ckt 1
314214 to 314258 ckt 1
314214 to 314903 ckt 1
314286 to 314309 ckt 1
314175 to 314132 ckt 1
314134 to 313421 ckt 1
314290 to 223938 ckt 1
314218 to 314222 ckt 1
314218 to 314908 ckt 1
314218 to 314908 ckt 2
314163 to 314137 ckt 1
314212 to 314150 ckt 1
314137 to 314134 ckt 1
314140 to 314144 ckt 1
314222 to 314212 ckt 1
314309 to 314338 ckt 1
314322 to 314914 ckt 1
314182 to 314183 ckt 1
314236 to 314218 ckt 1
314139 to 944490 ckt 1
314183 to 314190 ckt 1
313421 to 314142 ckt 1
314150 to 315672 ckt 1
313911 to 314290 ckt 1
314190 to 970736 ckt 1
314933 to 972284 ckt 1
314902 to 314914 ckt 1
314905 to 314900 ckt 1
314903 to 314908 ckt 1
314908 to 314911 ckt 1
314911 to 314905 ckt 1
314911 to 314922 ckt 1
314914 to 314918 ckt 1
314918 to 314934 ckt 1
314922 to 200019 ckt 1
314934 to 314916 ckt 1
316479 to 962970 ckt 1
316399 to 314181 ckt 1
315672 to 314197 ckt 1
944490 to 313810 ckt 1
957190 to 314131 ckt 1
962860 to 314173 ckt 1
962970 to 314178 ckt 1
970736 to 314139 ckt 1

Winter Peak Analysis

The New Service Request AG2-215 was evaluated as a 0.0 MW (36.92 MW Capacity) injection in the Dominion area.

AG2-215 was evaluated as part of a plant. The plant consists of AG2-215, AG2-005. The total Energy output of the plant was evaluated at its maximum seasonal capability of 196.0 MW (20.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Light Load Analysis

