AG2-270 Phase I Study Report

v1.00 released 2025-10-29 22:02

Clover 230 kV

105.0 MW Capacity / 150.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Clover Storage, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed a Storage facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — Halifax County, Virginia. The installed facilities will have a total capability of 150.0 MW with 105.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-270
Project Name:
Clover 230 kV
Project Developer Name:
Clover Storage, LLC
State:
Virginia
County:
Halifax
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
150.0
MWE:
150.0
MWC:
105.0
Battery Storage Specification:
600.0 MWh, 4.0-hr class
Grid Charging:
Yes
Fuel Type:
Storage
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AG2-270 will interconnect on the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) transmission system at the Clover 230 kV Substation.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AG2-270 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-270Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$3,500,000$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$14,500,000$14,500,000
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$38,189,600$38,189,600
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$56,189,600$52,689,600

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AG2-270

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AG2-270 Project due at DP1
ABA - B
AG2-270$5,268,960$600,000$4,668,960

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Interconnection Facilities
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Install the Point of Change in Ownership (PCO) disconnect switch, the overhead line conductor from the PCO to the bus position that serves as the Point of Interconnection (POI), as well as any metering and associated protection equipment.$3,500,000 $3,500,000
Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Extend the existing Clover 230 kV Substation by adding two (2) breakers at a detached station. Additional substation modification/expansion cost may be required after detailed design.$14,500,000 $14,500,000

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 46 to 50 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2028 load flow model and the results were verified by Dominion.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-270 was evaluated as a 150.0 MW (105.0 MW Capacity) injection in the Dominion area.

AG2-270 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 150.0 MW (150.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC203.13 %678.68B1378.610.91
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC185.6 %830.0C1540.510.89
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC185.6 %830.0C1540.4910.89
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-3
SingleAC158.61 %678.68B1076.489.66
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Base Case
SingleAC113.92 %678.68A773.168.8
GD2DVP
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC117.42 %800.88B940.379.55
GD2DVP
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC117.01 %800.88B937.129.55
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC202.03 %678.68B1371.1710.91
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC184.71 %830.0C1533.1110.89
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC184.71 %830.0C1533.110.89
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-3
SingleAC157.52 %678.68B1069.039.66
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Base Case
SingleAC112.86 %678.68A765.978.8
GD2DVP
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC131.81 %571.52B753.2929.36
GD2DVP
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC129.23 %571.52B738.5829.36
GD2DVP
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC129.16 %699.0C902.8529.41
GD2DVP
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC129.12 %699.0C902.5629.41
GD2DVP
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC125.93 %699.0C880.2229.36
GD2DVP
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC119.97 %699.0C838.6129.36
GD2DVP
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC119.97 %699.0C838.6129.36
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC212.98 %699.0C1488.7629.95
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC212.93 %699.0C1488.3729.95
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC209.35 %699.0C1463.3729.89
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC207.29 %571.52B1184.729.89
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC204.76 %571.52B1170.2729.89
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC203.45 %699.0C1422.1129.89
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC203.45 %699.0C1422.1129.89
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC130.37 %699.0C911.2912.88
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P7-1: LN 2106-2111_SRT-A
TowerAC130.23 %699.0C910.3312.39
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P7-1: LN 2003-205_SRT-S
TowerAC126.86 %699.0C886.7312.71
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
BusAC118.39 %699.0C827.5212.56
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Base Case
SingleAC112.79 %571.52A644.6112.47
GD2DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC154.83 %1204.0C1864.1611.15
GD2DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC145.18 %984.18B1428.848.81
GD2DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P1-2: LN 2002_SRT-A
SingleAC121.21 %984.18B1192.966.97
GD2DVP
6CARSON-6POE 230.0 kV Ckt 1 line
DVP_P1-2: LN 249_SRT-A
SingleAC124.58 %678.68B845.485.5
GD2DVP
6CARSON-6POE 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC116.29 %678.68B789.265.63
GD2DVP
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC119.72 %800.88B958.859.55
GD2DVP
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC119.32 %800.88B955.69.55
GD2DVP
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC152.97 %1204.0C1841.811.15
GD2DVP
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC142.99 %984.18B1407.248.81
GD2DVP
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
DVP_P1-2: LN 2002_SRT-A
SingleAC119.0 %984.18B1171.166.97
GD2DVP
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC131.7 %678.68B893.856.8
GD2DVP
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC131.06 %678.68B889.456.8
GD2DVP
6EDMONSON-6SEDGE HILL 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC103.9 %997.0C1035.956.8
GD2DVP
6EDMONSON-6SEDGE HILL 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC102.06 %997.0C1017.5856.73
GD2DVP
6EDMONSON-6SEDGE HILL 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC102.05 %997.0C1017.4156.73
GD2DVP
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC141.24 %678.68B958.546.8
GD2DVP
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC140.59 %678.68B954.156.8
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC201.24 %684.0C1376.5129.97
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC201.19 %684.0C1376.1329.97
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC197.56 %684.0C1351.3429.9
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC195.93 %559.3B1095.8629.9
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC193.37 %559.3B1081.5129.9
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC191.54 %684.0C1310.1229.9
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC191.54 %684.0C1310.1229.9
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P7-1: LN 2106-2111_SRT-A
TowerAC119.01 %684.0C814.0512.4
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC118.81 %684.0C812.6512.9
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P7-1: LN 2003-205_SRT-S
TowerAC115.25 %684.0C788.3312.73
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P2-2: ALTAVISTA 115KV_SRT-A
BusAC113.26 %684.0C774.7313.01
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Base Case
SingleAC101.32 %559.3A566.6712.48
GD2DVP
6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 1 transformer
DVP_P4-5: 556X2_SRT-S
BreakerAC139.23 %1050.6C1462.7436.37
GD2DVP
6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 2 transformer
DVP_P4-5: 556X1_SRT-S
BreakerAC138.76 %1053.0C1461.1236.33
GD2DVP
6FINNEYWOOD-AG1-098 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC113.83 %571.52B650.5529.36
GD2DVP
6FINNEYWOOD-AG1-098 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC111.27 %571.52B635.9329.36
GD2DVP
6FINNEYWOOD-AG1-098 TP 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC109.84 %699.0C767.7829.41
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC196.14 %678.68B1331.1410.24
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-3
SingleAC162.3 %678.68B1101.519.03
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Base Case
SingleAC108.58 %678.68A736.928.22
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC198.54 %661.76B1313.8810.24
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-3
SingleAC163.84 %661.76B1084.239.03
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Base Case
SingleAC108.74 %661.76A719.628.22
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC195.13 %661.76B1291.3110.24
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-3
SingleAC160.44 %661.76B1061.79.03
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Base Case
SingleAC105.36 %661.76A697.238.22
GD2DVP
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC131.64 %678.68B893.446.8
GD2DVP
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC130.99 %678.68B889.036.8
GD2DVP
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC125.17 %800.88B1002.469.49
GD2DVP
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC124.77 %800.88B999.289.49
GD2DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC145.19 %678.68B985.376.79
GD2DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC144.54 %678.68B980.946.79
GD2DVP
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC108.88 %1105.0C1203.1247.2
GD2DVP
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC106.72 %1105.0C1179.2447.11
GD2DVP
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC106.7 %1105.0C1179.0547.11
GD2DVP
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
DVP_P4-5: 593X1_SRT-A
BreakerAC104.45 %1105.0C1154.1547.65
GD2DVP
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
DVP_P4-5: 593X2_SRT-A
BreakerAC104.44 %1105.0C1154.0947.64
GD2DVP
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
DVP_P4-2: 56372_SRT-S
BreakerAC150.06 %1056.8C1585.7911.1
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC139.66 %3220.44B4497.8325.77
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: 56272_SRT-S
BreakerAC131.96 %3118.0C4114.6524.95
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S
BreakerAC128.65 %3940.0C5068.7525.88
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: H1T574_SRT-S
BreakerAC128.38 %3940.0C5058.2725.73
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P1-2: LN 562_SRT-S-1
SingleAC115.67 %3118.0B3606.724.95
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P2-2: BREMO B1_SRT-A
BusAC108.3 %3940.0C4267.1526.2
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P7-1: LN 2003-205_SRT-S
TowerAC107.33 %3940.0C4228.6724.3
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P7-1: LN 208-259_SRT-S
TowerAC106.32 %3940.0C4188.8223.17
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Base Case
SingleAC105.09 %3220.44A3384.2822.56
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC104.67 %3940.0C4124.0523.74
GD2DVP
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 576_SRT-S
SingleAC127.08 %1057.5B1343.98.96
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-1: G202_SRT-S
BreakerAC131.07 %3118.0C4086.8821.45
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P2-2: NORTH ANNA B1_SRT-S
BusAC126.92 %3118.0C3957.4421.55
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P2-2: NORTH ANNA B2_SRT-S
BusAC126.92 %3118.0C3957.4421.55
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 2028_SRT-A
SingleAC120.6 %3220.44B3883.8623.56
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 9812_SRT-A
SingleAC119.45 %3220.44B3846.722.19
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Base Case
SingleAC113.34 %3193.18A3619.1321.55
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P7-1: LN 2090-256_SRT-S
TowerAC104.73 %3940.0C4126.1822.11
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P7-1: LN 2054-2135_SRT-A
TowerAC104.47 %3940.0C4115.9521.93
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-1
SingleAC139.73 %4070.2B5687.3346.45
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-2
SingleAC133.78 %4070.2B5445.2846.45
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 58572_SRT-A
BreakerAC124.04 %4996.0C6196.9546.45
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-5: W72_SRT-A
BreakerAC123.43 %4996.0C6166.5646.16
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: XT585_SRT-S
BreakerAC114.16 %4996.0C5703.6646.45
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 54472_SRT-S
BreakerAC111.74 %2858.0C3193.4934.77
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC123.06 %4070.2B5008.6540.85
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51192_SRT-S
BreakerAC109.25 %4996.0C5458.0640.85
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51172_SRT-S
BreakerAC108.79 %4996.0C5435.0740.64
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P4-2: 511T544_SRT-S
BreakerAC107.19 %4996.0C5355.1940.27
GD2DVP
8SEPTA-8SURRY 500.0 kV Ckt 1 line
DVP_P4-2: 56372_SRT-S
BreakerAC103.87 %2931.0C3044.3718.7
GD2DVP
8SEPTA-8SURRY 500.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC101.05 %2931.0C2961.8618.09
GD2DVP
8SEPTA-8SURRY 500.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC101.05 %2931.0C2961.8618.09
GD2DVP
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC113.0 %1105.0C1248.6147.17
GD2DVP
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC110.45 %1105.0C1220.4647.09
GD2DVP
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC110.42 %1105.0C1220.1947.09
GD2DVP
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-5: 593X1_SRT-A
BreakerAC108.84 %1105.0C1202.6947.62
GD2DVP
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-5: 593X2_SRT-A
BreakerAC108.84 %1105.0C1202.6347.62
GD2DVP
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC103.96 %903.34B939.1147.17
GD2DVP
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC102.05 %903.34B921.8947.17
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC239.46 %541.0B1295.4647.15
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC234.05 %541.0B1266.2347.06
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC234.0 %541.0B1265.9647.06
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-5: 593X1_SRT-A
BreakerAC231.01 %541.0B1249.7947.59
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-5: 593X2_SRT-A
BreakerAC231.0 %541.0B1249.7447.59
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC192.41 %508.54B978.4647.15
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC189.13 %508.54B961.8147.15
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P2-2: BREMO B1_SRT-A
BusAC102.04 %541.0B552.0124.08
GD2DVP
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC125.65 %800.88B1006.319.51
GD2DVP
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC125.22 %800.88B1002.889.51
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC136.1 %4070.2B5539.4140.85
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 51192_SRT-S
BreakerAC120.36 %4996.0C6013.1140.85
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 51172_SRT-S
BreakerAC119.82 %4996.0C5986.2940.64
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 511T544_SRT-S
BreakerAC118.15 %4996.0C5902.940.27
GD2DVP
AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC117.76 %571.52B673.0429.36
GD2DVP
AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC115.2 %571.52B658.3829.36
GD2DVP
AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC114.07 %699.0C797.3729.41
GD2DVP
AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC114.03 %699.0C797.0829.41
GD2DVP
AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC110.84 %699.0C774.7929.36
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC211.67 %684.0C1447.7929.97
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC211.61 %684.0C1447.429.97
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC207.99 %684.0C1422.6229.9
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC206.17 %559.3B1153.1229.9
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC203.59 %559.3B1138.6829.9
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC201.95 %684.0C1381.3529.9
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC201.95 %684.0C1381.3529.9
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P7-1: LN 2106-2111_SRT-A
TowerAC128.21 %684.0C876.9612.4
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC128.06 %684.0C875.9512.9
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P7-1: LN 2003-205_SRT-S
TowerAC124.48 %684.0C851.4712.73
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
BusAC115.8 %684.0C792.0612.58
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Base Case
SingleAC110.37 %559.3A617.3212.48
GD2DVP
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC132.79 %571.52B758.9329.36
GD2DVP
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC130.22 %571.52B744.2429.36
GD2DVP
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC129.97 %699.0C908.529.41
GD2DVP
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC129.93 %699.0C908.2129.41
GD2DVP
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC126.73 %699.0C885.8629.36
GD2DVP
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC120.78 %699.0C844.2729.36
GD2DVP
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC120.78 %699.0C844.2729.36
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC129.2 %4070.2B5258.7240.85
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51192_SRT-S
BreakerAC114.25 %4996.0C5708.1240.85
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51172_SRT-S
BreakerAC113.76 %4996.0C5683.4440.64
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P4-2: 511T544_SRT-S
BreakerAC112.13 %4996.0C5601.840.27
GD2DVP
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC120.99 %800.88B969.019.55
GD2DVP
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC120.59 %800.88B965.759.55
GD2DVP
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC127.24 %571.52B727.229.36
GD2DVP
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC124.67 %571.52B712.5229.36
GD2DVP
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC124.28 %699.0C868.7129.41
GD2DVP
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC124.24 %699.0C868.4129.41
GD2DVP
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC121.04 %699.0C846.0929.36
GD2DVP
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC115.09 %699.0C804.5129.36
GD2DVP
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC115.09 %699.0C804.5129.36
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC218.2 %684.0C1492.529.97
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC218.14 %684.0C1492.1129.97
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC214.52 %684.0C1467.3429.9
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC212.24 %559.3B1187.0429.9
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC209.65 %559.3B1172.5929.9
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC208.48 %684.0C1426.0329.9
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC208.48 %684.0C1426.0329.9
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P7-1: LN 2106-2111_SRT-A
TowerAC134.05 %684.0C916.9112.4
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC133.94 %684.0C916.1212.9
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P7-1: LN 2003-205_SRT-S
TowerAC130.34 %684.0C891.5412.73
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
BusAC121.65 %684.0C832.1112.58
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Base Case
SingleAC115.81 %559.3A647.712.48
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC219.98 %699.0C1537.6529.95
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC219.92 %699.0C1537.2629.95
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC216.35 %699.0C1512.3129.89
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC213.74 %571.52B1221.629.89
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC211.19 %571.52B1206.9729.89
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC210.43 %699.0C1470.929.89
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC210.43 %699.0C1470.929.89
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC137.05 %699.0C957.9712.88
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P7-1: LN 2106-2111_SRT-A
TowerAC136.87 %699.0C956.6912.39
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P7-1: LN 2003-205_SRT-S
TowerAC133.52 %699.0C933.3112.71
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
BusAC125.05 %699.0C874.112.56
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Base Case
SingleAC118.94 %571.52A679.7712.47

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:203.13 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1378.6
MW Contribution:10.91
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.18
316303AF2-085
50/50
2.224
3151541CLOVER2
50/50
2.487
3151611KERR 4
50/50
0.234
3151621KERR 5
50/50
0.234
3151631KERR 6
50/50
0.234
3151641KERR 7
50/50
0.234
963041AG1-153 GEN
50/50
2.299
315244AE2-183_ST
50/50
2.451
3151281ROARAP4
50/50
0.1
3151281ROARAP4
50/50
0.094
971285AH1-108 GEN
50/50
0.651
315779AE2-040
50/50
1.092
971845AH1-439 GEN
Solar/Wind Harmer
17.513
970285AG2-188 GEN
Solar/Wind Harmer
29.552
315657AE1-056 GEN
Solar/Wind Harmer
8.144
946301AF1-294 GEN
Solar/Wind Harmer
4.404
961791AG1-021 GEN
Solar/Wind Harmer
2.143
970683AG2-441 GEN
Solar/Wind Harmer
13.644
970681AG2-440 GEN
Solar/Wind Harmer
10.915
3144303KENBRDG
Solar/Wind Harmer
0.148
971443AH1-215 GEN
Solar/Wind Harmer
3.079
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316233AE1-074 FULL
Solar/Wind Harmer
0.084
971281AH1-106 GEN
Solar/Wind Harmer
1.459
3151921BEARGRDN G2
50/50
4.548
3144293JTRSVLE
50/50
0.754
970413AG2-270 GEN
50/50
10.906
3151591KERR 2
50/50
0.234
3151031BRUNSWICKG2
50/50
1.135
3151261ROARAP2
50/50
0.101
3150861SPRUNCD
50/50
0.398
3151391GASTONA
50/50
0.204
3151411GASTONB
50/50
0.204
3146776BUCKING
Solar/Wind Harmer
0.141
3146926FARMVIL
Solar/Wind Harmer
0.188
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
316313AB2-026
Solar/Wind Harmer
0.171
316258AE1-075 C
Solar/Wind Harmer
0.204
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.088
970909AG2-566 GEN
Solar/Wind Harmer
2.566
3147133PAMPLIN
Solar/Wind Harmer
0.741
971193AH1-056 GEN
Solar/Wind Harmer
14.378
963181AG1-167 GEN
Solar/Wind Harmer
0.893
959311AF2-222 GEN
Solar/Wind Harmer
16.945
970257AG2-171 GEN
Solar/Wind Harmer
5.919
315785AD2-033 C
Solar/Wind Harmer
1.44
964241AG1-285 GEN
Solar/Wind Harmer
10.432
316131AB2-060 GEN
Solar/Wind Harmer
0.453
970221AG2-151 GEN
Solar/Wind Harmer
7.009
316478AD1-087 GEN
Solar/Wind Harmer
0.407
316486AD2-202 GEN
Solar/Wind Harmer
0.12
3147043LAWRENC
Solar/Wind Harmer
0.063
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.061
313506AB2-031 GEN
Solar/Wind Harmer
0.265
971683AH1-343 GEN
Solar/Wind Harmer
3.059
971283AH1-107 GEN
Solar/Wind Harmer
1.459
316118AC1-105 GEN
Solar/Wind Harmer
0.27
270494AE1-108_GEN
Solar/Wind Harmer
1.236
970831AG2-522 GEN
Solar/Wind Harmer
4.291
3147173SINAI
Solar/Wind Harmer
0.095
3147243WELCO
Solar/Wind Harmer
0.059
971967AH1-528 GEN
Solar/Wind Harmer
14.709
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
18.242
970673AG2-436 GEN
Solar/Wind Harmer
12.162
941031AE2-094 GEN
Solar/Wind Harmer
15.639
944011AF1-069 GEN
Solar/Wind Harmer
5.11
3137643SOCKMAN
Solar/Wind Harmer
0.336
970085AG2-068 GEN
Solar/Wind Harmer
4.411
970581AG2-369 GEN
Solar/Wind Harmer
3.794
315607AA1-063A GEN
Solar/Wind Harmer
0.164
3146043SEABORD
Solar/Wind Harmer
0.08
315814AE2-033 C
Solar/Wind Harmer
6.192
316315AB2-025 C
Solar/Wind Harmer
0.063
970865AG2-541 GEN
Solar/Wind Harmer
2.68
965291AG1-394 GEN
Solar/Wind Harmer
0.339
315652AC1-086 GEN
Solar/Wind Harmer
8.307
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
3145796HORNRTN
Solar/Wind Harmer
0.238
3145796HORNRTN
Solar/Wind Harmer
0.03
3143316POE
Solar/Wind Harmer
0.292
3146033SCOT NK
Solar/Wind Harmer
0.294
3145513AHOSKIE
Solar/Wind Harmer
0.153
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.146
3145683EARLEYS
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
3146206CASHIE
Solar/Wind Harmer
0.07
970601AG2-382 GEN
Solar/Wind Harmer
2.62
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.048
316311AC2-079 GEN
Solar/Wind Harmer
2.01
316319Z2-044 C
Solar/Wind Harmer
0
315732AD1-074 GEN1
Solar/Wind Harmer
0.4
315733AD1-074 GEN2
Solar/Wind Harmer
0.4
315735AD1-075 GEN1
Solar/Wind Harmer
0.2
3130546PLYMOUTH
Solar/Wind Harmer
0.07
315835AF2-110_GEN
Solar/Wind Harmer
0.478
315816AE2-034 GEN
Solar/Wind Harmer
0.298
3130156CHOWAN
Solar/Wind Harmer
0.069
3130156CHOWAN
Solar/Wind Harmer
0.069
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3146486SUNBURY
Solar/Wind Harmer
0.069
3146486SUNBURY
Solar/Wind Harmer
0.069
316321Z2-027
Solar/Wind Harmer
0.013
3145176PASQUOTANK
Solar/Wind Harmer
0.043
3146396TANGLEW
Solar/Wind Harmer
0.19
316305AF2-043 C
Solar/Wind Harmer
0.001
313526AB2-022
Solar/Wind Harmer
0.037
3146406KITTY HAWK
Solar/Wind Harmer
0.009
319010AE1-072 C
Solar/Wind Harmer
0.346
957871AF2-081 GEN
Solar/Wind Harmer
3.419
3151081ELIZAR1
Adder
6.268
3151091ELIZAR2
Adder
6.16
3152611GOSPORTB
Adder
0.871
3152621GOSPORTC
Adder
0.739
3152601GOSPORTA
Adder
0.682
3145573BETHELC
Solar/Wind Harmer
0.067
3145573BETHELC
Solar/Wind Harmer
0.067
316420AA1-050 GEN
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
2.903
316005AA1-067
Solar/Wind Harmer
0.072
3145746EVERETS
Solar/Wind Harmer
0.267
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
970181AG2-120 GEN
Solar/Wind Harmer
0.836
971445AH1-216 GEN
Solar/Wind Harmer
4.703
972265AH1-717 GEN
Adder
5.124
3151201GRAVEL4
Adder
4.803
3151191GRAVEL3
Adder
4.742
3151211GRAVEL5
Adder
4.742
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.353
316123AC1-075 GEN
Solar/Wind Harmer
0.09
3144293JTRSVLE
50/50
0.754
3144293JTRSVLE
50/50
0.635
970535AG2-341 GEN
50/50
2.24
3152661PLYWOOD A
50/50
0.227
3151041BRUNSWICKG3
50/50
1.135
972187AH1-678 GEN
50/50
2.606
315242AE2-183_GT2
50/50
1.418
315241AE2-183_GT1
50/50
1.409
972185AH1-677 GEN
50/50
5.111
970533AG2-339 GEN
50/50
7.548
970531AG2-338 GEN
50/50
3.019
3146776BUCKING
Solar/Wind Harmer
1.571
3146776BUCKING
Solar/Wind Harmer
0.127
970301AG2-198 GEN
Solar/Wind Harmer
10.262
3147133PAMPLIN
Solar/Wind Harmer
0.236
3147133PAMPLIN
Solar/Wind Harmer
0.189
958211AF2-115 GEN
Solar/Wind Harmer
2.678
963191AG1-168 GEN
Solar/Wind Harmer
0.893
971741AH1-377 GEN
Solar/Wind Harmer
21.598
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
7.892
971775AH1-396 GEN
Solar/Wind Harmer
0.296
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971489AH1-241 GEN
Solar/Wind Harmer
7.009
971223AH1-071 GEN
Solar/Wind Harmer
1.334
962561AG1-105 GEN
Solar/Wind Harmer
5.681
939181AE1-148 GEN
Solar/Wind Harmer
5.661
970099AG2-077 GEN
Solar/Wind Harmer
12.506
964791AG1-342 GEN
Solar/Wind Harmer
2.195
3146843MT LREL
Solar/Wind Harmer
0.114
3146843MT LREL
Solar/Wind Harmer
0.114
3143526WINTERP
Solar/Wind Harmer
0.547
970933AG2-581 GEN
Solar/Wind Harmer
7.995
316181AB2-040 GEN
Solar/Wind Harmer
0.124
3145593CAROLNA
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.083
966811AG1-552 GEN
Solar/Wind Harmer
0.899
3145593CAROLNA
Solar/Wind Harmer
0.103
3145783HORNRTN
Solar/Wind Harmer
1.451
3145783HORNRTN
Solar/Wind Harmer
1.161
3145783HORNRTN
Solar/Wind Harmer
0.363
3145783HORNRTN
Solar/Wind Harmer
0.145
316426AA2-053 GEN
Solar/Wind Harmer
0.274
3144356SAPONY
Solar/Wind Harmer
0.654
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
0.503
3145893MURPHYS
Solar/Wind Harmer
0.135
316274AC1-208 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
0.223
3146173TUNIS
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
315742AE1-103 GEN
Solar/Wind Harmer
0.001
970657AG2-426 GEN
Solar/Wind Harmer
2.47
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.223
3146376EDENTON
Solar/Wind Harmer
0.308
3146376EDENTON
Solar/Wind Harmer
0.308
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146386ELIZ CT
Solar/Wind Harmer
0.069
316240AF1-291 C
Solar/Wind Harmer
0.001
3130086AYDLETT
Solar/Wind Harmer
0.275
3137176SLIGO L2192
Solar/Wind Harmer
0.273
3146456SLIGO L269
Solar/Wind Harmer
1.215
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.038
316339AD2-160 GEN
Solar/Wind Harmer
0.111
3145506HICKORY
Solar/Wind Harmer
0.274
3145506HICKORY
Solar/Wind Harmer
0.165
3145506HICKORY
Solar/Wind Harmer
0.041
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.066
316036AC1-147 C
Solar/Wind Harmer
0.013
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.505
316222AC1-221 GEN
Solar/Wind Harmer
0.283
316263AC1-034 GEN
Solar/Wind Harmer
2.586
3145933PARMELE
Solar/Wind Harmer
0.135
3145933PARMELE
Solar/Wind Harmer
0.068
961601AG1-000A GEN
Solar/Wind Harmer
1.202
3145493TOT1
Solar/Wind Harmer
0.156
3145453TOT5
Solar/Wind Harmer
0.094
3145603CNETO
Solar/Wind Harmer
0.063
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.074
3142366NRTHEST
Adder
0.195
3142946ENON
Solar/Wind Harmer
0.006
3150691DARBY 3
Adder
4.195
3150701DARBY 4
Adder
4.185
3150681DARBY 2
Adder
4.18
3150671DARBY 1
Adder
4.175
942751AE2-291 GEN
Solar/Wind Harmer
3.155
966001AG1-469 GEN
Solar/Wind Helper
0.19
3151931BEARGRDN S1
50/50
5.869
3151911BEARGRDN G1
50/50
4.548
3144293JTRSVLE
50/50
0.754
970119AG2-088 GEN
50/50
16.679
3151531CLOVER1
50/50
2.499
3151601KERR 3
50/50
0.234
3151581KERR 1
50/50
0.083
3147043LAWRENC
50/50
1
3151051BRUNSWICKS1
50/50
2.357
3151021BRUNSWICKG1
50/50
1.135
971451AH1-221 GEN
50/50
3.449
315243AE2-183_GT3
50/50
1.418
3151261ROARAP2
50/50
0.103
3150851SPRUNCC
50/50
0.398
3151391GASTONA
50/50
0.204
3151411GASTONB
50/50
0.204
972003AH1-546 GEN
Solar/Wind Harmer
20.039
970937AG2-583 GEN
Solar/Wind Harmer
24.928
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.157
3146926FARMVIL
Solar/Wind Harmer
0.188
316336AC2-165 C
Solar/Wind Harmer
0.012
3143336POWHATN
Solar/Wind Harmer
4.81
963171AG1-166 GEN
Solar/Wind Harmer
1.19
971563AH1-280 GEN
Solar/Wind Harmer
2.381
970685AG2-442 GEN
Solar/Wind Harmer
15.281
962491AG1-098 GEN
Solar/Wind Harmer
8.349
315693AD1-088 GEN
Solar/Wind Harmer
6.776
316237AB2-079_GEN
Solar/Wind Harmer
0.001
971377AH1-170 GEN
Solar/Wind Harmer
1.402
3147623JAMES R
Solar/Wind Harmer
0.305
3143226MDLTHAN
Solar/Wind Harmer
0.125
957481AF2-042 GEN
Solar/Wind Harmer
31.266
970401AG2-262 GEN
Solar/Wind Harmer
0.671
315687AD1-152 GEN
Solar/Wind Harmer
0.003
3143526WINTERP
Solar/Wind Harmer
0.547
971065AG2-659 GEN
Solar/Wind Harmer
4.446
316129AC1-054 GEN
Solar/Wind Harmer
0.385
971795AH1-408 GEN
Solar/Wind Harmer
6.611
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.847
970919AG2-571 GEN
Solar/Wind Harmer
2.953
970087AG2-069 GEN
Solar/Wind Harmer
6.617
3145783HORNRTN
Solar/Wind Harmer
0.082
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
6.459
316023GEN1_S
Solar/Wind Harmer
0.176
939411AE1-173 GEN
Solar/Wind Harmer
33.156
3146263WOODLND
Solar/Wind Harmer
0.076
316011AB1-132 GEN
Solar/Wind Harmer
1.373
962571AG1-106 GEN
Solar/Wind Harmer
1.074
3145893MURPHYS
Solar/Wind Harmer
0.301
3145893MURPHYS
Solar/Wind Harmer
0.334
3145796HORNRTN
Solar/Wind Harmer
0.245
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316212AC1-099_GEN
Solar/Wind Harmer
0.382
3145823KELFORD
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
315722AD1-056 GEN
Solar/Wind Harmer
0.447
970659AG2-427 GEN
Solar/Wind Harmer
3.416
316381AD1-082 GEN
Solar/Wind Harmer
0.074
970661AG2-428 GEN
Solar/Wind Harmer
7.004
3146206CASHIE
Solar/Wind Harmer
0.07
971547AH1-271 GEN
Solar/Wind Harmer
1.497
3142543TWELFTH
Solar/Wind Harmer
0.007
3146233WITAKRS
Solar/Wind Harmer
0.278
316093AE2-104_GEN
Solar/Wind Harmer
1.171
3145663CRESWEL
Solar/Wind Harmer
0.194
971163AH1-040 GEN
Solar/Wind Harmer
5.558
3130156CHOWAN
Solar/Wind Harmer
0.069
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.223
3146516WINFALL
Solar/Wind Harmer
0.069
315671AE2-027_GEN
Solar/Wind Harmer
4.41
316246AF1-032 C
Solar/Wind Harmer
0.031
3146456SLIGO L269
Solar/Wind Harmer
0.069
316388AE2-253 GEN
Solar/Wind Harmer
0.215
944591AF1-124 GEN
Solar/Wind Harmer
15.512
3145963POPLR C
Solar/Wind Harmer
0.069
316174AB2-169 GEN
Solar/Wind Harmer
0.002
316375AC2-012 GEN
Solar/Wind Harmer
0.002
970917AG2-570 GEN
Solar/Wind Harmer
7.384
316365GEN2_N
Solar/Wind Harmer
0.176
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
957521AF2-046 GEN
Solar/Wind Harmer
5.572
961681AG1-008 GEN
Solar/Wind Harmer
5.572
3145796HORNRTN
Solar/Wind Harmer
0.297
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316210AC1-098 GEN
Solar/Wind Harmer
0.686
316463AE2-346 GEN
Solar/Wind Harmer
0.063
316140AB2-099
Solar/Wind Harmer
0.026
962331AG1-082 GEN
Solar/Wind Harmer
0.783
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.073
316327AA2-057 GEN
Solar/Wind Harmer
0.108
3145273HOLLAND
Solar/Wind Harmer
0.054
315813AE1-149 C
Solar/Wind Harmer
3.784
3156021HOLLOMANSOL
Solar/Wind Harmer
0.322
315839AE2-212 C
Solar/Wind Harmer
0.001
315724AD1-057 GEN
Solar/Wind Harmer
0.265
970659AG2-427 GEN
Solar/Wind Harmer
0.747
316083AB2-161 GEN
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
0.07
3146233WITAKRS
Solar/Wind Harmer
0.351
3146233WITAKRS
Solar/Wind Harmer
0.048
3138543CONSLDL
Solar/Wind Harmer
0.046
315737AD1-076 GEN
Solar/Wind Harmer
0.896
971157AH1-035 GEN
Solar/Wind Harmer
0.836
965281AG1-393 GEN
Solar/Wind Harmer
0.741
315614AA2-178 GEN
Solar/Wind Harmer
0.398
3146376EDENTON
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
316435W1029_GEN3
Solar/Wind Harmer
0
316320Y1-086
Solar/Wind Harmer
0
3146456SLIGO L269
Solar/Wind Harmer
0.069
971153AH1-033 GEN
Solar/Wind Harmer
0.794
944581AF1-123 GEN
Solar/Wind Harmer
15.457
944601AF1-125 GEN
Solar/Wind Harmer
15.219
3145963POPLR C
Solar/Wind Harmer
0.069
3151101ELIZAR3
Adder
6.349
3144873MCLAUGH
Solar/Wind Harmer
0.002
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.068
971623AH1-311 GEN
Solar/Wind Harmer
0.136
3144536CHRHLND
Solar/Wind Harmer
0.01
3145933PARMELE
Solar/Wind Harmer
0.068
966801AG1-551 GEN
Solar/Wind Harmer
0.788
961601AG1-000A GEN
Solar/Wind Harmer
4.808
315773AC2-141 GEN
Solar/Wind Harmer
2.468
3146073TAR RVR
Solar/Wind Harmer
0.067
970165AG2-112 GEN
Solar/Wind Harmer
0.531
970163AG2-111 GEN
Solar/Wind Harmer
0.506
971447AH1-217 GEN
Solar/Wind Harmer
1.848
971167AH1-042 GEN
Solar/Wind Harmer
5.088
3138283WHITEMARSH
Solar/Wind Harmer
0.013
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.105
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.12
3150981CHESPKA
Adder
0.853
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.054
316359AB2-059 GEN
Solar/Wind Harmer
0.244
316049AB1-081 GEN
Solar/Wind Harmer
0.389
3142053HEARTS
Solar/Wind Harmer
0.12
316072AD1-144
Solar/Wind Harmer
0.025
3146293MARTNCO
Solar/Wind Harmer
0.063
316294AC1-161 GEN
Solar/Wind Harmer
1.171
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.067
3145493TOT1
Solar/Wind Harmer
0.3
316494AC1-189 GEN
Solar/Wind Harmer
0.227
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.267
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
961611AG1-000B GEN
Solar/Wind Harmer
3.457
971647AH1-324 GEN
Solar/Wind Harmer
2.81
971069AG2-661 GEN
Solar/Wind Harmer
1.169
316458AB2-190 GEN2
Solar/Wind Harmer
0.353
970129AG2-093 GEN
Solar/Wind Harmer
1.869
944631AF1-128 GEN
Adder
29.45
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971317AH1-138 GEN
Solar/Wind Harmer
0.439
316159AE1-175 C
Solar/Wind Harmer
0.05
3142433PROV 92
Solar/Wind Harmer
0.226
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.056
316192AB2-158 GEN
Solar/Wind Helper
0.823
3147666LOUISA
Solar/Wind Helper
0.475
3146083TARBORO
Solar/Wind Harmer
0.067
316283AC2-100 C
Solar/Wind Harmer
0.132
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.027
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.798
3151171GRAVELC
Adder
0.923
961611AG1-000B GEN
Solar/Wind Harmer
1.758
315778AD1-151 GEN
Solar/Wind Harmer
5.261
970129AG2-093 GEN
Solar/Wind Harmer
3.971
970133AG2-095 GEN
Solar/Wind Harmer
0.63
3144216WINCHST
Adder
0.231
3150921YORKTN3
Adder
1.525
3142946ENON
Solar/Wind Harmer
0.02
316382AG1-145 C
Solar/Wind Harmer
0
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.175
316499AE2-029_GEN
Solar/Wind Helper
0.514
3132273ORANGE
Solar/Wind Helper
0.027
315616AA1-038_C
Solar/Wind Helper
0.545
3147666LOUISA
Solar/Wind Helper
0.273
CPLELTFEXP_CPLE->PJM
CLTF
4.352
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.276
LAGNLTFEXP_LAGN->PJM
CLTF
1.781
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.535
TVALTFEXP_TVA->PJM
CLTF
0.87
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.726
MECLTFEXP_MEC->PJM
CLTF
0.354
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.579
LGEELTFEXP_LGEE->PJM
CLTF
0.048
WECLTFEXP_WEC->PJM
CLTF
0.018

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:185.6 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1540.5
MW Contribution:10.89
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.146
316303AF2-085
50/50
2.223
3151541CLOVER2
50/50
2.485
3151611KERR 4
50/50
0.233
3151621KERR 5
50/50
0.233
3151631KERR 6
50/50
0.233
3151641KERR 7
50/50
0.233
971845AH1-439 GEN
Solar/Wind Harmer
23.024
970285AG2-188 GEN
Solar/Wind Harmer
36.67
315657AE1-056 GEN
Solar/Wind Harmer
9.935
946301AF1-294 GEN
Solar/Wind Harmer
6.417
961791AG1-021 GEN
Solar/Wind Harmer
3.13
970683AG2-441 GEN
Solar/Wind Harmer
17.94
970681AG2-440 GEN
Solar/Wind Harmer
14.352
3144303KENBRDG
Solar/Wind Harmer
-0.017
971443AH1-215 GEN
Solar/Wind Harmer
4.049
316239AB2-077_GEN
Solar/Wind Harmer
0.467
316238AB2-078_GEN
Solar/Wind Harmer
0.467
3151931BEARGRDN S1
50/50
5.86
3151911BEARGRDN G1
50/50
4.541
3144293JTRSVLE
50/50
0.753
970119AG2-088 GEN
50/50
16.672
3151531CLOVER1
50/50
2.497
3151601KERR 3
50/50
0.233
3151581KERR 1
50/50
0.083
972003AH1-546 GEN
Solar/Wind Harmer
26.388
970937AG2-583 GEN
Solar/Wind Harmer
32.774
316322AB2-045
Solar/Wind Harmer
1.483
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.021
316336AC2-165 C
Solar/Wind Harmer
6.018
3143336POWHATN
Solar/Wind Harmer
3.603
963171AG1-166 GEN
Solar/Wind Harmer
3.13
971563AH1-280 GEN
Solar/Wind Harmer
3.13
970685AG2-442 GEN
Solar/Wind Harmer
20.093
962491AG1-098 GEN
Solar/Wind Harmer
10.981
315693AD1-088 GEN
Solar/Wind Harmer
7.922
316237AB2-079_GEN
Solar/Wind Harmer
0.467
971377AH1-170 GEN
Solar/Wind Harmer
1.836
3147623JAMES R
Solar/Wind Harmer
0.227
3143226MDLTHAN
Solar/Wind Harmer
-0.014
957481AF2-042 GEN
Solar/Wind Harmer
41.127
970401AG2-262 GEN
Solar/Wind Harmer
0.837
315687AD1-152 GEN
Solar/Wind Harmer
1.432
3143526WINTERP
Solar/Wind Harmer
-0.061
3147043LAWRENC
Adder
0.942
971065AG2-659 GEN
Solar/Wind Harmer
5.848
316129AC1-054 GEN
Solar/Wind Harmer
1.008
971795AH1-408 GEN
Solar/Wind Harmer
8.35
316003AC1-222 GEN
Solar/Wind Harmer
0.972
960081AF2-299 GEN
Solar/Wind Harmer
1.114
970919AG2-571 GEN
Solar/Wind Harmer
2.952
970087AG2-069 GEN
Solar/Wind Harmer
8.708
3145783HORNRTN
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.375
316190AA2-174 GEN
Solar/Wind Harmer
0.112
940641AE2-051 GEN
Solar/Wind Harmer
8.503
316023GEN1_S
Solar/Wind Harmer
0.594
939411AE1-173 GEN
Solar/Wind Harmer
43.657
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.775
962571AG1-106 GEN
Solar/Wind Harmer
1.22
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.723
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.219
316381AD1-082 GEN
Solar/Wind Harmer
0.728
315722AD1-056 GEN
Solar/Wind Harmer
0.83
970661AG2-428 GEN
Solar/Wind Harmer
8.41
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
1.971
3146233WITAKRS
Solar/Wind Harmer
-0.031
316093AE2-104_GEN
Solar/Wind Harmer
2.275
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.318
3130156CHOWAN
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
1.92
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.811
316246AF1-032 C
Solar/Wind Harmer
0.157
3146456SLIGO L269
Solar/Wind Harmer
-0.008
316388AE2-253 GEN
Solar/Wind Harmer
0.521
944591AF1-124 GEN
Solar/Wind Harmer
35.229
3150981CHESPKA
Adder
0.854
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
944631AF1-128 GEN
Adder
29.484
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.057
3151921BEARGRDN G2
50/50
4.541
3144293JTRSVLE
50/50
0.753
970413AG2-270 GEN
50/50
10.895
3151591KERR 2
50/50
0.233
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
4.6
316313AB2-026
Solar/Wind Harmer
0.819
316258AE1-075 C
Solar/Wind Harmer
0.737
316405AF2-144 C
Solar/Wind Harmer
0.778
316233AE1-074 FULL
Solar/Wind Harmer
0.318
971281AH1-106 GEN
Solar/Wind Harmer
1.921
971283AH1-107 GEN
Solar/Wind Harmer
1.921
316118AC1-105 GEN
Solar/Wind Harmer
0.807
270494AE1-108_GEN
Solar/Wind Harmer
2.995
970831AG2-522 GEN
Solar/Wind Harmer
5.644
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
19.409
946281AF1-292 GEN
Solar/Wind Harmer
0.222
316087AB2-174 GEN
Solar/Wind Harmer
1.385
970673AG2-436 GEN
Solar/Wind Harmer
20.177
970673AG2-436 GEN
Solar/Wind Harmer
10.216
941031AE2-094 GEN
Solar/Wind Harmer
17.883
944011AF1-069 GEN
Solar/Wind Harmer
5.603
3137643SOCKMAN
Solar/Wind Harmer
-0.038
970085AG2-068 GEN
Solar/Wind Harmer
5.805
970581AG2-369 GEN
Solar/Wind Harmer
4.993
971285AH1-108 GEN
Adder
0.613
315607AA1-063A GEN
Solar/Wind Harmer
0.911
3146043SEABORD
Solar/Wind Harmer
-0.009
315814AE2-033 C
Solar/Wind Harmer
8.189
316315AB2-025 C
Solar/Wind Harmer
0.237
970865AG2-541 GEN
Solar/Wind Harmer
3.523
965291AG1-394 GEN
Solar/Wind Harmer
0.761
315652AC1-086 GEN
Solar/Wind Harmer
9.545
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.033
3146033SCOT NK
Solar/Wind Harmer
-0.033
3145513AHOSKIE
Solar/Wind Harmer
0.072
961941AG1-037 GEN
Solar/Wind Harmer
0.062
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.449
315833AF1-017_GEN
Solar/Wind Harmer
1.494
316349AD2-085 GEN
Solar/Wind Harmer
0.7
316311AC2-079 GEN
Solar/Wind Harmer
3.968
316319Z2-044 C
Solar/Wind Harmer
0.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.583
315733AD1-074 GEN2
Solar/Wind Harmer
1.583
315735AD1-075 GEN1
Solar/Wind Harmer
0.792
315835AF2-110_GEN
Solar/Wind Harmer
0.978
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.632
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
1.92
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.209
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.142
316305AF2-043 C
Solar/Wind Harmer
0.233
313526AB2-022
Solar/Wind Harmer
0.209
319010AE1-072 C
Solar/Wind Harmer
1.562
3146406KITTY HAWK
Solar/Wind Harmer
0.006
957871AF2-081 GEN
Solar/Wind Harmer
3.86
3151081ELIZAR1
Adder
6.271
3151091ELIZAR2
Adder
6.162
3152611GOSPORTB
Adder
0.871
3152621GOSPORTC
Adder
0.739
3152601GOSPORTA
Adder
0.682
972265AH1-717 GEN
Adder
5.127
3151201GRAVEL4
Adder
4.806
3151191GRAVEL3
Adder
4.745
3151211GRAVEL5
Adder
4.745
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.121
3143336POWHATN
Solar/Wind Harmer
3.062
970909AG2-566 GEN
Solar/Wind Harmer
2.562
3147133PAMPLIN
Solar/Wind Harmer
-0.083
971193AH1-056 GEN
Solar/Wind Harmer
16.559
963181AG1-167 GEN
Solar/Wind Harmer
2.348
959311AF2-222 GEN
Solar/Wind Harmer
22.325
970257AG2-171 GEN
Solar/Wind Harmer
7.783
315785AD2-033 C
Solar/Wind Harmer
4.506
964241AG1-285 GEN
Solar/Wind Harmer
13.718
316131AB2-060 GEN
Solar/Wind Harmer
1.742
970221AG2-151 GEN
Solar/Wind Harmer
9.178
316478AD1-087 GEN
Solar/Wind Harmer
1.133
316486AD2-202 GEN
Solar/Wind Harmer
0.332
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.322
960061AF2-297 GEN
Solar/Wind Harmer
5.34
966621AG1-532 GEN
Solar/Wind Harmer
0.201
313506AB2-031 GEN
Solar/Wind Harmer
0.773
970917AG2-570 GEN
Solar/Wind Harmer
23.32
971683AH1-343 GEN
Solar/Wind Harmer
4.021
3150861SPRUNCD
Adder
0.375
316365GEN2_N
Solar/Wind Harmer
0.594
3156081AA2-088 GEN
Solar/Wind Harmer
2.773
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.624
961681AG1-008 GEN
Solar/Wind Harmer
6.624
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.302
316463AE2-346 GEN
Solar/Wind Harmer
0.133
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.031
316317KELFORD C
Solar/Wind Harmer
0.388
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.813
3145273HOLLAND
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
4.985
3156021HOLLOMANSOL
Solar/Wind Harmer
1.073
315839AE2-212 C
Solar/Wind Harmer
0.24
970659AG2-427 GEN
Solar/Wind Harmer
0.748
316083AB2-161 GEN
Solar/Wind Harmer
1.288
315724AD1-057 GEN
Solar/Wind Harmer
0.456
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
-0.008
3146233WITAKRS
Solar/Wind Harmer
0.164
3144293JTRSVLE
50/50
0.753
3144293JTRSVLE
50/50
0.634
970535AG2-341 GEN
50/50
2.238
3146776BUCKING
Solar/Wind Harmer
-0.175
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.493
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.913
963191AG1-168 GEN
Solar/Wind Harmer
2.348
971741AH1-377 GEN
Solar/Wind Harmer
28.4
316034AC1-036 C
Solar/Wind Harmer
0.386
970323AG2-213 GEN
Solar/Wind Harmer
10.377
971775AH1-396 GEN
Solar/Wind Harmer
1.478
313527AB2-043 GEN
Solar/Wind Harmer
2.568
971489AH1-241 GEN
Solar/Wind Harmer
8.713
971223AH1-071 GEN
Solar/Wind Harmer
1.756
962561AG1-105 GEN
Solar/Wind Harmer
7.471
939181AE1-148 GEN
Solar/Wind Harmer
7.446
970099AG2-077 GEN
Solar/Wind Harmer
16.451
964791AG1-342 GEN
Solar/Wind Harmer
2.74
3146843MT LREL
Solar/Wind Harmer
-0.013
3146843MT LREL
Solar/Wind Harmer
-0.013
3143526WINTERP
Solar/Wind Harmer
-0.061
970933AG2-581 GEN
Solar/Wind Harmer
10.52
972187AH1-678 GEN
Adder
2.454
972185AH1-677 GEN
Adder
4.815
316181AB2-040 GEN
Solar/Wind Harmer
1.342
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
1.047
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.088
3145783HORNRTN
Solar/Wind Harmer
0.87
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.488
971157AH1-035 GEN
Solar/Wind Harmer
0.978
965281AG1-393 GEN
Solar/Wind Harmer
0.977
315614AA2-178 GEN
Solar/Wind Harmer
0.842
3146376EDENTON
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316435W1029_GEN3
Solar/Wind Harmer
1.405
316320Y1-086
Solar/Wind Harmer
0.453
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.941
944581AF1-123 GEN
Solar/Wind Harmer
35.103
3151101ELIZAR3
Adder
6.351
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.801
3151171GRAVELC
Adder
0.924
3144216WINCHST
Adder
0.232
3150921YORKTN3
Adder
1.526
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.176
316499AE2-029_GEN
Solar/Wind Helper
0.517
3132273ORANGE
Solar/Wind Helper
0.028
3147666LOUISA
Solar/Wind Helper
0.309
315616AA1-038_C
Solar/Wind Helper
0.548
944601AF1-125 GEN
Solar/Wind Harmer
11.266
316192AB2-158 GEN
Solar/Wind Helper
0.927
3147666LOUISA
Solar/Wind Helper
0.538
3145783HORNRTN
Solar/Wind Harmer
0.272
3145783HORNRTN
Solar/Wind Harmer
0.109
316426AA2-053 GEN
Solar/Wind Harmer
0.92
3144356SAPONY
Solar/Wind Harmer
0.307
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
316274AC1-208 GEN
Solar/Wind Harmer
0.909
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.852
970657AG2-426 GEN
Solar/Wind Harmer
2.477
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.932
3146376EDENTON
Solar/Wind Harmer
0.231
3146376EDENTON
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.405
316433W1029_GEN2
Solar/Wind Harmer
1.405
316240AF1-291 C
Solar/Wind Harmer
0.233
3146386ELIZ CT
Solar/Wind Harmer
-0.008
3130086AYDLETT
Solar/Wind Harmer
-0.031
3137176SLIGO L2192
Solar/Wind Harmer
-0.031
3146456SLIGO L269
Solar/Wind Harmer
0.912
316018AA1-139 ULT2
Solar/Wind Harmer
0.661
316017AA1-139 ULT1
Solar/Wind Harmer
0.625
316339AD2-160 GEN
Solar/Wind Harmer
0.521
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.529
3142366NRTHEST
Adder
0.195
3150691DARBY 3
Adder
4.201
3150701DARBY 4
Adder
4.191
3150681DARBY 2
Adder
4.186
3150671DARBY 1
Adder
4.181
966001AG1-469 GEN
Solar/Wind Helper
0.199
CPLELTFEXP_CPLE->PJM
CLTF
4.345
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.202
LAGNLTFEXP_LAGN->PJM
CLTF
1.77
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.515
TVALTFEXP_TVA->PJM
CLTF
0.864
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
0.346
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.574
LGEELTFEXP_LGEE->PJM
CLTF
0.044
WECLTFEXP_WEC->PJM
CLTF
0.016

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:185.6 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1540.49
MW Contribution:10.89
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.145
316303AF2-085
50/50
2.223
3151541CLOVER2
50/50
2.485
3151611KERR 4
50/50
0.233
3151621KERR 5
50/50
0.233
3151921BEARGRDN G2
50/50
4.54
3144293JTRSVLE
50/50
0.753
970413AG2-270 GEN
50/50
10.894
3151591KERR 2
50/50
0.233
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
4.6
316313AB2-026
Solar/Wind Harmer
0.819
316258AE1-075 C
Solar/Wind Harmer
0.737
316405AF2-144 C
Solar/Wind Harmer
0.778
3143336POWHATN
Solar/Wind Harmer
3.062
970909AG2-566 GEN
Solar/Wind Harmer
2.562
3147133PAMPLIN
Solar/Wind Harmer
-0.083
971193AH1-056 GEN
Solar/Wind Harmer
16.559
963181AG1-167 GEN
Solar/Wind Harmer
2.348
959311AF2-222 GEN
Solar/Wind Harmer
22.325
970257AG2-171 GEN
Solar/Wind Harmer
7.783
315785AD2-033 C
Solar/Wind Harmer
4.506
964241AG1-285 GEN
Solar/Wind Harmer
13.718
316131AB2-060 GEN
Solar/Wind Harmer
1.742
970221AG2-151 GEN
Solar/Wind Harmer
9.177
316478AD1-087 GEN
Solar/Wind Harmer
1.133
316486AD2-202 GEN
Solar/Wind Harmer
0.332
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.322
960061AF2-297 GEN
Solar/Wind Harmer
5.34
966621AG1-532 GEN
Solar/Wind Harmer
0.201
313506AB2-031 GEN
Solar/Wind Harmer
0.773
970917AG2-570 GEN
Solar/Wind Harmer
23.32
971683AH1-343 GEN
Solar/Wind Harmer
4.021
3150861SPRUNCD
Adder
0.375
316365GEN2_N
Solar/Wind Harmer
0.594
3156081AA2-088 GEN
Solar/Wind Harmer
2.773
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.624
961681AG1-008 GEN
Solar/Wind Harmer
6.624
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.302
316463AE2-346 GEN
Solar/Wind Harmer
0.133
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.031
316317KELFORD C
Solar/Wind Harmer
0.388
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.813
3145273HOLLAND
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
4.985
3156021HOLLOMANSOL
Solar/Wind Harmer
1.073
315839AE2-212 C
Solar/Wind Harmer
0.24
970659AG2-427 GEN
Solar/Wind Harmer
0.748
316083AB2-161 GEN
Solar/Wind Harmer
1.288
315724AD1-057 GEN
Solar/Wind Harmer
0.456
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
-0.008
3146233WITAKRS
Solar/Wind Harmer
0.164
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.488
971157AH1-035 GEN
Solar/Wind Harmer
0.978
965281AG1-393 GEN
Solar/Wind Harmer
0.977
315614AA2-178 GEN
Solar/Wind Harmer
0.842
3146376EDENTON
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316435W1029_GEN3
Solar/Wind Harmer
1.405
316320Y1-086
Solar/Wind Harmer
0.453
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.941
944581AF1-123 GEN
Solar/Wind Harmer
35.103
3151101ELIZAR3
Adder
6.351
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.801
3151171GRAVELC
Adder
0.924
3144216WINCHST
Adder
0.232
3150921YORKTN3
Adder
1.526
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.176
316499AE2-029_GEN
Solar/Wind Helper
0.517
3132273ORANGE
Solar/Wind Helper
0.028
3147666LOUISA
Solar/Wind Helper
0.31
315616AA1-038_C
Solar/Wind Helper
0.549
944601AF1-125 GEN
Solar/Wind Harmer
11.266
3151631KERR 6
50/50
0.233
3151641KERR 7
50/50
0.233
971845AH1-439 GEN
Solar/Wind Harmer
23.024
970285AG2-188 GEN
Solar/Wind Harmer
36.669
315657AE1-056 GEN
Solar/Wind Harmer
9.935
946301AF1-294 GEN
Solar/Wind Harmer
6.417
961791AG1-021 GEN
Solar/Wind Harmer
3.13
970683AG2-441 GEN
Solar/Wind Harmer
17.94
970681AG2-440 GEN
Solar/Wind Harmer
14.352
3144303KENBRDG
Solar/Wind Harmer
-0.017
971443AH1-215 GEN
Solar/Wind Harmer
4.049
316239AB2-077_GEN
Solar/Wind Harmer
0.467
316238AB2-078_GEN
Solar/Wind Harmer
0.467
316233AE1-074 FULL
Solar/Wind Harmer
0.318
971281AH1-106 GEN
Solar/Wind Harmer
1.921
971283AH1-107 GEN
Solar/Wind Harmer
1.921
316118AC1-105 GEN
Solar/Wind Harmer
0.807
270494AE1-108_GEN
Solar/Wind Harmer
2.995
970831AG2-522 GEN
Solar/Wind Harmer
5.644
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
19.408
946281AF1-292 GEN
Solar/Wind Harmer
0.222
316087AB2-174 GEN
Solar/Wind Harmer
1.385
970673AG2-436 GEN
Solar/Wind Harmer
20.177
970673AG2-436 GEN
Solar/Wind Harmer
10.216
941031AE2-094 GEN
Solar/Wind Harmer
17.883
944011AF1-069 GEN
Solar/Wind Harmer
5.603
3137643SOCKMAN
Solar/Wind Harmer
-0.038
970085AG2-068 GEN
Solar/Wind Harmer
5.805
970581AG2-369 GEN
Solar/Wind Harmer
4.993
971285AH1-108 GEN
Adder
0.613
315607AA1-063A GEN
Solar/Wind Harmer
0.911
3146043SEABORD
Solar/Wind Harmer
-0.009
315814AE2-033 C
Solar/Wind Harmer
8.189
316315AB2-025 C
Solar/Wind Harmer
0.237
970865AG2-541 GEN
Solar/Wind Harmer
3.523
965291AG1-394 GEN
Solar/Wind Harmer
0.761
315652AC1-086 GEN
Solar/Wind Harmer
9.545
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.033
3146033SCOT NK
Solar/Wind Harmer
-0.033
3145513AHOSKIE
Solar/Wind Harmer
0.072
961941AG1-037 GEN
Solar/Wind Harmer
0.062
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.449
315833AF1-017_GEN
Solar/Wind Harmer
1.494
316349AD2-085 GEN
Solar/Wind Harmer
0.7
316311AC2-079 GEN
Solar/Wind Harmer
3.968
316319Z2-044 C
Solar/Wind Harmer
0.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.583
315733AD1-074 GEN2
Solar/Wind Harmer
1.583
315735AD1-075 GEN1
Solar/Wind Harmer
0.792
315835AF2-110_GEN
Solar/Wind Harmer
0.978
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.632
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
1.92
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.209
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.142
316305AF2-043 C
Solar/Wind Harmer
0.233
313526AB2-022
Solar/Wind Harmer
0.209
319010AE1-072 C
Solar/Wind Harmer
1.562
3146406KITTY HAWK
Solar/Wind Harmer
0.006
957871AF2-081 GEN
Solar/Wind Harmer
3.86
3151081ELIZAR1
Adder
6.271
3151091ELIZAR2
Adder
6.162
3152611GOSPORTB
Adder
0.871
3152621GOSPORTC
Adder
0.739
3152601GOSPORTA
Adder
0.682
972265AH1-717 GEN
Adder
5.127
3151201GRAVEL4
Adder
4.806
3151191GRAVEL3
Adder
4.746
3151211GRAVEL5
Adder
4.746
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.121
3151931BEARGRDN S1
50/50
5.86
3151911BEARGRDN G1
50/50
4.54
3144293JTRSVLE
50/50
0.753
970119AG2-088 GEN
50/50
16.671
3151531CLOVER1
50/50
2.497
3151601KERR 3
50/50
0.233
3151581KERR 1
50/50
0.083
972003AH1-546 GEN
Solar/Wind Harmer
26.387
970937AG2-583 GEN
Solar/Wind Harmer
32.773
316322AB2-045
Solar/Wind Harmer
1.483
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.021
316336AC2-165 C
Solar/Wind Harmer
6.018
3143336POWHATN
Solar/Wind Harmer
3.603
963171AG1-166 GEN
Solar/Wind Harmer
3.13
971563AH1-280 GEN
Solar/Wind Harmer
3.13
970685AG2-442 GEN
Solar/Wind Harmer
20.093
962491AG1-098 GEN
Solar/Wind Harmer
10.981
315693AD1-088 GEN
Solar/Wind Harmer
7.922
316237AB2-079_GEN
Solar/Wind Harmer
0.467
971377AH1-170 GEN
Solar/Wind Harmer
1.835
3147623JAMES R
Solar/Wind Harmer
0.227
3143226MDLTHAN
Solar/Wind Harmer
-0.014
957481AF2-042 GEN
Solar/Wind Harmer
41.127
970401AG2-262 GEN
Solar/Wind Harmer
0.837
315687AD1-152 GEN
Solar/Wind Harmer
1.432
3143526WINTERP
Solar/Wind Harmer
-0.061
3147043LAWRENC
Adder
0.942
971065AG2-659 GEN
Solar/Wind Harmer
5.848
316129AC1-054 GEN
Solar/Wind Harmer
1.008
971795AH1-408 GEN
Solar/Wind Harmer
8.349
316003AC1-222 GEN
Solar/Wind Harmer
0.972
960081AF2-299 GEN
Solar/Wind Harmer
1.114
970919AG2-571 GEN
Solar/Wind Harmer
2.952
970087AG2-069 GEN
Solar/Wind Harmer
8.708
3145783HORNRTN
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.375
316190AA2-174 GEN
Solar/Wind Harmer
0.112
940641AE2-051 GEN
Solar/Wind Harmer
8.503
316023GEN1_S
Solar/Wind Harmer
0.594
939411AE1-173 GEN
Solar/Wind Harmer
43.657
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.775
962571AG1-106 GEN
Solar/Wind Harmer
1.22
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.723
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.219
316381AD1-082 GEN
Solar/Wind Harmer
0.728
315722AD1-056 GEN
Solar/Wind Harmer
0.83
970661AG2-428 GEN
Solar/Wind Harmer
8.41
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
1.971
3146233WITAKRS
Solar/Wind Harmer
-0.031
316093AE2-104_GEN
Solar/Wind Harmer
2.275
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.318
3130156CHOWAN
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
1.92
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.811
316246AF1-032 C
Solar/Wind Harmer
0.157
3146456SLIGO L269
Solar/Wind Harmer
-0.008
316388AE2-253 GEN
Solar/Wind Harmer
0.521
944591AF1-124 GEN
Solar/Wind Harmer
35.23
3150981CHESPKA
Adder
0.854
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
944631AF1-128 GEN
Adder
29.485
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.057
316192AB2-158 GEN
Solar/Wind Helper
0.928
3147666LOUISA
Solar/Wind Helper
0.539
3144293JTRSVLE
50/50
0.753
3144293JTRSVLE
50/50
0.634
970535AG2-341 GEN
50/50
2.237
3146776BUCKING
Solar/Wind Harmer
-0.175
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.493
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.913
963191AG1-168 GEN
Solar/Wind Harmer
2.348
971741AH1-377 GEN
Solar/Wind Harmer
28.4
316034AC1-036 C
Solar/Wind Harmer
0.386
970323AG2-213 GEN
Solar/Wind Harmer
10.377
971775AH1-396 GEN
Solar/Wind Harmer
1.478
313527AB2-043 GEN
Solar/Wind Harmer
2.568
971489AH1-241 GEN
Solar/Wind Harmer
8.713
971223AH1-071 GEN
Solar/Wind Harmer
1.756
962561AG1-105 GEN
Solar/Wind Harmer
7.471
939181AE1-148 GEN
Solar/Wind Harmer
7.446
970099AG2-077 GEN
Solar/Wind Harmer
16.451
964791AG1-342 GEN
Solar/Wind Harmer
2.74
3146843MT LREL
Solar/Wind Harmer
-0.013
3146843MT LREL
Solar/Wind Harmer
-0.013
3143526WINTERP
Solar/Wind Harmer
-0.061
970933AG2-581 GEN
Solar/Wind Harmer
10.52
972187AH1-678 GEN
Adder
2.454
972185AH1-677 GEN
Adder
4.815
316181AB2-040 GEN
Solar/Wind Harmer
1.342
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
1.047
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.088
3145783HORNRTN
Solar/Wind Harmer
0.87
3145783HORNRTN
Solar/Wind Harmer
0.272
3145783HORNRTN
Solar/Wind Harmer
0.109
316426AA2-053 GEN
Solar/Wind Harmer
0.92
3144356SAPONY
Solar/Wind Harmer
0.307
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
316274AC1-208 GEN
Solar/Wind Harmer
0.909
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.852
970657AG2-426 GEN
Solar/Wind Harmer
2.477
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.932
3146376EDENTON
Solar/Wind Harmer
0.231
3146376EDENTON
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.405
316433W1029_GEN2
Solar/Wind Harmer
1.405
316240AF1-291 C
Solar/Wind Harmer
0.233
3146386ELIZ CT
Solar/Wind Harmer
-0.008
3130086AYDLETT
Solar/Wind Harmer
-0.031
3137176SLIGO L2192
Solar/Wind Harmer
-0.031
3146456SLIGO L269
Solar/Wind Harmer
0.912
316018AA1-139 ULT2
Solar/Wind Harmer
0.661
316017AA1-139 ULT1
Solar/Wind Harmer
0.625
316339AD2-160 GEN
Solar/Wind Harmer
0.521
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.53
3142366NRTHEST
Adder
0.195
3150691DARBY 3
Adder
4.201
3150701DARBY 4
Adder
4.191
3150681DARBY 2
Adder
4.186
3150671DARBY 1
Adder
4.181
966001AG1-469 GEN
Solar/Wind Helper
0.199
CPLELTFEXP_CPLE->PJM
CLTF
4.345
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.201
LAGNLTFEXP_LAGN->PJM
CLTF
1.769
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.514
TVALTFEXP_TVA->PJM
CLTF
0.864
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
0.346
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.574
LGEELTFEXP_LGEE->PJM
CLTF
0.044
WECLTFEXP_WEC->PJM
CLTF
0.016

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:158.61 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1076.48
MW Contribution:9.66
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.881
3144293JTRSVLE
50/50
0.742
970535AG2-341 GEN
50/50
2.183
3152661PLYWOOD A
50/50
0.212
3146776BUCKING
Solar/Wind Harmer
2.017
3146776BUCKING
Solar/Wind Harmer
0.163
970301AG2-198 GEN
Solar/Wind Harmer
12.027
3147133PAMPLIN
Solar/Wind Harmer
0.279
3147133PAMPLIN
Solar/Wind Harmer
0.223
971489AH1-241 GEN
Solar/Wind Harmer
14.368
958211AF2-115 GEN
Solar/Wind Harmer
3.13
963191AG1-168 GEN
Solar/Wind Harmer
1.043
971741AH1-377 GEN
Solar/Wind Harmer
24.65
316034AC1-036 C
Solar/Wind Harmer
0.015
970323AG2-213 GEN
Solar/Wind Harmer
8.817
971775AH1-396 GEN
Solar/Wind Harmer
0.331
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
5.577
315821AE2-092 GEN
Solar/Wind Harmer
0.007
939181AE1-148 GEN
Solar/Wind Harmer
5.338
964791AG1-342 GEN
Solar/Wind Harmer
2.134
3146843MT LREL
Solar/Wind Harmer
0.111
3146843MT LREL
Solar/Wind Harmer
0.111
970099AG2-077 GEN
Solar/Wind Harmer
10.736
970933AG2-581 GEN
Solar/Wind Harmer
5.58
316181AB2-040 GEN
Solar/Wind Harmer
0.086
942751AE2-291 GEN
Solar/Wind Harmer
3.114
3145593CAROLNA
Solar/Wind Harmer
0.057
3145593CAROLNA
Solar/Wind Harmer
0.057
966811AG1-552 GEN
Solar/Wind Harmer
0.619
3145593CAROLNA
Solar/Wind Harmer
0.071
966001AG1-469 GEN
Solar/Wind Helper
0.14
3151931BEARGRDN S1
50/50
7.734
3151911BEARGRDN G1
50/50
5.993
3144293JTRSVLE
50/50
0.881
3151601KERR 3
50/50
0.215
3151581KERR 1
50/50
0.077
3151531CLOVER1
50/50
2.214
3147043LAWRENC
50/50
0.833
3151261ROARAP2
50/50
0.071
970937AG2-583 GEN
Solar/Wind Harmer
39.544
316336AC2-165 C
Solar/Wind Harmer
0.025
972003AH1-546 GEN
Solar/Wind Harmer
26.303
316322AB2-045
Solar/Wind Harmer
0.004
3146776BUCKING
Solar/Wind Harmer
0.202
3146926FARMVIL
Solar/Wind Harmer
0.234
971377AH1-170 GEN
Solar/Wind Harmer
2.874
3147623JAMES R
Solar/Wind Harmer
0.624
963171AG1-166 GEN
Solar/Wind Harmer
1.391
971563AH1-280 GEN
Solar/Wind Harmer
2.782
970685AG2-442 GEN
Solar/Wind Harmer
17.514
962491AG1-098 GEN
Solar/Wind Harmer
8.209
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
6.543
970401AG2-262 GEN
Solar/Wind Harmer
0.652
957481AF2-042 GEN
Solar/Wind Harmer
26.84
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.856
316129AC1-054 GEN
Solar/Wind Harmer
0.33
316003AC1-222 GEN
Solar/Wind Harmer
0.002
971795AH1-408 GEN
Solar/Wind Harmer
5.259
960081AF2-299 GEN
Solar/Wind Harmer
0.593
972205AH1-687 GEN
50/50
29.229
3151611KERR 4
50/50
0.215
3151621KERR 5
50/50
0.215
3151631KERR 6
50/50
0.215
3151641KERR 7
50/50
0.215
3151541CLOVER2
50/50
2.204
3151281ROARAP4
50/50
0.069
3151281ROARAP4
50/50
0.065
971845AH1-439 GEN
Solar/Wind Harmer
22.434
970285AG2-188 GEN
Solar/Wind Harmer
37.679
315657AE1-056 GEN
Solar/Wind Harmer
9.629
946301AF1-294 GEN
Solar/Wind Harmer
5.147
961791AG1-021 GEN
Solar/Wind Harmer
2.504
970683AG2-441 GEN
Solar/Wind Harmer
15.638
970681AG2-440 GEN
Solar/Wind Harmer
12.51
270494AE1-108_GEN
Solar/Wind Harmer
2.538
3144303KENBRDG
Solar/Wind Harmer
0.165
971443AH1-215 GEN
Solar/Wind Harmer
3.431
971447AH1-217 GEN
Solar/Wind Harmer
5.812
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.256
3147173SINAI
Solar/Wind Harmer
0.087
3147243WELCO
Solar/Wind Harmer
0.055
970831AG2-522 GEN
Solar/Wind Harmer
3.614
970865AG2-541 GEN
Solar/Wind Harmer
2.528
316123AC1-075 GEN
Solar/Wind Harmer
0.087
970165AG2-112 GEN
Solar/Wind Harmer
0.513
970163AG2-111 GEN
Solar/Wind Harmer
0.49
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.232
3138266HYDRAULIC
Solar/Wind Helper
0.014
3138266HYDRAULIC
Solar/Wind Helper
0.009
3151921BEARGRDN G2
50/50
5.993
3144293JTRSVLE
50/50
0.881
3151591KERR 2
50/50
0.215
970413AG2-270 GEN
50/50
9.663
3151261ROARAP2
50/50
0.069
3146776BUCKING
Solar/Wind Harmer
0.182
3146926FARMVIL
Solar/Wind Harmer
0.234
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
970909AG2-566 GEN
Solar/Wind Harmer
3.007
3147133PAMPLIN
Solar/Wind Harmer
0.876
971193AH1-056 GEN
Solar/Wind Harmer
16.999
970221AG2-151 GEN
Solar/Wind Harmer
14.368
963181AG1-167 GEN
Solar/Wind Harmer
1.043
959311AF2-222 GEN
Solar/Wind Harmer
19.082
970257AG2-171 GEN
Solar/Wind Harmer
6.613
315785AD2-033 C
Solar/Wind Harmer
1.59
964241AG1-285 GEN
Solar/Wind Harmer
11.084
316131AB2-060 GEN
Solar/Wind Harmer
0.467
316478AD1-087 GEN
Solar/Wind Harmer
0.361
316486AD2-202 GEN
Solar/Wind Harmer
0.106
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.73
3147043LAWRENC
Solar/Wind Harmer
0.052
958131AF2-107 GEN
Solar/Wind Harmer
2.449
971683AH1-343 GEN
Solar/Wind Harmer
2.857
313506AB2-031 GEN
Solar/Wind Harmer
0.184
CPLELTFEXP_CPLE->PJM
CLTF
3.067
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.792
LAGNLTFEXP_LAGN->PJM
CLTF
1.359
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.117
TVALTFEXP_TVA->PJM
CLTF
0.671
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.534
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.133
MECLTFEXP_MEC->PJM
CLTF
0.325
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.488
LGEELTFEXP_LGEE->PJM
CLTF
0.069
WECLTFEXP_WEC->PJM
CLTF
0.029

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.92 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:773.16
MW Contribution:8.8
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
21.569
316303AF2-085
50/50
1.694
3151541CLOVER2
50/50
2.007
3151611KERR 4
50/50
0.192
3151621KERR 5
50/50
0.192
3151631KERR 6
50/50
0.192
3151641KERR 7
50/50
0.192
3151281ROARAP4
50/50
0.075
3151281ROARAP4
50/50
0.07
971285AH1-108 GEN
50/50
0.486
963041AG1-153 GEN
50/50
1.59
315244AE2-183_ST
50/50
1.681
971845AH1-439 GEN
Solar/Wind Harmer
16.786
970285AG2-188 GEN
Solar/Wind Harmer
28.258
315657AE1-056 GEN
Solar/Wind Harmer
7.498
946301AF1-294 GEN
Solar/Wind Harmer
4.032
961791AG1-021 GEN
Solar/Wind Harmer
1.962
970683AG2-441 GEN
Solar/Wind Harmer
12.373
970681AG2-440 GEN
Solar/Wind Harmer
9.898
3144303KENBRDG
Solar/Wind Harmer
0.132
971443AH1-215 GEN
Solar/Wind Harmer
2.755
316239AB2-077_GEN
Solar/Wind Harmer
0.001
3151931BEARGRDN S1
50/50
5.707
3151911BEARGRDN G1
50/50
4.422
3144293JTRSVLE
50/50
0.69
970119AG2-088 GEN
50/50
12.707
3151531CLOVER1
50/50
2.017
3151601KERR 3
50/50
0.192
3151581KERR 1
50/50
0.069
3147043LAWRENC
50/50
0.8
3151261ROARAP2
50/50
0.077
3150851SPRUNCC
50/50
0.297
3151051BRUNSWICKS1
50/50
1.63
3151021BRUNSWICKG1
50/50
0.785
971451AH1-221 GEN
50/50
2.385
315243AE2-183_GT3
50/50
0.972
972003AH1-546 GEN
Solar/Wind Harmer
19.447
970937AG2-583 GEN
Solar/Wind Harmer
23.874
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.151
3146926FARMVIL
Solar/Wind Harmer
0.178
316336AC2-165 C
Solar/Wind Harmer
0.011
3143336POWHATN
Solar/Wind Harmer
4.396
963171AG1-166 GEN
Solar/Wind Harmer
1.09
971563AH1-280 GEN
Solar/Wind Harmer
2.18
970685AG2-442 GEN
Solar/Wind Harmer
13.857
962491AG1-098 GEN
Solar/Wind Harmer
7.06
971377AH1-170 GEN
Solar/Wind Harmer
1.272
3147623JAMES R
Solar/Wind Harmer
0.276
315693AD1-088 GEN
Solar/Wind Harmer
5.685
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Harmer
0.095
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Harmer
1.107
316118AC1-105 GEN
Solar/Wind Harmer
0.222
970831AG2-522 GEN
Solar/Wind Harmer
3.422
316233AE1-074 FULL
Solar/Wind Harmer
0.064
971281AH1-106 GEN
Solar/Wind Harmer
1.107
971283AH1-107 GEN
Solar/Wind Harmer
1.107
3147173SINAI
Solar/Wind Harmer
0.077
3147243WELCO
Solar/Wind Harmer
0.048
316087AB2-174 GEN
Solar/Wind Harmer
0.002
971967AH1-528 GEN
Solar/Wind Harmer
10.427
3137643SOCKMAN
Solar/Wind Harmer
0.253
970865AG2-541 GEN
Solar/Wind Harmer
2.127
315607AA1-063A GEN
Solar/Wind Harmer
0.122
3146043SEABORD
Solar/Wind Harmer
0.059
970673AG2-436 GEN
Solar/Wind Harmer
12.427
970673AG2-436 GEN
Solar/Wind Harmer
8.285
970085AG2-068 GEN
Solar/Wind Harmer
3.058
970581AG2-369 GEN
Solar/Wind Harmer
2.63
941031AE2-094 GEN
Solar/Wind Harmer
10.513
944011AF1-069 GEN
Solar/Wind Harmer
3.435
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.108
3148013FISHERV
Solar/Wind Helper
0.103
3148463FAIRFLD
Solar/Wind Helper
0.124
970401AG2-262 GEN
Solar/Wind Harmer
0.559
957481AF2-042 GEN
Solar/Wind Harmer
24.966
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.579
316129AC1-054 GEN
Solar/Wind Harmer
0.309
3143526WINTERP
Solar/Wind Harmer
0.415
971795AH1-408 GEN
Solar/Wind Harmer
5.206
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.641
3145783HORNRTN
Solar/Wind Harmer
0.061
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
2.047
970087AG2-069 GEN
Solar/Wind Harmer
4.587
316023GEN1_S
Solar/Wind Harmer
0.127
3147983MERCK5
Solar/Wind Helper
0.057
3144293JTRSVLE
50/50
0.69
3144293JTRSVLE
50/50
0.581
970535AG2-341 GEN
50/50
1.885
3152661PLYWOOD A
50/50
0.185
3151041BRUNSWICKG3
50/50
0.785
972187AH1-678 GEN
50/50
1.802
315242AE2-183_GT2
50/50
0.972
315241AE2-183_GT1
50/50
0.966
972185AH1-677 GEN
50/50
3.505
970533AG2-339 GEN
50/50
5.074
970531AG2-338 GEN
50/50
2.029
3146776BUCKING
Solar/Wind Harmer
1.508
3146776BUCKING
Solar/Wind Harmer
0.122
970301AG2-198 GEN
Solar/Wind Harmer
9.412
3147133PAMPLIN
Solar/Wind Harmer
0.217
3147133PAMPLIN
Solar/Wind Harmer
0.174
958211AF2-115 GEN
Solar/Wind Harmer
2.452
963191AG1-168 GEN
Solar/Wind Harmer
0.817
971741AH1-377 GEN
Solar/Wind Harmer
19.558
316034AC1-036 C
Solar/Wind Harmer
0.012
970323AG2-213 GEN
Solar/Wind Harmer
7.069
971775AH1-396 GEN
Solar/Wind Harmer
0.265
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971489AH1-241 GEN
Solar/Wind Harmer
6.362
962561AG1-105 GEN
Solar/Wind Harmer
4.763
939181AE1-148 GEN
Solar/Wind Harmer
4.697
971223AH1-071 GEN
Solar/Wind Harmer
1.017
964791AG1-342 GEN
Solar/Wind Harmer
1.83
3146843MT LREL
Solar/Wind Harmer
0.095
3146843MT LREL
Solar/Wind Harmer
0.095
970099AG2-077 GEN
Solar/Wind Harmer
9.986
3143526WINTERP
Solar/Wind Harmer
0.415
970933AG2-581 GEN
Solar/Wind Harmer
5.925
316181AB2-040 GEN
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.062
3145593CAROLNA
Solar/Wind Harmer
0.062
966811AG1-552 GEN
Solar/Wind Harmer
0.675
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.086
3145783HORNRTN
Solar/Wind Harmer
0.869
3145783HORNRTN
Solar/Wind Harmer
0.271
3145783HORNRTN
Solar/Wind Harmer
0.109
316426AA2-053 GEN
Solar/Wind Harmer
0.204
966001AG1-469 GEN
Solar/Wind Helper
0.174
3151921BEARGRDN G2
50/50
4.422
3144293JTRSVLE
50/50
0.69
970413AG2-270 GEN
50/50
8.802
3151591KERR 2
50/50
0.192
3151261ROARAP2
50/50
0.076
3150861SPRUNCD
50/50
0.297
3151031BRUNSWICKG2
50/50
0.785
3146776BUCKING
Solar/Wind Harmer
0.136
3146926FARMVIL
Solar/Wind Harmer
0.178
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.156
316258AE1-075 C
Solar/Wind Harmer
0.187
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.737
970909AG2-566 GEN
Solar/Wind Harmer
2.353
3147133PAMPLIN
Solar/Wind Harmer
0.682
971193AH1-056 GEN
Solar/Wind Harmer
13.238
963181AG1-167 GEN
Solar/Wind Harmer
0.817
959311AF2-222 GEN
Solar/Wind Harmer
15.236
970257AG2-171 GEN
Solar/Wind Harmer
5.302
315785AD2-033 C
Solar/Wind Harmer
1.283
964241AG1-285 GEN
Solar/Wind Harmer
9.125
316131AB2-060 GEN
Solar/Wind Harmer
0.39
970221AG2-151 GEN
Solar/Wind Harmer
6.362
316478AD1-087 GEN
Solar/Wind Harmer
0.328
316486AD2-202 GEN
Solar/Wind Harmer
0.096
3147043LAWRENC
Solar/Wind Harmer
0.05
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.274
971683AH1-343 GEN
Solar/Wind Harmer
2.442
313506AB2-031 GEN
Solar/Wind Harmer
0.2
970917AG2-570 GEN
Solar/Wind Harmer
5.117
316365GEN2_N
Solar/Wind Harmer
0.127
3148013FISHERV
Solar/Wind Helper
0.18
316499AE2-029_GEN
Solar/Wind Helper
0.518
315616AA1-038_C
Solar/Wind Helper
0.562
3132273ORANGE
Solar/Wind Helper
0.024
CPLELTFEXP_CPLE->PJM
CLTF
3.08
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.625
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.118
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.349
LAGNLTFEXP_LAGN->PJM
CLTF
0.897
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.783
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.427
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.208
NYPJM->LTFIMP_NY
CLTF
0.345

Details for 6BREMO-AG2-583 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.42 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:940.37
MW Contribution:9.55
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.503
3144293JTRSVLE
50/50
0.423
970535AG2-341 GEN
50/50
1.349
3152661PLYWOOD A
50/50
0.157
971489AH1-241 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
1.049
3146776BUCKING
Solar/Wind Harmer
0.085
315821AE2-092 GEN
Solar/Wind Harmer
0.013
970301AG2-198 GEN
Solar/Wind Harmer
7.476
971741AH1-377 GEN
Solar/Wind Harmer
16.133
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.127
958211AF2-115 GEN
Solar/Wind Harmer
1.786
963191AG1-168 GEN
Solar/Wind Harmer
0.595
316034AC1-036 C
Solar/Wind Harmer
0.009
970323AG2-213 GEN
Solar/Wind Harmer
5.145
971775AH1-396 GEN
Solar/Wind Harmer
0.193
970099AG2-077 GEN
Solar/Wind Harmer
11.665
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.768
964791AG1-342 GEN
Solar/Wind Harmer
1.475
3146843MT LREL
Solar/Wind Harmer
0.077
3146843MT LREL
Solar/Wind Harmer
0.077
939181AE1-148 GEN
Solar/Wind Harmer
3.325
3143526WINTERP
Solar/Wind Helper
1.294
316240AF1-291 C
Solar/Wind Helper
0.162
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.156
316075AC2-137 C
Solar/Wind Helper
0.172
3151931BEARGRDN S1
50/50
3.828
3151911BEARGRDN G1
50/50
2.966
3144293JTRSVLE
50/50
0.503
3151531CLOVER1
50/50
2.188
3151601KERR 3
50/50
0.135
3151581KERR 1
50/50
0.048
972003AH1-546 GEN
Solar/Wind Harmer
13.118
971377AH1-170 GEN
Solar/Wind Harmer
3.027
3147623JAMES R
Solar/Wind Harmer
0.658
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
963171AG1-166 GEN
Solar/Wind Harmer
0.794
971563AH1-280 GEN
Solar/Wind Harmer
1.587
970685AG2-442 GEN
Solar/Wind Harmer
10.089
962491AG1-098 GEN
Solar/Wind Harmer
7.03
315693AD1-088 GEN
Solar/Wind Harmer
5.777
957481AF2-042 GEN
Solar/Wind Harmer
29.163
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.003
970401AG2-262 GEN
Solar/Wind Harmer
0.451
316003AC1-222 GEN
Solar/Wind Harmer
0.002
316336AC2-165 C
Solar/Wind Helper
5.135
3143226MDLTHAN
Solar/Wind Helper
0.3
3143526WINTERP
Solar/Wind Helper
1.294
3142543TWELFTH
Solar/Wind Helper
0.014
3142416OLDCHRC
Solar/Wind Helper
0.296
3142416OLDCHRC
Solar/Wind Helper
0.113
316458AB2-190 GEN2
Solar/Wind Helper
0.639
972205AH1-687 GEN
50/50
14.467
3151541CLOVER2
50/50
2.177
3151611KERR 4
50/50
0.135
3151621KERR 5
50/50
0.135
3151631KERR 6
50/50
0.135
3151641KERR 7
50/50
0.135
971447AH1-217 GEN
Solar/Wind Harmer
8.145
971845AH1-439 GEN
Solar/Wind Harmer
11.716
970285AG2-188 GEN
Solar/Wind Harmer
19.851
270494AE1-108_GEN
Solar/Wind Harmer
2.723
315657AE1-056 GEN
Solar/Wind Harmer
5.462
946301AF1-294 GEN
Solar/Wind Harmer
2.936
961791AG1-021 GEN
Solar/Wind Harmer
1.429
970683AG2-441 GEN
Solar/Wind Harmer
9.008
970681AG2-440 GEN
Solar/Wind Harmer
7.206
3144303KENBRDG
Solar/Wind Harmer
0.096
971443AH1-215 GEN
Solar/Wind Harmer
2.005
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.188
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.069
3147243WELCO
Solar/Wind Harmer
0.043
970865AG2-541 GEN
Solar/Wind Harmer
2.13
316123AC1-075 GEN
Solar/Wind Harmer
0.077
970165AG2-112 GEN
Solar/Wind Harmer
0.459
970163AG2-111 GEN
Solar/Wind Harmer
0.438
316233AE1-074 FULL
Solar/Wind Helper
0.38
316312AB1-027
Solar/Wind Helper
0.217
316132AB2-190 GEN1
Solar/Wind Helper
0.639
3151921BEARGRDN G2
50/50
2.966
3144293JTRSVLE
50/50
0.503
970413AG2-270 GEN
50/50
9.546
966251AG1-494 GEN
50/50
1.198
3151591KERR 2
50/50
0.135
970221AG2-151 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
0.094
3146926FARMVIL
Solar/Wind Harmer
0.129
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
1.869
3147133PAMPLIN
Solar/Wind Harmer
0.497
971193AH1-056 GEN
Solar/Wind Harmer
9.642
963181AG1-167 GEN
Solar/Wind Harmer
0.595
959311AF2-222 GEN
Solar/Wind Harmer
11.09
970257AG2-171 GEN
Solar/Wind Harmer
3.859
315785AD2-033 C
Solar/Wind Harmer
0.934
958131AF2-107 GEN
Solar/Wind Harmer
2.955
316478AD1-087 GEN
Solar/Wind Harmer
0.356
316486AD2-202 GEN
Solar/Wind Harmer
0.105
964241AG1-285 GEN
Solar/Wind Harmer
6.636
316131AB2-060 GEN
Solar/Wind Harmer
0.284
3148013FISHERV
Solar/Wind Harmer
0.071
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.932
971683AH1-343 GEN
Solar/Wind Harmer
2.348
316313AB2-026
Solar/Wind Helper
1.245
316258AE1-075 C
Solar/Wind Helper
1.12
316405AF2-144 C
Solar/Wind Helper
0.933
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.709
315839AE2-212 C
Solar/Wind Helper
0.155
CPLELTFEXP_CPLE->PJM
CLTF
0.611
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.053
LAGNLTFEXP_LAGN->PJM
CLTF
1.406
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.04
TVALTFEXP_TVA->PJM
CLTF
0.731
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.581
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
1.069
SIGELTFEXP_SIGE->PJM
CLTF
0.035
NYPJM->LTFIMP_NY
CLTF
0.331
LGEELTFEXP_LGEE->PJM
CLTF
0.459
WECLTFEXP_WEC->PJM
CLTF
0.235

Details for 6BREMO-AG2-583 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.01 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:937.12
MW Contribution:9.55
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
3.828
3151911BEARGRDN G1
50/50
2.966
3144293JTRSVLE
50/50
0.503
3151531CLOVER1
50/50
2.188
3151601KERR 3
50/50
0.135
3151581KERR 1
50/50
0.048
972003AH1-546 GEN
Solar/Wind Harmer
13.118
971377AH1-170 GEN
Solar/Wind Harmer
3.027
3147623JAMES R
Solar/Wind Harmer
0.658
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
963171AG1-166 GEN
Solar/Wind Harmer
0.794
971563AH1-280 GEN
Solar/Wind Harmer
1.587
970685AG2-442 GEN
Solar/Wind Harmer
10.089
962491AG1-098 GEN
Solar/Wind Harmer
7.03
315693AD1-088 GEN
Solar/Wind Harmer
5.777
957481AF2-042 GEN
Solar/Wind Harmer
29.163
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.003
970401AG2-262 GEN
Solar/Wind Harmer
0.451
316003AC1-222 GEN
Solar/Wind Harmer
0.002
316336AC2-165 C
Solar/Wind Helper
5.135
3143226MDLTHAN
Solar/Wind Helper
0.3
3143526WINTERP
Solar/Wind Helper
1.294
3142543TWELFTH
Solar/Wind Helper
0.014
3142416OLDCHRC
Solar/Wind Helper
0.296
3142416OLDCHRC
Solar/Wind Helper
0.113
316458AB2-190 GEN2
Solar/Wind Helper
0.639
972205AH1-687 GEN
50/50
14.467
3151541CLOVER2
50/50
2.177
3151611KERR 4
50/50
0.135
3151621KERR 5
50/50
0.135
3151631KERR 6
50/50
0.135
3151641KERR 7
50/50
0.135
971447AH1-217 GEN
Solar/Wind Harmer
8.145
971845AH1-439 GEN
Solar/Wind Harmer
11.716
970285AG2-188 GEN
Solar/Wind Harmer
19.851
270494AE1-108_GEN
Solar/Wind Harmer
2.723
315657AE1-056 GEN
Solar/Wind Harmer
5.462
946301AF1-294 GEN
Solar/Wind Harmer
2.936
961791AG1-021 GEN
Solar/Wind Harmer
1.429
970683AG2-441 GEN
Solar/Wind Harmer
9.008
970681AG2-440 GEN
Solar/Wind Harmer
7.206
3144303KENBRDG
Solar/Wind Harmer
0.096
971443AH1-215 GEN
Solar/Wind Harmer
2.005
971967AH1-528 GEN
Solar/Wind Harmer
17.843
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.188
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.069
3147243WELCO
Solar/Wind Harmer
0.043
970865AG2-541 GEN
Solar/Wind Harmer
2.13
316123AC1-075 GEN
Solar/Wind Harmer
0.077
970165AG2-112 GEN
Solar/Wind Harmer
0.459
970163AG2-111 GEN
Solar/Wind Harmer
0.438
316233AE1-074 FULL
Solar/Wind Helper
0.38
316312AB1-027
Solar/Wind Helper
0.217
316132AB2-190 GEN1
Solar/Wind Helper
0.639
3144293JTRSVLE
50/50
0.503
3144293JTRSVLE
50/50
0.423
970535AG2-341 GEN
50/50
1.349
3152661PLYWOOD A
50/50
0.157
971489AH1-241 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
1.049
3146776BUCKING
Solar/Wind Harmer
0.085
315821AE2-092 GEN
Solar/Wind Harmer
0.013
970301AG2-198 GEN
Solar/Wind Harmer
7.476
971741AH1-377 GEN
Solar/Wind Harmer
16.133
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.127
958211AF2-115 GEN
Solar/Wind Harmer
1.786
963191AG1-168 GEN
Solar/Wind Harmer
0.595
316034AC1-036 C
Solar/Wind Harmer
0.009
970323AG2-213 GEN
Solar/Wind Harmer
5.145
971775AH1-396 GEN
Solar/Wind Harmer
0.193
970933AG2-581 GEN
Solar/Wind Harmer
8.922
970099AG2-077 GEN
Solar/Wind Harmer
11.665
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.768
964791AG1-342 GEN
Solar/Wind Harmer
1.475
3146843MT LREL
Solar/Wind Harmer
0.077
3146843MT LREL
Solar/Wind Harmer
0.077
939181AE1-148 GEN
Solar/Wind Harmer
3.325
3143526WINTERP
Solar/Wind Helper
1.294
316240AF1-291 C
Solar/Wind Helper
0.162
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.156
316075AC2-137 C
Solar/Wind Helper
0.172
3151921BEARGRDN G2
50/50
2.966
3144293JTRSVLE
50/50
0.503
970413AG2-270 GEN
50/50
9.546
966251AG1-494 GEN
50/50
1.198
3151591KERR 2
50/50
0.135
970221AG2-151 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
0.094
3146926FARMVIL
Solar/Wind Harmer
0.129
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
1.869
3147133PAMPLIN
Solar/Wind Harmer
0.497
971193AH1-056 GEN
Solar/Wind Harmer
9.642
963181AG1-167 GEN
Solar/Wind Harmer
0.595
959311AF2-222 GEN
Solar/Wind Harmer
11.09
970257AG2-171 GEN
Solar/Wind Harmer
3.859
315785AD2-033 C
Solar/Wind Harmer
0.934
958131AF2-107 GEN
Solar/Wind Harmer
2.955
316478AD1-087 GEN
Solar/Wind Harmer
0.356
316486AD2-202 GEN
Solar/Wind Harmer
0.105
964241AG1-285 GEN
Solar/Wind Harmer
6.636
316131AB2-060 GEN
Solar/Wind Harmer
0.284
3148013FISHERV
Solar/Wind Harmer
0.071
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.932
971683AH1-343 GEN
Solar/Wind Harmer
2.348
316313AB2-026
Solar/Wind Helper
1.245
316258AE1-075 C
Solar/Wind Helper
1.12
316405AF2-144 C
Solar/Wind Helper
0.933
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.709
315839AE2-212 C
Solar/Wind Helper
0.155
CPLELTFEXP_CPLE->PJM
CLTF
0.611
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.053
LAGNLTFEXP_LAGN->PJM
CLTF
1.406
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.04
TVALTFEXP_TVA->PJM
CLTF
0.731
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.581
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
1.069
SIGELTFEXP_SIGE->PJM
CLTF
0.035
NYPJM->LTFIMP_NY
CLTF
0.331
LGEELTFEXP_LGEE->PJM
CLTF
0.459
WECLTFEXP_WEC->PJM
CLTF
0.235

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:202.03 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1371.17
MW Contribution:10.91
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.754
3144293JTRSVLE
50/50
0.635
970535AG2-341 GEN
50/50
2.24
3152661PLYWOOD A
50/50
0.227
3151041BRUNSWICKG3
50/50
1.135
972187AH1-678 GEN
50/50
2.606
315242AE2-183_GT2
50/50
1.418
315241AE2-183_GT1
50/50
1.409
972185AH1-677 GEN
50/50
5.111
970533AG2-339 GEN
50/50
7.548
970531AG2-338 GEN
50/50
3.019
3146776BUCKING
Solar/Wind Harmer
1.571
3146776BUCKING
Solar/Wind Harmer
0.127
970301AG2-198 GEN
Solar/Wind Harmer
10.262
3147133PAMPLIN
Solar/Wind Harmer
0.236
3147133PAMPLIN
Solar/Wind Harmer
0.189
958211AF2-115 GEN
Solar/Wind Harmer
2.678
963191AG1-168 GEN
Solar/Wind Harmer
0.893
971741AH1-377 GEN
Solar/Wind Harmer
21.598
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
7.892
971775AH1-396 GEN
Solar/Wind Harmer
0.296
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971489AH1-241 GEN
Solar/Wind Harmer
7.009
971223AH1-071 GEN
Solar/Wind Harmer
1.334
962561AG1-105 GEN
Solar/Wind Harmer
5.681
939181AE1-148 GEN
Solar/Wind Harmer
5.661
970099AG2-077 GEN
Solar/Wind Harmer
12.506
964791AG1-342 GEN
Solar/Wind Harmer
2.195
3146843MT LREL
Solar/Wind Harmer
0.114
3146843MT LREL
Solar/Wind Harmer
0.114
3143526WINTERP
Solar/Wind Harmer
0.547
970933AG2-581 GEN
Solar/Wind Harmer
7.995
316181AB2-040 GEN
Solar/Wind Harmer
0.124
3145593CAROLNA
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.083
966811AG1-552 GEN
Solar/Wind Harmer
0.899
3145593CAROLNA
Solar/Wind Harmer
0.103
3145783HORNRTN
Solar/Wind Harmer
1.451
3145783HORNRTN
Solar/Wind Harmer
1.161
3145783HORNRTN
Solar/Wind Harmer
0.363
3145783HORNRTN
Solar/Wind Harmer
0.145
316426AA2-053 GEN
Solar/Wind Harmer
0.274
3144356SAPONY
Solar/Wind Harmer
0.654
972205AH1-687 GEN
50/50
22.18
316303AF2-085
50/50
2.224
3151541CLOVER2
50/50
2.487
3151611KERR 4
50/50
0.234
3151621KERR 5
50/50
0.234
3151631KERR 6
50/50
0.234
3151641KERR 7
50/50
0.234
963041AG1-153 GEN
50/50
2.299
315244AE2-183_ST
50/50
2.451
3151281ROARAP4
50/50
0.1
3151281ROARAP4
50/50
0.094
971285AH1-108 GEN
50/50
0.651
315779AE2-040
50/50
1.092
971845AH1-439 GEN
Solar/Wind Harmer
17.513
970285AG2-188 GEN
Solar/Wind Harmer
29.552
315657AE1-056 GEN
Solar/Wind Harmer
8.144
946301AF1-294 GEN
Solar/Wind Harmer
4.404
961791AG1-021 GEN
Solar/Wind Harmer
2.143
970683AG2-441 GEN
Solar/Wind Harmer
13.644
970681AG2-440 GEN
Solar/Wind Harmer
10.915
3144303KENBRDG
Solar/Wind Harmer
0.148
971443AH1-215 GEN
Solar/Wind Harmer
3.079
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316233AE1-074 FULL
Solar/Wind Harmer
0.084
971281AH1-106 GEN
Solar/Wind Harmer
1.459
971283AH1-107 GEN
Solar/Wind Harmer
1.459
316118AC1-105 GEN
Solar/Wind Harmer
0.27
270494AE1-108_GEN
Solar/Wind Harmer
1.236
970831AG2-522 GEN
Solar/Wind Harmer
4.291
3147173SINAI
Solar/Wind Harmer
0.095
3147243WELCO
Solar/Wind Harmer
0.059
971967AH1-528 GEN
Solar/Wind Harmer
14.709
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
18.242
970673AG2-436 GEN
Solar/Wind Harmer
12.162
941031AE2-094 GEN
Solar/Wind Harmer
15.639
944011AF1-069 GEN
Solar/Wind Harmer
5.11
3137643SOCKMAN
Solar/Wind Harmer
0.336
970085AG2-068 GEN
Solar/Wind Harmer
4.411
970581AG2-369 GEN
Solar/Wind Harmer
3.794
315607AA1-063A GEN
Solar/Wind Harmer
0.164
3146043SEABORD
Solar/Wind Harmer
0.08
315814AE2-033 C
Solar/Wind Harmer
6.192
316315AB2-025 C
Solar/Wind Harmer
0.063
970865AG2-541 GEN
Solar/Wind Harmer
2.68
965291AG1-394 GEN
Solar/Wind Harmer
0.339
315652AC1-086 GEN
Solar/Wind Harmer
8.307
3151931BEARGRDN S1
50/50
5.869
3151911BEARGRDN G1
50/50
4.548
3144293JTRSVLE
50/50
0.754
970119AG2-088 GEN
50/50
16.679
3151531CLOVER1
50/50
2.499
3151601KERR 3
50/50
0.234
3151581KERR 1
50/50
0.083
3147043LAWRENC
50/50
1
3151051BRUNSWICKS1
50/50
2.357
3151021BRUNSWICKG1
50/50
1.135
971451AH1-221 GEN
50/50
3.449
315243AE2-183_GT3
50/50
1.418
3151261ROARAP2
50/50
0.103
3150851SPRUNCC
50/50
0.398
3151391GASTONA
50/50
0.204
3151411GASTONB
50/50
0.204
972003AH1-546 GEN
Solar/Wind Harmer
20.039
970937AG2-583 GEN
Solar/Wind Harmer
24.928
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.157
3146926FARMVIL
Solar/Wind Harmer
0.188
316336AC2-165 C
Solar/Wind Harmer
0.012
3143336POWHATN
Solar/Wind Harmer
4.81
963171AG1-166 GEN
Solar/Wind Harmer
1.19
971563AH1-280 GEN
Solar/Wind Harmer
2.381
970685AG2-442 GEN
Solar/Wind Harmer
15.281
962491AG1-098 GEN
Solar/Wind Harmer
8.349
315693AD1-088 GEN
Solar/Wind Harmer
6.776
316237AB2-079_GEN
Solar/Wind Harmer
0.001
971377AH1-170 GEN
Solar/Wind Harmer
1.402
3147623JAMES R
Solar/Wind Harmer
0.305
3143226MDLTHAN
Solar/Wind Harmer
0.125
957481AF2-042 GEN
Solar/Wind Harmer
31.266
970401AG2-262 GEN
Solar/Wind Harmer
0.671
315687AD1-152 GEN
Solar/Wind Harmer
0.003
3143526WINTERP
Solar/Wind Harmer
0.547
971065AG2-659 GEN
Solar/Wind Harmer
4.446
316129AC1-054 GEN
Solar/Wind Harmer
0.385
971795AH1-408 GEN
Solar/Wind Harmer
6.611
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.847
970919AG2-571 GEN
Solar/Wind Harmer
2.953
970087AG2-069 GEN
Solar/Wind Harmer
6.617
3145783HORNRTN
Solar/Wind Harmer
0.082
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
6.459
316023GEN1_S
Solar/Wind Harmer
0.176
939411AE1-173 GEN
Solar/Wind Harmer
33.156
3146263WOODLND
Solar/Wind Harmer
0.076
316011AB1-132 GEN
Solar/Wind Harmer
1.373
3151921BEARGRDN G2
50/50
4.548
3144293JTRSVLE
50/50
0.754
970413AG2-270 GEN
50/50
10.906
3151591KERR 2
50/50
0.234
3151031BRUNSWICKG2
50/50
1.135
3151261ROARAP2
50/50
0.101
3150861SPRUNCD
50/50
0.398
3151391GASTONA
50/50
0.204
3151411GASTONB
50/50
0.204
3146776BUCKING
Solar/Wind Harmer
0.141
3146926FARMVIL
Solar/Wind Harmer
0.188
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
316313AB2-026
Solar/Wind Harmer
0.171
316258AE1-075 C
Solar/Wind Harmer
0.204
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.088
970909AG2-566 GEN
Solar/Wind Harmer
2.566
3147133PAMPLIN
Solar/Wind Harmer
0.741
971193AH1-056 GEN
Solar/Wind Harmer
14.378
963181AG1-167 GEN
Solar/Wind Harmer
0.893
959311AF2-222 GEN
Solar/Wind Harmer
16.945
970257AG2-171 GEN
Solar/Wind Harmer
5.919
315785AD2-033 C
Solar/Wind Harmer
1.44
964241AG1-285 GEN
Solar/Wind Harmer
10.432
316131AB2-060 GEN
Solar/Wind Harmer
0.453
970221AG2-151 GEN
Solar/Wind Harmer
7.009
316478AD1-087 GEN
Solar/Wind Harmer
0.407
316486AD2-202 GEN
Solar/Wind Harmer
0.12
3147043LAWRENC
Solar/Wind Harmer
0.063
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.061
313506AB2-031 GEN
Solar/Wind Harmer
0.265
971683AH1-343 GEN
Solar/Wind Harmer
3.059
970917AG2-570 GEN
Solar/Wind Harmer
7.384
316365GEN2_N
Solar/Wind Harmer
0.176
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
957521AF2-046 GEN
Solar/Wind Harmer
5.572
961681AG1-008 GEN
Solar/Wind Harmer
5.572
3145796HORNRTN
Solar/Wind Harmer
0.297
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316210AC1-098 GEN
Solar/Wind Harmer
0.686
316463AE2-346 GEN
Solar/Wind Harmer
0.063
316140AB2-099
Solar/Wind Harmer
0.026
962331AG1-082 GEN
Solar/Wind Harmer
0.783
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.073
316327AA2-057 GEN
Solar/Wind Harmer
0.108
3145273HOLLAND
Solar/Wind Harmer
0.054
315813AE1-149 C
Solar/Wind Harmer
3.784
3156021HOLLOMANSOL
Solar/Wind Harmer
0.322
315839AE2-212 C
Solar/Wind Harmer
0.001
315724AD1-057 GEN
Solar/Wind Harmer
0.265
970659AG2-427 GEN
Solar/Wind Harmer
0.747
316083AB2-161 GEN
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
0.07
3146233WITAKRS
Solar/Wind Harmer
0.351
3146233WITAKRS
Solar/Wind Harmer
0.048
3138543CONSLDL
Solar/Wind Harmer
0.046
315737AD1-076 GEN
Solar/Wind Harmer
0.896
971157AH1-035 GEN
Solar/Wind Harmer
0.836
965281AG1-393 GEN
Solar/Wind Harmer
0.741
315614AA2-178 GEN
Solar/Wind Harmer
0.398
3146376EDENTON
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
316435W1029_GEN3
Solar/Wind Harmer
0
316320Y1-086
Solar/Wind Harmer
0
3146456SLIGO L269
Solar/Wind Harmer
0.069
971153AH1-033 GEN
Solar/Wind Harmer
0.794
944581AF1-123 GEN
Solar/Wind Harmer
15.457
944601AF1-125 GEN
Solar/Wind Harmer
15.219
3145963POPLR C
Solar/Wind Harmer
0.069
3151101ELIZAR3
Adder
6.349
3144873MCLAUGH
Solar/Wind Harmer
0.002
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.068
971623AH1-311 GEN
Solar/Wind Harmer
0.136
3144536CHRHLND
Solar/Wind Harmer
0.01
3145933PARMELE
Solar/Wind Harmer
0.068
966801AG1-551 GEN
Solar/Wind Harmer
0.788
961601AG1-000A GEN
Solar/Wind Harmer
4.808
315773AC2-141 GEN
Solar/Wind Harmer
2.468
3146073TAR RVR
Solar/Wind Harmer
0.067
3146083TARBORO
Solar/Wind Harmer
0.067
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
3145796HORNRTN
Solar/Wind Harmer
0.238
3145796HORNRTN
Solar/Wind Harmer
0.03
3143316POE
Solar/Wind Harmer
0.292
3146033SCOT NK
Solar/Wind Harmer
0.294
3145513AHOSKIE
Solar/Wind Harmer
0.153
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.146
3145683EARLEYS
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
3146206CASHIE
Solar/Wind Harmer
0.07
970601AG2-382 GEN
Solar/Wind Harmer
2.62
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.048
316311AC2-079 GEN
Solar/Wind Harmer
2.01
316319Z2-044 C
Solar/Wind Harmer
0
315732AD1-074 GEN1
Solar/Wind Harmer
0.4
315733AD1-074 GEN2
Solar/Wind Harmer
0.4
315735AD1-075 GEN1
Solar/Wind Harmer
0.2
3130546PLYMOUTH
Solar/Wind Harmer
0.07
315835AF2-110_GEN
Solar/Wind Harmer
0.478
315816AE2-034 GEN
Solar/Wind Harmer
0.298
3130156CHOWAN
Solar/Wind Harmer
0.069
3130156CHOWAN
Solar/Wind Harmer
0.069
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3146486SUNBURY
Solar/Wind Harmer
0.069
3146486SUNBURY
Solar/Wind Harmer
0.069
316321Z2-027
Solar/Wind Harmer
0.013
3145176PASQUOTANK
Solar/Wind Harmer
0.043
3146396TANGLEW
Solar/Wind Harmer
0.19
316305AF2-043 C
Solar/Wind Harmer
0.001
313526AB2-022
Solar/Wind Harmer
0.037
3146406KITTY HAWK
Solar/Wind Harmer
0.009
319010AE1-072 C
Solar/Wind Harmer
0.346
957871AF2-081 GEN
Solar/Wind Harmer
3.419
3151081ELIZAR1
Adder
6.268
3151091ELIZAR2
Adder
6.16
3152611GOSPORTB
Adder
0.871
3152621GOSPORTC
Adder
0.739
3152601GOSPORTA
Adder
0.682
962571AG1-106 GEN
Solar/Wind Harmer
1.074
3145893MURPHYS
Solar/Wind Harmer
0.301
316283AC2-100 C
Solar/Wind Harmer
0.132
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.027
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.798
3151171GRAVELC
Adder
0.923
961611AG1-000B GEN
Solar/Wind Harmer
1.758
315778AD1-151 GEN
Solar/Wind Harmer
5.261
970129AG2-093 GEN
Solar/Wind Harmer
3.971
970133AG2-095 GEN
Solar/Wind Harmer
0.63
3144216WINCHST
Adder
0.231
3150921YORKTN3
Adder
1.525
3142946ENON
Solar/Wind Harmer
0.02
316382AG1-145 C
Solar/Wind Harmer
0
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.175
316499AE2-029_GEN
Solar/Wind Helper
0.514
3132273ORANGE
Solar/Wind Helper
0.027
315616AA1-038_C
Solar/Wind Helper
0.545
3147666LOUISA
Solar/Wind Helper
0.273
3145573BETHELC
Solar/Wind Harmer
0.067
3145573BETHELC
Solar/Wind Harmer
0.067
316420AA1-050 GEN
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
2.903
316005AA1-067
Solar/Wind Harmer
0.072
3145746EVERETS
Solar/Wind Harmer
0.267
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
970181AG2-120 GEN
Solar/Wind Harmer
0.836
971445AH1-216 GEN
Solar/Wind Harmer
4.703
972265AH1-717 GEN
Adder
5.124
3151201GRAVEL4
Adder
4.803
3151191GRAVEL3
Adder
4.742
3151211GRAVEL5
Adder
4.742
316369SG1_INVT
Solar/Wind Harmer
0.002
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
0.503
3145893MURPHYS
Solar/Wind Harmer
0.135
316274AC1-208 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
0.223
3146173TUNIS
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
315742AE1-103 GEN
Solar/Wind Harmer
0.001
970657AG2-426 GEN
Solar/Wind Harmer
2.47
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.223
3146376EDENTON
Solar/Wind Harmer
0.308
3146376EDENTON
Solar/Wind Harmer
0.308
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146386ELIZ CT
Solar/Wind Harmer
0.069
316240AF1-291 C
Solar/Wind Harmer
0.001
3130086AYDLETT
Solar/Wind Harmer
0.275
3137176SLIGO L2192
Solar/Wind Harmer
0.273
3146456SLIGO L269
Solar/Wind Harmer
1.215
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.038
316339AD2-160 GEN
Solar/Wind Harmer
0.111
3145506HICKORY
Solar/Wind Harmer
0.274
3145506HICKORY
Solar/Wind Harmer
0.165
3145506HICKORY
Solar/Wind Harmer
0.041
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.066
316036AC1-147 C
Solar/Wind Harmer
0.013
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.505
316222AC1-221 GEN
Solar/Wind Harmer
0.283
316263AC1-034 GEN
Solar/Wind Harmer
2.586
3145933PARMELE
Solar/Wind Harmer
0.135
3145933PARMELE
Solar/Wind Harmer
0.068
961601AG1-000A GEN
Solar/Wind Harmer
1.202
3145493TOT1
Solar/Wind Harmer
0.156
3145453TOT5
Solar/Wind Harmer
0.094
3145603CNETO
Solar/Wind Harmer
0.063
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.074
3142366NRTHEST
Adder
0.195
3142946ENON
Solar/Wind Harmer
0.006
3150691DARBY 3
Adder
4.195
3150701DARBY 4
Adder
4.185
3150681DARBY 2
Adder
4.18
3150671DARBY 1
Adder
4.175
942751AE2-291 GEN
Solar/Wind Harmer
3.155
966001AG1-469 GEN
Solar/Wind Helper
0.19
3145893MURPHYS
Solar/Wind Harmer
0.334
3145796HORNRTN
Solar/Wind Harmer
0.245
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316212AC1-099_GEN
Solar/Wind Harmer
0.382
3145823KELFORD
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
315722AD1-056 GEN
Solar/Wind Harmer
0.447
970659AG2-427 GEN
Solar/Wind Harmer
3.416
316381AD1-082 GEN
Solar/Wind Harmer
0.074
970661AG2-428 GEN
Solar/Wind Harmer
7.004
3146206CASHIE
Solar/Wind Harmer
0.07
971547AH1-271 GEN
Solar/Wind Harmer
1.497
3142543TWELFTH
Solar/Wind Harmer
0.007
3146233WITAKRS
Solar/Wind Harmer
0.278
316093AE2-104_GEN
Solar/Wind Harmer
1.171
3145663CRESWEL
Solar/Wind Harmer
0.194
971163AH1-040 GEN
Solar/Wind Harmer
5.558
3130156CHOWAN
Solar/Wind Harmer
0.069
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.223
3146516WINFALL
Solar/Wind Harmer
0.069
315671AE2-027_GEN
Solar/Wind Harmer
4.41
316246AF1-032 C
Solar/Wind Harmer
0.031
3146456SLIGO L269
Solar/Wind Harmer
0.069
316388AE2-253 GEN
Solar/Wind Harmer
0.215
944591AF1-124 GEN
Solar/Wind Harmer
15.512
3145963POPLR C
Solar/Wind Harmer
0.069
316174AB2-169 GEN
Solar/Wind Harmer
0.002
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.853
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.054
316359AB2-059 GEN
Solar/Wind Harmer
0.244
316049AB1-081 GEN
Solar/Wind Harmer
0.389
3142053HEARTS
Solar/Wind Harmer
0.12
316072AD1-144
Solar/Wind Harmer
0.025
3146293MARTNCO
Solar/Wind Harmer
0.063
316294AC1-161 GEN
Solar/Wind Harmer
1.171
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.067
3145493TOT1
Solar/Wind Harmer
0.3
316494AC1-189 GEN
Solar/Wind Harmer
0.227
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.267
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
961611AG1-000B GEN
Solar/Wind Harmer
3.457
971647AH1-324 GEN
Solar/Wind Harmer
2.81
971069AG2-661 GEN
Solar/Wind Harmer
1.169
316458AB2-190 GEN2
Solar/Wind Harmer
0.353
970129AG2-093 GEN
Solar/Wind Harmer
1.869
944631AF1-128 GEN
Adder
29.45
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971317AH1-138 GEN
Solar/Wind Harmer
0.439
316159AE1-175 C
Solar/Wind Harmer
0.05
3142433PROV 92
Solar/Wind Harmer
0.226
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.056
316192AB2-158 GEN
Solar/Wind Helper
0.823
3147666LOUISA
Solar/Wind Helper
0.475
316132AB2-190 GEN1
Solar/Wind Harmer
0.353
316123AC1-075 GEN
Solar/Wind Harmer
0.09
970165AG2-112 GEN
Solar/Wind Harmer
0.531
970163AG2-111 GEN
Solar/Wind Harmer
0.506
971447AH1-217 GEN
Solar/Wind Harmer
1.848
971167AH1-042 GEN
Solar/Wind Harmer
5.088
3138283WHITEMARSH
Solar/Wind Harmer
0.013
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.105
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.12
CPLELTFEXP_CPLE->PJM
CLTF
4.352
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.276
LAGNLTFEXP_LAGN->PJM
CLTF
1.781
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.535
TVALTFEXP_TVA->PJM
CLTF
0.87
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.726
MECLTFEXP_MEC->PJM
CLTF
0.354
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.579
LGEELTFEXP_LGEE->PJM
CLTF
0.048
WECLTFEXP_WEC->PJM
CLTF
0.018

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:184.71 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1533.11
MW Contribution:10.89
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.146
316303AF2-085
50/50
2.223
3151541CLOVER2
50/50
2.485
3151611KERR 4
50/50
0.233
3151621KERR 5
50/50
0.233
3151631KERR 6
50/50
0.233
3151641KERR 7
50/50
0.233
971845AH1-439 GEN
Solar/Wind Harmer
23.024
970285AG2-188 GEN
Solar/Wind Harmer
36.67
315657AE1-056 GEN
Solar/Wind Harmer
9.935
946301AF1-294 GEN
Solar/Wind Harmer
6.417
961791AG1-021 GEN
Solar/Wind Harmer
3.13
970683AG2-441 GEN
Solar/Wind Harmer
17.94
970681AG2-440 GEN
Solar/Wind Harmer
14.352
3144303KENBRDG
Solar/Wind Harmer
-0.017
971443AH1-215 GEN
Solar/Wind Harmer
4.049
316239AB2-077_GEN
Solar/Wind Harmer
0.467
316238AB2-078_GEN
Solar/Wind Harmer
0.467
316233AE1-074 FULL
Solar/Wind Harmer
0.318
971281AH1-106 GEN
Solar/Wind Harmer
1.921
971283AH1-107 GEN
Solar/Wind Harmer
1.921
316118AC1-105 GEN
Solar/Wind Harmer
0.807
270494AE1-108_GEN
Solar/Wind Harmer
2.995
970831AG2-522 GEN
Solar/Wind Harmer
5.644
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
19.409
946281AF1-292 GEN
Solar/Wind Harmer
0.222
316087AB2-174 GEN
Solar/Wind Harmer
1.385
970673AG2-436 GEN
Solar/Wind Harmer
20.177
970673AG2-436 GEN
Solar/Wind Harmer
10.216
941031AE2-094 GEN
Solar/Wind Harmer
17.883
944011AF1-069 GEN
Solar/Wind Harmer
5.603
3137643SOCKMAN
Solar/Wind Harmer
-0.038
970085AG2-068 GEN
Solar/Wind Harmer
5.805
970581AG2-369 GEN
Solar/Wind Harmer
4.993
971285AH1-108 GEN
Adder
0.613
315607AA1-063A GEN
Solar/Wind Harmer
0.911
3146043SEABORD
Solar/Wind Harmer
-0.009
315814AE2-033 C
Solar/Wind Harmer
8.189
316315AB2-025 C
Solar/Wind Harmer
0.237
3151921BEARGRDN G2
50/50
4.541
3144293JTRSVLE
50/50
0.753
970413AG2-270 GEN
50/50
10.895
3151591KERR 2
50/50
0.233
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
4.6
316313AB2-026
Solar/Wind Harmer
0.819
316258AE1-075 C
Solar/Wind Harmer
0.737
316405AF2-144 C
Solar/Wind Harmer
0.778
3143336POWHATN
Solar/Wind Harmer
3.062
970909AG2-566 GEN
Solar/Wind Harmer
2.562
3147133PAMPLIN
Solar/Wind Harmer
-0.083
971193AH1-056 GEN
Solar/Wind Harmer
16.559
963181AG1-167 GEN
Solar/Wind Harmer
2.348
959311AF2-222 GEN
Solar/Wind Harmer
22.325
970257AG2-171 GEN
Solar/Wind Harmer
7.783
315785AD2-033 C
Solar/Wind Harmer
4.506
964241AG1-285 GEN
Solar/Wind Harmer
13.718
316131AB2-060 GEN
Solar/Wind Harmer
1.742
970221AG2-151 GEN
Solar/Wind Harmer
9.178
316478AD1-087 GEN
Solar/Wind Harmer
1.133
316486AD2-202 GEN
Solar/Wind Harmer
0.332
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.322
960061AF2-297 GEN
Solar/Wind Harmer
5.34
966621AG1-532 GEN
Solar/Wind Harmer
0.201
313506AB2-031 GEN
Solar/Wind Harmer
0.773
970917AG2-570 GEN
Solar/Wind Harmer
23.32
971683AH1-343 GEN
Solar/Wind Harmer
4.021
3150861SPRUNCD
Adder
0.375
316365GEN2_N
Solar/Wind Harmer
0.594
3156081AA2-088 GEN
Solar/Wind Harmer
2.773
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.624
961681AG1-008 GEN
Solar/Wind Harmer
6.624
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.302
316463AE2-346 GEN
Solar/Wind Harmer
0.133
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.031
316317KELFORD C
Solar/Wind Harmer
0.388
3144293JTRSVLE
50/50
0.753
3144293JTRSVLE
50/50
0.634
970535AG2-341 GEN
50/50
2.238
3146776BUCKING
Solar/Wind Harmer
-0.175
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.493
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.913
963191AG1-168 GEN
Solar/Wind Harmer
2.348
971741AH1-377 GEN
Solar/Wind Harmer
28.4
316034AC1-036 C
Solar/Wind Harmer
0.386
970323AG2-213 GEN
Solar/Wind Harmer
10.377
971775AH1-396 GEN
Solar/Wind Harmer
1.478
313527AB2-043 GEN
Solar/Wind Harmer
2.568
971489AH1-241 GEN
Solar/Wind Harmer
8.713
971223AH1-071 GEN
Solar/Wind Harmer
1.756
962561AG1-105 GEN
Solar/Wind Harmer
7.471
939181AE1-148 GEN
Solar/Wind Harmer
7.446
970099AG2-077 GEN
Solar/Wind Harmer
16.451
964791AG1-342 GEN
Solar/Wind Harmer
2.74
3146843MT LREL
Solar/Wind Harmer
-0.013
3146843MT LREL
Solar/Wind Harmer
-0.013
3143526WINTERP
Solar/Wind Harmer
-0.061
970933AG2-581 GEN
Solar/Wind Harmer
10.52
972187AH1-678 GEN
Adder
2.454
972185AH1-677 GEN
Adder
4.815
316181AB2-040 GEN
Solar/Wind Harmer
1.342
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
1.047
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.088
3145783HORNRTN
Solar/Wind Harmer
0.87
3145783HORNRTN
Solar/Wind Harmer
0.272
3145783HORNRTN
Solar/Wind Harmer
0.109
316426AA2-053 GEN
Solar/Wind Harmer
0.92
3144356SAPONY
Solar/Wind Harmer
0.307
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
316274AC1-208 GEN
Solar/Wind Harmer
0.909
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.852
970657AG2-426 GEN
Solar/Wind Harmer
2.477
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.932
3146376EDENTON
Solar/Wind Harmer
0.231
3146376EDENTON
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.405
316433W1029_GEN2
Solar/Wind Harmer
1.405
316240AF1-291 C
Solar/Wind Harmer
0.233
3146386ELIZ CT
Solar/Wind Harmer
-0.008
3130086AYDLETT
Solar/Wind Harmer
-0.031
3137176SLIGO L2192
Solar/Wind Harmer
-0.031
3146456SLIGO L269
Solar/Wind Harmer
0.912
316018AA1-139 ULT2
Solar/Wind Harmer
0.661
316017AA1-139 ULT1
Solar/Wind Harmer
0.625
316339AD2-160 GEN
Solar/Wind Harmer
0.521
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.529
3142366NRTHEST
Adder
0.195
3150691DARBY 3
Adder
4.201
3150701DARBY 4
Adder
4.191
3150681DARBY 2
Adder
4.186
3150671DARBY 1
Adder
4.181
966001AG1-469 GEN
Solar/Wind Helper
0.199
970865AG2-541 GEN
Solar/Wind Harmer
3.523
965291AG1-394 GEN
Solar/Wind Harmer
0.761
315652AC1-086 GEN
Solar/Wind Harmer
9.545
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.033
3146033SCOT NK
Solar/Wind Harmer
-0.033
3145513AHOSKIE
Solar/Wind Harmer
0.072
961941AG1-037 GEN
Solar/Wind Harmer
0.062
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.449
315833AF1-017_GEN
Solar/Wind Harmer
1.494
316349AD2-085 GEN
Solar/Wind Harmer
0.7
316311AC2-079 GEN
Solar/Wind Harmer
3.968
316319Z2-044 C
Solar/Wind Harmer
0.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.583
315733AD1-074 GEN2
Solar/Wind Harmer
1.583
315735AD1-075 GEN1
Solar/Wind Harmer
0.792
315835AF2-110_GEN
Solar/Wind Harmer
0.978
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.632
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
1.92
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.209
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.142
316305AF2-043 C
Solar/Wind Harmer
0.233
313526AB2-022
Solar/Wind Harmer
0.209
319010AE1-072 C
Solar/Wind Harmer
1.562
3146406KITTY HAWK
Solar/Wind Harmer
0.006
957871AF2-081 GEN
Solar/Wind Harmer
3.86
3151081ELIZAR1
Adder
6.271
3151091ELIZAR2
Adder
6.162
3152611GOSPORTB
Adder
0.871
3151931BEARGRDN S1
50/50
5.86
3151911BEARGRDN G1
50/50
4.541
3144293JTRSVLE
50/50
0.753
970119AG2-088 GEN
50/50
16.672
3151531CLOVER1
50/50
2.497
3151601KERR 3
50/50
0.233
3151581KERR 1
50/50
0.083
972003AH1-546 GEN
Solar/Wind Harmer
26.388
970937AG2-583 GEN
Solar/Wind Harmer
32.774
316322AB2-045
Solar/Wind Harmer
1.483
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.021
316336AC2-165 C
Solar/Wind Harmer
6.018
3143336POWHATN
Solar/Wind Harmer
3.603
963171AG1-166 GEN
Solar/Wind Harmer
3.13
971563AH1-280 GEN
Solar/Wind Harmer
3.13
970685AG2-442 GEN
Solar/Wind Harmer
20.093
962491AG1-098 GEN
Solar/Wind Harmer
10.981
315693AD1-088 GEN
Solar/Wind Harmer
7.922
316237AB2-079_GEN
Solar/Wind Harmer
0.467
971377AH1-170 GEN
Solar/Wind Harmer
1.836
3147623JAMES R
Solar/Wind Harmer
0.227
3143226MDLTHAN
Solar/Wind Harmer
-0.014
957481AF2-042 GEN
Solar/Wind Harmer
41.127
970401AG2-262 GEN
Solar/Wind Harmer
0.837
315687AD1-152 GEN
Solar/Wind Harmer
1.432
3143526WINTERP
Solar/Wind Harmer
-0.061
3147043LAWRENC
Adder
0.942
971065AG2-659 GEN
Solar/Wind Harmer
5.848
316129AC1-054 GEN
Solar/Wind Harmer
1.008
971795AH1-408 GEN
Solar/Wind Harmer
8.35
316003AC1-222 GEN
Solar/Wind Harmer
0.972
960081AF2-299 GEN
Solar/Wind Harmer
1.114
970919AG2-571 GEN
Solar/Wind Harmer
2.952
970087AG2-069 GEN
Solar/Wind Harmer
8.708
3145783HORNRTN
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.375
316190AA2-174 GEN
Solar/Wind Harmer
0.112
940641AE2-051 GEN
Solar/Wind Harmer
8.503
316023GEN1_S
Solar/Wind Harmer
0.594
939411AE1-173 GEN
Solar/Wind Harmer
43.657
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.775
962571AG1-106 GEN
Solar/Wind Harmer
1.22
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.813
3145273HOLLAND
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
4.985
3156021HOLLOMANSOL
Solar/Wind Harmer
1.073
315839AE2-212 C
Solar/Wind Harmer
0.24
970659AG2-427 GEN
Solar/Wind Harmer
0.748
316083AB2-161 GEN
Solar/Wind Harmer
1.288
315724AD1-057 GEN
Solar/Wind Harmer
0.456
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
-0.008
3146233WITAKRS
Solar/Wind Harmer
0.164
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.488
971157AH1-035 GEN
Solar/Wind Harmer
0.978
965281AG1-393 GEN
Solar/Wind Harmer
0.977
315614AA2-178 GEN
Solar/Wind Harmer
0.842
3146376EDENTON
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316435W1029_GEN3
Solar/Wind Harmer
1.405
316320Y1-086
Solar/Wind Harmer
0.453
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.941
944581AF1-123 GEN
Solar/Wind Harmer
35.103
3151101ELIZAR3
Adder
6.351
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.801
3151171GRAVELC
Adder
0.924
3144216WINCHST
Adder
0.232
3150921YORKTN3
Adder
1.526
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.176
316499AE2-029_GEN
Solar/Wind Helper
0.517
3132273ORANGE
Solar/Wind Helper
0.028
3147666LOUISA
Solar/Wind Helper
0.309
315616AA1-038_C
Solar/Wind Helper
0.548
944601AF1-125 GEN
Solar/Wind Harmer
11.266
3152621GOSPORTC
Adder
0.739
3152601GOSPORTA
Adder
0.682
972265AH1-717 GEN
Adder
5.127
3151201GRAVEL4
Adder
4.806
3151191GRAVEL3
Adder
4.745
3151211GRAVEL5
Adder
4.745
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.121
316212AC1-099_GEN
Solar/Wind Harmer
0.723
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.219
316381AD1-082 GEN
Solar/Wind Harmer
0.728
315722AD1-056 GEN
Solar/Wind Harmer
0.83
970661AG2-428 GEN
Solar/Wind Harmer
8.41
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
1.971
3146233WITAKRS
Solar/Wind Harmer
-0.031
316093AE2-104_GEN
Solar/Wind Harmer
2.275
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.318
3130156CHOWAN
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
1.92
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.811
316246AF1-032 C
Solar/Wind Harmer
0.157
3146456SLIGO L269
Solar/Wind Harmer
-0.008
316388AE2-253 GEN
Solar/Wind Harmer
0.521
944591AF1-124 GEN
Solar/Wind Harmer
35.229
3150981CHESPKA
Adder
0.854
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
944631AF1-128 GEN
Adder
29.484
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.057
316192AB2-158 GEN
Solar/Wind Helper
0.927
3147666LOUISA
Solar/Wind Helper
0.538
CPLELTFEXP_CPLE->PJM
CLTF
4.345
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.202
LAGNLTFEXP_LAGN->PJM
CLTF
1.77
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.515
TVALTFEXP_TVA->PJM
CLTF
0.864
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
0.346
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.574
LGEELTFEXP_LGEE->PJM
CLTF
0.044
WECLTFEXP_WEC->PJM
CLTF
0.016

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:184.71 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1533.1
MW Contribution:10.89
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.753
3144293JTRSVLE
50/50
0.634
970535AG2-341 GEN
50/50
2.237
3146776BUCKING
Solar/Wind Harmer
-0.175
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.493
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.913
963191AG1-168 GEN
Solar/Wind Harmer
2.348
971741AH1-377 GEN
Solar/Wind Harmer
28.4
316034AC1-036 C
Solar/Wind Harmer
0.386
970323AG2-213 GEN
Solar/Wind Harmer
10.377
971775AH1-396 GEN
Solar/Wind Harmer
1.478
313527AB2-043 GEN
Solar/Wind Harmer
2.568
971489AH1-241 GEN
Solar/Wind Harmer
8.713
971223AH1-071 GEN
Solar/Wind Harmer
1.756
962561AG1-105 GEN
Solar/Wind Harmer
7.471
939181AE1-148 GEN
Solar/Wind Harmer
7.446
970099AG2-077 GEN
Solar/Wind Harmer
16.451
964791AG1-342 GEN
Solar/Wind Harmer
2.74
3146843MT LREL
Solar/Wind Harmer
-0.013
3146843MT LREL
Solar/Wind Harmer
-0.013
3143526WINTERP
Solar/Wind Harmer
-0.061
970933AG2-581 GEN
Solar/Wind Harmer
10.52
972187AH1-678 GEN
Adder
2.454
972185AH1-677 GEN
Adder
4.815
316181AB2-040 GEN
Solar/Wind Harmer
1.342
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
1.047
3145593CAROLNA
Solar/Wind Harmer
0.077
3151921BEARGRDN G2
50/50
4.54
3144293JTRSVLE
50/50
0.753
970413AG2-270 GEN
50/50
10.894
3151591KERR 2
50/50
0.233
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
4.6
316313AB2-026
Solar/Wind Harmer
0.819
316258AE1-075 C
Solar/Wind Harmer
0.737
316405AF2-144 C
Solar/Wind Harmer
0.778
3143336POWHATN
Solar/Wind Harmer
3.062
970909AG2-566 GEN
Solar/Wind Harmer
2.562
3147133PAMPLIN
Solar/Wind Harmer
-0.083
971193AH1-056 GEN
Solar/Wind Harmer
16.559
963181AG1-167 GEN
Solar/Wind Harmer
2.348
959311AF2-222 GEN
Solar/Wind Harmer
22.325
970257AG2-171 GEN
Solar/Wind Harmer
7.783
315785AD2-033 C
Solar/Wind Harmer
4.506
964241AG1-285 GEN
Solar/Wind Harmer
13.718
316131AB2-060 GEN
Solar/Wind Harmer
1.742
970221AG2-151 GEN
Solar/Wind Harmer
9.177
316478AD1-087 GEN
Solar/Wind Harmer
1.133
316486AD2-202 GEN
Solar/Wind Harmer
0.332
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.322
960061AF2-297 GEN
Solar/Wind Harmer
5.34
966621AG1-532 GEN
Solar/Wind Harmer
0.201
313506AB2-031 GEN
Solar/Wind Harmer
0.773
970917AG2-570 GEN
Solar/Wind Harmer
23.32
971683AH1-343 GEN
Solar/Wind Harmer
4.021
3150861SPRUNCD
Adder
0.375
316365GEN2_N
Solar/Wind Harmer
0.594
3156081AA2-088 GEN
Solar/Wind Harmer
2.773
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.624
961681AG1-008 GEN
Solar/Wind Harmer
6.624
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.302
316463AE2-346 GEN
Solar/Wind Harmer
0.133
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.031
316317KELFORD C
Solar/Wind Harmer
0.388
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.813
3145273HOLLAND
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
4.985
3156021HOLLOMANSOL
Solar/Wind Harmer
1.073
315839AE2-212 C
Solar/Wind Harmer
0.24
970659AG2-427 GEN
Solar/Wind Harmer
0.748
316083AB2-161 GEN
Solar/Wind Harmer
1.288
315724AD1-057 GEN
Solar/Wind Harmer
0.456
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
-0.008
3146233WITAKRS
Solar/Wind Harmer
0.164
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.488
971157AH1-035 GEN
Solar/Wind Harmer
0.978
965281AG1-393 GEN
Solar/Wind Harmer
0.977
315614AA2-178 GEN
Solar/Wind Harmer
0.842
3146376EDENTON
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
972205AH1-687 GEN
50/50
22.145
316303AF2-085
50/50
2.223
3151541CLOVER2
50/50
2.485
3151611KERR 4
50/50
0.233
3151621KERR 5
50/50
0.233
3151631KERR 6
50/50
0.233
3151641KERR 7
50/50
0.233
971845AH1-439 GEN
Solar/Wind Harmer
23.024
970285AG2-188 GEN
Solar/Wind Harmer
36.669
315657AE1-056 GEN
Solar/Wind Harmer
9.935
946301AF1-294 GEN
Solar/Wind Harmer
6.417
961791AG1-021 GEN
Solar/Wind Harmer
3.13
970683AG2-441 GEN
Solar/Wind Harmer
17.94
970681AG2-440 GEN
Solar/Wind Harmer
14.352
3144303KENBRDG
Solar/Wind Harmer
-0.017
971443AH1-215 GEN
Solar/Wind Harmer
4.049
316239AB2-077_GEN
Solar/Wind Harmer
0.467
316238AB2-078_GEN
Solar/Wind Harmer
0.467
316233AE1-074 FULL
Solar/Wind Harmer
0.318
971281AH1-106 GEN
Solar/Wind Harmer
1.921
971283AH1-107 GEN
Solar/Wind Harmer
1.921
316118AC1-105 GEN
Solar/Wind Harmer
0.807
270494AE1-108_GEN
Solar/Wind Harmer
2.995
970831AG2-522 GEN
Solar/Wind Harmer
5.644
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
19.408
946281AF1-292 GEN
Solar/Wind Harmer
0.222
316087AB2-174 GEN
Solar/Wind Harmer
1.385
970673AG2-436 GEN
Solar/Wind Harmer
20.177
970673AG2-436 GEN
Solar/Wind Harmer
10.216
941031AE2-094 GEN
Solar/Wind Harmer
17.883
944011AF1-069 GEN
Solar/Wind Harmer
5.603
3137643SOCKMAN
Solar/Wind Harmer
-0.038
970085AG2-068 GEN
Solar/Wind Harmer
5.805
970581AG2-369 GEN
Solar/Wind Harmer
4.993
971285AH1-108 GEN
Adder
0.613
315607AA1-063A GEN
Solar/Wind Harmer
0.911
3146043SEABORD
Solar/Wind Harmer
-0.009
315814AE2-033 C
Solar/Wind Harmer
8.189
316315AB2-025 C
Solar/Wind Harmer
0.237
970865AG2-541 GEN
Solar/Wind Harmer
3.523
965291AG1-394 GEN
Solar/Wind Harmer
0.761
315652AC1-086 GEN
Solar/Wind Harmer
9.545
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.033
3146033SCOT NK
Solar/Wind Harmer
-0.033
3145513AHOSKIE
Solar/Wind Harmer
0.072
961941AG1-037 GEN
Solar/Wind Harmer
0.062
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.449
315833AF1-017_GEN
Solar/Wind Harmer
1.494
316349AD2-085 GEN
Solar/Wind Harmer
0.7
316311AC2-079 GEN
Solar/Wind Harmer
3.968
316319Z2-044 C
Solar/Wind Harmer
0.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.583
315733AD1-074 GEN2
Solar/Wind Harmer
1.583
315735AD1-075 GEN1
Solar/Wind Harmer
0.792
315835AF2-110_GEN
Solar/Wind Harmer
0.978
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.632
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
1.92
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
3151931BEARGRDN S1
50/50
5.86
3151911BEARGRDN G1
50/50
4.54
3144293JTRSVLE
50/50
0.753
970119AG2-088 GEN
50/50
16.671
3151531CLOVER1
50/50
2.497
3151601KERR 3
50/50
0.233
3151581KERR 1
50/50
0.083
972003AH1-546 GEN
Solar/Wind Harmer
26.387
970937AG2-583 GEN
Solar/Wind Harmer
32.773
316322AB2-045
Solar/Wind Harmer
1.483
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.021
316336AC2-165 C
Solar/Wind Harmer
6.018
3143336POWHATN
Solar/Wind Harmer
3.603
963171AG1-166 GEN
Solar/Wind Harmer
3.13
971563AH1-280 GEN
Solar/Wind Harmer
3.13
970685AG2-442 GEN
Solar/Wind Harmer
20.093
962491AG1-098 GEN
Solar/Wind Harmer
10.981
315693AD1-088 GEN
Solar/Wind Harmer
7.922
316237AB2-079_GEN
Solar/Wind Harmer
0.467
971377AH1-170 GEN
Solar/Wind Harmer
1.835
3147623JAMES R
Solar/Wind Harmer
0.227
3143226MDLTHAN
Solar/Wind Harmer
-0.014
957481AF2-042 GEN
Solar/Wind Harmer
41.127
970401AG2-262 GEN
Solar/Wind Harmer
0.837
315687AD1-152 GEN
Solar/Wind Harmer
1.432
3143526WINTERP
Solar/Wind Harmer
-0.061
3147043LAWRENC
Adder
0.942
971065AG2-659 GEN
Solar/Wind Harmer
5.848
316129AC1-054 GEN
Solar/Wind Harmer
1.008
971795AH1-408 GEN
Solar/Wind Harmer
8.349
316003AC1-222 GEN
Solar/Wind Harmer
0.972
960081AF2-299 GEN
Solar/Wind Harmer
1.114
970919AG2-571 GEN
Solar/Wind Harmer
2.952
970087AG2-069 GEN
Solar/Wind Harmer
8.708
3145783HORNRTN
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.375
316190AA2-174 GEN
Solar/Wind Harmer
0.112
940641AE2-051 GEN
Solar/Wind Harmer
8.503
316023GEN1_S
Solar/Wind Harmer
0.594
939411AE1-173 GEN
Solar/Wind Harmer
43.657
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.775
962571AG1-106 GEN
Solar/Wind Harmer
1.22
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145783HORNRTN
Solar/Wind Harmer
1.088
3145783HORNRTN
Solar/Wind Harmer
0.87
3145783HORNRTN
Solar/Wind Harmer
0.272
3145783HORNRTN
Solar/Wind Harmer
0.109
316426AA2-053 GEN
Solar/Wind Harmer
0.92
3144356SAPONY
Solar/Wind Harmer
0.307
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
316274AC1-208 GEN
Solar/Wind Harmer
0.909
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.852
970657AG2-426 GEN
Solar/Wind Harmer
2.477
3146516WINFALL
Solar/Wind Harmer
-0.008
316435W1029_GEN3
Solar/Wind Harmer
1.405
316320Y1-086
Solar/Wind Harmer
0.453
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.941
944581AF1-123 GEN
Solar/Wind Harmer
35.103
3151101ELIZAR3
Adder
6.351
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.801
3151171GRAVELC
Adder
0.924
3144216WINCHST
Adder
0.232
3150921YORKTN3
Adder
1.526
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.176
316499AE2-029_GEN
Solar/Wind Helper
0.517
3132273ORANGE
Solar/Wind Helper
0.028
3147666LOUISA
Solar/Wind Helper
0.31
315616AA1-038_C
Solar/Wind Helper
0.549
944601AF1-125 GEN
Solar/Wind Harmer
11.266
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.932
3146376EDENTON
Solar/Wind Harmer
0.231
3146376EDENTON
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.405
316433W1029_GEN2
Solar/Wind Harmer
1.405
316240AF1-291 C
Solar/Wind Harmer
0.233
3146386ELIZ CT
Solar/Wind Harmer
-0.008
3130086AYDLETT
Solar/Wind Harmer
-0.031
3137176SLIGO L2192
Solar/Wind Harmer
-0.031
3146456SLIGO L269
Solar/Wind Harmer
0.912
316018AA1-139 ULT2
Solar/Wind Harmer
0.661
316017AA1-139 ULT1
Solar/Wind Harmer
0.625
316339AD2-160 GEN
Solar/Wind Harmer
0.521
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.53
3142366NRTHEST
Adder
0.195
3150691DARBY 3
Adder
4.201
3150701DARBY 4
Adder
4.191
3150681DARBY 2
Adder
4.186
3150671DARBY 1
Adder
4.181
966001AG1-469 GEN
Solar/Wind Helper
0.199
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.723
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.219
316381AD1-082 GEN
Solar/Wind Harmer
0.728
315722AD1-056 GEN
Solar/Wind Harmer
0.83
970661AG2-428 GEN
Solar/Wind Harmer
8.41
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
1.971
3146233WITAKRS
Solar/Wind Harmer
-0.031
316093AE2-104_GEN
Solar/Wind Harmer
2.275
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.318
3130156CHOWAN
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
1.92
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.811
316246AF1-032 C
Solar/Wind Harmer
0.157
3146456SLIGO L269
Solar/Wind Harmer
-0.008
316388AE2-253 GEN
Solar/Wind Harmer
0.521
944591AF1-124 GEN
Solar/Wind Harmer
35.23
3150981CHESPKA
Adder
0.854
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
944631AF1-128 GEN
Adder
29.485
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.057
316192AB2-158 GEN
Solar/Wind Helper
0.928
316321Z2-027
Solar/Wind Harmer
0.209
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.142
316305AF2-043 C
Solar/Wind Harmer
0.233
313526AB2-022
Solar/Wind Harmer
0.209
319010AE1-072 C
Solar/Wind Harmer
1.562
3146406KITTY HAWK
Solar/Wind Harmer
0.006
957871AF2-081 GEN
Solar/Wind Harmer
3.86
3151081ELIZAR1
Adder
6.271
3151091ELIZAR2
Adder
6.162
3152611GOSPORTB
Adder
0.871
3152621GOSPORTC
Adder
0.739
3152601GOSPORTA
Adder
0.682
972265AH1-717 GEN
Adder
5.127
3151201GRAVEL4
Adder
4.806
3151191GRAVEL3
Adder
4.746
3151211GRAVEL5
Adder
4.746
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.121
3147666LOUISA
Solar/Wind Helper
0.539
CPLELTFEXP_CPLE->PJM
CLTF
4.345
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.201
LAGNLTFEXP_LAGN->PJM
CLTF
1.769
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.514
TVALTFEXP_TVA->PJM
CLTF
0.864
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
0.346
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.574
LGEELTFEXP_LGEE->PJM
CLTF
0.044
WECLTFEXP_WEC->PJM
CLTF
0.016

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:157.52 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1069.03
MW Contribution:9.66
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.881
3151931BEARGRDN S1
50/50
7.734
3151911BEARGRDN G1
50/50
5.993
3144293JTRSVLE
50/50
0.881
3151601KERR 3
50/50
0.215
3151581KERR 1
50/50
0.077
3151531CLOVER1
50/50
2.214
3147043LAWRENC
50/50
0.833
972205AH1-687 GEN
50/50
29.229
3151611KERR 4
50/50
0.215
3151621KERR 5
50/50
0.215
3151631KERR 6
50/50
0.215
3151641KERR 7
50/50
0.215
3151541CLOVER2
50/50
2.204
3151281ROARAP4
50/50
0.069
3151281ROARAP4
50/50
0.065
971845AH1-439 GEN
Solar/Wind Harmer
22.434
970285AG2-188 GEN
Solar/Wind Harmer
37.679
3151261ROARAP2
50/50
0.071
970937AG2-583 GEN
Solar/Wind Harmer
39.544
316336AC2-165 C
Solar/Wind Harmer
0.025
972003AH1-546 GEN
Solar/Wind Harmer
26.303
316322AB2-045
Solar/Wind Harmer
0.004
3146776BUCKING
Solar/Wind Harmer
0.202
3146926FARMVIL
Solar/Wind Harmer
0.234
971377AH1-170 GEN
Solar/Wind Harmer
2.874
3147623JAMES R
Solar/Wind Harmer
0.624
963171AG1-166 GEN
Solar/Wind Harmer
1.391
971563AH1-280 GEN
Solar/Wind Harmer
2.782
970685AG2-442 GEN
Solar/Wind Harmer
17.514
962491AG1-098 GEN
Solar/Wind Harmer
8.209
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
6.543
970401AG2-262 GEN
Solar/Wind Harmer
0.652
957481AF2-042 GEN
Solar/Wind Harmer
26.84
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.856
316129AC1-054 GEN
Solar/Wind Harmer
0.33
316003AC1-222 GEN
Solar/Wind Harmer
0.002
971795AH1-408 GEN
Solar/Wind Harmer
5.259
960081AF2-299 GEN
Solar/Wind Harmer
0.593
3144293JTRSVLE
50/50
0.742
970535AG2-341 GEN
50/50
2.183
3152661PLYWOOD A
50/50
0.212
3146776BUCKING
Solar/Wind Harmer
2.017
3146776BUCKING
Solar/Wind Harmer
0.163
970301AG2-198 GEN
Solar/Wind Harmer
12.027
3147133PAMPLIN
Solar/Wind Harmer
0.279
3147133PAMPLIN
Solar/Wind Harmer
0.223
971489AH1-241 GEN
Solar/Wind Harmer
14.368
958211AF2-115 GEN
Solar/Wind Harmer
3.13
963191AG1-168 GEN
Solar/Wind Harmer
1.043
971741AH1-377 GEN
Solar/Wind Harmer
24.65
316034AC1-036 C
Solar/Wind Harmer
0.015
970323AG2-213 GEN
Solar/Wind Harmer
8.817
971775AH1-396 GEN
Solar/Wind Harmer
0.331
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
5.577
315821AE2-092 GEN
Solar/Wind Harmer
0.007
939181AE1-148 GEN
Solar/Wind Harmer
5.338
964791AG1-342 GEN
Solar/Wind Harmer
2.134
3146843MT LREL
Solar/Wind Harmer
0.111
3146843MT LREL
Solar/Wind Harmer
0.111
970099AG2-077 GEN
Solar/Wind Harmer
10.736
970933AG2-581 GEN
Solar/Wind Harmer
5.58
316181AB2-040 GEN
Solar/Wind Harmer
0.086
942751AE2-291 GEN
Solar/Wind Harmer
3.114
3145593CAROLNA
Solar/Wind Harmer
0.057
3145593CAROLNA
Solar/Wind Harmer
0.057
966811AG1-552 GEN
Solar/Wind Harmer
0.619
3145593CAROLNA
Solar/Wind Harmer
0.071
966001AG1-469 GEN
Solar/Wind Helper
0.14
315657AE1-056 GEN
Solar/Wind Harmer
9.629
946301AF1-294 GEN
Solar/Wind Harmer
5.147
961791AG1-021 GEN
Solar/Wind Harmer
2.504
970683AG2-441 GEN
Solar/Wind Harmer
15.638
970681AG2-440 GEN
Solar/Wind Harmer
12.51
270494AE1-108_GEN
Solar/Wind Harmer
2.538
3144303KENBRDG
Solar/Wind Harmer
0.165
971443AH1-215 GEN
Solar/Wind Harmer
3.431
971447AH1-217 GEN
Solar/Wind Harmer
5.812
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.256
3147173SINAI
Solar/Wind Harmer
0.087
3147243WELCO
Solar/Wind Harmer
0.055
970831AG2-522 GEN
Solar/Wind Harmer
3.614
970865AG2-541 GEN
Solar/Wind Harmer
2.528
316123AC1-075 GEN
Solar/Wind Harmer
0.087
970165AG2-112 GEN
Solar/Wind Harmer
0.513
970163AG2-111 GEN
Solar/Wind Harmer
0.49
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.232
3138266HYDRAULIC
Solar/Wind Helper
0.014
3138266HYDRAULIC
Solar/Wind Helper
0.009
3151921BEARGRDN G2
50/50
5.993
3144293JTRSVLE
50/50
0.881
3151591KERR 2
50/50
0.215
970413AG2-270 GEN
50/50
9.663
3151261ROARAP2
50/50
0.069
3146776BUCKING
Solar/Wind Harmer
0.182
3146926FARMVIL
Solar/Wind Harmer
0.234
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
970909AG2-566 GEN
Solar/Wind Harmer
3.007
3147133PAMPLIN
Solar/Wind Harmer
0.876
971193AH1-056 GEN
Solar/Wind Harmer
16.999
970221AG2-151 GEN
Solar/Wind Harmer
14.368
963181AG1-167 GEN
Solar/Wind Harmer
1.043
959311AF2-222 GEN
Solar/Wind Harmer
19.082
970257AG2-171 GEN
Solar/Wind Harmer
6.613
315785AD2-033 C
Solar/Wind Harmer
1.59
964241AG1-285 GEN
Solar/Wind Harmer
11.084
316131AB2-060 GEN
Solar/Wind Harmer
0.467
316478AD1-087 GEN
Solar/Wind Harmer
0.361
316486AD2-202 GEN
Solar/Wind Harmer
0.106
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.73
3147043LAWRENC
Solar/Wind Harmer
0.052
958131AF2-107 GEN
Solar/Wind Harmer
2.449
971683AH1-343 GEN
Solar/Wind Harmer
2.857
313506AB2-031 GEN
Solar/Wind Harmer
0.184
CPLELTFEXP_CPLE->PJM
CLTF
3.067
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.792
LAGNLTFEXP_LAGN->PJM
CLTF
1.359
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.117
TVALTFEXP_TVA->PJM
CLTF
0.671
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.534
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.133
MECLTFEXP_MEC->PJM
CLTF
0.325
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.488
LGEELTFEXP_LGEE->PJM
CLTF
0.069
WECLTFEXP_WEC->PJM
CLTF
0.029

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.86 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:765.97
MW Contribution:8.8
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
21.569
316303AF2-085
50/50
1.694
3151541CLOVER2
50/50
2.007
3151611KERR 4
50/50
0.192
3151621KERR 5
50/50
0.192
3151631KERR 6
50/50
0.192
3151641KERR 7
50/50
0.192
3151281ROARAP4
50/50
0.075
3151281ROARAP4
50/50
0.07
971285AH1-108 GEN
50/50
0.486
963041AG1-153 GEN
50/50
1.59
315244AE2-183_ST
50/50
1.681
971845AH1-439 GEN
Solar/Wind Harmer
16.786
970285AG2-188 GEN
Solar/Wind Harmer
28.258
315657AE1-056 GEN
Solar/Wind Harmer
7.498
946301AF1-294 GEN
Solar/Wind Harmer
4.032
961791AG1-021 GEN
Solar/Wind Harmer
1.962
970683AG2-441 GEN
Solar/Wind Harmer
12.373
970681AG2-440 GEN
Solar/Wind Harmer
9.898
3144303KENBRDG
Solar/Wind Harmer
0.132
971443AH1-215 GEN
Solar/Wind Harmer
2.755
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Harmer
1.107
316118AC1-105 GEN
Solar/Wind Harmer
0.222
970831AG2-522 GEN
Solar/Wind Harmer
3.422
316233AE1-074 FULL
Solar/Wind Harmer
0.064
971281AH1-106 GEN
Solar/Wind Harmer
1.107
971283AH1-107 GEN
Solar/Wind Harmer
1.107
3147173SINAI
Solar/Wind Harmer
0.077
3147243WELCO
Solar/Wind Harmer
0.048
316087AB2-174 GEN
Solar/Wind Harmer
0.002
971967AH1-528 GEN
Solar/Wind Harmer
10.427
3137643SOCKMAN
Solar/Wind Harmer
0.253
970865AG2-541 GEN
Solar/Wind Harmer
2.127
315607AA1-063A GEN
Solar/Wind Harmer
0.122
3146043SEABORD
Solar/Wind Harmer
0.059
970673AG2-436 GEN
Solar/Wind Harmer
12.427
970673AG2-436 GEN
Solar/Wind Harmer
8.285
970085AG2-068 GEN
Solar/Wind Harmer
3.058
970581AG2-369 GEN
Solar/Wind Harmer
2.63
941031AE2-094 GEN
Solar/Wind Harmer
10.513
944011AF1-069 GEN
Solar/Wind Harmer
3.435
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.108
3148013FISHERV
Solar/Wind Helper
0.103
3148463FAIRFLD
Solar/Wind Helper
0.124
3151931BEARGRDN S1
50/50
5.707
3151911BEARGRDN G1
50/50
4.422
3144293JTRSVLE
50/50
0.69
970119AG2-088 GEN
50/50
12.707
3151531CLOVER1
50/50
2.017
3151601KERR 3
50/50
0.192
3151581KERR 1
50/50
0.069
3147043LAWRENC
50/50
0.8
3151261ROARAP2
50/50
0.077
3150851SPRUNCC
50/50
0.297
3151051BRUNSWICKS1
50/50
1.63
3151021BRUNSWICKG1
50/50
0.785
971451AH1-221 GEN
50/50
2.385
315243AE2-183_GT3
50/50
0.972
972003AH1-546 GEN
Solar/Wind Harmer
19.447
970937AG2-583 GEN
Solar/Wind Harmer
23.874
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.151
3146926FARMVIL
Solar/Wind Harmer
0.178
316336AC2-165 C
Solar/Wind Harmer
0.011
3143336POWHATN
Solar/Wind Harmer
4.396
963171AG1-166 GEN
Solar/Wind Harmer
1.09
971563AH1-280 GEN
Solar/Wind Harmer
2.18
970685AG2-442 GEN
Solar/Wind Harmer
13.857
962491AG1-098 GEN
Solar/Wind Harmer
7.06
971377AH1-170 GEN
Solar/Wind Harmer
1.272
3147623JAMES R
Solar/Wind Harmer
0.276
315693AD1-088 GEN
Solar/Wind Harmer
5.685
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Harmer
0.095
970401AG2-262 GEN
Solar/Wind Harmer
0.559
957481AF2-042 GEN
Solar/Wind Harmer
24.966
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.579
316129AC1-054 GEN
Solar/Wind Harmer
0.309
3143526WINTERP
Solar/Wind Harmer
0.415
971795AH1-408 GEN
Solar/Wind Harmer
5.206
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.641
3145783HORNRTN
Solar/Wind Harmer
0.061
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
2.047
970087AG2-069 GEN
Solar/Wind Harmer
4.587
316023GEN1_S
Solar/Wind Harmer
0.127
3147983MERCK5
Solar/Wind Helper
0.057
3144293JTRSVLE
50/50
0.69
3144293JTRSVLE
50/50
0.581
970535AG2-341 GEN
50/50
1.885
3152661PLYWOOD A
50/50
0.185
3151041BRUNSWICKG3
50/50
0.785
972187AH1-678 GEN
50/50
1.802
315242AE2-183_GT2
50/50
0.972
315241AE2-183_GT1
50/50
0.966
972185AH1-677 GEN
50/50
3.505
970533AG2-339 GEN
50/50
5.074
970531AG2-338 GEN
50/50
2.029
3146776BUCKING
Solar/Wind Harmer
1.508
3146776BUCKING
Solar/Wind Harmer
0.122
970301AG2-198 GEN
Solar/Wind Harmer
9.412
3147133PAMPLIN
Solar/Wind Harmer
0.217
3147133PAMPLIN
Solar/Wind Harmer
0.174
958211AF2-115 GEN
Solar/Wind Harmer
2.452
963191AG1-168 GEN
Solar/Wind Harmer
0.817
971741AH1-377 GEN
Solar/Wind Harmer
19.558
316034AC1-036 C
Solar/Wind Harmer
0.012
970323AG2-213 GEN
Solar/Wind Harmer
7.069
971775AH1-396 GEN
Solar/Wind Harmer
0.265
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971489AH1-241 GEN
Solar/Wind Harmer
6.362
962561AG1-105 GEN
Solar/Wind Harmer
4.763
939181AE1-148 GEN
Solar/Wind Harmer
4.697
971223AH1-071 GEN
Solar/Wind Harmer
1.017
964791AG1-342 GEN
Solar/Wind Harmer
1.83
3146843MT LREL
Solar/Wind Harmer
0.095
3146843MT LREL
Solar/Wind Harmer
0.095
970099AG2-077 GEN
Solar/Wind Harmer
9.986
3143526WINTERP
Solar/Wind Harmer
0.415
970933AG2-581 GEN
Solar/Wind Harmer
5.925
316181AB2-040 GEN
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.062
3145593CAROLNA
Solar/Wind Harmer
0.062
966811AG1-552 GEN
Solar/Wind Harmer
0.675
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.086
3145783HORNRTN
Solar/Wind Harmer
0.869
3145783HORNRTN
Solar/Wind Harmer
0.271
3145783HORNRTN
Solar/Wind Harmer
0.109
316426AA2-053 GEN
Solar/Wind Harmer
0.204
966001AG1-469 GEN
Solar/Wind Helper
0.174
3151921BEARGRDN G2
50/50
4.422
3144293JTRSVLE
50/50
0.69
970413AG2-270 GEN
50/50
8.802
3151591KERR 2
50/50
0.192
3151261ROARAP2
50/50
0.076
3150861SPRUNCD
50/50
0.297
3151031BRUNSWICKG2
50/50
0.785
3146776BUCKING
Solar/Wind Harmer
0.136
3146926FARMVIL
Solar/Wind Harmer
0.178
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.156
316258AE1-075 C
Solar/Wind Harmer
0.187
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.737
970909AG2-566 GEN
Solar/Wind Harmer
2.353
3147133PAMPLIN
Solar/Wind Harmer
0.682
971193AH1-056 GEN
Solar/Wind Harmer
13.238
963181AG1-167 GEN
Solar/Wind Harmer
0.817
959311AF2-222 GEN
Solar/Wind Harmer
15.236
970257AG2-171 GEN
Solar/Wind Harmer
5.302
315785AD2-033 C
Solar/Wind Harmer
1.283
964241AG1-285 GEN
Solar/Wind Harmer
9.125
316131AB2-060 GEN
Solar/Wind Harmer
0.39
970221AG2-151 GEN
Solar/Wind Harmer
6.362
316478AD1-087 GEN
Solar/Wind Harmer
0.328
316486AD2-202 GEN
Solar/Wind Harmer
0.096
3147043LAWRENC
Solar/Wind Harmer
0.05
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.274
971683AH1-343 GEN
Solar/Wind Harmer
2.442
313506AB2-031 GEN
Solar/Wind Harmer
0.2
970917AG2-570 GEN
Solar/Wind Harmer
5.117
316365GEN2_N
Solar/Wind Harmer
0.127
3148013FISHERV
Solar/Wind Helper
0.18
316499AE2-029_GEN
Solar/Wind Helper
0.518
315616AA1-038_C
Solar/Wind Helper
0.562
3132273ORANGE
Solar/Wind Helper
0.024
CPLELTFEXP_CPLE->PJM
CLTF
3.08
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.625
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.118
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.349
LAGNLTFEXP_LAGN->PJM
CLTF
0.897
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.783
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.427
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.208
NYPJM->LTFIMP_NY
CLTF
0.345

Details for 6BRIERY-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.81 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:753.29
MW Contribution:29.36
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
971629AH1-314 GEN
50/50
5.006
962491AG1-098 GEN
Solar/Wind Harmer
22.331
315693AD1-088 GEN
Solar/Wind Harmer
18.25
957481AF2-042 GEN
Solar/Wind Harmer
90.747
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.071
316129AC1-054 GEN
Solar/Wind Harmer
0.427
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
3152661PLYWOOD A
50/50
0.346
970535AG2-341 GEN
50/50
1.993
970301AG2-198 GEN
Solar/Wind Harmer
25.388
971741AH1-377 GEN
Solar/Wind Harmer
54.138
970933AG2-581 GEN
Solar/Wind Harmer
27.859
970099AG2-077 GEN
Solar/Wind Harmer
36.299
939181AE1-148 GEN
Solar/Wind Harmer
6.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.689
316222AC1-221 GEN
Solar/Wind Harmer
0.447
942751AE2-291 GEN
Solar/Wind Harmer
5.336
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
316336AC2-165 C
Solar/Wind Helper
0.999
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
970909AG2-566 GEN
Solar/Wind Harmer
6.347
316478AD1-087 GEN
Solar/Wind Harmer
1.094
316486AD2-202 GEN
Solar/Wind Harmer
0.321
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.01
971683AH1-343 GEN
Solar/Wind Harmer
5.256
316283AC2-100 C
Solar/Wind Harmer
0.206
316131AB2-060 GEN
Solar/Wind Harmer
0.208
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
971967AH1-528 GEN
Solar/Wind Harmer
55.717
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
316118AC1-105 GEN
Solar/Wind Harmer
0.376
970865AG2-541 GEN
Solar/Wind Harmer
4.593
316123AC1-075 GEN
Solar/Wind Harmer
0.152
970165AG2-112 GEN
Solar/Wind Harmer
0.903
970163AG2-111 GEN
Solar/Wind Harmer
0.862
970831AG2-522 GEN
Solar/Wind Harmer
4.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for 6BRIERY-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:129.23 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:738.58
MW Contribution:29.36
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
0.346
970535AG2-341 GEN
50/50
1.993
970301AG2-198 GEN
Solar/Wind Harmer
25.388
971741AH1-377 GEN
Solar/Wind Harmer
54.138
970099AG2-077 GEN
Solar/Wind Harmer
36.299
939181AE1-148 GEN
Solar/Wind Harmer
6.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.689
316222AC1-221 GEN
Solar/Wind Harmer
0.447
942751AE2-291 GEN
Solar/Wind Harmer
5.336
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
971629AH1-314 GEN
50/50
5.006
962491AG1-098 GEN
Solar/Wind Harmer
22.331
315693AD1-088 GEN
Solar/Wind Harmer
18.25
957481AF2-042 GEN
Solar/Wind Harmer
90.747
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.071
316129AC1-054 GEN
Solar/Wind Harmer
0.427
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
970909AG2-566 GEN
Solar/Wind Harmer
6.347
316478AD1-087 GEN
Solar/Wind Harmer
1.094
316486AD2-202 GEN
Solar/Wind Harmer
0.321
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.01
971683AH1-343 GEN
Solar/Wind Harmer
5.256
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
316118AC1-105 GEN
Solar/Wind Harmer
0.376
970865AG2-541 GEN
Solar/Wind Harmer
4.593
316123AC1-075 GEN
Solar/Wind Harmer
0.152
970165AG2-112 GEN
Solar/Wind Harmer
0.903
970163AG2-111 GEN
Solar/Wind Harmer
0.862
970831AG2-522 GEN
Solar/Wind Harmer
4.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
316283AC2-100 C
Solar/Wind Harmer
0.206
316131AB2-060 GEN
Solar/Wind Harmer
0.208
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for 6BRIERY-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:129.16 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:902.85
MW Contribution:29.41
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.708
3151611KERR 4
50/50
0.302
3151621KERR 5
50/50
0.302
3151631KERR 6
50/50
0.302
3151641KERR 7
50/50
0.302
971967AH1-528 GEN
Solar/Wind Harmer
73.672
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.131
970865AG2-541 GEN
Solar/Wind Harmer
6.075
316123AC1-075 GEN
Solar/Wind Harmer
1.358
970165AG2-112 GEN
Solar/Wind Harmer
1.195
970163AG2-111 GEN
Solar/Wind Harmer
1.14
970831AG2-522 GEN
Solar/Wind Harmer
6.069
316239AB2-077_GEN
Solar/Wind Harmer
0.274
316238AB2-078_GEN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Harmer
1.371
270457AD2-023 GEN
Solar/Wind Harmer
0.695
270494AE1-108_GEN
Solar/Wind Helper
2.769
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3152661PLYWOOD A
50/50
0.348
970535AG2-341 GEN
50/50
2.001
970301AG2-198 GEN
Solar/Wind Harmer
33.445
971741AH1-377 GEN
Solar/Wind Harmer
71.327
970933AG2-581 GEN
Solar/Wind Harmer
36.739
970099AG2-077 GEN
Solar/Wind Harmer
47.872
939181AE1-148 GEN
Solar/Wind Harmer
8.421
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.05
962561AG1-105 GEN
Solar/Wind Harmer
7.525
316222AC1-221 GEN
Solar/Wind Harmer
1.236
942751AE2-291 GEN
Solar/Wind Harmer
7.063
313527AB2-043 GEN
Solar/Wind Harmer
1.361
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.338
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.919
970413AG2-270 GEN
50/50
29.414
3151591KERR 2
50/50
0.302
970909AG2-566 GEN
Solar/Wind Harmer
6.35
316478AD1-087 GEN
Solar/Wind Harmer
3.055
316486AD2-202 GEN
Solar/Wind Harmer
0.895
316248AF1-058 C
Solar/Wind Harmer
0.559
960061AF2-297 GEN
Solar/Wind Harmer
9.268
971683AH1-343 GEN
Solar/Wind Harmer
6.951
316283AC2-100 C
Solar/Wind Harmer
1.124
316131AB2-060 GEN
Solar/Wind Harmer
0.808
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.542
3147133PAMPLIN
Solar/Wind Helper
1.062
316313AB2-026
Solar/Wind Helper
0.243
316258AE1-075 C
Solar/Wind Helper
0.219
316405AF2-144 C
Solar/Wind Helper
0.182
3151531CLOVER1
50/50
6.74
3151601KERR 3
50/50
0.302
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.44
315693AD1-088 GEN
Solar/Wind Harmer
21.388
957481AF2-042 GEN
Solar/Wind Harmer
119.681
315687AD1-152 GEN
Solar/Wind Harmer
3.524
316003AC1-222 GEN
Solar/Wind Harmer
1.683
970401AG2-262 GEN
Solar/Wind Harmer
0.932
971065AG2-659 GEN
Solar/Wind Harmer
6.697
316129AC1-054 GEN
Solar/Wind Harmer
1.121
316237AB2-079_GEN
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Helper
0.44
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
1.003
CPLELTFEXP_CPLE->PJM
CLTF
4.232
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.165
LAGNLTFEXP_LAGN->PJM
CLTF
2.703
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.92
TVALTFEXP_TVA->PJM
CLTF
1.347
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.6
MECLTFEXP_MEC->PJM
CLTF
1.297
SIGELTFEXP_SIGE->PJM
CLTF
0.038
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.461
WECLTFEXP_WEC->PJM
CLTF
0.241

Details for 6BRIERY-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:129.12 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:902.56
MW Contribution:29.41
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
29.414
3151591KERR 2
50/50
0.302
970909AG2-566 GEN
Solar/Wind Harmer
6.35
316478AD1-087 GEN
Solar/Wind Harmer
3.055
316486AD2-202 GEN
Solar/Wind Harmer
0.895
316248AF1-058 C
Solar/Wind Harmer
0.559
960061AF2-297 GEN
Solar/Wind Harmer
9.268
971683AH1-343 GEN
Solar/Wind Harmer
6.951
316283AC2-100 C
Solar/Wind Harmer
1.124
316131AB2-060 GEN
Solar/Wind Harmer
0.808
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.542
3147133PAMPLIN
Solar/Wind Helper
1.062
3151541CLOVER2
50/50
6.708
3151611KERR 4
50/50
0.302
3151621KERR 5
50/50
0.302
3151631KERR 6
50/50
0.302
3151641KERR 7
50/50
0.302
971967AH1-528 GEN
Solar/Wind Harmer
73.672
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.131
970865AG2-541 GEN
Solar/Wind Harmer
6.075
316123AC1-075 GEN
Solar/Wind Harmer
1.358
970165AG2-112 GEN
Solar/Wind Harmer
1.195
970163AG2-111 GEN
Solar/Wind Harmer
1.14
970831AG2-522 GEN
Solar/Wind Harmer
6.069
316239AB2-077_GEN
Solar/Wind Harmer
0.274
316238AB2-078_GEN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Harmer
1.371
270457AD2-023 GEN
Solar/Wind Harmer
0.695
270494AE1-108_GEN
Solar/Wind Helper
2.769
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
316313AB2-026
Solar/Wind Helper
0.243
316258AE1-075 C
Solar/Wind Helper
0.219
316405AF2-144 C
Solar/Wind Helper
0.182
3151531CLOVER1
50/50
6.74
3151601KERR 3
50/50
0.302
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.44
315693AD1-088 GEN
Solar/Wind Harmer
21.388
957481AF2-042 GEN
Solar/Wind Harmer
119.681
315687AD1-152 GEN
Solar/Wind Harmer
3.524
316003AC1-222 GEN
Solar/Wind Harmer
1.683
970401AG2-262 GEN
Solar/Wind Harmer
0.932
971065AG2-659 GEN
Solar/Wind Harmer
6.697
316129AC1-054 GEN
Solar/Wind Harmer
1.121
316237AB2-079_GEN
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Helper
0.44
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
1.003
3152661PLYWOOD A
50/50
0.348
970535AG2-341 GEN
50/50
2.001
970301AG2-198 GEN
Solar/Wind Harmer
33.445
971741AH1-377 GEN
Solar/Wind Harmer
71.327
970933AG2-581 GEN
Solar/Wind Harmer
36.739
970099AG2-077 GEN
Solar/Wind Harmer
47.872
939181AE1-148 GEN
Solar/Wind Harmer
8.421
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.05
962561AG1-105 GEN
Solar/Wind Harmer
7.525
316222AC1-221 GEN
Solar/Wind Harmer
1.236
942751AE2-291 GEN
Solar/Wind Harmer
7.063
313527AB2-043 GEN
Solar/Wind Harmer
1.361
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.338
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.919
CPLELTFEXP_CPLE->PJM
CLTF
4.232
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.165
LAGNLTFEXP_LAGN->PJM
CLTF
2.703
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.92
TVALTFEXP_TVA->PJM
CLTF
1.347
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.6
MECLTFEXP_MEC->PJM
CLTF
1.297
SIGELTFEXP_SIGE->PJM
CLTF
0.038
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.461
WECLTFEXP_WEC->PJM
CLTF
0.241

Details for 6BRIERY-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.93 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:880.22
MW Contribution:29.36
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
970909AG2-566 GEN
Solar/Wind Harmer
6.347
316478AD1-087 GEN
Solar/Wind Harmer
3.05
316486AD2-202 GEN
Solar/Wind Harmer
0.893
316248AF1-058 C
Solar/Wind Harmer
0.556
960061AF2-297 GEN
Solar/Wind Harmer
9.23
971683AH1-343 GEN
Solar/Wind Harmer
6.92
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
971967AH1-528 GEN
Solar/Wind Harmer
73.556
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.126
970865AG2-541 GEN
Solar/Wind Harmer
6.047
316123AC1-075 GEN
Solar/Wind Harmer
1.351
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.135
316283AC2-100 C
Solar/Wind Harmer
1.112
316131AB2-060 GEN
Solar/Wind Harmer
0.803
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.403
315693AD1-088 GEN
Solar/Wind Harmer
21.359
957481AF2-042 GEN
Solar/Wind Harmer
119.484
315687AD1-152 GEN
Solar/Wind Harmer
3.515
316003AC1-222 GEN
Solar/Wind Harmer
1.676
970401AG2-262 GEN
Solar/Wind Harmer
0.928
971065AG2-659 GEN
Solar/Wind Harmer
6.677
316129AC1-054 GEN
Solar/Wind Harmer
1.118
316237AB2-079_GEN
Solar/Wind Harmer
0.273
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
3152661PLYWOOD A
50/50
0.346
970301AG2-198 GEN
Solar/Wind Harmer
33.428
971741AH1-377 GEN
Solar/Wind Harmer
71.281
970933AG2-581 GEN
Solar/Wind Harmer
36.681
970099AG2-077 GEN
Solar/Wind Harmer
47.793
939181AE1-148 GEN
Solar/Wind Harmer
8.391
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.036
962561AG1-105 GEN
Solar/Wind Harmer
7.49
316222AC1-221 GEN
Solar/Wind Harmer
1.223
942751AE2-291 GEN
Solar/Wind Harmer
7.025
313527AB2-043 GEN
Solar/Wind Harmer
1.353
3146776BUCKING
Solar/Wind Helper
2.175
970831AG2-522 GEN
Solar/Wind Harmer
6.052
316239AB2-077_GEN
Solar/Wind Harmer
0.273
316238AB2-078_GEN
Solar/Wind Harmer
0.273
270455AD2-022 GEN
Solar/Wind Harmer
1.35
270457AD2-023 GEN
Solar/Wind Harmer
0.684
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for 6BRIERY-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.97 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:838.61
MW Contribution:29.36
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.126
970865AG2-541 GEN
Solar/Wind Harmer
6.047
316123AC1-075 GEN
Solar/Wind Harmer
1.351
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.135
970831AG2-522 GEN
Solar/Wind Harmer
6.052
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.403
315693AD1-088 GEN
Solar/Wind Harmer
21.359
957481AF2-042 GEN
Solar/Wind Harmer
119.484
315687AD1-152 GEN
Solar/Wind Harmer
3.515
316003AC1-222 GEN
Solar/Wind Harmer
1.676
970401AG2-262 GEN
Solar/Wind Harmer
0.928
971065AG2-659 GEN
Solar/Wind Harmer
6.677
316129AC1-054 GEN
Solar/Wind Harmer
1.118
316237AB2-079_GEN
Solar/Wind Harmer
0.273
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
316239AB2-077_GEN
Solar/Wind Harmer
0.273
316238AB2-078_GEN
Solar/Wind Harmer
0.273
270455AD2-022 GEN
Solar/Wind Harmer
1.35
270457AD2-023 GEN
Solar/Wind Harmer
0.684
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
970909AG2-566 GEN
Solar/Wind Harmer
6.347
316478AD1-087 GEN
Solar/Wind Harmer
3.05
316486AD2-202 GEN
Solar/Wind Harmer
0.893
316248AF1-058 C
Solar/Wind Harmer
0.556
960061AF2-297 GEN
Solar/Wind Harmer
9.23
971683AH1-343 GEN
Solar/Wind Harmer
6.92
316283AC2-100 C
Solar/Wind Harmer
1.112
316131AB2-060 GEN
Solar/Wind Harmer
0.803
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
3152661PLYWOOD A
50/50
0.346
970301AG2-198 GEN
Solar/Wind Harmer
33.428
971741AH1-377 GEN
Solar/Wind Harmer
71.281
970099AG2-077 GEN
Solar/Wind Harmer
47.793
939181AE1-148 GEN
Solar/Wind Harmer
8.391
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.036
962561AG1-105 GEN
Solar/Wind Harmer
7.49
316222AC1-221 GEN
Solar/Wind Harmer
1.223
942751AE2-291 GEN
Solar/Wind Harmer
7.025
313527AB2-043 GEN
Solar/Wind Harmer
1.353
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for 6BRIERY-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.97 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:838.61
MW Contribution:29.36
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.403
315693AD1-088 GEN
Solar/Wind Harmer
21.359
957481AF2-042 GEN
Solar/Wind Harmer
119.484
315687AD1-152 GEN
Solar/Wind Harmer
3.515
316003AC1-222 GEN
Solar/Wind Harmer
1.676
970401AG2-262 GEN
Solar/Wind Harmer
0.928
971065AG2-659 GEN
Solar/Wind Harmer
6.677
316129AC1-054 GEN
Solar/Wind Harmer
1.118
316237AB2-079_GEN
Solar/Wind Harmer
0.273
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.126
970865AG2-541 GEN
Solar/Wind Harmer
6.047
316123AC1-075 GEN
Solar/Wind Harmer
1.351
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.135
970831AG2-522 GEN
Solar/Wind Harmer
6.052
316239AB2-077_GEN
Solar/Wind Harmer
0.273
316238AB2-078_GEN
Solar/Wind Harmer
0.273
270455AD2-022 GEN
Solar/Wind Harmer
1.35
270457AD2-023 GEN
Solar/Wind Harmer
0.684
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
970909AG2-566 GEN
Solar/Wind Harmer
6.347
316478AD1-087 GEN
Solar/Wind Harmer
3.05
316486AD2-202 GEN
Solar/Wind Harmer
0.893
316248AF1-058 C
Solar/Wind Harmer
0.556
960061AF2-297 GEN
Solar/Wind Harmer
9.23
971683AH1-343 GEN
Solar/Wind Harmer
6.92
316283AC2-100 C
Solar/Wind Harmer
1.112
316131AB2-060 GEN
Solar/Wind Harmer
0.803
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
3152661PLYWOOD A
50/50
0.346
970301AG2-198 GEN
Solar/Wind Harmer
33.428
971741AH1-377 GEN
Solar/Wind Harmer
71.281
970099AG2-077 GEN
Solar/Wind Harmer
47.793
939181AE1-148 GEN
Solar/Wind Harmer
8.391
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.036
962561AG1-105 GEN
Solar/Wind Harmer
7.49
316222AC1-221 GEN
Solar/Wind Harmer
1.223
942751AE2-291 GEN
Solar/Wind Harmer
7.025
313527AB2-043 GEN
Solar/Wind Harmer
1.353
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:212.98 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1488.76
MW Contribution:29.95
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.627
3152661PLYWOOD A
50/50
0.509
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.363
971741AH1-377 GEN
Solar/Wind Harmer
63.743
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.98
963191AG1-168 GEN
Solar/Wind Harmer
4.788
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.282
971775AH1-396 GEN
Solar/Wind Harmer
3.031
970933AG2-581 GEN
Solar/Wind Harmer
36.542
970099AG2-077 GEN
Solar/Wind Harmer
47.863
313527AB2-043 GEN
Solar/Wind Harmer
5.319
962561AG1-105 GEN
Solar/Wind Harmer
16.15
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.863
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.477
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.384
971563AH1-280 GEN
Solar/Wind Harmer
6.384
970685AG2-442 GEN
Solar/Wind Harmer
41.078
962491AG1-098 GEN
Solar/Wind Harmer
28.511
315693AD1-088 GEN
Solar/Wind Harmer
20.878
957481AF2-042 GEN
Solar/Wind Harmer
119.657
964791AG1-342 GEN
Solar/Wind Harmer
5.978
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.382
942751AE2-291 GEN
Solar/Wind Harmer
9.268
316222AC1-221 GEN
Solar/Wind Harmer
1.428
316181AB2-040 GEN
Solar/Wind Harmer
1.451
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.155
3151541CLOVER2
50/50
6.83
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
971845AH1-439 GEN
Solar/Wind Harmer
44.827
970285AG2-188 GEN
Solar/Wind Harmer
71.81
315657AE1-056 GEN
Solar/Wind Harmer
20.233
946301AF1-294 GEN
Solar/Wind Harmer
13.088
961791AG1-021 GEN
Solar/Wind Harmer
6.384
970683AG2-441 GEN
Solar/Wind Harmer
36.677
316237AB2-079_GEN
Solar/Wind Harmer
0.969
315687AD1-152 GEN
Solar/Wind Harmer
3.719
970681AG2-440 GEN
Solar/Wind Harmer
29.342
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.305
971967AH1-528 GEN
Solar/Wind Harmer
73.277
316239AB2-077_GEN
Solar/Wind Harmer
0.969
316238AB2-078_GEN
Solar/Wind Harmer
0.969
316118AC1-105 GEN
Solar/Wind Harmer
1.805
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.02
970831AG2-522 GEN
Solar/Wind Harmer
9.81
316123AC1-075 GEN
Solar/Wind Harmer
1.786
970165AG2-112 GEN
Solar/Wind Harmer
1.573
970163AG2-111 GEN
Solar/Wind Harmer
1.5
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.489
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.631
270457AD2-023 GEN
Solar/Wind Harmer
0.827
315607AA1-063A GEN
Solar/Wind Harmer
0.88
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.41
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.561
270494AE1-108_GEN
Solar/Wind Helper
3.67
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.067
3148013FISHERV
Solar/Wind Helper
0.064
970401AG2-262 GEN
Solar/Wind Harmer
1.826
316003AC1-222 GEN
Solar/Wind Harmer
2.228
971065AG2-659 GEN
Solar/Wind Harmer
10.772
316129AC1-054 GEN
Solar/Wind Harmer
1.807
971795AH1-408 GEN
Solar/Wind Harmer
11.365
960081AF2-299 GEN
Solar/Wind Harmer
1.184
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.962
316049AB1-081 GEN
Solar/Wind Harmer
0.77
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.712
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
970223AG2-152 GEN
Solar/Wind Harmer
5.769
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.191
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.405
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.316
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.18
3145783HORNRTN
Solar/Wind Harmer
0.944
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.888
316263AC1-034 GEN
Solar/Wind Harmer
3.343
961601AG1-000A GEN
Solar/Wind Harmer
2.724
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.041
316197AC1-042 GEN
Solar/Wind Harmer
0.789
942671AE2-283 GEN
Solar/Wind Harmer
2.125
315821AE2-092 GEN
Solar/Wind Helper
2.535
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.951
3151591KERR 2
50/50
0.482
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.336
970909AG2-566 GEN
Solar/Wind Harmer
5.575
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.721
963181AG1-167 GEN
Solar/Wind Harmer
4.788
959311AF2-222 GEN
Solar/Wind Harmer
45.74
970257AG2-171 GEN
Solar/Wind Harmer
15.961
315785AD2-033 C
Solar/Wind Harmer
9.254
964241AG1-285 GEN
Solar/Wind Harmer
28.298
316478AD1-087 GEN
Solar/Wind Harmer
3.113
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.606
316248AF1-058 C
Solar/Wind Harmer
0.74
960061AF2-297 GEN
Solar/Wind Harmer
12.278
971683AH1-343 GEN
Solar/Wind Harmer
9.189
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.301
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.773
316210AC1-098 GEN
Solar/Wind Harmer
1.19
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.758
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.392
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.405
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.318
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
3148013FISHERV
Solar/Wind Helper
0.111
CPLELTFEXP_CPLE->PJM
CLTF
5.212
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.402
LAGNLTFEXP_LAGN->PJM
CLTF
3.179
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.848
TVALTFEXP_TVA->PJM
CLTF
1.583
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.278
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.374
MECLTFEXP_MEC->PJM
CLTF
1.462
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.53
LGEELTFEXP_LGEE->PJM
CLTF
0.51
WECLTFEXP_WEC->PJM
CLTF
0.265

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:212.93 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1488.37
MW Contribution:29.95
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.83
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
971845AH1-439 GEN
Solar/Wind Harmer
44.827
970285AG2-188 GEN
Solar/Wind Harmer
71.81
315657AE1-056 GEN
Solar/Wind Harmer
20.233
946301AF1-294 GEN
Solar/Wind Harmer
13.088
961791AG1-021 GEN
Solar/Wind Harmer
6.384
970683AG2-441 GEN
Solar/Wind Harmer
36.677
970681AG2-440 GEN
Solar/Wind Harmer
29.342
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.305
971967AH1-528 GEN
Solar/Wind Harmer
73.277
316239AB2-077_GEN
Solar/Wind Harmer
0.969
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.863
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.477
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.384
971563AH1-280 GEN
Solar/Wind Harmer
6.384
970685AG2-442 GEN
Solar/Wind Harmer
41.078
962491AG1-098 GEN
Solar/Wind Harmer
28.511
315693AD1-088 GEN
Solar/Wind Harmer
20.878
957481AF2-042 GEN
Solar/Wind Harmer
119.657
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.627
3152661PLYWOOD A
50/50
0.509
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.363
971741AH1-377 GEN
Solar/Wind Harmer
63.743
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.98
963191AG1-168 GEN
Solar/Wind Harmer
4.788
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.282
971775AH1-396 GEN
Solar/Wind Harmer
3.031
970933AG2-581 GEN
Solar/Wind Harmer
36.542
970099AG2-077 GEN
Solar/Wind Harmer
47.863
313527AB2-043 GEN
Solar/Wind Harmer
5.319
962561AG1-105 GEN
Solar/Wind Harmer
16.15
964791AG1-342 GEN
Solar/Wind Harmer
5.978
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.382
942751AE2-291 GEN
Solar/Wind Harmer
9.268
316222AC1-221 GEN
Solar/Wind Harmer
1.428
316181AB2-040 GEN
Solar/Wind Harmer
1.451
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.155
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.18
3145783HORNRTN
Solar/Wind Harmer
0.944
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.888
316263AC1-034 GEN
Solar/Wind Harmer
3.343
961601AG1-000A GEN
Solar/Wind Harmer
2.724
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
316238AB2-078_GEN
Solar/Wind Harmer
0.969
316118AC1-105 GEN
Solar/Wind Harmer
1.805
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.02
970831AG2-522 GEN
Solar/Wind Harmer
9.81
316123AC1-075 GEN
Solar/Wind Harmer
1.786
970165AG2-112 GEN
Solar/Wind Harmer
1.573
970163AG2-111 GEN
Solar/Wind Harmer
1.5
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.489
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.631
270457AD2-023 GEN
Solar/Wind Harmer
0.827
315607AA1-063A GEN
Solar/Wind Harmer
0.88
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.41
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.561
270494AE1-108_GEN
Solar/Wind Helper
3.67
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.067
3148013FISHERV
Solar/Wind Helper
0.064
316237AB2-079_GEN
Solar/Wind Harmer
0.969
315687AD1-152 GEN
Solar/Wind Harmer
3.719
970401AG2-262 GEN
Solar/Wind Harmer
1.826
316003AC1-222 GEN
Solar/Wind Harmer
2.228
971065AG2-659 GEN
Solar/Wind Harmer
10.772
316129AC1-054 GEN
Solar/Wind Harmer
1.807
971795AH1-408 GEN
Solar/Wind Harmer
11.365
960081AF2-299 GEN
Solar/Wind Harmer
1.184
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.962
316049AB1-081 GEN
Solar/Wind Harmer
0.77
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.712
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
970223AG2-152 GEN
Solar/Wind Harmer
5.769
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.191
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.405
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.316
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.951
3151591KERR 2
50/50
0.482
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.336
970909AG2-566 GEN
Solar/Wind Harmer
5.575
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.721
963181AG1-167 GEN
Solar/Wind Harmer
4.788
959311AF2-222 GEN
Solar/Wind Harmer
45.74
970257AG2-171 GEN
Solar/Wind Harmer
15.961
315785AD2-033 C
Solar/Wind Harmer
9.254
964241AG1-285 GEN
Solar/Wind Harmer
28.298
316478AD1-087 GEN
Solar/Wind Harmer
3.113
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.606
316248AF1-058 C
Solar/Wind Harmer
0.74
960061AF2-297 GEN
Solar/Wind Harmer
12.278
971683AH1-343 GEN
Solar/Wind Harmer
9.189
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.301
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.773
316210AC1-098 GEN
Solar/Wind Harmer
1.19
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.758
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.392
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.405
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.318
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
3148013FISHERV
Solar/Wind Helper
0.111
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.041
316197AC1-042 GEN
Solar/Wind Harmer
0.789
942671AE2-283 GEN
Solar/Wind Harmer
2.125
315821AE2-092 GEN
Solar/Wind Helper
2.535
CPLELTFEXP_CPLE->PJM
CLTF
5.212
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.402
LAGNLTFEXP_LAGN->PJM
CLTF
3.179
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.848
TVALTFEXP_TVA->PJM
CLTF
1.583
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.278
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.374
MECLTFEXP_MEC->PJM
CLTF
1.462
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.53
LGEELTFEXP_LGEE->PJM
CLTF
0.51
WECLTFEXP_WEC->PJM
CLTF
0.265

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:209.35 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1463.37
MW Contribution:29.89
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.826
970285AG2-188 GEN
Solar/Wind Harmer
71.806
315657AE1-056 GEN
Solar/Wind Harmer
20.219
946301AF1-294 GEN
Solar/Wind Harmer
13.078
961791AG1-021 GEN
Solar/Wind Harmer
6.379
970683AG2-441 GEN
Solar/Wind Harmer
36.643
970681AG2-440 GEN
Solar/Wind Harmer
29.315
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.296
971967AH1-528 GEN
Solar/Wind Harmer
73.139
316239AB2-077_GEN
Solar/Wind Harmer
0.967
316238AB2-078_GEN
Solar/Wind Harmer
0.967
316118AC1-105 GEN
Solar/Wind Harmer
1.799
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.987
970831AG2-522 GEN
Solar/Wind Harmer
9.789
316123AC1-075 GEN
Solar/Wind Harmer
1.778
970165AG2-112 GEN
Solar/Wind Harmer
1.566
970163AG2-111 GEN
Solar/Wind Harmer
1.494
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.49
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.605
270457AD2-023 GEN
Solar/Wind Harmer
0.814
315607AA1-063A GEN
Solar/Wind Harmer
0.881
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.406
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.564
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.379
971563AH1-280 GEN
Solar/Wind Harmer
6.379
970685AG2-442 GEN
Solar/Wind Harmer
41.041
962491AG1-098 GEN
Solar/Wind Harmer
28.467
315693AD1-088 GEN
Solar/Wind Harmer
20.844
957481AF2-042 GEN
Solar/Wind Harmer
119.424
316237AB2-079_GEN
Solar/Wind Harmer
0.967
315687AD1-152 GEN
Solar/Wind Harmer
3.708
970401AG2-262 GEN
Solar/Wind Harmer
1.822
316003AC1-222 GEN
Solar/Wind Harmer
2.219
971065AG2-659 GEN
Solar/Wind Harmer
10.747
316129AC1-054 GEN
Solar/Wind Harmer
1.803
971795AH1-408 GEN
Solar/Wind Harmer
11.364
960081AF2-299 GEN
Solar/Wind Harmer
1.186
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.658
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.951
316049AB1-081 GEN
Solar/Wind Harmer
0.761
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.707
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
970223AG2-152 GEN
Solar/Wind Harmer
5.68
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.385
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.31
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.343
971741AH1-377 GEN
Solar/Wind Harmer
63.689
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.974
963191AG1-168 GEN
Solar/Wind Harmer
4.785
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.258
971775AH1-396 GEN
Solar/Wind Harmer
3.027
970933AG2-581 GEN
Solar/Wind Harmer
36.473
970099AG2-077 GEN
Solar/Wind Harmer
47.77
313527AB2-043 GEN
Solar/Wind Harmer
5.31
962561AG1-105 GEN
Solar/Wind Harmer
16.108
964791AG1-342 GEN
Solar/Wind Harmer
5.961
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.346
942751AE2-291 GEN
Solar/Wind Harmer
9.222
316222AC1-221 GEN
Solar/Wind Harmer
1.414
316181AB2-040 GEN
Solar/Wind Harmer
1.452
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.154
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.178
3145783HORNRTN
Solar/Wind Harmer
0.943
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.884
316263AC1-034 GEN
Solar/Wind Harmer
3.306
961601AG1-000A GEN
Solar/Wind Harmer
2.693
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
316217AC1-145 GEN
Solar/Wind Harmer
1.032
316197AC1-042 GEN
Solar/Wind Harmer
0.782
942671AE2-283 GEN
Solar/Wind Harmer
2.107
315821AE2-092 GEN
Solar/Wind Helper
2.531
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.331
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
-0.168
971193AH1-056 GEN
Solar/Wind Harmer
33.698
963181AG1-167 GEN
Solar/Wind Harmer
4.785
959311AF2-222 GEN
Solar/Wind Harmer
45.693
970257AG2-171 GEN
Solar/Wind Harmer
15.944
315785AD2-033 C
Solar/Wind Harmer
9.243
964241AG1-285 GEN
Solar/Wind Harmer
28.257
316478AD1-087 GEN
Solar/Wind Harmer
3.106
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.6
316248AF1-058 C
Solar/Wind Harmer
0.737
960061AF2-297 GEN
Solar/Wind Harmer
12.232
971683AH1-343 GEN
Solar/Wind Harmer
9.152
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.287
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.767
316210AC1-098 GEN
Solar/Wind Harmer
1.185
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.727
315724AD1-057 GEN
Solar/Wind Harmer
0.389
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.385
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:207.29 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:1184.7
MW Contribution:29.89
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.212
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.099
3146776BUCKING
Solar/Wind Harmer
3.045
3146776BUCKING
Solar/Wind Harmer
0.247
970301AG2-198 GEN
Solar/Wind Harmer
22.286
971741AH1-377 GEN
Solar/Wind Harmer
48.371
3147133PAMPLIN
Solar/Wind Harmer
0.479
3147133PAMPLIN
Solar/Wind Harmer
0.383
958211AF2-115 GEN
Solar/Wind Harmer
5.451
963191AG1-168 GEN
Solar/Wind Harmer
1.817
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.146
971775AH1-396 GEN
Solar/Wind Harmer
0.605
970933AG2-581 GEN
Solar/Wind Harmer
27.701
970099AG2-077 GEN
Solar/Wind Harmer
36.281
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.234
964791AG1-342 GEN
Solar/Wind Harmer
4.769
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.655
942751AE2-291 GEN
Solar/Wind Harmer
7.004
316222AC1-221 GEN
Solar/Wind Harmer
0.516
316181AB2-040 GEN
Solar/Wind Harmer
0.134
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.99
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.571
3145783HORNRTN
Solar/Wind Harmer
1.257
3145783HORNRTN
Solar/Wind Harmer
0.393
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.283
316274AC1-208 GEN
Solar/Wind Harmer
0.379
316263AC1-034 GEN
Solar/Wind Harmer
2.385
961601AG1-000A GEN
Solar/Wind Harmer
1.084
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.103
971845AH1-439 GEN
Solar/Wind Harmer
34.045
970285AG2-188 GEN
Solar/Wind Harmer
57.782
315657AE1-056 GEN
Solar/Wind Harmer
16.55
946301AF1-294 GEN
Solar/Wind Harmer
8.963
961791AG1-021 GEN
Solar/Wind Harmer
4.361
970683AG2-441 GEN
Solar/Wind Harmer
27.831
970681AG2-440 GEN
Solar/Wind Harmer
22.264
3144303KENBRDG
Solar/Wind Harmer
0.302
971443AH1-215 GEN
Solar/Wind Harmer
6.301
971967AH1-528 GEN
Solar/Wind Harmer
55.401
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.601
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.066
970831AG2-522 GEN
Solar/Wind Harmer
7.435
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.134
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.367
315607AA1-063A GEN
Solar/Wind Harmer
0.158
3146043SEABORD
Solar/Wind Harmer
0.075
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.249
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.44
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.158
3151411GASTONB
50/50
0.158
3146776BUCKING
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Harmer
0.38
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.219
963181AG1-167 GEN
Solar/Wind Harmer
1.817
959311AF2-222 GEN
Solar/Wind Harmer
34.634
970257AG2-171 GEN
Solar/Wind Harmer
12.109
315785AD2-033 C
Solar/Wind Harmer
2.951
964241AG1-285 GEN
Solar/Wind Harmer
21.461
316478AD1-087 GEN
Solar/Wind Harmer
1.114
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.934
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.29
971683AH1-343 GEN
Solar/Wind Harmer
6.951
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.286
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.624
3146233WITAKRS
Solar/Wind Harmer
0.328
3146233WITAKRS
Solar/Wind Harmer
0.044
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.061
961601AG1-000A GEN
Solar/Wind Harmer
4.335
315724AD1-057 GEN
Solar/Wind Harmer
0.226
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.952
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.158
3151411GASTONB
50/50
0.158
316322AB2-045
Solar/Wind Harmer
0.006
3146776BUCKING
Solar/Wind Harmer
0.305
3146926FARMVIL
Solar/Wind Harmer
0.38
963171AG1-166 GEN
Solar/Wind Harmer
2.423
971563AH1-280 GEN
Solar/Wind Harmer
4.845
970685AG2-442 GEN
Solar/Wind Harmer
31.17
962491AG1-098 GEN
Solar/Wind Harmer
21.62
315693AD1-088 GEN
Solar/Wind Harmer
17.81
957481AF2-042 GEN
Solar/Wind Harmer
90.702
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.457
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.163
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
8.991
960081AF2-299 GEN
Solar/Wind Harmer
0.901
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.348
3146233WITAKRS
Solar/Wind Harmer
0.26
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
316359AB2-059 GEN
Solar/Wind Harmer
0.225
316049AB1-081 GEN
Solar/Wind Harmer
0.359
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.061
315722AD1-056 GEN
Solar/Wind Harmer
0.381
3145796HORNRTN
Solar/Wind Harmer
0.194
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.064
962571AG1-106 GEN
Solar/Wind Harmer
0.833
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.252
970223AG2-152 GEN
Solar/Wind Harmer
3.983
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.042
941801AE2-185 GEN
Solar/Wind Harmer
1.811
3145823KELFORD
Solar/Wind Harmer
0.056
316336AC2-165 C
Solar/Wind Helper
1.31
3145493TOT1
Solar/Wind Harmer
0.131
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.409
315821AE2-092 GEN
Solar/Wind Helper
2.531
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.811
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
965291AG1-394 GEN
Solar/Wind Harmer
0.251
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:204.76 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:1170.27
MW Contribution:29.89
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.952
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.158
3151411GASTONB
50/50
0.158
316322AB2-045
Solar/Wind Harmer
0.006
3146776BUCKING
Solar/Wind Harmer
0.305
3146926FARMVIL
Solar/Wind Harmer
0.38
963171AG1-166 GEN
Solar/Wind Harmer
2.423
971563AH1-280 GEN
Solar/Wind Harmer
4.845
970685AG2-442 GEN
Solar/Wind Harmer
31.17
962491AG1-098 GEN
Solar/Wind Harmer
21.62
315693AD1-088 GEN
Solar/Wind Harmer
17.81
957481AF2-042 GEN
Solar/Wind Harmer
90.702
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.457
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.163
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
8.991
960081AF2-299 GEN
Solar/Wind Harmer
0.901
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.348
3146233WITAKRS
Solar/Wind Harmer
0.26
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
316359AB2-059 GEN
Solar/Wind Harmer
0.225
316049AB1-081 GEN
Solar/Wind Harmer
0.359
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.061
315722AD1-056 GEN
Solar/Wind Harmer
0.381
3145796HORNRTN
Solar/Wind Harmer
0.194
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.064
962571AG1-106 GEN
Solar/Wind Harmer
0.833
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.252
970223AG2-152 GEN
Solar/Wind Harmer
3.983
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.042
941801AE2-185 GEN
Solar/Wind Harmer
1.811
3145823KELFORD
Solar/Wind Harmer
0.056
316336AC2-165 C
Solar/Wind Helper
1.31
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.158
3151411GASTONB
50/50
0.158
3146776BUCKING
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Harmer
0.38
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.219
963181AG1-167 GEN
Solar/Wind Harmer
1.817
959311AF2-222 GEN
Solar/Wind Harmer
34.634
970257AG2-171 GEN
Solar/Wind Harmer
12.109
315785AD2-033 C
Solar/Wind Harmer
2.951
964241AG1-285 GEN
Solar/Wind Harmer
21.461
316478AD1-087 GEN
Solar/Wind Harmer
1.114
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.934
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.29
971683AH1-343 GEN
Solar/Wind Harmer
6.951
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.286
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.624
3146233WITAKRS
Solar/Wind Harmer
0.328
3146233WITAKRS
Solar/Wind Harmer
0.044
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.103
971845AH1-439 GEN
Solar/Wind Harmer
34.045
970285AG2-188 GEN
Solar/Wind Harmer
57.782
315657AE1-056 GEN
Solar/Wind Harmer
16.55
946301AF1-294 GEN
Solar/Wind Harmer
8.963
961791AG1-021 GEN
Solar/Wind Harmer
4.361
970683AG2-441 GEN
Solar/Wind Harmer
27.831
970681AG2-440 GEN
Solar/Wind Harmer
22.264
3144303KENBRDG
Solar/Wind Harmer
0.302
971443AH1-215 GEN
Solar/Wind Harmer
6.301
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.601
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.066
970831AG2-522 GEN
Solar/Wind Harmer
7.435
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.134
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.367
315607AA1-063A GEN
Solar/Wind Harmer
0.158
3146043SEABORD
Solar/Wind Harmer
0.075
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.249
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.44
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.251
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.212
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.099
3146776BUCKING
Solar/Wind Harmer
3.045
3146776BUCKING
Solar/Wind Harmer
0.247
970301AG2-198 GEN
Solar/Wind Harmer
22.286
971741AH1-377 GEN
Solar/Wind Harmer
48.371
3147133PAMPLIN
Solar/Wind Harmer
0.479
3147133PAMPLIN
Solar/Wind Harmer
0.383
958211AF2-115 GEN
Solar/Wind Harmer
5.451
963191AG1-168 GEN
Solar/Wind Harmer
1.817
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.146
971775AH1-396 GEN
Solar/Wind Harmer
0.605
970099AG2-077 GEN
Solar/Wind Harmer
36.281
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.234
964791AG1-342 GEN
Solar/Wind Harmer
4.769
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.655
942751AE2-291 GEN
Solar/Wind Harmer
7.004
316222AC1-221 GEN
Solar/Wind Harmer
0.516
316181AB2-040 GEN
Solar/Wind Harmer
0.134
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.99
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.571
3145783HORNRTN
Solar/Wind Harmer
1.257
3145783HORNRTN
Solar/Wind Harmer
0.393
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.283
316274AC1-208 GEN
Solar/Wind Harmer
0.379
316263AC1-034 GEN
Solar/Wind Harmer
2.385
961601AG1-000A GEN
Solar/Wind Harmer
1.084
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.131
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.409
315821AE2-092 GEN
Solar/Wind Helper
2.531
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.061
961601AG1-000A GEN
Solar/Wind Harmer
4.335
315724AD1-057 GEN
Solar/Wind Harmer
0.226
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.811
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:203.45 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1422.11
MW Contribution:29.89
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.379
971563AH1-280 GEN
Solar/Wind Harmer
6.379
970685AG2-442 GEN
Solar/Wind Harmer
41.041
962491AG1-098 GEN
Solar/Wind Harmer
28.467
315693AD1-088 GEN
Solar/Wind Harmer
20.844
957481AF2-042 GEN
Solar/Wind Harmer
119.424
316237AB2-079_GEN
Solar/Wind Harmer
0.967
315687AD1-152 GEN
Solar/Wind Harmer
3.708
970401AG2-262 GEN
Solar/Wind Harmer
1.822
316003AC1-222 GEN
Solar/Wind Harmer
2.219
971065AG2-659 GEN
Solar/Wind Harmer
10.747
316129AC1-054 GEN
Solar/Wind Harmer
1.803
971795AH1-408 GEN
Solar/Wind Harmer
11.364
960081AF2-299 GEN
Solar/Wind Harmer
1.186
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.658
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.951
316049AB1-081 GEN
Solar/Wind Harmer
0.761
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.707
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
970223AG2-152 GEN
Solar/Wind Harmer
5.68
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.385
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.31
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.826
970285AG2-188 GEN
Solar/Wind Harmer
71.806
315657AE1-056 GEN
Solar/Wind Harmer
20.219
946301AF1-294 GEN
Solar/Wind Harmer
13.078
961791AG1-021 GEN
Solar/Wind Harmer
6.379
970683AG2-441 GEN
Solar/Wind Harmer
36.643
970681AG2-440 GEN
Solar/Wind Harmer
29.315
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.296
316239AB2-077_GEN
Solar/Wind Harmer
0.967
316238AB2-078_GEN
Solar/Wind Harmer
0.967
316118AC1-105 GEN
Solar/Wind Harmer
1.799
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.987
970831AG2-522 GEN
Solar/Wind Harmer
9.789
316123AC1-075 GEN
Solar/Wind Harmer
1.778
970165AG2-112 GEN
Solar/Wind Harmer
1.566
970163AG2-111 GEN
Solar/Wind Harmer
1.494
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.49
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.605
270457AD2-023 GEN
Solar/Wind Harmer
0.814
315607AA1-063A GEN
Solar/Wind Harmer
0.881
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.406
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.564
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.331
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
-0.168
971193AH1-056 GEN
Solar/Wind Harmer
33.698
963181AG1-167 GEN
Solar/Wind Harmer
4.785
959311AF2-222 GEN
Solar/Wind Harmer
45.693
970257AG2-171 GEN
Solar/Wind Harmer
15.944
315785AD2-033 C
Solar/Wind Harmer
9.243
964241AG1-285 GEN
Solar/Wind Harmer
28.257
316478AD1-087 GEN
Solar/Wind Harmer
3.106
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.6
316248AF1-058 C
Solar/Wind Harmer
0.737
960061AF2-297 GEN
Solar/Wind Harmer
12.232
971683AH1-343 GEN
Solar/Wind Harmer
9.152
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.287
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.767
316210AC1-098 GEN
Solar/Wind Harmer
1.185
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.727
315724AD1-057 GEN
Solar/Wind Harmer
0.389
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.385
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.343
971741AH1-377 GEN
Solar/Wind Harmer
63.689
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.974
963191AG1-168 GEN
Solar/Wind Harmer
4.785
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.258
971775AH1-396 GEN
Solar/Wind Harmer
3.027
970099AG2-077 GEN
Solar/Wind Harmer
47.77
313527AB2-043 GEN
Solar/Wind Harmer
5.31
962561AG1-105 GEN
Solar/Wind Harmer
16.108
964791AG1-342 GEN
Solar/Wind Harmer
5.961
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.346
942751AE2-291 GEN
Solar/Wind Harmer
9.222
316222AC1-221 GEN
Solar/Wind Harmer
1.414
316181AB2-040 GEN
Solar/Wind Harmer
1.452
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.154
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.178
3145783HORNRTN
Solar/Wind Harmer
0.943
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.884
316263AC1-034 GEN
Solar/Wind Harmer
3.306
961601AG1-000A GEN
Solar/Wind Harmer
2.693
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
316217AC1-145 GEN
Solar/Wind Harmer
1.032
316197AC1-042 GEN
Solar/Wind Harmer
0.782
942671AE2-283 GEN
Solar/Wind Harmer
2.107
315821AE2-092 GEN
Solar/Wind Helper
2.531
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:203.45 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1422.11
MW Contribution:29.89
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.379
971563AH1-280 GEN
Solar/Wind Harmer
6.379
970685AG2-442 GEN
Solar/Wind Harmer
41.041
962491AG1-098 GEN
Solar/Wind Harmer
28.467
315693AD1-088 GEN
Solar/Wind Harmer
20.844
957481AF2-042 GEN
Solar/Wind Harmer
119.424
316237AB2-079_GEN
Solar/Wind Harmer
0.967
315687AD1-152 GEN
Solar/Wind Harmer
3.708
970401AG2-262 GEN
Solar/Wind Harmer
1.822
316003AC1-222 GEN
Solar/Wind Harmer
2.219
971065AG2-659 GEN
Solar/Wind Harmer
10.747
316129AC1-054 GEN
Solar/Wind Harmer
1.803
971795AH1-408 GEN
Solar/Wind Harmer
11.364
960081AF2-299 GEN
Solar/Wind Harmer
1.186
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.658
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.951
316049AB1-081 GEN
Solar/Wind Harmer
0.761
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.707
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
970223AG2-152 GEN
Solar/Wind Harmer
5.68
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.385
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.31
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.826
970285AG2-188 GEN
Solar/Wind Harmer
71.806
315657AE1-056 GEN
Solar/Wind Harmer
20.219
946301AF1-294 GEN
Solar/Wind Harmer
13.078
961791AG1-021 GEN
Solar/Wind Harmer
6.379
970683AG2-441 GEN
Solar/Wind Harmer
36.643
970681AG2-440 GEN
Solar/Wind Harmer
29.315
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.296
316239AB2-077_GEN
Solar/Wind Harmer
0.967
316238AB2-078_GEN
Solar/Wind Harmer
0.967
316118AC1-105 GEN
Solar/Wind Harmer
1.799
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.987
970831AG2-522 GEN
Solar/Wind Harmer
9.789
316123AC1-075 GEN
Solar/Wind Harmer
1.778
970165AG2-112 GEN
Solar/Wind Harmer
1.566
970163AG2-111 GEN
Solar/Wind Harmer
1.494
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.49
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.605
270457AD2-023 GEN
Solar/Wind Harmer
0.814
315607AA1-063A GEN
Solar/Wind Harmer
0.881
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.406
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.564
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.331
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
-0.168
971193AH1-056 GEN
Solar/Wind Harmer
33.698
963181AG1-167 GEN
Solar/Wind Harmer
4.785
959311AF2-222 GEN
Solar/Wind Harmer
45.693
970257AG2-171 GEN
Solar/Wind Harmer
15.944
315785AD2-033 C
Solar/Wind Harmer
9.243
964241AG1-285 GEN
Solar/Wind Harmer
28.257
316478AD1-087 GEN
Solar/Wind Harmer
3.106
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.6
316248AF1-058 C
Solar/Wind Harmer
0.737
960061AF2-297 GEN
Solar/Wind Harmer
12.232
971683AH1-343 GEN
Solar/Wind Harmer
9.152
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.287
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.767
316210AC1-098 GEN
Solar/Wind Harmer
1.185
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.727
315724AD1-057 GEN
Solar/Wind Harmer
0.389
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.385
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.343
971741AH1-377 GEN
Solar/Wind Harmer
63.689
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.974
963191AG1-168 GEN
Solar/Wind Harmer
4.785
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.258
971775AH1-396 GEN
Solar/Wind Harmer
3.027
970099AG2-077 GEN
Solar/Wind Harmer
47.77
313527AB2-043 GEN
Solar/Wind Harmer
5.31
962561AG1-105 GEN
Solar/Wind Harmer
16.108
964791AG1-342 GEN
Solar/Wind Harmer
5.961
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.346
942751AE2-291 GEN
Solar/Wind Harmer
9.222
316222AC1-221 GEN
Solar/Wind Harmer
1.414
316181AB2-040 GEN
Solar/Wind Harmer
1.452
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.154
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.178
3145783HORNRTN
Solar/Wind Harmer
0.943
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.884
316263AC1-034 GEN
Solar/Wind Harmer
3.306
961601AG1-000A GEN
Solar/Wind Harmer
2.693
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
316217AC1-145 GEN
Solar/Wind Harmer
1.032
316197AC1-042 GEN
Solar/Wind Harmer
0.782
942671AE2-283 GEN
Solar/Wind Harmer
2.107
315821AE2-092 GEN
Solar/Wind Helper
2.531
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:130.37 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:911.29
MW Contribution:12.88
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.288
3151621KERR 5
50/50
0.288
3151631KERR 6
50/50
0.288
3151641KERR 7
50/50
0.288
3151541CLOVER2
50/50
2.937
971845AH1-439 GEN
Solar/Wind Harmer
40.264
970285AG2-188 GEN
Solar/Wind Harmer
63.811
315657AE1-056 GEN
Solar/Wind Harmer
15.96
946301AF1-294 GEN
Solar/Wind Harmer
10.183
961791AG1-021 GEN
Solar/Wind Harmer
4.967
970683AG2-441 GEN
Solar/Wind Harmer
27.881
970681AG2-440 GEN
Solar/Wind Harmer
22.305
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.107
316239AB2-077_GEN
Solar/Wind Harmer
0.638
316238AB2-078_GEN
Solar/Wind Harmer
0.638
316118AC1-105 GEN
Solar/Wind Harmer
1.013
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.344
970865AG2-541 GEN
Solar/Wind Harmer
4.105
946281AF1-292 GEN
Solar/Wind Harmer
0.203
316087AB2-174 GEN
Solar/Wind Harmer
1.262
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.891
970165AG2-112 GEN
Solar/Wind Harmer
0.785
970163AG2-111 GEN
Solar/Wind Harmer
0.749
971967AH1-528 GEN
Solar/Wind Harmer
15.159
315607AA1-063A GEN
Solar/Wind Harmer
0.776
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.313
970581AG2-369 GEN
Solar/Wind Harmer
3.709
316319Z2-044 C
Solar/Wind Harmer
0.377
3146033SCOT NK
Solar/Wind Harmer
-0.027
315652AC1-086 GEN
Solar/Wind Harmer
7.536
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
965291AG1-394 GEN
Solar/Wind Harmer
0.58
970673AG2-436 GEN
Solar/Wind Harmer
13.57
970673AG2-436 GEN
Solar/Wind Harmer
6.871
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
270494AE1-108_GEN
Solar/Wind Helper
4.47
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.195
3151591KERR 2
50/50
0.288
970413AG2-270 GEN
50/50
12.878
3146776BUCKING
Solar/Wind Harmer
-0.028
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.6
970909AG2-566 GEN
Solar/Wind Harmer
4.079
3147133PAMPLIN
Solar/Wind Harmer
-0.133
971193AH1-056 GEN
Solar/Wind Harmer
26.601
963181AG1-167 GEN
Solar/Wind Harmer
3.725
959311AF2-222 GEN
Solar/Wind Harmer
34.052
970257AG2-171 GEN
Solar/Wind Harmer
11.771
315785AD2-033 C
Solar/Wind Harmer
6.728
964241AG1-285 GEN
Solar/Wind Harmer
19.662
316131AB2-060 GEN
Solar/Wind Harmer
2.419
316478AD1-087 GEN
Solar/Wind Harmer
1.34
316486AD2-202 GEN
Solar/Wind Harmer
0.392
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.389
960061AF2-297 GEN
Solar/Wind Harmer
6.446
971683AH1-343 GEN
Solar/Wind Harmer
4.749
966621AG1-532 GEN
Solar/Wind Harmer
0.184
313506AB2-031 GEN
Solar/Wind Harmer
0.704
316283AC2-100 C
Solar/Wind Harmer
0.785
316210AC1-098 GEN
Solar/Wind Harmer
1.101
316327AA2-057 GEN
Solar/Wind Harmer
0.705
970917AG2-570 GEN
Solar/Wind Harmer
17.269
3146233WITAKRS
Solar/Wind Harmer
0.143
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.004
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.38
316365GEN2_N
Solar/Wind Harmer
0.442
961601AG1-000A GEN
Solar/Wind Harmer
2.606
316317KELFORD C
Solar/Wind Harmer
0.305
3145823KELFORD
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.082
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
957521AF2-046 GEN
Solar/Wind Harmer
5.021
961681AG1-008 GEN
Solar/Wind Harmer
5.021
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.333
316258AE1-075 C
Solar/Wind Helper
0.299
316405AF2-144 C
Solar/Wind Helper
0.249
3148013FISHERV
Solar/Wind Helper
0.124
3144293JTRSVLE
50/50
1.195
3144293JTRSVLE
50/50
1.006
970535AG2-341 GEN
50/50
2.93
3152661PLYWOOD A
50/50
0.279
3146776BUCKING
Solar/Wind Harmer
-0.308
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.483
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.209
963191AG1-168 GEN
Solar/Wind Harmer
3.725
971741AH1-377 GEN
Solar/Wind Harmer
43.964
316034AC1-036 C
Solar/Wind Harmer
0.583
970323AG2-213 GEN
Solar/Wind Harmer
15.694
971775AH1-396 GEN
Solar/Wind Harmer
2.235
313527AB2-043 GEN
Solar/Wind Harmer
3.534
962561AG1-105 GEN
Solar/Wind Harmer
9.782
939181AE1-148 GEN
Solar/Wind Harmer
9.427
964791AG1-342 GEN
Solar/Wind Harmer
3.547
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
970099AG2-077 GEN
Solar/Wind Harmer
18.781
970933AG2-581 GEN
Solar/Wind Harmer
9.57
316181AB2-040 GEN
Solar/Wind Harmer
1.222
316222AC1-221 GEN
Solar/Wind Harmer
0.854
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.948
3145593CAROLNA
Solar/Wind Harmer
0.07
3145783HORNRTN
Solar/Wind Harmer
0.979
3145783HORNRTN
Solar/Wind Harmer
0.783
3145783HORNRTN
Solar/Wind Harmer
0.245
3145783HORNRTN
Solar/Wind Harmer
0.098
316426AA2-053 GEN
Solar/Wind Harmer
0.81
316274AC1-208 GEN
Solar/Wind Harmer
0.791
942751AE2-291 GEN
Solar/Wind Harmer
4.521
972187AH1-678 GEN
Adder
1.767
972185AH1-677 GEN
Adder
3.338
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
316263AC1-034 GEN
Solar/Wind Harmer
3.115
961601AG1-000A GEN
Solar/Wind Harmer
2.573
3145893MURPHYS
Solar/Wind Harmer
0.179
3145893MURPHYS
Solar/Wind Harmer
-0.012
3145493TOT1
Solar/Wind Harmer
0.098
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
315821AE2-092 GEN
Solar/Wind Helper
2.966
3144293JTRSVLE
50/50
1.195
3151601KERR 3
50/50
0.288
3151581KERR 1
50/50
0.103
3151531CLOVER1
50/50
2.951
3147043LAWRENC
50/50
1.104
316322AB2-045
Solar/Wind Harmer
2.6
3146776BUCKING
Solar/Wind Harmer
-0.031
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.967
971563AH1-280 GEN
Solar/Wind Harmer
4.967
970685AG2-442 GEN
Solar/Wind Harmer
31.227
962491AG1-098 GEN
Solar/Wind Harmer
14.504
316237AB2-079_GEN
Solar/Wind Harmer
0.638
315693AD1-088 GEN
Solar/Wind Harmer
10.264
970401AG2-262 GEN
Solar/Wind Harmer
1.084
957481AF2-042 GEN
Solar/Wind Harmer
46.952
315687AD1-152 GEN
Solar/Wind Harmer
1.686
971065AG2-659 GEN
Solar/Wind Harmer
6.782
316129AC1-054 GEN
Solar/Wind Harmer
1.152
316003AC1-222 GEN
Solar/Wind Harmer
1.16
971795AH1-408 GEN
Solar/Wind Harmer
8.774
960081AF2-299 GEN
Solar/Wind Harmer
1.019
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
316212AC1-099_GEN
Solar/Wind Harmer
0.612
970919AG2-571 GEN
Solar/Wind Harmer
2.186
970087AG2-069 GEN
Solar/Wind Harmer
6.469
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.401
962571AG1-106 GEN
Solar/Wind Harmer
0.963
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316359AB2-059 GEN
Solar/Wind Harmer
0.896
316049AB1-081 GEN
Solar/Wind Harmer
0.717
3142053HEARTS
Solar/Wind Harmer
0.078
315722AD1-056 GEN
Solar/Wind Harmer
0.692
316023GEN1_S
Solar/Wind Harmer
0.442
3145823KELFORD
Solar/Wind Harmer
-0.006
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.19
961671AG1-007 GEN
Solar/Wind Harmer
0.08
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.188
316336AC2-165 C
Solar/Wind Helper
1.427
CPLELTFEXP_CPLE->PJM
CLTF
4.525
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.338
LAGNLTFEXP_LAGN->PJM
CLTF
2.472
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.204
TVALTFEXP_TVA->PJM
CLTF
1.2
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.871
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.899
MECLTFEXP_MEC->PJM
CLTF
0.811
SIGELTFEXP_SIGE->PJM
CLTF
0.021
NYPJM->LTFIMP_NY
CLTF
0.305
LGEELTFEXP_LGEE->PJM
CLTF
0.208
WECLTFEXP_WEC->PJM
CLTF
0.117

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2106-2111_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2106-2111_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:130.23 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:910.33
MW Contribution:12.39
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.277
3151621KERR 5
50/50
0.277
3151631KERR 6
50/50
0.277
3151641KERR 7
50/50
0.277
3144293JTRSVLE
50/50
1.179
3151601KERR 3
50/50
0.277
3151581KERR 1
50/50
0.099
3151531CLOVER1
50/50
2.838
316322AB2-045
Solar/Wind Harmer
2.588
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.904
971563AH1-280 GEN
Solar/Wind Harmer
4.904
970685AG2-442 GEN
Solar/Wind Harmer
30.768
962491AG1-098 GEN
Solar/Wind Harmer
14.136
316237AB2-079_GEN
Solar/Wind Harmer
0.62
315693AD1-088 GEN
Solar/Wind Harmer
9.987
970401AG2-262 GEN
Solar/Wind Harmer
1.044
957481AF2-042 GEN
Solar/Wind Harmer
45.172
315687AD1-152 GEN
Solar/Wind Harmer
1.609
971065AG2-659 GEN
Solar/Wind Harmer
6.46
316129AC1-054 GEN
Solar/Wind Harmer
1.096
3147043LAWRENC
Adder
0.992
316003AC1-222 GEN
Solar/Wind Harmer
1.105
971795AH1-408 GEN
Solar/Wind Harmer
8.324
960081AF2-299 GEN
Solar/Wind Harmer
0.951
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.091
316336AC2-165 C
Solar/Wind Helper
1.456
3151541CLOVER2
50/50
2.825
971845AH1-439 GEN
Solar/Wind Harmer
40.074
970285AG2-188 GEN
Solar/Wind Harmer
63.49
315657AE1-056 GEN
Solar/Wind Harmer
15.775
946301AF1-294 GEN
Solar/Wind Harmer
10.053
961791AG1-021 GEN
Solar/Wind Harmer
4.904
970683AG2-441 GEN
Solar/Wind Harmer
27.471
970681AG2-440 GEN
Solar/Wind Harmer
21.977
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
5.999
316239AB2-077_GEN
Solar/Wind Harmer
0.62
316238AB2-078_GEN
Solar/Wind Harmer
0.62
316118AC1-105 GEN
Solar/Wind Harmer
0.971
3147173SINAI
Solar/Wind Harmer
-0.012
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.022
970865AG2-541 GEN
Solar/Wind Harmer
3.914
946281AF1-292 GEN
Solar/Wind Harmer
0.189
316087AB2-174 GEN
Solar/Wind Harmer
1.174
3137643SOCKMAN
Solar/Wind Harmer
-0.032
316123AC1-075 GEN
Solar/Wind Harmer
0.851
970165AG2-112 GEN
Solar/Wind Harmer
0.749
970163AG2-111 GEN
Solar/Wind Harmer
0.714
971967AH1-528 GEN
Solar/Wind Harmer
14.144
315607AA1-063A GEN
Solar/Wind Harmer
0.713
3146043SEABORD
Solar/Wind Harmer
-0.007
270494AE1-108_GEN
Solar/Wind Helper
4.505
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3144293JTRSVLE
50/50
1.179
3144293JTRSVLE
50/50
0.993
970535AG2-341 GEN
50/50
2.832
3152661PLYWOOD A
50/50
0.267
3146776BUCKING
Solar/Wind Harmer
-0.306
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.246
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.13
963191AG1-168 GEN
Solar/Wind Harmer
3.678
971741AH1-377 GEN
Solar/Wind Harmer
43.39
316034AC1-036 C
Solar/Wind Harmer
0.573
970323AG2-213 GEN
Solar/Wind Harmer
15.422
971775AH1-396 GEN
Solar/Wind Harmer
2.196
313527AB2-043 GEN
Solar/Wind Harmer
3.438
962561AG1-105 GEN
Solar/Wind Harmer
9.444
939181AE1-148 GEN
Solar/Wind Harmer
9.07
964791AG1-342 GEN
Solar/Wind Harmer
3.418
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.069
970933AG2-581 GEN
Solar/Wind Harmer
9.057
316181AB2-040 GEN
Solar/Wind Harmer
1.135
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.876
3145593CAROLNA
Solar/Wind Harmer
0.065
3145783HORNRTN
Solar/Wind Harmer
0.902
3145783HORNRTN
Solar/Wind Harmer
0.721
3145783HORNRTN
Solar/Wind Harmer
0.225
3145783HORNRTN
Solar/Wind Harmer
0.09
316222AC1-221 GEN
Solar/Wind Harmer
0.766
316426AA2-053 GEN
Solar/Wind Harmer
0.746
942751AE2-291 GEN
Solar/Wind Harmer
4.318
316274AC1-208 GEN
Solar/Wind Harmer
0.714
972187AH1-678 GEN
Adder
1.624
315821AE2-092 GEN
Solar/Wind Helper
2.997
3144293JTRSVLE
50/50
1.179
3151591KERR 2
50/50
0.277
970413AG2-270 GEN
50/50
12.386
3146776BUCKING
Solar/Wind Harmer
-0.027
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.532
970909AG2-566 GEN
Solar/Wind Harmer
4.034
3147133PAMPLIN
Solar/Wind Harmer
-0.131
971193AH1-056 GEN
Solar/Wind Harmer
26.292
963181AG1-167 GEN
Solar/Wind Harmer
3.678
959311AF2-222 GEN
Solar/Wind Harmer
33.489
970257AG2-171 GEN
Solar/Wind Harmer
11.567
315785AD2-033 C
Solar/Wind Harmer
6.603
964241AG1-285 GEN
Solar/Wind Harmer
19.215
316131AB2-060 GEN
Solar/Wind Harmer
2.356
316478AD1-087 GEN
Solar/Wind Harmer
1.288
316486AD2-202 GEN
Solar/Wind Harmer
0.377
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.37
960061AF2-297 GEN
Solar/Wind Harmer
6.139
971683AH1-343 GEN
Solar/Wind Harmer
4.525
966621AG1-532 GEN
Solar/Wind Harmer
0.171
313506AB2-031 GEN
Solar/Wind Harmer
0.654
316283AC2-100 C
Solar/Wind Harmer
0.703
316313AB2-026
Solar/Wind Helper
0.341
316258AE1-075 C
Solar/Wind Helper
0.307
316405AF2-144 C
Solar/Wind Helper
0.256
3148013FISHERV
Solar/Wind Helper
0.125
CPLELTFEXP_CPLE->PJM
CLTF
3.699
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.437
LAGNLTFEXP_LAGN->PJM
CLTF
1.81
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.409
TVALTFEXP_TVA->PJM
CLTF
0.888
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.959
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.906
MECLTFEXP_MEC->PJM
CLTF
0.618
SIGELTFEXP_SIGE->PJM
CLTF
0.017
NYPJM->LTFIMP_NY
CLTF
0.351
LGEELTFEXP_LGEE->PJM
CLTF
0.175
WECLTFEXP_WEC->PJM
CLTF
0.091

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2003-205_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2003-205_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:126.86 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:886.73
MW Contribution:12.71
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.189
3151601KERR 3
50/50
0.284
3151581KERR 1
50/50
0.101
3151531CLOVER1
50/50
2.913
3147043LAWRENC
50/50
1.1
316322AB2-045
Solar/Wind Harmer
2.593
3146776BUCKING
Solar/Wind Harmer
-0.031
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.943
971563AH1-280 GEN
Solar/Wind Harmer
4.943
970685AG2-442 GEN
Solar/Wind Harmer
31.058
962491AG1-098 GEN
Solar/Wind Harmer
14.389
316237AB2-079_GEN
Solar/Wind Harmer
0.632
315693AD1-088 GEN
Solar/Wind Harmer
10.178
970401AG2-262 GEN
Solar/Wind Harmer
1.068
957481AF2-042 GEN
Solar/Wind Harmer
46.433
315687AD1-152 GEN
Solar/Wind Harmer
1.654
971065AG2-659 GEN
Solar/Wind Harmer
6.674
316129AC1-054 GEN
Solar/Wind Harmer
1.134
971795AH1-408 GEN
Solar/Wind Harmer
8.763
316003AC1-222 GEN
Solar/Wind Harmer
1.138
960081AF2-299 GEN
Solar/Wind Harmer
1.022
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.097
316212AC1-099_GEN
Solar/Wind Harmer
0.589
970919AG2-571 GEN
Solar/Wind Harmer
2.13
970087AG2-069 GEN
Solar/Wind Harmer
6.297
316023GEN1_S
Solar/Wind Harmer
0.451
316011AB1-132 GEN
Solar/Wind Harmer
1.384
962571AG1-106 GEN
Solar/Wind Harmer
0.951
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
-0.026
315722AD1-056 GEN
Solar/Wind Harmer
0.665
316336AC2-165 C
Solar/Wind Helper
1.458
3151611KERR 4
50/50
0.284
3151621KERR 5
50/50
0.284
3151631KERR 6
50/50
0.284
3151641KERR 7
50/50
0.284
3151541CLOVER2
50/50
2.899
971845AH1-439 GEN
Solar/Wind Harmer
40.166
970285AG2-188 GEN
Solar/Wind Harmer
63.65
315657AE1-056 GEN
Solar/Wind Harmer
15.889
946301AF1-294 GEN
Solar/Wind Harmer
10.133
961791AG1-021 GEN
Solar/Wind Harmer
4.943
970683AG2-441 GEN
Solar/Wind Harmer
27.73
970681AG2-440 GEN
Solar/Wind Harmer
22.184
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.068
316239AB2-077_GEN
Solar/Wind Harmer
0.632
316238AB2-078_GEN
Solar/Wind Harmer
0.632
316118AC1-105 GEN
Solar/Wind Harmer
0.995
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.242
970865AG2-541 GEN
Solar/Wind Harmer
4.039
946281AF1-292 GEN
Solar/Wind Harmer
0.204
316087AB2-174 GEN
Solar/Wind Harmer
1.259
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.881
970165AG2-112 GEN
Solar/Wind Harmer
0.776
970163AG2-111 GEN
Solar/Wind Harmer
0.74
971967AH1-528 GEN
Solar/Wind Harmer
14.996
315607AA1-063A GEN
Solar/Wind Harmer
0.76
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.198
970581AG2-369 GEN
Solar/Wind Harmer
3.61
315652AC1-086 GEN
Solar/Wind Harmer
7.443
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.026
316319Z2-044 C
Solar/Wind Harmer
0.358
970673AG2-436 GEN
Solar/Wind Harmer
13.401
970673AG2-436 GEN
Solar/Wind Harmer
6.785
965291AG1-394 GEN
Solar/Wind Harmer
0.563
270494AE1-108_GEN
Solar/Wind Helper
4.481
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3144293JTRSVLE
50/50
1.189
3144293JTRSVLE
50/50
1.001
970535AG2-341 GEN
50/50
2.895
3152661PLYWOOD A
50/50
0.274
3146776BUCKING
Solar/Wind Harmer
-0.307
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.395
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.179
963191AG1-168 GEN
Solar/Wind Harmer
3.707
971741AH1-377 GEN
Solar/Wind Harmer
43.759
316034AC1-036 C
Solar/Wind Harmer
0.58
970323AG2-213 GEN
Solar/Wind Harmer
15.596
971775AH1-396 GEN
Solar/Wind Harmer
2.221
313527AB2-043 GEN
Solar/Wind Harmer
3.501
962561AG1-105 GEN
Solar/Wind Harmer
9.651
939181AE1-148 GEN
Solar/Wind Harmer
9.294
964791AG1-342 GEN
Solar/Wind Harmer
3.496
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.573
970933AG2-581 GEN
Solar/Wind Harmer
9.469
316181AB2-040 GEN
Solar/Wind Harmer
1.215
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.932
3145593CAROLNA
Solar/Wind Harmer
0.069
3145783HORNRTN
Solar/Wind Harmer
0.96
3145783HORNRTN
Solar/Wind Harmer
0.768
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
316222AC1-221 GEN
Solar/Wind Harmer
0.8
316426AA2-053 GEN
Solar/Wind Harmer
0.794
316274AC1-208 GEN
Solar/Wind Harmer
0.763
942751AE2-291 GEN
Solar/Wind Harmer
4.488
972187AH1-678 GEN
Adder
1.739
972185AH1-677 GEN
Adder
3.291
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
315821AE2-092 GEN
Solar/Wind Helper
2.986
3144293JTRSVLE
50/50
1.189
3151591KERR 2
50/50
0.284
970413AG2-270 GEN
50/50
12.71
3146776BUCKING
Solar/Wind Harmer
-0.027
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.572
970909AG2-566 GEN
Solar/Wind Harmer
4.062
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.482
963181AG1-167 GEN
Solar/Wind Harmer
3.707
959311AF2-222 GEN
Solar/Wind Harmer
33.848
970257AG2-171 GEN
Solar/Wind Harmer
11.697
315785AD2-033 C
Solar/Wind Harmer
6.684
964241AG1-285 GEN
Solar/Wind Harmer
19.507
316131AB2-060 GEN
Solar/Wind Harmer
2.398
316478AD1-087 GEN
Solar/Wind Harmer
1.322
316486AD2-202 GEN
Solar/Wind Harmer
0.387
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.38
960061AF2-297 GEN
Solar/Wind Harmer
6.313
971683AH1-343 GEN
Solar/Wind Harmer
4.664
966621AG1-532 GEN
Solar/Wind Harmer
0.184
313506AB2-031 GEN
Solar/Wind Harmer
0.7
316283AC2-100 C
Solar/Wind Harmer
0.734
316210AC1-098 GEN
Solar/Wind Harmer
1.061
970917AG2-570 GEN
Solar/Wind Harmer
16.827
316365GEN2_N
Solar/Wind Harmer
0.451
316327AA2-057 GEN
Solar/Wind Harmer
0.674
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.136
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
315724AD1-057 GEN
Solar/Wind Harmer
0.366
316313AB2-026
Solar/Wind Helper
0.342
316258AE1-075 C
Solar/Wind Helper
0.308
316405AF2-144 C
Solar/Wind Helper
0.257
3148013FISHERV
Solar/Wind Helper
0.124
CPLELTFEXP_CPLE->PJM
CLTF
3.934
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.902
LAGNLTFEXP_LAGN->PJM
CLTF
2.053
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.953
TVALTFEXP_TVA->PJM
CLTF
1.009
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.279
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.343
MECLTFEXP_MEC->PJM
CLTF
0.782
SIGELTFEXP_SIGE->PJM
CLTF
0.022
NYPJM->LTFIMP_NY
CLTF
0.325
LGEELTFEXP_LGEE->PJM
CLTF
0.24
WECLTFEXP_WEC->PJM
CLTF
0.127

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:118.39 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:827.52
MW Contribution:12.56
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.281
3144293JTRSVLE
50/50
1.186
3151591KERR 2
50/50
0.281
970413AG2-270 GEN
50/50
12.559
3146776BUCKING
Solar/Wind Harmer
-0.027
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.558
970909AG2-566 GEN
Solar/Wind Harmer
4.05
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.415
963181AG1-167 GEN
Solar/Wind Harmer
3.697
959311AF2-222 GEN
Solar/Wind Harmer
33.722
970257AG2-171 GEN
Solar/Wind Harmer
11.651
315785AD2-033 C
Solar/Wind Harmer
6.656
964241AG1-285 GEN
Solar/Wind Harmer
19.405
316131AB2-060 GEN
Solar/Wind Harmer
2.383
316478AD1-087 GEN
Solar/Wind Harmer
1.306
316486AD2-202 GEN
Solar/Wind Harmer
0.383
316248AF1-058 C
Solar/Wind Harmer
0.383
960061AF2-297 GEN
Solar/Wind Harmer
6.356
3147043LAWRENC
Solar/Wind Harmer
-0.007
971683AH1-343 GEN
Solar/Wind Harmer
4.828
966621AG1-532 GEN
Solar/Wind Harmer
0.175
313506AB2-031 GEN
Solar/Wind Harmer
0.668
316283AC2-100 C
Solar/Wind Harmer
0.723
316210AC1-098 GEN
Solar/Wind Harmer
1.017
970917AG2-570 GEN
Solar/Wind Harmer
16.116
316327AA2-057 GEN
Solar/Wind Harmer
0.646
316313AB2-026
Solar/Wind Helper
0.338
3151621KERR 5
50/50
0.281
3151631KERR 6
50/50
0.281
3151641KERR 7
50/50
0.281
3151541CLOVER2
50/50
2.864
971845AH1-439 GEN
Solar/Wind Harmer
40.143
970285AG2-188 GEN
Solar/Wind Harmer
63.606
315657AE1-056 GEN
Solar/Wind Harmer
15.849
946301AF1-294 GEN
Solar/Wind Harmer
10.105
961791AG1-021 GEN
Solar/Wind Harmer
4.929
970683AG2-441 GEN
Solar/Wind Harmer
27.639
970681AG2-440 GEN
Solar/Wind Harmer
22.111
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.044
316239AB2-077_GEN
Solar/Wind Harmer
0.628
316238AB2-078_GEN
Solar/Wind Harmer
0.628
316118AC1-105 GEN
Solar/Wind Harmer
0.998
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.123
970865AG2-541 GEN
Solar/Wind Harmer
4.251
316123AC1-075 GEN
Solar/Wind Harmer
0.968
970165AG2-112 GEN
Solar/Wind Harmer
0.853
970163AG2-111 GEN
Solar/Wind Harmer
0.813
946281AF1-292 GEN
Solar/Wind Harmer
0.193
316087AB2-174 GEN
Solar/Wind Harmer
1.199
3137643SOCKMAN
Solar/Wind Harmer
-0.032
971967AH1-528 GEN
Solar/Wind Harmer
14.441
315607AA1-063A GEN
Solar/Wind Harmer
0.73
3144293JTRSVLE
50/50
1.186
3151601KERR 3
50/50
0.281
3151581KERR 1
50/50
0.1
3151531CLOVER1
50/50
2.878
316322AB2-045
Solar/Wind Harmer
2.592
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.929
971563AH1-280 GEN
Solar/Wind Harmer
4.929
970685AG2-442 GEN
Solar/Wind Harmer
30.955
962491AG1-098 GEN
Solar/Wind Harmer
14.261
316237AB2-079_GEN
Solar/Wind Harmer
0.628
315693AD1-088 GEN
Solar/Wind Harmer
10.081
970401AG2-262 GEN
Solar/Wind Harmer
1.068
957481AF2-042 GEN
Solar/Wind Harmer
45.769
315687AD1-152 GEN
Solar/Wind Harmer
1.638
971065AG2-659 GEN
Solar/Wind Harmer
6.564
316129AC1-054 GEN
Solar/Wind Harmer
1.114
3147043LAWRENC
Adder
1.008
316003AC1-222 GEN
Solar/Wind Harmer
1.162
971795AH1-408 GEN
Solar/Wind Harmer
8.467
960081AF2-299 GEN
Solar/Wind Harmer
0.97
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.093
316212AC1-099_GEN
Solar/Wind Harmer
0.565
970919AG2-571 GEN
Solar/Wind Harmer
2.04
970087AG2-069 GEN
Solar/Wind Harmer
6.032
316336AC2-165 C
Solar/Wind Helper
1.446
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.021
970581AG2-369 GEN
Solar/Wind Harmer
3.458
270494AE1-108_GEN
Solar/Wind Helper
4.516
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.186
3144293JTRSVLE
50/50
0.998
970535AG2-341 GEN
50/50
2.87
3152661PLYWOOD A
50/50
0.275
3146776BUCKING
Solar/Wind Harmer
-0.307
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.329
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.162
963191AG1-168 GEN
Solar/Wind Harmer
3.697
971741AH1-377 GEN
Solar/Wind Harmer
43.59
316034AC1-036 C
Solar/Wind Harmer
0.577
970323AG2-213 GEN
Solar/Wind Harmer
15.535
971775AH1-396 GEN
Solar/Wind Harmer
2.212
313527AB2-043 GEN
Solar/Wind Harmer
3.479
962561AG1-105 GEN
Solar/Wind Harmer
9.636
964791AG1-342 GEN
Solar/Wind Harmer
3.494
939181AE1-148 GEN
Solar/Wind Harmer
9.198
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.308
970933AG2-581 GEN
Solar/Wind Harmer
9.214
316181AB2-040 GEN
Solar/Wind Harmer
1.159
942751AE2-291 GEN
Solar/Wind Harmer
5.121
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.895
3145593CAROLNA
Solar/Wind Harmer
0.066
316222AC1-221 GEN
Solar/Wind Harmer
0.788
3145783HORNRTN
Solar/Wind Harmer
0.922
3145783HORNRTN
Solar/Wind Harmer
0.738
3145783HORNRTN
Solar/Wind Harmer
0.231
3145783HORNRTN
Solar/Wind Harmer
0.092
316426AA2-053 GEN
Solar/Wind Harmer
0.763
316274AC1-208 GEN
Solar/Wind Harmer
0.732
972187AH1-678 GEN
Adder
1.663
315821AE2-092 GEN
Solar/Wind Helper
2.985
316258AE1-075 C
Solar/Wind Helper
0.304
316405AF2-144 C
Solar/Wind Helper
0.253
3148013FISHERV
Solar/Wind Helper
0.124
CPLELTFEXP_CPLE->PJM
CLTF
3.818
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.266
LAGNLTFEXP_LAGN->PJM
CLTF
1.942
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.684
TVALTFEXP_TVA->PJM
CLTF
0.953
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.791
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.144
MECLTFEXP_MEC->PJM
CLTF
0.716
SIGELTFEXP_SIGE->PJM
CLTF
0.02
NYPJM->LTFIMP_NY
CLTF
0.309
LGEELTFEXP_LGEE->PJM
CLTF
0.214
WECLTFEXP_WEC->PJM
CLTF
0.113

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.79 %
Rating:571.52 MVA
Rating Type:A
MVA to Mitigate:644.61
MW Contribution:12.47
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.278
3151621KERR 5
50/50
0.278
3151631KERR 6
50/50
0.278
3151641KERR 7
50/50
0.278
3151541CLOVER2
50/50
2.843
3151281ROARAP4
50/50
0.085
3151281ROARAP4
50/50
0.079
963041AG1-153 GEN
50/50
1.544
971845AH1-439 GEN
Solar/Wind Harmer
30.475
970285AG2-188 GEN
Solar/Wind Harmer
51.158
315657AE1-056 GEN
Solar/Wind Harmer
12.943
946301AF1-294 GEN
Solar/Wind Harmer
6.907
961791AG1-021 GEN
Solar/Wind Harmer
3.36
970683AG2-441 GEN
Solar/Wind Harmer
20.922
970681AG2-440 GEN
Solar/Wind Harmer
16.737
3144303KENBRDG
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
4.571
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.326
3147173SINAI
Solar/Wind Harmer
0.11
3147243WELCO
Solar/Wind Harmer
0.069
970831AG2-522 GEN
Solar/Wind Harmer
4.61
970865AG2-541 GEN
Solar/Wind Harmer
3.002
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.286
316123AC1-075 GEN
Solar/Wind Harmer
0.097
970165AG2-112 GEN
Solar/Wind Harmer
0.576
970163AG2-111 GEN
Solar/Wind Harmer
0.549
971967AH1-528 GEN
Solar/Wind Harmer
10.852
315607AA1-063A GEN
Solar/Wind Harmer
0.13
3146043SEABORD
Solar/Wind Harmer
0.063
970085AG2-068 GEN
Solar/Wind Harmer
3.026
970581AG2-369 GEN
Solar/Wind Harmer
2.602
270494AE1-108_GEN
Solar/Wind Helper
4.482
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.182
3151601KERR 3
50/50
0.278
3151581KERR 1
50/50
0.099
3151531CLOVER1
50/50
2.857
3147043LAWRENC
50/50
1.061
3151261ROARAP2
50/50
0.087
3151051BRUNSWICKS1
50/50
1.582
3151021BRUNSWICKG1
50/50
0.762
971451AH1-221 GEN
50/50
2.315
316322AB2-045
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Harmer
0.316
963171AG1-166 GEN
Solar/Wind Harmer
1.867
971563AH1-280 GEN
Solar/Wind Harmer
3.734
970685AG2-442 GEN
Solar/Wind Harmer
23.432
962491AG1-098 GEN
Solar/Wind Harmer
10.785
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
8.574
970401AG2-262 GEN
Solar/Wind Harmer
0.841
957481AF2-042 GEN
Solar/Wind Harmer
34.537
315687AD1-152 GEN
Solar/Wind Harmer
0.004
971065AG2-659 GEN
Solar/Wind Harmer
4.943
316129AC1-054 GEN
Solar/Wind Harmer
0.422
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971795AH1-408 GEN
Solar/Wind Harmer
6.643
960081AF2-299 GEN
Solar/Wind Harmer
0.73
3145783HORNRTN
Solar/Wind Harmer
0.068
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
0.295
970919AG2-571 GEN
Solar/Wind Harmer
2.021
970087AG2-069 GEN
Solar/Wind Harmer
4.539
316336AC2-165 C
Solar/Wind Helper
1.447
3144293JTRSVLE
50/50
1.182
3144293JTRSVLE
50/50
0.996
970535AG2-341 GEN
50/50
2.848
3152661PLYWOOD A
50/50
0.269
3151041BRUNSWICKG3
50/50
0.762
972187AH1-678 GEN
50/50
1.749
3146776BUCKING
Solar/Wind Harmer
2.741
3146776BUCKING
Solar/Wind Harmer
0.222
970301AG2-198 GEN
Solar/Wind Harmer
16.173
3147133PAMPLIN
Solar/Wind Harmer
0.375
3147133PAMPLIN
Solar/Wind Harmer
0.3
958211AF2-115 GEN
Solar/Wind Harmer
4.2
963191AG1-168 GEN
Solar/Wind Harmer
1.4
971741AH1-377 GEN
Solar/Wind Harmer
33.04
316034AC1-036 C
Solar/Wind Harmer
0.02
970323AG2-213 GEN
Solar/Wind Harmer
11.75
971775AH1-396 GEN
Solar/Wind Harmer
0.441
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
7.214
939181AE1-148 GEN
Solar/Wind Harmer
6.93
964791AG1-342 GEN
Solar/Wind Harmer
2.751
3146843MT LREL
Solar/Wind Harmer
0.143
3146843MT LREL
Solar/Wind Harmer
0.143
970099AG2-077 GEN
Solar/Wind Harmer
13.815
970933AG2-581 GEN
Solar/Wind Harmer
6.948
316181AB2-040 GEN
Solar/Wind Harmer
0.106
3145593CAROLNA
Solar/Wind Harmer
0.07
3145593CAROLNA
Solar/Wind Harmer
0.07
966811AG1-552 GEN
Solar/Wind Harmer
0.761
3145593CAROLNA
Solar/Wind Harmer
0.087
3145783HORNRTN
Solar/Wind Harmer
1.218
3145783HORNRTN
Solar/Wind Harmer
0.974
3145783HORNRTN
Solar/Wind Harmer
0.304
3145783HORNRTN
Solar/Wind Harmer
0.122
316222AC1-221 GEN
Solar/Wind Harmer
0.283
316426AA2-053 GEN
Solar/Wind Harmer
0.225
942751AE2-291 GEN
Solar/Wind Harmer
3.327
316274AC1-208 GEN
Solar/Wind Harmer
0.31
315821AE2-092 GEN
Solar/Wind Helper
2.982
3144293JTRSVLE
50/50
1.182
3151591KERR 2
50/50
0.278
970413AG2-270 GEN
50/50
12.466
3151261ROARAP2
50/50
0.085
3151031BRUNSWICKG2
50/50
0.762
3146776BUCKING
Solar/Wind Harmer
0.247
3146926FARMVIL
Solar/Wind Harmer
0.316
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.043
3147133PAMPLIN
Solar/Wind Harmer
1.178
971193AH1-056 GEN
Solar/Wind Harmer
22.85
963181AG1-167 GEN
Solar/Wind Harmer
1.4
959311AF2-222 GEN
Solar/Wind Harmer
25.461
970257AG2-171 GEN
Solar/Wind Harmer
8.812
315785AD2-033 C
Solar/Wind Harmer
2.115
964241AG1-285 GEN
Solar/Wind Harmer
14.651
316131AB2-060 GEN
Solar/Wind Harmer
0.614
316478AD1-087 GEN
Solar/Wind Harmer
0.465
316486AD2-202 GEN
Solar/Wind Harmer
0.137
3147043LAWRENC
Solar/Wind Harmer
0.066
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.699
971683AH1-343 GEN
Solar/Wind Harmer
3.468
313506AB2-031 GEN
Solar/Wind Harmer
0.226
316283AC2-100 C
Solar/Wind Harmer
0.132
316210AC1-098 GEN
Solar/Wind Harmer
0.53
970917AG2-570 GEN
Solar/Wind Harmer
5.054
316327AA2-057 GEN
Solar/Wind Harmer
0.085
316313AB2-026
Solar/Wind Helper
0.339
316258AE1-075 C
Solar/Wind Helper
0.305
316405AF2-144 C
Solar/Wind Helper
0.254
3148013FISHERV
Solar/Wind Helper
0.124
CPLELTFEXP_CPLE->PJM
CLTF
3.771
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.326
LAGNLTFEXP_LAGN->PJM
CLTF
1.944
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.608
TVALTFEXP_TVA->PJM
CLTF
0.955
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.922
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.157
MECLTFEXP_MEC->PJM
CLTF
0.729
SIGELTFEXP_SIGE->PJM
CLTF
0.02
NYPJM->LTFIMP_NY
CLTF
0.308
LGEELTFEXP_LGEE->PJM
CLTF
0.221
WECLTFEXP_WEC->PJM
CLTF
0.117

