AG2-341 Phase I Study Report

v1.00 released 2025-10-29 22:07

Ridge Road 115 kV

20.0 MW Capacity / 50.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Mighty Blue LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed a Storage facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — Mecklenburg County, Virginia. The installed facilities will have a total capability of 50.0 MW with 20.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-341
Project Name:
Ridge Road 115 kV
Project Developer Name:
Mighty Blue LLC
State:
Virginia
County:
Mecklenburg
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
50.0
MWE:
50.0
MWC:
20.0
Battery Storage Specification:
200.0 MWh, 4.0-hr class
Grid Charging:
Yes
Fuel Type:
Storage
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AG2-341 will interconnect on the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) transmission system at the Ridge Road 115 kV Substation.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AG2-341 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-341Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$3,200,000$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$5,000,000$5,000,000
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$1,517,742$1,517,742
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$9,717,742$6,517,742

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AG2-341

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AG2-341 Project due at DP1
ABA - B
AG2-341$651,774$200,000$451,774

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Interconnection Facilities
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Install the Point of Change in Ownership (PCO) disconnect switch, the overhead line conductor from the PCO to the bus position that serves as the Point of Interconnection (POI), as well as any metering and associated protection equipment.$3,200,000 $3,200,000
Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Add two (2) new 115 kV breakers to the existing Ridge Road 115 kV Substation. Additional substation modification/expansion cost may be required after detailed design.$5,000,000 $5,000,000

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 36 to 40 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2028 load flow model and the results were verified by Dominion.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-341 was evaluated as a 50.0 MW (20.0 MW Capacity) injection in the Dominion area.

AG2-341 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 50.0 MW (50.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 593_SRT-A
SingleAC111.98 %239.89B268.621.95
GD2DVP
3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 587_SRT-A-1
SingleAC107.24 %239.89B257.271.95
GD2DVP
3CLOUD-6CLOUD 115.0/230.0 kV Ckt 1 transformer
DVP_P4-3: CLOUD H222_SRT-A
BreakerAC105.97 %288.0C305.194.9
GD2DVP
3CLOUD-6CLOUD 115.0/230.0 kV Ckt 1 transformer
DVP_P4-2: 222922-4_SRT-A
BreakerAC104.11 %288.0C299.834.55
GD2DVP
3CLOUD-6CLOUD 115.0/230.0 kV Ckt 2 transformer
DVP_P4-3: CLOUD H122_SRT-A
BreakerAC103.38 %295.2C305.194.9
GD2DVP
3CLOUD-6CLOUD 115.0/230.0 kV Ckt 2 transformer
DVP_P4-2: 222922-3_SRT-A
BreakerAC101.57 %295.2C299.834.55
GD2DVP
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 2201_SRT-S
SingleAC132.37 %250.89B332.11.66
GD2DVP
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 254_SRT-S
SingleAC127.2 %250.89B319.141.66
GD2DVP
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 298_SRT-A-1
SingleAC143.44 %198.15B284.231.86
GD2DVP
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
DVP_P1-2: LN 235_SRT-A-4
SingleAC203.55 %182.74B371.982.5
GD2DVP
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
DVP_P1-2: LN 1012_SRT-A-2
SingleAC163.16 %182.74B298.151.01
GD2DVP
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
DVP_P7-1: LN 1041-38_SRT-A
TowerAC150.91 %208.7C314.942.05
GD2DVP
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
DVP_P7-1: LN 1041-137_SRT-A
TowerAC146.35 %208.7C305.443.21
GD2DVP
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
Base Case
SingleAC111.74 %176.91A197.681.47
GD2CPLE/DVP
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC110.62 %199.0B220.142.95
GD2CPLE/DVP
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
DVP_P4-5: 593X2_SRT-A
BreakerAC108.8 %199.0B216.522.95
GD2CPLE/DVP
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
DVP_P4-5: 593X1_SRT-A
BreakerAC108.8 %199.0B216.512.95
GD2CPLE/DVP
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC106.88 %199.0B212.682.95
GD2CPLE/DVP
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC106.88 %199.0B212.682.95
GD2DVP
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer
DVP_P4-6: SEDGE H T452_SRT-A
BreakerAC130.8 %264.1C345.452.37
GD2DVP
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer
DVP_P4-5: SEDGE H L202_SRT-A
BreakerAC130.8 %264.1C345.452.37
GD2DVP
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer
DVP_P1-3: 6SEDGE HILL-TX#2_SRT-A
SingleAC101.36 %242.52B245.832.37
GD2DVP
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer
DVP_P4-2: 3202_SRT-A
BreakerAC131.16 %276.6C362.792.36
GD2DVP
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer
DVP_P4-5: SEDGE H L102_SRT-A
BreakerAC124.48 %276.6C344.322.36
GD2DVP
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
Base Case
SingleAC156.12 %186.12A290.571.16
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC203.13 %678.68B1378.62.24
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC185.6 %830.0C1540.52.24
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC185.6 %830.0C1540.492.24
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC173.49 %830.0C1439.972.16
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC173.49 %830.0C1439.972.16
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-3
SingleAC158.61 %678.68B1076.482.18
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: 242T2027_SRT-A
BreakerAC148.82 %830.0C1235.222.18
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P2-2: BREMO B3_SRT-A
BusAC130.0 %830.0C1079.042.13
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Base Case
SingleAC113.92 %678.68A773.161.89
GD2DVP
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 2028_SRT-A
SingleAC118.12 %800.88B946.031.3
GD2DVP
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC117.42 %800.88B940.371.35
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC202.03 %678.68B1371.172.24
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC184.71 %830.0C1533.112.24
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC184.71 %830.0C1533.12.24
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC172.6 %830.0C1432.612.16
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC172.6 %830.0C1432.612.16
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-3
SingleAC157.52 %678.68B1069.032.18
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: 202712_SRT-S
BreakerAC147.93 %830.0C1227.792.18
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P2-2: BREMO B3_SRT-A
BusAC129.14 %830.0C1071.92.13
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Base Case
SingleAC112.86 %678.68A765.971.89
GD2DVP
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC131.81 %571.52B753.291.99
GD2DVP
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC129.23 %571.52B738.581.99
GD2DVP
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC129.16 %699.0C902.852.0
GD2DVP
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC129.12 %699.0C902.562.0
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC212.98 %699.0C1488.764.63
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC212.93 %699.0C1488.374.63
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC209.35 %699.0C1463.374.62
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC207.29 %571.52B1184.74.62
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC204.76 %571.52B1170.274.62
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC203.45 %699.0C1422.114.62
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC203.45 %699.0C1422.114.62
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC130.37 %699.0C911.292.93
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P7-1: LN 2106-2111_SRT-A
TowerAC130.23 %699.0C910.332.83
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P7-1: LN 2003-205_SRT-S
TowerAC126.86 %699.0C886.732.9
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
BusAC118.39 %699.0C827.522.87
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Base Case
SingleAC112.79 %571.52A644.612.85
GD2DVP
6CAROLNA-6NORTHAMPTON 230.0 kV Ckt 1 line
DVP_P1-2: LN 238_SRT-A
SingleAC101.63 %559.3B568.391.36
GD2DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC145.18 %984.18B1428.841.57
GD2DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P1-2: LN 2002_SRT-A
SingleAC121.21 %984.18B1192.961.33
GD2DVP
6CARSON-6POE 230.0 kV Ckt 1 line
DVP_P1-2: LN 249_SRT-A
SingleAC124.58 %678.68B845.481.04
GD2DVP
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 2028_SRT-A
SingleAC121.53 %800.88B973.31.3
GD2DVP
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC119.72 %800.88B958.851.35
GD2DVP
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC142.99 %984.18B1407.241.57
GD2DVP
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
DVP_P1-2: LN 2002_SRT-A
SingleAC119.0 %984.18B1171.161.33
GD2DVP
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC131.7 %678.68B893.852.32
GD2DVP
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC131.06 %678.68B889.452.32
GD2DVP
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC126.07 %830.0C1046.372.34
GD2DVP
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC125.99 %830.0C1045.72.34
GD2DVP
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
DVP_P4-5: 593X1_SRT-A
BreakerAC121.06 %830.0C1004.832.32
GD2DVP
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
DVP_P4-5: 593X2_SRT-A
BreakerAC121.06 %830.0C1004.822.32
GD2DVP
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC121.05 %830.0C1004.682.32
GD2DVP
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
DVP_P7-1: LN 2012-54_SRT-A
TowerAC107.09 %830.0C888.862.08
GD2DVP
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
DVP_P7-1: LN 1010-2012_SRT-A
TowerAC106.11 %830.0C880.732.14
GD2DVP
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
Base Case
SingleAC104.83 %678.68A711.431.74
GD2DVP
6EDMONSON-6SEDGE HILL 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC103.9 %997.0C1035.92.75
GD2DVP
6EDMONSON-6SEDGE HILL 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC102.06 %997.0C1017.582.74
GD2DVP
6EDMONSON-6SEDGE HILL 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC102.05 %997.0C1017.412.74
GD2DVP
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC141.24 %678.68B958.542.32
GD2DVP
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC140.59 %678.68B954.152.32
GD2DVP
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC136.41 %830.0C1132.242.34
GD2DVP
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC136.35 %830.0C1131.672.34
GD2DVP
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
DVP_P4-5: 593X2_SRT-A
BreakerAC131.42 %830.0C1090.772.32
GD2DVP
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
DVP_P4-5: 593X1_SRT-A
BreakerAC131.42 %830.0C1090.772.32
GD2DVP
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC131.4 %830.0C1090.632.32
GD2DVP
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
DVP_P7-1: LN 2012-54_SRT-A
TowerAC117.86 %830.0C978.272.08
GD2DVP
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
DVP_P7-1: LN 1010-2012_SRT-A
TowerAC116.91 %830.0C970.322.14
GD2DVP
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
Base Case
SingleAC114.42 %678.68A776.571.74
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC201.24 %684.0C1376.514.63
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC201.19 %684.0C1376.134.63
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC197.56 %684.0C1351.344.62
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC195.93 %559.3B1095.864.62
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC193.37 %559.3B1081.514.62
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC191.54 %684.0C1310.124.62
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC191.54 %684.0C1310.124.62
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P7-1: LN 2106-2111_SRT-A
TowerAC119.01 %684.0C814.052.84
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC118.81 %684.0C812.652.93
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P7-1: LN 2003-205_SRT-S
TowerAC115.25 %684.0C788.332.9
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P2-2: ALTAVISTA 115KV_SRT-A
BusAC113.26 %684.0C774.732.98
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Base Case
SingleAC101.32 %559.3A566.672.85
GD2DVP
6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 1 transformer
DVP_P4-5: 556X2_SRT-S
BreakerAC139.23 %1050.6C1462.744.48
GD2DVP
6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 2 transformer
DVP_P4-5: 556X1_SRT-S
BreakerAC138.76 %1053.0C1461.124.47
GD2DVP
6FINNEYWOOD-AG1-098 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC113.83 %571.52B650.551.99
GD2DVP
6FINNEYWOOD-AG1-098 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC111.27 %571.52B635.931.99
GD2DVP
6FINNEYWOOD-AG1-098 TP 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC109.84 %699.0C767.782.0
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC196.14 %678.68B1331.142.11
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC182.57 %830.0C1515.372.11
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC182.57 %830.0C1515.342.11
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC175.31 %830.0C1455.082.03
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC175.31 %830.0C1455.082.03
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-3
SingleAC162.3 %678.68B1101.512.05
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P4-2: 202712_SRT-S
BreakerAC153.09 %830.0C1270.662.05
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Base Case
SingleAC108.58 %678.68A736.921.77
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC198.54 %661.76B1313.882.11
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC185.18 %809.0C1498.12.11
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC185.18 %809.0C1498.082.11
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC177.73 %809.0C1437.822.03
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC177.73 %809.0C1437.822.03
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-3
SingleAC163.84 %661.76B1084.232.05
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: 242T2027_SRT-A
BreakerAC154.93 %809.0C1253.382.05
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Base Case
SingleAC108.74 %661.76A719.621.77
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC195.13 %661.76B1291.312.11
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC182.39 %809.0C1475.572.11
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC182.39 %809.0C1475.542.11
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC174.94 %809.0C1415.272.03
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC174.94 %809.0C1415.272.03
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 2027_SRT-A-3
SingleAC160.44 %661.76B1061.72.05
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P4-2: 242T2027_SRT-A
BreakerAC152.15 %809.0C1230.872.05
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Base Case
SingleAC105.36 %661.76A697.231.77
GD2DVP
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC131.64 %678.68B893.442.32
GD2DVP
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC130.99 %678.68B889.032.32
GD2DVP
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC126.02 %830.0C1045.982.34
GD2DVP
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC125.95 %830.0C1045.352.34
GD2DVP
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
DVP_P4-5: 593X1_SRT-A
BreakerAC121.01 %830.0C1004.42.32
GD2DVP
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
DVP_P4-5: 593X2_SRT-A
BreakerAC121.01 %830.0C1004.42.32
GD2DVP
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC121.0 %830.0C1004.262.32
GD2DVP
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
DVP_P7-1: LN 2012-54_SRT-A
TowerAC107.04 %830.0C888.462.08
GD2DVP
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
DVP_P7-1: LN 1010-2012_SRT-A
TowerAC106.06 %830.0C880.332.14
GD2DVP
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
Base Case
SingleAC104.76 %678.68A710.981.74
GD2DVP
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
DVP_P1-2: LN 2028_SRT-A
SingleAC127.75 %800.88B1023.091.29
GD2DVP
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC125.17 %800.88B1002.461.34
GD2DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC145.19 %678.68B985.372.32
GD2DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC144.54 %678.68B980.942.32
GD2DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC139.4 %830.0C1156.992.33
GD2DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC139.34 %830.0C1156.562.33
GD2DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
DVP_P4-5: 593X1_SRT-A
BreakerAC134.4 %830.0C1115.542.32
GD2DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
DVP_P4-5: 593X2_SRT-A
BreakerAC134.4 %830.0C1115.542.32
GD2DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC134.39 %830.0C1115.42.32
GD2DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
DVP_P7-1: LN 2012-54_SRT-A
TowerAC120.98 %830.0C1004.152.08
GD2DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
DVP_P7-1: LN 1010-2012_SRT-A
TowerAC120.03 %830.0C996.242.14
GD2DVP
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Base Case
SingleAC117.79 %678.68A799.441.74
GD2DVP
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC108.88 %1105.0C1203.125.16
GD2DVP
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC106.72 %1105.0C1179.245.14
GD2DVP
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC106.7 %1105.0C1179.055.14
GD2DVP
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
DVP_P4-5: 593X1_SRT-A
BreakerAC104.45 %1105.0C1154.155.14
GD2DVP
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
DVP_P4-5: 593X2_SRT-A
BreakerAC104.44 %1105.0C1154.095.14
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: 56272_SRT-S
BreakerAC131.96 %3118.0C4114.653.83
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P1-2: LN 562_SRT-S-1
SingleAC115.67 %3118.0B3606.73.83
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P1-2: LN 298_SRT-A-4
SingleAC114.73 %3220.44B3694.834.47
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P2-2: BREMO B1_SRT-A
BusAC108.3 %3940.0C4267.154.4
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-1
SingleAC139.73 %4070.2B5687.335.15
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-2
SingleAC133.78 %4070.2B5445.285.15
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 58572_SRT-A
BreakerAC124.04 %4996.0C6196.955.15
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-5: W72_SRT-A
BreakerAC123.43 %4996.0C6166.565.15
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: XT585_SRT-S
BreakerAC114.16 %4996.0C5703.665.15
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 54472_SRT-S
BreakerAC111.74 %2858.0C3193.493.78
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC123.06 %4070.2B5008.654.57
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51192_SRT-S
BreakerAC109.25 %4996.0C5458.064.57
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51172_SRT-S
BreakerAC108.79 %4996.0C5435.074.58
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P4-2: 511T544_SRT-S
BreakerAC107.19 %4996.0C5355.194.52
GD2DVP
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC113.0 %1105.0C1248.615.15
GD2DVP
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC110.45 %1105.0C1220.465.14
GD2DVP
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC110.42 %1105.0C1220.195.14
GD2DVP
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-5: 593X1_SRT-A
BreakerAC108.84 %1105.0C1202.695.14
GD2DVP
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-5: 593X2_SRT-A
BreakerAC108.84 %1105.0C1202.635.14
GD2DVP
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC103.96 %903.34B939.115.15
GD2DVP
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC102.05 %903.34B921.895.15
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC239.46 %541.0B1295.465.14
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC234.05 %541.0B1266.235.13
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC234.0 %541.0B1265.965.13
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-5: 593X1_SRT-A
BreakerAC231.01 %541.0B1249.795.13
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-5: 593X2_SRT-A
BreakerAC231.0 %541.0B1249.745.13
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC192.41 %508.54B978.465.14
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC189.13 %508.54B961.815.14
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P2-2: BREMO B1_SRT-A
BusAC102.04 %541.0B552.013.06
GD2DVP
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
DVP_P1-2: LN 2028_SRT-A
SingleAC127.59 %800.88B1021.821.29
GD2DVP
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC125.65 %800.88B1006.311.34
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC136.1 %4070.2B5539.414.57
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 51192_SRT-S
BreakerAC120.36 %4996.0C6013.114.57
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 51172_SRT-S
BreakerAC119.82 %4996.0C5986.294.58
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 511T544_SRT-S
BreakerAC118.15 %4996.0C5902.94.52
GD2DVP
AG1-098 TP-6FINNEYWOOD 230.0 kV Ckt 1 line
DVP_P4-2: 211122_SRT-A
BreakerAC122.55 %699.0C856.62.1
GD2DVP
AG1-098 TP-6FINNEYWOOD 230.0 kV Ckt 1 line
DVP_P4-2: 219322_SRT-A
BreakerAC122.55 %699.0C856.62.1
GD2DVP
AG1-098 TP-6FINNEYWOOD 230.0 kV Ckt 1 line
DVP_P2-2: BREMO B1_SRT-A
BusAC122.55 %699.0C856.62.1
GD2DVP
AG1-098 TP-6FINNEYWOOD 230.0 kV Ckt 1 line
DVP_P1-2: LN 298_SRT-A-4
SingleAC111.11 %571.52B635.032.1
GD2DVP
AG1-098 TP-6FINNEYWOOD 230.0 kV Ckt 1 line
DVP_P1-2: LN 298_SRT-A-3
SingleAC104.38 %571.52B596.582.1
GD2DVP
AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC117.76 %571.52B673.041.99
GD2DVP
AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC115.2 %571.52B658.381.99
GD2DVP
AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC114.07 %699.0C797.372.0
GD2DVP
AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC114.03 %699.0C797.082.0
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC211.67 %684.0C1447.794.63
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC211.61 %684.0C1447.44.63
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC207.99 %684.0C1422.624.62
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC206.17 %559.3B1153.124.62
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC203.59 %559.3B1138.684.62
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC201.95 %684.0C1381.354.62
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC201.95 %684.0C1381.354.62
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P7-1: LN 2106-2111_SRT-A
TowerAC128.21 %684.0C876.962.84
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC128.06 %684.0C875.952.93
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P7-1: LN 2003-205_SRT-S
TowerAC124.48 %684.0C851.472.9
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
BusAC115.8 %684.0C792.062.87
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Base Case
SingleAC110.37 %559.3A617.322.85
GD2DVP
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC132.79 %571.52B758.931.99
GD2DVP
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC130.22 %571.52B744.241.99
GD2DVP
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC129.97 %699.0C908.52.0
GD2DVP
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC129.93 %699.0C908.212.0
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC129.2 %4070.2B5258.724.57
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51192_SRT-S
BreakerAC114.25 %4996.0C5708.124.57
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51172_SRT-S
BreakerAC113.76 %4996.0C5683.444.58
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P4-2: 511T544_SRT-S
BreakerAC112.13 %4996.0C5601.84.52
GD2DVP
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
DVP_P1-2: LN 2028_SRT-A
SingleAC122.8 %800.88B983.471.3
GD2DVP
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC120.99 %800.88B969.011.35
GD2DVP
AH1-377 TP-AG1-098 TP 230.0 kV Ckt 1 line
DVP_P4-2: 211122_SRT-A
BreakerAC110.18 %699.0C770.152.1
GD2DVP
AH1-377 TP-AG1-098 TP 230.0 kV Ckt 1 line
DVP_P2-2: BREMO B1_SRT-A
BusAC110.18 %699.0C770.152.1
GD2DVP
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC127.24 %571.52B727.21.99
GD2DVP
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC124.67 %571.52B712.521.99
GD2DVP
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC124.28 %699.0C868.712.0
GD2DVP
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC124.24 %699.0C868.412.0
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC218.2 %684.0C1492.54.63
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC218.14 %684.0C1492.114.63
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC214.52 %684.0C1467.344.62
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC212.24 %559.3B1187.044.62
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC209.65 %559.3B1172.594.62
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC208.48 %684.0C1426.034.62
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC208.48 %684.0C1426.034.62
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P7-1: LN 2106-2111_SRT-A
TowerAC134.05 %684.0C916.912.84
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC133.94 %684.0C916.122.93
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P7-1: LN 2003-205_SRT-S
TowerAC130.34 %684.0C891.542.9
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
BusAC121.65 %684.0C832.112.87
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Base Case
SingleAC115.81 %559.3A647.72.85
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: 511T556_SRT-S
BreakerAC219.98 %699.0C1537.654.63
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: 587T591_SRT-S
BreakerAC219.92 %699.0C1537.264.63
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: 55692_SRT-S
BreakerAC216.35 %699.0C1512.314.62
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P1-2: LN 587_SRT-A-3
SingleAC213.74 %571.52B1221.64.62
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC211.19 %571.52B1206.974.62
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC210.43 %699.0C1470.94.62
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC210.43 %699.0C1470.94.62
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC137.05 %699.0C957.972.93
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P7-1: LN 2106-2111_SRT-A
TowerAC136.87 %699.0C956.692.83
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P7-1: LN 2003-205_SRT-S
TowerAC133.52 %699.0C933.312.9
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
BusAC125.05 %699.0C874.12.87
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Base Case
SingleAC118.94 %571.52A679.772.85

Details for 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.98 %
Rating:239.89 MVA
Rating Type:B
MVA to Mitigate:268.62
MW Contribution:1.95
Bus #Bus NameTypeMW Contribution
3151281ROARAP4
50/50
0.518
3151281ROARAP4
50/50
0.484
3151151S HAMPT1
50/50
0.38
3151611KERR 4
50/50
0.279
3151621KERR 5
50/50
0.279
3151631KERR 6
50/50
0.279
3151641KERR 7
50/50
0.279
315607AA1-063A GEN
Solar/Wind Harmer
0.697
3137643SOCKMAN
Solar/Wind Harmer
1.362
3146043SEABORD
Solar/Wind Harmer
0.327
970831AG2-522 GEN
Solar/Wind Harmer
10.885
965291AG1-394 GEN
Solar/Wind Harmer
0.929
316087AB2-174 GEN
Solar/Wind Harmer
0.005
3145893MURPHYS
Solar/Wind Harmer
0.427
3145893MURPHYS
Solar/Wind Harmer
0.158
3146033SCOT NK
Solar/Wind Harmer
0.447
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3145513AHOSKIE
Solar/Wind Harmer
0.159
3145513AHOSKIE
Solar/Wind Harmer
0.076
971443AH1-215 GEN
Solar/Wind Harmer
1.17
3144303KENBRDG
Solar/Wind Harmer
0.055
970683AG2-441 GEN
Solar/Wind Harmer
4.26
970681AG2-440 GEN
Solar/Wind Harmer
3.408
946301AF1-294 GEN
Solar/Wind Harmer
1.163
961791AG1-021 GEN
Solar/Wind Harmer
0.566
3145796HORNRTN
Solar/Wind Helper
0.923
3145796HORNRTN
Solar/Wind Helper
0.115
3151261ROARAP2
50/50
0.52
3151591KERR 2
50/50
0.279
3144293JTRSVLE
50/50
0.199
313506AB2-031 GEN
Solar/Wind Harmer
0.737
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
3145893MURPHYS
Solar/Wind Harmer
0.265
3145893MURPHYS
Solar/Wind Harmer
0.158
3146263WOODLND
Solar/Wind Harmer
0.153
957521AF2-046 GEN
Solar/Wind Harmer
10.591
961681AG1-008 GEN
Solar/Wind Harmer
10.591
316210AC1-098 GEN
Solar/Wind Harmer
1.27
3146173TUNIS
Solar/Wind Harmer
0.106
316327AA2-057 GEN
Solar/Wind Harmer
0.133
316317KELFORD C
Solar/Wind Harmer
0.008
3145823KELFORD
Solar/Wind Harmer
0.081
316131AB2-060 GEN
Solar/Wind Harmer
0.252
964241AG1-285 GEN
Solar/Wind Harmer
5.121
316463AE2-346 GEN
Solar/Wind Harmer
0.065
316140AB2-099
Solar/Wind Harmer
0.027
962331AG1-082 GEN
Solar/Wind Harmer
0.81
3147043LAWRENC
Solar/Wind Harmer
0.044
315785AD2-033 C
Solar/Wind Harmer
0.579
970257AG2-171 GEN
Solar/Wind Harmer
2.214
3145273HOLLAND
Solar/Wind Harmer
0.052
959311AF2-222 GEN
Solar/Wind Harmer
6.015
963181AG1-167 GEN
Solar/Wind Harmer
0.236
3142666NORTHAMPTON
Solar/Wind Helper
0.333
3145796HORNRTN
Solar/Wind Helper
1.154
3145796HORNRTN
Solar/Wind Helper
0.289
315724AD1-057 GEN
Solar/Wind Helper
0.526
316365GEN2_N
Solar/Wind Helper
0.635
3151261ROARAP2
50/50
0.532
3151601KERR 3
50/50
0.279
3151581KERR 1
50/50
0.1
3147043LAWRENC
50/50
0.705
3144293JTRSVLE
50/50
0.199
3145783HORNRTN
Solar/Wind Harmer
0.388
316190AA2-174 GEN
Solar/Wind Harmer
0.001
316129AC1-054 GEN
Solar/Wind Harmer
0.891
971065AG2-659 GEN
Solar/Wind Harmer
9.376
3145893MURPHYS
Solar/Wind Harmer
0.633
3145893MURPHYS
Solar/Wind Harmer
0.703
3146263WOODLND
Solar/Wind Harmer
0.153
316212AC1-099_GEN
Solar/Wind Harmer
0.708
3146173TUNIS
Solar/Wind Harmer
0.106
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3145823KELFORD
Solar/Wind Harmer
0.081
971795AH1-408 GEN
Solar/Wind Harmer
4.829
960081AF2-299 GEN
Solar/Wind Harmer
0.674
970685AG2-442 GEN
Solar/Wind Harmer
4.771
970401AG2-262 GEN
Solar/Wind Harmer
0.349
963171AG1-166 GEN
Solar/Wind Harmer
0.314
971563AH1-280 GEN
Solar/Wind Harmer
0.629
957481AF2-042 GEN
Solar/Wind Harmer
13.033
316011AB1-132 GEN
Solar/Wind Helper
3.47
3145796HORNRTN
Solar/Wind Helper
0.952
3145796HORNRTN
Solar/Wind Helper
0.289
315722AD1-056 GEN
Solar/Wind Helper
0.957
316023GEN1_S
Solar/Wind Helper
0.635
970535AG2-341 GEN
50/50
1.948
3144293JTRSVLE
50/50
0.199
3144293JTRSVLE
50/50
0.168
3152661PLYWOOD A
50/50
0.127
3145593CAROLNA
Solar/Wind Harmer
0.427
3145593CAROLNA
Solar/Wind Harmer
0.427
966811AG1-552 GEN
Solar/Wind Harmer
4.632
3145593CAROLNA
Solar/Wind Harmer
0.532
3145783HORNRTN
Solar/Wind Harmer
6.907
3145783HORNRTN
Solar/Wind Harmer
5.526
3145783HORNRTN
Solar/Wind Harmer
1.727
3145783HORNRTN
Solar/Wind Harmer
0.691
316426AA2-053 GEN
Solar/Wind Harmer
1.214
316181AB2-040 GEN
Solar/Wind Harmer
0.346
316274AC1-208 GEN
Solar/Wind Harmer
0.957
3145893MURPHYS
Solar/Wind Harmer
1.059
3145893MURPHYS
Solar/Wind Harmer
0.285
939181AE1-148 GEN
Solar/Wind Harmer
6.006
3146173TUNIS
Solar/Wind Harmer
0.106
3146173TUNIS
Solar/Wind Harmer
0.106
315742AE1-103 GEN
Solar/Wind Harmer
0.001
313527AB2-043 GEN
Solar/Wind Harmer
0.001
970323AG2-213 GEN
Solar/Wind Harmer
2.952
971775AH1-396 GEN
Solar/Wind Harmer
0.111
316034AC1-036 C
Solar/Wind Harmer
0.005
962561AG1-105 GEN
Solar/Wind Harmer
3.011
964791AG1-342 GEN
Solar/Wind Harmer
1.141
3146843MT LREL
Solar/Wind Harmer
0.059
3146843MT LREL
Solar/Wind Harmer
0.059
958211AF2-115 GEN
Solar/Wind Harmer
0.707
963191AG1-168 GEN
Solar/Wind Harmer
0.236
970099AG2-077 GEN
Solar/Wind Harmer
5.213
3142666NORTHAMPTON
Solar/Wind Helper
0.333
3142666NORTHAMPTON
Solar/Wind Helper
0.333
3142666NORTHAMPTON
Solar/Wind Helper
0.333
3142666NORTHAMPTON
Solar/Wind Helper
0.2
3145796HORNRTN
Solar/Wind Helper
0.865
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.044
MECLTFEXP_MEC->PJM
CLTF
0.007
SIGELTFEXP_SIGE->PJM
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.09
LAGNLTFEXP_LAGN->PJM
CLTF
0.014
TVALTFEXP_TVA->PJM
CLTF
0.012
NYPJM->LTFIMP_NY
CLTF
0.082
LGEELTFEXP_LGEE->PJM
CLTF
0.007
WECLTFEXP_WEC->PJM
CLTF
0.001
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.056

Details for 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 587_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 587_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.24 %
Rating:239.89 MVA
Rating Type:B
MVA to Mitigate:257.27
MW Contribution:1.95
Bus #Bus NameTypeMW Contribution
3151261ROARAP2
50/50
0.532
3151601KERR 3
50/50
0.279
3151581KERR 1
50/50
0.1
3147043LAWRENC
50/50
0.705
3144293JTRSVLE
50/50
0.199
3145783HORNRTN
Solar/Wind Harmer
0.388
316190AA2-174 GEN
Solar/Wind Harmer
0.001
316129AC1-054 GEN
Solar/Wind Harmer
0.891
971065AG2-659 GEN
Solar/Wind Harmer
9.376
3145893MURPHYS
Solar/Wind Harmer
0.633
3145893MURPHYS
Solar/Wind Harmer
0.703
3146263WOODLND
Solar/Wind Harmer
0.153
316212AC1-099_GEN
Solar/Wind Harmer
0.708
3146173TUNIS
Solar/Wind Harmer
0.106
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3145823KELFORD
Solar/Wind Harmer
0.081
971795AH1-408 GEN
Solar/Wind Harmer
4.829
960081AF2-299 GEN
Solar/Wind Harmer
0.674
970685AG2-442 GEN
Solar/Wind Harmer
4.771
970401AG2-262 GEN
Solar/Wind Harmer
0.349
963171AG1-166 GEN
Solar/Wind Harmer
0.314
971563AH1-280 GEN
Solar/Wind Harmer
0.629
957481AF2-042 GEN
Solar/Wind Harmer
13.033
316011AB1-132 GEN
Solar/Wind Helper
3.47
3145796HORNRTN
Solar/Wind Helper
0.952
3145796HORNRTN
Solar/Wind Helper
0.289
315722AD1-056 GEN
Solar/Wind Helper
0.957
316023GEN1_S
Solar/Wind Helper
0.635
3151281ROARAP4
50/50
0.518
3151281ROARAP4
50/50
0.484
3151151S HAMPT1
50/50
0.38
3151611KERR 4
50/50
0.279
3151621KERR 5
50/50
0.279
3151631KERR 6
50/50
0.279
3151641KERR 7
50/50
0.279
315607AA1-063A GEN
Solar/Wind Harmer
0.697
3137643SOCKMAN
Solar/Wind Harmer
1.362
3146043SEABORD
Solar/Wind Harmer
0.327
970831AG2-522 GEN
Solar/Wind Harmer
10.885
965291AG1-394 GEN
Solar/Wind Harmer
0.929
316087AB2-174 GEN
Solar/Wind Harmer
0.005
3145893MURPHYS
Solar/Wind Harmer
0.427
3145893MURPHYS
Solar/Wind Harmer
0.158
3146033SCOT NK
Solar/Wind Harmer
0.447
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3145513AHOSKIE
Solar/Wind Harmer
0.159
3145513AHOSKIE
Solar/Wind Harmer
0.076
971443AH1-215 GEN
Solar/Wind Harmer
1.17
3144303KENBRDG
Solar/Wind Harmer
0.055
970683AG2-441 GEN
Solar/Wind Harmer
4.26
970681AG2-440 GEN
Solar/Wind Harmer
3.408
946301AF1-294 GEN
Solar/Wind Harmer
1.163
961791AG1-021 GEN
Solar/Wind Harmer
0.566
3145796HORNRTN
Solar/Wind Helper
0.923
3145796HORNRTN
Solar/Wind Helper
0.115
970535AG2-341 GEN
50/50
1.948
3144293JTRSVLE
50/50
0.199
3144293JTRSVLE
50/50
0.168
3152661PLYWOOD A
50/50
0.127
3145593CAROLNA
Solar/Wind Harmer
0.427
3145593CAROLNA
Solar/Wind Harmer
0.427
966811AG1-552 GEN
Solar/Wind Harmer
4.632
3145593CAROLNA
Solar/Wind Harmer
0.532
3145783HORNRTN
Solar/Wind Harmer
6.907
3145783HORNRTN
Solar/Wind Harmer
5.526
3145783HORNRTN
Solar/Wind Harmer
1.727
3145783HORNRTN
Solar/Wind Harmer
0.691
316426AA2-053 GEN
Solar/Wind Harmer
1.214
316181AB2-040 GEN
Solar/Wind Harmer
0.346
316274AC1-208 GEN
Solar/Wind Harmer
0.957
3145893MURPHYS
Solar/Wind Harmer
1.059
3145893MURPHYS
Solar/Wind Harmer
0.285
939181AE1-148 GEN
Solar/Wind Harmer
6.006
3146173TUNIS
Solar/Wind Harmer
0.106
3146173TUNIS
Solar/Wind Harmer
0.106
315742AE1-103 GEN
Solar/Wind Harmer
0.001
313527AB2-043 GEN
Solar/Wind Harmer
0.001
970323AG2-213 GEN
Solar/Wind Harmer
2.952
971775AH1-396 GEN
Solar/Wind Harmer
0.111
316034AC1-036 C
Solar/Wind Harmer
0.005
962561AG1-105 GEN
Solar/Wind Harmer
3.011
964791AG1-342 GEN
Solar/Wind Harmer
1.141
3146843MT LREL
Solar/Wind Harmer
0.059
3146843MT LREL
Solar/Wind Harmer
0.059
958211AF2-115 GEN
Solar/Wind Harmer
0.707
963191AG1-168 GEN
Solar/Wind Harmer
0.236
970099AG2-077 GEN
Solar/Wind Harmer
5.213
3142666NORTHAMPTON
Solar/Wind Helper
0.333
3142666NORTHAMPTON
Solar/Wind Helper
0.333
3142666NORTHAMPTON
Solar/Wind Helper
0.333
3142666NORTHAMPTON
Solar/Wind Helper
0.2
3145796HORNRTN
Solar/Wind Helper
0.865
3151261ROARAP2
50/50
0.52
3151591KERR 2
50/50
0.279
3144293JTRSVLE
50/50
0.199
313506AB2-031 GEN
Solar/Wind Harmer
0.737
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
3145893MURPHYS
Solar/Wind Harmer
0.265
3145893MURPHYS
Solar/Wind Harmer
0.158
3146263WOODLND
Solar/Wind Harmer
0.153
957521AF2-046 GEN
Solar/Wind Harmer
10.591
961681AG1-008 GEN
Solar/Wind Harmer
10.591
316210AC1-098 GEN
Solar/Wind Harmer
1.27
3146173TUNIS
Solar/Wind Harmer
0.106
316327AA2-057 GEN
Solar/Wind Harmer
0.133
316317KELFORD C
Solar/Wind Harmer
0.008
3145823KELFORD
Solar/Wind Harmer
0.081
316131AB2-060 GEN
Solar/Wind Harmer
0.252
964241AG1-285 GEN
Solar/Wind Harmer
5.121
316463AE2-346 GEN
Solar/Wind Harmer
0.065
316140AB2-099
Solar/Wind Harmer
0.027
962331AG1-082 GEN
Solar/Wind Harmer
0.81
3147043LAWRENC
Solar/Wind Harmer
0.044
315785AD2-033 C
Solar/Wind Harmer
0.579
970257AG2-171 GEN
Solar/Wind Harmer
2.214
3145273HOLLAND
Solar/Wind Harmer
0.052
959311AF2-222 GEN
Solar/Wind Harmer
6.015
963181AG1-167 GEN
Solar/Wind Harmer
0.236
3142666NORTHAMPTON
Solar/Wind Helper
0.333
3145796HORNRTN
Solar/Wind Helper
1.154
3145796HORNRTN
Solar/Wind Helper
0.289
315724AD1-057 GEN
Solar/Wind Helper
0.526
316365GEN2_N
Solar/Wind Helper
0.635
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.044
MECLTFEXP_MEC->PJM
CLTF
0.007
SIGELTFEXP_SIGE->PJM
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.09
LAGNLTFEXP_LAGN->PJM
CLTF
0.014
TVALTFEXP_TVA->PJM
CLTF
0.012
NYPJM->LTFIMP_NY
CLTF
0.082
LGEELTFEXP_LGEE->PJM
CLTF
0.007
WECLTFEXP_WEC->PJM
CLTF
0.001
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.056

Details for 3CLOUD-6CLOUD 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-3: CLOUD H222_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3CLOUD-6CLOUD 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-3: CLOUD H222_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.97 %
Rating:288.0 MVA
Rating Type:C
MVA to Mitigate:305.19
MW Contribution:4.9
Bus #Bus NameTypeMW Contribution
3151601KERR 3
50/50
0.66
3151581KERR 1
50/50
0.236
3147043LAWRENC
50/50
1.169
3144293JTRSVLE
50/50
0.381
971065AG2-659 GEN
Solar/Wind Harmer
14.241
316129AC1-054 GEN
Solar/Wind Harmer
2.367
316237AB2-079_GEN
Solar/Wind Harmer
0.762
970685AG2-442 GEN
Solar/Wind Harmer
13.605
970401AG2-262 GEN
Solar/Wind Harmer
0.868
963171AG1-166 GEN
Solar/Wind Harmer
1.585
971563AH1-280 GEN
Solar/Wind Harmer
1.585
971795AH1-408 GEN
Solar/Wind Harmer
9.054
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.114
960081AF2-299 GEN
Solar/Wind Harmer
0.963
3151591KERR 2
50/50
0.66
3144293JTRSVLE
50/50
0.381
316131AB2-060 GEN
Solar/Wind Harmer
2.689
964241AG1-285 GEN
Solar/Wind Harmer
17.961
315785AD2-033 C
Solar/Wind Harmer
4.483
970257AG2-171 GEN
Solar/Wind Harmer
6.967
959311AF2-222 GEN
Solar/Wind Harmer
18.491
3147043LAWRENC
Solar/Wind Harmer
-0.008
963181AG1-167 GEN
Solar/Wind Harmer
1.189
3147133PAMPLIN
Solar/Wind Harmer
-0.033
971193AH1-056 GEN
Solar/Wind Harmer
6.679
313506AB2-031 GEN
Solar/Wind Harmer
0.759
966621AG1-532 GEN
Solar/Wind Harmer
0.174
316478AD1-087 GEN
Solar/Wind Helper
0.605
316486AD2-202 GEN
Solar/Wind Helper
0.177
3151611KERR 4
50/50
0.66
3151621KERR 5
50/50
0.66
3151631KERR 6
50/50
0.66
3151641KERR 7
50/50
0.66
970831AG2-522 GEN
Solar/Wind Harmer
12.702
316239AB2-077_GEN
Solar/Wind Harmer
0.762
316238AB2-078_GEN
Solar/Wind Harmer
0.762
971443AH1-215 GEN
Solar/Wind Harmer
3.711
3144303KENBRDG
Solar/Wind Harmer
-0.015
970683AG2-441 GEN
Solar/Wind Harmer
12.147
970681AG2-440 GEN
Solar/Wind Harmer
9.718
946301AF1-294 GEN
Solar/Wind Harmer
3.249
961791AG1-021 GEN
Solar/Wind Harmer
1.585
315657AE1-056 GEN
Solar/Wind Harmer
4.008
3137643SOCKMAN
Solar/Wind Harmer
-0.04
316087AB2-174 GEN
Solar/Wind Harmer
1.31
316118AC1-105 GEN
Solar/Wind Harmer
0.61
315607AA1-063A GEN
Solar/Wind Harmer
0.87
946281AF1-292 GEN
Solar/Wind Harmer
0.192
3146043SEABORD
Solar/Wind Harmer
-0.008
970535AG2-341 GEN
50/50
4.9
3144293JTRSVLE
50/50
0.381
3144293JTRSVLE
50/50
0.321
939181AE1-148 GEN
Solar/Wind Harmer
19.123
313527AB2-043 GEN
Solar/Wind Harmer
4.128
970323AG2-213 GEN
Solar/Wind Harmer
9.29
971775AH1-396 GEN
Solar/Wind Harmer
1.323
316034AC1-036 C
Solar/Wind Harmer
0.344
962561AG1-105 GEN
Solar/Wind Harmer
8.518
964791AG1-342 GEN
Solar/Wind Harmer
2.84
3146843MT LREL
Solar/Wind Harmer
-0.013
3146843MT LREL
Solar/Wind Harmer
-0.013
958211AF2-115 GEN
Solar/Wind Harmer
1.981
963191AG1-168 GEN
Solar/Wind Harmer
1.189
3147133PAMPLIN
Solar/Wind Harmer
-0.011
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.174
3145593CAROLNA
Solar/Wind Harmer
0.087
3145783HORNRTN
Solar/Wind Harmer
1.166
3145783HORNRTN
Solar/Wind Harmer
0.932
3145783HORNRTN
Solar/Wind Harmer
0.291
3145783HORNRTN
Solar/Wind Harmer
0.117
316181AB2-040 GEN
Solar/Wind Harmer
1.318
316426AA2-053 GEN
Solar/Wind Harmer
0.94
316274AC1-208 GEN
Solar/Wind Harmer
0.709
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.765
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.935
MECLTFEXP_MEC->PJM
CLTF
0.268
SIGELTFEXP_SIGE->PJM
CLTF
0.008
CPLELTFEXP_CPLE->PJM
CLTF
0.975
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.885
LAGNLTFEXP_LAGN->PJM
CLTF
0.545
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.83
TVALTFEXP_TVA->PJM
CLTF
0.273
NYPJM->LTFIMP_NY
CLTF
0.111
LGEELTFEXP_LGEE->PJM
CLTF
0.097
WECLTFEXP_WEC->PJM
CLTF
0.05

Details for 3CLOUD-6CLOUD 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 222922-4_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3CLOUD-6CLOUD 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: 222922-4_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.11 %
Rating:288.0 MVA
Rating Type:C
MVA to Mitigate:299.83
MW Contribution:4.55
Bus #Bus NameTypeMW Contribution
3151601KERR 3
50/50
0.613
3151581KERR 1
50/50
0.219
3147043LAWRENC
50/50
1.086
971065AG2-659 GEN
Solar/Wind Harmer
13.225
316129AC1-054 GEN
Solar/Wind Harmer
2.198
316237AB2-079_GEN
Solar/Wind Harmer
0.708
970685AG2-442 GEN
Solar/Wind Harmer
12.312
970535AG2-341 GEN
50/50
4.548
939181AE1-148 GEN
Solar/Wind Harmer
17.754
313527AB2-043 GEN
Solar/Wind Harmer
3.829
970323AG2-213 GEN
Solar/Wind Harmer
8.496
971775AH1-396 GEN
Solar/Wind Harmer
1.21
316034AC1-036 C
Solar/Wind Harmer
0.315
962561AG1-105 GEN
Solar/Wind Harmer
8.097
964791AG1-342 GEN
Solar/Wind Harmer
2.722
3146843MT LREL
Solar/Wind Harmer
-0.013
3146843MT LREL
Solar/Wind Harmer
-0.013
958211AF2-115 GEN
Solar/Wind Harmer
1.767
963191AG1-168 GEN
Solar/Wind Harmer
1.06
3144293JTRSVLE
Adder
0.32
3144293JTRSVLE
Adder
0.27
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.093
3145593CAROLNA
Solar/Wind Harmer
0.081
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.008
3145783HORNRTN
Solar/Wind Harmer
1.085
3145783HORNRTN
Solar/Wind Harmer
0.868
3145783HORNRTN
Solar/Wind Harmer
0.271
3145783HORNRTN
Solar/Wind Harmer
0.109
316181AB2-040 GEN
Solar/Wind Harmer
1.225
316426AA2-053 GEN
Solar/Wind Harmer
0.875
970401AG2-262 GEN
Solar/Wind Harmer
0.832
963171AG1-166 GEN
Solar/Wind Harmer
1.413
971563AH1-280 GEN
Solar/Wind Harmer
1.413
3144293JTRSVLE
Adder
0.32
971795AH1-408 GEN
Solar/Wind Harmer
8.406
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.106
960081AF2-299 GEN
Solar/Wind Harmer
0.895
3151591KERR 2
50/50
0.613
316131AB2-060 GEN
Solar/Wind Harmer
2.492
964241AG1-285 GEN
Solar/Wind Harmer
16.594
315785AD2-033 C
Solar/Wind Harmer
4.113
970257AG2-171 GEN
Solar/Wind Harmer
6.372
959311AF2-222 GEN
Solar/Wind Harmer
16.866
3147043LAWRENC
Solar/Wind Harmer
-0.008
963181AG1-167 GEN
Solar/Wind Harmer
1.06
3144293JTRSVLE
Adder
0.32
3147133PAMPLIN
Solar/Wind Harmer
-0.029
971193AH1-056 GEN
Solar/Wind Harmer
5.867
313506AB2-031 GEN
Solar/Wind Harmer
0.706
966621AG1-532 GEN
Solar/Wind Harmer
0.161
3151611KERR 4
50/50
0.613
3151621KERR 5
50/50
0.613
3151631KERR 6
50/50
0.613
3151641KERR 7
50/50
0.613
970831AG2-522 GEN
Solar/Wind Harmer
11.798
316239AB2-077_GEN
Solar/Wind Harmer
0.708
316238AB2-078_GEN
Solar/Wind Harmer
0.708
971443AH1-215 GEN
Solar/Wind Harmer
3.397
3144303KENBRDG
Solar/Wind Harmer
-0.014
970683AG2-441 GEN
Solar/Wind Harmer
10.993
970681AG2-440 GEN
Solar/Wind Harmer
8.795
946301AF1-294 GEN
Solar/Wind Harmer
2.897
961791AG1-021 GEN
Solar/Wind Harmer
1.413
315657AE1-056 GEN
Solar/Wind Harmer
3.52
3137643SOCKMAN
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
0.605
316087AB2-174 GEN
Solar/Wind Harmer
1.217
315607AA1-063A GEN
Solar/Wind Harmer
0.809
946281AF1-292 GEN
Solar/Wind Harmer
0.178
3146043SEABORD
Solar/Wind Harmer
-0.008
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.95
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.024
MECLTFEXP_MEC->PJM
CLTF
0.294
SIGELTFEXP_SIGE->PJM
CLTF
0.009
CPLELTFEXP_CPLE->PJM
CLTF
1.034
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.162
LAGNLTFEXP_LAGN->PJM
CLTF
0.596
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.98
TVALTFEXP_TVA->PJM
CLTF
0.298
NYPJM->LTFIMP_NY
CLTF
0.116
LGEELTFEXP_LGEE->PJM
CLTF
0.107
WECLTFEXP_WEC->PJM
CLTF
0.055

Details for 3CLOUD-6CLOUD 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-3: CLOUD H122_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3CLOUD-6CLOUD 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-3: CLOUD H122_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.38 %
Rating:295.2 MVA
Rating Type:C
MVA to Mitigate:305.19
MW Contribution:4.9
Bus #Bus NameTypeMW Contribution
3151601KERR 3
50/50
0.66
3151581KERR 1
50/50
0.236
3147043LAWRENC
50/50
1.169
3144293JTRSVLE
50/50
0.381
971065AG2-659 GEN
Solar/Wind Harmer
14.241
316129AC1-054 GEN
Solar/Wind Harmer
2.367
316237AB2-079_GEN
Solar/Wind Harmer
0.762
970685AG2-442 GEN
Solar/Wind Harmer
13.605
970401AG2-262 GEN
Solar/Wind Harmer
0.868
963171AG1-166 GEN
Solar/Wind Harmer
1.585
971563AH1-280 GEN
Solar/Wind Harmer
1.585
971795AH1-408 GEN
Solar/Wind Harmer
9.054
3145783HORNRTN
Solar/Wind Harmer
-0.01
970535AG2-341 GEN
50/50
4.9
3144293JTRSVLE
50/50
0.381
3144293JTRSVLE
50/50
0.321
939181AE1-148 GEN
Solar/Wind Harmer
19.123
313527AB2-043 GEN
Solar/Wind Harmer
4.128
970323AG2-213 GEN
Solar/Wind Harmer
9.29
971775AH1-396 GEN
Solar/Wind Harmer
1.323
316034AC1-036 C
Solar/Wind Harmer
0.344
962561AG1-105 GEN
Solar/Wind Harmer
8.518
964791AG1-342 GEN
Solar/Wind Harmer
2.84
3146843MT LREL
Solar/Wind Harmer
-0.013
3146843MT LREL
Solar/Wind Harmer
-0.013
958211AF2-115 GEN
Solar/Wind Harmer
1.981
963191AG1-168 GEN
Solar/Wind Harmer
1.189
3147133PAMPLIN
Solar/Wind Harmer
-0.011
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3151591KERR 2
50/50
0.66
3144293JTRSVLE
50/50
0.381
316131AB2-060 GEN
Solar/Wind Harmer
2.689
964241AG1-285 GEN
Solar/Wind Harmer
17.961
315785AD2-033 C
Solar/Wind Harmer
4.483
970257AG2-171 GEN
Solar/Wind Harmer
6.967
959311AF2-222 GEN
Solar/Wind Harmer
18.491
3147043LAWRENC
Solar/Wind Harmer
-0.008
963181AG1-167 GEN
Solar/Wind Harmer
1.189
3147133PAMPLIN
Solar/Wind Harmer
-0.033
971193AH1-056 GEN
Solar/Wind Harmer
6.679
313506AB2-031 GEN
Solar/Wind Harmer
0.759
966621AG1-532 GEN
Solar/Wind Harmer
0.174
316478AD1-087 GEN
Solar/Wind Helper
0.605
316486AD2-202 GEN
Solar/Wind Helper
0.177
316190AA2-174 GEN
Solar/Wind Harmer
0.114
960081AF2-299 GEN
Solar/Wind Harmer
0.963
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.174
3145593CAROLNA
Solar/Wind Harmer
0.087
3145783HORNRTN
Solar/Wind Harmer
1.166
3145783HORNRTN
Solar/Wind Harmer
0.932
3145783HORNRTN
Solar/Wind Harmer
0.291
3145783HORNRTN
Solar/Wind Harmer
0.117
316181AB2-040 GEN
Solar/Wind Harmer
1.318
316426AA2-053 GEN
Solar/Wind Harmer
0.94
316274AC1-208 GEN
Solar/Wind Harmer
0.709
3151611KERR 4
50/50
0.66
3151621KERR 5
50/50
0.66
3151631KERR 6
50/50
0.66
3151641KERR 7
50/50
0.66
970831AG2-522 GEN
Solar/Wind Harmer
12.702
316239AB2-077_GEN
Solar/Wind Harmer
0.762
316238AB2-078_GEN
Solar/Wind Harmer
0.762
971443AH1-215 GEN
Solar/Wind Harmer
3.711
3144303KENBRDG
Solar/Wind Harmer
-0.015
970683AG2-441 GEN
Solar/Wind Harmer
12.147
970681AG2-440 GEN
Solar/Wind Harmer
9.718
946301AF1-294 GEN
Solar/Wind Harmer
3.249
961791AG1-021 GEN
Solar/Wind Harmer
1.585
315657AE1-056 GEN
Solar/Wind Harmer
4.008
3137643SOCKMAN
Solar/Wind Harmer
-0.04
316087AB2-174 GEN
Solar/Wind Harmer
1.31
316118AC1-105 GEN
Solar/Wind Harmer
0.61
315607AA1-063A GEN
Solar/Wind Harmer
0.87
946281AF1-292 GEN
Solar/Wind Harmer
0.192
3146043SEABORD
Solar/Wind Harmer
-0.008
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.765
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.935
MECLTFEXP_MEC->PJM
CLTF
0.268
SIGELTFEXP_SIGE->PJM
CLTF
0.008
CPLELTFEXP_CPLE->PJM
CLTF
0.975
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.885
LAGNLTFEXP_LAGN->PJM
CLTF
0.545
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.83
TVALTFEXP_TVA->PJM
CLTF
0.273
NYPJM->LTFIMP_NY
CLTF
0.111
LGEELTFEXP_LGEE->PJM
CLTF
0.097
WECLTFEXP_WEC->PJM
CLTF
0.05

Details for 3CLOUD-6CLOUD 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 222922-3_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3CLOUD-6CLOUD 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-2: 222922-3_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.57 %
Rating:295.2 MVA
Rating Type:C
MVA to Mitigate:299.83
MW Contribution:4.55
Bus #Bus NameTypeMW Contribution
3151591KERR 2
50/50
0.613
316131AB2-060 GEN
Solar/Wind Harmer
2.492
964241AG1-285 GEN
Solar/Wind Harmer
16.594
315785AD2-033 C
Solar/Wind Harmer
4.113
970257AG2-171 GEN
Solar/Wind Harmer
6.372
959311AF2-222 GEN
Solar/Wind Harmer
16.866
3147043LAWRENC
Solar/Wind Harmer
-0.008
963181AG1-167 GEN
Solar/Wind Harmer
1.06
3151601KERR 3
50/50
0.613
3151581KERR 1
50/50
0.219
3147043LAWRENC
50/50
1.086
971065AG2-659 GEN
Solar/Wind Harmer
13.225
316129AC1-054 GEN
Solar/Wind Harmer
2.198
316237AB2-079_GEN
Solar/Wind Harmer
0.708
970685AG2-442 GEN
Solar/Wind Harmer
12.312
970401AG2-262 GEN
Solar/Wind Harmer
0.832
963171AG1-166 GEN
Solar/Wind Harmer
1.413
971563AH1-280 GEN
Solar/Wind Harmer
1.413
3144293JTRSVLE
Adder
0.32
971795AH1-408 GEN
Solar/Wind Harmer
8.406
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.106
960081AF2-299 GEN
Solar/Wind Harmer
0.895
3151611KERR 4
50/50
0.613
3151621KERR 5
50/50
0.613
3151631KERR 6
50/50
0.613
3151641KERR 7
50/50
0.613
970831AG2-522 GEN
Solar/Wind Harmer
11.798
970535AG2-341 GEN
50/50
4.548
939181AE1-148 GEN
Solar/Wind Harmer
17.754
313527AB2-043 GEN
Solar/Wind Harmer
3.829
970323AG2-213 GEN
Solar/Wind Harmer
8.496
971775AH1-396 GEN
Solar/Wind Harmer
1.21
316034AC1-036 C
Solar/Wind Harmer
0.315
962561AG1-105 GEN
Solar/Wind Harmer
8.097
964791AG1-342 GEN
Solar/Wind Harmer
2.722
3146843MT LREL
Solar/Wind Harmer
-0.013
3146843MT LREL
Solar/Wind Harmer
-0.013
958211AF2-115 GEN
Solar/Wind Harmer
1.767
963191AG1-168 GEN
Solar/Wind Harmer
1.06
3144293JTRSVLE
Adder
0.32
3144293JTRSVLE
Adder
0.27
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.093
3145593CAROLNA
Solar/Wind Harmer
0.081
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.008
3145783HORNRTN
Solar/Wind Harmer
1.085
3145783HORNRTN
Solar/Wind Harmer
0.868
3145783HORNRTN
Solar/Wind Harmer
0.271
3145783HORNRTN
Solar/Wind Harmer
0.109
316181AB2-040 GEN
Solar/Wind Harmer
1.225
316426AA2-053 GEN
Solar/Wind Harmer
0.875
3144293JTRSVLE
Adder
0.32
3147133PAMPLIN
Solar/Wind Harmer
-0.029
971193AH1-056 GEN
Solar/Wind Harmer
5.867
313506AB2-031 GEN
Solar/Wind Harmer
0.706
966621AG1-532 GEN
Solar/Wind Harmer
0.161
316239AB2-077_GEN
Solar/Wind Harmer
0.708
316238AB2-078_GEN
Solar/Wind Harmer
0.708
971443AH1-215 GEN
Solar/Wind Harmer
3.397
3144303KENBRDG
Solar/Wind Harmer
-0.014
970683AG2-441 GEN
Solar/Wind Harmer
10.993
970681AG2-440 GEN
Solar/Wind Harmer
8.795
946301AF1-294 GEN
Solar/Wind Harmer
2.897
961791AG1-021 GEN
Solar/Wind Harmer
1.413
315657AE1-056 GEN
Solar/Wind Harmer
3.52
3137643SOCKMAN
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
0.605
316087AB2-174 GEN
Solar/Wind Harmer
1.217
315607AA1-063A GEN
Solar/Wind Harmer
0.809
946281AF1-292 GEN
Solar/Wind Harmer
0.178
3146043SEABORD
Solar/Wind Harmer
-0.008
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.95
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.024
MECLTFEXP_MEC->PJM
CLTF
0.294
SIGELTFEXP_SIGE->PJM
CLTF
0.009
CPLELTFEXP_CPLE->PJM
CLTF
1.034
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.162
LAGNLTFEXP_LAGN->PJM
CLTF
0.596
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.98
TVALTFEXP_TVA->PJM
CLTF
0.298
NYPJM->LTFIMP_NY
CLTF
0.116
LGEELTFEXP_LGEE->PJM
CLTF
0.107
WECLTFEXP_WEC->PJM
CLTF
0.055

Details for 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 2201_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:132.37 %
Rating:250.89 MVA
Rating Type:B
MVA to Mitigate:332.1
MW Contribution:1.66
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
4.233
3151261ROARAP2
50/50
0.184
3151601KERR 3
50/50
0.161
3151581KERR 1
50/50
0.058
3151391GASTONA
50/50
0.203
3151411GASTONB
50/50
0.203
3144293JTRSVLE
50/50
0.226
960081AF2-299 GEN
Solar/Wind Harmer
5.617
971795AH1-408 GEN
Solar/Wind Harmer
32.424
3145783HORNRTN
Solar/Wind Harmer
0.139
316190AA2-174 GEN
Solar/Wind Harmer
0
316237AB2-079_GEN
Solar/Wind Harmer
0.001
316129AC1-054 GEN
Solar/Wind Harmer
0.385
971065AG2-659 GEN
Solar/Wind Harmer
4.195
3146263WOODLND
Solar/Wind Harmer
0.084
316212AC1-099_GEN
Solar/Wind Harmer
0.427
970685AG2-442 GEN
Solar/Wind Harmer
5.741
3151281ROARAP4
50/50
0.179
3151281ROARAP4
50/50
0.168
3151611KERR 4
50/50
0.161
3151621KERR 5
50/50
0.161
3151631KERR 6
50/50
0.161
3151641KERR 7
50/50
0.161
3151151S HAMPT1
50/50
0.149
316087AB2-174 GEN
Solar/Wind Harmer
0.013
3137643SOCKMAN
Solar/Wind Harmer
1.011
315607AA1-063A GEN
Solar/Wind Harmer
0.249
3146043SEABORD
Solar/Wind Harmer
0.118
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
970831AG2-522 GEN
Solar/Wind Harmer
4.555
971443AH1-215 GEN
Solar/Wind Harmer
1.484
3144303KENBRDG
Solar/Wind Harmer
0.07
965291AG1-394 GEN
Solar/Wind Harmer
0.365
970683AG2-441 GEN
Solar/Wind Harmer
5.125
970681AG2-440 GEN
Solar/Wind Harmer
4.1
3146033SCOT NK
Solar/Wind Harmer
0.305
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
315652AC1-086 GEN
Solar/Wind Harmer
8.263
3145796HORNRTN
Solar/Wind Harmer
0.228
3145796HORNRTN
Solar/Wind Harmer
0.028
946301AF1-294 GEN
Solar/Wind Harmer
1.32
961791AG1-021 GEN
Solar/Wind Harmer
0.642
3145513AHOSKIE
Solar/Wind Harmer
0.134
3145513AHOSKIE
Solar/Wind Harmer
0.064
316319Z2-044 C
Solar/Wind Harmer
0
3145683EARLEYS
Solar/Wind Harmer
0.121
3145893MURPHYS
Solar/Wind Harmer
0.301
3145893MURPHYS
Solar/Wind Harmer
0.334
316011AB1-132 GEN
Solar/Wind Harmer
1.366
316023GEN1_S
Solar/Wind Harmer
0.169
962571AG1-106 GEN
Solar/Wind Harmer
1.069
3145796HORNRTN
Solar/Wind Harmer
0.235
3151261ROARAP2
50/50
0.18
3151591KERR 2
50/50
0.161
3151391GASTONA
50/50
0.203
3151411GASTONB
50/50
0.203
3144293JTRSVLE
50/50
0.226
3147043LAWRENC
Solar/Wind Harmer
0.265
313506AB2-031 GEN
Solar/Wind Harmer
1.171
316131AB2-060 GEN
Solar/Wind Harmer
0.344
964241AG1-285 GEN
Solar/Wind Harmer
6.845
315785AD2-033 C
Solar/Wind Harmer
0.744
970257AG2-171 GEN
Solar/Wind Harmer
2.795
959311AF2-222 GEN
Solar/Wind Harmer
7.502
3146263WOODLND
Solar/Wind Harmer
0.084
316210AC1-098 GEN
Solar/Wind Harmer
0.766
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
316365GEN2_N
Solar/Wind Harmer
0.169
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
957521AF2-046 GEN
Solar/Wind Harmer
5.432
961681AG1-008 GEN
Solar/Wind Harmer
5.432
316327AA2-057 GEN
Solar/Wind Harmer
0.11
3145796HORNRTN
Solar/Wind Harmer
0.285
3145796HORNRTN
Solar/Wind Harmer
0.071
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.068
3146173TUNIS
Solar/Wind Harmer
0.068
963181AG1-167 GEN
Solar/Wind Harmer
0.268
316463AE2-346 GEN
Solar/Wind Harmer
0.055
316140AB2-099
Solar/Wind Harmer
0.023
962331AG1-082 GEN
Solar/Wind Harmer
0.682
3146233WITAKRS
Solar/Wind Harmer
0.316
3146233WITAKRS
Solar/Wind Harmer
0.043
3138543CONSLDL
Solar/Wind Harmer
0.041
3147133PAMPLIN
Solar/Wind Harmer
0.188
971193AH1-056 GEN
Solar/Wind Harmer
3.655
315724AD1-057 GEN
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
0.071
3145823KELFORD
Solar/Wind Harmer
0.068
3146173TUNIS
Solar/Wind Harmer
0.068
970401AG2-262 GEN
Solar/Wind Harmer
0.399
963171AG1-166 GEN
Solar/Wind Harmer
0.357
971563AH1-280 GEN
Solar/Wind Harmer
0.714
3146233WITAKRS
Solar/Wind Harmer
0.25
3145683EARLEYS
Solar/Wind Harmer
0.06
315722AD1-056 GEN
Solar/Wind Harmer
0.369
970535AG2-341 GEN
50/50
1.661
3151361ROSEMG1
50/50
0.256
3151371ROSEMS1
50/50
0.159
3151381ROSEMG2
50/50
0.12
3144293JTRSVLE
50/50
0.226
3144293JTRSVLE
50/50
0.19
316181AB2-040 GEN
Solar/Wind Harmer
0.55
3145593CAROLNA
Solar/Wind Harmer
0.148
3145593CAROLNA
Solar/Wind Harmer
0.148
966811AG1-552 GEN
Solar/Wind Harmer
1.603
3145593CAROLNA
Solar/Wind Harmer
0.184
3145783HORNRTN
Solar/Wind Harmer
2.476
3145783HORNRTN
Solar/Wind Harmer
1.98
3145783HORNRTN
Solar/Wind Harmer
0.619
3145783HORNRTN
Solar/Wind Harmer
0.248
316426AA2-053 GEN
Solar/Wind Harmer
0.446
313527AB2-043 GEN
Solar/Wind Harmer
0.001
316274AC1-208 GEN
Solar/Wind Harmer
0.487
970323AG2-213 GEN
Solar/Wind Harmer
3.727
971775AH1-396 GEN
Solar/Wind Harmer
0.14
316034AC1-036 C
Solar/Wind Harmer
0.006
939181AE1-148 GEN
Solar/Wind Harmer
4.028
3145893MURPHYS
Solar/Wind Harmer
0.503
3145893MURPHYS
Solar/Wind Harmer
0.135
962561AG1-105 GEN
Solar/Wind Harmer
3.576
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.045
3145796HORNRTN
Solar/Wind Harmer
0.213
3146173TUNIS
Solar/Wind Harmer
0.068
3146173TUNIS
Solar/Wind Harmer
0.068
964791AG1-342 GEN
Solar/Wind Harmer
1.304
3146843MT LREL
Solar/Wind Harmer
0.068
3146843MT LREL
Solar/Wind Harmer
0.068
958211AF2-115 GEN
Solar/Wind Harmer
0.803
963191AG1-168 GEN
Solar/Wind Harmer
0.268
3147133PAMPLIN
Solar/Wind Harmer
0.06
3147133PAMPLIN
Solar/Wind Harmer
0.048
3144356SAPONY
Solar/Wind Helper
0.423
3145683EARLEYS
Solar/Wind Harmer
0.06
3145683EARLEYS
Solar/Wind Harmer
0.06
315657AE1-056 GEN
Solar/Wind Harmer
2.07
316315AB2-025 C
Solar/Wind Helper
0.36
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.644
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.446
MECLTFEXP_MEC->PJM
CLTF
0.407
SIGELTFEXP_SIGE->PJM
CLTF
0.012
CPLELTFEXP_CPLE->PJM
CLTF
1.408
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.445
LAGNLTFEXP_LAGN->PJM
CLTF
0.846
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.786
TVALTFEXP_TVA->PJM
CLTF
0.423
NYPJM->LTFIMP_NY
CLTF
0.184
LGEELTFEXP_LGEE->PJM
CLTF
0.147
WECLTFEXP_WEC->PJM
CLTF
0.076

Details for 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 254_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.2 %
Rating:250.89 MVA
Rating Type:B
MVA to Mitigate:319.14
MW Contribution:1.66
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
4.234
3151261ROARAP2
50/50
0.184
3151601KERR 3
50/50
0.162
3151581KERR 1
50/50
0.058
3151391GASTONA
50/50
0.204
3151411GASTONB
50/50
0.204
3144293JTRSVLE
50/50
0.226
960081AF2-299 GEN
Solar/Wind Harmer
5.618
971795AH1-408 GEN
Solar/Wind Harmer
32.433
3145783HORNRTN
Solar/Wind Harmer
0.139
316190AA2-174 GEN
Solar/Wind Harmer
0
316237AB2-079_GEN
Solar/Wind Harmer
0.001
316129AC1-054 GEN
Solar/Wind Harmer
0.386
971065AG2-659 GEN
Solar/Wind Harmer
4.2
3146263WOODLND
Solar/Wind Harmer
0.084
316212AC1-099_GEN
Solar/Wind Harmer
0.428
970685AG2-442 GEN
Solar/Wind Harmer
5.75
3145893MURPHYS
Solar/Wind Harmer
0.301
3145893MURPHYS
Solar/Wind Harmer
0.335
316011AB1-132 GEN
Solar/Wind Harmer
1.368
962571AG1-106 GEN
Solar/Wind Harmer
1.071
3145796HORNRTN
Solar/Wind Harmer
0.235
3145796HORNRTN
Solar/Wind Harmer
0.071
3145823KELFORD
Solar/Wind Harmer
0.068
3146173TUNIS
Solar/Wind Harmer
0.068
970401AG2-262 GEN
Solar/Wind Harmer
0.399
963171AG1-166 GEN
Solar/Wind Harmer
0.358
971563AH1-280 GEN
Solar/Wind Harmer
0.715
3146233WITAKRS
Solar/Wind Harmer
0.251
3145683EARLEYS
Solar/Wind Harmer
0.06
315722AD1-056 GEN
Solar/Wind Harmer
0.369
316023GEN1_S
Solar/Wind Helper
1.974
3151281ROARAP4
50/50
0.179
3151281ROARAP4
50/50
0.168
3151611KERR 4
50/50
0.162
3151621KERR 5
50/50
0.162
3151631KERR 6
50/50
0.162
3151641KERR 7
50/50
0.162
3151151S HAMPT1
50/50
0.149
316087AB2-174 GEN
Solar/Wind Harmer
0.013
3137643SOCKMAN
Solar/Wind Harmer
1.012
315607AA1-063A GEN
Solar/Wind Harmer
0.249
3146043SEABORD
Solar/Wind Harmer
0.118
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
970831AG2-522 GEN
Solar/Wind Harmer
4.56
971443AH1-215 GEN
Solar/Wind Harmer
1.486
3144303KENBRDG
Solar/Wind Harmer
0.07
965291AG1-394 GEN
Solar/Wind Harmer
0.366
970683AG2-441 GEN
Solar/Wind Harmer
5.134
970681AG2-440 GEN
Solar/Wind Harmer
4.107
3146033SCOT NK
Solar/Wind Harmer
0.305
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
315652AC1-086 GEN
Solar/Wind Harmer
8.277
3145796HORNRTN
Solar/Wind Harmer
0.228
3145796HORNRTN
Solar/Wind Harmer
0.029
946301AF1-294 GEN
Solar/Wind Harmer
1.323
961791AG1-021 GEN
Solar/Wind Harmer
0.644
3145513AHOSKIE
Solar/Wind Harmer
0.134
3145513AHOSKIE
Solar/Wind Harmer
0.064
316319Z2-044 C
Solar/Wind Harmer
0
3145683EARLEYS
Solar/Wind Harmer
0.121
3145683EARLEYS
Solar/Wind Harmer
0.06
3145683EARLEYS
Solar/Wind Harmer
0.06
315657AE1-056 GEN
Solar/Wind Harmer
2.075
316315AB2-025 C
Solar/Wind Helper
0.359
3151261ROARAP2
50/50
0.18
3151591KERR 2
50/50
0.162
3151391GASTONA
50/50
0.204
3151411GASTONB
50/50
0.204
3144293JTRSVLE
50/50
0.226
3147043LAWRENC
Solar/Wind Harmer
0.265
313506AB2-031 GEN
Solar/Wind Harmer
1.172
316131AB2-060 GEN
Solar/Wind Harmer
0.344
964241AG1-285 GEN
Solar/Wind Harmer
6.854
315785AD2-033 C
Solar/Wind Harmer
0.745
970257AG2-171 GEN
Solar/Wind Harmer
2.799
959311AF2-222 GEN
Solar/Wind Harmer
7.513
3146263WOODLND
Solar/Wind Harmer
0.084
316210AC1-098 GEN
Solar/Wind Harmer
0.768
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
957521AF2-046 GEN
Solar/Wind Harmer
5.441
961681AG1-008 GEN
Solar/Wind Harmer
5.441
316327AA2-057 GEN
Solar/Wind Harmer
0.11
3145796HORNRTN
Solar/Wind Harmer
0.285
3145796HORNRTN
Solar/Wind Harmer
0.071
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.068
3146173TUNIS
Solar/Wind Harmer
0.068
963181AG1-167 GEN
Solar/Wind Harmer
0.268
316463AE2-346 GEN
Solar/Wind Harmer
0.055
316140AB2-099
Solar/Wind Harmer
0.023
962331AG1-082 GEN
Solar/Wind Harmer
0.683
3146233WITAKRS
Solar/Wind Harmer
0.316
3146233WITAKRS
Solar/Wind Harmer
0.043
3138543CONSLDL
Solar/Wind Harmer
0.041
3147133PAMPLIN
Solar/Wind Harmer
0.189
971193AH1-056 GEN
Solar/Wind Harmer
3.663
315724AD1-057 GEN
Solar/Wind Harmer
0.219
316365GEN2_N
Solar/Wind Helper
1.974
970535AG2-341 GEN
50/50
1.663
3151361ROSEMG1
50/50
0.257
3151371ROSEMS1
50/50
0.159
3151381ROSEMG2
50/50
0.12
3144293JTRSVLE
50/50
0.226
3144293JTRSVLE
50/50
0.191
316181AB2-040 GEN
Solar/Wind Harmer
0.55
3145593CAROLNA
Solar/Wind Harmer
0.148
3145593CAROLNA
Solar/Wind Harmer
0.148
966811AG1-552 GEN
Solar/Wind Harmer
1.605
3145593CAROLNA
Solar/Wind Harmer
0.184
3145783HORNRTN
Solar/Wind Harmer
2.478
3145783HORNRTN
Solar/Wind Harmer
1.982
3145783HORNRTN
Solar/Wind Harmer
0.619
3145783HORNRTN
Solar/Wind Harmer
0.248
316426AA2-053 GEN
Solar/Wind Harmer
0.447
313527AB2-043 GEN
Solar/Wind Harmer
0.001
316274AC1-208 GEN
Solar/Wind Harmer
0.487
970323AG2-213 GEN
Solar/Wind Harmer
3.732
971775AH1-396 GEN
Solar/Wind Harmer
0.14
316034AC1-036 C
Solar/Wind Harmer
0.006
939181AE1-148 GEN
Solar/Wind Harmer
4.034
3145893MURPHYS
Solar/Wind Harmer
0.504
3145893MURPHYS
Solar/Wind Harmer
0.135
962561AG1-105 GEN
Solar/Wind Harmer
3.582
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3142666NORTHAMPTON
Solar/Wind Harmer
0.045
3145796HORNRTN
Solar/Wind Harmer
0.214
3146173TUNIS
Solar/Wind Harmer
0.068
3146173TUNIS
Solar/Wind Harmer
0.068
964791AG1-342 GEN
Solar/Wind Harmer
1.307
3146843MT LREL
Solar/Wind Harmer
0.068
3146843MT LREL
Solar/Wind Harmer
0.068
958211AF2-115 GEN
Solar/Wind Harmer
0.804
963191AG1-168 GEN
Solar/Wind Harmer
0.268
3147133PAMPLIN
Solar/Wind Harmer
0.06
3147133PAMPLIN
Solar/Wind Harmer
0.048
3144356SAPONY
Solar/Wind Helper
0.423
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.782
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.482
MECLTFEXP_MEC->PJM
CLTF
0.423
SIGELTFEXP_SIGE->PJM
CLTF
0.013
CPLELTFEXP_CPLE->PJM
CLTF
1.418
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.573
LAGNLTFEXP_LAGN->PJM
CLTF
0.865
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.815
TVALTFEXP_TVA->PJM
CLTF
0.432
NYPJM->LTFIMP_NY
CLTF
0.178
LGEELTFEXP_LGEE->PJM
CLTF
0.153
WECLTFEXP_WEC->PJM
CLTF
0.079

Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 298_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:143.44 %
Rating:198.15 MVA
Rating Type:B
MVA to Mitigate:284.23
MW Contribution:1.86
Bus #Bus NameTypeMW Contribution
315657AE1-056 GEN
Solar/Wind Harmer
17.667
946301AF1-294 GEN
Solar/Wind Harmer
9.167
961791AG1-021 GEN
Solar/Wind Harmer
4.46
970683AG2-441 GEN
Solar/Wind Harmer
26.407
970681AG2-440 GEN
Solar/Wind Harmer
21.126
3144303KENBRDG
Solar/Wind Harmer
0.258
971443AH1-215 GEN
Solar/Wind Harmer
5.329
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.147
3144293JTRSVLE
50/50
1.569
942461AE2-259 GEN
Solar/Wind Harmer
-0.004
3147133PAMPLIN
Solar/Wind Harmer
1.607
971193AH1-056 GEN
Solar/Wind Harmer
31.191
963181AG1-167 GEN
Solar/Wind Harmer
1.858
959311AF2-222 GEN
Solar/Wind Harmer
30.607
970257AG2-171 GEN
Solar/Wind Harmer
10.351
315785AD2-033 C
Solar/Wind Harmer
2.396
964241AG1-285 GEN
Solar/Wind Harmer
14.554
316131AB2-060 GEN
Solar/Wind Harmer
0.541
3147043LAWRENC
Solar/Wind Harmer
0.044
3146926FARMVIL
Solar/Wind Helper
0.23
3144293JTRSVLE
50/50
1.569
3147043LAWRENC
50/50
0.703
963171AG1-166 GEN
Solar/Wind Harmer
2.478
971563AH1-280 GEN
Solar/Wind Harmer
4.955
970685AG2-442 GEN
Solar/Wind Harmer
29.576
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970401AG2-262 GEN
Solar/Wind Harmer
0.497
971795AH1-408 GEN
Solar/Wind Harmer
4.08
3146926FARMVIL
Solar/Wind Helper
0.23
3144293JTRSVLE
50/50
1.569
3144293JTRSVLE
50/50
1.321
970535AG2-341 GEN
50/50
1.858
3147133PAMPLIN
Solar/Wind Harmer
0.512
3147133PAMPLIN
Solar/Wind Harmer
0.409
958211AF2-115 GEN
Solar/Wind Harmer
5.574
963191AG1-168 GEN
Solar/Wind Harmer
1.858
316034AC1-036 C
Solar/Wind Harmer
0.024
970323AG2-213 GEN
Solar/Wind Harmer
13.801
971775AH1-396 GEN
Solar/Wind Harmer
0.518
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
4.623
964791AG1-342 GEN
Solar/Wind Harmer
1.627
3146843MT LREL
Solar/Wind Harmer
0.084
3146843MT LREL
Solar/Wind Harmer
0.084
939181AE1-148 GEN
Solar/Wind Harmer
3.552
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.236
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.202
MECLTFEXP_MEC->PJM
CLTF
0.047
SIGELTFEXP_SIGE->PJM
CLTF
0.001
CPLELTFEXP_CPLE->PJM
CLTF
0.235
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.587
LAGNLTFEXP_LAGN->PJM
CLTF
0.119
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.444
TVALTFEXP_TVA->PJM
CLTF
0.06
NYPJM->LTFIMP_NY
CLTF
0.058
LGEELTFEXP_LGEE->PJM
CLTF
0.017
WECLTFEXP_WEC->PJM
CLTF
0.008

Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235_SRT-A-4


Base Case Flowgate

Area:DVP
Facility Description:
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-2: LN 235_SRT-A-4
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:203.55 %
Rating:182.74 MVA
Rating Type:B
MVA to Mitigate:371.98
MW Contribution:2.5
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.671
3147043LAWRENC
50/50
0.941
3151601KERR 3
50/50
0.191
3151581KERR 1
50/50
0.068
963171AG1-166 GEN
Solar/Wind Harmer
2.639
971563AH1-280 GEN
Solar/Wind Harmer
5.278
970685AG2-442 GEN
Solar/Wind Harmer
31.919
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970401AG2-262 GEN
Solar/Wind Harmer
0.698
971795AH1-408 GEN
Solar/Wind Harmer
5.637
971065AG2-659 GEN
Solar/Wind Harmer
3.322
316129AC1-054 GEN
Solar/Wind Harmer
0.282
316003AC1-222 GEN
Solar/Wind Harmer
0.002
957481AF2-042 GEN
Solar/Wind Harmer
8.413
3146926FARMVIL
Solar/Wind Helper
0.257
316322AB2-045
Solar/Wind Helper
0.352
3146776BUCKING
Solar/Wind Helper
0.126
3144293JTRSVLE
50/50
1.671
3151591KERR 2
50/50
0.191
942461AE2-259 GEN
Solar/Wind Harmer
-0.004
3147133PAMPLIN
Solar/Wind Harmer
1.7
971193AH1-056 GEN
Solar/Wind Harmer
32.99
963181AG1-167 GEN
Solar/Wind Harmer
1.979
959311AF2-222 GEN
Solar/Wind Harmer
33.47
970257AG2-171 GEN
Solar/Wind Harmer
11.392
315785AD2-033 C
Solar/Wind Harmer
2.664
964241AG1-285 GEN
Solar/Wind Harmer
16.835
316131AB2-060 GEN
Solar/Wind Harmer
0.651
3147043LAWRENC
Solar/Wind Harmer
0.059
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.714
3146926FARMVIL
Solar/Wind Helper
0.257
3146776BUCKING
Solar/Wind Helper
0.114
3144293JTRSVLE
50/50
1.671
3144293JTRSVLE
50/50
1.408
970535AG2-341 GEN
50/50
2.502
3152661PLYWOOD A
50/50
0.176
3147133PAMPLIN
Solar/Wind Harmer
0.541
3147133PAMPLIN
Solar/Wind Harmer
0.433
958211AF2-115 GEN
Solar/Wind Harmer
5.938
963191AG1-168 GEN
Solar/Wind Harmer
1.979
316034AC1-036 C
Solar/Wind Harmer
0.026
970323AG2-213 GEN
Solar/Wind Harmer
15.189
971775AH1-396 GEN
Solar/Wind Harmer
0.57
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
6.273
964791AG1-342 GEN
Solar/Wind Harmer
2.284
3146843MT LREL
Solar/Wind Harmer
0.118
3146843MT LREL
Solar/Wind Harmer
0.118
939181AE1-148 GEN
Solar/Wind Harmer
5.321
970099AG2-077 GEN
Solar/Wind Harmer
3.365
3146776BUCKING
Solar/Wind Helper
1.263
3146776BUCKING
Solar/Wind Helper
0.102
315821AE2-092 GEN
Solar/Wind Helper
1.092
3151611KERR 4
50/50
0.191
3151621KERR 5
50/50
0.191
3151631KERR 6
50/50
0.191
3151641KERR 7
50/50
0.191
315657AE1-056 GEN
Solar/Wind Harmer
18.686
946301AF1-294 GEN
Solar/Wind Harmer
9.765
961791AG1-021 GEN
Solar/Wind Harmer
4.75
970683AG2-441 GEN
Solar/Wind Harmer
28.499
970681AG2-440 GEN
Solar/Wind Harmer
22.8
3144303KENBRDG
Solar/Wind Harmer
0.284
971443AH1-215 GEN
Solar/Wind Harmer
5.877
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.235
970831AG2-522 GEN
Solar/Wind Harmer
3.065
3147173SINAI
Solar/Wind Harmer
0.064
3147243WELCO
Solar/Wind Harmer
0.04
270494AE1-108_GEN
Solar/Wind Helper
1.623
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.693
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.323
MECLTFEXP_MEC->PJM
CLTF
0.31
SIGELTFEXP_SIGE->PJM
CLTF
0.009
CPLELTFEXP_CPLE->PJM
CLTF
1.553
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.912
LAGNLTFEXP_LAGN->PJM
CLTF
0.808
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.114
TVALTFEXP_TVA->PJM
CLTF
0.399
NYPJM->LTFIMP_NY
CLTF
0.153
LGEELTFEXP_LGEE->PJM
CLTF
0.097
WECLTFEXP_WEC->PJM
CLTF
0.05

Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-2: LN 1012_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:163.16 %
Rating:182.74 MVA
Rating Type:B
MVA to Mitigate:298.15
MW Contribution:1.01
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.139
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
3147133PAMPLIN
Solar/Wind Harmer
1.658
959311AF2-222 GEN
Solar/Wind Harmer
46.956
964241AG1-285 GEN
Solar/Wind Harmer
35.217
971193AH1-056 GEN
Solar/Wind Harmer
32.165
963181AG1-167 GEN
Solar/Wind Harmer
1.349
970257AG2-171 GEN
Solar/Wind Harmer
7.017
315785AD2-033 C
Solar/Wind Harmer
1.588
316131AB2-060 GEN
Solar/Wind Harmer
0.291
3144293JTRSVLE
50/50
1.139
970685AG2-442 GEN
Solar/Wind Harmer
39.443
963171AG1-166 GEN
Solar/Wind Harmer
1.799
971563AH1-280 GEN
Solar/Wind Harmer
3.597
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970683AG2-441 GEN
Solar/Wind Harmer
35.217
970681AG2-440 GEN
Solar/Wind Harmer
28.173
315657AE1-056 GEN
Solar/Wind Harmer
18.219
971443AH1-215 GEN
Solar/Wind Harmer
8.875
946301AF1-294 GEN
Solar/Wind Harmer
6.655
961791AG1-021 GEN
Solar/Wind Harmer
3.238
3144303KENBRDG
Solar/Wind Harmer
0.175
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3144293JTRSVLE
50/50
1.139
3144293JTRSVLE
50/50
0.959
970535AG2-341 GEN
50/50
1.009
316034AC1-036 C
Solar/Wind Harmer
0.039
3147133PAMPLIN
Solar/Wind Harmer
0.528
3147133PAMPLIN
Solar/Wind Harmer
0.422
958211AF2-115 GEN
Solar/Wind Harmer
4.047
963191AG1-168 GEN
Solar/Wind Harmer
1.349
970323AG2-213 GEN
Solar/Wind Harmer
9.357
971775AH1-396 GEN
Solar/Wind Harmer
0.351
313527AB2-043 GEN
Solar/Wind Harmer
0.001
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.242
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.281
MECLTFEXP_MEC->PJM
CLTF
0.057
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CPLELTFEXP_CPLE->PJM
CLTF
0.369
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.803
LAGNLTFEXP_LAGN->PJM
CLTF
0.174
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.722
TVALTFEXP_TVA->PJM
CLTF
0.086
NYPJM->LTFIMP_NY
CLTF
0.054
LGEELTFEXP_LGEE->PJM
CLTF
0.016
WECLTFEXP_WEC->PJM
CLTF
0.008

Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P7-1: LN 1041-38_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P7-1: LN 1041-38_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:150.91 %
Rating:208.7 MVA
Rating Type:C
MVA to Mitigate:314.94
MW Contribution:2.05
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.178
963171AG1-166 GEN
Solar/Wind Harmer
4.896
971563AH1-280 GEN
Solar/Wind Harmer
4.896
970685AG2-442 GEN
Solar/Wind Harmer
30.066
316237AB2-079_GEN
Solar/Wind Harmer
0.51
970401AG2-262 GEN
Solar/Wind Harmer
0.645
3147043LAWRENC
Adder
0.688
971795AH1-408 GEN
Solar/Wind Harmer
5.453
971065AG2-659 GEN
Solar/Wind Harmer
3.571
316129AC1-054 GEN
Solar/Wind Harmer
0.599
3146926FARMVIL
Solar/Wind Helper
0.077
315657AE1-056 GEN
Solar/Wind Harmer
15.948
946301AF1-294 GEN
Solar/Wind Harmer
10.037
961791AG1-021 GEN
Solar/Wind Harmer
4.896
970683AG2-441 GEN
Solar/Wind Harmer
26.845
970681AG2-440 GEN
Solar/Wind Harmer
21.476
3144303KENBRDG
Solar/Wind Harmer
-0.023
971443AH1-215 GEN
Solar/Wind Harmer
5.673
316239AB2-077_GEN
Solar/Wind Harmer
0.51
316238AB2-078_GEN
Solar/Wind Harmer
0.51
316118AC1-105 GEN
Solar/Wind Harmer
0.48
970831AG2-522 GEN
Solar/Wind Harmer
3.251
3144293JTRSVLE
50/50
1.178
942461AE2-259 GEN
Solar/Wind Harmer
7.822
3147133PAMPLIN
Solar/Wind Harmer
-0.133
971193AH1-056 GEN
Solar/Wind Harmer
26.58
963181AG1-167 GEN
Solar/Wind Harmer
3.672
959311AF2-222 GEN
Solar/Wind Harmer
32.066
970257AG2-171 GEN
Solar/Wind Harmer
10.969
315785AD2-033 C
Solar/Wind Harmer
6.171
964241AG1-285 GEN
Solar/Wind Harmer
17.08
316131AB2-060 GEN
Solar/Wind Harmer
2.006
3147043LAWRENC
Solar/Wind Harmer
-0.005
3146926FARMVIL
Solar/Wind Helper
0.077
3144293JTRSVLE
50/50
1.178
3144293JTRSVLE
50/50
0.992
970535AG2-341 GEN
50/50
2.049
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.12
963191AG1-168 GEN
Solar/Wind Harmer
3.672
316034AC1-036 C
Solar/Wind Harmer
0.544
970323AG2-213 GEN
Solar/Wind Harmer
14.625
971775AH1-396 GEN
Solar/Wind Harmer
2.083
313527AB2-043 GEN
Solar/Wind Harmer
2.892
962561AG1-105 GEN
Solar/Wind Harmer
6.237
939181AE1-148 GEN
Solar/Wind Harmer
5.801
964791AG1-342 GEN
Solar/Wind Harmer
2.11
3146843MT LREL
Solar/Wind Harmer
-0.01
3146843MT LREL
Solar/Wind Harmer
-0.01
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.77
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.562
MECLTFEXP_MEC->PJM
CLTF
0.137
SIGELTFEXP_SIGE->PJM
CLTF
0.004
CPLELTFEXP_CPLE->PJM
CLTF
0.643
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.67
LAGNLTFEXP_LAGN->PJM
CLTF
0.338
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.267
TVALTFEXP_TVA->PJM
CLTF
0.168
NYPJM->LTFIMP_NY
CLTF
0.08
LGEELTFEXP_LGEE->PJM
CLTF
0.045
WECLTFEXP_WEC->PJM
CLTF
0.023

Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P7-1: LN 1041-137_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P7-1: LN 1041-137_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:146.35 %
Rating:208.7 MVA
Rating Type:C
MVA to Mitigate:305.44
MW Contribution:3.21
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.226
963171AG1-166 GEN
Solar/Wind Harmer
5.096
971563AH1-280 GEN
Solar/Wind Harmer
5.096
970685AG2-442 GEN
Solar/Wind Harmer
31.639
316237AB2-079_GEN
Solar/Wind Harmer
0.57
970401AG2-262 GEN
Solar/Wind Harmer
0.725
3147043LAWRENC
Adder
0.739
971795AH1-408 GEN
Solar/Wind Harmer
5.73
3146926FARMVIL
Solar/Wind Helper
0.071
315657AE1-056 GEN
Solar/Wind Harmer
16.495
946301AF1-294 GEN
Solar/Wind Harmer
10.448
961791AG1-021 GEN
Solar/Wind Harmer
5.096
970683AG2-441 GEN
Solar/Wind Harmer
28.249
970681AG2-440 GEN
Solar/Wind Harmer
22.599
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.071
316239AB2-077_GEN
Solar/Wind Harmer
0.57
316238AB2-078_GEN
Solar/Wind Harmer
0.57
316118AC1-105 GEN
Solar/Wind Harmer
0.533
3144293JTRSVLE
50/50
1.226
3144293JTRSVLE
50/50
1.032
970535AG2-341 GEN
50/50
3.21
3147133PAMPLIN
Solar/Wind Harmer
-0.044
3147133PAMPLIN
Solar/Wind Harmer
-0.035
958211AF2-115 GEN
Solar/Wind Harmer
6.37
963191AG1-168 GEN
Solar/Wind Harmer
3.822
316034AC1-036 C
Solar/Wind Harmer
0.581
970323AG2-213 GEN
Solar/Wind Harmer
15.631
971775AH1-396 GEN
Solar/Wind Harmer
2.226
939181AE1-148 GEN
Solar/Wind Harmer
11.412
313527AB2-043 GEN
Solar/Wind Harmer
3.295
962561AG1-105 GEN
Solar/Wind Harmer
7.037
964791AG1-342 GEN
Solar/Wind Harmer
2.373
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
3144293JTRSVLE
50/50
1.226
942461AE2-259 GEN
Solar/Wind Harmer
7.982
3147133PAMPLIN
Solar/Wind Harmer
-0.137
971193AH1-056 GEN
Solar/Wind Harmer
27.492
963181AG1-167 GEN
Solar/Wind Harmer
3.822
959311AF2-222 GEN
Solar/Wind Harmer
34.098
970257AG2-171 GEN
Solar/Wind Harmer
11.723
315785AD2-033 C
Solar/Wind Harmer
6.646
964241AG1-285 GEN
Solar/Wind Harmer
18.887
316131AB2-060 GEN
Solar/Wind Harmer
2.271
3147043LAWRENC
Solar/Wind Harmer
-0.005
3146926FARMVIL
Solar/Wind Helper
0.071
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.555
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.435
MECLTFEXP_MEC->PJM
CLTF
0.103
SIGELTFEXP_SIGE->PJM
CLTF
0.003
CPLELTFEXP_CPLE->PJM
CLTF
0.493
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.283
LAGNLTFEXP_LAGN->PJM
CLTF
0.263
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.989
TVALTFEXP_TVA->PJM
CLTF
0.131
NYPJM->LTFIMP_NY
CLTF
0.069
LGEELTFEXP_LGEE->PJM
CLTF
0.034
WECLTFEXP_WEC->PJM
CLTF
0.017

Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.74 %
Rating:176.91 MVA
Rating Type:A
MVA to Mitigate:197.68
MW Contribution:1.47
Bus #Bus NameTypeMW Contribution
315657AE1-056 GEN
Solar/Wind Harmer
12.474
946301AF1-294 GEN
Solar/Wind Harmer
6.493
961791AG1-021 GEN
Solar/Wind Harmer
3.159
970683AG2-441 GEN
Solar/Wind Harmer
18.815
970681AG2-440 GEN
Solar/Wind Harmer
15.052
3144303KENBRDG
Solar/Wind Harmer
0.186
971443AH1-215 GEN
Solar/Wind Harmer
3.834
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3144293JTRSVLE
50/50
1.111
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
3147133PAMPLIN
Solar/Wind Harmer
1.135
971193AH1-056 GEN
Solar/Wind Harmer
22.023
963181AG1-167 GEN
Solar/Wind Harmer
1.316
959311AF2-222 GEN
Solar/Wind Harmer
21.938
970257AG2-171 GEN
Solar/Wind Harmer
7.441
315785AD2-033 C
Solar/Wind Harmer
1.731
3144293JTRSVLE
50/50
1.111
3147043LAWRENC
50/50
0.555
963171AG1-166 GEN
Solar/Wind Harmer
1.755
971563AH1-280 GEN
Solar/Wind Harmer
3.51
970685AG2-442 GEN
Solar/Wind Harmer
21.072
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970401AG2-262 GEN
Solar/Wind Harmer
0.402
3146926FARMVIL
Solar/Wind Helper
0.077
3144293JTRSVLE
50/50
1.111
3144293JTRSVLE
50/50
0.936
970535AG2-341 GEN
50/50
1.472
3147133PAMPLIN
Solar/Wind Harmer
0.361
3147133PAMPLIN
Solar/Wind Harmer
0.289
958211AF2-115 GEN
Solar/Wind Harmer
3.948
963191AG1-168 GEN
Solar/Wind Harmer
1.316
316034AC1-036 C
Solar/Wind Harmer
0.017
970323AG2-213 GEN
Solar/Wind Harmer
9.921
971775AH1-396 GEN
Solar/Wind Harmer
0.372
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
3.676
964791AG1-342 GEN
Solar/Wind Harmer
1.316
3146843MT LREL
Solar/Wind Harmer
0.068
3146843MT LREL
Solar/Wind Harmer
0.068
939181AE1-148 GEN
Solar/Wind Harmer
2.974
964241AG1-285 GEN
Solar/Wind Harmer
10.706
316131AB2-060 GEN
Solar/Wind Harmer
0.405
3147043LAWRENC
Solar/Wind Harmer
0.035
3146926FARMVIL
Solar/Wind Helper
0.077
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.594
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.472
MECLTFEXP_MEC->PJM
CLTF
0.111
SIGELTFEXP_SIGE->PJM
CLTF
0.003
CPLELTFEXP_CPLE->PJM
CLTF
0.554
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.392
LAGNLTFEXP_LAGN->PJM
CLTF
0.287
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.1
TVALTFEXP_TVA->PJM
CLTF
0.142
NYPJM->LTFIMP_NY
CLTF
0.068
LGEELTFEXP_LGEE->PJM
CLTF
0.035
WECLTFEXP_WEC->PJM
CLTF
0.018

Details for 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.62 %
Rating:199.0 MVA
Rating Type:B
MVA to Mitigate:220.14
MW Contribution:2.95
Bus #Bus NameTypeMW Contribution
3151601KERR 3
50/50
0.441
3151581KERR 1
50/50
0.157
971065AG2-659 GEN
Solar/Wind Harmer
9.388
316129AC1-054 GEN
Solar/Wind Harmer
1.555
316237AB2-079_GEN
Solar/Wind Harmer
0.392
970685AG2-442 GEN
Solar/Wind Harmer
8.731
963171AG1-166 GEN
Solar/Wind Harmer
1.15
971563AH1-280 GEN
Solar/Wind Harmer
1.15
3144293JTRSVLE
Adder
0.261
970401AG2-262 GEN
Solar/Wind Harmer
0.556
315693AD1-088 GEN
Solar/Wind Harmer
3.668
962491AG1-098 GEN
Solar/Wind Harmer
4.867
3147043LAWRENC
Adder
0.571
957481AF2-042 GEN
Solar/Wind Harmer
21.613
3151611KERR 4
50/50
0.441
3151621KERR 5
50/50
0.441
3151631KERR 6
50/50
0.441
3151641KERR 7
50/50
0.441
970831AG2-522 GEN
Solar/Wind Harmer
8.315
316239AB2-077_GEN
Solar/Wind Harmer
0.392
316238AB2-078_GEN
Solar/Wind Harmer
0.392
971443AH1-215 GEN
Solar/Wind Harmer
2.141
3144303KENBRDG
Solar/Wind Harmer
-0.009
970683AG2-441 GEN
Solar/Wind Harmer
7.795
970681AG2-440 GEN
Solar/Wind Harmer
6.236
946301AF1-294 GEN
Solar/Wind Harmer
2.358
961791AG1-021 GEN
Solar/Wind Harmer
1.15
315657AE1-056 GEN
Solar/Wind Harmer
3.246
316118AC1-105 GEN
Solar/Wind Harmer
0.482
971967AH1-528 GEN
Solar/Wind Harmer
13.161
970535AG2-341 GEN
50/50
2.952
939181AE1-148 GEN
Solar/Wind Harmer
12.325
313527AB2-043 GEN
Solar/Wind Harmer
2.056
970323AG2-213 GEN
Solar/Wind Harmer
5.403
971775AH1-396 GEN
Solar/Wind Harmer
0.769
316034AC1-036 C
Solar/Wind Harmer
0.2
958211AF2-115 GEN
Solar/Wind Harmer
1.438
963191AG1-168 GEN
Solar/Wind Harmer
0.863
3144293JTRSVLE
Adder
0.261
3144293JTRSVLE
Adder
0.219
962561AG1-105 GEN
Solar/Wind Harmer
5.146
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.007
964791AG1-342 GEN
Solar/Wind Harmer
1.819
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
970933AG2-581 GEN
Solar/Wind Harmer
6.563
970099AG2-077 GEN
Solar/Wind Harmer
8.645
971741AH1-377 GEN
Solar/Wind Harmer
7.526
3151591KERR 2
50/50
0.441
316131AB2-060 GEN
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
9.376
315785AD2-033 C
Solar/Wind Harmer
2.523
970257AG2-171 GEN
Solar/Wind Harmer
4.052
959311AF2-222 GEN
Solar/Wind Harmer
11.03
963181AG1-167 GEN
Solar/Wind Harmer
0.863
3144293JTRSVLE
Adder
0.261
3147133PAMPLIN
Solar/Wind Harmer
-0.027
971193AH1-056 GEN
Solar/Wind Harmer
5.41
942461AE2-259 GEN
Solar/Wind Harmer
1.069
3147043LAWRENC
Solar/Wind Harmer
-0.004
316478AD1-087 GEN
Solar/Wind Harmer
0.573
316486AD2-202 GEN
Solar/Wind Harmer
0.168
VTFLTFEXP_VFT->PJM
CMTX
0.415
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.437
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.297
G-007ALTFEXP_G-007A->PJM
CMTX
0.157
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.159
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.228
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.718
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.84

Details for 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: 593X2_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.8 %
Rating:199.0 MVA
Rating Type:B
MVA to Mitigate:216.52
MW Contribution:2.95
Bus #Bus NameTypeMW Contribution
3151601KERR 3
50/50
0.441
3151581KERR 1
50/50
0.157
971065AG2-659 GEN
Solar/Wind Harmer
9.391
316129AC1-054 GEN
Solar/Wind Harmer
1.556
316237AB2-079_GEN
Solar/Wind Harmer
0.392
970685AG2-442 GEN
Solar/Wind Harmer
8.749
963171AG1-166 GEN
Solar/Wind Harmer
1.153
971563AH1-280 GEN
Solar/Wind Harmer
1.153
3144293JTRSVLE
Adder
0.261
970401AG2-262 GEN
Solar/Wind Harmer
0.555
315693AD1-088 GEN
Solar/Wind Harmer
3.709
962491AG1-098 GEN
Solar/Wind Harmer
4.921
3147043LAWRENC
Adder
0.571
957481AF2-042 GEN
Solar/Wind Harmer
21.271
971795AH1-408 GEN
Solar/Wind Harmer
4.741
970535AG2-341 GEN
50/50
2.953
939181AE1-148 GEN
Solar/Wind Harmer
12.329
313527AB2-043 GEN
Solar/Wind Harmer
2.058
970323AG2-213 GEN
Solar/Wind Harmer
5.411
971775AH1-396 GEN
Solar/Wind Harmer
0.771
316034AC1-036 C
Solar/Wind Harmer
0.2
958211AF2-115 GEN
Solar/Wind Harmer
1.441
963191AG1-168 GEN
Solar/Wind Harmer
0.865
3144293JTRSVLE
Adder
0.261
3144293JTRSVLE
Adder
0.22
962561AG1-105 GEN
Solar/Wind Harmer
5.142
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.007
964791AG1-342 GEN
Solar/Wind Harmer
1.817
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
8.508
971741AH1-377 GEN
Solar/Wind Harmer
7.601
3151591KERR 2
50/50
0.441
316131AB2-060 GEN
Solar/Wind Harmer
1.353
964241AG1-285 GEN
Solar/Wind Harmer
9.384
315785AD2-033 C
Solar/Wind Harmer
2.527
970257AG2-171 GEN
Solar/Wind Harmer
4.058
959311AF2-222 GEN
Solar/Wind Harmer
11.048
963181AG1-167 GEN
Solar/Wind Harmer
0.865
3144293JTRSVLE
Adder
0.261
3147133PAMPLIN
Solar/Wind Harmer
-0.027
971193AH1-056 GEN
Solar/Wind Harmer
5.427
942461AE2-259 GEN
Solar/Wind Harmer
1.074
3147043LAWRENC
Solar/Wind Harmer
-0.004
316478AD1-087 GEN
Solar/Wind Harmer
0.568
316486AD2-202 GEN
Solar/Wind Harmer
0.166
3151611KERR 4
50/50
0.441
3151621KERR 5
50/50
0.441
3151631KERR 6
50/50
0.441
3151641KERR 7
50/50
0.441
970831AG2-522 GEN
Solar/Wind Harmer
8.318
316239AB2-077_GEN
Solar/Wind Harmer
0.392
316238AB2-078_GEN
Solar/Wind Harmer
0.392
971443AH1-215 GEN
Solar/Wind Harmer
2.144
3144303KENBRDG
Solar/Wind Harmer
-0.009
970683AG2-441 GEN
Solar/Wind Harmer
7.811
970681AG2-440 GEN
Solar/Wind Harmer
6.249
946301AF1-294 GEN
Solar/Wind Harmer
2.364
961791AG1-021 GEN
Solar/Wind Harmer
1.153
315657AE1-056 GEN
Solar/Wind Harmer
3.256
316118AC1-105 GEN
Solar/Wind Harmer
0.48
VTFLTFEXP_VFT->PJM
CMTX
0.421
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.438
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.3
G-007ALTFEXP_G-007A->PJM
CMTX
0.16
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.163
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.229
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.72
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.843

Details for 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: 593X1_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.8 %
Rating:199.0 MVA
Rating Type:B
MVA to Mitigate:216.51
MW Contribution:2.95
Bus #Bus NameTypeMW Contribution
3151601KERR 3
50/50
0.441
3151581KERR 1
50/50
0.157
971065AG2-659 GEN
Solar/Wind Harmer
9.391
316129AC1-054 GEN
Solar/Wind Harmer
1.556
316237AB2-079_GEN
Solar/Wind Harmer
0.392
970685AG2-442 GEN
Solar/Wind Harmer
8.749
963171AG1-166 GEN
Solar/Wind Harmer
1.153
971563AH1-280 GEN
Solar/Wind Harmer
1.153
3144293JTRSVLE
Adder
0.261
970401AG2-262 GEN
Solar/Wind Harmer
0.555
315693AD1-088 GEN
Solar/Wind Harmer
3.709
962491AG1-098 GEN
Solar/Wind Harmer
4.921
3147043LAWRENC
Adder
0.571
957481AF2-042 GEN
Solar/Wind Harmer
21.268
971795AH1-408 GEN
Solar/Wind Harmer
4.741
970535AG2-341 GEN
50/50
2.953
939181AE1-148 GEN
Solar/Wind Harmer
12.329
313527AB2-043 GEN
Solar/Wind Harmer
2.058
970323AG2-213 GEN
Solar/Wind Harmer
5.411
971775AH1-396 GEN
Solar/Wind Harmer
0.771
316034AC1-036 C
Solar/Wind Harmer
0.2
958211AF2-115 GEN
Solar/Wind Harmer
1.441
963191AG1-168 GEN
Solar/Wind Harmer
0.865
3144293JTRSVLE
Adder
0.261
3144293JTRSVLE
Adder
0.22
962561AG1-105 GEN
Solar/Wind Harmer
5.142
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.007
964791AG1-342 GEN
Solar/Wind Harmer
1.817
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
8.507
971741AH1-377 GEN
Solar/Wind Harmer
7.601
3151591KERR 2
50/50
0.441
316131AB2-060 GEN
Solar/Wind Harmer
1.353
964241AG1-285 GEN
Solar/Wind Harmer
9.384
315785AD2-033 C
Solar/Wind Harmer
2.527
970257AG2-171 GEN
Solar/Wind Harmer
4.059
959311AF2-222 GEN
Solar/Wind Harmer
11.048
963181AG1-167 GEN
Solar/Wind Harmer
0.865
3144293JTRSVLE
Adder
0.261
3147133PAMPLIN
Solar/Wind Harmer
-0.027
971193AH1-056 GEN
Solar/Wind Harmer
5.427
942461AE2-259 GEN
Solar/Wind Harmer
1.074
3147043LAWRENC
Solar/Wind Harmer
-0.004
316478AD1-087 GEN
Solar/Wind Harmer
0.568
316486AD2-202 GEN
Solar/Wind Harmer
0.166
3151611KERR 4
50/50
0.441
3151621KERR 5
50/50
0.441
3151631KERR 6
50/50
0.441
3151641KERR 7
50/50
0.441
970831AG2-522 GEN
Solar/Wind Harmer
8.318
316239AB2-077_GEN
Solar/Wind Harmer
0.392
316238AB2-078_GEN
Solar/Wind Harmer
0.392
971443AH1-215 GEN
Solar/Wind Harmer
2.144
3144303KENBRDG
Solar/Wind Harmer
-0.009
970683AG2-441 GEN
Solar/Wind Harmer
7.811
970681AG2-440 GEN
Solar/Wind Harmer
6.249
946301AF1-294 GEN
Solar/Wind Harmer
2.364
961791AG1-021 GEN
Solar/Wind Harmer
1.153
315657AE1-056 GEN
Solar/Wind Harmer
3.256
316118AC1-105 GEN
Solar/Wind Harmer
0.48
VTFLTFEXP_VFT->PJM
CMTX
0.421
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.438
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.3
G-007ALTFEXP_G-007A->PJM
CMTX
0.16
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.163
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.229
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.72
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.843

Details for 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.88 %
Rating:199.0 MVA
Rating Type:B
MVA to Mitigate:212.68
MW Contribution:2.95
Bus #Bus NameTypeMW Contribution
3151601KERR 3
50/50
0.441
3151581KERR 1
50/50
0.157
971065AG2-659 GEN
Solar/Wind Harmer
9.388
316129AC1-054 GEN
Solar/Wind Harmer
1.555
316237AB2-079_GEN
Solar/Wind Harmer
0.392
970685AG2-442 GEN
Solar/Wind Harmer
8.731
963171AG1-166 GEN
Solar/Wind Harmer
1.15
971563AH1-280 GEN
Solar/Wind Harmer
1.15
3144293JTRSVLE
Adder
0.261
970401AG2-262 GEN
Solar/Wind Harmer
0.556
315693AD1-088 GEN
Solar/Wind Harmer
3.668
962491AG1-098 GEN
Solar/Wind Harmer
4.867
3147043LAWRENC
Adder
0.571
957481AF2-042 GEN
Solar/Wind Harmer
21.613
970535AG2-341 GEN
50/50
2.952
939181AE1-148 GEN
Solar/Wind Harmer
12.325
313527AB2-043 GEN
Solar/Wind Harmer
2.056
970323AG2-213 GEN
Solar/Wind Harmer
5.403
971775AH1-396 GEN
Solar/Wind Harmer
0.769
316034AC1-036 C
Solar/Wind Harmer
0.2
958211AF2-115 GEN
Solar/Wind Harmer
1.438
963191AG1-168 GEN
Solar/Wind Harmer
0.863
3144293JTRSVLE
Adder
0.261
3144293JTRSVLE
Adder
0.219
962561AG1-105 GEN
Solar/Wind Harmer
5.146
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.007
964791AG1-342 GEN
Solar/Wind Harmer
1.819
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
8.645
971741AH1-377 GEN
Solar/Wind Harmer
7.526
3151591KERR 2
50/50
0.441
316131AB2-060 GEN
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
9.376
315785AD2-033 C
Solar/Wind Harmer
2.523
970257AG2-171 GEN
Solar/Wind Harmer
4.052
959311AF2-222 GEN
Solar/Wind Harmer
11.03
963181AG1-167 GEN
Solar/Wind Harmer
0.863
3144293JTRSVLE
Adder
0.261
3147133PAMPLIN
Solar/Wind Harmer
-0.027
971193AH1-056 GEN
Solar/Wind Harmer
5.41
942461AE2-259 GEN
Solar/Wind Harmer
1.069
3147043LAWRENC
Solar/Wind Harmer
-0.004
316478AD1-087 GEN
Solar/Wind Harmer
0.573
316486AD2-202 GEN
Solar/Wind Harmer
0.168
3151611KERR 4
50/50
0.441
3151621KERR 5
50/50
0.441
3151631KERR 6
50/50
0.441
3151641KERR 7
50/50
0.441
970831AG2-522 GEN
Solar/Wind Harmer
8.315
316239AB2-077_GEN
Solar/Wind Harmer
0.392
316238AB2-078_GEN
Solar/Wind Harmer
0.392
971443AH1-215 GEN
Solar/Wind Harmer
2.141
3144303KENBRDG
Solar/Wind Harmer
-0.009
970683AG2-441 GEN
Solar/Wind Harmer
7.795
970681AG2-440 GEN
Solar/Wind Harmer
6.236
946301AF1-294 GEN
Solar/Wind Harmer
2.358
961791AG1-021 GEN
Solar/Wind Harmer
1.15
315657AE1-056 GEN
Solar/Wind Harmer
3.246
316118AC1-105 GEN
Solar/Wind Harmer
0.482
VTFLTFEXP_VFT->PJM
CMTX
0.415
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.437
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.297
G-007ALTFEXP_G-007A->PJM
CMTX
0.157
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.159
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.228
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.718
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.84

Details for 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.88 %
Rating:199.0 MVA
Rating Type:B
MVA to Mitigate:212.68
MW Contribution:2.95
Bus #Bus NameTypeMW Contribution
3151601KERR 3
50/50
0.441
3151581KERR 1
50/50
0.157
971065AG2-659 GEN
Solar/Wind Harmer
9.388
316129AC1-054 GEN
Solar/Wind Harmer
1.555
316237AB2-079_GEN
Solar/Wind Harmer
0.392
970685AG2-442 GEN
Solar/Wind Harmer
8.731
963171AG1-166 GEN
Solar/Wind Harmer
1.15
971563AH1-280 GEN
Solar/Wind Harmer
1.15
3144293JTRSVLE
Adder
0.261
970401AG2-262 GEN
Solar/Wind Harmer
0.556
315693AD1-088 GEN
Solar/Wind Harmer
3.668
962491AG1-098 GEN
Solar/Wind Harmer
4.867
3147043LAWRENC
Adder
0.571
957481AF2-042 GEN
Solar/Wind Harmer
21.613
970535AG2-341 GEN
50/50
2.952
939181AE1-148 GEN
Solar/Wind Harmer
12.325
313527AB2-043 GEN
Solar/Wind Harmer
2.056
970323AG2-213 GEN
Solar/Wind Harmer
5.403
971775AH1-396 GEN
Solar/Wind Harmer
0.769
316034AC1-036 C
Solar/Wind Harmer
0.2
958211AF2-115 GEN
Solar/Wind Harmer
1.438
963191AG1-168 GEN
Solar/Wind Harmer
0.863
3144293JTRSVLE
Adder
0.261
3144293JTRSVLE
Adder
0.219
962561AG1-105 GEN
Solar/Wind Harmer
5.146
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.007
964791AG1-342 GEN
Solar/Wind Harmer
1.819
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
8.645
971741AH1-377 GEN
Solar/Wind Harmer
7.526
3151591KERR 2
50/50
0.441
316131AB2-060 GEN
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
9.376
315785AD2-033 C
Solar/Wind Harmer
2.523
970257AG2-171 GEN
Solar/Wind Harmer
4.052
959311AF2-222 GEN
Solar/Wind Harmer
11.03
963181AG1-167 GEN
Solar/Wind Harmer
0.863
3144293JTRSVLE
Adder
0.261
3147133PAMPLIN
Solar/Wind Harmer
-0.027
971193AH1-056 GEN
Solar/Wind Harmer
5.41
942461AE2-259 GEN
Solar/Wind Harmer
1.069
3147043LAWRENC
Solar/Wind Harmer
-0.004
316478AD1-087 GEN
Solar/Wind Harmer
0.573
316486AD2-202 GEN
Solar/Wind Harmer
0.168
3151611KERR 4
50/50
0.441
3151621KERR 5
50/50
0.441
3151631KERR 6
50/50
0.441
3151641KERR 7
50/50
0.441
970831AG2-522 GEN
Solar/Wind Harmer
8.315
316239AB2-077_GEN
Solar/Wind Harmer
0.392
316238AB2-078_GEN
Solar/Wind Harmer
0.392
971443AH1-215 GEN
Solar/Wind Harmer
2.141
3144303KENBRDG
Solar/Wind Harmer
-0.009
970683AG2-441 GEN
Solar/Wind Harmer
7.795
970681AG2-440 GEN
Solar/Wind Harmer
6.236
946301AF1-294 GEN
Solar/Wind Harmer
2.358
961791AG1-021 GEN
Solar/Wind Harmer
1.15
315657AE1-056 GEN
Solar/Wind Harmer
3.246
316118AC1-105 GEN
Solar/Wind Harmer
0.482
VTFLTFEXP_VFT->PJM
CMTX
0.415
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.437
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.297
G-007ALTFEXP_G-007A->PJM
CMTX
0.157
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.159
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.228
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.718
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.84

Details for 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: SEDGE H T452_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-6: SEDGE H T452_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.8 %
Rating:264.1 MVA
Rating Type:C
MVA to Mitigate:345.45
MW Contribution:2.37
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
0.455
316003AC1-222 GEN
Solar/Wind Harmer
6.335
970401AG2-262 GEN
Solar/Wind Harmer
3.216
316237AB2-079_GEN
Solar/Wind Harmer
0.648
3147123OTTER R
Solar/Wind Harmer
-0.013
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
941801AE2-185 GEN
Solar/Wind Harmer
6.153
970685AG2-442 GEN
Solar/Wind Harmer
11.731
963171AG1-166 GEN
Solar/Wind Harmer
1.421
971563AH1-280 GEN
Solar/Wind Harmer
1.421
3144293JTRSVLE
Adder
0.322
3147043LAWRENC
Adder
0.723
971065AG2-659 GEN
Solar/Wind Harmer
3.959
316129AC1-054 GEN
Solar/Wind Harmer
0.656
971795AH1-408 GEN
Solar/Wind Harmer
5.546
315687AD1-152 GEN
Solar/Wind Helper
0.95
3147173SINAI
Solar/Wind Harmer
-0.07
3147243WELCO
Solar/Wind Harmer
-0.043
316118AC1-105 GEN
Solar/Wind Harmer
4.113
970865AG2-541 GEN
Solar/Wind Harmer
22.679
316123AC1-075 GEN
Solar/Wind Harmer
5.01
970165AG2-112 GEN
Solar/Wind Harmer
4.412
970163AG2-111 GEN
Solar/Wind Harmer
4.208
316239AB2-077_GEN
Solar/Wind Harmer
0.648
316238AB2-078_GEN
Solar/Wind Harmer
0.648
971443AH1-215 GEN
Solar/Wind Harmer
3.105
3144303KENBRDG
Solar/Wind Harmer
-0.012
970683AG2-441 GEN
Solar/Wind Harmer
10.474
970681AG2-440 GEN
Solar/Wind Harmer
8.379
946301AF1-294 GEN
Solar/Wind Harmer
2.912
961791AG1-021 GEN
Solar/Wind Harmer
1.421
315657AE1-056 GEN
Solar/Wind Harmer
3.721
970831AG2-522 GEN
Solar/Wind Harmer
3.505
3152661PLYWOOD A
50/50
1.189
970535AG2-341 GEN
50/50
2.368
3146843MT LREL
Solar/Wind Harmer
-0.049
3146843MT LREL
Solar/Wind Harmer
-0.049
964791AG1-342 GEN
Solar/Wind Harmer
10.524
962561AG1-105 GEN
Solar/Wind Harmer
25.243
942751AE2-291 GEN
Solar/Wind Harmer
25.811
313527AB2-043 GEN
Solar/Wind Harmer
3.325
316217AC1-145 GEN
Solar/Wind Harmer
2.663
316197AC1-042 GEN
Solar/Wind Harmer
2.019
942671AE2-283 GEN
Solar/Wind Harmer
5.435
970323AG2-213 GEN
Solar/Wind Harmer
7.8
971775AH1-396 GEN
Solar/Wind Harmer
1.111
316034AC1-036 C
Solar/Wind Harmer
0.288
939181AE1-148 GEN
Solar/Wind Harmer
6.731
958211AF2-115 GEN
Solar/Wind Harmer
1.776
963191AG1-168 GEN
Solar/Wind Harmer
1.065
3144293JTRSVLE
Adder
0.322
3144293JTRSVLE
Adder
0.271
3147133PAMPLIN
Solar/Wind Harmer
-0.01
3147133PAMPLIN
Solar/Wind Harmer
-0.008
316222AC1-221 GEN
Solar/Wind Helper
0.679
316248AF1-058 C
Solar/Wind Harmer
2.11
960061AF2-297 GEN
Solar/Wind Harmer
35.005
971683AH1-343 GEN
Solar/Wind Harmer
26.063
316131AB2-060 GEN
Solar/Wind Harmer
2.174
964241AG1-285 GEN
Solar/Wind Harmer
14.639
315785AD2-033 C
Solar/Wind Harmer
3.731
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
6.153
970257AG2-171 GEN
Solar/Wind Harmer
5.85
959311AF2-222 GEN
Solar/Wind Harmer
15.614
963181AG1-167 GEN
Solar/Wind Harmer
1.065
3144293JTRSVLE
Adder
0.322
3147133PAMPLIN
Solar/Wind Harmer
-0.031
971193AH1-056 GEN
Solar/Wind Harmer
6.202
3147043LAWRENC
Solar/Wind Harmer
-0.005
316283AC2-100 C
Solar/Wind Helper
0.615
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.384
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.384
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.016
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.06
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.061
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.822