The New Service Request AG2-215 was evaluated as a 0.0 MW injection

AG2-215 was evaluated as part of a plant. The plant consists of AG2-215, AG2-005. The total Energy output of the plant was evaluated at its maximum seasonal capability of 196.0 MW (20.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability Analysis is Not Required.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-038Lexington-Low Moor 230kVUnder Construction
AA1-050Tarboro-Everetts 230kVIn Service
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-067Everetts 34.5kVIn Service
AA1-095Halfway-Marlowe 34.5kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA1-145Four Rivers 230kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-057Hornertown-Whitakers 115kVIn Service
AA2-174Carolina-Jackson 115kVIn Service
AA2-178Mackeys 230kVIn Service
AA2-184Atlantic-Red Bank 34kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-096Carroll-Mt. Airy 34.5kVIn Service
AB1-124Carroll-Monocacy 34.5kVPartially in Service - Under Construction
AB1-125Carroll-Monocacy 34.5kVIn Service
AB1-127St. Thomas-Guilford 34.5kVIn Service
AB1-128St. Thomas-Mercersburg 34.5kVIn Service
AB1-132Thelma 230kVIn Service
AB1-138Navy 34.5kVIn Service
AB1-139Metuchen 26kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB2-022Elizabeth City 34.5kVIn Service
AB2-024Correctional 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-031Brink-Trego 115kVIn Service
AB2-032Church-Wye Mills 138 kVIn Service
AB2-037Keeney-Steele 230kVUnder Construction
AB2-040Brink 115kVIn Service
AB2-043Chase City 115kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-049Gloucester Township 12kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-134Hopewell-Surry 230kVIn Service
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVUnder Construction
AB2-153Church-Wye Mills 138 kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-169Pantago-Five Points 115kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AB2-179Townsend 138kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-010Gloucester 26kVUnder Construction
AC1-017Levittown 13 kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVSuspended
AC1-036Twittys Creek 34.5kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-086Thelma 230kVSuspended
AC1-091Cedar Creek 138kV IEngineering & Procurement
AC1-092Cedar Creek 138kV IIEngineering & Procurement
AC1-093Cedar Creek 138kV IIIEngineering & Procurement
AC1-094Cedar Creek 138kV IVEngineering & Procurement
AC1-098Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-099Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-191Elmont 115kVEngineering & Procurement
AC1-208Cox-Whitakers 115kVUnder Construction
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-023Hebron 69kVEngineering & Procurement
AC2-079Ivor-Oak Ridge 115kVSuspended
AC2-100Halifax-Person 230kVIn Service
AC2-120Ripley 69kVIn Service
AC2-136East Hagerstown 12kVUnder Construction
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-165Bremo-Powhatan 230kVSuspended
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AD1-017Smith Mountain-Bearskin 138 kVIn Service
AD1-020Hunterstown-Lincoln 115 kVIn Service
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVUnder Construction
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-060Mercersburg-Milnor 34.5 kVIn Service
AD1-061McConnelsburg-Mercersburg 34 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-088Briery-Clover 230 kVSuspended
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-144Kings Fork 34.5 kVIn Service
AD1-151Hopewell-Surry 230 kVSuspended
AD1-152Clover-Sedge Hill 230 kVIn Service
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-009McConnellsburg 138 kVIn Service
AD2-027Camden Switch 26 kVIn Service
AD2-030Wan 34.5 kVIn Service
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-042Camden Switch 26 kV IIIn Service
AD2-058St. Barnabas 13 kVIn Service
AD2-065Atco 12 kVIn Service
AD2-070Gilbert-Morris Park 34.5kVIn Service
AD2-073Sanders DP 230 kVIn Service
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-115Lyons-Moselem 69kVIn Service
AD2-116Hokes-Grantley 69 kVIn Service
AD2-135Williamstown 12kVPartially in Service - Under Construction
AD2-160Hickory-Moyock 230kVIn Service
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-041Edison 4kVIn Service
AE1-056Red House-South Creek 115 kVWithdrawn
AE1-071Shade Gap-Roxbury 115 kVIn Service
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-081Landing 12.47 kVIn Service
AE1-100Axton 138 kVIn Service
AE1-101McConnellsburg-Texas Eastern 138 kVIn Service
AE1-103Holland-Union Camp 115 kVUnder Construction
AE1-108Bremo-Scottsville 138 kVEngineering & Procurement
AE1-142Manitou-Pleasant Plains 34.5 kVIn Service
AE1-148Kerr Dam-Ridge Rd 115 kVActive
AE1-149Disputanta-Poe 115 kVSuspended
AE1-153Remington-Gordonsville 230 kVSuspended
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-156Quakertown Solar II 34.5 kVPartially in Service - Under Construction
AE1-157Ladysmith CT-St. Johns 230 kVSuspended
AE1-162Smithfield 34.5 kVIn Service
AE1-173Carson-Suffolk 500 kVUnder Construction
AE1-175Light Foot 34.5 kVIn Service
AE1-185Hokes-Jackson 69 kVIn Service
AE1-190Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-191Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-196Hokes-Jackson 69 kV IIIn Service
AE1-229Deepwater-Upper Pittsgrove 138 kVSuspended
AE1-250Smith Mountain-E. Danville 138 kVEngineering & Procurement
AE2-005Harmony Village-Shackleford 115 kVUnder Construction
AE2-019New Road 230 kVUnder Construction
AE2-027Harrowgate-Locks 115kVUnder Construction
AE2-033Clubhouse-Sapony 230 kVSuspended
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-040Sapony 34.5 kVPartially in Service - Under Construction
AE2-041Harmony Village 230 kVEngineering & Procurement
AE2-042Milton 69 kVIn Service
AE2-047Ridgeway-Solite 69 kVEngineering & Procurement
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-054Warfordsburg 34 kVIn Service
AE2-059Derry Tap-Derry Bus 69 kVIn Service
AE2-060Mifflintown Bus-Mifflintown Tap 69 kVIn Service
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-094Carson-Rogers Road 500 kVEngineering & Procurement
AE2-104Suffolk 115 kVSuspended
AE2-133Penns Tap-Richfield Tie 69 kVIn Service
AE2-140Axton-Danville 138 kVSuspended
AE2-156Yadkin 115 kVActive
AE2-166Stockton 138 kVSuspended
AE2-175Jackson-Long Pond 69 kVPartially in Service - Under Construction
AE2-183Rogers Road 500 kVIn Service
AE2-185Gladys DP-Stonemill Switching Station 69 kVActive
AE2-187Shockoe DP-Chatham 69 kVActive
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-253Hickory-Moyock 230 kVIn Service
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVActive
AE2-291Grit DP-Perth 115 kVActive
AE2-346Ahoskie 34.5 kVIn Service
AF1-007Indian River 230 kV ISuspended
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-018Harmony Village 230 kVEngineering & Procurement
AF1-032Suffolk 34.5 kVIn Service
AF1-049Berry Hill 138 kVUnder Construction
AF1-058Welco 34.5 kVIn Service
AF1-069Carson-Rogers Rd 500 kVEngineering & Procurement
AF1-075Harrisburg-Endless Caverns 230 kVSuspended
AF1-114Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF1-123Harper 230 kVActive
AF1-124Harper 230 kVActive
AF1-125Harper 230 kVActive
AF1-128Chesterfield 230 kVActive
AF1-129Chesterfield 230 kVEngineering & Procurement
AF1-136Warfordsburg-Purcell Junction 34.5 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVUnder Construction
AF1-254Milnor-Huyetts 34.5 kVUnder Construction
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF1-290Feagans Mill-Millville 138 kVIn Service
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-294Jetersville-Ponton 115 kVActive
AF1-299Otter Point 34.5 kV IIn Service
AF1-300Otter Point 34.5 kV IIIn Service
AF1-320Merrill Creek 115 kVEngineering & Procurement
AF1-333Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-337Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-338Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-339Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF2-013Arnold's Corner-Dahlgren 230 kVEngineering & Procurement
AF2-035St. Johns 115 kVActive
AF2-042Clover-Rawlings 500 kVActive
AF2-043Suffolk 34.5 kVIn Service
AF2-046Tunis-Mapleton 115 kVActive
AF2-080Chinquapin-Everetts 230 kVActive
AF2-081Moyock 230 kVActive
AF2-085Midlothian 34.5 kVIn Service
AF2-086Scott Tap-Bowmans Mill Tap 69 kVEngineering & Procurement
AF2-107Clifford 138 kVEngineering & Procurement
AF2-110Suffolk 115 kVSuspended
AF2-115Jetersville-Ponton 115 kVActive
AF2-120Garner-Northern Neck 115 kVActive
AF2-138Flanders-West Wharton 34.5 kVIn Service
AF2-139Gilbert-Warren Glen 34.5 kVIn Service
AF2-144Powhatan 34.5 kVIn Service
AF2-192Frenchtown Solar-West Flemington 34.5 kVSuspended
AF2-222Madisonville DP-Twitty's Creek 115 kVActive
AF2-229Roxbury 23 kVEngineering & Procurement
AF2-233Penns-Richfield Tie #1 69 kVEngineering & Procurement
AF2-234Sunbury Yard #1-Richfield Tie #2 69 kVEngineering & Procurement
AF2-247Bustleton 13.2 kVIn Service
AF2-250Edgewood 12 kV IIIIn Service
AF2-297Sedge Hill 115 kVActive
AF2-299Fields 34.5 kVActive
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-354Washington 34.5 kV IIEngineering & Procurement
AF2-361Mifflintown Tap 69 kVEngineering & Procurement
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AF2-383Tolna 115 kVWithdrawn
AF2-417West Damascus Tap-West Damascus 69 kVEngineering & Procurement
AF2-421East Hazelton-Weatherly Tap 69Engineering & Procurement
AF2-424Reed-Reed Tap #1 69 kVEngineering & Procurement
AF2-425Reed-Reed Tap#1 69 kVEngineering & Procurement
AF2-433Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AF2-434Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AG1-007Tar River 12.5 kVEngineering & Procurement
AG1-008Tunis-Mapleton 115 kVActive
AG1-021Jetersville-Ponton 115 kVActive
AG1-082Ahoskie 34.5 kVActive
AG1-098Briery-Clover 230 kVActive
AG1-105Mount Laurel-Barnes Junction 115 kVActive
AG1-106Thelma 230 kVActive
AG1-124Gladstone 138 kVActive
AG1-135Garner-Lancaster 115 kVActive
AG1-145Lightfoot 34.5 kVIn Service
AG1-146Garner DP-Lancaster 115 kVActive
AG1-147Garner DP-Lancaster 115 kVActive
AG1-153Heritage 500 kVActive
AG1-154Ladysmith CT 230 kVActive
AG1-156Jack Frost-Lake Harmony 69 kVEngineering & Procurement
AG1-164East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-165East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-166Lone Pine 115 kVActive
AG1-167Lone Pine 115 kVActive
AG1-168Lone Pine 115 kVActive
AG1-188Manitou-Oyster Creek 34.5 kVEngineering & Procurement
AG1-189Oyster Creek-Bamber Lake 34.5Engineering & Procurement
AG1-191Chester-Pohatcong Mountain 34.5 kVPartially in Service - Under Construction
AG1-210Northern Neck 34.5 kVEngineering & Procurement
AG1-221Poland Rd-Runway DP 230 kVUnder Construction
AG1-223Larrabee-Allaire 34.5 kVUnder Construction
AG1-254Salem-Woodstown 69 kVEngineering & Procurement
AG1-259Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-260Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-285Chase City-Central 115 kVActive
AG1-342Dryburg 115 kVActive
AG1-348Pequest River-Washington 34.5 kVIn Service
AG1-393Sapony 34.5 kVActive
AG1-394Boykins 34.5 kVActive
AG1-397Walston 12 kVWithdrawn
AG1-469Gordonsville 34.5 kVEngineering & Procurement
AG1-480Shawnee 34.5 kVEngineering & Procurement
AG1-482Hamilton 115 kVWithdrawn
AG1-495Gilbert-Rocktown 34.5 kVEngineering & Procurement
AG1-499Lambs 12.47 kVUnder Construction
AG1-536Garner-Northern Neck 115 kVActive
AG1-551Parmele 34.5 kVActive
AG1-552Carolina 34.5 kVActive
AG1-558Buckner 34.5 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
AG2-005Garner DP-Lancaster 115 kVActive
AG2-010Peninsula-Whealton 115 kVActive
AG2-049Van Dorn 34.5 kVActive
AG2-068Heritage - Wake 500 kVActive
AG2-069Heritage - Wake 500 kVActive
AG2-077Clover-Rawlings 500 kVActive
AG2-086Mt. Jackson DP-Mt. Jackson 115 kVActive
AG2-088Midlothian 230 kVActive
AG2-093Colonial Trail-Hopewell 230 kVActive
AG2-095Hopewell 34.5 kV (Circuit 313)Active
AG2-111Perth 34.5 kV Substation (Circuit 408)Active
AG2-112Perth 34.5 kV Substation (Circuit 404)Active
AG2-120Everetts 34.5 kVActive
AG2-124Shackleford-Harmony 115 kVActive
AG2-151Trices Lake - James River Tap 115 kVActive
AG2-152Banister-Bear Skin 138 kVActive
AG2-171Lunenburg-Nutbush 115 kVActive
AG2-188Farmville - Buckingham 230 kVActive
AG2-193Turner 34.5 kVActive
AG2-198Briery - Finneywood 230 kVActive
AG2-208Greenwood DP - St. Johns DP 115 kVActive
AG2-213Gary D.P Tap - Gary D.P 115 kVActive
AG2-262Dryburg 115 kVActive
AG2-270Clover 230 kVActive
AG2-304Liberty 230 kVActive
AG2-320Ladysmith 230 kVActive
AG2-338Rogers Road - Carson 500 kVActive
AG2-339Rogers Road - Carson 500 kVActive
AG2-366Garner Delivery Point - Lancaster 115 kVActive
AG2-369Heritage - Wake 500 kVActive
AG2-382Cashie 230 kVActive
AG2-384Chesterfield 230 kVActive
AG2-426Wakefield - Waverly 115 kVActive
AG2-427Waverly 115 kVActive
AG2-428Wakefield 115 kVActive
AG2-436Carson - Rogers Road 500 kVActive
AG2-440Twittys Creek - Madisonville 115 kVActive
AG2-441Twittys Creek - Madisonville 115 kVActive
AG2-442Twittys Creek - Madisonville 115 kVActive
AG2-469Westmoreland – Oak Grove 230 kVActive
AG2-522Five Forks DP 115 kVActive
AG2-541Perth - Crystal Hill 115 kVActive
AG2-566Briery - Finneywood 230 kVActive
AG2-570Heritage - Wake 500 kVActive
AG2-571Heritage - Wake 500 kVActive
AG2-581Rawlings-Clover 500 kVActive
AG2-583Bremo - Cartersville 230 kVActive
AG2-646Chesterfield 230 kVActive
AG2-659Kerr Dam – Hawtree 115 kVActive
AG2-661Hopewell - Colonial Trail 230 kVActive
AH1-012Louisa - North Anna 230 kVActive
AH1-033Sligo 34.5 kVActive
AH1-035Plymouth 34.5 kVActive
AH1-040Mackeys - Creswell 115 kVActive
AH1-042Providence Forge-Turner 115kVActive
AH1-056Red House DP 115kVActive
AH1-065Hopewell 34.5kVActive
AH1-066Hopewell 34.5kVActive
AH1-071Midlothian 34.5 kVActive
AH1-086Morrisville 230kVActive
AH1-087Morrisville 230kVActive
AH1-088Morrisville 230kVActive
AH1-089Morrisville 230kVActive
AH1-106Winterpock 34.5kVActive
AH1-107Winterpock 34.5kVActive
AH1-108Spruance NUG 230 kVActive
AH1-138Penniman 34.5 kVActive
AH1-157Penniman - Waller 230 kVActive
AH1-164Oak Level - Tank Hill 138 kVActive
AH1-170Columbia DP 115kVActive
AH1-215Central VA-Twitty 115 kVActive
AH1-216Smithfield-Surry 230 kVActive
AH1-217Kidds Store - Fork Union 115 kV IIActive
AH1-221Heritage 500 kVActive
AH1-223Poland Rd-Runway DP 230 kVActive
AH1-241Cobbs Creek - James River Industrial 115kVActive
AH1-251Todds Tavern- Spotsylvania/Goldsdale 115kVActive
AH1-263Chancellor 115 kVActive
AH1-271Cashie 230 kVActive
AH1-280Jetersville-Ponton 115 kVActive
AH1-311Heartsease DP - Mayo Dunbar 115kVActive
AH1-323Elmont 230 kVActive
AH1-324Colonial Trail – Surry 230 kVActive
AH1-343Crystal Hill DP- Perth 115kVActive
AH1-345Remington 324 34.5 kVActive
AH1-377Clover- Farmville 230kVActive
AH1-387Meadowbrook-Greenland Gap 500kVActive
AH1-396Gary 24.94 kVActive
AH1-397Shacklesford 34.5 kVActive
AH1-399North Doswell 12.5 kVActive
AH1-408Freeman DP – Lawrenceville 115 kVActive
AH1-439Buckingham- Farmville 230kVActive
AH1-528Rawlings - Unity 500 kVActive
AH1-546Bremo - Buckingham 230 kVActive
AH1-637Oak Grove 34.5 kVActive
AH1-676Gordonsville 230 kVActive
AH1-677Rogers Road 500 kVActive
AH1-678Heritage 500 kVActive
AH1-679Four Rivers 230 kVActive
AH1-681Cunningham 500 kVActive
AH1-682Ladysmith CT 230 kVActive
AH1-683Ladysmith CT 230 kVActive
AH1-684Remington CT 230 kVActive
AH1-685Remington CT 230 kVActive
AH1-687Bear Garden 230kVActive
AH1-691Ladysmith CT 230 kVActive
AH1-692Ladysmith CT 230 kVActive
AH1-693Remington CT 230 kVActive
AH1-694Ladysmith CT 230 kVActive
AH1-696Possum Point 230kVActive
AH1-712Cunningham 500 kVActive
AH1-716Surry-Skiffes Creek 500kVActive
AH1-717Surry 230kVActive
AH1-723Cunningham 500 kVActive
AH1-727Brambleton-Goose Creek 500kVActive
AH1-729Ocean Court 230 kVActive
V4-067Cates Road Egg Harbor Township 12kVDeactivated
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
W3-077Broadway-Stewartsville 34.5kVIn Service
X3-066Church Hill 69kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y1-086Morgans CornerIn Service
Y3-058Rockawalkin 69kVIn Service
Z1-036WinFall-Chowan 230kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-044Whitakers 34.5kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase I analysis results, this project may have a cost responsibility for the following System Reinforcements:

