AG2-311 Phase I Study Report

v1.00 released 2025-10-29 20:45

Smith Mountain 138 kV

52.5 MW Capacity / 75.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Smith Mountain Storage, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is American Electric Power.

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed a Storage facility located in the American Electric Power zone — Bedford County, Virginia. The installed facilities will have a total capability of 75.0 MW with 52.5 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-311
Project Name:
Smith Mountain 138 kV
Project Developer Name:
Smith Mountain Storage, LLC
State:
Virginia
County:
Bedford
Transmission Owner:
American Electric Power
MFO:
75.0
MWE:
75.0
MWC:
52.5
Battery Storage Specification:
381.14 MWh, 4.0-hr class
Grid Charging:
Yes
Fuel Type:
Storage
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AG2-311 will interconnect on the American Electric Power  transmission system  at the Smith Mountain 138 kV Substation.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AG2-311 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-311Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$26,432,226$26,432,226
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$12,008,717$12,008,717
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$38,440,943$38,440,943

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AG2-311

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AG2-311 Project due at DP1
ABA - B
AG2-311$3,844,094$300,000$3,544,094

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)AEP will construct a new circuit breaker and line exit for the new generator as well as the associated facilities required to support the interconnection.$26,432,226 $26,432,226

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 24 to 30 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Transmission Owner Analysis

No Transmission Owner impacts identified.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-311 was evaluated as a 75.0 MW (52.5 MW Capacity) injection in the AEP area.

AG2-311 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 75.0 MW (75.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
AEP_P7-1_#10817___SRT-A
TowerAC120.87 %388.0B468.9719.05
GD2AEP
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
AEP_P4_#10213_05CLOVRD 138_A_SRT-A
BreakerAC113.77 %388.0B441.4316.7
GD2AEP
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
AEP_P4_#10210_05CLOVRD 138_A2_SRT-A
BreakerAC113.52 %388.0B440.4416.68
GD2AEP
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
AEP_P7-1_#10808___SRT-A
TowerAC110.55 %388.0B428.9419.06
GD2AEP
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
AEP_P2-2_#6213_05WLAKE 138_1_SRT-A
BusAC104.39 %388.0B405.0314.46
GD2AEP
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
AEP_P2-2_#6212_05WLAKE 138_2_SRT-A
BusAC102.03 %388.0B395.8914.46
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC121.06 %3393.4B4107.9711.94
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC117.02 %3610.0B4224.5511.95
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC116.77 %3610.0B4215.4311.94
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC116.68 %3610.0B4211.9811.94
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC116.36 %3610.0B4200.4311.94
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
DVP_P4-2: 151T1047_SRT-A
BreakerAC134.96 %245.0B330.656.75
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
DVP_P4-2: 104702_SRT-A
BreakerAC134.95 %245.0B330.636.75
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
DVP_P4-2: 1016T1047_SRT-A
BreakerAC128.07 %245.0B313.776.76
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
DVP_P4-2: 101672_SRT-A
BreakerAC128.05 %245.0B313.736.76
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
DVP_P4-2: 104772_SRT-A
BreakerAC126.62 %245.0B310.216.76
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
DVP_P1-2: LN 1047_SRT-A
SingleAC106.29 %245.0B260.46.75
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
DVP_P1-2: LN 1016_SRT-A-1
SingleAC101.51 %245.0B248.716.76
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
BusAC100.25 %245.0B245.616.43
GD2AEP
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
AEP_P7-1_#10778___SRT-A
TowerAC100.25 %245.0B245.66.43
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Base Case
SingleAC118.66 %192.7A228.6610.45
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
BreakerAC117.03 %284.0B332.3613.87
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
BreakerAC116.49 %284.0B330.8213.82
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
BusAC115.7 %284.0B328.5813.82
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P7-1_#10778___SRT-A
TowerAC115.69 %284.0B328.5613.82
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P4_#10687_05EDAN 2 138_N_SRT-A
BreakerAC115.68 %284.0B328.5413.82
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P4_#8676_05EDANV2 230_S_SRT-A
BreakerAC115.67 %284.0B328.513.82
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P1-2_#5366_SRT-A-1
SingleAC110.86 %266.96B295.9513.81
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P1-3_#10688_05EDANV2 230_4_SRT-A
SingleAC110.35 %266.96B294.613.82
IPDAEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Base Case
SingleAC106.65 %192.7A205.5114.93
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P4_#10213_05CLOVRD 138_A_SRT-A
BreakerAC106.32 %284.0B301.9614.26
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P7-1_#10781___SRT-A-1
TowerAC100.01 %284.0B284.0111.5
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
DVP_P4-2: 151T1047_SRT-A
BreakerAC136.34 %245.0B334.026.75
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
DVP_P4-2: 104702_SRT-A
BreakerAC136.33 %245.0B334.06.75
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
DVP_P4-2: 1016T1047_SRT-A
BreakerAC129.43 %245.0B317.116.76
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
DVP_P4-2: 101672_SRT-A
BreakerAC129.42 %245.0B317.076.76
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
DVP_P4-2: 104772_SRT-A
BreakerAC127.97 %245.0B313.536.76
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
DVP_P1-2: LN 1047_SRT-A
SingleAC107.67 %245.0B263.786.75
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
DVP_P1-2: LN 1016_SRT-A-1
SingleAC102.87 %245.0B252.046.76
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
BusAC101.55 %245.0B248.86.43
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
AEP_P7-1_#10778___SRT-A
TowerAC101.55 %245.0B248.796.43
GD2AEP
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
DVP_P2-2: ALTAVISTA 115KV_SRT-A
BusAC100.37 %245.0B245.97.7
GD2AEP
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
BreakerAC113.61 %255.0B289.7113.88
GD2AEP
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
BreakerAC113.02 %255.0B288.213.83
GD2AEP
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
BusAC112.15 %255.0B285.9713.83
GD2AEP
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
AEP_P7-1_#10778___SRT-A
TowerAC112.13 %255.0B285.9413.83
GD2AEP
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
AEP_P4_#10687_05EDAN 2 138_N_SRT-A
BreakerAC112.13 %255.0B285.9213.83
GD2AEP
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
AEP_P4_#8676_05EDANV2 230_S_SRT-A
BreakerAC112.11 %255.0B285.8913.83
GD2AEP
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
AEP_P4_#10213_05CLOVRD 138_A_SRT-A
BreakerAC101.78 %255.0B259.5514.28
GD2DVP
3CRSTL HILL-AC1-222 TAP 115.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC106.3 %285.76B303.764.8
GD2DVP
3CRSTL HILL-AC1-222 TAP 115.0 kV Ckt 1 line
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
BreakerAC100.59 %350.0C352.076.09
GD2DVP
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC116.18 %285.76B331.994.79
GD2DVP
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
BreakerAC111.45 %350.0C390.086.07
GD2DVP
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
BreakerAC109.96 %350.0C384.855.99
GD2DVP
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
BusAC109.7 %350.0C383.945.99
GD2DVP
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
AEP_P7-1_#10778___SRT-A
TowerAC109.69 %350.0C383.925.99
GD2DVP
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
DVP_P1-2: LN 553_SRT-S
SingleAC107.38 %285.76B306.864.38
GD2DVP
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
BusAC105.51 %350.0C369.275.58
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
DVP_P4-2: 151T1047_SRT-A
BreakerAC137.18 %245.0B336.086.75
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
DVP_P4-2: 104702_SRT-A
BreakerAC137.17 %245.0B336.066.75
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
DVP_P4-2: 1016T1047_SRT-A
BreakerAC130.26 %245.0B319.146.76
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
DVP_P4-2: 101672_SRT-A
BreakerAC130.24 %245.0B319.16.76
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
DVP_P4-2: 104772_SRT-A
BreakerAC128.8 %245.0B315.556.76
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
DVP_P1-2: LN 1047_SRT-A
SingleAC115.43 %230.3B265.846.75
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
DVP_P1-2: LN 1016_SRT-A-1
SingleAC110.32 %230.3B254.076.76
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Base Case
SingleAC104.83 %156.98A164.565.0
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
BusAC102.33 %245.0B250.716.43
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
AEP_P7-1_#10778___SRT-A
TowerAC102.33 %245.0B250.76.43
GD2AEP/DVP
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
DVP_P2-2: ALTAVISTA 115KV_SRT-A
BusAC101.22 %245.0B247.987.7
GD2DVP
4ALTVSTA-3ALTVSTA 138.0/115.0 kV Ckt 1 transformer
DVP_P1-3: 4ALTVSTA-TX#4_SRT-A
SingleAC107.36 %123.7B132.84.91
GD2DVP
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-3
SingleAC108.64 %814.98B885.414.59
GD2DVP
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-2
SingleAC106.47 %814.98B867.674.59
GD2DVP
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-3
SingleAC103.53 %814.98B843.754.61
GD2DVP
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-2
SingleAC101.35 %814.98B825.974.61
GD2DVP
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC118.6 %285.76B338.914.79
GD2DVP
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
BreakerAC113.44 %350.0C397.056.07
GD2DVP
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
BreakerAC111.95 %350.0C391.835.99
GD2DVP
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
BusAC111.69 %350.0C390.935.99
GD2DVP
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
AEP_P7-1_#10778___SRT-A
TowerAC111.69 %350.0C390.915.99
GD2DVP
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
DVP_P1-2: LN 553_SRT-S
SingleAC109.82 %285.76B313.834.38
GD2DVP
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
BusAC107.51 %350.0C376.285.58
GD2DVP
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
AEP_P2-2_#17572_05MUSEVILLE 138_1_SRT-A
BusAC100.61 %350.0C352.155.97
GD2AEP
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
AEP_P7-1_#10817___SRT-A
TowerAC121.83 %392.0B477.5719.05
GD2AEP
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
AEP_P4_#10213_05CLOVRD 138_A_SRT-A
BreakerAC114.79 %392.0B450.016.7
GD2AEP
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
AEP_P4_#10210_05CLOVRD 138_A2_SRT-A
BreakerAC114.54 %392.0B449.0116.68
GD2AEP
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
AEP_P7-1_#10808___SRT-A
TowerAC111.62 %392.0B437.5419.06
GD2AEP
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
AEP_P2-2_#6213_05WLAKE 138_1_SRT-A
BusAC105.51 %392.0B413.614.46
GD2AEP
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
AEP_P2-2_#6212_05WLAKE 138_2_SRT-A
BusAC103.18 %392.0B404.4514.46
GD2DVP
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC109.29 %285.76B312.324.8
GD2DVP
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
BreakerAC103.04 %350.0C360.646.09
GD2DVP
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
BreakerAC101.53 %350.0C355.376.0
GD2DVP
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
BusAC101.27 %350.0C354.466.0
GD2DVP
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
AEP_P7-1_#10778___SRT-A
TowerAC101.27 %350.0C354.446.0
GD2DVP
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
DVP_P1-2: LN 553_SRT-S
SingleAC100.5 %285.76B287.194.39

Details for 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line l/o AEP_P7-1_#10817___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10817___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:120.87 %
Rating:388.0 MVA
Rating Type:B
MVA to Mitigate:468.97
MW Contribution:19.05
Bus #Bus NameTypeMW Contribution
24684605SMG4
50/50
3.572
24728405LEESVG
50/50
0.495
270197AD1-017 GEN1
Solar/Wind Harmer
7.076
24684705SMG5
50/50
1.367
970481AG2-311 GEN
50/50
19.048
24728405LEESVG
50/50
0.493
970223AG2-152 GEN
Solar/Wind Harmer
80.422
270016AE1-250 BESS
Solar/Wind Harmer
12.954
270574AD1-017 GEN2
Solar/Wind Harmer
23.549
270173AC1-122 GEN
Solar/Wind Harmer
4.971
270455AD2-022 GEN
Solar/Wind Helper
0.924
270457AD2-023 GEN
Solar/Wind Helper
0.609
24684405SMG2
50/50
3.549
24684505SMG3
50/50
2.195
24684305SMG1
50/50
1.287
270013AE1-250 PV
Solar/Wind Harmer
12.954
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.611
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.571
NYPJM->LTFIMP_NY
CLTF
0.099
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.315
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.014
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.058
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line l/o AEP_P4_#10213_05CLOVRD 138_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10213_05CLOVRD 138_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.77 %
Rating:388.0 MVA
Rating Type:B
MVA to Mitigate:441.43
MW Contribution:16.7
Bus #Bus NameTypeMW Contribution
24684705SMG5
50/50
1.198
970481AG2-311 GEN
50/50
16.703
24728405LEESVG
50/50
0.334
3151561HALLBR1
50/50
0.448
970223AG2-152 GEN
Solar/Wind Harmer
78.334
270016AE1-250 BESS
Solar/Wind Harmer
12.518
270574AD1-017 GEN2
Solar/Wind Harmer
22.147
270173AC1-122 GEN
Solar/Wind Harmer
3.243
3147312GRETNA
Solar/Wind Harmer
-0.017
3146802CHATHAM
Solar/Wind Harmer
-0.016
941801AE2-185 GEN
Solar/Wind Harmer
8.005
3147123OTTER R
Solar/Wind Harmer
-0.011
962751AG1-124 GEN
Solar/Wind Harmer
5.228
316123AC1-075 GEN
Solar/Wind Harmer
1.01
970165AG2-112 GEN
Solar/Wind Harmer
0.889
970163AG2-111 GEN
Solar/Wind Harmer
0.849
270455AD2-022 GEN
Solar/Wind Helper
0.935
270457AD2-023 GEN
Solar/Wind Helper
0.616
24684405SMG2
50/50
3.112
24684505SMG3
50/50
1.925
24684305SMG1
50/50
1.128
270013AE1-250 PV
Solar/Wind Harmer
12.518
316217AC1-145 GEN
Solar/Wind Harmer
3.465
316197AC1-042 GEN
Solar/Wind Harmer
2.627
942671AE2-283 GEN
Solar/Wind Harmer
7.071
942751AE2-291 GEN
Solar/Wind Harmer
7.417
24684605SMG4
50/50
3.133
24728405LEESVG
50/50
0.336
270197AD1-017 GEN1
Solar/Wind Harmer
6.655
3147312GRETNA
Solar/Wind Harmer
-0.004
941821AE2-187 GEN
Solar/Wind Harmer
8.005
958131AF2-107 GEN
Solar/Wind Harmer
2.397
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.589
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.768
NYPJM->LTFIMP_NY
CLTF
0.079
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.234
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.068
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.225
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line l/o AEP_P4_#10210_05CLOVRD 138_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10210_05CLOVRD 138_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.52 %
Rating:388.0 MVA
Rating Type:B
MVA to Mitigate:440.44
MW Contribution:16.68
Bus #Bus NameTypeMW Contribution
24684705SMG5
50/50
1.197
970481AG2-311 GEN
50/50
16.68
24728405LEESVG
50/50
0.334
3151561HALLBR1
50/50
0.448
970223AG2-152 GEN
Solar/Wind Harmer
78.303
270016AE1-250 BESS
Solar/Wind Harmer
12.513
270574AD1-017 GEN2
Solar/Wind Harmer
22.132
270173AC1-122 GEN
Solar/Wind Harmer
3.239
3147312GRETNA
Solar/Wind Harmer
-0.017
3146802CHATHAM
Solar/Wind Harmer
-0.016
941801AE2-185 GEN
Solar/Wind Harmer
7.991
3147123OTTER R
Solar/Wind Harmer
-0.011
962751AG1-124 GEN
Solar/Wind Harmer
5.215
316123AC1-075 GEN
Solar/Wind Harmer
1.008
970165AG2-112 GEN
Solar/Wind Harmer
0.887
970163AG2-111 GEN
Solar/Wind Harmer
0.846
270455AD2-022 GEN
Solar/Wind Helper
0.937
270457AD2-023 GEN
Solar/Wind Helper
0.617
24684405SMG2
50/50
3.108
24684505SMG3
50/50
1.922
24684305SMG1
50/50
1.127
270013AE1-250 PV
Solar/Wind Harmer
12.513
316217AC1-145 GEN
Solar/Wind Harmer
3.459
316197AC1-042 GEN
Solar/Wind Harmer
2.622
942671AE2-283 GEN
Solar/Wind Harmer
7.059
942751AE2-291 GEN
Solar/Wind Harmer
7.401
24684605SMG4
50/50
3.128
24728405LEESVG
50/50
0.335
270197AD1-017 GEN1
Solar/Wind Harmer
6.65
3147312GRETNA
Solar/Wind Harmer
-0.004
941821AE2-187 GEN
Solar/Wind Harmer
7.991
958131AF2-107 GEN
Solar/Wind Harmer
2.391
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.59
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.771
NYPJM->LTFIMP_NY
CLTF
0.078
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.237
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.068
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.226
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line l/o AEP_P7-1_#10808___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10808___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.55 %
Rating:388.0 MVA
Rating Type:B
MVA to Mitigate:428.94
MW Contribution:19.06
Bus #Bus NameTypeMW Contribution
24684605SMG4
50/50
3.574
270197AD1-017 GEN1
Solar/Wind Harmer
7.079
24684705SMG5
50/50
1.367
970481AG2-311 GEN
50/50
19.058
970223AG2-152 GEN
Solar/Wind Harmer
80.445
270016AE1-250 BESS
Solar/Wind Harmer
12.958
270574AD1-017 GEN2
Solar/Wind Harmer
23.558
270455AD2-022 GEN
Solar/Wind Helper
0.921
270457AD2-023 GEN
Solar/Wind Helper
0.607
24684405SMG2
50/50
3.551
24684505SMG3
50/50
2.196
24684305SMG1
50/50
1.287
270013AE1-250 PV
Solar/Wind Harmer
12.958
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.604
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.518
NYPJM->LTFIMP_NY
CLTF
0.088
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.303
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.003
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.023
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line l/o AEP_P2-2_#6213_05WLAKE 138_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#6213_05WLAKE 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.39 %
Rating:388.0 MVA
Rating Type:B
MVA to Mitigate:405.03
MW Contribution:14.46
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
2.694
24684505SMG3
50/50
1.666
24684305SMG1
50/50
0.977
270013AE1-250 PV
Solar/Wind Harmer
12.034
316217AC1-145 GEN
Solar/Wind Harmer
3.013
316197AC1-042 GEN
Solar/Wind Harmer
2.284
942671AE2-283 GEN
Solar/Wind Harmer
6.149
942751AE2-291 GEN
Solar/Wind Harmer
6.246
24684705SMG5
50/50
1.038
970481AG2-311 GEN
50/50
14.46
24728405LEESVG
50/50
0.29
3151561HALLBR1
50/50
0.389
970223AG2-152 GEN
Solar/Wind Harmer
75.879
270016AE1-250 BESS
Solar/Wind Harmer
12.034
270574AD1-017 GEN2
Solar/Wind Harmer
20.72
270173AC1-122 GEN
Solar/Wind Harmer
2.826
3147312GRETNA
Solar/Wind Harmer
-0.015
3146802CHATHAM
Solar/Wind Harmer
-0.014
941801AE2-185 GEN
Solar/Wind Harmer
6.961
3147123OTTER R
Solar/Wind Harmer
-0.01
962751AG1-124 GEN
Solar/Wind Harmer
4.826
24684605SMG4
50/50
2.712
24728405LEESVG
50/50
0.291
270197AD1-017 GEN1
Solar/Wind Harmer
6.226
3147312GRETNA
Solar/Wind Harmer
-0.004
941821AE2-187 GEN
Solar/Wind Harmer
6.961
958131AF2-107 GEN
Solar/Wind Harmer
2.203
270018AE2-047 C O1
Solar/Wind Helper
0.451
943811AF1-049 GEN
Solar/Wind Helper
0.749
316123AC1-075 GEN
Solar/Wind Harmer
0.835
970165AG2-112 GEN
Solar/Wind Harmer
0.735
970163AG2-111 GEN
Solar/Wind Harmer
0.701
270455AD2-022 GEN
Solar/Wind Helper
1.036
270457AD2-023 GEN
Solar/Wind Helper
0.682
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.663
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.766
NYPJM->LTFIMP_NY
CLTF
0.061
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.391
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.052
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.178
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05BANSTR-05EDAN 2 138.0 kV Ckt 1 line l/o AEP_P2-2_#6212_05WLAKE 138_2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#6212_05WLAKE 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.03 %
Rating:388.0 MVA
Rating Type:B
MVA to Mitigate:395.89
MW Contribution:14.46
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
2.694
24684505SMG3
50/50
1.666
24684305SMG1
50/50
0.977
270013AE1-250 PV
Solar/Wind Harmer
12.034
316217AC1-145 GEN
Solar/Wind Harmer
3.013
316197AC1-042 GEN
Solar/Wind Harmer
2.284
942671AE2-283 GEN
Solar/Wind Harmer
6.149
942751AE2-291 GEN
Solar/Wind Harmer
6.246
24684705SMG5
50/50
1.038
970481AG2-311 GEN
50/50
14.46
24728405LEESVG
50/50
0.29
3151561HALLBR1
50/50
0.389
970223AG2-152 GEN
Solar/Wind Harmer
75.879
270016AE1-250 BESS
Solar/Wind Harmer
12.034
270574AD1-017 GEN2
Solar/Wind Harmer
20.72
270173AC1-122 GEN
Solar/Wind Harmer
2.826
3147312GRETNA
Solar/Wind Harmer
-0.015
3146802CHATHAM
Solar/Wind Harmer
-0.014
941801AE2-185 GEN
Solar/Wind Harmer
6.961
3147123OTTER R
Solar/Wind Harmer
-0.01
962751AG1-124 GEN
Solar/Wind Harmer
4.826
24684605SMG4
50/50
2.712
24728405LEESVG
50/50
0.291
270197AD1-017 GEN1
Solar/Wind Harmer
6.226
3147312GRETNA
Solar/Wind Harmer
-0.004
941821AE2-187 GEN
Solar/Wind Harmer
6.961
958131AF2-107 GEN
Solar/Wind Harmer
2.203
270018AE2-047 C O1
Solar/Wind Helper
0.451
943811AF1-049 GEN
Solar/Wind Helper
0.749
316123AC1-075 GEN
Solar/Wind Harmer
0.835
970165AG2-112 GEN
Solar/Wind Harmer
0.735
970163AG2-111 GEN
Solar/Wind Harmer
0.701
270455AD2-022 GEN
Solar/Wind Helper
1.036
270457AD2-023 GEN
Solar/Wind Helper
0.682
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.663
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.766
NYPJM->LTFIMP_NY
CLTF
0.061
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.391
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.052
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.178
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.06 %
Rating:3393.4 MVA
Rating Type:B
MVA to Mitigate:4107.97
MW Contribution:11.94
Bus #Bus NameTypeMW Contribution
970823AG2-518 GEN
50/50
8.384
247619Y1-049
50/50
0.913
24684705SMG5
50/50
0.856
970481AG2-311 GEN
50/50
11.937
24728405LEESVG
50/50
0.295
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.829
962751AG1-124 GEN
Solar/Wind Harmer
12.893
958121AF2-106 GEN
Solar/Wind Harmer
0.001
270173AC1-122 GEN
Solar/Wind Harmer
0.677
971331AH1-145 GEN
Solar/Wind Harmer
18.361
943031AE2-326 GEN
Solar/Wind Harmer
6.784
3147312GRETNA
Solar/Wind Harmer
0.186
3146802CHATHAM
Solar/Wind Harmer
0.175
941801AE2-185 GEN
Solar/Wind Harmer
7.452
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147123OTTER R
Solar/Wind Harmer
0.13
270346AE1-212 GEN
Solar/Wind Harmer
9.542
270030AE2-140 GEN
Solar/Wind Harmer
21.578
960911AF2-382 GEN
Solar/Wind Harmer
7.638
270016AE1-250 BESS
Solar/Wind Harmer
0.006
970913AG2-568 GEN
Solar/Wind Harmer
7.677
971461AH1-227 GEN
Solar/Wind Harmer
4.886
970223AG2-152 GEN
Solar/Wind Harmer
12.358
270053AF1-130 C
Solar/Wind Harmer
2.047
972103AH1-617 GEN
Solar/Wind Harmer
18.024
24686205CER G4
Adder
9.835
24686405CER G5
Adder
9.796
972273AH1-721 GEN
Adder
89.316
24721905FLATG4
Adder
21.686
970273AG2-179 GEN
Solar/Wind Harmer
4.425
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
8.427
962251AG1-071 GEN
Solar/Wind Harmer
4.496
966571AG1-526 GEN
Solar/Wind Harmer
15.967
970093AG2-073 GEN
Solar/Wind Harmer
7.166
960741AF2-365 GEN
Solar/Wind Harmer
3.563
3429391JKCT 9G
Adder
8.402
971191AH1-055 GEN
Solar/Wind Harmer
18.055
972167AH1-666 GEN
Solar/Wind Harmer
5.419
958171AF2-111 GEN
Solar/Wind Harmer
16.681
970243AG2-164 GEN
Solar/Wind Harmer
3.891
970519AG2-331 GEN
Solar/Wind Harmer
17.292
970699AG2-449 GEN
Solar/Wind Harmer
1.663
25196008MFTGT1
Adder
1.252
252510AF1-249 C
Solar/Wind Harmer
0.05
25194608D.CRK4
Adder
1.508
25196608WSDLE5
Adder
7.849
970193AG2-126 GEN
Solar/Wind Harmer
9.55
942481AE2-261 GEN
Solar/Wind Harmer
18.997
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.231
24728705AND G3
Adder
7.277
24728505AND G1
Adder
3.48
276621W2-048 GEN
Solar/Wind Harmer
0.318
276838X2-022 GEN2
Solar/Wind Harmer
0.355
276686W4-005 GEN3
Solar/Wind Harmer
0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.229
971993AH1-541 GEN
Solar/Wind Harmer
2.905
270356AE2-297 GEN
Solar/Wind Harmer
0.008
253406AD2-031_GEN
Solar/Wind Harmer
0.467
270222AC2-111 GEN
Solar/Wind Harmer
3.158
965931AG1-462 GEN
Solar/Wind Harmer
15.879
270291AC1-194 GEN
Solar/Wind Harmer
4.924
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
18.654
959611AF2-252 GEN
Solar/Wind Harmer
2.073
942111AE2-223 GEN
Solar/Wind Harmer
2.013
274878BISHOP HL;2U
Solar/Wind Harmer
0.208
276157O29GEN1
Solar/Wind Harmer
0.999
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
8.222
274767LEE CO EC;8U
Adder
8.125
270437AC2-090 C
Solar/Wind Harmer
0.003
970571AG2-364 GEN
Solar/Wind Harmer
12.296
253415AE1-040 GEN
Solar/Wind Harmer
0.002
972236AH1-702 GEN2
Adder
1.93
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.144
959091AF2-200 GEN
Solar/Wind Harmer
12.273
276889AE2-281 GEN
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.225
274850MENDOTA H;RU
Solar/Wind Harmer
0.072
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.11
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.654
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.673
970291AG2-192 GEN
Solar/Wind Harmer
0.612
274872LEEDK;1U
Solar/Wind Harmer
0.224
958821AF2-173 GEN
Solar/Wind Harmer
8.556
270004AE1-209 GEN
Solar/Wind Harmer
1.324
276805AD2-038 GEN
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
15.703
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
946031AF1-268 GEN
Solar/Wind Harmer
5.79
943121AE2-341 GEN
Solar/Wind Harmer
10.192
943591AF1-030 GEN
Solar/Wind Harmer
6.778
274729ELWOOD EC;1P
Adder
13.481
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.838
3147666LOUISA
Solar/Wind Helper
1.088
316254AC1-120 GEN1
Solar/Wind Helper
1.159
970479AG2-310 GEN
50/50
20.255
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
966251AG1-494 GEN
50/50
4.388
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
4.886
971329AH1-144 GEN
Solar/Wind Harmer
11.568
3147312GRETNA
Solar/Wind Harmer
0.047
941821AE2-187 GEN
Solar/Wind Harmer
7.452
270197AD1-017 GEN1
Solar/Wind Harmer
1.429
270336AE1-100 GEN
Solar/Wind Harmer
0.006
943811AF1-049 GEN
Solar/Wind Harmer
-0.002
24728305BUCHG2
Adder
6.75
270018AE2-047 C O1
Solar/Wind Harmer
0.004
958131AF2-107 GEN
Solar/Wind Harmer
5.339
24735205WLF2G2
Adder
8.023
971687AH1-348 GEN
Solar/Wind Harmer
0.948
971403AH1-188 GEN
Solar/Wind Harmer
13.153
24723205RIVRG3
Adder
22.954
971315AH1-136 GEN
Solar/Wind Harmer
1.695
24686105CER G3
Adder
9.887
24686505CER G6
Adder
9.874
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
24721705FLATG2
Adder
21.686
970947AG2-589 GEN
Solar/Wind Harmer
0.249
970273AG2-179 GEN
Solar/Wind Harmer
2.581
971821AH1-427 GEN
Solar/Wind Harmer
7.218
964901AG1-354 GEN
Solar/Wind Harmer
10.814
962241AG1-070 GEN
Solar/Wind Harmer
3.92
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
12.029
3429421JKCT 10G
Adder
8.402
971565AH1-281 GEN
Solar/Wind Harmer
1.396
339216AC1-074 GEN
Solar/Wind Harmer
0.187
945681AF1-233 GEN
Solar/Wind Harmer
12.782
927014AC1-188 GEN
Solar/Wind Harmer
0.004
970091AG2-072 GEN
Adder
74.012
970333AG2-219 GEN
Solar/Wind Harmer
4.755
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
25196808ZIMRHP
Adder
70.616
252507AC2-088 GEN
Solar/Wind Harmer
0.295
25196008MFTGT1
Adder
1.293
25194608D.CRK4
Adder
1.508
965911AG1-460 GEN
Solar/Wind Harmer
1.271
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.331
24728605AND G2
Adder
3.48
276615X2-022 GEN
Solar/Wind Harmer
0.066
963831AG1-236 GEN
Solar/Wind Harmer
2.455
274880W4-005 GEN4
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.107
963741AG1-226 GEN
Solar/Wind Harmer
14.811
972175AH1-670 GEN
Solar/Wind Harmer
5.171
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
8.673
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
274877BISHOP HL;1U
Solar/Wind Harmer
0.208
276158O29GEN2
Solar/Wind Harmer
0.001
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
8.222
274766LEE CO EC;7U
Adder
8.125
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.519
276903AD2-071 C
Solar/Wind Harmer
6.874
971475AH1-234 GEN
Solar/Wind Harmer
2.986
970819AG2-516 GEN
Solar/Wind Harmer
7.379
970569AG2-363 GEN
Solar/Wind Harmer
18.444
972235AH1-702 GEN1
Adder
2.22
24791305MDL-5G
Solar/Wind Harmer
0.001
274822ROCKFORD ;11
Adder
17.275
957471AF2-041 GEN
Solar/Wind Harmer
18.409
959081AF2-199 GEN
Solar/Wind Harmer
6.136
971067AG2-660 GEN
Solar/Wind Harmer
2.045
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
276861AD2-134 GEN
Solar/Wind Harmer
0.11
970291AG2-192 GEN
Solar/Wind Harmer
0.796
971997AH1-543 GEN
Solar/Wind Harmer
3.211
270032AE2-172
Solar/Wind Harmer
4.079
270263AC1-001 GEN
Solar/Wind Harmer
0.614
274872LEEDK;1U
Solar/Wind Harmer
0.004
270005AE1-210 C O1
Solar/Wind Harmer
1.324
965031AG1-367 GEN
Solar/Wind Harmer
6.111
962781AG1-127 GEN
Solar/Wind Harmer
5.815
276901AD2-066 C O1
Solar/Wind Harmer
0.006
939401AE1-172 GEN
Solar/Wind Harmer
4.568
970825AG2-519 GEN
Solar/Wind Harmer
2.167
274828WAUKEGAN ;BP
Adder
9.655
274682WAUKEGAN ;7U
Adder
15.703
276691AA1-018 GEN1
Solar/Wind Harmer
0.737
274745AC1-111 GEN9
Adder
4.87
315616AA1-038_C
Solar/Wind Helper
3.293
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.725
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.625
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.386
23583801GRNGAP
Solar/Wind Helper
4.287
316095T157 G97
Solar/Wind Helper
1.125
238147AE2-230_GEN1
Solar/Wind Helper
0.421
238149AF1-291A_GEN
Solar/Wind Helper
0.12
316313AB2-026
Solar/Wind Helper
0.354
316258AE1-075 C
Solar/Wind Helper
0.319
316405AF2-144 C
Solar/Wind Helper
0.265
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.387
316044AC1-158 PL1
Solar/Wind Helper
1.257
316450AC1-158 RIC
Solar/Wind Helper
0.335
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684405SMG2
50/50
2.224
24684505SMG3
50/50
1.376
24684305SMG1
50/50
0.806
270583AD2-179 GEN
Solar/Wind Harmer
14.457
971277AH1-098 GEN
Solar/Wind Harmer
5.177
316217AC1-145 GEN
Solar/Wind Harmer
0.003
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
5.796
24728205BUCHG1
Adder
6.75
270013AE1-250 PV
Solar/Wind Harmer
0.006
971225AH1-072 GEN
Solar/Wind Harmer
1.905
971227AH1-073 GEN
Solar/Wind Harmer
1.905
944971AF1-162 GEN
Solar/Wind Harmer
9.068
24723005RIVRG1
Adder
22.954
24723105RIVRG2
Adder
22.954
24685805CER G1
Adder
9.822
24685905CER G2
Adder
9.822
942751AE2-291 GEN
Solar/Wind Harmer
7.887
966021AG1-471 GEN
Solar/Wind Harmer
4.013
971485AH1-239 GEN
Solar/Wind Harmer
5.928
960161AF2-307 GEN
Solar/Wind Harmer
4.775
339255AE2-071 GEN
Solar/Wind Harmer
-0.119
964781AG1-341 GEN
Solar/Wind Harmer
7.653
971081AG2-670 GEN
Solar/Wind Harmer
5.396
942891AE2-308 GEN
Solar/Wind Harmer
7.099
970653AG2-424 GEN
Solar/Wind Harmer
3.405
970653AG2-424 GEN
Solar/Wind Harmer
1.764
964571AG1-320 GEN
Solar/Wind Harmer
6.361
971125AH1-004 GEN
Solar/Wind Harmer
2.777
970107AG2-081 GEN
Solar/Wind Harmer
2.083
972043AH1-570 GEN
Solar/Wind Harmer
1.796
972045AH1-571 GEN
Solar/Wind Harmer
1.439
339221AD2-048_GEN
Solar/Wind Harmer
0.004
970235AG2-159 GEN
Solar/Wind Harmer
4.126
970235AG2-159 GEN
Solar/Wind Harmer
2.367
270186AC1-089 GEN
Solar/Wind Harmer
0.004
970239AG2-162 GEN
Solar/Wind Harmer
1.663
962581AG1-107 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.8
252509AD1-136 GEN
Solar/Wind Harmer
0.033
25183208HLCRTG
Solar/Wind Harmer
0.01
252519AF1-045_GEN
Solar/Wind Harmer
5.589
252516AE2-318_GEN
Solar/Wind Harmer
4.958
25194408D.CRK1
Adder
6.938
25194508D.CRK3
Adder
1.297
971073AG2-665 GEN
Solar/Wind Harmer
5.761
945391AF1-204 GEN
Solar/Wind Harmer
6.765
276916AD2-100_GEN
Solar/Wind Harmer
13.364
276911AD2-131_GEN
Solar/Wind Harmer
0.88
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.651
24728805RICHG1
Adder
3.384
24728905RICHG2
Adder
3.384
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
960251AF2-316 GEN
Solar/Wind Harmer
8.583
960201AF2-311 GEN
Solar/Wind Harmer
5.708
960611AF2-352 GEN
Solar/Wind Harmer
2.073
966841AG1-555 GEN
Solar/Wind Harmer
0.701
276782AC1-033 GEN
Solar/Wind Harmer
0.001
276741O09 GEN1
Solar/Wind Harmer
0.22
276708O09 GEN2
Solar/Wind Harmer
0.22
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.243
276646AC1-214 GEN2
Solar/Wind Harmer
0.243
972267AH1-718 GEN
Adder
3.688
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
8.241
274765LEE CO EC;6U
Adder
8.241
274762LEE CO EC;3U
Adder
8.222
274763LEE CO EC;4U
Adder
8.144
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
3.491
274856ECOGROVE ;U1
Solar/Wind Harmer
0.145
276611AD2-172 GEN
Solar/Wind Harmer
0.002
270383AD1-128 GEN
Solar/Wind Harmer
0.004
971341AH1-150 GEN
Solar/Wind Harmer
12.273
971343AH1-151 GEN
Solar/Wind Harmer
12.273
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
971333AH1-146 GEN
Solar/Wind Harmer
12.256
971335AH1-147 GEN
Solar/Wind Harmer
12.256
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
942991AE2-321 GEN
Solar/Wind Harmer
6.834
971613AH1-306 GEN
Solar/Wind Harmer
2.937
274879MINONK ;1U
Solar/Wind Harmer
0.258
970921AG2-575 GEN
Solar/Wind Harmer
6.111
970921AG2-575 GEN
Solar/Wind Harmer
2.037
962691AG1-118 GEN
Solar/Wind Harmer
18.322
958491AF2-143 GEN
Solar/Wind Harmer
9.158
960441AF2-335 GEN
Solar/Wind Harmer
6.106
970825AG2-519 GEN
Solar/Wind Harmer
6.767
274683WAUKEGAN ;8U
Adder
18.419
274683WAUKEGAN ;8U
Adder
15.526
274696ROCKY RD ;4P
Adder
9.957
274695ROCKY RD ;2P
Adder
9.727
274693ROCKY RD ;1P
Adder
9.632
274697ROCKY RD ;3P
Adder
2.642
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.824
958481AF2-142 GEN
Solar/Wind Harmer
9.131
971573AH1-285 GEN
Solar/Wind Harmer
1.134
3132123MT JACKSON
Solar/Wind Helper
1.389
315821AE2-092 GEN
Solar/Wind Helper
3.216
966001AG1-469 GEN
Solar/Wind Helper
0.32
315651AD1-115 GEN
Solar/Wind Helper
0.837
966871AG1-558 GEN
Solar/Wind Helper
0.306
316447AC1-158 HLD
Solar/Wind Helper
2.766
316468AD1-105 GEN
Solar/Wind Helper
1.124
971543AH1-269 GEN
50/50
12.247
966391AG1-508 GEN
Solar/Wind Harmer
1.993
270069AE2-166 C O1
Solar/Wind Harmer
0.008
971313AH1-133 GEN
Solar/Wind Harmer
10.952
24734705WLF1G3
Adder
8.194
24734805WLF1G4
Adder
8.194
24734905WLF1G5
Adder
8.194
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.023
270399AC1-101 GEN
Solar/Wind Harmer
2.892
270400AC1-102 GEN
Solar/Wind Harmer
2.892
941621AE2-160 GEN
Adder
4.285
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
970281AG2-184 GEN
Solar/Wind Harmer
18.925
972143AH1-644 GEN
Solar/Wind Harmer
9.763
971981AH1-535 GEN
Solar/Wind Harmer
5.843
971061AG2-657 GEN
Solar/Wind Harmer
5.368
24477305BRIDGE
Adder
0.419
972203AH1-686 GEN
Adder
2.704
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
965401AG1-405 GEN
Solar/Wind Harmer
4.227
965411AG1-406 GEN
Solar/Wind Harmer
2.719
339211AE2-254 GEN
Solar/Wind Harmer
0.003
3429211JKCT 2G
Adder
11.873
970455AG2-298 GEN
Solar/Wind Harmer
4.677
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
972163AH1-664 GEN
Solar/Wind Harmer
7.568
972165AH1-665 GEN
Solar/Wind Harmer
6.061
971985AH1-537 GEN
Solar/Wind Harmer
2.011
270367AC2-061_GEN
Solar/Wind Harmer
0.005
316123AC1-075 GEN
Solar/Wind Harmer
0.168
970165AG2-112 GEN
Solar/Wind Harmer
0.998
970163AG2-111 GEN
Solar/Wind Harmer
0.952
25196108MFTGT2
Adder
1.425
25196108MFTGT2
Adder
1.324
970879AG2-548 GEN
Solar/Wind Harmer
5.761
944221AF1-090 GEN
Solar/Wind Harmer
3.754
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.08
25196308WSDLE2
Adder
8.01
25196208WSDLE1
Adder
7.99
25196708WSDLE6
Adder
7.97
25196508WSDLE4
Adder
7.769
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.229
276848AB2-070 GEN3
Solar/Wind Harmer
0.228
963841AG1-237 GEN
Solar/Wind Harmer
2.698
946321AF1-296 GEN
Solar/Wind Harmer
3.483
270340AC2-060 GEN
Solar/Wind Harmer
0.007
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.505
941731AE2-173 GEN
Solar/Wind Harmer
5.162
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.204
961011AF2-392 GEN
Solar/Wind Harmer
3.623
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270240V3-007_GEN2
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
9.917
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.045
970169AG2-114 GEN
Solar/Wind Harmer
6.149
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
17.15
971171AH1-044 GEN
Solar/Wind Harmer
12.273
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971675AH1-338 GEN
Solar/Wind Harmer
2.39
971411AH1-196 GEN
Solar/Wind Harmer
9.19
970289AG2-191 GEN
Solar/Wind Harmer
1.163
971177AH1-047 GEN
Solar/Wind Harmer
3.774
270594AE1-207 GEN
Solar/Wind Harmer
6.853
276868AE1-113 GEN
Solar/Wind Harmer
1.227
276882AE2-255 GEN
Solar/Wind Harmer
0.715
970115AG2-085 GEN
Solar/Wind Harmer
2.442
971673AH1-337 GEN
Solar/Wind Harmer
3.956
274746AC1-111 G10
Adder
4.87
274744AC1-111 GEN8
Adder
4.87
25306009OHH W.
Adder
2.505
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.313
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.078
316164AC1-076 GEN
Solar/Wind Helper
1.172
238152AF2-075_GEN
Solar/Wind Helper
0.602
971029AG2-637 GEN
Solar/Wind Harmer
2.803
316097T157 G90
Solar/Wind Helper
1.125
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316336AC2-165 C
Solar/Wind Helper
1.285
316006AB2-029 C
Solar/Wind Helper
0.112
316045AC1-158 PL2
Solar/Wind Helper
4.023
944201AF1-088_MTX
Adder
109.09
957141AF2-008_MTX
Adder
54.545
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.415
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.315
MECLTFEXP_MEC->PJM
CLTF
15.415
SIGELTFEXP_SIGE->PJM
CLTF
0.508
NYPJM->LTFIMP_NY
CLTF
3.248
LGEELTFEXP_LGEE->PJM
CLTF
6.763
WECLTFEXP_WEC->PJM
CLTF
3.371
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
CPLELTFEXP_CPLE->PJM
CLTF
6.226
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.111
LAGNLTFEXP_LAGN->PJM
CLTF
20.28
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.555
TVALTFEXP_TVA->PJM
CLTF
10.606