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.83 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1864.16
MW Contribution:11.15
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
1.972
3151391GASTONA
50/50
0.365
3151411GASTONB
50/50
0.365
970413AG2-270 GEN
50/50
11.155
3151261ROARAP2
50/50
0.144
316365GEN2_N
Solar/Wind Harmer
1.302
966621AG1-532 GEN
Solar/Wind Harmer
0.347
970917AG2-570 GEN
Solar/Wind Harmer
40.235
3147043LAWRENC
Solar/Wind Harmer
-0.009
313506AB2-031 GEN
Solar/Wind Harmer
1.233
3145796HORNRTN
Solar/Wind Harmer
-0.058
3145796HORNRTN
Solar/Wind Harmer
-0.015
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316478AD1-087 GEN
Solar/Wind Harmer
1.161
316486AD2-202 GEN
Solar/Wind Harmer
0.34
315724AD1-057 GEN
Solar/Wind Harmer
0.758
316327AA2-057 GEN
Solar/Wind Harmer
1.21
961601AG1-000A GEN
Solar/Wind Harmer
4.742
3146233WITAKRS
Solar/Wind Harmer
0.249
3146233WITAKRS
Solar/Wind Harmer
-0.008
3138543CONSLDL
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.012
315779AE2-040
50/50
3.378
315244AE2-183_ST
50/50
4.349
963041AG1-153 GEN
50/50
3.994
3151541CLOVER2
50/50
2.544
3151281ROARAP4
50/50
0.144
3151281ROARAP4
50/50
0.134
316315AB2-025 C
Solar/Wind Harmer
0.734
315814AE2-033 C
Solar/Wind Harmer
24.939
941031AE2-094 GEN
Solar/Wind Harmer
33.281
944011AF1-069 GEN
Solar/Wind Harmer
10.428
970673AG2-436 GEN
Solar/Wind Harmer
36.399
970673AG2-436 GEN
Solar/Wind Harmer
18.43
946281AF1-292 GEN
Solar/Wind Harmer
0.383
971967AH1-528 GEN
Solar/Wind Harmer
31.705
970085AG2-068 GEN
Solar/Wind Harmer
10.008
970581AG2-369 GEN
Solar/Wind Harmer
8.607
316087AB2-174 GEN
Solar/Wind Harmer
2.265
315652AC1-086 GEN
Solar/Wind Harmer
17.05
3145796HORNRTN
Solar/Wind Harmer
-0.047
3145796HORNRTN
Solar/Wind Harmer
-0.006
3137643SOCKMAN
Solar/Wind Harmer
-0.057
970831AG2-522 GEN
Solar/Wind Harmer
6.31
315607AA1-063A GEN
Solar/Wind Harmer
1.207
316319Z2-044 C
Solar/Wind Harmer
0.657
3146043SEABORD
Solar/Wind Harmer
-0.012
316239AB2-077_GEN
Solar/Wind Harmer
0.35
316238AB2-078_GEN
Solar/Wind Harmer
0.35
3146033SCOT NK
Solar/Wind Harmer
-0.045
3145573BETHELC
Solar/Wind Harmer
-0.011
3145573BETHELC
Solar/Wind Harmer
-0.011
316420AA1-050 GEN
Solar/Wind Harmer
1.267
316118AC1-105 GEN
Solar/Wind Harmer
0.759
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
4.731
971443AH1-215 GEN
Solar/Wind Harmer
2.043
3145683EARLEYS
Solar/Wind Harmer
-0.021
3145683EARLEYS
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.01
3144303KENBRDG
Solar/Wind Harmer
-0.008
3145513AHOSKIE
Solar/Wind Harmer
0.089
961941AG1-037 GEN
Solar/Wind Harmer
0.077
3145513AHOSKIE
Solar/Wind Harmer
-0.01
316005AA1-067
Solar/Wind Harmer
0.207
3145746EVERETS
Solar/Wind Harmer
-0.041
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
970181AG2-120 GEN
Solar/Wind Harmer
1.344
316318V4-068
Solar/Wind Harmer
0.249
3145893MURPHYS
Solar/Wind Harmer
-0.027
3145893MURPHYS
Solar/Wind Harmer
-0.01
965291AG1-394 GEN
Solar/Wind Harmer
0.871
970683AG2-441 GEN
Solar/Wind Harmer
7.621
970681AG2-440 GEN
Solar/Wind Harmer
6.097
3143316POE
Solar/Wind Harmer
-0.038
970865AG2-541 GEN
Solar/Wind Harmer
3.743
946301AF1-294 GEN
Solar/Wind Harmer
2.361
961791AG1-021 GEN
Solar/Wind Harmer
1.152
315657AE1-056 GEN
Solar/Wind Harmer
3.313
3146206CASHIE
Solar/Wind Harmer
-0.009
970601AG2-382 GEN
Solar/Wind Harmer
3.864
270455AD2-022 GEN
Solar/Wind Harmer
1.529
270457AD2-023 GEN
Solar/Wind Harmer
0.775
315732AD1-074 GEN1
Solar/Wind Harmer
1.65
315733AD1-074 GEN2
Solar/Wind Harmer
1.65
315735AD1-075 GEN1
Solar/Wind Harmer
0.825
316123AC1-075 GEN
Solar/Wind Harmer
0.874
970165AG2-112 GEN
Solar/Wind Harmer
0.77
970163AG2-111 GEN
Solar/Wind Harmer
0.734
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.593
3130156CHOWAN
Solar/Wind Harmer
-0.006
3130156CHOWAN
Solar/Wind Harmer
-0.006
316132AB2-190 GEN1
Solar/Wind Helper
0.976
316233AE1-074 FULL
Solar/Wind Helper
0.226
316312AB1-027
Solar/Wind Helper
0.27
3143873LANEXA
Solar/Wind Helper
0.076
316369SG1_INVT
Solar/Wind Helper
0.602
3145543BTLEBRO
Solar/Wind Harmer
-0.012
316210AC1-098 GEN
Solar/Wind Harmer
1.85
316131AB2-060 GEN
Solar/Wind Harmer
1.244
3146073TAR RVR
Solar/Wind Harmer
-0.011
3146083TARBORO
Solar/Wind Harmer
-0.011
964241AG1-285 GEN
Solar/Wind Harmer
8.72
3146263WOODLND
Solar/Wind Harmer
-0.011
316248AF1-058 C
Solar/Wind Harmer
0.328
960061AF2-297 GEN
Solar/Wind Harmer
5.444
316317KELFORD C
Solar/Wind Harmer
0.511
3145823KELFORD
Solar/Wind Harmer
-0.011
315785AD2-033 C
Solar/Wind Harmer
2.392
970257AG2-171 GEN
Solar/Wind Harmer
3.873
316463AE2-346 GEN
Solar/Wind Harmer
0.166
316140AB2-099
Solar/Wind Harmer
0.069
962331AG1-082 GEN
Solar/Wind Harmer
1.281
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
959311AF2-222 GEN
Solar/Wind Harmer
10.609
3146173TUNIS
Solar/Wind Harmer
-0.01
957521AF2-046 GEN
Solar/Wind Harmer
7.902
961681AG1-008 GEN
Solar/Wind Harmer
7.902
316283AC2-100 C
Solar/Wind Harmer
0.942
3145893MURPHYS
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
-0.01
3145933PARMELE
Solar/Wind Harmer
-0.01
966801AG1-551 GEN
Solar/Wind Harmer
1.233
3156021HOLLOMANSOL
Solar/Wind Harmer
1.319
971683AH1-343 GEN
Solar/Wind Harmer
4.208
3156081AA2-088 GEN
Solar/Wind Harmer
3.105
970909AG2-566 GEN
Solar/Wind Harmer
0.889
963181AG1-167 GEN
Solar/Wind Harmer
0.864
3144293JTRSVLE
Adder
0.261
3145963POPLR C
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.028
971193AH1-056 GEN
Solar/Wind Harmer
5.522
3146206CASHIE
Solar/Wind Harmer
-0.009
315737AD1-076 GEN
Solar/Wind Harmer
1.551
971157AH1-035 GEN
Solar/Wind Harmer
1.003
942461AE2-259 GEN
Solar/Wind Harmer
1.167
315614AA2-178 GEN
Solar/Wind Harmer
0.791
3146926FARMVIL
Solar/Wind Harmer
-0.004
3146376EDENTON
Solar/Wind Harmer
-0.006
315839AE2-212 C
Solar/Wind Helper
0.966
3142946ENON
Solar/Wind Helper
0.055
316473AC1-191 GEN
Solar/Wind Helper
1
315243AE2-183_GT3
50/50
2.516
3151051BRUNSWICKS1
50/50
4.094
3151021BRUNSWICKG1
50/50
1.972
971451AH1-221 GEN
50/50
5.991
3147043LAWRENC
50/50
1.32
3151391GASTONA
50/50
0.365
3151411GASTONB
50/50
0.365
3151531CLOVER1
50/50
2.556
3151261ROARAP2
50/50
0.148
316023GEN1_S
Solar/Wind Harmer
1.302
960081AF2-299 GEN
Solar/Wind Harmer
1.926
970919AG2-571 GEN
Solar/Wind Harmer
5.093
970087AG2-069 GEN
Solar/Wind Harmer
15.012
971795AH1-408 GEN
Solar/Wind Harmer
11.982
316011AB1-132 GEN
Solar/Wind Harmer
3.171
962571AG1-106 GEN
Solar/Wind Harmer
2.179
3145796HORNRTN
Solar/Wind Harmer
-0.048
3145796HORNRTN
Solar/Wind Harmer
-0.015
957481AF2-042 GEN
Solar/Wind Harmer
44.356
315722AD1-056 GEN
Solar/Wind Harmer
1.378
3145783HORNRTN
Solar/Wind Harmer
-0.013
315693AD1-088 GEN
Solar/Wind Harmer
6.574
939411AE1-173 GEN
Solar/Wind Harmer
65.115
962491AG1-098 GEN
Solar/Wind Harmer
8.662
316190AA2-174 GEN
Solar/Wind Harmer
0.157
316129AC1-054 GEN
Solar/Wind Harmer
1.1
315687AD1-152 GEN
Solar/Wind Harmer
1.509
971065AG2-659 GEN
Solar/Wind Harmer
6.236
3146233WITAKRS
Solar/Wind Harmer
-0.047
316359AB2-059 GEN
Solar/Wind Harmer
1.597
316049AB1-081 GEN
Solar/Wind Harmer
1.278
3142053HEARTS
Solar/Wind Harmer
0.139
3145543BTLEBRO
Solar/Wind Harmer
-0.012
3145543BTLEBRO
Solar/Wind Harmer
-0.009
316212AC1-099_GEN
Solar/Wind Harmer
1.028
316237AB2-079_GEN
Solar/Wind Harmer
0.35
961671AG1-007 GEN
Solar/Wind Harmer
0.143
3146083TARBORO
Solar/Wind Harmer
-0.011
3145493TOT1
Solar/Wind Harmer
0.335
970401AG2-262 GEN
Solar/Wind Harmer
0.731
3146263WOODLND
Solar/Wind Harmer
-0.011
3145823KELFORD
Solar/Wind Harmer
-0.011
316494AC1-189 GEN
Solar/Wind Harmer
1.164
3145683EARLEYS
Solar/Wind Harmer
-0.01
316003AC1-222 GEN
Solar/Wind Harmer
1.004
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
3146173TUNIS
Solar/Wind Harmer
-0.01
3145893MURPHYS
Solar/Wind Harmer
-0.04
3145893MURPHYS
Solar/Wind Harmer
0.296
3146293MARTNCO
Solar/Wind Harmer
0.061
970685AG2-442 GEN
Solar/Wind Harmer
8.535
316174AB2-169 GEN
Solar/Wind Harmer
1.424
963171AG1-166 GEN
Solar/Wind Harmer
1.152
971563AH1-280 GEN
Solar/Wind Harmer
1.152
3144293JTRSVLE
Adder
0.261
3145963POPLR C
Solar/Wind Harmer
-0.009
3146206CASHIE
Solar/Wind Harmer
-0.009
971547AH1-271 GEN
Solar/Wind Harmer
2.208
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.873
3146926FARMVIL
Solar/Wind Harmer
-0.004
3130156CHOWAN
Solar/Wind Harmer
-0.006
3142543TWELFTH
Solar/Wind Helper
0.024
3142433PROV 92
Solar/Wind Helper
0.7
316458AB2-190 GEN2
Solar/Wind Helper
0.976
3143526WINTERP
Solar/Wind Helper
0.769
3142416OLDCHRC
Solar/Wind Helper
0.369
3142416OLDCHRC
Solar/Wind Helper
0.141
3143226MDLTHAN
Solar/Wind Helper
0.133
970533AG2-339 GEN
50/50
14.043
970531AG2-338 GEN
50/50
5.617
315242AE2-183_GT2
50/50
2.516
315241AE2-183_GT1
50/50
2.5
972185AH1-677 GEN
50/50
9.069
3151041BRUNSWICKG3
50/50
1.972
972187AH1-678 GEN
50/50
4.526
3151361ROSEMG1
50/50
0.471
3151371ROSEMS1
50/50
0.292
3151381ROSEMG2
50/50
0.22
3144356SAPONY
Solar/Wind Harmer
0.948
970933AG2-581 GEN
Solar/Wind Harmer
15.092
316181AB2-040 GEN
Solar/Wind Harmer
2.139
3145796HORNRTN
Solar/Wind Harmer
-0.044
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
970099AG2-077 GEN
Solar/Wind Harmer
17.742
3145593CAROLNA
Solar/Wind Harmer
-0.013
3145593CAROLNA
Solar/Wind Harmer
-0.013
966811AG1-552 GEN
Solar/Wind Harmer
1.5
3145593CAROLNA
Solar/Wind Harmer
0.111
3145783HORNRTN
Solar/Wind Harmer
1.561
3145783HORNRTN
Solar/Wind Harmer
1.249
3145783HORNRTN
Solar/Wind Harmer
0.39
3145783HORNRTN
Solar/Wind Harmer
0.156
316426AA2-053 GEN
Solar/Wind Harmer
1.293
316274AC1-208 GEN
Solar/Wind Harmer
1.319
939181AE1-148 GEN
Solar/Wind Harmer
6.767
961601AG1-000A GEN
Solar/Wind Harmer
4.682
316263AC1-034 GEN
Solar/Wind Harmer
5.552
313527AB2-043 GEN
Solar/Wind Harmer
1.888
3145493TOT1
Solar/Wind Harmer
0.175
3145453TOT5
Solar/Wind Harmer
0.105
3145603CNETO
Solar/Wind Harmer
0.07
962561AG1-105 GEN
Solar/Wind Harmer
6.333
964791AG1-342 GEN
Solar/Wind Harmer
2.391
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970323AG2-213 GEN
Solar/Wind Harmer
5.164
971775AH1-396 GEN
Solar/Wind Harmer
0.735
316034AC1-036 C
Solar/Wind Harmer
0.191
971741AH1-377 GEN
Solar/Wind Harmer
11.893
3146173TUNIS
Solar/Wind Harmer
-0.01
3146173TUNIS
Solar/Wind Harmer
-0.01
316222AC1-221 GEN
Solar/Wind Harmer
1.018
3145893MURPHYS
Solar/Wind Harmer
0.278
3145893MURPHYS
Solar/Wind Harmer
-0.018
3145933PARMELE
Solar/Wind Harmer
-0.02
3145933PARMELE
Solar/Wind Harmer
-0.01
970301AG2-198 GEN
Solar/Wind Harmer
4.681
958211AF2-115 GEN
Solar/Wind Harmer
1.439
963191AG1-168 GEN
Solar/Wind Harmer
0.864
3144293JTRSVLE
Adder
0.261
3144293JTRSVLE
Adder
0.22
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.007
316065AD1-022 GEN
Solar/Wind Harmer
4.293
942751AE2-291 GEN
Solar/Wind Harmer
4.718
315742AE1-103 GEN
Solar/Wind Harmer
0.706
3146376EDENTON
Solar/Wind Harmer
0.191
3146376EDENTON
Solar/Wind Harmer
0.191
316240AF1-291 C
Solar/Wind Helper
0.402
3142946ENON
Solar/Wind Helper
0.017
966871AG1-558 GEN
Solar/Wind Helper
0.221
3143526WINTERP
Solar/Wind Helper
0.769
316468AD1-105 GEN
Solar/Wind Helper
0.714
316075AC2-137 C
Solar/Wind Helper
0.21
316033AB2-134 GEN
Solar/Wind Helper
0.43
315697AD1-025 GEN
Solar/Wind Helper
1.43
CPLELTFEXP_CPLE->PJM
CLTF
6.792
CBM West 2LTFEXP_CBM-W2->PJM
CBM
24.55
LAGNLTFEXP_LAGN->PJM
CLTF
4.648
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.569
TVALTFEXP_TVA->PJM
CLTF
2.315
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.091
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.934
MECLTFEXP_MEC->PJM
CLTF
2.276
SIGELTFEXP_SIGE->PJM
CLTF
0.068
NYPJM->LTFIMP_NY
CLTF
0.817
LGEELTFEXP_LGEE->PJM
CLTF
0.818
WECLTFEXP_WEC->PJM
CLTF
0.427

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:145.18 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1428.84
MW Contribution:8.81
Bus #Bus NameTypeMW Contribution
970533AG2-339 GEN
50/50
10.894
970531AG2-338 GEN
50/50
4.358
3151361ROSEMG1
50/50
0.433
3151371ROSEMS1
50/50
0.268
3151381ROSEMG2
50/50
0.203
315242AE2-183_GT2
50/50
1.956
315241AE2-183_GT1
50/50
1.944
972185AH1-677 GEN
50/50
7.053
3151041BRUNSWICKG3
50/50
1.536
972187AH1-678 GEN
50/50
3.524
970535AG2-341 GEN
50/50
1.57
3152661PLYWOOD A
50/50
0.18
3144356SAPONY
Solar/Wind Harmer
1.857
315779AE2-040
50/50
3.099
315244AE2-183_ST
50/50
3.382
963041AG1-153 GEN
50/50
3.109
3151281ROARAP4
50/50
0.132
3151281ROARAP4
50/50
0.123
3151541CLOVER2
50/50
2.008
3151611KERR 4
50/50
0.187
3151621KERR 5
50/50
0.187
3151631KERR 6
50/50
0.187
3151641KERR 7
50/50
0.187
316315AB2-025 C
Solar/Wind Harmer
0.179
315814AE2-033 C
Solar/Wind Harmer
17.298
316087AB2-174 GEN
Solar/Wind Harmer
0.004
315652AC1-086 GEN
Solar/Wind Harmer
13.694
941031AE2-094 GEN
Solar/Wind Harmer
22.572
944011AF1-069 GEN
Solar/Wind Harmer
7.375
3145796HORNRTN
Solar/Wind Harmer
0.385
3145796HORNRTN
Solar/Wind Harmer
0.048
970673AG2-436 GEN
Solar/Wind Harmer
25.561
970673AG2-436 GEN
Solar/Wind Harmer
17.041
971967AH1-528 GEN
Solar/Wind Harmer
18.68
3137643SOCKMAN
Solar/Wind Harmer
0.464
970085AG2-068 GEN
Solar/Wind Harmer
5.942
970581AG2-369 GEN
Solar/Wind Harmer
5.11
315607AA1-063A GEN
Solar/Wind Harmer
0.204
3146043SEABORD
Solar/Wind Harmer
0.098
970831AG2-522 GEN
Solar/Wind Harmer
4.182
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.379
3145573BETHELC
Solar/Wind Harmer
0.092
3145573BETHELC
Solar/Wind Harmer
0.092
316420AA1-050 GEN
Solar/Wind Harmer
0.003
3145683EARLEYS
Solar/Wind Harmer
0.179
3145683EARLEYS
Solar/Wind Harmer
0.09
3145683EARLEYS
Solar/Wind Harmer
0.09
3145513AHOSKIE
Solar/Wind Harmer
0.186
3145513AHOSKIE
Solar/Wind Harmer
0.089
957861AF2-080 GEN
Solar/Wind Harmer
3.828
3145893MURPHYS
Solar/Wind Harmer
0.235
3145893MURPHYS
Solar/Wind Harmer
0.087
965291AG1-394 GEN
Solar/Wind Harmer
0.382
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316005AA1-067
Solar/Wind Harmer
0.092
3145746EVERETS
Solar/Wind Harmer
0.34
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
970181AG2-120 GEN
Solar/Wind Harmer
1.064
3146206CASHIE
Solar/Wind Harmer
0.08
970601AG2-382 GEN
Solar/Wind Harmer
3.008
316118AC1-105 GEN
Solar/Wind Harmer
0.206
3147173SINAI
Solar/Wind Harmer
0.078
3147243WELCO
Solar/Wind Harmer
0.049
315732AD1-074 GEN1
Solar/Wind Harmer
0.439
315733AD1-074 GEN2
Solar/Wind Harmer
0.439
315735AD1-075 GEN1
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
1.275
3130546PLYMOUTH
Solar/Wind Harmer
0.076
3144303KENBRDG
Solar/Wind Harmer
0.06
3143316POE
Solar/Wind Harmer
0.287
315816AE2-034 GEN
Solar/Wind Harmer
0.308
970683AG2-441 GEN
Solar/Wind Harmer
4.722
970681AG2-440 GEN
Solar/Wind Harmer
3.778
3130156CHOWAN
Solar/Wind Harmer
0.066
3130156CHOWAN
Solar/Wind Harmer
0.066
946301AF1-294 GEN
Solar/Wind Harmer
1.311
961791AG1-021 GEN
Solar/Wind Harmer
0.638
970865AG2-541 GEN
Solar/Wind Harmer
2.298
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
315657AE1-056 GEN
Solar/Wind Harmer
2.185
316123AC1-075 GEN
Solar/Wind Harmer
0.08
970165AG2-112 GEN
Solar/Wind Harmer
0.473
970163AG2-111 GEN
Solar/Wind Harmer
0.451
3145176PASQUOTANK
Solar/Wind Harmer
0.036
316321Z2-027
Solar/Wind Harmer
0.011
3146396TANGLEW
Solar/Wind Harmer
0.161
313526AB2-022
Solar/Wind Harmer
0.031
3146486SUNBURY
Solar/Wind Harmer
0.057
3146486SUNBURY
Solar/Wind Harmer
0.057
3151391GASTONA
50/50
0.337
3151411GASTONB
50/50
0.337
3151031BRUNSWICKG2
50/50
1.536
3151261ROARAP2
50/50
0.133
970413AG2-270 GEN
50/50
8.806
3151591KERR 2
50/50
0.187
316365GEN2_N
Solar/Wind Harmer
0.354
313506AB2-031 GEN
Solar/Wind Harmer
0.385
3147043LAWRENC
Solar/Wind Harmer
0.074
3145796HORNRTN
Solar/Wind Harmer
0.481
3145796HORNRTN
Solar/Wind Harmer
0.12
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
970917AG2-570 GEN
Solar/Wind Harmer
9.95
315724AD1-057 GEN
Solar/Wind Harmer
0.4
3151391GASTONA
50/50
0.337
3151411GASTONB
50/50
0.337
3147043LAWRENC
50/50
1.178
315243AE2-183_GT3
50/50
1.956
3151051BRUNSWICKS1
50/50
3.187
3151021BRUNSWICKG1
50/50
1.536
971451AH1-221 GEN
50/50
4.664
3151261ROARAP2
50/50
0.136
3151531CLOVER1
50/50
2.018
3151601KERR 3
50/50
0.187
3151581KERR 1
50/50
0.067
316023GEN1_S
Solar/Wind Harmer
0.354
960081AF2-299 GEN
Solar/Wind Harmer
1.332
971795AH1-408 GEN
Solar/Wind Harmer
8.516
316011AB1-132 GEN
Solar/Wind Harmer
2.263
962571AG1-106 GEN
Solar/Wind Harmer
1.771
3145796HORNRTN
Solar/Wind Harmer
0.397
3145796HORNRTN
Solar/Wind Harmer
0.12
940641AE2-051 GEN
Solar/Wind Harmer
9.263
970919AG2-571 GEN
Solar/Wind Harmer
3.98
970087AG2-069 GEN
Solar/Wind Harmer
8.913
3145783HORNRTN
Solar/Wind Harmer
0.107
315722AD1-056 GEN
Solar/Wind Harmer
0.674
316190AA2-174 GEN
Solar/Wind Harmer
0
939411AE1-173 GEN
Solar/Wind Harmer
42.901
957481AF2-042 GEN
Solar/Wind Harmer
26.456
316212AC1-099_GEN
Solar/Wind Harmer
0.502
316129AC1-054 GEN
Solar/Wind Harmer
0.364
971065AG2-659 GEN
Solar/Wind Harmer
4.087
3146233WITAKRS
Solar/Wind Harmer
0.38
3146263WOODLND
Solar/Wind Harmer
0.095
316359AB2-059 GEN
Solar/Wind Harmer
0.34
316049AB1-081 GEN
Solar/Wind Harmer
0.541
3142053HEARTS
Solar/Wind Harmer
0.166
3145543BTLEBRO
Solar/Wind Harmer
0.094
3145543BTLEBRO
Solar/Wind Harmer
0.075
3145823KELFORD
Solar/Wind Harmer
0.092
315693AD1-088 GEN
Solar/Wind Harmer
4.418
961671AG1-007 GEN
Solar/Wind Harmer
0.014
3146083TARBORO
Solar/Wind Harmer
0.092
3145493TOT1
Solar/Wind Harmer
0.407
962491AG1-098 GEN
Solar/Wind Harmer
5.172
3145683EARLEYS
Solar/Wind Harmer
0.09
316494AC1-189 GEN
Solar/Wind Harmer
0.3
315687AD1-152 GEN
Solar/Wind Harmer
0.003
3146173TUNIS
Solar/Wind Harmer
0.088
3145893MURPHYS
Solar/Wind Harmer
0.348
3145893MURPHYS
Solar/Wind Harmer
0.387
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
3146293MARTNCO
Solar/Wind Harmer
0.078
970401AG2-262 GEN
Solar/Wind Harmer
0.478
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3146206CASHIE
Solar/Wind Harmer
0.08
971547AH1-271 GEN
Solar/Wind Harmer
1.719
3145963POPLR C
Solar/Wind Harmer
0.08
316003AC1-222 GEN
Solar/Wind Harmer
0.002
3145663CRESWEL
Solar/Wind Harmer
0.201
971163AH1-040 GEN
Solar/Wind Harmer
5.738
970685AG2-442 GEN
Solar/Wind Harmer
5.289
3130156CHOWAN
Solar/Wind Harmer
0.066
963171AG1-166 GEN
Solar/Wind Harmer
0.354
971563AH1-280 GEN
Solar/Wind Harmer
0.708
3144293JTRSVLE
Adder
0.211
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
316294AC1-161 GEN
Solar/Wind Harmer
1.066
3146516WINFALL
Solar/Wind Harmer
0.194
3146516WINFALL
Solar/Wind Harmer
0.06
944591AF1-124 GEN
Solar/Wind Harmer
12.705
3142543TWELFTH
Solar/Wind Helper
0.024
316458AB2-190 GEN2
Solar/Wind Helper
0.895
3142433PROV 92
Solar/Wind Helper
0.616
3143526WINTERP
Solar/Wind Helper
0.72
3143226MDLTHAN
Solar/Wind Helper
0.125
3142416OLDCHRC
Solar/Wind Helper
0.323
3142416OLDCHRC
Solar/Wind Helper
0.124
316132AB2-190 GEN1
Solar/Wind Helper
0.895
316233AE1-074 FULL
Solar/Wind Helper
0.212
316312AB1-027
Solar/Wind Helper
0.237
316210AC1-098 GEN
Solar/Wind Harmer
0.901
316327AA2-057 GEN
Solar/Wind Harmer
0.146
3146233WITAKRS
Solar/Wind Harmer
0.48
3146233WITAKRS
Solar/Wind Harmer
0.065
3138543CONSLDL
Solar/Wind Harmer
0.063
961601AG1-000A GEN
Solar/Wind Harmer
6.766
3146263WOODLND
Solar/Wind Harmer
0.095
971623AH1-311 GEN
Solar/Wind Harmer
0.189
3145543BTLEBRO
Solar/Wind Harmer
0.094
3145543BTLEBRO
Solar/Wind Harmer
0.094
316478AD1-087 GEN
Solar/Wind Harmer
0.329
316486AD2-202 GEN
Solar/Wind Harmer
0.097
316317KELFORD C
Solar/Wind Harmer
0.009
3145823KELFORD
Solar/Wind Harmer
0.092
3146073TAR RVR
Solar/Wind Harmer
0.092
3146083TARBORO
Solar/Wind Harmer
0.092
316463AE2-346 GEN
Solar/Wind Harmer
0.076
316140AB2-099
Solar/Wind Harmer
0.032
962331AG1-082 GEN
Solar/Wind Harmer
0.95
3146173TUNIS
Solar/Wind Harmer
0.088
957521AF2-046 GEN
Solar/Wind Harmer
6.513
961681AG1-008 GEN
Solar/Wind Harmer
6.513
3145893MURPHYS
Solar/Wind Harmer
0.146
3145893MURPHYS
Solar/Wind Harmer
0.087
3156021HOLLOMANSOL
Solar/Wind Harmer
0.393
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
316131AB2-060 GEN
Solar/Wind Harmer
0.268
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3145933PARMELE
Solar/Wind Harmer
0.084
966801AG1-551 GEN
Solar/Wind Harmer
0.976
964241AG1-285 GEN
Solar/Wind Harmer
5.485
3146206CASHIE
Solar/Wind Harmer
0.08
3145963POPLR C
Solar/Wind Harmer
0.08
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.344
315785AD2-033 C
Solar/Wind Harmer
0.629
315737AD1-076 GEN
Solar/Wind Harmer
0.983
971157AH1-035 GEN
Solar/Wind Harmer
0.908
970257AG2-171 GEN
Solar/Wind Harmer
2.416
959311AF2-222 GEN
Solar/Wind Harmer
6.592
316283AC2-100 C
Solar/Wind Harmer
0.142
315614AA2-178 GEN
Solar/Wind Harmer
0.41
971683AH1-343 GEN
Solar/Wind Harmer
2.584
3146376EDENTON
Solar/Wind Harmer
0.067
963181AG1-167 GEN
Solar/Wind Harmer
0.266
3144293JTRSVLE
Adder
0.211
970909AG2-566 GEN
Solar/Wind Harmer
0.692
3147133PAMPLIN
Solar/Wind Harmer
0.199
971193AH1-056 GEN
Solar/Wind Harmer
3.857
315773AC2-141 GEN
Solar/Wind Harmer
2.248
3146626S HERTFORD
Solar/Wind Harmer
0.061
3145273HOLLAND
Solar/Wind Harmer
0.046
3146516WINFALL
Solar/Wind Harmer
0.06
316435W1029_GEN3
Solar/Wind Harmer
0
316320Y1-086
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
12.66
944601AF1-125 GEN
Solar/Wind Harmer
12.465
315839AE2-212 C
Solar/Wind Helper
0.986
316473AC1-191 GEN
Solar/Wind Helper
0.925
3142946ENON
Solar/Wind Helper
0.049
316181AB2-040 GEN
Solar/Wind Harmer
0.181
3145796HORNRTN
Solar/Wind Harmer
0.361
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
970933AG2-581 GEN
Solar/Wind Harmer
8.936
3145593CAROLNA
Solar/Wind Harmer
0.109
3145593CAROLNA
Solar/Wind Harmer
0.109
966811AG1-552 GEN
Solar/Wind Harmer
1.182
3145593CAROLNA
Solar/Wind Harmer
0.136
3145783HORNRTN
Solar/Wind Harmer
1.911
3145783HORNRTN
Solar/Wind Harmer
1.529
3145783HORNRTN
Solar/Wind Harmer
0.478
3145783HORNRTN
Solar/Wind Harmer
0.191
316426AA2-053 GEN
Solar/Wind Harmer
0.356
316274AC1-208 GEN
Solar/Wind Harmer
0.518
970099AG2-077 GEN
Solar/Wind Harmer
10.582
961601AG1-000A GEN
Solar/Wind Harmer
1.691
316263AC1-034 GEN
Solar/Wind Harmer
3.592
3145493TOT1
Solar/Wind Harmer
0.212
3145453TOT5
Solar/Wind Harmer
0.127
3145603CNETO
Solar/Wind Harmer
0.085
939181AE1-148 GEN
Solar/Wind Harmer
4.3
3146173TUNIS
Solar/Wind Harmer
0.088
3146173TUNIS
Solar/Wind Harmer
0.088
3145893MURPHYS
Solar/Wind Harmer
0.583
3145893MURPHYS
Solar/Wind Harmer
0.157
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3145933PARMELE
Solar/Wind Harmer
0.168
3145933PARMELE
Solar/Wind Harmer
0.084
962561AG1-105 GEN
Solar/Wind Harmer
3.947
964791AG1-342 GEN
Solar/Wind Harmer
1.566
3146843MT LREL
Solar/Wind Harmer
0.081
3146843MT LREL
Solar/Wind Harmer
0.081
316065AD1-022 GEN
Solar/Wind Harmer
3.64
970323AG2-213 GEN
Solar/Wind Harmer
3.221
971775AH1-396 GEN
Solar/Wind Harmer
0.121
316034AC1-036 C
Solar/Wind Harmer
0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.303
971741AH1-377 GEN
Solar/Wind Harmer
7.057
3146376EDENTON
Solar/Wind Harmer
0.296
3146376EDENTON
Solar/Wind Harmer
0.296
958211AF2-115 GEN
Solar/Wind Harmer
0.797
963191AG1-168 GEN
Solar/Wind Harmer
0.266
3144293JTRSVLE
Adder
0.211
3144293JTRSVLE
Adder
0.178
315742AE1-103 GEN
Solar/Wind Harmer
0.001
970301AG2-198 GEN
Solar/Wind Harmer
2.77
3147133PAMPLIN
Solar/Wind Harmer
0.063
3147133PAMPLIN
Solar/Wind Harmer
0.051
3146626S HERTFORD
Solar/Wind Harmer
0.061
3146626S HERTFORD
Solar/Wind Harmer
0.061
3146516WINFALL
Solar/Wind Harmer
0.06
3146516WINFALL
Solar/Wind Harmer
0.06
3146516WINFALL
Solar/Wind Harmer
0.06
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146386ELIZ CT
Solar/Wind Harmer
0.057
316240AF1-291 C
Solar/Wind Helper
0.411
966871AG1-558 GEN
Solar/Wind Helper
0.204
3142946ENON
Solar/Wind Helper
0.015
3143526WINTERP
Solar/Wind Helper
0.72
316468AD1-105 GEN
Solar/Wind Helper
0.653
316075AC2-137 C
Solar/Wind Helper
0.178
CPLELTFEXP_CPLE->PJM
CLTF
5.631
CBM West 2LTFEXP_CBM-W2->PJM
CBM
19.951
LAGNLTFEXP_LAGN->PJM
CLTF
3.79
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.991
TVALTFEXP_TVA->PJM
CLTF
1.888
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.11
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.461
MECLTFEXP_MEC->PJM
CLTF
1.839
SIGELTFEXP_SIGE->PJM
CLTF
0.055
NYPJM->LTFIMP_NY
CLTF
0.691
LGEELTFEXP_LGEE->PJM
CLTF
0.659
WECLTFEXP_WEC->PJM
CLTF
0.343

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2002_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.21 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1192.96
MW Contribution:6.97
Bus #Bus NameTypeMW Contribution
3151361ROSEMG1
50/50
0.408
3151371ROSEMS1
50/50
0.253
3151381ROSEMG2
50/50
0.191
970533AG2-339 GEN
50/50
8.434
970531AG2-338 GEN
50/50
3.373
315779AE2-040
50/50
3.401
3151281ROARAP4
50/50
0.118
3151281ROARAP4
50/50
0.11
315244AE2-183_ST
50/50
2.625
963041AG1-153 GEN
50/50
2.415
3151611KERR 4
50/50
0.157
3151621KERR 5
50/50
0.157
3151631KERR 6
50/50
0.157
3151641KERR 7
50/50
0.157
3151541CLOVER2
50/50
1.589
316315AB2-025 C
Solar/Wind Harmer
0.197
315814AE2-033 C
Solar/Wind Harmer
18.936
316087AB2-174 GEN
Solar/Wind Harmer
0.004
315652AC1-086 GEN
Solar/Wind Harmer
13.019
3145796HORNRTN
Solar/Wind Harmer
0.362
3145796HORNRTN
Solar/Wind Harmer
0.045
3137643SOCKMAN
Solar/Wind Harmer
0.427
941031AE2-094 GEN
Solar/Wind Harmer
17.475
944011AF1-069 GEN
Solar/Wind Harmer
5.71
970673AG2-436 GEN
Solar/Wind Harmer
19.819
970673AG2-436 GEN
Solar/Wind Harmer
13.213
971967AH1-528 GEN
Solar/Wind Harmer
14.51
970085AG2-068 GEN
Solar/Wind Harmer
4.631
970581AG2-369 GEN
Solar/Wind Harmer
3.982
970831AG2-522 GEN
Solar/Wind Harmer
3.621
315607AA1-063A GEN
Solar/Wind Harmer
0.17
316319Z2-044 C
Solar/Wind Harmer
0
3146043SEABORD
Solar/Wind Harmer
0.081
3146033SCOT NK
Solar/Wind Harmer
0.318
3145573BETHELC
Solar/Wind Harmer
0.078
3145573BETHELC
Solar/Wind Harmer
0.078
316420AA1-050 GEN
Solar/Wind Harmer
0.003
957861AF2-080 GEN
Solar/Wind Harmer
3.178
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3145683EARLEYS
Solar/Wind Harmer
0.142
3145683EARLEYS
Solar/Wind Harmer
0.071
3145683EARLEYS
Solar/Wind Harmer
0.071
3145513AHOSKIE
Solar/Wind Harmer
0.145
3145513AHOSKIE
Solar/Wind Harmer
0.07
316005AA1-067
Solar/Wind Harmer
0.074
3145746EVERETS
Solar/Wind Harmer
0.274
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
970181AG2-120 GEN
Solar/Wind Harmer
0.856
316118AC1-105 GEN
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
0.175
3145893MURPHYS
Solar/Wind Harmer
0.065
971443AH1-215 GEN
Solar/Wind Harmer
1.078
3144303KENBRDG
Solar/Wind Harmer
0.051
3147173SINAI
Solar/Wind Harmer
0.064
3147243WELCO
Solar/Wind Harmer
0.04
965291AG1-394 GEN
Solar/Wind Harmer
0.275
970683AG2-441 GEN
Solar/Wind Harmer
3.967
970681AG2-440 GEN
Solar/Wind Harmer
3.174
3146206CASHIE
Solar/Wind Harmer
0.059
970601AG2-382 GEN
Solar/Wind Harmer
2.2
3143316POE
Solar/Wind Helper
1.93
316132AB2-190 GEN1
Solar/Wind Helper
1.544
316369SG1_INVT
Solar/Wind Helper
1.002
316312AB1-027
Solar/Wind Helper
0.328
3143873LANEXA
Solar/Wind Helper
0.095
316233AE1-074 FULL
Solar/Wind Helper
0.214
315662AE1-191 GEN
Solar/Wind Helper
0.666
315666AE1-190 GEN
Solar/Wind Helper
0.167
316059AD1-063 C
Solar/Wind Helper
0.122
3141813NORNECK
Solar/Wind Helper
0.113
3141783LANCAST
Solar/Wind Helper
0.068
3141783LANCAST
Solar/Wind Helper
0.045
3141913WHIT STONE
Solar/Wind Helper
0.113
3138133OCRAN
Solar/Wind Helper
0.034
957601AF2-054 GEN
Solar/Wind Helper
0.152
3141873WAN 176
Solar/Wind Helper
0.023
3151391GASTONA
50/50
0.32
3151411GASTONB
50/50
0.32
3147043LAWRENC
50/50
1.13
3151261ROARAP2
50/50
0.121
315243AE2-183_GT3
50/50
1.518
3151051BRUNSWICKS1
50/50
2.476
3151021BRUNSWICKG1
50/50
1.193
971451AH1-221 GEN
50/50
3.623
3151601KERR 3
50/50
0.157
3151581KERR 1
50/50
0.056
3151531CLOVER1
50/50
1.596
316023GEN1_S
Solar/Wind Harmer
0.362
960081AF2-299 GEN
Solar/Wind Harmer
1.316
971795AH1-408 GEN
Solar/Wind Harmer
8.254
316011AB1-132 GEN
Solar/Wind Harmer
2.152
962571AG1-106 GEN
Solar/Wind Harmer
1.684
3145796HORNRTN
Solar/Wind Harmer
0.374
3145796HORNRTN
Solar/Wind Harmer
0.113
315722AD1-056 GEN
Solar/Wind Harmer
0.612
3145783HORNRTN
Solar/Wind Harmer
0.096
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
3.101
970087AG2-069 GEN
Solar/Wind Harmer
6.946
940641AE2-051 GEN
Solar/Wind Harmer
6.931
316129AC1-054 GEN
Solar/Wind Harmer
0.314
316212AC1-099_GEN
Solar/Wind Harmer
0.43
3146233WITAKRS
Solar/Wind Harmer
0.33
971065AG2-659 GEN
Solar/Wind Harmer
3.51
316359AB2-059 GEN
Solar/Wind Harmer
0.295
316049AB1-081 GEN
Solar/Wind Harmer
0.471
3142053HEARTS
Solar/Wind Harmer
0.145
3145543BTLEBRO
Solar/Wind Harmer
0.082
3145543BTLEBRO
Solar/Wind Harmer
0.066
3146263WOODLND
Solar/Wind Harmer
0.078
957481AF2-042 GEN
Solar/Wind Harmer
20.812
961671AG1-007 GEN
Solar/Wind Harmer
0.012
3146083TARBORO
Solar/Wind Harmer
0.078
3145493TOT1
Solar/Wind Harmer
0.346
3145823KELFORD
Solar/Wind Harmer
0.075
316494AC1-189 GEN
Solar/Wind Harmer
0.249
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
3.49
962491AG1-098 GEN
Solar/Wind Harmer
4.086
3145683EARLEYS
Solar/Wind Harmer
0.071
315687AD1-152 GEN
Solar/Wind Harmer
0.002
939411AE1-173 GEN
Solar/Wind Harmer
30.084
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.068
970401AG2-262 GEN
Solar/Wind Harmer
0.397
3146293MARTNCO
Solar/Wind Harmer
0.061
3145893MURPHYS
Solar/Wind Harmer
0.259
3145893MURPHYS
Solar/Wind Harmer
0.288
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145963POPLR C
Solar/Wind Harmer
0.06
316003AC1-222 GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
4.444
3146206CASHIE
Solar/Wind Harmer
0.059
971547AH1-271 GEN
Solar/Wind Harmer
1.257
3142543TWELFTH
Solar/Wind Helper
0.031
316458AB2-190 GEN2
Solar/Wind Helper
1.544
316381AD1-082 GEN
Solar/Wind Helper
1.346
3142433PROV 92
Solar/Wind Helper
0.863
3142416OLDCHRC
Solar/Wind Helper
0.448
3142416OLDCHRC
Solar/Wind Helper
0.172
3143526WINTERP
Solar/Wind Helper
0.727
3141766HARMONY
Solar/Wind Helper
0.024
964211AG1-282 GEN
Solar/Wind Helper
0.157
3141726DUNNSVL
Solar/Wind Helper
0.465
3138133OCRAN
Solar/Wind Helper
0.068
315242AE2-183_GT2
50/50
1.518
315241AE2-183_GT1
50/50
1.509
972185AH1-677 GEN
50/50
5.473
3151041BRUNSWICKG3
50/50
1.193
972187AH1-678 GEN
50/50
2.737
970535AG2-341 GEN
50/50
1.329
3152661PLYWOOD A
50/50
0.148
3144356SAPONY
Solar/Wind Harmer
2.038
316181AB2-040 GEN
Solar/Wind Harmer
0.172
3145796HORNRTN
Solar/Wind Harmer
0.34
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
3142666NORTHAMPTON
Solar/Wind Harmer
0.067
3145593CAROLNA
Solar/Wind Harmer
0.097
3145593CAROLNA
Solar/Wind Harmer
0.097
966811AG1-552 GEN
Solar/Wind Harmer
1.057
3145593CAROLNA
Solar/Wind Harmer
0.121
3145783HORNRTN
Solar/Wind Harmer
1.703
3145783HORNRTN
Solar/Wind Harmer
1.362
3145783HORNRTN
Solar/Wind Harmer
0.426
3145783HORNRTN
Solar/Wind Harmer
0.17
316426AA2-053 GEN
Solar/Wind Harmer
0.313
970933AG2-581 GEN
Solar/Wind Harmer
6.963
316274AC1-208 GEN
Solar/Wind Harmer
0.45
961601AG1-000A GEN
Solar/Wind Harmer
1.477
316263AC1-034 GEN
Solar/Wind Harmer
3.125
970099AG2-077 GEN
Solar/Wind Harmer
8.325
3145493TOT1
Solar/Wind Harmer
0.181
3145453TOT5
Solar/Wind Harmer
0.108
3145603CNETO
Solar/Wind Harmer
0.072
939181AE1-148 GEN
Solar/Wind Harmer
3.627
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.291
3146173TUNIS
Solar/Wind Harmer
0.068
3146173TUNIS
Solar/Wind Harmer
0.068
964791AG1-342 GEN
Solar/Wind Harmer
1.3
3146843MT LREL
Solar/Wind Harmer
0.068
3146843MT LREL
Solar/Wind Harmer
0.068
3145933PARMELE
Solar/Wind Harmer
0.132
3145933PARMELE
Solar/Wind Harmer
0.066
3145893MURPHYS
Solar/Wind Harmer
0.433
3145893MURPHYS
Solar/Wind Harmer
0.116
970323AG2-213 GEN
Solar/Wind Harmer
2.721
971775AH1-396 GEN
Solar/Wind Harmer
0.102
316034AC1-036 C
Solar/Wind Harmer
0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.245
316065AD1-022 GEN
Solar/Wind Harmer
2.617
971741AH1-377 GEN
Solar/Wind Harmer
5.589
316240AF1-291 C
Solar/Wind Helper
0.691
3142946ENON
Solar/Wind Helper
0.022
316033AB2-134 GEN
Solar/Wind Helper
0.717
315697AD1-025 GEN
Solar/Wind Helper
2.382
966871AG1-558 GEN
Solar/Wind Helper
0.262
316075AC2-137 C
Solar/Wind Helper
0.263
316468AD1-105 GEN
Solar/Wind Helper
0.815
3143526WINTERP
Solar/Wind Helper
0.727
316077AC2-138 C
Solar/Wind Helper
0.107
316487AF1-042 GEN
Solar/Wind Helper
0.114
3151391GASTONA
50/50
0.32
3151411GASTONB
50/50
0.32
3151261ROARAP2
50/50
0.119
3151031BRUNSWICKG2
50/50
1.193
3151591KERR 2
50/50
0.157
970413AG2-270 GEN
50/50
6.966
316365GEN2_N
Solar/Wind Harmer
0.362
313506AB2-031 GEN
Solar/Wind Harmer
0.366
3147043LAWRENC
Solar/Wind Harmer
0.071
3145796HORNRTN
Solar/Wind Harmer
0.453
3145796HORNRTN
Solar/Wind Harmer
0.113
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
315724AD1-057 GEN
Solar/Wind Harmer
0.363
970917AG2-570 GEN
Solar/Wind Harmer
7.751
316327AA2-057 GEN
Solar/Wind Harmer
0.127
961601AG1-000A GEN
Solar/Wind Harmer
5.909
316210AC1-098 GEN
Solar/Wind Harmer
0.77
3146233WITAKRS
Solar/Wind Harmer
0.417
3146233WITAKRS
Solar/Wind Harmer
0.056
3138543CONSLDL
Solar/Wind Harmer
0.055
971623AH1-311 GEN
Solar/Wind Harmer
0.164
3145543BTLEBRO
Solar/Wind Harmer
0.082
3145543BTLEBRO
Solar/Wind Harmer
0.082
3146263WOODLND
Solar/Wind Harmer
0.078
3146073TAR RVR
Solar/Wind Harmer
0.078
3146083TARBORO
Solar/Wind Harmer
0.078
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.075
316478AD1-087 GEN
Solar/Wind Harmer
0.26
316486AD2-202 GEN
Solar/Wind Harmer
0.076
316131AB2-060 GEN
Solar/Wind Harmer
0.229
964241AG1-285 GEN
Solar/Wind Harmer
4.665
316463AE2-346 GEN
Solar/Wind Harmer
0.06
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.742
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.068
3156021HOLLOMANSOL
Solar/Wind Harmer
0.305
3145933PARMELE
Solar/Wind Harmer
0.066
966801AG1-551 GEN
Solar/Wind Harmer
0.769
957521AF2-046 GEN
Solar/Wind Harmer
4.888
961681AG1-008 GEN
Solar/Wind Harmer
4.888
315785AD2-033 C
Solar/Wind Harmer
0.532
3145893MURPHYS
Solar/Wind Harmer
0.108
3145893MURPHYS
Solar/Wind Harmer
0.065
970257AG2-171 GEN
Solar/Wind Harmer
2.041
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.715
959311AF2-222 GEN
Solar/Wind Harmer
5.561
3145963POPLR C
Solar/Wind Harmer
0.06
3156081AA2-088 GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.059
316283AC2-100 C
Solar/Wind Harmer
0.115
971683AH1-343 GEN
Solar/Wind Harmer
2.095
315839AE2-212 C
Solar/Wind Helper
1.113
3142946ENON
Solar/Wind Helper
0.074
316473AC1-191 GEN
Solar/Wind Helper
1.189
316280AD1-041 GEN
Solar/Wind Helper
0.416
316404AE1-155 C
Solar/Wind Helper
0.956
316484AD2-074 GEN
Solar/Wind Helper
0.219
316156AD2-030 GEN
Solar/Wind Helper
0.171
CPLELTFEXP_CPLE->PJM
CLTF
4.572
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.518
LAGNLTFEXP_LAGN->PJM
CLTF
3.11
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.716
TVALTFEXP_TVA->PJM
CLTF
1.547
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.423
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.312
MECLTFEXP_MEC->PJM
CLTF
1.548
SIGELTFEXP_SIGE->PJM
CLTF
0.046
NYPJM->LTFIMP_NY
CLTF
0.457
LGEELTFEXP_LGEE->PJM
CLTF
0.557
WECLTFEXP_WEC->PJM
CLTF
0.293

Details for 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6POE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 249_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.58 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:845.48
MW Contribution:5.5
Bus #Bus NameTypeMW Contribution
3151361ROSEMG1
50/50
0.317
3151371ROSEMS1
50/50
0.196
3151381ROSEMG2
50/50
0.148
970533AG2-339 GEN
50/50
6.689
970531AG2-338 GEN
50/50
2.675
315242AE2-183_GT2
50/50
1.203
315241AE2-183_GT1
50/50
1.196
972185AH1-677 GEN
50/50
4.338
3151041BRUNSWICKG3
50/50
0.945
972187AH1-678 GEN
50/50
2.169
970535AG2-341 GEN
50/50
1.039
3144356SAPONY
Solar/Wind Harmer
1.648
316181AB2-040 GEN
Solar/Wind Harmer
0.133
3145796HORNRTN
Solar/Wind Harmer
0.264
3142666NORTHAMPTON
Solar/Wind Harmer
0.086
3142666NORTHAMPTON
Solar/Wind Harmer
0.086
3142666NORTHAMPTON
Solar/Wind Harmer
0.086
3142666NORTHAMPTON
Solar/Wind Harmer
0.052
3147043LAWRENC
50/50
0.889
3151391GASTONA
50/50
0.249
3151411GASTONB
50/50
0.249
3151261ROARAP2
50/50
0.092
315243AE2-183_GT3
50/50
1.203
3151051BRUNSWICKS1
50/50
1.962
3151021BRUNSWICKG1
50/50
0.945
971451AH1-221 GEN
50/50
2.871
3151601KERR 3
50/50
0.122
3151581KERR 1
50/50
0.044
3151531CLOVER1
50/50
1.261
316023GEN1_S
Solar/Wind Harmer
0.287
960081AF2-299 GEN
Solar/Wind Harmer
1.037
971795AH1-408 GEN
Solar/Wind Harmer
6.499
316011AB1-132 GEN
Solar/Wind Harmer
1.672
962571AG1-106 GEN
Solar/Wind Harmer
1.309
3145796HORNRTN
Solar/Wind Harmer
0.29
3145796HORNRTN
Solar/Wind Harmer
0.088
315722AD1-056 GEN
Solar/Wind Harmer
0.473
315779AE2-040
50/50
2.75
3151281ROARAP4
50/50
0.089
3151281ROARAP4
50/50
0.084
315244AE2-183_ST
50/50
2.08
963041AG1-153 GEN
50/50
1.914
3151611KERR 4
50/50
0.122
3151621KERR 5
50/50
0.122
3151631KERR 6
50/50
0.122
3151641KERR 7
50/50
0.122
3151541CLOVER2
50/50
1.255
316315AB2-025 C
Solar/Wind Harmer
0.159
315814AE2-033 C
Solar/Wind Harmer
15.301
316087AB2-174 GEN
Solar/Wind Harmer
0.003
315652AC1-086 GEN
Solar/Wind Harmer
10.118
3145796HORNRTN
Solar/Wind Harmer
0.281
3145796HORNRTN
Solar/Wind Harmer
0.035
3137643SOCKMAN
Solar/Wind Harmer
0.328
941031AE2-094 GEN
Solar/Wind Harmer
13.859
944011AF1-069 GEN
Solar/Wind Harmer
4.528
3145783HORNRTN
Solar/Wind Harmer
0.072
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
2.454
970087AG2-069 GEN
Solar/Wind Harmer
5.498
940641AE2-051 GEN
Solar/Wind Harmer
5.458
316129AC1-054 GEN
Solar/Wind Harmer
0.242
971065AG2-659 GEN
Solar/Wind Harmer
2.706
3146233WITAKRS
Solar/Wind Harmer
0.252
316359AB2-059 GEN
Solar/Wind Harmer
0.227
316049AB1-081 GEN
Solar/Wind Harmer
0.361
3142053HEARTS
Solar/Wind Harmer
0.111
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
316212AC1-099_GEN
Solar/Wind Harmer
0.322
957481AF2-042 GEN
Solar/Wind Harmer
16.463
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.059
3145493TOT1
Solar/Wind Harmer
0.263
315693AD1-088 GEN
Solar/Wind Harmer
2.76
316237AB2-079_GEN
Solar/Wind Harmer
0
3146263WOODLND
Solar/Wind Harmer
0.057
962491AG1-098 GEN
Solar/Wind Harmer
3.232
316381AD1-082 GEN
Solar/Wind Helper
2.648
316458AB2-190 GEN2
Solar/Wind Helper
1.354
3142543TWELFTH
Solar/Wind Helper
0.022
3142433PROV 92
Solar/Wind Helper
0.592
3142416OLDCHRC
Solar/Wind Helper
0.348
3142416OLDCHRC
Solar/Wind Helper
0.133
3145593CAROLNA
Solar/Wind Harmer
0.074
3145593CAROLNA
Solar/Wind Harmer
0.074
966811AG1-552 GEN
Solar/Wind Harmer
0.8
3145593CAROLNA
Solar/Wind Harmer
0.092
3145783HORNRTN
Solar/Wind Harmer
1.288
3145783HORNRTN
Solar/Wind Harmer
1.031
3145783HORNRTN
Solar/Wind Harmer
0.322
3145783HORNRTN
Solar/Wind Harmer
0.129
3151391GASTONA
50/50
0.249
3151411GASTONB
50/50
0.249
3151261ROARAP2
50/50
0.09
3151031BRUNSWICKG2
50/50
0.945
3151591KERR 2
50/50
0.122
970413AG2-270 GEN
50/50
5.504
316365GEN2_N
Solar/Wind Harmer
0.287
3147043LAWRENC
Solar/Wind Harmer
0.056
313506AB2-031 GEN
Solar/Wind Harmer
0.284
3145796HORNRTN
Solar/Wind Harmer
0.352
970673AG2-436 GEN
Solar/Wind Harmer
15.712
970673AG2-436 GEN
Solar/Wind Harmer
10.474
971967AH1-528 GEN
Solar/Wind Harmer
11.501
970085AG2-068 GEN
Solar/Wind Harmer
3.665
970581AG2-369 GEN
Solar/Wind Harmer
3.152
970831AG2-522 GEN
Solar/Wind Harmer
2.782
316319Z2-044 C
Solar/Wind Harmer
0
315607AA1-063A GEN
Solar/Wind Harmer
0.121
3145573BETHELC
Solar/Wind Harmer
0.059
3145573BETHELC
Solar/Wind Harmer
0.059
3146033SCOT NK
Solar/Wind Harmer
0.235
316420AA1-050 GEN
Solar/Wind Harmer
0.002
316239AB2-077_GEN
Solar/Wind Harmer
0
316238AB2-078_GEN
Solar/Wind Harmer
0
3146043SEABORD
Solar/Wind Harmer
0.057
3143316POE
Solar/Wind Helper
4.642
316132AB2-190 GEN1
Solar/Wind Helper
1.354
316349AD2-085 GEN
Solar/Wind Helper
1.038
316369SG1_INVT
Solar/Wind Helper
0.893
316312AB1-027
Solar/Wind Helper
0.255
3143873LANEXA
Solar/Wind Helper
0.07
316426AA2-053 GEN
Solar/Wind Harmer
0.235
970933AG2-581 GEN
Solar/Wind Harmer
5.516
316274AC1-208 GEN
Solar/Wind Harmer
0.34
961601AG1-000A GEN
Solar/Wind Harmer
1.135
316263AC1-034 GEN
Solar/Wind Harmer
2.397
970099AG2-077 GEN
Solar/Wind Harmer
6.585
3145493TOT1
Solar/Wind Harmer
0.137
3145453TOT5
Solar/Wind Harmer
0.082
3145603CNETO
Solar/Wind Harmer
0.055
939181AE1-148 GEN
Solar/Wind Harmer
2.827
313527AB2-043 GEN
Solar/Wind Harmer
0.001
316240AF1-291 C
Solar/Wind Helper
0.668
316033AB2-134 GEN
Solar/Wind Helper
0.639
315697AD1-025 GEN
Solar/Wind Helper
2.123
3142946ENON
Solar/Wind Helper
0.018
966871AG1-558 GEN
Solar/Wind Helper
0.198
316075AC2-137 C
Solar/Wind Helper
0.206
316468AD1-105 GEN
Solar/Wind Helper
0.615
3145796HORNRTN
Solar/Wind Harmer
0.088
3142666NORTHAMPTON
Solar/Wind Harmer
0.086
315724AD1-057 GEN
Solar/Wind Harmer
0.281
970917AG2-570 GEN
Solar/Wind Harmer
6.136
961601AG1-000A GEN
Solar/Wind Harmer
4.539
316327AA2-057 GEN
Solar/Wind Harmer
0.096
3146233WITAKRS
Solar/Wind Harmer
0.318
3146233WITAKRS
Solar/Wind Harmer
0.043
3138543CONSLDL
Solar/Wind Harmer
0.042
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
316210AC1-098 GEN
Solar/Wind Harmer
0.577
3146073TAR RVR
Solar/Wind Harmer
0.059
3146083TARBORO
Solar/Wind Harmer
0.059
316478AD1-087 GEN
Solar/Wind Harmer
0.206
316486AD2-202 GEN
Solar/Wind Harmer
0.06
316131AB2-060 GEN
Solar/Wind Harmer
0.179
3146263WOODLND
Solar/Wind Harmer
0.057
315839AE2-212 C
Solar/Wind Helper
0.548
3142946ENON
Solar/Wind Helper
0.059
316473AC1-191 GEN
Solar/Wind Helper
0.896
CPLELTFEXP_CPLE->PJM
CLTF
3.563
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.107
LAGNLTFEXP_LAGN->PJM
CLTF
2.457
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.602
TVALTFEXP_TVA->PJM
CLTF
1.222
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.398
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.204
MECLTFEXP_MEC->PJM
CLTF
1.237
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.342
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.235

Details for 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6POE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.29 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:789.26
MW Contribution:5.63
Bus #Bus NameTypeMW Contribution
970533AG2-339 GEN
50/50
7.009
970531AG2-338 GEN
50/50
2.804
315242AE2-183_GT2
50/50
1.258
315241AE2-183_GT1
50/50
1.25
972185AH1-677 GEN
50/50
4.534
3151041BRUNSWICKG3
50/50
0.987
972187AH1-678 GEN
50/50
2.264
3151361ROSEMG1
50/50
0.269
3151371ROSEMS1
50/50
0.167
3151381ROSEMG2
50/50
0.126
3144356SAPONY
Solar/Wind Harmer
1.251
316181AB2-040 GEN
Solar/Wind Harmer
0.112
3145796HORNRTN
Solar/Wind Harmer
0.224
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3142666NORTHAMPTON
Solar/Wind Harmer
0.044
970933AG2-581 GEN
Solar/Wind Harmer
5.741
3145593CAROLNA
Solar/Wind Harmer
0.065
3145593CAROLNA
Solar/Wind Harmer
0.065
966811AG1-552 GEN
Solar/Wind Harmer
0.703
3145593CAROLNA
Solar/Wind Harmer
0.081
3145783HORNRTN
Solar/Wind Harmer
1.137
3145783HORNRTN
Solar/Wind Harmer
0.909
3145783HORNRTN
Solar/Wind Harmer
0.284
3145783HORNRTN
Solar/Wind Harmer
0.114
970099AG2-077 GEN
Solar/Wind Harmer
6.784
316426AA2-053 GEN
Solar/Wind Harmer
0.209
316274AC1-208 GEN
Solar/Wind Harmer
0.307
961601AG1-000A GEN
Solar/Wind Harmer
1.034
316263AC1-034 GEN
Solar/Wind Harmer
2.189
316240AF1-291 C
Solar/Wind Helper
0.46
3147043LAWRENC
50/50
0.75
3151391GASTONA
50/50
0.21
3151411GASTONB
50/50
0.21
315243AE2-183_GT3
50/50
1.258
3151051BRUNSWICKS1
50/50
2.048
3151021BRUNSWICKG1
50/50
0.987
971451AH1-221 GEN
50/50
2.997
3151261ROARAP2
50/50
0.081
3151531CLOVER1
50/50
1.291
3151601KERR 3
50/50
0.117
3151581KERR 1
50/50
0.042
316023GEN1_S
Solar/Wind Harmer
0.229
960081AF2-299 GEN
Solar/Wind Harmer
0.85
971795AH1-408 GEN
Solar/Wind Harmer
5.427
316011AB1-132 GEN
Solar/Wind Harmer
1.409
962571AG1-106 GEN
Solar/Wind Harmer
1.102
3145796HORNRTN
Solar/Wind Harmer
0.246
3145796HORNRTN
Solar/Wind Harmer
0.075
940641AE2-051 GEN
Solar/Wind Harmer
5.897
970919AG2-571 GEN
Solar/Wind Harmer
2.554
970087AG2-069 GEN
Solar/Wind Harmer
5.718
315722AD1-056 GEN
Solar/Wind Harmer
0.416
3145783HORNRTN
Solar/Wind Harmer
0.064
957481AF2-042 GEN
Solar/Wind Harmer
16.959
316190AA2-174 GEN
Solar/Wind Harmer
0
939411AE1-173 GEN
Solar/Wind Harmer
26.124
316129AC1-054 GEN
Solar/Wind Harmer
0.223
315693AD1-088 GEN
Solar/Wind Harmer
2.832
971065AG2-659 GEN
Solar/Wind Harmer
2.514
962491AG1-098 GEN
Solar/Wind Harmer
3.316
3146233WITAKRS
Solar/Wind Harmer
0.23
316359AB2-059 GEN
Solar/Wind Harmer
0.207
316049AB1-081 GEN
Solar/Wind Harmer
0.33
3142053HEARTS
Solar/Wind Harmer
0.101
3145543BTLEBRO
Solar/Wind Harmer
0.057
3145543BTLEBRO
Solar/Wind Harmer
0.046
316212AC1-099_GEN
Solar/Wind Harmer
0.294
315687AD1-152 GEN
Solar/Wind Harmer
0.002
316381AD1-082 GEN
Solar/Wind Helper
2.389
316458AB2-190 GEN2
Solar/Wind Helper
0.785
3142543TWELFTH
Solar/Wind Helper
0.012
315779AE2-040
50/50
2.087
315244AE2-183_ST
50/50
2.174
963041AG1-153 GEN
50/50
1.998
3151281ROARAP4
50/50
0.079
3151281ROARAP4
50/50
0.073
3151541CLOVER2
50/50
1.285
3151611KERR 4
50/50
0.117
3151621KERR 5
50/50
0.117
3151631KERR 6
50/50
0.117
3151641KERR 7
50/50
0.117
316315AB2-025 C
Solar/Wind Harmer
0.121
315814AE2-033 C
Solar/Wind Harmer
11.633
316087AB2-174 GEN
Solar/Wind Harmer
0.002
941031AE2-094 GEN
Solar/Wind Harmer
14.523
944011AF1-069 GEN
Solar/Wind Harmer
4.745
315652AC1-086 GEN
Solar/Wind Harmer
8.522
970673AG2-436 GEN
Solar/Wind Harmer
16.437
970673AG2-436 GEN
Solar/Wind Harmer
10.958
971967AH1-528 GEN
Solar/Wind Harmer
12.009
3145796HORNRTN
Solar/Wind Harmer
0.239
3145796HORNRTN
Solar/Wind Harmer
0.03
970085AG2-068 GEN
Solar/Wind Harmer
3.812
970581AG2-369 GEN
Solar/Wind Harmer
3.278
3137643SOCKMAN
Solar/Wind Harmer
0.282
970831AG2-522 GEN
Solar/Wind Harmer
2.557
316319Z2-044 C
Solar/Wind Harmer
0
3143316POE
Solar/Wind Helper
4.623
316349AD2-085 GEN
Solar/Wind Helper
0.873
316132AB2-190 GEN1
Solar/Wind Helper
0.785
3151391GASTONA
50/50
0.21
3151411GASTONB
50/50
0.21
3151031BRUNSWICKG2
50/50
0.987
3151261ROARAP2
50/50
0.079
970413AG2-270 GEN
50/50
5.635
3151591KERR 2
50/50
0.117
316365GEN2_N
Solar/Wind Harmer
0.229
3147043LAWRENC
Solar/Wind Harmer
0.047
313506AB2-031 GEN
Solar/Wind Harmer
0.239
3145796HORNRTN
Solar/Wind Harmer
0.299
3145796HORNRTN
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
970917AG2-570 GEN
Solar/Wind Harmer
6.384
315724AD1-057 GEN
Solar/Wind Harmer
0.246
316478AD1-087 GEN
Solar/Wind Harmer
0.21
316486AD2-202 GEN
Solar/Wind Harmer
0.062
961601AG1-000A GEN
Solar/Wind Harmer
4.135
316327AA2-057 GEN
Solar/Wind Harmer
0.088
3146233WITAKRS
Solar/Wind Harmer
0.29
3146233WITAKRS
Solar/Wind Harmer
0.039
3138543CONSLDL
Solar/Wind Harmer
0.038
971623AH1-311 GEN
Solar/Wind Harmer
0.115
3145543BTLEBRO
Solar/Wind Harmer
0.057
3145543BTLEBRO
Solar/Wind Harmer
0.057
316210AC1-098 GEN
Solar/Wind Harmer
0.528
CPLELTFEXP_CPLE->PJM
CLTF
3.53
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.861
LAGNLTFEXP_LAGN->PJM
CLTF
2.426
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.56
TVALTFEXP_TVA->PJM
CLTF
1.209
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.008
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.148
MECLTFEXP_MEC->PJM
CLTF
1.199
SIGELTFEXP_SIGE->PJM
CLTF
0.036
NYPJM->LTFIMP_NY
CLTF
0.411
LGEELTFEXP_LGEE->PJM
CLTF
0.433
WECLTFEXP_WEC->PJM
CLTF
0.226

Details for 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.72 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:958.85
MW Contribution:9.55
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
3.828
3151911BEARGRDN G1
50/50
2.966
3144293JTRSVLE
50/50
0.503
3151531CLOVER1
50/50
2.188
3151601KERR 3
50/50
0.135
3151581KERR 1
50/50
0.048
970937AG2-583 GEN
Solar/Wind Harmer
28.699
972003AH1-546 GEN
Solar/Wind Harmer
13.118
971377AH1-170 GEN
Solar/Wind Harmer
3.027
3147623JAMES R
Solar/Wind Harmer
0.658
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
963171AG1-166 GEN
Solar/Wind Harmer
0.794
971563AH1-280 GEN
Solar/Wind Harmer
1.587
970685AG2-442 GEN
Solar/Wind Harmer
10.089
962491AG1-098 GEN
Solar/Wind Harmer
7.03
315693AD1-088 GEN
Solar/Wind Harmer
5.777
957481AF2-042 GEN
Solar/Wind Harmer
29.163
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.003
970401AG2-262 GEN
Solar/Wind Harmer
0.451
316003AC1-222 GEN
Solar/Wind Harmer
0.002
316336AC2-165 C
Solar/Wind Helper
5.135
3143226MDLTHAN
Solar/Wind Helper
0.3
3143526WINTERP
Solar/Wind Helper
1.294
3142543TWELFTH
Solar/Wind Helper
0.014
3142416OLDCHRC
Solar/Wind Helper
0.296
3142416OLDCHRC
Solar/Wind Helper
0.113
316458AB2-190 GEN2
Solar/Wind Helper
0.639
972205AH1-687 GEN
50/50
14.467
3151541CLOVER2
50/50
2.177
3151611KERR 4
50/50
0.135
3151621KERR 5
50/50
0.135
3151631KERR 6
50/50
0.135
3151641KERR 7
50/50
0.135
971447AH1-217 GEN
Solar/Wind Harmer
8.145
971845AH1-439 GEN
Solar/Wind Harmer
11.716
970285AG2-188 GEN
Solar/Wind Harmer
19.851
270494AE1-108_GEN
Solar/Wind Harmer
2.723
315657AE1-056 GEN
Solar/Wind Harmer
5.462
946301AF1-294 GEN
Solar/Wind Harmer
2.936
961791AG1-021 GEN
Solar/Wind Harmer
1.429
970683AG2-441 GEN
Solar/Wind Harmer
9.008
970681AG2-440 GEN
Solar/Wind Harmer
7.206
3144303KENBRDG
Solar/Wind Harmer
0.096
971443AH1-215 GEN
Solar/Wind Harmer
2.005
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.188
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.069
3147243WELCO
Solar/Wind Harmer
0.043
970865AG2-541 GEN
Solar/Wind Harmer
2.13
316123AC1-075 GEN
Solar/Wind Harmer
0.077
970165AG2-112 GEN
Solar/Wind Harmer
0.459
970163AG2-111 GEN
Solar/Wind Harmer
0.438
316233AE1-074 FULL
Solar/Wind Helper
0.38
316312AB1-027
Solar/Wind Helper
0.217
316132AB2-190 GEN1
Solar/Wind Helper
0.639
3144293JTRSVLE
50/50
0.503
3144293JTRSVLE
50/50
0.423
970535AG2-341 GEN
50/50
1.349
3152661PLYWOOD A
50/50
0.157
971489AH1-241 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
1.049
3146776BUCKING
Solar/Wind Harmer
0.085
315821AE2-092 GEN
Solar/Wind Harmer
0.013
970301AG2-198 GEN
Solar/Wind Harmer
7.476
971741AH1-377 GEN
Solar/Wind Harmer
16.133
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.127
958211AF2-115 GEN
Solar/Wind Harmer
1.786
963191AG1-168 GEN
Solar/Wind Harmer
0.595
316034AC1-036 C
Solar/Wind Harmer
0.009
970323AG2-213 GEN
Solar/Wind Harmer
5.145
971775AH1-396 GEN
Solar/Wind Harmer
0.193
970099AG2-077 GEN
Solar/Wind Harmer
11.665
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.768
964791AG1-342 GEN
Solar/Wind Harmer
1.475
3146843MT LREL
Solar/Wind Harmer
0.077
3146843MT LREL
Solar/Wind Harmer
0.077
939181AE1-148 GEN
Solar/Wind Harmer
3.325
3143526WINTERP
Solar/Wind Helper
1.294
316240AF1-291 C
Solar/Wind Helper
0.162
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.156
316075AC2-137 C
Solar/Wind Helper
0.172
3151921BEARGRDN G2
50/50
2.966
3144293JTRSVLE
50/50
0.503
970413AG2-270 GEN
50/50
9.546
966251AG1-494 GEN
50/50
1.198
3151591KERR 2
50/50
0.135
970221AG2-151 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
0.094
3146926FARMVIL
Solar/Wind Harmer
0.129
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
1.869
3147133PAMPLIN
Solar/Wind Harmer
0.497
971193AH1-056 GEN
Solar/Wind Harmer
9.642
963181AG1-167 GEN
Solar/Wind Harmer
0.595
959311AF2-222 GEN
Solar/Wind Harmer
11.09
970257AG2-171 GEN
Solar/Wind Harmer
3.859
315785AD2-033 C
Solar/Wind Harmer
0.934
958131AF2-107 GEN
Solar/Wind Harmer
2.955
316478AD1-087 GEN
Solar/Wind Harmer
0.356
316486AD2-202 GEN
Solar/Wind Harmer
0.105
964241AG1-285 GEN
Solar/Wind Harmer
6.636
316131AB2-060 GEN
Solar/Wind Harmer
0.284
3148013FISHERV
Solar/Wind Harmer
0.071
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.932
971683AH1-343 GEN
Solar/Wind Harmer
2.348
316313AB2-026
Solar/Wind Helper
1.245
316258AE1-075 C
Solar/Wind Helper
1.12
316405AF2-144 C
Solar/Wind Helper
0.933
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.709
315839AE2-212 C
Solar/Wind Helper
0.155
CPLELTFEXP_CPLE->PJM
CLTF
0.611
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.053
LAGNLTFEXP_LAGN->PJM
CLTF
1.406
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.04
TVALTFEXP_TVA->PJM
CLTF
0.731
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.581
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
1.069
SIGELTFEXP_SIGE->PJM
CLTF
0.035
NYPJM->LTFIMP_NY
CLTF
0.331
LGEELTFEXP_LGEE->PJM
CLTF
0.459
WECLTFEXP_WEC->PJM
CLTF
0.235

Details for 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.32 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:955.6
MW Contribution:9.55
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
3.828
3151911BEARGRDN G1
50/50
2.966
3144293JTRSVLE
50/50
0.503
3151531CLOVER1
50/50
2.188
3151601KERR 3
50/50
0.135
3151581KERR 1
50/50
0.048
970937AG2-583 GEN
Solar/Wind Harmer
28.699
972003AH1-546 GEN
Solar/Wind Harmer
13.118
971377AH1-170 GEN
Solar/Wind Harmer
3.027
3147623JAMES R
Solar/Wind Harmer
0.658
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
963171AG1-166 GEN
Solar/Wind Harmer
0.794
971563AH1-280 GEN
Solar/Wind Harmer
1.587
970685AG2-442 GEN
Solar/Wind Harmer
10.089
962491AG1-098 GEN
Solar/Wind Harmer
7.03
315693AD1-088 GEN
Solar/Wind Harmer
5.777
957481AF2-042 GEN
Solar/Wind Harmer
29.163
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.003
970401AG2-262 GEN
Solar/Wind Harmer
0.451
316003AC1-222 GEN
Solar/Wind Harmer
0.002
316336AC2-165 C
Solar/Wind Helper
5.135
3143226MDLTHAN
Solar/Wind Helper
0.3
3143526WINTERP
Solar/Wind Helper
1.294
3142543TWELFTH
Solar/Wind Helper
0.014
3142416OLDCHRC
Solar/Wind Helper
0.296
3142416OLDCHRC
Solar/Wind Helper
0.113
316458AB2-190 GEN2
Solar/Wind Helper
0.639
972205AH1-687 GEN
50/50
14.467
3151541CLOVER2
50/50
2.177
3151611KERR 4
50/50
0.135
3151621KERR 5
50/50
0.135
3151631KERR 6
50/50
0.135
3151641KERR 7
50/50
0.135
971447AH1-217 GEN
Solar/Wind Harmer
8.145
971845AH1-439 GEN
Solar/Wind Harmer
11.716
970285AG2-188 GEN
Solar/Wind Harmer
19.851
270494AE1-108_GEN
Solar/Wind Harmer
2.723
315657AE1-056 GEN
Solar/Wind Harmer
5.462
946301AF1-294 GEN
Solar/Wind Harmer
2.936
961791AG1-021 GEN
Solar/Wind Harmer
1.429
970683AG2-441 GEN
Solar/Wind Harmer
9.008
970681AG2-440 GEN
Solar/Wind Harmer
7.206
3144303KENBRDG
Solar/Wind Harmer
0.096
971443AH1-215 GEN
Solar/Wind Harmer
2.005
971967AH1-528 GEN
Solar/Wind Harmer
17.843
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.188
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.069
3147243WELCO
Solar/Wind Harmer
0.043
970865AG2-541 GEN
Solar/Wind Harmer
2.13
316123AC1-075 GEN
Solar/Wind Harmer
0.077
970165AG2-112 GEN
Solar/Wind Harmer
0.459
970163AG2-111 GEN
Solar/Wind Harmer
0.438
316233AE1-074 FULL
Solar/Wind Helper
0.38
316312AB1-027
Solar/Wind Helper
0.217
316132AB2-190 GEN1
Solar/Wind Helper
0.639
3144293JTRSVLE
50/50
0.503
3144293JTRSVLE
50/50
0.423
970535AG2-341 GEN
50/50
1.349
3152661PLYWOOD A
50/50
0.157
971489AH1-241 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
1.049
3146776BUCKING
Solar/Wind Harmer
0.085
315821AE2-092 GEN
Solar/Wind Harmer
0.013
970301AG2-198 GEN
Solar/Wind Harmer
7.476
971741AH1-377 GEN
Solar/Wind Harmer
16.133
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.127
958211AF2-115 GEN
Solar/Wind Harmer
1.786
963191AG1-168 GEN
Solar/Wind Harmer
0.595
316034AC1-036 C
Solar/Wind Harmer
0.009
970323AG2-213 GEN
Solar/Wind Harmer
5.145
971775AH1-396 GEN
Solar/Wind Harmer
0.193
970933AG2-581 GEN
Solar/Wind Harmer
8.922
970099AG2-077 GEN
Solar/Wind Harmer
11.665
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.768
964791AG1-342 GEN
Solar/Wind Harmer
1.475
3146843MT LREL
Solar/Wind Harmer
0.077
3146843MT LREL
Solar/Wind Harmer
0.077
939181AE1-148 GEN
Solar/Wind Harmer
3.325
3143526WINTERP
Solar/Wind Helper
1.294
316240AF1-291 C
Solar/Wind Helper
0.162
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.156
316075AC2-137 C
Solar/Wind Helper
0.172
3151921BEARGRDN G2
50/50
2.966
3144293JTRSVLE
50/50
0.503
970413AG2-270 GEN
50/50
9.546
966251AG1-494 GEN
50/50
1.198
3151591KERR 2
50/50
0.135
970221AG2-151 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
0.094
3146926FARMVIL
Solar/Wind Harmer
0.129
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
1.869
3147133PAMPLIN
Solar/Wind Harmer
0.497
971193AH1-056 GEN
Solar/Wind Harmer
9.642
963181AG1-167 GEN
Solar/Wind Harmer
0.595
959311AF2-222 GEN
Solar/Wind Harmer
11.09
970257AG2-171 GEN
Solar/Wind Harmer
3.859
315785AD2-033 C
Solar/Wind Harmer
0.934
958131AF2-107 GEN
Solar/Wind Harmer
2.955
316478AD1-087 GEN
Solar/Wind Harmer
0.356
316486AD2-202 GEN
Solar/Wind Harmer
0.105
964241AG1-285 GEN
Solar/Wind Harmer
6.636
316131AB2-060 GEN
Solar/Wind Harmer
0.284
3148013FISHERV
Solar/Wind Harmer
0.071
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.932
971683AH1-343 GEN
Solar/Wind Harmer
2.348
316313AB2-026
Solar/Wind Helper
1.245
316258AE1-075 C
Solar/Wind Helper
1.12
316405AF2-144 C
Solar/Wind Helper
0.933
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.709
315839AE2-212 C
Solar/Wind Helper
0.155
CPLELTFEXP_CPLE->PJM
CLTF
0.611
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.053
LAGNLTFEXP_LAGN->PJM
CLTF
1.406
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.04
TVALTFEXP_TVA->PJM
CLTF
0.731
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.581
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
1.069
SIGELTFEXP_SIGE->PJM
CLTF
0.035
NYPJM->LTFIMP_NY
CLTF
0.331
LGEELTFEXP_LGEE->PJM
CLTF
0.459
WECLTFEXP_WEC->PJM
CLTF
0.235

Details for 6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:152.97 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1841.8
MW Contribution:11.15
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
1.972
3151391GASTONA
50/50
0.365
3151411GASTONB
50/50
0.365
970533AG2-339 GEN
50/50
14.043
970531AG2-338 GEN
50/50
5.617
315242AE2-183_GT2
50/50
2.516
315241AE2-183_GT1
50/50
2.5
972185AH1-677 GEN
50/50
9.069
3151041BRUNSWICKG3
50/50
1.972
972187AH1-678 GEN
50/50
4.526
3151361ROSEMG1
50/50
0.471
3151371ROSEMS1
50/50
0.292
3151381ROSEMG2
50/50
0.22
3144356SAPONY
Solar/Wind Harmer
0.948
970933AG2-581 GEN
Solar/Wind Harmer
15.092
316181AB2-040 GEN
Solar/Wind Harmer
2.139
3145796HORNRTN
Solar/Wind Harmer
-0.044
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
970099AG2-077 GEN
Solar/Wind Harmer
17.742
3145593CAROLNA
Solar/Wind Harmer
-0.013
3145593CAROLNA
Solar/Wind Harmer
-0.013
966811AG1-552 GEN
Solar/Wind Harmer
1.5
3145593CAROLNA
Solar/Wind Harmer
0.111
3145783HORNRTN
Solar/Wind Harmer
1.561
3145783HORNRTN
Solar/Wind Harmer
1.249
3145783HORNRTN
Solar/Wind Harmer
0.39
3145783HORNRTN
Solar/Wind Harmer
0.156
316426AA2-053 GEN
Solar/Wind Harmer
1.293
316274AC1-208 GEN
Solar/Wind Harmer
1.319
939181AE1-148 GEN
Solar/Wind Harmer
6.767
961601AG1-000A GEN
Solar/Wind Harmer
4.682
316263AC1-034 GEN
Solar/Wind Harmer
5.552
313527AB2-043 GEN
Solar/Wind Harmer
1.888
3145493TOT1
Solar/Wind Harmer
0.175
3145453TOT5
Solar/Wind Harmer
0.105
3145603CNETO
Solar/Wind Harmer
0.07
962561AG1-105 GEN
Solar/Wind Harmer
6.333
964791AG1-342 GEN
Solar/Wind Harmer
2.391
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970323AG2-213 GEN
Solar/Wind Harmer
5.164
971775AH1-396 GEN
Solar/Wind Harmer
0.735
316034AC1-036 C
Solar/Wind Harmer
0.191
971741AH1-377 GEN
Solar/Wind Harmer
11.893
3146173TUNIS
Solar/Wind Harmer
-0.01
3146173TUNIS
Solar/Wind Harmer
-0.01
316222AC1-221 GEN
Solar/Wind Harmer
1.018
3145893MURPHYS
Solar/Wind Harmer
0.278
3145893MURPHYS
Solar/Wind Harmer
-0.018
3145933PARMELE
Solar/Wind Harmer
-0.02
3145933PARMELE
Solar/Wind Harmer
-0.01
970301AG2-198 GEN
Solar/Wind Harmer
4.681
958211AF2-115 GEN
Solar/Wind Harmer
1.439
963191AG1-168 GEN
Solar/Wind Harmer
0.864
3144293JTRSVLE
Adder
0.261
3144293JTRSVLE
Adder
0.22
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.007
316065AD1-022 GEN
Solar/Wind Harmer
4.293
942751AE2-291 GEN
Solar/Wind Harmer
4.718
315742AE1-103 GEN
Solar/Wind Harmer
0.706
3146376EDENTON
Solar/Wind Harmer
0.191
3146376EDENTON
Solar/Wind Harmer
0.191
316240AF1-291 C
Solar/Wind Helper
0.402
3142946ENON
Solar/Wind Helper
0.017
966871AG1-558 GEN
Solar/Wind Helper
0.221
3143526WINTERP
Solar/Wind Helper
0.769
316468AD1-105 GEN
Solar/Wind Helper
0.714
316075AC2-137 C
Solar/Wind Helper
0.21
316033AB2-134 GEN
Solar/Wind Helper
0.43
315697AD1-025 GEN
Solar/Wind Helper
1.43
970413AG2-270 GEN
50/50
11.155
3151261ROARAP2
50/50
0.144
316365GEN2_N
Solar/Wind Harmer
1.302
966621AG1-532 GEN
Solar/Wind Harmer
0.347
970917AG2-570 GEN
Solar/Wind Harmer
40.235
3147043LAWRENC
Solar/Wind Harmer
-0.009
313506AB2-031 GEN
Solar/Wind Harmer
1.233
3145796HORNRTN
Solar/Wind Harmer
-0.058
3145796HORNRTN
Solar/Wind Harmer
-0.015
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
315779AE2-040
50/50
3.378
315244AE2-183_ST
50/50
4.349
963041AG1-153 GEN
50/50
3.994
3151541CLOVER2
50/50
2.544
3151281ROARAP4
50/50
0.144
3151281ROARAP4
50/50
0.134
316478AD1-087 GEN
Solar/Wind Harmer
1.161
316486AD2-202 GEN
Solar/Wind Harmer
0.34
315724AD1-057 GEN
Solar/Wind Harmer
0.758
316327AA2-057 GEN
Solar/Wind Harmer
1.21
961601AG1-000A GEN
Solar/Wind Harmer
4.742
3146233WITAKRS
Solar/Wind Harmer
0.249
3146233WITAKRS
Solar/Wind Harmer
-0.008
3138543CONSLDL
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.012
3145543BTLEBRO
Solar/Wind Harmer
-0.012
316210AC1-098 GEN
Solar/Wind Harmer
1.85
316131AB2-060 GEN
Solar/Wind Harmer
1.244
3146073TAR RVR
Solar/Wind Harmer
-0.011
3146083TARBORO
Solar/Wind Harmer
-0.011
964241AG1-285 GEN
Solar/Wind Harmer
8.72
3146263WOODLND
Solar/Wind Harmer
-0.011
316248AF1-058 C
Solar/Wind Harmer
0.328
960061AF2-297 GEN
Solar/Wind Harmer
5.444
316317KELFORD C
Solar/Wind Harmer
0.511
3145823KELFORD
Solar/Wind Harmer
-0.011
315785AD2-033 C
Solar/Wind Harmer
2.392
970257AG2-171 GEN
Solar/Wind Harmer
3.873
316463AE2-346 GEN
Solar/Wind Harmer
0.166
316140AB2-099
Solar/Wind Harmer
0.069
962331AG1-082 GEN
Solar/Wind Harmer
1.281
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
959311AF2-222 GEN
Solar/Wind Harmer
10.609
3146173TUNIS
Solar/Wind Harmer
-0.01
957521AF2-046 GEN
Solar/Wind Harmer
7.902
961681AG1-008 GEN
Solar/Wind Harmer
7.902
316283AC2-100 C
Solar/Wind Harmer
0.942
3145893MURPHYS
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
-0.01
3145933PARMELE
Solar/Wind Harmer
-0.01
966801AG1-551 GEN
Solar/Wind Harmer
1.233
3156021HOLLOMANSOL
Solar/Wind Harmer
1.319
971683AH1-343 GEN
Solar/Wind Harmer
4.208
3156081AA2-088 GEN
Solar/Wind Harmer
3.105
970909AG2-566 GEN
Solar/Wind Harmer
0.889
963181AG1-167 GEN
Solar/Wind Harmer
0.864
3144293JTRSVLE
Adder
0.261
3145963POPLR C
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.028
971193AH1-056 GEN
Solar/Wind Harmer
5.522
3146206CASHIE
Solar/Wind Harmer
-0.009
315737AD1-076 GEN
Solar/Wind Harmer
1.551
971157AH1-035 GEN
Solar/Wind Harmer
1.003
942461AE2-259 GEN
Solar/Wind Harmer
1.167
315614AA2-178 GEN
Solar/Wind Harmer
0.791
3146926FARMVIL
Solar/Wind Harmer
-0.004
3146376EDENTON
Solar/Wind Harmer
-0.006
315839AE2-212 C
Solar/Wind Helper
0.966
3142946ENON
Solar/Wind Helper
0.055
316473AC1-191 GEN
Solar/Wind Helper
1
316315AB2-025 C
Solar/Wind Harmer
0.734
315814AE2-033 C
Solar/Wind Harmer
24.939
941031AE2-094 GEN
Solar/Wind Harmer
33.281
944011AF1-069 GEN
Solar/Wind Harmer
10.428
970673AG2-436 GEN
Solar/Wind Harmer
36.399
970673AG2-436 GEN
Solar/Wind Harmer
18.43
946281AF1-292 GEN
Solar/Wind Harmer
0.383
971967AH1-528 GEN
Solar/Wind Harmer
31.705
970085AG2-068 GEN
Solar/Wind Harmer
10.008
970581AG2-369 GEN
Solar/Wind Harmer
8.607
316087AB2-174 GEN
Solar/Wind Harmer
2.265
315652AC1-086 GEN
Solar/Wind Harmer
17.05
3145796HORNRTN
Solar/Wind Harmer
-0.047
3145796HORNRTN
Solar/Wind Harmer
-0.006
3137643SOCKMAN
Solar/Wind Harmer
-0.057
970831AG2-522 GEN
Solar/Wind Harmer
6.31
315607AA1-063A GEN
Solar/Wind Harmer
1.207
316319Z2-044 C
Solar/Wind Harmer
0.657
3146043SEABORD
Solar/Wind Harmer
-0.012
316239AB2-077_GEN
Solar/Wind Harmer
0.35
316238AB2-078_GEN
Solar/Wind Harmer
0.35
3146033SCOT NK
Solar/Wind Harmer
-0.045
3145573BETHELC
Solar/Wind Harmer
-0.011
3145573BETHELC
Solar/Wind Harmer
-0.011
316420AA1-050 GEN
Solar/Wind Harmer
1.267
316118AC1-105 GEN
Solar/Wind Harmer
0.759
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
4.731
971443AH1-215 GEN
Solar/Wind Harmer
2.043
3145683EARLEYS
Solar/Wind Harmer
-0.021
3145683EARLEYS
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.01
3144303KENBRDG
Solar/Wind Harmer
-0.008
3145513AHOSKIE
Solar/Wind Harmer
0.089
961941AG1-037 GEN
Solar/Wind Harmer
0.077
3145513AHOSKIE
Solar/Wind Harmer
-0.01
316005AA1-067
Solar/Wind Harmer
0.207
3145746EVERETS
Solar/Wind Harmer
-0.041
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
970181AG2-120 GEN
Solar/Wind Harmer
1.344
316318V4-068
Solar/Wind Harmer
0.249
3145893MURPHYS
Solar/Wind Harmer
-0.027
3145893MURPHYS
Solar/Wind Harmer
-0.01
965291AG1-394 GEN
Solar/Wind Harmer
0.871
970683AG2-441 GEN
Solar/Wind Harmer
7.621
970681AG2-440 GEN
Solar/Wind Harmer
6.097
3143316POE
Solar/Wind Harmer
-0.038
970865AG2-541 GEN
Solar/Wind Harmer
3.743
946301AF1-294 GEN
Solar/Wind Harmer
2.361
961791AG1-021 GEN
Solar/Wind Harmer
1.152
315657AE1-056 GEN
Solar/Wind Harmer
3.313
3146206CASHIE
Solar/Wind Harmer
-0.009
970601AG2-382 GEN
Solar/Wind Harmer
3.864
270455AD2-022 GEN
Solar/Wind Harmer
1.529
270457AD2-023 GEN
Solar/Wind Harmer
0.775
315732AD1-074 GEN1
Solar/Wind Harmer
1.65
315733AD1-074 GEN2
Solar/Wind Harmer
1.65
315735AD1-075 GEN1
Solar/Wind Harmer
0.825
316123AC1-075 GEN
Solar/Wind Harmer
0.874
970165AG2-112 GEN
Solar/Wind Harmer
0.77
970163AG2-111 GEN
Solar/Wind Harmer
0.734
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.593
3130156CHOWAN
Solar/Wind Harmer
-0.006
3130156CHOWAN
Solar/Wind Harmer
-0.006
316132AB2-190 GEN1
Solar/Wind Helper
0.976
316233AE1-074 FULL
Solar/Wind Helper
0.226
316312AB1-027
Solar/Wind Helper
0.27
3143873LANEXA
Solar/Wind Helper
0.076
316369SG1_INVT
Solar/Wind Helper
0.602
315243AE2-183_GT3
50/50
2.516
3151051BRUNSWICKS1
50/50
4.094
3151021BRUNSWICKG1
50/50
1.972
971451AH1-221 GEN
50/50
5.991
3147043LAWRENC
50/50
1.32
3151391GASTONA
50/50
0.365
3151411GASTONB
50/50
0.365
3151531CLOVER1
50/50
2.556
3151261ROARAP2
50/50
0.148
316023GEN1_S
Solar/Wind Harmer
1.302
960081AF2-299 GEN
Solar/Wind Harmer
1.926
970919AG2-571 GEN
Solar/Wind Harmer
5.093
970087AG2-069 GEN
Solar/Wind Harmer
15.012
971795AH1-408 GEN
Solar/Wind Harmer
11.982
316011AB1-132 GEN
Solar/Wind Harmer
3.171
962571AG1-106 GEN
Solar/Wind Harmer
2.179
3145796HORNRTN
Solar/Wind Harmer
-0.048
3145796HORNRTN
Solar/Wind Harmer
-0.015
957481AF2-042 GEN
Solar/Wind Harmer
44.356
315722AD1-056 GEN
Solar/Wind Harmer
1.378
3145783HORNRTN
Solar/Wind Harmer
-0.013
315693AD1-088 GEN
Solar/Wind Harmer
6.574
939411AE1-173 GEN
Solar/Wind Harmer
65.115
962491AG1-098 GEN
Solar/Wind Harmer
8.662
316190AA2-174 GEN
Solar/Wind Harmer
0.157
316129AC1-054 GEN
Solar/Wind Harmer
1.1
315687AD1-152 GEN
Solar/Wind Harmer
1.509
971065AG2-659 GEN
Solar/Wind Harmer
6.236
3146233WITAKRS
Solar/Wind Harmer
-0.047
316359AB2-059 GEN
Solar/Wind Harmer
1.597
316049AB1-081 GEN
Solar/Wind Harmer
1.278
3142053HEARTS
Solar/Wind Harmer
0.139
3145543BTLEBRO
Solar/Wind Harmer
-0.012
3145543BTLEBRO
Solar/Wind Harmer
-0.009
316212AC1-099_GEN
Solar/Wind Harmer
1.028
316237AB2-079_GEN
Solar/Wind Harmer
0.35
961671AG1-007 GEN
Solar/Wind Harmer
0.143
3146083TARBORO
Solar/Wind Harmer
-0.011
3145493TOT1
Solar/Wind Harmer
0.335
970401AG2-262 GEN
Solar/Wind Harmer
0.731
3146263WOODLND
Solar/Wind Harmer
-0.011
3145823KELFORD
Solar/Wind Harmer
-0.011
316494AC1-189 GEN
Solar/Wind Harmer
1.164
3145683EARLEYS
Solar/Wind Harmer
-0.01
316003AC1-222 GEN
Solar/Wind Harmer
1.004
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
3146173TUNIS
Solar/Wind Harmer
-0.01
3145893MURPHYS
Solar/Wind Harmer
-0.04
3145893MURPHYS
Solar/Wind Harmer
0.296
3146293MARTNCO
Solar/Wind Harmer
0.061
970685AG2-442 GEN
Solar/Wind Harmer
8.535
316174AB2-169 GEN
Solar/Wind Harmer
1.424
963171AG1-166 GEN
Solar/Wind Harmer
1.152
971563AH1-280 GEN
Solar/Wind Harmer
1.152
3144293JTRSVLE
Adder
0.261
3145963POPLR C
Solar/Wind Harmer
-0.009
3146206CASHIE
Solar/Wind Harmer
-0.009
971547AH1-271 GEN
Solar/Wind Harmer
2.208
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.873
3146926FARMVIL
Solar/Wind Harmer
-0.004
3130156CHOWAN
Solar/Wind Harmer
-0.006
3142543TWELFTH
Solar/Wind Helper
0.024
3142433PROV 92
Solar/Wind Helper
0.7
316458AB2-190 GEN2
Solar/Wind Helper
0.976
3143526WINTERP
Solar/Wind Helper
0.769
3142416OLDCHRC
Solar/Wind Helper
0.369
3142416OLDCHRC
Solar/Wind Helper
0.141
3143226MDLTHAN
Solar/Wind Helper
0.133
CPLELTFEXP_CPLE->PJM
CLTF
6.792
CBM West 2LTFEXP_CBM-W2->PJM
CBM
24.55
LAGNLTFEXP_LAGN->PJM
CLTF
4.648
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.569
TVALTFEXP_TVA->PJM
CLTF
2.315
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.091
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.934
MECLTFEXP_MEC->PJM
CLTF
2.276
SIGELTFEXP_SIGE->PJM
CLTF
0.068
NYPJM->LTFIMP_NY
CLTF
0.817
LGEELTFEXP_LGEE->PJM
CLTF
0.818
WECLTFEXP_WEC->PJM
CLTF
0.427

Details for 6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:142.99 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1407.24
MW Contribution:8.81
Bus #Bus NameTypeMW Contribution
315779AE2-040
50/50
3.099
315244AE2-183_ST
50/50
3.382
963041AG1-153 GEN
50/50
3.109
3151281ROARAP4
50/50
0.132
3151281ROARAP4
50/50
0.123
3151541CLOVER2
50/50
2.008
3151611KERR 4
50/50
0.187
3151621KERR 5
50/50
0.187
3151631KERR 6
50/50
0.187
3151641KERR 7
50/50
0.187
316315AB2-025 C
Solar/Wind Harmer
0.179
315814AE2-033 C
Solar/Wind Harmer
17.298
316087AB2-174 GEN
Solar/Wind Harmer
0.004
315652AC1-086 GEN
Solar/Wind Harmer
13.694
941031AE2-094 GEN
Solar/Wind Harmer
22.572
944011AF1-069 GEN
Solar/Wind Harmer
7.375
3145796HORNRTN
Solar/Wind Harmer
0.385
3145796HORNRTN
Solar/Wind Harmer
0.048
970673AG2-436 GEN
Solar/Wind Harmer
25.561
970673AG2-436 GEN
Solar/Wind Harmer
17.041
971967AH1-528 GEN
Solar/Wind Harmer
18.68
3137643SOCKMAN
Solar/Wind Harmer
0.464
970085AG2-068 GEN
Solar/Wind Harmer
5.942
970581AG2-369 GEN
Solar/Wind Harmer
5.11
315607AA1-063A GEN
Solar/Wind Harmer
0.204
3146043SEABORD
Solar/Wind Harmer
0.098
970831AG2-522 GEN
Solar/Wind Harmer
4.182
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.379
3145573BETHELC
Solar/Wind Harmer
0.092
3145573BETHELC
Solar/Wind Harmer
0.092
316420AA1-050 GEN
Solar/Wind Harmer
0.003
3145683EARLEYS
Solar/Wind Harmer
0.179
3145683EARLEYS
Solar/Wind Harmer
0.09
3145683EARLEYS
Solar/Wind Harmer
0.09
3145513AHOSKIE
Solar/Wind Harmer
0.186
3145513AHOSKIE
Solar/Wind Harmer
0.089
957861AF2-080 GEN
Solar/Wind Harmer
3.828
3145893MURPHYS
Solar/Wind Harmer
0.235
3145893MURPHYS
Solar/Wind Harmer
0.087
965291AG1-394 GEN
Solar/Wind Harmer
0.382
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316005AA1-067
Solar/Wind Harmer
0.092
3145746EVERETS
Solar/Wind Harmer
0.34
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
970181AG2-120 GEN
Solar/Wind Harmer
1.064
3146206CASHIE
Solar/Wind Harmer
0.08
970601AG2-382 GEN
Solar/Wind Harmer
3.008
316118AC1-105 GEN
Solar/Wind Harmer
0.206
3147173SINAI
Solar/Wind Harmer
0.078
3147243WELCO
Solar/Wind Harmer
0.049
315732AD1-074 GEN1
Solar/Wind Harmer
0.439
315733AD1-074 GEN2
Solar/Wind Harmer
0.439
315735AD1-075 GEN1
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
1.275
3130546PLYMOUTH
Solar/Wind Harmer
0.076
3144303KENBRDG
Solar/Wind Harmer
0.06
3143316POE
Solar/Wind Harmer
0.287
315816AE2-034 GEN
Solar/Wind Harmer
0.308
970683AG2-441 GEN
Solar/Wind Harmer
4.722
970681AG2-440 GEN
Solar/Wind Harmer
3.778
3130156CHOWAN
Solar/Wind Harmer
0.066
3130156CHOWAN
Solar/Wind Harmer
0.066
946301AF1-294 GEN
Solar/Wind Harmer
1.311
961791AG1-021 GEN
Solar/Wind Harmer
0.638
970865AG2-541 GEN
Solar/Wind Harmer
2.298
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
315657AE1-056 GEN
Solar/Wind Harmer
2.185
316123AC1-075 GEN
Solar/Wind Harmer
0.08
970165AG2-112 GEN
Solar/Wind Harmer
0.473
970163AG2-111 GEN
Solar/Wind Harmer
0.451
3145176PASQUOTANK
Solar/Wind Harmer
0.036
316321Z2-027
Solar/Wind Harmer
0.011
3146396TANGLEW
Solar/Wind Harmer
0.161
313526AB2-022
Solar/Wind Harmer
0.031
3146486SUNBURY
Solar/Wind Harmer
0.057
3146486SUNBURY
Solar/Wind Harmer
0.057
316132AB2-190 GEN1
Solar/Wind Helper
0.895
316233AE1-074 FULL
Solar/Wind Helper
0.212
316312AB1-027
Solar/Wind Helper
0.237
3151391GASTONA
50/50
0.337
3151411GASTONB
50/50
0.337
3147043LAWRENC
50/50
1.178
315243AE2-183_GT3
50/50
1.956
3151051BRUNSWICKS1
50/50
3.187
3151021BRUNSWICKG1
50/50
1.536
971451AH1-221 GEN
50/50
4.664
3151261ROARAP2
50/50
0.136
3151531CLOVER1
50/50
2.018
3151601KERR 3
50/50
0.187
3151581KERR 1
50/50
0.067
316023GEN1_S
Solar/Wind Harmer
0.354
960081AF2-299 GEN
Solar/Wind Harmer
1.332
971795AH1-408 GEN
Solar/Wind Harmer
8.516
316011AB1-132 GEN
Solar/Wind Harmer
2.263
962571AG1-106 GEN
Solar/Wind Harmer
1.771
3145796HORNRTN
Solar/Wind Harmer
0.397
3145796HORNRTN
Solar/Wind Harmer
0.12
940641AE2-051 GEN
Solar/Wind Harmer
9.263
970919AG2-571 GEN
Solar/Wind Harmer
3.98
970087AG2-069 GEN
Solar/Wind Harmer
8.913
3145783HORNRTN
Solar/Wind Harmer
0.107
315722AD1-056 GEN
Solar/Wind Harmer
0.674
316190AA2-174 GEN
Solar/Wind Harmer
0
939411AE1-173 GEN
Solar/Wind Harmer
42.901
957481AF2-042 GEN
Solar/Wind Harmer
26.456
316212AC1-099_GEN
Solar/Wind Harmer
0.502
316129AC1-054 GEN
Solar/Wind Harmer
0.364
971065AG2-659 GEN
Solar/Wind Harmer
4.087
3146233WITAKRS
Solar/Wind Harmer
0.38
3146263WOODLND
Solar/Wind Harmer
0.095
316359AB2-059 GEN
Solar/Wind Harmer
0.34
316049AB1-081 GEN
Solar/Wind Harmer
0.541
3142053HEARTS
Solar/Wind Harmer
0.166
3145543BTLEBRO
Solar/Wind Harmer
0.094
3145543BTLEBRO
Solar/Wind Harmer
0.075
3145823KELFORD
Solar/Wind Harmer
0.092
315693AD1-088 GEN
Solar/Wind Harmer
4.418
961671AG1-007 GEN
Solar/Wind Harmer
0.014
3146083TARBORO
Solar/Wind Harmer
0.092
3145493TOT1
Solar/Wind Harmer
0.407
962491AG1-098 GEN
Solar/Wind Harmer
5.172
3145683EARLEYS
Solar/Wind Harmer
0.09
316494AC1-189 GEN
Solar/Wind Harmer
0.3
315687AD1-152 GEN
Solar/Wind Harmer
0.003
3146173TUNIS
Solar/Wind Harmer
0.088
3145893MURPHYS
Solar/Wind Harmer
0.348
3145893MURPHYS
Solar/Wind Harmer
0.387
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
3146293MARTNCO
Solar/Wind Harmer
0.078
970401AG2-262 GEN
Solar/Wind Harmer
0.478
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3146206CASHIE
Solar/Wind Harmer
0.08
971547AH1-271 GEN
Solar/Wind Harmer
1.719
3145963POPLR C
Solar/Wind Harmer
0.08
316003AC1-222 GEN
Solar/Wind Harmer
0.002
3145663CRESWEL
Solar/Wind Harmer
0.201
971163AH1-040 GEN
Solar/Wind Harmer
5.738
970685AG2-442 GEN
Solar/Wind Harmer
5.289
3130156CHOWAN
Solar/Wind Harmer
0.066
963171AG1-166 GEN
Solar/Wind Harmer
0.354
971563AH1-280 GEN
Solar/Wind Harmer
0.708
3144293JTRSVLE
Adder
0.211
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
316294AC1-161 GEN
Solar/Wind Harmer
1.066
3146516WINFALL
Solar/Wind Harmer
0.194
3146516WINFALL
Solar/Wind Harmer
0.06
944591AF1-124 GEN
Solar/Wind Harmer
12.705
3142543TWELFTH
Solar/Wind Helper
0.024
316458AB2-190 GEN2
Solar/Wind Helper
0.895
3142433PROV 92
Solar/Wind Helper
0.616
3143526WINTERP
Solar/Wind Helper
0.72
3143226MDLTHAN
Solar/Wind Helper
0.125
3142416OLDCHRC
Solar/Wind Helper
0.323
3142416OLDCHRC
Solar/Wind Helper
0.124
3151391GASTONA
50/50
0.337
3151411GASTONB
50/50
0.337
3151031BRUNSWICKG2
50/50
1.536
3151261ROARAP2
50/50
0.133
970413AG2-270 GEN
50/50
8.806
3151591KERR 2
50/50
0.187
316365GEN2_N
Solar/Wind Harmer
0.354
313506AB2-031 GEN
Solar/Wind Harmer
0.385
3147043LAWRENC
Solar/Wind Harmer
0.074
3145796HORNRTN
Solar/Wind Harmer
0.481
3145796HORNRTN
Solar/Wind Harmer
0.12
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
970917AG2-570 GEN
Solar/Wind Harmer
9.95
315724AD1-057 GEN
Solar/Wind Harmer
0.4
316210AC1-098 GEN
Solar/Wind Harmer
0.901
316327AA2-057 GEN
Solar/Wind Harmer
0.146
3146233WITAKRS
Solar/Wind Harmer
0.48
3146233WITAKRS
Solar/Wind Harmer
0.065
3138543CONSLDL
Solar/Wind Harmer
0.063
961601AG1-000A GEN
Solar/Wind Harmer
6.766
3146263WOODLND
Solar/Wind Harmer
0.095
971623AH1-311 GEN
Solar/Wind Harmer
0.189
3145543BTLEBRO
Solar/Wind Harmer
0.094
3145543BTLEBRO
Solar/Wind Harmer
0.094
316478AD1-087 GEN
Solar/Wind Harmer
0.329
316486AD2-202 GEN
Solar/Wind Harmer
0.097
316317KELFORD C
Solar/Wind Harmer
0.009
3145823KELFORD
Solar/Wind Harmer
0.092
3146073TAR RVR
Solar/Wind Harmer
0.092
3146083TARBORO
Solar/Wind Harmer
0.092
316463AE2-346 GEN
Solar/Wind Harmer
0.076
316140AB2-099
Solar/Wind Harmer
0.032
962331AG1-082 GEN
Solar/Wind Harmer
0.95
3146173TUNIS
Solar/Wind Harmer
0.088
957521AF2-046 GEN
Solar/Wind Harmer
6.513
961681AG1-008 GEN
Solar/Wind Harmer
6.513
3145893MURPHYS
Solar/Wind Harmer
0.146
3145893MURPHYS
Solar/Wind Harmer
0.087
3156021HOLLOMANSOL
Solar/Wind Harmer
0.393
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
316131AB2-060 GEN
Solar/Wind Harmer
0.268
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3145933PARMELE
Solar/Wind Harmer
0.084
966801AG1-551 GEN
Solar/Wind Harmer
0.976
964241AG1-285 GEN
Solar/Wind Harmer
5.485
3146206CASHIE
Solar/Wind Harmer
0.08
3145963POPLR C
Solar/Wind Harmer
0.08
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.344
315785AD2-033 C
Solar/Wind Harmer
0.629
315737AD1-076 GEN
Solar/Wind Harmer
0.983
971157AH1-035 GEN
Solar/Wind Harmer
0.908
970257AG2-171 GEN
Solar/Wind Harmer
2.416
959311AF2-222 GEN
Solar/Wind Harmer
6.592
316283AC2-100 C
Solar/Wind Harmer
0.142
315614AA2-178 GEN
Solar/Wind Harmer
0.41
971683AH1-343 GEN
Solar/Wind Harmer
2.584
3146376EDENTON
Solar/Wind Harmer
0.067
963181AG1-167 GEN
Solar/Wind Harmer
0.266
3144293JTRSVLE
Adder
0.211
970909AG2-566 GEN
Solar/Wind Harmer
0.692
3147133PAMPLIN
Solar/Wind Harmer
0.199
971193AH1-056 GEN
Solar/Wind Harmer
3.857
315773AC2-141 GEN
Solar/Wind Harmer
2.248
3146626S HERTFORD
Solar/Wind Harmer
0.061
3145273HOLLAND
Solar/Wind Harmer
0.046
3146516WINFALL
Solar/Wind Harmer
0.06
316435W1029_GEN3
Solar/Wind Harmer
0
316320Y1-086
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
12.66
944601AF1-125 GEN
Solar/Wind Harmer
12.465
315839AE2-212 C
Solar/Wind Helper
0.986
316473AC1-191 GEN
Solar/Wind Helper
0.925
3142946ENON
Solar/Wind Helper
0.049
970533AG2-339 GEN
50/50
10.894
970531AG2-338 GEN
50/50
4.358
3151361ROSEMG1
50/50
0.433
3151371ROSEMS1
50/50
0.268
3151381ROSEMG2
50/50
0.203
315242AE2-183_GT2
50/50
1.956
315241AE2-183_GT1
50/50
1.944
972185AH1-677 GEN
50/50
7.053
3151041BRUNSWICKG3
50/50
1.536
972187AH1-678 GEN
50/50
3.524
970535AG2-341 GEN
50/50
1.57
3152661PLYWOOD A
50/50
0.18
3144356SAPONY
Solar/Wind Harmer
1.857
316181AB2-040 GEN
Solar/Wind Harmer
0.181
3145796HORNRTN
Solar/Wind Harmer
0.361
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
970933AG2-581 GEN
Solar/Wind Harmer
8.936
3145593CAROLNA
Solar/Wind Harmer
0.109
3145593CAROLNA
Solar/Wind Harmer
0.109
966811AG1-552 GEN
Solar/Wind Harmer
1.182
3145593CAROLNA
Solar/Wind Harmer
0.136
3145783HORNRTN
Solar/Wind Harmer
1.911
3145783HORNRTN
Solar/Wind Harmer
1.529
3145783HORNRTN
Solar/Wind Harmer
0.478
3145783HORNRTN
Solar/Wind Harmer
0.191
316426AA2-053 GEN
Solar/Wind Harmer
0.356
316274AC1-208 GEN
Solar/Wind Harmer
0.518
970099AG2-077 GEN
Solar/Wind Harmer
10.582
961601AG1-000A GEN
Solar/Wind Harmer
1.691
316263AC1-034 GEN
Solar/Wind Harmer
3.592
3145493TOT1
Solar/Wind Harmer
0.212
3145453TOT5
Solar/Wind Harmer
0.127
3145603CNETO
Solar/Wind Harmer
0.085
939181AE1-148 GEN
Solar/Wind Harmer
4.3
3146173TUNIS
Solar/Wind Harmer
0.088
3146173TUNIS
Solar/Wind Harmer
0.088
3145893MURPHYS
Solar/Wind Harmer
0.583
3145893MURPHYS
Solar/Wind Harmer
0.157
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3145933PARMELE
Solar/Wind Harmer
0.168
3145933PARMELE
Solar/Wind Harmer
0.084
962561AG1-105 GEN
Solar/Wind Harmer
3.947
964791AG1-342 GEN
Solar/Wind Harmer
1.566
3146843MT LREL
Solar/Wind Harmer
0.081
3146843MT LREL
Solar/Wind Harmer
0.081
316065AD1-022 GEN
Solar/Wind Harmer
3.64
970323AG2-213 GEN
Solar/Wind Harmer
3.221
971775AH1-396 GEN
Solar/Wind Harmer
0.121
316034AC1-036 C
Solar/Wind Harmer
0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.303
971741AH1-377 GEN
Solar/Wind Harmer
7.057
3146376EDENTON
Solar/Wind Harmer
0.296
3146376EDENTON
Solar/Wind Harmer
0.296
958211AF2-115 GEN
Solar/Wind Harmer
0.797
963191AG1-168 GEN
Solar/Wind Harmer
0.266
3144293JTRSVLE
Adder
0.211
3144293JTRSVLE
Adder
0.178
315742AE1-103 GEN
Solar/Wind Harmer
0.001
970301AG2-198 GEN
Solar/Wind Harmer
2.77
3147133PAMPLIN
Solar/Wind Harmer
0.063
3147133PAMPLIN
Solar/Wind Harmer
0.051
3146626S HERTFORD
Solar/Wind Harmer
0.061
3146626S HERTFORD
Solar/Wind Harmer
0.061
3146516WINFALL
Solar/Wind Harmer
0.06
3146516WINFALL
Solar/Wind Harmer
0.06
3146516WINFALL
Solar/Wind Harmer
0.06
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146386ELIZ CT
Solar/Wind Harmer
0.057
316240AF1-291 C
Solar/Wind Helper
0.411
966871AG1-558 GEN
Solar/Wind Helper
0.204
3142946ENON
Solar/Wind Helper
0.015
3143526WINTERP
Solar/Wind Helper
0.72
316468AD1-105 GEN
Solar/Wind Helper
0.653
316075AC2-137 C
Solar/Wind Helper
0.178
CPLELTFEXP_CPLE->PJM
CLTF
5.631
CBM West 2LTFEXP_CBM-W2->PJM
CBM
19.951
LAGNLTFEXP_LAGN->PJM
CLTF
3.79
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.991
TVALTFEXP_TVA->PJM
CLTF
1.888
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.11
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.461
MECLTFEXP_MEC->PJM
CLTF
1.839
SIGELTFEXP_SIGE->PJM
CLTF
0.055
NYPJM->LTFIMP_NY
CLTF
0.691
LGEELTFEXP_LGEE->PJM
CLTF
0.659
WECLTFEXP_WEC->PJM
CLTF
0.343

Details for 6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2002_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.0 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1171.16
MW Contribution:6.97
Bus #Bus NameTypeMW Contribution
315779AE2-040
50/50
3.401
3151281ROARAP4
50/50
0.118
3151281ROARAP4
50/50
0.11
315244AE2-183_ST
50/50
2.625
963041AG1-153 GEN
50/50
2.415
3151611KERR 4
50/50
0.157
3151621KERR 5
50/50
0.157
3151631KERR 6
50/50
0.157
3151641KERR 7
50/50
0.157
3151541CLOVER2
50/50
1.589
316315AB2-025 C
Solar/Wind Harmer
0.197
315814AE2-033 C
Solar/Wind Harmer
18.936
316087AB2-174 GEN
Solar/Wind Harmer
0.004
315652AC1-086 GEN
Solar/Wind Harmer
13.019
3145796HORNRTN
Solar/Wind Harmer
0.362
3145796HORNRTN
Solar/Wind Harmer
0.045
3137643SOCKMAN
Solar/Wind Harmer
0.427
941031AE2-094 GEN
Solar/Wind Harmer
17.475
944011AF1-069 GEN
Solar/Wind Harmer
5.71
970673AG2-436 GEN
Solar/Wind Harmer
19.819
970673AG2-436 GEN
Solar/Wind Harmer
13.213
3151391GASTONA
50/50
0.32
3151411GASTONB
50/50
0.32
3147043LAWRENC
50/50
1.13
3151261ROARAP2
50/50
0.121
315243AE2-183_GT3
50/50
1.518
3151051BRUNSWICKS1
50/50
2.476
3151021BRUNSWICKG1
50/50
1.193
971451AH1-221 GEN
50/50
3.623
3151601KERR 3
50/50
0.157
3151581KERR 1
50/50
0.056
3151531CLOVER1
50/50
1.596
316023GEN1_S
Solar/Wind Harmer
0.362
960081AF2-299 GEN
Solar/Wind Harmer
1.316
971795AH1-408 GEN
Solar/Wind Harmer
8.254
316011AB1-132 GEN
Solar/Wind Harmer
2.152
962571AG1-106 GEN
Solar/Wind Harmer
1.684
3145796HORNRTN
Solar/Wind Harmer
0.374
3145796HORNRTN
Solar/Wind Harmer
0.113
315722AD1-056 GEN
Solar/Wind Harmer
0.612
3145783HORNRTN
Solar/Wind Harmer
0.096
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
3.101
970087AG2-069 GEN
Solar/Wind Harmer
6.946
940641AE2-051 GEN
Solar/Wind Harmer
6.931
3151361ROSEMG1
50/50
0.408
3151371ROSEMS1
50/50
0.253
3151381ROSEMG2
50/50
0.191
970533AG2-339 GEN
50/50
8.434
970531AG2-338 GEN
50/50
3.373
315242AE2-183_GT2
50/50
1.518
315241AE2-183_GT1
50/50
1.509
972185AH1-677 GEN
50/50
5.473
3151041BRUNSWICKG3
50/50
1.193
972187AH1-678 GEN
50/50
2.737
970535AG2-341 GEN
50/50
1.329
3152661PLYWOOD A
50/50
0.148
3144356SAPONY
Solar/Wind Harmer
2.038
316181AB2-040 GEN
Solar/Wind Harmer
0.172
3145796HORNRTN
Solar/Wind Harmer
0.34
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
3142666NORTHAMPTON
Solar/Wind Harmer
0.067
3145593CAROLNA
Solar/Wind Harmer
0.097
3145593CAROLNA
Solar/Wind Harmer
0.097
966811AG1-552 GEN
Solar/Wind Harmer
1.057
3151391GASTONA
50/50
0.32
3151411GASTONB
50/50
0.32
3151261ROARAP2
50/50
0.119
3151031BRUNSWICKG2
50/50
1.193
3151591KERR 2
50/50
0.157
970413AG2-270 GEN
50/50
6.966
316365GEN2_N
Solar/Wind Harmer
0.362
313506AB2-031 GEN
Solar/Wind Harmer
0.366
3147043LAWRENC
Solar/Wind Harmer
0.071
3145796HORNRTN
Solar/Wind Harmer
0.453
3145796HORNRTN
Solar/Wind Harmer
0.113
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
315724AD1-057 GEN
Solar/Wind Harmer
0.363
970917AG2-570 GEN
Solar/Wind Harmer
7.751
316327AA2-057 GEN
Solar/Wind Harmer
0.127
961601AG1-000A GEN
Solar/Wind Harmer
5.909
316210AC1-098 GEN
Solar/Wind Harmer
0.77
3146233WITAKRS
Solar/Wind Harmer
0.417
3146233WITAKRS
Solar/Wind Harmer
0.056
3138543CONSLDL
Solar/Wind Harmer
0.055
971623AH1-311 GEN
Solar/Wind Harmer
0.164
3145543BTLEBRO
Solar/Wind Harmer
0.082
3145543BTLEBRO
Solar/Wind Harmer
0.082
3146263WOODLND
Solar/Wind Harmer
0.078
3146073TAR RVR
Solar/Wind Harmer
0.078
3146083TARBORO
Solar/Wind Harmer
0.078
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.075
316478AD1-087 GEN
Solar/Wind Harmer
0.26
316486AD2-202 GEN
Solar/Wind Harmer
0.076
316131AB2-060 GEN
Solar/Wind Harmer
0.229
964241AG1-285 GEN
Solar/Wind Harmer
4.665
316463AE2-346 GEN
Solar/Wind Harmer
0.06
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.742
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.068
3156021HOLLOMANSOL
Solar/Wind Harmer
0.305
3145933PARMELE
Solar/Wind Harmer
0.066
966801AG1-551 GEN
Solar/Wind Harmer
0.769
957521AF2-046 GEN
Solar/Wind Harmer
4.888
961681AG1-008 GEN
Solar/Wind Harmer
4.888
971967AH1-528 GEN
Solar/Wind Harmer
14.51
970085AG2-068 GEN
Solar/Wind Harmer
4.631
970581AG2-369 GEN
Solar/Wind Harmer
3.982
970831AG2-522 GEN
Solar/Wind Harmer
3.621
315607AA1-063A GEN
Solar/Wind Harmer
0.17
316319Z2-044 C
Solar/Wind Harmer
0
3146043SEABORD
Solar/Wind Harmer
0.081
3146033SCOT NK
Solar/Wind Harmer
0.318
3145593CAROLNA
Solar/Wind Harmer
0.121
3145783HORNRTN
Solar/Wind Harmer
1.703
3145783HORNRTN
Solar/Wind Harmer
1.362
3145783HORNRTN
Solar/Wind Harmer
0.426
3145783HORNRTN
Solar/Wind Harmer
0.17
316426AA2-053 GEN
Solar/Wind Harmer
0.313
970933AG2-581 GEN
Solar/Wind Harmer
6.963
316274AC1-208 GEN
Solar/Wind Harmer
0.45
961601AG1-000A GEN
Solar/Wind Harmer
1.477
316263AC1-034 GEN
Solar/Wind Harmer
3.125
970099AG2-077 GEN
Solar/Wind Harmer
8.325
3145493TOT1
Solar/Wind Harmer
0.181
3145453TOT5
Solar/Wind Harmer
0.108
3145603CNETO
Solar/Wind Harmer
0.072
939181AE1-148 GEN
Solar/Wind Harmer
3.627
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.291
3146173TUNIS
Solar/Wind Harmer
0.068
3146173TUNIS
Solar/Wind Harmer
0.068
964791AG1-342 GEN
Solar/Wind Harmer
1.3
3146843MT LREL
Solar/Wind Harmer
0.068
3146843MT LREL
Solar/Wind Harmer
0.068
3145933PARMELE
Solar/Wind Harmer
0.132
3145933PARMELE
Solar/Wind Harmer
0.066
3145893MURPHYS
Solar/Wind Harmer
0.433
3145893MURPHYS
Solar/Wind Harmer
0.116
970323AG2-213 GEN
Solar/Wind Harmer
2.721
971775AH1-396 GEN
Solar/Wind Harmer
0.102
316034AC1-036 C
Solar/Wind Harmer
0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.245
316065AD1-022 GEN
Solar/Wind Harmer
2.617
971741AH1-377 GEN
Solar/Wind Harmer
5.589
316240AF1-291 C
Solar/Wind Helper
0.691
3142946ENON
Solar/Wind Helper
0.022
316033AB2-134 GEN
Solar/Wind Helper
0.717
315697AD1-025 GEN
Solar/Wind Helper
2.382
966871AG1-558 GEN
Solar/Wind Helper
0.262
316075AC2-137 C
Solar/Wind Helper
0.263
316468AD1-105 GEN
Solar/Wind Helper
0.815
3143526WINTERP
Solar/Wind Helper
0.727
316077AC2-138 C
Solar/Wind Helper
0.107
316487AF1-042 GEN
Solar/Wind Helper
0.114
316129AC1-054 GEN
Solar/Wind Harmer
0.314
316212AC1-099_GEN
Solar/Wind Harmer
0.43
3146233WITAKRS
Solar/Wind Harmer
0.33
971065AG2-659 GEN
Solar/Wind Harmer
3.51
316359AB2-059 GEN
Solar/Wind Harmer
0.295
316049AB1-081 GEN
Solar/Wind Harmer
0.471
3142053HEARTS
Solar/Wind Harmer
0.145
3145543BTLEBRO
Solar/Wind Harmer
0.082
3145543BTLEBRO
Solar/Wind Harmer
0.066
3146263WOODLND
Solar/Wind Harmer
0.078
957481AF2-042 GEN
Solar/Wind Harmer
20.812
961671AG1-007 GEN
Solar/Wind Harmer
0.012
3146083TARBORO
Solar/Wind Harmer
0.078
3145493TOT1
Solar/Wind Harmer
0.346
3145823KELFORD
Solar/Wind Harmer
0.075
316494AC1-189 GEN
Solar/Wind Harmer
0.249
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
3.49
962491AG1-098 GEN
Solar/Wind Harmer
4.086
3145683EARLEYS
Solar/Wind Harmer
0.071
315687AD1-152 GEN
Solar/Wind Harmer
0.002
939411AE1-173 GEN
Solar/Wind Harmer
30.084
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.068
970401AG2-262 GEN
Solar/Wind Harmer
0.397
3146293MARTNCO
Solar/Wind Harmer
0.061
3145893MURPHYS
Solar/Wind Harmer
0.259
3145893MURPHYS
Solar/Wind Harmer
0.288
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145963POPLR C
Solar/Wind Harmer
0.06
316003AC1-222 GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
4.444
3146206CASHIE
Solar/Wind Harmer
0.059
971547AH1-271 GEN
Solar/Wind Harmer
1.257
3142543TWELFTH
Solar/Wind Helper
0.031
316458AB2-190 GEN2
Solar/Wind Helper
1.544
316381AD1-082 GEN
Solar/Wind Helper
1.346
3142433PROV 92
Solar/Wind Helper
0.863
3142416OLDCHRC
Solar/Wind Helper
0.448
3142416OLDCHRC
Solar/Wind Helper
0.172
3143526WINTERP
Solar/Wind Helper
0.727
3141766HARMONY
Solar/Wind Helper
0.024
964211AG1-282 GEN
Solar/Wind Helper
0.157
3141726DUNNSVL
Solar/Wind Helper
0.465
3138133OCRAN
Solar/Wind Helper
0.068
3145573BETHELC
Solar/Wind Harmer
0.078
3145573BETHELC
Solar/Wind Harmer
0.078
316420AA1-050 GEN
Solar/Wind Harmer
0.003
957861AF2-080 GEN
Solar/Wind Harmer
3.178
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3145683EARLEYS
Solar/Wind Harmer
0.142
3145683EARLEYS
Solar/Wind Harmer
0.071
3145683EARLEYS
Solar/Wind Harmer
0.071
3145513AHOSKIE
Solar/Wind Harmer
0.145
3145513AHOSKIE
Solar/Wind Harmer
0.07
316005AA1-067
Solar/Wind Harmer
0.074
3145746EVERETS
Solar/Wind Harmer
0.274
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
970181AG2-120 GEN
Solar/Wind Harmer
0.856
316118AC1-105 GEN
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
0.175
3145893MURPHYS
Solar/Wind Harmer
0.065
971443AH1-215 GEN
Solar/Wind Harmer
1.078
3144303KENBRDG
Solar/Wind Harmer
0.051
3147173SINAI
Solar/Wind Harmer
0.064
3147243WELCO
Solar/Wind Harmer
0.04
965291AG1-394 GEN
Solar/Wind Harmer
0.275
970683AG2-441 GEN
Solar/Wind Harmer
3.967
970681AG2-440 GEN
Solar/Wind Harmer
3.174
3146206CASHIE
Solar/Wind Harmer
0.059
970601AG2-382 GEN
Solar/Wind Harmer
2.2
3143316POE
Solar/Wind Helper
1.93
316132AB2-190 GEN1
Solar/Wind Helper
1.544
316369SG1_INVT
Solar/Wind Helper
1.002
316312AB1-027
Solar/Wind Helper
0.328
3143873LANEXA
Solar/Wind Helper
0.095
316233AE1-074 FULL
Solar/Wind Helper
0.214
315662AE1-191 GEN
Solar/Wind Helper
0.666
315666AE1-190 GEN
Solar/Wind Helper
0.167
316059AD1-063 C
Solar/Wind Helper
0.122
3141813NORNECK
Solar/Wind Helper
0.113
3141783LANCAST
Solar/Wind Helper
0.068
3141783LANCAST
Solar/Wind Helper
0.045
3141913WHIT STONE
Solar/Wind Helper
0.113
3138133OCRAN
Solar/Wind Helper
0.034
957601AF2-054 GEN
Solar/Wind Helper
0.152
3141873WAN 176
Solar/Wind Helper
0.023
315785AD2-033 C
Solar/Wind Harmer
0.532
3145893MURPHYS
Solar/Wind Harmer
0.108
3145893MURPHYS
Solar/Wind Harmer
0.065
970257AG2-171 GEN
Solar/Wind Harmer
2.041
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.715
959311AF2-222 GEN
Solar/Wind Harmer
5.561
3145963POPLR C
Solar/Wind Harmer
0.06
3156081AA2-088 GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.059
316283AC2-100 C
Solar/Wind Harmer
0.115
971683AH1-343 GEN
Solar/Wind Harmer
2.095
315839AE2-212 C
Solar/Wind Helper
1.113
3142946ENON
Solar/Wind Helper
0.074
316473AC1-191 GEN
Solar/Wind Helper
1.189
316280AD1-041 GEN
Solar/Wind Helper
0.416
316404AE1-155 C
Solar/Wind Helper
0.956
316484AD2-074 GEN
Solar/Wind Helper
0.219
316156AD2-030 GEN
Solar/Wind Helper
0.171
CPLELTFEXP_CPLE->PJM
CLTF
4.572
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.518
LAGNLTFEXP_LAGN->PJM
CLTF
3.11
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.716
TVALTFEXP_TVA->PJM
CLTF
1.547
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.423
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.312
MECLTFEXP_MEC->PJM
CLTF
1.548
SIGELTFEXP_SIGE->PJM
CLTF
0.046
NYPJM->LTFIMP_NY
CLTF
0.457
LGEELTFEXP_LGEE->PJM
CLTF
0.557
WECLTFEXP_WEC->PJM
CLTF
0.293

Details for 6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.7 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:893.85
MW Contribution:6.8
Bus #Bus NameTypeMW Contribution
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3151261ROARAP2
50/50
0.313
3151591KERR 2
50/50
0.27
3144293JTRSVLE
50/50
0.305
970413AG2-270 GEN
50/50
6.801
316365GEN2_N
Solar/Wind Harmer
1.155
313506AB2-031 GEN
Solar/Wind Harmer
1.049
3147043LAWRENC
Solar/Wind Harmer
0.196
3145796HORNRTN
Solar/Wind Harmer
1.268
3145796HORNRTN
Solar/Wind Harmer
0.317
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
315724AD1-057 GEN
Solar/Wind Harmer
0.907
316210AC1-098 GEN
Solar/Wind Harmer
1.821
316327AA2-057 GEN
Solar/Wind Harmer
0.289
3146263WOODLND
Solar/Wind Harmer
0.191
3146233WITAKRS
Solar/Wind Harmer
0.921
3146233WITAKRS
Solar/Wind Harmer
0.125
3138543CONSLDL
Solar/Wind Harmer
0.12
961601AG1-000A GEN
Solar/Wind Harmer
12.805
316317KELFORD C
Solar/Wind Harmer
0.017
3145823KELFORD
Solar/Wind Harmer
0.177
971623AH1-311 GEN
Solar/Wind Harmer
0.353
3145543BTLEBRO
Solar/Wind Harmer
0.175
3145543BTLEBRO
Solar/Wind Harmer
0.175
316463AE2-346 GEN
Solar/Wind Harmer
0.142
316140AB2-099
Solar/Wind Harmer
0.059
962331AG1-082 GEN
Solar/Wind Harmer
1.76
3146073TAR RVR
Solar/Wind Harmer
0.165
3146083TARBORO
Solar/Wind Harmer
0.165
3146173TUNIS
Solar/Wind Harmer
0.163
957521AF2-046 GEN
Solar/Wind Harmer
11.982
961681AG1-008 GEN
Solar/Wind Harmer
11.982
3145893MURPHYS
Solar/Wind Harmer
0.268
3145893MURPHYS
Solar/Wind Harmer
0.16
3156021HOLLOMANSOL
Solar/Wind Harmer
0.689
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3145933PARMELE
Solar/Wind Harmer
0.131
966801AG1-551 GEN
Solar/Wind Harmer
1.529
316131AB2-060 GEN
Solar/Wind Harmer
0.407
964241AG1-285 GEN
Solar/Wind Harmer
8.211
3146206CASHIE
Solar/Wind Harmer
0.122
3145963POPLR C
Solar/Wind Harmer
0.118
315785AD2-033 C
Solar/Wind Harmer
0.918
970257AG2-171 GEN
Solar/Wind Harmer
3.491
959311AF2-222 GEN
Solar/Wind Harmer
9.454
315737AD1-076 GEN
Solar/Wind Harmer
1.314
971157AH1-035 GEN
Solar/Wind Harmer
1.183
963181AG1-167 GEN
Solar/Wind Harmer
0.361
3147133PAMPLIN
Solar/Wind Harmer
0.263
971193AH1-056 GEN
Solar/Wind Harmer
5.112
315614AA2-178 GEN
Solar/Wind Harmer
0.458
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.273
316478AD1-087 GEN
Solar/Wind Harmer
0.254
316486AD2-202 GEN
Solar/Wind Harmer
0.075
971683AH1-343 GEN
Solar/Wind Harmer
2.513
942461AE2-259 GEN
Solar/Wind Harmer
0
316283AC2-100 C
Solar/Wind Harmer
0.113
970909AG2-566 GEN
Solar/Wind Harmer
0.605
315839AE2-212 C
Solar/Wind Helper
0.197
3151611KERR 4
50/50
0.27
3151621KERR 5
50/50
0.27
3151631KERR 6
50/50
0.27
3151641KERR 7
50/50
0.27
3151151S HAMPT1
50/50
0.285
3151541CLOVER2
50/50
1.551
316087AB2-174 GEN
Solar/Wind Harmer
0.01
315652AC1-086 GEN
Solar/Wind Harmer
37.428
3145796HORNRTN
Solar/Wind Harmer
1.015
3145796HORNRTN
Solar/Wind Harmer
0.127
3137643SOCKMAN
Solar/Wind Harmer
1.176
315607AA1-063A GEN
Solar/Wind Harmer
0.444
3146043SEABORD
Solar/Wind Harmer
0.211
3146033SCOT NK
Solar/Wind Harmer
0.75
316319Z2-044 C
Solar/Wind Harmer
0
970831AG2-522 GEN
Solar/Wind Harmer
7.783
3145683EARLEYS
Solar/Wind Harmer
0.333
3145683EARLEYS
Solar/Wind Harmer
0.166
3145683EARLEYS
Solar/Wind Harmer
0.166
3145513AHOSKIE
Solar/Wind Harmer
0.345
3145513AHOSKIE
Solar/Wind Harmer
0.165
3145573BETHELC
Solar/Wind Harmer
0.165
3145573BETHELC
Solar/Wind Harmer
0.165
3145893MURPHYS
Solar/Wind Harmer
0.432
3145893MURPHYS
Solar/Wind Harmer
0.16
316420AA1-050 GEN
Solar/Wind Harmer
0.005
965291AG1-394 GEN
Solar/Wind Harmer
0.698
957861AF2-080 GEN
Solar/Wind Harmer
6.563
316005AA1-067
Solar/Wind Harmer
0.148
3145746EVERETS
Solar/Wind Harmer
0.548
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
970181AG2-120 GEN
Solar/Wind Harmer
1.713
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.122
970601AG2-382 GEN
Solar/Wind Harmer
4.575
971443AH1-215 GEN
Solar/Wind Harmer
1.848
3144303KENBRDG
Solar/Wind Harmer
0.087
315732AD1-074 GEN1
Solar/Wind Harmer
0.587
315733AD1-074 GEN2
Solar/Wind Harmer
0.587
315735AD1-075 GEN1
Solar/Wind Harmer
0.294
970683AG2-441 GEN
Solar/Wind Harmer
6.63
970681AG2-440 GEN
Solar/Wind Harmer
5.304
3130546PLYMOUTH
Solar/Wind Harmer
0.098
946301AF1-294 GEN
Solar/Wind Harmer
1.782
961791AG1-021 GEN
Solar/Wind Harmer
0.867
316118AC1-105 GEN
Solar/Wind Harmer
0.227
315657AE1-056 GEN
Solar/Wind Harmer
2.895
315816AE2-034 GEN
Solar/Wind Harmer
0.344
3147173SINAI
Solar/Wind Harmer
0.077
3147243WELCO
Solar/Wind Harmer
0.048
970865AG2-541 GEN
Solar/Wind Harmer
2.227
316315AB2-025 C
Solar/Wind Helper
0.826
3143316POE
Solar/Wind Helper
0.688
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3147043LAWRENC
50/50
3.141
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.27
3151581KERR 1
50/50
0.096
3144293JTRSVLE
50/50
0.305
3151531CLOVER1
50/50
1.558
316023GEN1_S
Solar/Wind Harmer
1.155
960081AF2-299 GEN
Solar/Wind Harmer
3.965
971795AH1-408 GEN
Solar/Wind Harmer
23.615
316011AB1-132 GEN
Solar/Wind Harmer
6.186
962571AG1-106 GEN
Solar/Wind Harmer
4.841
3145796HORNRTN
Solar/Wind Harmer
1.046
3145796HORNRTN
Solar/Wind Harmer
0.317
3145783HORNRTN
Solar/Wind Harmer
0.249
315722AD1-056 GEN
Solar/Wind Harmer
1.531
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
1.015
3146263WOODLND
Solar/Wind Harmer
0.191
3146233WITAKRS
Solar/Wind Harmer
0.73
3145823KELFORD
Solar/Wind Harmer
0.177
316359AB2-059 GEN
Solar/Wind Harmer
0.634
316049AB1-081 GEN
Solar/Wind Harmer
1.01
3142053HEARTS
Solar/Wind Harmer
0.311
3145543BTLEBRO
Solar/Wind Harmer
0.175
3145543BTLEBRO
Solar/Wind Harmer
0.14
316129AC1-054 GEN
Solar/Wind Harmer
0.656
971065AG2-659 GEN
Solar/Wind Harmer
7.13
3145683EARLEYS
Solar/Wind Harmer
0.166
961671AG1-007 GEN
Solar/Wind Harmer
0.025
3146083TARBORO
Solar/Wind Harmer
0.165
3145493TOT1
Solar/Wind Harmer
0.732
3146173TUNIS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
0.64
3145893MURPHYS
Solar/Wind Harmer
0.712
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.321
3144293JTRSVLE
50/50
0.305
3144293JTRSVLE
50/50
0.257
3152661PLYWOOD A
50/50
0.195
316181AB2-040 GEN
Solar/Wind Harmer
0.492
3145796HORNRTN
Solar/Wind Harmer
0.951
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3145593CAROLNA
Solar/Wind Harmer
0.257
3145593CAROLNA
Solar/Wind Harmer
0.257
966811AG1-552 GEN
Solar/Wind Harmer
2.785
3145593CAROLNA
Solar/Wind Harmer
0.32
3145783HORNRTN
Solar/Wind Harmer
4.428
3145783HORNRTN
Solar/Wind Harmer
3.543
3145783HORNRTN
Solar/Wind Harmer
1.107
3145783HORNRTN
Solar/Wind Harmer
0.443
316426AA2-053 GEN
Solar/Wind Harmer
0.813
316274AC1-208 GEN
Solar/Wind Harmer
1.081
961601AG1-000A GEN
Solar/Wind Harmer
3.201
316263AC1-034 GEN
Solar/Wind Harmer
6.707
3145493TOT1
Solar/Wind Harmer
0.382
3145453TOT5
Solar/Wind Harmer
0.229
3145603CNETO
Solar/Wind Harmer
0.153
3146173TUNIS
Solar/Wind Harmer
0.163
3146173TUNIS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
1.071
3145893MURPHYS
Solar/Wind Harmer
0.288
3145933PARMELE
Solar/Wind Harmer
0.262
3145933PARMELE
Solar/Wind Harmer
0.131
313527AB2-043 GEN
Solar/Wind Harmer
0.002
939181AE1-148 GEN
Solar/Wind Harmer
6.26
316065AD1-022 GEN
Solar/Wind Harmer
5.298
970323AG2-213 GEN
Solar/Wind Harmer
4.655
971775AH1-396 GEN
Solar/Wind Harmer
0.175
316034AC1-036 C
Solar/Wind Harmer
0.008
962561AG1-105 GEN
Solar/Wind Harmer
5
964791AG1-342 GEN
Solar/Wind Harmer
1.908
3146843MT LREL
Solar/Wind Harmer
0.099
3146843MT LREL
Solar/Wind Harmer
0.099
958211AF2-115 GEN
Solar/Wind Harmer
1.083
963191AG1-168 GEN
Solar/Wind Harmer
0.361
3147133PAMPLIN
Solar/Wind Harmer
0.084
3147133PAMPLIN
Solar/Wind Harmer
0.067
970099AG2-077 GEN
Solar/Wind Harmer
7.723
315742AE1-103 GEN
Solar/Wind Harmer
0.001
971741AH1-377 GEN
Solar/Wind Harmer
5.969
316222AC1-221 GEN
Solar/Wind Harmer
0.242
970301AG2-198 GEN
Solar/Wind Harmer
2.421
3144356SAPONY
Solar/Wind Helper
0.972
316240AF1-291 C
Solar/Wind Helper
0.168
316494AC1-189 GEN
Solar/Wind Harmer
0.514
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3146293MARTNCO
Solar/Wind Harmer
0.122
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.122
971547AH1-271 GEN
Solar/Wind Harmer
2.614
316174AB2-169 GEN
Solar/Wind Harmer
0.003
3145963POPLR C
Solar/Wind Harmer
0.118
970685AG2-442 GEN
Solar/Wind Harmer
7.425
970401AG2-262 GEN
Solar/Wind Harmer
0.583
963171AG1-166 GEN
Solar/Wind Harmer
0.482
971563AH1-280 GEN
Solar/Wind Harmer
0.963
3145663CRESWEL
Solar/Wind Harmer
0.224
971163AH1-040 GEN
Solar/Wind Harmer
6.407
957481AF2-042 GEN
Solar/Wind Harmer
19.308
316003AC1-222 GEN
Solar/Wind Harmer
0.002
315693AD1-088 GEN
Solar/Wind Harmer
3.442
315687AD1-152 GEN
Solar/Wind Harmer
0.002
962491AG1-098 GEN
Solar/Wind Harmer
4.048
CPLELTFEXP_CPLE->PJM
CLTF
4.45
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.218
LAGNLTFEXP_LAGN->PJM
CLTF
2.678
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.707
TVALTFEXP_TVA->PJM
CLTF
1.336
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.85
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.587
MECLTFEXP_MEC->PJM
CLTF
1.327
SIGELTFEXP_SIGE->PJM
CLTF
0.04
NYPJM->LTFIMP_NY
CLTF
0.49
LGEELTFEXP_LGEE->PJM
CLTF
0.481
WECLTFEXP_WEC->PJM
CLTF
0.25

Details for 6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.06 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:889.45
MW Contribution:6.8
Bus #Bus NameTypeMW Contribution
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.27
3151621KERR 5
50/50
0.27
3151631KERR 6
50/50
0.27
3151641KERR 7
50/50
0.27
3151151S HAMPT1
50/50
0.285
3151541CLOVER2
50/50
1.551
316087AB2-174 GEN
Solar/Wind Harmer
0.01
315652AC1-086 GEN
Solar/Wind Harmer
37.428
3145796HORNRTN
Solar/Wind Harmer
1.015
3145796HORNRTN
Solar/Wind Harmer
0.127
3137643SOCKMAN
Solar/Wind Harmer
1.176
315607AA1-063A GEN
Solar/Wind Harmer
0.444
3146043SEABORD
Solar/Wind Harmer
0.211
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3151261ROARAP2
50/50
0.313
3151591KERR 2
50/50
0.27
3144293JTRSVLE
50/50
0.305
970413AG2-270 GEN
50/50
6.801
316365GEN2_N
Solar/Wind Harmer
1.155
313506AB2-031 GEN
Solar/Wind Harmer
1.049
3147043LAWRENC
Solar/Wind Harmer
0.196
3145796HORNRTN
Solar/Wind Harmer
1.268
3145796HORNRTN
Solar/Wind Harmer
0.317
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
315724AD1-057 GEN
Solar/Wind Harmer
0.907
316210AC1-098 GEN
Solar/Wind Harmer
1.821
316327AA2-057 GEN
Solar/Wind Harmer
0.289
3146263WOODLND
Solar/Wind Harmer
0.191
3146233WITAKRS
Solar/Wind Harmer
0.921
3146233WITAKRS
Solar/Wind Harmer
0.125
3138543CONSLDL
Solar/Wind Harmer
0.12
961601AG1-000A GEN
Solar/Wind Harmer
12.805
316317KELFORD C
Solar/Wind Harmer
0.017
3145823KELFORD
Solar/Wind Harmer
0.177
971623AH1-311 GEN
Solar/Wind Harmer
0.353
3145543BTLEBRO
Solar/Wind Harmer
0.175
3145543BTLEBRO
Solar/Wind Harmer
0.175
316463AE2-346 GEN
Solar/Wind Harmer
0.142
316140AB2-099
Solar/Wind Harmer
0.059
962331AG1-082 GEN
Solar/Wind Harmer
1.76
3146073TAR RVR
Solar/Wind Harmer
0.165
3146083TARBORO
Solar/Wind Harmer
0.165
3146173TUNIS
Solar/Wind Harmer
0.163
957521AF2-046 GEN
Solar/Wind Harmer
11.982
961681AG1-008 GEN
Solar/Wind Harmer
11.982
3145893MURPHYS
Solar/Wind Harmer
0.268
3145893MURPHYS
Solar/Wind Harmer
0.16
3156021HOLLOMANSOL
Solar/Wind Harmer
0.689
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3145933PARMELE
Solar/Wind Harmer
0.131
966801AG1-551 GEN
Solar/Wind Harmer
1.529
316131AB2-060 GEN
Solar/Wind Harmer
0.407
964241AG1-285 GEN
Solar/Wind Harmer
8.211
3146206CASHIE
Solar/Wind Harmer
0.122
3145963POPLR C
Solar/Wind Harmer
0.118
315785AD2-033 C
Solar/Wind Harmer
0.918
970257AG2-171 GEN
Solar/Wind Harmer
3.491
959311AF2-222 GEN
Solar/Wind Harmer
9.454
315737AD1-076 GEN
Solar/Wind Harmer
1.314
971157AH1-035 GEN
Solar/Wind Harmer
1.183
963181AG1-167 GEN
Solar/Wind Harmer
0.361
3147133PAMPLIN
Solar/Wind Harmer
0.263
971193AH1-056 GEN
Solar/Wind Harmer
5.112
315614AA2-178 GEN
Solar/Wind Harmer
0.458
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.273
316478AD1-087 GEN
Solar/Wind Harmer
0.254
316486AD2-202 GEN
Solar/Wind Harmer
0.075
971683AH1-343 GEN
Solar/Wind Harmer
2.513
942461AE2-259 GEN
Solar/Wind Harmer
0
316283AC2-100 C
Solar/Wind Harmer
0.113
970909AG2-566 GEN
Solar/Wind Harmer
0.605
315839AE2-212 C
Solar/Wind Helper
0.197
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3146033SCOT NK
Solar/Wind Harmer
0.75
316319Z2-044 C
Solar/Wind Harmer
0
970831AG2-522 GEN
Solar/Wind Harmer
7.783
3145683EARLEYS
Solar/Wind Harmer
0.333
3145683EARLEYS
Solar/Wind Harmer
0.166
3145683EARLEYS
Solar/Wind Harmer
0.166
3145513AHOSKIE
Solar/Wind Harmer
0.345
3145513AHOSKIE
Solar/Wind Harmer
0.165
3145573BETHELC
Solar/Wind Harmer
0.165
3145573BETHELC
Solar/Wind Harmer
0.165
3145893MURPHYS
Solar/Wind Harmer
0.432
3145893MURPHYS
Solar/Wind Harmer
0.16
316420AA1-050 GEN
Solar/Wind Harmer
0.005
965291AG1-394 GEN
Solar/Wind Harmer
0.698
957861AF2-080 GEN
Solar/Wind Harmer
6.563
316005AA1-067
Solar/Wind Harmer
0.148
3145746EVERETS
Solar/Wind Harmer
0.548
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
970181AG2-120 GEN
Solar/Wind Harmer
1.713
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.122
970601AG2-382 GEN
Solar/Wind Harmer
4.575
971443AH1-215 GEN
Solar/Wind Harmer
1.848
3144303KENBRDG
Solar/Wind Harmer
0.087
315732AD1-074 GEN1
Solar/Wind Harmer
0.587
315733AD1-074 GEN2
Solar/Wind Harmer
0.587
315735AD1-075 GEN1
Solar/Wind Harmer
0.294
970683AG2-441 GEN
Solar/Wind Harmer
6.63
970681AG2-440 GEN
Solar/Wind Harmer
5.304
3130546PLYMOUTH
Solar/Wind Harmer
0.098
946301AF1-294 GEN
Solar/Wind Harmer
1.782
961791AG1-021 GEN
Solar/Wind Harmer
0.867
316118AC1-105 GEN
Solar/Wind Harmer
0.227
315657AE1-056 GEN
Solar/Wind Harmer
2.895
315816AE2-034 GEN
Solar/Wind Harmer
0.344
3147173SINAI
Solar/Wind Harmer
0.077
3147243WELCO
Solar/Wind Harmer
0.048
971967AH1-528 GEN
Solar/Wind Harmer
11.557
970865AG2-541 GEN
Solar/Wind Harmer
2.227
316315AB2-025 C
Solar/Wind Helper
0.826
3143316POE
Solar/Wind Helper
0.688
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.321
3144293JTRSVLE
50/50
0.305
3144293JTRSVLE
50/50
0.257
3152661PLYWOOD A
50/50
0.195
316181AB2-040 GEN
Solar/Wind Harmer
0.492
3145796HORNRTN
Solar/Wind Harmer
0.951
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3145593CAROLNA
Solar/Wind Harmer
0.257
3145593CAROLNA
Solar/Wind Harmer
0.257
966811AG1-552 GEN
Solar/Wind Harmer
2.785
3145593CAROLNA
Solar/Wind Harmer
0.32
3145783HORNRTN
Solar/Wind Harmer
4.428
3145783HORNRTN
Solar/Wind Harmer
3.543
3145783HORNRTN
Solar/Wind Harmer
1.107
3145783HORNRTN
Solar/Wind Harmer
0.443
316426AA2-053 GEN
Solar/Wind Harmer
0.813
316274AC1-208 GEN
Solar/Wind Harmer
1.081
961601AG1-000A GEN
Solar/Wind Harmer
3.201
316263AC1-034 GEN
Solar/Wind Harmer
6.707
3145493TOT1
Solar/Wind Harmer
0.382
3145453TOT5
Solar/Wind Harmer
0.229
3145603CNETO
Solar/Wind Harmer
0.153
3146173TUNIS
Solar/Wind Harmer
0.163
3146173TUNIS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
1.071
3145893MURPHYS
Solar/Wind Harmer
0.288
3145933PARMELE
Solar/Wind Harmer
0.262
3145933PARMELE
Solar/Wind Harmer
0.131
313527AB2-043 GEN
Solar/Wind Harmer
0.002
939181AE1-148 GEN
Solar/Wind Harmer
6.26
316065AD1-022 GEN
Solar/Wind Harmer
5.298
970323AG2-213 GEN
Solar/Wind Harmer
4.655
971775AH1-396 GEN
Solar/Wind Harmer
0.175
316034AC1-036 C
Solar/Wind Harmer
0.008
962561AG1-105 GEN
Solar/Wind Harmer
5
964791AG1-342 GEN
Solar/Wind Harmer
1.908
3146843MT LREL
Solar/Wind Harmer
0.099
3146843MT LREL
Solar/Wind Harmer
0.099
958211AF2-115 GEN
Solar/Wind Harmer
1.083
963191AG1-168 GEN
Solar/Wind Harmer
0.361
3147133PAMPLIN
Solar/Wind Harmer
0.084
3147133PAMPLIN
Solar/Wind Harmer
0.067
970099AG2-077 GEN
Solar/Wind Harmer
7.723
970933AG2-581 GEN
Solar/Wind Harmer
5.779
315742AE1-103 GEN
Solar/Wind Harmer
0.001
971741AH1-377 GEN
Solar/Wind Harmer
5.969
316222AC1-221 GEN
Solar/Wind Harmer
0.242
970301AG2-198 GEN
Solar/Wind Harmer
2.421
3144356SAPONY
Solar/Wind Helper
0.972
316240AF1-291 C
Solar/Wind Helper
0.168
3147043LAWRENC
50/50
3.141
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.27
3151581KERR 1
50/50
0.096
3144293JTRSVLE
50/50
0.305
3151531CLOVER1
50/50
1.558
316023GEN1_S
Solar/Wind Harmer
1.155
960081AF2-299 GEN
Solar/Wind Harmer
3.965
971795AH1-408 GEN
Solar/Wind Harmer
23.615
316011AB1-132 GEN
Solar/Wind Harmer
6.186
962571AG1-106 GEN
Solar/Wind Harmer
4.841
3145796HORNRTN
Solar/Wind Harmer
1.046
3145796HORNRTN
Solar/Wind Harmer
0.317
3145783HORNRTN
Solar/Wind Harmer
0.249
315722AD1-056 GEN
Solar/Wind Harmer
1.531
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
1.015
3146263WOODLND
Solar/Wind Harmer
0.191
3146233WITAKRS
Solar/Wind Harmer
0.73
3145823KELFORD
Solar/Wind Harmer
0.177
316359AB2-059 GEN
Solar/Wind Harmer
0.634
316049AB1-081 GEN
Solar/Wind Harmer
1.01
3142053HEARTS
Solar/Wind Harmer
0.311
3145543BTLEBRO
Solar/Wind Harmer
0.175
3145543BTLEBRO
Solar/Wind Harmer
0.14
316129AC1-054 GEN
Solar/Wind Harmer
0.656
971065AG2-659 GEN
Solar/Wind Harmer
7.13
3145683EARLEYS
Solar/Wind Harmer
0.166
961671AG1-007 GEN
Solar/Wind Harmer
0.025
3146083TARBORO
Solar/Wind Harmer
0.165
3145493TOT1
Solar/Wind Harmer
0.732
3146173TUNIS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
0.64
3145893MURPHYS
Solar/Wind Harmer
0.712
316494AC1-189 GEN
Solar/Wind Harmer
0.514
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3146293MARTNCO
Solar/Wind Harmer
0.122
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.122
971547AH1-271 GEN
Solar/Wind Harmer
2.614
316174AB2-169 GEN
Solar/Wind Harmer
0.003
3145963POPLR C
Solar/Wind Harmer
0.118
970685AG2-442 GEN
Solar/Wind Harmer
7.425
970401AG2-262 GEN
Solar/Wind Harmer
0.583
963171AG1-166 GEN
Solar/Wind Harmer
0.482
971563AH1-280 GEN
Solar/Wind Harmer
0.963
3145663CRESWEL
Solar/Wind Harmer
0.224
971163AH1-040 GEN
Solar/Wind Harmer
6.407
957481AF2-042 GEN
Solar/Wind Harmer
19.308
316003AC1-222 GEN
Solar/Wind Harmer
0.002
315693AD1-088 GEN
Solar/Wind Harmer
3.442
315687AD1-152 GEN
Solar/Wind Harmer
0.002
962491AG1-098 GEN
Solar/Wind Harmer
4.048
CPLELTFEXP_CPLE->PJM
CLTF
4.45
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.218
LAGNLTFEXP_LAGN->PJM
CLTF
2.678
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.707
TVALTFEXP_TVA->PJM
CLTF
1.336
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.85
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.587
MECLTFEXP_MEC->PJM
CLTF
1.327
SIGELTFEXP_SIGE->PJM
CLTF
0.04
NYPJM->LTFIMP_NY
CLTF
0.49
LGEELTFEXP_LGEE->PJM
CLTF
0.481
WECLTFEXP_WEC->PJM
CLTF
0.25

Details for 6EDMONSON-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6SEDGE HILL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.9 %
Rating:997.0 MVA
Rating Type:C
MVA to Mitigate:1035.9
MW Contribution:56.8
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
12.953
3151611KERR 4
50/50
0.363
3151621KERR 5
50/50
0.363
3151631KERR 6
50/50
0.363
3151641KERR 7
50/50
0.363
972205AH1-687 GEN
50/50
5.359
971967AH1-528 GEN
Solar/Wind Harmer
119.231
970285AG2-188 GEN
Solar/Wind Harmer
22.292
971845AH1-439 GEN
Solar/Wind Harmer
12.82
315657AE1-056 GEN
Solar/Wind Harmer
9.035
946301AF1-294 GEN
Solar/Wind Harmer
5.845
961791AG1-021 GEN
Solar/Wind Harmer
2.851
970683AG2-441 GEN
Solar/Wind Harmer
16.398
970681AG2-440 GEN
Solar/Wind Harmer
13.118
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.717
316239AB2-077_GEN
Solar/Wind Harmer
0.417
316238AB2-078_GEN
Solar/Wind Harmer
0.417
970831AG2-522 GEN
Solar/Wind Harmer
6.725
971447AH1-217 GEN
Solar/Wind Harmer
3.924
270494AE1-108_GEN
Solar/Wind Harmer
2.176
3147173SINAI
Solar/Wind Helper
0.374
3147243WELCO
Solar/Wind Helper
0.234
316123AC1-075 GEN
Solar/Wind Helper
1.587
316118AC1-105 GEN
Solar/Wind Helper
0.947
270455AD2-022 GEN
Solar/Wind Helper
0.922
270457AD2-023 GEN
Solar/Wind Helper
0.608
970413AG2-270 GEN
50/50
56.795
3144293JTRSVLE
50/50
0.686
3151591KERR 2
50/50
0.363
3151921BEARGRDN G2
50/50
1.099
316478AD1-087 GEN
Solar/Wind Harmer
5.94
316486AD2-202 GEN
Solar/Wind Harmer
1.74
970909AG2-566 GEN
Solar/Wind Harmer
4.103
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.165
3147133PAMPLIN
Solar/Wind Harmer
-0.075
971193AH1-056 GEN
Solar/Wind Harmer
15.059
3146776BUCKING
Solar/Wind Harmer
-0.008
963181AG1-167 GEN
Solar/Wind Harmer
2.139
959311AF2-222 GEN
Solar/Wind Harmer
20.462
970257AG2-171 GEN
Solar/Wind Harmer
7.138
315785AD2-033 C
Solar/Wind Harmer
4.14
964241AG1-285 GEN
Solar/Wind Harmer
12.684
316131AB2-060 GEN
Solar/Wind Harmer
1.616
970221AG2-151 GEN
Solar/Wind Harmer
7.267
3147043LAWRENC
Solar/Wind Harmer
-0.004
316313AB2-026
Solar/Wind Harmer
0.185
316258AE1-075 C
Solar/Wind Harmer
0.166
316405AF2-144 C
Solar/Wind Harmer
0.176
3143336POWHATN
Solar/Wind Harmer
0.692
316248AF1-058 C
Solar/Wind Helper
0.503
316283AC2-100 C
Solar/Wind Helper
1.45
3147312GRETNA
Solar/Wind Helper
0.023
3144293JTRSVLE
50/50
0.686
3144293JTRSVLE
50/50
0.578
970535AG2-341 GEN
50/50
2.746
970099AG2-077 GEN
Solar/Wind Harmer
80.733
970933AG2-581 GEN
Solar/Wind Harmer
59.456
971741AH1-377 GEN
Solar/Wind Harmer
54.374
970301AG2-198 GEN
Solar/Wind Harmer
21.608
3147133PAMPLIN
Solar/Wind Harmer
-0.024
3147133PAMPLIN
Solar/Wind Harmer
-0.019
3146776BUCKING
Solar/Wind Harmer
-0.093
3146776BUCKING
Solar/Wind Harmer
-0.008
958211AF2-115 GEN
Solar/Wind Harmer
3.564
963191AG1-168 GEN
Solar/Wind Harmer
2.139
316034AC1-036 C
Solar/Wind Harmer
0.354
970323AG2-213 GEN
Solar/Wind Harmer
9.517
971775AH1-396 GEN
Solar/Wind Harmer
1.355
939181AE1-148 GEN
Solar/Wind Harmer
10.582
313527AB2-043 GEN
Solar/Wind Harmer
2.387
971489AH1-241 GEN
Solar/Wind Harmer
6.899
315821AE2-092 GEN
Solar/Wind Harmer
1.789
316222AC1-221 GEN
Solar/Wind Helper
1.594
316197AC1-042 GEN
Solar/Wind Helper
0.109
270013AE1-250 PV
Solar/Wind Helper
0.416
3146843MT LREL
Solar/Wind Helper
0.112
3146843MT LREL
Solar/Wind Helper
0.112
3151531CLOVER1
50/50
13.015
3144293JTRSVLE
50/50
0.686
3151601KERR 3
50/50
0.363
3151581KERR 1
50/50
0.13
3151931BEARGRDN S1
50/50
1.418
3151911BEARGRDN G1
50/50
1.099
315687AD1-152 GEN
Solar/Wind Harmer
9.7
957481AF2-042 GEN
Solar/Wind Harmer
201.833
315693AD1-088 GEN
Solar/Wind Harmer
29.361
962491AG1-098 GEN
Solar/Wind Harmer
38.734
3146926FARMVIL
Solar/Wind Harmer
-0.019
316322AB2-045
Solar/Wind Harmer
0.788
3146776BUCKING
Solar/Wind Harmer
-0.009
963171AG1-166 GEN
Solar/Wind Harmer
2.851
971563AH1-280 GEN
Solar/Wind Harmer
2.851
970685AG2-442 GEN
Solar/Wind Harmer
18.365
971065AG2-659 GEN
Solar/Wind Harmer
7.646
972003AH1-546 GEN
Solar/Wind Harmer
7.552
316129AC1-054 GEN
Solar/Wind Harmer
1.263
316237AB2-079_GEN
Solar/Wind Harmer
0.417
971377AH1-170 GEN
Solar/Wind Harmer
1.453
3147623JAMES R
Solar/Wind Harmer
0.18
970937AG2-583 GEN
Solar/Wind Harmer
7.798
316336AC2-165 C
Solar/Wind Harmer
1.386
3147043LAWRENC
Adder
0.584
3143336POWHATN
Solar/Wind Harmer
0.814
316003AC1-222 GEN
Solar/Wind Helper
1.516
3147123OTTER R
Solar/Wind Helper
0.083
3147312GRETNA
Solar/Wind Helper
0.093
3146802CHATHAM
Solar/Wind Helper
0.087
270016AE1-250 BESS
Solar/Wind Helper
0.416
G-007ALTFEXP_G-007A->PJM
CMTX
0.61
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.686
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.756
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.372
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.612
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.251
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.119
HAMLETPJM->LTFIMP_HAMLET
CLTF
2.242

Details for 6EDMONSON-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6SEDGE HILL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.06 %
Rating:997.0 MVA
Rating Type:C
MVA to Mitigate:1017.58
MW Contribution:56.73
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
12.939
3151611KERR 4
50/50
0.362
3151621KERR 5
50/50
0.362
3151631KERR 6
50/50
0.362
3151641KERR 7
50/50
0.362
972205AH1-687 GEN
50/50
5.369
971967AH1-528 GEN
Solar/Wind Harmer
119.102
970285AG2-188 GEN
Solar/Wind Harmer
22.288
970413AG2-270 GEN
50/50
56.734
3144293JTRSVLE
50/50
0.685
3151591KERR 2
50/50
0.362
3151921BEARGRDN G2
50/50
1.101
316478AD1-087 GEN
Solar/Wind Harmer
5.933
316486AD2-202 GEN
Solar/Wind Harmer
1.738
970909AG2-566 GEN
Solar/Wind Harmer
4.099
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.161
3147133PAMPLIN
Solar/Wind Harmer
-0.075
971193AH1-056 GEN
Solar/Wind Harmer
15.038
3146776BUCKING
Solar/Wind Harmer
-0.008
963181AG1-167 GEN
Solar/Wind Harmer
2.135
959311AF2-222 GEN
Solar/Wind Harmer
20.417
970257AG2-171 GEN
Solar/Wind Harmer
7.122
315785AD2-033 C
Solar/Wind Harmer
4.129
964241AG1-285 GEN
Solar/Wind Harmer
12.645
316131AB2-060 GEN
Solar/Wind Harmer
1.61
970221AG2-151 GEN
Solar/Wind Harmer
7.28
3147043LAWRENC
Solar/Wind Harmer
-0.004
316313AB2-026
Solar/Wind Harmer
0.187
316258AE1-075 C
Solar/Wind Harmer
0.168
316405AF2-144 C
Solar/Wind Harmer
0.177
3143336POWHATN
Solar/Wind Harmer
0.698
316248AF1-058 C
Solar/Wind Helper
0.505
316283AC2-100 C
Solar/Wind Helper
1.462
3147312GRETNA
Solar/Wind Helper
0.023
3151531CLOVER1
50/50
13.001
3144293JTRSVLE
50/50
0.685
3151601KERR 3
50/50
0.362
3151581KERR 1
50/50
0.129
3151931BEARGRDN S1
50/50
1.421
3151911BEARGRDN G1
50/50
1.101
315687AD1-152 GEN
Solar/Wind Harmer
9.69
957481AF2-042 GEN
Solar/Wind Harmer
201.613
315693AD1-088 GEN
Solar/Wind Harmer
29.329
962491AG1-098 GEN
Solar/Wind Harmer
38.693
3146926FARMVIL
Solar/Wind Harmer
-0.019
316322AB2-045
Solar/Wind Harmer
0.788
3146776BUCKING
Solar/Wind Harmer
-0.009
963171AG1-166 GEN
Solar/Wind Harmer
2.847
971563AH1-280 GEN
Solar/Wind Harmer
2.847
970685AG2-442 GEN
Solar/Wind Harmer
18.33
971065AG2-659 GEN
Solar/Wind Harmer
7.623
972003AH1-546 GEN
Solar/Wind Harmer
7.562
316129AC1-054 GEN
Solar/Wind Harmer
1.259
316237AB2-079_GEN
Solar/Wind Harmer
0.415
971377AH1-170 GEN
Solar/Wind Harmer
1.456
3147623JAMES R
Solar/Wind Harmer
0.18
970937AG2-583 GEN
Solar/Wind Harmer
7.825
316336AC2-165 C
Solar/Wind Harmer
1.396
3147043LAWRENC
Adder
0.584
3143336POWHATN
Solar/Wind Harmer
0.821
316003AC1-222 GEN
Solar/Wind Helper
1.523
3147123OTTER R
Solar/Wind Helper
0.083
3147312GRETNA
Solar/Wind Helper
0.093
3146802CHATHAM
Solar/Wind Helper
0.087
270016AE1-250 BESS
Solar/Wind Helper
0.421
971845AH1-439 GEN
Solar/Wind Harmer
12.819
315657AE1-056 GEN
Solar/Wind Harmer
9.023
946301AF1-294 GEN
Solar/Wind Harmer
5.836
961791AG1-021 GEN
Solar/Wind Harmer
2.847
970683AG2-441 GEN
Solar/Wind Harmer
16.366
970681AG2-440 GEN
Solar/Wind Harmer
13.093
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.708
316239AB2-077_GEN
Solar/Wind Harmer
0.415
316238AB2-078_GEN
Solar/Wind Harmer
0.415
970831AG2-522 GEN
Solar/Wind Harmer
6.705
971447AH1-217 GEN
Solar/Wind Harmer
3.932
270494AE1-108_GEN
Solar/Wind Harmer
2.178
3147173SINAI
Solar/Wind Helper
0.376
3147243WELCO
Solar/Wind Helper
0.235
316123AC1-075 GEN
Solar/Wind Helper
1.594
316118AC1-105 GEN
Solar/Wind Helper
0.953
270455AD2-022 GEN
Solar/Wind Helper
0.936
270457AD2-023 GEN
Solar/Wind Helper
0.617
3144293JTRSVLE
50/50
0.685
3144293JTRSVLE
50/50
0.577
970535AG2-341 GEN
50/50
2.737
970099AG2-077 GEN
Solar/Wind Harmer
80.645
970933AG2-581 GEN
Solar/Wind Harmer
59.392
971741AH1-377 GEN
Solar/Wind Harmer
54.323
970301AG2-198 GEN
Solar/Wind Harmer
21.589
3147133PAMPLIN
Solar/Wind Harmer
-0.024
3147133PAMPLIN
Solar/Wind Harmer
-0.019
3146776BUCKING
Solar/Wind Harmer
-0.093
3146776BUCKING
Solar/Wind Harmer
-0.008
958211AF2-115 GEN
Solar/Wind Harmer
3.559
963191AG1-168 GEN
Solar/Wind Harmer
2.135
316034AC1-036 C
Solar/Wind Harmer
0.353
970323AG2-213 GEN
Solar/Wind Harmer
9.495
971775AH1-396 GEN
Solar/Wind Harmer
1.352
939181AE1-148 GEN
Solar/Wind Harmer
10.548
313527AB2-043 GEN
Solar/Wind Harmer
2.378
971489AH1-241 GEN
Solar/Wind Harmer
6.911
315821AE2-092 GEN
Solar/Wind Harmer
1.794
316222AC1-221 GEN
Solar/Wind Helper
1.608
316197AC1-042 GEN
Solar/Wind Helper
0.109
270013AE1-250 PV
Solar/Wind Helper
0.421
3146843MT LREL
Solar/Wind Helper
0.113
3146843MT LREL
Solar/Wind Helper
0.113
G-007ALTFEXP_G-007A->PJM
CMTX
0.675
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.798
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.769
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.415
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.784
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.284
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.201
HAMLETPJM->LTFIMP_HAMLET
CLTF
2.312

Details for 6EDMONSON-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6SEDGE HILL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.05 %
Rating:997.0 MVA
Rating Type:C
MVA to Mitigate:1017.41
MW Contribution:56.73
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
56.734
3144293JTRSVLE
50/50
0.685
3151591KERR 2
50/50
0.362
3151921BEARGRDN G2
50/50
1.101
316478AD1-087 GEN
Solar/Wind Harmer
5.933
316486AD2-202 GEN
Solar/Wind Harmer
1.738
970909AG2-566 GEN
Solar/Wind Harmer
4.099
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.161
3147133PAMPLIN
Solar/Wind Harmer
-0.075
971193AH1-056 GEN
Solar/Wind Harmer
15.038
3146776BUCKING
Solar/Wind Harmer
-0.008
963181AG1-167 GEN
Solar/Wind Harmer
2.135
959311AF2-222 GEN
Solar/Wind Harmer
20.417
970257AG2-171 GEN
Solar/Wind Harmer
7.122
315785AD2-033 C
Solar/Wind Harmer
4.129
964241AG1-285 GEN
Solar/Wind Harmer
12.645
316131AB2-060 GEN
Solar/Wind Harmer
1.61
970221AG2-151 GEN
Solar/Wind Harmer
7.28
3147043LAWRENC
Solar/Wind Harmer
-0.004
316313AB2-026
Solar/Wind Harmer
0.187
316258AE1-075 C
Solar/Wind Harmer
0.168
316405AF2-144 C
Solar/Wind Harmer
0.177
3143336POWHATN
Solar/Wind Harmer
0.698
316248AF1-058 C
Solar/Wind Helper
0.505
316283AC2-100 C
Solar/Wind Helper
1.462
3147312GRETNA
Solar/Wind Helper
0.023
3151531CLOVER1
50/50
13.001
3144293JTRSVLE
50/50
0.685
3151541CLOVER2
50/50
12.939
3151611KERR 4
50/50
0.362
3151621KERR 5
50/50
0.362
3151631KERR 6
50/50
0.362
3151641KERR 7
50/50
0.362
972205AH1-687 GEN
50/50
5.369
971967AH1-528 GEN
Solar/Wind Harmer
119.102
970285AG2-188 GEN
Solar/Wind Harmer
22.288
971845AH1-439 GEN
Solar/Wind Harmer
12.819
315657AE1-056 GEN
Solar/Wind Harmer
9.023
946301AF1-294 GEN
Solar/Wind Harmer
5.836
961791AG1-021 GEN
Solar/Wind Harmer
2.847
970683AG2-441 GEN
Solar/Wind Harmer
16.366
970681AG2-440 GEN
Solar/Wind Harmer
13.093
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.708
316239AB2-077_GEN
Solar/Wind Harmer
0.415
316238AB2-078_GEN
Solar/Wind Harmer
0.415
970831AG2-522 GEN
Solar/Wind Harmer
6.705
971447AH1-217 GEN
Solar/Wind Harmer
3.932
270494AE1-108_GEN
Solar/Wind Harmer
2.178
3147173SINAI
Solar/Wind Helper
0.376
3147243WELCO
Solar/Wind Helper
0.235
316123AC1-075 GEN
Solar/Wind Helper
1.594
316118AC1-105 GEN
Solar/Wind Helper
0.953
270455AD2-022 GEN
Solar/Wind Helper
0.936
270457AD2-023 GEN
Solar/Wind Helper
0.617
3144293JTRSVLE
50/50
0.685
3144293JTRSVLE
50/50
0.577
970535AG2-341 GEN
50/50
2.737
970099AG2-077 GEN
Solar/Wind Harmer
80.645
970933AG2-581 GEN
Solar/Wind Harmer
59.392
971741AH1-377 GEN
Solar/Wind Harmer
54.323
970301AG2-198 GEN
Solar/Wind Harmer
21.589
3147133PAMPLIN
Solar/Wind Harmer
-0.024
3147133PAMPLIN
Solar/Wind Harmer
-0.019
3146776BUCKING
Solar/Wind Harmer
-0.093
3146776BUCKING
Solar/Wind Harmer
-0.008
958211AF2-115 GEN
Solar/Wind Harmer
3.559
963191AG1-168 GEN
Solar/Wind Harmer
2.135
316034AC1-036 C
Solar/Wind Harmer
0.353
970323AG2-213 GEN
Solar/Wind Harmer
9.495
971775AH1-396 GEN
Solar/Wind Harmer
1.352
939181AE1-148 GEN
Solar/Wind Harmer
10.548
313527AB2-043 GEN
Solar/Wind Harmer
2.378
971489AH1-241 GEN
Solar/Wind Harmer
6.911
315821AE2-092 GEN
Solar/Wind Harmer
1.794
316222AC1-221 GEN
Solar/Wind Helper
1.608
316197AC1-042 GEN
Solar/Wind Helper
0.109
270013AE1-250 PV
Solar/Wind Helper
0.421
3146843MT LREL
Solar/Wind Helper
0.113
3146843MT LREL
Solar/Wind Helper
0.113
3151601KERR 3
50/50
0.362
3151581KERR 1
50/50
0.129
3151931BEARGRDN S1
50/50
1.421
3151911BEARGRDN G1
50/50
1.101
315687AD1-152 GEN
Solar/Wind Harmer
9.69
957481AF2-042 GEN
Solar/Wind Harmer
201.613
315693AD1-088 GEN
Solar/Wind Harmer
29.329
962491AG1-098 GEN
Solar/Wind Harmer
38.693
3146926FARMVIL
Solar/Wind Harmer
-0.019
316322AB2-045
Solar/Wind Harmer
0.788
3146776BUCKING
Solar/Wind Harmer
-0.009
963171AG1-166 GEN
Solar/Wind Harmer
2.847
971563AH1-280 GEN
Solar/Wind Harmer
2.847
970685AG2-442 GEN
Solar/Wind Harmer
18.33
971065AG2-659 GEN
Solar/Wind Harmer
7.623
972003AH1-546 GEN
Solar/Wind Harmer
7.562
316129AC1-054 GEN
Solar/Wind Harmer
1.259
316237AB2-079_GEN
Solar/Wind Harmer
0.415
971377AH1-170 GEN
Solar/Wind Harmer
1.456
3147623JAMES R
Solar/Wind Harmer
0.18
970937AG2-583 GEN
Solar/Wind Harmer
7.825
316336AC2-165 C
Solar/Wind Harmer
1.396
3147043LAWRENC
Adder
0.584
3143336POWHATN
Solar/Wind Harmer
0.821
316003AC1-222 GEN
Solar/Wind Helper
1.523
3147123OTTER R
Solar/Wind Helper
0.083
3147312GRETNA
Solar/Wind Helper
0.093
3146802CHATHAM
Solar/Wind Helper
0.087
270016AE1-250 BESS
Solar/Wind Helper
0.421
G-007ALTFEXP_G-007A->PJM
CMTX
0.675
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.798
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.769
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.415
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.784
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.284
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.201
HAMLETPJM->LTFIMP_HAMLET
CLTF
2.312

Details for 6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:141.24 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:958.54
MW Contribution:6.8
Bus #Bus NameTypeMW Contribution
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.321
3144293JTRSVLE
50/50
0.305
3144293JTRSVLE
50/50
0.257
3152661PLYWOOD A
50/50
0.195
316181AB2-040 GEN
Solar/Wind Harmer
0.492
3145796HORNRTN
Solar/Wind Harmer
0.951
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3145593CAROLNA
Solar/Wind Harmer
0.257
3145593CAROLNA
Solar/Wind Harmer
0.257
966811AG1-552 GEN
Solar/Wind Harmer
2.785
3145593CAROLNA
Solar/Wind Harmer
0.32
3145783HORNRTN
Solar/Wind Harmer
4.428
3145783HORNRTN
Solar/Wind Harmer
3.543
3145783HORNRTN
Solar/Wind Harmer
1.107
3145783HORNRTN
Solar/Wind Harmer
0.443
316426AA2-053 GEN
Solar/Wind Harmer
0.813
316274AC1-208 GEN
Solar/Wind Harmer
1.081
961601AG1-000A GEN
Solar/Wind Harmer
3.201
316263AC1-034 GEN
Solar/Wind Harmer
6.707
3145493TOT1
Solar/Wind Harmer
0.382
3145453TOT5
Solar/Wind Harmer
0.229
3145603CNETO
Solar/Wind Harmer
0.153
3146173TUNIS
Solar/Wind Harmer
0.163
3146173TUNIS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
1.071
3145893MURPHYS
Solar/Wind Harmer
0.288
3145933PARMELE
Solar/Wind Harmer
0.262
3145933PARMELE
Solar/Wind Harmer
0.131
313527AB2-043 GEN
Solar/Wind Harmer
0.002
939181AE1-148 GEN
Solar/Wind Harmer
6.26
316065AD1-022 GEN
Solar/Wind Harmer
5.298
970323AG2-213 GEN
Solar/Wind Harmer
4.655
971775AH1-396 GEN
Solar/Wind Harmer
0.175
316034AC1-036 C
Solar/Wind Harmer
0.008
962561AG1-105 GEN
Solar/Wind Harmer
5
964791AG1-342 GEN
Solar/Wind Harmer
1.908
3146843MT LREL
Solar/Wind Harmer
0.099
3146843MT LREL
Solar/Wind Harmer
0.099
958211AF2-115 GEN
Solar/Wind Harmer
1.083
963191AG1-168 GEN
Solar/Wind Harmer
0.361
3147133PAMPLIN
Solar/Wind Harmer
0.084
3147133PAMPLIN
Solar/Wind Harmer
0.067
970099AG2-077 GEN
Solar/Wind Harmer
7.723
315742AE1-103 GEN
Solar/Wind Harmer
0.001
971741AH1-377 GEN
Solar/Wind Harmer
5.969
316222AC1-221 GEN
Solar/Wind Harmer
0.242
970301AG2-198 GEN
Solar/Wind Harmer
2.421
3144356SAPONY
Solar/Wind Helper
0.972
316240AF1-291 C
Solar/Wind Helper
0.168
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.27
3151621KERR 5
50/50
0.27
3151631KERR 6
50/50
0.27
3151641KERR 7
50/50
0.27
3151151S HAMPT1
50/50
0.285
3151541CLOVER2
50/50
1.551
315814AE2-033 C
Solar/Wind Harmer
65.923
316087AB2-174 GEN
Solar/Wind Harmer
0.01
315652AC1-086 GEN
Solar/Wind Harmer
37.428
3145796HORNRTN
Solar/Wind Harmer
1.015
3145796HORNRTN
Solar/Wind Harmer
0.127
3137643SOCKMAN
Solar/Wind Harmer
1.176
315607AA1-063A GEN
Solar/Wind Harmer
0.444
3146043SEABORD
Solar/Wind Harmer
0.211
3146033SCOT NK
Solar/Wind Harmer
0.75
316319Z2-044 C
Solar/Wind Harmer
0
970831AG2-522 GEN
Solar/Wind Harmer
7.783
3145683EARLEYS
Solar/Wind Harmer
0.333
3145683EARLEYS
Solar/Wind Harmer
0.166
3145683EARLEYS
Solar/Wind Harmer
0.166
3145513AHOSKIE
Solar/Wind Harmer
0.345
3145513AHOSKIE
Solar/Wind Harmer
0.165
3145573BETHELC
Solar/Wind Harmer
0.165
3145573BETHELC
Solar/Wind Harmer
0.165
3145893MURPHYS
Solar/Wind Harmer
0.432
3145893MURPHYS
Solar/Wind Harmer
0.16
316420AA1-050 GEN
Solar/Wind Harmer
0.005
965291AG1-394 GEN
Solar/Wind Harmer
0.698
957861AF2-080 GEN
Solar/Wind Harmer
6.563
316005AA1-067
Solar/Wind Harmer
0.148
3145746EVERETS
Solar/Wind Harmer
0.548
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
970181AG2-120 GEN
Solar/Wind Harmer
1.713
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.122
970601AG2-382 GEN
Solar/Wind Harmer
4.575
971443AH1-215 GEN
Solar/Wind Harmer
1.848
3144303KENBRDG
Solar/Wind Harmer
0.087
315732AD1-074 GEN1
Solar/Wind Harmer
0.587
315733AD1-074 GEN2
Solar/Wind Harmer
0.587
315735AD1-075 GEN1
Solar/Wind Harmer
0.294
970683AG2-441 GEN
Solar/Wind Harmer
6.63
970681AG2-440 GEN
Solar/Wind Harmer
5.304
3130546PLYMOUTH
Solar/Wind Harmer
0.098
946301AF1-294 GEN
Solar/Wind Harmer
1.782
961791AG1-021 GEN
Solar/Wind Harmer
0.867
316118AC1-105 GEN
Solar/Wind Harmer
0.227
315657AE1-056 GEN
Solar/Wind Harmer
2.895
315816AE2-034 GEN
Solar/Wind Harmer
0.344
3147173SINAI
Solar/Wind Harmer
0.077
3147243WELCO
Solar/Wind Harmer
0.048
970865AG2-541 GEN
Solar/Wind Harmer
2.227
316315AB2-025 C
Solar/Wind Helper
0.826
3143316POE
Solar/Wind Helper
0.688
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3151261ROARAP2
50/50
0.313
3151591KERR 2
50/50
0.27
3144293JTRSVLE
50/50
0.305
970413AG2-270 GEN
50/50
6.801
316365GEN2_N
Solar/Wind Harmer
1.155
313506AB2-031 GEN
Solar/Wind Harmer
1.049
3147043LAWRENC
Solar/Wind Harmer
0.196
3145796HORNRTN
Solar/Wind Harmer
1.268
3145796HORNRTN
Solar/Wind Harmer
0.317
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
315724AD1-057 GEN
Solar/Wind Harmer
0.907
316210AC1-098 GEN
Solar/Wind Harmer
1.821
316327AA2-057 GEN
Solar/Wind Harmer
0.289
3146263WOODLND
Solar/Wind Harmer
0.191
3146233WITAKRS
Solar/Wind Harmer
0.921
3146233WITAKRS
Solar/Wind Harmer
0.125
3138543CONSLDL
Solar/Wind Harmer
0.12
961601AG1-000A GEN
Solar/Wind Harmer
12.805
316317KELFORD C
Solar/Wind Harmer
0.017
3145823KELFORD
Solar/Wind Harmer
0.177
971623AH1-311 GEN
Solar/Wind Harmer
0.353
3145543BTLEBRO
Solar/Wind Harmer
0.175
3145543BTLEBRO
Solar/Wind Harmer
0.175
316463AE2-346 GEN
Solar/Wind Harmer
0.142
316140AB2-099
Solar/Wind Harmer
0.059
962331AG1-082 GEN
Solar/Wind Harmer
1.76
3146073TAR RVR
Solar/Wind Harmer
0.165
3146083TARBORO
Solar/Wind Harmer
0.165
3146173TUNIS
Solar/Wind Harmer
0.163
957521AF2-046 GEN
Solar/Wind Harmer
11.982
961681AG1-008 GEN
Solar/Wind Harmer
11.982
3145893MURPHYS
Solar/Wind Harmer
0.268
3145893MURPHYS
Solar/Wind Harmer
0.16
3156021HOLLOMANSOL
Solar/Wind Harmer
0.689
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3145933PARMELE
Solar/Wind Harmer
0.131
966801AG1-551 GEN
Solar/Wind Harmer
1.529
316131AB2-060 GEN
Solar/Wind Harmer
0.407
964241AG1-285 GEN
Solar/Wind Harmer
8.211
3146206CASHIE
Solar/Wind Harmer
0.122
3145963POPLR C
Solar/Wind Harmer
0.118
315785AD2-033 C
Solar/Wind Harmer
0.918
970257AG2-171 GEN
Solar/Wind Harmer
3.491
959311AF2-222 GEN
Solar/Wind Harmer
9.454
315737AD1-076 GEN
Solar/Wind Harmer
1.314
971157AH1-035 GEN
Solar/Wind Harmer
1.183
963181AG1-167 GEN
Solar/Wind Harmer
0.361
3147133PAMPLIN
Solar/Wind Harmer
0.263
971193AH1-056 GEN
Solar/Wind Harmer
5.112
315614AA2-178 GEN
Solar/Wind Harmer
0.458
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.273
316478AD1-087 GEN
Solar/Wind Harmer
0.254
316486AD2-202 GEN
Solar/Wind Harmer
0.075
971683AH1-343 GEN
Solar/Wind Harmer
2.513
942461AE2-259 GEN
Solar/Wind Harmer
0
316283AC2-100 C
Solar/Wind Harmer
0.113
970909AG2-566 GEN
Solar/Wind Harmer
0.605
315839AE2-212 C
Solar/Wind Helper
0.197
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3147043LAWRENC
50/50
3.141
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.27
3151581KERR 1
50/50
0.096
3144293JTRSVLE
50/50
0.305
3151531CLOVER1
50/50
1.558
316023GEN1_S
Solar/Wind Harmer
1.155
960081AF2-299 GEN
Solar/Wind Harmer
3.965
971795AH1-408 GEN
Solar/Wind Harmer
23.615
316011AB1-132 GEN
Solar/Wind Harmer
6.186
962571AG1-106 GEN
Solar/Wind Harmer
4.841
3145796HORNRTN
Solar/Wind Harmer
1.046
3145796HORNRTN
Solar/Wind Harmer
0.317
3145783HORNRTN
Solar/Wind Harmer
0.249
315722AD1-056 GEN
Solar/Wind Harmer
1.531
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
1.015
3146263WOODLND
Solar/Wind Harmer
0.191
3146233WITAKRS
Solar/Wind Harmer
0.73
3145823KELFORD
Solar/Wind Harmer
0.177
316359AB2-059 GEN
Solar/Wind Harmer
0.634
316049AB1-081 GEN
Solar/Wind Harmer
1.01
3142053HEARTS
Solar/Wind Harmer
0.311
3145543BTLEBRO
Solar/Wind Harmer
0.175
3145543BTLEBRO
Solar/Wind Harmer
0.14
316129AC1-054 GEN
Solar/Wind Harmer
0.656
971065AG2-659 GEN
Solar/Wind Harmer
7.13
3145683EARLEYS
Solar/Wind Harmer
0.166
961671AG1-007 GEN
Solar/Wind Harmer
0.025
3146083TARBORO
Solar/Wind Harmer
0.165
3145493TOT1
Solar/Wind Harmer
0.732
3146173TUNIS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
0.64
3145893MURPHYS
Solar/Wind Harmer
0.712
316494AC1-189 GEN
Solar/Wind Harmer
0.514
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3146293MARTNCO
Solar/Wind Harmer
0.122
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.122
971547AH1-271 GEN
Solar/Wind Harmer
2.614
316174AB2-169 GEN
Solar/Wind Harmer
0.003
3145963POPLR C
Solar/Wind Harmer
0.118
970685AG2-442 GEN
Solar/Wind Harmer
7.425
970401AG2-262 GEN
Solar/Wind Harmer
0.583
963171AG1-166 GEN
Solar/Wind Harmer
0.482
971563AH1-280 GEN
Solar/Wind Harmer
0.963
3145663CRESWEL
Solar/Wind Harmer
0.224
971163AH1-040 GEN
Solar/Wind Harmer
6.407
957481AF2-042 GEN
Solar/Wind Harmer
19.308
316003AC1-222 GEN
Solar/Wind Harmer
0.002
315693AD1-088 GEN
Solar/Wind Harmer
3.442
315687AD1-152 GEN
Solar/Wind Harmer
0.002
962491AG1-098 GEN
Solar/Wind Harmer
4.048
CPLELTFEXP_CPLE->PJM
CLTF
4.45
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.218
LAGNLTFEXP_LAGN->PJM
CLTF
2.678
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.707
TVALTFEXP_TVA->PJM
CLTF
1.336
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.85
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.587
MECLTFEXP_MEC->PJM
CLTF
1.327
SIGELTFEXP_SIGE->PJM
CLTF
0.04
NYPJM->LTFIMP_NY
CLTF
0.49
LGEELTFEXP_LGEE->PJM
CLTF
0.481
WECLTFEXP_WEC->PJM
CLTF
0.25

Details for 6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:140.59 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:954.15
MW Contribution:6.8
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3147043LAWRENC
50/50
3.141
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.27
3151581KERR 1
50/50
0.096
3144293JTRSVLE
50/50
0.305
3151531CLOVER1
50/50
1.558
316023GEN1_S
Solar/Wind Harmer
1.155
960081AF2-299 GEN
Solar/Wind Harmer
3.965
971795AH1-408 GEN
Solar/Wind Harmer
23.615
316011AB1-132 GEN
Solar/Wind Harmer
6.186
962571AG1-106 GEN
Solar/Wind Harmer
4.841
3145796HORNRTN
Solar/Wind Harmer
1.046
3145796HORNRTN
Solar/Wind Harmer
0.317
3145783HORNRTN
Solar/Wind Harmer
0.249
315722AD1-056 GEN
Solar/Wind Harmer
1.531
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
1.015
3146263WOODLND
Solar/Wind Harmer
0.191
3146233WITAKRS
Solar/Wind Harmer
0.73
3145823KELFORD
Solar/Wind Harmer
0.177
316359AB2-059 GEN
Solar/Wind Harmer
0.634
316049AB1-081 GEN
Solar/Wind Harmer
1.01
3142053HEARTS
Solar/Wind Harmer
0.311
3145543BTLEBRO
Solar/Wind Harmer
0.175
3145543BTLEBRO
Solar/Wind Harmer
0.14
316129AC1-054 GEN
Solar/Wind Harmer
0.656
971065AG2-659 GEN
Solar/Wind Harmer
7.13
3145683EARLEYS
Solar/Wind Harmer
0.166
961671AG1-007 GEN
Solar/Wind Harmer
0.025
3146083TARBORO
Solar/Wind Harmer
0.165
3145493TOT1
Solar/Wind Harmer
0.732
3146173TUNIS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
0.64
3145893MURPHYS
Solar/Wind Harmer
0.712
316494AC1-189 GEN
Solar/Wind Harmer
0.514
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3146293MARTNCO
Solar/Wind Harmer
0.122
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.122
971547AH1-271 GEN
Solar/Wind Harmer
2.614
316174AB2-169 GEN
Solar/Wind Harmer
0.003
3145963POPLR C
Solar/Wind Harmer
0.118
970685AG2-442 GEN
Solar/Wind Harmer
7.425
970401AG2-262 GEN
Solar/Wind Harmer
0.583
963171AG1-166 GEN
Solar/Wind Harmer
0.482
971563AH1-280 GEN
Solar/Wind Harmer
0.963
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.27
3151621KERR 5
50/50
0.27
3151631KERR 6
50/50
0.27
3151641KERR 7
50/50
0.27
3151151S HAMPT1
50/50
0.285
3151541CLOVER2
50/50
1.551
315814AE2-033 C
Solar/Wind Harmer
65.923
316087AB2-174 GEN
Solar/Wind Harmer
0.01
315652AC1-086 GEN
Solar/Wind Harmer
37.428
3145796HORNRTN
Solar/Wind Harmer
1.015
3145796HORNRTN
Solar/Wind Harmer
0.127
3137643SOCKMAN
Solar/Wind Harmer
1.176
315607AA1-063A GEN
Solar/Wind Harmer
0.444
3146043SEABORD
Solar/Wind Harmer
0.211
3146033SCOT NK
Solar/Wind Harmer
0.75
316319Z2-044 C
Solar/Wind Harmer
0
970831AG2-522 GEN
Solar/Wind Harmer
7.783
3145683EARLEYS
Solar/Wind Harmer
0.333
3145683EARLEYS
Solar/Wind Harmer
0.166
3145683EARLEYS
Solar/Wind Harmer
0.166
3145513AHOSKIE
Solar/Wind Harmer
0.345
3145513AHOSKIE
Solar/Wind Harmer
0.165
3145573BETHELC
Solar/Wind Harmer
0.165
3145573BETHELC
Solar/Wind Harmer
0.165
3145893MURPHYS
Solar/Wind Harmer
0.432
3145893MURPHYS
Solar/Wind Harmer
0.16
316420AA1-050 GEN
Solar/Wind Harmer
0.005
965291AG1-394 GEN
Solar/Wind Harmer
0.698
957861AF2-080 GEN
Solar/Wind Harmer
6.563
316005AA1-067
Solar/Wind Harmer
0.148
3145746EVERETS
Solar/Wind Harmer
0.548
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
970181AG2-120 GEN
Solar/Wind Harmer
1.713
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.122
970601AG2-382 GEN
Solar/Wind Harmer
4.575
971443AH1-215 GEN
Solar/Wind Harmer
1.848
3144303KENBRDG
Solar/Wind Harmer
0.087
315732AD1-074 GEN1
Solar/Wind Harmer
0.587
315733AD1-074 GEN2
Solar/Wind Harmer
0.587
315735AD1-075 GEN1
Solar/Wind Harmer
0.294
970683AG2-441 GEN
Solar/Wind Harmer
6.63
970681AG2-440 GEN
Solar/Wind Harmer
5.304
3130546PLYMOUTH
Solar/Wind Harmer
0.098
946301AF1-294 GEN
Solar/Wind Harmer
1.782
961791AG1-021 GEN
Solar/Wind Harmer
0.867
316118AC1-105 GEN
Solar/Wind Harmer
0.227
315657AE1-056 GEN
Solar/Wind Harmer
2.895
315816AE2-034 GEN
Solar/Wind Harmer
0.344
3147173SINAI
Solar/Wind Harmer
0.077
3147243WELCO
Solar/Wind Harmer
0.048
971967AH1-528 GEN
Solar/Wind Harmer
11.557
970865AG2-541 GEN
Solar/Wind Harmer
2.227
316315AB2-025 C
Solar/Wind Helper
0.826
3143316POE
Solar/Wind Helper
0.688
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3151261ROARAP2
50/50
0.313
3151591KERR 2
50/50
0.27
3144293JTRSVLE
50/50
0.305
970413AG2-270 GEN
50/50
6.801
316365GEN2_N
Solar/Wind Harmer
1.155
313506AB2-031 GEN
Solar/Wind Harmer
1.049
3147043LAWRENC
Solar/Wind Harmer
0.196
3145796HORNRTN
Solar/Wind Harmer
1.268
3145796HORNRTN
Solar/Wind Harmer
0.317
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
315724AD1-057 GEN
Solar/Wind Harmer
0.907
316210AC1-098 GEN
Solar/Wind Harmer
1.821
316327AA2-057 GEN
Solar/Wind Harmer
0.289
3146263WOODLND
Solar/Wind Harmer
0.191
3146233WITAKRS
Solar/Wind Harmer
0.921
3146233WITAKRS
Solar/Wind Harmer
0.125
3138543CONSLDL
Solar/Wind Harmer
0.12
961601AG1-000A GEN
Solar/Wind Harmer
12.805
316317KELFORD C
Solar/Wind Harmer
0.017
3145823KELFORD
Solar/Wind Harmer
0.177
971623AH1-311 GEN
Solar/Wind Harmer
0.353
3145543BTLEBRO
Solar/Wind Harmer
0.175
3145543BTLEBRO
Solar/Wind Harmer
0.175
316463AE2-346 GEN
Solar/Wind Harmer
0.142
316140AB2-099
Solar/Wind Harmer
0.059
962331AG1-082 GEN
Solar/Wind Harmer
1.76
3146073TAR RVR
Solar/Wind Harmer
0.165
3146083TARBORO
Solar/Wind Harmer
0.165
3146173TUNIS
Solar/Wind Harmer
0.163
957521AF2-046 GEN
Solar/Wind Harmer
11.982
961681AG1-008 GEN
Solar/Wind Harmer
11.982
3145893MURPHYS
Solar/Wind Harmer
0.268
3145893MURPHYS
Solar/Wind Harmer
0.16
3156021HOLLOMANSOL
Solar/Wind Harmer
0.689
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3145933PARMELE
Solar/Wind Harmer
0.131
966801AG1-551 GEN
Solar/Wind Harmer
1.529
316131AB2-060 GEN
Solar/Wind Harmer
0.407
964241AG1-285 GEN
Solar/Wind Harmer
8.211
3146206CASHIE
Solar/Wind Harmer
0.122
3145963POPLR C
Solar/Wind Harmer
0.118
315785AD2-033 C
Solar/Wind Harmer
0.918
970257AG2-171 GEN
Solar/Wind Harmer
3.491
959311AF2-222 GEN
Solar/Wind Harmer
9.454
315737AD1-076 GEN
Solar/Wind Harmer
1.314
971157AH1-035 GEN
Solar/Wind Harmer
1.183
963181AG1-167 GEN
Solar/Wind Harmer
0.361
3147133PAMPLIN
Solar/Wind Harmer
0.263
971193AH1-056 GEN
Solar/Wind Harmer
5.112
315614AA2-178 GEN
Solar/Wind Harmer
0.458
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.273
316478AD1-087 GEN
Solar/Wind Harmer
0.254
316486AD2-202 GEN
Solar/Wind Harmer
0.075
971683AH1-343 GEN
Solar/Wind Harmer
2.513
942461AE2-259 GEN
Solar/Wind Harmer
0
316283AC2-100 C
Solar/Wind Harmer
0.113
970909AG2-566 GEN
Solar/Wind Harmer
0.605
315839AE2-212 C
Solar/Wind Helper
0.197
3145663CRESWEL
Solar/Wind Harmer
0.224
971163AH1-040 GEN
Solar/Wind Harmer
6.407
957481AF2-042 GEN
Solar/Wind Harmer
19.308
316003AC1-222 GEN
Solar/Wind Harmer
0.002
315693AD1-088 GEN
Solar/Wind Harmer
3.442
315687AD1-152 GEN
Solar/Wind Harmer
0.002
962491AG1-098 GEN
Solar/Wind Harmer
4.048
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.321
3144293JTRSVLE
50/50
0.305
3144293JTRSVLE
50/50
0.257
3152661PLYWOOD A
50/50
0.195
316181AB2-040 GEN
Solar/Wind Harmer
0.492
3145796HORNRTN
Solar/Wind Harmer
0.951
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3145593CAROLNA
Solar/Wind Harmer
0.257
3145593CAROLNA
Solar/Wind Harmer
0.257
966811AG1-552 GEN
Solar/Wind Harmer
2.785
3145593CAROLNA
Solar/Wind Harmer
0.32
3145783HORNRTN
Solar/Wind Harmer
4.428
3145783HORNRTN
Solar/Wind Harmer
3.543
3145783HORNRTN
Solar/Wind Harmer
1.107
3145783HORNRTN
Solar/Wind Harmer
0.443
316426AA2-053 GEN
Solar/Wind Harmer
0.813
316274AC1-208 GEN
Solar/Wind Harmer
1.081
961601AG1-000A GEN
Solar/Wind Harmer
3.201
316263AC1-034 GEN
Solar/Wind Harmer
6.707
3145493TOT1
Solar/Wind Harmer
0.382
3145453TOT5
Solar/Wind Harmer
0.229
3145603CNETO
Solar/Wind Harmer
0.153
3146173TUNIS
Solar/Wind Harmer
0.163
3146173TUNIS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
1.071
3145893MURPHYS
Solar/Wind Harmer
0.288
3145933PARMELE
Solar/Wind Harmer
0.262
3145933PARMELE
Solar/Wind Harmer
0.131
313527AB2-043 GEN
Solar/Wind Harmer
0.002
939181AE1-148 GEN
Solar/Wind Harmer
6.26
316065AD1-022 GEN
Solar/Wind Harmer
5.298
970323AG2-213 GEN
Solar/Wind Harmer
4.655
971775AH1-396 GEN
Solar/Wind Harmer
0.175
316034AC1-036 C
Solar/Wind Harmer
0.008
962561AG1-105 GEN
Solar/Wind Harmer
5
964791AG1-342 GEN
Solar/Wind Harmer
1.908
3146843MT LREL
Solar/Wind Harmer
0.099
3146843MT LREL
Solar/Wind Harmer
0.099
958211AF2-115 GEN
Solar/Wind Harmer
1.083
963191AG1-168 GEN
Solar/Wind Harmer
0.361
3147133PAMPLIN
Solar/Wind Harmer
0.084
3147133PAMPLIN
Solar/Wind Harmer
0.067
970099AG2-077 GEN
Solar/Wind Harmer
7.723
970933AG2-581 GEN
Solar/Wind Harmer
5.779
315742AE1-103 GEN
Solar/Wind Harmer
0.001
971741AH1-377 GEN
Solar/Wind Harmer
5.969
316222AC1-221 GEN
Solar/Wind Harmer
0.242
970301AG2-198 GEN
Solar/Wind Harmer
2.421
3144356SAPONY
Solar/Wind Helper
0.972
316240AF1-291 C
Solar/Wind Helper
0.168
CPLELTFEXP_CPLE->PJM
CLTF
4.45
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.218
LAGNLTFEXP_LAGN->PJM
CLTF
2.678
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.707
TVALTFEXP_TVA->PJM
CLTF
1.336
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.85
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.587
MECLTFEXP_MEC->PJM
CLTF
1.327
SIGELTFEXP_SIGE->PJM
CLTF
0.04
NYPJM->LTFIMP_NY
CLTF
0.49
LGEELTFEXP_LGEE->PJM
CLTF
0.481
WECLTFEXP_WEC->PJM
CLTF
0.25

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:201.24 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1376.51
MW Contribution:29.97
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.835
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
315657AE1-056 GEN
Solar/Wind Harmer
20.241
946301AF1-294 GEN
Solar/Wind Harmer
13.094
961791AG1-021 GEN
Solar/Wind Harmer
6.387
970683AG2-441 GEN
Solar/Wind Harmer
36.695
970681AG2-440 GEN
Solar/Wind Harmer
29.356
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.31
971967AH1-528 GEN
Solar/Wind Harmer
73.321
316239AB2-077_GEN
Solar/Wind Harmer
0.97
316238AB2-078_GEN
Solar/Wind Harmer
0.97
316118AC1-105 GEN
Solar/Wind Harmer
1.807
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.03
970831AG2-522 GEN
Solar/Wind Harmer
9.822
316123AC1-075 GEN
Solar/Wind Harmer
1.789
970165AG2-112 GEN
Solar/Wind Harmer
1.575
970163AG2-111 GEN
Solar/Wind Harmer
1.503
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.493
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.635
270457AD2-023 GEN
Solar/Wind Harmer
0.829
315607AA1-063A GEN
Solar/Wind Harmer
0.882
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.411
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
3144293JTRSVLE
50/50
1.536
3151531CLOVER1
50/50
6.868
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.479
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.387
971563AH1-280 GEN
Solar/Wind Harmer
6.387
970685AG2-442 GEN
Solar/Wind Harmer
41.098
962491AG1-098 GEN
Solar/Wind Harmer
28.527
315693AD1-088 GEN
Solar/Wind Harmer
20.89
957481AF2-042 GEN
Solar/Wind Harmer
119.73
316237AB2-079_GEN
Solar/Wind Harmer
0.97
315687AD1-152 GEN
Solar/Wind Harmer
3.722
970401AG2-262 GEN
Solar/Wind Harmer
1.828
316003AC1-222 GEN
Solar/Wind Harmer
2.23
971065AG2-659 GEN
Solar/Wind Harmer
10.784
316129AC1-054 GEN
Solar/Wind Harmer
1.809
971795AH1-408 GEN
Solar/Wind Harmer
11.382
960081AF2-299 GEN
Solar/Wind Harmer
1.187
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.663
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3144293JTRSVLE
50/50
1.536
3144293JTRSVLE
50/50
1.294
970535AG2-341 GEN
50/50
4.631
3152661PLYWOOD A
50/50
0.509
970301AG2-198 GEN
Solar/Wind Harmer
29.375
971741AH1-377 GEN
Solar/Wind Harmer
63.77
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.984
963191AG1-168 GEN
Solar/Wind Harmer
4.79
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.293
971775AH1-396 GEN
Solar/Wind Harmer
3.032
970933AG2-581 GEN
Solar/Wind Harmer
36.564
970099AG2-077 GEN
Solar/Wind Harmer
47.892
313527AB2-043 GEN
Solar/Wind Harmer
5.323
962561AG1-105 GEN
Solar/Wind Harmer
16.163
964791AG1-342 GEN
Solar/Wind Harmer
5.983
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.395
942751AE2-291 GEN
Solar/Wind Harmer
9.282
316222AC1-221 GEN
Solar/Wind Harmer
1.431
316181AB2-040 GEN
Solar/Wind Harmer
1.454
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.157
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.182
3145783HORNRTN
Solar/Wind Harmer
0.946
3145783HORNRTN
Solar/Wind Harmer
0.296
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.956
316274AC1-208 GEN
Solar/Wind Harmer
0.891
316263AC1-034 GEN
Solar/Wind Harmer
3.354
961601AG1-000A GEN
Solar/Wind Harmer
2.733
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.045
316197AC1-042 GEN
Solar/Wind Harmer
0.792
942671AE2-283 GEN
Solar/Wind Harmer
2.132
316359AB2-059 GEN
Solar/Wind Harmer
0.965
316049AB1-081 GEN
Solar/Wind Harmer
0.772
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.715
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
970223AG2-152 GEN
Solar/Wind Harmer
5.79
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.192
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.414
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.314
3144293JTRSVLE
50/50
1.536
970413AG2-270 GEN
50/50
29.97
3151591KERR 2
50/50
0.482
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.339
970909AG2-566 GEN
Solar/Wind Harmer
5.578
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.735
963181AG1-167 GEN
Solar/Wind Harmer
4.79
959311AF2-222 GEN
Solar/Wind Harmer
45.765
970257AG2-171 GEN
Solar/Wind Harmer
15.97
315785AD2-033 C
Solar/Wind Harmer
9.259
964241AG1-285 GEN
Solar/Wind Harmer
28.316
316478AD1-087 GEN
Solar/Wind Harmer
3.115
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.609
316248AF1-058 C
Solar/Wind Harmer
0.741
960061AF2-297 GEN
Solar/Wind Harmer
12.289
971683AH1-343 GEN
Solar/Wind Harmer
9.199
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.303
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.775
316210AC1-098 GEN
Solar/Wind Harmer
1.194
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.767
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.393
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.414
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.317
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
965291AG1-394 GEN
Solar/Wind Harmer
0.563
270494AE1-108_GEN
Solar/Wind Helper
3.665
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.531
CPLELTFEXP_CPLE->PJM
CLTF
5.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.616
LAGNLTFEXP_LAGN->PJM
CLTF
3.212
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.896
TVALTFEXP_TVA->PJM
CLTF
1.599
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.51
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.435
MECLTFEXP_MEC->PJM
CLTF
1.488
SIGELTFEXP_SIGE->PJM
CLTF
0.044
NYPJM->LTFIMP_NY
CLTF
0.52
LGEELTFEXP_LGEE->PJM
CLTF
0.521
WECLTFEXP_WEC->PJM
CLTF
0.271

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:201.19 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1376.13
MW Contribution:29.97
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.536
970413AG2-270 GEN
50/50
29.97
3151541CLOVER2
50/50
6.835
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
315657AE1-056 GEN
Solar/Wind Harmer
20.241
946301AF1-294 GEN
Solar/Wind Harmer
13.094
961791AG1-021 GEN
Solar/Wind Harmer
6.387
970683AG2-441 GEN
Solar/Wind Harmer
36.695
970681AG2-440 GEN
Solar/Wind Harmer
29.356
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.31
971967AH1-528 GEN
Solar/Wind Harmer
73.321
316239AB2-077_GEN
Solar/Wind Harmer
0.97
316238AB2-078_GEN
Solar/Wind Harmer
0.97
316118AC1-105 GEN
Solar/Wind Harmer
1.807
3147173SINAI
Solar/Wind Harmer
-0.025
3144293JTRSVLE
50/50
1.536
3151531CLOVER1
50/50
6.868
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.479
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.387
3144293JTRSVLE
50/50
1.536
3144293JTRSVLE
50/50
1.294
970535AG2-341 GEN
50/50
4.631
3151591KERR 2
50/50
0.482
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.339
970909AG2-566 GEN
Solar/Wind Harmer
5.578
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.735
963181AG1-167 GEN
Solar/Wind Harmer
4.79
959311AF2-222 GEN
Solar/Wind Harmer
45.765
970257AG2-171 GEN
Solar/Wind Harmer
15.97
315785AD2-033 C
Solar/Wind Harmer
9.259
964241AG1-285 GEN
Solar/Wind Harmer
28.316
316478AD1-087 GEN
Solar/Wind Harmer
3.115
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.609
316248AF1-058 C
Solar/Wind Harmer
0.741
960061AF2-297 GEN
Solar/Wind Harmer
12.289
971683AH1-343 GEN
Solar/Wind Harmer
9.199
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.303
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.775
316210AC1-098 GEN
Solar/Wind Harmer
1.194
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.767
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.393
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.414
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.317
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.03
970831AG2-522 GEN
Solar/Wind Harmer
9.822
316123AC1-075 GEN
Solar/Wind Harmer
1.789
970165AG2-112 GEN
Solar/Wind Harmer
1.575
970163AG2-111 GEN
Solar/Wind Harmer
1.503
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.493
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.635
270457AD2-023 GEN
Solar/Wind Harmer
0.829
315607AA1-063A GEN
Solar/Wind Harmer
0.882
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.411
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.563
270494AE1-108_GEN
Solar/Wind Helper
3.665
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
971563AH1-280 GEN
Solar/Wind Harmer
6.387
970685AG2-442 GEN
Solar/Wind Harmer
41.098
962491AG1-098 GEN
Solar/Wind Harmer
28.527
315693AD1-088 GEN
Solar/Wind Harmer
20.89
957481AF2-042 GEN
Solar/Wind Harmer
119.73
316237AB2-079_GEN
Solar/Wind Harmer
0.97
315687AD1-152 GEN
Solar/Wind Harmer
3.722
970401AG2-262 GEN
Solar/Wind Harmer
1.828
316003AC1-222 GEN
Solar/Wind Harmer
2.23
971065AG2-659 GEN
Solar/Wind Harmer
10.784
316129AC1-054 GEN
Solar/Wind Harmer
1.809
971795AH1-408 GEN
Solar/Wind Harmer
11.382
960081AF2-299 GEN
Solar/Wind Harmer
1.187
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.663
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.965
316049AB1-081 GEN
Solar/Wind Harmer
0.772
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.715
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
970223AG2-152 GEN
Solar/Wind Harmer
5.79
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.192
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.414
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.314
3152661PLYWOOD A
50/50
0.509
970301AG2-198 GEN
Solar/Wind Harmer
29.375
971741AH1-377 GEN
Solar/Wind Harmer
63.77
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.984
963191AG1-168 GEN
Solar/Wind Harmer
4.79
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.293
971775AH1-396 GEN
Solar/Wind Harmer
3.032
970933AG2-581 GEN
Solar/Wind Harmer
36.564
970099AG2-077 GEN
Solar/Wind Harmer
47.892
313527AB2-043 GEN
Solar/Wind Harmer
5.323
962561AG1-105 GEN
Solar/Wind Harmer
16.163
964791AG1-342 GEN
Solar/Wind Harmer
5.983
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.395
942751AE2-291 GEN
Solar/Wind Harmer
9.282
316222AC1-221 GEN
Solar/Wind Harmer
1.431
316181AB2-040 GEN
Solar/Wind Harmer
1.454
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.157
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.182
3145783HORNRTN
Solar/Wind Harmer
0.946
3145783HORNRTN
Solar/Wind Harmer
0.296
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.956
316274AC1-208 GEN
Solar/Wind Harmer
0.891
316263AC1-034 GEN
Solar/Wind Harmer
3.354
961601AG1-000A GEN
Solar/Wind Harmer
2.733
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.045
316197AC1-042 GEN
Solar/Wind Harmer
0.792
942671AE2-283 GEN
Solar/Wind Harmer
2.132
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.531
CPLELTFEXP_CPLE->PJM
CLTF
5.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.616
LAGNLTFEXP_LAGN->PJM
CLTF
3.212
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.896
TVALTFEXP_TVA->PJM
CLTF
1.599
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.51
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.435
MECLTFEXP_MEC->PJM
CLTF
1.488
SIGELTFEXP_SIGE->PJM
CLTF
0.044
NYPJM->LTFIMP_NY
CLTF
0.52
LGEELTFEXP_LGEE->PJM
CLTF
0.521
WECLTFEXP_WEC->PJM
CLTF
0.271

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:197.56 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1351.34
MW Contribution:29.9
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
971967AH1-528 GEN
Solar/Wind Harmer
73.183
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970933AG2-581 GEN
Solar/Wind Harmer
36.495
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:195.93 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:1095.86
MW Contribution:29.9
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.97
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
963171AG1-166 GEN
Solar/Wind Harmer
2.424
971563AH1-280 GEN
Solar/Wind Harmer
4.847
970685AG2-442 GEN
Solar/Wind Harmer
31.186
962491AG1-098 GEN
Solar/Wind Harmer
21.632
315693AD1-088 GEN
Solar/Wind Harmer
17.82
957481AF2-042 GEN
Solar/Wind Harmer
90.757
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.458
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.171
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
9.004
960081AF2-299 GEN
Solar/Wind Harmer
0.903
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.349
3146233WITAKRS
Solar/Wind Harmer
0.261
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.051
316359AB2-059 GEN
Solar/Wind Harmer
0.226
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.062
315722AD1-056 GEN
Solar/Wind Harmer
0.382
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.213
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.1
970301AG2-198 GEN
Solar/Wind Harmer
22.295
971741AH1-377 GEN
Solar/Wind Harmer
48.392
3147133PAMPLIN
Solar/Wind Harmer
0.48
3147133PAMPLIN
Solar/Wind Harmer
0.384
958211AF2-115 GEN
Solar/Wind Harmer
5.453
963191AG1-168 GEN
Solar/Wind Harmer
1.818
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.154
971775AH1-396 GEN
Solar/Wind Harmer
0.606
970933AG2-581 GEN
Solar/Wind Harmer
27.718
970099AG2-077 GEN
Solar/Wind Harmer
36.303
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.244
964791AG1-342 GEN
Solar/Wind Harmer
4.773
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.665
942751AE2-291 GEN
Solar/Wind Harmer
7.016
316222AC1-221 GEN
Solar/Wind Harmer
0.517
316181AB2-040 GEN
Solar/Wind Harmer
0.135
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.992
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.575
3145783HORNRTN
Solar/Wind Harmer
1.26
3145783HORNRTN
Solar/Wind Harmer
0.394
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.38
316263AC1-034 GEN
Solar/Wind Harmer
2.393
961601AG1-000A GEN
Solar/Wind Harmer
1.088
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.132
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.414
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
3145796HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.068
962571AG1-106 GEN
Solar/Wind Harmer
0.836
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.253
970223AG2-152 GEN
Solar/Wind Harmer
3.997
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.043
941801AE2-185 GEN
Solar/Wind Harmer
1.818
3145823KELFORD
Solar/Wind Harmer
0.056
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.232
963181AG1-167 GEN
Solar/Wind Harmer
1.818
959311AF2-222 GEN
Solar/Wind Harmer
34.653
970257AG2-171 GEN
Solar/Wind Harmer
12.116
315785AD2-033 C
Solar/Wind Harmer
2.953
964241AG1-285 GEN
Solar/Wind Harmer
21.475
316478AD1-087 GEN
Solar/Wind Harmer
1.115
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.935
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.299
971683AH1-343 GEN
Solar/Wind Harmer
6.959
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.287
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.626
3146233WITAKRS
Solar/Wind Harmer
0.329
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.062
961601AG1-000A GEN
Solar/Wind Harmer
4.35
315724AD1-057 GEN
Solar/Wind Harmer
0.227
3145796HORNRTN
Solar/Wind Harmer
0.236
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.104
315657AE1-056 GEN
Solar/Wind Harmer
16.558
946301AF1-294 GEN
Solar/Wind Harmer
8.968
961791AG1-021 GEN
Solar/Wind Harmer
4.363
970683AG2-441 GEN
Solar/Wind Harmer
27.844
970681AG2-440 GEN
Solar/Wind Harmer
22.275
3144303KENBRDG
Solar/Wind Harmer
0.303
971443AH1-215 GEN
Solar/Wind Harmer
6.304
971967AH1-528 GEN
Solar/Wind Harmer
55.434
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.602
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.073
970831AG2-522 GEN
Solar/Wind Harmer
7.443
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.191
970163AG2-111 GEN
Solar/Wind Harmer
1.136
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.368
315607AA1-063A GEN
Solar/Wind Harmer
0.159
3146043SEABORD
Solar/Wind Harmer
0.076
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.25
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.462
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.252
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.818
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:193.37 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:1081.51
MW Contribution:29.9
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.232
963181AG1-167 GEN
Solar/Wind Harmer
1.818
959311AF2-222 GEN
Solar/Wind Harmer
34.653
970257AG2-171 GEN
Solar/Wind Harmer
12.116
315785AD2-033 C
Solar/Wind Harmer
2.953
964241AG1-285 GEN
Solar/Wind Harmer
21.475
316478AD1-087 GEN
Solar/Wind Harmer
1.115
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.935
316248AF1-058 C
Solar/Wind Harmer
0.002
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.213
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.1
970301AG2-198 GEN
Solar/Wind Harmer
22.295
971741AH1-377 GEN
Solar/Wind Harmer
48.392
3147133PAMPLIN
Solar/Wind Harmer
0.48
3147133PAMPLIN
Solar/Wind Harmer
0.384
958211AF2-115 GEN
Solar/Wind Harmer
5.453
963191AG1-168 GEN
Solar/Wind Harmer
1.818
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.154
971775AH1-396 GEN
Solar/Wind Harmer
0.606
970099AG2-077 GEN
Solar/Wind Harmer
36.303
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.244
964791AG1-342 GEN
Solar/Wind Harmer
4.773
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.665
942751AE2-291 GEN
Solar/Wind Harmer
7.016
316222AC1-221 GEN
Solar/Wind Harmer
0.517
316181AB2-040 GEN
Solar/Wind Harmer
0.135
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.992
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.575
3145783HORNRTN
Solar/Wind Harmer
1.26
3145783HORNRTN
Solar/Wind Harmer
0.394
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.38
316263AC1-034 GEN
Solar/Wind Harmer
2.393
961601AG1-000A GEN
Solar/Wind Harmer
1.088
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.132
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.414
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.97
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
963171AG1-166 GEN
Solar/Wind Harmer
2.424
971563AH1-280 GEN
Solar/Wind Harmer
4.847
970685AG2-442 GEN
Solar/Wind Harmer
31.186
962491AG1-098 GEN
Solar/Wind Harmer
21.632
315693AD1-088 GEN
Solar/Wind Harmer
17.82
957481AF2-042 GEN
Solar/Wind Harmer
90.757
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.458
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.171
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
9.004
960081AF2-299 GEN
Solar/Wind Harmer
0.903
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.349
3146233WITAKRS
Solar/Wind Harmer
0.261
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.051
316359AB2-059 GEN
Solar/Wind Harmer
0.226
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.062
315722AD1-056 GEN
Solar/Wind Harmer
0.382
3145796HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.068
962571AG1-106 GEN
Solar/Wind Harmer
0.836
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.253
970223AG2-152 GEN
Solar/Wind Harmer
3.997
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.043
941801AE2-185 GEN
Solar/Wind Harmer
1.818
3145823KELFORD
Solar/Wind Harmer
0.056
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
960061AF2-297 GEN
Solar/Wind Harmer
9.299
971683AH1-343 GEN
Solar/Wind Harmer
6.959
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.287
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.626
3146233WITAKRS
Solar/Wind Harmer
0.329
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.062
961601AG1-000A GEN
Solar/Wind Harmer
4.35
315724AD1-057 GEN
Solar/Wind Harmer
0.227
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.818
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.104
315657AE1-056 GEN
Solar/Wind Harmer
16.558
946301AF1-294 GEN
Solar/Wind Harmer
8.968
961791AG1-021 GEN
Solar/Wind Harmer
4.363
970683AG2-441 GEN
Solar/Wind Harmer
27.844
970681AG2-440 GEN
Solar/Wind Harmer
22.275
3144303KENBRDG
Solar/Wind Harmer
0.303
971443AH1-215 GEN
Solar/Wind Harmer
6.304
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.602
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.073
970831AG2-522 GEN
Solar/Wind Harmer
7.443
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.191
970163AG2-111 GEN
Solar/Wind Harmer
1.136
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.368
315607AA1-063A GEN
Solar/Wind Harmer
0.159
3146043SEABORD
Solar/Wind Harmer
0.076
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.25
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.462
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.252
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:191.54 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1310.12
MW Contribution:29.9
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:191.54 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1310.12
MW Contribution:29.9
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2106-2111_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2106-2111_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:119.01 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:814.05
MW Contribution:12.4
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.18
3151601KERR 3
50/50
0.277
3151581KERR 1
50/50
0.099
3151531CLOVER1
50/50
2.843
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.907
971563AH1-280 GEN
Solar/Wind Harmer
4.907
970685AG2-442 GEN
Solar/Wind Harmer
30.788
962491AG1-098 GEN
Solar/Wind Harmer
14.151
316237AB2-079_GEN
Solar/Wind Harmer
0.621
315693AD1-088 GEN
Solar/Wind Harmer
9.998
970401AG2-262 GEN
Solar/Wind Harmer
1.046
957481AF2-042 GEN
Solar/Wind Harmer
45.244
315687AD1-152 GEN
Solar/Wind Harmer
1.611
971065AG2-659 GEN
Solar/Wind Harmer
6.471
316129AC1-054 GEN
Solar/Wind Harmer
1.098
3147043LAWRENC
Adder
0.994
316003AC1-222 GEN
Solar/Wind Harmer
1.108
971795AH1-408 GEN
Solar/Wind Harmer
8.341
960081AF2-299 GEN
Solar/Wind Harmer
0.953
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.091
316212AC1-099_GEN
Solar/Wind Harmer
0.553
316322AB2-045
Solar/Wind Helper
0.97
3146776BUCKING
Solar/Wind Helper
0.348
316336AC2-165 C
Solar/Wind Helper
1.454
3151611KERR 4
50/50
0.277
3151621KERR 5
50/50
0.277
3151631KERR 6
50/50
0.277
3151641KERR 7
50/50
0.277
3151541CLOVER2
50/50
2.829
315657AE1-056 GEN
Solar/Wind Harmer
15.784
946301AF1-294 GEN
Solar/Wind Harmer
10.059
961791AG1-021 GEN
Solar/Wind Harmer
4.907
970683AG2-441 GEN
Solar/Wind Harmer
27.489
970681AG2-440 GEN
Solar/Wind Harmer
21.992
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.004
316239AB2-077_GEN
Solar/Wind Harmer
0.621
316238AB2-078_GEN
Solar/Wind Harmer
0.621
316118AC1-105 GEN
Solar/Wind Harmer
0.972
3147173SINAI
Solar/Wind Harmer
-0.012
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.033
970865AG2-541 GEN
Solar/Wind Harmer
3.923
946281AF1-292 GEN
Solar/Wind Harmer
0.19
316087AB2-174 GEN
Solar/Wind Harmer
1.178
3137643SOCKMAN
Solar/Wind Harmer
-0.032
316123AC1-075 GEN
Solar/Wind Harmer
0.853
970165AG2-112 GEN
Solar/Wind Harmer
0.751
970163AG2-111 GEN
Solar/Wind Harmer
0.717
971967AH1-528 GEN
Solar/Wind Harmer
14.188
315607AA1-063A GEN
Solar/Wind Harmer
0.715
3146043SEABORD
Solar/Wind Harmer
-0.007
270494AE1-108_GEN
Solar/Wind Helper
4.499
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3144293JTRSVLE
50/50
1.18
3144293JTRSVLE
50/50
0.994
970535AG2-341 GEN
50/50
2.836
3152661PLYWOOD A
50/50
0.267
970301AG2-198 GEN
Solar/Wind Harmer
21.257
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.133
963191AG1-168 GEN
Solar/Wind Harmer
3.68
971741AH1-377 GEN
Solar/Wind Harmer
43.417
316034AC1-036 C
Solar/Wind Harmer
0.574
970323AG2-213 GEN
Solar/Wind Harmer
15.434
971775AH1-396 GEN
Solar/Wind Harmer
2.198
313527AB2-043 GEN
Solar/Wind Harmer
3.442
962561AG1-105 GEN
Solar/Wind Harmer
9.457
939181AE1-148 GEN
Solar/Wind Harmer
9.083
964791AG1-342 GEN
Solar/Wind Harmer
3.423
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.098
970933AG2-581 GEN
Solar/Wind Harmer
9.079
316181AB2-040 GEN
Solar/Wind Harmer
1.138
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.878
3145593CAROLNA
Solar/Wind Harmer
0.065
3145783HORNRTN
Solar/Wind Harmer
0.905
3145783HORNRTN
Solar/Wind Harmer
0.724
3145783HORNRTN
Solar/Wind Harmer
0.226
3145783HORNRTN
Solar/Wind Harmer
0.09
316222AC1-221 GEN
Solar/Wind Harmer
0.769
316426AA2-053 GEN
Solar/Wind Harmer
0.748
942751AE2-291 GEN
Solar/Wind Harmer
4.333
316274AC1-208 GEN
Solar/Wind Harmer
0.717
972187AH1-678 GEN
Adder
1.63
3146776BUCKING
Solar/Wind Helper
3.482
3146776BUCKING
Solar/Wind Helper
0.282
315821AE2-092 GEN
Solar/Wind Helper
2.994
3144293JTRSVLE
50/50
1.18
3151591KERR 2
50/50
0.277
970413AG2-270 GEN
50/50
12.405
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.535
970909AG2-566 GEN
Solar/Wind Harmer
4.036
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.307
963181AG1-167 GEN
Solar/Wind Harmer
3.68
959311AF2-222 GEN
Solar/Wind Harmer
33.514
970257AG2-171 GEN
Solar/Wind Harmer
11.575
315785AD2-033 C
Solar/Wind Harmer
6.609
964241AG1-285 GEN
Solar/Wind Harmer
19.233
316131AB2-060 GEN
Solar/Wind Harmer
2.359
316478AD1-087 GEN
Solar/Wind Harmer
1.29
316486AD2-202 GEN
Solar/Wind Harmer
0.378
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.371
960061AF2-297 GEN
Solar/Wind Harmer
6.151
971683AH1-343 GEN
Solar/Wind Harmer
4.535
966621AG1-532 GEN
Solar/Wind Harmer
0.172
313506AB2-031 GEN
Solar/Wind Harmer
0.656
316283AC2-100 C
Solar/Wind Harmer
0.705
316210AC1-098 GEN
Solar/Wind Harmer
0.995
3146776BUCKING
Solar/Wind Helper
0.313
316313AB2-026
Solar/Wind Helper
0.341
316258AE1-075 C
Solar/Wind Helper
0.306
316405AF2-144 C
Solar/Wind Helper
0.255
3148013FISHERV
Solar/Wind Helper
0.125
CPLELTFEXP_CPLE->PJM
CLTF
3.717
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.651
LAGNLTFEXP_LAGN->PJM
CLTF
1.842
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.457
TVALTFEXP_TVA->PJM
CLTF
0.904
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.19
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.966
MECLTFEXP_MEC->PJM
CLTF
0.645
SIGELTFEXP_SIGE->PJM
CLTF
0.018
NYPJM->LTFIMP_NY
CLTF
0.34
LGEELTFEXP_LGEE->PJM
CLTF
0.186
WECLTFEXP_WEC->PJM
CLTF
0.097

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:118.81 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:812.65
MW Contribution:12.9
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.195
3151591KERR 2
50/50
0.289
970413AG2-270 GEN
50/50
12.897
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.604
970909AG2-566 GEN
Solar/Wind Harmer
4.081
3147133PAMPLIN
Solar/Wind Harmer
-0.133
971193AH1-056 GEN
Solar/Wind Harmer
26.615
963181AG1-167 GEN
Solar/Wind Harmer
3.727
959311AF2-222 GEN
Solar/Wind Harmer
34.076
970257AG2-171 GEN
Solar/Wind Harmer
11.779
315785AD2-033 C
Solar/Wind Harmer
6.734
964241AG1-285 GEN
Solar/Wind Harmer
19.68
316131AB2-060 GEN
Solar/Wind Harmer
2.422
316478AD1-087 GEN
Solar/Wind Harmer
1.342
316486AD2-202 GEN
Solar/Wind Harmer
0.393
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.389
3151611KERR 4
50/50
0.289
3151621KERR 5
50/50
0.289
3151631KERR 6
50/50
0.289
3151641KERR 7
50/50
0.289
3151541CLOVER2
50/50
2.941
315657AE1-056 GEN
Solar/Wind Harmer
15.969
946301AF1-294 GEN
Solar/Wind Harmer
10.188
961791AG1-021 GEN
Solar/Wind Harmer
4.97
970683AG2-441 GEN
Solar/Wind Harmer
27.899
970681AG2-440 GEN
Solar/Wind Harmer
22.32
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.111
316239AB2-077_GEN
Solar/Wind Harmer
0.639
316238AB2-078_GEN
Solar/Wind Harmer
0.639
316118AC1-105 GEN
Solar/Wind Harmer
1.014
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.355
970865AG2-541 GEN
Solar/Wind Harmer
4.115
946281AF1-292 GEN
Solar/Wind Harmer
0.203
316087AB2-174 GEN
Solar/Wind Harmer
1.265
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.894
970165AG2-112 GEN
Solar/Wind Harmer
0.787
970163AG2-111 GEN
Solar/Wind Harmer
0.751
971967AH1-528 GEN
Solar/Wind Harmer
15.203
315607AA1-063A GEN
Solar/Wind Harmer
0.778
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.327
970581AG2-369 GEN
Solar/Wind Harmer
3.722
316319Z2-044 C
Solar/Wind Harmer
0.378
3146033SCOT NK
Solar/Wind Harmer
-0.027
315652AC1-086 GEN
Solar/Wind Harmer
7.562
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
965291AG1-394 GEN
Solar/Wind Harmer
0.582
970673AG2-436 GEN
Solar/Wind Harmer
13.618
970673AG2-436 GEN
Solar/Wind Harmer
6.895
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
270494AE1-108_GEN
Solar/Wind Helper
4.464
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
960061AF2-297 GEN
Solar/Wind Harmer
6.458
971683AH1-343 GEN
Solar/Wind Harmer
4.759
966621AG1-532 GEN
Solar/Wind Harmer
0.184
313506AB2-031 GEN
Solar/Wind Harmer
0.706
316283AC2-100 C
Solar/Wind Harmer
0.787
316210AC1-098 GEN
Solar/Wind Harmer
1.105
316327AA2-057 GEN
Solar/Wind Harmer
0.707
970917AG2-570 GEN
Solar/Wind Harmer
17.327
3146233WITAKRS
Solar/Wind Harmer
0.143
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.004
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.382
316365GEN2_N
Solar/Wind Harmer
0.443
961601AG1-000A GEN
Solar/Wind Harmer
2.615
316317KELFORD C
Solar/Wind Harmer
0.306
3145823KELFORD
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.09
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
957521AF2-046 GEN
Solar/Wind Harmer
5.039
961681AG1-008 GEN
Solar/Wind Harmer
5.039
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.311
316313AB2-026
Solar/Wind Helper
0.332
316258AE1-075 C
Solar/Wind Helper
0.299
316405AF2-144 C
Solar/Wind Helper
0.249
3148013FISHERV
Solar/Wind Helper
0.123
3144293JTRSVLE
50/50
1.195
3144293JTRSVLE
50/50
1.007
970535AG2-341 GEN
50/50
2.934
3152661PLYWOOD A
50/50
0.28
970301AG2-198 GEN
Solar/Wind Harmer
21.495
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.212
963191AG1-168 GEN
Solar/Wind Harmer
3.727
971741AH1-377 GEN
Solar/Wind Harmer
43.991
316034AC1-036 C
Solar/Wind Harmer
0.584
970323AG2-213 GEN
Solar/Wind Harmer
15.706
971775AH1-396 GEN
Solar/Wind Harmer
2.237
313527AB2-043 GEN
Solar/Wind Harmer
3.538
962561AG1-105 GEN
Solar/Wind Harmer
9.795
939181AE1-148 GEN
Solar/Wind Harmer
9.44
964791AG1-342 GEN
Solar/Wind Harmer
3.552
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
970099AG2-077 GEN
Solar/Wind Harmer
18.81
970933AG2-581 GEN
Solar/Wind Harmer
9.592
316181AB2-040 GEN
Solar/Wind Harmer
1.225
316222AC1-221 GEN
Solar/Wind Harmer
0.857
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.951
3145593CAROLNA
Solar/Wind Harmer
0.07
3145783HORNRTN
Solar/Wind Harmer
0.982
3145783HORNRTN
Solar/Wind Harmer
0.786
3145783HORNRTN
Solar/Wind Harmer
0.245
3145783HORNRTN
Solar/Wind Harmer
0.098
316426AA2-053 GEN
Solar/Wind Harmer
0.813
316274AC1-208 GEN
Solar/Wind Harmer
0.793
942751AE2-291 GEN
Solar/Wind Harmer
4.536
972187AH1-678 GEN
Adder
1.773
972185AH1-677 GEN
Adder
3.35
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
316263AC1-034 GEN
Solar/Wind Harmer
3.126
961601AG1-000A GEN
Solar/Wind Harmer
2.583
3145893MURPHYS
Solar/Wind Harmer
0.18
3145893MURPHYS
Solar/Wind Harmer
-0.012
3145493TOT1
Solar/Wind Harmer
0.098
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
3146776BUCKING
Solar/Wind Helper
3.457
3146776BUCKING
Solar/Wind Helper
0.28
315821AE2-092 GEN
Solar/Wind Helper
2.963
3144293JTRSVLE
50/50
1.195
3151601KERR 3
50/50
0.289
3151581KERR 1
50/50
0.103
3151531CLOVER1
50/50
2.955
3147043LAWRENC
50/50
1.106
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.97
971563AH1-280 GEN
Solar/Wind Harmer
4.97
970685AG2-442 GEN
Solar/Wind Harmer
31.247
962491AG1-098 GEN
Solar/Wind Harmer
14.52
316237AB2-079_GEN
Solar/Wind Harmer
0.639
315693AD1-088 GEN
Solar/Wind Harmer
10.276
970401AG2-262 GEN
Solar/Wind Harmer
1.085
957481AF2-042 GEN
Solar/Wind Harmer
47.025
315687AD1-152 GEN
Solar/Wind Harmer
1.689
971065AG2-659 GEN
Solar/Wind Harmer
6.793
316129AC1-054 GEN
Solar/Wind Harmer
1.154
316003AC1-222 GEN
Solar/Wind Harmer
1.163
971795AH1-408 GEN
Solar/Wind Harmer
8.792
960081AF2-299 GEN
Solar/Wind Harmer
1.021
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.099
316212AC1-099_GEN
Solar/Wind Harmer
0.614
970919AG2-571 GEN
Solar/Wind Harmer
2.193
970087AG2-069 GEN
Solar/Wind Harmer
6.491
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.406
962571AG1-106 GEN
Solar/Wind Harmer
0.966
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316359AB2-059 GEN
Solar/Wind Harmer
0.899
316049AB1-081 GEN
Solar/Wind Harmer
0.72
3142053HEARTS
Solar/Wind Harmer
0.078
315722AD1-056 GEN
Solar/Wind Harmer
0.694
316023GEN1_S
Solar/Wind Harmer
0.443
3145823KELFORD
Solar/Wind Harmer
-0.006
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.191
961671AG1-007 GEN
Solar/Wind Harmer
0.08
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
316322AB2-045
Solar/Wind Helper
0.963
3146776BUCKING
Solar/Wind Helper
0.346
316336AC2-165 C
Solar/Wind Helper
1.425
CPLELTFEXP_CPLE->PJM
CLTF
4.543
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.552
LAGNLTFEXP_LAGN->PJM
CLTF
2.505
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.252
TVALTFEXP_TVA->PJM
CLTF
1.216
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.102
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.96
MECLTFEXP_MEC->PJM
CLTF
0.838
SIGELTFEXP_SIGE->PJM
CLTF
0.022
NYPJM->LTFIMP_NY
CLTF
0.295
LGEELTFEXP_LGEE->PJM
CLTF
0.219
WECLTFEXP_WEC->PJM
CLTF
0.123

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2003-205_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2003-205_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:115.25 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:788.33
MW Contribution:12.73
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.19
3151601KERR 3
50/50
0.284
3151581KERR 1
50/50
0.102
3151531CLOVER1
50/50
2.917
3147043LAWRENC
50/50
1.102
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.946
971563AH1-280 GEN
Solar/Wind Harmer
4.946
970685AG2-442 GEN
Solar/Wind Harmer
31.078
962491AG1-098 GEN
Solar/Wind Harmer
14.404
316237AB2-079_GEN
Solar/Wind Harmer
0.632
315693AD1-088 GEN
Solar/Wind Harmer
10.19
970401AG2-262 GEN
Solar/Wind Harmer
1.07
957481AF2-042 GEN
Solar/Wind Harmer
46.506
315687AD1-152 GEN
Solar/Wind Harmer
1.657
971065AG2-659 GEN
Solar/Wind Harmer
6.686
316129AC1-054 GEN
Solar/Wind Harmer
1.136
971795AH1-408 GEN
Solar/Wind Harmer
8.781
316003AC1-222 GEN
Solar/Wind Harmer
1.14
960081AF2-299 GEN
Solar/Wind Harmer
1.025
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.097
316212AC1-099_GEN
Solar/Wind Harmer
0.591
970919AG2-571 GEN
Solar/Wind Harmer
2.137
970087AG2-069 GEN
Solar/Wind Harmer
6.318
316023GEN1_S
Solar/Wind Harmer
0.452
316011AB1-132 GEN
Solar/Wind Harmer
1.389
962571AG1-106 GEN
Solar/Wind Harmer
0.954
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
-0.026
315722AD1-056 GEN
Solar/Wind Harmer
0.667
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316322AB2-045
Solar/Wind Helper
0.967
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.456
3151611KERR 4
50/50
0.284
3151621KERR 5
50/50
0.284
3151631KERR 6
50/50
0.284
3151641KERR 7
50/50
0.284
3151541CLOVER2
50/50
2.903
315657AE1-056 GEN
Solar/Wind Harmer
15.898
946301AF1-294 GEN
Solar/Wind Harmer
10.139
961791AG1-021 GEN
Solar/Wind Harmer
4.946
970683AG2-441 GEN
Solar/Wind Harmer
27.748
970681AG2-440 GEN
Solar/Wind Harmer
22.198
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.073
316239AB2-077_GEN
Solar/Wind Harmer
0.632
316238AB2-078_GEN
Solar/Wind Harmer
0.632
316118AC1-105 GEN
Solar/Wind Harmer
0.997
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.254
970865AG2-541 GEN
Solar/Wind Harmer
4.048
946281AF1-292 GEN
Solar/Wind Harmer
0.204
316087AB2-174 GEN
Solar/Wind Harmer
1.262
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.884
970165AG2-112 GEN
Solar/Wind Harmer
0.778
970163AG2-111 GEN
Solar/Wind Harmer
0.742
971967AH1-528 GEN
Solar/Wind Harmer
15.039
315607AA1-063A GEN
Solar/Wind Harmer
0.762
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.212
970581AG2-369 GEN
Solar/Wind Harmer
3.623
315652AC1-086 GEN
Solar/Wind Harmer
7.469
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.026
316319Z2-044 C
Solar/Wind Harmer
0.36
970673AG2-436 GEN
Solar/Wind Harmer
13.449
970673AG2-436 GEN
Solar/Wind Harmer
6.81
965291AG1-394 GEN
Solar/Wind Harmer
0.565
270494AE1-108_GEN
Solar/Wind Helper
4.476
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.19
3144293JTRSVLE
50/50
1.002
970535AG2-341 GEN
50/50
2.898
3152661PLYWOOD A
50/50
0.275
970301AG2-198 GEN
Solar/Wind Harmer
21.406
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.183
963191AG1-168 GEN
Solar/Wind Harmer
3.71
971741AH1-377 GEN
Solar/Wind Harmer
43.786
316034AC1-036 C
Solar/Wind Harmer
0.58
970323AG2-213 GEN
Solar/Wind Harmer
15.608
971775AH1-396 GEN
Solar/Wind Harmer
2.223
313527AB2-043 GEN
Solar/Wind Harmer
3.505
962561AG1-105 GEN
Solar/Wind Harmer
9.664
939181AE1-148 GEN
Solar/Wind Harmer
9.308
964791AG1-342 GEN
Solar/Wind Harmer
3.501
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.602
970933AG2-581 GEN
Solar/Wind Harmer
9.49
316181AB2-040 GEN
Solar/Wind Harmer
1.218
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.934
3145593CAROLNA
Solar/Wind Harmer
0.069
3145783HORNRTN
Solar/Wind Harmer
0.963
3145783HORNRTN
Solar/Wind Harmer
0.77
3145783HORNRTN
Solar/Wind Harmer
0.241
3145783HORNRTN
Solar/Wind Harmer
0.096
316222AC1-221 GEN
Solar/Wind Harmer
0.802
316426AA2-053 GEN
Solar/Wind Harmer
0.797
316274AC1-208 GEN
Solar/Wind Harmer
0.766
942751AE2-291 GEN
Solar/Wind Harmer
4.503
972187AH1-678 GEN
Adder
1.745
972185AH1-677 GEN
Adder
3.302
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3146776BUCKING
Solar/Wind Helper
3.47
3146776BUCKING
Solar/Wind Helper
0.281
315821AE2-092 GEN
Solar/Wind Helper
2.982
3144293JTRSVLE
50/50
1.19
3151591KERR 2
50/50
0.284
970413AG2-270 GEN
50/50
12.729
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.576
970909AG2-566 GEN
Solar/Wind Harmer
4.064
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.496
963181AG1-167 GEN
Solar/Wind Harmer
3.71
959311AF2-222 GEN
Solar/Wind Harmer
33.872
970257AG2-171 GEN
Solar/Wind Harmer
11.706
315785AD2-033 C
Solar/Wind Harmer
6.689
964241AG1-285 GEN
Solar/Wind Harmer
19.525
316131AB2-060 GEN
Solar/Wind Harmer
2.4
316478AD1-087 GEN
Solar/Wind Harmer
1.324
316486AD2-202 GEN
Solar/Wind Harmer
0.388
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.381
960061AF2-297 GEN
Solar/Wind Harmer
6.325
971683AH1-343 GEN
Solar/Wind Harmer
4.674
966621AG1-532 GEN
Solar/Wind Harmer
0.185
313506AB2-031 GEN
Solar/Wind Harmer
0.702
316283AC2-100 C
Solar/Wind Harmer
0.736
316210AC1-098 GEN
Solar/Wind Harmer
1.064
970917AG2-570 GEN
Solar/Wind Harmer
16.885
316365GEN2_N
Solar/Wind Harmer
0.452
316327AA2-057 GEN
Solar/Wind Harmer
0.676
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.136
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
315724AD1-057 GEN
Solar/Wind Harmer
0.367
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.312
316313AB2-026
Solar/Wind Helper
0.342
316258AE1-075 C
Solar/Wind Helper
0.307
316405AF2-144 C
Solar/Wind Helper
0.256
3148013FISHERV
Solar/Wind Helper
0.124
CPLELTFEXP_CPLE->PJM
CLTF
3.951
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.116
LAGNLTFEXP_LAGN->PJM
CLTF
2.085
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.001
TVALTFEXP_TVA->PJM
CLTF
1.025
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.511
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.403
MECLTFEXP_MEC->PJM
CLTF
0.809
SIGELTFEXP_SIGE->PJM
CLTF
0.023
NYPJM->LTFIMP_NY
CLTF
0.315
LGEELTFEXP_LGEE->PJM
CLTF
0.251
WECLTFEXP_WEC->PJM
CLTF
0.133

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P2-2: ALTAVISTA 115KV_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: ALTAVISTA 115KV_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:113.26 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:774.73
MW Contribution:13.01
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.292
3151621KERR 5
50/50
0.292
3151631KERR 6
50/50
0.292
3151641KERR 7
50/50
0.292
3151541CLOVER2
50/50
2.967
315657AE1-056 GEN
Solar/Wind Harmer
16.053
946301AF1-294 GEN
Solar/Wind Harmer
10.253
961791AG1-021 GEN
Solar/Wind Harmer
5.001
970683AG2-441 GEN
Solar/Wind Harmer
28.127
970681AG2-440 GEN
Solar/Wind Harmer
22.501
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.178
316239AB2-077_GEN
Solar/Wind Harmer
0.652
316238AB2-078_GEN
Solar/Wind Harmer
0.652
316118AC1-105 GEN
Solar/Wind Harmer
1.105
316123AC1-075 GEN
Solar/Wind Harmer
1.561
970165AG2-112 GEN
Solar/Wind Harmer
1.375
970163AG2-111 GEN
Solar/Wind Harmer
1.311
970865AG2-541 GEN
Solar/Wind Harmer
5.879
3147173SINAI
Solar/Wind Harmer
-0.014
3147243WELCO
Solar/Wind Harmer
-0.009
970831AG2-522 GEN
Solar/Wind Harmer
6.369
946281AF1-292 GEN
Solar/Wind Harmer
0.201
316087AB2-174 GEN
Solar/Wind Harmer
1.25
3137643SOCKMAN
Solar/Wind Harmer
-0.034
971967AH1-528 GEN
Solar/Wind Harmer
14.997
315607AA1-063A GEN
Solar/Wind Harmer
0.762
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.185
970581AG2-369 GEN
Solar/Wind Harmer
3.599
3146033SCOT NK
Solar/Wind Harmer
-0.026
315652AC1-086 GEN
Solar/Wind Harmer
7.298
316319Z2-044 C
Solar/Wind Harmer
0.358
3145796HORNRTN
Solar/Wind Harmer
-0.02
3145796HORNRTN
Solar/Wind Harmer
-0.003
965291AG1-394 GEN
Solar/Wind Harmer
0.567
970673AG2-436 GEN
Solar/Wind Harmer
13.3
970673AG2-436 GEN
Solar/Wind Harmer
6.734
270494AE1-108_GEN
Solar/Wind Helper
4.519
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.203
3151591KERR 2
50/50
0.292
970413AG2-270 GEN
50/50
13.01
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.625
970909AG2-566 GEN
Solar/Wind Harmer
4.087
3147133PAMPLIN
Solar/Wind Harmer
-0.134
3144293JTRSVLE
50/50
1.203
3144293JTRSVLE
50/50
1.013
970535AG2-341 GEN
50/50
2.978
3152661PLYWOOD A
50/50
0.306
970301AG2-198 GEN
Solar/Wind Harmer
21.525
3147133PAMPLIN
Solar/Wind Harmer
-0.043
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.252
963191AG1-168 GEN
Solar/Wind Harmer
3.751
971741AH1-377 GEN
Solar/Wind Harmer
44.063
316034AC1-036 C
Solar/Wind Harmer
0.59
970323AG2-213 GEN
Solar/Wind Harmer
15.873
971775AH1-396 GEN
Solar/Wind Harmer
2.26
313527AB2-043 GEN
Solar/Wind Harmer
3.607
962561AG1-105 GEN
Solar/Wind Harmer
10.348
964791AG1-342 GEN
Solar/Wind Harmer
3.783
3146843MT LREL
Solar/Wind Harmer
-0.018
3146843MT LREL
Solar/Wind Harmer
-0.018
939181AE1-148 GEN
Solar/Wind Harmer
9.553
970099AG2-077 GEN
Solar/Wind Harmer
18.881
942751AE2-291 GEN
Solar/Wind Harmer
9.226
970933AG2-581 GEN
Solar/Wind Harmer
9.531
316181AB2-040 GEN
Solar/Wind Harmer
1.209
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.934
3145593CAROLNA
Solar/Wind Harmer
0.069
316222AC1-221 GEN
Solar/Wind Harmer
0.828
3145783HORNRTN
Solar/Wind Harmer
0.962
3145783HORNRTN
Solar/Wind Harmer
0.77
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
316426AA2-053 GEN
Solar/Wind Harmer
0.796
316274AC1-208 GEN
Solar/Wind Harmer
0.764
3144293JTRSVLE
50/50
1.203
3151601KERR 3
50/50
0.292
3151581KERR 1
50/50
0.104
3151531CLOVER1
50/50
2.981
3147043LAWRENC
50/50
1.112
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
5.001
971563AH1-280 GEN
Solar/Wind Harmer
5.001
970685AG2-442 GEN
Solar/Wind Harmer
31.502
962491AG1-098 GEN
Solar/Wind Harmer
14.564
316237AB2-079_GEN
Solar/Wind Harmer
0.652
315693AD1-088 GEN
Solar/Wind Harmer
10.309
970401AG2-262 GEN
Solar/Wind Harmer
1.156
957481AF2-042 GEN
Solar/Wind Harmer
47.203
3147123OTTER R
Solar/Wind Harmer
-0.009
316003AC1-222 GEN
Solar/Wind Harmer
1.413
315687AD1-152 GEN
Solar/Wind Harmer
1.721
971065AG2-659 GEN
Solar/Wind Harmer
6.825
316129AC1-054 GEN
Solar/Wind Harmer
1.158
971795AH1-408 GEN
Solar/Wind Harmer
8.808
960081AF2-299 GEN
Solar/Wind Harmer
1.012
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.097
316212AC1-099_GEN
Solar/Wind Harmer
0.59
970919AG2-571 GEN
Solar/Wind Harmer
2.123
970087AG2-069 GEN
Solar/Wind Harmer
6.277
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.357
962571AG1-106 GEN
Solar/Wind Harmer
0.932
3146233WITAKRS
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.006
316023GEN1_S
Solar/Wind Harmer
0.431
316322AB2-045
Solar/Wind Helper
0.963
3146776BUCKING
Solar/Wind Helper
0.345
316336AC2-165 C
Solar/Wind Helper
1.43
972187AH1-678 GEN
Adder
1.732
972185AH1-677 GEN
Adder
3.271
3145796HORNRTN
Solar/Wind Harmer
-0.019
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3146776BUCKING
Solar/Wind Helper
3.456
3146776BUCKING
Solar/Wind Helper
0.28
315821AE2-092 GEN
Solar/Wind Helper
2.97
971193AH1-056 GEN
Solar/Wind Harmer
26.755
963181AG1-167 GEN
Solar/Wind Harmer
3.751
959311AF2-222 GEN
Solar/Wind Harmer
34.411
970257AG2-171 GEN
Solar/Wind Harmer
11.905
315785AD2-033 C
Solar/Wind Harmer
6.813
964241AG1-285 GEN
Solar/Wind Harmer
19.989
316131AB2-060 GEN
Solar/Wind Harmer
2.467
316478AD1-087 GEN
Solar/Wind Harmer
1.354
316486AD2-202 GEN
Solar/Wind Harmer
0.396
971683AH1-343 GEN
Solar/Wind Harmer
6.24
316248AF1-058 C
Solar/Wind Harmer
0.436
960061AF2-297 GEN
Solar/Wind Harmer
7.234
3147043LAWRENC
Solar/Wind Harmer
-0.008
966621AG1-532 GEN
Solar/Wind Harmer
0.182
313506AB2-031 GEN
Solar/Wind Harmer
0.697
316283AC2-100 C
Solar/Wind Harmer
0.759
316210AC1-098 GEN
Solar/Wind Harmer
1.062
970917AG2-570 GEN
Solar/Wind Harmer
16.773
316327AA2-057 GEN
Solar/Wind Harmer
0.674
3146263WOODLND
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.136
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
316365GEN2_N
Solar/Wind Harmer
0.431
3146776BUCKING
Solar/Wind Helper
0.311
316313AB2-026
Solar/Wind Helper
0.334
316258AE1-075 C
Solar/Wind Helper
0.3
316405AF2-144 C
Solar/Wind Helper
0.25
3148013FISHERV
Solar/Wind Helper
0.123
CPLELTFEXP_CPLE->PJM
CLTF
3.953
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.193
LAGNLTFEXP_LAGN->PJM
CLTF
1.949
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.898
TVALTFEXP_TVA->PJM
CLTF
0.953
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.579
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.131
MECLTFEXP_MEC->PJM
CLTF
0.695
SIGELTFEXP_SIGE->PJM
CLTF
0.019
NYPJM->LTFIMP_NY
CLTF
0.29
LGEELTFEXP_LGEE->PJM
CLTF
0.201
WECLTFEXP_WEC->PJM
CLTF
0.107