AG2-215 System Reinforcements:
TORTEP IDTitleAllocated Cost ($USD)
Dominion(Pending) / TC2-PH1-DOM-2074Rebuild underground line from Harmony Village to Greyspoint and operating the line at 230 kV.$19,059,373
Dominionn7556 / dom-461-TC2Reconductor 3.53 miles of 115 kV Line 65 from AD2-074 Tap to AG1-146 Tap with (1) 768.2 ACSS/TW (20/70) ""Maumee"" conductor @ 250 degrees C$11,550,348
Dominion(Pending) / TC2-PH1-DOM-2049Wreck and rebuild 5.86 mi of 115 kV line 65 from Lancaster to AG1-146 with (2) 768.2 ACSS/TW (20/7) "Maumee" conductor @ 250 degrees C. and replace 636 ACSR and 1534 ACAR Jumper.$6,918,781
Dominion(Pending) / TC2-PH1-DOM-2048Wreck and rebuild 2.97 mi of 115 kV line 65 from Ocran to Lancaster with (2) 768.2 ACSS/TW (20/7) "Maumee" conductor @ 250 degrees C.$3,930,500
Dominionn7576 / dom-281-TC2Rebuild 7.91 miles of 230 kV Line 2083 from Birchwood to Fines with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"" conductor 250 degrees C.$2,376,443
Dominionn7575 / dom-286-TC2Rebuild 6.46 mi miles of 2-545.6 ACAR (15/7) 90 MOT 230 kV Line 2083 from Fredericksburg to Fines with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"" conductor @ 250 degrees C.$2,231,729
Dominion(Pending) / TC2-PH1-DOM-2045Wreck and rebuild 1.33 miles of 115 kV Line 65 between White Stone and Ocran with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C$1,760,093
Dominion(Pending) / TC2-PH1-DOM-1007Wreck and rebuild 0.87 miles of 230 kV Line 2083 between Fredericksburg to Fines with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 Deg. C.$219,850
Grand Total:$48,047,117