Details for 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-5: SEDGE H L202_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-5: SEDGE H L202_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.8 %
Rating:264.1 MVA
Rating Type:C
MVA to Mitigate:345.45
MW Contribution:2.37
Bus #Bus NameTypeMW Contribution
3147173SINAI
Solar/Wind Harmer
-0.07
3147243WELCO
Solar/Wind Harmer
-0.043
316118AC1-105 GEN
Solar/Wind Harmer
4.113
970865AG2-541 GEN
Solar/Wind Harmer
22.679
316123AC1-075 GEN
Solar/Wind Harmer
5.01
970165AG2-112 GEN
Solar/Wind Harmer
4.412
970163AG2-111 GEN
Solar/Wind Harmer
4.208
316239AB2-077_GEN
Solar/Wind Harmer
0.648
316238AB2-078_GEN
Solar/Wind Harmer
0.648
971443AH1-215 GEN
Solar/Wind Harmer
3.105
3144303KENBRDG
Solar/Wind Harmer
-0.012
970683AG2-441 GEN
Solar/Wind Harmer
10.474
970681AG2-440 GEN
Solar/Wind Harmer
8.379
946301AF1-294 GEN
Solar/Wind Harmer
2.912
961791AG1-021 GEN
Solar/Wind Harmer
1.421
316248AF1-058 C
Solar/Wind Harmer
2.11
960061AF2-297 GEN
Solar/Wind Harmer
35.005
971683AH1-343 GEN
Solar/Wind Harmer
26.063
316131AB2-060 GEN
Solar/Wind Harmer
2.174
964241AG1-285 GEN
Solar/Wind Harmer
14.639
315785AD2-033 C
Solar/Wind Harmer
3.731
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
6.153
970257AG2-171 GEN
Solar/Wind Harmer
5.85
959311AF2-222 GEN
Solar/Wind Harmer
15.614
963181AG1-167 GEN
Solar/Wind Harmer
1.065
3144293JTRSVLE
Adder
0.322
3147133PAMPLIN
Solar/Wind Harmer
-0.031
971193AH1-056 GEN
Solar/Wind Harmer
6.202
3147043LAWRENC
Solar/Wind Harmer
-0.005
316283AC2-100 C
Solar/Wind Helper
0.615
3152661PLYWOOD A
50/50
1.189
970535AG2-341 GEN
50/50
2.368
3146843MT LREL
Solar/Wind Harmer
-0.049
3146843MT LREL
Solar/Wind Harmer
-0.049
964791AG1-342 GEN
Solar/Wind Harmer
10.524
962561AG1-105 GEN
Solar/Wind Harmer
25.243
942751AE2-291 GEN
Solar/Wind Harmer
25.811
313527AB2-043 GEN
Solar/Wind Harmer
3.325
316217AC1-145 GEN
Solar/Wind Harmer
2.663
316197AC1-042 GEN
Solar/Wind Harmer
2.019
942671AE2-283 GEN
Solar/Wind Harmer
5.435
970323AG2-213 GEN
Solar/Wind Harmer
7.8
971775AH1-396 GEN
Solar/Wind Harmer
1.111
316034AC1-036 C
Solar/Wind Harmer
0.288
939181AE1-148 GEN
Solar/Wind Harmer
6.731
958211AF2-115 GEN
Solar/Wind Harmer
1.776
963191AG1-168 GEN
Solar/Wind Harmer
1.065
3144293JTRSVLE
Adder
0.322
3144293JTRSVLE
Adder
0.271
3147133PAMPLIN
Solar/Wind Harmer
-0.01
3147133PAMPLIN
Solar/Wind Harmer
-0.008
316222AC1-221 GEN
Solar/Wind Helper
0.679
3151561HALLBR1
50/50
0.455
316003AC1-222 GEN
Solar/Wind Harmer
6.335
970401AG2-262 GEN
Solar/Wind Harmer
3.216
316237AB2-079_GEN
Solar/Wind Harmer
0.648
3147123OTTER R
Solar/Wind Harmer
-0.013
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
941801AE2-185 GEN
Solar/Wind Harmer
6.153
970685AG2-442 GEN
Solar/Wind Harmer
11.731
963171AG1-166 GEN
Solar/Wind Harmer
1.421
971563AH1-280 GEN
Solar/Wind Harmer
1.421
3144293JTRSVLE
Adder
0.322
3147043LAWRENC
Adder
0.723
971065AG2-659 GEN
Solar/Wind Harmer
3.959
316129AC1-054 GEN
Solar/Wind Harmer
0.656
971795AH1-408 GEN
Solar/Wind Harmer
5.546
315687AD1-152 GEN
Solar/Wind Helper
0.95
315657AE1-056 GEN
Solar/Wind Harmer
3.721
970831AG2-522 GEN
Solar/Wind Harmer
3.505
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.384
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.384
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.016
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.06
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.061
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.822

Details for 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-3: 6SEDGE HILL-TX#2_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.36 %
Rating:242.52 MVA
Rating Type:B
MVA to Mitigate:245.83
MW Contribution:2.37
Bus #Bus NameTypeMW Contribution
3151561HALLBR1
50/50
0.455
3144293JTRSVLE
50/50
0.342
24728405LEESVG
50/50
0.119
3151601KERR 3
50/50
0.186
3151581KERR 1
50/50
0.066
3147043LAWRENC
50/50
0.767
316003AC1-222 GEN
Solar/Wind Harmer
0.015
970401AG2-262 GEN
Solar/Wind Harmer
2.573
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3147123OTTER R
Solar/Wind Harmer
0.113
3147312GRETNA
Solar/Wind Harmer
0.117
3146802CHATHAM
Solar/Wind Harmer
0.109
941801AE2-185 GEN
Solar/Wind Harmer
4.673
970685AG2-442 GEN
Solar/Wind Harmer
8.91
963171AG1-166 GEN
Solar/Wind Harmer
0.539
971563AH1-280 GEN
Solar/Wind Harmer
1.079
971065AG2-659 GEN
Solar/Wind Harmer
3.007
316129AC1-054 GEN
Solar/Wind Harmer
0.25
971795AH1-408 GEN
Solar/Wind Harmer
4.388
315687AD1-152 GEN
Solar/Wind Helper
0.95
3151611KERR 4
50/50
0.186
3151621KERR 5
50/50
0.186
3151631KERR 6
50/50
0.186
3151641KERR 7
50/50
0.186
3147173SINAI
Solar/Wind Harmer
0.623
3147243WELCO
Solar/Wind Harmer
0.389
316118AC1-105 GEN
Solar/Wind Harmer
1.374
970865AG2-541 GEN
Solar/Wind Harmer
17.225
316123AC1-075 GEN
Solar/Wind Harmer
0.565
970165AG2-112 GEN
Solar/Wind Harmer
3.351
970163AG2-111 GEN
Solar/Wind Harmer
3.196
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
2.358
3144303KENBRDG
Solar/Wind Harmer
0.111
970683AG2-441 GEN
Solar/Wind Harmer
7.955
970681AG2-440 GEN
Solar/Wind Harmer
6.364
946301AF1-294 GEN
Solar/Wind Harmer
1.996
961791AG1-021 GEN
Solar/Wind Harmer
0.971
315657AE1-056 GEN
Solar/Wind Harmer
3.046
970831AG2-522 GEN
Solar/Wind Harmer
2.662
3152661PLYWOOD A
50/50
1.189
970535AG2-341 GEN
50/50
2.368
3144293JTRSVLE
50/50
0.342
3144293JTRSVLE
50/50
0.288
3146843MT LREL
Solar/Wind Harmer
0.44
3146843MT LREL
Solar/Wind Harmer
0.44
964791AG1-342 GEN
Solar/Wind Harmer
8.419
962561AG1-105 GEN
Solar/Wind Harmer
19.172
942751AE2-291 GEN
Solar/Wind Harmer
19.603
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
3.635
970323AG2-213 GEN
Solar/Wind Harmer
5.924
971775AH1-396 GEN
Solar/Wind Harmer
0.222
316034AC1-036 C
Solar/Wind Harmer
0.01
939181AE1-148 GEN
Solar/Wind Harmer
5.112
958211AF2-115 GEN
Solar/Wind Harmer
1.214
963191AG1-168 GEN
Solar/Wind Harmer
0.405
3147133PAMPLIN
Solar/Wind Harmer
0.088
3147133PAMPLIN
Solar/Wind Harmer
0.071
316222AC1-221 GEN
Solar/Wind Helper
0.679
3144293JTRSVLE
50/50
0.342
24728405LEESVG
50/50
0.119
3151591KERR 2
50/50
0.186
316248AF1-058 C
Solar/Wind Harmer
0.005
960061AF2-297 GEN
Solar/Wind Harmer
26.586
971683AH1-343 GEN
Solar/Wind Harmer
19.795
316131AB2-060 GEN
Solar/Wind Harmer
0.564
964241AG1-285 GEN
Solar/Wind Harmer
11.118
315785AD2-033 C
Solar/Wind Harmer
1.191
3147312GRETNA
Solar/Wind Harmer
0.029
941821AE2-187 GEN
Solar/Wind Harmer
4.673
970257AG2-171 GEN
Solar/Wind Harmer
4.443
959311AF2-222 GEN
Solar/Wind Harmer
11.835
963181AG1-167 GEN
Solar/Wind Harmer
0.405
3147133PAMPLIN
Solar/Wind Harmer
0.277
971193AH1-056 GEN
Solar/Wind Harmer
5.378
3147043LAWRENC
Solar/Wind Harmer
0.048
316283AC2-100 C
Solar/Wind Helper
0.615
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.384
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.384
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.016
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.06
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.061
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.822

Details for 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-2: 3202_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.16 %
Rating:276.6 MVA
Rating Type:C
MVA to Mitigate:362.79
MW Contribution:2.36
Bus #Bus NameTypeMW Contribution
316118AC1-105 GEN
Solar/Wind Harmer
4.1
970865AG2-541 GEN
Solar/Wind Harmer
22.609
316123AC1-075 GEN
Solar/Wind Harmer
4.995
970165AG2-112 GEN
Solar/Wind Harmer
4.398
970163AG2-111 GEN
Solar/Wind Harmer
4.196
316239AB2-077_GEN
Solar/Wind Harmer
0.646
316238AB2-078_GEN
Solar/Wind Harmer
0.646
971443AH1-215 GEN
Solar/Wind Harmer
3.097
3144303KENBRDG
Solar/Wind Harmer
-0.012
970683AG2-441 GEN
Solar/Wind Harmer
10.446
970681AG2-440 GEN
Solar/Wind Harmer
8.357
946301AF1-294 GEN
Solar/Wind Harmer
2.905
961791AG1-021 GEN
Solar/Wind Harmer
1.417
315657AE1-056 GEN
Solar/Wind Harmer
3.712
970831AG2-522 GEN
Solar/Wind Harmer
3.497
960061AF2-297 GEN
Solar/Wind Harmer
34.896
971683AH1-343 GEN
Solar/Wind Harmer
25.983
316131AB2-060 GEN
Solar/Wind Harmer
2.168
964241AG1-285 GEN
Solar/Wind Harmer
14.598
315785AD2-033 C
Solar/Wind Harmer
3.721
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
6.136
970257AG2-171 GEN
Solar/Wind Harmer
5.834
959311AF2-222 GEN
Solar/Wind Harmer
15.571
963181AG1-167 GEN
Solar/Wind Harmer
1.063
3144293JTRSVLE
Adder
0.321
3147133PAMPLIN
Solar/Wind Harmer
-0.031
971193AH1-056 GEN
Solar/Wind Harmer
6.187
3147043LAWRENC
Solar/Wind Harmer
-0.005
316283AC2-100 C
Solar/Wind Helper
0.612
3152661PLYWOOD A
50/50
1.185
970535AG2-341 GEN
50/50
2.362
3146843MT LREL
Solar/Wind Harmer
-0.049
3146843MT LREL
Solar/Wind Harmer
-0.049
964791AG1-342 GEN
Solar/Wind Harmer
10.492
962561AG1-105 GEN
Solar/Wind Harmer
25.166
942751AE2-291 GEN
Solar/Wind Harmer
25.733
313527AB2-043 GEN
Solar/Wind Harmer
3.316
316217AC1-145 GEN
Solar/Wind Harmer
2.656
316197AC1-042 GEN
Solar/Wind Harmer
2.013
942671AE2-283 GEN
Solar/Wind Harmer
5.42
970323AG2-213 GEN
Solar/Wind Harmer
7.779
971775AH1-396 GEN
Solar/Wind Harmer
1.108
316034AC1-036 C
Solar/Wind Harmer
0.288
939181AE1-148 GEN
Solar/Wind Harmer
6.713
958211AF2-115 GEN
Solar/Wind Harmer
1.771
963191AG1-168 GEN
Solar/Wind Harmer
1.063
3144293JTRSVLE
Adder
0.321
3144293JTRSVLE
Adder
0.27
3147133PAMPLIN
Solar/Wind Harmer
-0.01
3147133PAMPLIN
Solar/Wind Harmer
-0.008
316222AC1-221 GEN
Solar/Wind Helper
0.676
3151561HALLBR1
50/50
0.454
316003AC1-222 GEN
Solar/Wind Harmer
6.315
970401AG2-262 GEN
Solar/Wind Harmer
3.206
316237AB2-079_GEN
Solar/Wind Harmer
0.646
3147123OTTER R
Solar/Wind Harmer
-0.012
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
941801AE2-185 GEN
Solar/Wind Harmer
6.136
970685AG2-442 GEN
Solar/Wind Harmer
11.7
963171AG1-166 GEN
Solar/Wind Harmer
1.417
971563AH1-280 GEN
Solar/Wind Harmer
1.417
3144293JTRSVLE
Adder
0.321
3147043LAWRENC
Adder
0.721
971065AG2-659 GEN
Solar/Wind Harmer
3.95
316129AC1-054 GEN
Solar/Wind Harmer
0.654
971795AH1-408 GEN
Solar/Wind Harmer
5.534
315687AD1-152 GEN
Solar/Wind Helper
0.946
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.381
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.367
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.013
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.049
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.057
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.816

Details for 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-5: SEDGE H L102_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-5: SEDGE H L102_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.48 %
Rating:276.6 MVA
Rating Type:C
MVA to Mitigate:344.32
MW Contribution:2.36
Bus #Bus NameTypeMW Contribution
3147173SINAI
Solar/Wind Harmer
-0.07
3147243WELCO
Solar/Wind Harmer
-0.043
316118AC1-105 GEN
Solar/Wind Harmer
4.099
970865AG2-541 GEN
Solar/Wind Harmer
22.606
316123AC1-075 GEN
Solar/Wind Harmer
4.994
970165AG2-112 GEN
Solar/Wind Harmer
4.397
970163AG2-111 GEN
Solar/Wind Harmer
4.195
316239AB2-077_GEN
Solar/Wind Harmer
0.646
316238AB2-078_GEN
Solar/Wind Harmer
0.646
971443AH1-215 GEN
Solar/Wind Harmer
3.095
3144303KENBRDG
Solar/Wind Harmer
-0.012
970683AG2-441 GEN
Solar/Wind Harmer
10.44
970681AG2-440 GEN
Solar/Wind Harmer
8.352
946301AF1-294 GEN
Solar/Wind Harmer
2.903
961791AG1-021 GEN
Solar/Wind Harmer
1.416
315657AE1-056 GEN
Solar/Wind Harmer
3.709
970831AG2-522 GEN
Solar/Wind Harmer
3.493
3151561HALLBR1
50/50
0.454
316003AC1-222 GEN
Solar/Wind Harmer
6.314
970401AG2-262 GEN
Solar/Wind Harmer
3.205
316237AB2-079_GEN
Solar/Wind Harmer
0.646
3147123OTTER R
Solar/Wind Harmer
-0.012
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
941801AE2-185 GEN
Solar/Wind Harmer
6.133
970685AG2-442 GEN
Solar/Wind Harmer
11.693
963171AG1-166 GEN
Solar/Wind Harmer
1.416
971563AH1-280 GEN
Solar/Wind Harmer
1.416
3144293JTRSVLE
Adder
0.321
3147043LAWRENC
Adder
0.721
971065AG2-659 GEN
Solar/Wind Harmer
3.947
316129AC1-054 GEN
Solar/Wind Harmer
0.654
971795AH1-408 GEN
Solar/Wind Harmer
5.528
315687AD1-152 GEN
Solar/Wind Helper
0.947
3152661PLYWOOD A
50/50
1.185
970535AG2-341 GEN
50/50
2.36
3146843MT LREL
Solar/Wind Harmer
-0.049
3146843MT LREL
Solar/Wind Harmer
-0.049
964791AG1-342 GEN
Solar/Wind Harmer
10.49
962561AG1-105 GEN
Solar/Wind Harmer
25.162
942751AE2-291 GEN
Solar/Wind Harmer
25.728
313527AB2-043 GEN
Solar/Wind Harmer
3.315
316217AC1-145 GEN
Solar/Wind Harmer
2.654
316197AC1-042 GEN
Solar/Wind Harmer
2.012
942671AE2-283 GEN
Solar/Wind Harmer
5.418
970323AG2-213 GEN
Solar/Wind Harmer
7.775
971775AH1-396 GEN
Solar/Wind Harmer
1.107
316034AC1-036 C
Solar/Wind Harmer
0.288
939181AE1-148 GEN
Solar/Wind Harmer
6.709
958211AF2-115 GEN
Solar/Wind Harmer
1.77
963191AG1-168 GEN
Solar/Wind Harmer
1.062
3144293JTRSVLE
Adder
0.321
3144293JTRSVLE
Adder
0.27
3147133PAMPLIN
Solar/Wind Harmer
-0.01
3147133PAMPLIN
Solar/Wind Harmer
-0.008
316222AC1-221 GEN
Solar/Wind Helper
0.676
316248AF1-058 C
Solar/Wind Harmer
2.103
960061AF2-297 GEN
Solar/Wind Harmer
34.892
971683AH1-343 GEN
Solar/Wind Harmer
25.98
316131AB2-060 GEN
Solar/Wind Harmer
2.167
964241AG1-285 GEN
Solar/Wind Harmer
14.592
315785AD2-033 C
Solar/Wind Harmer
3.719
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
6.133
970257AG2-171 GEN
Solar/Wind Harmer
5.831
959311AF2-222 GEN
Solar/Wind Harmer
15.563
963181AG1-167 GEN
Solar/Wind Harmer
1.062
3144293JTRSVLE
Adder
0.321
3147133PAMPLIN
Solar/Wind Harmer
-0.031
971193AH1-056 GEN
Solar/Wind Harmer
6.182
3147043LAWRENC
Solar/Wind Harmer
-0.005
316283AC2-100 C
Solar/Wind Helper
0.613
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.383
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.382
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.016
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.06
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.061
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.819

Details for 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:156.12 %
Rating:186.12 MVA
Rating Type:A
MVA to Mitigate:290.57
MW Contribution:1.16
Bus #Bus NameTypeMW Contribution
970685AG2-442 GEN
Solar/Wind Harmer
37.535
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970535AG2-341 GEN
50/50
1.158
3147133PAMPLIN
Solar/Wind Harmer
0.703
3147133PAMPLIN
Solar/Wind Harmer
0.562
316034AC1-036 C
Solar/Wind Harmer
0.028
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
2.89
942461AE2-259 GEN
Solar/Wind Harmer
-0.005
3147133PAMPLIN
Solar/Wind Harmer
2.207
971193AH1-056 GEN
Solar/Wind Harmer
42.837
959311AF2-222 GEN
Solar/Wind Harmer
36.728
964241AG1-285 GEN
Solar/Wind Harmer
13.022
316131AB2-060 GEN
Solar/Wind Harmer
0.286
315657AE1-056 GEN
Solar/Wind Harmer
24.264
970683AG2-441 GEN
Solar/Wind Harmer
33.514
970681AG2-440 GEN
Solar/Wind Harmer
26.811
971443AH1-215 GEN
Solar/Wind Harmer
6.153
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.238
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.313
MECLTFEXP_MEC->PJM
CLTF
0.061
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CPLELTFEXP_CPLE->PJM
CLTF
0.421
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.886
LAGNLTFEXP_LAGN->PJM
CLTF
0.194
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.821
TVALTFEXP_TVA->PJM
CLTF
0.096
NYPJM->LTFIMP_NY
CLTF
0.064
LGEELTFEXP_LGEE->PJM
CLTF
0.017
WECLTFEXP_WEC->PJM
CLTF
0.008

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:203.13 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1378.6
MW Contribution:2.24
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.18
316303AF2-085
50/50
2.224
3151541CLOVER2
50/50
2.487
3151611KERR 4
50/50
0.234
3151621KERR 5
50/50
0.234
3151631KERR 6
50/50
0.234
3151641KERR 7
50/50
0.234
963041AG1-153 GEN
50/50
2.299
315244AE2-183_ST
50/50
2.451
3151281ROARAP4
50/50
0.1
3151281ROARAP4
50/50
0.094
971285AH1-108 GEN
50/50
0.651
315779AE2-040
50/50
1.092
971845AH1-439 GEN
Solar/Wind Harmer
17.513
970285AG2-188 GEN
Solar/Wind Harmer
29.552
315657AE1-056 GEN
Solar/Wind Harmer
8.144
946301AF1-294 GEN
Solar/Wind Harmer
4.404
961791AG1-021 GEN
Solar/Wind Harmer
2.143
970683AG2-441 GEN
Solar/Wind Harmer
13.644
970681AG2-440 GEN
Solar/Wind Harmer
10.915
3144303KENBRDG
Solar/Wind Harmer
0.148
971443AH1-215 GEN
Solar/Wind Harmer
3.079
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316233AE1-074 FULL
Solar/Wind Harmer
0.084
971281AH1-106 GEN
Solar/Wind Harmer
1.459
3151931BEARGRDN S1
50/50
5.869
3151911BEARGRDN G1
50/50
4.548
3144293JTRSVLE
50/50
0.754
970119AG2-088 GEN
50/50
16.679
3151531CLOVER1
50/50
2.499
3151601KERR 3
50/50
0.234
3151581KERR 1
50/50
0.083
3147043LAWRENC
50/50
1
3151051BRUNSWICKS1
50/50
2.357
3151021BRUNSWICKG1
50/50
1.135
971451AH1-221 GEN
50/50
3.449
315243AE2-183_GT3
50/50
1.418
3151261ROARAP2
50/50
0.103
3150851SPRUNCC
50/50
0.398
3151391GASTONA
50/50
0.204
3151411GASTONB
50/50
0.204
972003AH1-546 GEN
Solar/Wind Harmer
20.039
970937AG2-583 GEN
Solar/Wind Harmer
24.928
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.157
3146926FARMVIL
Solar/Wind Harmer
0.188
316336AC2-165 C
Solar/Wind Harmer
0.012
3143336POWHATN
Solar/Wind Harmer
4.81
963171AG1-166 GEN
Solar/Wind Harmer
1.19
971563AH1-280 GEN
Solar/Wind Harmer
2.381
970685AG2-442 GEN
Solar/Wind Harmer
15.281
962491AG1-098 GEN
Solar/Wind Harmer
8.349
315693AD1-088 GEN
Solar/Wind Harmer
6.776
316237AB2-079_GEN
Solar/Wind Harmer
0.001
971377AH1-170 GEN
Solar/Wind Harmer
1.402
3147623JAMES R
Solar/Wind Harmer
0.305
3143226MDLTHAN
Solar/Wind Harmer
0.125
957481AF2-042 GEN
Solar/Wind Harmer
31.266
970401AG2-262 GEN
Solar/Wind Harmer
0.671
315687AD1-152 GEN
Solar/Wind Harmer
0.003
3143526WINTERP
Solar/Wind Harmer
0.547
971065AG2-659 GEN
Solar/Wind Harmer
4.446
316129AC1-054 GEN
Solar/Wind Harmer
0.385
971795AH1-408 GEN
Solar/Wind Harmer
6.611
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.847
970919AG2-571 GEN
Solar/Wind Harmer
2.953
970087AG2-069 GEN
Solar/Wind Harmer
6.617
3145783HORNRTN
Solar/Wind Harmer
0.082
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
6.459
316023GEN1_S
Solar/Wind Harmer
0.176
939411AE1-173 GEN
Solar/Wind Harmer
33.156
3146263WOODLND
Solar/Wind Harmer
0.076
316011AB1-132 GEN
Solar/Wind Harmer
1.373
962571AG1-106 GEN
Solar/Wind Harmer
1.074
3145893MURPHYS
Solar/Wind Harmer
0.301
3145893MURPHYS
Solar/Wind Harmer
0.334
3145796HORNRTN
Solar/Wind Harmer
0.245
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316212AC1-099_GEN
Solar/Wind Harmer
0.382
3145823KELFORD
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
315722AD1-056 GEN
Solar/Wind Harmer
0.447
970659AG2-427 GEN
Solar/Wind Harmer
3.416
316381AD1-082 GEN
Solar/Wind Harmer
0.074
970661AG2-428 GEN
Solar/Wind Harmer
7.004
3146206CASHIE
Solar/Wind Harmer
0.07
971547AH1-271 GEN
Solar/Wind Harmer
1.497
3142543TWELFTH
Solar/Wind Harmer
0.007
3146233WITAKRS
Solar/Wind Harmer
0.278
316093AE2-104_GEN
Solar/Wind Harmer
1.171
3145663CRESWEL
Solar/Wind Harmer
0.194
971163AH1-040 GEN
Solar/Wind Harmer
5.558
3130156CHOWAN
Solar/Wind Harmer
0.069
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.223
3146516WINFALL
Solar/Wind Harmer
0.069
315671AE2-027_GEN
Solar/Wind Harmer
4.41
316246AF1-032 C
Solar/Wind Harmer
0.031
3146456SLIGO L269
Solar/Wind Harmer
0.069
316388AE2-253 GEN
Solar/Wind Harmer
0.215
944591AF1-124 GEN
Solar/Wind Harmer
15.512
3145963POPLR C
Solar/Wind Harmer
0.069
316174AB2-169 GEN
Solar/Wind Harmer
0.002
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.853
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.054
316359AB2-059 GEN
Solar/Wind Harmer
0.244
316049AB1-081 GEN
Solar/Wind Harmer
0.389
3142053HEARTS
Solar/Wind Harmer
0.12
316072AD1-144
Solar/Wind Harmer
0.025
3146293MARTNCO
Solar/Wind Harmer
0.063
316294AC1-161 GEN
Solar/Wind Harmer
1.171
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.067
3145493TOT1
Solar/Wind Harmer
0.3
316494AC1-189 GEN
Solar/Wind Harmer
0.227
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.267
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
961611AG1-000B GEN
Solar/Wind Harmer
3.457
971647AH1-324 GEN
Solar/Wind Harmer
2.81
971069AG2-661 GEN
Solar/Wind Harmer
1.169
316458AB2-190 GEN2
Solar/Wind Harmer
0.353
970129AG2-093 GEN
Solar/Wind Harmer
1.869
944631AF1-128 GEN
Adder
29.45
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971317AH1-138 GEN
Solar/Wind Harmer
0.439
3151921BEARGRDN G2
50/50
4.548
3144293JTRSVLE
50/50
0.754
970413AG2-270 GEN
50/50
10.906
3151591KERR 2
50/50
0.234
3151031BRUNSWICKG2
50/50
1.135
3151261ROARAP2
50/50
0.101
3150861SPRUNCD
50/50
0.398
3151391GASTONA
50/50
0.204
3151411GASTONB
50/50
0.204
971283AH1-107 GEN
Solar/Wind Harmer
1.459
316118AC1-105 GEN
Solar/Wind Harmer
0.27
270494AE1-108_GEN
Solar/Wind Harmer
1.236
970831AG2-522 GEN
Solar/Wind Harmer
4.291
3147173SINAI
Solar/Wind Harmer
0.095
3147243WELCO
Solar/Wind Harmer
0.059
971967AH1-528 GEN
Solar/Wind Harmer
14.709
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
18.242
970673AG2-436 GEN
Solar/Wind Harmer
12.162
941031AE2-094 GEN
Solar/Wind Harmer
15.639
944011AF1-069 GEN
Solar/Wind Harmer
5.11
3137643SOCKMAN
Solar/Wind Harmer
0.336
970085AG2-068 GEN
Solar/Wind Harmer
4.411
970581AG2-369 GEN
Solar/Wind Harmer
3.794
315607AA1-063A GEN
Solar/Wind Harmer
0.164
3146043SEABORD
Solar/Wind Harmer
0.08
315814AE2-033 C
Solar/Wind Harmer
6.192
316315AB2-025 C
Solar/Wind Harmer
0.063
970865AG2-541 GEN
Solar/Wind Harmer
2.68
965291AG1-394 GEN
Solar/Wind Harmer
0.339
315652AC1-086 GEN
Solar/Wind Harmer
8.307
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
3145796HORNRTN
Solar/Wind Harmer
0.238
3145796HORNRTN
Solar/Wind Harmer
0.03
3143316POE
Solar/Wind Harmer
0.292
3146033SCOT NK
Solar/Wind Harmer
0.294
3145513AHOSKIE
Solar/Wind Harmer
0.153
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.146
3145683EARLEYS
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
3146206CASHIE
Solar/Wind Harmer
0.07
970601AG2-382 GEN
Solar/Wind Harmer
2.62
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.048
316311AC2-079 GEN
Solar/Wind Harmer
2.01
316319Z2-044 C
Solar/Wind Harmer
0
315732AD1-074 GEN1
Solar/Wind Harmer
0.4
315733AD1-074 GEN2
Solar/Wind Harmer
0.4
315735AD1-075 GEN1
Solar/Wind Harmer
0.2
3130546PLYMOUTH
Solar/Wind Harmer
0.07
315835AF2-110_GEN
Solar/Wind Harmer
0.478
315816AE2-034 GEN
Solar/Wind Harmer
0.298
3130156CHOWAN
Solar/Wind Harmer
0.069
3130156CHOWAN
Solar/Wind Harmer
0.069
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3146486SUNBURY
Solar/Wind Harmer
0.069
3146486SUNBURY
Solar/Wind Harmer
0.069
316321Z2-027
Solar/Wind Harmer
0.013
3145176PASQUOTANK
Solar/Wind Harmer
0.043
3146396TANGLEW
Solar/Wind Harmer
0.19
316305AF2-043 C
Solar/Wind Harmer
0.001
313526AB2-022
Solar/Wind Harmer
0.037
3146406KITTY HAWK
Solar/Wind Harmer
0.009
319010AE1-072 C
Solar/Wind Harmer
0.346
957871AF2-081 GEN
Solar/Wind Harmer
3.419
3151081ELIZAR1
Adder
6.268
3151091ELIZAR2
Adder
6.16
3152611GOSPORTB
Adder
0.871
3152621GOSPORTC
Adder
0.739
3152601GOSPORTA
Adder
0.682
3145573BETHELC
Solar/Wind Harmer
0.067
3145573BETHELC
Solar/Wind Harmer
0.067
316420AA1-050 GEN
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
2.903
316005AA1-067
Solar/Wind Harmer
0.072
3145746EVERETS
Solar/Wind Harmer
0.267
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
970181AG2-120 GEN
Solar/Wind Harmer
0.836
971445AH1-216 GEN
Solar/Wind Harmer
4.703
972265AH1-717 GEN
Adder
5.124
3151201GRAVEL4
Adder
4.803
3151191GRAVEL3
Adder
4.742
3151211GRAVEL5
Adder
4.742
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.353
316123AC1-075 GEN
Solar/Wind Harmer
0.09
970165AG2-112 GEN
Solar/Wind Harmer
0.531
970163AG2-111 GEN
Solar/Wind Harmer
0.506
971447AH1-217 GEN
Solar/Wind Harmer
1.848
971167AH1-042 GEN
Solar/Wind Harmer
5.088
3138283WHITEMARSH
Solar/Wind Harmer
0.013
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.105
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.12
3144293JTRSVLE
50/50
0.754
3144293JTRSVLE
50/50
0.635
970535AG2-341 GEN
50/50
2.24
3152661PLYWOOD A
50/50
0.227
3151041BRUNSWICKG3
50/50
1.135
972187AH1-678 GEN
50/50
2.606
315242AE2-183_GT2
50/50
1.418
315241AE2-183_GT1
50/50
1.409
972185AH1-677 GEN
50/50
5.111
970533AG2-339 GEN
50/50
7.548
970531AG2-338 GEN
50/50
3.019
3146776BUCKING
Solar/Wind Harmer
1.571
3146776BUCKING
Solar/Wind Harmer
0.127
970301AG2-198 GEN
Solar/Wind Harmer
10.262
3147133PAMPLIN
Solar/Wind Harmer
0.236
3147133PAMPLIN
Solar/Wind Harmer
0.189
958211AF2-115 GEN
Solar/Wind Harmer
2.678
963191AG1-168 GEN
Solar/Wind Harmer
0.893
971741AH1-377 GEN
Solar/Wind Harmer
21.598
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
7.892
971775AH1-396 GEN
Solar/Wind Harmer
0.296
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971489AH1-241 GEN
Solar/Wind Harmer
7.009
971223AH1-071 GEN
Solar/Wind Harmer
1.334
962561AG1-105 GEN
Solar/Wind Harmer
5.681
939181AE1-148 GEN
Solar/Wind Harmer
5.661
970099AG2-077 GEN
Solar/Wind Harmer
12.506
964791AG1-342 GEN
Solar/Wind Harmer
2.195
3146843MT LREL
Solar/Wind Harmer
0.114
3146843MT LREL
Solar/Wind Harmer
0.114
3143526WINTERP
Solar/Wind Harmer
0.547
970933AG2-581 GEN
Solar/Wind Harmer
7.995
316181AB2-040 GEN
Solar/Wind Harmer
0.124
3145593CAROLNA
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.083
966811AG1-552 GEN
Solar/Wind Harmer
0.899
3145593CAROLNA
Solar/Wind Harmer
0.103
3145783HORNRTN
Solar/Wind Harmer
1.451
3145783HORNRTN
Solar/Wind Harmer
1.161
3145783HORNRTN
Solar/Wind Harmer
0.363
3145783HORNRTN
Solar/Wind Harmer
0.145
316426AA2-053 GEN
Solar/Wind Harmer
0.274
3144356SAPONY
Solar/Wind Harmer
0.654
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
0.503
3145893MURPHYS
Solar/Wind Harmer
0.135
316274AC1-208 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
0.223
3146173TUNIS
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
315742AE1-103 GEN
Solar/Wind Harmer
0.001
970657AG2-426 GEN
Solar/Wind Harmer
2.47
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.223
3146376EDENTON
Solar/Wind Harmer
0.308
3146376EDENTON
Solar/Wind Harmer
0.308
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146386ELIZ CT
Solar/Wind Harmer
0.069
316240AF1-291 C
Solar/Wind Harmer
0.001
3130086AYDLETT
Solar/Wind Harmer
0.275
3137176SLIGO L2192
Solar/Wind Harmer
0.273
3146456SLIGO L269
Solar/Wind Harmer
1.215
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.038
316339AD2-160 GEN
Solar/Wind Harmer
0.111
3145506HICKORY
Solar/Wind Harmer
0.274
3145506HICKORY
Solar/Wind Harmer
0.165
3145506HICKORY
Solar/Wind Harmer
0.041
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.066
316036AC1-147 C
Solar/Wind Harmer
0.013
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.505
316222AC1-221 GEN
Solar/Wind Harmer
0.283
316263AC1-034 GEN
Solar/Wind Harmer
2.586
3145933PARMELE
Solar/Wind Harmer
0.135
3145933PARMELE
Solar/Wind Harmer
0.068
961601AG1-000A GEN
Solar/Wind Harmer
1.202
3145493TOT1
Solar/Wind Harmer
0.156
3145453TOT5
Solar/Wind Harmer
0.094
3145603CNETO
Solar/Wind Harmer
0.063
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.074
3142366NRTHEST
Adder
0.195
3142946ENON
Solar/Wind Harmer
0.006
3150691DARBY 3
Adder
4.195
3150701DARBY 4
Adder
4.185
3150681DARBY 2
Adder
4.18
3150671DARBY 1
Adder
4.175
942751AE2-291 GEN
Solar/Wind Harmer
3.155
966001AG1-469 GEN
Solar/Wind Helper
0.19
316159AE1-175 C
Solar/Wind Harmer
0.05
3142433PROV 92
Solar/Wind Harmer
0.226
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.056
316192AB2-158 GEN
Solar/Wind Helper
0.823
3147666LOUISA
Solar/Wind Helper
0.475
3146776BUCKING
Solar/Wind Harmer
0.141
3146926FARMVIL
Solar/Wind Harmer
0.188
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
316313AB2-026
Solar/Wind Harmer
0.171
316258AE1-075 C
Solar/Wind Harmer
0.204
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.088
970909AG2-566 GEN
Solar/Wind Harmer
2.566
3147133PAMPLIN
Solar/Wind Harmer
0.741
971193AH1-056 GEN
Solar/Wind Harmer
14.378
963181AG1-167 GEN
Solar/Wind Harmer
0.893
959311AF2-222 GEN
Solar/Wind Harmer
16.945
970257AG2-171 GEN
Solar/Wind Harmer
5.919
315785AD2-033 C
Solar/Wind Harmer
1.44
964241AG1-285 GEN
Solar/Wind Harmer
10.432
316131AB2-060 GEN
Solar/Wind Harmer
0.453
970221AG2-151 GEN
Solar/Wind Harmer
7.009
316478AD1-087 GEN
Solar/Wind Harmer
0.407
316486AD2-202 GEN
Solar/Wind Harmer
0.12
3147043LAWRENC
Solar/Wind Harmer
0.063
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.061
313506AB2-031 GEN
Solar/Wind Harmer
0.265
971683AH1-343 GEN
Solar/Wind Harmer
3.059
970917AG2-570 GEN
Solar/Wind Harmer
7.384
316365GEN2_N
Solar/Wind Harmer
0.176
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
957521AF2-046 GEN
Solar/Wind Harmer
5.572
961681AG1-008 GEN
Solar/Wind Harmer
5.572
3145796HORNRTN
Solar/Wind Harmer
0.297
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316210AC1-098 GEN
Solar/Wind Harmer
0.686
316463AE2-346 GEN
Solar/Wind Harmer
0.063
316140AB2-099
Solar/Wind Harmer
0.026
962331AG1-082 GEN
Solar/Wind Harmer
0.783
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.073
316327AA2-057 GEN
Solar/Wind Harmer
0.108
3145273HOLLAND
Solar/Wind Harmer
0.054
315813AE1-149 C
Solar/Wind Harmer
3.784
3156021HOLLOMANSOL
Solar/Wind Harmer
0.322
315839AE2-212 C
Solar/Wind Harmer
0.001
315724AD1-057 GEN
Solar/Wind Harmer
0.265
970659AG2-427 GEN
Solar/Wind Harmer
0.747
316083AB2-161 GEN
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
0.07
3146233WITAKRS
Solar/Wind Harmer
0.351
3146233WITAKRS
Solar/Wind Harmer
0.048
3138543CONSLDL
Solar/Wind Harmer
0.046
315737AD1-076 GEN
Solar/Wind Harmer
0.896
971157AH1-035 GEN
Solar/Wind Harmer
0.836
965281AG1-393 GEN
Solar/Wind Harmer
0.741
315614AA2-178 GEN
Solar/Wind Harmer
0.398
3146376EDENTON
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
316435W1029_GEN3
Solar/Wind Harmer
0
316320Y1-086
Solar/Wind Harmer
0
3146456SLIGO L269
Solar/Wind Harmer
0.069
971153AH1-033 GEN
Solar/Wind Harmer
0.794
944581AF1-123 GEN
Solar/Wind Harmer
15.457
944601AF1-125 GEN
Solar/Wind Harmer
15.219
3145963POPLR C
Solar/Wind Harmer
0.069
3151101ELIZAR3
Adder
6.349
3144873MCLAUGH
Solar/Wind Harmer
0.002
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.068
971623AH1-311 GEN
Solar/Wind Harmer
0.136
3144536CHRHLND
Solar/Wind Harmer
0.01
3145933PARMELE
Solar/Wind Harmer
0.068
966801AG1-551 GEN
Solar/Wind Harmer
0.788
961601AG1-000A GEN
Solar/Wind Harmer
4.808
315773AC2-141 GEN
Solar/Wind Harmer
2.468
3146073TAR RVR
Solar/Wind Harmer
0.067
3146083TARBORO
Solar/Wind Harmer
0.067
316283AC2-100 C
Solar/Wind Harmer
0.132
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.027
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.798
3151171GRAVELC
Adder
0.923
961611AG1-000B GEN
Solar/Wind Harmer
1.758
315778AD1-151 GEN
Solar/Wind Harmer
5.261
970129AG2-093 GEN
Solar/Wind Harmer
3.971
970133AG2-095 GEN
Solar/Wind Harmer
0.63
3144216WINCHST
Adder
0.231
3150921YORKTN3
Adder
1.525
3142946ENON
Solar/Wind Harmer
0.02
316382AG1-145 C
Solar/Wind Harmer
0
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.175
316499AE2-029_GEN
Solar/Wind Helper
0.514
3132273ORANGE
Solar/Wind Helper
0.027
315616AA1-038_C
Solar/Wind Helper
0.545
3147666LOUISA
Solar/Wind Helper
0.273
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.726
MECLTFEXP_MEC->PJM
CLTF
0.354
SIGELTFEXP_SIGE->PJM
CLTF
0.008
CPLELTFEXP_CPLE->PJM
CLTF
4.352
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.276
LAGNLTFEXP_LAGN->PJM
CLTF
1.781
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.535
TVALTFEXP_TVA->PJM
CLTF
0.87
NYPJM->LTFIMP_NY
CLTF
0.579
LGEELTFEXP_LGEE->PJM
CLTF
0.048
WECLTFEXP_WEC->PJM
CLTF
0.018

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:185.6 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1540.5
MW Contribution:2.24
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.146
316303AF2-085
50/50
2.223
3151541CLOVER2
50/50
2.485
3151611KERR 4
50/50
0.233
3151621KERR 5
50/50
0.233
3151631KERR 6
50/50
0.233
3151641KERR 7
50/50
0.233
971845AH1-439 GEN
Solar/Wind Harmer
23.024
970285AG2-188 GEN
Solar/Wind Harmer
36.67
315657AE1-056 GEN
Solar/Wind Harmer
9.935
946301AF1-294 GEN
Solar/Wind Harmer
6.417
961791AG1-021 GEN
Solar/Wind Harmer
3.13
970683AG2-441 GEN
Solar/Wind Harmer
17.94
970681AG2-440 GEN
Solar/Wind Harmer
14.352
3144303KENBRDG
Solar/Wind Harmer
-0.017
971443AH1-215 GEN
Solar/Wind Harmer
4.049
316239AB2-077_GEN
Solar/Wind Harmer
0.467
316238AB2-078_GEN
Solar/Wind Harmer
0.467
316233AE1-074 FULL
Solar/Wind Harmer
0.318
971281AH1-106 GEN
Solar/Wind Harmer
1.921
971283AH1-107 GEN
Solar/Wind Harmer
1.921
316118AC1-105 GEN
Solar/Wind Harmer
0.807
270494AE1-108_GEN
Solar/Wind Harmer
2.995
970831AG2-522 GEN
Solar/Wind Harmer
5.644
3147173SINAI
Solar/Wind Harmer
-0.011
3151931BEARGRDN S1
50/50
5.86
3151911BEARGRDN G1
50/50
4.541
3144293JTRSVLE
50/50
0.753
970119AG2-088 GEN
50/50
16.672
3151531CLOVER1
50/50
2.497
3151601KERR 3
50/50
0.233
3151581KERR 1
50/50
0.083
972003AH1-546 GEN
Solar/Wind Harmer
26.388
970937AG2-583 GEN
Solar/Wind Harmer
32.774
316322AB2-045
Solar/Wind Harmer
1.483
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.021
316336AC2-165 C
Solar/Wind Harmer
6.018
3143336POWHATN
Solar/Wind Harmer
3.603
963171AG1-166 GEN
Solar/Wind Harmer
3.13
971563AH1-280 GEN
Solar/Wind Harmer
3.13
970685AG2-442 GEN
Solar/Wind Harmer
20.093
962491AG1-098 GEN
Solar/Wind Harmer
10.981
3151921BEARGRDN G2
50/50
4.541
3144293JTRSVLE
50/50
0.753
970413AG2-270 GEN
50/50
10.895
3151591KERR 2
50/50
0.233
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
4.6
316313AB2-026
Solar/Wind Harmer
0.819
316258AE1-075 C
Solar/Wind Harmer
0.737
316405AF2-144 C
Solar/Wind Harmer
0.778
3143336POWHATN
Solar/Wind Harmer
3.062
970909AG2-566 GEN
Solar/Wind Harmer
2.562
3147133PAMPLIN
Solar/Wind Harmer
-0.083
971193AH1-056 GEN
Solar/Wind Harmer
16.559
963181AG1-167 GEN
Solar/Wind Harmer
2.348
959311AF2-222 GEN
Solar/Wind Harmer
22.325
970257AG2-171 GEN
Solar/Wind Harmer
7.783
315785AD2-033 C
Solar/Wind Harmer
4.506
964241AG1-285 GEN
Solar/Wind Harmer
13.718
316131AB2-060 GEN
Solar/Wind Harmer
1.742
970221AG2-151 GEN
Solar/Wind Harmer
9.178
316478AD1-087 GEN
Solar/Wind Harmer
1.133
316486AD2-202 GEN
Solar/Wind Harmer
0.332
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.322
960061AF2-297 GEN
Solar/Wind Harmer
5.34
966621AG1-532 GEN
Solar/Wind Harmer
0.201
313506AB2-031 GEN
Solar/Wind Harmer
0.773
970917AG2-570 GEN
Solar/Wind Harmer
23.32
971683AH1-343 GEN
Solar/Wind Harmer
4.021
3150861SPRUNCD
Adder
0.375
316365GEN2_N
Solar/Wind Harmer
0.594
3156081AA2-088 GEN
Solar/Wind Harmer
2.773
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.624
961681AG1-008 GEN
Solar/Wind Harmer
6.624
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.302
316463AE2-346 GEN
Solar/Wind Harmer
0.133
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.031
316317KELFORD C
Solar/Wind Harmer
0.388
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.813
3145273HOLLAND
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
4.985
3156021HOLLOMANSOL
Solar/Wind Harmer
1.073
315839AE2-212 C
Solar/Wind Harmer
0.24
970659AG2-427 GEN
Solar/Wind Harmer
0.748
316083AB2-161 GEN
Solar/Wind Harmer
1.288
315724AD1-057 GEN
Solar/Wind Harmer
0.456
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
-0.008
3146233WITAKRS
Solar/Wind Harmer
0.164
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.488
971157AH1-035 GEN
Solar/Wind Harmer
0.978
965281AG1-393 GEN
Solar/Wind Harmer
0.977
315614AA2-178 GEN
Solar/Wind Harmer
0.842
3146376EDENTON
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316435W1029_GEN3
Solar/Wind Harmer
1.405
316320Y1-086
Solar/Wind Harmer
0.453
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.941
944581AF1-123 GEN
Solar/Wind Harmer
35.103
3151101ELIZAR3
Adder
6.351
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.801
3151171GRAVELC
Adder
0.924
3144216WINCHST
Adder
0.232
3150921YORKTN3
Adder
1.526
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.176
316499AE2-029_GEN
Solar/Wind Helper
0.517
3132273ORANGE
Solar/Wind Helper
0.028
3147666LOUISA
Solar/Wind Helper
0.309
315616AA1-038_C
Solar/Wind Helper
0.548
944601AF1-125 GEN
Solar/Wind Harmer
11.266
315693AD1-088 GEN
Solar/Wind Harmer
7.922
316237AB2-079_GEN
Solar/Wind Harmer
0.467
971377AH1-170 GEN
Solar/Wind Harmer
1.836
3147623JAMES R
Solar/Wind Harmer
0.227
3143226MDLTHAN
Solar/Wind Harmer
-0.014
957481AF2-042 GEN
Solar/Wind Harmer
41.127
970401AG2-262 GEN
Solar/Wind Harmer
0.837
315687AD1-152 GEN
Solar/Wind Harmer
1.432
3143526WINTERP
Solar/Wind Harmer
-0.061
3147043LAWRENC
Adder
0.942
971065AG2-659 GEN
Solar/Wind Harmer
5.848
316129AC1-054 GEN
Solar/Wind Harmer
1.008
971795AH1-408 GEN
Solar/Wind Harmer
8.35
316003AC1-222 GEN
Solar/Wind Harmer
0.972
960081AF2-299 GEN
Solar/Wind Harmer
1.114
970919AG2-571 GEN
Solar/Wind Harmer
2.952
970087AG2-069 GEN
Solar/Wind Harmer
8.708
3145783HORNRTN
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.375
316190AA2-174 GEN
Solar/Wind Harmer
0.112
940641AE2-051 GEN
Solar/Wind Harmer
8.503
316023GEN1_S
Solar/Wind Harmer
0.594
939411AE1-173 GEN
Solar/Wind Harmer
43.657
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.775
962571AG1-106 GEN
Solar/Wind Harmer
1.22
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.723
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.219
316381AD1-082 GEN
Solar/Wind Harmer
0.728
315722AD1-056 GEN
Solar/Wind Harmer
0.83
970661AG2-428 GEN
Solar/Wind Harmer
8.41
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
1.971
3146233WITAKRS
Solar/Wind Harmer
-0.031
316093AE2-104_GEN
Solar/Wind Harmer
2.275
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.318
3130156CHOWAN
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
1.92
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.811
316246AF1-032 C
Solar/Wind Harmer
0.157
3146456SLIGO L269
Solar/Wind Harmer
-0.008
316388AE2-253 GEN
Solar/Wind Harmer
0.521
944591AF1-124 GEN
Solar/Wind Harmer
35.229
3150981CHESPKA
Adder
0.854
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
944631AF1-128 GEN
Adder
29.484
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.057
316192AB2-158 GEN
Solar/Wind Helper
0.927
3147666LOUISA
Solar/Wind Helper
0.538
3144293JTRSVLE
50/50
0.753
3144293JTRSVLE
50/50
0.634
970535AG2-341 GEN
50/50
2.238
3146776BUCKING
Solar/Wind Harmer
-0.175
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.493
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.913
963191AG1-168 GEN
Solar/Wind Harmer
2.348
971741AH1-377 GEN
Solar/Wind Harmer
28.4
316034AC1-036 C
Solar/Wind Harmer
0.386
970323AG2-213 GEN
Solar/Wind Harmer
10.377
971775AH1-396 GEN
Solar/Wind Harmer
1.478
313527AB2-043 GEN
Solar/Wind Harmer
2.568
971489AH1-241 GEN
Solar/Wind Harmer
8.713
971223AH1-071 GEN
Solar/Wind Harmer
1.756
962561AG1-105 GEN
Solar/Wind Harmer
7.471
939181AE1-148 GEN
Solar/Wind Harmer
7.446
970099AG2-077 GEN
Solar/Wind Harmer
16.451
964791AG1-342 GEN
Solar/Wind Harmer
2.74
3146843MT LREL
Solar/Wind Harmer
-0.013
3146843MT LREL
Solar/Wind Harmer
-0.013
3143526WINTERP
Solar/Wind Harmer
-0.061
970933AG2-581 GEN
Solar/Wind Harmer
10.52
972187AH1-678 GEN
Adder
2.454
972185AH1-677 GEN
Adder
4.815
316181AB2-040 GEN
Solar/Wind Harmer
1.342
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
1.047
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.088
3145783HORNRTN
Solar/Wind Harmer
0.87
3145783HORNRTN
Solar/Wind Harmer
0.272
3145783HORNRTN
Solar/Wind Harmer
0.109
316426AA2-053 GEN
Solar/Wind Harmer
0.92
3144356SAPONY
Solar/Wind Harmer
0.307
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
316274AC1-208 GEN
Solar/Wind Harmer
0.909
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.852
970657AG2-426 GEN
Solar/Wind Harmer
2.477
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.932
3146376EDENTON
Solar/Wind Harmer
0.231
3146376EDENTON
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.405
316433W1029_GEN2
Solar/Wind Harmer
1.405
316240AF1-291 C
Solar/Wind Harmer
0.233
3146386ELIZ CT
Solar/Wind Harmer
-0.008
3130086AYDLETT
Solar/Wind Harmer
-0.031
3137176SLIGO L2192
Solar/Wind Harmer
-0.031
3146456SLIGO L269
Solar/Wind Harmer
0.912
316018AA1-139 ULT2
Solar/Wind Harmer
0.661
316017AA1-139 ULT1
Solar/Wind Harmer
0.625
316339AD2-160 GEN
Solar/Wind Harmer
0.521
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.529
3142366NRTHEST
Adder
0.195
3150691DARBY 3
Adder
4.201
3150701DARBY 4
Adder
4.191
3150681DARBY 2
Adder
4.186
3150671DARBY 1
Adder
4.181
966001AG1-469 GEN
Solar/Wind Helper
0.199
3147243WELCO
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
19.409
946281AF1-292 GEN
Solar/Wind Harmer
0.222
316087AB2-174 GEN
Solar/Wind Harmer
1.385
970673AG2-436 GEN
Solar/Wind Harmer
20.177
970673AG2-436 GEN
Solar/Wind Harmer
10.216
941031AE2-094 GEN
Solar/Wind Harmer
17.883
944011AF1-069 GEN
Solar/Wind Harmer
5.603
3137643SOCKMAN
Solar/Wind Harmer
-0.038
970085AG2-068 GEN
Solar/Wind Harmer
5.805
970581AG2-369 GEN
Solar/Wind Harmer
4.993
971285AH1-108 GEN
Adder
0.613
315607AA1-063A GEN
Solar/Wind Harmer
0.911
3146043SEABORD
Solar/Wind Harmer
-0.009
315814AE2-033 C
Solar/Wind Harmer
8.189
316315AB2-025 C
Solar/Wind Harmer
0.237
970865AG2-541 GEN
Solar/Wind Harmer
3.523
965291AG1-394 GEN
Solar/Wind Harmer
0.761
315652AC1-086 GEN
Solar/Wind Harmer
9.545
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.033
3146033SCOT NK
Solar/Wind Harmer
-0.033
3145513AHOSKIE
Solar/Wind Harmer
0.072
961941AG1-037 GEN
Solar/Wind Harmer
0.062
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.449
315833AF1-017_GEN
Solar/Wind Harmer
1.494
316349AD2-085 GEN
Solar/Wind Harmer
0.7
316311AC2-079 GEN
Solar/Wind Harmer
3.968
316319Z2-044 C
Solar/Wind Harmer
0.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.583
315733AD1-074 GEN2
Solar/Wind Harmer
1.583
315735AD1-075 GEN1
Solar/Wind Harmer
0.792
315835AF2-110_GEN
Solar/Wind Harmer
0.978
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.632
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
1.92
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.209
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.142
316305AF2-043 C
Solar/Wind Harmer
0.233
313526AB2-022
Solar/Wind Harmer
0.209
319010AE1-072 C
Solar/Wind Harmer
1.562
3146406KITTY HAWK
Solar/Wind Harmer
0.006
957871AF2-081 GEN
Solar/Wind Harmer
3.86
3151081ELIZAR1
Adder
6.271
3151091ELIZAR2
Adder
6.162
3152611GOSPORTB
Adder
0.871
3152621GOSPORTC
Adder
0.739
3152601GOSPORTA
Adder
0.682
972265AH1-717 GEN
Adder
5.127
3151201GRAVEL4
Adder
4.806
3151191GRAVEL3
Adder
4.745
3151211GRAVEL5
Adder
4.745
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.121
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
0.346
SIGELTFEXP_SIGE->PJM
CLTF
0.008
CPLELTFEXP_CPLE->PJM
CLTF
4.345
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.202
LAGNLTFEXP_LAGN->PJM
CLTF
1.77
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.515
TVALTFEXP_TVA->PJM
CLTF
0.864
NYPJM->LTFIMP_NY
CLTF
0.574
LGEELTFEXP_LGEE->PJM
CLTF
0.044
WECLTFEXP_WEC->PJM
CLTF
0.016

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:185.6 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1540.49
MW Contribution:2.24
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.54
3144293JTRSVLE
50/50
0.753
3151931BEARGRDN S1
50/50
5.86
3151911BEARGRDN G1
50/50
4.54
3144293JTRSVLE
50/50
0.753
970119AG2-088 GEN
50/50
16.671
3151531CLOVER1
50/50
2.497
3151601KERR 3
50/50
0.233
3151581KERR 1
50/50
0.083
972003AH1-546 GEN
Solar/Wind Harmer
26.387
970937AG2-583 GEN
Solar/Wind Harmer
32.773
316322AB2-045
Solar/Wind Harmer
1.483
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.021
316336AC2-165 C
Solar/Wind Harmer
6.018
3143336POWHATN
Solar/Wind Harmer
3.603
963171AG1-166 GEN
Solar/Wind Harmer
3.13
971563AH1-280 GEN
Solar/Wind Harmer
3.13
970685AG2-442 GEN
Solar/Wind Harmer
20.093
962491AG1-098 GEN
Solar/Wind Harmer
10.981
315693AD1-088 GEN
Solar/Wind Harmer
7.922
316237AB2-079_GEN
Solar/Wind Harmer
0.467
971377AH1-170 GEN
Solar/Wind Harmer
1.835
3147623JAMES R
Solar/Wind Harmer
0.227
3143226MDLTHAN
Solar/Wind Harmer
-0.014
957481AF2-042 GEN
Solar/Wind Harmer
41.127
970401AG2-262 GEN
Solar/Wind Harmer
0.837
315687AD1-152 GEN
Solar/Wind Harmer
1.432
3143526WINTERP
Solar/Wind Harmer
-0.061
3147043LAWRENC
Adder
0.942
971065AG2-659 GEN
Solar/Wind Harmer
5.848
316129AC1-054 GEN
Solar/Wind Harmer
1.008
971795AH1-408 GEN
Solar/Wind Harmer
8.349
316003AC1-222 GEN
Solar/Wind Harmer
0.972
960081AF2-299 GEN
Solar/Wind Harmer
1.114
970919AG2-571 GEN
Solar/Wind Harmer
2.952
970087AG2-069 GEN
Solar/Wind Harmer
8.708
3145783HORNRTN
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.375
316190AA2-174 GEN
Solar/Wind Harmer
0.112
940641AE2-051 GEN
Solar/Wind Harmer
8.503
316023GEN1_S
Solar/Wind Harmer
0.594
939411AE1-173 GEN
Solar/Wind Harmer
43.657
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.775
3144293JTRSVLE
50/50
0.753
3144293JTRSVLE
50/50
0.634
970535AG2-341 GEN
50/50
2.237
3146776BUCKING
Solar/Wind Harmer
-0.175
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.493
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.913
963191AG1-168 GEN
Solar/Wind Harmer
2.348
971741AH1-377 GEN
Solar/Wind Harmer
28.4
316034AC1-036 C
Solar/Wind Harmer
0.386
970323AG2-213 GEN
Solar/Wind Harmer
10.377
971775AH1-396 GEN
Solar/Wind Harmer
1.478
313527AB2-043 GEN
Solar/Wind Harmer
2.568
971489AH1-241 GEN
Solar/Wind Harmer
8.713
971223AH1-071 GEN
Solar/Wind Harmer
1.756
962561AG1-105 GEN
Solar/Wind Harmer
7.471
939181AE1-148 GEN
Solar/Wind Harmer
7.446
970099AG2-077 GEN
Solar/Wind Harmer
16.451
964791AG1-342 GEN
Solar/Wind Harmer
2.74
3146843MT LREL
Solar/Wind Harmer
-0.013
3146843MT LREL
Solar/Wind Harmer
-0.013
3143526WINTERP
Solar/Wind Harmer
-0.061
970933AG2-581 GEN
Solar/Wind Harmer
10.52
972187AH1-678 GEN
Adder
2.454
972185AH1-677 GEN
Adder
4.815
316181AB2-040 GEN
Solar/Wind Harmer
1.342
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
1.047
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.088
3145783HORNRTN
Solar/Wind Harmer
0.87
3145783HORNRTN
Solar/Wind Harmer
0.272
3145783HORNRTN
Solar/Wind Harmer
0.109
316426AA2-053 GEN
Solar/Wind Harmer
0.92
3144356SAPONY
Solar/Wind Harmer
0.307
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
316274AC1-208 GEN
Solar/Wind Harmer
0.909
3145796HORNRTN
Solar/Wind Harmer
-0.025
962571AG1-106 GEN
Solar/Wind Harmer
1.22
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.723
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.219
316381AD1-082 GEN
Solar/Wind Harmer
0.728
315722AD1-056 GEN
Solar/Wind Harmer
0.83
970661AG2-428 GEN
Solar/Wind Harmer
8.41
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
1.971
3146233WITAKRS
Solar/Wind Harmer
-0.031
316093AE2-104_GEN
Solar/Wind Harmer
2.275
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.318
3130156CHOWAN
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
1.92
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.811
316246AF1-032 C
Solar/Wind Harmer
0.157
3146456SLIGO L269
Solar/Wind Harmer
-0.008
316388AE2-253 GEN
Solar/Wind Harmer
0.521
944591AF1-124 GEN
Solar/Wind Harmer
35.23
3150981CHESPKA
Adder
0.854
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
944631AF1-128 GEN
Adder
29.485
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.057
316192AB2-158 GEN
Solar/Wind Helper
0.928
3147666LOUISA
Solar/Wind Helper
0.539
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.852
970657AG2-426 GEN
Solar/Wind Harmer
2.477
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.932
3146376EDENTON
Solar/Wind Harmer
0.231
3146376EDENTON
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.405
316433W1029_GEN2
Solar/Wind Harmer
1.405
316240AF1-291 C
Solar/Wind Harmer
0.233
3146386ELIZ CT
Solar/Wind Harmer
-0.008
3130086AYDLETT
Solar/Wind Harmer
-0.031
3137176SLIGO L2192
Solar/Wind Harmer
-0.031
3146456SLIGO L269
Solar/Wind Harmer
0.912
316018AA1-139 ULT2
Solar/Wind Harmer
0.661
316017AA1-139 ULT1
Solar/Wind Harmer
0.625
316339AD2-160 GEN
Solar/Wind Harmer
0.521
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.53
3142366NRTHEST
Adder
0.195
3150691DARBY 3
Adder
4.201
3150701DARBY 4
Adder
4.191
3150681DARBY 2
Adder
4.186
3150671DARBY 1
Adder
4.181
966001AG1-469 GEN
Solar/Wind Helper
0.199
970413AG2-270 GEN
50/50
10.894
3151591KERR 2
50/50
0.233
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
4.6
316313AB2-026
Solar/Wind Harmer
0.819
316258AE1-075 C
Solar/Wind Harmer
0.737
316405AF2-144 C
Solar/Wind Harmer
0.778
3143336POWHATN
Solar/Wind Harmer
3.062
970909AG2-566 GEN
Solar/Wind Harmer
2.562
3147133PAMPLIN
Solar/Wind Harmer
-0.083
971193AH1-056 GEN
Solar/Wind Harmer
16.559
963181AG1-167 GEN
Solar/Wind Harmer
2.348
959311AF2-222 GEN
Solar/Wind Harmer
22.325
970257AG2-171 GEN
Solar/Wind Harmer
7.783
315785AD2-033 C
Solar/Wind Harmer
4.506
964241AG1-285 GEN
Solar/Wind Harmer
13.718
316131AB2-060 GEN
Solar/Wind Harmer
1.742
970221AG2-151 GEN
Solar/Wind Harmer
9.177
316478AD1-087 GEN
Solar/Wind Harmer
1.133
316486AD2-202 GEN
Solar/Wind Harmer
0.332
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.322
960061AF2-297 GEN
Solar/Wind Harmer
5.34
966621AG1-532 GEN
Solar/Wind Harmer
0.201
313506AB2-031 GEN
Solar/Wind Harmer
0.773
970917AG2-570 GEN
Solar/Wind Harmer
23.32
971683AH1-343 GEN
Solar/Wind Harmer
4.021
3150861SPRUNCD
Adder
0.375
316365GEN2_N
Solar/Wind Harmer
0.594
3156081AA2-088 GEN
Solar/Wind Harmer
2.773
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.624
961681AG1-008 GEN
Solar/Wind Harmer
6.624
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.302
316463AE2-346 GEN
Solar/Wind Harmer
0.133
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.031
316317KELFORD C
Solar/Wind Harmer
0.388
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.813
3145273HOLLAND
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
4.985
3156021HOLLOMANSOL
Solar/Wind Harmer
1.073
315839AE2-212 C
Solar/Wind Harmer
0.24
970659AG2-427 GEN
Solar/Wind Harmer
0.748
316083AB2-161 GEN
Solar/Wind Harmer
1.288
315724AD1-057 GEN
Solar/Wind Harmer
0.456
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
-0.008
3146233WITAKRS
Solar/Wind Harmer
0.164
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.488
971157AH1-035 GEN
Solar/Wind Harmer
0.978
965281AG1-393 GEN
Solar/Wind Harmer
0.977
315614AA2-178 GEN
Solar/Wind Harmer
0.842
3146376EDENTON
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316435W1029_GEN3
Solar/Wind Harmer
1.405
316320Y1-086
Solar/Wind Harmer
0.453
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.941
944581AF1-123 GEN
Solar/Wind Harmer
35.103
3151101ELIZAR3
Adder
6.351
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.801
3151171GRAVELC
Adder
0.924
3144216WINCHST
Adder
0.232
3150921YORKTN3
Adder
1.526
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.176
316499AE2-029_GEN
Solar/Wind Helper
0.517
3132273ORANGE
Solar/Wind Helper
0.028
3147666LOUISA
Solar/Wind Helper
0.31
315616AA1-038_C
Solar/Wind Helper
0.549
944601AF1-125 GEN
Solar/Wind Harmer
11.266
972205AH1-687 GEN
50/50
22.145
316303AF2-085
50/50
2.223
3151541CLOVER2
50/50
2.485
3151611KERR 4
50/50
0.233
3151621KERR 5
50/50
0.233
3151631KERR 6
50/50
0.233
3151641KERR 7
50/50
0.233
971845AH1-439 GEN
Solar/Wind Harmer
23.024
970285AG2-188 GEN
Solar/Wind Harmer
36.669
315657AE1-056 GEN
Solar/Wind Harmer
9.935
946301AF1-294 GEN
Solar/Wind Harmer
6.417
961791AG1-021 GEN
Solar/Wind Harmer
3.13
970683AG2-441 GEN
Solar/Wind Harmer
17.94
970681AG2-440 GEN
Solar/Wind Harmer
14.352
3144303KENBRDG
Solar/Wind Harmer
-0.017
971443AH1-215 GEN
Solar/Wind Harmer
4.049
316239AB2-077_GEN
Solar/Wind Harmer
0.467
316238AB2-078_GEN
Solar/Wind Harmer
0.467
316233AE1-074 FULL
Solar/Wind Harmer
0.318
971281AH1-106 GEN
Solar/Wind Harmer
1.921
971283AH1-107 GEN
Solar/Wind Harmer
1.921
316118AC1-105 GEN
Solar/Wind Harmer
0.807
270494AE1-108_GEN
Solar/Wind Harmer
2.995
970831AG2-522 GEN
Solar/Wind Harmer
5.644
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
19.408
946281AF1-292 GEN
Solar/Wind Harmer
0.222
316087AB2-174 GEN
Solar/Wind Harmer
1.385
970673AG2-436 GEN
Solar/Wind Harmer
20.177
970673AG2-436 GEN
Solar/Wind Harmer
10.216
941031AE2-094 GEN
Solar/Wind Harmer
17.883
944011AF1-069 GEN
Solar/Wind Harmer
5.603
3137643SOCKMAN
Solar/Wind Harmer
-0.038
970085AG2-068 GEN
Solar/Wind Harmer
5.805
970581AG2-369 GEN
Solar/Wind Harmer
4.993
971285AH1-108 GEN
Adder
0.613
315607AA1-063A GEN
Solar/Wind Harmer
0.911
3146043SEABORD
Solar/Wind Harmer
-0.009
315814AE2-033 C
Solar/Wind Harmer
8.189
316315AB2-025 C
Solar/Wind Harmer
0.237
970865AG2-541 GEN
Solar/Wind Harmer
3.523
965291AG1-394 GEN
Solar/Wind Harmer
0.761
315652AC1-086 GEN
Solar/Wind Harmer
9.545
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.033
3146033SCOT NK
Solar/Wind Harmer
-0.033
3145513AHOSKIE
Solar/Wind Harmer
0.072
961941AG1-037 GEN
Solar/Wind Harmer
0.062
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.449
315833AF1-017_GEN
Solar/Wind Harmer
1.494
316349AD2-085 GEN
Solar/Wind Harmer
0.7
316311AC2-079 GEN
Solar/Wind Harmer
3.968
316319Z2-044 C
Solar/Wind Harmer
0.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.583
315733AD1-074 GEN2
Solar/Wind Harmer
1.583
315735AD1-075 GEN1
Solar/Wind Harmer
0.792
315835AF2-110_GEN
Solar/Wind Harmer
0.978
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.632
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
1.92
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.209
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.142
316305AF2-043 C
Solar/Wind Harmer
0.233
313526AB2-022
Solar/Wind Harmer
0.209
319010AE1-072 C
Solar/Wind Harmer
1.562
3146406KITTY HAWK
Solar/Wind Harmer
0.006
957871AF2-081 GEN
Solar/Wind Harmer
3.86
3151081ELIZAR1
Adder
6.271
3151091ELIZAR2
Adder
6.162
3152611GOSPORTB
Adder
0.871
3152621GOSPORTC
Adder
0.739
3152601GOSPORTA
Adder
0.682
972265AH1-717 GEN
Adder
5.127
3151201GRAVEL4
Adder
4.806
3151191GRAVEL3
Adder
4.746
3151211GRAVEL5
Adder
4.746
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.121
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
0.346
SIGELTFEXP_SIGE->PJM
CLTF
0.008
CPLELTFEXP_CPLE->PJM
CLTF
4.345
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.201
LAGNLTFEXP_LAGN->PJM
CLTF
1.769
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.514
TVALTFEXP_TVA->PJM
CLTF
0.864
NYPJM->LTFIMP_NY
CLTF
0.574
LGEELTFEXP_LGEE->PJM
CLTF
0.044
WECLTFEXP_WEC->PJM
CLTF
0.016

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.49 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1439.97
MW Contribution:2.16
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.601
3144293JTRSVLE
50/50
0.746
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
316313AB2-026
Solar/Wind Harmer
0.868
316258AE1-075 C
Solar/Wind Harmer
0.782
316405AF2-144 C
Solar/Wind Harmer
0.825
3143336POWHATN
Solar/Wind Harmer
3.247
942461AE2-259 GEN
Solar/Wind Harmer
4.59
970909AG2-566 GEN
Solar/Wind Harmer
2.539
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.45
963181AG1-167 GEN
Solar/Wind Harmer
2.328
959311AF2-222 GEN
Solar/Wind Harmer
22.003
970257AG2-171 GEN
Solar/Wind Harmer
7.661
315785AD2-033 C
Solar/Wind Harmer
4.427
964241AG1-285 GEN
Solar/Wind Harmer
13.397
316131AB2-060 GEN
Solar/Wind Harmer
1.694
970221AG2-151 GEN
Solar/Wind Harmer
9.59
316478AD1-087 GEN
Solar/Wind Harmer
1.073
316486AD2-202 GEN
Solar/Wind Harmer
0.314
3147043LAWRENC
Solar/Wind Harmer
-0.007
3150861SPRUNCD
Adder
0.417
316248AF1-058 C
Solar/Wind Harmer
0.306
960061AF2-297 GEN
Solar/Wind Harmer
5.079
966621AG1-532 GEN
Solar/Wind Harmer
0.189
313506AB2-031 GEN
Solar/Wind Harmer
0.727
971683AH1-343 GEN
Solar/Wind Harmer
3.823
970917AG2-570 GEN
Solar/Wind Harmer
20.936
316365GEN2_N
Solar/Wind Harmer
0.554
3143096IRON208
Adder
0.298
3143096IRON208
Adder
0.292
3156081AA2-088 GEN
Solar/Wind Harmer
2.589
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
315839AE2-212 C
Solar/Wind Harmer
0.237
957521AF2-046 GEN
Solar/Wind Harmer
6.176
961681AG1-008 GEN
Solar/Wind Harmer
6.176
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
965281AG1-393 GEN
Solar/Wind Harmer
0.97
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.214
315813AE1-149 C
Solar/Wind Harmer
4.801
316463AE2-346 GEN
Solar/Wind Harmer
0.124
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.959
316317KELFORD C
Solar/Wind Harmer
0.361
3145823KELFORD
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
0.714
316083AB2-161 GEN
Solar/Wind Harmer
1.228
970661AG2-428 GEN
Solar/Wind Harmer
1.415
316327AA2-057 GEN
Solar/Wind Harmer
0.756
3145273HOLLAND
Solar/Wind Harmer
-0.006
970133AG2-095 GEN
Solar/Wind Harmer
0.837
3156021HOLLOMANSOL
Solar/Wind Harmer
0.996
315724AD1-057 GEN
Solar/Wind Harmer
0.424
970129AG2-093 GEN
Solar/Wind Harmer
4.142
3146206CASHIE
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.153
3146233WITAKRS
Solar/Wind Harmer
-0.005
315778AD1-151 GEN
Solar/Wind Harmer
6.319
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.378
971157AH1-035 GEN
Solar/Wind Harmer
0.905
315614AA2-178 GEN
Solar/Wind Harmer
0.779
3146376EDENTON
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.298
961611AG1-000B GEN
Solar/Wind Harmer
1.508
316320Y1-086
Solar/Wind Harmer
0.418
3145963POPLR C
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151221GRAVEL6
Adder
4.597
3151171GRAVELC
Adder
0.884
3144293JTRSVLE
50/50
0.746
3144293JTRSVLE
50/50
0.629
970535AG2-341 GEN
50/50
2.158
3146776BUCKING
Solar/Wind Harmer
-0.177
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.372
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.88
963191AG1-168 GEN
Solar/Wind Harmer
2.328
971741AH1-377 GEN
Solar/Wind Harmer
28.01
316034AC1-036 C
Solar/Wind Harmer
0.38
970323AG2-213 GEN
Solar/Wind Harmer
10.214
971775AH1-396 GEN
Solar/Wind Harmer
1.455
971223AH1-071 GEN
Solar/Wind Harmer
2.076
313527AB2-043 GEN
Solar/Wind Harmer
2.493
971489AH1-241 GEN
Solar/Wind Harmer
9.104
3143526WINTERP
Solar/Wind Harmer
-0.071
962561AG1-105 GEN
Solar/Wind Harmer
7.195
939181AE1-148 GEN
Solar/Wind Harmer
7.148
970099AG2-077 GEN
Solar/Wind Harmer
15.503
964791AG1-342 GEN
Solar/Wind Harmer
2.634
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970933AG2-581 GEN
Solar/Wind Harmer
9.649
316181AB2-040 GEN
Solar/Wind Harmer
1.262
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.983
3145593CAROLNA
Solar/Wind Harmer
0.073
972187AH1-678 GEN
Adder
2.2
972185AH1-677 GEN
Adder
4.302
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
316274AC1-208 GEN
Solar/Wind Harmer
0.849
316240AF1-291 C
Solar/Wind Harmer
0.235
944641AF1-129 GEN
Adder
33.028
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.793
970657AG2-426 GEN
Solar/Wind Harmer
2.358
970657AG2-426 GEN
Solar/Wind Harmer
0.493
316065AD1-022 GEN
Solar/Wind Harmer
3.643
316033AB2-134 GEN
Solar/Wind Harmer
2.34
315697AD1-025 GEN
Solar/Wind Harmer
1.468
3142366NRTHEST
Adder
0.21
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3144873MCLAUGH
Solar/Wind Harmer
0
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.866
3144216WINCHST
Adder
0.221
3150921YORKTN3
Adder
1.456
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3148013FISHERV
Solar/Wind Helper
0.171
316499AE2-029_GEN
Solar/Wind Helper
0.503
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.534
3147666LOUISA
Solar/Wind Helper
0.265
944581AF1-123 GEN
Solar/Wind Harmer
1.127
3151931BEARGRDN S1
50/50
5.938
3151911BEARGRDN G1
50/50
4.601
3144293JTRSVLE
50/50
0.746
970119AG2-088 GEN
50/50
19.705
972003AH1-546 GEN
Solar/Wind Harmer
26.72
970937AG2-583 GEN
Solar/Wind Harmer
33.599
316322AB2-045
Solar/Wind Harmer
1.495
3146776BUCKING
Solar/Wind Harmer
-0.018
316336AC2-165 C
Solar/Wind Harmer
6.302
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.82
963171AG1-166 GEN
Solar/Wind Harmer
3.104
971563AH1-280 GEN
Solar/Wind Harmer
3.104
970685AG2-442 GEN
Solar/Wind Harmer
19.859
3143226MDLTHAN
Solar/Wind Harmer
-0.017
962491AG1-098 GEN
Solar/Wind Harmer
10.562
971377AH1-170 GEN
Solar/Wind Harmer
1.918
3147623JAMES R
Solar/Wind Harmer
0.237
315693AD1-088 GEN
Solar/Wind Harmer
7.599
316237AB2-079_GEN
Solar/Wind Harmer
0.453
3143526WINTERP
Solar/Wind Harmer
-0.071
957481AF2-042 GEN
Solar/Wind Harmer
38.757
970401AG2-262 GEN
Solar/Wind Harmer
0.805
315687AD1-152 GEN
Solar/Wind Harmer
1.355
3147043LAWRENC
Adder
0.898
971065AG2-659 GEN
Solar/Wind Harmer
5.572
316129AC1-054 GEN
Solar/Wind Harmer
0.96
971795AH1-408 GEN
Solar/Wind Harmer
7.936
3150851SPRUNCC
Adder
0.417
316003AC1-222 GEN
Solar/Wind Harmer
0.924
960081AF2-299 GEN
Solar/Wind Harmer
1.049
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
3142543TWELFTH
Solar/Wind Harmer
-0.001
970919AG2-571 GEN
Solar/Wind Harmer
2.65
970087AG2-069 GEN
Solar/Wind Harmer
7.82
316023GEN1_S
Solar/Wind Harmer
0.554
940641AE2-051 GEN
Solar/Wind Harmer
7.517
3143096IRON208
Adder
0.298
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.653
962571AG1-106 GEN
Solar/Wind Harmer
1.136
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
939411AE1-173 GEN
Solar/Wind Harmer
38.95
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.803
316212AC1-099_GEN
Solar/Wind Harmer
0.674
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.029
316381AD1-082 GEN
Solar/Wind Harmer
0.694
970661AG2-428 GEN
Solar/Wind Harmer
7.982
315722AD1-056 GEN
Solar/Wind Harmer
0.771
970129AG2-093 GEN
Solar/Wind Harmer
1.678
316458AB2-190 GEN2
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.827
3146233WITAKRS
Solar/Wind Harmer
-0.029
971069AG2-661 GEN
Solar/Wind Harmer
1.154
316093AE2-104_GEN
Solar/Wind Harmer
2.113
944631AF1-128 GEN
Adder
30.658
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.298
316433W1029_GEN2
Solar/Wind Harmer
1.298
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316222AC1-221 GEN
Solar/Wind Harmer
0.722
3130086AYDLETT
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.75
3142956BIRDNECK
Solar/Wind Harmer
0.381
316316AC1-027 C
Solar/Wind Harmer
0.218
316236AE1-162_GEN
Solar/Wind Harmer
0.214
316036AC1-147 C
Solar/Wind Harmer
0.192
3150991CHESPKB
Adder
0.662
3150991CHESPKB
Adder
0.646
3150691DARBY 3
Adder
4.502
3150701DARBY 4
Adder
4.491
3150681DARBY 2
Adder
4.486
3150671DARBY 1
Adder
4.481
966001AG1-469 GEN
Solar/Wind Helper
0.186
972205AH1-687 GEN
50/50
22.442
316303AF2-085
50/50
2.627
971845AH1-439 GEN
Solar/Wind Harmer
23.203
970285AG2-188 GEN
Solar/Wind Harmer
36.921
315657AE1-056 GEN
Solar/Wind Harmer
9.87
946301AF1-294 GEN
Solar/Wind Harmer
6.363
961791AG1-021 GEN
Solar/Wind Harmer
3.104
970683AG2-441 GEN
Solar/Wind Harmer
17.731
970681AG2-440 GEN
Solar/Wind Harmer
14.185
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.983
316239AB2-077_GEN
Solar/Wind Harmer
0.453
316238AB2-078_GEN
Solar/Wind Harmer
0.453
316233AE1-074 FULL
Solar/Wind Harmer
0.37
971281AH1-106 GEN
Solar/Wind Harmer
2.234
971283AH1-107 GEN
Solar/Wind Harmer
2.234
270494AE1-108_GEN
Solar/Wind Harmer
3.125
316118AC1-105 GEN
Solar/Wind Harmer
0.772
970831AG2-522 GEN
Solar/Wind Harmer
5.366
971285AH1-108 GEN
Adder
0.682
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
946281AF1-292 GEN
Solar/Wind Harmer
0.209
971967AH1-528 GEN
Solar/Wind Harmer
17.53
316087AB2-174 GEN
Solar/Wind Harmer
1.303
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970673AG2-436 GEN
Solar/Wind Harmer
17.985
970673AG2-436 GEN
Solar/Wind Harmer
9.106
941031AE2-094 GEN
Solar/Wind Harmer
15.864
944011AF1-069 GEN
Solar/Wind Harmer
4.971
315607AA1-063A GEN
Solar/Wind Harmer
0.854
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.213
970581AG2-369 GEN
Solar/Wind Harmer
4.483
970865AG2-541 GEN
Solar/Wind Harmer
3.349
315814AE2-033 C
Solar/Wind Harmer
7.587
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.711
3143316POE
Solar/Wind Harmer
-0.031
315652AC1-086 GEN
Solar/Wind Harmer
8.889
316318V4-068
Solar/Wind Harmer
0.196
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315833AF1-017_GEN
Solar/Wind Harmer
1.402
316349AD2-085 GEN
Solar/Wind Harmer
0.657
971447AH1-217 GEN
Solar/Wind Harmer
2.63
316311AC2-079 GEN
Solar/Wind Harmer
3.722
316132AB2-190 GEN1
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.197
316319Z2-044 C
Solar/Wind Harmer
0.403
315835AF2-110_GEN
Solar/Wind Harmer
0.908
316369SG1_INVT
Solar/Wind Harmer
1.296
315732AD1-074 GEN1
Solar/Wind Harmer
1.466
315733AD1-074 GEN2
Solar/Wind Harmer
1.466
315735AD1-075 GEN1
Solar/Wind Harmer
0.733
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
0.585
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.775
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316305AF2-043 C
Solar/Wind Harmer
0.216
316321Z2-027
Solar/Wind Harmer
0.193
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
313526AB2-022
Solar/Wind Harmer
0.193
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
972265AH1-717 GEN
Adder
4.91
3151201GRAVEL4
Adder
4.602
3151191GRAVEL3
Adder
4.544
3151211GRAVEL5
Adder
4.544
3152611GOSPORTB
Adder
0.805
3152621GOSPORTC
Adder
0.683
3152601GOSPORTA
Adder
0.63
971445AH1-216 GEN
Solar/Wind Harmer
4.395
3151081ELIZAR1
Adder
5.792
3151091ELIZAR2
Adder
5.691
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.103
3148013FISHERV
Solar/Wind Helper
0.098
3148463FAIRFLD
Solar/Wind Helper
0.118
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.772
971647AH1-324 GEN
Solar/Wind Harmer
3.605
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.775
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.535
316246AF1-032 C
Solar/Wind Harmer
0.145
3145963POPLR C
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
316174AB2-169 GEN
Solar/Wind Harmer
1.097
3151171GRAVELC
Adder
0.673
316375AC2-012 GEN
Solar/Wind Harmer
2.457
3145336SMITFLD
Solar/Wind Harmer
-0.028
3150981CHESPKA
Adder
0.789
944591AF1-124 GEN
Solar/Wind Harmer
32.38
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.798
3147666LOUISA
Solar/Wind Helper
0.46
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.345
MECLTFEXP_MEC->PJM
CLTF
0.252
SIGELTFEXP_SIGE->PJM
CLTF
0.005
CPLELTFEXP_CPLE->PJM
CLTF
3.992
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.116
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.012
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.013
LAGNLTFEXP_LAGN->PJM
CLTF
1.555
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.774
TVALTFEXP_TVA->PJM
CLTF
0.758
NYPJM->LTFIMP_NY
CLTF
0.536
LGEELTFEXP_LGEE->PJM
CLTF
0.012

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.49 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1439.97
MW Contribution:2.16
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.601
3144293JTRSVLE
50/50
0.746
3144293JTRSVLE
50/50
0.746
3144293JTRSVLE
50/50
0.629
970535AG2-341 GEN
50/50
2.158
972205AH1-687 GEN
50/50
22.442
316303AF2-085
50/50
2.627
971845AH1-439 GEN
Solar/Wind Harmer
23.203
970285AG2-188 GEN
Solar/Wind Harmer
36.921
315657AE1-056 GEN
Solar/Wind Harmer
9.87
946301AF1-294 GEN
Solar/Wind Harmer
6.363
961791AG1-021 GEN
Solar/Wind Harmer
3.104
970683AG2-441 GEN
Solar/Wind Harmer
17.731
970681AG2-440 GEN
Solar/Wind Harmer
14.185
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.983
316239AB2-077_GEN
Solar/Wind Harmer
0.453
316238AB2-078_GEN
Solar/Wind Harmer
0.453
316233AE1-074 FULL
Solar/Wind Harmer
0.37
971281AH1-106 GEN
Solar/Wind Harmer
2.234
971283AH1-107 GEN
Solar/Wind Harmer
2.234
270494AE1-108_GEN
Solar/Wind Harmer
3.125
316118AC1-105 GEN
Solar/Wind Harmer
0.772
970831AG2-522 GEN
Solar/Wind Harmer
5.366
971285AH1-108 GEN
Adder
0.682
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
946281AF1-292 GEN
Solar/Wind Harmer
0.209
971967AH1-528 GEN
Solar/Wind Harmer
17.53
316087AB2-174 GEN
Solar/Wind Harmer
1.303
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970673AG2-436 GEN
Solar/Wind Harmer
17.985
970673AG2-436 GEN
Solar/Wind Harmer
9.106
941031AE2-094 GEN
Solar/Wind Harmer
15.864
944011AF1-069 GEN
Solar/Wind Harmer
4.971
315607AA1-063A GEN
Solar/Wind Harmer
0.854
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.213
970581AG2-369 GEN
Solar/Wind Harmer
4.483
970865AG2-541 GEN
Solar/Wind Harmer
3.349
315814AE2-033 C
Solar/Wind Harmer
7.587
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.711
3143316POE
Solar/Wind Harmer
-0.031
315652AC1-086 GEN
Solar/Wind Harmer
8.889
316318V4-068
Solar/Wind Harmer
0.196
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315833AF1-017_GEN
Solar/Wind Harmer
1.402
316349AD2-085 GEN
Solar/Wind Harmer
0.657
971447AH1-217 GEN
Solar/Wind Harmer
2.63
316311AC2-079 GEN
Solar/Wind Harmer
3.722
316132AB2-190 GEN1
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.197
316319Z2-044 C
Solar/Wind Harmer
0.403
315835AF2-110_GEN
Solar/Wind Harmer
0.908
316369SG1_INVT
Solar/Wind Harmer
1.296
315732AD1-074 GEN1
Solar/Wind Harmer
1.466
315733AD1-074 GEN2
Solar/Wind Harmer
1.466
315735AD1-075 GEN1
Solar/Wind Harmer
0.733
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
0.585
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.775
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316305AF2-043 C
Solar/Wind Harmer
0.216
316321Z2-027
Solar/Wind Harmer
0.193
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
313526AB2-022
Solar/Wind Harmer
0.193
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
972265AH1-717 GEN
Adder
4.91
3151201GRAVEL4
Adder
4.602
3151191GRAVEL3
Adder
4.544
3151211GRAVEL5
Adder
4.544
3152611GOSPORTB
Adder
0.805
3152621GOSPORTC
Adder
0.683
3152601GOSPORTA
Adder
0.63
971445AH1-216 GEN
Solar/Wind Harmer
4.395
3151081ELIZAR1
Adder
5.792
3151091ELIZAR2
Adder
5.691
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.103
3148013FISHERV
Solar/Wind Helper
0.098
3148463FAIRFLD
Solar/Wind Helper
0.118
3151931BEARGRDN S1
50/50
5.938
3151911BEARGRDN G1
50/50
4.601
3144293JTRSVLE
50/50
0.746
970119AG2-088 GEN
50/50
19.705
972003AH1-546 GEN
Solar/Wind Harmer
26.72
970937AG2-583 GEN
Solar/Wind Harmer
33.599
316322AB2-045
Solar/Wind Harmer
1.495
3146776BUCKING
Solar/Wind Harmer
-0.018
316336AC2-165 C
Solar/Wind Harmer
6.302
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.82
963171AG1-166 GEN
Solar/Wind Harmer
3.104
971563AH1-280 GEN
Solar/Wind Harmer
3.104
970685AG2-442 GEN
Solar/Wind Harmer
19.859
3143226MDLTHAN
Solar/Wind Harmer
-0.017
962491AG1-098 GEN
Solar/Wind Harmer
10.562
971377AH1-170 GEN
Solar/Wind Harmer
1.918
3147623JAMES R
Solar/Wind Harmer
0.237
315693AD1-088 GEN
Solar/Wind Harmer
7.599
316237AB2-079_GEN
Solar/Wind Harmer
0.453
3143526WINTERP
Solar/Wind Harmer
-0.071
957481AF2-042 GEN
Solar/Wind Harmer
38.757
970401AG2-262 GEN
Solar/Wind Harmer
0.805
315687AD1-152 GEN
Solar/Wind Harmer
1.355
3147043LAWRENC
Adder
0.898
971065AG2-659 GEN
Solar/Wind Harmer
5.572
316129AC1-054 GEN
Solar/Wind Harmer
0.96
971795AH1-408 GEN
Solar/Wind Harmer
7.936
3150851SPRUNCC
Adder
0.417
316003AC1-222 GEN
Solar/Wind Harmer
0.924
960081AF2-299 GEN
Solar/Wind Harmer
1.049
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
3142543TWELFTH
Solar/Wind Harmer
-0.001
970919AG2-571 GEN
Solar/Wind Harmer
2.65
970087AG2-069 GEN
Solar/Wind Harmer
7.82
316023GEN1_S
Solar/Wind Harmer
0.554
3146776BUCKING
Solar/Wind Harmer
-0.177
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.372
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.88
963191AG1-168 GEN
Solar/Wind Harmer
2.328
971741AH1-377 GEN
Solar/Wind Harmer
28.01
316034AC1-036 C
Solar/Wind Harmer
0.38
970323AG2-213 GEN
Solar/Wind Harmer
10.214
971775AH1-396 GEN
Solar/Wind Harmer
1.455
971223AH1-071 GEN
Solar/Wind Harmer
2.076
313527AB2-043 GEN
Solar/Wind Harmer
2.493
971489AH1-241 GEN
Solar/Wind Harmer
9.104
3143526WINTERP
Solar/Wind Harmer
-0.071
962561AG1-105 GEN
Solar/Wind Harmer
7.195
939181AE1-148 GEN
Solar/Wind Harmer
7.148
970099AG2-077 GEN
Solar/Wind Harmer
15.503
964791AG1-342 GEN
Solar/Wind Harmer
2.634
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970933AG2-581 GEN
Solar/Wind Harmer
9.649
316181AB2-040 GEN
Solar/Wind Harmer
1.262
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.983
3145593CAROLNA
Solar/Wind Harmer
0.073
972187AH1-678 GEN
Adder
2.2
972185AH1-677 GEN
Adder
4.302
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
316274AC1-208 GEN
Solar/Wind Harmer
0.849
316240AF1-291 C
Solar/Wind Harmer
0.235
944641AF1-129 GEN
Adder
33.028
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.793
970657AG2-426 GEN
Solar/Wind Harmer
2.358
970657AG2-426 GEN
Solar/Wind Harmer
0.493
316065AD1-022 GEN
Solar/Wind Harmer
3.643
316033AB2-134 GEN
Solar/Wind Harmer
2.34
315697AD1-025 GEN
Solar/Wind Harmer
1.468
3142366NRTHEST
Adder
0.21
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.298
316433W1029_GEN2
Solar/Wind Harmer
1.298
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316222AC1-221 GEN
Solar/Wind Harmer
0.722
3130086AYDLETT
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.75
3142956BIRDNECK
Solar/Wind Harmer
0.381
316316AC1-027 C
Solar/Wind Harmer
0.218
316236AE1-162_GEN
Solar/Wind Harmer
0.214
316036AC1-147 C
Solar/Wind Harmer
0.192
3150991CHESPKB
Adder
0.662
3150991CHESPKB
Adder
0.646
3150691DARBY 3
Adder
4.502
3150701DARBY 4
Adder
4.491
3150681DARBY 2
Adder
4.486
3150671DARBY 1
Adder
4.481
966001AG1-469 GEN
Solar/Wind Helper
0.186
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
316313AB2-026
Solar/Wind Harmer
0.868
316258AE1-075 C
Solar/Wind Harmer
0.782
316405AF2-144 C
Solar/Wind Harmer
0.825
3143336POWHATN
Solar/Wind Harmer
3.247
942461AE2-259 GEN
Solar/Wind Harmer
4.59
970909AG2-566 GEN
Solar/Wind Harmer
2.539
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.45
963181AG1-167 GEN
Solar/Wind Harmer
2.328
959311AF2-222 GEN
Solar/Wind Harmer
22.003
970257AG2-171 GEN
Solar/Wind Harmer
7.661
315785AD2-033 C
Solar/Wind Harmer
4.427
964241AG1-285 GEN
Solar/Wind Harmer
13.397
316131AB2-060 GEN
Solar/Wind Harmer
1.694
970221AG2-151 GEN
Solar/Wind Harmer
9.59
316478AD1-087 GEN
Solar/Wind Harmer
1.073
316486AD2-202 GEN
Solar/Wind Harmer
0.314
3147043LAWRENC
Solar/Wind Harmer
-0.007
3150861SPRUNCD
Adder
0.417
316248AF1-058 C
Solar/Wind Harmer
0.306
960061AF2-297 GEN
Solar/Wind Harmer
5.079
966621AG1-532 GEN
Solar/Wind Harmer
0.189
313506AB2-031 GEN
Solar/Wind Harmer
0.727
971683AH1-343 GEN
Solar/Wind Harmer
3.823
970917AG2-570 GEN
Solar/Wind Harmer
20.936
316365GEN2_N
Solar/Wind Harmer
0.554
3143096IRON208
Adder
0.298
3143096IRON208
Adder
0.292
3156081AA2-088 GEN
Solar/Wind Harmer
2.589
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
315839AE2-212 C
Solar/Wind Harmer
0.237
957521AF2-046 GEN
Solar/Wind Harmer
6.176
961681AG1-008 GEN
Solar/Wind Harmer
6.176
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
965281AG1-393 GEN
Solar/Wind Harmer
0.97
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.214
315813AE1-149 C
Solar/Wind Harmer
4.801
316463AE2-346 GEN
Solar/Wind Harmer
0.124
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.959
316317KELFORD C
Solar/Wind Harmer
0.361
3145823KELFORD
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
0.714
316083AB2-161 GEN
Solar/Wind Harmer
1.228
970661AG2-428 GEN
Solar/Wind Harmer
1.415
316327AA2-057 GEN
Solar/Wind Harmer
0.756
3145273HOLLAND
Solar/Wind Harmer
-0.006
970133AG2-095 GEN
Solar/Wind Harmer
0.837
3156021HOLLOMANSOL
Solar/Wind Harmer
0.996
315724AD1-057 GEN
Solar/Wind Harmer
0.424
970129AG2-093 GEN
Solar/Wind Harmer
4.142
3146206CASHIE
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.153
3146233WITAKRS
Solar/Wind Harmer
-0.005
315778AD1-151 GEN
Solar/Wind Harmer
6.319
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.378
971157AH1-035 GEN
Solar/Wind Harmer
0.905
315614AA2-178 GEN
Solar/Wind Harmer
0.779
3146376EDENTON
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.298
961611AG1-000B GEN
Solar/Wind Harmer
1.508
316320Y1-086
Solar/Wind Harmer
0.418
3145963POPLR C
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151221GRAVEL6
Adder
4.597
3151171GRAVELC
Adder
0.884
3144873MCLAUGH
Solar/Wind Harmer
0
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.866
3144216WINCHST
Adder
0.221
3150921YORKTN3
Adder
1.456
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3148013FISHERV
Solar/Wind Helper
0.171
316499AE2-029_GEN
Solar/Wind Helper
0.503
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.534
3147666LOUISA
Solar/Wind Helper
0.265
944581AF1-123 GEN
Solar/Wind Harmer
1.127
940641AE2-051 GEN
Solar/Wind Harmer
7.517
3143096IRON208
Adder
0.298
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.653
962571AG1-106 GEN
Solar/Wind Harmer
1.136
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
939411AE1-173 GEN
Solar/Wind Harmer
38.95
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.803
316212AC1-099_GEN
Solar/Wind Harmer
0.674
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.029
316381AD1-082 GEN
Solar/Wind Harmer
0.694
970661AG2-428 GEN
Solar/Wind Harmer
7.982
315722AD1-056 GEN
Solar/Wind Harmer
0.771
970129AG2-093 GEN
Solar/Wind Harmer
1.678
316458AB2-190 GEN2
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.827
3146233WITAKRS
Solar/Wind Harmer
-0.029
971069AG2-661 GEN
Solar/Wind Harmer
1.154
316093AE2-104_GEN
Solar/Wind Harmer
2.113
944631AF1-128 GEN
Adder
30.658
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.772
971647AH1-324 GEN
Solar/Wind Harmer
3.605
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.775
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.535
316246AF1-032 C
Solar/Wind Harmer
0.145
3145963POPLR C
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
316174AB2-169 GEN
Solar/Wind Harmer
1.097
3151171GRAVELC
Adder
0.673
316375AC2-012 GEN
Solar/Wind Harmer
2.457
3145336SMITFLD
Solar/Wind Harmer
-0.028
3150981CHESPKA
Adder
0.789
944591AF1-124 GEN
Solar/Wind Harmer
32.38
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.798
3147666LOUISA
Solar/Wind Helper
0.46
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.345
MECLTFEXP_MEC->PJM
CLTF
0.252
SIGELTFEXP_SIGE->PJM
CLTF
0.005
CPLELTFEXP_CPLE->PJM
CLTF
3.992
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.116
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.012
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.013
LAGNLTFEXP_LAGN->PJM
CLTF
1.555
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.774
TVALTFEXP_TVA->PJM
CLTF
0.758
NYPJM->LTFIMP_NY
CLTF
0.536
LGEELTFEXP_LGEE->PJM
CLTF
0.012

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:158.61 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1076.48
MW Contribution:2.18
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
5.993
3144293JTRSVLE
50/50
0.881
3151591KERR 2
50/50
0.215
970413AG2-270 GEN
50/50
9.663
3151261ROARAP2
50/50
0.069
3146776BUCKING
Solar/Wind Harmer
0.182
3146926FARMVIL
Solar/Wind Harmer
0.234
3151931BEARGRDN S1
50/50
7.734
3151911BEARGRDN G1
50/50
5.993
3144293JTRSVLE
50/50
0.881
3151601KERR 3
50/50
0.215
3151581KERR 1
50/50
0.077
3151531CLOVER1
50/50
2.214
3147043LAWRENC
50/50
0.833
3151261ROARAP2
50/50
0.071
970937AG2-583 GEN
Solar/Wind Harmer
39.544
316336AC2-165 C
Solar/Wind Harmer
0.025
972003AH1-546 GEN
Solar/Wind Harmer
26.303
316322AB2-045
Solar/Wind Harmer
0.004
3146776BUCKING
Solar/Wind Harmer
0.202
3146926FARMVIL
Solar/Wind Harmer
0.234
971377AH1-170 GEN
Solar/Wind Harmer
2.874
3147623JAMES R
Solar/Wind Harmer
0.624
963171AG1-166 GEN
Solar/Wind Harmer
1.391
971563AH1-280 GEN
Solar/Wind Harmer
2.782
970685AG2-442 GEN
Solar/Wind Harmer
17.514
962491AG1-098 GEN
Solar/Wind Harmer
8.209
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
6.543
970401AG2-262 GEN
Solar/Wind Harmer
0.652
957481AF2-042 GEN
Solar/Wind Harmer
26.84
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.856
316129AC1-054 GEN
Solar/Wind Harmer
0.33
316003AC1-222 GEN
Solar/Wind Harmer
0.002
971795AH1-408 GEN
Solar/Wind Harmer
5.259
960081AF2-299 GEN
Solar/Wind Harmer
0.593
972205AH1-687 GEN
50/50
29.229
3151611KERR 4
50/50
0.215
3151621KERR 5
50/50
0.215
3151631KERR 6
50/50
0.215
3151641KERR 7
50/50
0.215
3151541CLOVER2
50/50
2.204
3151281ROARAP4
50/50
0.069
3151281ROARAP4
50/50
0.065
971845AH1-439 GEN
Solar/Wind Harmer
22.434
970285AG2-188 GEN
Solar/Wind Harmer
37.679
315657AE1-056 GEN
Solar/Wind Harmer
9.629
946301AF1-294 GEN
Solar/Wind Harmer
5.147
961791AG1-021 GEN
Solar/Wind Harmer
2.504
970683AG2-441 GEN
Solar/Wind Harmer
15.638
970681AG2-440 GEN
Solar/Wind Harmer
12.51
270494AE1-108_GEN
Solar/Wind Harmer
2.538
3144303KENBRDG
Solar/Wind Harmer
0.165
971443AH1-215 GEN
Solar/Wind Harmer
3.431
971447AH1-217 GEN
Solar/Wind Harmer
5.812
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.256
3147173SINAI
Solar/Wind Harmer
0.087
3147243WELCO
Solar/Wind Harmer
0.055
970831AG2-522 GEN
Solar/Wind Harmer
3.614
970865AG2-541 GEN
Solar/Wind Harmer
2.528
316123AC1-075 GEN
Solar/Wind Harmer
0.087
970165AG2-112 GEN
Solar/Wind Harmer
0.513
970163AG2-111 GEN
Solar/Wind Harmer
0.49
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.232
3138266HYDRAULIC
Solar/Wind Helper
0.014
3138266HYDRAULIC
Solar/Wind Helper
0.009
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
970909AG2-566 GEN
Solar/Wind Harmer
3.007
3147133PAMPLIN
Solar/Wind Harmer
0.876
971193AH1-056 GEN
Solar/Wind Harmer
16.999
970221AG2-151 GEN
Solar/Wind Harmer
14.368
963181AG1-167 GEN
Solar/Wind Harmer
1.043
959311AF2-222 GEN
Solar/Wind Harmer
19.082
970257AG2-171 GEN
Solar/Wind Harmer
6.613
315785AD2-033 C
Solar/Wind Harmer
1.59
964241AG1-285 GEN
Solar/Wind Harmer
11.084
316131AB2-060 GEN
Solar/Wind Harmer
0.467
316478AD1-087 GEN
Solar/Wind Harmer
0.361
316486AD2-202 GEN
Solar/Wind Harmer
0.106
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.73
3147043LAWRENC
Solar/Wind Harmer
0.052
958131AF2-107 GEN
Solar/Wind Harmer
2.449
971683AH1-343 GEN
Solar/Wind Harmer
2.857
313506AB2-031 GEN
Solar/Wind Harmer
0.184
3144293JTRSVLE
50/50
0.881
3144293JTRSVLE
50/50
0.742
970535AG2-341 GEN
50/50
2.183
3152661PLYWOOD A
50/50
0.212
3146776BUCKING
Solar/Wind Harmer
2.017
3146776BUCKING
Solar/Wind Harmer
0.163
970301AG2-198 GEN
Solar/Wind Harmer
12.027
3147133PAMPLIN
Solar/Wind Harmer
0.279
3147133PAMPLIN
Solar/Wind Harmer
0.223
971489AH1-241 GEN
Solar/Wind Harmer
14.368
958211AF2-115 GEN
Solar/Wind Harmer
3.13
963191AG1-168 GEN
Solar/Wind Harmer
1.043
971741AH1-377 GEN
Solar/Wind Harmer
24.65
316034AC1-036 C
Solar/Wind Harmer
0.015
970323AG2-213 GEN
Solar/Wind Harmer
8.817
971775AH1-396 GEN
Solar/Wind Harmer
0.331
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
5.577
315821AE2-092 GEN
Solar/Wind Harmer
0.007
939181AE1-148 GEN
Solar/Wind Harmer
5.338
964791AG1-342 GEN
Solar/Wind Harmer
2.134
3146843MT LREL
Solar/Wind Harmer
0.111
3146843MT LREL
Solar/Wind Harmer
0.111
970099AG2-077 GEN
Solar/Wind Harmer
10.736
970933AG2-581 GEN
Solar/Wind Harmer
5.58
316181AB2-040 GEN
Solar/Wind Harmer
0.086
942751AE2-291 GEN
Solar/Wind Harmer
3.114
3145593CAROLNA
Solar/Wind Harmer
0.057
3145593CAROLNA
Solar/Wind Harmer
0.057
966811AG1-552 GEN
Solar/Wind Harmer
0.619
3145593CAROLNA
Solar/Wind Harmer
0.071
966001AG1-469 GEN
Solar/Wind Helper
0.14
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.534
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.133
MECLTFEXP_MEC->PJM
CLTF
0.325
SIGELTFEXP_SIGE->PJM
CLTF
0.008
CPLELTFEXP_CPLE->PJM
CLTF
3.067
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.792
LAGNLTFEXP_LAGN->PJM
CLTF
1.359
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.117
TVALTFEXP_TVA->PJM
CLTF
0.671
NYPJM->LTFIMP_NY
CLTF
0.488
LGEELTFEXP_LGEE->PJM
CLTF
0.069
WECLTFEXP_WEC->PJM
CLTF
0.029

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 242T2027_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 242T2027_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.82 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1235.22
MW Contribution:2.18
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
7.734
3151911BEARGRDN G1
50/50
5.993
3144293JTRSVLE
50/50
0.881
970937AG2-583 GEN
Solar/Wind Harmer
52.066
316336AC2-165 C
Solar/Wind Harmer
12.588
972003AH1-546 GEN
Solar/Wind Harmer
34.691
316322AB2-045
Solar/Wind Harmer
1.907
3146776BUCKING
Solar/Wind Harmer
-0.022
3146926FARMVIL
Solar/Wind Harmer
-0.026
971377AH1-170 GEN
Solar/Wind Harmer
3.783
3147623JAMES R
Solar/Wind Harmer
0.468
963171AG1-166 GEN
Solar/Wind Harmer
3.664
971563AH1-280 GEN
Solar/Wind Harmer
3.664
970685AG2-442 GEN
Solar/Wind Harmer
23.061
962491AG1-098 GEN
Solar/Wind Harmer
10.808
316237AB2-079_GEN
Solar/Wind Harmer
0.475
315693AD1-088 GEN
Solar/Wind Harmer
7.658
970401AG2-262 GEN
Solar/Wind Harmer
0.815
957481AF2-042 GEN
Solar/Wind Harmer
35.339
315687AD1-152 GEN
Solar/Wind Harmer
1.264
971065AG2-659 GEN
Solar/Wind Harmer
5.078
316129AC1-054 GEN
Solar/Wind Harmer
0.863
3147043LAWRENC
Adder
0.785
316003AC1-222 GEN
Solar/Wind Harmer
0.902
3144293JTRSVLE
50/50
0.881
3144293JTRSVLE
50/50
0.742
970535AG2-341 GEN
50/50
2.183
3146776BUCKING
Solar/Wind Harmer
-0.226
3146776BUCKING
Solar/Wind Harmer
-0.018
970301AG2-198 GEN
Solar/Wind Harmer
15.836
3147133PAMPLIN
Solar/Wind Harmer
-0.031
3147133PAMPLIN
Solar/Wind Harmer
-0.025
971489AH1-241 GEN
Solar/Wind Harmer
17.959
958211AF2-115 GEN
Solar/Wind Harmer
4.579
963191AG1-168 GEN
Solar/Wind Harmer
2.748
971741AH1-377 GEN
Solar/Wind Harmer
32.456
316034AC1-036 C
Solar/Wind Harmer
0.432
970323AG2-213 GEN
Solar/Wind Harmer
11.609
971775AH1-396 GEN
Solar/Wind Harmer
1.653
313527AB2-043 GEN
Solar/Wind Harmer
2.63
962561AG1-105 GEN
Solar/Wind Harmer
7.343
315821AE2-092 GEN
Solar/Wind Harmer
2.71
939181AE1-148 GEN
Solar/Wind Harmer
7.029
964791AG1-342 GEN
Solar/Wind Harmer
2.668
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.136
970933AG2-581 GEN
Solar/Wind Harmer
7.348
316181AB2-040 GEN
Solar/Wind Harmer
0.933
942751AE2-291 GEN
Solar/Wind Harmer
4.1
3145593CAROLNA
Solar/Wind Harmer
-0.006
3145593CAROLNA
Solar/Wind Harmer
-0.006
966811AG1-552 GEN
Solar/Wind Harmer
0.721
3145593CAROLNA
Solar/Wind Harmer
0.053
966001AG1-469 GEN
Solar/Wind Helper
0.14
971795AH1-408 GEN
Solar/Wind Harmer
6.647
960081AF2-299 GEN
Solar/Wind Harmer
0.78
972205AH1-687 GEN
50/50
29.229
971845AH1-439 GEN
Solar/Wind Harmer
29.538
970285AG2-188 GEN
Solar/Wind Harmer
46.824
315657AE1-056 GEN
Solar/Wind Harmer
11.763
946301AF1-294 GEN
Solar/Wind Harmer
7.51
961791AG1-021 GEN
Solar/Wind Harmer
3.664
970683AG2-441 GEN
Solar/Wind Harmer
20.59
970681AG2-440 GEN
Solar/Wind Harmer
16.472
270494AE1-108_GEN
Solar/Wind Harmer
6.187
3144303KENBRDG
Solar/Wind Harmer
-0.019
971443AH1-215 GEN
Solar/Wind Harmer
4.518
971447AH1-217 GEN
Solar/Wind Harmer
7.652
316239AB2-077_GEN
Solar/Wind Harmer
0.475
316238AB2-078_GEN
Solar/Wind Harmer
0.475
316118AC1-105 GEN
Solar/Wind Harmer
0.766
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
970831AG2-522 GEN
Solar/Wind Harmer
4.758
970865AG2-541 GEN
Solar/Wind Harmer
3.329
316123AC1-075 GEN
Solar/Wind Harmer
0.768
970165AG2-112 GEN
Solar/Wind Harmer
0.676
970163AG2-111 GEN
Solar/Wind Harmer
0.645
946281AF1-292 GEN
Solar/Wind Harmer
0.155
316087AB2-174 GEN
Solar/Wind Harmer
0.965
3137643SOCKMAN
Solar/Wind Harmer
-0.026
3138266HYDRAULIC
Solar/Wind Helper
0.014
3138266HYDRAULIC
Solar/Wind Helper
0.009
3151921BEARGRDN G2
50/50
5.993
3144293JTRSVLE
50/50
0.881
3146776BUCKING
Solar/Wind Harmer
-0.02
3146926FARMVIL
Solar/Wind Harmer
-0.026
942461AE2-259 GEN
Solar/Wind Harmer
5.592
970909AG2-566 GEN
Solar/Wind Harmer
3.007
3147133PAMPLIN
Solar/Wind Harmer
-0.098
971193AH1-056 GEN
Solar/Wind Harmer
19.605
970221AG2-151 GEN
Solar/Wind Harmer
18.917
963181AG1-167 GEN
Solar/Wind Harmer
2.748
959311AF2-222 GEN
Solar/Wind Harmer
25.175
970257AG2-171 GEN
Solar/Wind Harmer
8.707
315785AD2-033 C
Solar/Wind Harmer
4.981
964241AG1-285 GEN
Solar/Wind Harmer
14.595
316131AB2-060 GEN
Solar/Wind Harmer
1.799
316478AD1-087 GEN
Solar/Wind Harmer
1.005
316486AD2-202 GEN
Solar/Wind Harmer
0.294
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.911
3147043LAWRENC
Solar/Wind Harmer
-0.006
958131AF2-107 GEN
Solar/Wind Harmer
3.26
971683AH1-343 GEN
Solar/Wind Harmer
3.762
966621AG1-532 GEN
Solar/Wind Harmer
0.141
313506AB2-031 GEN
Solar/Wind Harmer
0.538
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.534
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.133
MECLTFEXP_MEC->PJM
CLTF
0.325
SIGELTFEXP_SIGE->PJM
CLTF
0.008
CPLELTFEXP_CPLE->PJM
CLTF
3.067
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.792
LAGNLTFEXP_LAGN->PJM
CLTF
1.359
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.117
TVALTFEXP_TVA->PJM
CLTF
0.671
NYPJM->LTFIMP_NY
CLTF
0.488
LGEELTFEXP_LGEE->PJM
CLTF
0.069
WECLTFEXP_WEC->PJM
CLTF
0.029