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.32 %
Rating:559.3 MVA
Rating Type:A
MVA to Mitigate:566.67
MW Contribution:12.48
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.279
3151621KERR 5
50/50
0.279
3151631KERR 6
50/50
0.279
3151641KERR 7
50/50
0.279
3151541CLOVER2
50/50
2.847
3151281ROARAP4
50/50
0.085
3151281ROARAP4
50/50
0.08
963041AG1-153 GEN
50/50
1.549
315657AE1-056 GEN
Solar/Wind Harmer
12.95
946301AF1-294 GEN
Solar/Wind Harmer
6.911
961791AG1-021 GEN
Solar/Wind Harmer
3.362
970683AG2-441 GEN
Solar/Wind Harmer
20.935
970681AG2-440 GEN
Solar/Wind Harmer
16.748
3144303KENBRDG
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
4.574
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.327
3147173SINAI
Solar/Wind Harmer
0.11
3147243WELCO
Solar/Wind Harmer
0.069
970831AG2-522 GEN
Solar/Wind Harmer
4.619
970865AG2-541 GEN
Solar/Wind Harmer
3.009
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.287
316123AC1-075 GEN
Solar/Wind Harmer
0.097
970165AG2-112 GEN
Solar/Wind Harmer
0.577
970163AG2-111 GEN
Solar/Wind Harmer
0.551
971967AH1-528 GEN
Solar/Wind Harmer
10.885
315607AA1-063A GEN
Solar/Wind Harmer
0.13
3146043SEABORD
Solar/Wind Harmer
0.063
970085AG2-068 GEN
Solar/Wind Harmer
3.037
970581AG2-369 GEN
Solar/Wind Harmer
2.612
270494AE1-108_GEN
Solar/Wind Helper
4.476
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.183
3151601KERR 3
50/50
0.279
3151581KERR 1
50/50
0.1
3151531CLOVER1
50/50
2.861
3147043LAWRENC
50/50
1.063
3151261ROARAP2
50/50
0.088
3151051BRUNSWICKS1
50/50
1.588
3151021BRUNSWICKG1
50/50
0.765
971451AH1-221 GEN
50/50
2.324
3146926FARMVIL
Solar/Wind Harmer
0.316
963171AG1-166 GEN
Solar/Wind Harmer
1.868
971563AH1-280 GEN
Solar/Wind Harmer
3.736
970685AG2-442 GEN
Solar/Wind Harmer
23.448
962491AG1-098 GEN
Solar/Wind Harmer
10.797
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
8.584
970401AG2-262 GEN
Solar/Wind Harmer
0.842
957481AF2-042 GEN
Solar/Wind Harmer
34.592
315687AD1-152 GEN
Solar/Wind Harmer
0.004
971065AG2-659 GEN
Solar/Wind Harmer
4.952
316129AC1-054 GEN
Solar/Wind Harmer
0.422
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971795AH1-408 GEN
Solar/Wind Harmer
6.656
960081AF2-299 GEN
Solar/Wind Harmer
0.732
3145783HORNRTN
Solar/Wind Harmer
0.069
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
0.296
970919AG2-571 GEN
Solar/Wind Harmer
2.029
970087AG2-069 GEN
Solar/Wind Harmer
4.556
316322AB2-045
Solar/Wind Helper
0.968
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.445
3144293JTRSVLE
50/50
1.183
3144293JTRSVLE
50/50
0.996
970535AG2-341 GEN
50/50
2.851
3152661PLYWOOD A
50/50
0.269
3151041BRUNSWICKG3
50/50
0.765
972187AH1-678 GEN
50/50
1.756
970301AG2-198 GEN
Solar/Wind Harmer
16.182
3147133PAMPLIN
Solar/Wind Harmer
0.375
3147133PAMPLIN
Solar/Wind Harmer
0.3
958211AF2-115 GEN
Solar/Wind Harmer
4.203
963191AG1-168 GEN
Solar/Wind Harmer
1.401
971741AH1-377 GEN
Solar/Wind Harmer
33.06
316034AC1-036 C
Solar/Wind Harmer
0.02
970323AG2-213 GEN
Solar/Wind Harmer
11.759
971775AH1-396 GEN
Solar/Wind Harmer
0.441
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
7.224
939181AE1-148 GEN
Solar/Wind Harmer
6.94
964791AG1-342 GEN
Solar/Wind Harmer
2.755
3146843MT LREL
Solar/Wind Harmer
0.143
3146843MT LREL
Solar/Wind Harmer
0.143
970099AG2-077 GEN
Solar/Wind Harmer
13.837
970933AG2-581 GEN
Solar/Wind Harmer
6.964
316181AB2-040 GEN
Solar/Wind Harmer
0.107
3145593CAROLNA
Solar/Wind Harmer
0.07
3145593CAROLNA
Solar/Wind Harmer
0.07
966811AG1-552 GEN
Solar/Wind Harmer
0.763
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.221
3145783HORNRTN
Solar/Wind Harmer
0.977
3145783HORNRTN
Solar/Wind Harmer
0.305
3145783HORNRTN
Solar/Wind Harmer
0.122
316222AC1-221 GEN
Solar/Wind Harmer
0.284
316426AA2-053 GEN
Solar/Wind Harmer
0.225
942751AE2-291 GEN
Solar/Wind Harmer
3.338
316274AC1-208 GEN
Solar/Wind Harmer
0.311
3146776BUCKING
Solar/Wind Helper
3.475
3146776BUCKING
Solar/Wind Helper
0.282
315821AE2-092 GEN
Solar/Wind Helper
2.978
3144293JTRSVLE
50/50
1.183
3151591KERR 2
50/50
0.279
970413AG2-270 GEN
50/50
12.485
3151261ROARAP2
50/50
0.086
3151031BRUNSWICKG2
50/50
0.765
3146926FARMVIL
Solar/Wind Harmer
0.316
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.045
3147133PAMPLIN
Solar/Wind Harmer
1.178
971193AH1-056 GEN
Solar/Wind Harmer
22.863
963181AG1-167 GEN
Solar/Wind Harmer
1.401
959311AF2-222 GEN
Solar/Wind Harmer
25.479
970257AG2-171 GEN
Solar/Wind Harmer
8.819
315785AD2-033 C
Solar/Wind Harmer
2.117
964241AG1-285 GEN
Solar/Wind Harmer
14.665
316131AB2-060 GEN
Solar/Wind Harmer
0.615
316478AD1-087 GEN
Solar/Wind Harmer
0.466
316486AD2-202 GEN
Solar/Wind Harmer
0.137
3147043LAWRENC
Solar/Wind Harmer
0.066
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.708
971683AH1-343 GEN
Solar/Wind Harmer
3.476
313506AB2-031 GEN
Solar/Wind Harmer
0.227
316283AC2-100 C
Solar/Wind Harmer
0.132
316210AC1-098 GEN
Solar/Wind Harmer
0.531
970917AG2-570 GEN
Solar/Wind Harmer
5.072
316327AA2-057 GEN
Solar/Wind Harmer
0.085
3146776BUCKING
Solar/Wind Helper
0.313
316313AB2-026
Solar/Wind Helper
0.338
316258AE1-075 C
Solar/Wind Helper
0.304
316405AF2-144 C
Solar/Wind Helper
0.253
3148013FISHERV
Solar/Wind Helper
0.123
CPLELTFEXP_CPLE->PJM
CLTF
3.789
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.54
LAGNLTFEXP_LAGN->PJM
CLTF
1.976
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.656
TVALTFEXP_TVA->PJM
CLTF
0.971
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.153
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.217
MECLTFEXP_MEC->PJM
CLTF
0.756
SIGELTFEXP_SIGE->PJM
CLTF
0.021
NYPJM->LTFIMP_NY
CLTF
0.298
LGEELTFEXP_LGEE->PJM
CLTF
0.232
WECLTFEXP_WEC->PJM
CLTF
0.123

Details for 6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-5: 556X2_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-5: 556X2_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.23 %
Rating:1050.6 MVA
Rating Type:C
MVA to Mitigate:1462.74
MW Contribution:36.37
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
36.366
3144293JTRSVLE
50/50
0.954
3151591KERR 2
50/50
0.512
3151921BEARGRDN G2
50/50
1.071
970909AG2-566 GEN
Solar/Wind Harmer
4.458
316478AD1-087 GEN
Solar/Wind Harmer
3.778
316486AD2-202 GEN
Solar/Wind Harmer
1.106
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
5.027
3147133PAMPLIN
Solar/Wind Harmer
-0.101
971193AH1-056 GEN
Solar/Wind Harmer
20.111
963181AG1-167 GEN
Solar/Wind Harmer
2.974
959311AF2-222 GEN
Solar/Wind Harmer
31.935
970257AG2-171 GEN
Solar/Wind Harmer
11.4
315785AD2-033 C
Solar/Wind Harmer
6.828
3151541CLOVER2
50/50
8.294
3151611KERR 4
50/50
0.512
3151621KERR 5
50/50
0.512
3151631KERR 6
50/50
0.512
3151641KERR 7
50/50
0.512
972205AH1-687 GEN
50/50
5.225
315657AE1-056 GEN
Solar/Wind Harmer
12.067
946301AF1-294 GEN
Solar/Wind Harmer
8.13
961791AG1-021 GEN
Solar/Wind Harmer
3.966
970683AG2-441 GEN
Solar/Wind Harmer
24.284
970681AG2-440 GEN
Solar/Wind Harmer
19.428
3144303KENBRDG
Solar/Wind Harmer
-0.024
971443AH1-215 GEN
Solar/Wind Harmer
5.973
316239AB2-077_GEN
Solar/Wind Harmer
0.866
316238AB2-078_GEN
Solar/Wind Harmer
0.866
970285AG2-188 GEN
Solar/Wind Harmer
23.989
316118AC1-105 GEN
Solar/Wind Harmer
1.858
3147173SINAI
Solar/Wind Harmer
-0.026
3147243WELCO
Solar/Wind Harmer
-0.016
971845AH1-439 GEN
Solar/Wind Harmer
13.717
970865AG2-541 GEN
Solar/Wind Harmer
8.867
970831AG2-522 GEN
Solar/Wind Harmer
9.395
316123AC1-075 GEN
Solar/Wind Harmer
2.019
970165AG2-112 GEN
Solar/Wind Harmer
1.778
970163AG2-111 GEN
Solar/Wind Harmer
1.696
971447AH1-217 GEN
Solar/Wind Harmer
3.892
270494AE1-108_GEN
Solar/Wind Harmer
2.597
270455AD2-022 GEN
Solar/Wind Harmer
1.324
270457AD2-023 GEN
Solar/Wind Harmer
0.671
3143316POE
Solar/Wind Helper
0.479
319010AE1-072 C
Solar/Wind Helper
1.317
316305AF2-043 C
Solar/Wind Helper
0.151
964241AG1-285 GEN
Solar/Wind Harmer
22.977
316131AB2-060 GEN
Solar/Wind Harmer
3.126
316248AF1-058 C
Solar/Wind Harmer
0.799
960061AF2-297 GEN
Solar/Wind Harmer
13.263
3146776BUCKING
Solar/Wind Harmer
-0.009
971683AH1-343 GEN
Solar/Wind Harmer
10.071
316283AC2-100 C
Solar/Wind Harmer
1.212
3147043LAWRENC
Solar/Wind Harmer
-0.007
970221AG2-151 GEN
Solar/Wind Harmer
7.265
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
3.291
958131AF2-107 GEN
Solar/Wind Harmer
2.165
315773AC2-141 GEN
Solar/Wind Helper
2.933
3144873MCLAUGH
Solar/Wind Helper
0.003
3144536CHRHLND
Solar/Wind Helper
0.018
3145336SMITFLD
Solar/Wind Helper
0.047
3146456SLIGO L269
Solar/Wind Helper
0.116
3151531CLOVER1
50/50
8.333
3144293JTRSVLE
50/50
0.954
3151601KERR 3
50/50
0.512
3151581KERR 1
50/50
0.183
3151931BEARGRDN S1
50/50
1.383
3151911BEARGRDN G1
50/50
1.071
315693AD1-088 GEN
Solar/Wind Harmer
31.661
962491AG1-098 GEN
Solar/Wind Harmer
41.781
957481AF2-042 GEN
Solar/Wind Harmer
136.799
315687AD1-152 GEN
Solar/Wind Harmer
4.384
3146926FARMVIL
Solar/Wind Harmer
-0.021
963171AG1-166 GEN
Solar/Wind Harmer
3.966
971563AH1-280 GEN
Solar/Wind Harmer
3.966
970685AG2-442 GEN
Solar/Wind Harmer
27.199
316237AB2-079_GEN
Solar/Wind Harmer
0.866
970401AG2-262 GEN
Solar/Wind Harmer
1.795
316322AB2-045
Solar/Wind Harmer
0.84
3146776BUCKING
Solar/Wind Harmer
-0.01
316003AC1-222 GEN
Solar/Wind Harmer
2.424
971065AG2-659 GEN
Solar/Wind Harmer
10.717
316129AC1-054 GEN
Solar/Wind Harmer
1.767
972003AH1-546 GEN
Solar/Wind Harmer
7.559
3147043LAWRENC
Adder
0.99
971377AH1-170 GEN
Solar/Wind Harmer
1.453
3147623JAMES R
Solar/Wind Harmer
0.18
3147123OTTER R
Solar/Wind Harmer
-0.006
971795AH1-408 GEN
Solar/Wind Harmer
7.507
970937AG2-583 GEN
Solar/Wind Harmer
6.673
3147312GRETNA
Solar/Wind Harmer
-0.007
3146802CHATHAM
Solar/Wind Harmer
-0.007
941801AE2-185 GEN
Solar/Wind Harmer
3.291
316294AC1-161 GEN
Solar/Wind Helper
2.492
316375AC2-012 GEN
Solar/Wind Helper
0.324
316388AE2-253 GEN
Solar/Wind Helper
0.45
3145336SMITFLD
Solar/Wind Helper
0.467
3146456SLIGO L269
Solar/Wind Helper
0.116
316246AF1-032 C
Solar/Wind Helper
0.129
316072AD1-144
Solar/Wind Helper
0.129
3144293JTRSVLE
50/50
0.954
3144293JTRSVLE
50/50
0.803
970535AG2-341 GEN
50/50
4.477
3152661PLYWOOD A
50/50
0.537
971741AH1-377 GEN
Solar/Wind Harmer
58.955
970301AG2-198 GEN
Solar/Wind Harmer
23.48
970099AG2-077 GEN
Solar/Wind Harmer
54.72
3147133PAMPLIN
Solar/Wind Harmer
-0.032
3147133PAMPLIN
Solar/Wind Harmer
-0.026
958211AF2-115 GEN
Solar/Wind Harmer
4.957
963191AG1-168 GEN
Solar/Wind Harmer
2.974
316034AC1-036 C
Solar/Wind Harmer
0.564
970323AG2-213 GEN
Solar/Wind Harmer
15.2
971775AH1-396 GEN
Solar/Wind Harmer
2.165
313527AB2-043 GEN
Solar/Wind Harmer
4.69
939181AE1-148 GEN
Solar/Wind Harmer
15.738
962561AG1-105 GEN
Solar/Wind Harmer
15.589
964791AG1-342 GEN
Solar/Wind Harmer
5.876
3146843MT LREL
Solar/Wind Harmer
-0.027
3146843MT LREL
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.099
3146776BUCKING
Solar/Wind Harmer
-0.008
942751AE2-291 GEN
Solar/Wind Harmer
10.674
316222AC1-221 GEN
Solar/Wind Harmer
1.342
971489AH1-241 GEN
Solar/Wind Harmer
6.897
316217AC1-145 GEN
Solar/Wind Harmer
1.425
316197AC1-042 GEN
Solar/Wind Harmer
1.08
942671AE2-283 GEN
Solar/Wind Harmer
2.907
315821AE2-092 GEN
Solar/Wind Harmer
1.728
316036AC1-147 C
Solar/Wind Helper
0.189
3142956BIRDNECK
Solar/Wind Helper
0.083
316316AC1-027 C
Solar/Wind Helper
0.194
316185AD1-033 GEN
Solar/Wind Helper
0.577
3145506HICKORY
Solar/Wind Helper
0.484
3145506HICKORY
Solar/Wind Helper
0.291
3145506HICKORY
Solar/Wind Helper
0.073
316339AD2-160 GEN
Solar/Wind Helper
0.45
316018AA1-139 ULT2
Solar/Wind Helper
0.505
316017AA1-139 ULT1
Solar/Wind Helper
0.536
316236AE1-162_GEN
Solar/Wind Helper
0.157
3137176SLIGO L2192
Solar/Wind Helper
0.462
3130086AYDLETT
Solar/Wind Helper
0.459
CPLELTFEXP_CPLE->PJM
CLTF
2.622
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.961
LAGNLTFEXP_LAGN->PJM
CLTF
2.391
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.949
TVALTFEXP_TVA->PJM
CLTF
1.221
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.001
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.345
MECLTFEXP_MEC->PJM
CLTF
1.48
SIGELTFEXP_SIGE->PJM
CLTF
0.047
NYPJM->LTFIMP_NY
CLTF
0.45
LGEELTFEXP_LGEE->PJM
CLTF
0.594
WECLTFEXP_WEC->PJM
CLTF
0.305

Details for 6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: 556X1_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-5: 556X1_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.76 %
Rating:1053.0 MVA
Rating Type:C
MVA to Mitigate:1461.12
MW Contribution:36.33
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
8.324
3144293JTRSVLE
50/50
0.953
3151601KERR 3
50/50
0.511
3151581KERR 1
50/50
0.182
3151931BEARGRDN S1
50/50
1.381
3151911BEARGRDN G1
50/50
1.07
315693AD1-088 GEN
Solar/Wind Harmer
31.626
962491AG1-098 GEN
Solar/Wind Harmer
41.735
957481AF2-042 GEN
Solar/Wind Harmer
136.647
315687AD1-152 GEN
Solar/Wind Harmer
4.379
3146926FARMVIL
Solar/Wind Harmer
-0.021
963171AG1-166 GEN
Solar/Wind Harmer
3.962
971563AH1-280 GEN
Solar/Wind Harmer
3.962
970685AG2-442 GEN
Solar/Wind Harmer
27.168
316237AB2-079_GEN
Solar/Wind Harmer
0.865
970401AG2-262 GEN
Solar/Wind Harmer
1.793
316322AB2-045
Solar/Wind Harmer
0.839
3146776BUCKING
Solar/Wind Harmer
-0.01
316003AC1-222 GEN
Solar/Wind Harmer
2.421
971065AG2-659 GEN
Solar/Wind Harmer
10.705
316129AC1-054 GEN
Solar/Wind Harmer
1.765
972003AH1-546 GEN
Solar/Wind Harmer
7.55
3147043LAWRENC
Adder
0.989
971377AH1-170 GEN
Solar/Wind Harmer
1.451
3147623JAMES R
Solar/Wind Harmer
0.18
3147123OTTER R
Solar/Wind Harmer
-0.006
971795AH1-408 GEN
Solar/Wind Harmer
7.499
970937AG2-583 GEN
Solar/Wind Harmer
6.666
3147312GRETNA
Solar/Wind Harmer
-0.007
3146802CHATHAM
Solar/Wind Harmer
-0.007
941801AE2-185 GEN
Solar/Wind Harmer
3.288
316294AC1-161 GEN
Solar/Wind Helper
2.489
3151541CLOVER2
50/50
8.284
3151611KERR 4
50/50
0.511
3151621KERR 5
50/50
0.511
3151631KERR 6
50/50
0.511
3151641KERR 7
50/50
0.511
972205AH1-687 GEN
50/50
5.219
315657AE1-056 GEN
Solar/Wind Harmer
12.053
946301AF1-294 GEN
Solar/Wind Harmer
8.121
961791AG1-021 GEN
Solar/Wind Harmer
3.962
970683AG2-441 GEN
Solar/Wind Harmer
24.258
970681AG2-440 GEN
Solar/Wind Harmer
19.406
3144303KENBRDG
Solar/Wind Harmer
-0.024
971443AH1-215 GEN
Solar/Wind Harmer
5.967
316239AB2-077_GEN
Solar/Wind Harmer
0.865
316238AB2-078_GEN
Solar/Wind Harmer
0.865
970285AG2-188 GEN
Solar/Wind Harmer
23.962
316118AC1-105 GEN
Solar/Wind Harmer
1.856
3147173SINAI
Solar/Wind Harmer
-0.026
3147243WELCO
Solar/Wind Harmer
-0.016
971845AH1-439 GEN
Solar/Wind Harmer
13.702
970865AG2-541 GEN
Solar/Wind Harmer
8.857
970831AG2-522 GEN
Solar/Wind Harmer
9.385
316123AC1-075 GEN
Solar/Wind Harmer
2.017
970165AG2-112 GEN
Solar/Wind Harmer
1.776
970163AG2-111 GEN
Solar/Wind Harmer
1.694
971447AH1-217 GEN
Solar/Wind Harmer
3.888
270494AE1-108_GEN
Solar/Wind Harmer
2.594
270455AD2-022 GEN
Solar/Wind Harmer
1.322
270457AD2-023 GEN
Solar/Wind Harmer
0.671
3143316POE
Solar/Wind Helper
0.479
319010AE1-072 C
Solar/Wind Helper
1.315
316305AF2-043 C
Solar/Wind Helper
0.151
316375AC2-012 GEN
Solar/Wind Helper
0.324
316388AE2-253 GEN
Solar/Wind Helper
0.45
3145336SMITFLD
Solar/Wind Helper
0.467
3146456SLIGO L269
Solar/Wind Helper
0.116
316246AF1-032 C
Solar/Wind Helper
0.128
316072AD1-144
Solar/Wind Helper
0.128
3144293JTRSVLE
50/50
0.953
3144293JTRSVLE
50/50
0.802
970535AG2-341 GEN
50/50
4.472
3152661PLYWOOD A
50/50
0.536
971741AH1-377 GEN
Solar/Wind Harmer
58.889
970301AG2-198 GEN
Solar/Wind Harmer
23.454
970099AG2-077 GEN
Solar/Wind Harmer
54.659
3147133PAMPLIN
Solar/Wind Harmer
-0.032
3147133PAMPLIN
Solar/Wind Harmer
-0.026
958211AF2-115 GEN
Solar/Wind Harmer
4.952
963191AG1-168 GEN
Solar/Wind Harmer
2.971
316034AC1-036 C
Solar/Wind Harmer
0.563
970323AG2-213 GEN
Solar/Wind Harmer
15.183
971775AH1-396 GEN
Solar/Wind Harmer
2.162
313527AB2-043 GEN
Solar/Wind Harmer
4.685
939181AE1-148 GEN
Solar/Wind Harmer
15.721
962561AG1-105 GEN
Solar/Wind Harmer
15.572
964791AG1-342 GEN
Solar/Wind Harmer
5.869
3146843MT LREL
Solar/Wind Harmer
-0.027
3146843MT LREL
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.099
3146776BUCKING
Solar/Wind Harmer
-0.008
942751AE2-291 GEN
Solar/Wind Harmer
10.662
316222AC1-221 GEN
Solar/Wind Harmer
1.341
971489AH1-241 GEN
Solar/Wind Harmer
6.89
316217AC1-145 GEN
Solar/Wind Harmer
1.423
316197AC1-042 GEN
Solar/Wind Harmer
1.079
942671AE2-283 GEN
Solar/Wind Harmer
2.904
315821AE2-092 GEN
Solar/Wind Harmer
1.726
316036AC1-147 C
Solar/Wind Helper
0.188
3142956BIRDNECK
Solar/Wind Helper
0.083
316316AC1-027 C
Solar/Wind Helper
0.194
316185AD1-033 GEN
Solar/Wind Helper
0.577
3145506HICKORY
Solar/Wind Helper
0.484
3145506HICKORY
Solar/Wind Helper
0.29
3145506HICKORY
Solar/Wind Helper
0.073
316339AD2-160 GEN
Solar/Wind Helper
0.45
316018AA1-139 ULT2
Solar/Wind Helper
0.504
316017AA1-139 ULT1
Solar/Wind Helper
0.536
316236AE1-162_GEN
Solar/Wind Helper
0.157
3137176SLIGO L2192
Solar/Wind Helper
0.461
3130086AYDLETT
Solar/Wind Helper
0.459
970413AG2-270 GEN
50/50
36.326
3144293JTRSVLE
50/50
0.953
3151591KERR 2
50/50
0.511
3151921BEARGRDN G2
50/50
1.07
970909AG2-566 GEN
Solar/Wind Harmer
4.453
316478AD1-087 GEN
Solar/Wind Harmer
3.774
316486AD2-202 GEN
Solar/Wind Harmer
1.105
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
5.021
3147133PAMPLIN
Solar/Wind Harmer
-0.1
971193AH1-056 GEN
Solar/Wind Harmer
20.089
963181AG1-167 GEN
Solar/Wind Harmer
2.971
959311AF2-222 GEN
Solar/Wind Harmer
31.9
970257AG2-171 GEN
Solar/Wind Harmer
11.387
315785AD2-033 C
Solar/Wind Harmer
6.821
964241AG1-285 GEN
Solar/Wind Harmer
22.951
316131AB2-060 GEN
Solar/Wind Harmer
3.123
316248AF1-058 C
Solar/Wind Harmer
0.798
960061AF2-297 GEN
Solar/Wind Harmer
13.248
3146776BUCKING
Solar/Wind Harmer
-0.009
971683AH1-343 GEN
Solar/Wind Harmer
10.06
316283AC2-100 C
Solar/Wind Harmer
1.21
3147043LAWRENC
Solar/Wind Harmer
-0.007
970221AG2-151 GEN
Solar/Wind Harmer
7.257
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
3.288
958131AF2-107 GEN
Solar/Wind Harmer
2.163
315773AC2-141 GEN
Solar/Wind Helper
2.93
3144873MCLAUGH
Solar/Wind Helper
0.003
3144536CHRHLND
Solar/Wind Helper
0.018
3145336SMITFLD
Solar/Wind Helper
0.047
3146456SLIGO L269
Solar/Wind Helper
0.116
CPLELTFEXP_CPLE->PJM
CLTF
2.619
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.946
LAGNLTFEXP_LAGN->PJM
CLTF
2.389
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.942
TVALTFEXP_TVA->PJM
CLTF
1.22
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.989
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.34
MECLTFEXP_MEC->PJM
CLTF
1.478
SIGELTFEXP_SIGE->PJM
CLTF
0.046
NYPJM->LTFIMP_NY
CLTF
0.449
LGEELTFEXP_LGEE->PJM
CLTF
0.593
WECLTFEXP_WEC->PJM
CLTF
0.305

Details for 6FINNEYWOOD-AG1-098 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-AG1-098 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.83 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:650.55
MW Contribution:29.36
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
0.346
970535AG2-341 GEN
50/50
1.993
970933AG2-581 GEN
Solar/Wind Harmer
27.859
970099AG2-077 GEN
Solar/Wind Harmer
36.299
939181AE1-148 GEN
Solar/Wind Harmer
6.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.689
316222AC1-221 GEN
Solar/Wind Harmer
0.447
942751AE2-291 GEN
Solar/Wind Harmer
5.336
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
971629AH1-314 GEN
50/50
5.006
315693AD1-088 GEN
Solar/Wind Harmer
18.25
957481AF2-042 GEN
Solar/Wind Harmer
90.747
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.071
316129AC1-054 GEN
Solar/Wind Harmer
0.427
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
971967AH1-528 GEN
Solar/Wind Harmer
55.717
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
316118AC1-105 GEN
Solar/Wind Harmer
0.376
970865AG2-541 GEN
Solar/Wind Harmer
4.593
316123AC1-075 GEN
Solar/Wind Harmer
0.152
970165AG2-112 GEN
Solar/Wind Harmer
0.903
970163AG2-111 GEN
Solar/Wind Harmer
0.862
970831AG2-522 GEN
Solar/Wind Harmer
4.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
316478AD1-087 GEN
Solar/Wind Harmer
1.094
316486AD2-202 GEN
Solar/Wind Harmer
0.321
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.01
971683AH1-343 GEN
Solar/Wind Harmer
5.256
316283AC2-100 C
Solar/Wind Harmer
0.206
316131AB2-060 GEN
Solar/Wind Harmer
0.208
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for 6FINNEYWOOD-AG1-098 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-AG1-098 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.27 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:635.93
MW Contribution:29.36
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
971629AH1-314 GEN
50/50
5.006
315693AD1-088 GEN
Solar/Wind Harmer
18.25
957481AF2-042 GEN
Solar/Wind Harmer
90.747
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.071
316129AC1-054 GEN
Solar/Wind Harmer
0.427
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
316118AC1-105 GEN
Solar/Wind Harmer
0.376
970865AG2-541 GEN
Solar/Wind Harmer
4.593
316123AC1-075 GEN
Solar/Wind Harmer
0.152
970165AG2-112 GEN
Solar/Wind Harmer
0.903
970163AG2-111 GEN
Solar/Wind Harmer
0.862
970831AG2-522 GEN
Solar/Wind Harmer
4.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3152661PLYWOOD A
50/50
0.346
970535AG2-341 GEN
50/50
1.993
970099AG2-077 GEN
Solar/Wind Harmer
36.299
939181AE1-148 GEN
Solar/Wind Harmer
6.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.689
316222AC1-221 GEN
Solar/Wind Harmer
0.447
942751AE2-291 GEN
Solar/Wind Harmer
5.336
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
316478AD1-087 GEN
Solar/Wind Harmer
1.094
316486AD2-202 GEN
Solar/Wind Harmer
0.321
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.01
971683AH1-343 GEN
Solar/Wind Harmer
5.256
316283AC2-100 C
Solar/Wind Harmer
0.206
316131AB2-060 GEN
Solar/Wind Harmer
0.208
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for 6FINNEYWOOD-AG1-098 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-AG1-098 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.84 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:767.78
MW Contribution:29.41
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.708
3151611KERR 4
50/50
0.302
3151621KERR 5
50/50
0.302
3151631KERR 6
50/50
0.302
3151641KERR 7
50/50
0.302
971967AH1-528 GEN
Solar/Wind Harmer
73.672
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.131
970865AG2-541 GEN
Solar/Wind Harmer
6.075
970413AG2-270 GEN
50/50
29.414
3151591KERR 2
50/50
0.302
316478AD1-087 GEN
Solar/Wind Harmer
3.055
316486AD2-202 GEN
Solar/Wind Harmer
0.895
316248AF1-058 C
Solar/Wind Harmer
0.559
960061AF2-297 GEN
Solar/Wind Harmer
9.268
971683AH1-343 GEN
Solar/Wind Harmer
6.951
316283AC2-100 C
Solar/Wind Harmer
1.124
316131AB2-060 GEN
Solar/Wind Harmer
0.808
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.542
3147133PAMPLIN
Solar/Wind Helper
1.062
316313AB2-026
Solar/Wind Helper
0.243
316258AE1-075 C
Solar/Wind Helper
0.219
316405AF2-144 C
Solar/Wind Helper
0.182
3152661PLYWOOD A
50/50
0.348
970535AG2-341 GEN
50/50
2.001
970933AG2-581 GEN
Solar/Wind Harmer
36.739
970099AG2-077 GEN
Solar/Wind Harmer
47.872
939181AE1-148 GEN
Solar/Wind Harmer
8.421
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.05
962561AG1-105 GEN
Solar/Wind Harmer
7.525
316222AC1-221 GEN
Solar/Wind Harmer
1.236
942751AE2-291 GEN
Solar/Wind Harmer
7.063
313527AB2-043 GEN
Solar/Wind Harmer
1.361
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.338
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.919
316123AC1-075 GEN
Solar/Wind Harmer
1.358
970165AG2-112 GEN
Solar/Wind Harmer
1.195
970163AG2-111 GEN
Solar/Wind Harmer
1.14
970831AG2-522 GEN
Solar/Wind Harmer
6.069
316239AB2-077_GEN
Solar/Wind Harmer
0.274
316238AB2-078_GEN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Harmer
1.371
270457AD2-023 GEN
Solar/Wind Harmer
0.695
270494AE1-108_GEN
Solar/Wind Helper
2.769
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3151531CLOVER1
50/50
6.74
3151601KERR 3
50/50
0.302
3151581KERR 1
50/50
0.108
315693AD1-088 GEN
Solar/Wind Harmer
21.388
957481AF2-042 GEN
Solar/Wind Harmer
119.681
315687AD1-152 GEN
Solar/Wind Harmer
3.524
316003AC1-222 GEN
Solar/Wind Harmer
1.683
970401AG2-262 GEN
Solar/Wind Harmer
0.932
971065AG2-659 GEN
Solar/Wind Harmer
6.697
316129AC1-054 GEN
Solar/Wind Harmer
1.121
316237AB2-079_GEN
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Helper
0.44
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
1.003
CPLELTFEXP_CPLE->PJM
CLTF
4.232
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.165
LAGNLTFEXP_LAGN->PJM
CLTF
2.703
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.92
TVALTFEXP_TVA->PJM
CLTF
1.347
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.6
MECLTFEXP_MEC->PJM
CLTF
1.297
SIGELTFEXP_SIGE->PJM
CLTF
0.038
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.461
WECLTFEXP_WEC->PJM
CLTF
0.241

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:196.14 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1331.14
MW Contribution:10.24
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.238
3144293JTRSVLE
50/50
0.706
970413AG2-270 GEN
50/50
10.245
3151591KERR 2
50/50
0.22
3151031BRUNSWICKG2
50/50
1.059
3151261ROARAP2
50/50
0.095
3150861SPRUNCD
50/50
0.364
966251AG1-494 GEN
50/50
1.288
970221AG2-151 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
0.132
3146926FARMVIL
Solar/Wind Harmer
0.176
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.159
316258AE1-075 C
Solar/Wind Harmer
0.19
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.801
970909AG2-566 GEN
Solar/Wind Harmer
2.396
3147133PAMPLIN
Solar/Wind Harmer
0.693
971193AH1-056 GEN
Solar/Wind Harmer
13.448
963181AG1-167 GEN
Solar/Wind Harmer
0.835
959311AF2-222 GEN
Solar/Wind Harmer
15.884
970257AG2-171 GEN
Solar/Wind Harmer
5.55
315785AD2-033 C
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
9.804
316131AB2-060 GEN
Solar/Wind Harmer
0.426
958131AF2-107 GEN
Solar/Wind Harmer
3.651
316478AD1-087 GEN
Solar/Wind Harmer
0.382
316486AD2-202 GEN
Solar/Wind Harmer
0.112
3147043LAWRENC
Solar/Wind Harmer
0.059
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.912
971683AH1-343 GEN
Solar/Wind Harmer
3.032
3144293JTRSVLE
50/50
0.706
3144293JTRSVLE
50/50
0.594
970535AG2-341 GEN
50/50
2.11
3152661PLYWOOD A
50/50
0.217
3151041BRUNSWICKG3
50/50
1.059
972187AH1-678 GEN
50/50
2.43
315242AE2-183_GT2
50/50
1.321
315241AE2-183_GT1
50/50
1.313
972185AH1-677 GEN
50/50
4.762
970533AG2-339 GEN
50/50
7.019
970531AG2-338 GEN
50/50
2.808
971489AH1-241 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
1.465
3146776BUCKING
Solar/Wind Harmer
0.119
315821AE2-092 GEN
Solar/Wind Harmer
0.014
970301AG2-198 GEN
Solar/Wind Harmer
9.583
3147133PAMPLIN
Solar/Wind Harmer
0.221
3147133PAMPLIN
Solar/Wind Harmer
0.176
958211AF2-115 GEN
Solar/Wind Harmer
2.506
963191AG1-168 GEN
Solar/Wind Harmer
0.835
971741AH1-377 GEN
Solar/Wind Harmer
20.177
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.401
971775AH1-396 GEN
Solar/Wind Harmer
0.278
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971223AH1-071 GEN
Solar/Wind Harmer
1.233
962561AG1-105 GEN
Solar/Wind Harmer
5.397
939181AE1-148 GEN
Solar/Wind Harmer
5.333
970099AG2-077 GEN
Solar/Wind Harmer
11.718
964791AG1-342 GEN
Solar/Wind Harmer
2.089
3146843MT LREL
Solar/Wind Harmer
0.109
3146843MT LREL
Solar/Wind Harmer
0.109
3143526WINTERP
Solar/Wind Harmer
0.504
970933AG2-581 GEN
Solar/Wind Harmer
7.465
316181AB2-040 GEN
Solar/Wind Harmer
0.116
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.078
966811AG1-552 GEN
Solar/Wind Harmer
0.843
3145593CAROLNA
Solar/Wind Harmer
0.097
3145783HORNRTN
Solar/Wind Harmer
1.361
3145783HORNRTN
Solar/Wind Harmer
1.089
3145783HORNRTN
Solar/Wind Harmer
0.34
3145783HORNRTN
Solar/Wind Harmer
0.136
316426AA2-053 GEN
Solar/Wind Harmer
0.256
3144356SAPONY
Solar/Wind Harmer
0.607
316274AC1-208 GEN
Solar/Wind Harmer
0.366
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.042
3145893MURPHYS
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
0.126
3145796HORNRTN
Solar/Wind Harmer
0.209
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
315742AE1-103 GEN
Solar/Wind Harmer
0.001
316222AC1-221 GEN
Solar/Wind Harmer
0.272
316065AD1-022 GEN
Solar/Wind Harmer
3.004
970657AG2-426 GEN
Solar/Wind Harmer
2.275
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
2.446
3146376EDENTON
Solar/Wind Harmer
0.286
3146376EDENTON
Solar/Wind Harmer
0.286
961601AG1-000A GEN
Solar/Wind Harmer
1.137
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3145493TOT1
Solar/Wind Harmer
0.148
3145453TOT5
Solar/Wind Harmer
0.089
3145603CNETO
Solar/Wind Harmer
0.059
3146386ELIZ CT
Solar/Wind Harmer
0.064
3145933PARMELE
Solar/Wind Harmer
0.127
3145933PARMELE
Solar/Wind Harmer
0.063
3130086AYDLETT
Solar/Wind Harmer
0.253
3137176SLIGO L2192
Solar/Wind Harmer
0.252
3146456SLIGO L269
Solar/Wind Harmer
1.121
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.035
316339AD2-160 GEN
Solar/Wind Harmer
0.103
3145506HICKORY
Solar/Wind Harmer
0.253
3145506HICKORY
Solar/Wind Harmer
0.152
3145506HICKORY
Solar/Wind Harmer
0.038
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.061
942751AE2-291 GEN
Solar/Wind Harmer
3.43
316240AF1-291 C
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.012
3150991CHESPKB
Adder
0.659
3150991CHESPKB
Adder
0.643
944641AF1-129 GEN
Adder
29.755
316236AE1-162_GEN
Solar/Wind Harmer
0
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.068
966001AG1-469 GEN
Solar/Wind Helper
0.206
3151931BEARGRDN S1
50/50
5.469
3151911BEARGRDN G1
50/50
4.238
3144293JTRSVLE
50/50
0.706
970119AG2-088 GEN
50/50
15.414
3151531CLOVER1
50/50
2.348
3151601KERR 3
50/50
0.22
3151581KERR 1
50/50
0.079
3147043LAWRENC
50/50
0.939
3151051BRUNSWICKS1
50/50
2.197
3151021BRUNSWICKG1
50/50
1.059
971451AH1-221 GEN
50/50
3.216
315243AE2-183_GT3
50/50
1.321
3151261ROARAP2
50/50
0.097
3150851SPRUNCC
50/50
0.364
972003AH1-546 GEN
Solar/Wind Harmer
18.676
971377AH1-170 GEN
Solar/Wind Harmer
4.327
3147623JAMES R
Solar/Wind Harmer
0.94
970937AG2-583 GEN
Solar/Wind Harmer
23.217
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.147
3146926FARMVIL
Solar/Wind Harmer
0.176
316336AC2-165 C
Solar/Wind Harmer
0.011
3143336POWHATN
Solar/Wind Harmer
4.472
963171AG1-166 GEN
Solar/Wind Harmer
1.114
971563AH1-280 GEN
Solar/Wind Harmer
2.228
970685AG2-442 GEN
Solar/Wind Harmer
14.313
962491AG1-098 GEN
Solar/Wind Harmer
7.815
315693AD1-088 GEN
Solar/Wind Harmer
6.344
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Harmer
0.116
957481AF2-042 GEN
Solar/Wind Harmer
29.295
970401AG2-262 GEN
Solar/Wind Harmer
0.638
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
4.184
3143526WINTERP
Solar/Wind Harmer
0.504
316129AC1-054 GEN
Solar/Wind Harmer
0.363
971795AH1-408 GEN
Solar/Wind Harmer
6.199
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.793
970919AG2-571 GEN
Solar/Wind Harmer
2.76
970087AG2-069 GEN
Solar/Wind Harmer
6.187
3145783HORNRTN
Solar/Wind Harmer
0.076
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
5.984
316023GEN1_S
Solar/Wind Harmer
0.164
939411AE1-173 GEN
Solar/Wind Harmer
30.681
316011AB1-132 GEN
Solar/Wind Harmer
1.286
962571AG1-106 GEN
Solar/Wind Harmer
1.007
3146263WOODLND
Solar/Wind Harmer
0.071
3145893MURPHYS
Solar/Wind Harmer
0.281
3145893MURPHYS
Solar/Wind Harmer
0.312
3145796HORNRTN
Solar/Wind Harmer
0.23
3145796HORNRTN
Solar/Wind Harmer
0.07
316212AC1-099_GEN
Solar/Wind Harmer
0.359
3146173TUNIS
Solar/Wind Harmer
0.069
3145823KELFORD
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
315722AD1-056 GEN
Solar/Wind Harmer
0.422
3146233WITAKRS
Solar/Wind Harmer
0.263
3146206CASHIE
Solar/Wind Harmer
0.065
971547AH1-271 GEN
Solar/Wind Harmer
1.396
970659AG2-427 GEN
Solar/Wind Harmer
3.146
316381AD1-082 GEN
Solar/Wind Harmer
0.068
970661AG2-428 GEN
Solar/Wind Harmer
6.453
3145663CRESWEL
Solar/Wind Harmer
0.181
971163AH1-040 GEN
Solar/Wind Harmer
5.167
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.052
316359AB2-059 GEN
Solar/Wind Harmer
0.231
316049AB1-081 GEN
Solar/Wind Harmer
0.368
3142053HEARTS
Solar/Wind Harmer
0.113
316093AE2-104_GEN
Solar/Wind Harmer
1.081
3130156CHOWAN
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3142543TWELFTH
Solar/Wind Harmer
0.006
3146516WINFALL
Solar/Wind Harmer
0.207
3146516WINFALL
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.283
316246AF1-032 C
Solar/Wind Harmer
0.029
3146293MARTNCO
Solar/Wind Harmer
0.059
316494AC1-189 GEN
Solar/Wind Harmer
0.214
3146456SLIGO L269
Solar/Wind Harmer
0.063
316388AE2-253 GEN
Solar/Wind Harmer
0.198
944591AF1-124 GEN
Solar/Wind Harmer
14.289
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
315671AE2-027_GEN
Solar/Wind Harmer
4.043
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
1.077
3145336SMITFLD
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
0.644
961611AG1-000B GEN
Solar/Wind Harmer
3.17
971647AH1-324 GEN
Solar/Wind Harmer
2.576
3143096IRON208
Adder
0.252
971069AG2-661 GEN
Solar/Wind Harmer
1.071
316458AB2-190 GEN2
Solar/Wind Harmer
0.323
970129AG2-093 GEN
Solar/Wind Harmer
1.71
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.903
3147666LOUISA
Solar/Wind Helper
0.521
313506AB2-031 GEN
Solar/Wind Harmer
0.248
970917AG2-570 GEN
Solar/Wind Harmer
6.901
316365GEN2_N
Solar/Wind Harmer
0.164
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
0.117
3145893MURPHYS
Solar/Wind Harmer
0.07
957521AF2-046 GEN
Solar/Wind Harmer
5.202
961681AG1-008 GEN
Solar/Wind Harmer
5.202
3145796HORNRTN
Solar/Wind Harmer
0.279
3145796HORNRTN
Solar/Wind Harmer
0.07
316210AC1-098 GEN
Solar/Wind Harmer
0.644
3146173TUNIS
Solar/Wind Harmer
0.069
316463AE2-346 GEN
Solar/Wind Harmer
0.059
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.732
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.069
316327AA2-057 GEN
Solar/Wind Harmer
0.102
315724AD1-057 GEN
Solar/Wind Harmer
0.25
3145273HOLLAND
Solar/Wind Harmer
0.05
3156021HOLLOMANSOL
Solar/Wind Harmer
0.301
3146233WITAKRS
Solar/Wind Harmer
0.331
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3146206CASHIE
Solar/Wind Harmer
0.065
315813AE1-149 C
Solar/Wind Harmer
3.482
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316283AC2-100 C
Solar/Wind Harmer
0.127
315839AE2-212 C
Solar/Wind Harmer
0.001
315737AD1-076 GEN
Solar/Wind Harmer
0.835
970661AG2-428 GEN
Solar/Wind Harmer
1.373
971157AH1-035 GEN
Solar/Wind Harmer
0.778
315614AA2-178 GEN
Solar/Wind Harmer
0.37
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.129
3146376EDENTON
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
4.548
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316435W1029_GEN3
Solar/Wind Harmer
0
965281AG1-393 GEN
Solar/Wind Harmer
0.68
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
316320Y1-086
Solar/Wind Harmer
0
3145933PARMELE
Solar/Wind Harmer
0.063
966801AG1-551 GEN
Solar/Wind Harmer
0.74
3146456SLIGO L269
Solar/Wind Harmer
0.063
971153AH1-033 GEN
Solar/Wind Harmer
0.732
944581AF1-123 GEN
Solar/Wind Harmer
14.239
944601AF1-125 GEN
Solar/Wind Harmer
14.019
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3151101ELIZAR3
Adder
5.847
3144873MCLAUGH
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.009
315773AC2-141 GEN
Solar/Wind Harmer
2.27
3145336SMITFLD
Solar/Wind Harmer
0.025
3151221GRAVEL6
Adder
4.403
3151171GRAVELC
Adder
0.847
961611AG1-000B GEN
Solar/Wind Harmer
1.612
3143096IRON208
Adder
0.252
3143096IRON208
Adder
0.247
315778AD1-151 GEN
Solar/Wind Harmer
4.818
970129AG2-093 GEN
Solar/Wind Harmer
3.634
970133AG2-095 GEN
Solar/Wind Harmer
0.576
316499AE2-029_GEN
Solar/Wind Helper
0.501
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.3
3148013FISHERV
Solar/Wind Helper
0.129
315616AA1-038_C
Solar/Wind Helper
0.524
972205AH1-687 GEN
50/50
20.67
316303AF2-085
50/50
2.055
3151541CLOVER2
50/50
2.336
3151611KERR 4
50/50
0.22
3151621KERR 5
50/50
0.22
3151631KERR 6
50/50
0.22
3151641KERR 7
50/50
0.22
963041AG1-153 GEN
50/50
2.144
315244AE2-183_ST
50/50
2.284
3151281ROARAP4
50/50
0.094
3151281ROARAP4
50/50
0.088
971285AH1-108 GEN
50/50
0.596
315779AE2-040
50/50
1.013
971447AH1-217 GEN
Solar/Wind Harmer
11.337
971845AH1-439 GEN
Solar/Wind Harmer
16.33
970285AG2-188 GEN
Solar/Wind Harmer
27.559
270494AE1-108_GEN
Solar/Wind Harmer
3.817
315657AE1-056 GEN
Solar/Wind Harmer
7.617
946301AF1-294 GEN
Solar/Wind Harmer
4.122
961791AG1-021 GEN
Solar/Wind Harmer
2.005
970683AG2-441 GEN
Solar/Wind Harmer
12.78
970681AG2-440 GEN
Solar/Wind Harmer
10.224
3144303KENBRDG
Solar/Wind Harmer
0.139
971443AH1-215 GEN
Solar/Wind Harmer
2.888
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.258
316233AE1-074 FULL
Solar/Wind Harmer
0.078
971281AH1-106 GEN
Solar/Wind Harmer
1.344
971283AH1-107 GEN
Solar/Wind Harmer
1.344
970831AG2-522 GEN
Solar/Wind Harmer
4.036
3147173SINAI
Solar/Wind Harmer
0.092
3147243WELCO
Solar/Wind Harmer
0.057
971967AH1-528 GEN
Solar/Wind Harmer
13.711
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
16.986
970673AG2-436 GEN
Solar/Wind Harmer
11.324
941031AE2-094 GEN
Solar/Wind Harmer
14.544
944011AF1-069 GEN
Solar/Wind Harmer
4.752
3137643SOCKMAN
Solar/Wind Harmer
0.315
970865AG2-541 GEN
Solar/Wind Harmer
2.702
970085AG2-068 GEN
Solar/Wind Harmer
4.124
970581AG2-369 GEN
Solar/Wind Harmer
3.547
315607AA1-063A GEN
Solar/Wind Harmer
0.154
3146043SEABORD
Solar/Wind Harmer
0.075
315814AE2-033 C
Solar/Wind Harmer
5.747
316315AB2-025 C
Solar/Wind Harmer
0.059
965291AG1-394 GEN
Solar/Wind Harmer
0.317
315652AC1-086 GEN
Solar/Wind Harmer
7.782
3145893MURPHYS
Solar/Wind Harmer
0.19
3145893MURPHYS
Solar/Wind Harmer
0.07
3145796HORNRTN
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.028
3146033SCOT NK
Solar/Wind Harmer
0.276
316123AC1-075 GEN
Solar/Wind Harmer
0.094
970165AG2-112 GEN
Solar/Wind Harmer
0.558
970163AG2-111 GEN
Solar/Wind Harmer
0.532
3145513AHOSKIE
Solar/Wind Harmer
0.143
3145513AHOSKIE
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3143316POE
Solar/Wind Harmer
0.269
316319Z2-044 C
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.065
970601AG2-382 GEN
Solar/Wind Harmer
2.444
315732AD1-074 GEN1
Solar/Wind Harmer
0.373
315733AD1-074 GEN2
Solar/Wind Harmer
0.373
315735AD1-075 GEN1
Solar/Wind Harmer
0.187
3130546PLYMOUTH
Solar/Wind Harmer
0.065
315816AE2-034 GEN
Solar/Wind Harmer
0.277
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.044
316311AC2-079 GEN
Solar/Wind Harmer
1.853
315835AF2-110_GEN
Solar/Wind Harmer
0.441
3130156CHOWAN
Solar/Wind Harmer
0.064
3130156CHOWAN
Solar/Wind Harmer
0.064
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
316321Z2-027
Solar/Wind Harmer
0.012
3145176PASQUOTANK
Solar/Wind Harmer
0.039
3146396TANGLEW
Solar/Wind Harmer
0.175
316420AA1-050 GEN
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.034
316305AF2-043 C
Solar/Wind Harmer
0.001
957861AF2-080 GEN
Solar/Wind Harmer
2.737
3146406KITTY HAWK
Solar/Wind Harmer
0.008
319010AE1-072 C
Solar/Wind Harmer
0.319
957871AF2-081 GEN
Solar/Wind Harmer
3.153
316005AA1-067
Solar/Wind Harmer
0.068
3145746EVERETS
Solar/Wind Harmer
0.252
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
970181AG2-120 GEN
Solar/Wind Harmer
0.787
3151081ELIZAR1
Adder
5.773
3151091ELIZAR2
Adder
5.672
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.68
3152601GOSPORTA
Adder
0.628
971445AH1-216 GEN
Solar/Wind Harmer
4.321
972265AH1-717 GEN
Adder
4.702
3151201GRAVEL4
Adder
4.408
3151191GRAVEL3
Adder
4.352
3151211GRAVEL5
Adder
4.352
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.323
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.077
3148013FISHERV
Solar/Wind Helper
0.074
3148463FAIRFLD
Solar/Wind Helper
0.116
CPLELTFEXP_CPLE->PJM
CLTF
4.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.705
LAGNLTFEXP_LAGN->PJM
CLTF
1.972
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.458
TVALTFEXP_TVA->PJM
CLTF
0.973
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.131
MECLTFEXP_MEC->PJM
CLTF
0.546
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.616
LGEELTFEXP_LGEE->PJM
CLTF
0.137
WECLTFEXP_WEC->PJM
CLTF
0.063

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:162.3 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1101.51
MW Contribution:9.03
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.823
3144293JTRSVLE
50/50
0.693
970535AG2-341 GEN
50/50
2.047
3152661PLYWOOD A
50/50
0.202
971489AH1-241 GEN
Solar/Wind Harmer
28.504
3146776BUCKING
Solar/Wind Harmer
1.881
3146776BUCKING
Solar/Wind Harmer
0.152
315821AE2-092 GEN
Solar/Wind Harmer
0.02
970301AG2-198 GEN
Solar/Wind Harmer
11.214
3147133PAMPLIN
Solar/Wind Harmer
0.26
3147133PAMPLIN
Solar/Wind Harmer
0.208
958211AF2-115 GEN
Solar/Wind Harmer
2.924
963191AG1-168 GEN
Solar/Wind Harmer
0.975
971741AH1-377 GEN
Solar/Wind Harmer
22.982
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.246
971775AH1-396 GEN
Solar/Wind Harmer
0.309
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
5.277
964791AG1-342 GEN
Solar/Wind Harmer
2.024
3146843MT LREL
Solar/Wind Harmer
0.105
3146843MT LREL
Solar/Wind Harmer
0.105
939181AE1-148 GEN
Solar/Wind Harmer
5.007
970099AG2-077 GEN
Solar/Wind Harmer
9.999
970933AG2-581 GEN
Solar/Wind Harmer
5.154
942751AE2-291 GEN
Solar/Wind Harmer
3.374
966001AG1-469 GEN
Solar/Wind Helper
0.159
3151931BEARGRDN S1
50/50
7.21
3151911BEARGRDN G1
50/50
5.587
3144293JTRSVLE
50/50
0.823
3151601KERR 3
50/50
0.202
3151581KERR 1
50/50
0.072
3151531CLOVER1
50/50
2.069
3147043LAWRENC
50/50
0.777
970937AG2-583 GEN
Solar/Wind Harmer
36.866
316336AC2-165 C
Solar/Wind Harmer
0.024
972003AH1-546 GEN
Solar/Wind Harmer
24.522
971377AH1-170 GEN
Solar/Wind Harmer
5.701
3147623JAMES R
Solar/Wind Harmer
1.238
316322AB2-045
Solar/Wind Harmer
0.004
3146776BUCKING
Solar/Wind Harmer
0.188
3146926FARMVIL
Solar/Wind Harmer
0.218
963171AG1-166 GEN
Solar/Wind Harmer
1.299
971563AH1-280 GEN
Solar/Wind Harmer
2.599
970685AG2-442 GEN
Solar/Wind Harmer
16.367
962491AG1-098 GEN
Solar/Wind Harmer
7.651
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
6.098
970401AG2-262 GEN
Solar/Wind Harmer
0.618
957481AF2-042 GEN
Solar/Wind Harmer
24.997
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.611
316129AC1-054 GEN
Solar/Wind Harmer
0.309
316003AC1-222 GEN
Solar/Wind Harmer
0.002
971795AH1-408 GEN
Solar/Wind Harmer
4.899
962751AG1-124 GEN
Solar/Wind Harmer
3.147
960081AF2-299 GEN
Solar/Wind Harmer
0.55
3151921BEARGRDN G2
50/50
5.587
3144293JTRSVLE
50/50
0.823
3151591KERR 2
50/50
0.202
970413AG2-270 GEN
50/50
9.029
966251AG1-494 GEN
50/50
1.716
970221AG2-151 GEN
Solar/Wind Harmer
28.504
3146776BUCKING
Solar/Wind Harmer
0.169
3146926FARMVIL
Solar/Wind Harmer
0.218
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
970909AG2-566 GEN
Solar/Wind Harmer
2.804
3147133PAMPLIN
Solar/Wind Harmer
0.818
971193AH1-056 GEN
Solar/Wind Harmer
15.872
963181AG1-167 GEN
Solar/Wind Harmer
0.975
959311AF2-222 GEN
Solar/Wind Harmer
17.841
970257AG2-171 GEN
Solar/Wind Harmer
6.184
315785AD2-033 C
Solar/Wind Harmer
1.488
958131AF2-107 GEN
Solar/Wind Harmer
4.835
964241AG1-285 GEN
Solar/Wind Harmer
10.382
316131AB2-060 GEN
Solar/Wind Harmer
0.438
972205AH1-687 GEN
50/50
27.249
3151611KERR 4
50/50
0.202
3151621KERR 5
50/50
0.202
3151631KERR 6
50/50
0.202
3151641KERR 7
50/50
0.202
3151541CLOVER2
50/50
2.059
971447AH1-217 GEN
Solar/Wind Harmer
15.037
971845AH1-439 GEN
Solar/Wind Harmer
20.916
970285AG2-188 GEN
Solar/Wind Harmer
35.131
270494AE1-108_GEN
Solar/Wind Harmer
5.032
315657AE1-056 GEN
Solar/Wind Harmer
8.99
946301AF1-294 GEN
Solar/Wind Harmer
4.808
961791AG1-021 GEN
Solar/Wind Harmer
2.339
970683AG2-441 GEN
Solar/Wind Harmer
14.613
970681AG2-440 GEN
Solar/Wind Harmer
11.691
3144303KENBRDG
Solar/Wind Harmer
0.154
971443AH1-215 GEN
Solar/Wind Harmer
3.209
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.244
3147173SINAI
Solar/Wind Harmer
0.084
3147243WELCO
Solar/Wind Harmer
0.052
970831AG2-522 GEN
Solar/Wind Harmer
3.381
970865AG2-541 GEN
Solar/Wind Harmer
2.545
316123AC1-075 GEN
Solar/Wind Harmer
0.091
970165AG2-112 GEN
Solar/Wind Harmer
0.539
970163AG2-111 GEN
Solar/Wind Harmer
0.514
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
316478AD1-087 GEN
Solar/Wind Harmer
0.337
316486AD2-202 GEN
Solar/Wind Harmer
0.099
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.582
3147043LAWRENC
Solar/Wind Harmer
0.049
971683AH1-343 GEN
Solar/Wind Harmer
2.828
3132273ORANGE
Solar/Wind Helper
0.023
CPLELTFEXP_CPLE->PJM
CLTF
2.979
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.201
LAGNLTFEXP_LAGN->PJM
CLTF
1.554
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.128
TVALTFEXP_TVA->PJM
CLTF
0.776
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.084
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.539
MECLTFEXP_MEC->PJM
CLTF
0.508
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.525
LGEELTFEXP_LGEE->PJM
CLTF
0.153
WECLTFEXP_WEC->PJM
CLTF
0.071

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.58 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:736.92
MW Contribution:8.22
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.083
3151541CLOVER2
50/50
1.876
3151611KERR 4
50/50
0.18
3151621KERR 5
50/50
0.18
3151631KERR 6
50/50
0.18
3151641KERR 7
50/50
0.18
316303AF2-085
50/50
1.546
3151281ROARAP4
50/50
0.07
3151281ROARAP4
50/50
0.066
971447AH1-217 GEN
Solar/Wind Harmer
11.004
971845AH1-439 GEN
Solar/Wind Harmer
15.632
970285AG2-188 GEN
Solar/Wind Harmer
26.316
270494AE1-108_GEN
Solar/Wind Harmer
3.693
315657AE1-056 GEN
Solar/Wind Harmer
6.997
946301AF1-294 GEN
Solar/Wind Harmer
3.764
961791AG1-021 GEN
Solar/Wind Harmer
1.831
970683AG2-441 GEN
Solar/Wind Harmer
11.558
970681AG2-440 GEN
Solar/Wind Harmer
9.247
3144303KENBRDG
Solar/Wind Harmer
0.124
971443AH1-215 GEN
Solar/Wind Harmer
2.576
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.212
970831AG2-522 GEN
Solar/Wind Harmer
3.201
3147173SINAI
Solar/Wind Harmer
0.074
3147243WELCO
Solar/Wind Harmer
0.046
316233AE1-074 FULL
Solar/Wind Harmer
0.058
971281AH1-106 GEN
Solar/Wind Harmer
1.006
971283AH1-107 GEN
Solar/Wind Harmer
1.006
970865AG2-541 GEN
Solar/Wind Harmer
2.17
316087AB2-174 GEN
Solar/Wind Harmer
0.002
971967AH1-528 GEN
Solar/Wind Harmer
9.597
3137643SOCKMAN
Solar/Wind Harmer
0.235
3138266HYDRAULIC
Solar/Wind Helper
0.021
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.08
3148013FISHERV
Solar/Wind Helper
0.077
3148463FAIRFLD
Solar/Wind Helper
0.119
3151931BEARGRDN S1
50/50
5.314
3151911BEARGRDN G1
50/50
4.118
3144293JTRSVLE
50/50
0.644
3151531CLOVER1
50/50
1.885
3151601KERR 3
50/50
0.18
3151581KERR 1
50/50
0.064
970119AG2-088 GEN
50/50
11.599
3147043LAWRENC
50/50
0.746
3151261ROARAP2
50/50
0.072
972003AH1-546 GEN
Solar/Wind Harmer
18.108
971377AH1-170 GEN
Solar/Wind Harmer
4.203
3147623JAMES R
Solar/Wind Harmer
0.913
970937AG2-583 GEN
Solar/Wind Harmer
22.204
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.14
3146926FARMVIL
Solar/Wind Harmer
0.165
316336AC2-165 C
Solar/Wind Harmer
0.01
3143336POWHATN
Solar/Wind Harmer
4.074
963171AG1-166 GEN
Solar/Wind Harmer
1.017
971563AH1-280 GEN
Solar/Wind Harmer
2.035
970685AG2-442 GEN
Solar/Wind Harmer
12.945
962491AG1-098 GEN
Solar/Wind Harmer
6.577
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
5.296
970401AG2-262 GEN
Solar/Wind Harmer
0.531
957481AF2-042 GEN
Solar/Wind Harmer
23.244
3143226MDLTHAN
Solar/Wind Harmer
0.087
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.352
316129AC1-054 GEN
Solar/Wind Harmer
0.289
971795AH1-408 GEN
Solar/Wind Harmer
4.849
3143526WINTERP
Solar/Wind Harmer
0.377
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.595
3145783HORNRTN
Solar/Wind Harmer
0.057
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.752
3144293JTRSVLE
50/50
0.644
3144293JTRSVLE
50/50
0.543
970535AG2-341 GEN
50/50
1.768
3152661PLYWOOD A
50/50
0.177
971489AH1-241 GEN
Solar/Wind Harmer
21.013
3146776BUCKING
Solar/Wind Harmer
1.404
3146776BUCKING
Solar/Wind Harmer
0.114
315821AE2-092 GEN
Solar/Wind Harmer
0.014
970301AG2-198 GEN
Solar/Wind Harmer
8.767
3147133PAMPLIN
Solar/Wind Harmer
0.203
3147133PAMPLIN
Solar/Wind Harmer
0.162
958211AF2-115 GEN
Solar/Wind Harmer
2.289
963191AG1-168 GEN
Solar/Wind Harmer
0.763
971741AH1-377 GEN
Solar/Wind Harmer
18.217
316034AC1-036 C
Solar/Wind Harmer
0.011
970323AG2-213 GEN
Solar/Wind Harmer
6.61
971775AH1-396 GEN
Solar/Wind Harmer
0.248
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
4.515
939181AE1-148 GEN
Solar/Wind Harmer
4.407
964791AG1-342 GEN
Solar/Wind Harmer
1.738
3146843MT LREL
Solar/Wind Harmer
0.09
3146843MT LREL
Solar/Wind Harmer
0.09
970099AG2-077 GEN
Solar/Wind Harmer
9.298
971223AH1-071 GEN
Solar/Wind Harmer
0.928
3143526WINTERP
Solar/Wind Harmer
0.377
970933AG2-581 GEN
Solar/Wind Harmer
5.476
316181AB2-040 GEN
Solar/Wind Harmer
0.087
3145593CAROLNA
Solar/Wind Harmer
0.058
3145593CAROLNA
Solar/Wind Harmer
0.058
966811AG1-552 GEN
Solar/Wind Harmer
0.627
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.01
3145783HORNRTN
Solar/Wind Harmer
0.808
3145783HORNRTN
Solar/Wind Harmer
0.253
3145783HORNRTN
Solar/Wind Harmer
0.101
966001AG1-469 GEN
Solar/Wind Helper
0.19
3151921BEARGRDN G2
50/50
4.118
3144293JTRSVLE
50/50
0.644
970413AG2-270 GEN
50/50
8.224
3151591KERR 2
50/50
0.18
966251AG1-494 GEN
50/50
1.173
3151261ROARAP2
50/50
0.07
970221AG2-151 GEN
Solar/Wind Harmer
21.013
3146776BUCKING
Solar/Wind Harmer
0.126
3146926FARMVIL
Solar/Wind Harmer
0.165
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.144
316258AE1-075 C
Solar/Wind Harmer
0.173
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.463
970909AG2-566 GEN
Solar/Wind Harmer
2.192
3147133PAMPLIN
Solar/Wind Harmer
0.637
971193AH1-056 GEN
Solar/Wind Harmer
12.353
963181AG1-167 GEN
Solar/Wind Harmer
0.763
959311AF2-222 GEN
Solar/Wind Harmer
14.242
970257AG2-171 GEN
Solar/Wind Harmer
4.957
315785AD2-033 C
Solar/Wind Harmer
1.2
964241AG1-285 GEN
Solar/Wind Harmer
8.548
958131AF2-107 GEN
Solar/Wind Harmer
3.44
316131AB2-060 GEN
Solar/Wind Harmer
0.366
316478AD1-087 GEN
Solar/Wind Harmer
0.307
316486AD2-202 GEN
Solar/Wind Harmer
0.09
3147043LAWRENC
Solar/Wind Harmer
0.047
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.155
971683AH1-343 GEN
Solar/Wind Harmer
2.44
313506AB2-031 GEN
Solar/Wind Harmer
0.186
316499AE2-029_GEN
Solar/Wind Helper
0.505
3148013FISHERV
Solar/Wind Helper
0.133
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.54
CPLELTFEXP_CPLE->PJM
CLTF
2.992
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.238
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.029
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.072
LAGNLTFEXP_LAGN->PJM
CLTF
1.122
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.815
TVALTFEXP_TVA->PJM
CLTF
0.547
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.673
MECLTFEXP_MEC->PJM
CLTF
0.138
SIGELTFEXP_SIGE->PJM
CLTF
0.002
NYPJM->LTFIMP_NY
CLTF
0.391

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:198.54 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:1313.88
MW Contribution:10.24
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.469
3151911BEARGRDN G1
50/50
4.238
3144293JTRSVLE
50/50
0.706
970119AG2-088 GEN
50/50
15.414
3151531CLOVER1
50/50
2.348
3151601KERR 3
50/50
0.22
3151581KERR 1
50/50
0.079
3147043LAWRENC
50/50
0.939
3151051BRUNSWICKS1
50/50
2.197
3151021BRUNSWICKG1
50/50
1.059
971451AH1-221 GEN
50/50
3.216
315243AE2-183_GT3
50/50
1.321
3151261ROARAP2
50/50
0.097
3150851SPRUNCC
50/50
0.364
972003AH1-546 GEN
Solar/Wind Harmer
18.676
971377AH1-170 GEN
Solar/Wind Harmer
4.327
3147623JAMES R
Solar/Wind Harmer
0.94
970937AG2-583 GEN
Solar/Wind Harmer
23.217
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.147
3146926FARMVIL
Solar/Wind Harmer
0.176
316336AC2-165 C
Solar/Wind Harmer
0.011
3143336POWHATN
Solar/Wind Harmer
4.472
963171AG1-166 GEN
Solar/Wind Harmer
1.114
971563AH1-280 GEN
Solar/Wind Harmer
2.228
970685AG2-442 GEN
Solar/Wind Harmer
14.313
962491AG1-098 GEN
Solar/Wind Harmer
7.815
315693AD1-088 GEN
Solar/Wind Harmer
6.344
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Harmer
0.116
957481AF2-042 GEN
Solar/Wind Harmer
29.295
970401AG2-262 GEN
Solar/Wind Harmer
0.638
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
4.184
3143526WINTERP
Solar/Wind Harmer
0.504
316129AC1-054 GEN
Solar/Wind Harmer
0.363
971795AH1-408 GEN
Solar/Wind Harmer
6.199
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.793
970919AG2-571 GEN
Solar/Wind Harmer
2.76
970087AG2-069 GEN
Solar/Wind Harmer
6.187
3145783HORNRTN
Solar/Wind Harmer
0.076
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
5.984
316023GEN1_S
Solar/Wind Harmer
0.164
939411AE1-173 GEN
Solar/Wind Harmer
30.681
316011AB1-132 GEN
Solar/Wind Harmer
1.286
962571AG1-106 GEN
Solar/Wind Harmer
1.007
3146263WOODLND
Solar/Wind Harmer
0.071
3145893MURPHYS
Solar/Wind Harmer
0.281
3145893MURPHYS
Solar/Wind Harmer
0.312
3145796HORNRTN
Solar/Wind Harmer
0.23
3145796HORNRTN
Solar/Wind Harmer
0.07
316212AC1-099_GEN
Solar/Wind Harmer
0.359
3146173TUNIS
Solar/Wind Harmer
0.069
3145823KELFORD
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
315722AD1-056 GEN
Solar/Wind Harmer
0.422
3146233WITAKRS
Solar/Wind Harmer
0.263
3146206CASHIE
Solar/Wind Harmer
0.065
971547AH1-271 GEN
Solar/Wind Harmer
1.396
970659AG2-427 GEN
Solar/Wind Harmer
3.146
316381AD1-082 GEN
Solar/Wind Harmer
0.068
970661AG2-428 GEN
Solar/Wind Harmer
6.453
3145663CRESWEL
Solar/Wind Harmer
0.181
971163AH1-040 GEN
Solar/Wind Harmer
5.167
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.052
316359AB2-059 GEN
Solar/Wind Harmer
0.231
316049AB1-081 GEN
Solar/Wind Harmer
0.368
3142053HEARTS
Solar/Wind Harmer
0.113
316093AE2-104_GEN
Solar/Wind Harmer
1.081
3130156CHOWAN
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
3144293JTRSVLE
50/50
0.706
3144293JTRSVLE
50/50
0.594
970535AG2-341 GEN
50/50
2.11
3152661PLYWOOD A
50/50
0.217
3151041BRUNSWICKG3
50/50
1.059
972187AH1-678 GEN
50/50
2.43
315242AE2-183_GT2
50/50
1.321
315241AE2-183_GT1
50/50
1.313
972185AH1-677 GEN
50/50
4.762
970533AG2-339 GEN
50/50
7.019
970531AG2-338 GEN
50/50
2.808
971489AH1-241 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
1.465
3146776BUCKING
Solar/Wind Harmer
0.119
315821AE2-092 GEN
Solar/Wind Harmer
0.014
970301AG2-198 GEN
Solar/Wind Harmer
9.583
3147133PAMPLIN
Solar/Wind Harmer
0.221
3147133PAMPLIN
Solar/Wind Harmer
0.176
958211AF2-115 GEN
Solar/Wind Harmer
2.506
963191AG1-168 GEN
Solar/Wind Harmer
0.835
971741AH1-377 GEN
Solar/Wind Harmer
20.177
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.401
971775AH1-396 GEN
Solar/Wind Harmer
0.278
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971223AH1-071 GEN
Solar/Wind Harmer
1.233
962561AG1-105 GEN
Solar/Wind Harmer
5.397
939181AE1-148 GEN
Solar/Wind Harmer
5.333
970099AG2-077 GEN
Solar/Wind Harmer
11.718
964791AG1-342 GEN
Solar/Wind Harmer
2.089
3146843MT LREL
Solar/Wind Harmer
0.109
3146843MT LREL
Solar/Wind Harmer
0.109
3143526WINTERP
Solar/Wind Harmer
0.504
970933AG2-581 GEN
Solar/Wind Harmer
7.465
316181AB2-040 GEN
Solar/Wind Harmer
0.116
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.078
966811AG1-552 GEN
Solar/Wind Harmer
0.843
3145593CAROLNA
Solar/Wind Harmer
0.097
3145783HORNRTN
Solar/Wind Harmer
1.361
3145783HORNRTN
Solar/Wind Harmer
1.089
3145783HORNRTN
Solar/Wind Harmer
0.34
3145783HORNRTN
Solar/Wind Harmer
0.136
316426AA2-053 GEN
Solar/Wind Harmer
0.256
3144356SAPONY
Solar/Wind Harmer
0.607
316274AC1-208 GEN
Solar/Wind Harmer
0.366
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.042
3145893MURPHYS
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
0.126
3145796HORNRTN
Solar/Wind Harmer
0.209
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
315742AE1-103 GEN
Solar/Wind Harmer
0.001
316222AC1-221 GEN
Solar/Wind Harmer
0.272
316065AD1-022 GEN
Solar/Wind Harmer
3.004
970657AG2-426 GEN
Solar/Wind Harmer
2.275
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
2.446
3146376EDENTON
Solar/Wind Harmer
0.286
3146376EDENTON
Solar/Wind Harmer
0.286
3151921BEARGRDN G2
50/50
4.238
3144293JTRSVLE
50/50
0.706
970413AG2-270 GEN
50/50
10.245
3151591KERR 2
50/50
0.22
3151031BRUNSWICKG2
50/50
1.059
3151261ROARAP2
50/50
0.095
3150861SPRUNCD
50/50
0.364
966251AG1-494 GEN
50/50
1.288
970221AG2-151 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
0.132
3146926FARMVIL
Solar/Wind Harmer
0.176
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.159
316258AE1-075 C
Solar/Wind Harmer
0.19
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.801
970909AG2-566 GEN
Solar/Wind Harmer
2.396
3147133PAMPLIN
Solar/Wind Harmer
0.693
971193AH1-056 GEN
Solar/Wind Harmer
13.448
963181AG1-167 GEN
Solar/Wind Harmer
0.835
959311AF2-222 GEN
Solar/Wind Harmer
15.884
970257AG2-171 GEN
Solar/Wind Harmer
5.55
315785AD2-033 C
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
9.804
316131AB2-060 GEN
Solar/Wind Harmer
0.426
958131AF2-107 GEN
Solar/Wind Harmer
3.651
316478AD1-087 GEN
Solar/Wind Harmer
0.382
316486AD2-202 GEN
Solar/Wind Harmer
0.112
3147043LAWRENC
Solar/Wind Harmer
0.059
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.912
971683AH1-343 GEN
Solar/Wind Harmer
3.032
313506AB2-031 GEN
Solar/Wind Harmer
0.248
970917AG2-570 GEN
Solar/Wind Harmer
6.901
316365GEN2_N
Solar/Wind Harmer
0.164
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
0.117
3145893MURPHYS
Solar/Wind Harmer
0.07
957521AF2-046 GEN
Solar/Wind Harmer
5.202
961681AG1-008 GEN
Solar/Wind Harmer
5.202
3145796HORNRTN
Solar/Wind Harmer
0.279
3145796HORNRTN
Solar/Wind Harmer
0.07
316210AC1-098 GEN
Solar/Wind Harmer
0.644
3146173TUNIS
Solar/Wind Harmer
0.069
316463AE2-346 GEN
Solar/Wind Harmer
0.059
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.732
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.069
316327AA2-057 GEN
Solar/Wind Harmer
0.102
315724AD1-057 GEN
Solar/Wind Harmer
0.25
3145273HOLLAND
Solar/Wind Harmer
0.05
3156021HOLLOMANSOL
Solar/Wind Harmer
0.301
3146233WITAKRS
Solar/Wind Harmer
0.331
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3146206CASHIE
Solar/Wind Harmer
0.065
315813AE1-149 C
Solar/Wind Harmer
3.482
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316283AC2-100 C
Solar/Wind Harmer
0.127
315839AE2-212 C
Solar/Wind Harmer
0.001
315737AD1-076 GEN
Solar/Wind Harmer
0.835
970661AG2-428 GEN
Solar/Wind Harmer
1.373
971157AH1-035 GEN
Solar/Wind Harmer
0.778
315614AA2-178 GEN
Solar/Wind Harmer
0.37
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.129
3146376EDENTON
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
1.137
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3142543TWELFTH
Solar/Wind Harmer
0.006
3146516WINFALL
Solar/Wind Harmer
0.207
3146516WINFALL
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.064
972205AH1-687 GEN
50/50
20.67
316303AF2-085
50/50
2.055
3151541CLOVER2
50/50
2.336
3151611KERR 4
50/50
0.22
3151621KERR 5
50/50
0.22
3151631KERR 6
50/50
0.22
3151641KERR 7
50/50
0.22
963041AG1-153 GEN
50/50
2.144
315244AE2-183_ST
50/50
2.284
3151281ROARAP4
50/50
0.094
3151281ROARAP4
50/50
0.088
971285AH1-108 GEN
50/50
0.596
315779AE2-040
50/50
1.013
971447AH1-217 GEN
Solar/Wind Harmer
11.337
971845AH1-439 GEN
Solar/Wind Harmer
16.33
970285AG2-188 GEN
Solar/Wind Harmer
27.559
270494AE1-108_GEN
Solar/Wind Harmer
3.817
315657AE1-056 GEN
Solar/Wind Harmer
7.617
946301AF1-294 GEN
Solar/Wind Harmer
4.122
961791AG1-021 GEN
Solar/Wind Harmer
2.005
970683AG2-441 GEN
Solar/Wind Harmer
12.78
970681AG2-440 GEN
Solar/Wind Harmer
10.224
3144303KENBRDG
Solar/Wind Harmer
0.139
971443AH1-215 GEN
Solar/Wind Harmer
2.888
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.258
316233AE1-074 FULL
Solar/Wind Harmer
0.078
971281AH1-106 GEN
Solar/Wind Harmer
1.344
971283AH1-107 GEN
Solar/Wind Harmer
1.344
970831AG2-522 GEN
Solar/Wind Harmer
4.036
3147173SINAI
Solar/Wind Harmer
0.092
3147243WELCO
Solar/Wind Harmer
0.057
971967AH1-528 GEN
Solar/Wind Harmer
13.711
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
16.986
970673AG2-436 GEN
Solar/Wind Harmer
11.324
941031AE2-094 GEN
Solar/Wind Harmer
14.544
944011AF1-069 GEN
Solar/Wind Harmer
4.752
3137643SOCKMAN
Solar/Wind Harmer
0.315
970865AG2-541 GEN
Solar/Wind Harmer
2.702
970085AG2-068 GEN
Solar/Wind Harmer
4.124
970581AG2-369 GEN
Solar/Wind Harmer
3.547
315607AA1-063A GEN
Solar/Wind Harmer
0.154
3146043SEABORD
Solar/Wind Harmer
0.075
315814AE2-033 C
Solar/Wind Harmer
5.747
316315AB2-025 C
Solar/Wind Harmer
0.059
965291AG1-394 GEN
Solar/Wind Harmer
0.317
315652AC1-086 GEN
Solar/Wind Harmer
7.782
3145893MURPHYS
Solar/Wind Harmer
0.19
3145893MURPHYS
Solar/Wind Harmer
0.07
3145796HORNRTN
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.028
3146033SCOT NK
Solar/Wind Harmer
0.276
316123AC1-075 GEN
Solar/Wind Harmer
0.094
970165AG2-112 GEN
Solar/Wind Harmer
0.558
970163AG2-111 GEN
Solar/Wind Harmer
0.532
3145513AHOSKIE
Solar/Wind Harmer
0.143
3145513AHOSKIE
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3143316POE
Solar/Wind Harmer
0.269
316319Z2-044 C
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.065
970601AG2-382 GEN
Solar/Wind Harmer
2.444
315732AD1-074 GEN1
Solar/Wind Harmer
0.373
315733AD1-074 GEN2
Solar/Wind Harmer
0.373
315735AD1-075 GEN1
Solar/Wind Harmer
0.187
3130546PLYMOUTH
Solar/Wind Harmer
0.065
315816AE2-034 GEN
Solar/Wind Harmer
0.277
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.044
316311AC2-079 GEN
Solar/Wind Harmer
1.853
315835AF2-110_GEN
Solar/Wind Harmer
0.441
3130156CHOWAN
Solar/Wind Harmer
0.064
3130156CHOWAN
Solar/Wind Harmer
0.064
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
316321Z2-027
Solar/Wind Harmer
0.012
3145176PASQUOTANK
Solar/Wind Harmer
0.039
3146396TANGLEW
Solar/Wind Harmer
0.175
316420AA1-050 GEN
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.034
316305AF2-043 C
Solar/Wind Harmer
0.001
957861AF2-080 GEN
Solar/Wind Harmer
2.737
3146406KITTY HAWK
Solar/Wind Harmer
0.008
319010AE1-072 C
Solar/Wind Harmer
0.319
957871AF2-081 GEN
Solar/Wind Harmer
3.153
316005AA1-067
Solar/Wind Harmer
0.068
3145746EVERETS
Solar/Wind Harmer
0.252
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
970181AG2-120 GEN
Solar/Wind Harmer
0.787
3151081ELIZAR1
Adder
5.773
3151091ELIZAR2
Adder
5.672
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.68
3152601GOSPORTA
Adder
0.628
971445AH1-216 GEN
Solar/Wind Harmer
4.321
972265AH1-717 GEN
Adder
4.702
3151201GRAVEL4
Adder
4.408
3151191GRAVEL3
Adder
4.352
3151211GRAVEL5
Adder
4.352
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.323
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.077
3148013FISHERV
Solar/Wind Helper
0.074
3148463FAIRFLD
Solar/Wind Helper
0.116
3145493TOT1
Solar/Wind Harmer
0.283
316246AF1-032 C
Solar/Wind Harmer
0.029
3146293MARTNCO
Solar/Wind Harmer
0.059
316494AC1-189 GEN
Solar/Wind Harmer
0.214
3146456SLIGO L269
Solar/Wind Harmer
0.063
316388AE2-253 GEN
Solar/Wind Harmer
0.198
944591AF1-124 GEN
Solar/Wind Harmer
14.289
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
315671AE2-027_GEN
Solar/Wind Harmer
4.043
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
1.077
3145336SMITFLD
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
0.644
961611AG1-000B GEN
Solar/Wind Harmer
3.17
971647AH1-324 GEN
Solar/Wind Harmer
2.576
3143096IRON208
Adder
0.252
971069AG2-661 GEN
Solar/Wind Harmer
1.071
316458AB2-190 GEN2
Solar/Wind Harmer
0.323
970129AG2-093 GEN
Solar/Wind Harmer
1.71
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.903
3147666LOUISA
Solar/Wind Helper
0.521
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3145493TOT1
Solar/Wind Harmer
0.148
3145453TOT5
Solar/Wind Harmer
0.089
3145603CNETO
Solar/Wind Harmer
0.059
3146386ELIZ CT
Solar/Wind Harmer
0.064
3145933PARMELE
Solar/Wind Harmer
0.127
3145933PARMELE
Solar/Wind Harmer
0.063
3130086AYDLETT
Solar/Wind Harmer
0.253
3137176SLIGO L2192
Solar/Wind Harmer
0.252
3146456SLIGO L269
Solar/Wind Harmer
1.121
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.035
316339AD2-160 GEN
Solar/Wind Harmer
0.103
3145506HICKORY
Solar/Wind Harmer
0.253
3145506HICKORY
Solar/Wind Harmer
0.152
3145506HICKORY
Solar/Wind Harmer
0.038
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.061
942751AE2-291 GEN
Solar/Wind Harmer
3.43
316240AF1-291 C
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.012
3150991CHESPKB
Adder
0.659
3150991CHESPKB
Adder
0.643
944641AF1-129 GEN
Adder
29.755
316236AE1-162_GEN
Solar/Wind Harmer
0
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.068
966001AG1-469 GEN
Solar/Wind Helper
0.206
961601AG1-000A GEN
Solar/Wind Harmer
4.548
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316435W1029_GEN3
Solar/Wind Harmer
0
965281AG1-393 GEN
Solar/Wind Harmer
0.68
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
316320Y1-086
Solar/Wind Harmer
0
3145933PARMELE
Solar/Wind Harmer
0.063
966801AG1-551 GEN
Solar/Wind Harmer
0.74
3146456SLIGO L269
Solar/Wind Harmer
0.063
971153AH1-033 GEN
Solar/Wind Harmer
0.732
944581AF1-123 GEN
Solar/Wind Harmer
14.239
944601AF1-125 GEN
Solar/Wind Harmer
14.019
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3151101ELIZAR3
Adder
5.847
3144873MCLAUGH
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.009
315773AC2-141 GEN
Solar/Wind Harmer
2.27
3145336SMITFLD
Solar/Wind Harmer
0.025
3151221GRAVEL6
Adder
4.403
3151171GRAVELC
Adder
0.847
961611AG1-000B GEN
Solar/Wind Harmer
1.612
3143096IRON208
Adder
0.252
3143096IRON208
Adder
0.247
315778AD1-151 GEN
Solar/Wind Harmer
4.818
970129AG2-093 GEN
Solar/Wind Harmer
3.634
970133AG2-095 GEN
Solar/Wind Harmer
0.576
316499AE2-029_GEN
Solar/Wind Helper
0.501
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.3
3148013FISHERV
Solar/Wind Helper
0.129
315616AA1-038_C
Solar/Wind Helper
0.524
CPLELTFEXP_CPLE->PJM
CLTF
4.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.705
LAGNLTFEXP_LAGN->PJM
CLTF
1.972
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.458
TVALTFEXP_TVA->PJM
CLTF
0.973
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.131
MECLTFEXP_MEC->PJM
CLTF
0.546
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.616
LGEELTFEXP_LGEE->PJM
CLTF
0.137
WECLTFEXP_WEC->PJM
CLTF
0.063

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:163.84 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:1084.23
MW Contribution:9.03
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
27.249
3151611KERR 4
50/50
0.202
3151621KERR 5
50/50
0.202
3151631KERR 6
50/50
0.202
3151641KERR 7
50/50
0.202
3151541CLOVER2
50/50
2.059
971447AH1-217 GEN
Solar/Wind Harmer
15.037
971845AH1-439 GEN
Solar/Wind Harmer
20.916
970285AG2-188 GEN
Solar/Wind Harmer
35.131
270494AE1-108_GEN
Solar/Wind Harmer
5.032
315657AE1-056 GEN
Solar/Wind Harmer
8.99
946301AF1-294 GEN
Solar/Wind Harmer
4.808
961791AG1-021 GEN
Solar/Wind Harmer
2.339
970683AG2-441 GEN
Solar/Wind Harmer
14.613
970681AG2-440 GEN
Solar/Wind Harmer
11.691
3144303KENBRDG
Solar/Wind Harmer
0.154
971443AH1-215 GEN
Solar/Wind Harmer
3.209
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.244
3147173SINAI
Solar/Wind Harmer
0.084
3147243WELCO
Solar/Wind Harmer
0.052
970831AG2-522 GEN
Solar/Wind Harmer
3.381
970865AG2-541 GEN
Solar/Wind Harmer
2.545
316123AC1-075 GEN
Solar/Wind Harmer
0.091
970165AG2-112 GEN
Solar/Wind Harmer
0.539
970163AG2-111 GEN
Solar/Wind Harmer
0.514
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
3151931BEARGRDN S1
50/50
7.21
3151911BEARGRDN G1
50/50
5.587
3144293JTRSVLE
50/50
0.823
3151601KERR 3
50/50
0.202
3151581KERR 1
50/50
0.072
3151531CLOVER1
50/50
2.069
3147043LAWRENC
50/50
0.777
970937AG2-583 GEN
Solar/Wind Harmer
36.866
316336AC2-165 C
Solar/Wind Harmer
0.024
972003AH1-546 GEN
Solar/Wind Harmer
24.522
971377AH1-170 GEN
Solar/Wind Harmer
5.701
3147623JAMES R
Solar/Wind Harmer
1.238
316322AB2-045
Solar/Wind Harmer
0.004
3146776BUCKING
Solar/Wind Harmer
0.188
3146926FARMVIL
Solar/Wind Harmer
0.218
963171AG1-166 GEN
Solar/Wind Harmer
1.299
971563AH1-280 GEN
Solar/Wind Harmer
2.599
970685AG2-442 GEN
Solar/Wind Harmer
16.367
962491AG1-098 GEN
Solar/Wind Harmer
7.651
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
6.098
970401AG2-262 GEN
Solar/Wind Harmer
0.618
957481AF2-042 GEN
Solar/Wind Harmer
24.997
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.611
316129AC1-054 GEN
Solar/Wind Harmer
0.309
316003AC1-222 GEN
Solar/Wind Harmer
0.002
971795AH1-408 GEN
Solar/Wind Harmer
4.899
962751AG1-124 GEN
Solar/Wind Harmer
3.147
960081AF2-299 GEN
Solar/Wind Harmer
0.55
3144293JTRSVLE
50/50
0.823
3144293JTRSVLE
50/50
0.693
970535AG2-341 GEN
50/50
2.047
3152661PLYWOOD A
50/50
0.202
971489AH1-241 GEN
Solar/Wind Harmer
28.504
3146776BUCKING
Solar/Wind Harmer
1.881
3146776BUCKING
Solar/Wind Harmer
0.152
315821AE2-092 GEN
Solar/Wind Harmer
0.02
970301AG2-198 GEN
Solar/Wind Harmer
11.214
3147133PAMPLIN
Solar/Wind Harmer
0.26
3147133PAMPLIN
Solar/Wind Harmer
0.208
958211AF2-115 GEN
Solar/Wind Harmer
2.924
963191AG1-168 GEN
Solar/Wind Harmer
0.975
971741AH1-377 GEN
Solar/Wind Harmer
22.982
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.246
971775AH1-396 GEN
Solar/Wind Harmer
0.309
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
5.277
964791AG1-342 GEN
Solar/Wind Harmer
2.024
3146843MT LREL
Solar/Wind Harmer
0.105
3146843MT LREL
Solar/Wind Harmer
0.105
939181AE1-148 GEN
Solar/Wind Harmer
5.007
970099AG2-077 GEN
Solar/Wind Harmer
9.999
970933AG2-581 GEN
Solar/Wind Harmer
5.154
942751AE2-291 GEN
Solar/Wind Harmer
3.374
966001AG1-469 GEN
Solar/Wind Helper
0.159
3151921BEARGRDN G2
50/50
5.587
3144293JTRSVLE
50/50
0.823
3151591KERR 2
50/50
0.202
970413AG2-270 GEN
50/50
9.029
966251AG1-494 GEN
50/50
1.716
970221AG2-151 GEN
Solar/Wind Harmer
28.504
3146776BUCKING
Solar/Wind Harmer
0.169
3146926FARMVIL
Solar/Wind Harmer
0.218
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
970909AG2-566 GEN
Solar/Wind Harmer
2.804
3147133PAMPLIN
Solar/Wind Harmer
0.818
971193AH1-056 GEN
Solar/Wind Harmer
15.872
963181AG1-167 GEN
Solar/Wind Harmer
0.975
959311AF2-222 GEN
Solar/Wind Harmer
17.841
970257AG2-171 GEN
Solar/Wind Harmer
6.184
315785AD2-033 C
Solar/Wind Harmer
1.488
958131AF2-107 GEN
Solar/Wind Harmer
4.835
964241AG1-285 GEN
Solar/Wind Harmer
10.382
316131AB2-060 GEN
Solar/Wind Harmer
0.438
316478AD1-087 GEN
Solar/Wind Harmer
0.337
316486AD2-202 GEN
Solar/Wind Harmer
0.099
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.582
3147043LAWRENC
Solar/Wind Harmer
0.049
971683AH1-343 GEN
Solar/Wind Harmer
2.828
3132273ORANGE
Solar/Wind Helper
0.023
CPLELTFEXP_CPLE->PJM
CLTF
2.979
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.201
LAGNLTFEXP_LAGN->PJM
CLTF
1.554
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.128
TVALTFEXP_TVA->PJM
CLTF
0.776
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.084
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.539
MECLTFEXP_MEC->PJM
CLTF
0.508
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.525
LGEELTFEXP_LGEE->PJM
CLTF
0.153
WECLTFEXP_WEC->PJM
CLTF
0.071

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.74 %
Rating:661.76 MVA
Rating Type:A
MVA to Mitigate:719.62
MW Contribution:8.22
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.644
3144293JTRSVLE
50/50
0.543
970535AG2-341 GEN
50/50
1.768
3152661PLYWOOD A
50/50
0.177
971489AH1-241 GEN
Solar/Wind Harmer
21.013
3146776BUCKING
Solar/Wind Harmer
1.404
3146776BUCKING
Solar/Wind Harmer
0.114
315821AE2-092 GEN
Solar/Wind Harmer
0.014
970301AG2-198 GEN
Solar/Wind Harmer
8.767
3147133PAMPLIN
Solar/Wind Harmer
0.203
3147133PAMPLIN
Solar/Wind Harmer
0.162
958211AF2-115 GEN
Solar/Wind Harmer
2.289
963191AG1-168 GEN
Solar/Wind Harmer
0.763
971741AH1-377 GEN
Solar/Wind Harmer
18.217
316034AC1-036 C
Solar/Wind Harmer
0.011
970323AG2-213 GEN
Solar/Wind Harmer
6.61
971775AH1-396 GEN
Solar/Wind Harmer
0.248
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
4.515
939181AE1-148 GEN
Solar/Wind Harmer
4.407
964791AG1-342 GEN
Solar/Wind Harmer
1.738
3146843MT LREL
Solar/Wind Harmer
0.09
3146843MT LREL
Solar/Wind Harmer
0.09
970099AG2-077 GEN
Solar/Wind Harmer
9.298
971223AH1-071 GEN
Solar/Wind Harmer
0.928
3143526WINTERP
Solar/Wind Harmer
0.377
970933AG2-581 GEN
Solar/Wind Harmer
5.476
316181AB2-040 GEN
Solar/Wind Harmer
0.087
3145593CAROLNA
Solar/Wind Harmer
0.058
3145593CAROLNA
Solar/Wind Harmer
0.058
966811AG1-552 GEN
Solar/Wind Harmer
0.627
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.01
3145783HORNRTN
Solar/Wind Harmer
0.808
3145783HORNRTN
Solar/Wind Harmer
0.253
3145783HORNRTN
Solar/Wind Harmer
0.101
966001AG1-469 GEN
Solar/Wind Helper
0.19
3151931BEARGRDN S1
50/50
5.314
3151911BEARGRDN G1
50/50
4.118
3144293JTRSVLE
50/50
0.644
3151531CLOVER1
50/50
1.885
3151601KERR 3
50/50
0.18
3151581KERR 1
50/50
0.064
970119AG2-088 GEN
50/50
11.599
3147043LAWRENC
50/50
0.746
3151261ROARAP2
50/50
0.072
972003AH1-546 GEN
Solar/Wind Harmer
18.108
971377AH1-170 GEN
Solar/Wind Harmer
4.203
3147623JAMES R
Solar/Wind Harmer
0.913
970937AG2-583 GEN
Solar/Wind Harmer
22.204
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.14
3146926FARMVIL
Solar/Wind Harmer
0.165
316336AC2-165 C
Solar/Wind Harmer
0.01
3143336POWHATN
Solar/Wind Harmer
4.074
963171AG1-166 GEN
Solar/Wind Harmer
1.017
971563AH1-280 GEN
Solar/Wind Harmer
2.035
970685AG2-442 GEN
Solar/Wind Harmer
12.945
962491AG1-098 GEN
Solar/Wind Harmer
6.577
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
5.296
970401AG2-262 GEN
Solar/Wind Harmer
0.531
957481AF2-042 GEN
Solar/Wind Harmer
23.244
3143226MDLTHAN
Solar/Wind Harmer
0.087
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.352
316129AC1-054 GEN
Solar/Wind Harmer
0.289
971795AH1-408 GEN
Solar/Wind Harmer
4.849
3143526WINTERP
Solar/Wind Harmer
0.377
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.595
3145783HORNRTN
Solar/Wind Harmer
0.057
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.752
972205AH1-687 GEN
50/50
20.083
3151541CLOVER2
50/50
1.876
3151611KERR 4
50/50
0.18
3151621KERR 5
50/50
0.18
3151631KERR 6
50/50
0.18
3151641KERR 7
50/50
0.18
316303AF2-085
50/50
1.546
3151281ROARAP4
50/50
0.07
3151281ROARAP4
50/50
0.066
971447AH1-217 GEN
Solar/Wind Harmer
11.004
971845AH1-439 GEN
Solar/Wind Harmer
15.632
970285AG2-188 GEN
Solar/Wind Harmer
26.316
270494AE1-108_GEN
Solar/Wind Harmer
3.693
315657AE1-056 GEN
Solar/Wind Harmer
6.997
946301AF1-294 GEN
Solar/Wind Harmer
3.764
961791AG1-021 GEN
Solar/Wind Harmer
1.831
970683AG2-441 GEN
Solar/Wind Harmer
11.558
970681AG2-440 GEN
Solar/Wind Harmer
9.247
3144303KENBRDG
Solar/Wind Harmer
0.124
971443AH1-215 GEN
Solar/Wind Harmer
2.576
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.212
970831AG2-522 GEN
Solar/Wind Harmer
3.201
3147173SINAI
Solar/Wind Harmer
0.074
3147243WELCO
Solar/Wind Harmer
0.046
316233AE1-074 FULL
Solar/Wind Harmer
0.058
971281AH1-106 GEN
Solar/Wind Harmer
1.006
971283AH1-107 GEN
Solar/Wind Harmer
1.006
970865AG2-541 GEN
Solar/Wind Harmer
2.17
316087AB2-174 GEN
Solar/Wind Harmer
0.002
971967AH1-528 GEN
Solar/Wind Harmer
9.597
3137643SOCKMAN
Solar/Wind Harmer
0.235
3138266HYDRAULIC
Solar/Wind Helper
0.021
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.08
3148013FISHERV
Solar/Wind Helper
0.077
3148463FAIRFLD
Solar/Wind Helper
0.119
3151921BEARGRDN G2
50/50
4.118
3144293JTRSVLE
50/50
0.644
970413AG2-270 GEN
50/50
8.224
3151591KERR 2
50/50
0.18
966251AG1-494 GEN
50/50
1.173
3151261ROARAP2
50/50
0.07
970221AG2-151 GEN
Solar/Wind Harmer
21.013
3146776BUCKING
Solar/Wind Harmer
0.126
3146926FARMVIL
Solar/Wind Harmer
0.165
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.144
316258AE1-075 C
Solar/Wind Harmer
0.173
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.463
970909AG2-566 GEN
Solar/Wind Harmer
2.192
3147133PAMPLIN
Solar/Wind Harmer
0.637
971193AH1-056 GEN
Solar/Wind Harmer
12.353
963181AG1-167 GEN
Solar/Wind Harmer
0.763
959311AF2-222 GEN
Solar/Wind Harmer
14.242
970257AG2-171 GEN
Solar/Wind Harmer
4.957
315785AD2-033 C
Solar/Wind Harmer
1.2
964241AG1-285 GEN
Solar/Wind Harmer
8.548
958131AF2-107 GEN
Solar/Wind Harmer
3.44
316131AB2-060 GEN
Solar/Wind Harmer
0.366
316478AD1-087 GEN
Solar/Wind Harmer
0.307
316486AD2-202 GEN
Solar/Wind Harmer
0.09
3147043LAWRENC
Solar/Wind Harmer
0.047
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.155
971683AH1-343 GEN
Solar/Wind Harmer
2.44
313506AB2-031 GEN
Solar/Wind Harmer
0.186
316499AE2-029_GEN
Solar/Wind Helper
0.505
3148013FISHERV
Solar/Wind Helper
0.133
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.54
CPLELTFEXP_CPLE->PJM
CLTF
2.992
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.238
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.029
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.072
LAGNLTFEXP_LAGN->PJM
CLTF
1.122
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.815
TVALTFEXP_TVA->PJM
CLTF
0.547
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.673
MECLTFEXP_MEC->PJM
CLTF
0.138
SIGELTFEXP_SIGE->PJM
CLTF
0.002
NYPJM->LTFIMP_NY
CLTF
0.391

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:195.13 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:1291.31
MW Contribution:10.24
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.706
3144293JTRSVLE
50/50
0.594
970535AG2-341 GEN
50/50
2.11
3152661PLYWOOD A
50/50
0.217
3151041BRUNSWICKG3
50/50
1.059
972187AH1-678 GEN
50/50
2.43
315242AE2-183_GT2
50/50
1.321
315241AE2-183_GT1
50/50
1.313
972185AH1-677 GEN
50/50
4.762
970533AG2-339 GEN
50/50
7.019
970531AG2-338 GEN
50/50
2.808
971489AH1-241 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
1.465
3146776BUCKING
Solar/Wind Harmer
0.119
315821AE2-092 GEN
Solar/Wind Harmer
0.014
970301AG2-198 GEN
Solar/Wind Harmer
9.583
3147133PAMPLIN
Solar/Wind Harmer
0.221
3147133PAMPLIN
Solar/Wind Harmer
0.176
958211AF2-115 GEN
Solar/Wind Harmer
2.506
963191AG1-168 GEN
Solar/Wind Harmer
0.835
971741AH1-377 GEN
Solar/Wind Harmer
20.177
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.401
971775AH1-396 GEN
Solar/Wind Harmer
0.278
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971223AH1-071 GEN
Solar/Wind Harmer
1.233
962561AG1-105 GEN
Solar/Wind Harmer
5.397
939181AE1-148 GEN
Solar/Wind Harmer
5.333
970099AG2-077 GEN
Solar/Wind Harmer
11.718
964791AG1-342 GEN
Solar/Wind Harmer
2.089
3146843MT LREL
Solar/Wind Harmer
0.109
3146843MT LREL
Solar/Wind Harmer
0.109
3143526WINTERP
Solar/Wind Harmer
0.504
970933AG2-581 GEN
Solar/Wind Harmer
7.465
316181AB2-040 GEN
Solar/Wind Harmer
0.116
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.078
966811AG1-552 GEN
Solar/Wind Harmer
0.843
3145593CAROLNA
Solar/Wind Harmer
0.097
3145783HORNRTN
Solar/Wind Harmer
1.361
3145783HORNRTN
Solar/Wind Harmer
1.089
3145783HORNRTN
Solar/Wind Harmer
0.34
3145783HORNRTN
Solar/Wind Harmer
0.136
316426AA2-053 GEN
Solar/Wind Harmer
0.256
3144356SAPONY
Solar/Wind Harmer
0.607
316274AC1-208 GEN
Solar/Wind Harmer
0.366
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.042
3145893MURPHYS
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
0.126
3145796HORNRTN
Solar/Wind Harmer
0.209
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
315742AE1-103 GEN
Solar/Wind Harmer
0.001
316222AC1-221 GEN
Solar/Wind Harmer
0.272
316065AD1-022 GEN
Solar/Wind Harmer
3.004
970657AG2-426 GEN
Solar/Wind Harmer
2.275
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
2.446
3146376EDENTON
Solar/Wind Harmer
0.286
3146376EDENTON
Solar/Wind Harmer
0.286
961601AG1-000A GEN
Solar/Wind Harmer
1.137
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3145493TOT1
Solar/Wind Harmer
0.148
3145453TOT5
Solar/Wind Harmer
0.089
3145603CNETO
Solar/Wind Harmer
0.059
3146386ELIZ CT
Solar/Wind Harmer
0.064
3145933PARMELE
Solar/Wind Harmer
0.127
3145933PARMELE
Solar/Wind Harmer
0.063
3130086AYDLETT
Solar/Wind Harmer
0.253
3137176SLIGO L2192
Solar/Wind Harmer
0.252
3146456SLIGO L269
Solar/Wind Harmer
1.121
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.035
316339AD2-160 GEN
Solar/Wind Harmer
0.103
3145506HICKORY
Solar/Wind Harmer
0.253
3145506HICKORY
Solar/Wind Harmer
0.152
3145506HICKORY
Solar/Wind Harmer
0.038
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.061
942751AE2-291 GEN
Solar/Wind Harmer
3.43
316240AF1-291 C
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.012
3150991CHESPKB
Adder
0.659
3150991CHESPKB
Adder
0.643
944641AF1-129 GEN
Adder
29.755
316236AE1-162_GEN
Solar/Wind Harmer
0
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.068
966001AG1-469 GEN
Solar/Wind Helper
0.206
3151931BEARGRDN S1
50/50
5.469
3151911BEARGRDN G1
50/50
4.238
3144293JTRSVLE
50/50
0.706
970119AG2-088 GEN
50/50
15.414
3151531CLOVER1
50/50
2.348
3151601KERR 3
50/50
0.22
3151581KERR 1
50/50
0.079
3147043LAWRENC
50/50
0.939
3151051BRUNSWICKS1
50/50
2.197
3151021BRUNSWICKG1
50/50
1.059
971451AH1-221 GEN
50/50
3.216
315243AE2-183_GT3
50/50
1.321
3151261ROARAP2
50/50
0.097
3150851SPRUNCC
50/50
0.364
972003AH1-546 GEN
Solar/Wind Harmer
18.676
971377AH1-170 GEN
Solar/Wind Harmer
4.327
3147623JAMES R
Solar/Wind Harmer
0.94
970937AG2-583 GEN
Solar/Wind Harmer
23.217
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.147
3146926FARMVIL
Solar/Wind Harmer
0.176
316336AC2-165 C
Solar/Wind Harmer
0.011
3143336POWHATN
Solar/Wind Harmer
4.472
963171AG1-166 GEN
Solar/Wind Harmer
1.114
971563AH1-280 GEN
Solar/Wind Harmer
2.228
970685AG2-442 GEN
Solar/Wind Harmer
14.313
962491AG1-098 GEN
Solar/Wind Harmer
7.815
315693AD1-088 GEN
Solar/Wind Harmer
6.344
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Harmer
0.116
957481AF2-042 GEN
Solar/Wind Harmer
29.295
970401AG2-262 GEN
Solar/Wind Harmer
0.638
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
4.184
3143526WINTERP
Solar/Wind Harmer
0.504
316129AC1-054 GEN
Solar/Wind Harmer
0.363
971795AH1-408 GEN
Solar/Wind Harmer
6.199
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.793
970919AG2-571 GEN
Solar/Wind Harmer
2.76
970087AG2-069 GEN
Solar/Wind Harmer
6.187
3145783HORNRTN
Solar/Wind Harmer
0.076
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
5.984
316023GEN1_S
Solar/Wind Harmer
0.164
939411AE1-173 GEN
Solar/Wind Harmer
30.681
316011AB1-132 GEN
Solar/Wind Harmer
1.286
962571AG1-106 GEN
Solar/Wind Harmer
1.007
3146263WOODLND
Solar/Wind Harmer
0.071
3145893MURPHYS
Solar/Wind Harmer
0.281
3145893MURPHYS
Solar/Wind Harmer
0.312
3145796HORNRTN
Solar/Wind Harmer
0.23
3145796HORNRTN
Solar/Wind Harmer
0.07
316212AC1-099_GEN
Solar/Wind Harmer
0.359
3146173TUNIS
Solar/Wind Harmer
0.069
3145823KELFORD
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
315722AD1-056 GEN
Solar/Wind Harmer
0.422
3146233WITAKRS
Solar/Wind Harmer
0.263
3146206CASHIE
Solar/Wind Harmer
0.065
971547AH1-271 GEN
Solar/Wind Harmer
1.396
970659AG2-427 GEN
Solar/Wind Harmer
3.146
316381AD1-082 GEN
Solar/Wind Harmer
0.068
970661AG2-428 GEN
Solar/Wind Harmer
6.453
3145663CRESWEL
Solar/Wind Harmer
0.181
971163AH1-040 GEN
Solar/Wind Harmer
5.167
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.052
316359AB2-059 GEN
Solar/Wind Harmer
0.231
316049AB1-081 GEN
Solar/Wind Harmer
0.368
3142053HEARTS
Solar/Wind Harmer
0.113
316093AE2-104_GEN
Solar/Wind Harmer
1.081
3130156CHOWAN
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3142543TWELFTH
Solar/Wind Harmer
0.006
3146516WINFALL
Solar/Wind Harmer
0.207
3146516WINFALL
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.283
316246AF1-032 C
Solar/Wind Harmer
0.029
3146293MARTNCO
Solar/Wind Harmer
0.059
316494AC1-189 GEN
Solar/Wind Harmer
0.214
3146456SLIGO L269
Solar/Wind Harmer
0.063
316388AE2-253 GEN
Solar/Wind Harmer
0.198
944591AF1-124 GEN
Solar/Wind Harmer
14.289
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
315671AE2-027_GEN
Solar/Wind Harmer
4.043
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
1.077
3145336SMITFLD
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
0.644
961611AG1-000B GEN
Solar/Wind Harmer
3.17
971647AH1-324 GEN
Solar/Wind Harmer
2.576
3143096IRON208
Adder
0.252
971069AG2-661 GEN
Solar/Wind Harmer
1.071
316458AB2-190 GEN2
Solar/Wind Harmer
0.323
970129AG2-093 GEN
Solar/Wind Harmer
1.71
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.903
3147666LOUISA
Solar/Wind Helper
0.521
3151921BEARGRDN G2
50/50
4.238
3144293JTRSVLE
50/50
0.706
970413AG2-270 GEN
50/50
10.245
3151591KERR 2
50/50
0.22
3151031BRUNSWICKG2
50/50
1.059
3151261ROARAP2
50/50
0.095
3150861SPRUNCD
50/50
0.364
966251AG1-494 GEN
50/50
1.288
970221AG2-151 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
0.132
3146926FARMVIL
Solar/Wind Harmer
0.176
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.159
316258AE1-075 C
Solar/Wind Harmer
0.19
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.801
970909AG2-566 GEN
Solar/Wind Harmer
2.396
3147133PAMPLIN
Solar/Wind Harmer
0.693
971193AH1-056 GEN
Solar/Wind Harmer
13.448
963181AG1-167 GEN
Solar/Wind Harmer
0.835
959311AF2-222 GEN
Solar/Wind Harmer
15.884
970257AG2-171 GEN
Solar/Wind Harmer
5.55
315785AD2-033 C
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
9.804
316131AB2-060 GEN
Solar/Wind Harmer
0.426
958131AF2-107 GEN
Solar/Wind Harmer
3.651
316478AD1-087 GEN
Solar/Wind Harmer
0.382
316486AD2-202 GEN
Solar/Wind Harmer
0.112
3147043LAWRENC
Solar/Wind Harmer
0.059
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.912
971683AH1-343 GEN
Solar/Wind Harmer
3.032
313506AB2-031 GEN
Solar/Wind Harmer
0.248
970917AG2-570 GEN
Solar/Wind Harmer
6.901
316365GEN2_N
Solar/Wind Harmer
0.164
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
0.117
3145893MURPHYS
Solar/Wind Harmer
0.07
957521AF2-046 GEN
Solar/Wind Harmer
5.202
961681AG1-008 GEN
Solar/Wind Harmer
5.202
3145796HORNRTN
Solar/Wind Harmer
0.279
3145796HORNRTN
Solar/Wind Harmer
0.07
316210AC1-098 GEN
Solar/Wind Harmer
0.644
3146173TUNIS
Solar/Wind Harmer
0.069
316463AE2-346 GEN
Solar/Wind Harmer
0.059
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.732
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.069
316327AA2-057 GEN
Solar/Wind Harmer
0.102
315724AD1-057 GEN
Solar/Wind Harmer
0.25
3145273HOLLAND
Solar/Wind Harmer
0.05
3156021HOLLOMANSOL
Solar/Wind Harmer
0.301
3146233WITAKRS
Solar/Wind Harmer
0.331
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3146206CASHIE
Solar/Wind Harmer
0.065
315813AE1-149 C
Solar/Wind Harmer
3.482
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316283AC2-100 C
Solar/Wind Harmer
0.127
315839AE2-212 C
Solar/Wind Harmer
0.001
972205AH1-687 GEN
50/50
20.67
316303AF2-085
50/50
2.055
3151541CLOVER2
50/50
2.336
3151611KERR 4
50/50
0.22
3151621KERR 5
50/50
0.22
3151631KERR 6
50/50
0.22
3151641KERR 7
50/50
0.22
963041AG1-153 GEN
50/50
2.144
315244AE2-183_ST
50/50
2.284
3151281ROARAP4
50/50
0.094
3151281ROARAP4
50/50
0.088
971285AH1-108 GEN
50/50
0.596
315779AE2-040
50/50
1.013
971447AH1-217 GEN
Solar/Wind Harmer
11.337
971845AH1-439 GEN
Solar/Wind Harmer
16.33
970285AG2-188 GEN
Solar/Wind Harmer
27.559
270494AE1-108_GEN
Solar/Wind Harmer
3.817
315657AE1-056 GEN
Solar/Wind Harmer
7.617
946301AF1-294 GEN
Solar/Wind Harmer
4.122
961791AG1-021 GEN
Solar/Wind Harmer
2.005
970683AG2-441 GEN
Solar/Wind Harmer
12.78
970681AG2-440 GEN
Solar/Wind Harmer
10.224
3144303KENBRDG
Solar/Wind Harmer
0.139
971443AH1-215 GEN
Solar/Wind Harmer
2.888
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.258
316233AE1-074 FULL
Solar/Wind Harmer
0.078
971281AH1-106 GEN
Solar/Wind Harmer
1.344
971283AH1-107 GEN
Solar/Wind Harmer
1.344
970831AG2-522 GEN
Solar/Wind Harmer
4.036
3147173SINAI
Solar/Wind Harmer
0.092
3147243WELCO
Solar/Wind Harmer
0.057
971967AH1-528 GEN
Solar/Wind Harmer
13.711
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
16.986
970673AG2-436 GEN
Solar/Wind Harmer
11.324
941031AE2-094 GEN
Solar/Wind Harmer
14.544
944011AF1-069 GEN
Solar/Wind Harmer
4.752
3137643SOCKMAN
Solar/Wind Harmer
0.315
970865AG2-541 GEN
Solar/Wind Harmer
2.702
970085AG2-068 GEN
Solar/Wind Harmer
4.124
970581AG2-369 GEN
Solar/Wind Harmer
3.547
315607AA1-063A GEN
Solar/Wind Harmer
0.154
3146043SEABORD
Solar/Wind Harmer
0.075
315814AE2-033 C
Solar/Wind Harmer
5.747
316315AB2-025 C
Solar/Wind Harmer
0.059
965291AG1-394 GEN
Solar/Wind Harmer
0.317
315652AC1-086 GEN
Solar/Wind Harmer
7.782
3145893MURPHYS
Solar/Wind Harmer
0.19
3145893MURPHYS
Solar/Wind Harmer
0.07
3145796HORNRTN
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.028
3146033SCOT NK
Solar/Wind Harmer
0.276
316123AC1-075 GEN
Solar/Wind Harmer
0.094
970165AG2-112 GEN
Solar/Wind Harmer
0.558
970163AG2-111 GEN
Solar/Wind Harmer
0.532
3145513AHOSKIE
Solar/Wind Harmer
0.143
3145513AHOSKIE
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3143316POE
Solar/Wind Harmer
0.269
316319Z2-044 C
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.065
970601AG2-382 GEN
Solar/Wind Harmer
2.444
315732AD1-074 GEN1
Solar/Wind Harmer
0.373
315733AD1-074 GEN2
Solar/Wind Harmer
0.373
315735AD1-075 GEN1
Solar/Wind Harmer
0.187
3130546PLYMOUTH
Solar/Wind Harmer
0.065
315816AE2-034 GEN
Solar/Wind Harmer
0.277
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.044
316311AC2-079 GEN
Solar/Wind Harmer
1.853
315835AF2-110_GEN
Solar/Wind Harmer
0.441
3130156CHOWAN
Solar/Wind Harmer
0.064
3130156CHOWAN
Solar/Wind Harmer
0.064
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
316321Z2-027
Solar/Wind Harmer
0.012
3145176PASQUOTANK
Solar/Wind Harmer
0.039
3146396TANGLEW
Solar/Wind Harmer
0.175
316420AA1-050 GEN
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.034
316305AF2-043 C
Solar/Wind Harmer
0.001
957861AF2-080 GEN
Solar/Wind Harmer
2.737
3146406KITTY HAWK
Solar/Wind Harmer
0.008
319010AE1-072 C
Solar/Wind Harmer
0.319
957871AF2-081 GEN
Solar/Wind Harmer
3.153
316005AA1-067
Solar/Wind Harmer
0.068
3145746EVERETS
Solar/Wind Harmer
0.252
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
970181AG2-120 GEN
Solar/Wind Harmer
0.787
3151081ELIZAR1
Adder
5.773
3151091ELIZAR2
Adder
5.672
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.68
3152601GOSPORTA
Adder
0.628
971445AH1-216 GEN
Solar/Wind Harmer
4.321
972265AH1-717 GEN
Adder
4.702
3151201GRAVEL4
Adder
4.408
3151191GRAVEL3
Adder
4.352
3151211GRAVEL5
Adder
4.352
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.323
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
315737AD1-076 GEN
Solar/Wind Harmer
0.835
970661AG2-428 GEN
Solar/Wind Harmer
1.373
971157AH1-035 GEN
Solar/Wind Harmer
0.778
315614AA2-178 GEN
Solar/Wind Harmer
0.37
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.129
3146376EDENTON
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
4.548
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316435W1029_GEN3
Solar/Wind Harmer
0
965281AG1-393 GEN
Solar/Wind Harmer
0.68
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
316320Y1-086
Solar/Wind Harmer
0
3145933PARMELE
Solar/Wind Harmer
0.063
966801AG1-551 GEN
Solar/Wind Harmer
0.74
3146456SLIGO L269
Solar/Wind Harmer
0.063
971153AH1-033 GEN
Solar/Wind Harmer
0.732
944581AF1-123 GEN
Solar/Wind Harmer
14.239
944601AF1-125 GEN
Solar/Wind Harmer
14.019
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3151101ELIZAR3
Adder
5.847
3144873MCLAUGH
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.009
315773AC2-141 GEN
Solar/Wind Harmer
2.27
3145336SMITFLD
Solar/Wind Harmer
0.025
3151221GRAVEL6
Adder
4.403
3151171GRAVELC
Adder
0.847
961611AG1-000B GEN
Solar/Wind Harmer
1.612
3143096IRON208
Adder
0.252
3143096IRON208
Adder
0.247
315778AD1-151 GEN
Solar/Wind Harmer
4.818
970129AG2-093 GEN
Solar/Wind Harmer
3.634
970133AG2-095 GEN
Solar/Wind Harmer
0.576
316499AE2-029_GEN
Solar/Wind Helper
0.501
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.3
3148013FISHERV
Solar/Wind Helper
0.129
315616AA1-038_C
Solar/Wind Helper
0.524
3148133STUARTS
Solar/Wind Helper
0.077
3148013FISHERV
Solar/Wind Helper
0.074
3148463FAIRFLD
Solar/Wind Helper
0.116
CPLELTFEXP_CPLE->PJM
CLTF
4.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.705
LAGNLTFEXP_LAGN->PJM
CLTF
1.972
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.458
TVALTFEXP_TVA->PJM
CLTF
0.973
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.131
MECLTFEXP_MEC->PJM
CLTF
0.546
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.616
LGEELTFEXP_LGEE->PJM
CLTF
0.137
WECLTFEXP_WEC->PJM
CLTF
0.063

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:160.44 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:1061.7
MW Contribution:9.03
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.823
3144293JTRSVLE
50/50
0.693
970535AG2-341 GEN
50/50
2.047
3152661PLYWOOD A
50/50
0.202
971489AH1-241 GEN
Solar/Wind Harmer
28.504
3146776BUCKING
Solar/Wind Harmer
1.881
3146776BUCKING
Solar/Wind Harmer
0.152
315821AE2-092 GEN
Solar/Wind Harmer
0.02
970301AG2-198 GEN
Solar/Wind Harmer
11.214
3147133PAMPLIN
Solar/Wind Harmer
0.26
3147133PAMPLIN
Solar/Wind Harmer
0.208
958211AF2-115 GEN
Solar/Wind Harmer
2.924
963191AG1-168 GEN
Solar/Wind Harmer
0.975
971741AH1-377 GEN
Solar/Wind Harmer
22.982
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.246
971775AH1-396 GEN
Solar/Wind Harmer
0.309
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
5.277
964791AG1-342 GEN
Solar/Wind Harmer
2.024
3146843MT LREL
Solar/Wind Harmer
0.105
3146843MT LREL
Solar/Wind Harmer
0.105
939181AE1-148 GEN
Solar/Wind Harmer
5.007
970099AG2-077 GEN
Solar/Wind Harmer
9.999
970933AG2-581 GEN
Solar/Wind Harmer
5.154
942751AE2-291 GEN
Solar/Wind Harmer
3.374
966001AG1-469 GEN
Solar/Wind Helper
0.159
3151931BEARGRDN S1
50/50
7.21
3151911BEARGRDN G1
50/50
5.587
3144293JTRSVLE
50/50
0.823
3151601KERR 3
50/50
0.202
3151581KERR 1
50/50
0.072
3151531CLOVER1
50/50
2.069
3147043LAWRENC
50/50
0.777
970937AG2-583 GEN
Solar/Wind Harmer
36.866
316336AC2-165 C
Solar/Wind Harmer
0.024
972003AH1-546 GEN
Solar/Wind Harmer
24.522
971377AH1-170 GEN
Solar/Wind Harmer
5.701
3147623JAMES R
Solar/Wind Harmer
1.238
316322AB2-045
Solar/Wind Harmer
0.004
3146776BUCKING
Solar/Wind Harmer
0.188
3146926FARMVIL
Solar/Wind Harmer
0.218
963171AG1-166 GEN
Solar/Wind Harmer
1.299
971563AH1-280 GEN
Solar/Wind Harmer
2.599
970685AG2-442 GEN
Solar/Wind Harmer
16.367
962491AG1-098 GEN
Solar/Wind Harmer
7.651
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
6.098
970401AG2-262 GEN
Solar/Wind Harmer
0.618
957481AF2-042 GEN
Solar/Wind Harmer
24.997
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.611
316129AC1-054 GEN
Solar/Wind Harmer
0.309
316003AC1-222 GEN
Solar/Wind Harmer
0.002
971795AH1-408 GEN
Solar/Wind Harmer
4.899
962751AG1-124 GEN
Solar/Wind Harmer
3.147
960081AF2-299 GEN
Solar/Wind Harmer
0.55
972205AH1-687 GEN
50/50
27.249
3151611KERR 4
50/50
0.202
3151621KERR 5
50/50
0.202
3151631KERR 6
50/50
0.202
3151641KERR 7
50/50
0.202
3151541CLOVER2
50/50
2.059
971447AH1-217 GEN
Solar/Wind Harmer
15.037
971845AH1-439 GEN
Solar/Wind Harmer
20.916
970285AG2-188 GEN
Solar/Wind Harmer
35.131
270494AE1-108_GEN
Solar/Wind Harmer
5.032
315657AE1-056 GEN
Solar/Wind Harmer
8.99
946301AF1-294 GEN
Solar/Wind Harmer
4.808
961791AG1-021 GEN
Solar/Wind Harmer
2.339
970683AG2-441 GEN
Solar/Wind Harmer
14.613
970681AG2-440 GEN
Solar/Wind Harmer
11.691
3144303KENBRDG
Solar/Wind Harmer
0.154
971443AH1-215 GEN
Solar/Wind Harmer
3.209
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.244
3147173SINAI
Solar/Wind Harmer
0.084
3147243WELCO
Solar/Wind Harmer
0.052
970831AG2-522 GEN
Solar/Wind Harmer
3.381
970865AG2-541 GEN
Solar/Wind Harmer
2.545
316123AC1-075 GEN
Solar/Wind Harmer
0.091
970165AG2-112 GEN
Solar/Wind Harmer
0.539
970163AG2-111 GEN
Solar/Wind Harmer
0.514
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
3151921BEARGRDN G2
50/50
5.587
3144293JTRSVLE
50/50
0.823
3151591KERR 2
50/50
0.202
970413AG2-270 GEN
50/50
9.029
966251AG1-494 GEN
50/50
1.716
970221AG2-151 GEN
Solar/Wind Harmer
28.504
3146776BUCKING
Solar/Wind Harmer
0.169
3146926FARMVIL
Solar/Wind Harmer
0.218
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
970909AG2-566 GEN
Solar/Wind Harmer
2.804
3147133PAMPLIN
Solar/Wind Harmer
0.818
971193AH1-056 GEN
Solar/Wind Harmer
15.872
963181AG1-167 GEN
Solar/Wind Harmer
0.975
959311AF2-222 GEN
Solar/Wind Harmer
17.841
970257AG2-171 GEN
Solar/Wind Harmer
6.184
315785AD2-033 C
Solar/Wind Harmer
1.488
958131AF2-107 GEN
Solar/Wind Harmer
4.835
964241AG1-285 GEN
Solar/Wind Harmer
10.382
316131AB2-060 GEN
Solar/Wind Harmer
0.438
316478AD1-087 GEN
Solar/Wind Harmer
0.337
316486AD2-202 GEN
Solar/Wind Harmer
0.099
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.582
3147043LAWRENC
Solar/Wind Harmer
0.049
971683AH1-343 GEN
Solar/Wind Harmer
2.828
3132273ORANGE
Solar/Wind Helper
0.023
CPLELTFEXP_CPLE->PJM
CLTF
2.979
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.201
LAGNLTFEXP_LAGN->PJM
CLTF
1.554
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.128
TVALTFEXP_TVA->PJM
CLTF
0.776
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.084
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.539
MECLTFEXP_MEC->PJM
CLTF
0.508
SIGELTFEXP_SIGE->PJM
CLTF
0.014
NYPJM->LTFIMP_NY
CLTF
0.525
LGEELTFEXP_LGEE->PJM
CLTF
0.153
WECLTFEXP_WEC->PJM
CLTF
0.071

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.36 %
Rating:661.76 MVA
Rating Type:A
MVA to Mitigate:697.23
MW Contribution:8.22
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.314
3151911BEARGRDN G1
50/50
4.118
3144293JTRSVLE
50/50
0.644
3151531CLOVER1
50/50
1.885
3151601KERR 3
50/50
0.18
3151581KERR 1
50/50
0.064
970119AG2-088 GEN
50/50
11.599
3147043LAWRENC
50/50
0.746
3151261ROARAP2
50/50
0.072
972003AH1-546 GEN
Solar/Wind Harmer
18.108
971377AH1-170 GEN
Solar/Wind Harmer
4.203
3147623JAMES R
Solar/Wind Harmer
0.913
970937AG2-583 GEN
Solar/Wind Harmer
22.204
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.14
3146926FARMVIL
Solar/Wind Harmer
0.165
316336AC2-165 C
Solar/Wind Harmer
0.01
3143336POWHATN
Solar/Wind Harmer
4.074
963171AG1-166 GEN
Solar/Wind Harmer
1.017
971563AH1-280 GEN
Solar/Wind Harmer
2.035
970685AG2-442 GEN
Solar/Wind Harmer
12.945
962491AG1-098 GEN
Solar/Wind Harmer
6.577
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
5.296
970401AG2-262 GEN
Solar/Wind Harmer
0.531
957481AF2-042 GEN
Solar/Wind Harmer
23.244
3143226MDLTHAN
Solar/Wind Harmer
0.087
972205AH1-687 GEN
50/50
20.083
3151541CLOVER2
50/50
1.876
3151611KERR 4
50/50
0.18
3151621KERR 5
50/50
0.18
3151631KERR 6
50/50
0.18
3151641KERR 7
50/50
0.18
316303AF2-085
50/50
1.546
3151281ROARAP4
50/50
0.07
3151281ROARAP4
50/50
0.066
971447AH1-217 GEN
Solar/Wind Harmer
11.004
971845AH1-439 GEN
Solar/Wind Harmer
15.632
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.352
316129AC1-054 GEN
Solar/Wind Harmer
0.289
971795AH1-408 GEN
Solar/Wind Harmer
4.849
3143526WINTERP
Solar/Wind Harmer
0.377
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.595
3145783HORNRTN
Solar/Wind Harmer
0.057
3147983MERCK5
Solar/Wind Helper
0.055
3144293JTRSVLE
50/50
0.644
3144293JTRSVLE
50/50
0.543
970535AG2-341 GEN
50/50
1.768
3152661PLYWOOD A
50/50
0.177
971489AH1-241 GEN
Solar/Wind Harmer
21.013
3146776BUCKING
Solar/Wind Harmer
1.404
3146776BUCKING
Solar/Wind Harmer
0.114
315821AE2-092 GEN
Solar/Wind Harmer
0.014
970301AG2-198 GEN
Solar/Wind Harmer
8.767
3147133PAMPLIN
Solar/Wind Harmer
0.203
3147133PAMPLIN
Solar/Wind Harmer
0.162
958211AF2-115 GEN
Solar/Wind Harmer
2.289
963191AG1-168 GEN
Solar/Wind Harmer
0.763
971741AH1-377 GEN
Solar/Wind Harmer
18.217
316034AC1-036 C
Solar/Wind Harmer
0.011
970323AG2-213 GEN
Solar/Wind Harmer
6.61
971775AH1-396 GEN
Solar/Wind Harmer
0.248
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
4.515
939181AE1-148 GEN
Solar/Wind Harmer
4.407
964791AG1-342 GEN
Solar/Wind Harmer
1.738
3146843MT LREL
Solar/Wind Harmer
0.09
3146843MT LREL
Solar/Wind Harmer
0.09
970099AG2-077 GEN
Solar/Wind Harmer
9.298
971223AH1-071 GEN
Solar/Wind Harmer
0.928
3143526WINTERP
Solar/Wind Harmer
0.377
970933AG2-581 GEN
Solar/Wind Harmer
5.476
316181AB2-040 GEN
Solar/Wind Harmer
0.087
3145593CAROLNA
Solar/Wind Harmer
0.058
3145593CAROLNA
Solar/Wind Harmer
0.058
966811AG1-552 GEN
Solar/Wind Harmer
0.627
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.01
3145783HORNRTN
Solar/Wind Harmer
0.808
3145783HORNRTN
Solar/Wind Harmer
0.253
3145783HORNRTN
Solar/Wind Harmer
0.101
966001AG1-469 GEN
Solar/Wind Helper
0.19
3151921BEARGRDN G2
50/50
4.118
3144293JTRSVLE
50/50
0.644
970413AG2-270 GEN
50/50
8.224
3151591KERR 2
50/50
0.18
966251AG1-494 GEN
50/50
1.173
3151261ROARAP2
50/50
0.07
970221AG2-151 GEN
Solar/Wind Harmer
21.013
3146776BUCKING
Solar/Wind Harmer
0.126
3146926FARMVIL
Solar/Wind Harmer
0.165
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.144
316258AE1-075 C
Solar/Wind Harmer
0.173
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.463
970909AG2-566 GEN
Solar/Wind Harmer
2.192
3147133PAMPLIN
Solar/Wind Harmer
0.637
971193AH1-056 GEN
Solar/Wind Harmer
12.353
963181AG1-167 GEN
Solar/Wind Harmer
0.763
959311AF2-222 GEN
Solar/Wind Harmer
14.242
970257AG2-171 GEN
Solar/Wind Harmer
4.957
315785AD2-033 C
Solar/Wind Harmer
1.2
964241AG1-285 GEN
Solar/Wind Harmer
8.548
958131AF2-107 GEN
Solar/Wind Harmer
3.44
316131AB2-060 GEN
Solar/Wind Harmer
0.366
316478AD1-087 GEN
Solar/Wind Harmer
0.307
316486AD2-202 GEN
Solar/Wind Harmer
0.09
3147043LAWRENC
Solar/Wind Harmer
0.047
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.155
971683AH1-343 GEN
Solar/Wind Harmer
2.44
313506AB2-031 GEN
Solar/Wind Harmer
0.186
316499AE2-029_GEN
Solar/Wind Helper
0.505
3148013FISHERV
Solar/Wind Helper
0.133
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.54
316192AB2-158 GEN
Solar/Wind Helper
0.752
970285AG2-188 GEN
Solar/Wind Harmer
26.316
270494AE1-108_GEN
Solar/Wind Harmer
3.693
315657AE1-056 GEN
Solar/Wind Harmer
6.997
946301AF1-294 GEN
Solar/Wind Harmer
3.764
961791AG1-021 GEN
Solar/Wind Harmer
1.831
970683AG2-441 GEN
Solar/Wind Harmer
11.558
970681AG2-440 GEN
Solar/Wind Harmer
9.247
3144303KENBRDG
Solar/Wind Harmer
0.124
971443AH1-215 GEN
Solar/Wind Harmer
2.576
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.212
970831AG2-522 GEN
Solar/Wind Harmer
3.201
3147173SINAI
Solar/Wind Harmer
0.074
3147243WELCO
Solar/Wind Harmer
0.046
316233AE1-074 FULL
Solar/Wind Harmer
0.058
971281AH1-106 GEN
Solar/Wind Harmer
1.006
971283AH1-107 GEN
Solar/Wind Harmer
1.006
970865AG2-541 GEN
Solar/Wind Harmer
2.17
316087AB2-174 GEN
Solar/Wind Harmer
0.002
971967AH1-528 GEN
Solar/Wind Harmer
9.597
3137643SOCKMAN
Solar/Wind Harmer
0.235
3138266HYDRAULIC
Solar/Wind Helper
0.021
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.08
3148013FISHERV
Solar/Wind Helper
0.077
3148463FAIRFLD
Solar/Wind Helper
0.119
CPLELTFEXP_CPLE->PJM
CLTF
2.992
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.238
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.029
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.072
LAGNLTFEXP_LAGN->PJM
CLTF
1.122
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.815
TVALTFEXP_TVA->PJM
CLTF
0.547
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.673
MECLTFEXP_MEC->PJM
CLTF
0.138
SIGELTFEXP_SIGE->PJM
CLTF
0.002
NYPJM->LTFIMP_NY
CLTF
0.391

Details for 6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.64 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:893.44
MW Contribution:6.8
Bus #Bus NameTypeMW Contribution
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.27
3151621KERR 5
50/50
0.27
3151631KERR 6
50/50
0.27
3151641KERR 7
50/50
0.27
3151151S HAMPT1
50/50
0.285
3151541CLOVER2
50/50
1.551
316087AB2-174 GEN
Solar/Wind Harmer
0.01
315652AC1-086 GEN
Solar/Wind Harmer
37.428
3145796HORNRTN
Solar/Wind Harmer
1.015
3145796HORNRTN
Solar/Wind Harmer
0.127
3137643SOCKMAN
Solar/Wind Harmer
1.176
315607AA1-063A GEN
Solar/Wind Harmer
0.444
3146043SEABORD
Solar/Wind Harmer
0.211
3146033SCOT NK
Solar/Wind Harmer
0.75
316319Z2-044 C
Solar/Wind Harmer
0
970831AG2-522 GEN
Solar/Wind Harmer
7.783
3145683EARLEYS
Solar/Wind Harmer
0.333
3145683EARLEYS
Solar/Wind Harmer
0.166
3145683EARLEYS
Solar/Wind Harmer
0.166
3145513AHOSKIE
Solar/Wind Harmer
0.345
3145513AHOSKIE
Solar/Wind Harmer
0.165
3145573BETHELC
Solar/Wind Harmer
0.165
3145573BETHELC
Solar/Wind Harmer
0.165
3145893MURPHYS
Solar/Wind Harmer
0.432
3145893MURPHYS
Solar/Wind Harmer
0.16
316420AA1-050 GEN
Solar/Wind Harmer
0.005
965291AG1-394 GEN
Solar/Wind Harmer
0.698
957861AF2-080 GEN
Solar/Wind Harmer
6.563
316005AA1-067
Solar/Wind Harmer
0.148
3145746EVERETS
Solar/Wind Harmer
0.548
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
970181AG2-120 GEN
Solar/Wind Harmer
1.713
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.122
970601AG2-382 GEN
Solar/Wind Harmer
4.575
971443AH1-215 GEN
Solar/Wind Harmer
1.848
3144303KENBRDG
Solar/Wind Harmer
0.087
315732AD1-074 GEN1
Solar/Wind Harmer
0.587
315733AD1-074 GEN2
Solar/Wind Harmer
0.587
315735AD1-075 GEN1
Solar/Wind Harmer
0.294
970683AG2-441 GEN
Solar/Wind Harmer
6.63
970681AG2-440 GEN
Solar/Wind Harmer
5.304
3130546PLYMOUTH
Solar/Wind Harmer
0.098
946301AF1-294 GEN
Solar/Wind Harmer
1.782
961791AG1-021 GEN
Solar/Wind Harmer
0.867
316118AC1-105 GEN
Solar/Wind Harmer
0.227
315657AE1-056 GEN
Solar/Wind Harmer
2.895
315816AE2-034 GEN
Solar/Wind Harmer
0.344
3147173SINAI
Solar/Wind Harmer
0.077
3147243WELCO
Solar/Wind Harmer
0.048
970865AG2-541 GEN
Solar/Wind Harmer
2.227
316315AB2-025 C
Solar/Wind Helper
0.826
3143316POE
Solar/Wind Helper
0.688
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3147043LAWRENC
50/50
3.141
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.27
3151581KERR 1
50/50
0.096
3144293JTRSVLE
50/50
0.305
3151531CLOVER1
50/50
1.558
316023GEN1_S
Solar/Wind Harmer
1.155
960081AF2-299 GEN
Solar/Wind Harmer
3.965
971795AH1-408 GEN
Solar/Wind Harmer
23.615
316011AB1-132 GEN
Solar/Wind Harmer
6.186
962571AG1-106 GEN
Solar/Wind Harmer
4.841
3145796HORNRTN
Solar/Wind Harmer
1.046
3145796HORNRTN
Solar/Wind Harmer
0.317
3145783HORNRTN
Solar/Wind Harmer
0.249
315722AD1-056 GEN
Solar/Wind Harmer
1.531
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
1.015
3146263WOODLND
Solar/Wind Harmer
0.191
3146233WITAKRS
Solar/Wind Harmer
0.73
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3151261ROARAP2
50/50
0.313
3151591KERR 2
50/50
0.27
3144293JTRSVLE
50/50
0.305
970413AG2-270 GEN
50/50
6.801
316365GEN2_N
Solar/Wind Harmer
1.155
313506AB2-031 GEN
Solar/Wind Harmer
1.049
3147043LAWRENC
Solar/Wind Harmer
0.196
3145796HORNRTN
Solar/Wind Harmer
1.268
3145796HORNRTN
Solar/Wind Harmer
0.317
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
315724AD1-057 GEN
Solar/Wind Harmer
0.907
316210AC1-098 GEN
Solar/Wind Harmer
1.821
316327AA2-057 GEN
Solar/Wind Harmer
0.289
3146263WOODLND
Solar/Wind Harmer
0.191
3146233WITAKRS
Solar/Wind Harmer
0.921
3146233WITAKRS
Solar/Wind Harmer
0.125
3138543CONSLDL
Solar/Wind Harmer
0.12
961601AG1-000A GEN
Solar/Wind Harmer
12.805
316317KELFORD C
Solar/Wind Harmer
0.017
3145823KELFORD
Solar/Wind Harmer
0.177
971623AH1-311 GEN
Solar/Wind Harmer
0.353
3145543BTLEBRO
Solar/Wind Harmer
0.175
3145543BTLEBRO
Solar/Wind Harmer
0.175
316463AE2-346 GEN
Solar/Wind Harmer
0.142
316140AB2-099
Solar/Wind Harmer
0.059
962331AG1-082 GEN
Solar/Wind Harmer
1.76
3146073TAR RVR
Solar/Wind Harmer
0.165
3146083TARBORO
Solar/Wind Harmer
0.165
3146173TUNIS
Solar/Wind Harmer
0.163
957521AF2-046 GEN
Solar/Wind Harmer
11.982
961681AG1-008 GEN
Solar/Wind Harmer
11.982
3145893MURPHYS
Solar/Wind Harmer
0.268
3145893MURPHYS
Solar/Wind Harmer
0.16
3156021HOLLOMANSOL
Solar/Wind Harmer
0.689
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3145933PARMELE
Solar/Wind Harmer
0.131
966801AG1-551 GEN
Solar/Wind Harmer
1.529
316131AB2-060 GEN
Solar/Wind Harmer
0.407
964241AG1-285 GEN
Solar/Wind Harmer
8.211
3146206CASHIE
Solar/Wind Harmer
0.122
3145963POPLR C
Solar/Wind Harmer
0.118
315785AD2-033 C
Solar/Wind Harmer
0.918
970257AG2-171 GEN
Solar/Wind Harmer
3.491
959311AF2-222 GEN
Solar/Wind Harmer
9.454
315737AD1-076 GEN
Solar/Wind Harmer
1.314
971157AH1-035 GEN
Solar/Wind Harmer
1.183
963181AG1-167 GEN
Solar/Wind Harmer
0.361
3147133PAMPLIN
Solar/Wind Harmer
0.263
971193AH1-056 GEN
Solar/Wind Harmer
5.112
315614AA2-178 GEN
Solar/Wind Harmer
0.458
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.273
316478AD1-087 GEN
Solar/Wind Harmer
0.254
316486AD2-202 GEN
Solar/Wind Harmer
0.075
971683AH1-343 GEN
Solar/Wind Harmer
2.513
942461AE2-259 GEN
Solar/Wind Harmer
0
316283AC2-100 C
Solar/Wind Harmer
0.113
970909AG2-566 GEN
Solar/Wind Harmer
0.605
315839AE2-212 C
Solar/Wind Helper
0.197
3145823KELFORD
Solar/Wind Harmer
0.177
316359AB2-059 GEN
Solar/Wind Harmer
0.634
316049AB1-081 GEN
Solar/Wind Harmer
1.01
3142053HEARTS
Solar/Wind Harmer
0.311
3145543BTLEBRO
Solar/Wind Harmer
0.175
3145543BTLEBRO
Solar/Wind Harmer
0.14
316129AC1-054 GEN
Solar/Wind Harmer
0.656
971065AG2-659 GEN
Solar/Wind Harmer
7.13
3145683EARLEYS
Solar/Wind Harmer
0.166
961671AG1-007 GEN
Solar/Wind Harmer
0.025
3146083TARBORO
Solar/Wind Harmer
0.165
3145493TOT1
Solar/Wind Harmer
0.732
3146173TUNIS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
0.64
3145893MURPHYS
Solar/Wind Harmer
0.712
316494AC1-189 GEN
Solar/Wind Harmer
0.514
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3146293MARTNCO
Solar/Wind Harmer
0.122
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.122
971547AH1-271 GEN
Solar/Wind Harmer
2.614
316174AB2-169 GEN
Solar/Wind Harmer
0.003
3145963POPLR C
Solar/Wind Harmer
0.118
970685AG2-442 GEN
Solar/Wind Harmer
7.425
970401AG2-262 GEN
Solar/Wind Harmer
0.583
963171AG1-166 GEN
Solar/Wind Harmer
0.482
971563AH1-280 GEN
Solar/Wind Harmer
0.963
3145663CRESWEL
Solar/Wind Harmer
0.224
971163AH1-040 GEN
Solar/Wind Harmer
6.407
957481AF2-042 GEN
Solar/Wind Harmer
19.308
316003AC1-222 GEN
Solar/Wind Harmer
0.002
315693AD1-088 GEN
Solar/Wind Harmer
3.442
315687AD1-152 GEN
Solar/Wind Harmer
0.002
962491AG1-098 GEN
Solar/Wind Harmer
4.048
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.321
3144293JTRSVLE
50/50
0.305
3144293JTRSVLE
50/50
0.257
3152661PLYWOOD A
50/50
0.195
316181AB2-040 GEN
Solar/Wind Harmer
0.492
3145796HORNRTN
Solar/Wind Harmer
0.951
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3145593CAROLNA
Solar/Wind Harmer
0.257
3145593CAROLNA
Solar/Wind Harmer
0.257
966811AG1-552 GEN
Solar/Wind Harmer
2.785
3145593CAROLNA
Solar/Wind Harmer
0.32
3145783HORNRTN
Solar/Wind Harmer
4.428
3145783HORNRTN
Solar/Wind Harmer
3.543
3145783HORNRTN
Solar/Wind Harmer
1.107
3145783HORNRTN
Solar/Wind Harmer
0.443
316426AA2-053 GEN
Solar/Wind Harmer
0.813
316274AC1-208 GEN
Solar/Wind Harmer
1.081
961601AG1-000A GEN
Solar/Wind Harmer
3.201
316263AC1-034 GEN
Solar/Wind Harmer
6.707
3145493TOT1
Solar/Wind Harmer
0.382
3145453TOT5
Solar/Wind Harmer
0.229
3145603CNETO
Solar/Wind Harmer
0.153
3146173TUNIS
Solar/Wind Harmer
0.163
3146173TUNIS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
1.071
3145893MURPHYS
Solar/Wind Harmer
0.288
3145933PARMELE
Solar/Wind Harmer
0.262
3145933PARMELE
Solar/Wind Harmer
0.131
313527AB2-043 GEN
Solar/Wind Harmer
0.002
939181AE1-148 GEN
Solar/Wind Harmer
6.26
316065AD1-022 GEN
Solar/Wind Harmer
5.298
970323AG2-213 GEN
Solar/Wind Harmer
4.655
971775AH1-396 GEN
Solar/Wind Harmer
0.175
316034AC1-036 C
Solar/Wind Harmer
0.008
962561AG1-105 GEN
Solar/Wind Harmer
5
964791AG1-342 GEN
Solar/Wind Harmer
1.908
3146843MT LREL
Solar/Wind Harmer
0.099
3146843MT LREL
Solar/Wind Harmer
0.099
958211AF2-115 GEN
Solar/Wind Harmer
1.083
963191AG1-168 GEN
Solar/Wind Harmer
0.361
3147133PAMPLIN
Solar/Wind Harmer
0.084
3147133PAMPLIN
Solar/Wind Harmer
0.067
970099AG2-077 GEN
Solar/Wind Harmer
7.723
315742AE1-103 GEN
Solar/Wind Harmer
0.001
971741AH1-377 GEN
Solar/Wind Harmer
5.969
316222AC1-221 GEN
Solar/Wind Harmer
0.242
970301AG2-198 GEN
Solar/Wind Harmer
2.421
3144356SAPONY
Solar/Wind Helper
0.972
316240AF1-291 C
Solar/Wind Helper
0.168
CPLELTFEXP_CPLE->PJM
CLTF
4.45
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.218
LAGNLTFEXP_LAGN->PJM
CLTF
2.678
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.707
TVALTFEXP_TVA->PJM
CLTF
1.336
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.85
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.587
MECLTFEXP_MEC->PJM
CLTF
1.327
SIGELTFEXP_SIGE->PJM
CLTF
0.04
NYPJM->LTFIMP_NY
CLTF
0.49
LGEELTFEXP_LGEE->PJM
CLTF
0.481
WECLTFEXP_WEC->PJM
CLTF
0.25

Details for 6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.99 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:889.03
MW Contribution:6.8
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3151261ROARAP2
50/50
0.313
3151591KERR 2
50/50
0.27
3144293JTRSVLE
50/50
0.305
970413AG2-270 GEN
50/50
6.801
316365GEN2_N
Solar/Wind Harmer
1.155
313506AB2-031 GEN
Solar/Wind Harmer
1.049
3147043LAWRENC
Solar/Wind Harmer
0.196
3145796HORNRTN
Solar/Wind Harmer
1.268
3145796HORNRTN
Solar/Wind Harmer
0.317
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
315724AD1-057 GEN
Solar/Wind Harmer
0.907
316210AC1-098 GEN
Solar/Wind Harmer
1.821
316327AA2-057 GEN
Solar/Wind Harmer
0.289
3146263WOODLND
Solar/Wind Harmer
0.191
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.27
3151621KERR 5
50/50
0.27
3151631KERR 6
50/50
0.27
3151641KERR 7
50/50
0.27
3151151S HAMPT1
50/50
0.285
3151541CLOVER2
50/50
1.551
316087AB2-174 GEN
Solar/Wind Harmer
0.01
315652AC1-086 GEN
Solar/Wind Harmer
37.428
3145796HORNRTN
Solar/Wind Harmer
1.015
3145796HORNRTN
Solar/Wind Harmer
0.127
3137643SOCKMAN
Solar/Wind Harmer
1.176
315607AA1-063A GEN
Solar/Wind Harmer
0.444
3146043SEABORD
Solar/Wind Harmer
0.211
3146033SCOT NK
Solar/Wind Harmer
0.75
316319Z2-044 C
Solar/Wind Harmer
0
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.321
3144293JTRSVLE
50/50
0.305
3144293JTRSVLE
50/50
0.257
3152661PLYWOOD A
50/50
0.195
316181AB2-040 GEN
Solar/Wind Harmer
0.492
3145796HORNRTN
Solar/Wind Harmer
0.951
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3145593CAROLNA
Solar/Wind Harmer
0.257
3145593CAROLNA
Solar/Wind Harmer
0.257
966811AG1-552 GEN
Solar/Wind Harmer
2.785
3145593CAROLNA
Solar/Wind Harmer
0.32
3145783HORNRTN
Solar/Wind Harmer
4.428
3145783HORNRTN
Solar/Wind Harmer
3.543
3145783HORNRTN
Solar/Wind Harmer
1.107
3145783HORNRTN
Solar/Wind Harmer
0.443
316426AA2-053 GEN
Solar/Wind Harmer
0.813
316274AC1-208 GEN
Solar/Wind Harmer
1.081
961601AG1-000A GEN
Solar/Wind Harmer
3.201
316263AC1-034 GEN
Solar/Wind Harmer
6.707
3145493TOT1
Solar/Wind Harmer
0.382
3145453TOT5
Solar/Wind Harmer
0.229
3145603CNETO
Solar/Wind Harmer
0.153
3146173TUNIS
Solar/Wind Harmer
0.163
3146173TUNIS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
1.071
3145893MURPHYS
Solar/Wind Harmer
0.288
3145933PARMELE
Solar/Wind Harmer
0.262
3145933PARMELE
Solar/Wind Harmer
0.131
313527AB2-043 GEN
Solar/Wind Harmer
0.002
939181AE1-148 GEN
Solar/Wind Harmer
6.26
316065AD1-022 GEN
Solar/Wind Harmer
5.298
970323AG2-213 GEN
Solar/Wind Harmer
4.655
971775AH1-396 GEN
Solar/Wind Harmer
0.175
316034AC1-036 C
Solar/Wind Harmer
0.008
962561AG1-105 GEN
Solar/Wind Harmer
5
964791AG1-342 GEN
Solar/Wind Harmer
1.908
3146843MT LREL
Solar/Wind Harmer
0.099
3146843MT LREL
Solar/Wind Harmer
0.099
958211AF2-115 GEN
Solar/Wind Harmer
1.083
963191AG1-168 GEN
Solar/Wind Harmer
0.361
3147133PAMPLIN
Solar/Wind Harmer
0.084
3147133PAMPLIN
Solar/Wind Harmer
0.067
970099AG2-077 GEN
Solar/Wind Harmer
7.723
970933AG2-581 GEN
Solar/Wind Harmer
5.779
315742AE1-103 GEN
Solar/Wind Harmer
0.001
971741AH1-377 GEN
Solar/Wind Harmer
5.969
316222AC1-221 GEN
Solar/Wind Harmer
0.242
970301AG2-198 GEN
Solar/Wind Harmer
2.421
3144356SAPONY
Solar/Wind Helper
0.972
316240AF1-291 C
Solar/Wind Helper
0.168
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3147043LAWRENC
50/50
3.141
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.27
3151581KERR 1
50/50
0.096
3144293JTRSVLE
50/50
0.305
3151531CLOVER1
50/50
1.558
316023GEN1_S
Solar/Wind Harmer
1.155
960081AF2-299 GEN
Solar/Wind Harmer
3.965
971795AH1-408 GEN
Solar/Wind Harmer
23.615
316011AB1-132 GEN
Solar/Wind Harmer
6.186
962571AG1-106 GEN
Solar/Wind Harmer
4.841
3145796HORNRTN
Solar/Wind Harmer
1.046
3145796HORNRTN
Solar/Wind Harmer
0.317
3145783HORNRTN
Solar/Wind Harmer
0.249
315722AD1-056 GEN
Solar/Wind Harmer
1.531
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
1.015
3146263WOODLND
Solar/Wind Harmer
0.191
3146233WITAKRS
Solar/Wind Harmer
0.73
3145823KELFORD
Solar/Wind Harmer
0.177
316359AB2-059 GEN
Solar/Wind Harmer
0.634
316049AB1-081 GEN
Solar/Wind Harmer
1.01
3142053HEARTS
Solar/Wind Harmer
0.311
3145543BTLEBRO
Solar/Wind Harmer
0.175
3145543BTLEBRO
Solar/Wind Harmer
0.14
316129AC1-054 GEN
Solar/Wind Harmer
0.656
971065AG2-659 GEN
Solar/Wind Harmer
7.13
3145683EARLEYS
Solar/Wind Harmer
0.166
961671AG1-007 GEN
Solar/Wind Harmer
0.025
3146083TARBORO
Solar/Wind Harmer
0.165
3145493TOT1
Solar/Wind Harmer
0.732
3146173TUNIS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
0.64
3145893MURPHYS
Solar/Wind Harmer
0.712
316494AC1-189 GEN
Solar/Wind Harmer
0.514
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3146293MARTNCO
Solar/Wind Harmer
0.122
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.122
971547AH1-271 GEN
Solar/Wind Harmer
2.614
316174AB2-169 GEN
Solar/Wind Harmer
0.003
3145963POPLR C
Solar/Wind Harmer
0.118
970685AG2-442 GEN
Solar/Wind Harmer
7.425
970401AG2-262 GEN
Solar/Wind Harmer
0.583
963171AG1-166 GEN
Solar/Wind Harmer
0.482
971563AH1-280 GEN
Solar/Wind Harmer
0.963
3145663CRESWEL
Solar/Wind Harmer
0.224
971163AH1-040 GEN
Solar/Wind Harmer
6.407
957481AF2-042 GEN
Solar/Wind Harmer
19.308
316003AC1-222 GEN
Solar/Wind Harmer
0.002
315693AD1-088 GEN
Solar/Wind Harmer
3.442
315687AD1-152 GEN
Solar/Wind Harmer
0.002
962491AG1-098 GEN
Solar/Wind Harmer
4.048
3146233WITAKRS
Solar/Wind Harmer
0.921
3146233WITAKRS
Solar/Wind Harmer
0.125
3138543CONSLDL
Solar/Wind Harmer
0.12
961601AG1-000A GEN
Solar/Wind Harmer
12.805
316317KELFORD C
Solar/Wind Harmer
0.017
3145823KELFORD
Solar/Wind Harmer
0.177
971623AH1-311 GEN
Solar/Wind Harmer
0.353
3145543BTLEBRO
Solar/Wind Harmer
0.175
3145543BTLEBRO
Solar/Wind Harmer
0.175
316463AE2-346 GEN
Solar/Wind Harmer
0.142
316140AB2-099
Solar/Wind Harmer
0.059
962331AG1-082 GEN
Solar/Wind Harmer
1.76
3146073TAR RVR
Solar/Wind Harmer
0.165
3146083TARBORO
Solar/Wind Harmer
0.165
3146173TUNIS
Solar/Wind Harmer
0.163
957521AF2-046 GEN
Solar/Wind Harmer
11.982
961681AG1-008 GEN
Solar/Wind Harmer
11.982
3145893MURPHYS
Solar/Wind Harmer
0.268
3145893MURPHYS
Solar/Wind Harmer
0.16
3156021HOLLOMANSOL
Solar/Wind Harmer
0.689
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3145933PARMELE
Solar/Wind Harmer
0.131
966801AG1-551 GEN
Solar/Wind Harmer
1.529
316131AB2-060 GEN
Solar/Wind Harmer
0.407
964241AG1-285 GEN
Solar/Wind Harmer
8.211
3146206CASHIE
Solar/Wind Harmer
0.122
3145963POPLR C
Solar/Wind Harmer
0.118
315785AD2-033 C
Solar/Wind Harmer
0.918
970257AG2-171 GEN
Solar/Wind Harmer
3.491
959311AF2-222 GEN
Solar/Wind Harmer
9.454
315737AD1-076 GEN
Solar/Wind Harmer
1.314
971157AH1-035 GEN
Solar/Wind Harmer
1.183
963181AG1-167 GEN
Solar/Wind Harmer
0.361
3147133PAMPLIN
Solar/Wind Harmer
0.263
971193AH1-056 GEN
Solar/Wind Harmer
5.112
315614AA2-178 GEN
Solar/Wind Harmer
0.458
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.273
316478AD1-087 GEN
Solar/Wind Harmer
0.254
316486AD2-202 GEN
Solar/Wind Harmer
0.075
971683AH1-343 GEN
Solar/Wind Harmer
2.513
942461AE2-259 GEN
Solar/Wind Harmer
0
316283AC2-100 C
Solar/Wind Harmer
0.113
970909AG2-566 GEN
Solar/Wind Harmer
0.605
315839AE2-212 C
Solar/Wind Helper
0.197
970831AG2-522 GEN
Solar/Wind Harmer
7.783
3145683EARLEYS
Solar/Wind Harmer
0.333
3145683EARLEYS
Solar/Wind Harmer
0.166
3145683EARLEYS
Solar/Wind Harmer
0.166
3145513AHOSKIE
Solar/Wind Harmer
0.345
3145513AHOSKIE
Solar/Wind Harmer
0.165
3145573BETHELC
Solar/Wind Harmer
0.165
3145573BETHELC
Solar/Wind Harmer
0.165
3145893MURPHYS
Solar/Wind Harmer
0.432
3145893MURPHYS
Solar/Wind Harmer
0.16
316420AA1-050 GEN
Solar/Wind Harmer
0.005
965291AG1-394 GEN
Solar/Wind Harmer
0.698
957861AF2-080 GEN
Solar/Wind Harmer
6.563
316005AA1-067
Solar/Wind Harmer
0.148
3145746EVERETS
Solar/Wind Harmer
0.548
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
970181AG2-120 GEN
Solar/Wind Harmer
1.713
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.122
970601AG2-382 GEN
Solar/Wind Harmer
4.575
971443AH1-215 GEN
Solar/Wind Harmer
1.848
3144303KENBRDG
Solar/Wind Harmer
0.087
315732AD1-074 GEN1
Solar/Wind Harmer
0.587
315733AD1-074 GEN2
Solar/Wind Harmer
0.587
315735AD1-075 GEN1
Solar/Wind Harmer
0.294
970683AG2-441 GEN
Solar/Wind Harmer
6.63
970681AG2-440 GEN
Solar/Wind Harmer
5.304
3130546PLYMOUTH
Solar/Wind Harmer
0.098
946301AF1-294 GEN
Solar/Wind Harmer
1.782
961791AG1-021 GEN
Solar/Wind Harmer
0.867
316118AC1-105 GEN
Solar/Wind Harmer
0.227
315657AE1-056 GEN
Solar/Wind Harmer
2.895
315816AE2-034 GEN
Solar/Wind Harmer
0.344
3147173SINAI
Solar/Wind Harmer
0.077
3147243WELCO
Solar/Wind Harmer
0.048
971967AH1-528 GEN
Solar/Wind Harmer
11.557
970865AG2-541 GEN
Solar/Wind Harmer
2.227
316315AB2-025 C
Solar/Wind Helper
0.826
3143316POE
Solar/Wind Helper
0.688
CPLELTFEXP_CPLE->PJM
CLTF
4.45
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.218
LAGNLTFEXP_LAGN->PJM
CLTF
2.678
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.707
TVALTFEXP_TVA->PJM
CLTF
1.336
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.85
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.587
MECLTFEXP_MEC->PJM
CLTF
1.327
SIGELTFEXP_SIGE->PJM
CLTF
0.04
NYPJM->LTFIMP_NY
CLTF
0.49
LGEELTFEXP_LGEE->PJM
CLTF
0.481
WECLTFEXP_WEC->PJM
CLTF
0.25

Details for 6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.17 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:1002.46
MW Contribution:9.49
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.501
3144293JTRSVLE
50/50
0.422
970535AG2-341 GEN
50/50
1.338
3152661PLYWOOD A
50/50
0.156
971489AH1-241 GEN
Solar/Wind Harmer
15.103
3146776BUCKING
Solar/Wind Harmer
1.047
3146776BUCKING
Solar/Wind Harmer
0.085
315821AE2-092 GEN
Solar/Wind Harmer
0.012
970301AG2-198 GEN
Solar/Wind Harmer
7.451
971741AH1-377 GEN
Solar/Wind Harmer
16.073
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.126
958211AF2-115 GEN
Solar/Wind Harmer
1.778
3151931BEARGRDN S1
50/50
3.821
3151911BEARGRDN G1
50/50
2.961
3144293JTRSVLE
50/50
0.501
3151531CLOVER1
50/50
2.175
3151601KERR 3
50/50
0.134
3151581KERR 1
50/50
0.048
3143336POWHATN
Solar/Wind Harmer
12.647
316336AC2-165 C
Solar/Wind Harmer
0.025
970937AG2-583 GEN
Solar/Wind Harmer
28.662
972003AH1-546 GEN
Solar/Wind Harmer
13.092
971377AH1-170 GEN
Solar/Wind Harmer
3.021
3147623JAMES R
Solar/Wind Harmer
0.656
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
963171AG1-166 GEN
Solar/Wind Harmer
0.79
3151921BEARGRDN G2
50/50
2.961
3144293JTRSVLE
50/50
0.501
970413AG2-270 GEN
50/50
9.49
972205AH1-687 GEN
50/50
14.44
3151541CLOVER2
50/50
2.164
3151611KERR 4
50/50
0.134
3151621KERR 5
50/50
0.134
3151631KERR 6
50/50
0.134
3151641KERR 7
50/50
0.134
971447AH1-217 GEN
Solar/Wind Harmer
8.127
971845AH1-439 GEN
Solar/Wind Harmer
11.689
970285AG2-188 GEN
Solar/Wind Harmer
19.803
270494AE1-108_GEN
Solar/Wind Harmer
2.716
315657AE1-056 GEN
Solar/Wind Harmer
5.441
946301AF1-294 GEN
Solar/Wind Harmer
2.925
961791AG1-021 GEN
Solar/Wind Harmer
1.423
970683AG2-441 GEN
Solar/Wind Harmer
8.968
970681AG2-440 GEN
Solar/Wind Harmer
7.174
3144303KENBRDG
Solar/Wind Harmer
0.096
971443AH1-215 GEN
Solar/Wind Harmer
1.995
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.186
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.04
3147173SINAI
Solar/Wind Harmer
0.068
3147243WELCO
Solar/Wind Harmer
0.043
970865AG2-541 GEN
Solar/Wind Harmer
2.11
316233AE1-074 FULL
Solar/Wind Helper
0.382
316312AB1-027
Solar/Wind Helper
0.219
316132AB2-190 GEN1
Solar/Wind Helper
0.646
966251AG1-494 GEN
50/50
1.187
3151591KERR 2
50/50
0.134
316313AB2-026
Solar/Wind Harmer
0.448
316258AE1-075 C
Solar/Wind Harmer
0.537
316405AF2-144 C
Solar/Wind Harmer
0.005
3143336POWHATN
Solar/Wind Harmer
10.75
970221AG2-151 GEN
Solar/Wind Harmer
15.103
3146776BUCKING
Solar/Wind Harmer
0.094
3146926FARMVIL
Solar/Wind Harmer
0.129
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
1.863
3147133PAMPLIN
Solar/Wind Harmer
0.495
971193AH1-056 GEN
Solar/Wind Harmer
9.605
963181AG1-167 GEN
Solar/Wind Harmer
0.593
959311AF2-222 GEN
Solar/Wind Harmer
11.036
970257AG2-171 GEN
Solar/Wind Harmer
3.839
315785AD2-033 C
Solar/Wind Harmer
0.929
958131AF2-107 GEN
Solar/Wind Harmer
2.937
316478AD1-087 GEN
Solar/Wind Harmer
0.354
316486AD2-202 GEN
Solar/Wind Harmer
0.104
964241AG1-285 GEN
Solar/Wind Harmer
6.596
316131AB2-060 GEN
Solar/Wind Harmer
0.282
3148013FISHERV
Solar/Wind Harmer
0.07
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.906
971683AH1-343 GEN
Solar/Wind Harmer
2.326
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.716
315839AE2-212 C
Solar/Wind Helper
0.157
971563AH1-280 GEN
Solar/Wind Harmer
1.581
970685AG2-442 GEN
Solar/Wind Harmer
10.044
962491AG1-098 GEN
Solar/Wind Harmer
6.995
315693AD1-088 GEN
Solar/Wind Harmer
5.748
957481AF2-042 GEN
Solar/Wind Harmer
29.002
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.003
970401AG2-262 GEN
Solar/Wind Harmer
0.447
316003AC1-222 GEN
Solar/Wind Harmer
0.002
3143226MDLTHAN
Solar/Wind Helper
0.301
3143526WINTERP
Solar/Wind Helper
1.3
3142543TWELFTH
Solar/Wind Helper
0.014
3142416OLDCHRC
Solar/Wind Helper
0.299
3142416OLDCHRC
Solar/Wind Helper
0.115
316458AB2-190 GEN2
Solar/Wind Helper
0.646
3142433PROV 92
Solar/Wind Helper
0.449
963191AG1-168 GEN
Solar/Wind Harmer
0.593
316034AC1-036 C
Solar/Wind Harmer
0.009
970323AG2-213 GEN
Solar/Wind Harmer
5.119
971775AH1-396 GEN
Solar/Wind Harmer
0.192
970099AG2-077 GEN
Solar/Wind Harmer
11.601
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.739
964791AG1-342 GEN
Solar/Wind Harmer
1.463
3146843MT LREL
Solar/Wind Harmer
0.076
3146843MT LREL
Solar/Wind Harmer
0.076
939181AE1-148 GEN
Solar/Wind Harmer
3.296
3143526WINTERP
Solar/Wind Helper
1.3
316240AF1-291 C
Solar/Wind Helper
0.164
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.158
316075AC2-137 C
Solar/Wind Helper
0.174
CPLELTFEXP_CPLE->PJM
CLTF
0.56
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.43
LAGNLTFEXP_LAGN->PJM
CLTF
1.312
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.9
TVALTFEXP_TVA->PJM
CLTF
0.684
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.906
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.527
MECLTFEXP_MEC->PJM
CLTF
0.991
SIGELTFEXP_SIGE->PJM
CLTF
0.032
NYPJM->LTFIMP_NY
CLTF
0.361
LGEELTFEXP_LGEE->PJM
CLTF
0.427
WECLTFEXP_WEC->PJM
CLTF
0.217

Details for 6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.77 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:999.28
MW Contribution:9.49
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.501
3144293JTRSVLE
50/50
0.422
970535AG2-341 GEN
50/50
1.338
3152661PLYWOOD A
50/50
0.156
971489AH1-241 GEN
Solar/Wind Harmer
15.103
3146776BUCKING
Solar/Wind Harmer
1.047
3146776BUCKING
Solar/Wind Harmer
0.085
315821AE2-092 GEN
Solar/Wind Harmer
0.012
970301AG2-198 GEN
Solar/Wind Harmer
7.451
971741AH1-377 GEN
Solar/Wind Harmer
16.073
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.126
958211AF2-115 GEN
Solar/Wind Harmer
1.778
963191AG1-168 GEN
Solar/Wind Harmer
0.593
316034AC1-036 C
Solar/Wind Harmer
0.009
970323AG2-213 GEN
Solar/Wind Harmer
5.119
971775AH1-396 GEN
Solar/Wind Harmer
0.192
970933AG2-581 GEN
Solar/Wind Harmer
8.874
970099AG2-077 GEN
Solar/Wind Harmer
11.601
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.739
964791AG1-342 GEN
Solar/Wind Harmer
1.463
3146843MT LREL
Solar/Wind Harmer
0.076
3146843MT LREL
Solar/Wind Harmer
0.076
939181AE1-148 GEN
Solar/Wind Harmer
3.296
3143526WINTERP
Solar/Wind Helper
1.3
316240AF1-291 C
Solar/Wind Helper
0.164
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.158
316075AC2-137 C
Solar/Wind Helper
0.174
3151931BEARGRDN S1
50/50
3.821
3151911BEARGRDN G1
50/50
2.961
3144293JTRSVLE
50/50
0.501
3151531CLOVER1
50/50
2.175
3151601KERR 3
50/50
0.134
3151581KERR 1
50/50
0.048
3143336POWHATN
Solar/Wind Harmer
12.647
316336AC2-165 C
Solar/Wind Harmer
0.025
970937AG2-583 GEN
Solar/Wind Harmer
28.662
972003AH1-546 GEN
Solar/Wind Harmer
13.092
971377AH1-170 GEN
Solar/Wind Harmer
3.021
3147623JAMES R
Solar/Wind Harmer
0.656
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
963171AG1-166 GEN
Solar/Wind Harmer
0.79
971563AH1-280 GEN
Solar/Wind Harmer
1.581
970685AG2-442 GEN
Solar/Wind Harmer
10.044
962491AG1-098 GEN
Solar/Wind Harmer
6.995
972205AH1-687 GEN
50/50
14.44
3151541CLOVER2
50/50
2.164
3151611KERR 4
50/50
0.134
3151621KERR 5
50/50
0.134
3151631KERR 6
50/50
0.134
3151641KERR 7
50/50
0.134
971447AH1-217 GEN
Solar/Wind Harmer
8.127
971845AH1-439 GEN
Solar/Wind Harmer
11.689
970285AG2-188 GEN
Solar/Wind Harmer
19.803
270494AE1-108_GEN
Solar/Wind Harmer
2.716
315657AE1-056 GEN
Solar/Wind Harmer
5.441
946301AF1-294 GEN
Solar/Wind Harmer
2.925
961791AG1-021 GEN
Solar/Wind Harmer
1.423
970683AG2-441 GEN
Solar/Wind Harmer
8.968
970681AG2-440 GEN
Solar/Wind Harmer
7.174
3144303KENBRDG
Solar/Wind Harmer
0.096
971443AH1-215 GEN
Solar/Wind Harmer
1.995
971967AH1-528 GEN
Solar/Wind Harmer
17.746
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.186
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.04
3147173SINAI
Solar/Wind Harmer
0.068
3147243WELCO
Solar/Wind Harmer
0.043
970865AG2-541 GEN
Solar/Wind Harmer
2.11
316233AE1-074 FULL
Solar/Wind Helper
0.382
316312AB1-027
Solar/Wind Helper
0.219
316132AB2-190 GEN1
Solar/Wind Helper
0.646
3151921BEARGRDN G2
50/50
2.961
3144293JTRSVLE
50/50
0.501
970413AG2-270 GEN
50/50
9.49
966251AG1-494 GEN
50/50
1.187
3151591KERR 2
50/50
0.134
316313AB2-026
Solar/Wind Harmer
0.448
316258AE1-075 C
Solar/Wind Harmer
0.537
316405AF2-144 C
Solar/Wind Harmer
0.005
3143336POWHATN
Solar/Wind Harmer
10.75
970221AG2-151 GEN
Solar/Wind Harmer
15.103
3146776BUCKING
Solar/Wind Harmer
0.094
3146926FARMVIL
Solar/Wind Harmer
0.129
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
1.863
3147133PAMPLIN
Solar/Wind Harmer
0.495
971193AH1-056 GEN
Solar/Wind Harmer
9.605
963181AG1-167 GEN
Solar/Wind Harmer
0.593
959311AF2-222 GEN
Solar/Wind Harmer
11.036
970257AG2-171 GEN
Solar/Wind Harmer
3.839
315785AD2-033 C
Solar/Wind Harmer
0.929
958131AF2-107 GEN
Solar/Wind Harmer
2.937
316478AD1-087 GEN
Solar/Wind Harmer
0.354
316486AD2-202 GEN
Solar/Wind Harmer
0.104
964241AG1-285 GEN
Solar/Wind Harmer
6.596
316131AB2-060 GEN
Solar/Wind Harmer
0.282
3148013FISHERV
Solar/Wind Harmer
0.07
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.906
971683AH1-343 GEN
Solar/Wind Harmer
2.326
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.716
315839AE2-212 C
Solar/Wind Helper
0.157
315693AD1-088 GEN
Solar/Wind Harmer
5.748
957481AF2-042 GEN
Solar/Wind Harmer
29.002
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.003
970401AG2-262 GEN
Solar/Wind Harmer
0.447
316003AC1-222 GEN
Solar/Wind Harmer
0.002
3143226MDLTHAN
Solar/Wind Helper
0.301
3143526WINTERP
Solar/Wind Helper
1.3
3142543TWELFTH
Solar/Wind Helper
0.014
3142416OLDCHRC
Solar/Wind Helper
0.299
3142416OLDCHRC
Solar/Wind Helper
0.115
316458AB2-190 GEN2
Solar/Wind Helper
0.646
3142433PROV 92
Solar/Wind Helper
0.449
CPLELTFEXP_CPLE->PJM
CLTF
0.56
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.43
LAGNLTFEXP_LAGN->PJM
CLTF
1.312
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.9
TVALTFEXP_TVA->PJM
CLTF
0.684
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.906
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.527
MECLTFEXP_MEC->PJM
CLTF
0.991
SIGELTFEXP_SIGE->PJM
CLTF
0.032
NYPJM->LTFIMP_NY
CLTF
0.361
LGEELTFEXP_LGEE->PJM
CLTF
0.427
WECLTFEXP_WEC->PJM
CLTF
0.217

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:145.19 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:985.37
MW Contribution:6.79
Bus #Bus NameTypeMW Contribution
315779AE2-040
50/50
11.875
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.269
3151621KERR 5
50/50
0.269
3151631KERR 6
50/50
0.269
3151641KERR 7
50/50
0.269
3151151S HAMPT1
50/50
0.284
3151541CLOVER2
50/50
1.548
316315AB2-025 C
Solar/Wind Harmer
0.688
315814AE2-033 C
Solar/Wind Harmer
65.911
316087AB2-174 GEN
Solar/Wind Harmer
0.01
315652AC1-086 GEN
Solar/Wind Harmer
37.411
3145796HORNRTN
Solar/Wind Harmer
1.014
3145796HORNRTN
Solar/Wind Harmer
0.127
3137643SOCKMAN
Solar/Wind Harmer
1.175
315607AA1-063A GEN
Solar/Wind Harmer
0.444
3146043SEABORD
Solar/Wind Harmer
0.211
3146033SCOT NK
Solar/Wind Harmer
0.75
316319Z2-044 C
Solar/Wind Harmer
0
970831AG2-522 GEN
Solar/Wind Harmer
7.776
3145683EARLEYS
Solar/Wind Harmer
0.333
3145683EARLEYS
Solar/Wind Harmer
0.166
3145683EARLEYS
Solar/Wind Harmer
0.166
3145513AHOSKIE
Solar/Wind Harmer
0.345
3145513AHOSKIE
Solar/Wind Harmer
0.165
3145573BETHELC
Solar/Wind Harmer
0.164
3145573BETHELC
Solar/Wind Harmer
0.164
3145893MURPHYS
Solar/Wind Harmer
0.432
3145893MURPHYS
Solar/Wind Harmer
0.16
316420AA1-050 GEN
Solar/Wind Harmer
0.005
965291AG1-394 GEN
Solar/Wind Harmer
0.697
957861AF2-080 GEN
Solar/Wind Harmer
6.557
316005AA1-067
Solar/Wind Harmer
0.148
3145746EVERETS
Solar/Wind Harmer
0.547
3145746EVERETS
Solar/Wind Harmer
0.137
3145746EVERETS
Solar/Wind Harmer
0.137
3145746EVERETS
Solar/Wind Harmer
0.137
970181AG2-120 GEN
Solar/Wind Harmer
1.711
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.122
970601AG2-382 GEN
Solar/Wind Harmer
4.57
971443AH1-215 GEN
Solar/Wind Harmer
1.845
3144303KENBRDG
Solar/Wind Harmer
0.087
315732AD1-074 GEN1
Solar/Wind Harmer
0.586
315733AD1-074 GEN2
Solar/Wind Harmer
0.586
315735AD1-075 GEN1
Solar/Wind Harmer
0.293
970683AG2-441 GEN
Solar/Wind Harmer
6.62
970681AG2-440 GEN
Solar/Wind Harmer
5.296
3130546PLYMOUTH
Solar/Wind Harmer
0.098
946301AF1-294 GEN
Solar/Wind Harmer
1.779
961791AG1-021 GEN
Solar/Wind Harmer
0.865
316118AC1-105 GEN
Solar/Wind Harmer
0.226
315657AE1-056 GEN
Solar/Wind Harmer
2.89
315816AE2-034 GEN
Solar/Wind Harmer
0.343
3151391GASTONA
50/50
0.92
3151411GASTONB
50/50
0.92
3147043LAWRENC
50/50
3.139
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.269
3151581KERR 1
50/50
0.096
3144293JTRSVLE
50/50
0.304
3151531CLOVER1
50/50
1.555
316023GEN1_S
Solar/Wind Harmer
1.155
960081AF2-299 GEN
Solar/Wind Harmer
3.963
971795AH1-408 GEN
Solar/Wind Harmer
23.605
316011AB1-132 GEN
Solar/Wind Harmer
6.184
962571AG1-106 GEN
Solar/Wind Harmer
4.839
3145796HORNRTN
Solar/Wind Harmer
1.046
3145796HORNRTN
Solar/Wind Harmer
0.317
3145783HORNRTN
Solar/Wind Harmer
0.249
315722AD1-056 GEN
Solar/Wind Harmer
1.53
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
1.015
3146263WOODLND
Solar/Wind Harmer
0.191
3146233WITAKRS
Solar/Wind Harmer
0.73
3145823KELFORD
Solar/Wind Harmer
0.177
316359AB2-059 GEN
Solar/Wind Harmer
0.633
316049AB1-081 GEN
Solar/Wind Harmer
1.009
3142053HEARTS
Solar/Wind Harmer
0.311
3145543BTLEBRO
Solar/Wind Harmer
0.175
3145543BTLEBRO
Solar/Wind Harmer
0.14
316129AC1-054 GEN
Solar/Wind Harmer
0.656
971065AG2-659 GEN
Solar/Wind Harmer
7.123
3145683EARLEYS
Solar/Wind Harmer
0.166
961671AG1-007 GEN
Solar/Wind Harmer
0.025
3146083TARBORO
Solar/Wind Harmer
0.164
3145493TOT1
Solar/Wind Harmer
0.732
3146173TUNIS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
0.639
3145893MURPHYS
Solar/Wind Harmer
0.711
316494AC1-189 GEN
Solar/Wind Harmer
0.514
3145746EVERETS
Solar/Wind Harmer
0.137
3145746EVERETS
Solar/Wind Harmer
0.137
3146293MARTNCO
Solar/Wind Harmer
0.122
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.122
971547AH1-271 GEN
Solar/Wind Harmer
2.611
3147173SINAI
Solar/Wind Harmer
0.076
3147243WELCO
Solar/Wind Harmer
0.048
970865AG2-541 GEN
Solar/Wind Harmer
2.221
3143316POE
Solar/Wind Helper
0.689
3151391GASTONA
50/50
0.92
3151411GASTONB
50/50
0.92
3151261ROARAP2
50/50
0.312
3151591KERR 2
50/50
0.269
3144293JTRSVLE
50/50
0.304
970413AG2-270 GEN
50/50
6.787
316365GEN2_N
Solar/Wind Harmer
1.155
313506AB2-031 GEN
Solar/Wind Harmer
1.048
316174AB2-169 GEN
Solar/Wind Harmer
0.003
3145963POPLR C
Solar/Wind Harmer
0.117
970685AG2-442 GEN
Solar/Wind Harmer
7.414
970401AG2-262 GEN
Solar/Wind Harmer
0.582
963171AG1-166 GEN
Solar/Wind Harmer
0.481
971563AH1-280 GEN
Solar/Wind Harmer
0.961
3145663CRESWEL
Solar/Wind Harmer
0.224
971163AH1-040 GEN
Solar/Wind Harmer
6.395
957481AF2-042 GEN
Solar/Wind Harmer
19.267
316003AC1-222 GEN
Solar/Wind Harmer
0.002
315693AD1-088 GEN
Solar/Wind Harmer
3.435
315687AD1-152 GEN
Solar/Wind Harmer
0.002
962491AG1-098 GEN
Solar/Wind Harmer
4.04
3147043LAWRENC
Solar/Wind Harmer
0.196
3145796HORNRTN
Solar/Wind Harmer
1.267
3145796HORNRTN
Solar/Wind Harmer
0.317
3142666NORTHAMPTON
Solar/Wind Harmer
0.314
315724AD1-057 GEN
Solar/Wind Harmer
0.907
316210AC1-098 GEN
Solar/Wind Harmer
1.819
316327AA2-057 GEN
Solar/Wind Harmer
0.289
3146263WOODLND
Solar/Wind Harmer
0.191
3146233WITAKRS
Solar/Wind Harmer
0.92
3146233WITAKRS
Solar/Wind Harmer
0.125
3138543CONSLDL
Solar/Wind Harmer
0.12
961601AG1-000A GEN
Solar/Wind Harmer
12.794
316317KELFORD C
Solar/Wind Harmer
0.017
3145823KELFORD
Solar/Wind Harmer
0.177
971623AH1-311 GEN
Solar/Wind Harmer
0.353
3145543BTLEBRO
Solar/Wind Harmer
0.175
3145543BTLEBRO
Solar/Wind Harmer
0.175
316463AE2-346 GEN
Solar/Wind Harmer
0.142
316140AB2-099
Solar/Wind Harmer
0.059
962331AG1-082 GEN
Solar/Wind Harmer
1.759
3146073TAR RVR
Solar/Wind Harmer
0.164
3146083TARBORO
Solar/Wind Harmer
0.164
3146173TUNIS
Solar/Wind Harmer
0.163
957521AF2-046 GEN
Solar/Wind Harmer
11.971
961681AG1-008 GEN
Solar/Wind Harmer
11.971
3145893MURPHYS
Solar/Wind Harmer
0.268
3145893MURPHYS
Solar/Wind Harmer
0.16
3156021HOLLOMANSOL
Solar/Wind Harmer
0.688
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
3145746EVERETS
Solar/Wind Harmer
0.137
3145746EVERETS
Solar/Wind Harmer
0.137
3145933PARMELE
Solar/Wind Harmer
0.131
966801AG1-551 GEN
Solar/Wind Harmer
1.527
316131AB2-060 GEN
Solar/Wind Harmer
0.406
964241AG1-285 GEN
Solar/Wind Harmer
8.201
3146206CASHIE
Solar/Wind Harmer
0.122
3145963POPLR C
Solar/Wind Harmer
0.117
315785AD2-033 C
Solar/Wind Harmer
0.917
970257AG2-171 GEN
Solar/Wind Harmer
3.486
959311AF2-222 GEN
Solar/Wind Harmer
9.44
315737AD1-076 GEN
Solar/Wind Harmer
1.312
971157AH1-035 GEN
Solar/Wind Harmer
1.181
963181AG1-167 GEN
Solar/Wind Harmer
0.361
3147133PAMPLIN
Solar/Wind Harmer
0.263
971193AH1-056 GEN
Solar/Wind Harmer
5.102
315614AA2-178 GEN
Solar/Wind Harmer
0.457
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.266
316478AD1-087 GEN
Solar/Wind Harmer
0.254
316486AD2-202 GEN
Solar/Wind Harmer
0.074
971683AH1-343 GEN
Solar/Wind Harmer
2.507
942461AE2-259 GEN
Solar/Wind Harmer
0
316283AC2-100 C
Solar/Wind Harmer
0.113
970909AG2-566 GEN
Solar/Wind Harmer
0.604
315839AE2-212 C
Solar/Wind Helper
0.198
3151361ROSEMG1
50/50
1.142
3151371ROSEMS1
50/50
0.707
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.318
3144293JTRSVLE
50/50
0.304
3144293JTRSVLE
50/50
0.256
3152661PLYWOOD A
50/50
0.195
3144356SAPONY
Solar/Wind Harmer
7.116
316181AB2-040 GEN
Solar/Wind Harmer
0.492
3145796HORNRTN
Solar/Wind Harmer
0.951
3142666NORTHAMPTON
Solar/Wind Harmer
0.314
3142666NORTHAMPTON
Solar/Wind Harmer
0.314
3142666NORTHAMPTON
Solar/Wind Harmer
0.314
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3145593CAROLNA
Solar/Wind Harmer
0.256
3145593CAROLNA
Solar/Wind Harmer
0.256
966811AG1-552 GEN
Solar/Wind Harmer
2.783
3145593CAROLNA
Solar/Wind Harmer
0.319
3145783HORNRTN
Solar/Wind Harmer
4.426
3145783HORNRTN
Solar/Wind Harmer
3.54
3145783HORNRTN
Solar/Wind Harmer
1.106
3145783HORNRTN
Solar/Wind Harmer
0.443
316426AA2-053 GEN
Solar/Wind Harmer
0.812
316274AC1-208 GEN
Solar/Wind Harmer
1.08
961601AG1-000A GEN
Solar/Wind Harmer
3.199
316263AC1-034 GEN
Solar/Wind Harmer
6.701
3145493TOT1
Solar/Wind Harmer
0.381
3145453TOT5
Solar/Wind Harmer
0.229
3145603CNETO
Solar/Wind Harmer
0.153
3146173TUNIS
Solar/Wind Harmer
0.163
3146173TUNIS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
1.07
3145893MURPHYS
Solar/Wind Harmer
0.288
3145933PARMELE
Solar/Wind Harmer
0.262
3145933PARMELE
Solar/Wind Harmer
0.131
313527AB2-043 GEN
Solar/Wind Harmer
0.002
939181AE1-148 GEN
Solar/Wind Harmer
6.253
316065AD1-022 GEN
Solar/Wind Harmer
5.291
970323AG2-213 GEN
Solar/Wind Harmer
4.648
971775AH1-396 GEN
Solar/Wind Harmer
0.174
316034AC1-036 C
Solar/Wind Harmer
0.008
962561AG1-105 GEN
Solar/Wind Harmer
4.993
964791AG1-342 GEN
Solar/Wind Harmer
1.905
3146843MT LREL
Solar/Wind Harmer
0.099
3146843MT LREL
Solar/Wind Harmer
0.099
958211AF2-115 GEN
Solar/Wind Harmer
1.082
963191AG1-168 GEN
Solar/Wind Harmer
0.361
3147133PAMPLIN
Solar/Wind Harmer
0.084
3147133PAMPLIN
Solar/Wind Harmer
0.067
970099AG2-077 GEN
Solar/Wind Harmer
7.707
315742AE1-103 GEN
Solar/Wind Harmer
0.001
971741AH1-377 GEN
Solar/Wind Harmer
5.954
316222AC1-221 GEN
Solar/Wind Harmer
0.241
970301AG2-198 GEN
Solar/Wind Harmer
2.414
316240AF1-291 C
Solar/Wind Helper
0.169
CPLELTFEXP_CPLE->PJM
CLTF
4.437
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.06
LAGNLTFEXP_LAGN->PJM
CLTF
2.654
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.672
TVALTFEXP_TVA->PJM
CLTF
1.324
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.679
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.543
MECLTFEXP_MEC->PJM
CLTF
1.307
SIGELTFEXP_SIGE->PJM
CLTF
0.039
NYPJM->LTFIMP_NY
CLTF
0.497
LGEELTFEXP_LGEE->PJM
CLTF
0.473
WECLTFEXP_WEC->PJM
CLTF
0.246

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:144.54 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:980.94
MW Contribution:6.79
Bus #Bus NameTypeMW Contribution
315779AE2-040
50/50
11.875
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.269
3151621KERR 5
50/50
0.269
3151631KERR 6
50/50
0.269
3151641KERR 7
50/50
0.269
3151151S HAMPT1
50/50
0.284
3151541CLOVER2
50/50
1.548
316315AB2-025 C
Solar/Wind Harmer
0.688
315814AE2-033 C
Solar/Wind Harmer
65.911
316087AB2-174 GEN
Solar/Wind Harmer
0.01
315652AC1-086 GEN
Solar/Wind Harmer
37.411
3145796HORNRTN
Solar/Wind Harmer
1.014
3145796HORNRTN
Solar/Wind Harmer
0.127
3137643SOCKMAN
Solar/Wind Harmer
1.175
315607AA1-063A GEN
Solar/Wind Harmer
0.444
3146043SEABORD
Solar/Wind Harmer
0.211
3146033SCOT NK
Solar/Wind Harmer
0.75
316319Z2-044 C
Solar/Wind Harmer
0
970831AG2-522 GEN
Solar/Wind Harmer
7.776
3145683EARLEYS
Solar/Wind Harmer
0.333
3151391GASTONA
50/50
0.92
3151411GASTONB
50/50
0.92
3151261ROARAP2
50/50
0.312
3151591KERR 2
50/50
0.269
3144293JTRSVLE
50/50
0.304
970413AG2-270 GEN
50/50
6.787
3145683EARLEYS
Solar/Wind Harmer
0.166
3145683EARLEYS
Solar/Wind Harmer
0.166
3145513AHOSKIE
Solar/Wind Harmer
0.345
3145513AHOSKIE
Solar/Wind Harmer
0.165
3145573BETHELC
Solar/Wind Harmer
0.164
3145573BETHELC
Solar/Wind Harmer
0.164
3145893MURPHYS
Solar/Wind Harmer
0.432
3145893MURPHYS
Solar/Wind Harmer
0.16
316420AA1-050 GEN
Solar/Wind Harmer
0.005
965291AG1-394 GEN
Solar/Wind Harmer
0.697
957861AF2-080 GEN
Solar/Wind Harmer
6.557
316005AA1-067
Solar/Wind Harmer
0.148
3145746EVERETS
Solar/Wind Harmer
0.547
3145746EVERETS
Solar/Wind Harmer
0.137
3145746EVERETS
Solar/Wind Harmer
0.137
3145746EVERETS
Solar/Wind Harmer
0.137
970181AG2-120 GEN
Solar/Wind Harmer
1.711
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.122
970601AG2-382 GEN
Solar/Wind Harmer
4.57
971443AH1-215 GEN
Solar/Wind Harmer
1.845
3144303KENBRDG
Solar/Wind Harmer
0.087
315732AD1-074 GEN1
Solar/Wind Harmer
0.586
315733AD1-074 GEN2
Solar/Wind Harmer
0.586
315735AD1-075 GEN1
Solar/Wind Harmer
0.293
970683AG2-441 GEN
Solar/Wind Harmer
6.62
970681AG2-440 GEN
Solar/Wind Harmer
5.296
3130546PLYMOUTH
Solar/Wind Harmer
0.098
946301AF1-294 GEN
Solar/Wind Harmer
1.779
961791AG1-021 GEN
Solar/Wind Harmer
0.865
316118AC1-105 GEN
Solar/Wind Harmer
0.226
315657AE1-056 GEN
Solar/Wind Harmer
2.89
315816AE2-034 GEN
Solar/Wind Harmer
0.343
3147173SINAI
Solar/Wind Harmer
0.076
3147243WELCO
Solar/Wind Harmer
0.048
971967AH1-528 GEN
Solar/Wind Harmer
11.533
970865AG2-541 GEN
Solar/Wind Harmer
2.221
3143316POE
Solar/Wind Helper
0.689
316365GEN2_N
Solar/Wind Harmer
1.155
313506AB2-031 GEN
Solar/Wind Harmer
1.048
3147043LAWRENC
Solar/Wind Harmer
0.196
3145796HORNRTN
Solar/Wind Harmer
1.267
3145796HORNRTN
Solar/Wind Harmer
0.317
3142666NORTHAMPTON
Solar/Wind Harmer
0.314
315724AD1-057 GEN
Solar/Wind Harmer
0.907
316210AC1-098 GEN
Solar/Wind Harmer
1.819
316327AA2-057 GEN
Solar/Wind Harmer
0.289
3146263WOODLND
Solar/Wind Harmer
0.191
3146233WITAKRS
Solar/Wind Harmer
0.92
3146233WITAKRS
Solar/Wind Harmer
0.125
3138543CONSLDL
Solar/Wind Harmer
0.12
961601AG1-000A GEN
Solar/Wind Harmer
12.794
316317KELFORD C
Solar/Wind Harmer
0.017
3145823KELFORD
Solar/Wind Harmer
0.177
971623AH1-311 GEN
Solar/Wind Harmer
0.353
3145543BTLEBRO
Solar/Wind Harmer
0.175
3145543BTLEBRO
Solar/Wind Harmer
0.175
3151391GASTONA
50/50
0.92
3151411GASTONB
50/50
0.92
3147043LAWRENC
50/50
3.139
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.269
3151581KERR 1
50/50
0.096
3144293JTRSVLE
50/50
0.304
3151531CLOVER1
50/50
1.555
316023GEN1_S
Solar/Wind Harmer
1.155
960081AF2-299 GEN
Solar/Wind Harmer
3.963
971795AH1-408 GEN
Solar/Wind Harmer
23.605
316011AB1-132 GEN
Solar/Wind Harmer
6.184
962571AG1-106 GEN
Solar/Wind Harmer
4.839
3145796HORNRTN
Solar/Wind Harmer
1.046
3145796HORNRTN
Solar/Wind Harmer
0.317
3145783HORNRTN
Solar/Wind Harmer
0.249
315722AD1-056 GEN
Solar/Wind Harmer
1.53
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
1.015
3146263WOODLND
Solar/Wind Harmer
0.191
3146233WITAKRS
Solar/Wind Harmer
0.73
3145823KELFORD
Solar/Wind Harmer
0.177
316359AB2-059 GEN
Solar/Wind Harmer
0.633
316049AB1-081 GEN
Solar/Wind Harmer
1.009
3142053HEARTS
Solar/Wind Harmer
0.311
3145543BTLEBRO
Solar/Wind Harmer
0.175
3145543BTLEBRO
Solar/Wind Harmer
0.14
316129AC1-054 GEN
Solar/Wind Harmer
0.656
971065AG2-659 GEN
Solar/Wind Harmer
7.123
3145683EARLEYS
Solar/Wind Harmer
0.166
961671AG1-007 GEN
Solar/Wind Harmer
0.025
3146083TARBORO
Solar/Wind Harmer
0.164
3145493TOT1
Solar/Wind Harmer
0.732
3146173TUNIS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
0.639
3145893MURPHYS
Solar/Wind Harmer
0.711
316494AC1-189 GEN
Solar/Wind Harmer
0.514
3145746EVERETS
Solar/Wind Harmer
0.137
3145746EVERETS
Solar/Wind Harmer
0.137
3146293MARTNCO
Solar/Wind Harmer
0.122
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.122
971547AH1-271 GEN
Solar/Wind Harmer
2.611
316174AB2-169 GEN
Solar/Wind Harmer
0.003
3145963POPLR C
Solar/Wind Harmer
0.117
970685AG2-442 GEN
Solar/Wind Harmer
7.414
970401AG2-262 GEN
Solar/Wind Harmer
0.582
963171AG1-166 GEN
Solar/Wind Harmer
0.481
971563AH1-280 GEN
Solar/Wind Harmer
0.961
3145663CRESWEL
Solar/Wind Harmer
0.224
971163AH1-040 GEN
Solar/Wind Harmer
6.395
957481AF2-042 GEN
Solar/Wind Harmer
19.267
316003AC1-222 GEN
Solar/Wind Harmer
0.002
315693AD1-088 GEN
Solar/Wind Harmer
3.435
315687AD1-152 GEN
Solar/Wind Harmer
0.002
962491AG1-098 GEN
Solar/Wind Harmer
4.04
316463AE2-346 GEN
Solar/Wind Harmer
0.142
316140AB2-099
Solar/Wind Harmer
0.059
962331AG1-082 GEN
Solar/Wind Harmer
1.759
3146073TAR RVR
Solar/Wind Harmer
0.164
3146083TARBORO
Solar/Wind Harmer
0.164
3146173TUNIS
Solar/Wind Harmer
0.163
957521AF2-046 GEN
Solar/Wind Harmer
11.971
961681AG1-008 GEN
Solar/Wind Harmer
11.971
3145893MURPHYS
Solar/Wind Harmer
0.268
3145893MURPHYS
Solar/Wind Harmer
0.16
3156021HOLLOMANSOL
Solar/Wind Harmer
0.688
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
3145746EVERETS
Solar/Wind Harmer
0.137
3145746EVERETS
Solar/Wind Harmer
0.137
3145933PARMELE
Solar/Wind Harmer
0.131
966801AG1-551 GEN
Solar/Wind Harmer
1.527
316131AB2-060 GEN
Solar/Wind Harmer
0.406
964241AG1-285 GEN
Solar/Wind Harmer
8.201
3146206CASHIE
Solar/Wind Harmer
0.122
3145963POPLR C
Solar/Wind Harmer
0.117
315785AD2-033 C
Solar/Wind Harmer
0.917
970257AG2-171 GEN
Solar/Wind Harmer
3.486
959311AF2-222 GEN
Solar/Wind Harmer
9.44
315737AD1-076 GEN
Solar/Wind Harmer
1.312
971157AH1-035 GEN
Solar/Wind Harmer
1.181
963181AG1-167 GEN
Solar/Wind Harmer
0.361
3147133PAMPLIN
Solar/Wind Harmer
0.263
971193AH1-056 GEN
Solar/Wind Harmer
5.102
315614AA2-178 GEN
Solar/Wind Harmer
0.457
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.266
316478AD1-087 GEN
Solar/Wind Harmer
0.254
316486AD2-202 GEN
Solar/Wind Harmer
0.074
971683AH1-343 GEN
Solar/Wind Harmer
2.507
942461AE2-259 GEN
Solar/Wind Harmer
0
316283AC2-100 C
Solar/Wind Harmer
0.113
970909AG2-566 GEN
Solar/Wind Harmer
0.604
315839AE2-212 C
Solar/Wind Helper
0.198
3151361ROSEMG1
50/50
1.142
3151371ROSEMS1
50/50
0.707
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.318
3144293JTRSVLE
50/50
0.304
3144293JTRSVLE
50/50
0.256
3152661PLYWOOD A
50/50
0.195
3144356SAPONY
Solar/Wind Harmer
7.116
316181AB2-040 GEN
Solar/Wind Harmer
0.492
3145796HORNRTN
Solar/Wind Harmer
0.951
3142666NORTHAMPTON
Solar/Wind Harmer
0.314
3142666NORTHAMPTON
Solar/Wind Harmer
0.314
3142666NORTHAMPTON
Solar/Wind Harmer
0.314
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3145593CAROLNA
Solar/Wind Harmer
0.256
3145593CAROLNA
Solar/Wind Harmer
0.256
966811AG1-552 GEN
Solar/Wind Harmer
2.783
3145593CAROLNA
Solar/Wind Harmer
0.319
3145783HORNRTN
Solar/Wind Harmer
4.426
3145783HORNRTN
Solar/Wind Harmer
3.54
3145783HORNRTN
Solar/Wind Harmer
1.106
3145783HORNRTN
Solar/Wind Harmer
0.443
316426AA2-053 GEN
Solar/Wind Harmer
0.812
316274AC1-208 GEN
Solar/Wind Harmer
1.08
961601AG1-000A GEN
Solar/Wind Harmer
3.199
316263AC1-034 GEN
Solar/Wind Harmer
6.701
3145493TOT1
Solar/Wind Harmer
0.381
3145453TOT5
Solar/Wind Harmer
0.229
3145603CNETO
Solar/Wind Harmer
0.153
3146173TUNIS
Solar/Wind Harmer
0.163
3146173TUNIS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
1.07
3145893MURPHYS
Solar/Wind Harmer
0.288
3145933PARMELE
Solar/Wind Harmer
0.262
3145933PARMELE
Solar/Wind Harmer
0.131
313527AB2-043 GEN
Solar/Wind Harmer
0.002
939181AE1-148 GEN
Solar/Wind Harmer
6.253
316065AD1-022 GEN
Solar/Wind Harmer
5.291
970323AG2-213 GEN
Solar/Wind Harmer
4.648
971775AH1-396 GEN
Solar/Wind Harmer
0.174
316034AC1-036 C
Solar/Wind Harmer
0.008
962561AG1-105 GEN
Solar/Wind Harmer
4.993
964791AG1-342 GEN
Solar/Wind Harmer
1.905
3146843MT LREL
Solar/Wind Harmer
0.099
3146843MT LREL
Solar/Wind Harmer
0.099
958211AF2-115 GEN
Solar/Wind Harmer
1.082
963191AG1-168 GEN
Solar/Wind Harmer
0.361
3147133PAMPLIN
Solar/Wind Harmer
0.084
3147133PAMPLIN
Solar/Wind Harmer
0.067
970099AG2-077 GEN
Solar/Wind Harmer
7.707
970933AG2-581 GEN
Solar/Wind Harmer
5.767
315742AE1-103 GEN
Solar/Wind Harmer
0.001
971741AH1-377 GEN
Solar/Wind Harmer
5.954
316222AC1-221 GEN
Solar/Wind Harmer
0.241
970301AG2-198 GEN
Solar/Wind Harmer
2.414
316240AF1-291 C
Solar/Wind Helper
0.169
CPLELTFEXP_CPLE->PJM
CLTF
4.437
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.06
LAGNLTFEXP_LAGN->PJM
CLTF
2.654
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.672
TVALTFEXP_TVA->PJM
CLTF
1.324
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.679
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.543
MECLTFEXP_MEC->PJM
CLTF
1.307
SIGELTFEXP_SIGE->PJM
CLTF
0.039
NYPJM->LTFIMP_NY
CLTF
0.497
LGEELTFEXP_LGEE->PJM
CLTF
0.473
WECLTFEXP_WEC->PJM
CLTF
0.246

Details for 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.88 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1203.12
MW Contribution:47.2
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
10.817
3144293JTRSVLE
50/50
1.01
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3147043LAWRENC
50/50
1.438
3151561HALLBR1
50/50
0.348
3151931BEARGRDN S1
50/50
1.386
3151911BEARGRDN G1
50/50
1.074
315687AD1-152 GEN
Solar/Wind Harmer
7.758
316003AC1-222 GEN
Solar/Wind Harmer
5.37
957481AF2-042 GEN
Solar/Wind Harmer
169.864
315693AD1-088 GEN
Solar/Wind Harmer
25.266
962491AG1-098 GEN
Solar/Wind Harmer
33.395
970401AG2-262 GEN
Solar/Wind Harmer
3.255
316237AB2-079_GEN
Solar/Wind Harmer
1.109
970685AG2-442 GEN
Solar/Wind Harmer
29.964
963171AG1-166 GEN
Solar/Wind Harmer
4.201
971563AH1-280 GEN
Solar/Wind Harmer
4.201
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.371
316322AB2-045
Solar/Wind Harmer
0.76
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.88
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.352
971795AH1-408 GEN
Solar/Wind Harmer
10.596
3147312GRETNA
Solar/Wind Harmer
-0.01
3152661PLYWOOD A
50/50
1.087
3144293JTRSVLE
50/50
1.01
3144293JTRSVLE
50/50
0.851
970535AG2-341 GEN
50/50
5.156
970099AG2-077 GEN
Solar/Wind Harmer
67.945
970933AG2-581 GEN
Solar/Wind Harmer
50.247
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.651
3151541CLOVER2
50/50
10.765
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
972205AH1-687 GEN
50/50
5.237
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.767
971967AH1-528 GEN
Solar/Wind Harmer
100.764
970865AG2-541 GEN
Solar/Wind Harmer
19.09
316123AC1-075 GEN
Solar/Wind Harmer
4.175
970165AG2-112 GEN
Solar/Wind Harmer
3.676
970163AG2-111 GEN
Solar/Wind Harmer
3.506
316239AB2-077_GEN
Solar/Wind Harmer
1.109
316238AB2-078_GEN
Solar/Wind Harmer
1.109
971443AH1-215 GEN
Solar/Wind Harmer
6.887
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.754
970681AG2-440 GEN
Solar/Wind Harmer
21.403
946301AF1-294 GEN
Solar/Wind Harmer
8.613
961791AG1-021 GEN
Solar/Wind Harmer
4.201
315657AE1-056 GEN
Solar/Wind Harmer
12.436
970285AG2-188 GEN
Solar/Wind Harmer
21.464
971845AH1-439 GEN
Solar/Wind Harmer
12.355
970831AG2-522 GEN
Solar/Wind Harmer
10.03
971447AH1-217 GEN
Solar/Wind Harmer
3.932
270494AE1-108_GEN
Solar/Wind Harmer
2.515
946281AF1-292 GEN
Solar/Wind Harmer
0.185
316087AB2-174 GEN
Solar/Wind Harmer
1.12
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.372
270457AD2-023 GEN
Solar/Wind Helper
0.904
970413AG2-270 GEN
50/50
47.203
3144293JTRSVLE
50/50
1.01
3151591KERR 2
50/50
0.537
3151921BEARGRDN G2
50/50
1.074
316248AF1-058 C
Solar/Wind Harmer
1.794
960061AF2-297 GEN
Solar/Wind Harmer
29.766
316478AD1-087 GEN
Solar/Wind Harmer
4.933
316486AD2-202 GEN
Solar/Wind Harmer
1.445
971683AH1-343 GEN
Solar/Wind Harmer
22.023
970909AG2-566 GEN
Solar/Wind Harmer
3.703
316131AB2-060 GEN
Solar/Wind Harmer
3.921
964241AG1-285 GEN
Solar/Wind Harmer
28.048
315785AD2-033 C
Solar/Wind Harmer
7.977
970257AG2-171 GEN
Solar/Wind Harmer
13.098
959311AF2-222 GEN
Solar/Wind Harmer
36.247
963181AG1-167 GEN
Solar/Wind Harmer
3.151
3147133PAMPLIN
Solar/Wind Harmer
-0.104
971193AH1-056 GEN
Solar/Wind Harmer
20.727
942461AE2-259 GEN
Solar/Wind Harmer
4.793
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.538
970221AG2-151 GEN
Solar/Wind Harmer
7.287
966621AG1-532 GEN
Solar/Wind Harmer
0.168
313506AB2-031 GEN
Solar/Wind Harmer
0.617
316313AB2-026
Solar/Wind Harmer
0.177
316258AE1-075 C
Solar/Wind Harmer
0.159
316405AF2-144 C
Solar/Wind Harmer
0.168
3143336POWHATN
Solar/Wind Harmer
0.661
316283AC2-100 C
Solar/Wind Helper
2.321
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.538
971377AH1-170 GEN
Solar/Wind Harmer
1.457
3147623JAMES R
Solar/Wind Harmer
0.18
970937AG2-583 GEN
Solar/Wind Harmer
7.58
960081AF2-299 GEN
Solar/Wind Harmer
0.929
316336AC2-165 C
Solar/Wind Harmer
1.333
3143336POWHATN
Solar/Wind Harmer
0.777
962561AG1-105 GEN
Solar/Wind Harmer
26.897
971741AH1-377 GEN
Solar/Wind Harmer
48.415
970301AG2-198 GEN
Solar/Wind Harmer
19.501
313527AB2-043 GEN
Solar/Wind Harmer
5.92
970323AG2-213 GEN
Solar/Wind Harmer
17.464
971775AH1-396 GEN
Solar/Wind Harmer
2.487
316034AC1-036 C
Solar/Wind Harmer
0.648
958211AF2-115 GEN
Solar/Wind Harmer
5.252
963191AG1-168 GEN
Solar/Wind Harmer
3.151
942751AE2-291 GEN
Solar/Wind Harmer
21.312
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.148
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.964
316197AC1-042 GEN
Solar/Wind Harmer
1.489
942671AE2-283 GEN
Solar/Wind Harmer
4.009
971489AH1-241 GEN
Solar/Wind Harmer
6.918
315821AE2-092 GEN
Solar/Wind Harmer
1.803
316181AB2-040 GEN
Solar/Wind Harmer
1.071
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.79
3145593CAROLNA
Solar/Wind Harmer
0.058
316222AC1-221 GEN
Solar/Wind Helper
2.556
G-007ALTFEXP_G-007A->PJM
CMTX
0.495
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.478
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.834
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.63
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.304
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.8
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.891
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.359

Details for 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.72 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1179.24
MW Contribution:47.11
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.745
3151611KERR 4
50/50
0.536
3151621KERR 5
50/50
0.536
3151631KERR 6
50/50
0.536
3151641KERR 7
50/50
0.536
972205AH1-687 GEN
50/50
5.251
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.759
971967AH1-528 GEN
Solar/Wind Harmer
100.577
970865AG2-541 GEN
Solar/Wind Harmer
19.046
316123AC1-075 GEN
Solar/Wind Harmer
4.164
970165AG2-112 GEN
Solar/Wind Harmer
3.666
970163AG2-111 GEN
Solar/Wind Harmer
3.497
316239AB2-077_GEN
Solar/Wind Harmer
1.106
316238AB2-078_GEN
Solar/Wind Harmer
1.106
971443AH1-215 GEN
Solar/Wind Harmer
6.874
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.709
970681AG2-440 GEN
Solar/Wind Harmer
21.367
946301AF1-294 GEN
Solar/Wind Harmer
8.599
961791AG1-021 GEN
Solar/Wind Harmer
4.195
315657AE1-056 GEN
Solar/Wind Harmer
12.418
970285AG2-188 GEN
Solar/Wind Harmer
21.458
971845AH1-439 GEN
Solar/Wind Harmer
12.354
970831AG2-522 GEN
Solar/Wind Harmer
10.001
971447AH1-217 GEN
Solar/Wind Harmer
3.943
270494AE1-108_GEN
Solar/Wind Harmer
2.518
946281AF1-292 GEN
Solar/Wind Harmer
0.185
316087AB2-174 GEN
Solar/Wind Harmer
1.121
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.392
270457AD2-023 GEN
Solar/Wind Helper
0.917
970413AG2-270 GEN
50/50
47.114
3144293JTRSVLE
50/50
1.009
3151591KERR 2
50/50
0.536
3151921BEARGRDN G2
50/50
1.077
316248AF1-058 C
Solar/Wind Harmer
1.79
960061AF2-297 GEN
Solar/Wind Harmer
29.705
316478AD1-087 GEN
Solar/Wind Harmer
4.923
316486AD2-202 GEN
Solar/Wind Harmer
1.442
971683AH1-343 GEN
Solar/Wind Harmer
21.974
970909AG2-566 GEN
Solar/Wind Harmer
3.698
316131AB2-060 GEN
Solar/Wind Harmer
3.913
964241AG1-285 GEN
Solar/Wind Harmer
27.993
315785AD2-033 C
Solar/Wind Harmer
7.962
970257AG2-171 GEN
Solar/Wind Harmer
13.074
959311AF2-222 GEN
Solar/Wind Harmer
36.183
963181AG1-167 GEN
Solar/Wind Harmer
3.146
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.696
942461AE2-259 GEN
Solar/Wind Harmer
4.788
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.511
970221AG2-151 GEN
Solar/Wind Harmer
7.306
966621AG1-532 GEN
Solar/Wind Harmer
0.168
313506AB2-031 GEN
Solar/Wind Harmer
0.617
316313AB2-026
Solar/Wind Harmer
0.179
316258AE1-075 C
Solar/Wind Harmer
0.161
316405AF2-144 C
Solar/Wind Harmer
0.17
3143336POWHATN
Solar/Wind Harmer
0.67
316283AC2-100 C
Solar/Wind Helper
2.34
270018AE2-047 C O1
Solar/Wind Helper
0.398
3151531CLOVER1
50/50
10.796
3144293JTRSVLE
50/50
1.009
3151601KERR 3
50/50
0.536
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.437
3151561HALLBR1
50/50
0.346
3151931BEARGRDN S1
50/50
1.389
3151911BEARGRDN G1
50/50
1.077
315687AD1-152 GEN
Solar/Wind Harmer
7.743
316003AC1-222 GEN
Solar/Wind Harmer
5.358
957481AF2-042 GEN
Solar/Wind Harmer
169.548
315693AD1-088 GEN
Solar/Wind Harmer
25.22
962491AG1-098 GEN
Solar/Wind Harmer
33.335
970401AG2-262 GEN
Solar/Wind Harmer
3.248
316237AB2-079_GEN
Solar/Wind Harmer
1.106
970685AG2-442 GEN
Solar/Wind Harmer
29.914
963171AG1-166 GEN
Solar/Wind Harmer
4.195
971563AH1-280 GEN
Solar/Wind Harmer
4.195
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.337
316322AB2-045
Solar/Wind Harmer
0.76
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.875
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.366
971795AH1-408 GEN
Solar/Wind Harmer
10.594
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.511
971377AH1-170 GEN
Solar/Wind Harmer
1.461
3147623JAMES R
Solar/Wind Harmer
0.181
970937AG2-583 GEN
Solar/Wind Harmer
7.619
960081AF2-299 GEN
Solar/Wind Harmer
0.931
316336AC2-165 C
Solar/Wind Harmer
1.347
3143336POWHATN
Solar/Wind Harmer
0.788
3152661PLYWOOD A
50/50
1.084
3144293JTRSVLE
50/50
1.009
3144293JTRSVLE
50/50
0.85
970535AG2-341 GEN
50/50
5.143
970099AG2-077 GEN
Solar/Wind Harmer
67.819
970933AG2-581 GEN
Solar/Wind Harmer
50.154
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.629
962561AG1-105 GEN
Solar/Wind Harmer
26.841
971741AH1-377 GEN
Solar/Wind Harmer
48.342
970301AG2-198 GEN
Solar/Wind Harmer
19.474
313527AB2-043 GEN
Solar/Wind Harmer
5.908
970323AG2-213 GEN
Solar/Wind Harmer
17.432
971775AH1-396 GEN
Solar/Wind Harmer
2.482
316034AC1-036 C
Solar/Wind Harmer
0.646
958211AF2-115 GEN
Solar/Wind Harmer
5.244
963191AG1-168 GEN
Solar/Wind Harmer
3.146
942751AE2-291 GEN
Solar/Wind Harmer
21.251
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.099
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.952
316197AC1-042 GEN
Solar/Wind Harmer
1.48
942671AE2-283 GEN
Solar/Wind Harmer
3.984
971489AH1-241 GEN
Solar/Wind Harmer
6.936
315821AE2-092 GEN
Solar/Wind Harmer
1.81
316181AB2-040 GEN
Solar/Wind Harmer
1.071
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.789
3145593CAROLNA
Solar/Wind Harmer
0.058
316222AC1-221 GEN
Solar/Wind Helper
2.576
G-007ALTFEXP_G-007A->PJM
CMTX
0.588
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.64
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.854
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.69
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.552
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.847
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.009
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.461

Details for 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.7 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1179.05
MW Contribution:47.11
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.745
3151611KERR 4
50/50
0.536
3151621KERR 5
50/50
0.536
3151631KERR 6
50/50
0.536
3151641KERR 7
50/50
0.536
972205AH1-687 GEN
50/50
5.251
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.759
971967AH1-528 GEN
Solar/Wind Harmer
100.577
970865AG2-541 GEN
Solar/Wind Harmer
19.046
316123AC1-075 GEN
Solar/Wind Harmer
4.164
970165AG2-112 GEN
Solar/Wind Harmer
3.666
970163AG2-111 GEN
Solar/Wind Harmer
3.497
316239AB2-077_GEN
Solar/Wind Harmer
1.106
316238AB2-078_GEN
Solar/Wind Harmer
1.106
971443AH1-215 GEN
Solar/Wind Harmer
6.874
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.709
970681AG2-440 GEN
Solar/Wind Harmer
21.367
946301AF1-294 GEN
Solar/Wind Harmer
8.599
961791AG1-021 GEN
Solar/Wind Harmer
4.195
315657AE1-056 GEN
Solar/Wind Harmer
12.418
970285AG2-188 GEN
Solar/Wind Harmer
21.458
971845AH1-439 GEN
Solar/Wind Harmer
12.354
970831AG2-522 GEN
Solar/Wind Harmer
10.001
971447AH1-217 GEN
Solar/Wind Harmer
3.943
270494AE1-108_GEN
Solar/Wind Harmer
2.518
946281AF1-292 GEN
Solar/Wind Harmer
0.185
316087AB2-174 GEN
Solar/Wind Harmer
1.121
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.392
270457AD2-023 GEN
Solar/Wind Helper
0.917
970413AG2-270 GEN
50/50
47.114
3144293JTRSVLE
50/50
1.009
3151591KERR 2
50/50
0.536
3151921BEARGRDN G2
50/50
1.077
316248AF1-058 C
Solar/Wind Harmer
1.79
960061AF2-297 GEN
Solar/Wind Harmer
29.705
316478AD1-087 GEN
Solar/Wind Harmer
4.923
316486AD2-202 GEN
Solar/Wind Harmer
1.442
971683AH1-343 GEN
Solar/Wind Harmer
21.974
970909AG2-566 GEN
Solar/Wind Harmer
3.698
316131AB2-060 GEN
Solar/Wind Harmer
3.913
964241AG1-285 GEN
Solar/Wind Harmer
27.993
315785AD2-033 C
Solar/Wind Harmer
7.962
970257AG2-171 GEN
Solar/Wind Harmer
13.074
959311AF2-222 GEN
Solar/Wind Harmer
36.183
963181AG1-167 GEN
Solar/Wind Harmer
3.146
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.696
942461AE2-259 GEN
Solar/Wind Harmer
4.788
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.511
970221AG2-151 GEN
Solar/Wind Harmer
7.306
966621AG1-532 GEN
Solar/Wind Harmer
0.168
313506AB2-031 GEN
Solar/Wind Harmer
0.617
316313AB2-026
Solar/Wind Harmer
0.179
316258AE1-075 C
Solar/Wind Harmer
0.161
316405AF2-144 C
Solar/Wind Harmer
0.17
3143336POWHATN
Solar/Wind Harmer
0.67
316283AC2-100 C
Solar/Wind Helper
2.34
270018AE2-047 C O1
Solar/Wind Helper
0.398
3151531CLOVER1
50/50
10.796
3144293JTRSVLE
50/50
1.009
3151601KERR 3
50/50
0.536
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.437
3151561HALLBR1
50/50
0.346
3151931BEARGRDN S1
50/50
1.389
3151911BEARGRDN G1
50/50
1.077
315687AD1-152 GEN
Solar/Wind Harmer
7.743
316003AC1-222 GEN
Solar/Wind Harmer
5.358
957481AF2-042 GEN
Solar/Wind Harmer
169.548
315693AD1-088 GEN
Solar/Wind Harmer
25.22
962491AG1-098 GEN
Solar/Wind Harmer
33.335
970401AG2-262 GEN
Solar/Wind Harmer
3.248
316237AB2-079_GEN
Solar/Wind Harmer
1.106
970685AG2-442 GEN
Solar/Wind Harmer
29.914
963171AG1-166 GEN
Solar/Wind Harmer
4.195
971563AH1-280 GEN
Solar/Wind Harmer
4.195
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.337
316322AB2-045
Solar/Wind Harmer
0.76
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.875
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.366
971795AH1-408 GEN
Solar/Wind Harmer
10.594
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.511
971377AH1-170 GEN
Solar/Wind Harmer
1.461
3147623JAMES R
Solar/Wind Harmer
0.181
3152661PLYWOOD A
50/50
1.084
3144293JTRSVLE
50/50
1.009
3144293JTRSVLE
50/50
0.85
970535AG2-341 GEN
50/50
5.143
970099AG2-077 GEN
Solar/Wind Harmer
67.819
970933AG2-581 GEN
Solar/Wind Harmer
50.154
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.629
962561AG1-105 GEN
Solar/Wind Harmer
26.841
971741AH1-377 GEN
Solar/Wind Harmer
48.342
970301AG2-198 GEN
Solar/Wind Harmer
19.474
313527AB2-043 GEN
Solar/Wind Harmer
5.908
970323AG2-213 GEN
Solar/Wind Harmer
17.432
971775AH1-396 GEN
Solar/Wind Harmer
2.482
316034AC1-036 C
Solar/Wind Harmer
0.646
958211AF2-115 GEN
Solar/Wind Harmer
5.244
963191AG1-168 GEN
Solar/Wind Harmer
3.146
942751AE2-291 GEN
Solar/Wind Harmer
21.251
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.099
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.952
316197AC1-042 GEN
Solar/Wind Harmer
1.48
942671AE2-283 GEN
Solar/Wind Harmer
3.984
971489AH1-241 GEN
Solar/Wind Harmer
6.936
315821AE2-092 GEN
Solar/Wind Harmer
1.81
316181AB2-040 GEN
Solar/Wind Harmer
1.071
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.789
3145593CAROLNA
Solar/Wind Harmer
0.058
316222AC1-221 GEN
Solar/Wind Helper
2.576
970937AG2-583 GEN
Solar/Wind Harmer
7.619
960081AF2-299 GEN
Solar/Wind Harmer
0.931
316336AC2-165 C
Solar/Wind Harmer
1.347
3143336POWHATN
Solar/Wind Harmer
0.788
G-007ALTFEXP_G-007A->PJM
CMTX
0.588
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.64
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.854
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.69
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.552
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.847
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.009
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.461

Details for 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.45 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1154.15
MW Contribution:47.65
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
10.918
3144293JTRSVLE
50/50
1.004
3151601KERR 3
50/50
0.536
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.435
3151561HALLBR1
50/50
0.35
3151931BEARGRDN S1
50/50
1.368
3151911BEARGRDN G1
50/50
1.06
315687AD1-152 GEN
Solar/Wind Harmer
7.81
957481AF2-042 GEN
Solar/Wind Harmer
173.007
316003AC1-222 GEN
Solar/Wind Harmer
5.389
970401AG2-262 GEN
Solar/Wind Harmer
3.261
315693AD1-088 GEN
Solar/Wind Harmer
24.89
962491AG1-098 GEN
Solar/Wind Harmer
32.899
316237AB2-079_GEN
Solar/Wind Harmer
1.107
970685AG2-442 GEN
Solar/Wind Harmer
29.8
963171AG1-166 GEN
Solar/Wind Harmer
4.173
971563AH1-280 GEN
Solar/Wind Harmer
4.173
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.345
316322AB2-045
Solar/Wind Harmer
0.75
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.876
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.257
971795AH1-408 GEN
Solar/Wind Harmer
10.577
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.561
971377AH1-170 GEN
Solar/Wind Harmer
1.439
3147623JAMES R
Solar/Wind Harmer
0.178
970937AG2-583 GEN
Solar/Wind Harmer
7.48
960081AF2-299 GEN
Solar/Wind Harmer
0.928
3151541CLOVER2
50/50
10.866
3151611KERR 4
50/50
0.536
3151621KERR 5
50/50
0.536
3151631KERR 6
50/50
0.536
3151641KERR 7
50/50
0.536
972205AH1-687 GEN
50/50
5.169
3147173SINAI
Solar/Wind Harmer
-0.06
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.778
970865AG2-541 GEN
Solar/Wind Harmer
19.161
316123AC1-075 GEN
Solar/Wind Harmer
4.191
970165AG2-112 GEN
Solar/Wind Harmer
3.69
970163AG2-111 GEN
Solar/Wind Harmer
3.52
316239AB2-077_GEN
Solar/Wind Harmer
1.107
316238AB2-078_GEN
Solar/Wind Harmer
1.107
971443AH1-215 GEN
Solar/Wind Harmer
6.858
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.607
970681AG2-440 GEN
Solar/Wind Harmer
21.285
946301AF1-294 GEN
Solar/Wind Harmer
8.556
961791AG1-021 GEN
Solar/Wind Harmer
4.173
315657AE1-056 GEN
Solar/Wind Harmer
12.343
970285AG2-188 GEN
Solar/Wind Harmer
21.187
971845AH1-439 GEN
Solar/Wind Harmer
12.195
970831AG2-522 GEN
Solar/Wind Harmer
10.008
971447AH1-217 GEN
Solar/Wind Harmer
3.882
270494AE1-108_GEN
Solar/Wind Harmer
2.486
946281AF1-292 GEN
Solar/Wind Harmer
0.185
316087AB2-174 GEN
Solar/Wind Harmer
1.118
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.363
270457AD2-023 GEN
Solar/Wind Helper
0.898
3152661PLYWOOD A
50/50
1.09
3144293JTRSVLE
50/50
1.004
3144293JTRSVLE
50/50
0.845
970535AG2-341 GEN
50/50
5.145
970413AG2-270 GEN
50/50
47.647
3144293JTRSVLE
50/50
1.004
3151591KERR 2
50/50
0.536
3151921BEARGRDN G2
50/50
1.06
316248AF1-058 C
Solar/Wind Harmer
1.8
960061AF2-297 GEN
Solar/Wind Harmer
29.874
316478AD1-087 GEN
Solar/Wind Harmer
4.979
316486AD2-202 GEN
Solar/Wind Harmer
1.458
971683AH1-343 GEN
Solar/Wind Harmer
22.104
970909AG2-566 GEN
Solar/Wind Harmer
3.651
316131AB2-060 GEN
Solar/Wind Harmer
3.913
964241AG1-285 GEN
Solar/Wind Harmer
27.972
315785AD2-033 C
Solar/Wind Harmer
7.946
970257AG2-171 GEN
Solar/Wind Harmer
13.041
959311AF2-222 GEN
Solar/Wind Harmer
36.078
963181AG1-167 GEN
Solar/Wind Harmer
3.13
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.572
942461AE2-259 GEN
Solar/Wind Harmer
4.746
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.561
970221AG2-151 GEN
Solar/Wind Harmer
7.194
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.616
316313AB2-026
Solar/Wind Harmer
0.174
316258AE1-075 C
Solar/Wind Harmer
0.157
316405AF2-144 C
Solar/Wind Harmer
0.166
3143336POWHATN
Solar/Wind Harmer
0.652
316283AC2-100 C
Solar/Wind Helper
2.307
970099AG2-077 GEN
Solar/Wind Harmer
69.203
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.672
962561AG1-105 GEN
Solar/Wind Harmer
26.937
971741AH1-377 GEN
Solar/Wind Harmer
47.726
970301AG2-198 GEN
Solar/Wind Harmer
19.228
313527AB2-043 GEN
Solar/Wind Harmer
5.909
970323AG2-213 GEN
Solar/Wind Harmer
17.388
971775AH1-396 GEN
Solar/Wind Harmer
2.476
316034AC1-036 C
Solar/Wind Harmer
0.645
942751AE2-291 GEN
Solar/Wind Harmer
21.395
958211AF2-115 GEN
Solar/Wind Harmer
5.217
963191AG1-168 GEN
Solar/Wind Harmer
3.13
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.11
3146776BUCKING
Solar/Wind Harmer
-0.089
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.974
316197AC1-042 GEN
Solar/Wind Harmer
1.496
942671AE2-283 GEN
Solar/Wind Harmer
4.029
971489AH1-241 GEN
Solar/Wind Harmer
6.83
315821AE2-092 GEN
Solar/Wind Harmer
1.78
316181AB2-040 GEN
Solar/Wind Harmer
1.069
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.789
3145593CAROLNA
Solar/Wind Harmer
0.058
316222AC1-221 GEN
Solar/Wind Helper
2.541
316336AC2-165 C
Solar/Wind Harmer
1.315
3143336POWHATN
Solar/Wind Harmer
0.767
G-007ALTFEXP_G-007A->PJM
CMTX
0.474
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.441
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.83
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.615
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.248
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.788
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.862
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.337

Details for 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.44 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1154.09
MW Contribution:47.64
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.865
3151611KERR 4
50/50
0.536
3151621KERR 5
50/50
0.536
3151631KERR 6
50/50
0.536
3151641KERR 7
50/50
0.536
972205AH1-687 GEN
50/50
5.17
3147173SINAI
Solar/Wind Harmer
-0.06
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.778
970865AG2-541 GEN
Solar/Wind Harmer
19.161
316123AC1-075 GEN
Solar/Wind Harmer
4.19
970165AG2-112 GEN
Solar/Wind Harmer
3.69
970163AG2-111 GEN
Solar/Wind Harmer
3.52
316239AB2-077_GEN
Solar/Wind Harmer
1.107
316238AB2-078_GEN
Solar/Wind Harmer
1.107
971443AH1-215 GEN
Solar/Wind Harmer
6.858
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.608
970681AG2-440 GEN
Solar/Wind Harmer
21.286
946301AF1-294 GEN
Solar/Wind Harmer
8.556
961791AG1-021 GEN
Solar/Wind Harmer
4.174
315657AE1-056 GEN
Solar/Wind Harmer
12.344
970285AG2-188 GEN
Solar/Wind Harmer
21.189
971845AH1-439 GEN
Solar/Wind Harmer
12.197
970831AG2-522 GEN
Solar/Wind Harmer
10.008
971447AH1-217 GEN
Solar/Wind Harmer
3.882
270494AE1-108_GEN
Solar/Wind Harmer
2.486
946281AF1-292 GEN
Solar/Wind Harmer
0.185
316087AB2-174 GEN
Solar/Wind Harmer
1.118
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.363
270457AD2-023 GEN
Solar/Wind Helper
0.898
970413AG2-270 GEN
50/50
47.644
3144293JTRSVLE
50/50
1.004
3151591KERR 2
50/50
0.536
3151921BEARGRDN G2
50/50
1.06
316248AF1-058 C
Solar/Wind Harmer
1.8
960061AF2-297 GEN
Solar/Wind Harmer
29.873
316478AD1-087 GEN
Solar/Wind Harmer
4.978
316486AD2-202 GEN
Solar/Wind Harmer
1.458
971683AH1-343 GEN
Solar/Wind Harmer
22.104
970909AG2-566 GEN
Solar/Wind Harmer
3.651
316131AB2-060 GEN
Solar/Wind Harmer
3.913
964241AG1-285 GEN
Solar/Wind Harmer
27.973
315785AD2-033 C
Solar/Wind Harmer
7.946
970257AG2-171 GEN
Solar/Wind Harmer
13.042
959311AF2-222 GEN
Solar/Wind Harmer
36.079
963181AG1-167 GEN
Solar/Wind Harmer
3.13
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.573
942461AE2-259 GEN
Solar/Wind Harmer
4.746
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.561
970221AG2-151 GEN
Solar/Wind Harmer
7.195
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.616
316313AB2-026
Solar/Wind Harmer
0.174
316258AE1-075 C
Solar/Wind Harmer
0.157
316405AF2-144 C
Solar/Wind Harmer
0.166
3143336POWHATN
Solar/Wind Harmer
0.652
316283AC2-100 C
Solar/Wind Helper
2.307
3152661PLYWOOD A
50/50
1.09
3144293JTRSVLE
50/50
1.004
3144293JTRSVLE
50/50
0.845
970535AG2-341 GEN
50/50
5.145
970099AG2-077 GEN
Solar/Wind Harmer
69.194
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.672
962561AG1-105 GEN
Solar/Wind Harmer
26.937
971741AH1-377 GEN
Solar/Wind Harmer
47.731
970301AG2-198 GEN
Solar/Wind Harmer
19.23
313527AB2-043 GEN
Solar/Wind Harmer
5.909
970323AG2-213 GEN
Solar/Wind Harmer
17.389
971775AH1-396 GEN
Solar/Wind Harmer
2.476
316034AC1-036 C
Solar/Wind Harmer
0.645
942751AE2-291 GEN
Solar/Wind Harmer
21.394
958211AF2-115 GEN
Solar/Wind Harmer
5.217
963191AG1-168 GEN
Solar/Wind Harmer
3.13
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.11
3146776BUCKING
Solar/Wind Harmer
-0.089
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.974
316197AC1-042 GEN
Solar/Wind Harmer
1.496
942671AE2-283 GEN
Solar/Wind Harmer
4.029
971489AH1-241 GEN
Solar/Wind Harmer
6.83
315821AE2-092 GEN
Solar/Wind Harmer
1.78
316181AB2-040 GEN
Solar/Wind Harmer
1.069
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.789
3145593CAROLNA
Solar/Wind Harmer
0.058
316222AC1-221 GEN
Solar/Wind Helper
2.541
3151531CLOVER1
50/50
10.918
3144293JTRSVLE
50/50
1.004
3151601KERR 3
50/50
0.536
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.436
3151561HALLBR1
50/50
0.35
3151931BEARGRDN S1
50/50
1.368
3151911BEARGRDN G1
50/50
1.06
315687AD1-152 GEN
Solar/Wind Harmer
7.809
957481AF2-042 GEN
Solar/Wind Harmer
172.984
316003AC1-222 GEN
Solar/Wind Harmer
5.389
970401AG2-262 GEN
Solar/Wind Harmer
3.261
315693AD1-088 GEN
Solar/Wind Harmer
24.893
962491AG1-098 GEN
Solar/Wind Harmer
32.903
316237AB2-079_GEN
Solar/Wind Harmer
1.107
970685AG2-442 GEN
Solar/Wind Harmer
29.801
963171AG1-166 GEN
Solar/Wind Harmer
4.174
971563AH1-280 GEN
Solar/Wind Harmer
4.174
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.345
316322AB2-045
Solar/Wind Harmer
0.75
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.876
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.258
971795AH1-408 GEN
Solar/Wind Harmer
10.578
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.561
971377AH1-170 GEN
Solar/Wind Harmer
1.439
3147623JAMES R
Solar/Wind Harmer
0.178
970937AG2-583 GEN
Solar/Wind Harmer
7.481
960081AF2-299 GEN
Solar/Wind Harmer
0.928
316336AC2-165 C
Solar/Wind Harmer
1.315
3143336POWHATN
Solar/Wind Harmer
0.767
G-007ALTFEXP_G-007A->PJM
CMTX
0.475
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.441
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.83
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.615
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.249
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.788
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.862
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.337

Details for 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:150.06 %
Rating:1056.8 MVA
Rating Type:C
MVA to Mitigate:1585.79
MW Contribution:11.1
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
5.093
963041AG1-153 GEN
50/50
4.635
3151031BRUNSWICKG2
50/50
2.289
970413AG2-270 GEN
50/50
11.103
970917AG2-570 GEN
Solar/Wind Harmer
45.471
316478AD1-087 GEN
Solar/Wind Harmer
1.154
316486AD2-202 GEN
Solar/Wind Harmer
0.338
315773AC2-141 GEN
Solar/Wind Harmer
4.566
970909AG2-566 GEN
Solar/Wind Harmer
0.861
944581AF1-123 GEN
Solar/Wind Harmer
39.916
944601AF1-125 GEN
Solar/Wind Harmer
39.293
316248AF1-058 C
Solar/Wind Harmer
0.247
960061AF2-297 GEN
Solar/Wind Harmer
4.091
3151101ELIZAR3
Adder
6.215
316283AC2-100 C
Solar/Wind Harmer
0.699
971683AH1-343 GEN
Solar/Wind Harmer
3.159
3144873MCLAUGH
Solar/Wind Harmer
0
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.87
316320Y1-086
Solar/Wind Harmer
0.371
315839AE2-212 C
Solar/Wind Helper
0.734
316365GEN2_N
Solar/Wind Helper
1.533
966621AG1-532 GEN
Solar/Wind Helper
0.257
313506AB2-031 GEN
Solar/Wind Helper
0.926
3142666NORTHAMPTON
Solar/Wind Helper
0.188
3145796HORNRTN
Solar/Wind Helper
0.75
3145796HORNRTN
Solar/Wind Helper
0.187
3147043LAWRENC
Solar/Wind Helper
0.104
3142946ENON
Solar/Wind Helper
0.049
316473AC1-191 GEN
Solar/Wind Helper
0.882
3151541CLOVER2
50/50
2.532
941031AE2-094 GEN
Solar/Wind Harmer
39.728
944011AF1-069 GEN
Solar/Wind Harmer
12.448
970673AG2-436 GEN
Solar/Wind Harmer
42.909
970673AG2-436 GEN
Solar/Wind Harmer
21.726
971967AH1-528 GEN
Solar/Wind Harmer
36.888
970085AG2-068 GEN
Solar/Wind Harmer
11.275
970581AG2-369 GEN
Solar/Wind Harmer
9.696
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
3151081ELIZAR1
Adder
6.136
3151091ELIZAR2
Adder
6.029
316118AC1-105 GEN
Solar/Wind Harmer
0.506
3152611GOSPORTB
Adder
0.827
3152621GOSPORTC
Adder
0.702
3152601GOSPORTA
Adder
0.647
957871AF2-081 GEN
Solar/Wind Harmer
3.642
319010AE1-072 C
Solar/Wind Harmer
1.431
3146406KITTY HAWK
Solar/Wind Harmer
0.006
970865AG2-541 GEN
Solar/Wind Harmer
2.808
313526AB2-022
Solar/Wind Harmer
0.171
316315AB2-025 C
Solar/Wind Helper
1.176
3143316POE
Solar/Wind Helper
2.759
946281AF1-292 GEN
Solar/Wind Helper
0.283
316087AB2-174 GEN
Solar/Wind Helper
1.592
3145796HORNRTN
Solar/Wind Helper
0.6
3145796HORNRTN
Solar/Wind Helper
0.075
316132AB2-190 GEN1
Solar/Wind Helper
1.032
3137643SOCKMAN
Solar/Wind Helper
0.624
316233AE1-074 FULL
Solar/Wind Helper
0.206
316369SG1_INVT
Solar/Wind Helper
0.569
316312AB1-027
Solar/Wind Helper
0.221
315243AE2-183_GT3
50/50
2.946
3151051BRUNSWICKS1
50/50
4.751
3151021BRUNSWICKG1
50/50
2.289
971451AH1-221 GEN
50/50
6.952
3151531CLOVER1
50/50
2.544
940641AE2-051 GEN
Solar/Wind Harmer
19.26
970919AG2-571 GEN
Solar/Wind Harmer
5.756
970087AG2-069 GEN
Solar/Wind Harmer
16.912
939411AE1-173 GEN
Solar/Wind Harmer
86.789
957481AF2-042 GEN
Solar/Wind Harmer
46.49
315693AD1-088 GEN
Solar/Wind Harmer
6.649
962491AG1-098 GEN
Solar/Wind Harmer
8.746
315687AD1-152 GEN
Solar/Wind Harmer
1.407
316294AC1-161 GEN
Solar/Wind Harmer
3.53
944591AF1-124 GEN
Solar/Wind Harmer
40.06
316003AC1-222 GEN
Solar/Wind Harmer
0.754
316388AE2-253 GEN
Solar/Wind Harmer
0.496
316375AC2-012 GEN
Solar/Wind Harmer
2.531
3150981CHESPKA
Adder
0.813
3146456SLIGO L269
Solar/Wind Harmer
-0.007
970401AG2-262 GEN
Solar/Wind Harmer
0.425
316023GEN1_S
Solar/Wind Helper
1.533
316381AD1-082 GEN
Solar/Wind Helper
1.562
3142543TWELFTH
Solar/Wind Helper
0.023
316011AB1-132 GEN
Solar/Wind Helper
2.299
3145796HORNRTN
Solar/Wind Helper
0.619
3145796HORNRTN
Solar/Wind Helper
0.187
316458AB2-190 GEN2
Solar/Wind Helper
1.032
3143526WINTERP
Solar/Wind Helper
0.702
3142433PROV 92
Solar/Wind Helper
0.503
3143226MDLTHAN
Solar/Wind Helper
0.121
3142416OLDCHRC
Solar/Wind Helper
0.302
3142416OLDCHRC
Solar/Wind Helper
0.116
970533AG2-339 GEN
50/50
16.763
970531AG2-338 GEN
50/50
6.705
315242AE2-183_GT2
50/50
2.946
315241AE2-183_GT1
50/50
2.928
972185AH1-677 GEN
50/50
10.62
3151041BRUNSWICKG3
50/50
2.289
972187AH1-678 GEN
50/50
5.253
970933AG2-581 GEN
Solar/Wind Harmer
17.132
970099AG2-077 GEN
Solar/Wind Harmer
18.596
971741AH1-377 GEN
Solar/Wind Harmer
11.67
970301AG2-198 GEN
Solar/Wind Harmer
4.534
316185AD1-033 GEN
Solar/Wind Harmer
0.819
3145506HICKORY
Solar/Wind Harmer
-0.03
3145506HICKORY
Solar/Wind Harmer
-0.018
3145506HICKORY
Solar/Wind Harmer
-0.005
3142956BIRDNECK
Solar/Wind Harmer
0.405
316316AC1-027 C
Solar/Wind Harmer
0.23
316222AC1-221 GEN
Solar/Wind Harmer
0.758
316339AD2-160 GEN
Solar/Wind Harmer
0.496
316036AC1-147 C
Solar/Wind Harmer
0.197
3150991CHESPKB
Adder
0.682
3150991CHESPKB
Adder
0.665
316018AA1-139 ULT2
Solar/Wind Harmer
0.624
316017AA1-139 ULT1
Solar/Wind Harmer
0.589
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.843
3130086AYDLETT
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.007
3146843MT LREL
Solar/Wind Harmer
-0.007
964791AG1-342 GEN
Solar/Wind Harmer
1.391
3146386ELIZ CT
Solar/Wind Harmer
-0.006
3144356SAPONY
Solar/Wind Helper
1.384
316240AF1-291 C
Solar/Wind Helper
0.58
316181AB2-040 GEN
Solar/Wind Helper
1.463
3142666NORTHAMPTON
Solar/Wind Helper
0.188
3142666NORTHAMPTON
Solar/Wind Helper
0.188
3142666NORTHAMPTON
Solar/Wind Helper
0.188
3142666NORTHAMPTON
Solar/Wind Helper
0.112
3145796HORNRTN
Solar/Wind Helper
0.562
3142946ENON
Solar/Wind Helper
0.015
966871AG1-558 GEN
Solar/Wind Helper
0.195
3143526WINTERP
Solar/Wind Helper
0.702
316468AD1-105 GEN
Solar/Wind Helper
0.616
316033AB2-134 GEN
Solar/Wind Helper
0.407
315697AD1-025 GEN
Solar/Wind Helper
1.353
3145593CAROLNA
Solar/Wind Helper
0.116
3145593CAROLNA
Solar/Wind Helper
0.116
CPLELTFEXP_CPLE->PJM
CLTF
4.36
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.578
LAGNLTFEXP_LAGN->PJM
CLTF
3.312
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.993
TVALTFEXP_TVA->PJM
CLTF
1.652
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.972
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.67
MECLTFEXP_MEC->PJM
CLTF
1.642
SIGELTFEXP_SIGE->PJM
CLTF
0.049
NYPJM->LTFIMP_NY
CLTF
0.573
LGEELTFEXP_LGEE->PJM
CLTF
0.594
WECLTFEXP_WEC->PJM
CLTF
0.31