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2074
Title
Rebuild underground line from Harmony Village to Greyspoint and operating the line at 230 kV.
Description
Wreck and rebuild existing line 1021, Harmony Village to Greyspoint transition station, as a 230 kV line using (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Expand Harmony Village 230 kV to accommodate the new 230 kV line and associated breaker. Operate the existing underground portion of line 1021 as a 230 kV circuit. Build a new 230 kV station at Rappahannock and connect the existing underground cable, two new reactors and associated breakers and two new 224 MVA 115/230 kV transformers to tie into the existing 115 kV bus at Rappahannock. All 230 kV substation terminal equipment to be rated at 4000 Amps.
Total Cost ($USD)
$53,000,000
Allocated Cost ($USD)
$19,059,373
Time Estimate
48 to 60 Months

Contributor

FacilityContingency
3GREYSPT-3HARMONY 115.0 kV Ckt 1 line(Any)
3GREYSPT-3RAPP TR 115.0 kV Ckt 1 line(Any)
3GREYSPT-3RAPP TR 115.0 kV Ckt 2 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-005
31.6 MW15.4%$8,156,529
AG2-215
73.8 MW36.0%$19,059,373
AG2-366
99.8 MW48.6%$25,784,098

System Reinforcement: n7556
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7556 / dom-461-TC2
Title
Reconductor 3.53 miles of 115 kV Line 65 from AD2-074 Tap to AG1-146 Tap with (1) 768.2 ACSS/TW (20/70) ""Maumee"" conductor @ 250 degrees C
Description
Reconductor 3.53 miles of 115 kV Line 65 from AD2-074 Tap to AG1-146 Tap with (1) 768.2 ACSS/TW (20/70) ""Maumee"" conductor @ 250 degrees C
Total Cost ($USD)
$16,493,251
Allocated Cost ($USD)
$11,550,348
Time Estimate
43 to 44 Months

Contributor

FacilityContingency
AD2-074 TAP-AG1-146 TP 115.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-005
15.8 MW30.0%$4,942,903
AG2-215
36.9 MW70.0%$11,550,348

