AG2-311 Phase I Study Report
v1.00 released 2025-10-29 20:45
Smith Mountain 138 kV
52.5 MW Capacity / 75.0 MW Energy
Introduction
This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Smith Mountain Storage, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is American Electric Power.
Preface
The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.
In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
- PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
- PJM will only perform load flow analysis during the Phase I System Impact Study.
- In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
- PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
- The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
- Identify required Interconnection Facilities to accommodate the New Service Request.
- Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
- Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.
Decision Point I Requirements
At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.
Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.
General
The Project Developer has proposed a Storage facility located in the American Electric Power zone — Bedford County, Virginia. The installed facilities will have a total capability of 75.0 MW with 52.5 MW of this output being recognized by PJM as Capacity.Project Information
Physical Interconnection Facility Study
Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.
Point of Interconnection
AG2-311 will interconnect on the American Electric Power transmission system at the Smith Mountain 138 kV Substation.
Cost Summary
The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.
Based on the Phase I SIS results, the AG2-311 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.
| Cost Summary | |||
|---|---|---|---|
| Description | Cost Allocated to AG2-311 | Cost Subject to Readiness* | |
| Transmission Owner Interconnection Facilities (TOIF) | $0 | $0 | |
| Other Scope | $0 | $0 | |
| Option To Build Oversight | $0 | $0 | |
| Physical Interconnection Network Upgrades | |||
| Stand Alone Network Upgrades | $0 | $0 | |
| Network Upgrades | $26,432,226 | $26,432,226 | |
| System Reliability Network Upgrades | |||
| Steady State Thermal & Voltage (SP & LL) | $12,008,717 | $12,008,717 | |
| Transient Stability | $0 | $0 | |
| Short Circuit | $0 | $0 | |
| Transmission Owner Analysis | |||
| SubRegional | $0 | $0 | |
| Distribution | $0 | $0 | |
| Affected System Reinforcements | |||
| AFS - PJM Violatons | $0 | $0 | |
| AFS - Non-PJM Violations | $0 | $0 | |
| Total | $38,440,943 | $38,440,943 | |
* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.
Definitions
Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.
Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.
Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.
Notes
Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.
Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.
Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.
Readiness Deposit
Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.
During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.
Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.
Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))
Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.
Readiness Deposit #2 Due for Project AG2-311
Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.
| Readiness Deposit | |||
|---|---|---|---|
| Project ID | 10% of cost allocation for Phase I Network Upgrades | Readiness Deposit #1 Received (RD1) | Readiness Deposit #2 (RD2) for AG2-311 Project due at DP1 |
| A | B | A - B | |
| AG2-311 | $3,844,094 | $300,000 | $3,544,094 |
Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.
For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.
Transmission Owner Scope of Work
The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.
| Network Upgrades | |||
|---|---|---|---|
| RTEP ID | Description | Total Cost ($USD) | Allocated Cost ($USD) |
| (Pending) | AEP will construct a new circuit breaker and line exit for the new generator as well as the associated facilities required to support the interconnection. | $26,432,226 | $26,432,226 |
Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 24 to 30 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.
The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.
Transmission Owner Analysis
No Transmission Owner impacts identified.
Developer Requirements
The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.
To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.
Revenue Metering and SCADA Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.
Summer Peak Analysis
The New Service Request AG2-311 was evaluated as a 75.0 MW (52.5 MW Capacity) injection in the AEP area.
AG2-311 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 75.0 MW (75.0 MW under study).
Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.
| Study | Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Final Cycle Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
|---|---|---|---|---|---|---|---|---|---|---|---|
| GD2 | AEP | 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line | AEP_P7-1_#10817___SRT-A | Tower | AC | 120.87 % | 388.0 | B | 468.97 | 19.05 | |
| GD2 | AEP | 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line | AEP_P4_#10213_05CLOVRD 138_A_SRT-A | Breaker | AC | 113.77 % | 388.0 | B | 441.43 | 16.7 | |
| GD2 | AEP | 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line | AEP_P4_#10210_05CLOVRD 138_A2_SRT-A | Breaker | AC | 113.52 % | 388.0 | B | 440.44 | 16.68 | |
| GD2 | AEP | 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line | AEP_P7-1_#10808___SRT-A | Tower | AC | 110.55 % | 388.0 | B | 428.94 | 19.06 | |
| GD2 | AEP | 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line | AEP_P2-2_#6213_05WLAKE 138_1_SRT-A | Bus | AC | 104.39 % | 388.0 | B | 405.03 | 14.46 | |
| GD2 | AEP | 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line | AEP_P2-2_#6212_05WLAKE 138_2_SRT-A | Bus | AC | 102.03 % | 388.0 | B | 395.89 | 14.46 | |
| GD2 | AEP/DVP | 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | AP_P1-3_MP-765-501T_SRT-A | Single | AC | 121.06 % | 3393.4 | B | 4107.97 | 11.94 | |
| GD2 | AEP/DVP | 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | AP_P2-3_MP-500-020_SRT-SL | Breaker | AC | 117.02 % | 3610.0 | B | 4224.55 | 11.95 | |
| GD2 | AEP/DVP | 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | AP_P2-3_MP-500-021_SRT-SL | Breaker | AC | 116.77 % | 3610.0 | B | 4215.43 | 11.94 | |
| GD2 | AEP/DVP | 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | AEP_P4_#37_05MOUNTN 765_B1_SRT-A | Breaker | AC | 116.68 % | 3610.0 | B | 4211.98 | 11.94 | |
| GD2 | AEP/DVP | 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | AEP_P4_#2942_05KAMMER 765_PP_SRT-A | Breaker | AC | 116.36 % | 3610.0 | B | 4200.43 | 11.94 | |
| GD2 | AEP | 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line | DVP_P4-2: 151T1047_SRT-A | Breaker | AC | 134.96 % | 245.0 | B | 330.65 | 6.75 | |
| GD2 | AEP | 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line | DVP_P4-2: 104702_SRT-A | Breaker | AC | 134.95 % | 245.0 | B | 330.63 | 6.75 | |
| GD2 | AEP | 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line | DVP_P4-2: 1016T1047_SRT-A | Breaker | AC | 128.07 % | 245.0 | B | 313.77 | 6.76 | |
| GD2 | AEP | 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line | DVP_P4-2: 101672_SRT-A | Breaker | AC | 128.05 % | 245.0 | B | 313.73 | 6.76 | |
| GD2 | AEP | 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line | DVP_P4-2: 104772_SRT-A | Breaker | AC | 126.62 % | 245.0 | B | 310.21 | 6.76 | |
| GD2 | AEP | 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line | DVP_P1-2: LN 1047_SRT-A | Single | AC | 106.29 % | 245.0 | B | 260.4 | 6.75 | |
| GD2 | AEP | 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line | DVP_P1-2: LN 1016_SRT-A-1 | Single | AC | 101.51 % | 245.0 | B | 248.71 | 6.76 | |