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.66 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4497.83
MW Contribution:25.77
Bus #Bus NameTypeMW Contribution
970533AG2-339 GEN
50/50
32.288
970531AG2-338 GEN
50/50
12.915
315242AE2-183_GT2
50/50
5.789
315241AE2-183_GT1
50/50
5.753
972185AH1-677 GEN
50/50
20.868
3151041BRUNSWICKG3
50/50
4.54
972187AH1-678 GEN
50/50
10.419
970933AG2-581 GEN
Solar/Wind Harmer
26.407
970099AG2-077 GEN
Solar/Wind Harmer
31.122
3144356SAPONY
Solar/Wind Harmer
2.393
316185AD1-033 GEN
Solar/Wind Harmer
0.008
3145506HICKORY
Solar/Wind Harmer
1.094
3145506HICKORY
Solar/Wind Harmer
0.657
3145506HICKORY
Solar/Wind Harmer
0.164
316339AD2-160 GEN
Solar/Wind Harmer
0.443
316018AA1-139 ULT2
Solar/Wind Harmer
0.007
316017AA1-139 ULT1
Solar/Wind Harmer
0.152
3142956BIRDNECK
Solar/Wind Harmer
0
3137176SLIGO L2192
Solar/Wind Harmer
1.084
3146456SLIGO L269
Solar/Wind Harmer
4.819
316316AC1-027 C
Solar/Wind Harmer
0.261
3130086AYDLETT
Solar/Wind Harmer
1.088
316036AC1-147 C
Solar/Wind Harmer
0.05
3150991CHESPKB
Adder
2.836
3150991CHESPKB
Adder
2.768
3146386ELIZ CT
Solar/Wind Harmer
0.27
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.268
3146516WINFALL
Solar/Wind Harmer
0.268
3146516WINFALL
Solar/Wind Harmer
0.268
3146626S HERTFORD
Solar/Wind Harmer
0.267
3146626S HERTFORD
Solar/Wind Harmer
0.267
3146376EDENTON
Solar/Wind Harmer
1.171
3146376EDENTON
Solar/Wind Harmer
1.171
315742AE1-103 GEN
Solar/Wind Harmer
0.003
316065AD1-022 GEN
Solar/Wind Harmer
11.799
3145893MURPHYS
Solar/Wind Harmer
1.706
3145893MURPHYS
Solar/Wind Harmer
0.459
316181AB2-040 GEN
Solar/Wind Harmer
0.369
3142666NORTHAMPTON
Solar/Wind Harmer
0.254
3142666NORTHAMPTON
Solar/Wind Harmer
0.254
3142666NORTHAMPTON
Solar/Wind Harmer
0.254
3142666NORTHAMPTON
Solar/Wind Harmer
0.153
3146173TUNIS
Solar/Wind Harmer
0.254
3146173TUNIS
Solar/Wind Harmer
0.254
316426AA2-053 GEN
Solar/Wind Harmer
0.849
3145796HORNRTN
Solar/Wind Harmer
0.754
3145593CAROLNA
Solar/Wind Harmer
0.251
3145593CAROLNA
Solar/Wind Harmer
0.251
966811AG1-552 GEN
Solar/Wind Harmer
2.724
3145593CAROLNA
Solar/Wind Harmer
0.313
3145783HORNRTN
Solar/Wind Harmer
4.447
3145783HORNRTN
Solar/Wind Harmer
3.557
3145783HORNRTN
Solar/Wind Harmer
1.112
3145783HORNRTN
Solar/Wind Harmer
0.445
316274AC1-208 GEN
Solar/Wind Harmer
1.268
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3145933PARMELE
Solar/Wind Harmer
0.486
3145933PARMELE
Solar/Wind Harmer
0.243
970657AG2-426 GEN
Solar/Wind Harmer
8.443
970657AG2-426 GEN
Solar/Wind Harmer
1.77
939181AE1-148 GEN
Solar/Wind Harmer
11.415
3145493TOT1
Solar/Wind Harmer
0.548
3145453TOT5
Solar/Wind Harmer
0.329
3145603CNETO
Solar/Wind Harmer
0.219
961601AG1-000A GEN
Solar/Wind Harmer
4.164
316263AC1-034 GEN
Solar/Wind Harmer
8.897
313527AB2-043 GEN
Solar/Wind Harmer
0.003
315244AE2-183_ST
50/50
10.008
963041AG1-153 GEN
50/50
9.194
315779AE2-040
50/50
3.994
3151541CLOVER2
50/50
5.877
3151081ELIZAR1
50/50
26.432
941031AE2-094 GEN
Solar/Wind Harmer
66.901
944011AF1-069 GEN
Solar/Wind Harmer
21.859
970673AG2-436 GEN
Solar/Wind Harmer
75.678
970673AG2-436 GEN
Solar/Wind Harmer
50.452
971967AH1-528 GEN
Solar/Wind Harmer
55.275
970085AG2-068 GEN
Solar/Wind Harmer
17.517
970581AG2-369 GEN
Solar/Wind Harmer
15.064
316315AB2-025 C
Solar/Wind Harmer
0.231
315814AE2-033 C
Solar/Wind Harmer
22.552
957871AF2-081 GEN
Solar/Wind Harmer
13.58
319010AE1-072 C
Solar/Wind Harmer
1.371
3146406KITTY HAWK
Solar/Wind Harmer
0.034
3151091ELIZAR2
Adder
24.477
3152611GOSPORTB
Adder
3.448
3152621GOSPORTC
Adder
2.926
3152601GOSPORTA
Adder
2.699
313526AB2-022
Solar/Wind Harmer
0.146
316305AF2-043 C
Solar/Wind Harmer
0.002
316321Z2-027
Solar/Wind Harmer
0.05
3146396TANGLEW
Solar/Wind Harmer
0.743
3145176PASQUOTANK
Solar/Wind Harmer
0.167
3146486SUNBURY
Solar/Wind Harmer
0.269
3146486SUNBURY
Solar/Wind Harmer
0.269
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
315835AF2-110_GEN
Solar/Wind Harmer
1.82
3130156CHOWAN
Solar/Wind Harmer
0.263
3130156CHOWAN
Solar/Wind Harmer
0.263
315816AE2-034 GEN
Solar/Wind Harmer
1.116
3130546PLYMOUTH
Solar/Wind Harmer
0.257
315732AD1-074 GEN1
Solar/Wind Harmer
1.477
315733AD1-074 GEN2
Solar/Wind Harmer
1.477
315735AD1-075 GEN1
Solar/Wind Harmer
0.74
965291AG1-394 GEN
Solar/Wind Harmer
1.138
3146206CASHIE
Solar/Wind Harmer
0.256
970601AG2-382 GEN
Solar/Wind Harmer
9.549
316311AC2-079 GEN
Solar/Wind Harmer
7.334
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.175
316087AB2-174 GEN
Solar/Wind Harmer
0.007
3145893MURPHYS
Solar/Wind Harmer
0.688
3145893MURPHYS
Solar/Wind Harmer
0.255
315652AC1-086 GEN
Solar/Wind Harmer
27.966
3145513AHOSKIE
Solar/Wind Harmer
0.53
3145513AHOSKIE
Solar/Wind Harmer
0.253
3146043SEABORD
Solar/Wind Harmer
0.253
315607AA1-063A GEN
Solar/Wind Harmer
0.517
3145683EARLEYS
Solar/Wind Harmer
0.506
3145683EARLEYS
Solar/Wind Harmer
0.253
3145683EARLEYS
Solar/Wind Harmer
0.253
3137643SOCKMAN
Solar/Wind Harmer
1.009
3145796HORNRTN
Solar/Wind Harmer
0.804
3145796HORNRTN
Solar/Wind Harmer
0.101
3146033SCOT NK
Solar/Wind Harmer
0.989
970831AG2-522 GEN
Solar/Wind Harmer
10.446
3143316POE
Solar/Wind Harmer
0.965
971445AH1-216 GEN
Solar/Wind Harmer
17.029
316005AA1-067
Solar/Wind Harmer
0.257
3145746EVERETS
Solar/Wind Harmer
0.955
3145746EVERETS
Solar/Wind Harmer
0.24
3145746EVERETS
Solar/Wind Harmer
0.24
3145746EVERETS
Solar/Wind Harmer
0.24
970181AG2-120 GEN
Solar/Wind Harmer
2.987
957861AF2-080 GEN
Solar/Wind Harmer
10.262
316420AA1-050 GEN
Solar/Wind Harmer
0.008
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.236
3145573BETHELC
Solar/Wind Harmer
0.236
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
972265AH1-717 GEN
Adder
17.569
3151201GRAVEL4
Adder
16.47
3151191GRAVEL3
Adder
16.261
3151211GRAVEL5
Adder
16.261
316118AC1-105 GEN
Solar/Wind Harmer
0.578
3147173SINAI
Solar/Wind Harmer
0.223
3147243WELCO
Solar/Wind Harmer
0.14
971443AH1-215 GEN
Solar/Wind Harmer
3.472
3144303KENBRDG
Solar/Wind Harmer
0.165
316369SG1_INVT
Solar/Wind Harmer
0.007
970683AG2-441 GEN
Solar/Wind Harmer
13.122
970681AG2-440 GEN
Solar/Wind Harmer
10.498
970865AG2-541 GEN
Solar/Wind Harmer
6.671
946301AF1-294 GEN
Solar/Wind Harmer
3.715
961791AG1-021 GEN
Solar/Wind Harmer
1.807
3138283WHITEMARSH
Solar/Wind Harmer
0.044
316132AB2-190 GEN1
Solar/Wind Harmer
0.989
315657AE1-056 GEN
Solar/Wind Harmer
6.288
316123AC1-075 GEN
Solar/Wind Harmer
0.235
970165AG2-112 GEN
Solar/Wind Harmer
1.394
970163AG2-111 GEN
Solar/Wind Harmer
1.33
3141873WAN 176
Solar/Wind Harmer
0.031
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.431
3151031BRUNSWICKG2
50/50
4.54
970413AG2-270 GEN
50/50
25.77
3151101ELIZAR3
50/50
26.77
970917AG2-570 GEN
Solar/Wind Harmer
29.34
315773AC2-141 GEN
Solar/Wind Harmer
10.33
944581AF1-123 GEN
Solar/Wind Harmer
62.596
944601AF1-125 GEN
Solar/Wind Harmer
61.631
316478AD1-087 GEN
Solar/Wind Harmer
0.962
316486AD2-202 GEN
Solar/Wind Harmer
0.283
3146456SLIGO L269
Solar/Wind Harmer
0.272
971153AH1-033 GEN
Solar/Wind Harmer
3.148
3144873MCLAUGH
Solar/Wind Harmer
0.007
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.268
3146626S HERTFORD
Solar/Wind Harmer
0.267
316365GEN2_N
Solar/Wind Harmer
0.594
3146376EDENTON
Solar/Wind Harmer
0.263
3144536CHRHLND
Solar/Wind Harmer
0.039
3145273HOLLAND
Solar/Wind Harmer
0.197
315614AA2-178 GEN
Solar/Wind Harmer
1.489
971157AH1-035 GEN
Solar/Wind Harmer
3.091
315737AD1-076 GEN
Solar/Wind Harmer
3.308
3156081AA2-088 GEN
Solar/Wind Harmer
0.006
3146206CASHIE
Solar/Wind Harmer
0.256
3145893MURPHYS
Solar/Wind Harmer
0.427
3145893MURPHYS
Solar/Wind Harmer
0.255
957521AF2-046 GEN
Solar/Wind Harmer
18.955
961681AG1-008 GEN
Solar/Wind Harmer
18.955
313506AB2-031 GEN
Solar/Wind Harmer
0.786
3142666NORTHAMPTON
Solar/Wind Harmer
0.254
3146173TUNIS
Solar/Wind Harmer
0.254
3156021HOLLOMANSOL
Solar/Wind Harmer
1.153
316463AE2-346 GEN
Solar/Wind Harmer
0.218
316140AB2-099
Solar/Wind Harmer
0.091
962331AG1-082 GEN
Solar/Wind Harmer
2.704
3146263WOODLND
Solar/Wind Harmer
0.252
3145796HORNRTN
Solar/Wind Harmer
1.005
3145796HORNRTN
Solar/Wind Harmer
0.251
316317KELFORD C
Solar/Wind Harmer
0.024
3145823KELFORD
Solar/Wind Harmer
0.25
3145963POPLR C
Solar/Wind Harmer
0.249
3147043LAWRENC
Solar/Wind Harmer
0.149
316210AC1-098 GEN
Solar/Wind Harmer
2.273
970661AG2-428 GEN
Solar/Wind Harmer
5.16
3145336SMITFLD
Solar/Wind Harmer
0.097
3145933PARMELE
Solar/Wind Harmer
0.243
966801AG1-551 GEN
Solar/Wind Harmer
2.83
315724AD1-057 GEN
Solar/Wind Harmer
0.908
3145746EVERETS
Solar/Wind Harmer
0.24
3145746EVERETS
Solar/Wind Harmer
0.24
316327AA2-057 GEN
Solar/Wind Harmer
0.362
316083AB2-161 GEN
Solar/Wind Harmer
0.003
970659AG2-427 GEN
Solar/Wind Harmer
2.515
3146233WITAKRS
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.161
3138543CONSLDL
Solar/Wind Harmer
0.156
3146073TAR RVR
Solar/Wind Harmer
0.236
3146083TARBORO
Solar/Wind Harmer
0.236
961601AG1-000A GEN
Solar/Wind Harmer
16.657
3145543BTLEBRO
Solar/Wind Harmer
0.234
3145543BTLEBRO
Solar/Wind Harmer
0.234
971623AH1-311 GEN
Solar/Wind Harmer
0.468
315813AE1-149 C
Solar/Wind Harmer
12.227
3151221GRAVEL6
Adder
16.451
3151171GRAVELC
Adder
3.165
316131AB2-060 GEN
Solar/Wind Harmer
0.707
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.527
3144216WINCHST
Adder
0.83
964241AG1-285 GEN
Solar/Wind Harmer
14.603
3150921YORKTN3
Adder
5.498
961611AG1-000B GEN
Solar/Wind Harmer
5.762
315785AD2-033 C
Solar/Wind Harmer
1.703
316283AC2-100 C
Solar/Wind Harmer
0.406
970257AG2-171 GEN
Solar/Wind Harmer
6.589
959311AF2-222 GEN
Solar/Wind Harmer
18.071
971683AH1-343 GEN
Solar/Wind Harmer
7.451
315839AE2-212 C
Solar/Wind Harmer
0.002
970909AG2-566 GEN
Solar/Wind Harmer
2.128
315778AD1-151 GEN
Solar/Wind Harmer
15.484
316382AG1-145 C
Solar/Wind Harmer
0.002
965281AG1-393 GEN
Solar/Wind Harmer
2.04
963181AG1-167 GEN
Solar/Wind Harmer
0.753
3144293JTRSVLE
Adder
0.599
970129AG2-093 GEN
Solar/Wind Harmer
11.049
315243AE2-183_GT3
50/50
5.789
3151051BRUNSWICKS1
50/50
9.423
3151021BRUNSWICKG1
50/50
4.54
971451AH1-221 GEN
50/50
13.79
3151531CLOVER1
50/50
5.905
940641AE2-051 GEN
Solar/Wind Harmer
28.987
939411AE1-173 GEN
Solar/Wind Harmer
145.254
970919AG2-571 GEN
Solar/Wind Harmer
11.736
970087AG2-069 GEN
Solar/Wind Harmer
26.275
957481AF2-042 GEN
Solar/Wind Harmer
77.806
316294AC1-161 GEN
Solar/Wind Harmer
4.901
944591AF1-124 GEN
Solar/Wind Harmer
62.818
316388AE2-253 GEN
Solar/Wind Harmer
0.855
3146456SLIGO L269
Solar/Wind Harmer
0.272
315693AD1-088 GEN
Solar/Wind Harmer
13.02
316375AC2-012 GEN
Solar/Wind Harmer
0.007
3150981CHESPKA
Adder
3.38
316246AF1-032 C
Solar/Wind Harmer
0.122
3146516WINFALL
Solar/Wind Harmer
0.867
3146516WINFALL
Solar/Wind Harmer
0.268
962491AG1-098 GEN
Solar/Wind Harmer
15.268
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
316093AE2-104_GEN
Solar/Wind Harmer
4.461
316023GEN1_S
Solar/Wind Harmer
0.594
3130156CHOWAN
Solar/Wind Harmer
0.263
3145663CRESWEL
Solar/Wind Harmer
0.728
971163AH1-040 GEN
Solar/Wind Harmer
20.811
3147133PAMPLIN
Solar/Wind Harmer
0.572
971193AH1-056 GEN
Solar/Wind Harmer
11.101
970133AG2-095 GEN
Solar/Wind Harmer
1.61
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316156AD2-030 GEN
Solar/Wind Harmer
0.114
3141873WAN 176
Solar/Wind Harmer
2.731
316280AD1-041 GEN
Solar/Wind Harmer
0.003
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141843SHACKLE
Adder
0.764
3141766HARMONY
Solar/Wind Harmer
1.984
3146926FARMVIL
Solar/Wind Harmer
0.088
3142433PROV 92
Adder
0.271
3142433PROV 92
Adder
0.271
962971AG1-146 GEN
Solar/Wind Harmer
2.159
3142946ENON
Solar/Wind Harmer
0.044
316072AD1-144
Solar/Wind Harmer
0.094
315687AD1-152 GEN
Solar/Wind Harmer
0.008
960081AF2-299 GEN
Solar/Wind Harmer
2.469
3146206CASHIE
Solar/Wind Harmer
0.256
971547AH1-271 GEN
Solar/Wind Harmer
5.457
3145893MURPHYS
Solar/Wind Harmer
1.02
3145893MURPHYS
Solar/Wind Harmer
1.134
316011AB1-132 GEN
Solar/Wind Harmer
4.622
962571AG1-106 GEN
Solar/Wind Harmer
3.617
3146173TUNIS
Solar/Wind Harmer
0.254
3145683EARLEYS
Solar/Wind Harmer
0.253
3146263WOODLND
Solar/Wind Harmer
0.252
316190AA2-174 GEN
Solar/Wind Harmer
0
3145796HORNRTN
Solar/Wind Harmer
0.829
3145796HORNRTN
Solar/Wind Harmer
0.251
971795AH1-408 GEN
Solar/Wind Harmer
16.715
3145823KELFORD
Solar/Wind Harmer
0.25
3145783HORNRTN
Solar/Wind Harmer
0.25
3145963POPLR C
Solar/Wind Harmer
0.249
316174AB2-169 GEN
Solar/Wind Harmer
0.007
3147043LAWRENC
Adder
2.242
316212AC1-099_GEN
Solar/Wind Harmer
1.268
316129AC1-054 GEN
Solar/Wind Harmer
0.918
970661AG2-428 GEN
Solar/Wind Harmer
24.263
971065AG2-659 GEN
Solar/Wind Harmer
10.39
3145336SMITFLD
Solar/Wind Harmer
0.973
3146293MARTNCO
Solar/Wind Harmer
0.225
315722AD1-056 GEN
Solar/Wind Harmer
1.532
3145746EVERETS
Solar/Wind Harmer
0.24
3145746EVERETS
Solar/Wind Harmer
0.24
316381AD1-082 GEN
Solar/Wind Harmer
0.249
316494AC1-189 GEN
Solar/Wind Harmer
0.804
970659AG2-427 GEN
Solar/Wind Harmer
11.496
3146233WITAKRS
Solar/Wind Harmer
0.942
961671AG1-007 GEN
Solar/Wind Harmer
0.036
3146083TARBORO
Solar/Wind Harmer
0.236
3145493TOT1
Solar/Wind Harmer
1.05
316359AB2-059 GEN
Solar/Wind Harmer
0.841
316049AB1-081 GEN
Solar/Wind Harmer
1.34
3145543BTLEBRO
Solar/Wind Harmer
0.234
3145543BTLEBRO
Solar/Wind Harmer
0.187
3142053HEARTS
Solar/Wind Harmer
0.412
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3151171GRAVELC
Adder
2.407
970401AG2-262 GEN
Solar/Wind Harmer
1.317
3138126ROCKLANDING
Solar/Wind Harmer
0.101
961611AG1-000B GEN
Solar/Wind Harmer
11.332
316003AC1-222 GEN
Solar/Wind Harmer
0.006
971647AH1-324 GEN
Solar/Wind Harmer
8.873
971317AH1-138 GEN
Solar/Wind Harmer
1.539
970685AG2-442 GEN
Solar/Wind Harmer
14.697
971069AG2-661 GEN
Solar/Wind Harmer
3.441
316159AE1-175 C
Solar/Wind Harmer
0.165
963171AG1-166 GEN
Solar/Wind Harmer
1.004
971563AH1-280 GEN
Solar/Wind Harmer
2.008
3144293JTRSVLE
Adder
0.599
316458AB2-190 GEN2
Solar/Wind Harmer
0.989
315671AE2-027_GEN
Solar/Wind Harmer
11.755
970129AG2-093 GEN
Solar/Wind Harmer
5.199
971777AH1-397 GEN
Solar/Wind Harmer
0.395
3141843SHACKLE
Adder
0.764
3141766HARMONY
Solar/Wind Harmer
0.03
3146926FARMVIL
Solar/Wind Harmer
0.088
3138133OCRAN
Solar/Wind Harmer
0.087
3142433PROV 92
Solar/Wind Harmer
0.557
3142433PROV 92
Adder
0.271
3142433PROV 92
Adder
0.271
970223AG2-152 GEN
Solar/Wind Harmer
9.565
944631AF1-128 GEN
Adder
62.411
270016AE1-250 BESS
Solar/Wind Harmer
0.004
962861AG1-135 GEN
Solar/Wind Harmer
4.023
3147123OTTER R
Solar/Wind Harmer
0.07
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3141726DUNNSVL
Solar/Wind Harmer
0.457
316045AC1-158 PL2
Solar/Wind Helper
5.221
3147666LOUISA
Solar/Wind Helper
1.002
316192AB2-158 GEN
Solar/Wind Helper
1.658
316254AC1-120 GEN1
Solar/Wind Helper
1.035
962561AG1-105 GEN
Solar/Wind Harmer
10.79
964791AG1-342 GEN
Solar/Wind Harmer
4.311
3146843MT LREL
Solar/Wind Harmer
0.224
3146843MT LREL
Solar/Wind Harmer
0.224
971741AH1-377 GEN
Solar/Wind Harmer
21.422
316222AC1-221 GEN
Solar/Wind Harmer
0.867
970323AG2-213 GEN
Solar/Wind Harmer
8.785
971775AH1-396 GEN
Solar/Wind Harmer
0.329
316034AC1-036 C
Solar/Wind Harmer
0.015
316033AB2-134 GEN
Solar/Wind Harmer
0.012
315697AD1-025 GEN
Solar/Wind Harmer
0.225
970301AG2-198 GEN
Solar/Wind Harmer
8.511
958211AF2-115 GEN
Solar/Wind Harmer
2.259
963191AG1-168 GEN
Solar/Wind Harmer
0.753
3144293JTRSVLE
Adder
0.599
3144293JTRSVLE
Adder
0.505
3147133PAMPLIN
Solar/Wind Harmer
0.182
3147133PAMPLIN
Solar/Wind Harmer
0.146
316240AF1-291 C
Solar/Wind Harmer
0.001
944641AF1-129 GEN
Adder
78.098
942751AE2-291 GEN
Solar/Wind Harmer
8.652
3142946ENON
Solar/Wind Harmer
0.013
270013AE1-250 PV
Solar/Wind Harmer
0.004
958261AF2-120 GEN
Solar/Wind Harmer
4.097
316075AC2-137 C
Solar/Wind Harmer
0.033
316447AC1-158 HLD
Solar/Wind Helper
3.59
315651AD1-115 GEN
Solar/Wind Helper
0.751
970009AG2-005 GEN
Solar/Wind Harmer
0.976
316404AE1-155 C
Solar/Wind Harmer
0.028
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
0.766
316044AC1-158 PL1
Solar/Wind Helper
1.631
316450AC1-158 RIC
Solar/Wind Helper
0.435
3147666LOUISA
Solar/Wind Helper
0.576
316170AC1-121 GEN2
Solar/Wind Helper
0.345
316059AD1-063 C
Solar/Wind Harmer
0.001
3141913WHIT STONE
Solar/Wind Harmer
0.147
316314AB2-024 C
Solar/Wind Harmer
0.001
3138133OCRAN
Solar/Wind Harmer
0.044
3143873LANEXA
Solar/Wind Harmer
0.086
3141783LANCAST
Solar/Wind Harmer
0.085
3141783LANCAST
Solar/Wind Harmer
0.057
3142433PROV 92
Adder
0.271
3142433PROV 92
Adder
0.271
971167AH1-042 GEN
Solar/Wind Harmer
12.277
315976AC1-164 GENA
Solar/Wind Harmer
14.222
316169AC1-164_GENC
Solar/Wind Harmer
12.287
315975AC1-164 GENB
Solar/Wind Harmer
0.421
962981AG1-147 GEN
Solar/Wind Harmer
5.038
970327AG2-215 GEN
Solar/Wind Harmer
4.29
316164AC1-076 GEN
Solar/Wind Helper
1.17
CPLELTFEXP_CPLE->PJM
CLTF
15.998
CBM West 2LTFEXP_CBM-W2->PJM
CBM
59.498
LAGNLTFEXP_LAGN->PJM
CLTF
11.265
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.702
TVALTFEXP_TVA->PJM
CLTF
5.645
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.7
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.348
MECLTFEXP_MEC->PJM
CLTF
5.484
SIGELTFEXP_SIGE->PJM
CLTF
0.165
NYPJM->LTFIMP_NY
CLTF
2.873
LGEELTFEXP_LGEE->PJM
CLTF
2
WECLTFEXP_WEC->PJM
CLTF
1.023

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 56272_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56272_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.96 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:4114.65
MW Contribution:24.95
Bus #Bus NameTypeMW Contribution
970533AG2-339 GEN
50/50
32.21
970531AG2-338 GEN
50/50
12.884
315242AE2-183_GT2
50/50
5.755
315241AE2-183_GT1
50/50
5.72
972185AH1-677 GEN
50/50
20.748
3151041BRUNSWICKG3
50/50
4.507
972187AH1-678 GEN
50/50
10.344
3151361ROSEMG1
50/50
0.776
3151371ROSEMS1
50/50
0.481
3151031BRUNSWICKG2
50/50
4.507
970413AG2-270 GEN
50/50
24.952
3151591KERR 2
50/50
0.458
3151391GASTONA
50/50
0.588
3151411GASTONB
50/50
0.588
3151261ROARAP2
50/50
0.26
970917AG2-570 GEN
Solar/Wind Harmer
91.647
316478AD1-087 GEN
Solar/Wind Harmer
2.597
316486AD2-202 GEN
Solar/Wind Harmer
0.761
316365GEN2_N
Solar/Wind Harmer
1.761
966621AG1-532 GEN
Solar/Wind Harmer
0.515
3147043LAWRENC
Solar/Wind Harmer
-0.015
313506AB2-031 GEN
Solar/Wind Harmer
1.989
3145796HORNRTN
Solar/Wind Harmer
-0.096
3145796HORNRTN
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
316248AF1-058 C
Solar/Wind Harmer
0.711
960061AF2-297 GEN
Solar/Wind Harmer
11.79
315724AD1-057 GEN
Solar/Wind Harmer
1.351
316131AB2-060 GEN
Solar/Wind Harmer
2.509
316210AC1-098 GEN
Solar/Wind Harmer
3.629
316327AA2-057 GEN
Solar/Wind Harmer
2.332
3146263WOODLND
Solar/Wind Harmer
-0.023
3146233WITAKRS
Solar/Wind Harmer
0.481
3146233WITAKRS
Solar/Wind Harmer
-0.015
3138543CONSLDL
Solar/Wind Harmer
-0.015
961601AG1-000A GEN
Solar/Wind Harmer
9.103
3145543BTLEBRO
Solar/Wind Harmer
-0.023
3145543BTLEBRO
Solar/Wind Harmer
-0.023
316317KELFORD C
Solar/Wind Harmer
1.074
3145823KELFORD
Solar/Wind Harmer
-0.023
3146073TAR RVR
Solar/Wind Harmer
-0.023
3146083TARBORO
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
0.158
3145893MURPHYS
Solar/Wind Harmer
-0.023
957521AF2-046 GEN
Solar/Wind Harmer
17.808
961681AG1-008 GEN
Solar/Wind Harmer
17.808
964241AG1-285 GEN
Solar/Wind Harmer
17.664
3146173TUNIS
Solar/Wind Harmer
-0.023
316463AE2-346 GEN
Solar/Wind Harmer
0.366
316140AB2-099
Solar/Wind Harmer
0.152
962331AG1-082 GEN
Solar/Wind Harmer
2.826
3156081AA2-088 GEN
Solar/Wind Harmer
7.311
3156021HOLLOMANSOL
Solar/Wind Harmer
3.009
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3145933PARMELE
Solar/Wind Harmer
-0.022
966801AG1-551 GEN
Solar/Wind Harmer
2.766
3146206CASHIE
Solar/Wind Harmer
-0.022
3145963POPLR C
Solar/Wind Harmer
-0.022
315244AE2-183_ST
50/50
9.95
963041AG1-153 GEN
50/50
9.127
3151541CLOVER2
50/50
5.691
315779AE2-040
50/50
3.626
3151611KERR 4
50/50
0.458
3151621KERR 5
50/50
0.458
3151631KERR 6
50/50
0.458
3151641KERR 7
50/50
0.458
3151281ROARAP4
50/50
0.259
3151281ROARAP4
50/50
0.243
941031AE2-094 GEN
Solar/Wind Harmer
76.337
944011AF1-069 GEN
Solar/Wind Harmer
23.919
970673AG2-436 GEN
Solar/Wind Harmer
83.349
970673AG2-436 GEN
Solar/Wind Harmer
42.202
971967AH1-528 GEN
Solar/Wind Harmer
72.452
970085AG2-068 GEN
Solar/Wind Harmer
22.787
970581AG2-369 GEN
Solar/Wind Harmer
19.597
316315AB2-025 C
Solar/Wind Harmer
0.787
315814AE2-033 C
Solar/Wind Harmer
27.034
946281AF1-292 GEN
Solar/Wind Harmer
0.568
316087AB2-174 GEN
Solar/Wind Harmer
3.556
970831AG2-522 GEN
Solar/Wind Harmer
12.26
315652AC1-086 GEN
Solar/Wind Harmer
27.499
3137643SOCKMAN
Solar/Wind Harmer
-0.097
3145796HORNRTN
Solar/Wind Harmer
-0.077
3145796HORNRTN
Solar/Wind Harmer
-0.01
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
316118AC1-105 GEN
Solar/Wind Harmer
1.62
316239AB2-077_GEN
Solar/Wind Harmer
0.708
316238AB2-078_GEN
Solar/Wind Harmer
0.708
315607AA1-063A GEN
Solar/Wind Harmer
2.372
3146043SEABORD
Solar/Wind Harmer
-0.023
316319Z2-044 C
Solar/Wind Harmer
1.269
3146033SCOT NK
Solar/Wind Harmer
-0.091
3143316POE
Solar/Wind Harmer
-0.09
3145573BETHELC
Solar/Wind Harmer
-0.023
3145573BETHELC
Solar/Wind Harmer
-0.023
965291AG1-394 GEN
Solar/Wind Harmer
2.008
316318V4-068
Solar/Wind Harmer
0.563
3145893MURPHYS
Solar/Wind Harmer
-0.061
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145513AHOSKIE
Solar/Wind Harmer
0.197
961941AG1-037 GEN
Solar/Wind Harmer
0.17
3145513AHOSKIE
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.045
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
316420AA1-050 GEN
Solar/Wind Harmer
2.577
957861AF2-080 GEN
Solar/Wind Harmer
9.823
316005AA1-067
Solar/Wind Harmer
0.45
3145746EVERETS
Solar/Wind Harmer
-0.088
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
970181AG2-120 GEN
Solar/Wind Harmer
2.918
3146206CASHIE
Solar/Wind Harmer
-0.022
970601AG2-382 GEN
Solar/Wind Harmer
9.603
315732AD1-074 GEN1
Solar/Wind Harmer
4.385
315733AD1-074 GEN2
Solar/Wind Harmer
4.385
315735AD1-075 GEN1
Solar/Wind Harmer
2.193
3130546PLYMOUTH
Solar/Wind Harmer
-0.022
315816AE2-034 GEN
Solar/Wind Harmer
1.73
971443AH1-215 GEN
Solar/Wind Harmer
4.181
3144303KENBRDG
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.021
3130156CHOWAN
Solar/Wind Harmer
-0.021
315611Z1-036_GEN2
Solar/Wind Harmer
5.153
315835AF2-110_GEN
Solar/Wind Harmer
2.575
3146486SUNBURY
Solar/Wind Harmer
-0.021
3146486SUNBURY
Solar/Wind Harmer
-0.021
316305AF2-043 C
Solar/Wind Harmer
0.619
3145176PASQUOTANK
Solar/Wind Harmer
-0.013
316321Z2-027
Solar/Wind Harmer
0.551
3146396TANGLEW
Solar/Wind Harmer
0.375
313526AB2-022
Solar/Wind Harmer
0.548
316311AC2-079 GEN
Solar/Wind Harmer
10.237
315833AF1-017_GEN
Solar/Wind Harmer
3.854
316349AD2-085 GEN
Solar/Wind Harmer
1.805
970683AG2-441 GEN
Solar/Wind Harmer
15.731
970681AG2-440 GEN
Solar/Wind Harmer
12.585
3146406KITTY HAWK
Solar/Wind Harmer
0.017
319010AE1-072 C
Solar/Wind Harmer
4.06
970865AG2-541 GEN
Solar/Wind Harmer
8.137
957871AF2-081 GEN
Solar/Wind Harmer
10.005
3151081ELIZAR1
Adder
15.891
3151091ELIZAR2
Adder
15.615
3152611GOSPORTB
Adder
2.203
3152621GOSPORTC
Adder
1.869
3152601GOSPORTA
Adder
1.724
946301AF1-294 GEN
Solar/Wind Harmer
4.916
961791AG1-021 GEN
Solar/Wind Harmer
2.398
270455AD2-022 GEN
Solar/Wind Harmer
3.325
270457AD2-023 GEN
Solar/Wind Harmer
1.686
315657AE1-056 GEN
Solar/Wind Harmer
6.945
316123AC1-075 GEN
Solar/Wind Harmer
1.908
970165AG2-112 GEN
Solar/Wind Harmer
1.68
970163AG2-111 GEN
Solar/Wind Harmer
1.602
972265AH1-717 GEN
Adder
10.663
3151201GRAVEL4
Adder
9.996
3151191GRAVEL3
Adder
9.869
3151211GRAVEL5
Adder
9.869
971445AH1-216 GEN
Solar/Wind Harmer
2.771
3151381ROSEMG2
50/50
0.363
970535AG2-341 GEN
50/50
3.826
3152661PLYWOOD A
50/50
0.474
970933AG2-581 GEN
Solar/Wind Harmer
34.364
970099AG2-077 GEN
Solar/Wind Harmer
39.953
3144356SAPONY
Solar/Wind Harmer
1.018
316181AB2-040 GEN
Solar/Wind Harmer
3.451
939181AE1-148 GEN
Solar/Wind Harmer
13.835
3145796HORNRTN
Solar/Wind Harmer
-0.072
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
966811AG1-552 GEN
Solar/Wind Harmer
2.705
3145593CAROLNA
Solar/Wind Harmer
0.2
3145783HORNRTN
Solar/Wind Harmer
2.839
3145783HORNRTN
Solar/Wind Harmer
2.272
3145783HORNRTN
Solar/Wind Harmer
0.71
3145783HORNRTN
Solar/Wind Harmer
0.284
316426AA2-053 GEN
Solar/Wind Harmer
2.403
3146843MT LREL
Solar/Wind Harmer
-0.023
3146843MT LREL
Solar/Wind Harmer
-0.023
964791AG1-342 GEN
Solar/Wind Harmer
5.022
962561AG1-105 GEN
Solar/Wind Harmer
13.216
313527AB2-043 GEN
Solar/Wind Harmer
3.804
316274AC1-208 GEN
Solar/Wind Harmer
2.516
961601AG1-000A GEN
Solar/Wind Harmer
8.989
316263AC1-034 GEN
Solar/Wind Harmer
10.719
971741AH1-377 GEN
Solar/Wind Harmer
26.554
3145493TOT1
Solar/Wind Harmer
0.35
3145453TOT5
Solar/Wind Harmer
0.21
3145603CNETO
Solar/Wind Harmer
0.14
3145893MURPHYS
Solar/Wind Harmer
0.631
3145893MURPHYS
Solar/Wind Harmer
-0.041
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
3145933PARMELE
Solar/Wind Harmer
-0.044
3145933PARMELE
Solar/Wind Harmer
-0.022
316222AC1-221 GEN
Solar/Wind Harmer
2.217
316065AD1-022 GEN
Solar/Wind Harmer
10.926
315742AE1-103 GEN
Solar/Wind Harmer
2.245
970323AG2-213 GEN
Solar/Wind Harmer
10.573
971775AH1-396 GEN
Solar/Wind Harmer
1.506
316034AC1-036 C
Solar/Wind Harmer
0.392
3146376EDENTON
Solar/Wind Harmer
0.624
3146376EDENTON
Solar/Wind Harmer
0.624
970301AG2-198 GEN
Solar/Wind Harmer
10.435
3146626S HERTFORD
Solar/Wind Harmer
-0.021
3146626S HERTFORD
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.021
316431W1029_GEN1
Solar/Wind Harmer
3.733
316433W1029_GEN2
Solar/Wind Harmer
3.733
3146386ELIZ CT
Solar/Wind Harmer
-0.02
3130086AYDLETT
Solar/Wind Harmer
-0.08
3146456SLIGO L269
Solar/Wind Harmer
2.368
3137176SLIGO L2192
Solar/Wind Harmer
-0.079
316018AA1-139 ULT2
Solar/Wind Harmer
1.714
316017AA1-139 ULT1
Solar/Wind Harmer
1.619
316339AD2-160 GEN
Solar/Wind Harmer
1.348
3145506HICKORY
Solar/Wind Harmer
-0.079
3145506HICKORY
Solar/Wind Harmer
-0.048
3145506HICKORY
Solar/Wind Harmer
-0.012
970657AG2-426 GEN
Solar/Wind Harmer
6.206
970657AG2-426 GEN
Solar/Wind Harmer
1.298
316185AD1-033 GEN
Solar/Wind Harmer
2.091
3142956BIRDNECK
Solar/Wind Harmer
1.055
316316AC1-027 C
Solar/Wind Harmer
0.603
316036AC1-147 C
Solar/Wind Harmer
0.524
3150991CHESPKB
Adder
1.81
3150991CHESPKB
Adder
1.767
958211AF2-115 GEN
Solar/Wind Harmer
2.997
963191AG1-168 GEN
Solar/Wind Harmer
1.798
3144293JTRSVLE
Adder
0.543
3144293JTRSVLE
Adder
0.458
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.015
316236AE1-162_GEN
Solar/Wind Harmer
0.511
316447AC1-158 HLD
Solar/Wind Helper
2.845
316283AC2-100 C
Solar/Wind Harmer
2.053
315737AD1-076 GEN
Solar/Wind Harmer
4.121
971157AH1-035 GEN
Solar/Wind Harmer
2.704
315785AD2-033 C
Solar/Wind Harmer
4.883
315614AA2-178 GEN
Solar/Wind Harmer
2.306
3145273HOLLAND
Solar/Wind Harmer
-0.016
971683AH1-343 GEN
Solar/Wind Harmer
9.136
970257AG2-171 GEN
Solar/Wind Harmer
7.93
3146376EDENTON
Solar/Wind Harmer
-0.021
970909AG2-566 GEN
Solar/Wind Harmer
1.981
959311AF2-222 GEN
Solar/Wind Harmer
21.769
3146626S HERTFORD
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.021
316435W1029_GEN3
Solar/Wind Harmer
3.733
316320Y1-086
Solar/Wind Harmer
1.19
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.444
970661AG2-428 GEN
Solar/Wind Harmer
3.756
944581AF1-123 GEN
Solar/Wind Harmer
90.622
944601AF1-125 GEN
Solar/Wind Harmer
89.208
316083AB2-161 GEN
Solar/Wind Harmer
3.214
970659AG2-427 GEN
Solar/Wind Harmer
1.86
315813AE1-149 C
Solar/Wind Harmer
12.185
3151101ELIZAR3
Adder
16.095
3144873MCLAUGH
Solar/Wind Harmer
0
963181AG1-167 GEN
Solar/Wind Harmer
1.798
3144293JTRSVLE
Adder
0.543
3144536CHRHLND
Solar/Wind Harmer
-0.003
3147133PAMPLIN
Solar/Wind Harmer
-0.058
971193AH1-056 GEN
Solar/Wind Harmer
11.575
3145336SMITFLD
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.509
3151221GRAVEL6
Adder
9.984
3151171GRAVELC
Adder
1.921
3144216WINCHST
Adder
0.443
3150921YORKTN3
Adder
2.878
316044AC1-158 PL1
Solar/Wind Helper
1.293
316450AC1-158 RIC
Solar/Wind Helper
0.345
315243AE2-183_GT3
50/50
5.755
3151051BRUNSWICKS1
50/50
9.355
3151021BRUNSWICKG1
50/50
4.507
971451AH1-221 GEN
50/50
13.69
3151531CLOVER1
50/50
5.718
3151601KERR 3
50/50
0.458
3151581KERR 1
50/50
0.163
3147043LAWRENC
50/50
2.116
3151391GASTONA
50/50
0.588
3151411GASTONB
50/50
0.588
3151261ROARAP2
50/50
0.266
970919AG2-571 GEN
Solar/Wind Harmer
11.601
970087AG2-069 GEN
Solar/Wind Harmer
34.181
939411AE1-173 GEN
Solar/Wind Harmer
170.129
957481AF2-042 GEN
Solar/Wind Harmer
99.882
315693AD1-088 GEN
Solar/Wind Harmer
14.731
962491AG1-098 GEN
Solar/Wind Harmer
19.405
315687AD1-152 GEN
Solar/Wind Harmer
3.35
316023GEN1_S
Solar/Wind Harmer
1.761
960081AF2-299 GEN
Solar/Wind Harmer
2.853
971795AH1-408 GEN
Solar/Wind Harmer
18.718
971065AG2-659 GEN
Solar/Wind Harmer
12.309
316129AC1-054 GEN
Solar/Wind Harmer
2.154
316011AB1-132 GEN
Solar/Wind Harmer
5.114
962571AG1-106 GEN
Solar/Wind Harmer
3.514
3145796HORNRTN
Solar/Wind Harmer
-0.08
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145783HORNRTN
Solar/Wind Harmer
-0.024
316190AA2-174 GEN
Solar/Wind Harmer
0.292
970401AG2-262 GEN
Solar/Wind Harmer
1.534
316237AB2-079_GEN
Solar/Wind Harmer
0.708
315722AD1-056 GEN
Solar/Wind Harmer
2.456
316212AC1-099_GEN
Solar/Wind Harmer
2.016
3146263WOODLND
Solar/Wind Harmer
-0.023
3146233WITAKRS
Solar/Wind Harmer
-0.091
316359AB2-059 GEN
Solar/Wind Harmer
3.083
316049AB1-081 GEN
Solar/Wind Harmer
2.467
3142053HEARTS
Solar/Wind Harmer
0.269
3145543BTLEBRO
Solar/Wind Harmer
-0.023
3145543BTLEBRO
Solar/Wind Harmer
-0.018
3145823KELFORD
Solar/Wind Harmer
-0.023
961671AG1-007 GEN
Solar/Wind Harmer
0.286
3146083TARBORO
Solar/Wind Harmer
-0.023
3145493TOT1
Solar/Wind Harmer
0.672
3145893MURPHYS
Solar/Wind Harmer
-0.09
3145893MURPHYS
Solar/Wind Harmer
0.671
3146173TUNIS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
316494AC1-189 GEN
Solar/Wind Harmer
2.416
316003AC1-222 GEN
Solar/Wind Harmer
2.177
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3146293MARTNCO
Solar/Wind Harmer
0.137
316174AB2-169 GEN
Solar/Wind Harmer
3.387
3146206CASHIE
Solar/Wind Harmer
-0.022
971547AH1-271 GEN
Solar/Wind Harmer
5.488
3145963POPLR C
Solar/Wind Harmer
-0.022
3145663CRESWEL
Solar/Wind Harmer
-0.06
971163AH1-040 GEN
Solar/Wind Harmer
20.04
3130156CHOWAN
Solar/Wind Harmer
-0.021
315800Z1-036_GEN1
Solar/Wind Harmer
5.153
3146516WINFALL
Solar/Wind Harmer
-0.066
3146516WINFALL
Solar/Wind Harmer
-0.021
316093AE2-104_GEN
Solar/Wind Harmer
5.989
316246AF1-032 C
Solar/Wind Harmer
0.415
970685AG2-442 GEN
Solar/Wind Harmer
17.619
3146456SLIGO L269
Solar/Wind Harmer
-0.02
316388AE2-253 GEN
Solar/Wind Harmer
1.348
970661AG2-428 GEN
Solar/Wind Harmer
21.192
944591AF1-124 GEN
Solar/Wind Harmer
90.948
316381AD1-082 GEN
Solar/Wind Harmer
1.816
970659AG2-427 GEN
Solar/Wind Harmer
10.495
316375AC2-012 GEN
Solar/Wind Harmer
6.72
3150981CHESPKA
Adder
2.158
963171AG1-166 GEN
Solar/Wind Harmer
2.398
971563AH1-280 GEN
Solar/Wind Harmer
2.398
3144293JTRSVLE
Adder
0.543
316072AD1-144
Solar/Wind Harmer
0.387
3145336SMITFLD
Solar/Wind Harmer
-0.067
3151171GRAVELC
Adder
1.461
3143226MDLTHAN
Solar/Wind Helper
0.294
316045AC1-158 PL2
Solar/Wind Helper
4.138
CPLELTFEXP_CPLE->PJM
CLTF
14.701
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.1
LAGNLTFEXP_LAGN->PJM
CLTF
9.968
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.656
TVALTFEXP_TVA->PJM
CLTF
4.976
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.472
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.988
MECLTFEXP_MEC->PJM
CLTF
4.732
SIGELTFEXP_SIGE->PJM
CLTF
0.141
NYPJM->LTFIMP_NY
CLTF
2.22
LGEELTFEXP_LGEE->PJM
CLTF
1.693
WECLTFEXP_WEC->PJM
CLTF
0.873

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.65 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5068.75
MW Contribution:25.88
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
10.046
963041AG1-153 GEN
50/50
9.229
315779AE2-040
50/50
4.019
3151541CLOVER2
50/50
5.903
3151081ELIZAR1
50/50
26.625
941031AE2-094 GEN
Solar/Wind Harmer
76.807
944011AF1-069 GEN
Solar/Wind Harmer
24.066
970673AG2-436 GEN
Solar/Wind Harmer
84.048
970673AG2-436 GEN
Solar/Wind Harmer
42.556
971967AH1-528 GEN
Solar/Wind Harmer
73.252
970085AG2-068 GEN
Solar/Wind Harmer
23.153
970581AG2-369 GEN
Solar/Wind Harmer
19.912
316315AB2-025 C
Solar/Wind Harmer
0.873
315814AE2-033 C
Solar/Wind Harmer
30.01
957871AF2-081 GEN
Solar/Wind Harmer
15.436
319010AE1-072 C
Solar/Wind Harmer
6.231
3146406KITTY HAWK
Solar/Wind Harmer
0.026
3151091ELIZAR2
Adder
24.656
3152611GOSPORTB
Adder
3.473
3152621GOSPORTC
Adder
2.948
3152601GOSPORTA
Adder
2.719
313526AB2-022
Solar/Wind Harmer
0.825
316305AF2-043 C
Solar/Wind Harmer
0.92
316321Z2-027
Solar/Wind Harmer
0.822
3146396TANGLEW
Solar/Wind Harmer
0.561
3145176PASQUOTANK
Solar/Wind Harmer
-0.019
3146486SUNBURY
Solar/Wind Harmer
-0.03
3146486SUNBURY
Solar/Wind Harmer
-0.03
315611Z1-036_GEN2
Solar/Wind Harmer
7.417
315835AF2-110_GEN
Solar/Wind Harmer
3.752
3130156CHOWAN
Solar/Wind Harmer
-0.03
3130156CHOWAN
Solar/Wind Harmer
-0.03
315816AE2-034 GEN
Solar/Wind Harmer
2.381
3130546PLYMOUTH
Solar/Wind Harmer
-0.029
3151031BRUNSWICKG2
50/50
4.558
970413AG2-270 GEN
50/50
25.882
3151101ELIZAR3
50/50
26.966
970917AG2-570 GEN
Solar/Wind Harmer
93.072
315773AC2-141 GEN
Solar/Wind Harmer
13.388
944581AF1-123 GEN
Solar/Wind Harmer
143.09
944601AF1-125 GEN
Solar/Wind Harmer
140.857
316478AD1-087 GEN
Solar/Wind Harmer
2.694
316486AD2-202 GEN
Solar/Wind Harmer
0.789
3146456SLIGO L269
Solar/Wind Harmer
-0.031
971153AH1-033 GEN
Solar/Wind Harmer
3.757
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316320Y1-086
Solar/Wind Harmer
1.792
316435W1029_GEN3
Solar/Wind Harmer
5.494
3146516WINFALL
Solar/Wind Harmer
-0.03
3146626S HERTFORD
Solar/Wind Harmer
-0.03
316365GEN2_N
Solar/Wind Harmer
2.02
3146376EDENTON
Solar/Wind Harmer
-0.03
3144536CHRHLND
Solar/Wind Harmer
-0.005
3145273HOLLAND
Solar/Wind Harmer
-0.022
315614AA2-178 GEN
Solar/Wind Harmer
3.175
971157AH1-035 GEN
Solar/Wind Harmer
3.641
315737AD1-076 GEN
Solar/Wind Harmer
5.527
966621AG1-532 GEN
Solar/Wind Harmer
0.59
3156081AA2-088 GEN
Solar/Wind Harmer
9.415
3146206CASHIE
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.201
3145893MURPHYS
Solar/Wind Harmer
-0.029
957521AF2-046 GEN
Solar/Wind Harmer
22.687
961681AG1-008 GEN
Solar/Wind Harmer
22.687
313506AB2-031 GEN
Solar/Wind Harmer
2.311
3142666NORTHAMPTON
Solar/Wind Harmer
-0.029
3146173TUNIS
Solar/Wind Harmer
-0.029
3156021HOLLOMANSOL
Solar/Wind Harmer
3.868
316463AE2-346 GEN
Solar/Wind Harmer
0.464
316140AB2-099
Solar/Wind Harmer
0.193
962331AG1-082 GEN
Solar/Wind Harmer
3.582
3146263WOODLND
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.028
316317KELFORD C
Solar/Wind Harmer
1.333
3145823KELFORD
Solar/Wind Harmer
-0.028
3145963POPLR C
Solar/Wind Harmer
-0.028
3147043LAWRENC
Solar/Wind Harmer
-0.017
316210AC1-098 GEN
Solar/Wind Harmer
4.347
970661AG2-428 GEN
Solar/Wind Harmer
5.205
3145336SMITFLD
Solar/Wind Harmer
-0.011
3145933PARMELE
Solar/Wind Harmer
-0.027
966801AG1-551 GEN
Solar/Wind Harmer
3.433
315724AD1-057 GEN
Solar/Wind Harmer
1.573
316083AB2-161 GEN
Solar/Wind Harmer
4.404
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
316327AA2-057 GEN
Solar/Wind Harmer
2.736
970659AG2-427 GEN
Solar/Wind Harmer
2.538
3146233WITAKRS
Solar/Wind Harmer
0.56
3146233WITAKRS
Solar/Wind Harmer
-0.018
3138543CONSLDL
Solar/Wind Harmer
-0.018
3146073TAR RVR
Solar/Wind Harmer
-0.027
3146083TARBORO
Solar/Wind Harmer
-0.027
961601AG1-000A GEN
Solar/Wind Harmer
10.535
3145543BTLEBRO
Solar/Wind Harmer
-0.026
3145543BTLEBRO
Solar/Wind Harmer
-0.026
315813AE1-149 C
Solar/Wind Harmer
16.256
3151221GRAVEL6
Adder
16.617
3151171GRAVELC
Adder
3.197
316131AB2-060 GEN
Solar/Wind Harmer
2.74
316248AF1-058 C
Solar/Wind Harmer
0.76
960061AF2-297 GEN
Solar/Wind Harmer
12.605
3144216WINCHST
Adder
0.839
3150921YORKTN3
Adder
5.559
964241AG1-285 GEN
Solar/Wind Harmer
19.332
961611AG1-000B GEN
Solar/Wind Harmer
5.168
315785AD2-033 C
Solar/Wind Harmer
5.364
316283AC2-100 C
Solar/Wind Harmer
2.209
970257AG2-171 GEN
Solar/Wind Harmer
8.725
959311AF2-222 GEN
Solar/Wind Harmer
23.978
971683AH1-343 GEN
Solar/Wind Harmer
9.859
315839AE2-212 C
Solar/Wind Harmer
0.685
970909AG2-566 GEN
Solar/Wind Harmer
2.14
3144293JTRSVLE
Adder
0.603
3141843SHACKLE
Adder
0.78
3142433PROV 92
Adder
0.277
3142433PROV 92
Adder
0.277
3150351NORNECKC2
Adder
1.171
315732AD1-074 GEN1
Solar/Wind Harmer
5.881
315733AD1-074 GEN2
Solar/Wind Harmer
5.881
315735AD1-075 GEN1
Solar/Wind Harmer
2.941
946281AF1-292 GEN
Solar/Wind Harmer
0.651
965291AG1-394 GEN
Solar/Wind Harmer
2.57
316311AC2-079 GEN
Solar/Wind Harmer
14.59
3146206CASHIE
Solar/Wind Harmer
-0.029
970601AG2-382 GEN
Solar/Wind Harmer
12.655
315833AF1-017_GEN
Solar/Wind Harmer
5.49
316349AD2-085 GEN
Solar/Wind Harmer
2.571
316087AB2-174 GEN
Solar/Wind Harmer
4.115
316318V4-068
Solar/Wind Harmer
0.719
3145893MURPHYS
Solar/Wind Harmer
-0.077
3145893MURPHYS
Solar/Wind Harmer
-0.029
315652AC1-086 GEN
Solar/Wind Harmer
32.341
3145513AHOSKIE
Solar/Wind Harmer
0.25
961941AG1-037 GEN
Solar/Wind Harmer
0.215
3145513AHOSKIE
Solar/Wind Harmer
-0.029
3146043SEABORD
Solar/Wind Harmer
-0.029
315607AA1-063A GEN
Solar/Wind Harmer
2.891
3145683EARLEYS
Solar/Wind Harmer
-0.057
3145683EARLEYS
Solar/Wind Harmer
-0.029
3145683EARLEYS
Solar/Wind Harmer
-0.029
3137643SOCKMAN
Solar/Wind Harmer
-0.114
3145796HORNRTN
Solar/Wind Harmer
-0.09
3145796HORNRTN
Solar/Wind Harmer
-0.011
3146033SCOT NK
Solar/Wind Harmer
-0.111
970831AG2-522 GEN
Solar/Wind Harmer
13.829
3143316POE
Solar/Wind Harmer
-0.109
971445AH1-216 GEN
Solar/Wind Harmer
16.968
316005AA1-067
Solar/Wind Harmer
0.549
3145746EVERETS
Solar/Wind Harmer
-0.107
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
970181AG2-120 GEN
Solar/Wind Harmer
3.56
957861AF2-080 GEN
Solar/Wind Harmer
11.769
316420AA1-050 GEN
Solar/Wind Harmer
3.06
316319Z2-044 C
Solar/Wind Harmer
1.479
3145573BETHELC
Solar/Wind Harmer
-0.027
3145573BETHELC
Solar/Wind Harmer
-0.027
972265AH1-717 GEN
Adder
17.747
3151201GRAVEL4
Adder
16.636
3151191GRAVEL3
Adder
16.426
3151211GRAVEL5
Adder
16.426
316239AB2-077_GEN
Solar/Wind Harmer
0.772
316238AB2-078_GEN
Solar/Wind Harmer
0.772
316118AC1-105 GEN
Solar/Wind Harmer
1.739
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
4.598
3144303KENBRDG
Solar/Wind Harmer
-0.019
316369SG1_INVT
Solar/Wind Harmer
4.063
3142433PROV 92
Adder
0.277
3142433PROV 92
Adder
0.277
316164AC1-076 GEN
Solar/Wind Helper
1.186
970683AG2-441 GEN
Solar/Wind Harmer
2.176
970681AG2-440 GEN
Solar/Wind Harmer
1.741
316044AC1-158 PL1
Solar/Wind Helper
1.651
316450AC1-158 RIC
Solar/Wind Helper
0.44
3147666LOUISA
Solar/Wind Helper
0.583
316170AC1-121 GEN2
Solar/Wind Helper
0.349
315243AE2-183_GT3
50/50
5.81
3151051BRUNSWICKS1
50/50
9.459
3151021BRUNSWICKG1
50/50
4.558
971451AH1-221 GEN
50/50
13.843
3151531CLOVER1
50/50
5.931
940641AE2-051 GEN
Solar/Wind Harmer
38.323
939411AE1-173 GEN
Solar/Wind Harmer
192.154
970919AG2-571 GEN
Solar/Wind Harmer
11.781
970087AG2-069 GEN
Solar/Wind Harmer
34.73
957481AF2-042 GEN
Solar/Wind Harmer
102.878
316294AC1-161 GEN
Solar/Wind Harmer
10.352
944591AF1-124 GEN
Solar/Wind Harmer
143.606
316388AE2-253 GEN
Solar/Wind Harmer
2.083
3146456SLIGO L269
Solar/Wind Harmer
-0.031
316375AC2-012 GEN
Solar/Wind Harmer
10.604
3150981CHESPKA
Adder
3.405
315693AD1-088 GEN
Solar/Wind Harmer
15.307
316246AF1-032 C
Solar/Wind Harmer
0.618
3146516WINFALL
Solar/Wind Harmer
-0.098
3146516WINFALL
Solar/Wind Harmer
-0.03
962491AG1-098 GEN
Solar/Wind Harmer
20.194
315800Z1-036_GEN1
Solar/Wind Harmer
7.417
316093AE2-104_GEN
Solar/Wind Harmer
8.728
316023GEN1_S
Solar/Wind Harmer
2.02
3130156CHOWAN
Solar/Wind Harmer
-0.03
3145663CRESWEL
Solar/Wind Harmer
-0.082
971163AH1-040 GEN
Solar/Wind Harmer
27.585
316072AD1-144
Solar/Wind Harmer
0.593
315687AD1-152 GEN
Solar/Wind Harmer
3.505
960081AF2-299 GEN
Solar/Wind Harmer
3.27
3146206CASHIE
Solar/Wind Harmer
-0.029
971547AH1-271 GEN
Solar/Wind Harmer
7.231
3145893MURPHYS
Solar/Wind Harmer
-0.115
3145893MURPHYS
Solar/Wind Harmer
0.856
316011AB1-132 GEN
Solar/Wind Harmer
6.015
962571AG1-106 GEN
Solar/Wind Harmer
4.132
3146173TUNIS
Solar/Wind Harmer
-0.029
3145683EARLEYS
Solar/Wind Harmer
-0.029
3146263WOODLND
Solar/Wind Harmer
-0.028
316190AA2-174 GEN
Solar/Wind Harmer
0.349
3145796HORNRTN
Solar/Wind Harmer
-0.093
3145796HORNRTN
Solar/Wind Harmer
-0.028
971795AH1-408 GEN
Solar/Wind Harmer
21.251
3145823KELFORD
Solar/Wind Harmer
-0.028
3145783HORNRTN
Solar/Wind Harmer
-0.028
3145963POPLR C
Solar/Wind Harmer
-0.028
316174AB2-169 GEN
Solar/Wind Harmer
4.328
3147043LAWRENC
Adder
2.254
316212AC1-099_GEN
Solar/Wind Harmer
2.415
970661AG2-428 GEN
Solar/Wind Harmer
29.373
3145336SMITFLD
Solar/Wind Harmer
-0.11
316129AC1-054 GEN
Solar/Wind Harmer
2.418
971065AG2-659 GEN
Solar/Wind Harmer
13.753
3146293MARTNCO
Solar/Wind Harmer
0.17
315722AD1-056 GEN
Solar/Wind Harmer
2.859
316381AD1-082 GEN
Solar/Wind Harmer
2.488
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
970659AG2-427 GEN
Solar/Wind Harmer
14.32
316494AC1-189 GEN
Solar/Wind Harmer
2.894
3146233WITAKRS
Solar/Wind Harmer
-0.106
961671AG1-007 GEN
Solar/Wind Harmer
0.338
3146083TARBORO
Solar/Wind Harmer
-0.027
3145493TOT1
Solar/Wind Harmer
0.792
316359AB2-059 GEN
Solar/Wind Harmer
3.567
316049AB1-081 GEN
Solar/Wind Harmer
2.854
3142053HEARTS
Solar/Wind Harmer
0.311
3145543BTLEBRO
Solar/Wind Harmer
-0.026
3145543BTLEBRO
Solar/Wind Harmer
-0.021
3151171GRAVELC
Adder
2.431
316237AB2-079_GEN
Solar/Wind Harmer
0.772
970401AG2-262 GEN
Solar/Wind Harmer
1.655
3138126ROCKLANDING
Solar/Wind Harmer
0.076
961611AG1-000B GEN
Solar/Wind Harmer
12.112
316003AC1-222 GEN
Solar/Wind Harmer
2.339
971647AH1-324 GEN
Solar/Wind Harmer
11.817
971317AH1-138 GEN
Solar/Wind Harmer
2.931
970685AG2-442 GEN
Solar/Wind Harmer
19.464
3144293JTRSVLE
Adder
0.603
3141843SHACKLE
Adder
0.78
3142433PROV 92
Adder
0.277
3142433PROV 92
Adder
0.277
944631AF1-128 GEN
Adder
63.787
3150351NORNECKC2
Adder
1.152
316045AC1-158 PL2
Solar/Wind Helper
5.286
3147666LOUISA
Solar/Wind Helper
1.014
316192AB2-158 GEN
Solar/Wind Helper
1.677
316254AC1-120 GEN1
Solar/Wind Helper
1.048
970533AG2-339 GEN
50/50
32.408
970531AG2-338 GEN
50/50
12.963
315242AE2-183_GT2
50/50
5.81
315241AE2-183_GT1
50/50
5.775
972185AH1-677 GEN
50/50
20.947
3151041BRUNSWICKG3
50/50
4.558
972187AH1-678 GEN
50/50
10.459
970933AG2-581 GEN
Solar/Wind Harmer
34.906
970099AG2-077 GEN
Solar/Wind Harmer
41.151
3144356SAPONY
Solar/Wind Harmer
1.128
316185AD1-033 GEN
Solar/Wind Harmer
3.27
3145506HICKORY
Solar/Wind Harmer
-0.123
3145506HICKORY
Solar/Wind Harmer
-0.074
3145506HICKORY
Solar/Wind Harmer
-0.018
316339AD2-160 GEN
Solar/Wind Harmer
2.083
316018AA1-139 ULT2
Solar/Wind Harmer
2.645
316017AA1-139 ULT1
Solar/Wind Harmer
2.498
3142956BIRDNECK
Solar/Wind Harmer
1.655
3137176SLIGO L2192
Solar/Wind Harmer
-0.122
3146456SLIGO L269
Solar/Wind Harmer
3.64
316316AC1-027 C
Solar/Wind Harmer
0.946
3130086AYDLETT
Solar/Wind Harmer
-0.123
316036AC1-147 C
Solar/Wind Harmer
0.827
3150991CHESPKB
Adder
2.857
3150991CHESPKB
Adder
2.788
3146386ELIZ CT
Solar/Wind Harmer
-0.03
316431W1029_GEN1
Solar/Wind Harmer
5.494
316433W1029_GEN2
Solar/Wind Harmer
5.494
3146516WINFALL
Solar/Wind Harmer
-0.03
3146516WINFALL
Solar/Wind Harmer
-0.03
3146516WINFALL
Solar/Wind Harmer
-0.03
3146626S HERTFORD
Solar/Wind Harmer
-0.03
3146626S HERTFORD
Solar/Wind Harmer
-0.03
3146376EDENTON
Solar/Wind Harmer
0.884
3146376EDENTON
Solar/Wind Harmer
0.884
315742AE1-103 GEN
Solar/Wind Harmer
3.09
316065AD1-022 GEN
Solar/Wind Harmer
14.49
3145893MURPHYS
Solar/Wind Harmer
0.805
3145893MURPHYS
Solar/Wind Harmer
-0.052
316181AB2-040 GEN
Solar/Wind Harmer
4.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.029
3146173TUNIS
Solar/Wind Harmer
-0.029
316426AA2-053 GEN
Solar/Wind Harmer
2.872
3145796HORNRTN
Solar/Wind Harmer
-0.085
3145593CAROLNA
Solar/Wind Harmer
-0.028
3145593CAROLNA
Solar/Wind Harmer
-0.028
966811AG1-552 GEN
Solar/Wind Harmer
3.194
3145593CAROLNA
Solar/Wind Harmer
0.236
3145783HORNRTN
Solar/Wind Harmer
3.355
3145783HORNRTN
Solar/Wind Harmer
2.684
3145783HORNRTN
Solar/Wind Harmer
0.839
3145783HORNRTN
Solar/Wind Harmer
0.335
316274AC1-208 GEN
Solar/Wind Harmer
2.979
316236AE1-162_GEN
Solar/Wind Harmer
0.832
3145933PARMELE
Solar/Wind Harmer
-0.055
3145933PARMELE
Solar/Wind Harmer
-0.027
970657AG2-426 GEN
Solar/Wind Harmer
8.539
970657AG2-426 GEN
Solar/Wind Harmer
1.786
939181AE1-148 GEN
Solar/Wind Harmer
15.107
3145493TOT1
Solar/Wind Harmer
0.413
3145453TOT5
Solar/Wind Harmer
0.248
3145603CNETO
Solar/Wind Harmer
0.165
961601AG1-000A GEN
Solar/Wind Harmer
10.403
316263AC1-034 GEN
Solar/Wind Harmer
12.4
313527AB2-043 GEN
Solar/Wind Harmer
4.152
962561AG1-105 GEN
Solar/Wind Harmer
14.279
964791AG1-342 GEN
Solar/Wind Harmer
5.416
3146843MT LREL
Solar/Wind Harmer
-0.025
3146843MT LREL
Solar/Wind Harmer
-0.025
971741AH1-377 GEN
Solar/Wind Harmer
28.356
316222AC1-221 GEN
Solar/Wind Harmer
2.385
970323AG2-213 GEN
Solar/Wind Harmer
11.633
971775AH1-396 GEN
Solar/Wind Harmer
1.657
316034AC1-036 C
Solar/Wind Harmer
0.431
316033AB2-134 GEN
Solar/Wind Harmer
7.334
315697AD1-025 GEN
Solar/Wind Harmer
4.6
970301AG2-198 GEN
Solar/Wind Harmer
11.27
3144293JTRSVLE
Adder
0.603
3144293JTRSVLE
Adder
0.508
944641AF1-129 GEN
Adder
79.37
3150341NORNECKC1
Adder
1.21
3150341NORNECKC1
Adder
1.2
316447AC1-158 HLD
Solar/Wind Helper
3.634
315651AD1-115 GEN
Solar/Wind Helper
0.76
CPLELTFEXP_CPLE->PJM
CLTF
16.076
CBM West 2LTFEXP_CBM-W2->PJM
CBM
59.809
LAGNLTFEXP_LAGN->PJM
CLTF
11.324
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.876
TVALTFEXP_TVA->PJM
CLTF
5.674
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.878
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.45
MECLTFEXP_MEC->PJM
CLTF
5.512
SIGELTFEXP_SIGE->PJM
CLTF
0.166
NYPJM->LTFIMP_NY
CLTF
2.897
LGEELTFEXP_LGEE->PJM
CLTF
2.011
WECLTFEXP_WEC->PJM
CLTF
1.028

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.38 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5058.27
MW Contribution:25.73
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
9.99
963041AG1-153 GEN
50/50
9.178
315779AE2-040
50/50
3.975
3151541CLOVER2
50/50
5.868
3151081ELIZAR1
50/50
26.417
941031AE2-094 GEN
Solar/Wind Harmer
76.384
944011AF1-069 GEN
Solar/Wind Harmer
23.934
970673AG2-436 GEN
Solar/Wind Harmer
83.585
970673AG2-436 GEN
Solar/Wind Harmer
42.321
971967AH1-528 GEN
Solar/Wind Harmer
72.843
970085AG2-068 GEN
Solar/Wind Harmer
23.025
970581AG2-369 GEN
Solar/Wind Harmer
19.802
316315AB2-025 C
Solar/Wind Harmer
0.863
315814AE2-033 C
Solar/Wind Harmer
29.689
957871AF2-081 GEN
Solar/Wind Harmer
15.319
319010AE1-072 C
Solar/Wind Harmer
6.184
3146406KITTY HAWK
Solar/Wind Harmer
0.025
3151091ELIZAR2
Adder
24.463
3152611GOSPORTB
Adder
3.446
3152621GOSPORTC
Adder
2.924
3152601GOSPORTA
Adder
2.697
313526AB2-022
Solar/Wind Harmer
0.819
316305AF2-043 C
Solar/Wind Harmer
0.913
316321Z2-027
Solar/Wind Harmer
0.816
3146396TANGLEW
Solar/Wind Harmer
0.557
3145176PASQUOTANK
Solar/Wind Harmer
-0.019
3146486SUNBURY
Solar/Wind Harmer
-0.03
3146486SUNBURY
Solar/Wind Harmer
-0.03
315611Z1-036_GEN2
Solar/Wind Harmer
7.359
315835AF2-110_GEN
Solar/Wind Harmer
3.719
3130156CHOWAN
Solar/Wind Harmer
-0.029
3130156CHOWAN
Solar/Wind Harmer
-0.029
315816AE2-034 GEN
Solar/Wind Harmer
2.363
3130546PLYMOUTH
Solar/Wind Harmer
-0.029
315732AD1-074 GEN1
Solar/Wind Harmer
5.835
315733AD1-074 GEN2
Solar/Wind Harmer
5.835
315735AD1-075 GEN1
Solar/Wind Harmer
2.918
946281AF1-292 GEN
Solar/Wind Harmer
0.645
965291AG1-394 GEN
Solar/Wind Harmer
2.549
3146206CASHIE
Solar/Wind Harmer
-0.029
970601AG2-382 GEN
Solar/Wind Harmer
12.557
316318V4-068
Solar/Wind Harmer
0.713
3145893MURPHYS
Solar/Wind Harmer
-0.077
3145893MURPHYS
Solar/Wind Harmer
-0.029
316311AC2-079 GEN
Solar/Wind Harmer
14.429
316087AB2-174 GEN
Solar/Wind Harmer
4.08
315833AF1-017_GEN
Solar/Wind Harmer
5.429
316349AD2-085 GEN
Solar/Wind Harmer
2.542
3151031BRUNSWICKG2
50/50
4.532
970413AG2-270 GEN
50/50
25.729
3151101ELIZAR3
50/50
26.755
970917AG2-570 GEN
Solar/Wind Harmer
92.559
315773AC2-141 GEN
Solar/Wind Harmer
13.31
944581AF1-123 GEN
Solar/Wind Harmer
142.072
944601AF1-125 GEN
Solar/Wind Harmer
139.855
316478AD1-087 GEN
Solar/Wind Harmer
2.678
316486AD2-202 GEN
Solar/Wind Harmer
0.784
3146456SLIGO L269
Solar/Wind Harmer
-0.03
971153AH1-033 GEN
Solar/Wind Harmer
3.729
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316320Y1-086
Solar/Wind Harmer
1.779
316435W1029_GEN3
Solar/Wind Harmer
5.451
3146516WINFALL
Solar/Wind Harmer
-0.03
3146626S HERTFORD
Solar/Wind Harmer
-0.03
316365GEN2_N
Solar/Wind Harmer
2.001
3146376EDENTON
Solar/Wind Harmer
-0.029
3144536CHRHLND
Solar/Wind Harmer
-0.005
3145273HOLLAND
Solar/Wind Harmer
-0.022
315614AA2-178 GEN
Solar/Wind Harmer
3.15
971157AH1-035 GEN
Solar/Wind Harmer
3.613
315737AD1-076 GEN
Solar/Wind Harmer
5.484
966621AG1-532 GEN
Solar/Wind Harmer
0.585
3156081AA2-088 GEN
Solar/Wind Harmer
9.337
3146206CASHIE
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.2
3145893MURPHYS
Solar/Wind Harmer
-0.029
957521AF2-046 GEN
Solar/Wind Harmer
22.503
961681AG1-008 GEN
Solar/Wind Harmer
22.503
313506AB2-031 GEN
Solar/Wind Harmer
2.291
3146173TUNIS
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3156021HOLLOMANSOL
Solar/Wind Harmer
3.838
316463AE2-346 GEN
Solar/Wind Harmer
0.46
316140AB2-099
Solar/Wind Harmer
0.192
962331AG1-082 GEN
Solar/Wind Harmer
3.554
3146263WOODLND
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.112
3145796HORNRTN
Solar/Wind Harmer
-0.028
316317KELFORD C
Solar/Wind Harmer
1.323
3145823KELFORD
Solar/Wind Harmer
-0.028
3145963POPLR C
Solar/Wind Harmer
-0.028
3147043LAWRENC
Solar/Wind Harmer
-0.016
316210AC1-098 GEN
Solar/Wind Harmer
4.313
3145336SMITFLD
Solar/Wind Harmer
-0.011
3145933PARMELE
Solar/Wind Harmer
-0.027
966801AG1-551 GEN
Solar/Wind Harmer
3.408
970661AG2-428 GEN
Solar/Wind Harmer
5.132
315724AD1-057 GEN
Solar/Wind Harmer
1.561
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
316327AA2-057 GEN
Solar/Wind Harmer
2.715
316083AB2-161 GEN
Solar/Wind Harmer
4.337
3146233WITAKRS
Solar/Wind Harmer
0.556
3146233WITAKRS
Solar/Wind Harmer
-0.018
3138543CONSLDL
Solar/Wind Harmer
-0.017
970659AG2-427 GEN
Solar/Wind Harmer
2.498
3146073TAR RVR
Solar/Wind Harmer
-0.026
3146083TARBORO
Solar/Wind Harmer
-0.026
961601AG1-000A GEN
Solar/Wind Harmer
10.46
3145543BTLEBRO
Solar/Wind Harmer
-0.026
3145543BTLEBRO
Solar/Wind Harmer
-0.026
315813AE1-149 C
Solar/Wind Harmer
15.961
3151221GRAVEL6
Adder
16.378
3151171GRAVELC
Adder
3.151
316131AB2-060 GEN
Solar/Wind Harmer
2.721
316248AF1-058 C
Solar/Wind Harmer
0.755
960061AF2-297 GEN
Solar/Wind Harmer
12.532
3144216WINCHST
Adder
0.828
964241AG1-285 GEN
Solar/Wind Harmer
19.192
3150921YORKTN3
Adder
5.492
961611AG1-000B GEN
Solar/Wind Harmer
5.082
315785AD2-033 C
Solar/Wind Harmer
5.324
316283AC2-100 C
Solar/Wind Harmer
2.197
970257AG2-171 GEN
Solar/Wind Harmer
8.658
959311AF2-222 GEN
Solar/Wind Harmer
23.794
971683AH1-343 GEN
Solar/Wind Harmer
9.806
970909AG2-566 GEN
Solar/Wind Harmer
2.123
315839AE2-212 C
Solar/Wind Harmer
0.667
3144293JTRSVLE
Adder
0.598
3141843SHACKLE
Adder
0.757
3142433PROV 92
Adder
0.267
3142433PROV 92
Adder
0.267
316044AC1-158 PL1
Solar/Wind Helper
1.641
316450AC1-158 RIC
Solar/Wind Helper
0.438
3147666LOUISA
Solar/Wind Helper
0.579
316170AC1-121 GEN2
Solar/Wind Helper
0.347
315652AC1-086 GEN
Solar/Wind Harmer
32.069
3145513AHOSKIE
Solar/Wind Harmer
0.248
961941AG1-037 GEN
Solar/Wind Harmer
0.214
3145513AHOSKIE
Solar/Wind Harmer
-0.028
3146043SEABORD
Solar/Wind Harmer
-0.028
315607AA1-063A GEN
Solar/Wind Harmer
2.867
3145683EARLEYS
Solar/Wind Harmer
-0.056
3145683EARLEYS
Solar/Wind Harmer
-0.028
3145683EARLEYS
Solar/Wind Harmer
-0.028
3137643SOCKMAN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.09
3145796HORNRTN
Solar/Wind Harmer
-0.011
3146033SCOT NK
Solar/Wind Harmer
-0.11
970831AG2-522 GEN
Solar/Wind Harmer
13.728
3143316POE
Solar/Wind Harmer
-0.107
971445AH1-216 GEN
Solar/Wind Harmer
16.766
316005AA1-067
Solar/Wind Harmer
0.545
3145746EVERETS
Solar/Wind Harmer
-0.107
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
970181AG2-120 GEN
Solar/Wind Harmer
3.535
957861AF2-080 GEN
Solar/Wind Harmer
11.684
316420AA1-050 GEN
Solar/Wind Harmer
3.038
316319Z2-044 C
Solar/Wind Harmer
1.468
3145573BETHELC
Solar/Wind Harmer
-0.026
3145573BETHELC
Solar/Wind Harmer
-0.026
316239AB2-077_GEN
Solar/Wind Harmer
0.767
316238AB2-078_GEN
Solar/Wind Harmer
0.767
972265AH1-717 GEN
Adder
17.492
3151201GRAVEL4
Adder
16.397
3151191GRAVEL3
Adder
16.19
3151211GRAVEL5
Adder
16.19
316118AC1-105 GEN
Solar/Wind Harmer
1.728
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
4.563
3144303KENBRDG
Solar/Wind Harmer
-0.018
316369SG1_INVT
Solar/Wind Harmer
3.979
3142433PROV 92
Adder
0.267
3142433PROV 92
Adder
0.267
316164AC1-076 GEN
Solar/Wind Helper
1.177
970683AG2-441 GEN
Solar/Wind Harmer
2.159
970681AG2-440 GEN
Solar/Wind Harmer
1.727
315243AE2-183_GT3
50/50
5.778
3151051BRUNSWICKS1
50/50
9.407
3151021BRUNSWICKG1
50/50
4.532
971451AH1-221 GEN
50/50
13.766
3151531CLOVER1
50/50
5.896
940641AE2-051 GEN
Solar/Wind Harmer
38.111
939411AE1-173 GEN
Solar/Wind Harmer
191.017
970919AG2-571 GEN
Solar/Wind Harmer
11.716
970087AG2-069 GEN
Solar/Wind Harmer
34.538
957481AF2-042 GEN
Solar/Wind Harmer
102.271
316294AC1-161 GEN
Solar/Wind Harmer
10.291
944591AF1-124 GEN
Solar/Wind Harmer
142.584
316388AE2-253 GEN
Solar/Wind Harmer
2.068
3146456SLIGO L269
Solar/Wind Harmer
-0.03
315693AD1-088 GEN
Solar/Wind Harmer
15.212
316375AC2-012 GEN
Solar/Wind Harmer
10.52
3150981CHESPKA
Adder
3.378
316246AF1-032 C
Solar/Wind Harmer
0.613
3146516WINFALL
Solar/Wind Harmer
-0.097
3146516WINFALL
Solar/Wind Harmer
-0.03
962491AG1-098 GEN
Solar/Wind Harmer
20.067
315800Z1-036_GEN1
Solar/Wind Harmer
7.359
316093AE2-104_GEN
Solar/Wind Harmer
8.651
316023GEN1_S
Solar/Wind Harmer
2.001
3130156CHOWAN
Solar/Wind Harmer
-0.029
3145663CRESWEL
Solar/Wind Harmer
-0.081
971163AH1-040 GEN
Solar/Wind Harmer
27.372
316072AD1-144
Solar/Wind Harmer
0.588
315687AD1-152 GEN
Solar/Wind Harmer
3.484
960081AF2-299 GEN
Solar/Wind Harmer
3.241
3146206CASHIE
Solar/Wind Harmer
-0.029
971547AH1-271 GEN
Solar/Wind Harmer
7.175
3145893MURPHYS
Solar/Wind Harmer
-0.114
3145893MURPHYS
Solar/Wind Harmer
0.849
316011AB1-132 GEN
Solar/Wind Harmer
5.964
962571AG1-106 GEN
Solar/Wind Harmer
4.098
3146173TUNIS
Solar/Wind Harmer
-0.028
3145683EARLEYS
Solar/Wind Harmer
-0.028
3146263WOODLND
Solar/Wind Harmer
-0.028
316190AA2-174 GEN
Solar/Wind Harmer
0.346
3145796HORNRTN
Solar/Wind Harmer
-0.093
3145796HORNRTN
Solar/Wind Harmer
-0.028
971795AH1-408 GEN
Solar/Wind Harmer
21.071
3145823KELFORD
Solar/Wind Harmer
-0.028
3145783HORNRTN
Solar/Wind Harmer
-0.028
3145963POPLR C
Solar/Wind Harmer
-0.028
316174AB2-169 GEN
Solar/Wind Harmer
4.295
3147043LAWRENC
Adder
2.236
316212AC1-099_GEN
Solar/Wind Harmer
2.396
316129AC1-054 GEN
Solar/Wind Harmer
2.4
971065AG2-659 GEN
Solar/Wind Harmer
13.655
3145336SMITFLD
Solar/Wind Harmer
-0.109
3146293MARTNCO
Solar/Wind Harmer
0.169
970661AG2-428 GEN
Solar/Wind Harmer
28.962
315722AD1-056 GEN
Solar/Wind Harmer
2.838
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
316381AD1-082 GEN
Solar/Wind Harmer
2.45
316494AC1-189 GEN
Solar/Wind Harmer
2.873
3146233WITAKRS
Solar/Wind Harmer
-0.105
970659AG2-427 GEN
Solar/Wind Harmer
14.096
961671AG1-007 GEN
Solar/Wind Harmer
0.335
3146083TARBORO
Solar/Wind Harmer
-0.026
3145493TOT1
Solar/Wind Harmer
0.787
316359AB2-059 GEN
Solar/Wind Harmer
3.541
316049AB1-081 GEN
Solar/Wind Harmer
2.834
3145543BTLEBRO
Solar/Wind Harmer
-0.026
3145543BTLEBRO
Solar/Wind Harmer
-0.021
3142053HEARTS
Solar/Wind Harmer
0.309
316237AB2-079_GEN
Solar/Wind Harmer
0.767
3151171GRAVELC
Adder
2.396
970401AG2-262 GEN
Solar/Wind Harmer
1.644
3138126ROCKLANDING
Solar/Wind Harmer
0.075
961611AG1-000B GEN
Solar/Wind Harmer
11.911
316003AC1-222 GEN
Solar/Wind Harmer
2.326
971647AH1-324 GEN
Solar/Wind Harmer
11.598
971317AH1-138 GEN
Solar/Wind Harmer
2.891
970685AG2-442 GEN
Solar/Wind Harmer
19.311
3144293JTRSVLE
Adder
0.598
3141843SHACKLE
Adder
0.757
3142433PROV 92
Adder
0.267
3142433PROV 92
Adder
0.267
944631AF1-128 GEN
Adder
61.132
316045AC1-158 PL2
Solar/Wind Helper
5.253
3147666LOUISA
Solar/Wind Helper
1.007
316192AB2-158 GEN
Solar/Wind Helper
1.665
3143226MDLTHAN
Solar/Wind Helper
0.228
316254AC1-120 GEN1
Solar/Wind Helper
1.04
970533AG2-339 GEN
50/50
32.23
970531AG2-338 GEN
50/50
12.892
315242AE2-183_GT2
50/50
5.778
315241AE2-183_GT1
50/50
5.743
972185AH1-677 GEN
50/50
20.831
3151041BRUNSWICKG3
50/50
4.532
972187AH1-678 GEN
50/50
10.401
970933AG2-581 GEN
Solar/Wind Harmer
34.708
970099AG2-077 GEN
Solar/Wind Harmer
40.908
3144356SAPONY
Solar/Wind Harmer
1.116
316185AD1-033 GEN
Solar/Wind Harmer
3.245
3145506HICKORY
Solar/Wind Harmer
-0.122
3145506HICKORY
Solar/Wind Harmer
-0.073
3145506HICKORY
Solar/Wind Harmer
-0.018
316339AD2-160 GEN
Solar/Wind Harmer
2.068
316018AA1-139 ULT2
Solar/Wind Harmer
2.625
316017AA1-139 ULT1
Solar/Wind Harmer
2.479
3142956BIRDNECK
Solar/Wind Harmer
1.642
3137176SLIGO L2192
Solar/Wind Harmer
-0.121
3146456SLIGO L269
Solar/Wind Harmer
3.613
316316AC1-027 C
Solar/Wind Harmer
0.938
3130086AYDLETT
Solar/Wind Harmer
-0.122
316036AC1-147 C
Solar/Wind Harmer
0.82
3150991CHESPKB
Adder
2.834
3150991CHESPKB
Adder
2.766
3146386ELIZ CT
Solar/Wind Harmer
-0.03
316431W1029_GEN1
Solar/Wind Harmer
5.451
316433W1029_GEN2
Solar/Wind Harmer
5.451
3146516WINFALL
Solar/Wind Harmer
-0.03
3146516WINFALL
Solar/Wind Harmer
-0.03
3146516WINFALL
Solar/Wind Harmer
-0.03
3146626S HERTFORD
Solar/Wind Harmer
-0.03
3146626S HERTFORD
Solar/Wind Harmer
-0.03
3146376EDENTON
Solar/Wind Harmer
0.877
3146376EDENTON
Solar/Wind Harmer
0.877
315742AE1-103 GEN
Solar/Wind Harmer
3.064
316065AD1-022 GEN
Solar/Wind Harmer
14.378
3145893MURPHYS
Solar/Wind Harmer
0.798
3145893MURPHYS
Solar/Wind Harmer
-0.051
316181AB2-040 GEN
Solar/Wind Harmer
3.977
3146173TUNIS
Solar/Wind Harmer
-0.028
3146173TUNIS
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
316426AA2-053 GEN
Solar/Wind Harmer
2.849
3145796HORNRTN
Solar/Wind Harmer
-0.084
3145593CAROLNA
Solar/Wind Harmer
-0.028
3145593CAROLNA
Solar/Wind Harmer
-0.028
966811AG1-552 GEN
Solar/Wind Harmer
3.169
3145593CAROLNA
Solar/Wind Harmer
0.234
3145783HORNRTN
Solar/Wind Harmer
3.328
3145783HORNRTN
Solar/Wind Harmer
2.662
3145783HORNRTN
Solar/Wind Harmer
0.832
3145783HORNRTN
Solar/Wind Harmer
0.333
316274AC1-208 GEN
Solar/Wind Harmer
2.956
316236AE1-162_GEN
Solar/Wind Harmer
0.822
3145933PARMELE
Solar/Wind Harmer
-0.054
3145933PARMELE
Solar/Wind Harmer
-0.027
970657AG2-426 GEN
Solar/Wind Harmer
8.413
970657AG2-426 GEN
Solar/Wind Harmer
1.759
939181AE1-148 GEN
Solar/Wind Harmer
15.005
3145493TOT1
Solar/Wind Harmer
0.41
3145453TOT5
Solar/Wind Harmer
0.246
3145603CNETO
Solar/Wind Harmer
0.164
961601AG1-000A GEN
Solar/Wind Harmer
10.329
316263AC1-034 GEN
Solar/Wind Harmer
12.313
313527AB2-043 GEN
Solar/Wind Harmer
4.123
962561AG1-105 GEN
Solar/Wind Harmer
14.187
964791AG1-342 GEN
Solar/Wind Harmer
5.382
3146843MT LREL
Solar/Wind Harmer
-0.025
3146843MT LREL
Solar/Wind Harmer
-0.025
971741AH1-377 GEN
Solar/Wind Harmer
28.148
316222AC1-221 GEN
Solar/Wind Harmer
2.372
970323AG2-213 GEN
Solar/Wind Harmer
11.545
971775AH1-396 GEN
Solar/Wind Harmer
1.644
316034AC1-036 C
Solar/Wind Harmer
0.428
970301AG2-198 GEN
Solar/Wind Harmer
11.182
316033AB2-134 GEN
Solar/Wind Harmer
7.183
315697AD1-025 GEN
Solar/Wind Harmer
4.505
3144293JTRSVLE
Adder
0.598
3144293JTRSVLE
Adder
0.504
944641AF1-129 GEN
Adder
76.466
316447AC1-158 HLD
Solar/Wind Helper
3.611
315651AD1-115 GEN
Solar/Wind Helper
0.755
CPLELTFEXP_CPLE->PJM
CLTF
15.993
CBM West 2LTFEXP_CBM-W2->PJM
CBM
59.825
LAGNLTFEXP_LAGN->PJM
CLTF
11.311
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.727
TVALTFEXP_TVA->PJM
CLTF
5.669
CBM West 1LTFEXP_CBM-W1->PJM
CBM
36.059
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.441
MECLTFEXP_MEC->PJM
CLTF
5.526
SIGELTFEXP_SIGE->PJM
CLTF
0.166
NYPJM->LTFIMP_NY
CLTF
2.883
LGEELTFEXP_LGEE->PJM
CLTF
2.019
WECLTFEXP_WEC->PJM
CLTF
1.033

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562_SRT-S-1


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 562_SRT-S-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.67 %
Rating:3118.0 MVA
Rating Type:B
MVA to Mitigate:3606.7
MW Contribution:24.95
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
5.755
3151051BRUNSWICKS1
50/50
9.355
3151021BRUNSWICKG1
50/50
4.507
971451AH1-221 GEN
50/50
13.69
3151531CLOVER1
50/50
5.718
3151601KERR 3
50/50
0.458
3151581KERR 1
50/50
0.163
3147043LAWRENC
50/50
2.116
3151391GASTONA
50/50
0.588
3151411GASTONB
50/50
0.588
3151261ROARAP2
50/50
0.266
970919AG2-571 GEN
Solar/Wind Harmer
11.601
970087AG2-069 GEN
Solar/Wind Harmer
25.96
939411AE1-173 GEN
Solar/Wind Harmer
129.212
957481AF2-042 GEN
Solar/Wind Harmer
75.86
315693AD1-088 GEN
Solar/Wind Harmer
12.586
962491AG1-098 GEN
Solar/Wind Harmer
14.738
315687AD1-152 GEN
Solar/Wind Harmer
0.008
316023GEN1_S
Solar/Wind Harmer
0.521
960081AF2-299 GEN
Solar/Wind Harmer
2.167
971795AH1-408 GEN
Solar/Wind Harmer
14.808
971065AG2-659 GEN
Solar/Wind Harmer
9.349
316129AC1-054 GEN
Solar/Wind Harmer
0.822
316011AB1-132 GEN
Solar/Wind Harmer
3.954
962571AG1-106 GEN
Solar/Wind Harmer
3.094
3145796HORNRTN
Solar/Wind Harmer
0.711
3145796HORNRTN
Solar/Wind Harmer
0.215
3145783HORNRTN
Solar/Wind Harmer
0.213
316190AA2-174 GEN
Solar/Wind Harmer
0
970401AG2-262 GEN
Solar/Wind Harmer
1.228
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315722AD1-056 GEN
Solar/Wind Harmer
1.323
316212AC1-099_GEN
Solar/Wind Harmer
1.065
3146263WOODLND
Solar/Wind Harmer
0.205
3146233WITAKRS
Solar/Wind Harmer
0.813
316359AB2-059 GEN
Solar/Wind Harmer
0.731
316049AB1-081 GEN
Solar/Wind Harmer
1.165
3142053HEARTS
Solar/Wind Harmer
0.358
3145543BTLEBRO
Solar/Wind Harmer
0.203
3145543BTLEBRO
Solar/Wind Harmer
0.163
3145823KELFORD
Solar/Wind Harmer
0.203
961671AG1-007 GEN
Solar/Wind Harmer
0.031
3146083TARBORO
Solar/Wind Harmer
0.201
3145493TOT1
Solar/Wind Harmer
0.896
3145893MURPHYS
Solar/Wind Harmer
0.805
3145893MURPHYS
Solar/Wind Harmer
0.895
3146173TUNIS
Solar/Wind Harmer
0.201
3145683EARLEYS
Solar/Wind Harmer
0.201
316494AC1-189 GEN
Solar/Wind Harmer
0.675
316003AC1-222 GEN
Solar/Wind Harmer
0.005
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
3146293MARTNCO
Solar/Wind Harmer
0.183
316174AB2-169 GEN
Solar/Wind Harmer
0.005
3146206CASHIE
Solar/Wind Harmer
0.195
971547AH1-271 GEN
Solar/Wind Harmer
4.168
3145963POPLR C
Solar/Wind Harmer
0.195
3145663CRESWEL
Solar/Wind Harmer
0.532
971163AH1-040 GEN
Solar/Wind Harmer
15.22
3130156CHOWAN
Solar/Wind Harmer
0.187
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.594
3146516WINFALL
Solar/Wind Harmer
0.183
316093AE2-104_GEN
Solar/Wind Harmer
3.083
316246AF1-032 C
Solar/Wind Harmer
0.082
970685AG2-442 GEN
Solar/Wind Harmer
13.382
3146456SLIGO L269
Solar/Wind Harmer
0.178
316388AE2-253 GEN
Solar/Wind Harmer
0.557
970661AG2-428 GEN
Solar/Wind Harmer
17.657
944591AF1-124 GEN
Solar/Wind Harmer
40.063
316381AD1-082 GEN
Solar/Wind Harmer
0.184
970659AG2-427 GEN
Solar/Wind Harmer
8.503
316375AC2-012 GEN
Solar/Wind Harmer
0.004
3150981CHESPKA
Adder
2.158
963171AG1-166 GEN
Solar/Wind Harmer
0.911
971563AH1-280 GEN
Solar/Wind Harmer
1.821
3144293JTRSVLE
Adder
0.543
316072AD1-144
Solar/Wind Harmer
0.062
3145336SMITFLD
Solar/Wind Harmer
0.603
940641AE2-051 GEN
Solar/Wind Harmer
11.478
316294AC1-161 GEN
Solar/Wind Harmer
2.485
3151171GRAVELC
Adder
1.461
961611AG1-000B GEN
Solar/Wind Harmer
6.829
3146926FARMVIL
Solar/Wind Harmer
0.078
315671AE2-027_GEN
Solar/Wind Harmer
8.236
971647AH1-324 GEN
Solar/Wind Harmer
5.314
970223AG2-152 GEN
Solar/Wind Harmer
8.513
3138126ROCKLANDING
Solar/Wind Harmer
0.053
270016AE1-250 BESS
Solar/Wind Harmer
0.003
971069AG2-661 GEN
Solar/Wind Harmer
2.035
315244AE2-183_ST
50/50
9.95
963041AG1-153 GEN
50/50
9.127
3151541CLOVER2
50/50
5.691
315779AE2-040
50/50
3.626
3151611KERR 4
50/50
0.458
3151621KERR 5
50/50
0.458
3151631KERR 6
50/50
0.458
3151641KERR 7
50/50
0.458
3151281ROARAP4
50/50
0.259
3151281ROARAP4
50/50
0.243
941031AE2-094 GEN
Solar/Wind Harmer
66.739
944011AF1-069 GEN
Solar/Wind Harmer
21.806
970673AG2-436 GEN
Solar/Wind Harmer
75.33
970673AG2-436 GEN
Solar/Wind Harmer
50.22
971967AH1-528 GEN
Solar/Wind Harmer
54.881
970085AG2-068 GEN
Solar/Wind Harmer
17.307
970581AG2-369 GEN
Solar/Wind Harmer
14.884
316315AB2-025 C
Solar/Wind Harmer
0.21
315814AE2-033 C
Solar/Wind Harmer
20.441
316087AB2-174 GEN
Solar/Wind Harmer
0.006
970831AG2-522 GEN
Solar/Wind Harmer
9.311
315652AC1-086 GEN
Solar/Wind Harmer
23.921
3137643SOCKMAN
Solar/Wind Harmer
0.866
3145796HORNRTN
Solar/Wind Harmer
0.689
3145796HORNRTN
Solar/Wind Harmer
0.086
3147173SINAI
Solar/Wind Harmer
0.21
3147243WELCO
Solar/Wind Harmer
0.131
316118AC1-105 GEN
Solar/Wind Harmer
0.541
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
315607AA1-063A GEN
Solar/Wind Harmer
0.427
3146043SEABORD
Solar/Wind Harmer
0.208
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.817
3143316POE
Solar/Wind Harmer
0.807
3145573BETHELC
Solar/Wind Harmer
0.201
3145573BETHELC
Solar/Wind Harmer
0.201
965291AG1-394 GEN
Solar/Wind Harmer
0.895
3145893MURPHYS
Solar/Wind Harmer
0.543
3145893MURPHYS
Solar/Wind Harmer
0.201
3145513AHOSKIE
Solar/Wind Harmer
0.421
3145513AHOSKIE
Solar/Wind Harmer
0.201
3145683EARLEYS
Solar/Wind Harmer
0.402
3145683EARLEYS
Solar/Wind Harmer
0.201
3145683EARLEYS
Solar/Wind Harmer
0.201
316420AA1-050 GEN
Solar/Wind Harmer
0.007
957861AF2-080 GEN
Solar/Wind Harmer
8.615
316005AA1-067
Solar/Wind Harmer
0.212
3145746EVERETS
Solar/Wind Harmer
0.787
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
970181AG2-120 GEN
Solar/Wind Harmer
2.463
3146206CASHIE
Solar/Wind Harmer
0.195
970601AG2-382 GEN
Solar/Wind Harmer
7.294
315732AD1-074 GEN1
Solar/Wind Harmer
1.109
315733AD1-074 GEN2
Solar/Wind Harmer
1.109
315735AD1-075 GEN1
Solar/Wind Harmer
0.555
3130546PLYMOUTH
Solar/Wind Harmer
0.192
315816AE2-034 GEN
Solar/Wind Harmer
0.816
971443AH1-215 GEN
Solar/Wind Harmer
3.175
3144303KENBRDG
Solar/Wind Harmer
0.15
3130156CHOWAN
Solar/Wind Harmer
0.187
3130156CHOWAN
Solar/Wind Harmer
0.187
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
315835AF2-110_GEN
Solar/Wind Harmer
1.258
3146486SUNBURY
Solar/Wind Harmer
0.183
3146486SUNBURY
Solar/Wind Harmer
0.183
316305AF2-043 C
Solar/Wind Harmer
0.001
3145176PASQUOTANK
Solar/Wind Harmer
0.113
316321Z2-027
Solar/Wind Harmer
0.034
3146396TANGLEW
Solar/Wind Harmer
0.501
313526AB2-022
Solar/Wind Harmer
0.098
316311AC2-079 GEN
Solar/Wind Harmer
5.187
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.124
970683AG2-441 GEN
Solar/Wind Harmer
11.948
970681AG2-440 GEN
Solar/Wind Harmer
9.558
3146406KITTY HAWK
Solar/Wind Harmer
0.022
319010AE1-072 C
Solar/Wind Harmer
0.9
970865AG2-541 GEN
Solar/Wind Harmer
6.18
957871AF2-081 GEN
Solar/Wind Harmer
8.865
3151081ELIZAR1
Adder
15.891
3151091ELIZAR2
Adder
15.615
3152611GOSPORTB
Adder
2.203
3152621GOSPORTC
Adder
1.869
3152601GOSPORTA
Adder
1.724
946301AF1-294 GEN
Solar/Wind Harmer
3.369
961791AG1-021 GEN
Solar/Wind Harmer
1.639
315657AE1-056 GEN
Solar/Wind Harmer
5.685
316123AC1-075 GEN
Solar/Wind Harmer
0.215
970165AG2-112 GEN
Solar/Wind Harmer
1.276
970163AG2-111 GEN
Solar/Wind Harmer
1.217
971445AH1-216 GEN
Solar/Wind Harmer
10.534
972265AH1-717 GEN
Adder
10.663
3151201GRAVEL4
Adder
9.996
3151191GRAVEL3
Adder
9.869
3151211GRAVEL5
Adder
9.869
316369SG1_INVT
Solar/Wind Harmer
0.004
3143226MDLTHAN
Solar/Wind Helper
0.294
316045AC1-158 PL2
Solar/Wind Helper
4.138
970533AG2-339 GEN
50/50
32.21
970531AG2-338 GEN
50/50
12.884
315242AE2-183_GT2
50/50
5.755
315241AE2-183_GT1
50/50
5.72
972185AH1-677 GEN
50/50
20.748
3151041BRUNSWICKG3
50/50
4.507
972187AH1-678 GEN
50/50
10.344
3151361ROSEMG1
50/50
0.776
3151371ROSEMS1
50/50
0.481
3151381ROSEMG2
50/50
0.363
970535AG2-341 GEN
50/50
3.826
3152661PLYWOOD A
50/50
0.474
970933AG2-581 GEN
Solar/Wind Harmer
26.1
970099AG2-077 GEN
Solar/Wind Harmer
30.344
3144356SAPONY
Solar/Wind Harmer
2.173
316181AB2-040 GEN
Solar/Wind Harmer
0.319
939181AE1-148 GEN
Solar/Wind Harmer
10.508
3145796HORNRTN
Solar/Wind Harmer
0.646
3142666NORTHAMPTON
Solar/Wind Harmer
0.215
3142666NORTHAMPTON
Solar/Wind Harmer
0.215
3142666NORTHAMPTON
Solar/Wind Harmer
0.215
3142666NORTHAMPTON
Solar/Wind Harmer
0.129
3145593CAROLNA
Solar/Wind Harmer
0.214
3145593CAROLNA
Solar/Wind Harmer
0.214
966811AG1-552 GEN
Solar/Wind Harmer
2.321
3145593CAROLNA
Solar/Wind Harmer
0.266
3145783HORNRTN
Solar/Wind Harmer
3.786
3145783HORNRTN
Solar/Wind Harmer
3.029
3145783HORNRTN
Solar/Wind Harmer
0.946
3145783HORNRTN
Solar/Wind Harmer
0.379
316426AA2-053 GEN
Solar/Wind Harmer
0.715
3146843MT LREL
Solar/Wind Harmer
0.209
3146843MT LREL
Solar/Wind Harmer
0.209
964791AG1-342 GEN
Solar/Wind Harmer
4.018
962561AG1-105 GEN
Solar/Wind Harmer
10.037
313527AB2-043 GEN
Solar/Wind Harmer
0.003
316274AC1-208 GEN
Solar/Wind Harmer
1.077
961601AG1-000A GEN
Solar/Wind Harmer
3.618
316263AC1-034 GEN
Solar/Wind Harmer
7.734
971741AH1-377 GEN
Solar/Wind Harmer
20.167
3145493TOT1
Solar/Wind Harmer
0.467
3145453TOT5
Solar/Wind Harmer
0.28
3145603CNETO
Solar/Wind Harmer
0.187
3145893MURPHYS
Solar/Wind Harmer
1.347
3145893MURPHYS
Solar/Wind Harmer
0.362
3146173TUNIS
Solar/Wind Harmer
0.201
3146173TUNIS
Solar/Wind Harmer
0.201
3145933PARMELE
Solar/Wind Harmer
0.394
3145933PARMELE
Solar/Wind Harmer
0.197
316222AC1-221 GEN
Solar/Wind Harmer
0.81
316065AD1-022 GEN
Solar/Wind Harmer
8.955
315742AE1-103 GEN
Solar/Wind Harmer
0.002
970323AG2-213 GEN
Solar/Wind Harmer
8.03
971775AH1-396 GEN
Solar/Wind Harmer
0.301
316034AC1-036 C
Solar/Wind Harmer
0.014
3146376EDENTON
Solar/Wind Harmer
0.832
3146376EDENTON
Solar/Wind Harmer
0.832
970301AG2-198 GEN
Solar/Wind Harmer
7.926
3146626S HERTFORD
Solar/Wind Harmer
0.184
3146626S HERTFORD
Solar/Wind Harmer
0.184
3146516WINFALL
Solar/Wind Harmer
0.183
3146516WINFALL
Solar/Wind Harmer
0.183
3146516WINFALL
Solar/Wind Harmer
0.183
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146386ELIZ CT
Solar/Wind Harmer
0.181
3130086AYDLETT
Solar/Wind Harmer
0.715
3146456SLIGO L269
Solar/Wind Harmer
3.157
3137176SLIGO L2192
Solar/Wind Harmer
0.71
316018AA1-139 ULT2
Solar/Wind Harmer
0.004
316017AA1-139 ULT1
Solar/Wind Harmer
0.099
316339AD2-160 GEN
Solar/Wind Harmer
0.288
3145506HICKORY
Solar/Wind Harmer
0.708
3145506HICKORY
Solar/Wind Harmer
0.425
3145506HICKORY
Solar/Wind Harmer
0.106
970657AG2-426 GEN
Solar/Wind Harmer
6.19
970657AG2-426 GEN
Solar/Wind Harmer
1.298
316185AD1-033 GEN
Solar/Wind Harmer
0.005
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.168
316036AC1-147 C
Solar/Wind Harmer
0.032
3150991CHESPKB
Adder
1.81
3150991CHESPKB
Adder
1.767
958211AF2-115 GEN
Solar/Wind Harmer
2.049
963191AG1-168 GEN
Solar/Wind Harmer
0.683
3144293JTRSVLE
Adder
0.543
3144293JTRSVLE
Adder
0.458
3147133PAMPLIN
Solar/Wind Harmer
0.165
3147133PAMPLIN
Solar/Wind Harmer
0.132
316236AE1-162_GEN
Solar/Wind Harmer
0.001
942751AE2-291 GEN
Solar/Wind Harmer
7.84
316033AB2-134 GEN
Solar/Wind Harmer
0.007
315697AD1-025 GEN
Solar/Wind Harmer
0.134
316240AF1-291 C
Solar/Wind Harmer
0.001
270013AE1-250 PV
Solar/Wind Harmer
0.003
316447AC1-158 HLD
Solar/Wind Helper
2.845
3151031BRUNSWICKG2
50/50
4.507
970413AG2-270 GEN
50/50
24.952
3151591KERR 2
50/50
0.458
3151391GASTONA
50/50
0.588
3151411GASTONB
50/50
0.588
3151261ROARAP2
50/50
0.26
970917AG2-570 GEN
Solar/Wind Harmer
29.002
316478AD1-087 GEN
Solar/Wind Harmer
0.932
316486AD2-202 GEN
Solar/Wind Harmer
0.274
316365GEN2_N
Solar/Wind Harmer
0.521
3147043LAWRENC
Solar/Wind Harmer
0.132
313506AB2-031 GEN
Solar/Wind Harmer
0.68
3145796HORNRTN
Solar/Wind Harmer
0.862
3145796HORNRTN
Solar/Wind Harmer
0.215
3142666NORTHAMPTON
Solar/Wind Harmer
0.215
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
8.955
315724AD1-057 GEN
Solar/Wind Harmer
0.784
316131AB2-060 GEN
Solar/Wind Harmer
0.651
316210AC1-098 GEN
Solar/Wind Harmer
1.909
316327AA2-057 GEN
Solar/Wind Harmer
0.31
3146263WOODLND
Solar/Wind Harmer
0.205
3146233WITAKRS
Solar/Wind Harmer
1.026
3146233WITAKRS
Solar/Wind Harmer
0.139
3138543CONSLDL
Solar/Wind Harmer
0.135
961601AG1-000A GEN
Solar/Wind Harmer
14.474
971623AH1-311 GEN
Solar/Wind Harmer
0.407
3145543BTLEBRO
Solar/Wind Harmer
0.203
3145543BTLEBRO
Solar/Wind Harmer
0.203
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.203
3146073TAR RVR
Solar/Wind Harmer
0.201
3146083TARBORO
Solar/Wind Harmer
0.201
3145893MURPHYS
Solar/Wind Harmer
0.337
3145893MURPHYS
Solar/Wind Harmer
0.201
957521AF2-046 GEN
Solar/Wind Harmer
14.974
961681AG1-008 GEN
Solar/Wind Harmer
14.974
964241AG1-285 GEN
Solar/Wind Harmer
13.416
3146173TUNIS
Solar/Wind Harmer
0.201
316463AE2-346 GEN
Solar/Wind Harmer
0.173
316140AB2-099
Solar/Wind Harmer
0.072
962331AG1-082 GEN
Solar/Wind Harmer
2.146
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
3156021HOLLOMANSOL
Solar/Wind Harmer
0.903
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
3145933PARMELE
Solar/Wind Harmer
0.197
966801AG1-551 GEN
Solar/Wind Harmer
2.294
3146206CASHIE
Solar/Wind Harmer
0.195
3145963POPLR C
Solar/Wind Harmer
0.195
316283AC2-100 C
Solar/Wind Harmer
0.379
315737AD1-076 GEN
Solar/Wind Harmer
2.483
971157AH1-035 GEN
Solar/Wind Harmer
2.31
315785AD2-033 C
Solar/Wind Harmer
1.559
315614AA2-178 GEN
Solar/Wind Harmer
1.089
3145273HOLLAND
Solar/Wind Harmer
0.141
971683AH1-343 GEN
Solar/Wind Harmer
6.939
970257AG2-171 GEN
Solar/Wind Harmer
6.023
3146376EDENTON
Solar/Wind Harmer
0.187
970909AG2-566 GEN
Solar/Wind Harmer
1.981
959311AF2-222 GEN
Solar/Wind Harmer
16.501
3146626S HERTFORD
Solar/Wind Harmer
0.184
3146516WINFALL
Solar/Wind Harmer
0.183
316435W1029_GEN3
Solar/Wind Harmer
0.001
316320Y1-086
Solar/Wind Harmer
0.001
3146456SLIGO L269
Solar/Wind Harmer
0.178
971153AH1-033 GEN
Solar/Wind Harmer
2.063
970661AG2-428 GEN
Solar/Wind Harmer
3.756
944581AF1-123 GEN
Solar/Wind Harmer
39.921
944601AF1-125 GEN
Solar/Wind Harmer
39.306
316083AB2-161 GEN
Solar/Wind Harmer
0.002
970659AG2-427 GEN
Solar/Wind Harmer
1.86
315813AE1-149 C
Solar/Wind Harmer
9.255
3151101ELIZAR3
Adder
16.095
3144873MCLAUGH
Solar/Wind Harmer
0.004
963181AG1-167 GEN
Solar/Wind Harmer
0.683
3144293JTRSVLE
Adder
0.543
3144536CHRHLND
Solar/Wind Harmer
0.025
3147133PAMPLIN
Solar/Wind Harmer
0.517
971193AH1-056 GEN
Solar/Wind Harmer
10.036
3145336SMITFLD
Solar/Wind Harmer
0.06
315839AE2-212 C
Solar/Wind Harmer
0.001
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
315773AC2-141 GEN
Solar/Wind Harmer
5.238
965281AG1-393 GEN
Solar/Wind Harmer
1.472
3151221GRAVEL6
Adder
9.984
3151171GRAVELC
Adder
1.921
961611AG1-000B GEN
Solar/Wind Harmer
3.472
3146926FARMVIL
Solar/Wind Harmer
0.078
3144216WINCHST
Adder
0.443
3150921YORKTN3
Adder
2.878
315778AD1-151 GEN
Solar/Wind Harmer
9.159
316044AC1-158 PL1
Solar/Wind Helper
1.293
316450AC1-158 RIC
Solar/Wind Helper
0.345
CPLELTFEXP_CPLE->PJM
CLTF
14.701
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.1
LAGNLTFEXP_LAGN->PJM
CLTF
9.968
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.656
TVALTFEXP_TVA->PJM
CLTF
4.976
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.472
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.988
MECLTFEXP_MEC->PJM
CLTF
4.732
SIGELTFEXP_SIGE->PJM
CLTF
0.141
NYPJM->LTFIMP_NY
CLTF
2.22
LGEELTFEXP_LGEE->PJM
CLTF
1.693
WECLTFEXP_WEC->PJM
CLTF
0.873

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: BREMO B1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:108.3 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4267.15
MW Contribution:26.2
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
9.302
963041AG1-153 GEN
50/50
8.566
3151541CLOVER2
50/50
5.976
315779AE2-040
50/50
3.486
3151611KERR 4
50/50
0.508
3151621KERR 5
50/50
0.508
3151631KERR 6
50/50
0.508
3151641KERR 7
50/50
0.508
3151281ROARAP4
50/50
0.278
3151281ROARAP4
50/50
0.26
941031AE2-094 GEN
Solar/Wind Harmer
70.747
944011AF1-069 GEN
Solar/Wind Harmer
22.167
970673AG2-436 GEN
Solar/Wind Harmer
77.682
970673AG2-436 GEN
Solar/Wind Harmer
39.333
971967AH1-528 GEN
Solar/Wind Harmer
68.625
970085AG2-068 GEN
Solar/Wind Harmer
21.474
970581AG2-369 GEN
Solar/Wind Harmer
18.468
970285AG2-188 GEN
Solar/Wind Harmer
27.712
971845AH1-439 GEN
Solar/Wind Harmer
16.825
315657AE1-056 GEN
Solar/Wind Harmer
11.27
946301AF1-294 GEN
Solar/Wind Harmer
7.632
961791AG1-021 GEN
Solar/Wind Harmer
3.723
970683AG2-441 GEN
Solar/Wind Harmer
22.967
970681AG2-440 GEN
Solar/Wind Harmer
18.373
3144303KENBRDG
Solar/Wind Harmer
-0.023
971443AH1-215 GEN
Solar/Wind Harmer
5.7
316315AB2-025 C
Solar/Wind Harmer
0.757
315814AE2-033 C
Solar/Wind Harmer
26.059
316239AB2-077_GEN
Solar/Wind Harmer
0.842
316238AB2-078_GEN
Solar/Wind Harmer
0.842
970831AG2-522 GEN
Solar/Wind Harmer
13.417
946281AF1-292 GEN
Solar/Wind Harmer
0.596
316087AB2-174 GEN
Solar/Wind Harmer
3.756
3137643SOCKMAN
Solar/Wind Harmer
-0.103
316118AC1-105 GEN
Solar/Wind Harmer
1.777
315607AA1-063A GEN
Solar/Wind Harmer
2.581
3146043SEABORD
Solar/Wind Harmer
-0.025
315652AC1-086 GEN
Solar/Wind Harmer
28.68
957871AF2-081 GEN
Solar/Wind Harmer
12.659
319010AE1-072 C
Solar/Wind Harmer
5.115
3146406KITTY HAWK
Solar/Wind Harmer
0.021
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.016
3145796HORNRTN
Solar/Wind Harmer
-0.08
3145796HORNRTN
Solar/Wind Harmer
-0.01
965291AG1-394 GEN
Solar/Wind Harmer
2.237
313526AB2-022
Solar/Wind Harmer
0.68
316321Z2-027
Solar/Wind Harmer
0.679
3146396TANGLEW
Solar/Wind Harmer
0.463
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
316318V4-068
Solar/Wind Harmer
0.626
3145893MURPHYS
Solar/Wind Harmer
-0.067
3145893MURPHYS
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
316305AF2-043 C
Solar/Wind Harmer
0.755
3151081ELIZAR1
Adder
20.42
3151091ELIZAR2
Adder
20.065
315611Z1-036_GEN2
Solar/Wind Harmer
6.178
3145513AHOSKIE
Solar/Wind Harmer
0.218
961941AG1-037 GEN
Solar/Wind Harmer
0.188
3145513AHOSKIE
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
3152611GOSPORTB
Adder
2.824
3152621GOSPORTC
Adder
2.396
3152601GOSPORTA
Adder
2.211
3145683EARLEYS
Solar/Wind Harmer
-0.049
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
315816AE2-034 GEN
Solar/Wind Harmer
2.011
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
3146206CASHIE
Solar/Wind Harmer
-0.025
970601AG2-382 GEN
Solar/Wind Harmer
10.834
3146033SCOT NK
Solar/Wind Harmer
-0.099
315732AD1-074 GEN1
Solar/Wind Harmer
5.007
315733AD1-074 GEN2
Solar/Wind Harmer
5.007
315735AD1-075 GEN1
Solar/Wind Harmer
2.504
315835AF2-110_GEN
Solar/Wind Harmer
3.076
316319Z2-044 C
Solar/Wind Harmer
1.327
316005AA1-067
Solar/Wind Harmer
0.482
3145746EVERETS
Solar/Wind Harmer
-0.094
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
970181AG2-120 GEN
Solar/Wind Harmer
3.13
957861AF2-080 GEN
Solar/Wind Harmer
10.414
316420AA1-050 GEN
Solar/Wind Harmer
2.716
3145573BETHELC
Solar/Wind Harmer
-0.024
3145573BETHELC
Solar/Wind Harmer
-0.024
316311AC2-079 GEN
Solar/Wind Harmer
11.791
315833AF1-017_GEN
Solar/Wind Harmer
4.435
316349AD2-085 GEN
Solar/Wind Harmer
2.077
3143316POE
Solar/Wind Harmer
-0.087
972265AH1-717 GEN
Adder
13.355
3151201GRAVEL4
Adder
12.519
3151191GRAVEL3
Adder
12.361
3151211GRAVEL5
Adder
12.361
316233AE1-074 FULL
Solar/Wind Helper
0.35
315243AE2-183_GT3
50/50
5.38
3151051BRUNSWICKS1
50/50
8.78
3151021BRUNSWICKG1
50/50
4.23
971451AH1-221 GEN
50/50
12.849
3151531CLOVER1
50/50
6.004
3144293JTRSVLE
50/50
0.895
3151601KERR 3
50/50
0.508
3151581KERR 1
50/50
0.181
3147043LAWRENC
50/50
2.311
3151261ROARAP2
50/50
0.286
3151391GASTONA
50/50
0.614
3151411GASTONB
50/50
0.614
940641AE2-051 GEN
Solar/Wind Harmer
34.524
970919AG2-571 GEN
Solar/Wind Harmer
10.928
970087AG2-069 GEN
Solar/Wind Harmer
32.211
939411AE1-173 GEN
Solar/Wind Harmer
169.915
957481AF2-042 GEN
Solar/Wind Harmer
103.233
315693AD1-088 GEN
Solar/Wind Harmer
16.294
962491AG1-098 GEN
Solar/Wind Harmer
21.776
3146926FARMVIL
Solar/Wind Harmer
-0.019
316322AB2-045
Solar/Wind Harmer
1.065
3146776BUCKING
Solar/Wind Harmer
-0.013
972003AH1-546 GEN
Solar/Wind Harmer
15.792
963171AG1-166 GEN
Solar/Wind Harmer
3.723
971563AH1-280 GEN
Solar/Wind Harmer
3.723
970685AG2-442 GEN
Solar/Wind Harmer
25.722
315687AD1-152 GEN
Solar/Wind Harmer
3.514
316237AB2-079_GEN
Solar/Wind Harmer
0.842
971065AG2-659 GEN
Solar/Wind Harmer
13.526
316129AC1-054 GEN
Solar/Wind Harmer
2.362
971795AH1-408 GEN
Solar/Wind Harmer
20.182
960081AF2-299 GEN
Solar/Wind Harmer
2.993
316023GEN1_S
Solar/Wind Harmer
1.787
970401AG2-262 GEN
Solar/Wind Harmer
1.725
316294AC1-161 GEN
Solar/Wind Harmer
8.447
944591AF1-124 GEN
Solar/Wind Harmer
117.74
316190AA2-174 GEN
Solar/Wind Harmer
0.315
3145783HORNRTN
Solar/Wind Harmer
-0.026
316011AB1-132 GEN
Solar/Wind Harmer
5.334
962571AG1-106 GEN
Solar/Wind Harmer
3.665
316388AE2-253 GEN
Solar/Wind Harmer
1.708
3146456SLIGO L269
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.083
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146263WOODLND
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
-0.1
3145893MURPHYS
Solar/Wind Harmer
0.745
3146516WINFALL
Solar/Wind Harmer
-0.081
3146516WINFALL
Solar/Wind Harmer
-0.025
316246AF1-032 C
Solar/Wind Harmer
0.507
3146173TUNIS
Solar/Wind Harmer
-0.025
315800Z1-036_GEN1
Solar/Wind Harmer
6.178
3130156CHOWAN
Solar/Wind Harmer
-0.025
316375AC2-012 GEN
Solar/Wind Harmer
8.621
3150981CHESPKA
Adder
2.768
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145663CRESWEL
Solar/Wind Harmer
-0.069
971163AH1-040 GEN
Solar/Wind Harmer
23.294
3145823KELFORD
Solar/Wind Harmer
-0.025
3146206CASHIE
Solar/Wind Harmer
-0.025
971547AH1-271 GEN
Solar/Wind Harmer
6.191
316212AC1-099_GEN
Solar/Wind Harmer
2.154
316093AE2-104_GEN
Solar/Wind Harmer
7.155
315722AD1-056 GEN
Solar/Wind Harmer
2.553
3145963POPLR C
Solar/Wind Harmer
-0.024
316174AB2-169 GEN
Solar/Wind Harmer
3.744
3146233WITAKRS
Solar/Wind Harmer
-0.095
3146293MARTNCO
Solar/Wind Harmer
0.149
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
316003AC1-222 GEN
Solar/Wind Harmer
2.327
316494AC1-189 GEN
Solar/Wind Harmer
2.561
961671AG1-007 GEN
Solar/Wind Harmer
0.3
3146083TARBORO
Solar/Wind Harmer
-0.024
3145493TOT1
Solar/Wind Harmer
0.705
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.019
316359AB2-059 GEN
Solar/Wind Harmer
3.202
316049AB1-081 GEN
Solar/Wind Harmer
2.562
3142053HEARTS
Solar/Wind Harmer
0.279
316072AD1-144
Solar/Wind Harmer
0.477
3151171GRAVELC
Adder
1.83
3143226MDLTHAN
Solar/Wind Helper
0.35
316336AC2-165 C
Solar/Wind Helper
1.883
316045AC1-158 PL2
Solar/Wind Helper
4.241
3143526WINTERP
Solar/Wind Helper
1.191
970661AG2-428 GEN
Solar/Wind Harmer
10.44
970533AG2-339 GEN
50/50
29.851
970531AG2-338 GEN
50/50
11.94
315242AE2-183_GT2
50/50
5.38
315241AE2-183_GT1
50/50
5.347
972185AH1-677 GEN
50/50
19.395
3151041BRUNSWICKG3
50/50
4.23
972187AH1-678 GEN
50/50
9.708
3144293JTRSVLE
50/50
0.895
3144293JTRSVLE
50/50
0.754
970535AG2-341 GEN
50/50
4.4
3152661PLYWOOD A
50/50
0.514
3151361ROSEMG1
50/50
0.809
3151371ROSEMS1
50/50
0.501
3151381ROSEMG2
50/50
0.379
970933AG2-581 GEN
Solar/Wind Harmer
33.334
970099AG2-077 GEN
Solar/Wind Harmer
41.293
971741AH1-377 GEN
Solar/Wind Harmer
37.414
970301AG2-198 GEN
Solar/Wind Harmer
16.032
3146776BUCKING
Solar/Wind Harmer
-0.126
3146776BUCKING
Solar/Wind Harmer
-0.01
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
958211AF2-115 GEN
Solar/Wind Harmer
4.654
963191AG1-168 GEN
Solar/Wind Harmer
2.792
316034AC1-036 C
Solar/Wind Harmer
0.538
970323AG2-213 GEN
Solar/Wind Harmer
14.493
971775AH1-396 GEN
Solar/Wind Harmer
2.064
313527AB2-043 GEN
Solar/Wind Harmer
4.56
3144356SAPONY
Solar/Wind Harmer
0.979
939181AE1-148 GEN
Solar/Wind Harmer
15.561
962561AG1-105 GEN
Solar/Wind Harmer
15.007
964791AG1-342 GEN
Solar/Wind Harmer
5.646
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
316181AB2-040 GEN
Solar/Wind Harmer
3.656
3145593CAROLNA
Solar/Wind Harmer
-0.026
3145593CAROLNA
Solar/Wind Harmer
-0.026
966811AG1-552 GEN
Solar/Wind Harmer
2.899
3145593CAROLNA
Solar/Wind Harmer
0.214
316426AA2-053 GEN
Solar/Wind Harmer
2.588
3145783HORNRTN
Solar/Wind Harmer
3.04
3145783HORNRTN
Solar/Wind Harmer
2.432
3145783HORNRTN
Solar/Wind Harmer
0.76
3145783HORNRTN
Solar/Wind Harmer
0.304
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
3145506HICKORY
Solar/Wind Harmer
-0.101
3145506HICKORY
Solar/Wind Harmer
-0.061
3145506HICKORY
Solar/Wind Harmer
-0.015
316185AD1-033 GEN
Solar/Wind Harmer
2.674
316339AD2-160 GEN
Solar/Wind Harmer
1.708
316018AA1-139 ULT2
Solar/Wind Harmer
2.169
316017AA1-139 ULT1
Solar/Wind Harmer
2.049
3137176SLIGO L2192
Solar/Wind Harmer
-0.1
3146456SLIGO L269
Solar/Wind Harmer
2.987
3130086AYDLETT
Solar/Wind Harmer
-0.101
3145796HORNRTN
Solar/Wind Harmer
-0.075
3146386ELIZ CT
Solar/Wind Harmer
-0.025
3142956BIRDNECK
Solar/Wind Harmer
1.35
316316AC1-027 C
Solar/Wind Harmer
0.771
3145893MURPHYS
Solar/Wind Harmer
0.7
3145893MURPHYS
Solar/Wind Harmer
-0.045
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
316431W1029_GEN1
Solar/Wind Harmer
4.542
316433W1029_GEN2
Solar/Wind Harmer
4.542
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
3146376EDENTON
Solar/Wind Harmer
0.74
3146376EDENTON
Solar/Wind Harmer
0.74
316036AC1-147 C
Solar/Wind Harmer
0.672
3150991CHESPKB
Adder
2.322
3150991CHESPKB
Adder
2.267
315742AE1-103 GEN
Solar/Wind Harmer
2.599
316274AC1-208 GEN
Solar/Wind Harmer
2.674
316065AD1-022 GEN
Solar/Wind Harmer
12.38
3145933PARMELE
Solar/Wind Harmer
-0.048
3145933PARMELE
Solar/Wind Harmer
-0.024
3145493TOT1
Solar/Wind Harmer
0.368
3145453TOT5
Solar/Wind Harmer
0.221
3145603CNETO
Solar/Wind Harmer
0.147
316263AC1-034 GEN
Solar/Wind Harmer
11.133
961601AG1-000A GEN
Solar/Wind Harmer
9.326
316222AC1-221 GEN
Solar/Wind Harmer
2.263
316447AC1-158 HLD
Solar/Wind Helper
2.916
3143526WINTERP
Solar/Wind Helper
1.191
3151031BRUNSWICKG2
50/50
4.23
970413AG2-270 GEN
50/50
26.203
3144293JTRSVLE
50/50
0.895
3151591KERR 2
50/50
0.508
3151261ROARAP2
50/50
0.279
3151391GASTONA
50/50
0.614
3151411GASTONB
50/50
0.614
970917AG2-570 GEN
Solar/Wind Harmer
86.33
970909AG2-566 GEN
Solar/Wind Harmer
3.044
3146926FARMVIL
Solar/Wind Harmer
-0.019
3146776BUCKING
Solar/Wind Harmer
-0.011
316478AD1-087 GEN
Solar/Wind Harmer
2.727
316486AD2-202 GEN
Solar/Wind Harmer
0.799
942461AE2-259 GEN
Solar/Wind Harmer
4.631
3147133PAMPLIN
Solar/Wind Harmer
-0.094
971193AH1-056 GEN
Solar/Wind Harmer
18.784
963181AG1-167 GEN
Solar/Wind Harmer
2.792
959311AF2-222 GEN
Solar/Wind Harmer
30.378
970257AG2-171 GEN
Solar/Wind Harmer
10.87
315785AD2-033 C
Solar/Wind Harmer
6.532
964241AG1-285 GEN
Solar/Wind Harmer
22.181
316131AB2-060 GEN
Solar/Wind Harmer
3.035
3147043LAWRENC
Solar/Wind Harmer
-0.016
966621AG1-532 GEN
Solar/Wind Harmer
0.54
316365GEN2_N
Solar/Wind Harmer
1.787
313506AB2-031 GEN
Solar/Wind Harmer
2.107
315773AC2-141 GEN
Solar/Wind Harmer
10.925
944581AF1-123 GEN
Solar/Wind Harmer
117.317
944601AF1-125 GEN
Solar/Wind Harmer
115.486
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3146456SLIGO L269
Solar/Wind Harmer
-0.025
971153AH1-033 GEN
Solar/Wind Harmer
3.083
316248AF1-058 C
Solar/Wind Harmer
0.761
960061AF2-297 GEN
Solar/Wind Harmer
12.626
3145796HORNRTN
Solar/Wind Harmer
-0.1
3145796HORNRTN
Solar/Wind Harmer
-0.025
316320Y1-086
Solar/Wind Harmer
1.477
3156081AA2-088 GEN
Solar/Wind Harmer
8.171
3146263WOODLND
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.175
3145893MURPHYS
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
957521AF2-046 GEN
Solar/Wind Harmer
19.748
961681AG1-008 GEN
Solar/Wind Harmer
19.748
316435W1029_GEN3
Solar/Wind Harmer
4.542
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3151101ELIZAR3
Adder
20.681
3146173TUNIS
Solar/Wind Harmer
-0.025
316463AE2-346 GEN
Solar/Wind Harmer
0.404
316140AB2-099
Solar/Wind Harmer
0.168
962331AG1-082 GEN
Solar/Wind Harmer
3.119
3146376EDENTON
Solar/Wind Harmer
-0.025
3144873MCLAUGH
Solar/Wind Harmer
-0.001
315614AA2-178 GEN
Solar/Wind Harmer
2.681
316317KELFORD C
Solar/Wind Harmer
1.17
3145823KELFORD
Solar/Wind Harmer
-0.025
3145273HOLLAND
Solar/Wind Harmer
-0.019
3156021HOLLOMANSOL
Solar/Wind Harmer
3.338
971157AH1-035 GEN
Solar/Wind Harmer
3.096
3146206CASHIE
Solar/Wind Harmer
-0.025
315737AD1-076 GEN
Solar/Wind Harmer
4.705
316210AC1-098 GEN
Solar/Wind Harmer
3.877
315724AD1-057 GEN
Solar/Wind Harmer
1.404
3145963POPLR C
Solar/Wind Harmer
-0.024
316327AA2-057 GEN
Solar/Wind Harmer
2.454
3146233WITAKRS
Solar/Wind Harmer
0.503
3146233WITAKRS
Solar/Wind Harmer
-0.016
3145933PARMELE
Solar/Wind Harmer
-0.024
966801AG1-551 GEN
Solar/Wind Harmer
2.999
3138543CONSLDL
Solar/Wind Harmer
-0.016
3144536CHRHLND
Solar/Wind Harmer
-0.004
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
3146073TAR RVR
Solar/Wind Harmer
-0.024
3146083TARBORO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.024
961601AG1-000A GEN
Solar/Wind Harmer
9.444
971683AH1-343 GEN
Solar/Wind Harmer
9.745
316283AC2-100 C
Solar/Wind Harmer
2.093
3151221GRAVEL6
Adder
12.505
3151171GRAVELC
Adder
2.406
3144216WINCHST
Adder
0.613
3150921YORKTN3
Adder
4.045
316313AB2-026
Solar/Wind Helper
0.532
316258AE1-075 C
Solar/Wind Helper
0.479
316405AF2-144 C
Solar/Wind Helper
0.399
316044AC1-158 PL1
Solar/Wind Helper
1.325
316450AC1-158 RIC
Solar/Wind Helper
0.353
970661AG2-428 GEN
Solar/Wind Harmer
1.85
CPLELTFEXP_CPLE->PJM
CLTF
14.708
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.937
LAGNLTFEXP_LAGN->PJM
CLTF
9.794
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.485
TVALTFEXP_TVA->PJM
CLTF
4.889
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.197
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.662
MECLTFEXP_MEC->PJM
CLTF
4.586
SIGELTFEXP_SIGE->PJM
CLTF
0.137
NYPJM->LTFIMP_NY
CLTF
2.27
LGEELTFEXP_LGEE->PJM
CLTF
1.633
WECLTFEXP_WEC->PJM
CLTF
0.839

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2003-205_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2003-205_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:107.33 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4228.67
MW Contribution:24.3
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
9.597
963041AG1-153 GEN
50/50
8.809
315779AE2-040
50/50
4.21
3151541CLOVER2
50/50
5.541
3151281ROARAP4
50/50
0.287
3151281ROARAP4
50/50
0.268
3151151S HAMPT1
50/50
0.598
3151611KERR 4
50/50
0.465
3151621KERR 5
50/50
0.465
3151631KERR 6
50/50
0.465
3151641KERR 7
50/50
0.465
941031AE2-094 GEN
Solar/Wind Harmer
73.515
944011AF1-069 GEN
Solar/Wind Harmer
23.035
970673AG2-436 GEN
Solar/Wind Harmer
80.349
970673AG2-436 GEN
Solar/Wind Harmer
40.683
971967AH1-528 GEN
Solar/Wind Harmer
69.889
970085AG2-068 GEN
Solar/Wind Harmer
22.054
970581AG2-369 GEN
Solar/Wind Harmer
18.967
316315AB2-025 C
Solar/Wind Harmer
0.914
315814AE2-033 C
Solar/Wind Harmer
31.355
3143316POE
Solar/Wind Harmer
-0.131
946281AF1-292 GEN
Solar/Wind Harmer
0.632
316087AB2-174 GEN
Solar/Wind Harmer
3.95
315652AC1-086 GEN
Solar/Wind Harmer
30.832
3145796HORNRTN
Solar/Wind Harmer
-0.086
3145796HORNRTN
Solar/Wind Harmer
-0.011
3137643SOCKMAN
Solar/Wind Harmer
-0.107
315607AA1-063A GEN
Solar/Wind Harmer
2.662
3146043SEABORD
Solar/Wind Harmer
-0.026
965291AG1-394 GEN
Solar/Wind Harmer
2.306
316318V4-068
Solar/Wind Harmer
0.646
3145893MURPHYS
Solar/Wind Harmer
-0.07
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145513AHOSKIE
Solar/Wind Harmer
0.225
961941AG1-037 GEN
Solar/Wind Harmer
0.194
3145513AHOSKIE
Solar/Wind Harmer
-0.026
3145683EARLEYS
Solar/Wind Harmer
-0.051
3145683EARLEYS
Solar/Wind Harmer
-0.026
3145683EARLEYS
Solar/Wind Harmer
-0.026
970831AG2-522 GEN
Solar/Wind Harmer
12.905
957871AF2-081 GEN
Solar/Wind Harmer
12.847
319010AE1-072 C
Solar/Wind Harmer
5.194
3146406KITTY HAWK
Solar/Wind Harmer
0.021
3146033SCOT NK
Solar/Wind Harmer
-0.102
313526AB2-022
Solar/Wind Harmer
0.691
316321Z2-027
Solar/Wind Harmer
0.691
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3146396TANGLEW
Solar/Wind Harmer
0.471
3146206CASHIE
Solar/Wind Harmer
-0.026
970601AG2-382 GEN
Solar/Wind Harmer
11.197
315611Z1-036_GEN2
Solar/Wind Harmer
6.312
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
315816AE2-034 GEN
Solar/Wind Harmer
2.065
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
315732AD1-074 GEN1
Solar/Wind Harmer
5.158
315733AD1-074 GEN2
Solar/Wind Harmer
5.158
315735AD1-075 GEN1
Solar/Wind Harmer
2.58
316305AF2-043 C
Solar/Wind Harmer
0.767
3151081ELIZAR1
Adder
20.599
3151091ELIZAR2
Adder
20.241
315835AF2-110_GEN
Solar/Wind Harmer
3.156
3152611GOSPORTB
Adder
2.846
3152621GOSPORTC
Adder
2.415
3152601GOSPORTA
Adder
2.228
316319Z2-044 C
Solar/Wind Harmer
1.375
3145573BETHELC
Solar/Wind Harmer
-0.025
3145573BETHELC
Solar/Wind Harmer
-0.025
316420AA1-050 GEN
Solar/Wind Harmer
2.815
957861AF2-080 GEN
Solar/Wind Harmer
10.782
316005AA1-067
Solar/Wind Harmer
0.498
3145746EVERETS
Solar/Wind Harmer
-0.097
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
970181AG2-120 GEN
Solar/Wind Harmer
3.234
316311AC2-079 GEN
Solar/Wind Harmer
12.392
315833AF1-017_GEN
Solar/Wind Harmer
4.664
316349AD2-085 GEN
Solar/Wind Harmer
2.184
316239AB2-077_GEN
Solar/Wind Harmer
0.715
316238AB2-078_GEN
Solar/Wind Harmer
0.715
316118AC1-105 GEN
Solar/Wind Harmer
1.61
3147173SINAI
Solar/Wind Harmer
-0.023
3147243WELCO
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
4.184
3144303KENBRDG
Solar/Wind Harmer
-0.017
971445AH1-216 GEN
Solar/Wind Harmer
12.623
970683AG2-441 GEN
Solar/Wind Harmer
15.657
970681AG2-440 GEN
Solar/Wind Harmer
12.525
970865AG2-541 GEN
Solar/Wind Harmer
8.054
972265AH1-717 GEN
Adder
12.35
3151201GRAVEL4
Adder
11.578
3151191GRAVEL3
Adder
11.431
3151211GRAVEL5
Adder
11.431
316233AE1-074 FULL
Solar/Wind Helper
0.343
946301AF1-294 GEN
Solar/Wind Harmer
3.153
961791AG1-021 GEN
Solar/Wind Harmer
1.538
315243AE2-183_GT3
50/50
5.551
3151051BRUNSWICKS1
50/50
9.029
3151021BRUNSWICKG1
50/50
4.351
971451AH1-221 GEN
50/50
13.214
3151531CLOVER1
50/50
5.567
3151391GASTONA
50/50
0.66
3151411GASTONB
50/50
0.66
3147043LAWRENC
50/50
2.293
3151261ROARAP2
50/50
0.295
3151601KERR 3
50/50
0.465
3151581KERR 1
50/50
0.166
940641AE2-051 GEN
Solar/Wind Harmer
36.076
970919AG2-571 GEN
Solar/Wind Harmer
11.225
939411AE1-173 GEN
Solar/Wind Harmer
176.638
970087AG2-069 GEN
Solar/Wind Harmer
33.081
957481AF2-042 GEN
Solar/Wind Harmer
96.924
316023GEN1_S
Solar/Wind Harmer
1.997
315693AD1-088 GEN
Solar/Wind Harmer
14.305
960081AF2-299 GEN
Solar/Wind Harmer
3.176
962491AG1-098 GEN
Solar/Wind Harmer
18.84
316011AB1-132 GEN
Solar/Wind Harmer
5.734
962571AG1-106 GEN
Solar/Wind Harmer
3.94
971795AH1-408 GEN
Solar/Wind Harmer
20.458
315687AD1-152 GEN
Solar/Wind Harmer
3.278
3145796HORNRTN
Solar/Wind Harmer
-0.089
3145796HORNRTN
Solar/Wind Harmer
-0.027
316294AC1-161 GEN
Solar/Wind Harmer
8.644
316190AA2-174 GEN
Solar/Wind Harmer
0.325
3145783HORNRTN
Solar/Wind Harmer
-0.026
944591AF1-124 GEN
Solar/Wind Harmer
119.684
3146263WOODLND
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
-0.103
3145893MURPHYS
Solar/Wind Harmer
0.769
3146173TUNIS
Solar/Wind Harmer
-0.026
3145683EARLEYS
Solar/Wind Harmer
-0.026
316129AC1-054 GEN
Solar/Wind Harmer
2.255
3145823KELFORD
Solar/Wind Harmer
-0.026
315722AD1-056 GEN
Solar/Wind Harmer
2.689
316388AE2-253 GEN
Solar/Wind Harmer
1.733
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971065AG2-659 GEN
Solar/Wind Harmer
12.825
3146206CASHIE
Solar/Wind Harmer
-0.026
971547AH1-271 GEN
Solar/Wind Harmer
6.398
316212AC1-099_GEN
Solar/Wind Harmer
2.229
3146516WINFALL
Solar/Wind Harmer
-0.082
3146516WINFALL
Solar/Wind Harmer
-0.025
315800Z1-036_GEN1
Solar/Wind Harmer
6.312
3130156CHOWAN
Solar/Wind Harmer
-0.025
3145663CRESWEL
Solar/Wind Harmer
-0.071
971163AH1-040 GEN
Solar/Wind Harmer
23.925
316246AF1-032 C
Solar/Wind Harmer
0.515
316093AE2-104_GEN
Solar/Wind Harmer
7.34
3145963POPLR C
Solar/Wind Harmer
-0.025
316375AC2-012 GEN
Solar/Wind Harmer
8.687
3150981CHESPKA
Adder
2.789
316174AB2-169 GEN
Solar/Wind Harmer
3.863
3146233WITAKRS
Solar/Wind Harmer
-0.098
3146293MARTNCO
Solar/Wind Harmer
0.153
961671AG1-007 GEN
Solar/Wind Harmer
0.312
3146083TARBORO
Solar/Wind Harmer
-0.025
3145493TOT1
Solar/Wind Harmer
0.731
316494AC1-189 GEN
Solar/Wind Harmer
2.652
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
316359AB2-059 GEN
Solar/Wind Harmer
3.32
316049AB1-081 GEN
Solar/Wind Harmer
2.657
3142053HEARTS
Solar/Wind Harmer
0.289
3145543BTLEBRO
Solar/Wind Harmer
-0.025
3145543BTLEBRO
Solar/Wind Harmer
-0.02
970661AG2-428 GEN
Solar/Wind Harmer
25.261
316237AB2-079_GEN
Solar/Wind Harmer
0.715
316072AD1-144
Solar/Wind Harmer
0.478
970401AG2-262 GEN
Solar/Wind Harmer
1.532
316381AD1-082 GEN
Solar/Wind Harmer
2.151
970659AG2-427 GEN
Solar/Wind Harmer
12.403
316003AC1-222 GEN
Solar/Wind Harmer
2.155
3145336SMITFLD
Solar/Wind Harmer
-0.082
970685AG2-442 GEN
Solar/Wind Harmer
17.535
3144293JTRSVLE
Adder
0.538
3151171GRAVELC
Adder
1.692
3143226MDLTHAN
Solar/Wind Helper
0.326
316045AC1-158 PL2
Solar/Wind Helper
4.217
3143526WINTERP
Solar/Wind Helper
1.167
971563AH1-280 GEN
Solar/Wind Harmer
1.538
970533AG2-339 GEN
50/50
31.019
970531AG2-338 GEN
50/50
12.408
315242AE2-183_GT2
50/50
5.551
315241AE2-183_GT1
50/50
5.517
972185AH1-677 GEN
50/50
20.012
3151041BRUNSWICKG3
50/50
4.351
972187AH1-678 GEN
50/50
9.984
3151361ROSEMG1
50/50
0.866
3151371ROSEMS1
50/50
0.536
3151381ROSEMG2
50/50
0.405
970933AG2-581 GEN
Solar/Wind Harmer
33.195
3144356SAPONY
Solar/Wind Harmer
1.182
970099AG2-077 GEN
Solar/Wind Harmer
38.77
316181AB2-040 GEN
Solar/Wind Harmer
3.83
3142666NORTHAMPTON
Solar/Wind Harmer
-0.027
3142666NORTHAMPTON
Solar/Wind Harmer
-0.027
3142666NORTHAMPTON
Solar/Wind Harmer
-0.027
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3145796HORNRTN
Solar/Wind Harmer
-0.081
3145593CAROLNA
Solar/Wind Harmer
-0.026
3145593CAROLNA
Solar/Wind Harmer
-0.026
966811AG1-552 GEN
Solar/Wind Harmer
2.991
3145593CAROLNA
Solar/Wind Harmer
0.221
316426AA2-053 GEN
Solar/Wind Harmer
2.671
3145783HORNRTN
Solar/Wind Harmer
3.137
3145783HORNRTN
Solar/Wind Harmer
2.509
3145783HORNRTN
Solar/Wind Harmer
0.784
3145783HORNRTN
Solar/Wind Harmer
0.314
3145893MURPHYS
Solar/Wind Harmer
0.723
3145893MURPHYS
Solar/Wind Harmer
-0.047
3146173TUNIS
Solar/Wind Harmer
-0.026
3146173TUNIS
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.102
3145506HICKORY
Solar/Wind Harmer
-0.061
3145506HICKORY
Solar/Wind Harmer
-0.015
316339AD2-160 GEN
Solar/Wind Harmer
1.733
316018AA1-139 ULT2
Solar/Wind Harmer
2.201
316017AA1-139 ULT1
Solar/Wind Harmer
2.079
316185AD1-033 GEN
Solar/Wind Harmer
2.71
3137176SLIGO L2192
Solar/Wind Harmer
-0.102
3146456SLIGO L269
Solar/Wind Harmer
3.033
3130086AYDLETT
Solar/Wind Harmer
-0.102
316274AC1-208 GEN
Solar/Wind Harmer
2.766
3146386ELIZ CT
Solar/Wind Harmer
-0.026
315742AE1-103 GEN
Solar/Wind Harmer
2.672
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
316065AD1-022 GEN
Solar/Wind Harmer
12.78
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
316431W1029_GEN1
Solar/Wind Harmer
4.628
316433W1029_GEN2
Solar/Wind Harmer
4.628
3146376EDENTON
Solar/Wind Harmer
0.758
3146376EDENTON
Solar/Wind Harmer
0.758
3142956BIRDNECK
Solar/Wind Harmer
1.365
316316AC1-027 C
Solar/Wind Harmer
0.78
316036AC1-147 C
Solar/Wind Harmer
0.677
3150991CHESPKB
Adder
2.34
3150991CHESPKB
Adder
2.284
939181AE1-148 GEN
Solar/Wind Harmer
14.051
3145933PARMELE
Solar/Wind Harmer
-0.049
3145933PARMELE
Solar/Wind Harmer
-0.025
961601AG1-000A GEN
Solar/Wind Harmer
9.691
3145493TOT1
Solar/Wind Harmer
0.381
3145453TOT5
Solar/Wind Harmer
0.229
3145603CNETO
Solar/Wind Harmer
0.153
316263AC1-034 GEN
Solar/Wind Harmer
11.543
313527AB2-043 GEN
Solar/Wind Harmer
3.843
970657AG2-426 GEN
Solar/Wind Harmer
7.368
970657AG2-426 GEN
Solar/Wind Harmer
1.541
962561AG1-105 GEN
Solar/Wind Harmer
13.218
964791AG1-342 GEN
Solar/Wind Harmer
5.014
3146843MT LREL
Solar/Wind Harmer
-0.023
3146843MT LREL
Solar/Wind Harmer
-0.023
971741AH1-377 GEN
Solar/Wind Harmer
25.656
316222AC1-221 GEN
Solar/Wind Harmer
2.208
970323AG2-213 GEN
Solar/Wind Harmer
10.577
971775AH1-396 GEN
Solar/Wind Harmer
1.506
316034AC1-036 C
Solar/Wind Harmer
0.392
316236AE1-162_GEN
Solar/Wind Harmer
0.622
970301AG2-198 GEN
Solar/Wind Harmer
10.061
3144293JTRSVLE
Adder
0.538
3144293JTRSVLE
Adder
0.453
316447AC1-158 HLD
Solar/Wind Helper
2.9
3143526WINTERP
Solar/Wind Helper
1.167
958211AF2-115 GEN
Solar/Wind Harmer
1.923
3151031BRUNSWICKG2
50/50
4.351
970413AG2-270 GEN
50/50
24.296
3151391GASTONA
50/50
0.66
3151411GASTONB
50/50
0.66
3151261ROARAP2
50/50
0.288
3151591KERR 2
50/50
0.465
970917AG2-570 GEN
Solar/Wind Harmer
88.674
316365GEN2_N
Solar/Wind Harmer
1.997
316478AD1-087 GEN
Solar/Wind Harmer
2.529
316486AD2-202 GEN
Solar/Wind Harmer
0.741
966621AG1-532 GEN
Solar/Wind Harmer
0.573
313506AB2-031 GEN
Solar/Wind Harmer
2.207
3142666NORTHAMPTON
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.107
3145796HORNRTN
Solar/Wind Harmer
-0.027
3147043LAWRENC
Solar/Wind Harmer
-0.016
315773AC2-141 GEN
Solar/Wind Harmer
11.18
944581AF1-123 GEN
Solar/Wind Harmer
119.255
944601AF1-125 GEN
Solar/Wind Harmer
117.394
3146263WOODLND
Solar/Wind Harmer
-0.026
3156081AA2-088 GEN
Solar/Wind Harmer
8.422
3145893MURPHYS
Solar/Wind Harmer
0.181
3145893MURPHYS
Solar/Wind Harmer
-0.026
957521AF2-046 GEN
Solar/Wind Harmer
20.404
961681AG1-008 GEN
Solar/Wind Harmer
20.404
3146173TUNIS
Solar/Wind Harmer
-0.026
316463AE2-346 GEN
Solar/Wind Harmer
0.418
316140AB2-099
Solar/Wind Harmer
0.174
962331AG1-082 GEN
Solar/Wind Harmer
3.23
316317KELFORD C
Solar/Wind Harmer
1.212
3145823KELFORD
Solar/Wind Harmer
-0.026
3156021HOLLOMANSOL
Solar/Wind Harmer
3.465
315724AD1-057 GEN
Solar/Wind Harmer
1.479
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.13
316320Y1-086
Solar/Wind Harmer
1.502
3146206CASHIE
Solar/Wind Harmer
-0.026
316210AC1-098 GEN
Solar/Wind Harmer
4.012
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
316435W1029_GEN3
Solar/Wind Harmer
4.628
3146376EDENTON
Solar/Wind Harmer
-0.025
315614AA2-178 GEN
Solar/Wind Harmer
2.753
971157AH1-035 GEN
Solar/Wind Harmer
3.188
315737AD1-076 GEN
Solar/Wind Harmer
4.848
3145273HOLLAND
Solar/Wind Harmer
-0.019
3151101ELIZAR3
Adder
20.863
316327AA2-057 GEN
Solar/Wind Harmer
2.54
3145963POPLR C
Solar/Wind Harmer
-0.025
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146233WITAKRS
Solar/Wind Harmer
0.521
3146233WITAKRS
Solar/Wind Harmer
-0.017
3138543CONSLDL
Solar/Wind Harmer
-0.016
3145933PARMELE
Solar/Wind Harmer
-0.025
966801AG1-551 GEN
Solar/Wind Harmer
3.098
961601AG1-000A GEN
Solar/Wind Harmer
9.813
3146073TAR RVR
Solar/Wind Harmer
-0.025
3146083TARBORO
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
3145543BTLEBRO
Solar/Wind Harmer
-0.025
3145543BTLEBRO
Solar/Wind Harmer
-0.025
3144536CHRHLND
Solar/Wind Harmer
-0.004
970661AG2-428 GEN
Solar/Wind Harmer
4.477
316131AB2-060 GEN
Solar/Wind Harmer
2.533
316083AB2-161 GEN
Solar/Wind Harmer
3.807
970659AG2-427 GEN
Solar/Wind Harmer
2.198
316248AF1-058 C
Solar/Wind Harmer
0.703
960061AF2-297 GEN
Solar/Wind Harmer
11.67
964241AG1-285 GEN
Solar/Wind Harmer
17.789
315813AE1-149 C
Solar/Wind Harmer
14.226
316283AC2-100 C
Solar/Wind Harmer
2.044
315785AD2-033 C
Solar/Wind Harmer
4.894
970257AG2-171 GEN
Solar/Wind Harmer
7.933
971683AH1-343 GEN
Solar/Wind Harmer
9.043
959311AF2-222 GEN
Solar/Wind Harmer
21.747
3145336SMITFLD
Solar/Wind Harmer
-0.008
970909AG2-566 GEN
Solar/Wind Harmer
1.91
3144293JTRSVLE
Adder
0.538
3151221GRAVEL6
Adder
11.564
3151171GRAVELC
Adder
2.225
3144216WINCHST
Adder
0.593
3150921YORKTN3
Adder
3.941
316044AC1-158 PL1
Solar/Wind Helper
1.317
316450AC1-158 RIC
Solar/Wind Helper
0.351
CPLELTFEXP_CPLE->PJM
CLTF
14.825
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.72
LAGNLTFEXP_LAGN->PJM
CLTF
9.924
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.751
TVALTFEXP_TVA->PJM
CLTF
4.954
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.902
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.895
MECLTFEXP_MEC->PJM
CLTF
4.674
SIGELTFEXP_SIGE->PJM
CLTF
0.139
NYPJM->LTFIMP_NY
CLTF
2.268
LGEELTFEXP_LGEE->PJM
CLTF
1.668
WECLTFEXP_WEC->PJM
CLTF
0.858

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 208-259_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 208-259_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.32 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4188.82
MW Contribution:23.17
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
5.316
3151051BRUNSWICKS1
50/50
8.646
3151021BRUNSWICKG1
50/50
4.166
971451AH1-221 GEN
50/50
12.653
3151531CLOVER1
50/50
5.309
940641AE2-051 GEN
Solar/Wind Harmer
34.779
939411AE1-173 GEN
Solar/Wind Harmer
172.015
970919AG2-571 GEN
Solar/Wind Harmer
10.745
970087AG2-069 GEN
Solar/Wind Harmer
31.667
957481AF2-042 GEN
Solar/Wind Harmer
92.508
315693AD1-088 GEN
Solar/Wind Harmer
13.627
962491AG1-098 GEN
Solar/Wind Harmer
17.939
316294AC1-161 GEN
Solar/Wind Harmer
8.659
316023GEN1_S
Solar/Wind Harmer
1.804
944591AF1-124 GEN
Solar/Wind Harmer
121.578
316388AE2-253 GEN
Solar/Wind Harmer
1.767
315244AE2-183_ST
50/50
9.192
963041AG1-153 GEN
50/50
8.436
315779AE2-040
50/50
3.649
3151541CLOVER2
50/50
5.284
3151081ELIZAR1
50/50
22.53
941031AE2-094 GEN
Solar/Wind Harmer
70.434
944011AF1-069 GEN
Solar/Wind Harmer
22.069
970673AG2-436 GEN
Solar/Wind Harmer
76.963
970673AG2-436 GEN
Solar/Wind Harmer
38.968
971967AH1-528 GEN
Solar/Wind Harmer
66.91
970085AG2-068 GEN
Solar/Wind Harmer
21.111
970581AG2-369 GEN
Solar/Wind Harmer
18.156
316315AB2-025 C
Solar/Wind Harmer
0.792
315814AE2-033 C
Solar/Wind Harmer
27.227
957871AF2-081 GEN
Solar/Wind Harmer
13.091
319010AE1-072 C
Solar/Wind Harmer
5.287
3146406KITTY HAWK
Solar/Wind Harmer
0.022
3151091ELIZAR2
Adder
20.863
313526AB2-022
Solar/Wind Harmer
0.701
316321Z2-027
Solar/Wind Harmer
0.7
3146396TANGLEW
Solar/Wind Harmer
0.477
316305AF2-043 C
Solar/Wind Harmer
0.782
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3152611GOSPORTB
Adder
2.939
3152621GOSPORTC
Adder
2.494
3152601GOSPORTA
Adder
2.301
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
946281AF1-292 GEN
Solar/Wind Harmer
0.578
315611Z1-036_GEN2
Solar/Wind Harmer
6.337
315835AF2-110_GEN
Solar/Wind Harmer
3.202
316087AB2-174 GEN
Solar/Wind Harmer
3.644
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
315652AC1-086 GEN
Solar/Wind Harmer
28.603
3143316POE
Solar/Wind Harmer
-0.099
315816AE2-034 GEN
Solar/Wind Harmer
2.046
3137643SOCKMAN
Solar/Wind Harmer
-0.1
965291AG1-394 GEN
Solar/Wind Harmer
2.234
3145796HORNRTN
Solar/Wind Harmer
-0.08
3145796HORNRTN
Solar/Wind Harmer
-0.01
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
315732AD1-074 GEN1
Solar/Wind Harmer
5.073
315733AD1-074 GEN2
Solar/Wind Harmer
5.073
315735AD1-075 GEN1
Solar/Wind Harmer
2.537
316318V4-068
Solar/Wind Harmer
0.625
3145893MURPHYS
Solar/Wind Harmer
-0.067
3145893MURPHYS
Solar/Wind Harmer
-0.025
3146043SEABORD
Solar/Wind Harmer
-0.025
315607AA1-063A GEN
Solar/Wind Harmer
2.532
3146206CASHIE
Solar/Wind Harmer
-0.025
970601AG2-382 GEN
Solar/Wind Harmer
10.946
3145513AHOSKIE
Solar/Wind Harmer
0.217
961941AG1-037 GEN
Solar/Wind Harmer
0.187
3145513AHOSKIE
Solar/Wind Harmer
-0.025
316311AC2-079 GEN
Solar/Wind Harmer
12.569
315833AF1-017_GEN
Solar/Wind Harmer
4.73
316349AD2-085 GEN
Solar/Wind Harmer
2.215
3145683EARLEYS
Solar/Wind Harmer
-0.049
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
3146033SCOT NK
Solar/Wind Harmer
-0.097
970831AG2-522 GEN
Solar/Wind Harmer
12.178
316005AA1-067
Solar/Wind Harmer
0.479
3145746EVERETS
Solar/Wind Harmer
-0.094
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
970181AG2-120 GEN
Solar/Wind Harmer
3.109
957861AF2-080 GEN
Solar/Wind Harmer
10.308
316319Z2-044 C
Solar/Wind Harmer
1.301
316420AA1-050 GEN
Solar/Wind Harmer
2.684
3145573BETHELC
Solar/Wind Harmer
-0.023
3145573BETHELC
Solar/Wind Harmer
-0.023
971445AH1-216 GEN
Solar/Wind Harmer
14.288
316239AB2-077_GEN
Solar/Wind Harmer
0.674
316238AB2-078_GEN
Solar/Wind Harmer
0.674
316118AC1-105 GEN
Solar/Wind Harmer
1.527
3147173SINAI
Solar/Wind Harmer
-0.022
3147243WELCO
Solar/Wind Harmer
-0.014
972265AH1-717 GEN
Adder
14.899
3151201GRAVEL4
Adder
13.967
3151191GRAVEL3
Adder
13.79
3151211GRAVEL5
Adder
13.79
971443AH1-215 GEN
Solar/Wind Harmer
3.932
3144303KENBRDG
Solar/Wind Harmer
-0.016
316369SG1_INVT
Solar/Wind Harmer
3.462
316233AE1-074 FULL
Solar/Wind Helper
0.392
970865AG2-541 GEN
Solar/Wind Harmer
2.854
3146456SLIGO L269
Solar/Wind Harmer
-0.026
316375AC2-012 GEN
Solar/Wind Harmer
8.973
3150981CHESPKA
Adder
2.881
316246AF1-032 C
Solar/Wind Harmer
0.525
315687AD1-152 GEN
Solar/Wind Harmer
3.124
960081AF2-299 GEN
Solar/Wind Harmer
2.904
3146516WINFALL
Solar/Wind Harmer
-0.083
3146516WINFALL
Solar/Wind Harmer
-0.026
315800Z1-036_GEN1
Solar/Wind Harmer
6.337
316093AE2-104_GEN
Solar/Wind Harmer
7.449
3130156CHOWAN
Solar/Wind Harmer
-0.025
316011AB1-132 GEN
Solar/Wind Harmer
5.319
962571AG1-106 GEN
Solar/Wind Harmer
3.655
3145663CRESWEL
Solar/Wind Harmer
-0.07
971163AH1-040 GEN
Solar/Wind Harmer
23.71
3145796HORNRTN
Solar/Wind Harmer
-0.082
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
-0.1
3145893MURPHYS
Solar/Wind Harmer
0.744
971795AH1-408 GEN
Solar/Wind Harmer
18.809
3146206CASHIE
Solar/Wind Harmer
-0.025
971547AH1-271 GEN
Solar/Wind Harmer
6.255
3146173TUNIS
Solar/Wind Harmer
-0.025
316190AA2-174 GEN
Solar/Wind Harmer
0.307
3146263WOODLND
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145783HORNRTN
Solar/Wind Harmer
-0.025
3147043LAWRENC
Adder
1.992
316072AD1-144
Solar/Wind Harmer
0.5
3145823KELFORD
Solar/Wind Harmer
-0.025
3145963POPLR C
Solar/Wind Harmer
-0.024
316174AB2-169 GEN
Solar/Wind Harmer
3.756
316212AC1-099_GEN
Solar/Wind Harmer
2.118
316129AC1-054 GEN
Solar/Wind Harmer
2.129
971065AG2-659 GEN
Solar/Wind Harmer
12.112
315722AD1-056 GEN
Solar/Wind Harmer
2.523
970661AG2-428 GEN
Solar/Wind Harmer
25.606
3146293MARTNCO
Solar/Wind Harmer
0.148
316381AD1-082 GEN
Solar/Wind Harmer
2.18
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
970659AG2-427 GEN
Solar/Wind Harmer
12.568
316494AC1-189 GEN
Solar/Wind Harmer
2.535
3146233WITAKRS
Solar/Wind Harmer
-0.093
961671AG1-007 GEN
Solar/Wind Harmer
0.296
3146083TARBORO
Solar/Wind Harmer
-0.023
3145493TOT1
Solar/Wind Harmer
0.696
316359AB2-059 GEN
Solar/Wind Harmer
3.141
316049AB1-081 GEN
Solar/Wind Harmer
2.514
3142053HEARTS
Solar/Wind Harmer
0.274
3145543BTLEBRO
Solar/Wind Harmer
-0.023
3145543BTLEBRO
Solar/Wind Harmer
-0.019
3145336SMITFLD
Solar/Wind Harmer
-0.093
316237AB2-079_GEN
Solar/Wind Harmer
0.674
970401AG2-262 GEN
Solar/Wind Harmer
1.45
3151171GRAVELC
Adder
2.041
316003AC1-222 GEN
Solar/Wind Harmer
2.048
961611AG1-000B GEN
Solar/Wind Harmer
10.222
971647AH1-324 GEN
Solar/Wind Harmer
10.02
3138126ROCKLANDING
Solar/Wind Harmer
0.06
971069AG2-661 GEN
Solar/Wind Harmer
2.982
3144293JTRSVLE
Adder
0.504
3143226MDLTHAN
Solar/Wind Helper
0.345
3143526WINTERP
Solar/Wind Helper
1.336
316045AC1-158 PL2
Solar/Wind Helper
4.18
970533AG2-339 GEN
50/50
29.719
970531AG2-338 GEN
50/50
11.888
315242AE2-183_GT2
50/50
5.316
315241AE2-183_GT1
50/50
5.284
972185AH1-677 GEN
50/50
19.166
3151041BRUNSWICKG3
50/50
4.166
972187AH1-678 GEN
50/50
9.56
970933AG2-581 GEN
Solar/Wind Harmer
31.755
970099AG2-077 GEN
Solar/Wind Harmer
37.003
3144356SAPONY
Solar/Wind Harmer
1.024
316185AD1-033 GEN
Solar/Wind Harmer
2.769
3145506HICKORY
Solar/Wind Harmer
-0.104
3145506HICKORY
Solar/Wind Harmer
-0.063
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.767
316018AA1-139 ULT2
Solar/Wind Harmer
2.243
316017AA1-139 ULT1
Solar/Wind Harmer
2.119
3137176SLIGO L2192
Solar/Wind Harmer
-0.103
3146456SLIGO L269
Solar/Wind Harmer
3.088
3130086AYDLETT
Solar/Wind Harmer
-0.104
3142956BIRDNECK
Solar/Wind Harmer
1.401
316316AC1-027 C
Solar/Wind Harmer
0.801
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316036AC1-147 C
Solar/Wind Harmer
0.7
3150991CHESPKB
Adder
2.417
3150991CHESPKB
Adder
2.359
316431W1029_GEN1
Solar/Wind Harmer
4.679
316433W1029_GEN2
Solar/Wind Harmer
4.679
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146376EDENTON
Solar/Wind Harmer
0.757
3146376EDENTON
Solar/Wind Harmer
0.757
316181AB2-040 GEN
Solar/Wind Harmer
3.547
315742AE1-103 GEN
Solar/Wind Harmer
2.658
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
3145796HORNRTN
Solar/Wind Harmer
-0.075
3145893MURPHYS
Solar/Wind Harmer
0.7
3145893MURPHYS
Solar/Wind Harmer
-0.045
316065AD1-022 GEN
Solar/Wind Harmer
12.521
3145593CAROLNA
Solar/Wind Harmer
-0.025
3145593CAROLNA
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
966811AG1-552 GEN
Solar/Wind Harmer
2.811
3145593CAROLNA
Solar/Wind Harmer
0.208
316426AA2-053 GEN
Solar/Wind Harmer
2.523
3145783HORNRTN
Solar/Wind Harmer
2.952
3145783HORNRTN
Solar/Wind Harmer
2.361
3145783HORNRTN
Solar/Wind Harmer
0.738
3145783HORNRTN
Solar/Wind Harmer
0.295
316274AC1-208 GEN
Solar/Wind Harmer
2.617
3145933PARMELE
Solar/Wind Harmer
-0.048
3145933PARMELE
Solar/Wind Harmer
-0.024
970657AG2-426 GEN
Solar/Wind Harmer
7.467
970657AG2-426 GEN
Solar/Wind Harmer
1.562
939181AE1-148 GEN
Solar/Wind Harmer
13.286
3145493TOT1
Solar/Wind Harmer
0.363
3145453TOT5
Solar/Wind Harmer
0.218
3145603CNETO
Solar/Wind Harmer
0.145
961601AG1-000A GEN
Solar/Wind Harmer
9.163
316263AC1-034 GEN
Solar/Wind Harmer
10.92
316236AE1-162_GEN
Solar/Wind Harmer
0.701
313527AB2-043 GEN
Solar/Wind Harmer
3.62
962561AG1-105 GEN
Solar/Wind Harmer
12.505
3146843MT LREL
Solar/Wind Harmer
-0.022
3146843MT LREL
Solar/Wind Harmer
-0.022
964791AG1-342 GEN
Solar/Wind Harmer
4.747
971741AH1-377 GEN
Solar/Wind Harmer
24.269
316222AC1-221 GEN
Solar/Wind Harmer
2.102
970323AG2-213 GEN
Solar/Wind Harmer
9.94
971775AH1-396 GEN
Solar/Wind Harmer
1.416
316034AC1-036 C
Solar/Wind Harmer
0.368
316033AB2-134 GEN
Solar/Wind Harmer
6.249
315697AD1-025 GEN
Solar/Wind Harmer
3.919
970301AG2-198 GEN
Solar/Wind Harmer
9.489
3144293JTRSVLE
Adder
0.504
3144293JTRSVLE
Adder
0.425
944641AF1-129 GEN
Adder
75.287
3143526WINTERP
Solar/Wind Helper
1.336
316447AC1-158 HLD
Solar/Wind Helper
2.874
3151031BRUNSWICKG2
50/50
4.166
970413AG2-270 GEN
50/50
23.168
3151101ELIZAR3
50/50
22.818
970917AG2-570 GEN
Solar/Wind Harmer
84.887
316478AD1-087 GEN
Solar/Wind Harmer
2.411
316486AD2-202 GEN
Solar/Wind Harmer
0.706
315773AC2-141 GEN
Solar/Wind Harmer
11.199
316365GEN2_N
Solar/Wind Harmer
1.804
944581AF1-123 GEN
Solar/Wind Harmer
121.142
944601AF1-125 GEN
Solar/Wind Harmer
119.252
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.188
316320Y1-086
Solar/Wind Harmer
1.524
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316435W1029_GEN3
Solar/Wind Harmer
4.679
966621AG1-532 GEN
Solar/Wind Harmer
0.524
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146376EDENTON
Solar/Wind Harmer
-0.025
3145273HOLLAND
Solar/Wind Harmer
-0.019
313506AB2-031 GEN
Solar/Wind Harmer
2.044
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
315614AA2-178 GEN
Solar/Wind Harmer
2.729
3156081AA2-088 GEN
Solar/Wind Harmer
8.176
3144536CHRHLND
Solar/Wind Harmer
-0.004
3145796HORNRTN
Solar/Wind Harmer
-0.1
3145796HORNRTN
Solar/Wind Harmer
-0.025
971157AH1-035 GEN
Solar/Wind Harmer
3.139
315737AD1-076 GEN
Solar/Wind Harmer
4.767
3145893MURPHYS
Solar/Wind Harmer
0.175
3145893MURPHYS
Solar/Wind Harmer
-0.025
957521AF2-046 GEN
Solar/Wind Harmer
19.729
961681AG1-008 GEN
Solar/Wind Harmer
19.729
3146206CASHIE
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
316463AE2-346 GEN
Solar/Wind Harmer
0.404
316140AB2-099
Solar/Wind Harmer
0.168
962331AG1-082 GEN
Solar/Wind Harmer
3.117
3156021HOLLOMANSOL
Solar/Wind Harmer
3.359
3146263WOODLND
Solar/Wind Harmer
-0.025
3147043LAWRENC
Solar/Wind Harmer
-0.015
316317KELFORD C
Solar/Wind Harmer
1.163
3145823KELFORD
Solar/Wind Harmer
-0.025
3145963POPLR C
Solar/Wind Harmer
-0.024
316210AC1-098 GEN
Solar/Wind Harmer
3.812
315724AD1-057 GEN
Solar/Wind Harmer
1.388
970661AG2-428 GEN
Solar/Wind Harmer
4.538
3145933PARMELE
Solar/Wind Harmer
-0.024
966801AG1-551 GEN
Solar/Wind Harmer
2.991
316327AA2-057 GEN
Solar/Wind Harmer
2.405
316083AB2-161 GEN
Solar/Wind Harmer
3.858
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
970659AG2-427 GEN
Solar/Wind Harmer
2.227
3146233WITAKRS
Solar/Wind Harmer
0.493
3146233WITAKRS
Solar/Wind Harmer
-0.016
3138543CONSLDL
Solar/Wind Harmer
-0.015
3146073TAR RVR
Solar/Wind Harmer
-0.023
3146083TARBORO
Solar/Wind Harmer
-0.023
961601AG1-000A GEN
Solar/Wind Harmer
9.279
3145543BTLEBRO
Solar/Wind Harmer
-0.023
3145543BTLEBRO
Solar/Wind Harmer
-0.023
3145336SMITFLD
Solar/Wind Harmer
-0.009
315813AE1-149 C
Solar/Wind Harmer
14.408
316248AF1-058 C
Solar/Wind Harmer
0.668
960061AF2-297 GEN
Solar/Wind Harmer
11.09
316131AB2-060 GEN
Solar/Wind Harmer
2.386
3151221GRAVEL6
Adder
13.951
3151171GRAVELC
Adder
2.684
964241AG1-285 GEN
Solar/Wind Harmer
16.743
315839AE2-212 C
Solar/Wind Harmer
0.632
961611AG1-000B GEN
Solar/Wind Harmer
4.362
316283AC2-100 C
Solar/Wind Harmer
1.947
315785AD2-033 C
Solar/Wind Harmer
4.601
971683AH1-343 GEN
Solar/Wind Harmer
8.591
970257AG2-171 GEN
Solar/Wind Harmer
7.455
3144216WINCHST
Adder
0.658
959311AF2-222 GEN
Solar/Wind Harmer
20.43
3150921YORKTN3
Adder
4.314
970909AG2-566 GEN
Solar/Wind Harmer
1.802
315778AD1-151 GEN
Solar/Wind Harmer
16.326
3144293JTRSVLE
Adder
0.504
316044AC1-158 PL1
Solar/Wind Helper
1.306
316450AC1-158 RIC
Solar/Wind Helper
0.348
CPLELTFEXP_CPLE->PJM
CLTF
14.126
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.754
LAGNLTFEXP_LAGN->PJM
CLTF
9.388
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.224
TVALTFEXP_TVA->PJM
CLTF
4.687
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.772
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.963
MECLTFEXP_MEC->PJM
CLTF
4.378
SIGELTFEXP_SIGE->PJM
CLTF
0.13
NYPJM->LTFIMP_NY
CLTF
2.225
LGEELTFEXP_LGEE->PJM
CLTF
1.558
WECLTFEXP_WEC->PJM
CLTF
0.8

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.09 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:3384.28
MW Contribution:22.56
Bus #Bus NameTypeMW Contribution
970533AG2-339 GEN
50/50
28.925
970531AG2-338 GEN
50/50
11.57
315242AE2-183_GT2
50/50
5.174
315241AE2-183_GT1
50/50
5.142
972185AH1-677 GEN
50/50
18.653
3151041BRUNSWICKG3
50/50
4.054
972187AH1-678 GEN
50/50
9.304
970933AG2-581 GEN
Solar/Wind Harmer
23.481
970099AG2-077 GEN
Solar/Wind Harmer
27.375
3144356SAPONY
Solar/Wind Harmer
2.028
316185AD1-033 GEN
Solar/Wind Harmer
0.006
3145506HICKORY
Solar/Wind Harmer
0.885
3145506HICKORY
Solar/Wind Harmer
0.531
3145506HICKORY
Solar/Wind Harmer
0.133
316339AD2-160 GEN
Solar/Wind Harmer
0.358
316018AA1-139 ULT2
Solar/Wind Harmer
0.005
316017AA1-139 ULT1
Solar/Wind Harmer
0.123
3137176SLIGO L2192
Solar/Wind Harmer
0.878
3146456SLIGO L269
Solar/Wind Harmer
3.903
3130086AYDLETT
Solar/Wind Harmer
0.881
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.211
3146386ELIZ CT
Solar/Wind Harmer
0.219
316036AC1-147 C
Solar/Wind Harmer
0.04
3150991CHESPKB
Adder
2.282
3150991CHESPKB
Adder
2.228
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.217
3146516WINFALL
Solar/Wind Harmer
0.217
3146516WINFALL
Solar/Wind Harmer
0.217
3146626S HERTFORD
Solar/Wind Harmer
0.217
3146626S HERTFORD
Solar/Wind Harmer
0.217
3146376EDENTON
Solar/Wind Harmer
0.957
3146376EDENTON
Solar/Wind Harmer
0.957
316181AB2-040 GEN
Solar/Wind Harmer
0.311
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.128
315742AE1-103 GEN
Solar/Wind Harmer
0.002
3145796HORNRTN
Solar/Wind Harmer
0.634
316065AD1-022 GEN
Solar/Wind Harmer
9.736
3145893MURPHYS
Solar/Wind Harmer
1.414
3145893MURPHYS
Solar/Wind Harmer
0.38
3145593CAROLNA
Solar/Wind Harmer
0.211
3145593CAROLNA
Solar/Wind Harmer
0.211
966811AG1-552 GEN
Solar/Wind Harmer
2.291
3145593CAROLNA
Solar/Wind Harmer
0.263
316426AA2-053 GEN
Solar/Wind Harmer
0.712
3146173TUNIS
Solar/Wind Harmer
0.211
3146173TUNIS
Solar/Wind Harmer
0.211
3145783HORNRTN
Solar/Wind Harmer
3.739
3145783HORNRTN
Solar/Wind Harmer
2.991
3145783HORNRTN
Solar/Wind Harmer
0.935
3145783HORNRTN
Solar/Wind Harmer
0.374
316274AC1-208 GEN
Solar/Wind Harmer
1.066
939181AE1-148 GEN
Solar/Wind Harmer
9.756
3145933PARMELE
Solar/Wind Harmer
0.406
3145933PARMELE
Solar/Wind Harmer
0.203
3145493TOT1
Solar/Wind Harmer
0.462
3145453TOT5
Solar/Wind Harmer
0.277
3145603CNETO
Solar/Wind Harmer
0.185
961601AG1-000A GEN
Solar/Wind Harmer
3.522
316263AC1-034 GEN
Solar/Wind Harmer
7.526
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
9.215
3146843MT LREL
Solar/Wind Harmer
0.192
3146843MT LREL
Solar/Wind Harmer
0.192
964791AG1-342 GEN
Solar/Wind Harmer
3.686
970657AG2-426 GEN
Solar/Wind Harmer
6.636
970657AG2-426 GEN
Solar/Wind Harmer
1.391
316236AE1-162_GEN
Solar/Wind Harmer
0.002
971741AH1-377 GEN
Solar/Wind Harmer
18.103
316222AC1-221 GEN
Solar/Wind Harmer
0.745
970323AG2-213 GEN
Solar/Wind Harmer
7.354
971775AH1-396 GEN
Solar/Wind Harmer
0.276
316034AC1-036 C
Solar/Wind Harmer
0.013
970301AG2-198 GEN
Solar/Wind Harmer
7.099
958211AF2-115 GEN
Solar/Wind Harmer
1.863
963191AG1-168 GEN
Solar/Wind Harmer
0.621
3144293JTRSVLE
Adder
0.494
3144293JTRSVLE
Adder
0.416
3147133PAMPLIN
Solar/Wind Harmer
0.149
3147133PAMPLIN
Solar/Wind Harmer
0.119
316033AB2-134 GEN
Solar/Wind Harmer
0.008
315697AD1-025 GEN
Solar/Wind Harmer
0.161
942751AE2-291 GEN
Solar/Wind Harmer
7.176
316240AF1-291 C
Solar/Wind Harmer
0.001
316447AC1-158 HLD
Solar/Wind Helper
2.812
315243AE2-183_GT3
50/50
5.174
3151051BRUNSWICKS1
50/50
8.414
3151021BRUNSWICKG1
50/50
4.054
971451AH1-221 GEN
50/50
12.314
3151531CLOVER1
50/50
5.17
940641AE2-051 GEN
Solar/Wind Harmer
25.663
939411AE1-173 GEN
Solar/Wind Harmer
126.366
970919AG2-571 GEN
Solar/Wind Harmer
10.453
970087AG2-069 GEN
Solar/Wind Harmer
23.397
957481AF2-042 GEN
Solar/Wind Harmer
68.436
315693AD1-088 GEN
Solar/Wind Harmer
11.355
962491AG1-098 GEN
Solar/Wind Harmer
13.293
316294AC1-161 GEN
Solar/Wind Harmer
3.96
944591AF1-124 GEN
Solar/Wind Harmer
50.934
315687AD1-152 GEN
Solar/Wind Harmer
0.007
316023GEN1_S
Solar/Wind Harmer
0.501
316388AE2-253 GEN
Solar/Wind Harmer
0.692
3146456SLIGO L269
Solar/Wind Harmer
0.22
316246AF1-032 C
Solar/Wind Harmer
0.098
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.721
3146516WINFALL
Solar/Wind Harmer
0.705
3146516WINFALL
Solar/Wind Harmer
0.217
960081AF2-299 GEN
Solar/Wind Harmer
2.083
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.215
316093AE2-104_GEN
Solar/Wind Harmer
3.601
316011AB1-132 GEN
Solar/Wind Harmer
3.888
962571AG1-106 GEN
Solar/Wind Harmer
3.042
3145663CRESWEL
Solar/Wind Harmer
0.597
971163AH1-040 GEN
Solar/Wind Harmer
17.076
971795AH1-408 GEN
Solar/Wind Harmer
14.122
3145796HORNRTN
Solar/Wind Harmer
0.698
3145796HORNRTN
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
0.845
3145893MURPHYS
Solar/Wind Harmer
0.939
3146206CASHIE
Solar/Wind Harmer
0.211
971547AH1-271 GEN
Solar/Wind Harmer
4.506
316190AA2-174 GEN
Solar/Wind Harmer
0
3146173TUNIS
Solar/Wind Harmer
0.211
3146263WOODLND
Solar/Wind Harmer
0.21
3145783HORNRTN
Solar/Wind Harmer
0.21
3145683EARLEYS
Solar/Wind Harmer
0.21
3147043LAWRENC
Adder
1.895
3145823KELFORD
Solar/Wind Harmer
0.208
316129AC1-054 GEN
Solar/Wind Harmer
0.781
971065AG2-659 GEN
Solar/Wind Harmer
8.844
3145963POPLR C
Solar/Wind Harmer
0.207
316072AD1-144
Solar/Wind Harmer
0.075
316174AB2-169 GEN
Solar/Wind Harmer
0.005
316212AC1-099_GEN
Solar/Wind Harmer
1.064
315722AD1-056 GEN
Solar/Wind Harmer
1.293
3146293MARTNCO
Solar/Wind Harmer
0.188
3145746EVERETS
Solar/Wind Harmer
0.201
3145746EVERETS
Solar/Wind Harmer
0.201
3146233WITAKRS
Solar/Wind Harmer
0.796
316494AC1-189 GEN
Solar/Wind Harmer
0.676
961671AG1-007 GEN
Solar/Wind Harmer
0.03
3146083TARBORO
Solar/Wind Harmer
0.199
3145493TOT1
Solar/Wind Harmer
0.885
316359AB2-059 GEN
Solar/Wind Harmer
0.711
316049AB1-081 GEN
Solar/Wind Harmer
1.133
3145543BTLEBRO
Solar/Wind Harmer
0.198
3145543BTLEBRO
Solar/Wind Harmer
0.158
3142053HEARTS
Solar/Wind Harmer
0.349
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
19.138
970401AG2-262 GEN
Solar/Wind Harmer
1.126
3145336SMITFLD
Solar/Wind Harmer
0.755
316381AD1-082 GEN
Solar/Wind Harmer
0.196
970659AG2-427 GEN
Solar/Wind Harmer
8.999
316003AC1-222 GEN
Solar/Wind Harmer
0.005
3151171GRAVELC
Adder
1.816
970685AG2-442 GEN
Solar/Wind Harmer
12.211
3138126ROCKLANDING
Solar/Wind Harmer
0.074
961611AG1-000B GEN
Solar/Wind Harmer
8.399
963171AG1-166 GEN
Solar/Wind Harmer
0.828
971563AH1-280 GEN
Solar/Wind Harmer
1.656
3144293JTRSVLE
Adder
0.494
971647AH1-324 GEN
Solar/Wind Harmer
6.473
971317AH1-138 GEN
Solar/Wind Harmer
1.095
971069AG2-661 GEN
Solar/Wind Harmer
2.431
316159AE1-175 C
Solar/Wind Harmer
0.112
315671AE2-027_GEN
Solar/Wind Harmer
8.259
316458AB2-190 GEN2
Solar/Wind Harmer
0.682
970129AG2-093 GEN
Solar/Wind Harmer
3.572
3146926FARMVIL
Solar/Wind Harmer
0.069
3143226MDLTHAN
Solar/Wind Helper
0.299
315244AE2-183_ST
50/50
8.945
963041AG1-153 GEN
50/50
8.209
315779AE2-040
50/50
3.384
3151541CLOVER2
50/50
5.145
3151081ELIZAR1
50/50
21.293
941031AE2-094 GEN
Solar/Wind Harmer
59.933
944011AF1-069 GEN
Solar/Wind Harmer
19.582
970673AG2-436 GEN
Solar/Wind Harmer
67.697
970673AG2-436 GEN
Solar/Wind Harmer
45.131
971967AH1-528 GEN
Solar/Wind Harmer
49.335
970085AG2-068 GEN
Solar/Wind Harmer
15.598
970581AG2-369 GEN
Solar/Wind Harmer
13.414
316315AB2-025 C
Solar/Wind Harmer
0.196
315814AE2-033 C
Solar/Wind Harmer
19.104
957871AF2-081 GEN
Solar/Wind Harmer
10.995
319010AE1-072 C
Solar/Wind Harmer
1.11
3146406KITTY HAWK
Solar/Wind Harmer
0.027
313526AB2-022
Solar/Wind Harmer
0.119
3151091ELIZAR2
Adder
19.718
316321Z2-027
Solar/Wind Harmer
0.041
3146396TANGLEW
Solar/Wind Harmer
0.603
3145176PASQUOTANK
Solar/Wind Harmer
0.136
316305AF2-043 C
Solar/Wind Harmer
0.002
3146486SUNBURY
Solar/Wind Harmer
0.218
3146486SUNBURY
Solar/Wind Harmer
0.218
3152611GOSPORTB
Adder
2.775
3152621GOSPORTC
Adder
2.355
3152601GOSPORTA
Adder
2.173
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.215
3130156CHOWAN
Solar/Wind Harmer
0.215
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315835AF2-110_GEN
Solar/Wind Harmer
1.469
315652AC1-086 GEN
Solar/Wind Harmer
23.522
315816AE2-034 GEN
Solar/Wind Harmer
0.916
3137643SOCKMAN
Solar/Wind Harmer
0.849
3130546PLYMOUTH
Solar/Wind Harmer
0.212
965291AG1-394 GEN
Solar/Wind Harmer
0.942
315732AD1-074 GEN1
Solar/Wind Harmer
1.217
315733AD1-074 GEN2
Solar/Wind Harmer
1.217
315735AD1-075 GEN1
Solar/Wind Harmer
0.609
3145796HORNRTN
Solar/Wind Harmer
0.677
3145796HORNRTN
Solar/Wind Harmer
0.085
3146043SEABORD
Solar/Wind Harmer
0.211
315607AA1-063A GEN
Solar/Wind Harmer
0.432
3145893MURPHYS
Solar/Wind Harmer
0.57
3145893MURPHYS
Solar/Wind Harmer
0.211
3146206CASHIE
Solar/Wind Harmer
0.211
970601AG2-382 GEN
Solar/Wind Harmer
7.886
3145513AHOSKIE
Solar/Wind Harmer
0.44
3145513AHOSKIE
Solar/Wind Harmer
0.21
3145683EARLEYS
Solar/Wind Harmer
0.42
3145683EARLEYS
Solar/Wind Harmer
0.21
3145683EARLEYS
Solar/Wind Harmer
0.21
970831AG2-522 GEN
Solar/Wind Harmer
8.873
3146033SCOT NK
Solar/Wind Harmer
0.827
316311AC2-079 GEN
Solar/Wind Harmer
5.862
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.14
316005AA1-067
Solar/Wind Harmer
0.216
3145746EVERETS
Solar/Wind Harmer
0.8
3145746EVERETS
Solar/Wind Harmer
0.201
3145746EVERETS
Solar/Wind Harmer
0.201
3145746EVERETS
Solar/Wind Harmer
0.201
970181AG2-120 GEN
Solar/Wind Harmer
2.501
316319Z2-044 C
Solar/Wind Harmer
0
957861AF2-080 GEN
Solar/Wind Harmer
8.623
316420AA1-050 GEN
Solar/Wind Harmer
0.007
3145573BETHELC
Solar/Wind Harmer
0.199
3145573BETHELC
Solar/Wind Harmer
0.199
3143316POE
Solar/Wind Harmer
0.769
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.495
3147173SINAI
Solar/Wind Harmer
0.192
3147243WELCO
Solar/Wind Harmer
0.12
971445AH1-216 GEN
Solar/Wind Harmer
13.184
971443AH1-215 GEN
Solar/Wind Harmer
2.909
3144303KENBRDG
Solar/Wind Harmer
0.138
972265AH1-717 GEN
Adder
13.258
3151201GRAVEL4
Adder
12.428
3151191GRAVEL3
Adder
12.271
3151211GRAVEL5
Adder
12.271
970683AG2-441 GEN
Solar/Wind Harmer
10.903
970681AG2-440 GEN
Solar/Wind Harmer
8.722
970865AG2-541 GEN
Solar/Wind Harmer
5.652
946301AF1-294 GEN
Solar/Wind Harmer
3.063
961791AG1-021 GEN
Solar/Wind Harmer
1.49
315657AE1-056 GEN
Solar/Wind Harmer
5.154
316123AC1-075 GEN
Solar/Wind Harmer
0.197
970165AG2-112 GEN
Solar/Wind Harmer
1.167
970163AG2-111 GEN
Solar/Wind Harmer
1.113
316369SG1_INVT
Solar/Wind Harmer
0.005
3138283WHITEMARSH
Solar/Wind Harmer
0.03
316132AB2-190 GEN1
Solar/Wind Harmer
0.682
316045AC1-158 PL2
Solar/Wind Helper
4.09
3151031BRUNSWICKG2
50/50
4.054
970413AG2-270 GEN
50/50
22.561
3151101ELIZAR3
50/50
21.566
970917AG2-570 GEN
Solar/Wind Harmer
26.133
316478AD1-087 GEN
Solar/Wind Harmer
0.842
316486AD2-202 GEN
Solar/Wind Harmer
0.247
315773AC2-141 GEN
Solar/Wind Harmer
8.348
944581AF1-123 GEN
Solar/Wind Harmer
50.754
944601AF1-125 GEN
Solar/Wind Harmer
49.972
316365GEN2_N
Solar/Wind Harmer
0.501
3146456SLIGO L269
Solar/Wind Harmer
0.22
971153AH1-033 GEN
Solar/Wind Harmer
2.55
316320Y1-086
Solar/Wind Harmer
0.001
3144873MCLAUGH
Solar/Wind Harmer
0.005
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.217
3146626S HERTFORD
Solar/Wind Harmer
0.217
3146376EDENTON
Solar/Wind Harmer
0.215
313506AB2-031 GEN
Solar/Wind Harmer
0.662
3145273HOLLAND
Solar/Wind Harmer
0.16
315614AA2-178 GEN
Solar/Wind Harmer
1.222
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
971157AH1-035 GEN
Solar/Wind Harmer
2.545
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
315737AD1-076 GEN
Solar/Wind Harmer
2.725
3145796HORNRTN
Solar/Wind Harmer
0.846
3145796HORNRTN
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
0.354
3145893MURPHYS
Solar/Wind Harmer
0.211
3146206CASHIE
Solar/Wind Harmer
0.211
957521AF2-046 GEN
Solar/Wind Harmer
15.712
961681AG1-008 GEN
Solar/Wind Harmer
15.712
3146173TUNIS
Solar/Wind Harmer
0.211
3156021HOLLOMANSOL
Solar/Wind Harmer
0.955
316463AE2-346 GEN
Solar/Wind Harmer
0.181
316140AB2-099
Solar/Wind Harmer
0.075
3146263WOODLND
Solar/Wind Harmer
0.21
962331AG1-082 GEN
Solar/Wind Harmer
2.245
3144536CHRHLND
Solar/Wind Harmer
0.031
3147043LAWRENC
Solar/Wind Harmer
0.126
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.208
3145963POPLR C
Solar/Wind Harmer
0.207
316210AC1-098 GEN
Solar/Wind Harmer
1.908
315724AD1-057 GEN
Solar/Wind Harmer
0.766
3145933PARMELE
Solar/Wind Harmer
0.203
966801AG1-551 GEN
Solar/Wind Harmer
2.363
316327AA2-057 GEN
Solar/Wind Harmer
0.305
3145746EVERETS
Solar/Wind Harmer
0.201
3145746EVERETS
Solar/Wind Harmer
0.201
3146233WITAKRS
Solar/Wind Harmer
1.004
3146233WITAKRS
Solar/Wind Harmer
0.136
3138543CONSLDL
Solar/Wind Harmer
0.132
3146073TAR RVR
Solar/Wind Harmer
0.199
3146083TARBORO
Solar/Wind Harmer
0.199
961601AG1-000A GEN
Solar/Wind Harmer
14.088
3145543BTLEBRO
Solar/Wind Harmer
0.198
3145543BTLEBRO
Solar/Wind Harmer
0.198
971623AH1-311 GEN
Solar/Wind Harmer
0.396
970661AG2-428 GEN
Solar/Wind Harmer
4.071
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
8.184
316131AB2-060 GEN
Solar/Wind Harmer
0.6
3145336SMITFLD
Solar/Wind Harmer
0.076
316083AB2-161 GEN
Solar/Wind Harmer
0.003
970659AG2-427 GEN
Solar/Wind Harmer
1.969
964241AG1-285 GEN
Solar/Wind Harmer
12.343
316283AC2-100 C
Solar/Wind Harmer
0.349
315813AE1-149 C
Solar/Wind Harmer
9.464
315785AD2-033 C
Solar/Wind Harmer
1.43
971683AH1-343 GEN
Solar/Wind Harmer
6.344
970257AG2-171 GEN
Solar/Wind Harmer
5.516
3151221GRAVEL6
Adder
12.414
3151171GRAVELC
Adder
2.388
959311AF2-222 GEN
Solar/Wind Harmer
15.096
970909AG2-566 GEN
Solar/Wind Harmer
1.775
3144216WINCHST
Adder
0.609
961611AG1-000B GEN
Solar/Wind Harmer
4.271
3150921YORKTN3
Adder
4.021
963181AG1-167 GEN
Solar/Wind Harmer
0.621
3144293JTRSVLE
Adder
0.494
3147133PAMPLIN
Solar/Wind Harmer
0.469
971193AH1-056 GEN
Solar/Wind Harmer
9.098
315839AE2-212 C
Solar/Wind Harmer
0.001
965281AG1-393 GEN
Solar/Wind Harmer
1.464
315778AD1-151 GEN
Solar/Wind Harmer
10.941
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
970129AG2-093 GEN
Solar/Wind Harmer
7.591
3146926FARMVIL
Solar/Wind Harmer
0.069
316044AC1-158 PL1
Solar/Wind Helper
1.278
316450AC1-158 RIC
Solar/Wind Helper
0.341
CPLELTFEXP_CPLE->PJM
CLTF
13.67
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.627
LAGNLTFEXP_LAGN->PJM
CLTF
9.15
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.306
TVALTFEXP_TVA->PJM
CLTF
4.569
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.362
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.575
MECLTFEXP_MEC->PJM
CLTF
4.294
SIGELTFEXP_SIGE->PJM
CLTF
0.128
NYPJM->LTFIMP_NY
CLTF
2.148
LGEELTFEXP_LGEE->PJM
CLTF
1.532
WECLTFEXP_WEC->PJM
CLTF
0.787

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.67 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4124.05
MW Contribution:23.74
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
5.365
3151051BRUNSWICKS1
50/50
8.74
3151021BRUNSWICKG1
50/50
4.211
971451AH1-221 GEN
50/50
12.79
3151531CLOVER1
50/50
5.439
3151391GASTONA
50/50
0.617
3151411GASTONB
50/50
0.617
940641AE2-051 GEN
Solar/Wind Harmer
34.798
970919AG2-571 GEN
Solar/Wind Harmer
10.923
970087AG2-069 GEN
Solar/Wind Harmer
32.213
939411AE1-173 GEN
Solar/Wind Harmer
171.7
957481AF2-042 GEN
Solar/Wind Harmer
94.326
315693AD1-088 GEN
Solar/Wind Harmer
13.943
962491AG1-098 GEN
Solar/Wind Harmer
18.368
315687AD1-152 GEN
Solar/Wind Harmer
3.227
316294AC1-161 GEN
Solar/Wind Harmer
8.621
316023GEN1_S
Solar/Wind Harmer
1.79
944591AF1-124 GEN
Solar/Wind Harmer
120.234
316388AE2-253 GEN
Solar/Wind Harmer
1.745
315244AE2-183_ST
50/50
9.276
963041AG1-153 GEN
50/50
8.526
3151541CLOVER2
50/50
5.413
315779AE2-040
50/50
3.53
941031AE2-094 GEN
Solar/Wind Harmer
70.83
944011AF1-069 GEN
Solar/Wind Harmer
22.193
970673AG2-436 GEN
Solar/Wind Harmer
77.572
970673AG2-436 GEN
Solar/Wind Harmer
39.277
971967AH1-528 GEN
Solar/Wind Harmer
67.508
970085AG2-068 GEN
Solar/Wind Harmer
21.475
970581AG2-369 GEN
Solar/Wind Harmer
18.469
316315AB2-025 C
Solar/Wind Harmer
0.766
315814AE2-033 C
Solar/Wind Harmer
26.373
957871AF2-081 GEN
Solar/Wind Harmer
12.934
319010AE1-072 C
Solar/Wind Harmer
5.226
3146406KITTY HAWK
Solar/Wind Harmer
0.021
946281AF1-292 GEN
Solar/Wind Harmer
0.578
313526AB2-022
Solar/Wind Harmer
0.694
316321Z2-027
Solar/Wind Harmer
0.693
3146396TANGLEW
Solar/Wind Harmer
0.473
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
316087AB2-174 GEN
Solar/Wind Harmer
3.659
315652AC1-086 GEN
Solar/Wind Harmer
28.827
3151081ELIZAR1
Adder
20.887
3151091ELIZAR2
Adder
20.524
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
316305AF2-043 C
Solar/Wind Harmer
0.771
315611Z1-036_GEN2
Solar/Wind Harmer
6.305
3152611GOSPORTB
Adder
2.889
3152621GOSPORTC
Adder
2.452
3152601GOSPORTA
Adder
2.262
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.081
3145796HORNRTN
Solar/Wind Harmer
-0.01
3137643SOCKMAN
Solar/Wind Harmer
-0.101
315816AE2-034 GEN
Solar/Wind Harmer
2.05
315607AA1-063A GEN
Solar/Wind Harmer
2.551
3146043SEABORD
Solar/Wind Harmer
-0.025
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
315732AD1-074 GEN1
Solar/Wind Harmer
5.102
315733AD1-074 GEN2
Solar/Wind Harmer
5.102
315735AD1-075 GEN1
Solar/Wind Harmer
2.552
965291AG1-394 GEN
Solar/Wind Harmer
2.237
3146206CASHIE
Solar/Wind Harmer
-0.025
970601AG2-382 GEN
Solar/Wind Harmer
11.025
316318V4-068
Solar/Wind Harmer
0.628
3145893MURPHYS
Solar/Wind Harmer
-0.068
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145513AHOSKIE
Solar/Wind Harmer
0.219
961941AG1-037 GEN
Solar/Wind Harmer
0.189
3145513AHOSKIE
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.05
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
315835AF2-110_GEN
Solar/Wind Harmer
3.142
3146033SCOT NK
Solar/Wind Harmer
-0.099
970831AG2-522 GEN
Solar/Wind Harmer
12.462
316005AA1-067
Solar/Wind Harmer
0.494
3145746EVERETS
Solar/Wind Harmer
-0.097
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
970181AG2-120 GEN
Solar/Wind Harmer
3.208
316319Z2-044 C
Solar/Wind Harmer
1.348
957861AF2-080 GEN
Solar/Wind Harmer
10.667
316420AA1-050 GEN
Solar/Wind Harmer
2.781
3145573BETHELC
Solar/Wind Harmer
-0.024
3145573BETHELC
Solar/Wind Harmer
-0.024
316311AC2-079 GEN
Solar/Wind Harmer
12.096
315833AF1-017_GEN
Solar/Wind Harmer
4.55
316349AD2-085 GEN
Solar/Wind Harmer
2.131
316239AB2-077_GEN
Solar/Wind Harmer
0.695
316238AB2-078_GEN
Solar/Wind Harmer
0.695
3147173SINAI
Solar/Wind Harmer
-0.023
3147243WELCO
Solar/Wind Harmer
-0.014
316118AC1-105 GEN
Solar/Wind Harmer
1.583
3143316POE
Solar/Wind Harmer
-0.09
971445AH1-216 GEN
Solar/Wind Harmer
13.611
971443AH1-215 GEN
Solar/Wind Harmer
4.082
3144303KENBRDG
Solar/Wind Harmer
-0.016
972265AH1-717 GEN
Adder
13.901
3151201GRAVEL4
Adder
13.031
3151191GRAVEL3
Adder
12.866
3151211GRAVEL5
Adder
12.866
970683AG2-441 GEN
Solar/Wind Harmer
15.31
970681AG2-440 GEN
Solar/Wind Harmer
12.248
970865AG2-541 GEN
Solar/Wind Harmer
7.877
270455AD2-022 GEN
Solar/Wind Harmer
3.414
270457AD2-023 GEN
Solar/Wind Harmer
1.731
3146456SLIGO L269
Solar/Wind Harmer
-0.026
960081AF2-299 GEN
Solar/Wind Harmer
2.906
316011AB1-132 GEN
Solar/Wind Harmer
5.361
962571AG1-106 GEN
Solar/Wind Harmer
3.683
3146516WINFALL
Solar/Wind Harmer
-0.082
3146516WINFALL
Solar/Wind Harmer
-0.026
316246AF1-032 C
Solar/Wind Harmer
0.518
315800Z1-036_GEN1
Solar/Wind Harmer
6.305
316375AC2-012 GEN
Solar/Wind Harmer
8.82
3150981CHESPKA
Adder
2.832
3130156CHOWAN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.083
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145663CRESWEL
Solar/Wind Harmer
-0.071
971163AH1-040 GEN
Solar/Wind Harmer
23.751
316190AA2-174 GEN
Solar/Wind Harmer
0.31
971795AH1-408 GEN
Solar/Wind Harmer
18.929
3145783HORNRTN
Solar/Wind Harmer
-0.025
3146206CASHIE
Solar/Wind Harmer
-0.025
971547AH1-271 GEN
Solar/Wind Harmer
6.3
3145893MURPHYS
Solar/Wind Harmer
-0.1
3145893MURPHYS
Solar/Wind Harmer
0.747
3146263WOODLND
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
316093AE2-104_GEN
Solar/Wind Harmer
7.308
3145823KELFORD
Solar/Wind Harmer
-0.025
3147043LAWRENC
Adder
2.01
316129AC1-054 GEN
Solar/Wind Harmer
2.182
3145963POPLR C
Solar/Wind Harmer
-0.025
971065AG2-659 GEN
Solar/Wind Harmer
12.425
316212AC1-099_GEN
Solar/Wind Harmer
2.165
316174AB2-169 GEN
Solar/Wind Harmer
3.827
315722AD1-056 GEN
Solar/Wind Harmer
2.593
3146293MARTNCO
Solar/Wind Harmer
0.152
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
3146233WITAKRS
Solar/Wind Harmer
-0.097
316494AC1-189 GEN
Solar/Wind Harmer
2.623
961671AG1-007 GEN
Solar/Wind Harmer
0.308
3146083TARBORO
Solar/Wind Harmer
-0.024
3145493TOT1
Solar/Wind Harmer
0.722
316359AB2-059 GEN
Solar/Wind Harmer
3.27
316049AB1-081 GEN
Solar/Wind Harmer
2.617
3142053HEARTS
Solar/Wind Harmer
0.285
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.019
316072AD1-144
Solar/Wind Harmer
0.489
316237AB2-079_GEN
Solar/Wind Harmer
0.695
970401AG2-262 GEN
Solar/Wind Harmer
1.502
970661AG2-428 GEN
Solar/Wind Harmer
24.038
3145336SMITFLD
Solar/Wind Harmer
-0.088
316381AD1-082 GEN
Solar/Wind Harmer
2.025
970659AG2-427 GEN
Solar/Wind Harmer
11.632
316003AC1-222 GEN
Solar/Wind Harmer
2.12
3151171GRAVELC
Adder
1.904
970685AG2-442 GEN
Solar/Wind Harmer
17.147
3138126ROCKLANDING
Solar/Wind Harmer
0.058
3144293JTRSVLE
Adder
0.527
3143226MDLTHAN
Solar/Wind Helper
0.287
316045AC1-158 PL2
Solar/Wind Helper
3.977
961611AG1-000B GEN
Solar/Wind Harmer
2.084
970533AG2-339 GEN
50/50
29.886
970531AG2-338 GEN
50/50
11.954
315242AE2-183_GT2
50/50
5.365
315241AE2-183_GT1
50/50
5.332
972185AH1-677 GEN
50/50
19.342
3151041BRUNSWICKG3
50/50
4.211
972187AH1-678 GEN
50/50
9.663
970933AG2-581 GEN
Solar/Wind Harmer
32.122
970099AG2-077 GEN
Solar/Wind Harmer
37.73
3144356SAPONY
Solar/Wind Harmer
0.991
3145506HICKORY
Solar/Wind Harmer
-0.103
3145506HICKORY
Solar/Wind Harmer
-0.062
3145506HICKORY
Solar/Wind Harmer
-0.015
316185AD1-033 GEN
Solar/Wind Harmer
2.733
316339AD2-160 GEN
Solar/Wind Harmer
1.745
316018AA1-139 ULT2
Solar/Wind Harmer
2.216
316017AA1-139 ULT1
Solar/Wind Harmer
2.093
3137176SLIGO L2192
Solar/Wind Harmer
-0.102
3146456SLIGO L269
Solar/Wind Harmer
3.052
3130086AYDLETT
Solar/Wind Harmer
-0.103
3146386ELIZ CT
Solar/Wind Harmer
-0.026
3142956BIRDNECK
Solar/Wind Harmer
1.38
316316AC1-027 C
Solar/Wind Harmer
0.789
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.638
316433W1029_GEN2
Solar/Wind Harmer
4.638
316181AB2-040 GEN
Solar/Wind Harmer
3.567
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
316036AC1-147 C
Solar/Wind Harmer
0.688
3150991CHESPKB
Adder
2.376
3150991CHESPKB
Adder
2.319
3146376EDENTON
Solar/Wind Harmer
0.755
3146376EDENTON
Solar/Wind Harmer
0.755
3145796HORNRTN
Solar/Wind Harmer
-0.076
3145593CAROLNA
Solar/Wind Harmer
-0.025
3145593CAROLNA
Solar/Wind Harmer
-0.025
966811AG1-552 GEN
Solar/Wind Harmer
2.845
3145593CAROLNA
Solar/Wind Harmer
0.21
316426AA2-053 GEN
Solar/Wind Harmer
2.552
3145783HORNRTN
Solar/Wind Harmer
2.992
3145783HORNRTN
Solar/Wind Harmer
2.394
3145783HORNRTN
Solar/Wind Harmer
0.748
3145783HORNRTN
Solar/Wind Harmer
0.299
316065AD1-022 GEN
Solar/Wind Harmer
12.605
3145893MURPHYS
Solar/Wind Harmer
0.703
3145893MURPHYS
Solar/Wind Harmer
-0.045
3146173TUNIS
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
315742AE1-103 GEN
Solar/Wind Harmer
2.631
316274AC1-208 GEN
Solar/Wind Harmer
2.679
3145933PARMELE
Solar/Wind Harmer
-0.049
3145933PARMELE
Solar/Wind Harmer
-0.025
939181AE1-148 GEN
Solar/Wind Harmer
13.708
3145493TOT1
Solar/Wind Harmer
0.376
3145453TOT5
Solar/Wind Harmer
0.226
3145603CNETO
Solar/Wind Harmer
0.151
961601AG1-000A GEN
Solar/Wind Harmer
9.538
316263AC1-034 GEN
Solar/Wind Harmer
11.37
3146843MT LREL
Solar/Wind Harmer
-0.023
3146843MT LREL
Solar/Wind Harmer
-0.023
964791AG1-342 GEN
Solar/Wind Harmer
4.916
962561AG1-105 GEN
Solar/Wind Harmer
12.943
313527AB2-043 GEN
Solar/Wind Harmer
3.735
316222AC1-221 GEN
Solar/Wind Harmer
2.263
970657AG2-426 GEN
Solar/Wind Harmer
6.965
970657AG2-426 GEN
Solar/Wind Harmer
1.456
316236AE1-162_GEN
Solar/Wind Harmer
0.669
971741AH1-377 GEN
Solar/Wind Harmer
25.152
970323AG2-213 GEN
Solar/Wind Harmer
10.321
971775AH1-396 GEN
Solar/Wind Harmer
1.47
316034AC1-036 C
Solar/Wind Harmer
0.383
970301AG2-198 GEN
Solar/Wind Harmer
9.888
3144293JTRSVLE
Adder
0.527
3144293JTRSVLE
Adder
0.444
944641AF1-129 GEN
Adder
54.839
316447AC1-158 HLD
Solar/Wind Helper
2.734
3151031BRUNSWICKG2
50/50
4.211
970413AG2-270 GEN
50/50
23.737
3151391GASTONA
50/50
0.617
3151411GASTONB
50/50
0.617
3151101ELIZAR3
50/50
22.447
970917AG2-570 GEN
Solar/Wind Harmer
86.292
316478AD1-087 GEN
Solar/Wind Harmer
2.471
316486AD2-202 GEN
Solar/Wind Harmer
0.724
315773AC2-141 GEN
Solar/Wind Harmer
11.15
316365GEN2_N
Solar/Wind Harmer
1.79
944581AF1-123 GEN
Solar/Wind Harmer
119.802
944601AF1-125 GEN
Solar/Wind Harmer
117.933
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.15
966621AG1-532 GEN
Solar/Wind Harmer
0.524
316320Y1-086
Solar/Wind Harmer
1.508
3146516WINFALL
Solar/Wind Harmer
-0.026
316435W1029_GEN3
Solar/Wind Harmer
4.638
313506AB2-031 GEN
Solar/Wind Harmer
2.056
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146376EDENTON
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.101
3145796HORNRTN
Solar/Wind Harmer
-0.025
315614AA2-178 GEN
Solar/Wind Harmer
2.733
971157AH1-035 GEN
Solar/Wind Harmer
3.155
315737AD1-076 GEN
Solar/Wind Harmer
4.795
3156081AA2-088 GEN
Solar/Wind Harmer
8.181
3146206CASHIE
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.176
3145893MURPHYS
Solar/Wind Harmer
-0.025
3146263WOODLND
Solar/Wind Harmer
-0.025
957521AF2-046 GEN
Solar/Wind Harmer
19.831
961681AG1-008 GEN
Solar/Wind Harmer
19.831
3146173TUNIS
Solar/Wind Harmer
-0.025
3156021HOLLOMANSOL
Solar/Wind Harmer
3.39
3145273HOLLAND
Solar/Wind Harmer
-0.019
316463AE2-346 GEN
Solar/Wind Harmer
0.407
316140AB2-099
Solar/Wind Harmer
0.17
962331AG1-082 GEN
Solar/Wind Harmer
3.145
316317KELFORD C
Solar/Wind Harmer
1.18
3145823KELFORD
Solar/Wind Harmer
-0.025
3147043LAWRENC
Solar/Wind Harmer
-0.015
3145963POPLR C
Solar/Wind Harmer
-0.025
316210AC1-098 GEN
Solar/Wind Harmer
3.898
315724AD1-057 GEN
Solar/Wind Harmer
1.426
3145933PARMELE
Solar/Wind Harmer
-0.025
966801AG1-551 GEN
Solar/Wind Harmer
3.071
3144536CHRHLND
Solar/Wind Harmer
-0.004
316327AA2-057 GEN
Solar/Wind Harmer
2.481
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
3146233WITAKRS
Solar/Wind Harmer
0.511
3146233WITAKRS
Solar/Wind Harmer
-0.016
3138543CONSLDL
Solar/Wind Harmer
-0.016
3146073TAR RVR
Solar/Wind Harmer
-0.024
3146083TARBORO
Solar/Wind Harmer
-0.024
961601AG1-000A GEN
Solar/Wind Harmer
9.659
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.024
316248AF1-058 C
Solar/Wind Harmer
0.694
960061AF2-297 GEN
Solar/Wind Harmer
11.515
316131AB2-060 GEN
Solar/Wind Harmer
2.463
970661AG2-428 GEN
Solar/Wind Harmer
4.26
316283AC2-100 C
Solar/Wind Harmer
2.097
3145336SMITFLD
Solar/Wind Harmer
-0.009
964241AG1-285 GEN
Solar/Wind Harmer
17.312
316083AB2-161 GEN
Solar/Wind Harmer
3.584
970659AG2-427 GEN
Solar/Wind Harmer
2.061
315785AD2-033 C
Solar/Wind Harmer
4.772
315813AE1-149 C
Solar/Wind Harmer
13.059
970257AG2-171 GEN
Solar/Wind Harmer
7.741
971683AH1-343 GEN
Solar/Wind Harmer
8.872
959311AF2-222 GEN
Solar/Wind Harmer
21.233
3151221GRAVEL6
Adder
13.016
3151171GRAVELC
Adder
2.504
970909AG2-566 GEN
Solar/Wind Harmer
1.877
3144216WINCHST
Adder
0.639
3150921YORKTN3
Adder
4.218
3144293JTRSVLE
Adder
0.527
316044AC1-158 PL1
Solar/Wind Helper
1.242
316450AC1-158 RIC
Solar/Wind Helper
0.331
961611AG1-000B GEN
Solar/Wind Harmer
0.889
CPLELTFEXP_CPLE->PJM
CLTF
15.822
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.369
LAGNLTFEXP_LAGN->PJM
CLTF
10.658
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.715
TVALTFEXP_TVA->PJM
CLTF
5.269
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.217
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.694
MECLTFEXP_MEC->PJM
CLTF
4.528
SIGELTFEXP_SIGE->PJM
CLTF
0.13
NYPJM->LTFIMP_NY
CLTF
2.139
LGEELTFEXP_LGEE->PJM
CLTF
1.496
WECLTFEXP_WEC->PJM
CLTF
0.787

Details for 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.08 %
Rating:1057.5 MVA
Rating Type:B
MVA to Mitigate:1343.9
MW Contribution:8.96
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
2.294
3151051BRUNSWICKS1
50/50
3.716
3151021BRUNSWICKG1
50/50
1.791
971451AH1-221 GEN
50/50
5.439
3151531CLOVER1
50/50
2.053
3151391GASTONA
50/50
0.214
3151411GASTONB
50/50
0.214
940641AE2-051 GEN
Solar/Wind Harmer
11.353
970919AG2-571 GEN
Solar/Wind Harmer
4.592
970087AG2-069 GEN
Solar/Wind Harmer
10.271
939411AE1-173 GEN
Solar/Wind Harmer
54.111
957481AF2-042 GEN
Solar/Wind Harmer
27.71
315693AD1-088 GEN
Solar/Wind Harmer
4.301
970533AG2-339 GEN
50/50
12.931
970531AG2-338 GEN
50/50
5.172
315242AE2-183_GT2
50/50
2.294
315241AE2-183_GT1
50/50
2.28
972185AH1-677 GEN
50/50
8.27
3151041BRUNSWICKG3
50/50
1.791
972187AH1-678 GEN
50/50
4.109
970933AG2-581 GEN
Solar/Wind Harmer
10.096
970099AG2-077 GEN
Solar/Wind Harmer
11.084
3144356SAPONY
Solar/Wind Harmer
0.732
3145506HICKORY
Solar/Wind Harmer
0.323
3145506HICKORY
Solar/Wind Harmer
0.194
3145506HICKORY
Solar/Wind Harmer
0.049
316185AD1-033 GEN
Solar/Wind Harmer
0.002
316339AD2-160 GEN
Solar/Wind Harmer
0.131
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.045
3137176SLIGO L2192
Solar/Wind Harmer
0.32
3146456SLIGO L269
Solar/Wind Harmer
1.425
3130086AYDLETT
Solar/Wind Harmer
0.322
3146386ELIZ CT
Solar/Wind Harmer
0.08
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.076
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146626S HERTFORD
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.079
3142666NORTHAMPTON
Solar/Wind Harmer
0.079
3142666NORTHAMPTON
Solar/Wind Harmer
0.079
3142666NORTHAMPTON
Solar/Wind Harmer
0.079
3142666NORTHAMPTON
Solar/Wind Harmer
0.047
3146376EDENTON
Solar/Wind Harmer
0.35
3146376EDENTON
Solar/Wind Harmer
0.35
3145796HORNRTN
Solar/Wind Harmer
0.236
316181AB2-040 GEN
Solar/Wind Harmer
0.113
316065AD1-022 GEN
Solar/Wind Harmer
3.592
316036AC1-147 C
Solar/Wind Harmer
0.014
3150991CHESPKB
Adder
0.817
3150991CHESPKB
Adder
0.797
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.078
966811AG1-552 GEN
Solar/Wind Harmer
0.842
3145593CAROLNA
Solar/Wind Harmer
0.097
316426AA2-053 GEN
Solar/Wind Harmer
0.262
3145783HORNRTN
Solar/Wind Harmer
1.378
3145783HORNRTN
Solar/Wind Harmer
1.102
3145783HORNRTN
Solar/Wind Harmer
0.345
3145783HORNRTN
Solar/Wind Harmer
0.138
3146173TUNIS
Solar/Wind Harmer
0.077
3146173TUNIS
Solar/Wind Harmer
0.077
3145893MURPHYS
Solar/Wind Harmer
0.515
3145893MURPHYS
Solar/Wind Harmer
0.139
316274AC1-208 GEN
Solar/Wind Harmer
0.399
3145933PARMELE
Solar/Wind Harmer
0.153
3145933PARMELE
Solar/Wind Harmer
0.076
3145493TOT1
Solar/Wind Harmer
0.176
3145453TOT5
Solar/Wind Harmer
0.105
3145603CNETO
Solar/Wind Harmer
0.07
315742AE1-103 GEN
Solar/Wind Harmer
0.001
961601AG1-000A GEN
Solar/Wind Harmer
1.347
316263AC1-034 GEN
Solar/Wind Harmer
2.877
939181AE1-148 GEN
Solar/Wind Harmer
3.519
316222AC1-221 GEN
Solar/Wind Harmer
0.294
3146843MT LREL
Solar/Wind Harmer
0.069
3146843MT LREL
Solar/Wind Harmer
0.069
964791AG1-342 GEN
Solar/Wind Harmer
1.325
962561AG1-105 GEN
Solar/Wind Harmer
3.278
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3143526WINTERP
Solar/Wind Helper
2.674
966871AG1-558 GEN
Solar/Wind Helper
0.173
315821AE2-092 GEN
Solar/Wind Helper
1.114
315687AD1-152 GEN
Solar/Wind Harmer
0.003
316294AC1-161 GEN
Solar/Wind Harmer
1.513
962491AG1-098 GEN
Solar/Wind Harmer
4.96
944591AF1-124 GEN
Solar/Wind Harmer
18.908
316023GEN1_S
Solar/Wind Harmer
0.183
316388AE2-253 GEN
Solar/Wind Harmer
0.253
3146456SLIGO L269
Solar/Wind Harmer
0.08
3146516WINFALL
Solar/Wind Harmer
0.257
3146516WINFALL
Solar/Wind Harmer
0.079
316011AB1-132 GEN
Solar/Wind Harmer
1.438
962571AG1-106 GEN
Solar/Wind Harmer
1.125
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.079
316246AF1-032 C
Solar/Wind Harmer
0.035
3145796HORNRTN
Solar/Wind Harmer
0.259
3145796HORNRTN
Solar/Wind Harmer
0.079
960081AF2-299 GEN
Solar/Wind Harmer
0.754
3145663CRESWEL
Solar/Wind Harmer
0.22
971163AH1-040 GEN
Solar/Wind Harmer
6.276
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.974
3146206CASHIE
Solar/Wind Harmer
0.078
971547AH1-271 GEN
Solar/Wind Harmer
1.663
316190AA2-174 GEN
Solar/Wind Harmer
0
3146263WOODLND
Solar/Wind Harmer
0.078
3145683EARLEYS
Solar/Wind Harmer
0.078
3145783HORNRTN
Solar/Wind Harmer
0.077
3145823KELFORD
Solar/Wind Harmer
0.077
3146173TUNIS
Solar/Wind Harmer
0.077
3145963POPLR C
Solar/Wind Harmer
0.077
3145893MURPHYS
Solar/Wind Harmer
0.308
3145893MURPHYS
Solar/Wind Harmer
0.342
315722AD1-056 GEN
Solar/Wind Harmer
0.488
316174AB2-169 GEN
Solar/Wind Harmer
0.002
316212AC1-099_GEN
Solar/Wind Harmer
0.398
3146293MARTNCO
Solar/Wind Harmer
0.071
316129AC1-054 GEN
Solar/Wind Harmer
0.286
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
3146233WITAKRS
Solar/Wind Harmer
0.302
971065AG2-659 GEN
Solar/Wind Harmer
3.242
316494AC1-189 GEN
Solar/Wind Harmer
0.256
961671AG1-007 GEN
Solar/Wind Harmer
0.012
3146083TARBORO
Solar/Wind Harmer
0.076
3145493TOT1
Solar/Wind Harmer
0.337
316359AB2-059 GEN
Solar/Wind Harmer
0.272
316049AB1-081 GEN
Solar/Wind Harmer
0.433
3142053HEARTS
Solar/Wind Harmer
0.133
3145543BTLEBRO
Solar/Wind Harmer
0.076
3145543BTLEBRO
Solar/Wind Harmer
0.06
971795AH1-408 GEN
Solar/Wind Harmer
5.038
316093AE2-104_GEN
Solar/Wind Harmer
1.261
3147043LAWRENC
Adder
0.671
316072AD1-144
Solar/Wind Harmer
0.025
970401AG2-262 GEN
Solar/Wind Harmer
0.405
316003AC1-222 GEN
Solar/Wind Harmer
0.002
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Helper
0.68
3143526WINTERP
Solar/Wind Helper
2.674
316336AC2-165 C
Solar/Wind Helper
2.289
3142543TWELFTH
Solar/Wind Helper
0.016
3151031BRUNSWICKG2
50/50
1.791
970413AG2-270 GEN
50/50
8.961
3151391GASTONA
50/50
0.214
3151411GASTONB
50/50
0.214
3151101ELIZAR3
50/50
7.756
970917AG2-570 GEN
Solar/Wind Harmer
11.479
316478AD1-087 GEN
Solar/Wind Harmer
0.335
316486AD2-202 GEN
Solar/Wind Harmer
0.098
315773AC2-141 GEN
Solar/Wind Harmer
3.189
944581AF1-123 GEN
Solar/Wind Harmer
18.841
944601AF1-125 GEN
Solar/Wind Harmer
18.551
316365GEN2_N
Solar/Wind Harmer
0.183
3146456SLIGO L269
Solar/Wind Harmer
0.08
971153AH1-033 GEN
Solar/Wind Harmer
0.931
316320Y1-086
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.079
316435W1029_GEN3
Solar/Wind Harmer
0
3146626S HERTFORD
Solar/Wind Harmer
0.079
3142666NORTHAMPTON
Solar/Wind Harmer
0.079
3146376EDENTON
Solar/Wind Harmer
0.079
3145796HORNRTN
Solar/Wind Harmer
0.314
3145796HORNRTN
Solar/Wind Harmer
0.079
315614AA2-178 GEN
Solar/Wind Harmer
0.449
315244AE2-183_ST
50/50
3.966
963041AG1-153 GEN
50/50
3.626
3151541CLOVER2
50/50
2.044
315779AE2-040
50/50
1.222
941031AE2-094 GEN
Solar/Wind Harmer
26.792
944011AF1-069 GEN
Solar/Wind Harmer
8.754
970673AG2-436 GEN
Solar/Wind Harmer
30.101
970673AG2-436 GEN
Solar/Wind Harmer
20.067
971967AH1-528 GEN
Solar/Wind Harmer
21.652
970085AG2-068 GEN
Solar/Wind Harmer
6.847
970581AG2-369 GEN
Solar/Wind Harmer
5.888
316315AB2-025 C
Solar/Wind Harmer
0.071
315814AE2-033 C
Solar/Wind Harmer
6.9
957871AF2-081 GEN
Solar/Wind Harmer
4.015
319010AE1-072 C
Solar/Wind Harmer
0.405
3146406KITTY HAWK
Solar/Wind Harmer
0.01
313526AB2-022
Solar/Wind Harmer
0.043
316321Z2-027
Solar/Wind Harmer
0.015
3145176PASQUOTANK
Solar/Wind Harmer
0.049
3146396TANGLEW
Solar/Wind Harmer
0.22
315652AC1-086 GEN
Solar/Wind Harmer
8.7
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3146486SUNBURY
Solar/Wind Harmer
0.079
3146486SUNBURY
Solar/Wind Harmer
0.079
3130156CHOWAN
Solar/Wind Harmer
0.079
3130156CHOWAN
Solar/Wind Harmer
0.079
3151081ELIZAR1
Adder
7.217
3151091ELIZAR2
Adder
7.092
316305AF2-043 C
Solar/Wind Harmer
0.001
3145796HORNRTN
Solar/Wind Harmer
0.251
3145796HORNRTN
Solar/Wind Harmer
0.031
315816AE2-034 GEN
Solar/Wind Harmer
0.337
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3130546PLYMOUTH
Solar/Wind Harmer
0.078
315732AD1-074 GEN1
Solar/Wind Harmer
0.449
315733AD1-074 GEN2
Solar/Wind Harmer
0.449
315735AD1-075 GEN1
Solar/Wind Harmer
0.225
3152611GOSPORTB
Adder
0.993
3152621GOSPORTC
Adder
0.843
3152601GOSPORTA
Adder
0.777
3146206CASHIE
Solar/Wind Harmer
0.078
970601AG2-382 GEN
Solar/Wind Harmer
2.911
3137643SOCKMAN
Solar/Wind Harmer
0.311
3145683EARLEYS
Solar/Wind Harmer
0.155
3145683EARLEYS
Solar/Wind Harmer
0.078
3145683EARLEYS
Solar/Wind Harmer
0.078
3145513AHOSKIE
Solar/Wind Harmer
0.162
3145513AHOSKIE
Solar/Wind Harmer
0.077
315607AA1-063A GEN
Solar/Wind Harmer
0.158
3146043SEABORD
Solar/Wind Harmer
0.077
3146033SCOT NK
Solar/Wind Harmer
0.308
3145893MURPHYS
Solar/Wind Harmer
0.208
3145893MURPHYS
Solar/Wind Harmer
0.077
965291AG1-394 GEN
Solar/Wind Harmer
0.341
970831AG2-522 GEN
Solar/Wind Harmer
3.254
316005AA1-067
Solar/Wind Harmer
0.082
3145746EVERETS
Solar/Wind Harmer
0.302
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
970181AG2-120 GEN
Solar/Wind Harmer
0.946
316319Z2-044 C
Solar/Wind Harmer
0
957861AF2-080 GEN
Solar/Wind Harmer
3.273
316420AA1-050 GEN
Solar/Wind Harmer
0.002
3145573BETHELC
Solar/Wind Harmer
0.076
3145573BETHELC
Solar/Wind Harmer
0.076
315835AF2-110_GEN
Solar/Wind Harmer
0.515
3147173SINAI
Solar/Wind Harmer
0.072
3147243WELCO
Solar/Wind Harmer
0.045
316118AC1-105 GEN
Solar/Wind Harmer
0.183
316311AC2-079 GEN
Solar/Wind Harmer
1.874
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.045
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
970865AG2-541 GEN
Solar/Wind Harmer
2.076
316233AE1-074 FULL
Solar/Wind Helper
0.785
270494AE1-108_GEN
Solar/Wind Helper
1.529
971157AH1-035 GEN
Solar/Wind Harmer
0.938
313506AB2-031 GEN
Solar/Wind Harmer
0.241
315737AD1-076 GEN
Solar/Wind Harmer
1.005
3144873MCLAUGH
Solar/Wind Harmer
0.002
3146206CASHIE
Solar/Wind Harmer
0.078
3156021HOLLOMANSOL
Solar/Wind Harmer
0.353
3146263WOODLND
Solar/Wind Harmer
0.078
316463AE2-346 GEN
Solar/Wind Harmer
0.067
316140AB2-099
Solar/Wind Harmer
0.028
962331AG1-082 GEN
Solar/Wind Harmer
0.826
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.077
3146173TUNIS
Solar/Wind Harmer
0.077
3145963POPLR C
Solar/Wind Harmer
0.077
957521AF2-046 GEN
Solar/Wind Harmer
5.738
961681AG1-008 GEN
Solar/Wind Harmer
5.738
3145893MURPHYS
Solar/Wind Harmer
0.129
3145893MURPHYS
Solar/Wind Harmer
0.077
315724AD1-057 GEN
Solar/Wind Harmer
0.289
316210AC1-098 GEN
Solar/Wind Harmer
0.713
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3145933PARMELE
Solar/Wind Harmer
0.076
966801AG1-551 GEN
Solar/Wind Harmer
0.89
316327AA2-057 GEN
Solar/Wind Harmer
0.115
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
3146233WITAKRS
Solar/Wind Harmer
0.381
3146233WITAKRS
Solar/Wind Harmer
0.052
3138543CONSLDL
Solar/Wind Harmer
0.05
3146073TAR RVR
Solar/Wind Harmer
0.076
3146083TARBORO
Solar/Wind Harmer
0.076
961601AG1-000A GEN
Solar/Wind Harmer
5.386
971623AH1-311 GEN
Solar/Wind Harmer
0.151
3145543BTLEBRO
Solar/Wind Harmer
0.076
3145543BTLEBRO
Solar/Wind Harmer
0.076
3145273HOLLAND
Solar/Wind Harmer
0.057
3147043LAWRENC
Solar/Wind Harmer
0.045
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.092
3144536CHRHLND
Solar/Wind Harmer
0.011
316283AC2-100 C
Solar/Wind Harmer
0.138
971683AH1-343 GEN
Solar/Wind Harmer
2.355
316131AB2-060 GEN
Solar/Wind Harmer
0.198
964241AG1-285 GEN
Solar/Wind Harmer
3.891
316313AB2-026
Solar/Wind Helper
0.727
316258AE1-075 C
Solar/Wind Helper
0.654
316405AF2-144 C
Solar/Wind Helper
0.545
316473AC1-191 GEN
Solar/Wind Helper
0.782
CPLELTFEXP_CPLE->PJM
CLTF
5.449
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.56
LAGNLTFEXP_LAGN->PJM
CLTF
3.43
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.518
TVALTFEXP_TVA->PJM
CLTF
1.701
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.686
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.763
MECLTFEXP_MEC->PJM
CLTF
1.546
SIGELTFEXP_SIGE->PJM
CLTF
0.045
NYPJM->LTFIMP_NY
CLTF
0.638
LGEELTFEXP_LGEE->PJM
CLTF
0.533
WECLTFEXP_WEC->PJM
CLTF
0.278

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-1: G202_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-1: G202_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.07 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:4086.88
MW Contribution:21.45
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
5.403
315244AE2-183_ST
50/50
7.855
963041AG1-153 GEN
50/50
7.23
315779AE2-040
50/50
3.41
3151541CLOVER2
50/50
4.892
941031AE2-094 GEN
Solar/Wind Harmer
59.803
944011AF1-069 GEN
Solar/Wind Harmer
18.738
970673AG2-436 GEN
Solar/Wind Harmer
65.622
970673AG2-436 GEN
Solar/Wind Harmer
33.227
971967AH1-528 GEN
Solar/Wind Harmer
57.655
970085AG2-068 GEN
Solar/Wind Harmer
18.173
970581AG2-369 GEN
Solar/Wind Harmer
15.629
316233AE1-074 FULL
Solar/Wind Harmer
0.781
971281AH1-106 GEN
Solar/Wind Harmer
4.721
971283AH1-107 GEN
Solar/Wind Harmer
4.721
316315AB2-025 C
Solar/Wind Harmer
0.74
315814AE2-033 C
Solar/Wind Harmer
25.448
3143316POE
Solar/Wind Harmer
-0.102
3151081ELIZAR1
Adder
20.247
3151091ELIZAR2
Adder
19.895
957871AF2-081 GEN
Solar/Wind Harmer
12.412
319010AE1-072 C
Solar/Wind Harmer
5.013
3146406KITTY HAWK
Solar/Wind Harmer
0.021
3152611GOSPORTB
Adder
2.808
3152621GOSPORTC
Adder
2.383
3152601GOSPORTA
Adder
2.198
316305AF2-043 C
Solar/Wind Harmer
0.745
313526AB2-022
Solar/Wind Harmer
0.665
315835AF2-110_GEN
Solar/Wind Harmer
3.079
316321Z2-027
Solar/Wind Harmer
0.663
3146396TANGLEW
Solar/Wind Harmer
0.452
3145176PASQUOTANK
Solar/Wind Harmer
-0.015
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
316311AC2-079 GEN
Solar/Wind Harmer
12.402
315833AF1-017_GEN
Solar/Wind Harmer
4.67
316349AD2-085 GEN
Solar/Wind Harmer
2.187
946281AF1-292 GEN
Solar/Wind Harmer
0.549
315611Z1-036_GEN2
Solar/Wind Harmer
6.004
316087AB2-174 GEN
Solar/Wind Harmer
3.457
3130156CHOWAN
Solar/Wind Harmer
-0.024
3130156CHOWAN
Solar/Wind Harmer
-0.024
965291AG1-394 GEN
Solar/Wind Harmer
2.123
315816AE2-034 GEN
Solar/Wind Harmer
1.934
315652AC1-086 GEN
Solar/Wind Harmer
26.851
3137643SOCKMAN
Solar/Wind Harmer
-0.095
316318V4-068
Solar/Wind Harmer
0.593
3145893MURPHYS
Solar/Wind Harmer
-0.064
3145893MURPHYS
Solar/Wind Harmer
-0.024
3146043SEABORD
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.4
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.786
315733AD1-074 GEN2
Solar/Wind Harmer
4.786
315735AD1-075 GEN1
Solar/Wind Harmer
2.394
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.322
3145513AHOSKIE
Solar/Wind Harmer
0.205
961941AG1-037 GEN
Solar/Wind Harmer
0.177
3145513AHOSKIE
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.075
3145796HORNRTN
Solar/Wind Harmer
-0.009
971285AH1-108 GEN
Adder
1.578
971445AH1-216 GEN
Solar/Wind Harmer
14.547
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
970831AG2-522 GEN
Solar/Wind Harmer
11.661
3146033SCOT NK
Solar/Wind Harmer
-0.092
972265AH1-717 GEN
Adder
15.775
3151201GRAVEL4
Adder
14.788
3151191GRAVEL3
Adder
14.601
3151211GRAVEL5
Adder
14.601
316239AB2-077_GEN
Solar/Wind Harmer
0.682
316238AB2-078_GEN
Solar/Wind Harmer
0.682
971443AH1-215 GEN
Solar/Wind Harmer
4.356
316005AA1-067
Solar/Wind Harmer
0.448
3145746EVERETS
Solar/Wind Harmer
-0.088
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
970181AG2-120 GEN
Solar/Wind Harmer
2.904
3144303KENBRDG
Solar/Wind Harmer
-0.018
316369SG1_INVT
Solar/Wind Harmer
3.949
957861AF2-080 GEN
Solar/Wind Harmer
9.609
316319Z2-044 C
Solar/Wind Harmer
1.213
316420AA1-050 GEN
Solar/Wind Harmer
2.5
3142433PROV 92
Adder
0.303
3142433PROV 92
Adder
0.303
972205AH1-687 GEN
Adder
5.892
970683AG2-441 GEN
Solar/Wind Harmer
7.481
970681AG2-440 GEN
Solar/Wind Harmer
5.985
3151031BRUNSWICKG2
50/50
3.571
970413AG2-270 GEN
50/50
21.45
3151101ELIZAR3
50/50
21.759
970917AG2-570 GEN
Solar/Wind Harmer
73.039
316313AB2-026
Solar/Wind Harmer
0.72
316258AE1-075 C
Solar/Wind Harmer
0.648
316405AF2-144 C
Solar/Wind Harmer
0.684
3143336POWHATN
Solar/Wind Harmer
2.693
316478AD1-087 GEN
Solar/Wind Harmer
2.233
316486AD2-202 GEN
Solar/Wind Harmer
0.654
316365GEN2_N
Solar/Wind Harmer
1.694
944581AF1-123 GEN
Solar/Wind Harmer
114.149
944601AF1-125 GEN
Solar/Wind Harmer
112.367
315773AC2-141 GEN
Solar/Wind Harmer
10.461
3146456SLIGO L269
Solar/Wind Harmer
-0.025
971153AH1-033 GEN
Solar/Wind Harmer
3.022
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316320Y1-086
Solar/Wind Harmer
1.445
970661AG2-428 GEN
Solar/Wind Harmer
4.62
966621AG1-532 GEN
Solar/Wind Harmer
0.498
316435W1029_GEN3
Solar/Wind Harmer
4.441
316083AB2-161 GEN
Solar/Wind Harmer
3.979
970659AG2-427 GEN
Solar/Wind Harmer
2.307
3146516WINFALL
Solar/Wind Harmer
-0.024
315813AE1-149 C
Solar/Wind Harmer
15.291
3144536CHRHLND
Solar/Wind Harmer
-0.004
3145273HOLLAND
Solar/Wind Harmer
-0.018
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146376EDENTON
Solar/Wind Harmer
-0.024
313506AB2-031 GEN
Solar/Wind Harmer
1.938
3156081AA2-088 GEN
Solar/Wind Harmer
7.776
3147043LAWRENC
Solar/Wind Harmer
-0.014
315614AA2-178 GEN
Solar/Wind Harmer
2.579
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
0.166
3145893MURPHYS
Solar/Wind Harmer
-0.024
315839AE2-212 C
Solar/Wind Harmer
0.716
957521AF2-046 GEN
Solar/Wind Harmer
18.692
961681AG1-008 GEN
Solar/Wind Harmer
18.692
971157AH1-035 GEN
Solar/Wind Harmer
2.963
315737AD1-076 GEN
Solar/Wind Harmer
4.498
3146173TUNIS
Solar/Wind Harmer
-0.024
3146206CASHIE
Solar/Wind Harmer
-0.024
3145336SMITFLD
Solar/Wind Harmer
-0.009
316463AE2-346 GEN
Solar/Wind Harmer
0.381
316140AB2-099
Solar/Wind Harmer
0.159
962331AG1-082 GEN
Solar/Wind Harmer
2.944
3145796HORNRTN
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146263WOODLND
Solar/Wind Harmer
-0.023
3150861SPRUNCD
Adder
0.964
3156021HOLLOMANSOL
Solar/Wind Harmer
3.164
316317KELFORD C
Solar/Wind Harmer
1.095
3145823KELFORD
Solar/Wind Harmer
-0.023
965281AG1-393 GEN
Solar/Wind Harmer
2.888
3145963POPLR C
Solar/Wind Harmer
-0.023
970909AG2-566 GEN
Solar/Wind Harmer
2.169
970119AG2-088 GEN
50/50
40.525
315243AE2-183_GT3
50/50
4.543
3151051BRUNSWICKS1
50/50
7.411
3151021BRUNSWICKG1
50/50
3.571
971451AH1-221 GEN
50/50
10.845
3151531CLOVER1
50/50
4.915
3143226MDLTHAN
Solar/Wind Harmer
-0.034
940641AE2-051 GEN
Solar/Wind Harmer
29.721
939411AE1-173 GEN
Solar/Wind Harmer
150.037
970919AG2-571 GEN
Solar/Wind Harmer
9.245
970087AG2-069 GEN
Solar/Wind Harmer
27.26
3143526WINTERP
Solar/Wind Harmer
-0.15
957481AF2-042 GEN
Solar/Wind Harmer
84.586
3143336POWHATN
Solar/Wind Harmer
3.168
315693AD1-088 GEN
Solar/Wind Harmer
13.025
962491AG1-098 GEN
Solar/Wind Harmer
17.31
316023GEN1_S
Solar/Wind Harmer
1.694
944591AF1-124 GEN
Solar/Wind Harmer
114.56
316294AC1-161 GEN
Solar/Wind Harmer
8.089
316388AE2-253 GEN
Solar/Wind Harmer
1.675
3146456SLIGO L269
Solar/Wind Harmer
-0.025
316375AC2-012 GEN
Solar/Wind Harmer
8.572
3150981CHESPKA
Adder
2.753
316336AC2-165 C
Solar/Wind Harmer
4.3
316246AF1-032 C
Solar/Wind Harmer
0.5
316093AE2-104_GEN
Solar/Wind Harmer
7.163
970661AG2-428 GEN
Solar/Wind Harmer
26.068
960081AF2-299 GEN
Solar/Wind Harmer
2.759
316381AD1-082 GEN
Solar/Wind Harmer
2.248
970659AG2-427 GEN
Solar/Wind Harmer
13.019
3146516WINFALL
Solar/Wind Harmer
-0.079
3146516WINFALL
Solar/Wind Harmer
-0.024
315800Z1-036_GEN1
Solar/Wind Harmer
6.004
3130156CHOWAN
Solar/Wind Harmer
-0.024
971795AH1-408 GEN
Solar/Wind Harmer
18.101
316072AD1-144
Solar/Wind Harmer
0.488
315687AD1-152 GEN
Solar/Wind Harmer
2.903
3147043LAWRENC
Adder
1.929
3145663CRESWEL
Solar/Wind Harmer
-0.067
971163AH1-040 GEN
Solar/Wind Harmer
22.406
316011AB1-132 GEN
Solar/Wind Harmer
4.994
962571AG1-106 GEN
Solar/Wind Harmer
3.431
3145893MURPHYS
Solar/Wind Harmer
-0.095
3145893MURPHYS
Solar/Wind Harmer
0.706
3146173TUNIS
Solar/Wind Harmer
-0.024
316190AA2-174 GEN
Solar/Wind Harmer
0.29
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
5.898
3145336SMITFLD
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.077
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146263WOODLND
Solar/Wind Harmer
-0.023
3150851SPRUNCC
Adder
0.964
3145783HORNRTN
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
316129AC1-054 GEN
Solar/Wind Harmer
2.042
971065AG2-659 GEN
Solar/Wind Harmer
11.627
3145823KELFORD
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
316174AB2-169 GEN
Solar/Wind Harmer
3.526
3151171GRAVELC
Adder
2.161
316212AC1-099_GEN
Solar/Wind Harmer
1.989
315671AE2-027_GEN
Solar/Wind Harmer
17.038
316237AB2-079_GEN
Solar/Wind Harmer
0.682
961611AG1-000B GEN
Solar/Wind Harmer
11.126
315722AD1-056 GEN
Solar/Wind Harmer
2.354
3146293MARTNCO
Solar/Wind Harmer
0.139
971647AH1-324 GEN
Solar/Wind Harmer
11.16
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
316494AC1-189 GEN
Solar/Wind Harmer
2.363
3146233WITAKRS
Solar/Wind Harmer
-0.087
971069AG2-661 GEN
Solar/Wind Harmer
3.469
970685AG2-442 GEN
Solar/Wind Harmer
19.125
3144293JTRSVLE
Adder
0.613
3143096IRON208
Adder
0.73
944631AF1-128 GEN
Adder
80.725
3142433PROV 92
Adder
0.303
3142433PROV 92
Adder
0.303
3141843SHACKLE
Adder
0.759
3150351NORNECKC2
Adder
1.14
316045AC1-158 PL2
Solar/Wind Helper
5.258
3147666LOUISA
Solar/Wind Helper
0.902
970533AG2-339 GEN
50/50
25.233
970531AG2-338 GEN
50/50
10.093
315242AE2-183_GT2
50/50
4.543
315241AE2-183_GT1
50/50
4.515
3151221GRAVEL6
Adder
14.771
3151171GRAVELC
Adder
2.842
316210AC1-098 GEN
Solar/Wind Harmer
3.58
316131AB2-060 GEN
Solar/Wind Harmer
2.441
961611AG1-000B GEN
Solar/Wind Harmer
4.747
315724AD1-057 GEN
Solar/Wind Harmer
1.295
964241AG1-285 GEN
Solar/Wind Harmer
17.552
3145933PARMELE
Solar/Wind Harmer
-0.022
966801AG1-551 GEN
Solar/Wind Harmer
2.798
316327AA2-057 GEN
Solar/Wind Harmer
2.249
315785AD2-033 C
Solar/Wind Harmer
5.032
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
970257AG2-171 GEN
Solar/Wind Harmer
8.289
959311AF2-222 GEN
Solar/Wind Harmer
22.999
3146233WITAKRS
Solar/Wind Harmer
0.46
3146233WITAKRS
Solar/Wind Harmer
-0.015
3138543CONSLDL
Solar/Wind Harmer
-0.014
315778AD1-151 GEN
Solar/Wind Harmer
18.993
3144293JTRSVLE
Adder
0.613
3144216WINCHST
Adder
0.711
3150921YORKTN3
Adder
4.681
3143096IRON208
Adder
0.73
3143096IRON208
Adder
0.715
3142433PROV 92
Adder
0.303
3142433PROV 92
Adder
0.303
3141843SHACKLE
Adder
0.759
3150351NORNECKC2
Adder
1.16
316044AC1-158 PL1
Solar/Wind Helper
1.642
316450AC1-158 RIC
Solar/Wind Helper
0.438
3147666LOUISA
Solar/Wind Helper
0.519
972185AH1-677 GEN
50/50
16.379
3151041BRUNSWICKG3
50/50
3.571
972187AH1-678 GEN
50/50
8.194
971223AH1-071 GEN
Solar/Wind Harmer
4.269
970933AG2-581 GEN
Solar/Wind Harmer
27.802
3143526WINTERP
Solar/Wind Harmer
-0.15
3144356SAPONY
Solar/Wind Harmer
0.957
970099AG2-077 GEN
Solar/Wind Harmer
33.834
316185AD1-033 GEN
Solar/Wind Harmer
2.627
3145506HICKORY
Solar/Wind Harmer
-0.099
3145506HICKORY
Solar/Wind Harmer
-0.059
3145506HICKORY
Solar/Wind Harmer
-0.015
3142956BIRDNECK
Solar/Wind Harmer
1.333
316316AC1-027 C
Solar/Wind Harmer
0.762
316339AD2-160 GEN
Solar/Wind Harmer
1.675
316018AA1-139 ULT2
Solar/Wind Harmer
2.126
316017AA1-139 ULT1
Solar/Wind Harmer
2.009
3137176SLIGO L2192
Solar/Wind Harmer
-0.098
3146456SLIGO L269
Solar/Wind Harmer
2.928
3130086AYDLETT
Solar/Wind Harmer
-0.099
316036AC1-147 C
Solar/Wind Harmer
0.668
3150991CHESPKB
Adder
2.309
3150991CHESPKB
Adder
2.254
3146386ELIZ CT
Solar/Wind Harmer
-0.025
970657AG2-426 GEN
Solar/Wind Harmer
7.663
970657AG2-426 GEN
Solar/Wind Harmer
1.602
316431W1029_GEN1
Solar/Wind Harmer
4.441
316433W1029_GEN2
Solar/Wind Harmer
4.441
3146516WINFALL
Solar/Wind Harmer
-0.024
3146516WINFALL
Solar/Wind Harmer
-0.024
3146516WINFALL
Solar/Wind Harmer
-0.024
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146626S HERTFORD
Solar/Wind Harmer
-0.024
315742AE1-103 GEN
Solar/Wind Harmer
2.543
3146376EDENTON
Solar/Wind Harmer
0.717
3146376EDENTON
Solar/Wind Harmer
0.717
316181AB2-040 GEN
Solar/Wind Harmer
3.363
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145893MURPHYS
Solar/Wind Harmer
0.663
3145893MURPHYS
Solar/Wind Harmer
-0.043
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
966811AG1-552 GEN
Solar/Wind Harmer
2.661
3145593CAROLNA
Solar/Wind Harmer
0.196
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
316426AA2-053 GEN
Solar/Wind Harmer
2.386
316065AD1-022 GEN
Solar/Wind Harmer
11.81
316236AE1-162_GEN
Solar/Wind Harmer
0.711
971741AH1-377 GEN
Solar/Wind Harmer
27.409
3145796HORNRTN
Solar/Wind Harmer
-0.07
3145783HORNRTN
Solar/Wind Harmer
2.79
3145783HORNRTN
Solar/Wind Harmer
2.232
3145783HORNRTN
Solar/Wind Harmer
0.698
3145783HORNRTN
Solar/Wind Harmer
0.279
939181AE1-148 GEN
Solar/Wind Harmer
12.946
970301AG2-198 GEN
Solar/Wind Harmer
11.421
316274AC1-208 GEN
Solar/Wind Harmer
2.458
313527AB2-043 GEN
Solar/Wind Harmer
3.682
316240AF1-291 C
Solar/Wind Harmer
0.675
3145933PARMELE
Solar/Wind Harmer
-0.044
3145933PARMELE
Solar/Wind Harmer
-0.022
970323AG2-213 GEN
Solar/Wind Harmer
11.053
971775AH1-396 GEN
Solar/Wind Harmer
1.574
316034AC1-036 C
Solar/Wind Harmer
0.41
316033AB2-134 GEN
Solar/Wind Harmer
7.127
315697AD1-025 GEN
Solar/Wind Harmer
4.47
944641AF1-129 GEN
Adder
93.238
962561AG1-105 GEN
Solar/Wind Harmer
12.325
3144293JTRSVLE
Adder
0.613
3144293JTRSVLE
Adder
0.516
3142366NRTHEST
Adder
0.501
3150691DARBY 3
Adder
10.867
3150701DARBY 4
Adder
10.841
3150681DARBY 2
Adder
10.829
3150671DARBY 1
Adder
10.816
3142296MT RD221
Adder
0.386
3150341NORNECKC1
Adder
1.198
3150341NORNECKC1
Adder
1.188
316447AC1-158 HLD
Solar/Wind Helper
3.615
CPLELTFEXP_CPLE->PJM
CLTF
12.94
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.681
LAGNLTFEXP_LAGN->PJM
CLTF
8.918
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.956
TVALTFEXP_TVA->PJM
CLTF
4.471
CBM West 1LTFEXP_CBM-W1->PJM
CBM
26.974
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.275
MECLTFEXP_MEC->PJM
CLTF
4.234
SIGELTFEXP_SIGE->PJM
CLTF
0.127
NYPJM->LTFIMP_NY
CLTF
2.444
LGEELTFEXP_LGEE->PJM
CLTF
1.534
WECLTFEXP_WEC->PJM
CLTF
0.779

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P2-2: NORTH ANNA B1_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: NORTH ANNA B1_SRT-S
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:126.92 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:3957.44
MW Contribution:21.55
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
5.424
315244AE2-183_ST
50/50
7.889
963041AG1-153 GEN
50/50
7.262
315779AE2-040
50/50
3.426
3151541CLOVER2
50/50
4.914
941031AE2-094 GEN
Solar/Wind Harmer
60.059
944011AF1-069 GEN
Solar/Wind Harmer
18.818
970673AG2-436 GEN
Solar/Wind Harmer
65.906
970673AG2-436 GEN
Solar/Wind Harmer
33.37
971967AH1-528 GEN
Solar/Wind Harmer
57.904
970085AG2-068 GEN
Solar/Wind Harmer
18.255
970581AG2-369 GEN
Solar/Wind Harmer
15.699
316233AE1-074 FULL
Solar/Wind Harmer
0.785
971281AH1-106 GEN
Solar/Wind Harmer
4.743
971283AH1-107 GEN
Solar/Wind Harmer
4.743
316315AB2-025 C
Solar/Wind Harmer
0.744
315814AE2-033 C
Solar/Wind Harmer
25.573
3143316POE
Solar/Wind Harmer
-0.102
957871AF2-081 GEN
Solar/Wind Harmer
12.48
3151081ELIZAR1
Adder
20.359
3151091ELIZAR2
Adder
20.005
319010AE1-072 C
Solar/Wind Harmer
5.041
3146406KITTY HAWK
Solar/Wind Harmer
0.021
3152611GOSPORTB
Adder
2.823
3152621GOSPORTC
Adder
2.396
3152601GOSPORTA
Adder
2.21
316305AF2-043 C
Solar/Wind Harmer
0.749
313526AB2-022
Solar/Wind Harmer
0.669
315835AF2-110_GEN
Solar/Wind Harmer
3.096
316321Z2-027
Solar/Wind Harmer
0.667
3146396TANGLEW
Solar/Wind Harmer
0.455
3145176PASQUOTANK
Solar/Wind Harmer
-0.015
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
316311AC2-079 GEN
Solar/Wind Harmer
12.471
315833AF1-017_GEN
Solar/Wind Harmer
4.696
316349AD2-085 GEN
Solar/Wind Harmer
2.199
946281AF1-292 GEN
Solar/Wind Harmer
0.552
315611Z1-036_GEN2
Solar/Wind Harmer
6.037
316087AB2-174 GEN
Solar/Wind Harmer
3.475
3130156CHOWAN
Solar/Wind Harmer
-0.024
3130156CHOWAN
Solar/Wind Harmer
-0.024
965291AG1-394 GEN
Solar/Wind Harmer
2.135
315816AE2-034 GEN
Solar/Wind Harmer
1.945
315652AC1-086 GEN
Solar/Wind Harmer
26.995
3137643SOCKMAN
Solar/Wind Harmer
-0.095
316318V4-068
Solar/Wind Harmer
0.596
3145893MURPHYS
Solar/Wind Harmer
-0.064
3145893MURPHYS
Solar/Wind Harmer
-0.024
3146043SEABORD
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.413
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.813
315733AD1-074 GEN2
Solar/Wind Harmer
4.813
315735AD1-075 GEN1
Solar/Wind Harmer
2.407
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.379
3145513AHOSKIE
Solar/Wind Harmer
0.206
961941AG1-037 GEN
Solar/Wind Harmer
0.178
3145513AHOSKIE
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.075
3145796HORNRTN
Solar/Wind Harmer
-0.009
971285AH1-108 GEN
Adder
1.587
971445AH1-216 GEN
Solar/Wind Harmer
14.632
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
970831AG2-522 GEN
Solar/Wind Harmer
11.72
3146033SCOT NK
Solar/Wind Harmer
-0.092
972265AH1-717 GEN
Adder
15.87
3151201GRAVEL4
Adder
14.877
3151191GRAVEL3
Adder
14.689
3151211GRAVEL5
Adder
14.689
316239AB2-077_GEN
Solar/Wind Harmer
0.685
316238AB2-078_GEN
Solar/Wind Harmer
0.685
316005AA1-067
Solar/Wind Harmer
0.45
3145746EVERETS
Solar/Wind Harmer
-0.088
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
970181AG2-120 GEN
Solar/Wind Harmer
2.92
316369SG1_INVT
Solar/Wind Harmer
3.973
971443AH1-215 GEN
Solar/Wind Harmer
4.375
3144303KENBRDG
Solar/Wind Harmer
-0.018
957861AF2-080 GEN
Solar/Wind Harmer
9.664
316319Z2-044 C
Solar/Wind Harmer
1.22
316420AA1-050 GEN
Solar/Wind Harmer
2.514
3145573BETHELC
Solar/Wind Harmer
-0.022
3145573BETHELC
Solar/Wind Harmer
-0.022
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
972205AH1-687 GEN
Adder
5.897
970683AG2-441 GEN
Solar/Wind Harmer
6.68
970681AG2-440 GEN
Solar/Wind Harmer
5.344
3151031BRUNSWICKG2
50/50
3.586
970413AG2-270 GEN
50/50
21.547
3151101ELIZAR3
50/50
21.88
970917AG2-570 GEN
Solar/Wind Harmer
73.368
316313AB2-026
Solar/Wind Harmer
0.722
316258AE1-075 C
Solar/Wind Harmer
0.65
316405AF2-144 C
Solar/Wind Harmer
0.686
3143336POWHATN
Solar/Wind Harmer
2.702
316478AD1-087 GEN
Solar/Wind Harmer
2.243
316486AD2-202 GEN
Solar/Wind Harmer
0.657
316365GEN2_N
Solar/Wind Harmer
1.702
944581AF1-123 GEN
Solar/Wind Harmer
114.775
944601AF1-125 GEN
Solar/Wind Harmer
112.984
315773AC2-141 GEN
Solar/Wind Harmer
10.519
3146456SLIGO L269
Solar/Wind Harmer
-0.025
971153AH1-033 GEN
Solar/Wind Harmer
3.039
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316320Y1-086
Solar/Wind Harmer
1.453
970661AG2-428 GEN
Solar/Wind Harmer
4.646
316435W1029_GEN3
Solar/Wind Harmer
4.466
316083AB2-161 GEN
Solar/Wind Harmer
4.001
966621AG1-532 GEN
Solar/Wind Harmer
0.5
970659AG2-427 GEN
Solar/Wind Harmer
2.32
3146516WINFALL
Solar/Wind Harmer
-0.025
315813AE1-149 C
Solar/Wind Harmer
15.377
3144536CHRHLND
Solar/Wind Harmer
-0.004
3145273HOLLAND
Solar/Wind Harmer
-0.018
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146376EDENTON
Solar/Wind Harmer
-0.024
313506AB2-031 GEN
Solar/Wind Harmer
1.948
3156081AA2-088 GEN
Solar/Wind Harmer
7.818
3147043LAWRENC
Solar/Wind Harmer
-0.014
315614AA2-178 GEN
Solar/Wind Harmer
2.593
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
0.167
3145893MURPHYS
Solar/Wind Harmer
-0.024
315839AE2-212 C
Solar/Wind Harmer
0.72
957521AF2-046 GEN
Solar/Wind Harmer
18.794
961681AG1-008 GEN
Solar/Wind Harmer
18.794
971157AH1-035 GEN
Solar/Wind Harmer
2.979
315737AD1-076 GEN
Solar/Wind Harmer
4.523
3146173TUNIS
Solar/Wind Harmer
-0.024
3146206CASHIE
Solar/Wind Harmer
-0.024
3145336SMITFLD
Solar/Wind Harmer
-0.009
316463AE2-346 GEN
Solar/Wind Harmer
0.383
316140AB2-099
Solar/Wind Harmer
0.16
962331AG1-082 GEN
Solar/Wind Harmer
2.96
3145796HORNRTN
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.024
3150861SPRUNCD
Adder
0.97
3146263WOODLND
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.182
316317KELFORD C
Solar/Wind Harmer
1.101
3145823KELFORD
Solar/Wind Harmer
-0.023
965281AG1-393 GEN
Solar/Wind Harmer
2.906
3145963POPLR C
Solar/Wind Harmer
-0.023
3151221GRAVEL6
Adder
14.86
3151171GRAVELC
Adder
2.859
316210AC1-098 GEN
Solar/Wind Harmer
3.599
970909AG2-566 GEN
Solar/Wind Harmer
2.177
316131AB2-060 GEN
Solar/Wind Harmer
2.453
961611AG1-000B GEN
Solar/Wind Harmer
4.776
315724AD1-057 GEN
Solar/Wind Harmer
1.302
964241AG1-285 GEN
Solar/Wind Harmer
17.632
3145933PARMELE
Solar/Wind Harmer
-0.022
966801AG1-551 GEN
Solar/Wind Harmer
2.814
316327AA2-057 GEN
Solar/Wind Harmer
2.261
315785AD2-033 C
Solar/Wind Harmer
5.054
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
970257AG2-171 GEN
Solar/Wind Harmer
8.325
959311AF2-222 GEN
Solar/Wind Harmer
23.096
3146233WITAKRS
Solar/Wind Harmer
0.462
3146233WITAKRS
Solar/Wind Harmer
-0.015
315778AD1-151 GEN
Solar/Wind Harmer
19.113
3138543CONSLDL
Solar/Wind Harmer
-0.014
3146073TAR RVR
Solar/Wind Harmer
-0.022
3146083TARBORO
Solar/Wind Harmer
-0.022
3144293JTRSVLE
Adder
0.615
3144216WINCHST
Adder
0.716
3150921YORKTN3
Adder
4.712
3143096IRON208
Adder
0.735
3143096IRON208
Adder
0.72
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3141843SHACKLE
Adder
0.766
3150351NORNECKC2
Adder
1.172
316044AC1-158 PL1
Solar/Wind Helper
1.626
316450AC1-158 RIC
Solar/Wind Helper
0.434
3147666LOUISA
Solar/Wind Helper
0.562
970533AG2-339 GEN
50/50
25.341
970531AG2-338 GEN
50/50
10.136
315242AE2-183_GT2
50/50
4.563
315241AE2-183_GT1
50/50
4.535
972185AH1-677 GEN
50/50
16.45
3151041BRUNSWICKG3
50/50
3.586
972187AH1-678 GEN
50/50
8.23
971223AH1-071 GEN
Solar/Wind Harmer
4.285
970933AG2-581 GEN
Solar/Wind Harmer
27.922
3143526WINTERP
Solar/Wind Harmer
-0.151
3144356SAPONY
Solar/Wind Harmer
0.962
970099AG2-077 GEN
Solar/Wind Harmer
33.984
316185AD1-033 GEN
Solar/Wind Harmer
2.641
3145506HICKORY
Solar/Wind Harmer
-0.1
3145506HICKORY
Solar/Wind Harmer
-0.06
3145506HICKORY
Solar/Wind Harmer
-0.015
3142956BIRDNECK
Solar/Wind Harmer
1.34
316316AC1-027 C
Solar/Wind Harmer
0.766
316339AD2-160 GEN
Solar/Wind Harmer
1.684
316018AA1-139 ULT2
Solar/Wind Harmer
2.138
316017AA1-139 ULT1
Solar/Wind Harmer
2.02
3137176SLIGO L2192
Solar/Wind Harmer
-0.099
3146456SLIGO L269
Solar/Wind Harmer
2.944
316036AC1-147 C
Solar/Wind Harmer
0.672
3130086AYDLETT
Solar/Wind Harmer
-0.099
3150991CHESPKB
Adder
2.322
3150991CHESPKB
Adder
2.266
3146386ELIZ CT
Solar/Wind Harmer
-0.025
970657AG2-426 GEN
Solar/Wind Harmer
7.706
970657AG2-426 GEN
Solar/Wind Harmer
1.611
316431W1029_GEN1
Solar/Wind Harmer
4.466
316433W1029_GEN2
Solar/Wind Harmer
4.466
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146626S HERTFORD
Solar/Wind Harmer
-0.024
315742AE1-103 GEN
Solar/Wind Harmer
2.557
3146376EDENTON
Solar/Wind Harmer
0.721
3146376EDENTON
Solar/Wind Harmer
0.721
316181AB2-040 GEN
Solar/Wind Harmer
3.381
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145893MURPHYS
Solar/Wind Harmer
0.667
3145893MURPHYS
Solar/Wind Harmer
-0.043
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
966811AG1-552 GEN
Solar/Wind Harmer
2.675
3145593CAROLNA
Solar/Wind Harmer
0.198
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
316065AD1-022 GEN
Solar/Wind Harmer
11.875
316426AA2-053 GEN
Solar/Wind Harmer
2.399
316236AE1-162_GEN
Solar/Wind Harmer
0.715
3145796HORNRTN
Solar/Wind Harmer
-0.071
971741AH1-377 GEN
Solar/Wind Harmer
27.515
3145783HORNRTN
Solar/Wind Harmer
2.805
3145783HORNRTN
Solar/Wind Harmer
2.244
3145783HORNRTN
Solar/Wind Harmer
0.701
3145783HORNRTN
Solar/Wind Harmer
0.281
939181AE1-148 GEN
Solar/Wind Harmer
13.009
970301AG2-198 GEN
Solar/Wind Harmer
11.463
316274AC1-208 GEN
Solar/Wind Harmer
2.472
313527AB2-043 GEN
Solar/Wind Harmer
3.699
316240AF1-291 C
Solar/Wind Harmer
0.679
3145933PARMELE
Solar/Wind Harmer
-0.045
3145933PARMELE
Solar/Wind Harmer
-0.022
316033AB2-134 GEN
Solar/Wind Harmer
7.172
315697AD1-025 GEN
Solar/Wind Harmer
4.498
970323AG2-213 GEN
Solar/Wind Harmer
11.1
971775AH1-396 GEN
Solar/Wind Harmer
1.581
316034AC1-036 C
Solar/Wind Harmer
0.412
944641AF1-129 GEN
Adder
93.824
962561AG1-105 GEN
Solar/Wind Harmer
12.386
3145493TOT1
Solar/Wind Harmer
0.34
3145453TOT5
Solar/Wind Harmer
0.204
3145603CNETO
Solar/Wind Harmer
0.136
3144293JTRSVLE
Adder
0.615
3144293JTRSVLE
Adder
0.518
3142366NRTHEST
Adder
0.505
3150691DARBY 3
Adder
10.955
3150701DARBY 4
Adder
10.93
3150681DARBY 2
Adder
10.917
3150671DARBY 1
Adder
10.904
3142296MT RD221
Adder
0.39
3150341NORNECKC1
Adder
1.211
3150341NORNECKC1
Adder
1.201
316447AC1-158 HLD
Solar/Wind Helper
3.579
970119AG2-088 GEN
50/50
40.684
315243AE2-183_GT3
50/50
4.563
3151051BRUNSWICKS1
50/50
7.443
3151021BRUNSWICKG1
50/50
3.586
971451AH1-221 GEN
50/50
10.893
3151531CLOVER1
50/50
4.938
3143226MDLTHAN
Solar/Wind Harmer
-0.034
940641AE2-051 GEN
Solar/Wind Harmer
29.852
939411AE1-173 GEN
Solar/Wind Harmer
150.731
970919AG2-571 GEN
Solar/Wind Harmer
9.287
970087AG2-069 GEN
Solar/Wind Harmer
27.383
3143526WINTERP
Solar/Wind Harmer
-0.151
957481AF2-042 GEN
Solar/Wind Harmer
84.959
3143336POWHATN
Solar/Wind Harmer
3.179
315693AD1-088 GEN
Solar/Wind Harmer
13.081
962491AG1-098 GEN
Solar/Wind Harmer
17.384
316023GEN1_S
Solar/Wind Harmer
1.702
944591AF1-124 GEN
Solar/Wind Harmer
115.189
316294AC1-161 GEN
Solar/Wind Harmer
8.133
316388AE2-253 GEN
Solar/Wind Harmer
1.684
3146456SLIGO L269
Solar/Wind Harmer
-0.025
316375AC2-012 GEN
Solar/Wind Harmer
8.62
3150981CHESPKA
Adder
2.768
316246AF1-032 C
Solar/Wind Harmer
0.503
316336AC2-165 C
Solar/Wind Harmer
4.313
316093AE2-104_GEN
Solar/Wind Harmer
7.202
970661AG2-428 GEN
Solar/Wind Harmer
26.214
316381AD1-082 GEN
Solar/Wind Harmer
2.261
960081AF2-299 GEN
Solar/Wind Harmer
2.773
970659AG2-427 GEN
Solar/Wind Harmer
13.092
3146516WINFALL
Solar/Wind Harmer
-0.079
3146516WINFALL
Solar/Wind Harmer
-0.025
315800Z1-036_GEN1
Solar/Wind Harmer
6.037
3130156CHOWAN
Solar/Wind Harmer
-0.024
971795AH1-408 GEN
Solar/Wind Harmer
18.192
316072AD1-144
Solar/Wind Harmer
0.491
315687AD1-152 GEN
Solar/Wind Harmer
2.916
3147043LAWRENC
Adder
1.939
3145663CRESWEL
Solar/Wind Harmer
-0.067
971163AH1-040 GEN
Solar/Wind Harmer
22.53
316011AB1-132 GEN
Solar/Wind Harmer
5.02
962571AG1-106 GEN
Solar/Wind Harmer
3.449
3145893MURPHYS
Solar/Wind Harmer
-0.095
3145893MURPHYS
Solar/Wind Harmer
0.709
3146173TUNIS
Solar/Wind Harmer
-0.024
316190AA2-174 GEN
Solar/Wind Harmer
0.292
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
5.931
3145336SMITFLD
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.078
3145796HORNRTN
Solar/Wind Harmer
-0.024
3150851SPRUNCC
Adder
0.97
3146263WOODLND
Solar/Wind Harmer
-0.024
3145783HORNRTN
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
316129AC1-054 GEN
Solar/Wind Harmer
2.052
971065AG2-659 GEN
Solar/Wind Harmer
11.686
3145823KELFORD
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
316174AB2-169 GEN
Solar/Wind Harmer
3.546
3151171GRAVELC
Adder
2.174
316212AC1-099_GEN
Solar/Wind Harmer
2
315671AE2-027_GEN
Solar/Wind Harmer
17.142
316237AB2-079_GEN
Solar/Wind Harmer
0.685
961611AG1-000B GEN
Solar/Wind Harmer
11.194
315722AD1-056 GEN
Solar/Wind Harmer
2.367
3146293MARTNCO
Solar/Wind Harmer
0.139
971647AH1-324 GEN
Solar/Wind Harmer
11.229
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
316494AC1-189 GEN
Solar/Wind Harmer
2.377
3146233WITAKRS
Solar/Wind Harmer
-0.087
971069AG2-661 GEN
Solar/Wind Harmer
3.491
961671AG1-007 GEN
Solar/Wind Harmer
0.278
3146083TARBORO
Solar/Wind Harmer
-0.022
3145493TOT1
Solar/Wind Harmer
0.651
970685AG2-442 GEN
Solar/Wind Harmer
19.204
3144293JTRSVLE
Adder
0.615
3143096IRON208
Adder
0.735
944631AF1-128 GEN
Adder
81.311
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3141843SHACKLE
Adder
0.766
3150351NORNECKC2
Adder
1.153
316045AC1-158 PL2
Solar/Wind Helper
5.205
3147666LOUISA
Solar/Wind Helper
0.977
316192AB2-158 GEN
Solar/Wind Helper
1.608
CPLELTFEXP_CPLE->PJM
CLTF
13.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.637
LAGNLTFEXP_LAGN->PJM
CLTF
9.063
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.182
TVALTFEXP_TVA->PJM
CLTF
4.543
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.006
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.545
MECLTFEXP_MEC->PJM
CLTF
4.353
SIGELTFEXP_SIGE->PJM
CLTF
0.131
NYPJM->LTFIMP_NY
CLTF
2.393
LGEELTFEXP_LGEE->PJM
CLTF
1.582
WECLTFEXP_WEC->PJM
CLTF
0.806