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2049
Title
Wreck and rebuild 5.86 mi of 115 kV line 65 from Lancaster to AG1-146 with (2) 768.2 ACSS/TW (20/7) "Maumee" conductor @ 250 degrees C. and replace 636 ACSR and 1534 ACAR Jumper.
Description
Wreck and rebuild 5.86 mi of 115 kV line 65 from Lancaster to AG1-146 with (2) 768.2 ACSS/TW (20/7) "Maumee" conductor @ 250 degrees C. and replace 636 ACSR and 1534 ACAR Jumper.
Total Cost ($USD)
$21,569,800
Allocated Cost ($USD)
$6,918,781
Time Estimate
30 to 36 Months

Contributor

FacilityContingency
3LANCAST-AG1-146 TP 115.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-005
15.8 MW13.7%$2,960,851
AG2-215
36.9 MW32.1%$6,918,781
AG2-366
49.9 MW43.4%$9,359,524
AG2-469
12.4 MW10.8%$2,330,644

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2048
Title
Wreck and rebuild 2.97 mi of 115 kV line 65 from Ocran to Lancaster with (2) 768.2 ACSS/TW (20/7) "Maumee" conductor @ 250 degrees C.
Description
Wreck and rebuild 2.97 mi of 115 kV line 65 from Ocran to Lancaster with (2) 768.2 ACSS/TW (20/7) "Maumee" conductor @ 250 degrees C.
Total Cost ($USD)
$10,929,600
Allocated Cost ($USD)
$3,930,500
Time Estimate
30 to 36 Months

Contributor

FacilityContingency
3OCRAN-3LANCAST 115.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-005
15.8 MW15.4%$1,682,034
AG2-215
36.9 MW36.0%$3,930,500
AG2-366
49.9 MW48.6%$5,317,065

System Reinforcement: n7576
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7576 / dom-281-TC2
Title
Rebuild 7.91 miles of 230 kV Line 2083 from Birchwood to Fines with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"" conductor 250 degrees C.
Description
Rebuild 7.91 miles of 230 kV Line 2083 from Birchwood to Fines with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"" conductor 250 degrees C.
Total Cost ($USD)
$35,735,843
Allocated Cost ($USD)
$2,376,443
Time Estimate
43 to 44 Months

Contributor

FacilityContingency
6BIRCHWD-6FINES 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-005
1.6 MW1.5%$540,761
AG2-215
7.2 MW6.7%$2,376,443
AG2-366
9.1 MW8.5%$3,020,931
AG2-469
26.8 MW24.8%$8,868,884
AG2-646
11.2 MW10.4%$3,706,710
AH1-042
11.7 MW10.8%$3,876,834
AH1-157
7.5 MW7.0%$2,486,776
AH1-716
32.9 MW30.4%$10,858,503

System Reinforcement: n7575
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7575 / dom-286-TC2
Title
Rebuild 6.46 mi miles of 2-545.6 ACAR (15/7) 90 MOT 230 kV Line 2083 from Fredericksburg to Fines with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"" conductor @ 250 degrees C.
Description
Rebuild 6.46 mi miles of 2-545.6 ACAR (15/7) 90 MOT 230 kV Line 2083 from Fredericksburg to Fines with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"" conductor @ 250 degrees C.
Total Cost ($USD)
$33,559,690
Allocated Cost ($USD)
$2,231,729
Time Estimate
43 to 44 Months

Contributor

FacilityContingency
6FREDBRG-6FINES 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-005
1.6 MW1.5%$507,832
AG2-215
7.2 MW6.7%$2,231,729
AG2-366
9.1 MW8.5%$2,836,970
AG2-469
26.8 MW24.8%$8,328,809
AG2-646
11.2 MW10.4%$3,480,988
AH1-042
11.7 MW10.8%$3,640,752
AH1-157
7.5 MW7.0%$2,335,342
AH1-716
32.9 MW30.4%$10,197,269

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2045
Title
Wreck and rebuild 1.33 miles of 115 kV Line 65 between White Stone and Ocran with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C
Description
Wreck and rebuild 1.33 miles of 115 kV Line 65 between White Stone and Ocran with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C
Total Cost ($USD)
$4,894,400
Allocated Cost ($USD)
$1,760,093
Time Estimate
30 to 36 Months

Contributor

FacilityContingency
3OCRAN-3WHIT STONE 115.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-005
15.8 MW15.4%$753,242
AG2-215
36.9 MW36.0%$1,760,093
AG2-366
49.9 MW48.6%$2,381,066

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-1007
Title
Wreck and rebuild 0.87 miles of 230 kV Line 2083 between Fredericksburg to Fines with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 Deg. C.
Description
Wreck and rebuild 0.87 miles of 230 kV Line 2083 between Fredericksburg to Fines with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 Deg. C.
Total Cost ($USD)
$3,306,000
Allocated Cost ($USD)
$219,850
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6FREDBRG-6FINES 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-005
1.6 MW1.5%$50,027
AG2-215
7.2 MW6.7%$219,850
AG2-366
9.1 MW8.5%$279,473
AG2-469
26.8 MW24.8%$820,480
AG2-646
11.2 MW10.4%$342,916
AH1-042
11.7 MW10.8%$358,654
AH1-157
7.5 MW7.0%$230,057
AH1-716
32.9 MW30.4%$1,004,544

System Reinforcement: n9145.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9145.0 / TC1-PH1-DOM-008
Title
Reconductor 0.11 miles of 115 kV line between Garner DP and Moon Corner with single (1) 768.2 aluminum conductor steel supported trapezoidal shaped aluminum strands ("ACSS/TW") (20/7).
Description
Reconductor 0.11 miles of 115 kV line 65 between Garner DP and Moon Corner with single (1) 768.2 aluminum conductor steel supported trapezoidal shaped aluminum strands (ACSS/TW) (20/7) "Maumee" conductor @ 250 degrees C.
Total Cost ($USD)
$2,096,619
Allocated Cost ($USD)
$0
Time Estimate
18 to 19 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 may need this upgrade in-service to be deliverable to the PJM system. If AG2-215 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
3GARNER-AE1-155 TAP 115.0 kV Ckt 1 line(Any)