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-020_SRT-SL


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.02 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4224.55
MW Contribution:11.95
Bus #Bus NameTypeMW Contribution
970479AG2-310 GEN
50/50
20.278
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.241
966251AG1-494 GEN
50/50
4.391
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
7.012
971329AH1-144 GEN
Solar/Wind Harmer
23.734
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
9.82
270197AD1-017 GEN1
Solar/Wind Harmer
2.549
270336AE1-100 GEN
Solar/Wind Harmer
2.762
943811AF1-049 GEN
Solar/Wind Harmer
5.705
24728305BUCHG2
Adder
6.772
270018AE2-047 C O1
Solar/Wind Harmer
1.828
958131AF2-107 GEN
Solar/Wind Harmer
7.112
24735205WLF2G2
Adder
8.049
971687AH1-348 GEN
Solar/Wind Harmer
1.364
971403AH1-188 GEN
Solar/Wind Harmer
18.932
24723205RIVRG3
Adder
23.068
971315AH1-136 GEN
Solar/Wind Harmer
2.441
24686105CER G3
Adder
9.94
24686505CER G6
Adder
9.927
270331AC1-082 GEN3
Solar/Wind Harmer
0.49
970947AG2-589 GEN
Solar/Wind Harmer
2.153
24721705FLATG2
Adder
21.813
970273AG2-179 GEN
Solar/Wind Harmer
2.594
971821AH1-427 GEN
Solar/Wind Harmer
10.401
964901AG1-354 GEN
Solar/Wind Harmer
15.577
960001AF2-291 GEN
Solar/Wind Harmer
3.136
339241AF1-083 GEN
Solar/Wind Harmer
1.723
962241AG1-070 GEN
Solar/Wind Harmer
4.662
3429241JKCT 3G
Adder
12.097
3429421JKCT 10G
Adder
8.45
971565AH1-281 GEN
Solar/Wind Harmer
2.012
943111AE2-339 GEN
Solar/Wind Harmer
0.888
339216AC1-074 GEN
Solar/Wind Harmer
1.659
945681AF1-233 GEN
Solar/Wind Harmer
18.436
927014AC1-188 GEN
Solar/Wind Harmer
1.543
970091AG2-072 GEN
Adder
74.457
970333AG2-219 GEN
Solar/Wind Harmer
30.235
270445AC2-157 GEN2
Solar/Wind Harmer
5.271
25196808ZIMRHP
Adder
71.09
252507AC2-088 GEN
Solar/Wind Harmer
1.681
25196008MFTGT1
Adder
1.302
25194608D.CRK4
Adder
1.519
965911AG1-460 GEN
Solar/Wind Harmer
1.278
253432AC1-085 GEN2
Solar/Wind Harmer
0.245
946171AF1-282 GEN
Solar/Wind Harmer
9.139
24728605AND G2
Adder
3.502
276615X2-022 GEN
Solar/Wind Harmer
1.783
963831AG1-236 GEN
Solar/Wind Harmer
8.931
274880W4-005 GEN4
Solar/Wind Harmer
2.743
963741AG1-226 GEN
Solar/Wind Harmer
40.621
274761LEE CO EC;2U
Adder
8.273
274766LEE CO EC;7U
Adder
8.175
972235AH1-702 GEN1
Adder
2.234
274822ROCKFORD ;11
Adder
17.383
274828WAUKEGAN ;BP
Adder
9.716
274682WAUKEGAN ;7U
Adder
15.803
274745AC1-111 GEN9
Adder
4.901
253370AE2-315 SEC1
Adder
1.753
253371AE2-315 SEC2
Adder
1.658
315616AA1-038_C
Solar/Wind Helper
3.295
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.727
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.628
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.388
23583801GRNGAP
Solar/Wind Helper
4.315
316095T157 G97
Solar/Wind Helper
1.133
238147AE2-230_GEN1
Solar/Wind Helper
0.423
238149AF1-291A_GEN
Solar/Wind Helper
0.121
966881AG1-559 GEN
Solar/Wind Helper
0.314
316313AB2-026
Solar/Wind Helper
0.355
316258AE1-075 C
Solar/Wind Helper
0.319
316405AF2-144 C
Solar/Wind Helper
0.266
316044AC1-158 PL1
Solar/Wind Helper
1.263
316450AC1-158 RIC
Solar/Wind Helper
0.337
316473AC1-191 GEN
Solar/Wind Helper
1.391
972175AH1-670 GEN
Solar/Wind Harmer
4.749
970823AG2-518 GEN
50/50
8.396
247619Y1-049
50/50
0.915
24684705SMG5
50/50
0.857
970481AG2-311 GEN
50/50
11.948
24728405LEESVG
50/50
0.296
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.959
962751AG1-124 GEN
Solar/Wind Harmer
18.84
958121AF2-106 GEN
Solar/Wind Harmer
9.423
270173AC1-122 GEN
Solar/Wind Harmer
3.281
971331AH1-145 GEN
Solar/Wind Harmer
18.398
943031AE2-326 GEN
Solar/Wind Harmer
6.798
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.82
270574AD1-017 GEN2
Solar/Wind Harmer
8.482
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.986
270030AE2-140 GEN
Solar/Wind Harmer
30.98
960911AF2-382 GEN
Solar/Wind Harmer
10.985
270016AE1-250 BESS
Solar/Wind Harmer
3.259
970913AG2-568 GEN
Solar/Wind Harmer
11.054
971461AH1-227 GEN
Solar/Wind Harmer
7.029
24290605CLAY-1
50/50
0.256
24290605CLAY-1
50/50
0.256
24290705CLAY-2
50/50
0.256
24290705CLAY-2
50/50
0.256
24684405SMG2
50/50
2.226
24684505SMG3
50/50
1.377
24684305SMG1
50/50
0.807
270583AD2-179 GEN
Solar/Wind Harmer
20.758
270214AC2-123 GEN
Solar/Wind Harmer
4.319
971277AH1-098 GEN
Solar/Wind Harmer
7.435
316217AC1-145 GEN
Solar/Wind Harmer
4.25
316197AC1-042 GEN
Solar/Wind Harmer
3.222
942671AE2-283 GEN
Solar/Wind Harmer
8.674
24728205BUCHG1
Adder
6.772
270013AE1-250 PV
Solar/Wind Harmer
3.259
971225AH1-072 GEN
Solar/Wind Harmer
2.74
971227AH1-073 GEN
Solar/Wind Harmer
2.74
944971AF1-162 GEN
Solar/Wind Harmer
9.108
24723005RIVRG1
Adder
23.068
24723105RIVRG2
Adder
23.068
24685805CER G1
Adder
9.875
24685905CER G2
Adder
9.875
942751AE2-291 GEN
Solar/Wind Harmer
10.391
966021AG1-471 GEN
Solar/Wind Harmer
5.779
971485AH1-239 GEN
Solar/Wind Harmer
8.537
339231AF1-038_GEN
Solar/Wind Harmer
1.927
960161AF2-307 GEN
Solar/Wind Harmer
6.695
339255AE2-071 GEN
Solar/Wind Harmer
1.104
964781AG1-341 GEN
Solar/Wind Harmer
11.023
339236AF1-050_GEN
Solar/Wind Harmer
1.882
971081AG2-670 GEN
Solar/Wind Harmer
7.773
942891AE2-308 GEN
Solar/Wind Harmer
10.233
970653AG2-424 GEN
Solar/Wind Harmer
4.906
970653AG2-424 GEN
Solar/Wind Harmer
1.774
964571AG1-320 GEN
Solar/Wind Harmer
8.231
971125AH1-004 GEN
Solar/Wind Harmer
4.003
970107AG2-081 GEN
Solar/Wind Harmer
3.003
972043AH1-570 GEN
Solar/Wind Harmer
2.49
972045AH1-571 GEN
Solar/Wind Harmer
1.992
339221AD2-048_GEN
Solar/Wind Harmer
1.523
970235AG2-159 GEN
Solar/Wind Harmer
3.901
970235AG2-159 GEN
Solar/Wind Harmer
2.382
270186AC1-089 GEN
Solar/Wind Harmer
5.863
970239AG2-162 GEN
Solar/Wind Harmer
10.536
962581AG1-107 GEN
Solar/Wind Harmer
4.763
961491AF2-440 GEN
Solar/Wind Harmer
1.98
270444AC2-157 GEN1
Solar/Wind Harmer
5.271
252509AD1-136 GEN
Solar/Wind Harmer
0.24
25183208HLCRTG
Solar/Wind Harmer
5.62
252519AF1-045_GEN
Solar/Wind Harmer
5.628
252516AE2-318_GEN
Solar/Wind Harmer
4.293
970879AG2-548 GEN
Solar/Wind Harmer
5.702
971073AG2-665 GEN
Solar/Wind Harmer
5.702
971073AG2-665 GEN
Solar/Wind Harmer
3.978
25194408D.CRK1
Adder
6.985
25194508D.CRK3
Adder
1.306
945391AF1-204 GEN
Solar/Wind Harmer
12.796
276916AD2-100_GEN
Solar/Wind Harmer
19.269
276911AD2-131_GEN
Solar/Wind Harmer
3.894
957381AF2-032 GEN
Solar/Wind Harmer
0.383
253317AC1-085 GEN4
Solar/Wind Harmer
7.655
276763AC1-053 GEN1
Solar/Wind Harmer
3.59
276764AC1-053 GEN2
Solar/Wind Harmer
3.59
970241AG2-163 GEN
Solar/Wind Harmer
22.567
24728805RICHG1
Adder
3.406
24728905RICHG2
Adder
3.406
972267AH1-718 GEN
Adder
3.711
274764LEE CO EC;5U
Adder
8.292
274765LEE CO EC;6U
Adder
8.292
274762LEE CO EC;3U
Adder
8.273
274763LEE CO EC;4U
Adder
8.195
274683WAUKEGAN ;8U
Adder
18.536
274683WAUKEGAN ;8U
Adder
15.625
274696ROCKY RD ;4P
Adder
10.02
274695ROCKY RD ;2P
Adder
9.789
274693ROCKY RD ;1P
Adder
9.693
274697ROCKY RD ;3P
Adder
2.659
253370AE2-315 SEC1
Adder
1.753
3132123MT JACKSON
Solar/Wind Helper
1.392
315821AE2-092 GEN
Solar/Wind Helper
3.222
966001AG1-469 GEN
Solar/Wind Helper
0.321
315651AD1-115 GEN
Solar/Wind Helper
0.841
316447AC1-158 HLD
Solar/Wind Helper
2.779
966871AG1-558 GEN
Solar/Wind Helper
0.307
316468AD1-105 GEN
Solar/Wind Helper
1.129
970223AG2-152 GEN
Solar/Wind Harmer
17.643
270053AF1-130 C
Solar/Wind Harmer
4.837
972103AH1-617 GEN
Solar/Wind Harmer
25.94
24686205CER G4
Adder
9.888
24686405CER G5
Adder
9.849
972273AH1-721 GEN
Adder
89.748
24721905FLATG4
Adder
21.813
970273AG2-179 GEN
Solar/Wind Harmer
4.143
339250AF1-203 GEN
Solar/Wind Harmer
0.631
971155AH1-034 GEN
Solar/Wind Harmer
10.404
966571AG1-526 GEN
Solar/Wind Harmer
23.009
962251AG1-071 GEN
Solar/Wind Harmer
5.699
970093AG2-073 GEN
Solar/Wind Harmer
10.328
960741AF2-365 GEN
Solar/Wind Harmer
5.133
971191AH1-055 GEN
Solar/Wind Harmer
22.339
3429391JKCT 9G
Adder
8.45
972167AH1-666 GEN
Solar/Wind Harmer
7.817
957541AF2-048 GEN
Solar/Wind Harmer
1.539
958171AF2-111 GEN
Solar/Wind Harmer
24.064
970243AG2-164 GEN
Solar/Wind Harmer
24.738
970519AG2-331 GEN
Solar/Wind Harmer
16.62
970699AG2-449 GEN
Solar/Wind Harmer
10.995
25196008MFTGT1
Adder
1.261
252510AF1-249 C
Solar/Wind Harmer
0.387
25194608D.CRK4
Adder
1.519
25196608WSDLE5
Adder
7.903
970193AG2-126 GEN
Solar/Wind Harmer
13.773
942481AE2-261 GEN
Solar/Wind Harmer
27.393
253316AC1-085 GEN3
Solar/Wind Harmer
7.655
253433AC1-085 GEN1
Solar/Wind Harmer
4.859
946181AF1-283 GEN
Solar/Wind Harmer
11.881
24728705AND G3
Adder
7.324
24728505AND G1
Adder
3.502
276621W2-048 GEN
Solar/Wind Harmer
5.679
276838X2-022 GEN2
Solar/Wind Harmer
0.212
276686W4-005 GEN3
Solar/Wind Harmer
2.743
276668AB2-070 GEN1
Solar/Wind Harmer
2.04
971993AH1-541 GEN
Solar/Wind Harmer
8.379
253406AD2-031_GEN
Solar/Wind Harmer
1.157
270356AE2-297 GEN
Solar/Wind Harmer
4.125
274760LEE CO EC;1U
Adder
8.273
274767LEE CO EC;8U
Adder
8.175
972236AH1-702 GEN2
Adder
1.942
274682WAUKEGAN ;7U
Adder
15.803
253370AE2-315 SEC1
Adder
1.753
253371AE2-315 SEC2
Adder
1.658
274729ELWOOD EC;1P
Adder
1.688
3147983MERCK5
Solar/Wind Helper
0.199
316192AB2-158 GEN
Solar/Wind Helper
1.845
3147666LOUISA
Solar/Wind Helper
1.091
316254AC1-120 GEN1
Solar/Wind Helper
1.164
316097T157 G90
Solar/Wind Helper
1.133
238148AE2-230_GEN2
Solar/Wind Helper
0.425
316336AC2-165 C
Solar/Wind Helper
1.289
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.042
3142416OLDCHRC
Solar/Wind Helper
0.58
3142416OLDCHRC
Solar/Wind Helper
0.222
971543AH1-269 GEN
50/50
12.267
966391AG1-508 GEN
Solar/Wind Harmer
6.388
270069AE2-166 C O1
Solar/Wind Harmer
4.514
971313AH1-133 GEN
Solar/Wind Harmer
15.745
24734705WLF1G3
Adder
8.22
24734805WLF1G4
Adder
8.22
24734905WLF1G5
Adder
8.22
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.049
270399AC1-101 GEN
Solar/Wind Harmer
5.58
270400AC1-102 GEN
Solar/Wind Harmer
5.58
941621AE2-160 GEN
Adder
4.308
957241AF2-018 GEN
Solar/Wind Harmer
5.782
970281AG2-184 GEN
Solar/Wind Harmer
27.237
972143AH1-644 GEN
Solar/Wind Harmer
12.97
971981AH1-535 GEN
Solar/Wind Harmer
12.604
962211AG1-066 GEN
Solar/Wind Harmer
3.014
971061AG2-657 GEN
Solar/Wind Harmer
11.059
24477305BRIDGE
Adder
0.422
972203AH1-686 GEN
Adder
2.718
270330AC1-082 GEN2
Solar/Wind Harmer
0.83
270329AC1-082 GEN1
Solar/Wind Harmer
0.489
965401AG1-405 GEN
Solar/Wind Harmer
6.089
965411AG1-406 GEN
Solar/Wind Harmer
2.733
339211AE2-254 GEN
Solar/Wind Harmer
1.572
3429211JKCT 2G
Adder
11.941
970455AG2-298 GEN
Solar/Wind Harmer
6.067
339243AC2-075 GEN1
Solar/Wind Harmer
0.449
972163AH1-664 GEN
Solar/Wind Harmer
9.805
972165AH1-665 GEN
Solar/Wind Harmer
7.844
971985AH1-537 GEN
Solar/Wind Harmer
17.415
270367AC2-061_GEN
Solar/Wind Harmer
3.029
316123AC1-075 GEN
Solar/Wind Harmer
1.494
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.255
25196108MFTGT2
Adder
1.435
25196108MFTGT2
Adder
1.332
970879AG2-548 GEN
Solar/Wind Harmer
3.978
944221AF1-090 GEN
Solar/Wind Harmer
10.083
252524AE2-267 GEN
Solar/Wind Harmer
1.454
25196408WSDLE3
Adder
8.135
25196308WSDLE2
Adder
8.064
25196208WSDLE1
Adder
8.044
25196708WSDLE6
Adder
8.024
25196508WSDLE4
Adder
7.822
276785W4-005 GEN1
Solar/Wind Harmer
2.743
276174W4-005 GEN2
Solar/Wind Harmer
2.743
276849AB2-070 GEN2
Solar/Wind Harmer
2.04
276848AB2-070 GEN3
Solar/Wind Harmer
2.04
274823ROCKFORD ;21
Adder
17.257
274746AC1-111 G10
Adder
4.901
274744AC1-111 GEN8
Adder
4.901
25306009OHH W.
Adder
2.523
253372AE2-315 SEC3
Adder
1.658
253372AE2-315 SEC3
Adder
1.658
3148463FAIRFLD
Solar/Wind Helper
0.727
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.301
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.079
316164AC1-076 GEN
Solar/Wind Helper
1.177
238152AF2-075_GEN
Solar/Wind Helper
0.605
316312AB1-027
Solar/Wind Helper
0.425
3141426STAFORD
Solar/Wind Helper
0.049
944201AF1-088_MTX
Adder
109.749
957141AF2-008_MTX
Adder
54.874
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.199
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.491
MECLTFEXP_MEC->PJM
CLTF
15.504
SIGELTFEXP_SIGE->PJM
CLTF
0.511
NYPJM->LTFIMP_NY
CLTF
3.272
LGEELTFEXP_LGEE->PJM
CLTF
6.802
WECLTFEXP_WEC->PJM
CLTF
3.393
AG2-052LTFEXP_AG2-052->PJM
LTF
0.203
AH1-155LTFEXP_AH1-155->PJM
LTF
0.304
CPLELTFEXP_CPLE->PJM
CLTF
6.237
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.77
LAGNLTFEXP_LAGN->PJM
CLTF
20.369
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.617
TVALTFEXP_TVA->PJM
CLTF
10.651

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-021_SRT-SL


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.77 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4215.43
MW Contribution:11.94
Bus #Bus NameTypeMW Contribution
970479AG2-310 GEN
50/50
20.262
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
966251AG1-494 GEN
50/50
4.389
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
7.006
971329AH1-144 GEN
Solar/Wind Harmer
23.701
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
9.814
270197AD1-017 GEN1
Solar/Wind Harmer
2.547
270336AE1-100 GEN
Solar/Wind Harmer
2.759
943811AF1-049 GEN
Solar/Wind Harmer
5.698
24728305BUCHG2
Adder
6.757
270018AE2-047 C O1
Solar/Wind Harmer
1.826
958131AF2-107 GEN
Solar/Wind Harmer
7.109
24735205WLF2G2
Adder
8.031
971687AH1-348 GEN
Solar/Wind Harmer
1.36
971403AH1-188 GEN
Solar/Wind Harmer
18.877
24723205RIVRG3
Adder
22.989
971315AH1-136 GEN
Solar/Wind Harmer
2.433
24686105CER G3
Adder
9.903
24686505CER G6
Adder
9.89
270331AC1-082 GEN3
Solar/Wind Harmer
0.488
24721705FLATG2
Adder
21.725
970947AG2-589 GEN
Solar/Wind Harmer
2.143
970273AG2-179 GEN
Solar/Wind Harmer
2.585
971821AH1-427 GEN
Solar/Wind Harmer
10.363
964901AG1-354 GEN
Solar/Wind Harmer
15.523
339241AF1-083 GEN
Solar/Wind Harmer
1.717
962241AG1-070 GEN
Solar/Wind Harmer
4.647
960001AF2-291 GEN
Solar/Wind Harmer
3.12
3429241JKCT 3G
Adder
12.05
3429421JKCT 10G
Adder
8.417
971565AH1-281 GEN
Solar/Wind Harmer
2.004
943111AE2-339 GEN
Solar/Wind Harmer
0.884
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684405SMG2
50/50
2.225
24684505SMG3
50/50
1.376
24684305SMG1
50/50
0.806
270583AD2-179 GEN
Solar/Wind Harmer
20.732
270214AC2-123 GEN
Solar/Wind Harmer
4.313
971277AH1-098 GEN
Solar/Wind Harmer
7.425
316217AC1-145 GEN
Solar/Wind Harmer
4.248
316197AC1-042 GEN
Solar/Wind Harmer
3.22
942671AE2-283 GEN
Solar/Wind Harmer
8.669
24728205BUCHG1
Adder
6.757
270013AE1-250 PV
Solar/Wind Harmer
3.257
971225AH1-072 GEN
Solar/Wind Harmer
2.733
971227AH1-073 GEN
Solar/Wind Harmer
2.733
944971AF1-162 GEN
Solar/Wind Harmer
9.08
24723005RIVRG1
Adder
22.989
24723105RIVRG2
Adder
22.989
24685805CER G1
Adder
9.838
24685905CER G2
Adder
9.838
942751AE2-291 GEN
Solar/Wind Harmer
10.387
966021AG1-471 GEN
Solar/Wind Harmer
5.761
971485AH1-239 GEN
Solar/Wind Harmer
8.509
339231AF1-038_GEN
Solar/Wind Harmer
1.921
960161AF2-307 GEN
Solar/Wind Harmer
6.669
339255AE2-071 GEN
Solar/Wind Harmer
1.1
964781AG1-341 GEN
Solar/Wind Harmer
10.986
339236AF1-050_GEN
Solar/Wind Harmer
1.875
971081AG2-670 GEN
Solar/Wind Harmer
7.746
942891AE2-308 GEN
Solar/Wind Harmer
10.193
970653AG2-424 GEN
Solar/Wind Harmer
4.888
970653AG2-424 GEN
Solar/Wind Harmer
1.767
964571AG1-320 GEN
Solar/Wind Harmer
8.199
971125AH1-004 GEN
Solar/Wind Harmer
3.987
970107AG2-081 GEN
Solar/Wind Harmer
2.99
972043AH1-570 GEN
Solar/Wind Harmer
2.479
972045AH1-571 GEN
Solar/Wind Harmer
1.983
339221AD2-048_GEN
Solar/Wind Harmer
1.517
970235AG2-159 GEN
Solar/Wind Harmer
3.885
970235AG2-159 GEN
Solar/Wind Harmer
2.372
270186AC1-089 GEN
Solar/Wind Harmer
5.836
970239AG2-162 GEN
Solar/Wind Harmer
10.492
962581AG1-107 GEN
Solar/Wind Harmer
4.741
961491AF2-440 GEN
Solar/Wind Harmer
1.97
270444AC2-157 GEN1
Solar/Wind Harmer
5.249
252509AD1-136 GEN
Solar/Wind Harmer
0.239
25183208HLCRTG
Solar/Wind Harmer
5.594
252519AF1-045_GEN
Solar/Wind Harmer
5.601
252516AE2-318_GEN
Solar/Wind Harmer
4.272
970879AG2-548 GEN
Solar/Wind Harmer
5.67
971073AG2-665 GEN
Solar/Wind Harmer
5.67
971073AG2-665 GEN
Solar/Wind Harmer
3.956
25194408D.CRK1
Adder
6.953
25194508D.CRK3
Adder
1.3
945391AF1-204 GEN
Solar/Wind Harmer
12.742
276916AD2-100_GEN
Solar/Wind Harmer
19.19
276911AD2-131_GEN
Solar/Wind Harmer
3.878
957381AF2-032 GEN
Solar/Wind Harmer
0.382
253317AC1-085 GEN4
Solar/Wind Harmer
7.618
276763AC1-053 GEN1
Solar/Wind Harmer
3.575
276764AC1-053 GEN2
Solar/Wind Harmer
3.575
970241AG2-163 GEN
Solar/Wind Harmer
22.469
24728805RICHG1
Adder
3.391
24728905RICHG2
Adder
3.391
972267AH1-718 GEN
Adder
3.695
274764LEE CO EC;5U
Adder
8.257
274765LEE CO EC;6U
Adder
8.257
274762LEE CO EC;3U
Adder
8.237
274763LEE CO EC;4U
Adder
8.16
274683WAUKEGAN ;8U
Adder
18.455
274683WAUKEGAN ;8U
Adder
15.556
274696ROCKY RD ;4P
Adder
9.976
274695ROCKY RD ;2P
Adder
9.746
274693ROCKY RD ;1P
Adder
9.65
274697ROCKY RD ;3P
Adder
2.648
253370AE2-315 SEC1
Adder
1.744
3132123MT JACKSON
Solar/Wind Helper
1.39
315821AE2-092 GEN
Solar/Wind Helper
3.218
966001AG1-469 GEN
Solar/Wind Helper
0.32
315651AD1-115 GEN
Solar/Wind Helper
0.839
966871AG1-558 GEN
Solar/Wind Helper
0.306
316447AC1-158 HLD
Solar/Wind Helper
2.77
316468AD1-105 GEN
Solar/Wind Helper
1.126
970823AG2-518 GEN
50/50
8.387
247619Y1-049
50/50
0.914
24684705SMG5
50/50
0.857
970481AG2-311 GEN
50/50
11.94
24728405LEESVG
50/50
0.296
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.869
962751AG1-124 GEN
Solar/Wind Harmer
18.829
958121AF2-106 GEN
Solar/Wind Harmer
9.412
270173AC1-122 GEN
Solar/Wind Harmer
3.279
971331AH1-145 GEN
Solar/Wind Harmer
18.373
943031AE2-326 GEN
Solar/Wind Harmer
6.789
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.814
270574AD1-017 GEN2
Solar/Wind Harmer
8.476
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.951
270030AE2-140 GEN
Solar/Wind Harmer
30.945
960911AF2-382 GEN
Solar/Wind Harmer
10.959
270016AE1-250 BESS
Solar/Wind Harmer
3.257
970913AG2-568 GEN
Solar/Wind Harmer
11.019
971461AH1-227 GEN
Solar/Wind Harmer
7.011
970223AG2-152 GEN
Solar/Wind Harmer
17.629
270053AF1-130 C
Solar/Wind Harmer
4.822
972103AH1-617 GEN
Solar/Wind Harmer
25.867
24686205CER G4
Adder
9.851
24686405CER G5
Adder
9.812
972273AH1-721 GEN
Adder
89.448
24721905FLATG4
Adder
21.725
970273AG2-179 GEN
Solar/Wind Harmer
4.129
339250AF1-203 GEN
Solar/Wind Harmer
0.629
971155AH1-034 GEN
Solar/Wind Harmer
10.369
966571AG1-526 GEN
Solar/Wind Harmer
22.923
962251AG1-071 GEN
Solar/Wind Harmer
5.679
970093AG2-073 GEN
Solar/Wind Harmer
10.289
960741AF2-365 GEN
Solar/Wind Harmer
5.115
3429391JKCT 9G
Adder
8.417
971543AH1-269 GEN
50/50
12.253
966391AG1-508 GEN
Solar/Wind Harmer
6.379
270069AE2-166 C O1
Solar/Wind Harmer
4.509
971313AH1-133 GEN
Solar/Wind Harmer
15.712
24734705WLF1G3
Adder
8.202
24734805WLF1G4
Adder
8.202
24734905WLF1G5
Adder
8.202
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.031
270399AC1-101 GEN
Solar/Wind Harmer
5.563
270400AC1-102 GEN
Solar/Wind Harmer
5.563
941621AE2-160 GEN
Adder
4.292
957241AF2-018 GEN
Solar/Wind Harmer
5.764
970281AG2-184 GEN
Solar/Wind Harmer
27.16
972143AH1-644 GEN
Solar/Wind Harmer
12.933
971981AH1-535 GEN
Solar/Wind Harmer
12.575
962211AG1-066 GEN
Solar/Wind Harmer
3.005
971061AG2-657 GEN
Solar/Wind Harmer
11.012
24477305BRIDGE
Adder
0.42
972203AH1-686 GEN
Adder
2.709
270330AC1-082 GEN2
Solar/Wind Harmer
0.826
270329AC1-082 GEN1
Solar/Wind Harmer
0.486
965401AG1-405 GEN
Solar/Wind Harmer
6.068
965411AG1-406 GEN
Solar/Wind Harmer
2.724
339211AE2-254 GEN
Solar/Wind Harmer
1.566
3429211JKCT 2G
Adder
11.894
970455AG2-298 GEN
Solar/Wind Harmer
6.044
339243AC2-075 GEN1
Solar/Wind Harmer
0.447
972163AH1-664 GEN
Solar/Wind Harmer
9.762
972165AH1-665 GEN
Solar/Wind Harmer
7.81
971985AH1-537 GEN
Solar/Wind Harmer
17.332
270367AC2-061_GEN
Solar/Wind Harmer
3.015
316123AC1-075 GEN
Solar/Wind Harmer
1.493
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.254
25196108MFTGT2
Adder
1.428
25196108MFTGT2
Adder
1.326
970879AG2-548 GEN
Solar/Wind Harmer
3.956
944221AF1-090 GEN
Solar/Wind Harmer
10.042
252524AE2-267 GEN
Solar/Wind Harmer
1.447
25196408WSDLE3
Adder
8.097
25196308WSDLE2
Adder
8.027
25196208WSDLE1
Adder
8.006
25196708WSDLE6
Adder
7.986
25196508WSDLE4
Adder
7.785
276849AB2-070 GEN2
Solar/Wind Harmer
2.031
276848AB2-070 GEN3
Solar/Wind Harmer
2.031
276785W4-005 GEN1
Solar/Wind Harmer
2.731
276174W4-005 GEN2
Solar/Wind Harmer
2.731
274823ROCKFORD ;21
Adder
17.182
274746AC1-111 G10
Adder
4.879
274744AC1-111 GEN8
Adder
4.879
25306009OHH W.
Adder
2.51
253372AE2-315 SEC3
Adder
1.649
253372AE2-315 SEC3
Adder
1.649
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.314
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.079
316164AC1-076 GEN
Solar/Wind Helper
1.173
238152AF2-075_GEN
Solar/Wind Helper
0.603
339216AC1-074 GEN
Solar/Wind Harmer
1.652
945681AF1-233 GEN
Solar/Wind Harmer
18.356
927014AC1-188 GEN
Solar/Wind Harmer
1.535
970091AG2-072 GEN
Adder
74.149
970333AG2-219 GEN
Solar/Wind Harmer
30.107
270445AC2-157 GEN2
Solar/Wind Harmer
5.249
25196808ZIMRHP
Adder
70.761
252507AC2-088 GEN
Solar/Wind Harmer
1.673
25196008MFTGT1
Adder
1.296
25194608D.CRK4
Adder
1.511
965911AG1-460 GEN
Solar/Wind Harmer
1.273
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
946171AF1-282 GEN
Solar/Wind Harmer
9.095
24728605AND G2
Adder
3.486
276615X2-022 GEN
Solar/Wind Harmer
1.776
963831AG1-236 GEN
Solar/Wind Harmer
8.893
274880W4-005 GEN4
Solar/Wind Harmer
2.731
963741AG1-226 GEN
Solar/Wind Harmer
40.444
274761LEE CO EC;2U
Adder
8.237
274766LEE CO EC;7U
Adder
8.14
972235AH1-702 GEN1
Adder
2.224
274822ROCKFORD ;11
Adder
17.308
274828WAUKEGAN ;BP
Adder
9.674
274682WAUKEGAN ;7U
Adder
15.734
274745AC1-111 GEN9
Adder
4.879
253370AE2-315 SEC1
Adder
1.744
253371AE2-315 SEC2
Adder
1.649
315616AA1-038_C
Solar/Wind Helper
3.294
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.725
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.626
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.387
23583801GRNGAP
Solar/Wind Helper
4.296
316095T157 G97
Solar/Wind Helper
1.128
238147AE2-230_GEN1
Solar/Wind Helper
0.422
238149AF1-291A_GEN
Solar/Wind Helper
0.12
966881AG1-559 GEN
Solar/Wind Helper
0.314
316313AB2-026
Solar/Wind Helper
0.354
316258AE1-075 C
Solar/Wind Helper
0.319
316405AF2-144 C
Solar/Wind Helper
0.266
316473AC1-191 GEN
Solar/Wind Helper
1.388
316044AC1-158 PL1
Solar/Wind Helper
1.259
316450AC1-158 RIC
Solar/Wind Helper
0.336
972175AH1-670 GEN
Solar/Wind Harmer
4.729
971191AH1-055 GEN
Solar/Wind Harmer
22.23
972167AH1-666 GEN
Solar/Wind Harmer
7.783
957541AF2-048 GEN
Solar/Wind Harmer
1.531
958171AF2-111 GEN
Solar/Wind Harmer
23.957
970243AG2-164 GEN
Solar/Wind Harmer
24.633
970519AG2-331 GEN
Solar/Wind Harmer
16.549
970699AG2-449 GEN
Solar/Wind Harmer
10.948
25196008MFTGT1
Adder
1.255
252510AF1-249 C
Solar/Wind Harmer
0.385
25194608D.CRK4
Adder
1.511
25196608WSDLE5
Adder
7.866
970193AG2-126 GEN
Solar/Wind Harmer
13.715
942481AE2-261 GEN
Solar/Wind Harmer
27.279
253316AC1-085 GEN3
Solar/Wind Harmer
7.618
253433AC1-085 GEN1
Solar/Wind Harmer
4.836
946181AF1-283 GEN
Solar/Wind Harmer
11.823
24728705AND G3
Adder
7.292
24728505AND G1
Adder
3.486
276621W2-048 GEN
Solar/Wind Harmer
5.656
276838X2-022 GEN2
Solar/Wind Harmer
0.211
276668AB2-070 GEN1
Solar/Wind Harmer
2.031
276686W4-005 GEN3
Solar/Wind Harmer
2.731
971993AH1-541 GEN
Solar/Wind Harmer
8.344
270356AE2-297 GEN
Solar/Wind Harmer
4.106
253406AD2-031_GEN
Solar/Wind Harmer
1.151
274760LEE CO EC;1U
Adder
8.237
274767LEE CO EC;8U
Adder
8.14
972236AH1-702 GEN2
Adder
1.934
274682WAUKEGAN ;7U
Adder
15.734
253370AE2-315 SEC1
Adder
1.744
253371AE2-315 SEC2
Adder
1.649
274729ELWOOD EC;1P
Adder
1.681
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.84
3147666LOUISA
Solar/Wind Helper
1.089
316254AC1-120 GEN1
Solar/Wind Helper
1.161
316097T157 G90
Solar/Wind Helper
1.128
238148AE2-230_GEN2
Solar/Wind Helper
0.424
316336AC2-165 C
Solar/Wind Helper
1.286
316006AB2-029 C
Solar/Wind Helper
0.113
316045AC1-158 PL2
Solar/Wind Helper
4.029
944201AF1-088_MTX
Adder
109.291
957141AF2-008_MTX
Adder
54.646
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.655
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.369
MECLTFEXP_MEC->PJM
CLTF
15.442
SIGELTFEXP_SIGE->PJM
CLTF
0.509
NYPJM->LTFIMP_NY
CLTF
3.255
LGEELTFEXP_LGEE->PJM
CLTF
6.775
WECLTFEXP_WEC->PJM
CLTF
3.378
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
CPLELTFEXP_CPLE->PJM
CLTF
6.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.312
LAGNLTFEXP_LAGN->PJM
CLTF
20.308
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.574
TVALTFEXP_TVA->PJM
CLTF
10.62

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.68 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4211.98
MW Contribution:11.94
Bus #Bus NameTypeMW Contribution
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684405SMG2
50/50
2.224
971543AH1-269 GEN
50/50
12.247
966391AG1-508 GEN
Solar/Wind Harmer
6.374
270069AE2-166 C O1
Solar/Wind Harmer
4.507
971313AH1-133 GEN
Solar/Wind Harmer
15.698
24734705WLF1G3
Adder
8.194
24734805WLF1G4
Adder
8.194
24734905WLF1G5
Adder
8.194
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.023
270399AC1-101 GEN
Solar/Wind Harmer
5.556
270400AC1-102 GEN
Solar/Wind Harmer
5.556
941621AE2-160 GEN
Adder
4.285
957241AF2-018 GEN
Solar/Wind Harmer
5.757
970281AG2-184 GEN
Solar/Wind Harmer
27.126
972143AH1-644 GEN
Solar/Wind Harmer
12.917
971981AH1-535 GEN
Solar/Wind Harmer
12.563
962211AG1-066 GEN
Solar/Wind Harmer
3.001
971061AG2-657 GEN
Solar/Wind Harmer
10.991
24477305BRIDGE
Adder
0.419
972203AH1-686 GEN
Adder
2.704
270330AC1-082 GEN2
Solar/Wind Harmer
0.824
270329AC1-082 GEN1
Solar/Wind Harmer
0.485
965401AG1-405 GEN
Solar/Wind Harmer
6.059
965411AG1-406 GEN
Solar/Wind Harmer
2.719
339211AE2-254 GEN
Solar/Wind Harmer
1.563
3429211JKCT 2G
Adder
11.873
970455AG2-298 GEN
Solar/Wind Harmer
6.034
339243AC2-075 GEN1
Solar/Wind Harmer
0.446
972163AH1-664 GEN
Solar/Wind Harmer
9.743
972165AH1-665 GEN
Solar/Wind Harmer
7.794
971985AH1-537 GEN
Solar/Wind Harmer
17.295
270367AC2-061_GEN
Solar/Wind Harmer
3.009
316123AC1-075 GEN
Solar/Wind Harmer
1.493
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.254
25196108MFTGT2
Adder
1.425
25196108MFTGT2
Adder
1.324
970879AG2-548 GEN
Solar/Wind Harmer
3.946
944221AF1-090 GEN
Solar/Wind Harmer
10.024
252524AE2-267 GEN
Solar/Wind Harmer
1.444
25196408WSDLE3
Adder
8.08
25196308WSDLE2
Adder
8.01
25196208WSDLE1
Adder
7.99
25196708WSDLE6
Adder
7.97
25196508WSDLE4
Adder
7.769
276785W4-005 GEN1
Solar/Wind Harmer
2.726
276174W4-005 GEN2
Solar/Wind Harmer
2.726
276849AB2-070 GEN2
Solar/Wind Harmer
2.027
276848AB2-070 GEN3
Solar/Wind Harmer
2.027
274823ROCKFORD ;21
Adder
17.15
274746AC1-111 G10
Adder
4.87
274744AC1-111 GEN8
Adder
4.87
25306009OHH W.
Adder
2.505
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.313
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.078
316164AC1-076 GEN
Solar/Wind Helper
1.172
238152AF2-075_GEN
Solar/Wind Helper
0.602
24684505SMG3
50/50
1.376
24684305SMG1
50/50
0.806
270583AD2-179 GEN
Solar/Wind Harmer
20.721
270214AC2-123 GEN
Solar/Wind Harmer
4.311
971277AH1-098 GEN
Solar/Wind Harmer
7.42
316217AC1-145 GEN
Solar/Wind Harmer
4.247
316197AC1-042 GEN
Solar/Wind Harmer
3.219
942671AE2-283 GEN
Solar/Wind Harmer
8.667
24728205BUCHG1
Adder
6.75
270013AE1-250 PV
Solar/Wind Harmer
3.256
971225AH1-072 GEN
Solar/Wind Harmer
2.73
971227AH1-073 GEN
Solar/Wind Harmer
2.73
944971AF1-162 GEN
Solar/Wind Harmer
9.068
24723005RIVRG1
Adder
22.954
24723105RIVRG2
Adder
22.954
24685805CER G1
Adder
9.822
24685905CER G2
Adder
9.822
942751AE2-291 GEN
Solar/Wind Harmer
10.385
966021AG1-471 GEN
Solar/Wind Harmer
5.753
971485AH1-239 GEN
Solar/Wind Harmer
8.497
339231AF1-038_GEN
Solar/Wind Harmer
1.918
960161AF2-307 GEN
Solar/Wind Harmer
6.658
339255AE2-071 GEN
Solar/Wind Harmer
1.099
964781AG1-341 GEN
Solar/Wind Harmer
10.97
339236AF1-050_GEN
Solar/Wind Harmer
1.872
971081AG2-670 GEN
Solar/Wind Harmer
7.734
942891AE2-308 GEN
Solar/Wind Harmer
10.176
970653AG2-424 GEN
Solar/Wind Harmer
4.88
970653AG2-424 GEN
Solar/Wind Harmer
1.764
964571AG1-320 GEN
Solar/Wind Harmer
8.186
971125AH1-004 GEN
Solar/Wind Harmer
3.98
970107AG2-081 GEN
Solar/Wind Harmer
2.985
972043AH1-570 GEN
Solar/Wind Harmer
2.475
972045AH1-571 GEN
Solar/Wind Harmer
1.98
339221AD2-048_GEN
Solar/Wind Harmer
1.514
970235AG2-159 GEN
Solar/Wind Harmer
3.878
970235AG2-159 GEN
Solar/Wind Harmer
2.367
270186AC1-089 GEN
Solar/Wind Harmer
5.824
970239AG2-162 GEN
Solar/Wind Harmer
10.472
962581AG1-107 GEN
Solar/Wind Harmer
4.731
961491AF2-440 GEN
Solar/Wind Harmer
1.966
270444AC2-157 GEN1
Solar/Wind Harmer
5.239
252509AD1-136 GEN
Solar/Wind Harmer
0.238
25183208HLCRTG
Solar/Wind Harmer
5.582
252519AF1-045_GEN
Solar/Wind Harmer
5.589
252516AE2-318_GEN
Solar/Wind Harmer
4.263
25194408D.CRK1
Adder
6.938
25194508D.CRK3
Adder
1.297
970879AG2-548 GEN
Solar/Wind Harmer
5.656
971073AG2-665 GEN
Solar/Wind Harmer
5.656
971073AG2-665 GEN
Solar/Wind Harmer
3.946
945391AF1-204 GEN
Solar/Wind Harmer
12.718
276916AD2-100_GEN
Solar/Wind Harmer
19.154
276911AD2-131_GEN
Solar/Wind Harmer
3.871
957381AF2-032 GEN
Solar/Wind Harmer
0.381
253317AC1-085 GEN4
Solar/Wind Harmer
7.601
276763AC1-053 GEN1
Solar/Wind Harmer
3.568
276764AC1-053 GEN2
Solar/Wind Harmer
3.568
970241AG2-163 GEN
Solar/Wind Harmer
22.426
24728805RICHG1
Adder
3.384
24728905RICHG2
Adder
3.384
972267AH1-718 GEN
Adder
3.688
274764LEE CO EC;5U
Adder
8.241
274765LEE CO EC;6U
Adder
8.241
274762LEE CO EC;3U
Adder
8.222
274763LEE CO EC;4U
Adder
8.144
274683WAUKEGAN ;8U
Adder
18.419
274683WAUKEGAN ;8U
Adder
15.526
274696ROCKY RD ;4P
Adder
9.957
274695ROCKY RD ;2P
Adder
9.727
274693ROCKY RD ;1P
Adder
9.632
274697ROCKY RD ;3P
Adder
2.642
3132123MT JACKSON
Solar/Wind Helper
1.389
315821AE2-092 GEN
Solar/Wind Helper
3.216
966001AG1-469 GEN
Solar/Wind Helper
0.32
315651AD1-115 GEN
Solar/Wind Helper
0.837
966871AG1-558 GEN
Solar/Wind Helper
0.306
316447AC1-158 HLD
Solar/Wind Helper
2.766
316468AD1-105 GEN
Solar/Wind Helper
1.124
970479AG2-310 GEN
50/50
20.255
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
966251AG1-494 GEN
50/50
4.388
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
7.003
971329AH1-144 GEN
Solar/Wind Harmer
23.686
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
9.812
270197AD1-017 GEN1
Solar/Wind Harmer
2.546
270336AE1-100 GEN
Solar/Wind Harmer
2.757
943811AF1-049 GEN
Solar/Wind Harmer
5.695
24728305BUCHG2
Adder
6.75
270018AE2-047 C O1
Solar/Wind Harmer
1.826
958131AF2-107 GEN
Solar/Wind Harmer
7.108
24735205WLF2G2
Adder
8.023
971687AH1-348 GEN
Solar/Wind Harmer
1.359
971403AH1-188 GEN
Solar/Wind Harmer
18.852
24723205RIVRG3
Adder
22.954
971315AH1-136 GEN
Solar/Wind Harmer
2.43
24686105CER G3
Adder
9.887
24686505CER G6
Adder
9.874
270331AC1-082 GEN3
Solar/Wind Harmer
0.487
24721705FLATG2
Adder
21.686
970947AG2-589 GEN
Solar/Wind Harmer
2.139
970273AG2-179 GEN
Solar/Wind Harmer
2.581
971821AH1-427 GEN
Solar/Wind Harmer
10.346
964901AG1-354 GEN
Solar/Wind Harmer
15.5
339241AF1-083 GEN
Solar/Wind Harmer
1.715
962241AG1-070 GEN
Solar/Wind Harmer
4.64
960001AF2-291 GEN
Solar/Wind Harmer
3.113
3429241JKCT 3G
Adder
12.029
3429421JKCT 10G
Adder
8.402
971565AH1-281 GEN
Solar/Wind Harmer
2.001
943111AE2-339 GEN
Solar/Wind Harmer
0.883
339216AC1-074 GEN
Solar/Wind Harmer
1.649
945681AF1-233 GEN
Solar/Wind Harmer
18.32
927014AC1-188 GEN
Solar/Wind Harmer
1.532
970091AG2-072 GEN
Adder
74.012
970333AG2-219 GEN
Solar/Wind Harmer
30.05
270445AC2-157 GEN2
Solar/Wind Harmer
5.239
25196808ZIMRHP
Adder
70.616
252507AC2-088 GEN
Solar/Wind Harmer
1.669
25196008MFTGT1
Adder
1.293
25194608D.CRK4
Adder
1.508
965911AG1-460 GEN
Solar/Wind Harmer
1.271
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
946171AF1-282 GEN
Solar/Wind Harmer
9.075
24728605AND G2
Adder
3.48
276615X2-022 GEN
Solar/Wind Harmer
1.772
963831AG1-236 GEN
Solar/Wind Harmer
8.877
274880W4-005 GEN4
Solar/Wind Harmer
2.726
963741AG1-226 GEN
Solar/Wind Harmer
40.366
274761LEE CO EC;2U
Adder
8.222
274766LEE CO EC;7U
Adder
8.125
972235AH1-702 GEN1
Adder
2.22
274822ROCKFORD ;11
Adder
17.275
274828WAUKEGAN ;BP
Adder
9.655
274682WAUKEGAN ;7U
Adder
15.703
274745AC1-111 GEN9
Adder
4.87
315616AA1-038_C
Solar/Wind Helper
3.293
970823AG2-518 GEN
50/50
8.384
247619Y1-049
50/50
0.913
24684705SMG5
50/50
0.856
970481AG2-311 GEN
50/50
11.937
24728405LEESVG
50/50
0.295
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.829
962751AG1-124 GEN
Solar/Wind Harmer
18.825
958121AF2-106 GEN
Solar/Wind Harmer
9.407
270173AC1-122 GEN
Solar/Wind Harmer
3.278
971331AH1-145 GEN
Solar/Wind Harmer
18.361
943031AE2-326 GEN
Solar/Wind Harmer
6.784
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.812
270574AD1-017 GEN2
Solar/Wind Harmer
8.473
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.936
270030AE2-140 GEN
Solar/Wind Harmer
30.929
960911AF2-382 GEN
Solar/Wind Harmer
10.948
270016AE1-250 BESS
Solar/Wind Harmer
3.256
970913AG2-568 GEN
Solar/Wind Harmer
11.004
971461AH1-227 GEN
Solar/Wind Harmer
7.003
970223AG2-152 GEN
Solar/Wind Harmer
17.623
270053AF1-130 C
Solar/Wind Harmer
4.815
972103AH1-617 GEN
Solar/Wind Harmer
25.835
24686205CER G4
Adder
9.835
24686405CER G5
Adder
9.796
972273AH1-721 GEN
Adder
89.316
24721905FLATG4
Adder
21.686
970273AG2-179 GEN
Solar/Wind Harmer
4.123
339250AF1-203 GEN
Solar/Wind Harmer
0.628
971155AH1-034 GEN
Solar/Wind Harmer
10.354
962251AG1-071 GEN
Solar/Wind Harmer
5.671
966571AG1-526 GEN
Solar/Wind Harmer
22.886
970093AG2-073 GEN
Solar/Wind Harmer
10.271
960741AF2-365 GEN
Solar/Wind Harmer
5.107
3429391JKCT 9G
Adder
8.402
971191AH1-055 GEN
Solar/Wind Harmer
22.182
972167AH1-666 GEN
Solar/Wind Harmer
7.768
957541AF2-048 GEN
Solar/Wind Harmer
1.528
958171AF2-111 GEN
Solar/Wind Harmer
23.91
970243AG2-164 GEN
Solar/Wind Harmer
24.587
970519AG2-331 GEN
Solar/Wind Harmer
16.518
970699AG2-449 GEN
Solar/Wind Harmer
10.927
25196008MFTGT1
Adder
1.252
252510AF1-249 C
Solar/Wind Harmer
0.384
25194608D.CRK4
Adder
1.508
25196608WSDLE5
Adder
7.849
970193AG2-126 GEN
Solar/Wind Harmer
13.689
942481AE2-261 GEN
Solar/Wind Harmer
27.229
253316AC1-085 GEN3
Solar/Wind Harmer
7.601
253433AC1-085 GEN1
Solar/Wind Harmer
4.825
946181AF1-283 GEN
Solar/Wind Harmer
11.797
24728705AND G3
Adder
7.277
24728505AND G1
Adder
3.48
276621W2-048 GEN
Solar/Wind Harmer
5.645
276838X2-022 GEN2
Solar/Wind Harmer
0.211
276686W4-005 GEN3
Solar/Wind Harmer
2.726
276668AB2-070 GEN1
Solar/Wind Harmer
2.027
971993AH1-541 GEN
Solar/Wind Harmer
8.328
270356AE2-297 GEN
Solar/Wind Harmer
4.098
253406AD2-031_GEN
Solar/Wind Harmer
1.149
274760LEE CO EC;1U
Adder
8.222
274767LEE CO EC;8U
Adder
8.125
972236AH1-702 GEN2
Adder
1.93
274682WAUKEGAN ;7U
Adder
15.703
274729ELWOOD EC;1P
Adder
13.481
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.838
3147666LOUISA
Solar/Wind Helper
1.088
316254AC1-120 GEN1
Solar/Wind Helper
1.159
316097T157 G90
Solar/Wind Helper
1.125
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316336AC2-165 C
Solar/Wind Helper
1.285
316006AB2-029 C
Solar/Wind Helper
0.112
316045AC1-158 PL2
Solar/Wind Helper
4.023
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.725
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.625
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.386
23583801GRNGAP
Solar/Wind Helper
4.287
316095T157 G97
Solar/Wind Helper
1.125
238147AE2-230_GEN1
Solar/Wind Helper
0.421
238149AF1-291A_GEN
Solar/Wind Helper
0.12
316313AB2-026
Solar/Wind Helper
0.354
316258AE1-075 C
Solar/Wind Helper
0.319
316405AF2-144 C
Solar/Wind Helper
0.265
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.387
316044AC1-158 PL1
Solar/Wind Helper
1.257
316450AC1-158 RIC
Solar/Wind Helper
0.335
972175AH1-670 GEN
Solar/Wind Harmer
4.72
944201AF1-088_MTX
Adder
109.09
957141AF2-008_MTX
Adder
54.545
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.415
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.315
MECLTFEXP_MEC->PJM
CLTF
15.415
SIGELTFEXP_SIGE->PJM
CLTF
0.508
NYPJM->LTFIMP_NY
CLTF
3.248
LGEELTFEXP_LGEE->PJM
CLTF
6.763
WECLTFEXP_WEC->PJM
CLTF
3.371
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
CPLELTFEXP_CPLE->PJM
CLTF
6.226
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.111
LAGNLTFEXP_LAGN->PJM
CLTF
20.28
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.555
TVALTFEXP_TVA->PJM
CLTF
10.606