| GD2 | AEP | 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line | AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A | Bus | AC | 100.25 % | 245.0 | B | 245.61 | 6.43 | |
| GD2 | AEP | 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line | AEP_P7-1_#10778___SRT-A | Tower | AC | 100.25 % | 245.0 | B | 245.6 | 6.43 | |
| GD2 | AEP/DVP | 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | Base Case | Single | AC | 118.66 % | 192.7 | A | 228.66 | 10.45 | |
| GD2 | AEP/DVP | 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | AEP_P4_#10162_05EDAN 1 138_P_SRT-A | Breaker | AC | 117.03 % | 284.0 | B | 332.36 | 13.87 | |
| GD2 | AEP/DVP | 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | AEP_P4_#10164_05EDAN 2 138_M_SRT-A | Breaker | AC | 116.49 % | 284.0 | B | 330.82 | 13.82 | |
| GD2 | AEP/DVP | 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A | Bus | AC | 115.7 % | 284.0 | B | 328.58 | 13.82 | |
| GD2 | AEP/DVP | 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | AEP_P7-1_#10778___SRT-A | Tower | AC | 115.69 % | 284.0 | B | 328.56 | 13.82 | |
| GD2 | AEP/DVP | 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | AEP_P4_#10687_05EDAN 2 138_N_SRT-A | Breaker | AC | 115.68 % | 284.0 | B | 328.54 | 13.82 | |
| GD2 | AEP/DVP | 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | AEP_P4_#8676_05EDANV2 230_S_SRT-A | Breaker | AC | 115.67 % | 284.0 | B | 328.5 | 13.82 | |
| GD2 | AEP/DVP | 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | AEP_P1-2_#5366_SRT-A-1 | Single | AC | 110.86 % | 266.96 | B | 295.95 | 13.81 | |
| GD2 | AEP/DVP | 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | AEP_P1-3_#10688_05EDANV2 230_4_SRT-A | Single | AC | 110.35 % | 266.96 | B | 294.6 | 13.82 | |
| IPD | AEP/DVP | 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | Base Case | Single | AC | 106.65 % | 192.7 | A | 205.51 | 14.93 | |
| GD2 | AEP/DVP | 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | AEP_P4_#10213_05CLOVRD 138_A_SRT-A | Breaker | AC | 106.32 % | 284.0 | B | 301.96 | 14.26 | |
| GD2 | AEP/DVP | 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | AEP_P7-1_#10781___SRT-A-1 | Tower | AC | 100.01 % | 284.0 | B | 284.01 | 11.5 | |
| GD2 | AEP | 05OTTER-05JOHNMT 138.0 kV Ckt 1 line | DVP_P4-2: 151T1047_SRT-A | Breaker | AC | 136.34 % | 245.0 | B | 334.02 | 6.75 | |
| GD2 | AEP | 05OTTER-05JOHNMT 138.0 kV Ckt 1 line | DVP_P4-2: 104702_SRT-A | Breaker | AC | 136.33 % | 245.0 | B | 334.0 | 6.75 | |
| GD2 | AEP | 05OTTER-05JOHNMT 138.0 kV Ckt 1 line | DVP_P4-2: 1016T1047_SRT-A | Breaker | AC | 129.43 % | 245.0 | B | 317.11 | 6.76 | |
| GD2 | AEP | 05OTTER-05JOHNMT 138.0 kV Ckt 1 line | DVP_P4-2: 101672_SRT-A | Breaker | AC | 129.42 % | 245.0 | B | 317.07 | 6.76 | |
| GD2 | AEP | 05OTTER-05JOHNMT 138.0 kV Ckt 1 line | DVP_P4-2: 104772_SRT-A | Breaker | AC | 127.97 % | 245.0 | B | 313.53 | 6.76 | |
| GD2 | AEP | 05OTTER-05JOHNMT 138.0 kV Ckt 1 line | DVP_P1-2: LN 1047_SRT-A | Single | AC | 107.67 % | 245.0 | B | 263.78 | 6.75 | |
| GD2 | AEP | 05OTTER-05JOHNMT 138.0 kV Ckt 1 line | DVP_P1-2: LN 1016_SRT-A-1 | Single | AC | 102.87 % | 245.0 | B | 252.04 | 6.76 | |
| GD2 | AEP | 05OTTER-05JOHNMT 138.0 kV Ckt 1 line | AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A | Bus | AC | 101.55 % | 245.0 | B | 248.8 | 6.43 | |
| GD2 | AEP | 05OTTER-05JOHNMT 138.0 kV Ckt 1 line | AEP_P7-1_#10778___SRT-A | Tower | AC | 101.55 % | 245.0 | B | 248.79 | 6.43 | |
| GD2 | AEP | 05OTTER-05JOHNMT 138.0 kV Ckt 1 line | DVP_P2-2: ALTAVISTA 115KV_SRT-A | Bus | AC | 100.37 % | 245.0 | B | 245.9 | 7.7 | |
| GD2 | AEP | 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line | AEP_P4_#10162_05EDAN 1 138_P_SRT-A | Breaker | AC | 113.61 % | 255.0 | B | 289.71 | 13.88 | |
| GD2 | AEP | 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line | AEP_P4_#10164_05EDAN 2 138_M_SRT-A | Breaker | AC | 113.02 % | 255.0 | B | 288.2 | 13.83 | |
| GD2 | AEP | 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line | AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A | Bus | AC | 112.15 % | 255.0 | B | 285.97 | 13.83 | |
| GD2 | AEP | 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line | AEP_P7-1_#10778___SRT-A | Tower | AC | 112.13 % | 255.0 | B | 285.94 | 13.83 | |
| GD2 | AEP | 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line | AEP_P4_#10687_05EDAN 2 138_N_SRT-A | Breaker | AC | 112.13 % | 255.0 | B | 285.92 | 13.83 | |
| GD2 | AEP | 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line | AEP_P4_#8676_05EDANV2 230_S_SRT-A | Breaker | AC | 112.11 % | 255.0 | B | 285.89 | 13.83 | |
| GD2 | AEP | 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line | AEP_P4_#10213_05CLOVRD 138_A_SRT-A | Breaker | AC | 101.78 % | 255.0 | B | 259.55 | 14.28 | |
| GD2 | DVP | 3CRSTL HILL-AC1-222 TAP 115.0 kV Ckt 1 line | AEP_P1-2_#7422_16_SRT-A | Single | AC | 106.3 % | 285.76 | B | 303.76 | 4.8 | |
| GD2 | DVP | 3CRSTL HILL-AC1-222 TAP 115.0 kV Ckt 1 line | AEP_P4_#10162_05EDAN 1 138_P_SRT-A | Breaker | AC | 100.59 % | 350.0 | C | 352.07 | 6.09 | |
| GD2 | DVP | 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line | AEP_P1-2_#7422_16_SRT-A | Single | AC | 116.18 % | 285.76 | B | 331.99 | 4.79 | |
| GD2 | DVP | 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line | AEP_P4_#10162_05EDAN 1 138_P_SRT-A | Breaker | AC | 111.45 % | 350.0 | C | 390.08 | 6.07 | |
| GD2 | DVP | 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line | AEP_P4_#10164_05EDAN 2 138_M_SRT-A | Breaker | AC | 109.96 % | 350.0 | C | 384.85 | 5.99 | |
| GD2 | DVP | 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line | AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A | Bus | AC | 109.7 % | 350.0 | C | 383.94 | 5.99 | |
| GD2 | DVP | 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line | AEP_P7-1_#10778___SRT-A | Tower | AC | 109.69 % | 350.0 | C | 383.92 | 5.99 | |
| GD2 | DVP | 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line | DVP_P1-2: LN 553_SRT-S | Single | AC | 107.38 % | 285.76 | B | 306.86 | 4.38 | |
| GD2 | DVP | 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line | AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A | Bus | AC | 105.51 % | 350.0 | C | 369.27 | 5.58 | |
| GD2 | AEP/DVP | 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line | DVP_P4-2: 151T1047_SRT-A | Breaker | AC | 137.18 % | 245.0 | B | 336.08 | 6.75 | |
| GD2 | AEP/DVP | 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line | DVP_P4-2: 104702_SRT-A | Breaker | AC | 137.17 % | 245.0 | B | 336.06 | 6.75 | |
| GD2 | AEP/DVP | 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line | DVP_P4-2: 1016T1047_SRT-A | Breaker | AC | 130.26 % | 245.0 | B | 319.14 | 6.76 | |
| GD2 | AEP/DVP | 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line | DVP_P4-2: 101672_SRT-A | Breaker | AC | 130.24 % | 245.0 | B | 319.1 | 6.76 | |
| GD2 | AEP/DVP | 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line | DVP_P4-2: 104772_SRT-A | Breaker | AC | 128.8 % | 245.0 | B | 315.55 | 6.76 | |
| GD2 | AEP/DVP | 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line | DVP_P1-2: LN 1047_SRT-A | Single | AC | 115.43 % | 230.3 | B | 265.84 | 6.75 | |
| GD2 | AEP/DVP | 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line | DVP_P1-2: LN 1016_SRT-A-1 | Single | AC | 110.32 % | 230.3 | B | 254.07 | 6.76 | |
| GD2 | AEP/DVP | 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line | Base Case | Single | AC | 104.83 % | 156.98 | A | 164.56 | 5.0 | |
| GD2 | AEP/DVP | 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line | AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A | Bus | AC | 102.33 % | 245.0 | B | 250.71 | 6.43 | |
| GD2 | AEP/DVP | 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line | AEP_P7-1_#10778___SRT-A | Tower | AC | 102.33 % | 245.0 | B | 250.7 | 6.43 | |
| GD2 | AEP/DVP | 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line | DVP_P2-2: ALTAVISTA 115KV_SRT-A | Bus | AC | 101.22 % | 245.0 | B | 247.98 | 7.7 | |