System Reinforcement: n9136.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9136.0 / TC1-PH1-DOM-066
Title
Wreck and rebuild 1.32 miles of 115 kV line from Garner to AG1-135 with 768.2 aluminum conductor steel supported trapezoidal shaped aluminum strands ("ACSS/TW") (20/7). Replace line lead at Garner DP.
Description
Wreck and rebuild 1.32 miles of 115 kV line 65 between Garner and AG1-135 with one (1) 768.2 aluminum conductor steel supported trapezoidal shaped aluminum strands (ACSS/TW) (20/7) "MAUMEE" conductor @ 250 degrees C. Replace line lead at Garner DP substation.
Total Cost ($USD)
$8,145,385
Allocated Cost ($USD)
$0
Time Estimate
42 to 43 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 may need this upgrade in-service to be deliverable to the PJM system. If AG2-215 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
3GARNER-AG1-135 TP 115.0 kV Ckt 1 line(Any)

System Reinforcement: n7549
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7549 / dom-428
Title
Replace Northern Neck 115/230 kV transformer #4 with a 224 MVA (260/271/295 MVA).
Description
Replace Northern Neck 115/230 kV transformer #4 with a 224 MVA (260/271/295 MVA).
Total Cost ($USD)
$7,324,554
Allocated Cost ($USD)
$0
Time Estimate
59 to 60 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 may need this upgrade in-service to be deliverable to the PJM system. If AG2-215 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer(Any)

System Reinforcement: n7553
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7553 / dom-427
Title
Replace Northern Neck 115/230 kV transformer #6 with a 224 MVA (260/271/295 MVA).
Description
Replace Northern Neck 115/230 kV transformer #6 with a 224 MVA (260/271/295 MVA).
Total Cost ($USD)
$7,242,347
Allocated Cost ($USD)
$0
Time Estimate
59 to 60 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 may need this upgrade in-service to be deliverable to the PJM system. If AG2-215 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer(Any)

System Reinforcement: n9651.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9651.0 / TC1-PH2-DOM-009
Title
Wreck and rebuild 10.05 miles of 115 kV Line 1059 between Northern Neck and Moon Corner with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 Deg. C.
Description
Wreck and rebuild 10.05 miles of 115 kV Line 1059 between Northern Neck and Moon Corner with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 Deg. C.
Total Cost ($USD)
$28,476,954
Allocated Cost ($USD)
$0
Time Estimate
Mar 31 2029

Contingent

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 may need this upgrade in-service to be deliverable to the PJM system. If AG2-215 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
3NORNECK-AE1-155 TAP 115.0 kV Ckt 1 line(Any)

System Reinforcement: n9652.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9652.0 / TC1-PH2-DOM-010
Title
Replace Wave Trap at Northern Neck for increased rating of Line 1059 between Northern Neck and Moon Corner
Description
Replace Wave Trap at Northern Neck for increased rating of Line 1059 between Northern Neck and Moon Corner
Total Cost ($USD)
$1,065,776
Allocated Cost ($USD)
$0
Time Estimate
Mar 01 2027

Contingent

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 may need this upgrade in-service to be deliverable to the PJM system. If AG2-215 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
3NORNECK-AE1-155 TAP 115.0 kV Ckt 1 line(Any)

System Reinforcement: n9653.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9653.0 / TC1-PH2-DOM-011
Title
Replace Line Switch at Northern Neck for increased rating of Line 1059 between Northern Neck and Moon Corner
Description
Replace Line Switch at Northern Neck for increased rating of Line 1059 between Northern Neck and Moon Corner
Total Cost ($USD)
$454,326
Allocated Cost ($USD)
$0
Time Estimate
Mar 01 2027

Contingent

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 may need this upgrade in-service to be deliverable to the PJM system. If AG2-215 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
3NORNECK-AE1-155 TAP 115.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0043
Title
Wreck and rebuild 3.62 miles of 230 kV Line 2091 between Chickahominy and Elko with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 3.62 miles of 230 kV Line 2091 between Chickahominy and Elko with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$13,756,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 is a potential Aggregate Pool Contributor.

FacilityContingency
6CHCKAHM-6ELKO 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9261.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9261.0 / TC1-PH2-DOM-060
Title
Replace Existing Chickahominy XFRM 1 with 3-480 MVA Single Phase XFRM.
Description
Replace Existing Chickahominy XFRM 1 with 3-480 MVA Single Phase XFRM.
Total Cost ($USD)
$40,000,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 is a potential Aggregate Pool Contributor.

FacilityContingency
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer(Any)

System Reinforcement: n6551
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n6551 / dom-159
Title
Wreck and rebuild 7.32 miles of 230 kV Line 208 between Chesterfield and Ironbridge with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 7.32 miles of 230 kV Line 208 between Chesterfield and Ironbridge with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$27,816,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 is a potential Aggregate Pool Contributor.

FacilityContingency
6CHESTF A-6IRON208 230.0 kV Ckt 1 line(Any)

System Reinforcement: n7685
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7685 / dom-283-TC2
Title
Rebuild 4.56 miles of 230 kV Line 2157 from Fredericksburg to Cranes Corner with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"" conductor at 250 C and replace Line Lead at Cranes Corner.
Description
Rebuild 4.56 miles of 230 kV Line 2157 from Fredericksburg to Cranes Corner with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 C and replace Line Lead at Cranes Corner.
Total Cost ($USD)
$15,674,813
Allocated Cost ($USD)
$0
Time Estimate
43 to 44 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 is a potential Aggregate Pool Contributor.

FacilityContingency
6CRANES-6FREDBRG 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0049
Title
Wreck and rebuild 12.98 miles of 230 kV Line 283 between Elmont and Northeast with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees
Description
Wreck and rebuild 12.98 miles of 230 kV Line 283 between Elmont and Northeast with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees
Total Cost ($USD)
$49,324,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 is a potential Aggregate Pool Contributor.

FacilityContingency
6ELMONT-6NRTHEST 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2090
Title
Add a 3rd new 3-480 MVA 230/500 kV Transformer at Elmont substation. Add one (1) 500 kV breaker and one (1) 230 kV breaker as required for the new transformer
Description
Add a 3rd new 3-480 MVA 230/500 kV Transformer at Elmont substation. Add one (1) 500 kV breaker and one (1) 230 kV breaker as required for the new transformer
Total Cost ($USD)
$40,000,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 is a potential Aggregate Pool Contributor.

FacilityContingency
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 1 transformer(Any)
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2004
Title
Replace 2-1590 AAC 61 line lead on line 2032 at Four Rivers 230 kV.
Description
Replace 2-1590 AAC 61 line lead on line 2032 at Four Rivers 230 kV.
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 is a potential Aggregate Pool Contributor.