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.36 %
Rating:3610.0 MVA
Rating Type:B
MVA to Mitigate:4200.43
MW Contribution:11.94
Bus #Bus NameTypeMW Contribution
971543AH1-269 GEN
50/50
12.251
966391AG1-508 GEN
Solar/Wind Harmer
6.377
270069AE2-166 C O1
Solar/Wind Harmer
4.508
971313AH1-133 GEN
Solar/Wind Harmer
15.705
24734705WLF1G3
Adder
8.198
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684405SMG2
50/50
2.225
24684505SMG3
50/50
1.376
24684305SMG1
50/50
0.806
270583AD2-179 GEN
Solar/Wind Harmer
20.728
270214AC2-123 GEN
Solar/Wind Harmer
4.312
971277AH1-098 GEN
Solar/Wind Harmer
7.423
316217AC1-145 GEN
Solar/Wind Harmer
4.248
316197AC1-042 GEN
Solar/Wind Harmer
3.22
942671AE2-283 GEN
Solar/Wind Harmer
8.67
24728205BUCHG1
Adder
6.753
270013AE1-250 PV
Solar/Wind Harmer
3.257
971225AH1-072 GEN
Solar/Wind Harmer
2.732
971227AH1-073 GEN
Solar/Wind Harmer
2.732
944971AF1-162 GEN
Solar/Wind Harmer
9.072
24723005RIVRG1
Adder
22.966
24723105RIVRG2
Adder
22.966
24685805CER G1
Adder
9.828
24685905CER G2
Adder
9.828
942751AE2-291 GEN
Solar/Wind Harmer
10.391
966021AG1-471 GEN
Solar/Wind Harmer
5.756
970823AG2-518 GEN
50/50
8.386
247619Y1-049
50/50
0.913
24684705SMG5
50/50
0.857
970481AG2-311 GEN
50/50
11.941
24728405LEESVG
50/50
0.296
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.847
962751AG1-124 GEN
Solar/Wind Harmer
18.831
958121AF2-106 GEN
Solar/Wind Harmer
9.409
270173AC1-122 GEN
Solar/Wind Harmer
3.279
971331AH1-145 GEN
Solar/Wind Harmer
18.367
943031AE2-326 GEN
Solar/Wind Harmer
6.787
3147312GRETNA
Solar/Wind Harmer
-0.021
3146802CHATHAM
Solar/Wind Harmer
-0.02
941801AE2-185 GEN
Solar/Wind Harmer
9.815
270574AD1-017 GEN2
Solar/Wind Harmer
8.476
3147123OTTER R
Solar/Wind Harmer
-0.014
270346AE1-212 GEN
Solar/Wind Harmer
13.941
270030AE2-140 GEN
Solar/Wind Harmer
30.942
960911AF2-382 GEN
Solar/Wind Harmer
10.952
270016AE1-250 BESS
Solar/Wind Harmer
3.257
970913AG2-568 GEN
Solar/Wind Harmer
11.009
971461AH1-227 GEN
Solar/Wind Harmer
7.007
970223AG2-152 GEN
Solar/Wind Harmer
17.631
270053AF1-130 C
Solar/Wind Harmer
4.818
972103AH1-617 GEN
Solar/Wind Harmer
25.847
24686205CER G4
Adder
9.841
24686405CER G5
Adder
9.802
972273AH1-721 GEN
Adder
89.369
24721905FLATG4
Adder
21.699
970273AG2-179 GEN
Solar/Wind Harmer
4.125
339250AF1-203 GEN
Solar/Wind Harmer
0.628
971155AH1-034 GEN
Solar/Wind Harmer
10.36
962251AG1-071 GEN
Solar/Wind Harmer
5.674
966571AG1-526 GEN
Solar/Wind Harmer
22.9
970093AG2-073 GEN
Solar/Wind Harmer
10.278
960741AF2-365 GEN
Solar/Wind Harmer
5.111
3429391JKCT 9G
Adder
8.407
971191AH1-055 GEN
Solar/Wind Harmer
22.196
972167AH1-666 GEN
Solar/Wind Harmer
7.773
957541AF2-048 GEN
Solar/Wind Harmer
1.529
958171AF2-111 GEN
Solar/Wind Harmer
23.926
970243AG2-164 GEN
Solar/Wind Harmer
24.603
970519AG2-331 GEN
Solar/Wind Harmer
16.529
970699AG2-449 GEN
Solar/Wind Harmer
10.935
25196008MFTGT1
Adder
1.253
252510AF1-249 C
Solar/Wind Harmer
0.385
25194608D.CRK4
Adder
1.509
25196608WSDLE5
Adder
7.855
970193AG2-126 GEN
Solar/Wind Harmer
13.698
942481AE2-261 GEN
Solar/Wind Harmer
27.248
253316AC1-085 GEN3
Solar/Wind Harmer
7.607
253433AC1-085 GEN1
Solar/Wind Harmer
4.829
946181AF1-283 GEN
Solar/Wind Harmer
11.806
24728705AND G3
Adder
7.283
24728505AND G1
Adder
3.482
276621W2-048 GEN
Solar/Wind Harmer
5.649
276838X2-022 GEN2
Solar/Wind Harmer
0.211
276668AB2-070 GEN1
Solar/Wind Harmer
2.029
276686W4-005 GEN3
Solar/Wind Harmer
2.728
971993AH1-541 GEN
Solar/Wind Harmer
8.334
270356AE2-297 GEN
Solar/Wind Harmer
4.101
253406AD2-031_GEN
Solar/Wind Harmer
1.149
274760LEE CO EC;1U
Adder
8.227
274767LEE CO EC;8U
Adder
8.131
972236AH1-702 GEN2
Adder
1.932
274682WAUKEGAN ;7U
Adder
15.715
274729ELWOOD EC;1P
Adder
13.491
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.837
3147666LOUISA
Solar/Wind Helper
1.087
316254AC1-120 GEN1
Solar/Wind Helper
1.158
316097T157 G90
Solar/Wind Helper
1.124
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316336AC2-165 C
Solar/Wind Helper
1.284
316006AB2-029 C
Solar/Wind Helper
0.112
316045AC1-158 PL2
Solar/Wind Helper
4.02
970479AG2-310 GEN
50/50
20.26
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
24684605SMG4
50/50
2.239
966251AG1-494 GEN
50/50
4.39
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
7.005
971329AH1-144 GEN
Solar/Wind Harmer
23.694
3147312GRETNA
Solar/Wind Harmer
-0.005
941821AE2-187 GEN
Solar/Wind Harmer
9.815
270197AD1-017 GEN1
Solar/Wind Harmer
2.547
270336AE1-100 GEN
Solar/Wind Harmer
2.758
943811AF1-049 GEN
Solar/Wind Harmer
5.698
24728305BUCHG2
Adder
6.753
270018AE2-047 C O1
Solar/Wind Harmer
1.826
958131AF2-107 GEN
Solar/Wind Harmer
7.111
24735205WLF2G2
Adder
8.027
971687AH1-348 GEN
Solar/Wind Harmer
1.359
971403AH1-188 GEN
Solar/Wind Harmer
18.861
24723205RIVRG3
Adder
22.966
971315AH1-136 GEN
Solar/Wind Harmer
2.431
24686105CER G3
Adder
9.893
24686505CER G6
Adder
9.88
270331AC1-082 GEN3
Solar/Wind Harmer
0.487
24721705FLATG2
Adder
21.699
970947AG2-589 GEN
Solar/Wind Harmer
2.14
970273AG2-179 GEN
Solar/Wind Harmer
2.583
971821AH1-427 GEN
Solar/Wind Harmer
10.353
964901AG1-354 GEN
Solar/Wind Harmer
15.509
339241AF1-083 GEN
Solar/Wind Harmer
1.716
962241AG1-070 GEN
Solar/Wind Harmer
4.643
960001AF2-291 GEN
Solar/Wind Harmer
3.115
3429241JKCT 3G
Adder
12.037
3429421JKCT 10G
Adder
8.407
971565AH1-281 GEN
Solar/Wind Harmer
2.002
943111AE2-339 GEN
Solar/Wind Harmer
0.883
339216AC1-074 GEN
Solar/Wind Harmer
1.65
945681AF1-233 GEN
Solar/Wind Harmer
18.332
927014AC1-188 GEN
Solar/Wind Harmer
1.533
970091AG2-072 GEN
Adder
74.061
970333AG2-219 GEN
Solar/Wind Harmer
30.071
270445AC2-157 GEN2
Solar/Wind Harmer
5.243
25196808ZIMRHP
Adder
70.665
252507AC2-088 GEN
Solar/Wind Harmer
1.671
25196008MFTGT1
Adder
1.294
25194608D.CRK4
Adder
1.509
965911AG1-460 GEN
Solar/Wind Harmer
1.272
253432AC1-085 GEN2
Solar/Wind Harmer
0.243
946171AF1-282 GEN
Solar/Wind Harmer
9.081
24728605AND G2
Adder
3.482
276615X2-022 GEN
Solar/Wind Harmer
1.774
963831AG1-236 GEN
Solar/Wind Harmer
8.883
274880W4-005 GEN4
Solar/Wind Harmer
2.728
963741AG1-226 GEN
Solar/Wind Harmer
40.395
274761LEE CO EC;2U
Adder
8.227
274766LEE CO EC;7U
Adder
8.131
972235AH1-702 GEN1
Adder
2.221
274822ROCKFORD ;11
Adder
17.288
274828WAUKEGAN ;BP
Adder
9.662
274682WAUKEGAN ;7U
Adder
15.715
274745AC1-111 GEN9
Adder
4.873
315616AA1-038_C
Solar/Wind Helper
3.292
3148013FISHERV
Solar/Wind Helper
0.522
316499AE2-029_GEN
Solar/Wind Helper
1.724
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.625
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.386
23583801GRNGAP
Solar/Wind Helper
4.284
316095T157 G97
Solar/Wind Helper
1.124
238147AE2-230_GEN1
Solar/Wind Helper
0.421
238149AF1-291A_GEN
Solar/Wind Helper
0.12
316313AB2-026
Solar/Wind Helper
0.354
316258AE1-075 C
Solar/Wind Helper
0.318
316405AF2-144 C
Solar/Wind Helper
0.265
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.386
316044AC1-158 PL1
Solar/Wind Helper
1.256
316450AC1-158 RIC
Solar/Wind Helper
0.335
972175AH1-670 GEN
Solar/Wind Harmer
4.723
24734805WLF1G4
Adder
8.198
24734905WLF1G5
Adder
8.198
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.027
270399AC1-101 GEN
Solar/Wind Harmer
5.558
270400AC1-102 GEN
Solar/Wind Harmer
5.558
941621AE2-160 GEN
Adder
4.287
957241AF2-018 GEN
Solar/Wind Harmer
5.759
970281AG2-184 GEN
Solar/Wind Harmer
27.14
972143AH1-644 GEN
Solar/Wind Harmer
12.924
971981AH1-535 GEN
Solar/Wind Harmer
12.569
962211AG1-066 GEN
Solar/Wind Harmer
3.003
971061AG2-657 GEN
Solar/Wind Harmer
10.996
24477305BRIDGE
Adder
0.419
972203AH1-686 GEN
Adder
2.706
270330AC1-082 GEN2
Solar/Wind Harmer
0.824
270329AC1-082 GEN1
Solar/Wind Harmer
0.486
965401AG1-405 GEN
Solar/Wind Harmer
6.063
965411AG1-406 GEN
Solar/Wind Harmer
2.721
339211AE2-254 GEN
Solar/Wind Harmer
1.564
3429211JKCT 2G
Adder
11.881
970455AG2-298 GEN
Solar/Wind Harmer
6.038
339243AC2-075 GEN1
Solar/Wind Harmer
0.447
972163AH1-664 GEN
Solar/Wind Harmer
9.749
972165AH1-665 GEN
Solar/Wind Harmer
7.8
971985AH1-537 GEN
Solar/Wind Harmer
17.306
270367AC2-061_GEN
Solar/Wind Harmer
3.011
316123AC1-075 GEN
Solar/Wind Harmer
1.494
970165AG2-112 GEN
Solar/Wind Harmer
1.315
970163AG2-111 GEN
Solar/Wind Harmer
1.255
25196108MFTGT2
Adder
1.426
25196108MFTGT2
Adder
1.325
970879AG2-548 GEN
Solar/Wind Harmer
3.949
944221AF1-090 GEN
Solar/Wind Harmer
10.031
252524AE2-267 GEN
Solar/Wind Harmer
1.445
25196408WSDLE3
Adder
8.086
25196308WSDLE2
Adder
8.015
25196208WSDLE1
Adder
7.995
25196708WSDLE6
Adder
7.975
25196508WSDLE4
Adder
7.774
276849AB2-070 GEN2
Solar/Wind Harmer
2.029
276848AB2-070 GEN3
Solar/Wind Harmer
2.029
276785W4-005 GEN1
Solar/Wind Harmer
2.728
276174W4-005 GEN2
Solar/Wind Harmer
2.728
274823ROCKFORD ;21
Adder
17.162
274746AC1-111 G10
Adder
4.873
274744AC1-111 GEN8
Adder
4.873
25306009OHH W.
Adder
2.506
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.313
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.078
316164AC1-076 GEN
Solar/Wind Helper
1.171
238152AF2-075_GEN
Solar/Wind Helper
0.601
971485AH1-239 GEN
Solar/Wind Harmer
8.502
339231AF1-038_GEN
Solar/Wind Harmer
1.919
960161AF2-307 GEN
Solar/Wind Harmer
6.662
339255AE2-071 GEN
Solar/Wind Harmer
1.099
964781AG1-341 GEN
Solar/Wind Harmer
10.976
339236AF1-050_GEN
Solar/Wind Harmer
1.873
971081AG2-670 GEN
Solar/Wind Harmer
7.739
942891AE2-308 GEN
Solar/Wind Harmer
10.182
970653AG2-424 GEN
Solar/Wind Harmer
4.883
970653AG2-424 GEN
Solar/Wind Harmer
1.765
964571AG1-320 GEN
Solar/Wind Harmer
8.191
971125AH1-004 GEN
Solar/Wind Harmer
3.983
970107AG2-081 GEN
Solar/Wind Harmer
2.987
972043AH1-570 GEN
Solar/Wind Harmer
2.476
972045AH1-571 GEN
Solar/Wind Harmer
1.981
339221AD2-048_GEN
Solar/Wind Harmer
1.515
970235AG2-159 GEN
Solar/Wind Harmer
3.88
970235AG2-159 GEN
Solar/Wind Harmer
2.369
270186AC1-089 GEN
Solar/Wind Harmer
5.828
970239AG2-162 GEN
Solar/Wind Harmer
10.479
962581AG1-107 GEN
Solar/Wind Harmer
4.734
961491AF2-440 GEN
Solar/Wind Harmer
1.967
270444AC2-157 GEN1
Solar/Wind Harmer
5.243
252509AD1-136 GEN
Solar/Wind Harmer
0.239
25183208HLCRTG
Solar/Wind Harmer
5.586
252519AF1-045_GEN
Solar/Wind Harmer
5.593
252516AE2-318_GEN
Solar/Wind Harmer
4.266
25194408D.CRK1
Adder
6.943
25194508D.CRK3
Adder
1.298
970879AG2-548 GEN
Solar/Wind Harmer
5.66
971073AG2-665 GEN
Solar/Wind Harmer
5.66
971073AG2-665 GEN
Solar/Wind Harmer
3.949
945391AF1-204 GEN
Solar/Wind Harmer
12.727
276916AD2-100_GEN
Solar/Wind Harmer
19.168
276911AD2-131_GEN
Solar/Wind Harmer
3.874
957381AF2-032 GEN
Solar/Wind Harmer
0.381
253317AC1-085 GEN4
Solar/Wind Harmer
7.607
276763AC1-053 GEN1
Solar/Wind Harmer
3.571
276764AC1-053 GEN2
Solar/Wind Harmer
3.571
970241AG2-163 GEN
Solar/Wind Harmer
22.442
24728805RICHG1
Adder
3.386
24728905RICHG2
Adder
3.386
972267AH1-718 GEN
Adder
3.691
274764LEE CO EC;5U
Adder
8.247
274765LEE CO EC;6U
Adder
8.247
274762LEE CO EC;3U
Adder
8.227
274763LEE CO EC;4U
Adder
8.15
274683WAUKEGAN ;8U
Adder
18.432
274683WAUKEGAN ;8U
Adder
15.538
274696ROCKY RD ;4P
Adder
9.964
274695ROCKY RD ;2P
Adder
9.734
274693ROCKY RD ;1P
Adder
9.639
274697ROCKY RD ;3P
Adder
2.644
3132123MT JACKSON
Solar/Wind Helper
1.388
315821AE2-092 GEN
Solar/Wind Helper
3.215
966001AG1-469 GEN
Solar/Wind Helper
0.32
315651AD1-115 GEN
Solar/Wind Helper
0.837
966871AG1-558 GEN
Solar/Wind Helper
0.306
316447AC1-158 HLD
Solar/Wind Helper
2.764
316468AD1-105 GEN
Solar/Wind Helper
1.124
944201AF1-088_MTX
Adder
109.164
957141AF2-008_MTX
Adder
54.582
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.508
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.339
MECLTFEXP_MEC->PJM
CLTF
15.425
SIGELTFEXP_SIGE->PJM
CLTF
0.508
NYPJM->LTFIMP_NY
CLTF
3.243
LGEELTFEXP_LGEE->PJM
CLTF
6.767
WECLTFEXP_WEC->PJM
CLTF
3.374
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
CPLELTFEXP_CPLE->PJM
CLTF
6.233
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.197
LAGNLTFEXP_LAGN->PJM
CLTF
20.293
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.574
TVALTFEXP_TVA->PJM
CLTF
10.613

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o DVP_P4-2: 151T1047_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 151T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.96 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:330.65
MW Contribution:6.75
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.266
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.139
971683AH1-343 GEN
Solar/Wind Harmer
22.238
270197AD1-017 GEN1
Solar/Wind Harmer
1.246
3151561HALLBR1
50/50
1.184
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.484
970481AG2-311 GEN
50/50
6.751
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.139
316003AC1-222 GEN
Solar/Wind Harmer
5.036
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.147
270016AE1-250 BESS
Solar/Wind Harmer
1.342
270173AC1-122 GEN
Solar/Wind Harmer
0.85
970223AG2-152 GEN
Solar/Wind Harmer
6.601
316123AC1-075 GEN
Solar/Wind Harmer
5.564
970865AG2-541 GEN
Solar/Wind Harmer
20.949
970165AG2-112 GEN
Solar/Wind Harmer
4.899
970163AG2-111 GEN
Solar/Wind Harmer
4.673
24684405SMG2
50/50
1.258
24684505SMG3
50/50
0.778
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.716
316197AC1-042 GEN
Solar/Wind Harmer
6.608
942671AE2-283 GEN
Solar/Wind Harmer
17.789
942751AE2-291 GEN
Solar/Wind Harmer
32.874
270013AE1-250 PV
Solar/Wind Harmer
1.342
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.177
NYPJM->LTFIMP_NY
CLTF
0.065
CPLELTFEXP_CPLE->PJM
CLTF
0.484
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.061
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
0.013
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.831
GibsonPJM->LTFIMP_GIBSON
CLTF
0

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o DVP_P4-2: 104702_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104702_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.95 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:330.63
MW Contribution:6.75
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.266
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.139
971683AH1-343 GEN
Solar/Wind Harmer
22.238
270197AD1-017 GEN1
Solar/Wind Harmer
1.246
3151561HALLBR1
50/50
1.184
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.484
970481AG2-311 GEN
50/50
6.751
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.139
316003AC1-222 GEN
Solar/Wind Harmer
5.035
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.147
270016AE1-250 BESS
Solar/Wind Harmer
1.342
270173AC1-122 GEN
Solar/Wind Harmer
0.85
970223AG2-152 GEN
Solar/Wind Harmer
6.6
316123AC1-075 GEN
Solar/Wind Harmer
5.564
970865AG2-541 GEN
Solar/Wind Harmer
20.949
970165AG2-112 GEN
Solar/Wind Harmer
4.899
970163AG2-111 GEN
Solar/Wind Harmer
4.673
24684405SMG2
50/50
1.258
24684505SMG3
50/50
0.778
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.716
316197AC1-042 GEN
Solar/Wind Harmer
6.608
942671AE2-283 GEN
Solar/Wind Harmer
17.789
942751AE2-291 GEN
Solar/Wind Harmer
32.874
270013AE1-250 PV
Solar/Wind Harmer
1.342
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.178
NYPJM->LTFIMP_NY
CLTF
0.065
CPLELTFEXP_CPLE->PJM
CLTF
0.484
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.061
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
0.012
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.829
GibsonPJM->LTFIMP_GIBSON
CLTF
0

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o DVP_P4-2: 1016T1047_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 1016T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.07 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:313.77
MW Contribution:6.76
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.143
971683AH1-343 GEN
Solar/Wind Harmer
22.243
270197AD1-017 GEN1
Solar/Wind Harmer
1.247
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.143
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.151
270016AE1-250 BESS
Solar/Wind Harmer
1.344
270173AC1-122 GEN
Solar/Wind Harmer
0.851
970223AG2-152 GEN
Solar/Wind Harmer
6.611
316123AC1-075 GEN
Solar/Wind Harmer
5.565
970865AG2-541 GEN
Solar/Wind Harmer
20.954
970165AG2-112 GEN
Solar/Wind Harmer
4.9
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.718
316197AC1-042 GEN
Solar/Wind Harmer
6.609
942671AE2-283 GEN
Solar/Wind Harmer
17.793
942751AE2-291 GEN
Solar/Wind Harmer
32.881
270013AE1-250 PV
Solar/Wind Harmer
1.344
970163AG2-111 GEN
Solar/Wind Harmer
4.674
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.153
NYPJM->LTFIMP_NY
CLTF
0.06
CPLELTFEXP_CPLE->PJM
CLTF
0.492
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.029
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o DVP_P4-2: 101672_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 101672_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.05 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:313.73
MW Contribution:6.76
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.143
971683AH1-343 GEN
Solar/Wind Harmer
22.243
270197AD1-017 GEN1
Solar/Wind Harmer
1.247
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.143
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.151
270016AE1-250 BESS
Solar/Wind Harmer
1.344
270173AC1-122 GEN
Solar/Wind Harmer
0.851
970223AG2-152 GEN
Solar/Wind Harmer
6.611
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.718
316197AC1-042 GEN
Solar/Wind Harmer
6.609
942671AE2-283 GEN
Solar/Wind Harmer
17.793
942751AE2-291 GEN
Solar/Wind Harmer
32.881
270013AE1-250 PV
Solar/Wind Harmer
1.344
316123AC1-075 GEN
Solar/Wind Harmer
5.565
970865AG2-541 GEN
Solar/Wind Harmer
20.954
970165AG2-112 GEN
Solar/Wind Harmer
4.9
970163AG2-111 GEN
Solar/Wind Harmer
4.674
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.153
NYPJM->LTFIMP_NY
CLTF
0.06
CPLELTFEXP_CPLE->PJM
CLTF
0.492
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.029
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o DVP_P4-2: 104772_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104772_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.62 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:310.21
MW Contribution:6.76
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.143
971683AH1-343 GEN
Solar/Wind Harmer
22.243
270197AD1-017 GEN1
Solar/Wind Harmer
1.247
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.143
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.151
270016AE1-250 BESS
Solar/Wind Harmer
1.344
270173AC1-122 GEN
Solar/Wind Harmer
0.851
970223AG2-152 GEN
Solar/Wind Harmer
6.611
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.718
316197AC1-042 GEN
Solar/Wind Harmer
6.609
942671AE2-283 GEN
Solar/Wind Harmer
17.793
942751AE2-291 GEN
Solar/Wind Harmer
32.881
270013AE1-250 PV
Solar/Wind Harmer
1.344
316123AC1-075 GEN
Solar/Wind Harmer
5.565
970865AG2-541 GEN
Solar/Wind Harmer
20.954
970165AG2-112 GEN
Solar/Wind Harmer
4.9
970163AG2-111 GEN
Solar/Wind Harmer
4.674
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.153
NYPJM->LTFIMP_NY
CLTF
0.06
CPLELTFEXP_CPLE->PJM
CLTF
0.492
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.029
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 1047_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1047_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.29 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:260.4
MW Contribution:6.75
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.258
24684505SMG3
50/50
0.778
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.266
3147312GRETNA
Solar/Wind Harmer
0.096
941821AE2-187 GEN
Solar/Wind Harmer
15.295
971683AH1-343 GEN
Solar/Wind Harmer
16.89
270197AD1-017 GEN1
Solar/Wind Harmer
0.699
3151561HALLBR1
50/50
1.184
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.484
970481AG2-311 GEN
50/50
6.751
3147312GRETNA
Solar/Wind Harmer
0.382
3146802CHATHAM
Solar/Wind Harmer
0.358
941801AE2-185 GEN
Solar/Wind Harmer
15.295
316003AC1-222 GEN
Solar/Wind Harmer
0.012
3147123OTTER R
Solar/Wind Harmer
0.275
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.002
270173AC1-122 GEN
Solar/Wind Harmer
0.175
970223AG2-152 GEN
Solar/Wind Harmer
4.628
316123AC1-075 GEN
Solar/Wind Harmer
0.627
970865AG2-541 GEN
Solar/Wind Harmer
15.911
970165AG2-112 GEN
Solar/Wind Harmer
3.721
970163AG2-111 GEN
Solar/Wind Harmer
3.549
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
0.006
316197AC1-042 GEN
Solar/Wind Harmer
0.005
942671AE2-283 GEN
Solar/Wind Harmer
11.896
942751AE2-291 GEN
Solar/Wind Harmer
24.967
270013AE1-250 PV
Solar/Wind Harmer
0.002
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.178
NYPJM->LTFIMP_NY
CLTF
0.065
CPLELTFEXP_CPLE->PJM
CLTF
0.484
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.061
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
0.012
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.829
GibsonPJM->LTFIMP_GIBSON
CLTF
0

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 1016_SRT-A-1


Base Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1016_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.51 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:248.71
MW Contribution:6.76
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
0.096
941821AE2-187 GEN
Solar/Wind Harmer
15.299
971683AH1-343 GEN
Solar/Wind Harmer
16.893
270197AD1-017 GEN1
Solar/Wind Harmer
0.7
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
0.382
3146802CHATHAM
Solar/Wind Harmer
0.358
941801AE2-185 GEN
Solar/Wind Harmer
15.299
3147123OTTER R
Solar/Wind Harmer
0.275
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.002
270173AC1-122 GEN
Solar/Wind Harmer
0.176
970223AG2-152 GEN
Solar/Wind Harmer
4.636
316123AC1-075 GEN
Solar/Wind Harmer
0.628
970865AG2-541 GEN
Solar/Wind Harmer
15.914
970165AG2-112 GEN
Solar/Wind Harmer
3.721
970163AG2-111 GEN
Solar/Wind Harmer
3.55
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
0.006
316197AC1-042 GEN
Solar/Wind Harmer
0.005
942671AE2-283 GEN
Solar/Wind Harmer
11.899
942751AE2-291 GEN
Solar/Wind Harmer
24.973
270013AE1-250 PV
Solar/Wind Harmer
0.002
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.154
NYPJM->LTFIMP_NY
CLTF
0.06
CPLELTFEXP_CPLE->PJM
CLTF
0.492
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.028
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.25 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:245.61
MW Contribution:6.43
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.32
24684605SMG4
50/50
1.206
3147312GRETNA
Solar/Wind Harmer
-0.009
941821AE2-187 GEN
Solar/Wind Harmer
16.868
270197AD1-017 GEN1
Solar/Wind Harmer
1.62
971683AH1-343 GEN
Solar/Wind Harmer
5.942
316248AF1-058 C
Solar/Wind Harmer
0.225
960061AF2-297 GEN
Solar/Wind Harmer
3.734
3151561HALLBR1
50/50
0.931
24728405LEESVG
50/50
0.319
24684705SMG5
50/50
0.461
970481AG2-311 GEN
50/50
6.43
3147312GRETNA
Solar/Wind Harmer
-0.036
3146802CHATHAM
Solar/Wind Harmer
-0.034
941801AE2-185 GEN
Solar/Wind Harmer
16.868
3147123OTTER R
Solar/Wind Harmer
-0.024
270574AD1-017 GEN2
Solar/Wind Harmer
5.39
270016AE1-250 BESS
Solar/Wind Harmer
2.392
970223AG2-152 GEN
Solar/Wind Harmer
13.798
316003AC1-222 GEN
Solar/Wind Harmer
1.06
270173AC1-122 GEN
Solar/Wind Harmer
0.706
316123AC1-075 GEN
Solar/Wind Harmer
2.482
970165AG2-112 GEN
Solar/Wind Harmer
2.186
970163AG2-111 GEN
Solar/Wind Harmer
2.085
970865AG2-541 GEN
Solar/Wind Harmer
6.833
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.005
316118AC1-105 GEN
Solar/Wind Harmer
0.454
24684405SMG2
50/50
1.198
24684505SMG3
50/50
0.741
24684305SMG1
50/50
0.434
316217AC1-145 GEN
Solar/Wind Harmer
7.301
316197AC1-042 GEN
Solar/Wind Harmer
5.534
942671AE2-283 GEN
Solar/Wind Harmer
14.9
942751AE2-291 GEN
Solar/Wind Harmer
17.168
270013AE1-250 PV
Solar/Wind Harmer
2.392
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.539
NYPJM->LTFIMP_NY
CLTF
0.033
CPLELTFEXP_CPLE->PJM
CLTF
0.729
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.153
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.471
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.072
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line l/o AEP_P7-1_#10778___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10778___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.25 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:245.6
MW Contribution:6.43
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.32
24684605SMG4
50/50
1.206
3147312GRETNA
Solar/Wind Harmer
-0.009
941821AE2-187 GEN
Solar/Wind Harmer
16.868
270197AD1-017 GEN1
Solar/Wind Harmer
1.62
971683AH1-343 GEN
Solar/Wind Harmer
5.942
316248AF1-058 C
Solar/Wind Harmer
0.225
960061AF2-297 GEN
Solar/Wind Harmer
3.734
3151561HALLBR1
50/50
0.931
24728405LEESVG
50/50
0.319
24684705SMG5
50/50
0.461
970481AG2-311 GEN
50/50
6.43
3147312GRETNA
Solar/Wind Harmer
-0.036
3146802CHATHAM
Solar/Wind Harmer
-0.034
941801AE2-185 GEN
Solar/Wind Harmer
16.868
3147123OTTER R
Solar/Wind Harmer
-0.024
270574AD1-017 GEN2
Solar/Wind Harmer
5.39
270016AE1-250 BESS
Solar/Wind Harmer
2.392
970223AG2-152 GEN
Solar/Wind Harmer
13.798
316003AC1-222 GEN
Solar/Wind Harmer
1.06
270173AC1-122 GEN
Solar/Wind Harmer
0.706
316123AC1-075 GEN
Solar/Wind Harmer
2.482
970165AG2-112 GEN
Solar/Wind Harmer
2.186
970163AG2-111 GEN
Solar/Wind Harmer
2.085
970865AG2-541 GEN
Solar/Wind Harmer
6.833
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.005
316118AC1-105 GEN
Solar/Wind Harmer
0.454
24684405SMG2
50/50
1.198
24684505SMG3
50/50
0.741
24684305SMG1
50/50
0.434
316217AC1-145 GEN
Solar/Wind Harmer
7.301
316197AC1-042 GEN
Solar/Wind Harmer
5.534
942671AE2-283 GEN
Solar/Wind Harmer
14.9
942751AE2-291 GEN
Solar/Wind Harmer
17.168
270013AE1-250 PV
Solar/Wind Harmer
2.392
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.539
NYPJM->LTFIMP_NY
CLTF
0.033
CPLELTFEXP_CPLE->PJM
CLTF
0.729
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.153
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.471
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.072
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.66 %
Rating:192.7 MVA
Rating Type:A
MVA to Mitigate:228.66
MW Contribution:10.45
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.551
24684605SMG4
50/50
1.96
270197AD1-017 GEN1
Solar/Wind Harmer
1.068
3147312GRETNA
Solar/Wind Helper
0.167
316248AF1-058 C
Solar/Wind Helper
0.17
24684405SMG2
50/50
1.947
24684505SMG3
50/50
1.204
24684305SMG1
50/50
0.706
270013AE1-250 PV
Solar/Wind Harmer
0.004
316197AC1-042 GEN
Solar/Wind Helper
0.783
316123AC1-075 GEN
Solar/Wind Helper
2.591
3147173SINAI
Solar/Wind Helper
0.126
3147243WELCO
Solar/Wind Helper
0.079
24728405LEESVG
50/50
0.549
24684705SMG5
50/50
0.75
970481AG2-311 GEN
50/50
10.451
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270173AC1-122 GEN
Solar/Wind Harmer
0.32
270016AE1-250 BESS
Solar/Wind Harmer
0.004
970223AG2-152 GEN
Solar/Wind Harmer
6.853
3147312GRETNA
Solar/Wind Helper
0.668
3146802CHATHAM
Solar/Wind Helper
0.626
3147123OTTER R
Solar/Wind Helper
0.448
316003AC1-222 GEN
Solar/Wind Helper
0.83
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.65
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.52
MECLTFEXP_MEC->PJM
CLTF
0.207
SIGELTFEXP_SIGE->PJM
CLTF
0.007
NYPJM->LTFIMP_NY
CLTF
0.068
LGEELTFEXP_LGEE->PJM
CLTF
0.091
WECLTFEXP_WEC->PJM
CLTF
0.046
CPLELTFEXP_CPLE->PJM
CLTF
0.047
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.737
LAGNLTFEXP_LAGN->PJM
CLTF
0.265
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.314
TVALTFEXP_TVA->PJM
CLTF
0.14

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#10162_05EDAN 1 138_P_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.03 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:332.36
MW Contribution:13.87
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.619
24684605SMG4
50/50
2.601
270197AD1-017 GEN1
Solar/Wind Harmer
3.493
3147312GRETNA
Solar/Wind Helper
0.151
316248AF1-058 C
Solar/Wind Helper
0.182
24684405SMG2
50/50
2.584
24684505SMG3
50/50
1.598
24684305SMG1
50/50
0.937
270013AE1-250 PV
Solar/Wind Harmer
5.16
316197AC1-042 GEN
Solar/Wind Helper
0.711
24728405LEESVG
50/50
0.617
24684705SMG5
50/50
0.995
970481AG2-311 GEN
50/50
13.869
270574AD1-017 GEN2
Solar/Wind Harmer
11.625
270016AE1-250 BESS
Solar/Wind Harmer
5.16
970223AG2-152 GEN
Solar/Wind Harmer
29.761
270173AC1-122 GEN
Solar/Wind Harmer
2.227
3147312GRETNA
Solar/Wind Helper
0.606
3146802CHATHAM
Solar/Wind Helper
0.568
3147123OTTER R
Solar/Wind Helper
0.407
316003AC1-222 GEN
Solar/Wind Helper
0.836
316123AC1-075 GEN
Solar/Wind Helper
2.422
3147173SINAI
Solar/Wind Helper
0.136
3147243WELCO
Solar/Wind Helper
0.085
316118AC1-105 GEN
Solar/Wind Helper
0.472
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.176
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.725
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.075
MECLTFEXP_MEC->PJM
CLTF
0.162
SIGELTFEXP_SIGE->PJM
CLTF
0.007
NYPJM->LTFIMP_NY
CLTF
0.09
LGEELTFEXP_LGEE->PJM
CLTF
0.102
WECLTFEXP_WEC->PJM
CLTF
0.047
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.462
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.53
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.49 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:330.82
MW Contribution:13.82
Bus #Bus NameTypeMW Contribution
316123AC1-075 GEN
Solar/Wind Helper
2.409
3147173SINAI
Solar/Wind Helper
0.131
3147243WELCO
Solar/Wind Helper
0.082
316118AC1-105 GEN
Solar/Wind Helper
0.455
24684405SMG2
50/50
2.574
24684505SMG3
50/50
1.592
24684305SMG1
50/50
0.933
270013AE1-250 PV
Solar/Wind Harmer
5.141
316197AC1-042 GEN
Solar/Wind Helper
0.712
24728405LEESVG
50/50
0.616
24684705SMG5
50/50
0.991
970481AG2-311 GEN
50/50
13.817
270574AD1-017 GEN2
Solar/Wind Harmer
11.581
270016AE1-250 BESS
Solar/Wind Harmer
5.141
970223AG2-152 GEN
Solar/Wind Harmer
29.649
270173AC1-122 GEN
Solar/Wind Harmer
2.215
3147312GRETNA
Solar/Wind Helper
0.607
3146802CHATHAM
Solar/Wind Helper
0.569
3147123OTTER R
Solar/Wind Helper
0.407
316003AC1-222 GEN
Solar/Wind Helper
0.819
24728405LEESVG
50/50
0.619
24684605SMG4
50/50
2.591
270197AD1-017 GEN1
Solar/Wind Harmer
3.48
3147312GRETNA
Solar/Wind Helper
0.152
316248AF1-058 C
Solar/Wind Helper
0.177
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.414
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.075
MECLTFEXP_MEC->PJM
CLTF
0.135
SIGELTFEXP_SIGE->PJM
CLTF
0.005
NYPJM->LTFIMP_NY
CLTF
0.085
LGEELTFEXP_LGEE->PJM
CLTF
0.084
WECLTFEXP_WEC->PJM
CLTF
0.038
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.368
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.474
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:115.7 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:328.58
MW Contribution:13.82
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
2.574
24684505SMG3
50/50
1.592
24684305SMG1
50/50
0.933
270013AE1-250 PV
Solar/Wind Harmer
5.141
316197AC1-042 GEN
Solar/Wind Helper
0.712
24728405LEESVG
50/50
0.616
24684705SMG5
50/50
0.991
970481AG2-311 GEN
50/50
13.817
270574AD1-017 GEN2
Solar/Wind Harmer
11.581
270016AE1-250 BESS
Solar/Wind Harmer
5.141
970223AG2-152 GEN
Solar/Wind Harmer
29.649
270173AC1-122 GEN
Solar/Wind Harmer
2.215
3147312GRETNA
Solar/Wind Helper
0.607
3146802CHATHAM
Solar/Wind Helper
0.569
3147123OTTER R
Solar/Wind Helper
0.407
316003AC1-222 GEN
Solar/Wind Helper
0.819
316123AC1-075 GEN
Solar/Wind Helper
2.409
3147173SINAI
Solar/Wind Helper
0.131
3147243WELCO
Solar/Wind Helper
0.082
316118AC1-105 GEN
Solar/Wind Helper
0.455
24728405LEESVG
50/50
0.619
24684605SMG4
50/50
2.591
270197AD1-017 GEN1
Solar/Wind Harmer
3.48
3147312GRETNA
Solar/Wind Helper
0.152
316248AF1-058 C
Solar/Wind Helper
0.177
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.414
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.075
MECLTFEXP_MEC->PJM
CLTF
0.135
SIGELTFEXP_SIGE->PJM
CLTF
0.005
NYPJM->LTFIMP_NY
CLTF
0.085
LGEELTFEXP_LGEE->PJM
CLTF
0.084
WECLTFEXP_WEC->PJM
CLTF
0.038
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.368
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.474
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P7-1_#10778___SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10778___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:115.69 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:328.56
MW Contribution:13.82
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.619
24684605SMG4
50/50
2.591
270197AD1-017 GEN1
Solar/Wind Harmer
3.48
3147312GRETNA
Solar/Wind Helper
0.152
316248AF1-058 C
Solar/Wind Helper
0.177
24728405LEESVG
50/50
0.616
24684705SMG5
50/50
0.991
970481AG2-311 GEN
50/50
13.817
270574AD1-017 GEN2
Solar/Wind Harmer
11.582
270016AE1-250 BESS
Solar/Wind Harmer
5.141
970223AG2-152 GEN
Solar/Wind Harmer
29.65
270173AC1-122 GEN
Solar/Wind Harmer
2.215
3147312GRETNA
Solar/Wind Helper
0.607
3146802CHATHAM
Solar/Wind Helper
0.569
3147123OTTER R
Solar/Wind Helper
0.407
316003AC1-222 GEN
Solar/Wind Helper
0.819
316123AC1-075 GEN
Solar/Wind Helper
2.409
3147173SINAI
Solar/Wind Helper
0.131
3147243WELCO
Solar/Wind Helper
0.082
316118AC1-105 GEN
Solar/Wind Helper
0.455
24684405SMG2
50/50
2.574
24684505SMG3
50/50
1.592
24684305SMG1
50/50
0.933
270013AE1-250 PV
Solar/Wind Harmer
5.141
316197AC1-042 GEN
Solar/Wind Helper
0.712
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.414
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.075
MECLTFEXP_MEC->PJM
CLTF
0.135
SIGELTFEXP_SIGE->PJM
CLTF
0.005
NYPJM->LTFIMP_NY
CLTF
0.085
LGEELTFEXP_LGEE->PJM
CLTF
0.084
WECLTFEXP_WEC->PJM
CLTF
0.038
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.368
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.474
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#10687_05EDAN 2 138_N_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10687_05EDAN 2 138_N_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.68 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:328.54
MW Contribution:13.82
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.616
24684705SMG5
50/50
0.991
970481AG2-311 GEN
50/50
13.817
270574AD1-017 GEN2
Solar/Wind Harmer
11.582
270016AE1-250 BESS
Solar/Wind Harmer
5.141
970223AG2-152 GEN
Solar/Wind Harmer
29.65
270173AC1-122 GEN
Solar/Wind Harmer
2.215
3147312GRETNA
Solar/Wind Helper
0.607
3146802CHATHAM
Solar/Wind Helper
0.569
3147123OTTER R
Solar/Wind Helper
0.407
316003AC1-222 GEN
Solar/Wind Helper
0.819
24728405LEESVG
50/50
0.619
24684605SMG4
50/50
2.591
270197AD1-017 GEN1
Solar/Wind Harmer
3.48
3147312GRETNA
Solar/Wind Helper
0.152
316123AC1-075 GEN
Solar/Wind Helper
2.409
3147173SINAI
Solar/Wind Helper
0.131
3147243WELCO
Solar/Wind Helper
0.082
316118AC1-105 GEN
Solar/Wind Helper
0.455
24684405SMG2
50/50
2.574
24684505SMG3
50/50
1.592
24684305SMG1
50/50
0.933
270013AE1-250 PV
Solar/Wind Harmer
5.141
316197AC1-042 GEN
Solar/Wind Helper
0.712
316248AF1-058 C
Solar/Wind Helper
0.177
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.414
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.075
MECLTFEXP_MEC->PJM
CLTF
0.135
SIGELTFEXP_SIGE->PJM
CLTF
0.005
NYPJM->LTFIMP_NY
CLTF
0.085
LGEELTFEXP_LGEE->PJM
CLTF
0.084
WECLTFEXP_WEC->PJM
CLTF
0.038
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.368
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.474
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#8676_05EDANV2 230_S_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8676_05EDANV2 230_S_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.67 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:328.5
MW Contribution:13.82
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.616
24684705SMG5
50/50
0.991
970481AG2-311 GEN
50/50
13.817
270574AD1-017 GEN2
Solar/Wind Harmer
11.581
270016AE1-250 BESS
Solar/Wind Harmer
5.141
970223AG2-152 GEN
Solar/Wind Harmer
29.649
270173AC1-122 GEN
Solar/Wind Harmer
2.215
3147312GRETNA
Solar/Wind Helper
0.607
3146802CHATHAM
Solar/Wind Helper
0.569
3147123OTTER R
Solar/Wind Helper
0.407
316003AC1-222 GEN
Solar/Wind Helper
0.819
316123AC1-075 GEN
Solar/Wind Helper
2.409
3147173SINAI
Solar/Wind Helper
0.131
3147243WELCO
Solar/Wind Helper
0.082
316118AC1-105 GEN
Solar/Wind Helper
0.455
24684405SMG2
50/50
2.574
24684505SMG3
50/50
1.592
24684305SMG1
50/50
0.933
270013AE1-250 PV
Solar/Wind Harmer
5.141
316197AC1-042 GEN
Solar/Wind Helper
0.712
24728405LEESVG
50/50
0.619
24684605SMG4
50/50
2.591
270197AD1-017 GEN1
Solar/Wind Harmer
3.48
3147312GRETNA
Solar/Wind Helper
0.152
316248AF1-058 C
Solar/Wind Helper
0.177
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.414
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.075
MECLTFEXP_MEC->PJM
CLTF
0.135
SIGELTFEXP_SIGE->PJM
CLTF
0.005
NYPJM->LTFIMP_NY
CLTF
0.085
LGEELTFEXP_LGEE->PJM
CLTF
0.084
WECLTFEXP_WEC->PJM
CLTF
0.038
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.368
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.474
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P1-2_#5366_SRT-A-1


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#5366_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.86 %
Rating:266.96 MVA
Rating Type:B
MVA to Mitigate:295.95
MW Contribution:13.81
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.618
24684605SMG4
50/50
2.589
270197AD1-017 GEN1
Solar/Wind Harmer
1.952
3147312GRETNA
Solar/Wind Helper
0.152
316248AF1-058 C
Solar/Wind Helper
0.175
24684405SMG2
50/50
2.572
24684505SMG3
50/50
1.591
24684305SMG1
50/50
0.933
270013AE1-250 PV
Solar/Wind Harmer
0.009
316197AC1-042 GEN
Solar/Wind Helper
0.712
316123AC1-075 GEN
Solar/Wind Helper
2.407
3147173SINAI
Solar/Wind Helper
0.13
3147243WELCO
Solar/Wind Helper
0.082
316118AC1-105 GEN
Solar/Wind Helper
0.452
24728405LEESVG
50/50
0.616
24684705SMG5
50/50
0.991
970481AG2-311 GEN
50/50
13.806
270574AD1-017 GEN2
Solar/Wind Harmer
0.002
270016AE1-250 BESS
Solar/Wind Harmer
0.009
970223AG2-152 GEN
Solar/Wind Harmer
20.775
270173AC1-122 GEN
Solar/Wind Harmer
0.457
3147312GRETNA
Solar/Wind Helper
0.607
3146802CHATHAM
Solar/Wind Helper
0.569
3147123OTTER R
Solar/Wind Helper
0.407
316003AC1-222 GEN
Solar/Wind Helper
0.816
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.131
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.352
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.076
MECLTFEXP_MEC->PJM
CLTF
0.129
SIGELTFEXP_SIGE->PJM
CLTF
0.005
NYPJM->LTFIMP_NY
CLTF
0.084
LGEELTFEXP_LGEE->PJM
CLTF
0.081
WECLTFEXP_WEC->PJM
CLTF
0.037
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.349
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.464
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P1-3_#10688_05EDANV2 230_4_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-3_#10688_05EDANV2 230_4_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.35 %
Rating:266.96 MVA
Rating Type:B
MVA to Mitigate:294.6
MW Contribution:13.82
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.619
24684605SMG4
50/50
2.591
270197AD1-017 GEN1
Solar/Wind Harmer
1.954
3147312GRETNA
Solar/Wind Helper
0.152
316248AF1-058 C
Solar/Wind Helper
0.177
24684405SMG2
50/50
2.574
24684505SMG3
50/50
1.592
24684305SMG1
50/50
0.933
270013AE1-250 PV
Solar/Wind Harmer
0.009
316197AC1-042 GEN
Solar/Wind Helper
0.712
316123AC1-075 GEN
Solar/Wind Helper
2.409
3147173SINAI
Solar/Wind Helper
0.131
3147243WELCO
Solar/Wind Helper
0.082
316118AC1-105 GEN
Solar/Wind Helper
0.455
24728405LEESVG
50/50
0.616
24684705SMG5
50/50
0.991
970481AG2-311 GEN
50/50
13.817
270574AD1-017 GEN2
Solar/Wind Harmer
0.002
270016AE1-250 BESS
Solar/Wind Harmer
0.009
970223AG2-152 GEN
Solar/Wind Harmer
20.791
270173AC1-122 GEN
Solar/Wind Harmer
0.457
3147312GRETNA
Solar/Wind Helper
0.607
3146802CHATHAM
Solar/Wind Helper
0.569
3147123OTTER R
Solar/Wind Helper
0.407
316003AC1-222 GEN
Solar/Wind Helper
0.819
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.414
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.075
MECLTFEXP_MEC->PJM
CLTF
0.135
SIGELTFEXP_SIGE->PJM
CLTF
0.005
NYPJM->LTFIMP_NY
CLTF
0.085
LGEELTFEXP_LGEE->PJM
CLTF
0.084
WECLTFEXP_WEC->PJM
CLTF
0.038
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.368
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.474
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for [AG2-311] 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.65 %
Rating:192.7 MVA
Rating Type:A
MVA to Mitigate:205.51
MW Contribution:14.93
IPD Plant:AG2-311
Bus #Bus NameTypeMW Contribution
970481AG2-311 GEN
PJM_IPD
14.93

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#10213_05CLOVRD 138_A_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10213_05CLOVRD 138_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.32 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:301.96
MW Contribution:14.26
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.624
24684705SMG5
50/50
1.023
970481AG2-311 GEN
50/50
14.263
270574AD1-017 GEN2
Solar/Wind Harmer
8.687
270173AC1-122 GEN
Solar/Wind Harmer
2.265
270016AE1-250 BESS
Solar/Wind Harmer
2.778
970223AG2-152 GEN
Solar/Wind Harmer
13.563
3147312GRETNA
Solar/Wind Helper
0.601
3146802CHATHAM
Solar/Wind Helper
0.564
3147123OTTER R
Solar/Wind Helper
0.402
316003AC1-222 GEN
Solar/Wind Helper
0.716
24728405LEESVG
50/50
0.627
24684605SMG4
50/50
2.675
270197AD1-017 GEN1
Solar/Wind Harmer
2.61
3147312GRETNA
Solar/Wind Helper
0.15
24684405SMG2
50/50
2.657
24684505SMG3
50/50
1.644
24684305SMG1
50/50
0.963
270013AE1-250 PV
Solar/Wind Harmer
2.778
316197AC1-042 GEN
Solar/Wind Helper
0.705
316123AC1-075 GEN
Solar/Wind Helper
2.304
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.842
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.522
MECLTFEXP_MEC->PJM
CLTF
0.138
SIGELTFEXP_SIGE->PJM
CLTF
0.004
NYPJM->LTFIMP_NY
CLTF
0.088
LGEELTFEXP_LGEE->PJM
CLTF
0.05
WECLTFEXP_WEC->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
0.438
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.568
LAGNLTFEXP_LAGN->PJM
CLTF
0.303
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.003
TVALTFEXP_TVA->PJM
CLTF
0.153

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P7-1_#10781___SRT-A-1


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10781___SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.01 %
Rating:284.0 MVA
Rating Type:B
MVA to Mitigate:284.01
MW Contribution:11.5
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.572
24684605SMG4
50/50
2.158
270197AD1-017 GEN1
Solar/Wind Harmer
2.352
270018AE2-047 C O1
Solar/Wind Harmer
0.617
943811AF1-049 GEN
Solar/Wind Harmer
1.677
3147312GRETNA
Solar/Wind Helper
0.162
316248AF1-058 C
Solar/Wind Helper
0.195
24728405LEESVG
50/50
0.569
24684705SMG5
50/50
0.825
970481AG2-311 GEN
50/50
11.504
270574AD1-017 GEN2
Solar/Wind Harmer
7.826
270016AE1-250 BESS
Solar/Wind Harmer
2.875
970223AG2-152 GEN
Solar/Wind Harmer
15.211
270173AC1-122 GEN
Solar/Wind Harmer
1.769
3147312GRETNA
Solar/Wind Helper
0.65
3146802CHATHAM
Solar/Wind Helper
0.609
3147123OTTER R
Solar/Wind Helper
0.437
316003AC1-222 GEN
Solar/Wind Helper
0.895
316123AC1-075 GEN
Solar/Wind Helper
2.596
3147173SINAI
Solar/Wind Helper
0.145
3147243WELCO
Solar/Wind Helper
0.091
316118AC1-105 GEN
Solar/Wind Helper
0.504
24684405SMG2
50/50
2.143
24684505SMG3
50/50
1.326
24684305SMG1
50/50
0.777
270013AE1-250 PV
Solar/Wind Harmer
2.875
316197AC1-042 GEN
Solar/Wind Helper
0.762
3146843MT LREL
Solar/Wind Helper
0.114
3146843MT LREL
Solar/Wind Helper
0.114
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.149
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.826
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.405
MECLTFEXP_MEC->PJM
CLTF
0.296
SIGELTFEXP_SIGE->PJM
CLTF
0.011
NYPJM->LTFIMP_NY
CLTF
0.092
LGEELTFEXP_LGEE->PJM
CLTF
0.16
WECLTFEXP_WEC->PJM
CLTF
0.077
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.442
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.64
LAGNLTFEXP_LAGN->PJM
CLTF
0.11
TVALTFEXP_TVA->PJM
CLTF
0.08

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o DVP_P4-2: 151T1047_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 151T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:136.34 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:334.02
MW Contribution:6.75
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.266
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.139
971683AH1-343 GEN
Solar/Wind Harmer
22.238
270197AD1-017 GEN1
Solar/Wind Harmer
1.246
3151561HALLBR1
50/50
1.184
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.484
970481AG2-311 GEN
50/50
6.751
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.139
316003AC1-222 GEN
Solar/Wind Harmer
5.036
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.147
270016AE1-250 BESS
Solar/Wind Harmer
1.342
270173AC1-122 GEN
Solar/Wind Harmer
0.85
970223AG2-152 GEN
Solar/Wind Harmer
6.601
316123AC1-075 GEN
Solar/Wind Harmer
5.564
970865AG2-541 GEN
Solar/Wind Harmer
20.949
970165AG2-112 GEN
Solar/Wind Harmer
4.899
970163AG2-111 GEN
Solar/Wind Harmer
4.673
24684405SMG2
50/50
1.258
24684505SMG3
50/50
0.778
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.716
316197AC1-042 GEN
Solar/Wind Harmer
6.608
942671AE2-283 GEN
Solar/Wind Harmer
17.789
942751AE2-291 GEN
Solar/Wind Harmer
32.874
270013AE1-250 PV
Solar/Wind Harmer
1.342
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.177
NYPJM->LTFIMP_NY
CLTF
0.065
CPLELTFEXP_CPLE->PJM
CLTF
0.484
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.061
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
0.013
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.831
GibsonPJM->LTFIMP_GIBSON
CLTF
0

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o DVP_P4-2: 104702_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104702_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:136.33 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:334.0
MW Contribution:6.75
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.266
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.139
971683AH1-343 GEN
Solar/Wind Harmer
22.238
270197AD1-017 GEN1
Solar/Wind Harmer
1.246
3151561HALLBR1
50/50
1.184
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.484
970481AG2-311 GEN
50/50
6.751
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.139
316003AC1-222 GEN
Solar/Wind Harmer
5.035
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.147
270016AE1-250 BESS
Solar/Wind Harmer
1.342
270173AC1-122 GEN
Solar/Wind Harmer
0.85
970223AG2-152 GEN
Solar/Wind Harmer
6.6
316123AC1-075 GEN
Solar/Wind Harmer
5.564
970865AG2-541 GEN
Solar/Wind Harmer
20.949
970165AG2-112 GEN
Solar/Wind Harmer
4.899
970163AG2-111 GEN
Solar/Wind Harmer
4.673
24684405SMG2
50/50
1.258
24684505SMG3
50/50
0.778
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.716
316197AC1-042 GEN
Solar/Wind Harmer
6.608
942671AE2-283 GEN
Solar/Wind Harmer
17.789
942751AE2-291 GEN
Solar/Wind Harmer
32.874
270013AE1-250 PV
Solar/Wind Harmer
1.342
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.178
NYPJM->LTFIMP_NY
CLTF
0.065
CPLELTFEXP_CPLE->PJM
CLTF
0.484
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.061
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
0.012
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.829
GibsonPJM->LTFIMP_GIBSON
CLTF
0

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o DVP_P4-2: 1016T1047_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 1016T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:129.43 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:317.11
MW Contribution:6.76
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.143
971683AH1-343 GEN
Solar/Wind Harmer
22.243
270197AD1-017 GEN1
Solar/Wind Harmer
1.247
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.143
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.151
270016AE1-250 BESS
Solar/Wind Harmer
1.344
270173AC1-122 GEN
Solar/Wind Harmer
0.851
970223AG2-152 GEN
Solar/Wind Harmer
6.611
316123AC1-075 GEN
Solar/Wind Harmer
5.565
970865AG2-541 GEN
Solar/Wind Harmer
20.954
970165AG2-112 GEN
Solar/Wind Harmer
4.9
970163AG2-111 GEN
Solar/Wind Harmer
4.674
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.718
316197AC1-042 GEN
Solar/Wind Harmer
6.609
942671AE2-283 GEN
Solar/Wind Harmer
17.793
942751AE2-291 GEN
Solar/Wind Harmer
32.881
270013AE1-250 PV
Solar/Wind Harmer
1.344
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.153
NYPJM->LTFIMP_NY
CLTF
0.06
CPLELTFEXP_CPLE->PJM
CLTF
0.492
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.029
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o DVP_P4-2: 101672_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 101672_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:129.42 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:317.07
MW Contribution:6.76
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.143
971683AH1-343 GEN
Solar/Wind Harmer
22.243
270197AD1-017 GEN1
Solar/Wind Harmer
1.247
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.143
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.151
270016AE1-250 BESS
Solar/Wind Harmer
1.344
270173AC1-122 GEN
Solar/Wind Harmer
0.851
970223AG2-152 GEN
Solar/Wind Harmer
6.611
316123AC1-075 GEN
Solar/Wind Harmer
5.565
970865AG2-541 GEN
Solar/Wind Harmer
20.954
970165AG2-112 GEN
Solar/Wind Harmer
4.9
970163AG2-111 GEN
Solar/Wind Harmer
4.674
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.718
316197AC1-042 GEN
Solar/Wind Harmer
6.609
942671AE2-283 GEN
Solar/Wind Harmer
17.793
942751AE2-291 GEN
Solar/Wind Harmer
32.881
270013AE1-250 PV
Solar/Wind Harmer
1.344
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.153
NYPJM->LTFIMP_NY
CLTF
0.06
CPLELTFEXP_CPLE->PJM
CLTF
0.492
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.029
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o DVP_P4-2: 104772_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104772_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.97 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:313.53
MW Contribution:6.76
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.143
971683AH1-343 GEN
Solar/Wind Harmer
22.243
270197AD1-017 GEN1
Solar/Wind Harmer
1.247
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.143
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.151
270016AE1-250 BESS
Solar/Wind Harmer
1.344
270173AC1-122 GEN
Solar/Wind Harmer
0.851
970223AG2-152 GEN
Solar/Wind Harmer
6.611
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.718
316197AC1-042 GEN
Solar/Wind Harmer
6.609
942671AE2-283 GEN
Solar/Wind Harmer
17.793
942751AE2-291 GEN
Solar/Wind Harmer
32.881
270013AE1-250 PV
Solar/Wind Harmer
1.344
316123AC1-075 GEN
Solar/Wind Harmer
5.565
970865AG2-541 GEN
Solar/Wind Harmer
20.954
970165AG2-112 GEN
Solar/Wind Harmer
4.9
970163AG2-111 GEN
Solar/Wind Harmer
4.674
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.153
NYPJM->LTFIMP_NY
CLTF
0.06
CPLELTFEXP_CPLE->PJM
CLTF
0.492
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.029
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 1047_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1047_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.67 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:263.78
MW Contribution:6.75
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.258
24684505SMG3
50/50
0.778
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
0.006
316197AC1-042 GEN
Solar/Wind Harmer
0.005
942671AE2-283 GEN
Solar/Wind Harmer
11.896
942751AE2-291 GEN
Solar/Wind Harmer
24.967
270013AE1-250 PV
Solar/Wind Harmer
0.002
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.266
3147312GRETNA
Solar/Wind Harmer
0.096
941821AE2-187 GEN
Solar/Wind Harmer
15.295
971683AH1-343 GEN
Solar/Wind Harmer
16.89
270197AD1-017 GEN1
Solar/Wind Harmer
0.699
316123AC1-075 GEN
Solar/Wind Harmer
0.627
970865AG2-541 GEN
Solar/Wind Harmer
15.911
970165AG2-112 GEN
Solar/Wind Harmer
3.721
970163AG2-111 GEN
Solar/Wind Harmer
3.549
3151561HALLBR1
50/50
1.184
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.484
970481AG2-311 GEN
50/50
6.751
3147312GRETNA
Solar/Wind Harmer
0.382
3146802CHATHAM
Solar/Wind Harmer
0.358
941801AE2-185 GEN
Solar/Wind Harmer
15.295
316003AC1-222 GEN
Solar/Wind Harmer
0.012
3147123OTTER R
Solar/Wind Harmer
0.275
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.002
270173AC1-122 GEN
Solar/Wind Harmer
0.175
970223AG2-152 GEN
Solar/Wind Harmer
4.628
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.178
NYPJM->LTFIMP_NY
CLTF
0.065
CPLELTFEXP_CPLE->PJM
CLTF
0.484
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.061
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
0.012
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.829
GibsonPJM->LTFIMP_GIBSON
CLTF
0