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B3_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: BREMO B3_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:130.0 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1079.04
MW Contribution:2.13
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.78
3144293JTRSVLE
50/50
0.657
970535AG2-341 GEN
50/50
2.128
3146776BUCKING
Solar/Wind Harmer
-0.191
3146776BUCKING
Solar/Wind Harmer
-0.016
970301AG2-198 GEN
Solar/Wind Harmer
14.025
3147133PAMPLIN
Solar/Wind Harmer
-0.028
3147133PAMPLIN
Solar/Wind Harmer
-0.022
958211AF2-115 GEN
Solar/Wind Harmer
4.056
963191AG1-168 GEN
Solar/Wind Harmer
2.434
971741AH1-377 GEN
Solar/Wind Harmer
29.148
316034AC1-036 C
Solar/Wind Harmer
0.391
970323AG2-213 GEN
Solar/Wind Harmer
10.518
971775AH1-396 GEN
Solar/Wind Harmer
1.498
313527AB2-043 GEN
Solar/Wind Harmer
2.495
962561AG1-105 GEN
Solar/Wind Harmer
7.049
939181AE1-148 GEN
Solar/Wind Harmer
6.984
971223AH1-071 GEN
Solar/Wind Harmer
1.533
964791AG1-342 GEN
Solar/Wind Harmer
2.568
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.91
3143526WINTERP
Solar/Wind Harmer
-0.053
970933AG2-581 GEN
Solar/Wind Harmer
8.884
316181AB2-040 GEN
Solar/Wind Harmer
1.151
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.893
3145593CAROLNA
Solar/Wind Harmer
0.066
3145783HORNRTN
Solar/Wind Harmer
0.925
3145783HORNRTN
Solar/Wind Harmer
0.74
3145783HORNRTN
Solar/Wind Harmer
0.231
3145783HORNRTN
Solar/Wind Harmer
0.092
316426AA2-053 GEN
Solar/Wind Harmer
0.779
972187AH1-678 GEN
Adder
1.94
972185AH1-677 GEN
Adder
3.777
316274AC1-208 GEN
Solar/Wind Harmer
0.758
3144356SAPONY
Solar/Wind Harmer
0.244
3145893MURPHYS
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145796HORNRTN
Solar/Wind Harmer
-0.021
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
315742AE1-103 GEN
Solar/Wind Harmer
0.691
316222AC1-221 GEN
Solar/Wind Harmer
0.652
316240AF1-291 C
Solar/Wind Harmer
0.193
944641AF1-129 GEN
Adder
26.988
970657AG2-426 GEN
Solar/Wind Harmer
1.987
970657AG2-426 GEN
Solar/Wind Harmer
0.415
316065AD1-022 GEN
Solar/Wind Harmer
3.168
315821AE2-092 GEN
Solar/Wind Helper
6.532
966001AG1-469 GEN
Solar/Wind Helper
0.168
3132123MT JACKSON
Solar/Wind Helper
0.376
3151931BEARGRDN S1
50/50
6.456
3151911BEARGRDN G1
50/50
5.002
3144293JTRSVLE
50/50
0.78
972003AH1-546 GEN
Solar/Wind Harmer
29.014
970937AG2-583 GEN
Solar/Wind Harmer
35.582
316322AB2-045
Solar/Wind Harmer
1.612
3146776BUCKING
Solar/Wind Harmer
-0.019
3146926FARMVIL
Solar/Wind Harmer
-0.022
316336AC2-165 C
Solar/Wind Harmer
6.353
3143336POWHATN
Solar/Wind Harmer
3.74
963171AG1-166 GEN
Solar/Wind Harmer
3.245
971563AH1-280 GEN
Solar/Wind Harmer
3.245
970685AG2-442 GEN
Solar/Wind Harmer
20.625
962491AG1-098 GEN
Solar/Wind Harmer
10.531
315693AD1-088 GEN
Solar/Wind Harmer
7.538
316237AB2-079_GEN
Solar/Wind Harmer
0.452
3143226MDLTHAN
Solar/Wind Harmer
-0.012
970401AG2-262 GEN
Solar/Wind Harmer
0.785
957481AF2-042 GEN
Solar/Wind Harmer
37.275
315687AD1-152 GEN
Solar/Wind Harmer
1.296
971065AG2-659 GEN
Solar/Wind Harmer
5.329
3147043LAWRENC
Adder
0.854
316129AC1-054 GEN
Solar/Wind Harmer
0.915
3143526WINTERP
Solar/Wind Harmer
-0.053
971795AH1-408 GEN
Solar/Wind Harmer
7.462
316003AC1-222 GEN
Solar/Wind Harmer
0.864
960081AF2-299 GEN
Solar/Wind Harmer
0.959
3150851SPRUNCC
Adder
0.323
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.095
970919AG2-571 GEN
Solar/Wind Harmer
2.334
970087AG2-069 GEN
Solar/Wind Harmer
6.886
316023GEN1_S
Solar/Wind Harmer
0.488
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.463
962571AG1-106 GEN
Solar/Wind Harmer
1.005
3145893MURPHYS
Solar/Wind Harmer
-0.028
3145893MURPHYS
Solar/Wind Harmer
0.207
316212AC1-099_GEN
Solar/Wind Harmer
0.6
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.007
940641AE2-051 GEN
Solar/Wind Harmer
6.428
3146173TUNIS
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
3145683EARLEYS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
33.3
315722AD1-056 GEN
Solar/Wind Harmer
0.679
3146233WITAKRS
Solar/Wind Harmer
-0.026
3143096IRON208
Adder
0.238
970659AG2-427 GEN
Solar/Wind Harmer
3.387
316381AD1-082 GEN
Solar/Wind Harmer
0.584
315671AE2-027_GEN
Solar/Wind Harmer
4.776
3146206CASHIE
Solar/Wind Harmer
-0.006
971547AH1-271 GEN
Solar/Wind Harmer
1.59
970661AG2-428 GEN
Solar/Wind Harmer
6.738
3147983MERCK5
Solar/Wind Helper
0.064
972205AH1-687 GEN
50/50
24.399
971845AH1-439 GEN
Solar/Wind Harmer
25.003
970285AG2-188 GEN
Solar/Wind Harmer
39.727
315657AE1-056 GEN
Solar/Wind Harmer
10.359
946301AF1-294 GEN
Solar/Wind Harmer
6.652
961791AG1-021 GEN
Solar/Wind Harmer
3.245
970683AG2-441 GEN
Solar/Wind Harmer
18.415
970681AG2-440 GEN
Solar/Wind Harmer
14.732
3144303KENBRDG
Solar/Wind Harmer
-0.017
971443AH1-215 GEN
Solar/Wind Harmer
4.098
316239AB2-077_GEN
Solar/Wind Harmer
0.452
316238AB2-078_GEN
Solar/Wind Harmer
0.452
316118AC1-105 GEN
Solar/Wind Harmer
0.743
316233AE1-074 FULL
Solar/Wind Harmer
0.277
971281AH1-106 GEN
Solar/Wind Harmer
1.674
971283AH1-107 GEN
Solar/Wind Harmer
1.674
970831AG2-522 GEN
Solar/Wind Harmer
5.097
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
946281AF1-292 GEN
Solar/Wind Harmer
0.191
971967AH1-528 GEN
Solar/Wind Harmer
15.717
316087AB2-174 GEN
Solar/Wind Harmer
1.189
3137643SOCKMAN
Solar/Wind Harmer
-0.032
971285AH1-108 GEN
Adder
0.528
315607AA1-063A GEN
Solar/Wind Harmer
0.769
3146043SEABORD
Solar/Wind Harmer
-0.008
970673AG2-436 GEN
Solar/Wind Harmer
15.733
970673AG2-436 GEN
Solar/Wind Harmer
7.966
970865AG2-541 GEN
Solar/Wind Harmer
3.042
941031AE2-094 GEN
Solar/Wind Harmer
13.777
944011AF1-069 GEN
Solar/Wind Harmer
4.317
970085AG2-068 GEN
Solar/Wind Harmer
4.591
970581AG2-369 GEN
Solar/Wind Harmer
3.948
965291AG1-394 GEN
Solar/Wind Harmer
0.631
315814AE2-033 C
Solar/Wind Harmer
6.526
316315AB2-025 C
Solar/Wind Harmer
0.189
315652AC1-086 GEN
Solar/Wind Harmer
7.864
316318V4-068
Solar/Wind Harmer
0.174
3145893MURPHYS
Solar/Wind Harmer
-0.019
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.027
3145513AHOSKIE
Solar/Wind Harmer
0.059
961941AG1-037 GEN
Solar/Wind Harmer
0.051
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
3143316POE
Solar/Wind Harmer
-0.026
316319Z2-044 C
Solar/Wind Harmer
0.356
3146206CASHIE
Solar/Wind Harmer
-0.006
970601AG2-382 GEN
Solar/Wind Harmer
2.783
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.164
3148013FISHERV
Solar/Wind Helper
0.157
3148463FAIRFLD
Solar/Wind Helper
0.142
3151921BEARGRDN G2
50/50
5.002
3144293JTRSVLE
50/50
0.78
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.022
942461AE2-259 GEN
Solar/Wind Harmer
4.861
316313AB2-026
Solar/Wind Harmer
0.85
316258AE1-075 C
Solar/Wind Harmer
0.765
316405AF2-144 C
Solar/Wind Harmer
0.807
3143336POWHATN
Solar/Wind Harmer
3.179
970909AG2-566 GEN
Solar/Wind Harmer
2.663
3147133PAMPLIN
Solar/Wind Harmer
-0.086
971193AH1-056 GEN
Solar/Wind Harmer
17.264
963181AG1-167 GEN
Solar/Wind Harmer
2.434
959311AF2-222 GEN
Solar/Wind Harmer
22.717
970257AG2-171 GEN
Solar/Wind Harmer
7.889
315785AD2-033 C
Solar/Wind Harmer
4.54
964241AG1-285 GEN
Solar/Wind Harmer
13.569
316131AB2-060 GEN
Solar/Wind Harmer
1.699
316478AD1-087 GEN
Solar/Wind Harmer
1.036
316486AD2-202 GEN
Solar/Wind Harmer
0.304
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.29
960061AF2-297 GEN
Solar/Wind Harmer
4.81
966621AG1-532 GEN
Solar/Wind Harmer
0.173
313506AB2-031 GEN
Solar/Wind Harmer
0.663
971683AH1-343 GEN
Solar/Wind Harmer
3.528
3150861SPRUNCD
Adder
0.323
970917AG2-570 GEN
Solar/Wind Harmer
18.441
316365GEN2_N
Solar/Wind Harmer
0.488
3156081AA2-088 GEN
Solar/Wind Harmer
2.294
3146263WOODLND
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.049
3145893MURPHYS
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.463
961681AG1-008 GEN
Solar/Wind Harmer
5.463
316210AC1-098 GEN
Solar/Wind Harmer
1.08
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316463AE2-346 GEN
Solar/Wind Harmer
0.11
316140AB2-099
Solar/Wind Harmer
0.046
962331AG1-082 GEN
Solar/Wind Harmer
0.846
316317KELFORD C
Solar/Wind Harmer
0.319
3145823KELFORD
Solar/Wind Harmer
-0.007
316327AA2-057 GEN
Solar/Wind Harmer
0.671
315724AD1-057 GEN
Solar/Wind Harmer
0.374
315839AE2-212 C
Solar/Wind Harmer
0.195
3145273HOLLAND
Solar/Wind Harmer
-0.005
3156021HOLLOMANSOL
Solar/Wind Harmer
0.87
3146233WITAKRS
Solar/Wind Harmer
0.135
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
4.015
965281AG1-393 GEN
Solar/Wind Harmer
0.8
3143096IRON208
Adder
0.238
3143096IRON208
Adder
0.233
970659AG2-427 GEN
Solar/Wind Harmer
0.6
316083AB2-161 GEN
Solar/Wind Harmer
1.033
3146206CASHIE
Solar/Wind Harmer
-0.006
316283AC2-100 C
Solar/Wind Harmer
0.599
970661AG2-428 GEN
Solar/Wind Harmer
1.194
3148013FISHERV
Solar/Wind Helper
0.273
316499AE2-029_GEN
Solar/Wind Helper
0.588
315616AA1-038_C
Solar/Wind Helper
0.641
3132273ORANGE
Solar/Wind Helper
0.023
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.127
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.049
CPLELTFEXP_CPLE->PJM
CLTF
3.425
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.931
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.181
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.543
LAGNLTFEXP_LAGN->PJM
CLTF
0.85
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.313
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.396
NYPJM->LTFIMP_NY
CLTF
0.338

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.92 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:773.16
MW Contribution:1.89
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
21.569
316303AF2-085
50/50
1.694
3151541CLOVER2
50/50
2.007
3151611KERR 4
50/50
0.192
3151621KERR 5
50/50
0.192
3151631KERR 6
50/50
0.192
3151641KERR 7
50/50
0.192
3151281ROARAP4
50/50
0.075
3151281ROARAP4
50/50
0.07
971285AH1-108 GEN
50/50
0.486
963041AG1-153 GEN
50/50
1.59
315244AE2-183_ST
50/50
1.681
971845AH1-439 GEN
Solar/Wind Harmer
16.786
970285AG2-188 GEN
Solar/Wind Harmer
28.258
315657AE1-056 GEN
Solar/Wind Harmer
7.498
946301AF1-294 GEN
Solar/Wind Harmer
4.032
961791AG1-021 GEN
Solar/Wind Harmer
1.962
970683AG2-441 GEN
Solar/Wind Harmer
12.373
970681AG2-440 GEN
Solar/Wind Harmer
9.898
3144303KENBRDG
Solar/Wind Harmer
0.132
971443AH1-215 GEN
Solar/Wind Harmer
2.755
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Harmer
1.107
316118AC1-105 GEN
Solar/Wind Harmer
0.222
970831AG2-522 GEN
Solar/Wind Harmer
3.422
316233AE1-074 FULL
Solar/Wind Harmer
0.064
971281AH1-106 GEN
Solar/Wind Harmer
1.107
971283AH1-107 GEN
Solar/Wind Harmer
1.107
3147173SINAI
Solar/Wind Harmer
0.077
3147243WELCO
Solar/Wind Harmer
0.048
316087AB2-174 GEN
Solar/Wind Harmer
0.002
971967AH1-528 GEN
Solar/Wind Harmer
10.427
3137643SOCKMAN
Solar/Wind Harmer
0.253
970865AG2-541 GEN
Solar/Wind Harmer
2.127
315607AA1-063A GEN
Solar/Wind Harmer
0.122
3146043SEABORD
Solar/Wind Harmer
0.059
970673AG2-436 GEN
Solar/Wind Harmer
12.427
970673AG2-436 GEN
Solar/Wind Harmer
8.285
970085AG2-068 GEN
Solar/Wind Harmer
3.058
970581AG2-369 GEN
Solar/Wind Harmer
2.63
941031AE2-094 GEN
Solar/Wind Harmer
10.513
944011AF1-069 GEN
Solar/Wind Harmer
3.435
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.108
3148013FISHERV
Solar/Wind Helper
0.103
3148463FAIRFLD
Solar/Wind Helper
0.124
3151921BEARGRDN G2
50/50
4.422
3144293JTRSVLE
50/50
0.69
970413AG2-270 GEN
50/50
8.802
3151591KERR 2
50/50
0.192
3151261ROARAP2
50/50
0.076
3150861SPRUNCD
50/50
0.297
3151031BRUNSWICKG2
50/50
0.785
3146776BUCKING
Solar/Wind Harmer
0.136
3146926FARMVIL
Solar/Wind Harmer
0.178
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.156
316258AE1-075 C
Solar/Wind Harmer
0.187
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.737
970909AG2-566 GEN
Solar/Wind Harmer
2.353
3147133PAMPLIN
Solar/Wind Harmer
0.682
971193AH1-056 GEN
Solar/Wind Harmer
13.238
963181AG1-167 GEN
Solar/Wind Harmer
0.817
959311AF2-222 GEN
Solar/Wind Harmer
15.236
970257AG2-171 GEN
Solar/Wind Harmer
5.302
315785AD2-033 C
Solar/Wind Harmer
1.283
964241AG1-285 GEN
Solar/Wind Harmer
9.125
316131AB2-060 GEN
Solar/Wind Harmer
0.39
970221AG2-151 GEN
Solar/Wind Harmer
6.362
316478AD1-087 GEN
Solar/Wind Harmer
0.328
316486AD2-202 GEN
Solar/Wind Harmer
0.096
3147043LAWRENC
Solar/Wind Harmer
0.05
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.274
971683AH1-343 GEN
Solar/Wind Harmer
2.442
313506AB2-031 GEN
Solar/Wind Harmer
0.2
970917AG2-570 GEN
Solar/Wind Harmer
5.117
316365GEN2_N
Solar/Wind Harmer
0.127
3148013FISHERV
Solar/Wind Helper
0.18
316499AE2-029_GEN
Solar/Wind Helper
0.518
315616AA1-038_C
Solar/Wind Helper
0.562
3132273ORANGE
Solar/Wind Helper
0.024
3151931BEARGRDN S1
50/50
5.707
3151911BEARGRDN G1
50/50
4.422
3144293JTRSVLE
50/50
0.69
970119AG2-088 GEN
50/50
12.707
3151531CLOVER1
50/50
2.017
3151601KERR 3
50/50
0.192
3151581KERR 1
50/50
0.069
3147043LAWRENC
50/50
0.8
3151261ROARAP2
50/50
0.077
3150851SPRUNCC
50/50
0.297
3151051BRUNSWICKS1
50/50
1.63
3151021BRUNSWICKG1
50/50
0.785
971451AH1-221 GEN
50/50
2.385
315243AE2-183_GT3
50/50
0.972
972003AH1-546 GEN
Solar/Wind Harmer
19.447
970937AG2-583 GEN
Solar/Wind Harmer
23.874
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.151
3146926FARMVIL
Solar/Wind Harmer
0.178
316336AC2-165 C
Solar/Wind Harmer
0.011
3143336POWHATN
Solar/Wind Harmer
4.396
963171AG1-166 GEN
Solar/Wind Harmer
1.09
971563AH1-280 GEN
Solar/Wind Harmer
2.18
970685AG2-442 GEN
Solar/Wind Harmer
13.857
962491AG1-098 GEN
Solar/Wind Harmer
7.06
971377AH1-170 GEN
Solar/Wind Harmer
1.272
3147623JAMES R
Solar/Wind Harmer
0.276
315693AD1-088 GEN
Solar/Wind Harmer
5.685
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Harmer
0.095
970401AG2-262 GEN
Solar/Wind Harmer
0.559
957481AF2-042 GEN
Solar/Wind Harmer
24.966
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.579
316129AC1-054 GEN
Solar/Wind Harmer
0.309
3143526WINTERP
Solar/Wind Harmer
0.415
971795AH1-408 GEN
Solar/Wind Harmer
5.206
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.641
3145783HORNRTN
Solar/Wind Harmer
0.061
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
2.047
970087AG2-069 GEN
Solar/Wind Harmer
4.587
316023GEN1_S
Solar/Wind Harmer
0.127
3147983MERCK5
Solar/Wind Helper
0.057
3144293JTRSVLE
50/50
0.69
3144293JTRSVLE
50/50
0.581
970535AG2-341 GEN
50/50
1.885
3152661PLYWOOD A
50/50
0.185
3151041BRUNSWICKG3
50/50
0.785
972187AH1-678 GEN
50/50
1.802
315242AE2-183_GT2
50/50
0.972
315241AE2-183_GT1
50/50
0.966
972185AH1-677 GEN
50/50
3.505
970533AG2-339 GEN
50/50
5.074
970531AG2-338 GEN
50/50
2.029
3146776BUCKING
Solar/Wind Harmer
1.508
3146776BUCKING
Solar/Wind Harmer
0.122
970301AG2-198 GEN
Solar/Wind Harmer
9.412
3147133PAMPLIN
Solar/Wind Harmer
0.217
3147133PAMPLIN
Solar/Wind Harmer
0.174
958211AF2-115 GEN
Solar/Wind Harmer
2.452
963191AG1-168 GEN
Solar/Wind Harmer
0.817
971741AH1-377 GEN
Solar/Wind Harmer
19.558
316034AC1-036 C
Solar/Wind Harmer
0.012
970323AG2-213 GEN
Solar/Wind Harmer
7.069
971775AH1-396 GEN
Solar/Wind Harmer
0.265
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971489AH1-241 GEN
Solar/Wind Harmer
6.362
962561AG1-105 GEN
Solar/Wind Harmer
4.763
939181AE1-148 GEN
Solar/Wind Harmer
4.697
971223AH1-071 GEN
Solar/Wind Harmer
1.017
964791AG1-342 GEN
Solar/Wind Harmer
1.83
3146843MT LREL
Solar/Wind Harmer
0.095
3146843MT LREL
Solar/Wind Harmer
0.095
970099AG2-077 GEN
Solar/Wind Harmer
9.986
3143526WINTERP
Solar/Wind Harmer
0.415
970933AG2-581 GEN
Solar/Wind Harmer
5.925
316181AB2-040 GEN
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.062
3145593CAROLNA
Solar/Wind Harmer
0.062
966811AG1-552 GEN
Solar/Wind Harmer
0.675
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.086
3145783HORNRTN
Solar/Wind Harmer
0.869
3145783HORNRTN
Solar/Wind Harmer
0.271
3145783HORNRTN
Solar/Wind Harmer
0.109
316426AA2-053 GEN
Solar/Wind Harmer
0.204
966001AG1-469 GEN
Solar/Wind Helper
0.174
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.208
CPLELTFEXP_CPLE->PJM
CLTF
3.08
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.625
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.118
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.349
LAGNLTFEXP_LAGN->PJM
CLTF
0.897
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.783
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.427
NYPJM->LTFIMP_NY
CLTF
0.345

Details for 6BREMO-AG2-583 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.12 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:946.03
MW Contribution:1.3
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.898
3151911BEARGRDN G1
50/50
4.57
3144293JTRSVLE
50/50
0.618
3151601KERR 3
50/50
0.12
3151581KERR 1
50/50
0.043
972003AH1-546 GEN
Solar/Wind Harmer
20.008
971377AH1-170 GEN
Solar/Wind Harmer
4.662
3147623JAMES R
Solar/Wind Harmer
1.013
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.151
3146926FARMVIL
Solar/Wind Harmer
0.171
963171AG1-166 GEN
Solar/Wind Harmer
0.976
971563AH1-280 GEN
Solar/Wind Harmer
1.952
970685AG2-442 GEN
Solar/Wind Harmer
12.103
316237AB2-079_GEN
Solar/Wind Harmer
0.001
962491AG1-098 GEN
Solar/Wind Harmer
4.891
315693AD1-088 GEN
Solar/Wind Harmer
3.821
970401AG2-262 GEN
Solar/Wind Harmer
0.396
962751AG1-124 GEN
Solar/Wind Harmer
2.983
316336AC2-165 C
Solar/Wind Helper
3.978
3143226MDLTHAN
Solar/Wind Helper
0.214
3143526WINTERP
Solar/Wind Helper
0.904
3151921BEARGRDN G2
50/50
4.57
3144293JTRSVLE
50/50
0.618
966251AG1-494 GEN
50/50
1.545
3151591KERR 2
50/50
0.12
970221AG2-151 GEN
Solar/Wind Harmer
23.308
3146776BUCKING
Solar/Wind Harmer
0.136
3146926FARMVIL
Solar/Wind Harmer
0.171
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
2.11
3147133PAMPLIN
Solar/Wind Harmer
0.62
971193AH1-056 GEN
Solar/Wind Harmer
12.029
963181AG1-167 GEN
Solar/Wind Harmer
0.732
959311AF2-222 GEN
Solar/Wind Harmer
13.003
958131AF2-107 GEN
Solar/Wind Harmer
4.145
970257AG2-171 GEN
Solar/Wind Harmer
4.477
315785AD2-033 C
Solar/Wind Harmer
1.066
964241AG1-285 GEN
Solar/Wind Harmer
7.188
316131AB2-060 GEN
Solar/Wind Harmer
0.295
316313AB2-026
Solar/Wind Helper
0.958
316258AE1-075 C
Solar/Wind Helper
0.862
316405AF2-144 C
Solar/Wind Helper
0.719
972205AH1-687 GEN
50/50
22.289
3151611KERR 4
50/50
0.12
3151621KERR 5
50/50
0.12
3151631KERR 6
50/50
0.12
3151641KERR 7
50/50
0.12
971447AH1-217 GEN
Solar/Wind Harmer
12.416
971845AH1-439 GEN
Solar/Wind Harmer
16.793
970285AG2-188 GEN
Solar/Wind Harmer
28.117
270494AE1-108_GEN
Solar/Wind Harmer
4.14
315657AE1-056 GEN
Solar/Wind Harmer
6.813
946301AF1-294 GEN
Solar/Wind Harmer
3.611
961791AG1-021 GEN
Solar/Wind Harmer
1.757
970683AG2-441 GEN
Solar/Wind Harmer
10.806
970681AG2-440 GEN
Solar/Wind Harmer
8.645
3144303KENBRDG
Solar/Wind Harmer
0.112
971443AH1-215 GEN
Solar/Wind Harmer
2.318
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.153
316233AE1-074 FULL
Solar/Wind Helper
0.266
3144293JTRSVLE
50/50
0.618
3144293JTRSVLE
50/50
0.52
970535AG2-341 GEN
50/50
1.297
971489AH1-241 GEN
Solar/Wind Harmer
23.308
3146776BUCKING
Solar/Wind Harmer
1.512
3146776BUCKING
Solar/Wind Harmer
0.122
315821AE2-092 GEN
Solar/Wind Harmer
0.018
970301AG2-198 GEN
Solar/Wind Harmer
8.441
3147133PAMPLIN
Solar/Wind Harmer
0.197
3147133PAMPLIN
Solar/Wind Harmer
0.158
958211AF2-115 GEN
Solar/Wind Harmer
2.196
963191AG1-168 GEN
Solar/Wind Harmer
0.732
971741AH1-377 GEN
Solar/Wind Harmer
16.934
316034AC1-036 C
Solar/Wind Harmer
0.01
970323AG2-213 GEN
Solar/Wind Harmer
5.97
971775AH1-396 GEN
Solar/Wind Harmer
0.224
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.408
964791AG1-342 GEN
Solar/Wind Harmer
1.297
3146843MT LREL
Solar/Wind Harmer
0.067
3146843MT LREL
Solar/Wind Harmer
0.067
939181AE1-148 GEN
Solar/Wind Harmer
3.054
3143526WINTERP
Solar/Wind Helper
0.904
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.841
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.476
MECLTFEXP_MEC->PJM
CLTF
0.813
SIGELTFEXP_SIGE->PJM
CLTF
0.026
CPLELTFEXP_CPLE->PJM
CLTF
1.292
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.85
LAGNLTFEXP_LAGN->PJM
CLTF
1.363
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.179
TVALTFEXP_TVA->PJM
CLTF
0.699
NYPJM->LTFIMP_NY
CLTF
0.404
LGEELTFEXP_LGEE->PJM
CLTF
0.328
WECLTFEXP_WEC->PJM
CLTF
0.165

Details for 6BREMO-AG2-583 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.42 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:940.37
MW Contribution:1.35
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
3.828
3151911BEARGRDN G1
50/50
2.966
3144293JTRSVLE
50/50
0.503
3151531CLOVER1
50/50
2.188
3151601KERR 3
50/50
0.135
3151581KERR 1
50/50
0.048
972003AH1-546 GEN
Solar/Wind Harmer
13.118
971377AH1-170 GEN
Solar/Wind Harmer
3.027
3147623JAMES R
Solar/Wind Harmer
0.658
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
963171AG1-166 GEN
Solar/Wind Harmer
0.794
971563AH1-280 GEN
Solar/Wind Harmer
1.587
970685AG2-442 GEN
Solar/Wind Harmer
10.089
962491AG1-098 GEN
Solar/Wind Harmer
7.03
315693AD1-088 GEN
Solar/Wind Harmer
5.777
957481AF2-042 GEN
Solar/Wind Harmer
29.163
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.003
970401AG2-262 GEN
Solar/Wind Harmer
0.451
316003AC1-222 GEN
Solar/Wind Harmer
0.002
316336AC2-165 C
Solar/Wind Helper
5.135
3143226MDLTHAN
Solar/Wind Helper
0.3
3143526WINTERP
Solar/Wind Helper
1.294
3142543TWELFTH
Solar/Wind Helper
0.014
3142416OLDCHRC
Solar/Wind Helper
0.296
3142416OLDCHRC
Solar/Wind Helper
0.113
316458AB2-190 GEN2
Solar/Wind Helper
0.639
3151921BEARGRDN G2
50/50
2.966
3144293JTRSVLE
50/50
0.503
970413AG2-270 GEN
50/50
9.546
966251AG1-494 GEN
50/50
1.198
3151591KERR 2
50/50
0.135
970221AG2-151 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
0.094
3146926FARMVIL
Solar/Wind Harmer
0.129
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
1.869
3147133PAMPLIN
Solar/Wind Harmer
0.497
971193AH1-056 GEN
Solar/Wind Harmer
9.642
963181AG1-167 GEN
Solar/Wind Harmer
0.595
959311AF2-222 GEN
Solar/Wind Harmer
11.09
970257AG2-171 GEN
Solar/Wind Harmer
3.859
315785AD2-033 C
Solar/Wind Harmer
0.934
958131AF2-107 GEN
Solar/Wind Harmer
2.955
316478AD1-087 GEN
Solar/Wind Harmer
0.356
316486AD2-202 GEN
Solar/Wind Harmer
0.105
964241AG1-285 GEN
Solar/Wind Harmer
6.636
316131AB2-060 GEN
Solar/Wind Harmer
0.284
3148013FISHERV
Solar/Wind Harmer
0.071
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.932
971683AH1-343 GEN
Solar/Wind Harmer
2.348
316313AB2-026
Solar/Wind Helper
1.245
316258AE1-075 C
Solar/Wind Helper
1.12
316405AF2-144 C
Solar/Wind Helper
0.933
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.709
315839AE2-212 C
Solar/Wind Helper
0.155
3144293JTRSVLE
50/50
0.503
3144293JTRSVLE
50/50
0.423
970535AG2-341 GEN
50/50
1.349
3152661PLYWOOD A
50/50
0.157
971489AH1-241 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
1.049
3146776BUCKING
Solar/Wind Harmer
0.085
315821AE2-092 GEN
Solar/Wind Harmer
0.013
970301AG2-198 GEN
Solar/Wind Harmer
7.476
971741AH1-377 GEN
Solar/Wind Harmer
16.133
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.127
958211AF2-115 GEN
Solar/Wind Harmer
1.786
963191AG1-168 GEN
Solar/Wind Harmer
0.595
316034AC1-036 C
Solar/Wind Harmer
0.009
970323AG2-213 GEN
Solar/Wind Harmer
5.145
971775AH1-396 GEN
Solar/Wind Harmer
0.193
970099AG2-077 GEN
Solar/Wind Harmer
11.665
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.768
964791AG1-342 GEN
Solar/Wind Harmer
1.475
3146843MT LREL
Solar/Wind Harmer
0.077
3146843MT LREL
Solar/Wind Harmer
0.077
939181AE1-148 GEN
Solar/Wind Harmer
3.325
3143526WINTERP
Solar/Wind Helper
1.294
316240AF1-291 C
Solar/Wind Helper
0.162
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.156
316075AC2-137 C
Solar/Wind Helper
0.172
972205AH1-687 GEN
50/50
14.467
3151541CLOVER2
50/50
2.177
3151611KERR 4
50/50
0.135
3151621KERR 5
50/50
0.135
3151631KERR 6
50/50
0.135
3151641KERR 7
50/50
0.135
971447AH1-217 GEN
Solar/Wind Harmer
8.145
971845AH1-439 GEN
Solar/Wind Harmer
11.716
970285AG2-188 GEN
Solar/Wind Harmer
19.851
270494AE1-108_GEN
Solar/Wind Harmer
2.723
315657AE1-056 GEN
Solar/Wind Harmer
5.462
946301AF1-294 GEN
Solar/Wind Harmer
2.936
961791AG1-021 GEN
Solar/Wind Harmer
1.429
970683AG2-441 GEN
Solar/Wind Harmer
9.008
970681AG2-440 GEN
Solar/Wind Harmer
7.206
3144303KENBRDG
Solar/Wind Harmer
0.096
971443AH1-215 GEN
Solar/Wind Harmer
2.005
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.188
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.069
3147243WELCO
Solar/Wind Harmer
0.043
970865AG2-541 GEN
Solar/Wind Harmer
2.13
316123AC1-075 GEN
Solar/Wind Harmer
0.077
970165AG2-112 GEN
Solar/Wind Harmer
0.459
970163AG2-111 GEN
Solar/Wind Harmer
0.438
316233AE1-074 FULL
Solar/Wind Helper
0.38
316312AB1-027
Solar/Wind Helper
0.217
316132AB2-190 GEN1
Solar/Wind Helper
0.639
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.581
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
1.069
SIGELTFEXP_SIGE->PJM
CLTF
0.035
CPLELTFEXP_CPLE->PJM
CLTF
0.611
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.053
LAGNLTFEXP_LAGN->PJM
CLTF
1.406
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.04
TVALTFEXP_TVA->PJM
CLTF
0.731
NYPJM->LTFIMP_NY
CLTF
0.331
LGEELTFEXP_LGEE->PJM
CLTF
0.459
WECLTFEXP_WEC->PJM
CLTF
0.235

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:202.03 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1371.17
MW Contribution:2.24
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.18
316303AF2-085
50/50
2.224
3151541CLOVER2
50/50
2.487
3151611KERR 4
50/50
0.234
3151621KERR 5
50/50
0.234
3151631KERR 6
50/50
0.234
3151641KERR 7
50/50
0.234
963041AG1-153 GEN
50/50
2.299
315244AE2-183_ST
50/50
2.451
3151281ROARAP4
50/50
0.1
3151281ROARAP4
50/50
0.094
971285AH1-108 GEN
50/50
0.651
315779AE2-040
50/50
1.092
971845AH1-439 GEN
Solar/Wind Harmer
17.513
970285AG2-188 GEN
Solar/Wind Harmer
29.552
315657AE1-056 GEN
Solar/Wind Harmer
8.144
946301AF1-294 GEN
Solar/Wind Harmer
4.404
961791AG1-021 GEN
Solar/Wind Harmer
2.143
970683AG2-441 GEN
Solar/Wind Harmer
13.644
970681AG2-440 GEN
Solar/Wind Harmer
10.915
3144303KENBRDG
Solar/Wind Harmer
0.148
971443AH1-215 GEN
Solar/Wind Harmer
3.079
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316233AE1-074 FULL
Solar/Wind Harmer
0.084
971281AH1-106 GEN
Solar/Wind Harmer
1.459
971283AH1-107 GEN
Solar/Wind Harmer
1.459
316118AC1-105 GEN
Solar/Wind Harmer
0.27
270494AE1-108_GEN
Solar/Wind Harmer
1.236
970831AG2-522 GEN
Solar/Wind Harmer
4.291
3147173SINAI
Solar/Wind Harmer
0.095
3147243WELCO
Solar/Wind Harmer
0.059
971967AH1-528 GEN
Solar/Wind Harmer
14.709
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
18.242
970673AG2-436 GEN
Solar/Wind Harmer
12.162
941031AE2-094 GEN
Solar/Wind Harmer
15.639
944011AF1-069 GEN
Solar/Wind Harmer
5.11
3137643SOCKMAN
Solar/Wind Harmer
0.336
970085AG2-068 GEN
Solar/Wind Harmer
4.411
970581AG2-369 GEN
Solar/Wind Harmer
3.794
315607AA1-063A GEN
Solar/Wind Harmer
0.164
3146043SEABORD
Solar/Wind Harmer
0.08
315814AE2-033 C
Solar/Wind Harmer
6.192
316315AB2-025 C
Solar/Wind Harmer
0.063
970865AG2-541 GEN
Solar/Wind Harmer
2.68
965291AG1-394 GEN
Solar/Wind Harmer
0.339
315652AC1-086 GEN
Solar/Wind Harmer
8.307
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
3145796HORNRTN
Solar/Wind Harmer
0.238
3145796HORNRTN
Solar/Wind Harmer
0.03
3143316POE
Solar/Wind Harmer
0.292
3146033SCOT NK
Solar/Wind Harmer
0.294
3145513AHOSKIE
Solar/Wind Harmer
0.153
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.146
3145683EARLEYS
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
3146206CASHIE
Solar/Wind Harmer
0.07
970601AG2-382 GEN
Solar/Wind Harmer
2.62
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.048
316311AC2-079 GEN
Solar/Wind Harmer
2.01
316319Z2-044 C
Solar/Wind Harmer
0
315732AD1-074 GEN1
Solar/Wind Harmer
0.4
315733AD1-074 GEN2
Solar/Wind Harmer
0.4
315735AD1-075 GEN1
Solar/Wind Harmer
0.2
3130546PLYMOUTH
Solar/Wind Harmer
0.07
315835AF2-110_GEN
Solar/Wind Harmer
0.478
315816AE2-034 GEN
Solar/Wind Harmer
0.298
3130156CHOWAN
Solar/Wind Harmer
0.069
3130156CHOWAN
Solar/Wind Harmer
0.069
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3146486SUNBURY
Solar/Wind Harmer
0.069
3146486SUNBURY
Solar/Wind Harmer
0.069
316321Z2-027
Solar/Wind Harmer
0.013
3145176PASQUOTANK
Solar/Wind Harmer
0.043
3146396TANGLEW
Solar/Wind Harmer
0.19
316305AF2-043 C
Solar/Wind Harmer
0.001
313526AB2-022
Solar/Wind Harmer
0.037
3146406KITTY HAWK
Solar/Wind Harmer
0.009
319010AE1-072 C
Solar/Wind Harmer
0.346
957871AF2-081 GEN
Solar/Wind Harmer
3.419
3151081ELIZAR1
Adder
6.268
3151091ELIZAR2
Adder
6.16
3152611GOSPORTB
Adder
0.871
3152621GOSPORTC
Adder
0.739
3152601GOSPORTA
Adder
0.682
3145573BETHELC
Solar/Wind Harmer
0.067
3145573BETHELC
Solar/Wind Harmer
0.067
316420AA1-050 GEN
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
2.903
316005AA1-067
Solar/Wind Harmer
0.072
3145746EVERETS
Solar/Wind Harmer
0.267
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
970181AG2-120 GEN
Solar/Wind Harmer
0.836
971445AH1-216 GEN
Solar/Wind Harmer
4.703
972265AH1-717 GEN
Adder
5.124
3151201GRAVEL4
Adder
4.803
3151191GRAVEL3
Adder
4.742
3151211GRAVEL5
Adder
4.742
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.353
316123AC1-075 GEN
Solar/Wind Harmer
0.09
970165AG2-112 GEN
Solar/Wind Harmer
0.531
970163AG2-111 GEN
Solar/Wind Harmer
0.506
971447AH1-217 GEN
Solar/Wind Harmer
1.848
971167AH1-042 GEN
Solar/Wind Harmer
5.088
3138283WHITEMARSH
Solar/Wind Harmer
0.013
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.105
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.12
3144293JTRSVLE
50/50
0.754
3144293JTRSVLE
50/50
0.635
970535AG2-341 GEN
50/50
2.24
3152661PLYWOOD A
50/50
0.227
3151041BRUNSWICKG3
50/50
1.135
972187AH1-678 GEN
50/50
2.606
315242AE2-183_GT2
50/50
1.418
315241AE2-183_GT1
50/50
1.409
972185AH1-677 GEN
50/50
5.111
970533AG2-339 GEN
50/50
7.548
970531AG2-338 GEN
50/50
3.019
3146776BUCKING
Solar/Wind Harmer
1.571
3146776BUCKING
Solar/Wind Harmer
0.127
970301AG2-198 GEN
Solar/Wind Harmer
10.262
3147133PAMPLIN
Solar/Wind Harmer
0.236
3147133PAMPLIN
Solar/Wind Harmer
0.189
958211AF2-115 GEN
Solar/Wind Harmer
2.678
963191AG1-168 GEN
Solar/Wind Harmer
0.893
971741AH1-377 GEN
Solar/Wind Harmer
21.598
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
7.892
971775AH1-396 GEN
Solar/Wind Harmer
0.296
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971489AH1-241 GEN
Solar/Wind Harmer
7.009
971223AH1-071 GEN
Solar/Wind Harmer
1.334
962561AG1-105 GEN
Solar/Wind Harmer
5.681
939181AE1-148 GEN
Solar/Wind Harmer
5.661
970099AG2-077 GEN
Solar/Wind Harmer
12.506
964791AG1-342 GEN
Solar/Wind Harmer
2.195
3146843MT LREL
Solar/Wind Harmer
0.114
3146843MT LREL
Solar/Wind Harmer
0.114
3143526WINTERP
Solar/Wind Harmer
0.547
970933AG2-581 GEN
Solar/Wind Harmer
7.995
316181AB2-040 GEN
Solar/Wind Harmer
0.124
3145593CAROLNA
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.083
966811AG1-552 GEN
Solar/Wind Harmer
0.899
3145593CAROLNA
Solar/Wind Harmer
0.103
3145783HORNRTN
Solar/Wind Harmer
1.451
3145783HORNRTN
Solar/Wind Harmer
1.161
3145783HORNRTN
Solar/Wind Harmer
0.363
3145783HORNRTN
Solar/Wind Harmer
0.145
316426AA2-053 GEN
Solar/Wind Harmer
0.274
3144356SAPONY
Solar/Wind Harmer
0.654
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
0.503
3145893MURPHYS
Solar/Wind Harmer
0.135
316274AC1-208 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
0.223
3146173TUNIS
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
315742AE1-103 GEN
Solar/Wind Harmer
0.001
970657AG2-426 GEN
Solar/Wind Harmer
2.47
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.223
3146376EDENTON
Solar/Wind Harmer
0.308
3146376EDENTON
Solar/Wind Harmer
0.308
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146386ELIZ CT
Solar/Wind Harmer
0.069
316240AF1-291 C
Solar/Wind Harmer
0.001
3130086AYDLETT
Solar/Wind Harmer
0.275
3137176SLIGO L2192
Solar/Wind Harmer
0.273
3146456SLIGO L269
Solar/Wind Harmer
1.215
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.038
316339AD2-160 GEN
Solar/Wind Harmer
0.111
3145506HICKORY
Solar/Wind Harmer
0.274
3145506HICKORY
Solar/Wind Harmer
0.165
3145506HICKORY
Solar/Wind Harmer
0.041
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.066
316036AC1-147 C
Solar/Wind Harmer
0.013
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.505
316222AC1-221 GEN
Solar/Wind Harmer
0.283
316263AC1-034 GEN
Solar/Wind Harmer
2.586
3145933PARMELE
Solar/Wind Harmer
0.135
3145933PARMELE
Solar/Wind Harmer
0.068
961601AG1-000A GEN
Solar/Wind Harmer
1.202
3145493TOT1
Solar/Wind Harmer
0.156
3145453TOT5
Solar/Wind Harmer
0.094
3145603CNETO
Solar/Wind Harmer
0.063
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.074
3142366NRTHEST
Adder
0.195
3142946ENON
Solar/Wind Harmer
0.006
3150691DARBY 3
Adder
4.195
3150701DARBY 4
Adder
4.185
3150681DARBY 2
Adder
4.18
3150671DARBY 1
Adder
4.175
942751AE2-291 GEN
Solar/Wind Harmer
3.155
966001AG1-469 GEN
Solar/Wind Helper
0.19
3151931BEARGRDN S1
50/50
5.869
3151911BEARGRDN G1
50/50
4.548
3144293JTRSVLE
50/50
0.754
970119AG2-088 GEN
50/50
16.679
3151531CLOVER1
50/50
2.499
3151601KERR 3
50/50
0.234
3151581KERR 1
50/50
0.083
3147043LAWRENC
50/50
1
3151051BRUNSWICKS1
50/50
2.357
3151021BRUNSWICKG1
50/50
1.135
971451AH1-221 GEN
50/50
3.449
315243AE2-183_GT3
50/50
1.418
3151261ROARAP2
50/50
0.103
3150851SPRUNCC
50/50
0.398
3151391GASTONA
50/50
0.204
3151411GASTONB
50/50
0.204
972003AH1-546 GEN
Solar/Wind Harmer
20.039
970937AG2-583 GEN
Solar/Wind Harmer
24.928
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.157
3146926FARMVIL
Solar/Wind Harmer
0.188
316336AC2-165 C
Solar/Wind Harmer
0.012
3143336POWHATN
Solar/Wind Harmer
4.81
963171AG1-166 GEN
Solar/Wind Harmer
1.19
971563AH1-280 GEN
Solar/Wind Harmer
2.381
970685AG2-442 GEN
Solar/Wind Harmer
15.281
962491AG1-098 GEN
Solar/Wind Harmer
8.349
315693AD1-088 GEN
Solar/Wind Harmer
6.776
316237AB2-079_GEN
Solar/Wind Harmer
0.001
971377AH1-170 GEN
Solar/Wind Harmer
1.402
3147623JAMES R
Solar/Wind Harmer
0.305
3143226MDLTHAN
Solar/Wind Harmer
0.125
957481AF2-042 GEN
Solar/Wind Harmer
31.266
970401AG2-262 GEN
Solar/Wind Harmer
0.671
315687AD1-152 GEN
Solar/Wind Harmer
0.003
3143526WINTERP
Solar/Wind Harmer
0.547
971065AG2-659 GEN
Solar/Wind Harmer
4.446
316129AC1-054 GEN
Solar/Wind Harmer
0.385
971795AH1-408 GEN
Solar/Wind Harmer
6.611
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.847
970919AG2-571 GEN
Solar/Wind Harmer
2.953
970087AG2-069 GEN
Solar/Wind Harmer
6.617
3145783HORNRTN
Solar/Wind Harmer
0.082
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
6.459
316023GEN1_S
Solar/Wind Harmer
0.176
939411AE1-173 GEN
Solar/Wind Harmer
33.156
3146263WOODLND
Solar/Wind Harmer
0.076
316011AB1-132 GEN
Solar/Wind Harmer
1.373
962571AG1-106 GEN
Solar/Wind Harmer
1.074
3145893MURPHYS
Solar/Wind Harmer
0.301
3145893MURPHYS
Solar/Wind Harmer
0.334
3145796HORNRTN
Solar/Wind Harmer
0.245
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316212AC1-099_GEN
Solar/Wind Harmer
0.382
3145823KELFORD
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
315722AD1-056 GEN
Solar/Wind Harmer
0.447
970659AG2-427 GEN
Solar/Wind Harmer
3.416
316381AD1-082 GEN
Solar/Wind Harmer
0.074
970661AG2-428 GEN
Solar/Wind Harmer
7.004
3146206CASHIE
Solar/Wind Harmer
0.07
971547AH1-271 GEN
Solar/Wind Harmer
1.497
3142543TWELFTH
Solar/Wind Harmer
0.007
3146233WITAKRS
Solar/Wind Harmer
0.278
316093AE2-104_GEN
Solar/Wind Harmer
1.171
3145663CRESWEL
Solar/Wind Harmer
0.194
971163AH1-040 GEN
Solar/Wind Harmer
5.558
3130156CHOWAN
Solar/Wind Harmer
0.069
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.223
3146516WINFALL
Solar/Wind Harmer
0.069
315671AE2-027_GEN
Solar/Wind Harmer
4.41
316246AF1-032 C
Solar/Wind Harmer
0.031
3146456SLIGO L269
Solar/Wind Harmer
0.069
316388AE2-253 GEN
Solar/Wind Harmer
0.215
944591AF1-124 GEN
Solar/Wind Harmer
15.512
3145963POPLR C
Solar/Wind Harmer
0.069
316174AB2-169 GEN
Solar/Wind Harmer
0.002
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.853
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.054
316359AB2-059 GEN
Solar/Wind Harmer
0.244
316049AB1-081 GEN
Solar/Wind Harmer
0.389
3142053HEARTS
Solar/Wind Harmer
0.12
316072AD1-144
Solar/Wind Harmer
0.025
3146293MARTNCO
Solar/Wind Harmer
0.063
316294AC1-161 GEN
Solar/Wind Harmer
1.171
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.067
3145493TOT1
Solar/Wind Harmer
0.3
316494AC1-189 GEN
Solar/Wind Harmer
0.227
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.267
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
961611AG1-000B GEN
Solar/Wind Harmer
3.457
971647AH1-324 GEN
Solar/Wind Harmer
2.81
971069AG2-661 GEN
Solar/Wind Harmer
1.169
316458AB2-190 GEN2
Solar/Wind Harmer
0.353
970129AG2-093 GEN
Solar/Wind Harmer
1.869
944631AF1-128 GEN
Adder
29.45
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971317AH1-138 GEN
Solar/Wind Harmer
0.439
316159AE1-175 C
Solar/Wind Harmer
0.05
3142433PROV 92
Solar/Wind Harmer
0.226
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.056
316192AB2-158 GEN
Solar/Wind Helper
0.823
3147666LOUISA
Solar/Wind Helper
0.475
3151921BEARGRDN G2
50/50
4.548
3144293JTRSVLE
50/50
0.754
970413AG2-270 GEN
50/50
10.906
3151591KERR 2
50/50
0.234
3151031BRUNSWICKG2
50/50
1.135
3151261ROARAP2
50/50
0.101
3150861SPRUNCD
50/50
0.398
3151391GASTONA
50/50
0.204
3151411GASTONB
50/50
0.204
3146776BUCKING
Solar/Wind Harmer
0.141
3146926FARMVIL
Solar/Wind Harmer
0.188
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
316313AB2-026
Solar/Wind Harmer
0.171
316258AE1-075 C
Solar/Wind Harmer
0.204
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.088
970909AG2-566 GEN
Solar/Wind Harmer
2.566
3147133PAMPLIN
Solar/Wind Harmer
0.741
971193AH1-056 GEN
Solar/Wind Harmer
14.378
963181AG1-167 GEN
Solar/Wind Harmer
0.893
959311AF2-222 GEN
Solar/Wind Harmer
16.945
970257AG2-171 GEN
Solar/Wind Harmer
5.919
315785AD2-033 C
Solar/Wind Harmer
1.44
964241AG1-285 GEN
Solar/Wind Harmer
10.432
316131AB2-060 GEN
Solar/Wind Harmer
0.453
970221AG2-151 GEN
Solar/Wind Harmer
7.009
316478AD1-087 GEN
Solar/Wind Harmer
0.407
316486AD2-202 GEN
Solar/Wind Harmer
0.12
3147043LAWRENC
Solar/Wind Harmer
0.063
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.061
313506AB2-031 GEN
Solar/Wind Harmer
0.265
971683AH1-343 GEN
Solar/Wind Harmer
3.059
970917AG2-570 GEN
Solar/Wind Harmer
7.384
316365GEN2_N
Solar/Wind Harmer
0.176
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
957521AF2-046 GEN
Solar/Wind Harmer
5.572
961681AG1-008 GEN
Solar/Wind Harmer
5.572
3145796HORNRTN
Solar/Wind Harmer
0.297
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316210AC1-098 GEN
Solar/Wind Harmer
0.686
316463AE2-346 GEN
Solar/Wind Harmer
0.063
316140AB2-099
Solar/Wind Harmer
0.026
962331AG1-082 GEN
Solar/Wind Harmer
0.783
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.073
316327AA2-057 GEN
Solar/Wind Harmer
0.108
3145273HOLLAND
Solar/Wind Harmer
0.054
315813AE1-149 C
Solar/Wind Harmer
3.784
3156021HOLLOMANSOL
Solar/Wind Harmer
0.322
315839AE2-212 C
Solar/Wind Harmer
0.001
315724AD1-057 GEN
Solar/Wind Harmer
0.265
970659AG2-427 GEN
Solar/Wind Harmer
0.747
316083AB2-161 GEN
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
0.07
3146233WITAKRS
Solar/Wind Harmer
0.351
3146233WITAKRS
Solar/Wind Harmer
0.048
3138543CONSLDL
Solar/Wind Harmer
0.046
315737AD1-076 GEN
Solar/Wind Harmer
0.896
971157AH1-035 GEN
Solar/Wind Harmer
0.836
965281AG1-393 GEN
Solar/Wind Harmer
0.741
315614AA2-178 GEN
Solar/Wind Harmer
0.398
3146376EDENTON
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
316435W1029_GEN3
Solar/Wind Harmer
0
316320Y1-086
Solar/Wind Harmer
0
3146456SLIGO L269
Solar/Wind Harmer
0.069
971153AH1-033 GEN
Solar/Wind Harmer
0.794
944581AF1-123 GEN
Solar/Wind Harmer
15.457
944601AF1-125 GEN
Solar/Wind Harmer
15.219
3145963POPLR C
Solar/Wind Harmer
0.069
3151101ELIZAR3
Adder
6.349
3144873MCLAUGH
Solar/Wind Harmer
0.002
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.068
971623AH1-311 GEN
Solar/Wind Harmer
0.136
3144536CHRHLND
Solar/Wind Harmer
0.01
3145933PARMELE
Solar/Wind Harmer
0.068
966801AG1-551 GEN
Solar/Wind Harmer
0.788
961601AG1-000A GEN
Solar/Wind Harmer
4.808
315773AC2-141 GEN
Solar/Wind Harmer
2.468
3146073TAR RVR
Solar/Wind Harmer
0.067
3146083TARBORO
Solar/Wind Harmer
0.067
316283AC2-100 C
Solar/Wind Harmer
0.132
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.027
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.798
3151171GRAVELC
Adder
0.923
961611AG1-000B GEN
Solar/Wind Harmer
1.758
315778AD1-151 GEN
Solar/Wind Harmer
5.261
970129AG2-093 GEN
Solar/Wind Harmer
3.971
970133AG2-095 GEN
Solar/Wind Harmer
0.63
3144216WINCHST
Adder
0.231
3150921YORKTN3
Adder
1.525
3142946ENON
Solar/Wind Harmer
0.02
316382AG1-145 C
Solar/Wind Harmer
0
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.175
316499AE2-029_GEN
Solar/Wind Helper
0.514
3132273ORANGE
Solar/Wind Helper
0.027
315616AA1-038_C
Solar/Wind Helper
0.545
3147666LOUISA
Solar/Wind Helper
0.273
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.726
MECLTFEXP_MEC->PJM
CLTF
0.354
SIGELTFEXP_SIGE->PJM
CLTF
0.008
CPLELTFEXP_CPLE->PJM
CLTF
4.352
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.276
LAGNLTFEXP_LAGN->PJM
CLTF
1.781
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.535
TVALTFEXP_TVA->PJM
CLTF
0.87
NYPJM->LTFIMP_NY
CLTF
0.579
LGEELTFEXP_LGEE->PJM
CLTF
0.048
WECLTFEXP_WEC->PJM
CLTF
0.018

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:184.71 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1533.11
MW Contribution:2.24
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.86
3151911BEARGRDN G1
50/50
4.541
3144293JTRSVLE
50/50
0.753
970119AG2-088 GEN
50/50
16.672
3151531CLOVER1
50/50
2.497
3151601KERR 3
50/50
0.233
3151581KERR 1
50/50
0.083
972003AH1-546 GEN
Solar/Wind Harmer
26.388
970937AG2-583 GEN
Solar/Wind Harmer
32.774
316322AB2-045
Solar/Wind Harmer
1.483
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.021
316336AC2-165 C
Solar/Wind Harmer
6.018
3143336POWHATN
Solar/Wind Harmer
3.603
963171AG1-166 GEN
Solar/Wind Harmer
3.13
971563AH1-280 GEN
Solar/Wind Harmer
3.13
970685AG2-442 GEN
Solar/Wind Harmer
20.093
962491AG1-098 GEN
Solar/Wind Harmer
10.981
315693AD1-088 GEN
Solar/Wind Harmer
7.922
316237AB2-079_GEN
Solar/Wind Harmer
0.467
971377AH1-170 GEN
Solar/Wind Harmer
1.836
3147623JAMES R
Solar/Wind Harmer
0.227
3143226MDLTHAN
Solar/Wind Harmer
-0.014
957481AF2-042 GEN
Solar/Wind Harmer
41.127
970401AG2-262 GEN
Solar/Wind Harmer
0.837
315687AD1-152 GEN
Solar/Wind Harmer
1.432
3143526WINTERP
Solar/Wind Harmer
-0.061
3147043LAWRENC
Adder
0.942
971065AG2-659 GEN
Solar/Wind Harmer
5.848
316129AC1-054 GEN
Solar/Wind Harmer
1.008
971795AH1-408 GEN
Solar/Wind Harmer
8.35
316003AC1-222 GEN
Solar/Wind Harmer
0.972
960081AF2-299 GEN
Solar/Wind Harmer
1.114
970919AG2-571 GEN
Solar/Wind Harmer
2.952
970087AG2-069 GEN
Solar/Wind Harmer
8.708
3145783HORNRTN
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.375
316190AA2-174 GEN
Solar/Wind Harmer
0.112
940641AE2-051 GEN
Solar/Wind Harmer
8.503
316023GEN1_S
Solar/Wind Harmer
0.594
939411AE1-173 GEN
Solar/Wind Harmer
43.657
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.775
962571AG1-106 GEN
Solar/Wind Harmer
1.22
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.723
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.219
316381AD1-082 GEN
Solar/Wind Harmer
0.728
315722AD1-056 GEN
Solar/Wind Harmer
0.83
970661AG2-428 GEN
Solar/Wind Harmer
8.41
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
1.971
3146233WITAKRS
Solar/Wind Harmer
-0.031
316093AE2-104_GEN
Solar/Wind Harmer
2.275
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.318
3130156CHOWAN
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
1.92
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.811
316246AF1-032 C
Solar/Wind Harmer
0.157
3146456SLIGO L269
Solar/Wind Harmer
-0.008
316388AE2-253 GEN
Solar/Wind Harmer
0.521
944591AF1-124 GEN
Solar/Wind Harmer
35.229
3150981CHESPKA
Adder
0.854
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
944631AF1-128 GEN
Adder
29.484
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.057
316192AB2-158 GEN
Solar/Wind Helper
0.927
3147666LOUISA
Solar/Wind Helper
0.538
3151921BEARGRDN G2
50/50
4.541
3144293JTRSVLE
50/50
0.753
970413AG2-270 GEN
50/50
10.895
3151591KERR 2
50/50
0.233
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
4.6
316313AB2-026
Solar/Wind Harmer
0.819
316258AE1-075 C
Solar/Wind Harmer
0.737
316405AF2-144 C
Solar/Wind Harmer
0.778
3143336POWHATN
Solar/Wind Harmer
3.062
970909AG2-566 GEN
Solar/Wind Harmer
2.562
3147133PAMPLIN
Solar/Wind Harmer
-0.083
971193AH1-056 GEN
Solar/Wind Harmer
16.559
963181AG1-167 GEN
Solar/Wind Harmer
2.348
959311AF2-222 GEN
Solar/Wind Harmer
22.325
970257AG2-171 GEN
Solar/Wind Harmer
7.783
315785AD2-033 C
Solar/Wind Harmer
4.506
964241AG1-285 GEN
Solar/Wind Harmer
13.718
316131AB2-060 GEN
Solar/Wind Harmer
1.742
970221AG2-151 GEN
Solar/Wind Harmer
9.178
316478AD1-087 GEN
Solar/Wind Harmer
1.133
316486AD2-202 GEN
Solar/Wind Harmer
0.332
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.322
960061AF2-297 GEN
Solar/Wind Harmer
5.34
966621AG1-532 GEN
Solar/Wind Harmer
0.201
313506AB2-031 GEN
Solar/Wind Harmer
0.773
970917AG2-570 GEN
Solar/Wind Harmer
23.32
971683AH1-343 GEN
Solar/Wind Harmer
4.021
3150861SPRUNCD
Adder
0.375
316365GEN2_N
Solar/Wind Harmer
0.594
3156081AA2-088 GEN
Solar/Wind Harmer
2.773
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.624
961681AG1-008 GEN
Solar/Wind Harmer
6.624
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.302
316463AE2-346 GEN
Solar/Wind Harmer
0.133
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.031
316317KELFORD C
Solar/Wind Harmer
0.388
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.813
3145273HOLLAND
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
4.985
3156021HOLLOMANSOL
Solar/Wind Harmer
1.073
315839AE2-212 C
Solar/Wind Harmer
0.24
970659AG2-427 GEN
Solar/Wind Harmer
0.748
316083AB2-161 GEN
Solar/Wind Harmer
1.288
315724AD1-057 GEN
Solar/Wind Harmer
0.456
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
-0.008
3146233WITAKRS
Solar/Wind Harmer
0.164
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.488
971157AH1-035 GEN
Solar/Wind Harmer
0.978
965281AG1-393 GEN
Solar/Wind Harmer
0.977
315614AA2-178 GEN
Solar/Wind Harmer
0.842
3146376EDENTON
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316435W1029_GEN3
Solar/Wind Harmer
1.405
316320Y1-086
Solar/Wind Harmer
0.453
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.941
944581AF1-123 GEN
Solar/Wind Harmer
35.103
3151101ELIZAR3
Adder
6.351
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.801
3151171GRAVELC
Adder
0.924
3144216WINCHST
Adder
0.232
3150921YORKTN3
Adder
1.526
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.176
316499AE2-029_GEN
Solar/Wind Helper
0.517
3132273ORANGE
Solar/Wind Helper
0.028
3147666LOUISA
Solar/Wind Helper
0.309
315616AA1-038_C
Solar/Wind Helper
0.548
944601AF1-125 GEN
Solar/Wind Harmer
11.266
3144293JTRSVLE
50/50
0.753
3144293JTRSVLE
50/50
0.634
970535AG2-341 GEN
50/50
2.238
3146776BUCKING
Solar/Wind Harmer
-0.175
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.493
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.913
963191AG1-168 GEN
Solar/Wind Harmer
2.348
971741AH1-377 GEN
Solar/Wind Harmer
28.4
316034AC1-036 C
Solar/Wind Harmer
0.386
970323AG2-213 GEN
Solar/Wind Harmer
10.377
971775AH1-396 GEN
Solar/Wind Harmer
1.478
313527AB2-043 GEN
Solar/Wind Harmer
2.568
971489AH1-241 GEN
Solar/Wind Harmer
8.713
971223AH1-071 GEN
Solar/Wind Harmer
1.756
962561AG1-105 GEN
Solar/Wind Harmer
7.471
939181AE1-148 GEN
Solar/Wind Harmer
7.446
970099AG2-077 GEN
Solar/Wind Harmer
16.451
964791AG1-342 GEN
Solar/Wind Harmer
2.74
3146843MT LREL
Solar/Wind Harmer
-0.013
3146843MT LREL
Solar/Wind Harmer
-0.013
3143526WINTERP
Solar/Wind Harmer
-0.061
970933AG2-581 GEN
Solar/Wind Harmer
10.52
972187AH1-678 GEN
Adder
2.454
972185AH1-677 GEN
Adder
4.815
316181AB2-040 GEN
Solar/Wind Harmer
1.342
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
1.047
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.088
3145783HORNRTN
Solar/Wind Harmer
0.87
3145783HORNRTN
Solar/Wind Harmer
0.272
3145783HORNRTN
Solar/Wind Harmer
0.109
316426AA2-053 GEN
Solar/Wind Harmer
0.92
3144356SAPONY
Solar/Wind Harmer
0.307
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
316274AC1-208 GEN
Solar/Wind Harmer
0.909
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.852
970657AG2-426 GEN
Solar/Wind Harmer
2.477
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.932
3146376EDENTON
Solar/Wind Harmer
0.231
3146376EDENTON
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.405
316433W1029_GEN2
Solar/Wind Harmer
1.405
316240AF1-291 C
Solar/Wind Harmer
0.233
3146386ELIZ CT
Solar/Wind Harmer
-0.008
3130086AYDLETT
Solar/Wind Harmer
-0.031
3137176SLIGO L2192
Solar/Wind Harmer
-0.031
3146456SLIGO L269
Solar/Wind Harmer
0.912
316018AA1-139 ULT2
Solar/Wind Harmer
0.661
316017AA1-139 ULT1
Solar/Wind Harmer
0.625
316339AD2-160 GEN
Solar/Wind Harmer
0.521
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.529
3142366NRTHEST
Adder
0.195
3150691DARBY 3
Adder
4.201
3150701DARBY 4
Adder
4.191
3150681DARBY 2
Adder
4.186
3150671DARBY 1
Adder
4.181
966001AG1-469 GEN
Solar/Wind Helper
0.199
972205AH1-687 GEN
50/50
22.146
316303AF2-085
50/50
2.223
3151541CLOVER2
50/50
2.485
3151611KERR 4
50/50
0.233
3151621KERR 5
50/50
0.233
3151631KERR 6
50/50
0.233
3151641KERR 7
50/50
0.233
971845AH1-439 GEN
Solar/Wind Harmer
23.024
970285AG2-188 GEN
Solar/Wind Harmer
36.67
315657AE1-056 GEN
Solar/Wind Harmer
9.935
946301AF1-294 GEN
Solar/Wind Harmer
6.417
961791AG1-021 GEN
Solar/Wind Harmer
3.13
970683AG2-441 GEN
Solar/Wind Harmer
17.94
970681AG2-440 GEN
Solar/Wind Harmer
14.352
3144303KENBRDG
Solar/Wind Harmer
-0.017
971443AH1-215 GEN
Solar/Wind Harmer
4.049
316239AB2-077_GEN
Solar/Wind Harmer
0.467
316238AB2-078_GEN
Solar/Wind Harmer
0.467
316233AE1-074 FULL
Solar/Wind Harmer
0.318
971281AH1-106 GEN
Solar/Wind Harmer
1.921
971283AH1-107 GEN
Solar/Wind Harmer
1.921
316118AC1-105 GEN
Solar/Wind Harmer
0.807
270494AE1-108_GEN
Solar/Wind Harmer
2.995
970831AG2-522 GEN
Solar/Wind Harmer
5.644
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
19.409
946281AF1-292 GEN
Solar/Wind Harmer
0.222
316087AB2-174 GEN
Solar/Wind Harmer
1.385
970673AG2-436 GEN
Solar/Wind Harmer
20.177
970673AG2-436 GEN
Solar/Wind Harmer
10.216
941031AE2-094 GEN
Solar/Wind Harmer
17.883
944011AF1-069 GEN
Solar/Wind Harmer
5.603
3137643SOCKMAN
Solar/Wind Harmer
-0.038
970085AG2-068 GEN
Solar/Wind Harmer
5.805
970581AG2-369 GEN
Solar/Wind Harmer
4.993
971285AH1-108 GEN
Adder
0.613
315607AA1-063A GEN
Solar/Wind Harmer
0.911
3146043SEABORD
Solar/Wind Harmer
-0.009
315814AE2-033 C
Solar/Wind Harmer
8.189
316315AB2-025 C
Solar/Wind Harmer
0.237
970865AG2-541 GEN
Solar/Wind Harmer
3.523
965291AG1-394 GEN
Solar/Wind Harmer
0.761
315652AC1-086 GEN
Solar/Wind Harmer
9.545
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.033
3146033SCOT NK
Solar/Wind Harmer
-0.033
3145513AHOSKIE
Solar/Wind Harmer
0.072
961941AG1-037 GEN
Solar/Wind Harmer
0.062
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.449
315833AF1-017_GEN
Solar/Wind Harmer
1.494
316349AD2-085 GEN
Solar/Wind Harmer
0.7
316311AC2-079 GEN
Solar/Wind Harmer
3.968
316319Z2-044 C
Solar/Wind Harmer
0.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.583
315733AD1-074 GEN2
Solar/Wind Harmer
1.583
315735AD1-075 GEN1
Solar/Wind Harmer
0.792
315835AF2-110_GEN
Solar/Wind Harmer
0.978
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.632
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
1.92
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.209
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.142
316305AF2-043 C
Solar/Wind Harmer
0.233
313526AB2-022
Solar/Wind Harmer
0.209
319010AE1-072 C
Solar/Wind Harmer
1.562
3146406KITTY HAWK
Solar/Wind Harmer
0.006
957871AF2-081 GEN
Solar/Wind Harmer
3.86
3151081ELIZAR1
Adder
6.271
3151091ELIZAR2
Adder
6.162
3152611GOSPORTB
Adder
0.871
3152621GOSPORTC
Adder
0.739
3152601GOSPORTA
Adder
0.682
972265AH1-717 GEN
Adder
5.127
3151201GRAVEL4
Adder
4.806
3151191GRAVEL3
Adder
4.745
3151211GRAVEL5
Adder
4.745
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.121
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
0.346
SIGELTFEXP_SIGE->PJM
CLTF
0.008
CPLELTFEXP_CPLE->PJM
CLTF
4.345
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.202
LAGNLTFEXP_LAGN->PJM
CLTF
1.77
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.515
TVALTFEXP_TVA->PJM
CLTF
0.864
NYPJM->LTFIMP_NY
CLTF
0.574
LGEELTFEXP_LGEE->PJM
CLTF
0.044
WECLTFEXP_WEC->PJM
CLTF
0.016

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:184.71 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1533.1
MW Contribution:2.24
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.86
3151911BEARGRDN G1
50/50
4.54
3144293JTRSVLE
50/50
0.753
970119AG2-088 GEN
50/50
16.671
3151531CLOVER1
50/50
2.497
3151601KERR 3
50/50
0.233
3151581KERR 1
50/50
0.083
972003AH1-546 GEN
Solar/Wind Harmer
26.387
970937AG2-583 GEN
Solar/Wind Harmer
32.773
316322AB2-045
Solar/Wind Harmer
1.483
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.021
316336AC2-165 C
Solar/Wind Harmer
6.018
3143336POWHATN
Solar/Wind Harmer
3.603
963171AG1-166 GEN
Solar/Wind Harmer
3.13
971563AH1-280 GEN
Solar/Wind Harmer
3.13
970685AG2-442 GEN
Solar/Wind Harmer
20.093
962491AG1-098 GEN
Solar/Wind Harmer
10.981
315693AD1-088 GEN
Solar/Wind Harmer
7.922
316237AB2-079_GEN
Solar/Wind Harmer
0.467
971377AH1-170 GEN
Solar/Wind Harmer
1.835
3147623JAMES R
Solar/Wind Harmer
0.227
3143226MDLTHAN
Solar/Wind Harmer
-0.014
957481AF2-042 GEN
Solar/Wind Harmer
41.127
970401AG2-262 GEN
Solar/Wind Harmer
0.837
315687AD1-152 GEN
Solar/Wind Harmer
1.432
3143526WINTERP
Solar/Wind Harmer
-0.061
3147043LAWRENC
Adder
0.942
971065AG2-659 GEN
Solar/Wind Harmer
5.848
316129AC1-054 GEN
Solar/Wind Harmer
1.008
971795AH1-408 GEN
Solar/Wind Harmer
8.349
316003AC1-222 GEN
Solar/Wind Harmer
0.972
960081AF2-299 GEN
Solar/Wind Harmer
1.114
970919AG2-571 GEN
Solar/Wind Harmer
2.952
970087AG2-069 GEN
Solar/Wind Harmer
8.708
3145783HORNRTN
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.375
316190AA2-174 GEN
Solar/Wind Harmer
0.112
940641AE2-051 GEN
Solar/Wind Harmer
8.503
316023GEN1_S
Solar/Wind Harmer
0.594
939411AE1-173 GEN
Solar/Wind Harmer
43.657
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.775
962571AG1-106 GEN
Solar/Wind Harmer
1.22
3151921BEARGRDN G2
50/50
4.54
3144293JTRSVLE
50/50
0.753
970413AG2-270 GEN
50/50
10.894
3151591KERR 2
50/50
0.233
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
4.6
316313AB2-026
Solar/Wind Harmer
0.819
316258AE1-075 C
Solar/Wind Harmer
0.737
316405AF2-144 C
Solar/Wind Harmer
0.778
3143336POWHATN
Solar/Wind Harmer
3.062
970909AG2-566 GEN
Solar/Wind Harmer
2.562
3147133PAMPLIN
Solar/Wind Harmer
-0.083
971193AH1-056 GEN
Solar/Wind Harmer
16.559
963181AG1-167 GEN
Solar/Wind Harmer
2.348
959311AF2-222 GEN
Solar/Wind Harmer
22.325
970257AG2-171 GEN
Solar/Wind Harmer
7.783
315785AD2-033 C
Solar/Wind Harmer
4.506
964241AG1-285 GEN
Solar/Wind Harmer
13.718
316131AB2-060 GEN
Solar/Wind Harmer
1.742
970221AG2-151 GEN
Solar/Wind Harmer
9.177
316478AD1-087 GEN
Solar/Wind Harmer
1.133
316486AD2-202 GEN
Solar/Wind Harmer
0.332
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.322
960061AF2-297 GEN
Solar/Wind Harmer
5.34
966621AG1-532 GEN
Solar/Wind Harmer
0.201
313506AB2-031 GEN
Solar/Wind Harmer
0.773
970917AG2-570 GEN
Solar/Wind Harmer
23.32
971683AH1-343 GEN
Solar/Wind Harmer
4.021
3150861SPRUNCD
Adder
0.375
316365GEN2_N
Solar/Wind Harmer
0.594
3156081AA2-088 GEN
Solar/Wind Harmer
2.773
3144293JTRSVLE
50/50
0.753
3144293JTRSVLE
50/50
0.634
970535AG2-341 GEN
50/50
2.237
3146776BUCKING
Solar/Wind Harmer
-0.175
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.493
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.913
963191AG1-168 GEN
Solar/Wind Harmer
2.348
971741AH1-377 GEN
Solar/Wind Harmer
28.4
316034AC1-036 C
Solar/Wind Harmer
0.386
970323AG2-213 GEN
Solar/Wind Harmer
10.377
971775AH1-396 GEN
Solar/Wind Harmer
1.478
313527AB2-043 GEN
Solar/Wind Harmer
2.568
971489AH1-241 GEN
Solar/Wind Harmer
8.713
971223AH1-071 GEN
Solar/Wind Harmer
1.756
962561AG1-105 GEN
Solar/Wind Harmer
7.471
939181AE1-148 GEN
Solar/Wind Harmer
7.446
970099AG2-077 GEN
Solar/Wind Harmer
16.451
964791AG1-342 GEN
Solar/Wind Harmer
2.74
3146843MT LREL
Solar/Wind Harmer
-0.013
3146843MT LREL
Solar/Wind Harmer
-0.013
3143526WINTERP
Solar/Wind Harmer
-0.061
970933AG2-581 GEN
Solar/Wind Harmer
10.52
972187AH1-678 GEN
Adder
2.454
972185AH1-677 GEN
Adder
4.815
316181AB2-040 GEN
Solar/Wind Harmer
1.342
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
1.047
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.088
3145783HORNRTN
Solar/Wind Harmer
0.87
3145783HORNRTN
Solar/Wind Harmer
0.272
3145783HORNRTN
Solar/Wind Harmer
0.109
316426AA2-053 GEN
Solar/Wind Harmer
0.92
3144356SAPONY
Solar/Wind Harmer
0.307
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
972205AH1-687 GEN
50/50
22.145
316303AF2-085
50/50
2.223
3151541CLOVER2
50/50
2.485
3151611KERR 4
50/50
0.233
3151621KERR 5
50/50
0.233
3151631KERR 6
50/50
0.233
3151641KERR 7
50/50
0.233
971845AH1-439 GEN
Solar/Wind Harmer
23.024
970285AG2-188 GEN
Solar/Wind Harmer
36.669
315657AE1-056 GEN
Solar/Wind Harmer
9.935
946301AF1-294 GEN
Solar/Wind Harmer
6.417
961791AG1-021 GEN
Solar/Wind Harmer
3.13
970683AG2-441 GEN
Solar/Wind Harmer
17.94
970681AG2-440 GEN
Solar/Wind Harmer
14.352
3144303KENBRDG
Solar/Wind Harmer
-0.017
971443AH1-215 GEN
Solar/Wind Harmer
4.049
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
316274AC1-208 GEN
Solar/Wind Harmer
0.909
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.852
970657AG2-426 GEN
Solar/Wind Harmer
2.477
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.932
3146376EDENTON
Solar/Wind Harmer
0.231
3146376EDENTON
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.405
316433W1029_GEN2
Solar/Wind Harmer
1.405
316240AF1-291 C
Solar/Wind Harmer
0.233
3146386ELIZ CT
Solar/Wind Harmer
-0.008
3130086AYDLETT
Solar/Wind Harmer
-0.031
3137176SLIGO L2192
Solar/Wind Harmer
-0.031
3146456SLIGO L269
Solar/Wind Harmer
0.912
316018AA1-139 ULT2
Solar/Wind Harmer
0.661
316017AA1-139 ULT1
Solar/Wind Harmer
0.625
316339AD2-160 GEN
Solar/Wind Harmer
0.521
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.53
3142366NRTHEST
Adder
0.195
3150691DARBY 3
Adder
4.201
3150701DARBY 4
Adder
4.191
3150681DARBY 2
Adder
4.186
3150671DARBY 1
Adder
4.181
966001AG1-469 GEN
Solar/Wind Helper
0.199
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.723
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.219
316381AD1-082 GEN
Solar/Wind Harmer
0.728
315722AD1-056 GEN
Solar/Wind Harmer
0.83
970661AG2-428 GEN
Solar/Wind Harmer
8.41
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
1.971
3146233WITAKRS
Solar/Wind Harmer
-0.031
316093AE2-104_GEN
Solar/Wind Harmer
2.275
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.318
3130156CHOWAN
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
1.92
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.811
316246AF1-032 C
Solar/Wind Harmer
0.157
3146456SLIGO L269
Solar/Wind Harmer
-0.008
316388AE2-253 GEN
Solar/Wind Harmer
0.521
944591AF1-124 GEN
Solar/Wind Harmer
35.23
3150981CHESPKA
Adder
0.854
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
944631AF1-128 GEN
Adder
29.485
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.057
316192AB2-158 GEN
Solar/Wind Helper
0.928
3147666LOUISA
Solar/Wind Helper
0.539
316239AB2-077_GEN
Solar/Wind Harmer
0.467
316238AB2-078_GEN
Solar/Wind Harmer
0.467
316233AE1-074 FULL
Solar/Wind Harmer
0.318
971281AH1-106 GEN
Solar/Wind Harmer
1.921
971283AH1-107 GEN
Solar/Wind Harmer
1.921
316118AC1-105 GEN
Solar/Wind Harmer
0.807
270494AE1-108_GEN
Solar/Wind Harmer
2.995
970831AG2-522 GEN
Solar/Wind Harmer
5.644
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
19.408
946281AF1-292 GEN
Solar/Wind Harmer
0.222
316087AB2-174 GEN
Solar/Wind Harmer
1.385
970673AG2-436 GEN
Solar/Wind Harmer
20.177
970673AG2-436 GEN
Solar/Wind Harmer
10.216
941031AE2-094 GEN
Solar/Wind Harmer
17.883
944011AF1-069 GEN
Solar/Wind Harmer
5.603
3137643SOCKMAN
Solar/Wind Harmer
-0.038
970085AG2-068 GEN
Solar/Wind Harmer
5.805
970581AG2-369 GEN
Solar/Wind Harmer
4.993
971285AH1-108 GEN
Adder
0.613
315607AA1-063A GEN
Solar/Wind Harmer
0.911
3146043SEABORD
Solar/Wind Harmer
-0.009
315814AE2-033 C
Solar/Wind Harmer
8.189
316315AB2-025 C
Solar/Wind Harmer
0.237
970865AG2-541 GEN
Solar/Wind Harmer
3.523
965291AG1-394 GEN
Solar/Wind Harmer
0.761
315652AC1-086 GEN
Solar/Wind Harmer
9.545
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.033
3146033SCOT NK
Solar/Wind Harmer
-0.033
3145513AHOSKIE
Solar/Wind Harmer
0.072
961941AG1-037 GEN
Solar/Wind Harmer
0.062
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.449
315833AF1-017_GEN
Solar/Wind Harmer
1.494
316349AD2-085 GEN
Solar/Wind Harmer
0.7
316311AC2-079 GEN
Solar/Wind Harmer
3.968
316319Z2-044 C
Solar/Wind Harmer
0.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.583
315733AD1-074 GEN2
Solar/Wind Harmer
1.583
315735AD1-075 GEN1
Solar/Wind Harmer
0.792
315835AF2-110_GEN
Solar/Wind Harmer
0.978
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.632
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
1.92
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.209
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.142
316305AF2-043 C
Solar/Wind Harmer
0.233
313526AB2-022
Solar/Wind Harmer
0.209
319010AE1-072 C
Solar/Wind Harmer
1.562
3146406KITTY HAWK
Solar/Wind Harmer
0.006
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.624
961681AG1-008 GEN
Solar/Wind Harmer
6.624
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.302
316463AE2-346 GEN
Solar/Wind Harmer
0.133
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.031
316317KELFORD C
Solar/Wind Harmer
0.388
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.813
3145273HOLLAND
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
4.985
3156021HOLLOMANSOL
Solar/Wind Harmer
1.073
315839AE2-212 C
Solar/Wind Harmer
0.24
970659AG2-427 GEN
Solar/Wind Harmer
0.748
316083AB2-161 GEN
Solar/Wind Harmer
1.288
315724AD1-057 GEN
Solar/Wind Harmer
0.456
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
-0.008
3146233WITAKRS
Solar/Wind Harmer
0.164
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.488
971157AH1-035 GEN
Solar/Wind Harmer
0.978
965281AG1-393 GEN
Solar/Wind Harmer
0.977
315614AA2-178 GEN
Solar/Wind Harmer
0.842
3146376EDENTON
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316435W1029_GEN3
Solar/Wind Harmer
1.405
316320Y1-086
Solar/Wind Harmer
0.453
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.941
944581AF1-123 GEN
Solar/Wind Harmer
35.103
3151101ELIZAR3
Adder
6.351
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.801
3151171GRAVELC
Adder
0.924
3144216WINCHST
Adder
0.232
3150921YORKTN3
Adder
1.526
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.176
316499AE2-029_GEN
Solar/Wind Helper
0.517
3132273ORANGE
Solar/Wind Helper
0.028
3147666LOUISA
Solar/Wind Helper
0.31
315616AA1-038_C
Solar/Wind Helper
0.549
944601AF1-125 GEN
Solar/Wind Harmer
11.266
957871AF2-081 GEN
Solar/Wind Harmer
3.86
3151081ELIZAR1
Adder
6.271
3151091ELIZAR2
Adder
6.162
3152611GOSPORTB
Adder
0.871
3152621GOSPORTC
Adder
0.739
3152601GOSPORTA
Adder
0.682
972265AH1-717 GEN
Adder
5.127
3151201GRAVEL4
Adder
4.806
3151191GRAVEL3
Adder
4.746
3151211GRAVEL5
Adder
4.746
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.121
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
0.346
SIGELTFEXP_SIGE->PJM
CLTF
0.008
CPLELTFEXP_CPLE->PJM
CLTF
4.345
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.201
LAGNLTFEXP_LAGN->PJM
CLTF
1.769
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.514
TVALTFEXP_TVA->PJM
CLTF
0.864
NYPJM->LTFIMP_NY
CLTF
0.574
LGEELTFEXP_LGEE->PJM
CLTF
0.044
WECLTFEXP_WEC->PJM
CLTF
0.016

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:172.6 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1432.61
MW Contribution:2.16
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.938
3151911BEARGRDN G1
50/50
4.601
3144293JTRSVLE
50/50
0.746
970119AG2-088 GEN
50/50
19.705
972003AH1-546 GEN
Solar/Wind Harmer
26.72
970937AG2-583 GEN
Solar/Wind Harmer
33.599
316322AB2-045
Solar/Wind Harmer
1.495
3146776BUCKING
Solar/Wind Harmer
-0.018
316336AC2-165 C
Solar/Wind Harmer
6.302
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.82
963171AG1-166 GEN
Solar/Wind Harmer
3.104
971563AH1-280 GEN
Solar/Wind Harmer
3.104
970685AG2-442 GEN
Solar/Wind Harmer
19.859
3143226MDLTHAN
Solar/Wind Harmer
-0.017
962491AG1-098 GEN
Solar/Wind Harmer
10.562
971377AH1-170 GEN
Solar/Wind Harmer
1.918
3147623JAMES R
Solar/Wind Harmer
0.237
315693AD1-088 GEN
Solar/Wind Harmer
7.599
316237AB2-079_GEN
Solar/Wind Harmer
0.453
3143526WINTERP
Solar/Wind Harmer
-0.071
957481AF2-042 GEN
Solar/Wind Harmer
38.757
970401AG2-262 GEN
Solar/Wind Harmer
0.805
315687AD1-152 GEN
Solar/Wind Harmer
1.355
3147043LAWRENC
Adder
0.898
971065AG2-659 GEN
Solar/Wind Harmer
5.572
316129AC1-054 GEN
Solar/Wind Harmer
0.96
971795AH1-408 GEN
Solar/Wind Harmer
7.936
3150851SPRUNCC
Adder
0.417
316003AC1-222 GEN
Solar/Wind Harmer
0.924
960081AF2-299 GEN
Solar/Wind Harmer
1.049
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
3142543TWELFTH
Solar/Wind Harmer
-0.001
970919AG2-571 GEN
Solar/Wind Harmer
2.65
970087AG2-069 GEN
Solar/Wind Harmer
7.82
316023GEN1_S
Solar/Wind Harmer
0.554
940641AE2-051 GEN
Solar/Wind Harmer
7.517
3143096IRON208
Adder
0.298
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.653
962571AG1-106 GEN
Solar/Wind Harmer
1.136
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3144293JTRSVLE
50/50
0.746
3144293JTRSVLE
50/50
0.629
970535AG2-341 GEN
50/50
2.158
3146776BUCKING
Solar/Wind Harmer
-0.177
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.372
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.88
963191AG1-168 GEN
Solar/Wind Harmer
2.328
971741AH1-377 GEN
Solar/Wind Harmer
28.01
316034AC1-036 C
Solar/Wind Harmer
0.38
970323AG2-213 GEN
Solar/Wind Harmer
10.214
971775AH1-396 GEN
Solar/Wind Harmer
1.455
971223AH1-071 GEN
Solar/Wind Harmer
2.076
313527AB2-043 GEN
Solar/Wind Harmer
2.493
971489AH1-241 GEN
Solar/Wind Harmer
9.104
3143526WINTERP
Solar/Wind Harmer
-0.071
962561AG1-105 GEN
Solar/Wind Harmer
7.195
939181AE1-148 GEN
Solar/Wind Harmer
7.148
970099AG2-077 GEN
Solar/Wind Harmer
15.503
964791AG1-342 GEN
Solar/Wind Harmer
2.634
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970933AG2-581 GEN
Solar/Wind Harmer
9.649
316181AB2-040 GEN
Solar/Wind Harmer
1.262
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.983
3145593CAROLNA
Solar/Wind Harmer
0.073
972187AH1-678 GEN
Adder
2.2
972185AH1-677 GEN
Adder
4.302
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
316274AC1-208 GEN
Solar/Wind Harmer
0.849
316240AF1-291 C
Solar/Wind Harmer
0.235
944641AF1-129 GEN
Adder
33.028
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.793
970657AG2-426 GEN
Solar/Wind Harmer
2.358
970657AG2-426 GEN
Solar/Wind Harmer
0.493
316065AD1-022 GEN
Solar/Wind Harmer
3.643
316033AB2-134 GEN
Solar/Wind Harmer
2.34
315697AD1-025 GEN
Solar/Wind Harmer
1.468
3142366NRTHEST
Adder
0.21
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.298
316433W1029_GEN2
Solar/Wind Harmer
1.298
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316222AC1-221 GEN
Solar/Wind Harmer
0.722
3130086AYDLETT
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.75
3142956BIRDNECK
Solar/Wind Harmer
0.381
316316AC1-027 C
Solar/Wind Harmer
0.218
316236AE1-162_GEN
Solar/Wind Harmer
0.214
316036AC1-147 C
Solar/Wind Harmer
0.192
3150991CHESPKB
Adder
0.662
3150991CHESPKB
Adder
0.646
3150691DARBY 3
Adder
4.502
3150701DARBY 4
Adder
4.491
3150681DARBY 2
Adder
4.486
3150671DARBY 1
Adder
4.481
966001AG1-469 GEN
Solar/Wind Helper
0.186
939411AE1-173 GEN
Solar/Wind Harmer
38.95
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.803
316212AC1-099_GEN
Solar/Wind Harmer
0.674
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.029
316381AD1-082 GEN
Solar/Wind Harmer
0.694
970661AG2-428 GEN
Solar/Wind Harmer
7.982
315722AD1-056 GEN
Solar/Wind Harmer
0.771
970129AG2-093 GEN
Solar/Wind Harmer
1.678
316458AB2-190 GEN2
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.827
3146233WITAKRS
Solar/Wind Harmer
-0.029
971069AG2-661 GEN
Solar/Wind Harmer
1.154
316093AE2-104_GEN
Solar/Wind Harmer
2.113
944631AF1-128 GEN
Adder
30.658
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.772
971647AH1-324 GEN
Solar/Wind Harmer
3.605
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.775
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.535
316246AF1-032 C
Solar/Wind Harmer
0.145
3145963POPLR C
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
316174AB2-169 GEN
Solar/Wind Harmer
1.097
3151171GRAVELC
Adder
0.673
316375AC2-012 GEN
Solar/Wind Harmer
2.457
3145336SMITFLD
Solar/Wind Harmer
-0.028
3150981CHESPKA
Adder
0.789
944591AF1-124 GEN
Solar/Wind Harmer
32.38
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.798
3147666LOUISA
Solar/Wind Helper
0.46
972205AH1-687 GEN
50/50
22.442
316303AF2-085
50/50
2.627
971845AH1-439 GEN
Solar/Wind Harmer
23.203
970285AG2-188 GEN
Solar/Wind Harmer
36.921
315657AE1-056 GEN
Solar/Wind Harmer
9.87
946301AF1-294 GEN
Solar/Wind Harmer
6.363
961791AG1-021 GEN
Solar/Wind Harmer
3.104
970683AG2-441 GEN
Solar/Wind Harmer
17.731
970681AG2-440 GEN
Solar/Wind Harmer
14.185
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.983
316239AB2-077_GEN
Solar/Wind Harmer
0.453
316238AB2-078_GEN
Solar/Wind Harmer
0.453
316233AE1-074 FULL
Solar/Wind Harmer
0.37
971281AH1-106 GEN
Solar/Wind Harmer
2.234
971283AH1-107 GEN
Solar/Wind Harmer
2.234
270494AE1-108_GEN
Solar/Wind Harmer
3.125
316118AC1-105 GEN
Solar/Wind Harmer
0.772
970831AG2-522 GEN
Solar/Wind Harmer
5.366
971285AH1-108 GEN
Adder
0.682
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
946281AF1-292 GEN
Solar/Wind Harmer
0.209
971967AH1-528 GEN
Solar/Wind Harmer
17.53
316087AB2-174 GEN
Solar/Wind Harmer
1.303
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970673AG2-436 GEN
Solar/Wind Harmer
17.985
970673AG2-436 GEN
Solar/Wind Harmer
9.106
941031AE2-094 GEN
Solar/Wind Harmer
15.864
944011AF1-069 GEN
Solar/Wind Harmer
4.971
315607AA1-063A GEN
Solar/Wind Harmer
0.854
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.213
970581AG2-369 GEN
Solar/Wind Harmer
4.483
970865AG2-541 GEN
Solar/Wind Harmer
3.349
315814AE2-033 C
Solar/Wind Harmer
7.587
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.711
3143316POE
Solar/Wind Harmer
-0.031
315652AC1-086 GEN
Solar/Wind Harmer
8.889
316318V4-068
Solar/Wind Harmer
0.196
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315833AF1-017_GEN
Solar/Wind Harmer
1.402
316349AD2-085 GEN
Solar/Wind Harmer
0.657
971447AH1-217 GEN
Solar/Wind Harmer
2.63
316311AC2-079 GEN
Solar/Wind Harmer
3.722
316132AB2-190 GEN1
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.197
316319Z2-044 C
Solar/Wind Harmer
0.403
315835AF2-110_GEN
Solar/Wind Harmer
0.908
316369SG1_INVT
Solar/Wind Harmer
1.296
315732AD1-074 GEN1
Solar/Wind Harmer
1.466
315733AD1-074 GEN2
Solar/Wind Harmer
1.466
315735AD1-075 GEN1
Solar/Wind Harmer
0.733
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
0.585
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.775
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316305AF2-043 C
Solar/Wind Harmer
0.216
316321Z2-027
Solar/Wind Harmer
0.193
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
313526AB2-022
Solar/Wind Harmer
0.193
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
972265AH1-717 GEN
Adder
4.91
3151201GRAVEL4
Adder
4.602
3151191GRAVEL3
Adder
4.544
3151211GRAVEL5
Adder
4.544
3152611GOSPORTB
Adder
0.805
3152621GOSPORTC
Adder
0.683
3152601GOSPORTA
Adder
0.63
971445AH1-216 GEN
Solar/Wind Harmer
4.395
3151081ELIZAR1
Adder
5.792
3151091ELIZAR2
Adder
5.691
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.103
3148013FISHERV
Solar/Wind Helper
0.098
3148463FAIRFLD
Solar/Wind Helper
0.118
3151921BEARGRDN G2
50/50
4.601
3144293JTRSVLE
50/50
0.746
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
316313AB2-026
Solar/Wind Harmer
0.868
316258AE1-075 C
Solar/Wind Harmer
0.782
316405AF2-144 C
Solar/Wind Harmer
0.825
3143336POWHATN
Solar/Wind Harmer
3.247
942461AE2-259 GEN
Solar/Wind Harmer
4.59
970909AG2-566 GEN
Solar/Wind Harmer
2.539
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.45
963181AG1-167 GEN
Solar/Wind Harmer
2.328
959311AF2-222 GEN
Solar/Wind Harmer
22.003
970257AG2-171 GEN
Solar/Wind Harmer
7.661
315785AD2-033 C
Solar/Wind Harmer
4.427
964241AG1-285 GEN
Solar/Wind Harmer
13.397
316131AB2-060 GEN
Solar/Wind Harmer
1.694
970221AG2-151 GEN
Solar/Wind Harmer
9.59
316478AD1-087 GEN
Solar/Wind Harmer
1.073
316486AD2-202 GEN
Solar/Wind Harmer
0.314
3147043LAWRENC
Solar/Wind Harmer
-0.007
3150861SPRUNCD
Adder
0.417
316248AF1-058 C
Solar/Wind Harmer
0.306
960061AF2-297 GEN
Solar/Wind Harmer
5.079
966621AG1-532 GEN
Solar/Wind Harmer
0.189
313506AB2-031 GEN
Solar/Wind Harmer
0.727
971683AH1-343 GEN
Solar/Wind Harmer
3.823
970917AG2-570 GEN
Solar/Wind Harmer
20.936
316365GEN2_N
Solar/Wind Harmer
0.554
3143096IRON208
Adder
0.298
3143096IRON208
Adder
0.292
3156081AA2-088 GEN
Solar/Wind Harmer
2.589
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
315839AE2-212 C
Solar/Wind Harmer
0.237
957521AF2-046 GEN
Solar/Wind Harmer
6.176
961681AG1-008 GEN
Solar/Wind Harmer
6.176
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
965281AG1-393 GEN
Solar/Wind Harmer
0.97
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.214
315813AE1-149 C
Solar/Wind Harmer
4.801
316463AE2-346 GEN
Solar/Wind Harmer
0.124
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.959
316317KELFORD C
Solar/Wind Harmer
0.361
3145823KELFORD
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
0.714
316083AB2-161 GEN
Solar/Wind Harmer
1.228
970661AG2-428 GEN
Solar/Wind Harmer
1.415
316327AA2-057 GEN
Solar/Wind Harmer
0.756
3145273HOLLAND
Solar/Wind Harmer
-0.006
970133AG2-095 GEN
Solar/Wind Harmer
0.837
3156021HOLLOMANSOL
Solar/Wind Harmer
0.996
315724AD1-057 GEN
Solar/Wind Harmer
0.424
970129AG2-093 GEN
Solar/Wind Harmer
4.142
3146206CASHIE
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.153
3146233WITAKRS
Solar/Wind Harmer
-0.005
315778AD1-151 GEN
Solar/Wind Harmer
6.319
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.378
971157AH1-035 GEN
Solar/Wind Harmer
0.905
315614AA2-178 GEN
Solar/Wind Harmer
0.779
3146376EDENTON
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.298
961611AG1-000B GEN
Solar/Wind Harmer
1.508
316320Y1-086
Solar/Wind Harmer
0.418
3145963POPLR C
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151221GRAVEL6
Adder
4.597
3151171GRAVELC
Adder
0.884
3144873MCLAUGH
Solar/Wind Harmer
0
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.866
3144216WINCHST
Adder
0.221
3150921YORKTN3
Adder
1.456
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3148013FISHERV
Solar/Wind Helper
0.171
316499AE2-029_GEN
Solar/Wind Helper
0.503
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.534
3147666LOUISA
Solar/Wind Helper
0.265
944581AF1-123 GEN
Solar/Wind Harmer
1.127
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.345
MECLTFEXP_MEC->PJM
CLTF
0.252
SIGELTFEXP_SIGE->PJM
CLTF
0.005
CPLELTFEXP_CPLE->PJM
CLTF
3.992
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.116
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.012
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.013
LAGNLTFEXP_LAGN->PJM
CLTF
1.555
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.774
TVALTFEXP_TVA->PJM
CLTF
0.758
NYPJM->LTFIMP_NY
CLTF
0.536
LGEELTFEXP_LGEE->PJM
CLTF
0.012

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:172.6 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1432.61
MW Contribution:2.16
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.938
3151911BEARGRDN G1
50/50
4.601
3144293JTRSVLE
50/50
0.746
970119AG2-088 GEN
50/50
19.705
972003AH1-546 GEN
Solar/Wind Harmer
26.72
970937AG2-583 GEN
Solar/Wind Harmer
33.599
316322AB2-045
Solar/Wind Harmer
1.495
3146776BUCKING
Solar/Wind Harmer
-0.018
316336AC2-165 C
Solar/Wind Harmer
6.302
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.82
963171AG1-166 GEN
Solar/Wind Harmer
3.104
971563AH1-280 GEN
Solar/Wind Harmer
3.104
970685AG2-442 GEN
Solar/Wind Harmer
19.859
3143226MDLTHAN
Solar/Wind Harmer
-0.017
962491AG1-098 GEN
Solar/Wind Harmer
10.562
971377AH1-170 GEN
Solar/Wind Harmer
1.918
3147623JAMES R
Solar/Wind Harmer
0.237
315693AD1-088 GEN
Solar/Wind Harmer
7.599
316237AB2-079_GEN
Solar/Wind Harmer
0.453
3143526WINTERP
Solar/Wind Harmer
-0.071
957481AF2-042 GEN
Solar/Wind Harmer
38.757
970401AG2-262 GEN
Solar/Wind Harmer
0.805
315687AD1-152 GEN
Solar/Wind Harmer
1.355
3147043LAWRENC
Adder
0.898
971065AG2-659 GEN
Solar/Wind Harmer
5.572
316129AC1-054 GEN
Solar/Wind Harmer
0.96
971795AH1-408 GEN
Solar/Wind Harmer
7.936
3150851SPRUNCC
Adder
0.417
316003AC1-222 GEN
Solar/Wind Harmer
0.924
960081AF2-299 GEN
Solar/Wind Harmer
1.049
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
3142543TWELFTH
Solar/Wind Harmer
-0.001
970919AG2-571 GEN
Solar/Wind Harmer
2.65
970087AG2-069 GEN
Solar/Wind Harmer
7.82
316023GEN1_S
Solar/Wind Harmer
0.554
940641AE2-051 GEN
Solar/Wind Harmer
7.517
3143096IRON208
Adder
0.298
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.653
962571AG1-106 GEN
Solar/Wind Harmer
1.136
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
939411AE1-173 GEN
Solar/Wind Harmer
38.95
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.803
316212AC1-099_GEN
Solar/Wind Harmer
0.674
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.029
316381AD1-082 GEN
Solar/Wind Harmer
0.694
970661AG2-428 GEN
Solar/Wind Harmer
7.982
315722AD1-056 GEN
Solar/Wind Harmer
0.771
970129AG2-093 GEN
Solar/Wind Harmer
1.678
316458AB2-190 GEN2
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.827
3146233WITAKRS
Solar/Wind Harmer
-0.029
971069AG2-661 GEN
Solar/Wind Harmer
1.154
316093AE2-104_GEN
Solar/Wind Harmer
2.113
944631AF1-128 GEN
Adder
30.658
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.772
971647AH1-324 GEN
Solar/Wind Harmer
3.605
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.775
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.535
316246AF1-032 C
Solar/Wind Harmer
0.145
3145963POPLR C
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
316174AB2-169 GEN
Solar/Wind Harmer
1.097
3151171GRAVELC
Adder
0.673
316375AC2-012 GEN
Solar/Wind Harmer
2.457
3145336SMITFLD
Solar/Wind Harmer
-0.028
3150981CHESPKA
Adder
0.789
944591AF1-124 GEN
Solar/Wind Harmer
32.38
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.798
3147666LOUISA
Solar/Wind Helper
0.46
3144293JTRSVLE
50/50
0.746
3144293JTRSVLE
50/50
0.629
970535AG2-341 GEN
50/50
2.158
3146776BUCKING
Solar/Wind Harmer
-0.177
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.372
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.88
963191AG1-168 GEN
Solar/Wind Harmer
2.328
971741AH1-377 GEN
Solar/Wind Harmer
28.01
316034AC1-036 C
Solar/Wind Harmer
0.38
970323AG2-213 GEN
Solar/Wind Harmer
10.214
971775AH1-396 GEN
Solar/Wind Harmer
1.455
971223AH1-071 GEN
Solar/Wind Harmer
2.076
313527AB2-043 GEN
Solar/Wind Harmer
2.493
971489AH1-241 GEN
Solar/Wind Harmer
9.104
3143526WINTERP
Solar/Wind Harmer
-0.071
962561AG1-105 GEN
Solar/Wind Harmer
7.195
939181AE1-148 GEN
Solar/Wind Harmer
7.148
970099AG2-077 GEN
Solar/Wind Harmer
15.503
964791AG1-342 GEN
Solar/Wind Harmer
2.634
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970933AG2-581 GEN
Solar/Wind Harmer
9.649
316181AB2-040 GEN
Solar/Wind Harmer
1.262
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.983
3145593CAROLNA
Solar/Wind Harmer
0.073
972187AH1-678 GEN
Adder
2.2
972185AH1-677 GEN
Adder
4.302
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
316274AC1-208 GEN
Solar/Wind Harmer
0.849
316240AF1-291 C
Solar/Wind Harmer
0.235
944641AF1-129 GEN
Adder
33.028
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.793
970657AG2-426 GEN
Solar/Wind Harmer
2.358
970657AG2-426 GEN
Solar/Wind Harmer
0.493
316065AD1-022 GEN
Solar/Wind Harmer
3.643
316033AB2-134 GEN
Solar/Wind Harmer
2.34
315697AD1-025 GEN
Solar/Wind Harmer
1.468
3142366NRTHEST
Adder
0.21
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.298
316433W1029_GEN2
Solar/Wind Harmer
1.298
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316222AC1-221 GEN
Solar/Wind Harmer
0.722
3130086AYDLETT
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.75
3142956BIRDNECK
Solar/Wind Harmer
0.381
316316AC1-027 C
Solar/Wind Harmer
0.218
316236AE1-162_GEN
Solar/Wind Harmer
0.214
316036AC1-147 C
Solar/Wind Harmer
0.192
3150991CHESPKB
Adder
0.662
3150991CHESPKB
Adder
0.646
3150691DARBY 3
Adder
4.502
3150701DARBY 4
Adder
4.491
3150681DARBY 2
Adder
4.486
3150671DARBY 1
Adder
4.481
966001AG1-469 GEN
Solar/Wind Helper
0.186
3151921BEARGRDN G2
50/50
4.601
3144293JTRSVLE
50/50
0.746
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
316313AB2-026
Solar/Wind Harmer
0.868
316258AE1-075 C
Solar/Wind Harmer
0.782
316405AF2-144 C
Solar/Wind Harmer
0.825
3143336POWHATN
Solar/Wind Harmer
3.247
942461AE2-259 GEN
Solar/Wind Harmer
4.59
970909AG2-566 GEN
Solar/Wind Harmer
2.539
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.45
963181AG1-167 GEN
Solar/Wind Harmer
2.328
959311AF2-222 GEN
Solar/Wind Harmer
22.003
970257AG2-171 GEN
Solar/Wind Harmer
7.661
315785AD2-033 C
Solar/Wind Harmer
4.427
964241AG1-285 GEN
Solar/Wind Harmer
13.397
316131AB2-060 GEN
Solar/Wind Harmer
1.694
970221AG2-151 GEN
Solar/Wind Harmer
9.59
316478AD1-087 GEN
Solar/Wind Harmer
1.073
316486AD2-202 GEN
Solar/Wind Harmer
0.314
3147043LAWRENC
Solar/Wind Harmer
-0.007
3150861SPRUNCD
Adder
0.417
316248AF1-058 C
Solar/Wind Harmer
0.306
960061AF2-297 GEN
Solar/Wind Harmer
5.079
966621AG1-532 GEN
Solar/Wind Harmer
0.189
313506AB2-031 GEN
Solar/Wind Harmer
0.727
971683AH1-343 GEN
Solar/Wind Harmer
3.823
970917AG2-570 GEN
Solar/Wind Harmer
20.936
316365GEN2_N
Solar/Wind Harmer
0.554
3143096IRON208
Adder
0.298
3143096IRON208
Adder
0.292
3156081AA2-088 GEN
Solar/Wind Harmer
2.589
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
315839AE2-212 C
Solar/Wind Harmer
0.237
957521AF2-046 GEN
Solar/Wind Harmer
6.176
961681AG1-008 GEN
Solar/Wind Harmer
6.176
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
965281AG1-393 GEN
Solar/Wind Harmer
0.97
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.214
315813AE1-149 C
Solar/Wind Harmer
4.801
316463AE2-346 GEN
Solar/Wind Harmer
0.124
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.959
316317KELFORD C
Solar/Wind Harmer
0.361
3145823KELFORD
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
0.714
316083AB2-161 GEN
Solar/Wind Harmer
1.228
970661AG2-428 GEN
Solar/Wind Harmer
1.415
316327AA2-057 GEN
Solar/Wind Harmer
0.756
3145273HOLLAND
Solar/Wind Harmer
-0.006
970133AG2-095 GEN
Solar/Wind Harmer
0.837
3156021HOLLOMANSOL
Solar/Wind Harmer
0.996
315724AD1-057 GEN
Solar/Wind Harmer
0.424
970129AG2-093 GEN
Solar/Wind Harmer
4.142
3146206CASHIE
Solar/Wind Harmer
-0.007
972205AH1-687 GEN
50/50
22.442
316303AF2-085
50/50
2.627
971845AH1-439 GEN
Solar/Wind Harmer
23.203
970285AG2-188 GEN
Solar/Wind Harmer
36.921
315657AE1-056 GEN
Solar/Wind Harmer
9.87
946301AF1-294 GEN
Solar/Wind Harmer
6.363
961791AG1-021 GEN
Solar/Wind Harmer
3.104
970683AG2-441 GEN
Solar/Wind Harmer
17.731
970681AG2-440 GEN
Solar/Wind Harmer
14.185
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.983
316239AB2-077_GEN
Solar/Wind Harmer
0.453
316238AB2-078_GEN
Solar/Wind Harmer
0.453
316233AE1-074 FULL
Solar/Wind Harmer
0.37
971281AH1-106 GEN
Solar/Wind Harmer
2.234
971283AH1-107 GEN
Solar/Wind Harmer
2.234
270494AE1-108_GEN
Solar/Wind Harmer
3.125
316118AC1-105 GEN
Solar/Wind Harmer
0.772
970831AG2-522 GEN
Solar/Wind Harmer
5.366
971285AH1-108 GEN
Adder
0.682
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
946281AF1-292 GEN
Solar/Wind Harmer
0.209
971967AH1-528 GEN
Solar/Wind Harmer
17.53
316087AB2-174 GEN
Solar/Wind Harmer
1.303
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970673AG2-436 GEN
Solar/Wind Harmer
17.985
970673AG2-436 GEN
Solar/Wind Harmer
9.106
941031AE2-094 GEN
Solar/Wind Harmer
15.864
944011AF1-069 GEN
Solar/Wind Harmer
4.971
315607AA1-063A GEN
Solar/Wind Harmer
0.854
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.213
970581AG2-369 GEN
Solar/Wind Harmer
4.483
970865AG2-541 GEN
Solar/Wind Harmer
3.349
315814AE2-033 C
Solar/Wind Harmer
7.587
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.711
3143316POE
Solar/Wind Harmer
-0.031
315652AC1-086 GEN
Solar/Wind Harmer
8.889
316318V4-068
Solar/Wind Harmer
0.196
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315833AF1-017_GEN
Solar/Wind Harmer
1.402
316349AD2-085 GEN
Solar/Wind Harmer
0.657
971447AH1-217 GEN
Solar/Wind Harmer
2.63
316311AC2-079 GEN
Solar/Wind Harmer
3.722
316132AB2-190 GEN1
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.197
316319Z2-044 C
Solar/Wind Harmer
0.403
315835AF2-110_GEN
Solar/Wind Harmer
0.908
316369SG1_INVT
Solar/Wind Harmer
1.296
315732AD1-074 GEN1
Solar/Wind Harmer
1.466
315733AD1-074 GEN2
Solar/Wind Harmer
1.466
315735AD1-075 GEN1
Solar/Wind Harmer
0.733
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
0.585
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.775
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316305AF2-043 C
Solar/Wind Harmer
0.216
316321Z2-027
Solar/Wind Harmer
0.193
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
313526AB2-022
Solar/Wind Harmer
0.193
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
972265AH1-717 GEN
Adder
4.91
3151201GRAVEL4
Adder
4.602
3151191GRAVEL3
Adder
4.544
3151211GRAVEL5
Adder
4.544
3152611GOSPORTB
Adder
0.805
3152621GOSPORTC
Adder
0.683
3152601GOSPORTA
Adder
0.63
971445AH1-216 GEN
Solar/Wind Harmer
4.395
3151081ELIZAR1
Adder
5.792
3151091ELIZAR2
Adder
5.691
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.103
3148013FISHERV
Solar/Wind Helper
0.098
3148463FAIRFLD
Solar/Wind Helper
0.118
3146233WITAKRS
Solar/Wind Harmer
0.153
3146233WITAKRS
Solar/Wind Harmer
-0.005
315778AD1-151 GEN
Solar/Wind Harmer
6.319
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.378
971157AH1-035 GEN
Solar/Wind Harmer
0.905
315614AA2-178 GEN
Solar/Wind Harmer
0.779
3146376EDENTON
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.298
961611AG1-000B GEN
Solar/Wind Harmer
1.508
316320Y1-086
Solar/Wind Harmer
0.418
3145963POPLR C
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151221GRAVEL6
Adder
4.597
3151171GRAVELC
Adder
0.884
3144873MCLAUGH
Solar/Wind Harmer
0
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.866
3144216WINCHST
Adder
0.221
3150921YORKTN3
Adder
1.456
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3148013FISHERV
Solar/Wind Helper
0.171
316499AE2-029_GEN
Solar/Wind Helper
0.503
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.534
3147666LOUISA
Solar/Wind Helper
0.265
944581AF1-123 GEN
Solar/Wind Harmer
1.127
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.345
MECLTFEXP_MEC->PJM
CLTF
0.252
SIGELTFEXP_SIGE->PJM
CLTF
0.005
CPLELTFEXP_CPLE->PJM
CLTF
3.992
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.116
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.012
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.013
LAGNLTFEXP_LAGN->PJM
CLTF
1.555
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.774
TVALTFEXP_TVA->PJM
CLTF
0.758
NYPJM->LTFIMP_NY
CLTF
0.536
LGEELTFEXP_LGEE->PJM
CLTF
0.012

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:157.52 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1069.03
MW Contribution:2.18
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
7.734
3151911BEARGRDN G1
50/50
5.993
3144293JTRSVLE
50/50
0.881
3151601KERR 3
50/50
0.215
3151581KERR 1
50/50
0.077
3151531CLOVER1
50/50
2.214
3147043LAWRENC
50/50
0.833
3151261ROARAP2
50/50
0.071
970937AG2-583 GEN
Solar/Wind Harmer
39.544
316336AC2-165 C
Solar/Wind Harmer
0.025
972003AH1-546 GEN
Solar/Wind Harmer
26.303
316322AB2-045
Solar/Wind Harmer
0.004
3146776BUCKING
Solar/Wind Harmer
0.202
3146926FARMVIL
Solar/Wind Harmer
0.234
971377AH1-170 GEN
Solar/Wind Harmer
2.874
3147623JAMES R
Solar/Wind Harmer
0.624
963171AG1-166 GEN
Solar/Wind Harmer
1.391
971563AH1-280 GEN
Solar/Wind Harmer
2.782
970685AG2-442 GEN
Solar/Wind Harmer
17.514
962491AG1-098 GEN
Solar/Wind Harmer
8.209
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
6.543
970401AG2-262 GEN
Solar/Wind Harmer
0.652
957481AF2-042 GEN
Solar/Wind Harmer
26.84
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.856
316129AC1-054 GEN
Solar/Wind Harmer
0.33
316003AC1-222 GEN
Solar/Wind Harmer
0.002
971795AH1-408 GEN
Solar/Wind Harmer
5.259
960081AF2-299 GEN
Solar/Wind Harmer
0.593
972205AH1-687 GEN
50/50
29.229
3151611KERR 4
50/50
0.215
3151621KERR 5
50/50
0.215
3151631KERR 6
50/50
0.215
3151641KERR 7
50/50
0.215
3151541CLOVER2
50/50
2.204
3151281ROARAP4
50/50
0.069
3151281ROARAP4
50/50
0.065
971845AH1-439 GEN
Solar/Wind Harmer
22.434
970285AG2-188 GEN
Solar/Wind Harmer
37.679
315657AE1-056 GEN
Solar/Wind Harmer
9.629
946301AF1-294 GEN
Solar/Wind Harmer
5.147
961791AG1-021 GEN
Solar/Wind Harmer
2.504
970683AG2-441 GEN
Solar/Wind Harmer
15.638
970681AG2-440 GEN
Solar/Wind Harmer
12.51
270494AE1-108_GEN
Solar/Wind Harmer
2.538
3144303KENBRDG
Solar/Wind Harmer
0.165
971443AH1-215 GEN
Solar/Wind Harmer
3.431
971447AH1-217 GEN
Solar/Wind Harmer
5.812
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.256
3147173SINAI
Solar/Wind Harmer
0.087
3147243WELCO
Solar/Wind Harmer
0.055
970831AG2-522 GEN
Solar/Wind Harmer
3.614
970865AG2-541 GEN
Solar/Wind Harmer
2.528
316123AC1-075 GEN
Solar/Wind Harmer
0.087
970165AG2-112 GEN
Solar/Wind Harmer
0.513
970163AG2-111 GEN
Solar/Wind Harmer
0.49
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.232
3138266HYDRAULIC
Solar/Wind Helper
0.014
3138266HYDRAULIC
Solar/Wind Helper
0.009
3151921BEARGRDN G2
50/50
5.993
3144293JTRSVLE
50/50
0.881
3151591KERR 2
50/50
0.215
970413AG2-270 GEN
50/50
9.663
3151261ROARAP2
50/50
0.069
3146776BUCKING
Solar/Wind Harmer
0.182
3146926FARMVIL
Solar/Wind Harmer
0.234
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
970909AG2-566 GEN
Solar/Wind Harmer
3.007
3147133PAMPLIN
Solar/Wind Harmer
0.876
971193AH1-056 GEN
Solar/Wind Harmer
16.999
970221AG2-151 GEN
Solar/Wind Harmer
14.368
963181AG1-167 GEN
Solar/Wind Harmer
1.043
959311AF2-222 GEN
Solar/Wind Harmer
19.082
970257AG2-171 GEN
Solar/Wind Harmer
6.613
315785AD2-033 C
Solar/Wind Harmer
1.59
964241AG1-285 GEN
Solar/Wind Harmer
11.084
316131AB2-060 GEN
Solar/Wind Harmer
0.467
316478AD1-087 GEN
Solar/Wind Harmer
0.361
316486AD2-202 GEN
Solar/Wind Harmer
0.106
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.73
3147043LAWRENC
Solar/Wind Harmer
0.052
958131AF2-107 GEN
Solar/Wind Harmer
2.449
971683AH1-343 GEN
Solar/Wind Harmer
2.857
313506AB2-031 GEN
Solar/Wind Harmer
0.184
3144293JTRSVLE
50/50
0.881
3144293JTRSVLE
50/50
0.742
970535AG2-341 GEN
50/50
2.183
3152661PLYWOOD A
50/50
0.212
3146776BUCKING
Solar/Wind Harmer
2.017
3146776BUCKING
Solar/Wind Harmer
0.163
970301AG2-198 GEN
Solar/Wind Harmer
12.027
3147133PAMPLIN
Solar/Wind Harmer
0.279
3147133PAMPLIN
Solar/Wind Harmer
0.223
971489AH1-241 GEN
Solar/Wind Harmer
14.368
958211AF2-115 GEN
Solar/Wind Harmer
3.13
963191AG1-168 GEN
Solar/Wind Harmer
1.043
971741AH1-377 GEN
Solar/Wind Harmer
24.65
316034AC1-036 C
Solar/Wind Harmer
0.015
970323AG2-213 GEN
Solar/Wind Harmer
8.817
971775AH1-396 GEN
Solar/Wind Harmer
0.331
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
5.577
315821AE2-092 GEN
Solar/Wind Harmer
0.007
939181AE1-148 GEN
Solar/Wind Harmer
5.338
964791AG1-342 GEN
Solar/Wind Harmer
2.134
3146843MT LREL
Solar/Wind Harmer
0.111
3146843MT LREL
Solar/Wind Harmer
0.111
970099AG2-077 GEN
Solar/Wind Harmer
10.736
970933AG2-581 GEN
Solar/Wind Harmer
5.58
316181AB2-040 GEN
Solar/Wind Harmer
0.086
942751AE2-291 GEN
Solar/Wind Harmer
3.114
3145593CAROLNA
Solar/Wind Harmer
0.057
3145593CAROLNA
Solar/Wind Harmer
0.057
966811AG1-552 GEN
Solar/Wind Harmer
0.619
3145593CAROLNA
Solar/Wind Harmer
0.071
966001AG1-469 GEN
Solar/Wind Helper
0.14
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.534
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.133
MECLTFEXP_MEC->PJM
CLTF
0.325
SIGELTFEXP_SIGE->PJM
CLTF
0.008
CPLELTFEXP_CPLE->PJM
CLTF
3.067
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.792
LAGNLTFEXP_LAGN->PJM
CLTF
1.359
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.117
TVALTFEXP_TVA->PJM
CLTF
0.671
NYPJM->LTFIMP_NY
CLTF
0.488
LGEELTFEXP_LGEE->PJM
CLTF
0.069
WECLTFEXP_WEC->PJM
CLTF
0.029

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 202712_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 202712_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:147.93 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1227.79
MW Contribution:2.18
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
7.734
3151911BEARGRDN G1
50/50
5.993
3144293JTRSVLE
50/50
0.881
970937AG2-583 GEN
Solar/Wind Harmer
52.066
972205AH1-687 GEN
50/50
29.229
971845AH1-439 GEN
Solar/Wind Harmer
29.538
970285AG2-188 GEN
Solar/Wind Harmer
46.824
315657AE1-056 GEN
Solar/Wind Harmer
11.763
946301AF1-294 GEN
Solar/Wind Harmer
7.51
961791AG1-021 GEN
Solar/Wind Harmer
3.664
970683AG2-441 GEN
Solar/Wind Harmer
20.59
970681AG2-440 GEN
Solar/Wind Harmer
16.472
270494AE1-108_GEN
Solar/Wind Harmer
6.187
3144303KENBRDG
Solar/Wind Harmer
-0.019
971443AH1-215 GEN
Solar/Wind Harmer
4.518
971447AH1-217 GEN
Solar/Wind Harmer
7.652
316239AB2-077_GEN
Solar/Wind Harmer
0.475
316238AB2-078_GEN
Solar/Wind Harmer
0.475
316118AC1-105 GEN
Solar/Wind Harmer
0.766
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
970831AG2-522 GEN
Solar/Wind Harmer
4.758
970865AG2-541 GEN
Solar/Wind Harmer
3.329
316123AC1-075 GEN
Solar/Wind Harmer
0.768
970165AG2-112 GEN
Solar/Wind Harmer
0.676
970163AG2-111 GEN
Solar/Wind Harmer
0.645
946281AF1-292 GEN
Solar/Wind Harmer
0.155
316087AB2-174 GEN
Solar/Wind Harmer
0.965
3137643SOCKMAN
Solar/Wind Harmer
-0.026
3138266HYDRAULIC
Solar/Wind Helper
0.014
3138266HYDRAULIC
Solar/Wind Helper
0.009
3144293JTRSVLE
50/50
0.881
3144293JTRSVLE
50/50
0.742
970535AG2-341 GEN
50/50
2.183
3146776BUCKING
Solar/Wind Harmer
-0.226
3146776BUCKING
Solar/Wind Harmer
-0.018
970301AG2-198 GEN
Solar/Wind Harmer
15.836
3147133PAMPLIN
Solar/Wind Harmer
-0.031
3147133PAMPLIN
Solar/Wind Harmer
-0.025
971489AH1-241 GEN
Solar/Wind Harmer
17.959
958211AF2-115 GEN
Solar/Wind Harmer
4.579
963191AG1-168 GEN
Solar/Wind Harmer
2.748
971741AH1-377 GEN
Solar/Wind Harmer
32.456
316034AC1-036 C
Solar/Wind Harmer
0.432
970323AG2-213 GEN
Solar/Wind Harmer
11.609
971775AH1-396 GEN
Solar/Wind Harmer
1.653
313527AB2-043 GEN
Solar/Wind Harmer
2.63
962561AG1-105 GEN
Solar/Wind Harmer
7.343
315821AE2-092 GEN
Solar/Wind Harmer
2.71
939181AE1-148 GEN
Solar/Wind Harmer
7.029
964791AG1-342 GEN
Solar/Wind Harmer
2.668
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.136
970933AG2-581 GEN
Solar/Wind Harmer
7.348
316181AB2-040 GEN
Solar/Wind Harmer
0.933
942751AE2-291 GEN
Solar/Wind Harmer
4.1
3145593CAROLNA
Solar/Wind Harmer
-0.006
3145593CAROLNA
Solar/Wind Harmer
-0.006
966811AG1-552 GEN
Solar/Wind Harmer
0.721
3145593CAROLNA
Solar/Wind Harmer
0.053
966001AG1-469 GEN
Solar/Wind Helper
0.14
3151921BEARGRDN G2
50/50
5.993
3144293JTRSVLE
50/50
0.881
3146776BUCKING
Solar/Wind Harmer
-0.02
3146926FARMVIL
Solar/Wind Harmer
-0.026
942461AE2-259 GEN
Solar/Wind Harmer
5.592
970909AG2-566 GEN
Solar/Wind Harmer
3.007
3147133PAMPLIN
Solar/Wind Harmer
-0.098
971193AH1-056 GEN
Solar/Wind Harmer
19.605
970221AG2-151 GEN
Solar/Wind Harmer
18.917
963181AG1-167 GEN
Solar/Wind Harmer
2.748
959311AF2-222 GEN
Solar/Wind Harmer
25.175
970257AG2-171 GEN
Solar/Wind Harmer
8.707
315785AD2-033 C
Solar/Wind Harmer
4.981
964241AG1-285 GEN
Solar/Wind Harmer
14.595
316131AB2-060 GEN
Solar/Wind Harmer
1.799
316478AD1-087 GEN
Solar/Wind Harmer
1.005
316486AD2-202 GEN
Solar/Wind Harmer
0.294
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.911
3147043LAWRENC
Solar/Wind Harmer
-0.006
958131AF2-107 GEN
Solar/Wind Harmer
3.26
971683AH1-343 GEN
Solar/Wind Harmer
3.762
966621AG1-532 GEN
Solar/Wind Harmer
0.141
313506AB2-031 GEN
Solar/Wind Harmer
0.538
316336AC2-165 C
Solar/Wind Harmer
12.588
972003AH1-546 GEN
Solar/Wind Harmer
34.691
316322AB2-045
Solar/Wind Harmer
1.907
3146776BUCKING
Solar/Wind Harmer
-0.022
3146926FARMVIL
Solar/Wind Harmer
-0.026
971377AH1-170 GEN
Solar/Wind Harmer
3.783
3147623JAMES R
Solar/Wind Harmer
0.468
963171AG1-166 GEN
Solar/Wind Harmer
3.664
971563AH1-280 GEN
Solar/Wind Harmer
3.664
970685AG2-442 GEN
Solar/Wind Harmer
23.061
962491AG1-098 GEN
Solar/Wind Harmer
10.808
316237AB2-079_GEN
Solar/Wind Harmer
0.475
315693AD1-088 GEN
Solar/Wind Harmer
7.658
970401AG2-262 GEN
Solar/Wind Harmer
0.815
957481AF2-042 GEN
Solar/Wind Harmer
35.339
315687AD1-152 GEN
Solar/Wind Harmer
1.264
971065AG2-659 GEN
Solar/Wind Harmer
5.078
316129AC1-054 GEN
Solar/Wind Harmer
0.863
3147043LAWRENC
Adder
0.785
316003AC1-222 GEN
Solar/Wind Harmer
0.902
971795AH1-408 GEN
Solar/Wind Harmer
6.647
960081AF2-299 GEN
Solar/Wind Harmer
0.78
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.534
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.133
MECLTFEXP_MEC->PJM
CLTF
0.325
SIGELTFEXP_SIGE->PJM
CLTF
0.008
CPLELTFEXP_CPLE->PJM
CLTF
3.067
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.792
LAGNLTFEXP_LAGN->PJM
CLTF
1.359
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.117
TVALTFEXP_TVA->PJM
CLTF
0.671
NYPJM->LTFIMP_NY
CLTF
0.488
LGEELTFEXP_LGEE->PJM
CLTF
0.069
WECLTFEXP_WEC->PJM
CLTF
0.029