| GD2 | DVP | 4ALTVSTA-3ALTVSTA 138.0/115.0 kV Ckt 1 transformer | DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | Single | AC | 107.36 % | 123.7 | B | 132.8 | 4.91 | |
| GD2 | DVP | 6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line | DVP_P1-2: LN 570_SRT-A-3 | Single | AC | 108.64 % | 814.98 | B | 885.41 | 4.59 | |
| GD2 | DVP | 6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line | DVP_P1-2: LN 570_SRT-A-2 | Single | AC | 106.47 % | 814.98 | B | 867.67 | 4.59 | |
| GD2 | DVP | 6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line | DVP_P1-2: LN 570_SRT-A-3 | Single | AC | 103.53 % | 814.98 | B | 843.75 | 4.61 | |
| GD2 | DVP | 6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line | DVP_P1-2: LN 570_SRT-A-2 | Single | AC | 101.35 % | 814.98 | B | 825.97 | 4.61 | |
| GD2 | DVP | AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line | AEP_P1-2_#7422_16_SRT-A | Single | AC | 118.6 % | 285.76 | B | 338.91 | 4.79 | |
| GD2 | DVP | AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line | AEP_P4_#10162_05EDAN 1 138_P_SRT-A | Breaker | AC | 113.44 % | 350.0 | C | 397.05 | 6.07 | |
| GD2 | DVP | AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line | AEP_P4_#10164_05EDAN 2 138_M_SRT-A | Breaker | AC | 111.95 % | 350.0 | C | 391.83 | 5.99 | |
| GD2 | DVP | AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line | AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A | Bus | AC | 111.69 % | 350.0 | C | 390.93 | 5.99 | |
| GD2 | DVP | AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line | AEP_P7-1_#10778___SRT-A | Tower | AC | 111.69 % | 350.0 | C | 390.91 | 5.99 | |
| GD2 | DVP | AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line | DVP_P1-2: LN 553_SRT-S | Single | AC | 109.82 % | 285.76 | B | 313.83 | 4.38 | |
| GD2 | DVP | AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line | AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A | Bus | AC | 107.51 % | 350.0 | C | 376.28 | 5.58 | |
| GD2 | DVP | AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line | AEP_P2-2_#17572_05MUSEVILLE 138_1_SRT-A | Bus | AC | 100.61 % | 350.0 | C | 352.15 | 5.97 | |
| GD2 | AEP | AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line | AEP_P7-1_#10817___SRT-A | Tower | AC | 121.83 % | 392.0 | B | 477.57 | 19.05 | |
| GD2 | AEP | AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line | AEP_P4_#10213_05CLOVRD 138_A_SRT-A | Breaker | AC | 114.79 % | 392.0 | B | 450.0 | 16.7 | |
| GD2 | AEP | AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line | AEP_P4_#10210_05CLOVRD 138_A2_SRT-A | Breaker | AC | 114.54 % | 392.0 | B | 449.01 | 16.68 | |
| GD2 | AEP | AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line | AEP_P7-1_#10808___SRT-A | Tower | AC | 111.62 % | 392.0 | B | 437.54 | 19.06 | |
| GD2 | AEP | AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line | AEP_P2-2_#6213_05WLAKE 138_1_SRT-A | Bus | AC | 105.51 % | 392.0 | B | 413.6 | 14.46 | |
| GD2 | AEP | AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line | AEP_P2-2_#6212_05WLAKE 138_2_SRT-A | Bus | AC | 103.18 % | 392.0 | B | 404.45 | 14.46 | |
| GD2 | DVP | AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line | AEP_P1-2_#7422_16_SRT-A | Single | AC | 109.29 % | 285.76 | B | 312.32 | 4.8 | |
| GD2 | DVP | AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line | AEP_P4_#10162_05EDAN 1 138_P_SRT-A | Breaker | AC | 103.04 % | 350.0 | C | 360.64 | 6.09 | |
| GD2 | DVP | AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line | AEP_P4_#10164_05EDAN 2 138_M_SRT-A | Breaker | AC | 101.53 % | 350.0 | C | 355.37 | 6.0 | |
| GD2 | DVP | AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line | AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A | Bus | AC | 101.27 % | 350.0 | C | 354.46 | 6.0 | |
| GD2 | DVP | AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line | AEP_P7-1_#10778___SRT-A | Tower | AC | 101.27 % | 350.0 | C | 354.44 | 6.0 | |
| GD2 | DVP | AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line | DVP_P1-2: LN 553_SRT-S | Single | AC | 100.5 % | 285.76 | B | 287.19 | 4.39 |
Winter Peak Analysis
The New Service Request AG2-311 was evaluated as a 75.0 MW (52.5 MW Capacity) injection in the AEP area.
AG2-311 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 75.0 MW (75.0 MW under study).
Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.
| Study | Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Final Cycle Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
|---|---|---|---|---|---|---|---|---|---|---|---|
| GD2 | AEP/DVP | 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | AEP_P1-2_#3174_6_SRT-A | Single | AC | 101.09 % | 304.56 | B | 307.89 | 9.13 | |
| GD2 | AEP/DVP | 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | AEP_P1-3_#1372_05JOSHUA 765_1_SRT-A | Single | AC | 100.99 % | 304.56 | B | 307.57 | 9.13 |
Light Load Analysis
The New Service Request AG2-311 was evaluated as a 75.0 MW injection and 75.0 MW withdrawal in the AEP area.
AG2-311 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 75.0 MW (75.0 MW under study).
Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.
| Study | Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Final Cycle Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
|---|---|---|---|---|---|---|---|---|---|---|---|
| GD2 | AEP | 05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line | AEP_P4_#10294_05NEWLDN 138_D_SRT-A | Breaker | AC | 110.7 % | 255.0 | B | 282.29 | 11.01 | |
| GD2 | AEP | 05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line | AEP_P4_#10293_05NEWLDN 138_C_SRT-A | Breaker | AC | 110.51 % | 255.0 | B | 281.79 | 11.01 | |
| GD2 | AEP | 05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line | AEP_P4_#10292_05NEWLDN 138_E_SRT-A | Breaker | AC | 110.5 % | 255.0 | B | 281.78 | 11.01 | |
| GD2 | AEP | 05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line | AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A | Bus | AC | 110.5 % | 255.0 | B | 281.78 | 11.01 | |
| GD2 | AEP | 05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line | DVP_P4-2: 151T1047_SRT-A | Breaker | AC | 106.71 % | 255.0 | B | 272.1 | 12.14 | |
| GD2 | AEP | 05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line | DVP_P4-2: 104702_SRT-A | Breaker | AC | 106.67 % | 255.0 | B | 272.01 | 12.13 | |
| GD2 | AEP | 05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line | DVP_P1-2: LN 13_SRT-A | Single | AC | 105.36 % | 255.0 | B | 268.67 | 11.01 | |
| GD2 | AEP | 05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line | AEP_P1-2_#375_5201_SRT-A | Single | AC | 105.36 % | 255.0 | B | 268.67 | 11.01 | |
| GD2 | AEP | 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line | AEP_P1-2_#311_5_SRT-A | Single | AC | 125.64 % | 296.0 | B | 371.9 | 19.35 | |
| GD2 | AEP | 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line | AEP_P4_#7587_05J.FERR 765_B_SRT-A | Breaker | AC | 123.54 % | 296.0 | B | 365.69 | 19.36 | |
| GD2 | AEP | 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line | AEP_P4_#2914_05J.FERR 765_B2_SRT-A | Breaker | AC | 123.21 % | 296.0 | B | 364.71 | 19.35 | |
| GD2 | AEP | 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line | AEP_P7-1_#10781___SRT-A-3 | Tower | AC | 103.45 % | 296.0 | B | 306.2 | 13.79 | |
| GD2 | DVP | 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer | DVP_P1-3: 4ALTVSTA-TX#4_SRT-A | Single | AC | 119.84 % | 139.4 | B | 167.06 | 7.09 | |
| GD2 | DVP | 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer | DVP_P1-3: 4ALTVSTA-TX#3_SRT-A | Single | AC | 105.36 % | 168.45 | B | 177.48 | 7.54 |
Short Circuit Analysis
Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.
Stability Analysis
Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.
Reactive Power Analysis
Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.
Steady-State Voltage Analysis
Steady State Voltage Analysis is Not Required.
New Service Request Dependencies
The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.