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P2-2: NORTH ANNA B2_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: NORTH ANNA B2_SRT-S
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:126.92 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:3957.44
MW Contribution:21.55
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
5.424
315244AE2-183_ST
50/50
7.889
963041AG1-153 GEN
50/50
7.262
315779AE2-040
50/50
3.426
3151541CLOVER2
50/50
4.914
941031AE2-094 GEN
Solar/Wind Harmer
60.059
944011AF1-069 GEN
Solar/Wind Harmer
18.818
970673AG2-436 GEN
Solar/Wind Harmer
65.906
970673AG2-436 GEN
Solar/Wind Harmer
33.37
971967AH1-528 GEN
Solar/Wind Harmer
57.904
970085AG2-068 GEN
Solar/Wind Harmer
18.255
970581AG2-369 GEN
Solar/Wind Harmer
15.699
316233AE1-074 FULL
Solar/Wind Harmer
0.785
971281AH1-106 GEN
Solar/Wind Harmer
4.743
971283AH1-107 GEN
Solar/Wind Harmer
4.743
3151031BRUNSWICKG2
50/50
3.586
970413AG2-270 GEN
50/50
21.547
3151101ELIZAR3
50/50
21.88
970917AG2-570 GEN
Solar/Wind Harmer
73.368
316313AB2-026
Solar/Wind Harmer
0.722
316258AE1-075 C
Solar/Wind Harmer
0.65
316405AF2-144 C
Solar/Wind Harmer
0.686
3143336POWHATN
Solar/Wind Harmer
2.702
316478AD1-087 GEN
Solar/Wind Harmer
2.243
316486AD2-202 GEN
Solar/Wind Harmer
0.657
316365GEN2_N
Solar/Wind Harmer
1.702
944581AF1-123 GEN
Solar/Wind Harmer
114.775
944601AF1-125 GEN
Solar/Wind Harmer
112.984
315773AC2-141 GEN
Solar/Wind Harmer
10.519
3146456SLIGO L269
Solar/Wind Harmer
-0.025
971153AH1-033 GEN
Solar/Wind Harmer
3.039
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316320Y1-086
Solar/Wind Harmer
1.453
970661AG2-428 GEN
Solar/Wind Harmer
4.646
316435W1029_GEN3
Solar/Wind Harmer
4.466
316083AB2-161 GEN
Solar/Wind Harmer
4.001
966621AG1-532 GEN
Solar/Wind Harmer
0.5
970659AG2-427 GEN
Solar/Wind Harmer
2.32
3146516WINFALL
Solar/Wind Harmer
-0.025
315813AE1-149 C
Solar/Wind Harmer
15.377
3144536CHRHLND
Solar/Wind Harmer
-0.004
3145273HOLLAND
Solar/Wind Harmer
-0.018
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146376EDENTON
Solar/Wind Harmer
-0.024
313506AB2-031 GEN
Solar/Wind Harmer
1.948
3156081AA2-088 GEN
Solar/Wind Harmer
7.818
3147043LAWRENC
Solar/Wind Harmer
-0.014
315614AA2-178 GEN
Solar/Wind Harmer
2.593
970533AG2-339 GEN
50/50
25.341
970531AG2-338 GEN
50/50
10.136
315242AE2-183_GT2
50/50
4.563
315241AE2-183_GT1
50/50
4.535
972185AH1-677 GEN
50/50
16.45
3151041BRUNSWICKG3
50/50
3.586
972187AH1-678 GEN
50/50
8.23
971223AH1-071 GEN
Solar/Wind Harmer
4.285
970933AG2-581 GEN
Solar/Wind Harmer
27.922
3143526WINTERP
Solar/Wind Harmer
-0.151
3144356SAPONY
Solar/Wind Harmer
0.962
970099AG2-077 GEN
Solar/Wind Harmer
33.984
316185AD1-033 GEN
Solar/Wind Harmer
2.641
3145506HICKORY
Solar/Wind Harmer
-0.1
3145506HICKORY
Solar/Wind Harmer
-0.06
3145506HICKORY
Solar/Wind Harmer
-0.015
3142956BIRDNECK
Solar/Wind Harmer
1.34
316316AC1-027 C
Solar/Wind Harmer
0.766
316339AD2-160 GEN
Solar/Wind Harmer
1.684
316018AA1-139 ULT2
Solar/Wind Harmer
2.138
316017AA1-139 ULT1
Solar/Wind Harmer
2.02
3137176SLIGO L2192
Solar/Wind Harmer
-0.099
3146456SLIGO L269
Solar/Wind Harmer
2.944
316036AC1-147 C
Solar/Wind Harmer
0.672
3130086AYDLETT
Solar/Wind Harmer
-0.099
3150991CHESPKB
Adder
2.322
3150991CHESPKB
Adder
2.266
3146386ELIZ CT
Solar/Wind Harmer
-0.025
970657AG2-426 GEN
Solar/Wind Harmer
7.706
970657AG2-426 GEN
Solar/Wind Harmer
1.611
316431W1029_GEN1
Solar/Wind Harmer
4.466
316433W1029_GEN2
Solar/Wind Harmer
4.466
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146626S HERTFORD
Solar/Wind Harmer
-0.024
315742AE1-103 GEN
Solar/Wind Harmer
2.557
3146376EDENTON
Solar/Wind Harmer
0.721
3146376EDENTON
Solar/Wind Harmer
0.721
316181AB2-040 GEN
Solar/Wind Harmer
3.381
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145893MURPHYS
Solar/Wind Harmer
0.667
3145893MURPHYS
Solar/Wind Harmer
-0.043
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
966811AG1-552 GEN
Solar/Wind Harmer
2.675
3145593CAROLNA
Solar/Wind Harmer
0.198
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
316065AD1-022 GEN
Solar/Wind Harmer
11.875
316426AA2-053 GEN
Solar/Wind Harmer
2.399
316236AE1-162_GEN
Solar/Wind Harmer
0.715
316315AB2-025 C
Solar/Wind Harmer
0.744
315814AE2-033 C
Solar/Wind Harmer
25.573
3143316POE
Solar/Wind Harmer
-0.102
957871AF2-081 GEN
Solar/Wind Harmer
12.48
3151081ELIZAR1
Adder
20.359
3151091ELIZAR2
Adder
20.005
319010AE1-072 C
Solar/Wind Harmer
5.041
3146406KITTY HAWK
Solar/Wind Harmer
0.021
3152611GOSPORTB
Adder
2.823
3152621GOSPORTC
Adder
2.396
3152601GOSPORTA
Adder
2.21
316305AF2-043 C
Solar/Wind Harmer
0.749
313526AB2-022
Solar/Wind Harmer
0.669
315835AF2-110_GEN
Solar/Wind Harmer
3.096
316321Z2-027
Solar/Wind Harmer
0.667
3146396TANGLEW
Solar/Wind Harmer
0.455
3145176PASQUOTANK
Solar/Wind Harmer
-0.015
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
316311AC2-079 GEN
Solar/Wind Harmer
12.471
315833AF1-017_GEN
Solar/Wind Harmer
4.696
316349AD2-085 GEN
Solar/Wind Harmer
2.199
946281AF1-292 GEN
Solar/Wind Harmer
0.552
315611Z1-036_GEN2
Solar/Wind Harmer
6.037
316087AB2-174 GEN
Solar/Wind Harmer
3.475
3130156CHOWAN
Solar/Wind Harmer
-0.024
3130156CHOWAN
Solar/Wind Harmer
-0.024
965291AG1-394 GEN
Solar/Wind Harmer
2.135
315816AE2-034 GEN
Solar/Wind Harmer
1.945
315652AC1-086 GEN
Solar/Wind Harmer
26.995
3137643SOCKMAN
Solar/Wind Harmer
-0.095
316318V4-068
Solar/Wind Harmer
0.596
3145893MURPHYS
Solar/Wind Harmer
-0.064
3145893MURPHYS
Solar/Wind Harmer
-0.024
3146043SEABORD
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.413
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.813
315733AD1-074 GEN2
Solar/Wind Harmer
4.813
315735AD1-075 GEN1
Solar/Wind Harmer
2.407
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.379
3145513AHOSKIE
Solar/Wind Harmer
0.206
961941AG1-037 GEN
Solar/Wind Harmer
0.178
3145513AHOSKIE
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.075
3145796HORNRTN
Solar/Wind Harmer
-0.009
971285AH1-108 GEN
Adder
1.587
3145796HORNRTN
Solar/Wind Harmer
-0.071
971741AH1-377 GEN
Solar/Wind Harmer
27.515
3145783HORNRTN
Solar/Wind Harmer
2.805
3145783HORNRTN
Solar/Wind Harmer
2.244
3145783HORNRTN
Solar/Wind Harmer
0.701
3145783HORNRTN
Solar/Wind Harmer
0.281
939181AE1-148 GEN
Solar/Wind Harmer
13.009
970301AG2-198 GEN
Solar/Wind Harmer
11.463
316274AC1-208 GEN
Solar/Wind Harmer
2.472
313527AB2-043 GEN
Solar/Wind Harmer
3.699
316240AF1-291 C
Solar/Wind Harmer
0.679
3145933PARMELE
Solar/Wind Harmer
-0.045
3145933PARMELE
Solar/Wind Harmer
-0.022
316033AB2-134 GEN
Solar/Wind Harmer
7.172
315697AD1-025 GEN
Solar/Wind Harmer
4.498
970323AG2-213 GEN
Solar/Wind Harmer
11.1
971775AH1-396 GEN
Solar/Wind Harmer
1.581
316034AC1-036 C
Solar/Wind Harmer
0.412
944641AF1-129 GEN
Adder
93.824
962561AG1-105 GEN
Solar/Wind Harmer
12.386
3145493TOT1
Solar/Wind Harmer
0.34
3145453TOT5
Solar/Wind Harmer
0.204
3145603CNETO
Solar/Wind Harmer
0.136
3144293JTRSVLE
Adder
0.615
3144293JTRSVLE
Adder
0.518
3142366NRTHEST
Adder
0.505
3150691DARBY 3
Adder
10.955
3150701DARBY 4
Adder
10.93
3150681DARBY 2
Adder
10.917
3150671DARBY 1
Adder
10.904
3142296MT RD221
Adder
0.39
3150341NORNECKC1
Adder
1.211
3150341NORNECKC1
Adder
1.201
316447AC1-158 HLD
Solar/Wind Helper
3.579
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
0.167
3145893MURPHYS
Solar/Wind Harmer
-0.024
315839AE2-212 C
Solar/Wind Harmer
0.72
957521AF2-046 GEN
Solar/Wind Harmer
18.794
961681AG1-008 GEN
Solar/Wind Harmer
18.794
971157AH1-035 GEN
Solar/Wind Harmer
2.979
315737AD1-076 GEN
Solar/Wind Harmer
4.523
3146173TUNIS
Solar/Wind Harmer
-0.024
3146206CASHIE
Solar/Wind Harmer
-0.024
3145336SMITFLD
Solar/Wind Harmer
-0.009
316463AE2-346 GEN
Solar/Wind Harmer
0.383
316140AB2-099
Solar/Wind Harmer
0.16
962331AG1-082 GEN
Solar/Wind Harmer
2.96
3145796HORNRTN
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.024
3150861SPRUNCD
Adder
0.97
3146263WOODLND
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.182
316317KELFORD C
Solar/Wind Harmer
1.101
3145823KELFORD
Solar/Wind Harmer
-0.023
965281AG1-393 GEN
Solar/Wind Harmer
2.906
3145963POPLR C
Solar/Wind Harmer
-0.023
3151221GRAVEL6
Adder
14.86
3151171GRAVELC
Adder
2.859
316210AC1-098 GEN
Solar/Wind Harmer
3.599
970909AG2-566 GEN
Solar/Wind Harmer
2.177
316131AB2-060 GEN
Solar/Wind Harmer
2.453
961611AG1-000B GEN
Solar/Wind Harmer
4.776
315724AD1-057 GEN
Solar/Wind Harmer
1.302
964241AG1-285 GEN
Solar/Wind Harmer
17.632
3145933PARMELE
Solar/Wind Harmer
-0.022
966801AG1-551 GEN
Solar/Wind Harmer
2.814
316327AA2-057 GEN
Solar/Wind Harmer
2.261
315785AD2-033 C
Solar/Wind Harmer
5.054
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
970257AG2-171 GEN
Solar/Wind Harmer
8.325
971445AH1-216 GEN
Solar/Wind Harmer
14.632
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
970831AG2-522 GEN
Solar/Wind Harmer
11.72
3146033SCOT NK
Solar/Wind Harmer
-0.092
972265AH1-717 GEN
Adder
15.87
3151201GRAVEL4
Adder
14.877
3151191GRAVEL3
Adder
14.689
3151211GRAVEL5
Adder
14.689
316239AB2-077_GEN
Solar/Wind Harmer
0.685
316238AB2-078_GEN
Solar/Wind Harmer
0.685
316005AA1-067
Solar/Wind Harmer
0.45
3145746EVERETS
Solar/Wind Harmer
-0.088
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
970181AG2-120 GEN
Solar/Wind Harmer
2.92
316369SG1_INVT
Solar/Wind Harmer
3.973
971443AH1-215 GEN
Solar/Wind Harmer
4.375
3144303KENBRDG
Solar/Wind Harmer
-0.018
957861AF2-080 GEN
Solar/Wind Harmer
9.664
316319Z2-044 C
Solar/Wind Harmer
1.22
316420AA1-050 GEN
Solar/Wind Harmer
2.514
3145573BETHELC
Solar/Wind Harmer
-0.022
3145573BETHELC
Solar/Wind Harmer
-0.022
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
972205AH1-687 GEN
Adder
5.897
970683AG2-441 GEN
Solar/Wind Harmer
6.68
970681AG2-440 GEN
Solar/Wind Harmer
5.344
970119AG2-088 GEN
50/50
40.684
315243AE2-183_GT3
50/50
4.563
3151051BRUNSWICKS1
50/50
7.443
3151021BRUNSWICKG1
50/50
3.586
971451AH1-221 GEN
50/50
10.893
3151531CLOVER1
50/50
4.938
3143226MDLTHAN
Solar/Wind Harmer
-0.034
940641AE2-051 GEN
Solar/Wind Harmer
29.852
939411AE1-173 GEN
Solar/Wind Harmer
150.731
970919AG2-571 GEN
Solar/Wind Harmer
9.287
970087AG2-069 GEN
Solar/Wind Harmer
27.383
3143526WINTERP
Solar/Wind Harmer
-0.151
957481AF2-042 GEN
Solar/Wind Harmer
84.959
3143336POWHATN
Solar/Wind Harmer
3.179
315693AD1-088 GEN
Solar/Wind Harmer
13.081
962491AG1-098 GEN
Solar/Wind Harmer
17.384
316023GEN1_S
Solar/Wind Harmer
1.702
944591AF1-124 GEN
Solar/Wind Harmer
115.189
316294AC1-161 GEN
Solar/Wind Harmer
8.133
316388AE2-253 GEN
Solar/Wind Harmer
1.684
3146456SLIGO L269
Solar/Wind Harmer
-0.025
316375AC2-012 GEN
Solar/Wind Harmer
8.62
3150981CHESPKA
Adder
2.768
316246AF1-032 C
Solar/Wind Harmer
0.503
316336AC2-165 C
Solar/Wind Harmer
4.313
316093AE2-104_GEN
Solar/Wind Harmer
7.202
970661AG2-428 GEN
Solar/Wind Harmer
26.214
316381AD1-082 GEN
Solar/Wind Harmer
2.261
960081AF2-299 GEN
Solar/Wind Harmer
2.773
970659AG2-427 GEN
Solar/Wind Harmer
13.092
3146516WINFALL
Solar/Wind Harmer
-0.079
3146516WINFALL
Solar/Wind Harmer
-0.025
315800Z1-036_GEN1
Solar/Wind Harmer
6.037
3130156CHOWAN
Solar/Wind Harmer
-0.024
971795AH1-408 GEN
Solar/Wind Harmer
18.192
316072AD1-144
Solar/Wind Harmer
0.491
315687AD1-152 GEN
Solar/Wind Harmer
2.916
3147043LAWRENC
Adder
1.939
3145663CRESWEL
Solar/Wind Harmer
-0.067
971163AH1-040 GEN
Solar/Wind Harmer
22.53
316011AB1-132 GEN
Solar/Wind Harmer
5.02
962571AG1-106 GEN
Solar/Wind Harmer
3.449
3145893MURPHYS
Solar/Wind Harmer
-0.095
3145893MURPHYS
Solar/Wind Harmer
0.709
3146173TUNIS
Solar/Wind Harmer
-0.024
316190AA2-174 GEN
Solar/Wind Harmer
0.292
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
5.931
3145336SMITFLD
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.078
3145796HORNRTN
Solar/Wind Harmer
-0.024
3150851SPRUNCC
Adder
0.97
3146263WOODLND
Solar/Wind Harmer
-0.024
3145783HORNRTN
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
316129AC1-054 GEN
Solar/Wind Harmer
2.052
971065AG2-659 GEN
Solar/Wind Harmer
11.686
3145823KELFORD
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
316174AB2-169 GEN
Solar/Wind Harmer
3.546
3151171GRAVELC
Adder
2.174
316212AC1-099_GEN
Solar/Wind Harmer
2
315671AE2-027_GEN
Solar/Wind Harmer
17.142
316237AB2-079_GEN
Solar/Wind Harmer
0.685
961611AG1-000B GEN
Solar/Wind Harmer
11.194
315722AD1-056 GEN
Solar/Wind Harmer
2.367
3146293MARTNCO
Solar/Wind Harmer
0.139
971647AH1-324 GEN
Solar/Wind Harmer
11.229
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
316494AC1-189 GEN
Solar/Wind Harmer
2.377
3146233WITAKRS
Solar/Wind Harmer
-0.087
971069AG2-661 GEN
Solar/Wind Harmer
3.491
961671AG1-007 GEN
Solar/Wind Harmer
0.278
3146083TARBORO
Solar/Wind Harmer
-0.022
3145493TOT1
Solar/Wind Harmer
0.651
970685AG2-442 GEN
Solar/Wind Harmer
19.204
3144293JTRSVLE
Adder
0.615
3143096IRON208
Adder
0.735
944631AF1-128 GEN
Adder
81.311
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3141843SHACKLE
Adder
0.766
3150351NORNECKC2
Adder
1.153
316045AC1-158 PL2
Solar/Wind Helper
5.205
3147666LOUISA
Solar/Wind Helper
0.977
316192AB2-158 GEN
Solar/Wind Helper
1.608
959311AF2-222 GEN
Solar/Wind Harmer
23.096
3146233WITAKRS
Solar/Wind Harmer
0.462
3146233WITAKRS
Solar/Wind Harmer
-0.015
315778AD1-151 GEN
Solar/Wind Harmer
19.113
3138543CONSLDL
Solar/Wind Harmer
-0.014
3146073TAR RVR
Solar/Wind Harmer
-0.022
3146083TARBORO
Solar/Wind Harmer
-0.022
3144293JTRSVLE
Adder
0.615
3144216WINCHST
Adder
0.716
3150921YORKTN3
Adder
4.712
3143096IRON208
Adder
0.735
3143096IRON208
Adder
0.72
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3141843SHACKLE
Adder
0.766
3150351NORNECKC2
Adder
1.172
316044AC1-158 PL1
Solar/Wind Helper
1.626
316450AC1-158 RIC
Solar/Wind Helper
0.434
3147666LOUISA
Solar/Wind Helper
0.562
CPLELTFEXP_CPLE->PJM
CLTF
13.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.637
LAGNLTFEXP_LAGN->PJM
CLTF
9.063
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.182
TVALTFEXP_TVA->PJM
CLTF
4.543
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.006
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.545
MECLTFEXP_MEC->PJM
CLTF
4.353
SIGELTFEXP_SIGE->PJM
CLTF
0.131
NYPJM->LTFIMP_NY
CLTF
2.393
LGEELTFEXP_LGEE->PJM
CLTF
1.582
WECLTFEXP_WEC->PJM
CLTF
0.806

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.6 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3883.86
MW Contribution:23.56
Bus #Bus NameTypeMW Contribution
970119AG2-088 GEN
50/50
43.519
315243AE2-183_GT3
50/50
4.781
3151051BRUNSWICKS1
50/50
7.81
3151021BRUNSWICKG1
50/50
3.763
971451AH1-221 GEN
50/50
11.429
3151531CLOVER1
50/50
5.398
3151931BEARGRDN S1
50/50
2.955
3151911BEARGRDN G1
50/50
2.289
3144293JTRSVLE
50/50
0.81
3147043LAWRENC
50/50
2.239
3143226MDLTHAN
Solar/Wind Harmer
0.326
940641AE2-051 GEN
Solar/Wind Harmer
23.615
3143336POWHATN
Solar/Wind Harmer
5.234
316336AC2-165 C
Solar/Wind Harmer
0.011
939411AE1-173 GEN
Solar/Wind Harmer
119.354
3143526WINTERP
Solar/Wind Harmer
1.442
970919AG2-571 GEN
Solar/Wind Harmer
9.749
970087AG2-069 GEN
Solar/Wind Harmer
21.832
970937AG2-583 GEN
Solar/Wind Harmer
16.225
957481AF2-042 GEN
Solar/Wind Harmer
70.207
315693AD1-088 GEN
Solar/Wind Harmer
12.471
962491AG1-098 GEN
Solar/Wind Harmer
14.811
3146926FARMVIL
Solar/Wind Harmer
0.15
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.099
972003AH1-546 GEN
Solar/Wind Harmer
10.482
963171AG1-166 GEN
Solar/Wind Harmer
1.279
971563AH1-280 GEN
Solar/Wind Harmer
2.558
970685AG2-442 GEN
Solar/Wind Harmer
17.749
316023GEN1_S
Solar/Wind Harmer
0.533
944591AF1-124 GEN
Solar/Wind Harmer
53.071
315687AD1-152 GEN
Solar/Wind Harmer
0.008
960081AF2-299 GEN
Solar/Wind Harmer
2.251
316294AC1-161 GEN
Solar/Wind Harmer
4.051
971795AH1-408 GEN
Solar/Wind Harmer
15.577
316388AE2-253 GEN
Solar/Wind Harmer
0.729
3146456SLIGO L269
Solar/Wind Harmer
0.232
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.896
316246AF1-032 C
Solar/Wind Harmer
0.104
316093AE2-104_GEN
Solar/Wind Harmer
3.887
970661AG2-428 GEN
Solar/Wind Harmer
22.918
316381AD1-082 GEN
Solar/Wind Harmer
0.24
970659AG2-427 GEN
Solar/Wind Harmer
11.132
3146516WINFALL
Solar/Wind Harmer
0.744
3146516WINFALL
Solar/Wind Harmer
0.23
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
971065AG2-659 GEN
Solar/Wind Harmer
9.695
316129AC1-054 GEN
Solar/Wind Harmer
0.854
3130156CHOWAN
Solar/Wind Harmer
0.227
316072AD1-144
Solar/Wind Harmer
0.082
316011AB1-132 GEN
Solar/Wind Harmer
4.107
962571AG1-106 GEN
Solar/Wind Harmer
3.214
3145893MURPHYS
Solar/Wind Harmer
0.9
3145893MURPHYS
Solar/Wind Harmer
1
316190AA2-174 GEN
Solar/Wind Harmer
0
3145663CRESWEL
Solar/Wind Harmer
0.629
971163AH1-040 GEN
Solar/Wind Harmer
17.982
3145783HORNRTN
Solar/Wind Harmer
0.224
3150851SPRUNCC
Adder
1.032
3146173TUNIS
Solar/Wind Harmer
0.223
3146263WOODLND
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.735
3145796HORNRTN
Solar/Wind Harmer
0.223
3146206CASHIE
Solar/Wind Harmer
0.222
971547AH1-271 GEN
Solar/Wind Harmer
4.743
3145683EARLEYS
Solar/Wind Harmer
0.222
3145336SMITFLD
Solar/Wind Harmer
0.885
971377AH1-170 GEN
Solar/Wind Harmer
2.354
3147623JAMES R
Solar/Wind Harmer
0.511
3145823KELFORD
Solar/Wind Harmer
0.22
970401AG2-262 GEN
Solar/Wind Harmer
1.273
3145963POPLR C
Solar/Wind Harmer
0.217
316212AC1-099_GEN
Solar/Wind Harmer
1.12
316174AB2-169 GEN
Solar/Wind Harmer
0.006
3151171GRAVELC
Adder
2.282
315671AE2-027_GEN
Solar/Wind Harmer
13.709
315722AD1-056 GEN
Solar/Wind Harmer
1.349
961611AG1-000B GEN
Solar/Wind Harmer
11.12
3146293MARTNCO
Solar/Wind Harmer
0.196
971647AH1-324 GEN
Solar/Wind Harmer
8.963
3145746EVERETS
Solar/Wind Harmer
0.209
3145746EVERETS
Solar/Wind Harmer
0.209
3146233WITAKRS
Solar/Wind Harmer
0.828
316494AC1-189 GEN
Solar/Wind Harmer
0.701
971069AG2-661 GEN
Solar/Wind Harmer
3.673
961671AG1-007 GEN
Solar/Wind Harmer
0.032
3146083TARBORO
Solar/Wind Harmer
0.206
3145493TOT1
Solar/Wind Harmer
0.918
3145543BTLEBRO
Solar/Wind Harmer
0.205
3145543BTLEBRO
Solar/Wind Harmer
0.164
316359AB2-059 GEN
Solar/Wind Harmer
0.737
316049AB1-081 GEN
Solar/Wind Harmer
1.174
3142053HEARTS
Solar/Wind Harmer
0.361
316458AB2-190 GEN2
Solar/Wind Harmer
1.096
970129AG2-093 GEN
Solar/Wind Harmer
5.802
3138126ROCKLANDING
Solar/Wind Harmer
0.091
3142543TWELFTH
Solar/Wind Harmer
0.019
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971317AH1-138 GEN
Solar/Wind Harmer
1.404
3143096IRON208
Adder
0.78
316159AE1-175 C
Solar/Wind Harmer
0.157
944631AF1-128 GEN
Adder
85.999
3142433PROV 92
Solar/Wind Harmer
0.665
3142433PROV 92
Adder
0.323
3142433PROV 92
Adder
0.323
971777AH1-397 GEN
Solar/Wind Harmer
0.418
3141843SHACKLE
Adder
0.808
3141766HARMONY
Solar/Wind Harmer
0.031
3138133OCRAN
Solar/Wind Harmer
0.091
3142416OLDCHRC
Solar/Wind Harmer
0.353
3142416OLDCHRC
Solar/Wind Harmer
0.135
962861AG1-135 GEN
Solar/Wind Harmer
4.302
3141726DUNNSVL
Solar/Wind Harmer
0.503
3150351NORNECKC2
Adder
1.223
970223AG2-152 GEN
Solar/Wind Harmer
8.356
270016AE1-250 BESS
Solar/Wind Harmer
0.003
316045AC1-158 PL2
Solar/Wind Helper
5.212
3147666LOUISA
Solar/Wind Helper
1.082
316192AB2-158 GEN
Solar/Wind Helper
1.792
316303AF2-085
50/50
5.802
315244AE2-183_ST
50/50
8.266
963041AG1-153 GEN
50/50
7.619
315779AE2-040
50/50
3.595
3151541CLOVER2
50/50
5.372
972205AH1-687 GEN
50/50
11.166
941031AE2-094 GEN
Solar/Wind Harmer
54.858
944011AF1-069 GEN
Solar/Wind Harmer
17.924
970673AG2-436 GEN
Solar/Wind Harmer
62.352
970673AG2-436 GEN
Solar/Wind Harmer
41.568
971967AH1-528 GEN
Solar/Wind Harmer
46.206
316233AE1-074 FULL
Solar/Wind Harmer
0.222
971281AH1-106 GEN
Solar/Wind Harmer
3.848
971283AH1-107 GEN
Solar/Wind Harmer
3.848
970085AG2-068 GEN
Solar/Wind Harmer
14.555
970581AG2-369 GEN
Solar/Wind Harmer
12.517
316315AB2-025 C
Solar/Wind Harmer
0.208
315814AE2-033 C
Solar/Wind Harmer
20.297
970285AG2-188 GEN
Solar/Wind Harmer
19.688
971845AH1-439 GEN
Solar/Wind Harmer
11.269
3143316POE
Solar/Wind Harmer
0.959
315657AE1-056 GEN
Solar/Wind Harmer
8.322
946301AF1-294 GEN
Solar/Wind Harmer
4.733
961791AG1-021 GEN
Solar/Wind Harmer
2.302
970683AG2-441 GEN
Solar/Wind Harmer
15.848
970681AG2-440 GEN
Solar/Wind Harmer
12.678
3144303KENBRDG
Solar/Wind Harmer
0.188
971443AH1-215 GEN
Solar/Wind Harmer
3.953
957871AF2-081 GEN
Solar/Wind Harmer
11.576
3151081ELIZAR1
Adder
21.303
3151091ELIZAR2
Adder
20.933
319010AE1-072 C
Solar/Wind Harmer
1.169
3146406KITTY HAWK
Solar/Wind Harmer
0.029
3152611GOSPORTB
Adder
2.955
3152621GOSPORTC
Adder
2.507
3152601GOSPORTA
Adder
2.313
316305AF2-043 C
Solar/Wind Harmer
0.002
316087AB2-174 GEN
Solar/Wind Harmer
0.007
313526AB2-022
Solar/Wind Harmer
0.125
315835AF2-110_GEN
Solar/Wind Harmer
1.586
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.158
316311AC2-079 GEN
Solar/Wind Harmer
6.627
316321Z2-027
Solar/Wind Harmer
0.043
3146396TANGLEW
Solar/Wind Harmer
0.636
3145176PASQUOTANK
Solar/Wind Harmer
0.143
3146486SUNBURY
Solar/Wind Harmer
0.23
3146486SUNBURY
Solar/Wind Harmer
0.23
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.91
3130156CHOWAN
Solar/Wind Harmer
0.227
3130156CHOWAN
Solar/Wind Harmer
0.227
970831AG2-522 GEN
Solar/Wind Harmer
9.684
965291AG1-394 GEN
Solar/Wind Harmer
1.007
3146043SEABORD
Solar/Wind Harmer
0.226
315607AA1-063A GEN
Solar/Wind Harmer
0.462
315652AC1-086 GEN
Solar/Wind Harmer
24.846
3145893MURPHYS
Solar/Wind Harmer
0.607
3145893MURPHYS
Solar/Wind Harmer
0.225
315816AE2-034 GEN
Solar/Wind Harmer
0.965
971285AH1-108 GEN
Adder
1.688
3130546PLYMOUTH
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.713
3145796HORNRTN
Solar/Wind Harmer
0.089
315732AD1-074 GEN1
Solar/Wind Harmer
1.28
315733AD1-074 GEN2
Solar/Wind Harmer
1.28
315735AD1-075 GEN1
Solar/Wind Harmer
0.641
3145513AHOSKIE
Solar/Wind Harmer
0.466
3145513AHOSKIE
Solar/Wind Harmer
0.222
3146206CASHIE
Solar/Wind Harmer
0.222
970601AG2-382 GEN
Solar/Wind Harmer
8.299
3145683EARLEYS
Solar/Wind Harmer
0.444
3145683EARLEYS
Solar/Wind Harmer
0.222
3145683EARLEYS
Solar/Wind Harmer
0.222
971445AH1-216 GEN
Solar/Wind Harmer
15.534
3146033SCOT NK
Solar/Wind Harmer
0.871
972265AH1-717 GEN
Adder
16.655
3151201GRAVEL4
Adder
15.613
3151191GRAVEL3
Adder
15.416
3151211GRAVEL5
Adder
15.416
316118AC1-105 GEN
Solar/Wind Harmer
0.547
316005AA1-067
Solar/Wind Harmer
0.224
3145746EVERETS
Solar/Wind Harmer
0.831
3145746EVERETS
Solar/Wind Harmer
0.209
3145746EVERETS
Solar/Wind Harmer
0.209
3145746EVERETS
Solar/Wind Harmer
0.209
970181AG2-120 GEN
Solar/Wind Harmer
2.6
316319Z2-044 C
Solar/Wind Harmer
0
316369SG1_INVT
Solar/Wind Harmer
0.008
957861AF2-080 GEN
Solar/Wind Harmer
8.95
3147173SINAI
Solar/Wind Harmer
0.207
3147243WELCO
Solar/Wind Harmer
0.129
316420AA1-050 GEN
Solar/Wind Harmer
0.007
3145573BETHELC
Solar/Wind Harmer
0.206
3145573BETHELC
Solar/Wind Harmer
0.206
971447AH1-217 GEN
Solar/Wind Harmer
6.24
316132AB2-190 GEN1
Solar/Wind Harmer
1.096
270494AE1-108_GEN
Solar/Wind Harmer
2.223
970865AG2-541 GEN
Solar/Wind Harmer
6.195
3138283WHITEMARSH
Solar/Wind Harmer
0.041
971167AH1-042 GEN
Solar/Wind Harmer
14.937
3142433PROV 92
Adder
0.323
3142433PROV 92
Adder
0.323
316123AC1-075 GEN
Solar/Wind Harmer
0.219
970165AG2-112 GEN
Solar/Wind Harmer
1.296
970163AG2-111 GEN
Solar/Wind Harmer
1.236
3143873LANEXA
Solar/Wind Harmer
0.095
970189AG2-124 GEN
Solar/Wind Harmer
4.688
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.032
316059AD1-063 C
Solar/Wind Harmer
0.001
316314AB2-024 C
Solar/Wind Harmer
0.001
315976AC1-164 GENA
Solar/Wind Harmer
15.947
316169AC1-164_GENC
Solar/Wind Harmer
13.777
315975AC1-164 GENB
Solar/Wind Harmer
0.472
3141913WHIT STONE
Solar/Wind Harmer
0.152
3138133OCRAN
Solar/Wind Harmer
0.045
3141783LANCAST
Solar/Wind Harmer
0.089
3141783LANCAST
Solar/Wind Harmer
0.059
962981AG1-147 GEN
Solar/Wind Harmer
5.308
970327AG2-215 GEN
Solar/Wind Harmer
4.55
316312AB1-027
Solar/Wind Harmer
0.243
3141813NORNECK
Solar/Wind Harmer
0.123
316164AC1-076 GEN
Solar/Wind Helper
1.102
970533AG2-339 GEN
50/50
26.476
970531AG2-338 GEN
50/50
10.59
315242AE2-183_GT2
50/50
4.781
315241AE2-183_GT1
50/50
4.752
972185AH1-677 GEN
50/50
17.237
3151041BRUNSWICKG3
50/50
3.763
972187AH1-678 GEN
50/50
8.635
3144293JTRSVLE
50/50
0.81
3144293JTRSVLE
50/50
0.682
971223AH1-071 GEN
Solar/Wind Harmer
3.481
970933AG2-581 GEN
Solar/Wind Harmer
22.545
3143526WINTERP
Solar/Wind Harmer
1.442
970099AG2-077 GEN
Solar/Wind Harmer
28.083
3144356SAPONY
Solar/Wind Harmer
2.154
971741AH1-377 GEN
Solar/Wind Harmer
25.35
970301AG2-198 GEN
Solar/Wind Harmer
10.849
3146776BUCKING
Solar/Wind Harmer
0.993
3146776BUCKING
Solar/Wind Harmer
0.08
3147133PAMPLIN
Solar/Wind Harmer
0.241
3147133PAMPLIN
Solar/Wind Harmer
0.193
958211AF2-115 GEN
Solar/Wind Harmer
2.878
963191AG1-168 GEN
Solar/Wind Harmer
0.959
316034AC1-036 C
Solar/Wind Harmer
0.017
970323AG2-213 GEN
Solar/Wind Harmer
10.046
971775AH1-396 GEN
Solar/Wind Harmer
0.377
316185AD1-033 GEN
Solar/Wind Harmer
0.007
3145506HICKORY
Solar/Wind Harmer
0.932
3145506HICKORY
Solar/Wind Harmer
0.559
3145506HICKORY
Solar/Wind Harmer
0.14
3142956BIRDNECK
Solar/Wind Harmer
0
316339AD2-160 GEN
Solar/Wind Harmer
0.377
316316AC1-027 C
Solar/Wind Harmer
0.223
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.13
3137176SLIGO L2192
Solar/Wind Harmer
0.924
3146456SLIGO L269
Solar/Wind Harmer
4.11
3130086AYDLETT
Solar/Wind Harmer
0.928
316036AC1-147 C
Solar/Wind Harmer
0.043
3150991CHESPKB
Adder
2.43
3150991CHESPKB
Adder
2.372
3146386ELIZ CT
Solar/Wind Harmer
0.231
313527AB2-043 GEN
Solar/Wind Harmer
0.003
316181AB2-040 GEN
Solar/Wind Harmer
0.334
970657AG2-426 GEN
Solar/Wind Harmer
8.066
970657AG2-426 GEN
Solar/Wind Harmer
1.691
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.23
3146516WINFALL
Solar/Wind Harmer
0.23
3146516WINFALL
Solar/Wind Harmer
0.23
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146626S HERTFORD
Solar/Wind Harmer
0.229
3146626S HERTFORD
Solar/Wind Harmer
0.229
939181AE1-148 GEN
Solar/Wind Harmer
10.957
3146376EDENTON
Solar/Wind Harmer
1.009
3146376EDENTON
Solar/Wind Harmer
1.009
3145593CAROLNA
Solar/Wind Harmer
0.226
3145593CAROLNA
Solar/Wind Harmer
0.226
966811AG1-552 GEN
Solar/Wind Harmer
2.448
3145593CAROLNA
Solar/Wind Harmer
0.281
3142666NORTHAMPTON
Solar/Wind Harmer
0.225
3142666NORTHAMPTON
Solar/Wind Harmer
0.225
3142666NORTHAMPTON
Solar/Wind Harmer
0.225
3142666NORTHAMPTON
Solar/Wind Harmer
0.135
3145893MURPHYS
Solar/Wind Harmer
1.506
3145893MURPHYS
Solar/Wind Harmer
0.405
316426AA2-053 GEN
Solar/Wind Harmer
0.76
3145783HORNRTN
Solar/Wind Harmer
3.987
3145783HORNRTN
Solar/Wind Harmer
3.19
3145783HORNRTN
Solar/Wind Harmer
0.997
3145783HORNRTN
Solar/Wind Harmer
0.399
3146173TUNIS
Solar/Wind Harmer
0.223
3146173TUNIS
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.668
316065AD1-022 GEN
Solar/Wind Harmer
10.244
316236AE1-162_GEN
Solar/Wind Harmer
0.002
971489AH1-241 GEN
Solar/Wind Harmer
11.769
962561AG1-105 GEN
Solar/Wind Harmer
10.511
964791AG1-342 GEN
Solar/Wind Harmer
4.165
3146843MT LREL
Solar/Wind Harmer
0.217
3146843MT LREL
Solar/Wind Harmer
0.217
316274AC1-208 GEN
Solar/Wind Harmer
1.123
316240AF1-291 C
Solar/Wind Harmer
0.002
3145933PARMELE
Solar/Wind Harmer
0.423
3145933PARMELE
Solar/Wind Harmer
0.211
316033AB2-134 GEN
Solar/Wind Harmer
0.012
315697AD1-025 GEN
Solar/Wind Harmer
0.234
944641AF1-129 GEN
Adder
98.946
3145493TOT1
Solar/Wind Harmer
0.478
3145453TOT5
Solar/Wind Harmer
0.287
3145603CNETO
Solar/Wind Harmer
0.191
316263AC1-034 GEN
Solar/Wind Harmer
7.794
961601AG1-000A GEN
Solar/Wind Harmer
3.645
316222AC1-221 GEN
Solar/Wind Harmer
0.764
3142946ENON
Solar/Wind Harmer
0.017
3142366NRTHEST
Adder
0.536
3150691DARBY 3
Adder
11.633
3150701DARBY 4
Adder
11.606
3150681DARBY 2
Adder
11.592
3150671DARBY 1
Adder
11.579
316075AC2-137 C
Solar/Wind Harmer
0.042
942751AE2-291 GEN
Solar/Wind Harmer
8.048
315821AE2-092 GEN
Solar/Wind Harmer
0.009
958261AF2-120 GEN
Solar/Wind Harmer
4.395
3142296MT RD221
Adder
0.416
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.285
3150341NORNECKC1
Adder
1.275
966871AG1-558 GEN
Solar/Wind Harmer
0.14
270013AE1-250 PV
Solar/Wind Harmer
0.003
316447AC1-158 HLD
Solar/Wind Helper
3.584
3151031BRUNSWICKG2
50/50
3.763
970413AG2-270 GEN
50/50
23.558
3151921BEARGRDN G2
50/50
2.289
3144293JTRSVLE
50/50
0.81
3151101ELIZAR3
50/50
22.894
316313AB2-026
Solar/Wind Harmer
0.186
316258AE1-075 C
Solar/Wind Harmer
0.222
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.449
970917AG2-570 GEN
Solar/Wind Harmer
24.372
970909AG2-566 GEN
Solar/Wind Harmer
2.712
316478AD1-087 GEN
Solar/Wind Harmer
0.88
316486AD2-202 GEN
Solar/Wind Harmer
0.258
3146926FARMVIL
Solar/Wind Harmer
0.15
3146776BUCKING
Solar/Wind Harmer
0.089
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3147133PAMPLIN
Solar/Wind Harmer
0.757
971193AH1-056 GEN
Solar/Wind Harmer
14.693
963181AG1-167 GEN
Solar/Wind Harmer
0.959
316365GEN2_N
Solar/Wind Harmer
0.533
959311AF2-222 GEN
Solar/Wind Harmer
20.988
970257AG2-171 GEN
Solar/Wind Harmer
7.535
944581AF1-123 GEN
Solar/Wind Harmer
52.883
944601AF1-125 GEN
Solar/Wind Harmer
52.068
315785AD2-033 C
Solar/Wind Harmer
1.907
315773AC2-141 GEN
Solar/Wind Harmer
8.54
3147043LAWRENC
Solar/Wind Harmer
0.14
3146456SLIGO L269
Solar/Wind Harmer
0.232
971153AH1-033 GEN
Solar/Wind Harmer
2.685
964241AG1-285 GEN
Solar/Wind Harmer
15.481
3144873MCLAUGH
Solar/Wind Harmer
0.006
316320Y1-086
Solar/Wind Harmer
0.001
316131AB2-060 GEN
Solar/Wind Harmer
0.726
970661AG2-428 GEN
Solar/Wind Harmer
4.875
313506AB2-031 GEN
Solar/Wind Harmer
0.712
316083AB2-161 GEN
Solar/Wind Harmer
0.003
970659AG2-427 GEN
Solar/Wind Harmer
2.435
316435W1029_GEN3
Solar/Wind Harmer
0.001
315813AE1-149 C
Solar/Wind Harmer
12.262
3145273HOLLAND
Solar/Wind Harmer
0.172
3146516WINFALL
Solar/Wind Harmer
0.23
3146626S HERTFORD
Solar/Wind Harmer
0.229
3144536CHRHLND
Solar/Wind Harmer
0.034
3146376EDENTON
Solar/Wind Harmer
0.227
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
3142666NORTHAMPTON
Solar/Wind Harmer
0.225
3145893MURPHYS
Solar/Wind Harmer
0.377
3145893MURPHYS
Solar/Wind Harmer
0.225
315614AA2-178 GEN
Solar/Wind Harmer
1.286
957521AF2-046 GEN
Solar/Wind Harmer
16.712
961681AG1-008 GEN
Solar/Wind Harmer
16.712
3150861SPRUNCD
Adder
1.032
315839AE2-212 C
Solar/Wind Harmer
0.002
3146173TUNIS
Solar/Wind Harmer
0.223
971157AH1-035 GEN
Solar/Wind Harmer
2.677
3146263WOODLND
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.891
3145796HORNRTN
Solar/Wind Harmer
0.223
315737AD1-076 GEN
Solar/Wind Harmer
2.867
316463AE2-346 GEN
Solar/Wind Harmer
0.191
316140AB2-099
Solar/Wind Harmer
0.08
962331AG1-082 GEN
Solar/Wind Harmer
2.375
3146206CASHIE
Solar/Wind Harmer
0.222
3156021HOLLOMANSOL
Solar/Wind Harmer
1.006
3145336SMITFLD
Solar/Wind Harmer
0.089
970221AG2-151 GEN
Solar/Wind Harmer
11.769
316317KELFORD C
Solar/Wind Harmer
0.021
3145823KELFORD
Solar/Wind Harmer
0.22
965281AG1-393 GEN
Solar/Wind Harmer
2.322
3145963POPLR C
Solar/Wind Harmer
0.217
316210AC1-098 GEN
Solar/Wind Harmer
2.008
3151221GRAVEL6
Adder
15.595
3151171GRAVELC
Adder
3
315724AD1-057 GEN
Solar/Wind Harmer
0.8
961611AG1-000B GEN
Solar/Wind Harmer
5.654
3145933PARMELE
Solar/Wind Harmer
0.211
966801AG1-551 GEN
Solar/Wind Harmer
2.462
316327AA2-057 GEN
Solar/Wind Harmer
0.319
3145746EVERETS
Solar/Wind Harmer
0.209
3145746EVERETS
Solar/Wind Harmer
0.209
3146233WITAKRS
Solar/Wind Harmer
1.045
3146233WITAKRS
Solar/Wind Harmer
0.142
3138543CONSLDL
Solar/Wind Harmer
0.137
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
8.839
315778AD1-151 GEN
Solar/Wind Harmer
16.527
3146073TAR RVR
Solar/Wind Harmer
0.206
3146083TARBORO
Solar/Wind Harmer
0.206
3145543BTLEBRO
Solar/Wind Harmer
0.205
3145543BTLEBRO
Solar/Wind Harmer
0.205
971623AH1-311 GEN
Solar/Wind Harmer
0.41
961601AG1-000A GEN
Solar/Wind Harmer
14.582
970129AG2-093 GEN
Solar/Wind Harmer
12.33
970133AG2-095 GEN
Solar/Wind Harmer
1.923
3144216WINCHST
Adder
0.751
3150921YORKTN3
Adder
4.945
971683AH1-343 GEN
Solar/Wind Harmer
6.917
3143096IRON208
Adder
0.78
3143096IRON208
Adder
0.764
316283AC2-100 C
Solar/Wind Harmer
0.358
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.058
3142433PROV 92
Adder
0.323
3142433PROV 92
Adder
0.323
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141843SHACKLE
Adder
0.808
316280AD1-041 GEN
Solar/Wind Harmer
0.003
316156AD2-030 GEN
Solar/Wind Harmer
0.117
3141873WAN 176
Solar/Wind Harmer
2.805
970293AG2-193 GEN
Solar/Wind Harmer
1.678
3141766HARMONY
Solar/Wind Harmer
2.073
962971AG1-146 GEN
Solar/Wind Harmer
2.275
970009AG2-005 GEN
Solar/Wind Harmer
1.035
3142416OLDCHRC
Solar/Wind Harmer
1.315
316404AE1-155 C
Solar/Wind Harmer
0.03
3150351NORNECKC2
Adder
1.244
316473AC1-191 GEN
Solar/Wind Harmer
0.409
316044AC1-158 PL1
Solar/Wind Helper
1.628
316450AC1-158 RIC
Solar/Wind Helper
0.434
3147666LOUISA
Solar/Wind Helper
0.622
CPLELTFEXP_CPLE->PJM
CLTF
13.756
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.673
LAGNLTFEXP_LAGN->PJM
CLTF
9.337
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.604
TVALTFEXP_TVA->PJM
CLTF
4.677
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.765
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.954
MECLTFEXP_MEC->PJM
CLTF
4.387
SIGELTFEXP_SIGE->PJM
CLTF
0.131
NYPJM->LTFIMP_NY
CLTF
2.489
LGEELTFEXP_LGEE->PJM
CLTF
1.579
WECLTFEXP_WEC->PJM
CLTF
0.803

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 9812_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 9812_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.45 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3846.7
MW Contribution:22.19
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
5.642
315244AE2-183_ST
50/50
8.107
963041AG1-153 GEN
50/50
7.463
315779AE2-040
50/50
3.563
3151541CLOVER2
50/50
5.06
941031AE2-094 GEN
Solar/Wind Harmer
53.948
944011AF1-069 GEN
Solar/Wind Harmer
17.627
970673AG2-436 GEN
Solar/Wind Harmer
61.209
970673AG2-436 GEN
Solar/Wind Harmer
40.806
971967AH1-528 GEN
Solar/Wind Harmer
45.08
316233AE1-074 FULL
Solar/Wind Harmer
0.219
971281AH1-106 GEN
Solar/Wind Harmer
3.799
971283AH1-107 GEN
Solar/Wind Harmer
3.799
970085AG2-068 GEN
Solar/Wind Harmer
14.254
970581AG2-369 GEN
Solar/Wind Harmer
12.258
316315AB2-025 C
Solar/Wind Harmer
0.206
315814AE2-033 C
Solar/Wind Harmer
20.108
3143316POE
Solar/Wind Harmer
0.963
3151081ELIZAR1
Adder
21.226
3151091ELIZAR2
Adder
20.858
957871AF2-081 GEN
Solar/Wind Harmer
11.52
3152611GOSPORTB
Adder
2.944
3152621GOSPORTC
Adder
2.499
3152601GOSPORTA
Adder
2.305
319010AE1-072 C
Solar/Wind Harmer
1.164
3146406KITTY HAWK
Solar/Wind Harmer
0.029
316305AF2-043 C
Solar/Wind Harmer
0.002
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.158
316311AC2-079 GEN
Solar/Wind Harmer
6.612
315835AF2-110_GEN
Solar/Wind Harmer
1.578
313526AB2-022
Solar/Wind Harmer
0.124
3146486SUNBURY
Solar/Wind Harmer
0.229
3146486SUNBURY
Solar/Wind Harmer
0.229
316321Z2-027
Solar/Wind Harmer
0.043
3146396TANGLEW
Solar/Wind Harmer
0.632
3145176PASQUOTANK
Solar/Wind Harmer
0.142
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
971285AH1-108 GEN
Adder
1.707
3130156CHOWAN
Solar/Wind Harmer
0.225
3130156CHOWAN
Solar/Wind Harmer
0.225
316087AB2-174 GEN
Solar/Wind Harmer
0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.989
315816AE2-034 GEN
Solar/Wind Harmer
0.955
315652AC1-086 GEN
Solar/Wind Harmer
24.372
3137643SOCKMAN
Solar/Wind Harmer
0.884
3145893MURPHYS
Solar/Wind Harmer
0.597
3145893MURPHYS
Solar/Wind Harmer
0.221
971445AH1-216 GEN
Solar/Wind Harmer
15.561
3146043SEABORD
Solar/Wind Harmer
0.221
3151031BRUNSWICKG2
50/50
3.686
970413AG2-270 GEN
50/50
22.186
3151101ELIZAR3
50/50
22.812
970917AG2-570 GEN
Solar/Wind Harmer
23.868
316313AB2-026
Solar/Wind Harmer
0.156
316258AE1-075 C
Solar/Wind Harmer
0.187
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.749
316478AD1-087 GEN
Solar/Wind Harmer
0.828
316486AD2-202 GEN
Solar/Wind Harmer
0.243
944581AF1-123 GEN
Solar/Wind Harmer
52.645
944601AF1-125 GEN
Solar/Wind Harmer
51.834
316365GEN2_N
Solar/Wind Harmer
0.524
315773AC2-141 GEN
Solar/Wind Harmer
8.503
3144873MCLAUGH
Solar/Wind Harmer
0.006
3146456SLIGO L269
Solar/Wind Harmer
0.231
971153AH1-033 GEN
Solar/Wind Harmer
2.672
315813AE1-149 C
Solar/Wind Harmer
12.323
970659AG2-427 GEN
Solar/Wind Harmer
2.441
316083AB2-161 GEN
Solar/Wind Harmer
0.003
970661AG2-428 GEN
Solar/Wind Harmer
4.879
316320Y1-086
Solar/Wind Harmer
0.001
3144536CHRHLND
Solar/Wind Harmer
0.034
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.228
3145273HOLLAND
Solar/Wind Harmer
0.171
3146626S HERTFORD
Solar/Wind Harmer
0.227
3150861SPRUNCD
Adder
1.043
315839AE2-212 C
Solar/Wind Harmer
0.002
3146376EDENTON
Solar/Wind Harmer
0.225
313506AB2-031 GEN
Solar/Wind Harmer
0.691
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
315614AA2-178 GEN
Solar/Wind Harmer
1.273
3147043LAWRENC
Solar/Wind Harmer
0.133
3145336SMITFLD
Solar/Wind Harmer
0.089
3142666NORTHAMPTON
Solar/Wind Harmer
0.221
3145893MURPHYS
Solar/Wind Harmer
0.37
3145893MURPHYS
Solar/Wind Harmer
0.221
957521AF2-046 GEN
Solar/Wind Harmer
16.422
961681AG1-008 GEN
Solar/Wind Harmer
16.422
965281AG1-393 GEN
Solar/Wind Harmer
2.354
971157AH1-035 GEN
Solar/Wind Harmer
2.647
315737AD1-076 GEN
Solar/Wind Harmer
2.833
3146173TUNIS
Solar/Wind Harmer
0.22
3146206CASHIE
Solar/Wind Harmer
0.219
316463AE2-346 GEN
Solar/Wind Harmer
0.188
316140AB2-099
Solar/Wind Harmer
0.078
962331AG1-082 GEN
Solar/Wind Harmer
2.335
3145796HORNRTN
Solar/Wind Harmer
0.874
3145796HORNRTN
Solar/Wind Harmer
0.218
3146263WOODLND
Solar/Wind Harmer
0.218
3156021HOLLOMANSOL
Solar/Wind Harmer
0.992
970119AG2-088 GEN
50/50
42.315
315243AE2-183_GT3
50/50
4.689
3151051BRUNSWICKS1
50/50
7.65
3151021BRUNSWICKG1
50/50
3.686
971451AH1-221 GEN
50/50
11.195
3151531CLOVER1
50/50
5.084
3143226MDLTHAN
Solar/Wind Harmer
0.317
940641AE2-051 GEN
Solar/Wind Harmer
23.332
939411AE1-173 GEN
Solar/Wind Harmer
118.108
3143526WINTERP
Solar/Wind Harmer
1.424
970919AG2-571 GEN
Solar/Wind Harmer
9.547
970087AG2-069 GEN
Solar/Wind Harmer
21.38
957481AF2-042 GEN
Solar/Wind Harmer
66.41
3143336POWHATN
Solar/Wind Harmer
4.41
315693AD1-088 GEN
Solar/Wind Harmer
11.511
962491AG1-098 GEN
Solar/Wind Harmer
13.599
944591AF1-124 GEN
Solar/Wind Harmer
52.832
316023GEN1_S
Solar/Wind Harmer
0.524
316294AC1-161 GEN
Solar/Wind Harmer
4.034
316388AE2-253 GEN
Solar/Wind Harmer
0.725
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.886
3146456SLIGO L269
Solar/Wind Harmer
0.231
970659AG2-427 GEN
Solar/Wind Harmer
11.161
316381AD1-082 GEN
Solar/Wind Harmer
0.24
970661AG2-428 GEN
Solar/Wind Harmer
22.94
316246AF1-032 C
Solar/Wind Harmer
0.104
316093AE2-104_GEN
Solar/Wind Harmer
3.868
316336AC2-165 C
Solar/Wind Harmer
0.009
3146516WINFALL
Solar/Wind Harmer
0.739
3146516WINFALL
Solar/Wind Harmer
0.228
960081AF2-299 GEN
Solar/Wind Harmer
2.185
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3150851SPRUNCC
Adder
1.043
316072AD1-144
Solar/Wind Harmer
0.082
3130156CHOWAN
Solar/Wind Harmer
0.225
971795AH1-408 GEN
Solar/Wind Harmer
14.921
3145663CRESWEL
Solar/Wind Harmer
0.623
971163AH1-040 GEN
Solar/Wind Harmer
17.799
3147043LAWRENC
Adder
2.009
315687AD1-152 GEN
Solar/Wind Harmer
0.007
316011AB1-132 GEN
Solar/Wind Harmer
4.028
962571AG1-106 GEN
Solar/Wind Harmer
3.152
3145336SMITFLD
Solar/Wind Harmer
0.886
3145893MURPHYS
Solar/Wind Harmer
0.884
3145893MURPHYS
Solar/Wind Harmer
0.983
3146173TUNIS
Solar/Wind Harmer
0.22
3146206CASHIE
Solar/Wind Harmer
0.219
971547AH1-271 GEN
Solar/Wind Harmer
4.682
316190AA2-174 GEN
Solar/Wind Harmer
0
3145796HORNRTN
Solar/Wind Harmer
0.721
3145796HORNRTN
Solar/Wind Harmer
0.218
3146263WOODLND
Solar/Wind Harmer
0.218
3145683EARLEYS
Solar/Wind Harmer
0.218
3145783HORNRTN
Solar/Wind Harmer
0.218
315671AE2-027_GEN
Solar/Wind Harmer
13.915
3145823KELFORD
Solar/Wind Harmer
0.216
3151171GRAVELC
Adder
2.293
316129AC1-054 GEN
Solar/Wind Harmer
0.81
971065AG2-659 GEN
Solar/Wind Harmer
9.178
3145963POPLR C
Solar/Wind Harmer
0.213
961611AG1-000B GEN
Solar/Wind Harmer
11.197
316174AB2-169 GEN
Solar/Wind Harmer
0.006
971647AH1-324 GEN
Solar/Wind Harmer
9.042
316212AC1-099_GEN
Solar/Wind Harmer
1.095
316237AB2-079_GEN
Solar/Wind Harmer
0.002
971069AG2-661 GEN
Solar/Wind Harmer
3.717
315722AD1-056 GEN
Solar/Wind Harmer
1.322
3146293MARTNCO
Solar/Wind Harmer
0.193
316458AB2-190 GEN2
Solar/Wind Harmer
1.112
970129AG2-093 GEN
Solar/Wind Harmer
5.888
3145746EVERETS
Solar/Wind Harmer
0.205
3145746EVERETS
Solar/Wind Harmer
0.205
316494AC1-189 GEN
Solar/Wind Harmer
0.688
3146233WITAKRS
Solar/Wind Harmer
0.81
3142543TWELFTH
Solar/Wind Harmer
0.02
961671AG1-007 GEN
Solar/Wind Harmer
0.031
3146083TARBORO
Solar/Wind Harmer
0.202
3145493TOT1
Solar/Wind Harmer
0.9
970685AG2-442 GEN
Solar/Wind Harmer
15.076
970401AG2-262 GEN
Solar/Wind Harmer
1.179
316359AB2-059 GEN
Solar/Wind Harmer
0.721
316049AB1-081 GEN
Solar/Wind Harmer
1.149
3145543BTLEBRO
Solar/Wind Harmer
0.201
970533AG2-339 GEN
50/50
26.037
970531AG2-338 GEN
50/50
10.415
315242AE2-183_GT2
50/50
4.689
315241AE2-183_GT1
50/50
4.66
972185AH1-677 GEN
50/50
16.905
3151041BRUNSWICKG3
50/50
3.686
972187AH1-678 GEN
50/50
8.458
971223AH1-071 GEN
Solar/Wind Harmer
3.385
3143526WINTERP
Solar/Wind Harmer
1.424
970933AG2-581 GEN
Solar/Wind Harmer
21.804
3144356SAPONY
Solar/Wind Harmer
2.135
970099AG2-077 GEN
Solar/Wind Harmer
26.564
316185AD1-033 GEN
Solar/Wind Harmer
0.007
3145506HICKORY
Solar/Wind Harmer
0.927
3145506HICKORY
Solar/Wind Harmer
0.556
3145506HICKORY
Solar/Wind Harmer
0.139
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.222
316339AD2-160 GEN
Solar/Wind Harmer
0.375
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.129
316036AC1-147 C
Solar/Wind Harmer
0.043
3150991CHESPKB
Adder
2.421
3150991CHESPKB
Adder
2.363
3137176SLIGO L2192
Solar/Wind Harmer
0.92
3146456SLIGO L269
Solar/Wind Harmer
4.09
3130086AYDLETT
Solar/Wind Harmer
0.923
970657AG2-426 GEN
Solar/Wind Harmer
8.08
970657AG2-426 GEN
Solar/Wind Harmer
1.694
3146386ELIZ CT
Solar/Wind Harmer
0.23
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.228
3146516WINFALL
Solar/Wind Harmer
0.228
3146516WINFALL
Solar/Wind Harmer
0.228
3146626S HERTFORD
Solar/Wind Harmer
0.227
3146626S HERTFORD
Solar/Wind Harmer
0.227
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
1
3146376EDENTON
Solar/Wind Harmer
1
316181AB2-040 GEN
Solar/Wind Harmer
0.325
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3142666NORTHAMPTON
Solar/Wind Harmer
0.221
3142666NORTHAMPTON
Solar/Wind Harmer
0.221
3142666NORTHAMPTON
Solar/Wind Harmer
0.221
3142666NORTHAMPTON
Solar/Wind Harmer
0.133
3145893MURPHYS
Solar/Wind Harmer
1.479
3145893MURPHYS
Solar/Wind Harmer
0.398
3146173TUNIS
Solar/Wind Harmer
0.22
3146173TUNIS
Solar/Wind Harmer
0.22
316065AD1-022 GEN
Solar/Wind Harmer
10.117
3145593CAROLNA
Solar/Wind Harmer
0.219
3145593CAROLNA
Solar/Wind Harmer
0.219
966811AG1-552 GEN
Solar/Wind Harmer
2.38
3145593CAROLNA
Solar/Wind Harmer
0.273
316426AA2-053 GEN
Solar/Wind Harmer
0.74
3145796HORNRTN
Solar/Wind Harmer
0.655
3145783HORNRTN
Solar/Wind Harmer
3.879
3145783HORNRTN
Solar/Wind Harmer
3.103
3145783HORNRTN
Solar/Wind Harmer
0.97
3145783HORNRTN
Solar/Wind Harmer
0.388
971741AH1-377 GEN
Solar/Wind Harmer
21.562
316240AF1-291 C
Solar/Wind Harmer
0.002
939181AE1-148 GEN
Solar/Wind Harmer
10.205
944641AF1-129 GEN
Adder
101.02
316274AC1-208 GEN
Solar/Wind Harmer
1.097
970301AG2-198 GEN
Solar/Wind Harmer
8.989
316033AB2-134 GEN
Solar/Wind Harmer
0.012
315697AD1-025 GEN
Solar/Wind Harmer
0.237
313527AB2-043 GEN
Solar/Wind Harmer
0.003
3145933PARMELE
Solar/Wind Harmer
0.416
3145933PARMELE
Solar/Wind Harmer
0.208
970323AG2-213 GEN
Solar/Wind Harmer
8.713
971775AH1-396 GEN
Solar/Wind Harmer
0.327
316034AC1-036 C
Solar/Wind Harmer
0.015
3145493TOT1
Solar/Wind Harmer
0.469
3145453TOT5
Solar/Wind Harmer
0.281
3145603CNETO
Solar/Wind Harmer
0.188
962561AG1-105 GEN
Solar/Wind Harmer
9.71
964791AG1-342 GEN
Solar/Wind Harmer
3.86
3146843MT LREL
Solar/Wind Harmer
0.201
3146843MT LREL
Solar/Wind Harmer
0.201
961601AG1-000A GEN
Solar/Wind Harmer
3.57
316263AC1-034 GEN
Solar/Wind Harmer
7.628
316317KELFORD C
Solar/Wind Harmer
0.021
3145823KELFORD
Solar/Wind Harmer
0.216
3151221GRAVEL6
Adder
15.669
3151171GRAVELC
Adder
3.015
3145963POPLR C
Solar/Wind Harmer
0.213
961611AG1-000B GEN
Solar/Wind Harmer
5.693
316210AC1-098 GEN
Solar/Wind Harmer
1.964
970909AG2-566 GEN
Solar/Wind Harmer
2.247
315778AD1-151 GEN
Solar/Wind Harmer
16.728
316131AB2-060 GEN
Solar/Wind Harmer
0.657
315607AA1-063A GEN
Solar/Wind Harmer
0.451
3130546PLYMOUTH
Solar/Wind Harmer
0.22
315732AD1-074 GEN1
Solar/Wind Harmer
1.265
315733AD1-074 GEN2
Solar/Wind Harmer
1.265
315735AD1-075 GEN1
Solar/Wind Harmer
0.633
3146206CASHIE
Solar/Wind Harmer
0.219
970601AG2-382 GEN
Solar/Wind Harmer
8.193
3145513AHOSKIE
Solar/Wind Harmer
0.458
3145513AHOSKIE
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
0.699
3145796HORNRTN
Solar/Wind Harmer
0.087
3145683EARLEYS
Solar/Wind Harmer
0.436
3145683EARLEYS
Solar/Wind Harmer
0.218
3145683EARLEYS
Solar/Wind Harmer
0.218
970831AG2-522 GEN
Solar/Wind Harmer
9.21
972265AH1-717 GEN
Adder
16.734
3151201GRAVEL4
Adder
15.687
3151191GRAVEL3
Adder
15.488
3151211GRAVEL5
Adder
15.488
3146033SCOT NK
Solar/Wind Harmer
0.854
316369SG1_INVT
Solar/Wind Harmer
0.008
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
1.112
316005AA1-067
Solar/Wind Harmer
0.22
3145746EVERETS
Solar/Wind Harmer
0.817
3145746EVERETS
Solar/Wind Harmer
0.205
3145746EVERETS
Solar/Wind Harmer
0.205
3145746EVERETS
Solar/Wind Harmer
0.205
970181AG2-120 GEN
Solar/Wind Harmer
2.556
971443AH1-215 GEN
Solar/Wind Harmer
3.434
3144303KENBRDG
Solar/Wind Harmer
0.163
957861AF2-080 GEN
Solar/Wind Harmer
8.785
316319Z2-044 C
Solar/Wind Harmer
0
316420AA1-050 GEN
Solar/Wind Harmer
0.007
3145573BETHELC
Solar/Wind Harmer
0.202
3145573BETHELC
Solar/Wind Harmer
0.202
970683AG2-441 GEN
Solar/Wind Harmer
13.461
970681AG2-440 GEN
Solar/Wind Harmer
10.769
946301AF1-294 GEN
Solar/Wind Harmer
3.942
961791AG1-021 GEN
Solar/Wind Harmer
1.918
315657AE1-056 GEN
Solar/Wind Harmer
6.837
316118AC1-105 GEN
Solar/Wind Harmer
0.511
3147173SINAI
Solar/Wind Harmer
0.195
3147243WELCO
Solar/Wind Harmer
0.122
3138283WHITEMARSH
Solar/Wind Harmer
0.042
970285AG2-188 GEN
Solar/Wind Harmer
13.745
971167AH1-042 GEN
Solar/Wind Harmer
15.274
971845AH1-439 GEN
Solar/Wind Harmer
7.727
3142433PROV 92
Adder
0.33
3142433PROV 92
Adder
0.33
970865AG2-541 GEN
Solar/Wind Harmer
5.846
3143873LANEXA
Solar/Wind Harmer
0.097
970189AG2-124 GEN
Solar/Wind Harmer
4.755
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.032
315976AC1-164 GENA
Solar/Wind Harmer
16.473
316169AC1-164_GENC
Solar/Wind Harmer
14.231
315975AC1-164 GENB
Solar/Wind Harmer
0.487
316059AD1-063 C
Solar/Wind Harmer
0.001
316314AB2-024 C
Solar/Wind Harmer
0.001
3141913WHIT STONE
Solar/Wind Harmer
0.154
3138133OCRAN
Solar/Wind Harmer
0.046
316123AC1-075 GEN
Solar/Wind Harmer
0.207
970165AG2-112 GEN
Solar/Wind Harmer
1.226
970163AG2-111 GEN
Solar/Wind Harmer
1.169
3141783LANCAST
Solar/Wind Harmer
0.09
3141783LANCAST
Solar/Wind Harmer
0.06
316312AB1-027
Solar/Wind Harmer
0.264
972205AH1-687 GEN
Adder
6.146
962981AG1-147 GEN
Solar/Wind Harmer
5.333
970327AG2-215 GEN
Solar/Wind Harmer
4.564
972189AH1-679 GEN
Adder
2.259
3141813NORNECK
Solar/Wind Harmer
0.122
971447AH1-217 GEN
Solar/Wind Harmer
3.707
270494AE1-108_GEN
Solar/Wind Harmer
1.376
316164AC1-076 GEN
Solar/Wind Helper
1.076
3145543BTLEBRO
Solar/Wind Harmer
0.16
3142053HEARTS
Solar/Wind Harmer
0.353
963171AG1-166 GEN
Solar/Wind Harmer
1.065
971563AH1-280 GEN
Solar/Wind Harmer
2.131
3144293JTRSVLE
Adder
0.636
3138126ROCKLANDING
Solar/Wind Harmer
0.091
3143096IRON208
Adder
0.803
971317AH1-138 GEN
Solar/Wind Harmer
1.415
3146926FARMVIL
Solar/Wind Harmer
0.113
316003AC1-222 GEN
Solar/Wind Harmer
0.005
944631AF1-128 GEN
Adder
88.305
316159AE1-175 C
Solar/Wind Harmer
0.159
970937AG2-583 GEN
Solar/Wind Harmer
11.244
3142433PROV 92
Solar/Wind Harmer
0.679
3142433PROV 92
Adder
0.33
3142433PROV 92
Adder
0.33
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.067
971777AH1-397 GEN
Solar/Wind Harmer
0.424
3141843SHACKLE
Adder
0.82
3141766HARMONY
Solar/Wind Harmer
0.032
3138133OCRAN
Solar/Wind Harmer
0.092
972003AH1-546 GEN
Solar/Wind Harmer
6.306
3142416OLDCHRC
Solar/Wind Harmer
0.383
3142416OLDCHRC
Solar/Wind Harmer
0.147
966881AG1-559 GEN
Solar/Wind Harmer
0.156
962861AG1-135 GEN
Solar/Wind Harmer
4.306
971377AH1-170 GEN
Solar/Wind Harmer
1.384
3147623JAMES R
Solar/Wind Harmer
0.301
3141726DUNNSVL
Solar/Wind Harmer
0.502
3150351NORNECKC2
Adder
1.216
970223AG2-152 GEN
Solar/Wind Harmer
8.167
316045AC1-158 PL2
Solar/Wind Helper
5.32
3147666LOUISA
Solar/Wind Helper
0.991
316192AB2-158 GEN
Solar/Wind Helper
1.631
958211AF2-115 GEN
Solar/Wind Harmer
2.397
963191AG1-168 GEN
Solar/Wind Harmer
0.799
3144293JTRSVLE
Adder
0.636
3144293JTRSVLE
Adder
0.535
3147133PAMPLIN
Solar/Wind Harmer
0.198
3147133PAMPLIN
Solar/Wind Harmer
0.158
3142946ENON
Solar/Wind Harmer
0.018
316222AC1-221 GEN
Solar/Wind Harmer
0.736
3142366NRTHEST
Adder
0.567
3150691DARBY 3
Adder
12.268
3150701DARBY 4
Adder
12.239
3150681DARBY 2
Adder
12.225
3150671DARBY 1
Adder
12.21
3146776BUCKING
Solar/Wind Harmer
0.674
3146776BUCKING
Solar/Wind Harmer
0.055
316075AC2-137 C
Solar/Wind Harmer
0.044
3142296MT RD221
Adder
0.464
942751AE2-291 GEN
Solar/Wind Harmer
7.623
957411AF2-035 GEN
Solar/Wind Harmer
5.746
970317AG2-208 GEN
Solar/Wind Harmer
5.324
315673AE1-157 GEN
Solar/Wind Harmer
9.311
966871AG1-558 GEN
Solar/Wind Harmer
0.155
958261AF2-120 GEN
Solar/Wind Harmer
4.396
971489AH1-241 GEN
Solar/Wind Harmer
6.92
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.278
3150341NORNECKC1
Adder
1.267
316447AC1-158 HLD
Solar/Wind Helper
3.658
315724AD1-057 GEN
Solar/Wind Harmer
0.783
3145933PARMELE
Solar/Wind Harmer
0.208
966801AG1-551 GEN
Solar/Wind Harmer
2.422
964241AG1-285 GEN
Solar/Wind Harmer
13.836
970129AG2-093 GEN
Solar/Wind Harmer
12.511
316327AA2-057 GEN
Solar/Wind Harmer
0.312
3145746EVERETS
Solar/Wind Harmer
0.205
3145746EVERETS
Solar/Wind Harmer
0.205
315785AD2-033 C
Solar/Wind Harmer
1.668
970257AG2-171 GEN
Solar/Wind Harmer
6.535
970133AG2-095 GEN
Solar/Wind Harmer
1.959
3146233WITAKRS
Solar/Wind Harmer
1.022
3146233WITAKRS
Solar/Wind Harmer
0.138
959311AF2-222 GEN
Solar/Wind Harmer
18.094
3138543CONSLDL
Solar/Wind Harmer
0.134
3146073TAR RVR
Solar/Wind Harmer
0.202
3146083TARBORO
Solar/Wind Harmer
0.202
961601AG1-000A GEN
Solar/Wind Harmer
14.278
3145543BTLEBRO
Solar/Wind Harmer
0.201
3145543BTLEBRO
Solar/Wind Harmer
0.201
971623AH1-311 GEN
Solar/Wind Harmer
0.401
3144216WINCHST
Adder
0.755
963181AG1-167 GEN
Solar/Wind Harmer
0.799
3144293JTRSVLE
Adder
0.636
3147133PAMPLIN
Solar/Wind Harmer
0.622
971193AH1-056 GEN
Solar/Wind Harmer
12.07
3150921YORKTN3
Adder
4.971
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
8.321
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3143096IRON208
Adder
0.803
3143096IRON208
Adder
0.787
3146926FARMVIL
Solar/Wind Harmer
0.113
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.059
971683AH1-343 GEN
Solar/Wind Harmer
6.522
316283AC2-100 C
Solar/Wind Harmer
0.345
3142433PROV 92
Adder
0.33
3142433PROV 92
Adder
0.33
3146776BUCKING
Solar/Wind Harmer
0.061
970293AG2-193 GEN
Solar/Wind Harmer
1.763
3141843SHACKLE
Adder
0.82
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.003
316156AD2-030 GEN
Solar/Wind Harmer
0.118
3141873WAN 176
Solar/Wind Harmer
2.837
3141766HARMONY
Solar/Wind Harmer
2.104
3142416OLDCHRC
Solar/Wind Harmer
1.43
962971AG1-146 GEN
Solar/Wind Harmer
2.286
970009AG2-005 GEN
Solar/Wind Harmer
1.038
316473AC1-191 GEN
Solar/Wind Harmer
0.453
316404AE1-155 C
Solar/Wind Harmer
0.03
970221AG2-151 GEN
Solar/Wind Harmer
6.92
3150351NORNECKC2
Adder
1.237
316044AC1-158 PL1
Solar/Wind Helper
1.662
316450AC1-158 RIC
Solar/Wind Helper
0.443
3147666LOUISA
Solar/Wind Helper
0.57
CPLELTFEXP_CPLE->PJM
CLTF
13.441
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.073
LAGNLTFEXP_LAGN->PJM
CLTF
9.344
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.083
TVALTFEXP_TVA->PJM
CLTF
4.685
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.719
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.027
MECLTFEXP_MEC->PJM
CLTF
4.476
SIGELTFEXP_SIGE->PJM
CLTF
0.135
NYPJM->LTFIMP_NY
CLTF
2.526
LGEELTFEXP_LGEE->PJM
CLTF
1.627
WECLTFEXP_WEC->PJM
CLTF
0.828

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.34 %
Rating:3193.18 MVA
Rating Type:A
MVA to Mitigate:3619.13
MW Contribution:21.55
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
5.424
315244AE2-183_ST
50/50
7.889
963041AG1-153 GEN
50/50
7.262
315779AE2-040
50/50
3.426
3151541CLOVER2
50/50
4.914
941031AE2-094 GEN
Solar/Wind Harmer
52.507
944011AF1-069 GEN
Solar/Wind Harmer
17.156
970673AG2-436 GEN
Solar/Wind Harmer
59.565
970673AG2-436 GEN
Solar/Wind Harmer
39.71
971967AH1-528 GEN
Solar/Wind Harmer
43.86
970085AG2-068 GEN
Solar/Wind Harmer
13.865
970581AG2-369 GEN
Solar/Wind Harmer
11.924
316233AE1-074 FULL
Solar/Wind Harmer
0.208
971281AH1-106 GEN
Solar/Wind Harmer
3.602
971283AH1-107 GEN
Solar/Wind Harmer
3.602
316315AB2-025 C
Solar/Wind Harmer
0.198
315814AE2-033 C
Solar/Wind Harmer
19.336
3143316POE
Solar/Wind Harmer
0.915
957871AF2-081 GEN
Solar/Wind Harmer
11.058
3151081ELIZAR1
Adder
20.359
3151091ELIZAR2
Adder
20.005
319010AE1-072 C
Solar/Wind Harmer
1.117
970119AG2-088 GEN
50/50
40.684
315243AE2-183_GT3
50/50
4.563
3151051BRUNSWICKS1
50/50
7.443
3151021BRUNSWICKG1
50/50
3.586
971451AH1-221 GEN
50/50
10.893
3151531CLOVER1
50/50
4.938
3143226MDLTHAN
Solar/Wind Harmer
0.305
940641AE2-051 GEN
Solar/Wind Harmer
22.672
939411AE1-173 GEN
Solar/Wind Harmer
114.479
970919AG2-571 GEN
Solar/Wind Harmer
9.287
970087AG2-069 GEN
Solar/Wind Harmer
20.797
3143526WINTERP
Solar/Wind Harmer
1.35
957481AF2-042 GEN
Solar/Wind Harmer
64.526
3143336POWHATN
Solar/Wind Harmer
4.238
315693AD1-088 GEN
Solar/Wind Harmer
11.177
962491AG1-098 GEN
Solar/Wind Harmer
13.203
316023GEN1_S
Solar/Wind Harmer
0.504
944591AF1-124 GEN
Solar/Wind Harmer
50.741
316294AC1-161 GEN
Solar/Wind Harmer
3.877
316388AE2-253 GEN
Solar/Wind Harmer
0.696
3146456SLIGO L269
Solar/Wind Harmer
0.222
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.768
316246AF1-032 C
Solar/Wind Harmer
0.1
316336AC2-165 C
Solar/Wind Harmer
0.009
316093AE2-104_GEN
Solar/Wind Harmer
3.708
970661AG2-428 GEN
Solar/Wind Harmer
21.842
316381AD1-082 GEN
Solar/Wind Harmer
0.229
960081AF2-299 GEN
Solar/Wind Harmer
2.106
970659AG2-427 GEN
Solar/Wind Harmer
10.606
3146516WINFALL
Solar/Wind Harmer
0.71
3146516WINFALL
Solar/Wind Harmer
0.219
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.216
971795AH1-408 GEN
Solar/Wind Harmer
14.392
316072AD1-144
Solar/Wind Harmer
0.078
315687AD1-152 GEN
Solar/Wind Harmer
0.007
3147043LAWRENC
Adder
1.939
3145663CRESWEL
Solar/Wind Harmer
0.599
3146406KITTY HAWK
Solar/Wind Harmer
0.028
3152611GOSPORTB
Adder
2.823
3152621GOSPORTC
Adder
2.396
3152601GOSPORTA
Adder
2.21
316305AF2-043 C
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.119
315835AF2-110_GEN
Solar/Wind Harmer
1.513
316321Z2-027
Solar/Wind Harmer
0.041
3146396TANGLEW
Solar/Wind Harmer
0.607
3145176PASQUOTANK
Solar/Wind Harmer
0.136
3146486SUNBURY
Solar/Wind Harmer
0.22
3146486SUNBURY
Solar/Wind Harmer
0.22
316311AC2-079 GEN
Solar/Wind Harmer
6.318
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.151
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
316087AB2-174 GEN
Solar/Wind Harmer
0.006
3130156CHOWAN
Solar/Wind Harmer
0.216
3130156CHOWAN
Solar/Wind Harmer
0.216
965291AG1-394 GEN
Solar/Wind Harmer
0.951
315816AE2-034 GEN
Solar/Wind Harmer
0.918
315652AC1-086 GEN
Solar/Wind Harmer
23.483
3137643SOCKMAN
Solar/Wind Harmer
0.852
3145893MURPHYS
Solar/Wind Harmer
0.574
3145893MURPHYS
Solar/Wind Harmer
0.213
3146043SEABORD
Solar/Wind Harmer
0.213
315607AA1-063A GEN
Solar/Wind Harmer
0.434
971163AH1-040 GEN
Solar/Wind Harmer
17.112
316011AB1-132 GEN
Solar/Wind Harmer
3.881
962571AG1-106 GEN
Solar/Wind Harmer
3.037
3145893MURPHYS
Solar/Wind Harmer
0.851
3145893MURPHYS
Solar/Wind Harmer
0.946
3146173TUNIS
Solar/Wind Harmer
0.211
316190AA2-174 GEN
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.211
971547AH1-271 GEN
Solar/Wind Harmer
4.504
3145336SMITFLD
Solar/Wind Harmer
0.844
3145796HORNRTN
Solar/Wind Harmer
0.695
3145796HORNRTN
Solar/Wind Harmer
0.211
3150851SPRUNCC
Adder
0.97
3146263WOODLND
Solar/Wind Harmer
0.21
3145783HORNRTN
Solar/Wind Harmer
0.21
3145683EARLEYS
Solar/Wind Harmer
0.21
316129AC1-054 GEN
Solar/Wind Harmer
0.783
971065AG2-659 GEN
Solar/Wind Harmer
8.875
3145823KELFORD
Solar/Wind Harmer
0.208
3145963POPLR C
Solar/Wind Harmer
0.206
316174AB2-169 GEN
Solar/Wind Harmer
0.005
3151171GRAVELC
Adder
2.174
316212AC1-099_GEN
Solar/Wind Harmer
1.056
315671AE2-027_GEN
Solar/Wind Harmer
13.019
316237AB2-079_GEN
Solar/Wind Harmer
0.002
961611AG1-000B GEN
Solar/Wind Harmer
10.587
315722AD1-056 GEN
Solar/Wind Harmer
1.275
3146293MARTNCO
Solar/Wind Harmer
0.186
971647AH1-324 GEN
Solar/Wind Harmer
8.529
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
316494AC1-189 GEN
Solar/Wind Harmer
0.664
3146233WITAKRS
Solar/Wind Harmer
0.782
971069AG2-661 GEN
Solar/Wind Harmer
3.491
961671AG1-007 GEN
Solar/Wind Harmer
0.03
3146083TARBORO
Solar/Wind Harmer
0.195
3145493TOT1
Solar/Wind Harmer
0.868
970685AG2-442 GEN
Solar/Wind Harmer
14.585
970401AG2-262 GEN
Solar/Wind Harmer
1.143
316458AB2-190 GEN2
Solar/Wind Harmer
1.041
316359AB2-059 GEN
Solar/Wind Harmer
0.696
316049AB1-081 GEN
Solar/Wind Harmer
1.109
3145543BTLEBRO
Solar/Wind Harmer
0.194
3145543BTLEBRO
Solar/Wind Harmer
0.155
3142053HEARTS
Solar/Wind Harmer
0.341
970129AG2-093 GEN
Solar/Wind Harmer
5.511
963171AG1-166 GEN
Solar/Wind Harmer
1.03
971563AH1-280 GEN
Solar/Wind Harmer
2.061
3144293JTRSVLE
Adder
0.615
3138126ROCKLANDING
Solar/Wind Harmer
0.087
3142543TWELFTH
Solar/Wind Harmer
0.018
3146926FARMVIL
Solar/Wind Harmer
0.11
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971317AH1-138 GEN
Solar/Wind Harmer
1.337
970937AG2-583 GEN
Solar/Wind Harmer
10.797
3143096IRON208
Adder
0.735
316159AE1-175 C
Solar/Wind Harmer
0.149
944631AF1-128 GEN
Adder
81.311
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.065
3142433PROV 92
Solar/Wind Harmer
0.629
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
971777AH1-397 GEN
Solar/Wind Harmer
0.396
3141843SHACKLE
Adder
0.766
3141766HARMONY
Solar/Wind Harmer
0.029
3138133OCRAN
Solar/Wind Harmer
0.086
972003AH1-546 GEN
Solar/Wind Harmer
6.056
3142416OLDCHRC
Solar/Wind Harmer
0.332
3142416OLDCHRC
Solar/Wind Harmer
0.127
962861AG1-135 GEN
Solar/Wind Harmer
4.063
971377AH1-170 GEN
Solar/Wind Harmer
1.327
3147623JAMES R
Solar/Wind Harmer
0.288
3141726DUNNSVL
Solar/Wind Harmer
0.474
3150351NORNECKC2
Adder
1.153
970223AG2-152 GEN
Solar/Wind Harmer
7.902
316045AC1-158 PL2
Solar/Wind Helper
5.205
3147666LOUISA
Solar/Wind Helper
0.977
316192AB2-158 GEN
Solar/Wind Helper
1.608
970533AG2-339 GEN
50/50
25.341
970531AG2-338 GEN
50/50
10.136
315242AE2-183_GT2
50/50
4.563
315241AE2-183_GT1
50/50
4.535
972185AH1-677 GEN
50/50
16.45
3151041BRUNSWICKG3
50/50
3.586
972187AH1-678 GEN
50/50
8.23
971223AH1-071 GEN
Solar/Wind Harmer
3.255
970933AG2-581 GEN
Solar/Wind Harmer
21.207
3143526WINTERP
Solar/Wind Harmer
1.35
3144356SAPONY
Solar/Wind Harmer
2.053
970099AG2-077 GEN
Solar/Wind Harmer
25.81
316185AD1-033 GEN
Solar/Wind Harmer
0.006
3145506HICKORY
Solar/Wind Harmer
0.89
3145506HICKORY
Solar/Wind Harmer
0.534
3145506HICKORY
Solar/Wind Harmer
0.134
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.213
316339AD2-160 GEN
Solar/Wind Harmer
0.36
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.124
3137176SLIGO L2192
Solar/Wind Harmer
0.883
3146456SLIGO L269
Solar/Wind Harmer
3.926
316036AC1-147 C
Solar/Wind Harmer
0.041
3130086AYDLETT
Solar/Wind Harmer
0.886
3150991CHESPKB
Adder
2.322
3150991CHESPKB
Adder
2.266
3146386ELIZ CT
Solar/Wind Harmer
0.22
970657AG2-426 GEN
Solar/Wind Harmer
7.686
970657AG2-426 GEN
Solar/Wind Harmer
1.611
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.219
3146516WINFALL
Solar/Wind Harmer
0.219
3146516WINFALL
Solar/Wind Harmer
0.219
3146626S HERTFORD
Solar/Wind Harmer
0.218
3146626S HERTFORD
Solar/Wind Harmer
0.218
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
0.961
3146376EDENTON
Solar/Wind Harmer
0.961
316181AB2-040 GEN
Solar/Wind Harmer
0.313
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.128
3145893MURPHYS
Solar/Wind Harmer
1.424
3145893MURPHYS
Solar/Wind Harmer
0.383
3145593CAROLNA
Solar/Wind Harmer
0.211
3145593CAROLNA
Solar/Wind Harmer
0.211
966811AG1-552 GEN
Solar/Wind Harmer
2.295
3145593CAROLNA
Solar/Wind Harmer
0.263
3146173TUNIS
Solar/Wind Harmer
0.211
3146173TUNIS
Solar/Wind Harmer
0.211
316065AD1-022 GEN
Solar/Wind Harmer
9.733
316426AA2-053 GEN
Solar/Wind Harmer
0.714
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3145796HORNRTN
Solar/Wind Harmer
0.632
971741AH1-377 GEN
Solar/Wind Harmer
20.897
3145783HORNRTN
Solar/Wind Harmer
3.74
3145783HORNRTN
Solar/Wind Harmer
2.992
3145783HORNRTN
Solar/Wind Harmer
0.935
3145783HORNRTN
Solar/Wind Harmer
0.374
939181AE1-148 GEN
Solar/Wind Harmer
9.88
970301AG2-198 GEN
Solar/Wind Harmer
8.706
316274AC1-208 GEN
Solar/Wind Harmer
1.058
313527AB2-043 GEN
Solar/Wind Harmer
0.003
316240AF1-291 C
Solar/Wind Harmer
0.002
3145933PARMELE
Solar/Wind Harmer
0.401
3145933PARMELE
Solar/Wind Harmer
0.2
316033AB2-134 GEN
Solar/Wind Harmer
0.012
315697AD1-025 GEN
Solar/Wind Harmer
0.223
970323AG2-213 GEN
Solar/Wind Harmer
8.431
971775AH1-396 GEN
Solar/Wind Harmer
0.316
316034AC1-036 C
Solar/Wind Harmer
0.014
944641AF1-129 GEN
Adder
93.824
962561AG1-105 GEN
Solar/Wind Harmer
9.407
3145493TOT1
Solar/Wind Harmer
0.453
3145453TOT5
Solar/Wind Harmer
0.272
3145603CNETO
Solar/Wind Harmer
0.181
964791AG1-342 GEN
Solar/Wind Harmer
3.74
3146843MT LREL
Solar/Wind Harmer
0.195
3146843MT LREL
Solar/Wind Harmer
0.195
961601AG1-000A GEN
Solar/Wind Harmer
3.447
316263AC1-034 GEN
Solar/Wind Harmer
7.365
958211AF2-115 GEN
Solar/Wind Harmer
2.318
3151031BRUNSWICKG2
50/50
3.586
970413AG2-270 GEN
50/50
21.547
3151101ELIZAR3
50/50
21.88
970917AG2-570 GEN
Solar/Wind Harmer
23.218
316313AB2-026
Solar/Wind Harmer
0.15
316258AE1-075 C
Solar/Wind Harmer
0.18
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.602
316478AD1-087 GEN
Solar/Wind Harmer
0.805
316486AD2-202 GEN
Solar/Wind Harmer
0.236
316365GEN2_N
Solar/Wind Harmer
0.504
944581AF1-123 GEN
Solar/Wind Harmer
50.561
944601AF1-125 GEN
Solar/Wind Harmer
49.783
315773AC2-141 GEN
Solar/Wind Harmer
8.172
3146456SLIGO L269
Solar/Wind Harmer
0.222
971153AH1-033 GEN
Solar/Wind Harmer
2.565
3144873MCLAUGH
Solar/Wind Harmer
0.006
316320Y1-086
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
4.646
316435W1029_GEN3
Solar/Wind Harmer
0.001
316083AB2-161 GEN
Solar/Wind Harmer
0.003
970659AG2-427 GEN
Solar/Wind Harmer
2.32
3146516WINFALL
Solar/Wind Harmer
0.219
315813AE1-149 C
Solar/Wind Harmer
11.679
3144536CHRHLND
Solar/Wind Harmer
0.033
3145273HOLLAND
Solar/Wind Harmer
0.164
3146626S HERTFORD
Solar/Wind Harmer
0.218
3146376EDENTON
Solar/Wind Harmer
0.216
313506AB2-031 GEN
Solar/Wind Harmer
0.667
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
3147043LAWRENC
Solar/Wind Harmer
0.129
315614AA2-178 GEN
Solar/Wind Harmer
1.224
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3145893MURPHYS
Solar/Wind Harmer
0.356
3145893MURPHYS
Solar/Wind Harmer
0.213
315839AE2-212 C
Solar/Wind Harmer
0.002
957521AF2-046 GEN
Solar/Wind Harmer
15.803
961681AG1-008 GEN
Solar/Wind Harmer
15.803
971157AH1-035 GEN
Solar/Wind Harmer
2.546
315737AD1-076 GEN
Solar/Wind Harmer
2.725
3146173TUNIS
Solar/Wind Harmer
0.211
3146206CASHIE
Solar/Wind Harmer
0.211
3145336SMITFLD
Solar/Wind Harmer
0.084
316463AE2-346 GEN
Solar/Wind Harmer
0.181
316140AB2-099
Solar/Wind Harmer
0.075
962331AG1-082 GEN
Solar/Wind Harmer
2.248
3145796HORNRTN
Solar/Wind Harmer
0.842
3145796HORNRTN
Solar/Wind Harmer
0.211
3150861SPRUNCD
Adder
0.97
3146263WOODLND
Solar/Wind Harmer
0.21
3156021HOLLOMANSOL
Solar/Wind Harmer
0.954
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.208
965281AG1-393 GEN
Solar/Wind Harmer
2.207
3145963POPLR C
Solar/Wind Harmer
0.206
3151221GRAVEL6
Adder
14.86
3151171GRAVELC
Adder
2.859
316210AC1-098 GEN
Solar/Wind Harmer
1.894
970909AG2-566 GEN
Solar/Wind Harmer
2.177
316131AB2-060 GEN
Solar/Wind Harmer
0.636
961611AG1-000B GEN
Solar/Wind Harmer
5.383
315724AD1-057 GEN
Solar/Wind Harmer
0.756
964241AG1-285 GEN
Solar/Wind Harmer
13.392
3145933PARMELE
Solar/Wind Harmer
0.2
966801AG1-551 GEN
Solar/Wind Harmer
2.335
316327AA2-057 GEN
Solar/Wind Harmer
0.301
315785AD2-033 C
Solar/Wind Harmer
1.614
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
3130546PLYMOUTH
Solar/Wind Harmer
0.212
315732AD1-074 GEN1
Solar/Wind Harmer
1.217
315733AD1-074 GEN2
Solar/Wind Harmer
1.217
315735AD1-075 GEN1
Solar/Wind Harmer
0.609
3146206CASHIE
Solar/Wind Harmer
0.211
970601AG2-382 GEN
Solar/Wind Harmer
7.883
3145513AHOSKIE
Solar/Wind Harmer
0.441
3145513AHOSKIE
Solar/Wind Harmer
0.211
3145796HORNRTN
Solar/Wind Harmer
0.674
3145796HORNRTN
Solar/Wind Harmer
0.084
971285AH1-108 GEN
Adder
1.587
971445AH1-216 GEN
Solar/Wind Harmer
14.817
3145683EARLEYS
Solar/Wind Harmer
0.42
3145683EARLEYS
Solar/Wind Harmer
0.21
3145683EARLEYS
Solar/Wind Harmer
0.21
970831AG2-522 GEN
Solar/Wind Harmer
8.902
3146033SCOT NK
Solar/Wind Harmer
0.823
972265AH1-717 GEN
Adder
15.87
3151201GRAVEL4
Adder
14.877
3151191GRAVEL3
Adder
14.689
3151211GRAVEL5
Adder
14.689
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316005AA1-067
Solar/Wind Harmer
0.212
3145746EVERETS
Solar/Wind Harmer
0.788
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
970181AG2-120 GEN
Solar/Wind Harmer
2.464
316369SG1_INVT
Solar/Wind Harmer
0.007
971443AH1-215 GEN
Solar/Wind Harmer
3.323
3144303KENBRDG
Solar/Wind Harmer
0.158
957861AF2-080 GEN
Solar/Wind Harmer
8.475
316319Z2-044 C
Solar/Wind Harmer
0
316420AA1-050 GEN
Solar/Wind Harmer
0.006
3145573BETHELC
Solar/Wind Harmer
0.195
3145573BETHELC
Solar/Wind Harmer
0.195
970683AG2-441 GEN
Solar/Wind Harmer
13.022
970681AG2-440 GEN
Solar/Wind Harmer
10.418
316132AB2-190 GEN1
Solar/Wind Harmer
1.041
946301AF1-294 GEN
Solar/Wind Harmer
3.812
961791AG1-021 GEN
Solar/Wind Harmer
1.855
316118AC1-105 GEN
Solar/Wind Harmer
0.495
315657AE1-056 GEN
Solar/Wind Harmer
6.612
3147173SINAI
Solar/Wind Harmer
0.189
3147243WELCO
Solar/Wind Harmer
0.118
3138283WHITEMARSH
Solar/Wind Harmer
0.039
970285AG2-188 GEN
Solar/Wind Harmer
13.256
971845AH1-439 GEN
Solar/Wind Harmer
7.448
970865AG2-541 GEN
Solar/Wind Harmer
5.665
971167AH1-042 GEN
Solar/Wind Harmer
14.133
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3143873LANEXA
Solar/Wind Harmer
0.09
970189AG2-124 GEN
Solar/Wind Harmer
4.44
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.03
316059AD1-063 C
Solar/Wind Harmer
0.001
316123AC1-075 GEN
Solar/Wind Harmer
0.2
970165AG2-112 GEN
Solar/Wind Harmer
1.187
970163AG2-111 GEN
Solar/Wind Harmer
1.132
316314AB2-024 C
Solar/Wind Harmer
0.001
315976AC1-164 GENA
Solar/Wind Harmer
15.083
316169AC1-164_GENC
Solar/Wind Harmer
13.031
315975AC1-164 GENB
Solar/Wind Harmer
0.446
3141913WHIT STONE
Solar/Wind Harmer
0.144
3138133OCRAN
Solar/Wind Harmer
0.043
3141783LANCAST
Solar/Wind Harmer
0.084
3141783LANCAST
Solar/Wind Harmer
0.056
972205AH1-687 GEN
Adder
5.897
962981AG1-147 GEN
Solar/Wind Harmer
5.019
970327AG2-215 GEN
Solar/Wind Harmer
4.3
316312AB1-027
Solar/Wind Harmer
0.228
971447AH1-217 GEN
Solar/Wind Harmer
3.55
3141813NORNECK
Solar/Wind Harmer
0.116
963191AG1-168 GEN
Solar/Wind Harmer
0.773
3144293JTRSVLE
Adder
0.615
3144293JTRSVLE
Adder
0.518
3147133PAMPLIN
Solar/Wind Harmer
0.192
3147133PAMPLIN
Solar/Wind Harmer
0.153
316222AC1-221 GEN
Solar/Wind Harmer
0.714
3142946ENON
Solar/Wind Harmer
0.016
3146776BUCKING
Solar/Wind Harmer
0.65
3146776BUCKING
Solar/Wind Harmer
0.053
3142366NRTHEST
Adder
0.505
3150691DARBY 3
Adder
10.955
3150701DARBY 4
Adder
10.93
3150681DARBY 2
Adder
10.917
3150671DARBY 1
Adder
10.904
316075AC2-137 C
Solar/Wind Harmer
0.04
942751AE2-291 GEN
Solar/Wind Harmer
7.378
958261AF2-120 GEN
Solar/Wind Harmer
4.15
971489AH1-241 GEN
Solar/Wind Harmer
6.633
3142296MT RD221
Adder
0.39
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.211
3150341NORNECKC1
Adder
1.201
966871AG1-558 GEN
Solar/Wind Harmer
0.131
316447AC1-158 HLD
Solar/Wind Helper
3.579
970257AG2-171 GEN
Solar/Wind Harmer
6.323
959311AF2-222 GEN
Solar/Wind Harmer
17.507
3146233WITAKRS
Solar/Wind Harmer
0.986
3146233WITAKRS
Solar/Wind Harmer
0.134
315778AD1-151 GEN
Solar/Wind Harmer
15.709
3138543CONSLDL
Solar/Wind Harmer
0.129
3146073TAR RVR
Solar/Wind Harmer
0.195
3146083TARBORO
Solar/Wind Harmer
0.195
961601AG1-000A GEN
Solar/Wind Harmer
13.786
3145543BTLEBRO
Solar/Wind Harmer
0.194
3145543BTLEBRO
Solar/Wind Harmer
0.194
971623AH1-311 GEN
Solar/Wind Harmer
0.388
970129AG2-093 GEN
Solar/Wind Harmer
11.71
963181AG1-167 GEN
Solar/Wind Harmer
0.773
3144293JTRSVLE
Adder
0.615
3147133PAMPLIN
Solar/Wind Harmer
0.602
971193AH1-056 GEN
Solar/Wind Harmer
11.673
970133AG2-095 GEN
Solar/Wind Harmer
1.824
3144216WINCHST
Adder
0.716
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
8.068
3150921YORKTN3
Adder
4.712
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.11
3143096IRON208
Adder
0.735
3143096IRON208
Adder
0.72
316382AG1-145 C
Solar/Wind Harmer
0.001
971683AH1-343 GEN
Solar/Wind Harmer
6.321
316283AC2-100 C
Solar/Wind Harmer
0.335
3142946ENON
Solar/Wind Harmer
0.055
3146776BUCKING
Solar/Wind Harmer
0.059
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3141843SHACKLE
Adder
0.766
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.003
316156AD2-030 GEN
Solar/Wind Harmer
0.111
3141873WAN 176
Solar/Wind Harmer
2.658
970293AG2-193 GEN
Solar/Wind Harmer
1.582
3141766HARMONY
Solar/Wind Harmer
1.964
962971AG1-146 GEN
Solar/Wind Harmer
2.151
970009AG2-005 GEN
Solar/Wind Harmer
0.978
3142416OLDCHRC
Solar/Wind Harmer
1.237
316404AE1-155 C
Solar/Wind Harmer
0.028
970221AG2-151 GEN
Solar/Wind Harmer
6.633
3150351NORNECKC2
Adder
1.172
316473AC1-191 GEN
Solar/Wind Harmer
0.383
316044AC1-158 PL1
Solar/Wind Helper
1.626
316450AC1-158 RIC
Solar/Wind Helper
0.434
3147666LOUISA
Solar/Wind Helper
0.562
CPLELTFEXP_CPLE->PJM
CLTF
13.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.637
LAGNLTFEXP_LAGN->PJM
CLTF
9.063
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.182
TVALTFEXP_TVA->PJM
CLTF
4.543
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.006
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.545
MECLTFEXP_MEC->PJM
CLTF
4.353
SIGELTFEXP_SIGE->PJM
CLTF
0.131
NYPJM->LTFIMP_NY
CLTF
2.393
LGEELTFEXP_LGEE->PJM
CLTF
1.582
WECLTFEXP_WEC->PJM
CLTF
0.806

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2090-256_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2090-256_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.73 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4126.18
MW Contribution:22.11
Bus #Bus NameTypeMW Contribution
970119AG2-088 GEN
50/50
42.178
315243AE2-183_GT3
50/50
4.674
3151051BRUNSWICKS1
50/50
7.626
3151021BRUNSWICKG1
50/50
3.674
971451AH1-221 GEN
50/50
11.16
3151531CLOVER1
50/50
5.066
3143226MDLTHAN
Solar/Wind Harmer
-0.035
940641AE2-051 GEN
Solar/Wind Harmer
30.624
939411AE1-173 GEN
Solar/Wind Harmer
155.015
3143526WINTERP
Solar/Wind Harmer
-0.159
970919AG2-571 GEN
Solar/Wind Harmer
9.517
970087AG2-069 GEN
Solar/Wind Harmer
28.061
957481AF2-042 GEN
Solar/Wind Harmer
87.144
3143336POWHATN
Solar/Wind Harmer
3.295
315693AD1-088 GEN
Solar/Wind Harmer
13.425
962491AG1-098 GEN
Solar/Wind Harmer
17.843
944591AF1-124 GEN
Solar/Wind Harmer
119.528
316023GEN1_S
Solar/Wind Harmer
1.762
316294AC1-161 GEN
Solar/Wind Harmer
8.432
316388AE2-253 GEN
Solar/Wind Harmer
1.749
316375AC2-012 GEN
Solar/Wind Harmer
8.959
3150981CHESPKA
Adder
2.877
3146456SLIGO L269
Solar/Wind Harmer
-0.026
970659AG2-427 GEN
Solar/Wind Harmer
13.731
316381AD1-082 GEN
Solar/Wind Harmer
2.37
970661AG2-428 GEN
Solar/Wind Harmer
27.441
316246AF1-032 C
Solar/Wind Harmer
0.522
316093AE2-104_GEN
Solar/Wind Harmer
7.488
316336AC2-165 C
Solar/Wind Harmer
4.471
3146516WINFALL
Solar/Wind Harmer
-0.082
3146516WINFALL
Solar/Wind Harmer
-0.025
960081AF2-299 GEN
Solar/Wind Harmer
2.867
315800Z1-036_GEN1
Solar/Wind Harmer
6.264
3150851SPRUNCC
Adder
1.039
316072AD1-144
Solar/Wind Harmer
0.511
3130156CHOWAN
Solar/Wind Harmer
-0.025
971795AH1-408 GEN
Solar/Wind Harmer
18.794
3145663CRESWEL
Solar/Wind Harmer
-0.069
971163AH1-040 GEN
Solar/Wind Harmer
23.356
3147043LAWRENC
Adder
2.002
315687AD1-152 GEN
Solar/Wind Harmer
2.994
316011AB1-132 GEN
Solar/Wind Harmer
5.193
962571AG1-106 GEN
Solar/Wind Harmer
3.568
3145336SMITFLD
Solar/Wind Harmer
-0.099
3145893MURPHYS
Solar/Wind Harmer
-0.099
3145893MURPHYS
Solar/Wind Harmer
0.735
3146173TUNIS
Solar/Wind Harmer
-0.025
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
6.143
316190AA2-174 GEN
Solar/Wind Harmer
0.301
3145796HORNRTN
Solar/Wind Harmer
-0.08
3145796HORNRTN
Solar/Wind Harmer
-0.024
3146263WOODLND
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145783HORNRTN
Solar/Wind Harmer
-0.024
315671AE2-027_GEN
Solar/Wind Harmer
18.264
3145823KELFORD
Solar/Wind Harmer
-0.024
3151171GRAVELC
Adder
2.286
316129AC1-054 GEN
Solar/Wind Harmer
2.115
971065AG2-659 GEN
Solar/Wind Harmer
12.042
3145963POPLR C
Solar/Wind Harmer
-0.024
961611AG1-000B GEN
Solar/Wind Harmer
11.802
316174AB2-169 GEN
Solar/Wind Harmer
3.669
971647AH1-324 GEN
Solar/Wind Harmer
11.868
316212AC1-099_GEN
Solar/Wind Harmer
2.067
971069AG2-661 GEN
Solar/Wind Harmer
3.706
316237AB2-079_GEN
Solar/Wind Harmer
0.705
315722AD1-056 GEN
Solar/Wind Harmer
2.445
3146293MARTNCO
Solar/Wind Harmer
0.144
316458AB2-190 GEN2
Solar/Wind Harmer
2.348
970129AG2-093 GEN
Solar/Wind Harmer
5.287
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
316494AC1-189 GEN
Solar/Wind Harmer
2.455
3146233WITAKRS
Solar/Wind Harmer
-0.09
3142543TWELFTH
Solar/Wind Harmer
-0.002
961671AG1-007 GEN
Solar/Wind Harmer
0.287
3146083TARBORO
Solar/Wind Harmer
-0.023
3145493TOT1
Solar/Wind Harmer
0.672
3144293JTRSVLE
Adder
0.633
3143096IRON208
Adder
0.8
944631AF1-128 GEN
Adder
88.052
3142433PROV 92
Adder
0.331
3142433PROV 92
Adder
0.331
3141843SHACKLE
Adder
0.825
3150351NORNECKC2
Adder
1.255
316303AF2-085
50/50
5.624
315244AE2-183_ST
50/50
8.082
963041AG1-153 GEN
50/50
7.44
315779AE2-040
50/50
3.552
3151541CLOVER2
50/50
5.042
941031AE2-094 GEN
Solar/Wind Harmer
61.515
944011AF1-069 GEN
Solar/Wind Harmer
19.275
970673AG2-436 GEN
Solar/Wind Harmer
67.512
316045AC1-158 PL2
Solar/Wind Helper
5.365
3147666LOUISA
Solar/Wind Helper
1.003
316192AB2-158 GEN
Solar/Wind Helper
1.65
970685AG2-442 GEN
Solar/Wind Harmer
7.163
970673AG2-436 GEN
Solar/Wind Harmer
34.183
971967AH1-528 GEN
Solar/Wind Harmer
59.326
316233AE1-074 FULL
Solar/Wind Harmer
0.825
971281AH1-106 GEN
Solar/Wind Harmer
4.985
971283AH1-107 GEN
Solar/Wind Harmer
4.985
970085AG2-068 GEN
Solar/Wind Harmer
18.707
970581AG2-369 GEN
Solar/Wind Harmer
16.088
316315AB2-025 C
Solar/Wind Harmer
0.771
315814AE2-033 C
Solar/Wind Harmer
26.508
3143316POE
Solar/Wind Harmer
-0.107
3151081ELIZAR1
Adder
21.155
3151091ELIZAR2
Adder
20.788
957871AF2-081 GEN
Solar/Wind Harmer
12.957
3152611GOSPORTB
Adder
2.934
3152621GOSPORTC
Adder
2.49
3152601GOSPORTA
Adder
2.297
319010AE1-072 C
Solar/Wind Harmer
5.234
3146406KITTY HAWK
Solar/Wind Harmer
0.021
316305AF2-043 C
Solar/Wind Harmer
0.778
315833AF1-017_GEN
Solar/Wind Harmer
4.898
316349AD2-085 GEN
Solar/Wind Harmer
2.293
316311AC2-079 GEN
Solar/Wind Harmer
13.006
315835AF2-110_GEN
Solar/Wind Harmer
3.219
313526AB2-022
Solar/Wind Harmer
0.694
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
316321Z2-027
Solar/Wind Harmer
0.692
3146396TANGLEW
Solar/Wind Harmer
0.472
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
946281AF1-292 GEN
Solar/Wind Harmer
0.571
315611Z1-036_GEN2
Solar/Wind Harmer
6.264
971285AH1-108 GEN
Adder
1.701
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
316087AB2-174 GEN
Solar/Wind Harmer
3.593
965291AG1-394 GEN
Solar/Wind Harmer
2.212
315816AE2-034 GEN
Solar/Wind Harmer
2.016
315652AC1-086 GEN
Solar/Wind Harmer
27.921
3137643SOCKMAN
Solar/Wind Harmer
-0.099
316318V4-068
Solar/Wind Harmer
0.617
3145893MURPHYS
Solar/Wind Harmer
-0.066
3145893MURPHYS
Solar/Wind Harmer
-0.025
971445AH1-216 GEN
Solar/Wind Harmer
15.317
3146043SEABORD
Solar/Wind Harmer
-0.025
315607AA1-063A GEN
Solar/Wind Harmer
2.496
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
315732AD1-074 GEN1
Solar/Wind Harmer
4.987
315733AD1-074 GEN2
Solar/Wind Harmer
4.987
315735AD1-075 GEN1
Solar/Wind Harmer
2.494
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.751
3145513AHOSKIE
Solar/Wind Harmer
0.214
961941AG1-037 GEN
Solar/Wind Harmer
0.184
3145513AHOSKIE
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.078
3145796HORNRTN
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.049
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
970831AG2-522 GEN
Solar/Wind Harmer
12.084
972265AH1-717 GEN
Adder
16.682
3151201GRAVEL4
Adder
15.639
3151191GRAVEL3
Adder
15.441
3151211GRAVEL5
Adder
15.441
3146033SCOT NK
Solar/Wind Harmer
-0.095
316369SG1_INVT
Solar/Wind Harmer
4.209
316239AB2-077_GEN
Solar/Wind Harmer
0.705
316238AB2-078_GEN
Solar/Wind Harmer
0.705
316132AB2-190 GEN1
Solar/Wind Harmer
2.348
316005AA1-067
Solar/Wind Harmer
0.465
3145746EVERETS
Solar/Wind Harmer
-0.091
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
970181AG2-120 GEN
Solar/Wind Harmer
3.018
971443AH1-215 GEN
Solar/Wind Harmer
4.504
3144303KENBRDG
Solar/Wind Harmer
-0.018
957861AF2-080 GEN
Solar/Wind Harmer
9.982
316319Z2-044 C
Solar/Wind Harmer
1.259
316420AA1-050 GEN
Solar/Wind Harmer
2.596
3145573BETHELC
Solar/Wind Harmer
-0.023
3145573BETHELC
Solar/Wind Harmer
-0.023
3142433PROV 92
Adder
0.331
3142433PROV 92
Adder
0.331
972205AH1-687 GEN
Adder
6.109
972189AH1-679 GEN
Adder
2.243
316164AC1-076 GEN
Solar/Wind Helper
1.087
970533AG2-339 GEN
50/50
25.956
970531AG2-338 GEN
50/50
10.382
315242AE2-183_GT2
50/50
4.674
315241AE2-183_GT1
50/50
4.646
972185AH1-677 GEN
50/50
16.852
3151041BRUNSWICKG3
50/50
3.674
972187AH1-678 GEN
50/50
8.432
971223AH1-071 GEN
Solar/Wind Harmer
4.443
3143526WINTERP
Solar/Wind Harmer
-0.159
970933AG2-581 GEN
Solar/Wind Harmer
28.617
3144356SAPONY
Solar/Wind Harmer
0.997
970099AG2-077 GEN
Solar/Wind Harmer
34.857
316185AD1-033 GEN
Solar/Wind Harmer
2.743
3145506HICKORY
Solar/Wind Harmer
-0.103
3145506HICKORY
Solar/Wind Harmer
-0.062
3145506HICKORY
Solar/Wind Harmer
-0.015
3142956BIRDNECK
Solar/Wind Harmer
1.392
316316AC1-027 C
Solar/Wind Harmer
0.796
316339AD2-160 GEN
Solar/Wind Harmer
1.749
316018AA1-139 ULT2
Solar/Wind Harmer
2.22
316017AA1-139 ULT1
Solar/Wind Harmer
2.097
316036AC1-147 C
Solar/Wind Harmer
0.698
3150991CHESPKB
Adder
2.413
3150991CHESPKB
Adder
2.355
3137176SLIGO L2192
Solar/Wind Harmer
-0.102
3146456SLIGO L269
Solar/Wind Harmer
3.057
3130086AYDLETT
Solar/Wind Harmer
-0.103
970657AG2-426 GEN
Solar/Wind Harmer
8.074
970657AG2-426 GEN
Solar/Wind Harmer
1.688
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.635
316433W1029_GEN2
Solar/Wind Harmer
4.635
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
315742AE1-103 GEN
Solar/Wind Harmer
2.654
3146376EDENTON
Solar/Wind Harmer
0.747
3146376EDENTON
Solar/Wind Harmer
0.747
316181AB2-040 GEN
Solar/Wind Harmer
3.495
316236AE1-162_GEN
Solar/Wind Harmer
0.748
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
3145893MURPHYS
Solar/Wind Harmer
0.691
3145893MURPHYS
Solar/Wind Harmer
-0.044
316065AD1-022 GEN
Solar/Wind Harmer
12.302
3146173TUNIS
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
966811AG1-552 GEN
Solar/Wind Harmer
2.765
3145593CAROLNA
Solar/Wind Harmer
0.204
316426AA2-053 GEN
Solar/Wind Harmer
2.48
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145783HORNRTN
Solar/Wind Harmer
2.899
3145783HORNRTN
Solar/Wind Harmer
2.32
3145783HORNRTN
Solar/Wind Harmer
0.725
3145783HORNRTN
Solar/Wind Harmer
0.29
971741AH1-377 GEN
Solar/Wind Harmer
28.28
316240AF1-291 C
Solar/Wind Harmer
0.727
939181AE1-148 GEN
Solar/Wind Harmer
13.388
944641AF1-129 GEN
Adder
100.657
316274AC1-208 GEN
Solar/Wind Harmer
2.554
970301AG2-198 GEN
Solar/Wind Harmer
11.788
316033AB2-134 GEN
Solar/Wind Harmer
7.598
315697AD1-025 GEN
Solar/Wind Harmer
4.765
313527AB2-043 GEN
Solar/Wind Harmer
3.807
3145933PARMELE
Solar/Wind Harmer
-0.046
3145933PARMELE
Solar/Wind Harmer
-0.023
970323AG2-213 GEN
Solar/Wind Harmer
11.427
971775AH1-396 GEN
Solar/Wind Harmer
1.627
316034AC1-036 C
Solar/Wind Harmer
0.424
3145493TOT1
Solar/Wind Harmer
0.351
3145453TOT5
Solar/Wind Harmer
0.21
3145603CNETO
Solar/Wind Harmer
0.14
962561AG1-105 GEN
Solar/Wind Harmer
12.738
3144293JTRSVLE
Adder
0.633
3144293JTRSVLE
Adder
0.533
3142366NRTHEST
Adder
0.564
3150691DARBY 3
Adder
12.219
3150701DARBY 4
Adder
12.191
3150681DARBY 2
Adder
12.177
3150671DARBY 1
Adder
12.163
3142296MT RD221
Adder
0.462
3150341NORNECKC1
Adder
1.318
3150341NORNECKC1
Adder
1.308
316447AC1-158 HLD
Solar/Wind Helper
3.689
3151031BRUNSWICKG2
50/50
3.674
970413AG2-270 GEN
50/50
22.109
3151101ELIZAR3
50/50
22.735
970917AG2-570 GEN
Solar/Wind Harmer
75.183
316313AB2-026
Solar/Wind Harmer
0.749
316258AE1-075 C
Solar/Wind Harmer
0.674
316405AF2-144 C
Solar/Wind Harmer
0.711
3143336POWHATN
Solar/Wind Harmer
2.8
316478AD1-087 GEN
Solar/Wind Harmer
2.301
316486AD2-202 GEN
Solar/Wind Harmer
0.674
944581AF1-123 GEN
Solar/Wind Harmer
119.099
944601AF1-125 GEN
Solar/Wind Harmer
117.241
316365GEN2_N
Solar/Wind Harmer
1.762
315773AC2-141 GEN
Solar/Wind Harmer
10.906
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.155
315813AE1-149 C
Solar/Wind Harmer
16.172
970659AG2-427 GEN
Solar/Wind Harmer
2.433
316083AB2-161 GEN
Solar/Wind Harmer
4.194
970661AG2-428 GEN
Solar/Wind Harmer
4.863
316320Y1-086
Solar/Wind Harmer
1.508
3144536CHRHLND
Solar/Wind Harmer
-0.004
316435W1029_GEN3
Solar/Wind Harmer
4.635
3146516WINFALL
Solar/Wind Harmer
-0.025
3145273HOLLAND
Solar/Wind Harmer
-0.019
966621AG1-532 GEN
Solar/Wind Harmer
0.517
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3150861SPRUNCD
Adder
1.039
315839AE2-212 C
Solar/Wind Harmer
0.764
3146376EDENTON
Solar/Wind Harmer
-0.025
313506AB2-031 GEN
Solar/Wind Harmer
2.014
3156081AA2-088 GEN
Solar/Wind Harmer
8.101
315614AA2-178 GEN
Solar/Wind Harmer
2.688
3147043LAWRENC
Solar/Wind Harmer
-0.015
3145336SMITFLD
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.173
3145893MURPHYS
Solar/Wind Harmer
-0.025
957521AF2-046 GEN
Solar/Wind Harmer
19.463
961681AG1-008 GEN
Solar/Wind Harmer
19.463
965281AG1-393 GEN
Solar/Wind Harmer
3.089
971157AH1-035 GEN
Solar/Wind Harmer
3.087
315737AD1-076 GEN
Solar/Wind Harmer
4.686
3146173TUNIS
Solar/Wind Harmer
-0.025
3146206CASHIE
Solar/Wind Harmer
-0.024
316463AE2-346 GEN
Solar/Wind Harmer
0.397
316140AB2-099
Solar/Wind Harmer
0.165
962331AG1-082 GEN
Solar/Wind Harmer
3.064
3145796HORNRTN
Solar/Wind Harmer
-0.097
3145796HORNRTN
Solar/Wind Harmer
-0.024
3146263WOODLND
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.295
316317KELFORD C
Solar/Wind Harmer
1.139
3145823KELFORD
Solar/Wind Harmer
-0.024
3151221GRAVEL6
Adder
15.621
3151171GRAVELC
Adder
3.005
3145963POPLR C
Solar/Wind Harmer
-0.024
961611AG1-000B GEN
Solar/Wind Harmer
5.036
316210AC1-098 GEN
Solar/Wind Harmer
3.72
970909AG2-566 GEN
Solar/Wind Harmer
2.238
315778AD1-151 GEN
Solar/Wind Harmer
20.288
316131AB2-060 GEN
Solar/Wind Harmer
2.524
315724AD1-057 GEN
Solar/Wind Harmer
1.345
3145933PARMELE
Solar/Wind Harmer
-0.023
966801AG1-551 GEN
Solar/Wind Harmer
2.91
964241AG1-285 GEN
Solar/Wind Harmer
18.149
970129AG2-093 GEN
Solar/Wind Harmer
13.053
316327AA2-057 GEN
Solar/Wind Harmer
2.335
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
315785AD2-033 C
Solar/Wind Harmer
5.203
970257AG2-171 GEN
Solar/Wind Harmer
8.57
970133AG2-095 GEN
Solar/Wind Harmer
2.571
3146233WITAKRS
Solar/Wind Harmer
0.477
3146233WITAKRS
Solar/Wind Harmer
-0.015
959311AF2-222 GEN
Solar/Wind Harmer
23.777
3138543CONSLDL
Solar/Wind Harmer
-0.015
3146073TAR RVR
Solar/Wind Harmer
-0.023
3146083TARBORO
Solar/Wind Harmer
-0.023
3144216WINCHST
Adder
0.753
3144293JTRSVLE
Adder
0.633
3150921YORKTN3
Adder
4.961
3143096IRON208
Adder
0.8
3143096IRON208
Adder
0.784
3142433PROV 92
Adder
0.331
3142433PROV 92
Adder
0.331
3141843SHACKLE
Adder
0.825
3150351NORNECKC2
Adder
1.276
316044AC1-158 PL1
Solar/Wind Helper
1.676
316450AC1-158 RIC
Solar/Wind Helper
0.447
3147666LOUISA
Solar/Wind Helper
0.577
CPLELTFEXP_CPLE->PJM
CLTF
13.39
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.781
LAGNLTFEXP_LAGN->PJM
CLTF
9.293
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.961
TVALTFEXP_TVA->PJM
CLTF
4.659
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.498
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.936
MECLTFEXP_MEC->PJM
CLTF
4.446
SIGELTFEXP_SIGE->PJM
CLTF
0.134
NYPJM->LTFIMP_NY
CLTF
2.509
LGEELTFEXP_LGEE->PJM
CLTF
1.615
WECLTFEXP_WEC->PJM
CLTF
0.822

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2054-2135_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2054-2135_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.47 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4115.95
MW Contribution:21.93
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
5.455
315244AE2-183_ST
50/50
7.916
963041AG1-153 GEN
50/50
7.291
315779AE2-040
50/50
3.435
3151541CLOVER2
50/50
5.002
941031AE2-094 GEN
Solar/Wind Harmer
60.188
944011AF1-069 GEN
Solar/Wind Harmer
18.859
970673AG2-436 GEN
Solar/Wind Harmer
66.104
970673AG2-436 GEN
Solar/Wind Harmer
33.47
971967AH1-528 GEN
Solar/Wind Harmer
58.188
970085AG2-068 GEN
Solar/Wind Harmer
18.348
970581AG2-369 GEN
Solar/Wind Harmer
15.779
316233AE1-074 FULL
Solar/Wind Harmer
0.788
971281AH1-106 GEN
Solar/Wind Harmer
4.763
971283AH1-107 GEN
Solar/Wind Harmer
4.763
316315AB2-025 C
Solar/Wind Harmer
0.746
315814AE2-033 C
Solar/Wind Harmer
25.646
3143316POE
Solar/Wind Harmer
-0.102
957871AF2-081 GEN
Solar/Wind Harmer
12.489
3151081ELIZAR1
Adder
20.363
3151091ELIZAR2
Adder
20.009
319010AE1-072 C
Solar/Wind Harmer
5.045
3146406KITTY HAWK
Solar/Wind Harmer
0.021
3152611GOSPORTB
Adder
2.824
3152621GOSPORTC
Adder
2.397
3152601GOSPORTA
Adder
2.211
946281AF1-292 GEN
Solar/Wind Harmer
0.558
316305AF2-043 C
Solar/Wind Harmer
0.75
313526AB2-022
Solar/Wind Harmer
0.67
315835AF2-110_GEN
Solar/Wind Harmer
3.1
316321Z2-027
Solar/Wind Harmer
0.668
3146396TANGLEW
Solar/Wind Harmer
0.456
3145176PASQUOTANK
Solar/Wind Harmer
-0.015
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
315833AF1-017_GEN
Solar/Wind Harmer
4.701
316349AD2-085 GEN
Solar/Wind Harmer
2.201
316311AC2-079 GEN
Solar/Wind Harmer
12.483
316087AB2-174 GEN
Solar/Wind Harmer
3.511
315611Z1-036_GEN2
Solar/Wind Harmer
6.052
3130156CHOWAN
Solar/Wind Harmer
-0.024
3130156CHOWAN
Solar/Wind Harmer
-0.024
3137643SOCKMAN
Solar/Wind Harmer
-0.096
965291AG1-394 GEN
Solar/Wind Harmer
2.149
315652AC1-086 GEN
Solar/Wind Harmer
27.213
315816AE2-034 GEN
Solar/Wind Harmer
1.952
3146043SEABORD
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.435
316318V4-068
Solar/Wind Harmer
0.6
3145893MURPHYS
Solar/Wind Harmer
-0.065
3145893MURPHYS
Solar/Wind Harmer
-0.024
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.837
315733AD1-074 GEN2
Solar/Wind Harmer
4.837
315735AD1-075 GEN1
Solar/Wind Harmer
2.419
3145796HORNRTN
Solar/Wind Harmer
-0.076
3145796HORNRTN
Solar/Wind Harmer
-0.009
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.436
3145513AHOSKIE
Solar/Wind Harmer
0.208
961941AG1-037 GEN
Solar/Wind Harmer
0.179
3145513AHOSKIE
Solar/Wind Harmer
-0.024
970831AG2-522 GEN
Solar/Wind Harmer
11.922
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
971285AH1-108 GEN
Adder
1.59
971445AH1-216 GEN
Solar/Wind Harmer
14.631
316239AB2-077_GEN
Solar/Wind Harmer
0.706
316238AB2-078_GEN
Solar/Wind Harmer
0.706
3146033SCOT NK
Solar/Wind Harmer
-0.093
971443AH1-215 GEN
Solar/Wind Harmer
4.564
3144303KENBRDG
Solar/Wind Harmer
-0.019
970683AG2-441 GEN
Solar/Wind Harmer
18.002
970681AG2-440 GEN
Solar/Wind Harmer
14.401
972265AH1-717 GEN
Adder
15.866
3151201GRAVEL4
Adder
14.873
3151191GRAVEL3
Adder
14.685
3151211GRAVEL5
Adder
14.685
946301AF1-294 GEN
Solar/Wind Harmer
5.873
961791AG1-021 GEN
Solar/Wind Harmer
2.865
315657AE1-056 GEN
Solar/Wind Harmer
8.562
972205AH1-687 GEN
Adder
7.023
3142433PROV 92
Adder
0.305
3142433PROV 92
Adder
0.305
316164AC1-076 GEN
Solar/Wind Helper
1.276
970119AG2-088 GEN
50/50
40.916
315243AE2-183_GT3
50/50
4.579
3151051BRUNSWICKS1
50/50
7.473
3151021BRUNSWICKG1
50/50
3.601
971451AH1-221 GEN
50/50
10.937
3151531CLOVER1
50/50
5.026
3143226MDLTHAN
Solar/Wind Harmer
-0.034
940641AE2-051 GEN
Solar/Wind Harmer
29.864
939411AE1-173 GEN
Solar/Wind Harmer
150.793
970919AG2-571 GEN
Solar/Wind Harmer
9.333
970087AG2-069 GEN
Solar/Wind Harmer
27.522
3143526WINTERP
Solar/Wind Harmer
-0.152
3143336POWHATN
Solar/Wind Harmer
3.333
957481AF2-042 GEN
Solar/Wind Harmer
86.276
315693AD1-088 GEN
Solar/Wind Harmer
13.378
962491AG1-098 GEN
Solar/Wind Harmer
17.804
316336AC2-165 C
Solar/Wind Harmer
4.589
316023GEN1_S
Solar/Wind Harmer
1.714
944591AF1-124 GEN
Solar/Wind Harmer
115.211
316294AC1-161 GEN
Solar/Wind Harmer
8.131
316388AE2-253 GEN
Solar/Wind Harmer
1.685
3146456SLIGO L269
Solar/Wind Harmer
-0.025
316375AC2-012 GEN
Solar/Wind Harmer
8.622
3150981CHESPKA
Adder
2.768
960081AF2-299 GEN
Solar/Wind Harmer
2.801
316246AF1-032 C
Solar/Wind Harmer
0.503
316093AE2-104_GEN
Solar/Wind Harmer
7.211
970661AG2-428 GEN
Solar/Wind Harmer
26.234
316381AD1-082 GEN
Solar/Wind Harmer
2.262
3146516WINFALL
Solar/Wind Harmer
-0.079
3146516WINFALL
Solar/Wind Harmer
-0.025
970659AG2-427 GEN
Solar/Wind Harmer
13.1
315687AD1-152 GEN
Solar/Wind Harmer
2.972
971795AH1-408 GEN
Solar/Wind Harmer
18.452
315800Z1-036_GEN1
Solar/Wind Harmer
6.052
3147043LAWRENC
Adder
1.97
3130156CHOWAN
Solar/Wind Harmer
-0.024
316072AD1-144
Solar/Wind Harmer
0.491
316011AB1-132 GEN
Solar/Wind Harmer
5.061
962571AG1-106 GEN
Solar/Wind Harmer
3.477
3145663CRESWEL
Solar/Wind Harmer
-0.067
971163AH1-040 GEN
Solar/Wind Harmer
22.621
3145893MURPHYS
Solar/Wind Harmer
-0.096
3145893MURPHYS
Solar/Wind Harmer
0.714
316190AA2-174 GEN
Solar/Wind Harmer
0.294
3146173TUNIS
Solar/Wind Harmer
-0.024
3145783HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.078
3145796HORNRTN
Solar/Wind Harmer
-0.024
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
5.963
3146263WOODLND
Solar/Wind Harmer
-0.024
316129AC1-054 GEN
Solar/Wind Harmer
2.089
971065AG2-659 GEN
Solar/Wind Harmer
11.903
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145336SMITFLD
Solar/Wind Harmer
-0.094
3150851SPRUNCC
Adder
0.972
3145823KELFORD
Solar/Wind Harmer
-0.023
316237AB2-079_GEN
Solar/Wind Harmer
0.706
3145963POPLR C
Solar/Wind Harmer
-0.023
316212AC1-099_GEN
Solar/Wind Harmer
2.019
316174AB2-169 GEN
Solar/Wind Harmer
3.571
970685AG2-442 GEN
Solar/Wind Harmer
20.162
3151171GRAVELC
Adder
2.174
963171AG1-166 GEN
Solar/Wind Harmer
2.865
971563AH1-280 GEN
Solar/Wind Harmer
2.865
3144293JTRSVLE
Adder
0.649
315722AD1-056 GEN
Solar/Wind Harmer
2.391
315671AE2-027_GEN
Solar/Wind Harmer
17.138
3146293MARTNCO
Solar/Wind Harmer
0.141
961611AG1-000B GEN
Solar/Wind Harmer
11.191
3143096IRON208
Adder
0.735
944631AF1-128 GEN
Adder
81.193
3142433PROV 92
Adder
0.305
3142433PROV 92
Adder
0.305
3141843SHACKLE
Adder
0.762
3150351NORNECKC2
Adder
1.139
3147666LOUISA
Solar/Wind Helper
1.36
316192AB2-158 GEN
Solar/Wind Helper
2.271
316045AC1-158 PL2
Solar/Wind Helper
5.508
316254AC1-120 GEN1
Solar/Wind Helper
1.194
970401AG2-262 GEN
Solar/Wind Harmer
0.99
970533AG2-339 GEN
50/50
25.396
970531AG2-338 GEN
50/50
10.158
315242AE2-183_GT2
50/50
4.579
315241AE2-183_GT1
50/50
4.551
972185AH1-677 GEN
50/50
16.507
3151041BRUNSWICKG3
50/50
3.601
972187AH1-678 GEN
50/50
8.263
971223AH1-071 GEN
Solar/Wind Harmer
4.31
970933AG2-581 GEN
Solar/Wind Harmer
28.14
3143526WINTERP
Solar/Wind Harmer
-0.152
3144356SAPONY
Solar/Wind Harmer
0.965
970099AG2-077 GEN
Solar/Wind Harmer
34.511
316185AD1-033 GEN
Solar/Wind Harmer
2.642
3145506HICKORY
Solar/Wind Harmer
-0.1
3145506HICKORY
Solar/Wind Harmer
-0.06
3145506HICKORY
Solar/Wind Harmer
-0.015
3142956BIRDNECK
Solar/Wind Harmer
1.341
316339AD2-160 GEN
Solar/Wind Harmer
1.685
316316AC1-027 C
Solar/Wind Harmer
0.767
316018AA1-139 ULT2
Solar/Wind Harmer
2.14
316017AA1-139 ULT1
Solar/Wind Harmer
2.021
3137176SLIGO L2192
Solar/Wind Harmer
-0.099
3146456SLIGO L269
Solar/Wind Harmer
2.947
3130086AYDLETT
Solar/Wind Harmer
-0.099
316036AC1-147 C
Solar/Wind Harmer
0.672
3150991CHESPKB
Adder
2.323
3150991CHESPKB
Adder
2.267
3146386ELIZ CT
Solar/Wind Harmer
-0.025
971741AH1-377 GEN
Solar/Wind Harmer
28.815
316431W1029_GEN1
Solar/Wind Harmer
4.473
316433W1029_GEN2
Solar/Wind Harmer
4.473
970657AG2-426 GEN
Solar/Wind Harmer
7.711
970657AG2-426 GEN
Solar/Wind Harmer
1.613
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
315742AE1-103 GEN
Solar/Wind Harmer
2.566
316181AB2-040 GEN
Solar/Wind Harmer
3.416
3146376EDENTON
Solar/Wind Harmer
0.723
3146376EDENTON
Solar/Wind Harmer
0.723
970301AG2-198 GEN
Solar/Wind Harmer
12.1
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145893MURPHYS
Solar/Wind Harmer
0.672
3145893MURPHYS
Solar/Wind Harmer
-0.043
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
966811AG1-552 GEN
Solar/Wind Harmer
2.703
3145593CAROLNA
Solar/Wind Harmer
0.2
316426AA2-053 GEN
Solar/Wind Harmer
2.423
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
3145783HORNRTN
Solar/Wind Harmer
2.835
3145783HORNRTN
Solar/Wind Harmer
2.268
3145783HORNRTN
Solar/Wind Harmer
0.709
3145783HORNRTN
Solar/Wind Harmer
0.283
3145796HORNRTN
Solar/Wind Harmer
-0.071
316065AD1-022 GEN
Solar/Wind Harmer
11.938
316236AE1-162_GEN
Solar/Wind Harmer
0.715
939181AE1-148 GEN
Solar/Wind Harmer
13.315
313527AB2-043 GEN
Solar/Wind Harmer
3.812
970323AG2-213 GEN
Solar/Wind Harmer
11.586
971775AH1-396 GEN
Solar/Wind Harmer
1.65
316034AC1-036 C
Solar/Wind Harmer
0.43
316274AC1-208 GEN
Solar/Wind Harmer
2.497
958211AF2-115 GEN
Solar/Wind Harmer
3.581
963191AG1-168 GEN
Solar/Wind Harmer
2.149
3144293JTRSVLE
Adder
0.649
3144293JTRSVLE
Adder
0.547
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3145933PARMELE
Solar/Wind Harmer
-0.045
3145933PARMELE
Solar/Wind Harmer
-0.023
962561AG1-105 GEN
Solar/Wind Harmer
12.73
316240AF1-291 C
Solar/Wind Harmer
0.679
944641AF1-129 GEN
Adder
93.798
3142366NRTHEST
Adder
0.504
3150691DARBY 3
Adder
10.929
3150701DARBY 4
Adder
10.903
3150681DARBY 2
Adder
10.891
3150671DARBY 1
Adder
10.878
3142296MT RD221
Adder
0.387
3150341NORNECKC1
Adder
1.196
3150341NORNECKC1
Adder
1.186
316447AC1-158 HLD
Solar/Wind Helper
3.787
966001AG1-469 GEN
Solar/Wind Helper
0.322
315651AD1-115 GEN
Solar/Wind Helper
0.849
964791AG1-342 GEN
Solar/Wind Harmer
3.241
3151031BRUNSWICKG2
50/50
3.601
970413AG2-270 GEN
50/50
21.932
3151101ELIZAR3
50/50
21.884
970917AG2-570 GEN
Solar/Wind Harmer
73.734
316313AB2-026
Solar/Wind Harmer
0.757
316258AE1-075 C
Solar/Wind Harmer
0.682
316405AF2-144 C
Solar/Wind Harmer
0.719
3143336POWHATN
Solar/Wind Harmer
2.833
316478AD1-087 GEN
Solar/Wind Harmer
2.283
316486AD2-202 GEN
Solar/Wind Harmer
0.669
316365GEN2_N
Solar/Wind Harmer
1.714
944581AF1-123 GEN
Solar/Wind Harmer
114.798
944601AF1-125 GEN
Solar/Wind Harmer
113.006
315773AC2-141 GEN
Solar/Wind Harmer
10.516
3146456SLIGO L269
Solar/Wind Harmer
-0.025
971153AH1-033 GEN
Solar/Wind Harmer
3.041
3144873MCLAUGH
Solar/Wind Harmer
-0.001
966621AG1-532 GEN
Solar/Wind Harmer
0.505
316320Y1-086
Solar/Wind Harmer
1.455
316435W1029_GEN3
Solar/Wind Harmer
4.473
970661AG2-428 GEN
Solar/Wind Harmer
4.649
316083AB2-161 GEN
Solar/Wind Harmer
4.004
3146516WINFALL
Solar/Wind Harmer
-0.025
970659AG2-427 GEN
Solar/Wind Harmer
2.322
3145273HOLLAND
Solar/Wind Harmer
-0.018
315813AE1-149 C
Solar/Wind Harmer
15.384
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3144536CHRHLND
Solar/Wind Harmer
-0.004
313506AB2-031 GEN
Solar/Wind Harmer
1.969
3147043LAWRENC
Solar/Wind Harmer
-0.015
3146376EDENTON
Solar/Wind Harmer
-0.024
3156081AA2-088 GEN
Solar/Wind Harmer
7.869
970909AG2-566 GEN
Solar/Wind Harmer
2.298
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
315614AA2-178 GEN
Solar/Wind Harmer
2.603
3145893MURPHYS
Solar/Wind Harmer
0.168
3145893MURPHYS
Solar/Wind Harmer
-0.024
957521AF2-046 GEN
Solar/Wind Harmer
18.923
961681AG1-008 GEN
Solar/Wind Harmer
18.923
971157AH1-035 GEN
Solar/Wind Harmer
2.994
3146173TUNIS
Solar/Wind Harmer
-0.024
315737AD1-076 GEN
Solar/Wind Harmer
4.545
315839AE2-212 C
Solar/Wind Harmer
0.72
3145796HORNRTN
Solar/Wind Harmer
-0.095
3145796HORNRTN
Solar/Wind Harmer
-0.024
3146206CASHIE
Solar/Wind Harmer
-0.024
316463AE2-346 GEN
Solar/Wind Harmer
0.386
316140AB2-099
Solar/Wind Harmer
0.161
962331AG1-082 GEN
Solar/Wind Harmer
2.98
3146263WOODLND
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.202
3145336SMITFLD
Solar/Wind Harmer
-0.009
3150861SPRUNCD
Adder
0.972
316317KELFORD C
Solar/Wind Harmer
1.11
3145823KELFORD
Solar/Wind Harmer
-0.023
316131AB2-060 GEN
Solar/Wind Harmer
2.53
964241AG1-285 GEN
Solar/Wind Harmer
18.252
3145963POPLR C
Solar/Wind Harmer
-0.023
965281AG1-393 GEN
Solar/Wind Harmer
2.905
315785AD2-033 C
Solar/Wind Harmer
5.263
970257AG2-171 GEN
Solar/Wind Harmer
8.69
316210AC1-098 GEN
Solar/Wind Harmer
3.635
959311AF2-222 GEN
Solar/Wind Harmer
24.148
3151221GRAVEL6
Adder
14.856
3151171GRAVELC
Adder
2.858
963181AG1-167 GEN
Solar/Wind Harmer
2.149
3144293JTRSVLE
Adder
0.649
315724AD1-057 GEN
Solar/Wind Harmer
1.315
3147133PAMPLIN
Solar/Wind Harmer
-0.071
971193AH1-056 GEN
Solar/Wind Harmer
14.27
3145933PARMELE
Solar/Wind Harmer
-0.023
966801AG1-551 GEN
Solar/Wind Harmer
2.838
961611AG1-000B GEN
Solar/Wind Harmer
4.775
316327AA2-057 GEN
Solar/Wind Harmer
2.286
942461AE2-259 GEN
Solar/Wind Harmer
3.394
3144216WINCHST
Adder
0.715
3150921YORKTN3
Adder
4.706
3143096IRON208
Adder
0.735
3143096IRON208
Adder
0.72
3142433PROV 92
Adder
0.305
3142433PROV 92
Adder
0.305
3141843SHACKLE
Adder
0.762
3150351NORNECKC2
Adder
1.158
3147666LOUISA
Solar/Wind Helper
0.782
316044AC1-158 PL1
Solar/Wind Helper
1.721
316450AC1-158 RIC
Solar/Wind Helper
0.459
3132273ORANGE
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.398
CPLELTFEXP_CPLE->PJM
CLTF
13.285
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.607
LAGNLTFEXP_LAGN->PJM
CLTF
9.537
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.961
TVALTFEXP_TVA->PJM
CLTF
4.788
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.685
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.441
MECLTFEXP_MEC->PJM
CLTF
4.694
SIGELTFEXP_SIGE->PJM
CLTF
0.142
NYPJM->LTFIMP_NY
CLTF
2.522
LGEELTFEXP_LGEE->PJM
CLTF
1.726
WECLTFEXP_WEC->PJM
CLTF
0.88

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.73 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5687.33
MW Contribution:46.45
Bus #Bus NameTypeMW Contribution
3151041BRUNSWICKG3
50/50
8.505
972187AH1-678 GEN
50/50
19.517
315242AE2-183_GT2
50/50
10.667
315241AE2-183_GT1
50/50
10.602
972185AH1-677 GEN
50/50
38.457
970533AG2-339 GEN
50/50
57.391
970531AG2-338 GEN
50/50
22.956
3152661PLYWOOD A
50/50
0.751
970535AG2-341 GEN
50/50
5.149
3144293JTRSVLE
50/50
0.914
3144293JTRSVLE
50/50
0.769
970933AG2-581 GEN
Solar/Wind Harmer
51.542
970099AG2-077 GEN
Solar/Wind Harmer
57.884
971741AH1-377 GEN
Solar/Wind Harmer
38.437
970301AG2-198 GEN
Solar/Wind Harmer
15.165
3146843MT LREL
Solar/Wind Harmer
0.321
3146843MT LREL
Solar/Wind Harmer
0.321
964791AG1-342 GEN
Solar/Wind Harmer
6.159
962561AG1-105 GEN
Solar/Wind Harmer
15.15
316222AC1-221 GEN
Solar/Wind Harmer
1.267
939181AE1-148 GEN
Solar/Wind Harmer
13.97
313527AB2-043 GEN
Solar/Wind Harmer
0.004
970323AG2-213 GEN
Solar/Wind Harmer
11.867
971775AH1-396 GEN
Solar/Wind Harmer
0.445
316034AC1-036 C
Solar/Wind Harmer
0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.246
963191AG1-168 GEN
Solar/Wind Harmer
1.082
3147133PAMPLIN
Solar/Wind Harmer
0.268
3147133PAMPLIN
Solar/Wind Harmer
0.214
942751AE2-291 GEN
Solar/Wind Harmer
12.744
270013AE1-250 PV
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.64
3146776BUCKING
Solar/Wind Harmer
0.052
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
3.595
316263AC1-034 GEN
Solar/Wind Harmer
4.676
961601AG1-000A GEN
Solar/Wind Harmer
2.136
316036AC1-147 C
Solar/Wind Helper
0.621
3142956BIRDNECK
Solar/Wind Helper
0.272
316316AC1-027 C
Solar/Wind Helper
0.638
316185AD1-033 GEN
Solar/Wind Helper
1.893
3145506HICKORY
Solar/Wind Helper
1.587
3145506HICKORY
Solar/Wind Helper
0.952
3145506HICKORY
Solar/Wind Helper
0.238
316236AE1-162_GEN
Solar/Wind Helper
0.529
316339AD2-160 GEN
Solar/Wind Helper
1.472
316018AA1-139 ULT2
Solar/Wind Helper
1.65
316017AA1-139 ULT1
Solar/Wind Helper
1.754
3137176SLIGO L2192
Solar/Wind Helper
1.508
3130086AYDLETT
Solar/Wind Helper
1.498
316033AB2-134 GEN
Solar/Wind Helper
1.287
315697AD1-025 GEN
Solar/Wind Helper
4.277
316240AF1-291 C
Solar/Wind Helper
0.501
3146386ELIZ CT
Solar/Wind Helper
0.35
3142946ENON
Solar/Wind Helper
0.034
316487AF1-042 GEN
Solar/Wind Helper
0.339
3144356SAPONY
Solar/Wind Helper
0.597
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.305
316431W1029_GEN1
Solar/Wind Helper
1.295
316433W1029_GEN2
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
966871AG1-558 GEN
Solar/Wind Helper
0.403
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
316468AD1-105 GEN
Solar/Wind Helper
1.402
315742AE1-103 GEN
Solar/Wind Helper
0.368
963041AG1-153 GEN
50/50
17.22
315244AE2-183_ST
50/50
18.443
3151541CLOVER2
50/50
10.593
3151611KERR 4
50/50
0.604
3151621KERR 5
50/50
0.604
3151631KERR 6
50/50
0.604
3151641KERR 7
50/50
0.604
971967AH1-528 GEN
Solar/Wind Harmer
109.53
970673AG2-436 GEN
Solar/Wind Harmer
137.75
970673AG2-436 GEN
Solar/Wind Harmer
91.833
941031AE2-094 GEN
Solar/Wind Harmer
118.914
944011AF1-069 GEN
Solar/Wind Harmer
38.854
970085AG2-068 GEN
Solar/Wind Harmer
32.15
970581AG2-369 GEN
Solar/Wind Harmer
27.649
3147173SINAI
Solar/Wind Harmer
0.345
3147243WELCO
Solar/Wind Harmer
0.216
316118AC1-105 GEN
Solar/Wind Harmer
0.86
970865AG2-541 GEN
Solar/Wind Harmer
10.119
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.678
3144303KENBRDG
Solar/Wind Harmer
0.222
970683AG2-441 GEN
Solar/Wind Harmer
18.278
970681AG2-440 GEN
Solar/Wind Harmer
14.623
946301AF1-294 GEN
Solar/Wind Harmer
5.338
961791AG1-021 GEN
Solar/Wind Harmer
2.597
315657AE1-056 GEN
Solar/Wind Harmer
9.239
316123AC1-075 GEN
Solar/Wind Harmer
0.351
970165AG2-112 GEN
Solar/Wind Harmer
2.08
970163AG2-111 GEN
Solar/Wind Harmer
1.985
970831AG2-522 GEN
Solar/Wind Harmer
8.286
970285AG2-188 GEN
Solar/Wind Harmer
14.461
971845AH1-439 GEN
Solar/Wind Harmer
7.612
270069AE2-166 C O1
Solar/Wind Harmer
0.005
3143316POE
Solar/Wind Helper
1.64
319010AE1-072 C
Solar/Wind Helper
4.299
316369SG1_INVT
Solar/Wind Helper
1.8
316305AF2-043 C
Solar/Wind Helper
0.499
316132AB2-190 GEN1
Solar/Wind Helper
2.107
957831AF2-077 GEN
Solar/Wind Helper
0.495
316349AD2-085 GEN
Solar/Wind Helper
1.649
313526AB2-022
Solar/Wind Helper
0.533
957601AF2-054 GEN
Solar/Wind Helper
0.467
3141873WAN 176
Solar/Wind Helper
0.07
315662AE1-191 GEN
Solar/Wind Helper
1.865
315666AE1-190 GEN
Solar/Wind Helper
0.466
316059AD1-063 C
Solar/Wind Helper
0.348
3141913WHIT STONE
Solar/Wind Helper
0.345
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.137
3146486SUNBURY
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.341
316321Z2-027
Solar/Wind Helper
0.514
3145176PASQUOTANK
Solar/Wind Helper
0.209
316315AB2-025 C
Solar/Wind Helper
0.507
3141813NORNECK
Solar/Wind Helper
0.325
316312AB1-027
Solar/Wind Helper
0.597
316233AE1-074 FULL
Solar/Wind Helper
0.469
316223AC1-118
Solar/Wind Helper
0.466
315611Z1-036_GEN2
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
3151031BRUNSWICKG2
50/50
8.505
970413AG2-270 GEN
50/50
46.449
3151591KERR 2
50/50
0.604
3144293JTRSVLE
50/50
0.914
970917AG2-570 GEN
Solar/Wind Harmer
53.965
316478AD1-087 GEN
Solar/Wind Harmer
1.733
316486AD2-202 GEN
Solar/Wind Harmer
0.509
970909AG2-566 GEN
Solar/Wind Harmer
3.791
316248AF1-058 C
Solar/Wind Harmer
0.003
960061AF2-297 GEN
Solar/Wind Harmer
14.727
971683AH1-343 GEN
Solar/Wind Harmer
11.379
316283AC2-100 C
Solar/Wind Harmer
0.592
316131AB2-060 GEN
Solar/Wind Harmer
0.901
964241AG1-285 GEN
Solar/Wind Harmer
18.92
315785AD2-033 C
Solar/Wind Harmer
2.274
970257AG2-171 GEN
Solar/Wind Harmer
8.9
959311AF2-222 GEN
Solar/Wind Harmer
24.62
963181AG1-167 GEN
Solar/Wind Harmer
1.082
3147133PAMPLIN
Solar/Wind Harmer
0.841
971193AH1-056 GEN
Solar/Wind Harmer
16.311
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
3146926FARMVIL
Solar/Wind Harmer
0.151
3146776BUCKING
Solar/Wind Harmer
0.058
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
1.012
3147312GRETNA
Solar/Wind Harmer
0.029
941821AE2-187 GEN
Solar/Wind Harmer
4.622
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.004
3145543BTLEBRO
Solar/Wind Harmer
0.123
3145543BTLEBRO
Solar/Wind Harmer
0.123
971623AH1-311 GEN
Solar/Wind Harmer
0.246
961601AG1-000A GEN
Solar/Wind Harmer
8.544
315773AC2-141 GEN
Solar/Wind Helper
9.595
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3145336SMITFLD
Solar/Wind Helper
0.157
315839AE2-212 C
Solar/Wind Helper
0.523
3146456SLIGO L269
Solar/Wind Helper
0.379
316382AG1-145 C
Solar/Wind Helper
0.498
316320Y1-086
Solar/Wind Helper
0.156
316156AD2-030 GEN
Solar/Wind Helper
0.525
316280AD1-041 GEN
Solar/Wind Helper
1.166
3142946ENON
Solar/Wind Helper
0.114
316484AD2-074 GEN
Solar/Wind Helper
0.648
316404AE1-155 C
Solar/Wind Helper
2.8
316435W1029_GEN3
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3141906WESTMOR
Solar/Wind Helper
0.122
316473AC1-191 GEN
Solar/Wind Helper
1.829
3146626S HERTFORD
Solar/Wind Helper
0.296
3145273HOLLAND
Solar/Wind Helper
0.201
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.24
3151051BRUNSWICKS1
50/50
17.651
3151021BRUNSWICKG1
50/50
8.505
971451AH1-221 GEN
50/50
25.831
315243AE2-183_GT3
50/50
10.667
3151531CLOVER1
50/50
10.644
3151601KERR 3
50/50
0.604
3151581KERR 1
50/50
0.216
3144293JTRSVLE
50/50
0.914
971629AH1-314 GEN
50/50
19.06
3151561HALLBR1
50/50
0.404
970919AG2-571 GEN
Solar/Wind Harmer
21.586
970087AG2-069 GEN
Solar/Wind Harmer
48.225
957481AF2-042 GEN
Solar/Wind Harmer
144.711
315693AD1-088 GEN
Solar/Wind Harmer
23.762
962491AG1-098 GEN
Solar/Wind Harmer
27.839
315687AD1-152 GEN
Solar/Wind Harmer
0.015
316003AC1-222 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.882
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
20.472
963171AG1-166 GEN
Solar/Wind Harmer
1.443
971563AH1-280 GEN
Solar/Wind Harmer
2.885
3146926FARMVIL
Solar/Wind Harmer
0.151
971065AG2-659 GEN
Solar/Wind Harmer
9.511
316129AC1-054 GEN
Solar/Wind Harmer
0.786
970223AG2-152 GEN
Solar/Wind Harmer
12.908
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.097
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.064
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.115
3146802CHATHAM
Solar/Wind Harmer
0.108
941801AE2-185 GEN
Solar/Wind Harmer
4.622
270030AE2-140 GEN
Solar/Wind Harmer
14.688
3145543BTLEBRO
Solar/Wind Harmer
0.123
3145543BTLEBRO
Solar/Wind Harmer
0.099
316359AB2-059 GEN
Solar/Wind Harmer
0.442
316049AB1-081 GEN
Solar/Wind Harmer
0.704
3142053HEARTS
Solar/Wind Harmer
0.217
316294AC1-161 GEN
Solar/Wind Helper
8.153
316375AC2-012 GEN
Solar/Wind Helper
1.068
3145336SMITFLD
Solar/Wind Helper
1.575
316388AE2-253 GEN
Solar/Wind Helper
1.472
3146456SLIGO L269
Solar/Wind Helper
0.379
316381AD1-082 GEN
Solar/Wind Helper
1.955
316072AD1-144
Solar/Wind Helper
0.428
316246AF1-032 C
Solar/Wind Helper
0.424
316159AE1-175 C
Solar/Wind Helper
0.562
316458AB2-190 GEN2
Solar/Wind Helper
2.107
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.376
3138133OCRAN
Solar/Wind Helper
0.206
3142543TWELFTH
Solar/Wind Helper
0.032
964211AG1-282 GEN
Solar/Wind Helper
0.439
3141726DUNNSVL
Solar/Wind Helper
1.304
316337AD2-073 GEN
Solar/Wind Helper
0.478
3142416OLDCHRC
Solar/Wind Helper
0.816
3142416OLDCHRC
Solar/Wind Helper
0.312
3146516WINFALL
Solar/Wind Helper
1.016
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
3143226MDLTHAN
Solar/Wind Helper
0.3
315800Z1-036_GEN1
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
CPLELTFEXP_CPLE->PJM
CLTF
20.639
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.343
LAGNLTFEXP_LAGN->PJM
CLTF
15.403
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.288
TVALTFEXP_TVA->PJM
CLTF
7.684
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.447
MECLTFEXP_MEC->PJM
CLTF
7.78
SIGELTFEXP_SIGE->PJM
CLTF
0.233
NYPJM->LTFIMP_NY
CLTF
2.484
LGEELTFEXP_LGEE->PJM
CLTF
2.833
WECLTFEXP_WEC->PJM
CLTF
1.482
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.78 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5445.28
MW Contribution:46.45
Bus #Bus NameTypeMW Contribution
963041AG1-153 GEN
50/50
17.22
315244AE2-183_ST
50/50
18.443
3151541CLOVER2
50/50
10.593
3151611KERR 4
50/50
0.604
3151621KERR 5
50/50
0.604
3151631KERR 6
50/50
0.604
3151641KERR 7
50/50
0.604
971967AH1-528 GEN
Solar/Wind Harmer
109.53
970673AG2-436 GEN
Solar/Wind Harmer
137.75
970673AG2-436 GEN
Solar/Wind Harmer
91.833
970085AG2-068 GEN
Solar/Wind Harmer
32.15
970581AG2-369 GEN
Solar/Wind Harmer
27.649
3147173SINAI
Solar/Wind Harmer
0.345
3147243WELCO
Solar/Wind Harmer
0.216
316118AC1-105 GEN
Solar/Wind Harmer
0.86
970865AG2-541 GEN
Solar/Wind Harmer
10.119
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.678
3144303KENBRDG
Solar/Wind Harmer
0.222
970683AG2-441 GEN
Solar/Wind Harmer
18.278
970681AG2-440 GEN
Solar/Wind Harmer
14.623
946301AF1-294 GEN
Solar/Wind Harmer
5.338
961791AG1-021 GEN
Solar/Wind Harmer
2.597
315657AE1-056 GEN
Solar/Wind Harmer
9.239
316123AC1-075 GEN
Solar/Wind Harmer
0.351
970165AG2-112 GEN
Solar/Wind Harmer
2.08
970163AG2-111 GEN
Solar/Wind Harmer
1.985
970831AG2-522 GEN
Solar/Wind Harmer
8.286
970285AG2-188 GEN
Solar/Wind Harmer
14.461
971845AH1-439 GEN
Solar/Wind Harmer
7.612
270069AE2-166 C O1
Solar/Wind Harmer
0.005
3143316POE
Solar/Wind Helper
1.64
319010AE1-072 C
Solar/Wind Helper
4.299
316369SG1_INVT
Solar/Wind Helper
1.8
316305AF2-043 C
Solar/Wind Helper
0.499
316132AB2-190 GEN1
Solar/Wind Helper
2.107
3151051BRUNSWICKS1
50/50
17.651
3151021BRUNSWICKG1
50/50
8.505
971451AH1-221 GEN
50/50
25.831
315243AE2-183_GT3
50/50
10.667
3151531CLOVER1
50/50
10.644
3151601KERR 3
50/50
0.604
3151581KERR 1
50/50
0.216
3144293JTRSVLE
50/50
0.914
971629AH1-314 GEN
50/50
19.06
3151561HALLBR1
50/50
0.404
970919AG2-571 GEN
Solar/Wind Harmer
21.586
970087AG2-069 GEN
Solar/Wind Harmer
48.225
957481AF2-042 GEN
Solar/Wind Harmer
144.711
315693AD1-088 GEN
Solar/Wind Harmer
23.762
962491AG1-098 GEN
Solar/Wind Harmer
27.839
315687AD1-152 GEN
Solar/Wind Harmer
0.015
316003AC1-222 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.882
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
20.472
963171AG1-166 GEN
Solar/Wind Harmer
1.443
971563AH1-280 GEN
Solar/Wind Harmer
2.885
3146926FARMVIL
Solar/Wind Harmer
0.151
971065AG2-659 GEN
Solar/Wind Harmer
9.511
316129AC1-054 GEN
Solar/Wind Harmer
0.786
970223AG2-152 GEN
Solar/Wind Harmer
12.908
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.097
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.064
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.115
3146802CHATHAM
Solar/Wind Harmer
0.108
941801AE2-185 GEN
Solar/Wind Harmer
4.622
270030AE2-140 GEN
Solar/Wind Harmer
14.688
3145543BTLEBRO
Solar/Wind Harmer
0.123
3145543BTLEBRO
Solar/Wind Harmer
0.099
316359AB2-059 GEN
Solar/Wind Harmer
0.442
316049AB1-081 GEN
Solar/Wind Harmer
0.704
3142053HEARTS
Solar/Wind Harmer
0.217
316294AC1-161 GEN
Solar/Wind Helper
8.153
957831AF2-077 GEN
Solar/Wind Helper
0.495
316349AD2-085 GEN
Solar/Wind Helper
1.649
313526AB2-022
Solar/Wind Helper
0.533
957601AF2-054 GEN
Solar/Wind Helper
0.467
3141873WAN 176
Solar/Wind Helper
0.07
315662AE1-191 GEN
Solar/Wind Helper
1.865
3151031BRUNSWICKG2
50/50
8.505
970413AG2-270 GEN
50/50
46.449
3151591KERR 2
50/50
0.604
3144293JTRSVLE
50/50
0.914
970917AG2-570 GEN
Solar/Wind Harmer
53.965
316478AD1-087 GEN
Solar/Wind Harmer
1.733
316486AD2-202 GEN
Solar/Wind Harmer
0.509
970909AG2-566 GEN
Solar/Wind Harmer
3.791
316248AF1-058 C
Solar/Wind Harmer
0.003
960061AF2-297 GEN
Solar/Wind Harmer
14.727
971683AH1-343 GEN
Solar/Wind Harmer
11.379
316283AC2-100 C
Solar/Wind Harmer
0.592
316131AB2-060 GEN
Solar/Wind Harmer
0.901
964241AG1-285 GEN
Solar/Wind Harmer
18.92
315785AD2-033 C
Solar/Wind Harmer
2.274
970257AG2-171 GEN
Solar/Wind Harmer
8.9
959311AF2-222 GEN
Solar/Wind Harmer
24.62
963181AG1-167 GEN
Solar/Wind Harmer
1.082
3147133PAMPLIN
Solar/Wind Harmer
0.841
971193AH1-056 GEN
Solar/Wind Harmer
16.311
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
3146926FARMVIL
Solar/Wind Harmer
0.151
3146776BUCKING
Solar/Wind Harmer
0.058
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
1.012
3147312GRETNA
Solar/Wind Harmer
0.029
941821AE2-187 GEN
Solar/Wind Harmer
4.622
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.004
3145543BTLEBRO
Solar/Wind Harmer
0.123
3145543BTLEBRO
Solar/Wind Harmer
0.123
971623AH1-311 GEN
Solar/Wind Harmer
0.246
961601AG1-000A GEN
Solar/Wind Harmer
8.544
315773AC2-141 GEN
Solar/Wind Helper
9.595
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3145336SMITFLD
Solar/Wind Helper
0.157
316375AC2-012 GEN
Solar/Wind Helper
1.068
3145336SMITFLD
Solar/Wind Helper
1.575
316388AE2-253 GEN
Solar/Wind Helper
1.472
3146456SLIGO L269
Solar/Wind Helper
0.379
316381AD1-082 GEN
Solar/Wind Helper
1.955
316072AD1-144
Solar/Wind Helper
0.428
316246AF1-032 C
Solar/Wind Helper
0.424
316159AE1-175 C
Solar/Wind Helper
0.562
316458AB2-190 GEN2
Solar/Wind Helper
2.107
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.376
3138133OCRAN
Solar/Wind Helper
0.206
3142543TWELFTH
Solar/Wind Helper
0.032
964211AG1-282 GEN
Solar/Wind Helper
0.439
3141726DUNNSVL
Solar/Wind Helper
1.304
316337AD2-073 GEN
Solar/Wind Helper
0.478
3142416OLDCHRC
Solar/Wind Helper
0.816
3142416OLDCHRC
Solar/Wind Helper
0.312
3146516WINFALL
Solar/Wind Helper
1.016
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
3143226MDLTHAN
Solar/Wind Helper
0.3
315800Z1-036_GEN1
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3151041BRUNSWICKG3
50/50
8.505
972187AH1-678 GEN
50/50
19.517
315242AE2-183_GT2
50/50
10.667
315241AE2-183_GT1
50/50
10.602
972185AH1-677 GEN
50/50
38.457
3152661PLYWOOD A
50/50
0.751
970535AG2-341 GEN
50/50
5.149
3144293JTRSVLE
50/50
0.914
3144293JTRSVLE
50/50
0.769
970933AG2-581 GEN
Solar/Wind Harmer
51.542
970099AG2-077 GEN
Solar/Wind Harmer
57.884
971741AH1-377 GEN
Solar/Wind Harmer
38.437
970301AG2-198 GEN
Solar/Wind Harmer
15.165
3146843MT LREL
Solar/Wind Harmer
0.321
3146843MT LREL
Solar/Wind Harmer
0.321
964791AG1-342 GEN
Solar/Wind Harmer
6.159
962561AG1-105 GEN
Solar/Wind Harmer
15.15
316222AC1-221 GEN
Solar/Wind Harmer
1.267
939181AE1-148 GEN
Solar/Wind Harmer
13.97
313527AB2-043 GEN
Solar/Wind Harmer
0.004
970323AG2-213 GEN
Solar/Wind Harmer
11.867
971775AH1-396 GEN
Solar/Wind Harmer
0.445
316034AC1-036 C
Solar/Wind Harmer
0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.246
963191AG1-168 GEN
Solar/Wind Harmer
1.082
3147133PAMPLIN
Solar/Wind Harmer
0.268
3147133PAMPLIN
Solar/Wind Harmer
0.214
942751AE2-291 GEN
Solar/Wind Harmer
12.744
270013AE1-250 PV
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.64
3146776BUCKING
Solar/Wind Harmer
0.052
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
3.595
316263AC1-034 GEN
Solar/Wind Harmer
4.676
961601AG1-000A GEN
Solar/Wind Harmer
2.136
316036AC1-147 C
Solar/Wind Helper
0.621
3142956BIRDNECK
Solar/Wind Helper
0.272
316316AC1-027 C
Solar/Wind Helper
0.638
316185AD1-033 GEN
Solar/Wind Helper
1.893
3145506HICKORY
Solar/Wind Helper
1.587
3145506HICKORY
Solar/Wind Helper
0.952
3145506HICKORY
Solar/Wind Helper
0.238
316236AE1-162_GEN
Solar/Wind Helper
0.529
316339AD2-160 GEN
Solar/Wind Helper
1.472
316018AA1-139 ULT2
Solar/Wind Helper
1.65
316017AA1-139 ULT1
Solar/Wind Helper
1.754
3137176SLIGO L2192
Solar/Wind Helper
1.508
3130086AYDLETT
Solar/Wind Helper
1.498
316033AB2-134 GEN
Solar/Wind Helper
1.287
315697AD1-025 GEN
Solar/Wind Helper
4.277
316240AF1-291 C
Solar/Wind Helper
0.501
3146386ELIZ CT
Solar/Wind Helper
0.35
3142946ENON
Solar/Wind Helper
0.034
316487AF1-042 GEN
Solar/Wind Helper
0.339
3144356SAPONY
Solar/Wind Helper
0.597
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.305
316431W1029_GEN1
Solar/Wind Helper
1.295
316433W1029_GEN2
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
966871AG1-558 GEN
Solar/Wind Helper
0.403
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
316468AD1-105 GEN
Solar/Wind Helper
1.402
315742AE1-103 GEN
Solar/Wind Helper
0.368
315839AE2-212 C
Solar/Wind Helper
0.523
3146456SLIGO L269
Solar/Wind Helper
0.379
316382AG1-145 C
Solar/Wind Helper
0.498
316320Y1-086
Solar/Wind Helper
0.156
316156AD2-030 GEN
Solar/Wind Helper
0.525
316280AD1-041 GEN
Solar/Wind Helper
1.166
3142946ENON
Solar/Wind Helper
0.114
316484AD2-074 GEN
Solar/Wind Helper
0.648
316404AE1-155 C
Solar/Wind Helper
2.8
316435W1029_GEN3
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3141906WESTMOR
Solar/Wind Helper
0.122
316473AC1-191 GEN
Solar/Wind Helper
1.829
3146626S HERTFORD
Solar/Wind Helper
0.296
3145273HOLLAND
Solar/Wind Helper
0.201
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.24
315666AE1-190 GEN
Solar/Wind Helper
0.466
316059AD1-063 C
Solar/Wind Helper
0.348
3141913WHIT STONE
Solar/Wind Helper
0.345
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.137
3146486SUNBURY
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.341
316321Z2-027
Solar/Wind Helper
0.514
3145176PASQUOTANK
Solar/Wind Helper
0.209
316315AB2-025 C
Solar/Wind Helper
0.507
3141813NORNECK
Solar/Wind Helper
0.325
316312AB1-027
Solar/Wind Helper
0.597
316233AE1-074 FULL
Solar/Wind Helper
0.469
316223AC1-118
Solar/Wind Helper
0.466
315611Z1-036_GEN2
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
CPLELTFEXP_CPLE->PJM
CLTF
20.639
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.343
LAGNLTFEXP_LAGN->PJM
CLTF
15.403
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.288
TVALTFEXP_TVA->PJM
CLTF
7.684
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.447
MECLTFEXP_MEC->PJM
CLTF
7.78
SIGELTFEXP_SIGE->PJM
CLTF
0.233
NYPJM->LTFIMP_NY
CLTF
2.484
LGEELTFEXP_LGEE->PJM
CLTF
2.833
WECLTFEXP_WEC->PJM
CLTF
1.482
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 58572_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 58572_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.04 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:6196.95
MW Contribution:46.45
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
8.505
970413AG2-270 GEN
50/50
46.449
3151591KERR 2
50/50
0.604
3144293JTRSVLE
50/50
0.914
970917AG2-570 GEN
Solar/Wind Harmer
170.53
316478AD1-087 GEN
Solar/Wind Harmer
4.831
3151051BRUNSWICKS1
50/50
17.651
3151021BRUNSWICKG1
50/50
8.505
971451AH1-221 GEN
50/50
25.831
315243AE2-183_GT3
50/50
10.667
3151531CLOVER1
50/50
10.644
3151601KERR 3
50/50
0.604
3151581KERR 1
50/50
0.216
3144293JTRSVLE
50/50
0.914
971629AH1-314 GEN
50/50
19.06
3151561HALLBR1
50/50
0.404
970919AG2-571 GEN
Solar/Wind Harmer
21.586
970087AG2-069 GEN
Solar/Wind Harmer
63.496
957481AF2-042 GEN
Solar/Wind Harmer
190.536
315693AD1-088 GEN
Solar/Wind Harmer
27.811
962491AG1-098 GEN
Solar/Wind Harmer
36.654
315687AD1-152 GEN
Solar/Wind Harmer
6.022
316003AC1-222 GEN
Solar/Wind Harmer
3.575
970401AG2-262 GEN
Solar/Wind Harmer
2.352
316237AB2-079_GEN
Solar/Wind Harmer
0.978
970685AG2-442 GEN
Solar/Wind Harmer
26.954
963171AG1-166 GEN
Solar/Wind Harmer
3.799
971563AH1-280 GEN
Solar/Wind Harmer
3.799
3146926FARMVIL
Solar/Wind Harmer
-0.017
971065AG2-659 GEN
Solar/Wind Harmer
12.523
316129AC1-054 GEN
Solar/Wind Harmer
2.059
970223AG2-152 GEN
Solar/Wind Harmer
18.408
270016AE1-250 BESS
Solar/Wind Harmer
3.042
3147123OTTER R
Solar/Wind Harmer
-0.011
316322AB2-045
Solar/Wind Harmer
0.605
3146776BUCKING
Solar/Wind Harmer
-0.007
270574AD1-017 GEN2
Solar/Wind Harmer
5.998
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
941801AE2-185 GEN
Solar/Wind Harmer
6.086
270030AE2-140 GEN
Solar/Wind Harmer
21.053
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.864
316049AB1-081 GEN
Solar/Wind Harmer
1.492
3142053HEARTS
Solar/Wind Harmer
0.163
316294AC1-161 GEN
Solar/Wind Helper
8.153
316375AC2-012 GEN
Solar/Wind Helper
1.068
3145336SMITFLD
Solar/Wind Helper
1.575
316388AE2-253 GEN
Solar/Wind Helper
1.472
3146456SLIGO L269
Solar/Wind Helper
0.379
316381AD1-082 GEN
Solar/Wind Helper
1.955
316072AD1-144
Solar/Wind Helper
0.428
316246AF1-032 C
Solar/Wind Helper
0.424
316159AE1-175 C
Solar/Wind Helper
0.562
316458AB2-190 GEN2
Solar/Wind Helper
2.107
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.376
3138133OCRAN
Solar/Wind Helper
0.206
3142543TWELFTH
Solar/Wind Helper
0.032
964211AG1-282 GEN
Solar/Wind Helper
0.439
3141726DUNNSVL
Solar/Wind Helper
1.304
316337AD2-073 GEN
Solar/Wind Helper
0.478
3142416OLDCHRC
Solar/Wind Helper
0.816
3142416OLDCHRC
Solar/Wind Helper
0.312
3146516WINFALL
Solar/Wind Helper
1.016
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
3143226MDLTHAN
Solar/Wind Helper
0.3
315800Z1-036_GEN1
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
316486AD2-202 GEN
Solar/Wind Harmer
1.415
970909AG2-566 GEN
Solar/Wind Harmer
3.791
316248AF1-058 C
Solar/Wind Harmer
1.169
960061AF2-297 GEN
Solar/Wind Harmer
19.391
971683AH1-343 GEN
Solar/Wind Harmer
14.982
316283AC2-100 C
Solar/Wind Harmer
3.205
316131AB2-060 GEN
Solar/Wind Harmer
3.471
964241AG1-285 GEN
Solar/Wind Harmer
24.911
315785AD2-033 C
Solar/Wind Harmer
7.122
970257AG2-171 GEN
Solar/Wind Harmer
11.718
959311AF2-222 GEN
Solar/Wind Harmer
32.481
963181AG1-167 GEN
Solar/Wind Harmer
2.849
3147133PAMPLIN
Solar/Wind Harmer
-0.094
971193AH1-056 GEN
Solar/Wind Harmer
18.811
942461AE2-259 GEN
Solar/Wind Harmer
4.399
3146926FARMVIL
Solar/Wind Harmer
-0.017
3146776BUCKING
Solar/Wind Harmer
-0.006
270018AE2-047 C O1
Solar/Wind Harmer
1.466
270197AD1-017 GEN1
Solar/Wind Harmer
1.802
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
6.086
943811AF1-049 GEN
Solar/Wind Harmer
4.09
270336AE1-100 GEN
Solar/Wind Harmer
1.669
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
5.373
315773AC2-141 GEN
Solar/Wind Helper
9.595
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3145336SMITFLD
Solar/Wind Helper
0.157
315839AE2-212 C
Solar/Wind Helper
0.523
3146456SLIGO L269
Solar/Wind Helper
0.379
316382AG1-145 C
Solar/Wind Helper
0.498
316320Y1-086
Solar/Wind Helper
0.156
316156AD2-030 GEN
Solar/Wind Helper
0.525
316280AD1-041 GEN
Solar/Wind Helper
1.166
3142946ENON
Solar/Wind Helper
0.114
316484AD2-074 GEN
Solar/Wind Helper
0.648
316404AE1-155 C
Solar/Wind Helper
2.8
316435W1029_GEN3
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3141906WESTMOR
Solar/Wind Helper
0.122
316473AC1-191 GEN
Solar/Wind Helper
1.829
3146626S HERTFORD
Solar/Wind Helper
0.296
3145273HOLLAND
Solar/Wind Helper
0.201
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.24
963041AG1-153 GEN
50/50
17.22
315244AE2-183_ST
50/50
18.443
3151541CLOVER2
50/50
10.593
3151611KERR 4
50/50
0.604
3151621KERR 5
50/50
0.604
3151631KERR 6
50/50
0.604
3151641KERR 7
50/50
0.604
971967AH1-528 GEN
Solar/Wind Harmer
144.6
970673AG2-436 GEN
Solar/Wind Harmer
152.413
970673AG2-436 GEN
Solar/Wind Harmer
77.171
941031AE2-094 GEN
Solar/Wind Harmer
136.017
944011AF1-069 GEN
Solar/Wind Harmer
42.619
970085AG2-068 GEN
Solar/Wind Harmer
42.331
970581AG2-369 GEN
Solar/Wind Harmer
36.404
3147173SINAI
Solar/Wind Harmer
-0.039
3147243WELCO
Solar/Wind Harmer
-0.024
316118AC1-105 GEN
Solar/Wind Harmer
2.575
970865AG2-541 GEN
Solar/Wind Harmer
13.323
316239AB2-077_GEN
Solar/Wind Harmer
0.978
316238AB2-078_GEN
Solar/Wind Harmer
0.978
971443AH1-215 GEN
Solar/Wind Harmer
6.159
3144303KENBRDG
Solar/Wind Harmer
-0.025
970683AG2-441 GEN
Solar/Wind Harmer
24.066
970681AG2-440 GEN
Solar/Wind Harmer
19.253
946301AF1-294 GEN
Solar/Wind Harmer
7.788
961791AG1-021 GEN
Solar/Wind Harmer
3.799
315657AE1-056 GEN
Solar/Wind Harmer
11.287
316123AC1-075 GEN
Solar/Wind Harmer
3.111
970165AG2-112 GEN
Solar/Wind Harmer
2.739
970163AG2-111 GEN
Solar/Wind Harmer
2.613
270455AD2-022 GEN
Solar/Wind Harmer
5.008
270457AD2-023 GEN
Solar/Wind Harmer
2.539
970831AG2-522 GEN
Solar/Wind Harmer
10.909
970285AG2-188 GEN
Solar/Wind Harmer
17.971
971845AH1-439 GEN
Solar/Wind Harmer
10.023
270069AE2-166 C O1
Solar/Wind Harmer
2.578
3143316POE
Solar/Wind Helper
1.64
319010AE1-072 C
Solar/Wind Helper
4.299
316369SG1_INVT
Solar/Wind Helper
1.8
316305AF2-043 C
Solar/Wind Helper
0.499
316132AB2-190 GEN1
Solar/Wind Helper
2.107
957831AF2-077 GEN
Solar/Wind Helper
0.495
316349AD2-085 GEN
Solar/Wind Helper
1.649
313526AB2-022
Solar/Wind Helper
0.533
957601AF2-054 GEN
Solar/Wind Helper
0.467
3141873WAN 176
Solar/Wind Helper
0.07
315662AE1-191 GEN
Solar/Wind Helper
1.865
315666AE1-190 GEN
Solar/Wind Helper
0.466
316059AD1-063 C
Solar/Wind Helper
0.348
3141913WHIT STONE
Solar/Wind Helper
0.345
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.137
3146486SUNBURY
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.341
316321Z2-027
Solar/Wind Helper
0.514
3145176PASQUOTANK
Solar/Wind Helper
0.209
316315AB2-025 C
Solar/Wind Helper
0.507
3141813NORNECK
Solar/Wind Helper
0.325
316312AB1-027
Solar/Wind Helper
0.597
316233AE1-074 FULL
Solar/Wind Helper
0.469
316223AC1-118
Solar/Wind Helper
0.466
315611Z1-036_GEN2
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
3151041BRUNSWICKG3
50/50
8.505
972187AH1-678 GEN
50/50
19.517
315242AE2-183_GT2
50/50
10.667
315241AE2-183_GT1
50/50
10.602
972185AH1-677 GEN
50/50
38.457
970533AG2-339 GEN
50/50
57.391
970531AG2-338 GEN
50/50
22.956
3152661PLYWOOD A
50/50
0.751
970535AG2-341 GEN
50/50
5.149
3144293JTRSVLE
50/50
0.914
3144293JTRSVLE
50/50
0.769
970933AG2-581 GEN
Solar/Wind Harmer
67.863
970099AG2-077 GEN
Solar/Wind Harmer
76.214
971741AH1-377 GEN
Solar/Wind Harmer
50.609
970301AG2-198 GEN
Solar/Wind Harmer
19.968
3146843MT LREL
Solar/Wind Harmer
-0.036
3146843MT LREL
Solar/Wind Harmer
-0.036
964791AG1-342 GEN
Solar/Wind Harmer
7.699
962561AG1-105 GEN
Solar/Wind Harmer
19.948
316222AC1-221 GEN
Solar/Wind Harmer
3.472
939181AE1-148 GEN
Solar/Wind Harmer
18.394
313527AB2-043 GEN
Solar/Wind Harmer
5.237
970323AG2-213 GEN
Solar/Wind Harmer
15.625
971775AH1-396 GEN
Solar/Wind Harmer
2.225
316034AC1-036 C
Solar/Wind Harmer
0.579
958211AF2-115 GEN
Solar/Wind Harmer
4.748
963191AG1-168 GEN
Solar/Wind Harmer
2.849
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
942751AE2-291 GEN
Solar/Wind Harmer
16.78
270013AE1-250 PV
Solar/Wind Harmer
3.042
3146776BUCKING
Solar/Wind Harmer
-0.072
3146776BUCKING
Solar/Wind Harmer
-0.006
316217AC1-145 GEN
Solar/Wind Harmer
2.634
316197AC1-042 GEN
Solar/Wind Harmer
1.997
942671AE2-283 GEN
Solar/Wind Harmer
5.376
316263AC1-034 GEN
Solar/Wind Harmer
6.481
961601AG1-000A GEN
Solar/Wind Harmer
5.306
316036AC1-147 C
Solar/Wind Helper
0.621
3142956BIRDNECK
Solar/Wind Helper
0.272
316316AC1-027 C
Solar/Wind Helper
0.638
316185AD1-033 GEN
Solar/Wind Helper
1.893
3145506HICKORY
Solar/Wind Helper
1.587
3145506HICKORY
Solar/Wind Helper
0.952
3145506HICKORY
Solar/Wind Helper
0.238
316236AE1-162_GEN
Solar/Wind Helper
0.529
316339AD2-160 GEN
Solar/Wind Helper
1.472
316018AA1-139 ULT2
Solar/Wind Helper
1.65
316017AA1-139 ULT1
Solar/Wind Helper
1.754
3137176SLIGO L2192
Solar/Wind Helper
1.508
3130086AYDLETT
Solar/Wind Helper
1.498
316033AB2-134 GEN
Solar/Wind Helper
1.287
315697AD1-025 GEN
Solar/Wind Helper
4.277
316240AF1-291 C
Solar/Wind Helper
0.501
3146386ELIZ CT
Solar/Wind Helper
0.35
3142946ENON
Solar/Wind Helper
0.034
316487AF1-042 GEN
Solar/Wind Helper
0.339
3144356SAPONY
Solar/Wind Helper
0.597
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.305
316431W1029_GEN1
Solar/Wind Helper
1.295
316433W1029_GEN2
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
966871AG1-558 GEN
Solar/Wind Helper
0.403
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
316468AD1-105 GEN
Solar/Wind Helper
1.402
315742AE1-103 GEN
Solar/Wind Helper
0.368
CPLELTFEXP_CPLE->PJM
CLTF
20.639
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.343
LAGNLTFEXP_LAGN->PJM
CLTF
15.403
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.288
TVALTFEXP_TVA->PJM
CLTF
7.684
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.447
MECLTFEXP_MEC->PJM
CLTF
7.78
SIGELTFEXP_SIGE->PJM
CLTF
0.233
NYPJM->LTFIMP_NY
CLTF
2.484
LGEELTFEXP_LGEE->PJM
CLTF
2.833
WECLTFEXP_WEC->PJM
CLTF
1.482
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-5: W72_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: W72_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.43 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:6166.56
MW Contribution:46.16
Bus #Bus NameTypeMW Contribution
963041AG1-153 GEN
50/50
17.095
315244AE2-183_ST
50/50
18.308
3151541CLOVER2
50/50
10.527
3151611KERR 4
50/50
0.604
3151621KERR 5
50/50
0.604
3151631KERR 6
50/50
0.604
3151641KERR 7
50/50
0.604
971967AH1-528 GEN
Solar/Wind Harmer
143.519
970673AG2-436 GEN
Solar/Wind Harmer
151.3
970673AG2-436 GEN
Solar/Wind Harmer
76.608
941031AE2-094 GEN
Solar/Wind Harmer
135.024
944011AF1-069 GEN
Solar/Wind Harmer
42.308
970085AG2-068 GEN
Solar/Wind Harmer
42.031
970581AG2-369 GEN
Solar/Wind Harmer
36.147
3147173SINAI
Solar/Wind Harmer
-0.039
3147243WELCO
Solar/Wind Harmer
-0.024
316118AC1-105 GEN
Solar/Wind Harmer
2.567
970865AG2-541 GEN
Solar/Wind Harmer
13.271
316239AB2-077_GEN
Solar/Wind Harmer
0.98
316238AB2-078_GEN
Solar/Wind Harmer
0.98
971443AH1-215 GEN
Solar/Wind Harmer
6.158
3144303KENBRDG
Solar/Wind Harmer
-0.025
970683AG2-441 GEN
Solar/Wind Harmer
24.044
970681AG2-440 GEN
Solar/Wind Harmer
19.235
946301AF1-294 GEN
Solar/Wind Harmer
7.775
961791AG1-021 GEN
Solar/Wind Harmer
3.793
3151051BRUNSWICKS1
50/50
17.522
3151021BRUNSWICKG1
50/50
8.442
971451AH1-221 GEN
50/50
25.642
315243AE2-183_GT3
50/50
10.589
3151531CLOVER1
50/50
10.578
3151601KERR 3
50/50
0.604
3151581KERR 1
50/50
0.216
3144293JTRSVLE
50/50
0.912
971629AH1-314 GEN
50/50
18.997
3151561HALLBR1
50/50
0.403
970919AG2-571 GEN
Solar/Wind Harmer
21.433
970087AG2-069 GEN
Solar/Wind Harmer
63.047
957481AF2-042 GEN
Solar/Wind Harmer
189.269
315693AD1-088 GEN
Solar/Wind Harmer
27.634
962491AG1-098 GEN
Solar/Wind Harmer
36.422
315687AD1-152 GEN
Solar/Wind Harmer
5.988
316003AC1-222 GEN
Solar/Wind Harmer
3.561
970401AG2-262 GEN
Solar/Wind Harmer
2.348
316237AB2-079_GEN
Solar/Wind Harmer
0.98
970685AG2-442 GEN
Solar/Wind Harmer
26.929
963171AG1-166 GEN
Solar/Wind Harmer
3.793
971563AH1-280 GEN
Solar/Wind Harmer
3.793
3146926FARMVIL
Solar/Wind Harmer
-0.017
971065AG2-659 GEN
Solar/Wind Harmer
12.621
316129AC1-054 GEN
Solar/Wind Harmer
2.079
970223AG2-152 GEN
Solar/Wind Harmer
18.347
270016AE1-250 BESS
Solar/Wind Harmer
3.032
3147123OTTER R
Solar/Wind Harmer
-0.011
316322AB2-045
Solar/Wind Harmer
0.602
3146776BUCKING
Solar/Wind Harmer
-0.007
270574AD1-017 GEN2
Solar/Wind Harmer
5.978
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
941801AE2-185 GEN
Solar/Wind Harmer
6.064
270030AE2-140 GEN
Solar/Wind Harmer
20.984
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.909
316049AB1-081 GEN
Solar/Wind Harmer
1.528
3142053HEARTS
Solar/Wind Harmer
0.166
316294AC1-161 GEN
Solar/Wind Helper
8.246
316375AC2-012 GEN
Solar/Wind Helper
1.074
3145336SMITFLD
Solar/Wind Helper
1.568
3151031BRUNSWICKG2
50/50
8.442
970413AG2-270 GEN
50/50
46.159
3151591KERR 2
50/50
0.604
3144293JTRSVLE
50/50
0.912
970917AG2-570 GEN
Solar/Wind Harmer
169.32
316478AD1-087 GEN
Solar/Wind Harmer
4.801
316486AD2-202 GEN
Solar/Wind Harmer
1.406
970909AG2-566 GEN
Solar/Wind Harmer
3.769
316248AF1-058 C
Solar/Wind Harmer
1.164
960061AF2-297 GEN
Solar/Wind Harmer
19.314
315657AE1-056 GEN
Solar/Wind Harmer
11.263
316123AC1-075 GEN
Solar/Wind Harmer
3.099
970165AG2-112 GEN
Solar/Wind Harmer
2.728
970163AG2-111 GEN
Solar/Wind Harmer
2.603
270455AD2-022 GEN
Solar/Wind Harmer
4.991
270457AD2-023 GEN
Solar/Wind Harmer
2.531
970831AG2-522 GEN
Solar/Wind Harmer
11.041
970285AG2-188 GEN
Solar/Wind Harmer
17.881
971845AH1-439 GEN
Solar/Wind Harmer
9.974
270069AE2-166 C O1
Solar/Wind Harmer
2.569
319010AE1-072 C
Solar/Wind Helper
4.32
3143316POE
Solar/Wind Helper
1.486
316305AF2-043 C
Solar/Wind Helper
0.5
316369SG1_INVT
Solar/Wind Helper
1.758
957831AF2-077 GEN
Solar/Wind Helper
0.492
316132AB2-190 GEN1
Solar/Wind Helper
2.041
316349AD2-085 GEN
Solar/Wind Helper
1.61
313526AB2-022
Solar/Wind Helper
0.535
957601AF2-054 GEN
Solar/Wind Helper
0.462
3141873WAN 176
Solar/Wind Helper
0.069
315662AE1-191 GEN
Solar/Wind Helper
1.844
315666AE1-190 GEN
Solar/Wind Helper
0.461
3146486SUNBURY
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.341
316059AD1-063 C
Solar/Wind Helper
0.344
3141913WHIT STONE
Solar/Wind Helper
0.341
3138133OCRAN
Solar/Wind Helper
0.102
3143873LANEXA
Solar/Wind Helper
0.203
3141783LANCAST
Solar/Wind Helper
0.203
3141783LANCAST
Solar/Wind Helper
0.135
316321Z2-027
Solar/Wind Helper
0.515
3145176PASQUOTANK
Solar/Wind Helper
0.209
3141813NORNECK
Solar/Wind Helper
0.321
316312AB1-027
Solar/Wind Helper
0.585
316223AC1-118
Solar/Wind Helper
0.461
316233AE1-074 FULL
Solar/Wind Helper
0.462
316315AB2-025 C
Solar/Wind Helper
0.44
315611Z1-036_GEN2
Solar/Wind Helper
1.494
3130156CHOWAN
Solar/Wind Helper
0.24
3130156CHOWAN
Solar/Wind Helper
0.24
971683AH1-343 GEN
Solar/Wind Harmer
14.923
316283AC2-100 C
Solar/Wind Harmer
3.192
316131AB2-060 GEN
Solar/Wind Harmer
3.475
964241AG1-285 GEN
Solar/Wind Harmer
24.93
315785AD2-033 C
Solar/Wind Harmer
7.122
970257AG2-171 GEN
Solar/Wind Harmer
11.716
959311AF2-222 GEN
Solar/Wind Harmer
32.468
963181AG1-167 GEN
Solar/Wind Harmer
2.845
3147133PAMPLIN
Solar/Wind Harmer
-0.094
971193AH1-056 GEN
Solar/Wind Harmer
18.772
942461AE2-259 GEN
Solar/Wind Harmer
4.384
3146926FARMVIL
Solar/Wind Harmer
-0.017
3146776BUCKING
Solar/Wind Harmer
-0.006
270018AE2-047 C O1
Solar/Wind Harmer
1.461
270197AD1-017 GEN1
Solar/Wind Harmer
1.796
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
6.064
943811AF1-049 GEN
Solar/Wind Harmer
4.077
270336AE1-100 GEN
Solar/Wind Harmer
1.664
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
5.512
3138543CONSLDL
Solar/Wind Harmer
-0.008
315773AC2-141 GEN
Solar/Wind Helper
9.706
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3145336SMITFLD
Solar/Wind Helper
0.157
3146456SLIGO L269
Solar/Wind Helper
0.38
316382AG1-145 C
Solar/Wind Helper
0.496
315839AE2-212 C
Solar/Wind Helper
0.483
316320Y1-086
Solar/Wind Helper
0.157
316156AD2-030 GEN
Solar/Wind Helper
0.52
316280AD1-041 GEN
Solar/Wind Helper
1.152
3142946ENON
Solar/Wind Helper
0.111
316484AD2-074 GEN
Solar/Wind Helper
0.641
316404AE1-155 C
Solar/Wind Helper
2.769
316435W1029_GEN3
Solar/Wind Helper
1.297
3146516WINFALL
Solar/Wind Helper
0.314
3141906WESTMOR
Solar/Wind Helper
0.121
3146626S HERTFORD
Solar/Wind Helper
0.296
316473AC1-191 GEN
Solar/Wind Helper
1.785
3145273HOLLAND
Solar/Wind Helper
0.198
966881AG1-559 GEN
Solar/Wind Helper
0.346
3146376EDENTON
Solar/Wind Helper
0.239
316388AE2-253 GEN
Solar/Wind Helper
1.48
3146456SLIGO L269
Solar/Wind Helper
0.38
316072AD1-144
Solar/Wind Helper
0.428
316246AF1-032 C
Solar/Wind Helper
0.426
316159AE1-175 C
Solar/Wind Helper
0.559
316381AD1-082 GEN
Solar/Wind Helper
1.857
316458AB2-190 GEN2
Solar/Wind Helper
2.041
3141766HARMONY
Solar/Wind Helper
0.068
3138133OCRAN
Solar/Wind Helper
0.204
3142433PROV 92
Solar/Wind Helper
1.345
3142543TWELFTH
Solar/Wind Helper
0.031
964211AG1-282 GEN
Solar/Wind Helper
0.434
3141726DUNNSVL
Solar/Wind Helper
1.289
3146516WINFALL
Solar/Wind Helper
1.017
3146516WINFALL
Solar/Wind Helper
0.314
316337AD2-073 GEN
Solar/Wind Helper
0.473
3142416OLDCHRC
Solar/Wind Helper
0.799
3142416OLDCHRC
Solar/Wind Helper
0.306
3143526WINTERP
Solar/Wind Helper
1.573
3143226MDLTHAN
Solar/Wind Helper
0.298
315800Z1-036_GEN1
Solar/Wind Helper
1.494
3130156CHOWAN
Solar/Wind Helper
0.24
3151041BRUNSWICKG3
50/50
8.442
972187AH1-678 GEN
50/50
19.374
315242AE2-183_GT2
50/50
10.589
315241AE2-183_GT1
50/50
10.524
972185AH1-677 GEN
50/50
38.176
970533AG2-339 GEN
50/50
56.972
970531AG2-338 GEN
50/50
22.789
3152661PLYWOOD A
50/50
0.749
970535AG2-341 GEN
50/50
5.154
3144293JTRSVLE
50/50
0.912
3144293JTRSVLE
50/50
0.768
970933AG2-581 GEN
Solar/Wind Harmer
67.369
970099AG2-077 GEN
Solar/Wind Harmer
75.708
971741AH1-377 GEN
Solar/Wind Harmer
50.305
970301AG2-198 GEN
Solar/Wind Harmer
19.85
3146843MT LREL
Solar/Wind Harmer
-0.036
3146843MT LREL
Solar/Wind Harmer
-0.036
964791AG1-342 GEN
Solar/Wind Harmer
7.683
962561AG1-105 GEN
Solar/Wind Harmer
19.916
316222AC1-221 GEN
Solar/Wind Harmer
3.458
939181AE1-148 GEN
Solar/Wind Harmer
18.413
313527AB2-043 GEN
Solar/Wind Harmer
5.244
970323AG2-213 GEN
Solar/Wind Harmer
15.621
971775AH1-396 GEN
Solar/Wind Harmer
2.225
316034AC1-036 C
Solar/Wind Harmer
0.579
958211AF2-115 GEN
Solar/Wind Harmer
4.741
963191AG1-168 GEN
Solar/Wind Harmer
2.845
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
942751AE2-291 GEN
Solar/Wind Harmer
16.715
270013AE1-250 PV
Solar/Wind Harmer
3.032
3146776BUCKING
Solar/Wind Harmer
-0.071
3146776BUCKING
Solar/Wind Harmer
-0.006
316217AC1-145 GEN
Solar/Wind Harmer
2.625
316197AC1-042 GEN
Solar/Wind Harmer
1.99
942671AE2-283 GEN
Solar/Wind Harmer
5.357
316263AC1-034 GEN
Solar/Wind Harmer
6.638
961601AG1-000A GEN
Solar/Wind Harmer
5.443
316036AC1-147 C
Solar/Wind Helper
0.624
3142956BIRDNECK
Solar/Wind Helper
0.274
316316AC1-027 C
Solar/Wind Helper
0.642
316185AD1-033 GEN
Solar/Wind Helper
1.905
3145506HICKORY
Solar/Wind Helper
1.596
3145506HICKORY
Solar/Wind Helper
0.958
3145506HICKORY
Solar/Wind Helper
0.239
316236AE1-162_GEN
Solar/Wind Helper
0.527
316339AD2-160 GEN
Solar/Wind Helper
1.48
316018AA1-139 ULT2
Solar/Wind Helper
1.659
316017AA1-139 ULT1
Solar/Wind Helper
1.763
3137176SLIGO L2192
Solar/Wind Helper
1.516
3130086AYDLETT
Solar/Wind Helper
1.505
316033AB2-134 GEN
Solar/Wind Helper
1.257
315697AD1-025 GEN
Solar/Wind Helper
4.177
3146386ELIZ CT
Solar/Wind Helper
0.351
316240AF1-291 C
Solar/Wind Helper
0.468
3142946ENON
Solar/Wind Helper
0.033
316487AF1-042 GEN
Solar/Wind Helper
0.335
316075AC2-137 C
Solar/Wind Helper
0.492
316077AC2-138 C
Solar/Wind Helper
0.302
316431W1029_GEN1
Solar/Wind Helper
1.297
316433W1029_GEN2
Solar/Wind Helper
1.297
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.573
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
966871AG1-558 GEN
Solar/Wind Helper
0.394
3144356SAPONY
Solar/Wind Helper
0.518
316468AD1-105 GEN
Solar/Wind Helper
1.373
315742AE1-103 GEN
Solar/Wind Helper
0.362
CPLELTFEXP_CPLE->PJM
CLTF
20.587
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.048
LAGNLTFEXP_LAGN->PJM
CLTF
15.349
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.145
TVALTFEXP_TVA->PJM
CLTF
7.657
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.486
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.354
MECLTFEXP_MEC->PJM
CLTF
7.751
SIGELTFEXP_SIGE->PJM
CLTF
0.232
NYPJM->LTFIMP_NY
CLTF
2.481
LGEELTFEXP_LGEE->PJM
CLTF
2.822
WECLTFEXP_WEC->PJM
CLTF
1.476
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: XT585_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: XT585_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.16 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5703.66
MW Contribution:46.45
Bus #Bus NameTypeMW Contribution
3151051BRUNSWICKS1
50/50
17.651
3151021BRUNSWICKG1
50/50
8.505
971451AH1-221 GEN
50/50
25.831
315243AE2-183_GT3
50/50
10.667
963041AG1-153 GEN
50/50
17.22
315244AE2-183_ST
50/50
18.443
3151541CLOVER2
50/50
10.593
3151611KERR 4
50/50
0.604
3151621KERR 5
50/50
0.604
3151631KERR 6
50/50
0.604
3151641KERR 7
50/50
0.604
971967AH1-528 GEN
Solar/Wind Harmer
144.6
970085AG2-068 GEN
Solar/Wind Harmer
42.331
970581AG2-369 GEN
Solar/Wind Harmer
36.404
3147173SINAI
Solar/Wind Harmer
-0.039
3147243WELCO
Solar/Wind Harmer
-0.024
316118AC1-105 GEN
Solar/Wind Harmer
2.575
970865AG2-541 GEN
Solar/Wind Harmer
13.323
316239AB2-077_GEN
Solar/Wind Harmer
0.978
316238AB2-078_GEN
Solar/Wind Harmer
0.978
971443AH1-215 GEN
Solar/Wind Harmer
6.159
3144303KENBRDG
Solar/Wind Harmer
-0.025
970683AG2-441 GEN
Solar/Wind Harmer
24.066
970681AG2-440 GEN
Solar/Wind Harmer
19.253
946301AF1-294 GEN
Solar/Wind Harmer
7.788
961791AG1-021 GEN
Solar/Wind Harmer
3.799
315657AE1-056 GEN
Solar/Wind Harmer
11.287
316123AC1-075 GEN
Solar/Wind Harmer
3.111
970165AG2-112 GEN
Solar/Wind Harmer
2.739
970163AG2-111 GEN
Solar/Wind Harmer
2.613
270455AD2-022 GEN
Solar/Wind Harmer
5.008
270457AD2-023 GEN
Solar/Wind Harmer
2.539
970831AG2-522 GEN
Solar/Wind Harmer
10.909
970285AG2-188 GEN
Solar/Wind Harmer
17.971
971845AH1-439 GEN
Solar/Wind Harmer
10.023
270069AE2-166 C O1
Solar/Wind Harmer
2.578
3143316POE
Solar/Wind Helper
1.64
319010AE1-072 C
Solar/Wind Helper
4.299
316369SG1_INVT
Solar/Wind Helper
1.8
316305AF2-043 C
Solar/Wind Helper
0.499
316132AB2-190 GEN1
Solar/Wind Helper
2.107
957831AF2-077 GEN
Solar/Wind Helper
0.495
316349AD2-085 GEN
Solar/Wind Helper
1.649
313526AB2-022
Solar/Wind Helper
0.533
957601AF2-054 GEN
Solar/Wind Helper
0.467
3141873WAN 176
Solar/Wind Helper
0.07
315662AE1-191 GEN
Solar/Wind Helper
1.865
315666AE1-190 GEN
Solar/Wind Helper
0.466
316059AD1-063 C
Solar/Wind Helper
0.348
3141913WHIT STONE
Solar/Wind Helper
0.345
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.137
3146486SUNBURY
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.341
316321Z2-027
Solar/Wind Helper
0.514
3145176PASQUOTANK
Solar/Wind Helper
0.209
316315AB2-025 C
Solar/Wind Helper
0.507
3141813NORNECK
Solar/Wind Helper
0.325
316312AB1-027
Solar/Wind Helper
0.597
316233AE1-074 FULL
Solar/Wind Helper
0.469
316223AC1-118
Solar/Wind Helper
0.466
315611Z1-036_GEN2
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
3151531CLOVER1
50/50
10.644
3151601KERR 3
50/50
0.604
3151581KERR 1
50/50
0.216
3144293JTRSVLE
50/50
0.914
971629AH1-314 GEN
50/50
19.06
3151561HALLBR1
50/50
0.404
970919AG2-571 GEN
Solar/Wind Harmer
21.586
970087AG2-069 GEN
Solar/Wind Harmer
63.496
957481AF2-042 GEN
Solar/Wind Harmer
190.536
315693AD1-088 GEN
Solar/Wind Harmer
27.811
962491AG1-098 GEN
Solar/Wind Harmer
36.654
315687AD1-152 GEN
Solar/Wind Harmer
6.022
316003AC1-222 GEN
Solar/Wind Harmer
3.575
970401AG2-262 GEN
Solar/Wind Harmer
2.352
316237AB2-079_GEN
Solar/Wind Harmer
0.978
970685AG2-442 GEN
Solar/Wind Harmer
26.954
963171AG1-166 GEN
Solar/Wind Harmer
3.799
971563AH1-280 GEN
Solar/Wind Harmer
3.799
3146926FARMVIL
Solar/Wind Harmer
-0.017
971065AG2-659 GEN
Solar/Wind Harmer
12.523
316129AC1-054 GEN
Solar/Wind Harmer
2.059
970223AG2-152 GEN
Solar/Wind Harmer
18.408
270016AE1-250 BESS
Solar/Wind Harmer
3.042
3147123OTTER R
Solar/Wind Harmer
-0.011
316322AB2-045
Solar/Wind Harmer
0.605
3146776BUCKING
Solar/Wind Harmer
-0.007
270574AD1-017 GEN2
Solar/Wind Harmer
5.998
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
941801AE2-185 GEN
Solar/Wind Harmer
6.086
270030AE2-140 GEN
Solar/Wind Harmer
21.053
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.864
316049AB1-081 GEN
Solar/Wind Harmer
1.492
3142053HEARTS
Solar/Wind Harmer
0.163
316294AC1-161 GEN
Solar/Wind Helper
8.153
316375AC2-012 GEN
Solar/Wind Helper
1.068
3145336SMITFLD
Solar/Wind Helper
1.575
316388AE2-253 GEN
Solar/Wind Helper
1.472
3146456SLIGO L269
Solar/Wind Helper
0.379
316381AD1-082 GEN
Solar/Wind Helper
1.955
316072AD1-144
Solar/Wind Helper
0.428
316246AF1-032 C
Solar/Wind Helper
0.424
316159AE1-175 C
Solar/Wind Helper
0.562
316458AB2-190 GEN2
Solar/Wind Helper
2.107
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.376
3138133OCRAN
Solar/Wind Helper
0.206
3142543TWELFTH
Solar/Wind Helper
0.032
964211AG1-282 GEN
Solar/Wind Helper
0.439
3141726DUNNSVL
Solar/Wind Helper
1.304
316337AD2-073 GEN
Solar/Wind Helper
0.478
3142416OLDCHRC
Solar/Wind Helper
0.816
3142416OLDCHRC
Solar/Wind Helper
0.312
3146516WINFALL
Solar/Wind Helper
1.016
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
3143226MDLTHAN
Solar/Wind Helper
0.3
315800Z1-036_GEN1
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3151031BRUNSWICKG2
50/50
8.505
970413AG2-270 GEN
50/50
46.449
3151591KERR 2
50/50
0.604
3144293JTRSVLE
50/50
0.914
970917AG2-570 GEN
Solar/Wind Harmer
170.53
316478AD1-087 GEN
Solar/Wind Harmer
4.831
316486AD2-202 GEN
Solar/Wind Harmer
1.415
970909AG2-566 GEN
Solar/Wind Harmer
3.791
316248AF1-058 C
Solar/Wind Harmer
1.169
960061AF2-297 GEN
Solar/Wind Harmer
19.391
971683AH1-343 GEN
Solar/Wind Harmer
14.982
316283AC2-100 C
Solar/Wind Harmer
3.205
316131AB2-060 GEN
Solar/Wind Harmer
3.471
964241AG1-285 GEN
Solar/Wind Harmer
24.911
315785AD2-033 C
Solar/Wind Harmer
7.122
970257AG2-171 GEN
Solar/Wind Harmer
11.718
959311AF2-222 GEN
Solar/Wind Harmer
32.481
963181AG1-167 GEN
Solar/Wind Harmer
2.849
3147133PAMPLIN
Solar/Wind Harmer
-0.094
971193AH1-056 GEN
Solar/Wind Harmer
18.811
942461AE2-259 GEN
Solar/Wind Harmer
4.399
3146926FARMVIL
Solar/Wind Harmer
-0.017
3146776BUCKING
Solar/Wind Harmer
-0.006
270018AE2-047 C O1
Solar/Wind Harmer
1.466
270197AD1-017 GEN1
Solar/Wind Harmer
1.802
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
6.086
943811AF1-049 GEN
Solar/Wind Harmer
4.09
270336AE1-100 GEN
Solar/Wind Harmer
1.669
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
5.373
315773AC2-141 GEN
Solar/Wind Helper
9.595
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3145336SMITFLD
Solar/Wind Helper
0.157
315839AE2-212 C
Solar/Wind Helper
0.523
3146456SLIGO L269
Solar/Wind Helper
0.379
316382AG1-145 C
Solar/Wind Helper
0.498
316320Y1-086
Solar/Wind Helper
0.156
316156AD2-030 GEN
Solar/Wind Helper
0.525
316280AD1-041 GEN
Solar/Wind Helper
1.166
3142946ENON
Solar/Wind Helper
0.114
316484AD2-074 GEN
Solar/Wind Helper
0.648
316404AE1-155 C
Solar/Wind Helper
2.8
316435W1029_GEN3
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3141906WESTMOR
Solar/Wind Helper
0.122
316473AC1-191 GEN
Solar/Wind Helper
1.829
3146626S HERTFORD
Solar/Wind Helper
0.296
3145273HOLLAND
Solar/Wind Helper
0.201
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.24
3151041BRUNSWICKG3
50/50
8.505
972187AH1-678 GEN
50/50
19.517
315242AE2-183_GT2
50/50
10.667
315241AE2-183_GT1
50/50
10.602
972185AH1-677 GEN
50/50
38.457
3152661PLYWOOD A
50/50
0.751
970535AG2-341 GEN
50/50
5.149
3144293JTRSVLE
50/50
0.914
3144293JTRSVLE
50/50
0.769
970933AG2-581 GEN
Solar/Wind Harmer
67.863
970099AG2-077 GEN
Solar/Wind Harmer
76.214
971741AH1-377 GEN
Solar/Wind Harmer
50.609
970301AG2-198 GEN
Solar/Wind Harmer
19.968
3146843MT LREL
Solar/Wind Harmer
-0.036
3146843MT LREL
Solar/Wind Harmer
-0.036
964791AG1-342 GEN
Solar/Wind Harmer
7.699
962561AG1-105 GEN
Solar/Wind Harmer
19.948
316222AC1-221 GEN
Solar/Wind Harmer
3.472
939181AE1-148 GEN
Solar/Wind Harmer
18.394
313527AB2-043 GEN
Solar/Wind Harmer
5.237
970323AG2-213 GEN
Solar/Wind Harmer
15.625
971775AH1-396 GEN
Solar/Wind Harmer
2.225
316034AC1-036 C
Solar/Wind Harmer
0.579
958211AF2-115 GEN
Solar/Wind Harmer
4.748
963191AG1-168 GEN
Solar/Wind Harmer
2.849
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
942751AE2-291 GEN
Solar/Wind Harmer
16.78
270013AE1-250 PV
Solar/Wind Harmer
3.042
3146776BUCKING
Solar/Wind Harmer
-0.072
3146776BUCKING
Solar/Wind Harmer
-0.006
316217AC1-145 GEN
Solar/Wind Harmer
2.634
316197AC1-042 GEN
Solar/Wind Harmer
1.997
942671AE2-283 GEN
Solar/Wind Harmer
5.376
316263AC1-034 GEN
Solar/Wind Harmer
6.481
961601AG1-000A GEN
Solar/Wind Harmer
5.306
316036AC1-147 C
Solar/Wind Helper
0.621
3142956BIRDNECK
Solar/Wind Helper
0.272
316316AC1-027 C
Solar/Wind Helper
0.638
316185AD1-033 GEN
Solar/Wind Helper
1.893
3145506HICKORY
Solar/Wind Helper
1.587
3145506HICKORY
Solar/Wind Helper
0.952
3145506HICKORY
Solar/Wind Helper
0.238
316236AE1-162_GEN
Solar/Wind Helper
0.529
316339AD2-160 GEN
Solar/Wind Helper
1.472
316018AA1-139 ULT2
Solar/Wind Helper
1.65
316017AA1-139 ULT1
Solar/Wind Helper
1.754
3137176SLIGO L2192
Solar/Wind Helper
1.508
3130086AYDLETT
Solar/Wind Helper
1.498
316033AB2-134 GEN
Solar/Wind Helper
1.287
315697AD1-025 GEN
Solar/Wind Helper
4.277
316240AF1-291 C
Solar/Wind Helper
0.501
3146386ELIZ CT
Solar/Wind Helper
0.35
3142946ENON
Solar/Wind Helper
0.034
316487AF1-042 GEN
Solar/Wind Helper
0.339
3144356SAPONY
Solar/Wind Helper
0.597
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.305
316431W1029_GEN1
Solar/Wind Helper
1.295
316433W1029_GEN2
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
966871AG1-558 GEN
Solar/Wind Helper
0.403
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
316468AD1-105 GEN
Solar/Wind Helper
1.402
315742AE1-103 GEN
Solar/Wind Helper
0.368
CPLELTFEXP_CPLE->PJM
CLTF
20.639
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.343
LAGNLTFEXP_LAGN->PJM
CLTF
15.403
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.288
TVALTFEXP_TVA->PJM
CLTF
7.684
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.447
MECLTFEXP_MEC->PJM
CLTF
7.78
SIGELTFEXP_SIGE->PJM
CLTF
0.233
NYPJM->LTFIMP_NY
CLTF
2.484
LGEELTFEXP_LGEE->PJM
CLTF
2.833
WECLTFEXP_WEC->PJM
CLTF
1.482
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 54472_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 54472_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.74 %
Rating:2858.0 MVA
Rating Type:C
MVA to Mitigate:3193.49
MW Contribution:34.77
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
7.93
963041AG1-153 GEN
50/50
8.365
315244AE2-183_ST
50/50
6.698
3151611KERR 4
50/50
0.44
3151621KERR 5
50/50
0.44
3151631KERR 6
50/50
0.44
3151641KERR 7
50/50
0.44
971967AH1-528 GEN
Solar/Wind Harmer
110.812
970085AG2-068 GEN
Solar/Wind Harmer
20.738
970581AG2-369 GEN
Solar/Wind Harmer
17.835
3147173SINAI
Solar/Wind Harmer
-0.028
3147243WELCO
Solar/Wind Harmer
-0.017
316118AC1-105 GEN
Solar/Wind Harmer
1.848
316239AB2-077_GEN
Solar/Wind Harmer
0.722
316238AB2-078_GEN
Solar/Wind Harmer
0.722
971443AH1-215 GEN
Solar/Wind Harmer
4.604
3144303KENBRDG
Solar/Wind Harmer
-0.019
970865AG2-541 GEN
Solar/Wind Harmer
9.435
970683AG2-441 GEN
Solar/Wind Harmer
18.098
970681AG2-440 GEN
Solar/Wind Harmer
14.478
946301AF1-294 GEN
Solar/Wind Harmer
5.887
961791AG1-021 GEN
Solar/Wind Harmer
2.872
3151531CLOVER1
50/50
7.968
3151051BRUNSWICKS1
50/50
8.574
3151021BRUNSWICKG1
50/50
4.131
971451AH1-221 GEN
50/50
12.548
315243AE2-183_GT3
50/50
3.874
3151601KERR 3
50/50
0.44
3151581KERR 1
50/50
0.157
3144293JTRSVLE
50/50
0.691
971629AH1-314 GEN
50/50
11.594
957481AF2-042 GEN
Solar/Wind Harmer
144.035
315693AD1-088 GEN
Solar/Wind Harmer
21.036
962491AG1-098 GEN
Solar/Wind Harmer
27.737
315687AD1-152 GEN
Solar/Wind Harmer
4.411
970919AG2-571 GEN
Solar/Wind Harmer
10.566
970087AG2-069 GEN
Solar/Wind Harmer
31.107
970401AG2-262 GEN
Solar/Wind Harmer
1.7
316003AC1-222 GEN
Solar/Wind Harmer
2.544
316237AB2-079_GEN
Solar/Wind Harmer
0.722
970685AG2-442 GEN
Solar/Wind Harmer
20.27
963171AG1-166 GEN
Solar/Wind Harmer
2.872
971563AH1-280 GEN
Solar/Wind Harmer
2.872
3146926FARMVIL
Solar/Wind Harmer
-0.013
971065AG2-659 GEN
Solar/Wind Harmer
9.218
316129AC1-054 GEN
Solar/Wind Harmer
1.52
316322AB2-045
Solar/Wind Harmer
0.488
3146776BUCKING
Solar/Wind Harmer
-0.006
970223AG2-152 GEN
Solar/Wind Harmer
11.343
316294AC1-161 GEN
Solar/Wind Helper
4.653
315657AE1-056 GEN
Solar/Wind Harmer
8.565
316123AC1-075 GEN
Solar/Wind Harmer
2.19
970165AG2-112 GEN
Solar/Wind Harmer
1.928
970163AG2-111 GEN
Solar/Wind Harmer
1.839
970413AG2-270 GEN
50/50
34.77
3151031BRUNSWICKG2
50/50
4.131
3151591KERR 2
50/50
0.44
3144293JTRSVLE
50/50
0.691
316478AD1-087 GEN
Solar/Wind Harmer
3.615
316486AD2-202 GEN
Solar/Wind Harmer
1.059
970917AG2-570 GEN
Solar/Wind Harmer
83.468
970909AG2-566 GEN
Solar/Wind Harmer
2.9
316248AF1-058 C
Solar/Wind Harmer
0.833
960061AF2-297 GEN
Solar/Wind Harmer
13.826
971683AH1-343 GEN
Solar/Wind Harmer
10.636
316131AB2-060 GEN
Solar/Wind Harmer
2.567
964241AG1-285 GEN
Solar/Wind Harmer
18.486
315785AD2-033 C
Solar/Wind Harmer
5.315
970257AG2-171 GEN
Solar/Wind Harmer
8.764
959311AF2-222 GEN
Solar/Wind Harmer
24.33
963181AG1-167 GEN
Solar/Wind Harmer
2.154
3147133PAMPLIN
Solar/Wind Harmer
-0.071
971193AH1-056 GEN
Solar/Wind Harmer
14.275
3151041BRUNSWICKG3
50/50
4.131
972187AH1-678 GEN
50/50
9.481
3152661PLYWOOD A
50/50
0.538
315242AE2-183_GT2
50/50
3.874
315241AE2-183_GT1
50/50
3.85
972185AH1-677 GEN
50/50
13.967
970535AG2-341 GEN
50/50
3.778
3144293JTRSVLE
50/50
0.691
3144293JTRSVLE
50/50
0.582
970933AG2-581 GEN
Solar/Wind Harmer
51.852
970099AG2-077 GEN
Solar/Wind Harmer
57.614
971741AH1-377 GEN
Solar/Wind Harmer
38.586
970301AG2-198 GEN
Solar/Wind Harmer
15.274
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
964791AG1-342 GEN
Solar/Wind Harmer
5.564
962561AG1-105 GEN
Solar/Wind Harmer
14.462
939181AE1-148 GEN
Solar/Wind Harmer
13.444
313527AB2-043 GEN
Solar/Wind Harmer
3.87
970323AG2-213 GEN
Solar/Wind Harmer
11.685
971775AH1-396 GEN
Solar/Wind Harmer
1.664
316034AC1-036 C
Solar/Wind Harmer
0.433
958211AF2-115 GEN
Solar/Wind Harmer
3.59
963191AG1-168 GEN
Solar/Wind Harmer
2.154
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
316222AC1-221 GEN
Solar/Wind Harmer
2.218
942751AE2-291 GEN
Solar/Wind Harmer
11.754
3146776BUCKING
Solar/Wind Harmer
-0.058
3146776BUCKING
Solar/Wind Harmer
-0.005
316240AF1-291 C
Solar/Wind Helper
0.299
970673AG2-436 GEN
Solar/Wind Harmer
40.956
970673AG2-436 GEN
Solar/Wind Harmer
20.737
270455AD2-022 GEN
Solar/Wind Harmer
3.036
270457AD2-023 GEN
Solar/Wind Harmer
1.539
970285AG2-188 GEN
Solar/Wind Harmer
14.324
970831AG2-522 GEN
Solar/Wind Harmer
8.077
971845AH1-439 GEN
Solar/Wind Harmer
8.053
3143316POE
Solar/Wind Helper
1.004
942461AE2-259 GEN
Solar/Wind Harmer
3.375
3146926FARMVIL
Solar/Wind Harmer
-0.013
316283AC2-100 C
Solar/Wind Harmer
2.04
3146776BUCKING
Solar/Wind Harmer
-0.005
315773AC2-141 GEN
Solar/Wind Helper
5.476
315839AE2-212 C
Solar/Wind Helper
0.317
CPLELTFEXP_CPLE->PJM
CLTF
11.786
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.116
LAGNLTFEXP_LAGN->PJM
CLTF
8.928
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.434
TVALTFEXP_TVA->PJM
CLTF
4.461
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.523
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.401
MECLTFEXP_MEC->PJM
CLTF
4.601
SIGELTFEXP_SIGE->PJM
CLTF
0.139
NYPJM->LTFIMP_NY
CLTF
1.417
LGEELTFEXP_LGEE->PJM
CLTF
1.692
WECLTFEXP_WEC->PJM
CLTF
0.884

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.06 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5008.65
MW Contribution:40.85
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
44.982
970099AG2-077 GEN
Solar/Wind Harmer
50.723
971741AH1-377 GEN
Solar/Wind Harmer
33.569
970301AG2-198 GEN
Solar/Wind Harmer
13.228
3146843MT LREL
Solar/Wind Harmer
0.286
3146843MT LREL
Solar/Wind Harmer
0.286
964791AG1-342 GEN
Solar/Wind Harmer
5.488
316222AC1-221 GEN
Solar/Wind Harmer
1.175
962561AG1-105 GEN
Solar/Wind Harmer
13.485
939181AE1-148 GEN
Solar/Wind Harmer
12.41
313527AB2-043 GEN
Solar/Wind Harmer
0.003
970323AG2-213 GEN
Solar/Wind Harmer
10.445
971775AH1-396 GEN
Solar/Wind Harmer
0.392
316034AC1-036 C
Solar/Wind Harmer
0.018
958211AF2-115 GEN
Solar/Wind Harmer
2.845
963191AG1-168 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.234
3147133PAMPLIN
Solar/Wind Harmer
0.187
942751AE2-291 GEN
Solar/Wind Harmer
11.476
270013AE1-250 PV
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.546
3146776BUCKING
Solar/Wind Harmer
0.044
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
971967AH1-528 GEN
Solar/Wind Harmer
95.481
970085AG2-068 GEN
Solar/Wind Harmer
31.82
970581AG2-369 GEN
Solar/Wind Harmer
27.365
3147173SINAI
Solar/Wind Harmer
0.309
3147243WELCO
Solar/Wind Harmer
0.193
316118AC1-105 GEN
Solar/Wind Harmer
0.768
970865AG2-541 GEN
Solar/Wind Harmer
9.078
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.118
3144303KENBRDG
Solar/Wind Harmer
0.196
970683AG2-441 GEN
Solar/Wind Harmer
16.053
970681AG2-440 GEN
Solar/Wind Harmer
12.842
946301AF1-294 GEN
Solar/Wind Harmer
4.678
961791AG1-021 GEN
Solar/Wind Harmer
2.276
315657AE1-056 GEN
Solar/Wind Harmer
8.085
316123AC1-075 GEN
Solar/Wind Harmer
0.315
970165AG2-112 GEN
Solar/Wind Harmer
1.87
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
53.421
316478AD1-087 GEN
Solar/Wind Harmer
1.525
316486AD2-202 GEN
Solar/Wind Harmer
0.448
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
13.182
316283AC2-100 C
Solar/Wind Harmer
0.55
971683AH1-343 GEN
Solar/Wind Harmer
10.2
316131AB2-060 GEN
Solar/Wind Harmer
0.796
964241AG1-285 GEN
Solar/Wind Harmer
16.703
315785AD2-033 C
Solar/Wind Harmer
2.003
970257AG2-171 GEN
Solar/Wind Harmer
7.834
959311AF2-222 GEN
Solar/Wind Harmer
21.656
963181AG1-167 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.736
971193AH1-056 GEN
Solar/Wind Harmer
14.274
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.131
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
0.943
3146776BUCKING
Solar/Wind Harmer
0.049
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.212
270336AE1-100 GEN
Solar/Wind Harmer
0.003
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
47.73
957481AF2-042 GEN
Solar/Wind Harmer
126.807
315693AD1-088 GEN
Solar/Wind Harmer
20.818
962491AG1-098 GEN
Solar/Wind Harmer
24.385
315687AD1-152 GEN
Solar/Wind Harmer
0.013
316003AC1-222 GEN
Solar/Wind Harmer
0.008
970401AG2-262 GEN
Solar/Wind Harmer
1.677
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
17.979
963171AG1-166 GEN
Solar/Wind Harmer
1.264
971563AH1-280 GEN
Solar/Wind Harmer
2.529
3146926FARMVIL
Solar/Wind Harmer
0.131
971065AG2-659 GEN
Solar/Wind Harmer
8.445
316129AC1-054 GEN
Solar/Wind Harmer
0.698
970223AG2-152 GEN
Solar/Wind Harmer
12.094
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.088
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.055
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.099
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.276
316263AC1-034 GEN
Solar/Wind Harmer
4.449
961601AG1-000A GEN
Solar/Wind Harmer
2.035
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
970163AG2-111 GEN
Solar/Wind Harmer
1.784
970831AG2-522 GEN
Solar/Wind Harmer
7.35
970285AG2-188 GEN
Solar/Wind Harmer
12.402
971845AH1-439 GEN
Solar/Wind Harmer
6.507
270069AE2-166 C O1
Solar/Wind Harmer
0.004
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
941801AE2-185 GEN
Solar/Wind Harmer
4.212
270030AE2-140 GEN
Solar/Wind Harmer
13.804
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.094
316359AB2-059 GEN
Solar/Wind Harmer
0.421
316049AB1-081 GEN
Solar/Wind Harmer
0.67
3142053HEARTS
Solar/Wind Harmer
0.206
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.117
971623AH1-311 GEN
Solar/Wind Harmer
0.234
961601AG1-000A GEN
Solar/Wind Harmer
8.141
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221
NYPJM->LTFIMP_NY
CLTF
2.382
LGEELTFEXP_LGEE->PJM
CLTF
2.675
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51192_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51192_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.25 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5458.06
MW Contribution:40.85
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
62.844
957481AF2-042 GEN
Solar/Wind Harmer
166.962
315693AD1-088 GEN
Solar/Wind Harmer
24.364
962491AG1-098 GEN
Solar/Wind Harmer
32.107
315687AD1-152 GEN
Solar/Wind Harmer
5.339
316003AC1-222 GEN
Solar/Wind Harmer
3.203
970401AG2-262 GEN
Solar/Wind Harmer
2.096
316237AB2-079_GEN
Solar/Wind Harmer
0.866
970685AG2-442 GEN
Solar/Wind Harmer
23.673
963171AG1-166 GEN
Solar/Wind Harmer
3.329
971563AH1-280 GEN
Solar/Wind Harmer
3.329
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.119
316129AC1-054 GEN
Solar/Wind Harmer
1.828
970223AG2-152 GEN
Solar/Wind Harmer
17.247
270016AE1-250 BESS
Solar/Wind Harmer
2.846
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.591
316322AB2-045
Solar/Wind Harmer
0.516
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.545
270030AE2-140 GEN
Solar/Wind Harmer
19.786
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.774
316049AB1-081 GEN
Solar/Wind Harmer
1.419
3142053HEARTS
Solar/Wind Harmer
0.155
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
168.81
316478AD1-087 GEN
Solar/Wind Harmer
4.25
316486AD2-202 GEN
Solar/Wind Harmer
1.245
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
1.046
960061AF2-297 GEN
Solar/Wind Harmer
17.357
316283AC2-100 C
Solar/Wind Harmer
2.974
971683AH1-343 GEN
Solar/Wind Harmer
13.43
316131AB2-060 GEN
Solar/Wind Harmer
3.068
964241AG1-285 GEN
Solar/Wind Harmer
21.992
315785AD2-033 C
Solar/Wind Harmer
6.274
970257AG2-171 GEN
Solar/Wind Harmer
10.314
959311AF2-222 GEN
Solar/Wind Harmer
28.571
963181AG1-167 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.462
3151641KERR 7
50/50
0.537
971967AH1-528 GEN
Solar/Wind Harmer
126.052
970085AG2-068 GEN
Solar/Wind Harmer
41.896
970581AG2-369 GEN
Solar/Wind Harmer
36.031
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.3
970865AG2-541 GEN
Solar/Wind Harmer
11.953
316239AB2-077_GEN
Solar/Wind Harmer
0.866
316238AB2-078_GEN
Solar/Wind Harmer
0.866
971443AH1-215 GEN
Solar/Wind Harmer
5.422
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.136
970681AG2-440 GEN
Solar/Wind Harmer
16.909
946301AF1-294 GEN
Solar/Wind Harmer
6.825
961791AG1-021 GEN
Solar/Wind Harmer
3.329
270455AD2-022 GEN
Solar/Wind Harmer
4.714
270457AD2-023 GEN
Solar/Wind Harmer
2.39
315657AE1-056 GEN
Solar/Wind Harmer
9.877
316123AC1-075 GEN
Solar/Wind Harmer
2.797
970165AG2-112 GEN
Solar/Wind Harmer
2.462
970163AG2-111 GEN
Solar/Wind Harmer
2.349
970831AG2-522 GEN
Solar/Wind Harmer
9.678
970285AG2-188 GEN
Solar/Wind Harmer
15.412
971845AH1-439 GEN
Solar/Wind Harmer
8.567
270069AE2-166 C O1
Solar/Wind Harmer
2.422
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
942461AE2-259 GEN
Solar/Wind Harmer
3.832
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.378
270197AD1-017 GEN1
Solar/Wind Harmer
1.68
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.844
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.545
270336AE1-100 GEN
Solar/Wind Harmer
1.569
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
5.12
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
59.226
970099AG2-077 GEN
Solar/Wind Harmer
66.785
971741AH1-377 GEN
Solar/Wind Harmer
44.199
970301AG2-198 GEN
Solar/Wind Harmer
17.416
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.86
316222AC1-221 GEN
Solar/Wind Harmer
3.218
962561AG1-105 GEN
Solar/Wind Harmer
17.755
939181AE1-148 GEN
Solar/Wind Harmer
16.34
313527AB2-043 GEN
Solar/Wind Harmer
4.631
970323AG2-213 GEN
Solar/Wind Harmer
13.752
971775AH1-396 GEN
Solar/Wind Harmer
1.958
316034AC1-036 C
Solar/Wind Harmer
0.51
958211AF2-115 GEN
Solar/Wind Harmer
4.162
963191AG1-168 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.11
270013AE1-250 PV
Solar/Wind Harmer
2.846
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.4
316197AC1-042 GEN
Solar/Wind Harmer
1.819
942671AE2-283 GEN
Solar/Wind Harmer
4.898
316263AC1-034 GEN
Solar/Wind Harmer
6.166
961601AG1-000A GEN
Solar/Wind Harmer
5.056
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221
NYPJM->LTFIMP_NY
CLTF
2.382
LGEELTFEXP_LGEE->PJM
CLTF
2.675
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51172_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51172_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.79 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5435.07
MW Contribution:40.64
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
11.056
3151051BRUNSWICKS1
50/50
17.38
3151021BRUNSWICKG1
50/50
8.374
971451AH1-221 GEN
50/50
25.435
3151531CLOVER1
50/50
9.312
3151601KERR 3
50/50
0.538
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.8
971629AH1-314 GEN
50/50
17.875
3151561HALLBR1
50/50
0.366
970919AG2-571 GEN
Solar/Wind Harmer
21.227
970087AG2-069 GEN
Solar/Wind Harmer
62.431
957481AF2-042 GEN
Solar/Wind Harmer
166.01
315693AD1-088 GEN
Solar/Wind Harmer
24.233
962491AG1-098 GEN
Solar/Wind Harmer
31.935
315687AD1-152 GEN
Solar/Wind Harmer
5.313
316003AC1-222 GEN
Solar/Wind Harmer
3.193
970401AG2-262 GEN
Solar/Wind Harmer
2.094
316237AB2-079_GEN
Solar/Wind Harmer
0.868
970685AG2-442 GEN
Solar/Wind Harmer
23.682
963171AG1-166 GEN
Solar/Wind Harmer
3.328
971563AH1-280 GEN
Solar/Wind Harmer
3.328
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.224
316129AC1-054 GEN
Solar/Wind Harmer
1.849
970223AG2-152 GEN
Solar/Wind Harmer
17.201
270016AE1-250 BESS
Solar/Wind Harmer
2.839
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.577
316322AB2-045
Solar/Wind Harmer
0.514
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.53
270030AE2-140 GEN
Solar/Wind Harmer
19.734
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.817
316049AB1-081 GEN
Solar/Wind Harmer
1.454
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.785
316375AC2-012 GEN
Solar/Wind Helper
1.014
3145336SMITFLD
Solar/Wind Helper
1.482
316388AE2-253 GEN
Solar/Wind Helper
1.397
3146456SLIGO L269
Solar/Wind Helper
0.359
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.402
316159AE1-175 C
Solar/Wind Helper
0.529
316381AD1-082 GEN
Solar/Wind Helper
1.758
316458AB2-190 GEN2
Solar/Wind Helper
1.933
3141766HARMONY
Solar/Wind Helper
0.065
3138133OCRAN
Solar/Wind Helper
0.193
3142433PROV 92
Solar/Wind Helper
1.275
3142543TWELFTH
Solar/Wind Helper
0.029
964211AG1-282 GEN
Solar/Wind Helper
0.412
3141726DUNNSVL
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.961
3146516WINFALL
Solar/Wind Helper
0.297
316337AD2-073 GEN
Solar/Wind Helper
0.448
3142416OLDCHRC
Solar/Wind Helper
0.759
3142416OLDCHRC
Solar/Wind Helper
0.291
3143526WINTERP
Solar/Wind Helper
1.499
3143226MDLTHAN
Solar/Wind Helper
0.284
315800Z1-036_GEN1
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
315244AE2-183_ST
50/50
19.115
963041AG1-153 GEN
50/50
16.957
3151541CLOVER2
50/50
9.268
3151611KERR 4
50/50
0.538
3151621KERR 5
50/50
0.538
3151631KERR 6
50/50
0.538
3151641KERR 7
50/50
0.538
971967AH1-528 GEN
Solar/Wind Harmer
125.223
970085AG2-068 GEN
Solar/Wind Harmer
41.62
970581AG2-369 GEN
Solar/Wind Harmer
35.794
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.295
970865AG2-541 GEN
Solar/Wind Harmer
11.917
316239AB2-077_GEN
Solar/Wind Harmer
0.868
316238AB2-078_GEN
Solar/Wind Harmer
0.868
971443AH1-215 GEN
Solar/Wind Harmer
5.428
3144303KENBRDG
Solar/Wind Harmer
-0.022
3151031BRUNSWICKG2
50/50
8.374
970413AG2-270 GEN
50/50
40.637
3151591KERR 2
50/50
0.538
3144293JTRSVLE
50/50
0.8
970917AG2-570 GEN
Solar/Wind Harmer
167.695
316478AD1-087 GEN
Solar/Wind Harmer
4.227
316486AD2-202 GEN
Solar/Wind Harmer
1.238
970909AG2-566 GEN
Solar/Wind Harmer
3.291
316248AF1-058 C
Solar/Wind Harmer
1.043
960061AF2-297 GEN
Solar/Wind Harmer
17.305
316283AC2-100 C
Solar/Wind Harmer
2.965
971683AH1-343 GEN
Solar/Wind Harmer
13.39
316131AB2-060 GEN
Solar/Wind Harmer
3.076
964241AG1-285 GEN
Solar/Wind Harmer
22.038
315785AD2-033 C
Solar/Wind Harmer
6.282
970257AG2-171 GEN
Solar/Wind Harmer
10.326
959311AF2-222 GEN
Solar/Wind Harmer
28.597
963181AG1-167 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.449
942461AE2-259 GEN
Solar/Wind Harmer
3.824
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.375
270197AD1-017 GEN1
Solar/Wind Harmer
1.676
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.834
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.53
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
970683AG2-441 GEN
Solar/Wind Harmer
21.145
970681AG2-440 GEN
Solar/Wind Harmer
16.916
946301AF1-294 GEN
Solar/Wind Harmer
6.823
961791AG1-021 GEN
Solar/Wind Harmer
3.328
270455AD2-022 GEN
Solar/Wind Harmer
4.701
270457AD2-023 GEN
Solar/Wind Harmer
2.384
315657AE1-056 GEN
Solar/Wind Harmer
9.869
316123AC1-075 GEN
Solar/Wind Harmer
2.789
970165AG2-112 GEN
Solar/Wind Harmer
2.455
970163AG2-111 GEN
Solar/Wind Harmer
2.342
970831AG2-522 GEN
Solar/Wind Harmer
9.813
970285AG2-188 GEN
Solar/Wind Harmer
15.354
971845AH1-439 GEN
Solar/Wind Harmer
8.535
270069AE2-166 C O1
Solar/Wind Harmer
2.415
319010AE1-072 C
Solar/Wind Helper
4.079
3143316POE
Solar/Wind Helper
1.407
316305AF2-043 C
Solar/Wind Helper
0.473
316369SG1_INVT
Solar/Wind Helper
1.664
957831AF2-077 GEN
Solar/Wind Helper
0.466
316132AB2-190 GEN1
Solar/Wind Helper
1.933
316349AD2-085 GEN
Solar/Wind Helper
1.523
313526AB2-022
Solar/Wind Helper
0.505
957601AF2-054 GEN
Solar/Wind Helper
0.438
3141873WAN 176
Solar/Wind Helper
0.065
315662AE1-191 GEN
Solar/Wind Helper
1.747
315666AE1-190 GEN
Solar/Wind Helper
0.437
316059AD1-063 C
Solar/Wind Helper
0.326
3141913WHIT STONE
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3138133OCRAN
Solar/Wind Helper
0.097
3143873LANEXA
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.128
316321Z2-027
Solar/Wind Helper
0.487
3145176PASQUOTANK
Solar/Wind Helper
0.198
3141813NORNECK
Solar/Wind Helper
0.304
316312AB1-027
Solar/Wind Helper
0.556
316233AE1-074 FULL
Solar/Wind Helper
0.44
316223AC1-118
Solar/Wind Helper
0.438
316315AB2-025 C
Solar/Wind Helper
0.418
315611Z1-036_GEN2
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
3130156CHOWAN
Solar/Wind Helper
0.226
315242AE2-183_GT2
50/50
11.056
315241AE2-183_GT1
50/50
10.988
972185AH1-677 GEN
50/50
39.858
3151041BRUNSWICKG3
50/50
8.374
972187AH1-678 GEN
50/50
19.217
3152661PLYWOOD A
50/50
0.67
970535AG2-341 GEN
50/50
4.577
3144293JTRSVLE
50/50
0.8
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
58.849
970099AG2-077 GEN
Solar/Wind Harmer
66.404
971741AH1-377 GEN
Solar/Wind Harmer
43.978
970301AG2-198 GEN
Solar/Wind Harmer
17.332
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.854
316222AC1-221 GEN
Solar/Wind Harmer
3.208
962561AG1-105 GEN
Solar/Wind Harmer
17.747
939181AE1-148 GEN
Solar/Wind Harmer
16.378
313527AB2-043 GEN
Solar/Wind Harmer
4.643
970323AG2-213 GEN
Solar/Wind Harmer
13.768
971775AH1-396 GEN
Solar/Wind Harmer
1.961
316034AC1-036 C
Solar/Wind Harmer
0.511
958211AF2-115 GEN
Solar/Wind Harmer
4.16
963191AG1-168 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.066
270013AE1-250 PV
Solar/Wind Harmer
2.839
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.394
316197AC1-042 GEN
Solar/Wind Harmer
1.815
942671AE2-283 GEN
Solar/Wind Harmer
4.885
316263AC1-034 GEN
Solar/Wind Harmer
6.316
961601AG1-000A GEN
Solar/Wind Harmer
5.186
316036AC1-147 C
Solar/Wind Helper
0.59
3142956BIRDNECK
Solar/Wind Helper
0.259
316316AC1-027 C
Solar/Wind Helper
0.606
316185AD1-033 GEN
Solar/Wind Helper
1.799
3145506HICKORY
Solar/Wind Helper
1.507
3145506HICKORY
Solar/Wind Helper
0.904
3145506HICKORY
Solar/Wind Helper
0.226
316236AE1-162_GEN
Solar/Wind Helper
0.498
316339AD2-160 GEN
Solar/Wind Helper
1.397
316018AA1-139 ULT2
Solar/Wind Helper
1.567
316017AA1-139 ULT1
Solar/Wind Helper
1.665
3137176SLIGO L2192
Solar/Wind Helper
1.432
3130086AYDLETT
Solar/Wind Helper
1.421
316033AB2-134 GEN
Solar/Wind Helper
1.19
315697AD1-025 GEN
Solar/Wind Helper
3.953
3146386ELIZ CT
Solar/Wind Helper
0.331
316240AF1-291 C
Solar/Wind Helper
0.444
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.318
316075AC2-137 C
Solar/Wind Helper
0.467
316077AC2-138 C
Solar/Wind Helper
0.286
316431W1029_GEN1
Solar/Wind Helper
1.225
316433W1029_GEN2
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3143526WINTERP
Solar/Wind Helper
1.499
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
966871AG1-558 GEN
Solar/Wind Helper
0.374
3144356SAPONY
Solar/Wind Helper
0.492
316468AD1-105 GEN
Solar/Wind Helper
1.305
270336AE1-100 GEN
Solar/Wind Harmer
1.564
961601AG1-000A GEN
Solar/Wind Harmer
5.252
315773AC2-141 GEN
Solar/Wind Helper
9.163
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.058
3145336SMITFLD
Solar/Wind Helper
0.148
3146456SLIGO L269
Solar/Wind Helper
0.359
316382AG1-145 C
Solar/Wind Helper
0.469
315839AE2-212 C
Solar/Wind Helper
0.457
316320Y1-086
Solar/Wind Helper
0.148
316156AD2-030 GEN
Solar/Wind Helper
0.492
316280AD1-041 GEN
Solar/Wind Helper
1.092
3142946ENON
Solar/Wind Helper
0.105
316484AD2-074 GEN
Solar/Wind Helper
0.607
316404AE1-155 C
Solar/Wind Helper
2.624
316435W1029_GEN3
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3141906WESTMOR
Solar/Wind Helper
0.115
3146626S HERTFORD
Solar/Wind Helper
0.28
316473AC1-191 GEN
Solar/Wind Helper
1.696
3145273HOLLAND
Solar/Wind Helper
0.188
966881AG1-559 GEN
Solar/Wind Helper
0.329
3146376EDENTON
Solar/Wind Helper
0.226
CPLELTFEXP_CPLE->PJM
CLTF
19.708
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.004
LAGNLTFEXP_LAGN->PJM
CLTF
14.626
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.161
TVALTFEXP_TVA->PJM
CLTF
7.294
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.554
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.081
MECLTFEXP_MEC->PJM
CLTF
7.343
SIGELTFEXP_SIGE->PJM
CLTF
0.22
NYPJM->LTFIMP_NY
CLTF
2.38
LGEELTFEXP_LGEE->PJM
CLTF
2.666
WECLTFEXP_WEC->PJM
CLTF
1.395
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 511T544_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T544_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.19 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5355.19
MW Contribution:40.27
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
10.962
3151051BRUNSWICKS1
50/50
17.232
3151021BRUNSWICKG1
50/50
8.303
971451AH1-221 GEN
50/50
25.218
3151531CLOVER1
50/50
9.227
3151601KERR 3
50/50
0.532
3151581KERR 1
50/50
0.19
3144293JTRSVLE
50/50
0.79
971629AH1-314 GEN
50/50
17.731
3151561HALLBR1
50/50
0.363
970919AG2-571 GEN
Solar/Wind Harmer
21.047
970087AG2-069 GEN
Solar/Wind Harmer
61.902
957481AF2-042 GEN
Solar/Wind Harmer
164.509
315693AD1-088 GEN
Solar/Wind Harmer
24.007
962491AG1-098 GEN
Solar/Wind Harmer
31.634
315687AD1-152 GEN
Solar/Wind Harmer
5.265
316003AC1-222 GEN
Solar/Wind Harmer
3.162
970401AG2-262 GEN
Solar/Wind Harmer
2.07
316237AB2-079_GEN
Solar/Wind Harmer
0.856
970685AG2-442 GEN
Solar/Wind Harmer
23.354
963171AG1-166 GEN
Solar/Wind Harmer
3.283
971563AH1-280 GEN
Solar/Wind Harmer
3.283
3146926FARMVIL
Solar/Wind Harmer
-0.014
971065AG2-659 GEN
Solar/Wind Harmer
11.094
316129AC1-054 GEN
Solar/Wind Harmer
1.827
970223AG2-152 GEN
Solar/Wind Harmer
17.059
270016AE1-250 BESS
Solar/Wind Harmer
2.815
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.528
316322AB2-045
Solar/Wind Harmer
0.506
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.477
270030AE2-140 GEN
Solar/Wind Harmer
19.567
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.809
316049AB1-081 GEN
Solar/Wind Harmer
1.448
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.244
316381AD1-082 GEN
Solar/Wind Helper
1.747
316375AC2-012 GEN
Solar/Wind Helper
0.879
3145336SMITFLD
Solar/Wind Helper
1.331
316458AB2-190 GEN2
Solar/Wind Helper
1.893
316159AE1-175 C
Solar/Wind Helper
0.497
316388AE2-253 GEN
Solar/Wind Helper
1.201
3142433PROV 92
Solar/Wind Helper
1.254
3142543TWELFTH
Solar/Wind Helper
0.03
3141766HARMONY
Solar/Wind Helper
0.062
3146456SLIGO L269
Solar/Wind Helper
0.308
3138133OCRAN
Solar/Wind Helper
0.185
316072AD1-144
Solar/Wind Helper
0.35
316246AF1-032 C
Solar/Wind Helper
0.342
964211AG1-282 GEN
Solar/Wind Helper
0.397
3141726DUNNSVL
Solar/Wind Helper
1.179
3143526WINTERP
Solar/Wind Helper
1.519
3142416OLDCHRC
Solar/Wind Helper
0.752
3143226MDLTHAN
Solar/Wind Helper
0.289
3142416OLDCHRC
Solar/Wind Helper
0.288
316337AD2-073 GEN
Solar/Wind Helper
0.434
3146516WINFALL
Solar/Wind Helper
0.813
3146516WINFALL
Solar/Wind Helper
0.251
315244AE2-183_ST
50/50
18.952
963041AG1-153 GEN
50/50
16.812
3151541CLOVER2
50/50
9.183
3151611KERR 4
50/50
0.532
3151621KERR 5
50/50
0.532
3151631KERR 6
50/50
0.532
3151641KERR 7
50/50
0.532
971967AH1-528 GEN
Solar/Wind Harmer
124.141
970085AG2-068 GEN
Solar/Wind Harmer
41.268
970581AG2-369 GEN
Solar/Wind Harmer
35.491
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.271
970865AG2-541 GEN
Solar/Wind Harmer
11.801
316239AB2-077_GEN
Solar/Wind Harmer
0.856
316238AB2-078_GEN
Solar/Wind Harmer
0.856
971443AH1-215 GEN
Solar/Wind Harmer
5.352
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
20.851
970681AG2-440 GEN
Solar/Wind Harmer
16.681
946301AF1-294 GEN
Solar/Wind Harmer
6.73
961791AG1-021 GEN
Solar/Wind Harmer
3.283
270455AD2-022 GEN
Solar/Wind Harmer
4.664
270457AD2-023 GEN
Solar/Wind Harmer
2.365
315657AE1-056 GEN
Solar/Wind Harmer
9.735
316123AC1-075 GEN
Solar/Wind Harmer
2.761
970165AG2-112 GEN
Solar/Wind Harmer
2.431
970163AG2-111 GEN
Solar/Wind Harmer
2.319
970831AG2-522 GEN
Solar/Wind Harmer
9.696
970285AG2-188 GEN
Solar/Wind Harmer
15.118
971845AH1-439 GEN
Solar/Wind Harmer
8.397
270069AE2-166 C O1
Solar/Wind Harmer
2.394
3143316POE
Solar/Wind Helper
1.57
316132AB2-190 GEN1
Solar/Wind Helper
1.893
316369SG1_INVT
Solar/Wind Helper
1.59
957831AF2-077 GEN
Solar/Wind Helper
0.437
316315AB2-025 C
Solar/Wind Helper
0.494
957601AF2-054 GEN
Solar/Wind Helper
0.418
3141873WAN 176
Solar/Wind Helper
0.062
315662AE1-191 GEN
Solar/Wind Helper
1.674
315666AE1-190 GEN
Solar/Wind Helper
0.419
3143873LANEXA
Solar/Wind Helper
0.186
316059AD1-063 C
Solar/Wind Helper
0.312
3141913WHIT STONE
Solar/Wind Helper
0.309
3138133OCRAN
Solar/Wind Helper
0.093
3141783LANCAST
Solar/Wind Helper
0.184
3141783LANCAST
Solar/Wind Helper
0.123
319010AE1-072 C
Solar/Wind Helper
3.5
316349AD2-085 GEN
Solar/Wind Helper
1.396
316305AF2-043 C
Solar/Wind Helper
0.402
3141813NORNECK
Solar/Wind Helper
0.293
316233AE1-074 FULL
Solar/Wind Helper
0.446
316312AB1-027
Solar/Wind Helper
0.55
313526AB2-022
Solar/Wind Helper
0.431
316223AC1-118
Solar/Wind Helper
0.424
3146486SUNBURY
Solar/Wind Helper
0.274
3146486SUNBURY
Solar/Wind Helper
0.274
316321Z2-027
Solar/Wind Helper
0.414
3145176PASQUOTANK
Solar/Wind Helper
0.168
3151031BRUNSWICKG2
50/50
8.303
970413AG2-270 GEN
50/50
40.265
3151591KERR 2
50/50
0.532
3144293JTRSVLE
50/50
0.79
970917AG2-570 GEN
Solar/Wind Harmer
166.275
316478AD1-087 GEN
Solar/Wind Harmer
4.189
316486AD2-202 GEN
Solar/Wind Harmer
1.227
970909AG2-566 GEN
Solar/Wind Harmer
3.255
316248AF1-058 C
Solar/Wind Harmer
1.033
960061AF2-297 GEN
Solar/Wind Harmer
17.135
316283AC2-100 C
Solar/Wind Harmer
2.94
971683AH1-343 GEN
Solar/Wind Harmer
13.259
316131AB2-060 GEN
Solar/Wind Harmer
3.032
964241AG1-285 GEN
Solar/Wind Harmer
21.724
315785AD2-033 C
Solar/Wind Harmer
6.194
970257AG2-171 GEN
Solar/Wind Harmer
10.181
959311AF2-222 GEN
Solar/Wind Harmer
28.197
963181AG1-167 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.081
971193AH1-056 GEN
Solar/Wind Harmer
16.225
942461AE2-259 GEN
Solar/Wind Harmer
3.773
3146926FARMVIL
Solar/Wind Harmer
-0.014
270018AE2-047 C O1
Solar/Wind Harmer
1.363
270197AD1-017 GEN1
Solar/Wind Harmer
1.661
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.802
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.477
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.551
961601AG1-000A GEN
Solar/Wind Harmer
5.225
315773AC2-141 GEN
Solar/Wind Helper
8.525
315839AE2-212 C
Solar/Wind Helper
0.497
3144536CHRHLND
Solar/Wind Helper
0.05
3144873MCLAUGH
Solar/Wind Helper
0.008
3145336SMITFLD
Solar/Wind Helper
0.133
316382AG1-145 C
Solar/Wind Helper
0.441
316156AD2-030 GEN
Solar/Wind Helper
0.47
3142946ENON
Solar/Wind Helper
0.104
316280AD1-041 GEN
Solar/Wind Helper
1.046
3146456SLIGO L269
Solar/Wind Helper
0.308
316484AD2-074 GEN
Solar/Wind Helper
0.583
316404AE1-155 C
Solar/Wind Helper
2.523
316320Y1-086
Solar/Wind Helper
0.126
316473AC1-191 GEN
Solar/Wind Helper
1.704
3141906WESTMOR
Solar/Wind Helper
0.111
316435W1029_GEN3
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
966881AG1-559 GEN
Solar/Wind Helper
0.328
3146626S HERTFORD
Solar/Wind Helper
0.236
315242AE2-183_GT2
50/50
10.962
315241AE2-183_GT1
50/50
10.894
972185AH1-677 GEN
50/50
39.518
3151041BRUNSWICKG3
50/50
8.303
972187AH1-678 GEN
50/50
19.053
3152661PLYWOOD A
50/50
0.663
970535AG2-341 GEN
50/50
4.519
3144293JTRSVLE
50/50
0.79
3144293JTRSVLE
50/50
0.665
970933AG2-581 GEN
Solar/Wind Harmer
58.334
970099AG2-077 GEN
Solar/Wind Harmer
65.804
971741AH1-377 GEN
Solar/Wind Harmer
43.523
970301AG2-198 GEN
Solar/Wind Harmer
17.145
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.775
316222AC1-221 GEN
Solar/Wind Harmer
3.182
962561AG1-105 GEN
Solar/Wind Harmer
17.536
939181AE1-148 GEN
Solar/Wind Harmer
16.186
313527AB2-043 GEN
Solar/Wind Harmer
4.576
970323AG2-213 GEN
Solar/Wind Harmer
13.574
971775AH1-396 GEN
Solar/Wind Harmer
1.933
316034AC1-036 C
Solar/Wind Harmer
0.503
958211AF2-115 GEN
Solar/Wind Harmer
4.103
963191AG1-168 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
14.918
270013AE1-250 PV
Solar/Wind Harmer
2.815
3146776BUCKING
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.37
316197AC1-042 GEN
Solar/Wind Harmer
1.797
942671AE2-283 GEN
Solar/Wind Harmer
4.838
316263AC1-034 GEN
Solar/Wind Harmer
6.29
961601AG1-000A GEN
Solar/Wind Harmer
5.16
316240AF1-291 C
Solar/Wind Helper
0.471
316036AC1-147 C
Solar/Wind Helper
0.511
316236AE1-162_GEN
Solar/Wind Helper
0.447
316316AC1-027 C
Solar/Wind Helper
0.524
3142956BIRDNECK
Solar/Wind Helper
0.223
316033AB2-134 GEN
Solar/Wind Helper
1.137
315697AD1-025 GEN
Solar/Wind Helper
3.779
316185AD1-033 GEN
Solar/Wind Helper
1.551
3145506HICKORY
Solar/Wind Helper
1.298
3145506HICKORY
Solar/Wind Helper
0.779
3145506HICKORY
Solar/Wind Helper
0.195
3144356SAPONY
Solar/Wind Helper
0.581
316339AD2-160 GEN
Solar/Wind Helper
1.201
316018AA1-139 ULT2
Solar/Wind Helper
1.346
316017AA1-139 ULT1
Solar/Wind Helper
1.43
3142946ENON
Solar/Wind Helper
0.031
3137176SLIGO L2192
Solar/Wind Helper
1.229
3130086AYDLETT
Solar/Wind Helper
1.219
316487AF1-042 GEN
Solar/Wind Helper
0.305
316075AC2-137 C
Solar/Wind Helper
0.459
316077AC2-138 C
Solar/Wind Helper
0.276
3143526WINTERP
Solar/Wind Helper
1.519
3146386ELIZ CT
Solar/Wind Helper
0.283
966871AG1-558 GEN
Solar/Wind Helper
0.376
316468AD1-105 GEN
Solar/Wind Helper
1.308
316431W1029_GEN1
Solar/Wind Helper
1.037
316433W1029_GEN2
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146626S HERTFORD
Solar/Wind Helper
0.236
3146626S HERTFORD
Solar/Wind Helper
0.236
CPLELTFEXP_CPLE->PJM
CLTF
19.58
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.279
LAGNLTFEXP_LAGN->PJM
CLTF
14.499
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.842
TVALTFEXP_TVA->PJM
CLTF
7.231
CBM West 1LTFEXP_CBM-W1->PJM
CBM
48.979
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.858
MECLTFEXP_MEC->PJM
CLTF
7.267
SIGELTFEXP_SIGE->PJM
CLTF
0.218
NYPJM->LTFIMP_NY
CLTF
2.38
LGEELTFEXP_LGEE->PJM
CLTF
2.637
WECLTFEXP_WEC->PJM
CLTF
1.38
AG2-052LTFEXP_AG2-052->PJM
LTF
0.074
AH1-155LTFEXP_AH1-155->PJM
LTF
0.111