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 1016_SRT-A-1


Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1016_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.87 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:252.04
MW Contribution:6.76
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
0.096
941821AE2-187 GEN
Solar/Wind Harmer
15.299
971683AH1-343 GEN
Solar/Wind Harmer
16.893
270197AD1-017 GEN1
Solar/Wind Harmer
0.7
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
0.382
3146802CHATHAM
Solar/Wind Harmer
0.358
941801AE2-185 GEN
Solar/Wind Harmer
15.299
3147123OTTER R
Solar/Wind Harmer
0.275
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.002
270173AC1-122 GEN
Solar/Wind Harmer
0.176
970223AG2-152 GEN
Solar/Wind Harmer
4.636
316123AC1-075 GEN
Solar/Wind Harmer
0.628
970865AG2-541 GEN
Solar/Wind Harmer
15.914
970165AG2-112 GEN
Solar/Wind Harmer
3.721
970163AG2-111 GEN
Solar/Wind Harmer
3.55
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
0.006
316197AC1-042 GEN
Solar/Wind Harmer
0.005
942671AE2-283 GEN
Solar/Wind Harmer
11.899
942751AE2-291 GEN
Solar/Wind Harmer
24.973
270013AE1-250 PV
Solar/Wind Harmer
0.002
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.154
NYPJM->LTFIMP_NY
CLTF
0.06
CPLELTFEXP_CPLE->PJM
CLTF
0.492
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.028
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.55 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:248.8
MW Contribution:6.43
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.198
24684505SMG3
50/50
0.741
24684305SMG1
50/50
0.434
316217AC1-145 GEN
Solar/Wind Harmer
7.301
316197AC1-042 GEN
Solar/Wind Harmer
5.534
942671AE2-283 GEN
Solar/Wind Harmer
14.9
942751AE2-291 GEN
Solar/Wind Harmer
17.168
270013AE1-250 PV
Solar/Wind Harmer
2.392
3151561HALLBR1
50/50
0.931
24728405LEESVG
50/50
0.319
24684705SMG5
50/50
0.461
970481AG2-311 GEN
50/50
6.43
3147312GRETNA
Solar/Wind Harmer
-0.036
3146802CHATHAM
Solar/Wind Harmer
-0.034
941801AE2-185 GEN
Solar/Wind Harmer
16.868
3147123OTTER R
Solar/Wind Harmer
-0.024
270574AD1-017 GEN2
Solar/Wind Harmer
5.39
270016AE1-250 BESS
Solar/Wind Harmer
2.392
970223AG2-152 GEN
Solar/Wind Harmer
13.798
316003AC1-222 GEN
Solar/Wind Harmer
1.06
270173AC1-122 GEN
Solar/Wind Harmer
0.706
24728405LEESVG
50/50
0.32
24684605SMG4
50/50
1.206
3147312GRETNA
Solar/Wind Harmer
-0.009
941821AE2-187 GEN
Solar/Wind Harmer
16.868
270197AD1-017 GEN1
Solar/Wind Harmer
1.62
971683AH1-343 GEN
Solar/Wind Harmer
5.942
316248AF1-058 C
Solar/Wind Harmer
0.225
960061AF2-297 GEN
Solar/Wind Harmer
3.734
316123AC1-075 GEN
Solar/Wind Harmer
2.482
970165AG2-112 GEN
Solar/Wind Harmer
2.186
970163AG2-111 GEN
Solar/Wind Harmer
2.085
970865AG2-541 GEN
Solar/Wind Harmer
6.833
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.005
316118AC1-105 GEN
Solar/Wind Harmer
0.454
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.539
NYPJM->LTFIMP_NY
CLTF
0.033
CPLELTFEXP_CPLE->PJM
CLTF
0.729
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.153
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.471
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.072
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o AEP_P7-1_#10778___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10778___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.55 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:248.79
MW Contribution:6.43
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.32
24684605SMG4
50/50
1.206
3147312GRETNA
Solar/Wind Harmer
-0.009
941821AE2-187 GEN
Solar/Wind Harmer
16.868
270197AD1-017 GEN1
Solar/Wind Harmer
1.62
971683AH1-343 GEN
Solar/Wind Harmer
5.942
316248AF1-058 C
Solar/Wind Harmer
0.225
960061AF2-297 GEN
Solar/Wind Harmer
3.734
3151561HALLBR1
50/50
0.931
24728405LEESVG
50/50
0.319
24684705SMG5
50/50
0.461
970481AG2-311 GEN
50/50
6.43
3147312GRETNA
Solar/Wind Harmer
-0.036
3146802CHATHAM
Solar/Wind Harmer
-0.034
941801AE2-185 GEN
Solar/Wind Harmer
16.868
3147123OTTER R
Solar/Wind Harmer
-0.024
270574AD1-017 GEN2
Solar/Wind Harmer
5.39
270016AE1-250 BESS
Solar/Wind Harmer
2.392
970223AG2-152 GEN
Solar/Wind Harmer
13.798
316003AC1-222 GEN
Solar/Wind Harmer
1.06
270173AC1-122 GEN
Solar/Wind Harmer
0.706
316123AC1-075 GEN
Solar/Wind Harmer
2.482
970165AG2-112 GEN
Solar/Wind Harmer
2.186
970163AG2-111 GEN
Solar/Wind Harmer
2.085
970865AG2-541 GEN
Solar/Wind Harmer
6.833
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.005
316118AC1-105 GEN
Solar/Wind Harmer
0.454
24684405SMG2
50/50
1.198
24684505SMG3
50/50
0.741
24684305SMG1
50/50
0.434
316217AC1-145 GEN
Solar/Wind Harmer
7.301
316197AC1-042 GEN
Solar/Wind Harmer
5.534
942671AE2-283 GEN
Solar/Wind Harmer
14.9
942751AE2-291 GEN
Solar/Wind Harmer
17.168
270013AE1-250 PV
Solar/Wind Harmer
2.392
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.539
NYPJM->LTFIMP_NY
CLTF
0.033
CPLELTFEXP_CPLE->PJM
CLTF
0.729
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.153
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.471
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.072
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05OTTER-05JOHNMT 138.0 kV Ckt 1 line l/o DVP_P2-2: ALTAVISTA 115KV_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05OTTER-05JOHNMT 138.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: ALTAVISTA 115KV_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.37 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:245.9
MW Contribution:7.7
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.421
24684605SMG4
50/50
1.443
3147312GRETNA
Solar/Wind Harmer
-0.012
941821AE2-187 GEN
Solar/Wind Harmer
22.918
270197AD1-017 GEN1
Solar/Wind Harmer
1.422
24728405LEESVG
50/50
0.419
24684705SMG5
50/50
0.552
970481AG2-311 GEN
50/50
7.695
3147312GRETNA
Solar/Wind Harmer
-0.049
3146802CHATHAM
Solar/Wind Harmer
-0.046
941801AE2-185 GEN
Solar/Wind Harmer
22.918
270574AD1-017 GEN2
Solar/Wind Harmer
4.731
270016AE1-250 BESS
Solar/Wind Harmer
1.533
270173AC1-122 GEN
Solar/Wind Harmer
0.968
970223AG2-152 GEN
Solar/Wind Harmer
7.548
24684405SMG2
50/50
1.434
24684505SMG3
50/50
0.887
24684305SMG1
50/50
0.52
316217AC1-145 GEN
Solar/Wind Harmer
9.919
316197AC1-042 GEN
Solar/Wind Harmer
7.519
942671AE2-283 GEN
Solar/Wind Harmer
20.244
270013AE1-250 PV
Solar/Wind Harmer
1.533
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.099
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.056
NYPJM->LTFIMP_NY
CLTF
0.054
CPLELTFEXP_CPLE->PJM
CLTF
0.586
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.047
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.144
LAGNLTFEXP_LAGN->PJM
CLTF
0.083
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.044
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.034

Details for 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#10162_05EDAN 1 138_P_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.61 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:289.71
MW Contribution:13.88
Bus #Bus NameTypeMW Contribution
24684705SMG5
50/50
0.996
970481AG2-311 GEN
50/50
13.884
270574AD1-017 GEN2
Solar/Wind Harmer
11.637
270016AE1-250 BESS
Solar/Wind Harmer
5.166
970223AG2-152 GEN
Solar/Wind Harmer
29.792
270173AC1-122 GEN
Solar/Wind Harmer
2.231
3147312GRETNA
Solar/Wind Helper
0.606
3146802CHATHAM
Solar/Wind Helper
0.568
3147123OTTER R
Solar/Wind Helper
0.407
316003AC1-222 GEN
Solar/Wind Helper
0.834
316123AC1-075 GEN
Solar/Wind Helper
2.418
3147173SINAI
Solar/Wind Helper
0.135
3147243WELCO
Solar/Wind Helper
0.084
316118AC1-105 GEN
Solar/Wind Helper
0.469
24684405SMG2
50/50
2.587
24684505SMG3
50/50
1.6
24684305SMG1
50/50
0.938
270013AE1-250 PV
Solar/Wind Harmer
5.166
316197AC1-042 GEN
Solar/Wind Helper
0.71
24684605SMG4
50/50
2.604
270197AD1-017 GEN1
Solar/Wind Harmer
3.497
3147312GRETNA
Solar/Wind Helper
0.151
316248AF1-058 C
Solar/Wind Helper
0.182
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.167
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.07
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.165
MECLTFEXP_MEC->PJM
CLTF
0.201
SIGELTFEXP_SIGE->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.074
LGEELTFEXP_LGEE->PJM
CLTF
0.118
WECLTFEXP_WEC->PJM
CLTF
0.056
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.446
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.849
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.016
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.02 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:288.2
MW Contribution:13.83
Bus #Bus NameTypeMW Contribution
24684705SMG5
50/50
0.992
970481AG2-311 GEN
50/50
13.831
270574AD1-017 GEN2
Solar/Wind Harmer
11.593
270016AE1-250 BESS
Solar/Wind Harmer
5.146
970223AG2-152 GEN
Solar/Wind Harmer
29.68
270173AC1-122 GEN
Solar/Wind Harmer
2.218
3147312GRETNA
Solar/Wind Helper
0.606
3146802CHATHAM
Solar/Wind Helper
0.568
3147123OTTER R
Solar/Wind Helper
0.407
316003AC1-222 GEN
Solar/Wind Helper
0.817
316123AC1-075 GEN
Solar/Wind Helper
2.405
3147173SINAI
Solar/Wind Helper
0.131
3147243WELCO
Solar/Wind Helper
0.082
316118AC1-105 GEN
Solar/Wind Helper
0.453
24684605SMG4
50/50
2.594
270197AD1-017 GEN1
Solar/Wind Harmer
3.484
3147312GRETNA
Solar/Wind Helper
0.152
316248AF1-058 C
Solar/Wind Helper
0.176
24684405SMG2
50/50
2.577
24684505SMG3
50/50
1.594
24684305SMG1
50/50
0.934
270013AE1-250 PV
Solar/Wind Harmer
5.146
316197AC1-042 GEN
Solar/Wind Helper
0.711
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.129
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.759
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.165
MECLTFEXP_MEC->PJM
CLTF
0.174
SIGELTFEXP_SIGE->PJM
CLTF
0.007
NYPJM->LTFIMP_NY
CLTF
0.07
LGEELTFEXP_LGEE->PJM
CLTF
0.101
WECLTFEXP_WEC->PJM
CLTF
0.047
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.352
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.792
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.01
TVALTFEXP_TVA->PJM
CLTF
0.021
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:112.15 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:285.97
MW Contribution:13.83
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
2.577
24684505SMG3
50/50
1.594
24684305SMG1
50/50
0.934
270013AE1-250 PV
Solar/Wind Harmer
5.146
316197AC1-042 GEN
Solar/Wind Helper
0.711
24684705SMG5
50/50
0.992
970481AG2-311 GEN
50/50
13.831
270574AD1-017 GEN2
Solar/Wind Harmer
11.593
270016AE1-250 BESS
Solar/Wind Harmer
5.146
970223AG2-152 GEN
Solar/Wind Harmer
29.68
270173AC1-122 GEN
Solar/Wind Harmer
2.218
3147312GRETNA
Solar/Wind Helper
0.606
3146802CHATHAM
Solar/Wind Helper
0.568
3147123OTTER R
Solar/Wind Helper
0.407
316003AC1-222 GEN
Solar/Wind Helper
0.817
316123AC1-075 GEN
Solar/Wind Helper
2.405
3147173SINAI
Solar/Wind Helper
0.131
3147243WELCO
Solar/Wind Helper
0.082
316118AC1-105 GEN
Solar/Wind Helper
0.453
24684605SMG4
50/50
2.594
270197AD1-017 GEN1
Solar/Wind Harmer
3.484
3147312GRETNA
Solar/Wind Helper
0.152
316248AF1-058 C
Solar/Wind Helper
0.176
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.129
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.759
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.165
MECLTFEXP_MEC->PJM
CLTF
0.174
SIGELTFEXP_SIGE->PJM
CLTF
0.007
NYPJM->LTFIMP_NY
CLTF
0.07
LGEELTFEXP_LGEE->PJM
CLTF
0.101
WECLTFEXP_WEC->PJM
CLTF
0.047
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.352
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.792
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.01
TVALTFEXP_TVA->PJM
CLTF
0.021
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P7-1_#10778___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10778___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:112.13 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:285.94
MW Contribution:13.83
Bus #Bus NameTypeMW Contribution
24684605SMG4
50/50
2.594
270197AD1-017 GEN1
Solar/Wind Harmer
3.484
3147312GRETNA
Solar/Wind Helper
0.152
316248AF1-058 C
Solar/Wind Helper
0.176
24684705SMG5
50/50
0.992
970481AG2-311 GEN
50/50
13.832
270574AD1-017 GEN2
Solar/Wind Harmer
11.594
270016AE1-250 BESS
Solar/Wind Harmer
5.146
970223AG2-152 GEN
Solar/Wind Harmer
29.681
270173AC1-122 GEN
Solar/Wind Harmer
2.219
3147312GRETNA
Solar/Wind Helper
0.606
3146802CHATHAM
Solar/Wind Helper
0.568
3147123OTTER R
Solar/Wind Helper
0.407
316003AC1-222 GEN
Solar/Wind Helper
0.817
316123AC1-075 GEN
Solar/Wind Helper
2.405
3147173SINAI
Solar/Wind Helper
0.131
3147243WELCO
Solar/Wind Helper
0.082
316118AC1-105 GEN
Solar/Wind Helper
0.453
24684405SMG2
50/50
2.577
24684505SMG3
50/50
1.594
24684305SMG1
50/50
0.934
270013AE1-250 PV
Solar/Wind Harmer
5.146
316197AC1-042 GEN
Solar/Wind Helper
0.711
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.129
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.759
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.165
MECLTFEXP_MEC->PJM
CLTF
0.174
SIGELTFEXP_SIGE->PJM
CLTF
0.007
NYPJM->LTFIMP_NY
CLTF
0.07
LGEELTFEXP_LGEE->PJM
CLTF
0.101
WECLTFEXP_WEC->PJM
CLTF
0.047
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.353
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.792
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.01
TVALTFEXP_TVA->PJM
CLTF
0.021
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#10687_05EDAN 2 138_N_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10687_05EDAN 2 138_N_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.13 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:285.92
MW Contribution:13.83
Bus #Bus NameTypeMW Contribution
24684705SMG5
50/50
0.992
970481AG2-311 GEN
50/50
13.832
270574AD1-017 GEN2
Solar/Wind Harmer
11.594
270016AE1-250 BESS
Solar/Wind Harmer
5.146
970223AG2-152 GEN
Solar/Wind Harmer
29.681
316123AC1-075 GEN
Solar/Wind Helper
2.405
3147173SINAI
Solar/Wind Helper
0.131
3147243WELCO
Solar/Wind Helper
0.082
316118AC1-105 GEN
Solar/Wind Helper
0.453
270173AC1-122 GEN
Solar/Wind Harmer
2.219
3147312GRETNA
Solar/Wind Helper
0.606
3146802CHATHAM
Solar/Wind Helper
0.568
3147123OTTER R
Solar/Wind Helper
0.407
316003AC1-222 GEN
Solar/Wind Helper
0.817
24684605SMG4
50/50
2.594
270197AD1-017 GEN1
Solar/Wind Harmer
3.484
3147312GRETNA
Solar/Wind Helper
0.152
316248AF1-058 C
Solar/Wind Helper
0.176
24684405SMG2
50/50
2.577
24684505SMG3
50/50
1.594
24684305SMG1
50/50
0.934
270013AE1-250 PV
Solar/Wind Harmer
5.146
316197AC1-042 GEN
Solar/Wind Helper
0.711
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.129
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.759
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.165
MECLTFEXP_MEC->PJM
CLTF
0.174
SIGELTFEXP_SIGE->PJM
CLTF
0.007
NYPJM->LTFIMP_NY
CLTF
0.07
LGEELTFEXP_LGEE->PJM
CLTF
0.101
WECLTFEXP_WEC->PJM
CLTF
0.047
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.353
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.792
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.01
TVALTFEXP_TVA->PJM
CLTF
0.021
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#8676_05EDANV2 230_S_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8676_05EDANV2 230_S_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.11 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:285.89
MW Contribution:13.83
Bus #Bus NameTypeMW Contribution
24684705SMG5
50/50
0.992
970481AG2-311 GEN
50/50
13.831
270574AD1-017 GEN2
Solar/Wind Harmer
11.593
270016AE1-250 BESS
Solar/Wind Harmer
5.146
970223AG2-152 GEN
Solar/Wind Harmer
29.68
270173AC1-122 GEN
Solar/Wind Harmer
2.218
3147312GRETNA
Solar/Wind Helper
0.606
3146802CHATHAM
Solar/Wind Helper
0.568
3147123OTTER R
Solar/Wind Helper
0.407
316003AC1-222 GEN
Solar/Wind Helper
0.817
24684605SMG4
50/50
2.594
270197AD1-017 GEN1
Solar/Wind Harmer
3.484
3147312GRETNA
Solar/Wind Helper
0.152
316248AF1-058 C
Solar/Wind Helper
0.176
24684405SMG2
50/50
2.577
24684505SMG3
50/50
1.594
24684305SMG1
50/50
0.934
270013AE1-250 PV
Solar/Wind Harmer
5.146
316197AC1-042 GEN
Solar/Wind Helper
0.711
316123AC1-075 GEN
Solar/Wind Helper
2.405
3147173SINAI
Solar/Wind Helper
0.131
3147243WELCO
Solar/Wind Helper
0.082
316118AC1-105 GEN
Solar/Wind Helper
0.453
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.129
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.759
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.165
MECLTFEXP_MEC->PJM
CLTF
0.174
SIGELTFEXP_SIGE->PJM
CLTF
0.007
NYPJM->LTFIMP_NY
CLTF
0.07
LGEELTFEXP_LGEE->PJM
CLTF
0.101
WECLTFEXP_WEC->PJM
CLTF
0.047
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.352
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.792
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.01
TVALTFEXP_TVA->PJM
CLTF
0.021
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#10213_05CLOVRD 138_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10213_05CLOVRD 138_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.78 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:259.55
MW Contribution:14.28
Bus #Bus NameTypeMW Contribution
24684705SMG5
50/50
1.024
970481AG2-311 GEN
50/50
14.277
270574AD1-017 GEN2
Solar/Wind Harmer
8.699
270173AC1-122 GEN
Solar/Wind Harmer
2.269
270016AE1-250 BESS
Solar/Wind Harmer
2.784
970223AG2-152 GEN
Solar/Wind Harmer
13.594
3147312GRETNA
Solar/Wind Helper
0.601
3146802CHATHAM
Solar/Wind Helper
0.563
3147123OTTER R
Solar/Wind Helper
0.402
316003AC1-222 GEN
Solar/Wind Helper
0.713
24684605SMG4
50/50
2.678
270197AD1-017 GEN1
Solar/Wind Harmer
2.614
3147312GRETNA
Solar/Wind Helper
0.15
24684405SMG2
50/50
2.66
24684505SMG3
50/50
1.645
24684305SMG1
50/50
0.964
270013AE1-250 PV
Solar/Wind Harmer
2.784
316197AC1-042 GEN
Solar/Wind Helper
0.705
316123AC1-075 GEN
Solar/Wind Helper
2.3
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.187
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.612
MECLTFEXP_MEC->PJM
CLTF
0.178
SIGELTFEXP_SIGE->PJM
CLTF
0.005
NYPJM->LTFIMP_NY
CLTF
0.072
LGEELTFEXP_LGEE->PJM
CLTF
0.066
WECLTFEXP_WEC->PJM
CLTF
0.034
CPLELTFEXP_CPLE->PJM
CLTF
0.464
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.887
LAGNLTFEXP_LAGN->PJM
CLTF
0.351
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.075
TVALTFEXP_TVA->PJM
CLTF
0.177

Details for 3CRSTL HILL-AC1-222 TAP 115.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3CRSTL HILL-AC1-222 TAP 115.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.3 %
Rating:285.76 MVA
Rating Type:B
MVA to Mitigate:303.76
MW Contribution:4.8
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
0.894
24684505SMG3
50/50
0.553
24684305SMG1
50/50
0.324
942751AE2-291 GEN
Solar/Wind Harmer
31.036
316217AC1-145 GEN
Solar/Wind Harmer
0.003
316197AC1-042 GEN
Solar/Wind Harmer
0.003
942671AE2-283 GEN
Solar/Wind Harmer
6.03
3146843MT LREL
Solar/Wind Helper
0.232
3146843MT LREL
Solar/Wind Helper
0.232
316034AC1-036 C
Solar/Wind Helper
0.123
24728405LEESVG
50/50
0.206
24684605SMG4
50/50
0.9
24288905REUSENS
50/50
0.018
966251AG1-494 GEN
50/50
1.299
971683AH1-343 GEN
Solar/Wind Harmer
31.005
3147312GRETNA
Solar/Wind Harmer
0.048
941821AE2-187 GEN
Solar/Wind Harmer
7.752
270197AD1-017 GEN1
Solar/Wind Harmer
0.469
958131AF2-107 GEN
Solar/Wind Harmer
1.71
316248AF1-058 C
Solar/Wind Helper
0.404
316131AB2-060 GEN
Solar/Wind Helper
0.823
315785AD2-033 C
Solar/Wind Helper
1.409
3151561HALLBR1
50/50
0.745
24728405LEESVG
50/50
0.205
24684705SMG5
50/50
0.344
970481AG2-311 GEN
50/50
4.8
3147123OTTER R
Solar/Wind Harmer
0.184
3147312GRETNA
Solar/Wind Harmer
0.194
3146802CHATHAM
Solar/Wind Harmer
0.182
941801AE2-185 GEN
Solar/Wind Harmer
7.752
270173AC1-122 GEN
Solar/Wind Harmer
0.243
962751AG1-124 GEN
Solar/Wind Harmer
3.521
270574AD1-017 GEN2
Solar/Wind Harmer
0
316003AC1-222 GEN
Solar/Wind Helper
1.905
316237AB2-079_GEN
Solar/Wind Helper
0.188
315687AD1-152 GEN
Solar/Wind Helper
0.645
970865AG2-541 GEN
Solar/Wind Harmer
27.028
316123AC1-075 GEN
Solar/Wind Harmer
0.891
970165AG2-112 GEN
Solar/Wind Harmer
5.283
970163AG2-111 GEN
Solar/Wind Harmer
5.039
3147173SINAI
Solar/Wind Helper
0.301
3147243WELCO
Solar/Wind Helper
0.188
316118AC1-105 GEN
Solar/Wind Helper
1.036
316239AB2-077_GEN
Solar/Wind Helper
0.188
316238AB2-078_GEN
Solar/Wind Helper
0.188
3144303KENBRDG
Solar/Wind Helper
0.094
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.077
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.522
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.969
MECLTFEXP_MEC->PJM
CLTF
0.978
SIGELTFEXP_SIGE->PJM
CLTF
0.034
NYPJM->LTFIMP_NY
CLTF
0.187
LGEELTFEXP_LGEE->PJM
CLTF
0.468
WECLTFEXP_WEC->PJM
CLTF
0.232
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.458
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.014
LAGNLTFEXP_LAGN->PJM
CLTF
0.878
TVALTFEXP_TVA->PJM
CLTF
0.49

Details for 3CRSTL HILL-AC1-222 TAP 115.0 kV Ckt 1 line l/o AEP_P4_#10162_05EDAN 1 138_P_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3CRSTL HILL-AC1-222 TAP 115.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.59 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:352.07
MW Contribution:6.09
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.134
24684505SMG3
50/50
0.701
24684305SMG1
50/50
0.411
942751AE2-291 GEN
Solar/Wind Harmer
41.056
316217AC1-145 GEN
Solar/Wind Harmer
4.616
316197AC1-042 GEN
Solar/Wind Harmer
3.499
942671AE2-283 GEN
Solar/Wind Harmer
9.42
270013AE1-250 PV
Solar/Wind Harmer
2.264
3146843MT LREL
Solar/Wind Helper
0.245
3146843MT LREL
Solar/Wind Helper
0.245
316034AC1-036 C
Solar/Wind Helper
0.131
3151561HALLBR1
50/50
0.769
24728405LEESVG
50/50
0.229
24684705SMG5
50/50
0.437
970481AG2-311 GEN
50/50
6.086
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.665
270574AD1-017 GEN2
Solar/Wind Harmer
5.101
270016AE1-250 BESS
Solar/Wind Harmer
2.264
970223AG2-152 GEN
Solar/Wind Harmer
13.058
270173AC1-122 GEN
Solar/Wind Harmer
1.401
962751AG1-124 GEN
Solar/Wind Harmer
5.108
316003AC1-222 GEN
Solar/Wind Helper
1.949
316237AB2-079_GEN
Solar/Wind Helper
0.202
315687AD1-152 GEN
Solar/Wind Helper
0.724
970865AG2-541 GEN
Solar/Wind Harmer
35.485
316123AC1-075 GEN
Solar/Wind Harmer
7.909
970165AG2-112 GEN
Solar/Wind Harmer
6.964
970163AG2-111 GEN
Solar/Wind Harmer
6.643
3147173SINAI
Solar/Wind Helper
0.314
3147243WELCO
Solar/Wind Helper
0.196
316118AC1-105 GEN
Solar/Wind Helper
1.086
316239AB2-077_GEN
Solar/Wind Helper
0.202
316238AB2-078_GEN
Solar/Wind Helper
0.202
3144303KENBRDG
Solar/Wind Helper
0.1
24728405LEESVG
50/50
0.23
24684605SMG4
50/50
1.141
971683AH1-343 GEN
Solar/Wind Harmer
40.643
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.665
270197AD1-017 GEN1
Solar/Wind Harmer
1.533
958131AF2-107 GEN
Solar/Wind Harmer
2.307
316248AF1-058 C
Solar/Wind Helper
0.422
316131AB2-060 GEN
Solar/Wind Helper
0.886
315785AD2-033 C
Solar/Wind Helper
1.508
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.376
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.824
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.391
MECLTFEXP_MEC->PJM
CLTF
0.467
SIGELTFEXP_SIGE->PJM
CLTF
0.018
NYPJM->LTFIMP_NY
CLTF
0.1
LGEELTFEXP_LGEE->PJM
CLTF
0.269
WECLTFEXP_WEC->PJM
CLTF
0.129
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.998
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.996
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.041
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.18 %
Rating:285.76 MVA
Rating Type:B
MVA to Mitigate:331.99
MW Contribution:4.79
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.206
24684605SMG4
50/50
0.898
24288905REUSENS
50/50
0.018
966251AG1-494 GEN
50/50
1.295
971683AH1-343 GEN
Solar/Wind Harmer
30.996
3147312GRETNA
Solar/Wind Harmer
0.048
941821AE2-187 GEN
Solar/Wind Harmer
7.744
270197AD1-017 GEN1
Solar/Wind Harmer
0.467
958131AF2-107 GEN
Solar/Wind Harmer
1.702
316248AF1-058 C
Solar/Wind Helper
0.405
316131AB2-060 GEN
Solar/Wind Helper
0.826
315785AD2-033 C
Solar/Wind Helper
1.415
24684405SMG2
50/50
0.892
24684505SMG3
50/50
0.552
24684305SMG1
50/50
0.323
942751AE2-291 GEN
Solar/Wind Harmer
31.022
316217AC1-145 GEN
Solar/Wind Harmer
0.003
316197AC1-042 GEN
Solar/Wind Harmer
0.003
942671AE2-283 GEN
Solar/Wind Harmer
6.023
3146843MT LREL
Solar/Wind Helper
0.233
3146843MT LREL
Solar/Wind Helper
0.233
316034AC1-036 C
Solar/Wind Helper
0.123
970865AG2-541 GEN
Solar/Wind Harmer
27.019
316123AC1-075 GEN
Solar/Wind Harmer
0.891
970165AG2-112 GEN
Solar/Wind Harmer
5.281
970163AG2-111 GEN
Solar/Wind Harmer
5.037
3147173SINAI
Solar/Wind Helper
0.301
3147243WELCO
Solar/Wind Helper
0.188
316118AC1-105 GEN
Solar/Wind Helper
1.038
316239AB2-077_GEN
Solar/Wind Helper
0.189
316238AB2-078_GEN
Solar/Wind Helper
0.189
3144303KENBRDG
Solar/Wind Helper
0.094
3151561HALLBR1
50/50
0.745
24728405LEESVG
50/50
0.205
24684705SMG5
50/50
0.344
970481AG2-311 GEN
50/50
4.788
316003AC1-222 GEN
Solar/Wind Harmer
0.024
3147123OTTER R
Solar/Wind Harmer
0.184
3147312GRETNA
Solar/Wind Harmer
0.193
3146802CHATHAM
Solar/Wind Harmer
0.181
941801AE2-185 GEN
Solar/Wind Harmer
7.744
270173AC1-122 GEN
Solar/Wind Harmer
0.243
962751AG1-124 GEN
Solar/Wind Harmer
3.509
270574AD1-017 GEN2
Solar/Wind Harmer
0
316237AB2-079_GEN
Solar/Wind Helper
0.189
315687AD1-152 GEN
Solar/Wind Helper
0.648
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.085
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.233
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.894
MECLTFEXP_MEC->PJM
CLTF
0.944
SIGELTFEXP_SIGE->PJM
CLTF
0.033
NYPJM->LTFIMP_NY
CLTF
0.2
LGEELTFEXP_LGEE->PJM
CLTF
0.454
WECLTFEXP_WEC->PJM
CLTF
0.224
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.472
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.748
LAGNLTFEXP_LAGN->PJM
CLTF
0.838
TVALTFEXP_TVA->PJM
CLTF
0.47

Details for 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line l/o AEP_P4_#10162_05EDAN 1 138_P_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.45 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:390.08
MW Contribution:6.07
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
0.769
24728405LEESVG
50/50
0.228
24684705SMG5
50/50
0.436
970481AG2-311 GEN
50/50
6.074
316003AC1-222 GEN
Solar/Wind Harmer
9.848
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.654
270574AD1-017 GEN2
Solar/Wind Harmer
5.091
270016AE1-250 BESS
Solar/Wind Harmer
2.26
970223AG2-152 GEN
Solar/Wind Harmer
13.033
270173AC1-122 GEN
Solar/Wind Harmer
1.398
962751AG1-124 GEN
Solar/Wind Harmer
5.091
316237AB2-079_GEN
Solar/Wind Helper
0.203
315687AD1-152 GEN
Solar/Wind Helper
0.727
24728405LEESVG
50/50
0.229
24684605SMG4
50/50
1.139
971683AH1-343 GEN
Solar/Wind Harmer
40.631
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.654
270197AD1-017 GEN1
Solar/Wind Harmer
1.53
958131AF2-107 GEN
Solar/Wind Harmer
2.297
316248AF1-058 C
Solar/Wind Helper
0.423
316131AB2-060 GEN
Solar/Wind Helper
0.889
315785AD2-033 C
Solar/Wind Helper
1.513
24684405SMG2
50/50
1.132
24684505SMG3
50/50
0.7
24684305SMG1
50/50
0.41
942751AE2-291 GEN
Solar/Wind Harmer
41.038
316217AC1-145 GEN
Solar/Wind Harmer
4.611
316197AC1-042 GEN
Solar/Wind Harmer
3.495
942671AE2-283 GEN
Solar/Wind Harmer
9.411
270013AE1-250 PV
Solar/Wind Harmer
2.26
3146843MT LREL
Solar/Wind Helper
0.245
3146843MT LREL
Solar/Wind Helper
0.245
316034AC1-036 C
Solar/Wind Helper
0.132
970865AG2-541 GEN
Solar/Wind Harmer
35.473
316123AC1-075 GEN
Solar/Wind Harmer
7.906
970165AG2-112 GEN
Solar/Wind Harmer
6.961
970163AG2-111 GEN
Solar/Wind Harmer
6.641
3147173SINAI
Solar/Wind Helper
0.315
3147243WELCO
Solar/Wind Helper
0.197
316118AC1-105 GEN
Solar/Wind Helper
1.088
316239AB2-077_GEN
Solar/Wind Helper
0.203
316238AB2-078_GEN
Solar/Wind Helper
0.203
3144303KENBRDG
Solar/Wind Helper
0.101
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.384
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.535
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.316
MECLTFEXP_MEC->PJM
CLTF
0.433
SIGELTFEXP_SIGE->PJM
CLTF
0.017
NYPJM->LTFIMP_NY
CLTF
0.113
LGEELTFEXP_LGEE->PJM
CLTF
0.256
WECLTFEXP_WEC->PJM
CLTF
0.121
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.011
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.729
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.021
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.96 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:384.85
MW Contribution:5.99
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
0.767
24728405LEESVG
50/50
0.227
24684705SMG5
50/50
0.43
970481AG2-311 GEN
50/50
5.987
316003AC1-222 GEN
Solar/Wind Harmer
9.884
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.622
270574AD1-017 GEN2
Solar/Wind Harmer
5.018
270016AE1-250 BESS
Solar/Wind Harmer
2.228
970223AG2-152 GEN
Solar/Wind Harmer
12.847
270173AC1-122 GEN
Solar/Wind Harmer
1.377
962751AG1-124 GEN
Solar/Wind Harmer
5
316237AB2-079_GEN
Solar/Wind Helper
0.194
315687AD1-152 GEN
Solar/Wind Helper
0.686
24728405LEESVG
50/50
0.228
24684605SMG4
50/50
1.123
971683AH1-343 GEN
Solar/Wind Harmer
40.772
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.622
270197AD1-017 GEN1
Solar/Wind Harmer
1.508
958131AF2-107 GEN
Solar/Wind Harmer
2.266
316248AF1-058 C
Solar/Wind Helper
0.413
316131AB2-060 GEN
Solar/Wind Helper
0.85
315785AD2-033 C
Solar/Wind Helper
1.444
24684405SMG2
50/50
1.115
24684505SMG3
50/50
0.69
24684305SMG1
50/50
0.404
942751AE2-291 GEN
Solar/Wind Harmer
41.127
316217AC1-145 GEN
Solar/Wind Harmer
4.597
316197AC1-042 GEN
Solar/Wind Harmer
3.485
942671AE2-283 GEN
Solar/Wind Harmer
9.382
270013AE1-250 PV
Solar/Wind Harmer
2.228
3146843MT LREL
Solar/Wind Helper
0.238
3146843MT LREL
Solar/Wind Helper
0.238
316034AC1-036 C
Solar/Wind Helper
0.126
970865AG2-541 GEN
Solar/Wind Harmer
35.588
316123AC1-075 GEN
Solar/Wind Harmer
7.927
970165AG2-112 GEN
Solar/Wind Harmer
6.98
970163AG2-111 GEN
Solar/Wind Harmer
6.658
3147173SINAI
Solar/Wind Helper
0.307
3147243WELCO
Solar/Wind Helper
0.192
316118AC1-105 GEN
Solar/Wind Helper
1.06
316239AB2-077_GEN
Solar/Wind Helper
0.194
316238AB2-078_GEN
Solar/Wind Helper
0.194
3144303KENBRDG
Solar/Wind Helper
0.096
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.321
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.018
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.317
MECLTFEXP_MEC->PJM
CLTF
0.388
SIGELTFEXP_SIGE->PJM
CLTF
0.015
NYPJM->LTFIMP_NY
CLTF
0.104
LGEELTFEXP_LGEE->PJM
CLTF
0.226
WECLTFEXP_WEC->PJM
CLTF
0.108
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.855
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.635
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.03
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line l/o AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:109.7 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:383.94
MW Contribution:5.99
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.115
24684505SMG3
50/50
0.69
24684305SMG1
50/50
0.404
942751AE2-291 GEN
Solar/Wind Harmer
41.127
316217AC1-145 GEN
Solar/Wind Harmer
4.597
316197AC1-042 GEN
Solar/Wind Harmer
3.485
942671AE2-283 GEN
Solar/Wind Harmer
9.382
270013AE1-250 PV
Solar/Wind Harmer
2.228
3146843MT LREL
Solar/Wind Helper
0.238
3146843MT LREL
Solar/Wind Helper
0.238
316034AC1-036 C
Solar/Wind Helper
0.126
3151561HALLBR1
50/50
0.767
24728405LEESVG
50/50
0.227
24684705SMG5
50/50
0.43
970481AG2-311 GEN
50/50
5.987
316003AC1-222 GEN
Solar/Wind Harmer
9.884
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.622
270574AD1-017 GEN2
Solar/Wind Harmer
5.018
270016AE1-250 BESS
Solar/Wind Harmer
2.228
970223AG2-152 GEN
Solar/Wind Harmer
12.847
270173AC1-122 GEN
Solar/Wind Harmer
1.377
962751AG1-124 GEN
Solar/Wind Harmer
5
316237AB2-079_GEN
Solar/Wind Helper
0.194
315687AD1-152 GEN
Solar/Wind Helper
0.686
970865AG2-541 GEN
Solar/Wind Harmer
35.588
316123AC1-075 GEN
Solar/Wind Harmer
7.927
970165AG2-112 GEN
Solar/Wind Harmer
6.98
970163AG2-111 GEN
Solar/Wind Harmer
6.658
3147173SINAI
Solar/Wind Helper
0.307
3147243WELCO
Solar/Wind Helper
0.192
316118AC1-105 GEN
Solar/Wind Helper
1.06
316239AB2-077_GEN
Solar/Wind Helper
0.194
316238AB2-078_GEN
Solar/Wind Helper
0.194
3144303KENBRDG
Solar/Wind Helper
0.096
24728405LEESVG
50/50
0.228
24684605SMG4
50/50
1.123
971683AH1-343 GEN
Solar/Wind Harmer
40.772
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.622
270197AD1-017 GEN1
Solar/Wind Harmer
1.508
958131AF2-107 GEN
Solar/Wind Harmer
2.266
316248AF1-058 C
Solar/Wind Helper
0.413
316131AB2-060 GEN
Solar/Wind Helper
0.85
315785AD2-033 C
Solar/Wind Helper
1.444
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.321
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.018
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.317
MECLTFEXP_MEC->PJM
CLTF
0.388
SIGELTFEXP_SIGE->PJM
CLTF
0.015
NYPJM->LTFIMP_NY
CLTF
0.104
LGEELTFEXP_LGEE->PJM
CLTF
0.226
WECLTFEXP_WEC->PJM
CLTF
0.108
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.855
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.635
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.03
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line l/o AEP_P7-1_#10778___SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10778___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:109.69 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:383.92
MW Contribution:5.99
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.228
24684605SMG4
50/50
1.123
971683AH1-343 GEN
Solar/Wind Harmer
40.772
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.622
270197AD1-017 GEN1
Solar/Wind Harmer
1.508
958131AF2-107 GEN
Solar/Wind Harmer
2.266
316248AF1-058 C
Solar/Wind Helper
0.413
316131AB2-060 GEN
Solar/Wind Helper
0.85
315785AD2-033 C
Solar/Wind Helper
1.445
3151561HALLBR1
50/50
0.767
24728405LEESVG
50/50
0.227
24684705SMG5
50/50
0.43
970481AG2-311 GEN
50/50
5.987
316003AC1-222 GEN
Solar/Wind Harmer
9.884
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.622
270574AD1-017 GEN2
Solar/Wind Harmer
5.018
270016AE1-250 BESS
Solar/Wind Harmer
2.228
970223AG2-152 GEN
Solar/Wind Harmer
12.847
270173AC1-122 GEN
Solar/Wind Harmer
1.377
962751AG1-124 GEN
Solar/Wind Harmer
5
316237AB2-079_GEN
Solar/Wind Helper
0.194
315687AD1-152 GEN
Solar/Wind Helper
0.686
970865AG2-541 GEN
Solar/Wind Harmer
35.588
316123AC1-075 GEN
Solar/Wind Harmer
7.927
970165AG2-112 GEN
Solar/Wind Harmer
6.98
970163AG2-111 GEN
Solar/Wind Harmer
6.658
3147173SINAI
Solar/Wind Helper
0.307
3147243WELCO
Solar/Wind Helper
0.192
316118AC1-105 GEN
Solar/Wind Helper
1.06
316239AB2-077_GEN
Solar/Wind Helper
0.194
316238AB2-078_GEN
Solar/Wind Helper
0.194
3144303KENBRDG
Solar/Wind Helper
0.096
24684405SMG2
50/50
1.116
24684505SMG3
50/50
0.69
24684305SMG1
50/50
0.404
942751AE2-291 GEN
Solar/Wind Harmer
41.127
316217AC1-145 GEN
Solar/Wind Harmer
4.597
316197AC1-042 GEN
Solar/Wind Harmer
3.485
942671AE2-283 GEN
Solar/Wind Harmer
9.383
270013AE1-250 PV
Solar/Wind Harmer
2.228
3146843MT LREL
Solar/Wind Helper
0.238
3146843MT LREL
Solar/Wind Helper
0.238
316034AC1-036 C
Solar/Wind Helper
0.126
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.321
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.019
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.317
MECLTFEXP_MEC->PJM
CLTF
0.388
SIGELTFEXP_SIGE->PJM
CLTF
0.015
NYPJM->LTFIMP_NY
CLTF
0.104
LGEELTFEXP_LGEE->PJM
CLTF
0.226
WECLTFEXP_WEC->PJM
CLTF
0.108
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.855
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.635
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.03
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 553_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 553_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.38 %
Rating:285.76 MVA
Rating Type:B
MVA to Mitigate:306.86
MW Contribution:4.38
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
0.816
24684505SMG3
50/50
0.505
24684305SMG1
50/50
0.296
942751AE2-291 GEN
Solar/Wind Harmer
30.733
316217AC1-145 GEN
Solar/Wind Harmer
0.003
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
5.824
3146843MT LREL
Solar/Wind Helper
0.236
3146843MT LREL
Solar/Wind Helper
0.236
316034AC1-036 C
Solar/Wind Helper
0.122
24728405LEESVG
50/50
0.195
24684605SMG4
50/50
0.822
24288905REUSENS
50/50
0.016
966251AG1-494 GEN
50/50
1.151
971683AH1-343 GEN
Solar/Wind Harmer
30.882
3147312GRETNA
Solar/Wind Harmer
0.047
941821AE2-187 GEN
Solar/Wind Harmer
7.488
270197AD1-017 GEN1
Solar/Wind Harmer
0.418
316248AF1-058 C
Solar/Wind Helper
0.41
316131AB2-060 GEN
Solar/Wind Helper
0.829
315785AD2-033 C
Solar/Wind Helper
1.406
970865AG2-541 GEN
Solar/Wind Harmer
26.894
316123AC1-075 GEN
Solar/Wind Harmer
0.884
970165AG2-112 GEN
Solar/Wind Harmer
5.243
970163AG2-111 GEN
Solar/Wind Harmer
5.001
3147173SINAI
Solar/Wind Helper
0.305
3147243WELCO
Solar/Wind Helper
0.191
316118AC1-105 GEN
Solar/Wind Helper
1.051
316239AB2-077_GEN
Solar/Wind Helper
0.19
3151561HALLBR1
50/50
0.725
24728405LEESVG
50/50
0.195
24684705SMG5
50/50
0.314
970481AG2-311 GEN
50/50
4.381
316003AC1-222 GEN
Solar/Wind Harmer
0.024
3147123OTTER R
Solar/Wind Harmer
0.179
3147312GRETNA
Solar/Wind Harmer
0.187
3146802CHATHAM
Solar/Wind Harmer
0.175
941801AE2-185 GEN
Solar/Wind Harmer
7.488
270173AC1-122 GEN
Solar/Wind Harmer
0.22
962751AG1-124 GEN
Solar/Wind Harmer
3.082
270574AD1-017 GEN2
Solar/Wind Harmer
0
316237AB2-079_GEN
Solar/Wind Helper
0.19
315687AD1-152 GEN
Solar/Wind Helper
0.658
316238AB2-078_GEN
Solar/Wind Helper
0.19
3144303KENBRDG
Solar/Wind Helper
0.094
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.22
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.631
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.664
MECLTFEXP_MEC->PJM
CLTF
0.482
SIGELTFEXP_SIGE->PJM
CLTF
0.018
NYPJM->LTFIMP_NY
CLTF
0.114
LGEELTFEXP_LGEE->PJM
CLTF
0.255
WECLTFEXP_WEC->PJM
CLTF
0.124
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.654
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.709
LAGNLTFEXP_LAGN->PJM
CLTF
0.196
TVALTFEXP_TVA->PJM
CLTF
0.134

Details for 3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:105.51 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:369.27
MW Contribution:5.58
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.04
24684505SMG3
50/50
0.643
24684305SMG1
50/50
0.377
942751AE2-291 GEN
Solar/Wind Harmer
44.58
316217AC1-145 GEN
Solar/Wind Harmer
5.995
316197AC1-042 GEN
Solar/Wind Harmer
4.545
942671AE2-283 GEN
Solar/Wind Harmer
12.236
3146843MT LREL
Solar/Wind Helper
0.208
3146843MT LREL
Solar/Wind Helper
0.208
3151561HALLBR1
50/50
0.945
24728405LEESVG
50/50
0.266
24684705SMG5
50/50
0.401
970481AG2-311 GEN
50/50
5.583
316003AC1-222 GEN
Solar/Wind Harmer
10.144
3147123OTTER R
Solar/Wind Harmer
-0.025
3147312GRETNA
Solar/Wind Harmer
-0.03
3146802CHATHAM
Solar/Wind Harmer
-0.028
941801AE2-185 GEN
Solar/Wind Harmer
13.852
270173AC1-122 GEN
Solar/Wind Harmer
1.159
270574AD1-017 GEN2
Solar/Wind Harmer
3.24
316237AB2-079_GEN
Solar/Wind Helper
0.166
24728405LEESVG
50/50
0.267
24684605SMG4
50/50
1.047
971683AH1-343 GEN
Solar/Wind Harmer
42.136
3147312GRETNA
Solar/Wind Harmer
-0.007
941821AE2-187 GEN
Solar/Wind Harmer
13.852
270197AD1-017 GEN1
Solar/Wind Harmer
0.973
316248AF1-058 C
Solar/Wind Helper
0.364
316131AB2-060 GEN
Solar/Wind Helper
0.725
970865AG2-541 GEN
Solar/Wind Harmer
37.085
316123AC1-075 GEN
Solar/Wind Harmer
8.439
970165AG2-112 GEN
Solar/Wind Harmer
7.43
970163AG2-111 GEN
Solar/Wind Harmer
7.088
3147173SINAI
Solar/Wind Helper
0.271
3147243WELCO
Solar/Wind Helper
0.169
316118AC1-105 GEN
Solar/Wind Helper
0.93
316239AB2-077_GEN
Solar/Wind Helper
0.166
316238AB2-078_GEN
Solar/Wind Helper
0.166
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.175
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.335
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.465
MECLTFEXP_MEC->PJM
CLTF
0.347
SIGELTFEXP_SIGE->PJM
CLTF
0.013
NYPJM->LTFIMP_NY
CLTF
0.102
LGEELTFEXP_LGEE->PJM
CLTF
0.187
WECLTFEXP_WEC->PJM
CLTF
0.09
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.518
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.905
LAGNLTFEXP_LAGN->PJM
CLTF
0.125
TVALTFEXP_TVA->PJM
CLTF
0.091