| New Service Requests Dependencies | ||
|---|---|---|
| Project ID | Project Name | Status |
| AA1-018 | Powerton-Goodings Grove | In Service |
| AA1-038 | Lexington-Low Moor 230kV | Under Construction |
| AA1-139 | Hickory-Shawboro 230kV | In Service |
| AB1-006 | Meadow Lake 345kV | In Service |
| AB1-027 | Old Church 34.5 KV | In Service |
| AB1-081 | Anaconda-Mayo Dunbar 115kV | In Service |
| AB1-180 | Pine View 12kV | In Service |
| AB2-022 | Elizabeth City 34.5kV | In Service |
| AB2-025 | Sapony 34.5kV | In Service |
| AB2-026 | Powhatan 34.5kV | In Service |
| AB2-029 | Remington 34.5kV | In Service |
| AB2-045 | Buckingham 34.5kV | In Service |
| AB2-059 | Benson-Dunbar 115kV | In Service |
| AB2-060 | Chase City-Lunenburg 115kV | In Service |
| AB2-070 | Mt. Pulaski-Brokaw | In Service |
| AB2-077 | Buggs Island-Chase City 115kV | In Service |
| AB2-078 | Buggs Island-Chase City 115kV | In Service |
| AB2-079 | Buggs Island-Chase City 115kV | In Service |
| AB2-134 | Hopewell-Surry 230kV | In Service |
| AB2-158 | Louisa-South Anna 230kV | In Service |
| AB2-190 | Hopewell-Surry 230kV | In Service |
| AC1-001 | Delano 138kV | In Service |
| AC1-027 | Pendleton 34.5kV | In Service |
| AC1-033 | Kewanee 138 kV | In Service |
| AC1-034 | Heartsease DP - Mayo Dunbar 115kV | Suspended |
| AC1-036 | Twittys Creek 34.5kV | In Service |
| AC1-042 | Altavista-Mt. Airy 69kV | In Service |
| AC1-053 | Lanesville-Brokaw | Partially in Service - Under Construction |
| AC1-074 | Jacksonville-Renaker 138kV I | In Service |
| AC1-075 | Perth-Hickory Grove 115kV | In Service |
| AC1-076 | Locust Grove-Paytes 115kV | In Service |
| AC1-082 | Ravenswood-Hemlock 69kV | Under Construction |
| AC1-085 | Stuart-Clinton 345kV | In Service |
| AC1-089 | Hillsboro-Wildcat 138kV | In Service |
| AC1-101 | Johns Creek-Excel 138kV I | Suspended |
| AC1-102 | Johns Creek-Excel 138kV II | Suspended |
| AC1-105 | Halifax-Mt. Laurel 115kV | In Service |
| AC1-111 | Aurora 138kV | In Service |
| AC1-118 | Westmoreland 34.5kV | In Service |
| AC1-120 | Mitchell-Mountain Run 115kV | Engineering & Procurement |
| AC1-121 | Mitchell-Mountain Run 115kV | Engineering & Procurement |
| AC1-122 | Smith Mountain-Candler's Mountain 138kV | In Service |
| AC1-145 | Gretna DP 69 kV | In Service |
| AC1-147 | Grassfield 34.5kV | In Service |
| AC1-158 | Spotsylvania 500kV | In Service |
| AC1-161 | Septa 500kV | In Service |
| AC1-168 | Kewanee-Streator | Suspended |
| AC1-174 | Losantville 345kV | In Service |
| AC1-175 | Losantville 345kV | In Service |
| AC1-188 | Rio-Lick 138kV | Engineering & Procurement |
| AC1-191 | Elmont 115kV | Engineering & Procurement |
| AC1-194 | Elk 138kV | Active |
| AC1-214 | Crescent Ridge | In Service |
| AC1-221 | Halifax-Person 230kV | In Service |
| AC1-222 | Crystal Hill-Halifax 115kV | In Service |
| AC2-012 | Grassfield-Great Bridge 115kV | In Service |
| AC2-060 | Buckskin 69kV | In Service |
| AC2-061 | Hillsboro-Clinton 138kV | In Service |
| AC2-075 | Jacksonville-Renaker 138 kV | In Service |
| AC2-088 | S. Bethel-Brown 69kV | In Service |
| AC2-090 | Losantville 345kV | In Service |
| AC2-100 | Halifax-Person 230kV | In Service |
| AC2-111 | College Corner 138kV | Engineering & Procurement |
| AC2-123 | Jacksons Ferry 138kV | In Service |
| AC2-137 | Elko 34.5kV | In Service |
| AC2-138 | Northern Neck 34.5kV | In Service |
| AC2-141 | Septa 500kV | Engineering & Procurement |
| AC2-157 | Sullivan 345 kV | Under Construction |
| AC2-165 | Bremo-Powhatan 230kV | Suspended |
| AD1-013 | Twombly Road 138kV | Engineering & Procurement |
| AD1-017 | Smith Mountain-Bearskin 138 kV | In Service |
| AD1-025 | Hopewell-Surry 230 kV | Under Construction |
| AD1-033 | Fentress-Landstown 230 kV | In Service |
| AD1-041 | Harmony Village-Shackleford 115 kV | In Service |
| AD1-063 | Harmony Village 34.5 kV | In Service |
| AD1-082 | Bakers Pond-Ivor 115kV | In Service |
| AD1-087 | Clover-Sedge Hill 230 kV | In Service |
| AD1-105 | Kings Dominion DP 115 kV | Under Construction |
| AD1-115 | Mountain Run-Mitchell 115 kV | Engineering & Procurement |
| AD1-128 | Modoc-Delaware 138 kV | Partially in Service - Under Construction |
| AD1-136 | South Bethel-Brown 69 kV | In Service |
| AD1-144 | Kings Fork 34.5 kV | In Service |
| AD1-152 | Clover-Sedge Hill 230 kV | In Service |
| AD1-155 | Meadow Brook-Strasburg 138 kV | In Service |
| AD2-022 | East Danville - Roxborough 230 kV | Engineering & Procurement |
| AD2-023 | East Danville - Roxborough 230 kV | Engineering & Procurement |
| AD2-030 | Wan 34.5 kV | In Service |
| AD2-031 | Martinsville-Wilmington 69 kV | In Service |
| AD2-033 | Chase City-Lunenburg 115 kV | Under Construction |
| AD2-038 | Powerton-Nevada 345 kV | Under Construction |
| AD2-048 | Cynthia-Headquarters 69 kV | Under Construction |
| AD2-066 | Mazon-Crescent Ridge 138 kV | Engineering & Procurement |
| AD2-071 | Strawton-Deer Creek 138 kV | Suspended |
| AD2-073 | Sanders DP 230 kV | In Service |
| AD2-074 | Garner DP-Lancaster 115 kV | Engineering & Procurement |
| AD2-085 | Myrtle-Windsor DP 115kV | Engineering & Procurement |
| AD2-100 | Kincaid-Pana 345 kV | Suspended |
| AD2-131 | Kincaid-Pana 345kV | Suspended |
| AD2-134 | Shady Oaks | Partially in Service - Under Construction |
| AD2-160 | Hickory-Moyock 230kV | In Service |
| AD2-172 | Lena 138kV | In Service |
| AD2-179 | Morgans Cut-Glen Lyn 138kV | Suspended |
| AD2-202 | Clover-Sedge Hill 230kV | In Service |
| AE1-040 | Greenfield 69 kV | In Service |
| AE1-072 | Shawboro-Sligo 230 kV | Under Construction |
| AE1-074 | Winterpock 34.5 kV | Under Construction |
| AE1-075 | Powhatan 34.5 kV | In Service |
| AE1-100 | Axton 138 kV | In Service |
| AE1-113 | Mole Creek 345 kV | Engineering & Procurement |
| AE1-114 | Maryland-Lancaster 138 kV | Active |
| AE1-155 | Garner-Northern Neck 115 kV | In Service |
| AE1-162 | Smithfield 34.5 kV | In Service |
| AE1-163 | Powerton-Nevada 345 kV | Engineering & Procurement |
| AE1-172 | Loretto-Wilton Center | Active |
| AE1-175 | Light Foot 34.5 kV | In Service |
| AE1-176 | Roanoke-Vinton 12 kV (Niagara Hydro) | In Service |
| AE1-190 | Harmony Village-Shackleford 115 kV | Partially in Service - Under Construction |
| AE1-191 | Harmony Village-Shackleford 115 kV | Partially in Service - Under Construction |
| AE1-205 | McLean 345 kV | Engineering & Procurement |
| AE1-207 | Mississinewa-Gaston 138 kV | Suspended |
| AE1-209 | Desoto 345 kV | Suspended |
| AE1-210 | Desoto 345 kV | Suspended |
| AE1-212 | Grandview-Clifftop 138 kV | Suspended |
| AE1-250 | Smith Mountain-E. Danville 138 kV | Engineering & Procurement |
| AE2-029 | Grottoes-Merck 115kV | Under Construction |
| AE2-035 | Lena 138 kV | In Service |
| AE2-047 | Ridgeway-Solite 69 kV | Engineering & Procurement |
| AE2-071 | Patton Rd-Summer Shade 69 kV | In Service |
| AE2-092 | Kidds Store-Sherwood 115 kV | Engineering & Procurement |
| AE2-140 | Axton-Danville 138 kV | Suspended |