Details for 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SEPTA-8SURRY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.87 %
Rating:2931.0 MVA
Rating Type:C
MVA to Mitigate:3044.37
MW Contribution:18.7
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
7.478
963041AG1-153 GEN
50/50
6.855
3151541CLOVER2
50/50
4.265
3151081ELIZAR1
50/50
18.321
941031AE2-094 GEN
Solar/Wind Harmer
57.43
944011AF1-069 GEN
Solar/Wind Harmer
17.995
970673AG2-436 GEN
Solar/Wind Harmer
62.661
970673AG2-436 GEN
Solar/Wind Harmer
31.727
971967AH1-528 GEN
Solar/Wind Harmer
54.485
970085AG2-068 GEN
Solar/Wind Harmer
17.073
970581AG2-369 GEN
Solar/Wind Harmer
14.683
3151091ELIZAR2
Adder
16.966
3152611GOSPORTB
Adder
2.331
3152621GOSPORTC
Adder
1.978
3152601GOSPORTA
Adder
1.825
957871AF2-081 GEN
Solar/Wind Harmer
10.216
319010AE1-072 C
Solar/Wind Harmer
4.045
3146406KITTY HAWK
Solar/Wind Harmer
0.017
313526AB2-022
Solar/Wind Harmer
0.498
316321Z2-027
Solar/Wind Harmer
0.479
3146396TANGLEW
Solar/Wind Harmer
0.327
3145176PASQUOTANK
Solar/Wind Harmer
-0.011
3147173SINAI
Solar/Wind Harmer
-0.017
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.188
316239AB2-077_GEN
Solar/Wind Harmer
0.514
316238AB2-078_GEN
Solar/Wind Harmer
0.514
970831AG2-522 GEN
Solar/Wind Harmer
8.491
315611Z1-036_GEN2
Solar/Wind Harmer
4.001
3130156CHOWAN
Solar/Wind Harmer
-0.016
3130156CHOWAN
Solar/Wind Harmer
-0.016
316315AB2-025 C
Solar/Wind Harmer
0.431
315814AE2-033 C
Solar/Wind Harmer
14.87
946281AF1-292 GEN
Solar/Wind Harmer
0.356
316087AB2-174 GEN
Solar/Wind Harmer
2.26
971443AH1-215 GEN
Solar/Wind Harmer
3.103
3137643SOCKMAN
Solar/Wind Harmer
-0.063
315816AE2-034 GEN
Solar/Wind Harmer
1.272
3144303KENBRDG
Solar/Wind Harmer
-0.013
315652AC1-086 GEN
Solar/Wind Harmer
17.441
3145796HORNRTN
Solar/Wind Harmer
-0.049
3145796HORNRTN
Solar/Wind Harmer
-0.006
316319Z2-044 C
Solar/Wind Harmer
0.856
3130546PLYMOUTH
Solar/Wind Harmer
-0.015
315732AD1-074 GEN1
Solar/Wind Harmer
3.122
315733AD1-074 GEN2
Solar/Wind Harmer
3.122
315735AD1-075 GEN1
Solar/Wind Harmer
1.561
3145573BETHELC
Solar/Wind Harmer
-0.015
3145573BETHELC
Solar/Wind Harmer
-0.015
316420AA1-050 GEN
Solar/Wind Harmer
1.751
957861AF2-080 GEN
Solar/Wind Harmer
6.681
3146033SCOT NK
Solar/Wind Harmer
-0.061
315607AA1-063A GEN
Solar/Wind Harmer
1.534
316005AA1-067
Solar/Wind Harmer
0.307
3145746EVERETS
Solar/Wind Harmer
-0.06
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
1.989
3146206CASHIE
Solar/Wind Harmer
-0.015
970601AG2-382 GEN
Solar/Wind Harmer
6.629
970683AG2-441 GEN
Solar/Wind Harmer
11.827
970681AG2-440 GEN
Solar/Wind Harmer
9.461
3146043SEABORD
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.03
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145513AHOSKIE
Solar/Wind Harmer
0.129
961941AG1-037 GEN
Solar/Wind Harmer
0.111
3145513AHOSKIE
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
5.947
946301AF1-294 GEN
Solar/Wind Harmer
3.74
961791AG1-021 GEN
Solar/Wind Harmer
1.825
316318V4-068
Solar/Wind Harmer
0.362
3145893MURPHYS
Solar/Wind Harmer
-0.039
3145893MURPHYS
Solar/Wind Harmer
-0.014
3146486SUNBURY
Solar/Wind Harmer
-0.014
3146486SUNBURY
Solar/Wind Harmer
-0.014
965291AG1-394 GEN
Solar/Wind Harmer
1.275
315657AE1-056 GEN
Solar/Wind Harmer
5.332
270455AD2-022 GEN
Solar/Wind Harmer
2.402
270457AD2-023 GEN
Solar/Wind Harmer
1.218
316123AC1-075 GEN
Solar/Wind Harmer
1.387
970165AG2-112 GEN
Solar/Wind Harmer
1.221
970163AG2-111 GEN
Solar/Wind Harmer
1.165
957831AF2-077 GEN
Solar/Wind Helper
0.39
957601AF2-054 GEN
Solar/Wind Helper
0.337
3141873WAN 176
Solar/Wind Helper
0.05
3141913WHIT STONE
Solar/Wind Helper
0.247
316059AD1-063 C
Solar/Wind Helper
0.249
3138133OCRAN
Solar/Wind Helper
0.074
3141783LANCAST
Solar/Wind Helper
0.146
3141783LANCAST
Solar/Wind Helper
0.098
315662AE1-191 GEN
Solar/Wind Helper
1.31
315666AE1-190 GEN
Solar/Wind Helper
0.327
3141813NORNECK
Solar/Wind Helper
0.225
3151031BRUNSWICKG2
50/50
3.386
970413AG2-270 GEN
50/50
18.7
3151101ELIZAR3
50/50
18.555
315773AC2-141 GEN
Solar/Wind Harmer
27.544
970917AG2-570 GEN
Solar/Wind Harmer
68.686
944581AF1-123 GEN
Solar/Wind Harmer
109.673
944601AF1-125 GEN
Solar/Wind Harmer
107.961
316478AD1-087 GEN
Solar/Wind Harmer
1.946
316486AD2-202 GEN
Solar/Wind Harmer
0.57
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.454
316320Y1-086
Solar/Wind Harmer
1.083
3144536CHRHLND
Solar/Wind Harmer
-0.003
316248AF1-058 C
Solar/Wind Harmer
0.522
960061AF2-297 GEN
Solar/Wind Harmer
8.669
316131AB2-060 GEN
Solar/Wind Harmer
1.825
964241AG1-285 GEN
Solar/Wind Harmer
12.927
3146516WINFALL
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.016
970909AG2-566 GEN
Solar/Wind Harmer
1.549
3147043LAWRENC
Solar/Wind Harmer
-0.01
3146376EDENTON
Solar/Wind Harmer
-0.016
315785AD2-033 C
Solar/Wind Harmer
3.613
316435W1029_GEN3
Solar/Wind Harmer
2.886
966621AG1-532 GEN
Solar/Wind Harmer
0.323
316283AC2-100 C
Solar/Wind Harmer
1.496
313506AB2-031 GEN
Solar/Wind Harmer
1.271
316365GEN2_N
Solar/Wind Harmer
1.06
315614AA2-178 GEN
Solar/Wind Harmer
1.696
970257AG2-171 GEN
Solar/Wind Harmer
5.892
959311AF2-222 GEN
Solar/Wind Harmer
16.228
971683AH1-343 GEN
Solar/Wind Harmer
6.691
3145543BTLEBRO
Solar/Wind Harmer
-0.015
3145543BTLEBRO
Solar/Wind Harmer
-0.015
3145796HORNRTN
Solar/Wind Harmer
-0.062
3145796HORNRTN
Solar/Wind Harmer
-0.015
315724AD1-057 GEN
Solar/Wind Harmer
0.892
3138543CONSLDL
Solar/Wind Harmer
-0.01
3146233WITAKRS
Solar/Wind Harmer
0.324
3146233WITAKRS
Solar/Wind Harmer
-0.01
961601AG1-000A GEN
Solar/Wind Harmer
6.167
316327AA2-057 GEN
Solar/Wind Harmer
1.564
971157AH1-035 GEN
Solar/Wind Harmer
1.935
315737AD1-076 GEN
Solar/Wind Harmer
2.934
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
3146073TAR RVR
Solar/Wind Harmer
-0.015
3146083TARBORO
Solar/Wind Harmer
-0.015
316210AC1-098 GEN
Solar/Wind Harmer
2.411
3145963POPLR C
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.9
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146206CASHIE
Solar/Wind Harmer
-0.015
3146263WOODLND
Solar/Wind Harmer
-0.015
316317KELFORD C
Solar/Wind Harmer
0.709
3145823KELFORD
Solar/Wind Harmer
-0.015
316463AE2-346 GEN
Solar/Wind Harmer
0.239
316140AB2-099
Solar/Wind Harmer
0.1
962331AG1-082 GEN
Solar/Wind Harmer
1.848
3156021HOLLOMANSOL
Solar/Wind Harmer
1.987
3146173TUNIS
Solar/Wind Harmer
-0.015
963181AG1-167 GEN
Solar/Wind Harmer
1.368
3144293JTRSVLE
Adder
0.414
957521AF2-046 GEN
Solar/Wind Harmer
11.482
961681AG1-008 GEN
Solar/Wind Harmer
11.482
3145893MURPHYS
Solar/Wind Harmer
0.101
3145893MURPHYS
Solar/Wind Harmer
-0.014
3156081AA2-088 GEN
Solar/Wind Harmer
4.63
3147133PAMPLIN
Solar/Wind Harmer
-0.044
971193AH1-056 GEN
Solar/Wind Harmer
8.887
942461AE2-259 GEN
Solar/Wind Harmer
1.975
3145273HOLLAND
Solar/Wind Harmer
-0.01
316382AG1-145 C
Solar/Wind Helper
0.451
316156AD2-030 GEN
Solar/Wind Helper
0.379
316280AD1-041 GEN
Solar/Wind Helper
0.819
316484AD2-074 GEN
Solar/Wind Helper
0.458
316404AE1-155 C
Solar/Wind Helper
1.965
970533AG2-339 GEN
50/50
24.232
970531AG2-338 GEN
50/50
9.693
315242AE2-183_GT2
50/50
4.325
315241AE2-183_GT1
50/50
4.299
972185AH1-677 GEN
50/50
15.592
3151041BRUNSWICKG3
50/50
3.386
972187AH1-678 GEN
50/50
7.769
970933AG2-581 GEN
Solar/Wind Harmer
25.842
970099AG2-077 GEN
Solar/Wind Harmer
30.022
316185AD1-033 GEN
Solar/Wind Harmer
2.257
3145506HICKORY
Solar/Wind Harmer
-0.084
3145506HICKORY
Solar/Wind Harmer
-0.051
3145506HICKORY
Solar/Wind Harmer
-0.013
3142956BIRDNECK
Solar/Wind Harmer
1.119
316316AC1-027 C
Solar/Wind Harmer
0.638
316036AC1-147 C
Solar/Wind Harmer
0.557
3150991CHESPKB
Adder
1.926
3150991CHESPKB
Adder
1.879
316339AD2-160 GEN
Solar/Wind Harmer
1.388
316018AA1-139 ULT2
Solar/Wind Harmer
1.75
316017AA1-139 ULT1
Solar/Wind Harmer
1.653
3137176SLIGO L2192
Solar/Wind Harmer
-0.08
3146456SLIGO L269
Solar/Wind Harmer
2.378
3130086AYDLETT
Solar/Wind Harmer
-0.079
3146386ELIZ CT
Solar/Wind Harmer
-0.018
939181AE1-148 GEN
Solar/Wind Harmer
9.967
971741AH1-377 GEN
Solar/Wind Harmer
20.543
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
964791AG1-342 GEN
Solar/Wind Harmer
3.674
962561AG1-105 GEN
Solar/Wind Harmer
9.657
313527AB2-043 GEN
Solar/Wind Harmer
2.762
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.016
970301AG2-198 GEN
Solar/Wind Harmer
8.157
3146376EDENTON
Solar/Wind Harmer
0.475
3146376EDENTON
Solar/Wind Harmer
0.475
3144356SAPONY
Solar/Wind Harmer
0.557
316222AC1-221 GEN
Solar/Wind Harmer
1.617
316431W1029_GEN1
Solar/Wind Harmer
2.886
316433W1029_GEN2
Solar/Wind Harmer
2.886
316181AB2-040 GEN
Solar/Wind Harmer
2.206
970323AG2-213 GEN
Solar/Wind Harmer
7.857
971775AH1-396 GEN
Solar/Wind Harmer
1.119
3145593CAROLNA
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
-0.016
966811AG1-552 GEN
Solar/Wind Harmer
1.767
3145593CAROLNA
Solar/Wind Harmer
0.13
316034AC1-036 C
Solar/Wind Harmer
0.291
3145783HORNRTN
Solar/Wind Harmer
1.86
3145783HORNRTN
Solar/Wind Harmer
1.488
3145783HORNRTN
Solar/Wind Harmer
0.465
3145783HORNRTN
Solar/Wind Harmer
0.186
316426AA2-053 GEN
Solar/Wind Harmer
1.572
316263AC1-034 GEN
Solar/Wind Harmer
7.27
3145796HORNRTN
Solar/Wind Harmer
-0.046
961601AG1-000A GEN
Solar/Wind Harmer
6.09
316274AC1-208 GEN
Solar/Wind Harmer
1.672
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3145493TOT1
Solar/Wind Harmer
0.238
3145453TOT5
Solar/Wind Harmer
0.143
3145603CNETO
Solar/Wind Harmer
0.095
316065AD1-022 GEN
Solar/Wind Harmer
7.628
3145933PARMELE
Solar/Wind Harmer
-0.03
3145933PARMELE
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.015
958211AF2-115 GEN
Solar/Wind Harmer
2.281
963191AG1-168 GEN
Solar/Wind Harmer
1.368
3144293JTRSVLE
Adder
0.414
3144293JTRSVLE
Adder
0.348
3145893MURPHYS
Solar/Wind Harmer
0.405
3145893MURPHYS
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.014
3147133PAMPLIN
Solar/Wind Harmer
-0.011
315742AE1-103 GEN
Solar/Wind Harmer
1.368
316487AF1-042 GEN
Solar/Wind Helper
0.24
316077AC2-138 C
Solar/Wind Helper
0.212
315243AE2-183_GT3
50/50
4.325
3151051BRUNSWICKS1
50/50
7.027
3151021BRUNSWICKG1
50/50
3.386
971451AH1-221 GEN
50/50
10.283
3151531CLOVER1
50/50
4.285
316294AC1-161 GEN
Solar/Wind Harmer
21.297
940641AE2-051 GEN
Solar/Wind Harmer
36.033
970919AG2-571 GEN
Solar/Wind Harmer
8.694
970087AG2-069 GEN
Solar/Wind Harmer
25.61
944591AF1-124 GEN
Solar/Wind Harmer
110.068
957481AF2-042 GEN
Solar/Wind Harmer
75.055
939411AE1-173 GEN
Solar/Wind Harmer
119.429
315693AD1-088 GEN
Solar/Wind Harmer
11.114
962491AG1-098 GEN
Solar/Wind Harmer
14.661
315687AD1-152 GEN
Solar/Wind Harmer
2.497
316375AC2-012 GEN
Solar/Wind Harmer
7.148
3150981CHESPKA
Adder
2.295
316388AE2-253 GEN
Solar/Wind Harmer
1.388
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971065AG2-659 GEN
Solar/Wind Harmer
8.623
970401AG2-262 GEN
Solar/Wind Harmer
1.122
316129AC1-054 GEN
Solar/Wind Harmer
1.501
316237AB2-079_GEN
Solar/Wind Harmer
0.514
3146516WINFALL
Solar/Wind Harmer
-0.053
3146516WINFALL
Solar/Wind Harmer
-0.016
316003AC1-222 GEN
Solar/Wind Harmer
1.598
3147043LAWRENC
Adder
1.308
315800Z1-036_GEN1
Solar/Wind Harmer
4.001
971795AH1-408 GEN
Solar/Wind Harmer
12.102
3130156CHOWAN
Solar/Wind Harmer
-0.016
960081AF2-299 GEN
Solar/Wind Harmer
1.79
316023GEN1_S
Solar/Wind Harmer
1.06
3145663CRESWEL
Solar/Wind Harmer
-0.044
971163AH1-040 GEN
Solar/Wind Harmer
14.733
3145783HORNRTN
Solar/Wind Harmer
-0.016
316190AA2-174 GEN
Solar/Wind Harmer
0.191
3145543BTLEBRO
Solar/Wind Harmer
-0.015
3145543BTLEBRO
Solar/Wind Harmer
-0.012
316359AB2-059 GEN
Solar/Wind Harmer
2.091
316049AB1-081 GEN
Solar/Wind Harmer
1.673
3142053HEARTS
Solar/Wind Harmer
0.182
316011AB1-132 GEN
Solar/Wind Harmer
3.244
962571AG1-106 GEN
Solar/Wind Harmer
2.229
3145796HORNRTN
Solar/Wind Harmer
-0.051
3145796HORNRTN
Solar/Wind Harmer
-0.015
315722AD1-056 GEN
Solar/Wind Harmer
1.622
3146233WITAKRS
Solar/Wind Harmer
-0.061
961671AG1-007 GEN
Solar/Wind Harmer
0.194
3146083TARBORO
Solar/Wind Harmer
-0.015
3145493TOT1
Solar/Wind Harmer
0.456
316212AC1-099_GEN
Solar/Wind Harmer
1.34
3145963POPLR C
Solar/Wind Harmer
-0.015
316174AB2-169 GEN
Solar/Wind Harmer
2.357
316494AC1-189 GEN
Solar/Wind Harmer
1.643
3146293MARTNCO
Solar/Wind Harmer
0.094
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146206CASHIE
Solar/Wind Harmer
-0.015
971547AH1-271 GEN
Solar/Wind Harmer
3.788
970685AG2-442 GEN
Solar/Wind Harmer
13.246
3146263WOODLND
Solar/Wind Harmer
-0.015
3145823KELFORD
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.015
963171AG1-166 GEN
Solar/Wind Harmer
1.825
971563AH1-280 GEN
Solar/Wind Harmer
1.825
3144293JTRSVLE
Adder
0.414
3145893MURPHYS
Solar/Wind Harmer
-0.058
3145893MURPHYS
Solar/Wind Harmer
0.431
316159AE1-175 C
Solar/Wind Helper
0.509
3141766HARMONY
Solar/Wind Helper
0.049
3138133OCRAN
Solar/Wind Helper
0.148
964211AG1-282 GEN
Solar/Wind Helper
0.305
3141726DUNNSVL
Solar/Wind Helper
0.905
CPLELTFEXP_CPLE->PJM
CLTF
10.589
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.328
LAGNLTFEXP_LAGN->PJM
CLTF
7.136
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.765
TVALTFEXP_TVA->PJM
CLTF
3.554
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.129
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.134
MECLTFEXP_MEC->PJM
CLTF
3.403
SIGELTFEXP_SIGE->PJM
CLTF
0.101
NYPJM->LTFIMP_NY
CLTF
1.354
LGEELTFEXP_LGEE->PJM
CLTF
1.211
WECLTFEXP_WEC->PJM
CLTF
0.63

Details for 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8SEPTA-8SURRY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.05 %
Rating:2931.0 MVA
Rating Type:C
MVA to Mitigate:2961.86
MW Contribution:18.09
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
3.245
970413AG2-270 GEN
50/50
18.093
3151101ELIZAR3
50/50
18.321
315773AC2-141 GEN
Solar/Wind Harmer
27.318
970917AG2-570 GEN
Solar/Wind Harmer
65.93
944581AF1-123 GEN
Solar/Wind Harmer
107.997
944601AF1-125 GEN
Solar/Wind Harmer
106.312
316478AD1-087 GEN
Solar/Wind Harmer
1.883
316486AD2-202 GEN
Solar/Wind Harmer
0.551
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.424
316320Y1-086
Solar/Wind Harmer
1.072
3144536CHRHLND
Solar/Wind Harmer
-0.003
316365GEN2_N
Solar/Wind Harmer
1.198
966621AG1-532 GEN
Solar/Wind Harmer
0.354
3147043LAWRENC
Solar/Wind Harmer
-0.01
313506AB2-031 GEN
Solar/Wind Harmer
1.365
316248AF1-058 C
Solar/Wind Harmer
0.511
960061AF2-297 GEN
Solar/Wind Harmer
8.482
316131AB2-060 GEN
Solar/Wind Harmer
1.822
3145796HORNRTN
Solar/Wind Harmer
-0.066
3145796HORNRTN
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
964241AG1-285 GEN
Solar/Wind Harmer
12.904
3146516WINFALL
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.016
315724AD1-057 GEN
Solar/Wind Harmer
0.933
3146376EDENTON
Solar/Wind Harmer
-0.016
970909AG2-566 GEN
Solar/Wind Harmer
1.517
316327AA2-057 GEN
Solar/Wind Harmer
1.611
3146233WITAKRS
Solar/Wind Harmer
0.333
3146233WITAKRS
Solar/Wind Harmer
-0.011
3138543CONSLDL
Solar/Wind Harmer
-0.01
315785AD2-033 C
Solar/Wind Harmer
3.605
961601AG1-000A GEN
Solar/Wind Harmer
6.324
316210AC1-098 GEN
Solar/Wind Harmer
2.492
3145543BTLEBRO
Solar/Wind Harmer
-0.016
3145543BTLEBRO
Solar/Wind Harmer
-0.016
315614AA2-178 GEN
Solar/Wind Harmer
1.706
316435W1029_GEN3
Solar/Wind Harmer
2.865
3146073TAR RVR
Solar/Wind Harmer
-0.016
3146083TARBORO
Solar/Wind Harmer
-0.016
315244AE2-183_ST
50/50
7.165
963041AG1-153 GEN
50/50
6.572
3151541CLOVER2
50/50
4.126
3151081ELIZAR1
50/50
18.089
941031AE2-094 GEN
Solar/Wind Harmer
54.965
944011AF1-069 GEN
Solar/Wind Harmer
17.222
970673AG2-436 GEN
Solar/Wind Harmer
60.015
970673AG2-436 GEN
Solar/Wind Harmer
30.387
971967AH1-528 GEN
Solar/Wind Harmer
52.234
970085AG2-068 GEN
Solar/Wind Harmer
16.391
970581AG2-369 GEN
Solar/Wind Harmer
14.096
3151091ELIZAR2
Adder
16.751
3152611GOSPORTB
Adder
2.303
3152621GOSPORTC
Adder
1.954
3152601GOSPORTA
Adder
1.803
957871AF2-081 GEN
Solar/Wind Harmer
10.089
319010AE1-072 C
Solar/Wind Harmer
3.997
3146406KITTY HAWK
Solar/Wind Harmer
0.016
316315AB2-025 C
Solar/Wind Harmer
0.53
315814AE2-033 C
Solar/Wind Harmer
18.209
313526AB2-022
Solar/Wind Harmer
0.493
316321Z2-027
Solar/Wind Harmer
0.475
3146396TANGLEW
Solar/Wind Harmer
0.324
3145176PASQUOTANK
Solar/Wind Harmer
-0.011
946281AF1-292 GEN
Solar/Wind Harmer
0.39
970831AG2-522 GEN
Solar/Wind Harmer
8.629
316087AB2-174 GEN
Solar/Wind Harmer
2.442
316239AB2-077_GEN
Solar/Wind Harmer
0.513
316238AB2-078_GEN
Solar/Wind Harmer
0.513
316118AC1-105 GEN
Solar/Wind Harmer
1.167
3147173SINAI
Solar/Wind Harmer
-0.017
3147243WELCO
Solar/Wind Harmer
-0.011
3137643SOCKMAN
Solar/Wind Harmer
-0.066
315652AC1-086 GEN
Solar/Wind Harmer
18.802
3145796HORNRTN
Solar/Wind Harmer
-0.053
3145796HORNRTN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
3.991
3130156CHOWAN
Solar/Wind Harmer
-0.016
3130156CHOWAN
Solar/Wind Harmer
-0.016
316319Z2-044 C
Solar/Wind Harmer
0.879
315607AA1-063A GEN
Solar/Wind Harmer
1.601
315816AE2-034 GEN
Solar/Wind Harmer
1.28
3146043SEABORD
Solar/Wind Harmer
-0.016
970533AG2-339 GEN
50/50
23.192
970531AG2-338 GEN
50/50
9.277
315242AE2-183_GT2
50/50
4.144
315241AE2-183_GT1
50/50
4.119
972185AH1-677 GEN
50/50
14.94
3151041BRUNSWICKG3
50/50
3.245
972187AH1-678 GEN
50/50
7.448
970933AG2-581 GEN
Solar/Wind Harmer
24.816
970099AG2-077 GEN
Solar/Wind Harmer
28.974
316185AD1-033 GEN
Solar/Wind Harmer
2.226
3145506HICKORY
Solar/Wind Harmer
-0.083
3145506HICKORY
Solar/Wind Harmer
-0.05
3145506HICKORY
Solar/Wind Harmer
-0.012
3142956BIRDNECK
Solar/Wind Harmer
1.104
316316AC1-027 C
Solar/Wind Harmer
0.63
316036AC1-147 C
Solar/Wind Harmer
0.55
3150991CHESPKB
Adder
1.902
3150991CHESPKB
Adder
1.857
316339AD2-160 GEN
Solar/Wind Harmer
1.371
316018AA1-139 ULT2
Solar/Wind Harmer
1.729
316017AA1-139 ULT1
Solar/Wind Harmer
1.633
3137176SLIGO L2192
Solar/Wind Harmer
-0.079
3146456SLIGO L269
Solar/Wind Harmer
2.349
3130086AYDLETT
Solar/Wind Harmer
-0.078
3144356SAPONY
Solar/Wind Harmer
0.685
3146386ELIZ CT
Solar/Wind Harmer
-0.018
939181AE1-148 GEN
Solar/Wind Harmer
9.927
971741AH1-377 GEN
Solar/Wind Harmer
20.052
316181AB2-040 GEN
Solar/Wind Harmer
2.37
313527AB2-043 GEN
Solar/Wind Harmer
2.758
962561AG1-105 GEN
Solar/Wind Harmer
9.546
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
964791AG1-342 GEN
Solar/Wind Harmer
3.625
3145796HORNRTN
Solar/Wind Harmer
-0.049
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
-0.016
966811AG1-552 GEN
Solar/Wind Harmer
1.856
3145593CAROLNA
Solar/Wind Harmer
0.137
3145783HORNRTN
Solar/Wind Harmer
1.949
3145783HORNRTN
Solar/Wind Harmer
1.559
3145783HORNRTN
Solar/Wind Harmer
0.487
3145783HORNRTN
Solar/Wind Harmer
0.195
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
316426AA2-053 GEN
Solar/Wind Harmer
1.645
3146626S HERTFORD
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.016
316274AC1-208 GEN
Solar/Wind Harmer
1.732
3146376EDENTON
Solar/Wind Harmer
0.476
3146376EDENTON
Solar/Wind Harmer
0.476
970301AG2-198 GEN
Solar/Wind Harmer
7.988
961601AG1-000A GEN
Solar/Wind Harmer
6.245
316263AC1-034 GEN
Solar/Wind Harmer
7.445
316431W1029_GEN1
Solar/Wind Harmer
2.865
316433W1029_GEN2
Solar/Wind Harmer
2.865
3145493TOT1
Solar/Wind Harmer
0.243
3145453TOT5
Solar/Wind Harmer
0.146
3145603CNETO
Solar/Wind Harmer
0.097
970323AG2-213 GEN
Solar/Wind Harmer
7.839
971443AH1-215 GEN
Solar/Wind Harmer
3.096
3146033SCOT NK
Solar/Wind Harmer
-0.063
3145573BETHELC
Solar/Wind Harmer
-0.016
3145573BETHELC
Solar/Wind Harmer
-0.016
3144303KENBRDG
Solar/Wind Harmer
-0.013
316420AA1-050 GEN
Solar/Wind Harmer
1.787
3130546PLYMOUTH
Solar/Wind Harmer
-0.016
315732AD1-074 GEN1
Solar/Wind Harmer
3.159
315733AD1-074 GEN2
Solar/Wind Harmer
3.159
315735AD1-075 GEN1
Solar/Wind Harmer
1.58
957861AF2-080 GEN
Solar/Wind Harmer
6.812
3146206CASHIE
Solar/Wind Harmer
-0.015
970601AG2-382 GEN
Solar/Wind Harmer
6.746
316005AA1-067
Solar/Wind Harmer
0.312
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
2.022
3145683EARLEYS
Solar/Wind Harmer
-0.03
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145513AHOSKIE
Solar/Wind Harmer
0.133
961941AG1-037 GEN
Solar/Wind Harmer
0.115
3145513AHOSKIE
Solar/Wind Harmer
-0.015
970683AG2-441 GEN
Solar/Wind Harmer
11.796
970681AG2-440 GEN
Solar/Wind Harmer
9.436
316318V4-068
Solar/Wind Harmer
0.374
3145893MURPHYS
Solar/Wind Harmer
-0.04
3145893MURPHYS
Solar/Wind Harmer
-0.015
965291AG1-394 GEN
Solar/Wind Harmer
1.319
946301AF1-294 GEN
Solar/Wind Harmer
3.729
961791AG1-021 GEN
Solar/Wind Harmer
1.819
3146486SUNBURY
Solar/Wind Harmer
-0.014
3146486SUNBURY
Solar/Wind Harmer
-0.014
970865AG2-541 GEN
Solar/Wind Harmer
5.823
315657AE1-056 GEN
Solar/Wind Harmer
5.314
3143316POE
Solar/Wind Harmer
-0.054
270455AD2-022 GEN
Solar/Wind Harmer
2.354
270457AD2-023 GEN
Solar/Wind Harmer
1.194
957831AF2-077 GEN
Solar/Wind Helper
0.384
970257AG2-171 GEN
Solar/Wind Harmer
5.879
971157AH1-035 GEN
Solar/Wind Harmer
1.956
3146263WOODLND
Solar/Wind Harmer
-0.016
315737AD1-076 GEN
Solar/Wind Harmer
2.968
316283AC2-100 C
Solar/Wind Harmer
1.463
3145963POPLR C
Solar/Wind Harmer
-0.015
316317KELFORD C
Solar/Wind Harmer
0.731
3145823KELFORD
Solar/Wind Harmer
-0.015
959311AF2-222 GEN
Solar/Wind Harmer
16.19
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.929
3146206CASHIE
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
316463AE2-346 GEN
Solar/Wind Harmer
0.247
316140AB2-099
Solar/Wind Harmer
0.103
962331AG1-082 GEN
Solar/Wind Harmer
1.905
971683AH1-343 GEN
Solar/Wind Harmer
6.55
3146173TUNIS
Solar/Wind Harmer
-0.015
3156021HOLLOMANSOL
Solar/Wind Harmer
2.039
957521AF2-046 GEN
Solar/Wind Harmer
11.856
961681AG1-008 GEN
Solar/Wind Harmer
11.856
3145893MURPHYS
Solar/Wind Harmer
0.105
3145893MURPHYS
Solar/Wind Harmer
-0.015
3156081AA2-088 GEN
Solar/Wind Harmer
4.785
963181AG1-167 GEN
Solar/Wind Harmer
1.364
3144293JTRSVLE
Adder
0.412
3147133PAMPLIN
Solar/Wind Harmer
-0.044
971193AH1-056 GEN
Solar/Wind Harmer
8.857
942461AE2-259 GEN
Solar/Wind Harmer
1.967
3145273HOLLAND
Solar/Wind Harmer
-0.01
316382AG1-145 C
Solar/Wind Helper
0.445
316156AD2-030 GEN
Solar/Wind Helper
0.367
316280AD1-041 GEN
Solar/Wind Helper
0.788
316484AD2-074 GEN
Solar/Wind Helper
0.442
316404AE1-155 C
Solar/Wind Helper
1.895
957601AF2-054 GEN
Solar/Wind Helper
0.326
3141873WAN 176
Solar/Wind Helper
0.049
3141913WHIT STONE
Solar/Wind Helper
0.239
3138133OCRAN
Solar/Wind Helper
0.072
316059AD1-063 C
Solar/Wind Helper
0.24
3141783LANCAST
Solar/Wind Helper
0.142
3141783LANCAST
Solar/Wind Helper
0.094
315662AE1-191 GEN
Solar/Wind Helper
1.261
315666AE1-190 GEN
Solar/Wind Helper
0.315
971775AH1-396 GEN
Solar/Wind Harmer
1.116
316034AC1-036 C
Solar/Wind Harmer
0.291
316222AC1-221 GEN
Solar/Wind Harmer
1.581
316065AD1-022 GEN
Solar/Wind Harmer
7.746
3145933PARMELE
Solar/Wind Harmer
-0.031
3145933PARMELE
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.015
3145893MURPHYS
Solar/Wind Harmer
0.419
3145893MURPHYS
Solar/Wind Harmer
-0.027
958211AF2-115 GEN
Solar/Wind Harmer
2.274
963191AG1-168 GEN
Solar/Wind Harmer
1.364
3144293JTRSVLE
Adder
0.412
3144293JTRSVLE
Adder
0.347
3147133PAMPLIN
Solar/Wind Harmer
-0.014
3147133PAMPLIN
Solar/Wind Harmer
-0.011
315742AE1-103 GEN
Solar/Wind Harmer
1.397
316487AF1-042 GEN
Solar/Wind Helper
0.231
315243AE2-183_GT3
50/50
4.144
3151051BRUNSWICKS1
50/50
6.736
3151021BRUNSWICKG1
50/50
3.245
971451AH1-221 GEN
50/50
9.857
3151531CLOVER1
50/50
4.146
316294AC1-161 GEN
Solar/Wind Harmer
21.122
940641AE2-051 GEN
Solar/Wind Harmer
34.85
970919AG2-571 GEN
Solar/Wind Harmer
8.346
970087AG2-069 GEN
Solar/Wind Harmer
24.586
944591AF1-124 GEN
Solar/Wind Harmer
108.386
957481AF2-042 GEN
Solar/Wind Harmer
72.436
939411AE1-173 GEN
Solar/Wind Harmer
114.333
315693AD1-088 GEN
Solar/Wind Harmer
10.761
962491AG1-098 GEN
Solar/Wind Harmer
14.201
316375AC2-012 GEN
Solar/Wind Harmer
7.061
3150981CHESPKA
Adder
2.267
316388AE2-253 GEN
Solar/Wind Harmer
1.371
315687AD1-152 GEN
Solar/Wind Harmer
2.422
3146456SLIGO L269
Solar/Wind Harmer
-0.02
316023GEN1_S
Solar/Wind Harmer
1.198
960081AF2-299 GEN
Solar/Wind Harmer
1.961
971065AG2-659 GEN
Solar/Wind Harmer
8.708
316129AC1-054 GEN
Solar/Wind Harmer
1.52
971795AH1-408 GEN
Solar/Wind Harmer
13
3147043LAWRENC
Adder
1.392
316237AB2-079_GEN
Solar/Wind Harmer
0.513
970401AG2-262 GEN
Solar/Wind Harmer
1.108
316011AB1-132 GEN
Solar/Wind Harmer
3.497
962571AG1-106 GEN
Solar/Wind Harmer
2.402
3145796HORNRTN
Solar/Wind Harmer
-0.054
3145796HORNRTN
Solar/Wind Harmer
-0.017
3145783HORNRTN
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.053
3146516WINFALL
Solar/Wind Harmer
-0.016
316190AA2-174 GEN
Solar/Wind Harmer
0.2
315722AD1-056 GEN
Solar/Wind Harmer
1.696
315800Z1-036_GEN1
Solar/Wind Harmer
3.991
3130156CHOWAN
Solar/Wind Harmer
-0.016
316003AC1-222 GEN
Solar/Wind Harmer
1.563
3146233WITAKRS
Solar/Wind Harmer
-0.063
316359AB2-059 GEN
Solar/Wind Harmer
2.141
316049AB1-081 GEN
Solar/Wind Harmer
1.714
3142053HEARTS
Solar/Wind Harmer
0.187
316212AC1-099_GEN
Solar/Wind Harmer
1.384
3145543BTLEBRO
Solar/Wind Harmer
-0.016
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145663CRESWEL
Solar/Wind Harmer
-0.044
971163AH1-040 GEN
Solar/Wind Harmer
14.826
961671AG1-007 GEN
Solar/Wind Harmer
0.199
3146083TARBORO
Solar/Wind Harmer
-0.016
3145493TOT1
Solar/Wind Harmer
0.466
3146263WOODLND
Solar/Wind Harmer
-0.016
316494AC1-189 GEN
Solar/Wind Harmer
1.675
3145963POPLR C
Solar/Wind Harmer
-0.015
3145823KELFORD
Solar/Wind Harmer
-0.015
316174AB2-169 GEN
Solar/Wind Harmer
2.391
3146293MARTNCO
Solar/Wind Harmer
0.096
3146206CASHIE
Solar/Wind Harmer
-0.015
971547AH1-271 GEN
Solar/Wind Harmer
3.855
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.015
970685AG2-442 GEN
Solar/Wind Harmer
13.211
3145893MURPHYS
Solar/Wind Harmer
-0.06
3145893MURPHYS
Solar/Wind Harmer
0.445
963171AG1-166 GEN
Solar/Wind Harmer
1.819
971563AH1-280 GEN
Solar/Wind Harmer
1.819
3144293JTRSVLE
Adder
0.412
316159AE1-175 C
Solar/Wind Helper
0.502
3138133OCRAN
Solar/Wind Helper
0.143
3141766HARMONY
Solar/Wind Helper
0.048
CPLELTFEXP_CPLE->PJM
CLTF
10.401
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.559
LAGNLTFEXP_LAGN->PJM
CLTF
6.991
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.32
TVALTFEXP_TVA->PJM
CLTF
3.482
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.641
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.888
MECLTFEXP_MEC->PJM
CLTF
3.331
SIGELTFEXP_SIGE->PJM
CLTF
0.099
NYPJM->LTFIMP_NY
CLTF
1.344
LGEELTFEXP_LGEE->PJM
CLTF
1.186
WECLTFEXP_WEC->PJM
CLTF
0.616

Details for 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SEPTA-8SURRY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.05 %
Rating:2931.0 MVA
Rating Type:C
MVA to Mitigate:2961.86
MW Contribution:18.09
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
7.165
963041AG1-153 GEN
50/50
6.572
3151541CLOVER2
50/50
4.126
3151081ELIZAR1
50/50
18.089
941031AE2-094 GEN
Solar/Wind Harmer
54.965
944011AF1-069 GEN
Solar/Wind Harmer
17.222
970673AG2-436 GEN
Solar/Wind Harmer
60.015
970673AG2-436 GEN
Solar/Wind Harmer
30.387
971967AH1-528 GEN
Solar/Wind Harmer
52.234
970085AG2-068 GEN
Solar/Wind Harmer
16.391
970581AG2-369 GEN
Solar/Wind Harmer
14.096
3151091ELIZAR2
Adder
16.751
3152611GOSPORTB
Adder
2.303
3152621GOSPORTC
Adder
1.954
3152601GOSPORTA
Adder
1.803
957871AF2-081 GEN
Solar/Wind Harmer
10.089
319010AE1-072 C
Solar/Wind Harmer
3.997
3146406KITTY HAWK
Solar/Wind Harmer
0.016
316315AB2-025 C
Solar/Wind Harmer
0.53
315814AE2-033 C
Solar/Wind Harmer
18.209
313526AB2-022
Solar/Wind Harmer
0.493
316321Z2-027
Solar/Wind Harmer
0.475
3146396TANGLEW
Solar/Wind Harmer
0.324
3145176PASQUOTANK
Solar/Wind Harmer
-0.011
946281AF1-292 GEN
Solar/Wind Harmer
0.39
970831AG2-522 GEN
Solar/Wind Harmer
8.629
316087AB2-174 GEN
Solar/Wind Harmer
2.442
316239AB2-077_GEN
Solar/Wind Harmer
0.513
316238AB2-078_GEN
Solar/Wind Harmer
0.513
316118AC1-105 GEN
Solar/Wind Harmer
1.167
3147173SINAI
Solar/Wind Harmer
-0.017
3147243WELCO
Solar/Wind Harmer
-0.011
3137643SOCKMAN
Solar/Wind Harmer
-0.066
315652AC1-086 GEN
Solar/Wind Harmer
18.802
3145796HORNRTN
Solar/Wind Harmer
-0.053
3145796HORNRTN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
3.991
3130156CHOWAN
Solar/Wind Harmer
-0.016
3130156CHOWAN
Solar/Wind Harmer
-0.016
316319Z2-044 C
Solar/Wind Harmer
0.879
315607AA1-063A GEN
Solar/Wind Harmer
1.601
315816AE2-034 GEN
Solar/Wind Harmer
1.28
3146043SEABORD
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.096
3146033SCOT NK
Solar/Wind Harmer
-0.063
3145573BETHELC
Solar/Wind Harmer
-0.016
3145573BETHELC
Solar/Wind Harmer
-0.016
3144303KENBRDG
Solar/Wind Harmer
-0.013
316420AA1-050 GEN
Solar/Wind Harmer
1.787
3130546PLYMOUTH
Solar/Wind Harmer
-0.016
315732AD1-074 GEN1
Solar/Wind Harmer
3.159
315733AD1-074 GEN2
Solar/Wind Harmer
3.159
315735AD1-075 GEN1
Solar/Wind Harmer
1.58
957861AF2-080 GEN
Solar/Wind Harmer
6.812
3146206CASHIE
Solar/Wind Harmer
-0.015
970601AG2-382 GEN
Solar/Wind Harmer
6.746
316005AA1-067
Solar/Wind Harmer
0.312
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
2.022
3145683EARLEYS
Solar/Wind Harmer
-0.03
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145513AHOSKIE
Solar/Wind Harmer
0.133
961941AG1-037 GEN
Solar/Wind Harmer
0.115
3145513AHOSKIE
Solar/Wind Harmer
-0.015
970683AG2-441 GEN
Solar/Wind Harmer
11.796
970681AG2-440 GEN
Solar/Wind Harmer
9.436
316318V4-068
Solar/Wind Harmer
0.374
3145893MURPHYS
Solar/Wind Harmer
-0.04
3145893MURPHYS
Solar/Wind Harmer
-0.015
965291AG1-394 GEN
Solar/Wind Harmer
1.319
946301AF1-294 GEN
Solar/Wind Harmer
3.729
961791AG1-021 GEN
Solar/Wind Harmer
1.819
3146486SUNBURY
Solar/Wind Harmer
-0.014
3146486SUNBURY
Solar/Wind Harmer
-0.014
970865AG2-541 GEN
Solar/Wind Harmer
5.823
315657AE1-056 GEN
Solar/Wind Harmer
5.314
3143316POE
Solar/Wind Harmer
-0.054
270455AD2-022 GEN
Solar/Wind Harmer
2.354
270457AD2-023 GEN
Solar/Wind Harmer
1.194
957831AF2-077 GEN
Solar/Wind Helper
0.384
957601AF2-054 GEN
Solar/Wind Helper
0.326
3141873WAN 176
Solar/Wind Helper
0.049
3141913WHIT STONE
Solar/Wind Helper
0.239
3138133OCRAN
Solar/Wind Helper
0.072
316059AD1-063 C
Solar/Wind Helper
0.24
3141783LANCAST
Solar/Wind Helper
0.142
3141783LANCAST
Solar/Wind Helper
0.094
315662AE1-191 GEN
Solar/Wind Helper
1.261
315666AE1-190 GEN
Solar/Wind Helper
0.315
3151031BRUNSWICKG2
50/50
3.245
970413AG2-270 GEN
50/50
18.093
3151101ELIZAR3
50/50
18.321
315773AC2-141 GEN
Solar/Wind Harmer
27.318
970917AG2-570 GEN
Solar/Wind Harmer
65.93
944581AF1-123 GEN
Solar/Wind Harmer
107.997
944601AF1-125 GEN
Solar/Wind Harmer
106.312
316478AD1-087 GEN
Solar/Wind Harmer
1.883
316486AD2-202 GEN
Solar/Wind Harmer
0.551
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.424
316320Y1-086
Solar/Wind Harmer
1.072
3144536CHRHLND
Solar/Wind Harmer
-0.003
316365GEN2_N
Solar/Wind Harmer
1.198
966621AG1-532 GEN
Solar/Wind Harmer
0.354
3147043LAWRENC
Solar/Wind Harmer
-0.01
313506AB2-031 GEN
Solar/Wind Harmer
1.365
316248AF1-058 C
Solar/Wind Harmer
0.511
960061AF2-297 GEN
Solar/Wind Harmer
8.482
316131AB2-060 GEN
Solar/Wind Harmer
1.822
3145796HORNRTN
Solar/Wind Harmer
-0.066
3145796HORNRTN
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
964241AG1-285 GEN
Solar/Wind Harmer
12.904
3146516WINFALL
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.016
315724AD1-057 GEN
Solar/Wind Harmer
0.933
3146376EDENTON
Solar/Wind Harmer
-0.016
970909AG2-566 GEN
Solar/Wind Harmer
1.517
316327AA2-057 GEN
Solar/Wind Harmer
1.611
3146233WITAKRS
Solar/Wind Harmer
0.333
3146233WITAKRS
Solar/Wind Harmer
-0.011
3138543CONSLDL
Solar/Wind Harmer
-0.01
315785AD2-033 C
Solar/Wind Harmer
3.605
961601AG1-000A GEN
Solar/Wind Harmer
6.324
316210AC1-098 GEN
Solar/Wind Harmer
2.492
3145543BTLEBRO
Solar/Wind Harmer
-0.016
3145543BTLEBRO
Solar/Wind Harmer
-0.016
315614AA2-178 GEN
Solar/Wind Harmer
1.706
316435W1029_GEN3
Solar/Wind Harmer
2.865
3146073TAR RVR
Solar/Wind Harmer
-0.016
3146083TARBORO
Solar/Wind Harmer
-0.016
970257AG2-171 GEN
Solar/Wind Harmer
5.879
971157AH1-035 GEN
Solar/Wind Harmer
1.956
3146263WOODLND
Solar/Wind Harmer
-0.016
315737AD1-076 GEN
Solar/Wind Harmer
2.968
316283AC2-100 C
Solar/Wind Harmer
1.463
3145963POPLR C
Solar/Wind Harmer
-0.015
316317KELFORD C
Solar/Wind Harmer
0.731
3145823KELFORD
Solar/Wind Harmer
-0.015
959311AF2-222 GEN
Solar/Wind Harmer
16.19
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.929
3146206CASHIE
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
316463AE2-346 GEN
Solar/Wind Harmer
0.247
316140AB2-099
Solar/Wind Harmer
0.103
962331AG1-082 GEN
Solar/Wind Harmer
1.905
971683AH1-343 GEN
Solar/Wind Harmer
6.55
3146173TUNIS
Solar/Wind Harmer
-0.015
3156021HOLLOMANSOL
Solar/Wind Harmer
2.039
957521AF2-046 GEN
Solar/Wind Harmer
11.856
961681AG1-008 GEN
Solar/Wind Harmer
11.856
3145893MURPHYS
Solar/Wind Harmer
0.105
3145893MURPHYS
Solar/Wind Harmer
-0.015
3156081AA2-088 GEN
Solar/Wind Harmer
4.785
963181AG1-167 GEN
Solar/Wind Harmer
1.364
3144293JTRSVLE
Adder
0.412
3147133PAMPLIN
Solar/Wind Harmer
-0.044
971193AH1-056 GEN
Solar/Wind Harmer
8.857
942461AE2-259 GEN
Solar/Wind Harmer
1.967
3145273HOLLAND
Solar/Wind Harmer
-0.01
316382AG1-145 C
Solar/Wind Helper
0.445
316156AD2-030 GEN
Solar/Wind Helper
0.367
316280AD1-041 GEN
Solar/Wind Helper
0.788
316484AD2-074 GEN
Solar/Wind Helper
0.442
316404AE1-155 C
Solar/Wind Helper
1.895
970533AG2-339 GEN
50/50
23.192
970531AG2-338 GEN
50/50
9.277
315242AE2-183_GT2
50/50
4.144
315241AE2-183_GT1
50/50
4.119
972185AH1-677 GEN
50/50
14.94
3151041BRUNSWICKG3
50/50
3.245
972187AH1-678 GEN
50/50
7.448
970933AG2-581 GEN
Solar/Wind Harmer
24.816
970099AG2-077 GEN
Solar/Wind Harmer
28.974
316185AD1-033 GEN
Solar/Wind Harmer
2.226
3145506HICKORY
Solar/Wind Harmer
-0.083
3145506HICKORY
Solar/Wind Harmer
-0.05
3145506HICKORY
Solar/Wind Harmer
-0.012
3142956BIRDNECK
Solar/Wind Harmer
1.104
316316AC1-027 C
Solar/Wind Harmer
0.63
316036AC1-147 C
Solar/Wind Harmer
0.55
3150991CHESPKB
Adder
1.902
3150991CHESPKB
Adder
1.857
316339AD2-160 GEN
Solar/Wind Harmer
1.371
316018AA1-139 ULT2
Solar/Wind Harmer
1.729
316017AA1-139 ULT1
Solar/Wind Harmer
1.633
3137176SLIGO L2192
Solar/Wind Harmer
-0.079
3146456SLIGO L269
Solar/Wind Harmer
2.349
3130086AYDLETT
Solar/Wind Harmer
-0.078
3144356SAPONY
Solar/Wind Harmer
0.685
3146386ELIZ CT
Solar/Wind Harmer
-0.018
939181AE1-148 GEN
Solar/Wind Harmer
9.927
971741AH1-377 GEN
Solar/Wind Harmer
20.052
316181AB2-040 GEN
Solar/Wind Harmer
2.37
313527AB2-043 GEN
Solar/Wind Harmer
2.758
962561AG1-105 GEN
Solar/Wind Harmer
9.546
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
964791AG1-342 GEN
Solar/Wind Harmer
3.625
3145796HORNRTN
Solar/Wind Harmer
-0.049
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
-0.016
966811AG1-552 GEN
Solar/Wind Harmer
1.856
3145593CAROLNA
Solar/Wind Harmer
0.137
3145783HORNRTN
Solar/Wind Harmer
1.949
3145783HORNRTN
Solar/Wind Harmer
1.559
3145783HORNRTN
Solar/Wind Harmer
0.487
3145783HORNRTN
Solar/Wind Harmer
0.195
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
316426AA2-053 GEN
Solar/Wind Harmer
1.645
3146626S HERTFORD
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.016
316274AC1-208 GEN
Solar/Wind Harmer
1.732
3146376EDENTON
Solar/Wind Harmer
0.476
3146376EDENTON
Solar/Wind Harmer
0.476
970301AG2-198 GEN
Solar/Wind Harmer
7.988
961601AG1-000A GEN
Solar/Wind Harmer
6.245
316263AC1-034 GEN
Solar/Wind Harmer
7.445
316431W1029_GEN1
Solar/Wind Harmer
2.865
316433W1029_GEN2
Solar/Wind Harmer
2.865
3145493TOT1
Solar/Wind Harmer
0.243
3145453TOT5
Solar/Wind Harmer
0.146
3145603CNETO
Solar/Wind Harmer
0.097
970323AG2-213 GEN
Solar/Wind Harmer
7.839
971775AH1-396 GEN
Solar/Wind Harmer
1.116
316034AC1-036 C
Solar/Wind Harmer
0.291
316222AC1-221 GEN
Solar/Wind Harmer
1.581
316065AD1-022 GEN
Solar/Wind Harmer
7.746
3145933PARMELE
Solar/Wind Harmer
-0.031
3145933PARMELE
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.015
3145893MURPHYS
Solar/Wind Harmer
0.419
3145893MURPHYS
Solar/Wind Harmer
-0.027
958211AF2-115 GEN
Solar/Wind Harmer
2.274
963191AG1-168 GEN
Solar/Wind Harmer
1.364
3144293JTRSVLE
Adder
0.412
3144293JTRSVLE
Adder
0.347
3147133PAMPLIN
Solar/Wind Harmer
-0.014
3147133PAMPLIN
Solar/Wind Harmer
-0.011
315742AE1-103 GEN
Solar/Wind Harmer
1.397
316487AF1-042 GEN
Solar/Wind Helper
0.231
315243AE2-183_GT3
50/50
4.144
3151051BRUNSWICKS1
50/50
6.736
3151021BRUNSWICKG1
50/50
3.245
971451AH1-221 GEN
50/50
9.857
3151531CLOVER1
50/50
4.146
316294AC1-161 GEN
Solar/Wind Harmer
21.122
940641AE2-051 GEN
Solar/Wind Harmer
34.85
970919AG2-571 GEN
Solar/Wind Harmer
8.346
970087AG2-069 GEN
Solar/Wind Harmer
24.586
944591AF1-124 GEN
Solar/Wind Harmer
108.386
957481AF2-042 GEN
Solar/Wind Harmer
72.436
939411AE1-173 GEN
Solar/Wind Harmer
114.333
315693AD1-088 GEN
Solar/Wind Harmer
10.761
962491AG1-098 GEN
Solar/Wind Harmer
14.201
316375AC2-012 GEN
Solar/Wind Harmer
7.061
3150981CHESPKA
Adder
2.267
316388AE2-253 GEN
Solar/Wind Harmer
1.371
315687AD1-152 GEN
Solar/Wind Harmer
2.422
3146456SLIGO L269
Solar/Wind Harmer
-0.02
316023GEN1_S
Solar/Wind Harmer
1.198
960081AF2-299 GEN
Solar/Wind Harmer
1.961
971065AG2-659 GEN
Solar/Wind Harmer
8.708
316129AC1-054 GEN
Solar/Wind Harmer
1.52
971795AH1-408 GEN
Solar/Wind Harmer
13
3147043LAWRENC
Adder
1.392
316237AB2-079_GEN
Solar/Wind Harmer
0.513
970401AG2-262 GEN
Solar/Wind Harmer
1.108
316011AB1-132 GEN
Solar/Wind Harmer
3.497
962571AG1-106 GEN
Solar/Wind Harmer
2.402
3145796HORNRTN
Solar/Wind Harmer
-0.054
3145796HORNRTN
Solar/Wind Harmer
-0.017
3145783HORNRTN
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.053
3146516WINFALL
Solar/Wind Harmer
-0.016
316190AA2-174 GEN
Solar/Wind Harmer
0.2
315722AD1-056 GEN
Solar/Wind Harmer
1.696
315800Z1-036_GEN1
Solar/Wind Harmer
3.991
3130156CHOWAN
Solar/Wind Harmer
-0.016
316003AC1-222 GEN
Solar/Wind Harmer
1.563
3146233WITAKRS
Solar/Wind Harmer
-0.063
316359AB2-059 GEN
Solar/Wind Harmer
2.141
316049AB1-081 GEN
Solar/Wind Harmer
1.714
3142053HEARTS
Solar/Wind Harmer
0.187
316212AC1-099_GEN
Solar/Wind Harmer
1.384
3145543BTLEBRO
Solar/Wind Harmer
-0.016
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145663CRESWEL
Solar/Wind Harmer
-0.044
971163AH1-040 GEN
Solar/Wind Harmer
14.826
961671AG1-007 GEN
Solar/Wind Harmer
0.199
3146083TARBORO
Solar/Wind Harmer
-0.016
3145493TOT1
Solar/Wind Harmer
0.466
3146263WOODLND
Solar/Wind Harmer
-0.016
316494AC1-189 GEN
Solar/Wind Harmer
1.675
3145963POPLR C
Solar/Wind Harmer
-0.015
3145823KELFORD
Solar/Wind Harmer
-0.015
316174AB2-169 GEN
Solar/Wind Harmer
2.391
3146293MARTNCO
Solar/Wind Harmer
0.096
3146206CASHIE
Solar/Wind Harmer
-0.015
971547AH1-271 GEN
Solar/Wind Harmer
3.855
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.015
970685AG2-442 GEN
Solar/Wind Harmer
13.211
3145893MURPHYS
Solar/Wind Harmer
-0.06
3145893MURPHYS
Solar/Wind Harmer
0.445
963171AG1-166 GEN
Solar/Wind Harmer
1.819
971563AH1-280 GEN
Solar/Wind Harmer
1.819
3144293JTRSVLE
Adder
0.412
316159AE1-175 C
Solar/Wind Helper
0.502
3138133OCRAN
Solar/Wind Helper
0.143
3141766HARMONY
Solar/Wind Helper
0.048
CPLELTFEXP_CPLE->PJM
CLTF
10.401
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.559
LAGNLTFEXP_LAGN->PJM
CLTF
6.991
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.32
TVALTFEXP_TVA->PJM
CLTF
3.482
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.641
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.888
MECLTFEXP_MEC->PJM
CLTF
3.331
SIGELTFEXP_SIGE->PJM
CLTF
0.099
NYPJM->LTFIMP_NY
CLTF
1.344
LGEELTFEXP_LGEE->PJM
CLTF
1.186
WECLTFEXP_WEC->PJM
CLTF
0.616

Details for AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.0 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1248.61
MW Contribution:47.17
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
10.81
3144293JTRSVLE
50/50
1.009
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3147043LAWRENC
50/50
1.435
3151561HALLBR1
50/50
0.347
3151931BEARGRDN S1
50/50
1.382
3151911BEARGRDN G1
50/50
1.071
315687AD1-152 GEN
Solar/Wind Harmer
7.754
316003AC1-222 GEN
Solar/Wind Harmer
5.366
957481AF2-042 GEN
Solar/Wind Harmer
169.755
315693AD1-088 GEN
Solar/Wind Harmer
25.249
962491AG1-098 GEN
Solar/Wind Harmer
33.372
970401AG2-262 GEN
Solar/Wind Harmer
3.252
316237AB2-079_GEN
Solar/Wind Harmer
1.108
970685AG2-442 GEN
Solar/Wind Harmer
29.934
963171AG1-166 GEN
Solar/Wind Harmer
4.197
971563AH1-280 GEN
Solar/Wind Harmer
4.197
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.353
316322AB2-045
Solar/Wind Harmer
0.758
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.877
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.335
971795AH1-408 GEN
Solar/Wind Harmer
10.57
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.525
971377AH1-170 GEN
Solar/Wind Harmer
1.453
3147623JAMES R
Solar/Wind Harmer
0.18
970937AG2-583 GEN
Solar/Wind Harmer
7.555
960081AF2-299 GEN
Solar/Wind Harmer
0.925
316336AC2-165 C
Solar/Wind Harmer
1.327
3143336POWHATN
Solar/Wind Harmer
0.773
3152661PLYWOOD A
50/50
1.086
3144293JTRSVLE
50/50
1.009
3144293JTRSVLE
50/50
0.85
970535AG2-341 GEN
50/50
5.15
316222AC1-221 GEN
Solar/Wind Harmer
10.229
970099AG2-077 GEN
Solar/Wind Harmer
67.902
970933AG2-581 GEN
Solar/Wind Harmer
50.214
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.644
962561AG1-105 GEN
Solar/Wind Harmer
26.877
971741AH1-377 GEN
Solar/Wind Harmer
48.375
970301AG2-198 GEN
Solar/Wind Harmer
19.484
3151541CLOVER2
50/50
10.758
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
972205AH1-687 GEN
50/50
5.223
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.765
971967AH1-528 GEN
Solar/Wind Harmer
100.698
970865AG2-541 GEN
Solar/Wind Harmer
19.076
316123AC1-075 GEN
Solar/Wind Harmer
4.171
970165AG2-112 GEN
Solar/Wind Harmer
3.672
970163AG2-111 GEN
Solar/Wind Harmer
3.503
316239AB2-077_GEN
Solar/Wind Harmer
1.108
316238AB2-078_GEN
Solar/Wind Harmer
1.108
971443AH1-215 GEN
Solar/Wind Harmer
6.88
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.727
970681AG2-440 GEN
Solar/Wind Harmer
21.381
946301AF1-294 GEN
Solar/Wind Harmer
8.604
961791AG1-021 GEN
Solar/Wind Harmer
4.197
315657AE1-056 GEN
Solar/Wind Harmer
12.423
970285AG2-188 GEN
Solar/Wind Harmer
21.434
971845AH1-439 GEN
Solar/Wind Harmer
12.337
970831AG2-522 GEN
Solar/Wind Harmer
10.013
971447AH1-217 GEN
Solar/Wind Harmer
3.92
270494AE1-108_GEN
Solar/Wind Harmer
2.506
946281AF1-292 GEN
Solar/Wind Harmer
0.184
316087AB2-174 GEN
Solar/Wind Harmer
1.115
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.376
270457AD2-023 GEN
Solar/Wind Helper
0.907
970413AG2-270 GEN
50/50
47.174
3144293JTRSVLE
50/50
1.009
3151591KERR 2
50/50
0.537
3151921BEARGRDN G2
50/50
1.071
316248AF1-058 C
Solar/Wind Harmer
1.793
960061AF2-297 GEN
Solar/Wind Harmer
29.749
316478AD1-087 GEN
Solar/Wind Harmer
4.929
316486AD2-202 GEN
Solar/Wind Harmer
1.444
971683AH1-343 GEN
Solar/Wind Harmer
22.008
970909AG2-566 GEN
Solar/Wind Harmer
3.699
316131AB2-060 GEN
Solar/Wind Harmer
3.917
964241AG1-285 GEN
Solar/Wind Harmer
28.021
315785AD2-033 C
Solar/Wind Harmer
7.969
970257AG2-171 GEN
Solar/Wind Harmer
13.085
959311AF2-222 GEN
Solar/Wind Harmer
36.211
963181AG1-167 GEN
Solar/Wind Harmer
3.148
3147133PAMPLIN
Solar/Wind Harmer
-0.104
971193AH1-056 GEN
Solar/Wind Harmer
20.705
942461AE2-259 GEN
Solar/Wind Harmer
4.788
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.525
970221AG2-151 GEN
Solar/Wind Harmer
7.265
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.614
316313AB2-026
Solar/Wind Harmer
0.176
316258AE1-075 C
Solar/Wind Harmer
0.158
316405AF2-144 C
Solar/Wind Harmer
0.167
3143336POWHATN
Solar/Wind Harmer
0.657
316283AC2-100 C
Solar/Wind Helper
2.324
313527AB2-043 GEN
Solar/Wind Harmer
5.914
970323AG2-213 GEN
Solar/Wind Harmer
17.447
971775AH1-396 GEN
Solar/Wind Harmer
2.485
316034AC1-036 C
Solar/Wind Harmer
0.647
958211AF2-115 GEN
Solar/Wind Harmer
5.246
963191AG1-168 GEN
Solar/Wind Harmer
3.148
942751AE2-291 GEN
Solar/Wind Harmer
21.29
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.128
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.959
316197AC1-042 GEN
Solar/Wind Harmer
1.485
942671AE2-283 GEN
Solar/Wind Harmer
3.997
971489AH1-241 GEN
Solar/Wind Harmer
6.897
315821AE2-092 GEN
Solar/Wind Harmer
1.796
316181AB2-040 GEN
Solar/Wind Harmer
1.066
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.786
3145593CAROLNA
Solar/Wind Harmer
0.058
G-007ALTFEXP_G-007A->PJM
CMTX
0.429
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.343
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.85
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.677
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.127
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.809
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.962
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.375

Details for AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.45 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1220.46
MW Contribution:47.09
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.738
3151611KERR 4
50/50
0.535
3151621KERR 5
50/50
0.535
3151631KERR 6
50/50
0.535
3151641KERR 7
50/50
0.535
972205AH1-687 GEN
50/50
5.237
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.757
971967AH1-528 GEN
Solar/Wind Harmer
100.512
970865AG2-541 GEN
Solar/Wind Harmer
19.031
316123AC1-075 GEN
Solar/Wind Harmer
4.16
970165AG2-112 GEN
Solar/Wind Harmer
3.663
970163AG2-111 GEN
Solar/Wind Harmer
3.494
316239AB2-077_GEN
Solar/Wind Harmer
1.105
316238AB2-078_GEN
Solar/Wind Harmer
1.105
971443AH1-215 GEN
Solar/Wind Harmer
6.867
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.682
970681AG2-440 GEN
Solar/Wind Harmer
21.345
946301AF1-294 GEN
Solar/Wind Harmer
8.59
961791AG1-021 GEN
Solar/Wind Harmer
4.19
315657AE1-056 GEN
Solar/Wind Harmer
12.405
970285AG2-188 GEN
Solar/Wind Harmer
21.428
971845AH1-439 GEN
Solar/Wind Harmer
12.335
970831AG2-522 GEN
Solar/Wind Harmer
9.984
971447AH1-217 GEN
Solar/Wind Harmer
3.931
270494AE1-108_GEN
Solar/Wind Harmer
2.509
946281AF1-292 GEN
Solar/Wind Harmer
0.185
316087AB2-174 GEN
Solar/Wind Harmer
1.116
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.395
270457AD2-023 GEN
Solar/Wind Helper
0.919
3152661PLYWOOD A
50/50
1.084
3144293JTRSVLE
50/50
1.008
3144293JTRSVLE
50/50
0.849
970535AG2-341 GEN
50/50
5.137
316222AC1-221 GEN
Solar/Wind Harmer
10.209
970099AG2-077 GEN
Solar/Wind Harmer
67.776
970933AG2-581 GEN
Solar/Wind Harmer
50.121
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.622
962561AG1-105 GEN
Solar/Wind Harmer
26.822
971741AH1-377 GEN
Solar/Wind Harmer
48.301
970301AG2-198 GEN
Solar/Wind Harmer
19.456
313527AB2-043 GEN
Solar/Wind Harmer
5.902
970323AG2-213 GEN
Solar/Wind Harmer
17.415
971775AH1-396 GEN
Solar/Wind Harmer
2.48
316034AC1-036 C
Solar/Wind Harmer
0.646
958211AF2-115 GEN
Solar/Wind Harmer
5.238
963191AG1-168 GEN
Solar/Wind Harmer
3.143
942751AE2-291 GEN
Solar/Wind Harmer
21.229
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.08
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.947
316197AC1-042 GEN
Solar/Wind Harmer
1.476
942671AE2-283 GEN
Solar/Wind Harmer
3.973
971489AH1-241 GEN
Solar/Wind Harmer
6.915
315821AE2-092 GEN
Solar/Wind Harmer
1.803
316181AB2-040 GEN
Solar/Wind Harmer
1.066
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.785
3145593CAROLNA
Solar/Wind Harmer
0.058
970413AG2-270 GEN
50/50
47.085
3144293JTRSVLE
50/50
1.008
3151591KERR 2
50/50
0.535
3151921BEARGRDN G2
50/50
1.074
316248AF1-058 C
Solar/Wind Harmer
1.789
960061AF2-297 GEN
Solar/Wind Harmer
29.687
316478AD1-087 GEN
Solar/Wind Harmer
4.92
316486AD2-202 GEN
Solar/Wind Harmer
1.441
971683AH1-343 GEN
Solar/Wind Harmer
21.959
970909AG2-566 GEN
Solar/Wind Harmer
3.694
316131AB2-060 GEN
Solar/Wind Harmer
3.909
964241AG1-285 GEN
Solar/Wind Harmer
27.966
315785AD2-033 C
Solar/Wind Harmer
7.954
970257AG2-171 GEN
Solar/Wind Harmer
13.061
959311AF2-222 GEN
Solar/Wind Harmer
36.146
963181AG1-167 GEN
Solar/Wind Harmer
3.143
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.674
942461AE2-259 GEN
Solar/Wind Harmer
4.782
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.498
970221AG2-151 GEN
Solar/Wind Harmer
7.284
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.615
316313AB2-026
Solar/Wind Harmer
0.178
316258AE1-075 C
Solar/Wind Harmer
0.16
316405AF2-144 C
Solar/Wind Harmer
0.169
3143336POWHATN
Solar/Wind Harmer
0.666
316283AC2-100 C
Solar/Wind Helper
2.343
270018AE2-047 C O1
Solar/Wind Helper
0.4
3151531CLOVER1
50/50
10.79
3144293JTRSVLE
50/50
1.008
3151601KERR 3
50/50
0.535
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.434
3151561HALLBR1
50/50
0.346
3151931BEARGRDN S1
50/50
1.386
3151911BEARGRDN G1
50/50
1.074
315687AD1-152 GEN
Solar/Wind Harmer
7.739
316003AC1-222 GEN
Solar/Wind Harmer
5.355
957481AF2-042 GEN
Solar/Wind Harmer
169.439
315693AD1-088 GEN
Solar/Wind Harmer
25.203
962491AG1-098 GEN
Solar/Wind Harmer
33.312
970401AG2-262 GEN
Solar/Wind Harmer
3.246
316237AB2-079_GEN
Solar/Wind Harmer
1.105
970685AG2-442 GEN
Solar/Wind Harmer
29.883
963171AG1-166 GEN
Solar/Wind Harmer
4.19
971563AH1-280 GEN
Solar/Wind Harmer
4.19
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.32
316322AB2-045
Solar/Wind Harmer
0.758
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.872
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.349
971795AH1-408 GEN
Solar/Wind Harmer
10.568
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.498
971377AH1-170 GEN
Solar/Wind Harmer
1.457
3147623JAMES R
Solar/Wind Harmer
0.18
970937AG2-583 GEN
Solar/Wind Harmer
7.594
960081AF2-299 GEN
Solar/Wind Harmer
0.927
316336AC2-165 C
Solar/Wind Harmer
1.341
3143336POWHATN
Solar/Wind Harmer
0.784
G-007ALTFEXP_G-007A->PJM
CMTX
0.522
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.505
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.869
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.738
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.375
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.857
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.08
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.476

Details for AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.42 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1220.19
MW Contribution:47.09
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.738
3151611KERR 4
50/50
0.535
3151621KERR 5
50/50
0.535
3151631KERR 6
50/50
0.535
3151641KERR 7
50/50
0.535
972205AH1-687 GEN
50/50
5.237
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.757
971967AH1-528 GEN
Solar/Wind Harmer
100.512
970865AG2-541 GEN
Solar/Wind Harmer
19.031
316123AC1-075 GEN
Solar/Wind Harmer
4.16
970165AG2-112 GEN
Solar/Wind Harmer
3.663
970163AG2-111 GEN
Solar/Wind Harmer
3.494
316239AB2-077_GEN
Solar/Wind Harmer
1.105
316238AB2-078_GEN
Solar/Wind Harmer
1.105
971443AH1-215 GEN
Solar/Wind Harmer
6.867
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.682
970681AG2-440 GEN
Solar/Wind Harmer
21.345
946301AF1-294 GEN
Solar/Wind Harmer
8.59
961791AG1-021 GEN
Solar/Wind Harmer
4.19
315657AE1-056 GEN
Solar/Wind Harmer
12.405
970285AG2-188 GEN
Solar/Wind Harmer
21.428
971845AH1-439 GEN
Solar/Wind Harmer
12.335
970831AG2-522 GEN
Solar/Wind Harmer
9.984
971447AH1-217 GEN
Solar/Wind Harmer
3.931
270494AE1-108_GEN
Solar/Wind Harmer
2.509
946281AF1-292 GEN
Solar/Wind Harmer
0.185
316087AB2-174 GEN
Solar/Wind Harmer
1.116
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.395
270457AD2-023 GEN
Solar/Wind Helper
0.919
3152661PLYWOOD A
50/50
1.084
3144293JTRSVLE
50/50
1.008
3144293JTRSVLE
50/50
0.849
970535AG2-341 GEN
50/50
5.137
316222AC1-221 GEN
Solar/Wind Harmer
10.209
970099AG2-077 GEN
Solar/Wind Harmer
67.776
970933AG2-581 GEN
Solar/Wind Harmer
50.121
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.622
962561AG1-105 GEN
Solar/Wind Harmer
26.822
971741AH1-377 GEN
Solar/Wind Harmer
48.301
970413AG2-270 GEN
50/50
47.085
3144293JTRSVLE
50/50
1.008
3151591KERR 2
50/50
0.535
3151921BEARGRDN G2
50/50
1.074
316248AF1-058 C
Solar/Wind Harmer
1.789
960061AF2-297 GEN
Solar/Wind Harmer
29.687
316478AD1-087 GEN
Solar/Wind Harmer
4.92
316486AD2-202 GEN
Solar/Wind Harmer
1.441
971683AH1-343 GEN
Solar/Wind Harmer
21.959
970909AG2-566 GEN
Solar/Wind Harmer
3.694
316131AB2-060 GEN
Solar/Wind Harmer
3.909
964241AG1-285 GEN
Solar/Wind Harmer
27.966
315785AD2-033 C
Solar/Wind Harmer
7.954
970257AG2-171 GEN
Solar/Wind Harmer
13.061
959311AF2-222 GEN
Solar/Wind Harmer
36.146
963181AG1-167 GEN
Solar/Wind Harmer
3.143
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.674
942461AE2-259 GEN
Solar/Wind Harmer
4.782
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.498
970221AG2-151 GEN
Solar/Wind Harmer
7.284
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.615
316313AB2-026
Solar/Wind Harmer
0.178
316258AE1-075 C
Solar/Wind Harmer
0.16
316405AF2-144 C
Solar/Wind Harmer
0.169
3143336POWHATN
Solar/Wind Harmer
0.666
316283AC2-100 C
Solar/Wind Helper
2.343
270018AE2-047 C O1
Solar/Wind Helper
0.4
970301AG2-198 GEN
Solar/Wind Harmer
19.456
313527AB2-043 GEN
Solar/Wind Harmer
5.902
970323AG2-213 GEN
Solar/Wind Harmer
17.415
971775AH1-396 GEN
Solar/Wind Harmer
2.48
316034AC1-036 C
Solar/Wind Harmer
0.646
958211AF2-115 GEN
Solar/Wind Harmer
5.238
963191AG1-168 GEN
Solar/Wind Harmer
3.143
942751AE2-291 GEN
Solar/Wind Harmer
21.229
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.08
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.947
316197AC1-042 GEN
Solar/Wind Harmer
1.476
942671AE2-283 GEN
Solar/Wind Harmer
3.973
971489AH1-241 GEN
Solar/Wind Harmer
6.915
315821AE2-092 GEN
Solar/Wind Harmer
1.803
316181AB2-040 GEN
Solar/Wind Harmer
1.066
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.785
3145593CAROLNA
Solar/Wind Harmer
0.058
3151531CLOVER1
50/50
10.79
3144293JTRSVLE
50/50
1.008
3151601KERR 3
50/50
0.535
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.434
3151561HALLBR1
50/50
0.346
3151931BEARGRDN S1
50/50
1.386
3151911BEARGRDN G1
50/50
1.074
315687AD1-152 GEN
Solar/Wind Harmer
7.739
316003AC1-222 GEN
Solar/Wind Harmer
5.355
957481AF2-042 GEN
Solar/Wind Harmer
169.439
315693AD1-088 GEN
Solar/Wind Harmer
25.203
962491AG1-098 GEN
Solar/Wind Harmer
33.312
970401AG2-262 GEN
Solar/Wind Harmer
3.246
316237AB2-079_GEN
Solar/Wind Harmer
1.105
970685AG2-442 GEN
Solar/Wind Harmer
29.883
963171AG1-166 GEN
Solar/Wind Harmer
4.19
971563AH1-280 GEN
Solar/Wind Harmer
4.19
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.32
316322AB2-045
Solar/Wind Harmer
0.758
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.872
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.349
971795AH1-408 GEN
Solar/Wind Harmer
10.568
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.498
971377AH1-170 GEN
Solar/Wind Harmer
1.457
3147623JAMES R
Solar/Wind Harmer
0.18
970937AG2-583 GEN
Solar/Wind Harmer
7.594
960081AF2-299 GEN
Solar/Wind Harmer
0.927
316336AC2-165 C
Solar/Wind Harmer
1.341
3143336POWHATN
Solar/Wind Harmer
0.784
G-007ALTFEXP_G-007A->PJM
CMTX
0.522
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.505
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.869
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.738
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.375
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.857
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.08
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.476

Details for AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.84 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1202.69
MW Contribution:47.62
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
10.912
3144293JTRSVLE
50/50
1.003
3151601KERR 3
50/50
0.535
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.433
3151561HALLBR1
50/50
0.349
3151931BEARGRDN S1
50/50
1.364
3151911BEARGRDN G1
50/50
1.057
315687AD1-152 GEN
Solar/Wind Harmer
7.805
957481AF2-042 GEN
Solar/Wind Harmer
172.899
316003AC1-222 GEN
Solar/Wind Harmer
5.386
970401AG2-262 GEN
Solar/Wind Harmer
3.259
315693AD1-088 GEN
Solar/Wind Harmer
24.873
962491AG1-098 GEN
Solar/Wind Harmer
32.876
316237AB2-079_GEN
Solar/Wind Harmer
1.106
970685AG2-442 GEN
Solar/Wind Harmer
29.769
963171AG1-166 GEN
Solar/Wind Harmer
4.169
971563AH1-280 GEN
Solar/Wind Harmer
4.169
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.328
316322AB2-045
Solar/Wind Harmer
0.749
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.873
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.24
971795AH1-408 GEN
Solar/Wind Harmer
10.551
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.548
971377AH1-170 GEN
Solar/Wind Harmer
1.434
3147623JAMES R
Solar/Wind Harmer
0.178
970937AG2-583 GEN
Solar/Wind Harmer
7.455
960081AF2-299 GEN
Solar/Wind Harmer
0.924
316336AC2-165 C
Solar/Wind Harmer
1.309
3143336POWHATN
Solar/Wind Harmer
0.763
3151541CLOVER2
50/50
10.86
3151611KERR 4
50/50
0.535
3151621KERR 5
50/50
0.535
3151631KERR 6
50/50
0.535
3151641KERR 7
50/50
0.535
972205AH1-687 GEN
50/50
5.155
3147173SINAI
Solar/Wind Harmer
-0.06
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.776
970865AG2-541 GEN
Solar/Wind Harmer
19.147
316123AC1-075 GEN
Solar/Wind Harmer
4.187
970165AG2-112 GEN
Solar/Wind Harmer
3.686
970163AG2-111 GEN
Solar/Wind Harmer
3.517
316239AB2-077_GEN
Solar/Wind Harmer
1.106
316238AB2-078_GEN
Solar/Wind Harmer
1.106
971443AH1-215 GEN
Solar/Wind Harmer
6.851
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.58
970681AG2-440 GEN
Solar/Wind Harmer
21.264
946301AF1-294 GEN
Solar/Wind Harmer
8.547
961791AG1-021 GEN
Solar/Wind Harmer
4.169
315657AE1-056 GEN
Solar/Wind Harmer
12.33
970285AG2-188 GEN
Solar/Wind Harmer
21.156
971845AH1-439 GEN
Solar/Wind Harmer
12.177
970831AG2-522 GEN
Solar/Wind Harmer
9.991
971447AH1-217 GEN
Solar/Wind Harmer
3.869
270494AE1-108_GEN
Solar/Wind Harmer
2.477
946281AF1-292 GEN
Solar/Wind Harmer
0.184
316087AB2-174 GEN
Solar/Wind Harmer
1.113
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.367
270457AD2-023 GEN
Solar/Wind Helper
0.901
970413AG2-270 GEN
50/50
47.618
3144293JTRSVLE
50/50
1.003
3151591KERR 2
50/50
0.535
3151921BEARGRDN G2
50/50
1.057
316248AF1-058 C
Solar/Wind Harmer
1.799
960061AF2-297 GEN
Solar/Wind Harmer
29.857
316478AD1-087 GEN
Solar/Wind Harmer
4.976
316486AD2-202 GEN
Solar/Wind Harmer
1.457
971683AH1-343 GEN
Solar/Wind Harmer
22.089
970909AG2-566 GEN
Solar/Wind Harmer
3.648
316131AB2-060 GEN
Solar/Wind Harmer
3.91
964241AG1-285 GEN
Solar/Wind Harmer
27.945
315785AD2-033 C
Solar/Wind Harmer
7.938
970257AG2-171 GEN
Solar/Wind Harmer
13.028
959311AF2-222 GEN
Solar/Wind Harmer
36.042
963181AG1-167 GEN
Solar/Wind Harmer
3.127
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.55
942461AE2-259 GEN
Solar/Wind Harmer
4.741
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.548
970221AG2-151 GEN
Solar/Wind Harmer
7.172
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.613
316313AB2-026
Solar/Wind Harmer
0.173
316258AE1-075 C
Solar/Wind Harmer
0.156
316405AF2-144 C
Solar/Wind Harmer
0.165
3143336POWHATN
Solar/Wind Harmer
0.648
316283AC2-100 C
Solar/Wind Helper
2.31
3152661PLYWOOD A
50/50
1.089
3144293JTRSVLE
50/50
1.003
3144293JTRSVLE
50/50
0.844
970535AG2-341 GEN
50/50
5.14
316222AC1-221 GEN
Solar/Wind Harmer
10.244
970099AG2-077 GEN
Solar/Wind Harmer
69.159
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.665
962561AG1-105 GEN
Solar/Wind Harmer
26.917
971741AH1-377 GEN
Solar/Wind Harmer
47.685
970301AG2-198 GEN
Solar/Wind Harmer
19.211
313527AB2-043 GEN
Solar/Wind Harmer
5.903
970323AG2-213 GEN
Solar/Wind Harmer
17.371
971775AH1-396 GEN
Solar/Wind Harmer
2.474
316034AC1-036 C
Solar/Wind Harmer
0.644
942751AE2-291 GEN
Solar/Wind Harmer
21.373
958211AF2-115 GEN
Solar/Wind Harmer
5.211
963191AG1-168 GEN
Solar/Wind Harmer
3.127
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.09
3146776BUCKING
Solar/Wind Harmer
-0.089
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.968
316197AC1-042 GEN
Solar/Wind Harmer
1.492
942671AE2-283 GEN
Solar/Wind Harmer
4.017
971489AH1-241 GEN
Solar/Wind Harmer
6.809
315821AE2-092 GEN
Solar/Wind Harmer
1.772
316181AB2-040 GEN
Solar/Wind Harmer
1.064
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.785
3145593CAROLNA
Solar/Wind Harmer
0.058
G-007ALTFEXP_G-007A->PJM
CMTX
0.408
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.306
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.845
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.662
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.071
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.798
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.933
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.353

Details for AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.84 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1202.63
MW Contribution:47.62
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
47.615
3144293JTRSVLE
50/50
1.003
3151591KERR 2
50/50
0.535
3151921BEARGRDN G2
50/50
1.057
316248AF1-058 C
Solar/Wind Harmer
1.799
960061AF2-297 GEN
Solar/Wind Harmer
29.856
316478AD1-087 GEN
Solar/Wind Harmer
4.975
316486AD2-202 GEN
Solar/Wind Harmer
1.457
971683AH1-343 GEN
Solar/Wind Harmer
22.089
970909AG2-566 GEN
Solar/Wind Harmer
3.648
316131AB2-060 GEN
Solar/Wind Harmer
3.91
964241AG1-285 GEN
Solar/Wind Harmer
27.945
315785AD2-033 C
Solar/Wind Harmer
7.938
970257AG2-171 GEN
Solar/Wind Harmer
13.029
3152661PLYWOOD A
50/50
1.089
3144293JTRSVLE
50/50
1.003
3144293JTRSVLE
50/50
0.844
970535AG2-341 GEN
50/50
5.14
316222AC1-221 GEN
Solar/Wind Harmer
10.244
970099AG2-077 GEN
Solar/Wind Harmer
69.15
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.664
962561AG1-105 GEN
Solar/Wind Harmer
26.917
971741AH1-377 GEN
Solar/Wind Harmer
47.691
970301AG2-198 GEN
Solar/Wind Harmer
19.213
313527AB2-043 GEN
Solar/Wind Harmer
5.903
970323AG2-213 GEN
Solar/Wind Harmer
17.372
971775AH1-396 GEN
Solar/Wind Harmer
2.474
316034AC1-036 C
Solar/Wind Harmer
0.644
942751AE2-291 GEN
Solar/Wind Harmer
21.372
958211AF2-115 GEN
Solar/Wind Harmer
5.212
963191AG1-168 GEN
Solar/Wind Harmer
3.127
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.09
3146776BUCKING
Solar/Wind Harmer
-0.089
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.968
316197AC1-042 GEN
Solar/Wind Harmer
1.492
942671AE2-283 GEN
Solar/Wind Harmer
4.017
971489AH1-241 GEN
Solar/Wind Harmer
6.81
315821AE2-092 GEN
Solar/Wind Harmer
1.772
316181AB2-040 GEN
Solar/Wind Harmer
1.064
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.785
3145593CAROLNA
Solar/Wind Harmer
0.058
959311AF2-222 GEN
Solar/Wind Harmer
36.043
963181AG1-167 GEN
Solar/Wind Harmer
3.127
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.551
942461AE2-259 GEN
Solar/Wind Harmer
4.741
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.548
970221AG2-151 GEN
Solar/Wind Harmer
7.173
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.613
316313AB2-026
Solar/Wind Harmer
0.173
316258AE1-075 C
Solar/Wind Harmer
0.156
316405AF2-144 C
Solar/Wind Harmer
0.165
3143336POWHATN
Solar/Wind Harmer
0.648
316283AC2-100 C
Solar/Wind Helper
2.31
3151541CLOVER2
50/50
10.859
3151611KERR 4
50/50
0.535
3151621KERR 5
50/50
0.535
3151631KERR 6
50/50
0.535
3151641KERR 7
50/50
0.535
972205AH1-687 GEN
50/50
5.156
3147173SINAI
Solar/Wind Harmer
-0.06
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.775
970865AG2-541 GEN
Solar/Wind Harmer
19.147
316123AC1-075 GEN
Solar/Wind Harmer
4.187
970165AG2-112 GEN
Solar/Wind Harmer
3.686
970163AG2-111 GEN
Solar/Wind Harmer
3.517
316239AB2-077_GEN
Solar/Wind Harmer
1.106
316238AB2-078_GEN
Solar/Wind Harmer
1.106
971443AH1-215 GEN
Solar/Wind Harmer
6.851
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.581
970681AG2-440 GEN
Solar/Wind Harmer
21.265
946301AF1-294 GEN
Solar/Wind Harmer
8.547
961791AG1-021 GEN
Solar/Wind Harmer
4.169
315657AE1-056 GEN
Solar/Wind Harmer
12.331
970285AG2-188 GEN
Solar/Wind Harmer
21.159
971845AH1-439 GEN
Solar/Wind Harmer
12.178
970831AG2-522 GEN
Solar/Wind Harmer
9.991
971447AH1-217 GEN
Solar/Wind Harmer
3.87
270494AE1-108_GEN
Solar/Wind Harmer
2.477
946281AF1-292 GEN
Solar/Wind Harmer
0.184
316087AB2-174 GEN
Solar/Wind Harmer
1.113
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.367
270457AD2-023 GEN
Solar/Wind Helper
0.901
3151531CLOVER1
50/50
10.911
3144293JTRSVLE
50/50
1.003
3151601KERR 3
50/50
0.535
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.433
3151561HALLBR1
50/50
0.349
3151931BEARGRDN S1
50/50
1.364
3151911BEARGRDN G1
50/50
1.057
315687AD1-152 GEN
Solar/Wind Harmer
7.805
957481AF2-042 GEN
Solar/Wind Harmer
172.875
316003AC1-222 GEN
Solar/Wind Harmer
5.386
970401AG2-262 GEN
Solar/Wind Harmer
3.259
315693AD1-088 GEN
Solar/Wind Harmer
24.876
962491AG1-098 GEN
Solar/Wind Harmer
32.88
316237AB2-079_GEN
Solar/Wind Harmer
1.106
970685AG2-442 GEN
Solar/Wind Harmer
29.77
963171AG1-166 GEN
Solar/Wind Harmer
4.169
971563AH1-280 GEN
Solar/Wind Harmer
4.169
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.328
316322AB2-045
Solar/Wind Harmer
0.749
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.873
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.24
971795AH1-408 GEN
Solar/Wind Harmer
10.551
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.548
971377AH1-170 GEN
Solar/Wind Harmer
1.435
3147623JAMES R
Solar/Wind Harmer
0.178
970937AG2-583 GEN
Solar/Wind Harmer
7.456
960081AF2-299 GEN
Solar/Wind Harmer
0.924
316336AC2-165 C
Solar/Wind Harmer
1.309
3143336POWHATN
Solar/Wind Harmer
0.763
G-007ALTFEXP_G-007A->PJM
CMTX
0.409
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.307
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.845
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.662
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.071
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.798
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.933
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.353

Details for AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.96 %
Rating:903.34 MVA
Rating Type:B
MVA to Mitigate:939.11
MW Contribution:47.17
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
10.758
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
972205AH1-687 GEN
50/50
5.223
3151281ROARAP4
50/50
0.075
3151281ROARAP4
50/50
0.07
3147173SINAI
Solar/Wind Harmer
0.529
3147243WELCO
Solar/Wind Harmer
0.331
316118AC1-105 GEN
Solar/Wind Harmer
1.258
971967AH1-528 GEN
Solar/Wind Harmer
76.276
970865AG2-541 GEN
Solar/Wind Harmer
14.488
316123AC1-075 GEN
Solar/Wind Harmer
0.47
970165AG2-112 GEN
Solar/Wind Harmer
2.789
970163AG2-111 GEN
Solar/Wind Harmer
2.661
316239AB2-077_GEN
Solar/Wind Harmer
0.003
316238AB2-078_GEN
Solar/Wind Harmer
0.003
971443AH1-215 GEN
Solar/Wind Harmer
5.225
3144303KENBRDG
Solar/Wind Harmer
0.248
3151531CLOVER1
50/50
10.81
3144293JTRSVLE
50/50
1.009
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3147043LAWRENC
50/50
1.435
3151561HALLBR1
50/50
0.347
3151931BEARGRDN S1
50/50
1.382
3151911BEARGRDN G1
50/50
1.071
3151261ROARAP2
50/50
0.077
24728405LEESVG
50/50
0.073
315687AD1-152 GEN
Solar/Wind Harmer
0.019
316003AC1-222 GEN
Solar/Wind Harmer
0.013
957481AF2-042 GEN
Solar/Wind Harmer
128.928
315693AD1-088 GEN
Solar/Wind Harmer
21.573
962491AG1-098 GEN
Solar/Wind Harmer
25.346
970401AG2-262 GEN
Solar/Wind Harmer
2.602
316237AB2-079_GEN
Solar/Wind Harmer
0.003
970685AG2-442 GEN
Solar/Wind Harmer
22.735
963171AG1-166 GEN
Solar/Wind Harmer
1.594
971563AH1-280 GEN
Solar/Wind Harmer
3.188
3146926FARMVIL
Solar/Wind Harmer
0.163
971065AG2-659 GEN
Solar/Wind Harmer
8.623
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.08
316129AC1-054 GEN
Solar/Wind Harmer
0.717
3147123OTTER R
Solar/Wind Harmer
0.087
972003AH1-546 GEN
Solar/Wind Harmer
5.562
971795AH1-408 GEN
Solar/Wind Harmer
8.362
3147312GRETNA
Solar/Wind Harmer
0.086
3146802CHATHAM
Solar/Wind Harmer
0.08
941801AE2-185 GEN
Solar/Wind Harmer
3.437
971377AH1-170 GEN
Solar/Wind Harmer
1.104
3147623JAMES R
Solar/Wind Harmer
0.24
970937AG2-583 GEN
Solar/Wind Harmer
5.738
960081AF2-299 GEN
Solar/Wind Harmer
0.703
316336AC2-165 C
Solar/Wind Harmer
0.003
3152661PLYWOOD A
50/50
1.086
3144293JTRSVLE
50/50
1.009
3144293JTRSVLE
50/50
0.85
970535AG2-341 GEN
50/50
5.15
316222AC1-221 GEN
Solar/Wind Harmer
3.734
970099AG2-077 GEN
Solar/Wind Harmer
51.571
970933AG2-581 GEN
Solar/Wind Harmer
38.137
3146843MT LREL
Solar/Wind Harmer
0.444
3146843MT LREL
Solar/Wind Harmer
0.444
964791AG1-342 GEN
Solar/Wind Harmer
8.515
962561AG1-105 GEN
Solar/Wind Harmer
20.413
971741AH1-377 GEN
Solar/Wind Harmer
36.74
970301AG2-198 GEN
Solar/Wind Harmer
14.798
313527AB2-043 GEN
Solar/Wind Harmer
0.004
970323AG2-213 GEN
Solar/Wind Harmer
13.251
971775AH1-396 GEN
Solar/Wind Harmer
0.497
316034AC1-036 C
Solar/Wind Harmer
0.023
958211AF2-115 GEN
Solar/Wind Harmer
3.586
963191AG1-168 GEN
Solar/Wind Harmer
1.195
942751AE2-291 GEN
Solar/Wind Harmer
16.169
3147133PAMPLIN
Solar/Wind Harmer
0.295
3147133PAMPLIN
Solar/Wind Harmer
0.236
939181AE1-148 GEN
Solar/Wind Harmer
13.009
3146776BUCKING
Solar/Wind Harmer
0.802
3146776BUCKING
Solar/Wind Harmer
0.065
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
2.673
971489AH1-241 GEN
Solar/Wind Harmer
5.518
315821AE2-092 GEN
Solar/Wind Harmer
0.005
316181AB2-040 GEN
Solar/Wind Harmer
0.099
3145593CAROLNA
Solar/Wind Harmer
0.062
3145593CAROLNA
Solar/Wind Harmer
0.062
966811AG1-552 GEN
Solar/Wind Harmer
0.675
3145593CAROLNA
Solar/Wind Harmer
0.077
970413AG2-270 GEN
50/50
47.174
3144293JTRSVLE
50/50
1.009
3151591KERR 2
50/50
0.537
3151921BEARGRDN G2
50/50
1.071
3151261ROARAP2
50/50
0.076
24728405LEESVG
50/50
0.073
316248AF1-058 C
Solar/Wind Harmer
0.004
960061AF2-297 GEN
Solar/Wind Harmer
22.594
316478AD1-087 GEN
Solar/Wind Harmer
1.768
316486AD2-202 GEN
Solar/Wind Harmer
0.519
971683AH1-343 GEN
Solar/Wind Harmer
16.715
970909AG2-566 GEN
Solar/Wind Harmer
3.699
316131AB2-060 GEN
Solar/Wind Harmer
1.016
964241AG1-285 GEN
Solar/Wind Harmer
21.282
315785AD2-033 C
Solar/Wind Harmer
2.544
970257AG2-171 GEN
Solar/Wind Harmer
9.938
959311AF2-222 GEN
Solar/Wind Harmer
27.447
963181AG1-167 GEN
Solar/Wind Harmer
1.195
3147133PAMPLIN
Solar/Wind Harmer
0.925
971193AH1-056 GEN
Solar/Wind Harmer
17.953
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
3146926FARMVIL
Solar/Wind Harmer
0.163
3146776BUCKING
Solar/Wind Harmer
0.072
3147043LAWRENC
Solar/Wind Harmer
0.09
3147312GRETNA
Solar/Wind Harmer
0.021
941821AE2-187 GEN
Solar/Wind Harmer
3.437
970221AG2-151 GEN
Solar/Wind Harmer
5.518
313506AB2-031 GEN
Solar/Wind Harmer
0.21
316313AB2-026
Solar/Wind Harmer
0.037
316258AE1-075 C
Solar/Wind Harmer
0.044
316405AF2-144 C
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
0.876
316283AC2-100 C
Solar/Wind Helper
2.324
970683AG2-441 GEN
Solar/Wind Harmer
20.299
970681AG2-440 GEN
Solar/Wind Harmer
16.239
946301AF1-294 GEN
Solar/Wind Harmer
5.897
961791AG1-021 GEN
Solar/Wind Harmer
2.869
315657AE1-056 GEN
Solar/Wind Harmer
10.169
970285AG2-188 GEN
Solar/Wind Harmer
17.248
971845AH1-439 GEN
Solar/Wind Harmer
9.37
970831AG2-522 GEN
Solar/Wind Harmer
7.605
971447AH1-217 GEN
Solar/Wind Harmer
2.977
270494AE1-108_GEN
Solar/Wind Harmer
1.028
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.259
270455AD2-022 GEN
Solar/Wind Helper
1.376
270457AD2-023 GEN
Solar/Wind Helper
0.907
3143336POWHATN
Solar/Wind Harmer
1.031
G-007ALTFEXP_G-007A->PJM
CMTX
0.429
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.343
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.85
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.677
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.127
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.809
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.962
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.375

Details for AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.05 %
Rating:903.34 MVA
Rating Type:B
MVA to Mitigate:921.89
MW Contribution:47.17
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
1.086
3144293JTRSVLE
50/50
1.009
3144293JTRSVLE
50/50
0.85
970535AG2-341 GEN
50/50
5.15
316222AC1-221 GEN
Solar/Wind Harmer
3.734
970099AG2-077 GEN
Solar/Wind Harmer
51.571
3146843MT LREL
Solar/Wind Harmer
0.444
3146843MT LREL
Solar/Wind Harmer
0.444
964791AG1-342 GEN
Solar/Wind Harmer
8.515
962561AG1-105 GEN
Solar/Wind Harmer
20.413
971741AH1-377 GEN
Solar/Wind Harmer
36.74
970301AG2-198 GEN
Solar/Wind Harmer
14.798
313527AB2-043 GEN
Solar/Wind Harmer
0.004
970323AG2-213 GEN
Solar/Wind Harmer
13.251
971775AH1-396 GEN
Solar/Wind Harmer
0.497
316034AC1-036 C
Solar/Wind Harmer
0.023
958211AF2-115 GEN
Solar/Wind Harmer
3.586
963191AG1-168 GEN
Solar/Wind Harmer
1.195
942751AE2-291 GEN
Solar/Wind Harmer
16.169
3147133PAMPLIN
Solar/Wind Harmer
0.295
3147133PAMPLIN
Solar/Wind Harmer
0.236
939181AE1-148 GEN
Solar/Wind Harmer
13.009
3146776BUCKING
Solar/Wind Harmer
0.802
3146776BUCKING
Solar/Wind Harmer
0.065
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
2.673
971489AH1-241 GEN
Solar/Wind Harmer
5.518
315821AE2-092 GEN
Solar/Wind Harmer
0.005
316181AB2-040 GEN
Solar/Wind Harmer
0.099
3145593CAROLNA
Solar/Wind Harmer
0.062
3145593CAROLNA
Solar/Wind Harmer
0.062
966811AG1-552 GEN
Solar/Wind Harmer
0.675
3145593CAROLNA
Solar/Wind Harmer
0.077
3151541CLOVER2
50/50
10.758
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
972205AH1-687 GEN
50/50
5.223
3151281ROARAP4
50/50
0.075
3151281ROARAP4
50/50
0.07
3147173SINAI
Solar/Wind Harmer
0.529
3147243WELCO
Solar/Wind Harmer
0.331
316118AC1-105 GEN
Solar/Wind Harmer
1.258
970865AG2-541 GEN
Solar/Wind Harmer
14.488
316123AC1-075 GEN
Solar/Wind Harmer
0.47
970165AG2-112 GEN
Solar/Wind Harmer
2.789
970163AG2-111 GEN
Solar/Wind Harmer
2.661
316239AB2-077_GEN
Solar/Wind Harmer
0.003
316238AB2-078_GEN
Solar/Wind Harmer
0.003
971443AH1-215 GEN
Solar/Wind Harmer
5.225
3144303KENBRDG
Solar/Wind Harmer
0.248
970683AG2-441 GEN
Solar/Wind Harmer
20.299
970681AG2-440 GEN
Solar/Wind Harmer
16.239
946301AF1-294 GEN
Solar/Wind Harmer
5.897
961791AG1-021 GEN
Solar/Wind Harmer
2.869
315657AE1-056 GEN
Solar/Wind Harmer
10.169
970285AG2-188 GEN
Solar/Wind Harmer
17.248
971845AH1-439 GEN
Solar/Wind Harmer
9.37
970831AG2-522 GEN
Solar/Wind Harmer
7.605
971447AH1-217 GEN
Solar/Wind Harmer
2.977
270494AE1-108_GEN
Solar/Wind Harmer
1.028
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.259
270455AD2-022 GEN
Solar/Wind Helper
1.376
270457AD2-023 GEN
Solar/Wind Helper
0.907
3151531CLOVER1
50/50
10.81
3144293JTRSVLE
50/50
1.009
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3147043LAWRENC
50/50
1.435
3151561HALLBR1
50/50
0.347
3151931BEARGRDN S1
50/50
1.382
3151911BEARGRDN G1
50/50
1.071
3151261ROARAP2
50/50
0.077
24728405LEESVG
50/50
0.073
315687AD1-152 GEN
Solar/Wind Harmer
0.019
316003AC1-222 GEN
Solar/Wind Harmer
0.013
957481AF2-042 GEN
Solar/Wind Harmer
128.928
315693AD1-088 GEN
Solar/Wind Harmer
21.573
962491AG1-098 GEN
Solar/Wind Harmer
25.346
970401AG2-262 GEN
Solar/Wind Harmer
2.602
316237AB2-079_GEN
Solar/Wind Harmer
0.003
970685AG2-442 GEN
Solar/Wind Harmer
22.735
963171AG1-166 GEN
Solar/Wind Harmer
1.594
971563AH1-280 GEN
Solar/Wind Harmer
3.188
3146926FARMVIL
Solar/Wind Harmer
0.163
971065AG2-659 GEN
Solar/Wind Harmer
8.623
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.08
316129AC1-054 GEN
Solar/Wind Harmer
0.717
3147123OTTER R
Solar/Wind Harmer
0.087
972003AH1-546 GEN
Solar/Wind Harmer
5.562
971795AH1-408 GEN
Solar/Wind Harmer
8.362
3147312GRETNA
Solar/Wind Harmer
0.086
3146802CHATHAM
Solar/Wind Harmer
0.08
941801AE2-185 GEN
Solar/Wind Harmer
3.437
971377AH1-170 GEN
Solar/Wind Harmer
1.104
3147623JAMES R
Solar/Wind Harmer
0.24
970937AG2-583 GEN
Solar/Wind Harmer
5.738
960081AF2-299 GEN
Solar/Wind Harmer
0.703
316336AC2-165 C
Solar/Wind Harmer
0.003
3143336POWHATN
Solar/Wind Harmer
1.031
970413AG2-270 GEN
50/50
47.174
3144293JTRSVLE
50/50
1.009
3151591KERR 2
50/50
0.537
3151921BEARGRDN G2
50/50
1.071
3151261ROARAP2
50/50
0.076
24728405LEESVG
50/50
0.073
316248AF1-058 C
Solar/Wind Harmer
0.004
960061AF2-297 GEN
Solar/Wind Harmer
22.594
316478AD1-087 GEN
Solar/Wind Harmer
1.768
316486AD2-202 GEN
Solar/Wind Harmer
0.519
971683AH1-343 GEN
Solar/Wind Harmer
16.715
970909AG2-566 GEN
Solar/Wind Harmer
3.699
316131AB2-060 GEN
Solar/Wind Harmer
1.016
964241AG1-285 GEN
Solar/Wind Harmer
21.282
315785AD2-033 C
Solar/Wind Harmer
2.544
970257AG2-171 GEN
Solar/Wind Harmer
9.938
959311AF2-222 GEN
Solar/Wind Harmer
27.447
963181AG1-167 GEN
Solar/Wind Harmer
1.195
3147133PAMPLIN
Solar/Wind Harmer
0.925
971193AH1-056 GEN
Solar/Wind Harmer
17.953
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
3146926FARMVIL
Solar/Wind Harmer
0.163
3146776BUCKING
Solar/Wind Harmer
0.072
3147043LAWRENC
Solar/Wind Harmer
0.09
3147312GRETNA
Solar/Wind Harmer
0.021
941821AE2-187 GEN
Solar/Wind Harmer
3.437
970221AG2-151 GEN
Solar/Wind Harmer
5.518
313506AB2-031 GEN
Solar/Wind Harmer
0.21
316313AB2-026
Solar/Wind Harmer
0.037
316258AE1-075 C
Solar/Wind Harmer
0.044
316405AF2-144 C
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
0.876
316283AC2-100 C
Solar/Wind Helper
2.324
G-007ALTFEXP_G-007A->PJM
CMTX
0.429
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.343
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.85
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.677
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.127
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.809
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.962
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.375

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:239.46 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1295.46
MW Contribution:47.15
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
1.085
3144293JTRSVLE
50/50
1.008
3144293JTRSVLE
50/50
0.849
970535AG2-341 GEN
50/50
5.145
316222AC1-221 GEN
Solar/Wind Harmer
10.226
970099AG2-077 GEN
Solar/Wind Harmer
67.861
970933AG2-581 GEN
Solar/Wind Harmer
50.184
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.637
962561AG1-105 GEN
Solar/Wind Harmer
26.859
971741AH1-377 GEN
Solar/Wind Harmer
48.337
970301AG2-198 GEN
Solar/Wind Harmer
19.467
313527AB2-043 GEN
Solar/Wind Harmer
5.909
970323AG2-213 GEN
Solar/Wind Harmer
17.431
971775AH1-396 GEN
Solar/Wind Harmer
2.482
316034AC1-036 C
Solar/Wind Harmer
0.646
958211AF2-115 GEN
Solar/Wind Harmer
5.241
963191AG1-168 GEN
Solar/Wind Harmer
3.145
942751AE2-291 GEN
Solar/Wind Harmer
21.269
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.11
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.953
316197AC1-042 GEN
Solar/Wind Harmer
1.481
942671AE2-283 GEN
Solar/Wind Harmer
3.987
971489AH1-241 GEN
Solar/Wind Harmer
6.878
315821AE2-092 GEN
Solar/Wind Harmer
1.789
316181AB2-040 GEN
Solar/Wind Harmer
1.061
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.783
3145593CAROLNA
Solar/Wind Harmer
0.058
970413AG2-270 GEN
50/50
47.147
3144293JTRSVLE
50/50
1.008
3151591KERR 2
50/50
0.536
3151921BEARGRDN G2
50/50
1.068
316283AC2-100 C
Solar/Wind Harmer
9.573
316248AF1-058 C
Solar/Wind Harmer
1.792
960061AF2-297 GEN
Solar/Wind Harmer
29.732
316478AD1-087 GEN
Solar/Wind Harmer
4.927
316486AD2-202 GEN
Solar/Wind Harmer
1.443
971683AH1-343 GEN
Solar/Wind Harmer
21.994
970909AG2-566 GEN
Solar/Wind Harmer
3.696
316131AB2-060 GEN
Solar/Wind Harmer
3.914
964241AG1-285 GEN
Solar/Wind Harmer
27.996
315785AD2-033 C
Solar/Wind Harmer
7.961
970257AG2-171 GEN
Solar/Wind Harmer
13.073
959311AF2-222 GEN
Solar/Wind Harmer
36.177
963181AG1-167 GEN
Solar/Wind Harmer
3.145
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.685
942461AE2-259 GEN
Solar/Wind Harmer
4.783
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.513
970221AG2-151 GEN
Solar/Wind Harmer
7.245
966621AG1-532 GEN
Solar/Wind Harmer
0.166
313506AB2-031 GEN
Solar/Wind Harmer
0.612
316313AB2-026
Solar/Wind Harmer
0.175
316258AE1-075 C
Solar/Wind Harmer
0.157
316405AF2-144 C
Solar/Wind Harmer
0.166
3143336POWHATN
Solar/Wind Harmer
0.654
3151541CLOVER2
50/50
10.752
3151611KERR 4
50/50
0.536
3151621KERR 5
50/50
0.536
3151631KERR 6
50/50
0.536
3151641KERR 7
50/50
0.536
972205AH1-687 GEN
50/50
5.21
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.763
971967AH1-528 GEN
Solar/Wind Harmer
100.637
970865AG2-541 GEN
Solar/Wind Harmer
19.063
316123AC1-075 GEN
Solar/Wind Harmer
4.167
970165AG2-112 GEN
Solar/Wind Harmer
3.669
970163AG2-111 GEN
Solar/Wind Harmer
3.5
316239AB2-077_GEN
Solar/Wind Harmer
1.107
316238AB2-078_GEN
Solar/Wind Harmer
1.107
971443AH1-215 GEN
Solar/Wind Harmer
6.874
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.701
970681AG2-440 GEN
Solar/Wind Harmer
21.361
946301AF1-294 GEN
Solar/Wind Harmer
8.596
961791AG1-021 GEN
Solar/Wind Harmer
4.193
315657AE1-056 GEN
Solar/Wind Harmer
12.411
970285AG2-188 GEN
Solar/Wind Harmer
21.406
971845AH1-439 GEN
Solar/Wind Harmer
12.319
970831AG2-522 GEN
Solar/Wind Harmer
9.997
971447AH1-217 GEN
Solar/Wind Harmer
3.908
270494AE1-108_GEN
Solar/Wind Harmer
2.497
946281AF1-292 GEN
Solar/Wind Harmer
0.183
316087AB2-174 GEN
Solar/Wind Harmer
1.111
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.379
270457AD2-023 GEN
Solar/Wind Helper
0.909
3151531CLOVER1
50/50
10.804
3144293JTRSVLE
50/50
1.008
3151601KERR 3
50/50
0.536
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.432
3151561HALLBR1
50/50
0.347
3151931BEARGRDN S1
50/50
1.379
3151911BEARGRDN G1
50/50
1.068
315687AD1-152 GEN
Solar/Wind Harmer
7.75
316003AC1-222 GEN
Solar/Wind Harmer
5.363
957481AF2-042 GEN
Solar/Wind Harmer
169.654
315693AD1-088 GEN
Solar/Wind Harmer
25.233
962491AG1-098 GEN
Solar/Wind Harmer
33.35
970401AG2-262 GEN
Solar/Wind Harmer
3.25
316237AB2-079_GEN
Solar/Wind Harmer
1.107
970685AG2-442 GEN
Solar/Wind Harmer
29.906
963171AG1-166 GEN
Solar/Wind Harmer
4.193
971563AH1-280 GEN
Solar/Wind Harmer
4.193
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.337
316322AB2-045
Solar/Wind Harmer
0.757
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.874
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.319
971795AH1-408 GEN
Solar/Wind Harmer
10.545
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.513
971377AH1-170 GEN
Solar/Wind Harmer
1.449
3147623JAMES R
Solar/Wind Harmer
0.179
970937AG2-583 GEN
Solar/Wind Harmer
7.531
960081AF2-299 GEN
Solar/Wind Harmer
0.921
316336AC2-165 C
Solar/Wind Harmer
1.321
3143336POWHATN
Solar/Wind Harmer
0.769
270018AE2-047 C O1
Solar/Wind Helper
0.395
G-007ALTFEXP_G-007A->PJM
CMTX
0.368
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.218
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.864
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.722
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.961
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.818
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.028
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.39

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:234.05 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1266.23
MW Contribution:47.06
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
1.083
3144293JTRSVLE
50/50
1.007
3144293JTRSVLE
50/50
0.848
970535AG2-341 GEN
50/50
5.132
316222AC1-221 GEN
Solar/Wind Harmer
10.206
970099AG2-077 GEN
Solar/Wind Harmer
67.735
970933AG2-581 GEN
Solar/Wind Harmer
50.091
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
970413AG2-270 GEN
50/50
47.058
3144293JTRSVLE
50/50
1.007
3151591KERR 2
50/50
0.534
3151921BEARGRDN G2
50/50
1.071
316283AC2-100 C
Solar/Wind Harmer
9.554
316248AF1-058 C
Solar/Wind Harmer
1.788
960061AF2-297 GEN
Solar/Wind Harmer
29.671
316478AD1-087 GEN
Solar/Wind Harmer
4.917
316486AD2-202 GEN
Solar/Wind Harmer
1.44
971683AH1-343 GEN
Solar/Wind Harmer
21.945
970909AG2-566 GEN
Solar/Wind Harmer
3.691
316131AB2-060 GEN
Solar/Wind Harmer
3.906
964241AG1-285 GEN
Solar/Wind Harmer
27.94
315785AD2-033 C
Solar/Wind Harmer
7.947
970257AG2-171 GEN
Solar/Wind Harmer
13.049
959311AF2-222 GEN
Solar/Wind Harmer
36.112
963181AG1-167 GEN
Solar/Wind Harmer
3.14
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.654
942461AE2-259 GEN
Solar/Wind Harmer
4.777
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.485
970221AG2-151 GEN
Solar/Wind Harmer
7.264
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.612
316313AB2-026
Solar/Wind Harmer
0.177
316258AE1-075 C
Solar/Wind Harmer
0.16
964791AG1-342 GEN
Solar/Wind Harmer
10.615
962561AG1-105 GEN
Solar/Wind Harmer
26.803
971741AH1-377 GEN
Solar/Wind Harmer
48.264
970301AG2-198 GEN
Solar/Wind Harmer
19.44
313527AB2-043 GEN
Solar/Wind Harmer
5.897
970323AG2-213 GEN
Solar/Wind Harmer
17.399
971775AH1-396 GEN
Solar/Wind Harmer
2.478
316034AC1-036 C
Solar/Wind Harmer
0.645
958211AF2-115 GEN
Solar/Wind Harmer
5.233
963191AG1-168 GEN
Solar/Wind Harmer
3.14
942751AE2-291 GEN
Solar/Wind Harmer
21.208
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.061
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.941
316197AC1-042 GEN
Solar/Wind Harmer
1.472
942671AE2-283 GEN
Solar/Wind Harmer
3.962
971489AH1-241 GEN
Solar/Wind Harmer
6.896
315821AE2-092 GEN
Solar/Wind Harmer
1.796
316181AB2-040 GEN
Solar/Wind Harmer
1.062
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.781
3145593CAROLNA
Solar/Wind Harmer
0.058
3151531CLOVER1
50/50
10.784
3144293JTRSVLE
50/50
1.007
3151601KERR 3
50/50
0.534
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.431
3151561HALLBR1
50/50
0.345
3151931BEARGRDN S1
50/50
1.382
3151911BEARGRDN G1
50/50
1.071
315687AD1-152 GEN
Solar/Wind Harmer
7.735
316003AC1-222 GEN
Solar/Wind Harmer
5.352
957481AF2-042 GEN
Solar/Wind Harmer
169.338
315693AD1-088 GEN
Solar/Wind Harmer
25.187
962491AG1-098 GEN
Solar/Wind Harmer
33.29
970401AG2-262 GEN
Solar/Wind Harmer
3.243
316237AB2-079_GEN
Solar/Wind Harmer
1.104
970685AG2-442 GEN
Solar/Wind Harmer
29.855
963171AG1-166 GEN
Solar/Wind Harmer
4.186
971563AH1-280 GEN
Solar/Wind Harmer
4.186
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.304
316322AB2-045
Solar/Wind Harmer
0.757
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.869
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.333
971795AH1-408 GEN
Solar/Wind Harmer
10.544
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.485
971377AH1-170 GEN
Solar/Wind Harmer
1.453
3147623JAMES R
Solar/Wind Harmer
0.18
970937AG2-583 GEN
Solar/Wind Harmer
7.571
960081AF2-299 GEN
Solar/Wind Harmer
0.923
316336AC2-165 C
Solar/Wind Harmer
1.335
3143336POWHATN
Solar/Wind Harmer
0.78
3151541CLOVER2
50/50
10.732
3151611KERR 4
50/50
0.534
3151621KERR 5
50/50
0.534
3151631KERR 6
50/50
0.534
3151641KERR 7
50/50
0.534
972205AH1-687 GEN
50/50
5.224
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.755
971967AH1-528 GEN
Solar/Wind Harmer
100.451
970865AG2-541 GEN
Solar/Wind Harmer
19.018
316123AC1-075 GEN
Solar/Wind Harmer
4.156
970165AG2-112 GEN
Solar/Wind Harmer
3.66
970163AG2-111 GEN
Solar/Wind Harmer
3.491
316239AB2-077_GEN
Solar/Wind Harmer
1.104
316238AB2-078_GEN
Solar/Wind Harmer
1.104
971443AH1-215 GEN
Solar/Wind Harmer
6.861
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.656
970681AG2-440 GEN
Solar/Wind Harmer
21.325
946301AF1-294 GEN
Solar/Wind Harmer
8.582
961791AG1-021 GEN
Solar/Wind Harmer
4.186
315657AE1-056 GEN
Solar/Wind Harmer
12.392
970285AG2-188 GEN
Solar/Wind Harmer
21.4
971845AH1-439 GEN
Solar/Wind Harmer
12.318
970831AG2-522 GEN
Solar/Wind Harmer
9.968
971447AH1-217 GEN
Solar/Wind Harmer
3.919
270494AE1-108_GEN
Solar/Wind Harmer
2.5
946281AF1-292 GEN
Solar/Wind Harmer
0.184
316087AB2-174 GEN
Solar/Wind Harmer
1.112
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.399
270457AD2-023 GEN
Solar/Wind Helper
0.922
316405AF2-144 C
Solar/Wind Harmer
0.168
3143336POWHATN
Solar/Wind Harmer
0.663
270018AE2-047 C O1
Solar/Wind Helper
0.402
G-007ALTFEXP_G-007A->PJM
CMTX
0.461
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.38
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.883
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.782
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.209
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.866
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.147
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.491

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:234.0 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1265.96
MW Contribution:47.06
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
1.083
3144293JTRSVLE
50/50
1.007
3144293JTRSVLE
50/50
0.848
970535AG2-341 GEN
50/50
5.132
316222AC1-221 GEN
Solar/Wind Harmer
10.206
970099AG2-077 GEN
Solar/Wind Harmer
67.735
970933AG2-581 GEN
Solar/Wind Harmer
50.091
3146843MT LREL
Solar/Wind Harmer
-0.05
3151541CLOVER2
50/50
10.732
3151611KERR 4
50/50
0.534
3151621KERR 5
50/50
0.534
3151631KERR 6
50/50
0.534
3151641KERR 7
50/50
0.534
972205AH1-687 GEN
50/50
5.224
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.755
971967AH1-528 GEN
Solar/Wind Harmer
100.451
970865AG2-541 GEN
Solar/Wind Harmer
19.018
316123AC1-075 GEN
Solar/Wind Harmer
4.156
970165AG2-112 GEN
Solar/Wind Harmer
3.66
970163AG2-111 GEN
Solar/Wind Harmer
3.491
316239AB2-077_GEN
Solar/Wind Harmer
1.104
316238AB2-078_GEN
Solar/Wind Harmer
1.104
971443AH1-215 GEN
Solar/Wind Harmer
6.861
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.656
970681AG2-440 GEN
Solar/Wind Harmer
21.325
946301AF1-294 GEN
Solar/Wind Harmer
8.582
961791AG1-021 GEN
Solar/Wind Harmer
4.186
315657AE1-056 GEN
Solar/Wind Harmer
12.392
970285AG2-188 GEN
Solar/Wind Harmer
21.4
971845AH1-439 GEN
Solar/Wind Harmer
12.318
970831AG2-522 GEN
Solar/Wind Harmer
9.968
971447AH1-217 GEN
Solar/Wind Harmer
3.919
270494AE1-108_GEN
Solar/Wind Harmer
2.5
946281AF1-292 GEN
Solar/Wind Harmer
0.184
316087AB2-174 GEN
Solar/Wind Harmer
1.112
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.399
270457AD2-023 GEN
Solar/Wind Helper
0.922
3151531CLOVER1
50/50
10.784
3144293JTRSVLE
50/50
1.007
3151601KERR 3
50/50
0.534
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.431
3151561HALLBR1
50/50
0.345
3151931BEARGRDN S1
50/50
1.382
3151911BEARGRDN G1
50/50
1.071
315687AD1-152 GEN
Solar/Wind Harmer
7.735
316003AC1-222 GEN
Solar/Wind Harmer
5.352
957481AF2-042 GEN
Solar/Wind Harmer
169.338
315693AD1-088 GEN
Solar/Wind Harmer
25.187
962491AG1-098 GEN
Solar/Wind Harmer
33.29
970401AG2-262 GEN
Solar/Wind Harmer
3.243
316237AB2-079_GEN
Solar/Wind Harmer
1.104
970685AG2-442 GEN
Solar/Wind Harmer
29.855
963171AG1-166 GEN
Solar/Wind Harmer
4.186
971563AH1-280 GEN
Solar/Wind Harmer
4.186
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.304
316322AB2-045
Solar/Wind Harmer
0.757
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.869
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.333
971795AH1-408 GEN
Solar/Wind Harmer
10.544
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.485
971377AH1-170 GEN
Solar/Wind Harmer
1.453
3147623JAMES R
Solar/Wind Harmer
0.18
970937AG2-583 GEN
Solar/Wind Harmer
7.571
960081AF2-299 GEN
Solar/Wind Harmer
0.923
316336AC2-165 C
Solar/Wind Harmer
1.335
3143336POWHATN
Solar/Wind Harmer
0.78
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.615
962561AG1-105 GEN
Solar/Wind Harmer
26.803
971741AH1-377 GEN
Solar/Wind Harmer
48.264
970301AG2-198 GEN
Solar/Wind Harmer
19.44
313527AB2-043 GEN
Solar/Wind Harmer
5.897
970323AG2-213 GEN
Solar/Wind Harmer
17.399
971775AH1-396 GEN
Solar/Wind Harmer
2.478
316034AC1-036 C
Solar/Wind Harmer
0.645
958211AF2-115 GEN
Solar/Wind Harmer
5.233
963191AG1-168 GEN
Solar/Wind Harmer
3.14
942751AE2-291 GEN
Solar/Wind Harmer
21.208
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.061
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.941
316197AC1-042 GEN
Solar/Wind Harmer
1.472
942671AE2-283 GEN
Solar/Wind Harmer
3.962
971489AH1-241 GEN
Solar/Wind Harmer
6.896
315821AE2-092 GEN
Solar/Wind Harmer
1.796
316181AB2-040 GEN
Solar/Wind Harmer
1.062
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.781
3145593CAROLNA
Solar/Wind Harmer
0.058
970413AG2-270 GEN
50/50
47.058
3144293JTRSVLE
50/50
1.007
3151591KERR 2
50/50
0.534
3151921BEARGRDN G2
50/50
1.071
316283AC2-100 C
Solar/Wind Harmer
9.554
316248AF1-058 C
Solar/Wind Harmer
1.788
960061AF2-297 GEN
Solar/Wind Harmer
29.671
316478AD1-087 GEN
Solar/Wind Harmer
4.917
316486AD2-202 GEN
Solar/Wind Harmer
1.44
971683AH1-343 GEN
Solar/Wind Harmer
21.945
970909AG2-566 GEN
Solar/Wind Harmer
3.691
316131AB2-060 GEN
Solar/Wind Harmer
3.906
964241AG1-285 GEN
Solar/Wind Harmer
27.94
315785AD2-033 C
Solar/Wind Harmer
7.947
970257AG2-171 GEN
Solar/Wind Harmer
13.049
959311AF2-222 GEN
Solar/Wind Harmer
36.112
963181AG1-167 GEN
Solar/Wind Harmer
3.14
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.654
942461AE2-259 GEN
Solar/Wind Harmer
4.777
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.485
970221AG2-151 GEN
Solar/Wind Harmer
7.264
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.612
316313AB2-026
Solar/Wind Harmer
0.177
316258AE1-075 C
Solar/Wind Harmer
0.16
316405AF2-144 C
Solar/Wind Harmer
0.168
3143336POWHATN
Solar/Wind Harmer
0.663
270018AE2-047 C O1
Solar/Wind Helper
0.402
G-007ALTFEXP_G-007A->PJM
CMTX
0.461
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.38
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.883
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.782
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.209
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.866
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.147
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.491

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X1_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:231.01 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1249.79
MW Contribution:47.59
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
1.089
3144293JTRSVLE
50/50
1.002
3144293JTRSVLE
50/50
0.844
970535AG2-341 GEN
50/50
5.134
316222AC1-221 GEN
Solar/Wind Harmer
10.241
970099AG2-077 GEN
Solar/Wind Harmer
69.119
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.658
962561AG1-105 GEN
Solar/Wind Harmer
26.899
971741AH1-377 GEN
Solar/Wind Harmer
47.648
970301AG2-198 GEN
Solar/Wind Harmer
19.194
313527AB2-043 GEN
Solar/Wind Harmer
5.898
970323AG2-213 GEN
Solar/Wind Harmer
17.355
971775AH1-396 GEN
Solar/Wind Harmer
2.471
316034AC1-036 C
Solar/Wind Harmer
0.643
942751AE2-291 GEN
Solar/Wind Harmer
21.352
958211AF2-115 GEN
Solar/Wind Harmer
5.206
963191AG1-168 GEN
Solar/Wind Harmer
3.124
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.072
3146776BUCKING
Solar/Wind Harmer
-0.088
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.963
316197AC1-042 GEN
Solar/Wind Harmer
1.488
942671AE2-283 GEN
Solar/Wind Harmer
4.007
971489AH1-241 GEN
Solar/Wind Harmer
6.79
315821AE2-092 GEN
Solar/Wind Harmer
1.766
316181AB2-040 GEN
Solar/Wind Harmer
1.06
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.781
3145593CAROLNA
Solar/Wind Harmer
0.058
3151541CLOVER2
50/50
10.854
3151611KERR 4
50/50
0.535
3151621KERR 5
50/50
0.535
3151631KERR 6
50/50
0.535
3151641KERR 7
50/50
0.535
972205AH1-687 GEN
50/50
5.142
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.773
970865AG2-541 GEN
Solar/Wind Harmer
19.134
316123AC1-075 GEN
Solar/Wind Harmer
4.183
970165AG2-112 GEN
Solar/Wind Harmer
3.683
970163AG2-111 GEN
Solar/Wind Harmer
3.514
316239AB2-077_GEN
Solar/Wind Harmer
1.105
316238AB2-078_GEN
Solar/Wind Harmer
1.105
971443AH1-215 GEN
Solar/Wind Harmer
6.844
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.554
970681AG2-440 GEN
Solar/Wind Harmer
21.243
946301AF1-294 GEN
Solar/Wind Harmer
8.538
961791AG1-021 GEN
Solar/Wind Harmer
4.165
315657AE1-056 GEN
Solar/Wind Harmer
12.318
970285AG2-188 GEN
Solar/Wind Harmer
21.128
971845AH1-439 GEN
Solar/Wind Harmer
12.16
970831AG2-522 GEN
Solar/Wind Harmer
9.974
971447AH1-217 GEN
Solar/Wind Harmer
3.858
270494AE1-108_GEN
Solar/Wind Harmer
2.469
946281AF1-292 GEN
Solar/Wind Harmer
0.183
316087AB2-174 GEN
Solar/Wind Harmer
1.109
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.37
270457AD2-023 GEN
Solar/Wind Helper
0.903
3151531CLOVER1
50/50
10.906
3144293JTRSVLE
50/50
1.002
3151601KERR 3
50/50
0.535
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.43
3151561HALLBR1
50/50
0.348
3151931BEARGRDN S1
50/50
1.361
3151911BEARGRDN G1
50/50
1.054
315687AD1-152 GEN
Solar/Wind Harmer
7.801
957481AF2-042 GEN
Solar/Wind Harmer
172.797
316003AC1-222 GEN
Solar/Wind Harmer
5.383
970401AG2-262 GEN
Solar/Wind Harmer
3.256
315693AD1-088 GEN
Solar/Wind Harmer
24.857
962491AG1-098 GEN
Solar/Wind Harmer
32.854
316237AB2-079_GEN
Solar/Wind Harmer
1.105
970685AG2-442 GEN
Solar/Wind Harmer
29.741
963171AG1-166 GEN
Solar/Wind Harmer
4.165
971563AH1-280 GEN
Solar/Wind Harmer
4.165
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.312
316322AB2-045
Solar/Wind Harmer
0.748
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.87
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.224
971795AH1-408 GEN
Solar/Wind Harmer
10.527
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.536
971377AH1-170 GEN
Solar/Wind Harmer
1.43
3147623JAMES R
Solar/Wind Harmer
0.177
970937AG2-583 GEN
Solar/Wind Harmer
7.432
960081AF2-299 GEN
Solar/Wind Harmer
0.92
316336AC2-165 C
Solar/Wind Harmer
1.303
3143336POWHATN
Solar/Wind Harmer
0.759
970413AG2-270 GEN
50/50
47.591
3144293JTRSVLE
50/50
1.002
3151591KERR 2
50/50
0.535
3151921BEARGRDN G2
50/50
1.054
316283AC2-100 C
Solar/Wind Harmer
9.587
316248AF1-058 C
Solar/Wind Harmer
1.798
960061AF2-297 GEN
Solar/Wind Harmer
29.84
316478AD1-087 GEN
Solar/Wind Harmer
4.973
316486AD2-202 GEN
Solar/Wind Harmer
1.456
971683AH1-343 GEN
Solar/Wind Harmer
22.075
970909AG2-566 GEN
Solar/Wind Harmer
3.645
316131AB2-060 GEN
Solar/Wind Harmer
3.906
964241AG1-285 GEN
Solar/Wind Harmer
27.919
315785AD2-033 C
Solar/Wind Harmer
7.93
970257AG2-171 GEN
Solar/Wind Harmer
13.016
959311AF2-222 GEN
Solar/Wind Harmer
36.008
963181AG1-167 GEN
Solar/Wind Harmer
3.124
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.53
942461AE2-259 GEN
Solar/Wind Harmer
4.736
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.536
970221AG2-151 GEN
Solar/Wind Harmer
7.152
966621AG1-532 GEN
Solar/Wind Harmer
0.166
313506AB2-031 GEN
Solar/Wind Harmer
0.611
316313AB2-026
Solar/Wind Harmer
0.172
316258AE1-075 C
Solar/Wind Harmer
0.155
316405AF2-144 C
Solar/Wind Harmer
0.164
3143336POWHATN
Solar/Wind Harmer
0.645
G-007ALTFEXP_G-007A->PJM
CMTX
0.347
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.181
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.859
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.707
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.905
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.807
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.999
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.368

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X2_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:231.0 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1249.74
MW Contribution:47.59
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
1.089
3144293JTRSVLE
50/50
1.002
3144293JTRSVLE
50/50
0.844
970535AG2-341 GEN
50/50
5.134
316222AC1-221 GEN
Solar/Wind Harmer
10.241
970099AG2-077 GEN
Solar/Wind Harmer
69.109
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.657
962561AG1-105 GEN
Solar/Wind Harmer
26.899
971741AH1-377 GEN
Solar/Wind Harmer
47.653
970301AG2-198 GEN
Solar/Wind Harmer
19.197
313527AB2-043 GEN
Solar/Wind Harmer
5.898
970323AG2-213 GEN
Solar/Wind Harmer
17.355
971775AH1-396 GEN
Solar/Wind Harmer
2.471
316034AC1-036 C
Solar/Wind Harmer
0.644
942751AE2-291 GEN
Solar/Wind Harmer
21.351
958211AF2-115 GEN
Solar/Wind Harmer
5.207
963191AG1-168 GEN
Solar/Wind Harmer
3.124
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.072
3146776BUCKING
Solar/Wind Harmer
-0.088
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.963
316197AC1-042 GEN
Solar/Wind Harmer
1.488
942671AE2-283 GEN
Solar/Wind Harmer
4.007
971489AH1-241 GEN
Solar/Wind Harmer
6.79
315821AE2-092 GEN
Solar/Wind Harmer
1.766
316181AB2-040 GEN
Solar/Wind Harmer
1.06
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.781
3145593CAROLNA
Solar/Wind Harmer
0.058
3151531CLOVER1
50/50
10.905
3144293JTRSVLE
50/50
1.002
3151601KERR 3
50/50
0.535
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.43
3151561HALLBR1
50/50
0.348
3151931BEARGRDN S1
50/50
1.361
3151911BEARGRDN G1
50/50
1.054
315687AD1-152 GEN
Solar/Wind Harmer
7.801
957481AF2-042 GEN
Solar/Wind Harmer
172.774
316003AC1-222 GEN
Solar/Wind Harmer
5.383
970401AG2-262 GEN
Solar/Wind Harmer
3.256
315693AD1-088 GEN
Solar/Wind Harmer
24.86
962491AG1-098 GEN
Solar/Wind Harmer
32.858
316237AB2-079_GEN
Solar/Wind Harmer
1.105
970685AG2-442 GEN
Solar/Wind Harmer
29.742
963171AG1-166 GEN
Solar/Wind Harmer
4.165
971563AH1-280 GEN
Solar/Wind Harmer
4.165
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.312
316322AB2-045
Solar/Wind Harmer
0.748
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.87
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.224
971795AH1-408 GEN
Solar/Wind Harmer
10.527
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.536
971377AH1-170 GEN
Solar/Wind Harmer
1.431
3147623JAMES R
Solar/Wind Harmer
0.177
970937AG2-583 GEN
Solar/Wind Harmer
7.433
960081AF2-299 GEN
Solar/Wind Harmer
0.92
316336AC2-165 C
Solar/Wind Harmer
1.304
3143336POWHATN
Solar/Wind Harmer
0.759
3151541CLOVER2
50/50
10.853
3151611KERR 4
50/50
0.535
3151621KERR 5
50/50
0.535
3151631KERR 6
50/50
0.535
3151641KERR 7
50/50
0.535
972205AH1-687 GEN
50/50
5.143
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.773
970865AG2-541 GEN
Solar/Wind Harmer
19.133
316123AC1-075 GEN
Solar/Wind Harmer
4.183
970165AG2-112 GEN
Solar/Wind Harmer
3.683
970163AG2-111 GEN
Solar/Wind Harmer
3.514
316239AB2-077_GEN
Solar/Wind Harmer
1.105
316238AB2-078_GEN
Solar/Wind Harmer
1.105
971443AH1-215 GEN
Solar/Wind Harmer
6.845
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.555
970681AG2-440 GEN
Solar/Wind Harmer
21.244
946301AF1-294 GEN
Solar/Wind Harmer
8.539
961791AG1-021 GEN
Solar/Wind Harmer
4.165
315657AE1-056 GEN
Solar/Wind Harmer
12.319
970285AG2-188 GEN
Solar/Wind Harmer
21.13
971845AH1-439 GEN
Solar/Wind Harmer
12.161
970831AG2-522 GEN
Solar/Wind Harmer
9.975
971447AH1-217 GEN
Solar/Wind Harmer
3.858
270494AE1-108_GEN
Solar/Wind Harmer
2.469
946281AF1-292 GEN
Solar/Wind Harmer
0.183
316087AB2-174 GEN
Solar/Wind Harmer
1.109
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.37
270457AD2-023 GEN
Solar/Wind Helper
0.903
970413AG2-270 GEN
50/50
47.588
3144293JTRSVLE
50/50
1.002
3151591KERR 2
50/50
0.535
3151921BEARGRDN G2
50/50
1.054
316283AC2-100 C
Solar/Wind Harmer
9.586
316248AF1-058 C
Solar/Wind Harmer
1.798
960061AF2-297 GEN
Solar/Wind Harmer
29.84
316478AD1-087 GEN
Solar/Wind Harmer
4.972
316486AD2-202 GEN
Solar/Wind Harmer
1.456
971683AH1-343 GEN
Solar/Wind Harmer
22.075
970909AG2-566 GEN
Solar/Wind Harmer
3.645
316131AB2-060 GEN
Solar/Wind Harmer
3.906
964241AG1-285 GEN
Solar/Wind Harmer
27.92
315785AD2-033 C
Solar/Wind Harmer
7.931
970257AG2-171 GEN
Solar/Wind Harmer
13.017
959311AF2-222 GEN
Solar/Wind Harmer
36.009
963181AG1-167 GEN
Solar/Wind Harmer
3.124
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.531
942461AE2-259 GEN
Solar/Wind Harmer
4.736
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.536
970221AG2-151 GEN
Solar/Wind Harmer
7.153
966621AG1-532 GEN
Solar/Wind Harmer
0.166
313506AB2-031 GEN
Solar/Wind Harmer
0.611
316313AB2-026
Solar/Wind Harmer
0.173
316258AE1-075 C
Solar/Wind Harmer
0.155
316405AF2-144 C
Solar/Wind Harmer
0.164
3143336POWHATN
Solar/Wind Harmer
0.645
G-007ALTFEXP_G-007A->PJM
CMTX
0.347
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.181
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.859
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.707
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.906
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.807
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.999
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.368

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:192.41 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:978.46
MW Contribution:47.15
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
1.085
3144293JTRSVLE
50/50
1.008
3144293JTRSVLE
50/50
0.849
970535AG2-341 GEN
50/50
5.145
316222AC1-221 GEN
Solar/Wind Harmer
3.733
970099AG2-077 GEN
Solar/Wind Harmer
51.54
970933AG2-581 GEN
Solar/Wind Harmer
38.114
3146843MT LREL
Solar/Wind Harmer
0.444
3146843MT LREL
Solar/Wind Harmer
0.444
964791AG1-342 GEN
Solar/Wind Harmer
8.51
962561AG1-105 GEN
Solar/Wind Harmer
20.399
971741AH1-377 GEN
Solar/Wind Harmer
36.712
970301AG2-198 GEN
Solar/Wind Harmer
14.785
313527AB2-043 GEN
Solar/Wind Harmer
0.004
970323AG2-213 GEN
Solar/Wind Harmer
13.238
971775AH1-396 GEN
Solar/Wind Harmer
0.496
316034AC1-036 C
Solar/Wind Harmer
0.023
958211AF2-115 GEN
Solar/Wind Harmer
3.583
963191AG1-168 GEN
Solar/Wind Harmer
1.194
942751AE2-291 GEN
Solar/Wind Harmer
16.154
3147133PAMPLIN
Solar/Wind Harmer
0.294
3147133PAMPLIN
Solar/Wind Harmer
0.235
939181AE1-148 GEN
Solar/Wind Harmer
12.995
3146776BUCKING
Solar/Wind Harmer
0.801
3146776BUCKING
Solar/Wind Harmer
0.065
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
2.666
971489AH1-241 GEN
Solar/Wind Harmer
5.502
315821AE2-092 GEN
Solar/Wind Harmer
0.005
316181AB2-040 GEN
Solar/Wind Harmer
0.098
3145593CAROLNA
Solar/Wind Harmer
0.062
3145593CAROLNA
Solar/Wind Harmer
0.062
966811AG1-552 GEN
Solar/Wind Harmer
0.671
3145593CAROLNA
Solar/Wind Harmer
0.077
3151531CLOVER1
50/50
10.804
3144293JTRSVLE
50/50
1.008
3151601KERR 3
50/50
0.536
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.432
3151561HALLBR1
50/50
0.347
3151931BEARGRDN S1
50/50
1.379
3151911BEARGRDN G1
50/50
1.068
3151261ROARAP2
50/50
0.077
24728405LEESVG
50/50
0.072
315687AD1-152 GEN
Solar/Wind Harmer
0.019
316003AC1-222 GEN
Solar/Wind Harmer
0.013
957481AF2-042 GEN
Solar/Wind Harmer
128.851
315693AD1-088 GEN
Solar/Wind Harmer
21.559
962491AG1-098 GEN
Solar/Wind Harmer
25.329
970401AG2-262 GEN
Solar/Wind Harmer
2.6
316237AB2-079_GEN
Solar/Wind Harmer
0.003
970685AG2-442 GEN
Solar/Wind Harmer
22.713
963171AG1-166 GEN
Solar/Wind Harmer
1.592
971563AH1-280 GEN
Solar/Wind Harmer
3.185
3146926FARMVIL
Solar/Wind Harmer
0.162
971065AG2-659 GEN
Solar/Wind Harmer
8.611
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.08
316129AC1-054 GEN
Solar/Wind Harmer
0.716
3147123OTTER R
Solar/Wind Harmer
0.087
972003AH1-546 GEN
Solar/Wind Harmer
5.549
971795AH1-408 GEN
Solar/Wind Harmer
8.343
3147312GRETNA
Solar/Wind Harmer
0.086
3146802CHATHAM
Solar/Wind Harmer
0.08
941801AE2-185 GEN
Solar/Wind Harmer
3.428
971377AH1-170 GEN
Solar/Wind Harmer
1.1
3147623JAMES R
Solar/Wind Harmer
0.239
970937AG2-583 GEN
Solar/Wind Harmer
5.72
960081AF2-299 GEN
Solar/Wind Harmer
0.7
316336AC2-165 C
Solar/Wind Harmer
0.003
970413AG2-270 GEN
50/50
47.147
3144293JTRSVLE
50/50
1.008
3151591KERR 2
50/50
0.536
3151921BEARGRDN G2
50/50
1.068
3151261ROARAP2
50/50
0.075
24728405LEESVG
50/50
0.073
316283AC2-100 C
Solar/Wind Harmer
1.77
316248AF1-058 C
Solar/Wind Harmer
0.004
960061AF2-297 GEN
Solar/Wind Harmer
22.582
316478AD1-087 GEN
Solar/Wind Harmer
1.767
316486AD2-202 GEN
Solar/Wind Harmer
0.519
971683AH1-343 GEN
Solar/Wind Harmer
16.704
970909AG2-566 GEN
Solar/Wind Harmer
3.696
316131AB2-060 GEN
Solar/Wind Harmer
1.015
964241AG1-285 GEN
Solar/Wind Harmer
21.263
315785AD2-033 C
Solar/Wind Harmer
2.542
970257AG2-171 GEN
Solar/Wind Harmer
9.929
959311AF2-222 GEN
Solar/Wind Harmer
27.421
963181AG1-167 GEN
Solar/Wind Harmer
1.194
3147133PAMPLIN
Solar/Wind Harmer
0.924
971193AH1-056 GEN
Solar/Wind Harmer
17.935
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
3146926FARMVIL
Solar/Wind Harmer
0.162
3146776BUCKING
Solar/Wind Harmer
0.072
3147043LAWRENC
Solar/Wind Harmer
0.09
3147312GRETNA
Solar/Wind Harmer
0.021
941821AE2-187 GEN
Solar/Wind Harmer
3.428
970221AG2-151 GEN
Solar/Wind Harmer
5.502
313506AB2-031 GEN
Solar/Wind Harmer
0.209
316313AB2-026
Solar/Wind Harmer
0.036
316258AE1-075 C
Solar/Wind Harmer
0.044
316405AF2-144 C
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
0.872
270018AE2-047 C O1
Solar/Wind Helper
0.395
3143336POWHATN
Solar/Wind Harmer
1.026
3151541CLOVER2
50/50
10.752
3151611KERR 4
50/50
0.536
3151621KERR 5
50/50
0.536
3151631KERR 6
50/50
0.536
3151641KERR 7
50/50
0.536
972205AH1-687 GEN
50/50
5.21
3151281ROARAP4
50/50
0.075
3151281ROARAP4
50/50
0.07
3147173SINAI
Solar/Wind Harmer
0.529
3147243WELCO
Solar/Wind Harmer
0.331
316118AC1-105 GEN
Solar/Wind Harmer
1.257
971967AH1-528 GEN
Solar/Wind Harmer
76.23
970865AG2-541 GEN
Solar/Wind Harmer
14.478
316123AC1-075 GEN
Solar/Wind Harmer
0.47
970165AG2-112 GEN
Solar/Wind Harmer
2.787
970163AG2-111 GEN
Solar/Wind Harmer
2.658
316239AB2-077_GEN
Solar/Wind Harmer
0.003
316238AB2-078_GEN
Solar/Wind Harmer
0.003
971443AH1-215 GEN
Solar/Wind Harmer
5.22
3144303KENBRDG
Solar/Wind Harmer
0.248
970683AG2-441 GEN
Solar/Wind Harmer
20.28
970681AG2-440 GEN
Solar/Wind Harmer
16.224
946301AF1-294 GEN
Solar/Wind Harmer
5.891
961791AG1-021 GEN
Solar/Wind Harmer
2.866
315657AE1-056 GEN
Solar/Wind Harmer
10.159
970285AG2-188 GEN
Solar/Wind Harmer
17.225
971845AH1-439 GEN
Solar/Wind Harmer
9.357
970831AG2-522 GEN
Solar/Wind Harmer
7.592
971447AH1-217 GEN
Solar/Wind Harmer
2.968
270494AE1-108_GEN
Solar/Wind Harmer
1.024
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.258
270455AD2-022 GEN
Solar/Wind Helper
1.379
270457AD2-023 GEN
Solar/Wind Helper
0.909
G-007ALTFEXP_G-007A->PJM
CMTX
0.368
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.218
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.864
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.722
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.961
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.818
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.028
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.39

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:189.13 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:961.81
MW Contribution:47.15
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
1.085
3144293JTRSVLE
50/50
1.008
3144293JTRSVLE
50/50
0.849
970535AG2-341 GEN
50/50
5.145
316222AC1-221 GEN
Solar/Wind Harmer
3.733
970099AG2-077 GEN
Solar/Wind Harmer
51.54
3146843MT LREL
Solar/Wind Harmer
0.444
3146843MT LREL
Solar/Wind Harmer
0.444
964791AG1-342 GEN
Solar/Wind Harmer
8.51
962561AG1-105 GEN
Solar/Wind Harmer
20.399
971741AH1-377 GEN
Solar/Wind Harmer
36.712
970301AG2-198 GEN
Solar/Wind Harmer
14.785
313527AB2-043 GEN
Solar/Wind Harmer
0.004
970323AG2-213 GEN
Solar/Wind Harmer
13.238
971775AH1-396 GEN
Solar/Wind Harmer
0.496
316034AC1-036 C
Solar/Wind Harmer
0.023
958211AF2-115 GEN
Solar/Wind Harmer
3.583
963191AG1-168 GEN
Solar/Wind Harmer
1.194
942751AE2-291 GEN
Solar/Wind Harmer
16.154
3147133PAMPLIN
Solar/Wind Harmer
0.294
3147133PAMPLIN
Solar/Wind Harmer
0.235
939181AE1-148 GEN
Solar/Wind Harmer
12.995
3146776BUCKING
Solar/Wind Harmer
0.801
3146776BUCKING
Solar/Wind Harmer
0.065
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
2.666
971489AH1-241 GEN
Solar/Wind Harmer
5.502
315821AE2-092 GEN
Solar/Wind Harmer
0.005
316181AB2-040 GEN
Solar/Wind Harmer
0.098
3145593CAROLNA
Solar/Wind Harmer
0.062
3145593CAROLNA
Solar/Wind Harmer
0.062
966811AG1-552 GEN
Solar/Wind Harmer
0.671
970413AG2-270 GEN
50/50
47.147
3144293JTRSVLE
50/50
1.008
3151591KERR 2
50/50
0.536
3151921BEARGRDN G2
50/50
1.068
3151261ROARAP2
50/50
0.075
24728405LEESVG
50/50
0.073
316283AC2-100 C
Solar/Wind Harmer
1.77
316248AF1-058 C
Solar/Wind Harmer
0.004
960061AF2-297 GEN
Solar/Wind Harmer
22.582
316478AD1-087 GEN
Solar/Wind Harmer
1.767
316486AD2-202 GEN
Solar/Wind Harmer
0.519
971683AH1-343 GEN
Solar/Wind Harmer
16.704
970909AG2-566 GEN
Solar/Wind Harmer
3.696
316131AB2-060 GEN
Solar/Wind Harmer
1.015
964241AG1-285 GEN
Solar/Wind Harmer
21.263
315785AD2-033 C
Solar/Wind Harmer
2.542
970257AG2-171 GEN
Solar/Wind Harmer
9.929
959311AF2-222 GEN
Solar/Wind Harmer
27.421
963181AG1-167 GEN
Solar/Wind Harmer
1.194
3147133PAMPLIN
Solar/Wind Harmer
0.924
971193AH1-056 GEN
Solar/Wind Harmer
17.935
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
3146926FARMVIL
Solar/Wind Harmer
0.162
3146776BUCKING
Solar/Wind Harmer
0.072
3147043LAWRENC
Solar/Wind Harmer
0.09
3147312GRETNA
Solar/Wind Harmer
0.021
941821AE2-187 GEN
Solar/Wind Harmer
3.428
970221AG2-151 GEN
Solar/Wind Harmer
5.502
313506AB2-031 GEN
Solar/Wind Harmer
0.209
3145593CAROLNA
Solar/Wind Harmer
0.077
3151531CLOVER1
50/50
10.804
3144293JTRSVLE
50/50
1.008
3151601KERR 3
50/50
0.536
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.432
3151561HALLBR1
50/50
0.347
3151931BEARGRDN S1
50/50
1.379
3151911BEARGRDN G1
50/50
1.068
3151261ROARAP2
50/50
0.077
24728405LEESVG
50/50
0.072
315687AD1-152 GEN
Solar/Wind Harmer
0.019
316003AC1-222 GEN
Solar/Wind Harmer
0.013
957481AF2-042 GEN
Solar/Wind Harmer
128.851
315693AD1-088 GEN
Solar/Wind Harmer
21.559
962491AG1-098 GEN
Solar/Wind Harmer
25.329
970401AG2-262 GEN
Solar/Wind Harmer
2.6
316237AB2-079_GEN
Solar/Wind Harmer
0.003
970685AG2-442 GEN
Solar/Wind Harmer
22.713
963171AG1-166 GEN
Solar/Wind Harmer
1.592
971563AH1-280 GEN
Solar/Wind Harmer
3.185
3146926FARMVIL
Solar/Wind Harmer
0.162
971065AG2-659 GEN
Solar/Wind Harmer
8.611
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.08
316129AC1-054 GEN
Solar/Wind Harmer
0.716
3147123OTTER R
Solar/Wind Harmer
0.087
972003AH1-546 GEN
Solar/Wind Harmer
5.549
971795AH1-408 GEN
Solar/Wind Harmer
8.343
3147312GRETNA
Solar/Wind Harmer
0.086
3146802CHATHAM
Solar/Wind Harmer
0.08
941801AE2-185 GEN
Solar/Wind Harmer
3.428
971377AH1-170 GEN
Solar/Wind Harmer
1.1
3147623JAMES R
Solar/Wind Harmer
0.239
970937AG2-583 GEN
Solar/Wind Harmer
5.72
960081AF2-299 GEN
Solar/Wind Harmer
0.7
316336AC2-165 C
Solar/Wind Harmer
0.003
3143336POWHATN
Solar/Wind Harmer
1.026
3151541CLOVER2
50/50
10.752
3151611KERR 4
50/50
0.536
3151621KERR 5
50/50
0.536
3151631KERR 6
50/50
0.536
3151641KERR 7
50/50
0.536
972205AH1-687 GEN
50/50
5.21
3151281ROARAP4
50/50
0.075
3151281ROARAP4
50/50
0.07
3147173SINAI
Solar/Wind Harmer
0.529
3147243WELCO
Solar/Wind Harmer
0.331
316118AC1-105 GEN
Solar/Wind Harmer
1.257
970865AG2-541 GEN
Solar/Wind Harmer
14.478
316123AC1-075 GEN
Solar/Wind Harmer
0.47
970165AG2-112 GEN
Solar/Wind Harmer
2.787
970163AG2-111 GEN
Solar/Wind Harmer
2.658
316239AB2-077_GEN
Solar/Wind Harmer
0.003
316238AB2-078_GEN
Solar/Wind Harmer
0.003
971443AH1-215 GEN
Solar/Wind Harmer
5.22
3144303KENBRDG
Solar/Wind Harmer
0.248
970683AG2-441 GEN
Solar/Wind Harmer
20.28
970681AG2-440 GEN
Solar/Wind Harmer
16.224
946301AF1-294 GEN
Solar/Wind Harmer
5.891
961791AG1-021 GEN
Solar/Wind Harmer
2.866
315657AE1-056 GEN
Solar/Wind Harmer
10.159
970285AG2-188 GEN
Solar/Wind Harmer
17.225
971845AH1-439 GEN
Solar/Wind Harmer
9.357
970831AG2-522 GEN
Solar/Wind Harmer
7.592
971447AH1-217 GEN
Solar/Wind Harmer
2.968
270494AE1-108_GEN
Solar/Wind Harmer
1.024
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.258
270455AD2-022 GEN
Solar/Wind Helper
1.379
270457AD2-023 GEN
Solar/Wind Helper
0.909
316313AB2-026
Solar/Wind Harmer
0.036
316258AE1-075 C
Solar/Wind Harmer
0.044
316405AF2-144 C
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
0.872
270018AE2-047 C O1
Solar/Wind Helper
0.395
G-007ALTFEXP_G-007A->PJM
CMTX
0.368
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.218
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.864
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.722
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.961
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.818
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.028
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.39

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: BREMO B1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.04 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:552.01
MW Contribution:24.08
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
5.491
3151611KERR 4
50/50
0.291
3151621KERR 5
50/50
0.291
3151631KERR 6
50/50
0.291
3151641KERR 7
50/50
0.291
3147173SINAI
Solar/Wind Harmer
-0.044
3147243WELCO
Solar/Wind Harmer
-0.027
316118AC1-105 GEN
Solar/Wind Harmer
2.738
970865AG2-541 GEN
Solar/Wind Harmer
13.887
316123AC1-075 GEN
Solar/Wind Harmer
2.983
970165AG2-112 GEN
Solar/Wind Harmer
2.626
970163AG2-111 GEN
Solar/Wind Harmer
2.505
316239AB2-077_GEN
Solar/Wind Harmer
0.713
316238AB2-078_GEN
Solar/Wind Harmer
0.713
3144303KENBRDG
Solar/Wind Harmer
-0.019
971443AH1-215 GEN
Solar/Wind Harmer
4.576
970683AG2-441 GEN
Solar/Wind Harmer
18.096
970681AG2-440 GEN
Solar/Wind Harmer
14.477
946301AF1-294 GEN
Solar/Wind Harmer
5.918
961791AG1-021 GEN
Solar/Wind Harmer
2.887
315657AE1-056 GEN
Solar/Wind Harmer
8.642
971845AH1-439 GEN
Solar/Wind Harmer
12.087
970285AG2-188 GEN
Solar/Wind Harmer
19.908
970831AG2-522 GEN
Solar/Wind Harmer
5.656
971967AH1-528 GEN
Solar/Wind Harmer
18.182
970673AG2-436 GEN
Solar/Wind Harmer
14.386
970673AG2-436 GEN
Solar/Wind Harmer
7.284
946281AF1-292 GEN
Solar/Wind Harmer
0.153
941031AE2-094 GEN
Solar/Wind Harmer
12.694
944011AF1-069 GEN
Solar/Wind Harmer
3.977
270455AD2-022 GEN
Solar/Wind Helper
1.808
270457AD2-023 GEN
Solar/Wind Helper
1.191
270069AE2-166 C O1
Solar/Wind Helper
0.543
3151531CLOVER1
50/50
5.517
3144293JTRSVLE
50/50
0.694
3151601KERR 3
50/50
0.291
3151581KERR 1
50/50
0.104
315687AD1-152 GEN
Solar/Wind Harmer
5.005
316003AC1-222 GEN
Solar/Wind Harmer
3.954
970401AG2-262 GEN
Solar/Wind Harmer
2.311
316237AB2-079_GEN
Solar/Wind Harmer
0.713
970685AG2-442 GEN
Solar/Wind Harmer
20.268
963171AG1-166 GEN
Solar/Wind Harmer
2.887
971563AH1-280 GEN
Solar/Wind Harmer
2.887
972003AH1-546 GEN
Solar/Wind Harmer
11.349
316322AB2-045
Solar/Wind Harmer
0.765
3146776BUCKING
Solar/Wind Harmer
-0.009
3146926FARMVIL
Solar/Wind Harmer
-0.013
962491AG1-098 GEN
Solar/Wind Harmer
15.104
315693AD1-088 GEN
Solar/Wind Harmer
11.29
957481AF2-042 GEN
Solar/Wind Harmer
70.478
971065AG2-659 GEN
Solar/Wind Harmer
6.314
316129AC1-054 GEN
Solar/Wind Harmer
1.051
3147043LAWRENC
Adder
0.955
971795AH1-408 GEN
Solar/Wind Harmer
7.701
3147123OTTER R
Solar/Wind Harmer
-0.006
960081AF2-299 GEN
Solar/Wind Harmer
0.766
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.507
940641AE2-051 GEN
Solar/Wind Harmer
5.976
939411AE1-173 GEN
Solar/Wind Harmer
30.063
270016AE1-250 BESS
Solar/Wind Helper
0.571
3152661PLYWOOD A
50/50
0.786
3144293JTRSVLE
50/50
0.694
3144293JTRSVLE
50/50
0.585
970535AG2-341 GEN
50/50
3.063
316222AC1-221 GEN
Solar/Wind Harmer
9.436
3146843MT LREL
Solar/Wind Harmer
-0.035
3146843MT LREL
Solar/Wind Harmer
-0.035
964791AG1-342 GEN
Solar/Wind Harmer
7.565
962561AG1-105 GEN
Solar/Wind Harmer
18.89
942751AE2-291 GEN
Solar/Wind Harmer
14.981
313527AB2-043 GEN
Solar/Wind Harmer
3.802
970323AG2-213 GEN
Solar/Wind Harmer
11.621
971775AH1-396 GEN
Solar/Wind Harmer
1.655
316034AC1-036 C
Solar/Wind Harmer
0.431
958211AF2-115 GEN
Solar/Wind Harmer
3.609
963191AG1-168 GEN
Solar/Wind Harmer
2.165
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.091
3146776BUCKING
Solar/Wind Harmer
-0.007
970301AG2-198 GEN
Solar/Wind Harmer
11.339
971741AH1-377 GEN
Solar/Wind Harmer
26.337
970099AG2-077 GEN
Solar/Wind Harmer
28.191
939181AE1-148 GEN
Solar/Wind Harmer
9.651
970933AG2-581 GEN
Solar/Wind Harmer
12.282
972187AH1-678 GEN
Adder
1.759
972185AH1-677 GEN
Adder
3.44
316217AC1-145 GEN
Solar/Wind Harmer
1.085
316197AC1-042 GEN
Solar/Wind Harmer
0.823
942671AE2-283 GEN
Solar/Wind Harmer
2.215
270013AE1-250 PV
Solar/Wind Helper
0.571
970413AG2-270 GEN
50/50
24.076
3144293JTRSVLE
50/50
0.694
3151591KERR 2
50/50
0.291
316283AC2-100 C
Solar/Wind Harmer
8.862
316248AF1-058 C
Solar/Wind Harmer
1.328
960061AF2-297 GEN
Solar/Wind Harmer
22.033
971683AH1-343 GEN
Solar/Wind Harmer
16.127
316478AD1-087 GEN
Solar/Wind Harmer
2.53
316486AD2-202 GEN
Solar/Wind Harmer
0.741
316131AB2-060 GEN
Solar/Wind Harmer
2.525
964241AG1-285 GEN
Solar/Wind Harmer
18.238
315785AD2-033 C
Solar/Wind Harmer
5.274
970257AG2-171 GEN
Solar/Wind Harmer
8.716
959311AF2-222 GEN
Solar/Wind Harmer
24.232
963181AG1-167 GEN
Solar/Wind Harmer
2.165
3147133PAMPLIN
Solar/Wind Harmer
-0.072
971193AH1-056 GEN
Solar/Wind Harmer
14.403
942461AE2-259 GEN
Solar/Wind Harmer
3.442
3146776BUCKING
Solar/Wind Harmer
-0.008
3146926FARMVIL
Solar/Wind Harmer
-0.013
970909AG2-566 GEN
Solar/Wind Harmer
2.153
3147043LAWRENC
Solar/Wind Harmer
-0.007
966621AG1-532 GEN
Solar/Wind Harmer
0.138
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.507
270018AE2-047 C O1
Solar/Wind Helper
0.567
943811AF1-049 GEN
Solar/Wind Helper
0.923
270336AE1-100 GEN
Solar/Wind Helper
0.558
G-007ALTFEXP_G-007A->PJM
CMTX
1.744
CBM NorthLTFEXP_CBM-N->PJM
CBM
2.484
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
1.198
BlueGrassPJM->LTFIMP_BlueG
CLTF
3.768
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.632
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.206
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
6.697
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.87

Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.65 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:1006.31
MW Contribution:9.51
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.501
3144293JTRSVLE
50/50
0.422
970535AG2-341 GEN
50/50
1.342
3152661PLYWOOD A
50/50
0.157
971489AH1-241 GEN
Solar/Wind Harmer
15.115
3146776BUCKING
Solar/Wind Harmer
1.047
3146776BUCKING
Solar/Wind Harmer
0.085
315821AE2-092 GEN
Solar/Wind Harmer
0.012
970301AG2-198 GEN
Solar/Wind Harmer
7.46
971741AH1-377 GEN
Solar/Wind Harmer
16.096
3147133PAMPLIN
Solar/Wind Harmer
0.158
3151931BEARGRDN S1
50/50
3.824
3151911BEARGRDN G1
50/50
2.963
3144293JTRSVLE
50/50
0.501
3151531CLOVER1
50/50
2.179
3151601KERR 3
50/50
0.134
3151581KERR 1
50/50
0.048
316336AC2-165 C
Solar/Wind Harmer
0.025
970937AG2-583 GEN
Solar/Wind Harmer
28.676
972003AH1-546 GEN
Solar/Wind Harmer
13.102
971377AH1-170 GEN
Solar/Wind Harmer
3.023
3147623JAMES R
Solar/Wind Harmer
0.657
3147133PAMPLIN
Solar/Wind Harmer
0.126
958211AF2-115 GEN
Solar/Wind Harmer
1.781
963191AG1-168 GEN
Solar/Wind Harmer
0.594
316034AC1-036 C
Solar/Wind Harmer
0.009
970323AG2-213 GEN
Solar/Wind Harmer
5.129
971775AH1-396 GEN
Solar/Wind Harmer
0.192
970099AG2-077 GEN
Solar/Wind Harmer
11.625
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.75
964791AG1-342 GEN
Solar/Wind Harmer
1.467
3146843MT LREL
Solar/Wind Harmer
0.076
3146843MT LREL
Solar/Wind Harmer
0.076
939181AE1-148 GEN
Solar/Wind Harmer
3.307
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
963171AG1-166 GEN
Solar/Wind Harmer
0.792
971563AH1-280 GEN
Solar/Wind Harmer
1.583
970685AG2-442 GEN
Solar/Wind Harmer
10.06
962491AG1-098 GEN
Solar/Wind Harmer
7.008
315693AD1-088 GEN
Solar/Wind Harmer
5.758
957481AF2-042 GEN
Solar/Wind Harmer
29.062
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.003
970401AG2-262 GEN
Solar/Wind Harmer
0.448
316003AC1-222 GEN
Solar/Wind Harmer
0.002
972205AH1-687 GEN
50/50
14.45
3151541CLOVER2
50/50
2.169
3151611KERR 4
50/50
0.134
3151621KERR 5
50/50
0.134
3151631KERR 6
50/50
0.134
3151641KERR 7
50/50
0.134
971447AH1-217 GEN
Solar/Wind Harmer
8.134
971845AH1-439 GEN
Solar/Wind Harmer
11.699
970285AG2-188 GEN
Solar/Wind Harmer
19.821
270494AE1-108_GEN
Solar/Wind Harmer
2.719
315657AE1-056 GEN
Solar/Wind Harmer
5.448
946301AF1-294 GEN
Solar/Wind Harmer
2.929
961791AG1-021 GEN
Solar/Wind Harmer
1.425
970683AG2-441 GEN
Solar/Wind Harmer
8.983
970681AG2-440 GEN
Solar/Wind Harmer
7.186
3144303KENBRDG
Solar/Wind Harmer
0.096
971443AH1-215 GEN
Solar/Wind Harmer
1.998
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.187
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.068
3147243WELCO
Solar/Wind Harmer
0.043
970865AG2-541 GEN
Solar/Wind Harmer
2.117
316123AC1-075 GEN
Solar/Wind Harmer
0.077
970165AG2-112 GEN
Solar/Wind Harmer
0.456
970163AG2-111 GEN
Solar/Wind Harmer
0.435
316233AE1-074 FULL
Solar/Wind Helper
0.381
316312AB1-027
Solar/Wind Helper
0.218
316132AB2-190 GEN1
Solar/Wind Helper
0.644
3143226MDLTHAN
Solar/Wind Helper
0.301
3143526WINTERP
Solar/Wind Helper
1.298
3142543TWELFTH
Solar/Wind Helper
0.014
3142416OLDCHRC
Solar/Wind Helper
0.298
3142416OLDCHRC
Solar/Wind Helper
0.114
316458AB2-190 GEN2
Solar/Wind Helper
0.644
3142433PROV 92
Solar/Wind Helper
0.447
3143526WINTERP
Solar/Wind Helper
1.298
316240AF1-291 C
Solar/Wind Helper
0.163
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.157
316075AC2-137 C
Solar/Wind Helper
0.174
3151921BEARGRDN G2
50/50
2.963
3144293JTRSVLE
50/50
0.501
970413AG2-270 GEN
50/50
9.511
966251AG1-494 GEN
50/50
1.191
3151591KERR 2
50/50
0.134
970221AG2-151 GEN
Solar/Wind Harmer
15.115
3146776BUCKING
Solar/Wind Harmer
0.094
3146926FARMVIL
Solar/Wind Harmer
0.129
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
1.865
3147133PAMPLIN
Solar/Wind Harmer
0.496
971193AH1-056 GEN
Solar/Wind Harmer
9.619
963181AG1-167 GEN
Solar/Wind Harmer
0.594
959311AF2-222 GEN
Solar/Wind Harmer
11.056
970257AG2-171 GEN
Solar/Wind Harmer
3.847
315785AD2-033 C
Solar/Wind Harmer
0.931
958131AF2-107 GEN
Solar/Wind Harmer
2.944
316478AD1-087 GEN
Solar/Wind Harmer
0.355
316486AD2-202 GEN
Solar/Wind Harmer
0.104
964241AG1-285 GEN
Solar/Wind Harmer
6.611
316131AB2-060 GEN
Solar/Wind Harmer
0.283
3148013FISHERV
Solar/Wind Harmer
0.07
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.916
971683AH1-343 GEN
Solar/Wind Harmer
2.335
316313AB2-026
Solar/Wind Helper
1.246
316258AE1-075 C
Solar/Wind Helper
1.121
316405AF2-144 C
Solar/Wind Helper
0.934
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.714
315839AE2-212 C
Solar/Wind Helper
0.156
CPLELTFEXP_CPLE->PJM
CLTF
0.579
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.662
LAGNLTFEXP_LAGN->PJM
CLTF
1.347
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.952
TVALTFEXP_TVA->PJM
CLTF
0.702
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.157
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.592
MECLTFEXP_MEC->PJM
CLTF
1.02
SIGELTFEXP_SIGE->PJM
CLTF
0.033
NYPJM->LTFIMP_NY
CLTF
0.35
LGEELTFEXP_LGEE->PJM
CLTF
0.439
WECLTFEXP_WEC->PJM
CLTF
0.224

Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.22 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:1002.88
MW Contribution:9.51
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.501
3144293JTRSVLE
50/50
0.422
970535AG2-341 GEN
50/50
1.342
3152661PLYWOOD A
50/50
0.157
971489AH1-241 GEN
Solar/Wind Harmer
15.115
3146776BUCKING
Solar/Wind Harmer
1.047
3146776BUCKING
Solar/Wind Harmer
0.085
315821AE2-092 GEN
Solar/Wind Harmer
0.012
970301AG2-198 GEN
Solar/Wind Harmer
7.46
971741AH1-377 GEN
Solar/Wind Harmer
16.096
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.126
958211AF2-115 GEN
Solar/Wind Harmer
1.781
963191AG1-168 GEN
Solar/Wind Harmer
0.594
316034AC1-036 C
Solar/Wind Harmer
0.009
970323AG2-213 GEN
Solar/Wind Harmer
5.129
971775AH1-396 GEN
Solar/Wind Harmer
0.192
970933AG2-581 GEN
Solar/Wind Harmer
8.892
970099AG2-077 GEN
Solar/Wind Harmer
11.625
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.75
964791AG1-342 GEN
Solar/Wind Harmer
1.467
3146843MT LREL
Solar/Wind Harmer
0.076
3146843MT LREL
Solar/Wind Harmer
0.076
939181AE1-148 GEN
Solar/Wind Harmer
3.307
3143526WINTERP
Solar/Wind Helper
1.298
316240AF1-291 C
Solar/Wind Helper
0.163
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.157
316075AC2-137 C
Solar/Wind Helper
0.174
3151931BEARGRDN S1
50/50
3.824
3151911BEARGRDN G1
50/50
2.963
3144293JTRSVLE
50/50
0.501
3151531CLOVER1
50/50
2.179
3151601KERR 3
50/50
0.134
3151581KERR 1
50/50
0.048
316336AC2-165 C
Solar/Wind Harmer
0.025
970937AG2-583 GEN
Solar/Wind Harmer
28.676
972003AH1-546 GEN
Solar/Wind Harmer
13.102
971377AH1-170 GEN
Solar/Wind Harmer
3.023
3147623JAMES R
Solar/Wind Harmer
0.657
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
963171AG1-166 GEN
Solar/Wind Harmer
0.792
971563AH1-280 GEN
Solar/Wind Harmer
1.583
970685AG2-442 GEN
Solar/Wind Harmer
10.06
962491AG1-098 GEN
Solar/Wind Harmer
7.008
315693AD1-088 GEN
Solar/Wind Harmer
5.758
957481AF2-042 GEN
Solar/Wind Harmer
29.062
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.003
970401AG2-262 GEN
Solar/Wind Harmer
0.448
316003AC1-222 GEN
Solar/Wind Harmer
0.002
3143226MDLTHAN
Solar/Wind Helper
0.301
3143526WINTERP
Solar/Wind Helper
1.298
3142543TWELFTH
Solar/Wind Helper
0.014
3142416OLDCHRC
Solar/Wind Helper
0.298
3142416OLDCHRC
Solar/Wind Helper
0.114
316458AB2-190 GEN2
Solar/Wind Helper
0.644
3142433PROV 92
Solar/Wind Helper
0.447
3151921BEARGRDN G2
50/50
2.963
3144293JTRSVLE
50/50
0.501
970413AG2-270 GEN
50/50
9.511
966251AG1-494 GEN
50/50
1.191
3151591KERR 2
50/50
0.134
970221AG2-151 GEN
Solar/Wind Harmer
15.115
3146776BUCKING
Solar/Wind Harmer
0.094
3146926FARMVIL
Solar/Wind Harmer
0.129
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
1.865
3147133PAMPLIN
Solar/Wind Harmer
0.496
971193AH1-056 GEN
Solar/Wind Harmer
9.619
963181AG1-167 GEN
Solar/Wind Harmer
0.594
959311AF2-222 GEN
Solar/Wind Harmer
11.056
970257AG2-171 GEN
Solar/Wind Harmer
3.847
315785AD2-033 C
Solar/Wind Harmer
0.931
958131AF2-107 GEN
Solar/Wind Harmer
2.944
316478AD1-087 GEN
Solar/Wind Harmer
0.355
316486AD2-202 GEN
Solar/Wind Harmer
0.104
964241AG1-285 GEN
Solar/Wind Harmer
6.611
316131AB2-060 GEN
Solar/Wind Harmer
0.283
3148013FISHERV
Solar/Wind Harmer
0.07
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.916
971683AH1-343 GEN
Solar/Wind Harmer
2.335
316313AB2-026
Solar/Wind Helper
1.246
316258AE1-075 C
Solar/Wind Helper
1.121
316405AF2-144 C
Solar/Wind Helper
0.934
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.714
315839AE2-212 C
Solar/Wind Helper
0.156
972205AH1-687 GEN
50/50
14.45
3151541CLOVER2
50/50
2.169
3151611KERR 4
50/50
0.134
3151621KERR 5
50/50
0.134
3151631KERR 6
50/50
0.134
3151641KERR 7
50/50
0.134
971447AH1-217 GEN
Solar/Wind Harmer
8.134
971845AH1-439 GEN
Solar/Wind Harmer
11.699
970285AG2-188 GEN
Solar/Wind Harmer
19.821
270494AE1-108_GEN
Solar/Wind Harmer
2.719
315657AE1-056 GEN
Solar/Wind Harmer
5.448
946301AF1-294 GEN
Solar/Wind Harmer
2.929
961791AG1-021 GEN
Solar/Wind Harmer
1.425
970683AG2-441 GEN
Solar/Wind Harmer
8.983
970681AG2-440 GEN
Solar/Wind Harmer
7.186
3144303KENBRDG
Solar/Wind Harmer
0.096
971443AH1-215 GEN
Solar/Wind Harmer
1.998
971967AH1-528 GEN
Solar/Wind Harmer
17.782
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.187
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.068
3147243WELCO
Solar/Wind Harmer
0.043
970865AG2-541 GEN
Solar/Wind Harmer
2.117
316123AC1-075 GEN
Solar/Wind Harmer
0.077
970165AG2-112 GEN
Solar/Wind Harmer
0.456
970163AG2-111 GEN
Solar/Wind Harmer
0.435
316233AE1-074 FULL
Solar/Wind Helper
0.381
316312AB1-027
Solar/Wind Helper
0.218
316132AB2-190 GEN1
Solar/Wind Helper
0.644
CPLELTFEXP_CPLE->PJM
CLTF
0.579
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.662
LAGNLTFEXP_LAGN->PJM
CLTF
1.347
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.952
TVALTFEXP_TVA->PJM
CLTF
0.702
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.157
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.592
MECLTFEXP_MEC->PJM
CLTF
1.02
SIGELTFEXP_SIGE->PJM
CLTF
0.033
NYPJM->LTFIMP_NY
CLTF
0.35
LGEELTFEXP_LGEE->PJM
CLTF
0.439
WECLTFEXP_WEC->PJM
CLTF
0.224

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.1 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5539.41
MW Contribution:40.85
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
47.73
957481AF2-042 GEN
Solar/Wind Harmer
126.807
315693AD1-088 GEN
Solar/Wind Harmer
20.818
962491AG1-098 GEN
Solar/Wind Harmer
24.385
315687AD1-152 GEN
Solar/Wind Harmer
0.013
316003AC1-222 GEN
Solar/Wind Harmer
0.008
970401AG2-262 GEN
Solar/Wind Harmer
1.677
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
17.979
963171AG1-166 GEN
Solar/Wind Harmer
1.264
971563AH1-280 GEN
Solar/Wind Harmer
2.529
3146926FARMVIL
Solar/Wind Harmer
0.131
971065AG2-659 GEN
Solar/Wind Harmer
8.445
316129AC1-054 GEN
Solar/Wind Harmer
0.698
970223AG2-152 GEN
Solar/Wind Harmer
12.094
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.088
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.055
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.099
941801AE2-185 GEN
Solar/Wind Harmer
4.212
270030AE2-140 GEN
Solar/Wind Harmer
13.804
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.094
316359AB2-059 GEN
Solar/Wind Harmer
0.421
316049AB1-081 GEN
Solar/Wind Harmer
0.67
3142053HEARTS
Solar/Wind Harmer
0.206
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
970533AG2-339 GEN
50/50
66.733
970531AG2-338 GEN
50/50
26.693
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
44.982
970099AG2-077 GEN
Solar/Wind Harmer
50.723
971741AH1-377 GEN
Solar/Wind Harmer
33.569
970301AG2-198 GEN
Solar/Wind Harmer
13.228
3146843MT LREL
Solar/Wind Harmer
0.286
3146843MT LREL
Solar/Wind Harmer
0.286
964791AG1-342 GEN
Solar/Wind Harmer
5.488
316222AC1-221 GEN
Solar/Wind Harmer
1.175
962561AG1-105 GEN
Solar/Wind Harmer
13.485
939181AE1-148 GEN
Solar/Wind Harmer
12.41
313527AB2-043 GEN
Solar/Wind Harmer
0.003
970323AG2-213 GEN
Solar/Wind Harmer
10.445
971775AH1-396 GEN
Solar/Wind Harmer
0.392
316034AC1-036 C
Solar/Wind Harmer
0.018
958211AF2-115 GEN
Solar/Wind Harmer
2.845
963191AG1-168 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.234
3147133PAMPLIN
Solar/Wind Harmer
0.187
942751AE2-291 GEN
Solar/Wind Harmer
11.476
270013AE1-250 PV
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.546
3146776BUCKING
Solar/Wind Harmer
0.044
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.276
316263AC1-034 GEN
Solar/Wind Harmer
4.449
961601AG1-000A GEN
Solar/Wind Harmer
2.035
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
53.421
316478AD1-087 GEN
Solar/Wind Harmer
1.525
316486AD2-202 GEN
Solar/Wind Harmer
0.448
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
13.182
316283AC2-100 C
Solar/Wind Harmer
0.55
971683AH1-343 GEN
Solar/Wind Harmer
10.2
316131AB2-060 GEN
Solar/Wind Harmer
0.796
964241AG1-285 GEN
Solar/Wind Harmer
16.703
315785AD2-033 C
Solar/Wind Harmer
2.003
970257AG2-171 GEN
Solar/Wind Harmer
7.834
959311AF2-222 GEN
Solar/Wind Harmer
21.656
963181AG1-167 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.736
971193AH1-056 GEN
Solar/Wind Harmer
14.274
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.131
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
0.943
3146776BUCKING
Solar/Wind Harmer
0.049
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.212
270336AE1-100 GEN
Solar/Wind Harmer
0.003
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.117
971623AH1-311 GEN
Solar/Wind Harmer
0.234
961601AG1-000A GEN
Solar/Wind Harmer
8.141
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
941031AE2-094 GEN
Solar/Wind Harmer
138.271
944011AF1-069 GEN
Solar/Wind Harmer
45.178
970673AG2-436 GEN
Solar/Wind Harmer
149.315
970673AG2-436 GEN
Solar/Wind Harmer
99.544
971967AH1-528 GEN
Solar/Wind Harmer
95.481
970085AG2-068 GEN
Solar/Wind Harmer
31.82
970581AG2-369 GEN
Solar/Wind Harmer
27.365
3147173SINAI
Solar/Wind Harmer
0.309
3147243WELCO
Solar/Wind Harmer
0.193
316118AC1-105 GEN
Solar/Wind Harmer
0.768
970865AG2-541 GEN
Solar/Wind Harmer
9.078
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.118
3144303KENBRDG
Solar/Wind Harmer
0.196
970683AG2-441 GEN
Solar/Wind Harmer
16.053
970681AG2-440 GEN
Solar/Wind Harmer
12.842
946301AF1-294 GEN
Solar/Wind Harmer
4.678
961791AG1-021 GEN
Solar/Wind Harmer
2.276
315657AE1-056 GEN
Solar/Wind Harmer
8.085
316123AC1-075 GEN
Solar/Wind Harmer
0.315
970165AG2-112 GEN
Solar/Wind Harmer
1.87
970163AG2-111 GEN
Solar/Wind Harmer
1.784
970831AG2-522 GEN
Solar/Wind Harmer
7.35
970285AG2-188 GEN
Solar/Wind Harmer
12.402
971845AH1-439 GEN
Solar/Wind Harmer
6.507
270069AE2-166 C O1
Solar/Wind Harmer
0.004
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221
NYPJM->LTFIMP_NY
CLTF
2.382
LGEELTFEXP_LGEE->PJM
CLTF
2.675
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 51192_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51192_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.36 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:6013.11
MW Contribution:40.85
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
62.844
957481AF2-042 GEN
Solar/Wind Harmer
166.962
315693AD1-088 GEN
Solar/Wind Harmer
24.364
962491AG1-098 GEN
Solar/Wind Harmer
32.107
315687AD1-152 GEN
Solar/Wind Harmer
5.339
316003AC1-222 GEN
Solar/Wind Harmer
3.203
970401AG2-262 GEN
Solar/Wind Harmer
2.096
316237AB2-079_GEN
Solar/Wind Harmer
0.866
970685AG2-442 GEN
Solar/Wind Harmer
23.673
963171AG1-166 GEN
Solar/Wind Harmer
3.329
971563AH1-280 GEN
Solar/Wind Harmer
3.329
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.119
316129AC1-054 GEN
Solar/Wind Harmer
1.828
970223AG2-152 GEN
Solar/Wind Harmer
17.247
270016AE1-250 BESS
Solar/Wind Harmer
2.846
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.591
316322AB2-045
Solar/Wind Harmer
0.516
3146776BUCKING
Solar/Wind Harmer
-0.006
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.545
270030AE2-140 GEN
Solar/Wind Harmer
19.786
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.774
316049AB1-081 GEN
Solar/Wind Harmer
1.419
3142053HEARTS
Solar/Wind Harmer
0.155
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
941031AE2-094 GEN
Solar/Wind Harmer
158.157
944011AF1-069 GEN
Solar/Wind Harmer
49.556
970673AG2-436 GEN
Solar/Wind Harmer
165.209
970673AG2-436 GEN
Solar/Wind Harmer
83.65
971967AH1-528 GEN
Solar/Wind Harmer
126.052
970085AG2-068 GEN
Solar/Wind Harmer
41.896
970581AG2-369 GEN
Solar/Wind Harmer
36.031
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.3
970865AG2-541 GEN
Solar/Wind Harmer
11.953
316239AB2-077_GEN
Solar/Wind Harmer
0.866
316238AB2-078_GEN
Solar/Wind Harmer
0.866
971443AH1-215 GEN
Solar/Wind Harmer
5.422
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.136
970681AG2-440 GEN
Solar/Wind Harmer
16.909
946301AF1-294 GEN
Solar/Wind Harmer
6.825
961791AG1-021 GEN
Solar/Wind Harmer
3.329
270455AD2-022 GEN
Solar/Wind Harmer
4.714
270457AD2-023 GEN
Solar/Wind Harmer
2.39
315657AE1-056 GEN
Solar/Wind Harmer
9.877
316123AC1-075 GEN
Solar/Wind Harmer
2.797
970165AG2-112 GEN
Solar/Wind Harmer
2.462
970163AG2-111 GEN
Solar/Wind Harmer
2.349
970831AG2-522 GEN
Solar/Wind Harmer
9.678
970285AG2-188 GEN
Solar/Wind Harmer
15.412
971845AH1-439 GEN
Solar/Wind Harmer
8.567
270069AE2-166 C O1
Solar/Wind Harmer
2.422
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
168.81
316478AD1-087 GEN
Solar/Wind Harmer
4.25
316486AD2-202 GEN
Solar/Wind Harmer
1.245
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
1.046
960061AF2-297 GEN
Solar/Wind Harmer
17.357
316283AC2-100 C
Solar/Wind Harmer
2.974
971683AH1-343 GEN
Solar/Wind Harmer
13.43
316131AB2-060 GEN
Solar/Wind Harmer
3.068
964241AG1-285 GEN
Solar/Wind Harmer
21.992
315785AD2-033 C
Solar/Wind Harmer
6.274
970257AG2-171 GEN
Solar/Wind Harmer
10.314
959311AF2-222 GEN
Solar/Wind Harmer
28.571
963181AG1-167 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.462
942461AE2-259 GEN
Solar/Wind Harmer
3.832
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.378
270197AD1-017 GEN1
Solar/Wind Harmer
1.68
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.844
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.545
270336AE1-100 GEN
Solar/Wind Harmer
1.569
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
5.12
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
970533AG2-339 GEN
50/50
66.733
970531AG2-338 GEN
50/50
26.693
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
59.226
970099AG2-077 GEN
Solar/Wind Harmer
66.785
971741AH1-377 GEN
Solar/Wind Harmer
44.199
970301AG2-198 GEN
Solar/Wind Harmer
17.416
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.86
316222AC1-221 GEN
Solar/Wind Harmer
3.218
962561AG1-105 GEN
Solar/Wind Harmer
17.755
939181AE1-148 GEN
Solar/Wind Harmer
16.34
313527AB2-043 GEN
Solar/Wind Harmer
4.631
970323AG2-213 GEN
Solar/Wind Harmer
13.752
971775AH1-396 GEN
Solar/Wind Harmer
1.958
316034AC1-036 C
Solar/Wind Harmer
0.51
958211AF2-115 GEN
Solar/Wind Harmer
4.162
963191AG1-168 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.11
270013AE1-250 PV
Solar/Wind Harmer
2.846
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.4
316197AC1-042 GEN
Solar/Wind Harmer
1.819
942671AE2-283 GEN
Solar/Wind Harmer
4.898
316263AC1-034 GEN
Solar/Wind Harmer
6.166
961601AG1-000A GEN
Solar/Wind Harmer
5.056
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221
NYPJM->LTFIMP_NY
CLTF
2.382
LGEELTFEXP_LGEE->PJM
CLTF
2.675
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 51172_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51172_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.82 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5986.29
MW Contribution:40.64
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
11.056
3151051BRUNSWICKS1
50/50
17.38
3151021BRUNSWICKG1
50/50
8.374
971451AH1-221 GEN
50/50
25.435
3151531CLOVER1
50/50
9.312
3151601KERR 3
50/50
0.538
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.8
971629AH1-314 GEN
50/50
17.875
3151561HALLBR1
50/50
0.366
970919AG2-571 GEN
Solar/Wind Harmer
21.227
970087AG2-069 GEN
Solar/Wind Harmer
62.431
957481AF2-042 GEN
Solar/Wind Harmer
166.01
315693AD1-088 GEN
Solar/Wind Harmer
24.233
962491AG1-098 GEN
Solar/Wind Harmer
31.935
315687AD1-152 GEN
Solar/Wind Harmer
5.313
316003AC1-222 GEN
Solar/Wind Harmer
3.193
970401AG2-262 GEN
Solar/Wind Harmer
2.094
316237AB2-079_GEN
Solar/Wind Harmer
0.868
970685AG2-442 GEN
Solar/Wind Harmer
23.682
963171AG1-166 GEN
Solar/Wind Harmer
3.328
971563AH1-280 GEN
Solar/Wind Harmer
3.328
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.224
316129AC1-054 GEN
Solar/Wind Harmer
1.849
970223AG2-152 GEN
Solar/Wind Harmer
17.201
270016AE1-250 BESS
Solar/Wind Harmer
2.839
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.577
316322AB2-045
Solar/Wind Harmer
0.514
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.53
270030AE2-140 GEN
Solar/Wind Harmer
19.734
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.817
316049AB1-081 GEN
Solar/Wind Harmer
1.454
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.785
316375AC2-012 GEN
Solar/Wind Helper
1.014
3145336SMITFLD
Solar/Wind Helper
1.482
316388AE2-253 GEN
Solar/Wind Helper
1.397
3146456SLIGO L269
Solar/Wind Helper
0.359
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.402
316159AE1-175 C
Solar/Wind Helper
0.529
316381AD1-082 GEN
Solar/Wind Helper
1.758
316458AB2-190 GEN2
Solar/Wind Helper
1.933
3141766HARMONY
Solar/Wind Helper
0.065
3138133OCRAN
Solar/Wind Helper
0.193
3142433PROV 92
Solar/Wind Helper
1.275
3142543TWELFTH
Solar/Wind Helper
0.029
964211AG1-282 GEN
Solar/Wind Helper
0.412
3141726DUNNSVL
Solar/Wind Helper
1.222
315244AE2-183_ST
50/50
19.115
963041AG1-153 GEN
50/50
16.957
3151541CLOVER2
50/50
9.268
3151611KERR 4
50/50
0.538
3151621KERR 5
50/50
0.538
3151631KERR 6
50/50
0.538
3151641KERR 7
50/50
0.538
3146516WINFALL
Solar/Wind Helper
0.961
3146516WINFALL
Solar/Wind Helper
0.297
316337AD2-073 GEN
Solar/Wind Helper
0.448
3142416OLDCHRC
Solar/Wind Helper
0.759
3142416OLDCHRC
Solar/Wind Helper
0.291
3143526WINTERP
Solar/Wind Helper
1.499
3143226MDLTHAN
Solar/Wind Helper
0.284
315800Z1-036_GEN1
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
941031AE2-094 GEN
Solar/Wind Harmer
157.012
944011AF1-069 GEN
Solar/Wind Harmer
49.197
970673AG2-436 GEN
Solar/Wind Harmer
164.043
970673AG2-436 GEN
Solar/Wind Harmer
83.06
971967AH1-528 GEN
Solar/Wind Harmer
125.223
970085AG2-068 GEN
Solar/Wind Harmer
41.62
970581AG2-369 GEN
Solar/Wind Harmer
35.794
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.295
970865AG2-541 GEN
Solar/Wind Harmer
11.917
316239AB2-077_GEN
Solar/Wind Harmer
0.868
316238AB2-078_GEN
Solar/Wind Harmer
0.868
971443AH1-215 GEN
Solar/Wind Harmer
5.428
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.145
970681AG2-440 GEN
Solar/Wind Harmer
16.916
946301AF1-294 GEN
Solar/Wind Harmer
6.823
961791AG1-021 GEN
Solar/Wind Harmer
3.328
270455AD2-022 GEN
Solar/Wind Harmer
4.701
270457AD2-023 GEN
Solar/Wind Harmer
2.384
315657AE1-056 GEN
Solar/Wind Harmer
9.869
316123AC1-075 GEN
Solar/Wind Harmer
2.789
970165AG2-112 GEN
Solar/Wind Harmer
2.455
970163AG2-111 GEN
Solar/Wind Harmer
2.342
970831AG2-522 GEN
Solar/Wind Harmer
9.813
970285AG2-188 GEN
Solar/Wind Harmer
15.354
971845AH1-439 GEN
Solar/Wind Harmer
8.535
270069AE2-166 C O1
Solar/Wind Harmer
2.415
319010AE1-072 C
Solar/Wind Helper
4.079
3143316POE
Solar/Wind Helper
1.407
316305AF2-043 C
Solar/Wind Helper
0.473
316369SG1_INVT
Solar/Wind Helper
1.664
957831AF2-077 GEN
Solar/Wind Helper
0.466
316132AB2-190 GEN1
Solar/Wind Helper
1.933
316349AD2-085 GEN
Solar/Wind Helper
1.523
3151031BRUNSWICKG2
50/50
8.374
970413AG2-270 GEN
50/50
40.637
3151591KERR 2
50/50
0.538
3144293JTRSVLE
50/50
0.8
970917AG2-570 GEN
Solar/Wind Harmer
167.695
316478AD1-087 GEN
Solar/Wind Harmer
4.227
316486AD2-202 GEN
Solar/Wind Harmer
1.238
970909AG2-566 GEN
Solar/Wind Harmer
3.291
316248AF1-058 C
Solar/Wind Harmer
1.043
960061AF2-297 GEN
Solar/Wind Harmer
17.305
316283AC2-100 C
Solar/Wind Harmer
2.965
971683AH1-343 GEN
Solar/Wind Harmer
13.39
313526AB2-022
Solar/Wind Helper
0.505
957601AF2-054 GEN
Solar/Wind Helper
0.438
3141873WAN 176
Solar/Wind Helper
0.065
315662AE1-191 GEN
Solar/Wind Helper
1.747
315666AE1-190 GEN
Solar/Wind Helper
0.437
316059AD1-063 C
Solar/Wind Helper
0.326
3141913WHIT STONE
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3138133OCRAN
Solar/Wind Helper
0.097
3143873LANEXA
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.128
316321Z2-027
Solar/Wind Helper
0.487
3145176PASQUOTANK
Solar/Wind Helper
0.198
3141813NORNECK
Solar/Wind Helper
0.304
316312AB1-027
Solar/Wind Helper
0.556
316233AE1-074 FULL
Solar/Wind Helper
0.44
316223AC1-118
Solar/Wind Helper
0.438
316315AB2-025 C
Solar/Wind Helper
0.418
315611Z1-036_GEN2
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
3130156CHOWAN
Solar/Wind Helper
0.226
970533AG2-339 GEN
50/50
66.25
970531AG2-338 GEN
50/50
26.5
315242AE2-183_GT2
50/50
11.056
315241AE2-183_GT1
50/50
10.988
972185AH1-677 GEN
50/50
39.858
3151041BRUNSWICKG3
50/50
8.374
972187AH1-678 GEN
50/50
19.217
3152661PLYWOOD A
50/50
0.67
970535AG2-341 GEN
50/50
4.577
3144293JTRSVLE
50/50
0.8
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
58.849
970099AG2-077 GEN
Solar/Wind Harmer
66.404
971741AH1-377 GEN
Solar/Wind Harmer
43.978
970301AG2-198 GEN
Solar/Wind Harmer
17.332
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.854
316222AC1-221 GEN
Solar/Wind Harmer
3.208
962561AG1-105 GEN
Solar/Wind Harmer
17.747
939181AE1-148 GEN
Solar/Wind Harmer
16.378
313527AB2-043 GEN
Solar/Wind Harmer
4.643
970323AG2-213 GEN
Solar/Wind Harmer
13.768
971775AH1-396 GEN
Solar/Wind Harmer
1.961
316034AC1-036 C
Solar/Wind Harmer
0.511
958211AF2-115 GEN
Solar/Wind Harmer
4.16
963191AG1-168 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.066
270013AE1-250 PV
Solar/Wind Harmer
2.839
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.394
316197AC1-042 GEN
Solar/Wind Harmer
1.815
942671AE2-283 GEN
Solar/Wind Harmer
4.885
316263AC1-034 GEN
Solar/Wind Harmer
6.316
961601AG1-000A GEN
Solar/Wind Harmer
5.186
316036AC1-147 C
Solar/Wind Helper
0.59
3142956BIRDNECK
Solar/Wind Helper
0.259
316316AC1-027 C
Solar/Wind Helper
0.606
316185AD1-033 GEN
Solar/Wind Helper
1.799
3145506HICKORY
Solar/Wind Helper
1.507
3145506HICKORY
Solar/Wind Helper
0.904
3145506HICKORY
Solar/Wind Helper
0.226
316236AE1-162_GEN
Solar/Wind Helper
0.498
316339AD2-160 GEN
Solar/Wind Helper
1.397
316018AA1-139 ULT2
Solar/Wind Helper
1.567
316017AA1-139 ULT1
Solar/Wind Helper
1.665
3137176SLIGO L2192
Solar/Wind Helper
1.432
3130086AYDLETT
Solar/Wind Helper
1.421
316033AB2-134 GEN
Solar/Wind Helper
1.19
315697AD1-025 GEN
Solar/Wind Helper
3.953
3146386ELIZ CT
Solar/Wind Helper
0.331
316240AF1-291 C
Solar/Wind Helper
0.444
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.318
316075AC2-137 C
Solar/Wind Helper
0.467
316077AC2-138 C
Solar/Wind Helper
0.286
316431W1029_GEN1
Solar/Wind Helper
1.225
316433W1029_GEN2
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3143526WINTERP
Solar/Wind Helper
1.499
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
966871AG1-558 GEN
Solar/Wind Helper
0.374
3144356SAPONY
Solar/Wind Helper
0.492
316468AD1-105 GEN
Solar/Wind Helper
1.305
316131AB2-060 GEN
Solar/Wind Harmer
3.076
964241AG1-285 GEN
Solar/Wind Harmer
22.038
315785AD2-033 C
Solar/Wind Harmer
6.282
970257AG2-171 GEN
Solar/Wind Harmer
10.326
959311AF2-222 GEN
Solar/Wind Harmer
28.597
963181AG1-167 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.449
942461AE2-259 GEN
Solar/Wind Harmer
3.824
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.375
270197AD1-017 GEN1
Solar/Wind Harmer
1.676
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.834
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.53
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.564
961601AG1-000A GEN
Solar/Wind Harmer
5.252
315773AC2-141 GEN
Solar/Wind Helper
9.163
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.058
3145336SMITFLD
Solar/Wind Helper
0.148
3146456SLIGO L269
Solar/Wind Helper
0.359
316382AG1-145 C
Solar/Wind Helper
0.469
315839AE2-212 C
Solar/Wind Helper
0.457
316320Y1-086
Solar/Wind Helper
0.148
316156AD2-030 GEN
Solar/Wind Helper
0.492
316280AD1-041 GEN
Solar/Wind Helper
1.092
3142946ENON
Solar/Wind Helper
0.105
316484AD2-074 GEN
Solar/Wind Helper
0.607
316404AE1-155 C
Solar/Wind Helper
2.624
316435W1029_GEN3
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3141906WESTMOR
Solar/Wind Helper
0.115
3146626S HERTFORD
Solar/Wind Helper
0.28
316473AC1-191 GEN
Solar/Wind Helper
1.696
3145273HOLLAND
Solar/Wind Helper
0.188
966881AG1-559 GEN
Solar/Wind Helper
0.329
3146376EDENTON
Solar/Wind Helper
0.226
CPLELTFEXP_CPLE->PJM
CLTF
19.708
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.004
LAGNLTFEXP_LAGN->PJM
CLTF
14.626
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.161
TVALTFEXP_TVA->PJM
CLTF
7.294
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.554
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.081
MECLTFEXP_MEC->PJM
CLTF
7.343
SIGELTFEXP_SIGE->PJM
CLTF
0.22
NYPJM->LTFIMP_NY
CLTF
2.38
LGEELTFEXP_LGEE->PJM
CLTF
2.666
WECLTFEXP_WEC->PJM
CLTF
1.395
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 511T544_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T544_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.15 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5902.9
MW Contribution:40.27
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
8.303
970413AG2-270 GEN
50/50
40.265
3151591KERR 2
50/50
0.532
3144293JTRSVLE
50/50
0.79
970917AG2-570 GEN
Solar/Wind Harmer
166.275
316478AD1-087 GEN
Solar/Wind Harmer
4.189
316486AD2-202 GEN
Solar/Wind Harmer
1.227
970909AG2-566 GEN
Solar/Wind Harmer
3.255
316248AF1-058 C
Solar/Wind Harmer
1.033
960061AF2-297 GEN
Solar/Wind Harmer
17.135
316283AC2-100 C
Solar/Wind Harmer
2.94
971683AH1-343 GEN
Solar/Wind Harmer
13.259
316131AB2-060 GEN
Solar/Wind Harmer
3.032
964241AG1-285 GEN
Solar/Wind Harmer
21.724
315785AD2-033 C
Solar/Wind Harmer
6.194
970257AG2-171 GEN
Solar/Wind Harmer
10.181
959311AF2-222 GEN
Solar/Wind Harmer
28.197
963181AG1-167 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.081
971193AH1-056 GEN
Solar/Wind Harmer
16.225
942461AE2-259 GEN
Solar/Wind Harmer
3.773
3146926FARMVIL
Solar/Wind Harmer
-0.014
270018AE2-047 C O1
Solar/Wind Harmer
1.363
270197AD1-017 GEN1
Solar/Wind Harmer
1.661
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.802
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.477
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.551
961601AG1-000A GEN
Solar/Wind Harmer
5.225
315773AC2-141 GEN
Solar/Wind Helper
8.525
315839AE2-212 C
Solar/Wind Helper
0.497
315243AE2-183_GT3
50/50
10.962
3151051BRUNSWICKS1
50/50
17.232
3151021BRUNSWICKG1
50/50
8.303
971451AH1-221 GEN
50/50
25.218
3151531CLOVER1
50/50
9.227
3151601KERR 3
50/50
0.532
3151581KERR 1
50/50
0.19
3144293JTRSVLE
50/50
0.79
971629AH1-314 GEN
50/50
17.731
3151561HALLBR1
50/50
0.363
970919AG2-571 GEN
Solar/Wind Harmer
21.047
970087AG2-069 GEN
Solar/Wind Harmer
61.902
957481AF2-042 GEN
Solar/Wind Harmer
164.509
315693AD1-088 GEN
Solar/Wind Harmer
24.007
962491AG1-098 GEN
Solar/Wind Harmer
31.634
315687AD1-152 GEN
Solar/Wind Harmer
5.265
316003AC1-222 GEN
Solar/Wind Harmer
3.162
970401AG2-262 GEN
Solar/Wind Harmer
2.07
316237AB2-079_GEN
Solar/Wind Harmer
0.856
970685AG2-442 GEN
Solar/Wind Harmer
23.354
963171AG1-166 GEN
Solar/Wind Harmer
3.283
971563AH1-280 GEN
Solar/Wind Harmer
3.283
3146926FARMVIL
Solar/Wind Harmer
-0.014
971065AG2-659 GEN
Solar/Wind Harmer
11.094
316129AC1-054 GEN
Solar/Wind Harmer
1.827
970223AG2-152 GEN
Solar/Wind Harmer
17.059
270016AE1-250 BESS
Solar/Wind Harmer
2.815
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.528
316322AB2-045
Solar/Wind Harmer
0.506
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.477
270030AE2-140 GEN
Solar/Wind Harmer
19.567
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.809
316049AB1-081 GEN
Solar/Wind Harmer
1.448
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.244
316381AD1-082 GEN
Solar/Wind Helper
1.747
316375AC2-012 GEN
Solar/Wind Helper
0.879
3145336SMITFLD
Solar/Wind Helper
1.331
316458AB2-190 GEN2
Solar/Wind Helper
1.893
316159AE1-175 C
Solar/Wind Helper
0.497
316388AE2-253 GEN
Solar/Wind Helper
1.201
3142433PROV 92
Solar/Wind Helper
1.254
3142543TWELFTH
Solar/Wind Helper
0.03
3141766HARMONY
Solar/Wind Helper
0.062
3146456SLIGO L269
Solar/Wind Helper
0.308
3138133OCRAN
Solar/Wind Helper
0.185
316072AD1-144
Solar/Wind Helper
0.35
316246AF1-032 C
Solar/Wind Helper
0.342
964211AG1-282 GEN
Solar/Wind Helper
0.397
3141726DUNNSVL
Solar/Wind Helper
1.179
3143526WINTERP
Solar/Wind Helper
1.519
3142416OLDCHRC
Solar/Wind Helper
0.752
3143226MDLTHAN
Solar/Wind Helper
0.289
3142416OLDCHRC
Solar/Wind Helper
0.288
316337AD2-073 GEN
Solar/Wind Helper
0.434
3146516WINFALL
Solar/Wind Helper
0.813
3146516WINFALL
Solar/Wind Helper
0.251
970533AG2-339 GEN
50/50
65.686
970531AG2-338 GEN
50/50
26.274
315242AE2-183_GT2
50/50
10.962
315241AE2-183_GT1
50/50
10.894
972185AH1-677 GEN
50/50
39.518
3151041BRUNSWICKG3
50/50
8.303
972187AH1-678 GEN
50/50
19.053
3152661PLYWOOD A
50/50
0.663
970535AG2-341 GEN
50/50
4.519
3144293JTRSVLE
50/50
0.79
3144293JTRSVLE
50/50
0.665
970933AG2-581 GEN
Solar/Wind Harmer
58.334
970099AG2-077 GEN
Solar/Wind Harmer
65.804
971741AH1-377 GEN
Solar/Wind Harmer
43.523
970301AG2-198 GEN
Solar/Wind Harmer
17.145
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.775
316222AC1-221 GEN
Solar/Wind Harmer
3.182
962561AG1-105 GEN
Solar/Wind Harmer
17.536
939181AE1-148 GEN
Solar/Wind Harmer
16.186
313527AB2-043 GEN
Solar/Wind Harmer
4.576
970323AG2-213 GEN
Solar/Wind Harmer
13.574
971775AH1-396 GEN
Solar/Wind Harmer
1.933
316034AC1-036 C
Solar/Wind Harmer
0.503
958211AF2-115 GEN
Solar/Wind Harmer
4.103
963191AG1-168 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
14.918
270013AE1-250 PV
Solar/Wind Harmer
2.815
3146776BUCKING
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.37
316197AC1-042 GEN
Solar/Wind Harmer
1.797
942671AE2-283 GEN
Solar/Wind Harmer
4.838
316263AC1-034 GEN
Solar/Wind Harmer
6.29
961601AG1-000A GEN
Solar/Wind Harmer
5.16
316240AF1-291 C
Solar/Wind Helper
0.471
316036AC1-147 C
Solar/Wind Helper
0.511
316236AE1-162_GEN
Solar/Wind Helper
0.447
316316AC1-027 C
Solar/Wind Helper
0.524
3142956BIRDNECK
Solar/Wind Helper
0.223
316033AB2-134 GEN
Solar/Wind Helper
1.137
315697AD1-025 GEN
Solar/Wind Helper
3.779
316185AD1-033 GEN
Solar/Wind Helper
1.551
3145506HICKORY
Solar/Wind Helper
1.298
3145506HICKORY
Solar/Wind Helper
0.779
3145506HICKORY
Solar/Wind Helper
0.195
3144356SAPONY
Solar/Wind Helper
0.581
316339AD2-160 GEN
Solar/Wind Helper
1.201
316018AA1-139 ULT2
Solar/Wind Helper
1.346
316017AA1-139 ULT1
Solar/Wind Helper
1.43
3142946ENON
Solar/Wind Helper
0.031
3137176SLIGO L2192
Solar/Wind Helper
1.229
3130086AYDLETT
Solar/Wind Helper
1.219
316487AF1-042 GEN
Solar/Wind Helper
0.305
316075AC2-137 C
Solar/Wind Helper
0.459
316077AC2-138 C
Solar/Wind Helper
0.276
3143526WINTERP
Solar/Wind Helper
1.519
3146386ELIZ CT
Solar/Wind Helper
0.283
966871AG1-558 GEN
Solar/Wind Helper
0.376
316468AD1-105 GEN
Solar/Wind Helper
1.308
316431W1029_GEN1
Solar/Wind Helper
1.037
316433W1029_GEN2
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146626S HERTFORD
Solar/Wind Helper
0.236
3146626S HERTFORD
Solar/Wind Helper
0.236
315244AE2-183_ST
50/50
18.952
963041AG1-153 GEN
50/50
16.812
3151541CLOVER2
50/50
9.183
3151611KERR 4
50/50
0.532
3151621KERR 5
50/50
0.532
3151631KERR 6
50/50
0.532
3151641KERR 7
50/50
0.532
941031AE2-094 GEN
Solar/Wind Harmer
155.676
944011AF1-069 GEN
Solar/Wind Harmer
48.778
970673AG2-436 GEN
Solar/Wind Harmer
162.646
970673AG2-436 GEN
Solar/Wind Harmer
82.352
971967AH1-528 GEN
Solar/Wind Harmer
124.141
970085AG2-068 GEN
Solar/Wind Harmer
41.268
970581AG2-369 GEN
Solar/Wind Harmer
35.491
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.271
970865AG2-541 GEN
Solar/Wind Harmer
11.801
316239AB2-077_GEN
Solar/Wind Harmer
0.856
316238AB2-078_GEN
Solar/Wind Harmer
0.856
971443AH1-215 GEN
Solar/Wind Harmer
5.352
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
20.851
970681AG2-440 GEN
Solar/Wind Harmer
16.681
946301AF1-294 GEN
Solar/Wind Harmer
6.73
961791AG1-021 GEN
Solar/Wind Harmer
3.283
270455AD2-022 GEN
Solar/Wind Harmer
4.664
270457AD2-023 GEN
Solar/Wind Harmer
2.365
315657AE1-056 GEN
Solar/Wind Harmer
9.735
316123AC1-075 GEN
Solar/Wind Harmer
2.761
970165AG2-112 GEN
Solar/Wind Harmer
2.431
970163AG2-111 GEN
Solar/Wind Harmer
2.319
970831AG2-522 GEN
Solar/Wind Harmer
9.696
970285AG2-188 GEN
Solar/Wind Harmer
15.118
971845AH1-439 GEN
Solar/Wind Harmer
8.397
270069AE2-166 C O1
Solar/Wind Harmer
2.394
3143316POE
Solar/Wind Helper
1.57
316132AB2-190 GEN1
Solar/Wind Helper
1.893
316369SG1_INVT
Solar/Wind Helper
1.59
957831AF2-077 GEN
Solar/Wind Helper
0.437
316315AB2-025 C
Solar/Wind Helper
0.494
957601AF2-054 GEN
Solar/Wind Helper
0.418
3141873WAN 176
Solar/Wind Helper
0.062
315662AE1-191 GEN
Solar/Wind Helper
1.674
315666AE1-190 GEN
Solar/Wind Helper
0.419
3143873LANEXA
Solar/Wind Helper
0.186
316059AD1-063 C
Solar/Wind Helper
0.312
3141913WHIT STONE
Solar/Wind Helper
0.309
3138133OCRAN
Solar/Wind Helper
0.093
3141783LANCAST
Solar/Wind Helper
0.184
3141783LANCAST
Solar/Wind Helper
0.123
319010AE1-072 C
Solar/Wind Helper
3.5
316349AD2-085 GEN
Solar/Wind Helper
1.396
316305AF2-043 C
Solar/Wind Helper
0.402
3141813NORNECK
Solar/Wind Helper
0.293
316233AE1-074 FULL
Solar/Wind Helper
0.446
316312AB1-027
Solar/Wind Helper
0.55
313526AB2-022
Solar/Wind Helper
0.431
316223AC1-118
Solar/Wind Helper
0.424
3146486SUNBURY
Solar/Wind Helper
0.274
3146486SUNBURY
Solar/Wind Helper
0.274
316321Z2-027
Solar/Wind Helper
0.414
3145176PASQUOTANK
Solar/Wind Helper
0.168
3144536CHRHLND
Solar/Wind Helper
0.05
3144873MCLAUGH
Solar/Wind Helper
0.008
3145336SMITFLD
Solar/Wind Helper
0.133
316382AG1-145 C
Solar/Wind Helper
0.441
316156AD2-030 GEN
Solar/Wind Helper
0.47
3142946ENON
Solar/Wind Helper
0.104
316280AD1-041 GEN
Solar/Wind Helper
1.046
3146456SLIGO L269
Solar/Wind Helper
0.308
316484AD2-074 GEN
Solar/Wind Helper
0.583
316404AE1-155 C
Solar/Wind Helper
2.523
316320Y1-086
Solar/Wind Helper
0.126
316473AC1-191 GEN
Solar/Wind Helper
1.704
3141906WESTMOR
Solar/Wind Helper
0.111
316435W1029_GEN3
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
966881AG1-559 GEN
Solar/Wind Helper
0.328
3146626S HERTFORD
Solar/Wind Helper
0.236
CPLELTFEXP_CPLE->PJM
CLTF
19.58
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.279
LAGNLTFEXP_LAGN->PJM
CLTF
14.499
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.842
TVALTFEXP_TVA->PJM
CLTF
7.231
CBM West 1LTFEXP_CBM-W1->PJM
CBM
48.979
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.858
MECLTFEXP_MEC->PJM
CLTF
7.267
SIGELTFEXP_SIGE->PJM
CLTF
0.218
NYPJM->LTFIMP_NY
CLTF
2.38
LGEELTFEXP_LGEE->PJM
CLTF
2.637
WECLTFEXP_WEC->PJM
CLTF
1.38
AG2-052LTFEXP_AG2-052->PJM
LTF
0.074
AH1-155LTFEXP_AH1-155->PJM
LTF
0.111

Details for AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.76 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:673.04
MW Contribution:29.36
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
971967AH1-528 GEN
Solar/Wind Harmer
55.717
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
316118AC1-105 GEN
Solar/Wind Harmer
0.376
970865AG2-541 GEN
Solar/Wind Harmer
4.593
316123AC1-075 GEN
Solar/Wind Harmer
0.152
970165AG2-112 GEN
Solar/Wind Harmer
0.903
970163AG2-111 GEN
Solar/Wind Harmer
0.862
970831AG2-522 GEN
Solar/Wind Harmer
4.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
971629AH1-314 GEN
50/50
5.006
962491AG1-098 GEN
Solar/Wind Harmer
22.331
315693AD1-088 GEN
Solar/Wind Harmer
18.25
957481AF2-042 GEN
Solar/Wind Harmer
90.747
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.071
316129AC1-054 GEN
Solar/Wind Harmer
0.427
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
3152661PLYWOOD A
50/50
0.346
970535AG2-341 GEN
50/50
1.993
970933AG2-581 GEN
Solar/Wind Harmer
27.859
970099AG2-077 GEN
Solar/Wind Harmer
36.299
939181AE1-148 GEN
Solar/Wind Harmer
6.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.689
316222AC1-221 GEN
Solar/Wind Harmer
0.447
942751AE2-291 GEN
Solar/Wind Harmer
5.336
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
316478AD1-087 GEN
Solar/Wind Harmer
1.094
316486AD2-202 GEN
Solar/Wind Harmer
0.321
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.01
971683AH1-343 GEN
Solar/Wind Harmer
5.256
316283AC2-100 C
Solar/Wind Harmer
0.206
316131AB2-060 GEN
Solar/Wind Harmer
0.208
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.2 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:658.38
MW Contribution:29.36
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
316118AC1-105 GEN
Solar/Wind Harmer
0.376
970865AG2-541 GEN
Solar/Wind Harmer
4.593
316123AC1-075 GEN
Solar/Wind Harmer
0.152
970165AG2-112 GEN
Solar/Wind Harmer
0.903
970163AG2-111 GEN
Solar/Wind Harmer
0.862
970831AG2-522 GEN
Solar/Wind Harmer
4.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
971629AH1-314 GEN
50/50
5.006
962491AG1-098 GEN
Solar/Wind Harmer
22.331
315693AD1-088 GEN
Solar/Wind Harmer
18.25
957481AF2-042 GEN
Solar/Wind Harmer
90.747
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.071
316129AC1-054 GEN
Solar/Wind Harmer
0.427
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
3152661PLYWOOD A
50/50
0.346
970535AG2-341 GEN
50/50
1.993
970099AG2-077 GEN
Solar/Wind Harmer
36.299
939181AE1-148 GEN
Solar/Wind Harmer
6.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.689
316222AC1-221 GEN
Solar/Wind Harmer
0.447
942751AE2-291 GEN
Solar/Wind Harmer
5.336
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
316478AD1-087 GEN
Solar/Wind Harmer
1.094
316486AD2-202 GEN
Solar/Wind Harmer
0.321
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.01
971683AH1-343 GEN
Solar/Wind Harmer
5.256
316283AC2-100 C
Solar/Wind Harmer
0.206
316131AB2-060 GEN
Solar/Wind Harmer
0.208
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.07 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:797.37
MW Contribution:29.41
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.708
3151611KERR 4
50/50
0.302
3151621KERR 5
50/50
0.302
3151631KERR 6
50/50
0.302
3151641KERR 7
50/50
0.302
971967AH1-528 GEN
Solar/Wind Harmer
73.672
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.131
970865AG2-541 GEN
Solar/Wind Harmer
6.075
316123AC1-075 GEN
Solar/Wind Harmer
1.358
970165AG2-112 GEN
Solar/Wind Harmer
1.195
970163AG2-111 GEN
Solar/Wind Harmer
1.14
970831AG2-522 GEN
Solar/Wind Harmer
6.069
316239AB2-077_GEN
Solar/Wind Harmer
0.274
316238AB2-078_GEN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Harmer
1.371
270457AD2-023 GEN
Solar/Wind Harmer
0.695
270494AE1-108_GEN
Solar/Wind Helper
2.769
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
970413AG2-270 GEN
50/50
29.414
3151591KERR 2
50/50
0.302
316478AD1-087 GEN
Solar/Wind Harmer
3.055
316486AD2-202 GEN
Solar/Wind Harmer
0.895
316248AF1-058 C
Solar/Wind Harmer
0.559
960061AF2-297 GEN
Solar/Wind Harmer
9.268
971683AH1-343 GEN
Solar/Wind Harmer
6.951
316283AC2-100 C
Solar/Wind Harmer
1.124
316131AB2-060 GEN
Solar/Wind Harmer
0.808
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.542
3147133PAMPLIN
Solar/Wind Helper
1.062
316313AB2-026
Solar/Wind Helper
0.243
316258AE1-075 C
Solar/Wind Helper
0.219
316405AF2-144 C
Solar/Wind Helper
0.182
3151531CLOVER1
50/50
6.74
3151601KERR 3
50/50
0.302
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.44
315693AD1-088 GEN
Solar/Wind Harmer
21.388
957481AF2-042 GEN
Solar/Wind Harmer
119.681
315687AD1-152 GEN
Solar/Wind Harmer
3.524
316003AC1-222 GEN
Solar/Wind Harmer
1.683
970401AG2-262 GEN
Solar/Wind Harmer
0.932
971065AG2-659 GEN
Solar/Wind Harmer
6.697
316129AC1-054 GEN
Solar/Wind Harmer
1.121
316237AB2-079_GEN
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Helper
0.44
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
1.003
3152661PLYWOOD A
50/50
0.348
970535AG2-341 GEN
50/50
2.001
970933AG2-581 GEN
Solar/Wind Harmer
36.739
970099AG2-077 GEN
Solar/Wind Harmer
47.872
939181AE1-148 GEN
Solar/Wind Harmer
8.421
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.05
962561AG1-105 GEN
Solar/Wind Harmer
7.525
316222AC1-221 GEN
Solar/Wind Harmer
1.236
942751AE2-291 GEN
Solar/Wind Harmer
7.063
313527AB2-043 GEN
Solar/Wind Harmer
1.361
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.338
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.919
CPLELTFEXP_CPLE->PJM
CLTF
4.232
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.165
LAGNLTFEXP_LAGN->PJM
CLTF
2.703
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.92
TVALTFEXP_TVA->PJM
CLTF
1.347
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.6
MECLTFEXP_MEC->PJM
CLTF
1.297
SIGELTFEXP_SIGE->PJM
CLTF
0.038
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.461
WECLTFEXP_WEC->PJM
CLTF
0.241

Details for AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.03 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:797.08
MW Contribution:29.41
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.708
3151611KERR 4
50/50
0.302
3151621KERR 5
50/50
0.302
3151631KERR 6
50/50
0.302
3151641KERR 7
50/50
0.302
971967AH1-528 GEN
Solar/Wind Harmer
73.672
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.131
970865AG2-541 GEN
Solar/Wind Harmer
6.075
316123AC1-075 GEN
Solar/Wind Harmer
1.358
970165AG2-112 GEN
Solar/Wind Harmer
1.195
970163AG2-111 GEN
Solar/Wind Harmer
1.14
970831AG2-522 GEN
Solar/Wind Harmer
6.069
316239AB2-077_GEN
Solar/Wind Harmer
0.274
316238AB2-078_GEN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Harmer
1.371
270457AD2-023 GEN
Solar/Wind Harmer
0.695
270494AE1-108_GEN
Solar/Wind Helper
2.769
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
970413AG2-270 GEN
50/50
29.414
3151591KERR 2
50/50
0.302
316478AD1-087 GEN
Solar/Wind Harmer
3.055
316486AD2-202 GEN
Solar/Wind Harmer
0.895
316248AF1-058 C
Solar/Wind Harmer
0.559
960061AF2-297 GEN
Solar/Wind Harmer
9.268
971683AH1-343 GEN
Solar/Wind Harmer
6.951
316283AC2-100 C
Solar/Wind Harmer
1.124
316131AB2-060 GEN
Solar/Wind Harmer
0.808
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.542
3147133PAMPLIN
Solar/Wind Helper
1.062
316313AB2-026
Solar/Wind Helper
0.243
316258AE1-075 C
Solar/Wind Helper
0.219
316405AF2-144 C
Solar/Wind Helper
0.182
3151531CLOVER1
50/50
6.74
3151601KERR 3
50/50
0.302
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.44
315693AD1-088 GEN
Solar/Wind Harmer
21.388
957481AF2-042 GEN
Solar/Wind Harmer
119.681
315687AD1-152 GEN
Solar/Wind Harmer
3.524
316003AC1-222 GEN
Solar/Wind Harmer
1.683
970401AG2-262 GEN
Solar/Wind Harmer
0.932
971065AG2-659 GEN
Solar/Wind Harmer
6.697
316129AC1-054 GEN
Solar/Wind Harmer
1.121
316237AB2-079_GEN
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Helper
0.44
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
1.003
3152661PLYWOOD A
50/50
0.348
970535AG2-341 GEN
50/50
2.001
970933AG2-581 GEN
Solar/Wind Harmer
36.739
970099AG2-077 GEN
Solar/Wind Harmer
47.872
939181AE1-148 GEN
Solar/Wind Harmer
8.421
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.05
962561AG1-105 GEN
Solar/Wind Harmer
7.525
316222AC1-221 GEN
Solar/Wind Harmer
1.236
942751AE2-291 GEN
Solar/Wind Harmer
7.063
313527AB2-043 GEN
Solar/Wind Harmer
1.361
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.338
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.919
CPLELTFEXP_CPLE->PJM
CLTF
4.232
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.165
LAGNLTFEXP_LAGN->PJM
CLTF
2.703
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.92
TVALTFEXP_TVA->PJM
CLTF
1.347
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.6
MECLTFEXP_MEC->PJM
CLTF
1.297
SIGELTFEXP_SIGE->PJM
CLTF
0.038
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.461
WECLTFEXP_WEC->PJM
CLTF
0.241

Details for AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.84 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:774.79
MW Contribution:29.36
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.403
315693AD1-088 GEN
Solar/Wind Harmer
21.359
957481AF2-042 GEN
Solar/Wind Harmer
119.484
315687AD1-152 GEN
Solar/Wind Harmer
3.515
316003AC1-222 GEN
Solar/Wind Harmer
1.676
970401AG2-262 GEN
Solar/Wind Harmer
0.928
971065AG2-659 GEN
Solar/Wind Harmer
6.677
316129AC1-054 GEN
Solar/Wind Harmer
1.118
316237AB2-079_GEN
Solar/Wind Harmer
0.273
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
3152661PLYWOOD A
50/50
0.346
970933AG2-581 GEN
Solar/Wind Harmer
36.681
970099AG2-077 GEN
Solar/Wind Harmer
47.793
939181AE1-148 GEN
Solar/Wind Harmer
8.391
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.036
962561AG1-105 GEN
Solar/Wind Harmer
7.49
316222AC1-221 GEN
Solar/Wind Harmer
1.223
942751AE2-291 GEN
Solar/Wind Harmer
7.025
313527AB2-043 GEN
Solar/Wind Harmer
1.353
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
971967AH1-528 GEN
Solar/Wind Harmer
73.556
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.126
970865AG2-541 GEN
Solar/Wind Harmer
6.047
316123AC1-075 GEN
Solar/Wind Harmer
1.351
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.135
970831AG2-522 GEN
Solar/Wind Harmer
6.052
316239AB2-077_GEN
Solar/Wind Harmer
0.273
316238AB2-078_GEN
Solar/Wind Harmer
0.273
270455AD2-022 GEN
Solar/Wind Harmer
1.35
270457AD2-023 GEN
Solar/Wind Harmer
0.684
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
316478AD1-087 GEN
Solar/Wind Harmer
3.05
316486AD2-202 GEN
Solar/Wind Harmer
0.893
316248AF1-058 C
Solar/Wind Harmer
0.556
960061AF2-297 GEN
Solar/Wind Harmer
9.23
971683AH1-343 GEN
Solar/Wind Harmer
6.92
316283AC2-100 C
Solar/Wind Harmer
1.112
316131AB2-060 GEN
Solar/Wind Harmer
0.803
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:211.67 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1447.79
MW Contribution:29.97
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.536
3144293JTRSVLE
50/50
1.294
970535AG2-341 GEN
50/50
4.631
3152661PLYWOOD A
50/50
0.509
970301AG2-198 GEN
Solar/Wind Harmer
29.375
971741AH1-377 GEN
Solar/Wind Harmer
63.77
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.984
963191AG1-168 GEN
Solar/Wind Harmer
4.79
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.293
971775AH1-396 GEN
Solar/Wind Harmer
3.032
970933AG2-581 GEN
Solar/Wind Harmer
36.564
970099AG2-077 GEN
Solar/Wind Harmer
47.892
313527AB2-043 GEN
Solar/Wind Harmer
5.323
962561AG1-105 GEN
Solar/Wind Harmer
16.163
964791AG1-342 GEN
Solar/Wind Harmer
5.983
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.395
942751AE2-291 GEN
Solar/Wind Harmer
9.282
316222AC1-221 GEN
Solar/Wind Harmer
1.431
316181AB2-040 GEN
Solar/Wind Harmer
1.454
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.157
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.182
3145783HORNRTN
Solar/Wind Harmer
0.946
3145783HORNRTN
Solar/Wind Harmer
0.296
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.956
316274AC1-208 GEN
Solar/Wind Harmer
0.891
316263AC1-034 GEN
Solar/Wind Harmer
3.354
961601AG1-000A GEN
Solar/Wind Harmer
2.733
3145796HORNRTN
Solar/Wind Harmer
-0.02
3151541CLOVER2
50/50
6.835
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
970285AG2-188 GEN
Solar/Wind Harmer
71.83
315657AE1-056 GEN
Solar/Wind Harmer
20.241
946301AF1-294 GEN
Solar/Wind Harmer
13.094
961791AG1-021 GEN
Solar/Wind Harmer
6.387
970683AG2-441 GEN
Solar/Wind Harmer
36.695
970681AG2-440 GEN
Solar/Wind Harmer
29.356
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.31
971967AH1-528 GEN
Solar/Wind Harmer
73.321
316239AB2-077_GEN
Solar/Wind Harmer
0.97
316238AB2-078_GEN
Solar/Wind Harmer
0.97
316118AC1-105 GEN
Solar/Wind Harmer
1.807
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.03
970831AG2-522 GEN
Solar/Wind Harmer
9.822
316123AC1-075 GEN
Solar/Wind Harmer
1.789
970165AG2-112 GEN
Solar/Wind Harmer
1.575
3144293JTRSVLE
50/50
1.536
3151531CLOVER1
50/50
6.868
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.479
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.387
971563AH1-280 GEN
Solar/Wind Harmer
6.387
970685AG2-442 GEN
Solar/Wind Harmer
41.098
962491AG1-098 GEN
Solar/Wind Harmer
28.527
315693AD1-088 GEN
Solar/Wind Harmer
20.89
957481AF2-042 GEN
Solar/Wind Harmer
119.73
316237AB2-079_GEN
Solar/Wind Harmer
0.97
315687AD1-152 GEN
Solar/Wind Harmer
3.722
970401AG2-262 GEN
Solar/Wind Harmer
1.828
316003AC1-222 GEN
Solar/Wind Harmer
2.23
971065AG2-659 GEN
Solar/Wind Harmer
10.784
316129AC1-054 GEN
Solar/Wind Harmer
1.809
971795AH1-408 GEN
Solar/Wind Harmer
11.382
960081AF2-299 GEN
Solar/Wind Harmer
1.187
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.663
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.965
316049AB1-081 GEN
Solar/Wind Harmer
0.772
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.715
3144293JTRSVLE
50/50
1.536
970413AG2-270 GEN
50/50
29.97
3151591KERR 2
50/50
0.482
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.339
970909AG2-566 GEN
Solar/Wind Harmer
5.578
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.735
963181AG1-167 GEN
Solar/Wind Harmer
4.79
959311AF2-222 GEN
Solar/Wind Harmer
45.765
970257AG2-171 GEN
Solar/Wind Harmer
15.97
315785AD2-033 C
Solar/Wind Harmer
9.259
964241AG1-285 GEN
Solar/Wind Harmer
28.316
316478AD1-087 GEN
Solar/Wind Harmer
3.115
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.609
316248AF1-058 C
Solar/Wind Harmer
0.741
960061AF2-297 GEN
Solar/Wind Harmer
12.289
971683AH1-343 GEN
Solar/Wind Harmer
9.199
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.303
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.775
316210AC1-098 GEN
Solar/Wind Harmer
1.194
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.767
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.393
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.414
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.317
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
970223AG2-152 GEN
Solar/Wind Harmer
5.79
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.192
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.414
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.314
970163AG2-111 GEN
Solar/Wind Harmer
1.503
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.493
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.635
270457AD2-023 GEN
Solar/Wind Harmer
0.829
315607AA1-063A GEN
Solar/Wind Harmer
0.882
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.411
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.563
270494AE1-108_GEN
Solar/Wind Helper
3.665
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.045
316197AC1-042 GEN
Solar/Wind Harmer
0.792
942671AE2-283 GEN
Solar/Wind Harmer
2.132
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.531
CPLELTFEXP_CPLE->PJM
CLTF
5.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.616
LAGNLTFEXP_LAGN->PJM
CLTF
3.212
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.896
TVALTFEXP_TVA->PJM
CLTF
1.599
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.51
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.435
MECLTFEXP_MEC->PJM
CLTF
1.488
SIGELTFEXP_SIGE->PJM
CLTF
0.044
NYPJM->LTFIMP_NY
CLTF
0.52
LGEELTFEXP_LGEE->PJM
CLTF
0.521
WECLTFEXP_WEC->PJM
CLTF
0.271

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:211.61 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1447.4
MW Contribution:29.97
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.536
970413AG2-270 GEN
50/50
29.97
3151591KERR 2
50/50
0.482
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.339
970909AG2-566 GEN
Solar/Wind Harmer
5.578
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.735
963181AG1-167 GEN
Solar/Wind Harmer
4.79
959311AF2-222 GEN
Solar/Wind Harmer
45.765
970257AG2-171 GEN
Solar/Wind Harmer
15.97
315785AD2-033 C
Solar/Wind Harmer
9.259
964241AG1-285 GEN
Solar/Wind Harmer
28.316
316478AD1-087 GEN
Solar/Wind Harmer
3.115
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.609
316248AF1-058 C
Solar/Wind Harmer
0.741
960061AF2-297 GEN
Solar/Wind Harmer
12.289
971683AH1-343 GEN
Solar/Wind Harmer
9.199
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.303
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.775
316210AC1-098 GEN
Solar/Wind Harmer
1.194
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3144293JTRSVLE
50/50
1.536
3151531CLOVER1
50/50
6.868
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.479
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.387
971563AH1-280 GEN
Solar/Wind Harmer
6.387
970685AG2-442 GEN
Solar/Wind Harmer
41.098
962491AG1-098 GEN
Solar/Wind Harmer
28.527
315693AD1-088 GEN
Solar/Wind Harmer
20.89
957481AF2-042 GEN
Solar/Wind Harmer
119.73
316237AB2-079_GEN
Solar/Wind Harmer
0.97
315687AD1-152 GEN
Solar/Wind Harmer
3.722
970401AG2-262 GEN
Solar/Wind Harmer
1.828
316003AC1-222 GEN
Solar/Wind Harmer
2.23
971065AG2-659 GEN
Solar/Wind Harmer
10.784
316129AC1-054 GEN
Solar/Wind Harmer
1.809
971795AH1-408 GEN
Solar/Wind Harmer
11.382
960081AF2-299 GEN
Solar/Wind Harmer
1.187
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.663
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.965
316049AB1-081 GEN
Solar/Wind Harmer
0.772
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.715
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
970223AG2-152 GEN
Solar/Wind Harmer
5.79
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.192
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.414
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.314
3151541CLOVER2
50/50
6.835
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
970285AG2-188 GEN
Solar/Wind Harmer
71.83
315657AE1-056 GEN
Solar/Wind Harmer
20.241
946301AF1-294 GEN
Solar/Wind Harmer
13.094
961791AG1-021 GEN
Solar/Wind Harmer
6.387
970683AG2-441 GEN
Solar/Wind Harmer
36.695
970681AG2-440 GEN
Solar/Wind Harmer
29.356
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.31
971967AH1-528 GEN
Solar/Wind Harmer
73.321
316239AB2-077_GEN
Solar/Wind Harmer
0.97
316238AB2-078_GEN
Solar/Wind Harmer
0.97
316118AC1-105 GEN
Solar/Wind Harmer
1.807
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.03
970831AG2-522 GEN
Solar/Wind Harmer
9.822
316123AC1-075 GEN
Solar/Wind Harmer
1.789
970165AG2-112 GEN
Solar/Wind Harmer
1.575
970163AG2-111 GEN
Solar/Wind Harmer
1.503
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.493
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.635
270457AD2-023 GEN
Solar/Wind Harmer
0.829
315607AA1-063A GEN
Solar/Wind Harmer
0.882
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.411
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.563
270494AE1-108_GEN
Solar/Wind Helper
3.665
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.767
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.393
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.414
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.317
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
3144293JTRSVLE
50/50
1.536
3144293JTRSVLE
50/50
1.294
970535AG2-341 GEN
50/50
4.631
3152661PLYWOOD A
50/50
0.509
970301AG2-198 GEN
Solar/Wind Harmer
29.375
971741AH1-377 GEN
Solar/Wind Harmer
63.77
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.984
963191AG1-168 GEN
Solar/Wind Harmer
4.79
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.293
971775AH1-396 GEN
Solar/Wind Harmer
3.032
970933AG2-581 GEN
Solar/Wind Harmer
36.564
970099AG2-077 GEN
Solar/Wind Harmer
47.892
313527AB2-043 GEN
Solar/Wind Harmer
5.323
962561AG1-105 GEN
Solar/Wind Harmer
16.163
964791AG1-342 GEN
Solar/Wind Harmer
5.983
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.395
942751AE2-291 GEN
Solar/Wind Harmer
9.282
316222AC1-221 GEN
Solar/Wind Harmer
1.431
316181AB2-040 GEN
Solar/Wind Harmer
1.454
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.157
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.182
3145783HORNRTN
Solar/Wind Harmer
0.946
3145783HORNRTN
Solar/Wind Harmer
0.296
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.956
316274AC1-208 GEN
Solar/Wind Harmer
0.891
316263AC1-034 GEN
Solar/Wind Harmer
3.354
961601AG1-000A GEN
Solar/Wind Harmer
2.733
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.045
316197AC1-042 GEN
Solar/Wind Harmer
0.792
942671AE2-283 GEN
Solar/Wind Harmer
2.132
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.531
CPLELTFEXP_CPLE->PJM
CLTF
5.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.616
LAGNLTFEXP_LAGN->PJM
CLTF
3.212
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.896
TVALTFEXP_TVA->PJM
CLTF
1.599
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.51
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.435
MECLTFEXP_MEC->PJM
CLTF
1.488
SIGELTFEXP_SIGE->PJM
CLTF
0.044
NYPJM->LTFIMP_NY
CLTF
0.52
LGEELTFEXP_LGEE->PJM
CLTF
0.521
WECLTFEXP_WEC->PJM
CLTF
0.271