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B3_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: BREMO B3_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:129.14 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1071.9
MW Contribution:2.13
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
6.456
3151911BEARGRDN G1
50/50
5.002
3144293JTRSVLE
50/50
0.78
972003AH1-546 GEN
Solar/Wind Harmer
29.014
970937AG2-583 GEN
Solar/Wind Harmer
35.582
316322AB2-045
Solar/Wind Harmer
1.612
3146776BUCKING
Solar/Wind Harmer
-0.019
3146926FARMVIL
Solar/Wind Harmer
-0.022
316336AC2-165 C
Solar/Wind Harmer
6.353
3143336POWHATN
Solar/Wind Harmer
3.74
963171AG1-166 GEN
Solar/Wind Harmer
3.245
971563AH1-280 GEN
Solar/Wind Harmer
3.245
970685AG2-442 GEN
Solar/Wind Harmer
20.625
962491AG1-098 GEN
Solar/Wind Harmer
10.531
315693AD1-088 GEN
Solar/Wind Harmer
7.538
316237AB2-079_GEN
Solar/Wind Harmer
0.452
3143226MDLTHAN
Solar/Wind Harmer
-0.012
970401AG2-262 GEN
Solar/Wind Harmer
0.785
957481AF2-042 GEN
Solar/Wind Harmer
37.275
315687AD1-152 GEN
Solar/Wind Harmer
1.296
971065AG2-659 GEN
Solar/Wind Harmer
5.329
3147043LAWRENC
Adder
0.854
316129AC1-054 GEN
Solar/Wind Harmer
0.915
3143526WINTERP
Solar/Wind Harmer
-0.053
971795AH1-408 GEN
Solar/Wind Harmer
7.462
316003AC1-222 GEN
Solar/Wind Harmer
0.864
960081AF2-299 GEN
Solar/Wind Harmer
0.959
3150851SPRUNCC
Adder
0.323
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.095
970919AG2-571 GEN
Solar/Wind Harmer
2.334
970087AG2-069 GEN
Solar/Wind Harmer
6.886
316023GEN1_S
Solar/Wind Harmer
0.488
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.463
962571AG1-106 GEN
Solar/Wind Harmer
1.005
3145893MURPHYS
Solar/Wind Harmer
-0.028
3145893MURPHYS
Solar/Wind Harmer
0.207
316212AC1-099_GEN
Solar/Wind Harmer
0.6
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.007
940641AE2-051 GEN
Solar/Wind Harmer
6.428
3146173TUNIS
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
3145683EARLEYS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
33.3
315722AD1-056 GEN
Solar/Wind Harmer
0.679
3146233WITAKRS
Solar/Wind Harmer
-0.026
3143096IRON208
Adder
0.238
970659AG2-427 GEN
Solar/Wind Harmer
3.387
316381AD1-082 GEN
Solar/Wind Harmer
0.584
315671AE2-027_GEN
Solar/Wind Harmer
4.776
3146206CASHIE
Solar/Wind Harmer
-0.006
971547AH1-271 GEN
Solar/Wind Harmer
1.59
970661AG2-428 GEN
Solar/Wind Harmer
6.738
3147983MERCK5
Solar/Wind Helper
0.064
972205AH1-687 GEN
50/50
24.399
971845AH1-439 GEN
Solar/Wind Harmer
25.003
970285AG2-188 GEN
Solar/Wind Harmer
39.727
315657AE1-056 GEN
Solar/Wind Harmer
10.359
946301AF1-294 GEN
Solar/Wind Harmer
6.652
961791AG1-021 GEN
Solar/Wind Harmer
3.245
970683AG2-441 GEN
Solar/Wind Harmer
18.415
970681AG2-440 GEN
Solar/Wind Harmer
14.732
3144303KENBRDG
Solar/Wind Harmer
-0.017
971443AH1-215 GEN
Solar/Wind Harmer
4.098
316239AB2-077_GEN
Solar/Wind Harmer
0.452
316238AB2-078_GEN
Solar/Wind Harmer
0.452
316118AC1-105 GEN
Solar/Wind Harmer
0.743
316233AE1-074 FULL
Solar/Wind Harmer
0.277
971281AH1-106 GEN
Solar/Wind Harmer
1.674
971283AH1-107 GEN
Solar/Wind Harmer
1.674
970831AG2-522 GEN
Solar/Wind Harmer
5.097
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
946281AF1-292 GEN
Solar/Wind Harmer
0.191
971967AH1-528 GEN
Solar/Wind Harmer
15.717
316087AB2-174 GEN
Solar/Wind Harmer
1.189
3137643SOCKMAN
Solar/Wind Harmer
-0.032
971285AH1-108 GEN
Adder
0.528
315607AA1-063A GEN
Solar/Wind Harmer
0.769
3146043SEABORD
Solar/Wind Harmer
-0.008
970673AG2-436 GEN
Solar/Wind Harmer
15.733
970673AG2-436 GEN
Solar/Wind Harmer
7.966
970865AG2-541 GEN
Solar/Wind Harmer
3.042
941031AE2-094 GEN
Solar/Wind Harmer
13.777
944011AF1-069 GEN
Solar/Wind Harmer
4.317
970085AG2-068 GEN
Solar/Wind Harmer
4.591
970581AG2-369 GEN
Solar/Wind Harmer
3.948
965291AG1-394 GEN
Solar/Wind Harmer
0.631
315814AE2-033 C
Solar/Wind Harmer
6.526
316315AB2-025 C
Solar/Wind Harmer
0.189
315652AC1-086 GEN
Solar/Wind Harmer
7.864
316318V4-068
Solar/Wind Harmer
0.174
3145893MURPHYS
Solar/Wind Harmer
-0.019
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.027
3145513AHOSKIE
Solar/Wind Harmer
0.059
961941AG1-037 GEN
Solar/Wind Harmer
0.051
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
3143316POE
Solar/Wind Harmer
-0.026
316319Z2-044 C
Solar/Wind Harmer
0.356
3146206CASHIE
Solar/Wind Harmer
-0.006
970601AG2-382 GEN
Solar/Wind Harmer
2.783
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.164
3148013FISHERV
Solar/Wind Helper
0.157
3148463FAIRFLD
Solar/Wind Helper
0.142
3144293JTRSVLE
50/50
0.78
3144293JTRSVLE
50/50
0.657
970535AG2-341 GEN
50/50
2.128
3146776BUCKING
Solar/Wind Harmer
-0.191
3146776BUCKING
Solar/Wind Harmer
-0.016
970301AG2-198 GEN
Solar/Wind Harmer
14.025
3147133PAMPLIN
Solar/Wind Harmer
-0.028
3147133PAMPLIN
Solar/Wind Harmer
-0.022
958211AF2-115 GEN
Solar/Wind Harmer
4.056
963191AG1-168 GEN
Solar/Wind Harmer
2.434
971741AH1-377 GEN
Solar/Wind Harmer
29.148
316034AC1-036 C
Solar/Wind Harmer
0.391
970323AG2-213 GEN
Solar/Wind Harmer
10.518
971775AH1-396 GEN
Solar/Wind Harmer
1.498
313527AB2-043 GEN
Solar/Wind Harmer
2.495
962561AG1-105 GEN
Solar/Wind Harmer
7.049
939181AE1-148 GEN
Solar/Wind Harmer
6.984
971223AH1-071 GEN
Solar/Wind Harmer
1.533
964791AG1-342 GEN
Solar/Wind Harmer
2.568
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.91
3143526WINTERP
Solar/Wind Harmer
-0.053
970933AG2-581 GEN
Solar/Wind Harmer
8.884
316181AB2-040 GEN
Solar/Wind Harmer
1.151
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.893
3145593CAROLNA
Solar/Wind Harmer
0.066
3145783HORNRTN
Solar/Wind Harmer
0.925
3145783HORNRTN
Solar/Wind Harmer
0.74
3145783HORNRTN
Solar/Wind Harmer
0.231
3145783HORNRTN
Solar/Wind Harmer
0.092
316426AA2-053 GEN
Solar/Wind Harmer
0.779
972187AH1-678 GEN
Adder
1.94
972185AH1-677 GEN
Adder
3.777
316274AC1-208 GEN
Solar/Wind Harmer
0.758
3144356SAPONY
Solar/Wind Harmer
0.244
3145893MURPHYS
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145796HORNRTN
Solar/Wind Harmer
-0.021
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
315742AE1-103 GEN
Solar/Wind Harmer
0.691
316222AC1-221 GEN
Solar/Wind Harmer
0.652
316240AF1-291 C
Solar/Wind Harmer
0.193
944641AF1-129 GEN
Adder
26.988
970657AG2-426 GEN
Solar/Wind Harmer
1.987
970657AG2-426 GEN
Solar/Wind Harmer
0.415
316065AD1-022 GEN
Solar/Wind Harmer
3.168
315821AE2-092 GEN
Solar/Wind Helper
6.532
966001AG1-469 GEN
Solar/Wind Helper
0.168
3132123MT JACKSON
Solar/Wind Helper
0.376
3151921BEARGRDN G2
50/50
5.002
3144293JTRSVLE
50/50
0.78
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.022
942461AE2-259 GEN
Solar/Wind Harmer
4.861
316313AB2-026
Solar/Wind Harmer
0.85
316258AE1-075 C
Solar/Wind Harmer
0.765
316405AF2-144 C
Solar/Wind Harmer
0.807
3143336POWHATN
Solar/Wind Harmer
3.179
970909AG2-566 GEN
Solar/Wind Harmer
2.663
3147133PAMPLIN
Solar/Wind Harmer
-0.086
971193AH1-056 GEN
Solar/Wind Harmer
17.264
963181AG1-167 GEN
Solar/Wind Harmer
2.434
959311AF2-222 GEN
Solar/Wind Harmer
22.717
970257AG2-171 GEN
Solar/Wind Harmer
7.889
315785AD2-033 C
Solar/Wind Harmer
4.54
964241AG1-285 GEN
Solar/Wind Harmer
13.569
316131AB2-060 GEN
Solar/Wind Harmer
1.699
316478AD1-087 GEN
Solar/Wind Harmer
1.036
316486AD2-202 GEN
Solar/Wind Harmer
0.304
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.29
960061AF2-297 GEN
Solar/Wind Harmer
4.81
966621AG1-532 GEN
Solar/Wind Harmer
0.173
313506AB2-031 GEN
Solar/Wind Harmer
0.663
971683AH1-343 GEN
Solar/Wind Harmer
3.528
3150861SPRUNCD
Adder
0.323
970917AG2-570 GEN
Solar/Wind Harmer
18.441
316365GEN2_N
Solar/Wind Harmer
0.488
3156081AA2-088 GEN
Solar/Wind Harmer
2.294
3146263WOODLND
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.049
3145893MURPHYS
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.463
961681AG1-008 GEN
Solar/Wind Harmer
5.463
316210AC1-098 GEN
Solar/Wind Harmer
1.08
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316463AE2-346 GEN
Solar/Wind Harmer
0.11
316140AB2-099
Solar/Wind Harmer
0.046
962331AG1-082 GEN
Solar/Wind Harmer
0.846
316317KELFORD C
Solar/Wind Harmer
0.319
3145823KELFORD
Solar/Wind Harmer
-0.007
316327AA2-057 GEN
Solar/Wind Harmer
0.671
315724AD1-057 GEN
Solar/Wind Harmer
0.374
315839AE2-212 C
Solar/Wind Harmer
0.195
3145273HOLLAND
Solar/Wind Harmer
-0.005
3156021HOLLOMANSOL
Solar/Wind Harmer
0.87
3146233WITAKRS
Solar/Wind Harmer
0.135
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
4.015
965281AG1-393 GEN
Solar/Wind Harmer
0.8
3143096IRON208
Adder
0.238
3143096IRON208
Adder
0.233
970659AG2-427 GEN
Solar/Wind Harmer
0.6
316083AB2-161 GEN
Solar/Wind Harmer
1.033
3146206CASHIE
Solar/Wind Harmer
-0.006
316283AC2-100 C
Solar/Wind Harmer
0.599
970661AG2-428 GEN
Solar/Wind Harmer
1.194
3148013FISHERV
Solar/Wind Helper
0.273
316499AE2-029_GEN
Solar/Wind Helper
0.588
315616AA1-038_C
Solar/Wind Helper
0.641
3132273ORANGE
Solar/Wind Helper
0.023
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.127
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.049
CPLELTFEXP_CPLE->PJM
CLTF
3.425
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.931
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.181
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.543
LAGNLTFEXP_LAGN->PJM
CLTF
0.85
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.313
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.396
NYPJM->LTFIMP_NY
CLTF
0.338

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.86 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:765.97
MW Contribution:1.89
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
21.569
316303AF2-085
50/50
1.694
3151541CLOVER2
50/50
2.007
3151611KERR 4
50/50
0.192
3151621KERR 5
50/50
0.192
3151631KERR 6
50/50
0.192
3151641KERR 7
50/50
0.192
3151281ROARAP4
50/50
0.075
3151281ROARAP4
50/50
0.07
971285AH1-108 GEN
50/50
0.486
963041AG1-153 GEN
50/50
1.59
315244AE2-183_ST
50/50
1.681
971845AH1-439 GEN
Solar/Wind Harmer
16.786
970285AG2-188 GEN
Solar/Wind Harmer
28.258
315657AE1-056 GEN
Solar/Wind Harmer
7.498
946301AF1-294 GEN
Solar/Wind Harmer
4.032
961791AG1-021 GEN
Solar/Wind Harmer
1.962
970683AG2-441 GEN
Solar/Wind Harmer
12.373
970681AG2-440 GEN
Solar/Wind Harmer
9.898
3144303KENBRDG
Solar/Wind Harmer
0.132
971443AH1-215 GEN
Solar/Wind Harmer
2.755
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Harmer
1.107
316118AC1-105 GEN
Solar/Wind Harmer
0.222
970831AG2-522 GEN
Solar/Wind Harmer
3.422
316233AE1-074 FULL
Solar/Wind Harmer
0.064
971281AH1-106 GEN
Solar/Wind Harmer
1.107
971283AH1-107 GEN
Solar/Wind Harmer
1.107
3147173SINAI
Solar/Wind Harmer
0.077
3147243WELCO
Solar/Wind Harmer
0.048
316087AB2-174 GEN
Solar/Wind Harmer
0.002
971967AH1-528 GEN
Solar/Wind Harmer
10.427
3137643SOCKMAN
Solar/Wind Harmer
0.253
970865AG2-541 GEN
Solar/Wind Harmer
2.127
315607AA1-063A GEN
Solar/Wind Harmer
0.122
3146043SEABORD
Solar/Wind Harmer
0.059
970673AG2-436 GEN
Solar/Wind Harmer
12.427
970673AG2-436 GEN
Solar/Wind Harmer
8.285
970085AG2-068 GEN
Solar/Wind Harmer
3.058
970581AG2-369 GEN
Solar/Wind Harmer
2.63
941031AE2-094 GEN
Solar/Wind Harmer
10.513
944011AF1-069 GEN
Solar/Wind Harmer
3.435
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.108
3148013FISHERV
Solar/Wind Helper
0.103
3148463FAIRFLD
Solar/Wind Helper
0.124
3151921BEARGRDN G2
50/50
4.422
3144293JTRSVLE
50/50
0.69
970413AG2-270 GEN
50/50
8.802
3151591KERR 2
50/50
0.192
3151261ROARAP2
50/50
0.076
3150861SPRUNCD
50/50
0.297
3151031BRUNSWICKG2
50/50
0.785
3146776BUCKING
Solar/Wind Harmer
0.136
3146926FARMVIL
Solar/Wind Harmer
0.178
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.156
316258AE1-075 C
Solar/Wind Harmer
0.187
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.737
970909AG2-566 GEN
Solar/Wind Harmer
2.353
3147133PAMPLIN
Solar/Wind Harmer
0.682
971193AH1-056 GEN
Solar/Wind Harmer
13.238
963181AG1-167 GEN
Solar/Wind Harmer
0.817
959311AF2-222 GEN
Solar/Wind Harmer
15.236
970257AG2-171 GEN
Solar/Wind Harmer
5.302
315785AD2-033 C
Solar/Wind Harmer
1.283
964241AG1-285 GEN
Solar/Wind Harmer
9.125
316131AB2-060 GEN
Solar/Wind Harmer
0.39
970221AG2-151 GEN
Solar/Wind Harmer
6.362
316478AD1-087 GEN
Solar/Wind Harmer
0.328
316486AD2-202 GEN
Solar/Wind Harmer
0.096
3147043LAWRENC
Solar/Wind Harmer
0.05
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.274
971683AH1-343 GEN
Solar/Wind Harmer
2.442
313506AB2-031 GEN
Solar/Wind Harmer
0.2
970917AG2-570 GEN
Solar/Wind Harmer
5.117
316365GEN2_N
Solar/Wind Harmer
0.127
3148013FISHERV
Solar/Wind Helper
0.18
316499AE2-029_GEN
Solar/Wind Helper
0.518
315616AA1-038_C
Solar/Wind Helper
0.562
3132273ORANGE
Solar/Wind Helper
0.024
3151931BEARGRDN S1
50/50
5.707
3151911BEARGRDN G1
50/50
4.422
3144293JTRSVLE
50/50
0.69
970119AG2-088 GEN
50/50
12.707
3151531CLOVER1
50/50
2.017
3151601KERR 3
50/50
0.192
3151581KERR 1
50/50
0.069
3147043LAWRENC
50/50
0.8
3151261ROARAP2
50/50
0.077
3150851SPRUNCC
50/50
0.297
3151051BRUNSWICKS1
50/50
1.63
3151021BRUNSWICKG1
50/50
0.785
971451AH1-221 GEN
50/50
2.385
315243AE2-183_GT3
50/50
0.972
972003AH1-546 GEN
Solar/Wind Harmer
19.447
970937AG2-583 GEN
Solar/Wind Harmer
23.874
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.151
3146926FARMVIL
Solar/Wind Harmer
0.178
316336AC2-165 C
Solar/Wind Harmer
0.011
3143336POWHATN
Solar/Wind Harmer
4.396
963171AG1-166 GEN
Solar/Wind Harmer
1.09
971563AH1-280 GEN
Solar/Wind Harmer
2.18
970685AG2-442 GEN
Solar/Wind Harmer
13.857
962491AG1-098 GEN
Solar/Wind Harmer
7.06
971377AH1-170 GEN
Solar/Wind Harmer
1.272
3147623JAMES R
Solar/Wind Harmer
0.276
315693AD1-088 GEN
Solar/Wind Harmer
5.685
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Harmer
0.095
970401AG2-262 GEN
Solar/Wind Harmer
0.559
957481AF2-042 GEN
Solar/Wind Harmer
24.966
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.579
316129AC1-054 GEN
Solar/Wind Harmer
0.309
3143526WINTERP
Solar/Wind Harmer
0.415
971795AH1-408 GEN
Solar/Wind Harmer
5.206
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.641
3145783HORNRTN
Solar/Wind Harmer
0.061
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
2.047
970087AG2-069 GEN
Solar/Wind Harmer
4.587
316023GEN1_S
Solar/Wind Harmer
0.127
3147983MERCK5
Solar/Wind Helper
0.057
3144293JTRSVLE
50/50
0.69
3144293JTRSVLE
50/50
0.581
970535AG2-341 GEN
50/50
1.885
3152661PLYWOOD A
50/50
0.185
3151041BRUNSWICKG3
50/50
0.785
972187AH1-678 GEN
50/50
1.802
315242AE2-183_GT2
50/50
0.972
315241AE2-183_GT1
50/50
0.966
972185AH1-677 GEN
50/50
3.505
970533AG2-339 GEN
50/50
5.074
970531AG2-338 GEN
50/50
2.029
3146776BUCKING
Solar/Wind Harmer
1.508
3146776BUCKING
Solar/Wind Harmer
0.122
970301AG2-198 GEN
Solar/Wind Harmer
9.412
3147133PAMPLIN
Solar/Wind Harmer
0.217
3147133PAMPLIN
Solar/Wind Harmer
0.174
958211AF2-115 GEN
Solar/Wind Harmer
2.452
963191AG1-168 GEN
Solar/Wind Harmer
0.817
971741AH1-377 GEN
Solar/Wind Harmer
19.558
316034AC1-036 C
Solar/Wind Harmer
0.012
970323AG2-213 GEN
Solar/Wind Harmer
7.069
971775AH1-396 GEN
Solar/Wind Harmer
0.265
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971489AH1-241 GEN
Solar/Wind Harmer
6.362
962561AG1-105 GEN
Solar/Wind Harmer
4.763
939181AE1-148 GEN
Solar/Wind Harmer
4.697
971223AH1-071 GEN
Solar/Wind Harmer
1.017
964791AG1-342 GEN
Solar/Wind Harmer
1.83
3146843MT LREL
Solar/Wind Harmer
0.095
3146843MT LREL
Solar/Wind Harmer
0.095
970099AG2-077 GEN
Solar/Wind Harmer
9.986
3143526WINTERP
Solar/Wind Harmer
0.415
970933AG2-581 GEN
Solar/Wind Harmer
5.925
316181AB2-040 GEN
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.062
3145593CAROLNA
Solar/Wind Harmer
0.062
966811AG1-552 GEN
Solar/Wind Harmer
0.675
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.086
3145783HORNRTN
Solar/Wind Harmer
0.869
3145783HORNRTN
Solar/Wind Harmer
0.271
3145783HORNRTN
Solar/Wind Harmer
0.109
316426AA2-053 GEN
Solar/Wind Harmer
0.204
966001AG1-469 GEN
Solar/Wind Helper
0.174
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.208
CPLELTFEXP_CPLE->PJM
CLTF
3.08
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.625
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.118
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.349
LAGNLTFEXP_LAGN->PJM
CLTF
0.897
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.783
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.427
NYPJM->LTFIMP_NY
CLTF
0.345

Details for 6BRIERY-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.81 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:753.29
MW Contribution:1.99
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
971967AH1-528 GEN
Solar/Wind Harmer
55.717
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
316118AC1-105 GEN
Solar/Wind Harmer
0.376
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
970909AG2-566 GEN
Solar/Wind Harmer
6.347
316478AD1-087 GEN
Solar/Wind Harmer
1.094
316486AD2-202 GEN
Solar/Wind Harmer
0.321
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.01
971683AH1-343 GEN
Solar/Wind Harmer
5.256
316283AC2-100 C
Solar/Wind Harmer
0.206
316131AB2-060 GEN
Solar/Wind Harmer
0.208
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
971629AH1-314 GEN
50/50
5.006
962491AG1-098 GEN
Solar/Wind Harmer
22.331
315693AD1-088 GEN
Solar/Wind Harmer
18.25
957481AF2-042 GEN
Solar/Wind Harmer
90.747
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.071
316129AC1-054 GEN
Solar/Wind Harmer
0.427
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
3152661PLYWOOD A
50/50
0.346
970535AG2-341 GEN
50/50
1.993
970301AG2-198 GEN
Solar/Wind Harmer
25.388
971741AH1-377 GEN
Solar/Wind Harmer
54.138
970933AG2-581 GEN
Solar/Wind Harmer
27.859
970099AG2-077 GEN
Solar/Wind Harmer
36.299
939181AE1-148 GEN
Solar/Wind Harmer
6.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.689
316222AC1-221 GEN
Solar/Wind Harmer
0.447
942751AE2-291 GEN
Solar/Wind Harmer
5.336
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
970865AG2-541 GEN
Solar/Wind Harmer
4.593
316123AC1-075 GEN
Solar/Wind Harmer
0.152
970165AG2-112 GEN
Solar/Wind Harmer
0.903
970163AG2-111 GEN
Solar/Wind Harmer
0.862
970831AG2-522 GEN
Solar/Wind Harmer
4.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for 6BRIERY-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:129.23 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:738.58
MW Contribution:1.99
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
970909AG2-566 GEN
Solar/Wind Harmer
6.347
316478AD1-087 GEN
Solar/Wind Harmer
1.094
316486AD2-202 GEN
Solar/Wind Harmer
0.321
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.01
971683AH1-343 GEN
Solar/Wind Harmer
5.256
316283AC2-100 C
Solar/Wind Harmer
0.206
316131AB2-060 GEN
Solar/Wind Harmer
0.208
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
971629AH1-314 GEN
50/50
5.006
962491AG1-098 GEN
Solar/Wind Harmer
22.331
315693AD1-088 GEN
Solar/Wind Harmer
18.25
957481AF2-042 GEN
Solar/Wind Harmer
90.747
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.071
316129AC1-054 GEN
Solar/Wind Harmer
0.427
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
3152661PLYWOOD A
50/50
0.346
970535AG2-341 GEN
50/50
1.993
970301AG2-198 GEN
Solar/Wind Harmer
25.388
971741AH1-377 GEN
Solar/Wind Harmer
54.138
970099AG2-077 GEN
Solar/Wind Harmer
36.299
939181AE1-148 GEN
Solar/Wind Harmer
6.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.689
316222AC1-221 GEN
Solar/Wind Harmer
0.447
942751AE2-291 GEN
Solar/Wind Harmer
5.336
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
316118AC1-105 GEN
Solar/Wind Harmer
0.376
970865AG2-541 GEN
Solar/Wind Harmer
4.593
316123AC1-075 GEN
Solar/Wind Harmer
0.152
970165AG2-112 GEN
Solar/Wind Harmer
0.903
970163AG2-111 GEN
Solar/Wind Harmer
0.862
970831AG2-522 GEN
Solar/Wind Harmer
4.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for 6BRIERY-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:129.16 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:902.85
MW Contribution:2.0
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
6.74
3151601KERR 3
50/50
0.302
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.44
315693AD1-088 GEN
Solar/Wind Harmer
21.388
957481AF2-042 GEN
Solar/Wind Harmer
119.681
315687AD1-152 GEN
Solar/Wind Harmer
3.524
316003AC1-222 GEN
Solar/Wind Harmer
1.683
970401AG2-262 GEN
Solar/Wind Harmer
0.932
971065AG2-659 GEN
Solar/Wind Harmer
6.697
316129AC1-054 GEN
Solar/Wind Harmer
1.121
316237AB2-079_GEN
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Helper
0.44
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
1.003
3152661PLYWOOD A
50/50
0.348
970535AG2-341 GEN
50/50
2.001
970301AG2-198 GEN
Solar/Wind Harmer
33.445
971741AH1-377 GEN
Solar/Wind Harmer
71.327
970933AG2-581 GEN
Solar/Wind Harmer
36.739
970099AG2-077 GEN
Solar/Wind Harmer
47.872
939181AE1-148 GEN
Solar/Wind Harmer
8.421
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.05
962561AG1-105 GEN
Solar/Wind Harmer
7.525
316222AC1-221 GEN
Solar/Wind Harmer
1.236
942751AE2-291 GEN
Solar/Wind Harmer
7.063
313527AB2-043 GEN
Solar/Wind Harmer
1.361
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.338
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.919
3151541CLOVER2
50/50
6.708
3151611KERR 4
50/50
0.302
3151621KERR 5
50/50
0.302
3151631KERR 6
50/50
0.302
3151641KERR 7
50/50
0.302
971967AH1-528 GEN
Solar/Wind Harmer
73.672
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.131
970865AG2-541 GEN
Solar/Wind Harmer
6.075
316123AC1-075 GEN
Solar/Wind Harmer
1.358
970165AG2-112 GEN
Solar/Wind Harmer
1.195
970163AG2-111 GEN
Solar/Wind Harmer
1.14
970831AG2-522 GEN
Solar/Wind Harmer
6.069
316239AB2-077_GEN
Solar/Wind Harmer
0.274
316238AB2-078_GEN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Harmer
1.371
270457AD2-023 GEN
Solar/Wind Harmer
0.695
270494AE1-108_GEN
Solar/Wind Helper
2.769
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
970413AG2-270 GEN
50/50
29.414
3151591KERR 2
50/50
0.302
970909AG2-566 GEN
Solar/Wind Harmer
6.35
316478AD1-087 GEN
Solar/Wind Harmer
3.055
316486AD2-202 GEN
Solar/Wind Harmer
0.895
316248AF1-058 C
Solar/Wind Harmer
0.559
960061AF2-297 GEN
Solar/Wind Harmer
9.268
971683AH1-343 GEN
Solar/Wind Harmer
6.951
316283AC2-100 C
Solar/Wind Harmer
1.124
316131AB2-060 GEN
Solar/Wind Harmer
0.808
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.542
3147133PAMPLIN
Solar/Wind Helper
1.062
316313AB2-026
Solar/Wind Helper
0.243
316258AE1-075 C
Solar/Wind Helper
0.219
316405AF2-144 C
Solar/Wind Helper
0.182
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.6
MECLTFEXP_MEC->PJM
CLTF
1.297
SIGELTFEXP_SIGE->PJM
CLTF
0.038
CPLELTFEXP_CPLE->PJM
CLTF
4.232
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.165
LAGNLTFEXP_LAGN->PJM
CLTF
2.703
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.92
TVALTFEXP_TVA->PJM
CLTF
1.347
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.461
WECLTFEXP_WEC->PJM
CLTF
0.241

Details for 6BRIERY-6FARMVIL 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:129.12 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:902.56
MW Contribution:2.0
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.708
3151611KERR 4
50/50
0.302
3151621KERR 5
50/50
0.302
3151631KERR 6
50/50
0.302
3151641KERR 7
50/50
0.302
971967AH1-528 GEN
Solar/Wind Harmer
73.672
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.131
970865AG2-541 GEN
Solar/Wind Harmer
6.075
316123AC1-075 GEN
Solar/Wind Harmer
1.358
970165AG2-112 GEN
Solar/Wind Harmer
1.195
970163AG2-111 GEN
Solar/Wind Harmer
1.14
970831AG2-522 GEN
Solar/Wind Harmer
6.069
316239AB2-077_GEN
Solar/Wind Harmer
0.274
316238AB2-078_GEN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Harmer
1.371
270457AD2-023 GEN
Solar/Wind Harmer
0.695
270494AE1-108_GEN
Solar/Wind Helper
2.769
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3151531CLOVER1
50/50
6.74
3151601KERR 3
50/50
0.302
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.44
315693AD1-088 GEN
Solar/Wind Harmer
21.388
957481AF2-042 GEN
Solar/Wind Harmer
119.681
315687AD1-152 GEN
Solar/Wind Harmer
3.524
316003AC1-222 GEN
Solar/Wind Harmer
1.683
970401AG2-262 GEN
Solar/Wind Harmer
0.932
971065AG2-659 GEN
Solar/Wind Harmer
6.697
316129AC1-054 GEN
Solar/Wind Harmer
1.121
316237AB2-079_GEN
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Helper
0.44
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
1.003
3152661PLYWOOD A
50/50
0.348
970535AG2-341 GEN
50/50
2.001
970301AG2-198 GEN
Solar/Wind Harmer
33.445
971741AH1-377 GEN
Solar/Wind Harmer
71.327
970933AG2-581 GEN
Solar/Wind Harmer
36.739
970099AG2-077 GEN
Solar/Wind Harmer
47.872
939181AE1-148 GEN
Solar/Wind Harmer
8.421
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.05
962561AG1-105 GEN
Solar/Wind Harmer
7.525
316222AC1-221 GEN
Solar/Wind Harmer
1.236
942751AE2-291 GEN
Solar/Wind Harmer
7.063
313527AB2-043 GEN
Solar/Wind Harmer
1.361
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.338
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.919
970413AG2-270 GEN
50/50
29.414
3151591KERR 2
50/50
0.302
970909AG2-566 GEN
Solar/Wind Harmer
6.35
316478AD1-087 GEN
Solar/Wind Harmer
3.055
316486AD2-202 GEN
Solar/Wind Harmer
0.895
316248AF1-058 C
Solar/Wind Harmer
0.559
960061AF2-297 GEN
Solar/Wind Harmer
9.268
971683AH1-343 GEN
Solar/Wind Harmer
6.951
316283AC2-100 C
Solar/Wind Harmer
1.124
316131AB2-060 GEN
Solar/Wind Harmer
0.808
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.542
3147133PAMPLIN
Solar/Wind Helper
1.062
316313AB2-026
Solar/Wind Helper
0.243
316258AE1-075 C
Solar/Wind Helper
0.219
316405AF2-144 C
Solar/Wind Helper
0.182
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.6
MECLTFEXP_MEC->PJM
CLTF
1.297
SIGELTFEXP_SIGE->PJM
CLTF
0.038
CPLELTFEXP_CPLE->PJM
CLTF
4.232
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.165
LAGNLTFEXP_LAGN->PJM
CLTF
2.703
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.92
TVALTFEXP_TVA->PJM
CLTF
1.347
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.461
WECLTFEXP_WEC->PJM
CLTF
0.241

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:212.98 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1488.76
MW Contribution:4.63
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.83
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
971845AH1-439 GEN
Solar/Wind Harmer
44.827
970285AG2-188 GEN
Solar/Wind Harmer
71.81
315657AE1-056 GEN
Solar/Wind Harmer
20.233
946301AF1-294 GEN
Solar/Wind Harmer
13.088
961791AG1-021 GEN
Solar/Wind Harmer
6.384
970683AG2-441 GEN
Solar/Wind Harmer
36.677
970681AG2-440 GEN
Solar/Wind Harmer
29.342
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.305
971967AH1-528 GEN
Solar/Wind Harmer
73.277
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.951
3151591KERR 2
50/50
0.482
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.336
970909AG2-566 GEN
Solar/Wind Harmer
5.575
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.721
963181AG1-167 GEN
Solar/Wind Harmer
4.788
959311AF2-222 GEN
Solar/Wind Harmer
45.74
970257AG2-171 GEN
Solar/Wind Harmer
15.961
315785AD2-033 C
Solar/Wind Harmer
9.254
964241AG1-285 GEN
Solar/Wind Harmer
28.298
316478AD1-087 GEN
Solar/Wind Harmer
3.113
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.606
316248AF1-058 C
Solar/Wind Harmer
0.74
960061AF2-297 GEN
Solar/Wind Harmer
12.278
971683AH1-343 GEN
Solar/Wind Harmer
9.189
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.301
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.773
316210AC1-098 GEN
Solar/Wind Harmer
1.19
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.758
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.392
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.405
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.318
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
3148013FISHERV
Solar/Wind Helper
0.111
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.627
3152661PLYWOOD A
50/50
0.509
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.363
971741AH1-377 GEN
Solar/Wind Harmer
63.743
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.98
963191AG1-168 GEN
Solar/Wind Harmer
4.788
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.282
971775AH1-396 GEN
Solar/Wind Harmer
3.031
970933AG2-581 GEN
Solar/Wind Harmer
36.542
970099AG2-077 GEN
Solar/Wind Harmer
47.863
313527AB2-043 GEN
Solar/Wind Harmer
5.319
962561AG1-105 GEN
Solar/Wind Harmer
16.15
964791AG1-342 GEN
Solar/Wind Harmer
5.978
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.382
942751AE2-291 GEN
Solar/Wind Harmer
9.268
316222AC1-221 GEN
Solar/Wind Harmer
1.428
316181AB2-040 GEN
Solar/Wind Harmer
1.451
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.155
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.18
3145783HORNRTN
Solar/Wind Harmer
0.944
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.888
316263AC1-034 GEN
Solar/Wind Harmer
3.343
961601AG1-000A GEN
Solar/Wind Harmer
2.724
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.041
316197AC1-042 GEN
Solar/Wind Harmer
0.789
942671AE2-283 GEN
Solar/Wind Harmer
2.125
315821AE2-092 GEN
Solar/Wind Helper
2.535
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.863
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.477
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.384
971563AH1-280 GEN
Solar/Wind Harmer
6.384
970685AG2-442 GEN
Solar/Wind Harmer
41.078
962491AG1-098 GEN
Solar/Wind Harmer
28.511
315693AD1-088 GEN
Solar/Wind Harmer
20.878
957481AF2-042 GEN
Solar/Wind Harmer
119.657
316237AB2-079_GEN
Solar/Wind Harmer
0.969
315687AD1-152 GEN
Solar/Wind Harmer
3.719
970401AG2-262 GEN
Solar/Wind Harmer
1.826
316003AC1-222 GEN
Solar/Wind Harmer
2.228
971065AG2-659 GEN
Solar/Wind Harmer
10.772
316129AC1-054 GEN
Solar/Wind Harmer
1.807
971795AH1-408 GEN
Solar/Wind Harmer
11.365
960081AF2-299 GEN
Solar/Wind Harmer
1.184
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.962
316049AB1-081 GEN
Solar/Wind Harmer
0.77
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.712
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
970223AG2-152 GEN
Solar/Wind Harmer
5.769
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.191
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.405
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.316
316239AB2-077_GEN
Solar/Wind Harmer
0.969
316238AB2-078_GEN
Solar/Wind Harmer
0.969
316118AC1-105 GEN
Solar/Wind Harmer
1.805
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.02
970831AG2-522 GEN
Solar/Wind Harmer
9.81
316123AC1-075 GEN
Solar/Wind Harmer
1.786
970165AG2-112 GEN
Solar/Wind Harmer
1.573
970163AG2-111 GEN
Solar/Wind Harmer
1.5
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.489
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.631
270457AD2-023 GEN
Solar/Wind Harmer
0.827
315607AA1-063A GEN
Solar/Wind Harmer
0.88
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.41
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.561
270494AE1-108_GEN
Solar/Wind Helper
3.67
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.067
3148013FISHERV
Solar/Wind Helper
0.064
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.278
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.374
MECLTFEXP_MEC->PJM
CLTF
1.462
SIGELTFEXP_SIGE->PJM
CLTF
0.043
CPLELTFEXP_CPLE->PJM
CLTF
5.212
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.402
LAGNLTFEXP_LAGN->PJM
CLTF
3.179
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.848
TVALTFEXP_TVA->PJM
CLTF
1.583
NYPJM->LTFIMP_NY
CLTF
0.53
LGEELTFEXP_LGEE->PJM
CLTF
0.51
WECLTFEXP_WEC->PJM
CLTF
0.265

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:212.93 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1488.37
MW Contribution:4.63
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.83
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
971845AH1-439 GEN
Solar/Wind Harmer
44.827
970285AG2-188 GEN
Solar/Wind Harmer
71.81
315657AE1-056 GEN
Solar/Wind Harmer
20.233
946301AF1-294 GEN
Solar/Wind Harmer
13.088
961791AG1-021 GEN
Solar/Wind Harmer
6.384
970683AG2-441 GEN
Solar/Wind Harmer
36.677
970681AG2-440 GEN
Solar/Wind Harmer
29.342
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.305
971967AH1-528 GEN
Solar/Wind Harmer
73.277
316239AB2-077_GEN
Solar/Wind Harmer
0.969
316238AB2-078_GEN
Solar/Wind Harmer
0.969
316118AC1-105 GEN
Solar/Wind Harmer
1.805
3147173SINAI
Solar/Wind Harmer
-0.024
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.863
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.477
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.384
971563AH1-280 GEN
Solar/Wind Harmer
6.384
970685AG2-442 GEN
Solar/Wind Harmer
41.078
962491AG1-098 GEN
Solar/Wind Harmer
28.511
315693AD1-088 GEN
Solar/Wind Harmer
20.878
957481AF2-042 GEN
Solar/Wind Harmer
119.657
316237AB2-079_GEN
Solar/Wind Harmer
0.969
315687AD1-152 GEN
Solar/Wind Harmer
3.719
970401AG2-262 GEN
Solar/Wind Harmer
1.826
316003AC1-222 GEN
Solar/Wind Harmer
2.228
971065AG2-659 GEN
Solar/Wind Harmer
10.772
316129AC1-054 GEN
Solar/Wind Harmer
1.807
971795AH1-408 GEN
Solar/Wind Harmer
11.365
960081AF2-299 GEN
Solar/Wind Harmer
1.184
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.951
3151591KERR 2
50/50
0.482
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.336
970909AG2-566 GEN
Solar/Wind Harmer
5.575
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.721
963181AG1-167 GEN
Solar/Wind Harmer
4.788
959311AF2-222 GEN
Solar/Wind Harmer
45.74
970257AG2-171 GEN
Solar/Wind Harmer
15.961
315785AD2-033 C
Solar/Wind Harmer
9.254
964241AG1-285 GEN
Solar/Wind Harmer
28.298
316478AD1-087 GEN
Solar/Wind Harmer
3.113
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.606
316248AF1-058 C
Solar/Wind Harmer
0.74
960061AF2-297 GEN
Solar/Wind Harmer
12.278
971683AH1-343 GEN
Solar/Wind Harmer
9.189
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.301
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.773
316210AC1-098 GEN
Solar/Wind Harmer
1.19
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.758
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.392
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.405
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.318
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
3148013FISHERV
Solar/Wind Helper
0.111
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.627
3152661PLYWOOD A
50/50
0.509
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.363
971741AH1-377 GEN
Solar/Wind Harmer
63.743
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.98
963191AG1-168 GEN
Solar/Wind Harmer
4.788
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.282
971775AH1-396 GEN
Solar/Wind Harmer
3.031
970933AG2-581 GEN
Solar/Wind Harmer
36.542
970099AG2-077 GEN
Solar/Wind Harmer
47.863
313527AB2-043 GEN
Solar/Wind Harmer
5.319
962561AG1-105 GEN
Solar/Wind Harmer
16.15
964791AG1-342 GEN
Solar/Wind Harmer
5.978
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.382
942751AE2-291 GEN
Solar/Wind Harmer
9.268
316222AC1-221 GEN
Solar/Wind Harmer
1.428
316181AB2-040 GEN
Solar/Wind Harmer
1.451
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.155
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.18
3145783HORNRTN
Solar/Wind Harmer
0.944
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.888
316263AC1-034 GEN
Solar/Wind Harmer
3.343
961601AG1-000A GEN
Solar/Wind Harmer
2.724
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.041
316197AC1-042 GEN
Solar/Wind Harmer
0.789
942671AE2-283 GEN
Solar/Wind Harmer
2.125
315821AE2-092 GEN
Solar/Wind Helper
2.535
316359AB2-059 GEN
Solar/Wind Harmer
0.962
316049AB1-081 GEN
Solar/Wind Harmer
0.77
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.712
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
970223AG2-152 GEN
Solar/Wind Harmer
5.769
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.191
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.405
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.316
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.02
970831AG2-522 GEN
Solar/Wind Harmer
9.81
316123AC1-075 GEN
Solar/Wind Harmer
1.786
970165AG2-112 GEN
Solar/Wind Harmer
1.573
970163AG2-111 GEN
Solar/Wind Harmer
1.5
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.489
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.631
270457AD2-023 GEN
Solar/Wind Harmer
0.827
315607AA1-063A GEN
Solar/Wind Harmer
0.88
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.41
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.561
270494AE1-108_GEN
Solar/Wind Helper
3.67
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.067
3148013FISHERV
Solar/Wind Helper
0.064
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.278
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.374
MECLTFEXP_MEC->PJM
CLTF
1.462
SIGELTFEXP_SIGE->PJM
CLTF
0.043
CPLELTFEXP_CPLE->PJM
CLTF
5.212
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.402
LAGNLTFEXP_LAGN->PJM
CLTF
3.179
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.848
TVALTFEXP_TVA->PJM
CLTF
1.583
NYPJM->LTFIMP_NY
CLTF
0.53
LGEELTFEXP_LGEE->PJM
CLTF
0.51
WECLTFEXP_WEC->PJM
CLTF
0.265

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:209.35 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1463.37
MW Contribution:4.62
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.331
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
-0.168
971193AH1-056 GEN
Solar/Wind Harmer
33.698
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.343
971741AH1-377 GEN
Solar/Wind Harmer
63.689
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.974
963191AG1-168 GEN
Solar/Wind Harmer
4.785
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.258
971775AH1-396 GEN
Solar/Wind Harmer
3.027
970933AG2-581 GEN
Solar/Wind Harmer
36.473
970099AG2-077 GEN
Solar/Wind Harmer
47.77
313527AB2-043 GEN
Solar/Wind Harmer
5.31
962561AG1-105 GEN
Solar/Wind Harmer
16.108
964791AG1-342 GEN
Solar/Wind Harmer
5.961
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.346
942751AE2-291 GEN
Solar/Wind Harmer
9.222
316222AC1-221 GEN
Solar/Wind Harmer
1.414
316181AB2-040 GEN
Solar/Wind Harmer
1.452
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.154
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.178
3145783HORNRTN
Solar/Wind Harmer
0.943
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.379
971563AH1-280 GEN
Solar/Wind Harmer
6.379
970685AG2-442 GEN
Solar/Wind Harmer
41.041
962491AG1-098 GEN
Solar/Wind Harmer
28.467
315693AD1-088 GEN
Solar/Wind Harmer
20.844
957481AF2-042 GEN
Solar/Wind Harmer
119.424
316237AB2-079_GEN
Solar/Wind Harmer
0.967
315687AD1-152 GEN
Solar/Wind Harmer
3.708
970401AG2-262 GEN
Solar/Wind Harmer
1.822
316003AC1-222 GEN
Solar/Wind Harmer
2.219
971065AG2-659 GEN
Solar/Wind Harmer
10.747
316129AC1-054 GEN
Solar/Wind Harmer
1.803
971795AH1-408 GEN
Solar/Wind Harmer
11.364
960081AF2-299 GEN
Solar/Wind Harmer
1.186
3145783HORNRTN
Solar/Wind Harmer
-0.01
963181AG1-167 GEN
Solar/Wind Harmer
4.785
959311AF2-222 GEN
Solar/Wind Harmer
45.693
970257AG2-171 GEN
Solar/Wind Harmer
15.944
315785AD2-033 C
Solar/Wind Harmer
9.243
964241AG1-285 GEN
Solar/Wind Harmer
28.257
316478AD1-087 GEN
Solar/Wind Harmer
3.106
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.6
316248AF1-058 C
Solar/Wind Harmer
0.737
960061AF2-297 GEN
Solar/Wind Harmer
12.232
971683AH1-343 GEN
Solar/Wind Harmer
9.152
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.287
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.826
970285AG2-188 GEN
Solar/Wind Harmer
71.806
315657AE1-056 GEN
Solar/Wind Harmer
20.219
946301AF1-294 GEN
Solar/Wind Harmer
13.078
961791AG1-021 GEN
Solar/Wind Harmer
6.379
970683AG2-441 GEN
Solar/Wind Harmer
36.643
970681AG2-440 GEN
Solar/Wind Harmer
29.315
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.296
971967AH1-528 GEN
Solar/Wind Harmer
73.139
316239AB2-077_GEN
Solar/Wind Harmer
0.967
316238AB2-078_GEN
Solar/Wind Harmer
0.967
316118AC1-105 GEN
Solar/Wind Harmer
1.799
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.987
970831AG2-522 GEN
Solar/Wind Harmer
9.789
316123AC1-075 GEN
Solar/Wind Harmer
1.778
970165AG2-112 GEN
Solar/Wind Harmer
1.566
970163AG2-111 GEN
Solar/Wind Harmer
1.494
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.49
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.605
270457AD2-023 GEN
Solar/Wind Harmer
0.814
315607AA1-063A GEN
Solar/Wind Harmer
0.881
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.406
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.564
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.658
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.951
316049AB1-081 GEN
Solar/Wind Harmer
0.761
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.707
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
970223AG2-152 GEN
Solar/Wind Harmer
5.68
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.385
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.31
316327AA2-057 GEN
Solar/Wind Harmer
0.767
316210AC1-098 GEN
Solar/Wind Harmer
1.185
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.727
315724AD1-057 GEN
Solar/Wind Harmer
0.389
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.385
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.884
316263AC1-034 GEN
Solar/Wind Harmer
3.306
961601AG1-000A GEN
Solar/Wind Harmer
2.693
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
316217AC1-145 GEN
Solar/Wind Harmer
1.032
316197AC1-042 GEN
Solar/Wind Harmer
0.782
942671AE2-283 GEN
Solar/Wind Harmer
2.107
315821AE2-092 GEN
Solar/Wind Helper
2.531
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:207.29 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:1184.7
MW Contribution:4.62
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.952
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.158
3151411GASTONB
50/50
0.158
316322AB2-045
Solar/Wind Harmer
0.006
3146776BUCKING
Solar/Wind Harmer
0.305
3146926FARMVIL
Solar/Wind Harmer
0.38
963171AG1-166 GEN
Solar/Wind Harmer
2.423
971563AH1-280 GEN
Solar/Wind Harmer
4.845
970685AG2-442 GEN
Solar/Wind Harmer
31.17
962491AG1-098 GEN
Solar/Wind Harmer
21.62
315693AD1-088 GEN
Solar/Wind Harmer
17.81
957481AF2-042 GEN
Solar/Wind Harmer
90.702
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.457
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.163
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
8.991
960081AF2-299 GEN
Solar/Wind Harmer
0.901
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.348
3146233WITAKRS
Solar/Wind Harmer
0.26
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
316359AB2-059 GEN
Solar/Wind Harmer
0.225
316049AB1-081 GEN
Solar/Wind Harmer
0.359
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.061
315722AD1-056 GEN
Solar/Wind Harmer
0.381
3145796HORNRTN
Solar/Wind Harmer
0.194
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.064
962571AG1-106 GEN
Solar/Wind Harmer
0.833
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.252
970223AG2-152 GEN
Solar/Wind Harmer
3.983
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.042
941801AE2-185 GEN
Solar/Wind Harmer
1.811
3145823KELFORD
Solar/Wind Harmer
0.056
316336AC2-165 C
Solar/Wind Helper
1.31
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.158
3151411GASTONB
50/50
0.158
3146776BUCKING
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Harmer
0.38
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.219
963181AG1-167 GEN
Solar/Wind Harmer
1.817
959311AF2-222 GEN
Solar/Wind Harmer
34.634
970257AG2-171 GEN
Solar/Wind Harmer
12.109
315785AD2-033 C
Solar/Wind Harmer
2.951
964241AG1-285 GEN
Solar/Wind Harmer
21.461
316478AD1-087 GEN
Solar/Wind Harmer
1.114
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.934
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.29
971683AH1-343 GEN
Solar/Wind Harmer
6.951
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.286
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.624
3146233WITAKRS
Solar/Wind Harmer
0.328
3146233WITAKRS
Solar/Wind Harmer
0.044
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.061
961601AG1-000A GEN
Solar/Wind Harmer
4.335
315724AD1-057 GEN
Solar/Wind Harmer
0.226
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.811
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.212
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.099
3146776BUCKING
Solar/Wind Harmer
3.045
3146776BUCKING
Solar/Wind Harmer
0.247
970301AG2-198 GEN
Solar/Wind Harmer
22.286
971741AH1-377 GEN
Solar/Wind Harmer
48.371
3147133PAMPLIN
Solar/Wind Harmer
0.479
3147133PAMPLIN
Solar/Wind Harmer
0.383
958211AF2-115 GEN
Solar/Wind Harmer
5.451
963191AG1-168 GEN
Solar/Wind Harmer
1.817
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.146
971775AH1-396 GEN
Solar/Wind Harmer
0.605
970933AG2-581 GEN
Solar/Wind Harmer
27.701
970099AG2-077 GEN
Solar/Wind Harmer
36.281
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.234
964791AG1-342 GEN
Solar/Wind Harmer
4.769
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.655
942751AE2-291 GEN
Solar/Wind Harmer
7.004
316222AC1-221 GEN
Solar/Wind Harmer
0.516
316181AB2-040 GEN
Solar/Wind Harmer
0.134
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.99
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.571
3145783HORNRTN
Solar/Wind Harmer
1.257
3145783HORNRTN
Solar/Wind Harmer
0.393
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.283
316274AC1-208 GEN
Solar/Wind Harmer
0.379
316263AC1-034 GEN
Solar/Wind Harmer
2.385
961601AG1-000A GEN
Solar/Wind Harmer
1.084
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.131
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.409
315821AE2-092 GEN
Solar/Wind Helper
2.531
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.103
971845AH1-439 GEN
Solar/Wind Harmer
34.045
970285AG2-188 GEN
Solar/Wind Harmer
57.782
315657AE1-056 GEN
Solar/Wind Harmer
16.55
946301AF1-294 GEN
Solar/Wind Harmer
8.963
961791AG1-021 GEN
Solar/Wind Harmer
4.361
970683AG2-441 GEN
Solar/Wind Harmer
27.831
970681AG2-440 GEN
Solar/Wind Harmer
22.264
3144303KENBRDG
Solar/Wind Harmer
0.302
971443AH1-215 GEN
Solar/Wind Harmer
6.301
971967AH1-528 GEN
Solar/Wind Harmer
55.401
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.601
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.066
970831AG2-522 GEN
Solar/Wind Harmer
7.435
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.134
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.367
315607AA1-063A GEN
Solar/Wind Harmer
0.158
3146043SEABORD
Solar/Wind Harmer
0.075
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.249
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.44
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.251
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:204.76 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:1170.27
MW Contribution:4.62
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.212
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.099
3146776BUCKING
Solar/Wind Harmer
3.045
3146776BUCKING
Solar/Wind Harmer
0.247
970301AG2-198 GEN
Solar/Wind Harmer
22.286
971741AH1-377 GEN
Solar/Wind Harmer
48.371
3147133PAMPLIN
Solar/Wind Harmer
0.479
3147133PAMPLIN
Solar/Wind Harmer
0.383
958211AF2-115 GEN
Solar/Wind Harmer
5.451
963191AG1-168 GEN
Solar/Wind Harmer
1.817
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.146
971775AH1-396 GEN
Solar/Wind Harmer
0.605
970099AG2-077 GEN
Solar/Wind Harmer
36.281
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.234
964791AG1-342 GEN
Solar/Wind Harmer
4.769
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.655
942751AE2-291 GEN
Solar/Wind Harmer
7.004
316222AC1-221 GEN
Solar/Wind Harmer
0.516
316181AB2-040 GEN
Solar/Wind Harmer
0.134
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.99
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.571
3145783HORNRTN
Solar/Wind Harmer
1.257
3145783HORNRTN
Solar/Wind Harmer
0.393
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.283
316274AC1-208 GEN
Solar/Wind Harmer
0.379
316263AC1-034 GEN
Solar/Wind Harmer
2.385
961601AG1-000A GEN
Solar/Wind Harmer
1.084
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.131
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.409
315821AE2-092 GEN
Solar/Wind Helper
2.531
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.158
3151411GASTONB
50/50
0.158
3146776BUCKING
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Harmer
0.38
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.219
963181AG1-167 GEN
Solar/Wind Harmer
1.817
959311AF2-222 GEN
Solar/Wind Harmer
34.634
970257AG2-171 GEN
Solar/Wind Harmer
12.109
315785AD2-033 C
Solar/Wind Harmer
2.951
964241AG1-285 GEN
Solar/Wind Harmer
21.461
316478AD1-087 GEN
Solar/Wind Harmer
1.114
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.934
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.29
971683AH1-343 GEN
Solar/Wind Harmer
6.951
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.286
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.624
3146233WITAKRS
Solar/Wind Harmer
0.328
3146233WITAKRS
Solar/Wind Harmer
0.044
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.061
961601AG1-000A GEN
Solar/Wind Harmer
4.335
315724AD1-057 GEN
Solar/Wind Harmer
0.226
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.811
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.952
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.158
3151411GASTONB
50/50
0.158
316322AB2-045
Solar/Wind Harmer
0.006
3146776BUCKING
Solar/Wind Harmer
0.305
3146926FARMVIL
Solar/Wind Harmer
0.38
963171AG1-166 GEN
Solar/Wind Harmer
2.423
971563AH1-280 GEN
Solar/Wind Harmer
4.845
970685AG2-442 GEN
Solar/Wind Harmer
31.17
962491AG1-098 GEN
Solar/Wind Harmer
21.62
315693AD1-088 GEN
Solar/Wind Harmer
17.81
957481AF2-042 GEN
Solar/Wind Harmer
90.702
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.457
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.163
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
8.991
960081AF2-299 GEN
Solar/Wind Harmer
0.901
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.348
3146233WITAKRS
Solar/Wind Harmer
0.26
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
316359AB2-059 GEN
Solar/Wind Harmer
0.225
316049AB1-081 GEN
Solar/Wind Harmer
0.359
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.061
315722AD1-056 GEN
Solar/Wind Harmer
0.381
3145796HORNRTN
Solar/Wind Harmer
0.194
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.064
962571AG1-106 GEN
Solar/Wind Harmer
0.833
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.252
970223AG2-152 GEN
Solar/Wind Harmer
3.983
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.042
941801AE2-185 GEN
Solar/Wind Harmer
1.811
3145823KELFORD
Solar/Wind Harmer
0.056
316336AC2-165 C
Solar/Wind Helper
1.31
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.103
971845AH1-439 GEN
Solar/Wind Harmer
34.045
970285AG2-188 GEN
Solar/Wind Harmer
57.782
315657AE1-056 GEN
Solar/Wind Harmer
16.55
946301AF1-294 GEN
Solar/Wind Harmer
8.963
961791AG1-021 GEN
Solar/Wind Harmer
4.361
970683AG2-441 GEN
Solar/Wind Harmer
27.831
970681AG2-440 GEN
Solar/Wind Harmer
22.264
3144303KENBRDG
Solar/Wind Harmer
0.302
971443AH1-215 GEN
Solar/Wind Harmer
6.301
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.601
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.066
970831AG2-522 GEN
Solar/Wind Harmer
7.435
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.134
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.367
315607AA1-063A GEN
Solar/Wind Harmer
0.158
3146043SEABORD
Solar/Wind Harmer
0.075
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.249
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.44
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.251
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:203.45 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1422.11
MW Contribution:4.62
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.379
971563AH1-280 GEN
Solar/Wind Harmer
6.379
970685AG2-442 GEN
Solar/Wind Harmer
41.041
962491AG1-098 GEN
Solar/Wind Harmer
28.467
315693AD1-088 GEN
Solar/Wind Harmer
20.844
957481AF2-042 GEN
Solar/Wind Harmer
119.424
316237AB2-079_GEN
Solar/Wind Harmer
0.967
315687AD1-152 GEN
Solar/Wind Harmer
3.708
970401AG2-262 GEN
Solar/Wind Harmer
1.822
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.331
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
-0.168
971193AH1-056 GEN
Solar/Wind Harmer
33.698
963181AG1-167 GEN
Solar/Wind Harmer
4.785
959311AF2-222 GEN
Solar/Wind Harmer
45.693
970257AG2-171 GEN
Solar/Wind Harmer
15.944
315785AD2-033 C
Solar/Wind Harmer
9.243
964241AG1-285 GEN
Solar/Wind Harmer
28.257
316478AD1-087 GEN
Solar/Wind Harmer
3.106
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.6
316248AF1-058 C
Solar/Wind Harmer
0.737
960061AF2-297 GEN
Solar/Wind Harmer
12.232
971683AH1-343 GEN
Solar/Wind Harmer
9.152
3147043LAWRENC
Solar/Wind Harmer
-0.01
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.343
971741AH1-377 GEN
Solar/Wind Harmer
63.689
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.974
963191AG1-168 GEN
Solar/Wind Harmer
4.785
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.258
971775AH1-396 GEN
Solar/Wind Harmer
3.027
970099AG2-077 GEN
Solar/Wind Harmer
47.77
313527AB2-043 GEN
Solar/Wind Harmer
5.31
962561AG1-105 GEN
Solar/Wind Harmer
16.108
964791AG1-342 GEN
Solar/Wind Harmer
5.961
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.346
942751AE2-291 GEN
Solar/Wind Harmer
9.222
316222AC1-221 GEN
Solar/Wind Harmer
1.414
316181AB2-040 GEN
Solar/Wind Harmer
1.452
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.154
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.178
3145783HORNRTN
Solar/Wind Harmer
0.943
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.884
316263AC1-034 GEN
Solar/Wind Harmer
3.306
961601AG1-000A GEN
Solar/Wind Harmer
2.693
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
316217AC1-145 GEN
Solar/Wind Harmer
1.032
316197AC1-042 GEN
Solar/Wind Harmer
0.782
942671AE2-283 GEN
Solar/Wind Harmer
2.107
315821AE2-092 GEN
Solar/Wind Helper
2.531
316003AC1-222 GEN
Solar/Wind Harmer
2.219
971065AG2-659 GEN
Solar/Wind Harmer
10.747
316129AC1-054 GEN
Solar/Wind Harmer
1.803
971795AH1-408 GEN
Solar/Wind Harmer
11.364
960081AF2-299 GEN
Solar/Wind Harmer
1.186
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.658
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.951
316049AB1-081 GEN
Solar/Wind Harmer
0.761
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.707
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
970223AG2-152 GEN
Solar/Wind Harmer
5.68
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.385
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.31
316283AC2-100 C
Solar/Wind Harmer
1.287
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.767
316210AC1-098 GEN
Solar/Wind Harmer
1.185
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.727
315724AD1-057 GEN
Solar/Wind Harmer
0.389
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.385
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.826
970285AG2-188 GEN
Solar/Wind Harmer
71.806
315657AE1-056 GEN
Solar/Wind Harmer
20.219
946301AF1-294 GEN
Solar/Wind Harmer
13.078
961791AG1-021 GEN
Solar/Wind Harmer
6.379
970683AG2-441 GEN
Solar/Wind Harmer
36.643
970681AG2-440 GEN
Solar/Wind Harmer
29.315
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.296
316239AB2-077_GEN
Solar/Wind Harmer
0.967
316238AB2-078_GEN
Solar/Wind Harmer
0.967
316118AC1-105 GEN
Solar/Wind Harmer
1.799
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.987
970831AG2-522 GEN
Solar/Wind Harmer
9.789
316123AC1-075 GEN
Solar/Wind Harmer
1.778
970165AG2-112 GEN
Solar/Wind Harmer
1.566
970163AG2-111 GEN
Solar/Wind Harmer
1.494
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.49
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.605
270457AD2-023 GEN
Solar/Wind Harmer
0.814
315607AA1-063A GEN
Solar/Wind Harmer
0.881
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.406
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.564
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:203.45 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1422.11
MW Contribution:4.62
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.343
971741AH1-377 GEN
Solar/Wind Harmer
63.689
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.974
963191AG1-168 GEN
Solar/Wind Harmer
4.785
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.258
971775AH1-396 GEN
Solar/Wind Harmer
3.027
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.379
971563AH1-280 GEN
Solar/Wind Harmer
6.379
970685AG2-442 GEN
Solar/Wind Harmer
41.041
962491AG1-098 GEN
Solar/Wind Harmer
28.467
315693AD1-088 GEN
Solar/Wind Harmer
20.844
957481AF2-042 GEN
Solar/Wind Harmer
119.424
316237AB2-079_GEN
Solar/Wind Harmer
0.967
315687AD1-152 GEN
Solar/Wind Harmer
3.708
970401AG2-262 GEN
Solar/Wind Harmer
1.822
316003AC1-222 GEN
Solar/Wind Harmer
2.219
971065AG2-659 GEN
Solar/Wind Harmer
10.747
316129AC1-054 GEN
Solar/Wind Harmer
1.803
971795AH1-408 GEN
Solar/Wind Harmer
11.364
960081AF2-299 GEN
Solar/Wind Harmer
1.186
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.658
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.951
316049AB1-081 GEN
Solar/Wind Harmer
0.761
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.707
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
970223AG2-152 GEN
Solar/Wind Harmer
5.68
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.385
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.31
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.331
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
-0.168
971193AH1-056 GEN
Solar/Wind Harmer
33.698
963181AG1-167 GEN
Solar/Wind Harmer
4.785
959311AF2-222 GEN
Solar/Wind Harmer
45.693
970257AG2-171 GEN
Solar/Wind Harmer
15.944
315785AD2-033 C
Solar/Wind Harmer
9.243
964241AG1-285 GEN
Solar/Wind Harmer
28.257
316478AD1-087 GEN
Solar/Wind Harmer
3.106
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.6
316248AF1-058 C
Solar/Wind Harmer
0.737
960061AF2-297 GEN
Solar/Wind Harmer
12.232
971683AH1-343 GEN
Solar/Wind Harmer
9.152
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.287
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.767
316210AC1-098 GEN
Solar/Wind Harmer
1.185
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.727
315724AD1-057 GEN
Solar/Wind Harmer
0.389
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.385
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.826
970285AG2-188 GEN
Solar/Wind Harmer
71.806
315657AE1-056 GEN
Solar/Wind Harmer
20.219
946301AF1-294 GEN
Solar/Wind Harmer
13.078
961791AG1-021 GEN
Solar/Wind Harmer
6.379
970683AG2-441 GEN
Solar/Wind Harmer
36.643
970681AG2-440 GEN
Solar/Wind Harmer
29.315
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.296
316239AB2-077_GEN
Solar/Wind Harmer
0.967
316238AB2-078_GEN
Solar/Wind Harmer
0.967
316118AC1-105 GEN
Solar/Wind Harmer
1.799
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.987
970831AG2-522 GEN
Solar/Wind Harmer
9.789
316123AC1-075 GEN
Solar/Wind Harmer
1.778
970165AG2-112 GEN
Solar/Wind Harmer
1.566
970163AG2-111 GEN
Solar/Wind Harmer
1.494
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.49
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.605
270457AD2-023 GEN
Solar/Wind Harmer
0.814
315607AA1-063A GEN
Solar/Wind Harmer
0.881
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.406
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.564
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
970099AG2-077 GEN
Solar/Wind Harmer
47.77
313527AB2-043 GEN
Solar/Wind Harmer
5.31
962561AG1-105 GEN
Solar/Wind Harmer
16.108
964791AG1-342 GEN
Solar/Wind Harmer
5.961
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.346
942751AE2-291 GEN
Solar/Wind Harmer
9.222
316222AC1-221 GEN
Solar/Wind Harmer
1.414
316181AB2-040 GEN
Solar/Wind Harmer
1.452
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.154
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.178
3145783HORNRTN
Solar/Wind Harmer
0.943
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.884
316263AC1-034 GEN
Solar/Wind Harmer
3.306
961601AG1-000A GEN
Solar/Wind Harmer
2.693
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
316217AC1-145 GEN
Solar/Wind Harmer
1.032
316197AC1-042 GEN
Solar/Wind Harmer
0.782
942671AE2-283 GEN
Solar/Wind Harmer
2.107
315821AE2-092 GEN
Solar/Wind Helper
2.531
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:130.37 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:911.29
MW Contribution:2.93
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.195
3151601KERR 3
50/50
0.288
3151581KERR 1
50/50
0.103
3151531CLOVER1
50/50
2.951
3147043LAWRENC
50/50
1.104
316322AB2-045
Solar/Wind Harmer
2.6
3146776BUCKING
Solar/Wind Harmer
-0.031
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.967
971563AH1-280 GEN
Solar/Wind Harmer
4.967
970685AG2-442 GEN
Solar/Wind Harmer
31.227
962491AG1-098 GEN
Solar/Wind Harmer
14.504
316237AB2-079_GEN
Solar/Wind Harmer
0.638
315693AD1-088 GEN
Solar/Wind Harmer
10.264
970401AG2-262 GEN
Solar/Wind Harmer
1.084
957481AF2-042 GEN
Solar/Wind Harmer
46.952
315687AD1-152 GEN
Solar/Wind Harmer
1.686
971065AG2-659 GEN
Solar/Wind Harmer
6.782
316129AC1-054 GEN
Solar/Wind Harmer
1.152
316003AC1-222 GEN
Solar/Wind Harmer
1.16
971795AH1-408 GEN
Solar/Wind Harmer
8.774
960081AF2-299 GEN
Solar/Wind Harmer
1.019
3145783HORNRTN
Solar/Wind Harmer
-0.008
3144293JTRSVLE
50/50
1.195
3144293JTRSVLE
50/50
1.006
970535AG2-341 GEN
50/50
2.93
3152661PLYWOOD A
50/50
0.279
3146776BUCKING
Solar/Wind Harmer
-0.308
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.483
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.209
963191AG1-168 GEN
Solar/Wind Harmer
3.725
316190AA2-174 GEN
Solar/Wind Harmer
0.098
316212AC1-099_GEN
Solar/Wind Harmer
0.612
970919AG2-571 GEN
Solar/Wind Harmer
2.186
970087AG2-069 GEN
Solar/Wind Harmer
6.469
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.401
962571AG1-106 GEN
Solar/Wind Harmer
0.963
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316359AB2-059 GEN
Solar/Wind Harmer
0.896
316049AB1-081 GEN
Solar/Wind Harmer
0.717
3142053HEARTS
Solar/Wind Harmer
0.078
315722AD1-056 GEN
Solar/Wind Harmer
0.692
316023GEN1_S
Solar/Wind Harmer
0.442
3145823KELFORD
Solar/Wind Harmer
-0.006
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.19
961671AG1-007 GEN
Solar/Wind Harmer
0.08
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.188
316336AC2-165 C
Solar/Wind Helper
1.427
3151611KERR 4
50/50
0.288
3151621KERR 5
50/50
0.288
3151631KERR 6
50/50
0.288
3151641KERR 7
50/50
0.288
3151541CLOVER2
50/50
2.937
971845AH1-439 GEN
Solar/Wind Harmer
40.264
970285AG2-188 GEN
Solar/Wind Harmer
63.811
315657AE1-056 GEN
Solar/Wind Harmer
15.96
946301AF1-294 GEN
Solar/Wind Harmer
10.183
961791AG1-021 GEN
Solar/Wind Harmer
4.967
970683AG2-441 GEN
Solar/Wind Harmer
27.881
970681AG2-440 GEN
Solar/Wind Harmer
22.305
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.107
316239AB2-077_GEN
Solar/Wind Harmer
0.638
316238AB2-078_GEN
Solar/Wind Harmer
0.638
316118AC1-105 GEN
Solar/Wind Harmer
1.013
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.344
970865AG2-541 GEN
Solar/Wind Harmer
4.105
946281AF1-292 GEN
Solar/Wind Harmer
0.203
316087AB2-174 GEN
Solar/Wind Harmer
1.262
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.891
970165AG2-112 GEN
Solar/Wind Harmer
0.785
970163AG2-111 GEN
Solar/Wind Harmer
0.749
971967AH1-528 GEN
Solar/Wind Harmer
15.159
315607AA1-063A GEN
Solar/Wind Harmer
0.776
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.313
970581AG2-369 GEN
Solar/Wind Harmer
3.709
316319Z2-044 C
Solar/Wind Harmer
0.377
3146033SCOT NK
Solar/Wind Harmer
-0.027
315652AC1-086 GEN
Solar/Wind Harmer
7.536
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
965291AG1-394 GEN
Solar/Wind Harmer
0.58
970673AG2-436 GEN
Solar/Wind Harmer
13.57
970673AG2-436 GEN
Solar/Wind Harmer
6.871
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
270494AE1-108_GEN
Solar/Wind Helper
4.47
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
971741AH1-377 GEN
Solar/Wind Harmer
43.964
316034AC1-036 C
Solar/Wind Harmer
0.583
970323AG2-213 GEN
Solar/Wind Harmer
15.694
971775AH1-396 GEN
Solar/Wind Harmer
2.235
313527AB2-043 GEN
Solar/Wind Harmer
3.534
962561AG1-105 GEN
Solar/Wind Harmer
9.782
939181AE1-148 GEN
Solar/Wind Harmer
9.427
964791AG1-342 GEN
Solar/Wind Harmer
3.547
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
970099AG2-077 GEN
Solar/Wind Harmer
18.781
970933AG2-581 GEN
Solar/Wind Harmer
9.57
316181AB2-040 GEN
Solar/Wind Harmer
1.222
316222AC1-221 GEN
Solar/Wind Harmer
0.854
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.948
3145593CAROLNA
Solar/Wind Harmer
0.07
3145783HORNRTN
Solar/Wind Harmer
0.979
3145783HORNRTN
Solar/Wind Harmer
0.783
3145783HORNRTN
Solar/Wind Harmer
0.245
3145783HORNRTN
Solar/Wind Harmer
0.098
316426AA2-053 GEN
Solar/Wind Harmer
0.81
316274AC1-208 GEN
Solar/Wind Harmer
0.791
942751AE2-291 GEN
Solar/Wind Harmer
4.521
972187AH1-678 GEN
Adder
1.767
972185AH1-677 GEN
Adder
3.338
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
316263AC1-034 GEN
Solar/Wind Harmer
3.115
961601AG1-000A GEN
Solar/Wind Harmer
2.573
3145893MURPHYS
Solar/Wind Harmer
0.179
3145893MURPHYS
Solar/Wind Harmer
-0.012
3145493TOT1
Solar/Wind Harmer
0.098
3145453TOT5
Solar/Wind Harmer
0.059
3144293JTRSVLE
50/50
1.195
3151591KERR 2
50/50
0.288
970413AG2-270 GEN
50/50
12.878
3146776BUCKING
Solar/Wind Harmer
-0.028
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.6
970909AG2-566 GEN
Solar/Wind Harmer
4.079
3147133PAMPLIN
Solar/Wind Harmer
-0.133
971193AH1-056 GEN
Solar/Wind Harmer
26.601
963181AG1-167 GEN
Solar/Wind Harmer
3.725
959311AF2-222 GEN
Solar/Wind Harmer
34.052
970257AG2-171 GEN
Solar/Wind Harmer
11.771
315785AD2-033 C
Solar/Wind Harmer
6.728
964241AG1-285 GEN
Solar/Wind Harmer
19.662
316131AB2-060 GEN
Solar/Wind Harmer
2.419
316478AD1-087 GEN
Solar/Wind Harmer
1.34
316486AD2-202 GEN
Solar/Wind Harmer
0.392
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.389
960061AF2-297 GEN
Solar/Wind Harmer
6.446
971683AH1-343 GEN
Solar/Wind Harmer
4.749
966621AG1-532 GEN
Solar/Wind Harmer
0.184
313506AB2-031 GEN
Solar/Wind Harmer
0.704
316283AC2-100 C
Solar/Wind Harmer
0.785
316210AC1-098 GEN
Solar/Wind Harmer
1.101
316327AA2-057 GEN
Solar/Wind Harmer
0.705
970917AG2-570 GEN
Solar/Wind Harmer
17.269
3146233WITAKRS
Solar/Wind Harmer
0.143
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.004
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.38
316365GEN2_N
Solar/Wind Harmer
0.442
961601AG1-000A GEN
Solar/Wind Harmer
2.606
316317KELFORD C
Solar/Wind Harmer
0.305
3145823KELFORD
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.082
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
957521AF2-046 GEN
Solar/Wind Harmer
5.021
961681AG1-008 GEN
Solar/Wind Harmer
5.021
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.333
316258AE1-075 C
Solar/Wind Helper
0.299
316405AF2-144 C
Solar/Wind Helper
0.249
3148013FISHERV
Solar/Wind Helper
0.124
3145603CNETO
Solar/Wind Harmer
0.039
315821AE2-092 GEN
Solar/Wind Helper
2.966
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.871
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.899
MECLTFEXP_MEC->PJM
CLTF
0.811
SIGELTFEXP_SIGE->PJM
CLTF
0.021
CPLELTFEXP_CPLE->PJM
CLTF
4.525
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.338
LAGNLTFEXP_LAGN->PJM
CLTF
2.472
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.204
TVALTFEXP_TVA->PJM
CLTF
1.2
NYPJM->LTFIMP_NY
CLTF
0.305
LGEELTFEXP_LGEE->PJM
CLTF
0.208
WECLTFEXP_WEC->PJM
CLTF
0.117

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2106-2111_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2106-2111_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:130.23 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:910.33
MW Contribution:2.83
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.179
3144293JTRSVLE
50/50
0.993
970535AG2-341 GEN
50/50
2.832
3152661PLYWOOD A
50/50
0.267
3146776BUCKING
Solar/Wind Harmer
-0.306
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.246
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.13
963191AG1-168 GEN
Solar/Wind Harmer
3.678
971741AH1-377 GEN
Solar/Wind Harmer
43.39
316034AC1-036 C
Solar/Wind Harmer
0.573
970323AG2-213 GEN
Solar/Wind Harmer
15.422
971775AH1-396 GEN
Solar/Wind Harmer
2.196
313527AB2-043 GEN
Solar/Wind Harmer
3.438
962561AG1-105 GEN
Solar/Wind Harmer
9.444
939181AE1-148 GEN
Solar/Wind Harmer
9.07
964791AG1-342 GEN
Solar/Wind Harmer
3.418
3144293JTRSVLE
50/50
1.179
3151601KERR 3
50/50
0.277
3151581KERR 1
50/50
0.099
3151531CLOVER1
50/50
2.838
316322AB2-045
Solar/Wind Harmer
2.588
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.069
970933AG2-581 GEN
Solar/Wind Harmer
9.057
316181AB2-040 GEN
Solar/Wind Harmer
1.135
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.876
3145593CAROLNA
Solar/Wind Harmer
0.065
3145783HORNRTN
Solar/Wind Harmer
0.902
3145783HORNRTN
Solar/Wind Harmer
0.721
3145783HORNRTN
Solar/Wind Harmer
0.225
3145783HORNRTN
Solar/Wind Harmer
0.09
316222AC1-221 GEN
Solar/Wind Harmer
0.766
316426AA2-053 GEN
Solar/Wind Harmer
0.746
942751AE2-291 GEN
Solar/Wind Harmer
4.318
316274AC1-208 GEN
Solar/Wind Harmer
0.714
972187AH1-678 GEN
Adder
1.624
315821AE2-092 GEN
Solar/Wind Helper
2.997
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.904
971563AH1-280 GEN
Solar/Wind Harmer
4.904
970685AG2-442 GEN
Solar/Wind Harmer
30.768
962491AG1-098 GEN
Solar/Wind Harmer
14.136
316237AB2-079_GEN
Solar/Wind Harmer
0.62
315693AD1-088 GEN
Solar/Wind Harmer
9.987
970401AG2-262 GEN
Solar/Wind Harmer
1.044
957481AF2-042 GEN
Solar/Wind Harmer
45.172
315687AD1-152 GEN
Solar/Wind Harmer
1.609
971065AG2-659 GEN
Solar/Wind Harmer
6.46
316129AC1-054 GEN
Solar/Wind Harmer
1.096
3147043LAWRENC
Adder
0.992
316003AC1-222 GEN
Solar/Wind Harmer
1.105
971795AH1-408 GEN
Solar/Wind Harmer
8.324
960081AF2-299 GEN
Solar/Wind Harmer
0.951
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.091
316336AC2-165 C
Solar/Wind Helper
1.456
3151611KERR 4
50/50
0.277
3151621KERR 5
50/50
0.277
3151631KERR 6
50/50
0.277
3151641KERR 7
50/50
0.277
3151541CLOVER2
50/50
2.825
971845AH1-439 GEN
Solar/Wind Harmer
40.074
970285AG2-188 GEN
Solar/Wind Harmer
63.49
315657AE1-056 GEN
Solar/Wind Harmer
15.775
946301AF1-294 GEN
Solar/Wind Harmer
10.053
961791AG1-021 GEN
Solar/Wind Harmer
4.904
970683AG2-441 GEN
Solar/Wind Harmer
27.471
970681AG2-440 GEN
Solar/Wind Harmer
21.977
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
5.999
316239AB2-077_GEN
Solar/Wind Harmer
0.62
316238AB2-078_GEN
Solar/Wind Harmer
0.62
316118AC1-105 GEN
Solar/Wind Harmer
0.971
3147173SINAI
Solar/Wind Harmer
-0.012
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.022
970865AG2-541 GEN
Solar/Wind Harmer
3.914
946281AF1-292 GEN
Solar/Wind Harmer
0.189
316087AB2-174 GEN
Solar/Wind Harmer
1.174
3137643SOCKMAN
Solar/Wind Harmer
-0.032
316123AC1-075 GEN
Solar/Wind Harmer
0.851
970165AG2-112 GEN
Solar/Wind Harmer
0.749
970163AG2-111 GEN
Solar/Wind Harmer
0.714
971967AH1-528 GEN
Solar/Wind Harmer
14.144
315607AA1-063A GEN
Solar/Wind Harmer
0.713
3146043SEABORD
Solar/Wind Harmer
-0.007
270494AE1-108_GEN
Solar/Wind Helper
4.505
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3144293JTRSVLE
50/50
1.179
3151591KERR 2
50/50
0.277
970413AG2-270 GEN
50/50
12.386
3146776BUCKING
Solar/Wind Harmer
-0.027
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.532
970909AG2-566 GEN
Solar/Wind Harmer
4.034
3147133PAMPLIN
Solar/Wind Harmer
-0.131
971193AH1-056 GEN
Solar/Wind Harmer
26.292
963181AG1-167 GEN
Solar/Wind Harmer
3.678
959311AF2-222 GEN
Solar/Wind Harmer
33.489
970257AG2-171 GEN
Solar/Wind Harmer
11.567
315785AD2-033 C
Solar/Wind Harmer
6.603
964241AG1-285 GEN
Solar/Wind Harmer
19.215
316131AB2-060 GEN
Solar/Wind Harmer
2.356
316478AD1-087 GEN
Solar/Wind Harmer
1.288
316486AD2-202 GEN
Solar/Wind Harmer
0.377
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.37
960061AF2-297 GEN
Solar/Wind Harmer
6.139
971683AH1-343 GEN
Solar/Wind Harmer
4.525
966621AG1-532 GEN
Solar/Wind Harmer
0.171
313506AB2-031 GEN
Solar/Wind Harmer
0.654
316283AC2-100 C
Solar/Wind Harmer
0.703
316313AB2-026
Solar/Wind Helper
0.341
316258AE1-075 C
Solar/Wind Helper
0.307
316405AF2-144 C
Solar/Wind Helper
0.256
3148013FISHERV
Solar/Wind Helper
0.125
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.959
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.906
MECLTFEXP_MEC->PJM
CLTF
0.618
SIGELTFEXP_SIGE->PJM
CLTF
0.017
CPLELTFEXP_CPLE->PJM
CLTF
3.699
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.437
LAGNLTFEXP_LAGN->PJM
CLTF
1.81
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.409
TVALTFEXP_TVA->PJM
CLTF
0.888
NYPJM->LTFIMP_NY
CLTF
0.351
LGEELTFEXP_LGEE->PJM
CLTF
0.175
WECLTFEXP_WEC->PJM
CLTF
0.091

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2003-205_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2003-205_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:126.86 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:886.73
MW Contribution:2.9
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.284
3151621KERR 5
50/50
0.284
3151631KERR 6
50/50
0.284
3151641KERR 7
50/50
0.284
3151541CLOVER2
50/50
2.899
971845AH1-439 GEN
Solar/Wind Harmer
40.166
970285AG2-188 GEN
Solar/Wind Harmer
63.65
315657AE1-056 GEN
Solar/Wind Harmer
15.889
946301AF1-294 GEN
Solar/Wind Harmer
10.133
961791AG1-021 GEN
Solar/Wind Harmer
4.943
970683AG2-441 GEN
Solar/Wind Harmer
27.73
970681AG2-440 GEN
Solar/Wind Harmer
22.184
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.068
316239AB2-077_GEN
Solar/Wind Harmer
0.632
316238AB2-078_GEN
Solar/Wind Harmer
0.632
316118AC1-105 GEN
Solar/Wind Harmer
0.995
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.242
970865AG2-541 GEN
Solar/Wind Harmer
4.039
946281AF1-292 GEN
Solar/Wind Harmer
0.204
316087AB2-174 GEN
Solar/Wind Harmer
1.259
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.881
970165AG2-112 GEN
Solar/Wind Harmer
0.776
970163AG2-111 GEN
Solar/Wind Harmer
0.74
971967AH1-528 GEN
Solar/Wind Harmer
14.996
315607AA1-063A GEN
Solar/Wind Harmer
0.76
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.198
970581AG2-369 GEN
Solar/Wind Harmer
3.61
315652AC1-086 GEN
Solar/Wind Harmer
7.443
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.026
316319Z2-044 C
Solar/Wind Harmer
0.358
970673AG2-436 GEN
Solar/Wind Harmer
13.401
970673AG2-436 GEN
Solar/Wind Harmer
6.785
965291AG1-394 GEN
Solar/Wind Harmer
0.563
270494AE1-108_GEN
Solar/Wind Helper
4.481
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3144293JTRSVLE
50/50
1.189
3144293JTRSVLE
50/50
1.001
970535AG2-341 GEN
50/50
2.895
3152661PLYWOOD A
50/50
0.274
3146776BUCKING
Solar/Wind Harmer
-0.307
3146776BUCKING
Solar/Wind Harmer
-0.025
3144293JTRSVLE
50/50
1.189
3151591KERR 2
50/50
0.284
970413AG2-270 GEN
50/50
12.71
3146776BUCKING
Solar/Wind Harmer
-0.027
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.572
970909AG2-566 GEN
Solar/Wind Harmer
4.062
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.482
963181AG1-167 GEN
Solar/Wind Harmer
3.707
959311AF2-222 GEN
Solar/Wind Harmer
33.848
970257AG2-171 GEN
Solar/Wind Harmer
11.697
315785AD2-033 C
Solar/Wind Harmer
6.684
964241AG1-285 GEN
Solar/Wind Harmer
19.507
316131AB2-060 GEN
Solar/Wind Harmer
2.398
316478AD1-087 GEN
Solar/Wind Harmer
1.322
316486AD2-202 GEN
Solar/Wind Harmer
0.387
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.38
960061AF2-297 GEN
Solar/Wind Harmer
6.313
971683AH1-343 GEN
Solar/Wind Harmer
4.664
966621AG1-532 GEN
Solar/Wind Harmer
0.184
313506AB2-031 GEN
Solar/Wind Harmer
0.7
316283AC2-100 C
Solar/Wind Harmer
0.734
316210AC1-098 GEN
Solar/Wind Harmer
1.061
970917AG2-570 GEN
Solar/Wind Harmer
16.827
316365GEN2_N
Solar/Wind Harmer
0.451
316327AA2-057 GEN
Solar/Wind Harmer
0.674
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.136
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
315724AD1-057 GEN
Solar/Wind Harmer
0.366
316313AB2-026
Solar/Wind Helper
0.342
316258AE1-075 C
Solar/Wind Helper
0.308
316405AF2-144 C
Solar/Wind Helper
0.257
3148013FISHERV
Solar/Wind Helper
0.124
970301AG2-198 GEN
Solar/Wind Harmer
21.395
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.179
963191AG1-168 GEN
Solar/Wind Harmer
3.707
971741AH1-377 GEN
Solar/Wind Harmer
43.759
316034AC1-036 C
Solar/Wind Harmer
0.58
970323AG2-213 GEN
Solar/Wind Harmer
15.596
971775AH1-396 GEN
Solar/Wind Harmer
2.221
313527AB2-043 GEN
Solar/Wind Harmer
3.501
962561AG1-105 GEN
Solar/Wind Harmer
9.651
939181AE1-148 GEN
Solar/Wind Harmer
9.294
964791AG1-342 GEN
Solar/Wind Harmer
3.496
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.573
970933AG2-581 GEN
Solar/Wind Harmer
9.469
316181AB2-040 GEN
Solar/Wind Harmer
1.215
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.932
3145593CAROLNA
Solar/Wind Harmer
0.069
3145783HORNRTN
Solar/Wind Harmer
0.96
3145783HORNRTN
Solar/Wind Harmer
0.768
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
316222AC1-221 GEN
Solar/Wind Harmer
0.8
316426AA2-053 GEN
Solar/Wind Harmer
0.794
316274AC1-208 GEN
Solar/Wind Harmer
0.763
942751AE2-291 GEN
Solar/Wind Harmer
4.488
972187AH1-678 GEN
Adder
1.739
972185AH1-677 GEN
Adder
3.291
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
315821AE2-092 GEN
Solar/Wind Helper
2.986
3144293JTRSVLE
50/50
1.189
3151601KERR 3
50/50
0.284
3151581KERR 1
50/50
0.101
3151531CLOVER1
50/50
2.913
3147043LAWRENC
50/50
1.1
316322AB2-045
Solar/Wind Harmer
2.593
3146776BUCKING
Solar/Wind Harmer
-0.031
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.943
971563AH1-280 GEN
Solar/Wind Harmer
4.943
970685AG2-442 GEN
Solar/Wind Harmer
31.058
962491AG1-098 GEN
Solar/Wind Harmer
14.389
316237AB2-079_GEN
Solar/Wind Harmer
0.632
315693AD1-088 GEN
Solar/Wind Harmer
10.178
970401AG2-262 GEN
Solar/Wind Harmer
1.068
957481AF2-042 GEN
Solar/Wind Harmer
46.433
315687AD1-152 GEN
Solar/Wind Harmer
1.654
971065AG2-659 GEN
Solar/Wind Harmer
6.674
316129AC1-054 GEN
Solar/Wind Harmer
1.134
971795AH1-408 GEN
Solar/Wind Harmer
8.763
316003AC1-222 GEN
Solar/Wind Harmer
1.138
960081AF2-299 GEN
Solar/Wind Harmer
1.022
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.097
316212AC1-099_GEN
Solar/Wind Harmer
0.589
970919AG2-571 GEN
Solar/Wind Harmer
2.13
970087AG2-069 GEN
Solar/Wind Harmer
6.297
316023GEN1_S
Solar/Wind Harmer
0.451
316011AB1-132 GEN
Solar/Wind Harmer
1.384
962571AG1-106 GEN
Solar/Wind Harmer
0.951
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
-0.026
315722AD1-056 GEN
Solar/Wind Harmer
0.665
316336AC2-165 C
Solar/Wind Helper
1.458
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.279
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.343
MECLTFEXP_MEC->PJM
CLTF
0.782
SIGELTFEXP_SIGE->PJM
CLTF
0.022
CPLELTFEXP_CPLE->PJM
CLTF
3.934
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.902
LAGNLTFEXP_LAGN->PJM
CLTF
2.053
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.953
TVALTFEXP_TVA->PJM
CLTF
1.009
NYPJM->LTFIMP_NY
CLTF
0.325
LGEELTFEXP_LGEE->PJM
CLTF
0.24
WECLTFEXP_WEC->PJM
CLTF
0.127

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:118.39 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:827.52
MW Contribution:2.87
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.186
3151601KERR 3
50/50
0.281
3151581KERR 1
50/50
0.1
3151531CLOVER1
50/50
2.878
3144293JTRSVLE
50/50
1.186
3144293JTRSVLE
50/50
0.998
970535AG2-341 GEN
50/50
2.87
3152661PLYWOOD A
50/50
0.275
3146776BUCKING
Solar/Wind Harmer
-0.307
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.329
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.162
963191AG1-168 GEN
Solar/Wind Harmer
3.697
971741AH1-377 GEN
Solar/Wind Harmer
43.59
316034AC1-036 C
Solar/Wind Harmer
0.577
970323AG2-213 GEN
Solar/Wind Harmer
15.535
971775AH1-396 GEN
Solar/Wind Harmer
2.212
313527AB2-043 GEN
Solar/Wind Harmer
3.479
962561AG1-105 GEN
Solar/Wind Harmer
9.636
964791AG1-342 GEN
Solar/Wind Harmer
3.494
939181AE1-148 GEN
Solar/Wind Harmer
9.198
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.308
970933AG2-581 GEN
Solar/Wind Harmer
9.214
316181AB2-040 GEN
Solar/Wind Harmer
1.159
942751AE2-291 GEN
Solar/Wind Harmer
5.121
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.895
3145593CAROLNA
Solar/Wind Harmer
0.066
316222AC1-221 GEN
Solar/Wind Harmer
0.788
3145783HORNRTN
Solar/Wind Harmer
0.922
3145783HORNRTN
Solar/Wind Harmer
0.738
3145783HORNRTN
Solar/Wind Harmer
0.231
3145783HORNRTN
Solar/Wind Harmer
0.092
316322AB2-045
Solar/Wind Harmer
2.592
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.929
971563AH1-280 GEN
Solar/Wind Harmer
4.929
970685AG2-442 GEN
Solar/Wind Harmer
30.955
962491AG1-098 GEN
Solar/Wind Harmer
14.261
316237AB2-079_GEN
Solar/Wind Harmer
0.628
315693AD1-088 GEN
Solar/Wind Harmer
10.081
970401AG2-262 GEN
Solar/Wind Harmer
1.068
957481AF2-042 GEN
Solar/Wind Harmer
45.769
315687AD1-152 GEN
Solar/Wind Harmer
1.638
971065AG2-659 GEN
Solar/Wind Harmer
6.564
316129AC1-054 GEN
Solar/Wind Harmer
1.114
3147043LAWRENC
Adder
1.008
316003AC1-222 GEN
Solar/Wind Harmer
1.162
971795AH1-408 GEN
Solar/Wind Harmer
8.467
960081AF2-299 GEN
Solar/Wind Harmer
0.97
3145783HORNRTN
Solar/Wind Harmer
-0.008
3151611KERR 4
50/50
0.281
3151621KERR 5
50/50
0.281
3151631KERR 6
50/50
0.281
3151641KERR 7
50/50
0.281
3151541CLOVER2
50/50
2.864
971845AH1-439 GEN
Solar/Wind Harmer
40.143
970285AG2-188 GEN
Solar/Wind Harmer
63.606
315657AE1-056 GEN
Solar/Wind Harmer
15.849
946301AF1-294 GEN
Solar/Wind Harmer
10.105
961791AG1-021 GEN
Solar/Wind Harmer
4.929
970683AG2-441 GEN
Solar/Wind Harmer
27.639
970681AG2-440 GEN
Solar/Wind Harmer
22.111
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.044
316239AB2-077_GEN
Solar/Wind Harmer
0.628
316238AB2-078_GEN
Solar/Wind Harmer
0.628
316118AC1-105 GEN
Solar/Wind Harmer
0.998
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.123
970865AG2-541 GEN
Solar/Wind Harmer
4.251
316123AC1-075 GEN
Solar/Wind Harmer
0.968
970165AG2-112 GEN
Solar/Wind Harmer
0.853
970163AG2-111 GEN
Solar/Wind Harmer
0.813
946281AF1-292 GEN
Solar/Wind Harmer
0.193
316087AB2-174 GEN
Solar/Wind Harmer
1.199
3137643SOCKMAN
Solar/Wind Harmer
-0.032
971967AH1-528 GEN
Solar/Wind Harmer
14.441
316426AA2-053 GEN
Solar/Wind Harmer
0.763
316274AC1-208 GEN
Solar/Wind Harmer
0.732
972187AH1-678 GEN
Adder
1.663
315821AE2-092 GEN
Solar/Wind Helper
2.985
3144293JTRSVLE
50/50
1.186
3151591KERR 2
50/50
0.281
970413AG2-270 GEN
50/50
12.559
3146776BUCKING
Solar/Wind Harmer
-0.027
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.558
970909AG2-566 GEN
Solar/Wind Harmer
4.05
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.415
963181AG1-167 GEN
Solar/Wind Harmer
3.697
959311AF2-222 GEN
Solar/Wind Harmer
33.722
970257AG2-171 GEN
Solar/Wind Harmer
11.651
315785AD2-033 C
Solar/Wind Harmer
6.656
964241AG1-285 GEN
Solar/Wind Harmer
19.405
316131AB2-060 GEN
Solar/Wind Harmer
2.383
316478AD1-087 GEN
Solar/Wind Harmer
1.306
316486AD2-202 GEN
Solar/Wind Harmer
0.383
316248AF1-058 C
Solar/Wind Harmer
0.383
960061AF2-297 GEN
Solar/Wind Harmer
6.356
3147043LAWRENC
Solar/Wind Harmer
-0.007
971683AH1-343 GEN
Solar/Wind Harmer
4.828
966621AG1-532 GEN
Solar/Wind Harmer
0.175
313506AB2-031 GEN
Solar/Wind Harmer
0.668
316190AA2-174 GEN
Solar/Wind Harmer
0.093
316212AC1-099_GEN
Solar/Wind Harmer
0.565
970919AG2-571 GEN
Solar/Wind Harmer
2.04
970087AG2-069 GEN
Solar/Wind Harmer
6.032
316336AC2-165 C
Solar/Wind Helper
1.446
315607AA1-063A GEN
Solar/Wind Harmer
0.73
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.021
970581AG2-369 GEN
Solar/Wind Harmer
3.458
270494AE1-108_GEN
Solar/Wind Helper
4.516
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
316283AC2-100 C
Solar/Wind Harmer
0.723
316210AC1-098 GEN
Solar/Wind Harmer
1.017
970917AG2-570 GEN
Solar/Wind Harmer
16.116
316327AA2-057 GEN
Solar/Wind Harmer
0.646
316313AB2-026
Solar/Wind Helper
0.338
316258AE1-075 C
Solar/Wind Helper
0.304
316405AF2-144 C
Solar/Wind Helper
0.253
3148013FISHERV
Solar/Wind Helper
0.124
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.791
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.144
MECLTFEXP_MEC->PJM
CLTF
0.716
SIGELTFEXP_SIGE->PJM
CLTF
0.02
CPLELTFEXP_CPLE->PJM
CLTF
3.818
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.266
LAGNLTFEXP_LAGN->PJM
CLTF
1.942
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.684
TVALTFEXP_TVA->PJM
CLTF
0.953
NYPJM->LTFIMP_NY
CLTF
0.309
LGEELTFEXP_LGEE->PJM
CLTF
0.214
WECLTFEXP_WEC->PJM
CLTF
0.113

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.79 %
Rating:571.52 MVA
Rating Type:A
MVA to Mitigate:644.61
MW Contribution:2.85
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.278
3151621KERR 5
50/50
0.278
3151631KERR 6
50/50
0.278
3151641KERR 7
50/50
0.278
3151541CLOVER2
50/50
2.843
3151281ROARAP4
50/50
0.085
3151281ROARAP4
50/50
0.079
963041AG1-153 GEN
50/50
1.544
971845AH1-439 GEN
Solar/Wind Harmer
30.475
970285AG2-188 GEN
Solar/Wind Harmer
51.158
315657AE1-056 GEN
Solar/Wind Harmer
12.943
946301AF1-294 GEN
Solar/Wind Harmer
6.907
961791AG1-021 GEN
Solar/Wind Harmer
3.36
970683AG2-441 GEN
Solar/Wind Harmer
20.922
970681AG2-440 GEN
Solar/Wind Harmer
16.737
3144303KENBRDG
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
4.571
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.326
3147173SINAI
Solar/Wind Harmer
0.11
3147243WELCO
Solar/Wind Harmer
0.069
970831AG2-522 GEN
Solar/Wind Harmer
4.61
970865AG2-541 GEN
Solar/Wind Harmer
3.002
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.286
316123AC1-075 GEN
Solar/Wind Harmer
0.097
970165AG2-112 GEN
Solar/Wind Harmer
0.576
970163AG2-111 GEN
Solar/Wind Harmer
0.549
971967AH1-528 GEN
Solar/Wind Harmer
10.852
315607AA1-063A GEN
Solar/Wind Harmer
0.13
3146043SEABORD
Solar/Wind Harmer
0.063
970085AG2-068 GEN
Solar/Wind Harmer
3.026
970581AG2-369 GEN
Solar/Wind Harmer
2.602
270494AE1-108_GEN
Solar/Wind Helper
4.482
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.182
3151591KERR 2
50/50
0.278
970413AG2-270 GEN
50/50
12.466
3151261ROARAP2
50/50
0.085
3151031BRUNSWICKG2
50/50
0.762
3146776BUCKING
Solar/Wind Harmer
0.247
3146926FARMVIL
Solar/Wind Harmer
0.316
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.043
3147133PAMPLIN
Solar/Wind Harmer
1.178
971193AH1-056 GEN
Solar/Wind Harmer
22.85
963181AG1-167 GEN
Solar/Wind Harmer
1.4
959311AF2-222 GEN
Solar/Wind Harmer
25.461
970257AG2-171 GEN
Solar/Wind Harmer
8.812
315785AD2-033 C
Solar/Wind Harmer
2.115
964241AG1-285 GEN
Solar/Wind Harmer
14.651
316131AB2-060 GEN
Solar/Wind Harmer
0.614
316478AD1-087 GEN
Solar/Wind Harmer
0.465
316486AD2-202 GEN
Solar/Wind Harmer
0.137
3147043LAWRENC
Solar/Wind Harmer
0.066
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.699
971683AH1-343 GEN
Solar/Wind Harmer
3.468
313506AB2-031 GEN
Solar/Wind Harmer
0.226
316283AC2-100 C
Solar/Wind Harmer
0.132
316210AC1-098 GEN
Solar/Wind Harmer
0.53
970917AG2-570 GEN
Solar/Wind Harmer
5.054
316327AA2-057 GEN
Solar/Wind Harmer
0.085
316313AB2-026
Solar/Wind Helper
0.339
316258AE1-075 C
Solar/Wind Helper
0.305
316405AF2-144 C
Solar/Wind Helper
0.254
3148013FISHERV
Solar/Wind Helper
0.124
3144293JTRSVLE
50/50
1.182
3151601KERR 3
50/50
0.278
3151581KERR 1
50/50
0.099
3151531CLOVER1
50/50
2.857
3147043LAWRENC
50/50
1.061
3151261ROARAP2
50/50
0.087
3151051BRUNSWICKS1
50/50
1.582
3151021BRUNSWICKG1
50/50
0.762
971451AH1-221 GEN
50/50
2.315
316322AB2-045
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Harmer
0.316
963171AG1-166 GEN
Solar/Wind Harmer
1.867
971563AH1-280 GEN
Solar/Wind Harmer
3.734
970685AG2-442 GEN
Solar/Wind Harmer
23.432
962491AG1-098 GEN
Solar/Wind Harmer
10.785
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
8.574
970401AG2-262 GEN
Solar/Wind Harmer
0.841
957481AF2-042 GEN
Solar/Wind Harmer
34.537
315687AD1-152 GEN
Solar/Wind Harmer
0.004
971065AG2-659 GEN
Solar/Wind Harmer
4.943
316129AC1-054 GEN
Solar/Wind Harmer
0.422
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971795AH1-408 GEN
Solar/Wind Harmer
6.643
960081AF2-299 GEN
Solar/Wind Harmer
0.73
3145783HORNRTN
Solar/Wind Harmer
0.068
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
0.295
970919AG2-571 GEN
Solar/Wind Harmer
2.021
970087AG2-069 GEN
Solar/Wind Harmer
4.539
316336AC2-165 C
Solar/Wind Helper
1.447
3144293JTRSVLE
50/50
1.182
3144293JTRSVLE
50/50
0.996
970535AG2-341 GEN
50/50
2.848
3152661PLYWOOD A
50/50
0.269
3151041BRUNSWICKG3
50/50
0.762
972187AH1-678 GEN
50/50
1.749
3146776BUCKING
Solar/Wind Harmer
2.741
3146776BUCKING
Solar/Wind Harmer
0.222
970301AG2-198 GEN
Solar/Wind Harmer
16.173
3147133PAMPLIN
Solar/Wind Harmer
0.375
3147133PAMPLIN
Solar/Wind Harmer
0.3
958211AF2-115 GEN
Solar/Wind Harmer
4.2
963191AG1-168 GEN
Solar/Wind Harmer
1.4
971741AH1-377 GEN
Solar/Wind Harmer
33.04
316034AC1-036 C
Solar/Wind Harmer
0.02
970323AG2-213 GEN
Solar/Wind Harmer
11.75
971775AH1-396 GEN
Solar/Wind Harmer
0.441
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
7.214
939181AE1-148 GEN
Solar/Wind Harmer
6.93
964791AG1-342 GEN
Solar/Wind Harmer
2.751
3146843MT LREL
Solar/Wind Harmer
0.143
3146843MT LREL
Solar/Wind Harmer
0.143
970099AG2-077 GEN
Solar/Wind Harmer
13.815
970933AG2-581 GEN
Solar/Wind Harmer
6.948
316181AB2-040 GEN
Solar/Wind Harmer
0.106
3145593CAROLNA
Solar/Wind Harmer
0.07
3145593CAROLNA
Solar/Wind Harmer
0.07
966811AG1-552 GEN
Solar/Wind Harmer
0.761
3145593CAROLNA
Solar/Wind Harmer
0.087
3145783HORNRTN
Solar/Wind Harmer
1.218
3145783HORNRTN
Solar/Wind Harmer
0.974
3145783HORNRTN
Solar/Wind Harmer
0.304
3145783HORNRTN
Solar/Wind Harmer
0.122
316222AC1-221 GEN
Solar/Wind Harmer
0.283
316426AA2-053 GEN
Solar/Wind Harmer
0.225
942751AE2-291 GEN
Solar/Wind Harmer
3.327
316274AC1-208 GEN
Solar/Wind Harmer
0.31
315821AE2-092 GEN
Solar/Wind Helper
2.982
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.922
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.157
MECLTFEXP_MEC->PJM
CLTF
0.729
SIGELTFEXP_SIGE->PJM
CLTF
0.02
CPLELTFEXP_CPLE->PJM
CLTF
3.771
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.326
LAGNLTFEXP_LAGN->PJM
CLTF
1.944
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.608
TVALTFEXP_TVA->PJM
CLTF
0.955
NYPJM->LTFIMP_NY
CLTF
0.308
LGEELTFEXP_LGEE->PJM
CLTF
0.221
WECLTFEXP_WEC->PJM
CLTF
0.117

Details for 6CAROLNA-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CAROLNA-6NORTHAMPTON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 238_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.63 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:568.39
MW Contribution:1.36
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
1.028
3151411GASTONB
50/50
1.028
3147043LAWRENC
50/50
2.073
3151261ROARAP2
50/50
0.259
3151601KERR 3
50/50
0.163
3151581KERR 1
50/50
0.058
316011AB1-132 GEN
Solar/Wind Harmer
6.91
962571AG1-106 GEN
Solar/Wind Harmer
5.407
316023GEN1_S
Solar/Wind Harmer
0.795
3145796HORNRTN
Solar/Wind Harmer
1.133
3145796HORNRTN
Solar/Wind Harmer
0.343
960081AF2-299 GEN
Solar/Wind Harmer
2.67
971795AH1-408 GEN
Solar/Wind Harmer
15.703
315722AD1-056 GEN
Solar/Wind Harmer
1.419
3145783HORNRTN
Solar/Wind Harmer
0.193
316190AA2-174 GEN
Solar/Wind Harmer
0
316129AC1-054 GEN
Solar/Wind Harmer
0.465
316359AB2-059 GEN
Solar/Wind Harmer
0.423
316049AB1-081 GEN
Solar/Wind Harmer
0.673
3142053HEARTS
Solar/Wind Harmer
0.207
971065AG2-659 GEN
Solar/Wind Harmer
4.959
3145543BTLEBRO
Solar/Wind Harmer
0.115
3145543BTLEBRO
Solar/Wind Harmer
0.092
3146233WITAKRS
Solar/Wind Harmer
0.447
316237AB2-079_GEN
Solar/Wind Harmer
0.001
316212AC1-099_GEN
Solar/Wind Harmer
0.351
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.255
3146206CASHIE
Solar/Wind Helper
0.33
3145683EARLEYS
Solar/Wind Helper
0.237
3145663CRESWEL
Solar/Wind Helper
0.648
3145963POPLR C
Solar/Wind Helper
0.205
316174AB2-169 GEN
Solar/Wind Helper
0.492
3130156CHOWAN
Solar/Wind Helper
0.19
315800Z1-036_GEN1
Solar/Wind Helper
0.918
3146516WINFALL
Solar/Wind Helper
0.444
3146516WINFALL
Solar/Wind Helper
0.137
3151281ROARAP4
50/50
0.252
3151281ROARAP4
50/50
0.235
3151611KERR 4
50/50
0.163
3151621KERR 5
50/50
0.163
3151631KERR 6
50/50
0.163
3151641KERR 7
50/50
0.163
315652AC1-086 GEN
Solar/Wind Harmer
41.807
315814AE2-033 C
Solar/Wind Harmer
27.758
3145796HORNRTN
Solar/Wind Harmer
1.099
3145796HORNRTN
Solar/Wind Harmer
0.137
316087AB2-174 GEN
Solar/Wind Harmer
0.007
3137643SOCKMAN
Solar/Wind Harmer
0.897
315607AA1-063A GEN
Solar/Wind Harmer
0.301
3146043SEABORD
Solar/Wind Harmer
0.138
970831AG2-522 GEN
Solar/Wind Harmer
5.625
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
0.986
3144303KENBRDG
Solar/Wind Harmer
0.046
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
3146206CASHIE
Solar/Wind Helper
0.33
315732AD1-074 GEN1
Solar/Wind Helper
3.077
315733AD1-074 GEN2
Solar/Wind Helper
3.077
315735AD1-075 GEN1
Solar/Wind Helper
1.538
3130546PLYMOUTH
Solar/Wind Helper
0.263
3145683EARLEYS
Solar/Wind Helper
0.473
3145683EARLEYS
Solar/Wind Helper
0.237
3145683EARLEYS
Solar/Wind Helper
0.237
315816AE2-034 GEN
Solar/Wind Helper
1.058
3130156CHOWAN
Solar/Wind Helper
0.19
3130156CHOWAN
Solar/Wind Helper
0.19
3145513AHOSKIE
Solar/Wind Helper
0.081
961941AG1-037 GEN
Solar/Wind Helper
0.061
3145513AHOSKIE
Solar/Wind Helper
0.18
315611Z1-036_GEN2
Solar/Wind Helper
0.918
316005AA1-067
Solar/Wind Helper
0.14
3145746EVERETS
Solar/Wind Helper
0.488
3151361ROSEMG1
50/50
1.237
3151371ROSEMS1
50/50
0.767
3151381ROSEMG2
50/50
0.579
970535AG2-341 GEN
50/50
1.356
3145796HORNRTN
Solar/Wind Harmer
1.03
316181AB2-040 GEN
Solar/Wind Harmer
0.355
3145593CAROLNA
Solar/Wind Harmer
0.208
3145593CAROLNA
Solar/Wind Harmer
0.208
966811AG1-552 GEN
Solar/Wind Harmer
2.253
3145593CAROLNA
Solar/Wind Harmer
0.259
3145783HORNRTN
Solar/Wind Harmer
3.437
3145783HORNRTN
Solar/Wind Harmer
2.75
3145783HORNRTN
Solar/Wind Harmer
0.859
3145783HORNRTN
Solar/Wind Harmer
0.344
316426AA2-053 GEN
Solar/Wind Harmer
0.504
961601AG1-000A GEN
Solar/Wind Harmer
2.217
316263AC1-034 GEN
Solar/Wind Harmer
4.47
316274AC1-208 GEN
Solar/Wind Harmer
0.608
939181AE1-148 GEN
Solar/Wind Harmer
3.733
313527AB2-043 GEN
Solar/Wind Harmer
0.001
970323AG2-213 GEN
Solar/Wind Harmer
2.478
971775AH1-396 GEN
Solar/Wind Harmer
0.093
316034AC1-036 C
Solar/Wind Harmer
0.004
3145493TOT1
Solar/Wind Harmer
0.133
3145453TOT5
Solar/Wind Harmer
0.08
3145603CNETO
Solar/Wind Harmer
0.053
3142666NORTHAMPTON
Solar/Wind Helper
1.362
3142666NORTHAMPTON
Solar/Wind Helper
1.362
3142666NORTHAMPTON
Solar/Wind Helper
1.362
3142666NORTHAMPTON
Solar/Wind Helper
0.817
3146626S HERTFORD
Solar/Wind Helper
0.15
3146626S HERTFORD
Solar/Wind Helper
0.15
3145933PARMELE
Solar/Wind Helper
0.298
3145933PARMELE
Solar/Wind Helper
0.149
3146516WINFALL
Solar/Wind Helper
0.137
3146516WINFALL
Solar/Wind Helper
0.137
3146516WINFALL
Solar/Wind Helper
0.137
316431W1029_GEN1
Solar/Wind Helper
0.533
316433W1029_GEN2
Solar/Wind Helper
0.533
3151391GASTONA
50/50
1.028
3151411GASTONB
50/50
1.028
3151261ROARAP2
50/50
0.253
3151591KERR 2
50/50
0.163
316365GEN2_N
Solar/Wind Harmer
0.795
3145796HORNRTN
Solar/Wind Harmer
1.373
3145796HORNRTN
Solar/Wind Harmer
0.343
313506AB2-031 GEN
Solar/Wind Harmer
0.757
315724AD1-057 GEN
Solar/Wind Harmer
0.841
3147043LAWRENC
Solar/Wind Harmer
0.13
961601AG1-000A GEN
Solar/Wind Harmer
8.866
971623AH1-311 GEN
Solar/Wind Harmer
0.235
3145543BTLEBRO
Solar/Wind Harmer
0.115
3145543BTLEBRO
Solar/Wind Harmer
0.115
3138543CONSLDL
Solar/Wind Harmer
0.074
3146233WITAKRS
Solar/Wind Harmer
0.564
3146233WITAKRS
Solar/Wind Harmer
0.076
316327AA2-057 GEN
Solar/Wind Harmer
0.166
316131AB2-060 GEN
Solar/Wind Harmer
0.228
964241AG1-285 GEN
Solar/Wind Harmer
4.537
316210AC1-098 GEN
Solar/Wind Harmer
0.629
315785AD2-033 C
Solar/Wind Harmer
0.494
970257AG2-171 GEN
Solar/Wind Harmer
1.858
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3142666NORTHAMPTON
Solar/Wind Helper
1.362
3156021HOLLOMANSOL
Solar/Wind Helper
3.177
3146206CASHIE
Solar/Wind Helper
0.33
315737AD1-076 GEN
Solar/Wind Helper
2.631
315614AA2-178 GEN
Solar/Wind Helper
1.411
3145963POPLR C
Solar/Wind Helper
0.205
3146376EDENTON
Solar/Wind Helper
0.19
316463AE2-346 GEN
Solar/Wind Helper
0.165
316140AB2-099
Solar/Wind Helper
0.069
3146626S HERTFORD
Solar/Wind Helper
0.15
3145933PARMELE
Solar/Wind Helper
0.149
3146516WINFALL
Solar/Wind Helper
0.137
316435W1029_GEN3
Solar/Wind Helper
0.533
3145746EVERETS
Solar/Wind Helper
0.123
3145746EVERETS
Solar/Wind Helper
0.123
3146173TUNIS
Solar/Wind Helper
0.115
3145746EVERETS
Solar/Wind Helper
0.123
3145746EVERETS
Solar/Wind Helper
0.123
3145746EVERETS
Solar/Wind Helper
0.123
3145176PASQUOTANK
Solar/Wind Helper
0.075
316321Z2-027
Solar/Wind Helper
0.183
3146486SUNBURY
Solar/Wind Helper
0.117
3146486SUNBURY
Solar/Wind Helper
0.117
313526AB2-022
Solar/Wind Helper
0.17
3146173TUNIS
Solar/Wind Helper
0.115
3146173TUNIS
Solar/Wind Helper
0.115
3146386ELIZ CT
Solar/Wind Helper
0.112
3145746EVERETS
Solar/Wind Helper
0.123
3145746EVERETS
Solar/Wind Helper
0.123
3146173TUNIS
Solar/Wind Helper
0.115
316320Y1-086
Solar/Wind Helper
0.05
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.064
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.06
MECLTFEXP_MEC->PJM
CLTF
0.603
SIGELTFEXP_SIGE->PJM
CLTF
0.018
CPLELTFEXP_CPLE->PJM
CLTF
1.802
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.398
LAGNLTFEXP_LAGN->PJM
CLTF
1.198
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.764
TVALTFEXP_TVA->PJM
CLTF
0.599
NYPJM->LTFIMP_NY
CLTF
0.205
LGEELTFEXP_LGEE->PJM
CLTF
0.22
WECLTFEXP_WEC->PJM
CLTF
0.115