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o DVP_P4-2: 151T1047_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 151T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:137.18 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:336.08
MW Contribution:6.75
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.266
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.139
971683AH1-343 GEN
Solar/Wind Harmer
22.238
270197AD1-017 GEN1
Solar/Wind Harmer
1.246
3151561HALLBR1
50/50
1.184
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.484
970481AG2-311 GEN
50/50
6.751
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.139
316003AC1-222 GEN
Solar/Wind Harmer
5.036
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.147
270016AE1-250 BESS
Solar/Wind Harmer
1.342
270173AC1-122 GEN
Solar/Wind Harmer
0.85
970223AG2-152 GEN
Solar/Wind Harmer
6.601
316123AC1-075 GEN
Solar/Wind Harmer
5.564
970865AG2-541 GEN
Solar/Wind Harmer
20.949
970165AG2-112 GEN
Solar/Wind Harmer
4.899
970163AG2-111 GEN
Solar/Wind Harmer
4.673
24684405SMG2
50/50
1.258
24684505SMG3
50/50
0.778
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.716
316197AC1-042 GEN
Solar/Wind Harmer
6.608
942671AE2-283 GEN
Solar/Wind Harmer
17.789
942751AE2-291 GEN
Solar/Wind Harmer
32.874
270013AE1-250 PV
Solar/Wind Harmer
1.342
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.177
NYPJM->LTFIMP_NY
CLTF
0.065
CPLELTFEXP_CPLE->PJM
CLTF
0.484
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.061
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
0.013
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.831
GibsonPJM->LTFIMP_GIBSON
CLTF
0

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o DVP_P4-2: 104702_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104702_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:137.17 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:336.06
MW Contribution:6.75
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.266
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.139
971683AH1-343 GEN
Solar/Wind Harmer
22.238
270197AD1-017 GEN1
Solar/Wind Harmer
1.246
3151561HALLBR1
50/50
1.184
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.484
970481AG2-311 GEN
50/50
6.751
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.139
316003AC1-222 GEN
Solar/Wind Harmer
5.035
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.147
270016AE1-250 BESS
Solar/Wind Harmer
1.342
270173AC1-122 GEN
Solar/Wind Harmer
0.85
970223AG2-152 GEN
Solar/Wind Harmer
6.6
316123AC1-075 GEN
Solar/Wind Harmer
5.564
970865AG2-541 GEN
Solar/Wind Harmer
20.949
970165AG2-112 GEN
Solar/Wind Harmer
4.899
970163AG2-111 GEN
Solar/Wind Harmer
4.673
24684405SMG2
50/50
1.258
24684505SMG3
50/50
0.778
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.716
316197AC1-042 GEN
Solar/Wind Harmer
6.608
942671AE2-283 GEN
Solar/Wind Harmer
17.789
942751AE2-291 GEN
Solar/Wind Harmer
32.874
270013AE1-250 PV
Solar/Wind Harmer
1.342
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.178
NYPJM->LTFIMP_NY
CLTF
0.065
CPLELTFEXP_CPLE->PJM
CLTF
0.484
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.061
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
0.012
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.829
GibsonPJM->LTFIMP_GIBSON
CLTF
0

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o DVP_P4-2: 1016T1047_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 1016T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.26 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:319.14
MW Contribution:6.76
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.143
971683AH1-343 GEN
Solar/Wind Harmer
22.243
270197AD1-017 GEN1
Solar/Wind Harmer
1.247
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.143
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.151
270016AE1-250 BESS
Solar/Wind Harmer
1.344
270173AC1-122 GEN
Solar/Wind Harmer
0.851
970223AG2-152 GEN
Solar/Wind Harmer
6.611
316123AC1-075 GEN
Solar/Wind Harmer
5.565
970865AG2-541 GEN
Solar/Wind Harmer
20.954
970165AG2-112 GEN
Solar/Wind Harmer
4.9
970163AG2-111 GEN
Solar/Wind Harmer
4.674
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.718
316197AC1-042 GEN
Solar/Wind Harmer
6.609
942671AE2-283 GEN
Solar/Wind Harmer
17.793
942751AE2-291 GEN
Solar/Wind Harmer
32.881
270013AE1-250 PV
Solar/Wind Harmer
1.344
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.153
NYPJM->LTFIMP_NY
CLTF
0.06
CPLELTFEXP_CPLE->PJM
CLTF
0.492
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.029
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o DVP_P4-2: 101672_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 101672_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.24 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:319.1
MW Contribution:6.76
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.143
971683AH1-343 GEN
Solar/Wind Harmer
22.243
270197AD1-017 GEN1
Solar/Wind Harmer
1.247
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.143
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.151
270016AE1-250 BESS
Solar/Wind Harmer
1.344
270173AC1-122 GEN
Solar/Wind Harmer
0.851
970223AG2-152 GEN
Solar/Wind Harmer
6.611
316123AC1-075 GEN
Solar/Wind Harmer
5.565
970865AG2-541 GEN
Solar/Wind Harmer
20.954
970165AG2-112 GEN
Solar/Wind Harmer
4.9
970163AG2-111 GEN
Solar/Wind Harmer
4.674
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.718
316197AC1-042 GEN
Solar/Wind Harmer
6.609
942671AE2-283 GEN
Solar/Wind Harmer
17.793
942751AE2-291 GEN
Solar/Wind Harmer
32.881
270013AE1-250 PV
Solar/Wind Harmer
1.344
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.153
NYPJM->LTFIMP_NY
CLTF
0.06
CPLELTFEXP_CPLE->PJM
CLTF
0.492
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.029
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o DVP_P4-2: 104772_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104772_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.8 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:315.55
MW Contribution:6.76
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
-0.011
941821AE2-187 GEN
Solar/Wind Harmer
20.143
971683AH1-343 GEN
Solar/Wind Harmer
22.243
270197AD1-017 GEN1
Solar/Wind Harmer
1.247
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
-0.043
3146802CHATHAM
Solar/Wind Harmer
-0.04
941801AE2-185 GEN
Solar/Wind Harmer
20.143
3147123OTTER R
Solar/Wind Harmer
-0.031
270574AD1-017 GEN2
Solar/Wind Harmer
4.151
270016AE1-250 BESS
Solar/Wind Harmer
1.344
270173AC1-122 GEN
Solar/Wind Harmer
0.851
970223AG2-152 GEN
Solar/Wind Harmer
6.611
316123AC1-075 GEN
Solar/Wind Harmer
5.565
970865AG2-541 GEN
Solar/Wind Harmer
20.954
970165AG2-112 GEN
Solar/Wind Harmer
4.9
970163AG2-111 GEN
Solar/Wind Harmer
4.674
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
8.718
316197AC1-042 GEN
Solar/Wind Harmer
6.609
942671AE2-283 GEN
Solar/Wind Harmer
17.793
942751AE2-291 GEN
Solar/Wind Harmer
32.881
270013AE1-250 PV
Solar/Wind Harmer
1.344
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.153
NYPJM->LTFIMP_NY
CLTF
0.06
CPLELTFEXP_CPLE->PJM
CLTF
0.492
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.029
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 1047_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1047_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.43 %
Rating:230.3 MVA
Rating Type:B
MVA to Mitigate:265.84
MW Contribution:6.75
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.266
3147312GRETNA
Solar/Wind Harmer
0.096
941821AE2-187 GEN
Solar/Wind Harmer
15.295
971683AH1-343 GEN
Solar/Wind Harmer
16.89
270197AD1-017 GEN1
Solar/Wind Harmer
0.699
24684405SMG2
50/50
1.258
24684505SMG3
50/50
0.778
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
0.006
316197AC1-042 GEN
Solar/Wind Harmer
0.005
942671AE2-283 GEN
Solar/Wind Harmer
11.896
942751AE2-291 GEN
Solar/Wind Harmer
24.967
270013AE1-250 PV
Solar/Wind Harmer
0.002
316123AC1-075 GEN
Solar/Wind Harmer
0.627
970865AG2-541 GEN
Solar/Wind Harmer
15.911
970165AG2-112 GEN
Solar/Wind Harmer
3.721
970163AG2-111 GEN
Solar/Wind Harmer
3.549
3151561HALLBR1
50/50
1.184
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.484
970481AG2-311 GEN
50/50
6.751
3147312GRETNA
Solar/Wind Harmer
0.382
3146802CHATHAM
Solar/Wind Harmer
0.358
941801AE2-185 GEN
Solar/Wind Harmer
15.295
316003AC1-222 GEN
Solar/Wind Harmer
0.012
3147123OTTER R
Solar/Wind Harmer
0.275
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.002
270173AC1-122 GEN
Solar/Wind Harmer
0.175
970223AG2-152 GEN
Solar/Wind Harmer
4.628
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.178
NYPJM->LTFIMP_NY
CLTF
0.065
CPLELTFEXP_CPLE->PJM
CLTF
0.484
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.061
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
0.012
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.829
GibsonPJM->LTFIMP_GIBSON
CLTF
0

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 1016_SRT-A-1


Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1016_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.32 %
Rating:230.3 MVA
Rating Type:B
MVA to Mitigate:254.07
MW Contribution:6.76
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.37
24684605SMG4
50/50
1.267
3147312GRETNA
Solar/Wind Harmer
0.096
941821AE2-187 GEN
Solar/Wind Harmer
15.299
971683AH1-343 GEN
Solar/Wind Harmer
16.893
270197AD1-017 GEN1
Solar/Wind Harmer
0.7
24684405SMG2
50/50
1.259
24684505SMG3
50/50
0.779
24684305SMG1
50/50
0.456
316217AC1-145 GEN
Solar/Wind Harmer
0.006
316197AC1-042 GEN
Solar/Wind Harmer
0.005
942671AE2-283 GEN
Solar/Wind Harmer
11.899
942751AE2-291 GEN
Solar/Wind Harmer
24.973
270013AE1-250 PV
Solar/Wind Harmer
0.002
316123AC1-075 GEN
Solar/Wind Harmer
0.628
970865AG2-541 GEN
Solar/Wind Harmer
15.914
970165AG2-112 GEN
Solar/Wind Harmer
3.721
970163AG2-111 GEN
Solar/Wind Harmer
3.55
3151561HALLBR1
50/50
1.185
24728405LEESVG
50/50
0.368
24684705SMG5
50/50
0.485
970481AG2-311 GEN
50/50
6.756
3147312GRETNA
Solar/Wind Harmer
0.382
3146802CHATHAM
Solar/Wind Harmer
0.358
941801AE2-185 GEN
Solar/Wind Harmer
15.299
3147123OTTER R
Solar/Wind Harmer
0.275
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.002
270173AC1-122 GEN
Solar/Wind Harmer
0.176
970223AG2-152 GEN
Solar/Wind Harmer
4.636
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.154
NYPJM->LTFIMP_NY
CLTF
0.06
CPLELTFEXP_CPLE->PJM
CLTF
0.492
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.056
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
0.028
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.854
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.007

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.83 %
Rating:156.98 MVA
Rating Type:A
MVA to Mitigate:164.56
MW Contribution:5.0
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.291
24684605SMG4
50/50
0.938
3147312GRETNA
Solar/Wind Harmer
0.077
941821AE2-187 GEN
Solar/Wind Harmer
12.286
971683AH1-343 GEN
Solar/Wind Harmer
4.429
270197AD1-017 GEN1
Solar/Wind Harmer
0.533
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.866
3151561HALLBR1
50/50
0.893
24728405LEESVG
50/50
0.29
24684705SMG5
50/50
0.359
970481AG2-311 GEN
50/50
5.003
3147312GRETNA
Solar/Wind Harmer
0.307
3146802CHATHAM
Solar/Wind Harmer
0.288
941801AE2-185 GEN
Solar/Wind Harmer
12.286
3147123OTTER R
Solar/Wind Harmer
0.203
316003AC1-222 GEN
Solar/Wind Harmer
0.003
270574AD1-017 GEN2
Solar/Wind Harmer
0
270016AE1-250 BESS
Solar/Wind Harmer
0.002
316123AC1-075 GEN
Solar/Wind Harmer
0.271
970165AG2-112 GEN
Solar/Wind Harmer
1.606
970163AG2-111 GEN
Solar/Wind Harmer
1.532
970865AG2-541 GEN
Solar/Wind Harmer
5.06
3147173SINAI
Solar/Wind Harmer
0.067
3147243WELCO
Solar/Wind Harmer
0.042
316118AC1-105 GEN
Solar/Wind Harmer
0.154
24684405SMG2
50/50
0.932
24684505SMG3
50/50
0.577
24684305SMG1
50/50
0.338
3152661PLYWOOD A
50/50
0.134
316217AC1-145 GEN
Solar/Wind Harmer
0.005
316197AC1-042 GEN
Solar/Wind Harmer
0.004
942671AE2-283 GEN
Solar/Wind Harmer
9.556
942751AE2-291 GEN
Solar/Wind Harmer
12.576
270013AE1-250 PV
Solar/Wind Harmer
0.002
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.46
NYPJM->LTFIMP_NY
CLTF
0.027
CPLELTFEXP_CPLE->PJM
CLTF
1.048
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.148
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.456
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.688
GibsonPJM->LTFIMP_GIBSON
CLTF
0

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.33 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:250.71
MW Contribution:6.43
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.198
24684505SMG3
50/50
0.741
24684305SMG1
50/50
0.434
316217AC1-145 GEN
Solar/Wind Harmer
7.301
316197AC1-042 GEN
Solar/Wind Harmer
5.534
942671AE2-283 GEN
Solar/Wind Harmer
14.9
942751AE2-291 GEN
Solar/Wind Harmer
17.168
270013AE1-250 PV
Solar/Wind Harmer
2.392
3151561HALLBR1
50/50
0.931
24728405LEESVG
50/50
0.319
24684705SMG5
50/50
0.461
970481AG2-311 GEN
50/50
6.43
3147312GRETNA
Solar/Wind Harmer
-0.036
3146802CHATHAM
Solar/Wind Harmer
-0.034
941801AE2-185 GEN
Solar/Wind Harmer
16.868
3147123OTTER R
Solar/Wind Harmer
-0.024
270574AD1-017 GEN2
Solar/Wind Harmer
5.39
270016AE1-250 BESS
Solar/Wind Harmer
2.392
970223AG2-152 GEN
Solar/Wind Harmer
13.798
316003AC1-222 GEN
Solar/Wind Harmer
1.06
270173AC1-122 GEN
Solar/Wind Harmer
0.706
24728405LEESVG
50/50
0.32
24684605SMG4
50/50
1.206
3147312GRETNA
Solar/Wind Harmer
-0.009
941821AE2-187 GEN
Solar/Wind Harmer
16.868
270197AD1-017 GEN1
Solar/Wind Harmer
1.62
971683AH1-343 GEN
Solar/Wind Harmer
5.942
316248AF1-058 C
Solar/Wind Harmer
0.225
960061AF2-297 GEN
Solar/Wind Harmer
3.734
316123AC1-075 GEN
Solar/Wind Harmer
2.482
970165AG2-112 GEN
Solar/Wind Harmer
2.186
970163AG2-111 GEN
Solar/Wind Harmer
2.085
970865AG2-541 GEN
Solar/Wind Harmer
6.833
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.005
316118AC1-105 GEN
Solar/Wind Harmer
0.454
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.539
NYPJM->LTFIMP_NY
CLTF
0.033
CPLELTFEXP_CPLE->PJM
CLTF
0.729
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.153
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.471
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.072
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o AEP_P7-1_#10778___SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10778___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.33 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:250.7
MW Contribution:6.43
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.32
24684605SMG4
50/50
1.206
3147312GRETNA
Solar/Wind Harmer
-0.009
941821AE2-187 GEN
Solar/Wind Harmer
16.868
270197AD1-017 GEN1
Solar/Wind Harmer
1.62
971683AH1-343 GEN
Solar/Wind Harmer
5.942
316248AF1-058 C
Solar/Wind Harmer
0.225
960061AF2-297 GEN
Solar/Wind Harmer
3.734
3151561HALLBR1
50/50
0.931
24728405LEESVG
50/50
0.319
24684705SMG5
50/50
0.461
970481AG2-311 GEN
50/50
6.43
3147312GRETNA
Solar/Wind Harmer
-0.036
3146802CHATHAM
Solar/Wind Harmer
-0.034
941801AE2-185 GEN
Solar/Wind Harmer
16.868
3147123OTTER R
Solar/Wind Harmer
-0.024
270574AD1-017 GEN2
Solar/Wind Harmer
5.39
270016AE1-250 BESS
Solar/Wind Harmer
2.392
970223AG2-152 GEN
Solar/Wind Harmer
13.798
316003AC1-222 GEN
Solar/Wind Harmer
1.06
270173AC1-122 GEN
Solar/Wind Harmer
0.706
316123AC1-075 GEN
Solar/Wind Harmer
2.482
970165AG2-112 GEN
Solar/Wind Harmer
2.186
970163AG2-111 GEN
Solar/Wind Harmer
2.085
970865AG2-541 GEN
Solar/Wind Harmer
6.833
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.005
316118AC1-105 GEN
Solar/Wind Harmer
0.454
24684405SMG2
50/50
1.198
24684505SMG3
50/50
0.741
24684305SMG1
50/50
0.434
316217AC1-145 GEN
Solar/Wind Harmer
7.301
316197AC1-042 GEN
Solar/Wind Harmer
5.534
942671AE2-283 GEN
Solar/Wind Harmer
14.9
942751AE2-291 GEN
Solar/Wind Harmer
17.168
270013AE1-250 PV
Solar/Wind Harmer
2.392
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.539
NYPJM->LTFIMP_NY
CLTF
0.033
CPLELTFEXP_CPLE->PJM
CLTF
0.729
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.153
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.471
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.072
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 4ALTVSTA-05OTTER 138.0 kV Ckt 1 line l/o DVP_P2-2: ALTAVISTA 115KV_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
4ALTVSTA-05OTTER 138.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: ALTAVISTA 115KV_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.22 %
Rating:245.0 MVA
Rating Type:B
MVA to Mitigate:247.98
MW Contribution:7.7
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.434
24684505SMG3
50/50
0.887
24684305SMG1
50/50
0.52
316217AC1-145 GEN
Solar/Wind Harmer
9.919
316197AC1-042 GEN
Solar/Wind Harmer
7.519
942671AE2-283 GEN
Solar/Wind Harmer
20.244
270013AE1-250 PV
Solar/Wind Harmer
1.533
24728405LEESVG
50/50
0.419
24684705SMG5
50/50
0.552
970481AG2-311 GEN
50/50
7.695
3147312GRETNA
Solar/Wind Harmer
-0.049
3146802CHATHAM
Solar/Wind Harmer
-0.046
941801AE2-185 GEN
Solar/Wind Harmer
22.918
270574AD1-017 GEN2
Solar/Wind Harmer
4.731
270016AE1-250 BESS
Solar/Wind Harmer
1.533
270173AC1-122 GEN
Solar/Wind Harmer
0.968
970223AG2-152 GEN
Solar/Wind Harmer
7.548
24728405LEESVG
50/50
0.421
24684605SMG4
50/50
1.443
3147312GRETNA
Solar/Wind Harmer
-0.012
941821AE2-187 GEN
Solar/Wind Harmer
22.918
270197AD1-017 GEN1
Solar/Wind Harmer
1.422
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.099
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.056
NYPJM->LTFIMP_NY
CLTF
0.054
CPLELTFEXP_CPLE->PJM
CLTF
0.586
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.047
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.144
LAGNLTFEXP_LAGN->PJM
CLTF
0.083
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.044
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.034

Details for 4ALTVSTA-3ALTVSTA 138.0/115.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
4ALTVSTA-3ALTVSTA 138.0/115.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-3: 4ALTVSTA-TX#4_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.36 %
Rating:123.7 MVA
Rating Type:B
MVA to Mitigate:132.8
MW Contribution:4.91
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
0.915
24684505SMG3
50/50
0.566
24684305SMG1
50/50
0.332
316217AC1-145 GEN
Solar/Wind Harmer
0.004
316197AC1-042 GEN
Solar/Wind Harmer
0.003
942671AE2-283 GEN
Solar/Wind Harmer
7.171
3146843MT LREL
Solar/Wind Helper
0.18
3146843MT LREL
Solar/Wind Helper
0.18
24728405LEESVG
50/50
0.234
24684605SMG4
50/50
0.921
3147312GRETNA
Solar/Wind Harmer
0.058
941821AE2-187 GEN
Solar/Wind Harmer
9.22
270197AD1-017 GEN1
Solar/Wind Harmer
0.483
316248AF1-058 C
Solar/Wind Helper
0.315
24728405LEESVG
50/50
0.233
24684705SMG5
50/50
0.352
970481AG2-311 GEN
50/50
4.913
3147312GRETNA
Solar/Wind Harmer
0.23
3146802CHATHAM
Solar/Wind Harmer
0.216
941801AE2-185 GEN
Solar/Wind Harmer
9.22
270173AC1-122 GEN
Solar/Wind Harmer
0.21
270574AD1-017 GEN2
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Helper
0.768
316003AC1-222 GEN
Solar/Wind Helper
1.495
316123AC1-075 GEN
Solar/Wind Helper
4.504
3147173SINAI
Solar/Wind Helper
0.235
3147243WELCO
Solar/Wind Helper
0.147
316118AC1-105 GEN
Solar/Wind Helper
0.806
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.127
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.85
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.65
MECLTFEXP_MEC->PJM
CLTF
0.411
SIGELTFEXP_SIGE->PJM
CLTF
0.015
NYPJM->LTFIMP_NY
CLTF
0.049
LGEELTFEXP_LGEE->PJM
CLTF
0.208
WECLTFEXP_WEC->PJM
CLTF
0.103
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.41
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.529
LAGNLTFEXP_LAGN->PJM
CLTF
0.239
TVALTFEXP_TVA->PJM
CLTF
0.145

Details for 6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.64 %
Rating:814.98 MVA
Rating Type:B
MVA to Mitigate:885.41
MW Contribution:4.59
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.138
24684605SMG4
50/50
0.862
24288905REUSENS
50/50
0.013
316248AF1-058 C
Solar/Wind Harmer
0.003
960061AF2-297 GEN
Solar/Wind Harmer
16.042
971683AH1-343 GEN
Solar/Wind Harmer
12.22
316283AC2-100 C
Solar/Wind Harmer
0.523
970917AG2-570 GEN
Solar/Wind Harmer
12.67
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.18
270197AD1-017 GEN1
Solar/Wind Harmer
0.766
270018AE2-047 C O1
Solar/Wind Harmer
0.002
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.003
971367AH1-164 GEN
Solar/Wind Harmer
1.353
961601AG1-000A GEN
Solar/Wind Harmer
4.498
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
316478AD1-087 GEN
Solar/Wind Helper
3.07
316486AD2-202 GEN
Solar/Wind Helper
0.899
3146926FARMVIL
Solar/Wind Helper
0.144
3146776BUCKING
Solar/Wind Helper
0.069
315773AC2-141 GEN
Solar/Wind Helper
3.58
942461AE2-259 GEN
Solar/Wind Helper
1.12
3144873MCLAUGH
Solar/Wind Helper
0.004
3144536CHRHLND
Solar/Wind Helper
0.023
315839AE2-212 C
Solar/Wind Helper
0.202
3145336SMITFLD
Solar/Wind Helper
0.059
3152661PLYWOOD A
50/50
0.687
24684405SMG2
50/50
0.856
24684505SMG3
50/50
0.529
24684305SMG1
50/50
0.31
316222AC1-221 GEN
Solar/Wind Harmer
1.136
942751AE2-291 GEN
Solar/Wind Harmer
13.086
3146843MT LREL
Solar/Wind Harmer
0.235
3146843MT LREL
Solar/Wind Harmer
0.235
964791AG1-342 GEN
Solar/Wind Harmer
4.482
962561AG1-105 GEN
Solar/Wind Harmer
9.757
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.251
270013AE1-250 PV
Solar/Wind Harmer
0.004
961601AG1-000A GEN
Solar/Wind Harmer
1.124
316263AC1-034 GEN
Solar/Wind Harmer
2.389
3146776BUCKING
Solar/Wind Helper
0.771
3146776BUCKING
Solar/Wind Helper
0.062
316036AC1-147 C
Solar/Wind Helper
0.232
3142956BIRDNECK
Solar/Wind Helper
0.102
316316AC1-027 C
Solar/Wind Helper
0.238
316185AD1-033 GEN
Solar/Wind Helper
0.706
316236AE1-162_GEN
Solar/Wind Helper
0.2
3145506HICKORY
Solar/Wind Helper
0.591
3145506HICKORY
Solar/Wind Helper
0.355
3145506HICKORY
Solar/Wind Helper
0.089
316240AF1-291 C
Solar/Wind Helper
0.195
316339AD2-160 GEN
Solar/Wind Helper
0.548
316033AB2-134 GEN
Solar/Wind Helper
0.494
315697AD1-025 GEN
Solar/Wind Helper
1.643
316018AA1-139 ULT2
Solar/Wind Helper
0.614
316017AA1-139 ULT1
Solar/Wind Helper
0.652
3137176SLIGO L2192
Solar/Wind Helper
0.561
3130086AYDLETT
Solar/Wind Helper
0.556
3143526WINTERP
Solar/Wind Helper
0.708
3142946ENON
Solar/Wind Helper
0.013
316075AC2-137 C
Solar/Wind Helper
0.198
316487AF1-042 GEN
Solar/Wind Helper
0.131
3146386ELIZ CT
Solar/Wind Helper
0.129
3144356SAPONY
Solar/Wind Helper
0.23
316077AC2-138 C
Solar/Wind Helper
0.118
966871AG1-558 GEN
Solar/Wind Helper
0.162
316431W1029_GEN1
Solar/Wind Helper
0.477
316433W1029_GEN2
Solar/Wind Helper
0.477
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
316468AD1-105 GEN
Solar/Wind Helper
0.559
316382AG1-145 C
Solar/Wind Helper
0.191
3146456SLIGO L269
Solar/Wind Helper
0.141
316313AB2-026
Solar/Wind Helper
0.21
316258AE1-075 C
Solar/Wind Helper
0.189
316405AF2-144 C
Solar/Wind Helper
0.157
316156AD2-030 GEN
Solar/Wind Helper
0.203
316280AD1-041 GEN
Solar/Wind Helper
0.451
3142946ENON
Solar/Wind Helper
0.045
316484AD2-074 GEN
Solar/Wind Helper
0.25
316320Y1-086
Solar/Wind Helper
0.058
316404AE1-155 C
Solar/Wind Helper
1.083
316473AC1-191 GEN
Solar/Wind Helper
0.734
3141906WESTMOR
Solar/Wind Helper
0.047
316435W1029_GEN3
Solar/Wind Helper
0.477
3146516WINFALL
Solar/Wind Helper
0.115
3147173SINAI
Solar/Wind Harmer
0.376
3147243WELCO
Solar/Wind Harmer
0.235
970865AG2-541 GEN
Solar/Wind Harmer
10.778
316118AC1-105 GEN
Solar/Wind Harmer
0.789
316123AC1-075 GEN
Solar/Wind Harmer
0.366
970165AG2-112 GEN
Solar/Wind Harmer
2.171
970163AG2-111 GEN
Solar/Wind Harmer
2.071
970085AG2-068 GEN
Solar/Wind Harmer
7.603
970581AG2-369 GEN
Solar/Wind Harmer
6.538
270069AE2-166 C O1
Solar/Wind Harmer
0.003
971981AH1-535 GEN
Solar/Wind Harmer
2.177
3143316POE
Solar/Wind Helper
0.626
316369SG1_INVT
Solar/Wind Helper
0.691
316132AB2-190 GEN1
Solar/Wind Helper
0.815
957831AF2-077 GEN
Solar/Wind Helper
0.189
319010AE1-072 C
Solar/Wind Helper
1.597
316305AF2-043 C
Solar/Wind Helper
0.186
316349AD2-085 GEN
Solar/Wind Helper
0.628
316233AE1-074 FULL
Solar/Wind Helper
0.208
957601AF2-054 GEN
Solar/Wind Helper
0.18
3141873WAN 176
Solar/Wind Helper
0.027
315662AE1-191 GEN
Solar/Wind Helper
0.721
315666AE1-190 GEN
Solar/Wind Helper
0.18
3143873LANEXA
Solar/Wind Helper
0.08
316059AD1-063 C
Solar/Wind Helper
0.135
3141913WHIT STONE
Solar/Wind Helper
0.133
3138133OCRAN
Solar/Wind Helper
0.04
3141783LANCAST
Solar/Wind Helper
0.079
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.196
3146486SUNBURY
Solar/Wind Helper
0.126
3146486SUNBURY
Solar/Wind Helper
0.126
3141813NORNECK
Solar/Wind Helper
0.126
316312AB1-027
Solar/Wind Helper
0.238
316321Z2-027
Solar/Wind Helper
0.19
3145176PASQUOTANK
Solar/Wind Helper
0.077
316223AC1-118
Solar/Wind Helper
0.181
971629AH1-314 GEN
50/50
13.578
3151561HALLBR1
50/50
0.376
24728405LEESVG
50/50
0.138
970417AG2-272 GEN
50/50
1.899
24684705SMG5
50/50
0.33
970481AG2-311 GEN
50/50
4.594
315687AD1-152 GEN
Solar/Wind Harmer
0.022
316003AC1-222 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.37
3147123OTTER R
Solar/Wind Harmer
0.091
970087AG2-069 GEN
Solar/Wind Harmer
11.404
970919AG2-571 GEN
Solar/Wind Harmer
5.068
970223AG2-152 GEN
Solar/Wind Harmer
9.437
3147312GRETNA
Solar/Wind Harmer
0.104
3146802CHATHAM
Solar/Wind Harmer
0.098
941801AE2-185 GEN
Solar/Wind Harmer
4.18
270016AE1-250 BESS
Solar/Wind Harmer
0.004
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270030AE2-140 GEN
Solar/Wind Harmer
10.396
270173AC1-122 GEN
Solar/Wind Harmer
0.217
316359AB2-059 GEN
Solar/Wind Harmer
0.226
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3142053HEARTS
Solar/Wind Harmer
0.111
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
3146926FARMVIL
Solar/Wind Helper
0.144
316322AB2-045
Solar/Wind Helper
0.215
3146776BUCKING
Solar/Wind Helper
0.077
316294AC1-161 GEN
Solar/Wind Helper
3.041
316375AC2-012 GEN
Solar/Wind Helper
0.399
3145336SMITFLD
Solar/Wind Helper
0.594
316381AD1-082 GEN
Solar/Wind Helper
0.747
316388AE2-253 GEN
Solar/Wind Helper
0.548
316458AB2-190 GEN2
Solar/Wind Helper
0.815
316159AE1-175 C
Solar/Wind Helper
0.215
3146456SLIGO L269
Solar/Wind Helper
0.141
316072AD1-144
Solar/Wind Helper
0.16
3143226MDLTHAN
Solar/Wind Helper
0.139
316246AF1-032 C
Solar/Wind Helper
0.159
316336AC2-165 C
Solar/Wind Helper
0.741
3143526WINTERP
Solar/Wind Helper
0.708
3142543TWELFTH
Solar/Wind Helper
0.013
3142433PROV 92
Solar/Wind Helper
0.538
3141766HARMONY
Solar/Wind Helper
0.027
3138133OCRAN
Solar/Wind Helper
0.08
964211AG1-282 GEN
Solar/Wind Helper
0.17
3141726DUNNSVL
Solar/Wind Helper
0.505
3142416OLDCHRC
Solar/Wind Helper
0.325
3142416OLDCHRC
Solar/Wind Helper
0.124
316337AD2-073 GEN
Solar/Wind Helper
0.185
3146516WINFALL
Solar/Wind Helper
0.373
3146516WINFALL
Solar/Wind Helper
0.115
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.18
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.424
MECLTFEXP_MEC->PJM
CLTF
5.352
SIGELTFEXP_SIGE->PJM
CLTF
0.163
NYPJM->LTFIMP_NY
CLTF
0.706
LGEELTFEXP_LGEE->PJM
CLTF
2.033
WECLTFEXP_WEC->PJM
CLTF
1.077
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.091
CPLELTFEXP_CPLE->PJM
CLTF
11.235
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.568
LAGNLTFEXP_LAGN->PJM
CLTF
9.357
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.525
TVALTFEXP_TVA->PJM
CLTF
4.684

Details for 6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.47 %
Rating:814.98 MVA
Rating Type:B
MVA to Mitigate:867.67
MW Contribution:4.59
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
0.687
24684405SMG2
50/50
0.856
24684505SMG3
50/50
0.529
24684305SMG1
50/50
0.31
316222AC1-221 GEN
Solar/Wind Harmer
1.136
942751AE2-291 GEN
Solar/Wind Harmer
13.086
3146843MT LREL
Solar/Wind Harmer
0.235
3146843MT LREL
Solar/Wind Harmer
0.235
964791AG1-342 GEN
Solar/Wind Harmer
4.482
962561AG1-105 GEN
Solar/Wind Harmer
9.757
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.251
270013AE1-250 PV
Solar/Wind Harmer
0.004
961601AG1-000A GEN
Solar/Wind Harmer
1.124
316263AC1-034 GEN
Solar/Wind Harmer
2.389
3146776BUCKING
Solar/Wind Helper
0.771
3146776BUCKING
Solar/Wind Helper
0.062
316036AC1-147 C
Solar/Wind Helper
0.232
3142956BIRDNECK
Solar/Wind Helper
0.102
316316AC1-027 C
Solar/Wind Helper
0.238
316185AD1-033 GEN
Solar/Wind Helper
0.706
316236AE1-162_GEN
Solar/Wind Helper
0.2
3145506HICKORY
Solar/Wind Helper
0.591
3145506HICKORY
Solar/Wind Helper
0.355
3145506HICKORY
Solar/Wind Helper
0.089
316240AF1-291 C
Solar/Wind Helper
0.195
316339AD2-160 GEN
Solar/Wind Helper
0.548
316033AB2-134 GEN
Solar/Wind Helper
0.494
315697AD1-025 GEN
Solar/Wind Helper
1.643
316018AA1-139 ULT2
Solar/Wind Helper
0.614
316017AA1-139 ULT1
Solar/Wind Helper
0.652
3137176SLIGO L2192
Solar/Wind Helper
0.561
3130086AYDLETT
Solar/Wind Helper
0.556
3143526WINTERP
Solar/Wind Helper
0.708
3142946ENON
Solar/Wind Helper
0.013
316075AC2-137 C
Solar/Wind Helper
0.198
316487AF1-042 GEN
Solar/Wind Helper
0.131
3146386ELIZ CT
Solar/Wind Helper
0.129
3144356SAPONY
Solar/Wind Helper
0.23
316077AC2-138 C
Solar/Wind Helper
0.118
966871AG1-558 GEN
Solar/Wind Helper
0.162
316431W1029_GEN1
Solar/Wind Helper
0.477
316433W1029_GEN2
Solar/Wind Helper
0.477
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
316468AD1-105 GEN
Solar/Wind Helper
0.559
24728405LEESVG
50/50
0.138
24684605SMG4
50/50
0.862
24288905REUSENS
50/50
0.013
316248AF1-058 C
Solar/Wind Harmer
0.003
960061AF2-297 GEN
Solar/Wind Harmer
16.042
971683AH1-343 GEN
Solar/Wind Harmer
12.22
316283AC2-100 C
Solar/Wind Harmer
0.523
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.18
270197AD1-017 GEN1
Solar/Wind Harmer
0.766
270018AE2-047 C O1
Solar/Wind Harmer
0.002
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.003
971367AH1-164 GEN
Solar/Wind Harmer
1.353
961601AG1-000A GEN
Solar/Wind Harmer
4.498
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
316478AD1-087 GEN
Solar/Wind Helper
3.07
316486AD2-202 GEN
Solar/Wind Helper
0.899
3146926FARMVIL
Solar/Wind Helper
0.144
3146776BUCKING
Solar/Wind Helper
0.069
315773AC2-141 GEN
Solar/Wind Helper
3.58
942461AE2-259 GEN
Solar/Wind Helper
1.12
3144873MCLAUGH
Solar/Wind Helper
0.004
3144536CHRHLND
Solar/Wind Helper
0.023
315839AE2-212 C
Solar/Wind Helper
0.202
3145336SMITFLD
Solar/Wind Helper
0.059
316382AG1-145 C
Solar/Wind Helper
0.191
3146456SLIGO L269
Solar/Wind Helper
0.141
316313AB2-026
Solar/Wind Helper
0.21
316258AE1-075 C
Solar/Wind Helper
0.189
316405AF2-144 C
Solar/Wind Helper
0.157
316156AD2-030 GEN
Solar/Wind Helper
0.203
316280AD1-041 GEN
Solar/Wind Helper
0.451
3142946ENON
Solar/Wind Helper
0.045
316484AD2-074 GEN
Solar/Wind Helper
0.25
316320Y1-086
Solar/Wind Helper
0.058
316404AE1-155 C
Solar/Wind Helper
1.083
316473AC1-191 GEN
Solar/Wind Helper
0.734
3141906WESTMOR
Solar/Wind Helper
0.047
316435W1029_GEN3
Solar/Wind Helper
0.477
3146516WINFALL
Solar/Wind Helper
0.115
971629AH1-314 GEN
50/50
13.578
3151561HALLBR1
50/50
0.376
24728405LEESVG
50/50
0.138
970417AG2-272 GEN
50/50
1.899
24684705SMG5
50/50
0.33
970481AG2-311 GEN
50/50
4.594
315687AD1-152 GEN
Solar/Wind Harmer
0.022
316003AC1-222 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.37
3147123OTTER R
Solar/Wind Harmer
0.091
970087AG2-069 GEN
Solar/Wind Harmer
11.404
970223AG2-152 GEN
Solar/Wind Harmer
9.437
3147312GRETNA
Solar/Wind Harmer
0.104
3146802CHATHAM
Solar/Wind Harmer
0.098
941801AE2-185 GEN
Solar/Wind Harmer
4.18
270016AE1-250 BESS
Solar/Wind Harmer
0.004
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270030AE2-140 GEN
Solar/Wind Harmer
10.396
270173AC1-122 GEN
Solar/Wind Harmer
0.217
316359AB2-059 GEN
Solar/Wind Harmer
0.226
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3142053HEARTS
Solar/Wind Harmer
0.111
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
3146926FARMVIL
Solar/Wind Helper
0.144
316322AB2-045
Solar/Wind Helper
0.215
3146776BUCKING
Solar/Wind Helper
0.077
316294AC1-161 GEN
Solar/Wind Helper
3.041
316375AC2-012 GEN
Solar/Wind Helper
0.399
3145336SMITFLD
Solar/Wind Helper
0.594
316381AD1-082 GEN
Solar/Wind Helper
0.747
316388AE2-253 GEN
Solar/Wind Helper
0.548
316458AB2-190 GEN2
Solar/Wind Helper
0.815
316159AE1-175 C
Solar/Wind Helper
0.215
3146456SLIGO L269
Solar/Wind Helper
0.141
316072AD1-144
Solar/Wind Helper
0.16
3143226MDLTHAN
Solar/Wind Helper
0.139
316246AF1-032 C
Solar/Wind Helper
0.159
316336AC2-165 C
Solar/Wind Helper
0.741
3143526WINTERP
Solar/Wind Helper
0.708
3142543TWELFTH
Solar/Wind Helper
0.013
3142433PROV 92
Solar/Wind Helper
0.538
3141766HARMONY
Solar/Wind Helper
0.027
3138133OCRAN
Solar/Wind Helper
0.08
964211AG1-282 GEN
Solar/Wind Helper
0.17
3141726DUNNSVL
Solar/Wind Helper
0.505
3142416OLDCHRC
Solar/Wind Helper
0.325
3142416OLDCHRC
Solar/Wind Helper
0.124
316337AD2-073 GEN
Solar/Wind Helper
0.185
3146516WINFALL
Solar/Wind Helper
0.373
3146516WINFALL
Solar/Wind Helper
0.115
3147173SINAI
Solar/Wind Harmer
0.376
3147243WELCO
Solar/Wind Harmer
0.235
970865AG2-541 GEN
Solar/Wind Harmer
10.778
316118AC1-105 GEN
Solar/Wind Harmer
0.789
316123AC1-075 GEN
Solar/Wind Harmer
0.366
970165AG2-112 GEN
Solar/Wind Harmer
2.171
970163AG2-111 GEN
Solar/Wind Harmer
2.071
970085AG2-068 GEN
Solar/Wind Harmer
7.603
970581AG2-369 GEN
Solar/Wind Harmer
6.538
270069AE2-166 C O1
Solar/Wind Harmer
0.003
971981AH1-535 GEN
Solar/Wind Harmer
2.177
3143316POE
Solar/Wind Helper
0.626
316369SG1_INVT
Solar/Wind Helper
0.691
316132AB2-190 GEN1
Solar/Wind Helper
0.815
957831AF2-077 GEN
Solar/Wind Helper
0.189
319010AE1-072 C
Solar/Wind Helper
1.597
316305AF2-043 C
Solar/Wind Helper
0.186
316349AD2-085 GEN
Solar/Wind Helper
0.628
316233AE1-074 FULL
Solar/Wind Helper
0.208
957601AF2-054 GEN
Solar/Wind Helper
0.18
3141873WAN 176
Solar/Wind Helper
0.027
315662AE1-191 GEN
Solar/Wind Helper
0.721
315666AE1-190 GEN
Solar/Wind Helper
0.18
3143873LANEXA
Solar/Wind Helper
0.08
316059AD1-063 C
Solar/Wind Helper
0.135
3141913WHIT STONE
Solar/Wind Helper
0.133
3138133OCRAN
Solar/Wind Helper
0.04
3141783LANCAST
Solar/Wind Helper
0.079
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.196
3146486SUNBURY
Solar/Wind Helper
0.126
3146486SUNBURY
Solar/Wind Helper
0.126
3141813NORNECK
Solar/Wind Helper
0.126
316312AB1-027
Solar/Wind Helper
0.238
316321Z2-027
Solar/Wind Helper
0.19
3145176PASQUOTANK
Solar/Wind Helper
0.077
316223AC1-118
Solar/Wind Helper
0.181
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.18
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.424
MECLTFEXP_MEC->PJM
CLTF
5.352
SIGELTFEXP_SIGE->PJM
CLTF
0.163
NYPJM->LTFIMP_NY
CLTF
0.706
LGEELTFEXP_LGEE->PJM
CLTF
2.033
WECLTFEXP_WEC->PJM
CLTF
1.077
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.091
CPLELTFEXP_CPLE->PJM
CLTF
11.235
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.568
LAGNLTFEXP_LAGN->PJM
CLTF
9.357
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.525
TVALTFEXP_TVA->PJM
CLTF
4.684

Details for 6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.53 %
Rating:814.98 MVA
Rating Type:B
MVA to Mitigate:843.75
MW Contribution:4.61
Bus #Bus NameTypeMW Contribution
971629AH1-314 GEN
50/50
13.606
3151561HALLBR1
50/50
0.377
24728405LEESVG
50/50
0.138
970417AG2-272 GEN
50/50
1.905
24684705SMG5
50/50
0.331
970481AG2-311 GEN
50/50
4.609
316003AC1-222 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.371
3147123OTTER R
Solar/Wind Harmer
0.091
970087AG2-069 GEN
Solar/Wind Harmer
11.429
970919AG2-571 GEN
Solar/Wind Harmer
5.079
970223AG2-152 GEN
Solar/Wind Harmer
9.459
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.098
941801AE2-185 GEN
Solar/Wind Harmer
4.19
270016AE1-250 BESS
Solar/Wind Harmer
0.004
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270030AE2-140 GEN
Solar/Wind Harmer
10.43
270173AC1-122 GEN
Solar/Wind Harmer
0.218
316359AB2-059 GEN
Solar/Wind Harmer
0.227
316049AB1-081 GEN
Solar/Wind Harmer
0.362
3142053HEARTS
Solar/Wind Harmer
0.111
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
315687AD1-152 GEN
Solar/Wind Helper
4.927
3146926FARMVIL
Solar/Wind Helper
0.143
24728405LEESVG
50/50
0.138
24684605SMG4
50/50
0.864
24288905REUSENS
50/50
0.013
316248AF1-058 C
Solar/Wind Harmer
0.003
960061AF2-297 GEN
Solar/Wind Harmer
16.056
971683AH1-343 GEN
Solar/Wind Harmer
12.232
316283AC2-100 C
Solar/Wind Harmer
0.524
970917AG2-570 GEN
Solar/Wind Harmer
12.699
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.19
270197AD1-017 GEN1
Solar/Wind Harmer
0.768
270018AE2-047 C O1
Solar/Wind Harmer
0.002
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.003
971367AH1-164 GEN
Solar/Wind Harmer
1.359
961601AG1-000A GEN
Solar/Wind Harmer
4.52
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
316478AD1-087 GEN
Solar/Wind Helper
3.067
316486AD2-202 GEN
Solar/Wind Helper
0.898
3146926FARMVIL
Solar/Wind Helper
0.143
3146776BUCKING
Solar/Wind Helper
0.069
315773AC2-141 GEN
Solar/Wind Helper
3.566
942461AE2-259 GEN
Solar/Wind Helper
1.116
3144873MCLAUGH
Solar/Wind Helper
0.004
3144536CHRHLND
Solar/Wind Helper
0.023
315839AE2-212 C
Solar/Wind Helper
0.201
3145336SMITFLD
Solar/Wind Helper
0.059
316382AG1-145 C
Solar/Wind Helper
0.19
3146456SLIGO L269
Solar/Wind Helper
0.14
316313AB2-026
Solar/Wind Helper
0.209
316258AE1-075 C
Solar/Wind Helper
0.188
316405AF2-144 C
Solar/Wind Helper
0.157
316156AD2-030 GEN
Solar/Wind Helper
0.202
316280AD1-041 GEN
Solar/Wind Helper
0.449
3142946ENON
Solar/Wind Helper
0.045
316484AD2-074 GEN
Solar/Wind Helper
0.249
316320Y1-086
Solar/Wind Helper
0.057
316404AE1-155 C
Solar/Wind Helper
1.078
316473AC1-191 GEN
Solar/Wind Helper
0.73
3141906WESTMOR
Solar/Wind Helper
0.047
316435W1029_GEN3
Solar/Wind Helper
0.474
3146516WINFALL
Solar/Wind Helper
0.115
316322AB2-045
Solar/Wind Helper
0.214
3146776BUCKING
Solar/Wind Helper
0.077
316294AC1-161 GEN
Solar/Wind Helper
3.03
316375AC2-012 GEN
Solar/Wind Helper
0.398
3145336SMITFLD
Solar/Wind Helper
0.592
316381AD1-082 GEN
Solar/Wind Helper
0.744
316388AE2-253 GEN
Solar/Wind Helper
0.545
316458AB2-190 GEN2
Solar/Wind Helper
0.811
316159AE1-175 C
Solar/Wind Helper
0.214
3146456SLIGO L269
Solar/Wind Helper
0.14
316072AD1-144
Solar/Wind Helper
0.16
3143226MDLTHAN
Solar/Wind Helper
0.138
316246AF1-032 C
Solar/Wind Helper
0.158
316336AC2-165 C
Solar/Wind Helper
0.738
3143526WINTERP
Solar/Wind Helper
0.705
3142543TWELFTH
Solar/Wind Helper
0.013
3142433PROV 92
Solar/Wind Helper
0.535
3141766HARMONY
Solar/Wind Helper
0.027
3138133OCRAN
Solar/Wind Helper
0.079
964211AG1-282 GEN
Solar/Wind Helper
0.169
3141726DUNNSVL
Solar/Wind Helper
0.503
3142416OLDCHRC
Solar/Wind Helper
0.323
3142416OLDCHRC
Solar/Wind Helper
0.124
316337AD2-073 GEN
Solar/Wind Helper
0.184
3146516WINFALL
Solar/Wind Helper
0.371
3146516WINFALL
Solar/Wind Helper
0.115
3147173SINAI
Solar/Wind Harmer
0.376
3147243WELCO
Solar/Wind Harmer
0.235
970865AG2-541 GEN
Solar/Wind Harmer
10.789
316118AC1-105 GEN
Solar/Wind Harmer
0.79
316123AC1-075 GEN
Solar/Wind Harmer
0.367
970165AG2-112 GEN
Solar/Wind Harmer
2.174
970163AG2-111 GEN
Solar/Wind Harmer
2.074
970085AG2-068 GEN
Solar/Wind Harmer
7.62
970581AG2-369 GEN
Solar/Wind Harmer
6.553
270069AE2-166 C O1
Solar/Wind Harmer
0.003
971981AH1-535 GEN
Solar/Wind Harmer
2.189
3143316POE
Solar/Wind Helper
0.623
316369SG1_INVT
Solar/Wind Helper
0.688
316132AB2-190 GEN1
Solar/Wind Helper
0.811
957831AF2-077 GEN
Solar/Wind Helper
0.188
319010AE1-072 C
Solar/Wind Helper
1.59
316305AF2-043 C
Solar/Wind Helper
0.186
316349AD2-085 GEN
Solar/Wind Helper
0.625
316233AE1-074 FULL
Solar/Wind Helper
0.207
957601AF2-054 GEN
Solar/Wind Helper
0.179
3141873WAN 176
Solar/Wind Helper
0.027
315662AE1-191 GEN
Solar/Wind Helper
0.718
315666AE1-190 GEN
Solar/Wind Helper
0.179
3143873LANEXA
Solar/Wind Helper
0.08
316059AD1-063 C
Solar/Wind Helper
0.134
3141913WHIT STONE
Solar/Wind Helper
0.132
3138133OCRAN
Solar/Wind Helper
0.04
3141783LANCAST
Solar/Wind Helper
0.079
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.196
316315AB2-025 C
Solar/Wind Helper
0.195
3146486SUNBURY
Solar/Wind Helper
0.126
3146486SUNBURY
Solar/Wind Helper
0.126
3141813NORNECK
Solar/Wind Helper
0.125
316312AB1-027
Solar/Wind Helper
0.236
316321Z2-027
Solar/Wind Helper
0.189
3145176PASQUOTANK
Solar/Wind Helper
0.077
316223AC1-118
Solar/Wind Helper
0.18
3152661PLYWOOD A
50/50
0.688
24684405SMG2
50/50
0.859
24684505SMG3
50/50
0.531
24684305SMG1
50/50
0.311
316222AC1-221 GEN
Solar/Wind Harmer
1.137
942751AE2-291 GEN
Solar/Wind Harmer
13.103
3146843MT LREL
Solar/Wind Harmer
0.235
3146843MT LREL
Solar/Wind Harmer
0.235
964791AG1-342 GEN
Solar/Wind Harmer
4.488
962561AG1-105 GEN
Solar/Wind Harmer
9.772
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.259
270013AE1-250 PV
Solar/Wind Harmer
0.004
961601AG1-000A GEN
Solar/Wind Harmer
1.13
316263AC1-034 GEN
Solar/Wind Harmer
2.401
3146776BUCKING
Solar/Wind Helper
0.769
3146776BUCKING
Solar/Wind Helper
0.062
316036AC1-147 C
Solar/Wind Helper
0.231
316316AC1-027 C
Solar/Wind Helper
0.237
3142956BIRDNECK
Solar/Wind Helper
0.101
316185AD1-033 GEN
Solar/Wind Helper
0.703
316236AE1-162_GEN
Solar/Wind Helper
0.199
3145506HICKORY
Solar/Wind Helper
0.589
3145506HICKORY
Solar/Wind Helper
0.353
3145506HICKORY
Solar/Wind Helper
0.088
316240AF1-291 C
Solar/Wind Helper
0.194
316339AD2-160 GEN
Solar/Wind Helper
0.545
316033AB2-134 GEN
Solar/Wind Helper
0.492
315697AD1-025 GEN
Solar/Wind Helper
1.636
316018AA1-139 ULT2
Solar/Wind Helper
0.611
316017AA1-139 ULT1
Solar/Wind Helper
0.649
3137176SLIGO L2192
Solar/Wind Helper
0.558
3130086AYDLETT
Solar/Wind Helper
0.554
3143526WINTERP
Solar/Wind Helper
0.705
3142946ENON
Solar/Wind Helper
0.013
316075AC2-137 C
Solar/Wind Helper
0.197
316487AF1-042 GEN
Solar/Wind Helper
0.13
3146386ELIZ CT
Solar/Wind Helper
0.129
3144356SAPONY
Solar/Wind Helper
0.229
316077AC2-138 C
Solar/Wind Helper
0.118
966871AG1-558 GEN
Solar/Wind Helper
0.161
316431W1029_GEN1
Solar/Wind Helper
0.474
316433W1029_GEN2
Solar/Wind Helper
0.474
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
316468AD1-105 GEN
Solar/Wind Helper
0.556
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.537
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.517
MECLTFEXP_MEC->PJM
CLTF
5.393
SIGELTFEXP_SIGE->PJM
CLTF
0.165
NYPJM->LTFIMP_NY
CLTF
0.69
LGEELTFEXP_LGEE->PJM
CLTF
2.05
WECLTFEXP_WEC->PJM
CLTF
1.087
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.092
CPLELTFEXP_CPLE->PJM
CLTF
11.262
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.898
LAGNLTFEXP_LAGN->PJM
CLTF
9.406
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.599
TVALTFEXP_TVA->PJM
CLTF
4.709