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:207.99 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1422.62
MW Contribution:29.9
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
970285AG2-188 GEN
Solar/Wind Harmer
71.826
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
971967AH1-528 GEN
Solar/Wind Harmer
73.183
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970933AG2-581 GEN
Solar/Wind Harmer
36.495
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:206.17 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:1153.12
MW Contribution:29.9
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.97
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
963171AG1-166 GEN
Solar/Wind Harmer
2.424
971563AH1-280 GEN
Solar/Wind Harmer
4.847
970685AG2-442 GEN
Solar/Wind Harmer
31.186
962491AG1-098 GEN
Solar/Wind Harmer
21.632
315693AD1-088 GEN
Solar/Wind Harmer
17.82
957481AF2-042 GEN
Solar/Wind Harmer
90.757
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.458
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.171
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
9.004
960081AF2-299 GEN
Solar/Wind Harmer
0.903
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.349
3146233WITAKRS
Solar/Wind Harmer
0.261
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.051
316359AB2-059 GEN
Solar/Wind Harmer
0.226
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.062
315722AD1-056 GEN
Solar/Wind Harmer
0.382
3145796HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.068
962571AG1-106 GEN
Solar/Wind Harmer
0.836
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.253
970223AG2-152 GEN
Solar/Wind Harmer
3.997
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.043
941801AE2-185 GEN
Solar/Wind Harmer
1.818
3145823KELFORD
Solar/Wind Harmer
0.056
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.232
963181AG1-167 GEN
Solar/Wind Harmer
1.818
959311AF2-222 GEN
Solar/Wind Harmer
34.653
970257AG2-171 GEN
Solar/Wind Harmer
12.116
315785AD2-033 C
Solar/Wind Harmer
2.953
964241AG1-285 GEN
Solar/Wind Harmer
21.475
316478AD1-087 GEN
Solar/Wind Harmer
1.115
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.935
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.299
971683AH1-343 GEN
Solar/Wind Harmer
6.959
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.287
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.626
3146233WITAKRS
Solar/Wind Harmer
0.329
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.062
961601AG1-000A GEN
Solar/Wind Harmer
4.35
315724AD1-057 GEN
Solar/Wind Harmer
0.227
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.818
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.104
970285AG2-188 GEN
Solar/Wind Harmer
57.798
315657AE1-056 GEN
Solar/Wind Harmer
16.558
946301AF1-294 GEN
Solar/Wind Harmer
8.968
961791AG1-021 GEN
Solar/Wind Harmer
4.363
970683AG2-441 GEN
Solar/Wind Harmer
27.844
970681AG2-440 GEN
Solar/Wind Harmer
22.275
3144303KENBRDG
Solar/Wind Harmer
0.303
971443AH1-215 GEN
Solar/Wind Harmer
6.304
971967AH1-528 GEN
Solar/Wind Harmer
55.434
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.602
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.073
970831AG2-522 GEN
Solar/Wind Harmer
7.443
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.191
970163AG2-111 GEN
Solar/Wind Harmer
1.136
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.368
315607AA1-063A GEN
Solar/Wind Harmer
0.159
3146043SEABORD
Solar/Wind Harmer
0.076
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.25
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.462
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.252
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.213
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.1
970301AG2-198 GEN
Solar/Wind Harmer
22.295
971741AH1-377 GEN
Solar/Wind Harmer
48.392
3147133PAMPLIN
Solar/Wind Harmer
0.48
3147133PAMPLIN
Solar/Wind Harmer
0.384
958211AF2-115 GEN
Solar/Wind Harmer
5.453
963191AG1-168 GEN
Solar/Wind Harmer
1.818
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.154
971775AH1-396 GEN
Solar/Wind Harmer
0.606
970933AG2-581 GEN
Solar/Wind Harmer
27.718
970099AG2-077 GEN
Solar/Wind Harmer
36.303
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.244
964791AG1-342 GEN
Solar/Wind Harmer
4.773
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.665
942751AE2-291 GEN
Solar/Wind Harmer
7.016
316222AC1-221 GEN
Solar/Wind Harmer
0.517
316181AB2-040 GEN
Solar/Wind Harmer
0.135
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.992
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.575
3145783HORNRTN
Solar/Wind Harmer
1.26
3145783HORNRTN
Solar/Wind Harmer
0.394
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.38
316263AC1-034 GEN
Solar/Wind Harmer
2.393
961601AG1-000A GEN
Solar/Wind Harmer
1.088
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.132
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.414
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:203.59 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:1138.68
MW Contribution:29.9
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.97
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
963171AG1-166 GEN
Solar/Wind Harmer
2.424
971563AH1-280 GEN
Solar/Wind Harmer
4.847
970685AG2-442 GEN
Solar/Wind Harmer
31.186
962491AG1-098 GEN
Solar/Wind Harmer
21.632
315693AD1-088 GEN
Solar/Wind Harmer
17.82
957481AF2-042 GEN
Solar/Wind Harmer
90.757
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.458
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.171
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
9.004
960081AF2-299 GEN
Solar/Wind Harmer
0.903
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.349
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.104
970285AG2-188 GEN
Solar/Wind Harmer
57.798
315657AE1-056 GEN
Solar/Wind Harmer
16.558
946301AF1-294 GEN
Solar/Wind Harmer
8.968
961791AG1-021 GEN
Solar/Wind Harmer
4.363
970683AG2-441 GEN
Solar/Wind Harmer
27.844
970681AG2-440 GEN
Solar/Wind Harmer
22.275
3144303KENBRDG
Solar/Wind Harmer
0.303
971443AH1-215 GEN
Solar/Wind Harmer
6.304
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.602
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.073
970831AG2-522 GEN
Solar/Wind Harmer
7.443
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.191
970163AG2-111 GEN
Solar/Wind Harmer
1.136
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.368
315607AA1-063A GEN
Solar/Wind Harmer
0.159
3146043SEABORD
Solar/Wind Harmer
0.076
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.213
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.1
970301AG2-198 GEN
Solar/Wind Harmer
22.295
971741AH1-377 GEN
Solar/Wind Harmer
48.392
3147133PAMPLIN
Solar/Wind Harmer
0.48
3147133PAMPLIN
Solar/Wind Harmer
0.384
958211AF2-115 GEN
Solar/Wind Harmer
5.453
963191AG1-168 GEN
Solar/Wind Harmer
1.818
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.154
971775AH1-396 GEN
Solar/Wind Harmer
0.606
970099AG2-077 GEN
Solar/Wind Harmer
36.303
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.244
964791AG1-342 GEN
Solar/Wind Harmer
4.773
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.665
942751AE2-291 GEN
Solar/Wind Harmer
7.016
316222AC1-221 GEN
Solar/Wind Harmer
0.517
316181AB2-040 GEN
Solar/Wind Harmer
0.135
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.232
963181AG1-167 GEN
Solar/Wind Harmer
1.818
959311AF2-222 GEN
Solar/Wind Harmer
34.653
970257AG2-171 GEN
Solar/Wind Harmer
12.116
315785AD2-033 C
Solar/Wind Harmer
2.953
964241AG1-285 GEN
Solar/Wind Harmer
21.475
316478AD1-087 GEN
Solar/Wind Harmer
1.115
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.935
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.299
971683AH1-343 GEN
Solar/Wind Harmer
6.959
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.287
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.626
3146233WITAKRS
Solar/Wind Harmer
0.329
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.062
961601AG1-000A GEN
Solar/Wind Harmer
4.35
315724AD1-057 GEN
Solar/Wind Harmer
0.227
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.818
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.25
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.462
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.252
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.992
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.575
3145783HORNRTN
Solar/Wind Harmer
1.26
3145783HORNRTN
Solar/Wind Harmer
0.394
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.38
316263AC1-034 GEN
Solar/Wind Harmer
2.393
961601AG1-000A GEN
Solar/Wind Harmer
1.088
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.132
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.414
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
3146233WITAKRS
Solar/Wind Harmer
0.261
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.051
316359AB2-059 GEN
Solar/Wind Harmer
0.226
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.062
315722AD1-056 GEN
Solar/Wind Harmer
0.382
3145796HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.068
962571AG1-106 GEN
Solar/Wind Harmer
0.836
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.253
970223AG2-152 GEN
Solar/Wind Harmer
3.997
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.043
941801AE2-185 GEN
Solar/Wind Harmer
1.818
3145823KELFORD
Solar/Wind Harmer
0.056
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:201.95 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1381.35
MW Contribution:29.9
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
970285AG2-188 GEN
Solar/Wind Harmer
71.826
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:201.95 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1381.35
MW Contribution:29.9
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
970285AG2-188 GEN
Solar/Wind Harmer
71.826
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2106-2111_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2106-2111_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:128.21 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:876.96
MW Contribution:12.4
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.18
3151601KERR 3
50/50
0.277
3151581KERR 1
50/50
0.099
3151531CLOVER1
50/50
2.843
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.907
971563AH1-280 GEN
Solar/Wind Harmer
4.907
970685AG2-442 GEN
Solar/Wind Harmer
30.788
962491AG1-098 GEN
Solar/Wind Harmer
14.151
316237AB2-079_GEN
Solar/Wind Harmer
0.621
315693AD1-088 GEN
Solar/Wind Harmer
9.998
970401AG2-262 GEN
Solar/Wind Harmer
1.046
957481AF2-042 GEN
Solar/Wind Harmer
45.244
315687AD1-152 GEN
Solar/Wind Harmer
1.611
971065AG2-659 GEN
Solar/Wind Harmer
6.471
316129AC1-054 GEN
Solar/Wind Harmer
1.098
3147043LAWRENC
Adder
0.994
316003AC1-222 GEN
Solar/Wind Harmer
1.108
971795AH1-408 GEN
Solar/Wind Harmer
8.341
960081AF2-299 GEN
Solar/Wind Harmer
0.953
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.091
316212AC1-099_GEN
Solar/Wind Harmer
0.553
316322AB2-045
Solar/Wind Helper
0.97
3146776BUCKING
Solar/Wind Helper
0.348
316336AC2-165 C
Solar/Wind Helper
1.454
3151611KERR 4
50/50
0.277
3151621KERR 5
50/50
0.277
3151631KERR 6
50/50
0.277
3151641KERR 7
50/50
0.277
3151541CLOVER2
50/50
2.829
970285AG2-188 GEN
Solar/Wind Harmer
63.51
315657AE1-056 GEN
Solar/Wind Harmer
15.784
946301AF1-294 GEN
Solar/Wind Harmer
10.059
961791AG1-021 GEN
Solar/Wind Harmer
4.907
970683AG2-441 GEN
Solar/Wind Harmer
27.489
970681AG2-440 GEN
Solar/Wind Harmer
21.992
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.004
316239AB2-077_GEN
Solar/Wind Harmer
0.621
316238AB2-078_GEN
Solar/Wind Harmer
0.621
316118AC1-105 GEN
Solar/Wind Harmer
0.972
3147173SINAI
Solar/Wind Harmer
-0.012
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.033
970865AG2-541 GEN
Solar/Wind Harmer
3.923
946281AF1-292 GEN
Solar/Wind Harmer
0.19
316087AB2-174 GEN
Solar/Wind Harmer
1.178
3137643SOCKMAN
Solar/Wind Harmer
-0.032
316123AC1-075 GEN
Solar/Wind Harmer
0.853
970165AG2-112 GEN
Solar/Wind Harmer
0.751
970163AG2-111 GEN
Solar/Wind Harmer
0.717
971967AH1-528 GEN
Solar/Wind Harmer
14.188
315607AA1-063A GEN
Solar/Wind Harmer
0.715
3146043SEABORD
Solar/Wind Harmer
-0.007
270494AE1-108_GEN
Solar/Wind Helper
4.499
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3144293JTRSVLE
50/50
1.18
3144293JTRSVLE
50/50
0.994
970535AG2-341 GEN
50/50
2.836
3152661PLYWOOD A
50/50
0.267
970301AG2-198 GEN
Solar/Wind Harmer
21.257
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.133
963191AG1-168 GEN
Solar/Wind Harmer
3.68
971741AH1-377 GEN
Solar/Wind Harmer
43.417
316034AC1-036 C
Solar/Wind Harmer
0.574
970323AG2-213 GEN
Solar/Wind Harmer
15.434
971775AH1-396 GEN
Solar/Wind Harmer
2.198
313527AB2-043 GEN
Solar/Wind Harmer
3.442
962561AG1-105 GEN
Solar/Wind Harmer
9.457
939181AE1-148 GEN
Solar/Wind Harmer
9.083
964791AG1-342 GEN
Solar/Wind Harmer
3.423
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.098
970933AG2-581 GEN
Solar/Wind Harmer
9.079
316181AB2-040 GEN
Solar/Wind Harmer
1.138
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.878
3145593CAROLNA
Solar/Wind Harmer
0.065
3145783HORNRTN
Solar/Wind Harmer
0.905
3145783HORNRTN
Solar/Wind Harmer
0.724
3145783HORNRTN
Solar/Wind Harmer
0.226
3145783HORNRTN
Solar/Wind Harmer
0.09
316222AC1-221 GEN
Solar/Wind Harmer
0.769
316426AA2-053 GEN
Solar/Wind Harmer
0.748
942751AE2-291 GEN
Solar/Wind Harmer
4.333
316274AC1-208 GEN
Solar/Wind Harmer
0.717
972187AH1-678 GEN
Adder
1.63
3146776BUCKING
Solar/Wind Helper
3.482
3146776BUCKING
Solar/Wind Helper
0.282
315821AE2-092 GEN
Solar/Wind Helper
2.994
3144293JTRSVLE
50/50
1.18
3151591KERR 2
50/50
0.277
970413AG2-270 GEN
50/50
12.405
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.535
970909AG2-566 GEN
Solar/Wind Harmer
4.036
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.307
963181AG1-167 GEN
Solar/Wind Harmer
3.68
959311AF2-222 GEN
Solar/Wind Harmer
33.514
970257AG2-171 GEN
Solar/Wind Harmer
11.575
315785AD2-033 C
Solar/Wind Harmer
6.609
964241AG1-285 GEN
Solar/Wind Harmer
19.233
316131AB2-060 GEN
Solar/Wind Harmer
2.359
316478AD1-087 GEN
Solar/Wind Harmer
1.29
316486AD2-202 GEN
Solar/Wind Harmer
0.378
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.371
960061AF2-297 GEN
Solar/Wind Harmer
6.151
971683AH1-343 GEN
Solar/Wind Harmer
4.535
966621AG1-532 GEN
Solar/Wind Harmer
0.172
313506AB2-031 GEN
Solar/Wind Harmer
0.656
316283AC2-100 C
Solar/Wind Harmer
0.705
316210AC1-098 GEN
Solar/Wind Harmer
0.995
3146776BUCKING
Solar/Wind Helper
0.313
316313AB2-026
Solar/Wind Helper
0.341
316258AE1-075 C
Solar/Wind Helper
0.306
316405AF2-144 C
Solar/Wind Helper
0.255
3148013FISHERV
Solar/Wind Helper
0.125
CPLELTFEXP_CPLE->PJM
CLTF
3.717
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.651
LAGNLTFEXP_LAGN->PJM
CLTF
1.842
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.457
TVALTFEXP_TVA->PJM
CLTF
0.904
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.19
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.966
MECLTFEXP_MEC->PJM
CLTF
0.645
SIGELTFEXP_SIGE->PJM
CLTF
0.018
NYPJM->LTFIMP_NY
CLTF
0.34
LGEELTFEXP_LGEE->PJM
CLTF
0.186
WECLTFEXP_WEC->PJM
CLTF
0.097

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:128.06 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:875.95
MW Contribution:12.9
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.195
3144293JTRSVLE
50/50
1.007
970535AG2-341 GEN
50/50
2.934
3152661PLYWOOD A
50/50
0.28
970301AG2-198 GEN
Solar/Wind Harmer
21.495
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.212
963191AG1-168 GEN
Solar/Wind Harmer
3.727
971741AH1-377 GEN
Solar/Wind Harmer
43.991
316034AC1-036 C
Solar/Wind Harmer
0.584
970323AG2-213 GEN
Solar/Wind Harmer
15.706
971775AH1-396 GEN
Solar/Wind Harmer
2.237
313527AB2-043 GEN
Solar/Wind Harmer
3.538
962561AG1-105 GEN
Solar/Wind Harmer
9.795
939181AE1-148 GEN
Solar/Wind Harmer
9.44
964791AG1-342 GEN
Solar/Wind Harmer
3.552
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
970099AG2-077 GEN
Solar/Wind Harmer
18.81
970933AG2-581 GEN
Solar/Wind Harmer
9.592
316181AB2-040 GEN
Solar/Wind Harmer
1.225
316222AC1-221 GEN
Solar/Wind Harmer
0.857
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.951
3145593CAROLNA
Solar/Wind Harmer
0.07
3145783HORNRTN
Solar/Wind Harmer
0.982
3145783HORNRTN
Solar/Wind Harmer
0.786
3145783HORNRTN
Solar/Wind Harmer
0.245
3145783HORNRTN
Solar/Wind Harmer
0.098
316426AA2-053 GEN
Solar/Wind Harmer
0.813
316274AC1-208 GEN
Solar/Wind Harmer
0.793
942751AE2-291 GEN
Solar/Wind Harmer
4.536
972187AH1-678 GEN
Adder
1.773
972185AH1-677 GEN
Adder
3.35
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
316263AC1-034 GEN
Solar/Wind Harmer
3.126
961601AG1-000A GEN
Solar/Wind Harmer
2.583
3145893MURPHYS
Solar/Wind Harmer
0.18
3145893MURPHYS
Solar/Wind Harmer
-0.012
3145493TOT1
Solar/Wind Harmer
0.098
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
3146776BUCKING
Solar/Wind Helper
3.457
3146776BUCKING
Solar/Wind Helper
0.28
315821AE2-092 GEN
Solar/Wind Helper
2.963
3144293JTRSVLE
50/50
1.195
3151591KERR 2
50/50
0.289
970413AG2-270 GEN
50/50
12.897
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.604
970909AG2-566 GEN
Solar/Wind Harmer
4.081
3147133PAMPLIN
Solar/Wind Harmer
-0.133
971193AH1-056 GEN
Solar/Wind Harmer
26.615
963181AG1-167 GEN
Solar/Wind Harmer
3.727
959311AF2-222 GEN
Solar/Wind Harmer
34.076
970257AG2-171 GEN
Solar/Wind Harmer
11.779
315785AD2-033 C
Solar/Wind Harmer
6.734
964241AG1-285 GEN
Solar/Wind Harmer
19.68
316131AB2-060 GEN
Solar/Wind Harmer
2.422
316478AD1-087 GEN
Solar/Wind Harmer
1.342
316486AD2-202 GEN
Solar/Wind Harmer
0.393
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.389
960061AF2-297 GEN
Solar/Wind Harmer
6.458
971683AH1-343 GEN
Solar/Wind Harmer
4.759
966621AG1-532 GEN
Solar/Wind Harmer
0.184
313506AB2-031 GEN
Solar/Wind Harmer
0.706
316283AC2-100 C
Solar/Wind Harmer
0.787
316210AC1-098 GEN
Solar/Wind Harmer
1.105
316327AA2-057 GEN
Solar/Wind Harmer
0.707
970917AG2-570 GEN
Solar/Wind Harmer
17.327
3146233WITAKRS
Solar/Wind Harmer
0.143
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.004
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.382
316365GEN2_N
Solar/Wind Harmer
0.443
961601AG1-000A GEN
Solar/Wind Harmer
2.615
316317KELFORD C
Solar/Wind Harmer
0.306
3145823KELFORD
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.09
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
957521AF2-046 GEN
Solar/Wind Harmer
5.039
3151611KERR 4
50/50
0.289
3151621KERR 5
50/50
0.289
3151631KERR 6
50/50
0.289
3151641KERR 7
50/50
0.289
3151541CLOVER2
50/50
2.941
970285AG2-188 GEN
Solar/Wind Harmer
63.831
315657AE1-056 GEN
Solar/Wind Harmer
15.969
946301AF1-294 GEN
Solar/Wind Harmer
10.188
961791AG1-021 GEN
Solar/Wind Harmer
4.97
970683AG2-441 GEN
Solar/Wind Harmer
27.899
970681AG2-440 GEN
Solar/Wind Harmer
22.32
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.111
316239AB2-077_GEN
Solar/Wind Harmer
0.639
316238AB2-078_GEN
Solar/Wind Harmer
0.639
316118AC1-105 GEN
Solar/Wind Harmer
1.014
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.355
970865AG2-541 GEN
Solar/Wind Harmer
4.115
946281AF1-292 GEN
Solar/Wind Harmer
0.203
316087AB2-174 GEN
Solar/Wind Harmer
1.265
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.894
970165AG2-112 GEN
Solar/Wind Harmer
0.787
970163AG2-111 GEN
Solar/Wind Harmer
0.751
971967AH1-528 GEN
Solar/Wind Harmer
15.203
315607AA1-063A GEN
Solar/Wind Harmer
0.778
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.327
970581AG2-369 GEN
Solar/Wind Harmer
3.722
316319Z2-044 C
Solar/Wind Harmer
0.378
3146033SCOT NK
Solar/Wind Harmer
-0.027
315652AC1-086 GEN
Solar/Wind Harmer
7.562
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
965291AG1-394 GEN
Solar/Wind Harmer
0.582
970673AG2-436 GEN
Solar/Wind Harmer
13.618
970673AG2-436 GEN
Solar/Wind Harmer
6.895
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
270494AE1-108_GEN
Solar/Wind Helper
4.464
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
961681AG1-008 GEN
Solar/Wind Harmer
5.039
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.311
316313AB2-026
Solar/Wind Helper
0.332
316258AE1-075 C
Solar/Wind Helper
0.299
316405AF2-144 C
Solar/Wind Helper
0.249
3148013FISHERV
Solar/Wind Helper
0.123
3144293JTRSVLE
50/50
1.195
3151601KERR 3
50/50
0.289
3151581KERR 1
50/50
0.103
3151531CLOVER1
50/50
2.955
3147043LAWRENC
50/50
1.106
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.97
971563AH1-280 GEN
Solar/Wind Harmer
4.97
970685AG2-442 GEN
Solar/Wind Harmer
31.247
962491AG1-098 GEN
Solar/Wind Harmer
14.52
316237AB2-079_GEN
Solar/Wind Harmer
0.639
315693AD1-088 GEN
Solar/Wind Harmer
10.276
970401AG2-262 GEN
Solar/Wind Harmer
1.085
957481AF2-042 GEN
Solar/Wind Harmer
47.025
315687AD1-152 GEN
Solar/Wind Harmer
1.689
971065AG2-659 GEN
Solar/Wind Harmer
6.793
316129AC1-054 GEN
Solar/Wind Harmer
1.154
316003AC1-222 GEN
Solar/Wind Harmer
1.163
971795AH1-408 GEN
Solar/Wind Harmer
8.792
960081AF2-299 GEN
Solar/Wind Harmer
1.021
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.099
316212AC1-099_GEN
Solar/Wind Harmer
0.614
970919AG2-571 GEN
Solar/Wind Harmer
2.193
970087AG2-069 GEN
Solar/Wind Harmer
6.491
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.406
962571AG1-106 GEN
Solar/Wind Harmer
0.966
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316359AB2-059 GEN
Solar/Wind Harmer
0.899
316049AB1-081 GEN
Solar/Wind Harmer
0.72
3142053HEARTS
Solar/Wind Harmer
0.078
315722AD1-056 GEN
Solar/Wind Harmer
0.694
316023GEN1_S
Solar/Wind Harmer
0.443
3145823KELFORD
Solar/Wind Harmer
-0.006
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.191
961671AG1-007 GEN
Solar/Wind Harmer
0.08
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
316322AB2-045
Solar/Wind Helper
0.963
3146776BUCKING
Solar/Wind Helper
0.346
316336AC2-165 C
Solar/Wind Helper
1.425
CPLELTFEXP_CPLE->PJM
CLTF
4.543
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.552
LAGNLTFEXP_LAGN->PJM
CLTF
2.505
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.252
TVALTFEXP_TVA->PJM
CLTF
1.216
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.102
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.96
MECLTFEXP_MEC->PJM
CLTF
0.838
SIGELTFEXP_SIGE->PJM
CLTF
0.022
NYPJM->LTFIMP_NY
CLTF
0.295
LGEELTFEXP_LGEE->PJM
CLTF
0.219
WECLTFEXP_WEC->PJM
CLTF
0.123

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2003-205_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2003-205_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:124.48 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:851.47
MW Contribution:12.73
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.284
3151621KERR 5
50/50
0.284
3151631KERR 6
50/50
0.284
3151641KERR 7
50/50
0.284
3151541CLOVER2
50/50
2.903
970285AG2-188 GEN
Solar/Wind Harmer
63.671
315657AE1-056 GEN
Solar/Wind Harmer
15.898
946301AF1-294 GEN
Solar/Wind Harmer
10.139
961791AG1-021 GEN
Solar/Wind Harmer
4.946
970683AG2-441 GEN
Solar/Wind Harmer
27.748
970681AG2-440 GEN
Solar/Wind Harmer
22.198
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.073
316239AB2-077_GEN
Solar/Wind Harmer
0.632
316238AB2-078_GEN
Solar/Wind Harmer
0.632
316118AC1-105 GEN
Solar/Wind Harmer
0.997
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.254
970865AG2-541 GEN
Solar/Wind Harmer
4.048
946281AF1-292 GEN
Solar/Wind Harmer
0.204
316087AB2-174 GEN
Solar/Wind Harmer
1.262
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.884
970165AG2-112 GEN
Solar/Wind Harmer
0.778
970163AG2-111 GEN
Solar/Wind Harmer
0.742
971967AH1-528 GEN
Solar/Wind Harmer
15.039
315607AA1-063A GEN
Solar/Wind Harmer
0.762
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.212
970581AG2-369 GEN
Solar/Wind Harmer
3.623
315652AC1-086 GEN
Solar/Wind Harmer
7.469
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.026
316319Z2-044 C
Solar/Wind Harmer
0.36
970673AG2-436 GEN
Solar/Wind Harmer
13.449
970673AG2-436 GEN
Solar/Wind Harmer
6.81
965291AG1-394 GEN
Solar/Wind Harmer
0.565
270494AE1-108_GEN
Solar/Wind Helper
4.476
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.19
3151601KERR 3
50/50
0.284
3151581KERR 1
50/50
0.102
3151531CLOVER1
50/50
2.917
3147043LAWRENC
50/50
1.102
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.946
971563AH1-280 GEN
Solar/Wind Harmer
4.946
970685AG2-442 GEN
Solar/Wind Harmer
31.078
962491AG1-098 GEN
Solar/Wind Harmer
14.404
316237AB2-079_GEN
Solar/Wind Harmer
0.632
315693AD1-088 GEN
Solar/Wind Harmer
10.19
970401AG2-262 GEN
Solar/Wind Harmer
1.07
957481AF2-042 GEN
Solar/Wind Harmer
46.506
315687AD1-152 GEN
Solar/Wind Harmer
1.657
971065AG2-659 GEN
Solar/Wind Harmer
6.686
316129AC1-054 GEN
Solar/Wind Harmer
1.136
971795AH1-408 GEN
Solar/Wind Harmer
8.781
316003AC1-222 GEN
Solar/Wind Harmer
1.14
960081AF2-299 GEN
Solar/Wind Harmer
1.025
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.097
316212AC1-099_GEN
Solar/Wind Harmer
0.591
970919AG2-571 GEN
Solar/Wind Harmer
2.137
970087AG2-069 GEN
Solar/Wind Harmer
6.318
316023GEN1_S
Solar/Wind Harmer
0.452
316011AB1-132 GEN
Solar/Wind Harmer
1.389
962571AG1-106 GEN
Solar/Wind Harmer
0.954
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
-0.026
315722AD1-056 GEN
Solar/Wind Harmer
0.667
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316322AB2-045
Solar/Wind Helper
0.967
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.456
3144293JTRSVLE
50/50
1.19
3144293JTRSVLE
50/50
1.002
970535AG2-341 GEN
50/50
2.898
3152661PLYWOOD A
50/50
0.275
970301AG2-198 GEN
Solar/Wind Harmer
21.406
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.183
963191AG1-168 GEN
Solar/Wind Harmer
3.71
971741AH1-377 GEN
Solar/Wind Harmer
43.786
316034AC1-036 C
Solar/Wind Harmer
0.58
970323AG2-213 GEN
Solar/Wind Harmer
15.608
971775AH1-396 GEN
Solar/Wind Harmer
2.223
313527AB2-043 GEN
Solar/Wind Harmer
3.505
962561AG1-105 GEN
Solar/Wind Harmer
9.664
939181AE1-148 GEN
Solar/Wind Harmer
9.308
964791AG1-342 GEN
Solar/Wind Harmer
3.501
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.602
970933AG2-581 GEN
Solar/Wind Harmer
9.49
316181AB2-040 GEN
Solar/Wind Harmer
1.218
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.934
3145593CAROLNA
Solar/Wind Harmer
0.069
3145783HORNRTN
Solar/Wind Harmer
0.963
3145783HORNRTN
Solar/Wind Harmer
0.77
3145783HORNRTN
Solar/Wind Harmer
0.241
3145783HORNRTN
Solar/Wind Harmer
0.096
316222AC1-221 GEN
Solar/Wind Harmer
0.802
316426AA2-053 GEN
Solar/Wind Harmer
0.797
316274AC1-208 GEN
Solar/Wind Harmer
0.766
942751AE2-291 GEN
Solar/Wind Harmer
4.503
972187AH1-678 GEN
Adder
1.745
972185AH1-677 GEN
Adder
3.302
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3146776BUCKING
Solar/Wind Helper
3.47
3146776BUCKING
Solar/Wind Helper
0.281
315821AE2-092 GEN
Solar/Wind Helper
2.982
3144293JTRSVLE
50/50
1.19
3151591KERR 2
50/50
0.284
970413AG2-270 GEN
50/50
12.729
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.576
970909AG2-566 GEN
Solar/Wind Harmer
4.064
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.496
963181AG1-167 GEN
Solar/Wind Harmer
3.71
959311AF2-222 GEN
Solar/Wind Harmer
33.872
970257AG2-171 GEN
Solar/Wind Harmer
11.706
315785AD2-033 C
Solar/Wind Harmer
6.689
964241AG1-285 GEN
Solar/Wind Harmer
19.525
316131AB2-060 GEN
Solar/Wind Harmer
2.4
316478AD1-087 GEN
Solar/Wind Harmer
1.324
316486AD2-202 GEN
Solar/Wind Harmer
0.388
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.381
960061AF2-297 GEN
Solar/Wind Harmer
6.325
971683AH1-343 GEN
Solar/Wind Harmer
4.674
966621AG1-532 GEN
Solar/Wind Harmer
0.185
313506AB2-031 GEN
Solar/Wind Harmer
0.702
316283AC2-100 C
Solar/Wind Harmer
0.736
316210AC1-098 GEN
Solar/Wind Harmer
1.064
970917AG2-570 GEN
Solar/Wind Harmer
16.885
316365GEN2_N
Solar/Wind Harmer
0.452
316327AA2-057 GEN
Solar/Wind Harmer
0.676
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.136
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
315724AD1-057 GEN
Solar/Wind Harmer
0.367
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.312
316313AB2-026
Solar/Wind Helper
0.342
316258AE1-075 C
Solar/Wind Helper
0.307
316405AF2-144 C
Solar/Wind Helper
0.256
3148013FISHERV
Solar/Wind Helper
0.124
CPLELTFEXP_CPLE->PJM
CLTF
3.951
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.116
LAGNLTFEXP_LAGN->PJM
CLTF
2.085
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.001
TVALTFEXP_TVA->PJM
CLTF
1.025
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.511
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.403
MECLTFEXP_MEC->PJM
CLTF
0.809
SIGELTFEXP_SIGE->PJM
CLTF
0.023
NYPJM->LTFIMP_NY
CLTF
0.315
LGEELTFEXP_LGEE->PJM
CLTF
0.251
WECLTFEXP_WEC->PJM
CLTF
0.133

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:115.8 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:792.06
MW Contribution:12.58
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.281
3151621KERR 5
50/50
0.281
3151631KERR 6
50/50
0.281
3144293JTRSVLE
50/50
1.186
3151591KERR 2
50/50
0.281
970413AG2-270 GEN
50/50
12.579
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.561
970909AG2-566 GEN
Solar/Wind Harmer
4.052
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.429
963181AG1-167 GEN
Solar/Wind Harmer
3.699
3151641KERR 7
50/50
0.281
3151541CLOVER2
50/50
2.869
970285AG2-188 GEN
Solar/Wind Harmer
63.627
315657AE1-056 GEN
Solar/Wind Harmer
15.857
946301AF1-294 GEN
Solar/Wind Harmer
10.111
961791AG1-021 GEN
Solar/Wind Harmer
4.932
970683AG2-441 GEN
Solar/Wind Harmer
27.657
970681AG2-440 GEN
Solar/Wind Harmer
22.126
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.048
316239AB2-077_GEN
Solar/Wind Harmer
0.628
316238AB2-078_GEN
Solar/Wind Harmer
0.628
316118AC1-105 GEN
Solar/Wind Harmer
1
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.134
970865AG2-541 GEN
Solar/Wind Harmer
4.26
316123AC1-075 GEN
Solar/Wind Harmer
0.971
970165AG2-112 GEN
Solar/Wind Harmer
0.855
970163AG2-111 GEN
Solar/Wind Harmer
0.816
946281AF1-292 GEN
Solar/Wind Harmer
0.194
316087AB2-174 GEN
Solar/Wind Harmer
1.202
3137643SOCKMAN
Solar/Wind Harmer
-0.032
971967AH1-528 GEN
Solar/Wind Harmer
14.485
315607AA1-063A GEN
Solar/Wind Harmer
0.732
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.036
970581AG2-369 GEN
Solar/Wind Harmer
3.471
270494AE1-108_GEN
Solar/Wind Helper
4.511
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.186
3144293JTRSVLE
50/50
0.999
970535AG2-341 GEN
50/50
2.873
3152661PLYWOOD A
50/50
0.275
970301AG2-198 GEN
Solar/Wind Harmer
21.341
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.165
963191AG1-168 GEN
Solar/Wind Harmer
3.699
971741AH1-377 GEN
Solar/Wind Harmer
43.617
316034AC1-036 C
Solar/Wind Harmer
0.578
970323AG2-213 GEN
Solar/Wind Harmer
15.547
971775AH1-396 GEN
Solar/Wind Harmer
2.214
313527AB2-043 GEN
Solar/Wind Harmer
3.483
962561AG1-105 GEN
Solar/Wind Harmer
9.649
964791AG1-342 GEN
Solar/Wind Harmer
3.499
939181AE1-148 GEN
Solar/Wind Harmer
9.211
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.337
970933AG2-581 GEN
Solar/Wind Harmer
9.235
316181AB2-040 GEN
Solar/Wind Harmer
1.163
942751AE2-291 GEN
Solar/Wind Harmer
5.136
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.898
3145593CAROLNA
Solar/Wind Harmer
0.066
316222AC1-221 GEN
Solar/Wind Harmer
0.791
3145783HORNRTN
Solar/Wind Harmer
0.925
3145783HORNRTN
Solar/Wind Harmer
0.74
3145783HORNRTN
Solar/Wind Harmer
0.231
3145783HORNRTN
Solar/Wind Harmer
0.092
316426AA2-053 GEN
Solar/Wind Harmer
0.765
316274AC1-208 GEN
Solar/Wind Harmer
0.735
972187AH1-678 GEN
Adder
1.669
3146776BUCKING
Solar/Wind Helper
3.473
3146776BUCKING
Solar/Wind Helper
0.281
315821AE2-092 GEN
Solar/Wind Helper
2.981
3144293JTRSVLE
50/50
1.186
3151601KERR 3
50/50
0.281
3151581KERR 1
50/50
0.1
3151531CLOVER1
50/50
2.882
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.932
971563AH1-280 GEN
Solar/Wind Harmer
4.932
970685AG2-442 GEN
Solar/Wind Harmer
30.976
962491AG1-098 GEN
Solar/Wind Harmer
14.277
316237AB2-079_GEN
Solar/Wind Harmer
0.628
315693AD1-088 GEN
Solar/Wind Harmer
10.093
970401AG2-262 GEN
Solar/Wind Harmer
1.069
957481AF2-042 GEN
Solar/Wind Harmer
45.841
315687AD1-152 GEN
Solar/Wind Harmer
1.641
971065AG2-659 GEN
Solar/Wind Harmer
6.575
316129AC1-054 GEN
Solar/Wind Harmer
1.116
3147043LAWRENC
Adder
1.01
316003AC1-222 GEN
Solar/Wind Harmer
1.164
971795AH1-408 GEN
Solar/Wind Harmer
8.484
960081AF2-299 GEN
Solar/Wind Harmer
0.973
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.093
316212AC1-099_GEN
Solar/Wind Harmer
0.567
970919AG2-571 GEN
Solar/Wind Harmer
2.047
970087AG2-069 GEN
Solar/Wind Harmer
6.053
3146263WOODLND
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.968
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.444
959311AF2-222 GEN
Solar/Wind Harmer
33.746
970257AG2-171 GEN
Solar/Wind Harmer
11.66
315785AD2-033 C
Solar/Wind Harmer
6.661
964241AG1-285 GEN
Solar/Wind Harmer
19.423
316131AB2-060 GEN
Solar/Wind Harmer
2.386
316478AD1-087 GEN
Solar/Wind Harmer
1.308
316486AD2-202 GEN
Solar/Wind Harmer
0.383
316248AF1-058 C
Solar/Wind Harmer
0.384
960061AF2-297 GEN
Solar/Wind Harmer
6.368
3147043LAWRENC
Solar/Wind Harmer
-0.007
971683AH1-343 GEN
Solar/Wind Harmer
4.838
966621AG1-532 GEN
Solar/Wind Harmer
0.176
313506AB2-031 GEN
Solar/Wind Harmer
0.67
316283AC2-100 C
Solar/Wind Harmer
0.725
316210AC1-098 GEN
Solar/Wind Harmer
1.021
970917AG2-570 GEN
Solar/Wind Harmer
16.174
316327AA2-057 GEN
Solar/Wind Harmer
0.648
3146263WOODLND
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.312
316313AB2-026
Solar/Wind Helper
0.338
316258AE1-075 C
Solar/Wind Helper
0.304
316405AF2-144 C
Solar/Wind Helper
0.253
3148013FISHERV
Solar/Wind Helper
0.124
CPLELTFEXP_CPLE->PJM
CLTF
3.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.48
LAGNLTFEXP_LAGN->PJM
CLTF
1.974
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.732
TVALTFEXP_TVA->PJM
CLTF
0.969
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.023
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.205
MECLTFEXP_MEC->PJM
CLTF
0.743
SIGELTFEXP_SIGE->PJM
CLTF
0.021
NYPJM->LTFIMP_NY
CLTF
0.299
LGEELTFEXP_LGEE->PJM
CLTF
0.225
WECLTFEXP_WEC->PJM
CLTF
0.119

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.37 %
Rating:559.3 MVA
Rating Type:A
MVA to Mitigate:617.32
MW Contribution:12.48
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.279
3151621KERR 5
50/50
0.279
3151631KERR 6
50/50
0.279
3151641KERR 7
50/50
0.279
3151541CLOVER2
50/50
2.847
3151281ROARAP4
50/50
0.085
3151281ROARAP4
50/50
0.08
963041AG1-153 GEN
50/50
1.549
970285AG2-188 GEN
Solar/Wind Harmer
51.175
315657AE1-056 GEN
Solar/Wind Harmer
12.95
946301AF1-294 GEN
Solar/Wind Harmer
6.911
961791AG1-021 GEN
Solar/Wind Harmer
3.362
970683AG2-441 GEN
Solar/Wind Harmer
20.935
970681AG2-440 GEN
Solar/Wind Harmer
16.748
3144303KENBRDG
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
4.574
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.327
3147173SINAI
Solar/Wind Harmer
0.11
3147243WELCO
Solar/Wind Harmer
0.069
970831AG2-522 GEN
Solar/Wind Harmer
4.619
970865AG2-541 GEN
Solar/Wind Harmer
3.009
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.287
316123AC1-075 GEN
Solar/Wind Harmer
0.097
970165AG2-112 GEN
Solar/Wind Harmer
0.577
970163AG2-111 GEN
Solar/Wind Harmer
0.551
971967AH1-528 GEN
Solar/Wind Harmer
10.885
315607AA1-063A GEN
Solar/Wind Harmer
0.13
3146043SEABORD
Solar/Wind Harmer
0.063
970085AG2-068 GEN
Solar/Wind Harmer
3.037
970581AG2-369 GEN
Solar/Wind Harmer
2.612
270494AE1-108_GEN
Solar/Wind Helper
4.476
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.183
3151601KERR 3
50/50
0.279
3151581KERR 1
50/50
0.1
3151531CLOVER1
50/50
2.861
3147043LAWRENC
50/50
1.063
3151261ROARAP2
50/50
0.088
3151051BRUNSWICKS1
50/50
1.588
3151021BRUNSWICKG1
50/50
0.765
971451AH1-221 GEN
50/50
2.324
3146926FARMVIL
Solar/Wind Harmer
0.316
963171AG1-166 GEN
Solar/Wind Harmer
1.868
971563AH1-280 GEN
Solar/Wind Harmer
3.736
970685AG2-442 GEN
Solar/Wind Harmer
23.448
962491AG1-098 GEN
Solar/Wind Harmer
10.797
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
8.584
970401AG2-262 GEN
Solar/Wind Harmer
0.842
957481AF2-042 GEN
Solar/Wind Harmer
34.592
315687AD1-152 GEN
Solar/Wind Harmer
0.004
971065AG2-659 GEN
Solar/Wind Harmer
4.952
316129AC1-054 GEN
Solar/Wind Harmer
0.422
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971795AH1-408 GEN
Solar/Wind Harmer
6.656
960081AF2-299 GEN
Solar/Wind Harmer
0.732
3145783HORNRTN
Solar/Wind Harmer
0.069
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
0.296
970919AG2-571 GEN
Solar/Wind Harmer
2.029
970087AG2-069 GEN
Solar/Wind Harmer
4.556
316322AB2-045
Solar/Wind Helper
0.968
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.445
3144293JTRSVLE
50/50
1.183
3144293JTRSVLE
50/50
0.996
970535AG2-341 GEN
50/50
2.851
3152661PLYWOOD A
50/50
0.269
3151041BRUNSWICKG3
50/50
0.765
972187AH1-678 GEN
50/50
1.756
970301AG2-198 GEN
Solar/Wind Harmer
16.182
3147133PAMPLIN
Solar/Wind Harmer
0.375
3147133PAMPLIN
Solar/Wind Harmer
0.3
958211AF2-115 GEN
Solar/Wind Harmer
4.203
963191AG1-168 GEN
Solar/Wind Harmer
1.401
971741AH1-377 GEN
Solar/Wind Harmer
33.06
316034AC1-036 C
Solar/Wind Harmer
0.02
970323AG2-213 GEN
Solar/Wind Harmer
11.759
971775AH1-396 GEN
Solar/Wind Harmer
0.441
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
7.224
939181AE1-148 GEN
Solar/Wind Harmer
6.94
964791AG1-342 GEN
Solar/Wind Harmer
2.755
3146843MT LREL
Solar/Wind Harmer
0.143
3146843MT LREL
Solar/Wind Harmer
0.143
970099AG2-077 GEN
Solar/Wind Harmer
13.837
970933AG2-581 GEN
Solar/Wind Harmer
6.964
316181AB2-040 GEN
Solar/Wind Harmer
0.107
3145593CAROLNA
Solar/Wind Harmer
0.07
3145593CAROLNA
Solar/Wind Harmer
0.07
966811AG1-552 GEN
Solar/Wind Harmer
0.763
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.221
3145783HORNRTN
Solar/Wind Harmer
0.977
3145783HORNRTN
Solar/Wind Harmer
0.305
3145783HORNRTN
Solar/Wind Harmer
0.122
316222AC1-221 GEN
Solar/Wind Harmer
0.284
316426AA2-053 GEN
Solar/Wind Harmer
0.225
942751AE2-291 GEN
Solar/Wind Harmer
3.338
316274AC1-208 GEN
Solar/Wind Harmer
0.311
3146776BUCKING
Solar/Wind Helper
3.475
3146776BUCKING
Solar/Wind Helper
0.282
315821AE2-092 GEN
Solar/Wind Helper
2.978
3144293JTRSVLE
50/50
1.183
3151591KERR 2
50/50
0.279
970413AG2-270 GEN
50/50
12.485
3151261ROARAP2
50/50
0.086
3151031BRUNSWICKG2
50/50
0.765
3146926FARMVIL
Solar/Wind Harmer
0.316
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.045
3147133PAMPLIN
Solar/Wind Harmer
1.178
971193AH1-056 GEN
Solar/Wind Harmer
22.863
963181AG1-167 GEN
Solar/Wind Harmer
1.401
959311AF2-222 GEN
Solar/Wind Harmer
25.479
970257AG2-171 GEN
Solar/Wind Harmer
8.819
315785AD2-033 C
Solar/Wind Harmer
2.117
964241AG1-285 GEN
Solar/Wind Harmer
14.665
316131AB2-060 GEN
Solar/Wind Harmer
0.615
316478AD1-087 GEN
Solar/Wind Harmer
0.466
316486AD2-202 GEN
Solar/Wind Harmer
0.137
3147043LAWRENC
Solar/Wind Harmer
0.066
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.708
971683AH1-343 GEN
Solar/Wind Harmer
3.476
313506AB2-031 GEN
Solar/Wind Harmer
0.227
316283AC2-100 C
Solar/Wind Harmer
0.132
316210AC1-098 GEN
Solar/Wind Harmer
0.531
970917AG2-570 GEN
Solar/Wind Harmer
5.072
316327AA2-057 GEN
Solar/Wind Harmer
0.085
3146776BUCKING
Solar/Wind Helper
0.313
316313AB2-026
Solar/Wind Helper
0.338
316258AE1-075 C
Solar/Wind Helper
0.304
316405AF2-144 C
Solar/Wind Helper
0.253
3148013FISHERV
Solar/Wind Helper
0.123
CPLELTFEXP_CPLE->PJM
CLTF
3.789
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.54
LAGNLTFEXP_LAGN->PJM
CLTF
1.976
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.656
TVALTFEXP_TVA->PJM
CLTF
0.971
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.153
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.217
MECLTFEXP_MEC->PJM
CLTF
0.756
SIGELTFEXP_SIGE->PJM
CLTF
0.021
NYPJM->LTFIMP_NY
CLTF
0.298
LGEELTFEXP_LGEE->PJM
CLTF
0.232
WECLTFEXP_WEC->PJM
CLTF
0.123

Details for AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:132.79 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:758.93
MW Contribution:29.36
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
971967AH1-528 GEN
Solar/Wind Harmer
55.717
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
316118AC1-105 GEN
Solar/Wind Harmer
0.376
970865AG2-541 GEN
Solar/Wind Harmer
4.593
316123AC1-075 GEN
Solar/Wind Harmer
0.152
970165AG2-112 GEN
Solar/Wind Harmer
0.903
970163AG2-111 GEN
Solar/Wind Harmer
0.862
970831AG2-522 GEN
Solar/Wind Harmer
4.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
971629AH1-314 GEN
50/50
5.006
962491AG1-098 GEN
Solar/Wind Harmer
22.331
315693AD1-088 GEN
Solar/Wind Harmer
18.25
957481AF2-042 GEN
Solar/Wind Harmer
90.747
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.071
316129AC1-054 GEN
Solar/Wind Harmer
0.427
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
970909AG2-566 GEN
Solar/Wind Harmer
6.347
316478AD1-087 GEN
Solar/Wind Harmer
1.094
316486AD2-202 GEN
Solar/Wind Harmer
0.321
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.01
971683AH1-343 GEN
Solar/Wind Harmer
5.256
316283AC2-100 C
Solar/Wind Harmer
0.206
316131AB2-060 GEN
Solar/Wind Harmer
0.208
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
3152661PLYWOOD A
50/50
0.346
970535AG2-341 GEN
50/50
1.993
970301AG2-198 GEN
Solar/Wind Harmer
25.388
971741AH1-377 GEN
Solar/Wind Harmer
54.138
970933AG2-581 GEN
Solar/Wind Harmer
27.859
970099AG2-077 GEN
Solar/Wind Harmer
36.299
939181AE1-148 GEN
Solar/Wind Harmer
6.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.689
316222AC1-221 GEN
Solar/Wind Harmer
0.447
942751AE2-291 GEN
Solar/Wind Harmer
5.336
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.22 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:744.24
MW Contribution:29.36
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
970909AG2-566 GEN
Solar/Wind Harmer
6.347
316478AD1-087 GEN
Solar/Wind Harmer
1.094
316486AD2-202 GEN
Solar/Wind Harmer
0.321
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.01
971683AH1-343 GEN
Solar/Wind Harmer
5.256
316283AC2-100 C
Solar/Wind Harmer
0.206
316131AB2-060 GEN
Solar/Wind Harmer
0.208
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
316118AC1-105 GEN
Solar/Wind Harmer
0.376
970865AG2-541 GEN
Solar/Wind Harmer
4.593
316123AC1-075 GEN
Solar/Wind Harmer
0.152
970165AG2-112 GEN
Solar/Wind Harmer
0.903
970163AG2-111 GEN
Solar/Wind Harmer
0.862
970831AG2-522 GEN
Solar/Wind Harmer
4.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3152661PLYWOOD A
50/50
0.346
970535AG2-341 GEN
50/50
1.993
970301AG2-198 GEN
Solar/Wind Harmer
25.388
971741AH1-377 GEN
Solar/Wind Harmer
54.138
970099AG2-077 GEN
Solar/Wind Harmer
36.299
939181AE1-148 GEN
Solar/Wind Harmer
6.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.689
316222AC1-221 GEN
Solar/Wind Harmer
0.447
942751AE2-291 GEN
Solar/Wind Harmer
5.336
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
971629AH1-314 GEN
50/50
5.006
962491AG1-098 GEN
Solar/Wind Harmer
22.331
315693AD1-088 GEN
Solar/Wind Harmer
18.25
957481AF2-042 GEN
Solar/Wind Harmer
90.747
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.071
316129AC1-054 GEN
Solar/Wind Harmer
0.427
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:129.97 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:908.5
MW Contribution:29.41
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.708
3151611KERR 4
50/50
0.302
3151621KERR 5
50/50
0.302
3151631KERR 6
50/50
0.302
3151641KERR 7
50/50
0.302
971967AH1-528 GEN
Solar/Wind Harmer
73.672
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.131
970865AG2-541 GEN
Solar/Wind Harmer
6.075
316123AC1-075 GEN
Solar/Wind Harmer
1.358
970165AG2-112 GEN
Solar/Wind Harmer
1.195
970163AG2-111 GEN
Solar/Wind Harmer
1.14
970831AG2-522 GEN
Solar/Wind Harmer
6.069
316239AB2-077_GEN
Solar/Wind Harmer
0.274
316238AB2-078_GEN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Harmer
1.371
270457AD2-023 GEN
Solar/Wind Harmer
0.695
270494AE1-108_GEN
Solar/Wind Helper
2.769
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3151531CLOVER1
50/50
6.74
3151601KERR 3
50/50
0.302
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.44
315693AD1-088 GEN
Solar/Wind Harmer
21.388
957481AF2-042 GEN
Solar/Wind Harmer
119.681
315687AD1-152 GEN
Solar/Wind Harmer
3.524
316003AC1-222 GEN
Solar/Wind Harmer
1.683
970401AG2-262 GEN
Solar/Wind Harmer
0.932
971065AG2-659 GEN
Solar/Wind Harmer
6.697
316129AC1-054 GEN
Solar/Wind Harmer
1.121
316237AB2-079_GEN
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Helper
0.44
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
1.003
3152661PLYWOOD A
50/50
0.348
970535AG2-341 GEN
50/50
2.001
970301AG2-198 GEN
Solar/Wind Harmer
33.445
971741AH1-377 GEN
Solar/Wind Harmer
71.327
970933AG2-581 GEN
Solar/Wind Harmer
36.739
970099AG2-077 GEN
Solar/Wind Harmer
47.872
939181AE1-148 GEN
Solar/Wind Harmer
8.421
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.05
962561AG1-105 GEN
Solar/Wind Harmer
7.525
316222AC1-221 GEN
Solar/Wind Harmer
1.236
942751AE2-291 GEN
Solar/Wind Harmer
7.063
313527AB2-043 GEN
Solar/Wind Harmer
1.361
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.338
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.919
970413AG2-270 GEN
50/50
29.414
3151591KERR 2
50/50
0.302
970909AG2-566 GEN
Solar/Wind Harmer
6.35
316478AD1-087 GEN
Solar/Wind Harmer
3.055
316486AD2-202 GEN
Solar/Wind Harmer
0.895
316248AF1-058 C
Solar/Wind Harmer
0.559
960061AF2-297 GEN
Solar/Wind Harmer
9.268
971683AH1-343 GEN
Solar/Wind Harmer
6.951
316283AC2-100 C
Solar/Wind Harmer
1.124
316131AB2-060 GEN
Solar/Wind Harmer
0.808
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.542
3147133PAMPLIN
Solar/Wind Helper
1.062
316313AB2-026
Solar/Wind Helper
0.243
316258AE1-075 C
Solar/Wind Helper
0.219
316405AF2-144 C
Solar/Wind Helper
0.182
CPLELTFEXP_CPLE->PJM
CLTF
4.232
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.165
LAGNLTFEXP_LAGN->PJM
CLTF
2.703
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.92
TVALTFEXP_TVA->PJM
CLTF
1.347
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.6
MECLTFEXP_MEC->PJM
CLTF
1.297
SIGELTFEXP_SIGE->PJM
CLTF
0.038
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.461
WECLTFEXP_WEC->PJM
CLTF
0.241

Details for AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:129.93 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:908.21
MW Contribution:29.41
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
29.414
3151591KERR 2
50/50
0.302
970909AG2-566 GEN
Solar/Wind Harmer
6.35
316478AD1-087 GEN
Solar/Wind Harmer
3.055
316486AD2-202 GEN
Solar/Wind Harmer
0.895
316248AF1-058 C
Solar/Wind Harmer
0.559
960061AF2-297 GEN
Solar/Wind Harmer
9.268
971683AH1-343 GEN
Solar/Wind Harmer
6.951
316283AC2-100 C
Solar/Wind Harmer
1.124
316131AB2-060 GEN
Solar/Wind Harmer
0.808
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.542
3147133PAMPLIN
Solar/Wind Helper
1.062
316313AB2-026
Solar/Wind Helper
0.243
316258AE1-075 C
Solar/Wind Helper
0.219
316405AF2-144 C
Solar/Wind Helper
0.182
3151541CLOVER2
50/50
6.708
3151611KERR 4
50/50
0.302
3151621KERR 5
50/50
0.302
3151631KERR 6
50/50
0.302
3151641KERR 7
50/50
0.302
971967AH1-528 GEN
Solar/Wind Harmer
73.672
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.131
970865AG2-541 GEN
Solar/Wind Harmer
6.075
316123AC1-075 GEN
Solar/Wind Harmer
1.358
970165AG2-112 GEN
Solar/Wind Harmer
1.195
970163AG2-111 GEN
Solar/Wind Harmer
1.14
970831AG2-522 GEN
Solar/Wind Harmer
6.069
316239AB2-077_GEN
Solar/Wind Harmer
0.274
316238AB2-078_GEN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Harmer
1.371
270457AD2-023 GEN
Solar/Wind Harmer
0.695
270494AE1-108_GEN
Solar/Wind Helper
2.769
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3151531CLOVER1
50/50
6.74
3151601KERR 3
50/50
0.302
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.44
315693AD1-088 GEN
Solar/Wind Harmer
21.388
957481AF2-042 GEN
Solar/Wind Harmer
119.681
315687AD1-152 GEN
Solar/Wind Harmer
3.524
316003AC1-222 GEN
Solar/Wind Harmer
1.683
970401AG2-262 GEN
Solar/Wind Harmer
0.932
971065AG2-659 GEN
Solar/Wind Harmer
6.697
316129AC1-054 GEN
Solar/Wind Harmer
1.121
316237AB2-079_GEN
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Helper
0.44
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
1.003
3152661PLYWOOD A
50/50
0.348
970535AG2-341 GEN
50/50
2.001
970301AG2-198 GEN
Solar/Wind Harmer
33.445
971741AH1-377 GEN
Solar/Wind Harmer
71.327
970933AG2-581 GEN
Solar/Wind Harmer
36.739
970099AG2-077 GEN
Solar/Wind Harmer
47.872
939181AE1-148 GEN
Solar/Wind Harmer
8.421
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.05
962561AG1-105 GEN
Solar/Wind Harmer
7.525
316222AC1-221 GEN
Solar/Wind Harmer
1.236
942751AE2-291 GEN
Solar/Wind Harmer
7.063
313527AB2-043 GEN
Solar/Wind Harmer
1.361
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.338
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.919
CPLELTFEXP_CPLE->PJM
CLTF
4.232
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.165
LAGNLTFEXP_LAGN->PJM
CLTF
2.703
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.92
TVALTFEXP_TVA->PJM
CLTF
1.347
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.6
MECLTFEXP_MEC->PJM
CLTF
1.297
SIGELTFEXP_SIGE->PJM
CLTF
0.038
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.461
WECLTFEXP_WEC->PJM
CLTF
0.241

Details for AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.73 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:885.86
MW Contribution:29.36
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
971967AH1-528 GEN
Solar/Wind Harmer
73.556
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.126
970865AG2-541 GEN
Solar/Wind Harmer
6.047
316123AC1-075 GEN
Solar/Wind Harmer
1.351
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.135
970831AG2-522 GEN
Solar/Wind Harmer
6.052
316239AB2-077_GEN
Solar/Wind Harmer
0.273
3152661PLYWOOD A
50/50
0.346
970301AG2-198 GEN
Solar/Wind Harmer
33.428
971741AH1-377 GEN
Solar/Wind Harmer
71.281
970933AG2-581 GEN
Solar/Wind Harmer
36.681
970099AG2-077 GEN
Solar/Wind Harmer
47.793
939181AE1-148 GEN
Solar/Wind Harmer
8.391
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.036
962561AG1-105 GEN
Solar/Wind Harmer
7.49
316222AC1-221 GEN
Solar/Wind Harmer
1.223
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
970909AG2-566 GEN
Solar/Wind Harmer
6.347
316478AD1-087 GEN
Solar/Wind Harmer
3.05
316486AD2-202 GEN
Solar/Wind Harmer
0.893
316248AF1-058 C
Solar/Wind Harmer
0.556
960061AF2-297 GEN
Solar/Wind Harmer
9.23
971683AH1-343 GEN
Solar/Wind Harmer
6.92
316283AC2-100 C
Solar/Wind Harmer
1.112
316131AB2-060 GEN
Solar/Wind Harmer
0.803
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.403
315693AD1-088 GEN
Solar/Wind Harmer
21.359
957481AF2-042 GEN
Solar/Wind Harmer
119.484
315687AD1-152 GEN
Solar/Wind Harmer
3.515
316003AC1-222 GEN
Solar/Wind Harmer
1.676
970401AG2-262 GEN
Solar/Wind Harmer
0.928
971065AG2-659 GEN
Solar/Wind Harmer
6.677
316129AC1-054 GEN
Solar/Wind Harmer
1.118
316237AB2-079_GEN
Solar/Wind Harmer
0.273
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
942751AE2-291 GEN
Solar/Wind Harmer
7.025
313527AB2-043 GEN
Solar/Wind Harmer
1.353
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
316238AB2-078_GEN
Solar/Wind Harmer
0.273
270455AD2-022 GEN
Solar/Wind Harmer
1.35
270457AD2-023 GEN
Solar/Wind Harmer
0.684
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.78 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:844.27
MW Contribution:29.36
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.126
970865AG2-541 GEN
Solar/Wind Harmer
6.047
316123AC1-075 GEN
Solar/Wind Harmer
1.351
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.135
970831AG2-522 GEN
Solar/Wind Harmer
6.052
316239AB2-077_GEN
Solar/Wind Harmer
0.273
316238AB2-078_GEN
Solar/Wind Harmer
0.273
270455AD2-022 GEN
Solar/Wind Harmer
1.35
270457AD2-023 GEN
Solar/Wind Harmer
0.684
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
970909AG2-566 GEN
Solar/Wind Harmer
6.347
316478AD1-087 GEN
Solar/Wind Harmer
3.05
316486AD2-202 GEN
Solar/Wind Harmer
0.893
316248AF1-058 C
Solar/Wind Harmer
0.556
960061AF2-297 GEN
Solar/Wind Harmer
9.23
971683AH1-343 GEN
Solar/Wind Harmer
6.92
316283AC2-100 C
Solar/Wind Harmer
1.112
316131AB2-060 GEN
Solar/Wind Harmer
0.803
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.403
315693AD1-088 GEN
Solar/Wind Harmer
21.359
957481AF2-042 GEN
Solar/Wind Harmer
119.484
315687AD1-152 GEN
Solar/Wind Harmer
3.515
316003AC1-222 GEN
Solar/Wind Harmer
1.676
970401AG2-262 GEN
Solar/Wind Harmer
0.928
971065AG2-659 GEN
Solar/Wind Harmer
6.677
316129AC1-054 GEN
Solar/Wind Harmer
1.118
316237AB2-079_GEN
Solar/Wind Harmer
0.273
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
3152661PLYWOOD A
50/50
0.346
970301AG2-198 GEN
Solar/Wind Harmer
33.428
971741AH1-377 GEN
Solar/Wind Harmer
71.281
970099AG2-077 GEN
Solar/Wind Harmer
47.793
939181AE1-148 GEN
Solar/Wind Harmer
8.391
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.036
962561AG1-105 GEN
Solar/Wind Harmer
7.49
316222AC1-221 GEN
Solar/Wind Harmer
1.223
942751AE2-291 GEN
Solar/Wind Harmer
7.025
313527AB2-043 GEN
Solar/Wind Harmer
1.353
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.78 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:844.27
MW Contribution:29.36
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.126
970865AG2-541 GEN
Solar/Wind Harmer
6.047
316123AC1-075 GEN
Solar/Wind Harmer
1.351
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.135
970831AG2-522 GEN
Solar/Wind Harmer
6.052
316239AB2-077_GEN
Solar/Wind Harmer
0.273
316238AB2-078_GEN
Solar/Wind Harmer
0.273
270455AD2-022 GEN
Solar/Wind Harmer
1.35
270457AD2-023 GEN
Solar/Wind Harmer
0.684
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
970909AG2-566 GEN
Solar/Wind Harmer
6.347
316478AD1-087 GEN
Solar/Wind Harmer
3.05
316486AD2-202 GEN
Solar/Wind Harmer
0.893
316248AF1-058 C
Solar/Wind Harmer
0.556
960061AF2-297 GEN
Solar/Wind Harmer
9.23
971683AH1-343 GEN
Solar/Wind Harmer
6.92
316283AC2-100 C
Solar/Wind Harmer
1.112
316131AB2-060 GEN
Solar/Wind Harmer
0.803
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.403
315693AD1-088 GEN
Solar/Wind Harmer
21.359
957481AF2-042 GEN
Solar/Wind Harmer
119.484
315687AD1-152 GEN
Solar/Wind Harmer
3.515
316003AC1-222 GEN
Solar/Wind Harmer
1.676
970401AG2-262 GEN
Solar/Wind Harmer
0.928
971065AG2-659 GEN
Solar/Wind Harmer
6.677
316129AC1-054 GEN
Solar/Wind Harmer
1.118
316237AB2-079_GEN
Solar/Wind Harmer
0.273
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
3152661PLYWOOD A
50/50
0.346
970301AG2-198 GEN
Solar/Wind Harmer
33.428
971741AH1-377 GEN
Solar/Wind Harmer
71.281
970099AG2-077 GEN
Solar/Wind Harmer
47.793
939181AE1-148 GEN
Solar/Wind Harmer
8.391
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.036
962561AG1-105 GEN
Solar/Wind Harmer
7.49
316222AC1-221 GEN
Solar/Wind Harmer
1.223
942751AE2-291 GEN
Solar/Wind Harmer
7.025
313527AB2-043 GEN
Solar/Wind Harmer
1.353
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:129.2 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5258.72
MW Contribution:40.85
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
44.982
970099AG2-077 GEN
Solar/Wind Harmer
50.723
971741AH1-377 GEN
Solar/Wind Harmer
33.569
970301AG2-198 GEN
Solar/Wind Harmer
13.228
3146843MT LREL
Solar/Wind Harmer
0.286
3146843MT LREL
Solar/Wind Harmer
0.286
964791AG1-342 GEN
Solar/Wind Harmer
5.488
316222AC1-221 GEN
Solar/Wind Harmer
1.175
962561AG1-105 GEN
Solar/Wind Harmer
13.485
939181AE1-148 GEN
Solar/Wind Harmer
12.41
313527AB2-043 GEN
Solar/Wind Harmer
0.003
970323AG2-213 GEN
Solar/Wind Harmer
10.445
971775AH1-396 GEN
Solar/Wind Harmer
0.392
316034AC1-036 C
Solar/Wind Harmer
0.018
958211AF2-115 GEN
Solar/Wind Harmer
2.845
963191AG1-168 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.234
3147133PAMPLIN
Solar/Wind Harmer
0.187
942751AE2-291 GEN
Solar/Wind Harmer
11.476
270013AE1-250 PV
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.546
3146776BUCKING
Solar/Wind Harmer
0.044
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.276
316263AC1-034 GEN
Solar/Wind Harmer
4.449
961601AG1-000A GEN
Solar/Wind Harmer
2.035
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
47.73
957481AF2-042 GEN
Solar/Wind Harmer
126.807
315693AD1-088 GEN
Solar/Wind Harmer
20.818
962491AG1-098 GEN
Solar/Wind Harmer
24.385
315687AD1-152 GEN
Solar/Wind Harmer
0.013
316003AC1-222 GEN
Solar/Wind Harmer
0.008
970401AG2-262 GEN
Solar/Wind Harmer
1.677
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
17.979
963171AG1-166 GEN
Solar/Wind Harmer
1.264
971563AH1-280 GEN
Solar/Wind Harmer
2.529
3146926FARMVIL
Solar/Wind Harmer
0.131
971065AG2-659 GEN
Solar/Wind Harmer
8.445
316129AC1-054 GEN
Solar/Wind Harmer
0.698
970223AG2-152 GEN
Solar/Wind Harmer
12.094
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.088
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.055
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.099
941801AE2-185 GEN
Solar/Wind Harmer
4.212
270030AE2-140 GEN
Solar/Wind Harmer
13.804
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.094
316359AB2-059 GEN
Solar/Wind Harmer
0.421
316049AB1-081 GEN
Solar/Wind Harmer
0.67
3142053HEARTS
Solar/Wind Harmer
0.206
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
970673AG2-436 GEN
Solar/Wind Harmer
149.315
970673AG2-436 GEN
Solar/Wind Harmer
99.544
971967AH1-528 GEN
Solar/Wind Harmer
95.481
970085AG2-068 GEN
Solar/Wind Harmer
31.82
970581AG2-369 GEN
Solar/Wind Harmer
27.365
3147173SINAI
Solar/Wind Harmer
0.309
3147243WELCO
Solar/Wind Harmer
0.193
316118AC1-105 GEN
Solar/Wind Harmer
0.768
970865AG2-541 GEN
Solar/Wind Harmer
9.078
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.118
3144303KENBRDG
Solar/Wind Harmer
0.196
970683AG2-441 GEN
Solar/Wind Harmer
16.053
970681AG2-440 GEN
Solar/Wind Harmer
12.842
946301AF1-294 GEN
Solar/Wind Harmer
4.678
961791AG1-021 GEN
Solar/Wind Harmer
2.276
315657AE1-056 GEN
Solar/Wind Harmer
8.085
316123AC1-075 GEN
Solar/Wind Harmer
0.315
970165AG2-112 GEN
Solar/Wind Harmer
1.87
970163AG2-111 GEN
Solar/Wind Harmer
1.784
970831AG2-522 GEN
Solar/Wind Harmer
7.35
970285AG2-188 GEN
Solar/Wind Harmer
12.402
971845AH1-439 GEN
Solar/Wind Harmer
6.507
270069AE2-166 C O1
Solar/Wind Harmer
0.004
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
53.421
316478AD1-087 GEN
Solar/Wind Harmer
1.525
316486AD2-202 GEN
Solar/Wind Harmer
0.448
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
13.182
316283AC2-100 C
Solar/Wind Harmer
0.55
971683AH1-343 GEN
Solar/Wind Harmer
10.2
316131AB2-060 GEN
Solar/Wind Harmer
0.796
964241AG1-285 GEN
Solar/Wind Harmer
16.703
315785AD2-033 C
Solar/Wind Harmer
2.003
970257AG2-171 GEN
Solar/Wind Harmer
7.834
959311AF2-222 GEN
Solar/Wind Harmer
21.656
963181AG1-167 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.736
971193AH1-056 GEN
Solar/Wind Harmer
14.274
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.131
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
0.943
3146776BUCKING
Solar/Wind Harmer
0.049
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.212
270336AE1-100 GEN
Solar/Wind Harmer
0.003
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.117
971623AH1-311 GEN
Solar/Wind Harmer
0.234
961601AG1-000A GEN
Solar/Wind Harmer
8.141
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221
NYPJM->LTFIMP_NY
CLTF
2.382
LGEELTFEXP_LGEE->PJM
CLTF
2.675
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51192_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51192_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.25 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5708.12
MW Contribution:40.85
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
62.844
957481AF2-042 GEN
Solar/Wind Harmer
166.962
315693AD1-088 GEN
Solar/Wind Harmer
24.364
962491AG1-098 GEN
Solar/Wind Harmer
32.107
315687AD1-152 GEN
Solar/Wind Harmer
5.339
316003AC1-222 GEN
Solar/Wind Harmer
3.203
970401AG2-262 GEN
Solar/Wind Harmer
2.096
316237AB2-079_GEN
Solar/Wind Harmer
0.866
970685AG2-442 GEN
Solar/Wind Harmer
23.673
963171AG1-166 GEN
Solar/Wind Harmer
3.329
971563AH1-280 GEN
Solar/Wind Harmer
3.329
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.119
316129AC1-054 GEN
Solar/Wind Harmer
1.828
970223AG2-152 GEN
Solar/Wind Harmer
17.247
270016AE1-250 BESS
Solar/Wind Harmer
2.846
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.591
316322AB2-045
Solar/Wind Harmer
0.516
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.545
270030AE2-140 GEN
Solar/Wind Harmer
19.786
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.774
316049AB1-081 GEN
Solar/Wind Harmer
1.419
3142053HEARTS
Solar/Wind Harmer
0.155
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
970673AG2-436 GEN
Solar/Wind Harmer
165.209
970673AG2-436 GEN
Solar/Wind Harmer
83.65
971967AH1-528 GEN
Solar/Wind Harmer
126.052
970085AG2-068 GEN
Solar/Wind Harmer
41.896
970581AG2-369 GEN
Solar/Wind Harmer
36.031
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.3
970865AG2-541 GEN
Solar/Wind Harmer
11.953
316239AB2-077_GEN
Solar/Wind Harmer
0.866
316238AB2-078_GEN
Solar/Wind Harmer
0.866
971443AH1-215 GEN
Solar/Wind Harmer
5.422
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.136
970681AG2-440 GEN
Solar/Wind Harmer
16.909
946301AF1-294 GEN
Solar/Wind Harmer
6.825
961791AG1-021 GEN
Solar/Wind Harmer
3.329
270455AD2-022 GEN
Solar/Wind Harmer
4.714
270457AD2-023 GEN
Solar/Wind Harmer
2.39
315657AE1-056 GEN
Solar/Wind Harmer
9.877
316123AC1-075 GEN
Solar/Wind Harmer
2.797
970165AG2-112 GEN
Solar/Wind Harmer
2.462
970163AG2-111 GEN
Solar/Wind Harmer
2.349
970831AG2-522 GEN
Solar/Wind Harmer
9.678
970285AG2-188 GEN
Solar/Wind Harmer
15.412
971845AH1-439 GEN
Solar/Wind Harmer
8.567
270069AE2-166 C O1
Solar/Wind Harmer
2.422
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
168.81
316478AD1-087 GEN
Solar/Wind Harmer
4.25
316486AD2-202 GEN
Solar/Wind Harmer
1.245
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
1.046
960061AF2-297 GEN
Solar/Wind Harmer
17.357
316283AC2-100 C
Solar/Wind Harmer
2.974
971683AH1-343 GEN
Solar/Wind Harmer
13.43
316131AB2-060 GEN
Solar/Wind Harmer
3.068
964241AG1-285 GEN
Solar/Wind Harmer
21.992
315785AD2-033 C
Solar/Wind Harmer
6.274
970257AG2-171 GEN
Solar/Wind Harmer
10.314
959311AF2-222 GEN
Solar/Wind Harmer
28.571
963181AG1-167 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.462
942461AE2-259 GEN
Solar/Wind Harmer
3.832
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.378
270197AD1-017 GEN1
Solar/Wind Harmer
1.68
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.844
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.545
270336AE1-100 GEN
Solar/Wind Harmer
1.569
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
5.12
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
59.226
970099AG2-077 GEN
Solar/Wind Harmer
66.785
971741AH1-377 GEN
Solar/Wind Harmer
44.199
970301AG2-198 GEN
Solar/Wind Harmer
17.416
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.86
316222AC1-221 GEN
Solar/Wind Harmer
3.218
962561AG1-105 GEN
Solar/Wind Harmer
17.755
939181AE1-148 GEN
Solar/Wind Harmer
16.34
313527AB2-043 GEN
Solar/Wind Harmer
4.631
970323AG2-213 GEN
Solar/Wind Harmer
13.752
971775AH1-396 GEN
Solar/Wind Harmer
1.958
316034AC1-036 C
Solar/Wind Harmer
0.51
958211AF2-115 GEN
Solar/Wind Harmer
4.162
963191AG1-168 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.11
270013AE1-250 PV
Solar/Wind Harmer
2.846
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.4
316197AC1-042 GEN
Solar/Wind Harmer
1.819
942671AE2-283 GEN
Solar/Wind Harmer
4.898
316263AC1-034 GEN
Solar/Wind Harmer
6.166
961601AG1-000A GEN
Solar/Wind Harmer
5.056
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221
NYPJM->LTFIMP_NY
CLTF
2.382
LGEELTFEXP_LGEE->PJM
CLTF
2.675
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51172_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51172_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.76 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5683.44
MW Contribution:40.64
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
19.115
963041AG1-153 GEN
50/50
16.957
3151541CLOVER2
50/50
9.268
3151611KERR 4
50/50
0.538
3151621KERR 5
50/50
0.538
3151631KERR 6
50/50
0.538
3151641KERR 7
50/50
0.538
970673AG2-436 GEN
Solar/Wind Harmer
164.043
970673AG2-436 GEN
Solar/Wind Harmer
83.06
971967AH1-528 GEN
Solar/Wind Harmer
125.223
3151031BRUNSWICKG2
50/50
8.374
970413AG2-270 GEN
50/50
40.637
3151591KERR 2
50/50
0.538
3144293JTRSVLE
50/50
0.8
970917AG2-570 GEN
Solar/Wind Harmer
167.695
316478AD1-087 GEN
Solar/Wind Harmer
4.227
316486AD2-202 GEN
Solar/Wind Harmer
1.238
970909AG2-566 GEN
Solar/Wind Harmer
3.291
316248AF1-058 C
Solar/Wind Harmer
1.043
960061AF2-297 GEN
Solar/Wind Harmer
17.305
316283AC2-100 C
Solar/Wind Harmer
2.965
971683AH1-343 GEN
Solar/Wind Harmer
13.39
316131AB2-060 GEN
Solar/Wind Harmer
3.076
964241AG1-285 GEN
Solar/Wind Harmer
22.038
315785AD2-033 C
Solar/Wind Harmer
6.282
970257AG2-171 GEN
Solar/Wind Harmer
10.326
959311AF2-222 GEN
Solar/Wind Harmer
28.597
963181AG1-167 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.082
315243AE2-183_GT3
50/50
11.056
3151051BRUNSWICKS1
50/50
17.38
3151021BRUNSWICKG1
50/50
8.374
971451AH1-221 GEN
50/50
25.435
3151531CLOVER1
50/50
9.312
3151601KERR 3
50/50
0.538
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.8
971629AH1-314 GEN
50/50
17.875
3151561HALLBR1
50/50
0.366
970919AG2-571 GEN
Solar/Wind Harmer
21.227
970087AG2-069 GEN
Solar/Wind Harmer
62.431
957481AF2-042 GEN
Solar/Wind Harmer
166.01
315693AD1-088 GEN
Solar/Wind Harmer
24.233
962491AG1-098 GEN
Solar/Wind Harmer
31.935
315687AD1-152 GEN
Solar/Wind Harmer
5.313
316003AC1-222 GEN
Solar/Wind Harmer
3.193
970401AG2-262 GEN
Solar/Wind Harmer
2.094
316237AB2-079_GEN
Solar/Wind Harmer
0.868
970685AG2-442 GEN
Solar/Wind Harmer
23.682
963171AG1-166 GEN
Solar/Wind Harmer
3.328
971563AH1-280 GEN
Solar/Wind Harmer
3.328
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.224
316129AC1-054 GEN
Solar/Wind Harmer
1.849
970223AG2-152 GEN
Solar/Wind Harmer
17.201
270016AE1-250 BESS
Solar/Wind Harmer
2.839
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.577
316322AB2-045
Solar/Wind Harmer
0.514
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.53
270030AE2-140 GEN
Solar/Wind Harmer
19.734
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.817
316049AB1-081 GEN
Solar/Wind Harmer
1.454
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.785
316375AC2-012 GEN
Solar/Wind Helper
1.014
3145336SMITFLD
Solar/Wind Helper
1.482
316388AE2-253 GEN
Solar/Wind Helper
1.397
3146456SLIGO L269
Solar/Wind Helper
0.359
970085AG2-068 GEN
Solar/Wind Harmer
41.62
970581AG2-369 GEN
Solar/Wind Harmer
35.794
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.295
970865AG2-541 GEN
Solar/Wind Harmer
11.917
316239AB2-077_GEN
Solar/Wind Harmer
0.868
316238AB2-078_GEN
Solar/Wind Harmer
0.868
971443AH1-215 GEN
Solar/Wind Harmer
5.428
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.145
970681AG2-440 GEN
Solar/Wind Harmer
16.916
946301AF1-294 GEN
Solar/Wind Harmer
6.823
961791AG1-021 GEN
Solar/Wind Harmer
3.328
270455AD2-022 GEN
Solar/Wind Harmer
4.701
270457AD2-023 GEN
Solar/Wind Harmer
2.384
315657AE1-056 GEN
Solar/Wind Harmer
9.869
316123AC1-075 GEN
Solar/Wind Harmer
2.789
970165AG2-112 GEN
Solar/Wind Harmer
2.455
970163AG2-111 GEN
Solar/Wind Harmer
2.342
970831AG2-522 GEN
Solar/Wind Harmer
9.813
970285AG2-188 GEN
Solar/Wind Harmer
15.354
971845AH1-439 GEN
Solar/Wind Harmer
8.535
270069AE2-166 C O1
Solar/Wind Harmer
2.415
319010AE1-072 C
Solar/Wind Helper
4.079
3143316POE
Solar/Wind Helper
1.407
316305AF2-043 C
Solar/Wind Helper
0.473
316369SG1_INVT
Solar/Wind Helper
1.664
957831AF2-077 GEN
Solar/Wind Helper
0.466
316132AB2-190 GEN1
Solar/Wind Helper
1.933
316349AD2-085 GEN
Solar/Wind Helper
1.523
313526AB2-022
Solar/Wind Helper
0.505
957601AF2-054 GEN
Solar/Wind Helper
0.438
3141873WAN 176
Solar/Wind Helper
0.065
315662AE1-191 GEN
Solar/Wind Helper
1.747
315666AE1-190 GEN
Solar/Wind Helper
0.437
316059AD1-063 C
Solar/Wind Helper
0.326
3141913WHIT STONE
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3138133OCRAN
Solar/Wind Helper
0.097
3143873LANEXA
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.128
316321Z2-027
Solar/Wind Helper
0.487
3145176PASQUOTANK
Solar/Wind Helper
0.198
3141813NORNECK
Solar/Wind Helper
0.304
316312AB1-027
Solar/Wind Helper
0.556
316233AE1-074 FULL
Solar/Wind Helper
0.44
316223AC1-118
Solar/Wind Helper
0.438
316315AB2-025 C
Solar/Wind Helper
0.418
315611Z1-036_GEN2
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
3130156CHOWAN
Solar/Wind Helper
0.226
315242AE2-183_GT2
50/50
11.056
315241AE2-183_GT1
50/50
10.988
972185AH1-677 GEN
50/50
39.858
3151041BRUNSWICKG3
50/50
8.374
972187AH1-678 GEN
50/50
19.217
3152661PLYWOOD A
50/50
0.67
970535AG2-341 GEN
50/50
4.577
3144293JTRSVLE
50/50
0.8
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
58.849
970099AG2-077 GEN
Solar/Wind Harmer
66.404
971741AH1-377 GEN
Solar/Wind Harmer
43.978
970301AG2-198 GEN
Solar/Wind Harmer
17.332
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.854
316222AC1-221 GEN
Solar/Wind Harmer
3.208
962561AG1-105 GEN
Solar/Wind Harmer
17.747
939181AE1-148 GEN
Solar/Wind Harmer
16.378
313527AB2-043 GEN
Solar/Wind Harmer
4.643
970323AG2-213 GEN
Solar/Wind Harmer
13.768
971775AH1-396 GEN
Solar/Wind Harmer
1.961
316034AC1-036 C
Solar/Wind Harmer
0.511
958211AF2-115 GEN
Solar/Wind Harmer
4.16
963191AG1-168 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.066
270013AE1-250 PV
Solar/Wind Harmer
2.839
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.394
316197AC1-042 GEN
Solar/Wind Harmer
1.815
942671AE2-283 GEN
Solar/Wind Harmer
4.885
316263AC1-034 GEN
Solar/Wind Harmer
6.316
961601AG1-000A GEN
Solar/Wind Harmer
5.186
316036AC1-147 C
Solar/Wind Helper
0.59
3142956BIRDNECK
Solar/Wind Helper
0.259
316316AC1-027 C
Solar/Wind Helper
0.606
316185AD1-033 GEN
Solar/Wind Helper
1.799
3145506HICKORY
Solar/Wind Helper
1.507
3145506HICKORY
Solar/Wind Helper
0.904
3145506HICKORY
Solar/Wind Helper
0.226
316236AE1-162_GEN
Solar/Wind Helper
0.498
316339AD2-160 GEN
Solar/Wind Helper
1.397
316018AA1-139 ULT2
Solar/Wind Helper
1.567
316017AA1-139 ULT1
Solar/Wind Helper
1.665
3137176SLIGO L2192
Solar/Wind Helper
1.432
3130086AYDLETT
Solar/Wind Helper
1.421
316033AB2-134 GEN
Solar/Wind Helper
1.19
315697AD1-025 GEN
Solar/Wind Helper
3.953
3146386ELIZ CT
Solar/Wind Helper
0.331
316240AF1-291 C
Solar/Wind Helper
0.444
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.318
316075AC2-137 C
Solar/Wind Helper
0.467
316077AC2-138 C
Solar/Wind Helper
0.286
316431W1029_GEN1
Solar/Wind Helper
1.225
316433W1029_GEN2
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3143526WINTERP
Solar/Wind Helper
1.499
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
966871AG1-558 GEN
Solar/Wind Helper
0.374
3144356SAPONY
Solar/Wind Helper
0.492
316468AD1-105 GEN
Solar/Wind Helper
1.305
971193AH1-056 GEN
Solar/Wind Harmer
16.449
942461AE2-259 GEN
Solar/Wind Harmer
3.824
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.375
270197AD1-017 GEN1
Solar/Wind Harmer
1.676
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.834
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.53
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.564
961601AG1-000A GEN
Solar/Wind Harmer
5.252
315773AC2-141 GEN
Solar/Wind Helper
9.163
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.058
3145336SMITFLD
Solar/Wind Helper
0.148
3146456SLIGO L269
Solar/Wind Helper
0.359
316382AG1-145 C
Solar/Wind Helper
0.469
315839AE2-212 C
Solar/Wind Helper
0.457
316320Y1-086
Solar/Wind Helper
0.148
316156AD2-030 GEN
Solar/Wind Helper
0.492
316280AD1-041 GEN
Solar/Wind Helper
1.092
3142946ENON
Solar/Wind Helper
0.105
316484AD2-074 GEN
Solar/Wind Helper
0.607
316404AE1-155 C
Solar/Wind Helper
2.624
316435W1029_GEN3
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3141906WESTMOR
Solar/Wind Helper
0.115
3146626S HERTFORD
Solar/Wind Helper
0.28
316473AC1-191 GEN
Solar/Wind Helper
1.696
3145273HOLLAND
Solar/Wind Helper
0.188
966881AG1-559 GEN
Solar/Wind Helper
0.329
3146376EDENTON
Solar/Wind Helper
0.226
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.402
316159AE1-175 C
Solar/Wind Helper
0.529
316381AD1-082 GEN
Solar/Wind Helper
1.758
316458AB2-190 GEN2
Solar/Wind Helper
1.933
3141766HARMONY
Solar/Wind Helper
0.065
3138133OCRAN
Solar/Wind Helper
0.193
3142433PROV 92
Solar/Wind Helper
1.275
3142543TWELFTH
Solar/Wind Helper
0.029
964211AG1-282 GEN
Solar/Wind Helper
0.412
3141726DUNNSVL
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.961
3146516WINFALL
Solar/Wind Helper
0.297
316337AD2-073 GEN
Solar/Wind Helper
0.448
3142416OLDCHRC
Solar/Wind Helper
0.759
3142416OLDCHRC
Solar/Wind Helper
0.291
3143526WINTERP
Solar/Wind Helper
1.499
3143226MDLTHAN
Solar/Wind Helper
0.284
315800Z1-036_GEN1
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
CPLELTFEXP_CPLE->PJM
CLTF
19.708
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.004
LAGNLTFEXP_LAGN->PJM
CLTF
14.626
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.161
TVALTFEXP_TVA->PJM
CLTF
7.294
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.554
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.081
MECLTFEXP_MEC->PJM
CLTF
7.343
SIGELTFEXP_SIGE->PJM
CLTF
0.22
NYPJM->LTFIMP_NY
CLTF
2.38
LGEELTFEXP_LGEE->PJM
CLTF
2.666
WECLTFEXP_WEC->PJM
CLTF
1.395
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 511T544_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T544_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.13 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5601.8
MW Contribution:40.27
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
10.962
3151051BRUNSWICKS1
50/50
17.232
3151021BRUNSWICKG1
50/50
8.303
971451AH1-221 GEN
50/50
25.218
3151531CLOVER1
50/50
9.227
3151601KERR 3
50/50
0.532
3151581KERR 1
50/50
0.19
3144293JTRSVLE
50/50
0.79
971629AH1-314 GEN
50/50
17.731
3151561HALLBR1
50/50
0.363
970919AG2-571 GEN
Solar/Wind Harmer
21.047
970087AG2-069 GEN
Solar/Wind Harmer
61.902
957481AF2-042 GEN
Solar/Wind Harmer
164.509
315693AD1-088 GEN
Solar/Wind Harmer
24.007
962491AG1-098 GEN
Solar/Wind Harmer
31.634
315687AD1-152 GEN
Solar/Wind Harmer
5.265
316003AC1-222 GEN
Solar/Wind Harmer
3.162
970401AG2-262 GEN
Solar/Wind Harmer
2.07
316237AB2-079_GEN
Solar/Wind Harmer
0.856
970685AG2-442 GEN
Solar/Wind Harmer
23.354
963171AG1-166 GEN
Solar/Wind Harmer
3.283
971563AH1-280 GEN
Solar/Wind Harmer
3.283
3146926FARMVIL
Solar/Wind Harmer
-0.014
971065AG2-659 GEN
Solar/Wind Harmer
11.094
316129AC1-054 GEN
Solar/Wind Harmer
1.827
970223AG2-152 GEN
Solar/Wind Harmer
17.059
270016AE1-250 BESS
Solar/Wind Harmer
2.815
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.528
316322AB2-045
Solar/Wind Harmer
0.506
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.477
270030AE2-140 GEN
Solar/Wind Harmer
19.567
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.809
316049AB1-081 GEN
Solar/Wind Harmer
1.448
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.244
316381AD1-082 GEN
Solar/Wind Helper
1.747
316375AC2-012 GEN
Solar/Wind Helper
0.879
3145336SMITFLD
Solar/Wind Helper
1.331
316458AB2-190 GEN2
Solar/Wind Helper
1.893
316159AE1-175 C
Solar/Wind Helper
0.497
316388AE2-253 GEN
Solar/Wind Helper
1.201
3142433PROV 92
Solar/Wind Helper
1.254
3142543TWELFTH
Solar/Wind Helper
0.03
3141766HARMONY
Solar/Wind Helper
0.062
3146456SLIGO L269
Solar/Wind Helper
0.308
3138133OCRAN
Solar/Wind Helper
0.185
316072AD1-144
Solar/Wind Helper
0.35
316246AF1-032 C
Solar/Wind Helper
0.342
964211AG1-282 GEN
Solar/Wind Helper
0.397
3141726DUNNSVL
Solar/Wind Helper
1.179
3143526WINTERP
Solar/Wind Helper
1.519
3142416OLDCHRC
Solar/Wind Helper
0.752
3143226MDLTHAN
Solar/Wind Helper
0.289
3142416OLDCHRC
Solar/Wind Helper
0.288
316337AD2-073 GEN
Solar/Wind Helper
0.434
3146516WINFALL
Solar/Wind Helper
0.813
3146516WINFALL
Solar/Wind Helper
0.251
315244AE2-183_ST
50/50
18.952
963041AG1-153 GEN
50/50
16.812
3151541CLOVER2
50/50
9.183
3151611KERR 4
50/50
0.532
3151621KERR 5
50/50
0.532
3151631KERR 6
50/50
0.532
3151641KERR 7
50/50
0.532
970673AG2-436 GEN
Solar/Wind Harmer
162.646
970673AG2-436 GEN
Solar/Wind Harmer
82.352
971967AH1-528 GEN
Solar/Wind Harmer
124.141
970085AG2-068 GEN
Solar/Wind Harmer
41.268
970581AG2-369 GEN
Solar/Wind Harmer
35.491
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.271
970865AG2-541 GEN
Solar/Wind Harmer
11.801
316239AB2-077_GEN
Solar/Wind Harmer
0.856
316238AB2-078_GEN
Solar/Wind Harmer
0.856
971443AH1-215 GEN
Solar/Wind Harmer
5.352
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
20.851
970681AG2-440 GEN
Solar/Wind Harmer
16.681
946301AF1-294 GEN
Solar/Wind Harmer
6.73
961791AG1-021 GEN
Solar/Wind Harmer
3.283
270455AD2-022 GEN
Solar/Wind Harmer
4.664
270457AD2-023 GEN
Solar/Wind Harmer
2.365
315657AE1-056 GEN
Solar/Wind Harmer
9.735
316123AC1-075 GEN
Solar/Wind Harmer
2.761
970165AG2-112 GEN
Solar/Wind Harmer
2.431
970163AG2-111 GEN
Solar/Wind Harmer
2.319
970831AG2-522 GEN
Solar/Wind Harmer
9.696
970285AG2-188 GEN
Solar/Wind Harmer
15.118
971845AH1-439 GEN
Solar/Wind Harmer
8.397
270069AE2-166 C O1
Solar/Wind Harmer
2.394
3143316POE
Solar/Wind Helper
1.57
316132AB2-190 GEN1
Solar/Wind Helper
1.893
316369SG1_INVT
Solar/Wind Helper
1.59
957831AF2-077 GEN
Solar/Wind Helper
0.437
316315AB2-025 C
Solar/Wind Helper
0.494
957601AF2-054 GEN
Solar/Wind Helper
0.418
3141873WAN 176
Solar/Wind Helper
0.062
315662AE1-191 GEN
Solar/Wind Helper
1.674
315666AE1-190 GEN
Solar/Wind Helper
0.419
3143873LANEXA
Solar/Wind Helper
0.186
316059AD1-063 C
Solar/Wind Helper
0.312
3141913WHIT STONE
Solar/Wind Helper
0.309
3138133OCRAN
Solar/Wind Helper
0.093
3141783LANCAST
Solar/Wind Helper
0.184
3141783LANCAST
Solar/Wind Helper
0.123
319010AE1-072 C
Solar/Wind Helper
3.5
316349AD2-085 GEN
Solar/Wind Helper
1.396
316305AF2-043 C
Solar/Wind Helper
0.402
3141813NORNECK
Solar/Wind Helper
0.293
316233AE1-074 FULL
Solar/Wind Helper
0.446
316312AB1-027
Solar/Wind Helper
0.55
313526AB2-022
Solar/Wind Helper
0.431
316223AC1-118
Solar/Wind Helper
0.424
3146486SUNBURY
Solar/Wind Helper
0.274
3146486SUNBURY
Solar/Wind Helper
0.274
316321Z2-027
Solar/Wind Helper
0.414
3145176PASQUOTANK
Solar/Wind Helper
0.168
3151031BRUNSWICKG2
50/50
8.303
970413AG2-270 GEN
50/50
40.265
3151591KERR 2
50/50
0.532
3144293JTRSVLE
50/50
0.79
970917AG2-570 GEN
Solar/Wind Harmer
166.275
316478AD1-087 GEN
Solar/Wind Harmer
4.189
316486AD2-202 GEN
Solar/Wind Harmer
1.227
970909AG2-566 GEN
Solar/Wind Harmer
3.255
316248AF1-058 C
Solar/Wind Harmer
1.033
960061AF2-297 GEN
Solar/Wind Harmer
17.135
316283AC2-100 C
Solar/Wind Harmer
2.94
971683AH1-343 GEN
Solar/Wind Harmer
13.259
316131AB2-060 GEN
Solar/Wind Harmer
3.032
964241AG1-285 GEN
Solar/Wind Harmer
21.724
315785AD2-033 C
Solar/Wind Harmer
6.194
970257AG2-171 GEN
Solar/Wind Harmer
10.181
959311AF2-222 GEN
Solar/Wind Harmer
28.197
963181AG1-167 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.081
971193AH1-056 GEN
Solar/Wind Harmer
16.225
942461AE2-259 GEN
Solar/Wind Harmer
3.773
3146926FARMVIL
Solar/Wind Harmer
-0.014
270018AE2-047 C O1
Solar/Wind Harmer
1.363
270197AD1-017 GEN1
Solar/Wind Harmer
1.661
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.802
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.477
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.551
961601AG1-000A GEN
Solar/Wind Harmer
5.225
315773AC2-141 GEN
Solar/Wind Helper
8.525
315839AE2-212 C
Solar/Wind Helper
0.497
3144536CHRHLND
Solar/Wind Helper
0.05
3144873MCLAUGH
Solar/Wind Helper
0.008
3145336SMITFLD
Solar/Wind Helper
0.133
316382AG1-145 C
Solar/Wind Helper
0.441
316156AD2-030 GEN
Solar/Wind Helper
0.47
3142946ENON
Solar/Wind Helper
0.104
316280AD1-041 GEN
Solar/Wind Helper
1.046
3146456SLIGO L269
Solar/Wind Helper
0.308
316484AD2-074 GEN
Solar/Wind Helper
0.583
316404AE1-155 C
Solar/Wind Helper
2.523
316320Y1-086
Solar/Wind Helper
0.126
316473AC1-191 GEN
Solar/Wind Helper
1.704
3141906WESTMOR
Solar/Wind Helper
0.111
316435W1029_GEN3
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
966881AG1-559 GEN
Solar/Wind Helper
0.328
3146626S HERTFORD
Solar/Wind Helper
0.236
315242AE2-183_GT2
50/50
10.962
315241AE2-183_GT1
50/50
10.894
972185AH1-677 GEN
50/50
39.518
3151041BRUNSWICKG3
50/50
8.303
972187AH1-678 GEN
50/50
19.053
3152661PLYWOOD A
50/50
0.663
970535AG2-341 GEN
50/50
4.519
3144293JTRSVLE
50/50
0.79
3144293JTRSVLE
50/50
0.665
970933AG2-581 GEN
Solar/Wind Harmer
58.334
970099AG2-077 GEN
Solar/Wind Harmer
65.804
971741AH1-377 GEN
Solar/Wind Harmer
43.523
970301AG2-198 GEN
Solar/Wind Harmer
17.145
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.775
316222AC1-221 GEN
Solar/Wind Harmer
3.182
962561AG1-105 GEN
Solar/Wind Harmer
17.536
939181AE1-148 GEN
Solar/Wind Harmer
16.186
313527AB2-043 GEN
Solar/Wind Harmer
4.576
970323AG2-213 GEN
Solar/Wind Harmer
13.574
971775AH1-396 GEN
Solar/Wind Harmer
1.933
316034AC1-036 C
Solar/Wind Harmer
0.503
958211AF2-115 GEN
Solar/Wind Harmer
4.103
963191AG1-168 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
14.918
270013AE1-250 PV
Solar/Wind Harmer
2.815
3146776BUCKING
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.37
316197AC1-042 GEN
Solar/Wind Harmer
1.797
942671AE2-283 GEN
Solar/Wind Harmer
4.838
316263AC1-034 GEN
Solar/Wind Harmer
6.29
961601AG1-000A GEN
Solar/Wind Harmer
5.16
316240AF1-291 C
Solar/Wind Helper
0.471
316036AC1-147 C
Solar/Wind Helper
0.511
316236AE1-162_GEN
Solar/Wind Helper
0.447
316316AC1-027 C
Solar/Wind Helper
0.524
3142956BIRDNECK
Solar/Wind Helper
0.223
316033AB2-134 GEN
Solar/Wind Helper
1.137
315697AD1-025 GEN
Solar/Wind Helper
3.779
316185AD1-033 GEN
Solar/Wind Helper
1.551
3145506HICKORY
Solar/Wind Helper
1.298
3145506HICKORY
Solar/Wind Helper
0.779
3145506HICKORY
Solar/Wind Helper
0.195
3144356SAPONY
Solar/Wind Helper
0.581
316339AD2-160 GEN
Solar/Wind Helper
1.201
316018AA1-139 ULT2
Solar/Wind Helper
1.346
316017AA1-139 ULT1
Solar/Wind Helper
1.43
3142946ENON
Solar/Wind Helper
0.031
3137176SLIGO L2192
Solar/Wind Helper
1.229
3130086AYDLETT
Solar/Wind Helper
1.219
316487AF1-042 GEN
Solar/Wind Helper
0.305
316075AC2-137 C
Solar/Wind Helper
0.459
316077AC2-138 C
Solar/Wind Helper
0.276
3143526WINTERP
Solar/Wind Helper
1.519
3146386ELIZ CT
Solar/Wind Helper
0.283
966871AG1-558 GEN
Solar/Wind Helper
0.376
316468AD1-105 GEN
Solar/Wind Helper
1.308
316431W1029_GEN1
Solar/Wind Helper
1.037
316433W1029_GEN2
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146626S HERTFORD
Solar/Wind Helper
0.236
3146626S HERTFORD
Solar/Wind Helper
0.236
CPLELTFEXP_CPLE->PJM
CLTF
19.58
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.279
LAGNLTFEXP_LAGN->PJM
CLTF
14.499
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.842
TVALTFEXP_TVA->PJM
CLTF
7.231
CBM West 1LTFEXP_CBM-W1->PJM
CBM
48.979
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.858
MECLTFEXP_MEC->PJM
CLTF
7.267
SIGELTFEXP_SIGE->PJM
CLTF
0.218
NYPJM->LTFIMP_NY
CLTF
2.38
LGEELTFEXP_LGEE->PJM
CLTF
2.637
WECLTFEXP_WEC->PJM
CLTF
1.38
AG2-052LTFEXP_AG2-052->PJM
LTF
0.074
AH1-155LTFEXP_AH1-155->PJM
LTF
0.111

Details for AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.99 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:969.01
MW Contribution:9.55
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
14.467
3151541CLOVER2
50/50
2.177
3151611KERR 4
50/50
0.135
3151621KERR 5
50/50
0.135
3151631KERR 6
50/50
0.135
3151641KERR 7
50/50
0.135
971447AH1-217 GEN
Solar/Wind Harmer
8.145
971845AH1-439 GEN
Solar/Wind Harmer
11.716
970285AG2-188 GEN
Solar/Wind Harmer
19.851
270494AE1-108_GEN
Solar/Wind Harmer
2.723
315657AE1-056 GEN
Solar/Wind Harmer
5.462
946301AF1-294 GEN
Solar/Wind Harmer
2.936
961791AG1-021 GEN
Solar/Wind Harmer
1.429
970683AG2-441 GEN
Solar/Wind Harmer
9.008
970681AG2-440 GEN
Solar/Wind Harmer
7.206
3144303KENBRDG
Solar/Wind Harmer
0.096
971443AH1-215 GEN
Solar/Wind Harmer
2.005
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.188
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.069
3147243WELCO
Solar/Wind Harmer
0.043
970865AG2-541 GEN
Solar/Wind Harmer
2.13
316123AC1-075 GEN
Solar/Wind Harmer
0.077
970165AG2-112 GEN
Solar/Wind Harmer
0.459
970163AG2-111 GEN
Solar/Wind Harmer
0.438
316233AE1-074 FULL
Solar/Wind Helper
0.38
316312AB1-027
Solar/Wind Helper
0.217
316132AB2-190 GEN1
Solar/Wind Helper
0.639
3151931BEARGRDN S1
50/50
3.828
3151911BEARGRDN G1
50/50
2.966
3144293JTRSVLE
50/50
0.503
3151531CLOVER1
50/50
2.188
3151601KERR 3
50/50
0.135
3151581KERR 1
50/50
0.048
970937AG2-583 GEN
Solar/Wind Harmer
28.699
972003AH1-546 GEN
Solar/Wind Harmer
13.118
971377AH1-170 GEN
Solar/Wind Harmer
3.027
3147623JAMES R
Solar/Wind Harmer
0.658
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
963171AG1-166 GEN
Solar/Wind Harmer
0.794
971563AH1-280 GEN
Solar/Wind Harmer
1.587
970685AG2-442 GEN
Solar/Wind Harmer
10.089
962491AG1-098 GEN
Solar/Wind Harmer
7.03
315693AD1-088 GEN
Solar/Wind Harmer
5.777
957481AF2-042 GEN
Solar/Wind Harmer
29.163
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.003
970401AG2-262 GEN
Solar/Wind Harmer
0.451
316003AC1-222 GEN
Solar/Wind Harmer
0.002
316336AC2-165 C
Solar/Wind Helper
5.135
3143226MDLTHAN
Solar/Wind Helper
0.3
3143526WINTERP
Solar/Wind Helper
1.294
3142543TWELFTH
Solar/Wind Helper
0.014
3142416OLDCHRC
Solar/Wind Helper
0.296
3142416OLDCHRC
Solar/Wind Helper
0.113
316458AB2-190 GEN2
Solar/Wind Helper
0.639
3144293JTRSVLE
50/50
0.503
3144293JTRSVLE
50/50
0.423
970535AG2-341 GEN
50/50
1.349
3152661PLYWOOD A
50/50
0.157
971489AH1-241 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
1.049
3146776BUCKING
Solar/Wind Harmer
0.085
315821AE2-092 GEN
Solar/Wind Harmer
0.013
970301AG2-198 GEN
Solar/Wind Harmer
7.476
971741AH1-377 GEN
Solar/Wind Harmer
16.133
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.127
958211AF2-115 GEN
Solar/Wind Harmer
1.786
963191AG1-168 GEN
Solar/Wind Harmer
0.595
316034AC1-036 C
Solar/Wind Harmer
0.009
970323AG2-213 GEN
Solar/Wind Harmer
5.145
971775AH1-396 GEN
Solar/Wind Harmer
0.193
970099AG2-077 GEN
Solar/Wind Harmer
11.665
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.768
964791AG1-342 GEN
Solar/Wind Harmer
1.475
3146843MT LREL
Solar/Wind Harmer
0.077
3146843MT LREL
Solar/Wind Harmer
0.077
939181AE1-148 GEN
Solar/Wind Harmer
3.325
3143526WINTERP
Solar/Wind Helper
1.294
316240AF1-291 C
Solar/Wind Helper
0.162
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.156
316075AC2-137 C
Solar/Wind Helper
0.172
3151921BEARGRDN G2
50/50
2.966
3144293JTRSVLE
50/50
0.503
970413AG2-270 GEN
50/50
9.546
966251AG1-494 GEN
50/50
1.198
3151591KERR 2
50/50
0.135
970221AG2-151 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
0.094
3146926FARMVIL
Solar/Wind Harmer
0.129
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
1.869
3147133PAMPLIN
Solar/Wind Harmer
0.497
971193AH1-056 GEN
Solar/Wind Harmer
9.642
963181AG1-167 GEN
Solar/Wind Harmer
0.595
959311AF2-222 GEN
Solar/Wind Harmer
11.09
970257AG2-171 GEN
Solar/Wind Harmer
3.859
315785AD2-033 C
Solar/Wind Harmer
0.934
958131AF2-107 GEN
Solar/Wind Harmer
2.955
316478AD1-087 GEN
Solar/Wind Harmer
0.356
316486AD2-202 GEN
Solar/Wind Harmer
0.105
964241AG1-285 GEN
Solar/Wind Harmer
6.636
316131AB2-060 GEN
Solar/Wind Harmer
0.284
3148013FISHERV
Solar/Wind Harmer
0.071
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.932
971683AH1-343 GEN
Solar/Wind Harmer
2.348
316313AB2-026
Solar/Wind Helper
1.245
316258AE1-075 C
Solar/Wind Helper
1.12
316405AF2-144 C
Solar/Wind Helper
0.933
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.709
315839AE2-212 C
Solar/Wind Helper
0.155
CPLELTFEXP_CPLE->PJM
CLTF
0.611
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.053
LAGNLTFEXP_LAGN->PJM
CLTF
1.406
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.04
TVALTFEXP_TVA->PJM
CLTF
0.731
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.581
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
1.069
SIGELTFEXP_SIGE->PJM
CLTF
0.035
NYPJM->LTFIMP_NY
CLTF
0.331
LGEELTFEXP_LGEE->PJM
CLTF
0.459
WECLTFEXP_WEC->PJM
CLTF
0.235

Details for AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.59 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:965.75
MW Contribution:9.55
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
14.467
3151541CLOVER2
50/50
2.177
3151611KERR 4
50/50
0.135
3151621KERR 5
50/50
0.135
3151631KERR 6
50/50
0.135
3151641KERR 7
50/50
0.135
971447AH1-217 GEN
Solar/Wind Harmer
8.145
971845AH1-439 GEN
Solar/Wind Harmer
11.716
970285AG2-188 GEN
Solar/Wind Harmer
19.851
270494AE1-108_GEN
Solar/Wind Harmer
2.723
315657AE1-056 GEN
Solar/Wind Harmer
5.462
946301AF1-294 GEN
Solar/Wind Harmer
2.936
961791AG1-021 GEN
Solar/Wind Harmer
1.429
970683AG2-441 GEN
Solar/Wind Harmer
9.008
970681AG2-440 GEN
Solar/Wind Harmer
7.206
3144303KENBRDG
Solar/Wind Harmer
0.096
971443AH1-215 GEN
Solar/Wind Harmer
2.005
971967AH1-528 GEN
Solar/Wind Harmer
17.843
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.188
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.069
3147243WELCO
Solar/Wind Harmer
0.043
970865AG2-541 GEN
Solar/Wind Harmer
2.13
316123AC1-075 GEN
Solar/Wind Harmer
0.077
970165AG2-112 GEN
Solar/Wind Harmer
0.459
970163AG2-111 GEN
Solar/Wind Harmer
0.438
316233AE1-074 FULL
Solar/Wind Helper
0.38
316312AB1-027
Solar/Wind Helper
0.217
316132AB2-190 GEN1
Solar/Wind Helper
0.639
3151921BEARGRDN G2
50/50
2.966
3144293JTRSVLE
50/50
0.503
970413AG2-270 GEN
50/50
9.546
966251AG1-494 GEN
50/50
1.198
3151591KERR 2
50/50
0.135
970221AG2-151 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
0.094
3146926FARMVIL
Solar/Wind Harmer
0.129
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
1.869
3147133PAMPLIN
Solar/Wind Harmer
0.497
971193AH1-056 GEN
Solar/Wind Harmer
9.642
963181AG1-167 GEN
Solar/Wind Harmer
0.595
959311AF2-222 GEN
Solar/Wind Harmer
11.09
970257AG2-171 GEN
Solar/Wind Harmer
3.859
315785AD2-033 C
Solar/Wind Harmer
0.934
958131AF2-107 GEN
Solar/Wind Harmer
2.955
316478AD1-087 GEN
Solar/Wind Harmer
0.356
316486AD2-202 GEN
Solar/Wind Harmer
0.105
964241AG1-285 GEN
Solar/Wind Harmer
6.636
316131AB2-060 GEN
Solar/Wind Harmer
0.284
3148013FISHERV
Solar/Wind Harmer
0.071
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.932
971683AH1-343 GEN
Solar/Wind Harmer
2.348
316313AB2-026
Solar/Wind Helper
1.245
316258AE1-075 C
Solar/Wind Helper
1.12
316405AF2-144 C
Solar/Wind Helper
0.933
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.709
315839AE2-212 C
Solar/Wind Helper
0.155
3151931BEARGRDN S1
50/50
3.828
3151911BEARGRDN G1
50/50
2.966
3144293JTRSVLE
50/50
0.503
3151531CLOVER1
50/50
2.188
3151601KERR 3
50/50
0.135
3151581KERR 1
50/50
0.048
970937AG2-583 GEN
Solar/Wind Harmer
28.699
972003AH1-546 GEN
Solar/Wind Harmer
13.118
971377AH1-170 GEN
Solar/Wind Harmer
3.027
3147623JAMES R
Solar/Wind Harmer
0.658
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
963171AG1-166 GEN
Solar/Wind Harmer
0.794
971563AH1-280 GEN
Solar/Wind Harmer
1.587
970685AG2-442 GEN
Solar/Wind Harmer
10.089
962491AG1-098 GEN
Solar/Wind Harmer
7.03
315693AD1-088 GEN
Solar/Wind Harmer
5.777
957481AF2-042 GEN
Solar/Wind Harmer
29.163
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.003
970401AG2-262 GEN
Solar/Wind Harmer
0.451
316003AC1-222 GEN
Solar/Wind Harmer
0.002
316336AC2-165 C
Solar/Wind Helper
5.135
3143226MDLTHAN
Solar/Wind Helper
0.3
3143526WINTERP
Solar/Wind Helper
1.294
3142543TWELFTH
Solar/Wind Helper
0.014
3142416OLDCHRC
Solar/Wind Helper
0.296
3142416OLDCHRC
Solar/Wind Helper
0.113
316458AB2-190 GEN2
Solar/Wind Helper
0.639
3144293JTRSVLE
50/50
0.503
3144293JTRSVLE
50/50
0.423
970535AG2-341 GEN
50/50
1.349
3152661PLYWOOD A
50/50
0.157
971489AH1-241 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
1.049
3146776BUCKING
Solar/Wind Harmer
0.085
315821AE2-092 GEN
Solar/Wind Harmer
0.013
970301AG2-198 GEN
Solar/Wind Harmer
7.476
971741AH1-377 GEN
Solar/Wind Harmer
16.133
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.127
958211AF2-115 GEN
Solar/Wind Harmer
1.786
963191AG1-168 GEN
Solar/Wind Harmer
0.595
316034AC1-036 C
Solar/Wind Harmer
0.009
970323AG2-213 GEN
Solar/Wind Harmer
5.145
971775AH1-396 GEN
Solar/Wind Harmer
0.193
970933AG2-581 GEN
Solar/Wind Harmer
8.922
970099AG2-077 GEN
Solar/Wind Harmer
11.665
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.768
964791AG1-342 GEN
Solar/Wind Harmer
1.475
3146843MT LREL
Solar/Wind Harmer
0.077
3146843MT LREL
Solar/Wind Harmer
0.077
939181AE1-148 GEN
Solar/Wind Harmer
3.325
3143526WINTERP
Solar/Wind Helper
1.294
316240AF1-291 C
Solar/Wind Helper
0.162
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.156
316075AC2-137 C
Solar/Wind Helper
0.172
CPLELTFEXP_CPLE->PJM
CLTF
0.611
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.053
LAGNLTFEXP_LAGN->PJM
CLTF
1.406
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.04
TVALTFEXP_TVA->PJM
CLTF
0.731
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.581
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
1.069
SIGELTFEXP_SIGE->PJM
CLTF
0.035
NYPJM->LTFIMP_NY
CLTF
0.331
LGEELTFEXP_LGEE->PJM
CLTF
0.459
WECLTFEXP_WEC->PJM
CLTF
0.235

Details for AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.24 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:727.2
MW Contribution:29.36
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
0.346
970535AG2-341 GEN
50/50
1.993
971741AH1-377 GEN
Solar/Wind Harmer
54.138
970933AG2-581 GEN
Solar/Wind Harmer
27.859
970099AG2-077 GEN
Solar/Wind Harmer
36.299
939181AE1-148 GEN
Solar/Wind Harmer
6.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.689
316222AC1-221 GEN
Solar/Wind Harmer
0.447
942751AE2-291 GEN
Solar/Wind Harmer
5.336
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
971629AH1-314 GEN
50/50
5.006
962491AG1-098 GEN
Solar/Wind Harmer
22.331
315693AD1-088 GEN
Solar/Wind Harmer
18.25
957481AF2-042 GEN
Solar/Wind Harmer
90.747
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.071
316129AC1-054 GEN
Solar/Wind Harmer
0.427
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
971967AH1-528 GEN
Solar/Wind Harmer
55.717
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
316118AC1-105 GEN
Solar/Wind Harmer
0.376
970865AG2-541 GEN
Solar/Wind Harmer
4.593
316123AC1-075 GEN
Solar/Wind Harmer
0.152
970165AG2-112 GEN
Solar/Wind Harmer
0.903
970163AG2-111 GEN
Solar/Wind Harmer
0.862
970831AG2-522 GEN
Solar/Wind Harmer
4.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
316478AD1-087 GEN
Solar/Wind Harmer
1.094
316486AD2-202 GEN
Solar/Wind Harmer
0.321
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.01
971683AH1-343 GEN
Solar/Wind Harmer
5.256
316283AC2-100 C
Solar/Wind Harmer
0.206
316131AB2-060 GEN
Solar/Wind Harmer
0.208
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.67 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:712.52
MW Contribution:29.36
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
316118AC1-105 GEN
Solar/Wind Harmer
0.376
970865AG2-541 GEN
Solar/Wind Harmer
4.593
316123AC1-075 GEN
Solar/Wind Harmer
0.152
970165AG2-112 GEN
Solar/Wind Harmer
0.903
970163AG2-111 GEN
Solar/Wind Harmer
0.862
970831AG2-522 GEN
Solar/Wind Harmer
4.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
971629AH1-314 GEN
50/50
5.006
962491AG1-098 GEN
Solar/Wind Harmer
22.331
315693AD1-088 GEN
Solar/Wind Harmer
18.25
957481AF2-042 GEN
Solar/Wind Harmer
90.747
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.071
316129AC1-054 GEN
Solar/Wind Harmer
0.427
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
3152661PLYWOOD A
50/50
0.346
970535AG2-341 GEN
50/50
1.993
971741AH1-377 GEN
Solar/Wind Harmer
54.138
970099AG2-077 GEN
Solar/Wind Harmer
36.299
939181AE1-148 GEN
Solar/Wind Harmer
6.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.689
316222AC1-221 GEN
Solar/Wind Harmer
0.447
942751AE2-291 GEN
Solar/Wind Harmer
5.336
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
316478AD1-087 GEN
Solar/Wind Harmer
1.094
316486AD2-202 GEN
Solar/Wind Harmer
0.321
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.01
971683AH1-343 GEN
Solar/Wind Harmer
5.256
316283AC2-100 C
Solar/Wind Harmer
0.206
316131AB2-060 GEN
Solar/Wind Harmer
0.208
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.28 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:868.71
MW Contribution:29.41
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
29.414
3151591KERR 2
50/50
0.302
316478AD1-087 GEN
Solar/Wind Harmer
3.055
316486AD2-202 GEN
Solar/Wind Harmer
0.895
316248AF1-058 C
Solar/Wind Harmer
0.559
960061AF2-297 GEN
Solar/Wind Harmer
9.268
971683AH1-343 GEN
Solar/Wind Harmer
6.951
316283AC2-100 C
Solar/Wind Harmer
1.124
316131AB2-060 GEN
Solar/Wind Harmer
0.808
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.542
3147133PAMPLIN
Solar/Wind Helper
1.062
316313AB2-026
Solar/Wind Helper
0.243
316258AE1-075 C
Solar/Wind Helper
0.219
316405AF2-144 C
Solar/Wind Helper
0.182
3151531CLOVER1
50/50
6.74
3151601KERR 3
50/50
0.302
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.44
315693AD1-088 GEN
Solar/Wind Harmer
21.388
957481AF2-042 GEN
Solar/Wind Harmer
119.681
315687AD1-152 GEN
Solar/Wind Harmer
3.524
316003AC1-222 GEN
Solar/Wind Harmer
1.683
970401AG2-262 GEN
Solar/Wind Harmer
0.932
971065AG2-659 GEN
Solar/Wind Harmer
6.697
316129AC1-054 GEN
Solar/Wind Harmer
1.121
316237AB2-079_GEN
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Helper
0.44
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
1.003
3151541CLOVER2
50/50
6.708
3151611KERR 4
50/50
0.302
3151621KERR 5
50/50
0.302
3151631KERR 6
50/50
0.302
3151641KERR 7
50/50
0.302
971967AH1-528 GEN
Solar/Wind Harmer
73.672
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.131
970865AG2-541 GEN
Solar/Wind Harmer
6.075
316123AC1-075 GEN
Solar/Wind Harmer
1.358
970165AG2-112 GEN
Solar/Wind Harmer
1.195
970163AG2-111 GEN
Solar/Wind Harmer
1.14
970831AG2-522 GEN
Solar/Wind Harmer
6.069
316239AB2-077_GEN
Solar/Wind Harmer
0.274
316238AB2-078_GEN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Harmer
1.371
270457AD2-023 GEN
Solar/Wind Harmer
0.695
270494AE1-108_GEN
Solar/Wind Helper
2.769
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3152661PLYWOOD A
50/50
0.348
970535AG2-341 GEN
50/50
2.001
971741AH1-377 GEN
Solar/Wind Harmer
71.327
970933AG2-581 GEN
Solar/Wind Harmer
36.739
970099AG2-077 GEN
Solar/Wind Harmer
47.872
939181AE1-148 GEN
Solar/Wind Harmer
8.421
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.05
962561AG1-105 GEN
Solar/Wind Harmer
7.525
316222AC1-221 GEN
Solar/Wind Harmer
1.236
942751AE2-291 GEN
Solar/Wind Harmer
7.063
313527AB2-043 GEN
Solar/Wind Harmer
1.361
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.338
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.919
CPLELTFEXP_CPLE->PJM
CLTF
4.232
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.165
LAGNLTFEXP_LAGN->PJM
CLTF
2.703
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.92
TVALTFEXP_TVA->PJM
CLTF
1.347
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.6
MECLTFEXP_MEC->PJM
CLTF
1.297
SIGELTFEXP_SIGE->PJM
CLTF
0.038
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.461
WECLTFEXP_WEC->PJM
CLTF
0.241

Details for AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.24 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:868.41
MW Contribution:29.41
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.708
3151611KERR 4
50/50
0.302
3151621KERR 5
50/50
0.302
3151631KERR 6
50/50
0.302
3151641KERR 7
50/50
0.302
971967AH1-528 GEN
Solar/Wind Harmer
73.672
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.131
970865AG2-541 GEN
Solar/Wind Harmer
6.075
316123AC1-075 GEN
Solar/Wind Harmer
1.358
970165AG2-112 GEN
Solar/Wind Harmer
1.195
970163AG2-111 GEN
Solar/Wind Harmer
1.14
970831AG2-522 GEN
Solar/Wind Harmer
6.069
316239AB2-077_GEN
Solar/Wind Harmer
0.274
316238AB2-078_GEN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Harmer
1.371
270457AD2-023 GEN
Solar/Wind Harmer
0.695
270494AE1-108_GEN
Solar/Wind Helper
2.769
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3151531CLOVER1
50/50
6.74
3151601KERR 3
50/50
0.302
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.44
315693AD1-088 GEN
Solar/Wind Harmer
21.388
957481AF2-042 GEN
Solar/Wind Harmer
119.681
315687AD1-152 GEN
Solar/Wind Harmer
3.524
316003AC1-222 GEN
Solar/Wind Harmer
1.683
970401AG2-262 GEN
Solar/Wind Harmer
0.932
971065AG2-659 GEN
Solar/Wind Harmer
6.697
316129AC1-054 GEN
Solar/Wind Harmer
1.121
316237AB2-079_GEN
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Helper
0.44
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
1.003
970413AG2-270 GEN
50/50
29.414
3151591KERR 2
50/50
0.302
316478AD1-087 GEN
Solar/Wind Harmer
3.055
316486AD2-202 GEN
Solar/Wind Harmer
0.895
316248AF1-058 C
Solar/Wind Harmer
0.559
960061AF2-297 GEN
Solar/Wind Harmer
9.268
971683AH1-343 GEN
Solar/Wind Harmer
6.951
316283AC2-100 C
Solar/Wind Harmer
1.124
316131AB2-060 GEN
Solar/Wind Harmer
0.808
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.542
3147133PAMPLIN
Solar/Wind Helper
1.062
316313AB2-026
Solar/Wind Helper
0.243
316258AE1-075 C
Solar/Wind Helper
0.219
316405AF2-144 C
Solar/Wind Helper
0.182
3152661PLYWOOD A
50/50
0.348
970535AG2-341 GEN
50/50
2.001
971741AH1-377 GEN
Solar/Wind Harmer
71.327
970933AG2-581 GEN
Solar/Wind Harmer
36.739
970099AG2-077 GEN
Solar/Wind Harmer
47.872
939181AE1-148 GEN
Solar/Wind Harmer
8.421
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.05
962561AG1-105 GEN
Solar/Wind Harmer
7.525
316222AC1-221 GEN
Solar/Wind Harmer
1.236
942751AE2-291 GEN
Solar/Wind Harmer
7.063
313527AB2-043 GEN
Solar/Wind Harmer
1.361
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.338
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.919
CPLELTFEXP_CPLE->PJM
CLTF
4.232
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.165
LAGNLTFEXP_LAGN->PJM
CLTF
2.703
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.92
TVALTFEXP_TVA->PJM
CLTF
1.347
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.6
MECLTFEXP_MEC->PJM
CLTF
1.297
SIGELTFEXP_SIGE->PJM
CLTF
0.038
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.461
WECLTFEXP_WEC->PJM
CLTF
0.241

Details for AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.04 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:846.09
MW Contribution:29.36
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
971967AH1-528 GEN
Solar/Wind Harmer
73.556
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.126
970865AG2-541 GEN
Solar/Wind Harmer
6.047
316123AC1-075 GEN
Solar/Wind Harmer
1.351
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.135
970831AG2-522 GEN
Solar/Wind Harmer
6.052
316239AB2-077_GEN
Solar/Wind Harmer
0.273
316238AB2-078_GEN
Solar/Wind Harmer
0.273
270455AD2-022 GEN
Solar/Wind Harmer
1.35
270457AD2-023 GEN
Solar/Wind Harmer
0.684
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.403
315693AD1-088 GEN
Solar/Wind Harmer
21.359
957481AF2-042 GEN
Solar/Wind Harmer
119.484
315687AD1-152 GEN
Solar/Wind Harmer
3.515
316003AC1-222 GEN
Solar/Wind Harmer
1.676
970401AG2-262 GEN
Solar/Wind Harmer
0.928
971065AG2-659 GEN
Solar/Wind Harmer
6.677
316129AC1-054 GEN
Solar/Wind Harmer
1.118
316237AB2-079_GEN
Solar/Wind Harmer
0.273
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
3152661PLYWOOD A
50/50
0.346
971741AH1-377 GEN
Solar/Wind Harmer
71.281
970933AG2-581 GEN
Solar/Wind Harmer
36.681
970099AG2-077 GEN
Solar/Wind Harmer
47.793
939181AE1-148 GEN
Solar/Wind Harmer
8.391
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.036
962561AG1-105 GEN
Solar/Wind Harmer
7.49
316222AC1-221 GEN
Solar/Wind Harmer
1.223
942751AE2-291 GEN
Solar/Wind Harmer
7.025
313527AB2-043 GEN
Solar/Wind Harmer
1.353
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
316478AD1-087 GEN
Solar/Wind Harmer
3.05
316486AD2-202 GEN
Solar/Wind Harmer
0.893
316248AF1-058 C
Solar/Wind Harmer
0.556
960061AF2-297 GEN
Solar/Wind Harmer
9.23
971683AH1-343 GEN
Solar/Wind Harmer
6.92
316283AC2-100 C
Solar/Wind Harmer
1.112
316131AB2-060 GEN
Solar/Wind Harmer
0.803
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.09 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:804.51
MW Contribution:29.36
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.403
315693AD1-088 GEN
Solar/Wind Harmer
21.359
957481AF2-042 GEN
Solar/Wind Harmer
119.484
315687AD1-152 GEN
Solar/Wind Harmer
3.515
316003AC1-222 GEN
Solar/Wind Harmer
1.676
970401AG2-262 GEN
Solar/Wind Harmer
0.928
971065AG2-659 GEN
Solar/Wind Harmer
6.677
316129AC1-054 GEN
Solar/Wind Harmer
1.118
316237AB2-079_GEN
Solar/Wind Harmer
0.273
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.126
970865AG2-541 GEN
Solar/Wind Harmer
6.047
316123AC1-075 GEN
Solar/Wind Harmer
1.351
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.135
970831AG2-522 GEN
Solar/Wind Harmer
6.052
316239AB2-077_GEN
Solar/Wind Harmer
0.273
316238AB2-078_GEN
Solar/Wind Harmer
0.273
270455AD2-022 GEN
Solar/Wind Harmer
1.35
270457AD2-023 GEN
Solar/Wind Harmer
0.684
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3152661PLYWOOD A
50/50
0.346
971741AH1-377 GEN
Solar/Wind Harmer
71.281
970099AG2-077 GEN
Solar/Wind Harmer
47.793
939181AE1-148 GEN
Solar/Wind Harmer
8.391
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.036
962561AG1-105 GEN
Solar/Wind Harmer
7.49
316222AC1-221 GEN
Solar/Wind Harmer
1.223
942751AE2-291 GEN
Solar/Wind Harmer
7.025
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
316478AD1-087 GEN
Solar/Wind Harmer
3.05
316486AD2-202 GEN
Solar/Wind Harmer
0.893
316248AF1-058 C
Solar/Wind Harmer
0.556
960061AF2-297 GEN
Solar/Wind Harmer
9.23
971683AH1-343 GEN
Solar/Wind Harmer
6.92
316283AC2-100 C
Solar/Wind Harmer
1.112
316131AB2-060 GEN
Solar/Wind Harmer
0.803
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
313527AB2-043 GEN
Solar/Wind Harmer
1.353
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.09 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:804.51
MW Contribution:29.36
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.403
315693AD1-088 GEN
Solar/Wind Harmer
21.359
957481AF2-042 GEN
Solar/Wind Harmer
119.484
315687AD1-152 GEN
Solar/Wind Harmer
3.515
316003AC1-222 GEN
Solar/Wind Harmer
1.676
970401AG2-262 GEN
Solar/Wind Harmer
0.928
971065AG2-659 GEN
Solar/Wind Harmer
6.677
316129AC1-054 GEN
Solar/Wind Harmer
1.118
316237AB2-079_GEN
Solar/Wind Harmer
0.273
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
3152661PLYWOOD A
50/50
0.346
971741AH1-377 GEN
Solar/Wind Harmer
71.281
970099AG2-077 GEN
Solar/Wind Harmer
47.793
939181AE1-148 GEN
Solar/Wind Harmer
8.391
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.036
962561AG1-105 GEN
Solar/Wind Harmer
7.49
316222AC1-221 GEN
Solar/Wind Harmer
1.223
942751AE2-291 GEN
Solar/Wind Harmer
7.025
313527AB2-043 GEN
Solar/Wind Harmer
1.353
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.126
970865AG2-541 GEN
Solar/Wind Harmer
6.047
316123AC1-075 GEN
Solar/Wind Harmer
1.351
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.135
970831AG2-522 GEN
Solar/Wind Harmer
6.052
316239AB2-077_GEN
Solar/Wind Harmer
0.273
316238AB2-078_GEN
Solar/Wind Harmer
0.273
270455AD2-022 GEN
Solar/Wind Harmer
1.35
270457AD2-023 GEN
Solar/Wind Harmer
0.684
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
316478AD1-087 GEN
Solar/Wind Harmer
3.05
316486AD2-202 GEN
Solar/Wind Harmer
0.893
316248AF1-058 C
Solar/Wind Harmer
0.556
960061AF2-297 GEN
Solar/Wind Harmer
9.23
971683AH1-343 GEN
Solar/Wind Harmer
6.92
316283AC2-100 C
Solar/Wind Harmer
1.112
316131AB2-060 GEN
Solar/Wind Harmer
0.803
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:218.2 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1492.5
MW Contribution:29.97
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.536
3151531CLOVER1
50/50
6.868
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.479
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.387
971563AH1-280 GEN
Solar/Wind Harmer
6.387
970685AG2-442 GEN
Solar/Wind Harmer
41.098
962491AG1-098 GEN
Solar/Wind Harmer
28.527
315693AD1-088 GEN
Solar/Wind Harmer
20.89
957481AF2-042 GEN
Solar/Wind Harmer
119.73
316237AB2-079_GEN
Solar/Wind Harmer
0.97
315687AD1-152 GEN
Solar/Wind Harmer
3.722
970401AG2-262 GEN
Solar/Wind Harmer
1.828
316003AC1-222 GEN
Solar/Wind Harmer
2.23
971065AG2-659 GEN
Solar/Wind Harmer
10.784
316129AC1-054 GEN
Solar/Wind Harmer
1.809
971795AH1-408 GEN
Solar/Wind Harmer
11.382
960081AF2-299 GEN
Solar/Wind Harmer
1.187
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.663
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.965
316049AB1-081 GEN
Solar/Wind Harmer
0.772
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.715
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
970223AG2-152 GEN
Solar/Wind Harmer
5.79
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.192
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.414
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.314
3151541CLOVER2
50/50
6.835
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
971845AH1-439 GEN
Solar/Wind Harmer
44.839
970285AG2-188 GEN
Solar/Wind Harmer
71.83
315657AE1-056 GEN
Solar/Wind Harmer
20.241
946301AF1-294 GEN
Solar/Wind Harmer
13.094
961791AG1-021 GEN
Solar/Wind Harmer
6.387
970683AG2-441 GEN
Solar/Wind Harmer
36.695
970681AG2-440 GEN
Solar/Wind Harmer
29.356
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.31
971967AH1-528 GEN
Solar/Wind Harmer
73.321
316239AB2-077_GEN
Solar/Wind Harmer
0.97
316238AB2-078_GEN
Solar/Wind Harmer
0.97
316118AC1-105 GEN
Solar/Wind Harmer
1.807
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.03
970831AG2-522 GEN
Solar/Wind Harmer
9.822
316123AC1-075 GEN
Solar/Wind Harmer
1.789
970165AG2-112 GEN
Solar/Wind Harmer
1.575
970163AG2-111 GEN
Solar/Wind Harmer
1.503
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.493
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.635
270457AD2-023 GEN
Solar/Wind Harmer
0.829
315607AA1-063A GEN
Solar/Wind Harmer
0.882
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.411
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.563
270494AE1-108_GEN
Solar/Wind Helper
3.665
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.536
3144293JTRSVLE
50/50
1.294
970535AG2-341 GEN
50/50
4.631
3152661PLYWOOD A
50/50
0.509
970301AG2-198 GEN
Solar/Wind Harmer
29.375
971741AH1-377 GEN
Solar/Wind Harmer
63.77
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.984
963191AG1-168 GEN
Solar/Wind Harmer
4.79
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.293
971775AH1-396 GEN
Solar/Wind Harmer
3.032
970933AG2-581 GEN
Solar/Wind Harmer
36.564
970099AG2-077 GEN
Solar/Wind Harmer
47.892
313527AB2-043 GEN
Solar/Wind Harmer
5.323
962561AG1-105 GEN
Solar/Wind Harmer
16.163
964791AG1-342 GEN
Solar/Wind Harmer
5.983
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.395
942751AE2-291 GEN
Solar/Wind Harmer
9.282
316222AC1-221 GEN
Solar/Wind Harmer
1.431
316181AB2-040 GEN
Solar/Wind Harmer
1.454
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.157
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.182
3145783HORNRTN
Solar/Wind Harmer
0.946
3145783HORNRTN
Solar/Wind Harmer
0.296
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.956
316274AC1-208 GEN
Solar/Wind Harmer
0.891
316263AC1-034 GEN
Solar/Wind Harmer
3.354
961601AG1-000A GEN
Solar/Wind Harmer
2.733
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.045
316197AC1-042 GEN
Solar/Wind Harmer
0.792
942671AE2-283 GEN
Solar/Wind Harmer
2.132
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.531
3144293JTRSVLE
50/50
1.536
970413AG2-270 GEN
50/50
29.97
3151591KERR 2
50/50
0.482
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.339
970909AG2-566 GEN
Solar/Wind Harmer
5.578
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.735
963181AG1-167 GEN
Solar/Wind Harmer
4.79
959311AF2-222 GEN
Solar/Wind Harmer
45.765
970257AG2-171 GEN
Solar/Wind Harmer
15.97
315785AD2-033 C
Solar/Wind Harmer
9.259
964241AG1-285 GEN
Solar/Wind Harmer
28.316
316478AD1-087 GEN
Solar/Wind Harmer
3.115
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.609
316248AF1-058 C
Solar/Wind Harmer
0.741
960061AF2-297 GEN
Solar/Wind Harmer
12.289
971683AH1-343 GEN
Solar/Wind Harmer
9.199
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.303
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.775
316210AC1-098 GEN
Solar/Wind Harmer
1.194
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.767
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.393
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.414
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.317
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
CPLELTFEXP_CPLE->PJM
CLTF
5.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.616
LAGNLTFEXP_LAGN->PJM
CLTF
3.212
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.896
TVALTFEXP_TVA->PJM
CLTF
1.599
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.51
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.435
MECLTFEXP_MEC->PJM
CLTF
1.488
SIGELTFEXP_SIGE->PJM
CLTF
0.044
NYPJM->LTFIMP_NY
CLTF
0.52
LGEELTFEXP_LGEE->PJM
CLTF
0.521
WECLTFEXP_WEC->PJM
CLTF
0.271

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:218.14 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1492.11
MW Contribution:29.97
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.536
3151531CLOVER1
50/50
6.868
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.479
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.387
971563AH1-280 GEN
Solar/Wind Harmer
6.387
970685AG2-442 GEN
Solar/Wind Harmer
41.098
962491AG1-098 GEN
Solar/Wind Harmer
28.527
315693AD1-088 GEN
Solar/Wind Harmer
20.89
957481AF2-042 GEN
Solar/Wind Harmer
119.73
316237AB2-079_GEN
Solar/Wind Harmer
0.97
315687AD1-152 GEN
Solar/Wind Harmer
3.722
970401AG2-262 GEN
Solar/Wind Harmer
1.828
316003AC1-222 GEN
Solar/Wind Harmer
2.23
971065AG2-659 GEN
Solar/Wind Harmer
10.784
316129AC1-054 GEN
Solar/Wind Harmer
1.809
971795AH1-408 GEN
Solar/Wind Harmer
11.382
960081AF2-299 GEN
Solar/Wind Harmer
1.187
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.663
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.965
316049AB1-081 GEN
Solar/Wind Harmer
0.772
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.715
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
970223AG2-152 GEN
Solar/Wind Harmer
5.79
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.192
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.414
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.314
3151541CLOVER2
50/50
6.835
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
971845AH1-439 GEN
Solar/Wind Harmer
44.839
970285AG2-188 GEN
Solar/Wind Harmer
71.83
315657AE1-056 GEN
Solar/Wind Harmer
20.241
946301AF1-294 GEN
Solar/Wind Harmer
13.094
961791AG1-021 GEN
Solar/Wind Harmer
6.387
970683AG2-441 GEN
Solar/Wind Harmer
36.695
970681AG2-440 GEN
Solar/Wind Harmer
29.356
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.31
971967AH1-528 GEN
Solar/Wind Harmer
73.321
316239AB2-077_GEN
Solar/Wind Harmer
0.97
316238AB2-078_GEN
Solar/Wind Harmer
0.97
316118AC1-105 GEN
Solar/Wind Harmer
1.807
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.03
970831AG2-522 GEN
Solar/Wind Harmer
9.822
316123AC1-075 GEN
Solar/Wind Harmer
1.789
970165AG2-112 GEN
Solar/Wind Harmer
1.575
970163AG2-111 GEN
Solar/Wind Harmer
1.503
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.493
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.635
270457AD2-023 GEN
Solar/Wind Harmer
0.829
315607AA1-063A GEN
Solar/Wind Harmer
0.882
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.411
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.563
270494AE1-108_GEN
Solar/Wind Helper
3.665
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.536
3144293JTRSVLE
50/50
1.294
970535AG2-341 GEN
50/50
4.631
3152661PLYWOOD A
50/50
0.509
970301AG2-198 GEN
Solar/Wind Harmer
29.375
971741AH1-377 GEN
Solar/Wind Harmer
63.77
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.984
963191AG1-168 GEN
Solar/Wind Harmer
4.79
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.293
971775AH1-396 GEN
Solar/Wind Harmer
3.032
970933AG2-581 GEN
Solar/Wind Harmer
36.564
970099AG2-077 GEN
Solar/Wind Harmer
47.892
313527AB2-043 GEN
Solar/Wind Harmer
5.323
962561AG1-105 GEN
Solar/Wind Harmer
16.163
964791AG1-342 GEN
Solar/Wind Harmer
5.983
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.395
942751AE2-291 GEN
Solar/Wind Harmer
9.282
316222AC1-221 GEN
Solar/Wind Harmer
1.431
316181AB2-040 GEN
Solar/Wind Harmer
1.454
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.157
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.182
3145783HORNRTN
Solar/Wind Harmer
0.946
3145783HORNRTN
Solar/Wind Harmer
0.296
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.956
316274AC1-208 GEN
Solar/Wind Harmer
0.891
316263AC1-034 GEN
Solar/Wind Harmer
3.354
961601AG1-000A GEN
Solar/Wind Harmer
2.733
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.045
316197AC1-042 GEN
Solar/Wind Harmer
0.792
942671AE2-283 GEN
Solar/Wind Harmer
2.132
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.531
3144293JTRSVLE
50/50
1.536
970413AG2-270 GEN
50/50
29.97
3151591KERR 2
50/50
0.482
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.339
970909AG2-566 GEN
Solar/Wind Harmer
5.578
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.735
963181AG1-167 GEN
Solar/Wind Harmer
4.79
959311AF2-222 GEN
Solar/Wind Harmer
45.765
970257AG2-171 GEN
Solar/Wind Harmer
15.97
315785AD2-033 C
Solar/Wind Harmer
9.259
964241AG1-285 GEN
Solar/Wind Harmer
28.316
316478AD1-087 GEN
Solar/Wind Harmer
3.115
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.609
316248AF1-058 C
Solar/Wind Harmer
0.741
960061AF2-297 GEN
Solar/Wind Harmer
12.289
971683AH1-343 GEN
Solar/Wind Harmer
9.199
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.303
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.775
316210AC1-098 GEN
Solar/Wind Harmer
1.194
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.767
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.393
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.414
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.317
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
CPLELTFEXP_CPLE->PJM
CLTF
5.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.616
LAGNLTFEXP_LAGN->PJM
CLTF
3.212
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.896
TVALTFEXP_TVA->PJM
CLTF
1.599
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.51
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.435
MECLTFEXP_MEC->PJM
CLTF
1.488
SIGELTFEXP_SIGE->PJM
CLTF
0.044
NYPJM->LTFIMP_NY
CLTF
0.52
LGEELTFEXP_LGEE->PJM
CLTF
0.521
WECLTFEXP_WEC->PJM
CLTF
0.271

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:214.52 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1467.34
MW Contribution:29.9
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970933AG2-581 GEN
Solar/Wind Harmer
36.495
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.838
970285AG2-188 GEN
Solar/Wind Harmer
71.826
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
971967AH1-528 GEN
Solar/Wind Harmer
73.183
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:212.24 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:1187.04
MW Contribution:29.9
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.104
971845AH1-439 GEN
Solar/Wind Harmer
34.055
970285AG2-188 GEN
Solar/Wind Harmer
57.798
315657AE1-056 GEN
Solar/Wind Harmer
16.558
946301AF1-294 GEN
Solar/Wind Harmer
8.968
961791AG1-021 GEN
Solar/Wind Harmer
4.363
970683AG2-441 GEN
Solar/Wind Harmer
27.844
970681AG2-440 GEN
Solar/Wind Harmer
22.275
3144303KENBRDG
Solar/Wind Harmer
0.303
971443AH1-215 GEN
Solar/Wind Harmer
6.304
971967AH1-528 GEN
Solar/Wind Harmer
55.434
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.602
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.073
970831AG2-522 GEN
Solar/Wind Harmer
7.443
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.191
970163AG2-111 GEN
Solar/Wind Harmer
1.136
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.368
315607AA1-063A GEN
Solar/Wind Harmer
0.159
3146043SEABORD
Solar/Wind Harmer
0.076
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.25
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.97
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
963171AG1-166 GEN
Solar/Wind Harmer
2.424
971563AH1-280 GEN
Solar/Wind Harmer
4.847
970685AG2-442 GEN
Solar/Wind Harmer
31.186
962491AG1-098 GEN
Solar/Wind Harmer
21.632
315693AD1-088 GEN
Solar/Wind Harmer
17.82
957481AF2-042 GEN
Solar/Wind Harmer
90.757
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.458
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.171
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
9.004
960081AF2-299 GEN
Solar/Wind Harmer
0.903
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.349
3146233WITAKRS
Solar/Wind Harmer
0.261
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.051
316359AB2-059 GEN
Solar/Wind Harmer
0.226
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.062
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.232
963181AG1-167 GEN
Solar/Wind Harmer
1.818
959311AF2-222 GEN
Solar/Wind Harmer
34.653
970257AG2-171 GEN
Solar/Wind Harmer
12.116
315785AD2-033 C
Solar/Wind Harmer
2.953
964241AG1-285 GEN
Solar/Wind Harmer
21.475
316478AD1-087 GEN
Solar/Wind Harmer
1.115
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.935
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.299
971683AH1-343 GEN
Solar/Wind Harmer
6.959
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.287
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.626
3146233WITAKRS
Solar/Wind Harmer
0.329
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.062
961601AG1-000A GEN
Solar/Wind Harmer
4.35
315722AD1-056 GEN
Solar/Wind Harmer
0.382
3145796HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.068
962571AG1-106 GEN
Solar/Wind Harmer
0.836
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.253
970223AG2-152 GEN
Solar/Wind Harmer
3.997
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.043
941801AE2-185 GEN
Solar/Wind Harmer
1.818
3145823KELFORD
Solar/Wind Harmer
0.056
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.213
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.1
970301AG2-198 GEN
Solar/Wind Harmer
22.295
971741AH1-377 GEN
Solar/Wind Harmer
48.392
3147133PAMPLIN
Solar/Wind Harmer
0.48
3147133PAMPLIN
Solar/Wind Harmer
0.384
958211AF2-115 GEN
Solar/Wind Harmer
5.453
963191AG1-168 GEN
Solar/Wind Harmer
1.818
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.154
971775AH1-396 GEN
Solar/Wind Harmer
0.606
970933AG2-581 GEN
Solar/Wind Harmer
27.718
970099AG2-077 GEN
Solar/Wind Harmer
36.303
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.244
964791AG1-342 GEN
Solar/Wind Harmer
4.773
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.665
942751AE2-291 GEN
Solar/Wind Harmer
7.016
316222AC1-221 GEN
Solar/Wind Harmer
0.517
316181AB2-040 GEN
Solar/Wind Harmer
0.135
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.992
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.575
3145783HORNRTN
Solar/Wind Harmer
1.26
3145783HORNRTN
Solar/Wind Harmer
0.394
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.38
316263AC1-034 GEN
Solar/Wind Harmer
2.393
961601AG1-000A GEN
Solar/Wind Harmer
1.088
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.132
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.414
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
315724AD1-057 GEN
Solar/Wind Harmer
0.227
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.818
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.462
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.252
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:209.65 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:1172.59
MW Contribution:29.9
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.97
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
963171AG1-166 GEN
Solar/Wind Harmer
2.424
971563AH1-280 GEN
Solar/Wind Harmer
4.847
970685AG2-442 GEN
Solar/Wind Harmer
31.186
962491AG1-098 GEN
Solar/Wind Harmer
21.632
315693AD1-088 GEN
Solar/Wind Harmer
17.82
957481AF2-042 GEN
Solar/Wind Harmer
90.757
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.458
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.171
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
9.004
960081AF2-299 GEN
Solar/Wind Harmer
0.903
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.104
971845AH1-439 GEN
Solar/Wind Harmer
34.055
970285AG2-188 GEN
Solar/Wind Harmer
57.798
315657AE1-056 GEN
Solar/Wind Harmer
16.558
946301AF1-294 GEN
Solar/Wind Harmer
8.968
961791AG1-021 GEN
Solar/Wind Harmer
4.363
970683AG2-441 GEN
Solar/Wind Harmer
27.844
970681AG2-440 GEN
Solar/Wind Harmer
22.275
3144303KENBRDG
Solar/Wind Harmer
0.303
971443AH1-215 GEN
Solar/Wind Harmer
6.304
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.602
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.073
970831AG2-522 GEN
Solar/Wind Harmer
7.443
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.191
970163AG2-111 GEN
Solar/Wind Harmer
1.136
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.368
315607AA1-063A GEN
Solar/Wind Harmer
0.159
3146043SEABORD
Solar/Wind Harmer
0.076
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.25
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.462
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.252
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.232
963181AG1-167 GEN
Solar/Wind Harmer
1.818
959311AF2-222 GEN
Solar/Wind Harmer
34.653
970257AG2-171 GEN
Solar/Wind Harmer
12.116
315785AD2-033 C
Solar/Wind Harmer
2.953
964241AG1-285 GEN
Solar/Wind Harmer
21.475
316478AD1-087 GEN
Solar/Wind Harmer
1.115
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.935
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.299
971683AH1-343 GEN
Solar/Wind Harmer
6.959
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.287
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.626
3146233WITAKRS
Solar/Wind Harmer
0.329
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.062
961601AG1-000A GEN
Solar/Wind Harmer
4.35
315724AD1-057 GEN
Solar/Wind Harmer
0.227
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.818
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.213
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.1
970301AG2-198 GEN
Solar/Wind Harmer
22.295
971741AH1-377 GEN
Solar/Wind Harmer
48.392
3147133PAMPLIN
Solar/Wind Harmer
0.48
3147133PAMPLIN
Solar/Wind Harmer
0.384
958211AF2-115 GEN
Solar/Wind Harmer
5.453
963191AG1-168 GEN
Solar/Wind Harmer
1.818
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.154
971775AH1-396 GEN
Solar/Wind Harmer
0.606
970099AG2-077 GEN
Solar/Wind Harmer
36.303
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.244
964791AG1-342 GEN
Solar/Wind Harmer
4.773
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.665
942751AE2-291 GEN
Solar/Wind Harmer
7.016
316222AC1-221 GEN
Solar/Wind Harmer
0.517
316181AB2-040 GEN
Solar/Wind Harmer
0.135
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.992
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.575
3145783HORNRTN
Solar/Wind Harmer
1.26
3145783HORNRTN
Solar/Wind Harmer
0.394
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.38
316263AC1-034 GEN
Solar/Wind Harmer
2.393
961601AG1-000A GEN
Solar/Wind Harmer
1.088
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.132
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.414
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
316212AC1-099_GEN
Solar/Wind Harmer
0.349
3146233WITAKRS
Solar/Wind Harmer
0.261
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.051
316359AB2-059 GEN
Solar/Wind Harmer
0.226
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.062
315722AD1-056 GEN
Solar/Wind Harmer
0.382
3145796HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.068
962571AG1-106 GEN
Solar/Wind Harmer
0.836
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.253
970223AG2-152 GEN
Solar/Wind Harmer
3.997
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.043
941801AE2-185 GEN
Solar/Wind Harmer
1.818
3145823KELFORD
Solar/Wind Harmer
0.056
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:208.48 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1426.03
MW Contribution:29.9
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.838
970285AG2-188 GEN
Solar/Wind Harmer
71.826
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:208.48 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1426.03
MW Contribution:29.9
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.838
970285AG2-188 GEN
Solar/Wind Harmer
71.826
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2106-2111_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2106-2111_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:134.05 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:916.91
MW Contribution:12.4
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.277
3151621KERR 5
50/50
0.277
3151631KERR 6
50/50
0.277
3151641KERR 7
50/50
0.277
3151541CLOVER2
50/50
2.829
971845AH1-439 GEN
Solar/Wind Harmer
40.087
970285AG2-188 GEN
Solar/Wind Harmer
63.51
315657AE1-056 GEN
Solar/Wind Harmer
15.784
946301AF1-294 GEN
Solar/Wind Harmer
10.059
961791AG1-021 GEN
Solar/Wind Harmer
4.907
970683AG2-441 GEN
Solar/Wind Harmer
27.489
970681AG2-440 GEN
Solar/Wind Harmer
21.992
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.004
316239AB2-077_GEN
Solar/Wind Harmer
0.621
316238AB2-078_GEN
Solar/Wind Harmer
0.621
316118AC1-105 GEN
Solar/Wind Harmer
0.972
3147173SINAI
Solar/Wind Harmer
-0.012
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.033
970865AG2-541 GEN
Solar/Wind Harmer
3.923
946281AF1-292 GEN
Solar/Wind Harmer
0.19
316087AB2-174 GEN
Solar/Wind Harmer
1.178
3137643SOCKMAN
Solar/Wind Harmer
-0.032
316123AC1-075 GEN
Solar/Wind Harmer
0.853
970165AG2-112 GEN
Solar/Wind Harmer
0.751
970163AG2-111 GEN
Solar/Wind Harmer
0.717
971967AH1-528 GEN
Solar/Wind Harmer
14.188
315607AA1-063A GEN
Solar/Wind Harmer
0.715
3146043SEABORD
Solar/Wind Harmer
-0.007
270494AE1-108_GEN
Solar/Wind Helper
4.499
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3144293JTRSVLE
50/50
1.18
3151601KERR 3
50/50
0.277
3151581KERR 1
50/50
0.099
3151531CLOVER1
50/50
2.843
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.907
971563AH1-280 GEN
Solar/Wind Harmer
4.907
970685AG2-442 GEN
Solar/Wind Harmer
30.788
962491AG1-098 GEN
Solar/Wind Harmer
14.151
316237AB2-079_GEN
Solar/Wind Harmer
0.621
315693AD1-088 GEN
Solar/Wind Harmer
9.998
970401AG2-262 GEN
Solar/Wind Harmer
1.046
957481AF2-042 GEN
Solar/Wind Harmer
45.244
315687AD1-152 GEN
Solar/Wind Harmer
1.611
971065AG2-659 GEN
Solar/Wind Harmer
6.471
316129AC1-054 GEN
Solar/Wind Harmer
1.098
3147043LAWRENC
Adder
0.994
316003AC1-222 GEN
Solar/Wind Harmer
1.108
971795AH1-408 GEN
Solar/Wind Harmer
8.341
960081AF2-299 GEN
Solar/Wind Harmer
0.953
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.091
316212AC1-099_GEN
Solar/Wind Harmer
0.553
316322AB2-045
Solar/Wind Helper
0.97
3146776BUCKING
Solar/Wind Helper
0.348
316336AC2-165 C
Solar/Wind Helper
1.454
3144293JTRSVLE
50/50
1.18
3144293JTRSVLE
50/50
0.994
970535AG2-341 GEN
50/50
2.836
3152661PLYWOOD A
50/50
0.267
970301AG2-198 GEN
Solar/Wind Harmer
21.257
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.133
963191AG1-168 GEN
Solar/Wind Harmer
3.68
971741AH1-377 GEN
Solar/Wind Harmer
43.417
316034AC1-036 C
Solar/Wind Harmer
0.574
970323AG2-213 GEN
Solar/Wind Harmer
15.434
971775AH1-396 GEN
Solar/Wind Harmer
2.198
313527AB2-043 GEN
Solar/Wind Harmer
3.442
962561AG1-105 GEN
Solar/Wind Harmer
9.457
939181AE1-148 GEN
Solar/Wind Harmer
9.083
964791AG1-342 GEN
Solar/Wind Harmer
3.423
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.098
970933AG2-581 GEN
Solar/Wind Harmer
9.079
316181AB2-040 GEN
Solar/Wind Harmer
1.138
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.878
3145593CAROLNA
Solar/Wind Harmer
0.065
3145783HORNRTN
Solar/Wind Harmer
0.905
3145783HORNRTN
Solar/Wind Harmer
0.724
3145783HORNRTN
Solar/Wind Harmer
0.226
3145783HORNRTN
Solar/Wind Harmer
0.09
316222AC1-221 GEN
Solar/Wind Harmer
0.769
316426AA2-053 GEN
Solar/Wind Harmer
0.748
942751AE2-291 GEN
Solar/Wind Harmer
4.333
316274AC1-208 GEN
Solar/Wind Harmer
0.717
972187AH1-678 GEN
Adder
1.63
3146776BUCKING
Solar/Wind Helper
3.482
3146776BUCKING
Solar/Wind Helper
0.282
315821AE2-092 GEN
Solar/Wind Helper
2.994
3144293JTRSVLE
50/50
1.18
3151591KERR 2
50/50
0.277
970413AG2-270 GEN
50/50
12.405
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.535
970909AG2-566 GEN
Solar/Wind Harmer
4.036
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.307
963181AG1-167 GEN
Solar/Wind Harmer
3.68
959311AF2-222 GEN
Solar/Wind Harmer
33.514
970257AG2-171 GEN
Solar/Wind Harmer
11.575
315785AD2-033 C
Solar/Wind Harmer
6.609
964241AG1-285 GEN
Solar/Wind Harmer
19.233
316131AB2-060 GEN
Solar/Wind Harmer
2.359
316478AD1-087 GEN
Solar/Wind Harmer
1.29
316486AD2-202 GEN
Solar/Wind Harmer
0.378
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.371
960061AF2-297 GEN
Solar/Wind Harmer
6.151
971683AH1-343 GEN
Solar/Wind Harmer
4.535
966621AG1-532 GEN
Solar/Wind Harmer
0.172
313506AB2-031 GEN
Solar/Wind Harmer
0.656
316283AC2-100 C
Solar/Wind Harmer
0.705
316210AC1-098 GEN
Solar/Wind Harmer
0.995
3146776BUCKING
Solar/Wind Helper
0.313
316313AB2-026
Solar/Wind Helper
0.341
316258AE1-075 C
Solar/Wind Helper
0.306
316405AF2-144 C
Solar/Wind Helper
0.255
3148013FISHERV
Solar/Wind Helper
0.125
CPLELTFEXP_CPLE->PJM
CLTF
3.717
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.651
LAGNLTFEXP_LAGN->PJM
CLTF
1.842
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.457
TVALTFEXP_TVA->PJM
CLTF
0.904
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.19
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.966
MECLTFEXP_MEC->PJM
CLTF
0.645
SIGELTFEXP_SIGE->PJM
CLTF
0.018
NYPJM->LTFIMP_NY
CLTF
0.34
LGEELTFEXP_LGEE->PJM
CLTF
0.186
WECLTFEXP_WEC->PJM
CLTF
0.097

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:133.94 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:916.12
MW Contribution:12.9
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.289
3151621KERR 5
50/50
0.289
3151631KERR 6
50/50
0.289
3151641KERR 7
50/50
0.289
3151541CLOVER2
50/50
2.941
971845AH1-439 GEN
Solar/Wind Harmer
40.276
970285AG2-188 GEN
Solar/Wind Harmer
63.831
315657AE1-056 GEN
Solar/Wind Harmer
15.969
946301AF1-294 GEN
Solar/Wind Harmer
10.188
961791AG1-021 GEN
Solar/Wind Harmer
4.97
970683AG2-441 GEN
Solar/Wind Harmer
27.899
970681AG2-440 GEN
Solar/Wind Harmer
22.32
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.111
316239AB2-077_GEN
Solar/Wind Harmer
0.639
316238AB2-078_GEN
Solar/Wind Harmer
0.639
316118AC1-105 GEN
Solar/Wind Harmer
1.014
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.355
970865AG2-541 GEN
Solar/Wind Harmer
4.115
946281AF1-292 GEN
Solar/Wind Harmer
0.203
316087AB2-174 GEN
Solar/Wind Harmer
1.265
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.894
970165AG2-112 GEN
Solar/Wind Harmer
0.787
970163AG2-111 GEN
Solar/Wind Harmer
0.751
971967AH1-528 GEN
Solar/Wind Harmer
15.203
315607AA1-063A GEN
Solar/Wind Harmer
0.778
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.327
970581AG2-369 GEN
Solar/Wind Harmer
3.722
316319Z2-044 C
Solar/Wind Harmer
0.378
3146033SCOT NK
Solar/Wind Harmer
-0.027
315652AC1-086 GEN
Solar/Wind Harmer
7.562
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
965291AG1-394 GEN
Solar/Wind Harmer
0.582
970673AG2-436 GEN
Solar/Wind Harmer
13.618
970673AG2-436 GEN
Solar/Wind Harmer
6.895
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
270494AE1-108_GEN
Solar/Wind Helper
4.464
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.195
3151591KERR 2
50/50
0.289
970413AG2-270 GEN
50/50
12.897
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.604
970909AG2-566 GEN
Solar/Wind Harmer
4.081
3147133PAMPLIN
Solar/Wind Harmer
-0.133
971193AH1-056 GEN
Solar/Wind Harmer
26.615
963181AG1-167 GEN
Solar/Wind Harmer
3.727
959311AF2-222 GEN
Solar/Wind Harmer
34.076
970257AG2-171 GEN
Solar/Wind Harmer
11.779
315785AD2-033 C
Solar/Wind Harmer
6.734
964241AG1-285 GEN
Solar/Wind Harmer
19.68
316131AB2-060 GEN
Solar/Wind Harmer
2.422
316478AD1-087 GEN
Solar/Wind Harmer
1.342
316486AD2-202 GEN
Solar/Wind Harmer
0.393
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.389
960061AF2-297 GEN
Solar/Wind Harmer
6.458
971683AH1-343 GEN
Solar/Wind Harmer
4.759
966621AG1-532 GEN
Solar/Wind Harmer
0.184
313506AB2-031 GEN
Solar/Wind Harmer
0.706
316283AC2-100 C
Solar/Wind Harmer
0.787
316210AC1-098 GEN
Solar/Wind Harmer
1.105
316327AA2-057 GEN
Solar/Wind Harmer
0.707
970917AG2-570 GEN
Solar/Wind Harmer
17.327
3146233WITAKRS
Solar/Wind Harmer
0.143
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.004
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.382
316365GEN2_N
Solar/Wind Harmer
0.443
961601AG1-000A GEN
Solar/Wind Harmer
2.615
316317KELFORD C
Solar/Wind Harmer
0.306
3145823KELFORD
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.09
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
957521AF2-046 GEN
Solar/Wind Harmer
5.039
961681AG1-008 GEN
Solar/Wind Harmer
5.039
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.311
316313AB2-026
Solar/Wind Helper
0.332
316258AE1-075 C
Solar/Wind Helper
0.299
316405AF2-144 C
Solar/Wind Helper
0.249
3148013FISHERV
Solar/Wind Helper
0.123
3144293JTRSVLE
50/50
1.195
3144293JTRSVLE
50/50
1.007
970535AG2-341 GEN
50/50
2.934
3152661PLYWOOD A
50/50
0.28
970301AG2-198 GEN
Solar/Wind Harmer
21.495
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.212
963191AG1-168 GEN
Solar/Wind Harmer
3.727
971741AH1-377 GEN
Solar/Wind Harmer
43.991
316034AC1-036 C
Solar/Wind Harmer
0.584
970323AG2-213 GEN
Solar/Wind Harmer
15.706
971775AH1-396 GEN
Solar/Wind Harmer
2.237
313527AB2-043 GEN
Solar/Wind Harmer
3.538
962561AG1-105 GEN
Solar/Wind Harmer
9.795
939181AE1-148 GEN
Solar/Wind Harmer
9.44
964791AG1-342 GEN
Solar/Wind Harmer
3.552
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
970099AG2-077 GEN
Solar/Wind Harmer
18.81
970933AG2-581 GEN
Solar/Wind Harmer
9.592
316181AB2-040 GEN
Solar/Wind Harmer
1.225
316222AC1-221 GEN
Solar/Wind Harmer
0.857
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.951
3145593CAROLNA
Solar/Wind Harmer
0.07
3145783HORNRTN
Solar/Wind Harmer
0.982
3145783HORNRTN
Solar/Wind Harmer
0.786
3145783HORNRTN
Solar/Wind Harmer
0.245
3145783HORNRTN
Solar/Wind Harmer
0.098
316426AA2-053 GEN
Solar/Wind Harmer
0.813
316274AC1-208 GEN
Solar/Wind Harmer
0.793
942751AE2-291 GEN
Solar/Wind Harmer
4.536
972187AH1-678 GEN
Adder
1.773
972185AH1-677 GEN
Adder
3.35
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
316263AC1-034 GEN
Solar/Wind Harmer
3.126
961601AG1-000A GEN
Solar/Wind Harmer
2.583
3145893MURPHYS
Solar/Wind Harmer
0.18
3145893MURPHYS
Solar/Wind Harmer
-0.012
3145493TOT1
Solar/Wind Harmer
0.098
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
3146776BUCKING
Solar/Wind Helper
3.457
3146776BUCKING
Solar/Wind Helper
0.28
315821AE2-092 GEN
Solar/Wind Helper
2.963
3144293JTRSVLE
50/50
1.195
3151601KERR 3
50/50
0.289
3151581KERR 1
50/50
0.103
3151531CLOVER1
50/50
2.955
3147043LAWRENC
50/50
1.106
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.97
971563AH1-280 GEN
Solar/Wind Harmer
4.97
970685AG2-442 GEN
Solar/Wind Harmer
31.247
962491AG1-098 GEN
Solar/Wind Harmer
14.52
316237AB2-079_GEN
Solar/Wind Harmer
0.639
315693AD1-088 GEN
Solar/Wind Harmer
10.276
970401AG2-262 GEN
Solar/Wind Harmer
1.085
957481AF2-042 GEN
Solar/Wind Harmer
47.025
315687AD1-152 GEN
Solar/Wind Harmer
1.689
971065AG2-659 GEN
Solar/Wind Harmer
6.793
316129AC1-054 GEN
Solar/Wind Harmer
1.154
316003AC1-222 GEN
Solar/Wind Harmer
1.163
971795AH1-408 GEN
Solar/Wind Harmer
8.792
960081AF2-299 GEN
Solar/Wind Harmer
1.021
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.099
316212AC1-099_GEN
Solar/Wind Harmer
0.614
970919AG2-571 GEN
Solar/Wind Harmer
2.193
970087AG2-069 GEN
Solar/Wind Harmer
6.491
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.406
962571AG1-106 GEN
Solar/Wind Harmer
0.966
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316359AB2-059 GEN
Solar/Wind Harmer
0.899
316049AB1-081 GEN
Solar/Wind Harmer
0.72
3142053HEARTS
Solar/Wind Harmer
0.078
315722AD1-056 GEN
Solar/Wind Harmer
0.694
316023GEN1_S
Solar/Wind Harmer
0.443
3145823KELFORD
Solar/Wind Harmer
-0.006
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.191
961671AG1-007 GEN
Solar/Wind Harmer
0.08
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
316322AB2-045
Solar/Wind Helper
0.963
3146776BUCKING
Solar/Wind Helper
0.346
316336AC2-165 C
Solar/Wind Helper
1.425
CPLELTFEXP_CPLE->PJM
CLTF
4.543
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.552
LAGNLTFEXP_LAGN->PJM
CLTF
2.505
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.252
TVALTFEXP_TVA->PJM
CLTF
1.216
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.102
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.96
MECLTFEXP_MEC->PJM
CLTF
0.838
SIGELTFEXP_SIGE->PJM
CLTF
0.022
NYPJM->LTFIMP_NY
CLTF
0.295
LGEELTFEXP_LGEE->PJM
CLTF
0.219
WECLTFEXP_WEC->PJM
CLTF
0.123

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2003-205_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2003-205_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:130.34 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:891.54
MW Contribution:12.73
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.284
3151621KERR 5
50/50
0.284
3151631KERR 6
50/50
0.284
3151641KERR 7
50/50
0.284
3151541CLOVER2
50/50
2.903
971845AH1-439 GEN
Solar/Wind Harmer
40.178
970285AG2-188 GEN
Solar/Wind Harmer
63.671
3144293JTRSVLE
50/50
1.19
3151601KERR 3
50/50
0.284
3151581KERR 1
50/50
0.102
3151531CLOVER1
50/50
2.917
3147043LAWRENC
50/50
1.102
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.946
971563AH1-280 GEN
Solar/Wind Harmer
4.946
970685AG2-442 GEN
Solar/Wind Harmer
31.078
962491AG1-098 GEN
Solar/Wind Harmer
14.404
316237AB2-079_GEN
Solar/Wind Harmer
0.632
315693AD1-088 GEN
Solar/Wind Harmer
10.19
970401AG2-262 GEN
Solar/Wind Harmer
1.07
957481AF2-042 GEN
Solar/Wind Harmer
46.506
315687AD1-152 GEN
Solar/Wind Harmer
1.657
971065AG2-659 GEN
Solar/Wind Harmer
6.686
316129AC1-054 GEN
Solar/Wind Harmer
1.136
971795AH1-408 GEN
Solar/Wind Harmer
8.781
316003AC1-222 GEN
Solar/Wind Harmer
1.14
960081AF2-299 GEN
Solar/Wind Harmer
1.025
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.097
316212AC1-099_GEN
Solar/Wind Harmer
0.591
970919AG2-571 GEN
Solar/Wind Harmer
2.137
970087AG2-069 GEN
Solar/Wind Harmer
6.318
316023GEN1_S
Solar/Wind Harmer
0.452
316011AB1-132 GEN
Solar/Wind Harmer
1.389
962571AG1-106 GEN
Solar/Wind Harmer
0.954
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
-0.026
315722AD1-056 GEN
Solar/Wind Harmer
0.667
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.005
315657AE1-056 GEN
Solar/Wind Harmer
15.898
946301AF1-294 GEN
Solar/Wind Harmer
10.139
961791AG1-021 GEN
Solar/Wind Harmer
4.946
970683AG2-441 GEN
Solar/Wind Harmer
27.748
316322AB2-045
Solar/Wind Helper
0.967
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.456
970681AG2-440 GEN
Solar/Wind Harmer
22.198
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.073
316239AB2-077_GEN
Solar/Wind Harmer
0.632
316238AB2-078_GEN
Solar/Wind Harmer
0.632
316118AC1-105 GEN
Solar/Wind Harmer
0.997
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.254
970865AG2-541 GEN
Solar/Wind Harmer
4.048
946281AF1-292 GEN
Solar/Wind Harmer
0.204
316087AB2-174 GEN
Solar/Wind Harmer
1.262
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.884
970165AG2-112 GEN
Solar/Wind Harmer
0.778
970163AG2-111 GEN
Solar/Wind Harmer
0.742
971967AH1-528 GEN
Solar/Wind Harmer
15.039
315607AA1-063A GEN
Solar/Wind Harmer
0.762
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.212
970581AG2-369 GEN
Solar/Wind Harmer
3.623
315652AC1-086 GEN
Solar/Wind Harmer
7.469
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.026
316319Z2-044 C
Solar/Wind Harmer
0.36
970673AG2-436 GEN
Solar/Wind Harmer
13.449
970673AG2-436 GEN
Solar/Wind Harmer
6.81
965291AG1-394 GEN
Solar/Wind Harmer
0.565
270494AE1-108_GEN
Solar/Wind Helper
4.476
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.19
3144293JTRSVLE
50/50
1.002
970535AG2-341 GEN
50/50
2.898
3152661PLYWOOD A
50/50
0.275
970301AG2-198 GEN
Solar/Wind Harmer
21.406
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.183
963191AG1-168 GEN
Solar/Wind Harmer
3.71
971741AH1-377 GEN
Solar/Wind Harmer
43.786
316034AC1-036 C
Solar/Wind Harmer
0.58
970323AG2-213 GEN
Solar/Wind Harmer
15.608
971775AH1-396 GEN
Solar/Wind Harmer
2.223
313527AB2-043 GEN
Solar/Wind Harmer
3.505
962561AG1-105 GEN
Solar/Wind Harmer
9.664
939181AE1-148 GEN
Solar/Wind Harmer
9.308
964791AG1-342 GEN
Solar/Wind Harmer
3.501
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.602
970933AG2-581 GEN
Solar/Wind Harmer
9.49
316181AB2-040 GEN
Solar/Wind Harmer
1.218
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.934
3145593CAROLNA
Solar/Wind Harmer
0.069
3145783HORNRTN
Solar/Wind Harmer
0.963
3145783HORNRTN
Solar/Wind Harmer
0.77
3145783HORNRTN
Solar/Wind Harmer
0.241
3145783HORNRTN
Solar/Wind Harmer
0.096
316222AC1-221 GEN
Solar/Wind Harmer
0.802
316426AA2-053 GEN
Solar/Wind Harmer
0.797
316274AC1-208 GEN
Solar/Wind Harmer
0.766
942751AE2-291 GEN
Solar/Wind Harmer
4.503
972187AH1-678 GEN
Adder
1.745
972185AH1-677 GEN
Adder
3.302
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3146776BUCKING
Solar/Wind Helper
3.47
3146776BUCKING
Solar/Wind Helper
0.281
315821AE2-092 GEN
Solar/Wind Helper
2.982
3144293JTRSVLE
50/50
1.19
3151591KERR 2
50/50
0.284
970413AG2-270 GEN
50/50
12.729
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.576
970909AG2-566 GEN
Solar/Wind Harmer
4.064
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.496
963181AG1-167 GEN
Solar/Wind Harmer
3.71
959311AF2-222 GEN
Solar/Wind Harmer
33.872
970257AG2-171 GEN
Solar/Wind Harmer
11.706
315785AD2-033 C
Solar/Wind Harmer
6.689
964241AG1-285 GEN
Solar/Wind Harmer
19.525
316131AB2-060 GEN
Solar/Wind Harmer
2.4
316478AD1-087 GEN
Solar/Wind Harmer
1.324
316486AD2-202 GEN
Solar/Wind Harmer
0.388
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.381
960061AF2-297 GEN
Solar/Wind Harmer
6.325
971683AH1-343 GEN
Solar/Wind Harmer
4.674
966621AG1-532 GEN
Solar/Wind Harmer
0.185
313506AB2-031 GEN
Solar/Wind Harmer
0.702
316283AC2-100 C
Solar/Wind Harmer
0.736
316210AC1-098 GEN
Solar/Wind Harmer
1.064
970917AG2-570 GEN
Solar/Wind Harmer
16.885
316365GEN2_N
Solar/Wind Harmer
0.452
316327AA2-057 GEN
Solar/Wind Harmer
0.676
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.136
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
315724AD1-057 GEN
Solar/Wind Harmer
0.367
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.312
316313AB2-026
Solar/Wind Helper
0.342
316258AE1-075 C
Solar/Wind Helper
0.307
316405AF2-144 C
Solar/Wind Helper
0.256
3148013FISHERV
Solar/Wind Helper
0.124
CPLELTFEXP_CPLE->PJM
CLTF
3.951
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.116
LAGNLTFEXP_LAGN->PJM
CLTF
2.085
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.001
TVALTFEXP_TVA->PJM
CLTF
1.025
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.511
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.403
MECLTFEXP_MEC->PJM
CLTF
0.809
SIGELTFEXP_SIGE->PJM
CLTF
0.023
NYPJM->LTFIMP_NY
CLTF
0.315
LGEELTFEXP_LGEE->PJM
CLTF
0.251
WECLTFEXP_WEC->PJM
CLTF
0.133

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:121.65 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:832.11
MW Contribution:12.58
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.186
3151591KERR 2
50/50
0.281
970413AG2-270 GEN
50/50
12.579
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.561
970909AG2-566 GEN
Solar/Wind Harmer
4.052
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.429
963181AG1-167 GEN
Solar/Wind Harmer
3.699
959311AF2-222 GEN
Solar/Wind Harmer
33.746
970257AG2-171 GEN
Solar/Wind Harmer
11.66
315785AD2-033 C
Solar/Wind Harmer
6.661
964241AG1-285 GEN
Solar/Wind Harmer
19.423
316131AB2-060 GEN
Solar/Wind Harmer
2.386
316478AD1-087 GEN
Solar/Wind Harmer
1.308
316486AD2-202 GEN
Solar/Wind Harmer
0.383
316248AF1-058 C
Solar/Wind Harmer
0.384
960061AF2-297 GEN
Solar/Wind Harmer
6.368
3147043LAWRENC
Solar/Wind Harmer
-0.007
971683AH1-343 GEN
Solar/Wind Harmer
4.838
966621AG1-532 GEN
Solar/Wind Harmer
0.176
313506AB2-031 GEN
Solar/Wind Harmer
0.67
316283AC2-100 C
Solar/Wind Harmer
0.725
316210AC1-098 GEN
Solar/Wind Harmer
1.021
970917AG2-570 GEN
Solar/Wind Harmer
16.174
316327AA2-057 GEN
Solar/Wind Harmer
0.648
3146263WOODLND
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.312
316313AB2-026
Solar/Wind Helper
0.338
316258AE1-075 C
Solar/Wind Helper
0.304
316405AF2-144 C
Solar/Wind Helper
0.253
3148013FISHERV
Solar/Wind Helper
0.124
3151611KERR 4
50/50
0.281
3151621KERR 5
50/50
0.281
3151631KERR 6
50/50
0.281
3151641KERR 7
50/50
0.281
3151541CLOVER2
50/50
2.869
971845AH1-439 GEN
Solar/Wind Harmer
40.155
970285AG2-188 GEN
Solar/Wind Harmer
63.627
315657AE1-056 GEN
Solar/Wind Harmer
15.857
946301AF1-294 GEN
Solar/Wind Harmer
10.111
961791AG1-021 GEN
Solar/Wind Harmer
4.932
970683AG2-441 GEN
Solar/Wind Harmer
27.657
970681AG2-440 GEN
Solar/Wind Harmer
22.126
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.048
316239AB2-077_GEN
Solar/Wind Harmer
0.628
316238AB2-078_GEN
Solar/Wind Harmer
0.628
316118AC1-105 GEN
Solar/Wind Harmer
1
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.134
970865AG2-541 GEN
Solar/Wind Harmer
4.26
316123AC1-075 GEN
Solar/Wind Harmer
0.971
970165AG2-112 GEN
Solar/Wind Harmer
0.855
970163AG2-111 GEN
Solar/Wind Harmer
0.816
946281AF1-292 GEN
Solar/Wind Harmer
0.194
316087AB2-174 GEN
Solar/Wind Harmer
1.202
3137643SOCKMAN
Solar/Wind Harmer
-0.032
971967AH1-528 GEN
Solar/Wind Harmer
14.485
315607AA1-063A GEN
Solar/Wind Harmer
0.732
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.036
970581AG2-369 GEN
Solar/Wind Harmer
3.471
270494AE1-108_GEN
Solar/Wind Helper
4.511
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.186
3144293JTRSVLE
50/50
0.999
970535AG2-341 GEN
50/50
2.873
3152661PLYWOOD A
50/50
0.275
970301AG2-198 GEN
Solar/Wind Harmer
21.341
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.165
963191AG1-168 GEN
Solar/Wind Harmer
3.699
971741AH1-377 GEN
Solar/Wind Harmer
43.617
316034AC1-036 C
Solar/Wind Harmer
0.578
970323AG2-213 GEN
Solar/Wind Harmer
15.547
971775AH1-396 GEN
Solar/Wind Harmer
2.214
313527AB2-043 GEN
Solar/Wind Harmer
3.483
962561AG1-105 GEN
Solar/Wind Harmer
9.649
964791AG1-342 GEN
Solar/Wind Harmer
3.499
939181AE1-148 GEN
Solar/Wind Harmer
9.211
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.337
970933AG2-581 GEN
Solar/Wind Harmer
9.235
316181AB2-040 GEN
Solar/Wind Harmer
1.163
942751AE2-291 GEN
Solar/Wind Harmer
5.136
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.898
3145593CAROLNA
Solar/Wind Harmer
0.066
316222AC1-221 GEN
Solar/Wind Harmer
0.791
3145783HORNRTN
Solar/Wind Harmer
0.925
3145783HORNRTN
Solar/Wind Harmer
0.74
3145783HORNRTN
Solar/Wind Harmer
0.231
3145783HORNRTN
Solar/Wind Harmer
0.092
316426AA2-053 GEN
Solar/Wind Harmer
0.765
316274AC1-208 GEN
Solar/Wind Harmer
0.735
972187AH1-678 GEN
Adder
1.669
3146776BUCKING
Solar/Wind Helper
3.473
3146776BUCKING
Solar/Wind Helper
0.281
315821AE2-092 GEN
Solar/Wind Helper
2.981
3144293JTRSVLE
50/50
1.186
3151601KERR 3
50/50
0.281
3151581KERR 1
50/50
0.1
3151531CLOVER1
50/50
2.882
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.932
971563AH1-280 GEN
Solar/Wind Harmer
4.932
970685AG2-442 GEN
Solar/Wind Harmer
30.976
962491AG1-098 GEN
Solar/Wind Harmer
14.277
316237AB2-079_GEN
Solar/Wind Harmer
0.628
315693AD1-088 GEN
Solar/Wind Harmer
10.093
970401AG2-262 GEN
Solar/Wind Harmer
1.069
957481AF2-042 GEN
Solar/Wind Harmer
45.841
315687AD1-152 GEN
Solar/Wind Harmer
1.641
971065AG2-659 GEN
Solar/Wind Harmer
6.575
316129AC1-054 GEN
Solar/Wind Harmer
1.116
3147043LAWRENC
Adder
1.01
316003AC1-222 GEN
Solar/Wind Harmer
1.164
971795AH1-408 GEN
Solar/Wind Harmer
8.484
960081AF2-299 GEN
Solar/Wind Harmer
0.973
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.093
316212AC1-099_GEN
Solar/Wind Harmer
0.567
970919AG2-571 GEN
Solar/Wind Harmer
2.047
970087AG2-069 GEN
Solar/Wind Harmer
6.053
3146263WOODLND
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.968
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.444
CPLELTFEXP_CPLE->PJM
CLTF
3.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.48
LAGNLTFEXP_LAGN->PJM
CLTF
1.974
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.732
TVALTFEXP_TVA->PJM
CLTF
0.969
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.023
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.205
MECLTFEXP_MEC->PJM
CLTF
0.743
SIGELTFEXP_SIGE->PJM
CLTF
0.021
NYPJM->LTFIMP_NY
CLTF
0.299
LGEELTFEXP_LGEE->PJM
CLTF
0.225
WECLTFEXP_WEC->PJM
CLTF
0.119

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.81 %
Rating:559.3 MVA
Rating Type:A
MVA to Mitigate:647.7
MW Contribution:12.48
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.279
3151621KERR 5
50/50
0.279
3151631KERR 6
50/50
0.279
3151641KERR 7
50/50
0.279
3151541CLOVER2
50/50
2.847
3151281ROARAP4
50/50
0.085
3151281ROARAP4
50/50
0.08
963041AG1-153 GEN
50/50
1.549
971845AH1-439 GEN
Solar/Wind Harmer
30.485
970285AG2-188 GEN
Solar/Wind Harmer
51.175
315657AE1-056 GEN
Solar/Wind Harmer
12.95
946301AF1-294 GEN
Solar/Wind Harmer
6.911
961791AG1-021 GEN
Solar/Wind Harmer
3.362
970683AG2-441 GEN
Solar/Wind Harmer
20.935
970681AG2-440 GEN
Solar/Wind Harmer
16.748
3144303KENBRDG
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
4.574
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.327
3147173SINAI
Solar/Wind Harmer
0.11
3147243WELCO
Solar/Wind Harmer
0.069
970831AG2-522 GEN
Solar/Wind Harmer
4.619
970865AG2-541 GEN
Solar/Wind Harmer
3.009
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.287
316123AC1-075 GEN
Solar/Wind Harmer
0.097
970165AG2-112 GEN
Solar/Wind Harmer
0.577
970163AG2-111 GEN
Solar/Wind Harmer
0.551
971967AH1-528 GEN
Solar/Wind Harmer
10.885
315607AA1-063A GEN
Solar/Wind Harmer
0.13
3146043SEABORD
Solar/Wind Harmer
0.063
970085AG2-068 GEN
Solar/Wind Harmer
3.037
970581AG2-369 GEN
Solar/Wind Harmer
2.612
270494AE1-108_GEN
Solar/Wind Helper
4.476
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.183
3151601KERR 3
50/50
0.279
3151581KERR 1
50/50
0.1
3151531CLOVER1
50/50
2.861
3147043LAWRENC
50/50
1.063
3151261ROARAP2
50/50
0.088
3151051BRUNSWICKS1
50/50
1.588
3151021BRUNSWICKG1
50/50
0.765
971451AH1-221 GEN
50/50
2.324
3146926FARMVIL
Solar/Wind Harmer
0.316
963171AG1-166 GEN
Solar/Wind Harmer
1.868
971563AH1-280 GEN
Solar/Wind Harmer
3.736
970685AG2-442 GEN
Solar/Wind Harmer
23.448
962491AG1-098 GEN
Solar/Wind Harmer
10.797
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
8.584
970401AG2-262 GEN
Solar/Wind Harmer
0.842
957481AF2-042 GEN
Solar/Wind Harmer
34.592
315687AD1-152 GEN
Solar/Wind Harmer
0.004
971065AG2-659 GEN
Solar/Wind Harmer
4.952
316129AC1-054 GEN
Solar/Wind Harmer
0.422
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971795AH1-408 GEN
Solar/Wind Harmer
6.656
960081AF2-299 GEN
Solar/Wind Harmer
0.732
3145783HORNRTN
Solar/Wind Harmer
0.069
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
0.296
970919AG2-571 GEN
Solar/Wind Harmer
2.029
970087AG2-069 GEN
Solar/Wind Harmer
4.556
316322AB2-045
Solar/Wind Helper
0.968
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.445
3144293JTRSVLE
50/50
1.183
3144293JTRSVLE
50/50
0.996
970535AG2-341 GEN
50/50
2.851
3152661PLYWOOD A
50/50
0.269
3151041BRUNSWICKG3
50/50
0.765
972187AH1-678 GEN
50/50
1.756
970301AG2-198 GEN
Solar/Wind Harmer
16.182
3147133PAMPLIN
Solar/Wind Harmer
0.375
3147133PAMPLIN
Solar/Wind Harmer
0.3
958211AF2-115 GEN
Solar/Wind Harmer
4.203
963191AG1-168 GEN
Solar/Wind Harmer
1.401
971741AH1-377 GEN
Solar/Wind Harmer
33.06
316034AC1-036 C
Solar/Wind Harmer
0.02
970323AG2-213 GEN
Solar/Wind Harmer
11.759
971775AH1-396 GEN
Solar/Wind Harmer
0.441
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
7.224
939181AE1-148 GEN
Solar/Wind Harmer
6.94
964791AG1-342 GEN
Solar/Wind Harmer
2.755
3146843MT LREL
Solar/Wind Harmer
0.143
3146843MT LREL
Solar/Wind Harmer
0.143
970099AG2-077 GEN
Solar/Wind Harmer
13.837
970933AG2-581 GEN
Solar/Wind Harmer
6.964
316181AB2-040 GEN
Solar/Wind Harmer
0.107
3145593CAROLNA
Solar/Wind Harmer
0.07
3145593CAROLNA
Solar/Wind Harmer
0.07
966811AG1-552 GEN
Solar/Wind Harmer
0.763
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.221
3145783HORNRTN
Solar/Wind Harmer
0.977
3145783HORNRTN
Solar/Wind Harmer
0.305
3145783HORNRTN
Solar/Wind Harmer
0.122
316222AC1-221 GEN
Solar/Wind Harmer
0.284
316426AA2-053 GEN
Solar/Wind Harmer
0.225
942751AE2-291 GEN
Solar/Wind Harmer
3.338
316274AC1-208 GEN
Solar/Wind Harmer
0.311
3146776BUCKING
Solar/Wind Helper
3.475
3146776BUCKING
Solar/Wind Helper
0.282
315821AE2-092 GEN
Solar/Wind Helper
2.978
3144293JTRSVLE
50/50
1.183
3151591KERR 2
50/50
0.279
970413AG2-270 GEN
50/50
12.485
3151261ROARAP2
50/50
0.086
3151031BRUNSWICKG2
50/50
0.765
3146926FARMVIL
Solar/Wind Harmer
0.316
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.045
3147133PAMPLIN
Solar/Wind Harmer
1.178
971193AH1-056 GEN
Solar/Wind Harmer
22.863
963181AG1-167 GEN
Solar/Wind Harmer
1.401
959311AF2-222 GEN
Solar/Wind Harmer
25.479
970257AG2-171 GEN
Solar/Wind Harmer
8.819
315785AD2-033 C
Solar/Wind Harmer
2.117
964241AG1-285 GEN
Solar/Wind Harmer
14.665
316131AB2-060 GEN
Solar/Wind Harmer
0.615
316478AD1-087 GEN
Solar/Wind Harmer
0.466
316486AD2-202 GEN
Solar/Wind Harmer
0.137
3147043LAWRENC
Solar/Wind Harmer
0.066
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.708
971683AH1-343 GEN
Solar/Wind Harmer
3.476
313506AB2-031 GEN
Solar/Wind Harmer
0.227
316283AC2-100 C
Solar/Wind Harmer
0.132
316210AC1-098 GEN
Solar/Wind Harmer
0.531
970917AG2-570 GEN
Solar/Wind Harmer
5.072
316327AA2-057 GEN
Solar/Wind Harmer
0.085
3146776BUCKING
Solar/Wind Helper
0.313
316313AB2-026
Solar/Wind Helper
0.338
316258AE1-075 C
Solar/Wind Helper
0.304
316405AF2-144 C
Solar/Wind Helper
0.253
3148013FISHERV
Solar/Wind Helper
0.123
CPLELTFEXP_CPLE->PJM
CLTF
3.789
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.54
LAGNLTFEXP_LAGN->PJM
CLTF
1.976
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.656
TVALTFEXP_TVA->PJM
CLTF
0.971
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.153
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.217
MECLTFEXP_MEC->PJM
CLTF
0.756
SIGELTFEXP_SIGE->PJM
CLTF
0.021
NYPJM->LTFIMP_NY
CLTF
0.298
LGEELTFEXP_LGEE->PJM
CLTF
0.232
WECLTFEXP_WEC->PJM
CLTF
0.123

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:219.98 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1537.65
MW Contribution:29.95
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.83
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
971845AH1-439 GEN
Solar/Wind Harmer
44.827
970285AG2-188 GEN
Solar/Wind Harmer
71.81
315657AE1-056 GEN
Solar/Wind Harmer
20.233
946301AF1-294 GEN
Solar/Wind Harmer
13.088
961791AG1-021 GEN
Solar/Wind Harmer
6.384
970683AG2-441 GEN
Solar/Wind Harmer
36.677
970681AG2-440 GEN
Solar/Wind Harmer
29.342
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.305
971967AH1-528 GEN
Solar/Wind Harmer
73.277
316239AB2-077_GEN
Solar/Wind Harmer
0.969
316238AB2-078_GEN
Solar/Wind Harmer
0.969
316118AC1-105 GEN
Solar/Wind Harmer
1.805
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.02
970831AG2-522 GEN
Solar/Wind Harmer
9.81
316123AC1-075 GEN
Solar/Wind Harmer
1.786
970165AG2-112 GEN
Solar/Wind Harmer
1.573
970163AG2-111 GEN
Solar/Wind Harmer
1.5
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.489
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.631
270457AD2-023 GEN
Solar/Wind Harmer
0.827
315607AA1-063A GEN
Solar/Wind Harmer
0.88
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.41
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.561
270494AE1-108_GEN
Solar/Wind Helper
3.67
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.067
3148013FISHERV
Solar/Wind Helper
0.064
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.863
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.477
972003AH1-546 GEN
Solar/Wind Harmer
49.791
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.384
971563AH1-280 GEN
Solar/Wind Harmer
6.384
970685AG2-442 GEN
Solar/Wind Harmer
41.078
962491AG1-098 GEN
Solar/Wind Harmer
28.511
315693AD1-088 GEN
Solar/Wind Harmer
20.878
957481AF2-042 GEN
Solar/Wind Harmer
119.657
316237AB2-079_GEN
Solar/Wind Harmer
0.969
315687AD1-152 GEN
Solar/Wind Harmer
3.719
970401AG2-262 GEN
Solar/Wind Harmer
1.826
316003AC1-222 GEN
Solar/Wind Harmer
2.228
971065AG2-659 GEN
Solar/Wind Harmer
10.772
316129AC1-054 GEN
Solar/Wind Harmer
1.807
971795AH1-408 GEN
Solar/Wind Harmer
11.365
960081AF2-299 GEN
Solar/Wind Harmer
1.184
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.962
316049AB1-081 GEN
Solar/Wind Harmer
0.77
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.712
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
970223AG2-152 GEN
Solar/Wind Harmer
5.769
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.191
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.405
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.316
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.627
3152661PLYWOOD A
50/50
0.509
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.363
971741AH1-377 GEN
Solar/Wind Harmer
63.743
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.98
963191AG1-168 GEN
Solar/Wind Harmer
4.788
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.282
971775AH1-396 GEN
Solar/Wind Harmer
3.031
970933AG2-581 GEN
Solar/Wind Harmer
36.542
970099AG2-077 GEN
Solar/Wind Harmer
47.863
313527AB2-043 GEN
Solar/Wind Harmer
5.319
962561AG1-105 GEN
Solar/Wind Harmer
16.15
964791AG1-342 GEN
Solar/Wind Harmer
5.978
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.382
942751AE2-291 GEN
Solar/Wind Harmer
9.268
316222AC1-221 GEN
Solar/Wind Harmer
1.428
316181AB2-040 GEN
Solar/Wind Harmer
1.451
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.155
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.18
3145783HORNRTN
Solar/Wind Harmer
0.944
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.888
316263AC1-034 GEN
Solar/Wind Harmer
3.343
961601AG1-000A GEN
Solar/Wind Harmer
2.724
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.041
316197AC1-042 GEN
Solar/Wind Harmer
0.789
942671AE2-283 GEN
Solar/Wind Harmer
2.125
315821AE2-092 GEN
Solar/Wind Helper
2.535
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.951
3151591KERR 2
50/50
0.482
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.336
970909AG2-566 GEN
Solar/Wind Harmer
5.575
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.721
963181AG1-167 GEN
Solar/Wind Harmer
4.788
959311AF2-222 GEN
Solar/Wind Harmer
45.74
970257AG2-171 GEN
Solar/Wind Harmer
15.961
315785AD2-033 C
Solar/Wind Harmer
9.254
964241AG1-285 GEN
Solar/Wind Harmer
28.298
316478AD1-087 GEN
Solar/Wind Harmer
3.113
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.606
316248AF1-058 C
Solar/Wind Harmer
0.74
960061AF2-297 GEN
Solar/Wind Harmer
12.278
971683AH1-343 GEN
Solar/Wind Harmer
9.189
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.301
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.773
316210AC1-098 GEN
Solar/Wind Harmer
1.19
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.758
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.392
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.405
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.318
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
3148013FISHERV
Solar/Wind Helper
0.111
CPLELTFEXP_CPLE->PJM
CLTF
5.212
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.402
LAGNLTFEXP_LAGN->PJM
CLTF
3.179
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.848
TVALTFEXP_TVA->PJM
CLTF
1.583
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.278
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.374
MECLTFEXP_MEC->PJM
CLTF
1.462
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.53
LGEELTFEXP_LGEE->PJM
CLTF
0.51
WECLTFEXP_WEC->PJM
CLTF
0.265

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:219.92 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1537.26
MW Contribution:29.95
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.83
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
971845AH1-439 GEN
Solar/Wind Harmer
44.827
970285AG2-188 GEN
Solar/Wind Harmer
71.81
315657AE1-056 GEN
Solar/Wind Harmer
20.233
946301AF1-294 GEN
Solar/Wind Harmer
13.088
961791AG1-021 GEN
Solar/Wind Harmer
6.384
970683AG2-441 GEN
Solar/Wind Harmer
36.677
970681AG2-440 GEN
Solar/Wind Harmer
29.342
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.305
971967AH1-528 GEN
Solar/Wind Harmer
73.277
316239AB2-077_GEN
Solar/Wind Harmer
0.969
316238AB2-078_GEN
Solar/Wind Harmer
0.969
316118AC1-105 GEN
Solar/Wind Harmer
1.805
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.02
970831AG2-522 GEN
Solar/Wind Harmer
9.81
316123AC1-075 GEN
Solar/Wind Harmer
1.786
970165AG2-112 GEN
Solar/Wind Harmer
1.573
970163AG2-111 GEN
Solar/Wind Harmer
1.5
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.489
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.631
270457AD2-023 GEN
Solar/Wind Harmer
0.827
315607AA1-063A GEN
Solar/Wind Harmer
0.88
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.41
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.561
270494AE1-108_GEN
Solar/Wind Helper
3.67
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.067
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.863
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.477
972003AH1-546 GEN
Solar/Wind Harmer
49.791
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.384
971563AH1-280 GEN
Solar/Wind Harmer
6.384
970685AG2-442 GEN
Solar/Wind Harmer
41.078
962491AG1-098 GEN
Solar/Wind Harmer
28.511
315693AD1-088 GEN
Solar/Wind Harmer
20.878
957481AF2-042 GEN
Solar/Wind Harmer
119.657
316237AB2-079_GEN
Solar/Wind Harmer
0.969
315687AD1-152 GEN
Solar/Wind Harmer
3.719
970401AG2-262 GEN
Solar/Wind Harmer
1.826
316003AC1-222 GEN
Solar/Wind Harmer
2.228
971065AG2-659 GEN
Solar/Wind Harmer
10.772
316129AC1-054 GEN
Solar/Wind Harmer
1.807
971795AH1-408 GEN
Solar/Wind Harmer
11.365
960081AF2-299 GEN
Solar/Wind Harmer
1.184
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.962
316049AB1-081 GEN
Solar/Wind Harmer
0.77
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.712
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
970223AG2-152 GEN
Solar/Wind Harmer
5.769
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.191
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.405
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.316
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.627
3152661PLYWOOD A
50/50
0.509
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.363
971741AH1-377 GEN
Solar/Wind Harmer
63.743
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.98
963191AG1-168 GEN
Solar/Wind Harmer
4.788
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.282
971775AH1-396 GEN
Solar/Wind Harmer
3.031
970933AG2-581 GEN
Solar/Wind Harmer
36.542
970099AG2-077 GEN
Solar/Wind Harmer
47.863
313527AB2-043 GEN
Solar/Wind Harmer
5.319
962561AG1-105 GEN
Solar/Wind Harmer
16.15
964791AG1-342 GEN
Solar/Wind Harmer
5.978
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.382
3148013FISHERV
Solar/Wind Helper
0.064
942751AE2-291 GEN
Solar/Wind Harmer
9.268
316222AC1-221 GEN
Solar/Wind Harmer
1.428
316181AB2-040 GEN
Solar/Wind Harmer
1.451
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.155
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.18
3145783HORNRTN
Solar/Wind Harmer
0.944
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.888
316263AC1-034 GEN
Solar/Wind Harmer
3.343
961601AG1-000A GEN
Solar/Wind Harmer
2.724
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.041
316197AC1-042 GEN
Solar/Wind Harmer
0.789
942671AE2-283 GEN
Solar/Wind Harmer
2.125
315821AE2-092 GEN
Solar/Wind Helper
2.535
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.951
3151591KERR 2
50/50
0.482
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.336
970909AG2-566 GEN
Solar/Wind Harmer
5.575
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.721
963181AG1-167 GEN
Solar/Wind Harmer
4.788
959311AF2-222 GEN
Solar/Wind Harmer
45.74
970257AG2-171 GEN
Solar/Wind Harmer
15.961
315785AD2-033 C
Solar/Wind Harmer
9.254
964241AG1-285 GEN
Solar/Wind Harmer
28.298
316478AD1-087 GEN
Solar/Wind Harmer
3.113
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.606
316248AF1-058 C
Solar/Wind Harmer
0.74
960061AF2-297 GEN
Solar/Wind Harmer
12.278
971683AH1-343 GEN
Solar/Wind Harmer
9.189
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.301
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.773
316210AC1-098 GEN
Solar/Wind Harmer
1.19
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.758
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.392
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.405
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.318
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
3148013FISHERV
Solar/Wind Helper
0.111
CPLELTFEXP_CPLE->PJM
CLTF
5.212
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.402
LAGNLTFEXP_LAGN->PJM
CLTF
3.179
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.848
TVALTFEXP_TVA->PJM
CLTF
1.583
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.278
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.374
MECLTFEXP_MEC->PJM
CLTF
1.462
SIGELTFEXP_SIGE->PJM
CLTF
0.043
NYPJM->LTFIMP_NY
CLTF
0.53
LGEELTFEXP_LGEE->PJM
CLTF
0.51
WECLTFEXP_WEC->PJM
CLTF
0.265

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:216.35 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1512.31
MW Contribution:29.89
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.826
970285AG2-188 GEN
Solar/Wind Harmer
71.806
315657AE1-056 GEN
Solar/Wind Harmer
20.219
946301AF1-294 GEN
Solar/Wind Harmer
13.078
961791AG1-021 GEN
Solar/Wind Harmer
6.379
970683AG2-441 GEN
Solar/Wind Harmer
36.643
972003AH1-546 GEN
Solar/Wind Harmer
49.802
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.343
971741AH1-377 GEN
Solar/Wind Harmer
63.689
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.974
963191AG1-168 GEN
Solar/Wind Harmer
4.785
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.258
971775AH1-396 GEN
Solar/Wind Harmer
3.027
970933AG2-581 GEN
Solar/Wind Harmer
36.473
970099AG2-077 GEN
Solar/Wind Harmer
47.77
313527AB2-043 GEN
Solar/Wind Harmer
5.31
962561AG1-105 GEN
Solar/Wind Harmer
16.108
964791AG1-342 GEN
Solar/Wind Harmer
5.961
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.346
942751AE2-291 GEN
Solar/Wind Harmer
9.222
316222AC1-221 GEN
Solar/Wind Harmer
1.414
316181AB2-040 GEN
Solar/Wind Harmer
1.452
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.154
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.178
3145783HORNRTN
Solar/Wind Harmer
0.943
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.884
316263AC1-034 GEN
Solar/Wind Harmer
3.306
961601AG1-000A GEN
Solar/Wind Harmer
2.693
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
316217AC1-145 GEN
Solar/Wind Harmer
1.032
316197AC1-042 GEN
Solar/Wind Harmer
0.782
942671AE2-283 GEN
Solar/Wind Harmer
2.107
315821AE2-092 GEN
Solar/Wind Helper
2.531
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.331
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
-0.168
970681AG2-440 GEN
Solar/Wind Harmer
29.315
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.296
971967AH1-528 GEN
Solar/Wind Harmer
73.139
316239AB2-077_GEN
Solar/Wind Harmer
0.967
316238AB2-078_GEN
Solar/Wind Harmer
0.967
316118AC1-105 GEN
Solar/Wind Harmer
1.799
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.987
970831AG2-522 GEN
Solar/Wind Harmer
9.789
316123AC1-075 GEN
Solar/Wind Harmer
1.778
970165AG2-112 GEN
Solar/Wind Harmer
1.566
970163AG2-111 GEN
Solar/Wind Harmer
1.494
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.49
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.605
270457AD2-023 GEN
Solar/Wind Harmer
0.814
315607AA1-063A GEN
Solar/Wind Harmer
0.881
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.406
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.564
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.379
971563AH1-280 GEN
Solar/Wind Harmer
6.379
970685AG2-442 GEN
Solar/Wind Harmer
41.041
962491AG1-098 GEN
Solar/Wind Harmer
28.467
315693AD1-088 GEN
Solar/Wind Harmer
20.844
957481AF2-042 GEN
Solar/Wind Harmer
119.424
316237AB2-079_GEN
Solar/Wind Harmer
0.967
315687AD1-152 GEN
Solar/Wind Harmer
3.708
970401AG2-262 GEN
Solar/Wind Harmer
1.822
316003AC1-222 GEN
Solar/Wind Harmer
2.219
971065AG2-659 GEN
Solar/Wind Harmer
10.747
316129AC1-054 GEN
Solar/Wind Harmer
1.803
971795AH1-408 GEN
Solar/Wind Harmer
11.364
960081AF2-299 GEN
Solar/Wind Harmer
1.186
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.658
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.951
316049AB1-081 GEN
Solar/Wind Harmer
0.761
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.707
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
970223AG2-152 GEN
Solar/Wind Harmer
5.68
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.385
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.31
971193AH1-056 GEN
Solar/Wind Harmer
33.698
963181AG1-167 GEN
Solar/Wind Harmer
4.785
959311AF2-222 GEN
Solar/Wind Harmer
45.693
970257AG2-171 GEN
Solar/Wind Harmer
15.944
315785AD2-033 C
Solar/Wind Harmer
9.243
964241AG1-285 GEN
Solar/Wind Harmer
28.257
316478AD1-087 GEN
Solar/Wind Harmer
3.106
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.6
316248AF1-058 C
Solar/Wind Harmer
0.737
960061AF2-297 GEN
Solar/Wind Harmer
12.232
971683AH1-343 GEN
Solar/Wind Harmer
9.152
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.287
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.767
316210AC1-098 GEN
Solar/Wind Harmer
1.185
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.727
315724AD1-057 GEN
Solar/Wind Harmer
0.389
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.385
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:213.74 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:1221.6
MW Contribution:29.89
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.103
971845AH1-439 GEN
Solar/Wind Harmer
34.045
970285AG2-188 GEN
Solar/Wind Harmer
57.782
315657AE1-056 GEN
Solar/Wind Harmer
16.55
946301AF1-294 GEN
Solar/Wind Harmer
8.963
961791AG1-021 GEN
Solar/Wind Harmer
4.361
970683AG2-441 GEN
Solar/Wind Harmer
27.831
970681AG2-440 GEN
Solar/Wind Harmer
22.264
3144303KENBRDG
Solar/Wind Harmer
0.302
971443AH1-215 GEN
Solar/Wind Harmer
6.301
971967AH1-528 GEN
Solar/Wind Harmer
55.401
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.601
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.066
970831AG2-522 GEN
Solar/Wind Harmer
7.435
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.134
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.367
315607AA1-063A GEN
Solar/Wind Harmer
0.158
3146043SEABORD
Solar/Wind Harmer
0.075
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.249
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.44
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.251
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.952
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.158
3151411GASTONB
50/50
0.158
972003AH1-546 GEN
Solar/Wind Harmer
37.761
316322AB2-045
Solar/Wind Harmer
0.006
3146776BUCKING
Solar/Wind Harmer
0.305
3146926FARMVIL
Solar/Wind Harmer
0.38
963171AG1-166 GEN
Solar/Wind Harmer
2.423
971563AH1-280 GEN
Solar/Wind Harmer
4.845
970685AG2-442 GEN
Solar/Wind Harmer
31.17
962491AG1-098 GEN
Solar/Wind Harmer
21.62
315693AD1-088 GEN
Solar/Wind Harmer
17.81
957481AF2-042 GEN
Solar/Wind Harmer
90.702
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.457
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.163
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
8.991
960081AF2-299 GEN
Solar/Wind Harmer
0.901
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.348
3146233WITAKRS
Solar/Wind Harmer
0.26
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
316359AB2-059 GEN
Solar/Wind Harmer
0.225
316049AB1-081 GEN
Solar/Wind Harmer
0.359
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.061
315722AD1-056 GEN
Solar/Wind Harmer
0.381
3145796HORNRTN
Solar/Wind Harmer
0.194
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.064
962571AG1-106 GEN
Solar/Wind Harmer
0.833
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.252
970223AG2-152 GEN
Solar/Wind Harmer
3.983
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.042
941801AE2-185 GEN
Solar/Wind Harmer
1.811
3145823KELFORD
Solar/Wind Harmer
0.056
316336AC2-165 C
Solar/Wind Helper
1.31
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.158
3151411GASTONB
50/50
0.158
3146776BUCKING
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Harmer
0.38
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.219
963181AG1-167 GEN
Solar/Wind Harmer
1.817
959311AF2-222 GEN
Solar/Wind Harmer
34.634
970257AG2-171 GEN
Solar/Wind Harmer
12.109
315785AD2-033 C
Solar/Wind Harmer
2.951
964241AG1-285 GEN
Solar/Wind Harmer
21.461
316478AD1-087 GEN
Solar/Wind Harmer
1.114
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.934
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.29
971683AH1-343 GEN
Solar/Wind Harmer
6.951
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.286
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.624
3146233WITAKRS
Solar/Wind Harmer
0.328
3146233WITAKRS
Solar/Wind Harmer
0.044
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.061
961601AG1-000A GEN
Solar/Wind Harmer
4.335
315724AD1-057 GEN
Solar/Wind Harmer
0.226
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.811
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.212
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.099
3146776BUCKING
Solar/Wind Harmer
3.045
3146776BUCKING
Solar/Wind Harmer
0.247
970301AG2-198 GEN
Solar/Wind Harmer
22.286
971741AH1-377 GEN
Solar/Wind Harmer
48.371
3147133PAMPLIN
Solar/Wind Harmer
0.479
3147133PAMPLIN
Solar/Wind Harmer
0.383
958211AF2-115 GEN
Solar/Wind Harmer
5.451
963191AG1-168 GEN
Solar/Wind Harmer
1.817
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.146
971775AH1-396 GEN
Solar/Wind Harmer
0.605
970933AG2-581 GEN
Solar/Wind Harmer
27.701
970099AG2-077 GEN
Solar/Wind Harmer
36.281
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.234
964791AG1-342 GEN
Solar/Wind Harmer
4.769
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.655
942751AE2-291 GEN
Solar/Wind Harmer
7.004
316222AC1-221 GEN
Solar/Wind Harmer
0.516
316181AB2-040 GEN
Solar/Wind Harmer
0.134
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.99
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.571
3145783HORNRTN
Solar/Wind Harmer
1.257
3145783HORNRTN
Solar/Wind Harmer
0.393
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.283
316274AC1-208 GEN
Solar/Wind Harmer
0.379
316263AC1-034 GEN
Solar/Wind Harmer
2.385
961601AG1-000A GEN
Solar/Wind Harmer
1.084
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.131
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.409
315821AE2-092 GEN
Solar/Wind Helper
2.531
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:211.19 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:1206.97
MW Contribution:29.89
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.952
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.158
3151411GASTONB
50/50
0.158
972003AH1-546 GEN
Solar/Wind Harmer
37.761
316322AB2-045
Solar/Wind Harmer
0.006
3146776BUCKING
Solar/Wind Harmer
0.305
3146926FARMVIL
Solar/Wind Harmer
0.38
963171AG1-166 GEN
Solar/Wind Harmer
2.423
971563AH1-280 GEN
Solar/Wind Harmer
4.845
970685AG2-442 GEN
Solar/Wind Harmer
31.17
962491AG1-098 GEN
Solar/Wind Harmer
21.62
315693AD1-088 GEN
Solar/Wind Harmer
17.81
957481AF2-042 GEN
Solar/Wind Harmer
90.702
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.457
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.163
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
8.991
960081AF2-299 GEN
Solar/Wind Harmer
0.901
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.348
3146233WITAKRS
Solar/Wind Harmer
0.26
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
316359AB2-059 GEN
Solar/Wind Harmer
0.225
316049AB1-081 GEN
Solar/Wind Harmer
0.359
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.061
315722AD1-056 GEN
Solar/Wind Harmer
0.381
3145796HORNRTN
Solar/Wind Harmer
0.194
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.064
962571AG1-106 GEN
Solar/Wind Harmer
0.833
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.252
970223AG2-152 GEN
Solar/Wind Harmer
3.983
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.042
941801AE2-185 GEN
Solar/Wind Harmer
1.811
3145823KELFORD
Solar/Wind Harmer
0.056
316336AC2-165 C
Solar/Wind Helper
1.31
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.103
971845AH1-439 GEN
Solar/Wind Harmer
34.045
970285AG2-188 GEN
Solar/Wind Harmer
57.782
315657AE1-056 GEN
Solar/Wind Harmer
16.55
946301AF1-294 GEN
Solar/Wind Harmer
8.963
961791AG1-021 GEN
Solar/Wind Harmer
4.361
970683AG2-441 GEN
Solar/Wind Harmer
27.831
970681AG2-440 GEN
Solar/Wind Harmer
22.264
3144303KENBRDG
Solar/Wind Harmer
0.302
971443AH1-215 GEN
Solar/Wind Harmer
6.301
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.601
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.066
970831AG2-522 GEN
Solar/Wind Harmer
7.435
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.134
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.367
315607AA1-063A GEN
Solar/Wind Harmer
0.158
3146043SEABORD
Solar/Wind Harmer
0.075
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.249
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.44
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.251
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.158
3151411GASTONB
50/50
0.158
3146776BUCKING
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Harmer
0.38
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.219
963181AG1-167 GEN
Solar/Wind Harmer
1.817
959311AF2-222 GEN
Solar/Wind Harmer
34.634
970257AG2-171 GEN
Solar/Wind Harmer
12.109
315785AD2-033 C
Solar/Wind Harmer
2.951
964241AG1-285 GEN
Solar/Wind Harmer
21.461
316478AD1-087 GEN
Solar/Wind Harmer
1.114
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.934
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.29
971683AH1-343 GEN
Solar/Wind Harmer
6.951
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.286
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.624
3146233WITAKRS
Solar/Wind Harmer
0.328
3146233WITAKRS
Solar/Wind Harmer
0.044
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.061
961601AG1-000A GEN
Solar/Wind Harmer
4.335
315724AD1-057 GEN
Solar/Wind Harmer
0.226
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.811
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.212
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.099
3146776BUCKING
Solar/Wind Harmer
3.045
3146776BUCKING
Solar/Wind Harmer
0.247
970301AG2-198 GEN
Solar/Wind Harmer
22.286
971741AH1-377 GEN
Solar/Wind Harmer
48.371
3147133PAMPLIN
Solar/Wind Harmer
0.479
3147133PAMPLIN
Solar/Wind Harmer
0.383
958211AF2-115 GEN
Solar/Wind Harmer
5.451
963191AG1-168 GEN
Solar/Wind Harmer
1.817
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.146
971775AH1-396 GEN
Solar/Wind Harmer
0.605
970099AG2-077 GEN
Solar/Wind Harmer
36.281
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.234
964791AG1-342 GEN
Solar/Wind Harmer
4.769
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.655
942751AE2-291 GEN
Solar/Wind Harmer
7.004
316222AC1-221 GEN
Solar/Wind Harmer
0.516
316181AB2-040 GEN
Solar/Wind Harmer
0.134
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.99
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.571
3145783HORNRTN
Solar/Wind Harmer
1.257
3145783HORNRTN
Solar/Wind Harmer
0.393
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.283
316274AC1-208 GEN
Solar/Wind Harmer
0.379
316263AC1-034 GEN
Solar/Wind Harmer
2.385
961601AG1-000A GEN
Solar/Wind Harmer
1.084
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.131
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.409
315821AE2-092 GEN
Solar/Wind Helper
2.531
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:210.43 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1470.9
MW Contribution:29.89
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
972003AH1-546 GEN
Solar/Wind Harmer
49.802
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.379
971563AH1-280 GEN
Solar/Wind Harmer
6.379
970685AG2-442 GEN
Solar/Wind Harmer
41.041
962491AG1-098 GEN
Solar/Wind Harmer
28.467
315693AD1-088 GEN
Solar/Wind Harmer
20.844
957481AF2-042 GEN
Solar/Wind Harmer
119.424
316237AB2-079_GEN
Solar/Wind Harmer
0.967
315687AD1-152 GEN
Solar/Wind Harmer
3.708
970401AG2-262 GEN
Solar/Wind Harmer
1.822
316003AC1-222 GEN
Solar/Wind Harmer
2.219
971065AG2-659 GEN
Solar/Wind Harmer
10.747
316129AC1-054 GEN
Solar/Wind Harmer
1.803
971795AH1-408 GEN
Solar/Wind Harmer
11.364
960081AF2-299 GEN
Solar/Wind Harmer
1.186
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.658
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.951
316049AB1-081 GEN
Solar/Wind Harmer
0.761
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.707
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
970223AG2-152 GEN
Solar/Wind Harmer
5.68
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.385
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.31
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.826
970285AG2-188 GEN
Solar/Wind Harmer
71.806
315657AE1-056 GEN
Solar/Wind Harmer
20.219
946301AF1-294 GEN
Solar/Wind Harmer
13.078
961791AG1-021 GEN
Solar/Wind Harmer
6.379
970683AG2-441 GEN
Solar/Wind Harmer
36.643
970681AG2-440 GEN
Solar/Wind Harmer
29.315
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.296
316239AB2-077_GEN
Solar/Wind Harmer
0.967
316238AB2-078_GEN
Solar/Wind Harmer
0.967
316118AC1-105 GEN
Solar/Wind Harmer
1.799
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.987
970831AG2-522 GEN
Solar/Wind Harmer
9.789
316123AC1-075 GEN
Solar/Wind Harmer
1.778
970165AG2-112 GEN
Solar/Wind Harmer
1.566
970163AG2-111 GEN
Solar/Wind Harmer
1.494
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.49
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.605
270457AD2-023 GEN
Solar/Wind Harmer
0.814
315607AA1-063A GEN
Solar/Wind Harmer
0.881
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.406
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.564
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.331
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
-0.168
971193AH1-056 GEN
Solar/Wind Harmer
33.698
963181AG1-167 GEN
Solar/Wind Harmer
4.785
959311AF2-222 GEN
Solar/Wind Harmer
45.693
970257AG2-171 GEN
Solar/Wind Harmer
15.944
315785AD2-033 C
Solar/Wind Harmer
9.243
964241AG1-285 GEN
Solar/Wind Harmer
28.257
316478AD1-087 GEN
Solar/Wind Harmer
3.106
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.6
316248AF1-058 C
Solar/Wind Harmer
0.737
960061AF2-297 GEN
Solar/Wind Harmer
12.232
971683AH1-343 GEN
Solar/Wind Harmer
9.152
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.287
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.767
316210AC1-098 GEN
Solar/Wind Harmer
1.185
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.727
315724AD1-057 GEN
Solar/Wind Harmer
0.389
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.385
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.343
971741AH1-377 GEN
Solar/Wind Harmer
63.689
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.974
963191AG1-168 GEN
Solar/Wind Harmer
4.785
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.258
971775AH1-396 GEN
Solar/Wind Harmer
3.027
970099AG2-077 GEN
Solar/Wind Harmer
47.77
313527AB2-043 GEN
Solar/Wind Harmer
5.31
962561AG1-105 GEN
Solar/Wind Harmer
16.108
964791AG1-342 GEN
Solar/Wind Harmer
5.961
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.346
942751AE2-291 GEN
Solar/Wind Harmer
9.222
316222AC1-221 GEN
Solar/Wind Harmer
1.414
316181AB2-040 GEN
Solar/Wind Harmer
1.452
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.154
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.178
3145783HORNRTN
Solar/Wind Harmer
0.943
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.884
316263AC1-034 GEN
Solar/Wind Harmer
3.306
961601AG1-000A GEN
Solar/Wind Harmer
2.693
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
316217AC1-145 GEN
Solar/Wind Harmer
1.032
316197AC1-042 GEN
Solar/Wind Harmer
0.782
942671AE2-283 GEN
Solar/Wind Harmer
2.107
315821AE2-092 GEN
Solar/Wind Helper
2.531
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:210.43 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1470.9
MW Contribution:29.89
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.826
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
972003AH1-546 GEN
Solar/Wind Harmer
49.802
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.379
971563AH1-280 GEN
Solar/Wind Harmer
6.379
970685AG2-442 GEN
Solar/Wind Harmer
41.041
962491AG1-098 GEN
Solar/Wind Harmer
28.467
315693AD1-088 GEN
Solar/Wind Harmer
20.844
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.331
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
-0.168
971193AH1-056 GEN
Solar/Wind Harmer
33.698
963181AG1-167 GEN
Solar/Wind Harmer
4.785
959311AF2-222 GEN
Solar/Wind Harmer
45.693
970257AG2-171 GEN
Solar/Wind Harmer
15.944
315785AD2-033 C
Solar/Wind Harmer
9.243
964241AG1-285 GEN
Solar/Wind Harmer
28.257
316478AD1-087 GEN
Solar/Wind Harmer
3.106
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.6
316248AF1-058 C
Solar/Wind Harmer
0.737
960061AF2-297 GEN
Solar/Wind Harmer
12.232
971683AH1-343 GEN
Solar/Wind Harmer
9.152
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.287
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.767
316210AC1-098 GEN
Solar/Wind Harmer
1.185
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.727
315724AD1-057 GEN
Solar/Wind Harmer
0.389
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.385
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
970285AG2-188 GEN
Solar/Wind Harmer
71.806
315657AE1-056 GEN
Solar/Wind Harmer
20.219
946301AF1-294 GEN
Solar/Wind Harmer
13.078
961791AG1-021 GEN
Solar/Wind Harmer
6.379
970683AG2-441 GEN
Solar/Wind Harmer
36.643
970681AG2-440 GEN
Solar/Wind Harmer
29.315
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.296
316239AB2-077_GEN
Solar/Wind Harmer
0.967
316238AB2-078_GEN
Solar/Wind Harmer
0.967
316118AC1-105 GEN
Solar/Wind Harmer
1.799
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.987
970831AG2-522 GEN
Solar/Wind Harmer
9.789
316123AC1-075 GEN
Solar/Wind Harmer
1.778
970165AG2-112 GEN
Solar/Wind Harmer
1.566
970163AG2-111 GEN
Solar/Wind Harmer
1.494
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.49
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.605
270457AD2-023 GEN
Solar/Wind Harmer
0.814
315607AA1-063A GEN
Solar/Wind Harmer
0.881
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.406
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.564
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
957481AF2-042 GEN
Solar/Wind Harmer
119.424
316237AB2-079_GEN
Solar/Wind Harmer
0.967
315687AD1-152 GEN
Solar/Wind Harmer
3.708
970401AG2-262 GEN
Solar/Wind Harmer
1.822
316003AC1-222 GEN
Solar/Wind Harmer
2.219
971065AG2-659 GEN
Solar/Wind Harmer
10.747
316129AC1-054 GEN
Solar/Wind Harmer
1.803
971795AH1-408 GEN
Solar/Wind Harmer
11.364
960081AF2-299 GEN
Solar/Wind Harmer
1.186
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.658
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.951
316049AB1-081 GEN
Solar/Wind Harmer
0.761
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.707
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
970223AG2-152 GEN
Solar/Wind Harmer
5.68
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.385
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.31
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.343
971741AH1-377 GEN
Solar/Wind Harmer
63.689
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.974
963191AG1-168 GEN
Solar/Wind Harmer
4.785
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.258
971775AH1-396 GEN
Solar/Wind Harmer
3.027
970099AG2-077 GEN
Solar/Wind Harmer
47.77
313527AB2-043 GEN
Solar/Wind Harmer
5.31
962561AG1-105 GEN
Solar/Wind Harmer
16.108
964791AG1-342 GEN
Solar/Wind Harmer
5.961
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.346
942751AE2-291 GEN
Solar/Wind Harmer
9.222
316222AC1-221 GEN
Solar/Wind Harmer
1.414
316181AB2-040 GEN
Solar/Wind Harmer
1.452
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.154
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.178
3145783HORNRTN
Solar/Wind Harmer
0.943
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.884
316263AC1-034 GEN
Solar/Wind Harmer
3.306
961601AG1-000A GEN
Solar/Wind Harmer
2.693
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
316217AC1-145 GEN
Solar/Wind Harmer
1.032
316197AC1-042 GEN
Solar/Wind Harmer
0.782
942671AE2-283 GEN
Solar/Wind Harmer
2.107
315821AE2-092 GEN
Solar/Wind Helper
2.531
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:137.05 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:957.97
MW Contribution:12.88
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.288
3151621KERR 5
50/50
0.288
3151631KERR 6
50/50
0.288
3151641KERR 7
50/50
0.288
3151541CLOVER2
50/50
2.937
971845AH1-439 GEN
Solar/Wind Harmer
40.264
970285AG2-188 GEN
Solar/Wind Harmer
63.811
315657AE1-056 GEN
Solar/Wind Harmer
15.96
946301AF1-294 GEN
Solar/Wind Harmer
10.183
961791AG1-021 GEN
Solar/Wind Harmer
4.967
970683AG2-441 GEN
Solar/Wind Harmer
27.881
970681AG2-440 GEN
Solar/Wind Harmer
22.305
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.107
316239AB2-077_GEN
Solar/Wind Harmer
0.638
316238AB2-078_GEN
Solar/Wind Harmer
0.638
316118AC1-105 GEN
Solar/Wind Harmer
1.013
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.344
970865AG2-541 GEN
Solar/Wind Harmer
4.105
946281AF1-292 GEN
Solar/Wind Harmer
0.203
316087AB2-174 GEN
Solar/Wind Harmer
1.262
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.891
970165AG2-112 GEN
Solar/Wind Harmer
0.785
970163AG2-111 GEN
Solar/Wind Harmer
0.749
971967AH1-528 GEN
Solar/Wind Harmer
15.159
315607AA1-063A GEN
Solar/Wind Harmer
0.776
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.313
970581AG2-369 GEN
Solar/Wind Harmer
3.709
316319Z2-044 C
Solar/Wind Harmer
0.377
3146033SCOT NK
Solar/Wind Harmer
-0.027
315652AC1-086 GEN
Solar/Wind Harmer
7.536
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
965291AG1-394 GEN
Solar/Wind Harmer
0.58
970673AG2-436 GEN
Solar/Wind Harmer
13.57
970673AG2-436 GEN
Solar/Wind Harmer
6.871
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
270494AE1-108_GEN
Solar/Wind Helper
4.47
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.195
3151591KERR 2
50/50
0.288
970413AG2-270 GEN
50/50
12.878
3146776BUCKING
Solar/Wind Harmer
-0.028
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.6
970909AG2-566 GEN
Solar/Wind Harmer
4.079
3147133PAMPLIN
Solar/Wind Harmer
-0.133
971193AH1-056 GEN
Solar/Wind Harmer
26.601
963181AG1-167 GEN
Solar/Wind Harmer
3.725
959311AF2-222 GEN
Solar/Wind Harmer
34.052
970257AG2-171 GEN
Solar/Wind Harmer
11.771
315785AD2-033 C
Solar/Wind Harmer
6.728
964241AG1-285 GEN
Solar/Wind Harmer
19.662
316131AB2-060 GEN
Solar/Wind Harmer
2.419
316478AD1-087 GEN
Solar/Wind Harmer
1.34
316486AD2-202 GEN
Solar/Wind Harmer
0.392
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.389
960061AF2-297 GEN
Solar/Wind Harmer
6.446
971683AH1-343 GEN
Solar/Wind Harmer
4.749
966621AG1-532 GEN
Solar/Wind Harmer
0.184
313506AB2-031 GEN
Solar/Wind Harmer
0.704
316283AC2-100 C
Solar/Wind Harmer
0.785
316210AC1-098 GEN
Solar/Wind Harmer
1.101
316327AA2-057 GEN
Solar/Wind Harmer
0.705
970917AG2-570 GEN
Solar/Wind Harmer
17.269
3146233WITAKRS
Solar/Wind Harmer
0.143
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.004
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.38
316365GEN2_N
Solar/Wind Harmer
0.442
961601AG1-000A GEN
Solar/Wind Harmer
2.606
316317KELFORD C
Solar/Wind Harmer
0.305
3145823KELFORD
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.082
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
957521AF2-046 GEN
Solar/Wind Harmer
5.021
961681AG1-008 GEN
Solar/Wind Harmer
5.021
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.333
316258AE1-075 C
Solar/Wind Helper
0.299
316405AF2-144 C
Solar/Wind Helper
0.249
3148013FISHERV
Solar/Wind Helper
0.124
3144293JTRSVLE
50/50
1.195
3144293JTRSVLE
50/50
1.006
970535AG2-341 GEN
50/50
2.93
3152661PLYWOOD A
50/50
0.279
3146776BUCKING
Solar/Wind Harmer
-0.308
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.483
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.209
963191AG1-168 GEN
Solar/Wind Harmer
3.725
971741AH1-377 GEN
Solar/Wind Harmer
43.964
316034AC1-036 C
Solar/Wind Harmer
0.583
970323AG2-213 GEN
Solar/Wind Harmer
15.694
971775AH1-396 GEN
Solar/Wind Harmer
2.235
313527AB2-043 GEN
Solar/Wind Harmer
3.534
962561AG1-105 GEN
Solar/Wind Harmer
9.782
939181AE1-148 GEN
Solar/Wind Harmer
9.427
964791AG1-342 GEN
Solar/Wind Harmer
3.547
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
970099AG2-077 GEN
Solar/Wind Harmer
18.781
970933AG2-581 GEN
Solar/Wind Harmer
9.57
316181AB2-040 GEN
Solar/Wind Harmer
1.222
316222AC1-221 GEN
Solar/Wind Harmer
0.854
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.948
3145593CAROLNA
Solar/Wind Harmer
0.07
3145783HORNRTN
Solar/Wind Harmer
0.979
3145783HORNRTN
Solar/Wind Harmer
0.783
3145783HORNRTN
Solar/Wind Harmer
0.245
3145783HORNRTN
Solar/Wind Harmer
0.098
316426AA2-053 GEN
Solar/Wind Harmer
0.81
316274AC1-208 GEN
Solar/Wind Harmer
0.791
942751AE2-291 GEN
Solar/Wind Harmer
4.521
972187AH1-678 GEN
Adder
1.767
972185AH1-677 GEN
Adder
3.338
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
316263AC1-034 GEN
Solar/Wind Harmer
3.115
961601AG1-000A GEN
Solar/Wind Harmer
2.573
3145893MURPHYS
Solar/Wind Harmer
0.179
3145893MURPHYS
Solar/Wind Harmer
-0.012
3145493TOT1
Solar/Wind Harmer
0.098
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
315821AE2-092 GEN
Solar/Wind Helper
2.966
3144293JTRSVLE
50/50
1.195
3151601KERR 3
50/50
0.288
3151581KERR 1
50/50
0.103
3151531CLOVER1
50/50
2.951
3147043LAWRENC
50/50
1.104
972003AH1-546 GEN
Solar/Wind Harmer
47.347
316322AB2-045
Solar/Wind Harmer
2.6
3146776BUCKING
Solar/Wind Harmer
-0.031
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.967
971563AH1-280 GEN
Solar/Wind Harmer
4.967
970685AG2-442 GEN
Solar/Wind Harmer
31.227
962491AG1-098 GEN
Solar/Wind Harmer
14.504
316237AB2-079_GEN
Solar/Wind Harmer
0.638
315693AD1-088 GEN
Solar/Wind Harmer
10.264
970401AG2-262 GEN
Solar/Wind Harmer
1.084
957481AF2-042 GEN
Solar/Wind Harmer
46.952
315687AD1-152 GEN
Solar/Wind Harmer
1.686
971065AG2-659 GEN
Solar/Wind Harmer
6.782
316129AC1-054 GEN
Solar/Wind Harmer
1.152
316003AC1-222 GEN
Solar/Wind Harmer
1.16
971795AH1-408 GEN
Solar/Wind Harmer
8.774
960081AF2-299 GEN
Solar/Wind Harmer
1.019
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
316212AC1-099_GEN
Solar/Wind Harmer
0.612
970919AG2-571 GEN
Solar/Wind Harmer
2.186
970087AG2-069 GEN
Solar/Wind Harmer
6.469
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.401
962571AG1-106 GEN
Solar/Wind Harmer
0.963
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316359AB2-059 GEN
Solar/Wind Harmer
0.896
316049AB1-081 GEN
Solar/Wind Harmer
0.717
3142053HEARTS
Solar/Wind Harmer
0.078
315722AD1-056 GEN
Solar/Wind Harmer
0.692
316023GEN1_S
Solar/Wind Harmer
0.442
3145823KELFORD
Solar/Wind Harmer
-0.006
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.19
961671AG1-007 GEN
Solar/Wind Harmer
0.08
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.188
316336AC2-165 C
Solar/Wind Helper
1.427
CPLELTFEXP_CPLE->PJM
CLTF
4.525
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.338
LAGNLTFEXP_LAGN->PJM
CLTF
2.472
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.204
TVALTFEXP_TVA->PJM
CLTF
1.2
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.871
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.899
MECLTFEXP_MEC->PJM
CLTF
0.811
SIGELTFEXP_SIGE->PJM
CLTF
0.021
NYPJM->LTFIMP_NY
CLTF
0.305
LGEELTFEXP_LGEE->PJM
CLTF
0.208
WECLTFEXP_WEC->PJM
CLTF
0.117

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2106-2111_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2106-2111_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:136.87 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:956.69
MW Contribution:12.39
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.277
3151621KERR 5
50/50
0.277
3151631KERR 6
50/50
0.277
3151641KERR 7
50/50
0.277
3151541CLOVER2
50/50
2.825
971845AH1-439 GEN
Solar/Wind Harmer
40.074
970285AG2-188 GEN
Solar/Wind Harmer
63.49
315657AE1-056 GEN
Solar/Wind Harmer
15.775
946301AF1-294 GEN
Solar/Wind Harmer
10.053
961791AG1-021 GEN
Solar/Wind Harmer
4.904
970683AG2-441 GEN
Solar/Wind Harmer
27.471
970681AG2-440 GEN
Solar/Wind Harmer
21.977
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
5.999
316239AB2-077_GEN
Solar/Wind Harmer
0.62
316238AB2-078_GEN
Solar/Wind Harmer
0.62
316118AC1-105 GEN
Solar/Wind Harmer
0.971
3147173SINAI
Solar/Wind Harmer
-0.012
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.022
970865AG2-541 GEN
Solar/Wind Harmer
3.914
946281AF1-292 GEN
Solar/Wind Harmer
0.189
316087AB2-174 GEN
Solar/Wind Harmer
1.174
3137643SOCKMAN
Solar/Wind Harmer
-0.032
316123AC1-075 GEN
Solar/Wind Harmer
0.851
970165AG2-112 GEN
Solar/Wind Harmer
0.749
970163AG2-111 GEN
Solar/Wind Harmer
0.714
971967AH1-528 GEN
Solar/Wind Harmer
14.144
315607AA1-063A GEN
Solar/Wind Harmer
0.713
3146043SEABORD
Solar/Wind Harmer
-0.007
270494AE1-108_GEN
Solar/Wind Helper
4.505
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3144293JTRSVLE
50/50
1.179
3151601KERR 3
50/50
0.277
3151581KERR 1
50/50
0.099
3151531CLOVER1
50/50
2.838
972003AH1-546 GEN
Solar/Wind Harmer
47.205
316322AB2-045
Solar/Wind Harmer
2.588
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.904
971563AH1-280 GEN
Solar/Wind Harmer
4.904
970685AG2-442 GEN
Solar/Wind Harmer
30.768
962491AG1-098 GEN
Solar/Wind Harmer
14.136
316237AB2-079_GEN
Solar/Wind Harmer
0.62
315693AD1-088 GEN
Solar/Wind Harmer
9.987
970401AG2-262 GEN
Solar/Wind Harmer
1.044
957481AF2-042 GEN
Solar/Wind Harmer
45.172
315687AD1-152 GEN
Solar/Wind Harmer
1.609
971065AG2-659 GEN
Solar/Wind Harmer
6.46
316129AC1-054 GEN
Solar/Wind Harmer
1.096
3147043LAWRENC
Adder
0.992
316003AC1-222 GEN
Solar/Wind Harmer
1.105
971795AH1-408 GEN
Solar/Wind Harmer
8.324
960081AF2-299 GEN
Solar/Wind Harmer
0.951
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.091
316336AC2-165 C
Solar/Wind Helper
1.456
3144293JTRSVLE
50/50
1.179
3144293JTRSVLE
50/50
0.993
970535AG2-341 GEN
50/50
2.832
3152661PLYWOOD A
50/50
0.267
3146776BUCKING
Solar/Wind Harmer
-0.306
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.246
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.13
963191AG1-168 GEN
Solar/Wind Harmer
3.678
971741AH1-377 GEN
Solar/Wind Harmer
43.39
316034AC1-036 C
Solar/Wind Harmer
0.573
970323AG2-213 GEN
Solar/Wind Harmer
15.422
971775AH1-396 GEN
Solar/Wind Harmer
2.196
313527AB2-043 GEN
Solar/Wind Harmer
3.438
962561AG1-105 GEN
Solar/Wind Harmer
9.444
939181AE1-148 GEN
Solar/Wind Harmer
9.07
964791AG1-342 GEN
Solar/Wind Harmer
3.418
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.069
970933AG2-581 GEN
Solar/Wind Harmer
9.057
316181AB2-040 GEN
Solar/Wind Harmer
1.135
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.876
3145593CAROLNA
Solar/Wind Harmer
0.065
3145783HORNRTN
Solar/Wind Harmer
0.902
3145783HORNRTN
Solar/Wind Harmer
0.721
3145783HORNRTN
Solar/Wind Harmer
0.225
3145783HORNRTN
Solar/Wind Harmer
0.09
316222AC1-221 GEN
Solar/Wind Harmer
0.766
316426AA2-053 GEN
Solar/Wind Harmer
0.746
942751AE2-291 GEN
Solar/Wind Harmer
4.318
316274AC1-208 GEN
Solar/Wind Harmer
0.714
972187AH1-678 GEN
Adder
1.624
315821AE2-092 GEN
Solar/Wind Helper
2.997
3144293JTRSVLE
50/50
1.179
3151591KERR 2
50/50
0.277
970413AG2-270 GEN
50/50
12.386
3146776BUCKING
Solar/Wind Harmer
-0.027
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.532
970909AG2-566 GEN
Solar/Wind Harmer
4.034
3147133PAMPLIN
Solar/Wind Harmer
-0.131
971193AH1-056 GEN
Solar/Wind Harmer
26.292
963181AG1-167 GEN
Solar/Wind Harmer
3.678
959311AF2-222 GEN
Solar/Wind Harmer
33.489
970257AG2-171 GEN
Solar/Wind Harmer
11.567
315785AD2-033 C
Solar/Wind Harmer
6.603
964241AG1-285 GEN
Solar/Wind Harmer
19.215
316131AB2-060 GEN
Solar/Wind Harmer
2.356
316478AD1-087 GEN
Solar/Wind Harmer
1.288
316486AD2-202 GEN
Solar/Wind Harmer
0.377
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.37
960061AF2-297 GEN
Solar/Wind Harmer
6.139
971683AH1-343 GEN
Solar/Wind Harmer
4.525
966621AG1-532 GEN
Solar/Wind Harmer
0.171
313506AB2-031 GEN
Solar/Wind Harmer
0.654
316283AC2-100 C
Solar/Wind Harmer
0.703
316313AB2-026
Solar/Wind Helper
0.341
316258AE1-075 C
Solar/Wind Helper
0.307
316405AF2-144 C
Solar/Wind Helper
0.256
3148013FISHERV
Solar/Wind Helper
0.125
CPLELTFEXP_CPLE->PJM
CLTF
3.699
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.437
LAGNLTFEXP_LAGN->PJM
CLTF
1.81
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.409
TVALTFEXP_TVA->PJM
CLTF
0.888
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.959
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.906
MECLTFEXP_MEC->PJM
CLTF
0.618
SIGELTFEXP_SIGE->PJM
CLTF
0.017
NYPJM->LTFIMP_NY
CLTF
0.351
LGEELTFEXP_LGEE->PJM
CLTF
0.175
WECLTFEXP_WEC->PJM
CLTF
0.091

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2003-205_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2003-205_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:133.52 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:933.31
MW Contribution:12.71
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.284
3151621KERR 5
50/50
0.284
3151631KERR 6
50/50
0.284
3151641KERR 7
50/50
0.284
3151541CLOVER2
50/50
2.899
971845AH1-439 GEN
Solar/Wind Harmer
40.166
970285AG2-188 GEN
Solar/Wind Harmer
63.65
315657AE1-056 GEN
Solar/Wind Harmer
15.889
946301AF1-294 GEN
Solar/Wind Harmer
10.133
961791AG1-021 GEN
Solar/Wind Harmer
4.943
970683AG2-441 GEN
Solar/Wind Harmer
27.73
970681AG2-440 GEN
Solar/Wind Harmer
22.184
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.068
316239AB2-077_GEN
Solar/Wind Harmer
0.632
316238AB2-078_GEN
Solar/Wind Harmer
0.632
316118AC1-105 GEN
Solar/Wind Harmer
0.995
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.242
970865AG2-541 GEN
Solar/Wind Harmer
4.039
946281AF1-292 GEN
Solar/Wind Harmer
0.204
316087AB2-174 GEN
Solar/Wind Harmer
1.259
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.881
970165AG2-112 GEN
Solar/Wind Harmer
0.776
970163AG2-111 GEN
Solar/Wind Harmer
0.74
971967AH1-528 GEN
Solar/Wind Harmer
14.996
315607AA1-063A GEN
Solar/Wind Harmer
0.76
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.198
970581AG2-369 GEN
Solar/Wind Harmer
3.61
315652AC1-086 GEN
Solar/Wind Harmer
7.443
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.026
316319Z2-044 C
Solar/Wind Harmer
0.358
970673AG2-436 GEN
Solar/Wind Harmer
13.401
970673AG2-436 GEN
Solar/Wind Harmer
6.785
965291AG1-394 GEN
Solar/Wind Harmer
0.563
270494AE1-108_GEN
Solar/Wind Helper
4.481
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3144293JTRSVLE
50/50
1.189
3151601KERR 3
50/50
0.284
3151581KERR 1
50/50
0.101
3151531CLOVER1
50/50
2.913
3147043LAWRENC
50/50
1.1
972003AH1-546 GEN
Solar/Wind Harmer
47.254
316322AB2-045
Solar/Wind Harmer
2.593
3146776BUCKING
Solar/Wind Harmer
-0.031
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.943
971563AH1-280 GEN
Solar/Wind Harmer
4.943
970685AG2-442 GEN
Solar/Wind Harmer
31.058
962491AG1-098 GEN
Solar/Wind Harmer
14.389
316237AB2-079_GEN
Solar/Wind Harmer
0.632
315693AD1-088 GEN
Solar/Wind Harmer
10.178
970401AG2-262 GEN
Solar/Wind Harmer
1.068
957481AF2-042 GEN
Solar/Wind Harmer
46.433
315687AD1-152 GEN
Solar/Wind Harmer
1.654
971065AG2-659 GEN
Solar/Wind Harmer
6.674
316129AC1-054 GEN
Solar/Wind Harmer
1.134
971795AH1-408 GEN
Solar/Wind Harmer
8.763
316003AC1-222 GEN
Solar/Wind Harmer
1.138
960081AF2-299 GEN
Solar/Wind Harmer
1.022
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.097
316212AC1-099_GEN
Solar/Wind Harmer
0.589
970919AG2-571 GEN
Solar/Wind Harmer
2.13
970087AG2-069 GEN
Solar/Wind Harmer
6.297
316023GEN1_S
Solar/Wind Harmer
0.451
316011AB1-132 GEN
Solar/Wind Harmer
1.384
962571AG1-106 GEN
Solar/Wind Harmer
0.951
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
-0.026
315722AD1-056 GEN
Solar/Wind Harmer
0.665
316336AC2-165 C
Solar/Wind Helper
1.458
3144293JTRSVLE
50/50
1.189
3144293JTRSVLE
50/50
1.001
970535AG2-341 GEN
50/50
2.895
3152661PLYWOOD A
50/50
0.274
3146776BUCKING
Solar/Wind Harmer
-0.307
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.395
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.179
963191AG1-168 GEN
Solar/Wind Harmer
3.707
971741AH1-377 GEN
Solar/Wind Harmer
43.759
316034AC1-036 C
Solar/Wind Harmer
0.58
970323AG2-213 GEN
Solar/Wind Harmer
15.596
971775AH1-396 GEN
Solar/Wind Harmer
2.221
313527AB2-043 GEN
Solar/Wind Harmer
3.501
962561AG1-105 GEN
Solar/Wind Harmer
9.651
939181AE1-148 GEN
Solar/Wind Harmer
9.294
964791AG1-342 GEN
Solar/Wind Harmer
3.496
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.573
970933AG2-581 GEN
Solar/Wind Harmer
9.469
316181AB2-040 GEN
Solar/Wind Harmer
1.215
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.932
3145593CAROLNA
Solar/Wind Harmer
0.069
3145783HORNRTN
Solar/Wind Harmer
0.96
3145783HORNRTN
Solar/Wind Harmer
0.768
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
316222AC1-221 GEN
Solar/Wind Harmer
0.8
316426AA2-053 GEN
Solar/Wind Harmer
0.794
316274AC1-208 GEN
Solar/Wind Harmer
0.763
942751AE2-291 GEN
Solar/Wind Harmer
4.488
972187AH1-678 GEN
Adder
1.739
972185AH1-677 GEN
Adder
3.291
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
315821AE2-092 GEN
Solar/Wind Helper
2.986
3144293JTRSVLE
50/50
1.189
3151591KERR 2
50/50
0.284
970413AG2-270 GEN
50/50
12.71
3146776BUCKING
Solar/Wind Harmer
-0.027
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.572
970909AG2-566 GEN
Solar/Wind Harmer
4.062
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.482
963181AG1-167 GEN
Solar/Wind Harmer
3.707
959311AF2-222 GEN
Solar/Wind Harmer
33.848
970257AG2-171 GEN
Solar/Wind Harmer
11.697
315785AD2-033 C
Solar/Wind Harmer
6.684
964241AG1-285 GEN
Solar/Wind Harmer
19.507
316131AB2-060 GEN
Solar/Wind Harmer
2.398
316478AD1-087 GEN
Solar/Wind Harmer
1.322
316486AD2-202 GEN
Solar/Wind Harmer
0.387
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.38
960061AF2-297 GEN
Solar/Wind Harmer
6.313
971683AH1-343 GEN
Solar/Wind Harmer
4.664
966621AG1-532 GEN
Solar/Wind Harmer
0.184
313506AB2-031 GEN
Solar/Wind Harmer
0.7
316283AC2-100 C
Solar/Wind Harmer
0.734
316210AC1-098 GEN
Solar/Wind Harmer
1.061
970917AG2-570 GEN
Solar/Wind Harmer
16.827
316365GEN2_N
Solar/Wind Harmer
0.451
316327AA2-057 GEN
Solar/Wind Harmer
0.674
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.136
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
315724AD1-057 GEN
Solar/Wind Harmer
0.366
316313AB2-026
Solar/Wind Helper
0.342
316258AE1-075 C
Solar/Wind Helper
0.308
316405AF2-144 C
Solar/Wind Helper
0.257
3148013FISHERV
Solar/Wind Helper
0.124
CPLELTFEXP_CPLE->PJM
CLTF
3.934
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.902
LAGNLTFEXP_LAGN->PJM
CLTF
2.053
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.953
TVALTFEXP_TVA->PJM
CLTF
1.009
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.279
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.343
MECLTFEXP_MEC->PJM
CLTF
0.782
SIGELTFEXP_SIGE->PJM
CLTF
0.022
NYPJM->LTFIMP_NY
CLTF
0.325
LGEELTFEXP_LGEE->PJM
CLTF
0.24
WECLTFEXP_WEC->PJM
CLTF
0.127

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:125.05 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:874.1
MW Contribution:12.56
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.186
3144293JTRSVLE
50/50
0.998
970535AG2-341 GEN
50/50
2.87
3152661PLYWOOD A
50/50
0.275
3146776BUCKING
Solar/Wind Harmer
-0.307
3151611KERR 4
50/50
0.281
3151621KERR 5
50/50
0.281
3151631KERR 6
50/50
0.281
3151641KERR 7
50/50
0.281
3151541CLOVER2
50/50
2.864
971845AH1-439 GEN
Solar/Wind Harmer
40.143
970285AG2-188 GEN
Solar/Wind Harmer
63.606
315657AE1-056 GEN
Solar/Wind Harmer
15.849
946301AF1-294 GEN
Solar/Wind Harmer
10.105
961791AG1-021 GEN
Solar/Wind Harmer
4.929
970683AG2-441 GEN
Solar/Wind Harmer
27.639
970681AG2-440 GEN
Solar/Wind Harmer
22.111
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.044
316239AB2-077_GEN
Solar/Wind Harmer
0.628
316238AB2-078_GEN
Solar/Wind Harmer
0.628
316118AC1-105 GEN
Solar/Wind Harmer
0.998
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.123
970865AG2-541 GEN
Solar/Wind Harmer
4.251
316123AC1-075 GEN
Solar/Wind Harmer
0.968
970165AG2-112 GEN
Solar/Wind Harmer
0.853
970163AG2-111 GEN
Solar/Wind Harmer
0.813
946281AF1-292 GEN
Solar/Wind Harmer
0.193
316087AB2-174 GEN
Solar/Wind Harmer
1.199
3137643SOCKMAN
Solar/Wind Harmer
-0.032
971967AH1-528 GEN
Solar/Wind Harmer
14.441
315607AA1-063A GEN
Solar/Wind Harmer
0.73
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.021
970581AG2-369 GEN
Solar/Wind Harmer
3.458
270494AE1-108_GEN
Solar/Wind Helper
4.516
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.186
3151591KERR 2
50/50
0.281
970413AG2-270 GEN
50/50
12.559
3146776BUCKING
Solar/Wind Harmer
-0.027
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.558
970909AG2-566 GEN
Solar/Wind Harmer
4.05
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.415
963181AG1-167 GEN
Solar/Wind Harmer
3.697
959311AF2-222 GEN
Solar/Wind Harmer
33.722
970257AG2-171 GEN
Solar/Wind Harmer
11.651
315785AD2-033 C
Solar/Wind Harmer
6.656
964241AG1-285 GEN
Solar/Wind Harmer
19.405
316131AB2-060 GEN
Solar/Wind Harmer
2.383
316478AD1-087 GEN
Solar/Wind Harmer
1.306
316486AD2-202 GEN
Solar/Wind Harmer
0.383
316248AF1-058 C
Solar/Wind Harmer
0.383
960061AF2-297 GEN
Solar/Wind Harmer
6.356
3147043LAWRENC
Solar/Wind Harmer
-0.007
971683AH1-343 GEN
Solar/Wind Harmer
4.828
966621AG1-532 GEN
Solar/Wind Harmer
0.175
313506AB2-031 GEN
Solar/Wind Harmer
0.668
316283AC2-100 C
Solar/Wind Harmer
0.723
316210AC1-098 GEN
Solar/Wind Harmer
1.017
970917AG2-570 GEN
Solar/Wind Harmer
16.116
316327AA2-057 GEN
Solar/Wind Harmer
0.646
316313AB2-026
Solar/Wind Helper
0.338
316258AE1-075 C
Solar/Wind Helper
0.304
316405AF2-144 C
Solar/Wind Helper
0.253
3148013FISHERV
Solar/Wind Helper
0.124
3144293JTRSVLE
50/50
1.186
3151601KERR 3
50/50
0.281
3151581KERR 1
50/50
0.1
3151531CLOVER1
50/50
2.878
972003AH1-546 GEN
Solar/Wind Harmer
47.257
316322AB2-045
Solar/Wind Harmer
2.592
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.929
971563AH1-280 GEN
Solar/Wind Harmer
4.929
970685AG2-442 GEN
Solar/Wind Harmer
30.955
962491AG1-098 GEN
Solar/Wind Harmer
14.261
316237AB2-079_GEN
Solar/Wind Harmer
0.628
315693AD1-088 GEN
Solar/Wind Harmer
10.081
970401AG2-262 GEN
Solar/Wind Harmer
1.068
957481AF2-042 GEN
Solar/Wind Harmer
45.769
315687AD1-152 GEN
Solar/Wind Harmer
1.638
971065AG2-659 GEN
Solar/Wind Harmer
6.564
316129AC1-054 GEN
Solar/Wind Harmer
1.114
3147043LAWRENC
Adder
1.008
316003AC1-222 GEN
Solar/Wind Harmer
1.162
971795AH1-408 GEN
Solar/Wind Harmer
8.467
960081AF2-299 GEN
Solar/Wind Harmer
0.97
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.093
316212AC1-099_GEN
Solar/Wind Harmer
0.565
970919AG2-571 GEN
Solar/Wind Harmer
2.04
970087AG2-069 GEN
Solar/Wind Harmer
6.032
316336AC2-165 C
Solar/Wind Helper
1.446
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.329
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.162
963191AG1-168 GEN
Solar/Wind Harmer
3.697
971741AH1-377 GEN
Solar/Wind Harmer
43.59
316034AC1-036 C
Solar/Wind Harmer
0.577
970323AG2-213 GEN
Solar/Wind Harmer
15.535
971775AH1-396 GEN
Solar/Wind Harmer
2.212
313527AB2-043 GEN
Solar/Wind Harmer
3.479
962561AG1-105 GEN
Solar/Wind Harmer
9.636
964791AG1-342 GEN
Solar/Wind Harmer
3.494
939181AE1-148 GEN
Solar/Wind Harmer
9.198
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.308
970933AG2-581 GEN
Solar/Wind Harmer
9.214
316181AB2-040 GEN
Solar/Wind Harmer
1.159
942751AE2-291 GEN
Solar/Wind Harmer
5.121
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.895
3145593CAROLNA
Solar/Wind Harmer
0.066
316222AC1-221 GEN
Solar/Wind Harmer
0.788
3145783HORNRTN
Solar/Wind Harmer
0.922
3145783HORNRTN
Solar/Wind Harmer
0.738
3145783HORNRTN
Solar/Wind Harmer
0.231
3145783HORNRTN
Solar/Wind Harmer
0.092
316426AA2-053 GEN
Solar/Wind Harmer
0.763
316274AC1-208 GEN
Solar/Wind Harmer
0.732
972187AH1-678 GEN
Adder
1.663
315821AE2-092 GEN
Solar/Wind Helper
2.985
CPLELTFEXP_CPLE->PJM
CLTF
3.818
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.266
LAGNLTFEXP_LAGN->PJM
CLTF
1.942
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.684
TVALTFEXP_TVA->PJM
CLTF
0.953
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.791
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.144
MECLTFEXP_MEC->PJM
CLTF
0.716
SIGELTFEXP_SIGE->PJM
CLTF
0.02
NYPJM->LTFIMP_NY
CLTF
0.309
LGEELTFEXP_LGEE->PJM
CLTF
0.214
WECLTFEXP_WEC->PJM
CLTF
0.113

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.94 %
Rating:571.52 MVA
Rating Type:A
MVA to Mitigate:679.77
MW Contribution:12.47
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.182
3144293JTRSVLE
50/50
0.996
970535AG2-341 GEN
50/50
2.848
3152661PLYWOOD A
50/50
0.269
3151041BRUNSWICKG3
50/50
0.762
972187AH1-678 GEN
50/50
1.749
3146776BUCKING
Solar/Wind Harmer
2.741
3146776BUCKING
Solar/Wind Harmer
0.222
970301AG2-198 GEN
Solar/Wind Harmer
16.173
3147133PAMPLIN
Solar/Wind Harmer
0.375
3147133PAMPLIN
Solar/Wind Harmer
0.3
958211AF2-115 GEN
Solar/Wind Harmer
4.2
963191AG1-168 GEN
Solar/Wind Harmer
1.4
971741AH1-377 GEN
Solar/Wind Harmer
33.04
316034AC1-036 C
Solar/Wind Harmer
0.02
970323AG2-213 GEN
Solar/Wind Harmer
11.75
971775AH1-396 GEN
Solar/Wind Harmer
0.441
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
7.214
939181AE1-148 GEN
Solar/Wind Harmer
6.93
964791AG1-342 GEN
Solar/Wind Harmer
2.751
3146843MT LREL
Solar/Wind Harmer
0.143
3146843MT LREL
Solar/Wind Harmer
0.143
970099AG2-077 GEN
Solar/Wind Harmer
13.815
970933AG2-581 GEN
Solar/Wind Harmer
6.948
316181AB2-040 GEN
Solar/Wind Harmer
0.106
3145593CAROLNA
Solar/Wind Harmer
0.07
3145593CAROLNA
Solar/Wind Harmer
0.07
966811AG1-552 GEN
Solar/Wind Harmer
0.761
3145593CAROLNA
Solar/Wind Harmer
0.087
3145783HORNRTN
Solar/Wind Harmer
1.218
3145783HORNRTN
Solar/Wind Harmer
0.974
3145783HORNRTN
Solar/Wind Harmer
0.304
3145783HORNRTN
Solar/Wind Harmer
0.122
316222AC1-221 GEN
Solar/Wind Harmer
0.283
316426AA2-053 GEN
Solar/Wind Harmer
0.225
942751AE2-291 GEN
Solar/Wind Harmer
3.327
316274AC1-208 GEN
Solar/Wind Harmer
0.31
315821AE2-092 GEN
Solar/Wind Helper
2.982
3144293JTRSVLE
50/50
1.182
3151601KERR 3
50/50
0.278
3151581KERR 1
50/50
0.099
3151531CLOVER1
50/50
2.857
3147043LAWRENC
50/50
1.061
3151261ROARAP2
50/50
0.087
3151051BRUNSWICKS1
50/50
1.582
3151021BRUNSWICKG1
50/50
0.762
971451AH1-221 GEN
50/50
2.315
972003AH1-546 GEN
Solar/Wind Harmer
35.828
316322AB2-045
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Harmer
0.316
963171AG1-166 GEN
Solar/Wind Harmer
1.867
971563AH1-280 GEN
Solar/Wind Harmer
3.734
970685AG2-442 GEN
Solar/Wind Harmer
23.432
962491AG1-098 GEN
Solar/Wind Harmer
10.785
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
8.574
970401AG2-262 GEN
Solar/Wind Harmer
0.841
957481AF2-042 GEN
Solar/Wind Harmer
34.537
315687AD1-152 GEN
Solar/Wind Harmer
0.004
971065AG2-659 GEN
Solar/Wind Harmer
4.943
316129AC1-054 GEN
Solar/Wind Harmer
0.422
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971795AH1-408 GEN
Solar/Wind Harmer
6.643
960081AF2-299 GEN
Solar/Wind Harmer
0.73
3145783HORNRTN
Solar/Wind Harmer
0.068
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
0.295
970919AG2-571 GEN
Solar/Wind Harmer
2.021
970087AG2-069 GEN
Solar/Wind Harmer
4.539
316336AC2-165 C
Solar/Wind Helper
1.447
3151611KERR 4
50/50
0.278
3151621KERR 5
50/50
0.278
3151631KERR 6
50/50
0.278
3151641KERR 7
50/50
0.278
3151541CLOVER2
50/50
2.843
3151281ROARAP4
50/50
0.085
3151281ROARAP4
50/50
0.079
963041AG1-153 GEN
50/50
1.544
971845AH1-439 GEN
Solar/Wind Harmer
30.475
970285AG2-188 GEN
Solar/Wind Harmer
51.158
315657AE1-056 GEN
Solar/Wind Harmer
12.943
946301AF1-294 GEN
Solar/Wind Harmer
6.907
961791AG1-021 GEN
Solar/Wind Harmer
3.36
970683AG2-441 GEN
Solar/Wind Harmer
20.922
970681AG2-440 GEN
Solar/Wind Harmer
16.737
3144303KENBRDG
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
4.571
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.326
3147173SINAI
Solar/Wind Harmer
0.11
3147243WELCO
Solar/Wind Harmer
0.069
970831AG2-522 GEN
Solar/Wind Harmer
4.61
970865AG2-541 GEN
Solar/Wind Harmer
3.002
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.286
316123AC1-075 GEN
Solar/Wind Harmer
0.097
970165AG2-112 GEN
Solar/Wind Harmer
0.576
970163AG2-111 GEN
Solar/Wind Harmer
0.549
971967AH1-528 GEN
Solar/Wind Harmer
10.852
315607AA1-063A GEN
Solar/Wind Harmer
0.13
3146043SEABORD
Solar/Wind Harmer
0.063
970085AG2-068 GEN
Solar/Wind Harmer
3.026
970581AG2-369 GEN
Solar/Wind Harmer
2.602
270494AE1-108_GEN
Solar/Wind Helper
4.482
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.182
3151591KERR 2
50/50
0.278
970413AG2-270 GEN
50/50
12.466
3151261ROARAP2
50/50
0.085
3151031BRUNSWICKG2
50/50
0.762
3146776BUCKING
Solar/Wind Harmer
0.247
3146926FARMVIL
Solar/Wind Harmer
0.316
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.043
3147133PAMPLIN
Solar/Wind Harmer
1.178
971193AH1-056 GEN
Solar/Wind Harmer
22.85
963181AG1-167 GEN
Solar/Wind Harmer
1.4
959311AF2-222 GEN
Solar/Wind Harmer
25.461
970257AG2-171 GEN
Solar/Wind Harmer
8.812
315785AD2-033 C
Solar/Wind Harmer
2.115
964241AG1-285 GEN
Solar/Wind Harmer
14.651
316131AB2-060 GEN
Solar/Wind Harmer
0.614
316478AD1-087 GEN
Solar/Wind Harmer
0.465
316486AD2-202 GEN
Solar/Wind Harmer
0.137
3147043LAWRENC
Solar/Wind Harmer
0.066
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.699
971683AH1-343 GEN
Solar/Wind Harmer
3.468
313506AB2-031 GEN
Solar/Wind Harmer
0.226
316283AC2-100 C
Solar/Wind Harmer
0.132
316210AC1-098 GEN
Solar/Wind Harmer
0.53
970917AG2-570 GEN
Solar/Wind Harmer
5.054
316327AA2-057 GEN
Solar/Wind Harmer
0.085
316313AB2-026
Solar/Wind Helper
0.339
316258AE1-075 C
Solar/Wind Helper
0.305
316405AF2-144 C
Solar/Wind Helper
0.254
3148013FISHERV
Solar/Wind Helper
0.124
CPLELTFEXP_CPLE->PJM
CLTF
3.771
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.326
LAGNLTFEXP_LAGN->PJM
CLTF
1.944
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.608
TVALTFEXP_TVA->PJM
CLTF
0.955
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.922
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.157
MECLTFEXP_MEC->PJM
CLTF
0.729
SIGELTFEXP_SIGE->PJM
CLTF
0.02
NYPJM->LTFIMP_NY
CLTF
0.308
LGEELTFEXP_LGEE->PJM
CLTF
0.221
WECLTFEXP_WEC->PJM
CLTF
0.117
CONTINGENCY 'DVP_P1-2: LN 576_SRT-S'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: WT576_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 2                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: 57602_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 1                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 2027_SRT-A-3'
 OPEN BRANCH FROM BUS 314322 TO BUS 314333 CKT 1   /*6MDLTHAN     230.0 - 6POWHATN     230.0
 OPEN BRANCH FROM BUS 314333 TO BUS 316335 CKT 1   /*6POWHATN     230.0 - AC2-165 TAP  230.0
 OPEN BUS 314333                                   /*6POWHATN     230.0
 OPEN BUS 316258                                   /*AE1-075 C    230.0
 OPEN BUS 316313                                   /*AB2-026      230.0
 OPEN BUS 316405                                   /*AF2-144 C    230.0
END
CONTINGENCY 'DVP_P1-2: LN 593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P1-2: LN 587_SRT-A-3'
 OPEN BRANCH FROM BUS 971966 TO BUS 314936 CKT 1   /*AH1-528 TP   500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 511T556_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 OPEN BRANCH FROM BUS 971966 TO BUS 314936 CKT 1                /*AH1-528 TP   500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 587T591_SRT-S'
 OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1                /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 OPEN BRANCH FROM BUS 971966 TO BUS 314936 CKT 1                /*AH1-528 TP   500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 55692_SRT-S'
 OPEN BRANCH FROM BUS 314936 TO BUS 971966 CKT 1                /*8RAWLINGS    500.0 - AH1-528 TP   500.0
 OPEN BUS 314920                                                /*8RAWLIN_STC1 500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: H2T593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313986 CKT 2   /*8UNITY       500.0 - 6UNITY       230.0
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P4-2: H1T593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313986 CKT 1   /*8UNITY       500.0 - 6UNITY       230.0
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'AEP_P2-2_#1377_05J.FERR 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242514 TO BUS 290022 CKT 1   /*05J.FERR     765.0 - 05J.FERR 1EQ   1.0
 OPEN BRANCH FROM BUS 242520 TO BUS 290022 CKT 1   /*05J.FERR     500.0 - 05J.FERR 1EQ   1.0
 OPEN BRANCH FROM BUS 242520 TO BUS 306719 CKT 1   /*05J.FERR     500.0 - 8ANTIOCH     500.0
 OPEN BRANCH FROM BUS 290022 TO BUS 290023 CKT 1   /*05J.FERR 1EQ   1.0 - 05J.FERR T1   13.8
END
CONTINGENCY 'DVP_P7-1: LN 2106-2111_SRT-A'
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2   /*6BEARGRDN    230.0 - 6BREMO       230.0
END
CONTINGENCY 'DVP_P7-1: LN 2003-205_SRT-S'
 OPEN BRANCH FROM BUS 314263 TO BUS 314287 CKT 1                /*6TYLER1      230.0 - 6CHESTF B    230.0
 OPEN BRANCH FROM BUS 314263 TO BUS 314331 CKT 1                /*6TYLER1      230.0 - 6POE         230.0
 OPEN BRANCH FROM BUS 314287 TO BUS 314346 CKT 1                /*6CHESTF B    230.0 - 6TYLER       230.0
 OPEN BRANCH FROM BUS 314301 TO BUS 314316 CKT 1                /*6HARR205     230.0 - 6LOCKS       230.0
 OPEN BRANCH FROM BUS 314301 TO BUS 314346 CKT 1                /*6HARR205     230.0 - 6TYLER       230.0
 OPEN BRANCH FROM BUS 314314 TO BUS 314316 CKT 1                /*3LOCKS       115.0 - 6LOCKS       230.0
 OPEN BRANCH FROM BUS 314329 TO BUS 314331 CKT 2                /*3POE         115.0 - 6POE         230.0
 OPEN BUS 314263                                                /*6TYLER1      230.0
 OPEN BUS 314301                                                /*6HARR205     230.0
 OPEN BUS 314346                                                /*6TYLER       230.0
 OPEN BUS 315839                                                /*AE2-212 C    230.0
 OPEN BUS 316240                                                /*AF1-291 C    230.0
 SET POSTCONTRATING 956 BRANCH FROM BUS 314260 TO BUS 314287 CKT 1 /*6VARINA      230.0 - 6CHESTF B    230.0
 SET PRECONTRATING 876 BRANCH FROM BUS 314260 TO BUS 314287 CKT 1 /*6VARINA      230.0 - 6CHESTF B    230.0
END
CONTINGENCY 'AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A'
 OPEN BRANCH FROM BUS 242569 TO BUS 242734 CKT 1   /*05BRUSHT     138.0 - 05NEWLDN     138.0
 OPEN BRANCH FROM BUS 242641 TO BUS 242734 CKT 1   /*05FOREST     138.0 - 05NEWLDN     138.0
 OPEN BRANCH FROM BUS 242687 TO BUS 242734 CKT 1   /*05JOHNMT     138.0 - 05NEWLDN     138.0
END
CONTINGENCY 'DVP_P4-2: 562T563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1   /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1   /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 2002_SRT-A'
 OPEN BRANCH FROM BUS 314282 TO BUS 314331 CKT 1   /*6CARSON      230.0 - 6POE         230.0
 OPEN BRANCH FROM BUS 314329 TO BUS 314331 CKT 1   /*3POE         115.0 - 6POE         230.0
END
CONTINGENCY 'DVP_P1-2: LN 249_SRT-A'
 OPEN BRANCH FROM BUS 313014 TO BUS 314285 CKT 1   /*6CHAPARRAL   230.0 - 6CHAPARRAL T 230.0
 OPEN BRANCH FROM BUS 314282 TO BUS 314285 CKT 1   /*6CARSON      230.0 - 6CHAPARRAL T 230.0
 OPEN BRANCH FROM BUS 314285 TO BUS 314316 CKT 1   /*6CHAPARRAL T 230.0 - 6LOCKS       230.0
 OPEN BRANCH FROM BUS 314314 TO BUS 314316 CKT 2   /*3LOCKS       115.0 - 6LOCKS       230.0
 OPEN BUS 313014                                   /*6CHAPARRAL   230.0
 OPEN BUS 314285                                   /*6CHAPARRAL T 230.0
END
CONTINGENCY 'DVP_P2-2: ALTAVISTA 115KV_SRT-A'
 OPEN BUS 313162   /*3HALL BR TAP 115.0
 OPEN BUS 314515   /*3ALTVS_1     115.0
 OPEN BUS 314666   /*3ALTVSTA     115.0
 OPEN BUS 314700   /*3HALL BR     115.0
 OPEN BUS 314705   /*3HURT        115.0
 OPEN BUS 315156   /*1HALLBR1      13.8
END
CONTINGENCY 'DVP_P4-5: 556X2_SRT-S'
 OPEN BRANCH FROM BUS 313995 TO BUS 313996 CKT 2   /*8FINNEYWOOD  500.0 - 6FINNEYWOOD  230.0
 OPEN BRANCH FROM BUS 313995 TO BUS 957480 CKT 1   /*8FINNEYWOOD  500.0 - AF2-042 TP   500.0
END
CONTINGENCY 'DVP_P4-5: 556X1_SRT-S'
 OPEN BRANCH FROM BUS 313995 TO BUS 313996 CKT 1   /*8FINNEYWOOD  500.0 - 6FINNEYWOOD  230.0
 OPEN BRANCH FROM BUS 313995 TO BUS 957480 CKT 1   /*8FINNEYWOOD  500.0 - AF2-042 TP   500.0
END
CONTINGENCY 'DVP_P4-5: 593X1_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
 OPEN BRANCH FROM BUS 313995 TO BUS 313996 CKT 1   /*8FINNEYWOOD  500.0 - 6FINNEYWOOD  230.0
END
CONTINGENCY 'DVP_P4-5: 593X2_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
 OPEN BRANCH FROM BUS 313995 TO BUS 313996 CKT 2   /*8FINNEYWOOD  500.0 - 6FINNEYWOOD  230.0
END
CONTINGENCY 'DVP_P4-2: 56372_SRT-S'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1                /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 56272_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1                /*8CARSON      500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON      500.0 - 8MDLTHAN     500.0
END
CONTINGENCY 'DVP_P4-2: H2T574_SRT-S'
 OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 2                /*6LADYSMITH   230.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H1T574_SRT-S'
 OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 1                /*6ELMONT      230.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 562_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1                /*8CARSON      500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON      500.0 - 8MDLTHAN     500.0
END
CONTINGENCY 'DVP_P2-2: BREMO B1_SRT-A'
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1   /*3BREMO       115.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 970936 TO BUS 314747 CKT 1   /*AG2-583 TP   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 972002 TO BUS 314747 CKT 1   /*AH1-546 TP   230.0 - 6BREMO       230.0
 OPEN BUS 314326                                   /*6BEARGRDN    230.0
 OPEN BUS 314747                                   /*6BREMO       230.0
 OPEN BUS 315191                                   /*1BEARGRDN G1  18.0
 OPEN BUS 315192                                   /*1BEARGRDN G2  18.0
 OPEN BUS 315193                                   /*1BEARGRDN S1  18.0
END
CONTINGENCY 'DVP_P7-1: LN 208-259_SRT-S'
 OPEN BRANCH FROM BUS 314276 TO BUS 314287 CKT 1                /*6BASIN       230.0 - 6CHESTF B    230.0
 OPEN BRANCH FROM BUS 314286 TO BUS 314309 CKT 1                /*6CHESTF A    230.0 - 6IRON208     230.0
 OPEN BRANCH FROM BUS 314309 TO BUS 314338 CKT 1                /*6IRON208     230.0 - 6SOUWEST     230.0
 OPEN BUS 314309                                                /*6IRON208     230.0
 SET POSTCONTRATING 876 BRANCH FROM BUS 314263 TO BUS 314287 CKT 1 /*6TYLER1      230.0 - 6CHESTF B    230.0
 SET PRECONTRATING 813 BRANCH FROM BUS 314263 TO BUS 314287 CKT 1 /*6TYLER1      230.0 - 6CHESTF B    230.0
END
CONTINGENCY 'DVP_P4-1: G202_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 2                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314918 TO BUS 315226 CKT 1                /*8NO ANNA     500.0 - 1N ANNA2      22.0
 OPEN BUS 315226                                                /*1N ANNA2      22.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P2-2: NORTH ANNA B1_SRT-S'
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P2-2: NORTH ANNA B2_SRT-S'
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 2028_SRT-A'
 OPEN BRANCH FROM BUS 313373 TO BUS 313707 CKT 1   /*6GRAPEVINE   230.0 - 6FORK UNION  230.0
 OPEN BRANCH FROM BUS 313373 TO BUS 314765 CKT 1   /*6GRAPEVINE   230.0 - 6MTEAGLE     230.0
 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1   /*6CHARLVL     230.0 - 6MTEAGLE     230.0
 OPEN BUS 313373                                   /*6GRAPEVINE   230.0
 OPEN BUS 313493                                   /*3GRAPEVINE   115.0
 OPEN BUS 314754                                   /*3CUNNING     115.0
 OPEN BUS 314765                                   /*6MTEAGLE     230.0
END
CONTINGENCY 'DVP_P1-2: LN 9812_SRT-A'
 OPEN BRANCH FROM BUS 314197 TO BUS 315672 CKT 1   /*6LDYSMITH CT 230.0 - AE1-157 TAP  230.0
END
CONTINGENCY 'DVP_P7-1: LN 2090-256_SRT-S'
 OPEN BRANCH FROM BUS 313837 TO BUS 314138 CKT 1                /*6SUMMIT      230.0 - 6MINE RD     230.0
 OPEN BRANCH FROM BUS 313837 TO BUS 314197 CKT 1                /*6SUMMIT      230.0 - 6LDYSMITH CT 230.0
 OPEN BRANCH FROM BUS 314137 TO BUS 314138 CKT 1                /*6FREDBRG     230.0 - 6MINE RD     230.0
 OPEN BRANCH FROM BUS 314150 TO BUS 314212 CKT 1                /*6STJOHN      230.0 - 6FOUR RIVERS 230.0
 OPEN BRANCH FROM BUS 314197 TO BUS 315672 CKT 1                /*6LDYSMITH CT 230.0 - AE1-157 TAP  230.0
 OPEN BUS 313837                                                /*6SUMMIT      230.0
 OPEN BUS 314138                                                /*6MINE RD     230.0
 OPEN BUS 314149                                                /*3STJOHND     115.0
 OPEN BUS 314150                                                /*6STJOHN      230.0
 OPEN BUS 314154                                                /*3STJOHNS     115.0
 OPEN BUS 315672                                                /*AE1-157 TAP  230.0
 OPEN BUS 315673                                                /*AE1-157 GEN    0.6
 OPEN BUS 315803                                                /*AE1-157 MAIN 230.0
 OPEN BUS 315804                                                /*AE1-157 COL1  34.5
 OPEN BUS 315805                                                /*AE1-157 COL2  34.5
 SET POSTCONTRATING 657 BRANCH FROM BUS 313027 TO BUS 314212 CKT 1 /*6FOUR RIVER1 230.0 - 6FOUR RIVERS 230.0
 SET POSTCONTRATING 876 BRANCH FROM BUS 314212 TO BUS 315610 CKT 1 /*6FOUR RIVERS 230.0 - AA1-145 MAIN 230.0
 SET PRECONTRATING 598 BRANCH FROM BUS 313027 TO BUS 314212 CKT 1 /*6FOUR RIVER1 230.0 - 6FOUR RIVERS 230.0
 SET PRECONTRATING 813 BRANCH FROM BUS 314212 TO BUS 315610 CKT 1 /*6FOUR RIVERS 230.0 - AA1-145 MAIN 230.0
END
CONTINGENCY 'DVP_P7-1: LN 2054-2135_SRT-A'
 OPEN BRANCH FROM BUS 314734 TO BUS 314758 CKT 1   /*6CASHSCORNER 230.0 - 6GORDNVL     230.0
 OPEN BRANCH FROM BUS 314734 TO BUS 314759 CKT 1   /*6CASHSCORNER 230.0 - 6HOLLYMD     230.0
 OPEN BRANCH FROM BUS 314749 TO BUS 314772 CKT 1   /*6CHARLVL     230.0 - 6PROFFIT     230.0
 OPEN BRANCH FROM BUS 314759 TO BUS 314772 CKT 1   /*6HOLLYMD     230.0 - 6PROFFIT     230.0
 OPEN BUS 314734                                   /*6CASHSCORNER 230.0
 OPEN BUS 314772                                   /*6PROFFIT     230.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-2'
 OPEN BRANCH FROM BUS 941030 TO BUS 970672 CKT 1   /*AE2-094 TP   500.0 - AG2-436 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 58572_SRT-A'
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P4-5: W72_SRT-A'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1   /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P4-2: XT585_SRT-S'
 OPEN BRANCH FROM BUS 970672 TO BUS 314940 CKT 1                /*AG2-436 TP   500.0 - 8ROGERS RD   500.0
 SET POSTCONTRATING 3464 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET PRECONTRATING 3464 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
END
CONTINGENCY 'DVP_P4-2: 54472_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 939410 CKT 1                /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P1-2: LN 511_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 51192_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 OPEN BUS 314921                                                /*8RAWLIN_STC2 500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 51172_SRT-S'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1                /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 511T544_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 939410 CKT 1                /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: H6T576_SRT-A'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1   /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1   /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: H6T563_SRT-S'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1                /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
314747 to 313867 ckt 1
314747 to 970936 ckt 1
313867 to 313707 ckt 1
314268 to 314692 ckt 1
314677 to 972002 ckt 1
314282 to 314285 ckt 1
314282 to 314331 ckt 1
313868 to 316335 ckt 1
314285 to 314316 ckt 1
314563 to 313994 ckt 1
315684 to 314697 ckt 1
313178 to 314435 ckt 1
314692 to 970284 ckt 1
313996 to 313995 ckt 1
313996 to 313995 ckt 2
313996 to 962490 ckt 1
313707 to 313373 ckt 1
313373 to 314765 ckt 1
314765 to 314749 ckt 1
313994 to 313178 ckt 1
314333 to 314322 ckt 1
314435 to 314282 ckt 1
314697 to 316218 ckt 1
314902 to 314282 ckt 2
314902 to 314914 ckt 1
314914 to 314322 ckt 1
314914 to 314918 ckt 1
314936 to 314902 ckt 1
314940 to 970672 ckt 1
314923 to 314924 ckt 1
316218 to 316281 ckt 1
316281 to 304070 ckt 1
316335 to 314333 ckt 1
941030 to 314902 ckt 1
962490 to 971740 ckt 1
970284 to 971844 ckt 1
970300 to 314268 ckt 1
970672 to 941030 ckt 1
970936 to 313868 ckt 1
971740 to 970300 ckt 1
971844 to 314677 ckt 1
972002 to 314747 ckt 1

Winter Peak Analysis

The New Service Request AG2-270 was evaluated as a 150.0 MW (105.0 MW Capacity) injection in the Dominion area.