FacilityContingency
6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2005
Title
Wreck and rebuild 5.74 mi of 230 kV Line 230 between Four Rivers and Hanover with (2) 768.2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C
Description
Wreck and rebuild 5.74 mi of 230 kV Line 230 between Four Rivers and Hanover with (2) 768.2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C
Total Cost ($USD)
$21,812,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 is a potential Aggregate Pool Contributor.

FacilityContingency
6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-1013
Title
Re-conductor 5.8 mi of 230 kV underground cable 2120 from Garrisonville to Aquia Harbor with 2-5000 kcmil CU.
Description
Re-conductor 5.8 mi of 230 kV underground cable 2120 from Garrisonville to Aquia Harbor with 2-5000 kcmil CU.
Total Cost ($USD)
$116,000,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 is a potential Aggregate Pool Contributor.

FacilityContingency
6GARSVL-6AQUI_HARB_A 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9256.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9256.0 / TC1-PH2-DOM-049
Title
Re-conductor 5.8 mi of 230 kV underground cable 2119 from Garrisonville to Aquia Harbor with 2-5000 kcmil CU.
Description
Re-conductor 5.8 mi of 230 kV underground cable 2119 from Garrisonville to Aquia Harbor with 2-5000 kcmil CU.
Total Cost ($USD)
$116,000,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 is a potential Aggregate Pool Contributor.

FacilityContingency
6GARSVL-6AQUI_HARB_B 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / dom-164
Title
Wreck and rebuild 7.08 miles of 230 kV Line 208 between Ironbridge and Southwest with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 7.08 miles of 230 kV Line 208 between Ironbridge and Southwest with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$26,904,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 is a potential Aggregate Pool Contributor.

FacilityContingency
6IRON208-6SOUWEST 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9379.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9379.0 / TC1-PH3-DOM-011
Title
Replace existing 230/500 kV Transformer 1 at Midlothian with (4)-480 MVA Single Phase transformers.
Description
Replace existing 230/500 kV Transformer 1 at Midlothian with (4)-480 MVA Single Phase 500/230 kV transformers.
Total Cost ($USD)
$37,836,293
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2029

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 is a potential Aggregate Pool Contributor.

FacilityContingency
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer(Any)

System Reinforcement: b3694.4
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3694.4
Title
Reconductor/rebuild approx 7.6 miles of 230 kV line #2104 Cranes Corner-Stafford. Reconductor/rebuild approx 0.34 miles of 230 kV line #2104 Stafford-Aquia Harbor. Upgrade terminal equipment.
Description
Reconductor/rebuild approximately 7.6 miles of 230 kV line #2104 Cranes Corner-Stafford to achieve a summer rating of 1047 MVA(1). Reconductor/rebuild approximately 0.34 miles of 230 kV line #2104 Stafford-Aquia Harbor to achieve a summer rating of 1047 MVA. Upgrade terminal equipment at Cranes Corner to not limit the new conductor rating.
Cost Information
Time Estimate
Apr 17 2026

Not Contingent

Note: AG2-215 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-215 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6SPARTAN-6CRANES 230.0 kV Ckt 1 line(Any)
6SPARTAN-6STAFORD 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.355
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-215 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-215 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-215 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-215 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AG2-215 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-215 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-215 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-215 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AG2-215 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-215 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-215 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-215 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-215 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-215 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-215 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-215 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-215 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-215 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AG2-215 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-215 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-215 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-215 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-215 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-215 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-215 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-215 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-215 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-215 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AG2-215 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-215 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AG2-215 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-215 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6STJOHN-6FOUR RIVERS 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6ELMONT-6HANOVER 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6ELMONT-8ELMONT 230.0/500.0 kV Ckt 2 transformer(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6STJOHN-AE1-157 TAP 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6LDYSMITH CT-AE1-157 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.343
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.343
Title
Uprate bus at Brambleton to support 500kV Line #558 (Aspen to Brambleton) uprate.
Description
Uprate bus at Brambleton to support 500kV Line #558 (Aspen to Brambleton) uprate.
Cost Information
Time Estimate
Nov 28 2025

Not Contingent

Note: AG2-215 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-215 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8BRAMBLETON-AH1-727 TP 500.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-1036
Title
Wreck and rebuild 37.41 mi of 500 kV line 563 between Carson and Midlothian with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN" at 145 degrees C
Description
Wreck and rebuild 37.41 mi of 500 kV line 563 between Carson and Midlothian with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN" at 145 degrees C
Total Cost ($USD)
$157,122,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 is a potential Aggregate Pool Contributor.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: n9139.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9139.0 / TC1-PH1-DOM-073
Title
Wreck and rebuild 37.41 miles of 500kV line 563 between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" and associated substation work.
Description
Wreck and rebuild 37.41 miles of 500kV transmission line 563 between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA. Remove wave traps.
Total Cost ($USD)
$245,455,768
Allocated Cost ($USD)
$0
Time Estimate
69 to 70 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 is a potential Aggregate Pool Contributor.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S

System Reinforcement: n9249.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9249.0 / TC1-PH2-DOM-043
Title
Construct new 37.26 mile line between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C. Station upgrades at Midlothian and Carson to accommodate new line.
Description
Construct new 37.26 mile line between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C. Station upgrades at Midlothian and Carson to accommodate new line. New Rating = 4356/4356/5009 MVA
Total Cost ($USD)
$231,012,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 is a potential Aggregate Pool Contributor.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S

System Reinforcement: b3692
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3692
Title
Rebuild approximately 27.7-miles of 500 kV transmission line from Elmont to Chickahominy.
Description
Rebuild approximately 27.7-miles of 500 kV transmission line from Elmont to Chickahominy with current 500 kV standards construction practices to achieve a summer rating of 4330 MVA. Projected ISD: 06/01/2026
Cost Information
Time Estimate
Jun 01 2026

Not Contingent

Note: AG2-215 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-215 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line(Any)

System Reinforcement: n9248.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9248.0 / TC1-PH2-DOM-042
Title
Construct new 41.13 mile line between North Anna and Midlothian with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN" at 145 degrees C. Station upgrades at North Anna and Midlothian to accommodate new line.
Description
Construct new 41.13 mile line between North Anna and Midlothian with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN" at 145 degrees C. Station upgrades at North Anna and Midlothian to accommodate new line.
Total Cost ($USD)
$345,766,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 is a potential Aggregate Pool Contributor.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: WT576_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: 57602_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P1-2: LN 576_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P4-2: 557T574_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P1-2: LN 557_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S