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:145.18 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1428.84
MW Contribution:1.57
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.337
3151411GASTONB
50/50
0.337
3147043LAWRENC
50/50
1.178
315243AE2-183_GT3
50/50
1.956
3151051BRUNSWICKS1
50/50
3.187
3151021BRUNSWICKG1
50/50
1.536
971451AH1-221 GEN
50/50
4.664
3151261ROARAP2
50/50
0.136
3151531CLOVER1
50/50
2.018
3151391GASTONA
50/50
0.337
3151411GASTONB
50/50
0.337
3151031BRUNSWICKG2
50/50
1.536
3151261ROARAP2
50/50
0.133
970413AG2-270 GEN
50/50
8.806
3151591KERR 2
50/50
0.187
316365GEN2_N
Solar/Wind Harmer
0.354
313506AB2-031 GEN
Solar/Wind Harmer
0.385
3147043LAWRENC
Solar/Wind Harmer
0.074
3145796HORNRTN
Solar/Wind Harmer
0.481
3145796HORNRTN
Solar/Wind Harmer
0.12
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
970917AG2-570 GEN
Solar/Wind Harmer
9.95
315724AD1-057 GEN
Solar/Wind Harmer
0.4
316210AC1-098 GEN
Solar/Wind Harmer
0.901
316327AA2-057 GEN
Solar/Wind Harmer
0.146
3146233WITAKRS
Solar/Wind Harmer
0.48
3146233WITAKRS
Solar/Wind Harmer
0.065
3138543CONSLDL
Solar/Wind Harmer
0.063
961601AG1-000A GEN
Solar/Wind Harmer
6.766
970533AG2-339 GEN
50/50
10.894
970531AG2-338 GEN
50/50
4.358
3151361ROSEMG1
50/50
0.433
3151371ROSEMS1
50/50
0.268
3151381ROSEMG2
50/50
0.203
315242AE2-183_GT2
50/50
1.956
315241AE2-183_GT1
50/50
1.944
972185AH1-677 GEN
50/50
7.053
3151041BRUNSWICKG3
50/50
1.536
972187AH1-678 GEN
50/50
3.524
970535AG2-341 GEN
50/50
1.57
3152661PLYWOOD A
50/50
0.18
3144356SAPONY
Solar/Wind Harmer
1.857
316181AB2-040 GEN
Solar/Wind Harmer
0.181
3145796HORNRTN
Solar/Wind Harmer
0.361
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
970933AG2-581 GEN
Solar/Wind Harmer
8.936
3145593CAROLNA
Solar/Wind Harmer
0.109
3145593CAROLNA
Solar/Wind Harmer
0.109
966811AG1-552 GEN
Solar/Wind Harmer
1.182
3145593CAROLNA
Solar/Wind Harmer
0.136
3145783HORNRTN
Solar/Wind Harmer
1.911
3145783HORNRTN
Solar/Wind Harmer
1.529
3145783HORNRTN
Solar/Wind Harmer
0.478
3145783HORNRTN
Solar/Wind Harmer
0.191
316426AA2-053 GEN
Solar/Wind Harmer
0.356
316274AC1-208 GEN
Solar/Wind Harmer
0.518
970099AG2-077 GEN
Solar/Wind Harmer
10.582
961601AG1-000A GEN
Solar/Wind Harmer
1.691
316263AC1-034 GEN
Solar/Wind Harmer
3.592
3145493TOT1
Solar/Wind Harmer
0.212
3145453TOT5
Solar/Wind Harmer
0.127
3145603CNETO
Solar/Wind Harmer
0.085
939181AE1-148 GEN
Solar/Wind Harmer
4.3
3146173TUNIS
Solar/Wind Harmer
0.088
3146173TUNIS
Solar/Wind Harmer
0.088
3145893MURPHYS
Solar/Wind Harmer
0.583
3145893MURPHYS
Solar/Wind Harmer
0.157
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3145933PARMELE
Solar/Wind Harmer
0.168
3145933PARMELE
Solar/Wind Harmer
0.084
962561AG1-105 GEN
Solar/Wind Harmer
3.947
964791AG1-342 GEN
Solar/Wind Harmer
1.566
3146843MT LREL
Solar/Wind Harmer
0.081
3146843MT LREL
Solar/Wind Harmer
0.081
316065AD1-022 GEN
Solar/Wind Harmer
3.64
970323AG2-213 GEN
Solar/Wind Harmer
3.221
315779AE2-040
50/50
3.099
315244AE2-183_ST
50/50
3.382
963041AG1-153 GEN
50/50
3.109
3151281ROARAP4
50/50
0.132
3151281ROARAP4
50/50
0.123
3151541CLOVER2
50/50
2.008
3151611KERR 4
50/50
0.187
3151621KERR 5
50/50
0.187
3151631KERR 6
50/50
0.187
3151641KERR 7
50/50
0.187
316315AB2-025 C
Solar/Wind Harmer
0.179
315814AE2-033 C
Solar/Wind Harmer
17.298
316087AB2-174 GEN
Solar/Wind Harmer
0.004
315652AC1-086 GEN
Solar/Wind Harmer
13.694
3151601KERR 3
50/50
0.187
3151581KERR 1
50/50
0.067
316023GEN1_S
Solar/Wind Harmer
0.354
960081AF2-299 GEN
Solar/Wind Harmer
1.332
971795AH1-408 GEN
Solar/Wind Harmer
8.516
316011AB1-132 GEN
Solar/Wind Harmer
2.263
962571AG1-106 GEN
Solar/Wind Harmer
1.771
3145796HORNRTN
Solar/Wind Harmer
0.397
3145796HORNRTN
Solar/Wind Harmer
0.12
940641AE2-051 GEN
Solar/Wind Harmer
9.263
970919AG2-571 GEN
Solar/Wind Harmer
3.98
970087AG2-069 GEN
Solar/Wind Harmer
8.913
3145783HORNRTN
Solar/Wind Harmer
0.107
315722AD1-056 GEN
Solar/Wind Harmer
0.674
316190AA2-174 GEN
Solar/Wind Harmer
0
939411AE1-173 GEN
Solar/Wind Harmer
42.901
957481AF2-042 GEN
Solar/Wind Harmer
26.456
316212AC1-099_GEN
Solar/Wind Harmer
0.502
316129AC1-054 GEN
Solar/Wind Harmer
0.364
971065AG2-659 GEN
Solar/Wind Harmer
4.087
3146233WITAKRS
Solar/Wind Harmer
0.38
3146263WOODLND
Solar/Wind Harmer
0.095
316359AB2-059 GEN
Solar/Wind Harmer
0.34
316049AB1-081 GEN
Solar/Wind Harmer
0.541
3142053HEARTS
Solar/Wind Harmer
0.166
3145543BTLEBRO
Solar/Wind Harmer
0.094
3145543BTLEBRO
Solar/Wind Harmer
0.075
3145823KELFORD
Solar/Wind Harmer
0.092
315693AD1-088 GEN
Solar/Wind Harmer
4.418
961671AG1-007 GEN
Solar/Wind Harmer
0.014
3146083TARBORO
Solar/Wind Harmer
0.092
3145493TOT1
Solar/Wind Harmer
0.407
962491AG1-098 GEN
Solar/Wind Harmer
5.172
3145683EARLEYS
Solar/Wind Harmer
0.09
316494AC1-189 GEN
Solar/Wind Harmer
0.3
315687AD1-152 GEN
Solar/Wind Harmer
0.003
3146173TUNIS
Solar/Wind Harmer
0.088
3145893MURPHYS
Solar/Wind Harmer
0.348
3145893MURPHYS
Solar/Wind Harmer
0.387
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
3146293MARTNCO
Solar/Wind Harmer
0.078
970401AG2-262 GEN
Solar/Wind Harmer
0.478
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3146206CASHIE
Solar/Wind Harmer
0.08
971547AH1-271 GEN
Solar/Wind Harmer
1.719
3145963POPLR C
Solar/Wind Harmer
0.08
316003AC1-222 GEN
Solar/Wind Harmer
0.002
3145663CRESWEL
Solar/Wind Harmer
0.201
971163AH1-040 GEN
Solar/Wind Harmer
5.738
970685AG2-442 GEN
Solar/Wind Harmer
5.289
3130156CHOWAN
Solar/Wind Harmer
0.066
963171AG1-166 GEN
Solar/Wind Harmer
0.354
971563AH1-280 GEN
Solar/Wind Harmer
0.708
3144293JTRSVLE
Adder
0.211
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
316294AC1-161 GEN
Solar/Wind Harmer
1.066
3146516WINFALL
Solar/Wind Harmer
0.194
3146516WINFALL
Solar/Wind Harmer
0.06
944591AF1-124 GEN
Solar/Wind Harmer
12.705
3142543TWELFTH
Solar/Wind Helper
0.024
316458AB2-190 GEN2
Solar/Wind Helper
0.895
3142433PROV 92
Solar/Wind Helper
0.616
3143526WINTERP
Solar/Wind Helper
0.72
3143226MDLTHAN
Solar/Wind Helper
0.125
3142416OLDCHRC
Solar/Wind Helper
0.323
3142416OLDCHRC
Solar/Wind Helper
0.124
941031AE2-094 GEN
Solar/Wind Harmer
22.572
944011AF1-069 GEN
Solar/Wind Harmer
7.375
3145796HORNRTN
Solar/Wind Harmer
0.385
3145796HORNRTN
Solar/Wind Harmer
0.048
970673AG2-436 GEN
Solar/Wind Harmer
25.561
970673AG2-436 GEN
Solar/Wind Harmer
17.041
971967AH1-528 GEN
Solar/Wind Harmer
18.68
3137643SOCKMAN
Solar/Wind Harmer
0.464
970085AG2-068 GEN
Solar/Wind Harmer
5.942
970581AG2-369 GEN
Solar/Wind Harmer
5.11
315607AA1-063A GEN
Solar/Wind Harmer
0.204
3146043SEABORD
Solar/Wind Harmer
0.098
970831AG2-522 GEN
Solar/Wind Harmer
4.182
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.379
3145573BETHELC
Solar/Wind Harmer
0.092
3145573BETHELC
Solar/Wind Harmer
0.092
316420AA1-050 GEN
Solar/Wind Harmer
0.003
3145683EARLEYS
Solar/Wind Harmer
0.179
3145683EARLEYS
Solar/Wind Harmer
0.09
3145683EARLEYS
Solar/Wind Harmer
0.09
3145513AHOSKIE
Solar/Wind Harmer
0.186
3145513AHOSKIE
Solar/Wind Harmer
0.089
957861AF2-080 GEN
Solar/Wind Harmer
3.828
3145893MURPHYS
Solar/Wind Harmer
0.235
3145893MURPHYS
Solar/Wind Harmer
0.087
965291AG1-394 GEN
Solar/Wind Harmer
0.382
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316005AA1-067
Solar/Wind Harmer
0.092
3145746EVERETS
Solar/Wind Harmer
0.34
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
970181AG2-120 GEN
Solar/Wind Harmer
1.064
3146206CASHIE
Solar/Wind Harmer
0.08
970601AG2-382 GEN
Solar/Wind Harmer
3.008
316118AC1-105 GEN
Solar/Wind Harmer
0.206
3147173SINAI
Solar/Wind Harmer
0.078
3147243WELCO
Solar/Wind Harmer
0.049
315732AD1-074 GEN1
Solar/Wind Harmer
0.439
315733AD1-074 GEN2
Solar/Wind Harmer
0.439
315735AD1-075 GEN1
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
1.275
3130546PLYMOUTH
Solar/Wind Harmer
0.076
3144303KENBRDG
Solar/Wind Harmer
0.06
3143316POE
Solar/Wind Harmer
0.287
315816AE2-034 GEN
Solar/Wind Harmer
0.308
970683AG2-441 GEN
Solar/Wind Harmer
4.722
970681AG2-440 GEN
Solar/Wind Harmer
3.778
3130156CHOWAN
Solar/Wind Harmer
0.066
3130156CHOWAN
Solar/Wind Harmer
0.066
946301AF1-294 GEN
Solar/Wind Harmer
1.311
961791AG1-021 GEN
Solar/Wind Harmer
0.638
970865AG2-541 GEN
Solar/Wind Harmer
2.298
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
315657AE1-056 GEN
Solar/Wind Harmer
2.185
316123AC1-075 GEN
Solar/Wind Harmer
0.08
970165AG2-112 GEN
Solar/Wind Harmer
0.473
970163AG2-111 GEN
Solar/Wind Harmer
0.451
3145176PASQUOTANK
Solar/Wind Harmer
0.036
316321Z2-027
Solar/Wind Harmer
0.011
3146396TANGLEW
Solar/Wind Harmer
0.161
313526AB2-022
Solar/Wind Harmer
0.031
3146486SUNBURY
Solar/Wind Harmer
0.057
3146486SUNBURY
Solar/Wind Harmer
0.057
316132AB2-190 GEN1
Solar/Wind Helper
0.895
316233AE1-074 FULL
Solar/Wind Helper
0.212
316312AB1-027
Solar/Wind Helper
0.237
3146263WOODLND
Solar/Wind Harmer
0.095
971623AH1-311 GEN
Solar/Wind Harmer
0.189
3145543BTLEBRO
Solar/Wind Harmer
0.094
3145543BTLEBRO
Solar/Wind Harmer
0.094
316478AD1-087 GEN
Solar/Wind Harmer
0.329
316486AD2-202 GEN
Solar/Wind Harmer
0.097
316317KELFORD C
Solar/Wind Harmer
0.009
3145823KELFORD
Solar/Wind Harmer
0.092
3146073TAR RVR
Solar/Wind Harmer
0.092
3146083TARBORO
Solar/Wind Harmer
0.092
316463AE2-346 GEN
Solar/Wind Harmer
0.076
316140AB2-099
Solar/Wind Harmer
0.032
962331AG1-082 GEN
Solar/Wind Harmer
0.95
3146173TUNIS
Solar/Wind Harmer
0.088
957521AF2-046 GEN
Solar/Wind Harmer
6.513
961681AG1-008 GEN
Solar/Wind Harmer
6.513
3145893MURPHYS
Solar/Wind Harmer
0.146
3145893MURPHYS
Solar/Wind Harmer
0.087
3156021HOLLOMANSOL
Solar/Wind Harmer
0.393
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
316131AB2-060 GEN
Solar/Wind Harmer
0.268
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3145933PARMELE
Solar/Wind Harmer
0.084
966801AG1-551 GEN
Solar/Wind Harmer
0.976
964241AG1-285 GEN
Solar/Wind Harmer
5.485
3146206CASHIE
Solar/Wind Harmer
0.08
3145963POPLR C
Solar/Wind Harmer
0.08
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.344
315785AD2-033 C
Solar/Wind Harmer
0.629
315737AD1-076 GEN
Solar/Wind Harmer
0.983
971157AH1-035 GEN
Solar/Wind Harmer
0.908
970257AG2-171 GEN
Solar/Wind Harmer
2.416
959311AF2-222 GEN
Solar/Wind Harmer
6.592
316283AC2-100 C
Solar/Wind Harmer
0.142
315614AA2-178 GEN
Solar/Wind Harmer
0.41
971683AH1-343 GEN
Solar/Wind Harmer
2.584
3146376EDENTON
Solar/Wind Harmer
0.067
963181AG1-167 GEN
Solar/Wind Harmer
0.266
3144293JTRSVLE
Adder
0.211
970909AG2-566 GEN
Solar/Wind Harmer
0.692
3147133PAMPLIN
Solar/Wind Harmer
0.199
971193AH1-056 GEN
Solar/Wind Harmer
3.857
315773AC2-141 GEN
Solar/Wind Harmer
2.248
3146626S HERTFORD
Solar/Wind Harmer
0.061
3145273HOLLAND
Solar/Wind Harmer
0.046
3146516WINFALL
Solar/Wind Harmer
0.06
316435W1029_GEN3
Solar/Wind Harmer
0
316320Y1-086
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
12.66
944601AF1-125 GEN
Solar/Wind Harmer
12.465
315839AE2-212 C
Solar/Wind Helper
0.986
316473AC1-191 GEN
Solar/Wind Helper
0.925
3142946ENON
Solar/Wind Helper
0.049
971775AH1-396 GEN
Solar/Wind Harmer
0.121
316034AC1-036 C
Solar/Wind Harmer
0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.303
971741AH1-377 GEN
Solar/Wind Harmer
7.057
3146376EDENTON
Solar/Wind Harmer
0.296
3146376EDENTON
Solar/Wind Harmer
0.296
958211AF2-115 GEN
Solar/Wind Harmer
0.797
963191AG1-168 GEN
Solar/Wind Harmer
0.266
3144293JTRSVLE
Adder
0.211
3144293JTRSVLE
Adder
0.178
315742AE1-103 GEN
Solar/Wind Harmer
0.001
970301AG2-198 GEN
Solar/Wind Harmer
2.77
3147133PAMPLIN
Solar/Wind Harmer
0.063
3147133PAMPLIN
Solar/Wind Harmer
0.051
3146626S HERTFORD
Solar/Wind Harmer
0.061
3146626S HERTFORD
Solar/Wind Harmer
0.061
3146516WINFALL
Solar/Wind Harmer
0.06
3146516WINFALL
Solar/Wind Harmer
0.06
3146516WINFALL
Solar/Wind Harmer
0.06
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146386ELIZ CT
Solar/Wind Harmer
0.057
316240AF1-291 C
Solar/Wind Helper
0.411
966871AG1-558 GEN
Solar/Wind Helper
0.204
3142946ENON
Solar/Wind Helper
0.015
3143526WINTERP
Solar/Wind Helper
0.72
316468AD1-105 GEN
Solar/Wind Helper
0.653
316075AC2-137 C
Solar/Wind Helper
0.178
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.11
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.461
MECLTFEXP_MEC->PJM
CLTF
1.839
SIGELTFEXP_SIGE->PJM
CLTF
0.055
CPLELTFEXP_CPLE->PJM
CLTF
5.631
CBM West 2LTFEXP_CBM-W2->PJM
CBM
19.951
LAGNLTFEXP_LAGN->PJM
CLTF
3.79
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.991
TVALTFEXP_TVA->PJM
CLTF
1.888
NYPJM->LTFIMP_NY
CLTF
0.691
LGEELTFEXP_LGEE->PJM
CLTF
0.659
WECLTFEXP_WEC->PJM
CLTF
0.343

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2002_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.21 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1192.96
MW Contribution:1.33
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.32
3151411GASTONB
50/50
0.32
3147043LAWRENC
50/50
1.13
3151261ROARAP2
50/50
0.121
315243AE2-183_GT3
50/50
1.518
3151051BRUNSWICKS1
50/50
2.476
3151021BRUNSWICKG1
50/50
1.193
971451AH1-221 GEN
50/50
3.623
3151601KERR 3
50/50
0.157
3151581KERR 1
50/50
0.056
3151531CLOVER1
50/50
1.596
316023GEN1_S
Solar/Wind Harmer
0.362
960081AF2-299 GEN
Solar/Wind Harmer
1.316
971795AH1-408 GEN
Solar/Wind Harmer
8.254
316011AB1-132 GEN
Solar/Wind Harmer
2.152
962571AG1-106 GEN
Solar/Wind Harmer
1.684
3145796HORNRTN
Solar/Wind Harmer
0.374
3145796HORNRTN
Solar/Wind Harmer
0.113
315722AD1-056 GEN
Solar/Wind Harmer
0.612
3145783HORNRTN
Solar/Wind Harmer
0.096
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
3.101
970087AG2-069 GEN
Solar/Wind Harmer
6.946
940641AE2-051 GEN
Solar/Wind Harmer
6.931
316129AC1-054 GEN
Solar/Wind Harmer
0.314
316212AC1-099_GEN
Solar/Wind Harmer
0.43
3146233WITAKRS
Solar/Wind Harmer
0.33
971065AG2-659 GEN
Solar/Wind Harmer
3.51
316359AB2-059 GEN
Solar/Wind Harmer
0.295
316049AB1-081 GEN
Solar/Wind Harmer
0.471
3142053HEARTS
Solar/Wind Harmer
0.145
3145543BTLEBRO
Solar/Wind Harmer
0.082
3145543BTLEBRO
Solar/Wind Harmer
0.066
3146263WOODLND
Solar/Wind Harmer
0.078
957481AF2-042 GEN
Solar/Wind Harmer
20.812
961671AG1-007 GEN
Solar/Wind Harmer
0.012
3146083TARBORO
Solar/Wind Harmer
0.078
3145493TOT1
Solar/Wind Harmer
0.346
3145823KELFORD
Solar/Wind Harmer
0.075
316494AC1-189 GEN
Solar/Wind Harmer
0.249
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
3.49
962491AG1-098 GEN
Solar/Wind Harmer
4.086
3145683EARLEYS
Solar/Wind Harmer
0.071
315687AD1-152 GEN
Solar/Wind Harmer
0.002
939411AE1-173 GEN
Solar/Wind Harmer
30.084
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.068
970401AG2-262 GEN
Solar/Wind Harmer
0.397
3146293MARTNCO
Solar/Wind Harmer
0.061
3145893MURPHYS
Solar/Wind Harmer
0.259
3145893MURPHYS
Solar/Wind Harmer
0.288
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145963POPLR C
Solar/Wind Harmer
0.06
316003AC1-222 GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
4.444
315779AE2-040
50/50
3.401
3151281ROARAP4
50/50
0.118
3151281ROARAP4
50/50
0.11
315244AE2-183_ST
50/50
2.625
963041AG1-153 GEN
50/50
2.415
3151611KERR 4
50/50
0.157
3151621KERR 5
50/50
0.157
3151631KERR 6
50/50
0.157
3151641KERR 7
50/50
0.157
3151541CLOVER2
50/50
1.589
316315AB2-025 C
Solar/Wind Harmer
0.197
315814AE2-033 C
Solar/Wind Harmer
18.936
316087AB2-174 GEN
Solar/Wind Harmer
0.004
315652AC1-086 GEN
Solar/Wind Harmer
13.019
3145796HORNRTN
Solar/Wind Harmer
0.362
3145796HORNRTN
Solar/Wind Harmer
0.045
3137643SOCKMAN
Solar/Wind Harmer
0.427
941031AE2-094 GEN
Solar/Wind Harmer
17.475
944011AF1-069 GEN
Solar/Wind Harmer
5.71
970673AG2-436 GEN
Solar/Wind Harmer
19.819
970673AG2-436 GEN
Solar/Wind Harmer
13.213
971967AH1-528 GEN
Solar/Wind Harmer
14.51
970085AG2-068 GEN
Solar/Wind Harmer
4.631
970581AG2-369 GEN
Solar/Wind Harmer
3.982
970831AG2-522 GEN
Solar/Wind Harmer
3.621
315607AA1-063A GEN
Solar/Wind Harmer
0.17
316319Z2-044 C
Solar/Wind Harmer
0
3146043SEABORD
Solar/Wind Harmer
0.081
3146033SCOT NK
Solar/Wind Harmer
0.318
3145573BETHELC
Solar/Wind Harmer
0.078
3145573BETHELC
Solar/Wind Harmer
0.078
316420AA1-050 GEN
Solar/Wind Harmer
0.003
957861AF2-080 GEN
Solar/Wind Harmer
3.178
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3145683EARLEYS
Solar/Wind Harmer
0.142
3145683EARLEYS
Solar/Wind Harmer
0.071
3145683EARLEYS
Solar/Wind Harmer
0.071
3145513AHOSKIE
Solar/Wind Harmer
0.145
3145513AHOSKIE
Solar/Wind Harmer
0.07
316005AA1-067
Solar/Wind Harmer
0.074
3145746EVERETS
Solar/Wind Harmer
0.274
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
970181AG2-120 GEN
Solar/Wind Harmer
0.856
316118AC1-105 GEN
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
0.175
3145893MURPHYS
Solar/Wind Harmer
0.065
971443AH1-215 GEN
Solar/Wind Harmer
1.078
3144303KENBRDG
Solar/Wind Harmer
0.051
3147173SINAI
Solar/Wind Harmer
0.064
3147243WELCO
Solar/Wind Harmer
0.04
965291AG1-394 GEN
Solar/Wind Harmer
0.275
970683AG2-441 GEN
Solar/Wind Harmer
3.967
970681AG2-440 GEN
Solar/Wind Harmer
3.174
3146206CASHIE
Solar/Wind Harmer
0.059
970601AG2-382 GEN
Solar/Wind Harmer
2.2
3143316POE
Solar/Wind Helper
1.93
316132AB2-190 GEN1
Solar/Wind Helper
1.544
316369SG1_INVT
Solar/Wind Helper
1.002
316312AB1-027
Solar/Wind Helper
0.328
3143873LANEXA
Solar/Wind Helper
0.095
316233AE1-074 FULL
Solar/Wind Helper
0.214
3146206CASHIE
Solar/Wind Harmer
0.059
971547AH1-271 GEN
Solar/Wind Harmer
1.257
3142543TWELFTH
Solar/Wind Helper
0.031
316458AB2-190 GEN2
Solar/Wind Helper
1.544
316381AD1-082 GEN
Solar/Wind Helper
1.346
3142433PROV 92
Solar/Wind Helper
0.863
3142416OLDCHRC
Solar/Wind Helper
0.448
3142416OLDCHRC
Solar/Wind Helper
0.172
3143526WINTERP
Solar/Wind Helper
0.727
3141766HARMONY
Solar/Wind Helper
0.024
964211AG1-282 GEN
Solar/Wind Helper
0.157
3141726DUNNSVL
Solar/Wind Helper
0.465
3138133OCRAN
Solar/Wind Helper
0.068
315662AE1-191 GEN
Solar/Wind Helper
0.666
315666AE1-190 GEN
Solar/Wind Helper
0.167
316059AD1-063 C
Solar/Wind Helper
0.122
3141813NORNECK
Solar/Wind Helper
0.113
3141783LANCAST
Solar/Wind Helper
0.068
3141783LANCAST
Solar/Wind Helper
0.045
3141913WHIT STONE
Solar/Wind Helper
0.113
3138133OCRAN
Solar/Wind Helper
0.034
957601AF2-054 GEN
Solar/Wind Helper
0.152
3141873WAN 176
Solar/Wind Helper
0.023
3151391GASTONA
50/50
0.32
3151411GASTONB
50/50
0.32
3151261ROARAP2
50/50
0.119
3151031BRUNSWICKG2
50/50
1.193
3151591KERR 2
50/50
0.157
970413AG2-270 GEN
50/50
6.966
316365GEN2_N
Solar/Wind Harmer
0.362
313506AB2-031 GEN
Solar/Wind Harmer
0.366
3147043LAWRENC
Solar/Wind Harmer
0.071
3145796HORNRTN
Solar/Wind Harmer
0.453
3145796HORNRTN
Solar/Wind Harmer
0.113
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
315724AD1-057 GEN
Solar/Wind Harmer
0.363
970917AG2-570 GEN
Solar/Wind Harmer
7.751
316327AA2-057 GEN
Solar/Wind Harmer
0.127
961601AG1-000A GEN
Solar/Wind Harmer
5.909
316210AC1-098 GEN
Solar/Wind Harmer
0.77
3146233WITAKRS
Solar/Wind Harmer
0.417
3146233WITAKRS
Solar/Wind Harmer
0.056
3138543CONSLDL
Solar/Wind Harmer
0.055
971623AH1-311 GEN
Solar/Wind Harmer
0.164
3145543BTLEBRO
Solar/Wind Harmer
0.082
3145543BTLEBRO
Solar/Wind Harmer
0.082
3146263WOODLND
Solar/Wind Harmer
0.078
3146073TAR RVR
Solar/Wind Harmer
0.078
3146083TARBORO
Solar/Wind Harmer
0.078
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.075
316478AD1-087 GEN
Solar/Wind Harmer
0.26
316486AD2-202 GEN
Solar/Wind Harmer
0.076
316131AB2-060 GEN
Solar/Wind Harmer
0.229
964241AG1-285 GEN
Solar/Wind Harmer
4.665
316463AE2-346 GEN
Solar/Wind Harmer
0.06
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.742
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.068
3156021HOLLOMANSOL
Solar/Wind Harmer
0.305
3145933PARMELE
Solar/Wind Harmer
0.066
966801AG1-551 GEN
Solar/Wind Harmer
0.769
957521AF2-046 GEN
Solar/Wind Harmer
4.888
961681AG1-008 GEN
Solar/Wind Harmer
4.888
315785AD2-033 C
Solar/Wind Harmer
0.532
3145893MURPHYS
Solar/Wind Harmer
0.108
3145893MURPHYS
Solar/Wind Harmer
0.065
970257AG2-171 GEN
Solar/Wind Harmer
2.041
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.715
959311AF2-222 GEN
Solar/Wind Harmer
5.561
3145963POPLR C
Solar/Wind Harmer
0.06
3156081AA2-088 GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.059
316283AC2-100 C
Solar/Wind Harmer
0.115
971683AH1-343 GEN
Solar/Wind Harmer
2.095
315839AE2-212 C
Solar/Wind Helper
1.113
3142946ENON
Solar/Wind Helper
0.074
316473AC1-191 GEN
Solar/Wind Helper
1.189
316280AD1-041 GEN
Solar/Wind Helper
0.416
316404AE1-155 C
Solar/Wind Helper
0.956
316484AD2-074 GEN
Solar/Wind Helper
0.219
316156AD2-030 GEN
Solar/Wind Helper
0.171
3151361ROSEMG1
50/50
0.408
3151371ROSEMS1
50/50
0.253
3151381ROSEMG2
50/50
0.191
970533AG2-339 GEN
50/50
8.434
970531AG2-338 GEN
50/50
3.373
315242AE2-183_GT2
50/50
1.518
315241AE2-183_GT1
50/50
1.509
972185AH1-677 GEN
50/50
5.473
3151041BRUNSWICKG3
50/50
1.193
972187AH1-678 GEN
50/50
2.737
970535AG2-341 GEN
50/50
1.329
3152661PLYWOOD A
50/50
0.148
3144356SAPONY
Solar/Wind Harmer
2.038
316181AB2-040 GEN
Solar/Wind Harmer
0.172
3145796HORNRTN
Solar/Wind Harmer
0.34
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
3142666NORTHAMPTON
Solar/Wind Harmer
0.067
3145593CAROLNA
Solar/Wind Harmer
0.097
3145593CAROLNA
Solar/Wind Harmer
0.097
966811AG1-552 GEN
Solar/Wind Harmer
1.057
3145593CAROLNA
Solar/Wind Harmer
0.121
3145783HORNRTN
Solar/Wind Harmer
1.703
3145783HORNRTN
Solar/Wind Harmer
1.362
3145783HORNRTN
Solar/Wind Harmer
0.426
3145783HORNRTN
Solar/Wind Harmer
0.17
316426AA2-053 GEN
Solar/Wind Harmer
0.313
970933AG2-581 GEN
Solar/Wind Harmer
6.963
316274AC1-208 GEN
Solar/Wind Harmer
0.45
961601AG1-000A GEN
Solar/Wind Harmer
1.477
316263AC1-034 GEN
Solar/Wind Harmer
3.125
970099AG2-077 GEN
Solar/Wind Harmer
8.325
3145493TOT1
Solar/Wind Harmer
0.181
3145453TOT5
Solar/Wind Harmer
0.108
3145603CNETO
Solar/Wind Harmer
0.072
939181AE1-148 GEN
Solar/Wind Harmer
3.627
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.291
3146173TUNIS
Solar/Wind Harmer
0.068
3146173TUNIS
Solar/Wind Harmer
0.068
964791AG1-342 GEN
Solar/Wind Harmer
1.3
3146843MT LREL
Solar/Wind Harmer
0.068
3146843MT LREL
Solar/Wind Harmer
0.068
3145933PARMELE
Solar/Wind Harmer
0.132
3145933PARMELE
Solar/Wind Harmer
0.066
3145893MURPHYS
Solar/Wind Harmer
0.433
3145893MURPHYS
Solar/Wind Harmer
0.116
970323AG2-213 GEN
Solar/Wind Harmer
2.721
971775AH1-396 GEN
Solar/Wind Harmer
0.102
316034AC1-036 C
Solar/Wind Harmer
0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.245
316065AD1-022 GEN
Solar/Wind Harmer
2.617
971741AH1-377 GEN
Solar/Wind Harmer
5.589
316240AF1-291 C
Solar/Wind Helper
0.691
3142946ENON
Solar/Wind Helper
0.022
316033AB2-134 GEN
Solar/Wind Helper
0.717
315697AD1-025 GEN
Solar/Wind Helper
2.382
966871AG1-558 GEN
Solar/Wind Helper
0.262
316075AC2-137 C
Solar/Wind Helper
0.263
316468AD1-105 GEN
Solar/Wind Helper
0.815
3143526WINTERP
Solar/Wind Helper
0.727
316077AC2-138 C
Solar/Wind Helper
0.107
316487AF1-042 GEN
Solar/Wind Helper
0.114
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.423
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.312
MECLTFEXP_MEC->PJM
CLTF
1.548
SIGELTFEXP_SIGE->PJM
CLTF
0.046
CPLELTFEXP_CPLE->PJM
CLTF
4.572
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.518
LAGNLTFEXP_LAGN->PJM
CLTF
3.11
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.716
TVALTFEXP_TVA->PJM
CLTF
1.547
NYPJM->LTFIMP_NY
CLTF
0.457
LGEELTFEXP_LGEE->PJM
CLTF
0.557
WECLTFEXP_WEC->PJM
CLTF
0.293

Details for 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6POE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 249_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.58 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:845.48
MW Contribution:1.04
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.249
3151411GASTONB
50/50
0.249
3151261ROARAP2
50/50
0.09
3151031BRUNSWICKG2
50/50
0.945
3151591KERR 2
50/50
0.122
970413AG2-270 GEN
50/50
5.504
316365GEN2_N
Solar/Wind Harmer
0.287
3147043LAWRENC
Solar/Wind Harmer
0.056
313506AB2-031 GEN
Solar/Wind Harmer
0.284
3145796HORNRTN
Solar/Wind Harmer
0.352
3145796HORNRTN
Solar/Wind Harmer
0.088
3142666NORTHAMPTON
Solar/Wind Harmer
0.086
315724AD1-057 GEN
Solar/Wind Harmer
0.281
970917AG2-570 GEN
Solar/Wind Harmer
6.136
961601AG1-000A GEN
Solar/Wind Harmer
4.539
316327AA2-057 GEN
Solar/Wind Harmer
0.096
3146233WITAKRS
Solar/Wind Harmer
0.318
3146233WITAKRS
Solar/Wind Harmer
0.043
3138543CONSLDL
Solar/Wind Harmer
0.042
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
316210AC1-098 GEN
Solar/Wind Harmer
0.577
3147043LAWRENC
50/50
0.889
3151391GASTONA
50/50
0.249
3151411GASTONB
50/50
0.249
3151261ROARAP2
50/50
0.092
315243AE2-183_GT3
50/50
1.203
3151051BRUNSWICKS1
50/50
1.962
3151021BRUNSWICKG1
50/50
0.945
971451AH1-221 GEN
50/50
2.871
3151601KERR 3
50/50
0.122
3151581KERR 1
50/50
0.044
3151531CLOVER1
50/50
1.261
316023GEN1_S
Solar/Wind Harmer
0.287
960081AF2-299 GEN
Solar/Wind Harmer
1.037
971795AH1-408 GEN
Solar/Wind Harmer
6.499
316011AB1-132 GEN
Solar/Wind Harmer
1.672
962571AG1-106 GEN
Solar/Wind Harmer
1.309
3145796HORNRTN
Solar/Wind Harmer
0.29
3145796HORNRTN
Solar/Wind Harmer
0.088
315722AD1-056 GEN
Solar/Wind Harmer
0.473
3145783HORNRTN
Solar/Wind Harmer
0.072
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
2.454
970087AG2-069 GEN
Solar/Wind Harmer
5.498
940641AE2-051 GEN
Solar/Wind Harmer
5.458
316129AC1-054 GEN
Solar/Wind Harmer
0.242
971065AG2-659 GEN
Solar/Wind Harmer
2.706
3146233WITAKRS
Solar/Wind Harmer
0.252
316359AB2-059 GEN
Solar/Wind Harmer
0.227
316049AB1-081 GEN
Solar/Wind Harmer
0.361
3142053HEARTS
Solar/Wind Harmer
0.111
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
316212AC1-099_GEN
Solar/Wind Harmer
0.322
957481AF2-042 GEN
Solar/Wind Harmer
16.463
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.059
3145493TOT1
Solar/Wind Harmer
0.263
315693AD1-088 GEN
Solar/Wind Harmer
2.76
316237AB2-079_GEN
Solar/Wind Harmer
0
3146263WOODLND
Solar/Wind Harmer
0.057
962491AG1-098 GEN
Solar/Wind Harmer
3.232
316381AD1-082 GEN
Solar/Wind Helper
2.648
316458AB2-190 GEN2
Solar/Wind Helper
1.354
3142543TWELFTH
Solar/Wind Helper
0.022
3142433PROV 92
Solar/Wind Helper
0.592
3142416OLDCHRC
Solar/Wind Helper
0.348
3142416OLDCHRC
Solar/Wind Helper
0.133
3151361ROSEMG1
50/50
0.317
3151371ROSEMS1
50/50
0.196
3151381ROSEMG2
50/50
0.148
970533AG2-339 GEN
50/50
6.689
970531AG2-338 GEN
50/50
2.675
315242AE2-183_GT2
50/50
1.203
315241AE2-183_GT1
50/50
1.196
972185AH1-677 GEN
50/50
4.338
3151041BRUNSWICKG3
50/50
0.945
972187AH1-678 GEN
50/50
2.169
970535AG2-341 GEN
50/50
1.039
3144356SAPONY
Solar/Wind Harmer
1.648
316181AB2-040 GEN
Solar/Wind Harmer
0.133
3145796HORNRTN
Solar/Wind Harmer
0.264
3142666NORTHAMPTON
Solar/Wind Harmer
0.086
3142666NORTHAMPTON
Solar/Wind Harmer
0.086
3142666NORTHAMPTON
Solar/Wind Harmer
0.086
3142666NORTHAMPTON
Solar/Wind Harmer
0.052
3145593CAROLNA
Solar/Wind Harmer
0.074
3145593CAROLNA
Solar/Wind Harmer
0.074
966811AG1-552 GEN
Solar/Wind Harmer
0.8
3145593CAROLNA
Solar/Wind Harmer
0.092
3145783HORNRTN
Solar/Wind Harmer
1.288
3145783HORNRTN
Solar/Wind Harmer
1.031
3145783HORNRTN
Solar/Wind Harmer
0.322
3145783HORNRTN
Solar/Wind Harmer
0.129
316426AA2-053 GEN
Solar/Wind Harmer
0.235
970933AG2-581 GEN
Solar/Wind Harmer
5.516
316274AC1-208 GEN
Solar/Wind Harmer
0.34
961601AG1-000A GEN
Solar/Wind Harmer
1.135
316263AC1-034 GEN
Solar/Wind Harmer
2.397
970099AG2-077 GEN
Solar/Wind Harmer
6.585
3145493TOT1
Solar/Wind Harmer
0.137
3145453TOT5
Solar/Wind Harmer
0.082
3145603CNETO
Solar/Wind Harmer
0.055
939181AE1-148 GEN
Solar/Wind Harmer
2.827
313527AB2-043 GEN
Solar/Wind Harmer
0.001
316240AF1-291 C
Solar/Wind Helper
0.668
316033AB2-134 GEN
Solar/Wind Helper
0.639
315697AD1-025 GEN
Solar/Wind Helper
2.123
3142946ENON
Solar/Wind Helper
0.018
966871AG1-558 GEN
Solar/Wind Helper
0.198
316075AC2-137 C
Solar/Wind Helper
0.206
316468AD1-105 GEN
Solar/Wind Helper
0.615
3146073TAR RVR
Solar/Wind Harmer
0.059
3146083TARBORO
Solar/Wind Harmer
0.059
316478AD1-087 GEN
Solar/Wind Harmer
0.206
316486AD2-202 GEN
Solar/Wind Harmer
0.06
316131AB2-060 GEN
Solar/Wind Harmer
0.179
3146263WOODLND
Solar/Wind Harmer
0.057
315839AE2-212 C
Solar/Wind Helper
0.548
3142946ENON
Solar/Wind Helper
0.059
316473AC1-191 GEN
Solar/Wind Helper
0.896
315779AE2-040
50/50
2.75
3151281ROARAP4
50/50
0.089
3151281ROARAP4
50/50
0.084
315244AE2-183_ST
50/50
2.08
963041AG1-153 GEN
50/50
1.914
3151611KERR 4
50/50
0.122
3151621KERR 5
50/50
0.122
3151631KERR 6
50/50
0.122
3151641KERR 7
50/50
0.122
3151541CLOVER2
50/50
1.255
316315AB2-025 C
Solar/Wind Harmer
0.159
315814AE2-033 C
Solar/Wind Harmer
15.301
316087AB2-174 GEN
Solar/Wind Harmer
0.003
315652AC1-086 GEN
Solar/Wind Harmer
10.118
3145796HORNRTN
Solar/Wind Harmer
0.281
3145796HORNRTN
Solar/Wind Harmer
0.035
3137643SOCKMAN
Solar/Wind Harmer
0.328
941031AE2-094 GEN
Solar/Wind Harmer
13.859
944011AF1-069 GEN
Solar/Wind Harmer
4.528
970673AG2-436 GEN
Solar/Wind Harmer
15.712
970673AG2-436 GEN
Solar/Wind Harmer
10.474
971967AH1-528 GEN
Solar/Wind Harmer
11.501
970085AG2-068 GEN
Solar/Wind Harmer
3.665
970581AG2-369 GEN
Solar/Wind Harmer
3.152
970831AG2-522 GEN
Solar/Wind Harmer
2.782
316319Z2-044 C
Solar/Wind Harmer
0
315607AA1-063A GEN
Solar/Wind Harmer
0.121
3145573BETHELC
Solar/Wind Harmer
0.059
3145573BETHELC
Solar/Wind Harmer
0.059
3146033SCOT NK
Solar/Wind Harmer
0.235
316420AA1-050 GEN
Solar/Wind Harmer
0.002
316239AB2-077_GEN
Solar/Wind Harmer
0
316238AB2-078_GEN
Solar/Wind Harmer
0
3146043SEABORD
Solar/Wind Harmer
0.057
3143316POE
Solar/Wind Helper
4.642
316132AB2-190 GEN1
Solar/Wind Helper
1.354
316349AD2-085 GEN
Solar/Wind Helper
1.038
316369SG1_INVT
Solar/Wind Helper
0.893
316312AB1-027
Solar/Wind Helper
0.255
3143873LANEXA
Solar/Wind Helper
0.07
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.398
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.204
MECLTFEXP_MEC->PJM
CLTF
1.237
SIGELTFEXP_SIGE->PJM
CLTF
0.037
CPLELTFEXP_CPLE->PJM
CLTF
3.563
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.107
LAGNLTFEXP_LAGN->PJM
CLTF
2.457
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.602
TVALTFEXP_TVA->PJM
CLTF
1.222
NYPJM->LTFIMP_NY
CLTF
0.342
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.235

Details for 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.53 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:973.3
MW Contribution:1.3
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.618
3144293JTRSVLE
50/50
0.52
970535AG2-341 GEN
50/50
1.297
971489AH1-241 GEN
Solar/Wind Harmer
23.308
3146776BUCKING
Solar/Wind Harmer
1.512
3146776BUCKING
Solar/Wind Harmer
0.122
315821AE2-092 GEN
Solar/Wind Harmer
0.018
970301AG2-198 GEN
Solar/Wind Harmer
8.441
3147133PAMPLIN
Solar/Wind Harmer
0.197
3147133PAMPLIN
Solar/Wind Harmer
0.158
958211AF2-115 GEN
Solar/Wind Harmer
2.196
963191AG1-168 GEN
Solar/Wind Harmer
0.732
971741AH1-377 GEN
Solar/Wind Harmer
16.934
316034AC1-036 C
Solar/Wind Harmer
0.01
970323AG2-213 GEN
Solar/Wind Harmer
5.97
971775AH1-396 GEN
Solar/Wind Harmer
0.224
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.408
964791AG1-342 GEN
Solar/Wind Harmer
1.297
3146843MT LREL
Solar/Wind Harmer
0.067
3146843MT LREL
Solar/Wind Harmer
0.067
939181AE1-148 GEN
Solar/Wind Harmer
3.054
3143526WINTERP
Solar/Wind Helper
0.904
3151921BEARGRDN G2
50/50
4.57
3144293JTRSVLE
50/50
0.618
966251AG1-494 GEN
50/50
1.545
3151591KERR 2
50/50
0.12
970221AG2-151 GEN
Solar/Wind Harmer
23.308
3146776BUCKING
Solar/Wind Harmer
0.136
3146926FARMVIL
Solar/Wind Harmer
0.171
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
2.11
3147133PAMPLIN
Solar/Wind Harmer
0.62
971193AH1-056 GEN
Solar/Wind Harmer
12.029
963181AG1-167 GEN
Solar/Wind Harmer
0.732
959311AF2-222 GEN
Solar/Wind Harmer
13.003
958131AF2-107 GEN
Solar/Wind Harmer
4.145
970257AG2-171 GEN
Solar/Wind Harmer
4.477
315785AD2-033 C
Solar/Wind Harmer
1.066
964241AG1-285 GEN
Solar/Wind Harmer
7.188
316131AB2-060 GEN
Solar/Wind Harmer
0.295
316313AB2-026
Solar/Wind Helper
0.958
316258AE1-075 C
Solar/Wind Helper
0.862
316405AF2-144 C
Solar/Wind Helper
0.719
3151931BEARGRDN S1
50/50
5.898
3151911BEARGRDN G1
50/50
4.57
3144293JTRSVLE
50/50
0.618
3151601KERR 3
50/50
0.12
3151581KERR 1
50/50
0.043
970937AG2-583 GEN
Solar/Wind Harmer
37.481
972003AH1-546 GEN
Solar/Wind Harmer
20.008
971377AH1-170 GEN
Solar/Wind Harmer
4.662
3147623JAMES R
Solar/Wind Harmer
1.013
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.151
3146926FARMVIL
Solar/Wind Harmer
0.171
963171AG1-166 GEN
Solar/Wind Harmer
0.976
971563AH1-280 GEN
Solar/Wind Harmer
1.952
970685AG2-442 GEN
Solar/Wind Harmer
12.103
316237AB2-079_GEN
Solar/Wind Harmer
0.001
962491AG1-098 GEN
Solar/Wind Harmer
4.891
315693AD1-088 GEN
Solar/Wind Harmer
3.821
970401AG2-262 GEN
Solar/Wind Harmer
0.396
962751AG1-124 GEN
Solar/Wind Harmer
2.983
316336AC2-165 C
Solar/Wind Helper
3.978
3143226MDLTHAN
Solar/Wind Helper
0.214
3143526WINTERP
Solar/Wind Helper
0.904
972205AH1-687 GEN
50/50
22.289
3151611KERR 4
50/50
0.12
3151621KERR 5
50/50
0.12
3151631KERR 6
50/50
0.12
3151641KERR 7
50/50
0.12
971447AH1-217 GEN
Solar/Wind Harmer
12.416
971845AH1-439 GEN
Solar/Wind Harmer
16.793
970285AG2-188 GEN
Solar/Wind Harmer
28.117
270494AE1-108_GEN
Solar/Wind Harmer
4.14
315657AE1-056 GEN
Solar/Wind Harmer
6.813
946301AF1-294 GEN
Solar/Wind Harmer
3.611
961791AG1-021 GEN
Solar/Wind Harmer
1.757
970683AG2-441 GEN
Solar/Wind Harmer
10.806
970681AG2-440 GEN
Solar/Wind Harmer
8.645
3144303KENBRDG
Solar/Wind Harmer
0.112
971443AH1-215 GEN
Solar/Wind Harmer
2.318
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.153
316233AE1-074 FULL
Solar/Wind Helper
0.266
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.841
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.476
MECLTFEXP_MEC->PJM
CLTF
0.813
SIGELTFEXP_SIGE->PJM
CLTF
0.026
CPLELTFEXP_CPLE->PJM
CLTF
1.292
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.85
LAGNLTFEXP_LAGN->PJM
CLTF
1.363
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.179
TVALTFEXP_TVA->PJM
CLTF
0.699
NYPJM->LTFIMP_NY
CLTF
0.404
LGEELTFEXP_LGEE->PJM
CLTF
0.328
WECLTFEXP_WEC->PJM
CLTF
0.165

Details for 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.72 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:958.85
MW Contribution:1.35
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
3.828
3151911BEARGRDN G1
50/50
2.966
3144293JTRSVLE
50/50
0.503
3151531CLOVER1
50/50
2.188
3151601KERR 3
50/50
0.135
3151581KERR 1
50/50
0.048
970937AG2-583 GEN
Solar/Wind Harmer
28.699
972003AH1-546 GEN
Solar/Wind Harmer
13.118
971377AH1-170 GEN
Solar/Wind Harmer
3.027
3147623JAMES R
Solar/Wind Harmer
0.658
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
963171AG1-166 GEN
Solar/Wind Harmer
0.794
971563AH1-280 GEN
Solar/Wind Harmer
1.587
970685AG2-442 GEN
Solar/Wind Harmer
10.089
962491AG1-098 GEN
Solar/Wind Harmer
7.03
315693AD1-088 GEN
Solar/Wind Harmer
5.777
957481AF2-042 GEN
Solar/Wind Harmer
29.163
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.003
970401AG2-262 GEN
Solar/Wind Harmer
0.451
316003AC1-222 GEN
Solar/Wind Harmer
0.002
316336AC2-165 C
Solar/Wind Helper
5.135
3143226MDLTHAN
Solar/Wind Helper
0.3
3143526WINTERP
Solar/Wind Helper
1.294
3142543TWELFTH
Solar/Wind Helper
0.014
3142416OLDCHRC
Solar/Wind Helper
0.296
3142416OLDCHRC
Solar/Wind Helper
0.113
316458AB2-190 GEN2
Solar/Wind Helper
0.639
3144293JTRSVLE
50/50
0.503
3144293JTRSVLE
50/50
0.423
970535AG2-341 GEN
50/50
1.349
3152661PLYWOOD A
50/50
0.157
971489AH1-241 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
1.049
3146776BUCKING
Solar/Wind Harmer
0.085
315821AE2-092 GEN
Solar/Wind Harmer
0.013
970301AG2-198 GEN
Solar/Wind Harmer
7.476
971741AH1-377 GEN
Solar/Wind Harmer
16.133
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.127
958211AF2-115 GEN
Solar/Wind Harmer
1.786
963191AG1-168 GEN
Solar/Wind Harmer
0.595
316034AC1-036 C
Solar/Wind Harmer
0.009
970323AG2-213 GEN
Solar/Wind Harmer
5.145
971775AH1-396 GEN
Solar/Wind Harmer
0.193
970099AG2-077 GEN
Solar/Wind Harmer
11.665
3151921BEARGRDN G2
50/50
2.966
3144293JTRSVLE
50/50
0.503
970413AG2-270 GEN
50/50
9.546
966251AG1-494 GEN
50/50
1.198
3151591KERR 2
50/50
0.135
970221AG2-151 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
0.094
3146926FARMVIL
Solar/Wind Harmer
0.129
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
1.869
3147133PAMPLIN
Solar/Wind Harmer
0.497
971193AH1-056 GEN
Solar/Wind Harmer
9.642
963181AG1-167 GEN
Solar/Wind Harmer
0.595
959311AF2-222 GEN
Solar/Wind Harmer
11.09
970257AG2-171 GEN
Solar/Wind Harmer
3.859
315785AD2-033 C
Solar/Wind Harmer
0.934
958131AF2-107 GEN
Solar/Wind Harmer
2.955
316478AD1-087 GEN
Solar/Wind Harmer
0.356
316486AD2-202 GEN
Solar/Wind Harmer
0.105
964241AG1-285 GEN
Solar/Wind Harmer
6.636
316131AB2-060 GEN
Solar/Wind Harmer
0.284
3148013FISHERV
Solar/Wind Harmer
0.071
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.932
971683AH1-343 GEN
Solar/Wind Harmer
2.348
316313AB2-026
Solar/Wind Helper
1.245
316258AE1-075 C
Solar/Wind Helper
1.12
316405AF2-144 C
Solar/Wind Helper
0.933
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.709
315839AE2-212 C
Solar/Wind Helper
0.155
972205AH1-687 GEN
50/50
14.467
3151541CLOVER2
50/50
2.177
3151611KERR 4
50/50
0.135
3151621KERR 5
50/50
0.135
3151631KERR 6
50/50
0.135
3151641KERR 7
50/50
0.135
971447AH1-217 GEN
Solar/Wind Harmer
8.145
971845AH1-439 GEN
Solar/Wind Harmer
11.716
970285AG2-188 GEN
Solar/Wind Harmer
19.851
270494AE1-108_GEN
Solar/Wind Harmer
2.723
315657AE1-056 GEN
Solar/Wind Harmer
5.462
946301AF1-294 GEN
Solar/Wind Harmer
2.936
961791AG1-021 GEN
Solar/Wind Harmer
1.429
970683AG2-441 GEN
Solar/Wind Harmer
9.008
970681AG2-440 GEN
Solar/Wind Harmer
7.206
3144303KENBRDG
Solar/Wind Harmer
0.096
971443AH1-215 GEN
Solar/Wind Harmer
2.005
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.188
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.069
3147243WELCO
Solar/Wind Harmer
0.043
970865AG2-541 GEN
Solar/Wind Harmer
2.13
316123AC1-075 GEN
Solar/Wind Harmer
0.077
970165AG2-112 GEN
Solar/Wind Harmer
0.459
970163AG2-111 GEN
Solar/Wind Harmer
0.438
316233AE1-074 FULL
Solar/Wind Helper
0.38
316312AB1-027
Solar/Wind Helper
0.217
316132AB2-190 GEN1
Solar/Wind Helper
0.639
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.768
964791AG1-342 GEN
Solar/Wind Harmer
1.475
3146843MT LREL
Solar/Wind Harmer
0.077
3146843MT LREL
Solar/Wind Harmer
0.077
939181AE1-148 GEN
Solar/Wind Harmer
3.325
3143526WINTERP
Solar/Wind Helper
1.294
316240AF1-291 C
Solar/Wind Helper
0.162
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.156
316075AC2-137 C
Solar/Wind Helper
0.172
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.581
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
1.069
SIGELTFEXP_SIGE->PJM
CLTF
0.035
CPLELTFEXP_CPLE->PJM
CLTF
0.611
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.053
LAGNLTFEXP_LAGN->PJM
CLTF
1.406
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.04
TVALTFEXP_TVA->PJM
CLTF
0.731
NYPJM->LTFIMP_NY
CLTF
0.331
LGEELTFEXP_LGEE->PJM
CLTF
0.459
WECLTFEXP_WEC->PJM
CLTF
0.235

Details for 6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:142.99 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1407.24
MW Contribution:1.57
Bus #Bus NameTypeMW Contribution
315779AE2-040
50/50
3.099
315244AE2-183_ST
50/50
3.382
963041AG1-153 GEN
50/50
3.109
3151281ROARAP4
50/50
0.132
3151281ROARAP4
50/50
0.123
3151541CLOVER2
50/50
2.008
3151611KERR 4
50/50
0.187
3151621KERR 5
50/50
0.187
3151631KERR 6
50/50
0.187
3151641KERR 7
50/50
0.187
316315AB2-025 C
Solar/Wind Harmer
0.179
315814AE2-033 C
Solar/Wind Harmer
17.298
316087AB2-174 GEN
Solar/Wind Harmer
0.004
315652AC1-086 GEN
Solar/Wind Harmer
13.694
941031AE2-094 GEN
Solar/Wind Harmer
22.572
944011AF1-069 GEN
Solar/Wind Harmer
7.375
3145796HORNRTN
Solar/Wind Harmer
0.385
3145796HORNRTN
Solar/Wind Harmer
0.048
970673AG2-436 GEN
Solar/Wind Harmer
25.561
970673AG2-436 GEN
Solar/Wind Harmer
17.041
971967AH1-528 GEN
Solar/Wind Harmer
18.68
3137643SOCKMAN
Solar/Wind Harmer
0.464
970085AG2-068 GEN
Solar/Wind Harmer
5.942
970581AG2-369 GEN
Solar/Wind Harmer
5.11
315607AA1-063A GEN
Solar/Wind Harmer
0.204
3146043SEABORD
Solar/Wind Harmer
0.098
970831AG2-522 GEN
Solar/Wind Harmer
4.182
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.379
3145573BETHELC
Solar/Wind Harmer
0.092
3145573BETHELC
Solar/Wind Harmer
0.092
316420AA1-050 GEN
Solar/Wind Harmer
0.003
3145683EARLEYS
Solar/Wind Harmer
0.179
3145683EARLEYS
Solar/Wind Harmer
0.09
3145683EARLEYS
Solar/Wind Harmer
0.09
3145513AHOSKIE
Solar/Wind Harmer
0.186
3145513AHOSKIE
Solar/Wind Harmer
0.089
957861AF2-080 GEN
Solar/Wind Harmer
3.828
3145893MURPHYS
Solar/Wind Harmer
0.235
3145893MURPHYS
Solar/Wind Harmer
0.087
965291AG1-394 GEN
Solar/Wind Harmer
0.382
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316005AA1-067
Solar/Wind Harmer
0.092
3145746EVERETS
Solar/Wind Harmer
0.34
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
970181AG2-120 GEN
Solar/Wind Harmer
1.064
3146206CASHIE
Solar/Wind Harmer
0.08
970601AG2-382 GEN
Solar/Wind Harmer
3.008
316118AC1-105 GEN
Solar/Wind Harmer
0.206
3147173SINAI
Solar/Wind Harmer
0.078
3147243WELCO
Solar/Wind Harmer
0.049
315732AD1-074 GEN1
Solar/Wind Harmer
0.439
315733AD1-074 GEN2
Solar/Wind Harmer
0.439
315735AD1-075 GEN1
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
1.275
3130546PLYMOUTH
Solar/Wind Harmer
0.076
3144303KENBRDG
Solar/Wind Harmer
0.06
3143316POE
Solar/Wind Harmer
0.287
315816AE2-034 GEN
Solar/Wind Harmer
0.308
970683AG2-441 GEN
Solar/Wind Harmer
4.722
970681AG2-440 GEN
Solar/Wind Harmer
3.778
3130156CHOWAN
Solar/Wind Harmer
0.066
3130156CHOWAN
Solar/Wind Harmer
0.066
946301AF1-294 GEN
Solar/Wind Harmer
1.311
961791AG1-021 GEN
Solar/Wind Harmer
0.638
970865AG2-541 GEN
Solar/Wind Harmer
2.298
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
315657AE1-056 GEN
Solar/Wind Harmer
2.185
316123AC1-075 GEN
Solar/Wind Harmer
0.08
970165AG2-112 GEN
Solar/Wind Harmer
0.473
970163AG2-111 GEN
Solar/Wind Harmer
0.451
3145176PASQUOTANK
Solar/Wind Harmer
0.036
316321Z2-027
Solar/Wind Harmer
0.011
3146396TANGLEW
Solar/Wind Harmer
0.161
313526AB2-022
Solar/Wind Harmer
0.031
3146486SUNBURY
Solar/Wind Harmer
0.057
3146486SUNBURY
Solar/Wind Harmer
0.057
316132AB2-190 GEN1
Solar/Wind Helper
0.895
316233AE1-074 FULL
Solar/Wind Helper
0.212
316312AB1-027
Solar/Wind Helper
0.237
3151391GASTONA
50/50
0.337
3151411GASTONB
50/50
0.337
3151031BRUNSWICKG2
50/50
1.536
3151261ROARAP2
50/50
0.133
970413AG2-270 GEN
50/50
8.806
3151591KERR 2
50/50
0.187
316365GEN2_N
Solar/Wind Harmer
0.354
313506AB2-031 GEN
Solar/Wind Harmer
0.385
3147043LAWRENC
Solar/Wind Harmer
0.074
3145796HORNRTN
Solar/Wind Harmer
0.481
3145796HORNRTN
Solar/Wind Harmer
0.12
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
970917AG2-570 GEN
Solar/Wind Harmer
9.95
315724AD1-057 GEN
Solar/Wind Harmer
0.4
316210AC1-098 GEN
Solar/Wind Harmer
0.901
316327AA2-057 GEN
Solar/Wind Harmer
0.146
3146233WITAKRS
Solar/Wind Harmer
0.48
3146233WITAKRS
Solar/Wind Harmer
0.065
3138543CONSLDL
Solar/Wind Harmer
0.063
961601AG1-000A GEN
Solar/Wind Harmer
6.766
3146263WOODLND
Solar/Wind Harmer
0.095
971623AH1-311 GEN
Solar/Wind Harmer
0.189
3145543BTLEBRO
Solar/Wind Harmer
0.094
3145543BTLEBRO
Solar/Wind Harmer
0.094
316478AD1-087 GEN
Solar/Wind Harmer
0.329
316486AD2-202 GEN
Solar/Wind Harmer
0.097
316317KELFORD C
Solar/Wind Harmer
0.009
3145823KELFORD
Solar/Wind Harmer
0.092
3146073TAR RVR
Solar/Wind Harmer
0.092
3146083TARBORO
Solar/Wind Harmer
0.092
316463AE2-346 GEN
Solar/Wind Harmer
0.076
316140AB2-099
Solar/Wind Harmer
0.032
962331AG1-082 GEN
Solar/Wind Harmer
0.95
3146173TUNIS
Solar/Wind Harmer
0.088
957521AF2-046 GEN
Solar/Wind Harmer
6.513
961681AG1-008 GEN
Solar/Wind Harmer
6.513
3145893MURPHYS
Solar/Wind Harmer
0.146
3145893MURPHYS
Solar/Wind Harmer
0.087
3156021HOLLOMANSOL
Solar/Wind Harmer
0.393
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
316131AB2-060 GEN
Solar/Wind Harmer
0.268
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3145933PARMELE
Solar/Wind Harmer
0.084
966801AG1-551 GEN
Solar/Wind Harmer
0.976
964241AG1-285 GEN
Solar/Wind Harmer
5.485
3146206CASHIE
Solar/Wind Harmer
0.08
3145963POPLR C
Solar/Wind Harmer
0.08
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.344
315785AD2-033 C
Solar/Wind Harmer
0.629
315737AD1-076 GEN
Solar/Wind Harmer
0.983
971157AH1-035 GEN
Solar/Wind Harmer
0.908
970257AG2-171 GEN
Solar/Wind Harmer
2.416
959311AF2-222 GEN
Solar/Wind Harmer
6.592
316283AC2-100 C
Solar/Wind Harmer
0.142
315614AA2-178 GEN
Solar/Wind Harmer
0.41
971683AH1-343 GEN
Solar/Wind Harmer
2.584
3146376EDENTON
Solar/Wind Harmer
0.067
963181AG1-167 GEN
Solar/Wind Harmer
0.266
3144293JTRSVLE
Adder
0.211
970909AG2-566 GEN
Solar/Wind Harmer
0.692
3147133PAMPLIN
Solar/Wind Harmer
0.199
971193AH1-056 GEN
Solar/Wind Harmer
3.857
315773AC2-141 GEN
Solar/Wind Harmer
2.248
3146626S HERTFORD
Solar/Wind Harmer
0.061
3145273HOLLAND
Solar/Wind Harmer
0.046
3146516WINFALL
Solar/Wind Harmer
0.06
316435W1029_GEN3
Solar/Wind Harmer
0
316320Y1-086
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
12.66
944601AF1-125 GEN
Solar/Wind Harmer
12.465
315839AE2-212 C
Solar/Wind Helper
0.986
316473AC1-191 GEN
Solar/Wind Helper
0.925
3142946ENON
Solar/Wind Helper
0.049
3151391GASTONA
50/50
0.337
3151411GASTONB
50/50
0.337
3147043LAWRENC
50/50
1.178
315243AE2-183_GT3
50/50
1.956
3151051BRUNSWICKS1
50/50
3.187
3151021BRUNSWICKG1
50/50
1.536
971451AH1-221 GEN
50/50
4.664
3151261ROARAP2
50/50
0.136
3151531CLOVER1
50/50
2.018
3151601KERR 3
50/50
0.187
3151581KERR 1
50/50
0.067
316023GEN1_S
Solar/Wind Harmer
0.354
960081AF2-299 GEN
Solar/Wind Harmer
1.332
971795AH1-408 GEN
Solar/Wind Harmer
8.516
316011AB1-132 GEN
Solar/Wind Harmer
2.263
962571AG1-106 GEN
Solar/Wind Harmer
1.771
3145796HORNRTN
Solar/Wind Harmer
0.397
3145796HORNRTN
Solar/Wind Harmer
0.12
940641AE2-051 GEN
Solar/Wind Harmer
9.263
970919AG2-571 GEN
Solar/Wind Harmer
3.98
970087AG2-069 GEN
Solar/Wind Harmer
8.913
3145783HORNRTN
Solar/Wind Harmer
0.107
315722AD1-056 GEN
Solar/Wind Harmer
0.674
316190AA2-174 GEN
Solar/Wind Harmer
0
939411AE1-173 GEN
Solar/Wind Harmer
42.901
957481AF2-042 GEN
Solar/Wind Harmer
26.456
316212AC1-099_GEN
Solar/Wind Harmer
0.502
316129AC1-054 GEN
Solar/Wind Harmer
0.364
971065AG2-659 GEN
Solar/Wind Harmer
4.087
3146233WITAKRS
Solar/Wind Harmer
0.38
3146263WOODLND
Solar/Wind Harmer
0.095
316359AB2-059 GEN
Solar/Wind Harmer
0.34
316049AB1-081 GEN
Solar/Wind Harmer
0.541
3142053HEARTS
Solar/Wind Harmer
0.166
3145543BTLEBRO
Solar/Wind Harmer
0.094
3145543BTLEBRO
Solar/Wind Harmer
0.075
3145823KELFORD
Solar/Wind Harmer
0.092
315693AD1-088 GEN
Solar/Wind Harmer
4.418
961671AG1-007 GEN
Solar/Wind Harmer
0.014
3146083TARBORO
Solar/Wind Harmer
0.092
3145493TOT1
Solar/Wind Harmer
0.407
962491AG1-098 GEN
Solar/Wind Harmer
5.172
3145683EARLEYS
Solar/Wind Harmer
0.09
316494AC1-189 GEN
Solar/Wind Harmer
0.3
315687AD1-152 GEN
Solar/Wind Harmer
0.003
3146173TUNIS
Solar/Wind Harmer
0.088
3145893MURPHYS
Solar/Wind Harmer
0.348
3145893MURPHYS
Solar/Wind Harmer
0.387
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
3146293MARTNCO
Solar/Wind Harmer
0.078
970401AG2-262 GEN
Solar/Wind Harmer
0.478
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3146206CASHIE
Solar/Wind Harmer
0.08
971547AH1-271 GEN
Solar/Wind Harmer
1.719
3145963POPLR C
Solar/Wind Harmer
0.08
316003AC1-222 GEN
Solar/Wind Harmer
0.002
3145663CRESWEL
Solar/Wind Harmer
0.201
971163AH1-040 GEN
Solar/Wind Harmer
5.738
970685AG2-442 GEN
Solar/Wind Harmer
5.289
3130156CHOWAN
Solar/Wind Harmer
0.066
963171AG1-166 GEN
Solar/Wind Harmer
0.354
971563AH1-280 GEN
Solar/Wind Harmer
0.708
3144293JTRSVLE
Adder
0.211
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
316294AC1-161 GEN
Solar/Wind Harmer
1.066
3146516WINFALL
Solar/Wind Harmer
0.194
3146516WINFALL
Solar/Wind Harmer
0.06
944591AF1-124 GEN
Solar/Wind Harmer
12.705
3142543TWELFTH
Solar/Wind Helper
0.024
316458AB2-190 GEN2
Solar/Wind Helper
0.895
3142433PROV 92
Solar/Wind Helper
0.616
3143526WINTERP
Solar/Wind Helper
0.72
3143226MDLTHAN
Solar/Wind Helper
0.125
3142416OLDCHRC
Solar/Wind Helper
0.323
3142416OLDCHRC
Solar/Wind Helper
0.124
970533AG2-339 GEN
50/50
10.894
970531AG2-338 GEN
50/50
4.358
3151361ROSEMG1
50/50
0.433
3151371ROSEMS1
50/50
0.268
3151381ROSEMG2
50/50
0.203
315242AE2-183_GT2
50/50
1.956
315241AE2-183_GT1
50/50
1.944
972185AH1-677 GEN
50/50
7.053
3151041BRUNSWICKG3
50/50
1.536
972187AH1-678 GEN
50/50
3.524
970535AG2-341 GEN
50/50
1.57
3152661PLYWOOD A
50/50
0.18
3144356SAPONY
Solar/Wind Harmer
1.857
316181AB2-040 GEN
Solar/Wind Harmer
0.181
3145796HORNRTN
Solar/Wind Harmer
0.361
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
970933AG2-581 GEN
Solar/Wind Harmer
8.936
3145593CAROLNA
Solar/Wind Harmer
0.109
3145593CAROLNA
Solar/Wind Harmer
0.109
966811AG1-552 GEN
Solar/Wind Harmer
1.182
3145593CAROLNA
Solar/Wind Harmer
0.136
3145783HORNRTN
Solar/Wind Harmer
1.911
3145783HORNRTN
Solar/Wind Harmer
1.529
3145783HORNRTN
Solar/Wind Harmer
0.478
3145783HORNRTN
Solar/Wind Harmer
0.191
316426AA2-053 GEN
Solar/Wind Harmer
0.356
316274AC1-208 GEN
Solar/Wind Harmer
0.518
970099AG2-077 GEN
Solar/Wind Harmer
10.582
961601AG1-000A GEN
Solar/Wind Harmer
1.691
316263AC1-034 GEN
Solar/Wind Harmer
3.592
3145493TOT1
Solar/Wind Harmer
0.212
3145453TOT5
Solar/Wind Harmer
0.127
3145603CNETO
Solar/Wind Harmer
0.085
939181AE1-148 GEN
Solar/Wind Harmer
4.3
3146173TUNIS
Solar/Wind Harmer
0.088
3146173TUNIS
Solar/Wind Harmer
0.088
3145893MURPHYS
Solar/Wind Harmer
0.583
3145893MURPHYS
Solar/Wind Harmer
0.157
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3145933PARMELE
Solar/Wind Harmer
0.168
3145933PARMELE
Solar/Wind Harmer
0.084
962561AG1-105 GEN
Solar/Wind Harmer
3.947
964791AG1-342 GEN
Solar/Wind Harmer
1.566
3146843MT LREL
Solar/Wind Harmer
0.081
3146843MT LREL
Solar/Wind Harmer
0.081
316065AD1-022 GEN
Solar/Wind Harmer
3.64
970323AG2-213 GEN
Solar/Wind Harmer
3.221
971775AH1-396 GEN
Solar/Wind Harmer
0.121
316034AC1-036 C
Solar/Wind Harmer
0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.303
971741AH1-377 GEN
Solar/Wind Harmer
7.057
3146376EDENTON
Solar/Wind Harmer
0.296
3146376EDENTON
Solar/Wind Harmer
0.296
958211AF2-115 GEN
Solar/Wind Harmer
0.797
963191AG1-168 GEN
Solar/Wind Harmer
0.266
3144293JTRSVLE
Adder
0.211
3144293JTRSVLE
Adder
0.178
315742AE1-103 GEN
Solar/Wind Harmer
0.001
970301AG2-198 GEN
Solar/Wind Harmer
2.77
3147133PAMPLIN
Solar/Wind Harmer
0.063
3147133PAMPLIN
Solar/Wind Harmer
0.051
3146626S HERTFORD
Solar/Wind Harmer
0.061
3146626S HERTFORD
Solar/Wind Harmer
0.061
3146516WINFALL
Solar/Wind Harmer
0.06
3146516WINFALL
Solar/Wind Harmer
0.06
3146516WINFALL
Solar/Wind Harmer
0.06
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146386ELIZ CT
Solar/Wind Harmer
0.057
316240AF1-291 C
Solar/Wind Helper
0.411
966871AG1-558 GEN
Solar/Wind Helper
0.204
3142946ENON
Solar/Wind Helper
0.015
3143526WINTERP
Solar/Wind Helper
0.72
316468AD1-105 GEN
Solar/Wind Helper
0.653
316075AC2-137 C
Solar/Wind Helper
0.178
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.11
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.461
MECLTFEXP_MEC->PJM
CLTF
1.839
SIGELTFEXP_SIGE->PJM
CLTF
0.055
CPLELTFEXP_CPLE->PJM
CLTF
5.631
CBM West 2LTFEXP_CBM-W2->PJM
CBM
19.951
LAGNLTFEXP_LAGN->PJM
CLTF
3.79
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.991
TVALTFEXP_TVA->PJM
CLTF
1.888
NYPJM->LTFIMP_NY
CLTF
0.691
LGEELTFEXP_LGEE->PJM
CLTF
0.659
WECLTFEXP_WEC->PJM
CLTF
0.343

Details for 6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2002_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.0 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1171.16
MW Contribution:1.33
Bus #Bus NameTypeMW Contribution
3151361ROSEMG1
50/50
0.408
3151371ROSEMS1
50/50
0.253
3151381ROSEMG2
50/50
0.191
970533AG2-339 GEN
50/50
8.434
970531AG2-338 GEN
50/50
3.373
3151391GASTONA
50/50
0.32
3151411GASTONB
50/50
0.32
3151261ROARAP2
50/50
0.119
3151031BRUNSWICKG2
50/50
1.193
3151591KERR 2
50/50
0.157
970413AG2-270 GEN
50/50
6.966
316365GEN2_N
Solar/Wind Harmer
0.362
313506AB2-031 GEN
Solar/Wind Harmer
0.366
3147043LAWRENC
Solar/Wind Harmer
0.071
3145796HORNRTN
Solar/Wind Harmer
0.453
3145796HORNRTN
Solar/Wind Harmer
0.113
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
315724AD1-057 GEN
Solar/Wind Harmer
0.363
970917AG2-570 GEN
Solar/Wind Harmer
7.751
316327AA2-057 GEN
Solar/Wind Harmer
0.127
961601AG1-000A GEN
Solar/Wind Harmer
5.909
316210AC1-098 GEN
Solar/Wind Harmer
0.77
3146233WITAKRS
Solar/Wind Harmer
0.417
3146233WITAKRS
Solar/Wind Harmer
0.056
3138543CONSLDL
Solar/Wind Harmer
0.055
971623AH1-311 GEN
Solar/Wind Harmer
0.164
3145543BTLEBRO
Solar/Wind Harmer
0.082
3145543BTLEBRO
Solar/Wind Harmer
0.082
3146263WOODLND
Solar/Wind Harmer
0.078
3146073TAR RVR
Solar/Wind Harmer
0.078
3146083TARBORO
Solar/Wind Harmer
0.078
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.075
316478AD1-087 GEN
Solar/Wind Harmer
0.26
316486AD2-202 GEN
Solar/Wind Harmer
0.076
316131AB2-060 GEN
Solar/Wind Harmer
0.229
964241AG1-285 GEN
Solar/Wind Harmer
4.665
3151391GASTONA
50/50
0.32
3151411GASTONB
50/50
0.32
3147043LAWRENC
50/50
1.13
3151261ROARAP2
50/50
0.121
315243AE2-183_GT3
50/50
1.518
3151051BRUNSWICKS1
50/50
2.476
3151021BRUNSWICKG1
50/50
1.193
971451AH1-221 GEN
50/50
3.623
3151601KERR 3
50/50
0.157
3151581KERR 1
50/50
0.056
3151531CLOVER1
50/50
1.596
316023GEN1_S
Solar/Wind Harmer
0.362
960081AF2-299 GEN
Solar/Wind Harmer
1.316
971795AH1-408 GEN
Solar/Wind Harmer
8.254
316011AB1-132 GEN
Solar/Wind Harmer
2.152
315779AE2-040
50/50
3.401
3151281ROARAP4
50/50
0.118
3151281ROARAP4
50/50
0.11
315244AE2-183_ST
50/50
2.625
963041AG1-153 GEN
50/50
2.415
3151611KERR 4
50/50
0.157
3151621KERR 5
50/50
0.157
3151631KERR 6
50/50
0.157
3151641KERR 7
50/50
0.157
3151541CLOVER2
50/50
1.589
316315AB2-025 C
Solar/Wind Harmer
0.197
315814AE2-033 C
Solar/Wind Harmer
18.936
316087AB2-174 GEN
Solar/Wind Harmer
0.004
316463AE2-346 GEN
Solar/Wind Harmer
0.06
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.742
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.068
3156021HOLLOMANSOL
Solar/Wind Harmer
0.305
3145933PARMELE
Solar/Wind Harmer
0.066
962571AG1-106 GEN
Solar/Wind Harmer
1.684
3145796HORNRTN
Solar/Wind Harmer
0.374
3145796HORNRTN
Solar/Wind Harmer
0.113
315722AD1-056 GEN
Solar/Wind Harmer
0.612
3145783HORNRTN
Solar/Wind Harmer
0.096
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
3.101
970087AG2-069 GEN
Solar/Wind Harmer
6.946
940641AE2-051 GEN
Solar/Wind Harmer
6.931
316129AC1-054 GEN
Solar/Wind Harmer
0.314
316212AC1-099_GEN
Solar/Wind Harmer
0.43
3146233WITAKRS
Solar/Wind Harmer
0.33
971065AG2-659 GEN
Solar/Wind Harmer
3.51
316359AB2-059 GEN
Solar/Wind Harmer
0.295
316049AB1-081 GEN
Solar/Wind Harmer
0.471
3142053HEARTS
Solar/Wind Harmer
0.145
3145543BTLEBRO
Solar/Wind Harmer
0.082
3145543BTLEBRO
Solar/Wind Harmer
0.066
3146263WOODLND
Solar/Wind Harmer
0.078
957481AF2-042 GEN
Solar/Wind Harmer
20.812
961671AG1-007 GEN
Solar/Wind Harmer
0.012
3146083TARBORO
Solar/Wind Harmer
0.078
3145493TOT1
Solar/Wind Harmer
0.346
3145823KELFORD
Solar/Wind Harmer
0.075
316494AC1-189 GEN
Solar/Wind Harmer
0.249
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
3.49
962491AG1-098 GEN
Solar/Wind Harmer
4.086
3145683EARLEYS
Solar/Wind Harmer
0.071
315687AD1-152 GEN
Solar/Wind Harmer
0.002
939411AE1-173 GEN
Solar/Wind Harmer
30.084
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.068
970401AG2-262 GEN
Solar/Wind Harmer
0.397
3146293MARTNCO
Solar/Wind Harmer
0.061
3145893MURPHYS
Solar/Wind Harmer
0.259
3145893MURPHYS
Solar/Wind Harmer
0.288
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145963POPLR C
Solar/Wind Harmer
0.06
316003AC1-222 GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
4.444
3146206CASHIE
Solar/Wind Harmer
0.059
971547AH1-271 GEN
Solar/Wind Harmer
1.257
3142543TWELFTH
Solar/Wind Helper
0.031
316458AB2-190 GEN2
Solar/Wind Helper
1.544
316381AD1-082 GEN
Solar/Wind Helper
1.346
3142433PROV 92
Solar/Wind Helper
0.863
3142416OLDCHRC
Solar/Wind Helper
0.448
3142416OLDCHRC
Solar/Wind Helper
0.172
3143526WINTERP
Solar/Wind Helper
0.727
3141766HARMONY
Solar/Wind Helper
0.024
964211AG1-282 GEN
Solar/Wind Helper
0.157
3141726DUNNSVL
Solar/Wind Helper
0.465
3138133OCRAN
Solar/Wind Helper
0.068
315242AE2-183_GT2
50/50
1.518
315241AE2-183_GT1
50/50
1.509
972185AH1-677 GEN
50/50
5.473
3151041BRUNSWICKG3
50/50
1.193
972187AH1-678 GEN
50/50
2.737
970535AG2-341 GEN
50/50
1.329
3152661PLYWOOD A
50/50
0.148
3144356SAPONY
Solar/Wind Harmer
2.038
316181AB2-040 GEN
Solar/Wind Harmer
0.172
3145796HORNRTN
Solar/Wind Harmer
0.34
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
3142666NORTHAMPTON
Solar/Wind Harmer
0.067
3145593CAROLNA
Solar/Wind Harmer
0.097
3145593CAROLNA
Solar/Wind Harmer
0.097
966811AG1-552 GEN
Solar/Wind Harmer
1.057
3145593CAROLNA
Solar/Wind Harmer
0.121
3145783HORNRTN
Solar/Wind Harmer
1.703
3145783HORNRTN
Solar/Wind Harmer
1.362
3145783HORNRTN
Solar/Wind Harmer
0.426
3145783HORNRTN
Solar/Wind Harmer
0.17
316426AA2-053 GEN
Solar/Wind Harmer
0.313
970933AG2-581 GEN
Solar/Wind Harmer
6.963
316274AC1-208 GEN
Solar/Wind Harmer
0.45
961601AG1-000A GEN
Solar/Wind Harmer
1.477
316263AC1-034 GEN
Solar/Wind Harmer
3.125
970099AG2-077 GEN
Solar/Wind Harmer
8.325
3145493TOT1
Solar/Wind Harmer
0.181
3145453TOT5
Solar/Wind Harmer
0.108
3145603CNETO
Solar/Wind Harmer
0.072
939181AE1-148 GEN
Solar/Wind Harmer
3.627
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.291
3146173TUNIS
Solar/Wind Harmer
0.068
3146173TUNIS
Solar/Wind Harmer
0.068
964791AG1-342 GEN
Solar/Wind Harmer
1.3
3146843MT LREL
Solar/Wind Harmer
0.068
3146843MT LREL
Solar/Wind Harmer
0.068
3145933PARMELE
Solar/Wind Harmer
0.132
3145933PARMELE
Solar/Wind Harmer
0.066
3145893MURPHYS
Solar/Wind Harmer
0.433
3145893MURPHYS
Solar/Wind Harmer
0.116
970323AG2-213 GEN
Solar/Wind Harmer
2.721
971775AH1-396 GEN
Solar/Wind Harmer
0.102
316034AC1-036 C
Solar/Wind Harmer
0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.245
316065AD1-022 GEN
Solar/Wind Harmer
2.617
971741AH1-377 GEN
Solar/Wind Harmer
5.589
316240AF1-291 C
Solar/Wind Helper
0.691
3142946ENON
Solar/Wind Helper
0.022
316033AB2-134 GEN
Solar/Wind Helper
0.717
315697AD1-025 GEN
Solar/Wind Helper
2.382
966801AG1-551 GEN
Solar/Wind Harmer
0.769
957521AF2-046 GEN
Solar/Wind Harmer
4.888
961681AG1-008 GEN
Solar/Wind Harmer
4.888
315785AD2-033 C
Solar/Wind Harmer
0.532
3145893MURPHYS
Solar/Wind Harmer
0.108
3145893MURPHYS
Solar/Wind Harmer
0.065
970257AG2-171 GEN
Solar/Wind Harmer
2.041
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.715
959311AF2-222 GEN
Solar/Wind Harmer
5.561
3145963POPLR C
Solar/Wind Harmer
0.06
3156081AA2-088 GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.059
316283AC2-100 C
Solar/Wind Harmer
0.115
971683AH1-343 GEN
Solar/Wind Harmer
2.095
315839AE2-212 C
Solar/Wind Helper
1.113
3142946ENON
Solar/Wind Helper
0.074
316473AC1-191 GEN
Solar/Wind Helper
1.189
316280AD1-041 GEN
Solar/Wind Helper
0.416
316404AE1-155 C
Solar/Wind Helper
0.956
316484AD2-074 GEN
Solar/Wind Helper
0.219
316156AD2-030 GEN
Solar/Wind Helper
0.171
966871AG1-558 GEN
Solar/Wind Helper
0.262
316075AC2-137 C
Solar/Wind Helper
0.263
316468AD1-105 GEN
Solar/Wind Helper
0.815
3143526WINTERP
Solar/Wind Helper
0.727
316077AC2-138 C
Solar/Wind Helper
0.107
316487AF1-042 GEN
Solar/Wind Helper
0.114
315652AC1-086 GEN
Solar/Wind Harmer
13.019
3145796HORNRTN
Solar/Wind Harmer
0.362
3145796HORNRTN
Solar/Wind Harmer
0.045
3137643SOCKMAN
Solar/Wind Harmer
0.427
941031AE2-094 GEN
Solar/Wind Harmer
17.475
944011AF1-069 GEN
Solar/Wind Harmer
5.71
970673AG2-436 GEN
Solar/Wind Harmer
19.819
970673AG2-436 GEN
Solar/Wind Harmer
13.213
971967AH1-528 GEN
Solar/Wind Harmer
14.51
970085AG2-068 GEN
Solar/Wind Harmer
4.631
970581AG2-369 GEN
Solar/Wind Harmer
3.982
970831AG2-522 GEN
Solar/Wind Harmer
3.621
315607AA1-063A GEN
Solar/Wind Harmer
0.17
316319Z2-044 C
Solar/Wind Harmer
0
3146043SEABORD
Solar/Wind Harmer
0.081
3146033SCOT NK
Solar/Wind Harmer
0.318
3145573BETHELC
Solar/Wind Harmer
0.078
3145573BETHELC
Solar/Wind Harmer
0.078
316420AA1-050 GEN
Solar/Wind Harmer
0.003
957861AF2-080 GEN
Solar/Wind Harmer
3.178
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3145683EARLEYS
Solar/Wind Harmer
0.142
3145683EARLEYS
Solar/Wind Harmer
0.071
3145683EARLEYS
Solar/Wind Harmer
0.071
3145513AHOSKIE
Solar/Wind Harmer
0.145
3145513AHOSKIE
Solar/Wind Harmer
0.07
316005AA1-067
Solar/Wind Harmer
0.074
3145746EVERETS
Solar/Wind Harmer
0.274
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
970181AG2-120 GEN
Solar/Wind Harmer
0.856
316118AC1-105 GEN
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
0.175
3145893MURPHYS
Solar/Wind Harmer
0.065
971443AH1-215 GEN
Solar/Wind Harmer
1.078
3144303KENBRDG
Solar/Wind Harmer
0.051
3147173SINAI
Solar/Wind Harmer
0.064
3147243WELCO
Solar/Wind Harmer
0.04
965291AG1-394 GEN
Solar/Wind Harmer
0.275
970683AG2-441 GEN
Solar/Wind Harmer
3.967
970681AG2-440 GEN
Solar/Wind Harmer
3.174
3146206CASHIE
Solar/Wind Harmer
0.059
970601AG2-382 GEN
Solar/Wind Harmer
2.2
3143316POE
Solar/Wind Helper
1.93
316132AB2-190 GEN1
Solar/Wind Helper
1.544
316369SG1_INVT
Solar/Wind Helper
1.002
316312AB1-027
Solar/Wind Helper
0.328
3143873LANEXA
Solar/Wind Helper
0.095
316233AE1-074 FULL
Solar/Wind Helper
0.214
315662AE1-191 GEN
Solar/Wind Helper
0.666
315666AE1-190 GEN
Solar/Wind Helper
0.167
316059AD1-063 C
Solar/Wind Helper
0.122
3141813NORNECK
Solar/Wind Helper
0.113
3141783LANCAST
Solar/Wind Helper
0.068
3141783LANCAST
Solar/Wind Helper
0.045
3141913WHIT STONE
Solar/Wind Helper
0.113
3138133OCRAN
Solar/Wind Helper
0.034
957601AF2-054 GEN
Solar/Wind Helper
0.152
3141873WAN 176
Solar/Wind Helper
0.023
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.423
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.312
MECLTFEXP_MEC->PJM
CLTF
1.548
SIGELTFEXP_SIGE->PJM
CLTF
0.046
CPLELTFEXP_CPLE->PJM
CLTF
4.572
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.518
LAGNLTFEXP_LAGN->PJM
CLTF
3.11
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.716
TVALTFEXP_TVA->PJM
CLTF
1.547
NYPJM->LTFIMP_NY
CLTF
0.457
LGEELTFEXP_LGEE->PJM
CLTF
0.557
WECLTFEXP_WEC->PJM
CLTF
0.293

Details for 6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.7 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:893.85
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3151261ROARAP2
50/50
0.313
3151591KERR 2
50/50
0.27
3144293JTRSVLE
50/50
0.305
970413AG2-270 GEN
50/50
6.801
316365GEN2_N
Solar/Wind Harmer
1.155
313506AB2-031 GEN
Solar/Wind Harmer
1.049
3147043LAWRENC
Solar/Wind Harmer
0.196
3145796HORNRTN
Solar/Wind Harmer
1.268
3145796HORNRTN
Solar/Wind Harmer
0.317
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.321
3144293JTRSVLE
50/50
0.305
3144293JTRSVLE
50/50
0.257
3152661PLYWOOD A
50/50
0.195
316181AB2-040 GEN
Solar/Wind Harmer
0.492
3145796HORNRTN
Solar/Wind Harmer
0.951
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3145593CAROLNA
Solar/Wind Harmer
0.257
3145593CAROLNA
Solar/Wind Harmer
0.257
966811AG1-552 GEN
Solar/Wind Harmer
2.785
3145593CAROLNA
Solar/Wind Harmer
0.32
3145783HORNRTN
Solar/Wind Harmer
4.428
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3147043LAWRENC
50/50
3.141
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.27
3151581KERR 1
50/50
0.096
3145783HORNRTN
Solar/Wind Harmer
3.543
3145783HORNRTN
Solar/Wind Harmer
1.107
3145783HORNRTN
Solar/Wind Harmer
0.443
316426AA2-053 GEN
Solar/Wind Harmer
0.813
316274AC1-208 GEN
Solar/Wind Harmer
1.081
961601AG1-000A GEN
Solar/Wind Harmer
3.201
316263AC1-034 GEN
Solar/Wind Harmer
6.707
3145493TOT1
Solar/Wind Harmer
0.382
3145453TOT5
Solar/Wind Harmer
0.229
3145603CNETO
Solar/Wind Harmer
0.153
3146173TUNIS
Solar/Wind Harmer
0.163
3146173TUNIS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
1.071
3145893MURPHYS
Solar/Wind Harmer
0.288
3145933PARMELE
Solar/Wind Harmer
0.262
3145933PARMELE
Solar/Wind Harmer
0.131
313527AB2-043 GEN
Solar/Wind Harmer
0.002
939181AE1-148 GEN
Solar/Wind Harmer
6.26
316065AD1-022 GEN
Solar/Wind Harmer
5.298
970323AG2-213 GEN
Solar/Wind Harmer
4.655
971775AH1-396 GEN
Solar/Wind Harmer
0.175
316034AC1-036 C
Solar/Wind Harmer
0.008
962561AG1-105 GEN
Solar/Wind Harmer
5
964791AG1-342 GEN
Solar/Wind Harmer
1.908
3146843MT LREL
Solar/Wind Harmer
0.099
3146843MT LREL
Solar/Wind Harmer
0.099
958211AF2-115 GEN
Solar/Wind Harmer
1.083
963191AG1-168 GEN
Solar/Wind Harmer
0.361
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.27
3151621KERR 5
50/50
0.27
3151631KERR 6
50/50
0.27
3151641KERR 7
50/50
0.27
3151151S HAMPT1
50/50
0.285
3151541CLOVER2
50/50
1.551
316087AB2-174 GEN
Solar/Wind Harmer
0.01
315652AC1-086 GEN
Solar/Wind Harmer
37.428
3145796HORNRTN
Solar/Wind Harmer
1.015
3145796HORNRTN
Solar/Wind Harmer
0.127
3137643SOCKMAN
Solar/Wind Harmer
1.176
315607AA1-063A GEN
Solar/Wind Harmer
0.444
3146043SEABORD
Solar/Wind Harmer
0.211
3146033SCOT NK
Solar/Wind Harmer
0.75
316319Z2-044 C
Solar/Wind Harmer
0
970831AG2-522 GEN
Solar/Wind Harmer
7.783
3145683EARLEYS
Solar/Wind Harmer
0.333
3145683EARLEYS
Solar/Wind Harmer
0.166
3145683EARLEYS
Solar/Wind Harmer
0.166
3145513AHOSKIE
Solar/Wind Harmer
0.345
3145513AHOSKIE
Solar/Wind Harmer
0.165
3145573BETHELC
Solar/Wind Harmer
0.165
3145573BETHELC
Solar/Wind Harmer
0.165
3145893MURPHYS
Solar/Wind Harmer
0.432
3145893MURPHYS
Solar/Wind Harmer
0.16
316420AA1-050 GEN
Solar/Wind Harmer
0.005
965291AG1-394 GEN
Solar/Wind Harmer
0.698
957861AF2-080 GEN
Solar/Wind Harmer
6.563
316005AA1-067
Solar/Wind Harmer
0.148
3145746EVERETS
Solar/Wind Harmer
0.548
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
970181AG2-120 GEN
Solar/Wind Harmer
1.713
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.122
970601AG2-382 GEN
Solar/Wind Harmer
4.575
971443AH1-215 GEN
Solar/Wind Harmer
1.848
3144303KENBRDG
Solar/Wind Harmer
0.087
3147133PAMPLIN
Solar/Wind Harmer
0.084
3147133PAMPLIN
Solar/Wind Harmer
0.067
970099AG2-077 GEN
Solar/Wind Harmer
7.723
315742AE1-103 GEN
Solar/Wind Harmer
0.001
971741AH1-377 GEN
Solar/Wind Harmer
5.969
316222AC1-221 GEN
Solar/Wind Harmer
0.242
970301AG2-198 GEN
Solar/Wind Harmer
2.421
3144356SAPONY
Solar/Wind Helper
0.972
316240AF1-291 C
Solar/Wind Helper
0.168
3144293JTRSVLE
50/50
0.305
3151531CLOVER1
50/50
1.558
316023GEN1_S
Solar/Wind Harmer
1.155
960081AF2-299 GEN
Solar/Wind Harmer
3.965
971795AH1-408 GEN
Solar/Wind Harmer
23.615
316011AB1-132 GEN
Solar/Wind Harmer
6.186
962571AG1-106 GEN
Solar/Wind Harmer
4.841
3145796HORNRTN
Solar/Wind Harmer
1.046
3145796HORNRTN
Solar/Wind Harmer
0.317
3145783HORNRTN
Solar/Wind Harmer
0.249
315722AD1-056 GEN
Solar/Wind Harmer
1.531
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
1.015
3146263WOODLND
Solar/Wind Harmer
0.191
3146233WITAKRS
Solar/Wind Harmer
0.73
3145823KELFORD
Solar/Wind Harmer
0.177
316359AB2-059 GEN
Solar/Wind Harmer
0.634
316049AB1-081 GEN
Solar/Wind Harmer
1.01
3142053HEARTS
Solar/Wind Harmer
0.311
3145543BTLEBRO
Solar/Wind Harmer
0.175
3145543BTLEBRO
Solar/Wind Harmer
0.14
316129AC1-054 GEN
Solar/Wind Harmer
0.656
971065AG2-659 GEN
Solar/Wind Harmer
7.13
3145683EARLEYS
Solar/Wind Harmer
0.166
961671AG1-007 GEN
Solar/Wind Harmer
0.025
3146083TARBORO
Solar/Wind Harmer
0.165
3145493TOT1
Solar/Wind Harmer
0.732
3146173TUNIS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
0.64
3145893MURPHYS
Solar/Wind Harmer
0.712
316494AC1-189 GEN
Solar/Wind Harmer
0.514
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3146293MARTNCO
Solar/Wind Harmer
0.122
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.122
971547AH1-271 GEN
Solar/Wind Harmer
2.614
316174AB2-169 GEN
Solar/Wind Harmer
0.003
3145963POPLR C
Solar/Wind Harmer
0.118
970685AG2-442 GEN
Solar/Wind Harmer
7.425
970401AG2-262 GEN
Solar/Wind Harmer
0.583
963171AG1-166 GEN
Solar/Wind Harmer
0.482
971563AH1-280 GEN
Solar/Wind Harmer
0.963
3145663CRESWEL
Solar/Wind Harmer
0.224
971163AH1-040 GEN
Solar/Wind Harmer
6.407
957481AF2-042 GEN
Solar/Wind Harmer
19.308
316003AC1-222 GEN
Solar/Wind Harmer
0.002
315693AD1-088 GEN
Solar/Wind Harmer
3.442
315687AD1-152 GEN
Solar/Wind Harmer
0.002
962491AG1-098 GEN
Solar/Wind Harmer
4.048
315732AD1-074 GEN1
Solar/Wind Harmer
0.587
315733AD1-074 GEN2
Solar/Wind Harmer
0.587
315735AD1-075 GEN1
Solar/Wind Harmer
0.294
970683AG2-441 GEN
Solar/Wind Harmer
6.63
970681AG2-440 GEN
Solar/Wind Harmer
5.304
3130546PLYMOUTH
Solar/Wind Harmer
0.098
946301AF1-294 GEN
Solar/Wind Harmer
1.782
961791AG1-021 GEN
Solar/Wind Harmer
0.867
316118AC1-105 GEN
Solar/Wind Harmer
0.227
315657AE1-056 GEN
Solar/Wind Harmer
2.895
315816AE2-034 GEN
Solar/Wind Harmer
0.344
3147173SINAI
Solar/Wind Harmer
0.077
3147243WELCO
Solar/Wind Harmer
0.048
970865AG2-541 GEN
Solar/Wind Harmer
2.227
316315AB2-025 C
Solar/Wind Helper
0.826
3143316POE
Solar/Wind Helper
0.688
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
315724AD1-057 GEN
Solar/Wind Harmer
0.907
316210AC1-098 GEN
Solar/Wind Harmer
1.821
316327AA2-057 GEN
Solar/Wind Harmer
0.289
3146263WOODLND
Solar/Wind Harmer
0.191
3146233WITAKRS
Solar/Wind Harmer
0.921
3146233WITAKRS
Solar/Wind Harmer
0.125
3138543CONSLDL
Solar/Wind Harmer
0.12
961601AG1-000A GEN
Solar/Wind Harmer
12.805
316317KELFORD C
Solar/Wind Harmer
0.017
3145823KELFORD
Solar/Wind Harmer
0.177
971623AH1-311 GEN
Solar/Wind Harmer
0.353
3145543BTLEBRO
Solar/Wind Harmer
0.175
3145543BTLEBRO
Solar/Wind Harmer
0.175
316463AE2-346 GEN
Solar/Wind Harmer
0.142
316140AB2-099
Solar/Wind Harmer
0.059
962331AG1-082 GEN
Solar/Wind Harmer
1.76
3146073TAR RVR
Solar/Wind Harmer
0.165
3146083TARBORO
Solar/Wind Harmer
0.165
3146173TUNIS
Solar/Wind Harmer
0.163
957521AF2-046 GEN
Solar/Wind Harmer
11.982
961681AG1-008 GEN
Solar/Wind Harmer
11.982
3145893MURPHYS
Solar/Wind Harmer
0.268
3145893MURPHYS
Solar/Wind Harmer
0.16
3156021HOLLOMANSOL
Solar/Wind Harmer
0.689
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3145933PARMELE
Solar/Wind Harmer
0.131
966801AG1-551 GEN
Solar/Wind Harmer
1.529
316131AB2-060 GEN
Solar/Wind Harmer
0.407
964241AG1-285 GEN
Solar/Wind Harmer
8.211
3146206CASHIE
Solar/Wind Harmer
0.122
3145963POPLR C
Solar/Wind Harmer
0.118
315785AD2-033 C
Solar/Wind Harmer
0.918
970257AG2-171 GEN
Solar/Wind Harmer
3.491
959311AF2-222 GEN
Solar/Wind Harmer
9.454
315737AD1-076 GEN
Solar/Wind Harmer
1.314
971157AH1-035 GEN
Solar/Wind Harmer
1.183
963181AG1-167 GEN
Solar/Wind Harmer
0.361
3147133PAMPLIN
Solar/Wind Harmer
0.263
971193AH1-056 GEN
Solar/Wind Harmer
5.112
315614AA2-178 GEN
Solar/Wind Harmer
0.458
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.273
316478AD1-087 GEN
Solar/Wind Harmer
0.254
316486AD2-202 GEN
Solar/Wind Harmer
0.075
971683AH1-343 GEN
Solar/Wind Harmer
2.513
942461AE2-259 GEN
Solar/Wind Harmer
0
316283AC2-100 C
Solar/Wind Harmer
0.113
970909AG2-566 GEN
Solar/Wind Harmer
0.605
315839AE2-212 C
Solar/Wind Helper
0.197
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.85
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.587
MECLTFEXP_MEC->PJM
CLTF
1.327
SIGELTFEXP_SIGE->PJM
CLTF
0.04
CPLELTFEXP_CPLE->PJM
CLTF
4.45
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.218
LAGNLTFEXP_LAGN->PJM
CLTF
2.678
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.707
TVALTFEXP_TVA->PJM
CLTF
1.336
NYPJM->LTFIMP_NY
CLTF
0.49
LGEELTFEXP_LGEE->PJM
CLTF
0.481
WECLTFEXP_WEC->PJM
CLTF
0.25

Details for 6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.06 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:889.45
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3147043LAWRENC
50/50
3.141
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.27
3151581KERR 1
50/50
0.096
3144293JTRSVLE
50/50
0.305
3151531CLOVER1
50/50
1.558
316023GEN1_S
Solar/Wind Harmer
1.155
960081AF2-299 GEN
Solar/Wind Harmer
3.965
971795AH1-408 GEN
Solar/Wind Harmer
23.615
316011AB1-132 GEN
Solar/Wind Harmer
6.186
962571AG1-106 GEN
Solar/Wind Harmer
4.841
3145796HORNRTN
Solar/Wind Harmer
1.046
3145796HORNRTN
Solar/Wind Harmer
0.317
3145783HORNRTN
Solar/Wind Harmer
0.249
315722AD1-056 GEN
Solar/Wind Harmer
1.531
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
1.015
3146263WOODLND
Solar/Wind Harmer
0.191
3146233WITAKRS
Solar/Wind Harmer
0.73
3145823KELFORD
Solar/Wind Harmer
0.177
316359AB2-059 GEN
Solar/Wind Harmer
0.634
316049AB1-081 GEN
Solar/Wind Harmer
1.01
3142053HEARTS
Solar/Wind Harmer
0.311
3145543BTLEBRO
Solar/Wind Harmer
0.175
3145543BTLEBRO
Solar/Wind Harmer
0.14
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.27
3151621KERR 5
50/50
0.27
3151631KERR 6
50/50
0.27
3151641KERR 7
50/50
0.27
3151151S HAMPT1
50/50
0.285
3151541CLOVER2
50/50
1.551
316087AB2-174 GEN
Solar/Wind Harmer
0.01
315652AC1-086 GEN
Solar/Wind Harmer
37.428
3145796HORNRTN
Solar/Wind Harmer
1.015
3145796HORNRTN
Solar/Wind Harmer
0.127
3137643SOCKMAN
Solar/Wind Harmer
1.176
315607AA1-063A GEN
Solar/Wind Harmer
0.444
3146043SEABORD
Solar/Wind Harmer
0.211
3146033SCOT NK
Solar/Wind Harmer
0.75
316319Z2-044 C
Solar/Wind Harmer
0
970831AG2-522 GEN
Solar/Wind Harmer
7.783
3145683EARLEYS
Solar/Wind Harmer
0.333
3145683EARLEYS
Solar/Wind Harmer
0.166
3145683EARLEYS
Solar/Wind Harmer
0.166
3145513AHOSKIE
Solar/Wind Harmer
0.345
3145513AHOSKIE
Solar/Wind Harmer
0.165
3145573BETHELC
Solar/Wind Harmer
0.165
3145573BETHELC
Solar/Wind Harmer
0.165
3145893MURPHYS
Solar/Wind Harmer
0.432
3145893MURPHYS
Solar/Wind Harmer
0.16
316420AA1-050 GEN
Solar/Wind Harmer
0.005
965291AG1-394 GEN
Solar/Wind Harmer
0.698
957861AF2-080 GEN
Solar/Wind Harmer
6.563
316005AA1-067
Solar/Wind Harmer
0.148
3145746EVERETS
Solar/Wind Harmer
0.548
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
970181AG2-120 GEN
Solar/Wind Harmer
1.713
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.122
970601AG2-382 GEN
Solar/Wind Harmer
4.575
971443AH1-215 GEN
Solar/Wind Harmer
1.848
3144303KENBRDG
Solar/Wind Harmer
0.087
315732AD1-074 GEN1
Solar/Wind Harmer
0.587
315733AD1-074 GEN2
Solar/Wind Harmer
0.587
315735AD1-075 GEN1
Solar/Wind Harmer
0.294
970683AG2-441 GEN
Solar/Wind Harmer
6.63
970681AG2-440 GEN
Solar/Wind Harmer
5.304
3130546PLYMOUTH
Solar/Wind Harmer
0.098
946301AF1-294 GEN
Solar/Wind Harmer
1.782
961791AG1-021 GEN
Solar/Wind Harmer
0.867
316118AC1-105 GEN
Solar/Wind Harmer
0.227
315657AE1-056 GEN
Solar/Wind Harmer
2.895
315816AE2-034 GEN
Solar/Wind Harmer
0.344
3147173SINAI
Solar/Wind Harmer
0.077
3147243WELCO
Solar/Wind Harmer
0.048
971967AH1-528 GEN
Solar/Wind Harmer
11.557
970865AG2-541 GEN
Solar/Wind Harmer
2.227
316315AB2-025 C
Solar/Wind Helper
0.826
3143316POE
Solar/Wind Helper
0.688
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3151261ROARAP2
50/50
0.313
3151591KERR 2
50/50
0.27
3144293JTRSVLE
50/50
0.305
970413AG2-270 GEN
50/50
6.801
316365GEN2_N
Solar/Wind Harmer
1.155
313506AB2-031 GEN
Solar/Wind Harmer
1.049
3147043LAWRENC
Solar/Wind Harmer
0.196
3145796HORNRTN
Solar/Wind Harmer
1.268
3145796HORNRTN
Solar/Wind Harmer
0.317
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
315724AD1-057 GEN
Solar/Wind Harmer
0.907
316210AC1-098 GEN
Solar/Wind Harmer
1.821
316327AA2-057 GEN
Solar/Wind Harmer
0.289
3146263WOODLND
Solar/Wind Harmer
0.191
3146233WITAKRS
Solar/Wind Harmer
0.921
3146233WITAKRS
Solar/Wind Harmer
0.125
3138543CONSLDL
Solar/Wind Harmer
0.12
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.321
3144293JTRSVLE
50/50
0.305
3144293JTRSVLE
50/50
0.257
3152661PLYWOOD A
50/50
0.195
316181AB2-040 GEN
Solar/Wind Harmer
0.492
3145796HORNRTN
Solar/Wind Harmer
0.951
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3145593CAROLNA
Solar/Wind Harmer
0.257
3145593CAROLNA
Solar/Wind Harmer
0.257
966811AG1-552 GEN
Solar/Wind Harmer
2.785
3145593CAROLNA
Solar/Wind Harmer
0.32
3145783HORNRTN
Solar/Wind Harmer
4.428
3145783HORNRTN
Solar/Wind Harmer
3.543
3145783HORNRTN
Solar/Wind Harmer
1.107
3145783HORNRTN
Solar/Wind Harmer
0.443
316426AA2-053 GEN
Solar/Wind Harmer
0.813
316274AC1-208 GEN
Solar/Wind Harmer
1.081
961601AG1-000A GEN
Solar/Wind Harmer
3.201
316263AC1-034 GEN
Solar/Wind Harmer
6.707
3145493TOT1
Solar/Wind Harmer
0.382
3145453TOT5
Solar/Wind Harmer
0.229
3145603CNETO
Solar/Wind Harmer
0.153
3146173TUNIS
Solar/Wind Harmer
0.163
3146173TUNIS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
1.071
3145893MURPHYS
Solar/Wind Harmer
0.288
3145933PARMELE
Solar/Wind Harmer
0.262
3145933PARMELE
Solar/Wind Harmer
0.131
313527AB2-043 GEN
Solar/Wind Harmer
0.002
939181AE1-148 GEN
Solar/Wind Harmer
6.26
316065AD1-022 GEN
Solar/Wind Harmer
5.298
970323AG2-213 GEN
Solar/Wind Harmer
4.655
971775AH1-396 GEN
Solar/Wind Harmer
0.175
316034AC1-036 C
Solar/Wind Harmer
0.008
962561AG1-105 GEN
Solar/Wind Harmer
5
964791AG1-342 GEN
Solar/Wind Harmer
1.908
3146843MT LREL
Solar/Wind Harmer
0.099
3146843MT LREL
Solar/Wind Harmer
0.099
958211AF2-115 GEN
Solar/Wind Harmer
1.083
963191AG1-168 GEN
Solar/Wind Harmer
0.361
3147133PAMPLIN
Solar/Wind Harmer
0.084
3147133PAMPLIN
Solar/Wind Harmer
0.067
970099AG2-077 GEN
Solar/Wind Harmer
7.723
970933AG2-581 GEN
Solar/Wind Harmer
5.779
315742AE1-103 GEN
Solar/Wind Harmer
0.001
971741AH1-377 GEN
Solar/Wind Harmer
5.969
316222AC1-221 GEN
Solar/Wind Harmer
0.242
970301AG2-198 GEN
Solar/Wind Harmer
2.421
3144356SAPONY
Solar/Wind Helper
0.972
316240AF1-291 C
Solar/Wind Helper
0.168
961601AG1-000A GEN
Solar/Wind Harmer
12.805
316317KELFORD C
Solar/Wind Harmer
0.017
3145823KELFORD
Solar/Wind Harmer
0.177
971623AH1-311 GEN
Solar/Wind Harmer
0.353
3145543BTLEBRO
Solar/Wind Harmer
0.175
3145543BTLEBRO
Solar/Wind Harmer
0.175
316463AE2-346 GEN
Solar/Wind Harmer
0.142
316140AB2-099
Solar/Wind Harmer
0.059
962331AG1-082 GEN
Solar/Wind Harmer
1.76
3146073TAR RVR
Solar/Wind Harmer
0.165
3146083TARBORO
Solar/Wind Harmer
0.165
3146173TUNIS
Solar/Wind Harmer
0.163
957521AF2-046 GEN
Solar/Wind Harmer
11.982
961681AG1-008 GEN
Solar/Wind Harmer
11.982
3145893MURPHYS
Solar/Wind Harmer
0.268
3145893MURPHYS
Solar/Wind Harmer
0.16
3156021HOLLOMANSOL
Solar/Wind Harmer
0.689
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3145933PARMELE
Solar/Wind Harmer
0.131
966801AG1-551 GEN
Solar/Wind Harmer
1.529
316131AB2-060 GEN
Solar/Wind Harmer
0.407
964241AG1-285 GEN
Solar/Wind Harmer
8.211
3146206CASHIE
Solar/Wind Harmer
0.122
3145963POPLR C
Solar/Wind Harmer
0.118
315785AD2-033 C
Solar/Wind Harmer
0.918
970257AG2-171 GEN
Solar/Wind Harmer
3.491
959311AF2-222 GEN
Solar/Wind Harmer
9.454
315737AD1-076 GEN
Solar/Wind Harmer
1.314
971157AH1-035 GEN
Solar/Wind Harmer
1.183
963181AG1-167 GEN
Solar/Wind Harmer
0.361
3147133PAMPLIN
Solar/Wind Harmer
0.263
971193AH1-056 GEN
Solar/Wind Harmer
5.112
315614AA2-178 GEN
Solar/Wind Harmer
0.458
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.273
316478AD1-087 GEN
Solar/Wind Harmer
0.254
316486AD2-202 GEN
Solar/Wind Harmer
0.075
971683AH1-343 GEN
Solar/Wind Harmer
2.513
942461AE2-259 GEN
Solar/Wind Harmer
0
316283AC2-100 C
Solar/Wind Harmer
0.113
970909AG2-566 GEN
Solar/Wind Harmer
0.605
315839AE2-212 C
Solar/Wind Helper
0.197
316129AC1-054 GEN
Solar/Wind Harmer
0.656
971065AG2-659 GEN
Solar/Wind Harmer
7.13
3145683EARLEYS
Solar/Wind Harmer
0.166
961671AG1-007 GEN
Solar/Wind Harmer
0.025
3146083TARBORO
Solar/Wind Harmer
0.165
3145493TOT1
Solar/Wind Harmer
0.732
3146173TUNIS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
0.64
3145893MURPHYS
Solar/Wind Harmer
0.712
316494AC1-189 GEN
Solar/Wind Harmer
0.514
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3146293MARTNCO
Solar/Wind Harmer
0.122
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.122
971547AH1-271 GEN
Solar/Wind Harmer
2.614
316174AB2-169 GEN
Solar/Wind Harmer
0.003
3145963POPLR C
Solar/Wind Harmer
0.118
970685AG2-442 GEN
Solar/Wind Harmer
7.425
970401AG2-262 GEN
Solar/Wind Harmer
0.583
963171AG1-166 GEN
Solar/Wind Harmer
0.482
971563AH1-280 GEN
Solar/Wind Harmer
0.963
3145663CRESWEL
Solar/Wind Harmer
0.224
971163AH1-040 GEN
Solar/Wind Harmer
6.407
957481AF2-042 GEN
Solar/Wind Harmer
19.308
316003AC1-222 GEN
Solar/Wind Harmer
0.002
315693AD1-088 GEN
Solar/Wind Harmer
3.442
315687AD1-152 GEN
Solar/Wind Harmer
0.002
962491AG1-098 GEN
Solar/Wind Harmer
4.048
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.85
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.587
MECLTFEXP_MEC->PJM
CLTF
1.327
SIGELTFEXP_SIGE->PJM
CLTF
0.04
CPLELTFEXP_CPLE->PJM
CLTF
4.45
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.218
LAGNLTFEXP_LAGN->PJM
CLTF
2.678
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.707
TVALTFEXP_TVA->PJM
CLTF
1.336
NYPJM->LTFIMP_NY
CLTF
0.49
LGEELTFEXP_LGEE->PJM
CLTF
0.481
WECLTFEXP_WEC->PJM
CLTF
0.25

Details for 6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.07 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1046.37
MW Contribution:2.34
Bus #Bus NameTypeMW Contribution
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.272
3151621KERR 5
50/50
0.272
3151631KERR 6
50/50
0.272
3151641KERR 7
50/50
0.272
946281AF1-292 GEN
Solar/Wind Harmer
1.039
316087AB2-174 GEN
Solar/Wind Harmer
5.795
315652AC1-086 GEN
Solar/Wind Harmer
43.026
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.014
3137643SOCKMAN
Solar/Wind Harmer
-0.132
315607AA1-063A GEN
Solar/Wind Harmer
2.467
3146043SEABORD
Solar/Wind Harmer
-0.024
3146033SCOT NK
Solar/Wind Harmer
-0.084
316319Z2-044 C
Solar/Wind Harmer
1.146
970831AG2-522 GEN
Solar/Wind Harmer
10.282
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.161
961941AG1-037 GEN
Solar/Wind Harmer
0.139
3145513AHOSKIE
Solar/Wind Harmer
-0.018
316420AA1-050 GEN
Solar/Wind Harmer
2.056
316318V4-068
Solar/Wind Harmer
0.447
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
965291AG1-394 GEN
Solar/Wind Harmer
1.561
957861AF2-080 GEN
Solar/Wind Harmer
7.524
316005AA1-067
Solar/Wind Harmer
0.314
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
2.04
316239AB2-077_GEN
Solar/Wind Harmer
0.44
316238AB2-078_GEN
Solar/Wind Harmer
0.44
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
6.005
971443AH1-215 GEN
Solar/Wind Harmer
2.448
3144303KENBRDG
Solar/Wind Harmer
-0.01
315732AD1-074 GEN1
Solar/Wind Harmer
2.309
315733AD1-074 GEN2
Solar/Wind Harmer
2.309
315735AD1-075 GEN1
Solar/Wind Harmer
1.155
970683AG2-441 GEN
Solar/Wind Harmer
8.785
970681AG2-440 GEN
Solar/Wind Harmer
7.028
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
946301AF1-294 GEN
Solar/Wind Harmer
2.616
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3147043LAWRENC
50/50
3.142
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.272
3151581KERR 1
50/50
0.097
316023GEN1_S
Solar/Wind Harmer
3.898
960081AF2-299 GEN
Solar/Wind Harmer
5.218
971795AH1-408 GEN
Solar/Wind Harmer
29.85
316011AB1-132 GEN
Solar/Wind Harmer
8.002
962571AG1-106 GEN
Solar/Wind Harmer
5.498
3145796HORNRTN
Solar/Wind Harmer
-0.117
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145783HORNRTN
Solar/Wind Harmer
-0.028
315722AD1-056 GEN
Solar/Wind Harmer
2.85
316190AA2-174 GEN
Solar/Wind Harmer
0.332
316212AC1-099_GEN
Solar/Wind Harmer
1.927
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
-0.082
316359AB2-059 GEN
Solar/Wind Harmer
2.691
316049AB1-081 GEN
Solar/Wind Harmer
2.154
3142053HEARTS
Solar/Wind Harmer
0.235
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.337
316181AB2-040 GEN
Solar/Wind Harmer
5.319
3145796HORNRTN
Solar/Wind Harmer
-0.106
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3145593CAROLNA
Solar/Wind Harmer
-0.029
3145593CAROLNA
Solar/Wind Harmer
-0.029
966811AG1-552 GEN
Solar/Wind Harmer
3.248
3145593CAROLNA
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
3.324
3145783HORNRTN
Solar/Wind Harmer
2.659
3145783HORNRTN
Solar/Wind Harmer
0.831
3145783HORNRTN
Solar/Wind Harmer
0.332
316426AA2-053 GEN
Solar/Wind Harmer
2.733
316274AC1-208 GEN
Solar/Wind Harmer
2.531
961601AG1-000A GEN
Solar/Wind Harmer
8.004
316263AC1-034 GEN
Solar/Wind Harmer
9.357
3145493TOT1
Solar/Wind Harmer
0.288
3145453TOT5
Solar/Wind Harmer
0.173
3145603CNETO
Solar/Wind Harmer
0.115
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.501
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.029
3145933PARMELE
Solar/Wind Harmer
-0.015
313527AB2-043 GEN
Solar/Wind Harmer
2.404
939181AE1-148 GEN
Solar/Wind Harmer
8.303
316065AD1-022 GEN
Solar/Wind Harmer
6.44
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3151261ROARAP2
50/50
0.313
3151591KERR 2
50/50
0.272
316365GEN2_N
Solar/Wind Harmer
3.898
966621AG1-532 GEN
Solar/Wind Harmer
0.941
313506AB2-031 GEN
Solar/Wind Harmer
3.065
3147043LAWRENC
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.142
3145796HORNRTN
Solar/Wind Harmer
-0.036
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
315724AD1-057 GEN
Solar/Wind Harmer
1.567
316210AC1-098 GEN
Solar/Wind Harmer
3.469
316327AA2-057 GEN
Solar/Wind Harmer
2.181
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
0.434
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
8.106
316317KELFORD C
Solar/Wind Harmer
0.938
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3146073TAR RVR
Solar/Wind Harmer
-0.019
3146083TARBORO
Solar/Wind Harmer
-0.019
961791AG1-021 GEN
Solar/Wind Harmer
1.276
316118AC1-105 GEN
Solar/Wind Harmer
0.689
315657AE1-056 GEN
Solar/Wind Harmer
3.56
315816AE2-034 GEN
Solar/Wind Harmer
0.721
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
971967AH1-528 GEN
Solar/Wind Harmer
15.486
970865AG2-541 GEN
Solar/Wind Harmer
2.987
316123AC1-075 GEN
Solar/Wind Harmer
0.692
970165AG2-112 GEN
Solar/Wind Harmer
0.609
970163AG2-111 GEN
Solar/Wind Harmer
0.581
316315AB2-025 C
Solar/Wind Helper
0.83
3143316POE
Solar/Wind Helper
0.701
316129AC1-054 GEN
Solar/Wind Harmer
1.725
971065AG2-659 GEN
Solar/Wind Harmer
9.428
3145683EARLEYS
Solar/Wind Harmer
-0.019
961671AG1-007 GEN
Solar/Wind Harmer
0.235
3146083TARBORO
Solar/Wind Harmer
-0.019
3145493TOT1
Solar/Wind Harmer
0.552
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.071
3145893MURPHYS
Solar/Wind Harmer
0.532
316494AC1-189 GEN
Solar/Wind Harmer
1.85
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146293MARTNCO
Solar/Wind Harmer
0.092
316237AB2-079_GEN
Solar/Wind Harmer
0.44
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.431
316174AB2-169 GEN
Solar/Wind Harmer
2.09
3145963POPLR C
Solar/Wind Harmer
-0.013
970401AG2-262 GEN
Solar/Wind Harmer
0.737
970685AG2-442 GEN
Solar/Wind Harmer
9.839
963171AG1-166 GEN
Solar/Wind Harmer
1.276
971563AH1-280 GEN
Solar/Wind Harmer
1.276
3144293JTRSVLE
Adder
0.289
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.359
957481AF2-042 GEN
Solar/Wind Harmer
25.811
316003AC1-222 GEN
Solar/Wind Harmer
0.806
315693AD1-088 GEN
Solar/Wind Harmer
4.085
315687AD1-152 GEN
Solar/Wind Harmer
0.98
962491AG1-098 GEN
Solar/Wind Harmer
5.404
970323AG2-213 GEN
Solar/Wind Harmer
6.168
971775AH1-396 GEN
Solar/Wind Harmer
0.878
316034AC1-036 C
Solar/Wind Harmer
0.229
962561AG1-105 GEN
Solar/Wind Harmer
6.652
964791AG1-342 GEN
Solar/Wind Harmer
2.412
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
958211AF2-115 GEN
Solar/Wind Harmer
1.595
963191AG1-168 GEN
Solar/Wind Harmer
0.957
3144293JTRSVLE
Adder
0.289
3144293JTRSVLE
Adder
0.244
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.324
970933AG2-581 GEN
Solar/Wind Harmer
7.724
315742AE1-103 GEN
Solar/Wind Harmer
0.835
971741AH1-377 GEN
Solar/Wind Harmer
7.95
316222AC1-221 GEN
Solar/Wind Harmer
0.686
970301AG2-198 GEN
Solar/Wind Harmer
3.221
3144356SAPONY
Solar/Wind Helper
0.977
316240AF1-291 C
Solar/Wind Helper
0.173
316463AE2-346 GEN
Solar/Wind Harmer
0.3
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.315
3146173TUNIS
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.221
961681AG1-008 GEN
Solar/Wind Harmer
14.221
3145893MURPHYS
Solar/Wind Harmer
0.125
3145893MURPHYS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.293
3156081AA2-088 GEN
Solar/Wind Harmer
5.454
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.85
316131AB2-060 GEN
Solar/Wind Harmer
1.577
964241AG1-285 GEN
Solar/Wind Harmer
10.88
3146206CASHIE
Solar/Wind Harmer
-0.014
3145963POPLR C
Solar/Wind Harmer
-0.013
315785AD2-033 C
Solar/Wind Harmer
2.894
970257AG2-171 GEN
Solar/Wind Harmer
4.626
959311AF2-222 GEN
Solar/Wind Harmer
12.552
315737AD1-076 GEN
Solar/Wind Harmer
2.17
971157AH1-035 GEN
Solar/Wind Harmer
1.377
963181AG1-167 GEN
Solar/Wind Harmer
0.957
3144293JTRSVLE
Adder
0.289
3147133PAMPLIN
Solar/Wind Harmer
-0.03
971193AH1-056 GEN
Solar/Wind Harmer
5.933
315614AA2-178 GEN
Solar/Wind Harmer
0.962
316248AF1-058 C
Solar/Wind Harmer
0.264
960061AF2-297 GEN
Solar/Wind Harmer
4.385
316478AD1-087 GEN
Solar/Wind Harmer
0.72
316486AD2-202 GEN
Solar/Wind Harmer
0.211
971683AH1-343 GEN
Solar/Wind Harmer
3.369
942461AE2-259 GEN
Solar/Wind Harmer
1.119
316283AC2-100 C
Solar/Wind Harmer
0.635
970909AG2-566 GEN
Solar/Wind Harmer
0.612
315839AE2-212 C
Solar/Wind Helper
0.202
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.344
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.843
MECLTFEXP_MEC->PJM
CLTF
1.401
SIGELTFEXP_SIGE->PJM
CLTF
0.042
CPLELTFEXP_CPLE->PJM
CLTF
4.654
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.01
LAGNLTFEXP_LAGN->PJM
CLTF
2.828
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.165
TVALTFEXP_TVA->PJM
CLTF
1.41
NYPJM->LTFIMP_NY
CLTF
0.512
LGEELTFEXP_LGEE->PJM
CLTF
0.508
WECLTFEXP_WEC->PJM
CLTF
0.264