AG2-270 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 150.0 MW (150.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Light Load Analysis

The New Service Request AG2-270 was evaluated as a 150.0 MW injection and 150.0 MW withdrawal in the Dominion area.

AG2-270 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 150.0 MW (150.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
3CLOUD-6CLOUD 115.0/230.0 kV Ckt 1 transformer
DVP_P1-3: 6CLOUD-TX#2_SRT-A
SingleAC101.49 %298.45B302.898.55
GD2DVP
3CLOUD-6CLOUD 115.0/230.0 kV Ckt 2 transformer
DVP_P1-3: 6CLOUD-TX#1_SRT-A
SingleAC118.9 %254.74B302.898.55
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-L
SingleAC118.65 %830.96B985.9215.29
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC112.18 %830.96B932.1712.0
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-L
SingleAC118.47 %830.96B984.4115.29
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC112.0 %830.96B930.6412.0
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-L
SingleAC116.61 %698.42B814.4520.33
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC113.33 %698.42B791.542.69
GD2DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-L
SingleAC111.19 %722.86B803.757.54
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-L
SingleAC108.55 %687.14B745.8720.35
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC107.24 %687.14B736.9242.71
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-L
SingleAC121.87 %830.96B1012.6814.36
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC117.54 %830.96B976.7411.15
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-L
SingleAC124.77 %808.4B1008.6114.36
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC120.34 %808.4B972.8311.15
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-L
SingleAC124.16 %808.4B1003.714.36
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC119.74 %808.4B967.9511.15
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 509T570_SRT-A
BreakerAC109.87 %541.0B594.4234.02
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-3
SingleAC118.15 %508.54B600.8233.8
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-1
SingleAC115.23 %508.54B585.9833.8
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-5: 593X1_SRT-A
BreakerAC108.28 %541.0B585.7868.07
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-5: 593X2_SRT-A
BreakerAC108.27 %541.0B585.7568.06
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC107.54 %541.0B581.7867.43
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC107.54 %541.0B581.7867.43
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-L
SingleAC113.74 %687.14B781.5620.35
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC111.28 %687.14B764.6442.71
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-L
SingleAC117.02 %687.14B804.1120.35
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC113.89 %687.14B782.5642.71
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-L
SingleAC120.47 %698.42B841.4220.33
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC116.45 %698.42B813.2942.69

Details for 3CLOUD-6CLOUD 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6CLOUD-TX#2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3CLOUD-6CLOUD 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-3: 6CLOUD-TX#2_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.49 %
Rating:298.45 MVA
Rating Type:B
MVA to Mitigate:302.89
MW Contribution:8.55
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Harmer
0.187
316486AD2-202 GEN
Solar/Wind Helper
0.287
959311AF2-222 GEN
Solar/Wind Harmer
13.483
3146843MT LREL
Solar/Wind Harmer
0.3
3146843MT LREL
Solar/Wind Harmer
0.3
958211AF2-115 GEN
Solar/Wind Harmer
1.441
3147133PAMPLIN
Solar/Wind Harmer
0.242
3144303KENBRDG
Solar/Wind Harmer
0.339
946301AF1-294 GEN
Solar/Wind Harmer
2.363
3137643SOCKMAN
Solar/Wind Harmer
0.904
315657AE1-056 GEN
Solar/Wind Harmer
2.909
966811AG1-552 GEN
Solar/Wind Harmer
0.852
971775AH1-396 GEN
Solar/Wind Harmer
1.016
970685AG2-442 GEN
Solar/Wind Harmer
9.911
3147043LAWRENC
50/50
1.159
961791AG1-021 GEN
Solar/Wind Harmer
1.153
971795AH1-408 GEN
Solar/Wind Harmer
6.581
3147133PAMPLIN
Solar/Wind Harmer
0.194
970535AG2-341 GEN
50/50
12.202
939181AE1-148 GEN
Solar/Wind Harmer
13.99
964791AG1-342 GEN
Solar/Wind Harmer
2.177
3147133PAMPLIN
Solar/Wind Harmer
0.761
3146043SEABORD
Solar/Wind Harmer
0.188
316478AD1-087 GEN
Solar/Wind Helper
0.98
963171AG1-166 GEN
Solar/Wind Harmer
1.153
970413AG2-270 GEN
50/50
Charging
8.551
970831AG2-522 GEN
Solar/Wind Harmer
9.281
971065AG2-659 GEN
Solar/Wind Harmer
10.411
3145783HORNRTN
Solar/Wind Harmer
0.712
3145783HORNRTN
Solar/Wind Harmer
0.089
970683AG2-441 GEN
Solar/Wind Harmer
8.849
962561AG1-105 GEN
Solar/Wind Harmer
6.204
971193AH1-056 GEN
Solar/Wind Harmer
4.849
3145783HORNRTN
Solar/Wind Harmer
0.223
960081AF2-299 GEN
Solar/Wind Harmer
0.697
964241AG1-285 GEN
Solar/Wind Harmer
13.117
970681AG2-440 GEN
Solar/Wind Harmer
7.079
970401AG2-262 GEN
Solar/Wind Harmer
0.665
963191AG1-168 GEN
Solar/Wind Harmer
0.864
3145783HORNRTN
Solar/Wind Harmer
0.89
3145783HORNRTN
Solar/Wind Harmer
0.223
315785AD2-033 C
Solar/Wind Harmer
0.001
970323AG2-213 GEN
Solar/Wind Harmer
6.776
3145593CAROLNA
Solar/Wind Harmer
0.237
3145593CAROLNA
Solar/Wind Harmer
0.237
970257AG2-171 GEN
Solar/Wind Harmer
5.082
963181AG1-167 GEN
Solar/Wind Harmer
0.864
3145593CAROLNA
Solar/Wind Harmer
0.066
971563AH1-280 GEN
Solar/Wind Harmer
1.153
LAGNLTFEXP_LAGN->PJM
CLTF
0.378
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.399
TVALTFEXP_TVA->PJM
CLTF
0.196
NYPJM->LTFIMP_NY
CLTF
0.164
LGEELTFEXP_LGEE->PJM
CLTF
0.039
WECLTFEXP_WEC->PJM
CLTF
0.019
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.866
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.594
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.644
MECLTFEXP_MEC->PJM
CLTF
0.132
SIGELTFEXP_SIGE->PJM
CLTF
0.004
CPLELTFEXP_CPLE->PJM
CLTF
0.74
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.79

Details for 3CLOUD-6CLOUD 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6CLOUD-TX#1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3CLOUD-6CLOUD 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-3: 6CLOUD-TX#1_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.9 %
Rating:254.74 MVA
Rating Type:B
MVA to Mitigate:302.89
MW Contribution:8.55
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Harmer
0.187
316486AD2-202 GEN
Solar/Wind Helper
0.287
959311AF2-222 GEN
Solar/Wind Harmer
13.483
3146843MT LREL
Solar/Wind Harmer
0.3
3146843MT LREL
Solar/Wind Harmer
0.3
958211AF2-115 GEN
Solar/Wind Harmer
1.441
3147133PAMPLIN
Solar/Wind Harmer
0.242
3144303KENBRDG
Solar/Wind Harmer
0.339
946301AF1-294 GEN
Solar/Wind Harmer
2.363
3137643SOCKMAN
Solar/Wind Harmer
0.904
315657AE1-056 GEN
Solar/Wind Harmer
2.909
966811AG1-552 GEN
Solar/Wind Harmer
0.852
971775AH1-396 GEN
Solar/Wind Harmer
1.016
970685AG2-442 GEN
Solar/Wind Harmer
9.911
3147043LAWRENC
50/50
1.159
961791AG1-021 GEN
Solar/Wind Harmer
1.153
971795AH1-408 GEN
Solar/Wind Harmer
6.581
3147133PAMPLIN
Solar/Wind Harmer
0.194
970535AG2-341 GEN
50/50
12.202
939181AE1-148 GEN
Solar/Wind Harmer
13.99
964791AG1-342 GEN
Solar/Wind Harmer
2.177
3147133PAMPLIN
Solar/Wind Harmer
0.761
3146043SEABORD
Solar/Wind Harmer
0.188
316478AD1-087 GEN
Solar/Wind Helper
0.98
963171AG1-166 GEN
Solar/Wind Harmer
1.153
970413AG2-270 GEN
50/50
Charging
8.551
970831AG2-522 GEN
Solar/Wind Harmer
9.281
971065AG2-659 GEN
Solar/Wind Harmer
10.411
3145783HORNRTN
Solar/Wind Harmer
0.712
3145783HORNRTN
Solar/Wind Harmer
0.089
970683AG2-441 GEN
Solar/Wind Harmer
8.849
962561AG1-105 GEN
Solar/Wind Harmer
6.204
971193AH1-056 GEN
Solar/Wind Harmer
4.849
3145783HORNRTN
Solar/Wind Harmer
0.223
960081AF2-299 GEN
Solar/Wind Harmer
0.697
964241AG1-285 GEN
Solar/Wind Harmer
13.117
970681AG2-440 GEN
Solar/Wind Harmer
7.079
970401AG2-262 GEN
Solar/Wind Harmer
0.665
963191AG1-168 GEN
Solar/Wind Harmer
0.864
3145783HORNRTN
Solar/Wind Harmer
0.89
3145783HORNRTN
Solar/Wind Harmer
0.223
315785AD2-033 C
Solar/Wind Harmer
0.001
970323AG2-213 GEN
Solar/Wind Harmer
6.776
3145593CAROLNA
Solar/Wind Harmer
0.237
3145593CAROLNA
Solar/Wind Harmer
0.237
970257AG2-171 GEN
Solar/Wind Harmer
5.082
963181AG1-167 GEN
Solar/Wind Harmer
0.864
3145593CAROLNA
Solar/Wind Harmer
0.066
971563AH1-280 GEN
Solar/Wind Harmer
1.153
LAGNLTFEXP_LAGN->PJM
CLTF
0.378
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.399
TVALTFEXP_TVA->PJM
CLTF
0.196
NYPJM->LTFIMP_NY
CLTF
0.164
LGEELTFEXP_LGEE->PJM
CLTF
0.039
WECLTFEXP_WEC->PJM
CLTF
0.019
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.866
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.594
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.644
MECLTFEXP_MEC->PJM
CLTF
0.132
SIGELTFEXP_SIGE->PJM
CLTF
0.004
CPLELTFEXP_CPLE->PJM
CLTF
0.74
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.79

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.65 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:985.92
MW Contribution:15.29
Bus #Bus NameTypeMW Contribution
970531AG2-338 GEN
50/50
2.942
3146776BUCKING
Solar/Wind Harmer
4.03
3146776BUCKING
Solar/Wind Harmer
0.326
946301AF1-294 GEN
Solar/Wind Harmer
4.672
971741AH1-377 GEN
Solar/Wind Harmer
20.67
3144303KENBRDG
Solar/Wind Harmer
0.377
963041AG1-153 GEN
50/50
5.603
970285AG2-188 GEN
Solar/Wind Harmer
26.806
3147133PAMPLIN
Solar/Wind Harmer
0.603
958211AF2-115 GEN
Solar/Wind Harmer
2.849
959311AF2-222 GEN
Solar/Wind Harmer
16.226
941591AE2-156 GEN
50/50
5.885
3146926FARMVIL
Solar/Wind Harmer
0.482
3146926FARMVIL
Solar/Wind Harmer
0.482
970685AG2-442 GEN
Solar/Wind Harmer
14.615
971775AH1-396 GEN
Solar/Wind Harmer
1.131
966001AG1-469 GEN
Solar/Wind Helper
0.309
315616AA1-038_C
Solar/Wind Helper
1.093
316303AF2-085
50/50
2.185
3147043LAWRENC
50/50
0.98
3147133PAMPLIN
Solar/Wind Harmer
0.482
961791AG1-021 GEN
Solar/Wind Harmer
2.279
316192AB2-158 GEN
Solar/Wind Helper
1.356
315657AE1-056 GEN
Solar/Wind Harmer
7.237
970301AG2-198 GEN
Solar/Wind Harmer
9.831
970323AG2-213 GEN
Solar/Wind Harmer
7.539
315785AD2-033 C
Solar/Wind Harmer
0.001
970535AG2-341 GEN
50/50
5.504
972187AH1-678 GEN
50/50
2.54
315779AE2-040
50/50
1.062
3146776BUCKING
Solar/Wind Harmer
0.403
970937AG2-583 GEN
Solar/Wind Harmer
23.968
971845AH1-439 GEN
Solar/Wind Harmer
16.834
3147133PAMPLIN
Solar/Wind Harmer
1.894
316499AE2-029_GEN
Solar/Wind Helper
0.95
970119AG2-088 GEN
50/50
16.39
3146776BUCKING
Solar/Wind Harmer
0.363
963171AG1-166 GEN
Solar/Wind Harmer
2.279
962491AG1-098 GEN
Solar/Wind Harmer
5.987
970413AG2-270 GEN
50/50
15.291
316322AB2-045
Solar/Wind Harmer
0.029
972003AH1-546 GEN
Solar/Wind Harmer
19.314
972185AH1-677 GEN
50/50
4.982
944641AF1-129 GEN
50/50
18.776
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
6.356
963191AG1-168 GEN
Solar/Wind Harmer
1.709
970681AG2-440 GEN
Solar/Wind Harmer
10.44
964241AG1-285 GEN
Solar/Wind Harmer
9.945
3143336POWHATN
Solar/Wind Harmer
2.767
3143336POWHATN
Solar/Wind Harmer
2.352
971193AH1-056 GEN
Solar/Wind Harmer
12.062
970683AG2-441 GEN
Solar/Wind Harmer
13.049
963181AG1-167 GEN
Solar/Wind Harmer
1.709
970257AG2-171 GEN
Solar/Wind Harmer
5.655
972205AH1-687 GEN
50/50
22.082
970533AG2-339 GEN
50/50
7.355
971563AH1-280 GEN
Solar/Wind Harmer
2.279
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.088
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.247
LAGNLTFEXP_LAGN->PJM
CLTF
1.443
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.452
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.744
NYPJM->LTFIMP_NY
CLTF
0.685
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.518
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.233
MECLTFEXP_MEC->PJM
CLTF
0.086
CPLELTFEXP_CPLE->PJM
CLTF
3.897
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.1

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.18 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:932.17
MW Contribution:12.0
Bus #Bus NameTypeMW Contribution
3146776BUCKING
Solar/Wind Harmer
3.767
3146776BUCKING
Solar/Wind Harmer
0.305
946301AF1-294 GEN
Solar/Wind Harmer
4.18
971741AH1-377 GEN
Solar/Wind Harmer
18.185
3144303KENBRDG
Solar/Wind Harmer
0.331
3146926FARMVIL
Solar/Wind Harmer
0.443
3146926FARMVIL
Solar/Wind Harmer
0.443
970285AG2-188 GEN
Solar/Wind Harmer
24.963
3147133PAMPLIN
Solar/Wind Harmer
0.542
958211AF2-115 GEN
Solar/Wind Harmer
2.549
959311AF2-222 GEN
Solar/Wind Harmer
14.287
315657AE1-056 GEN
Solar/Wind Harmer
6.507
970685AG2-442 GEN
Solar/Wind Harmer
12.965
971775AH1-396 GEN
Solar/Wind Harmer
0.992
315616AA1-038_C
Solar/Wind Helper
1.713
966001AG1-469 GEN
Solar/Wind Helper
0.327
970301AG2-198 GEN
Solar/Wind Harmer
8.766
970323AG2-213 GEN
Solar/Wind Harmer
6.616
315785AD2-033 C
Solar/Wind Harmer
0
316303AF2-085
50/50
1.49
3147043LAWRENC
50/50
0.755
3147133PAMPLIN
Solar/Wind Harmer
0.434
961791AG1-021 GEN
Solar/Wind Harmer
2.039
316192AB2-158 GEN
Solar/Wind Helper
1.361
970535AG2-341 GEN
50/50
4.562
3146776BUCKING
Solar/Wind Harmer
0.377
970937AG2-583 GEN
Solar/Wind Harmer
22.266
971845AH1-439 GEN
Solar/Wind Harmer
15.715
3147133PAMPLIN
Solar/Wind Harmer
1.703
316499AE2-029_GEN
Solar/Wind Helper
1.238
970119AG2-088 GEN
50/50
11.178
3146776BUCKING
Solar/Wind Harmer
0.339
963171AG1-166 GEN
Solar/Wind Harmer
2.039
962491AG1-098 GEN
Solar/Wind Harmer
4.897
970413AG2-270 GEN
50/50
11.997
316322AB2-045
Solar/Wind Harmer
0.027
972003AH1-546 GEN
Solar/Wind Harmer
18.259
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
5.668
963191AG1-168 GEN
Solar/Wind Harmer
1.529
970681AG2-440 GEN
Solar/Wind Harmer
9.261
964241AG1-285 GEN
Solar/Wind Harmer
8.546
3143336POWHATN
Solar/Wind Harmer
2.42
3143336POWHATN
Solar/Wind Harmer
2.057
971193AH1-056 GEN
Solar/Wind Harmer
10.845
970683AG2-441 GEN
Solar/Wind Harmer
11.576
315760AF1-028 GEN
50/50
Charging
15.615
970117AG2-086 GEN
50/50
Charging
1.26
963181AG1-167 GEN
Solar/Wind Harmer
1.529
970257AG2-171 GEN
Solar/Wind Harmer
4.962
972205AH1-687 GEN
50/50
20.919
971563AH1-280 GEN
Solar/Wind Harmer
2.039
LAGNLTFEXP_LAGN->PJM
CLTF
2.195
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.99
TVALTFEXP_TVA->PJM
CLTF
1.148
NYPJM->LTFIMP_NY
CLTF
0.687
LGEELTFEXP_LGEE->PJM
CLTF
0.301
WECLTFEXP_WEC->PJM
CLTF
0.145
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
9.963
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.845
MECLTFEXP_MEC->PJM
CLTF
0.888
SIGELTFEXP_SIGE->PJM
CLTF
0.027
CPLELTFEXP_CPLE->PJM
CLTF
3.207
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.948

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.47 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:984.41
MW Contribution:15.29
Bus #Bus NameTypeMW Contribution
970531AG2-338 GEN
50/50
2.942
3146776BUCKING
Solar/Wind Harmer
4.03
3146776BUCKING
Solar/Wind Harmer
0.326
946301AF1-294 GEN
Solar/Wind Harmer
4.672
971741AH1-377 GEN
Solar/Wind Harmer
20.67
3144303KENBRDG
Solar/Wind Harmer
0.377
963041AG1-153 GEN
50/50
5.603
970285AG2-188 GEN
Solar/Wind Harmer
26.806
3147133PAMPLIN
Solar/Wind Harmer
0.603
958211AF2-115 GEN
Solar/Wind Harmer
2.849
959311AF2-222 GEN
Solar/Wind Harmer
16.226
941591AE2-156 GEN
50/50
5.885
3146926FARMVIL
Solar/Wind Harmer
0.482
3146926FARMVIL
Solar/Wind Harmer
0.482
970685AG2-442 GEN
Solar/Wind Harmer
14.615
971775AH1-396 GEN
Solar/Wind Harmer
1.131
966001AG1-469 GEN
Solar/Wind Helper
0.309
315616AA1-038_C
Solar/Wind Helper
1.093
316303AF2-085
50/50
2.185
3147043LAWRENC
50/50
0.98
3147133PAMPLIN
Solar/Wind Harmer
0.482
961791AG1-021 GEN
Solar/Wind Harmer
2.279
316192AB2-158 GEN
Solar/Wind Helper
1.356
315657AE1-056 GEN
Solar/Wind Harmer
7.237
970301AG2-198 GEN
Solar/Wind Harmer
9.831
970323AG2-213 GEN
Solar/Wind Harmer
7.539
315785AD2-033 C
Solar/Wind Harmer
0.001
970535AG2-341 GEN
50/50
5.504
972187AH1-678 GEN
50/50
2.54
315779AE2-040
50/50
1.062
3146776BUCKING
Solar/Wind Harmer
0.403
970937AG2-583 GEN
Solar/Wind Harmer
23.968
971845AH1-439 GEN
Solar/Wind Harmer
16.834
3147133PAMPLIN
Solar/Wind Harmer
1.894
316499AE2-029_GEN
Solar/Wind Helper
0.95
970119AG2-088 GEN
50/50
16.39
3146776BUCKING
Solar/Wind Harmer
0.363
963171AG1-166 GEN
Solar/Wind Harmer
2.279
962491AG1-098 GEN
Solar/Wind Harmer
5.987
970413AG2-270 GEN
50/50
15.291
316322AB2-045
Solar/Wind Harmer
0.029
972003AH1-546 GEN
Solar/Wind Harmer
19.314
972185AH1-677 GEN
50/50
4.982
944641AF1-129 GEN
50/50
18.776
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
6.356
963191AG1-168 GEN
Solar/Wind Harmer
1.709
970681AG2-440 GEN
Solar/Wind Harmer
10.44
964241AG1-285 GEN
Solar/Wind Harmer
9.945
3143336POWHATN
Solar/Wind Harmer
2.767
3143336POWHATN
Solar/Wind Harmer
2.352
971193AH1-056 GEN
Solar/Wind Harmer
12.062
970683AG2-441 GEN
Solar/Wind Harmer
13.049
963181AG1-167 GEN
Solar/Wind Harmer
1.709
970257AG2-171 GEN
Solar/Wind Harmer
5.655
972205AH1-687 GEN
50/50
22.082
970533AG2-339 GEN
50/50
7.355
971563AH1-280 GEN
Solar/Wind Harmer
2.279
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.088
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.247
LAGNLTFEXP_LAGN->PJM
CLTF
1.443
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.452
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.744
NYPJM->LTFIMP_NY
CLTF
0.685
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.518
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.233
MECLTFEXP_MEC->PJM
CLTF
0.086
CPLELTFEXP_CPLE->PJM
CLTF
3.897
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.1

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.0 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:930.64
MW Contribution:12.0
Bus #Bus NameTypeMW Contribution
970285AG2-188 GEN
Solar/Wind Harmer
24.963
3147133PAMPLIN
Solar/Wind Harmer
0.542
958211AF2-115 GEN
Solar/Wind Harmer
2.549
959311AF2-222 GEN
Solar/Wind Harmer
14.287
3146776BUCKING
Solar/Wind Harmer
3.767
3146776BUCKING
Solar/Wind Harmer
0.305
946301AF1-294 GEN
Solar/Wind Harmer
4.18
971741AH1-377 GEN
Solar/Wind Harmer
18.185
3144303KENBRDG
Solar/Wind Harmer
0.331
315657AE1-056 GEN
Solar/Wind Harmer
6.507
3146926FARMVIL
Solar/Wind Harmer
0.443
3146926FARMVIL
Solar/Wind Harmer
0.443
970685AG2-442 GEN
Solar/Wind Harmer
12.965
971775AH1-396 GEN
Solar/Wind Harmer
0.992
315616AA1-038_C
Solar/Wind Helper
1.713
966001AG1-469 GEN
Solar/Wind Helper
0.327
970301AG2-198 GEN
Solar/Wind Harmer
8.766
970323AG2-213 GEN
Solar/Wind Harmer
6.616
315785AD2-033 C
Solar/Wind Harmer
0
316303AF2-085
50/50
1.49
3147043LAWRENC
50/50
0.755
3147133PAMPLIN
Solar/Wind Harmer
0.434
961791AG1-021 GEN
Solar/Wind Harmer
2.039
316192AB2-158 GEN
Solar/Wind Helper
1.361
970535AG2-341 GEN
50/50
4.562
3146776BUCKING
Solar/Wind Harmer
0.377
970937AG2-583 GEN
Solar/Wind Harmer
22.266
971845AH1-439 GEN
Solar/Wind Harmer
15.715
3147133PAMPLIN
Solar/Wind Harmer
1.703
316499AE2-029_GEN
Solar/Wind Helper
1.238
970119AG2-088 GEN
50/50
11.178
3146776BUCKING
Solar/Wind Harmer
0.339
963171AG1-166 GEN
Solar/Wind Harmer
2.039
962491AG1-098 GEN
Solar/Wind Harmer
4.897
970413AG2-270 GEN
50/50
11.997
316322AB2-045
Solar/Wind Harmer
0.027
972003AH1-546 GEN
Solar/Wind Harmer
18.259
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
5.668
963191AG1-168 GEN
Solar/Wind Harmer
1.529
970681AG2-440 GEN
Solar/Wind Harmer
9.261
964241AG1-285 GEN
Solar/Wind Harmer
8.546
3143336POWHATN
Solar/Wind Harmer
2.42
3143336POWHATN
Solar/Wind Harmer
2.057
971193AH1-056 GEN
Solar/Wind Harmer
10.845
970683AG2-441 GEN
Solar/Wind Harmer
11.576
315760AF1-028 GEN
50/50
Charging
15.615
970117AG2-086 GEN
50/50
Charging
1.26
963181AG1-167 GEN
Solar/Wind Harmer
1.529
970257AG2-171 GEN
Solar/Wind Harmer
4.962
972205AH1-687 GEN
50/50
20.919
971563AH1-280 GEN
Solar/Wind Harmer
2.039
LAGNLTFEXP_LAGN->PJM
CLTF
2.195
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.99
TVALTFEXP_TVA->PJM
CLTF
1.148
NYPJM->LTFIMP_NY
CLTF
0.687
LGEELTFEXP_LGEE->PJM
CLTF
0.301
WECLTFEXP_WEC->PJM
CLTF
0.145
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
9.963
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.845
MECLTFEXP_MEC->PJM
CLTF
0.888
SIGELTFEXP_SIGE->PJM
CLTF
0.027
CPLELTFEXP_CPLE->PJM
CLTF
3.207
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.948

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.61 %
Rating:698.42 MVA
Rating Type:B
MVA to Mitigate:814.45
MW Contribution:20.33
Bus #Bus NameTypeMW Contribution
970531AG2-338 GEN
50/50
2.696
3146776BUCKING
Solar/Wind Harmer
7.109
3146776BUCKING
Solar/Wind Harmer
0.576
946301AF1-294 GEN
Solar/Wind Harmer
7.643
971741AH1-377 GEN
Solar/Wind Harmer
33.27
3144303KENBRDG
Solar/Wind Harmer
0.595
315693AD1-088 GEN
Solar/Wind Harmer
8.129
963041AG1-153 GEN
50/50
5.493
970285AG2-188 GEN
Solar/Wind Harmer
47.021
3147133PAMPLIN
Solar/Wind Harmer
0.996
958211AF2-115 GEN
Solar/Wind Harmer
4.66
959311AF2-222 GEN
Solar/Wind Harmer
25.764
3146926FARMVIL
Solar/Wind Harmer
0.828
3146926FARMVIL
Solar/Wind Harmer
0.828
970685AG2-442 GEN
Solar/Wind Harmer
23.537
971775AH1-396 GEN
Solar/Wind Harmer
1.784
315657AE1-056 GEN
Solar/Wind Harmer
11.951
970301AG2-198 GEN
Solar/Wind Harmer
16.15
970323AG2-213 GEN
Solar/Wind Harmer
11.895
315785AD2-033 C
Solar/Wind Harmer
0.001
3147043LAWRENC
50/50
1.216
3147133PAMPLIN
Solar/Wind Harmer
0.797
961791AG1-021 GEN
Solar/Wind Harmer
3.728
316336AC2-165 C
Solar/Wind Helper
3.444
970535AG2-341 GEN
50/50
7.8
972187AH1-678 GEN
50/50
2.49
315779AE2-040
50/50
0.838
3146776BUCKING
Solar/Wind Harmer
0.711
939181AE1-148 GEN
Solar/Wind Harmer
2.918
971845AH1-439 GEN
Solar/Wind Harmer
29.639
3147133PAMPLIN
Solar/Wind Harmer
3.127
3146776BUCKING
Solar/Wind Harmer
0.64
963171AG1-166 GEN
Solar/Wind Harmer
3.728
962491AG1-098 GEN
Solar/Wind Harmer
11.428
270494AE1-108_GEN
Solar/Wind Helper
6.761
316313AB2-026
Solar/Wind Helper
0.584
970413AG2-270 GEN
50/50
20.33
316322AB2-045
Solar/Wind Harmer
0.051
316258AE1-075 C
Solar/Wind Helper
0.526
315821AE2-092 GEN
Solar/Wind Helper
5.451
972185AH1-677 GEN
50/50
4.788
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
10.442
963191AG1-168 GEN
Solar/Wind Harmer
2.796
970681AG2-440 GEN
Solar/Wind Harmer
16.812
964241AG1-285 GEN
Solar/Wind Harmer
15.072
971193AH1-056 GEN
Solar/Wind Harmer
19.918
970683AG2-441 GEN
Solar/Wind Harmer
21.015
962561AG1-105 GEN
Solar/Wind Harmer
7.655
316405AF2-144 C
50/50
Charging
1.189
963181AG1-167 GEN
Solar/Wind Harmer
2.796
970257AG2-171 GEN
Solar/Wind Harmer
8.921
970533AG2-339 GEN
50/50
6.74
971563AH1-280 GEN
Solar/Wind Harmer
3.728
LAGNLTFEXP_LAGN->PJM
CLTF
2.469
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.083
TVALTFEXP_TVA->PJM
CLTF
1.262
NYPJM->LTFIMP_NY
CLTF
0.569
LGEELTFEXP_LGEE->PJM
CLTF
0.255
WECLTFEXP_WEC->PJM
CLTF
0.138
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.052
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.646
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.154
MECLTFEXP_MEC->PJM
CLTF
0.898
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
4.455
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.777

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.33 %
Rating:698.42 MVA
Rating Type:B
MVA to Mitigate:791.5
MW Contribution:42.69
Bus #Bus NameTypeMW Contribution
3146776BUCKING
Solar/Wind Harmer
7.855
3146776BUCKING
Solar/Wind Harmer
0.636
971741AH1-377 GEN
Solar/Wind Harmer
46.756
946301AF1-294 GEN
Solar/Wind Harmer
9.601
3144303KENBRDG
Solar/Wind Harmer
0.78
315693AD1-088 GEN
Solar/Wind Harmer
15.302
3146926FARMVIL
Solar/Wind Harmer
0.981
3146926FARMVIL
Solar/Wind Harmer
0.981
970685AG2-442 GEN
Solar/Wind Harmer
30.129
971775AH1-396 GEN
Solar/Wind Harmer
2.341
957481AF2-042 GEN
Solar/Wind Harmer
31.356
970285AG2-188 GEN
Solar/Wind Harmer
52.716
3147133PAMPLIN
Solar/Wind Harmer
1.237
958211AF2-115 GEN
Solar/Wind Harmer
5.854
959311AF2-222 GEN
Solar/Wind Harmer
33.544
315657AE1-056 GEN
Solar/Wind Harmer
14.843
970301AG2-198 GEN
Solar/Wind Harmer
21.542
970323AG2-213 GEN
Solar/Wind Harmer
15.606
315785AD2-033 C
Solar/Wind Harmer
0.001
3147043LAWRENC
50/50
1.476
971629AH1-314 GEN
50/50
5.948
3147133PAMPLIN
Solar/Wind Harmer
0.99
961791AG1-021 GEN
Solar/Wind Harmer
4.683
316336AC2-165 C
Solar/Wind Helper
2.946
970535AG2-341 GEN
50/50
11.543
3146776BUCKING
Solar/Wind Harmer
0.786
971845AH1-439 GEN
Solar/Wind Harmer
32.909
3147133PAMPLIN
Solar/Wind Harmer
3.884
3146776BUCKING
Solar/Wind Harmer
0.707
963171AG1-166 GEN
Solar/Wind Harmer
4.683
962491AG1-098 GEN
Solar/Wind Harmer
20.898
270494AE1-108_GEN
Solar/Wind Helper
5.515
316313AB2-026
Solar/Wind Helper
0.504
970413AG2-270 GEN
50/50
42.688
316322AB2-045
Solar/Wind Harmer
0.057
316258AE1-075 C
Solar/Wind Helper
0.453
315821AE2-092 GEN
Solar/Wind Helper
4.572
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
13.928
963191AG1-168 GEN
Solar/Wind Harmer
3.512
970681AG2-440 GEN
Solar/Wind Harmer
21.52
970099AG2-077 GEN
Solar/Wind Harmer
12.542
971193AH1-056 GEN
Solar/Wind Harmer
24.739
970683AG2-441 GEN
Solar/Wind Harmer
26.901
316405AF2-144 C
50/50
Charging
1.026
963181AG1-167 GEN
Solar/Wind Harmer
3.512
970257AG2-171 GEN
Solar/Wind Harmer
11.705
971563AH1-280 GEN
Solar/Wind Harmer
4.683
LAGNLTFEXP_LAGN->PJM
CLTF
3.082
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.689
TVALTFEXP_TVA->PJM
CLTF
1.577
NYPJM->LTFIMP_NY
CLTF
0.518
LGEELTFEXP_LGEE->PJM
CLTF
0.481
WECLTFEXP_WEC->PJM
CLTF
0.258
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.194
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.131
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.348
MECLTFEXP_MEC->PJM
CLTF
1.425
SIGELTFEXP_SIGE->PJM
CLTF
0.042
CPLELTFEXP_CPLE->PJM
CLTF
4.444
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.958

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.19 %
Rating:722.86 MVA
Rating Type:B
MVA to Mitigate:803.75
MW Contribution:7.54
Bus #Bus NameTypeMW Contribution
963041AG1-153 GEN
50/50
4.827
970133AG2-095 GEN
Solar/Wind Harmer
1.298
315813AE1-149 C
Solar/Wind Harmer
7.13
316083AB2-161 GEN
Solar/Wind Harmer
1.069
316311AC2-079 GEN
Solar/Wind Harmer
4.004
3145336SMITFLD
Solar/Wind Harmer
0.081
972265AH1-717 GEN
50/50
7.106
970531AG2-338 GEN
50/50
2.714
970659AG2-427 GEN
Solar/Wind Harmer
5.394
970659AG2-427 GEN
Solar/Wind Harmer
3.255
316233AE1-074 FULL
Solar/Wind Helper
0.35
944011AF1-069 GEN
Solar/Wind Harmer
2.029
944011AF1-069 GEN
Solar/Wind Harmer
2.52
941591AE2-156 GEN
50/50
5.949
971647AH1-324 GEN
Solar/Wind Harmer
4.248
316303AF2-085
50/50
Charging
1.778
3147043LAWRENC
50/50
0.689
3145336SMITFLD
Solar/Wind Harmer
0.813
316336AC2-165 C
Solar/Wind Helper
1.446
315779AE2-040
50/50
1.629
972187AH1-678 GEN
50/50
2.188
970603AG2-384 GEN
50/50
14.488
315814AE2-033 C
Solar/Wind Harmer
8.863
971211AH1-065 GEN
50/50
2.487
970119AG2-088 GEN
50/50
Charging
13.335
315652AC1-086 GEN
Solar/Wind Harmer
7.206
316313AB2-026
Solar/Wind Helper
0.329
970413AG2-270 GEN
50/50
7.54
316258AE1-075 C
Solar/Wind Helper
0.296
941031AE2-094 GEN
Solar/Wind Harmer
6.476
941031AE2-094 GEN
Solar/Wind Harmer
7.712
315697AD1-025 GEN
Solar/Wind Harmer
0
944641AF1-129 GEN
50/50
137.395
972185AH1-677 GEN
50/50
4.383
3144356SAPONY
Solar/Wind Harmer
1.204
315671AE2-027_GEN
Solar/Wind Harmer
5.491
315778AD1-151 GEN
Solar/Wind Harmer
8.057
960081AF2-299 GEN
Solar/Wind Harmer
0.756
3143316POE
Solar/Wind Harmer
1.758
970657AG2-426 GEN
Solar/Wind Harmer
3.02
970657AG2-426 GEN
Solar/Wind Harmer
2.15
971069AG2-661 GEN
Solar/Wind Harmer
5.165
316033AB2-134 GEN
Solar/Wind Harmer
0
971213AH1-066 GEN
50/50
1.244
316405AF2-144 C
50/50
Charging
0.67
970661AG2-428 GEN
Solar/Wind Harmer
5.924
965281AG1-393 GEN
Solar/Wind Harmer
1.078
970533AG2-339 GEN
50/50
6.785
970661AG2-428 GEN
Solar/Wind Harmer
9.817
LAGNLTFEXP_LAGN->PJM
CLTF
2.026
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.888
TVALTFEXP_TVA->PJM
CLTF
1.04
NYPJM->LTFIMP_NY
CLTF
0.604
LGEELTFEXP_LGEE->PJM
CLTF
0.263
WECLTFEXP_WEC->PJM
CLTF
0.137
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
8.583
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.674
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.475
MECLTFEXP_MEC->PJM
CLTF
0.825
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CPLELTFEXP_CPLE->PJM
CLTF
3.375
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.052

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.55 %
Rating:687.14 MVA
Rating Type:B
MVA to Mitigate:745.87
MW Contribution:20.35
Bus #Bus NameTypeMW Contribution
963041AG1-153 GEN
50/50
5.503
3147133PAMPLIN
Solar/Wind Harmer
0.996
958211AF2-115 GEN
Solar/Wind Harmer
4.662
959311AF2-222 GEN
Solar/Wind Harmer
25.776
3146843MT LREL
Solar/Wind Harmer
0.407
3146843MT LREL
Solar/Wind Harmer
0.407
970531AG2-338 GEN
50/50
2.701
946301AF1-294 GEN
Solar/Wind Harmer
7.646
971741AH1-377 GEN
Solar/Wind Harmer
33.284
3144303KENBRDG
Solar/Wind Harmer
0.595
315693AD1-088 GEN
Solar/Wind Harmer
8.135
315657AE1-056 GEN
Solar/Wind Harmer
11.956
3146926FARMVIL
Solar/Wind Harmer
0.828
3146926FARMVIL
Solar/Wind Harmer
0.828
970685AG2-442 GEN
Solar/Wind Harmer
23.547
971775AH1-396 GEN
Solar/Wind Harmer
1.785
957481AF2-042 GEN
Solar/Wind Harmer
7.666
3147043LAWRENC
50/50
1.217
3147133PAMPLIN
Solar/Wind Harmer
0.797
961791AG1-021 GEN
Solar/Wind Harmer
3.73
316336AC2-165 C
Solar/Wind Helper
3.441
970535AG2-341 GEN
50/50
7.806
972187AH1-678 GEN
50/50
2.495
315779AE2-040
50/50
0.84
939181AE1-148 GEN
Solar/Wind Harmer
7.432
964791AG1-342 GEN
Solar/Wind Harmer
2.934
3147133PAMPLIN
Solar/Wind Harmer
3.128
963171AG1-166 GEN
Solar/Wind Harmer
3.73
962491AG1-098 GEN
Solar/Wind Harmer
11.436
270494AE1-108_GEN
Solar/Wind Helper
6.756
316313AB2-026
Solar/Wind Helper
0.583
970413AG2-270 GEN
50/50
20.349
316322AB2-045
Solar/Wind Helper
2.037
316258AE1-075 C
Solar/Wind Helper
0.525
315821AE2-092 GEN
Solar/Wind Helper
5.447
972185AH1-677 GEN
50/50
4.797
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
10.446
963191AG1-168 GEN
Solar/Wind Harmer
2.797
970681AG2-440 GEN
Solar/Wind Harmer
16.82
964241AG1-285 GEN
Solar/Wind Harmer
15.081
970401AG2-262 GEN
Solar/Wind Harmer
0.897
971193AH1-056 GEN
Solar/Wind Harmer
19.926
970683AG2-441 GEN
Solar/Wind Harmer
21.024
962561AG1-105 GEN
Solar/Wind Harmer
7.662
970099AG2-077 GEN
Solar/Wind Harmer
3.066
970301AG2-198 GEN
Solar/Wind Harmer
16.156
970323AG2-213 GEN
Solar/Wind Harmer
11.901
315785AD2-033 C
Solar/Wind Harmer
0.001
316405AF2-144 C
50/50
Charging
1.188
963181AG1-167 GEN
Solar/Wind Harmer
2.797
970257AG2-171 GEN
Solar/Wind Harmer
8.926
970533AG2-339 GEN
50/50
6.753
971563AH1-280 GEN
Solar/Wind Harmer
3.73
LAGNLTFEXP_LAGN->PJM
CLTF
2.492
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.117
TVALTFEXP_TVA->PJM
CLTF
1.273
NYPJM->LTFIMP_NY
CLTF
0.562
LGEELTFEXP_LGEE->PJM
CLTF
0.263
WECLTFEXP_WEC->PJM
CLTF
0.142
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.052
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.808
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.196
MECLTFEXP_MEC->PJM
CLTF
0.917
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
4.467
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.926

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.24 %
Rating:687.14 MVA
Rating Type:B
MVA to Mitigate:736.92
MW Contribution:42.71
Bus #Bus NameTypeMW Contribution
3147133PAMPLIN
Solar/Wind Harmer
1.237
958211AF2-115 GEN
Solar/Wind Harmer
5.856
959311AF2-222 GEN
Solar/Wind Harmer
33.556
971741AH1-377 GEN
Solar/Wind Harmer
46.769
946301AF1-294 GEN
Solar/Wind Harmer
9.604
3144303KENBRDG
Solar/Wind Harmer
0.781
315693AD1-088 GEN
Solar/Wind Harmer
15.308
315657AE1-056 GEN
Solar/Wind Harmer
14.848
3146926FARMVIL
Solar/Wind Harmer
0.981
3146926FARMVIL
Solar/Wind Harmer
0.981
970685AG2-442 GEN
Solar/Wind Harmer
30.139
971775AH1-396 GEN
Solar/Wind Harmer
2.342
957481AF2-042 GEN
Solar/Wind Harmer
62.764
3147043LAWRENC
50/50
1.477
971629AH1-314 GEN
50/50
5.961
3147133PAMPLIN
Solar/Wind Harmer
0.99
961791AG1-021 GEN
Solar/Wind Harmer
4.685
316336AC2-165 C
Solar/Wind Helper
2.942
970535AG2-341 GEN
50/50
11.549
3147133PAMPLIN
Solar/Wind Harmer
3.885
963171AG1-166 GEN
Solar/Wind Harmer
4.685
962491AG1-098 GEN
Solar/Wind Harmer
20.906
270494AE1-108_GEN
Solar/Wind Helper
5.509
316313AB2-026
Solar/Wind Helper
0.503
970413AG2-270 GEN
50/50
42.707
316322AB2-045
Solar/Wind Helper
1.698
316258AE1-075 C
Solar/Wind Helper
0.453
315821AE2-092 GEN
Solar/Wind Helper
4.568
971193AH1-056 GEN
Solar/Wind Harmer
24.746
970683AG2-441 GEN
Solar/Wind Harmer
26.91
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
13.932
963191AG1-168 GEN
Solar/Wind Harmer
3.514
970681AG2-440 GEN
Solar/Wind Harmer
21.528
970099AG2-077 GEN
Solar/Wind Harmer
25.106
970301AG2-198 GEN
Solar/Wind Harmer
21.548
970323AG2-213 GEN
Solar/Wind Harmer
15.612
315785AD2-033 C
Solar/Wind Harmer
0.001
316405AF2-144 C
50/50
Charging
1.025
963181AG1-167 GEN
Solar/Wind Harmer
3.514
970257AG2-171 GEN
Solar/Wind Harmer
11.709
971563AH1-280 GEN
Solar/Wind Harmer
4.685
LAGNLTFEXP_LAGN->PJM
CLTF
3.105
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.723
TVALTFEXP_TVA->PJM
CLTF
1.589
NYPJM->LTFIMP_NY
CLTF
0.511
LGEELTFEXP_LGEE->PJM
CLTF
0.489
WECLTFEXP_WEC->PJM
CLTF
0.262
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.194
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.293
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.39
MECLTFEXP_MEC->PJM
CLTF
1.443
SIGELTFEXP_SIGE->PJM
CLTF
0.042
CPLELTFEXP_CPLE->PJM
CLTF
4.456
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.108

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.87 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:1012.68
MW Contribution:14.36
Bus #Bus NameTypeMW Contribution
970531AG2-338 GEN
50/50
2.734
3146776BUCKING
Solar/Wind Harmer
3.757
3146776BUCKING
Solar/Wind Harmer
0.304
946301AF1-294 GEN
Solar/Wind Harmer
4.371
971741AH1-377 GEN
Solar/Wind Harmer
19.305
963041AG1-153 GEN
50/50
5.221
970285AG2-188 GEN
Solar/Wind Harmer
24.994
3147133PAMPLIN
Solar/Wind Harmer
0.564
958211AF2-115 GEN
Solar/Wind Harmer
2.665
959311AF2-222 GEN
Solar/Wind Harmer
15.206
941591AE2-156 GEN
50/50
5.412
3146926FARMVIL
Solar/Wind Harmer
0.45
3146926FARMVIL
Solar/Wind Harmer
0.45
970685AG2-442 GEN
Solar/Wind Harmer
13.686
966001AG1-469 GEN
Solar/Wind Helper
0.334
315616AA1-038_C
Solar/Wind Helper
1.051
316303AF2-085
50/50
2.018
3147043LAWRENC
50/50
0.919
3147133PAMPLIN
Solar/Wind Harmer
0.451
961791AG1-021 GEN
Solar/Wind Harmer
2.132
316192AB2-158 GEN
Solar/Wind Helper
1.482
971489AH1-241 GEN
Solar/Wind Harmer
20.807
315657AE1-056 GEN
Solar/Wind Harmer
6.767
970301AG2-198 GEN
Solar/Wind Harmer
9.178
970323AG2-213 GEN
Solar/Wind Harmer
7.068
970535AG2-341 GEN
50/50
5.181
972187AH1-678 GEN
50/50
2.367
315779AE2-040
50/50
0.984
3146776BUCKING
Solar/Wind Harmer
0.376
966251AG1-494 GEN
50/50
3.128
970937AG2-583 GEN
Solar/Wind Harmer
22.319
971845AH1-439 GEN
Solar/Wind Harmer
15.695
3147133PAMPLIN
Solar/Wind Harmer
1.771
316499AE2-029_GEN
Solar/Wind Helper
0.927
970119AG2-088 GEN
50/50
15.136
970221AG2-151 GEN
Solar/Wind Harmer
20.807
3146776BUCKING
Solar/Wind Harmer
0.338
270494AE1-108_GEN
Solar/Wind Harmer
0
963171AG1-166 GEN
Solar/Wind Harmer
2.132
970413AG2-270 GEN
50/50
14.358
316322AB2-045
Solar/Wind Harmer
0.027
972003AH1-546 GEN
Solar/Wind Harmer
17.998
3147623JAMES R
Solar/Wind Harmer
0.542
971447AH1-217 GEN
Solar/Wind Harmer
10.898
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
972185AH1-677 GEN
50/50
4.638
944641AF1-129 GEN
50/50
25.205
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
5.934
963191AG1-168 GEN
Solar/Wind Harmer
1.599
970681AG2-440 GEN
Solar/Wind Harmer
9.775
3143336POWHATN
Solar/Wind Harmer
2.572
3143336POWHATN
Solar/Wind Harmer
2.186
971193AH1-056 GEN
Solar/Wind Harmer
11.279
970683AG2-441 GEN
Solar/Wind Harmer
12.219
315760AF1-028 GEN
50/50
Charging
11.333
971377AH1-170 GEN
Solar/Wind Harmer
4.161
963181AG1-167 GEN
Solar/Wind Harmer
1.599
970257AG2-171 GEN
Solar/Wind Harmer
0.174
972205AH1-687 GEN
50/50
20.575
970533AG2-339 GEN
50/50
6.834
971563AH1-280 GEN
Solar/Wind Harmer
2.132
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
1.646
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.434
TVALTFEXP_TVA->PJM
CLTF
0.852
NYPJM->LTFIMP_NY
CLTF
0.718
LGEELTFEXP_LGEE->PJM
CLTF
0.016
WECLTFEXP_WEC->PJM
CLTF
0.003
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.463
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.656
MECLTFEXP_MEC->PJM
CLTF
0.289
SIGELTFEXP_SIGE->PJM
CLTF
0.006
CPLELTFEXP_CPLE->PJM
CLTF
3.782
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.617

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.54 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:976.74
MW Contribution:11.15
Bus #Bus NameTypeMW Contribution
3146776BUCKING
Solar/Wind Harmer
3.491
3146776BUCKING
Solar/Wind Harmer
0.283
946301AF1-294 GEN
Solar/Wind Harmer
3.885
971741AH1-377 GEN
Solar/Wind Harmer
16.848
970285AG2-188 GEN
Solar/Wind Harmer
23.134
3147133PAMPLIN
Solar/Wind Harmer
0.504
958211AF2-115 GEN
Solar/Wind Harmer
2.369
959311AF2-222 GEN
Solar/Wind Harmer
13.304
3146926FARMVIL
Solar/Wind Harmer
0.41
3146926FARMVIL
Solar/Wind Harmer
0.41
970685AG2-442 GEN
Solar/Wind Harmer
12.063
966001AG1-469 GEN
Solar/Wind Helper
0.358
315616AA1-038_C
Solar/Wind Helper
1.725
971489AH1-241 GEN
Solar/Wind Harmer
19.574
315657AE1-056 GEN
Solar/Wind Harmer
6.045
970301AG2-198 GEN
Solar/Wind Harmer
8.122
970323AG2-213 GEN
Solar/Wind Harmer
6.163
316303AF2-085
50/50
1.328
3147043LAWRENC
50/50
0.699
3147133PAMPLIN
Solar/Wind Harmer
0.403
961791AG1-021 GEN
Solar/Wind Harmer
1.895
316192AB2-158 GEN
Solar/Wind Helper
1.52
970535AG2-341 GEN
50/50
4.269
3146776BUCKING
Solar/Wind Harmer
0.349
966251AG1-494 GEN
50/50
3.897
970937AG2-583 GEN
Solar/Wind Harmer
20.592
971845AH1-439 GEN
Solar/Wind Harmer
14.563
3147133PAMPLIN
Solar/Wind Harmer
1.582
316499AE2-029_GEN
Solar/Wind Helper
1.242
970119AG2-088 GEN
50/50
9.961
970221AG2-151 GEN
Solar/Wind Harmer
19.574
3146776BUCKING
Solar/Wind Harmer
0.314
270494AE1-108_GEN
Solar/Wind Harmer
0
963171AG1-166 GEN
Solar/Wind Harmer
1.895
970413AG2-270 GEN
50/50
11.154
316322AB2-045
Solar/Wind Harmer
0.025
972003AH1-546 GEN
Solar/Wind Harmer
16.919
3147623JAMES R
Solar/Wind Harmer
0.51
971447AH1-217 GEN
Solar/Wind Harmer
10.18
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
5.252
963191AG1-168 GEN
Solar/Wind Harmer
1.421
970681AG2-440 GEN
Solar/Wind Harmer
8.617
3143336POWHATN
Solar/Wind Harmer
2.224
3143336POWHATN
Solar/Wind Harmer
1.89
971193AH1-056 GEN
Solar/Wind Harmer
10.075
970683AG2-441 GEN
Solar/Wind Harmer
10.771
315760AF1-028 GEN
50/50
Charging
15.678
970117AG2-086 GEN
50/50
Charging
1.272
971377AH1-170 GEN
Solar/Wind Harmer
3.915
963181AG1-167 GEN
Solar/Wind Harmer
1.421
970257AG2-171 GEN
Solar/Wind Harmer
0.152
972205AH1-687 GEN
50/50
19.383
971563AH1-280 GEN
Solar/Wind Harmer
1.895
LAGNLTFEXP_LAGN->PJM
CLTF
2.588
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.28
TVALTFEXP_TVA->PJM
CLTF
1.354
NYPJM->LTFIMP_NY
CLTF
0.753
LGEELTFEXP_LGEE->PJM
CLTF
0.45
WECLTFEXP_WEC->PJM
CLTF
0.221
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.284
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.46
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.628
MECLTFEXP_MEC->PJM
CLTF
1.224
SIGELTFEXP_SIGE->PJM
CLTF
0.038
CPLELTFEXP_CPLE->PJM
CLTF
3.191
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.642

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.77 %
Rating:808.4 MVA
Rating Type:B
MVA to Mitigate:1008.61
MW Contribution:14.36
Bus #Bus NameTypeMW Contribution
970531AG2-338 GEN
50/50
2.734
3146776BUCKING
Solar/Wind Harmer
3.757
3146776BUCKING
Solar/Wind Harmer
0.304
946301AF1-294 GEN
Solar/Wind Harmer
4.371
971741AH1-377 GEN
Solar/Wind Harmer
19.305
963041AG1-153 GEN
50/50
5.221
970285AG2-188 GEN
Solar/Wind Harmer
24.994
3147133PAMPLIN
Solar/Wind Harmer
0.564
958211AF2-115 GEN
Solar/Wind Harmer
2.665
959311AF2-222 GEN
Solar/Wind Harmer
15.206
941591AE2-156 GEN
50/50
5.412
3146926FARMVIL
Solar/Wind Harmer
0.45
3146926FARMVIL
Solar/Wind Harmer
0.45
970685AG2-442 GEN
Solar/Wind Harmer
13.686
966001AG1-469 GEN
Solar/Wind Helper
0.334
315616AA1-038_C
Solar/Wind Helper
1.051
316303AF2-085
50/50
2.018
3147043LAWRENC
50/50
0.919
3147133PAMPLIN
Solar/Wind Harmer
0.451
961791AG1-021 GEN
Solar/Wind Harmer
2.132
316192AB2-158 GEN
Solar/Wind Helper
1.482
971489AH1-241 GEN
Solar/Wind Harmer
20.807
315657AE1-056 GEN
Solar/Wind Harmer
6.767
970535AG2-341 GEN
50/50
5.181
972187AH1-678 GEN
50/50
2.367
315779AE2-040
50/50
0.984
3146776BUCKING
Solar/Wind Harmer
0.376
970301AG2-198 GEN
Solar/Wind Harmer
9.178
970323AG2-213 GEN
Solar/Wind Harmer
7.068
966251AG1-494 GEN
50/50
3.128
970937AG2-583 GEN
Solar/Wind Harmer
22.319
971845AH1-439 GEN
Solar/Wind Harmer
15.695
3147133PAMPLIN
Solar/Wind Harmer
1.771
316499AE2-029_GEN
Solar/Wind Helper
0.927
970119AG2-088 GEN
50/50
15.136
970221AG2-151 GEN
Solar/Wind Harmer
20.807
3146776BUCKING
Solar/Wind Harmer
0.338
270494AE1-108_GEN
Solar/Wind Harmer
0
963171AG1-166 GEN
Solar/Wind Harmer
2.132
970413AG2-270 GEN
50/50
14.358
316322AB2-045
Solar/Wind Harmer
0.027
972003AH1-546 GEN
Solar/Wind Harmer
17.998
3147623JAMES R
Solar/Wind Harmer
0.542
971447AH1-217 GEN
Solar/Wind Harmer
10.898
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
972185AH1-677 GEN
50/50
4.638
944641AF1-129 GEN
50/50
25.205
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
5.934
963191AG1-168 GEN
Solar/Wind Harmer
1.599
970681AG2-440 GEN
Solar/Wind Harmer
9.775
3143336POWHATN
Solar/Wind Harmer
2.572
3143336POWHATN
Solar/Wind Harmer
2.186
971193AH1-056 GEN
Solar/Wind Harmer
11.279
970683AG2-441 GEN
Solar/Wind Harmer
12.219
315760AF1-028 GEN
50/50
Charging
11.333
971377AH1-170 GEN
Solar/Wind Harmer
4.161
963181AG1-167 GEN
Solar/Wind Harmer
1.599
970257AG2-171 GEN
Solar/Wind Harmer
0.174
972205AH1-687 GEN
50/50
20.575
970533AG2-339 GEN
50/50
6.834
971563AH1-280 GEN
Solar/Wind Harmer
2.132
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
1.646
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.434
TVALTFEXP_TVA->PJM
CLTF
0.852
NYPJM->LTFIMP_NY
CLTF
0.718
LGEELTFEXP_LGEE->PJM
CLTF
0.016
WECLTFEXP_WEC->PJM
CLTF
0.003
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.463
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.656
MECLTFEXP_MEC->PJM
CLTF
0.289
SIGELTFEXP_SIGE->PJM
CLTF
0.006
CPLELTFEXP_CPLE->PJM
CLTF
3.782
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.617

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.34 %
Rating:808.4 MVA
Rating Type:B
MVA to Mitigate:972.83
MW Contribution:11.15
Bus #Bus NameTypeMW Contribution
3146776BUCKING
Solar/Wind Harmer
3.491
3146776BUCKING
Solar/Wind Harmer
0.283
946301AF1-294 GEN
Solar/Wind Harmer
3.885
971741AH1-377 GEN
Solar/Wind Harmer
16.848
970285AG2-188 GEN
Solar/Wind Harmer
23.134
3147133PAMPLIN
Solar/Wind Harmer
0.504
958211AF2-115 GEN
Solar/Wind Harmer
2.369
959311AF2-222 GEN
Solar/Wind Harmer
13.304
3146926FARMVIL
Solar/Wind Harmer
0.41
3146926FARMVIL
Solar/Wind Harmer
0.41
970685AG2-442 GEN
Solar/Wind Harmer
12.063
966001AG1-469 GEN
Solar/Wind Helper
0.358
315616AA1-038_C
Solar/Wind Helper
1.725
316303AF2-085
50/50
1.328
3147043LAWRENC
50/50
0.699
3147133PAMPLIN
Solar/Wind Harmer
0.403
961791AG1-021 GEN
Solar/Wind Harmer
1.895
316192AB2-158 GEN
Solar/Wind Helper
1.52
971489AH1-241 GEN
Solar/Wind Harmer
19.574
315657AE1-056 GEN
Solar/Wind Harmer
6.045
970301AG2-198 GEN
Solar/Wind Harmer
8.122
970323AG2-213 GEN
Solar/Wind Harmer
6.163
970535AG2-341 GEN
50/50
4.269
3146776BUCKING
Solar/Wind Harmer
0.349
966251AG1-494 GEN
50/50
3.897
970937AG2-583 GEN
Solar/Wind Harmer
20.592
971845AH1-439 GEN
Solar/Wind Harmer
14.563
3147133PAMPLIN
Solar/Wind Harmer
1.582
316499AE2-029_GEN
Solar/Wind Helper
1.242
970119AG2-088 GEN
50/50
9.961
970221AG2-151 GEN
Solar/Wind Harmer
19.574
3146776BUCKING
Solar/Wind Harmer
0.314
270494AE1-108_GEN
Solar/Wind Harmer
0
963171AG1-166 GEN
Solar/Wind Harmer
1.895
970413AG2-270 GEN
50/50
11.154
316322AB2-045
Solar/Wind Harmer
0.025
972003AH1-546 GEN
Solar/Wind Harmer
16.919
3147623JAMES R
Solar/Wind Harmer
0.51
971447AH1-217 GEN
Solar/Wind Harmer
10.18
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
5.252
963191AG1-168 GEN
Solar/Wind Harmer
1.421
970681AG2-440 GEN
Solar/Wind Harmer
8.617
3143336POWHATN
Solar/Wind Harmer
2.224
3143336POWHATN
Solar/Wind Harmer
1.89
971193AH1-056 GEN
Solar/Wind Harmer
10.075
970683AG2-441 GEN
Solar/Wind Harmer
10.771
315760AF1-028 GEN
50/50
Charging
15.678
970117AG2-086 GEN
50/50
Charging
1.272
971377AH1-170 GEN
Solar/Wind Harmer
3.915
963181AG1-167 GEN
Solar/Wind Harmer
1.421
970257AG2-171 GEN
Solar/Wind Harmer
0.152
972205AH1-687 GEN
50/50
19.383
971563AH1-280 GEN
Solar/Wind Harmer
1.895
LAGNLTFEXP_LAGN->PJM
CLTF
2.588
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.28
TVALTFEXP_TVA->PJM
CLTF
1.354
NYPJM->LTFIMP_NY
CLTF
0.753
LGEELTFEXP_LGEE->PJM
CLTF
0.45
WECLTFEXP_WEC->PJM
CLTF
0.221
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.284
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.46
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.628
MECLTFEXP_MEC->PJM
CLTF
1.224
SIGELTFEXP_SIGE->PJM
CLTF
0.038
CPLELTFEXP_CPLE->PJM
CLTF
3.191
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.642

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.16 %
Rating:808.4 MVA
Rating Type:B
MVA to Mitigate:1003.7
MW Contribution:14.36
Bus #Bus NameTypeMW Contribution
970531AG2-338 GEN
50/50
2.734
3146776BUCKING
Solar/Wind Harmer
3.757
3146776BUCKING
Solar/Wind Harmer
0.304
946301AF1-294 GEN
Solar/Wind Harmer
4.371
971741AH1-377 GEN
Solar/Wind Harmer
19.305
963041AG1-153 GEN
50/50
5.221
970285AG2-188 GEN
Solar/Wind Harmer
24.994
3147133PAMPLIN
Solar/Wind Harmer
0.564
958211AF2-115 GEN
Solar/Wind Harmer
2.665
959311AF2-222 GEN
Solar/Wind Harmer
15.206
941591AE2-156 GEN
50/50
5.412
3146926FARMVIL
Solar/Wind Harmer
0.45
3146926FARMVIL
Solar/Wind Harmer
0.45
970685AG2-442 GEN
Solar/Wind Harmer
13.686
966001AG1-469 GEN
Solar/Wind Helper
0.334
315616AA1-038_C
Solar/Wind Helper
1.051
316303AF2-085
50/50
2.018
3147043LAWRENC
50/50
0.919
3147133PAMPLIN
Solar/Wind Harmer
0.451
961791AG1-021 GEN
Solar/Wind Harmer
2.132
316192AB2-158 GEN
Solar/Wind Helper
1.482
971489AH1-241 GEN
Solar/Wind Harmer
20.807
315657AE1-056 GEN
Solar/Wind Harmer
6.767
970535AG2-341 GEN
50/50
5.181
972187AH1-678 GEN
50/50
2.367
315779AE2-040
50/50
0.984
970301AG2-198 GEN
Solar/Wind Harmer
9.178
970323AG2-213 GEN
Solar/Wind Harmer
7.068
966251AG1-494 GEN
50/50
3.128
970937AG2-583 GEN
Solar/Wind Harmer
22.319
3146776BUCKING
Solar/Wind Harmer
0.376
970119AG2-088 GEN
50/50
15.136
970221AG2-151 GEN
Solar/Wind Harmer
20.807
3146776BUCKING
Solar/Wind Harmer
0.338
270494AE1-108_GEN
Solar/Wind Harmer
0
963171AG1-166 GEN
Solar/Wind Harmer
2.132
971845AH1-439 GEN
Solar/Wind Harmer
15.695
3147133PAMPLIN
Solar/Wind Harmer
1.771
316499AE2-029_GEN
Solar/Wind Helper
0.927
970413AG2-270 GEN
50/50
14.358
316322AB2-045
Solar/Wind Harmer
0.027
972003AH1-546 GEN
Solar/Wind Harmer
17.998
3147623JAMES R
Solar/Wind Harmer
0.542
971447AH1-217 GEN
Solar/Wind Harmer
10.898
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
972185AH1-677 GEN
50/50
4.638
944641AF1-129 GEN
50/50
25.205
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
5.934
963191AG1-168 GEN
Solar/Wind Harmer
1.599
970681AG2-440 GEN
Solar/Wind Harmer
9.775
3143336POWHATN
Solar/Wind Harmer
2.572
3143336POWHATN
Solar/Wind Harmer
2.186
971193AH1-056 GEN
Solar/Wind Harmer
11.279
970683AG2-441 GEN
Solar/Wind Harmer
12.219
315760AF1-028 GEN
50/50
Charging
11.333
971377AH1-170 GEN
Solar/Wind Harmer
4.161
963181AG1-167 GEN
Solar/Wind Harmer
1.599
970257AG2-171 GEN
Solar/Wind Harmer
0.174
972205AH1-687 GEN
50/50
20.575
970533AG2-339 GEN
50/50
6.834
971563AH1-280 GEN
Solar/Wind Harmer
2.132
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
1.646
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.434
TVALTFEXP_TVA->PJM
CLTF
0.852
NYPJM->LTFIMP_NY
CLTF
0.718
LGEELTFEXP_LGEE->PJM
CLTF
0.016
WECLTFEXP_WEC->PJM
CLTF
0.003
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.463
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.656
MECLTFEXP_MEC->PJM
CLTF
0.289
SIGELTFEXP_SIGE->PJM
CLTF
0.006
CPLELTFEXP_CPLE->PJM
CLTF
3.782
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.617

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.74 %
Rating:808.4 MVA
Rating Type:B
MVA to Mitigate:967.95
MW Contribution:11.15
Bus #Bus NameTypeMW Contribution
3146776BUCKING
Solar/Wind Harmer
3.491
3146776BUCKING
Solar/Wind Harmer
0.283
946301AF1-294 GEN
Solar/Wind Harmer
3.885
971741AH1-377 GEN
Solar/Wind Harmer
16.848
970285AG2-188 GEN
Solar/Wind Harmer
23.134
3147133PAMPLIN
Solar/Wind Harmer
0.504
958211AF2-115 GEN
Solar/Wind Harmer
2.369
959311AF2-222 GEN
Solar/Wind Harmer
13.304
3146926FARMVIL
Solar/Wind Harmer
0.41
3146926FARMVIL
Solar/Wind Harmer
0.41
970685AG2-442 GEN
Solar/Wind Harmer
12.063
966001AG1-469 GEN
Solar/Wind Helper
0.358
315616AA1-038_C
Solar/Wind Helper
1.725
316303AF2-085
50/50
1.328
3147043LAWRENC
50/50
0.699
3147133PAMPLIN
Solar/Wind Harmer
0.403
961791AG1-021 GEN
Solar/Wind Harmer
1.895
316192AB2-158 GEN
Solar/Wind Helper
1.52
971489AH1-241 GEN
Solar/Wind Harmer
19.574
315657AE1-056 GEN
Solar/Wind Harmer
6.045
970301AG2-198 GEN
Solar/Wind Harmer
8.122
970323AG2-213 GEN
Solar/Wind Harmer
6.163
970535AG2-341 GEN
50/50
4.269
3146776BUCKING
Solar/Wind Harmer
0.349
966251AG1-494 GEN
50/50
3.897
970937AG2-583 GEN
Solar/Wind Harmer
20.592
971845AH1-439 GEN
Solar/Wind Harmer
14.563
3147133PAMPLIN
Solar/Wind Harmer
1.582
316499AE2-029_GEN
Solar/Wind Helper
1.242
970119AG2-088 GEN
50/50
9.961
970221AG2-151 GEN
Solar/Wind Harmer
19.574
3146776BUCKING
Solar/Wind Harmer
0.314
270494AE1-108_GEN
Solar/Wind Harmer
0
963171AG1-166 GEN
Solar/Wind Harmer
1.895
970413AG2-270 GEN
50/50
11.154
316322AB2-045
Solar/Wind Harmer
0.025
972003AH1-546 GEN
Solar/Wind Harmer
16.919
3147623JAMES R
Solar/Wind Harmer
0.51
971447AH1-217 GEN
Solar/Wind Harmer
10.18
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
5.252
963191AG1-168 GEN
Solar/Wind Harmer
1.421
970681AG2-440 GEN
Solar/Wind Harmer
8.617
3143336POWHATN
Solar/Wind Harmer
2.224
3143336POWHATN
Solar/Wind Harmer
1.89
971193AH1-056 GEN
Solar/Wind Harmer
10.075
970683AG2-441 GEN
Solar/Wind Harmer
10.771
315760AF1-028 GEN
50/50
Charging
15.678
970117AG2-086 GEN
50/50
Charging
1.272
971377AH1-170 GEN
Solar/Wind Harmer
3.915
963181AG1-167 GEN
Solar/Wind Harmer
1.421
970257AG2-171 GEN
Solar/Wind Harmer
0.152
972205AH1-687 GEN
50/50
19.383
971563AH1-280 GEN
Solar/Wind Harmer
1.895
LAGNLTFEXP_LAGN->PJM
CLTF
2.588
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.28
TVALTFEXP_TVA->PJM
CLTF
1.354
NYPJM->LTFIMP_NY
CLTF
0.753
LGEELTFEXP_LGEE->PJM
CLTF
0.45
WECLTFEXP_WEC->PJM
CLTF
0.221
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.284
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.46
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.628
MECLTFEXP_MEC->PJM
CLTF
1.224
SIGELTFEXP_SIGE->PJM
CLTF
0.038
CPLELTFEXP_CPLE->PJM
CLTF
3.191
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.642

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 509T570_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.87 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:594.42
MW Contribution:34.02
Bus #Bus NameTypeMW Contribution
3146083TARBORO
Solar/Wind Harmer
0.166
3138543CONSLDL
Solar/Wind Harmer
0.102
316222AC1-221 GEN
Solar/Wind Helper
13.996
316486AD2-202 GEN
Solar/Wind Helper
1.16
316131AB2-060 GEN
Solar/Wind Helper
3.454
316294AC1-161 GEN
Solar/Wind Helper
4.209
316349AD2-085 GEN
Solar/Wind Helper
0.696
316487AF1-042 GEN
Solar/Wind Helper
0.577
270030AE2-140 GEN
Solar/Wind Harmer
10.168
316283AC2-100 C
Solar/Wind Helper
13.179
316083AB2-161 GEN
Solar/Wind Helper
0.201
316017AA1-139 ULT1
Solar/Wind Helper
0.898
316059AD1-063 C
Solar/Wind Helper
0.214
961951AG1-038 GEN
Solar/Wind Helper
0.624
970919AG2-571 GEN
Solar/Wind Harmer
15.391
961601AG1-000A GEN
Solar/Wind Harmer
2.81
961601AG1-000A GEN
Solar/Wind Harmer
3.875
316118AC1-105 GEN
Solar/Wind Helper
4.018
315666AE1-190 GEN
Solar/Wind Helper
0.287
970085AG2-068 GEN
Solar/Wind Harmer
8.927
316036AC1-147 C
Solar/Wind Helper
0.321
3142956BIRDNECK
Solar/Wind Helper
0.29
316132AB2-190 GEN1
Solar/Wind Helper
1.145
316018AA1-139 ULT2
Solar/Wind Helper
0.898
316233AE1-074 FULL
Solar/Wind Helper
0.298
3145493TOT1
Solar/Wind Harmer
0.166
3146233WITAKRS
Solar/Wind Harmer
0.102
316382AG1-145 C
Solar/Wind Helper
0.302
971629AH1-314 GEN
50/50
15.462
943811AF1-049 GEN
Solar/Wind Harmer
0
3146073TAR RVR
Solar/Wind Harmer
0.166
316003AC1-222 GEN
Solar/Wind Helper
5.211
316336AC2-165 C
Solar/Wind Helper
1.653
316375AC2-012 GEN
Solar/Wind Helper
1.755
971443AH1-215 GEN
50/50
Charging
2.844
970535AG2-341 GEN
50/50
Charging
6.525
3145543BTLEBRO
Solar/Wind Harmer
0.188
3145543BTLEBRO
Solar/Wind Harmer
0.188
3145543BTLEBRO
Solar/Wind Harmer
0.151
961671AG1-007 GEN
Solar/Wind Harmer
0.313
3145453TOT5
Solar/Wind Harmer
0.052
957601AF2-054 GEN
Solar/Wind Helper
0.286
316484AD2-074 GEN
Solar/Wind Helper
1.103
316359AB2-059 GEN
Solar/Wind Harmer
0
3142053HEARTS
Solar/Wind Harmer
0.075
971367AH1-164 GEN
Solar/Wind Harmer
1.119
3146083TARBORO
Solar/Wind Harmer
0.166
316478AD1-087 GEN
Solar/Wind Helper
3.961
3145543BTLEBRO
Solar/Wind Harmer
0.188
315773AC2-141 GEN
Solar/Wind Helper
3.897
316313AB2-026
Solar/Wind Helper
0.326
316240AF1-291 C
Solar/Wind Helper
0.313
316305AF2-043 C
Solar/Wind Helper
0.292
316156AD2-030 GEN
Solar/Wind Helper
0.284
316203AE2-005 GEN
Solar/Wind Helper
1.863
970413AG2-270 GEN
50/50
Charging
34.023
316034AC1-036 C
Solar/Wind Helper
0.557
316322AB2-045
Solar/Wind Helper
0.501
316258AE1-075 C
Solar/Wind Helper
0.293
316263AC1-034 GEN
Solar/Wind Harmer
2.844
3145573BETHELC
Solar/Wind Harmer
0.166
3145603CNETO
Solar/Wind Harmer
0.035
316237AB2-079_GEN
Solar/Wind Helper
0.88
316238AB2-078_GEN
Solar/Wind Helper
0.88
316239AB2-077_GEN
Solar/Wind Helper
0.88
315839AE2-212 C
Solar/Wind Helper
0.324
316316AC1-027 C
Solar/Wind Helper
0.259
316185AD1-033 GEN
Solar/Wind Helper
1.106
315697AD1-025 GEN
Solar/Wind Helper
2.301
315833AF1-017_GEN
Solar/Wind Helper
0.589
964211AG1-282 GEN
Solar/Wind Helper
0.27
970865AG2-541 GEN
50/50
Charging
16.223
316248AF1-058 C
Solar/Wind Helper
1.76
316123AC1-075 GEN
Solar/Wind Helper
4.3
316129AC1-054 GEN
Solar/Wind Helper
1.347
316441AF1-014 GEN
Solar/Wind Helper
0.285
316314AB2-024 C
Solar/Wind Helper
0.285
970909AG2-566 GEN
50/50
Charging
4.285
3145573BETHELC
Solar/Wind Harmer
0.166
315687AD1-152 GEN
Solar/Wind Helper
6.825
942461AE2-259 GEN
Solar/Wind Helper
3.485
957831AF2-077 GEN
Solar/Wind Helper
0.299
316072AD1-144
Solar/Wind Helper
0.222
316315AB2-025 C
Solar/Wind Helper
0.294
316075AC2-137 C
Solar/Wind Helper
0.279
970087AG2-069 GEN
Solar/Wind Harmer
13.39
970223AG2-152 GEN
Solar/Wind Harmer
8.162
971981AH1-535 GEN
Solar/Wind Harmer
2.856
3145493TOT1
Solar/Wind Harmer
0.087
315785AD2-033 C
Solar/Wind Helper
4.938
316381AD1-082 GEN
Solar/Wind Helper
1.054
316033AB2-134 GEN
Solar/Wind Helper
2.184
316369SG1_INVT
Solar/Wind Helper
1.502
316458AB2-190 GEN2
Solar/Wind Helper
1.145
319010AE1-072 C
Solar/Wind Helper
2.194
316280AD1-041 GEN
Solar/Wind Helper
0.717
3146233WITAKRS
Solar/Wind Harmer
0.595
316405AF2-144 C
Solar/Wind Helper
0.205
316236AE1-162_GEN
Solar/Wind Helper
0.315
316339AD2-160 GEN
Solar/Wind Helper
0.754
316246AF1-032 C
Solar/Wind Helper
0.219
315662AE1-191 GEN
Solar/Wind Helper
1.147
316404AE1-155 C
Solar/Wind Helper
1.741
970581AG2-369 GEN
Solar/Wind Harmer
7.677
970917AG2-570 GEN
Solar/Wind Harmer
35.706
971981AH1-535 GEN
Solar/Wind Harmer
3.116
3146233WITAKRS
Solar/Wind Harmer
0.359
313527AB2-043 GEN
Solar/Wind Helper
2.164
316159AE1-175 C
Solar/Wind Helper
0.301
316388AE2-253 GEN
Solar/Wind Helper
0.754
944201AF1-088_MTX
Adder
35.322
957141AF2-008_MTX
Adder
14.034
900033ID_568986
External Queue
3.5454747676849365
LAGNLTFEXP_LAGN->PJM
CLTF
10.551
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.334
TVALTFEXP_TVA->PJM
CLTF
5.364
NYPJM->LTFIMP_NY
CLTF
0.559
LGEELTFEXP_LGEE->PJM
CLTF
2.162
WECLTFEXP_WEC->PJM
CLTF
1.175
AG2-052LTFEXP_AG2-052->PJM
LTF
0.066
AH1-155LTFEXP_AH1-155->PJM
LTF
0.099
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
28.118
CBM West 1LTFEXP_CBM-W1->PJM
CBM
43.161
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.69
MECLTFEXP_MEC->PJM
CLTF
5.904
SIGELTFEXP_SIGE->PJM
CLTF
0.178
CPLELTFEXP_CPLE->PJM
CLTF
12.214
CBM West 2LTFEXP_CBM-W2->PJM
CBM
58.725

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-3


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.15 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:600.82
MW Contribution:33.8
Bus #Bus NameTypeMW Contribution
970919AG2-571 GEN
50/50
Charging
15.537
970531AG2-338 GEN
50/50
3.538
961601AG1-000A GEN
50/50
Charging
5.465
315693AD1-088 GEN
Solar/Wind Harmer
8.041
971741AH1-377 GEN
Solar/Wind Harmer
16.042
3144303KENBRDG
Solar/Wind Harmer
0.345
963041AG1-153 GEN
50/50
7.315
970163AG2-111 GEN
Solar/Wind Harmer
1.662
3146843MT LREL
Solar/Wind Harmer
0.742
3146843MT LREL
Solar/Wind Harmer
0.742
959311AF2-222 GEN
Solar/Wind Harmer
14.262
270197AD1-017 GEN1
Solar/Wind Helper
1.326
270574AD1-017 GEN2
Solar/Wind Helper
1.193
316420AA1-050 GEN
Solar/Wind Helper
1.199
970417AG2-272 GEN
50/50
Charging
5.345
941591AE2-156 GEN
50/50
5.817
957481AF2-042 GEN
Solar/Wind Harmer
52.946
971775AH1-396 GEN
Solar/Wind Harmer
1.034
270018AE2-047 C O1
Solar/Wind Helper
1.413
316049AB1-081 GEN
Solar/Wind Helper
1.444
970685AG2-442 GEN
Solar/Wind Harmer
6.971
971629AH1-314 GEN
50/50
Charging
15.608
3150921YORKTN3
50/50
1.678
942751AE2-291 GEN
Solar/Wind Harmer
9.796
316494AC1-189 GEN
Solar/Wind Helper
1.105
315785AD2-033 C
Solar/Wind Harmer
0.001
970323AG2-213 GEN
Solar/Wind Harmer
6.896
3147043LAWRENC
50/50
0.859
943811AF1-049 GEN
Solar/Wind Helper
3.28
316319Z2-044 C
Solar/Wind Helper
0.172
970535AG2-341 GEN
50/50
6.451
972187AH1-678 GEN
50/50
3.316
964791AG1-342 GEN
Solar/Wind Harmer
5.329
270457AD2-023 GEN
Solar/Wind Helper
2.773
3147173SINAI
Solar/Wind Harmer
0.941
3147243WELCO
Solar/Wind Harmer
0.588
970165AG2-112 GEN
Solar/Wind Harmer
1.742
270455AD2-022 GEN
Solar/Wind Helper
4.93
270336AE1-100 GEN
Solar/Wind Helper
1.52
316359AB2-059 GEN
Solar/Wind Helper
1.805
962491AG1-098 GEN
Solar/Wind Harmer
10.652
970413AG2-270 GEN
50/50
33.803
971683AH1-343 GEN
Solar/Wind Harmer
10.923
270013AE1-250 PV
Solar/Wind Helper
2.088
270016AE1-250 BESS
Solar/Wind Helper
2.088
972185AH1-677 GEN
50/50
6.349
944641AF1-129 GEN
50/50
8.974
960061AF2-297 GEN
Solar/Wind Harmer
15.055
970401AG2-262 GEN
Solar/Wind Harmer
1.628
970099AG2-077 GEN
Solar/Wind Harmer
21.178
964241AG1-285 GEN
Solar/Wind Harmer
11.266
962561AG1-105 GEN
Solar/Wind Harmer
12.558
972263AH1-716 GEN
50/50
38.484
970257AG2-171 GEN
Solar/Wind Harmer
5.172
270069AE2-166 C O1
Solar/Wind Helper
1.986
970533AG2-339 GEN
50/50
8.846
972205AH1-687 GEN
50/50
3.283
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.063
BlueGrassPJM->LTFIMP_BlueG
CLTF
6.491
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
7.441
VFTLTFEXP_VFT->PJM
CMTX
7.862
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.892
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
11.676
G-007ALTFEXP_G-007A->PJM
CMTX
2.959
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.232
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-1


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.23 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:585.98
MW Contribution:33.8
Bus #Bus NameTypeMW Contribution
970531AG2-338 GEN
50/50
3.538
961601AG1-000A GEN
50/50
Charging
5.465
315693AD1-088 GEN
Solar/Wind Harmer
8.041
971741AH1-377 GEN
Solar/Wind Harmer
16.042
3144303KENBRDG
Solar/Wind Harmer
0.345
963041AG1-153 GEN
50/50
7.315
970163AG2-111 GEN
Solar/Wind Harmer
1.662
3146843MT LREL
Solar/Wind Harmer
0.742
3146843MT LREL
Solar/Wind Harmer
0.742
959311AF2-222 GEN
Solar/Wind Harmer
14.262
270197AD1-017 GEN1
Solar/Wind Helper
1.326
270574AD1-017 GEN2
Solar/Wind Helper
1.193
316420AA1-050 GEN
Solar/Wind Helper
1.199
970417AG2-272 GEN
50/50
Charging
5.345
941591AE2-156 GEN
50/50
5.817
957481AF2-042 GEN
Solar/Wind Harmer
52.946
971775AH1-396 GEN
Solar/Wind Harmer
1.034
270018AE2-047 C O1
Solar/Wind Helper
1.413
316049AB1-081 GEN
Solar/Wind Helper
1.444
970685AG2-442 GEN
Solar/Wind Harmer
6.971
3150921YORKTN3
50/50
1.678
942751AE2-291 GEN
Solar/Wind Harmer
9.796
316494AC1-189 GEN
Solar/Wind Helper
1.105
315785AD2-033 C
Solar/Wind Harmer
0.001
970323AG2-213 GEN
Solar/Wind Harmer
6.896
971629AH1-314 GEN
50/50
Charging
15.608
3147043LAWRENC
50/50
0.859
943811AF1-049 GEN
Solar/Wind Helper
3.28
316319Z2-044 C
Solar/Wind Helper
0.172
970535AG2-341 GEN
50/50
6.451
972187AH1-678 GEN
50/50
3.316
964791AG1-342 GEN
Solar/Wind Harmer
5.329
270457AD2-023 GEN
Solar/Wind Helper
2.773
3147173SINAI
Solar/Wind Harmer
0.941
3147243WELCO
Solar/Wind Harmer
0.588
970165AG2-112 GEN
Solar/Wind Harmer
1.742
270455AD2-022 GEN
Solar/Wind Helper
4.93
270336AE1-100 GEN
Solar/Wind Helper
1.52
316359AB2-059 GEN
Solar/Wind Helper
1.805
962491AG1-098 GEN
Solar/Wind Harmer
10.652
970413AG2-270 GEN
50/50
33.803
971683AH1-343 GEN
Solar/Wind Harmer
10.923
270013AE1-250 PV
Solar/Wind Helper
2.088
270016AE1-250 BESS
Solar/Wind Helper
2.088
972185AH1-677 GEN
50/50
6.349
944641AF1-129 GEN
50/50
3.386
960061AF2-297 GEN
Solar/Wind Harmer
15.055
970401AG2-262 GEN
Solar/Wind Harmer
1.628
970099AG2-077 GEN
Solar/Wind Harmer
21.178
964241AG1-285 GEN
Solar/Wind Harmer
11.266
962561AG1-105 GEN
Solar/Wind Harmer
12.558
972263AH1-716 GEN
50/50
38.484
970257AG2-171 GEN
Solar/Wind Harmer
5.172
270069AE2-166 C O1
Solar/Wind Helper
1.986
970533AG2-339 GEN
50/50
8.846
972205AH1-687 GEN
50/50
3.283
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.063
BlueGrassPJM->LTFIMP_BlueG
CLTF
6.491
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
7.441
VFTLTFEXP_VFT->PJM
CMTX
7.862
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.892
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
11.676
G-007ALTFEXP_G-007A->PJM
CMTX
2.959
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.232
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X1_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.28 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:585.78
MW Contribution:68.07
Bus #Bus NameTypeMW Contribution
970163AG2-111 GEN
Solar/Wind Harmer
2.584
3146843MT LREL
Solar/Wind Harmer
1.148
3146843MT LREL
Solar/Wind Harmer
1.148
959311AF2-222 GEN
Solar/Wind Harmer
8.633
315693AD1-088 GEN
Solar/Wind Harmer
18.274
971741AH1-377 GEN
Solar/Wind Harmer
35.039
3144303KENBRDG
Solar/Wind Harmer
0.638
957481AF2-042 GEN
Solar/Wind Harmer
127.018
971775AH1-396 GEN
Solar/Wind Harmer
1.915
3147043LAWRENC
50/50
1.436
970535AG2-341 GEN
50/50
12.863
964791AG1-342 GEN
Solar/Wind Harmer
8.253
971443AH1-215 GEN
Solar/Wind Harmer
4.414
270457AD2-023 GEN
Solar/Wind Helper
1.534
3147173SINAI
Solar/Wind Harmer
1.371
3147243WELCO
Solar/Wind Harmer
0.857
970165AG2-112 GEN
Solar/Wind Harmer
2.709
270455AD2-022 GEN
Solar/Wind Helper
2.726
962491AG1-098 GEN
Solar/Wind Harmer
24.154
971443AH1-215 GEN
Solar/Wind Harmer
4.267
970413AG2-270 GEN
50/50
68.067
971683AH1-343 GEN
Solar/Wind Harmer
16.229
970865AG2-541 GEN
Solar/Wind Harmer
8.904
962561AG1-105 GEN
Solar/Wind Harmer
19.777
970865AG2-541 GEN
Solar/Wind Harmer
15.351
960061AF2-297 GEN
Solar/Wind Harmer
21.933
970099AG2-077 GEN
Solar/Wind Harmer
50.807
970401AG2-262 GEN
Solar/Wind Harmer
2.522
970909AG2-566 GEN
Solar/Wind Harmer
9.127
964241AG1-285 GEN
Solar/Wind Harmer
20.536
970301AG2-198 GEN
Solar/Wind Harmer
14.117
315785AD2-033 C
Solar/Wind Harmer
0.001
970323AG2-213 GEN
Solar/Wind Harmer
12.766
970257AG2-171 GEN
Solar/Wind Harmer
9.575
972205AH1-687 GEN
50/50
5.169
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.83
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.615
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.337
VFTLTFEXP_VFT->PJM
CMTX
1.251
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.788
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.864
G-007ALTFEXP_G-007A->PJM
CMTX
0.476
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.442
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X2_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.27 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:585.75
MW Contribution:68.06
Bus #Bus NameTypeMW Contribution
970163AG2-111 GEN
Solar/Wind Harmer
2.584
3146843MT LREL
Solar/Wind Harmer
1.148
3146843MT LREL
Solar/Wind Harmer
1.148
959311AF2-222 GEN
Solar/Wind Harmer
8.633
315693AD1-088 GEN
Solar/Wind Harmer
18.276
971741AH1-377 GEN
Solar/Wind Harmer
35.043
3144303KENBRDG
Solar/Wind Harmer
0.638
957481AF2-042 GEN
Solar/Wind Harmer
127.001
971775AH1-396 GEN
Solar/Wind Harmer
1.915
3147043LAWRENC
50/50
1.436
970535AG2-341 GEN
50/50
12.863
964791AG1-342 GEN
Solar/Wind Harmer
8.253
971443AH1-215 GEN
Solar/Wind Harmer
4.414
270457AD2-023 GEN
Solar/Wind Helper
1.534
3147173SINAI
Solar/Wind Harmer
1.371
3147243WELCO
Solar/Wind Harmer
0.857
970165AG2-112 GEN
Solar/Wind Harmer
2.709
270455AD2-022 GEN
Solar/Wind Helper
2.726
962491AG1-098 GEN
Solar/Wind Harmer
24.157
971443AH1-215 GEN
Solar/Wind Harmer
4.267
970413AG2-270 GEN
50/50
68.062
971683AH1-343 GEN
Solar/Wind Harmer
16.228
970865AG2-541 GEN
Solar/Wind Harmer
8.903
962561AG1-105 GEN
Solar/Wind Harmer
19.776
970865AG2-541 GEN
Solar/Wind Harmer
15.351
960061AF2-297 GEN
Solar/Wind Harmer
21.932
970099AG2-077 GEN
Solar/Wind Harmer
50.8
970401AG2-262 GEN
Solar/Wind Harmer
2.522
970909AG2-566 GEN
Solar/Wind Harmer
9.128
964241AG1-285 GEN
Solar/Wind Harmer
20.537
970301AG2-198 GEN
Solar/Wind Harmer
14.118
315785AD2-033 C
Solar/Wind Harmer
0.001
970323AG2-213 GEN
Solar/Wind Harmer
12.767
970257AG2-171 GEN
Solar/Wind Harmer
9.575
972205AH1-687 GEN
50/50
5.17
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.83
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.615
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.337
VFTLTFEXP_VFT->PJM
CMTX
1.252
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.788
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.864
G-007ALTFEXP_G-007A->PJM
CMTX
0.476
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.442
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.54 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:581.78
MW Contribution:67.43
Bus #Bus NameTypeMW Contribution
970163AG2-111 GEN
Solar/Wind Harmer
2.574
3146843MT LREL
Solar/Wind Harmer
1.146
315693AD1-088 GEN
Solar/Wind Harmer
18.549
971741AH1-377 GEN
Solar/Wind Harmer
35.543
3144303KENBRDG
Solar/Wind Harmer
0.641
957481AF2-042 GEN
Solar/Wind Harmer
124.704
971775AH1-396 GEN
Solar/Wind Harmer
1.923
3147043LAWRENC
50/50
1.438
3146843MT LREL
Solar/Wind Harmer
1.146
959311AF2-222 GEN
Solar/Wind Harmer
8.672
970535AG2-341 GEN
50/50
12.889
964791AG1-342 GEN
Solar/Wind Harmer
8.237
971443AH1-215 GEN
Solar/Wind Harmer
4.432
270457AD2-023 GEN
Solar/Wind Helper
1.544
3147173SINAI
Solar/Wind Harmer
1.366
3147243WELCO
Solar/Wind Harmer
0.854
970165AG2-112 GEN
Solar/Wind Harmer
2.698
270455AD2-022 GEN
Solar/Wind Helper
2.745
962491AG1-098 GEN
Solar/Wind Harmer
24.516
971443AH1-215 GEN
Solar/Wind Harmer
4.285
970413AG2-270 GEN
50/50
67.43
971683AH1-343 GEN
Solar/Wind Harmer
16.168
970865AG2-541 GEN
Solar/Wind Harmer
8.87
962561AG1-105 GEN
Solar/Wind Harmer
19.746
970865AG2-541 GEN
Solar/Wind Harmer
15.293
960061AF2-297 GEN
Solar/Wind Harmer
21.853
970099AG2-077 GEN
Solar/Wind Harmer
49.882
970401AG2-262 GEN
Solar/Wind Harmer
2.517
970909AG2-566 GEN
Solar/Wind Harmer
9.256
964241AG1-285 GEN
Solar/Wind Harmer
20.591
970301AG2-198 GEN
Solar/Wind Harmer
14.316
315785AD2-033 C
Solar/Wind Harmer
0.001
970323AG2-213 GEN
Solar/Wind Harmer
12.821
970257AG2-171 GEN
Solar/Wind Harmer
9.616
972205AH1-687 GEN
50/50
5.236
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.836
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.634
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.36
VFTLTFEXP_VFT->PJM
CMTX
1.294
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.8
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.898
G-007ALTFEXP_G-007A->PJM
CMTX
0.492
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.469
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.54 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:581.78
MW Contribution:67.43
Bus #Bus NameTypeMW Contribution
970163AG2-111 GEN
Solar/Wind Harmer
2.574
315693AD1-088 GEN
Solar/Wind Harmer
18.549
971741AH1-377 GEN
Solar/Wind Harmer
35.543
3144303KENBRDG
Solar/Wind Harmer
0.641
957481AF2-042 GEN
Solar/Wind Harmer
124.704
971775AH1-396 GEN
Solar/Wind Harmer
1.923
3146843MT LREL
Solar/Wind Harmer
1.146
3146843MT LREL
Solar/Wind Harmer
1.146
959311AF2-222 GEN
Solar/Wind Harmer
8.672
3147043LAWRENC
50/50
1.438
970535AG2-341 GEN
50/50
12.889
964791AG1-342 GEN
Solar/Wind Harmer
8.237
971443AH1-215 GEN
Solar/Wind Harmer
4.432
270457AD2-023 GEN
Solar/Wind Helper
1.544
3147173SINAI
Solar/Wind Harmer
1.366
3147243WELCO
Solar/Wind Harmer
0.854
970165AG2-112 GEN
Solar/Wind Harmer
2.698
270455AD2-022 GEN
Solar/Wind Helper
2.745
962491AG1-098 GEN
Solar/Wind Harmer
24.516
971443AH1-215 GEN
Solar/Wind Harmer
4.285
970413AG2-270 GEN
50/50
67.43
971683AH1-343 GEN
Solar/Wind Harmer
16.168
970865AG2-541 GEN
Solar/Wind Harmer
8.87
962561AG1-105 GEN
Solar/Wind Harmer
19.746
970865AG2-541 GEN
Solar/Wind Harmer
15.293
960061AF2-297 GEN
Solar/Wind Harmer
21.853
970099AG2-077 GEN
Solar/Wind Harmer
49.882
970401AG2-262 GEN
Solar/Wind Harmer
2.517
970909AG2-566 GEN
Solar/Wind Harmer
9.256
964241AG1-285 GEN
Solar/Wind Harmer
20.591
970301AG2-198 GEN
Solar/Wind Harmer
14.316
315785AD2-033 C
Solar/Wind Harmer
0.001
970323AG2-213 GEN
Solar/Wind Harmer
12.821
970257AG2-171 GEN
Solar/Wind Harmer
9.616
972205AH1-687 GEN
50/50
5.236
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.836
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.634
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.36
VFTLTFEXP_VFT->PJM
CMTX
1.294
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.8
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.898
G-007ALTFEXP_G-007A->PJM
CMTX
0.492
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.469
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.74 %
Rating:687.14 MVA
Rating Type:B
MVA to Mitigate:781.56
MW Contribution:20.35
Bus #Bus NameTypeMW Contribution
970531AG2-338 GEN
50/50
2.701
946301AF1-294 GEN
Solar/Wind Harmer
7.646
971741AH1-377 GEN
Solar/Wind Harmer
33.284
315693AD1-088 GEN
Solar/Wind Harmer
8.135
3146776BUCKING
Solar/Wind Harmer
-1.201
3146776BUCKING
Solar/Wind Harmer
-0.097
3144303KENBRDG
Solar/Wind Harmer
0.159
3137643SOCKMAN
Solar/Wind Harmer
0.243
3145893MURPHYS
Solar/Wind Harmer
0.19
3145893MURPHYS
Solar/Wind Harmer
0.129
3145513AHOSKIE
Solar/Wind Harmer
0.046
3145513AHOSKIE
Solar/Wind Harmer
0.046
3145963POPLR C
Solar/Wind Harmer
0.042
3145963POPLR C
Solar/Wind Harmer
0.042
3146516WINFALL
Solar/Wind Harmer
0.115
963041AG1-153 GEN
50/50
5.503
3147043LAWRENC
Solar/Wind Harmer
0.052
3138266HYDRAULIC
Solar/Wind Harmer
-0.003
3138543CONSLDL
Solar/Wind Harmer
0.032
3146173TUNIS
Solar/Wind Harmer
0.047
3146173TUNIS
Solar/Wind Harmer
0.047
3146173TUNIS
Solar/Wind Harmer
0.047
3146083TARBORO
Solar/Wind Harmer
0.045
3146376EDENTON
Solar/Wind Harmer
0.037
3146396TANGLEW
Solar/Wind Harmer
0.022
3142946ENON
Solar/Wind Harmer
0.003
3142946ENON
Solar/Wind Harmer
0.001
970685AG2-442 GEN
Solar/Wind Harmer
23.547
971775AH1-396 GEN
Solar/Wind Harmer
1.785
3146926FARMVIL
Solar/Wind Harmer
0.221
3146926FARMVIL
Solar/Wind Harmer
0.221
3146033SCOT NK
Solar/Wind Harmer
0.196
3142666NORTHAMPTON
Solar/Wind Harmer
0.029
3146233WITAKRS
Solar/Wind Harmer
0.033
3145493TOT1
Solar/Wind Harmer
0.045
3148013FISHERV
Solar/Wind Harmer
-0.045
3145933PARMELE
Solar/Wind Harmer
0.043
3146626S HERTFORD
Solar/Wind Harmer
0.036
3146626S HERTFORD
Solar/Wind Harmer
0.036
3141873WAN 176
Solar/Wind Harmer
0.003
3143873LANEXA
Solar/Wind Harmer
0.007
3142543TWELFTH
Solar/Wind Harmer
0.001
970285AG2-188 GEN
Solar/Wind Harmer
47.032
958211AF2-115 GEN
Solar/Wind Harmer
4.662
959311AF2-222 GEN
Solar/Wind Harmer
25.776
3147133PAMPLIN
Solar/Wind Harmer
0.267
3146843MT LREL
Solar/Wind Harmer
0.109
3146843MT LREL
Solar/Wind Harmer
0.109
3145683EARLEYS
Solar/Wind Harmer
0.092
3145683EARLEYS
Solar/Wind Harmer
0.046
3145273HOLLAND
Solar/Wind Harmer
0.029
3145336SMITFLD
Solar/Wind Harmer
0.011
3141766HARMONY
Solar/Wind Harmer
0.038
3141783LANCAST
Solar/Wind Harmer
0.005
3142433PROV 92
Solar/Wind Harmer
0.044
315657AE1-056 GEN
Solar/Wind Harmer
11.956
3146263WOODLND
Solar/Wind Harmer
0.05
3145893MURPHYS
Solar/Wind Harmer
0.048
3145893MURPHYS
Solar/Wind Harmer
0.048
3146516WINFALL
Solar/Wind Harmer
0.035
3146516WINFALL
Solar/Wind Harmer
0.035
3141726DUNNSVL
Solar/Wind Harmer
0.037
3141813NORNECK
Solar/Wind Harmer
0.009
970301AG2-198 GEN
Solar/Wind Harmer
16.156
970323AG2-213 GEN
Solar/Wind Harmer
11.901
315785AD2-033 C
Solar/Wind Harmer
0.001
3145593CAROLNA
Solar/Wind Harmer
0.06
3145593CAROLNA
Solar/Wind Harmer
0.06
3130156CHOWAN
Solar/Wind Harmer
0.037
3146486SUNBURY
Solar/Wind Harmer
0.035
3146486SUNBURY
Solar/Wind Harmer
0.035
3145506HICKORY
Solar/Wind Harmer
0.133
3145506HICKORY
Solar/Wind Harmer
0.08
3143316POE
Solar/Wind Harmer
0.114
3141873WAN 176
Solar/Wind Harmer
0.054
3141906WESTMOR
Solar/Wind Harmer
0.002
3147043LAWRENC
50/50
1.217
961791AG1-021 GEN
Solar/Wind Harmer
3.73
316336AC2-165 C
Solar/Wind Helper
3.441
3147133PAMPLIN
Solar/Wind Harmer
0.213
3138266HYDRAULIC
Solar/Wind Harmer
-0.002
3145683EARLEYS
Solar/Wind Harmer
0.046
3146073TAR RVR
Solar/Wind Harmer
0.045
3146206CASHIE
Solar/Wind Harmer
0.041
3146206CASHIE
Solar/Wind Harmer
0.041
3146376EDENTON
Solar/Wind Harmer
0.037
3146456SLIGO L269
Solar/Wind Harmer
0.135
3146456SLIGO L269
Solar/Wind Harmer
0.034
3145336SMITFLD
Solar/Wind Harmer
0.112
3147123OTTER R
Solar/Wind Harmer
0.015
3141766HARMONY
Solar/Wind Harmer
0.003
3142416OLDCHRC
Solar/Wind Harmer
0.008
970535AG2-341 GEN
50/50
7.806
972187AH1-678 GEN
50/50
2.495
315779AE2-040
50/50
0.84
939181AE1-148 GEN
Solar/Wind Harmer
7.432
964791AG1-342 GEN
Solar/Wind Harmer
2.934
3146776BUCKING
Solar/Wind Harmer
-0.12
3145893MURPHYS
Solar/Wind Harmer
0.048
3145543BTLEBRO
Solar/Wind Harmer
0.047
3145543BTLEBRO
Solar/Wind Harmer
0.047
3145543BTLEBRO
Solar/Wind Harmer
0.038
3146516WINFALL
Solar/Wind Harmer
0.035
3147133PAMPLIN
Solar/Wind Harmer
0.837
3147173SINAI
Solar/Wind Harmer
0.086
3147243WELCO
Solar/Wind Harmer
0.054
3146043SEABORD
Solar/Wind Harmer
0.055
3146173TUNIS
Solar/Wind Harmer
0.047
3145683EARLEYS
Solar/Wind Harmer
0.046
3146083TARBORO
Solar/Wind Harmer
0.045
3146206CASHIE
Solar/Wind Harmer
0.041
3145663CRESWEL
Solar/Wind Harmer
0.109
3146376EDENTON
Solar/Wind Harmer
0.037
3146386ELIZ CT
Solar/Wind Harmer
0.035
3146456SLIGO L269
Solar/Wind Harmer
0.034
3141783LANCAST
Solar/Wind Harmer
0.007
3142416OLDCHRC
Solar/Wind Harmer
0.003
963171AG1-166 GEN
Solar/Wind Harmer
3.73
962491AG1-098 GEN
Solar/Wind Harmer
11.436
270494AE1-108_GEN
Solar/Wind Helper
6.756
316313AB2-026
Solar/Wind Helper
0.583
3146776BUCKING
Solar/Wind Harmer
-0.108
3146263WOODLND
Solar/Wind Harmer
0.05
3145893MURPHYS
Solar/Wind Harmer
0.086
3145543BTLEBRO
Solar/Wind Harmer
0.047
3146516WINFALL
Solar/Wind Harmer
0.035
3146516WINFALL
Solar/Wind Harmer
0.035
3146406KITTY HAWK
Solar/Wind Harmer
0.001
3144536CHRHLND
Solar/Wind Harmer
0.005
970413AG2-270 GEN
50/50
20.349
316322AB2-045
Solar/Wind Helper
2.037
316258AE1-075 C
Solar/Wind Helper
0.525
3145796HORNRTN
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.173
3145746EVERETS
Solar/Wind Harmer
0.043
3145746EVERETS
Solar/Wind Harmer
0.043
3145746EVERETS
Solar/Wind Harmer
0.043
3145746EVERETS
Solar/Wind Harmer
0.043
3147312GRETNA
Solar/Wind Harmer
0.004
315821AE2-092 GEN
Solar/Wind Helper
5.447
3145783HORNRTN
Solar/Wind Harmer
0.187
3145783HORNRTN
Solar/Wind Harmer
0.023
3145796HORNRTN
Solar/Wind Harmer
0.161
3145796HORNRTN
Solar/Wind Harmer
0.156
3145796HORNRTN
Solar/Wind Harmer
0.146
3145796HORNRTN
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.047
3145823KELFORD
Solar/Wind Harmer
0.047
3145573BETHELC
Solar/Wind Harmer
0.045
316316AC1-027 C
Solar/Wind Harmer
0
3146802CHATHAM
Solar/Wind Harmer
0.014
3141913WHIT STONE
Solar/Wind Harmer
0.013
972185AH1-677 GEN
50/50
4.797
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
10.446
963191AG1-168 GEN
Solar/Wind Harmer
2.797
970681AG2-440 GEN
Solar/Wind Harmer
16.82
964241AG1-285 GEN
Solar/Wind Harmer
15.081
970401AG2-262 GEN
Solar/Wind Harmer
0.897
3145783HORNRTN
Solar/Wind Harmer
0.234
3145783HORNRTN
Solar/Wind Harmer
0.059
3145796HORNRTN
Solar/Wind Harmer
0.049
3145573BETHELC
Solar/Wind Harmer
0.045
3148133STUARTS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
0.043
3145746EVERETS
Solar/Wind Harmer
0.043
3144356SAPONY
Solar/Wind Harmer
0.166
3147312GRETNA
Solar/Wind Harmer
0.015
971193AH1-056 GEN
Solar/Wind Harmer
19.926
970683AG2-441 GEN
Solar/Wind Harmer
21.024
962561AG1-105 GEN
Solar/Wind Harmer
7.662
3143336POWHATN
Solar/Wind Harmer
-0.285
3145783HORNRTN
Solar/Wind Harmer
0.059
3145796HORNRTN
Solar/Wind Harmer
0.049
3145746EVERETS
Solar/Wind Harmer
0.043
316405AF2-144 C
50/50
Charging
1.188
963181AG1-167 GEN
Solar/Wind Harmer
2.797
970257AG2-171 GEN
Solar/Wind Harmer
8.926
3145593CAROLNA
Solar/Wind Harmer
0.017
3142666NORTHAMPTON
Solar/Wind Harmer
0.049
3142666NORTHAMPTON
Solar/Wind Harmer
0.049
3146233WITAKRS
Solar/Wind Harmer
0.193
3148013FISHERV
Solar/Wind Harmer
-0.026
3130546PLYMOUTH
Solar/Wind Harmer
0.04
3130156CHOWAN
Solar/Wind Harmer
0.037
3146626S HERTFORD
Solar/Wind Harmer
0.036
3130086AYDLETT
Solar/Wind Harmer
0.136
3145506HICKORY
Solar/Wind Harmer
0.02
3144873MCLAUGH
Solar/Wind Harmer
0.001
3138133OCRAN
Solar/Wind Harmer
0.008
970533AG2-339 GEN
50/50
6.753
971563AH1-280 GEN
Solar/Wind Harmer
3.73
3142666NORTHAMPTON
Solar/Wind Harmer
0.049
3142666NORTHAMPTON
Solar/Wind Harmer
0.049
3146233WITAKRS
Solar/Wind Harmer
0.116
3145933PARMELE
Solar/Wind Harmer
0.086
3145933PARMELE
Solar/Wind Harmer
0.043
3130156CHOWAN
Solar/Wind Harmer
0.037
3145176PASQUOTANK
Solar/Wind Harmer
0.022
3137176SLIGO L2192
Solar/Wind Harmer
0.134
3138133OCRAN
Solar/Wind Harmer
0.004
LAGNLTFEXP_LAGN->PJM
CLTF
2.492
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.117
TVALTFEXP_TVA->PJM
CLTF
1.273
NYPJM->LTFIMP_NY
CLTF
0.562
LGEELTFEXP_LGEE->PJM
CLTF
0.263
WECLTFEXP_WEC->PJM
CLTF
0.142
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.052
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.808
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.196
MECLTFEXP_MEC->PJM
CLTF
0.917
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
4.467
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.926

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.28 %
Rating:687.14 MVA
Rating Type:B
MVA to Mitigate:764.64
MW Contribution:42.71
Bus #Bus NameTypeMW Contribution
970285AG2-188 GEN
Solar/Wind Harmer
52.726
3147133PAMPLIN
Solar/Wind Harmer
1.237
958211AF2-115 GEN
Solar/Wind Harmer
5.856
959311AF2-222 GEN
Solar/Wind Harmer
33.556
971741AH1-377 GEN
Solar/Wind Harmer
46.769
946301AF1-294 GEN
Solar/Wind Harmer
9.604
3144303KENBRDG
Solar/Wind Harmer
0.781
315693AD1-088 GEN
Solar/Wind Harmer
15.308
315657AE1-056 GEN
Solar/Wind Harmer
14.848
3146926FARMVIL
Solar/Wind Harmer
0.981
3146926FARMVIL
Solar/Wind Harmer
0.981
970685AG2-442 GEN
Solar/Wind Harmer
30.139
971775AH1-396 GEN
Solar/Wind Harmer
2.342
957481AF2-042 GEN
Solar/Wind Harmer
45.223
970301AG2-198 GEN
Solar/Wind Harmer
21.548
970323AG2-213 GEN
Solar/Wind Harmer
15.612
3147043LAWRENC
50/50
1.477
971629AH1-314 GEN
50/50
5.961
3147133PAMPLIN
Solar/Wind Harmer
0.99
961791AG1-021 GEN
Solar/Wind Harmer
4.685
316336AC2-165 C
Solar/Wind Helper
2.942
970535AG2-341 GEN
50/50
11.549
3147133PAMPLIN
Solar/Wind Harmer
3.885
963171AG1-166 GEN
Solar/Wind Harmer
4.685
962491AG1-098 GEN
Solar/Wind Harmer
20.906
270494AE1-108_GEN
Solar/Wind Helper
5.509
316313AB2-026
Solar/Wind Helper
0.503
970413AG2-270 GEN
50/50
42.707
316322AB2-045
Solar/Wind Helper
1.698
316258AE1-075 C
Solar/Wind Helper
0.453
315821AE2-092 GEN
Solar/Wind Helper
4.568
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
13.932
963191AG1-168 GEN
Solar/Wind Harmer
3.514
970681AG2-440 GEN
Solar/Wind Harmer
21.528
970099AG2-077 GEN
Solar/Wind Harmer
18.089
971193AH1-056 GEN
Solar/Wind Harmer
24.746
970683AG2-441 GEN
Solar/Wind Harmer
26.91
315785AD2-033 C
Solar/Wind Harmer
0.001
316405AF2-144 C
50/50
Charging
1.025
963181AG1-167 GEN
Solar/Wind Harmer
3.514
970257AG2-171 GEN
Solar/Wind Harmer
11.709
971563AH1-280 GEN
Solar/Wind Harmer
4.685
LAGNLTFEXP_LAGN->PJM
CLTF
3.105
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.723
TVALTFEXP_TVA->PJM
CLTF
1.589
NYPJM->LTFIMP_NY
CLTF
0.511
LGEELTFEXP_LGEE->PJM
CLTF
0.489
WECLTFEXP_WEC->PJM
CLTF
0.262
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.194
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.293
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.39
MECLTFEXP_MEC->PJM
CLTF
1.443
SIGELTFEXP_SIGE->PJM
CLTF
0.042
CPLELTFEXP_CPLE->PJM
CLTF
4.456
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.108

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.02 %
Rating:687.14 MVA
Rating Type:B
MVA to Mitigate:804.11
MW Contribution:20.35
Bus #Bus NameTypeMW Contribution
970531AG2-338 GEN
50/50
2.701
946301AF1-294 GEN
Solar/Wind Harmer
7.646
971741AH1-377 GEN
Solar/Wind Harmer
33.284
3144303KENBRDG
Solar/Wind Harmer
0.595
315693AD1-088 GEN
Solar/Wind Harmer
8.135
963041AG1-153 GEN
50/50
5.503
970285AG2-188 GEN
Solar/Wind Harmer
47.032
3147133PAMPLIN
Solar/Wind Harmer
0.996
958211AF2-115 GEN
Solar/Wind Harmer
4.662
959311AF2-222 GEN
Solar/Wind Harmer
25.776
3146926FARMVIL
Solar/Wind Harmer
0.828
3146926FARMVIL
Solar/Wind Harmer
0.828
970685AG2-442 GEN
Solar/Wind Harmer
23.547
971775AH1-396 GEN
Solar/Wind Harmer
1.785
315657AE1-056 GEN
Solar/Wind Harmer
11.956
970301AG2-198 GEN
Solar/Wind Harmer
16.156
970323AG2-213 GEN
Solar/Wind Harmer
11.901
315785AD2-033 C
Solar/Wind Harmer
0.001
3147043LAWRENC
50/50
1.217
3147133PAMPLIN
Solar/Wind Harmer
0.797
961791AG1-021 GEN
Solar/Wind Harmer
3.73
316336AC2-165 C
Solar/Wind Helper
3.441
970535AG2-341 GEN
50/50
7.806
972187AH1-678 GEN
50/50
2.495
315779AE2-040
50/50
0.84
939181AE1-148 GEN
Solar/Wind Harmer
5.031
971845AH1-439 GEN
Solar/Wind Harmer
29.645
3147133PAMPLIN
Solar/Wind Harmer
3.128
963171AG1-166 GEN
Solar/Wind Harmer
3.73
962491AG1-098 GEN
Solar/Wind Harmer
11.436
270494AE1-108_GEN
Solar/Wind Helper
6.756
316313AB2-026
Solar/Wind Helper
0.583
970413AG2-270 GEN
50/50
20.349
316322AB2-045
Solar/Wind Helper
2.037
316258AE1-075 C
Solar/Wind Helper
0.525
315821AE2-092 GEN
Solar/Wind Helper
5.447
972185AH1-677 GEN
50/50
4.797
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
10.446
963191AG1-168 GEN
Solar/Wind Harmer
2.797
970681AG2-440 GEN
Solar/Wind Harmer
16.82
964241AG1-285 GEN
Solar/Wind Harmer
15.081
971193AH1-056 GEN
Solar/Wind Harmer
19.926
970683AG2-441 GEN
Solar/Wind Harmer
21.024
962561AG1-105 GEN
Solar/Wind Harmer
7.662
316405AF2-144 C
50/50
Charging
1.188
963181AG1-167 GEN
Solar/Wind Harmer
2.797
970257AG2-171 GEN
Solar/Wind Harmer
8.926
970533AG2-339 GEN
50/50
6.753
971563AH1-280 GEN
Solar/Wind Harmer
3.73
LAGNLTFEXP_LAGN->PJM
CLTF
2.492
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.117
TVALTFEXP_TVA->PJM
CLTF
1.273
NYPJM->LTFIMP_NY
CLTF
0.562
LGEELTFEXP_LGEE->PJM
CLTF
0.263
WECLTFEXP_WEC->PJM
CLTF
0.142
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.052
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.808
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.196
MECLTFEXP_MEC->PJM
CLTF
0.917
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
4.467
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.926

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.89 %
Rating:687.14 MVA
Rating Type:B
MVA to Mitigate:782.56
MW Contribution:42.71
Bus #Bus NameTypeMW Contribution
971741AH1-377 GEN
Solar/Wind Harmer
46.769
946301AF1-294 GEN
Solar/Wind Harmer
9.604
3144303KENBRDG
Solar/Wind Harmer
0.781
315693AD1-088 GEN
Solar/Wind Harmer
15.308
970285AG2-188 GEN
Solar/Wind Harmer
52.726
3146926FARMVIL
Solar/Wind Harmer
0.981
3146926FARMVIL
Solar/Wind Harmer
0.981
970685AG2-442 GEN
Solar/Wind Harmer
30.139
971775AH1-396 GEN
Solar/Wind Harmer
2.342
957481AF2-042 GEN
Solar/Wind Harmer
34.573
3147133PAMPLIN
Solar/Wind Harmer
1.237
958211AF2-115 GEN
Solar/Wind Harmer
5.856
959311AF2-222 GEN
Solar/Wind Harmer
33.556
315657AE1-056 GEN
Solar/Wind Harmer
14.848
970301AG2-198 GEN
Solar/Wind Harmer
21.548
970323AG2-213 GEN
Solar/Wind Harmer
15.612
315785AD2-033 C
Solar/Wind Harmer
0.001
3147043LAWRENC
50/50
1.477
971629AH1-314 GEN
50/50
5.961
3147133PAMPLIN
Solar/Wind Harmer
0.99
961791AG1-021 GEN
Solar/Wind Harmer
4.685
316336AC2-165 C
Solar/Wind Helper
2.942
970535AG2-341 GEN
50/50
11.549
971845AH1-439 GEN
Solar/Wind Harmer
32.915
3147133PAMPLIN
Solar/Wind Harmer
3.885
963171AG1-166 GEN
Solar/Wind Harmer
4.685
962491AG1-098 GEN
Solar/Wind Harmer
20.906
270494AE1-108_GEN
Solar/Wind Helper
5.509
316313AB2-026
Solar/Wind Helper
0.503
970413AG2-270 GEN
50/50
42.707
316322AB2-045
Solar/Wind Helper
1.698
316258AE1-075 C
Solar/Wind Helper
0.453
315821AE2-092 GEN
Solar/Wind Helper
4.568
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
13.932
963191AG1-168 GEN
Solar/Wind Harmer
3.514
970681AG2-440 GEN
Solar/Wind Harmer
21.528
970099AG2-077 GEN
Solar/Wind Harmer
13.829
971193AH1-056 GEN
Solar/Wind Harmer
24.746
970683AG2-441 GEN
Solar/Wind Harmer
26.91
316405AF2-144 C
50/50
Charging
1.025
963181AG1-167 GEN
Solar/Wind Harmer
3.514
970257AG2-171 GEN
Solar/Wind Harmer
11.709
971563AH1-280 GEN
Solar/Wind Harmer
4.685
LAGNLTFEXP_LAGN->PJM
CLTF
3.105
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.723
TVALTFEXP_TVA->PJM
CLTF
1.589
NYPJM->LTFIMP_NY
CLTF
0.511
LGEELTFEXP_LGEE->PJM
CLTF
0.489
WECLTFEXP_WEC->PJM
CLTF
0.262
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.194
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.293
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.39
MECLTFEXP_MEC->PJM
CLTF
1.443
SIGELTFEXP_SIGE->PJM
CLTF
0.042
CPLELTFEXP_CPLE->PJM
CLTF
4.456
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.108

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.47 %
Rating:698.42 MVA
Rating Type:B
MVA to Mitigate:841.42
MW Contribution:20.33
Bus #Bus NameTypeMW Contribution
970531AG2-338 GEN
50/50
2.696
3146776BUCKING
Solar/Wind Harmer
7.109
3146776BUCKING
Solar/Wind Harmer
0.576
946301AF1-294 GEN
Solar/Wind Harmer
7.643
971741AH1-377 GEN
Solar/Wind Harmer
33.27
3144303KENBRDG
Solar/Wind Harmer
0.595
315693AD1-088 GEN
Solar/Wind Harmer
8.129
963041AG1-153 GEN
50/50
5.493
970285AG2-188 GEN
Solar/Wind Harmer
47.021
3147133PAMPLIN
Solar/Wind Harmer
0.996
958211AF2-115 GEN
Solar/Wind Harmer
4.66
959311AF2-222 GEN
Solar/Wind Harmer
25.764
3146926FARMVIL
Solar/Wind Harmer
0.828
3146926FARMVIL
Solar/Wind Harmer
0.828
970685AG2-442 GEN
Solar/Wind Harmer
23.537
971775AH1-396 GEN
Solar/Wind Harmer
1.784
3147043LAWRENC
50/50
1.216
3147133PAMPLIN
Solar/Wind Harmer
0.797
961791AG1-021 GEN
Solar/Wind Harmer
3.728
316336AC2-165 C
Solar/Wind Helper
3.444
315657AE1-056 GEN
Solar/Wind Harmer
11.951
970301AG2-198 GEN
Solar/Wind Harmer
16.15
970323AG2-213 GEN
Solar/Wind Harmer
11.895
315785AD2-033 C
Solar/Wind Harmer
0.001
970535AG2-341 GEN
50/50
7.8
972187AH1-678 GEN
50/50
2.49
315779AE2-040
50/50
0.838
3146776BUCKING
Solar/Wind Harmer
0.711
971845AH1-439 GEN
Solar/Wind Harmer
29.639
3147133PAMPLIN
Solar/Wind Harmer
3.127
3146776BUCKING
Solar/Wind Harmer
0.64
963171AG1-166 GEN
Solar/Wind Harmer
3.728
962491AG1-098 GEN
Solar/Wind Harmer
11.428
270494AE1-108_GEN
Solar/Wind Helper
6.761
316313AB2-026
Solar/Wind Helper
0.584
970413AG2-270 GEN
50/50
20.33
316322AB2-045
Solar/Wind Harmer
0.051
316258AE1-075 C
Solar/Wind Helper
0.526
972003AH1-546 GEN
Solar/Wind Harmer
34.665
315821AE2-092 GEN
Solar/Wind Helper
5.451
972185AH1-677 GEN
50/50
4.788
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
10.442
963191AG1-168 GEN
Solar/Wind Harmer
2.796
970681AG2-440 GEN
Solar/Wind Harmer
16.812
964241AG1-285 GEN
Solar/Wind Harmer
15.072
971193AH1-056 GEN
Solar/Wind Harmer
19.918
970683AG2-441 GEN
Solar/Wind Harmer
21.015
962561AG1-105 GEN
Solar/Wind Harmer
3.875
316405AF2-144 C
50/50
Charging
1.189
963181AG1-167 GEN
Solar/Wind Harmer
2.796
970257AG2-171 GEN
Solar/Wind Harmer
8.921
970533AG2-339 GEN
50/50
6.74
971563AH1-280 GEN
Solar/Wind Harmer
3.728
LAGNLTFEXP_LAGN->PJM
CLTF
2.469
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.083
TVALTFEXP_TVA->PJM
CLTF
1.262
NYPJM->LTFIMP_NY
CLTF
0.569
LGEELTFEXP_LGEE->PJM
CLTF
0.255
WECLTFEXP_WEC->PJM
CLTF
0.138
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.052
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.646
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.154
MECLTFEXP_MEC->PJM
CLTF
0.898
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
4.455
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.777

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.45 %
Rating:698.42 MVA
Rating Type:B
MVA to Mitigate:813.29
MW Contribution:42.69
Bus #Bus NameTypeMW Contribution
3146776BUCKING
Solar/Wind Harmer
7.855
3146776BUCKING
Solar/Wind Harmer
0.636
971741AH1-377 GEN
Solar/Wind Harmer
46.756
946301AF1-294 GEN
Solar/Wind Harmer
9.601
3144303KENBRDG
Solar/Wind Harmer
0.78
315693AD1-088 GEN
Solar/Wind Harmer
15.302
970285AG2-188 GEN
Solar/Wind Harmer
52.716
3147133PAMPLIN
Solar/Wind Harmer
1.237
958211AF2-115 GEN
Solar/Wind Harmer
5.854
959311AF2-222 GEN
Solar/Wind Harmer
33.544
3146926FARMVIL
Solar/Wind Harmer
0.981
3146926FARMVIL
Solar/Wind Harmer
0.981
970685AG2-442 GEN
Solar/Wind Harmer
30.129
971775AH1-396 GEN
Solar/Wind Harmer
2.341
957481AF2-042 GEN
Solar/Wind Harmer
21.362
315657AE1-056 GEN
Solar/Wind Harmer
14.843
970301AG2-198 GEN
Solar/Wind Harmer
21.542
970323AG2-213 GEN
Solar/Wind Harmer
15.606
315785AD2-033 C
Solar/Wind Harmer
0.001
3147043LAWRENC
50/50
1.476
971629AH1-314 GEN
50/50
5.948
3147133PAMPLIN
Solar/Wind Harmer
0.99
961791AG1-021 GEN
Solar/Wind Harmer
4.683
316336AC2-165 C
Solar/Wind Helper
2.946
970535AG2-341 GEN
50/50
11.543
3146776BUCKING
Solar/Wind Harmer
0.786
971845AH1-439 GEN
Solar/Wind Harmer
32.909
3147133PAMPLIN
Solar/Wind Harmer
3.884
3146776BUCKING
Solar/Wind Harmer
0.707
963171AG1-166 GEN
Solar/Wind Harmer
4.683
962491AG1-098 GEN
Solar/Wind Harmer
20.898
270494AE1-108_GEN
Solar/Wind Helper
5.515
316313AB2-026
Solar/Wind Helper
0.504
970413AG2-270 GEN
50/50
42.688
316322AB2-045
Solar/Wind Harmer
0.057
316258AE1-075 C
Solar/Wind Helper
0.453
972003AH1-546 GEN
Solar/Wind Harmer
36.562
315821AE2-092 GEN
Solar/Wind Helper
4.572
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
13.928
963191AG1-168 GEN
Solar/Wind Harmer
3.512
970681AG2-440 GEN
Solar/Wind Harmer
21.52
970099AG2-077 GEN
Solar/Wind Harmer
8.545
971193AH1-056 GEN
Solar/Wind Harmer
24.739
970683AG2-441 GEN
Solar/Wind Harmer
26.901
316405AF2-144 C
50/50
Charging
1.026
963181AG1-167 GEN
Solar/Wind Harmer
3.512
970257AG2-171 GEN
Solar/Wind Harmer
11.705
971563AH1-280 GEN
Solar/Wind Harmer
4.683
LAGNLTFEXP_LAGN->PJM
CLTF
3.082
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.689
TVALTFEXP_TVA->PJM
CLTF
1.577
NYPJM->LTFIMP_NY
CLTF
0.518
LGEELTFEXP_LGEE->PJM
CLTF
0.481
WECLTFEXP_WEC->PJM
CLTF
0.258
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.194
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.131
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.348
MECLTFEXP_MEC->PJM
CLTF
1.425
SIGELTFEXP_SIGE->PJM
CLTF
0.042
CPLELTFEXP_CPLE->PJM
CLTF
4.444
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.958
CONTINGENCY 'DVP_P1-3: 6CLOUD-TX#2_SRT-A'
 OPEN BRANCH FROM BUS 313757 TO BUS 313785 CKT 2   /*3CLOUD       115.0 - 6CLOUD       230.0
END
CONTINGENCY 'DVP_P1-3: 6CLOUD-TX#1_SRT-A'
 OPEN BRANCH FROM BUS 313757 TO BUS 313785 CKT 1   /*3CLOUD       115.0 - 6CLOUD       230.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-L'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3914 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET PRECONTRATING 3880 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON      500.0 - 8MDLTHAN     500.0
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-L'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3359 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 3377 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P4-2: 509T570_SRT-A'
 OPEN BRANCH FROM BUS 314935 TO BUS 314945 CKT 1   /*8HERITAGE    500.0 - 8BRUNSWICK   500.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315102 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG1  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315103 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG2  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315104 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG3  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315105 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKS1  19.0
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 OPEN BUS 314945                                   /*8BRUNSWICK   500.0
 OPEN BUS 315102                                   /*1BRUNSWICKG1  21.0
 OPEN BUS 315103                                   /*1BRUNSWICKG2  21.0
 OPEN BUS 315104                                   /*1BRUNSWICKG3  21.0
 OPEN BUS 315105                                   /*1BRUNSWICKS1  19.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-3'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-1'
 OPEN BRANCH FROM BUS 304183 TO BUS 970084 CKT 1   /*8WAKE 500 TT 500.0 - AG2-068 TP   500.0
END
CONTINGENCY 'DVP_P4-5: 593X1_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
 OPEN BRANCH FROM BUS 313995 TO BUS 313996 CKT 1   /*8FINNEYWOOD  500.0 - 6FINNEYWOOD  230.0
END
CONTINGENCY 'DVP_P4-5: 593X2_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
 OPEN BRANCH FROM BUS 313995 TO BUS 313996 CKT 2   /*8FINNEYWOOD  500.0 - 6FINNEYWOOD  230.0
END
CONTINGENCY 'DVP_P4-2: H1T593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313986 CKT 1   /*8UNITY       500.0 - 6UNITY       230.0
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P4-2: H2T593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313986 CKT 2   /*8UNITY       500.0 - 6UNITY       230.0
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
313757 to 313785 ckt 1
313757 to 313785 ckt 2
314747 to 313867 ckt 1
313867 to 313707 ckt 1
314677 to 972002 ckt 1
314287 to 314276 ckt 1
314692 to 970284 ckt 1
313707 to 313373 ckt 1
313373 to 314765 ckt 1
314765 to 314749 ckt 1
304070 to 316281 ckt 1
316281 to 304070 ckt 1
970284 to 971844 ckt 1
971844 to 314677 ckt 1
972002 to 314747 ckt 1

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-038Lexington-Low Moor 230kVUnder Construction
AA1-050Tarboro-Everetts 230kVIn Service
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-067Everetts 34.5kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-057Hornertown-Whitakers 115kVIn Service
AA2-174Carolina-Jackson 115kVIn Service
AA2-178Mackeys 230kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-132Thelma 230kVIn Service
AB2-022Elizabeth City 34.5kVIn Service
AB2-024Correctional 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-031Brink-Trego 115kVIn Service
AB2-040Brink 115kVIn Service
AB2-043Chase City 115kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-134Hopewell-Surry 230kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-169Pantago-Five Points 115kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVSuspended
AC1-036Twittys Creek 34.5kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-086Thelma 230kVSuspended
AC1-098Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-099Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-145Gretna DP 69 kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-191Elmont 115kVEngineering & Procurement
AC1-208Cox-Whitakers 115kVUnder Construction
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-079Ivor-Oak Ridge 115kVSuspended
AC2-100Halifax-Person 230kVIn Service
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-165Bremo-Powhatan 230kVSuspended
AD1-017Smith Mountain-Bearskin 138 kVIn Service
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVUnder Construction
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-063Harmony Village 34.5 kVIn Service
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-088Briery-Clover 230 kVSuspended
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-144Kings Fork 34.5 kVIn Service
AD1-151Hopewell-Surry 230 kVSuspended
AD1-152Clover-Sedge Hill 230 kVIn Service
AD2-022East Danville - Roxborough 230 kVEngineering & Procurement
AD2-023East Danville - Roxborough 230 kVEngineering & Procurement
AD2-030Wan 34.5 kVIn Service
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVEngineering & Procurement
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-160Hickory-Moyock 230kVIn Service
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-056Red House-South Creek 115 kVWithdrawn
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-100Axton 138 kVIn Service
AE1-103Holland-Union Camp 115 kVUnder Construction
AE1-108Bremo-Scottsville 138 kVEngineering & Procurement
AE1-148Kerr Dam-Ridge Rd 115 kVActive
AE1-149Disputanta-Poe 115 kVSuspended
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-157Ladysmith CT-St. Johns 230 kVSuspended
AE1-162Smithfield 34.5 kVIn Service
AE1-173Carson-Suffolk 500 kVUnder Construction
AE1-175Light Foot 34.5 kVIn Service
AE1-190Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-191Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-250Smith Mountain-E. Danville 138 kVEngineering & Procurement
AE2-005Harmony Village-Shackleford 115 kVUnder Construction
AE2-027Harrowgate-Locks 115kVUnder Construction
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-033Clubhouse-Sapony 230 kVSuspended
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-040Sapony 34.5 kVPartially in Service - Under Construction
AE2-047Ridgeway-Solite 69 kVEngineering & Procurement
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-094Carson-Rogers Road 500 kVEngineering & Procurement
AE2-104Suffolk 115 kVSuspended
AE2-140Axton-Danville 138 kVSuspended
AE2-156Yadkin 115 kVActive
AE2-166Stockton 138 kVSuspended
AE2-183Rogers Road 500 kVIn Service
AE2-185Gladys DP-Stonemill Switching Station 69 kVActive
AE2-187Shockoe DP-Chatham 69 kVActive
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-253Hickory-Moyock 230 kVIn Service
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVActive
AE2-291Grit DP-Perth 115 kVActive
AE2-346Ahoskie 34.5 kVIn Service
AF1-014Harmony Village-Shackleford 115 kVUnder Construction
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-028Endless Caverns 115 kVUnder Construction
AF1-032Suffolk 34.5 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-049Berry Hill 138 kVUnder Construction
AF1-058Welco 34.5 kVIn Service
AF1-069Carson-Rogers Rd 500 kVEngineering & Procurement
AF1-088Sullivan 345 kVActive
AF1-123Harper 230 kVActive
AF1-124Harper 230 kVActive
AF1-125Harper 230 kVActive
AF1-128Chesterfield 230 kVActive
AF1-129Chesterfield 230 kVEngineering & Procurement
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-292Fields 34.5kVEngineering & Procurement
AF1-294Jetersville-Ponton 115 kVActive
AF2-008Sullivan 345 kVActive
AF2-035St. Johns 115 kVActive
AF2-042Clover-Rawlings 500 kVActive
AF2-043Suffolk 34.5 kVIn Service
AF2-046Tunis-Mapleton 115 kVActive
AF2-054Wan 34.5 kVIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-080Chinquapin-Everetts 230 kVActive
AF2-081Moyock 230 kVActive
AF2-085Midlothian 34.5 kVIn Service
AF2-107Clifford 138 kVEngineering & Procurement
AF2-110Suffolk 115 kVSuspended
AF2-115Jetersville-Ponton 115 kVActive
AF2-120Garner-Northern Neck 115 kVActive
AF2-144Powhatan 34.5 kVIn Service
AF2-222Madisonville DP-Twitty's Creek 115 kVActive
AF2-297Sedge Hill 115 kVActive
AF2-299Fields 34.5 kVActive
AG1-007Tar River 12.5 kVEngineering & Procurement
AG1-008Tunis-Mapleton 115 kVActive
AG1-021Jetersville-Ponton 115 kVActive
AG1-037Ahoskie 34.5 kVEngineering & Procurement
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-082Ahoskie 34.5 kVActive
AG1-098Briery-Clover 230 kVActive
AG1-105Mount Laurel-Barnes Junction 115 kVActive
AG1-106Thelma 230 kVActive
AG1-124Gladstone 138 kVActive
AG1-135Garner-Lancaster 115 kVActive
AG1-145Lightfoot 34.5 kVIn Service
AG1-146Garner DP-Lancaster 115 kVActive
AG1-147Garner DP-Lancaster 115 kVActive
AG1-153Heritage 500 kVActive
AG1-166Lone Pine 115 kVActive
AG1-167Lone Pine 115 kVActive
AG1-168Lone Pine 115 kVActive
AG1-282Dunnsville 34.5 kVEngineering & Procurement
AG1-285Chase City-Central 115 kVActive
AG1-342Dryburg 115 kVActive
AG1-393Sapony 34.5 kVActive
AG1-394Boykins 34.5 kVActive
AG1-469Gordonsville 34.5 kVEngineering & Procurement
AG1-494Boxwood-Riverville 138 kVActive
AG1-532Fields 34.5 kVEngineering & Procurement
AG1-551Parmele 34.5 kVActive
AG1-552Carolina 34.5 kVActive
AG1-558Buckner 34.5 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
AG2-005Garner DP-Lancaster 115 kVActive
AG2-068Heritage - Wake 500 kVActive
AG2-069Heritage - Wake 500 kVActive
AG2-077Clover-Rawlings 500 kVActive
AG2-086Mt. Jackson DP-Mt. Jackson 115 kVActive
AG2-088Midlothian 230 kVActive
AG2-093Colonial Trail-Hopewell 230 kVActive
AG2-095Hopewell 34.5 kV (Circuit 313)Active
AG2-111Perth 34.5 kV Substation (Circuit 408)Active
AG2-112Perth 34.5 kV Substation (Circuit 404)Active
AG2-120Everetts 34.5 kVActive
AG2-124Shackleford-Harmony 115 kVActive
AG2-151Trices Lake - James River Tap 115 kVActive
AG2-152Banister-Bear Skin 138 kVActive
AG2-171Lunenburg-Nutbush 115 kVActive
AG2-188Farmville - Buckingham 230 kVActive
AG2-193Turner 34.5 kVActive
AG2-198Briery - Finneywood 230 kVActive
AG2-208Greenwood DP - St. Johns DP 115 kVActive
AG2-213Gary D.P Tap - Gary D.P 115 kVActive
AG2-215Garner DP-Lancaster 115 kVActive
AG2-262Dryburg 115 kVActive
AG2-272Berry Hill 138 kVActive
AG2-338Rogers Road - Carson 500 kVActive
AG2-339Rogers Road - Carson 500 kVActive
AG2-341Ridge Road 115 kVActive
AG2-369Heritage - Wake 500 kVActive
AG2-382Cashie 230 kVActive
AG2-384Chesterfield 230 kVActive
AG2-426Wakefield - Waverly 115 kVActive
AG2-427Waverly 115 kVActive
AG2-428Wakefield 115 kVActive
AG2-436Carson - Rogers Road 500 kVActive
AG2-440Twittys Creek - Madisonville 115 kVActive
AG2-441Twittys Creek - Madisonville 115 kVActive
AG2-442Twittys Creek - Madisonville 115 kVActive
AG2-522Five Forks DP 115 kVActive
AG2-541Perth - Crystal Hill 115 kVActive
AG2-566Briery - Finneywood 230 kVActive
AG2-570Heritage - Wake 500 kVActive
AG2-571Heritage - Wake 500 kVActive
AG2-581Rawlings-Clover 500 kVActive
AG2-583Bremo - Cartersville 230 kVActive
AG2-659Kerr Dam – Hawtree 115 kVActive
AG2-661Hopewell - Colonial Trail 230 kVActive
AH1-033Sligo 34.5 kVActive
AH1-035Plymouth 34.5 kVActive
AH1-040Mackeys - Creswell 115 kVActive
AH1-042Providence Forge-Turner 115kVActive
AH1-056Red House DP 115kVActive
AH1-065Hopewell 34.5kVActive
AH1-066Hopewell 34.5kVActive
AH1-071Midlothian 34.5 kVActive
AH1-106Winterpock 34.5kVActive
AH1-107Winterpock 34.5kVActive
AH1-108Spruance NUG 230 kVActive
AH1-138Penniman 34.5 kVActive
AH1-164Oak Level - Tank Hill 138 kVActive
AH1-170Columbia DP 115kVActive
AH1-215Central VA-Twitty 115 kVActive
AH1-216Smithfield-Surry 230 kVActive
AH1-217Kidds Store - Fork Union 115 kV IIActive
AH1-221Heritage 500 kVActive
AH1-241Cobbs Creek - James River Industrial 115kVActive
AH1-271Cashie 230 kVActive
AH1-280Jetersville-Ponton 115 kVActive
AH1-311Heartsease DP - Mayo Dunbar 115kVActive
AH1-314East Danville 138 kVActive
AH1-324Colonial Trail – Surry 230 kVActive
AH1-343Crystal Hill DP- Perth 115kVActive
AH1-377Clover- Farmville 230kVActive
AH1-396Gary 24.94 kVActive
AH1-397Shacklesford 34.5 kVActive
AH1-408Freeman DP – Lawrenceville 115 kVActive
AH1-439Buckingham- Farmville 230kVActive
AH1-528Rawlings - Unity 500 kVActive
AH1-535Nagel - Cane River 230 kVActive
AH1-546Bremo - Buckingham 230 kVActive
AH1-677Rogers Road 500 kVActive
AH1-678Heritage 500 kVActive
AH1-679Four Rivers 230 kVActive
AH1-687Bear Garden 230kVActive
AH1-716Surry-Skiffes Creek 500kVActive
AH1-717Surry 230kVActive
V4-068Murphy's 34.5kVIn Service
Y1-086Morgans CornerIn Service
Z1-036WinFall-Chowan 230kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-044Whitakers 34.5kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)Identified Impacts

No cost allocated AFS Tie Line reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.


System Reinforcement
Type
Load Flow
TO
CPLE
RTEP ID / TO ID
(Pending) / TC2-CPLE-0001
Title
Person - VP Hendrick 230kV Line (Existing Line Uprate)
Description
Currently no costs since there is already a DEP project to reconductor to upgrade this line. This is the estimated ISD for the current project CPLE is developing. The Person - Hendrick 230 kV line will be reconductored with bundled 795 ACSS/TW and will have a rating 1195MVA.
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
0 to 48 Months

Info

Note: AG2-270 contributes to the loading of an overloaded tie line facility between PJM and an affected system entity, which was identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line and will be confirmed in subsequent study phases, along with cost allocation of such upgrade if applicable, in coordination with the affected system.

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
CPLE
RTEP ID / TO ID
(Pending) / TC2-CPLE-0002
Title
Person - VP Hendrick 230kV line (New Line)
Description
This project is to add second line that would be built to 1195MVA. Assumed ~5 mile 230kV line with bundled conductor and can utilize last remaining CB bay at Person (no fence expansion). Estimated ISD Assumed 5 years from Kick off to complete work (Site & acquire ROW, engineering, construction) and assuming no other outage constraints (DEP or PJM) from previous projects already planned. The new line will also be bundled 795 ACSS/TW.
Total Cost ($USD)
$28,300,000
Allocated Cost ($USD)
$0
Time Estimate
0 to 60 Months

Info

Note: AG2-270 contributes to the loading of an overloaded tie line facility between PJM and an affected system entity, which was identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line and will be confirmed in subsequent study phases, along with cost allocation of such upgrade if applicable, in coordination with the affected system.

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)

Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Study Pending
Duke Energy Progress – East (CPLE)Study Pending
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase I analysis results, this project may have a cost responsibility for the following System Reinforcements:

AG2-270 System Reinforcements:
TORTEP IDTitleAllocated Cost ($USD)
Dominion(Pending) / TC2-PH1-DOM-1031Wreck and rebuild 12.94 miles of 230 kV Line 235 from Briery to Farmville with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 degrees C.$6,140,173
Dominionn6215Wreck and rebuild 18.56 miles of 230 kV Line 296 between Sedge Hill and Alton Post (AC1-221) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.$6,014,792
Dominionn9376.0 / TC1-PH3-DOM-003-TC2Wreck and Rebuild 22.98 miles of 230 kV Line 235 from Briery to AG1-098 with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"" at 250 C.$5,231,403
Dominion(Pending) / TC2-PH1-DOM-2092Replace the existing Finneywood 230/500 kV XFRM T2 with a 3-480 MVA rated device$4,228,366
Dominion(Pending) / TC2-PH1-DOM-2091Replace the existing Finneywood 230/500 kV XFRM T1 with a 3-480 MVA rated device$4,228,310
Dominion(Pending) / TC2-PH1-DOM-0045Wreck and rebuild 8.3 miles of 230 kV Line 2250 between Edmonson and Sedge Hill with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.$2,844,056
Dominionn7796 / dom-302/3Wreck and rebuild 14.01 miles of 230 kV Line 2027 between Midlothian and Powhatan with (2) 768.2 ACSS/TW (20/7) "MAUMEE".$1,672,909
Dominionn7568 / dom-369-TC2Wreck and rebuild 6.47 miles of 230 kV transmission line 2028 between Charlottesville and Mt. Eagle with (2) 768.2 ACSS/TW (20/7) ""Maumee"" @ 250C and replace line lead at Mt. Eagle.$1,346,206
Dominion(Pending) / TC1-PH2-DOM-0012Wreck and rebuild 8.1 miles of 230 kV Line 2027 (future Line 2323) between Bremo and AG2-583 with (2) 768.2 ACSS/TW (20/7) "MAUMEE".$1,107,594
Dominionn9203.0 / TC1-PH2-DOM-008-TC2Wreck and rebuild 10.74 miles of line 2028 between Fork Union and Cunningham (Grape Vine) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C.$1,103,455
Dominion(Pending) / TC1-PH1-DOM-006Add a 3rd new 224 MVA 115/230 kV Transformer at Cloud substation, one (1) 230 kV breaker and one (1) 115 kV breaker.$816,814
Dominionn8256 / dom-277Wreck and rebuild 5.9 miles of 230 kV Line 2027 (future Line 2323) between Cartersville and AC2-165 (Sallee Creek) with (2) 768.2 ACSS/TW (20/7) "MAUMEE".$706,892
Dominionn8243 / dom-389Wreck and rebuild 5.8 miles of 230 kV Line 2027 between AC2-165 (Sallee Creek) and Powhatan with (2) 768.2 ACSS/TW (20/7) "MAUMEE".$693,450
Dominionn7569 / dom-490-TC2Upgrade a 3.78 mile segment of 230kV transmission line 2028 between Mt. Eagle and Grape Vine Substations at structure 2080/73.$488,713
Dominionn9644.0 / TC1-PH3-DOM-006-TC2Upgrade a 2.73 mile segment of 230kV transmission line 2028 between Mt. Eagle and Grape Vine. This segment runs from Grape Vine substation to structure 2080/73.$307,832
Dominion(Pending) / TC2-PH1-DOM-2043Wreck and rebuild 0.93 miles of 230 kV Line 2241 between Hendrick and Persons with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Dominion portion of line only.$203,423
Dominion(Pending) / TC2-PH1-DOM-0013Wreck and rebuild 1.51 miles of 230 kV Line 2027 (future Line 2323) between Cartersville and AG2-583 with (2) 768.2 ACSS/TW (20/7) "MAUMEE".$180,916
Dominion(Pending) / TC2-PH1-DOM-2008Wreck and rebuild 0.47 miles of 230 kV Line 2241 between Hendrick and Alton Post with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.$152,347
Dominion(Pending) / TC2-PH1-DOM-1032Wreck and rebuild 0.73 miles of 230 kV line 235 between AG1-098 and Finneywood with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C$94,621
Dominionn9198.0 / TC1-PH2-DOM-003-TC2Replace Circuit Breaker 219322 and Circuit Breaker Lead at Bremo 230 kV (Bremo - Fork Union).$82,279
Dominionn9221.0 / TC1-PH3-DOM-015-TC2Replace 230 kV Breaker 29822 at Bremo with a higher-rated device (Buckingham - Bremo).$80,033
Dominion(Pending) / TC2-PH1-DOM-2065Replace switches 219324 and 219325 at Bremo 230 kV$31,138
Dominion(Pending) / TC2-PH1-DOM-2077Replace switches 29824 and 29825 at Bremo 230 kV$31,121
Dominion(Pending) / TC2-PH1-DOM-2087Replace 2-1590 AAC 61 line lead on line 298 at Farmville 230 kV$28,019
Dominion(Pending) / TC2-PH1-DOM-2086Replace 3 1/2' AL Pipe line lead on line 298 at Farmville 230 kV$28,019
Dominionn9205.0 / TC1-PH2-DOM-015Replace Line Switch 23889 at Sapony 230 kV (Sapony - AE2-033 Tap)$27,336
Dominionn9202.0 / TC1-PH2-DOM-007Replace Line Switch 23886 at Sapony 230 kV (Carson - Sapony).$27,316
Dominion(Pending) / TC2-PH1-DOM-2085Replace wavetrap 298WT at Farmville 230 kV$24,400
Dominion(Pending) / TC2-PH1-DOM-2079Replace 3 1/2 " AL Pipe line lead on line 298 at Bremo 230 kV$21,185
Dominion(Pending) / TC2-PH1-DOM-0014Wreck and rebuild 0.17 miles of 230 kV Line 2027 between Midlothian and Powhatan with (2) 768.2 ACSS/TW (20/7) "MAUMEE".$20,299
Dominion(Pending) / TC2-PH1-DOM-2078Replace 2-636 ACSR line lead on line 298 at Bremo 230 kV$19,451
Dominion(Pending) / TC2-PH1-DOM-2072Replace 2500 ACAR line lead on line 2028 at Charlottesville 230 kV$18,290
Dominion(Pending) / TC2-PH1-DOM-2068Wreck and rebuild 0.12 miles of 230 kV line 2028 between Fork Union and Grape Vine with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C$17,034
Dominion(Pending) / TC2-PH1-DOM-2067Replace 3 1/2" pipe line lead on line 2193 at Bremo 230 kV$16,409
Dominion(Pending) / TC2-PH1-DOM-2066Replace 2-636 ACSR line lead on line 2193 at Bremo 230 kV$16,409
Dominion(Pending) / TC2-PH1-DOM-2064Replace 2-1590 line lead on line 2193 at Fork Union 230 kV$16,409
Dominion(Pending) / TC2-PH1-DOM-2063Wreck and rebuild 0.11 miles of 230 kV line 2193 between Fork Union and Bremo Dist with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C$16,270
Dominion(Pending) / TC2-PH1-DOM-0080Replace switch 219326 at Bremo 230 kV$15,569
Dominion(Pending) / TC2-PH1-DOM-2076Replace wave trap 298 WT at Bremo 230 kV$15,561
Dominion(Pending) / TC2-PH1-DOM-2070Replace wave trap 2028WT at Fork Union 230 kV$14,942
Dominion(Pending) / TC2-PH1-DOM-2069Replace 2-1590 AAC line lead on line 2028 at Fork Union 230 kV$14,911
Dominion(Pending) / TC2-PH1-DOM-2073Replace 2-1590 line lead on line 2028 at Charlottesville and Mt Eagle 230 kV$14,663
Dominion(Pending) / TC2-PH1-DOM-2071Replace 2-1590 line lead on line 2028 at Mt. Eagle 230 kV$14,663
Dominion(Pending) / TC1-PH3-DOM-007Replace Wave Trap 2028WT at Charlottesville$14,632
Dominion(Pending) / TC2-PH1-DOM-0051Wreck and rebuild 0.003 miles of 230 kV Line 296 between Sedge Hill and Alton Post (AC1-221) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.$972
Grand Total:$38,189,602

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-1031
Title
Wreck and rebuild 12.94 miles of 230 kV Line 235 from Briery to Farmville with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 degrees C.
Description
Wreck and rebuild 12.94 miles of 230 kV Line 235 from Briery to Farmville with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 degrees C.
Total Cost ($USD)
$49,172,000
Allocated Cost ($USD)
$6,140,173
Time Estimate
42 to 48 Months

Contributor

FacilityContingency
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-077
36.3 MW15.4%$7,591,871
AG2-198
25.4 MW10.8%$5,309,855
AG2-270
29.4 MW12.5%$6,140,173
AG2-566
6.3 MW2.7%$1,327,464
AG2-581
27.9 MW11.8%$5,826,660
AH1-377
54.1 MW23.0%$11,322,866
AH1-528
55.7 MW23.7%$11,653,111

System Reinforcement: n6215
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n6215
Title
Wreck and rebuild 18.56 miles of 230 kV Line 296 between Sedge Hill and Alton Post (AC1-221) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 18.56 miles of 230 kV Line 296 between Sedge Hill and Alton Post (AC1-221) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$70,528,000
Allocated Cost ($USD)
$6,014,792
Time Estimate
42 to 48 Months

Contributor

FacilityContingency
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-077
67.9 MW12.3%$8,657,819
AG2-171
13.1 MW2.4%$1,668,999
AG2-188
21.5 MW3.9%$2,735,027
AG2-198
19.5 MW3.5%$2,484,894
AG2-213
17.5 MW3.2%$2,225,332
AG2-270
47.2 MW8.5%$6,014,792
AG2-440
21.4 MW3.9%$2,727,254
AG2-441
26.8 MW4.8%$3,409,100
AG2-442
30.0 MW5.4%$3,818,131
AG2-541
19.1 MW3.4%$2,432,523
AG2-566
3.7 MW0.7%$471,851
AG2-581
50.2 MW9.1%$6,402,670
AG2-659
11.4 MW2.1%$1,448,938
AH1-056
20.7 MW3.7%$2,641,116
AH1-343
22.0 MW4.0%$2,806,257
AH1-377
48.4 MW8.7%$6,169,230
AH1-439
12.4 MW2.2%$1,574,323
AH1-528
100.8 MW18.2%$12,839,745

System Reinforcement: n9376.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9376.0 / TC1-PH3-DOM-003-TC2
Title
Wreck and Rebuild 22.98 miles of 230 kV Line 235 from Briery to AG1-098 with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"" at 250 C.
Description
Wreck and Rebuild 22.98 miles of 230 kV Line 235 from Briery to AG1-098 with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"" at 250 C.
Total Cost ($USD)
$69,323,785
Allocated Cost ($USD)
$5,231,403
Time Estimate
Dec 31 2029

Contributor

FacilityContingency
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line(Any)
AG2-198 TP-AH1-377 TP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-077
108.9 MW9.3%$6,468,244
AG2-151
13.9 MW1.2%$827,471
AG2-171
23.0 MW2.0%$1,365,259
AG2-188
42.9 MW3.7%$2,546,266
AG2-198
65.5 MW5.6%$3,889,072
AG2-213
30.6 MW2.6%$1,820,365
AG2-270
88.1 MW7.5%$5,231,403
AG2-440
38.3 MW3.3%$2,275,471
AG2-441
47.9 MW4.1%$2,844,324
AG2-442
53.6 MW4.6%$3,185,624
AG2-566
14.0 MW1.2%$829,075
AG2-581
83.6 MW7.2%$4,964,291
AG2-583
14.3 MW1.2%$849,686
AH1-056
38.3 MW3.3%$2,275,471
AH1-215
12.1 MW1.0%$716,753
AH1-217
7.5 MW0.6%$446,731
AH1-241
13.2 MW1.1%$785,596
AH1-280
7.7 MW0.7%$455,106
AH1-377
208.3 MW17.8%$12,372,387
AH1-439
24.6 MW2.1%$1,462,909
AH1-528
167.2 MW14.3%$9,928,404
AH1-546
14.4 MW1.2%$852,477
AH1-676
39.2 MW3.4%$2,328,929
AH1-687
10.1 MW0.9%$602,472

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2092
Title
Replace the existing Finneywood 230/500 kV XFRM T2 with a 3-480 MVA rated device
Description
Replace the existing Finneywood 230/500 kV XFRM T2 with a 3-480 MVA rated device
Total Cost ($USD)
$40,000,000
Allocated Cost ($USD)
$4,228,366
Time Estimate
42 to 48 Months

Contributor

FacilityContingency
8FINNEYWOOD-6FINNEYWOOD 500.0/230.0 kV Ckt 2 transformer(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-077
54.7 MW15.9%$6,362,337
AG2-171
11.4 MW3.3%$1,325,453
AG2-188
24.0 MW7.0%$2,789,190
AG2-198
23.5 MW6.8%$2,730,058
AG2-213
15.2 MW4.4%$1,767,309
AG2-270
36.3 MW10.6%$4,228,366
AG2-440
19.4 MW5.6%$2,258,869
AG2-441
24.3 MW7.1%$2,823,644
AG2-442
27.2 MW7.9%$3,162,370
AG2-566
4.5 MW1.3%$518,332
AG2-659
10.7 MW3.1%$1,246,068
AH1-056
20.1 MW5.8%$2,338,371
AH1-377
58.9 MW17.1%$6,854,712
AH1-439
13.7 MW4.0%$1,594,920

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2091
Title
Replace the existing Finneywood 230/500 kV XFRM T1 with a 3-480 MVA rated device
Description
Replace the existing Finneywood 230/500 kV XFRM T1 with a 3-480 MVA rated device
Total Cost ($USD)
$40,000,000
Allocated Cost ($USD)
$4,228,310
Time Estimate
42 to 48 Months

Contributor

FacilityContingency
8FINNEYWOOD-6FINNEYWOOD 500.0/230.0 kV Ckt 1 transformer(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-077
54.7 MW15.9%$6,362,347
AG2-171
11.4 MW3.3%$1,325,489
AG2-188
24.0 MW7.0%$2,789,224
AG2-198
23.5 MW6.8%$2,730,042
AG2-213
15.2 MW4.4%$1,767,319
AG2-270
36.4 MW10.6%$4,228,310
AG2-440
19.4 MW5.6%$2,258,912
AG2-441
24.3 MW7.1%$2,823,524
AG2-442
27.2 MW7.9%$3,162,454
AG2-566
4.5 MW1.3%$518,336
AG2-659
10.7 MW3.1%$1,246,076
AH1-056
20.1 MW5.8%$2,338,325
AH1-377
59.0 MW17.1%$6,854,754
AH1-439
13.7 MW4.0%$1,594,889

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0045
Title
Wreck and rebuild 8.3 miles of 230 kV Line 2250 between Edmonson and Sedge Hill with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 8.3 miles of 230 kV Line 2250 between Edmonson and Sedge Hill with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$31,540,000
Allocated Cost ($USD)
$2,844,056
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
10.0 MW1.6%$498,905
AG2-069
14.9 MW2.4%$748,333
AG2-077
80.7 MW12.8%$4,042,771
AG2-152
13.4 MW2.1%$670,515
AG2-188
22.3 MW3.5%$1,116,290
AG2-198
21.6 MW3.4%$1,082,038
AG2-270
56.8 MW9.0%$2,844,056
AG2-369
8.6 MW1.4%$429,050
AG2-440
13.1 MW2.1%$656,895
AG2-441
16.4 MW2.6%$821,143
AG2-442
18.4 MW2.9%$919,642
AG2-541
14.2 MW2.2%$709,124
AG2-566
4.1 MW0.7%$205,461
AG2-570
39.8 MW6.3%$1,995,421
AG2-571
5.0 MW0.8%$252,582
AG2-581
59.5 MW9.4%$2,977,307
AH1-056
15.1 MW2.4%$754,092
AH1-314
13.5 MW2.1%$676,925
AH1-343
16.1 MW2.5%$804,067
AH1-377
54.4 MW8.6%$2,722,822
AH1-439
12.8 MW2.0%$641,972
AH1-528
119.2 MW18.9%$5,970,589

System Reinforcement: n7796
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7796 / dom-302/3
Title
Wreck and rebuild 14.01 miles of 230 kV Line 2027 between Midlothian and Powhatan with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Description
Wreck and rebuild 14.01 miles of 230 kV Line 2027 between Midlothian and Powhatan with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Total Cost ($USD)
$53,238,000
Allocated Cost ($USD)
$1,672,909
Time Estimate
42 to 48 Months

Contributor

FacilityContingency
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-077
11.6 MW3.8%$2,045,039
AG2-151
23.3 MW7.7%$4,103,123
AG2-188
28.1 MW9.3%$4,948,039
AG2-198
8.4 MW2.8%$1,483,407
AG2-270
9.5 MW3.1%$1,672,909
AG2-440
8.6 MW2.9%$1,518,311
AG2-441
10.8 MW3.6%$1,897,844
AG2-442
12.1 MW4.0%$2,125,600
AG2-566
2.1 MW0.7%$370,896
AG2-581
8.9 MW2.9%$1,564,320
AG2-583
37.4 MW12.4%$6,600,676
AH1-056
12.0 MW4.0%$2,113,965
AH1-217
12.4 MW4.1%$2,185,535
AH1-241
23.3 MW7.7%$4,103,123
AH1-377
16.9 MW5.6%$2,974,570
AH1-439
16.8 MW5.6%$2,955,532
AH1-528
17.7 MW5.9%$3,128,287
AH1-546
20.0 MW6.6%$3,522,452
AH1-687
22.3 MW7.4%$3,924,374

System Reinforcement: n7568
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7568 / dom-369-TC2
Title
Wreck and rebuild 6.47 miles of 230 kV transmission line 2028 between Charlottesville and Mt. Eagle with (2) 768.2 ACSS/TW (20/7) ""Maumee"" @ 250C and replace line lead at Mt. Eagle.
Description
Wreck and rebuild 6.47 miles of 230 kV transmission line 2028 between Charlottesville and Mt. Eagle with (2) 768.2 ACSS/TW (20/7) ""Maumee"" @ 250C and replace line lead at Mt. Eagle.
Total Cost ($USD)
$36,802,018
Allocated Cost ($USD)
$1,346,206
Time Estimate
43 to 44 Months

Contributor

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.1 MW1.1%$386,666
AG2-069
6.2 MW1.6%$580,093
AG2-077
11.7 MW3.0%$1,098,680
AG2-088
15.4 MW3.9%$1,445,217
AG2-151
21.6 MW5.5%$2,028,498
AG2-171
8.1 MW2.1%$763,488
AG2-188
27.6 MW7.0%$2,583,932
AG2-198
9.6 MW2.4%$898,502
AG2-213
7.4 MW1.9%$693,918
AG2-270
14.4 MW3.7%$1,346,206
AG2-338
2.8 MW0.7%$263,278
AG2-339
7.0 MW1.8%$658,101
AG2-369
0.8 MW0.2%$79,602
AG2-428
7.8 MW2.0%$733,766
AG2-436
28.3 MW7.2%$2,654,439
AG2-440
10.2 MW2.6%$958,602
AG2-441
12.8 MW3.3%$1,198,253
AG2-442
14.3 MW3.6%$1,341,987
AG2-566
5.9 MW1.5%$556,372
AG2-570
6.9 MW1.8%$647,038
AG2-571
2.8 MW0.7%$258,778
AG2-581
7.5 MW1.9%$699,918
AG2-583
23.2 MW5.9%$2,176,826
AH1-056
13.4 MW3.4%$1,260,884
AH1-217
11.3 MW2.9%$1,062,957
AH1-241
21.6 MW5.5%$2,028,498
AH1-377
20.2 MW5.1%$1,891,795
AH1-439
16.3 MW4.2%$1,531,101
AH1-528
13.7 MW3.5%$1,285,543
AH1-546
18.7 MW4.8%$1,751,062
AH1-687
20.7 MW5.3%$1,938,019

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH2-DOM-0012
Title
Wreck and rebuild 8.1 miles of 230 kV Line 2027 (future Line 2323) between Bremo and AG2-583 with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Description
Wreck and rebuild 8.1 miles of 230 kV Line 2027 (future Line 2323) between Bremo and AG2-583 with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Total Cost ($USD)
$30,780,000
Allocated Cost ($USD)
$1,107,594
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-077
11.7 MW4.4%$1,353,455
AG2-151
23.3 MW8.8%$2,704,358
AG2-188
28.1 MW10.6%$3,262,332
AG2-198
8.4 MW3.2%$979,384
AG2-270
9.5 MW3.6%$1,107,594
AG2-440
8.6 MW3.3%$1,003,054
AG2-441
10.8 MW4.1%$1,253,788
AG2-442
12.1 MW4.6%$1,404,275
AG2-566
2.1 MW0.8%$244,817
AG2-581
8.9 MW3.4%$1,035,193
AH1-056
12.0 MW4.5%$1,395,689
AH1-217
12.4 MW4.7%$1,440,592
AH1-241
23.3 MW8.8%$2,704,358
AH1-377
16.9 MW6.4%$1,964,802
AH1-439
16.8 MW6.3%$1,948,442
AH1-528
17.8 MW6.7%$2,070,270
AH1-546
20.0 MW7.5%$2,321,469
AH1-687
22.3 MW8.4%$2,586,127

System Reinforcement: n9203.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9203.0 / TC1-PH2-DOM-008-TC2
Title
Wreck and rebuild 10.74 miles of line 2028 between Fork Union and Cunningham (Grape Vine) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C.
Description
Wreck and rebuild 10.74 miles of line 2028 between Fork Union and Cunningham (Grape Vine) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C.
Total Cost ($USD)
$29,539,973
Allocated Cost ($USD)
$1,103,455
Time Estimate
45 to 46 Months

Contributor

FacilityContingency
6GRAPEVINE-6FORK UNION 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.1 MW1.1%$316,942
AG2-069
6.2 MW1.6%$475,489
AG2-077
11.7 MW3.0%$900,563
AG2-088
15.4 MW4.0%$1,184,612
AG2-151
21.6 MW5.6%$1,662,714
AG2-188
27.6 MW7.2%$2,117,991
AG2-198
9.6 MW2.5%$736,482
AG2-213
7.4 MW1.9%$568,789
AG2-270
14.4 MW3.7%$1,103,455
AG2-338
2.8 MW0.7%$215,803
AG2-339
7.0 MW1.8%$539,431
AG2-369
0.8 MW0.2%$65,248
AG2-428
7.8 MW2.0%$601,451
AG2-436
28.3 MW7.4%$2,175,784
AG2-440
10.2 MW2.7%$785,745
AG2-441
12.8 MW3.3%$982,181
AG2-442
14.3 MW3.7%$1,099,996
AG2-566
5.9 MW1.5%$456,045
AG2-570
6.9 MW1.8%$530,362
AG2-571
2.8 MW0.7%$212,114
AG2-581
7.5 MW1.9%$573,707
AG2-583
23.2 MW6.0%$1,784,295
AH1-056
13.4 MW3.5%$1,033,519
AH1-217
11.3 MW2.9%$871,282
AH1-241
21.6 MW5.6%$1,662,714
AH1-377
20.2 MW5.2%$1,550,662
AH1-439
16.3 MW4.2%$1,255,009
AH1-528
13.7 MW3.6%$1,053,731
AH1-546
18.7 MW4.9%$1,435,306
AH1-687
20.7 MW5.4%$1,588,551

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH1-DOM-006
Title
Add a 3rd new 224 MVA 115/230 kV Transformer at Cloud substation, one (1) 230 kV breaker and one (1) 115 kV breaker.
Description
Add a 3rd new 224 MVA 115/230 kV Transformer at Cloud substation, one (1) 230 kV breaker and one (1) 115 kV breaker.
Total Cost ($USD)
$11,000,000
Allocated Cost ($USD)
$816,814
Time Estimate
42 to 44 Months

Contributor

FacilityContingency
3CLOUD-6CLOUD 115.0/230.0 kV Ckt 1 transformer(Any)
3CLOUD-6CLOUD 115.0/230.0 kV Ckt 2 transformer(Any)
(Any)DVP_P1-3: 6CLOUD-TX#1_SRT-A
(Any)DVP_P1-3: 6CLOUD-TX#2_SRT-A
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-171
13.9 MW6.1%$665,506
AG2-213
18.6 MW8.1%$887,405
AG2-270
17.1 MW7.4%$816,814
AG2-341
24.4 MW10.6%$1,165,567
AG2-440
19.4 MW8.4%$928,289
AG2-441
24.3 MW10.5%$1,160,313
AG2-442
27.2 MW11.8%$1,299,585
AG2-522
25.4 MW11.0%$1,213,328
AG2-659
28.5 MW12.4%$1,360,337
AH1-056
13.4 MW5.8%$637,995
AH1-408
18.1 MW7.9%$864,862

System Reinforcement: n8256
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n8256 / dom-277
Title
Wreck and rebuild 5.9 miles of 230 kV Line 2027 (future Line 2323) between Cartersville and AC2-165 (Sallee Creek) with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Description
Wreck and rebuild 5.9 miles of 230 kV Line 2027 (future Line 2323) between Cartersville and AC2-165 (Sallee Creek) with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Total Cost ($USD)
$22,420,000
Allocated Cost ($USD)
$706,892
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-077
11.7 MW3.9%$863,806
AG2-151
23.3 MW7.7%$1,725,982
AG2-188
28.1 MW9.3%$2,082,094
AG2-198
8.4 MW2.8%$625,065
AG2-270
9.5 MW3.2%$706,892
AG2-440
8.6 MW2.9%$640,172
AG2-441
10.8 MW3.6%$800,196
AG2-442
12.1 MW4.0%$896,240
AG2-566
2.1 MW0.7%$156,248
AG2-581
8.9 MW2.9%$660,684
AG2-583
37.5 MW12.4%$2,775,508
AH1-056
12.0 MW4.0%$890,760
AH1-217
12.4 MW4.1%$919,418
AH1-241
23.3 MW7.7%$1,725,982
AH1-377
16.9 MW5.6%$1,253,981
AH1-439
16.8 MW5.5%$1,243,540
AH1-528
17.8 MW5.9%$1,321,293
AH1-546
20.0 MW6.6%$1,481,614
AH1-687
22.3 MW7.4%$1,650,524

System Reinforcement: n8243
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n8243 / dom-389
Title
Wreck and rebuild 5.8 miles of 230 kV Line 2027 between AC2-165 (Sallee Creek) and Powhatan with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Description
Wreck and rebuild 5.8 miles of 230 kV Line 2027 between AC2-165 (Sallee Creek) and Powhatan with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Total Cost ($USD)
$22,040,000
Allocated Cost ($USD)
$693,450
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-077
11.6 MW3.8%$847,583
AG2-151
23.3 MW7.7%$1,697,936
AG2-188
28.1 MW9.3%$2,047,833
AG2-198
8.4 MW2.8%$614,270
AG2-270
9.5 MW3.1%$693,450
AG2-440
8.6 MW2.9%$628,852
AG2-441
10.8 MW3.6%$786,047
AG2-442
12.1 MW4.0%$880,393
AG2-566
2.1 MW0.7%$153,549
AG2-581
8.9 MW2.9%$648,319
AG2-583
37.5 MW12.4%$2,731,003
AH1-056
12.0 MW4.0%$875,362
AH1-217
12.4 MW4.1%$904,453
AH1-241
23.3 MW7.7%$1,697,936
AH1-377
16.9 MW5.6%$1,231,893
AH1-439
16.8 MW5.5%$1,223,144
AH1-528
17.8 MW5.9%$1,296,492
AH1-546
20.0 MW6.6%$1,457,624
AH1-687
22.3 MW7.4%$1,623,860

System Reinforcement: n7569
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7569 / dom-490-TC2
Title
Upgrade a 3.78 mile segment of 230kV transmission line 2028 between Mt. Eagle and Grape Vine Substations at structure 2080/73.
Description
Uograde 3.78 miles of transmission line 2028 between Mt. Eagle and Grape Vine with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"". The segment runs from Mt Eagle to structure 2080/73.
Total Cost ($USD)
$13,360,242
Allocated Cost ($USD)
$488,713
Time Estimate
43 to 44 Months

Contributor

FacilityContingency
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.1 MW1.1%$140,371
AG2-069
6.2 MW1.6%$210,591
AG2-077
11.7 MW3.0%$398,854
AG2-088
15.4 MW3.9%$524,657
AG2-151
21.6 MW5.5%$736,406
AG2-171
8.1 MW2.1%$277,169
AG2-188
27.6 MW7.0%$938,045
AG2-198
9.6 MW2.4%$326,183
AG2-213
7.4 MW1.9%$251,913
AG2-270
14.4 MW3.7%$488,713
AG2-338
2.8 MW0.7%$95,578
AG2-339
7.0 MW1.8%$238,911
AG2-369
0.8 MW0.2%$28,898
AG2-428
7.8 MW2.0%$266,379
AG2-436
28.3 MW7.2%$963,641
AG2-440
10.2 MW2.6%$348,002
AG2-441
12.8 MW3.3%$435,002
AG2-442
14.3 MW3.6%$487,182
AG2-566
5.9 MW1.5%$201,980
AG2-570
6.9 MW1.8%$234,894
AG2-571
2.8 MW0.7%$93,944
AG2-581
7.5 MW1.9%$254,091
AG2-583
23.2 MW5.9%$790,253
AH1-056
13.4 MW3.4%$457,739
AH1-217
11.3 MW2.9%$385,885
AH1-241
21.6 MW5.5%$736,406
AH1-377
20.2 MW5.1%$686,779
AH1-439
16.3 MW4.2%$555,836
AH1-528
13.7 MW3.5%$466,691
AH1-546
18.7 MW4.8%$635,688
AH1-687
20.7 MW5.3%$703,559

System Reinforcement: n9644.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9644.0 / TC1-PH3-DOM-006-TC2
Title
Upgrade a 2.73 mile segment of 230kV transmission line 2028 between Mt. Eagle and Grape Vine. This segment runs from Grape Vine substation to structure 2080/73.
Description
Rebuild a 2.73 mile segment of 230kV line 2028 between Mt. Eagle and Grape Vinew with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @250 degrees C.
Total Cost ($USD)
$8,415,380
Allocated Cost ($USD)
$307,832
Time Estimate
Mar 31 2029

Contributor

FacilityContingency
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.1 MW1.1%$88,418
AG2-069
6.2 MW1.6%$132,648
AG2-077
11.7 MW3.0%$251,231
AG2-088
15.4 MW3.9%$330,472
AG2-151
21.6 MW5.5%$463,849
AG2-171
8.1 MW2.1%$174,584
AG2-188
27.6 MW7.0%$590,858
AG2-198
9.6 MW2.4%$205,457
AG2-213
7.4 MW1.9%$158,676
AG2-270
14.4 MW3.7%$307,832
AG2-338
2.8 MW0.7%$60,203
AG2-339
7.0 MW1.8%$150,486
AG2-369
0.8 MW0.2%$18,202
AG2-428
7.8 MW2.0%$167,787
AG2-436
28.3 MW7.2%$606,981
AG2-440
10.2 MW2.6%$219,200
AG2-441
12.8 MW3.3%$274,000
AG2-442
14.3 MW3.6%$306,867
AG2-566
5.9 MW1.5%$127,223
AG2-570
6.9 MW1.8%$147,956
AG2-571
2.8 MW0.7%$59,174
AG2-581
7.5 MW1.9%$160,048
AG2-583
23.2 MW5.9%$497,767
AH1-056
13.4 MW3.4%$288,322
AH1-217
11.3 MW2.9%$243,062
AH1-241
21.6 MW5.5%$463,849
AH1-377
20.2 MW5.1%$432,590
AH1-439
16.3 MW4.2%$350,111
AH1-528
13.7 MW3.5%$293,960
AH1-546
18.7 MW4.8%$400,409
AH1-687
20.7 MW5.3%$443,160

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2043
Title
Wreck and rebuild 0.93 miles of 230 kV Line 2241 between Hendrick and Persons with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Dominion portion of line only.
Description
Wreck and rebuild 0.93 miles of 230 kV Line 2241 between Hendrick and Persons with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Dominion portion of line only.
Total Cost ($USD)
$3,534,000
Allocated Cost ($USD)
$203,423
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
9.2 MW1.1%$39,652
AG2-069
13.8 MW1.7%$59,477
AG2-077
67.9 MW8.3%$292,796
AG2-111
3.5 MW0.4%$15,101
AG2-112
3.7 MW0.4%$15,830
AG2-151
7.2 MW0.9%$31,260
AG2-152
14.7 MW1.8%$63,434
AG2-171
13.1 MW1.6%$56,405
AG2-188
21.4 MW2.6%$92,359
AG2-198
19.5 MW2.4%$83,993
AG2-213
17.4 MW2.1%$75,209
AG2-270
47.1 MW5.8%$203,423
AG2-272
5.3 MW0.7%$23,062
AG2-341
6.5 MW0.8%$27,834
AG2-369
7.9 MW1.0%$34,099
AG2-440
21.4 MW2.6%$92,165
AG2-441
26.7 MW3.3%$115,205
AG2-442
29.9 MW3.7%$129,034
AG2-522
10.0 MW1.2%$43,134
AG2-541
19.1 MW2.3%$82,250
AG2-566
9.3 MW1.1%$39,936
AG2-570
35.7 MW4.4%$154,059
AG2-571
15.5 MW1.9%$67,037
AG2-581
50.2 MW6.1%$216,526
AG2-583
7.5 MW0.9%$32,494
AG2-659
11.3 MW1.4%$48,915
AH1-056
20.7 MW2.5%$89,249
AH1-215
8.7 MW1.1%$37,455
AH1-241
6.9 MW0.8%$29,676
AH1-314
15.6 MW1.9%$67,343
AH1-343
22.0 MW2.7%$94,896
AH1-377
48.3 MW5.9%$208,557
AH1-408
10.5 MW1.3%$45,498
AH1-439
12.3 MW1.5%$53,152
AH1-528
100.6 MW12.3%$434,213
AH1-535
6.0 MW0.7%$25,767
AH1-546
7.3 MW0.9%$31,579
AH1-687
5.2 MW0.6%$22,479
AH1-690
28.7 MW3.5%$123,688
AH1-721
31.5 MW3.8%$135,756

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0013
Title
Wreck and rebuild 1.51 miles of 230 kV Line 2027 (future Line 2323) between Cartersville and AG2-583 with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Description
Wreck and rebuild 1.51 miles of 230 kV Line 2027 (future Line 2323) between Cartersville and AG2-583 with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Total Cost ($USD)
$5,738,000
Allocated Cost ($USD)
$180,916
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-077
11.7 MW3.9%$221,076
AG2-151
23.3 MW7.7%$441,734
AG2-188
28.1 MW9.3%$532,875
AG2-198
8.4 MW2.8%$159,974
AG2-270
9.5 MW3.2%$180,916
AG2-440
8.6 MW2.9%$163,841
AG2-441
10.8 MW3.6%$204,796
AG2-442
12.1 MW4.0%$229,377
AG2-566
2.1 MW0.7%$39,989
AG2-581
8.9 MW2.9%$169,090
AG2-583
37.5 MW12.4%$710,342
AH1-056
12.0 MW4.0%$227,974
AH1-217
12.4 MW4.1%$235,309
AH1-241
23.3 MW7.7%$441,734
AH1-377
16.9 MW5.6%$320,934
AH1-439
16.8 MW5.5%$318,262
AH1-528
17.8 MW5.9%$338,162
AH1-546
20.0 MW6.6%$379,193
AH1-687
22.3 MW7.4%$422,422

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2008
Title
Wreck and rebuild 0.47 miles of 230 kV Line 2241 between Hendrick and Alton Post with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 0.47 miles of 230 kV Line 2241 between Hendrick and Alton Post with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$1,786,000
Allocated Cost ($USD)
$152,347
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-077
67.9 MW12.3%$219,287
AG2-171
13.1 MW2.4%$42,258
AG2-188
21.4 MW3.9%$69,220
AG2-198
19.5 MW3.5%$62,923
AG2-213
17.4 MW3.2%$56,344
AG2-270
47.2 MW8.5%$152,347
AG2-440
21.4 MW3.9%$69,049
AG2-441
26.7 MW4.8%$86,314
AG2-442
29.9 MW5.4%$96,671
AG2-541
19.1 MW3.4%$61,605
AG2-566
3.7 MW0.7%$11,946
AG2-581
50.2 MW9.1%$162,164
AG2-659
11.4 MW2.1%$36,664
AH1-056
20.7 MW3.7%$66,866
AH1-343
22.0 MW4.0%$71,074
AH1-377
48.4 MW8.7%$156,225
AH1-439
12.3 MW2.2%$39,842
AH1-528
100.7 MW18.2%$325,201

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-1032
Title
Wreck and rebuild 0.73 miles of 230 kV line 235 between AG1-098 and Finneywood with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C
Description
Wreck and rebuild 0.73 miles of 230 kV line 235 between AG1-098 and Finneywood with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C
Total Cost ($USD)
$2,774,000
Allocated Cost ($USD)
$94,621
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6FINNEYWOOD-AG1-098 TP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-077
36.3 MW4.2%$116,992
AG2-151
13.9 MW1.6%$44,900
AG2-171
15.4 MW1.8%$49,715
AG2-188
89.0 MW10.3%$286,703
AG2-198
55.1 MW6.4%$177,623
AG2-213
20.6 MW2.4%$66,284
AG2-270
29.4 MW3.4%$94,621
AG2-440
31.5 MW3.7%$101,480
AG2-441
39.4 MW4.6%$126,851
AG2-442
44.1 MW5.1%$142,074
AG2-566
26.1 MW3.0%$84,275
AG2-581
27.9 MW3.2%$89,790
AG2-583
14.3 MW1.7%$46,105
AH1-056
40.7 MW4.7%$131,257
AH1-215
7.9 MW0.9%$25,594
AH1-217
7.5 MW0.9%$24,240
AH1-241
13.2 MW1.5%$42,628
AH1-280
7.4 MW0.9%$23,805
AH1-377
131.2 MW15.2%$422,936
AH1-439
54.0 MW6.3%$174,068
AH1-528
55.7 MW6.5%$179,576
AH1-546
50.7 MW5.9%$163,420
AH1-676
39.2 MW4.6%$126,371
AH1-687
10.1 MW1.2%$32,691

System Reinforcement: n9198.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9198.0 / TC1-PH2-DOM-003-TC2
Title
Replace Circuit Breaker 219322 and Circuit Breaker Lead at Bremo 230 kV (Bremo - Fork Union).
Description
Replace Circuit Breaker 219322 and Circuit Breaker Lead at Bremo 230 kV (Bremo - Fork Union).
Total Cost ($USD)
$2,113,879
Allocated Cost ($USD)
$82,279
Time Estimate
40 to 41 Months

Contributor

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
5.5 MW0.7%$14,813
AG2-069
8.3 MW1.1%$22,223
AG2-077
20.7 MW2.6%$55,670
AG2-088
33.4 MW4.2%$89,747
AG2-151
27.7 MW3.5%$74,401
AG2-171
17.4 MW2.2%$46,851
AG2-188
59.1 MW7.5%$159,015
AG2-198
20.5 MW2.6%$55,218
AG2-213
17.6 MW2.2%$47,443
AG2-270
30.6 MW3.9%$82,279
AG2-338
6.0 MW0.8%$16,245
AG2-339
15.1 MW1.9%$40,615
AG2-369
4.1 MW0.5%$10,993
AG2-428
17.0 MW2.2%$45,705
AG2-436
60.8 MW7.7%$163,599
AG2-440
20.9 MW2.7%$56,176
AG2-441
26.1 MW3.3%$70,215
AG2-442
30.6 MW3.9%$82,225
AG2-566
12.7 MW1.6%$34,201
AG2-570
14.8 MW1.9%$39,732
AG2-571
5.9 MW0.8%$15,890
AG2-581
16.0 MW2.0%$43,020
AG2-583
49.9 MW6.3%$134,134
AH1-056
28.8 MW3.7%$77,366
AH1-241
27.7 MW3.5%$74,401
AH1-377
43.2 MW5.5%$116,216
AH1-408
16.7 MW2.1%$44,930
AH1-439
35.0 MW4.5%$94,235
AH1-528
29.4 MW3.7%$79,147
AH1-546
40.1 MW5.1%$107,827
AH1-687
44.4 MW5.6%$119,347

System Reinforcement: n9221.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9221.0 / TC1-PH3-DOM-015-TC2
Title
Replace 230 kV Breaker 29822 at Bremo with a higher-rated device (Buckingham - Bremo).
Description
Replace 230 kV Breaker 29822 at Bremo with a higher-rated device (Buckingham - Bremo).
Total Cost ($USD)
$2,057,335
Allocated Cost ($USD)
$80,033
Time Estimate
38 to 39 Months

Contributor

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.3 MW0.6%$11,624
AG2-069
6.5 MW0.8%$17,436
AG2-077
47.9 MW6.2%$127,897
AG2-171
16.0 MW2.1%$42,650
AG2-188
71.8 MW9.3%$191,886
AG2-198
29.4 MW3.8%$78,462
AG2-213
21.3 MW2.8%$56,868
AG2-270
30.0 MW3.9%$80,033
AG2-338
2.8 MW0.4%$7,356
AG2-339
6.9 MW0.9%$18,392
AG2-341
7.8 MW1.0%$20,843
AG2-369
3.7 MW0.5%$9,996
AG2-436
28.6 MW3.7%$76,439
AG2-440
29.3 MW3.8%$78,406
AG2-441
36.7 MW4.8%$98,006
AG2-442
41.1 MW5.3%$109,766
AG2-522
9.8 MW1.3%$26,214
AG2-541
8.0 MW1.0%$21,431
AG2-566
10.4 MW1.4%$27,902
AG2-570
7.3 MW0.9%$19,429
AG2-571
2.9 MW0.4%$7,773
AG2-581
36.5 MW4.7%$97,645
AG2-659
10.8 MW1.4%$28,784
AH1-056
33.7 MW4.4%$90,107
AH1-215
8.3 MW1.1%$22,192
AH1-314
6.0 MW0.8%$15,905
AH1-343
9.2 MW1.2%$24,554
AH1-377
63.7 MW8.3%$170,330
AH1-408
11.4 MW1.5%$30,369
AH1-439
44.8 MW5.8%$119,784
AH1-528
73.3 MW9.5%$195,806
AH1-546
49.8 MW6.5%$133,048

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2065
Title
Replace switches 219324 and 219325 at Bremo 230 kV
Description
Replace switches 219324 and 219325 at Bremo 230 kV
Total Cost ($USD)
$800,000
Allocated Cost ($USD)
$31,138
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
2.8 MW0.7%$5,606
AG2-069
4.1 MW1.1%$8,410
AG2-077
10.3 MW2.6%$21,068
AG2-088
16.7 MW4.2%$33,965
AG2-151
13.8 MW3.5%$28,157
AG2-171
8.7 MW2.2%$17,731
AG2-188
29.6 MW7.5%$60,179
AG2-198
10.3 MW2.6%$20,897
AG2-213
8.8 MW2.2%$17,955
AG2-270
15.3 MW3.9%$31,138
AG2-338
3.0 MW0.8%$6,148
AG2-339
7.5 MW1.9%$15,371
AG2-369
2.0 MW0.5%$4,160
AG2-428
8.5 MW2.2%$17,297
AG2-436
30.4 MW7.7%$61,914
AG2-440
10.4 MW2.7%$21,260
AG2-441
13.0 MW3.3%$26,573
AG2-442
15.3 MW3.9%$31,118
AG2-566
6.4 MW1.6%$12,943
AG2-570
7.4 MW1.9%$15,037
AG2-571
3.0 MW0.8%$6,013
AG2-581
8.0 MW2.0%$16,281
AG2-583
24.9 MW6.3%$50,763
AH1-056
14.4 MW3.7%$29,279
AH1-241
13.8 MW3.5%$28,157
AH1-377
21.6 MW5.5%$43,982
AH1-408
8.3 MW2.1%$17,004
AH1-439
17.5 MW4.5%$35,663
AH1-528
14.7 MW3.7%$29,953
AH1-546
20.0 MW5.1%$40,807
AH1-687
22.2 MW5.6%$45,167

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2077
Title
Replace switches 29824 and 29825 at Bremo 230 kV
Description
Replace switches 29824 and 29825 at Bremo 230 kV
Total Cost ($USD)
$800,000
Allocated Cost ($USD)
$31,121
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.3 MW0.6%$4,520
AG2-069
6.5 MW0.8%$6,780
AG2-077
47.9 MW6.2%$49,733
AG2-171
16.0 MW2.1%$16,585
AG2-188
71.8 MW9.3%$74,615
AG2-198
29.4 MW3.8%$30,510
AG2-213
21.3 MW2.8%$22,113
AG2-270
30.0 MW3.9%$31,121
AG2-338
2.8 MW0.4%$2,861
AG2-339
6.9 MW0.9%$7,152
AG2-341
7.8 MW1.0%$8,105
AG2-369
3.7 MW0.5%$3,887
AG2-436
28.6 MW3.7%$29,724
AG2-440
29.3 MW3.8%$30,488
AG2-441
36.7 MW4.8%$38,110
AG2-442
41.1 MW5.3%$42,683
AG2-522
9.8 MW1.3%$10,193
AG2-541
8.0 MW1.0%$8,333
AG2-566
10.4 MW1.4%$10,850
AG2-570
7.3 MW0.9%$7,555
AG2-571
2.9 MW0.4%$3,023
AG2-581
36.5 MW4.7%$37,970
AG2-659
10.8 MW1.4%$11,193
AH1-056
33.7 MW4.4%$35,038
AH1-215
8.3 MW1.1%$8,629
AH1-314
6.0 MW0.8%$6,185
AH1-343
9.2 MW1.2%$9,548
AH1-377
63.7 MW8.3%$66,233
AH1-408
11.4 MW1.5%$11,809
AH1-439
44.8 MW5.8%$46,578
AH1-528
73.3 MW9.5%$76,140
AH1-546
49.8 MW6.5%$51,736

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2087
Title
Replace 2-1590 AAC 61 line lead on line 298 at Farmville 230 kV
Description
Replace 2-1590 AAC 61 line lead on line 298 at Farmville 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$28,019
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-077
47.9 MW9.0%$44,774
AG2-171
16.0 MW3.0%$14,930
AG2-198
29.4 MW5.5%$27,463
AG2-213
21.3 MW4.0%$19,907
AG2-270
30.0 MW5.6%$28,019
AG2-341
7.8 MW1.5%$7,298
AG2-440
29.4 MW5.5%$27,445
AG2-441
36.7 MW6.9%$34,306
AG2-442
41.1 MW7.7%$38,422
AG2-522
9.8 MW1.8%$9,183
AG2-541
8.0 MW1.5%$7,507
AG2-566
10.4 MW2.0%$9,766
AG2-581
36.6 MW6.8%$34,184
AG2-659
10.8 MW2.0%$10,082
AH1-056
33.7 MW6.3%$31,539
AH1-215
8.3 MW1.6%$7,769
AH1-343
9.2 MW1.7%$8,600
AH1-377
63.8 MW11.9%$59,618
AH1-408
11.4 MW2.1%$10,641
AH1-528
73.3 MW13.7%$68,548

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2086
Title
Replace 3 1/2' AL Pipe line lead on line 298 at Farmville 230 kV
Description
Replace 3 1/2' AL Pipe line lead on line 298 at Farmville 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$28,019
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-077
47.9 MW9.0%$44,774
AG2-171
16.0 MW3.0%$14,930
AG2-198
29.4 MW5.5%$27,463
AG2-213
21.3 MW4.0%$19,907
AG2-270
30.0 MW5.6%$28,019
AG2-341
7.8 MW1.5%$7,298
AG2-440
29.4 MW5.5%$27,445
AG2-441
36.7 MW6.9%$34,306
AG2-442
41.1 MW7.7%$38,422
AG2-522
9.8 MW1.8%$9,183
AG2-541
8.0 MW1.5%$7,507
AG2-566
10.4 MW2.0%$9,766
AG2-581
36.6 MW6.8%$34,184
AG2-659
10.8 MW2.0%$10,082
AH1-056
33.7 MW6.3%$31,539
AH1-215
8.3 MW1.6%$7,769
AH1-343
9.2 MW1.7%$8,600
AH1-377
63.8 MW11.9%$59,618
AH1-408
11.4 MW2.1%$10,641
AH1-528
73.3 MW13.7%$68,548

System Reinforcement: n9205.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9205.0 / TC1-PH2-DOM-015
Title
Replace Line Switch 23889 at Sapony 230 kV (Sapony - AE2-033 Tap)
Description
Replace Line Switch 23889 at Sapony 230 kV (Sapony - AE2-033 Tap)
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$27,336
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-077
7.7 MW7.8%$31,042
AG2-270
6.8 MW6.8%$27,336
AG2-382
4.6 MW4.6%$18,389
AG2-440
5.3 MW5.3%$21,319
AG2-441
6.6 MW6.7%$26,649
AG2-442
7.4 MW7.5%$29,844
AG2-522
7.8 MW7.8%$31,283
AG2-659
7.1 MW7.2%$28,659
AH1-040
8.4 MW8.4%$33,599
AH1-271
2.6 MW2.6%$10,507
AH1-408
23.6 MW23.7%$94,919
AH1-528
11.6 MW11.6%$46,453

System Reinforcement: n9202.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9202.0 / TC1-PH2-DOM-007
Title
Replace Line Switch 23886 at Sapony 230 kV (Carson - Sapony).
Description
Replace Line Switch 23886 at Sapony 230 kV (Carson - Sapony).
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$27,316
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6CARSON-6SAPONY 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-077
7.7 MW7.8%$31,019
AG2-270
6.8 MW6.8%$27,316
AG2-382
4.6 MW4.6%$18,393
AG2-440
5.3 MW5.3%$21,315
AG2-441
6.6 MW6.7%$26,644
AG2-442
7.4 MW7.5%$29,840
AG2-522
7.8 MW7.8%$31,297
AG2-659
7.1 MW7.2%$28,669
AH1-040
8.3 MW8.4%$33,575
AH1-271
2.6 MW2.6%$10,509
AH1-408
23.6 MW23.8%$95,005
AH1-528
11.5 MW11.6%$46,418

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2085
Title
Replace wavetrap 298WT at Farmville 230 kV
Description
Replace wavetrap 298WT at Farmville 230 kV
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$24,400
Time Estimate
16 to 18 Months

Contributor

FacilityContingency
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.4 MW0.9%$3,558
AG2-069
6.5 MW1.3%$5,337
AG2-077
36.3 MW7.4%$29,621
AG2-171
12.1 MW2.5%$9,886
AG2-198
22.3 MW4.5%$18,192
AG2-213
16.2 MW3.3%$13,181
AG2-270
29.9 MW6.1%$24,400
AG2-338
2.8 MW0.6%$2,252
AG2-339
6.9 MW1.4%$5,631
AG2-341
7.8 MW1.6%$6,369
AG2-369
3.8 MW0.8%$3,060
AG2-436
28.7 MW5.9%$23,401
AG2-440
22.3 MW4.5%$18,175
AG2-441
27.8 MW5.7%$22,719
AG2-442
31.2 MW6.4%$25,446
AG2-522
7.4 MW1.5%$6,073
AG2-541
6.1 MW1.2%$4,955
AG2-566
10.4 MW2.1%$8,523
AG2-570
7.3 MW1.5%$5,948
AG2-571
2.9 MW0.6%$2,379
AG2-581
27.7 MW5.7%$22,616
AG2-659
8.2 MW1.7%$6,667
AH1-056
29.2 MW6.0%$23,852
AH1-215
6.3 MW1.3%$5,144
AH1-314
6.0 MW1.2%$4,871
AH1-343
7.0 MW1.4%$5,678
AH1-377
48.4 MW9.9%$39,485
AH1-408
9.0 MW1.8%$7,347
AH1-528
55.4 MW11.3%$45,231

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2079
Title
Replace 3 1/2 " AL Pipe line lead on line 298 at Bremo 230 kV
Description
Replace 3 1/2 " AL Pipe line lead on line 298 at Bremo 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$21,185
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-077
47.9 MW6.8%$33,855
AG2-171
16.0 MW2.3%$11,290
AG2-188
71.8 MW10.2%$50,793
AG2-198
29.4 MW4.2%$20,769
AG2-213
21.3 MW3.0%$15,053
AG2-270
30.0 MW4.2%$21,185
AG2-341
7.8 MW1.1%$5,517
AG2-440
29.3 MW4.2%$20,754
AG2-441
36.7 MW5.2%$25,943
AG2-442
41.1 MW5.8%$29,056
AG2-522
9.8 MW1.4%$6,939
AG2-541
8.0 MW1.1%$5,673
AG2-566
10.4 MW1.5%$7,386
AG2-581
36.5 MW5.2%$25,847
AG2-659
10.8 MW1.5%$7,619
AH1-056
33.7 MW4.8%$23,852
AH1-215
8.3 MW1.2%$5,874
AH1-314
6.0 MW0.8%$4,210
AH1-343
9.2 MW1.3%$6,500
AH1-377
63.7 MW9.0%$45,087
AH1-408
11.4 MW1.6%$8,039
AH1-439
44.8 MW6.3%$31,708
AH1-528
73.3 MW10.4%$51,831
AH1-546
49.8 MW7.0%$35,219

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0014
Title
Wreck and rebuild 0.17 miles of 230 kV Line 2027 between Midlothian and Powhatan with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Description
Wreck and rebuild 0.17 miles of 230 kV Line 2027 between Midlothian and Powhatan with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Total Cost ($USD)
$646,000
Allocated Cost ($USD)
$20,299
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-077
11.6 MW3.8%$24,815
AG2-151
23.3 MW7.7%$49,788
AG2-188
28.1 MW9.3%$60,040
AG2-198
8.4 MW2.8%$18,000
AG2-270
9.5 MW3.1%$20,299
AG2-440
8.6 MW2.9%$18,423
AG2-441
10.8 MW3.6%$23,029
AG2-442
12.1 MW4.0%$25,792
AG2-566
2.1 MW0.7%$4,501
AG2-581
8.9 MW2.9%$18,982
AG2-583
37.4 MW12.4%$80,094
AH1-056
12.0 MW4.0%$25,651
AH1-217
12.4 MW4.1%$26,520
AH1-241
23.3 MW7.7%$49,788
AH1-377
16.9 MW5.6%$36,094
AH1-439
16.8 MW5.6%$35,863
AH1-528
17.7 MW5.9%$37,959
AH1-546
20.0 MW6.6%$42,742
AH1-687
22.3 MW7.4%$47,619

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2078
Title
Replace 2-636 ACSR line lead on line 298 at Bremo 230 kV
Description
Replace 2-636 ACSR line lead on line 298 at Bremo 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$19,451
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.3 MW0.6%$2,825
AG2-069
6.5 MW0.8%$4,237
AG2-077
47.9 MW6.2%$31,083
AG2-171
16.0 MW2.1%$10,365
AG2-188
71.8 MW9.3%$46,635
AG2-198
29.4 MW3.8%$19,069
AG2-213
21.3 MW2.8%$13,821
AG2-270
30.0 MW3.9%$19,451
AG2-338
2.8 MW0.4%$1,788
AG2-339
6.9 MW0.9%$4,470
AG2-341
7.8 MW1.0%$5,065
AG2-369
3.7 MW0.5%$2,429
AG2-436
28.6 MW3.7%$18,577
AG2-440
29.3 MW3.8%$19,055
AG2-441
36.7 MW4.8%$23,819
AG2-442
41.1 MW5.3%$26,677
AG2-522
9.8 MW1.3%$6,371
AG2-541
8.0 MW1.0%$5,208
AG2-566
10.4 MW1.4%$6,781
AG2-570
7.3 MW0.9%$4,722
AG2-571
2.9 MW0.4%$1,889
AG2-581
36.5 MW4.7%$23,731
AG2-659
10.8 MW1.4%$6,996
AH1-056
33.7 MW4.4%$21,899
AH1-215
8.3 MW1.1%$5,393
AH1-314
6.0 MW0.8%$3,865
AH1-343
9.2 MW1.2%$5,967
AH1-377
63.7 MW8.3%$41,396
AH1-408
11.4 MW1.5%$7,381
AH1-439
44.8 MW5.8%$29,111
AH1-528
73.3 MW9.5%$47,587
AH1-546
49.8 MW6.5%$32,335

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2072
Title
Replace 2500 ACAR line lead on line 2028 at Charlottesville 230 kV
Description
Replace 2500 ACAR line lead on line 2028 at Charlottesville 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$18,290
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.1 MW1.1%$5,253
AG2-069
6.2 MW1.6%$7,881
AG2-077
11.7 MW3.0%$14,927
AG2-088
15.4 MW3.9%$19,635
AG2-151
21.6 MW5.5%$27,560
AG2-171
8.1 MW2.1%$10,373
AG2-188
27.6 MW7.0%$35,106
AG2-198
9.6 MW2.4%$12,207
AG2-213
7.4 MW1.9%$9,428
AG2-270
14.4 MW3.7%$18,290
AG2-338
2.8 MW0.7%$3,577
AG2-339
7.0 MW1.8%$8,941
AG2-369
0.8 MW0.2%$1,081
AG2-428
7.8 MW2.0%$9,969
AG2-436
28.3 MW7.2%$36,064
AG2-440
10.2 MW2.6%$13,024
AG2-441
12.8 MW3.3%$16,280
AG2-442
14.3 MW3.6%$18,233
AG2-566
5.9 MW1.5%$7,559
AG2-570
6.9 MW1.8%$8,791
AG2-571
2.8 MW0.7%$3,516
AG2-581
7.5 MW1.9%$9,509
AG2-583
23.2 MW5.9%$29,575
AH1-056
13.4 MW3.4%$17,131
AH1-217
11.3 MW2.9%$14,442
AH1-241
21.6 MW5.5%$27,560
AH1-377
20.2 MW5.1%$25,702
AH1-439
16.3 MW4.2%$20,802
AH1-528
13.7 MW3.5%$17,466
AH1-546
18.7 MW4.8%$23,790
AH1-687
20.7 MW5.3%$26,330

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2068
Title
Wreck and rebuild 0.12 miles of 230 kV line 2028 between Fork Union and Grape Vine with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Description
Wreck and rebuild 0.12 miles of 230 kV line 2028 between Fork Union and Grape Vine with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Total Cost ($USD)
$456,000
Allocated Cost ($USD)
$17,034
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6GRAPEVINE-6FORK UNION 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.1 MW1.1%$4,893
AG2-069
6.2 MW1.6%$7,340
AG2-077
11.7 MW3.0%$13,902
AG2-088
15.4 MW4.0%$18,287
AG2-151
21.6 MW5.6%$25,667
AG2-188
27.6 MW7.2%$32,695
AG2-198
9.6 MW2.5%$11,369
AG2-213
7.4 MW1.9%$8,780
AG2-270
14.4 MW3.7%$17,034
AG2-338
2.8 MW0.7%$3,331
AG2-339
7.0 MW1.8%$8,327
AG2-369
0.8 MW0.2%$1,007
AG2-428
7.8 MW2.0%$9,284
AG2-436
28.3 MW7.4%$33,587
AG2-440
10.2 MW2.7%$12,129
AG2-441
12.8 MW3.3%$15,162
AG2-442
14.3 MW3.7%$16,980
AG2-566
5.9 MW1.5%$7,040
AG2-570
6.9 MW1.8%$8,187
AG2-571
2.8 MW0.7%$3,274
AG2-581
7.5 MW1.9%$8,856
AG2-583
23.2 MW6.0%$27,544
AH1-056
13.4 MW3.5%$15,954
AH1-217
11.3 MW2.9%$13,450
AH1-241
21.6 MW5.6%$25,667
AH1-377
20.2 MW5.2%$23,937
AH1-439
16.3 MW4.2%$19,373
AH1-528
13.7 MW3.6%$16,266
AH1-546
18.7 MW4.9%$22,156
AH1-687
20.7 MW5.4%$24,522

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2067
Title
Replace 3 1/2" pipe line lead on line 2193 at Bremo 230 kV
Description
Replace 3 1/2" pipe line lead on line 2193 at Bremo 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$16,409
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
2.8 MW0.6%$2,954
AG2-069
4.1 MW0.9%$4,432
AG2-077
10.3 MW2.2%$11,102
AG2-088
16.7 MW3.6%$17,891
AG2-151
13.8 MW3.0%$14,838
AG2-171
8.7 MW1.9%$9,343
AG2-188
36.7 MW7.9%$39,350
AG2-198
13.5 MW2.9%$14,479
AG2-213
11.6 MW2.5%$12,458
AG2-270
15.3 MW3.3%$16,409
AG2-338
3.0 MW0.6%$3,240
AG2-339
7.5 MW1.6%$8,100
AG2-369
2.0 MW0.4%$2,192
AG2-428
9.9 MW2.1%$10,624
AG2-436
30.4 MW6.5%$32,614
AG2-440
11.3 MW2.4%$12,126
AG2-441
14.1 MW3.0%$15,157
AG2-442
20.1 MW4.3%$21,562
AG2-566
6.4 MW1.4%$6,821
AG2-570
23.3 MW5.0%$25,024
AG2-571
3.0 MW0.6%$3,168
AG2-581
10.5 MW2.3%$11,289
AG2-583
32.8 MW7.0%$35,169
AH1-056
16.6 MW3.6%$17,769
AH1-241
13.8 MW3.0%$14,838
AH1-377
28.4 MW6.1%$30,476
AH1-408
8.3 MW1.8%$8,960
AH1-439
23.0 MW4.9%$24,707
AH1-528
19.4 MW4.2%$20,828
AH1-546
26.4 MW5.7%$28,317
AH1-687
22.1 MW4.8%$23,765

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2066
Title
Replace 2-636 ACSR line lead on line 2193 at Bremo 230 kV
Description
Replace 2-636 ACSR line lead on line 2193 at Bremo 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$16,409
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
2.8 MW0.6%$2,954
AG2-069
4.1 MW0.9%$4,432
AG2-077
10.3 MW2.2%$11,102
AG2-088
16.7 MW3.6%$17,891
AG2-151
13.8 MW3.0%$14,838
AG2-171
8.7 MW1.9%$9,343
AG2-188
36.7 MW7.9%$39,350
AG2-198
13.5 MW2.9%$14,479
AG2-213
11.6 MW2.5%$12,458
AG2-270
15.3 MW3.3%$16,409
AG2-338
3.0 MW0.6%$3,240
AG2-339
7.5 MW1.6%$8,100
AG2-369
2.0 MW0.4%$2,192
AG2-428
9.9 MW2.1%$10,624
AG2-436
30.4 MW6.5%$32,614
AG2-440
11.3 MW2.4%$12,126
AG2-441
14.1 MW3.0%$15,157
AG2-442
20.1 MW4.3%$21,562
AG2-566
6.4 MW1.4%$6,821
AG2-570
23.3 MW5.0%$25,024
AG2-571
3.0 MW0.6%$3,168
AG2-581
10.5 MW2.3%$11,289
AG2-583
32.8 MW7.0%$35,169
AH1-056
16.6 MW3.6%$17,769
AH1-241
13.8 MW3.0%$14,838
AH1-377
28.4 MW6.1%$30,476
AH1-408
8.3 MW1.8%$8,960
AH1-439
23.0 MW4.9%$24,707
AH1-528
19.4 MW4.2%$20,828
AH1-546
26.4 MW5.7%$28,317
AH1-687
22.1 MW4.8%$23,765

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2064
Title
Replace 2-1590 line lead on line 2193 at Fork Union 230 kV
Description
Replace 2-1590 line lead on line 2193 at Fork Union 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$16,409
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
2.8 MW0.6%$2,954
AG2-069
4.1 MW0.9%$4,432
AG2-077
10.3 MW2.2%$11,102
AG2-088
16.7 MW3.6%$17,891
AG2-151
13.8 MW3.0%$14,838
AG2-171
8.7 MW1.9%$9,343
AG2-188
36.7 MW7.9%$39,350
AG2-198
13.5 MW2.9%$14,479
AG2-213
11.6 MW2.5%$12,458
AG2-270
15.3 MW3.3%$16,409
AG2-338
3.0 MW0.6%$3,240
AG2-339
7.5 MW1.6%$8,100
AG2-369
2.0 MW0.4%$2,192
AG2-428
9.9 MW2.1%$10,624
AG2-436
30.4 MW6.5%$32,614
AG2-440
11.3 MW2.4%$12,126
AG2-441
14.1 MW3.0%$15,157
AG2-442
20.1 MW4.3%$21,562
AG2-566
6.4 MW1.4%$6,821
AG2-570
23.3 MW5.0%$25,024
AG2-571
3.0 MW0.6%$3,168
AG2-581
10.5 MW2.3%$11,289
AG2-583
32.8 MW7.0%$35,169
AH1-056
16.6 MW3.6%$17,769
AH1-241
13.8 MW3.0%$14,838
AH1-377
28.4 MW6.1%$30,476
AH1-408
8.3 MW1.8%$8,960
AH1-439
23.0 MW4.9%$24,707
AH1-528
19.4 MW4.2%$20,828
AH1-546
26.4 MW5.7%$28,317
AH1-687
22.1 MW4.8%$23,765

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2063
Title
Wreck and rebuild 0.11 miles of 230 kV line 2193 between Fork Union and Bremo Dist with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Description
Wreck and rebuild 0.11 miles of 230 kV line 2193 between Fork Union and Bremo Dist with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Total Cost ($USD)
$418,000
Allocated Cost ($USD)
$16,270
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
2.8 MW0.7%$2,929
AG2-069
4.1 MW1.1%$4,394
AG2-077
10.3 MW2.6%$11,008
AG2-088
16.7 MW4.2%$17,747
AG2-151
13.8 MW3.5%$14,712
AG2-171
8.7 MW2.2%$9,264
AG2-188
29.6 MW7.5%$31,444
AG2-198
10.3 MW2.6%$10,919
AG2-213
8.8 MW2.2%$9,381
AG2-270
15.3 MW3.9%$16,270
AG2-338
3.0 MW0.8%$3,212
AG2-339
7.5 MW1.9%$8,031
AG2-369
2.0 MW0.5%$2,174
AG2-428
8.5 MW2.2%$9,038
AG2-436
30.4 MW7.7%$32,350
AG2-440
10.4 MW2.7%$11,108
AG2-441
13.0 MW3.3%$13,884
AG2-442
15.3 MW3.9%$16,259
AG2-566
6.4 MW1.6%$6,763
AG2-570
7.4 MW1.9%$7,857
AG2-571
3.0 MW0.8%$3,142
AG2-581
8.0 MW2.0%$8,507
AG2-583
24.9 MW6.3%$26,524
AH1-056
14.4 MW3.7%$15,298
AH1-241
13.8 MW3.5%$14,712
AH1-377
21.6 MW5.5%$22,981
AH1-408
8.3 MW2.1%$8,885
AH1-439
17.5 MW4.5%$18,634
AH1-528
14.7 MW3.7%$15,651
AH1-546
20.0 MW5.1%$21,322
AH1-687
22.2 MW5.6%$23,600

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0080
Title
Replace switch 219326 at Bremo 230 kV
Description
Replace switch 219326 at Bremo 230 kV
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$15,569
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
2.8 MW0.7%$2,803
AG2-069
4.1 MW1.1%$4,205
AG2-077
10.3 MW2.6%$10,534
AG2-088
16.7 MW4.2%$16,982
AG2-151
13.8 MW3.5%$14,079
AG2-171
8.7 MW2.2%$8,865
AG2-188
29.6 MW7.5%$30,090
AG2-198
10.3 MW2.6%$10,449
AG2-213
8.8 MW2.2%$8,977
AG2-270
15.3 MW3.9%$15,569
AG2-338
3.0 MW0.8%$3,074
AG2-339
7.5 MW1.9%$7,685
AG2-369
2.0 MW0.5%$2,080
AG2-428
8.5 MW2.2%$8,649
AG2-436
30.4 MW7.7%$30,957
AG2-440
10.4 MW2.7%$10,630
AG2-441
13.0 MW3.3%$13,286
AG2-442
15.3 MW3.9%$15,559
AG2-566
6.4 MW1.6%$6,472
AG2-570
7.4 MW1.9%$7,518
AG2-571
3.0 MW0.8%$3,007
AG2-581
8.0 MW2.0%$8,140
AG2-583
24.9 MW6.3%$25,382
AH1-056
14.4 MW3.7%$14,640
AH1-241
13.8 MW3.5%$14,079
AH1-377
21.6 MW5.5%$21,991
AH1-408
8.3 MW2.1%$8,502
AH1-439
17.5 MW4.5%$17,832
AH1-528
14.7 MW3.7%$14,977
AH1-546
20.0 MW5.1%$20,404
AH1-687
22.2 MW5.6%$22,584

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2076
Title
Replace wave trap 298 WT at Bremo 230 kV
Description
Replace wave trap 298 WT at Bremo 230 kV
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$15,561
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.3 MW0.6%$2,260
AG2-069
6.5 MW0.8%$3,390
AG2-077
47.9 MW6.2%$24,866
AG2-171
16.0 MW2.1%$8,292
AG2-188
71.8 MW9.3%$37,308
AG2-198
29.4 MW3.8%$15,255
AG2-213
21.3 MW2.8%$11,057
AG2-270
30.0 MW3.9%$15,561
AG2-338
2.8 MW0.4%$1,430
AG2-339
6.9 MW0.9%$3,576
AG2-341
7.8 MW1.0%$4,052
AG2-369
3.7 MW0.5%$1,944
AG2-436
28.6 MW3.7%$14,862
AG2-440
29.3 MW3.8%$15,244
AG2-441
36.7 MW4.8%$19,055
AG2-442
41.1 MW5.3%$21,341
AG2-522
9.8 MW1.3%$5,097
AG2-541
8.0 MW1.0%$4,167
AG2-566
10.4 MW1.4%$5,425
AG2-570
7.3 MW0.9%$3,778
AG2-571
2.9 MW0.4%$1,511
AG2-581
36.5 MW4.7%$18,985
AG2-659
10.8 MW1.4%$5,596
AH1-056
33.7 MW4.4%$17,519
AH1-215
8.3 MW1.1%$4,315
AH1-314
6.0 MW0.8%$3,092
AH1-343
9.2 MW1.2%$4,774
AH1-377
63.7 MW8.3%$33,117
AH1-408
11.4 MW1.5%$5,905
AH1-439
44.8 MW5.8%$23,289
AH1-528
73.3 MW9.5%$38,070
AH1-546
49.8 MW6.5%$25,868

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2070
Title
Replace wave trap 2028WT at Fork Union 230 kV
Description
Replace wave trap 2028WT at Fork Union 230 kV
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$14,942
Time Estimate
16 to 18 Months

Contributor

FacilityContingency
6GRAPEVINE-6FORK UNION 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.1 MW1.1%$4,292
AG2-069
6.2 MW1.6%$6,439
AG2-077
11.7 MW3.0%$12,195
AG2-088
15.4 MW4.0%$16,041
AG2-151
21.6 MW5.6%$22,515
AG2-188
27.6 MW7.2%$28,680
AG2-198
9.6 MW2.5%$9,973
AG2-213
7.4 MW1.9%$7,702
AG2-270
14.4 MW3.7%$14,942
AG2-338
2.8 MW0.7%$2,922
AG2-339
7.0 MW1.8%$7,304
AG2-369
0.8 MW0.2%$884
AG2-428
7.8 MW2.0%$8,144
AG2-436
28.3 MW7.4%$29,462
AG2-440
10.2 MW2.7%$10,640
AG2-441
12.8 MW3.3%$13,300
AG2-442
14.3 MW3.7%$14,895
AG2-566
5.9 MW1.5%$6,175
AG2-570
6.9 MW1.8%$7,182
AG2-571
2.8 MW0.7%$2,872
AG2-581
7.5 MW1.9%$7,769
AG2-583
23.2 MW6.0%$24,161
AH1-056
13.4 MW3.5%$13,995
AH1-217
11.3 MW2.9%$11,798
AH1-241
21.6 MW5.6%$22,515
AH1-377
20.2 MW5.2%$20,997
AH1-439
16.3 MW4.2%$16,994
AH1-528
13.7 MW3.6%$14,269
AH1-546
18.7 MW4.9%$19,435
AH1-687
20.7 MW5.4%$21,511

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2069
Title
Replace 2-1590 AAC line lead on line 2028 at Fork Union 230 kV
Description
Replace 2-1590 AAC line lead on line 2028 at Fork Union 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$14,911
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6GRAPEVINE-6FORK UNION 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
5.4 MW1.1%$5,636
AG2-069
8.1 MW1.7%$8,454
AG2-077
15.4 MW3.2%$16,005
AG2-088
15.4 MW3.2%$15,999
AG2-151
28.4 MW5.9%$29,526
AG2-188
34.2 MW7.1%$35,506
AG2-198
12.6 MW2.6%$13,084
AG2-213
9.7 MW2.0%$10,104
AG2-270
14.4 MW3.0%$14,911
AG2-338
2.8 MW0.6%$2,916
AG2-339
7.0 MW1.5%$7,289
AG2-369
2.0 MW0.4%$2,042
AG2-428
9.1 MW1.9%$9,472
AG2-436
28.3 MW5.9%$29,388
AG2-440
13.4 MW2.8%$13,958
AG2-441
16.8 MW3.5%$17,448
AG2-442
18.8 MW3.9%$19,541
AG2-566
5.9 MW1.2%$6,162
AG2-570
21.8 MW4.5%$22,634
AG2-571
2.8 MW0.6%$2,865
AG2-581
9.8 MW2.0%$10,199
AG2-583
30.5 MW6.3%$31,692
AH1-056
15.5 MW3.2%$16,081
AH1-217
14.9 MW3.1%$15,470
AH1-241
27.0 MW5.6%$28,031
AH1-377
26.5 MW5.5%$27,548
AH1-439
21.5 MW4.5%$22,291
AH1-528
18.1 MW3.8%$18,786
AH1-546
24.6 MW5.1%$25,534
AH1-687
20.6 MW4.3%$21,427

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2073
Title
Replace 2-1590 line lead on line 2028 at Charlottesville and Mt Eagle 230 kV
Description
Replace 2-1590 line lead on line 2028 at Charlottesville and Mt Eagle 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$14,663
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
5.4 MW1.1%$5,542
AG2-069
8.1 MW1.7%$8,314
AG2-077
15.4 MW3.1%$15,739
AG2-088
15.4 MW3.1%$15,733
AG2-151
28.4 MW5.8%$29,035
AG2-171
8.1 MW1.7%$8,316
AG2-188
34.2 MW7.0%$34,915
AG2-198
12.6 MW2.6%$12,866
AG2-213
9.7 MW2.0%$9,936
AG2-270
14.4 MW2.9%$14,663
AG2-338
2.8 MW0.6%$2,868
AG2-339
7.0 MW1.4%$7,168
AG2-369
2.0 MW0.4%$2,008
AG2-428
9.1 MW1.9%$9,314
AG2-436
28.3 MW5.8%$28,899
AG2-440
13.4 MW2.7%$13,726
AG2-441
16.8 MW3.4%$17,157
AG2-442
18.8 MW3.8%$19,216
AG2-566
5.9 MW1.2%$6,060
AG2-570
21.8 MW4.5%$22,257
AG2-571
2.8 MW0.6%$2,818
AG2-581
9.8 MW2.0%$10,029
AG2-583
30.5 MW6.2%$31,165
AH1-056
15.5 MW3.2%$15,813
AH1-217
14.9 MW3.0%$15,213
AH1-241
27.0 MW5.5%$27,565
AH1-377
26.5 MW5.4%$27,090
AH1-439
21.5 MW4.4%$21,920
AH1-528
18.1 MW3.7%$18,474
AH1-546
24.6 MW5.0%$25,110
AH1-687
20.6 MW4.2%$21,071

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2071
Title
Replace 2-1590 line lead on line 2028 at Mt. Eagle 230 kV
Description
Replace 2-1590 line lead on line 2028 at Mt. Eagle 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$14,663
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
5.4 MW1.1%$5,542
AG2-069
8.1 MW1.7%$8,314
AG2-077
15.4 MW3.1%$15,739
AG2-088
15.4 MW3.1%$15,733
AG2-151
28.4 MW5.8%$29,035
AG2-171
8.1 MW1.7%$8,316
AG2-188
34.2 MW7.0%$34,915
AG2-198
12.6 MW2.6%$12,866
AG2-213
9.7 MW2.0%$9,936
AG2-270
14.4 MW2.9%$14,663
AG2-338
2.8 MW0.6%$2,868
AG2-339
7.0 MW1.4%$7,168
AG2-369
2.0 MW0.4%$2,008
AG2-428
9.1 MW1.9%$9,314
AG2-436
28.3 MW5.8%$28,899
AG2-440
13.4 MW2.7%$13,726
AG2-441
16.8 MW3.4%$17,157
AG2-442
18.8 MW3.8%$19,216
AG2-566
5.9 MW1.2%$6,060
AG2-570
21.8 MW4.5%$22,257
AG2-571
2.8 MW0.6%$2,818
AG2-581
9.8 MW2.0%$10,029
AG2-583
30.5 MW6.2%$31,165
AH1-056
15.5 MW3.2%$15,813
AH1-217
14.9 MW3.0%$15,213
AH1-241
27.0 MW5.5%$27,565
AH1-377
26.5 MW5.4%$27,090
AH1-439
21.5 MW4.4%$21,920
AH1-528
18.1 MW3.7%$18,474
AH1-546
24.6 MW5.0%$25,110
AH1-687
20.6 MW4.2%$21,071

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH3-DOM-007
Title
Replace Wave Trap 2028WT at Charlottesville
Description
Replace Wave Trap 2028WT at Charlottesville
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$14,632
Time Estimate
16 to 18 Months

Contributor

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.1 MW1.1%$4,203
AG2-069
6.2 MW1.6%$6,305
AG2-077
11.7 MW3.0%$11,942
AG2-088
15.4 MW3.9%$15,708
AG2-151
21.6 MW5.5%$22,048
AG2-171
8.1 MW2.1%$8,298
AG2-188
27.6 MW7.0%$28,085
AG2-198
9.6 MW2.4%$9,766
AG2-213
7.4 MW1.9%$7,542
AG2-270
14.4 MW3.7%$14,632
AG2-338
2.8 MW0.7%$2,862
AG2-339
7.0 MW1.8%$7,153
AG2-369
0.8 MW0.2%$865
AG2-428
7.8 MW2.0%$7,975
AG2-436
28.3 MW7.2%$28,851
AG2-440
10.2 MW2.6%$10,419
AG2-441
12.8 MW3.3%$13,024
AG2-442
14.3 MW3.6%$14,586
AG2-566
5.9 MW1.5%$6,047
AG2-570
6.9 MW1.8%$7,033
AG2-571
2.8 MW0.7%$2,813
AG2-581
7.5 MW1.9%$7,607
AG2-583
23.2 MW5.9%$23,660
AH1-056
13.4 MW3.4%$13,705
AH1-217
11.3 MW2.9%$11,553
AH1-241
21.6 MW5.5%$22,048
AH1-377
20.2 MW5.1%$20,562
AH1-439
16.3 MW4.2%$16,641
AH1-528
13.7 MW3.5%$13,973
AH1-546
18.7 MW4.8%$19,032
AH1-687
20.7 MW5.3%$21,064

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0051
Title
Wreck and rebuild 0.003 miles of 230 kV Line 296 between Sedge Hill and Alton Post (AC1-221) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 0.003 miles of 230 kV Line 296 between Sedge Hill and Alton Post (AC1-221) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$11,400
Allocated Cost ($USD)
$972
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-077
67.9 MW12.3%$1,399
AG2-171
13.1 MW2.4%$270
AG2-188
21.5 MW3.9%$442
AG2-198
19.5 MW3.5%$402
AG2-213
17.5 MW3.2%$360
AG2-270
47.2 MW8.5%$972
AG2-440
21.4 MW3.9%$441
AG2-441
26.8 MW4.8%$551
AG2-442
30.0 MW5.4%$617
AG2-541
19.1 MW3.4%$393
AG2-566
3.7 MW0.7%$76
AG2-581
50.2 MW9.1%$1,035
AG2-659
11.4 MW2.1%$234
AH1-056
20.7 MW3.7%$427
AH1-343
22.0 MW4.0%$454
AH1-377
48.4 MW8.7%$997
AH1-439
12.4 MW2.2%$254
AH1-528
100.8 MW18.2%$2,075

System Reinforcement: n9265.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9265.0 / TC1-PH2-DOM-064
Title
Replace 230 kV wave trap 259WT at Basin 230 kV (Basin - Chesterfield B).
Description
Replace 230 kV wave trap 259WT at Basin 230 kV (Basin - Chesterfield B).
Total Cost ($USD)
$396,021
Allocated Cost ($USD)
$0
Time Estimate
14 to 15 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-270 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-270 could receive cost allocation. Although AG2-270 may not presently have cost responsibility for this upgrade, AG2-270 may need this upgrade in-service to be deliverable to the PJM system. If AG2-270 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6BASIN-6CHESTF B 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9112.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9112.0 / TC1-PH2-DOM-063
Title
Wreck and Rebuild 12.4 miles of 230 kV line 259 with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 degrees C and replace line lead at Chesterfield.
Description
Wreck and Rebuild 12.4 miles of 230 kV line 259 with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 degrees C and replace line lead at Chesterfield.
Total Cost ($USD)
$87,030,447
Allocated Cost ($USD)
$0
Time Estimate
46 to 47 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-270 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-270 could receive cost allocation. Although AG2-270 may not presently have cost responsibility for this upgrade, AG2-270 may need this upgrade in-service to be deliverable to the PJM system. If AG2-270 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6BASIN-6CHESTF B 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9217.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9217.0 / TC1-PH2-DOM-028
Title
Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.
Total Cost ($USD)
$40,414,822
Allocated Cost ($USD)
$0
Time Estimate
45 to 46 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-270 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-270 could receive cost allocation. Although AG2-270 may not presently have cost responsibility for this upgrade, AG2-270 may need this upgrade in-service to be deliverable to the PJM system. If AG2-270 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6BUCKING-AH1-439 TP 230.0 kV Ckt 1 line(Any)
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line(Any)
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9220.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9220.0 / TC1-PH2-DOM-033
Title
Wreck and rebuild 15.42 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 15.42 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Total Cost ($USD)
$44,465,922
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-270 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-270 could receive cost allocation. Although AG2-270 may not presently have cost responsibility for this upgrade, AG2-270 may need this upgrade in-service to be deliverable to the PJM system. If AG2-270 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line(Any)
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3694.8
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3694.8
Title
Partial wreck and rebuild 10.34 miles of 230 kV line #249 Carson-Locks to achieve a minimum summer emergency rating of 1572 MVA.
Description
Partial wreck and rebuild 10.34 miles of 230 kV line #249 Carson-Locks to achieve a minimum summer emergency rating of 1572 MVA. Upgrade terminal equipment at Carson and Locks to not limit the new conductor rating.
Cost Information
Time Estimate
May 03 2025

Not Contingent

Note: AG2-270 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-270 is not contingent on this baseline upgrade as it is already in-service.

FacilityContingency
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.319
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.319
Title
Reconductor 230kV Line #2002 Carson – Poe. New conductor has a summer rating of 1573 MVA.
Description
Reconductor 230kV Line #2002 Carson – Poe. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Mar 20 2030

Not Contingent

Note: AG2-270 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-270 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6CARSON-6POE 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.320
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.320
Title
At Carson substation, upgrade all line #2002 terminal equipment at Carson to 4000A. CCVTs will also be replaced due to aging.
Description
At Carson substation, upgrade all line #2002 terminal equipment at Carson to 4000A. CCVTs will also be replaced due to aging.
Cost Information
Time Estimate
Mar 20 2030

Not Contingent

Note: AG2-270 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-270 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6CARSON-6POE 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.321
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.321
Title
At Poe substation, upgrade all line #2002 terminal equipment at Carson to 4000A. CCVTs will also be replaced due to aging.
Description
At Poe substation, upgrade all line #2002 terminal equipment at Carson to 4000A. CCVTs will also be replaced due to aging.
Cost Information
Time Estimate
Mar 20 2030

Not Contingent

Note: AG2-270 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-270 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6CARSON-6POE 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9200.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9200.0 / TC1-PH2-DOM-005
Title
Rebuild 11.79 miles of line 238 between Sapony and Carson with twin bundled (2) 768.2 ACSS/TW (20/7) "Maumee" conductors.
Description
Rebuild 11.79 miles of line 238 between Sapony and Carson with twin bundled (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Total Cost ($USD)
$38,691,326
Allocated Cost ($USD)
$0
Time Estimate
45 to 46 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-270 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-270 could receive cost allocation. Although AG2-270 may not presently have cost responsibility for this upgrade, AG2-270 may need this upgrade in-service to be deliverable to the PJM system. If AG2-270 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6CARSON-6SAPONY 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9201.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9201.0 / TC1-PH2-DOM-006
Title
Replace wave trap at Carson 230 kV (Carson - Sapony).
Description
Replace wave trap at Carson 230 kV (Carson - Sapony).
Total Cost ($USD)
$521,941
Allocated Cost ($USD)
$0
Time Estimate
14 to 15 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-270 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-270 could receive cost allocation. Although AG2-270 may not presently have cost responsibility for this upgrade, AG2-270 may need this upgrade in-service to be deliverable to the PJM system. If AG2-270 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6CARSON-6SAPONY 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9378.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9378.0 / TC1-PH3-DOM-010
Title
Replace existing 230/500 kV Carson transformer 2 with (4)-480 MVA single phase transformers.
Description
Replace Existing 230/500 kV Carson transformer 2 with (4)-480 MVA Single Phase transformers.
Total Cost ($USD)
$37,801,301
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2029

Contingent

Note: Based on PJM cost allocation criteria, AG2-270 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-270 could receive cost allocation. Although AG2-270 may not presently have cost responsibility for this upgrade, AG2-270 may need this upgrade in-service to be deliverable to the PJM system. If AG2-270 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6CARSON-8CARSON 230.0/500.0 kV Ckt 2 transformer(Any)

System Reinforcement: n6872
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n6872 / dom-047
Title
Wreck and rebuild 15.05 miles of 230 kV line No. 238 between Clubhouse and AE2-033 tap with (2) 768.2 ACSS/TW (20/7) at 250C.
Description
Wreck and rebuild 15.05 miles of 230 kV line No. 238 between Clubhouse and AE2-033 tap with (2) 768.2 ACSS/TW (20/7) at 250C
Total Cost ($USD)
$59,572,939
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2029

Contingent

Note: Based on PJM cost allocation criteria, AG2-270 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-270 could receive cost allocation. Although AG2-270 may not presently have cost responsibility for this upgrade, AG2-270 may need this upgrade in-service to be deliverable to the PJM system. If AG2-270 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6OTTERDAM-6CLUBHSE 230.0 kV Ckt 1 line(Any)
6ENCLAVE-6OTTERDAM 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9199.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9199.0 / TC1-PH2-DOM-004
Title
Wreck and rebuild 1.63 miles of line 2193 between Fork Union and Bremo with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C and replace line lead at Bremo.
Description
Wreck and rebuild 1.63 miles of line 2193 between Fork Union and Bremo with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C and replace line lead at Bremo.
Total Cost ($USD)
$7,947,612
Allocated Cost ($USD)
$0
Time Estimate
42 to 43 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-270 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-270 could receive cost allocation. Although AG2-270 may not presently have cost responsibility for this upgrade, AG2-270 may need this upgrade in-service to be deliverable to the PJM system. If AG2-270 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9379.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9379.0 / TC1-PH3-DOM-011
Title
Replace existing 230/500 kV Transformer 1 at Midlothian with (4)-480 MVA Single Phase transformers.
Description
Replace existing 230/500 kV Transformer 1 at Midlothian with (4)-480 MVA Single Phase 500/230 kV transformers.
Total Cost ($USD)
$37,836,293
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2029

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-270 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-270 could receive cost allocation. Although AG2-270 may not presently have cost responsibility for this upgrade, AG2-270 is a potential Aggregate Pool Contributor.

FacilityContingency
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending)
Title
Dominion work to accomodate new Person - Hendrick 230 kV tie line
Description
Add a breaker to existing three-breaker ring bus at Hendrick and construct 0.93 miles of new 230 kV line between Pesrons - Hendrick
Total Cost ($USD)
$8,894,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-270 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-270 could receive cost allocation. Although AG2-270 may not presently have cost responsibility for this upgrade, AG2-270 may need this upgrade in-service to be deliverable to the PJM system. If AG2-270 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending)
Title
DVP Rating: 961/961/1106 MVA
Description
DVP Rating: 961/961/1106 MVA
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9204.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9204.0 / TC1-PH2-DOM-014
Title
Wreck and rebuild 1.63 miles of line 238 between AE2-033 tap and Sapony with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 1.63 miles of line 238 between AE2-033 tap and Sapony with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C
Total Cost ($USD)
$6,764,273
Allocated Cost ($USD)
$0
Time Estimate
42 to 43 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-270 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-270 could receive cost allocation. Although AG2-270 may not presently have cost responsibility for this upgrade, AG2-270 may need this upgrade in-service to be deliverable to the PJM system. If AG2-270 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AG2-270 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-270 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S

System Reinforcement: b4000.355
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-270 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-270 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-270 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-270 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-270 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-270 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AG2-270 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-270 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AG2-270 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-270 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-270 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-270 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-270 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-270 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-270 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-270 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-270 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-270 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-270 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-270 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-270 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-270 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AG2-270 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-270 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AG2-270 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-270 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-270 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-270 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-270 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-270 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-1037
Title
Replace Breaker 56372 at Carson 500 kV with 5000 Amp device
Description
Replace Breaker 56372 at Carson 500 kV with 5000 Amp device
Total Cost ($USD)
$2,750,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-270 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-270 could receive cost allocation. Although AG2-270 may not presently have cost responsibility for this upgrade, AG2-270 is a potential Aggregate Pool Contributor.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-1
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-1036
Title
Wreck and rebuild 37.41 mi of 500 kV line 563 between Carson and Midlothian with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN" at 145 degrees C
Description
Wreck and rebuild 37.41 mi of 500 kV line 563 between Carson and Midlothian with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN" at 145 degrees C
Total Cost ($USD)
$157,122,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-270 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-270 could receive cost allocation. Although AG2-270 may not presently have cost responsibility for this upgrade, AG2-270 is a potential Aggregate Pool Contributor.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: n9139.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9139.0 / TC1-PH1-DOM-073
Title
Wreck and rebuild 37.41 miles of 500kV line 563 between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" and associated substation work.
Description
Wreck and rebuild 37.41 miles of 500kV transmission line 563 between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA. Remove wave traps.
Total Cost ($USD)
$245,455,768
Allocated Cost ($USD)
$0
Time Estimate
69 to 70 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-270 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-270 could receive cost allocation. Although AG2-270 may not presently have cost responsibility for this upgrade, AG2-270 is a potential Aggregate Pool Contributor.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: n9250.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9250.0 / TC1-PH2-DOM-044
Title
Construct a new 22.59 mile line between Carson and Rawlings Substations.
Description
Construct a new 22.59 mile line between Carson and Rawlings Substations.
Total Cost ($USD)
$108,728,086
Allocated Cost ($USD)
$0
Time Estimate
60 to 61 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-270 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-270 could receive cost allocation. Although AG2-270 may not presently have cost responsibility for this upgrade, AG2-270 may need this upgrade in-service to be deliverable to the PJM system. If AG2-270 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)

System Reinforcement: n9138.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9138.0 / TC1-PH1-DOM-070
Title
Wreck and rebuild 22.59 miles of Line #511 between Carson and Rawlings Substations with three (3) 1351 ACSS/TW and associated substation work.
Description
Wreck and rebuild 22.59 miles of Line 511 between Carson and Rawlings with three (3) 1351 ACSS/TW and associated substation work.
Total Cost ($USD)
$111,130,292
Allocated Cost ($USD)
$0
Time Estimate
60 to 61 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-270 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-270 could receive cost allocation. Although AG2-270 may not presently have cost responsibility for this upgrade, AG2-270 may need this upgrade in-service to be deliverable to the PJM system. If AG2-270 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)

System Reinforcement: n9191.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9191.0 / TC1-PH1-DOM-090
Title
Rebuild 41.13 miles of line 576 between North Anna and Midlothian with triple bundled (3) 1351.5 ACSR (45/7) "Dipper" conductor and associated substation work.
Description
Rebuild 41.13 miles of line 576 between North Anna and Midlothian with triple bundled (3) 1351.5 ACSR (45/7) "Dipper" conductor at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA.
Total Cost ($USD)
$256,706,175
Allocated Cost ($USD)
$0
Time Estimate
74 to 75 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-270 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-270 could receive cost allocation. Although AG2-270 may not presently have cost responsibility for this upgrade, AG2-270 is a potential Aggregate Pool Contributor.

FacilityContingency
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)
          AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-198, AG2-566
        
          AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-440, AG2-441, AG2-442
        
          AG2-068 500 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-068, AG2-069, AG2-369
        
          AG2-570 500 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-570, AG2-571
        
          AE2-094 500 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-338, AG2-339
        
          Perth 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-111, AG2-112
        
          Cashie 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-382, AH1-271
        

Attachments

AG2-270 One Line Diagram

AG2-270 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.