Details for 6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.35 %
Rating:814.98 MVA
Rating Type:B
MVA to Mitigate:825.97
MW Contribution:4.61
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.138
24684605SMG4
50/50
0.864
24288905REUSENS
50/50
0.013
316248AF1-058 C
Solar/Wind Harmer
0.003
960061AF2-297 GEN
Solar/Wind Harmer
16.056
971683AH1-343 GEN
Solar/Wind Harmer
12.232
316283AC2-100 C
Solar/Wind Harmer
0.524
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.19
270197AD1-017 GEN1
Solar/Wind Harmer
0.768
270018AE2-047 C O1
Solar/Wind Harmer
0.002
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.003
971367AH1-164 GEN
Solar/Wind Harmer
1.359
961601AG1-000A GEN
Solar/Wind Harmer
4.52
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
316478AD1-087 GEN
Solar/Wind Helper
3.067
316486AD2-202 GEN
Solar/Wind Helper
0.898
3146926FARMVIL
Solar/Wind Helper
0.143
3146776BUCKING
Solar/Wind Helper
0.069
315773AC2-141 GEN
Solar/Wind Helper
3.566
942461AE2-259 GEN
Solar/Wind Helper
1.116
3144873MCLAUGH
Solar/Wind Helper
0.004
3144536CHRHLND
Solar/Wind Helper
0.023
315839AE2-212 C
Solar/Wind Helper
0.201
3145336SMITFLD
Solar/Wind Helper
0.059
316382AG1-145 C
Solar/Wind Helper
0.19
3146456SLIGO L269
Solar/Wind Helper
0.14
316313AB2-026
Solar/Wind Helper
0.209
316258AE1-075 C
Solar/Wind Helper
0.188
316405AF2-144 C
Solar/Wind Helper
0.157
316156AD2-030 GEN
Solar/Wind Helper
0.202
316280AD1-041 GEN
Solar/Wind Helper
0.449
3142946ENON
Solar/Wind Helper
0.045
316484AD2-074 GEN
Solar/Wind Helper
0.249
316320Y1-086
Solar/Wind Helper
0.057
316404AE1-155 C
Solar/Wind Helper
1.078
316473AC1-191 GEN
Solar/Wind Helper
0.73
3141906WESTMOR
Solar/Wind Helper
0.047
316435W1029_GEN3
Solar/Wind Helper
0.474
3146516WINFALL
Solar/Wind Helper
0.115
971629AH1-314 GEN
50/50
13.606
3151561HALLBR1
50/50
0.377
24728405LEESVG
50/50
0.138
970417AG2-272 GEN
50/50
1.905
24684705SMG5
50/50
0.331
970481AG2-311 GEN
50/50
4.609
316003AC1-222 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.371
3147123OTTER R
Solar/Wind Harmer
0.091
970087AG2-069 GEN
Solar/Wind Harmer
11.429
970223AG2-152 GEN
Solar/Wind Harmer
9.459
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.098
941801AE2-185 GEN
Solar/Wind Harmer
4.19
270016AE1-250 BESS
Solar/Wind Harmer
0.004
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270030AE2-140 GEN
Solar/Wind Harmer
10.43
270173AC1-122 GEN
Solar/Wind Harmer
0.218
316359AB2-059 GEN
Solar/Wind Harmer
0.227
316049AB1-081 GEN
Solar/Wind Harmer
0.362
3142053HEARTS
Solar/Wind Harmer
0.111
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
315687AD1-152 GEN
Solar/Wind Helper
4.927
3146926FARMVIL
Solar/Wind Helper
0.143
316322AB2-045
Solar/Wind Helper
0.214
3146776BUCKING
Solar/Wind Helper
0.077
316294AC1-161 GEN
Solar/Wind Helper
3.03
316375AC2-012 GEN
Solar/Wind Helper
0.398
3145336SMITFLD
Solar/Wind Helper
0.592
316381AD1-082 GEN
Solar/Wind Helper
0.744
316388AE2-253 GEN
Solar/Wind Helper
0.545
316458AB2-190 GEN2
Solar/Wind Helper
0.811
316159AE1-175 C
Solar/Wind Helper
0.214
3146456SLIGO L269
Solar/Wind Helper
0.14
316072AD1-144
Solar/Wind Helper
0.16
3143226MDLTHAN
Solar/Wind Helper
0.138
316246AF1-032 C
Solar/Wind Helper
0.158
316336AC2-165 C
Solar/Wind Helper
0.738
3143526WINTERP
Solar/Wind Helper
0.705
3142543TWELFTH
Solar/Wind Helper
0.013
3142433PROV 92
Solar/Wind Helper
0.535
3141766HARMONY
Solar/Wind Helper
0.027
3138133OCRAN
Solar/Wind Helper
0.079
964211AG1-282 GEN
Solar/Wind Helper
0.169
3141726DUNNSVL
Solar/Wind Helper
0.503
3142416OLDCHRC
Solar/Wind Helper
0.323
3142416OLDCHRC
Solar/Wind Helper
0.124
316337AD2-073 GEN
Solar/Wind Helper
0.184
3146516WINFALL
Solar/Wind Helper
0.371
3146516WINFALL
Solar/Wind Helper
0.115
3147173SINAI
Solar/Wind Harmer
0.376
3147243WELCO
Solar/Wind Harmer
0.235
970865AG2-541 GEN
Solar/Wind Harmer
10.789
316118AC1-105 GEN
Solar/Wind Harmer
0.79
316123AC1-075 GEN
Solar/Wind Harmer
0.367
970165AG2-112 GEN
Solar/Wind Harmer
2.174
970163AG2-111 GEN
Solar/Wind Harmer
2.074
970085AG2-068 GEN
Solar/Wind Harmer
7.62
970581AG2-369 GEN
Solar/Wind Harmer
6.553
270069AE2-166 C O1
Solar/Wind Harmer
0.003
971981AH1-535 GEN
Solar/Wind Harmer
2.189
3143316POE
Solar/Wind Helper
0.623
316369SG1_INVT
Solar/Wind Helper
0.688
316132AB2-190 GEN1
Solar/Wind Helper
0.811
957831AF2-077 GEN
Solar/Wind Helper
0.188
319010AE1-072 C
Solar/Wind Helper
1.59
316305AF2-043 C
Solar/Wind Helper
0.186
316349AD2-085 GEN
Solar/Wind Helper
0.625
316233AE1-074 FULL
Solar/Wind Helper
0.207
957601AF2-054 GEN
Solar/Wind Helper
0.179
3141873WAN 176
Solar/Wind Helper
0.027
315662AE1-191 GEN
Solar/Wind Helper
0.718
315666AE1-190 GEN
Solar/Wind Helper
0.179
3143873LANEXA
Solar/Wind Helper
0.08
316059AD1-063 C
Solar/Wind Helper
0.134
3141913WHIT STONE
Solar/Wind Helper
0.132
3138133OCRAN
Solar/Wind Helper
0.04
3141783LANCAST
Solar/Wind Helper
0.079
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.196
316315AB2-025 C
Solar/Wind Helper
0.195
3146486SUNBURY
Solar/Wind Helper
0.126
3146486SUNBURY
Solar/Wind Helper
0.126
3141813NORNECK
Solar/Wind Helper
0.125
316312AB1-027
Solar/Wind Helper
0.236
316321Z2-027
Solar/Wind Helper
0.189
3145176PASQUOTANK
Solar/Wind Helper
0.077
316223AC1-118
Solar/Wind Helper
0.18
3152661PLYWOOD A
50/50
0.688
24684405SMG2
50/50
0.859
24684505SMG3
50/50
0.531
24684305SMG1
50/50
0.311
316222AC1-221 GEN
Solar/Wind Harmer
1.137
942751AE2-291 GEN
Solar/Wind Harmer
13.103
3146843MT LREL
Solar/Wind Harmer
0.235
3146843MT LREL
Solar/Wind Harmer
0.235
964791AG1-342 GEN
Solar/Wind Harmer
4.488
962561AG1-105 GEN
Solar/Wind Harmer
9.772
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.259
270013AE1-250 PV
Solar/Wind Harmer
0.004
961601AG1-000A GEN
Solar/Wind Harmer
1.13
316263AC1-034 GEN
Solar/Wind Harmer
2.401
3146776BUCKING
Solar/Wind Helper
0.769
3146776BUCKING
Solar/Wind Helper
0.062
316036AC1-147 C
Solar/Wind Helper
0.231
316316AC1-027 C
Solar/Wind Helper
0.237
3142956BIRDNECK
Solar/Wind Helper
0.101
316185AD1-033 GEN
Solar/Wind Helper
0.703
316236AE1-162_GEN
Solar/Wind Helper
0.199
3145506HICKORY
Solar/Wind Helper
0.589
3145506HICKORY
Solar/Wind Helper
0.353
3145506HICKORY
Solar/Wind Helper
0.088
316240AF1-291 C
Solar/Wind Helper
0.194
316339AD2-160 GEN
Solar/Wind Helper
0.545
316033AB2-134 GEN
Solar/Wind Helper
0.492
315697AD1-025 GEN
Solar/Wind Helper
1.636
316018AA1-139 ULT2
Solar/Wind Helper
0.611
316017AA1-139 ULT1
Solar/Wind Helper
0.649
3137176SLIGO L2192
Solar/Wind Helper
0.558
3130086AYDLETT
Solar/Wind Helper
0.554
3143526WINTERP
Solar/Wind Helper
0.705
3142946ENON
Solar/Wind Helper
0.013
316075AC2-137 C
Solar/Wind Helper
0.197
316487AF1-042 GEN
Solar/Wind Helper
0.13
3146386ELIZ CT
Solar/Wind Helper
0.129
3144356SAPONY
Solar/Wind Helper
0.229
316077AC2-138 C
Solar/Wind Helper
0.118
966871AG1-558 GEN
Solar/Wind Helper
0.161
316431W1029_GEN1
Solar/Wind Helper
0.474
316433W1029_GEN2
Solar/Wind Helper
0.474
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
316468AD1-105 GEN
Solar/Wind Helper
0.556
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.537
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.517
MECLTFEXP_MEC->PJM
CLTF
5.393
SIGELTFEXP_SIGE->PJM
CLTF
0.165
NYPJM->LTFIMP_NY
CLTF
0.69
LGEELTFEXP_LGEE->PJM
CLTF
2.05
WECLTFEXP_WEC->PJM
CLTF
1.087
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.092
CPLELTFEXP_CPLE->PJM
CLTF
11.262
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.898
LAGNLTFEXP_LAGN->PJM
CLTF
9.406
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.599
TVALTFEXP_TVA->PJM
CLTF
4.709

Details for AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.6 %
Rating:285.76 MVA
Rating Type:B
MVA to Mitigate:338.91
MW Contribution:4.79
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.206
24684605SMG4
50/50
0.898
24288905REUSENS
50/50
0.018
966251AG1-494 GEN
50/50
1.295
971683AH1-343 GEN
Solar/Wind Harmer
30.996
3147312GRETNA
Solar/Wind Harmer
0.048
941821AE2-187 GEN
Solar/Wind Harmer
7.744
270197AD1-017 GEN1
Solar/Wind Harmer
0.467
958131AF2-107 GEN
Solar/Wind Harmer
1.702
316248AF1-058 C
Solar/Wind Helper
0.405
316131AB2-060 GEN
Solar/Wind Helper
0.826
315785AD2-033 C
Solar/Wind Helper
1.415
24684405SMG2
50/50
0.892
24684505SMG3
50/50
0.552
24684305SMG1
50/50
0.323
942751AE2-291 GEN
Solar/Wind Harmer
31.022
316217AC1-145 GEN
Solar/Wind Harmer
0.003
316197AC1-042 GEN
Solar/Wind Harmer
0.003
942671AE2-283 GEN
Solar/Wind Harmer
6.023
3146843MT LREL
Solar/Wind Helper
0.233
3146843MT LREL
Solar/Wind Helper
0.233
316034AC1-036 C
Solar/Wind Helper
0.123
970865AG2-541 GEN
Solar/Wind Harmer
27.019
316123AC1-075 GEN
Solar/Wind Harmer
0.891
970165AG2-112 GEN
Solar/Wind Harmer
5.281
970163AG2-111 GEN
Solar/Wind Harmer
5.037
3147173SINAI
Solar/Wind Helper
0.301
3147243WELCO
Solar/Wind Helper
0.188
316118AC1-105 GEN
Solar/Wind Helper
1.038
316239AB2-077_GEN
Solar/Wind Helper
0.189
316238AB2-078_GEN
Solar/Wind Helper
0.189
3144303KENBRDG
Solar/Wind Helper
0.094
3151561HALLBR1
50/50
0.745
24728405LEESVG
50/50
0.205
24684705SMG5
50/50
0.344
970481AG2-311 GEN
50/50
4.788
316003AC1-222 GEN
Solar/Wind Harmer
0.024
3147123OTTER R
Solar/Wind Harmer
0.184
3147312GRETNA
Solar/Wind Harmer
0.193
3146802CHATHAM
Solar/Wind Harmer
0.181
941801AE2-185 GEN
Solar/Wind Harmer
7.744
270173AC1-122 GEN
Solar/Wind Harmer
0.243
962751AG1-124 GEN
Solar/Wind Harmer
3.509
270574AD1-017 GEN2
Solar/Wind Harmer
0
316237AB2-079_GEN
Solar/Wind Helper
0.189
315687AD1-152 GEN
Solar/Wind Helper
0.648
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.085
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.233
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.894
MECLTFEXP_MEC->PJM
CLTF
0.944
SIGELTFEXP_SIGE->PJM
CLTF
0.033
NYPJM->LTFIMP_NY
CLTF
0.2
LGEELTFEXP_LGEE->PJM
CLTF
0.454
WECLTFEXP_WEC->PJM
CLTF
0.224
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.472
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.748
LAGNLTFEXP_LAGN->PJM
CLTF
0.838
TVALTFEXP_TVA->PJM
CLTF
0.47

Details for AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line l/o AEP_P4_#10162_05EDAN 1 138_P_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.44 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:397.05
MW Contribution:6.07
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
0.769
24728405LEESVG
50/50
0.228
24684705SMG5
50/50
0.436
970481AG2-311 GEN
50/50
6.074
316003AC1-222 GEN
Solar/Wind Harmer
9.848
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.654
270574AD1-017 GEN2
Solar/Wind Harmer
5.091
270016AE1-250 BESS
Solar/Wind Harmer
2.26
970223AG2-152 GEN
Solar/Wind Harmer
13.033
270173AC1-122 GEN
Solar/Wind Harmer
1.398
962751AG1-124 GEN
Solar/Wind Harmer
5.091
316237AB2-079_GEN
Solar/Wind Helper
0.203
315687AD1-152 GEN
Solar/Wind Helper
0.727
970865AG2-541 GEN
Solar/Wind Harmer
35.473
316123AC1-075 GEN
Solar/Wind Harmer
7.906
970165AG2-112 GEN
Solar/Wind Harmer
6.961
970163AG2-111 GEN
Solar/Wind Harmer
6.641
3147173SINAI
Solar/Wind Helper
0.315
3147243WELCO
Solar/Wind Helper
0.197
316118AC1-105 GEN
Solar/Wind Helper
1.088
316239AB2-077_GEN
Solar/Wind Helper
0.203
316238AB2-078_GEN
Solar/Wind Helper
0.203
3144303KENBRDG
Solar/Wind Helper
0.101
24684405SMG2
50/50
1.132
24684505SMG3
50/50
0.7
24684305SMG1
50/50
0.41
24728405LEESVG
50/50
0.229
24684605SMG4
50/50
1.139
971683AH1-343 GEN
Solar/Wind Harmer
40.631
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.654
270197AD1-017 GEN1
Solar/Wind Harmer
1.53
958131AF2-107 GEN
Solar/Wind Harmer
2.297
316248AF1-058 C
Solar/Wind Helper
0.423
316131AB2-060 GEN
Solar/Wind Helper
0.889
315785AD2-033 C
Solar/Wind Helper
1.513
942751AE2-291 GEN
Solar/Wind Harmer
41.038
316217AC1-145 GEN
Solar/Wind Harmer
4.611
316197AC1-042 GEN
Solar/Wind Harmer
3.495
942671AE2-283 GEN
Solar/Wind Harmer
9.411
270013AE1-250 PV
Solar/Wind Harmer
2.26
3146843MT LREL
Solar/Wind Helper
0.245
3146843MT LREL
Solar/Wind Helper
0.245
316034AC1-036 C
Solar/Wind Helper
0.132
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.384
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.535
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.316
MECLTFEXP_MEC->PJM
CLTF
0.433
SIGELTFEXP_SIGE->PJM
CLTF
0.017
NYPJM->LTFIMP_NY
CLTF
0.113
LGEELTFEXP_LGEE->PJM
CLTF
0.256
WECLTFEXP_WEC->PJM
CLTF
0.121
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.011
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.729
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.021
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.95 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:391.83
MW Contribution:5.99
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
0.767
24728405LEESVG
50/50
0.227
24684705SMG5
50/50
0.43
970481AG2-311 GEN
50/50
5.987
316003AC1-222 GEN
Solar/Wind Harmer
9.884
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.622
270574AD1-017 GEN2
Solar/Wind Harmer
5.018
270016AE1-250 BESS
Solar/Wind Harmer
2.228
970223AG2-152 GEN
Solar/Wind Harmer
12.847
270173AC1-122 GEN
Solar/Wind Harmer
1.377
962751AG1-124 GEN
Solar/Wind Harmer
5
316237AB2-079_GEN
Solar/Wind Helper
0.194
315687AD1-152 GEN
Solar/Wind Helper
0.686
24728405LEESVG
50/50
0.228
24684605SMG4
50/50
1.123
971683AH1-343 GEN
Solar/Wind Harmer
40.772
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.622
270197AD1-017 GEN1
Solar/Wind Harmer
1.508
958131AF2-107 GEN
Solar/Wind Harmer
2.266
316248AF1-058 C
Solar/Wind Helper
0.413
316131AB2-060 GEN
Solar/Wind Helper
0.85
315785AD2-033 C
Solar/Wind Helper
1.444
24684405SMG2
50/50
1.115
24684505SMG3
50/50
0.69
24684305SMG1
50/50
0.404
942751AE2-291 GEN
Solar/Wind Harmer
41.127
316217AC1-145 GEN
Solar/Wind Harmer
4.597
316197AC1-042 GEN
Solar/Wind Harmer
3.485
942671AE2-283 GEN
Solar/Wind Harmer
9.382
270013AE1-250 PV
Solar/Wind Harmer
2.228
3146843MT LREL
Solar/Wind Helper
0.238
3146843MT LREL
Solar/Wind Helper
0.238
316034AC1-036 C
Solar/Wind Helper
0.126
970865AG2-541 GEN
Solar/Wind Harmer
35.588
316123AC1-075 GEN
Solar/Wind Harmer
7.927
970165AG2-112 GEN
Solar/Wind Harmer
6.98
970163AG2-111 GEN
Solar/Wind Harmer
6.658
3147173SINAI
Solar/Wind Helper
0.307
3147243WELCO
Solar/Wind Helper
0.192
316118AC1-105 GEN
Solar/Wind Helper
1.06
316239AB2-077_GEN
Solar/Wind Helper
0.194
316238AB2-078_GEN
Solar/Wind Helper
0.194
3144303KENBRDG
Solar/Wind Helper
0.096
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.321
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.018
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.317
MECLTFEXP_MEC->PJM
CLTF
0.388
SIGELTFEXP_SIGE->PJM
CLTF
0.015
NYPJM->LTFIMP_NY
CLTF
0.104
LGEELTFEXP_LGEE->PJM
CLTF
0.226
WECLTFEXP_WEC->PJM
CLTF
0.108
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.855
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.635
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.03
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line l/o AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:111.69 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:390.93
MW Contribution:5.99
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.115
24684505SMG3
50/50
0.69
24684305SMG1
50/50
0.404
942751AE2-291 GEN
Solar/Wind Harmer
41.127
316217AC1-145 GEN
Solar/Wind Harmer
4.597
316197AC1-042 GEN
Solar/Wind Harmer
3.485
942671AE2-283 GEN
Solar/Wind Harmer
9.382
270013AE1-250 PV
Solar/Wind Harmer
2.228
3146843MT LREL
Solar/Wind Helper
0.238
3146843MT LREL
Solar/Wind Helper
0.238
316034AC1-036 C
Solar/Wind Helper
0.126
3151561HALLBR1
50/50
0.767
24728405LEESVG
50/50
0.227
24684705SMG5
50/50
0.43
970481AG2-311 GEN
50/50
5.987
316003AC1-222 GEN
Solar/Wind Harmer
9.884
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.622
270574AD1-017 GEN2
Solar/Wind Harmer
5.018
270016AE1-250 BESS
Solar/Wind Harmer
2.228
970223AG2-152 GEN
Solar/Wind Harmer
12.847
270173AC1-122 GEN
Solar/Wind Harmer
1.377
962751AG1-124 GEN
Solar/Wind Harmer
5
316237AB2-079_GEN
Solar/Wind Helper
0.194
315687AD1-152 GEN
Solar/Wind Helper
0.686
970865AG2-541 GEN
Solar/Wind Harmer
35.588
316123AC1-075 GEN
Solar/Wind Harmer
7.927
970165AG2-112 GEN
Solar/Wind Harmer
6.98
970163AG2-111 GEN
Solar/Wind Harmer
6.658
3147173SINAI
Solar/Wind Helper
0.307
3147243WELCO
Solar/Wind Helper
0.192
316118AC1-105 GEN
Solar/Wind Helper
1.06
316239AB2-077_GEN
Solar/Wind Helper
0.194
316238AB2-078_GEN
Solar/Wind Helper
0.194
3144303KENBRDG
Solar/Wind Helper
0.096
24728405LEESVG
50/50
0.228
24684605SMG4
50/50
1.123
971683AH1-343 GEN
Solar/Wind Harmer
40.772
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.622
270197AD1-017 GEN1
Solar/Wind Harmer
1.508
958131AF2-107 GEN
Solar/Wind Harmer
2.266
316248AF1-058 C
Solar/Wind Helper
0.413
316131AB2-060 GEN
Solar/Wind Helper
0.85
315785AD2-033 C
Solar/Wind Helper
1.444
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.321
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.018
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.317
MECLTFEXP_MEC->PJM
CLTF
0.388
SIGELTFEXP_SIGE->PJM
CLTF
0.015
NYPJM->LTFIMP_NY
CLTF
0.104
LGEELTFEXP_LGEE->PJM
CLTF
0.226
WECLTFEXP_WEC->PJM
CLTF
0.108
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.855
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.635
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.03
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line l/o AEP_P7-1_#10778___SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10778___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:111.69 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:390.91
MW Contribution:5.99
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.228
24684605SMG4
50/50
1.123
971683AH1-343 GEN
Solar/Wind Harmer
40.772
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.622
270197AD1-017 GEN1
Solar/Wind Harmer
1.508
958131AF2-107 GEN
Solar/Wind Harmer
2.266
316248AF1-058 C
Solar/Wind Helper
0.413
316131AB2-060 GEN
Solar/Wind Helper
0.85
315785AD2-033 C
Solar/Wind Helper
1.445
3151561HALLBR1
50/50
0.767
24728405LEESVG
50/50
0.227
24684705SMG5
50/50
0.43
970481AG2-311 GEN
50/50
5.987
316003AC1-222 GEN
Solar/Wind Harmer
9.884
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.622
270574AD1-017 GEN2
Solar/Wind Harmer
5.018
270016AE1-250 BESS
Solar/Wind Harmer
2.228
970223AG2-152 GEN
Solar/Wind Harmer
12.847
270173AC1-122 GEN
Solar/Wind Harmer
1.377
962751AG1-124 GEN
Solar/Wind Harmer
5
316237AB2-079_GEN
Solar/Wind Helper
0.194
315687AD1-152 GEN
Solar/Wind Helper
0.686
970865AG2-541 GEN
Solar/Wind Harmer
35.588
316123AC1-075 GEN
Solar/Wind Harmer
7.927
970165AG2-112 GEN
Solar/Wind Harmer
6.98
970163AG2-111 GEN
Solar/Wind Harmer
6.658
3147173SINAI
Solar/Wind Helper
0.307
3147243WELCO
Solar/Wind Helper
0.192
316118AC1-105 GEN
Solar/Wind Helper
1.06
316239AB2-077_GEN
Solar/Wind Helper
0.194
316238AB2-078_GEN
Solar/Wind Helper
0.194
3144303KENBRDG
Solar/Wind Helper
0.096
24684405SMG2
50/50
1.116
24684505SMG3
50/50
0.69
24684305SMG1
50/50
0.404
942751AE2-291 GEN
Solar/Wind Harmer
41.127
316217AC1-145 GEN
Solar/Wind Harmer
4.597
316197AC1-042 GEN
Solar/Wind Harmer
3.485
942671AE2-283 GEN
Solar/Wind Harmer
9.383
270013AE1-250 PV
Solar/Wind Harmer
2.228
3146843MT LREL
Solar/Wind Helper
0.238
3146843MT LREL
Solar/Wind Helper
0.238
316034AC1-036 C
Solar/Wind Helper
0.126
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.321
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.019
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.317
MECLTFEXP_MEC->PJM
CLTF
0.388
SIGELTFEXP_SIGE->PJM
CLTF
0.015
NYPJM->LTFIMP_NY
CLTF
0.104
LGEELTFEXP_LGEE->PJM
CLTF
0.226
WECLTFEXP_WEC->PJM
CLTF
0.108
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.855
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.635
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.03
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 553_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 553_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.82 %
Rating:285.76 MVA
Rating Type:B
MVA to Mitigate:313.83
MW Contribution:4.38
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.195
24684605SMG4
50/50
0.822
24288905REUSENS
50/50
0.016
966251AG1-494 GEN
50/50
1.151
971683AH1-343 GEN
Solar/Wind Harmer
30.882
3147312GRETNA
Solar/Wind Harmer
0.047
941821AE2-187 GEN
Solar/Wind Harmer
7.488
270197AD1-017 GEN1
Solar/Wind Harmer
0.418
316248AF1-058 C
Solar/Wind Helper
0.41
316131AB2-060 GEN
Solar/Wind Helper
0.829
315785AD2-033 C
Solar/Wind Helper
1.406
24684405SMG2
50/50
0.816
24684505SMG3
50/50
0.505
24684305SMG1
50/50
0.296
942751AE2-291 GEN
Solar/Wind Harmer
30.733
316217AC1-145 GEN
Solar/Wind Harmer
0.003
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
5.824
3146843MT LREL
Solar/Wind Helper
0.236
3146843MT LREL
Solar/Wind Helper
0.236
316034AC1-036 C
Solar/Wind Helper
0.122
970865AG2-541 GEN
Solar/Wind Harmer
26.894
316123AC1-075 GEN
Solar/Wind Harmer
0.884
970165AG2-112 GEN
Solar/Wind Harmer
5.243
970163AG2-111 GEN
Solar/Wind Harmer
5.001
3147173SINAI
Solar/Wind Helper
0.305
3147243WELCO
Solar/Wind Helper
0.191
316118AC1-105 GEN
Solar/Wind Helper
1.051
316239AB2-077_GEN
Solar/Wind Helper
0.19
316238AB2-078_GEN
Solar/Wind Helper
0.19
3144303KENBRDG
Solar/Wind Helper
0.094
3151561HALLBR1
50/50
0.725
24728405LEESVG
50/50
0.195
24684705SMG5
50/50
0.314
970481AG2-311 GEN
50/50
4.381
316003AC1-222 GEN
Solar/Wind Harmer
0.024
3147123OTTER R
Solar/Wind Harmer
0.179
3147312GRETNA
Solar/Wind Harmer
0.187
3146802CHATHAM
Solar/Wind Harmer
0.175
941801AE2-185 GEN
Solar/Wind Harmer
7.488
270173AC1-122 GEN
Solar/Wind Harmer
0.22
962751AG1-124 GEN
Solar/Wind Harmer
3.082
270574AD1-017 GEN2
Solar/Wind Harmer
0
316237AB2-079_GEN
Solar/Wind Helper
0.19
315687AD1-152 GEN
Solar/Wind Helper
0.658
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.22
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.631
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.664
MECLTFEXP_MEC->PJM
CLTF
0.482
SIGELTFEXP_SIGE->PJM
CLTF
0.018
NYPJM->LTFIMP_NY
CLTF
0.114
LGEELTFEXP_LGEE->PJM
CLTF
0.255
WECLTFEXP_WEC->PJM
CLTF
0.124
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.654
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.709
LAGNLTFEXP_LAGN->PJM
CLTF
0.196
TVALTFEXP_TVA->PJM
CLTF
0.134

Details for AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.51 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:376.28
MW Contribution:5.58
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.04
24684505SMG3
50/50
0.643
24684305SMG1
50/50
0.377
942751AE2-291 GEN
Solar/Wind Harmer
44.58
316217AC1-145 GEN
Solar/Wind Harmer
5.995
316197AC1-042 GEN
Solar/Wind Harmer
4.545
942671AE2-283 GEN
Solar/Wind Harmer
12.236
3146843MT LREL
Solar/Wind Helper
0.208
3146843MT LREL
Solar/Wind Helper
0.208
3151561HALLBR1
50/50
0.945
24728405LEESVG
50/50
0.266
24684705SMG5
50/50
0.401
970481AG2-311 GEN
50/50
5.583
316003AC1-222 GEN
Solar/Wind Harmer
10.144
3147123OTTER R
Solar/Wind Harmer
-0.025
3147312GRETNA
Solar/Wind Harmer
-0.03
3146802CHATHAM
Solar/Wind Harmer
-0.028
941801AE2-185 GEN
Solar/Wind Harmer
13.852
270173AC1-122 GEN
Solar/Wind Harmer
1.159
270574AD1-017 GEN2
Solar/Wind Harmer
3.24
316237AB2-079_GEN
Solar/Wind Helper
0.166
970865AG2-541 GEN
Solar/Wind Harmer
37.085
316123AC1-075 GEN
Solar/Wind Harmer
8.439
970165AG2-112 GEN
Solar/Wind Harmer
7.43
970163AG2-111 GEN
Solar/Wind Harmer
7.088
3147173SINAI
Solar/Wind Helper
0.271
3147243WELCO
Solar/Wind Helper
0.169
316118AC1-105 GEN
Solar/Wind Helper
0.93
316239AB2-077_GEN
Solar/Wind Helper
0.166
316238AB2-078_GEN
Solar/Wind Helper
0.166
24728405LEESVG
50/50
0.267
24684605SMG4
50/50
1.047
971683AH1-343 GEN
Solar/Wind Harmer
42.136
3147312GRETNA
Solar/Wind Harmer
-0.007
941821AE2-187 GEN
Solar/Wind Harmer
13.852
270197AD1-017 GEN1
Solar/Wind Harmer
0.973
316248AF1-058 C
Solar/Wind Helper
0.364
316131AB2-060 GEN
Solar/Wind Helper
0.725
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.175
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.335
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.465
MECLTFEXP_MEC->PJM
CLTF
0.347
SIGELTFEXP_SIGE->PJM
CLTF
0.013
NYPJM->LTFIMP_NY
CLTF
0.102
LGEELTFEXP_LGEE->PJM
CLTF
0.187
WECLTFEXP_WEC->PJM
CLTF
0.09
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.518
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.905
LAGNLTFEXP_LAGN->PJM
CLTF
0.125
TVALTFEXP_TVA->PJM
CLTF
0.091

Details for AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line l/o AEP_P2-2_#17572_05MUSEVILLE 138_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC1-222 TAP-3HUBER DP 115.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#17572_05MUSEVILLE 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.61 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:352.15
MW Contribution:5.97
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.113
24684505SMG3
50/50
0.689
24684305SMG1
50/50
0.404
942751AE2-291 GEN
Solar/Wind Harmer
41.154
316217AC1-145 GEN
Solar/Wind Harmer
4.596
316197AC1-042 GEN
Solar/Wind Harmer
3.484
942671AE2-283 GEN
Solar/Wind Harmer
9.381
3146843MT LREL
Solar/Wind Helper
0.237
3146843MT LREL
Solar/Wind Helper
0.237
3151561HALLBR1
50/50
0.767
24728405LEESVG
50/50
0.227
24684705SMG5
50/50
0.429
970481AG2-311 GEN
50/50
5.974
316003AC1-222 GEN
Solar/Wind Harmer
9.893
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.62
270173AC1-122 GEN
Solar/Wind Harmer
1.374
962751AG1-124 GEN
Solar/Wind Harmer
4.989
24728405LEESVG
50/50
0.227
24684605SMG4
50/50
1.121
971683AH1-343 GEN
Solar/Wind Harmer
40.806
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.62
958131AF2-107 GEN
Solar/Wind Harmer
2.264
316248AF1-058 C
Solar/Wind Helper
0.411
316131AB2-060 GEN
Solar/Wind Helper
0.841
315785AD2-033 C
Solar/Wind Helper
1.428
316237AB2-079_GEN
Solar/Wind Helper
0.192
315687AD1-152 GEN
Solar/Wind Helper
0.677
970865AG2-541 GEN
Solar/Wind Harmer
35.617
316123AC1-075 GEN
Solar/Wind Harmer
7.933
970165AG2-112 GEN
Solar/Wind Harmer
6.985
970163AG2-111 GEN
Solar/Wind Harmer
6.663
3147173SINAI
Solar/Wind Helper
0.306
3147243WELCO
Solar/Wind Helper
0.191
316118AC1-105 GEN
Solar/Wind Helper
1.054
316239AB2-077_GEN
Solar/Wind Helper
0.192
316238AB2-078_GEN
Solar/Wind Helper
0.192
3144303KENBRDG
Solar/Wind Helper
0.095
316034AC1-036 C
Solar/Wind Helper
0.124
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.305
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.041
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.35
MECLTFEXP_MEC->PJM
CLTF
0.394
SIGELTFEXP_SIGE->PJM
CLTF
0.015
NYPJM->LTFIMP_NY
CLTF
0.097
LGEELTFEXP_LGEE->PJM
CLTF
0.226
WECLTFEXP_WEC->PJM
CLTF
0.108
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.817
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.734
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.006
TVALTFEXP_TVA->PJM
CLTF
0.041
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line l/o AEP_P7-1_#10817___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10817___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:121.83 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:477.57
MW Contribution:19.05
Bus #Bus NameTypeMW Contribution
24684605SMG4
50/50
3.572
24728405LEESVG
50/50
0.495
270197AD1-017 GEN1
Solar/Wind Harmer
7.076
24684705SMG5
50/50
1.367
970481AG2-311 GEN
50/50
19.048
24728405LEESVG
50/50
0.493
970223AG2-152 GEN
Solar/Wind Harmer
80.422
270016AE1-250 BESS
Solar/Wind Harmer
12.954
270574AD1-017 GEN2
Solar/Wind Harmer
23.549
270173AC1-122 GEN
Solar/Wind Harmer
4.971
270455AD2-022 GEN
Solar/Wind Helper
0.924
270457AD2-023 GEN
Solar/Wind Helper
0.609
24684405SMG2
50/50
3.549
24684505SMG3
50/50
2.195
24684305SMG1
50/50
1.287
270013AE1-250 PV
Solar/Wind Harmer
12.954
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.611
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.571
NYPJM->LTFIMP_NY
CLTF
0.099
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.315
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.014
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.058
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line l/o AEP_P4_#10213_05CLOVRD 138_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10213_05CLOVRD 138_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.79 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:450.0
MW Contribution:16.7
Bus #Bus NameTypeMW Contribution
24684705SMG5
50/50
1.198
970481AG2-311 GEN
50/50
16.703
24728405LEESVG
50/50
0.334
3151561HALLBR1
50/50
0.448
970223AG2-152 GEN
Solar/Wind Harmer
78.334
270016AE1-250 BESS
Solar/Wind Harmer
12.518
270574AD1-017 GEN2
Solar/Wind Harmer
22.147
270173AC1-122 GEN
Solar/Wind Harmer
3.243
3147312GRETNA
Solar/Wind Harmer
-0.017
3146802CHATHAM
Solar/Wind Harmer
-0.016
941801AE2-185 GEN
Solar/Wind Harmer
8.005
3147123OTTER R
Solar/Wind Harmer
-0.011
962751AG1-124 GEN
Solar/Wind Harmer
5.228
316123AC1-075 GEN
Solar/Wind Harmer
1.01
970165AG2-112 GEN
Solar/Wind Harmer
0.889
970163AG2-111 GEN
Solar/Wind Harmer
0.849
270455AD2-022 GEN
Solar/Wind Helper
0.935
270457AD2-023 GEN
Solar/Wind Helper
0.616
24684405SMG2
50/50
3.112
24684505SMG3
50/50
1.925
24684305SMG1
50/50
1.128
270013AE1-250 PV
Solar/Wind Harmer
12.518
316217AC1-145 GEN
Solar/Wind Harmer
3.465
316197AC1-042 GEN
Solar/Wind Harmer
2.627
942671AE2-283 GEN
Solar/Wind Harmer
7.071
942751AE2-291 GEN
Solar/Wind Harmer
7.417
24684605SMG4
50/50
3.133
24728405LEESVG
50/50
0.336
270197AD1-017 GEN1
Solar/Wind Harmer
6.655
3147312GRETNA
Solar/Wind Harmer
-0.004
941821AE2-187 GEN
Solar/Wind Harmer
8.005
958131AF2-107 GEN
Solar/Wind Harmer
2.397
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.589
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.768
NYPJM->LTFIMP_NY
CLTF
0.079
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.234
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.068
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.225
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line l/o AEP_P4_#10210_05CLOVRD 138_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10210_05CLOVRD 138_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.54 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:449.01
MW Contribution:16.68
Bus #Bus NameTypeMW Contribution
24684705SMG5
50/50
1.197
970481AG2-311 GEN
50/50
16.68
24728405LEESVG
50/50
0.334
3151561HALLBR1
50/50
0.448
970223AG2-152 GEN
Solar/Wind Harmer
78.303
270016AE1-250 BESS
Solar/Wind Harmer
12.513
270574AD1-017 GEN2
Solar/Wind Harmer
22.132
270173AC1-122 GEN
Solar/Wind Harmer
3.239
3147312GRETNA
Solar/Wind Harmer
-0.017
3146802CHATHAM
Solar/Wind Harmer
-0.016
941801AE2-185 GEN
Solar/Wind Harmer
7.991
3147123OTTER R
Solar/Wind Harmer
-0.011
962751AG1-124 GEN
Solar/Wind Harmer
5.215
316123AC1-075 GEN
Solar/Wind Harmer
1.008
970165AG2-112 GEN
Solar/Wind Harmer
0.887
970163AG2-111 GEN
Solar/Wind Harmer
0.846
270455AD2-022 GEN
Solar/Wind Helper
0.937
270457AD2-023 GEN
Solar/Wind Helper
0.617
24684405SMG2
50/50
3.108
24684505SMG3
50/50
1.922
24684305SMG1
50/50
1.127
270013AE1-250 PV
Solar/Wind Harmer
12.513
316217AC1-145 GEN
Solar/Wind Harmer
3.459
316197AC1-042 GEN
Solar/Wind Harmer
2.622
942671AE2-283 GEN
Solar/Wind Harmer
7.059
942751AE2-291 GEN
Solar/Wind Harmer
7.401
24684605SMG4
50/50
3.128
24728405LEESVG
50/50
0.335
270197AD1-017 GEN1
Solar/Wind Harmer
6.65
3147312GRETNA
Solar/Wind Harmer
-0.004
941821AE2-187 GEN
Solar/Wind Harmer
7.991
958131AF2-107 GEN
Solar/Wind Harmer
2.391
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.59
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.771
NYPJM->LTFIMP_NY
CLTF
0.078
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.237
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.068
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.226
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line l/o AEP_P7-1_#10808___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10808___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:111.62 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:437.54
MW Contribution:19.06
Bus #Bus NameTypeMW Contribution
24684605SMG4
50/50
3.574
270197AD1-017 GEN1
Solar/Wind Harmer
7.079
24684705SMG5
50/50
1.367
970481AG2-311 GEN
50/50
19.058
970223AG2-152 GEN
Solar/Wind Harmer
80.445
270016AE1-250 BESS
Solar/Wind Harmer
12.958
270574AD1-017 GEN2
Solar/Wind Harmer
23.558
270455AD2-022 GEN
Solar/Wind Helper
0.921
270457AD2-023 GEN
Solar/Wind Helper
0.607
24684405SMG2
50/50
3.551
24684505SMG3
50/50
2.196
24684305SMG1
50/50
1.287
270013AE1-250 PV
Solar/Wind Harmer
12.958
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.604
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.518
NYPJM->LTFIMP_NY
CLTF
0.088
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.303
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.003
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.023
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line l/o AEP_P2-2_#6213_05WLAKE 138_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#6213_05WLAKE 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:105.51 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:413.6
MW Contribution:14.46
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
2.694
24684505SMG3
50/50
1.666
24684305SMG1
50/50
0.977
270013AE1-250 PV
Solar/Wind Harmer
12.034
316217AC1-145 GEN
Solar/Wind Harmer
3.013
316197AC1-042 GEN
Solar/Wind Harmer
2.284
942671AE2-283 GEN
Solar/Wind Harmer
6.149
942751AE2-291 GEN
Solar/Wind Harmer
6.246
24684705SMG5
50/50
1.038
970481AG2-311 GEN
50/50
14.46
24728405LEESVG
50/50
0.29
3151561HALLBR1
50/50
0.389
970223AG2-152 GEN
Solar/Wind Harmer
75.879
270016AE1-250 BESS
Solar/Wind Harmer
12.034
270574AD1-017 GEN2
Solar/Wind Harmer
20.72
270173AC1-122 GEN
Solar/Wind Harmer
2.826
3147312GRETNA
Solar/Wind Harmer
-0.015
3146802CHATHAM
Solar/Wind Harmer
-0.014
941801AE2-185 GEN
Solar/Wind Harmer
6.961
3147123OTTER R
Solar/Wind Harmer
-0.01
962751AG1-124 GEN
Solar/Wind Harmer
4.826
316123AC1-075 GEN
Solar/Wind Harmer
0.835
24684605SMG4
50/50
2.712
24728405LEESVG
50/50
0.291
270197AD1-017 GEN1
Solar/Wind Harmer
6.226
3147312GRETNA
Solar/Wind Harmer
-0.004
941821AE2-187 GEN
Solar/Wind Harmer
6.961
958131AF2-107 GEN
Solar/Wind Harmer
2.203
270018AE2-047 C O1
Solar/Wind Helper
0.451
943811AF1-049 GEN
Solar/Wind Helper
0.749
970165AG2-112 GEN
Solar/Wind Harmer
0.735
970163AG2-111 GEN
Solar/Wind Harmer
0.701
270455AD2-022 GEN
Solar/Wind Helper
1.036
270457AD2-023 GEN
Solar/Wind Helper
0.682
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.663
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.766
NYPJM->LTFIMP_NY
CLTF
0.061
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.391
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.052
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.178
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line l/o AEP_P2-2_#6212_05WLAKE 138_2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG2-152 TP-05BANSTR 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#6212_05WLAKE 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:103.18 %
Rating:392.0 MVA
Rating Type:B
MVA to Mitigate:404.45
MW Contribution:14.46
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
2.694
24684505SMG3
50/50
1.666
24684305SMG1
50/50
0.977
270013AE1-250 PV
Solar/Wind Harmer
12.034
316217AC1-145 GEN
Solar/Wind Harmer
3.013
316197AC1-042 GEN
Solar/Wind Harmer
2.284
942671AE2-283 GEN
Solar/Wind Harmer
6.149
942751AE2-291 GEN
Solar/Wind Harmer
6.246
24684705SMG5
50/50
1.038
970481AG2-311 GEN
50/50
14.46
24728405LEESVG
50/50
0.29
3151561HALLBR1
50/50
0.389
970223AG2-152 GEN
Solar/Wind Harmer
75.879
270016AE1-250 BESS
Solar/Wind Harmer
12.034
270574AD1-017 GEN2
Solar/Wind Harmer
20.72
270173AC1-122 GEN
Solar/Wind Harmer
2.826
3147312GRETNA
Solar/Wind Harmer
-0.015
3146802CHATHAM
Solar/Wind Harmer
-0.014
941801AE2-185 GEN
Solar/Wind Harmer
6.961
3147123OTTER R
Solar/Wind Harmer
-0.01
962751AG1-124 GEN
Solar/Wind Harmer
4.826
24684605SMG4
50/50
2.712
24728405LEESVG
50/50
0.291
270197AD1-017 GEN1
Solar/Wind Harmer
6.226
3147312GRETNA
Solar/Wind Harmer
-0.004
941821AE2-187 GEN
Solar/Wind Harmer
6.961
958131AF2-107 GEN
Solar/Wind Harmer
2.203
270018AE2-047 C O1
Solar/Wind Helper
0.451
943811AF1-049 GEN
Solar/Wind Helper
0.749
316123AC1-075 GEN
Solar/Wind Harmer
0.835
970165AG2-112 GEN
Solar/Wind Harmer
0.735
970163AG2-111 GEN
Solar/Wind Harmer
0.701
270455AD2-022 GEN
Solar/Wind Helper
1.036
270457AD2-023 GEN
Solar/Wind Helper
0.682
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.663
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.766
NYPJM->LTFIMP_NY
CLTF
0.061
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.391
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.052
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.178
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.29 %
Rating:285.76 MVA
Rating Type:B
MVA to Mitigate:312.32
MW Contribution:4.8
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.206
24684605SMG4
50/50
0.9
24288905REUSENS
50/50
0.018
966251AG1-494 GEN
50/50
1.299
971683AH1-343 GEN
Solar/Wind Harmer
31.005
3147312GRETNA
Solar/Wind Harmer
0.048
941821AE2-187 GEN
Solar/Wind Harmer
7.752
270197AD1-017 GEN1
Solar/Wind Harmer
0.469
958131AF2-107 GEN
Solar/Wind Harmer
1.71
316248AF1-058 C
Solar/Wind Helper
0.404
316131AB2-060 GEN
Solar/Wind Helper
0.823
315785AD2-033 C
Solar/Wind Helper
1.409
24684405SMG2
50/50
0.894
24684505SMG3
50/50
0.553
24684305SMG1
50/50
0.324
942751AE2-291 GEN
Solar/Wind Harmer
31.036
316217AC1-145 GEN
Solar/Wind Harmer
0.003
316197AC1-042 GEN
Solar/Wind Harmer
0.003
942671AE2-283 GEN
Solar/Wind Harmer
6.03
3146843MT LREL
Solar/Wind Helper
0.232
3146843MT LREL
Solar/Wind Helper
0.232
316034AC1-036 C
Solar/Wind Helper
0.123
970865AG2-541 GEN
Solar/Wind Harmer
27.028
316123AC1-075 GEN
Solar/Wind Harmer
0.891
970165AG2-112 GEN
Solar/Wind Harmer
5.283
970163AG2-111 GEN
Solar/Wind Harmer
5.039
3147173SINAI
Solar/Wind Helper
0.301
3147243WELCO
Solar/Wind Helper
0.188
316118AC1-105 GEN
Solar/Wind Helper
1.036
316239AB2-077_GEN
Solar/Wind Helper
0.188
316238AB2-078_GEN
Solar/Wind Helper
0.188
3144303KENBRDG
Solar/Wind Helper
0.094
3151561HALLBR1
50/50
0.745
24728405LEESVG
50/50
0.205
24684705SMG5
50/50
0.344
970481AG2-311 GEN
50/50
4.8
3147123OTTER R
Solar/Wind Harmer
0.184
3147312GRETNA
Solar/Wind Harmer
0.194
3146802CHATHAM
Solar/Wind Harmer
0.182
941801AE2-185 GEN
Solar/Wind Harmer
7.752
270173AC1-122 GEN
Solar/Wind Harmer
0.243
962751AG1-124 GEN
Solar/Wind Harmer
3.521
270574AD1-017 GEN2
Solar/Wind Harmer
0
316003AC1-222 GEN
Solar/Wind Helper
1.905
316237AB2-079_GEN
Solar/Wind Helper
0.188
315687AD1-152 GEN
Solar/Wind Helper
0.645
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.077
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.522
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.969
MECLTFEXP_MEC->PJM
CLTF
0.978
SIGELTFEXP_SIGE->PJM
CLTF
0.034
NYPJM->LTFIMP_NY
CLTF
0.187
LGEELTFEXP_LGEE->PJM
CLTF
0.468
WECLTFEXP_WEC->PJM
CLTF
0.232
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.458
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.014
LAGNLTFEXP_LAGN->PJM
CLTF
0.878
TVALTFEXP_TVA->PJM
CLTF
0.49