Details for 6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.99 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1045.7
MW Contribution:2.34
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3147043LAWRENC
50/50
3.142
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.272
3151581KERR 1
50/50
0.097
316023GEN1_S
Solar/Wind Harmer
3.898
960081AF2-299 GEN
Solar/Wind Harmer
5.218
971795AH1-408 GEN
Solar/Wind Harmer
29.85
316011AB1-132 GEN
Solar/Wind Harmer
8.002
962571AG1-106 GEN
Solar/Wind Harmer
5.498
3145796HORNRTN
Solar/Wind Harmer
-0.117
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145783HORNRTN
Solar/Wind Harmer
-0.028
315722AD1-056 GEN
Solar/Wind Harmer
2.85
316190AA2-174 GEN
Solar/Wind Harmer
0.332
316212AC1-099_GEN
Solar/Wind Harmer
1.927
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
-0.082
316359AB2-059 GEN
Solar/Wind Harmer
2.691
316049AB1-081 GEN
Solar/Wind Harmer
2.154
3142053HEARTS
Solar/Wind Harmer
0.235
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316129AC1-054 GEN
Solar/Wind Harmer
1.725
971065AG2-659 GEN
Solar/Wind Harmer
9.428
3145683EARLEYS
Solar/Wind Harmer
-0.019
961671AG1-007 GEN
Solar/Wind Harmer
0.235
3146083TARBORO
Solar/Wind Harmer
-0.019
3145493TOT1
Solar/Wind Harmer
0.552
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.071
3145893MURPHYS
Solar/Wind Harmer
0.532
316494AC1-189 GEN
Solar/Wind Harmer
1.85
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146293MARTNCO
Solar/Wind Harmer
0.092
316237AB2-079_GEN
Solar/Wind Harmer
0.44
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.431
316174AB2-169 GEN
Solar/Wind Harmer
2.09
3145963POPLR C
Solar/Wind Harmer
-0.013
970401AG2-262 GEN
Solar/Wind Harmer
0.737
970685AG2-442 GEN
Solar/Wind Harmer
9.839
963171AG1-166 GEN
Solar/Wind Harmer
1.276
971563AH1-280 GEN
Solar/Wind Harmer
1.276
3144293JTRSVLE
Adder
0.289
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.359
957481AF2-042 GEN
Solar/Wind Harmer
25.811
316003AC1-222 GEN
Solar/Wind Harmer
0.806
315693AD1-088 GEN
Solar/Wind Harmer
4.085
315687AD1-152 GEN
Solar/Wind Harmer
0.98
962491AG1-098 GEN
Solar/Wind Harmer
5.404
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3151261ROARAP2
50/50
0.313
3151591KERR 2
50/50
0.272
316365GEN2_N
Solar/Wind Harmer
3.898
966621AG1-532 GEN
Solar/Wind Harmer
0.941
313506AB2-031 GEN
Solar/Wind Harmer
3.065
3147043LAWRENC
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.142
3145796HORNRTN
Solar/Wind Harmer
-0.036
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
315724AD1-057 GEN
Solar/Wind Harmer
1.567
316210AC1-098 GEN
Solar/Wind Harmer
3.469
316327AA2-057 GEN
Solar/Wind Harmer
2.181
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
0.434
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
8.106
316317KELFORD C
Solar/Wind Harmer
0.938
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3146073TAR RVR
Solar/Wind Harmer
-0.019
3146083TARBORO
Solar/Wind Harmer
-0.019
316463AE2-346 GEN
Solar/Wind Harmer
0.3
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.315
3146173TUNIS
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.221
961681AG1-008 GEN
Solar/Wind Harmer
14.221
3145893MURPHYS
Solar/Wind Harmer
0.125
3145893MURPHYS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.293
3156081AA2-088 GEN
Solar/Wind Harmer
5.454
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.85
316131AB2-060 GEN
Solar/Wind Harmer
1.577
964241AG1-285 GEN
Solar/Wind Harmer
10.88
3146206CASHIE
Solar/Wind Harmer
-0.014
3145963POPLR C
Solar/Wind Harmer
-0.013
315785AD2-033 C
Solar/Wind Harmer
2.894
970257AG2-171 GEN
Solar/Wind Harmer
4.626
959311AF2-222 GEN
Solar/Wind Harmer
12.552
315737AD1-076 GEN
Solar/Wind Harmer
2.17
971157AH1-035 GEN
Solar/Wind Harmer
1.377
963181AG1-167 GEN
Solar/Wind Harmer
0.957
3144293JTRSVLE
Adder
0.289
3147133PAMPLIN
Solar/Wind Harmer
-0.03
971193AH1-056 GEN
Solar/Wind Harmer
5.933
315614AA2-178 GEN
Solar/Wind Harmer
0.962
316248AF1-058 C
Solar/Wind Harmer
0.264
960061AF2-297 GEN
Solar/Wind Harmer
4.385
316478AD1-087 GEN
Solar/Wind Harmer
0.72
316486AD2-202 GEN
Solar/Wind Harmer
0.211
971683AH1-343 GEN
Solar/Wind Harmer
3.369
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.272
3151621KERR 5
50/50
0.272
3151631KERR 6
50/50
0.272
3151641KERR 7
50/50
0.272
946281AF1-292 GEN
Solar/Wind Harmer
1.039
316087AB2-174 GEN
Solar/Wind Harmer
5.795
315652AC1-086 GEN
Solar/Wind Harmer
43.026
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.014
3137643SOCKMAN
Solar/Wind Harmer
-0.132
315607AA1-063A GEN
Solar/Wind Harmer
2.467
3146043SEABORD
Solar/Wind Harmer
-0.024
3146033SCOT NK
Solar/Wind Harmer
-0.084
316319Z2-044 C
Solar/Wind Harmer
1.146
970831AG2-522 GEN
Solar/Wind Harmer
10.282
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.161
961941AG1-037 GEN
Solar/Wind Harmer
0.139
3145513AHOSKIE
Solar/Wind Harmer
-0.018
316420AA1-050 GEN
Solar/Wind Harmer
2.056
316318V4-068
Solar/Wind Harmer
0.447
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
965291AG1-394 GEN
Solar/Wind Harmer
1.561
957861AF2-080 GEN
Solar/Wind Harmer
7.524
316005AA1-067
Solar/Wind Harmer
0.314
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
2.04
316239AB2-077_GEN
Solar/Wind Harmer
0.44
316238AB2-078_GEN
Solar/Wind Harmer
0.44
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
6.005
971443AH1-215 GEN
Solar/Wind Harmer
2.448
3144303KENBRDG
Solar/Wind Harmer
-0.01
315732AD1-074 GEN1
Solar/Wind Harmer
2.309
315733AD1-074 GEN2
Solar/Wind Harmer
2.309
315735AD1-075 GEN1
Solar/Wind Harmer
1.155
970683AG2-441 GEN
Solar/Wind Harmer
8.785
970681AG2-440 GEN
Solar/Wind Harmer
7.028
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
946301AF1-294 GEN
Solar/Wind Harmer
2.616
961791AG1-021 GEN
Solar/Wind Harmer
1.276
316118AC1-105 GEN
Solar/Wind Harmer
0.689
315657AE1-056 GEN
Solar/Wind Harmer
3.56
315816AE2-034 GEN
Solar/Wind Harmer
0.721
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
971967AH1-528 GEN
Solar/Wind Harmer
15.486
970865AG2-541 GEN
Solar/Wind Harmer
2.987
316123AC1-075 GEN
Solar/Wind Harmer
0.692
970165AG2-112 GEN
Solar/Wind Harmer
0.609
970163AG2-111 GEN
Solar/Wind Harmer
0.581
316315AB2-025 C
Solar/Wind Helper
0.83
3143316POE
Solar/Wind Helper
0.701
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.337
316181AB2-040 GEN
Solar/Wind Harmer
5.319
3145796HORNRTN
Solar/Wind Harmer
-0.106
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3145593CAROLNA
Solar/Wind Harmer
-0.029
3145593CAROLNA
Solar/Wind Harmer
-0.029
966811AG1-552 GEN
Solar/Wind Harmer
3.248
3145593CAROLNA
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
3.324
3145783HORNRTN
Solar/Wind Harmer
2.659
3145783HORNRTN
Solar/Wind Harmer
0.831
3145783HORNRTN
Solar/Wind Harmer
0.332
316426AA2-053 GEN
Solar/Wind Harmer
2.733
316274AC1-208 GEN
Solar/Wind Harmer
2.531
961601AG1-000A GEN
Solar/Wind Harmer
8.004
316263AC1-034 GEN
Solar/Wind Harmer
9.357
3145493TOT1
Solar/Wind Harmer
0.288
3145453TOT5
Solar/Wind Harmer
0.173
3145603CNETO
Solar/Wind Harmer
0.115
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.501
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.029
3145933PARMELE
Solar/Wind Harmer
-0.015
313527AB2-043 GEN
Solar/Wind Harmer
2.404
939181AE1-148 GEN
Solar/Wind Harmer
8.303
316065AD1-022 GEN
Solar/Wind Harmer
6.44
970323AG2-213 GEN
Solar/Wind Harmer
6.168
971775AH1-396 GEN
Solar/Wind Harmer
0.878
942461AE2-259 GEN
Solar/Wind Harmer
1.119
316283AC2-100 C
Solar/Wind Harmer
0.635
970909AG2-566 GEN
Solar/Wind Harmer
0.612
315839AE2-212 C
Solar/Wind Helper
0.202
316034AC1-036 C
Solar/Wind Harmer
0.229
962561AG1-105 GEN
Solar/Wind Harmer
6.652
964791AG1-342 GEN
Solar/Wind Harmer
2.412
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
958211AF2-115 GEN
Solar/Wind Harmer
1.595
963191AG1-168 GEN
Solar/Wind Harmer
0.957
3144293JTRSVLE
Adder
0.289
3144293JTRSVLE
Adder
0.244
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.324
970933AG2-581 GEN
Solar/Wind Harmer
7.724
315742AE1-103 GEN
Solar/Wind Harmer
0.835
971741AH1-377 GEN
Solar/Wind Harmer
7.95
316222AC1-221 GEN
Solar/Wind Harmer
0.686
970301AG2-198 GEN
Solar/Wind Harmer
3.221
3144356SAPONY
Solar/Wind Helper
0.977
316240AF1-291 C
Solar/Wind Helper
0.173
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.344
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.843
MECLTFEXP_MEC->PJM
CLTF
1.401
SIGELTFEXP_SIGE->PJM
CLTF
0.042
CPLELTFEXP_CPLE->PJM
CLTF
4.654
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.01
LAGNLTFEXP_LAGN->PJM
CLTF
2.828
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.165
TVALTFEXP_TVA->PJM
CLTF
1.41
NYPJM->LTFIMP_NY
CLTF
0.512
LGEELTFEXP_LGEE->PJM
CLTF
0.508
WECLTFEXP_WEC->PJM
CLTF
0.264

Details for 6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.06 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1004.83
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3147043LAWRENC
50/50
3.141
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.27
3151581KERR 1
50/50
0.096
316023GEN1_S
Solar/Wind Harmer
3.902
960081AF2-299 GEN
Solar/Wind Harmer
5.22
971795AH1-408 GEN
Solar/Wind Harmer
29.849
316011AB1-132 GEN
Solar/Wind Harmer
8.002
962571AG1-106 GEN
Solar/Wind Harmer
5.498
3145796HORNRTN
Solar/Wind Harmer
-0.117
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145783HORNRTN
Solar/Wind Harmer
-0.028
315722AD1-056 GEN
Solar/Wind Harmer
2.841
316190AA2-174 GEN
Solar/Wind Harmer
0.332
316212AC1-099_GEN
Solar/Wind Harmer
1.923
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
-0.082
3145823KELFORD
Solar/Wind Harmer
-0.02
316359AB2-059 GEN
Solar/Wind Harmer
2.674
316049AB1-081 GEN
Solar/Wind Harmer
2.14
3142053HEARTS
Solar/Wind Harmer
0.233
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316129AC1-054 GEN
Solar/Wind Harmer
1.719
971065AG2-659 GEN
Solar/Wind Harmer
9.387
3145683EARLEYS
Solar/Wind Harmer
-0.019
961671AG1-007 GEN
Solar/Wind Harmer
0.234
3146083TARBORO
Solar/Wind Harmer
-0.018
3145493TOT1
Solar/Wind Harmer
0.549
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.072
3145893MURPHYS
Solar/Wind Harmer
0.534
316494AC1-189 GEN
Solar/Wind Harmer
1.84
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146293MARTNCO
Solar/Wind Harmer
0.091
316237AB2-079_GEN
Solar/Wind Harmer
0.437
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.442
316174AB2-169 GEN
Solar/Wind Harmer
2.088
3145963POPLR C
Solar/Wind Harmer
-0.013
970685AG2-442 GEN
Solar/Wind Harmer
9.773
970401AG2-262 GEN
Solar/Wind Harmer
0.729
963171AG1-166 GEN
Solar/Wind Harmer
1.268
971563AH1-280 GEN
Solar/Wind Harmer
1.268
3144293JTRSVLE
Adder
0.287
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.436
957481AF2-042 GEN
Solar/Wind Harmer
25.486
316003AC1-222 GEN
Solar/Wind Harmer
0.792
315693AD1-088 GEN
Solar/Wind Harmer
4.021
315687AD1-152 GEN
Solar/Wind Harmer
0.963
962491AG1-098 GEN
Solar/Wind Harmer
5.32
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.321
316181AB2-040 GEN
Solar/Wind Harmer
5.319
3145796HORNRTN
Solar/Wind Harmer
-0.106
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3145593CAROLNA
Solar/Wind Harmer
-0.029
3145593CAROLNA
Solar/Wind Harmer
-0.029
966811AG1-552 GEN
Solar/Wind Harmer
3.246
3145593CAROLNA
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
3.321
3145783HORNRTN
Solar/Wind Harmer
2.657
3145783HORNRTN
Solar/Wind Harmer
0.83
3145783HORNRTN
Solar/Wind Harmer
0.332
316426AA2-053 GEN
Solar/Wind Harmer
2.732
316274AC1-208 GEN
Solar/Wind Harmer
2.525
961601AG1-000A GEN
Solar/Wind Harmer
7.953
316263AC1-034 GEN
Solar/Wind Harmer
9.296
3145493TOT1
Solar/Wind Harmer
0.286
3145453TOT5
Solar/Wind Harmer
0.172
3145603CNETO
Solar/Wind Harmer
0.115
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.502
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.029
3145933PARMELE
Solar/Wind Harmer
-0.015
313527AB2-043 GEN
Solar/Wind Harmer
2.389
939181AE1-148 GEN
Solar/Wind Harmer
8.242
316065AD1-022 GEN
Solar/Wind Harmer
6.465
970323AG2-213 GEN
Solar/Wind Harmer
6.127
971775AH1-396 GEN
Solar/Wind Harmer
0.873
316034AC1-036 C
Solar/Wind Harmer
0.227
962561AG1-105 GEN
Solar/Wind Harmer
6.584
964791AG1-342 GEN
Solar/Wind Harmer
2.385
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
958211AF2-115 GEN
Solar/Wind Harmer
1.584
963191AG1-168 GEN
Solar/Wind Harmer
0.951
3144293JTRSVLE
Adder
0.287
3144293JTRSVLE
Adder
0.242
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.194
315742AE1-103 GEN
Solar/Wind Harmer
0.847
971741AH1-377 GEN
Solar/Wind Harmer
7.846
316222AC1-221 GEN
Solar/Wind Harmer
0.662
970301AG2-198 GEN
Solar/Wind Harmer
3.182
3144356SAPONY
Solar/Wind Helper
0.972
316240AF1-291 C
Solar/Wind Helper
0.168
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3151261ROARAP2
50/50
0.313
3151591KERR 2
50/50
0.27
316365GEN2_N
Solar/Wind Harmer
3.902
966621AG1-532 GEN
Solar/Wind Harmer
0.942
313506AB2-031 GEN
Solar/Wind Harmer
3.065
3147043LAWRENC
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.142
3145796HORNRTN
Solar/Wind Harmer
-0.036
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
315724AD1-057 GEN
Solar/Wind Harmer
1.563
316210AC1-098 GEN
Solar/Wind Harmer
3.461
316327AA2-057 GEN
Solar/Wind Harmer
2.172
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
0.432
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
8.054
316317KELFORD C
Solar/Wind Harmer
0.938
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
316463AE2-346 GEN
Solar/Wind Harmer
0.3
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.318
3146073TAR RVR
Solar/Wind Harmer
-0.018
3146083TARBORO
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.25
961681AG1-008 GEN
Solar/Wind Harmer
14.25
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.297
3156081AA2-088 GEN
Solar/Wind Harmer
5.472
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.843
316131AB2-060 GEN
Solar/Wind Harmer
1.567
964241AG1-285 GEN
Solar/Wind Harmer
10.81
3146206CASHIE
Solar/Wind Harmer
-0.014
3145963POPLR C
Solar/Wind Harmer
-0.013
315785AD2-033 C
Solar/Wind Harmer
2.875
970257AG2-171 GEN
Solar/Wind Harmer
4.596
959311AF2-222 GEN
Solar/Wind Harmer
12.469
315737AD1-076 GEN
Solar/Wind Harmer
2.181
971157AH1-035 GEN
Solar/Wind Harmer
1.384
963181AG1-167 GEN
Solar/Wind Harmer
0.951
3144293JTRSVLE
Adder
0.287
3147133PAMPLIN
Solar/Wind Harmer
-0.029
971193AH1-056 GEN
Solar/Wind Harmer
5.892
315614AA2-178 GEN
Solar/Wind Harmer
0.971
316248AF1-058 C
Solar/Wind Harmer
0.26
960061AF2-297 GEN
Solar/Wind Harmer
4.312
316478AD1-087 GEN
Solar/Wind Harmer
0.709
316486AD2-202 GEN
Solar/Wind Harmer
0.208
971683AH1-343 GEN
Solar/Wind Harmer
3.31
942461AE2-259 GEN
Solar/Wind Harmer
1.111
316283AC2-100 C
Solar/Wind Harmer
0.613
970909AG2-566 GEN
Solar/Wind Harmer
0.604
315839AE2-212 C
Solar/Wind Helper
0.197
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.27
3151621KERR 5
50/50
0.27
3151631KERR 6
50/50
0.27
3151641KERR 7
50/50
0.27
946281AF1-292 GEN
Solar/Wind Harmer
1.039
316087AB2-174 GEN
Solar/Wind Harmer
5.796
315652AC1-086 GEN
Solar/Wind Harmer
43.026
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.014
3137643SOCKMAN
Solar/Wind Harmer
-0.132
315607AA1-063A GEN
Solar/Wind Harmer
2.468
3146043SEABORD
Solar/Wind Harmer
-0.024
3146033SCOT NK
Solar/Wind Harmer
-0.084
316319Z2-044 C
Solar/Wind Harmer
1.139
970831AG2-522 GEN
Solar/Wind Harmer
10.247
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.162
961941AG1-037 GEN
Solar/Wind Harmer
0.139
3145513AHOSKIE
Solar/Wind Harmer
-0.018
3145573BETHELC
Solar/Wind Harmer
-0.018
3145573BETHELC
Solar/Wind Harmer
-0.018
316318V4-068
Solar/Wind Harmer
0.448
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
316420AA1-050 GEN
Solar/Wind Harmer
2.044
965291AG1-394 GEN
Solar/Wind Harmer
1.566
957861AF2-080 GEN
Solar/Wind Harmer
7.484
316005AA1-067
Solar/Wind Harmer
0.313
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
2.03
316239AB2-077_GEN
Solar/Wind Harmer
0.437
316238AB2-078_GEN
Solar/Wind Harmer
0.437
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
6.024
971443AH1-215 GEN
Solar/Wind Harmer
2.432
3144303KENBRDG
Solar/Wind Harmer
-0.01
315732AD1-074 GEN1
Solar/Wind Harmer
2.32
315733AD1-074 GEN2
Solar/Wind Harmer
2.32
315735AD1-075 GEN1
Solar/Wind Harmer
1.16
970683AG2-441 GEN
Solar/Wind Harmer
8.726
970681AG2-440 GEN
Solar/Wind Harmer
6.981
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
946301AF1-294 GEN
Solar/Wind Harmer
2.598
961791AG1-021 GEN
Solar/Wind Harmer
1.268
316118AC1-105 GEN
Solar/Wind Harmer
0.679
315657AE1-056 GEN
Solar/Wind Harmer
3.535
315816AE2-034 GEN
Solar/Wind Harmer
0.728
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
970865AG2-541 GEN
Solar/Wind Harmer
2.933
316315AB2-025 C
Solar/Wind Helper
0.826
3143316POE
Solar/Wind Helper
0.688
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.852
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.588
MECLTFEXP_MEC->PJM
CLTF
1.327
SIGELTFEXP_SIGE->PJM
CLTF
0.04
CPLELTFEXP_CPLE->PJM
CLTF
4.451
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.221
LAGNLTFEXP_LAGN->PJM
CLTF
2.679
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.709
TVALTFEXP_TVA->PJM
CLTF
1.336
NYPJM->LTFIMP_NY
CLTF
0.49
LGEELTFEXP_LGEE->PJM
CLTF
0.481
WECLTFEXP_WEC->PJM
CLTF
0.25

Details for 6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.06 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1004.82
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3147043LAWRENC
50/50
3.141
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.27
3151581KERR 1
50/50
0.096
316023GEN1_S
Solar/Wind Harmer
3.902
960081AF2-299 GEN
Solar/Wind Harmer
5.22
971795AH1-408 GEN
Solar/Wind Harmer
29.849
316011AB1-132 GEN
Solar/Wind Harmer
8.002
962571AG1-106 GEN
Solar/Wind Harmer
5.498
3145796HORNRTN
Solar/Wind Harmer
-0.117
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145783HORNRTN
Solar/Wind Harmer
-0.028
315722AD1-056 GEN
Solar/Wind Harmer
2.841
316190AA2-174 GEN
Solar/Wind Harmer
0.332
316212AC1-099_GEN
Solar/Wind Harmer
1.923
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
-0.082
3145823KELFORD
Solar/Wind Harmer
-0.02
316359AB2-059 GEN
Solar/Wind Harmer
2.674
316049AB1-081 GEN
Solar/Wind Harmer
2.14
3142053HEARTS
Solar/Wind Harmer
0.233
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316129AC1-054 GEN
Solar/Wind Harmer
1.719
971065AG2-659 GEN
Solar/Wind Harmer
9.387
3145683EARLEYS
Solar/Wind Harmer
-0.019
961671AG1-007 GEN
Solar/Wind Harmer
0.234
3146083TARBORO
Solar/Wind Harmer
-0.018
3145493TOT1
Solar/Wind Harmer
0.549
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.072
3145893MURPHYS
Solar/Wind Harmer
0.534
316494AC1-189 GEN
Solar/Wind Harmer
1.84
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146293MARTNCO
Solar/Wind Harmer
0.091
316237AB2-079_GEN
Solar/Wind Harmer
0.437
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.442
316174AB2-169 GEN
Solar/Wind Harmer
2.088
3145963POPLR C
Solar/Wind Harmer
-0.013
970685AG2-442 GEN
Solar/Wind Harmer
9.773
970401AG2-262 GEN
Solar/Wind Harmer
0.729
963171AG1-166 GEN
Solar/Wind Harmer
1.268
971563AH1-280 GEN
Solar/Wind Harmer
1.268
3144293JTRSVLE
Adder
0.287
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.436
957481AF2-042 GEN
Solar/Wind Harmer
25.485
316003AC1-222 GEN
Solar/Wind Harmer
0.792
315693AD1-088 GEN
Solar/Wind Harmer
4.021
315687AD1-152 GEN
Solar/Wind Harmer
0.963
962491AG1-098 GEN
Solar/Wind Harmer
5.32
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.27
3151621KERR 5
50/50
0.27
3151631KERR 6
50/50
0.27
3151641KERR 7
50/50
0.27
946281AF1-292 GEN
Solar/Wind Harmer
1.039
316087AB2-174 GEN
Solar/Wind Harmer
5.796
315652AC1-086 GEN
Solar/Wind Harmer
43.026
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.014
3137643SOCKMAN
Solar/Wind Harmer
-0.132
315607AA1-063A GEN
Solar/Wind Harmer
2.468
3146043SEABORD
Solar/Wind Harmer
-0.024
3146033SCOT NK
Solar/Wind Harmer
-0.084
316319Z2-044 C
Solar/Wind Harmer
1.139
970831AG2-522 GEN
Solar/Wind Harmer
10.247
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.162
961941AG1-037 GEN
Solar/Wind Harmer
0.139
3145513AHOSKIE
Solar/Wind Harmer
-0.018
3145573BETHELC
Solar/Wind Harmer
-0.018
3145573BETHELC
Solar/Wind Harmer
-0.018
316318V4-068
Solar/Wind Harmer
0.448
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
316420AA1-050 GEN
Solar/Wind Harmer
2.044
965291AG1-394 GEN
Solar/Wind Harmer
1.566
957861AF2-080 GEN
Solar/Wind Harmer
7.484
316005AA1-067
Solar/Wind Harmer
0.313
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
2.03
316239AB2-077_GEN
Solar/Wind Harmer
0.437
316238AB2-078_GEN
Solar/Wind Harmer
0.437
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
6.024
971443AH1-215 GEN
Solar/Wind Harmer
2.432
3144303KENBRDG
Solar/Wind Harmer
-0.01
315732AD1-074 GEN1
Solar/Wind Harmer
2.32
315733AD1-074 GEN2
Solar/Wind Harmer
2.32
315735AD1-075 GEN1
Solar/Wind Harmer
1.16
970683AG2-441 GEN
Solar/Wind Harmer
8.726
970681AG2-440 GEN
Solar/Wind Harmer
6.981
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
946301AF1-294 GEN
Solar/Wind Harmer
2.598
961791AG1-021 GEN
Solar/Wind Harmer
1.268
316118AC1-105 GEN
Solar/Wind Harmer
0.679
315657AE1-056 GEN
Solar/Wind Harmer
3.535
315816AE2-034 GEN
Solar/Wind Harmer
0.728
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
970865AG2-541 GEN
Solar/Wind Harmer
2.933
316315AB2-025 C
Solar/Wind Helper
0.826
3143316POE
Solar/Wind Helper
0.688
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.321
316181AB2-040 GEN
Solar/Wind Harmer
5.319
3145796HORNRTN
Solar/Wind Harmer
-0.106
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3145593CAROLNA
Solar/Wind Harmer
-0.029
3145593CAROLNA
Solar/Wind Harmer
-0.029
966811AG1-552 GEN
Solar/Wind Harmer
3.246
3145593CAROLNA
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
3.321
3145783HORNRTN
Solar/Wind Harmer
2.657
3145783HORNRTN
Solar/Wind Harmer
0.83
3145783HORNRTN
Solar/Wind Harmer
0.332
316426AA2-053 GEN
Solar/Wind Harmer
2.732
316274AC1-208 GEN
Solar/Wind Harmer
2.525
961601AG1-000A GEN
Solar/Wind Harmer
7.953
316263AC1-034 GEN
Solar/Wind Harmer
9.296
3145493TOT1
Solar/Wind Harmer
0.286
3145453TOT5
Solar/Wind Harmer
0.172
3145603CNETO
Solar/Wind Harmer
0.115
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.502
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.029
3145933PARMELE
Solar/Wind Harmer
-0.015
313527AB2-043 GEN
Solar/Wind Harmer
2.389
939181AE1-148 GEN
Solar/Wind Harmer
8.242
316065AD1-022 GEN
Solar/Wind Harmer
6.465
970323AG2-213 GEN
Solar/Wind Harmer
6.127
971775AH1-396 GEN
Solar/Wind Harmer
0.873
316034AC1-036 C
Solar/Wind Harmer
0.227
962561AG1-105 GEN
Solar/Wind Harmer
6.584
964791AG1-342 GEN
Solar/Wind Harmer
2.385
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
958211AF2-115 GEN
Solar/Wind Harmer
1.584
963191AG1-168 GEN
Solar/Wind Harmer
0.951
3144293JTRSVLE
Adder
0.287
3144293JTRSVLE
Adder
0.242
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.194
315742AE1-103 GEN
Solar/Wind Harmer
0.847
971741AH1-377 GEN
Solar/Wind Harmer
7.846
316222AC1-221 GEN
Solar/Wind Harmer
0.662
970301AG2-198 GEN
Solar/Wind Harmer
3.182
3144356SAPONY
Solar/Wind Helper
0.972
316240AF1-291 C
Solar/Wind Helper
0.168
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3151261ROARAP2
50/50
0.313
3151591KERR 2
50/50
0.27
316365GEN2_N
Solar/Wind Harmer
3.902
966621AG1-532 GEN
Solar/Wind Harmer
0.942
313506AB2-031 GEN
Solar/Wind Harmer
3.065
3147043LAWRENC
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.142
3145796HORNRTN
Solar/Wind Harmer
-0.036
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
315724AD1-057 GEN
Solar/Wind Harmer
1.563
316210AC1-098 GEN
Solar/Wind Harmer
3.461
316327AA2-057 GEN
Solar/Wind Harmer
2.172
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
0.432
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
8.054
316317KELFORD C
Solar/Wind Harmer
0.938
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
316463AE2-346 GEN
Solar/Wind Harmer
0.3
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.318
3146073TAR RVR
Solar/Wind Harmer
-0.018
3146083TARBORO
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.25
961681AG1-008 GEN
Solar/Wind Harmer
14.25
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.297
3156081AA2-088 GEN
Solar/Wind Harmer
5.472
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.843
316131AB2-060 GEN
Solar/Wind Harmer
1.567
964241AG1-285 GEN
Solar/Wind Harmer
10.81
3146206CASHIE
Solar/Wind Harmer
-0.014
3145963POPLR C
Solar/Wind Harmer
-0.013
315785AD2-033 C
Solar/Wind Harmer
2.875
970257AG2-171 GEN
Solar/Wind Harmer
4.596
959311AF2-222 GEN
Solar/Wind Harmer
12.469
315737AD1-076 GEN
Solar/Wind Harmer
2.181
971157AH1-035 GEN
Solar/Wind Harmer
1.384
963181AG1-167 GEN
Solar/Wind Harmer
0.951
3144293JTRSVLE
Adder
0.287
3147133PAMPLIN
Solar/Wind Harmer
-0.029
971193AH1-056 GEN
Solar/Wind Harmer
5.892
315614AA2-178 GEN
Solar/Wind Harmer
0.971
316248AF1-058 C
Solar/Wind Harmer
0.26
960061AF2-297 GEN
Solar/Wind Harmer
4.312
316478AD1-087 GEN
Solar/Wind Harmer
0.709
316486AD2-202 GEN
Solar/Wind Harmer
0.208
971683AH1-343 GEN
Solar/Wind Harmer
3.31
942461AE2-259 GEN
Solar/Wind Harmer
1.111
316283AC2-100 C
Solar/Wind Harmer
0.613
970909AG2-566 GEN
Solar/Wind Harmer
0.604
315839AE2-212 C
Solar/Wind Helper
0.197
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.852
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.588
MECLTFEXP_MEC->PJM
CLTF
1.327
SIGELTFEXP_SIGE->PJM
CLTF
0.04
CPLELTFEXP_CPLE->PJM
CLTF
4.451
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.221
LAGNLTFEXP_LAGN->PJM
CLTF
2.679
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.709
TVALTFEXP_TVA->PJM
CLTF
1.336
NYPJM->LTFIMP_NY
CLTF
0.49
LGEELTFEXP_LGEE->PJM
CLTF
0.481
WECLTFEXP_WEC->PJM
CLTF
0.25

Details for 6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.05 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1004.68
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3147043LAWRENC
50/50
3.141
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.27
3151581KERR 1
50/50
0.096
316023GEN1_S
Solar/Wind Harmer
3.902
960081AF2-299 GEN
Solar/Wind Harmer
5.22
971795AH1-408 GEN
Solar/Wind Harmer
29.849
316011AB1-132 GEN
Solar/Wind Harmer
8.002
962571AG1-106 GEN
Solar/Wind Harmer
5.498
3145796HORNRTN
Solar/Wind Harmer
-0.117
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145783HORNRTN
Solar/Wind Harmer
-0.028
315722AD1-056 GEN
Solar/Wind Harmer
2.841
316190AA2-174 GEN
Solar/Wind Harmer
0.332
316212AC1-099_GEN
Solar/Wind Harmer
1.922
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
-0.082
3145823KELFORD
Solar/Wind Harmer
-0.02
316359AB2-059 GEN
Solar/Wind Harmer
2.673
316049AB1-081 GEN
Solar/Wind Harmer
2.14
3142053HEARTS
Solar/Wind Harmer
0.233
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316129AC1-054 GEN
Solar/Wind Harmer
1.719
971065AG2-659 GEN
Solar/Wind Harmer
9.387
3145683EARLEYS
Solar/Wind Harmer
-0.019
961671AG1-007 GEN
Solar/Wind Harmer
0.234
3146083TARBORO
Solar/Wind Harmer
-0.018
3145493TOT1
Solar/Wind Harmer
0.549
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.072
3145893MURPHYS
Solar/Wind Harmer
0.534
316494AC1-189 GEN
Solar/Wind Harmer
1.84
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146293MARTNCO
Solar/Wind Harmer
0.091
316237AB2-079_GEN
Solar/Wind Harmer
0.437
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.442
316174AB2-169 GEN
Solar/Wind Harmer
2.088
3145963POPLR C
Solar/Wind Harmer
-0.013
970685AG2-442 GEN
Solar/Wind Harmer
9.777
970401AG2-262 GEN
Solar/Wind Harmer
0.729
963171AG1-166 GEN
Solar/Wind Harmer
1.268
971563AH1-280 GEN
Solar/Wind Harmer
1.268
3144293JTRSVLE
Adder
0.287
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.436
957481AF2-042 GEN
Solar/Wind Harmer
25.422
316003AC1-222 GEN
Solar/Wind Harmer
0.792
315693AD1-088 GEN
Solar/Wind Harmer
4.029
315687AD1-152 GEN
Solar/Wind Harmer
0.962
962491AG1-098 GEN
Solar/Wind Harmer
5.33
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.321
316181AB2-040 GEN
Solar/Wind Harmer
5.319
3145796HORNRTN
Solar/Wind Harmer
-0.106
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3145593CAROLNA
Solar/Wind Harmer
-0.029
3145593CAROLNA
Solar/Wind Harmer
-0.029
966811AG1-552 GEN
Solar/Wind Harmer
3.246
3145593CAROLNA
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
3.321
3145783HORNRTN
Solar/Wind Harmer
2.657
3145783HORNRTN
Solar/Wind Harmer
0.83
3145783HORNRTN
Solar/Wind Harmer
0.332
316426AA2-053 GEN
Solar/Wind Harmer
2.732
316274AC1-208 GEN
Solar/Wind Harmer
2.525
961601AG1-000A GEN
Solar/Wind Harmer
7.953
316263AC1-034 GEN
Solar/Wind Harmer
9.295
3145493TOT1
Solar/Wind Harmer
0.286
3145453TOT5
Solar/Wind Harmer
0.172
3145603CNETO
Solar/Wind Harmer
0.115
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.502
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.029
3145933PARMELE
Solar/Wind Harmer
-0.015
313527AB2-043 GEN
Solar/Wind Harmer
2.389
939181AE1-148 GEN
Solar/Wind Harmer
8.243
316065AD1-022 GEN
Solar/Wind Harmer
6.465
970323AG2-213 GEN
Solar/Wind Harmer
6.129
971775AH1-396 GEN
Solar/Wind Harmer
0.873
316034AC1-036 C
Solar/Wind Harmer
0.227
962561AG1-105 GEN
Solar/Wind Harmer
6.583
964791AG1-342 GEN
Solar/Wind Harmer
2.385
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
958211AF2-115 GEN
Solar/Wind Harmer
1.585
963191AG1-168 GEN
Solar/Wind Harmer
0.951
3144293JTRSVLE
Adder
0.287
3144293JTRSVLE
Adder
0.242
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.169
315742AE1-103 GEN
Solar/Wind Harmer
0.847
971741AH1-377 GEN
Solar/Wind Harmer
7.86
316222AC1-221 GEN
Solar/Wind Harmer
0.662
970301AG2-198 GEN
Solar/Wind Harmer
3.187
3144356SAPONY
Solar/Wind Helper
0.972
316240AF1-291 C
Solar/Wind Helper
0.168
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3151261ROARAP2
50/50
0.313
3151591KERR 2
50/50
0.27
316365GEN2_N
Solar/Wind Harmer
3.902
966621AG1-532 GEN
Solar/Wind Harmer
0.942
313506AB2-031 GEN
Solar/Wind Harmer
3.065
3147043LAWRENC
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.142
3145796HORNRTN
Solar/Wind Harmer
-0.036
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
315724AD1-057 GEN
Solar/Wind Harmer
1.563
316210AC1-098 GEN
Solar/Wind Harmer
3.461
316327AA2-057 GEN
Solar/Wind Harmer
2.172
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
0.432
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
8.053
316317KELFORD C
Solar/Wind Harmer
0.938
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
316463AE2-346 GEN
Solar/Wind Harmer
0.3
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.318
3146073TAR RVR
Solar/Wind Harmer
-0.018
3146083TARBORO
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.25
961681AG1-008 GEN
Solar/Wind Harmer
14.25
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.297
3156081AA2-088 GEN
Solar/Wind Harmer
5.472
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.843
316131AB2-060 GEN
Solar/Wind Harmer
1.567
964241AG1-285 GEN
Solar/Wind Harmer
10.812
3146206CASHIE
Solar/Wind Harmer
-0.014
3145963POPLR C
Solar/Wind Harmer
-0.013
315785AD2-033 C
Solar/Wind Harmer
2.876
970257AG2-171 GEN
Solar/Wind Harmer
4.597
959311AF2-222 GEN
Solar/Wind Harmer
12.472
315737AD1-076 GEN
Solar/Wind Harmer
2.181
971157AH1-035 GEN
Solar/Wind Harmer
1.384
963181AG1-167 GEN
Solar/Wind Harmer
0.951
3144293JTRSVLE
Adder
0.287
3147133PAMPLIN
Solar/Wind Harmer
-0.029
971193AH1-056 GEN
Solar/Wind Harmer
5.895
315614AA2-178 GEN
Solar/Wind Harmer
0.971
316248AF1-058 C
Solar/Wind Harmer
0.26
960061AF2-297 GEN
Solar/Wind Harmer
4.309
316478AD1-087 GEN
Solar/Wind Harmer
0.709
316486AD2-202 GEN
Solar/Wind Harmer
0.207
971683AH1-343 GEN
Solar/Wind Harmer
3.309
942461AE2-259 GEN
Solar/Wind Harmer
1.112
316283AC2-100 C
Solar/Wind Harmer
0.612
970909AG2-566 GEN
Solar/Wind Harmer
0.605
315839AE2-212 C
Solar/Wind Helper
0.197
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.27
3151621KERR 5
50/50
0.27
3151631KERR 6
50/50
0.27
3151641KERR 7
50/50
0.27
946281AF1-292 GEN
Solar/Wind Harmer
1.039
316087AB2-174 GEN
Solar/Wind Harmer
5.796
315652AC1-086 GEN
Solar/Wind Harmer
43.026
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.014
3137643SOCKMAN
Solar/Wind Harmer
-0.132
315607AA1-063A GEN
Solar/Wind Harmer
2.468
3146043SEABORD
Solar/Wind Harmer
-0.024
3146033SCOT NK
Solar/Wind Harmer
-0.084
316319Z2-044 C
Solar/Wind Harmer
1.139
970831AG2-522 GEN
Solar/Wind Harmer
10.247
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.162
961941AG1-037 GEN
Solar/Wind Harmer
0.139
3145513AHOSKIE
Solar/Wind Harmer
-0.018
3145573BETHELC
Solar/Wind Harmer
-0.018
3145573BETHELC
Solar/Wind Harmer
-0.018
316318V4-068
Solar/Wind Harmer
0.448
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
316420AA1-050 GEN
Solar/Wind Harmer
2.044
965291AG1-394 GEN
Solar/Wind Harmer
1.566
957861AF2-080 GEN
Solar/Wind Harmer
7.483
316005AA1-067
Solar/Wind Harmer
0.313
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
2.03
316239AB2-077_GEN
Solar/Wind Harmer
0.437
316238AB2-078_GEN
Solar/Wind Harmer
0.437
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
6.024
971443AH1-215 GEN
Solar/Wind Harmer
2.433
3144303KENBRDG
Solar/Wind Harmer
-0.01
315732AD1-074 GEN1
Solar/Wind Harmer
2.32
315733AD1-074 GEN2
Solar/Wind Harmer
2.32
315735AD1-075 GEN1
Solar/Wind Harmer
1.16
970683AG2-441 GEN
Solar/Wind Harmer
8.729
970681AG2-440 GEN
Solar/Wind Harmer
6.983
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
946301AF1-294 GEN
Solar/Wind Harmer
2.6
961791AG1-021 GEN
Solar/Wind Harmer
1.268
316118AC1-105 GEN
Solar/Wind Harmer
0.679
315657AE1-056 GEN
Solar/Wind Harmer
3.537
315816AE2-034 GEN
Solar/Wind Harmer
0.728
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
970865AG2-541 GEN
Solar/Wind Harmer
2.932
316315AB2-025 C
Solar/Wind Helper
0.826
3143316POE
Solar/Wind Helper
0.688
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.85
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.587
MECLTFEXP_MEC->PJM
CLTF
1.327
SIGELTFEXP_SIGE->PJM
CLTF
0.04
CPLELTFEXP_CPLE->PJM
CLTF
4.45
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.218
LAGNLTFEXP_LAGN->PJM
CLTF
2.678
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.707
TVALTFEXP_TVA->PJM
CLTF
1.336
NYPJM->LTFIMP_NY
CLTF
0.49
LGEELTFEXP_LGEE->PJM
CLTF
0.481
WECLTFEXP_WEC->PJM
CLTF
0.25

Details for 6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2012-54_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2012-54_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:107.09 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:888.86
MW Contribution:2.08
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
1.161
3151411GASTONB
50/50
1.161
3147043LAWRENC
50/50
3.414
3151261ROARAP2
50/50
0.385
3151601KERR 3
50/50
0.246
3151581KERR 1
50/50
0.088
316023GEN1_S
Solar/Wind Harmer
4.384
960081AF2-299 GEN
Solar/Wind Harmer
5.827
316011AB1-132 GEN
Solar/Wind Harmer
10.086
962571AG1-106 GEN
Solar/Wind Harmer
6.93
3145796HORNRTN
Solar/Wind Harmer
-0.146
3145796HORNRTN
Solar/Wind Harmer
-0.044
971795AH1-408 GEN
Solar/Wind Harmer
32.769
316190AA2-174 GEN
Solar/Wind Harmer
0.426
3145783HORNRTN
Solar/Wind Harmer
-0.033
315722AD1-056 GEN
Solar/Wind Harmer
3.384
3146233WITAKRS
Solar/Wind Harmer
-0.088
316359AB2-059 GEN
Solar/Wind Harmer
2.933
316049AB1-081 GEN
Solar/Wind Harmer
2.347
3142053HEARTS
Solar/Wind Harmer
0.256
316212AC1-099_GEN
Solar/Wind Harmer
1.883
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3145543BTLEBRO
Solar/Wind Harmer
-0.017
316129AC1-054 GEN
Solar/Wind Harmer
1.824
971065AG2-659 GEN
Solar/Wind Harmer
9.783
961671AG1-007 GEN
Solar/Wind Harmer
0.231
3146083TARBORO
Solar/Wind Harmer
-0.018
3145493TOT1
Solar/Wind Harmer
0.543
3145893MURPHYS
Solar/Wind Harmer
-0.061
3145893MURPHYS
Solar/Wind Harmer
0.453
316494AC1-189 GEN
Solar/Wind Harmer
1.612
3145823KELFORD
Solar/Wind Harmer
-0.014
316237AB2-079_GEN
Solar/Wind Harmer
0.382
3146173TUNIS
Solar/Wind Harmer
-0.013
3145746EVERETS
Solar/Wind Harmer
-0.011
3145746EVERETS
Solar/Wind Harmer
-0.011
3146293MARTNCO
Solar/Wind Harmer
0.062
3145683EARLEYS
Solar/Wind Harmer
-0.01
970685AG2-442 GEN
Solar/Wind Harmer
7.649
970401AG2-262 GEN
Solar/Wind Harmer
0.56
316174AB2-169 GEN
Solar/Wind Harmer
1.265
3145963POPLR C
Solar/Wind Harmer
-0.008
963171AG1-166 GEN
Solar/Wind Harmer
0.942
971563AH1-280 GEN
Solar/Wind Harmer
0.942
3144293JTRSVLE
Adder
0.213
3151281ROARAP4
50/50
0.374
3151281ROARAP4
50/50
0.35
3151611KERR 4
50/50
0.246
3151621KERR 5
50/50
0.246
3151631KERR 6
50/50
0.246
3151641KERR 7
50/50
0.246
946281AF1-292 GEN
Solar/Wind Harmer
1.16
315652AC1-086 GEN
Solar/Wind Harmer
54.232
316087AB2-174 GEN
Solar/Wind Harmer
6.587
3145796HORNRTN
Solar/Wind Harmer
-0.141
3145796HORNRTN
Solar/Wind Harmer
-0.018
3137643SOCKMAN
Solar/Wind Harmer
-0.154
315607AA1-063A GEN
Solar/Wind Harmer
2.838
3146043SEABORD
Solar/Wind Harmer
-0.027
316319Z2-044 C
Solar/Wind Harmer
1.232
970831AG2-522 GEN
Solar/Wind Harmer
11.073
3145573BETHELC
Solar/Wind Harmer
-0.018
3145573BETHELC
Solar/Wind Harmer
-0.018
3146033SCOT NK
Solar/Wind Harmer
-0.072
965291AG1-394 GEN
Solar/Wind Harmer
1.593
316420AA1-050 GEN
Solar/Wind Harmer
1.925
316318V4-068
Solar/Wind Harmer
0.381
3145893MURPHYS
Solar/Wind Harmer
-0.041
3145893MURPHYS
Solar/Wind Harmer
-0.015
957861AF2-080 GEN
Solar/Wind Harmer
6.557
316239AB2-077_GEN
Solar/Wind Harmer
0.382
316238AB2-078_GEN
Solar/Wind Harmer
0.382
316005AA1-067
Solar/Wind Harmer
0.225
3145746EVERETS
Solar/Wind Harmer
-0.044
3145746EVERETS
Solar/Wind Harmer
-0.011
3151361ROSEMG1
50/50
1.426
3151371ROSEMS1
50/50
0.883
3151381ROSEMG2
50/50
0.668
970535AG2-341 GEN
50/50
2.078
3145796HORNRTN
Solar/Wind Harmer
-0.133
316181AB2-040 GEN
Solar/Wind Harmer
6.101
316426AA2-053 GEN
Solar/Wind Harmer
3.505
3145593CAROLNA
Solar/Wind Harmer
-0.035
3145593CAROLNA
Solar/Wind Harmer
-0.035
966811AG1-552 GEN
Solar/Wind Harmer
3.903
3145593CAROLNA
Solar/Wind Harmer
0.288
3145783HORNRTN
Solar/Wind Harmer
3.938
3145783HORNRTN
Solar/Wind Harmer
3.15
3145783HORNRTN
Solar/Wind Harmer
0.985
3145783HORNRTN
Solar/Wind Harmer
0.394
316274AC1-208 GEN
Solar/Wind Harmer
2.719
961601AG1-000A GEN
Solar/Wind Harmer
8.791
316263AC1-034 GEN
Solar/Wind Harmer
10.196
3145493TOT1
Solar/Wind Harmer
0.283
3145453TOT5
Solar/Wind Harmer
0.17
3145603CNETO
Solar/Wind Harmer
0.113
3145893MURPHYS
Solar/Wind Harmer
0.426
3145893MURPHYS
Solar/Wind Harmer
-0.027
939181AE1-148 GEN
Solar/Wind Harmer
7.468
313527AB2-043 GEN
Solar/Wind Harmer
2.093
3146173TUNIS
Solar/Wind Harmer
-0.013
3146173TUNIS
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.02
3145933PARMELE
Solar/Wind Harmer
-0.01
970323AG2-213 GEN
Solar/Wind Harmer
5.007
971775AH1-396 GEN
Solar/Wind Harmer
0.713
316034AC1-036 C
Solar/Wind Harmer
0.185
962561AG1-105 GEN
Solar/Wind Harmer
5.198
964791AG1-342 GEN
Solar/Wind Harmer
1.834
3146843MT LREL
Solar/Wind Harmer
-0.009
3146843MT LREL
Solar/Wind Harmer
-0.009
315742AE1-103 GEN
Solar/Wind Harmer
0.81
958211AF2-115 GEN
Solar/Wind Harmer
1.177
963191AG1-168 GEN
Solar/Wind Harmer
0.706
3144293JTRSVLE
Adder
0.213
3144293JTRSVLE
Adder
0.18
3147133PAMPLIN
Solar/Wind Harmer
-0.007
3147133PAMPLIN
Solar/Wind Harmer
-0.005
3144356SAPONY
Solar/Wind Helper
0.862
3151391GASTONA
50/50
1.161
3151411GASTONB
50/50
1.161
3151261ROARAP2
50/50
0.376
3151591KERR 2
50/50
0.246
316365GEN2_N
Solar/Wind Harmer
4.384
966621AG1-532 GEN
Solar/Wind Harmer
1.051
3145796HORNRTN
Solar/Wind Harmer
-0.177
3145796HORNRTN
Solar/Wind Harmer
-0.044
313506AB2-031 GEN
Solar/Wind Harmer
3.516
3147043LAWRENC
Solar/Wind Harmer
-0.024
315724AD1-057 GEN
Solar/Wind Harmer
1.861
316327AA2-057 GEN
Solar/Wind Harmer
2.326
961601AG1-000A GEN
Solar/Wind Harmer
8.903
3146233WITAKRS
Solar/Wind Harmer
0.467
3146233WITAKRS
Solar/Wind Harmer
-0.015
3138543CONSLDL
Solar/Wind Harmer
-0.015
316210AC1-098 GEN
Solar/Wind Harmer
3.389
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3146073TAR RVR
Solar/Wind Harmer
-0.018
3146083TARBORO
Solar/Wind Harmer
-0.018
3156081AA2-088 GEN
Solar/Wind Harmer
5.553
3145893MURPHYS
Solar/Wind Harmer
0.107
3145893MURPHYS
Solar/Wind Harmer
-0.015
957521AF2-046 GEN
Solar/Wind Harmer
11.382
961681AG1-008 GEN
Solar/Wind Harmer
11.382
316317KELFORD C
Solar/Wind Harmer
0.654
3145823KELFORD
Solar/Wind Harmer
-0.014
316131AB2-060 GEN
Solar/Wind Harmer
1.368
3146173TUNIS
Solar/Wind Harmer
-0.013
964241AG1-285 GEN
Solar/Wind Harmer
9.271
3145746EVERETS
Solar/Wind Harmer
-0.011
3145746EVERETS
Solar/Wind Harmer
-0.011
316463AE2-346 GEN
Solar/Wind Harmer
0.178
316140AB2-099
Solar/Wind Harmer
0.074
962331AG1-082 GEN
Solar/Wind Harmer
1.372
315785AD2-033 C
Solar/Wind Harmer
2.384
3145933PARMELE
Solar/Wind Harmer
-0.01
966801AG1-551 GEN
Solar/Wind Harmer
1.254
970257AG2-171 GEN
Solar/Wind Harmer
3.755
959311AF2-222 GEN
Solar/Wind Harmer
10.074
3145963POPLR C
Solar/Wind Harmer
-0.008
963181AG1-167 GEN
Solar/Wind Harmer
0.706
3144293JTRSVLE
Adder
0.213
3156021HOLLOMANSOL
Solar/Wind Harmer
0.928
3147133PAMPLIN
Solar/Wind Harmer
-0.021
971193AH1-056 GEN
Solar/Wind Harmer
4.188
315839AE2-212 C
Solar/Wind Helper
0.172
3145746EVERETS
Solar/Wind Harmer
-0.011
3145746EVERETS
Solar/Wind Harmer
-0.011
970181AG2-120 GEN
Solar/Wind Harmer
1.46
3145513AHOSKIE
Solar/Wind Harmer
0.096
961941AG1-037 GEN
Solar/Wind Harmer
0.082
3145513AHOSKIE
Solar/Wind Harmer
-0.011
971443AH1-215 GEN
Solar/Wind Harmer
1.994
3144303KENBRDG
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.01
970683AG2-441 GEN
Solar/Wind Harmer
6.829
970681AG2-440 GEN
Solar/Wind Harmer
5.464
946301AF1-294 GEN
Solar/Wind Harmer
1.931
961791AG1-021 GEN
Solar/Wind Harmer
0.942
316118AC1-105 GEN
Solar/Wind Harmer
0.483
315657AE1-056 GEN
Solar/Wind Harmer
2.513
316315AB2-025 C
Solar/Wind Helper
0.732
3143316POE
Solar/Wind Helper
0.597
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.796
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.185
MECLTFEXP_MEC->PJM
CLTF
1.187
SIGELTFEXP_SIGE->PJM
CLTF
0.035
CPLELTFEXP_CPLE->PJM
CLTF
4.184
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.918
LAGNLTFEXP_LAGN->PJM
CLTF
2.459
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.164
TVALTFEXP_TVA->PJM
CLTF
1.224
NYPJM->LTFIMP_NY
CLTF
0.447
LGEELTFEXP_LGEE->PJM
CLTF
0.424
WECLTFEXP_WEC->PJM
CLTF
0.221

Details for 6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 1010-2012_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 1010-2012_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.11 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:880.73
MW Contribution:2.14
Bus #Bus NameTypeMW Contribution
3151361ROSEMG1
50/50
1.448
3151371ROSEMS1
50/50
0.897
3151381ROSEMG2
50/50
0.678
970535AG2-341 GEN
50/50
2.143
3145796HORNRTN
Solar/Wind Harmer
-0.135
316181AB2-040 GEN
Solar/Wind Harmer
6.25
3145593CAROLNA
Solar/Wind Harmer
-0.036
3145593CAROLNA
Solar/Wind Harmer
-0.036
966811AG1-552 GEN
Solar/Wind Harmer
4.066
3145593CAROLNA
Solar/Wind Harmer
0.3
3145783HORNRTN
Solar/Wind Harmer
4.104
3145783HORNRTN
Solar/Wind Harmer
3.283
3145783HORNRTN
Solar/Wind Harmer
1.026
3145783HORNRTN
Solar/Wind Harmer
0.41
316426AA2-053 GEN
Solar/Wind Harmer
3.206
316274AC1-208 GEN
Solar/Wind Harmer
2.846
961601AG1-000A GEN
Solar/Wind Harmer
9.006
316263AC1-034 GEN
Solar/Wind Harmer
10.482
3145493TOT1
Solar/Wind Harmer
0.292
3145453TOT5
Solar/Wind Harmer
0.175
3145603CNETO
Solar/Wind Harmer
0.117
939181AE1-148 GEN
Solar/Wind Harmer
7.724
313527AB2-043 GEN
Solar/Wind Harmer
2.147
3145933PARMELE
Solar/Wind Harmer
-0.021
3145933PARMELE
Solar/Wind Harmer
-0.011
970323AG2-213 GEN
Solar/Wind Harmer
5.14
971775AH1-396 GEN
Solar/Wind Harmer
0.732
316034AC1-036 C
Solar/Wind Harmer
0.19
962561AG1-105 GEN
Solar/Wind Harmer
5.343
3146173TUNIS
Solar/Wind Harmer
-0.009
3146173TUNIS
Solar/Wind Harmer
-0.009
964791AG1-342 GEN
Solar/Wind Harmer
1.886
3146843MT LREL
Solar/Wind Harmer
-0.009
3146843MT LREL
Solar/Wind Harmer
-0.009
958211AF2-115 GEN
Solar/Wind Harmer
1.21
963191AG1-168 GEN
Solar/Wind Harmer
0.726
3144293JTRSVLE
Adder
0.219
3144293JTRSVLE
Adder
0.185
3147133PAMPLIN
Solar/Wind Harmer
-0.007
3147133PAMPLIN
Solar/Wind Harmer
-0.006
3145893MURPHYS
Solar/Wind Harmer
0.179
3145893MURPHYS
Solar/Wind Harmer
-0.012
3144356SAPONY
Solar/Wind Helper
0.857
316240AF1-291 C
Solar/Wind Helper
0.15
3151391GASTONA
50/50
1.178
3151411GASTONB
50/50
1.178
3147043LAWRENC
50/50
3.466
3151261ROARAP2
50/50
0.401
3151601KERR 3
50/50
0.255
3151581KERR 1
50/50
0.091
316023GEN1_S
Solar/Wind Harmer
4.421
960081AF2-299 GEN
Solar/Wind Harmer
5.909
316011AB1-132 GEN
Solar/Wind Harmer
10.237
962571AG1-106 GEN
Solar/Wind Harmer
7.034
3145796HORNRTN
Solar/Wind Harmer
-0.148
3145796HORNRTN
Solar/Wind Harmer
-0.045
971795AH1-408 GEN
Solar/Wind Harmer
33.253
3145783HORNRTN
Solar/Wind Harmer
-0.034
315722AD1-056 GEN
Solar/Wind Harmer
3.448
316190AA2-174 GEN
Solar/Wind Harmer
0.39
3146233WITAKRS
Solar/Wind Harmer
-0.091
316212AC1-099_GEN
Solar/Wind Harmer
1.994
316359AB2-059 GEN
Solar/Wind Harmer
3.015
316049AB1-081 GEN
Solar/Wind Harmer
2.413
3142053HEARTS
Solar/Wind Harmer
0.263
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3145543BTLEBRO
Solar/Wind Harmer
-0.018
316129AC1-054 GEN
Solar/Wind Harmer
1.896
971065AG2-659 GEN
Solar/Wind Harmer
10.164
961671AG1-007 GEN
Solar/Wind Harmer
0.238
3146083TARBORO
Solar/Wind Harmer
-0.019
3145493TOT1
Solar/Wind Harmer
0.559
3146263WOODLND
Solar/Wind Harmer
-0.018
3145823KELFORD
Solar/Wind Harmer
-0.016
316494AC1-189 GEN
Solar/Wind Harmer
1.673
316237AB2-079_GEN
Solar/Wind Harmer
0.392
3145746EVERETS
Solar/Wind Harmer
-0.012
3145746EVERETS
Solar/Wind Harmer
-0.012
3145683EARLEYS
Solar/Wind Harmer
-0.012
3146293MARTNCO
Solar/Wind Harmer
0.065
970685AG2-442 GEN
Solar/Wind Harmer
7.857
3146173TUNIS
Solar/Wind Harmer
-0.009
970401AG2-262 GEN
Solar/Wind Harmer
0.576
316174AB2-169 GEN
Solar/Wind Harmer
1.341
3145963POPLR C
Solar/Wind Harmer
-0.008
963171AG1-166 GEN
Solar/Wind Harmer
0.968
971563AH1-280 GEN
Solar/Wind Harmer
0.968
3144293JTRSVLE
Adder
0.219
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.19
3146206CASHIE
Solar/Wind Harmer
-0.006
971547AH1-271 GEN
Solar/Wind Harmer
1.595
3151391GASTONA
50/50
1.178
3151411GASTONB
50/50
1.178
3151261ROARAP2
50/50
0.391
3151591KERR 2
50/50
0.255
316365GEN2_N
Solar/Wind Harmer
4.421
966621AG1-532 GEN
Solar/Wind Harmer
1.066
3145796HORNRTN
Solar/Wind Harmer
-0.18
3145796HORNRTN
Solar/Wind Harmer
-0.045
313506AB2-031 GEN
Solar/Wind Harmer
3.601
3147043LAWRENC
Solar/Wind Harmer
-0.024
315724AD1-057 GEN
Solar/Wind Harmer
1.896
316327AA2-057 GEN
Solar/Wind Harmer
2.42
3146233WITAKRS
Solar/Wind Harmer
0.483
3146233WITAKRS
Solar/Wind Harmer
-0.016
3138543CONSLDL
Solar/Wind Harmer
-0.015
961601AG1-000A GEN
Solar/Wind Harmer
9.12
316210AC1-098 GEN
Solar/Wind Harmer
3.589
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3146073TAR RVR
Solar/Wind Harmer
-0.019
3146083TARBORO
Solar/Wind Harmer
-0.019
3146263WOODLND
Solar/Wind Harmer
-0.018
316317KELFORD C
Solar/Wind Harmer
0.734
3145823KELFORD
Solar/Wind Harmer
-0.016
316131AB2-060 GEN
Solar/Wind Harmer
1.403
964241AG1-285 GEN
Solar/Wind Harmer
9.513
3145746EVERETS
Solar/Wind Harmer
-0.012
3145746EVERETS
Solar/Wind Harmer
-0.012
315785AD2-033 C
Solar/Wind Harmer
2.447
3145933PARMELE
Solar/Wind Harmer
-0.011
966801AG1-551 GEN
Solar/Wind Harmer
1.322
316463AE2-346 GEN
Solar/Wind Harmer
0.167
316140AB2-099
Solar/Wind Harmer
0.07
962331AG1-082 GEN
Solar/Wind Harmer
1.289
970257AG2-171 GEN
Solar/Wind Harmer
3.855
959311AF2-222 GEN
Solar/Wind Harmer
10.344
3146173TUNIS
Solar/Wind Harmer
-0.009
3145963POPLR C
Solar/Wind Harmer
-0.008
963181AG1-167 GEN
Solar/Wind Harmer
0.726
3144293JTRSVLE
Adder
0.219
3156021HOLLOMANSOL
Solar/Wind Harmer
1.032
957521AF2-046 GEN
Solar/Wind Harmer
5.637
961681AG1-008 GEN
Solar/Wind Harmer
5.637
3147133PAMPLIN
Solar/Wind Harmer
-0.022
971193AH1-056 GEN
Solar/Wind Harmer
4.307
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
3146206CASHIE
Solar/Wind Harmer
-0.006
315839AE2-212 C
Solar/Wind Helper
0.173
3151281ROARAP4
50/50
0.39
3151281ROARAP4
50/50
0.365
3151611KERR 4
50/50
0.255
3151621KERR 5
50/50
0.255
3151631KERR 6
50/50
0.255
3151641KERR 7
50/50
0.255
946281AF1-292 GEN
Solar/Wind Harmer
1.176
315652AC1-086 GEN
Solar/Wind Harmer
55.047
316087AB2-174 GEN
Solar/Wind Harmer
6.724
3145796HORNRTN
Solar/Wind Harmer
-0.144
3145796HORNRTN
Solar/Wind Harmer
-0.018
3137643SOCKMAN
Solar/Wind Harmer
-0.159
316319Z2-044 C
Solar/Wind Harmer
1.275
970831AG2-522 GEN
Solar/Wind Harmer
11.512
3146033SCOT NK
Solar/Wind Harmer
-0.078
3145573BETHELC
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
316420AA1-050 GEN
Solar/Wind Harmer
1.988
957861AF2-080 GEN
Solar/Wind Harmer
6.801
316239AB2-077_GEN
Solar/Wind Harmer
0.392
316238AB2-078_GEN
Solar/Wind Harmer
0.392
316005AA1-067
Solar/Wind Harmer
0.236
3145746EVERETS
Solar/Wind Harmer
-0.046
3145746EVERETS
Solar/Wind Harmer
-0.012
3145746EVERETS
Solar/Wind Harmer
-0.012
3145746EVERETS
Solar/Wind Harmer
-0.012
970181AG2-120 GEN
Solar/Wind Harmer
1.534
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.012
3145683EARLEYS
Solar/Wind Harmer
-0.012
971443AH1-215 GEN
Solar/Wind Harmer
2.047
3145513AHOSKIE
Solar/Wind Harmer
0.09
961941AG1-037 GEN
Solar/Wind Harmer
0.078
3145513AHOSKIE
Solar/Wind Harmer
-0.01
3144303KENBRDG
Solar/Wind Harmer
-0.008
970683AG2-441 GEN
Solar/Wind Harmer
7.015
970681AG2-440 GEN
Solar/Wind Harmer
5.612
946301AF1-294 GEN
Solar/Wind Harmer
1.985
961791AG1-021 GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
0.497
315657AE1-056 GEN
Solar/Wind Harmer
2.584
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
3146206CASHIE
Solar/Wind Harmer
-0.006
970601AG2-382 GEN
Solar/Wind Harmer
2.791
316315AB2-025 C
Solar/Wind Helper
0.728
3143316POE
Solar/Wind Helper
0.602
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.238
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.367
MECLTFEXP_MEC->PJM
CLTF
1.247
SIGELTFEXP_SIGE->PJM
CLTF
0.037
CPLELTFEXP_CPLE->PJM
CLTF
4.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.503
LAGNLTFEXP_LAGN->PJM
CLTF
2.563
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.458
TVALTFEXP_TVA->PJM
CLTF
1.275
NYPJM->LTFIMP_NY
CLTF
0.451
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.233

Details for 6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6CLUBHSE-6OTTERDAM 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.83 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:711.43
MW Contribution:1.74
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.917
3151411GASTONB
50/50
0.917
3151261ROARAP2
50/50
0.304
3151591KERR 2
50/50
0.204
3144293JTRSVLE
50/50
0.19
316365GEN2_N
Solar/Wind Harmer
1.156
313506AB2-031 GEN
Solar/Wind Harmer
1.029
3145796HORNRTN
Solar/Wind Harmer
1.262
3145796HORNRTN
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.313
3147043LAWRENC
Solar/Wind Harmer
0.188
315724AD1-057 GEN
Solar/Wind Harmer
0.899
316210AC1-098 GEN
Solar/Wind Harmer
1.79
3146263WOODLND
Solar/Wind Harmer
0.189
316327AA2-057 GEN
Solar/Wind Harmer
0.283
3146233WITAKRS
Solar/Wind Harmer
0.904
3146233WITAKRS
Solar/Wind Harmer
0.122
3138543CONSLDL
Solar/Wind Harmer
0.118
961601AG1-000A GEN
Solar/Wind Harmer
12.598
316317KELFORD C
Solar/Wind Harmer
0.017
3145823KELFORD
Solar/Wind Harmer
0.176
971623AH1-311 GEN
Solar/Wind Harmer
0.347
3145543BTLEBRO
Solar/Wind Harmer
0.172
3145543BTLEBRO
Solar/Wind Harmer
0.172
316463AE2-346 GEN
Solar/Wind Harmer
0.142
316140AB2-099
Solar/Wind Harmer
0.059
962331AG1-082 GEN
Solar/Wind Harmer
1.758
3146173TUNIS
Solar/Wind Harmer
0.163
3146073TAR RVR
Solar/Wind Harmer
0.163
3146083TARBORO
Solar/Wind Harmer
0.163
957521AF2-046 GEN
Solar/Wind Harmer
11.941
961681AG1-008 GEN
Solar/Wind Harmer
11.941
3145893MURPHYS
Solar/Wind Harmer
0.267
3151391GASTONA
50/50
0.917
3151411GASTONB
50/50
0.917
3147043LAWRENC
50/50
3.005
3151261ROARAP2
50/50
0.311
3151601KERR 3
50/50
0.204
3151581KERR 1
50/50
0.073
3144293JTRSVLE
50/50
0.19
316023GEN1_S
Solar/Wind Harmer
1.156
960081AF2-299 GEN
Solar/Wind Harmer
3.909
971795AH1-408 GEN
Solar/Wind Harmer
22.85
316011AB1-132 GEN
Solar/Wind Harmer
6.163
962571AG1-106 GEN
Solar/Wind Harmer
4.823
3151361ROSEMG1
50/50
1.137
3151371ROSEMS1
50/50
0.704
3151381ROSEMG2
50/50
0.532
970535AG2-341 GEN
50/50
1.744
3144293JTRSVLE
50/50
0.19
3144293JTRSVLE
50/50
0.16
316181AB2-040 GEN
Solar/Wind Harmer
0.483
3145796HORNRTN
Solar/Wind Harmer
0.947
3142666NORTHAMPTON
Solar/Wind Harmer
0.313
3142666NORTHAMPTON
Solar/Wind Harmer
0.313
3142666NORTHAMPTON
Solar/Wind Harmer
0.313
3142666NORTHAMPTON
Solar/Wind Harmer
0.188
3145593CAROLNA
Solar/Wind Harmer
0.25
3145593CAROLNA
Solar/Wind Harmer
0.25
966811AG1-552 GEN
Solar/Wind Harmer
2.71
3145593CAROLNA
Solar/Wind Harmer
0.311
3145783HORNRTN
Solar/Wind Harmer
4.313
3145783HORNRTN
Solar/Wind Harmer
3.451
3145783HORNRTN
Solar/Wind Harmer
1.078
3145783HORNRTN
Solar/Wind Harmer
0.431
316426AA2-053 GEN
Solar/Wind Harmer
0.793
316274AC1-208 GEN
Solar/Wind Harmer
1.059
961601AG1-000A GEN
Solar/Wind Harmer
3.149
316263AC1-034 GEN
Solar/Wind Harmer
6.585
3146173TUNIS
Solar/Wind Harmer
0.163
3146173TUNIS
Solar/Wind Harmer
0.163
3145493TOT1
Solar/Wind Harmer
0.377
3145453TOT5
Solar/Wind Harmer
0.226
3145603CNETO
Solar/Wind Harmer
0.151
3145893MURPHYS
Solar/Wind Harmer
1.067
3145893MURPHYS
Solar/Wind Harmer
0.287
3145933PARMELE
Solar/Wind Harmer
0.263
3145933PARMELE
Solar/Wind Harmer
0.131
316065AD1-022 GEN
Solar/Wind Harmer
5.42
939181AE1-148 GEN
Solar/Wind Harmer
4.721
313527AB2-043 GEN
Solar/Wind Harmer
0.001
315742AE1-103 GEN
Solar/Wind Harmer
0.001
970323AG2-213 GEN
Solar/Wind Harmer
3.223
971775AH1-396 GEN
Solar/Wind Harmer
0.121
316034AC1-036 C
Solar/Wind Harmer
0.005
962561AG1-105 GEN
Solar/Wind Harmer
3.364
964791AG1-342 GEN
Solar/Wind Harmer
1.25
3151281ROARAP4
50/50
0.303
3151281ROARAP4
50/50
0.283
3151151S HAMPT1
50/50
0.289
3151611KERR 4
50/50
0.204
3151621KERR 5
50/50
0.204
3151631KERR 6
50/50
0.204
3151641KERR 7
50/50
0.204
316087AB2-174 GEN
Solar/Wind Harmer
0.01
315652AC1-086 GEN
Solar/Wind Harmer
37.288
3145796HORNRTN
Solar/Wind Harmer
1.01
3145796HORNRTN
Solar/Wind Harmer
0.126
3137643SOCKMAN
Solar/Wind Harmer
1.149
315607AA1-063A GEN
Solar/Wind Harmer
0.435
3146043SEABORD
Solar/Wind Harmer
0.207
3146033SCOT NK
Solar/Wind Harmer
0.741
316319Z2-044 C
Solar/Wind Harmer
0
3145683EARLEYS
Solar/Wind Harmer
0.333
3145683EARLEYS
Solar/Wind Harmer
0.166
3145683EARLEYS
Solar/Wind Harmer
0.166
3145513AHOSKIE
Solar/Wind Harmer
0.345
3145796HORNRTN
Solar/Wind Harmer
1.041
3145796HORNRTN
Solar/Wind Harmer
0.315
3145783HORNRTN
Solar/Wind Harmer
0.242
315722AD1-056 GEN
Solar/Wind Harmer
1.516
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
0.998
3146263WOODLND
Solar/Wind Harmer
0.189
3146233WITAKRS
Solar/Wind Harmer
0.716
3145823KELFORD
Solar/Wind Harmer
0.176
316359AB2-059 GEN
Solar/Wind Harmer
0.622
316049AB1-081 GEN
Solar/Wind Harmer
0.992
3142053HEARTS
Solar/Wind Harmer
0.305
3145543BTLEBRO
Solar/Wind Harmer
0.172
3145543BTLEBRO
Solar/Wind Harmer
0.138
3145683EARLEYS
Solar/Wind Harmer
0.166
3146173TUNIS
Solar/Wind Harmer
0.163
961671AG1-007 GEN
Solar/Wind Harmer
0.025
3146083TARBORO
Solar/Wind Harmer
0.163
3145493TOT1
Solar/Wind Harmer
0.723
3145893MURPHYS
Solar/Wind Harmer
0.637
3145893MURPHYS
Solar/Wind Harmer
0.709
316129AC1-054 GEN
Solar/Wind Harmer
0.569
316494AC1-189 GEN
Solar/Wind Harmer
0.51
971065AG2-659 GEN
Solar/Wind Harmer
6.081
3145746EVERETS
Solar/Wind Harmer
0.137
3145746EVERETS
Solar/Wind Harmer
0.137
3146293MARTNCO
Solar/Wind Harmer
0.122
3146206CASHIE
Solar/Wind Harmer
0.125
971547AH1-271 GEN
Solar/Wind Harmer
2.665
316174AB2-169 GEN
Solar/Wind Harmer
0.003
3145963POPLR C
Solar/Wind Harmer
0.119
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3145663CRESWEL
Solar/Wind Harmer
0.236
971163AH1-040 GEN
Solar/Wind Harmer
6.734
970685AG2-442 GEN
Solar/Wind Harmer
4.905
970401AG2-262 GEN
Solar/Wind Harmer
0.382
3130156CHOWAN
Solar/Wind Harmer
0.061
963171AG1-166 GEN
Solar/Wind Harmer
0.3
971563AH1-280 GEN
Solar/Wind Harmer
0.601
3145513AHOSKIE
Solar/Wind Harmer
0.165
3145573BETHELC
Solar/Wind Harmer
0.163
3145573BETHELC
Solar/Wind Harmer
0.163
970831AG2-522 GEN
Solar/Wind Harmer
6.862
3145893MURPHYS
Solar/Wind Harmer
0.43
3145893MURPHYS
Solar/Wind Harmer
0.159
316420AA1-050 GEN
Solar/Wind Harmer
0.005
965291AG1-394 GEN
Solar/Wind Harmer
0.694
957861AF2-080 GEN
Solar/Wind Harmer
6.503
316005AA1-067
Solar/Wind Harmer
0.147
3145746EVERETS
Solar/Wind Harmer
0.545
3145746EVERETS
Solar/Wind Harmer
0.137
3145746EVERETS
Solar/Wind Harmer
0.137
3145746EVERETS
Solar/Wind Harmer
0.137
970181AG2-120 GEN
Solar/Wind Harmer
1.706
3146206CASHIE
Solar/Wind Harmer
0.125
970601AG2-382 GEN
Solar/Wind Harmer
4.665
315732AD1-074 GEN1
Solar/Wind Harmer
0.604
315733AD1-074 GEN2
Solar/Wind Harmer
0.604
315735AD1-075 GEN1
Solar/Wind Harmer
0.303
3130546PLYMOUTH
Solar/Wind Harmer
0.102
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
315816AE2-034 GEN
Solar/Wind Harmer
0.361
971443AH1-215 GEN
Solar/Wind Harmer
1.284
3144303KENBRDG
Solar/Wind Harmer
0.06
970683AG2-441 GEN
Solar/Wind Harmer
4.379
970681AG2-440 GEN
Solar/Wind Harmer
3.503
3130156CHOWAN
Solar/Wind Harmer
0.061
3130156CHOWAN
Solar/Wind Harmer
0.061
946301AF1-294 GEN
Solar/Wind Harmer
1.112
961791AG1-021 GEN
Solar/Wind Harmer
0.541
316315AB2-025 C
Solar/Wind Helper
0.806
3143316POE
Solar/Wind Helper
0.622
3146843MT LREL
Solar/Wind Harmer
0.065
3146843MT LREL
Solar/Wind Harmer
0.065
3146376EDENTON
Solar/Wind Harmer
0.271
3146376EDENTON
Solar/Wind Harmer
0.271
958211AF2-115 GEN
Solar/Wind Harmer
0.676
963191AG1-168 GEN
Solar/Wind Harmer
0.225
3144356SAPONY
Solar/Wind Helper
0.949
3145893MURPHYS
Solar/Wind Harmer
0.159
3156021HOLLOMANSOL
Solar/Wind Harmer
0.695
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
3145746EVERETS
Solar/Wind Harmer
0.137
3145746EVERETS
Solar/Wind Harmer
0.137
3145933PARMELE
Solar/Wind Harmer
0.131
966801AG1-551 GEN
Solar/Wind Harmer
1.53
3146206CASHIE
Solar/Wind Harmer
0.125
3145963POPLR C
Solar/Wind Harmer
0.119
315737AD1-076 GEN
Solar/Wind Harmer
1.353
971157AH1-035 GEN
Solar/Wind Harmer
1.222
316131AB2-060 GEN
Solar/Wind Harmer
0.302
964241AG1-285 GEN
Solar/Wind Harmer
5.993
315614AA2-178 GEN
Solar/Wind Harmer
0.482
315785AD2-033 C
Solar/Wind Harmer
0.646
970257AG2-171 GEN
Solar/Wind Harmer
2.417
959311AF2-222 GEN
Solar/Wind Harmer
6.465
3146376EDENTON
Solar/Wind Harmer
0.061
963181AG1-167 GEN
Solar/Wind Harmer
0.225
315839AE2-212 C
Solar/Wind Helper
0.177
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.202
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.915
MECLTFEXP_MEC->PJM
CLTF
1.103
SIGELTFEXP_SIGE->PJM
CLTF
0.033
CPLELTFEXP_CPLE->PJM
CLTF
4.021
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.068
LAGNLTFEXP_LAGN->PJM
CLTF
2.305
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.741
TVALTFEXP_TVA->PJM
CLTF
1.146
NYPJM->LTFIMP_NY
CLTF
0.422
LGEELTFEXP_LGEE->PJM
CLTF
0.392
WECLTFEXP_WEC->PJM
CLTF
0.205

Details for 6EDMONSON-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6SEDGE HILL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.9 %
Rating:997.0 MVA
Rating Type:C
MVA to Mitigate:1035.9
MW Contribution:2.75
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
13.015
3144293JTRSVLE
50/50
0.686
3151601KERR 3
50/50
0.363
3151581KERR 1
50/50
0.13
3151931BEARGRDN S1
50/50
1.418
3151911BEARGRDN G1
50/50
1.099
315687AD1-152 GEN
Solar/Wind Harmer
9.7
957481AF2-042 GEN
Solar/Wind Harmer
201.833
315693AD1-088 GEN
Solar/Wind Harmer
29.361
962491AG1-098 GEN
Solar/Wind Harmer
38.734
3146926FARMVIL
Solar/Wind Harmer
-0.019
316322AB2-045
Solar/Wind Harmer
0.788
3146776BUCKING
Solar/Wind Harmer
-0.009
963171AG1-166 GEN
Solar/Wind Harmer
2.851
971563AH1-280 GEN
Solar/Wind Harmer
2.851
970685AG2-442 GEN
Solar/Wind Harmer
18.365
971065AG2-659 GEN
Solar/Wind Harmer
7.646
972003AH1-546 GEN
Solar/Wind Harmer
7.552
316129AC1-054 GEN
Solar/Wind Harmer
1.263
316237AB2-079_GEN
Solar/Wind Harmer
0.417
971377AH1-170 GEN
Solar/Wind Harmer
1.453
3147623JAMES R
Solar/Wind Harmer
0.18
970937AG2-583 GEN
Solar/Wind Harmer
7.798
316336AC2-165 C
Solar/Wind Harmer
1.386
3147043LAWRENC
Adder
0.584
3143336POWHATN
Solar/Wind Harmer
0.814
316003AC1-222 GEN
Solar/Wind Helper
1.516
3147123OTTER R
Solar/Wind Helper
0.083
3147312GRETNA
Solar/Wind Helper
0.093
3146802CHATHAM
Solar/Wind Helper
0.087
270016AE1-250 BESS
Solar/Wind Helper
0.416
3144293JTRSVLE
50/50
0.686
3144293JTRSVLE
50/50
0.578
970535AG2-341 GEN
50/50
2.746
970099AG2-077 GEN
Solar/Wind Harmer
80.733
970933AG2-581 GEN
Solar/Wind Harmer
59.456
971741AH1-377 GEN
Solar/Wind Harmer
54.374
970301AG2-198 GEN
Solar/Wind Harmer
21.608
3147133PAMPLIN
Solar/Wind Harmer
-0.024
3147133PAMPLIN
Solar/Wind Harmer
-0.019
3146776BUCKING
Solar/Wind Harmer
-0.093
3146776BUCKING
Solar/Wind Harmer
-0.008
958211AF2-115 GEN
Solar/Wind Harmer
3.564
963191AG1-168 GEN
Solar/Wind Harmer
2.139
316034AC1-036 C
Solar/Wind Harmer
0.354
970323AG2-213 GEN
Solar/Wind Harmer
9.517
971775AH1-396 GEN
Solar/Wind Harmer
1.355
939181AE1-148 GEN
Solar/Wind Harmer
10.582
313527AB2-043 GEN
Solar/Wind Harmer
2.387
971489AH1-241 GEN
Solar/Wind Harmer
6.899
315821AE2-092 GEN
Solar/Wind Harmer
1.789
316222AC1-221 GEN
Solar/Wind Helper
1.594
316197AC1-042 GEN
Solar/Wind Helper
0.109
270013AE1-250 PV
Solar/Wind Helper
0.416
3146843MT LREL
Solar/Wind Helper
0.112
3146843MT LREL
Solar/Wind Helper
0.112
970413AG2-270 GEN
50/50
56.795
3144293JTRSVLE
50/50
0.686
3151591KERR 2
50/50
0.363
3151921BEARGRDN G2
50/50
1.099
316478AD1-087 GEN
Solar/Wind Harmer
5.94
316486AD2-202 GEN
Solar/Wind Harmer
1.74
970909AG2-566 GEN
Solar/Wind Harmer
4.103
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.165
3147133PAMPLIN
Solar/Wind Harmer
-0.075
971193AH1-056 GEN
Solar/Wind Harmer
15.059
3146776BUCKING
Solar/Wind Harmer
-0.008
963181AG1-167 GEN
Solar/Wind Harmer
2.139
959311AF2-222 GEN
Solar/Wind Harmer
20.462
970257AG2-171 GEN
Solar/Wind Harmer
7.138
315785AD2-033 C
Solar/Wind Harmer
4.14
964241AG1-285 GEN
Solar/Wind Harmer
12.684
316131AB2-060 GEN
Solar/Wind Harmer
1.616
970221AG2-151 GEN
Solar/Wind Harmer
7.267
3147043LAWRENC
Solar/Wind Harmer
-0.004
316313AB2-026
Solar/Wind Harmer
0.185
316258AE1-075 C
Solar/Wind Harmer
0.166
316405AF2-144 C
Solar/Wind Harmer
0.176
3143336POWHATN
Solar/Wind Harmer
0.692
316248AF1-058 C
Solar/Wind Helper
0.503
316283AC2-100 C
Solar/Wind Helper
1.45
3147312GRETNA
Solar/Wind Helper
0.023
3151541CLOVER2
50/50
12.953
3151611KERR 4
50/50
0.363
3151621KERR 5
50/50
0.363
3151631KERR 6
50/50
0.363
3151641KERR 7
50/50
0.363
972205AH1-687 GEN
50/50
5.359
971967AH1-528 GEN
Solar/Wind Harmer
119.231
970285AG2-188 GEN
Solar/Wind Harmer
22.292
971845AH1-439 GEN
Solar/Wind Harmer
12.82
315657AE1-056 GEN
Solar/Wind Harmer
9.035
946301AF1-294 GEN
Solar/Wind Harmer
5.845
961791AG1-021 GEN
Solar/Wind Harmer
2.851
970683AG2-441 GEN
Solar/Wind Harmer
16.398
970681AG2-440 GEN
Solar/Wind Harmer
13.118
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.717
316239AB2-077_GEN
Solar/Wind Harmer
0.417
316238AB2-078_GEN
Solar/Wind Harmer
0.417
970831AG2-522 GEN
Solar/Wind Harmer
6.725
971447AH1-217 GEN
Solar/Wind Harmer
3.924
270494AE1-108_GEN
Solar/Wind Harmer
2.176
3147173SINAI
Solar/Wind Helper
0.374
3147243WELCO
Solar/Wind Helper
0.234
316123AC1-075 GEN
Solar/Wind Helper
1.587
316118AC1-105 GEN
Solar/Wind Helper
0.947
270455AD2-022 GEN
Solar/Wind Helper
0.922
270457AD2-023 GEN
Solar/Wind Helper
0.608
VTFLTFEXP_VFT->PJM
CMTX
1.612
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.251
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.119
G-007ALTFEXP_G-007A->PJM
CMTX
0.61
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.686
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.756
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.372
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
2.242

Details for 6EDMONSON-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6SEDGE HILL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.06 %
Rating:997.0 MVA
Rating Type:C
MVA to Mitigate:1017.58
MW Contribution:2.74
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
13.001
3144293JTRSVLE
50/50
0.685
3151601KERR 3
50/50
0.362
3151581KERR 1
50/50
0.129
3151931BEARGRDN S1
50/50
1.421
3151911BEARGRDN G1
50/50
1.101
315687AD1-152 GEN
Solar/Wind Harmer
9.69
957481AF2-042 GEN
Solar/Wind Harmer
201.613
3144293JTRSVLE
50/50
0.685
3144293JTRSVLE
50/50
0.577
970535AG2-341 GEN
50/50
2.737
970099AG2-077 GEN
Solar/Wind Harmer
80.645
970933AG2-581 GEN
Solar/Wind Harmer
59.392
971741AH1-377 GEN
Solar/Wind Harmer
54.323
970301AG2-198 GEN
Solar/Wind Harmer
21.589
3147133PAMPLIN
Solar/Wind Harmer
-0.024
3147133PAMPLIN
Solar/Wind Harmer
-0.019
3146776BUCKING
Solar/Wind Harmer
-0.093
3146776BUCKING
Solar/Wind Harmer
-0.008
958211AF2-115 GEN
Solar/Wind Harmer
3.559
963191AG1-168 GEN
Solar/Wind Harmer
2.135
316034AC1-036 C
Solar/Wind Harmer
0.353
970323AG2-213 GEN
Solar/Wind Harmer
9.495
971775AH1-396 GEN
Solar/Wind Harmer
1.352
939181AE1-148 GEN
Solar/Wind Harmer
10.548
313527AB2-043 GEN
Solar/Wind Harmer
2.378
971489AH1-241 GEN
Solar/Wind Harmer
6.911
315821AE2-092 GEN
Solar/Wind Harmer
1.794
316222AC1-221 GEN
Solar/Wind Helper
1.608
316197AC1-042 GEN
Solar/Wind Helper
0.109
270013AE1-250 PV
Solar/Wind Helper
0.421
3146843MT LREL
Solar/Wind Helper
0.113
3146843MT LREL
Solar/Wind Helper
0.113
315693AD1-088 GEN
Solar/Wind Harmer
29.329
962491AG1-098 GEN
Solar/Wind Harmer
38.693
3146926FARMVIL
Solar/Wind Harmer
-0.019
316322AB2-045
Solar/Wind Harmer
0.788
3146776BUCKING
Solar/Wind Harmer
-0.009
963171AG1-166 GEN
Solar/Wind Harmer
2.847
971563AH1-280 GEN
Solar/Wind Harmer
2.847
970685AG2-442 GEN
Solar/Wind Harmer
18.33
971065AG2-659 GEN
Solar/Wind Harmer
7.623
972003AH1-546 GEN
Solar/Wind Harmer
7.562
316129AC1-054 GEN
Solar/Wind Harmer
1.259
316237AB2-079_GEN
Solar/Wind Harmer
0.415
971377AH1-170 GEN
Solar/Wind Harmer
1.456
3147623JAMES R
Solar/Wind Harmer
0.18
970937AG2-583 GEN
Solar/Wind Harmer
7.825
316336AC2-165 C
Solar/Wind Harmer
1.396
3147043LAWRENC
Adder
0.584
3143336POWHATN
Solar/Wind Harmer
0.821
316003AC1-222 GEN
Solar/Wind Helper
1.523
3147123OTTER R
Solar/Wind Helper
0.083
3147312GRETNA
Solar/Wind Helper
0.093
3146802CHATHAM
Solar/Wind Helper
0.087
270016AE1-250 BESS
Solar/Wind Helper
0.421
970413AG2-270 GEN
50/50
56.734
3144293JTRSVLE
50/50
0.685
3151591KERR 2
50/50
0.362
3151921BEARGRDN G2
50/50
1.101
316478AD1-087 GEN
Solar/Wind Harmer
5.933
316486AD2-202 GEN
Solar/Wind Harmer
1.738
970909AG2-566 GEN
Solar/Wind Harmer
4.099
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.161
3147133PAMPLIN
Solar/Wind Harmer
-0.075
971193AH1-056 GEN
Solar/Wind Harmer
15.038
3146776BUCKING
Solar/Wind Harmer
-0.008
963181AG1-167 GEN
Solar/Wind Harmer
2.135
959311AF2-222 GEN
Solar/Wind Harmer
20.417
970257AG2-171 GEN
Solar/Wind Harmer
7.122
315785AD2-033 C
Solar/Wind Harmer
4.129
964241AG1-285 GEN
Solar/Wind Harmer
12.645
316131AB2-060 GEN
Solar/Wind Harmer
1.61
970221AG2-151 GEN
Solar/Wind Harmer
7.28
3147043LAWRENC
Solar/Wind Harmer
-0.004
316313AB2-026
Solar/Wind Harmer
0.187
316258AE1-075 C
Solar/Wind Harmer
0.168
316405AF2-144 C
Solar/Wind Harmer
0.177
3143336POWHATN
Solar/Wind Harmer
0.698
316248AF1-058 C
Solar/Wind Helper
0.505
316283AC2-100 C
Solar/Wind Helper
1.462
3147312GRETNA
Solar/Wind Helper
0.023
3151541CLOVER2
50/50
12.939
3151611KERR 4
50/50
0.362
3151621KERR 5
50/50
0.362
3151631KERR 6
50/50
0.362
3151641KERR 7
50/50
0.362
972205AH1-687 GEN
50/50
5.369
971967AH1-528 GEN
Solar/Wind Harmer
119.102
970285AG2-188 GEN
Solar/Wind Harmer
22.288
971845AH1-439 GEN
Solar/Wind Harmer
12.819
315657AE1-056 GEN
Solar/Wind Harmer
9.023
946301AF1-294 GEN
Solar/Wind Harmer
5.836
961791AG1-021 GEN
Solar/Wind Harmer
2.847
970683AG2-441 GEN
Solar/Wind Harmer
16.366
970681AG2-440 GEN
Solar/Wind Harmer
13.093
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.708
316239AB2-077_GEN
Solar/Wind Harmer
0.415
316238AB2-078_GEN
Solar/Wind Harmer
0.415
970831AG2-522 GEN
Solar/Wind Harmer
6.705
971447AH1-217 GEN
Solar/Wind Harmer
3.932
270494AE1-108_GEN
Solar/Wind Harmer
2.178
3147173SINAI
Solar/Wind Helper
0.376
3147243WELCO
Solar/Wind Helper
0.235
316123AC1-075 GEN
Solar/Wind Helper
1.594
316118AC1-105 GEN
Solar/Wind Helper
0.953
270455AD2-022 GEN
Solar/Wind Helper
0.936
270457AD2-023 GEN
Solar/Wind Helper
0.617
VTFLTFEXP_VFT->PJM
CMTX
1.784
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.284
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.201
G-007ALTFEXP_G-007A->PJM
CMTX
0.675
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.798
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.769
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.415
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
2.312

Details for 6EDMONSON-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6SEDGE HILL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.05 %
Rating:997.0 MVA
Rating Type:C
MVA to Mitigate:1017.41
MW Contribution:2.74
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.685
3144293JTRSVLE
50/50
0.577
970535AG2-341 GEN
50/50
2.737
970099AG2-077 GEN
Solar/Wind Harmer
80.645
970933AG2-581 GEN
Solar/Wind Harmer
59.392
971741AH1-377 GEN
Solar/Wind Harmer
54.323
970301AG2-198 GEN
Solar/Wind Harmer
21.589
3147133PAMPLIN
Solar/Wind Harmer
-0.024
3147133PAMPLIN
Solar/Wind Harmer
-0.019
3146776BUCKING
Solar/Wind Harmer
-0.093
3146776BUCKING
Solar/Wind Harmer
-0.008
958211AF2-115 GEN
Solar/Wind Harmer
3.559
963191AG1-168 GEN
Solar/Wind Harmer
2.135
316034AC1-036 C
Solar/Wind Harmer
0.353
970323AG2-213 GEN
Solar/Wind Harmer
9.495
971775AH1-396 GEN
Solar/Wind Harmer
1.352
939181AE1-148 GEN
Solar/Wind Harmer
10.548
313527AB2-043 GEN
Solar/Wind Harmer
2.378
971489AH1-241 GEN
Solar/Wind Harmer
6.911
315821AE2-092 GEN
Solar/Wind Harmer
1.794
316222AC1-221 GEN
Solar/Wind Helper
1.608
316197AC1-042 GEN
Solar/Wind Helper
0.109
270013AE1-250 PV
Solar/Wind Helper
0.421
3146843MT LREL
Solar/Wind Helper
0.113
3146843MT LREL
Solar/Wind Helper
0.113
3151531CLOVER1
50/50
13.001
3144293JTRSVLE
50/50
0.685
3151601KERR 3
50/50
0.362
3151581KERR 1
50/50
0.129
3151931BEARGRDN S1
50/50
1.421
3151911BEARGRDN G1
50/50
1.101
315687AD1-152 GEN
Solar/Wind Harmer
9.69
957481AF2-042 GEN
Solar/Wind Harmer
201.613
315693AD1-088 GEN
Solar/Wind Harmer
29.329
962491AG1-098 GEN
Solar/Wind Harmer
38.693
3146926FARMVIL
Solar/Wind Harmer
-0.019
316322AB2-045
Solar/Wind Harmer
0.788
3146776BUCKING
Solar/Wind Harmer
-0.009
963171AG1-166 GEN
Solar/Wind Harmer
2.847
971563AH1-280 GEN
Solar/Wind Harmer
2.847
970685AG2-442 GEN
Solar/Wind Harmer
18.33
971065AG2-659 GEN
Solar/Wind Harmer
7.623
972003AH1-546 GEN
Solar/Wind Harmer
7.562
316129AC1-054 GEN
Solar/Wind Harmer
1.259
316237AB2-079_GEN
Solar/Wind Harmer
0.415
971377AH1-170 GEN
Solar/Wind Harmer
1.456
3147623JAMES R
Solar/Wind Harmer
0.18
970937AG2-583 GEN
Solar/Wind Harmer
7.825
316336AC2-165 C
Solar/Wind Harmer
1.396
3147043LAWRENC
Adder
0.584
3143336POWHATN
Solar/Wind Harmer
0.821
316003AC1-222 GEN
Solar/Wind Helper
1.523
3147123OTTER R
Solar/Wind Helper
0.083
3147312GRETNA
Solar/Wind Helper
0.093
3146802CHATHAM
Solar/Wind Helper
0.087
270016AE1-250 BESS
Solar/Wind Helper
0.421
970413AG2-270 GEN
50/50
56.734
3144293JTRSVLE
50/50
0.685
3151591KERR 2
50/50
0.362
3151921BEARGRDN G2
50/50
1.101
316478AD1-087 GEN
Solar/Wind Harmer
5.933
316486AD2-202 GEN
Solar/Wind Harmer
1.738
970909AG2-566 GEN
Solar/Wind Harmer
4.099
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.161
3147133PAMPLIN
Solar/Wind Harmer
-0.075
971193AH1-056 GEN
Solar/Wind Harmer
15.038
3146776BUCKING
Solar/Wind Harmer
-0.008
963181AG1-167 GEN
Solar/Wind Harmer
2.135
959311AF2-222 GEN
Solar/Wind Harmer
20.417
970257AG2-171 GEN
Solar/Wind Harmer
7.122
315785AD2-033 C
Solar/Wind Harmer
4.129
964241AG1-285 GEN
Solar/Wind Harmer
12.645
316131AB2-060 GEN
Solar/Wind Harmer
1.61
970221AG2-151 GEN
Solar/Wind Harmer
7.28
3147043LAWRENC
Solar/Wind Harmer
-0.004
316313AB2-026
Solar/Wind Harmer
0.187
316258AE1-075 C
Solar/Wind Harmer
0.168
316405AF2-144 C
Solar/Wind Harmer
0.177
3143336POWHATN
Solar/Wind Harmer
0.698
316248AF1-058 C
Solar/Wind Helper
0.505
316283AC2-100 C
Solar/Wind Helper
1.462
3147312GRETNA
Solar/Wind Helper
0.023
3151541CLOVER2
50/50
12.939
3151611KERR 4
50/50
0.362
3151621KERR 5
50/50
0.362
3151631KERR 6
50/50
0.362
3151641KERR 7
50/50
0.362
972205AH1-687 GEN
50/50
5.369
971967AH1-528 GEN
Solar/Wind Harmer
119.102
970285AG2-188 GEN
Solar/Wind Harmer
22.288
971845AH1-439 GEN
Solar/Wind Harmer
12.819
315657AE1-056 GEN
Solar/Wind Harmer
9.023
946301AF1-294 GEN
Solar/Wind Harmer
5.836
961791AG1-021 GEN
Solar/Wind Harmer
2.847
970683AG2-441 GEN
Solar/Wind Harmer
16.366
970681AG2-440 GEN
Solar/Wind Harmer
13.093
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.708
316239AB2-077_GEN
Solar/Wind Harmer
0.415
316238AB2-078_GEN
Solar/Wind Harmer
0.415
970831AG2-522 GEN
Solar/Wind Harmer
6.705
971447AH1-217 GEN
Solar/Wind Harmer
3.932
270494AE1-108_GEN
Solar/Wind Harmer
2.178
3147173SINAI
Solar/Wind Helper
0.376
3147243WELCO
Solar/Wind Helper
0.235
316123AC1-075 GEN
Solar/Wind Helper
1.594
316118AC1-105 GEN
Solar/Wind Helper
0.953
270455AD2-022 GEN
Solar/Wind Helper
0.936
270457AD2-023 GEN
Solar/Wind Helper
0.617
VTFLTFEXP_VFT->PJM
CMTX
1.784
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.284
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.201
G-007ALTFEXP_G-007A->PJM
CMTX
0.675
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.798
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.769
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.415
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
2.312

Details for 6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:141.24 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:958.54
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3147043LAWRENC
50/50
3.141
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.27
3151581KERR 1
50/50
0.096
3144293JTRSVLE
50/50
0.305
3151531CLOVER1
50/50
1.558
316023GEN1_S
Solar/Wind Harmer
1.155
960081AF2-299 GEN
Solar/Wind Harmer
3.965
971795AH1-408 GEN
Solar/Wind Harmer
23.615
316011AB1-132 GEN
Solar/Wind Harmer
6.186
962571AG1-106 GEN
Solar/Wind Harmer
4.841
3145796HORNRTN
Solar/Wind Harmer
1.046
3145796HORNRTN
Solar/Wind Harmer
0.317
3145783HORNRTN
Solar/Wind Harmer
0.249
315722AD1-056 GEN
Solar/Wind Harmer
1.531
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
1.015
3146263WOODLND
Solar/Wind Harmer
0.191
3146233WITAKRS
Solar/Wind Harmer
0.73
3145823KELFORD
Solar/Wind Harmer
0.177
316359AB2-059 GEN
Solar/Wind Harmer
0.634
316049AB1-081 GEN
Solar/Wind Harmer
1.01
3142053HEARTS
Solar/Wind Harmer
0.311
3145543BTLEBRO
Solar/Wind Harmer
0.175
3145543BTLEBRO
Solar/Wind Harmer
0.14
316129AC1-054 GEN
Solar/Wind Harmer
0.656
971065AG2-659 GEN
Solar/Wind Harmer
7.13
3145683EARLEYS
Solar/Wind Harmer
0.166
961671AG1-007 GEN
Solar/Wind Harmer
0.025
3146083TARBORO
Solar/Wind Harmer
0.165
3145493TOT1
Solar/Wind Harmer
0.732
3146173TUNIS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
0.64
3145893MURPHYS
Solar/Wind Harmer
0.712
316494AC1-189 GEN
Solar/Wind Harmer
0.514
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3146293MARTNCO
Solar/Wind Harmer
0.122
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.122
971547AH1-271 GEN
Solar/Wind Harmer
2.614
316174AB2-169 GEN
Solar/Wind Harmer
0.003
3145963POPLR C
Solar/Wind Harmer
0.118
970685AG2-442 GEN
Solar/Wind Harmer
7.425
970401AG2-262 GEN
Solar/Wind Harmer
0.583
963171AG1-166 GEN
Solar/Wind Harmer
0.482
971563AH1-280 GEN
Solar/Wind Harmer
0.963
3145663CRESWEL
Solar/Wind Harmer
0.224
971163AH1-040 GEN
Solar/Wind Harmer
6.407
957481AF2-042 GEN
Solar/Wind Harmer
19.308
316003AC1-222 GEN
Solar/Wind Harmer
0.002
315693AD1-088 GEN
Solar/Wind Harmer
3.442
315687AD1-152 GEN
Solar/Wind Harmer
0.002
962491AG1-098 GEN
Solar/Wind Harmer
4.048
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.27
3151621KERR 5
50/50
0.27
3151631KERR 6
50/50
0.27
3151641KERR 7
50/50
0.27
3151151S HAMPT1
50/50
0.285
3151541CLOVER2
50/50
1.551
315814AE2-033 C
Solar/Wind Harmer
65.923
316087AB2-174 GEN
Solar/Wind Harmer
0.01
315652AC1-086 GEN
Solar/Wind Harmer
37.428
3145796HORNRTN
Solar/Wind Harmer
1.015
3145796HORNRTN
Solar/Wind Harmer
0.127
3137643SOCKMAN
Solar/Wind Harmer
1.176
315607AA1-063A GEN
Solar/Wind Harmer
0.444
3146043SEABORD
Solar/Wind Harmer
0.211
3146033SCOT NK
Solar/Wind Harmer
0.75
316319Z2-044 C
Solar/Wind Harmer
0
970831AG2-522 GEN
Solar/Wind Harmer
7.783
3145683EARLEYS
Solar/Wind Harmer
0.333
3145683EARLEYS
Solar/Wind Harmer
0.166
3145683EARLEYS
Solar/Wind Harmer
0.166
3145513AHOSKIE
Solar/Wind Harmer
0.345
3145513AHOSKIE
Solar/Wind Harmer
0.165
3145573BETHELC
Solar/Wind Harmer
0.165
3145573BETHELC
Solar/Wind Harmer
0.165
3145893MURPHYS
Solar/Wind Harmer
0.432
3145893MURPHYS
Solar/Wind Harmer
0.16
316420AA1-050 GEN
Solar/Wind Harmer
0.005
965291AG1-394 GEN
Solar/Wind Harmer
0.698
957861AF2-080 GEN
Solar/Wind Harmer
6.563
316005AA1-067
Solar/Wind Harmer
0.148
3145746EVERETS
Solar/Wind Harmer
0.548
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
970181AG2-120 GEN
Solar/Wind Harmer
1.713
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.122
970601AG2-382 GEN
Solar/Wind Harmer
4.575
971443AH1-215 GEN
Solar/Wind Harmer
1.848
3144303KENBRDG
Solar/Wind Harmer
0.087
315732AD1-074 GEN1
Solar/Wind Harmer
0.587
315733AD1-074 GEN2
Solar/Wind Harmer
0.587
315735AD1-075 GEN1
Solar/Wind Harmer
0.294
970683AG2-441 GEN
Solar/Wind Harmer
6.63
970681AG2-440 GEN
Solar/Wind Harmer
5.304
3130546PLYMOUTH
Solar/Wind Harmer
0.098
946301AF1-294 GEN
Solar/Wind Harmer
1.782
961791AG1-021 GEN
Solar/Wind Harmer
0.867
316118AC1-105 GEN
Solar/Wind Harmer
0.227
315657AE1-056 GEN
Solar/Wind Harmer
2.895
315816AE2-034 GEN
Solar/Wind Harmer
0.344
3147173SINAI
Solar/Wind Harmer
0.077
3147243WELCO
Solar/Wind Harmer
0.048
970865AG2-541 GEN
Solar/Wind Harmer
2.227
316315AB2-025 C
Solar/Wind Helper
0.826
3143316POE
Solar/Wind Helper
0.688
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3151261ROARAP2
50/50
0.313
3151591KERR 2
50/50
0.27
3144293JTRSVLE
50/50
0.305
970413AG2-270 GEN
50/50
6.801
316365GEN2_N
Solar/Wind Harmer
1.155
313506AB2-031 GEN
Solar/Wind Harmer
1.049
3147043LAWRENC
Solar/Wind Harmer
0.196
3145796HORNRTN
Solar/Wind Harmer
1.268
3145796HORNRTN
Solar/Wind Harmer
0.317
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
315724AD1-057 GEN
Solar/Wind Harmer
0.907
316210AC1-098 GEN
Solar/Wind Harmer
1.821
316327AA2-057 GEN
Solar/Wind Harmer
0.289
3146263WOODLND
Solar/Wind Harmer
0.191
3146233WITAKRS
Solar/Wind Harmer
0.921
3146233WITAKRS
Solar/Wind Harmer
0.125
3138543CONSLDL
Solar/Wind Harmer
0.12
961601AG1-000A GEN
Solar/Wind Harmer
12.805
316317KELFORD C
Solar/Wind Harmer
0.017
3145823KELFORD
Solar/Wind Harmer
0.177
971623AH1-311 GEN
Solar/Wind Harmer
0.353
3145543BTLEBRO
Solar/Wind Harmer
0.175
3145543BTLEBRO
Solar/Wind Harmer
0.175
316463AE2-346 GEN
Solar/Wind Harmer
0.142
316140AB2-099
Solar/Wind Harmer
0.059
962331AG1-082 GEN
Solar/Wind Harmer
1.76
3146073TAR RVR
Solar/Wind Harmer
0.165
3146083TARBORO
Solar/Wind Harmer
0.165
3146173TUNIS
Solar/Wind Harmer
0.163
957521AF2-046 GEN
Solar/Wind Harmer
11.982
961681AG1-008 GEN
Solar/Wind Harmer
11.982
3145893MURPHYS
Solar/Wind Harmer
0.268
3145893MURPHYS
Solar/Wind Harmer
0.16
3156021HOLLOMANSOL
Solar/Wind Harmer
0.689
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3145933PARMELE
Solar/Wind Harmer
0.131
966801AG1-551 GEN
Solar/Wind Harmer
1.529
316131AB2-060 GEN
Solar/Wind Harmer
0.407
964241AG1-285 GEN
Solar/Wind Harmer
8.211
3146206CASHIE
Solar/Wind Harmer
0.122
3145963POPLR C
Solar/Wind Harmer
0.118
315785AD2-033 C
Solar/Wind Harmer
0.918
970257AG2-171 GEN
Solar/Wind Harmer
3.491
959311AF2-222 GEN
Solar/Wind Harmer
9.454
315737AD1-076 GEN
Solar/Wind Harmer
1.314
971157AH1-035 GEN
Solar/Wind Harmer
1.183
963181AG1-167 GEN
Solar/Wind Harmer
0.361
3147133PAMPLIN
Solar/Wind Harmer
0.263
971193AH1-056 GEN
Solar/Wind Harmer
5.112
315614AA2-178 GEN
Solar/Wind Harmer
0.458
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.273
316478AD1-087 GEN
Solar/Wind Harmer
0.254
316486AD2-202 GEN
Solar/Wind Harmer
0.075
971683AH1-343 GEN
Solar/Wind Harmer
2.513
942461AE2-259 GEN
Solar/Wind Harmer
0
316283AC2-100 C
Solar/Wind Harmer
0.113
970909AG2-566 GEN
Solar/Wind Harmer
0.605
315839AE2-212 C
Solar/Wind Helper
0.197
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.321
3144293JTRSVLE
50/50
0.305
3144293JTRSVLE
50/50
0.257
3152661PLYWOOD A
50/50
0.195
316181AB2-040 GEN
Solar/Wind Harmer
0.492
3145796HORNRTN
Solar/Wind Harmer
0.951
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3145593CAROLNA
Solar/Wind Harmer
0.257
3145593CAROLNA
Solar/Wind Harmer
0.257
966811AG1-552 GEN
Solar/Wind Harmer
2.785
3145593CAROLNA
Solar/Wind Harmer
0.32
3145783HORNRTN
Solar/Wind Harmer
4.428
3145783HORNRTN
Solar/Wind Harmer
3.543
3145783HORNRTN
Solar/Wind Harmer
1.107
3145783HORNRTN
Solar/Wind Harmer
0.443
316426AA2-053 GEN
Solar/Wind Harmer
0.813
316274AC1-208 GEN
Solar/Wind Harmer
1.081
961601AG1-000A GEN
Solar/Wind Harmer
3.201
316263AC1-034 GEN
Solar/Wind Harmer
6.707
3145493TOT1
Solar/Wind Harmer
0.382
3145453TOT5
Solar/Wind Harmer
0.229
3145603CNETO
Solar/Wind Harmer
0.153
3146173TUNIS
Solar/Wind Harmer
0.163
3146173TUNIS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
1.071
3145893MURPHYS
Solar/Wind Harmer
0.288
3145933PARMELE
Solar/Wind Harmer
0.262
3145933PARMELE
Solar/Wind Harmer
0.131
313527AB2-043 GEN
Solar/Wind Harmer
0.002
939181AE1-148 GEN
Solar/Wind Harmer
6.26
316065AD1-022 GEN
Solar/Wind Harmer
5.298
970323AG2-213 GEN
Solar/Wind Harmer
4.655
971775AH1-396 GEN
Solar/Wind Harmer
0.175
316034AC1-036 C
Solar/Wind Harmer
0.008
962561AG1-105 GEN
Solar/Wind Harmer
5
964791AG1-342 GEN
Solar/Wind Harmer
1.908
3146843MT LREL
Solar/Wind Harmer
0.099
3146843MT LREL
Solar/Wind Harmer
0.099
958211AF2-115 GEN
Solar/Wind Harmer
1.083
963191AG1-168 GEN
Solar/Wind Harmer
0.361
3147133PAMPLIN
Solar/Wind Harmer
0.084
3147133PAMPLIN
Solar/Wind Harmer
0.067
970099AG2-077 GEN
Solar/Wind Harmer
7.723
315742AE1-103 GEN
Solar/Wind Harmer
0.001
971741AH1-377 GEN
Solar/Wind Harmer
5.969
316222AC1-221 GEN
Solar/Wind Harmer
0.242
970301AG2-198 GEN
Solar/Wind Harmer
2.421
3144356SAPONY
Solar/Wind Helper
0.972
316240AF1-291 C
Solar/Wind Helper
0.168
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.85
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.587
MECLTFEXP_MEC->PJM
CLTF
1.327
SIGELTFEXP_SIGE->PJM
CLTF
0.04
CPLELTFEXP_CPLE->PJM
CLTF
4.45
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.218
LAGNLTFEXP_LAGN->PJM
CLTF
2.678
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.707
TVALTFEXP_TVA->PJM
CLTF
1.336
NYPJM->LTFIMP_NY
CLTF
0.49
LGEELTFEXP_LGEE->PJM
CLTF
0.481
WECLTFEXP_WEC->PJM
CLTF
0.25