| AE2-160 | Kanawha River 138 kV | Engineering & Procurement |
| AE2-166 | Stockton 138 kV | Suspended |
| AE2-172 | Mississinewa-Gaston 138 kV | Suspended |
| AE2-173 | McLean 345 kV | Active |
| AE2-185 | Gladys DP-Stonemill Switching Station 69 kV | Active |
| AE2-187 | Shockoe DP-Chatham 69 kV | Active |
| AE2-212 | Harrowgate 34 kV | Engineering & Procurement |
| AE2-220 | Losantville 345 kV | Engineering & Procurement |
| AE2-221 | Clinton-Stuart 345 kV | Under Construction |
| AE2-223 | McLean 345 kV | Active |
| AE2-230 | Bartonsville-Meadow Brook 138 kV | In Service |
| AE2-253 | Hickory-Moyock 230 kV | In Service |
| AE2-254 | Garrard County-Tommy-Gooch 69 kV | In Service |
| AE2-255 | Molecreek 345 kV | Engineering & Procurement |
| AE2-259 | Curdsville-Willis Mtn 115 kV | Engineering & Procurement |
| AE2-261 | Kincaid-Pana 345 kV | Active |
| AE2-267 | Woodsdale 345 kV | Engineering & Procurement |
| AE2-281 | Powerton-Nevada 345 kV | Engineering & Procurement |
| AE2-283 | Gladys-Stone Mill 69 kV | Active |
| AE2-291 | Grit DP-Perth 115 kV | Active |
| AE2-297 | Madison-Tanners Creek 138 kV | In Service |
| AE2-308 | Three Forks-Dale 138 kV | Active |
| AE2-315 | Yankee Tap 69 kV | In Service |
| AE2-318 | Ford-Cedarville 138 kV | Suspended |
| AE2-321 | Belvidere-Marengo 138 kV | Active |
| AE2-326 | Jacksons Ferry 138 kV | Engineering & Procurement |
| AE2-339 | Avon 138 kV | Engineering & Procurement |
| AE2-341 | Sandwich-Plano 138 kV | Active |
| AF1-030 | Sandwich-Plano 138 kV | Active |
| AF1-032 | Suffolk 34.5 kV | In Service |
| AF1-038 | Sewellton Jct-Webbs Crossroads 69 kV | Engineering & Procurement |
| AF1-042 | Garner DP-Lancaster 115 kV | Engineering & Procurement |
| AF1-045 | Cedarville-Ford 138 kV | Suspended |
| AF1-049 | Berry Hill 138 kV | Under Construction |
| AF1-050 | Summer Shade - Green County 161 kV | Engineering & Procurement |
| AF1-058 | Welco 34.5 kV | In Service |
| AF1-083 | Green County-Saloma 161 kV | Engineering & Procurement |
| AF1-088 | Sullivan 345 kV | Active |
| AF1-090 | Kincaid-Pana | Engineering & Procurement |
| AF1-124 | Harper 230 kV | Active |
| AF1-130 | Inez 138 kV | Suspended |
| AF1-162 | Inez 138 kV | Engineering & Procurement |
| AF1-203 | Patton Rd-Summer Shade 69 kV | In Service |
| AF1-204 | Eugene 345 kV | Active |
| AF1-207 | Reynolds-Olive #1 345 kV | Engineering & Procurement |
| AF1-233 | Flemingsburg – Spurlock 138kV | Active |
| AF1-249 | Nickel 12.47 kV | In Service |
| AF1-268 | Desoto-Jay 138 kV | Engineering & Procurement |
| AF1-282 | Stuart-Clinton 345 kV | Engineering & Procurement |
| AF1-283 | Stuart-Clinton 345 kV | Engineering & Procurement |
| AF1-291 | Tyler 34.5 kV | Engineering & Procurement |
| AF1-291A | Bartonsville-Meadow Brook 138 kV | In Service |
| AF1-296 | Garden Plain 138 kV | Active |
| AF1-322 | Meadow Lake 345 kV | Engineering & Procurement |
| AF1-331 | Twombley Road | Engineering & Procurement |
| AF2-008 | Sullivan 345 kV | Active |
| AF2-018 | Inez 138 kV | Engineering & Procurement |
| AF2-032 | Kincaid 345 kV | Engineering & Procurement |
| AF2-041 | Nelson-Electric Junction 345 kV | Active |
| AF2-042 | Clover-Rawlings 500 kV | Active |
| AF2-043 | Suffolk 34.5 kV | In Service |
| AF2-048 | Rio-Lick 138 kV | Engineering & Procurement |
| AF2-054 | Wan 34.5 kV | In Service |
| AF2-069 | Crescent Ridge 138 kV | Active |
| AF2-075 | Bartonsville-Meadow Brook 138 kV III | In Service |
| AF2-077 | White Marsh 34.5 kV | In Service |
| AF2-078 | Reynolds-Olive #1 345 kV | Engineering & Procurement |
| AF2-106 | Hazel Hollow-Glen Lyn #1 138 kV | Engineering & Procurement |
| AF2-107 | Clifford 138 kV | Engineering & Procurement |
| AF2-111 | North Clark-Spurlock 345 kV | Active |
| AF2-142 | Nevada 345 kV | Active |
| AF2-143 | Powerton-Nevada 345 kV | Active |
| AF2-144 | Powhatan 34.5 kV | In Service |
| AF2-173 | Desoto 345 kV | Active |
| AF2-199 | Nelson-Electric Junction 345 kV | Active |
| AF2-200 | Nelson-Electric Junction 345 kV | Active |
| AF2-225 | McLean 345 kV | Active |
| AF2-252 | Blue Mound 345 kV | Engineering & Procurement |
| AF2-291 | Sporn South-Leon 138 kV | Engineering & Procurement |
| AF2-297 | Sedge Hill 115 kV | Active |
| AF2-307 | Hope-Belvins Valley Tap 69 kV | Active |
| AF2-311 | Gilboa-Jones Branch 138 kV | Engineering & Procurement |
| AF2-316 | Gilboa-Jones Branch 138 kV II | Engineering & Procurement |
| AF2-335 | Delaware-Royerton 138 kV | Active |
| AF2-352 | Blue Mound 345 kV | Engineering & Procurement |
| AF2-365 | Munfordville KU Tap-Horse Cave Jct. 69 kV | Active |
| AF2-382 | Hurley 69 kV | Engineering & Procurement |
| AF2-392 | Nelson-Dixon 138 kV | Active |
| AF2-404 | Gladys DP-Stonemill 69 kV | Active |
| AF2-440 | Hillsboro-Middleboro 138 kV | Engineering & Procurement |
| AG1-066 | Bonnyman 69 kV | Engineering & Procurement |
| AG1-070 | Bon Ayr 69 kV | Active |
| AG1-071 | Bon Ayr 69 kV | Active |
| AG1-105 | Mount Laurel-Barnes Junction 115 kV | Active |
| AG1-107 | Hillsboro-Middleboro 138 kV | Engineering & Procurement |
| AG1-118 | Sugar Grove-Waterman 138kV | Active |
| AG1-124 | Gladstone 138 kV | Active |
| AG1-127 | Crego Rd 138 kV | Active |
| AG1-145 | Lightfoot 34.5 kV | In Service |
| AG1-226 | Dequine-Eugene 345 kV | Active |
| AG1-236 | Lanesville-Brokaw 345 kV | Active |
| AG1-237 | Dequine-Eugene 345 kV | Engineering & Procurement |
| AG1-282 | Dunnsville 34.5 kV | Engineering & Procurement |
| AG1-320 | Glendale-Stephensburg 69 kV | Active |
| AG1-341 | Summer Shade 161 kV | Active |
| AG1-342 | Dryburg 115 kV | Active |
| AG1-354 | Summershade-Green County 161 kV | Active |
| AG1-367 | DeSoto 345 kV | Active |
| AG1-374 | Blue Mound 345 kV | Active |
| AG1-405 | Walnut Grove-Asahi 69 kV | Active |
| AG1-406 | Walnut Grove-Asahi 69 kV | Active |
| AG1-460 | Kincaid-Pana 345 kV | Active |
| AG1-462 | Cordova 345 kV | Active |
| AG1-469 | Gordonsville 34.5 kV | Engineering & Procurement |
| AG1-471 | Up Church-Wayne County 69 kV | Active |
| AG1-494 | Boxwood-Riverville 138 kV | Active |
| AG1-508 | Point Lookout 69 kV | Engineering & Procurement |
| AG1-526 | West Garrard 345 kV | Active |
| AG1-555 | Dequine 345 kV | Engineering & Procurement |
| AG1-558 | Buckner 34.5 kV | Engineering & Procurement |
| AG1-559 | Caroline Pines 22 kV | Engineering & Procurement |
| AG2-068 | Heritage - Wake 500 kV | Active |
| AG2-069 | Heritage - Wake 500 kV | Active |
| AG2-072 | Rockport 765 kV | Active |
| AG2-073 | Crooksville 69 kV | Active |
| AG2-077 | Clover-Rawlings 500 kV | Active |
| AG2-081 | Mt. Sterling-Fogg Pike 69 kV | Active |
| AG2-085 | Delaware-Royerton 138 kV | Active |
| AG2-111 | Perth 34.5 kV Substation (Circuit 408) | Active |
| AG2-112 | Perth 34.5 kV Substation (Circuit 404) | Active |
| AG2-114 | Dresden-Pontiac Midpoint 345 kV | Active |
| AG2-126 | Eugene 345 kV | Active |
| AG2-152 | Banister-Bear Skin 138 kV | Active |
| AG2-159 | Williamstown 69 kV | Active |
| AG2-162 | Jefferson-Greentown 765 kV | Active |