Details for AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line l/o AEP_P4_#10162_05EDAN 1 138_P_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10162_05EDAN 1 138_P_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.04 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:360.64
MW Contribution:6.09
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
0.769
24728405LEESVG
50/50
0.229
24684705SMG5
50/50
0.437
970481AG2-311 GEN
50/50
6.086
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.665
270574AD1-017 GEN2
Solar/Wind Harmer
5.101
270016AE1-250 BESS
Solar/Wind Harmer
2.264
970223AG2-152 GEN
Solar/Wind Harmer
13.058
270173AC1-122 GEN
Solar/Wind Harmer
1.401
962751AG1-124 GEN
Solar/Wind Harmer
5.108
316003AC1-222 GEN
Solar/Wind Helper
1.949
316237AB2-079_GEN
Solar/Wind Helper
0.202
315687AD1-152 GEN
Solar/Wind Helper
0.724
24728405LEESVG
50/50
0.23
24684605SMG4
50/50
1.141
971683AH1-343 GEN
Solar/Wind Harmer
40.643
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.665
270197AD1-017 GEN1
Solar/Wind Harmer
1.533
958131AF2-107 GEN
Solar/Wind Harmer
2.307
316248AF1-058 C
Solar/Wind Helper
0.422
316131AB2-060 GEN
Solar/Wind Helper
0.886
315785AD2-033 C
Solar/Wind Helper
1.508
24684405SMG2
50/50
1.134
24684505SMG3
50/50
0.701
24684305SMG1
50/50
0.411
942751AE2-291 GEN
Solar/Wind Harmer
41.056
316217AC1-145 GEN
Solar/Wind Harmer
4.616
316197AC1-042 GEN
Solar/Wind Harmer
3.499
942671AE2-283 GEN
Solar/Wind Harmer
9.42
270013AE1-250 PV
Solar/Wind Harmer
2.264
3146843MT LREL
Solar/Wind Helper
0.245
3146843MT LREL
Solar/Wind Helper
0.245
316034AC1-036 C
Solar/Wind Helper
0.131
970865AG2-541 GEN
Solar/Wind Harmer
35.485
316123AC1-075 GEN
Solar/Wind Harmer
7.909
970165AG2-112 GEN
Solar/Wind Harmer
6.964
970163AG2-111 GEN
Solar/Wind Harmer
6.643
3147173SINAI
Solar/Wind Helper
0.314
3147243WELCO
Solar/Wind Helper
0.196
316118AC1-105 GEN
Solar/Wind Helper
1.086
316239AB2-077_GEN
Solar/Wind Helper
0.202
316238AB2-078_GEN
Solar/Wind Helper
0.202
3144303KENBRDG
Solar/Wind Helper
0.1
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.376
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.824
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.391
MECLTFEXP_MEC->PJM
CLTF
0.467
SIGELTFEXP_SIGE->PJM
CLTF
0.018
NYPJM->LTFIMP_NY
CLTF
0.1
LGEELTFEXP_LGEE->PJM
CLTF
0.269
WECLTFEXP_WEC->PJM
CLTF
0.129
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.998
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.996
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.041
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10164_05EDAN 2 138_M_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.53 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:355.37
MW Contribution:6.0
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
0.768
24728405LEESVG
50/50
0.227
24684705SMG5
50/50
0.43
970481AG2-311 GEN
50/50
5.999
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.632
24728405LEESVG
50/50
0.228
24684605SMG4
50/50
1.125
971683AH1-343 GEN
Solar/Wind Harmer
40.784
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.632
270197AD1-017 GEN1
Solar/Wind Harmer
1.511
24684405SMG2
50/50
1.118
24684505SMG3
50/50
0.691
24684305SMG1
50/50
0.405
942751AE2-291 GEN
Solar/Wind Harmer
41.146
316217AC1-145 GEN
Solar/Wind Harmer
4.602
316197AC1-042 GEN
Solar/Wind Harmer
3.489
942671AE2-283 GEN
Solar/Wind Harmer
9.392
270013AE1-250 PV
Solar/Wind Harmer
2.232
3146843MT LREL
Solar/Wind Helper
0.238
3146843MT LREL
Solar/Wind Helper
0.238
316034AC1-036 C
Solar/Wind Helper
0.125
270574AD1-017 GEN2
Solar/Wind Harmer
5.028
270016AE1-250 BESS
Solar/Wind Harmer
2.232
970223AG2-152 GEN
Solar/Wind Harmer
12.873
270173AC1-122 GEN
Solar/Wind Harmer
1.38
962751AG1-124 GEN
Solar/Wind Harmer
5.018
316003AC1-222 GEN
Solar/Wind Helper
1.921
316237AB2-079_GEN
Solar/Wind Helper
0.194
315687AD1-152 GEN
Solar/Wind Helper
0.683
970865AG2-541 GEN
Solar/Wind Harmer
35.6
316123AC1-075 GEN
Solar/Wind Harmer
7.93
970165AG2-112 GEN
Solar/Wind Harmer
6.982
970163AG2-111 GEN
Solar/Wind Harmer
6.661
3147173SINAI
Solar/Wind Helper
0.307
3147243WELCO
Solar/Wind Helper
0.192
316118AC1-105 GEN
Solar/Wind Helper
1.058
316239AB2-077_GEN
Solar/Wind Helper
0.194
316238AB2-078_GEN
Solar/Wind Helper
0.194
3144303KENBRDG
Solar/Wind Helper
0.096
958131AF2-107 GEN
Solar/Wind Harmer
2.276
316248AF1-058 C
Solar/Wind Helper
0.412
316131AB2-060 GEN
Solar/Wind Helper
0.847
315785AD2-033 C
Solar/Wind Helper
1.439
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.313
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.307
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.392
MECLTFEXP_MEC->PJM
CLTF
0.422
SIGELTFEXP_SIGE->PJM
CLTF
0.016
NYPJM->LTFIMP_NY
CLTF
0.092
LGEELTFEXP_LGEE->PJM
CLTF
0.24
WECLTFEXP_WEC->PJM
CLTF
0.115
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.841
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.902
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.022
TVALTFEXP_TVA->PJM
CLTF
0.051
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line l/o AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.27 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:354.46
MW Contribution:6.0
Bus #Bus NameTypeMW Contribution
24684405SMG2
50/50
1.118
24684505SMG3
50/50
0.691
24684305SMG1
50/50
0.405
942751AE2-291 GEN
Solar/Wind Harmer
41.146
316217AC1-145 GEN
Solar/Wind Harmer
4.602
316197AC1-042 GEN
Solar/Wind Harmer
3.489
942671AE2-283 GEN
Solar/Wind Harmer
9.392
270013AE1-250 PV
Solar/Wind Harmer
2.232
3146843MT LREL
Solar/Wind Helper
0.238
3146843MT LREL
Solar/Wind Helper
0.238
316034AC1-036 C
Solar/Wind Helper
0.125
3151561HALLBR1
50/50
0.768
24728405LEESVG
50/50
0.227
24684705SMG5
50/50
0.43
970481AG2-311 GEN
50/50
5.999
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.632
270574AD1-017 GEN2
Solar/Wind Harmer
5.028
270016AE1-250 BESS
Solar/Wind Harmer
2.232
970223AG2-152 GEN
Solar/Wind Harmer
12.873
270173AC1-122 GEN
Solar/Wind Harmer
1.38
962751AG1-124 GEN
Solar/Wind Harmer
5.018
316003AC1-222 GEN
Solar/Wind Helper
1.921
316237AB2-079_GEN
Solar/Wind Helper
0.194
315687AD1-152 GEN
Solar/Wind Helper
0.683
24728405LEESVG
50/50
0.228
24684605SMG4
50/50
1.125
971683AH1-343 GEN
Solar/Wind Harmer
40.784
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.632
270197AD1-017 GEN1
Solar/Wind Harmer
1.511
958131AF2-107 GEN
Solar/Wind Harmer
2.276
316248AF1-058 C
Solar/Wind Helper
0.412
316131AB2-060 GEN
Solar/Wind Helper
0.847
315785AD2-033 C
Solar/Wind Helper
1.439
970865AG2-541 GEN
Solar/Wind Harmer
35.6
316123AC1-075 GEN
Solar/Wind Harmer
7.93
970165AG2-112 GEN
Solar/Wind Harmer
6.982
970163AG2-111 GEN
Solar/Wind Harmer
6.661
3147173SINAI
Solar/Wind Helper
0.307
3147243WELCO
Solar/Wind Helper
0.192
316118AC1-105 GEN
Solar/Wind Helper
1.058
316239AB2-077_GEN
Solar/Wind Helper
0.194
316238AB2-078_GEN
Solar/Wind Helper
0.194
3144303KENBRDG
Solar/Wind Helper
0.096
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.313
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.307
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.392
MECLTFEXP_MEC->PJM
CLTF
0.422
SIGELTFEXP_SIGE->PJM
CLTF
0.016
NYPJM->LTFIMP_NY
CLTF
0.092
LGEELTFEXP_LGEE->PJM
CLTF
0.24
WECLTFEXP_WEC->PJM
CLTF
0.115
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.841
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.902
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.022
TVALTFEXP_TVA->PJM
CLTF
0.051
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line l/o AEP_P7-1_#10778___SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10778___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:101.27 %
Rating:350.0 MVA
Rating Type:C
MVA to Mitigate:354.44
MW Contribution:6.0
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.228
24684605SMG4
50/50
1.125
971683AH1-343 GEN
Solar/Wind Harmer
40.784
3147312GRETNA
Solar/Wind Harmer
-0.006
941821AE2-187 GEN
Solar/Wind Harmer
10.633
270197AD1-017 GEN1
Solar/Wind Harmer
1.511
958131AF2-107 GEN
Solar/Wind Harmer
2.276
316248AF1-058 C
Solar/Wind Helper
0.412
316131AB2-060 GEN
Solar/Wind Helper
0.847
315785AD2-033 C
Solar/Wind Helper
1.439
3151561HALLBR1
50/50
0.768
24728405LEESVG
50/50
0.227
24684705SMG5
50/50
0.43
970481AG2-311 GEN
50/50
5.999
3147123OTTER R
Solar/Wind Harmer
-0.021
3147312GRETNA
Solar/Wind Harmer
-0.023
3146802CHATHAM
Solar/Wind Harmer
-0.021
941801AE2-185 GEN
Solar/Wind Harmer
10.633
270574AD1-017 GEN2
Solar/Wind Harmer
5.028
270016AE1-250 BESS
Solar/Wind Harmer
2.232
970223AG2-152 GEN
Solar/Wind Harmer
12.873
270173AC1-122 GEN
Solar/Wind Harmer
1.38
962751AG1-124 GEN
Solar/Wind Harmer
5.018
316003AC1-222 GEN
Solar/Wind Helper
1.921
316237AB2-079_GEN
Solar/Wind Helper
0.194
315687AD1-152 GEN
Solar/Wind Helper
0.683
970865AG2-541 GEN
Solar/Wind Harmer
35.6
316123AC1-075 GEN
Solar/Wind Harmer
7.93
970165AG2-112 GEN
Solar/Wind Harmer
6.982
970163AG2-111 GEN
Solar/Wind Harmer
6.661
3147173SINAI
Solar/Wind Helper
0.307
3147243WELCO
Solar/Wind Helper
0.192
316118AC1-105 GEN
Solar/Wind Helper
1.058
316239AB2-077_GEN
Solar/Wind Helper
0.194
316238AB2-078_GEN
Solar/Wind Helper
0.194
3144303KENBRDG
Solar/Wind Helper
0.096
24684405SMG2
50/50
1.118
24684505SMG3
50/50
0.691
24684305SMG1
50/50
0.405
942751AE2-291 GEN
Solar/Wind Harmer
41.146
316217AC1-145 GEN
Solar/Wind Harmer
4.602
316197AC1-042 GEN
Solar/Wind Harmer
3.489
942671AE2-283 GEN
Solar/Wind Harmer
9.392
270013AE1-250 PV
Solar/Wind Harmer
2.232
3146843MT LREL
Solar/Wind Helper
0.238
3146843MT LREL
Solar/Wind Helper
0.238
316034AC1-036 C
Solar/Wind Helper
0.125
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.313
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.307
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.392
MECLTFEXP_MEC->PJM
CLTF
0.422
SIGELTFEXP_SIGE->PJM
CLTF
0.016
NYPJM->LTFIMP_NY
CLTF
0.092
LGEELTFEXP_LGEE->PJM
CLTF
0.24
WECLTFEXP_WEC->PJM
CLTF
0.115
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.842
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.902
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.022
TVALTFEXP_TVA->PJM
CLTF
0.051
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 553_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-343 TP-3CRSTL HILL 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 553_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.5 %
Rating:285.76 MVA
Rating Type:B
MVA to Mitigate:287.19
MW Contribution:4.39
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.196
24684605SMG4
50/50
0.824
24288905REUSENS
50/50
0.016
966251AG1-494 GEN
50/50
1.156
971683AH1-343 GEN
Solar/Wind Harmer
30.891
3147312GRETNA
Solar/Wind Harmer
0.047
941821AE2-187 GEN
Solar/Wind Harmer
7.497
270197AD1-017 GEN1
Solar/Wind Harmer
0.42
316248AF1-058 C
Solar/Wind Helper
0.409
316131AB2-060 GEN
Solar/Wind Helper
0.826
315785AD2-033 C
Solar/Wind Helper
1.4
3151561HALLBR1
50/50
0.726
24728405LEESVG
50/50
0.195
24684705SMG5
50/50
0.315
970481AG2-311 GEN
50/50
4.393
3147123OTTER R
Solar/Wind Harmer
0.179
3147312GRETNA
Solar/Wind Harmer
0.187
3146802CHATHAM
Solar/Wind Harmer
0.176
941801AE2-185 GEN
Solar/Wind Harmer
7.497
270173AC1-122 GEN
Solar/Wind Harmer
0.22
962751AG1-124 GEN
Solar/Wind Harmer
3.094
270574AD1-017 GEN2
Solar/Wind Harmer
0
316003AC1-222 GEN
Solar/Wind Helper
1.927
316237AB2-079_GEN
Solar/Wind Helper
0.189
315687AD1-152 GEN
Solar/Wind Helper
0.655
970865AG2-541 GEN
Solar/Wind Harmer
26.903
316123AC1-075 GEN
Solar/Wind Harmer
0.885
970165AG2-112 GEN
Solar/Wind Harmer
5.245
970163AG2-111 GEN
Solar/Wind Harmer
5.003
3147173SINAI
Solar/Wind Helper
0.305
3147243WELCO
Solar/Wind Helper
0.19
316118AC1-105 GEN
Solar/Wind Helper
1.049
316239AB2-077_GEN
Solar/Wind Helper
0.189
316238AB2-078_GEN
Solar/Wind Helper
0.189
3144303KENBRDG
Solar/Wind Helper
0.093
24684405SMG2
50/50
0.818
24684505SMG3
50/50
0.506
24684305SMG1
50/50
0.297
942751AE2-291 GEN
Solar/Wind Harmer
30.747
316217AC1-145 GEN
Solar/Wind Harmer
0.003
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
5.831
3146843MT LREL
Solar/Wind Helper
0.235
3146843MT LREL
Solar/Wind Helper
0.235
316034AC1-036 C
Solar/Wind Helper
0.122
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.212
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.92
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.739
MECLTFEXP_MEC->PJM
CLTF
0.515
SIGELTFEXP_SIGE->PJM
CLTF
0.019
NYPJM->LTFIMP_NY
CLTF
0.101
LGEELTFEXP_LGEE->PJM
CLTF
0.269
WECLTFEXP_WEC->PJM
CLTF
0.132
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.641
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.975
LAGNLTFEXP_LAGN->PJM
CLTF
0.236
TVALTFEXP_TVA->PJM
CLTF
0.154
CONTINGENCY 'AEP_P7-1_#10817___SRT-A'
 OPEN BRANCH FROM BUS 242575 TO BUS 242737 CKT 1   /*05CANDLER MT 138.0 - 05OPOSSUMCK  138.0
 OPEN BRANCH FROM BUS 242575 TO BUS 242781 CKT 1   /*05CANDLER MT 138.0 - 05RUSTBR     138.0
 OPEN BRANCH FROM BUS 242575 TO BUS 243814 CKT 1   /*05CANDLER MT 138.0 - 05REDEYE     138.0
 OPEN BRANCH FROM BUS 242701 TO BUS 314667 CKT 1   /*05LEESVI     138.0 - 4ALTVSTA     138.0
END
CONTINGENCY 'AEP_P4_#10213_05CLOVRD 138_A_SRT-A'
 OPEN BRANCH FROM BUS 242560 TO BUS 242607 CKT 1    /*05BONSCK     138.0 - 05CLOVRD     138.0
 OPEN BRANCH FROM BUS 242560 TO BUS 242840 CKT 1    /*05BONSCK     138.0 - 05VINTON     138.0
 OPEN BRANCH FROM BUS 242607 TO BUS 243892 CKT 1    /*05CLOVRD     138.0 - 05MEADSTORSS 138.0
 OPEN BRANCH FROM BUS 242720 TO BUS 242775 CKT 1    /*05MONETA     138.0 - 05ROCKCAS SS 138.0
 OPEN BRANCH FROM BUS 242720 TO BUS 243892 CKT 1    /*05MONETA     138.0 - 05MEADSTORSS 138.0
 OPEN BRANCH FROM BUS 242773 TO BUS 242840 CKT 1    /*05ROANO1     138.0 - 05VINTON     138.0
 OPEN BRANCH FROM BUS 242775 TO BUS 242802 CKT 1    /*05ROCKCAS SS 138.0 - 05SMITHMTN   138.0
 OPEN BRANCH FROM BUS 242775 TO BUS 245675 CKT Z1   /*05ROCKCAS SS 138.0 - 05WHITEHOUS8 138.0
 OPEN BRANCH FROM BUS 243892 TO BUS 290923 CKT Z1   /*05MEADSTORSS 138.0 - 05MEADSTOR8  138.0
END
CONTINGENCY 'AEP_P4_#10210_05CLOVRD 138_A2_SRT-A'
 OPEN BRANCH FROM BUS 242607 TO BUS 243892 CKT 1    /*05CLOVRD     138.0 - 05MEADSTORSS 138.0
 OPEN BRANCH FROM BUS 242720 TO BUS 242775 CKT 1    /*05MONETA     138.0 - 05ROCKCAS SS 138.0
 OPEN BRANCH FROM BUS 242720 TO BUS 243892 CKT 1    /*05MONETA     138.0 - 05MEADSTORSS 138.0
 OPEN BRANCH FROM BUS 242775 TO BUS 242802 CKT 1    /*05ROCKCAS SS 138.0 - 05SMITHMTN   138.0
 OPEN BRANCH FROM BUS 243892 TO BUS 290923 CKT Z1   /*05MEADSTORSS 138.0 - 05MEADSTOR8  138.0
 REMOVE LOAD D8 FROM BUS 242607                     /*05CLOVRD     138.0
END
CONTINGENCY 'AEP_P7-1_#10808___SRT-A'
 OPEN BRANCH FROM BUS 242701 TO BUS 242802 CKT 1   /*05LEESVI     138.0 - 05SMITHMTN   138.0
 OPEN BRANCH FROM BUS 242701 TO BUS 247284 CKT 1   /*05LEESVI     138.0 - 05LEESVG      13.8
 OPEN BRANCH FROM BUS 242701 TO BUS 314667 CKT 1   /*05LEESVI     138.0 - 4ALTVSTA     138.0
 OPEN BRANCH FROM BUS 242802 TO BUS 243814 CKT 1   /*05SMITHMTN   138.0 - 05REDEYE     138.0
END
CONTINGENCY 'AEP_P2-2_#6213_05WLAKE 138_1_SRT-A'
 OPEN BRANCH FROM BUS 242748 TO BUS 242802 CKT 1   /*05PENHOOK    138.0 - 05SMITHMTN   138.0
 OPEN BRANCH FROM BUS 242748 TO BUS 243951 CKT 1   /*05PENHOOK    138.0 - 05REDWOOD    138.0
 OPEN BRANCH FROM BUS 242843 TO BUS 243951 CKT 1   /*05WLAKE      138.0 - 05REDWOOD    138.0
END
CONTINGENCY 'AEP_P2-2_#6212_05WLAKE 138_2_SRT-A'
 OPEN BRANCH FROM BUS 242555 TO BUS 242843 CKT 1   /*05BLAINE     138.0 - 05WLAKE      138.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AP_P2-3_MP-500-020_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-021_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AEP_P4_#37_05MOUNTN 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
END
CONTINGENCY 'AEP_P4_#2942_05KAMMER 765_PP_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 OPEN BRANCH FROM BUS 242925 TO BUS 243188 CKT 1   /*05KAMMER     765.0 - 05MLG1        26.0
 REMOVE UNIT 1 FROM BUS 243188                     /*05MLG1        26.0
END
CONTINGENCY 'DVP_P4-2: 151T1047_SRT-A'
 OPEN BRANCH FROM BUS 313168 TO BUS 314696 CKT 1   /*3HUBER DP    115.0 - 3SEDGE HILL  115.0
 OPEN BRANCH FROM BUS 313168 TO BUS 316000 CKT 1   /*3HUBER DP    115.0 - AC1-222 TAP  115.0
 OPEN BRANCH FROM BUS 313825 TO BUS 314696 CKT 1   /*3PLYWOOD     115.0 - 3SEDGE HILL  115.0
 OPEN BUS 313168                                   /*3HUBER DP    115.0
END
CONTINGENCY 'DVP_P4-2: 104702_SRT-A'
 OPEN BRANCH FROM BUS 313168 TO BUS 314696 CKT 1   /*3HUBER DP    115.0 - 3SEDGE HILL  115.0
 OPEN BRANCH FROM BUS 313168 TO BUS 316000 CKT 1   /*3HUBER DP    115.0 - AC1-222 TAP  115.0
 OPEN BUS 313168                                   /*3HUBER DP    115.0
 OPEN BUS 314520                                   /*3SEDGE_1     115.0
END
CONTINGENCY 'DVP_P4-2: 1016T1047_SRT-A'
 OPEN BRANCH FROM BUS 313168 TO BUS 314696 CKT 1   /*3HUBER DP    115.0 - 3SEDGE HILL  115.0
 OPEN BRANCH FROM BUS 313168 TO BUS 316000 CKT 1   /*3HUBER DP    115.0 - AC1-222 TAP  115.0
 OPEN BRANCH FROM BUS 314688 TO BUS 316000 CKT 1   /*3CRSTL HILL  115.0 - AC1-222 TAP  115.0
 OPEN BRANCH FROM BUS 314688 TO BUS 971682 CKT 1   /*3CRSTL HILL  115.0 - AH1-343 TP   115.0
 OPEN BUS 313168                                   /*3HUBER DP    115.0
 OPEN BUS 314688                                   /*3CRSTL HILL  115.0
 OPEN BUS 316000                                   /*AC1-222 TAP  115.0
 OPEN BUS 316001                                   /*AC1-222 MAIN 115.0
 OPEN BUS 316002                                   /*AC1-222 COL   34.5
 OPEN BUS 316003                                   /*AC1-222 GEN    0.6
END
CONTINGENCY 'DVP_P4-2: 101672_SRT-A'
 OPEN BRANCH FROM BUS 314688 TO BUS 316000 CKT 1   /*3CRSTL HILL  115.0 - AC1-222 TAP  115.0
 OPEN BRANCH FROM BUS 314688 TO BUS 971682 CKT 1   /*3CRSTL HILL  115.0 - AH1-343 TP   115.0
 OPEN BUS 314688                                   /*3CRSTL HILL  115.0
 OPEN BUS 316000                                   /*AC1-222 TAP  115.0
 OPEN BUS 316001                                   /*AC1-222 MAIN 115.0
 OPEN BUS 316002                                   /*AC1-222 COL   34.5
 OPEN BUS 316003                                   /*AC1-222 GEN    0.6
END
CONTINGENCY 'DVP_P4-2: 104772_SRT-A'
 OPEN BRANCH FROM BUS 313168 TO BUS 314696 CKT 1   /*3HUBER DP    115.0 - 3SEDGE HILL  115.0
 OPEN BRANCH FROM BUS 313168 TO BUS 316000 CKT 1   /*3HUBER DP    115.0 - AC1-222 TAP  115.0
 OPEN BUS 313168                                   /*3HUBER DP    115.0
 OPEN BUS 316000                                   /*AC1-222 TAP  115.0
 OPEN BUS 316001                                   /*AC1-222 MAIN 115.0
 OPEN BUS 316002                                   /*AC1-222 COL   34.5
 OPEN BUS 316003                                   /*AC1-222 GEN    0.6
END
CONTINGENCY 'DVP_P1-2: LN 1047_SRT-A'
 OPEN BRANCH FROM BUS 313168 TO BUS 314696 CKT 1   /*3HUBER DP    115.0 - 3SEDGE HILL  115.0
 OPEN BRANCH FROM BUS 313168 TO BUS 316000 CKT 1   /*3HUBER DP    115.0 - AC1-222 TAP  115.0
 OPEN BUS 313168                                   /*3HUBER DP    115.0
END
CONTINGENCY 'DVP_P1-2: LN 1016_SRT-A-1'
 OPEN BRANCH FROM BUS 314688 TO BUS 316000 CKT 1   /*3CRSTL HILL  115.0 - AC1-222 TAP  115.0
 OPEN BRANCH FROM BUS 314688 TO BUS 971682 CKT 1   /*3CRSTL HILL  115.0 - AH1-343 TP   115.0
 OPEN BUS 314688                                   /*3CRSTL HILL  115.0
END
CONTINGENCY 'AEP_P2-2_#10163_05EDAN 2 138_2_SRT-A'
 OPEN BRANCH FROM BUS 242531 TO BUS 242632 CKT 4    /*05EDANV2     230.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242531 TO BUS 304094 CKT 1    /*05EDANV2     230.0 - 6YANCY TAP   230.0
 OPEN BRANCH FROM BUS 242549 TO BUS 242632 CKT 1    /*05BANSTR     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 242632 CKT 1    /*05E.MONU     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242631 TO BUS 242632 CKT Z1   /*05EDAN 1     138.0 - 05EDAN 2     138.0
END
CONTINGENCY 'AEP_P7-1_#10778___SRT-A'
 OPEN BRANCH FROM BUS 242531 TO BUS 242632 CKT 4    /*05EDANV2     230.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242531 TO BUS 304094 CKT 1    /*05EDANV2     230.0 - 6YANCY TAP   230.0
 OPEN BRANCH FROM BUS 242549 TO BUS 242632 CKT 1    /*05BANSTR     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 242632 CKT 1    /*05E.MONU     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 242770 CKT 1    /*05E.MONU     138.0 - 05RIGIS      138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 243948 CKT 3    /*05E.MONU     138.0 - 05BRANTLY     69.0
 OPEN BRANCH FROM BUS 242631 TO BUS 242632 CKT Z1   /*05EDAN 1     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242770 TO BUS 243988 CKT 1    /*05RIGIS      138.0 - 05RIGIS       69.0
 OPEN BRANCH FROM BUS 243974 TO BUS 243988 CKT 1    /*05GOODYEAR1   69.0 - 05RIGIS       69.0
END
CONTINGENCY 'AEP_P4_#10162_05EDAN 1 138_P_SRT-A'
 OPEN BRANCH FROM BUS 242530 TO BUS 242631 CKT 5    /*05EDANV1     230.0 - 05EDAN 1     138.0
 OPEN BRANCH FROM BUS 242530 TO BUS 270450 CKT 1    /*05EDANV1     230.0 - AD2-022 TAP  230.0
 OPEN BRANCH FROM BUS 242531 TO BUS 304094 CKT 1    /*05EDANV2     230.0 - 6YANCY TAP   230.0
 OPEN BRANCH FROM BUS 242549 TO BUS 242632 CKT 1    /*05BANSTR     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242620 TO BUS 242631 CKT 1    /*05DANVL2     138.0 - 05EDAN 1     138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 242632 CKT 1    /*05E.MONU     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242631 TO BUS 242632 CKT Z1   /*05EDAN 1     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242631 TO BUS 243962 CKT 1    /*05EDAN 1     138.0 - 05EDANV1EQ     1.0
 OPEN BRANCH FROM BUS 242631 TO BUS 246972 CKT 1    /*05EDAN 1     138.0 - 05ROCKSP     138.0
 OPEN BRANCH FROM BUS 243960 TO BUS 243962 CKT 1    /*05E.DANVIL    69.0 - 05EDANV1EQ     1.0
 OPEN BRANCH FROM BUS 243961 TO BUS 243962 CKT 1    /*05EDANVILL    12.0 - 05EDANV1EQ     1.0
 REMOVE SWSHUNT FROM BUS 242631                     /*05EDAN 1     138.0
 REMOVE SWSHUNT FROM BUS 243960                     /*05E.DANVIL    69.0
END
CONTINGENCY 'AEP_P4_#10164_05EDAN 2 138_M_SRT-A'
 OPEN BRANCH FROM BUS 242531 TO BUS 242632 CKT 4    /*05EDANV2     230.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242531 TO BUS 304094 CKT 1    /*05EDANV2     230.0 - 6YANCY TAP   230.0
 OPEN BRANCH FROM BUS 242549 TO BUS 242632 CKT 1    /*05BANSTR     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242549 TO BUS 314668 CKT Z1   /*05BANSTR     138.0 - 4BANISTR     138.0
 OPEN BRANCH FROM BUS 242549 TO BUS 970222 CKT 1    /*05BANSTR     138.0 - AG2-152 TP   138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 242632 CKT 1    /*05E.MONU     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242631 TO BUS 242632 CKT Z1   /*05EDAN 1     138.0 - 05EDAN 2     138.0
END
CONTINGENCY 'AEP_P4_#10687_05EDAN 2 138_N_SRT-A'
 OPEN BRANCH FROM BUS 242531 TO BUS 242632 CKT 4    /*05EDANV2     230.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242531 TO BUS 304094 CKT 1    /*05EDANV2     230.0 - 6YANCY TAP   230.0
 OPEN BRANCH FROM BUS 242549 TO BUS 242632 CKT 1    /*05BANSTR     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 242632 CKT 1    /*05E.MONU     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 242770 CKT 1    /*05E.MONU     138.0 - 05RIGIS      138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 243948 CKT 3    /*05E.MONU     138.0 - 05BRANTLY     69.0
 OPEN BRANCH FROM BUS 242631 TO BUS 242632 CKT Z1   /*05EDAN 1     138.0 - 05EDAN 2     138.0
 REMOVE SWSHUNT FROM BUS 242629                     /*05E.MONU     138.0
END
CONTINGENCY 'AEP_P4_#8676_05EDANV2 230_S_SRT-A'
 OPEN BRANCH FROM BUS 242531 TO BUS 242632 CKT 4    /*05EDANV2     230.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242531 TO BUS 304094 CKT 1    /*05EDANV2     230.0 - 6YANCY TAP   230.0
 OPEN BRANCH FROM BUS 242549 TO BUS 242632 CKT 1    /*05BANSTR     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 242632 CKT 1    /*05E.MONU     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242631 TO BUS 242632 CKT Z1   /*05EDAN 1     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 304094 TO BUS 304095 CKT 1    /*6YANCY TAP   230.0 - 6YANCYVILLE  230.0
 OPEN BRANCH FROM BUS 304094 TO BUS 304097 CKT 1    /*6YANCY TAP   230.0 - 6CONCD2230TT 230.0
END
CONTINGENCY 'AEP_P1-2_#5366_SRT-A-1'
 OPEN BRANCH FROM BUS 242549 TO BUS 242632 CKT 1    /*05BANSTR     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242549 TO BUS 314668 CKT Z1   /*05BANSTR     138.0 - 4BANISTR     138.0
 OPEN BRANCH FROM BUS 242549 TO BUS 970222 CKT 1    /*05BANSTR     138.0 - AG2-152 TP   138.0
END
CONTINGENCY 'AEP_P1-3_#10688_05EDANV2 230_4_SRT-A'
 OPEN BRANCH FROM BUS 242531 TO BUS 242632 CKT 4    /*05EDANV2     230.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242531 TO BUS 304094 CKT 1    /*05EDANV2     230.0 - 6YANCY TAP   230.0
 OPEN BRANCH FROM BUS 242549 TO BUS 242632 CKT 1    /*05BANSTR     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242629 TO BUS 242632 CKT 1    /*05E.MONU     138.0 - 05EDAN 2     138.0
 OPEN BRANCH FROM BUS 242631 TO BUS 242632 CKT Z1   /*05EDAN 1     138.0 - 05EDAN 2     138.0
END
CONTINGENCY 'AEP_P7-1_#10781___SRT-A-1'
 OPEN BRANCH FROM BUS 242530 TO BUS 270450 CKT 1   /*05EDANV1     230.0 - AD2-022 TAP  230.0
 OPEN BRANCH FROM BUS 242531 TO BUS 304094 CKT 1   /*05EDANV2     230.0 - 6YANCY TAP   230.0
 OPEN BRANCH FROM BUS 304094 TO BUS 304095 CKT 1   /*6YANCY TAP   230.0 - 6YANCYVILLE  230.0
 OPEN BRANCH FROM BUS 304094 TO BUS 304097 CKT 1   /*6YANCY TAP   230.0 - 6CONCD2230TT 230.0
END
CONTINGENCY 'DVP_P2-2: ALTAVISTA 115KV_SRT-A'
 OPEN BUS 313162   /*3HALL BR TAP 115.0
 OPEN BUS 314515   /*3ALTVS_1     115.0
 OPEN BUS 314666   /*3ALTVSTA     115.0
 OPEN BUS 314700   /*3HALL BR     115.0
 OPEN BUS 314705   /*3HURT        115.0
 OPEN BUS 315156   /*1HALLBR1      13.8
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P1-2: LN 553_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314910 CKT 1                /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
END
CONTINGENCY 'AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A'
 OPEN BRANCH FROM BUS 242569 TO BUS 242734 CKT 1   /*05BRUSHT     138.0 - 05NEWLDN     138.0
 OPEN BRANCH FROM BUS 242641 TO BUS 242734 CKT 1   /*05FOREST     138.0 - 05NEWLDN     138.0
 OPEN BRANCH FROM BUS 242687 TO BUS 242734 CKT 1   /*05JOHNMT     138.0 - 05NEWLDN     138.0
END
CONTINGENCY 'DVP_P1-3: 4ALTVSTA-TX#4_SRT-A'
 OPEN BRANCH FROM BUS 314666 TO BUS 314667 CKT 2   /*3ALTVSTA     115.0 - 4ALTVSTA     138.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-3'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-2'
 OPEN BRANCH FROM BUS 970916 TO BUS 970084 CKT 1   /*AG2-570 TP   500.0 - AG2-068 TP   500.0
END
CONTINGENCY 'AEP_P2-2_#17572_05MUSEVILLE 138_1_SRT-A'
 OPEN BRANCH FROM BUS 242802 TO BUS 290234 CKT 1   /*05SMITHMTN   138.0 - 05MUSEVILLE  138.0
END
242549 to 242632 ckt 1
242519 to 314912 ckt 1
242687 to 242734 ckt 1
242701 to 314667 ckt 1
242741 to 242687 ckt 1
242802 to 242701 ckt 1
314688 to 316000 ckt 1
313168 to 314696 ckt 1
314667 to 242741 ckt 1
314667 to 314666 ckt 1
315684 to 314690 ckt 1
314697 to 315684 ckt 1
316000 to 313168 ckt 1
970222 to 242549 ckt 1
971682 to 314688 ckt 1

Winter Peak Analysis

The New Service Request AG2-311 was evaluated as a 75.0 MW (52.5 MW Capacity) injection in the AEP area.

AG2-311 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 75.0 MW (75.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P1-2_#3174_6_SRT-A
SingleAC101.09 %304.56B307.899.13
GD2AEP/DVP
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
AEP_P1-3_#1372_05JOSHUA 765_1_SRT-A
SingleAC100.99 %304.56B307.579.13

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P1-2_#3174_6_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#3174_6_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.09 %
Rating:304.56 MVA
Rating Type:B
MVA to Mitigate:307.89
MW Contribution:9.13
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.51
24728405LEESVG
50/50
0.51
3146843MT LREL
Solar/Wind Helper
0.156
3146843MT LREL
Solar/Wind Helper
0.156
3147123OTTER R
Solar/Wind Helper
0.694
3147312GRETNA
Solar/Wind Helper
0.257
3147312GRETNA
Solar/Wind Helper
1.029
24684305SMG1
50/50
1.217
24684405SMG2
50/50
2.782
24684505SMG3
50/50
2.086
24684605SMG4
50/50
2.087
24684705SMG5
50/50
1.043
316248AF1-058 C
Solar/Wind Helper
0.065
3146802CHATHAM
Solar/Wind Helper
0.965
3147243WELCO
Solar/Wind Helper
0.127
3147173SINAI
Solar/Wind Helper
0.203
270173AC1-122 GEN
Solar/Wind Harmer
0
316123AC1-075 GEN
Solar/Wind Helper
0.852
316197AC1-042 GEN
Solar/Wind Helper
0.868
970223AG2-152 GEN
Solar/Wind Harmer
0.488
970481AG2-311 GEN
50/50
9.129
316003AC1-222 GEN
Solar/Wind Helper
0.316
316118AC1-105 GEN
Solar/Wind Helper
0.147
316217AC1-145 GEN
Solar/Wind Helper
1.033
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.554
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.36
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.69
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.024
NYPJM->LTFIMP_NY
CLTF
0.082
LGEELTFEXP_LGEE->PJM
CLTF
0.14
WECLTFEXP_WEC->PJM
CLTF
0.069
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.053
TVALTFEXP_TVA->PJM
CLTF
0.18
MECLTFEXP_MEC->PJM
CLTF
0.303
LAGNLTFEXP_LAGN->PJM
CLTF
0.33
SIGELTFEXP_SIGE->PJM
CLTF
0.01

Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P1-3_#1372_05JOSHUA 765_1_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-3_#1372_05JOSHUA 765_1_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.99 %
Rating:304.56 MVA
Rating Type:B
MVA to Mitigate:307.57
MW Contribution:9.13
Bus #Bus NameTypeMW Contribution
24728405LEESVG
50/50
0.51
24728405LEESVG
50/50
0.51
3146843MT LREL
Solar/Wind Helper
0.156
3146843MT LREL
Solar/Wind Helper
0.156
3147123OTTER R
Solar/Wind Helper
0.694
3147312GRETNA
Solar/Wind Helper
0.257
3147312GRETNA
Solar/Wind Helper
1.029
24684305SMG1
50/50
1.217
24684405SMG2
50/50
2.782
24684505SMG3
50/50
2.086
24684605SMG4
50/50
2.087
24684705SMG5
50/50
1.043
316248AF1-058 C
Solar/Wind Helper
0.065
3146802CHATHAM
Solar/Wind Helper
0.965
3147243WELCO
Solar/Wind Helper
0.127
3147173SINAI
Solar/Wind Helper
0.203
270173AC1-122 GEN
Solar/Wind Harmer
0
316123AC1-075 GEN
Solar/Wind Helper
0.852
316197AC1-042 GEN
Solar/Wind Helper
0.868
970223AG2-152 GEN
Solar/Wind Harmer
0.488
970481AG2-311 GEN
50/50
9.129
316003AC1-222 GEN
Solar/Wind Helper
0.316
316118AC1-105 GEN
Solar/Wind Helper
0.147
316217AC1-145 GEN
Solar/Wind Helper
1.033
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.554
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.36
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.69
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.024
NYPJM->LTFIMP_NY
CLTF
0.082
LGEELTFEXP_LGEE->PJM
CLTF
0.14
WECLTFEXP_WEC->PJM
CLTF
0.069
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.053
TVALTFEXP_TVA->PJM
CLTF
0.18
MECLTFEXP_MEC->PJM
CLTF
0.303
LAGNLTFEXP_LAGN->PJM
CLTF
0.33
SIGELTFEXP_SIGE->PJM
CLTF
0.01
CONTINGENCY 'AEP_P1-2_#3174_6_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 290614 CKT Z1   /*05CLOVRD     765.0 - 05CLOVRD_RJO 765.0
 OPEN BRANCH FROM BUS 242515 TO BUS 290614 CKT 1    /*05JOSHUA     765.0 - 05CLOVRD_RJO 765.0
END
CONTINGENCY 'AEP_P1-3_#1372_05JOSHUA 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242515 TO BUS 247669 CKT 1   /*05JOSHUA     765.0 - 05JOSHUA 1EQ   1.0
 OPEN BRANCH FROM BUS 242688 TO BUS 247670 CKT 1   /*05JOSHUA     138.0 - 05JOSHUA_XFL 138.0
 OPEN BRANCH FROM BUS 247669 TO BUS 247670 CKT 1   /*05JOSHUA 1EQ   1.0 - 05JOSHUA_XFL 138.0
END
242701 to 314667 ckt 1

Light Load Analysis

The New Service Request AG2-311 was evaluated as a 75.0 MW injection and 75.0 MW withdrawal in the AEP area.

AG2-311 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 75.0 MW (75.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line
AEP_P4_#10294_05NEWLDN 138_D_SRT-A
BreakerAC110.7 %255.0B282.2911.01
GD2AEP
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line
AEP_P4_#10293_05NEWLDN 138_C_SRT-A
BreakerAC110.51 %255.0B281.7911.01
GD2AEP
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line
AEP_P4_#10292_05NEWLDN 138_E_SRT-A
BreakerAC110.5 %255.0B281.7811.01
GD2AEP
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
BusAC110.5 %255.0B281.7811.01
GD2AEP
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line
DVP_P4-2: 151T1047_SRT-A
BreakerAC106.71 %255.0B272.112.14
GD2AEP
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line
DVP_P4-2: 104702_SRT-A
BreakerAC106.67 %255.0B272.0112.13
GD2AEP
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line
DVP_P1-2: LN 13_SRT-A
SingleAC105.36 %255.0B268.6711.01
GD2AEP
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line
AEP_P1-2_#375_5201_SRT-A
SingleAC105.36 %255.0B268.6711.01
GD2AEP
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
AEP_P1-2_#311_5_SRT-A
SingleAC125.64 %296.0B371.919.35
GD2AEP
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
AEP_P4_#7587_05J.FERR 765_B_SRT-A
BreakerAC123.54 %296.0B365.6919.36
GD2AEP
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
AEP_P4_#2914_05J.FERR 765_B2_SRT-A
BreakerAC123.21 %296.0B364.7119.35
GD2AEP
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
AEP_P7-1_#10781___SRT-A-3
TowerAC103.45 %296.0B306.213.79
GD2DVP
3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer
DVP_P1-3: 4ALTVSTA-TX#4_SRT-A
SingleAC119.84 %139.4B167.067.09
GD2DVP
3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer
DVP_P1-3: 4ALTVSTA-TX#3_SRT-A
SingleAC105.36 %168.45B177.487.54

Details for 05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line l/o AEP_P4_#10294_05NEWLDN 138_D_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10294_05NEWLDN 138_D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.7 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:282.29
MW Contribution:11.01
Bus #Bus NameTypeMW Contribution
3146843MT LREL
Solar/Wind Harmer
0.196
3146843MT LREL
Solar/Wind Harmer
0.196
3147123OTTER R
Solar/Wind Harmer
0.878
3147312GRETNA
Solar/Wind Harmer
1.315
3147312GRETNA
Solar/Wind Harmer
0.329
3146802CHATHAM
Solar/Wind Harmer
1.233
3147243WELCO
Solar/Wind Harmer
0.161
3147173SINAI
Solar/Wind Harmer
0.257
270197AD1-017 GEN1
Solar/Wind Helper
1.89
270574AD1-017 GEN2
Solar/Wind Helper
1.701
270173AC1-122 GEN
Solar/Wind Helper
1.998
270016AE1-250 BESS
Solar/Wind Helper
1.498
270013AE1-250 PV
Solar/Wind Helper
1.498
942671AE2-283 GEN
Solar/Wind Harmer
17.423
942751AE2-291 GEN
Solar/Wind Harmer
20.098
960061AF2-297 GEN
Solar/Wind Harmer
4.119
962561AG1-105 GEN
Solar/Wind Harmer
3.278
970163AG2-111 GEN
Solar/Wind Harmer
2.432
970165AG2-112 GEN
Solar/Wind Harmer
2.549
970401AG2-262 GEN
Solar/Wind Harmer
0.43
970481AG2-311 GEN
50/50
Charging
11.011
970865AG2-541 GEN
Solar/Wind Harmer
4.995
970865AG2-541 GEN
Solar/Wind Harmer
8.612
971683AH1-343 GEN
Solar/Wind Harmer
6.809
941801AE2-185 GEN
Solar/Wind Harmer
19.724
941821AE2-187 GEN
Solar/Wind Harmer
19.724
964791AG1-342 GEN
Solar/Wind Harmer
1.406
961131AF2-404 GEN
Solar/Wind Harmer
11.336
NYPJM->LTFIMP_NY
CLTF
0.044
CPLELTFEXP_CPLE->PJM
CLTF
0.314
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.008
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.095
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.266
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.826
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.064
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.607

Details for 05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line l/o AEP_P4_#10293_05NEWLDN 138_C_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10293_05NEWLDN 138_C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.51 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:281.79
MW Contribution:11.01
Bus #Bus NameTypeMW Contribution
3146843MT LREL
Solar/Wind Harmer
0.196
3146843MT LREL
Solar/Wind Harmer
0.196
3147123OTTER R
Solar/Wind Harmer
0.878
3147312GRETNA
Solar/Wind Harmer
1.315
3147312GRETNA
Solar/Wind Harmer
0.329
3146802CHATHAM
Solar/Wind Harmer
1.233
3147243WELCO
Solar/Wind Harmer
0.161
3147173SINAI
Solar/Wind Harmer
0.257
270197AD1-017 GEN1
Solar/Wind Helper
1.89
270574AD1-017 GEN2
Solar/Wind Helper
1.701
270173AC1-122 GEN
Solar/Wind Helper
1.998
270016AE1-250 BESS
Solar/Wind Helper
1.498
270013AE1-250 PV
Solar/Wind Helper
1.498
942671AE2-283 GEN
Solar/Wind Harmer
17.423
942751AE2-291 GEN
Solar/Wind Harmer
20.098
960061AF2-297 GEN
Solar/Wind Harmer
4.119
962561AG1-105 GEN
Solar/Wind Harmer
3.278
970163AG2-111 GEN
Solar/Wind Harmer
2.432
970165AG2-112 GEN
Solar/Wind Harmer
2.549
970401AG2-262 GEN
Solar/Wind Harmer
0.43
970481AG2-311 GEN
50/50
Charging
11.011
970865AG2-541 GEN
Solar/Wind Harmer
4.995
970865AG2-541 GEN
Solar/Wind Harmer
8.612
971683AH1-343 GEN
Solar/Wind Harmer
6.809
941801AE2-185 GEN
Solar/Wind Harmer
19.724
941821AE2-187 GEN
Solar/Wind Harmer
19.724
964791AG1-342 GEN
Solar/Wind Harmer
1.406
961131AF2-404 GEN
Solar/Wind Harmer
11.336
NYPJM->LTFIMP_NY
CLTF
0.044
CPLELTFEXP_CPLE->PJM
CLTF
0.314
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.008
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.095
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.266
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.826
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.064
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.607

Details for 05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line l/o AEP_P4_#10292_05NEWLDN 138_E_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10292_05NEWLDN 138_E_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.5 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:281.78
MW Contribution:11.01
Bus #Bus NameTypeMW Contribution
3146843MT LREL
Solar/Wind Harmer
0.196
3146843MT LREL
Solar/Wind Harmer
0.196
3147123OTTER R
Solar/Wind Harmer
0.878
3147312GRETNA
Solar/Wind Harmer
1.315
3147312GRETNA
Solar/Wind Harmer
0.329
3146802CHATHAM
Solar/Wind Harmer
1.233
3147243WELCO
Solar/Wind Harmer
0.161
3147173SINAI
Solar/Wind Harmer
0.257
270197AD1-017 GEN1
Solar/Wind Helper
1.89
270574AD1-017 GEN2
Solar/Wind Helper
1.701
270173AC1-122 GEN
Solar/Wind Helper
1.998
270016AE1-250 BESS
Solar/Wind Helper
1.498
270013AE1-250 PV
Solar/Wind Helper
1.498
942671AE2-283 GEN
Solar/Wind Harmer
17.423
942751AE2-291 GEN
Solar/Wind Harmer
20.098
960061AF2-297 GEN
Solar/Wind Harmer
4.119
962561AG1-105 GEN
Solar/Wind Harmer
3.278
970163AG2-111 GEN
Solar/Wind Harmer
2.432
970165AG2-112 GEN
Solar/Wind Harmer
2.549
970401AG2-262 GEN
Solar/Wind Harmer
0.43
970481AG2-311 GEN
50/50
Charging
11.011
970865AG2-541 GEN
Solar/Wind Harmer
4.995
970865AG2-541 GEN
Solar/Wind Harmer
8.612
971683AH1-343 GEN
Solar/Wind Harmer
6.809
941801AE2-185 GEN
Solar/Wind Harmer
19.724
941821AE2-187 GEN
Solar/Wind Harmer
19.724
964791AG1-342 GEN
Solar/Wind Harmer
1.406
961131AF2-404 GEN
Solar/Wind Harmer
11.336
NYPJM->LTFIMP_NY
CLTF
0.044
CPLELTFEXP_CPLE->PJM
CLTF
0.314
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.008
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.095
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.266
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.826
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.064
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.607

Details for 05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:110.5 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:281.78
MW Contribution:11.01
Bus #Bus NameTypeMW Contribution
3146843MT LREL
Solar/Wind Harmer
0.196
3146843MT LREL
Solar/Wind Harmer
0.196
3147123OTTER R
Solar/Wind Harmer
0.878
3147312GRETNA
Solar/Wind Harmer
1.315
3147312GRETNA
Solar/Wind Harmer
0.329
3146802CHATHAM
Solar/Wind Harmer
1.233
3147243WELCO
Solar/Wind Harmer
0.161
3147173SINAI
Solar/Wind Harmer
0.257
270197AD1-017 GEN1
Solar/Wind Helper
1.89
270574AD1-017 GEN2
Solar/Wind Helper
1.701
270173AC1-122 GEN
Solar/Wind Helper
1.998
270016AE1-250 BESS
Solar/Wind Helper
1.498
270013AE1-250 PV
Solar/Wind Helper
1.498
942671AE2-283 GEN
Solar/Wind Harmer
17.423
942751AE2-291 GEN
Solar/Wind Harmer
20.098
960061AF2-297 GEN
Solar/Wind Harmer
4.119
962561AG1-105 GEN
Solar/Wind Harmer
3.278
970163AG2-111 GEN
Solar/Wind Harmer
2.432
970165AG2-112 GEN
Solar/Wind Harmer
2.549
970401AG2-262 GEN
Solar/Wind Harmer
0.43
970481AG2-311 GEN
50/50
Charging
11.011
970865AG2-541 GEN
Solar/Wind Harmer
4.995
970865AG2-541 GEN
Solar/Wind Harmer
8.612
971683AH1-343 GEN
Solar/Wind Harmer
6.809
941801AE2-185 GEN
Solar/Wind Harmer
19.724
941821AE2-187 GEN
Solar/Wind Harmer
19.724
964791AG1-342 GEN
Solar/Wind Harmer
1.406
961131AF2-404 GEN
Solar/Wind Harmer
11.336
NYPJM->LTFIMP_NY
CLTF
0.044
CPLELTFEXP_CPLE->PJM
CLTF
0.314
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.008
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.095
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.266
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.826
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.064
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.607