Details for 6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:140.59 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:954.15
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3147043LAWRENC
50/50
3.141
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.27
3151581KERR 1
50/50
0.096
3144293JTRSVLE
50/50
0.305
3151531CLOVER1
50/50
1.558
316023GEN1_S
Solar/Wind Harmer
1.155
960081AF2-299 GEN
Solar/Wind Harmer
3.965
971795AH1-408 GEN
Solar/Wind Harmer
23.615
316011AB1-132 GEN
Solar/Wind Harmer
6.186
962571AG1-106 GEN
Solar/Wind Harmer
4.841
3145796HORNRTN
Solar/Wind Harmer
1.046
3145796HORNRTN
Solar/Wind Harmer
0.317
3145783HORNRTN
Solar/Wind Harmer
0.249
315722AD1-056 GEN
Solar/Wind Harmer
1.531
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
1.015
3146263WOODLND
Solar/Wind Harmer
0.191
3146233WITAKRS
Solar/Wind Harmer
0.73
3145823KELFORD
Solar/Wind Harmer
0.177
316359AB2-059 GEN
Solar/Wind Harmer
0.634
316049AB1-081 GEN
Solar/Wind Harmer
1.01
3142053HEARTS
Solar/Wind Harmer
0.311
3145543BTLEBRO
Solar/Wind Harmer
0.175
3145543BTLEBRO
Solar/Wind Harmer
0.14
316129AC1-054 GEN
Solar/Wind Harmer
0.656
971065AG2-659 GEN
Solar/Wind Harmer
7.13
3145683EARLEYS
Solar/Wind Harmer
0.166
961671AG1-007 GEN
Solar/Wind Harmer
0.025
3146083TARBORO
Solar/Wind Harmer
0.165
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.27
3151621KERR 5
50/50
0.27
3151631KERR 6
50/50
0.27
3151641KERR 7
50/50
0.27
3151151S HAMPT1
50/50
0.285
3151541CLOVER2
50/50
1.551
315814AE2-033 C
Solar/Wind Harmer
65.923
316087AB2-174 GEN
Solar/Wind Harmer
0.01
315652AC1-086 GEN
Solar/Wind Harmer
37.428
3145796HORNRTN
Solar/Wind Harmer
1.015
3145796HORNRTN
Solar/Wind Harmer
0.127
3137643SOCKMAN
Solar/Wind Harmer
1.176
315607AA1-063A GEN
Solar/Wind Harmer
0.444
3146043SEABORD
Solar/Wind Harmer
0.211
3146033SCOT NK
Solar/Wind Harmer
0.75
316319Z2-044 C
Solar/Wind Harmer
0
970831AG2-522 GEN
Solar/Wind Harmer
7.783
3145683EARLEYS
Solar/Wind Harmer
0.333
3145683EARLEYS
Solar/Wind Harmer
0.166
3145683EARLEYS
Solar/Wind Harmer
0.166
3145513AHOSKIE
Solar/Wind Harmer
0.345
3145513AHOSKIE
Solar/Wind Harmer
0.165
3145573BETHELC
Solar/Wind Harmer
0.165
3145573BETHELC
Solar/Wind Harmer
0.165
3145893MURPHYS
Solar/Wind Harmer
0.432
3145893MURPHYS
Solar/Wind Harmer
0.16
316420AA1-050 GEN
Solar/Wind Harmer
0.005
965291AG1-394 GEN
Solar/Wind Harmer
0.698
957861AF2-080 GEN
Solar/Wind Harmer
6.563
316005AA1-067
Solar/Wind Harmer
0.148
3145746EVERETS
Solar/Wind Harmer
0.548
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
970181AG2-120 GEN
Solar/Wind Harmer
1.713
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3151261ROARAP2
50/50
0.313
3151591KERR 2
50/50
0.27
3144293JTRSVLE
50/50
0.305
970413AG2-270 GEN
50/50
6.801
316365GEN2_N
Solar/Wind Harmer
1.155
313506AB2-031 GEN
Solar/Wind Harmer
1.049
3147043LAWRENC
Solar/Wind Harmer
0.196
3145796HORNRTN
Solar/Wind Harmer
1.268
3145796HORNRTN
Solar/Wind Harmer
0.317
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
315724AD1-057 GEN
Solar/Wind Harmer
0.907
316210AC1-098 GEN
Solar/Wind Harmer
1.821
316327AA2-057 GEN
Solar/Wind Harmer
0.289
3146263WOODLND
Solar/Wind Harmer
0.191
3146233WITAKRS
Solar/Wind Harmer
0.921
3146233WITAKRS
Solar/Wind Harmer
0.125
3138543CONSLDL
Solar/Wind Harmer
0.12
961601AG1-000A GEN
Solar/Wind Harmer
12.805
316317KELFORD C
Solar/Wind Harmer
0.017
3145823KELFORD
Solar/Wind Harmer
0.177
971623AH1-311 GEN
Solar/Wind Harmer
0.353
3145543BTLEBRO
Solar/Wind Harmer
0.175
3145543BTLEBRO
Solar/Wind Harmer
0.175
316463AE2-346 GEN
Solar/Wind Harmer
0.142
316140AB2-099
Solar/Wind Harmer
0.059
962331AG1-082 GEN
Solar/Wind Harmer
1.76
3146073TAR RVR
Solar/Wind Harmer
0.165
3146083TARBORO
Solar/Wind Harmer
0.165
3146173TUNIS
Solar/Wind Harmer
0.163
957521AF2-046 GEN
Solar/Wind Harmer
11.982
961681AG1-008 GEN
Solar/Wind Harmer
11.982
3145893MURPHYS
Solar/Wind Harmer
0.268
3145893MURPHYS
Solar/Wind Harmer
0.16
3156021HOLLOMANSOL
Solar/Wind Harmer
0.689
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3145933PARMELE
Solar/Wind Harmer
0.131
966801AG1-551 GEN
Solar/Wind Harmer
1.529
316131AB2-060 GEN
Solar/Wind Harmer
0.407
964241AG1-285 GEN
Solar/Wind Harmer
8.211
3146206CASHIE
Solar/Wind Harmer
0.122
3145963POPLR C
Solar/Wind Harmer
0.118
315785AD2-033 C
Solar/Wind Harmer
0.918
970257AG2-171 GEN
Solar/Wind Harmer
3.491
959311AF2-222 GEN
Solar/Wind Harmer
9.454
315737AD1-076 GEN
Solar/Wind Harmer
1.314
971157AH1-035 GEN
Solar/Wind Harmer
1.183
963181AG1-167 GEN
Solar/Wind Harmer
0.361
3147133PAMPLIN
Solar/Wind Harmer
0.263
971193AH1-056 GEN
Solar/Wind Harmer
5.112
315614AA2-178 GEN
Solar/Wind Harmer
0.458
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.273
316478AD1-087 GEN
Solar/Wind Harmer
0.254
316486AD2-202 GEN
Solar/Wind Harmer
0.075
971683AH1-343 GEN
Solar/Wind Harmer
2.513
942461AE2-259 GEN
Solar/Wind Harmer
0
316283AC2-100 C
Solar/Wind Harmer
0.113
970909AG2-566 GEN
Solar/Wind Harmer
0.605
315839AE2-212 C
Solar/Wind Helper
0.197
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.321
3144293JTRSVLE
50/50
0.305
3144293JTRSVLE
50/50
0.257
3152661PLYWOOD A
50/50
0.195
316181AB2-040 GEN
Solar/Wind Harmer
0.492
3145796HORNRTN
Solar/Wind Harmer
0.951
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3145593CAROLNA
Solar/Wind Harmer
0.257
3145593CAROLNA
Solar/Wind Harmer
0.257
966811AG1-552 GEN
Solar/Wind Harmer
2.785
3145593CAROLNA
Solar/Wind Harmer
0.32
3145783HORNRTN
Solar/Wind Harmer
4.428
3145783HORNRTN
Solar/Wind Harmer
3.543
3145783HORNRTN
Solar/Wind Harmer
1.107
3145783HORNRTN
Solar/Wind Harmer
0.443
316426AA2-053 GEN
Solar/Wind Harmer
0.813
316274AC1-208 GEN
Solar/Wind Harmer
1.081
961601AG1-000A GEN
Solar/Wind Harmer
3.201
316263AC1-034 GEN
Solar/Wind Harmer
6.707
3145493TOT1
Solar/Wind Harmer
0.382
3145453TOT5
Solar/Wind Harmer
0.229
3145603CNETO
Solar/Wind Harmer
0.153
3146173TUNIS
Solar/Wind Harmer
0.163
3146173TUNIS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
1.071
3145893MURPHYS
Solar/Wind Harmer
0.288
3145933PARMELE
Solar/Wind Harmer
0.262
3145933PARMELE
Solar/Wind Harmer
0.131
313527AB2-043 GEN
Solar/Wind Harmer
0.002
939181AE1-148 GEN
Solar/Wind Harmer
6.26
316065AD1-022 GEN
Solar/Wind Harmer
5.298
970323AG2-213 GEN
Solar/Wind Harmer
4.655
971775AH1-396 GEN
Solar/Wind Harmer
0.175
316034AC1-036 C
Solar/Wind Harmer
0.008
962561AG1-105 GEN
Solar/Wind Harmer
5
964791AG1-342 GEN
Solar/Wind Harmer
1.908
3146843MT LREL
Solar/Wind Harmer
0.099
3146843MT LREL
Solar/Wind Harmer
0.099
958211AF2-115 GEN
Solar/Wind Harmer
1.083
963191AG1-168 GEN
Solar/Wind Harmer
0.361
3147133PAMPLIN
Solar/Wind Harmer
0.084
3147133PAMPLIN
Solar/Wind Harmer
0.067
970099AG2-077 GEN
Solar/Wind Harmer
7.723
970933AG2-581 GEN
Solar/Wind Harmer
5.779
315742AE1-103 GEN
Solar/Wind Harmer
0.001
971741AH1-377 GEN
Solar/Wind Harmer
5.969
316222AC1-221 GEN
Solar/Wind Harmer
0.242
970301AG2-198 GEN
Solar/Wind Harmer
2.421
3144356SAPONY
Solar/Wind Helper
0.972
316240AF1-291 C
Solar/Wind Helper
0.168
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.122
970601AG2-382 GEN
Solar/Wind Harmer
4.575
971443AH1-215 GEN
Solar/Wind Harmer
1.848
3144303KENBRDG
Solar/Wind Harmer
0.087
315732AD1-074 GEN1
Solar/Wind Harmer
0.587
315733AD1-074 GEN2
Solar/Wind Harmer
0.587
315735AD1-075 GEN1
Solar/Wind Harmer
0.294
970683AG2-441 GEN
Solar/Wind Harmer
6.63
970681AG2-440 GEN
Solar/Wind Harmer
5.304
3130546PLYMOUTH
Solar/Wind Harmer
0.098
946301AF1-294 GEN
Solar/Wind Harmer
1.782
961791AG1-021 GEN
Solar/Wind Harmer
0.867
316118AC1-105 GEN
Solar/Wind Harmer
0.227
315657AE1-056 GEN
Solar/Wind Harmer
2.895
315816AE2-034 GEN
Solar/Wind Harmer
0.344
3147173SINAI
Solar/Wind Harmer
0.077
3147243WELCO
Solar/Wind Harmer
0.048
971967AH1-528 GEN
Solar/Wind Harmer
11.557
970865AG2-541 GEN
Solar/Wind Harmer
2.227
316315AB2-025 C
Solar/Wind Helper
0.826
3145493TOT1
Solar/Wind Harmer
0.732
3146173TUNIS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
0.64
3145893MURPHYS
Solar/Wind Harmer
0.712
316494AC1-189 GEN
Solar/Wind Harmer
0.514
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3146293MARTNCO
Solar/Wind Harmer
0.122
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.122
971547AH1-271 GEN
Solar/Wind Harmer
2.614
316174AB2-169 GEN
Solar/Wind Harmer
0.003
3145963POPLR C
Solar/Wind Harmer
0.118
970685AG2-442 GEN
Solar/Wind Harmer
7.425
970401AG2-262 GEN
Solar/Wind Harmer
0.583
963171AG1-166 GEN
Solar/Wind Harmer
0.482
971563AH1-280 GEN
Solar/Wind Harmer
0.963
3145663CRESWEL
Solar/Wind Harmer
0.224
971163AH1-040 GEN
Solar/Wind Harmer
6.407
957481AF2-042 GEN
Solar/Wind Harmer
19.308
316003AC1-222 GEN
Solar/Wind Harmer
0.002
315693AD1-088 GEN
Solar/Wind Harmer
3.442
315687AD1-152 GEN
Solar/Wind Harmer
0.002
962491AG1-098 GEN
Solar/Wind Harmer
4.048
3143316POE
Solar/Wind Helper
0.688
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.85
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.587
MECLTFEXP_MEC->PJM
CLTF
1.327
SIGELTFEXP_SIGE->PJM
CLTF
0.04
CPLELTFEXP_CPLE->PJM
CLTF
4.45
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.218
LAGNLTFEXP_LAGN->PJM
CLTF
2.678
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.707
TVALTFEXP_TVA->PJM
CLTF
1.336
NYPJM->LTFIMP_NY
CLTF
0.49
LGEELTFEXP_LGEE->PJM
CLTF
0.481
WECLTFEXP_WEC->PJM
CLTF
0.25

Details for 6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:136.41 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1132.24
MW Contribution:2.34
Bus #Bus NameTypeMW Contribution
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.337
316181AB2-040 GEN
Solar/Wind Harmer
5.319
3145796HORNRTN
Solar/Wind Harmer
-0.106
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3145593CAROLNA
Solar/Wind Harmer
-0.029
3145593CAROLNA
Solar/Wind Harmer
-0.029
966811AG1-552 GEN
Solar/Wind Harmer
3.248
3145593CAROLNA
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
3.324
3145783HORNRTN
Solar/Wind Harmer
2.659
3145783HORNRTN
Solar/Wind Harmer
0.831
3145783HORNRTN
Solar/Wind Harmer
0.332
316426AA2-053 GEN
Solar/Wind Harmer
2.733
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3147043LAWRENC
50/50
3.142
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.272
3151581KERR 1
50/50
0.097
316023GEN1_S
Solar/Wind Harmer
3.898
960081AF2-299 GEN
Solar/Wind Harmer
5.218
971795AH1-408 GEN
Solar/Wind Harmer
29.85
316011AB1-132 GEN
Solar/Wind Harmer
8.002
962571AG1-106 GEN
Solar/Wind Harmer
5.498
3145796HORNRTN
Solar/Wind Harmer
-0.117
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145783HORNRTN
Solar/Wind Harmer
-0.028
315722AD1-056 GEN
Solar/Wind Harmer
2.85
316190AA2-174 GEN
Solar/Wind Harmer
0.332
316212AC1-099_GEN
Solar/Wind Harmer
1.927
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
-0.082
316359AB2-059 GEN
Solar/Wind Harmer
2.691
316049AB1-081 GEN
Solar/Wind Harmer
2.154
3142053HEARTS
Solar/Wind Harmer
0.235
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316129AC1-054 GEN
Solar/Wind Harmer
1.725
971065AG2-659 GEN
Solar/Wind Harmer
9.428
3145683EARLEYS
Solar/Wind Harmer
-0.019
961671AG1-007 GEN
Solar/Wind Harmer
0.235
3146083TARBORO
Solar/Wind Harmer
-0.019
3145493TOT1
Solar/Wind Harmer
0.552
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.071
3145893MURPHYS
Solar/Wind Harmer
0.532
316494AC1-189 GEN
Solar/Wind Harmer
1.85
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146293MARTNCO
Solar/Wind Harmer
0.092
316237AB2-079_GEN
Solar/Wind Harmer
0.44
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.431
316174AB2-169 GEN
Solar/Wind Harmer
2.09
3145963POPLR C
Solar/Wind Harmer
-0.013
970401AG2-262 GEN
Solar/Wind Harmer
0.737
970685AG2-442 GEN
Solar/Wind Harmer
9.839
963171AG1-166 GEN
Solar/Wind Harmer
1.276
971563AH1-280 GEN
Solar/Wind Harmer
1.276
3144293JTRSVLE
Adder
0.289
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.359
957481AF2-042 GEN
Solar/Wind Harmer
25.811
316003AC1-222 GEN
Solar/Wind Harmer
0.806
315693AD1-088 GEN
Solar/Wind Harmer
4.085
315687AD1-152 GEN
Solar/Wind Harmer
0.98
962491AG1-098 GEN
Solar/Wind Harmer
5.404
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.272
3151621KERR 5
50/50
0.272
3151631KERR 6
50/50
0.272
3151641KERR 7
50/50
0.272
315814AE2-033 C
Solar/Wind Harmer
87.045
946281AF1-292 GEN
Solar/Wind Harmer
1.039
316087AB2-174 GEN
Solar/Wind Harmer
5.795
315652AC1-086 GEN
Solar/Wind Harmer
43.026
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.014
3137643SOCKMAN
Solar/Wind Harmer
-0.132
315607AA1-063A GEN
Solar/Wind Harmer
2.467
3146043SEABORD
Solar/Wind Harmer
-0.024
3146033SCOT NK
Solar/Wind Harmer
-0.084
316319Z2-044 C
Solar/Wind Harmer
1.146
970831AG2-522 GEN
Solar/Wind Harmer
10.282
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.161
961941AG1-037 GEN
Solar/Wind Harmer
0.139
3145513AHOSKIE
Solar/Wind Harmer
-0.018
316420AA1-050 GEN
Solar/Wind Harmer
2.056
316318V4-068
Solar/Wind Harmer
0.447
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
965291AG1-394 GEN
Solar/Wind Harmer
1.561
957861AF2-080 GEN
Solar/Wind Harmer
7.524
316005AA1-067
Solar/Wind Harmer
0.314
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
2.04
316239AB2-077_GEN
Solar/Wind Harmer
0.44
316238AB2-078_GEN
Solar/Wind Harmer
0.44
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
6.005
971443AH1-215 GEN
Solar/Wind Harmer
2.448
3144303KENBRDG
Solar/Wind Harmer
-0.01
315732AD1-074 GEN1
Solar/Wind Harmer
2.309
315733AD1-074 GEN2
Solar/Wind Harmer
2.309
315735AD1-075 GEN1
Solar/Wind Harmer
1.155
970683AG2-441 GEN
Solar/Wind Harmer
8.785
970681AG2-440 GEN
Solar/Wind Harmer
7.028
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
946301AF1-294 GEN
Solar/Wind Harmer
2.616
961791AG1-021 GEN
Solar/Wind Harmer
1.276
316118AC1-105 GEN
Solar/Wind Harmer
0.689
315657AE1-056 GEN
Solar/Wind Harmer
3.56
315816AE2-034 GEN
Solar/Wind Harmer
0.721
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
971967AH1-528 GEN
Solar/Wind Harmer
15.486
970865AG2-541 GEN
Solar/Wind Harmer
2.987
316123AC1-075 GEN
Solar/Wind Harmer
0.692
970165AG2-112 GEN
Solar/Wind Harmer
0.609
970163AG2-111 GEN
Solar/Wind Harmer
0.581
316315AB2-025 C
Solar/Wind Helper
0.83
3143316POE
Solar/Wind Helper
0.701
316274AC1-208 GEN
Solar/Wind Harmer
2.531
961601AG1-000A GEN
Solar/Wind Harmer
8.004
316263AC1-034 GEN
Solar/Wind Harmer
9.357
3145493TOT1
Solar/Wind Harmer
0.288
3145453TOT5
Solar/Wind Harmer
0.173
3145603CNETO
Solar/Wind Harmer
0.115
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.501
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.029
3145933PARMELE
Solar/Wind Harmer
-0.015
313527AB2-043 GEN
Solar/Wind Harmer
2.404
939181AE1-148 GEN
Solar/Wind Harmer
8.303
316065AD1-022 GEN
Solar/Wind Harmer
6.44
970323AG2-213 GEN
Solar/Wind Harmer
6.168
971775AH1-396 GEN
Solar/Wind Harmer
0.878
316034AC1-036 C
Solar/Wind Harmer
0.229
962561AG1-105 GEN
Solar/Wind Harmer
6.652
964791AG1-342 GEN
Solar/Wind Harmer
2.412
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
958211AF2-115 GEN
Solar/Wind Harmer
1.595
963191AG1-168 GEN
Solar/Wind Harmer
0.957
3144293JTRSVLE
Adder
0.289
3144293JTRSVLE
Adder
0.244
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.324
970933AG2-581 GEN
Solar/Wind Harmer
7.724
315742AE1-103 GEN
Solar/Wind Harmer
0.835
971741AH1-377 GEN
Solar/Wind Harmer
7.95
316222AC1-221 GEN
Solar/Wind Harmer
0.686
970301AG2-198 GEN
Solar/Wind Harmer
3.221
3144356SAPONY
Solar/Wind Helper
0.977
316240AF1-291 C
Solar/Wind Helper
0.173
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3151261ROARAP2
50/50
0.313
3151591KERR 2
50/50
0.272
316365GEN2_N
Solar/Wind Harmer
3.898
966621AG1-532 GEN
Solar/Wind Harmer
0.941
313506AB2-031 GEN
Solar/Wind Harmer
3.065
3147043LAWRENC
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.142
3145796HORNRTN
Solar/Wind Harmer
-0.036
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
315724AD1-057 GEN
Solar/Wind Harmer
1.567
316210AC1-098 GEN
Solar/Wind Harmer
3.469
316327AA2-057 GEN
Solar/Wind Harmer
2.181
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
0.434
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
8.106
316317KELFORD C
Solar/Wind Harmer
0.938
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3146073TAR RVR
Solar/Wind Harmer
-0.019
3146083TARBORO
Solar/Wind Harmer
-0.019
316463AE2-346 GEN
Solar/Wind Harmer
0.3
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.315
3146173TUNIS
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.221
961681AG1-008 GEN
Solar/Wind Harmer
14.221
3145893MURPHYS
Solar/Wind Harmer
0.125
3145893MURPHYS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.293
3156081AA2-088 GEN
Solar/Wind Harmer
5.454
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.85
316131AB2-060 GEN
Solar/Wind Harmer
1.577
964241AG1-285 GEN
Solar/Wind Harmer
10.88
3146206CASHIE
Solar/Wind Harmer
-0.014
3145963POPLR C
Solar/Wind Harmer
-0.013
315785AD2-033 C
Solar/Wind Harmer
2.894
970257AG2-171 GEN
Solar/Wind Harmer
4.626
959311AF2-222 GEN
Solar/Wind Harmer
12.552
315737AD1-076 GEN
Solar/Wind Harmer
2.17
971157AH1-035 GEN
Solar/Wind Harmer
1.377
963181AG1-167 GEN
Solar/Wind Harmer
0.957
3144293JTRSVLE
Adder
0.289
3147133PAMPLIN
Solar/Wind Harmer
-0.03
971193AH1-056 GEN
Solar/Wind Harmer
5.933
315614AA2-178 GEN
Solar/Wind Harmer
0.962
316248AF1-058 C
Solar/Wind Harmer
0.264
960061AF2-297 GEN
Solar/Wind Harmer
4.385
316478AD1-087 GEN
Solar/Wind Harmer
0.72
316486AD2-202 GEN
Solar/Wind Harmer
0.211
971683AH1-343 GEN
Solar/Wind Harmer
3.369
942461AE2-259 GEN
Solar/Wind Harmer
1.119
316283AC2-100 C
Solar/Wind Harmer
0.635
970909AG2-566 GEN
Solar/Wind Harmer
0.612
315839AE2-212 C
Solar/Wind Helper
0.202
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.344
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.843
MECLTFEXP_MEC->PJM
CLTF
1.401
SIGELTFEXP_SIGE->PJM
CLTF
0.042
CPLELTFEXP_CPLE->PJM
CLTF
4.654
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.01
LAGNLTFEXP_LAGN->PJM
CLTF
2.828
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.165
TVALTFEXP_TVA->PJM
CLTF
1.41
NYPJM->LTFIMP_NY
CLTF
0.512
LGEELTFEXP_LGEE->PJM
CLTF
0.508
WECLTFEXP_WEC->PJM
CLTF
0.264

Details for 6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:136.35 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1131.67
MW Contribution:2.34
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3147043LAWRENC
50/50
3.142
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.272
3151581KERR 1
50/50
0.097
316023GEN1_S
Solar/Wind Harmer
3.898
960081AF2-299 GEN
Solar/Wind Harmer
5.218
971795AH1-408 GEN
Solar/Wind Harmer
29.85
316011AB1-132 GEN
Solar/Wind Harmer
8.002
962571AG1-106 GEN
Solar/Wind Harmer
5.498
3145796HORNRTN
Solar/Wind Harmer
-0.117
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145783HORNRTN
Solar/Wind Harmer
-0.028
315722AD1-056 GEN
Solar/Wind Harmer
2.85
316190AA2-174 GEN
Solar/Wind Harmer
0.332
316212AC1-099_GEN
Solar/Wind Harmer
1.927
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
-0.082
316359AB2-059 GEN
Solar/Wind Harmer
2.691
316049AB1-081 GEN
Solar/Wind Harmer
2.154
3142053HEARTS
Solar/Wind Harmer
0.235
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316129AC1-054 GEN
Solar/Wind Harmer
1.725
971065AG2-659 GEN
Solar/Wind Harmer
9.428
3145683EARLEYS
Solar/Wind Harmer
-0.019
961671AG1-007 GEN
Solar/Wind Harmer
0.235
3146083TARBORO
Solar/Wind Harmer
-0.019
3145493TOT1
Solar/Wind Harmer
0.552
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.071
3145893MURPHYS
Solar/Wind Harmer
0.532
316494AC1-189 GEN
Solar/Wind Harmer
1.85
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146293MARTNCO
Solar/Wind Harmer
0.092
316237AB2-079_GEN
Solar/Wind Harmer
0.44
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.431
316174AB2-169 GEN
Solar/Wind Harmer
2.09
3145963POPLR C
Solar/Wind Harmer
-0.013
970401AG2-262 GEN
Solar/Wind Harmer
0.737
970685AG2-442 GEN
Solar/Wind Harmer
9.839
963171AG1-166 GEN
Solar/Wind Harmer
1.276
971563AH1-280 GEN
Solar/Wind Harmer
1.276
3144293JTRSVLE
Adder
0.289
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.359
957481AF2-042 GEN
Solar/Wind Harmer
25.811
316003AC1-222 GEN
Solar/Wind Harmer
0.806
315693AD1-088 GEN
Solar/Wind Harmer
4.085
315687AD1-152 GEN
Solar/Wind Harmer
0.98
962491AG1-098 GEN
Solar/Wind Harmer
5.404
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.272
3151621KERR 5
50/50
0.272
3151631KERR 6
50/50
0.272
3151641KERR 7
50/50
0.272
315814AE2-033 C
Solar/Wind Harmer
87.045
946281AF1-292 GEN
Solar/Wind Harmer
1.039
316087AB2-174 GEN
Solar/Wind Harmer
5.795
315652AC1-086 GEN
Solar/Wind Harmer
43.026
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.014
3137643SOCKMAN
Solar/Wind Harmer
-0.132
315607AA1-063A GEN
Solar/Wind Harmer
2.467
3146043SEABORD
Solar/Wind Harmer
-0.024
3146033SCOT NK
Solar/Wind Harmer
-0.084
316319Z2-044 C
Solar/Wind Harmer
1.146
970831AG2-522 GEN
Solar/Wind Harmer
10.282
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.161
961941AG1-037 GEN
Solar/Wind Harmer
0.139
3145513AHOSKIE
Solar/Wind Harmer
-0.018
316420AA1-050 GEN
Solar/Wind Harmer
2.056
316318V4-068
Solar/Wind Harmer
0.447
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
965291AG1-394 GEN
Solar/Wind Harmer
1.561
957861AF2-080 GEN
Solar/Wind Harmer
7.524
316005AA1-067
Solar/Wind Harmer
0.314
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
2.04
316239AB2-077_GEN
Solar/Wind Harmer
0.44
316238AB2-078_GEN
Solar/Wind Harmer
0.44
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
6.005
971443AH1-215 GEN
Solar/Wind Harmer
2.448
3144303KENBRDG
Solar/Wind Harmer
-0.01
315732AD1-074 GEN1
Solar/Wind Harmer
2.309
315733AD1-074 GEN2
Solar/Wind Harmer
2.309
315735AD1-075 GEN1
Solar/Wind Harmer
1.155
970683AG2-441 GEN
Solar/Wind Harmer
8.785
970681AG2-440 GEN
Solar/Wind Harmer
7.028
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
946301AF1-294 GEN
Solar/Wind Harmer
2.616
961791AG1-021 GEN
Solar/Wind Harmer
1.276
316118AC1-105 GEN
Solar/Wind Harmer
0.689
315657AE1-056 GEN
Solar/Wind Harmer
3.56
315816AE2-034 GEN
Solar/Wind Harmer
0.721
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
971967AH1-528 GEN
Solar/Wind Harmer
15.486
970865AG2-541 GEN
Solar/Wind Harmer
2.987
316123AC1-075 GEN
Solar/Wind Harmer
0.692
970165AG2-112 GEN
Solar/Wind Harmer
0.609
970163AG2-111 GEN
Solar/Wind Harmer
0.581
316315AB2-025 C
Solar/Wind Helper
0.83
3143316POE
Solar/Wind Helper
0.701
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.337
316181AB2-040 GEN
Solar/Wind Harmer
5.319
3145796HORNRTN
Solar/Wind Harmer
-0.106
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3145593CAROLNA
Solar/Wind Harmer
-0.029
3145593CAROLNA
Solar/Wind Harmer
-0.029
966811AG1-552 GEN
Solar/Wind Harmer
3.248
3145593CAROLNA
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
3.324
3145783HORNRTN
Solar/Wind Harmer
2.659
3145783HORNRTN
Solar/Wind Harmer
0.831
3145783HORNRTN
Solar/Wind Harmer
0.332
316426AA2-053 GEN
Solar/Wind Harmer
2.733
316274AC1-208 GEN
Solar/Wind Harmer
2.531
961601AG1-000A GEN
Solar/Wind Harmer
8.004
316263AC1-034 GEN
Solar/Wind Harmer
9.357
3145493TOT1
Solar/Wind Harmer
0.288
3145453TOT5
Solar/Wind Harmer
0.173
3145603CNETO
Solar/Wind Harmer
0.115
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.501
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.029
3145933PARMELE
Solar/Wind Harmer
-0.015
313527AB2-043 GEN
Solar/Wind Harmer
2.404
939181AE1-148 GEN
Solar/Wind Harmer
8.303
316065AD1-022 GEN
Solar/Wind Harmer
6.44
970323AG2-213 GEN
Solar/Wind Harmer
6.168
971775AH1-396 GEN
Solar/Wind Harmer
0.878
316034AC1-036 C
Solar/Wind Harmer
0.229
962561AG1-105 GEN
Solar/Wind Harmer
6.652
964791AG1-342 GEN
Solar/Wind Harmer
2.412
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
958211AF2-115 GEN
Solar/Wind Harmer
1.595
963191AG1-168 GEN
Solar/Wind Harmer
0.957
3144293JTRSVLE
Adder
0.289
3144293JTRSVLE
Adder
0.244
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.324
970933AG2-581 GEN
Solar/Wind Harmer
7.724
315742AE1-103 GEN
Solar/Wind Harmer
0.835
971741AH1-377 GEN
Solar/Wind Harmer
7.95
316222AC1-221 GEN
Solar/Wind Harmer
0.686
970301AG2-198 GEN
Solar/Wind Harmer
3.221
3144356SAPONY
Solar/Wind Helper
0.977
316240AF1-291 C
Solar/Wind Helper
0.173
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3151261ROARAP2
50/50
0.313
3151591KERR 2
50/50
0.272
316365GEN2_N
Solar/Wind Harmer
3.898
966621AG1-532 GEN
Solar/Wind Harmer
0.941
313506AB2-031 GEN
Solar/Wind Harmer
3.065
3147043LAWRENC
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.142
3145796HORNRTN
Solar/Wind Harmer
-0.036
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
315724AD1-057 GEN
Solar/Wind Harmer
1.567
316210AC1-098 GEN
Solar/Wind Harmer
3.469
316327AA2-057 GEN
Solar/Wind Harmer
2.181
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
0.434
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
8.106
316317KELFORD C
Solar/Wind Harmer
0.938
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3146073TAR RVR
Solar/Wind Harmer
-0.019
3146083TARBORO
Solar/Wind Harmer
-0.019
316463AE2-346 GEN
Solar/Wind Harmer
0.3
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.315
3146173TUNIS
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.221
961681AG1-008 GEN
Solar/Wind Harmer
14.221
3145893MURPHYS
Solar/Wind Harmer
0.125
3145893MURPHYS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.293
3156081AA2-088 GEN
Solar/Wind Harmer
5.454
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.85
316131AB2-060 GEN
Solar/Wind Harmer
1.577
964241AG1-285 GEN
Solar/Wind Harmer
10.88
3146206CASHIE
Solar/Wind Harmer
-0.014
3145963POPLR C
Solar/Wind Harmer
-0.013
315785AD2-033 C
Solar/Wind Harmer
2.894
970257AG2-171 GEN
Solar/Wind Harmer
4.626
959311AF2-222 GEN
Solar/Wind Harmer
12.552
315737AD1-076 GEN
Solar/Wind Harmer
2.17
971157AH1-035 GEN
Solar/Wind Harmer
1.377
963181AG1-167 GEN
Solar/Wind Harmer
0.957
3144293JTRSVLE
Adder
0.289
3147133PAMPLIN
Solar/Wind Harmer
-0.03
971193AH1-056 GEN
Solar/Wind Harmer
5.933
315614AA2-178 GEN
Solar/Wind Harmer
0.962
316248AF1-058 C
Solar/Wind Harmer
0.264
960061AF2-297 GEN
Solar/Wind Harmer
4.385
316478AD1-087 GEN
Solar/Wind Harmer
0.72
316486AD2-202 GEN
Solar/Wind Harmer
0.211
971683AH1-343 GEN
Solar/Wind Harmer
3.369
942461AE2-259 GEN
Solar/Wind Harmer
1.119
316283AC2-100 C
Solar/Wind Harmer
0.635
970909AG2-566 GEN
Solar/Wind Harmer
0.612
315839AE2-212 C
Solar/Wind Helper
0.202
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.344
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.843
MECLTFEXP_MEC->PJM
CLTF
1.401
SIGELTFEXP_SIGE->PJM
CLTF
0.042
CPLELTFEXP_CPLE->PJM
CLTF
4.654
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.01
LAGNLTFEXP_LAGN->PJM
CLTF
2.828
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.165
TVALTFEXP_TVA->PJM
CLTF
1.41
NYPJM->LTFIMP_NY
CLTF
0.512
LGEELTFEXP_LGEE->PJM
CLTF
0.508
WECLTFEXP_WEC->PJM
CLTF
0.264

Details for 6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.42 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1090.77
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3151261ROARAP2
50/50
0.313
3151591KERR 2
50/50
0.27
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3147043LAWRENC
50/50
3.141
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.27
3151581KERR 1
50/50
0.096
316023GEN1_S
Solar/Wind Harmer
3.902
960081AF2-299 GEN
Solar/Wind Harmer
5.22
971795AH1-408 GEN
Solar/Wind Harmer
29.849
316011AB1-132 GEN
Solar/Wind Harmer
8.002
962571AG1-106 GEN
Solar/Wind Harmer
5.498
3145796HORNRTN
Solar/Wind Harmer
-0.117
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145783HORNRTN
Solar/Wind Harmer
-0.028
315722AD1-056 GEN
Solar/Wind Harmer
2.841
316190AA2-174 GEN
Solar/Wind Harmer
0.332
316212AC1-099_GEN
Solar/Wind Harmer
1.923
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
-0.082
3145823KELFORD
Solar/Wind Harmer
-0.02
316359AB2-059 GEN
Solar/Wind Harmer
2.674
316049AB1-081 GEN
Solar/Wind Harmer
2.14
3142053HEARTS
Solar/Wind Harmer
0.233
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316129AC1-054 GEN
Solar/Wind Harmer
1.719
971065AG2-659 GEN
Solar/Wind Harmer
9.387
3145683EARLEYS
Solar/Wind Harmer
-0.019
961671AG1-007 GEN
Solar/Wind Harmer
0.234
3146083TARBORO
Solar/Wind Harmer
-0.018
3145493TOT1
Solar/Wind Harmer
0.549
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.072
3145893MURPHYS
Solar/Wind Harmer
0.534
316494AC1-189 GEN
Solar/Wind Harmer
1.84
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146293MARTNCO
Solar/Wind Harmer
0.091
316237AB2-079_GEN
Solar/Wind Harmer
0.437
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.442
316174AB2-169 GEN
Solar/Wind Harmer
2.088
3145963POPLR C
Solar/Wind Harmer
-0.013
970685AG2-442 GEN
Solar/Wind Harmer
9.773
970401AG2-262 GEN
Solar/Wind Harmer
0.729
963171AG1-166 GEN
Solar/Wind Harmer
1.268
971563AH1-280 GEN
Solar/Wind Harmer
1.268
3144293JTRSVLE
Adder
0.287
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.436
957481AF2-042 GEN
Solar/Wind Harmer
25.485
316003AC1-222 GEN
Solar/Wind Harmer
0.792
315693AD1-088 GEN
Solar/Wind Harmer
4.021
315687AD1-152 GEN
Solar/Wind Harmer
0.963
962491AG1-098 GEN
Solar/Wind Harmer
5.32
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.321
316181AB2-040 GEN
Solar/Wind Harmer
5.319
3145796HORNRTN
Solar/Wind Harmer
-0.106
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3145593CAROLNA
Solar/Wind Harmer
-0.029
3145593CAROLNA
Solar/Wind Harmer
-0.029
966811AG1-552 GEN
Solar/Wind Harmer
3.246
3145593CAROLNA
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
3.321
3145783HORNRTN
Solar/Wind Harmer
2.657
3145783HORNRTN
Solar/Wind Harmer
0.83
3145783HORNRTN
Solar/Wind Harmer
0.332
316426AA2-053 GEN
Solar/Wind Harmer
2.732
316274AC1-208 GEN
Solar/Wind Harmer
2.525
961601AG1-000A GEN
Solar/Wind Harmer
7.953
316263AC1-034 GEN
Solar/Wind Harmer
9.296
3145493TOT1
Solar/Wind Harmer
0.286
3145453TOT5
Solar/Wind Harmer
0.172
3145603CNETO
Solar/Wind Harmer
0.115
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.502
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.029
3145933PARMELE
Solar/Wind Harmer
-0.015
313527AB2-043 GEN
Solar/Wind Harmer
2.389
939181AE1-148 GEN
Solar/Wind Harmer
8.242
316065AD1-022 GEN
Solar/Wind Harmer
6.465
970323AG2-213 GEN
Solar/Wind Harmer
6.127
971775AH1-396 GEN
Solar/Wind Harmer
0.873
316034AC1-036 C
Solar/Wind Harmer
0.227
962561AG1-105 GEN
Solar/Wind Harmer
6.584
964791AG1-342 GEN
Solar/Wind Harmer
2.385
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
958211AF2-115 GEN
Solar/Wind Harmer
1.584
963191AG1-168 GEN
Solar/Wind Harmer
0.951
3144293JTRSVLE
Adder
0.287
3144293JTRSVLE
Adder
0.242
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.194
315742AE1-103 GEN
Solar/Wind Harmer
0.847
971741AH1-377 GEN
Solar/Wind Harmer
7.846
316222AC1-221 GEN
Solar/Wind Harmer
0.662
970301AG2-198 GEN
Solar/Wind Harmer
3.182
3144356SAPONY
Solar/Wind Helper
0.972
316240AF1-291 C
Solar/Wind Helper
0.168
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.27
3151621KERR 5
50/50
0.27
3151631KERR 6
50/50
0.27
3151641KERR 7
50/50
0.27
315814AE2-033 C
Solar/Wind Harmer
87.189
946281AF1-292 GEN
Solar/Wind Harmer
1.039
316087AB2-174 GEN
Solar/Wind Harmer
5.796
315652AC1-086 GEN
Solar/Wind Harmer
43.026
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.014
3137643SOCKMAN
Solar/Wind Harmer
-0.132
315607AA1-063A GEN
Solar/Wind Harmer
2.468
3146043SEABORD
Solar/Wind Harmer
-0.024
3146033SCOT NK
Solar/Wind Harmer
-0.084
316319Z2-044 C
Solar/Wind Harmer
1.139
970831AG2-522 GEN
Solar/Wind Harmer
10.247
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.162
961941AG1-037 GEN
Solar/Wind Harmer
0.139
3145513AHOSKIE
Solar/Wind Harmer
-0.018
3145573BETHELC
Solar/Wind Harmer
-0.018
3145573BETHELC
Solar/Wind Harmer
-0.018
316318V4-068
Solar/Wind Harmer
0.448
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
316420AA1-050 GEN
Solar/Wind Harmer
2.044
965291AG1-394 GEN
Solar/Wind Harmer
1.566
957861AF2-080 GEN
Solar/Wind Harmer
7.484
316005AA1-067
Solar/Wind Harmer
0.313
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
2.03
316239AB2-077_GEN
Solar/Wind Harmer
0.437
316238AB2-078_GEN
Solar/Wind Harmer
0.437
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
6.024
971443AH1-215 GEN
Solar/Wind Harmer
2.432
3144303KENBRDG
Solar/Wind Harmer
-0.01
315732AD1-074 GEN1
Solar/Wind Harmer
2.32
315733AD1-074 GEN2
Solar/Wind Harmer
2.32
315735AD1-075 GEN1
Solar/Wind Harmer
1.16
970683AG2-441 GEN
Solar/Wind Harmer
8.726
970681AG2-440 GEN
Solar/Wind Harmer
6.981
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
946301AF1-294 GEN
Solar/Wind Harmer
2.598
961791AG1-021 GEN
Solar/Wind Harmer
1.268
316118AC1-105 GEN
Solar/Wind Harmer
0.679
315657AE1-056 GEN
Solar/Wind Harmer
3.535
315816AE2-034 GEN
Solar/Wind Harmer
0.728
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
970865AG2-541 GEN
Solar/Wind Harmer
2.933
316315AB2-025 C
Solar/Wind Helper
0.826
3143316POE
Solar/Wind Helper
0.688
316365GEN2_N
Solar/Wind Harmer
3.902
966621AG1-532 GEN
Solar/Wind Harmer
0.942
313506AB2-031 GEN
Solar/Wind Harmer
3.065
3147043LAWRENC
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.142
3145796HORNRTN
Solar/Wind Harmer
-0.036
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
315724AD1-057 GEN
Solar/Wind Harmer
1.563
316210AC1-098 GEN
Solar/Wind Harmer
3.461
316327AA2-057 GEN
Solar/Wind Harmer
2.172
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
0.432
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
8.054
316317KELFORD C
Solar/Wind Harmer
0.938
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
316463AE2-346 GEN
Solar/Wind Harmer
0.3
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.318
3146073TAR RVR
Solar/Wind Harmer
-0.018
3146083TARBORO
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.25
961681AG1-008 GEN
Solar/Wind Harmer
14.25
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.297
3156081AA2-088 GEN
Solar/Wind Harmer
5.472
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.843
316131AB2-060 GEN
Solar/Wind Harmer
1.567
964241AG1-285 GEN
Solar/Wind Harmer
10.81
3146206CASHIE
Solar/Wind Harmer
-0.014
3145963POPLR C
Solar/Wind Harmer
-0.013
315785AD2-033 C
Solar/Wind Harmer
2.875
970257AG2-171 GEN
Solar/Wind Harmer
4.596
959311AF2-222 GEN
Solar/Wind Harmer
12.469
315737AD1-076 GEN
Solar/Wind Harmer
2.181
971157AH1-035 GEN
Solar/Wind Harmer
1.384
963181AG1-167 GEN
Solar/Wind Harmer
0.951
3144293JTRSVLE
Adder
0.287
3147133PAMPLIN
Solar/Wind Harmer
-0.029
971193AH1-056 GEN
Solar/Wind Harmer
5.892
315614AA2-178 GEN
Solar/Wind Harmer
0.971
316248AF1-058 C
Solar/Wind Harmer
0.26
960061AF2-297 GEN
Solar/Wind Harmer
4.312
316478AD1-087 GEN
Solar/Wind Harmer
0.709
316486AD2-202 GEN
Solar/Wind Harmer
0.208
971683AH1-343 GEN
Solar/Wind Harmer
3.31
942461AE2-259 GEN
Solar/Wind Harmer
1.111
316283AC2-100 C
Solar/Wind Harmer
0.613
970909AG2-566 GEN
Solar/Wind Harmer
0.604
315839AE2-212 C
Solar/Wind Helper
0.197
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.852
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.588
MECLTFEXP_MEC->PJM
CLTF
1.327
SIGELTFEXP_SIGE->PJM
CLTF
0.04
CPLELTFEXP_CPLE->PJM
CLTF
4.451
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.221
LAGNLTFEXP_LAGN->PJM
CLTF
2.679
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.709
TVALTFEXP_TVA->PJM
CLTF
1.336
NYPJM->LTFIMP_NY
CLTF
0.49
LGEELTFEXP_LGEE->PJM
CLTF
0.481
WECLTFEXP_WEC->PJM
CLTF
0.25

Details for 6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.42 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1090.77
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3147043LAWRENC
50/50
3.141
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.27
3151581KERR 1
50/50
0.096
316023GEN1_S
Solar/Wind Harmer
3.902
960081AF2-299 GEN
Solar/Wind Harmer
5.22
971795AH1-408 GEN
Solar/Wind Harmer
29.849
316011AB1-132 GEN
Solar/Wind Harmer
8.002
962571AG1-106 GEN
Solar/Wind Harmer
5.498
3145796HORNRTN
Solar/Wind Harmer
-0.117
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145783HORNRTN
Solar/Wind Harmer
-0.028
315722AD1-056 GEN
Solar/Wind Harmer
2.841
316190AA2-174 GEN
Solar/Wind Harmer
0.332
316212AC1-099_GEN
Solar/Wind Harmer
1.923
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
-0.082
3145823KELFORD
Solar/Wind Harmer
-0.02
316359AB2-059 GEN
Solar/Wind Harmer
2.674
316049AB1-081 GEN
Solar/Wind Harmer
2.14
3142053HEARTS
Solar/Wind Harmer
0.233
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316129AC1-054 GEN
Solar/Wind Harmer
1.719
971065AG2-659 GEN
Solar/Wind Harmer
9.387
3145683EARLEYS
Solar/Wind Harmer
-0.019
961671AG1-007 GEN
Solar/Wind Harmer
0.234
3146083TARBORO
Solar/Wind Harmer
-0.018
3145493TOT1
Solar/Wind Harmer
0.549
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.072
3145893MURPHYS
Solar/Wind Harmer
0.534
316494AC1-189 GEN
Solar/Wind Harmer
1.84
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146293MARTNCO
Solar/Wind Harmer
0.091
316237AB2-079_GEN
Solar/Wind Harmer
0.437
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.442
316174AB2-169 GEN
Solar/Wind Harmer
2.088
3145963POPLR C
Solar/Wind Harmer
-0.013
970685AG2-442 GEN
Solar/Wind Harmer
9.773
970401AG2-262 GEN
Solar/Wind Harmer
0.729
963171AG1-166 GEN
Solar/Wind Harmer
1.268
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.27
3151621KERR 5
50/50
0.27
3151631KERR 6
50/50
0.27
3151641KERR 7
50/50
0.27
315814AE2-033 C
Solar/Wind Harmer
87.189
946281AF1-292 GEN
Solar/Wind Harmer
1.039
316087AB2-174 GEN
Solar/Wind Harmer
5.796
315652AC1-086 GEN
Solar/Wind Harmer
43.026
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.014
3137643SOCKMAN
Solar/Wind Harmer
-0.132
315607AA1-063A GEN
Solar/Wind Harmer
2.468
3146043SEABORD
Solar/Wind Harmer
-0.024
3146033SCOT NK
Solar/Wind Harmer
-0.084
316319Z2-044 C
Solar/Wind Harmer
1.139
970831AG2-522 GEN
Solar/Wind Harmer
10.247
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.162
961941AG1-037 GEN
Solar/Wind Harmer
0.139
3145513AHOSKIE
Solar/Wind Harmer
-0.018
3145573BETHELC
Solar/Wind Harmer
-0.018
3145573BETHELC
Solar/Wind Harmer
-0.018
316318V4-068
Solar/Wind Harmer
0.448
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
316420AA1-050 GEN
Solar/Wind Harmer
2.044
965291AG1-394 GEN
Solar/Wind Harmer
1.566
957861AF2-080 GEN
Solar/Wind Harmer
7.484
316005AA1-067
Solar/Wind Harmer
0.313
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
2.03
316239AB2-077_GEN
Solar/Wind Harmer
0.437
316238AB2-078_GEN
Solar/Wind Harmer
0.437
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
6.024
971443AH1-215 GEN
Solar/Wind Harmer
2.432
3144303KENBRDG
Solar/Wind Harmer
-0.01
315732AD1-074 GEN1
Solar/Wind Harmer
2.32
315733AD1-074 GEN2
Solar/Wind Harmer
2.32
315735AD1-075 GEN1
Solar/Wind Harmer
1.16
970683AG2-441 GEN
Solar/Wind Harmer
8.726
970681AG2-440 GEN
Solar/Wind Harmer
6.981
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
946301AF1-294 GEN
Solar/Wind Harmer
2.598
961791AG1-021 GEN
Solar/Wind Harmer
1.268
316118AC1-105 GEN
Solar/Wind Harmer
0.679
315657AE1-056 GEN
Solar/Wind Harmer
3.535
315816AE2-034 GEN
Solar/Wind Harmer
0.728
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
970865AG2-541 GEN
Solar/Wind Harmer
2.933
316315AB2-025 C
Solar/Wind Helper
0.826
3143316POE
Solar/Wind Helper
0.688
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.321
316181AB2-040 GEN
Solar/Wind Harmer
5.319
3145796HORNRTN
Solar/Wind Harmer
-0.106
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3145593CAROLNA
Solar/Wind Harmer
-0.029
3145593CAROLNA
Solar/Wind Harmer
-0.029
966811AG1-552 GEN
Solar/Wind Harmer
3.246
3145593CAROLNA
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
3.321
3145783HORNRTN
Solar/Wind Harmer
2.657
3145783HORNRTN
Solar/Wind Harmer
0.83
3145783HORNRTN
Solar/Wind Harmer
0.332
316426AA2-053 GEN
Solar/Wind Harmer
2.732
316274AC1-208 GEN
Solar/Wind Harmer
2.525
961601AG1-000A GEN
Solar/Wind Harmer
7.953
316263AC1-034 GEN
Solar/Wind Harmer
9.296
3145493TOT1
Solar/Wind Harmer
0.286
3145453TOT5
Solar/Wind Harmer
0.172
3145603CNETO
Solar/Wind Harmer
0.115
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.502
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.029
3145933PARMELE
Solar/Wind Harmer
-0.015
313527AB2-043 GEN
Solar/Wind Harmer
2.389
939181AE1-148 GEN
Solar/Wind Harmer
8.242
316065AD1-022 GEN
Solar/Wind Harmer
6.465
970323AG2-213 GEN
Solar/Wind Harmer
6.127
971775AH1-396 GEN
Solar/Wind Harmer
0.873
316034AC1-036 C
Solar/Wind Harmer
0.227
962561AG1-105 GEN
Solar/Wind Harmer
6.584
964791AG1-342 GEN
Solar/Wind Harmer
2.385
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
958211AF2-115 GEN
Solar/Wind Harmer
1.584
963191AG1-168 GEN
Solar/Wind Harmer
0.951
3144293JTRSVLE
Adder
0.287
3144293JTRSVLE
Adder
0.242
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.194
315742AE1-103 GEN
Solar/Wind Harmer
0.847
971741AH1-377 GEN
Solar/Wind Harmer
7.846
316222AC1-221 GEN
Solar/Wind Harmer
0.662
970301AG2-198 GEN
Solar/Wind Harmer
3.182
3144356SAPONY
Solar/Wind Helper
0.972
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3151261ROARAP2
50/50
0.313
3151591KERR 2
50/50
0.27
316365GEN2_N
Solar/Wind Harmer
3.902
966621AG1-532 GEN
Solar/Wind Harmer
0.942
313506AB2-031 GEN
Solar/Wind Harmer
3.065
3147043LAWRENC
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.142
3145796HORNRTN
Solar/Wind Harmer
-0.036
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
315724AD1-057 GEN
Solar/Wind Harmer
1.563
316210AC1-098 GEN
Solar/Wind Harmer
3.461
316327AA2-057 GEN
Solar/Wind Harmer
2.172
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
0.432
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
8.054
316317KELFORD C
Solar/Wind Harmer
0.938
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
316463AE2-346 GEN
Solar/Wind Harmer
0.3
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.318
3146073TAR RVR
Solar/Wind Harmer
-0.018
3146083TARBORO
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.25
961681AG1-008 GEN
Solar/Wind Harmer
14.25
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.297
3156081AA2-088 GEN
Solar/Wind Harmer
5.472
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.843
316131AB2-060 GEN
Solar/Wind Harmer
1.567
964241AG1-285 GEN
Solar/Wind Harmer
10.81
3146206CASHIE
Solar/Wind Harmer
-0.014
3145963POPLR C
Solar/Wind Harmer
-0.013
315785AD2-033 C
Solar/Wind Harmer
2.875
970257AG2-171 GEN
Solar/Wind Harmer
4.596
959311AF2-222 GEN
Solar/Wind Harmer
12.469
315737AD1-076 GEN
Solar/Wind Harmer
2.181
971157AH1-035 GEN
Solar/Wind Harmer
1.384
963181AG1-167 GEN
Solar/Wind Harmer
0.951
3144293JTRSVLE
Adder
0.287
3147133PAMPLIN
Solar/Wind Harmer
-0.029
971193AH1-056 GEN
Solar/Wind Harmer
5.892
315614AA2-178 GEN
Solar/Wind Harmer
0.971
316248AF1-058 C
Solar/Wind Harmer
0.26
960061AF2-297 GEN
Solar/Wind Harmer
4.312
316478AD1-087 GEN
Solar/Wind Harmer
0.709
316486AD2-202 GEN
Solar/Wind Harmer
0.208
971683AH1-343 GEN
Solar/Wind Harmer
3.31
942461AE2-259 GEN
Solar/Wind Harmer
1.111
316283AC2-100 C
Solar/Wind Harmer
0.613
970909AG2-566 GEN
Solar/Wind Harmer
0.604
315839AE2-212 C
Solar/Wind Helper
0.197
316240AF1-291 C
Solar/Wind Helper
0.168
971563AH1-280 GEN
Solar/Wind Harmer
1.268
3144293JTRSVLE
Adder
0.287
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.436
957481AF2-042 GEN
Solar/Wind Harmer
25.486
316003AC1-222 GEN
Solar/Wind Harmer
0.792
315693AD1-088 GEN
Solar/Wind Harmer
4.021
315687AD1-152 GEN
Solar/Wind Harmer
0.963
962491AG1-098 GEN
Solar/Wind Harmer
5.32
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.852
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.588
MECLTFEXP_MEC->PJM
CLTF
1.327
SIGELTFEXP_SIGE->PJM
CLTF
0.04
CPLELTFEXP_CPLE->PJM
CLTF
4.451
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.221
LAGNLTFEXP_LAGN->PJM
CLTF
2.679
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.709
TVALTFEXP_TVA->PJM
CLTF
1.336
NYPJM->LTFIMP_NY
CLTF
0.49
LGEELTFEXP_LGEE->PJM
CLTF
0.481
WECLTFEXP_WEC->PJM
CLTF
0.25

Details for 6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.4 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1090.63
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3147043LAWRENC
50/50
3.141
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.27
3151581KERR 1
50/50
0.096
316023GEN1_S
Solar/Wind Harmer
3.902
960081AF2-299 GEN
Solar/Wind Harmer
5.22
971795AH1-408 GEN
Solar/Wind Harmer
29.849
316011AB1-132 GEN
Solar/Wind Harmer
8.002
962571AG1-106 GEN
Solar/Wind Harmer
5.498
3145796HORNRTN
Solar/Wind Harmer
-0.117
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145783HORNRTN
Solar/Wind Harmer
-0.028
315722AD1-056 GEN
Solar/Wind Harmer
2.841
316190AA2-174 GEN
Solar/Wind Harmer
0.332
316212AC1-099_GEN
Solar/Wind Harmer
1.922
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
-0.082
3145823KELFORD
Solar/Wind Harmer
-0.02
316359AB2-059 GEN
Solar/Wind Harmer
2.673
316049AB1-081 GEN
Solar/Wind Harmer
2.14
3142053HEARTS
Solar/Wind Harmer
0.233
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316129AC1-054 GEN
Solar/Wind Harmer
1.719
971065AG2-659 GEN
Solar/Wind Harmer
9.387
3145683EARLEYS
Solar/Wind Harmer
-0.019
961671AG1-007 GEN
Solar/Wind Harmer
0.234
3146083TARBORO
Solar/Wind Harmer
-0.018
3145493TOT1
Solar/Wind Harmer
0.549
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.072
3145893MURPHYS
Solar/Wind Harmer
0.534
316494AC1-189 GEN
Solar/Wind Harmer
1.84
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146293MARTNCO
Solar/Wind Harmer
0.091
316237AB2-079_GEN
Solar/Wind Harmer
0.437
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.442
316174AB2-169 GEN
Solar/Wind Harmer
2.088
3145963POPLR C
Solar/Wind Harmer
-0.013
970685AG2-442 GEN
Solar/Wind Harmer
9.777
970401AG2-262 GEN
Solar/Wind Harmer
0.729
963171AG1-166 GEN
Solar/Wind Harmer
1.268
971563AH1-280 GEN
Solar/Wind Harmer
1.268
3144293JTRSVLE
Adder
0.287
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.436
957481AF2-042 GEN
Solar/Wind Harmer
25.422
316003AC1-222 GEN
Solar/Wind Harmer
0.792
315693AD1-088 GEN
Solar/Wind Harmer
4.029
315687AD1-152 GEN
Solar/Wind Harmer
0.962
962491AG1-098 GEN
Solar/Wind Harmer
5.33
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.321
316181AB2-040 GEN
Solar/Wind Harmer
5.319
3145796HORNRTN
Solar/Wind Harmer
-0.106
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3145593CAROLNA
Solar/Wind Harmer
-0.029
3145593CAROLNA
Solar/Wind Harmer
-0.029
966811AG1-552 GEN
Solar/Wind Harmer
3.246
3145593CAROLNA
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
3.321
3145783HORNRTN
Solar/Wind Harmer
2.657
3145783HORNRTN
Solar/Wind Harmer
0.83
3145783HORNRTN
Solar/Wind Harmer
0.332
316426AA2-053 GEN
Solar/Wind Harmer
2.732
316274AC1-208 GEN
Solar/Wind Harmer
2.525
961601AG1-000A GEN
Solar/Wind Harmer
7.953
316263AC1-034 GEN
Solar/Wind Harmer
9.295
3145493TOT1
Solar/Wind Harmer
0.286
3145453TOT5
Solar/Wind Harmer
0.172
3145603CNETO
Solar/Wind Harmer
0.115
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.502
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.029
3145933PARMELE
Solar/Wind Harmer
-0.015
313527AB2-043 GEN
Solar/Wind Harmer
2.389
939181AE1-148 GEN
Solar/Wind Harmer
8.243
316065AD1-022 GEN
Solar/Wind Harmer
6.465
970323AG2-213 GEN
Solar/Wind Harmer
6.129
971775AH1-396 GEN
Solar/Wind Harmer
0.873
316034AC1-036 C
Solar/Wind Harmer
0.227
962561AG1-105 GEN
Solar/Wind Harmer
6.583
964791AG1-342 GEN
Solar/Wind Harmer
2.385
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
958211AF2-115 GEN
Solar/Wind Harmer
1.585
963191AG1-168 GEN
Solar/Wind Harmer
0.951
3144293JTRSVLE
Adder
0.287
3144293JTRSVLE
Adder
0.242
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.169
315742AE1-103 GEN
Solar/Wind Harmer
0.847
971741AH1-377 GEN
Solar/Wind Harmer
7.86
316222AC1-221 GEN
Solar/Wind Harmer
0.662
970301AG2-198 GEN
Solar/Wind Harmer
3.187
3144356SAPONY
Solar/Wind Helper
0.972
316240AF1-291 C
Solar/Wind Helper
0.168
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.27
3151621KERR 5
50/50
0.27
3151631KERR 6
50/50
0.27
3151641KERR 7
50/50
0.27
315814AE2-033 C
Solar/Wind Harmer
87.189
946281AF1-292 GEN
Solar/Wind Harmer
1.039
316087AB2-174 GEN
Solar/Wind Harmer
5.796
315652AC1-086 GEN
Solar/Wind Harmer
43.026
3145796HORNRTN
Solar/Wind Harmer
-0.113
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3145796HORNRTN
Solar/Wind Harmer
-0.014
3137643SOCKMAN
Solar/Wind Harmer
-0.132
315607AA1-063A GEN
Solar/Wind Harmer
2.468
3146043SEABORD
Solar/Wind Harmer
-0.024
3146033SCOT NK
Solar/Wind Harmer
-0.084
316319Z2-044 C
Solar/Wind Harmer
1.139
970831AG2-522 GEN
Solar/Wind Harmer
10.247
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.162
961941AG1-037 GEN
Solar/Wind Harmer
0.139
3145513AHOSKIE
Solar/Wind Harmer
-0.018
3145573BETHELC
Solar/Wind Harmer
-0.018
3145573BETHELC
Solar/Wind Harmer
-0.018
316318V4-068
Solar/Wind Harmer
0.448
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
316420AA1-050 GEN
Solar/Wind Harmer
2.044
965291AG1-394 GEN
Solar/Wind Harmer
1.566
957861AF2-080 GEN
Solar/Wind Harmer
7.483
316005AA1-067
Solar/Wind Harmer
0.313
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
2.03
316239AB2-077_GEN
Solar/Wind Harmer
0.437
316238AB2-078_GEN
Solar/Wind Harmer
0.437
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
6.024
971443AH1-215 GEN
Solar/Wind Harmer
2.433
3144303KENBRDG
Solar/Wind Harmer
-0.01
315732AD1-074 GEN1
Solar/Wind Harmer
2.32
315733AD1-074 GEN2
Solar/Wind Harmer
2.32
315735AD1-075 GEN1
Solar/Wind Harmer
1.16
970683AG2-441 GEN
Solar/Wind Harmer
8.729
970681AG2-440 GEN
Solar/Wind Harmer
6.983
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
946301AF1-294 GEN
Solar/Wind Harmer
2.6
961791AG1-021 GEN
Solar/Wind Harmer
1.268
316118AC1-105 GEN
Solar/Wind Harmer
0.679
315657AE1-056 GEN
Solar/Wind Harmer
3.537
315816AE2-034 GEN
Solar/Wind Harmer
0.728
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
970865AG2-541 GEN
Solar/Wind Harmer
2.932
316315AB2-025 C
Solar/Wind Helper
0.826
3143316POE
Solar/Wind Helper
0.688
3151261ROARAP2
50/50
0.313
3151591KERR 2
50/50
0.27
316365GEN2_N
Solar/Wind Harmer
3.902
966621AG1-532 GEN
Solar/Wind Harmer
0.942
313506AB2-031 GEN
Solar/Wind Harmer
3.065
3147043LAWRENC
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.142
3145796HORNRTN
Solar/Wind Harmer
-0.036
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
315724AD1-057 GEN
Solar/Wind Harmer
1.563
316210AC1-098 GEN
Solar/Wind Harmer
3.461
316327AA2-057 GEN
Solar/Wind Harmer
2.172
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
0.432
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
8.053
316317KELFORD C
Solar/Wind Harmer
0.938
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
316463AE2-346 GEN
Solar/Wind Harmer
0.3
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.318
3146073TAR RVR
Solar/Wind Harmer
-0.018
3146083TARBORO
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.25
961681AG1-008 GEN
Solar/Wind Harmer
14.25
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.297
3156081AA2-088 GEN
Solar/Wind Harmer
5.472
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.843
316131AB2-060 GEN
Solar/Wind Harmer
1.567
964241AG1-285 GEN
Solar/Wind Harmer
10.812
3146206CASHIE
Solar/Wind Harmer
-0.014
3145963POPLR C
Solar/Wind Harmer
-0.013
315785AD2-033 C
Solar/Wind Harmer
2.876
970257AG2-171 GEN
Solar/Wind Harmer
4.597
959311AF2-222 GEN
Solar/Wind Harmer
12.472
315737AD1-076 GEN
Solar/Wind Harmer
2.181
971157AH1-035 GEN
Solar/Wind Harmer
1.384
963181AG1-167 GEN
Solar/Wind Harmer
0.951
3144293JTRSVLE
Adder
0.287
3147133PAMPLIN
Solar/Wind Harmer
-0.029
971193AH1-056 GEN
Solar/Wind Harmer
5.895
315614AA2-178 GEN
Solar/Wind Harmer
0.971
316248AF1-058 C
Solar/Wind Harmer
0.26
960061AF2-297 GEN
Solar/Wind Harmer
4.309
316478AD1-087 GEN
Solar/Wind Harmer
0.709
316486AD2-202 GEN
Solar/Wind Harmer
0.207
971683AH1-343 GEN
Solar/Wind Harmer
3.309
942461AE2-259 GEN
Solar/Wind Harmer
1.112
316283AC2-100 C
Solar/Wind Harmer
0.612
970909AG2-566 GEN
Solar/Wind Harmer
0.605
315839AE2-212 C
Solar/Wind Helper
0.197
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.85
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.587
MECLTFEXP_MEC->PJM
CLTF
1.327
SIGELTFEXP_SIGE->PJM
CLTF
0.04
CPLELTFEXP_CPLE->PJM
CLTF
4.45
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.218
LAGNLTFEXP_LAGN->PJM
CLTF
2.678
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.707
TVALTFEXP_TVA->PJM
CLTF
1.336
NYPJM->LTFIMP_NY
CLTF
0.49
LGEELTFEXP_LGEE->PJM
CLTF
0.481
WECLTFEXP_WEC->PJM
CLTF
0.25

Details for 6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2012-54_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2012-54_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:117.86 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:978.27
MW Contribution:2.08
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
1.161
3151411GASTONB
50/50
1.161
3147043LAWRENC
50/50
3.414
3151261ROARAP2
50/50
0.385
3151601KERR 3
50/50
0.246
3151581KERR 1
50/50
0.088
316023GEN1_S
Solar/Wind Harmer
4.384
960081AF2-299 GEN
Solar/Wind Harmer
5.827
316011AB1-132 GEN
Solar/Wind Harmer
10.086
962571AG1-106 GEN
Solar/Wind Harmer
6.93
3145796HORNRTN
Solar/Wind Harmer
-0.146
3145796HORNRTN
Solar/Wind Harmer
-0.044
971795AH1-408 GEN
Solar/Wind Harmer
32.769
316190AA2-174 GEN
Solar/Wind Harmer
0.426
3145783HORNRTN
Solar/Wind Harmer
-0.033
315722AD1-056 GEN
Solar/Wind Harmer
3.384
3146233WITAKRS
Solar/Wind Harmer
-0.088
316359AB2-059 GEN
Solar/Wind Harmer
2.933
316049AB1-081 GEN
Solar/Wind Harmer
2.347
3142053HEARTS
Solar/Wind Harmer
0.256
316212AC1-099_GEN
Solar/Wind Harmer
1.883
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3145543BTLEBRO
Solar/Wind Harmer
-0.017
316129AC1-054 GEN
Solar/Wind Harmer
1.824
971065AG2-659 GEN
Solar/Wind Harmer
9.783
961671AG1-007 GEN
Solar/Wind Harmer
0.231
3146083TARBORO
Solar/Wind Harmer
-0.018
3145493TOT1
Solar/Wind Harmer
0.543
3145893MURPHYS
Solar/Wind Harmer
-0.061
3151281ROARAP4
50/50
0.374
3151281ROARAP4
50/50
0.35
3151611KERR 4
50/50
0.246
3151621KERR 5
50/50
0.246
3151631KERR 6
50/50
0.246
3151641KERR 7
50/50
0.246
315814AE2-033 C
Solar/Wind Harmer
90.6
946281AF1-292 GEN
Solar/Wind Harmer
1.16
315652AC1-086 GEN
Solar/Wind Harmer
54.232
316087AB2-174 GEN
Solar/Wind Harmer
6.587
3145796HORNRTN
Solar/Wind Harmer
-0.141
3145796HORNRTN
Solar/Wind Harmer
-0.018
3137643SOCKMAN
Solar/Wind Harmer
-0.154
315607AA1-063A GEN
Solar/Wind Harmer
2.838
3146043SEABORD
Solar/Wind Harmer
-0.027
316319Z2-044 C
Solar/Wind Harmer
1.232
970831AG2-522 GEN
Solar/Wind Harmer
11.073
3145573BETHELC
Solar/Wind Harmer
-0.018
3145573BETHELC
Solar/Wind Harmer
-0.018
3146033SCOT NK
Solar/Wind Harmer
-0.072
965291AG1-394 GEN
Solar/Wind Harmer
1.593
316420AA1-050 GEN
Solar/Wind Harmer
1.925
316318V4-068
Solar/Wind Harmer
0.381
3145893MURPHYS
Solar/Wind Harmer
-0.041
3151361ROSEMG1
50/50
1.426
3151391GASTONA
50/50
1.161
3151411GASTONB
50/50
1.161
3151261ROARAP2
50/50
0.376
3151591KERR 2
50/50
0.246
316365GEN2_N
Solar/Wind Harmer
4.384
966621AG1-532 GEN
Solar/Wind Harmer
1.051
3145796HORNRTN
Solar/Wind Harmer
-0.177
3145796HORNRTN
Solar/Wind Harmer
-0.044
313506AB2-031 GEN
Solar/Wind Harmer
3.516
3147043LAWRENC
Solar/Wind Harmer
-0.024
315724AD1-057 GEN
Solar/Wind Harmer
1.861
316327AA2-057 GEN
Solar/Wind Harmer
2.326
961601AG1-000A GEN
Solar/Wind Harmer
8.903
3146233WITAKRS
Solar/Wind Harmer
0.467
3146233WITAKRS
Solar/Wind Harmer
-0.015
3138543CONSLDL
Solar/Wind Harmer
-0.015
316210AC1-098 GEN
Solar/Wind Harmer
3.389
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3146073TAR RVR
Solar/Wind Harmer
-0.018
3146083TARBORO
Solar/Wind Harmer
-0.018
3156081AA2-088 GEN
Solar/Wind Harmer
5.553
3151371ROSEMS1
50/50
0.883
3151381ROSEMG2
50/50
0.668
970535AG2-341 GEN
50/50
2.078
3145796HORNRTN
Solar/Wind Harmer
-0.133
316181AB2-040 GEN
Solar/Wind Harmer
6.101
316426AA2-053 GEN
Solar/Wind Harmer
3.505
3145593CAROLNA
Solar/Wind Harmer
-0.035
3145593CAROLNA
Solar/Wind Harmer
-0.035
966811AG1-552 GEN
Solar/Wind Harmer
3.903
3145593CAROLNA
Solar/Wind Harmer
0.288
3145783HORNRTN
Solar/Wind Harmer
3.938
3145783HORNRTN
Solar/Wind Harmer
3.15
3145783HORNRTN
Solar/Wind Harmer
0.985
3145783HORNRTN
Solar/Wind Harmer
0.394
316274AC1-208 GEN
Solar/Wind Harmer
2.719
961601AG1-000A GEN
Solar/Wind Harmer
8.791
316263AC1-034 GEN
Solar/Wind Harmer
10.196
3145493TOT1
Solar/Wind Harmer
0.283
3145453TOT5
Solar/Wind Harmer
0.17
3145603CNETO
Solar/Wind Harmer
0.113
3145893MURPHYS
Solar/Wind Harmer
0.426
3145893MURPHYS
Solar/Wind Harmer
-0.027
939181AE1-148 GEN
Solar/Wind Harmer
7.468
313527AB2-043 GEN
Solar/Wind Harmer
2.093
3146173TUNIS
Solar/Wind Harmer
-0.013
3146173TUNIS
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.02
3145933PARMELE
Solar/Wind Harmer
-0.01
970323AG2-213 GEN
Solar/Wind Harmer
5.007
971775AH1-396 GEN
Solar/Wind Harmer
0.713
316034AC1-036 C
Solar/Wind Harmer
0.185
962561AG1-105 GEN
Solar/Wind Harmer
5.198
964791AG1-342 GEN
Solar/Wind Harmer
1.834
3146843MT LREL
Solar/Wind Harmer
-0.009
3146843MT LREL
Solar/Wind Harmer
-0.009
315742AE1-103 GEN
Solar/Wind Harmer
0.81
958211AF2-115 GEN
Solar/Wind Harmer
1.177
963191AG1-168 GEN
Solar/Wind Harmer
0.706
3144293JTRSVLE
Adder
0.213
3144293JTRSVLE
Adder
0.18
3147133PAMPLIN
Solar/Wind Harmer
-0.007
3147133PAMPLIN
Solar/Wind Harmer
-0.005
3144356SAPONY
Solar/Wind Helper
0.862
3145893MURPHYS
Solar/Wind Harmer
0.453
316494AC1-189 GEN
Solar/Wind Harmer
1.612
3145823KELFORD
Solar/Wind Harmer
-0.014
316237AB2-079_GEN
Solar/Wind Harmer
0.382
3146173TUNIS
Solar/Wind Harmer
-0.013
3145746EVERETS
Solar/Wind Harmer
-0.011
3145746EVERETS
Solar/Wind Harmer
-0.011
3146293MARTNCO
Solar/Wind Harmer
0.062
3145683EARLEYS
Solar/Wind Harmer
-0.01
970685AG2-442 GEN
Solar/Wind Harmer
7.649
970401AG2-262 GEN
Solar/Wind Harmer
0.56
316174AB2-169 GEN
Solar/Wind Harmer
1.265
3145963POPLR C
Solar/Wind Harmer
-0.008
963171AG1-166 GEN
Solar/Wind Harmer
0.942
971563AH1-280 GEN
Solar/Wind Harmer
0.942
3144293JTRSVLE
Adder
0.213
3145893MURPHYS
Solar/Wind Harmer
0.107
3145893MURPHYS
Solar/Wind Harmer
-0.015
957521AF2-046 GEN
Solar/Wind Harmer
11.382
961681AG1-008 GEN
Solar/Wind Harmer
11.382
316317KELFORD C
Solar/Wind Harmer
0.654
3145823KELFORD
Solar/Wind Harmer
-0.014
316131AB2-060 GEN
Solar/Wind Harmer
1.368
3146173TUNIS
Solar/Wind Harmer
-0.013
964241AG1-285 GEN
Solar/Wind Harmer
9.271
3145746EVERETS
Solar/Wind Harmer
-0.011
3145746EVERETS
Solar/Wind Harmer
-0.011
316463AE2-346 GEN
Solar/Wind Harmer
0.178
316140AB2-099
Solar/Wind Harmer
0.074
962331AG1-082 GEN
Solar/Wind Harmer
1.372
315785AD2-033 C
Solar/Wind Harmer
2.384
3145933PARMELE
Solar/Wind Harmer
-0.01
966801AG1-551 GEN
Solar/Wind Harmer
1.254
970257AG2-171 GEN
Solar/Wind Harmer
3.755
959311AF2-222 GEN
Solar/Wind Harmer
10.074
3145963POPLR C
Solar/Wind Harmer
-0.008
963181AG1-167 GEN
Solar/Wind Harmer
0.706
3144293JTRSVLE
Adder
0.213
3156021HOLLOMANSOL
Solar/Wind Harmer
0.928
3147133PAMPLIN
Solar/Wind Harmer
-0.021
971193AH1-056 GEN
Solar/Wind Harmer
4.188
315839AE2-212 C
Solar/Wind Helper
0.172
3145893MURPHYS
Solar/Wind Harmer
-0.015
957861AF2-080 GEN
Solar/Wind Harmer
6.557
316239AB2-077_GEN
Solar/Wind Harmer
0.382
316238AB2-078_GEN
Solar/Wind Harmer
0.382
316005AA1-067
Solar/Wind Harmer
0.225
3145746EVERETS
Solar/Wind Harmer
-0.044
3145746EVERETS
Solar/Wind Harmer
-0.011
3145746EVERETS
Solar/Wind Harmer
-0.011
3145746EVERETS
Solar/Wind Harmer
-0.011
970181AG2-120 GEN
Solar/Wind Harmer
1.46
3145513AHOSKIE
Solar/Wind Harmer
0.096
961941AG1-037 GEN
Solar/Wind Harmer
0.082
3145513AHOSKIE
Solar/Wind Harmer
-0.011
971443AH1-215 GEN
Solar/Wind Harmer
1.994
3144303KENBRDG
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.01
970683AG2-441 GEN
Solar/Wind Harmer
6.829
970681AG2-440 GEN
Solar/Wind Harmer
5.464
946301AF1-294 GEN
Solar/Wind Harmer
1.931
961791AG1-021 GEN
Solar/Wind Harmer
0.942
316118AC1-105 GEN
Solar/Wind Harmer
0.483
315657AE1-056 GEN
Solar/Wind Harmer
2.513
316315AB2-025 C
Solar/Wind Helper
0.732
3143316POE
Solar/Wind Helper
0.597
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.796
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.185
MECLTFEXP_MEC->PJM
CLTF
1.187
SIGELTFEXP_SIGE->PJM
CLTF
0.035
CPLELTFEXP_CPLE->PJM
CLTF
4.184
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.918
LAGNLTFEXP_LAGN->PJM
CLTF
2.459
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.164
TVALTFEXP_TVA->PJM
CLTF
1.224
NYPJM->LTFIMP_NY
CLTF
0.447
LGEELTFEXP_LGEE->PJM
CLTF
0.424
WECLTFEXP_WEC->PJM
CLTF
0.221

Details for 6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 1010-2012_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 1010-2012_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:116.91 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:970.32
MW Contribution:2.14
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
1.178
3151411GASTONB
50/50
1.178
3147043LAWRENC
50/50
3.466
3151261ROARAP2
50/50
0.401
3151601KERR 3
50/50
0.255
3151581KERR 1
50/50
0.091
316023GEN1_S
Solar/Wind Harmer
4.421
960081AF2-299 GEN
Solar/Wind Harmer
5.909
316011AB1-132 GEN
Solar/Wind Harmer
10.237
962571AG1-106 GEN
Solar/Wind Harmer
7.034
3145796HORNRTN
Solar/Wind Harmer
-0.148
3145796HORNRTN
Solar/Wind Harmer
-0.045
971795AH1-408 GEN
Solar/Wind Harmer
33.253
3145783HORNRTN
Solar/Wind Harmer
-0.034
315722AD1-056 GEN
Solar/Wind Harmer
3.448
316190AA2-174 GEN
Solar/Wind Harmer
0.39
3146233WITAKRS
Solar/Wind Harmer
-0.091
316212AC1-099_GEN
Solar/Wind Harmer
1.994
316359AB2-059 GEN
Solar/Wind Harmer
3.015
316049AB1-081 GEN
Solar/Wind Harmer
2.413
3142053HEARTS
Solar/Wind Harmer
0.263
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3145543BTLEBRO
Solar/Wind Harmer
-0.018
316129AC1-054 GEN
Solar/Wind Harmer
1.896
971065AG2-659 GEN
Solar/Wind Harmer
10.164
961671AG1-007 GEN
Solar/Wind Harmer
0.238
3146083TARBORO
Solar/Wind Harmer
-0.019
3145493TOT1
Solar/Wind Harmer
0.559
3151281ROARAP4
50/50
0.39
3151281ROARAP4
50/50
0.365
3151611KERR 4
50/50
0.255
3151621KERR 5
50/50
0.255
3151631KERR 6
50/50
0.255
3151641KERR 7
50/50
0.255
315814AE2-033 C
Solar/Wind Harmer
90.779
946281AF1-292 GEN
Solar/Wind Harmer
1.176
315652AC1-086 GEN
Solar/Wind Harmer
55.047
316087AB2-174 GEN
Solar/Wind Harmer
6.724
3145796HORNRTN
Solar/Wind Harmer
-0.144
3145796HORNRTN
Solar/Wind Harmer
-0.018
3137643SOCKMAN
Solar/Wind Harmer
-0.159
316319Z2-044 C
Solar/Wind Harmer
1.275
970831AG2-522 GEN
Solar/Wind Harmer
11.512
3146033SCOT NK
Solar/Wind Harmer
-0.078
3145573BETHELC
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
3151361ROSEMG1
50/50
1.448
3151371ROSEMS1
50/50
0.897
3151381ROSEMG2
50/50
0.678
970535AG2-341 GEN
50/50
2.143
3145796HORNRTN
Solar/Wind Harmer
-0.135
316181AB2-040 GEN
Solar/Wind Harmer
6.25
3145593CAROLNA
Solar/Wind Harmer
-0.036
3145593CAROLNA
Solar/Wind Harmer
-0.036
966811AG1-552 GEN
Solar/Wind Harmer
4.066
3145593CAROLNA
Solar/Wind Harmer
0.3
3145783HORNRTN
Solar/Wind Harmer
4.104
3145783HORNRTN
Solar/Wind Harmer
3.283
3145783HORNRTN
Solar/Wind Harmer
1.026
3145783HORNRTN
Solar/Wind Harmer
0.41
316426AA2-053 GEN
Solar/Wind Harmer
3.206
316274AC1-208 GEN
Solar/Wind Harmer
2.846
961601AG1-000A GEN
Solar/Wind Harmer
9.006
316263AC1-034 GEN
Solar/Wind Harmer
10.482
3145493TOT1
Solar/Wind Harmer
0.292
3145453TOT5
Solar/Wind Harmer
0.175
3146263WOODLND
Solar/Wind Harmer
-0.018
3145823KELFORD
Solar/Wind Harmer
-0.016
316494AC1-189 GEN
Solar/Wind Harmer
1.673
316237AB2-079_GEN
Solar/Wind Harmer
0.392
3145746EVERETS
Solar/Wind Harmer
-0.012
3145746EVERETS
Solar/Wind Harmer
-0.012
3145683EARLEYS
Solar/Wind Harmer
-0.012
3146293MARTNCO
Solar/Wind Harmer
0.065
970685AG2-442 GEN
Solar/Wind Harmer
7.857
3146173TUNIS
Solar/Wind Harmer
-0.009
970401AG2-262 GEN
Solar/Wind Harmer
0.576
316174AB2-169 GEN
Solar/Wind Harmer
1.341
3145963POPLR C
Solar/Wind Harmer
-0.008
963171AG1-166 GEN
Solar/Wind Harmer
0.968
971563AH1-280 GEN
Solar/Wind Harmer
0.968
3144293JTRSVLE
Adder
0.219
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.19
3146206CASHIE
Solar/Wind Harmer
-0.006
971547AH1-271 GEN
Solar/Wind Harmer
1.595
3151391GASTONA
50/50
1.178
3151411GASTONB
50/50
1.178
3151261ROARAP2
50/50
0.391
3151591KERR 2
50/50
0.255
316365GEN2_N
Solar/Wind Harmer
4.421
966621AG1-532 GEN
Solar/Wind Harmer
1.066
3145796HORNRTN
Solar/Wind Harmer
-0.18
3145796HORNRTN
Solar/Wind Harmer
-0.045
313506AB2-031 GEN
Solar/Wind Harmer
3.601
3147043LAWRENC
Solar/Wind Harmer
-0.024
315724AD1-057 GEN
Solar/Wind Harmer
1.896
316327AA2-057 GEN
Solar/Wind Harmer
2.42
3146233WITAKRS
Solar/Wind Harmer
0.483
3146233WITAKRS
Solar/Wind Harmer
-0.016
3138543CONSLDL
Solar/Wind Harmer
-0.015
961601AG1-000A GEN
Solar/Wind Harmer
9.12
316210AC1-098 GEN
Solar/Wind Harmer
3.589
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3146073TAR RVR
Solar/Wind Harmer
-0.019
3146083TARBORO
Solar/Wind Harmer
-0.019
3146263WOODLND
Solar/Wind Harmer
-0.018
316317KELFORD C
Solar/Wind Harmer
0.734
3145823KELFORD
Solar/Wind Harmer
-0.016
316131AB2-060 GEN
Solar/Wind Harmer
1.403
964241AG1-285 GEN
Solar/Wind Harmer
9.513
3145746EVERETS
Solar/Wind Harmer
-0.012
3145746EVERETS
Solar/Wind Harmer
-0.012
315785AD2-033 C
Solar/Wind Harmer
2.447
3145933PARMELE
Solar/Wind Harmer
-0.011
966801AG1-551 GEN
Solar/Wind Harmer
1.322
316463AE2-346 GEN
Solar/Wind Harmer
0.167
316140AB2-099
Solar/Wind Harmer
0.07
962331AG1-082 GEN
Solar/Wind Harmer
1.289
970257AG2-171 GEN
Solar/Wind Harmer
3.855
959311AF2-222 GEN
Solar/Wind Harmer
10.344
3146173TUNIS
Solar/Wind Harmer
-0.009
3145963POPLR C
Solar/Wind Harmer
-0.008
963181AG1-167 GEN
Solar/Wind Harmer
0.726
3144293JTRSVLE
Adder
0.219
3156021HOLLOMANSOL
Solar/Wind Harmer
1.032
957521AF2-046 GEN
Solar/Wind Harmer
5.637
961681AG1-008 GEN
Solar/Wind Harmer
5.637
3147133PAMPLIN
Solar/Wind Harmer
-0.022
971193AH1-056 GEN
Solar/Wind Harmer
4.307
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
3146206CASHIE
Solar/Wind Harmer
-0.006
315839AE2-212 C
Solar/Wind Helper
0.173
316420AA1-050 GEN
Solar/Wind Harmer
1.988
957861AF2-080 GEN
Solar/Wind Harmer
6.801
316239AB2-077_GEN
Solar/Wind Harmer
0.392
316238AB2-078_GEN
Solar/Wind Harmer
0.392
316005AA1-067
Solar/Wind Harmer
0.236
3145746EVERETS
Solar/Wind Harmer
-0.046
3145746EVERETS
Solar/Wind Harmer
-0.012
3145746EVERETS
Solar/Wind Harmer
-0.012
3145746EVERETS
Solar/Wind Harmer
-0.012
970181AG2-120 GEN
Solar/Wind Harmer
1.534
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.012
3145683EARLEYS
Solar/Wind Harmer
-0.012
971443AH1-215 GEN
Solar/Wind Harmer
2.047
3145513AHOSKIE
Solar/Wind Harmer
0.09
961941AG1-037 GEN
Solar/Wind Harmer
0.078
3145513AHOSKIE
Solar/Wind Harmer
-0.01
3144303KENBRDG
Solar/Wind Harmer
-0.008
970683AG2-441 GEN
Solar/Wind Harmer
7.015
970681AG2-440 GEN
Solar/Wind Harmer
5.612
946301AF1-294 GEN
Solar/Wind Harmer
1.985
961791AG1-021 GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
0.497
315657AE1-056 GEN
Solar/Wind Harmer
2.584
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
3146206CASHIE
Solar/Wind Harmer
-0.006
970601AG2-382 GEN
Solar/Wind Harmer
2.791
316315AB2-025 C
Solar/Wind Helper
0.728
3143316POE
Solar/Wind Helper
0.602
3145603CNETO
Solar/Wind Harmer
0.117
939181AE1-148 GEN
Solar/Wind Harmer
7.724
313527AB2-043 GEN
Solar/Wind Harmer
2.147
3145933PARMELE
Solar/Wind Harmer
-0.021
3145933PARMELE
Solar/Wind Harmer
-0.011
970323AG2-213 GEN
Solar/Wind Harmer
5.14
971775AH1-396 GEN
Solar/Wind Harmer
0.732
316034AC1-036 C
Solar/Wind Harmer
0.19
962561AG1-105 GEN
Solar/Wind Harmer
5.343
3146173TUNIS
Solar/Wind Harmer
-0.009
3146173TUNIS
Solar/Wind Harmer
-0.009
964791AG1-342 GEN
Solar/Wind Harmer
1.886
3146843MT LREL
Solar/Wind Harmer
-0.009
3146843MT LREL
Solar/Wind Harmer
-0.009
958211AF2-115 GEN
Solar/Wind Harmer
1.21
963191AG1-168 GEN
Solar/Wind Harmer
0.726
3144293JTRSVLE
Adder
0.219
3144293JTRSVLE
Adder
0.185
3147133PAMPLIN
Solar/Wind Harmer
-0.007
3147133PAMPLIN
Solar/Wind Harmer
-0.006
3145893MURPHYS
Solar/Wind Harmer
0.179
3145893MURPHYS
Solar/Wind Harmer
-0.012
3144356SAPONY
Solar/Wind Helper
0.857
316240AF1-291 C
Solar/Wind Helper
0.15
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.238
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.367
MECLTFEXP_MEC->PJM
CLTF
1.247
SIGELTFEXP_SIGE->PJM
CLTF
0.037
CPLELTFEXP_CPLE->PJM
CLTF
4.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.503
LAGNLTFEXP_LAGN->PJM
CLTF
2.563
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.458
TVALTFEXP_TVA->PJM
CLTF
1.275
NYPJM->LTFIMP_NY
CLTF
0.451
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.233

Details for 6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.42 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:776.57
MW Contribution:1.74
Bus #Bus NameTypeMW Contribution
3151281ROARAP4
50/50
0.303
3151281ROARAP4
50/50
0.283
3151151S HAMPT1
50/50
0.289
3151611KERR 4
50/50
0.204
3151621KERR 5
50/50
0.204
3151631KERR 6
50/50
0.204
3151641KERR 7
50/50
0.204
315814AE2-033 C
Solar/Wind Harmer
66.4
316087AB2-174 GEN
Solar/Wind Harmer
0.01
315652AC1-086 GEN
Solar/Wind Harmer
37.288
3145796HORNRTN
Solar/Wind Harmer
1.01
3145796HORNRTN
Solar/Wind Harmer
0.126
3137643SOCKMAN
Solar/Wind Harmer
1.149
315607AA1-063A GEN
Solar/Wind Harmer
0.435
3146043SEABORD
Solar/Wind Harmer
0.207
3146033SCOT NK
Solar/Wind Harmer
0.741
316319Z2-044 C
Solar/Wind Harmer
0
3145683EARLEYS
Solar/Wind Harmer
0.333
3145683EARLEYS
Solar/Wind Harmer
0.166
3145683EARLEYS
Solar/Wind Harmer
0.166
3145513AHOSKIE
Solar/Wind Harmer
0.345
3145513AHOSKIE
Solar/Wind Harmer
0.165
3145573BETHELC
Solar/Wind Harmer
0.163
3145573BETHELC
Solar/Wind Harmer
0.163
970831AG2-522 GEN
Solar/Wind Harmer
6.862
3145893MURPHYS
Solar/Wind Harmer
0.43
3145893MURPHYS
Solar/Wind Harmer
0.159
316420AA1-050 GEN
Solar/Wind Harmer
0.005
965291AG1-394 GEN
Solar/Wind Harmer
0.694
957861AF2-080 GEN
Solar/Wind Harmer
6.503
316005AA1-067
Solar/Wind Harmer
0.147
3145746EVERETS
Solar/Wind Harmer
0.545
3145746EVERETS
Solar/Wind Harmer
0.137
3145746EVERETS
Solar/Wind Harmer
0.137
3145746EVERETS
Solar/Wind Harmer
0.137
970181AG2-120 GEN
Solar/Wind Harmer
1.706
3146206CASHIE
Solar/Wind Harmer
0.125
970601AG2-382 GEN
Solar/Wind Harmer
4.665
315732AD1-074 GEN1
Solar/Wind Harmer
0.604
315733AD1-074 GEN2
Solar/Wind Harmer
0.604
315735AD1-075 GEN1
Solar/Wind Harmer
0.303
3130546PLYMOUTH
Solar/Wind Harmer
0.102
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
315816AE2-034 GEN
Solar/Wind Harmer
0.361
971443AH1-215 GEN
Solar/Wind Harmer
1.284
3144303KENBRDG
Solar/Wind Harmer
0.06
970683AG2-441 GEN
Solar/Wind Harmer
4.379
970681AG2-440 GEN
Solar/Wind Harmer
3.503
3130156CHOWAN
Solar/Wind Harmer
0.061
3130156CHOWAN
Solar/Wind Harmer
0.061
946301AF1-294 GEN
Solar/Wind Harmer
1.112
961791AG1-021 GEN
Solar/Wind Harmer
0.541
316315AB2-025 C
Solar/Wind Helper
0.806
3143316POE
Solar/Wind Helper
0.622
3151391GASTONA
50/50
0.917
3151411GASTONB
50/50
0.917
3151261ROARAP2
50/50
0.304
3151591KERR 2
50/50
0.204
3144293JTRSVLE
50/50
0.19
316365GEN2_N
Solar/Wind Harmer
1.156
313506AB2-031 GEN
Solar/Wind Harmer
1.029
3145796HORNRTN
Solar/Wind Harmer
1.262
3145796HORNRTN
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.313
3147043LAWRENC
Solar/Wind Harmer
0.188
315724AD1-057 GEN
Solar/Wind Harmer
0.899
316210AC1-098 GEN
Solar/Wind Harmer
1.79
3146263WOODLND
Solar/Wind Harmer
0.189
316327AA2-057 GEN
Solar/Wind Harmer
0.283
3146233WITAKRS
Solar/Wind Harmer
0.904
3146233WITAKRS
Solar/Wind Harmer
0.122
3138543CONSLDL
Solar/Wind Harmer
0.118
961601AG1-000A GEN
Solar/Wind Harmer
12.598
316317KELFORD C
Solar/Wind Harmer
0.017
3145823KELFORD
Solar/Wind Harmer
0.176
971623AH1-311 GEN
Solar/Wind Harmer
0.347
3145543BTLEBRO
Solar/Wind Harmer
0.172
3145543BTLEBRO
Solar/Wind Harmer
0.172
316463AE2-346 GEN
Solar/Wind Harmer
0.142
316140AB2-099
Solar/Wind Harmer
0.059
962331AG1-082 GEN
Solar/Wind Harmer
1.758
3146173TUNIS
Solar/Wind Harmer
0.163
3146073TAR RVR
Solar/Wind Harmer
0.163
3146083TARBORO
Solar/Wind Harmer
0.163
957521AF2-046 GEN
Solar/Wind Harmer
11.941
961681AG1-008 GEN
Solar/Wind Harmer
11.941
3145893MURPHYS
Solar/Wind Harmer
0.267
3145893MURPHYS
Solar/Wind Harmer
0.159
3156021HOLLOMANSOL
Solar/Wind Harmer
0.695
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
3145746EVERETS
Solar/Wind Harmer
0.137
3145746EVERETS
Solar/Wind Harmer
0.137
3145933PARMELE
Solar/Wind Harmer
0.131
966801AG1-551 GEN
Solar/Wind Harmer
1.53
3146206CASHIE
Solar/Wind Harmer
0.125
3145963POPLR C
Solar/Wind Harmer
0.119
315737AD1-076 GEN
Solar/Wind Harmer
1.353
971157AH1-035 GEN
Solar/Wind Harmer
1.222
316131AB2-060 GEN
Solar/Wind Harmer
0.302
964241AG1-285 GEN
Solar/Wind Harmer
5.993
315614AA2-178 GEN
Solar/Wind Harmer
0.482
315785AD2-033 C
Solar/Wind Harmer
0.646
970257AG2-171 GEN
Solar/Wind Harmer
2.417
959311AF2-222 GEN
Solar/Wind Harmer
6.465
3146376EDENTON
Solar/Wind Harmer
0.061
963181AG1-167 GEN
Solar/Wind Harmer
0.225
315839AE2-212 C
Solar/Wind Helper
0.177
3151391GASTONA
50/50
0.917
3151411GASTONB
50/50
0.917
3147043LAWRENC
50/50
3.005
3151261ROARAP2
50/50
0.311
3151601KERR 3
50/50
0.204
3151581KERR 1
50/50
0.073
3144293JTRSVLE
50/50
0.19
316023GEN1_S
Solar/Wind Harmer
1.156
960081AF2-299 GEN
Solar/Wind Harmer
3.909
971795AH1-408 GEN
Solar/Wind Harmer
22.85
316011AB1-132 GEN
Solar/Wind Harmer
6.163
962571AG1-106 GEN
Solar/Wind Harmer
4.823
3145796HORNRTN
Solar/Wind Harmer
1.041
3145796HORNRTN
Solar/Wind Harmer
0.315
3145783HORNRTN
Solar/Wind Harmer
0.242
315722AD1-056 GEN
Solar/Wind Harmer
1.516
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
0.998
3146263WOODLND
Solar/Wind Harmer
0.189
3146233WITAKRS
Solar/Wind Harmer
0.716
3145823KELFORD
Solar/Wind Harmer
0.176
316359AB2-059 GEN
Solar/Wind Harmer
0.622
316049AB1-081 GEN
Solar/Wind Harmer
0.992
3142053HEARTS
Solar/Wind Harmer
0.305
3145543BTLEBRO
Solar/Wind Harmer
0.172
3145543BTLEBRO
Solar/Wind Harmer
0.138
3145683EARLEYS
Solar/Wind Harmer
0.166
3146173TUNIS
Solar/Wind Harmer
0.163
961671AG1-007 GEN
Solar/Wind Harmer
0.025
3146083TARBORO
Solar/Wind Harmer
0.163
3145493TOT1
Solar/Wind Harmer
0.723
3145893MURPHYS
Solar/Wind Harmer
0.637
3145893MURPHYS
Solar/Wind Harmer
0.709
316129AC1-054 GEN
Solar/Wind Harmer
0.569
316494AC1-189 GEN
Solar/Wind Harmer
0.51
971065AG2-659 GEN
Solar/Wind Harmer
6.081
3145746EVERETS
Solar/Wind Harmer
0.137
3145746EVERETS
Solar/Wind Harmer
0.137
3146293MARTNCO
Solar/Wind Harmer
0.122
3146206CASHIE
Solar/Wind Harmer
0.125
971547AH1-271 GEN
Solar/Wind Harmer
2.665
316174AB2-169 GEN
Solar/Wind Harmer
0.003
3145963POPLR C
Solar/Wind Harmer
0.119
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3145663CRESWEL
Solar/Wind Harmer
0.236
971163AH1-040 GEN
Solar/Wind Harmer
6.734
970685AG2-442 GEN
Solar/Wind Harmer
4.905
970401AG2-262 GEN
Solar/Wind Harmer
0.382
3130156CHOWAN
Solar/Wind Harmer
0.061
963171AG1-166 GEN
Solar/Wind Harmer
0.3
971563AH1-280 GEN
Solar/Wind Harmer
0.601
3151361ROSEMG1
50/50
1.137
3151371ROSEMS1
50/50
0.704
3151381ROSEMG2
50/50
0.532
970535AG2-341 GEN
50/50
1.744
3144293JTRSVLE
50/50
0.19
3144293JTRSVLE
50/50
0.16
316181AB2-040 GEN
Solar/Wind Harmer
0.483
3145796HORNRTN
Solar/Wind Harmer
0.947
3142666NORTHAMPTON
Solar/Wind Harmer
0.313
3142666NORTHAMPTON
Solar/Wind Harmer
0.313
3142666NORTHAMPTON
Solar/Wind Harmer
0.313
3142666NORTHAMPTON
Solar/Wind Harmer
0.188
3145593CAROLNA
Solar/Wind Harmer
0.25
3145593CAROLNA
Solar/Wind Harmer
0.25
966811AG1-552 GEN
Solar/Wind Harmer
2.71
3145593CAROLNA
Solar/Wind Harmer
0.311
3145783HORNRTN
Solar/Wind Harmer
4.313
3145783HORNRTN
Solar/Wind Harmer
3.451
3145783HORNRTN
Solar/Wind Harmer
1.078
3145783HORNRTN
Solar/Wind Harmer
0.431
316426AA2-053 GEN
Solar/Wind Harmer
0.793
316274AC1-208 GEN
Solar/Wind Harmer
1.059
961601AG1-000A GEN
Solar/Wind Harmer
3.149
316263AC1-034 GEN
Solar/Wind Harmer
6.585
3146173TUNIS
Solar/Wind Harmer
0.163
3146173TUNIS
Solar/Wind Harmer
0.163
3145493TOT1
Solar/Wind Harmer
0.377
3145453TOT5
Solar/Wind Harmer
0.226
3145603CNETO
Solar/Wind Harmer
0.151
3145893MURPHYS
Solar/Wind Harmer
1.067
3145893MURPHYS
Solar/Wind Harmer
0.287
3145933PARMELE
Solar/Wind Harmer
0.263
3145933PARMELE
Solar/Wind Harmer
0.131
316065AD1-022 GEN
Solar/Wind Harmer
5.42
939181AE1-148 GEN
Solar/Wind Harmer
4.721
313527AB2-043 GEN
Solar/Wind Harmer
0.001
315742AE1-103 GEN
Solar/Wind Harmer
0.001
970323AG2-213 GEN
Solar/Wind Harmer
3.223
971775AH1-396 GEN
Solar/Wind Harmer
0.121
316034AC1-036 C
Solar/Wind Harmer
0.005
962561AG1-105 GEN
Solar/Wind Harmer
3.364
964791AG1-342 GEN
Solar/Wind Harmer
1.25
3146843MT LREL
Solar/Wind Harmer
0.065
3146843MT LREL
Solar/Wind Harmer
0.065
3146376EDENTON
Solar/Wind Harmer
0.271
3146376EDENTON
Solar/Wind Harmer
0.271
958211AF2-115 GEN
Solar/Wind Harmer
0.676
963191AG1-168 GEN
Solar/Wind Harmer
0.225
3144356SAPONY
Solar/Wind Helper
0.949
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.202
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.915
MECLTFEXP_MEC->PJM
CLTF
1.103
SIGELTFEXP_SIGE->PJM
CLTF
0.033
CPLELTFEXP_CPLE->PJM
CLTF
4.021
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.068
LAGNLTFEXP_LAGN->PJM
CLTF
2.305
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.741
TVALTFEXP_TVA->PJM
CLTF
1.146
NYPJM->LTFIMP_NY
CLTF
0.422
LGEELTFEXP_LGEE->PJM
CLTF
0.392
WECLTFEXP_WEC->PJM
CLTF
0.205

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:201.24 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1376.51
MW Contribution:4.63
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.835
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
315657AE1-056 GEN
Solar/Wind Harmer
20.241
946301AF1-294 GEN
Solar/Wind Harmer
13.094
961791AG1-021 GEN
Solar/Wind Harmer
6.387
970683AG2-441 GEN
Solar/Wind Harmer
36.695
970681AG2-440 GEN
Solar/Wind Harmer
29.356
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.31
971967AH1-528 GEN
Solar/Wind Harmer
73.321
316239AB2-077_GEN
Solar/Wind Harmer
0.97
316238AB2-078_GEN
Solar/Wind Harmer
0.97
316118AC1-105 GEN
Solar/Wind Harmer
1.807
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.03
970831AG2-522 GEN
Solar/Wind Harmer
9.822
316123AC1-075 GEN
Solar/Wind Harmer
1.789
970165AG2-112 GEN
Solar/Wind Harmer
1.575
970163AG2-111 GEN
Solar/Wind Harmer
1.503
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.493
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.635
270457AD2-023 GEN
Solar/Wind Harmer
0.829
315607AA1-063A GEN
Solar/Wind Harmer
0.882
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.411
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.563
270494AE1-108_GEN
Solar/Wind Helper
3.665
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.536
3151531CLOVER1
50/50
6.868
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.479
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.387
971563AH1-280 GEN
Solar/Wind Harmer
6.387
970685AG2-442 GEN
Solar/Wind Harmer
41.098
962491AG1-098 GEN
Solar/Wind Harmer
28.527
315693AD1-088 GEN
Solar/Wind Harmer
20.89
957481AF2-042 GEN
Solar/Wind Harmer
119.73
316237AB2-079_GEN
Solar/Wind Harmer
0.97
315687AD1-152 GEN
Solar/Wind Harmer
3.722
970401AG2-262 GEN
Solar/Wind Harmer
1.828
316003AC1-222 GEN
Solar/Wind Harmer
2.23
971065AG2-659 GEN
Solar/Wind Harmer
10.784
316129AC1-054 GEN
Solar/Wind Harmer
1.809
971795AH1-408 GEN
Solar/Wind Harmer
11.382
960081AF2-299 GEN
Solar/Wind Harmer
1.187
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.663
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.965
316049AB1-081 GEN
Solar/Wind Harmer
0.772
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.715
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
970223AG2-152 GEN
Solar/Wind Harmer
5.79
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.192
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.414
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.314
3144293JTRSVLE
50/50
1.536
970413AG2-270 GEN
50/50
29.97
3151591KERR 2
50/50
0.482
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.339
970909AG2-566 GEN
Solar/Wind Harmer
5.578
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.735
963181AG1-167 GEN
Solar/Wind Harmer
4.79
959311AF2-222 GEN
Solar/Wind Harmer
45.765
970257AG2-171 GEN
Solar/Wind Harmer
15.97
315785AD2-033 C
Solar/Wind Harmer
9.259
964241AG1-285 GEN
Solar/Wind Harmer
28.316
316478AD1-087 GEN
Solar/Wind Harmer
3.115
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.609
316248AF1-058 C
Solar/Wind Harmer
0.741
960061AF2-297 GEN
Solar/Wind Harmer
12.289
971683AH1-343 GEN
Solar/Wind Harmer
9.199
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.303
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.775
316210AC1-098 GEN
Solar/Wind Harmer
1.194
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.767
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.393
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.414
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.317
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
3144293JTRSVLE
50/50
1.536
3144293JTRSVLE
50/50
1.294
970535AG2-341 GEN
50/50
4.631
3152661PLYWOOD A
50/50
0.509
970301AG2-198 GEN
Solar/Wind Harmer
29.375
971741AH1-377 GEN
Solar/Wind Harmer
63.77
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.984
963191AG1-168 GEN
Solar/Wind Harmer
4.79
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.293
971775AH1-396 GEN
Solar/Wind Harmer
3.032
970933AG2-581 GEN
Solar/Wind Harmer
36.564
970099AG2-077 GEN
Solar/Wind Harmer
47.892
313527AB2-043 GEN
Solar/Wind Harmer
5.323
962561AG1-105 GEN
Solar/Wind Harmer
16.163
964791AG1-342 GEN
Solar/Wind Harmer
5.983
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.395
942751AE2-291 GEN
Solar/Wind Harmer
9.282
316222AC1-221 GEN
Solar/Wind Harmer
1.431
316181AB2-040 GEN
Solar/Wind Harmer
1.454
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.157
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.182
3145783HORNRTN
Solar/Wind Harmer
0.946
3145783HORNRTN
Solar/Wind Harmer
0.296
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.956
316274AC1-208 GEN
Solar/Wind Harmer
0.891
316263AC1-034 GEN
Solar/Wind Harmer
3.354
961601AG1-000A GEN
Solar/Wind Harmer
2.733
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.045
316197AC1-042 GEN
Solar/Wind Harmer
0.792
942671AE2-283 GEN
Solar/Wind Harmer
2.132
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.531
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.51
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.435
MECLTFEXP_MEC->PJM
CLTF
1.488
SIGELTFEXP_SIGE->PJM
CLTF
0.044
CPLELTFEXP_CPLE->PJM
CLTF
5.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.616
LAGNLTFEXP_LAGN->PJM
CLTF
3.212
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.896
TVALTFEXP_TVA->PJM
CLTF
1.599
NYPJM->LTFIMP_NY
CLTF
0.52
LGEELTFEXP_LGEE->PJM
CLTF
0.521
WECLTFEXP_WEC->PJM
CLTF
0.271

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:201.19 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1376.13
MW Contribution:4.63
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.536
3144293JTRSVLE
50/50
1.294
970535AG2-341 GEN
50/50
4.631
3152661PLYWOOD A
50/50
0.509
970301AG2-198 GEN
Solar/Wind Harmer
29.375
971741AH1-377 GEN
Solar/Wind Harmer
63.77
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.984
963191AG1-168 GEN
Solar/Wind Harmer
4.79
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.293
971775AH1-396 GEN
Solar/Wind Harmer
3.032
970933AG2-581 GEN
Solar/Wind Harmer
36.564
970099AG2-077 GEN
Solar/Wind Harmer
47.892
313527AB2-043 GEN
Solar/Wind Harmer
5.323
3144293JTRSVLE
50/50
1.536
3151531CLOVER1
50/50
6.868
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.479
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.387
971563AH1-280 GEN
Solar/Wind Harmer
6.387
970685AG2-442 GEN
Solar/Wind Harmer
41.098
962491AG1-098 GEN
Solar/Wind Harmer
28.527
315693AD1-088 GEN
Solar/Wind Harmer
20.89
957481AF2-042 GEN
Solar/Wind Harmer
119.73
316237AB2-079_GEN
Solar/Wind Harmer
0.97
315687AD1-152 GEN
Solar/Wind Harmer
3.722
970401AG2-262 GEN
Solar/Wind Harmer
1.828
316003AC1-222 GEN
Solar/Wind Harmer
2.23
971065AG2-659 GEN
Solar/Wind Harmer
10.784
316129AC1-054 GEN
Solar/Wind Harmer
1.809
971795AH1-408 GEN
Solar/Wind Harmer
11.382
960081AF2-299 GEN
Solar/Wind Harmer
1.187
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.663
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.965
316049AB1-081 GEN
Solar/Wind Harmer
0.772
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.715
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
970223AG2-152 GEN
Solar/Wind Harmer
5.79
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.192
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.414
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.314
3144293JTRSVLE
50/50
1.536
970413AG2-270 GEN
50/50
29.97
3151591KERR 2
50/50
0.482
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.339
970909AG2-566 GEN
Solar/Wind Harmer
5.578
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.735
963181AG1-167 GEN
Solar/Wind Harmer
4.79
959311AF2-222 GEN
Solar/Wind Harmer
45.765
970257AG2-171 GEN
Solar/Wind Harmer
15.97
315785AD2-033 C
Solar/Wind Harmer
9.259
964241AG1-285 GEN
Solar/Wind Harmer
28.316
316478AD1-087 GEN
Solar/Wind Harmer
3.115
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.609
316248AF1-058 C
Solar/Wind Harmer
0.741
960061AF2-297 GEN
Solar/Wind Harmer
12.289
971683AH1-343 GEN
Solar/Wind Harmer
9.199
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.303
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.775
316210AC1-098 GEN
Solar/Wind Harmer
1.194
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.767
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.393
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.414
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.317
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
962561AG1-105 GEN
Solar/Wind Harmer
16.163
964791AG1-342 GEN
Solar/Wind Harmer
5.983
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.395
942751AE2-291 GEN
Solar/Wind Harmer
9.282
316222AC1-221 GEN
Solar/Wind Harmer
1.431
316181AB2-040 GEN
Solar/Wind Harmer
1.454
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.157
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.182
3145783HORNRTN
Solar/Wind Harmer
0.946
3145783HORNRTN
Solar/Wind Harmer
0.296
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.956
316274AC1-208 GEN
Solar/Wind Harmer
0.891
316263AC1-034 GEN
Solar/Wind Harmer
3.354
961601AG1-000A GEN
Solar/Wind Harmer
2.733
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.045
316197AC1-042 GEN
Solar/Wind Harmer
0.792
942671AE2-283 GEN
Solar/Wind Harmer
2.132
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.531
3151541CLOVER2
50/50
6.835
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
315657AE1-056 GEN
Solar/Wind Harmer
20.241
946301AF1-294 GEN
Solar/Wind Harmer
13.094
961791AG1-021 GEN
Solar/Wind Harmer
6.387
970683AG2-441 GEN
Solar/Wind Harmer
36.695
970681AG2-440 GEN
Solar/Wind Harmer
29.356
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.31
971967AH1-528 GEN
Solar/Wind Harmer
73.321
316239AB2-077_GEN
Solar/Wind Harmer
0.97
316238AB2-078_GEN
Solar/Wind Harmer
0.97
316118AC1-105 GEN
Solar/Wind Harmer
1.807
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.03
970831AG2-522 GEN
Solar/Wind Harmer
9.822
316123AC1-075 GEN
Solar/Wind Harmer
1.789
970165AG2-112 GEN
Solar/Wind Harmer
1.575
970163AG2-111 GEN
Solar/Wind Harmer
1.503
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.493
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.635
270457AD2-023 GEN
Solar/Wind Harmer
0.829
315607AA1-063A GEN
Solar/Wind Harmer
0.882
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.411
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.563
270494AE1-108_GEN
Solar/Wind Helper
3.665
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.51
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.435
MECLTFEXP_MEC->PJM
CLTF
1.488
SIGELTFEXP_SIGE->PJM
CLTF
0.044
CPLELTFEXP_CPLE->PJM
CLTF
5.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.616
LAGNLTFEXP_LAGN->PJM
CLTF
3.212
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.896
TVALTFEXP_TVA->PJM
CLTF
1.599
NYPJM->LTFIMP_NY
CLTF
0.52
LGEELTFEXP_LGEE->PJM
CLTF
0.521
WECLTFEXP_WEC->PJM
CLTF
0.271

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:197.56 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1351.34
MW Contribution:4.62
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970933AG2-581 GEN
Solar/Wind Harmer
36.495
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
971967AH1-528 GEN
Solar/Wind Harmer
73.183
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:195.93 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:1095.86
MW Contribution:4.62
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.97
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
963171AG1-166 GEN
Solar/Wind Harmer
2.424
971563AH1-280 GEN
Solar/Wind Harmer
4.847
970685AG2-442 GEN
Solar/Wind Harmer
31.186
962491AG1-098 GEN
Solar/Wind Harmer
21.632
315693AD1-088 GEN
Solar/Wind Harmer
17.82
957481AF2-042 GEN
Solar/Wind Harmer
90.757
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.458
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.171
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
9.004
960081AF2-299 GEN
Solar/Wind Harmer
0.903
3145783HORNRTN
Solar/Wind Harmer
0.088
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.232
963181AG1-167 GEN
Solar/Wind Harmer
1.818
959311AF2-222 GEN
Solar/Wind Harmer
34.653
970257AG2-171 GEN
Solar/Wind Harmer
12.116
315785AD2-033 C
Solar/Wind Harmer
2.953
964241AG1-285 GEN
Solar/Wind Harmer
21.475
316478AD1-087 GEN
Solar/Wind Harmer
1.115
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.935
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.299
971683AH1-343 GEN
Solar/Wind Harmer
6.959
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.287
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.626
3146233WITAKRS
Solar/Wind Harmer
0.329
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.062
961601AG1-000A GEN
Solar/Wind Harmer
4.35
315724AD1-057 GEN
Solar/Wind Harmer
0.227
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.818
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.213
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.1
970301AG2-198 GEN
Solar/Wind Harmer
22.295
971741AH1-377 GEN
Solar/Wind Harmer
48.392
3147133PAMPLIN
Solar/Wind Harmer
0.48
3147133PAMPLIN
Solar/Wind Harmer
0.384
958211AF2-115 GEN
Solar/Wind Harmer
5.453
963191AG1-168 GEN
Solar/Wind Harmer
1.818
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.154
971775AH1-396 GEN
Solar/Wind Harmer
0.606
970933AG2-581 GEN
Solar/Wind Harmer
27.718
970099AG2-077 GEN
Solar/Wind Harmer
36.303
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.244
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.349
3146233WITAKRS
Solar/Wind Harmer
0.261
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.051
316359AB2-059 GEN
Solar/Wind Harmer
0.226
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.062
315722AD1-056 GEN
Solar/Wind Harmer
0.382
3145796HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.068
962571AG1-106 GEN
Solar/Wind Harmer
0.836
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.253
970223AG2-152 GEN
Solar/Wind Harmer
3.997
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.043
941801AE2-185 GEN
Solar/Wind Harmer
1.818
3145823KELFORD
Solar/Wind Harmer
0.056
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.104
315657AE1-056 GEN
Solar/Wind Harmer
16.558
946301AF1-294 GEN
Solar/Wind Harmer
8.968
961791AG1-021 GEN
Solar/Wind Harmer
4.363
970683AG2-441 GEN
Solar/Wind Harmer
27.844
970681AG2-440 GEN
Solar/Wind Harmer
22.275
3144303KENBRDG
Solar/Wind Harmer
0.303
971443AH1-215 GEN
Solar/Wind Harmer
6.304
971967AH1-528 GEN
Solar/Wind Harmer
55.434
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.602
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.073
970831AG2-522 GEN
Solar/Wind Harmer
7.443
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.191
970163AG2-111 GEN
Solar/Wind Harmer
1.136
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.368
315607AA1-063A GEN
Solar/Wind Harmer
0.159
3146043SEABORD
Solar/Wind Harmer
0.076
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.25
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.462
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.252
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
964791AG1-342 GEN
Solar/Wind Harmer
4.773
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.665
942751AE2-291 GEN
Solar/Wind Harmer
7.016
316222AC1-221 GEN
Solar/Wind Harmer
0.517
316181AB2-040 GEN
Solar/Wind Harmer
0.135
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.992
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.575
3145783HORNRTN
Solar/Wind Harmer
1.26
3145783HORNRTN
Solar/Wind Harmer
0.394
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.38
316263AC1-034 GEN
Solar/Wind Harmer
2.393
961601AG1-000A GEN
Solar/Wind Harmer
1.088
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.132
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.414
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:193.37 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:1081.51
MW Contribution:4.62
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.97
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
963171AG1-166 GEN
Solar/Wind Harmer
2.424
971563AH1-280 GEN
Solar/Wind Harmer
4.847
970685AG2-442 GEN
Solar/Wind Harmer
31.186
962491AG1-098 GEN
Solar/Wind Harmer
21.632
315693AD1-088 GEN
Solar/Wind Harmer
17.82
957481AF2-042 GEN
Solar/Wind Harmer
90.757
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.458
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.171
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
9.004
960081AF2-299 GEN
Solar/Wind Harmer
0.903
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.349
3146233WITAKRS
Solar/Wind Harmer
0.261
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.051
316359AB2-059 GEN
Solar/Wind Harmer
0.226
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.062
315722AD1-056 GEN
Solar/Wind Harmer
0.382
3145796HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.068
962571AG1-106 GEN
Solar/Wind Harmer
0.836
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.253
970223AG2-152 GEN
Solar/Wind Harmer
3.997
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.043
941801AE2-185 GEN
Solar/Wind Harmer
1.818
3145823KELFORD
Solar/Wind Harmer
0.056
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.104
315657AE1-056 GEN
Solar/Wind Harmer
16.558
946301AF1-294 GEN
Solar/Wind Harmer
8.968
961791AG1-021 GEN
Solar/Wind Harmer
4.363
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.213
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.1
970301AG2-198 GEN
Solar/Wind Harmer
22.295
971741AH1-377 GEN
Solar/Wind Harmer
48.392
3147133PAMPLIN
Solar/Wind Harmer
0.48
3147133PAMPLIN
Solar/Wind Harmer
0.384
958211AF2-115 GEN
Solar/Wind Harmer
5.453
963191AG1-168 GEN
Solar/Wind Harmer
1.818
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.154
971775AH1-396 GEN
Solar/Wind Harmer
0.606
970099AG2-077 GEN
Solar/Wind Harmer
36.303
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.244
964791AG1-342 GEN
Solar/Wind Harmer
4.773
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.665
942751AE2-291 GEN
Solar/Wind Harmer
7.016
316222AC1-221 GEN
Solar/Wind Harmer
0.517
316181AB2-040 GEN
Solar/Wind Harmer
0.135
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.992
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.575
3145783HORNRTN
Solar/Wind Harmer
1.26
3145783HORNRTN
Solar/Wind Harmer
0.394
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.38
316263AC1-034 GEN
Solar/Wind Harmer
2.393
961601AG1-000A GEN
Solar/Wind Harmer
1.088
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.132
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.414
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.232
963181AG1-167 GEN
Solar/Wind Harmer
1.818
959311AF2-222 GEN
Solar/Wind Harmer
34.653
970257AG2-171 GEN
Solar/Wind Harmer
12.116
315785AD2-033 C
Solar/Wind Harmer
2.953
964241AG1-285 GEN
Solar/Wind Harmer
21.475
316478AD1-087 GEN
Solar/Wind Harmer
1.115
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.935
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.299
971683AH1-343 GEN
Solar/Wind Harmer
6.959
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.287
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.626
3146233WITAKRS
Solar/Wind Harmer
0.329
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.062
961601AG1-000A GEN
Solar/Wind Harmer
4.35
315724AD1-057 GEN
Solar/Wind Harmer
0.227
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.818
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
970683AG2-441 GEN
Solar/Wind Harmer
27.844
970681AG2-440 GEN
Solar/Wind Harmer
22.275
3144303KENBRDG
Solar/Wind Harmer
0.303
971443AH1-215 GEN
Solar/Wind Harmer
6.304
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.602
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.073
970831AG2-522 GEN
Solar/Wind Harmer
7.443
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.191
970163AG2-111 GEN
Solar/Wind Harmer
1.136
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.368
315607AA1-063A GEN
Solar/Wind Harmer
0.159
3146043SEABORD
Solar/Wind Harmer
0.076
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.25
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.462
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.252
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:191.54 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1310.12
MW Contribution:4.62
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:191.54 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1310.12
MW Contribution:4.62
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2106-2111_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2106-2111_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:119.01 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:814.05
MW Contribution:2.84
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.18
3151601KERR 3
50/50
0.277
3151581KERR 1
50/50
0.099
3151531CLOVER1
50/50
2.843
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.907
971563AH1-280 GEN
Solar/Wind Harmer
4.907
970685AG2-442 GEN
Solar/Wind Harmer
30.788
962491AG1-098 GEN
Solar/Wind Harmer
14.151
316237AB2-079_GEN
Solar/Wind Harmer
0.621
315693AD1-088 GEN
Solar/Wind Harmer
9.998
970401AG2-262 GEN
Solar/Wind Harmer
1.046
957481AF2-042 GEN
Solar/Wind Harmer
45.244
315687AD1-152 GEN
Solar/Wind Harmer
1.611
971065AG2-659 GEN
Solar/Wind Harmer
6.471
316129AC1-054 GEN
Solar/Wind Harmer
1.098
3147043LAWRENC
Adder
0.994
316003AC1-222 GEN
Solar/Wind Harmer
1.108
971795AH1-408 GEN
Solar/Wind Harmer
8.341
960081AF2-299 GEN
Solar/Wind Harmer
0.953
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.091
316212AC1-099_GEN
Solar/Wind Harmer
0.553
316322AB2-045
Solar/Wind Helper
0.97
3146776BUCKING
Solar/Wind Helper
0.348
316336AC2-165 C
Solar/Wind Helper
1.454
3151611KERR 4
50/50
0.277
3151621KERR 5
50/50
0.277
3151631KERR 6
50/50
0.277
3151641KERR 7
50/50
0.277
3151541CLOVER2
50/50
2.829
315657AE1-056 GEN
Solar/Wind Harmer
15.784
946301AF1-294 GEN
Solar/Wind Harmer
10.059
961791AG1-021 GEN
Solar/Wind Harmer
4.907
970683AG2-441 GEN
Solar/Wind Harmer
27.489
970681AG2-440 GEN
Solar/Wind Harmer
21.992
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.004
316239AB2-077_GEN
Solar/Wind Harmer
0.621
316238AB2-078_GEN
Solar/Wind Harmer
0.621
316118AC1-105 GEN
Solar/Wind Harmer
0.972
3147173SINAI
Solar/Wind Harmer
-0.012
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.033
970865AG2-541 GEN
Solar/Wind Harmer
3.923
946281AF1-292 GEN
Solar/Wind Harmer
0.19
316087AB2-174 GEN
Solar/Wind Harmer
1.178
3137643SOCKMAN
Solar/Wind Harmer
-0.032
316123AC1-075 GEN
Solar/Wind Harmer
0.853
970165AG2-112 GEN
Solar/Wind Harmer
0.751
970163AG2-111 GEN
Solar/Wind Harmer
0.717
971967AH1-528 GEN
Solar/Wind Harmer
14.188
315607AA1-063A GEN
Solar/Wind Harmer
0.715
3146043SEABORD
Solar/Wind Harmer
-0.007
270494AE1-108_GEN
Solar/Wind Helper
4.499
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3144293JTRSVLE
50/50
1.18
3144293JTRSVLE
50/50
0.994
970535AG2-341 GEN
50/50
2.836
3152661PLYWOOD A
50/50
0.267
970301AG2-198 GEN
Solar/Wind Harmer
21.257
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.133
963191AG1-168 GEN
Solar/Wind Harmer
3.68
971741AH1-377 GEN
Solar/Wind Harmer
43.417
316034AC1-036 C
Solar/Wind Harmer
0.574
970323AG2-213 GEN
Solar/Wind Harmer
15.434
971775AH1-396 GEN
Solar/Wind Harmer
2.198
313527AB2-043 GEN
Solar/Wind Harmer
3.442
962561AG1-105 GEN
Solar/Wind Harmer
9.457
939181AE1-148 GEN
Solar/Wind Harmer
9.083
964791AG1-342 GEN
Solar/Wind Harmer
3.423
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.098
970933AG2-581 GEN
Solar/Wind Harmer
9.079
316181AB2-040 GEN
Solar/Wind Harmer
1.138
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.878
3145593CAROLNA
Solar/Wind Harmer
0.065
3145783HORNRTN
Solar/Wind Harmer
0.905
3145783HORNRTN
Solar/Wind Harmer
0.724
3145783HORNRTN
Solar/Wind Harmer
0.226
3145783HORNRTN
Solar/Wind Harmer
0.09
316222AC1-221 GEN
Solar/Wind Harmer
0.769
316426AA2-053 GEN
Solar/Wind Harmer
0.748
942751AE2-291 GEN
Solar/Wind Harmer
4.333
316274AC1-208 GEN
Solar/Wind Harmer
0.717
972187AH1-678 GEN
Adder
1.63
3146776BUCKING
Solar/Wind Helper
3.482
3146776BUCKING
Solar/Wind Helper
0.282
315821AE2-092 GEN
Solar/Wind Helper
2.994
3144293JTRSVLE
50/50
1.18
3151591KERR 2
50/50
0.277
970413AG2-270 GEN
50/50
12.405
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.535
970909AG2-566 GEN
Solar/Wind Harmer
4.036
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.307
963181AG1-167 GEN
Solar/Wind Harmer
3.68
959311AF2-222 GEN
Solar/Wind Harmer
33.514
970257AG2-171 GEN
Solar/Wind Harmer
11.575
315785AD2-033 C
Solar/Wind Harmer
6.609
964241AG1-285 GEN
Solar/Wind Harmer
19.233
316131AB2-060 GEN
Solar/Wind Harmer
2.359
316478AD1-087 GEN
Solar/Wind Harmer
1.29
316486AD2-202 GEN
Solar/Wind Harmer
0.378
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.371
960061AF2-297 GEN
Solar/Wind Harmer
6.151
971683AH1-343 GEN
Solar/Wind Harmer
4.535
966621AG1-532 GEN
Solar/Wind Harmer
0.172
313506AB2-031 GEN
Solar/Wind Harmer
0.656
316283AC2-100 C
Solar/Wind Harmer
0.705
316210AC1-098 GEN
Solar/Wind Harmer
0.995
3146776BUCKING
Solar/Wind Helper
0.313
316313AB2-026
Solar/Wind Helper
0.341
316258AE1-075 C
Solar/Wind Helper
0.306
316405AF2-144 C
Solar/Wind Helper
0.255
3148013FISHERV
Solar/Wind Helper
0.125
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.19
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.966
MECLTFEXP_MEC->PJM
CLTF
0.645
SIGELTFEXP_SIGE->PJM
CLTF
0.018
CPLELTFEXP_CPLE->PJM
CLTF
3.717
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.651
LAGNLTFEXP_LAGN->PJM
CLTF
1.842
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.457
TVALTFEXP_TVA->PJM
CLTF
0.904
NYPJM->LTFIMP_NY
CLTF
0.34
LGEELTFEXP_LGEE->PJM
CLTF
0.186
WECLTFEXP_WEC->PJM
CLTF
0.097