| AG2-163 | Dequine-Eugene 345 kV | Active |
| AG2-164 | Jefferson-Greentown 765 kV | Active |
| AG2-179 | Sewellton Junction 69 kV | Active |
| AG2-184 | Harbert Metering 138 kV | Active |
| AG2-191 | Mississinewa 138 kV | Active |
| AG2-192 | Mississinewa 138 kV | Active |
| AG2-219 | Jefferson-Greentown 765 kV | Active |
| AG2-262 | Dryburg 115 kV | Active |
| AG2-272 | Berry Hill 138 kV | Active |
| AG2-298 | Sulphur Creek-Loretto 69 kV | Active |
| AG2-310 | Matt Funk 138 kV | Active |
| AG2-331 | Jefferson-Greentown 765 kV | Active |
| AG2-360 | Broadford 138 kV | Active |
| AG2-363 | Powerton 345 kV | Active |
| AG2-364 | Powerton 345 kV | Active |
| AG2-369 | Heritage - Wake 500 kV | Active |
| AG2-401 | Losantville 345 kV | Active |
| AG2-424 | Magnolia - Summersville 69 kV | Active |
| AG2-449 | Jefferson-Greentown 765 kV | Active |
| AG2-487 | Madison - Tanners Creek 138 kV | Active |
| AG2-491 | Meadow Lake 345 kV | Active |
| AG2-516 | Pecatonica 138kV | Active |
| AG2-518 | Tech Drive 138 kV | Active |
| AG2-519 | Royerton - Desoto 138 kV | Active |
| AG2-541 | Perth - Crystal Hill 115 kV | Active |
| AG2-548 | Corwin - Elk 138 kV | Active |
| AG2-568 | Stink Run – Sundial 138 kV | Active |
| AG2-570 | Heritage - Wake 500 kV | Active |
| AG2-571 | Heritage - Wake 500 kV | Active |
| AG2-575 | Crego Rd. 138 kV | Active |
| AG2-589 | Ravenswood - Hemlock 69 kV | Active |
| AG2-637 | Randolph - Hodgin 138 kV | Active |
| AG2-657 | Kanawha River - Carbondale 138 kV | Active |
| AG2-660 | Nelson-Electric Junction 345 kV | Active |
| AG2-665 | Corwin - Elk 138 kV | Active |
| AG2-670 | Green County -Taylor County Junction 161 kV | Active |
| AH1-004 | Avon - Renaker 138 kV | Active |
| AH1-034 | Patton Road Junction - Summer Shade 69 kV | Active |
| AH1-044 | Nelson - Electric Junction 345 kV | Active |
| AH1-047 | Marengo - Belvidere 138 kV | Active |
| AH1-055 | Kyger Creek - Don Marquis 345 kV | Active |
| AH1-072 | Red Onion - VC5 69 kV | Active |
| AH1-073 | Red Onion - VC5 69 kV | Active |
| AH1-098 | Wolf Glade-West Carroll 138 kV | Active |
| AH1-133 | Saltville - Tazewell 138 kV | Active |
| AH1-136 | Falcon - Middle Creek 46 kV | Active |
| AH1-144 | Peter's Mountain 138 kV | Active |
| AH1-145 | Peter's Mountain 138 kV | Active |
| AH1-146 | White Rock - Wayne 345 kV | Active |
| AH1-147 | White Rock - Wayne 345 kV | Active |
| AH1-150 | Nelson-Electric Junction 345 kV | Active |
| AH1-151 | Nelson-Electric Junction 345 kV | Active |
| AH1-164 | Oak Level - Tank Hill 138 kV | Active |
| AH1-188 | Pigeon Creek 138 kV | Active |
| AH1-196 | Prairie 345 kV | Active |
| AH1-227 | Flemming - Fremont 69 kV | Active |
| AH1-234 | Wempletown - Paddock 345 kV | Active |
| AH1-239 | Upchurch - Zula 69 kV | Active |
| AH1-269 | Claytor 138 kV | Active |
| AH1-281 | Bluegrass Parkway Tap - Woodlawn 69 kV | Active |
| AH1-285 | Sandwich 138 kV | Active |
| AH1-292 | Sullivan 345 kV | Active |
| AH1-306 | Mississinewa-Gaston 138 kV | Active |
| AH1-311 | Heartsease DP - Mayo Dunbar 115kV | Active |
| AH1-314 | East Danville 138 kV | Active |
| AH1-337 | Randolph - Hodgin 138 kV | Active |
| AH1-338 | McGirr Rd - Ritchie Road 138kV | Active |
| AH1-341 | Stillman - Dixon 138KV | Active |
| AH1-343 | Crystal Hill DP- Perth 115kV | Active |
| AH1-348 | Pound 34.5 kV | Active |
| AH1-427 | Tommy Gooch - Garrard County 69 kV | Active |
| AH1-535 | Nagel - Cane River 230 kV | Active |
| AH1-537 | Pierce - Kyger Creek 345 kV | Active |
| AH1-541 | Chestnut 345 kV | Active |
| AH1-543 | Mulberry – Tazewell 345 kV | Active |
| AH1-570 | Headquarters - Millersburg Junction 69 kV | Active |
| AH1-571 | Headquarters - Millersburg Junction 69 kV | Active |
| AH1-617 | Harbert Metering 138 kV | Active |
| AH1-644 | Spicewood Metering 138 kV | Active |
| AH1-664 | Goddard-Plumville 138 kV | Active |
| AH1-665 | Goddard-Plumsville 138 kV II | Active |
| AH1-666 | Flemingsburg - Spurlock 138 kV | Active |
| AH1-670 | Blue Mound-Chestnut 345 kV | Active |
| AH1-686 | Hanging Rock 765 kV | Active |
| AH1-702 | Byron 345 kV | Active |
| AH1-718 | Nelson 345 kV | Active |
| AH1-721 | Laurel-Cooper 161 kV | Active |
| V3-007 | Desoto-Tanners Creek #1 345kV | In Service |
| W2-048 | Brokaw-Lanesville | In Service |
| W4-005 | Blue Mound-Latham | In Service |
| X2-022 | Brokaw-Lanesville | In Service |
| Y1-049 | Wurno 34.5kV | In Service |
| Y1-086 | Morgans Corner | In Service |
| Z2-027 | Pasquotank 34.5kV | In Service |
| Z2-087 | Pontiac MidPoint-Brokaw 345kV | In Service |
| Z2-115 | Deer Creek 12.47kV | In Service |
Affected System - PJM Identified Violations
As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.
Affected System - Non-PJM Identified Violations
In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:
System Reinforcements
Based on the Phase I analysis results, this project may have a cost responsibility for the following System Reinforcements:
| TO | RTEP ID | Title | Allocated Cost ($USD) |
|---|---|---|---|
| AEP | (Pending) / AEP-TC2-18704 | 05SMITHMTN 138.0 kV to 05LEESVI 138.0 kV ckt 1 - Rebuild | $6,172,896 |
| Dominion | n9132.0 / dom-122 | Add 3rd 138/115 kV transformer at Altavista substation | $3,776,023 |
| Dominion | (Pending) / TC1-PH1-DOM-096 | Wreck and rebuild 2.8 mi of 115 kV Line 15 between Huber DP and Sedgehill with (1) 768,2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C | $622,404 |
| Dominion | (Pending) / TC2-PH1-DOM-2001 | Wreck and rebuild 2.66 miles of 115 kV line 1016 between Crystal Hill DP and AH1-343 with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. | $592,053 |
| AEP | (Pending) / AEP-TC2-18717 | 05BANSTR 138.0 kV to 05EDAN 2 138.0 kV ckt 1 - Sag Study and Replace Equipment | $276,475 |
| Dominion | (Pending) / TC2-PH1-DOM-2002 | Replace 556.6 ACSR line lead on line 104 at AltaVista 138 kV | $241,586 |
| Dominion | (Pending) / dom-184 | Wreck and rebuild 0.97 mi of 115 kV Line 15 between Woodchuck Trail and Huber DP with (1) 768,2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C | $215,619 |
| AEP | (Pending) / AEP-TC2-18655 | 05MUSEVILLE 138.0 kV to 05SMITHMTN 138.0 kV ckt 1 - Replace Switch | $63,625 |
| AEP | (Pending) / AEPAPRJV004 | Replace wavetrap @ New London | $26,550 |
| Dominion | n8423 / dom-119 | Wreck and rebuild 0.06 miles of 115 kV line 1016 between Woodchuck Trail and Crystal Hill DP with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. | $13,355 |
| AEP | (Pending) / AEP-TC2-18709 | AG2-152 TP 138.0 kV to 05BANSTR 138.0 kV ckt 1 - Sag Study and Upgrade Equipment | $8,132 |
| Grand Total: | $12,008,718 | ||
Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.
System Reinforcement
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- (Pending) / AEP-TC2-18704
- Title
- 05SMITHMTN 138.0 kV to 05LEESVI 138.0 kV ckt 1 - Rebuild
- Description
- Rebuild ~8.2 miles of 138 kV line between Smith Mountain and Leesville, upgrade 795 AAC station conductor at Smith Mountain and Leesville.