System Reinforcement: n9191.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9191.0 / TC1-PH1-DOM-090
Title
Rebuild 41.13 miles of line 576 between North Anna and Midlothian with triple bundled (3) 1351.5 ACSR (45/7) "Dipper" conductor and associated substation work.
Description
Rebuild 41.13 miles of line 576 between North Anna and Midlothian with triple bundled (3) 1351.5 ACSR (45/7) "Dipper" conductor at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA.
Total Cost ($USD)
$256,706,175
Allocated Cost ($USD)
$0
Time Estimate
74 to 75 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 is a potential Aggregate Pool Contributor.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P1-2: LN 576_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: WT576_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: 57602_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0075
Title
Wreck and rebuild 18.75 miles of 500 kV Line 594 between Spotsylvania and Morrisville with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN"
Description
Wreck and rebuild 18.75 miles of 500 kV Line 594 between Spotsylvania and Morrisville with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN"
Total Cost ($USD)
$110,625,000
Allocated Cost ($USD)
$0
Time Estimate
18 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 is a potential Aggregate Pool Contributor.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P2-2: MORRISVILLE B1_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P4-2: 545T552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P4-2: H1T552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P4-2: H3T552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 550_SRT-A

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0076
Title
Replace Wave Trap 594WT at Morrisville 500 KV
Description
Replace Wave Trap 594WT at Morrisville 500 KV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$0
Time Estimate
16 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 is a potential Aggregate Pool Contributor.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0077
Title
Replace Wave Trap 594WT at Spotsylvania 500 KV
Description
Replace Wave Trap 594WT at Spotsylvania 500 KV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$0
Time Estimate
16 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 is a potential Aggregate Pool Contributor.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0078
Title
Replace 3-1590 AAC 61 line lead on Line 594 at Morrisville 500 kV
Description
Replace 3-1590 AAC 61 line lead on Line 594 at Morrisville 500 kV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 is a potential Aggregate Pool Contributor.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0071
Title
Wreck and rebuild 14.02 miles of 500 kV Line 573 between Spotsylvania and North Anna with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN".
Description
Wreck and rebuild 14.02 miles of 500 kV Line 573 between Spotsylvania and North Anna with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN".
Total Cost ($USD)
$82,718,000
Allocated Cost ($USD)
$0
Time Estimate
18 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 is a potential Aggregate Pool Contributor.

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0072
Title
Replace 2-2500 ACAR 84/7 line lead on Line 573 at North Anna 500 kV
Description
Replace 2-2500 ACAR 84/7 line lead on Line 573 at North Anna 500 kV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 is a potential Aggregate Pool Contributor.

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0073
Title
Replace Wave Trap 573WT at Spotsylvania 500 KV
Description
Replace Wave Trap 573WT at Spotsylvania 500 KV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$0
Time Estimate
16 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 is a potential Aggregate Pool Contributor.

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending)
Title
No overload on Dominion equipment for 8POSSUM - BURCHES (TC2)
Description
Dominion End Ratings Winter: 5414/5581/6107 Light Load: 5227/5388/5941 Summer: 4257/4388/5046
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
BURCHES-8POSSUM 500.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
(Pending) / (Pending)
Title
TC2 Upgrade for BURCHES 500.0 kV to 8POSSUM 500.0 kV ckt 1
Description
Replaces the terminal equipment at Burches Hill 500 kV station (breakers, switches, and stranded bus) that upgrades the ratings.
Total Cost ($USD)
$6,000,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 is a potential Aggregate Pool Contributor.

FacilityContingency
BURCHES-8POSSUM 500.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2097
Title
Build a new 11.95 mile line from Aspen 230 kV to Dickerson 230 kV with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 degrees C.
Description
Build a new 11.95 mile line from Aspen 230 kV to Dickerson 230 kV with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 degrees C.
Total Cost ($USD)
$33,230,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 is a potential Aggregate Pool Contributor.

FacilityContingency
DICKH230-6EDFERRY 230.0 kV Ckt 1 lineAP_P2-3_PE-500-019F_SRT-SL
DICKH230-6EDFERRY 230.0 kV Ckt 1 lineAP_P2-3_PE-500-019B_SRT-A
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
DICKH230-6EDFERRY 230.0 kV Ckt 1 linePEPCO_P1_5070_SRT-A
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 linePEPCO_P1_5070_SRT-A
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 lineAP_P2-3_PE-500-019B_SRT-A
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 lineAP_P2-3_PE-500-019F_SRT-SL
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 lineAP_P1-2_PE-500-406T_SRT-A

System Reinforcement: b3800.242
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.242
Title
Upgrading switches 20366M and 20369M and line leads to 4000A continuous current rating of 230kV Line #203 at Edwards Ferry substation
Description
Upgrading switches 20366M and 20369M and line leads to 4000A continuous current rating of 230kV Line #203 at Edwards Ferry substation
Cost Information
Time Estimate
Sep 13 2030

Not Contingent

Note: AG2-215 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-215 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.244
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b3800.244
Title
Rebuild 7.26 miles of existing 230 kV circuit from Dickerson Station H to Ed's Ferry area to accommodate the new 500 kV circuit between Doubs and Aspen. (The 230kV portion of the project)
Description
Rebuild 7.26 miles of existing 230 kV circuit from Dickerson Station H to Ed's Ferry area to accommodate the new 500 kV circuit between Doubs and Aspen. (The 230kV portion of the project)
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AG2-215 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-215 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
(Pending) / (Pending)
Title
Additional Aspen to Dickerson H 230 kV line
Description
PEPCO’s substation cost to accommodate an additional circuit at Dickerson H to be approximately $7.86 million. The cost for the remaining 7.25 miles of 230 kV transmission line is estimated at $78.62 million.
Total Cost ($USD)
$86,480,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-215 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-215 could receive cost allocation. Although AG2-215 may not presently have cost responsibility for this upgrade, AG2-215 is a potential Aggregate Pool Contributor.

FacilityContingency
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
          AD2-074 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-005, AG2-215
        

Attachments

AG2-215 One Line Diagram

AG2-215 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.