Details for 05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line l/o DVP_P4-2: 151T1047_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 151T1047_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.71 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:272.1
MW Contribution:12.14
Bus #Bus NameTypeMW Contribution
3147123OTTER R
Solar/Wind Harmer
0.796
3147312GRETNA
Solar/Wind Harmer
1.091
3147312GRETNA
Solar/Wind Harmer
0.273
3146802CHATHAM
Solar/Wind Harmer
1.023
270197AD1-017 GEN1
Solar/Wind Helper
2.145
270574AD1-017 GEN2
Solar/Wind Helper
1.931
270173AC1-122 GEN
Solar/Wind Helper
1.614
270016AE1-250 BESS
Solar/Wind Helper
1.772
270013AE1-250 PV
Solar/Wind Helper
1.772
942671AE2-283 GEN
Solar/Wind Harmer
14.461
942751AE2-291 GEN
Solar/Wind Harmer
27.071
962751AG1-124 GEN
Solar/Wind Harmer
3.544
970163AG2-111 GEN
Solar/Wind Harmer
3.848
970165AG2-112 GEN
Solar/Wind Harmer
4.034
970481AG2-311 GEN
50/50
Charging
12.136
970865AG2-541 GEN
Solar/Wind Harmer
10.918
970865AG2-541 GEN
Solar/Wind Harmer
18.825
971683AH1-343 GEN
Solar/Wind Harmer
18.313
941801AE2-185 GEN
Solar/Wind Harmer
16.371
941821AE2-187 GEN
Solar/Wind Harmer
16.371
958131AF2-107 GEN
Solar/Wind Harmer
1.778
961131AF2-404 GEN
Solar/Wind Harmer
9.408
NYPJM->LTFIMP_NY
CLTF
0.042
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.4
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.194
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.365
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.05
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.16
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line l/o DVP_P4-2: 104702_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 104702_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.67 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:272.01
MW Contribution:12.13
Bus #Bus NameTypeMW Contribution
3147123OTTER R
Solar/Wind Harmer
0.796
3147312GRETNA
Solar/Wind Harmer
1.091
3147312GRETNA
Solar/Wind Harmer
0.273
3146802CHATHAM
Solar/Wind Harmer
1.023
270197AD1-017 GEN1
Solar/Wind Helper
2.145
270574AD1-017 GEN2
Solar/Wind Helper
1.931
270173AC1-122 GEN
Solar/Wind Helper
1.614
270016AE1-250 BESS
Solar/Wind Helper
1.772
270013AE1-250 PV
Solar/Wind Helper
1.772
942671AE2-283 GEN
Solar/Wind Harmer
14.461
942751AE2-291 GEN
Solar/Wind Harmer
27.071
962751AG1-124 GEN
Solar/Wind Harmer
3.544
970163AG2-111 GEN
Solar/Wind Harmer
3.848
970165AG2-112 GEN
Solar/Wind Harmer
4.034
970481AG2-311 GEN
50/50
Charging
12.135
970865AG2-541 GEN
Solar/Wind Harmer
10.918
970865AG2-541 GEN
Solar/Wind Harmer
18.825
971683AH1-343 GEN
Solar/Wind Harmer
18.313
941801AE2-185 GEN
Solar/Wind Harmer
16.371
941821AE2-187 GEN
Solar/Wind Harmer
16.371
958131AF2-107 GEN
Solar/Wind Harmer
1.778
961131AF2-404 GEN
Solar/Wind Harmer
9.409
NYPJM->LTFIMP_NY
CLTF
0.042
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.399
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.194
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.363
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.05
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.159
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 13_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 13_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.36 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:268.67
MW Contribution:11.01
Bus #Bus NameTypeMW Contribution
3146843MT LREL
Solar/Wind Harmer
0.196
3146843MT LREL
Solar/Wind Harmer
0.196
3147123OTTER R
Solar/Wind Harmer
0.878
3147312GRETNA
Solar/Wind Harmer
1.315
3147312GRETNA
Solar/Wind Harmer
0.329
3146802CHATHAM
Solar/Wind Harmer
1.233
3147243WELCO
Solar/Wind Harmer
0.161
3147173SINAI
Solar/Wind Harmer
0.257
270197AD1-017 GEN1
Solar/Wind Helper
1.89
270574AD1-017 GEN2
Solar/Wind Helper
1.701
270173AC1-122 GEN
Solar/Wind Helper
1.997
270016AE1-250 BESS
Solar/Wind Helper
1.497
270013AE1-250 PV
Solar/Wind Helper
1.497
942671AE2-283 GEN
Solar/Wind Harmer
17.424
942751AE2-291 GEN
Solar/Wind Harmer
20.099
960061AF2-297 GEN
Solar/Wind Harmer
4.119
962561AG1-105 GEN
Solar/Wind Harmer
3.278
970163AG2-111 GEN
Solar/Wind Harmer
2.432
970165AG2-112 GEN
Solar/Wind Harmer
2.549
970401AG2-262 GEN
Solar/Wind Harmer
0.43
970481AG2-311 GEN
50/50
Charging
11.01
971683AH1-343 GEN
Solar/Wind Harmer
6.809
941801AE2-185 GEN
Solar/Wind Harmer
19.725
941821AE2-187 GEN
Solar/Wind Harmer
19.725
964791AG1-342 GEN
Solar/Wind Harmer
1.406
961131AF2-404 GEN
Solar/Wind Harmer
11.336
NYPJM->LTFIMP_NY
CLTF
0.044
CPLELTFEXP_CPLE->PJM
CLTF
0.314
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.008
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.095
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.266
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.826
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.064
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.607

Details for 05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line l/o AEP_P1-2_#375_5201_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#375_5201_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.36 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:268.67
MW Contribution:11.01
Bus #Bus NameTypeMW Contribution
3146843MT LREL
Solar/Wind Harmer
0.196
3146843MT LREL
Solar/Wind Harmer
0.196
3147123OTTER R
Solar/Wind Harmer
0.878
3147312GRETNA
Solar/Wind Harmer
1.315
3147312GRETNA
Solar/Wind Harmer
0.329
3146802CHATHAM
Solar/Wind Harmer
1.233
3147243WELCO
Solar/Wind Harmer
0.161
3147173SINAI
Solar/Wind Harmer
0.257
270197AD1-017 GEN1
Solar/Wind Helper
1.89
270574AD1-017 GEN2
Solar/Wind Helper
1.701
270173AC1-122 GEN
Solar/Wind Helper
1.997
270016AE1-250 BESS
Solar/Wind Helper
1.497
270013AE1-250 PV
Solar/Wind Helper
1.497
942671AE2-283 GEN
Solar/Wind Harmer
17.424
942751AE2-291 GEN
Solar/Wind Harmer
20.099
960061AF2-297 GEN
Solar/Wind Harmer
4.119
962561AG1-105 GEN
Solar/Wind Harmer
3.278
970163AG2-111 GEN
Solar/Wind Harmer
2.432
970165AG2-112 GEN
Solar/Wind Harmer
2.549
970401AG2-262 GEN
Solar/Wind Harmer
0.43
970481AG2-311 GEN
50/50
Charging
11.01
971683AH1-343 GEN
Solar/Wind Harmer
6.809
941801AE2-185 GEN
Solar/Wind Harmer
19.725
941821AE2-187 GEN
Solar/Wind Harmer
19.725
964791AG1-342 GEN
Solar/Wind Harmer
1.406
961131AF2-404 GEN
Solar/Wind Harmer
11.336
NYPJM->LTFIMP_NY
CLTF
0.044
CPLELTFEXP_CPLE->PJM
CLTF
0.314
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.008
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.095
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.266
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.826
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.064
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.607

Details for 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line l/o AEP_P1-2_#311_5_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#311_5_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.64 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:371.9
MW Contribution:19.35
Bus #Bus NameTypeMW Contribution
270173AC1-122 GEN
Solar/Wind Helper
4.149
316123AC1-075 GEN
Solar/Wind Helper
1.385
316197AC1-042 GEN
Solar/Wind Helper
1.563
316217AC1-145 GEN
Solar/Wind Helper
2.009
943811AF1-049 GEN
Solar/Wind Harmer
0
970223AG2-152 GEN
Solar/Wind Harmer
24.008
970417AG2-272 GEN
50/50
2.951
970481AG2-311 GEN
50/50
Charging
19.349
971629AH1-314 GEN
50/50
12.349
966251AG1-494 GEN
50/50
Charging
4.126
961131AF2-404 GEN
50/50
Charging
2.977
NYPJM->LTFIMP_NY
CLTF
0.212
LGEELTFEXP_LGEE->PJM
CLTF
0.235
WECLTFEXP_WEC->PJM
CLTF
0.127
CPLELTFEXP_CPLE->PJM
CLTF
2.551
LAGNLTFEXP_LAGN->PJM
CLTF
1.775
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.483
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.879
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.066
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.755
TVALTFEXP_TVA->PJM
CLTF
0.917
MECLTFEXP_MEC->PJM
CLTF
0.746
SIGELTFEXP_SIGE->PJM
CLTF
0.021
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
6.913

Details for 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line l/o AEP_P4_#7587_05J.FERR 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7587_05J.FERR 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.54 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:365.69
MW Contribution:19.36
Bus #Bus NameTypeMW Contribution
270173AC1-122 GEN
Solar/Wind Helper
4.153
316123AC1-075 GEN
Solar/Wind Helper
1.387
316197AC1-042 GEN
Solar/Wind Helper
1.565
316217AC1-145 GEN
Solar/Wind Helper
2.012
943811AF1-049 GEN
Solar/Wind Harmer
0
970223AG2-152 GEN
Solar/Wind Harmer
24.003
970481AG2-311 GEN
50/50
Charging
19.362
971629AH1-314 GEN
50/50
12.348
961131AF2-404 GEN
50/50
Charging
2.98
NYPJM->LTFIMP_NY
CLTF
0.213
LGEELTFEXP_LGEE->PJM
CLTF
0.237
WECLTFEXP_WEC->PJM
CLTF
0.129
CPLELTFEXP_CPLE->PJM
CLTF
2.555
LAGNLTFEXP_LAGN->PJM
CLTF
1.785
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.537
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.941
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.085
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.773
TVALTFEXP_TVA->PJM
CLTF
0.922
MECLTFEXP_MEC->PJM
CLTF
0.753
SIGELTFEXP_SIGE->PJM
CLTF
0.022
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
6.935

Details for 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line l/o AEP_P4_#2914_05J.FERR 765_B2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2914_05J.FERR 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.21 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:364.71
MW Contribution:19.35
Bus #Bus NameTypeMW Contribution
270173AC1-122 GEN
Solar/Wind Helper
4.149
316123AC1-075 GEN
Solar/Wind Helper
1.385
316197AC1-042 GEN
Solar/Wind Helper
1.563
316217AC1-145 GEN
Solar/Wind Helper
2.009
943811AF1-049 GEN
Solar/Wind Harmer
0
970223AG2-152 GEN
Solar/Wind Harmer
24.008
970481AG2-311 GEN
50/50
Charging
19.349
971629AH1-314 GEN
50/50
12.349
961131AF2-404 GEN
50/50
Charging
2.977
NYPJM->LTFIMP_NY
CLTF
0.212
LGEELTFEXP_LGEE->PJM
CLTF
0.235
WECLTFEXP_WEC->PJM
CLTF
0.127
CPLELTFEXP_CPLE->PJM
CLTF
2.551
LAGNLTFEXP_LAGN->PJM
CLTF
1.775
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.483
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.879
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.066
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.755
TVALTFEXP_TVA->PJM
CLTF
0.917
MECLTFEXP_MEC->PJM
CLTF
0.746
SIGELTFEXP_SIGE->PJM
CLTF
0.021
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
6.913

Details for 05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line l/o AEP_P7-1_#10781___SRT-A-3


Base Case Flowgate

Area:AEP
Facility Description:
05MUSEVILLE-05SMITHMTN 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10781___SRT-A-3
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:103.45 %
Rating:296.0 MVA
Rating Type:B
MVA to Mitigate:306.2
MW Contribution:13.79
Bus #Bus NameTypeMW Contribution
270173AC1-122 GEN
Solar/Wind Helper
2.81
270030AE2-140 GEN
Solar/Wind Harmer
14.512
316123AC1-075 GEN
Solar/Wind Helper
1.165
316197AC1-042 GEN
Solar/Wind Helper
1.06
316217AC1-145 GEN
Solar/Wind Helper
1.363
943811AF1-049 GEN
Solar/Wind Harmer
0
970223AG2-152 GEN
Solar/Wind Harmer
34.319
970417AG2-272 GEN
50/50
7.782
970481AG2-311 GEN
50/50
Charging
13.795
971629AH1-314 GEN
50/50
30.189
961131AF2-404 GEN
50/50
Charging
2.019
900033ID_568986
External Queue
14.067867279052734
NYPJM->LTFIMP_NY
CLTF
0.121
LGEELTFEXP_LGEE->PJM
CLTF
0.115
WECLTFEXP_WEC->PJM
CLTF
0.055
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.033
LAGNLTFEXP_LAGN->PJM
CLTF
0.33
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.934
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.17
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.676
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.179
TVALTFEXP_TVA->PJM
CLTF
0.183
MECLTFEXP_MEC->PJM
CLTF
0.254
SIGELTFEXP_SIGE->PJM
CLTF
0.009
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.661

Details for 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer l/o DVP_P1-3: 4ALTVSTA-TX#4_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-3: 4ALTVSTA-TX#4_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.84 %
Rating:139.4 MVA
Rating Type:B
MVA to Mitigate:167.06
MW Contribution:7.09
Bus #Bus NameTypeMW Contribution
3146843MT LREL
Solar/Wind Harmer
0.232
3146843MT LREL
Solar/Wind Harmer
0.232
3147123OTTER R
Solar/Wind Harmer
1
3147243WELCO
Solar/Wind Harmer
0.189
3147173SINAI
Solar/Wind Harmer
0.303
270197AD1-017 GEN1
Solar/Wind Helper
1.188
270574AD1-017 GEN2
Solar/Wind Helper
1.069
270173AC1-122 GEN
Solar/Wind Helper
1.539
316197AC1-042 GEN
Solar/Wind Helper
2.7
316217AC1-145 GEN
Solar/Wind Helper
3.471
942751AE2-291 GEN
Solar/Wind Harmer
22.975
944591AF1-124 GEN
Solar/Wind Harmer
5.534
960061AF2-297 GEN
Solar/Wind Harmer
4.846
962561AG1-105 GEN
Solar/Wind Harmer
3.891
970099AG2-077 GEN
Solar/Wind Harmer
2.96
970163AG2-111 GEN
Solar/Wind Harmer
2.785
970165AG2-112 GEN
Solar/Wind Harmer
2.919
970401AG2-262 GEN
Solar/Wind Harmer
0.509
970481AG2-311 GEN
50/50
Charging
7.092
971683AH1-343 GEN
Solar/Wind Harmer
7.864
957481AF2-042 GEN
Solar/Wind Harmer
7.4
964791AG1-342 GEN
Solar/Wind Harmer
1.665
961131AF2-404 GEN
50/50
Charging
5.142
G-007ALTFEXP_G-007A->PJM
CMTX
0.102
NYPJM->LTFIMP_NY
CLTF
0.005
CPLELTFEXP_CPLE->PJM
CLTF
0.709
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.959
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.253
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.784
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.835
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
0.26
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.245

Details for 3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer l/o DVP_P1-3: 4ALTVSTA-TX#3_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-3: 4ALTVSTA-TX#3_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.36 %
Rating:168.45 MVA
Rating Type:B
MVA to Mitigate:177.48
MW Contribution:7.54
Bus #Bus NameTypeMW Contribution
3146843MT LREL
Solar/Wind Harmer
0.247
3146843MT LREL
Solar/Wind Harmer
0.247
3147123OTTER R
Solar/Wind Harmer
1.063
3147243WELCO
Solar/Wind Harmer
0.201
3147173SINAI
Solar/Wind Harmer
0.322
270197AD1-017 GEN1
Solar/Wind Helper
1.263
270574AD1-017 GEN2
Solar/Wind Helper
1.136
270173AC1-122 GEN
Solar/Wind Helper
1.635
316197AC1-042 GEN
Solar/Wind Helper
2.869
316217AC1-145 GEN
Solar/Wind Helper
3.689
942751AE2-291 GEN
Solar/Wind Harmer
24.417
944591AF1-124 GEN
Solar/Wind Harmer
5.881
960061AF2-297 GEN
Solar/Wind Harmer
5.15
962561AG1-105 GEN
Solar/Wind Harmer
4.135
970099AG2-077 GEN
Solar/Wind Harmer
3.146
970163AG2-111 GEN
Solar/Wind Harmer
2.96
970165AG2-112 GEN
Solar/Wind Harmer
3.102
970401AG2-262 GEN
Solar/Wind Harmer
0.541
970481AG2-311 GEN
50/50
Charging
7.537
971683AH1-343 GEN
Solar/Wind Harmer
8.357
957481AF2-042 GEN
Solar/Wind Harmer
7.864
964791AG1-342 GEN
Solar/Wind Harmer
1.77
961131AF2-404 GEN
50/50
Charging
5.465
G-007ALTFEXP_G-007A->PJM
CMTX
0.108
NYPJM->LTFIMP_NY
CLTF
0.006
CPLELTFEXP_CPLE->PJM
CLTF
0.754
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.019
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.269
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.833
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.888
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
VFTLTFEXP_VFT->PJM
CMTX
0.276
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.324
CONTINGENCY 'AEP_P4_#10294_05NEWLDN 138_D_SRT-A'
 OPEN BRANCH FROM BUS 242569 TO BUS 242734 CKT 1   /*05BRUSHT     138.0 - 05NEWLDN     138.0
 OPEN BRANCH FROM BUS 242641 TO BUS 242734 CKT 1   /*05FOREST     138.0 - 05NEWLDN     138.0
 OPEN BRANCH FROM BUS 242687 TO BUS 242734 CKT 1   /*05JOHNMT     138.0 - 05NEWLDN     138.0
 OPEN BRANCH FROM BUS 242687 TO BUS 242741 CKT 1   /*05JOHNMT     138.0 - 05OTTER      138.0
 OPEN BRANCH FROM BUS 242741 TO BUS 314667 CKT 1   /*05OTTER      138.0 - 4ALTVSTA     138.0
END
CONTINGENCY 'AEP_P4_#10293_05NEWLDN 138_C_SRT-A'
 OPEN BRANCH FROM BUS 242561 TO BUS 242641 CKT 1   /*05BOONSBORO  138.0 - 05FOREST     138.0
 OPEN BRANCH FROM BUS 242561 TO BUS 242765 CKT 1   /*05BOONSBORO  138.0 - 05REUSENS1   138.0
 OPEN BRANCH FROM BUS 242569 TO BUS 242734 CKT 1   /*05BRUSHT     138.0 - 05NEWLDN     138.0
 OPEN BRANCH FROM BUS 242641 TO BUS 242734 CKT 1   /*05FOREST     138.0 - 05NEWLDN     138.0
 OPEN BRANCH FROM BUS 242687 TO BUS 242734 CKT 1   /*05JOHNMT     138.0 - 05NEWLDN     138.0
END
CONTINGENCY 'AEP_P4_#10292_05NEWLDN 138_E_SRT-A'
 OPEN BRANCH FROM BUS 242569 TO BUS 242734 CKT 1   /*05BRUSHT     138.0 - 05NEWLDN     138.0
 OPEN BRANCH FROM BUS 242641 TO BUS 242734 CKT 1   /*05FOREST     138.0 - 05NEWLDN     138.0
 OPEN BRANCH FROM BUS 242687 TO BUS 242734 CKT 1   /*05JOHNMT     138.0 - 05NEWLDN     138.0
END
CONTINGENCY 'AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A'
 OPEN BRANCH FROM BUS 242569 TO BUS 242734 CKT 1   /*05BRUSHT     138.0 - 05NEWLDN     138.0
 OPEN BRANCH FROM BUS 242641 TO BUS 242734 CKT 1   /*05FOREST     138.0 - 05NEWLDN     138.0
 OPEN BRANCH FROM BUS 242687 TO BUS 242734 CKT 1   /*05JOHNMT     138.0 - 05NEWLDN     138.0
END
CONTINGENCY 'DVP_P4-2: 151T1047_SRT-A'
 OPEN BRANCH FROM BUS 313168 TO BUS 314696 CKT 1   /*3HUBER DP    115.0 - 3SEDGE HILL  115.0
 OPEN BRANCH FROM BUS 313168 TO BUS 316000 CKT 1   /*3HUBER DP    115.0 - AC1-222 TAP  115.0
 OPEN BRANCH FROM BUS 313825 TO BUS 314696 CKT 1   /*3PLYWOOD     115.0 - 3SEDGE HILL  115.0
 OPEN BUS 313168                                   /*3HUBER DP    115.0
END
CONTINGENCY 'DVP_P4-2: 104702_SRT-A'
 OPEN BRANCH FROM BUS 313168 TO BUS 314696 CKT 1   /*3HUBER DP    115.0 - 3SEDGE HILL  115.0
 OPEN BRANCH FROM BUS 313168 TO BUS 316000 CKT 1   /*3HUBER DP    115.0 - AC1-222 TAP  115.0
 OPEN BUS 313168                                   /*3HUBER DP    115.0
 OPEN BUS 314520                                   /*3SEDGE_1     115.0
END
CONTINGENCY 'DVP_P1-2: LN 13_SRT-A'
 OPEN BRANCH FROM BUS 242741 TO BUS 314667 CKT 1   /*05OTTER      138.0 - 4ALTVSTA     138.0
 OPEN BUS 242687                                   /*05JOHNMT     138.0
 OPEN BUS 242741                                   /*05OTTER      138.0
END
CONTINGENCY 'AEP_P1-2_#375_5201_SRT-A'
 OPEN BRANCH FROM BUS 242687 TO BUS 242734 CKT 1   /*05JOHNMT     138.0 - 05NEWLDN     138.0
 OPEN BRANCH FROM BUS 242687 TO BUS 242741 CKT 1   /*05JOHNMT     138.0 - 05OTTER      138.0
 OPEN BRANCH FROM BUS 242741 TO BUS 314667 CKT 1   /*05OTTER      138.0 - 4ALTVSTA     138.0
END
CONTINGENCY 'AEP_P1-2_#311_5_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 290610 CKT Z1   /*05CLOVRD     765.0 - 05CLOVRD_RJA 765.0
 OPEN BRANCH FROM BUS 242514 TO BUS 290610 CKT 1    /*05J.FERR     765.0 - 05CLOVRD_RJA 765.0
 OPEN BRANCH FROM BUS 242684 TO BUS 242685 CKT ZB   /*05J.FERR     138.0 - 05J.FERX     138.0
END
CONTINGENCY 'AEP_P4_#7587_05J.FERR 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 290610 CKT Z1   /*05CLOVRD     765.0 - 05CLOVRD_RJA 765.0
 OPEN BRANCH FROM BUS 242514 TO BUS 242684 CKT 2    /*05J.FERR     765.0 - 05J.FERR     138.0
 OPEN BRANCH FROM BUS 242514 TO BUS 290610 CKT 1    /*05J.FERR     765.0 - 05CLOVRD_RJA 765.0
 OPEN BRANCH FROM BUS 242684 TO BUS 242685 CKT ZB   /*05J.FERR     138.0 - 05J.FERX     138.0
END
CONTINGENCY 'AEP_P4_#2914_05J.FERR 765_B2_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 290610 CKT Z1   /*05CLOVRD     765.0 - 05CLOVRD_RJA 765.0
 OPEN BRANCH FROM BUS 242514 TO BUS 245993 CKT 4    /*05J.FERR     765.0 - 05J.FERR SVS  20.6
 OPEN BRANCH FROM BUS 242514 TO BUS 290610 CKT 1    /*05J.FERR     765.0 - 05CLOVRD_RJA 765.0
 OPEN BRANCH FROM BUS 242684 TO BUS 242685 CKT ZB   /*05J.FERR     138.0 - 05J.FERX     138.0
 REMOVE SWSHUNT FROM BUS 242514                     /*05J.FERR     765.0
END
CONTINGENCY 'AEP_P7-1_#10781___SRT-A-3'
 OPEN BRANCH FROM BUS 242531 TO BUS 304094 CKT 1   /*05EDANV2     230.0 - 6YANCY TAP   230.0
 OPEN BRANCH FROM BUS 304094 TO BUS 304095 CKT 1   /*6YANCY TAP   230.0 - 6YANCYVILLE  230.0
 OPEN BRANCH FROM BUS 304094 TO BUS 304097 CKT 1   /*6YANCY TAP   230.0 - 6CONCD2230TT 230.0
 OPEN BRANCH FROM BUS 900033 TO BUS 304024 CKT 1   /*ID_568986    230.0 - 6ROXSEP230 T 230.0
END
CONTINGENCY 'DVP_P1-3: 4ALTVSTA-TX#4_SRT-A'
 OPEN BRANCH FROM BUS 314666 TO BUS 314667 CKT 2   /*3ALTVSTA     115.0 - 4ALTVSTA     138.0
END
CONTINGENCY 'DVP_P1-3: 4ALTVSTA-TX#3_SRT-A'
 OPEN BRANCH FROM BUS 314666 TO BUS 314667 CKT 1   /*3ALTVSTA     115.0 - 4ALTVSTA     138.0
END
242701 to 242802 ckt 1
290234 to 242802 ckt 1
314666 to 314667 ckt 1
314666 to 314667 ckt 2

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-038Lexington-Low Moor 230kVUnder Construction
AA1-139Hickory-Shawboro 230kVIn Service
AB1-006Meadow Lake 345kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-180Pine View 12kVIn Service
AB2-022Elizabeth City 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-134Hopewell-Surry 230kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-001Delano 138kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVSuspended
AC1-036Twittys Creek 34.5kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-053Lanesville-BrokawPartially in Service - Under Construction
AC1-074Jacksonville-Renaker 138kV IIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-082Ravenswood-Hemlock 69kVUnder Construction
AC1-085Stuart-Clinton 345kVIn Service
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-101Johns Creek-Excel 138kV ISuspended
AC1-102Johns Creek-Excel 138kV IISuspended
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-111Aurora 138kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-188Rio-Lick 138kVEngineering & Procurement
AC1-191Elmont 115kVEngineering & Procurement
AC1-194Elk 138kVActive
AC1-214Crescent RidgeIn Service
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-075Jacksonville-Renaker 138 kVIn Service
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-100Halifax-Person 230kVIn Service
AC2-111College Corner 138kVEngineering & Procurement
AC2-123Jacksons Ferry 138kVIn Service
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-157Sullivan 345 kVUnder Construction
AC2-165Bremo-Powhatan 230kVSuspended
AD1-013Twombly Road 138kVEngineering & Procurement
AD1-017Smith Mountain-Bearskin 138 kVIn Service
AD1-025Hopewell-Surry 230 kVUnder Construction
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-128Modoc-Delaware 138 kVPartially in Service - Under Construction
AD1-136South Bethel-Brown 69 kVIn Service
AD1-144Kings Fork 34.5 kVIn Service
AD1-152Clover-Sedge Hill 230 kVIn Service
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-022East Danville - Roxborough 230 kVEngineering & Procurement
AD2-023East Danville - Roxborough 230 kVEngineering & Procurement
AD2-030Wan 34.5 kVIn Service
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-048Cynthia-Headquarters 69 kVUnder Construction
AD2-066Mazon-Crescent Ridge 138 kVEngineering & Procurement
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVEngineering & Procurement
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-100Kincaid-Pana 345 kVSuspended
AD2-131Kincaid-Pana 345kVSuspended
AD2-134Shady OaksPartially in Service - Under Construction
AD2-160Hickory-Moyock 230kVIn Service
AD2-172Lena 138kVIn Service
AD2-179Morgans Cut-Glen Lyn 138kVSuspended
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-040Greenfield 69 kVIn Service
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-100Axton 138 kVIn Service
AE1-113Mole Creek 345 kVEngineering & Procurement
AE1-114Maryland-Lancaster 138 kVActive
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-162Smithfield 34.5 kVIn Service
AE1-163Powerton-Nevada 345 kVEngineering & Procurement
AE1-172Loretto-Wilton CenterActive
AE1-175Light Foot 34.5 kVIn Service
AE1-176Roanoke-Vinton 12 kV (Niagara Hydro)In Service
AE1-190Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-191Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-212Grandview-Clifftop 138 kVSuspended
AE1-250Smith Mountain-E. Danville 138 kVEngineering & Procurement
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-035Lena 138 kVIn Service
AE2-047Ridgeway-Solite 69 kVEngineering & Procurement
AE2-071Patton Rd-Summer Shade 69 kVIn Service
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-140Axton-Danville 138 kVSuspended
AE2-160Kanawha River 138 kVEngineering & Procurement
AE2-166Stockton 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-173McLean 345 kVActive
AE2-185Gladys DP-Stonemill Switching Station 69 kVActive
AE2-187Shockoe DP-Chatham 69 kVActive
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVActive
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-253Hickory-Moyock 230 kVIn Service
AE2-254Garrard County-Tommy-Gooch 69 kVIn Service
AE2-255Molecreek 345 kVEngineering & Procurement
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-261Kincaid-Pana 345 kVActive
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-281Powerton-Nevada 345 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVActive
AE2-291Grit DP-Perth 115 kVActive
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-308Three Forks-Dale 138 kVActive
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-321Belvidere-Marengo 138 kVActive
AE2-326Jacksons Ferry 138 kVEngineering & Procurement
AE2-339Avon 138 kVEngineering & Procurement
AE2-341Sandwich-Plano 138 kVActive
AF1-030Sandwich-Plano 138 kVActive
AF1-032Suffolk 34.5 kVIn Service
AF1-038Sewellton Jct-Webbs Crossroads 69 kVEngineering & Procurement
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-045Cedarville-Ford 138 kVSuspended
AF1-049Berry Hill 138 kVUnder Construction
AF1-050Summer Shade - Green County 161 kVEngineering & Procurement
AF1-058Welco 34.5 kVIn Service
AF1-083Green County-Saloma 161 kVEngineering & Procurement
AF1-088Sullivan 345 kVActive
AF1-090Kincaid-PanaEngineering & Procurement
AF1-124Harper 230 kVActive
AF1-130Inez 138 kVSuspended
AF1-162Inez 138 kVEngineering & Procurement
AF1-203Patton Rd-Summer Shade 69 kVIn Service
AF1-204Eugene 345 kVActive
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-233Flemingsburg – Spurlock 138kVActive
AF1-249Nickel 12.47 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-296Garden Plain 138 kVActive
AF1-322Meadow Lake 345 kVEngineering & Procurement
AF1-331Twombley RoadEngineering & Procurement
AF2-008Sullivan 345 kVActive
AF2-018Inez 138 kVEngineering & Procurement
AF2-032Kincaid 345 kVEngineering & Procurement
AF2-041Nelson-Electric Junction 345 kVActive
AF2-042Clover-Rawlings 500 kVActive
AF2-043Suffolk 34.5 kVIn Service
AF2-048Rio-Lick 138 kVEngineering & Procurement
AF2-054Wan 34.5 kVIn Service
AF2-069Crescent Ridge 138 kVActive
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-106Hazel Hollow-Glen Lyn #1 138 kVEngineering & Procurement
AF2-107Clifford 138 kVEngineering & Procurement
AF2-111North Clark-Spurlock 345 kVActive
AF2-142Nevada 345 kVActive
AF2-143Powerton-Nevada 345 kVActive
AF2-144Powhatan 34.5 kVIn Service
AF2-173Desoto 345 kVActive
AF2-199Nelson-Electric Junction 345 kVActive
AF2-200Nelson-Electric Junction 345 kVActive
AF2-225McLean 345 kVActive
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-297Sedge Hill 115 kVActive
AF2-307Hope-Belvins Valley Tap 69 kVActive
AF2-311Gilboa-Jones Branch 138 kVEngineering & Procurement
AF2-316Gilboa-Jones Branch 138 kV IIEngineering & Procurement
AF2-335Delaware-Royerton 138 kVActive
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-365Munfordville KU Tap-Horse Cave Jct. 69 kVActive
AF2-382Hurley 69 kVEngineering & Procurement
AF2-392Nelson-Dixon 138 kVActive
AF2-404Gladys DP-Stonemill 69 kVActive
AF2-440Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-066Bonnyman 69 kVEngineering & Procurement
AG1-070Bon Ayr 69 kVActive
AG1-071Bon Ayr 69 kVActive
AG1-105Mount Laurel-Barnes Junction 115 kVActive
AG1-107Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-118Sugar Grove-Waterman 138kVActive
AG1-124Gladstone 138 kVActive
AG1-127Crego Rd 138 kVActive
AG1-145Lightfoot 34.5 kVIn Service
AG1-226Dequine-Eugene 345 kVActive
AG1-236Lanesville-Brokaw 345 kVActive
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVEngineering & Procurement
AG1-320Glendale-Stephensburg 69 kVActive
AG1-341Summer Shade 161 kVActive
AG1-342Dryburg 115 kVActive
AG1-354Summershade-Green County 161 kVActive
AG1-367DeSoto 345 kVActive
AG1-374Blue Mound 345 kVActive
AG1-405Walnut Grove-Asahi 69 kVActive
AG1-406Walnut Grove-Asahi 69 kVActive
AG1-460Kincaid-Pana 345 kVActive
AG1-462Cordova 345 kVActive
AG1-469Gordonsville 34.5 kVEngineering & Procurement
AG1-471Up Church-Wayne County 69 kVActive
AG1-494Boxwood-Riverville 138 kVActive
AG1-508Point Lookout 69 kVEngineering & Procurement
AG1-526West Garrard 345 kVActive
AG1-555Dequine 345 kVEngineering & Procurement
AG1-558Buckner 34.5 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
AG2-068Heritage - Wake 500 kVActive
AG2-069Heritage - Wake 500 kVActive
AG2-072Rockport 765 kVActive
AG2-073Crooksville 69 kVActive
AG2-077Clover-Rawlings 500 kVActive
AG2-081Mt. Sterling-Fogg Pike 69 kVActive
AG2-085Delaware-Royerton 138 kVActive
AG2-111Perth 34.5 kV Substation (Circuit 408)Active
AG2-112Perth 34.5 kV Substation (Circuit 404)Active
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-126Eugene 345 kVActive
AG2-152Banister-Bear Skin 138 kVActive
AG2-159Williamstown 69 kVActive
AG2-162Jefferson-Greentown 765 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-164Jefferson-Greentown 765 kVActive
AG2-179Sewellton Junction 69 kVActive
AG2-184Harbert Metering 138 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-219Jefferson-Greentown 765 kVActive
AG2-262Dryburg 115 kVActive
AG2-272Berry Hill 138 kVActive
AG2-298Sulphur Creek-Loretto 69 kVActive
AG2-310Matt Funk 138 kVActive
AG2-331Jefferson-Greentown 765 kVActive
AG2-360Broadford 138 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-369Heritage - Wake 500 kVActive
AG2-401Losantville 345 kVActive
AG2-424Magnolia - Summersville 69 kVActive
AG2-449Jefferson-Greentown 765 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-516Pecatonica 138kVActive
AG2-518Tech Drive 138 kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-541Perth - Crystal Hill 115 kVActive
AG2-548Corwin - Elk 138 kVActive
AG2-568Stink Run – Sundial 138 kVActive
AG2-570Heritage - Wake 500 kVActive
AG2-571Heritage - Wake 500 kVActive
AG2-575Crego Rd. 138 kVActive
AG2-589Ravenswood - Hemlock 69 kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-657Kanawha River - Carbondale 138 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-665Corwin - Elk 138 kVActive
AG2-670Green County -Taylor County Junction 161 kVActive
AH1-004Avon - Renaker 138 kVActive
AH1-034Patton Road Junction - Summer Shade 69 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-047Marengo - Belvidere 138 kVActive
AH1-055Kyger Creek - Don Marquis 345 kVActive
AH1-072Red Onion - VC5 69 kVActive
AH1-073Red Onion - VC5 69 kVActive
AH1-098Wolf Glade-West Carroll 138 kVActive
AH1-133Saltville - Tazewell 138 kVActive
AH1-136Falcon - Middle Creek 46 kVActive
AH1-144Peter's Mountain 138 kVActive
AH1-145Peter's Mountain 138 kVActive
AH1-146White Rock - Wayne 345 kVActive
AH1-147White Rock - Wayne 345 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-164Oak Level - Tank Hill 138 kVActive
AH1-188Pigeon Creek 138 kVActive
AH1-196Prairie 345 kVActive
AH1-227Flemming - Fremont 69 kVActive
AH1-234Wempletown - Paddock 345 kVActive
AH1-239Upchurch - Zula 69 kVActive
AH1-269Claytor 138 kVActive
AH1-281Bluegrass Parkway Tap - Woodlawn 69 kVActive
AH1-285Sandwich 138 kVActive
AH1-292Sullivan 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-311Heartsease DP - Mayo Dunbar 115kVActive
AH1-314East Danville 138 kVActive
AH1-337Randolph - Hodgin 138 kVActive
AH1-338McGirr Rd - Ritchie Road 138kVActive
AH1-341Stillman - Dixon 138KVActive
AH1-343Crystal Hill DP- Perth 115kVActive
AH1-348Pound 34.5 kVActive
AH1-427Tommy Gooch - Garrard County 69 kVActive
AH1-535Nagel - Cane River 230 kVActive
AH1-537Pierce - Kyger Creek 345 kVActive
AH1-541Chestnut 345 kVActive
AH1-543Mulberry – Tazewell 345 kVActive
AH1-570Headquarters - Millersburg Junction 69 kVActive
AH1-571Headquarters - Millersburg Junction 69 kVActive
AH1-617Harbert Metering 138 kVActive
AH1-644Spicewood Metering 138 kVActive
AH1-664Goddard-Plumville 138 kVActive
AH1-665Goddard-Plumsville 138 kV IIActive
AH1-666Flemingsburg - Spurlock 138 kVActive
AH1-670Blue Mound-Chestnut 345 kVActive
AH1-686Hanging Rock 765 kVActive
AH1-702Byron 345 kVActive
AH1-718Nelson 345 kVActive
AH1-721Laurel-Cooper 161 kVActive
V3-007Desoto-Tanners Creek #1 345kVIn Service
W2-048Brokaw-LanesvilleIn Service
W4-005Blue Mound-LathamIn Service
X2-022Brokaw-LanesvilleIn Service
Y1-049Wurno 34.5kVIn Service
Y1-086Morgans CornerIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Study Pending
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase I analysis results, this project may have a cost responsibility for the following System Reinforcements:

AG2-311 System Reinforcements:
TORTEP IDTitleAllocated Cost ($USD)
AEP(Pending) / AEP-TC2-1870405SMITHMTN 138.0 kV to 05LEESVI 138.0 kV ckt 1 - Rebuild$6,172,896
Dominionn9132.0 / dom-122Add 3rd 138/115 kV transformer at Altavista substation$3,776,023
Dominion(Pending) / TC1-PH1-DOM-096Wreck and rebuild 2.8 mi of 115 kV Line 15 between Huber DP and Sedgehill with (1) 768,2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C$622,404
Dominion(Pending) / TC2-PH1-DOM-2001Wreck and rebuild 2.66 miles of 115 kV line 1016 between Crystal Hill DP and AH1-343 with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.$592,053
AEP(Pending) / AEP-TC2-1871705BANSTR 138.0 kV to 05EDAN 2 138.0 kV ckt 1 - Sag Study and Replace Equipment$276,475
Dominion(Pending) / TC2-PH1-DOM-2002Replace 556.6 ACSR line lead on line 104 at AltaVista 138 kV$241,586
Dominion(Pending) / dom-184Wreck and rebuild 0.97 mi of 115 kV Line 15 between Woodchuck Trail and Huber DP with (1) 768,2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C$215,619
AEP(Pending) / AEP-TC2-1865505MUSEVILLE 138.0 kV to 05SMITHMTN 138.0 kV ckt 1 - Replace Switch$63,625
AEP(Pending) / AEPAPRJV004Replace wavetrap @ New London$26,550
Dominionn8423 / dom-119Wreck and rebuild 0.06 miles of 115 kV line 1016 between Woodchuck Trail and Crystal Hill DP with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.$13,355
AEP(Pending) / AEP-TC2-18709AG2-152 TP 138.0 kV to 05BANSTR 138.0 kV ckt 1 - Sag Study and Upgrade Equipment$8,132
Grand Total:$12,008,718

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18704
Title
05SMITHMTN 138.0 kV to 05LEESVI 138.0 kV ckt 1 - Rebuild
Description
Rebuild ~8.2 miles of 138 kV line between Smith Mountain and Leesville, upgrade 795 AAC station conductor at Smith Mountain and Leesville.
Total Cost ($USD)
$32,000,000
Allocated Cost ($USD)
$6,172,896
Time Estimate
36 to 48 Months

Contributor

FacilityContingency
05LEESVI-05SMITHMTN 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-111
3.8 MW5.3%$1,710,840
AG2-112
4.0 MW5.6%$1,793,537
AG2-152
29.8 MW41.4%$13,245,672
AG2-311
13.9 MW19.3%$6,172,896
AG2-541
13.6 MW18.9%$6,049,740
AH1-343
6.8 MW9.5%$3,027,315

System Reinforcement: n9132.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9132.0 / dom-122
Title
Add 3rd 138/115 kV transformer at Altavista substation
Description
Add 3rd 138/115 kV transformer at Altavista substation
Total Cost ($USD)
$11,000,000
Allocated Cost ($USD)
$3,776,023
Time Estimate
42 to 44 Months

Contributor

FacilityContingency
3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 1 transformer(Any)
3ALTVSTA-4ALTVSTA 115.0/138.0 kV Ckt 2 transformer(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-111
5.7 MW13.5%$1,482,894
AG2-112
6.0 MW14.1%$1,554,135
AG2-311
14.6 MW34.3%$3,776,023
AH1-343
16.2 MW38.1%$4,186,949

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH1-DOM-096
Title
Wreck and rebuild 2.8 mi of 115 kV Line 15 between Huber DP and Sedgehill with (1) 768,2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C
Description
Wreck and rebuild 2.8 mi of 115 kV Line 15 between Huber DP and Sedgehill with (1) 768,2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C
Total Cost ($USD)
$8,960,000
Allocated Cost ($USD)
$622,404
Time Estimate
30 to 36 Months

Contributor

FacilityContingency
3HUBER DP-3SEDGE HILL 115.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-111
5.0 MW5.8%$516,143
AG2-112
5.3 MW6.0%$541,145
AG2-152
13.0 MW14.9%$1,335,495
AG2-311
6.1 MW6.9%$622,404
AG2-541
27.0 MW30.9%$2,768,644
AH1-343
31.0 MW35.4%$3,176,168

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2001
Title
Wreck and rebuild 2.66 miles of 115 kV line 1016 between Crystal Hill DP and AH1-343 with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 2.66 miles of 115 kV line 1016 between Crystal Hill DP and AH1-343 with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$8,512,000
Allocated Cost ($USD)
$592,053
Time Estimate
30 to 36 Months

Contributor

FacilityContingency
3CRSTL HILL-AH1-343 TP 115.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-111
5.0 MW5.8%$490,200
AG2-112
5.3 MW6.0%$513,936
AG2-152
13.1 MW14.9%$1,270,297
AG2-311
6.1 MW7.0%$592,053
AG2-541
27.0 MW30.9%$2,629,314
AH1-343
31.0 MW35.4%$3,016,201

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18717
Title
05BANSTR 138.0 kV to 05EDAN 2 138.0 kV ckt 1 - Sag Study and Replace Equipment
Description
Replace first overhead conductor span from East Danville to Structure 18-135 (1033 ACSR); Conduct sag clearance study on 10.7 miles between Structure 18-135 and Banister; Replace 1590 AAC station conductor at Banister; Replace 2000 AAC station conductor at East Danville
Total Cost ($USD)
$1,700,000
Allocated Cost ($USD)
$276,475
Time Estimate
36 to 48 Months

Contributor

FacilityContingency
05BANSTR-05EDAN 2 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-152
80.4 MW68.7%$1,167,298
AG2-311
19.0 MW16.3%$276,475
AG2-541
8.6 MW7.3%$124,289
AH1-343
9.1 MW7.8%$131,938

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2002
Title
Replace 556.6 ACSR line lead on line 104 at AltaVista 138 kV
Description
Replace 556.6 ACSR line lead on line 104 at AltaVista 138 kV
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$241,586
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-152
6.9 MW39.6%$158,414
AG2-311
10.5 MW60.4%$241,586

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / dom-184
Title
Wreck and rebuild 0.97 mi of 115 kV Line 15 between Woodchuck Trail and Huber DP with (1) 768,2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C
Description
Wreck and rebuild 0.97 mi of 115 kV Line 15 between Woodchuck Trail and Huber DP with (1) 768,2 ACSS/TW (20/7) "Maumee" conductor @ 250 Deg. C
Total Cost ($USD)
$3,104,000
Allocated Cost ($USD)
$215,619
Time Estimate
30 to 36 Months

Contributor

FacilityContingency
3HUBER DP-AC1-222 TAP 115.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-111
5.0 MW5.8%$178,807
AG2-112
5.3 MW6.0%$187,468
AG2-152
13.0 MW14.9%$462,654
AG2-311
6.1 MW6.9%$215,619
AG2-541
27.0 MW30.9%$959,137
AH1-343
31.0 MW35.4%$1,100,315

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18655
Title
05MUSEVILLE 138.0 kV to 05SMITHMTN 138.0 kV ckt 1 - Replace Switch
Description
Replace 138 kV Switch at Smith Mountain "C1S2"
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$63,625
Time Estimate
36 to 48 Months

Contributor

FacilityContingency
05SMITHMTN-05MUSEVILLE 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-152
112.6 MW74.0%$370,179
AG2-272
7.8 MW5.1%$25,589
AG2-311
19.3 MW12.7%$63,625
AH1-314
12.3 MW8.1%$40,607

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEPAPRJV004
Title
Replace wavetrap @ New London
Description
Replace wavetrap @ New London
Total Cost ($USD)
$260,000
Allocated Cost ($USD)
$26,550
Time Estimate
18 to 24 Months

Contributor

FacilityContingency
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-111
4.7 MW7.1%$18,378
AG2-112
4.9 MW7.4%$19,267
AG2-152
6.6 MW10.0%$25,960
AG2-311
6.8 MW10.2%$26,550
AG2-541
20.9 MW31.7%$82,388
AH1-343
22.2 MW33.6%$87,457

System Reinforcement: n8423
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n8423 / dom-119
Title
Wreck and rebuild 0.06 miles of 115 kV line 1016 between Woodchuck Trail and Crystal Hill DP with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 0.06 miles of 115 kV line 1016 between Woodchuck Trail and Crystal Hill DP with (1) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$192,000
Allocated Cost ($USD)
$13,355
Time Estimate
30 to 36 Months

Contributor

FacilityContingency
3CRSTL HILL-AC1-222 TAP 115.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-111
5.0 MW5.8%$11,057
AG2-112
5.3 MW6.0%$11,593
AG2-152
13.1 MW14.9%$28,653
AG2-311
6.1 MW7.0%$13,355
AG2-541
27.0 MW30.9%$59,308
AH1-343
31.0 MW35.4%$68,035

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18709
Title
AG2-152 TP 138.0 kV to 05BANSTR 138.0 kV ckt 1 - Sag Study and Upgrade Equipment
Description
Upgrade 1590 AAC station conductor at Banister. Perform sag clearance study for ~0.5 mile of 138 kV line between AG2-152 and Banister to determine any potential mitigation required to operate at a higher temperature.
Total Cost ($USD)
$50,000
Allocated Cost ($USD)
$8,132
Time Estimate
36 to 48 Months

Contributor

FacilityContingency
05BANSTR-AG2-152 TP 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-152
80.4 MW68.7%$34,332
AG2-311
19.0 MW16.3%$8,132
AG2-541
8.6 MW7.3%$3,656
AH1-343
9.1 MW7.8%$3,881

System Reinforcement: b4000.211
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.211
Title
Rebuild 6.5 miles of Johnson Mountain - New London 138 kV line
Description
Rebuild 6.5 miles of Johnson Mountain - New London 138 kV line Projected In Service Date: 06/01/2029
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-311 may not presently have cost responsibility for this upgrade, AG2-311 may need this upgrade in-service to be deliverable to the PJM system. If AG2-311 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05JOHNMT-05NEWLDN 138.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.210
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.210
Title
Rebuild 7 miles of Otter - Johnson Mountain 138 kV line.
Description
Rebuild 7 miles of Otter - Johnson Mountain 138 kV line.
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-311 may not presently have cost responsibility for this upgrade, AG2-311 may need this upgrade in-service to be deliverable to the PJM system. If AG2-311 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05JOHNMT-05OTTER 138.0 kV Ckt 1 line(Any)

System Reinforcement: n6594.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n6594.1 / AEPA0044a
Title
Rebuild 8.4 miles section of the Leesville - Alta Vista 138 kV line
Description
Rebuild 8.4 miles section of the Leesville - Alta Vista 138 kV line
Total Cost ($USD)
$23,571,948
Allocated Cost ($USD)
$0
Time Estimate
Nov 21 2027

Contingent

Note: Based on PJM cost allocation criteria, AG2-311 does not receive cost allocation towards this upgrade which has been securitized by a prior Queue/Cycle. Although AG2-311 may not have cost responsibility for this upgrade, AG2-311 may need this upgrade in-service to be deliverable for the reliability to the PJM system. If AG2-311 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.207
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.207
Title
Leesville Station Upgrade 138 kV
Description
Leesville Station Upgrade 138 kV: Replace 795 KCM AAC, 37-Str. IPS Sch. 40 1272 KCM AAC, 61-Str. 1272 KCM AAC, 61-Str. PH A,B,C ALTA VISTA CB-A BUS DISC ALTA VISTA CB-A LINE DISC Wavetrap (1200A) Relay Thermal Limit 1356 Amps
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-311 may not presently have cost responsibility for this upgrade, AG2-311 may need this upgrade in-service to be deliverable to the PJM system. If AG2-311 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line(Any)

System Reinforcement: n5613
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n5613 / AEPA0014a
Title
Rebuild 0.9 miles of the Otter - Alta Vista 138 kV line.
Description
Rebuild 0.9 miles of the Otter - Alta Vista 138 kV line.
Total Cost ($USD)
$2,740,849
Allocated Cost ($USD)
$0
Time Estimate
Nov 21 2027

Contingent

Note: Based on PJM cost allocation criteria, AG2-311 does not receive cost allocation towards this upgrade which has been securitized by a prior Queue/Cycle. Although AG2-311 may not have cost responsibility for this upgrade, AG2-311 may need this upgrade in-service to be deliverable for the reliability to the PJM system. If AG2-311 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05OTTER-4ALTVSTA 138.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending)
Title
Most limiting rating on the Dominion side is the Wave Trap and Lead at Altavista: 363 / 382 /420 MVA.
Description
Most limiting rating on the Dominion side is the Wave Trap and Lead at Altavista: 363 / 382 /420 MVA.
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
99 Months

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
05OTTER-4ALTVSTA 138.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0044
Title
Wreck and rebuild 4.5 miles of 230 kV Line 2204 between Black Walnut and Edmonson with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 4.5 miles of 230 kV Line 2204 between Black Walnut and Edmonson with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$17,100,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-311 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-311 could receive cost allocation. Although AG2-311 may not presently have cost responsibility for this upgrade, AG2-311 is a potential Aggregate Pool Contributor.

FacilityContingency
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0045
Title
Wreck and rebuild 8.3 miles of 230 kV Line 2250 between Edmonson and Sedge Hill with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 8.3 miles of 230 kV Line 2250 between Edmonson and Sedge Hill with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$31,540,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-311 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-311 could receive cost allocation. Although AG2-311 may not presently have cost responsibility for this upgrade, AG2-311 is a potential Aggregate Pool Contributor.

FacilityContingency
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-311 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-311 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AG2-311 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-311 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AG2-311 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-311 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.355
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-311 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-311 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AG2-311 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-311 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AG2-311 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-311 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AG2-311 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-311 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-311 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-311 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-311 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-311 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-311 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-311 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-311 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-311 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-311 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-311 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-311 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-311 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-311 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-311 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-311 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-311 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-311 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-311 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)
          Perth 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-111, AG2-112
        

Attachments

AG2-311 One Line Diagram

AG2-311 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.