- Total Cost ($USD)
- $32,000,000
- Allocated Cost ($USD)
- $6,172,896
- Time Estimate
- 36 to 48 Months
Contributor
| Facility | Contingency | |
|---|---|---|
| 05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line | (Any) |
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
AG2-111 | 3.8 MW | 5.3% | $1,710,840 |
AG2-112 | 4.0 MW | 5.6% | $1,793,537 |
AG2-152 | 29.8 MW | 41.4% | $13,245,672 |
AG2-311 | 13.9 MW | 19.3% | $6,172,896 |
AG2-541 | 13.6 MW | 18.9% | $6,049,740 |
AH1-343 | 6.8 MW | 9.5% | $3,027,315 |
System Reinforcement: n9132.0
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- n9132.0 / dom-122
- Title
- Add 3rd 138/115 kV transformer at Altavista substation
- Description
- Add 3rd 138/115 kV transformer at Altavista substation
- Total Cost ($USD)
- $11,000,000
- Allocated Cost ($USD)
- $3,776,023
- Time Estimate
- 42 to 44 Months
Contributor
| Facility | Contingency | |
|---|---|---|
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer | (Any) | |
| 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer | (Any) |
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
AG2-111 | 5.7 MW | 13.5% | $1,482,894 |
AG2-112 | 6.0 MW | 14.1% | $1,554,135 |
AG2-311 | 14.6 MW | 34.3% | $3,776,023 |
AH1-343 | 16.2 MW | 38.1% | $4,186,949 |
System Reinforcement
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- (Pending) / TC1-PH1-DOM-096
- Title
- Wreck and rebuild 2.8 mi of 115 kV Line 15 between Huber DP and Sedgehill with (1) 768,2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C
- Description
- Wreck and rebuild 2.8 mi of 115 kV Line 15 between Huber DP and Sedgehill with (1) 768,2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C
- Total Cost ($USD)
- $8,960,000
- Allocated Cost ($USD)
- $622,404
- Time Estimate
- 30 to 36 Months
Contributor
| Facility | Contingency | |
|---|---|---|
| 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line | (Any) |
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
AG2-111 | 5.0 MW | 5.8% | $516,143 |
AG2-112 | 5.3 MW | 6.0% | $541,145 |
AG2-152 | 13.0 MW | 14.9% | $1,335,495 |
AG2-311 | 6.1 MW | 6.9% | $622,404 |
AG2-541 | 27.0 MW | 30.9% | $2,768,644 |
AH1-343 | 31.0 MW | 35.4% | $3,176,168 |
System Reinforcement
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- (Pending) / TC2-PH1-DOM-2001
- Title
- Wreck and rebuild 2.66 miles of 115 kV line 1016 between Crystal Hill DP and AH1-343 with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
- Description
- Wreck and rebuild 2.66 miles of 115 kV line 1016 between Crystal Hill DP and AH1-343 with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
- Total Cost ($USD)
- $8,512,000
- Allocated Cost ($USD)
- $592,053
- Time Estimate
- 30 to 36 Months
Contributor
| Facility | Contingency | |
|---|---|---|
| 3CRSTL HILL-AH1-343 TP 115.0 kV Ckt 1 line | (Any) |
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
AG2-111 | 5.0 MW | 5.8% | $490,200 |
AG2-112 | 5.3 MW | 6.0% | $513,936 |
AG2-152 | 13.1 MW | 14.9% | $1,270,297 |
AG2-311 | 6.1 MW | 7.0% | $592,053 |
AG2-541 | 27.0 MW | 30.9% | $2,629,314 |
AH1-343 | 31.0 MW | 35.4% | $3,016,201 |
System Reinforcement
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- (Pending) / AEP-TC2-18717
- Title
- 05BANSTR 138.0 kV to 05EDAN 2 138.0 kV ckt 1 - Sag Study and Replace Equipment
- Description
- Replace first overhead conductor span from East Danville to Structure 18-135 (1033 ACSR); Conduct sag clearance study on 10.7 miles between Structure 18-135 and Banister; Replace 1590 AAC station conductor at Banister; Replace 2000 AAC station conductor at East Danville
- Total Cost ($USD)
- $1,700,000
- Allocated Cost ($USD)
- $276,475
- Time Estimate
- 36 to 48 Months
Contributor
| Facility | Contingency | |
|---|---|---|
| 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line | (Any) |
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
AG2-152 | 80.4 MW | 68.7% | $1,167,298 |
AG2-311 | 19.0 MW | 16.3% | $276,475 |
AG2-541 | 8.6 MW | 7.3% | $124,289 |
AH1-343 | 9.1 MW | 7.8% | $131,938 |
System Reinforcement
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- (Pending) / TC2-PH1-DOM-2002
- Title
- Replace 556.6 ACSR line lead on line 104 at AltaVista 138 kV
- Description
- Replace 556.6 ACSR line lead on line 104 at AltaVista 138 kV
- Total Cost ($USD)
- $400,000
- Allocated Cost ($USD)
- $241,586
- Time Estimate
- 12 to 18 Months
Contributor
| Facility | Contingency | |
|---|---|---|
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | (Any) |
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
AG2-152 | 6.9 MW | 39.6% | $158,414 |
AG2-311 | 10.5 MW | 60.4% | $241,586 |
System Reinforcement
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- (Pending) / dom-184
- Title
- Wreck and rebuild 0.97 mi of 115 kV Line 15 between Woodchuck Trail and Huber DP with (1) 768,2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C
- Description
- Wreck and rebuild 0.97 mi of 115 kV Line 15 between Woodchuck Trail and Huber DP with (1) 768,2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C
- Total Cost ($USD)
- $3,104,000
- Allocated Cost ($USD)
- $215,619
- Time Estimate
- 30 to 36 Months
Contributor
| Facility | Contingency | |
|---|---|---|
| 3HUBER DP-AC1-222 TAP 115.0 kV Ckt 1 line | (Any) |
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
AG2-111 | 5.0 MW | 5.8% | $178,807 |
AG2-112 | 5.3 MW | 6.0% | $187,468 |
AG2-152 | 13.0 MW | 14.9% | $462,654 |
AG2-311 | 6.1 MW | 6.9% | $215,619 |
AG2-541 | 27.0 MW | 30.9% | $959,137 |
AH1-343 | 31.0 MW | 35.4% | $1,100,315 |
System Reinforcement
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- (Pending) / AEP-TC2-18655
- Title
- 05MUSEVILLE 138.0 kV to 05SMITHMTN 138.0 kV ckt 1 - Replace Switch
- Description
- Replace 138 kV Switch at Smith Mountain "C1S2"
- Total Cost ($USD)
- $500,000
- Allocated Cost ($USD)
- $63,625
- Time Estimate
- 36 to 48 Months
Contributor
| Facility | Contingency | |
|---|---|---|
| 05SMITHMTN-05MUSEVILLE 138.0 kV Ckt 1 line | (Any) |
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
AG2-152 | 112.6 MW | 74.0% | $370,179 |
AG2-272 | 7.8 MW | 5.1% | $25,589 |
AG2-311 | 19.3 MW | 12.7% | $63,625 |
AH1-314 | 12.3 MW | 8.1% | $40,607 |
System Reinforcement
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- (Pending) / AEPAPRJV004
- Title
- Replace wavetrap @ New London
- Description
- Replace wavetrap @ New London
- Total Cost ($USD)
- $260,000
- Allocated Cost ($USD)
- $26,550
- Time Estimate
- 18 to 24 Months
Contributor
| Facility | Contingency | |
|---|---|---|
| 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line | (Any) |
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
AG2-111 | 4.7 MW | 7.1% | $18,378 |
AG2-112 | 4.9 MW | 7.4% | $19,267 |
AG2-152 | 6.6 MW | 10.0% | $25,960 |
AG2-311 | 6.8 MW | 10.2% | $26,550 |
AG2-541 | 20.9 MW | 31.7% | $82,388 |
AH1-343 | 22.2 MW | 33.6% | $87,457 |
System Reinforcement: n8423
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- n8423 / dom-119
- Title
- Wreck and rebuild 0.06 miles of 115 kV line 1016 between Woodchuck Trail and Crystal Hill DP with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
- Description
- Wreck and rebuild 0.06 miles of 115 kV line 1016 between Woodchuck Trail and Crystal Hill DP with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
- Total Cost ($USD)
- $192,000
- Allocated Cost ($USD)
- $13,355
- Time Estimate
- 30 to 36 Months
Contributor
| Facility | Contingency | |
|---|---|---|
| 3CRSTL HILL-AC1-222 TAP 115.0 kV Ckt 1 line | (Any) |
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
AG2-111 | 5.0 MW | 5.8% | $11,057 |
AG2-112 | 5.3 MW | 6.0% | $11,593 |
AG2-152 | 13.1 MW | 14.9% | $28,653 |
AG2-311 | 6.1 MW | 7.0% | $13,355 |
AG2-541 | 27.0 MW | 30.9% | $59,308 |
AH1-343 | 31.0 MW | 35.4% | $68,035 |
System Reinforcement
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- (Pending) / AEP-TC2-18709
- Title
- AG2-152 TP 138.0 kV to 05BANSTR 138.0 kV ckt 1 - Sag Study and Upgrade Equipment
- Description
- Upgrade 1590 AAC station conductor at Banister. Perform sag clearance study for ~0.5 mile of 138 kV line between AG2-152 and Banister to determine any potential mitigation required to operate at a higher temperature.
- Total Cost ($USD)
- $50,000
- Allocated Cost ($USD)
- $8,132
- Time Estimate
- 36 to 48 Months
Contributor
| Facility | Contingency | |
|---|---|---|
| 05BANSTR-AG2-152 TP 138.0 kV Ckt 1 line | (Any) |
| Project | MW Impact | Percent Allocation | Allocated Cost ($USD) |
|---|---|---|---|
AG2-152 | 80.4 MW | 68.7% | $34,332 |
AG2-311 | 19.0 MW | 16.3% | $8,132 |
AG2-541 | 8.6 MW | 7.3% | $3,656 |
AH1-343 | 9.1 MW | 7.8% | $3,881 |
System Reinforcement: b4000.211
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- b4000.211
- Title
- Rebuild 6.5 miles of Johnson Mountain - New London 138 kV line
- Description
- Rebuild 6.5 miles of Johnson Mountain - New London 138 kV line Projected In Service Date: 06/01/2029
- Cost Information
- Time Estimate
- Jun 01 2029
Contingent Note: Although AG2-311 may not presently have cost responsibility for this upgrade, AG2-311 may need this upgrade in-service to be deliverable to the PJM system. If AG2-311 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.
| Facility | Contingency | |
|---|---|---|
| 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.210
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- b4000.210
- Title
- Rebuild 7 miles of Otter - Johnson Mountain 138 kV line.
- Description
- Rebuild 7 miles of Otter - Johnson Mountain 138 kV line.
- Cost Information
- Time Estimate
- Jun 01 2029
Contingent Note: Although AG2-311 may not presently have cost responsibility for this upgrade, AG2-311 may need this upgrade in-service to be deliverable to the PJM system. If AG2-311 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.
| Facility | Contingency | |
|---|---|---|
| 05JOHNMT-05OTTER 138.0 kV Ckt 1 line | (Any) |
System Reinforcement: n6594.1
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- n6594.1 / AEPA0044a
- Title
- Rebuild 8.4 miles section of the Leesville - Alta Vista 138 kV line
- Description
- Rebuild 8.4 miles section of the Leesville - Alta Vista 138 kV line
- Total Cost ($USD)
- $23,571,948
- Allocated Cost ($USD)
- $0
- Time Estimate
- Nov 21 2027
Contingent Note: Based on PJM cost allocation criteria, AG2-311 does not receive cost allocation towards this upgrade which has been securitized by a prior Queue/Cycle. Although AG2-311 may not have cost responsibility for this upgrade, AG2-311 may need this upgrade in-service to be deliverable for the reliability to the PJM system. If AG2-311 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.
| Facility | Contingency | |
|---|---|---|
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.207
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- b4000.207
- Title
- Leesville Station Upgrade 138 kV
- Description
- Leesville Station Upgrade 138 kV: Replace 795 KCM AAC, 37-Str. IPS Sch. 40 1272 KCM AAC, 61-Str. 1272 KCM AAC, 61-Str. PH A,B,C ALTA VISTA CB-A BUS DISC ALTA VISTA CB-A LINE DISC Wavetrap (1200A) Relay Thermal Limit 1356 Amps
- Cost Information
- Time Estimate
- Jun 01 2029
Contingent Note: Although AG2-311 may not presently have cost responsibility for this upgrade, AG2-311 may need this upgrade in-service to be deliverable to the PJM system. If AG2-311 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.
| Facility | Contingency | |
|---|---|---|
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line | (Any) |
System Reinforcement: n5613
- Type
- Load Flow
- TO
- AEP
- RTEP ID / TO ID
- n5613 / AEPA0014a
- Title
- Rebuild 0.9 miles of the Otter - Alta Vista 138 kV line.
- Description
- Rebuild 0.9 miles of the Otter - Alta Vista 138 kV line.
- Total Cost ($USD)
- $2,740,849
- Allocated Cost ($USD)
- $0
- Time Estimate
- Nov 21 2027
Contingent Note: Based on PJM cost allocation criteria, AG2-311 does not receive cost allocation towards this upgrade which has been securitized by a prior Queue/Cycle. Although AG2-311 may not have cost responsibility for this upgrade, AG2-311 may need this upgrade in-service to be deliverable for the reliability to the PJM system. If AG2-311 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.
| Facility | Contingency | |
|---|---|---|
| 05OTTER-4ALTVSTA 138.0 kV Ckt 1 line | (Any) |
System Reinforcement
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- (Pending)
- Title
- Most limiting rating on the Dominion side is the Wave Trap and Lead at Altavista: 363 / 382 /420 MVA.
- Description
- Most limiting rating on the Dominion side is the Wave Trap and Lead at Altavista: 363 / 382 /420 MVA.
- Total Cost ($USD)
- $0
- Allocated Cost ($USD)
- $0
- Time Estimate
- 99 Months
Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.
| Facility | Contingency | |
|---|---|---|
| 05OTTER-4ALTVSTA 138.0 kV Ckt 1 line | (Any) |
System Reinforcement
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- (Pending) / TC2-PH1-DOM-0044
- Title
- Wreck and rebuild 4.5 miles of 230 kV Line 2204 between Black Walnut and Edmonson with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
- Description
- Wreck and rebuild 4.5 miles of 230 kV Line 2204 between Black Walnut and Edmonson with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
- Total Cost ($USD)
- $17,100,000
- Allocated Cost ($USD)
- $0
- Time Estimate
- 36 to 42 Months
Potential Aggregate Contributor Note: Based on PJM cost allocation criteria, AG2-311 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-311 could receive cost allocation. Although AG2-311 may not presently have cost responsibility for this upgrade, AG2-311 is a potential Aggregate Pool Contributor.
| Facility | Contingency | |
|---|---|---|
| 6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line | (Any) |
System Reinforcement
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- (Pending) / TC2-PH1-DOM-0045
- Title
- Wreck and rebuild 8.3 miles of 230 kV Line 2250 between Edmonson and Sedge Hill with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
- Description
- Wreck and rebuild 8.3 miles of 230 kV Line 2250 between Edmonson and Sedge Hill with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
- Total Cost ($USD)
- $31,540,000
- Allocated Cost ($USD)
- $0
- Time Estimate
- 36 to 42 Months
Potential Aggregate Contributor Note: Based on PJM cost allocation criteria, AG2-311 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-311 could receive cost allocation. Although AG2-311 may not presently have cost responsibility for this upgrade, AG2-311 is a potential Aggregate Pool Contributor.
| Facility | Contingency | |
|---|---|---|
| 6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.357
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.357
- Title
- Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
- Description
- Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
- Cost Information
- Time Estimate
- Jun 01 2029
Not Contingent Note: AG2-311 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-311 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.341
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.341
- Title
- Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
- Description
- Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
- Cost Information
- Time Estimate
- Jul 13 2029
Not Contingent Note: AG2-311 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-311 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.342
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.342
- Title
- Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
- Description
- Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
- Cost Information
- Time Estimate
- Jul 13 2029
Not Contingent Note: AG2-311 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-311 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.355
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.355
- Title
- Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
- Description
- Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
- Cost Information
- Time Estimate
- Jun 01 2029
Not Contingent Note: AG2-311 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-311 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.325
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.325
- Title
- Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
- Description
- Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
- Cost Information
- Time Estimate
- Feb 24 2029
Not Contingent Note: AG2-311 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-311 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.326
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.326
- Title
- At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
- Description
- At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
- Cost Information
- Time Estimate
- Feb 24 2029
Not Contingent Note: AG2-311 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-311 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.327
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.327
- Title
- Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
- Description
- Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
- Cost Information
- Time Estimate
- Feb 24 2029
Not Contingent Note: AG2-311 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-311 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.344
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.344
- Title
- Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
- Description
- Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
- Cost Information
- Time Estimate
- Sep 16 2030
Not Contingent Note: AG2-311 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-311 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.345
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.345
- Title
- Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
- Description
- Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
- Cost Information
- Time Estimate
- Sep 16 2030
Not Contingent Note: AG2-311 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-311 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.346
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.346
- Title
- Cut-in 500kV line from Kraken substation into Yeat substation
- Description
- Cut-in 500kV line from Kraken substation into Yeat substation
- Cost Information
- Time Estimate
- Jun 01 2029
Not Contingent Note: AG2-311 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-311 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.348
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.348
- Title
- Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
- Description
- Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
- Cost Information
- Time Estimate
- Jun 01 2029
Not Contingent Note: AG2-311 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-311 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.349
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.349
- Title
- Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
- Description
- Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
- Cost Information
- Time Estimate
- Sep 16 2030
Not Contingent Note: AG2-311 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-311 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.351
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.351
- Title
- Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
- Description
- Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
- Cost Information
- Time Estimate
- Sep 16 2030
Not Contingent Note: AG2-311 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-311 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.352
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.352
- Title
- Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
- Description
- Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
- Cost Information
- Time Estimate
- Sep 16 2030
Not Contingent Note: AG2-311 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-311 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.350
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.350
- Title
- Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
- Description
- Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
- Cost Information
- Time Estimate
- Sep 16 2030
Not Contingent Note: AG2-311 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-311 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) |
System Reinforcement: b4000.356
- Type
- Load Flow
- TO
- Dominion
- RTEP ID / TO ID
- b4000.356
- Title
- Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
- Description
- Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
- Cost Information
- Time Estimate
- Jun 01 2029
Not Contingent Note: AG2-311 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-311 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.
| Facility | Contingency | |
|---|---|---|
| 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line | (Any) |