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:118.81 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:812.65
MW Contribution:2.93
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.195
3151601KERR 3
50/50
0.289
3151581KERR 1
50/50
0.103
3151531CLOVER1
50/50
2.955
3147043LAWRENC
50/50
1.106
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.97
971563AH1-280 GEN
Solar/Wind Harmer
4.97
970685AG2-442 GEN
Solar/Wind Harmer
31.247
962491AG1-098 GEN
Solar/Wind Harmer
14.52
316237AB2-079_GEN
Solar/Wind Harmer
0.639
315693AD1-088 GEN
Solar/Wind Harmer
10.276
970401AG2-262 GEN
Solar/Wind Harmer
1.085
957481AF2-042 GEN
Solar/Wind Harmer
47.025
315687AD1-152 GEN
Solar/Wind Harmer
1.689
971065AG2-659 GEN
Solar/Wind Harmer
6.793
316129AC1-054 GEN
Solar/Wind Harmer
1.154
316003AC1-222 GEN
Solar/Wind Harmer
1.163
971795AH1-408 GEN
Solar/Wind Harmer
8.792
960081AF2-299 GEN
Solar/Wind Harmer
1.021
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.099
316212AC1-099_GEN
Solar/Wind Harmer
0.614
970919AG2-571 GEN
Solar/Wind Harmer
2.193
970087AG2-069 GEN
Solar/Wind Harmer
6.491
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.406
962571AG1-106 GEN
Solar/Wind Harmer
0.966
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3151611KERR 4
50/50
0.289
3151621KERR 5
50/50
0.289
3151631KERR 6
50/50
0.289
3151641KERR 7
50/50
0.289
3151541CLOVER2
50/50
2.941
315657AE1-056 GEN
Solar/Wind Harmer
15.969
946301AF1-294 GEN
Solar/Wind Harmer
10.188
961791AG1-021 GEN
Solar/Wind Harmer
4.97
970683AG2-441 GEN
Solar/Wind Harmer
27.899
970681AG2-440 GEN
Solar/Wind Harmer
22.32
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.111
316239AB2-077_GEN
Solar/Wind Harmer
0.639
316238AB2-078_GEN
Solar/Wind Harmer
0.639
316118AC1-105 GEN
Solar/Wind Harmer
1.014
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.355
970865AG2-541 GEN
Solar/Wind Harmer
4.115
946281AF1-292 GEN
Solar/Wind Harmer
0.203
316087AB2-174 GEN
Solar/Wind Harmer
1.265
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.894
970165AG2-112 GEN
Solar/Wind Harmer
0.787
970163AG2-111 GEN
Solar/Wind Harmer
0.751
971967AH1-528 GEN
Solar/Wind Harmer
15.203
315607AA1-063A GEN
Solar/Wind Harmer
0.778
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.327
970581AG2-369 GEN
Solar/Wind Harmer
3.722
316319Z2-044 C
Solar/Wind Harmer
0.378
3146033SCOT NK
Solar/Wind Harmer
-0.027
315652AC1-086 GEN
Solar/Wind Harmer
7.562
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
3144293JTRSVLE
50/50
1.195
3144293JTRSVLE
50/50
1.007
970535AG2-341 GEN
50/50
2.934
3152661PLYWOOD A
50/50
0.28
970301AG2-198 GEN
Solar/Wind Harmer
21.495
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.212
963191AG1-168 GEN
Solar/Wind Harmer
3.727
971741AH1-377 GEN
Solar/Wind Harmer
43.991
316034AC1-036 C
Solar/Wind Harmer
0.584
970323AG2-213 GEN
Solar/Wind Harmer
15.706
971775AH1-396 GEN
Solar/Wind Harmer
2.237
313527AB2-043 GEN
Solar/Wind Harmer
3.538
962561AG1-105 GEN
Solar/Wind Harmer
9.795
939181AE1-148 GEN
Solar/Wind Harmer
9.44
964791AG1-342 GEN
Solar/Wind Harmer
3.552
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
970099AG2-077 GEN
Solar/Wind Harmer
18.81
970933AG2-581 GEN
Solar/Wind Harmer
9.592
316181AB2-040 GEN
Solar/Wind Harmer
1.225
316222AC1-221 GEN
Solar/Wind Harmer
0.857
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.951
3145593CAROLNA
Solar/Wind Harmer
0.07
3145783HORNRTN
Solar/Wind Harmer
0.982
3145783HORNRTN
Solar/Wind Harmer
0.786
3145783HORNRTN
Solar/Wind Harmer
0.245
3145783HORNRTN
Solar/Wind Harmer
0.098
316426AA2-053 GEN
Solar/Wind Harmer
0.813
316274AC1-208 GEN
Solar/Wind Harmer
0.793
942751AE2-291 GEN
Solar/Wind Harmer
4.536
972187AH1-678 GEN
Adder
1.773
972185AH1-677 GEN
Adder
3.35
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
316263AC1-034 GEN
Solar/Wind Harmer
3.126
961601AG1-000A GEN
Solar/Wind Harmer
2.583
3145893MURPHYS
Solar/Wind Harmer
0.18
3145893MURPHYS
Solar/Wind Harmer
-0.012
3145493TOT1
Solar/Wind Harmer
0.098
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
3146776BUCKING
Solar/Wind Helper
3.457
3146776BUCKING
Solar/Wind Helper
0.28
315821AE2-092 GEN
Solar/Wind Helper
2.963
965291AG1-394 GEN
Solar/Wind Harmer
0.582
970673AG2-436 GEN
Solar/Wind Harmer
13.618
970673AG2-436 GEN
Solar/Wind Harmer
6.895
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
270494AE1-108_GEN
Solar/Wind Helper
4.464
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.195
3151591KERR 2
50/50
0.289
970413AG2-270 GEN
50/50
12.897
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.604
970909AG2-566 GEN
Solar/Wind Harmer
4.081
3147133PAMPLIN
Solar/Wind Harmer
-0.133
971193AH1-056 GEN
Solar/Wind Harmer
26.615
963181AG1-167 GEN
Solar/Wind Harmer
3.727
959311AF2-222 GEN
Solar/Wind Harmer
34.076
970257AG2-171 GEN
Solar/Wind Harmer
11.779
315785AD2-033 C
Solar/Wind Harmer
6.734
964241AG1-285 GEN
Solar/Wind Harmer
19.68
316131AB2-060 GEN
Solar/Wind Harmer
2.422
316478AD1-087 GEN
Solar/Wind Harmer
1.342
316486AD2-202 GEN
Solar/Wind Harmer
0.393
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.389
960061AF2-297 GEN
Solar/Wind Harmer
6.458
971683AH1-343 GEN
Solar/Wind Harmer
4.759
966621AG1-532 GEN
Solar/Wind Harmer
0.184
313506AB2-031 GEN
Solar/Wind Harmer
0.706
316283AC2-100 C
Solar/Wind Harmer
0.787
316210AC1-098 GEN
Solar/Wind Harmer
1.105
316327AA2-057 GEN
Solar/Wind Harmer
0.707
970917AG2-570 GEN
Solar/Wind Harmer
17.327
3146233WITAKRS
Solar/Wind Harmer
0.143
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.004
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.382
316365GEN2_N
Solar/Wind Harmer
0.443
961601AG1-000A GEN
Solar/Wind Harmer
2.615
316317KELFORD C
Solar/Wind Harmer
0.306
3145823KELFORD
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.09
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
957521AF2-046 GEN
Solar/Wind Harmer
5.039
961681AG1-008 GEN
Solar/Wind Harmer
5.039
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.311
316313AB2-026
Solar/Wind Helper
0.332
316258AE1-075 C
Solar/Wind Helper
0.299
316405AF2-144 C
Solar/Wind Helper
0.249
3148013FISHERV
Solar/Wind Helper
0.123
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316359AB2-059 GEN
Solar/Wind Harmer
0.899
316049AB1-081 GEN
Solar/Wind Harmer
0.72
3142053HEARTS
Solar/Wind Harmer
0.078
315722AD1-056 GEN
Solar/Wind Harmer
0.694
316023GEN1_S
Solar/Wind Harmer
0.443
3145823KELFORD
Solar/Wind Harmer
-0.006
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.191
961671AG1-007 GEN
Solar/Wind Harmer
0.08
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
316322AB2-045
Solar/Wind Helper
0.963
3146776BUCKING
Solar/Wind Helper
0.346
316336AC2-165 C
Solar/Wind Helper
1.425
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.102
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.96
MECLTFEXP_MEC->PJM
CLTF
0.838
SIGELTFEXP_SIGE->PJM
CLTF
0.022
CPLELTFEXP_CPLE->PJM
CLTF
4.543
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.552
LAGNLTFEXP_LAGN->PJM
CLTF
2.505
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.252
TVALTFEXP_TVA->PJM
CLTF
1.216
NYPJM->LTFIMP_NY
CLTF
0.295
LGEELTFEXP_LGEE->PJM
CLTF
0.219
WECLTFEXP_WEC->PJM
CLTF
0.123

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2003-205_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2003-205_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:115.25 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:788.33
MW Contribution:2.9
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.19
3144293JTRSVLE
50/50
1.19
3144293JTRSVLE
50/50
1.002
970535AG2-341 GEN
50/50
2.898
3152661PLYWOOD A
50/50
0.275
970301AG2-198 GEN
Solar/Wind Harmer
21.406
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.183
963191AG1-168 GEN
Solar/Wind Harmer
3.71
971741AH1-377 GEN
Solar/Wind Harmer
43.786
316034AC1-036 C
Solar/Wind Harmer
0.58
970323AG2-213 GEN
Solar/Wind Harmer
15.608
971775AH1-396 GEN
Solar/Wind Harmer
2.223
313527AB2-043 GEN
Solar/Wind Harmer
3.505
962561AG1-105 GEN
Solar/Wind Harmer
9.664
939181AE1-148 GEN
Solar/Wind Harmer
9.308
964791AG1-342 GEN
Solar/Wind Harmer
3.501
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.602
970933AG2-581 GEN
Solar/Wind Harmer
9.49
316181AB2-040 GEN
Solar/Wind Harmer
1.218
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.934
3145593CAROLNA
Solar/Wind Harmer
0.069
3145783HORNRTN
Solar/Wind Harmer
0.963
3145783HORNRTN
Solar/Wind Harmer
0.77
3145783HORNRTN
Solar/Wind Harmer
0.241
3145783HORNRTN
Solar/Wind Harmer
0.096
316222AC1-221 GEN
Solar/Wind Harmer
0.802
316426AA2-053 GEN
Solar/Wind Harmer
0.797
316274AC1-208 GEN
Solar/Wind Harmer
0.766
942751AE2-291 GEN
Solar/Wind Harmer
4.503
972187AH1-678 GEN
Adder
1.745
972185AH1-677 GEN
Adder
3.302
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3146776BUCKING
Solar/Wind Helper
3.47
3146776BUCKING
Solar/Wind Helper
0.281
315821AE2-092 GEN
Solar/Wind Helper
2.982
3144293JTRSVLE
50/50
1.19
3151601KERR 3
50/50
0.284
3151581KERR 1
50/50
0.102
3151531CLOVER1
50/50
2.917
3147043LAWRENC
50/50
1.102
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.946
971563AH1-280 GEN
Solar/Wind Harmer
4.946
970685AG2-442 GEN
Solar/Wind Harmer
31.078
962491AG1-098 GEN
Solar/Wind Harmer
14.404
316237AB2-079_GEN
Solar/Wind Harmer
0.632
315693AD1-088 GEN
Solar/Wind Harmer
10.19
970401AG2-262 GEN
Solar/Wind Harmer
1.07
957481AF2-042 GEN
Solar/Wind Harmer
46.506
315687AD1-152 GEN
Solar/Wind Harmer
1.657
971065AG2-659 GEN
Solar/Wind Harmer
6.686
316129AC1-054 GEN
Solar/Wind Harmer
1.136
971795AH1-408 GEN
Solar/Wind Harmer
8.781
316003AC1-222 GEN
Solar/Wind Harmer
1.14
960081AF2-299 GEN
Solar/Wind Harmer
1.025
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.097
316212AC1-099_GEN
Solar/Wind Harmer
0.591
970919AG2-571 GEN
Solar/Wind Harmer
2.137
970087AG2-069 GEN
Solar/Wind Harmer
6.318
316023GEN1_S
Solar/Wind Harmer
0.452
316011AB1-132 GEN
Solar/Wind Harmer
1.389
962571AG1-106 GEN
Solar/Wind Harmer
0.954
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
-0.026
315722AD1-056 GEN
Solar/Wind Harmer
0.667
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316322AB2-045
Solar/Wind Helper
0.967
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.456
3151591KERR 2
50/50
0.284
970413AG2-270 GEN
50/50
12.729
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.576
970909AG2-566 GEN
Solar/Wind Harmer
4.064
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.496
963181AG1-167 GEN
Solar/Wind Harmer
3.71
959311AF2-222 GEN
Solar/Wind Harmer
33.872
970257AG2-171 GEN
Solar/Wind Harmer
11.706
315785AD2-033 C
Solar/Wind Harmer
6.689
964241AG1-285 GEN
Solar/Wind Harmer
19.525
316131AB2-060 GEN
Solar/Wind Harmer
2.4
316478AD1-087 GEN
Solar/Wind Harmer
1.324
316486AD2-202 GEN
Solar/Wind Harmer
0.388
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.381
960061AF2-297 GEN
Solar/Wind Harmer
6.325
971683AH1-343 GEN
Solar/Wind Harmer
4.674
966621AG1-532 GEN
Solar/Wind Harmer
0.185
313506AB2-031 GEN
Solar/Wind Harmer
0.702
316283AC2-100 C
Solar/Wind Harmer
0.736
316210AC1-098 GEN
Solar/Wind Harmer
1.064
970917AG2-570 GEN
Solar/Wind Harmer
16.885
316365GEN2_N
Solar/Wind Harmer
0.452
316327AA2-057 GEN
Solar/Wind Harmer
0.676
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.136
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
315724AD1-057 GEN
Solar/Wind Harmer
0.367
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.312
316313AB2-026
Solar/Wind Helper
0.342
316258AE1-075 C
Solar/Wind Helper
0.307
316405AF2-144 C
Solar/Wind Helper
0.256
3148013FISHERV
Solar/Wind Helper
0.124
3151611KERR 4
50/50
0.284
3151621KERR 5
50/50
0.284
3151631KERR 6
50/50
0.284
3151641KERR 7
50/50
0.284
3151541CLOVER2
50/50
2.903
315657AE1-056 GEN
Solar/Wind Harmer
15.898
946301AF1-294 GEN
Solar/Wind Harmer
10.139
961791AG1-021 GEN
Solar/Wind Harmer
4.946
970683AG2-441 GEN
Solar/Wind Harmer
27.748
970681AG2-440 GEN
Solar/Wind Harmer
22.198
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.073
316239AB2-077_GEN
Solar/Wind Harmer
0.632
316238AB2-078_GEN
Solar/Wind Harmer
0.632
316118AC1-105 GEN
Solar/Wind Harmer
0.997
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.254
970865AG2-541 GEN
Solar/Wind Harmer
4.048
946281AF1-292 GEN
Solar/Wind Harmer
0.204
316087AB2-174 GEN
Solar/Wind Harmer
1.262
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.884
970165AG2-112 GEN
Solar/Wind Harmer
0.778
970163AG2-111 GEN
Solar/Wind Harmer
0.742
971967AH1-528 GEN
Solar/Wind Harmer
15.039
315607AA1-063A GEN
Solar/Wind Harmer
0.762
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.212
970581AG2-369 GEN
Solar/Wind Harmer
3.623
315652AC1-086 GEN
Solar/Wind Harmer
7.469
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.026
316319Z2-044 C
Solar/Wind Harmer
0.36
970673AG2-436 GEN
Solar/Wind Harmer
13.449
970673AG2-436 GEN
Solar/Wind Harmer
6.81
965291AG1-394 GEN
Solar/Wind Harmer
0.565
270494AE1-108_GEN
Solar/Wind Helper
4.476
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.511
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.403
MECLTFEXP_MEC->PJM
CLTF
0.809
SIGELTFEXP_SIGE->PJM
CLTF
0.023
CPLELTFEXP_CPLE->PJM
CLTF
3.951
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.116
LAGNLTFEXP_LAGN->PJM
CLTF
2.085
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.001
TVALTFEXP_TVA->PJM
CLTF
1.025
NYPJM->LTFIMP_NY
CLTF
0.315
LGEELTFEXP_LGEE->PJM
CLTF
0.251
WECLTFEXP_WEC->PJM
CLTF
0.133

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P2-2: ALTAVISTA 115KV_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: ALTAVISTA 115KV_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:113.26 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:774.73
MW Contribution:2.98
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.203
3151601KERR 3
50/50
0.292
3151581KERR 1
50/50
0.104
3151531CLOVER1
50/50
2.981
3147043LAWRENC
50/50
1.112
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
5.001
971563AH1-280 GEN
Solar/Wind Harmer
5.001
970685AG2-442 GEN
Solar/Wind Harmer
31.502
962491AG1-098 GEN
Solar/Wind Harmer
14.564
316237AB2-079_GEN
Solar/Wind Harmer
0.652
315693AD1-088 GEN
Solar/Wind Harmer
10.309
970401AG2-262 GEN
Solar/Wind Harmer
1.156
957481AF2-042 GEN
Solar/Wind Harmer
47.203
3147123OTTER R
Solar/Wind Harmer
-0.009
316003AC1-222 GEN
Solar/Wind Harmer
1.413
315687AD1-152 GEN
Solar/Wind Harmer
1.721
971065AG2-659 GEN
Solar/Wind Harmer
6.825
316129AC1-054 GEN
Solar/Wind Harmer
1.158
971795AH1-408 GEN
Solar/Wind Harmer
8.808
960081AF2-299 GEN
Solar/Wind Harmer
1.012
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.097
316212AC1-099_GEN
Solar/Wind Harmer
0.59
970919AG2-571 GEN
Solar/Wind Harmer
2.123
970087AG2-069 GEN
Solar/Wind Harmer
6.277
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.357
962571AG1-106 GEN
Solar/Wind Harmer
0.932
3146233WITAKRS
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.006
316023GEN1_S
Solar/Wind Harmer
0.431
316322AB2-045
Solar/Wind Helper
0.963
3146776BUCKING
Solar/Wind Helper
0.345
316336AC2-165 C
Solar/Wind Helper
1.43
3151611KERR 4
50/50
0.292
3151621KERR 5
50/50
0.292
3151631KERR 6
50/50
0.292
3151641KERR 7
50/50
0.292
3151541CLOVER2
50/50
2.967
315657AE1-056 GEN
Solar/Wind Harmer
16.053
946301AF1-294 GEN
Solar/Wind Harmer
10.253
961791AG1-021 GEN
Solar/Wind Harmer
5.001
970683AG2-441 GEN
Solar/Wind Harmer
28.127
970681AG2-440 GEN
Solar/Wind Harmer
22.501
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.178
316239AB2-077_GEN
Solar/Wind Harmer
0.652
316238AB2-078_GEN
Solar/Wind Harmer
0.652
316118AC1-105 GEN
Solar/Wind Harmer
1.105
316123AC1-075 GEN
Solar/Wind Harmer
1.561
970165AG2-112 GEN
Solar/Wind Harmer
1.375
970163AG2-111 GEN
Solar/Wind Harmer
1.311
970865AG2-541 GEN
Solar/Wind Harmer
5.879
3147173SINAI
Solar/Wind Harmer
-0.014
3147243WELCO
Solar/Wind Harmer
-0.009
970831AG2-522 GEN
Solar/Wind Harmer
6.369
946281AF1-292 GEN
Solar/Wind Harmer
0.201
316087AB2-174 GEN
Solar/Wind Harmer
1.25
3137643SOCKMAN
Solar/Wind Harmer
-0.034
971967AH1-528 GEN
Solar/Wind Harmer
14.997
315607AA1-063A GEN
Solar/Wind Harmer
0.762
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.185
970581AG2-369 GEN
Solar/Wind Harmer
3.599
3146033SCOT NK
Solar/Wind Harmer
-0.026
315652AC1-086 GEN
Solar/Wind Harmer
7.298
316319Z2-044 C
Solar/Wind Harmer
0.358
3145796HORNRTN
Solar/Wind Harmer
-0.02
3145796HORNRTN
Solar/Wind Harmer
-0.003
965291AG1-394 GEN
Solar/Wind Harmer
0.567
3144293JTRSVLE
50/50
1.203
3151591KERR 2
50/50
0.292
970413AG2-270 GEN
50/50
13.01
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.625
970909AG2-566 GEN
Solar/Wind Harmer
4.087
3147133PAMPLIN
Solar/Wind Harmer
-0.134
971193AH1-056 GEN
Solar/Wind Harmer
26.755
963181AG1-167 GEN
Solar/Wind Harmer
3.751
959311AF2-222 GEN
Solar/Wind Harmer
34.411
970257AG2-171 GEN
Solar/Wind Harmer
11.905
315785AD2-033 C
Solar/Wind Harmer
6.813
964241AG1-285 GEN
Solar/Wind Harmer
19.989
316131AB2-060 GEN
Solar/Wind Harmer
2.467
316478AD1-087 GEN
Solar/Wind Harmer
1.354
316486AD2-202 GEN
Solar/Wind Harmer
0.396
971683AH1-343 GEN
Solar/Wind Harmer
6.24
316248AF1-058 C
Solar/Wind Harmer
0.436
960061AF2-297 GEN
Solar/Wind Harmer
7.234
3147043LAWRENC
Solar/Wind Harmer
-0.008
966621AG1-532 GEN
Solar/Wind Harmer
0.182
3144293JTRSVLE
50/50
1.203
3144293JTRSVLE
50/50
1.013
970535AG2-341 GEN
50/50
2.978
3152661PLYWOOD A
50/50
0.306
970301AG2-198 GEN
Solar/Wind Harmer
21.525
3147133PAMPLIN
Solar/Wind Harmer
-0.043
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.252
963191AG1-168 GEN
Solar/Wind Harmer
3.751
971741AH1-377 GEN
Solar/Wind Harmer
44.063
316034AC1-036 C
Solar/Wind Harmer
0.59
970323AG2-213 GEN
Solar/Wind Harmer
15.873
971775AH1-396 GEN
Solar/Wind Harmer
2.26
313527AB2-043 GEN
Solar/Wind Harmer
3.607
962561AG1-105 GEN
Solar/Wind Harmer
10.348
964791AG1-342 GEN
Solar/Wind Harmer
3.783
3146843MT LREL
Solar/Wind Harmer
-0.018
3146843MT LREL
Solar/Wind Harmer
-0.018
939181AE1-148 GEN
Solar/Wind Harmer
9.553
970099AG2-077 GEN
Solar/Wind Harmer
18.881
942751AE2-291 GEN
Solar/Wind Harmer
9.226
970933AG2-581 GEN
Solar/Wind Harmer
9.531
316181AB2-040 GEN
Solar/Wind Harmer
1.209
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.934
3145593CAROLNA
Solar/Wind Harmer
0.069
316222AC1-221 GEN
Solar/Wind Harmer
0.828
3145783HORNRTN
Solar/Wind Harmer
0.962
3145783HORNRTN
Solar/Wind Harmer
0.77
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
316426AA2-053 GEN
Solar/Wind Harmer
0.796
316274AC1-208 GEN
Solar/Wind Harmer
0.764
972187AH1-678 GEN
Adder
1.732
972185AH1-677 GEN
Adder
3.271
3145796HORNRTN
Solar/Wind Harmer
-0.019
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3146776BUCKING
Solar/Wind Helper
3.456
3146776BUCKING
Solar/Wind Helper
0.28
315821AE2-092 GEN
Solar/Wind Helper
2.97
970673AG2-436 GEN
Solar/Wind Harmer
13.3
970673AG2-436 GEN
Solar/Wind Harmer
6.734
270494AE1-108_GEN
Solar/Wind Helper
4.519
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
313506AB2-031 GEN
Solar/Wind Harmer
0.697
316283AC2-100 C
Solar/Wind Harmer
0.759
316210AC1-098 GEN
Solar/Wind Harmer
1.062
970917AG2-570 GEN
Solar/Wind Harmer
16.773
316327AA2-057 GEN
Solar/Wind Harmer
0.674
3146263WOODLND
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.136
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
316365GEN2_N
Solar/Wind Harmer
0.431
3146776BUCKING
Solar/Wind Helper
0.311
316313AB2-026
Solar/Wind Helper
0.334
316258AE1-075 C
Solar/Wind Helper
0.3
316405AF2-144 C
Solar/Wind Helper
0.25
3148013FISHERV
Solar/Wind Helper
0.123
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.579
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.131
MECLTFEXP_MEC->PJM
CLTF
0.695
SIGELTFEXP_SIGE->PJM
CLTF
0.019
CPLELTFEXP_CPLE->PJM
CLTF
3.953
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.193
LAGNLTFEXP_LAGN->PJM
CLTF
1.949
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.898
TVALTFEXP_TVA->PJM
CLTF
0.953
NYPJM->LTFIMP_NY
CLTF
0.29
LGEELTFEXP_LGEE->PJM
CLTF
0.201
WECLTFEXP_WEC->PJM
CLTF
0.107

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.32 %
Rating:559.3 MVA
Rating Type:A
MVA to Mitigate:566.67
MW Contribution:2.85
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.183
3151601KERR 3
50/50
0.279
3151581KERR 1
50/50
0.1
3151531CLOVER1
50/50
2.861
3147043LAWRENC
50/50
1.063
3151261ROARAP2
50/50
0.088
3151051BRUNSWICKS1
50/50
1.588
3151021BRUNSWICKG1
50/50
0.765
971451AH1-221 GEN
50/50
2.324
3146926FARMVIL
Solar/Wind Harmer
0.316
963171AG1-166 GEN
Solar/Wind Harmer
1.868
971563AH1-280 GEN
Solar/Wind Harmer
3.736
970685AG2-442 GEN
Solar/Wind Harmer
23.448
962491AG1-098 GEN
Solar/Wind Harmer
10.797
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
8.584
970401AG2-262 GEN
Solar/Wind Harmer
0.842
957481AF2-042 GEN
Solar/Wind Harmer
34.592
315687AD1-152 GEN
Solar/Wind Harmer
0.004
971065AG2-659 GEN
Solar/Wind Harmer
4.952
316129AC1-054 GEN
Solar/Wind Harmer
0.422
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971795AH1-408 GEN
Solar/Wind Harmer
6.656
960081AF2-299 GEN
Solar/Wind Harmer
0.732
3145783HORNRTN
Solar/Wind Harmer
0.069
3144293JTRSVLE
50/50
1.183
3144293JTRSVLE
50/50
0.996
970535AG2-341 GEN
50/50
2.851
3152661PLYWOOD A
50/50
0.269
3151041BRUNSWICKG3
50/50
0.765
972187AH1-678 GEN
50/50
1.756
970301AG2-198 GEN
Solar/Wind Harmer
16.182
3147133PAMPLIN
Solar/Wind Harmer
0.375
3147133PAMPLIN
Solar/Wind Harmer
0.3
958211AF2-115 GEN
Solar/Wind Harmer
4.203
963191AG1-168 GEN
Solar/Wind Harmer
1.401
971741AH1-377 GEN
Solar/Wind Harmer
33.06
316034AC1-036 C
Solar/Wind Harmer
0.02
970323AG2-213 GEN
Solar/Wind Harmer
11.759
971775AH1-396 GEN
Solar/Wind Harmer
0.441
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
7.224
939181AE1-148 GEN
Solar/Wind Harmer
6.94
964791AG1-342 GEN
Solar/Wind Harmer
2.755
3146843MT LREL
Solar/Wind Harmer
0.143
3146843MT LREL
Solar/Wind Harmer
0.143
970099AG2-077 GEN
Solar/Wind Harmer
13.837
970933AG2-581 GEN
Solar/Wind Harmer
6.964
316181AB2-040 GEN
Solar/Wind Harmer
0.107
3145593CAROLNA
Solar/Wind Harmer
0.07
3145593CAROLNA
Solar/Wind Harmer
0.07
966811AG1-552 GEN
Solar/Wind Harmer
0.763
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.221
3145783HORNRTN
Solar/Wind Harmer
0.977
3145783HORNRTN
Solar/Wind Harmer
0.305
3145783HORNRTN
Solar/Wind Harmer
0.122
316222AC1-221 GEN
Solar/Wind Harmer
0.284
316426AA2-053 GEN
Solar/Wind Harmer
0.225
942751AE2-291 GEN
Solar/Wind Harmer
3.338
316274AC1-208 GEN
Solar/Wind Harmer
0.311
3146776BUCKING
Solar/Wind Helper
3.475
3146776BUCKING
Solar/Wind Helper
0.282
315821AE2-092 GEN
Solar/Wind Helper
2.978
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
0.296
970919AG2-571 GEN
Solar/Wind Harmer
2.029
970087AG2-069 GEN
Solar/Wind Harmer
4.556
316322AB2-045
Solar/Wind Helper
0.968
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.445
3151611KERR 4
50/50
0.279
3151621KERR 5
50/50
0.279
3151631KERR 6
50/50
0.279
3151641KERR 7
50/50
0.279
3151541CLOVER2
50/50
2.847
3151281ROARAP4
50/50
0.085
3151281ROARAP4
50/50
0.08
963041AG1-153 GEN
50/50
1.549
315657AE1-056 GEN
Solar/Wind Harmer
12.95
946301AF1-294 GEN
Solar/Wind Harmer
6.911
961791AG1-021 GEN
Solar/Wind Harmer
3.362
970683AG2-441 GEN
Solar/Wind Harmer
20.935
970681AG2-440 GEN
Solar/Wind Harmer
16.748
3144303KENBRDG
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
4.574
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.327
3147173SINAI
Solar/Wind Harmer
0.11
3147243WELCO
Solar/Wind Harmer
0.069
970831AG2-522 GEN
Solar/Wind Harmer
4.619
970865AG2-541 GEN
Solar/Wind Harmer
3.009
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.287
316123AC1-075 GEN
Solar/Wind Harmer
0.097
970165AG2-112 GEN
Solar/Wind Harmer
0.577
970163AG2-111 GEN
Solar/Wind Harmer
0.551
971967AH1-528 GEN
Solar/Wind Harmer
10.885
315607AA1-063A GEN
Solar/Wind Harmer
0.13
3146043SEABORD
Solar/Wind Harmer
0.063
970085AG2-068 GEN
Solar/Wind Harmer
3.037
970581AG2-369 GEN
Solar/Wind Harmer
2.612
270494AE1-108_GEN
Solar/Wind Helper
4.476
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.183
3151591KERR 2
50/50
0.279
970413AG2-270 GEN
50/50
12.485
3151261ROARAP2
50/50
0.086
3151031BRUNSWICKG2
50/50
0.765
3146926FARMVIL
Solar/Wind Harmer
0.316
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.045
3147133PAMPLIN
Solar/Wind Harmer
1.178
971193AH1-056 GEN
Solar/Wind Harmer
22.863
963181AG1-167 GEN
Solar/Wind Harmer
1.401
959311AF2-222 GEN
Solar/Wind Harmer
25.479
970257AG2-171 GEN
Solar/Wind Harmer
8.819
315785AD2-033 C
Solar/Wind Harmer
2.117
964241AG1-285 GEN
Solar/Wind Harmer
14.665
316131AB2-060 GEN
Solar/Wind Harmer
0.615
316478AD1-087 GEN
Solar/Wind Harmer
0.466
316486AD2-202 GEN
Solar/Wind Harmer
0.137
3147043LAWRENC
Solar/Wind Harmer
0.066
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.708
971683AH1-343 GEN
Solar/Wind Harmer
3.476
313506AB2-031 GEN
Solar/Wind Harmer
0.227
316283AC2-100 C
Solar/Wind Harmer
0.132
316210AC1-098 GEN
Solar/Wind Harmer
0.531
970917AG2-570 GEN
Solar/Wind Harmer
5.072
316327AA2-057 GEN
Solar/Wind Harmer
0.085
3146776BUCKING
Solar/Wind Helper
0.313
316313AB2-026
Solar/Wind Helper
0.338
316258AE1-075 C
Solar/Wind Helper
0.304
316405AF2-144 C
Solar/Wind Helper
0.253
3148013FISHERV
Solar/Wind Helper
0.123
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.153
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.217
MECLTFEXP_MEC->PJM
CLTF
0.756
SIGELTFEXP_SIGE->PJM
CLTF
0.021
CPLELTFEXP_CPLE->PJM
CLTF
3.789
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.54
LAGNLTFEXP_LAGN->PJM
CLTF
1.976
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.656
TVALTFEXP_TVA->PJM
CLTF
0.971
NYPJM->LTFIMP_NY
CLTF
0.298
LGEELTFEXP_LGEE->PJM
CLTF
0.232
WECLTFEXP_WEC->PJM
CLTF
0.123

Details for 6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-5: 556X2_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-5: 556X2_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.23 %
Rating:1050.6 MVA
Rating Type:C
MVA to Mitigate:1462.74
MW Contribution:4.48
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
8.333
3144293JTRSVLE
50/50
0.954
3151601KERR 3
50/50
0.512
3151581KERR 1
50/50
0.183
3151931BEARGRDN S1
50/50
1.383
3151911BEARGRDN G1
50/50
1.071
315693AD1-088 GEN
Solar/Wind Harmer
31.661
962491AG1-098 GEN
Solar/Wind Harmer
41.781
957481AF2-042 GEN
Solar/Wind Harmer
136.799
315687AD1-152 GEN
Solar/Wind Harmer
4.384
3146926FARMVIL
Solar/Wind Harmer
-0.021
963171AG1-166 GEN
Solar/Wind Harmer
3.966
971563AH1-280 GEN
Solar/Wind Harmer
3.966
970685AG2-442 GEN
Solar/Wind Harmer
27.199
316237AB2-079_GEN
Solar/Wind Harmer
0.866
970401AG2-262 GEN
Solar/Wind Harmer
1.795
316322AB2-045
Solar/Wind Harmer
0.84
3146776BUCKING
Solar/Wind Harmer
-0.01
316003AC1-222 GEN
Solar/Wind Harmer
2.424
971065AG2-659 GEN
Solar/Wind Harmer
10.717
316129AC1-054 GEN
Solar/Wind Harmer
1.767
972003AH1-546 GEN
Solar/Wind Harmer
7.559
3147043LAWRENC
Adder
0.99
971377AH1-170 GEN
Solar/Wind Harmer
1.453
3147623JAMES R
Solar/Wind Harmer
0.18
3147123OTTER R
Solar/Wind Harmer
-0.006
971795AH1-408 GEN
Solar/Wind Harmer
7.507
970937AG2-583 GEN
Solar/Wind Harmer
6.673
3147312GRETNA
Solar/Wind Harmer
-0.007
3146802CHATHAM
Solar/Wind Harmer
-0.007
941801AE2-185 GEN
Solar/Wind Harmer
3.291
316294AC1-161 GEN
Solar/Wind Helper
2.492
316375AC2-012 GEN
Solar/Wind Helper
0.324
316388AE2-253 GEN
Solar/Wind Helper
0.45
3145336SMITFLD
Solar/Wind Helper
0.467
3146456SLIGO L269
Solar/Wind Helper
0.116
316246AF1-032 C
Solar/Wind Helper
0.129
316072AD1-144
Solar/Wind Helper
0.129
3144293JTRSVLE
50/50
0.954
3144293JTRSVLE
50/50
0.803
970535AG2-341 GEN
50/50
4.477
3152661PLYWOOD A
50/50
0.537
971741AH1-377 GEN
Solar/Wind Harmer
58.955
970301AG2-198 GEN
Solar/Wind Harmer
23.48
970099AG2-077 GEN
Solar/Wind Harmer
54.72
3147133PAMPLIN
Solar/Wind Harmer
-0.032
3147133PAMPLIN
Solar/Wind Harmer
-0.026
958211AF2-115 GEN
Solar/Wind Harmer
4.957
963191AG1-168 GEN
Solar/Wind Harmer
2.974
316034AC1-036 C
Solar/Wind Harmer
0.564
970323AG2-213 GEN
Solar/Wind Harmer
15.2
971775AH1-396 GEN
Solar/Wind Harmer
2.165
313527AB2-043 GEN
Solar/Wind Harmer
4.69
939181AE1-148 GEN
Solar/Wind Harmer
15.738
962561AG1-105 GEN
Solar/Wind Harmer
15.589
964791AG1-342 GEN
Solar/Wind Harmer
5.876
3146843MT LREL
Solar/Wind Harmer
-0.027
3146843MT LREL
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.099
3146776BUCKING
Solar/Wind Harmer
-0.008
942751AE2-291 GEN
Solar/Wind Harmer
10.674
316222AC1-221 GEN
Solar/Wind Harmer
1.342
971489AH1-241 GEN
Solar/Wind Harmer
6.897
316217AC1-145 GEN
Solar/Wind Harmer
1.425
316197AC1-042 GEN
Solar/Wind Harmer
1.08
942671AE2-283 GEN
Solar/Wind Harmer
2.907
315821AE2-092 GEN
Solar/Wind Harmer
1.728
316036AC1-147 C
Solar/Wind Helper
0.189
3142956BIRDNECK
Solar/Wind Helper
0.083
316316AC1-027 C
Solar/Wind Helper
0.194
316185AD1-033 GEN
Solar/Wind Helper
0.577
3145506HICKORY
Solar/Wind Helper
0.484
3145506HICKORY
Solar/Wind Helper
0.291
3145506HICKORY
Solar/Wind Helper
0.073
316339AD2-160 GEN
Solar/Wind Helper
0.45
316018AA1-139 ULT2
Solar/Wind Helper
0.505
316017AA1-139 ULT1
Solar/Wind Helper
0.536
316236AE1-162_GEN
Solar/Wind Helper
0.157
3137176SLIGO L2192
Solar/Wind Helper
0.462
3130086AYDLETT
Solar/Wind Helper
0.459
970413AG2-270 GEN
50/50
36.366
3144293JTRSVLE
50/50
0.954
3151591KERR 2
50/50
0.512
3151921BEARGRDN G2
50/50
1.071
970909AG2-566 GEN
Solar/Wind Harmer
4.458
316478AD1-087 GEN
Solar/Wind Harmer
3.778
316486AD2-202 GEN
Solar/Wind Harmer
1.106
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
5.027
3147133PAMPLIN
Solar/Wind Harmer
-0.101
971193AH1-056 GEN
Solar/Wind Harmer
20.111
963181AG1-167 GEN
Solar/Wind Harmer
2.974
959311AF2-222 GEN
Solar/Wind Harmer
31.935
970257AG2-171 GEN
Solar/Wind Harmer
11.4
315785AD2-033 C
Solar/Wind Harmer
6.828
964241AG1-285 GEN
Solar/Wind Harmer
22.977
316131AB2-060 GEN
Solar/Wind Harmer
3.126
316248AF1-058 C
Solar/Wind Harmer
0.799
960061AF2-297 GEN
Solar/Wind Harmer
13.263
3146776BUCKING
Solar/Wind Harmer
-0.009
971683AH1-343 GEN
Solar/Wind Harmer
10.071
316283AC2-100 C
Solar/Wind Harmer
1.212
3147043LAWRENC
Solar/Wind Harmer
-0.007
970221AG2-151 GEN
Solar/Wind Harmer
7.265
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
3.291
958131AF2-107 GEN
Solar/Wind Harmer
2.165
315773AC2-141 GEN
Solar/Wind Helper
2.933
3144873MCLAUGH
Solar/Wind Helper
0.003
3144536CHRHLND
Solar/Wind Helper
0.018
3145336SMITFLD
Solar/Wind Helper
0.047
3146456SLIGO L269
Solar/Wind Helper
0.116
3151541CLOVER2
50/50
8.294
3151611KERR 4
50/50
0.512
3151621KERR 5
50/50
0.512
3151631KERR 6
50/50
0.512
3151641KERR 7
50/50
0.512
972205AH1-687 GEN
50/50
5.225
315657AE1-056 GEN
Solar/Wind Harmer
12.067
946301AF1-294 GEN
Solar/Wind Harmer
8.13
961791AG1-021 GEN
Solar/Wind Harmer
3.966
970683AG2-441 GEN
Solar/Wind Harmer
24.284
970681AG2-440 GEN
Solar/Wind Harmer
19.428
3144303KENBRDG
Solar/Wind Harmer
-0.024
971443AH1-215 GEN
Solar/Wind Harmer
5.973
316239AB2-077_GEN
Solar/Wind Harmer
0.866
316238AB2-078_GEN
Solar/Wind Harmer
0.866
970285AG2-188 GEN
Solar/Wind Harmer
23.989
316118AC1-105 GEN
Solar/Wind Harmer
1.858
3147173SINAI
Solar/Wind Harmer
-0.026
3147243WELCO
Solar/Wind Harmer
-0.016
971845AH1-439 GEN
Solar/Wind Harmer
13.717
970865AG2-541 GEN
Solar/Wind Harmer
8.867
970831AG2-522 GEN
Solar/Wind Harmer
9.395
316123AC1-075 GEN
Solar/Wind Harmer
2.019
970165AG2-112 GEN
Solar/Wind Harmer
1.778
970163AG2-111 GEN
Solar/Wind Harmer
1.696
971447AH1-217 GEN
Solar/Wind Harmer
3.892
270494AE1-108_GEN
Solar/Wind Harmer
2.597
270455AD2-022 GEN
Solar/Wind Harmer
1.324
270457AD2-023 GEN
Solar/Wind Harmer
0.671
3143316POE
Solar/Wind Helper
0.479
319010AE1-072 C
Solar/Wind Helper
1.317
316305AF2-043 C
Solar/Wind Helper
0.151
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.001
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.345
MECLTFEXP_MEC->PJM
CLTF
1.48
SIGELTFEXP_SIGE->PJM
CLTF
0.047
CPLELTFEXP_CPLE->PJM
CLTF
2.622
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.961
LAGNLTFEXP_LAGN->PJM
CLTF
2.391
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.949
TVALTFEXP_TVA->PJM
CLTF
1.221
NYPJM->LTFIMP_NY
CLTF
0.45
LGEELTFEXP_LGEE->PJM
CLTF
0.594
WECLTFEXP_WEC->PJM
CLTF
0.305

Details for 6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: 556X1_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-8FINNEYWOOD 230.0/500.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-5: 556X1_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.76 %
Rating:1053.0 MVA
Rating Type:C
MVA to Mitigate:1461.12
MW Contribution:4.47
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.953
3144293JTRSVLE
50/50
0.802
970535AG2-341 GEN
50/50
4.472
3152661PLYWOOD A
50/50
0.536
971741AH1-377 GEN
Solar/Wind Harmer
58.889
970301AG2-198 GEN
Solar/Wind Harmer
23.454
970099AG2-077 GEN
Solar/Wind Harmer
54.659
3147133PAMPLIN
Solar/Wind Harmer
-0.032
3147133PAMPLIN
Solar/Wind Harmer
-0.026
958211AF2-115 GEN
Solar/Wind Harmer
4.952
963191AG1-168 GEN
Solar/Wind Harmer
2.971
316034AC1-036 C
Solar/Wind Harmer
0.563
970323AG2-213 GEN
Solar/Wind Harmer
15.183
971775AH1-396 GEN
Solar/Wind Harmer
2.162
313527AB2-043 GEN
Solar/Wind Harmer
4.685
939181AE1-148 GEN
Solar/Wind Harmer
15.721
962561AG1-105 GEN
Solar/Wind Harmer
15.572
964791AG1-342 GEN
Solar/Wind Harmer
5.869
3146843MT LREL
Solar/Wind Harmer
-0.027
3146843MT LREL
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.099
3151531CLOVER1
50/50
8.324
3144293JTRSVLE
50/50
0.953
3151601KERR 3
50/50
0.511
3151581KERR 1
50/50
0.182
3151931BEARGRDN S1
50/50
1.381
3151911BEARGRDN G1
50/50
1.07
315693AD1-088 GEN
Solar/Wind Harmer
31.626
962491AG1-098 GEN
Solar/Wind Harmer
41.735
957481AF2-042 GEN
Solar/Wind Harmer
136.647
315687AD1-152 GEN
Solar/Wind Harmer
4.379
3146926FARMVIL
Solar/Wind Harmer
-0.021
963171AG1-166 GEN
Solar/Wind Harmer
3.962
971563AH1-280 GEN
Solar/Wind Harmer
3.962
970685AG2-442 GEN
Solar/Wind Harmer
27.168
316237AB2-079_GEN
Solar/Wind Harmer
0.865
970401AG2-262 GEN
Solar/Wind Harmer
1.793
316322AB2-045
Solar/Wind Harmer
0.839
3146776BUCKING
Solar/Wind Harmer
-0.01
316003AC1-222 GEN
Solar/Wind Harmer
2.421
971065AG2-659 GEN
Solar/Wind Harmer
10.705
316129AC1-054 GEN
Solar/Wind Harmer
1.765
972003AH1-546 GEN
Solar/Wind Harmer
7.55
3147043LAWRENC
Adder
0.989
971377AH1-170 GEN
Solar/Wind Harmer
1.451
3147623JAMES R
Solar/Wind Harmer
0.18
3147123OTTER R
Solar/Wind Harmer
-0.006
971795AH1-408 GEN
Solar/Wind Harmer
7.499
970937AG2-583 GEN
Solar/Wind Harmer
6.666
3147312GRETNA
Solar/Wind Harmer
-0.007
3146802CHATHAM
Solar/Wind Harmer
-0.007
941801AE2-185 GEN
Solar/Wind Harmer
3.288
316294AC1-161 GEN
Solar/Wind Helper
2.489
316375AC2-012 GEN
Solar/Wind Helper
0.324
316388AE2-253 GEN
Solar/Wind Helper
0.45
3145336SMITFLD
Solar/Wind Helper
0.467
3146456SLIGO L269
Solar/Wind Helper
0.116
316246AF1-032 C
Solar/Wind Helper
0.128
316072AD1-144
Solar/Wind Helper
0.128
3151541CLOVER2
50/50
8.284
3151611KERR 4
50/50
0.511
3151621KERR 5
50/50
0.511
3151631KERR 6
50/50
0.511
3151641KERR 7
50/50
0.511
972205AH1-687 GEN
50/50
5.219
315657AE1-056 GEN
Solar/Wind Harmer
12.053
946301AF1-294 GEN
Solar/Wind Harmer
8.121
961791AG1-021 GEN
Solar/Wind Harmer
3.962
970683AG2-441 GEN
Solar/Wind Harmer
24.258
970681AG2-440 GEN
Solar/Wind Harmer
19.406
3144303KENBRDG
Solar/Wind Harmer
-0.024
971443AH1-215 GEN
Solar/Wind Harmer
5.967
316239AB2-077_GEN
Solar/Wind Harmer
0.865
316238AB2-078_GEN
Solar/Wind Harmer
0.865
970285AG2-188 GEN
Solar/Wind Harmer
23.962
316118AC1-105 GEN
Solar/Wind Harmer
1.856
3147173SINAI
Solar/Wind Harmer
-0.026
3147243WELCO
Solar/Wind Harmer
-0.016
971845AH1-439 GEN
Solar/Wind Harmer
13.702
970865AG2-541 GEN
Solar/Wind Harmer
8.857
970831AG2-522 GEN
Solar/Wind Harmer
9.385
316123AC1-075 GEN
Solar/Wind Harmer
2.017
970165AG2-112 GEN
Solar/Wind Harmer
1.776
970163AG2-111 GEN
Solar/Wind Harmer
1.694
971447AH1-217 GEN
Solar/Wind Harmer
3.888
270494AE1-108_GEN
Solar/Wind Harmer
2.594
270455AD2-022 GEN
Solar/Wind Harmer
1.322
270457AD2-023 GEN
Solar/Wind Harmer
0.671
3143316POE
Solar/Wind Helper
0.479
319010AE1-072 C
Solar/Wind Helper
1.315
316305AF2-043 C
Solar/Wind Helper
0.151
3146776BUCKING
Solar/Wind Harmer
-0.008
942751AE2-291 GEN
Solar/Wind Harmer
10.662
316222AC1-221 GEN
Solar/Wind Harmer
1.341
971489AH1-241 GEN
Solar/Wind Harmer
6.89
316217AC1-145 GEN
Solar/Wind Harmer
1.423
316197AC1-042 GEN
Solar/Wind Harmer
1.079
942671AE2-283 GEN
Solar/Wind Harmer
2.904
315821AE2-092 GEN
Solar/Wind Harmer
1.726
316036AC1-147 C
Solar/Wind Helper
0.188
3142956BIRDNECK
Solar/Wind Helper
0.083
316316AC1-027 C
Solar/Wind Helper
0.194
316185AD1-033 GEN
Solar/Wind Helper
0.577
3145506HICKORY
Solar/Wind Helper
0.484
3145506HICKORY
Solar/Wind Helper
0.29
3145506HICKORY
Solar/Wind Helper
0.073
316339AD2-160 GEN
Solar/Wind Helper
0.45
316018AA1-139 ULT2
Solar/Wind Helper
0.504
316017AA1-139 ULT1
Solar/Wind Helper
0.536
316236AE1-162_GEN
Solar/Wind Helper
0.157
3137176SLIGO L2192
Solar/Wind Helper
0.461
3130086AYDLETT
Solar/Wind Helper
0.459
970413AG2-270 GEN
50/50
36.326
3144293JTRSVLE
50/50
0.953
3151591KERR 2
50/50
0.511
3151921BEARGRDN G2
50/50
1.07
970909AG2-566 GEN
Solar/Wind Harmer
4.453
316478AD1-087 GEN
Solar/Wind Harmer
3.774
316486AD2-202 GEN
Solar/Wind Harmer
1.105
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
5.021
3147133PAMPLIN
Solar/Wind Harmer
-0.1
971193AH1-056 GEN
Solar/Wind Harmer
20.089
963181AG1-167 GEN
Solar/Wind Harmer
2.971
959311AF2-222 GEN
Solar/Wind Harmer
31.9
970257AG2-171 GEN
Solar/Wind Harmer
11.387
315785AD2-033 C
Solar/Wind Harmer
6.821
964241AG1-285 GEN
Solar/Wind Harmer
22.951
316131AB2-060 GEN
Solar/Wind Harmer
3.123
316248AF1-058 C
Solar/Wind Harmer
0.798
960061AF2-297 GEN
Solar/Wind Harmer
13.248
3146776BUCKING
Solar/Wind Harmer
-0.009
971683AH1-343 GEN
Solar/Wind Harmer
10.06
316283AC2-100 C
Solar/Wind Harmer
1.21
3147043LAWRENC
Solar/Wind Harmer
-0.007
970221AG2-151 GEN
Solar/Wind Harmer
7.257
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
3.288
958131AF2-107 GEN
Solar/Wind Harmer
2.163
315773AC2-141 GEN
Solar/Wind Helper
2.93
3144873MCLAUGH
Solar/Wind Helper
0.003
3144536CHRHLND
Solar/Wind Helper
0.018
3145336SMITFLD
Solar/Wind Helper
0.047
3146456SLIGO L269
Solar/Wind Helper
0.116
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.989
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.34
MECLTFEXP_MEC->PJM
CLTF
1.478
SIGELTFEXP_SIGE->PJM
CLTF
0.046
CPLELTFEXP_CPLE->PJM
CLTF
2.619
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.946
LAGNLTFEXP_LAGN->PJM
CLTF
2.389
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.942
TVALTFEXP_TVA->PJM
CLTF
1.22
NYPJM->LTFIMP_NY
CLTF
0.449
LGEELTFEXP_LGEE->PJM
CLTF
0.593
WECLTFEXP_WEC->PJM
CLTF
0.305

Details for 6FINNEYWOOD-AG1-098 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-AG1-098 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.83 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:650.55
MW Contribution:1.99
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
971629AH1-314 GEN
50/50
5.006
315693AD1-088 GEN
Solar/Wind Harmer
18.25
957481AF2-042 GEN
Solar/Wind Harmer
90.747
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.071
316129AC1-054 GEN
Solar/Wind Harmer
0.427
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
316478AD1-087 GEN
Solar/Wind Harmer
1.094
316486AD2-202 GEN
Solar/Wind Harmer
0.321
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.01
971683AH1-343 GEN
Solar/Wind Harmer
5.256
316283AC2-100 C
Solar/Wind Harmer
0.206
316131AB2-060 GEN
Solar/Wind Harmer
0.208
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
3152661PLYWOOD A
50/50
0.346
970535AG2-341 GEN
50/50
1.993
970933AG2-581 GEN
Solar/Wind Harmer
27.859
970099AG2-077 GEN
Solar/Wind Harmer
36.299
939181AE1-148 GEN
Solar/Wind Harmer
6.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.689
316222AC1-221 GEN
Solar/Wind Harmer
0.447
942751AE2-291 GEN
Solar/Wind Harmer
5.336
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
971967AH1-528 GEN
Solar/Wind Harmer
55.717
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
316118AC1-105 GEN
Solar/Wind Harmer
0.376
970865AG2-541 GEN
Solar/Wind Harmer
4.593
316123AC1-075 GEN
Solar/Wind Harmer
0.152
970165AG2-112 GEN
Solar/Wind Harmer
0.903
970163AG2-111 GEN
Solar/Wind Harmer
0.862
970831AG2-522 GEN
Solar/Wind Harmer
4.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for 6FINNEYWOOD-AG1-098 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-AG1-098 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.27 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:635.93
MW Contribution:1.99
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
971629AH1-314 GEN
50/50
5.006
315693AD1-088 GEN
Solar/Wind Harmer
18.25
957481AF2-042 GEN
Solar/Wind Harmer
90.747
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.071
316129AC1-054 GEN
Solar/Wind Harmer
0.427
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
3152661PLYWOOD A
50/50
0.346
970535AG2-341 GEN
50/50
1.993
970099AG2-077 GEN
Solar/Wind Harmer
36.299
939181AE1-148 GEN
Solar/Wind Harmer
6.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.689
316222AC1-221 GEN
Solar/Wind Harmer
0.447
942751AE2-291 GEN
Solar/Wind Harmer
5.336
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
316118AC1-105 GEN
Solar/Wind Harmer
0.376
970865AG2-541 GEN
Solar/Wind Harmer
4.593
316123AC1-075 GEN
Solar/Wind Harmer
0.152
970165AG2-112 GEN
Solar/Wind Harmer
0.903
970163AG2-111 GEN
Solar/Wind Harmer
0.862
970831AG2-522 GEN
Solar/Wind Harmer
4.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
316478AD1-087 GEN
Solar/Wind Harmer
1.094
316486AD2-202 GEN
Solar/Wind Harmer
0.321
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.01
971683AH1-343 GEN
Solar/Wind Harmer
5.256
316283AC2-100 C
Solar/Wind Harmer
0.206
316131AB2-060 GEN
Solar/Wind Harmer
0.208
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for 6FINNEYWOOD-AG1-098 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FINNEYWOOD-AG1-098 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.84 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:767.78
MW Contribution:2.0
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
6.74
3151601KERR 3
50/50
0.302
3151581KERR 1
50/50
0.108
315693AD1-088 GEN
Solar/Wind Harmer
21.388
957481AF2-042 GEN
Solar/Wind Harmer
119.681
315687AD1-152 GEN
Solar/Wind Harmer
3.524
316003AC1-222 GEN
Solar/Wind Harmer
1.683
970401AG2-262 GEN
Solar/Wind Harmer
0.932
971065AG2-659 GEN
Solar/Wind Harmer
6.697
316129AC1-054 GEN
Solar/Wind Harmer
1.121
316237AB2-079_GEN
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Helper
0.44
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
1.003
3152661PLYWOOD A
50/50
0.348
970535AG2-341 GEN
50/50
2.001
970933AG2-581 GEN
Solar/Wind Harmer
36.739
970099AG2-077 GEN
Solar/Wind Harmer
47.872
939181AE1-148 GEN
Solar/Wind Harmer
8.421
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.05
962561AG1-105 GEN
Solar/Wind Harmer
7.525
316222AC1-221 GEN
Solar/Wind Harmer
1.236
942751AE2-291 GEN
Solar/Wind Harmer
7.063
313527AB2-043 GEN
Solar/Wind Harmer
1.361
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.338
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.919
970413AG2-270 GEN
50/50
29.414
3151591KERR 2
50/50
0.302
316478AD1-087 GEN
Solar/Wind Harmer
3.055
316486AD2-202 GEN
Solar/Wind Harmer
0.895
316248AF1-058 C
Solar/Wind Harmer
0.559
960061AF2-297 GEN
Solar/Wind Harmer
9.268
971683AH1-343 GEN
Solar/Wind Harmer
6.951
316283AC2-100 C
Solar/Wind Harmer
1.124
316131AB2-060 GEN
Solar/Wind Harmer
0.808
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.542
3147133PAMPLIN
Solar/Wind Helper
1.062
316313AB2-026
Solar/Wind Helper
0.243
316258AE1-075 C
Solar/Wind Helper
0.219
316405AF2-144 C
Solar/Wind Helper
0.182
3151541CLOVER2
50/50
6.708
3151611KERR 4
50/50
0.302
3151621KERR 5
50/50
0.302
3151631KERR 6
50/50
0.302
3151641KERR 7
50/50
0.302
971967AH1-528 GEN
Solar/Wind Harmer
73.672
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.131
970865AG2-541 GEN
Solar/Wind Harmer
6.075
316123AC1-075 GEN
Solar/Wind Harmer
1.358
970165AG2-112 GEN
Solar/Wind Harmer
1.195
970163AG2-111 GEN
Solar/Wind Harmer
1.14
970831AG2-522 GEN
Solar/Wind Harmer
6.069
316239AB2-077_GEN
Solar/Wind Harmer
0.274
316238AB2-078_GEN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Harmer
1.371
270457AD2-023 GEN
Solar/Wind Harmer
0.695
270494AE1-108_GEN
Solar/Wind Helper
2.769
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.6
MECLTFEXP_MEC->PJM
CLTF
1.297
SIGELTFEXP_SIGE->PJM
CLTF
0.038
CPLELTFEXP_CPLE->PJM
CLTF
4.232
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.165
LAGNLTFEXP_LAGN->PJM
CLTF
2.703
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.92
TVALTFEXP_TVA->PJM
CLTF
1.347
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.461
WECLTFEXP_WEC->PJM
CLTF
0.241

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:196.14 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1331.14
MW Contribution:2.11
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.67
316303AF2-085
50/50
2.055
3144293JTRSVLE
50/50
0.706
3144293JTRSVLE
50/50
0.594
970535AG2-341 GEN
50/50
2.11
3152661PLYWOOD A
50/50
0.217
3151041BRUNSWICKG3
50/50
1.059
972187AH1-678 GEN
50/50
2.43
315242AE2-183_GT2
50/50
1.321
315241AE2-183_GT1
50/50
1.313
972185AH1-677 GEN
50/50
4.762
970533AG2-339 GEN
50/50
7.019
970531AG2-338 GEN
50/50
2.808
971489AH1-241 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
1.465
3146776BUCKING
Solar/Wind Harmer
0.119
315821AE2-092 GEN
Solar/Wind Harmer
0.014
970301AG2-198 GEN
Solar/Wind Harmer
9.583
3147133PAMPLIN
Solar/Wind Harmer
0.221
3147133PAMPLIN
Solar/Wind Harmer
0.176
958211AF2-115 GEN
Solar/Wind Harmer
2.506
963191AG1-168 GEN
Solar/Wind Harmer
0.835
971741AH1-377 GEN
Solar/Wind Harmer
20.177
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.401
971775AH1-396 GEN
Solar/Wind Harmer
0.278
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971223AH1-071 GEN
Solar/Wind Harmer
1.233
962561AG1-105 GEN
Solar/Wind Harmer
5.397
939181AE1-148 GEN
Solar/Wind Harmer
5.333
970099AG2-077 GEN
Solar/Wind Harmer
11.718
964791AG1-342 GEN
Solar/Wind Harmer
2.089
3146843MT LREL
Solar/Wind Harmer
0.109
3146843MT LREL
Solar/Wind Harmer
0.109
3143526WINTERP
Solar/Wind Harmer
0.504
970933AG2-581 GEN
Solar/Wind Harmer
7.465
316181AB2-040 GEN
Solar/Wind Harmer
0.116
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.078
966811AG1-552 GEN
Solar/Wind Harmer
0.843
3145593CAROLNA
Solar/Wind Harmer
0.097
3145783HORNRTN
Solar/Wind Harmer
1.361
3145783HORNRTN
Solar/Wind Harmer
1.089
3145783HORNRTN
Solar/Wind Harmer
0.34
3145783HORNRTN
Solar/Wind Harmer
0.136
316426AA2-053 GEN
Solar/Wind Harmer
0.256
3144356SAPONY
Solar/Wind Harmer
0.607
316274AC1-208 GEN
Solar/Wind Harmer
0.366
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.042
3145893MURPHYS
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
0.126
3145796HORNRTN
Solar/Wind Harmer
0.209
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
315742AE1-103 GEN
Solar/Wind Harmer
0.001
316222AC1-221 GEN
Solar/Wind Harmer
0.272
316065AD1-022 GEN
Solar/Wind Harmer
3.004
970657AG2-426 GEN
Solar/Wind Harmer
2.275
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
2.446
3146376EDENTON
Solar/Wind Harmer
0.286
3146376EDENTON
Solar/Wind Harmer
0.286
961601AG1-000A GEN
Solar/Wind Harmer
1.137
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3145493TOT1
Solar/Wind Harmer
0.148
3145453TOT5
Solar/Wind Harmer
0.089
3145603CNETO
Solar/Wind Harmer
0.059
3146386ELIZ CT
Solar/Wind Harmer
0.064
3145933PARMELE
Solar/Wind Harmer
0.127
3145933PARMELE
Solar/Wind Harmer
0.063
3130086AYDLETT
Solar/Wind Harmer
0.253
3137176SLIGO L2192
Solar/Wind Harmer
0.252
3146456SLIGO L269
Solar/Wind Harmer
1.121
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.035
3151931BEARGRDN S1
50/50
5.469
3151911BEARGRDN G1
50/50
4.238
3144293JTRSVLE
50/50
0.706
970119AG2-088 GEN
50/50
15.414
3151531CLOVER1
50/50
2.348
3151601KERR 3
50/50
0.22
3151581KERR 1
50/50
0.079
3147043LAWRENC
50/50
0.939
3151051BRUNSWICKS1
50/50
2.197
3151021BRUNSWICKG1
50/50
1.059
971451AH1-221 GEN
50/50
3.216
315243AE2-183_GT3
50/50
1.321
3151261ROARAP2
50/50
0.097
3150851SPRUNCC
50/50
0.364
972003AH1-546 GEN
Solar/Wind Harmer
18.676
971377AH1-170 GEN
Solar/Wind Harmer
4.327
3147623JAMES R
Solar/Wind Harmer
0.94
970937AG2-583 GEN
Solar/Wind Harmer
23.217
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.147
3146926FARMVIL
Solar/Wind Harmer
0.176
316336AC2-165 C
Solar/Wind Harmer
0.011
3143336POWHATN
Solar/Wind Harmer
4.472
963171AG1-166 GEN
Solar/Wind Harmer
1.114
971563AH1-280 GEN
Solar/Wind Harmer
2.228
970685AG2-442 GEN
Solar/Wind Harmer
14.313
962491AG1-098 GEN
Solar/Wind Harmer
7.815
315693AD1-088 GEN
Solar/Wind Harmer
6.344
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Harmer
0.116
957481AF2-042 GEN
Solar/Wind Harmer
29.295
970401AG2-262 GEN
Solar/Wind Harmer
0.638
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
4.184
3143526WINTERP
Solar/Wind Harmer
0.504
316129AC1-054 GEN
Solar/Wind Harmer
0.363
971795AH1-408 GEN
Solar/Wind Harmer
6.199
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.793
970919AG2-571 GEN
Solar/Wind Harmer
2.76
970087AG2-069 GEN
Solar/Wind Harmer
6.187
3145783HORNRTN
Solar/Wind Harmer
0.076
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
5.984
316023GEN1_S
Solar/Wind Harmer
0.164
939411AE1-173 GEN
Solar/Wind Harmer
30.681
316011AB1-132 GEN
Solar/Wind Harmer
1.286
962571AG1-106 GEN
Solar/Wind Harmer
1.007
3146263WOODLND
Solar/Wind Harmer
0.071
3145893MURPHYS
Solar/Wind Harmer
0.281
3145893MURPHYS
Solar/Wind Harmer
0.312
3145796HORNRTN
Solar/Wind Harmer
0.23
3145796HORNRTN
Solar/Wind Harmer
0.07
316212AC1-099_GEN
Solar/Wind Harmer
0.359
3146173TUNIS
Solar/Wind Harmer
0.069
3145823KELFORD
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
315722AD1-056 GEN
Solar/Wind Harmer
0.422
3146233WITAKRS
Solar/Wind Harmer
0.263
3146206CASHIE
Solar/Wind Harmer
0.065
971547AH1-271 GEN
Solar/Wind Harmer
1.396
3151921BEARGRDN G2
50/50
4.238
3144293JTRSVLE
50/50
0.706
970413AG2-270 GEN
50/50
10.245
3151591KERR 2
50/50
0.22
3151031BRUNSWICKG2
50/50
1.059
3151261ROARAP2
50/50
0.095
3150861SPRUNCD
50/50
0.364
966251AG1-494 GEN
50/50
1.288
970221AG2-151 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
0.132
3146926FARMVIL
Solar/Wind Harmer
0.176
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.159
316258AE1-075 C
Solar/Wind Harmer
0.19
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.801
970909AG2-566 GEN
Solar/Wind Harmer
2.396
3147133PAMPLIN
Solar/Wind Harmer
0.693
971193AH1-056 GEN
Solar/Wind Harmer
13.448
963181AG1-167 GEN
Solar/Wind Harmer
0.835
959311AF2-222 GEN
Solar/Wind Harmer
15.884
970257AG2-171 GEN
Solar/Wind Harmer
5.55
315785AD2-033 C
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
9.804
316131AB2-060 GEN
Solar/Wind Harmer
0.426
958131AF2-107 GEN
Solar/Wind Harmer
3.651
316478AD1-087 GEN
Solar/Wind Harmer
0.382
316486AD2-202 GEN
Solar/Wind Harmer
0.112
3147043LAWRENC
Solar/Wind Harmer
0.059
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.912
971683AH1-343 GEN
Solar/Wind Harmer
3.032
313506AB2-031 GEN
Solar/Wind Harmer
0.248
970917AG2-570 GEN
Solar/Wind Harmer
6.901
316365GEN2_N
Solar/Wind Harmer
0.164
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
0.117
3145893MURPHYS
Solar/Wind Harmer
0.07
957521AF2-046 GEN
Solar/Wind Harmer
5.202
961681AG1-008 GEN
Solar/Wind Harmer
5.202
3145796HORNRTN
Solar/Wind Harmer
0.279
3145796HORNRTN
Solar/Wind Harmer
0.07
316210AC1-098 GEN
Solar/Wind Harmer
0.644
3146173TUNIS
Solar/Wind Harmer
0.069
316463AE2-346 GEN
Solar/Wind Harmer
0.059
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.732
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.069
316327AA2-057 GEN
Solar/Wind Harmer
0.102
315724AD1-057 GEN
Solar/Wind Harmer
0.25
3145273HOLLAND
Solar/Wind Harmer
0.05
3156021HOLLOMANSOL
Solar/Wind Harmer
0.301
3146233WITAKRS
Solar/Wind Harmer
0.331
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3146206CASHIE
Solar/Wind Harmer
0.065
315813AE1-149 C
Solar/Wind Harmer
3.482
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316283AC2-100 C
Solar/Wind Harmer
0.127
315839AE2-212 C
Solar/Wind Harmer
0.001
315737AD1-076 GEN
Solar/Wind Harmer
0.835
970661AG2-428 GEN
Solar/Wind Harmer
1.373
971157AH1-035 GEN
Solar/Wind Harmer
0.778
3151541CLOVER2
50/50
2.336
3151611KERR 4
50/50
0.22
3151621KERR 5
50/50
0.22
3151631KERR 6
50/50
0.22
3151641KERR 7
50/50
0.22
963041AG1-153 GEN
50/50
2.144
315244AE2-183_ST
50/50
2.284
3151281ROARAP4
50/50
0.094
3151281ROARAP4
50/50
0.088
971285AH1-108 GEN
50/50
0.596
315779AE2-040
50/50
1.013
971447AH1-217 GEN
Solar/Wind Harmer
11.337
971845AH1-439 GEN
Solar/Wind Harmer
16.33
970285AG2-188 GEN
Solar/Wind Harmer
27.559
270494AE1-108_GEN
Solar/Wind Harmer
3.817
315657AE1-056 GEN
Solar/Wind Harmer
7.617
946301AF1-294 GEN
Solar/Wind Harmer
4.122
961791AG1-021 GEN
Solar/Wind Harmer
2.005
970683AG2-441 GEN
Solar/Wind Harmer
12.78
970681AG2-440 GEN
Solar/Wind Harmer
10.224
3144303KENBRDG
Solar/Wind Harmer
0.139
971443AH1-215 GEN
Solar/Wind Harmer
2.888
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.258
316233AE1-074 FULL
Solar/Wind Harmer
0.078
971281AH1-106 GEN
Solar/Wind Harmer
1.344
971283AH1-107 GEN
Solar/Wind Harmer
1.344
970831AG2-522 GEN
Solar/Wind Harmer
4.036
3147173SINAI
Solar/Wind Harmer
0.092
3147243WELCO
Solar/Wind Harmer
0.057
971967AH1-528 GEN
Solar/Wind Harmer
13.711
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
16.986
970673AG2-436 GEN
Solar/Wind Harmer
11.324
941031AE2-094 GEN
Solar/Wind Harmer
14.544
944011AF1-069 GEN
Solar/Wind Harmer
4.752
3137643SOCKMAN
Solar/Wind Harmer
0.315
970865AG2-541 GEN
Solar/Wind Harmer
2.702
970085AG2-068 GEN
Solar/Wind Harmer
4.124
970581AG2-369 GEN
Solar/Wind Harmer
3.547
315607AA1-063A GEN
Solar/Wind Harmer
0.154
3146043SEABORD
Solar/Wind Harmer
0.075
315814AE2-033 C
Solar/Wind Harmer
5.747
316315AB2-025 C
Solar/Wind Harmer
0.059
965291AG1-394 GEN
Solar/Wind Harmer
0.317
315652AC1-086 GEN
Solar/Wind Harmer
7.782
3145893MURPHYS
Solar/Wind Harmer
0.19
3145893MURPHYS
Solar/Wind Harmer
0.07
3145796HORNRTN
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.028
3146033SCOT NK
Solar/Wind Harmer
0.276
316123AC1-075 GEN
Solar/Wind Harmer
0.094
970165AG2-112 GEN
Solar/Wind Harmer
0.558
970163AG2-111 GEN
Solar/Wind Harmer
0.532
3145513AHOSKIE
Solar/Wind Harmer
0.143
3145513AHOSKIE
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3143316POE
Solar/Wind Harmer
0.269
316319Z2-044 C
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.065
970601AG2-382 GEN
Solar/Wind Harmer
2.444
315732AD1-074 GEN1
Solar/Wind Harmer
0.373
315733AD1-074 GEN2
Solar/Wind Harmer
0.373
315735AD1-075 GEN1
Solar/Wind Harmer
0.187
3130546PLYMOUTH
Solar/Wind Harmer
0.065
315816AE2-034 GEN
Solar/Wind Harmer
0.277
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.044
316311AC2-079 GEN
Solar/Wind Harmer
1.853
970659AG2-427 GEN
Solar/Wind Harmer
3.146
316381AD1-082 GEN
Solar/Wind Harmer
0.068
970661AG2-428 GEN
Solar/Wind Harmer
6.453
3145663CRESWEL
Solar/Wind Harmer
0.181
971163AH1-040 GEN
Solar/Wind Harmer
5.167
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.052
316359AB2-059 GEN
Solar/Wind Harmer
0.231
316049AB1-081 GEN
Solar/Wind Harmer
0.368
3142053HEARTS
Solar/Wind Harmer
0.113
316093AE2-104_GEN
Solar/Wind Harmer
1.081
3130156CHOWAN
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3142543TWELFTH
Solar/Wind Harmer
0.006
3146516WINFALL
Solar/Wind Harmer
0.207
3146516WINFALL
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.283
316246AF1-032 C
Solar/Wind Harmer
0.029
3146293MARTNCO
Solar/Wind Harmer
0.059
316494AC1-189 GEN
Solar/Wind Harmer
0.214
3146456SLIGO L269
Solar/Wind Harmer
0.063
316388AE2-253 GEN
Solar/Wind Harmer
0.198
944591AF1-124 GEN
Solar/Wind Harmer
14.289
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
315671AE2-027_GEN
Solar/Wind Harmer
4.043
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
1.077
3145336SMITFLD
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
0.644
961611AG1-000B GEN
Solar/Wind Harmer
3.17
971647AH1-324 GEN
Solar/Wind Harmer
2.576
3143096IRON208
Adder
0.252
971069AG2-661 GEN
Solar/Wind Harmer
1.071
316458AB2-190 GEN2
Solar/Wind Harmer
0.323
970129AG2-093 GEN
Solar/Wind Harmer
1.71
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.903
3147666LOUISA
Solar/Wind Helper
0.521
315614AA2-178 GEN
Solar/Wind Harmer
0.37
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.129
3146376EDENTON
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
4.548
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316435W1029_GEN3
Solar/Wind Harmer
0
965281AG1-393 GEN
Solar/Wind Harmer
0.68
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
316320Y1-086
Solar/Wind Harmer
0
3145933PARMELE
Solar/Wind Harmer
0.063
966801AG1-551 GEN
Solar/Wind Harmer
0.74
3146456SLIGO L269
Solar/Wind Harmer
0.063
971153AH1-033 GEN
Solar/Wind Harmer
0.732
944581AF1-123 GEN
Solar/Wind Harmer
14.239
944601AF1-125 GEN
Solar/Wind Harmer
14.019
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3151101ELIZAR3
Adder
5.847
3144873MCLAUGH
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.009
315773AC2-141 GEN
Solar/Wind Harmer
2.27
3145336SMITFLD
Solar/Wind Harmer
0.025
3151221GRAVEL6
Adder
4.403
3151171GRAVELC
Adder
0.847
961611AG1-000B GEN
Solar/Wind Harmer
1.612
3143096IRON208
Adder
0.252
3143096IRON208
Adder
0.247
315778AD1-151 GEN
Solar/Wind Harmer
4.818
970129AG2-093 GEN
Solar/Wind Harmer
3.634
970133AG2-095 GEN
Solar/Wind Harmer
0.576
316499AE2-029_GEN
Solar/Wind Helper
0.501
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.3
3148013FISHERV
Solar/Wind Helper
0.129
315616AA1-038_C
Solar/Wind Helper
0.524
315835AF2-110_GEN
Solar/Wind Harmer
0.441
3130156CHOWAN
Solar/Wind Harmer
0.064
3130156CHOWAN
Solar/Wind Harmer
0.064
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
316321Z2-027
Solar/Wind Harmer
0.012
3145176PASQUOTANK
Solar/Wind Harmer
0.039
3146396TANGLEW
Solar/Wind Harmer
0.175
316420AA1-050 GEN
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.034
316305AF2-043 C
Solar/Wind Harmer
0.001
957861AF2-080 GEN
Solar/Wind Harmer
2.737
3146406KITTY HAWK
Solar/Wind Harmer
0.008
319010AE1-072 C
Solar/Wind Harmer
0.319
957871AF2-081 GEN
Solar/Wind Harmer
3.153
316005AA1-067
Solar/Wind Harmer
0.068
3145746EVERETS
Solar/Wind Harmer
0.252
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
970181AG2-120 GEN
Solar/Wind Harmer
0.787
3151081ELIZAR1
Adder
5.773
3151091ELIZAR2
Adder
5.672
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.68
3152601GOSPORTA
Adder
0.628
971445AH1-216 GEN
Solar/Wind Harmer
4.321
972265AH1-717 GEN
Adder
4.702
3151201GRAVEL4
Adder
4.408
3151191GRAVEL3
Adder
4.352
3151211GRAVEL5
Adder
4.352
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.323
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.077
3148013FISHERV
Solar/Wind Helper
0.074
3148463FAIRFLD
Solar/Wind Helper
0.116
316339AD2-160 GEN
Solar/Wind Harmer
0.103
3145506HICKORY
Solar/Wind Harmer
0.253
3145506HICKORY
Solar/Wind Harmer
0.152
3145506HICKORY
Solar/Wind Harmer
0.038
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.061
942751AE2-291 GEN
Solar/Wind Harmer
3.43
316240AF1-291 C
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.012
3150991CHESPKB
Adder
0.659
3150991CHESPKB
Adder
0.643
944641AF1-129 GEN
Adder
29.755
316236AE1-162_GEN
Solar/Wind Harmer
0
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.068
966001AG1-469 GEN
Solar/Wind Helper
0.206
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.131
MECLTFEXP_MEC->PJM
CLTF
0.546
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CPLELTFEXP_CPLE->PJM
CLTF
4.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.705
LAGNLTFEXP_LAGN->PJM
CLTF
1.972
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.458
TVALTFEXP_TVA->PJM
CLTF
0.973
NYPJM->LTFIMP_NY
CLTF
0.616
LGEELTFEXP_LGEE->PJM
CLTF
0.137
WECLTFEXP_WEC->PJM
CLTF
0.063

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:182.57 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1515.37
MW Contribution:2.11
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.46
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.704
970119AG2-088 GEN
50/50
15.406
972003AH1-546 GEN
Solar/Wind Harmer
24.588
971377AH1-170 GEN
Solar/Wind Harmer
5.686
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.518
316322AB2-045
Solar/Wind Harmer
1.382
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.598
3143336POWHATN
Solar/Wind Harmer
3.349
963171AG1-166 GEN
Solar/Wind Harmer
2.929
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
18.817
962491AG1-098 GEN
Solar/Wind Harmer
10.277
315693AD1-088 GEN
Solar/Wind Harmer
7.416
316237AB2-079_GEN
Solar/Wind Harmer
0.439
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.531
970401AG2-262 GEN
Solar/Wind Harmer
0.797
315687AD1-152 GEN
Solar/Wind Harmer
1.353
971065AG2-659 GEN
Solar/Wind Harmer
5.503
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.704
970221AG2-151 GEN
Solar/Wind Harmer
28.432
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.296
316313AB2-026
Solar/Wind Harmer
0.761
316258AE1-075 C
Solar/Wind Harmer
0.685
316405AF2-144 C
Solar/Wind Harmer
0.723
3143336POWHATN
Solar/Wind Harmer
2.847
970909AG2-566 GEN
Solar/Wind Harmer
2.392
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.485
963181AG1-167 GEN
Solar/Wind Harmer
2.197
959311AF2-222 GEN
Solar/Wind Harmer
20.924
970257AG2-171 GEN
Solar/Wind Harmer
7.297
315785AD2-033 C
Solar/Wind Harmer
4.227
964241AG1-285 GEN
Solar/Wind Harmer
12.89
316131AB2-060 GEN
Solar/Wind Harmer
1.639
316129AC1-054 GEN
Solar/Wind Harmer
0.948
971795AH1-408 GEN
Solar/Wind Harmer
7.828
316003AC1-222 GEN
Solar/Wind Harmer
0.95
960081AF2-299 GEN
Solar/Wind Harmer
1.043
970919AG2-571 GEN
Solar/Wind Harmer
2.759
970087AG2-069 GEN
Solar/Wind Harmer
8.141
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
940641AE2-051 GEN
Solar/Wind Harmer
7.878
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.555
939411AE1-173 GEN
Solar/Wind Harmer
40.398
316011AB1-132 GEN
Solar/Wind Harmer
1.663
962571AG1-106 GEN
Solar/Wind Harmer
1.142
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.68
958131AF2-107 GEN
Solar/Wind Harmer
4.847
316478AD1-087 GEN
Solar/Wind Harmer
1.065
316486AD2-202 GEN
Solar/Wind Harmer
0.312
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.31
960061AF2-297 GEN
Solar/Wind Harmer
5.143
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.986
3144293JTRSVLE
50/50
0.704
3144293JTRSVLE
50/50
0.593
970535AG2-341 GEN
50/50
2.107
971489AH1-241 GEN
Solar/Wind Harmer
26.992
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.547
970301AG2-198 GEN
Solar/Wind Harmer
12.599
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
963191AG1-168 GEN
Solar/Wind Harmer
2.197
971741AH1-377 GEN
Solar/Wind Harmer
26.527
316034AC1-036 C
Solar/Wind Harmer
0.362
970323AG2-213 GEN
Solar/Wind Harmer
9.73
971775AH1-396 GEN
Solar/Wind Harmer
1.386
313527AB2-043 GEN
Solar/Wind Harmer
2.416
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.096
939181AE1-148 GEN
Solar/Wind Harmer
7.013
970099AG2-077 GEN
Solar/Wind Harmer
15.412
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.821
972187AH1-678 GEN
Adder
2.289
316181AB2-040 GEN
Solar/Wind Harmer
1.257
972185AH1-677 GEN
Adder
4.486
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.855
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.79
316222AC1-221 GEN
Solar/Wind Harmer
0.745
316065AD1-022 GEN
Solar/Wind Harmer
3.665
970657AG2-426 GEN
Solar/Wind Harmer
2.282
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.782
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.838
970659AG2-427 GEN
Solar/Wind Harmer
3.885
316381AD1-082 GEN
Solar/Wind Harmer
0.67
970661AG2-428 GEN
Solar/Wind Harmer
7.748
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.803
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.974
316049AB1-081 GEN
Solar/Wind Harmer
0.78
316093AE2-104_GEN
Solar/Wind Harmer
2.1
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
315800Z1-036_GEN1
Solar/Wind Harmer
1.779
316174AB2-169 GEN
Solar/Wind Harmer
1.109
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
316246AF1-032 C
Solar/Wind Harmer
0.144
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
944591AF1-124 GEN
Solar/Wind Harmer
32.454
3150981CHESPKA
Adder
0.786
3151171GRAVELC
Adder
0.645
3143096IRON208
Adder
0.253
944631AF1-128 GEN
Adder
26.841
316192AB2-158 GEN
Solar/Wind Helper
1.013
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
972205AH1-687 GEN
50/50
20.633
316303AF2-085
50/50
2.054
971447AH1-217 GEN
Solar/Wind Harmer
14.897
971845AH1-439 GEN
Solar/Wind Harmer
21.465
970285AG2-188 GEN
Solar/Wind Harmer
34.19
270494AE1-108_GEN
Solar/Wind Harmer
9.286
315657AE1-056 GEN
Solar/Wind Harmer
9.291
946301AF1-294 GEN
Solar/Wind Harmer
6.004
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
16.801
970681AG2-440 GEN
Solar/Wind Harmer
13.441
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.796
316239AB2-077_GEN
Solar/Wind Harmer
0.439
316238AB2-078_GEN
Solar/Wind Harmer
0.439
316118AC1-105 GEN
Solar/Wind Harmer
0.773
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.769
971283AH1-107 GEN
Solar/Wind Harmer
1.769
970831AG2-522 GEN
Solar/Wind Harmer
5.308
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.09
946281AF1-292 GEN
Solar/Wind Harmer
0.208
316087AB2-174 GEN
Solar/Wind Harmer
1.297
970673AG2-436 GEN
Solar/Wind Harmer
18.787
970673AG2-436 GEN
Solar/Wind Harmer
9.512
941031AE2-094 GEN
Solar/Wind Harmer
16.63
944011AF1-069 GEN
Solar/Wind Harmer
5.211
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970865AG2-541 GEN
Solar/Wind Harmer
3.55
970085AG2-068 GEN
Solar/Wind Harmer
5.427
970581AG2-369 GEN
Solar/Wind Harmer
4.667
315607AA1-063A GEN
Solar/Wind Harmer
0.852
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.6
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.71
315652AC1-086 GEN
Solar/Wind Harmer
8.941
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
316123AC1-075 GEN
Solar/Wind Harmer
0.832
970165AG2-112 GEN
Solar/Wind Harmer
0.733
970163AG2-111 GEN
Solar/Wind Harmer
0.699
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316319Z2-044 C
Solar/Wind Harmer
0.41
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.217
315732AD1-074 GEN1
Solar/Wind Harmer
1.475
315733AD1-074 GEN2
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.737
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316349AD2-085 GEN
Solar/Wind Harmer
0.645
315816AE2-034 GEN
Solar/Wind Harmer
0.587
316311AC2-079 GEN
Solar/Wind Harmer
3.659
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.779
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
316321Z2-027
Solar/Wind Harmer
0.193
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.193
316420AA1-050 GEN
Solar/Wind Harmer
0.816
316305AF2-043 C
Solar/Wind Harmer
0.215
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
313506AB2-031 GEN
Solar/Wind Harmer
0.724
970917AG2-570 GEN
Solar/Wind Harmer
21.795
3150861SPRUNCD
Adder
0.344
316365GEN2_N
Solar/Wind Harmer
0.555
3156081AA2-088 GEN
Solar/Wind Harmer
2.586
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.185
961681AG1-008 GEN
Solar/Wind Harmer
6.185
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146173TUNIS
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.125
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.963
316317KELFORD C
Solar/Wind Harmer
0.363
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.766
315724AD1-057 GEN
Solar/Wind Harmer
0.43
3145273HOLLAND
Solar/Wind Harmer
-0.006
3156021HOLLOMANSOL
Solar/Wind Harmer
1.002
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.587
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
1.186
315839AE2-212 C
Solar/Wind Harmer
0.22
970661AG2-428 GEN
Solar/Wind Harmer
1.373
315737AD1-076 GEN
Solar/Wind Harmer
1.386
316283AC2-100 C
Solar/Wind Harmer
0.686
971157AH1-035 GEN
Solar/Wind Harmer
0.911
315614AA2-178 GEN
Solar/Wind Harmer
0.783
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.858
3146516WINFALL
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.896
316435W1029_GEN3
Solar/Wind Harmer
1.299
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.419
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.891
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151101ELIZAR3
Adder
5.849
3151221GRAVEL6
Adder
4.406
3151171GRAVELC
Adder
0.848
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.338
3148013FISHERV
Solar/Wind Helper
0.13
315616AA1-038_C
Solar/Wind Helper
0.528
944581AF1-123 GEN
Solar/Wind Harmer
20.452
3151081ELIZAR1
Adder
5.776
3151091ELIZAR2
Adder
5.675
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.681
3152601GOSPORTA
Adder
0.628
972265AH1-717 GEN
Adder
4.706
3151201GRAVEL4
Adder
4.411
3151191GRAVEL3
Adder
4.355
3151211GRAVEL5
Adder
4.355
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
3.387
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.822
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.78
966001AG1-469 GEN
Solar/Wind Helper
0.216
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.573
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.107
MECLTFEXP_MEC->PJM
CLTF
0.537
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CPLELTFEXP_CPLE->PJM
CLTF
4.206
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.627
LAGNLTFEXP_LAGN->PJM
CLTF
1.959
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.437
TVALTFEXP_TVA->PJM
CLTF
0.967
NYPJM->LTFIMP_NY
CLTF
0.612
LGEELTFEXP_LGEE->PJM
CLTF
0.133
WECLTFEXP_WEC->PJM
CLTF
0.061

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:182.57 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1515.34
MW Contribution:2.11
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.46
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.704
970119AG2-088 GEN
50/50
15.406
972003AH1-546 GEN
Solar/Wind Harmer
24.587
971377AH1-170 GEN
Solar/Wind Harmer
5.686
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.517
316322AB2-045
Solar/Wind Harmer
1.382
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.597
3143336POWHATN
Solar/Wind Harmer
3.349
963171AG1-166 GEN
Solar/Wind Harmer
2.929
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
18.817
962491AG1-098 GEN
Solar/Wind Harmer
10.277
315693AD1-088 GEN
Solar/Wind Harmer
7.416
316237AB2-079_GEN
Solar/Wind Harmer
0.439
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.531
970401AG2-262 GEN
Solar/Wind Harmer
0.797
315687AD1-152 GEN
Solar/Wind Harmer
1.353
971065AG2-659 GEN
Solar/Wind Harmer
5.503
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.948
971795AH1-408 GEN
Solar/Wind Harmer
7.828
316003AC1-222 GEN
Solar/Wind Harmer
0.95
960081AF2-299 GEN
Solar/Wind Harmer
1.043
970919AG2-571 GEN
Solar/Wind Harmer
2.759
970087AG2-069 GEN
Solar/Wind Harmer
8.141
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
940641AE2-051 GEN
Solar/Wind Harmer
7.878
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.555
939411AE1-173 GEN
Solar/Wind Harmer
40.398
316011AB1-132 GEN
Solar/Wind Harmer
1.663
962571AG1-106 GEN
Solar/Wind Harmer
1.142
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.68
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.782
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.838
970659AG2-427 GEN
Solar/Wind Harmer
3.885
316381AD1-082 GEN
Solar/Wind Harmer
0.67
970661AG2-428 GEN
Solar/Wind Harmer
7.748
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.803
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.974
316049AB1-081 GEN
Solar/Wind Harmer
0.78
316093AE2-104_GEN
Solar/Wind Harmer
2.1
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
315800Z1-036_GEN1
Solar/Wind Harmer
1.779
3144293JTRSVLE
50/50
0.704
3144293JTRSVLE
50/50
0.593
970535AG2-341 GEN
50/50
2.107
971489AH1-241 GEN
Solar/Wind Harmer
26.992
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.547
970301AG2-198 GEN
Solar/Wind Harmer
12.599
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
963191AG1-168 GEN
Solar/Wind Harmer
2.197
971741AH1-377 GEN
Solar/Wind Harmer
26.527
316034AC1-036 C
Solar/Wind Harmer
0.361
970323AG2-213 GEN
Solar/Wind Harmer
9.729
971775AH1-396 GEN
Solar/Wind Harmer
1.386
313527AB2-043 GEN
Solar/Wind Harmer
2.416
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.096
939181AE1-148 GEN
Solar/Wind Harmer
7.013
970099AG2-077 GEN
Solar/Wind Harmer
15.412
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.821
972187AH1-678 GEN
Adder
2.289
316181AB2-040 GEN
Solar/Wind Harmer
1.257
972185AH1-677 GEN
Adder
4.486
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.855
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.79
316222AC1-221 GEN
Solar/Wind Harmer
0.745
316065AD1-022 GEN
Solar/Wind Harmer
3.665
970657AG2-426 GEN
Solar/Wind Harmer
2.282
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
3.387
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.822
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.781
966001AG1-469 GEN
Solar/Wind Helper
0.216
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.704
970221AG2-151 GEN
Solar/Wind Harmer
28.431
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.296
316313AB2-026
Solar/Wind Harmer
0.761
316258AE1-075 C
Solar/Wind Harmer
0.685
316405AF2-144 C
Solar/Wind Harmer
0.723
3143336POWHATN
Solar/Wind Harmer
2.847
970909AG2-566 GEN
Solar/Wind Harmer
2.392
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.484
963181AG1-167 GEN
Solar/Wind Harmer
2.197
959311AF2-222 GEN
Solar/Wind Harmer
20.924
970257AG2-171 GEN
Solar/Wind Harmer
7.297
315785AD2-033 C
Solar/Wind Harmer
4.227
964241AG1-285 GEN
Solar/Wind Harmer
12.89
316131AB2-060 GEN
Solar/Wind Harmer
1.639
958131AF2-107 GEN
Solar/Wind Harmer
4.847
316478AD1-087 GEN
Solar/Wind Harmer
1.065
316486AD2-202 GEN
Solar/Wind Harmer
0.312
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.31
960061AF2-297 GEN
Solar/Wind Harmer
5.143
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.986
313506AB2-031 GEN
Solar/Wind Harmer
0.724
970917AG2-570 GEN
Solar/Wind Harmer
21.795
3150861SPRUNCD
Adder
0.344
316365GEN2_N
Solar/Wind Harmer
0.555
3156081AA2-088 GEN
Solar/Wind Harmer
2.585
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.185
961681AG1-008 GEN
Solar/Wind Harmer
6.185
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146173TUNIS
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.125
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.963
316317KELFORD C
Solar/Wind Harmer
0.363
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.766
315724AD1-057 GEN
Solar/Wind Harmer
0.43
3145273HOLLAND
Solar/Wind Harmer
-0.006
3156021HOLLOMANSOL
Solar/Wind Harmer
1.002
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.587
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
1.186
315839AE2-212 C
Solar/Wind Harmer
0.22
970661AG2-428 GEN
Solar/Wind Harmer
1.373
315737AD1-076 GEN
Solar/Wind Harmer
1.386
316283AC2-100 C
Solar/Wind Harmer
0.686
971157AH1-035 GEN
Solar/Wind Harmer
0.911
315614AA2-178 GEN
Solar/Wind Harmer
0.783
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.858
3146516WINFALL
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.896
316435W1029_GEN3
Solar/Wind Harmer
1.299
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.419
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.891
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151101ELIZAR3
Adder
5.85
3151221GRAVEL6
Adder
4.406
3151171GRAVELC
Adder
0.848
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.339
3148013FISHERV
Solar/Wind Helper
0.13
315616AA1-038_C
Solar/Wind Helper
0.528
944581AF1-123 GEN
Solar/Wind Harmer
20.452
316174AB2-169 GEN
Solar/Wind Harmer
1.109
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
316246AF1-032 C
Solar/Wind Harmer
0.144
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
944591AF1-124 GEN
Solar/Wind Harmer
32.454
3150981CHESPKA
Adder
0.786
3151171GRAVELC
Adder
0.645
3143096IRON208
Adder
0.253
944631AF1-128 GEN
Adder
26.842
316192AB2-158 GEN
Solar/Wind Helper
1.014
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
972205AH1-687 GEN
50/50
20.633
316303AF2-085
50/50
2.054
971447AH1-217 GEN
Solar/Wind Harmer
14.896
971845AH1-439 GEN
Solar/Wind Harmer
21.465
970285AG2-188 GEN
Solar/Wind Harmer
34.19
270494AE1-108_GEN
Solar/Wind Harmer
9.286
315657AE1-056 GEN
Solar/Wind Harmer
9.291
946301AF1-294 GEN
Solar/Wind Harmer
6.004
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
16.8
970681AG2-440 GEN
Solar/Wind Harmer
13.44
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.796
316239AB2-077_GEN
Solar/Wind Harmer
0.439
316238AB2-078_GEN
Solar/Wind Harmer
0.439
316118AC1-105 GEN
Solar/Wind Harmer
0.773
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.769
971283AH1-107 GEN
Solar/Wind Harmer
1.769
970831AG2-522 GEN
Solar/Wind Harmer
5.308
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.09
946281AF1-292 GEN
Solar/Wind Harmer
0.208
316087AB2-174 GEN
Solar/Wind Harmer
1.297
970673AG2-436 GEN
Solar/Wind Harmer
18.787
970673AG2-436 GEN
Solar/Wind Harmer
9.512
941031AE2-094 GEN
Solar/Wind Harmer
16.63
944011AF1-069 GEN
Solar/Wind Harmer
5.211
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970865AG2-541 GEN
Solar/Wind Harmer
3.55
970085AG2-068 GEN
Solar/Wind Harmer
5.427
970581AG2-369 GEN
Solar/Wind Harmer
4.667
315607AA1-063A GEN
Solar/Wind Harmer
0.852
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.6
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.71
315652AC1-086 GEN
Solar/Wind Harmer
8.941
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
316123AC1-075 GEN
Solar/Wind Harmer
0.832
970165AG2-112 GEN
Solar/Wind Harmer
0.733
970163AG2-111 GEN
Solar/Wind Harmer
0.699
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316319Z2-044 C
Solar/Wind Harmer
0.41
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.217
315732AD1-074 GEN1
Solar/Wind Harmer
1.475
315733AD1-074 GEN2
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.737
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316349AD2-085 GEN
Solar/Wind Harmer
0.645
315816AE2-034 GEN
Solar/Wind Harmer
0.587
316311AC2-079 GEN
Solar/Wind Harmer
3.659
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.779
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.193
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.193
316305AF2-043 C
Solar/Wind Harmer
0.215
316420AA1-050 GEN
Solar/Wind Harmer
0.816
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
3151081ELIZAR1
Adder
5.776
3151091ELIZAR2
Adder
5.675
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.681
3152601GOSPORTA
Adder
0.628
972265AH1-717 GEN
Adder
4.706
3151201GRAVEL4
Adder
4.411
3151191GRAVEL3
Adder
4.355
3151211GRAVEL5
Adder
4.355
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.572
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.107
MECLTFEXP_MEC->PJM
CLTF
0.537
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CPLELTFEXP_CPLE->PJM
CLTF
4.206
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.626
LAGNLTFEXP_LAGN->PJM
CLTF
1.959
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.437
TVALTFEXP_TVA->PJM
CLTF
0.967
NYPJM->LTFIMP_NY
CLTF
0.612
LGEELTFEXP_LGEE->PJM
CLTF
0.133
WECLTFEXP_WEC->PJM
CLTF
0.061

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:175.31 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1455.08
MW Contribution:2.03
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.91
316303AF2-085
50/50
2.425
971447AH1-217 GEN
Solar/Wind Harmer
15.108
971845AH1-439 GEN
Solar/Wind Harmer
21.634
970285AG2-188 GEN
Solar/Wind Harmer
34.428
270494AE1-108_GEN
Solar/Wind Harmer
9.407
315657AE1-056 GEN
Solar/Wind Harmer
9.233
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
16.612
970681AG2-440 GEN
Solar/Wind Harmer
13.29
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.737
316239AB2-077_GEN
Solar/Wind Harmer
0.427
316238AB2-078_GEN
Solar/Wind Harmer
0.427
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316118AC1-105 GEN
Solar/Wind Harmer
0.741
970831AG2-522 GEN
Solar/Wind Harmer
5.054
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
946281AF1-292 GEN
Solar/Wind Harmer
0.196
971967AH1-528 GEN
Solar/Wind Harmer
16.369
316087AB2-174 GEN
Solar/Wind Harmer
1.222
970865AG2-541 GEN
Solar/Wind Harmer
3.392
3137643SOCKMAN
Solar/Wind Harmer
-0.033
970673AG2-436 GEN
Solar/Wind Harmer
16.777
970673AG2-436 GEN
Solar/Wind Harmer
8.495
315607AA1-063A GEN
Solar/Wind Harmer
0.8
941031AE2-094 GEN
Solar/Wind Harmer
14.78
944011AF1-069 GEN
Solar/Wind Harmer
4.631
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.884
970581AG2-369 GEN
Solar/Wind Harmer
4.201
315814AE2-033 C
Solar/Wind Harmer
7.048
316315AB2-025 C
Solar/Wind Harmer
0.204
965291AG1-394 GEN
Solar/Wind Harmer
0.664
315652AC1-086 GEN
Solar/Wind Harmer
8.34
316123AC1-075 GEN
Solar/Wind Harmer
0.797
970165AG2-112 GEN
Solar/Wind Harmer
0.701
970163AG2-111 GEN
Solar/Wind Harmer
0.669
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.381
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.985
315833AF1-017_GEN
Solar/Wind Harmer
1.293
316349AD2-085 GEN
Solar/Wind Harmer
0.606
316311AC2-079 GEN
Solar/Wind Harmer
3.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.367
315733AD1-074 GEN2
Solar/Wind Harmer
1.367
315735AD1-075 GEN1
Solar/Wind Harmer
0.684
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.588
970535AG2-341 GEN
50/50
2.034
971489AH1-241 GEN
Solar/Wind Harmer
27.358
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.65
970301AG2-198 GEN
Solar/Wind Harmer
12.49
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.631
963191AG1-168 GEN
Solar/Wind Harmer
2.179
971741AH1-377 GEN
Solar/Wind Harmer
26.175
316034AC1-036 C
Solar/Wind Harmer
0.356
970323AG2-213 GEN
Solar/Wind Harmer
9.582
971775AH1-396 GEN
Solar/Wind Harmer
1.365
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.349
3143526WINTERP
Solar/Wind Harmer
-0.065
962561AG1-105 GEN
Solar/Wind Harmer
6.845
939181AE1-148 GEN
Solar/Wind Harmer
6.741
964791AG1-342 GEN
Solar/Wind Harmer
2.511
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.545
970933AG2-581 GEN
Solar/Wind Harmer
9.023
316181AB2-040 GEN
Solar/Wind Harmer
1.184
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.923
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.055
3145783HORNRTN
Solar/Wind Harmer
0.958
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.68
315816AE2-034 GEN
Solar/Wind Harmer
0.544
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3130156CHOWAN
Solar/Wind Harmer
-0.007
3151921BEARGRDN G2
50/50
4.287
3144293JTRSVLE
50/50
0.699
970221AG2-151 GEN
Solar/Wind Harmer
28.817
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.807
316258AE1-075 C
Solar/Wind Harmer
0.726
316405AF2-144 C
Solar/Wind Harmer
0.766
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.288
970909AG2-566 GEN
Solar/Wind Harmer
2.372
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.388
963181AG1-167 GEN
Solar/Wind Harmer
2.179
959311AF2-222 GEN
Solar/Wind Harmer
20.632
970257AG2-171 GEN
Solar/Wind Harmer
7.186
315785AD2-033 C
Solar/Wind Harmer
4.155
964241AG1-285 GEN
Solar/Wind Harmer
12.598
316131AB2-060 GEN
Solar/Wind Harmer
1.595
958131AF2-107 GEN
Solar/Wind Harmer
4.893
316478AD1-087 GEN
Solar/Wind Harmer
1.01
316486AD2-202 GEN
Solar/Wind Harmer
0.296
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.904
3150861SPRUNCD
Adder
0.382
971683AH1-343 GEN
Solar/Wind Harmer
3.805
966621AG1-532 GEN
Solar/Wind Harmer
0.177
313506AB2-031 GEN
Solar/Wind Harmer
0.682
970917AG2-570 GEN
Solar/Wind Harmer
19.61
316365GEN2_N
Solar/Wind Harmer
0.518
3156081AA2-088 GEN
Solar/Wind Harmer
2.417
3146263WOODLND
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.773
961681AG1-008 GEN
Solar/Wind Harmer
5.773
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316210AC1-098 GEN
Solar/Wind Harmer
1.142
3146173TUNIS
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
316140AB2-099
Solar/Wind Harmer
0.048
962331AG1-082 GEN
Solar/Wind Harmer
0.898
316317KELFORD C
Solar/Wind Harmer
0.338
3145823KELFORD
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.89
316327AA2-057 GEN
Solar/Wind Harmer
0.714
315813AE1-149 C
Solar/Wind Harmer
4.418
970659AG2-427 GEN
Solar/Wind Harmer
0.658
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
0.4
3145273HOLLAND
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
1.304
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315737AD1-076 GEN
Solar/Wind Harmer
1.285
971157AH1-035 GEN
Solar/Wind Harmer
0.844
970129AG2-093 GEN
Solar/Wind Harmer
3.791
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.016
316426AA2-053 GEN
Solar/Wind Harmer
0.809
3144356SAPONY
Solar/Wind Harmer
0.264
316274AC1-208 GEN
Solar/Wind Harmer
0.799
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.235
315742AE1-103 GEN
Solar/Wind Harmer
0.736
970657AG2-426 GEN
Solar/Wind Harmer
2.172
970657AG2-426 GEN
Solar/Wind Harmer
0.454
316222AC1-221 GEN
Solar/Wind Harmer
0.698
316065AD1-022 GEN
Solar/Wind Harmer
3.4
942751AE2-291 GEN
Solar/Wind Harmer
4.316
316263AC1-034 GEN
Solar/Wind Harmer
3.148
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.622
316033AB2-134 GEN
Solar/Wind Harmer
2.144
315697AD1-025 GEN
Solar/Wind Harmer
1.345
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.2
316433W1029_GEN2
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316018AA1-139 ULT2
Solar/Wind Harmer
0.563
316017AA1-139 ULT1
Solar/Wind Harmer
0.531
316339AD2-160 GEN
Solar/Wind Harmer
0.443
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.691
3142956BIRDNECK
Solar/Wind Harmer
0.351
316316AC1-027 C
Solar/Wind Harmer
0.201
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.082
3150701DARBY 4
Adder
4.072
3150681DARBY 2
Adder
4.067
3150671DARBY 1
Adder
4.063
966001AG1-469 GEN
Solar/Wind Helper
0.202
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.725
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.787
961601AG1-000A GEN
Solar/Wind Harmer
2.655
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.827
316320Y1-086
Solar/Wind Harmer
0.387
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.801
961611AG1-000B GEN
Solar/Wind Harmer
1.383
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.404
3151221GRAVEL6
Adder
4.219
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
315616AA1-038_C
Solar/Wind Helper
0.514
3151931BEARGRDN S1
50/50
5.533
3151911BEARGRDN G1
50/50
4.287
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
18.19
972003AH1-546 GEN
Solar/Wind Harmer
24.898
971377AH1-170 GEN
Solar/Wind Harmer
5.763
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.282
316322AB2-045
Solar/Wind Harmer
1.394
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.86
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
963171AG1-166 GEN
Solar/Wind Harmer
2.905
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
18.606
3143226MDLTHAN
Solar/Wind Harmer
-0.015
962491AG1-098 GEN
Solar/Wind Harmer
9.894
315693AD1-088 GEN
Solar/Wind Harmer
7.12
316237AB2-079_GEN
Solar/Wind Harmer
0.427
3143526WINTERP
Solar/Wind Harmer
-0.065
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.362
315687AD1-152 GEN
Solar/Wind Harmer
1.282
971065AG2-659 GEN
Solar/Wind Harmer
5.251
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.904
971795AH1-408 GEN
Solar/Wind Harmer
7.449
3150851SPRUNCC
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.906
960081AF2-299 GEN
Solar/Wind Harmer
0.983
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
970919AG2-571 GEN
Solar/Wind Harmer
2.482
970087AG2-069 GEN
Solar/Wind Harmer
7.326
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.518
940641AE2-051 GEN
Solar/Wind Harmer
6.973
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.551
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
316212AC1-099_GEN
Solar/Wind Harmer
0.635
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.08
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
5.319
970659AG2-427 GEN
Solar/Wind Harmer
3.71
316381AD1-082 GEN
Solar/Wind Harmer
0.639
315722AD1-056 GEN
Solar/Wind Harmer
0.728
970661AG2-428 GEN
Solar/Wind Harmer
7.356
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
970129AG2-093 GEN
Solar/Wind Harmer
1.536
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316458AB2-190 GEN2
Solar/Wind Harmer
0.68
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.303
316359AB2-059 GEN
Solar/Wind Harmer
0.905
316049AB1-081 GEN
Solar/Wind Harmer
0.725
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.951
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
316174AB2-169 GEN
Solar/Wind Harmer
1.029
315800Z1-036_GEN1
Solar/Wind Harmer
1.645
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
971647AH1-324 GEN
Solar/Wind Harmer
3.305
316246AF1-032 C
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.913
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.242
316388AE2-253 GEN
Solar/Wind Harmer
0.443
316375AC2-012 GEN
Solar/Wind Harmer
2.263
3150981CHESPKA
Adder
0.727
3151171GRAVELC
Adder
0.617
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.88
3147666LOUISA
Solar/Wind Helper
0.508
944591AF1-124 GEN
Solar/Wind Harmer
8.419
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.645
316369SG1_INVT
Solar/Wind Harmer
1.188
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.757
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.895
316321Z2-027
Solar/Wind Harmer
0.178
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
316305AF2-043 C
Solar/Wind Harmer
0.199
313526AB2-022
Solar/Wind Harmer
0.178
316005AA1-067
Solar/Wind Harmer
0.133
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.865
3146406KITTY HAWK
Solar/Wind Harmer
0.005
319010AE1-072 C
Solar/Wind Harmer
1.33
957871AF2-081 GEN
Solar/Wind Harmer
3.284
3152611GOSPORTB
Adder
0.742
3152621GOSPORTC
Adder
0.629
3152601GOSPORTA
Adder
0.581
3151081ELIZAR1
Adder
5.335
3151091ELIZAR2
Adder
5.243
972265AH1-717 GEN
Adder
4.506
3151201GRAVEL4
Adder
4.224
3151191GRAVEL3
Adder
4.17
3151211GRAVEL5
Adder
4.17
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.055
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.782
MECLTFEXP_MEC->PJM
CLTF
0.452
SIGELTFEXP_SIGE->PJM
CLTF
0.012
CPLELTFEXP_CPLE->PJM
CLTF
3.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.641
LAGNLTFEXP_LAGN->PJM
CLTF
1.764
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.761
TVALTFEXP_TVA->PJM
CLTF
0.87
NYPJM->LTFIMP_NY
CLTF
0.577
LGEELTFEXP_LGEE->PJM
CLTF
0.104
WECLTFEXP_WEC->PJM
CLTF
0.046

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:175.31 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1455.08
MW Contribution:2.03
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.588
3151931BEARGRDN S1
50/50
5.533
3151911BEARGRDN G1
50/50
4.287
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
18.19
972003AH1-546 GEN
Solar/Wind Harmer
24.898
971377AH1-170 GEN
Solar/Wind Harmer
5.763
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.282
316322AB2-045
Solar/Wind Harmer
1.394
970535AG2-341 GEN
50/50
2.034
971489AH1-241 GEN
Solar/Wind Harmer
27.358
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.65
970301AG2-198 GEN
Solar/Wind Harmer
12.49
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.631
963191AG1-168 GEN
Solar/Wind Harmer
2.179
971741AH1-377 GEN
Solar/Wind Harmer
26.175
316034AC1-036 C
Solar/Wind Harmer
0.356
970323AG2-213 GEN
Solar/Wind Harmer
9.582
971775AH1-396 GEN
Solar/Wind Harmer
1.365
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.349
3143526WINTERP
Solar/Wind Harmer
-0.065
962561AG1-105 GEN
Solar/Wind Harmer
6.845
939181AE1-148 GEN
Solar/Wind Harmer
6.741
964791AG1-342 GEN
Solar/Wind Harmer
2.511
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.545
970933AG2-581 GEN
Solar/Wind Harmer
9.023
316181AB2-040 GEN
Solar/Wind Harmer
1.184
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.923
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.055
3145783HORNRTN
Solar/Wind Harmer
0.958
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.016
316426AA2-053 GEN
Solar/Wind Harmer
0.809
3144356SAPONY
Solar/Wind Harmer
0.264
316274AC1-208 GEN
Solar/Wind Harmer
0.799
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3151921BEARGRDN G2
50/50
4.287
3144293JTRSVLE
50/50
0.699
970221AG2-151 GEN
Solar/Wind Harmer
28.817
3146776BUCKING
Solar/Wind Harmer
-0.015
972205AH1-687 GEN
50/50
20.91
316303AF2-085
50/50
2.425
971447AH1-217 GEN
Solar/Wind Harmer
15.108
971845AH1-439 GEN
Solar/Wind Harmer
21.634
970285AG2-188 GEN
Solar/Wind Harmer
34.428
270494AE1-108_GEN
Solar/Wind Harmer
9.407
315657AE1-056 GEN
Solar/Wind Harmer
9.233
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
16.612
970681AG2-440 GEN
Solar/Wind Harmer
13.29
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.737
316239AB2-077_GEN
Solar/Wind Harmer
0.427
316238AB2-078_GEN
Solar/Wind Harmer
0.427
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316118AC1-105 GEN
Solar/Wind Harmer
0.741
970831AG2-522 GEN
Solar/Wind Harmer
5.054
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
946281AF1-292 GEN
Solar/Wind Harmer
0.196
971967AH1-528 GEN
Solar/Wind Harmer
16.369
316087AB2-174 GEN
Solar/Wind Harmer
1.222
970865AG2-541 GEN
Solar/Wind Harmer
3.392
3137643SOCKMAN
Solar/Wind Harmer
-0.033
970673AG2-436 GEN
Solar/Wind Harmer
16.777
970673AG2-436 GEN
Solar/Wind Harmer
8.495
315607AA1-063A GEN
Solar/Wind Harmer
0.8
941031AE2-094 GEN
Solar/Wind Harmer
14.78
944011AF1-069 GEN
Solar/Wind Harmer
4.631
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.884
970581AG2-369 GEN
Solar/Wind Harmer
4.201
315814AE2-033 C
Solar/Wind Harmer
7.048
316315AB2-025 C
Solar/Wind Harmer
0.204
965291AG1-394 GEN
Solar/Wind Harmer
0.664
315652AC1-086 GEN
Solar/Wind Harmer
8.34
316123AC1-075 GEN
Solar/Wind Harmer
0.797
970165AG2-112 GEN
Solar/Wind Harmer
0.701
970163AG2-111 GEN
Solar/Wind Harmer
0.669
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.381
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.985
315833AF1-017_GEN
Solar/Wind Harmer
1.293
316349AD2-085 GEN
Solar/Wind Harmer
0.606
316311AC2-079 GEN
Solar/Wind Harmer
3.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.367
315733AD1-074 GEN2
Solar/Wind Harmer
1.367
315735AD1-075 GEN1
Solar/Wind Harmer
0.684
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.68
315816AE2-034 GEN
Solar/Wind Harmer
0.544
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.645
316369SG1_INVT
Solar/Wind Harmer
1.188
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.757
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.895
316321Z2-027
Solar/Wind Harmer
0.178
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
316305AF2-043 C
Solar/Wind Harmer
0.199
313526AB2-022
Solar/Wind Harmer
0.178
316005AA1-067
Solar/Wind Harmer
0.133
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.865
3146406KITTY HAWK
Solar/Wind Harmer
0.005
319010AE1-072 C
Solar/Wind Harmer
1.33
957871AF2-081 GEN
Solar/Wind Harmer
3.284
3152611GOSPORTB
Adder
0.742
3152621GOSPORTC
Adder
0.629
3152601GOSPORTA
Adder
0.581
3151081ELIZAR1
Adder
5.335
3151091ELIZAR2
Adder
5.243
972265AH1-717 GEN
Adder
4.506
3151201GRAVEL4
Adder
4.224
3151191GRAVEL3
Adder
4.17
3151211GRAVEL5
Adder
4.17
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.807
316258AE1-075 C
Solar/Wind Harmer
0.726
316405AF2-144 C
Solar/Wind Harmer
0.766
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.288
970909AG2-566 GEN
Solar/Wind Harmer
2.372
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.388
963181AG1-167 GEN
Solar/Wind Harmer
2.179
959311AF2-222 GEN
Solar/Wind Harmer
20.632
970257AG2-171 GEN
Solar/Wind Harmer
7.186
315785AD2-033 C
Solar/Wind Harmer
4.155
964241AG1-285 GEN
Solar/Wind Harmer
12.598
316131AB2-060 GEN
Solar/Wind Harmer
1.595
958131AF2-107 GEN
Solar/Wind Harmer
4.893
316478AD1-087 GEN
Solar/Wind Harmer
1.01
316486AD2-202 GEN
Solar/Wind Harmer
0.296
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.904
3150861SPRUNCD
Adder
0.382
971683AH1-343 GEN
Solar/Wind Harmer
3.805
966621AG1-532 GEN
Solar/Wind Harmer
0.177
313506AB2-031 GEN
Solar/Wind Harmer
0.682
970917AG2-570 GEN
Solar/Wind Harmer
19.61
316365GEN2_N
Solar/Wind Harmer
0.518
3156081AA2-088 GEN
Solar/Wind Harmer
2.417
3146263WOODLND
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.773
961681AG1-008 GEN
Solar/Wind Harmer
5.773
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316210AC1-098 GEN
Solar/Wind Harmer
1.142
3146173TUNIS
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
316140AB2-099
Solar/Wind Harmer
0.048
962331AG1-082 GEN
Solar/Wind Harmer
0.898
316317KELFORD C
Solar/Wind Harmer
0.338
3145823KELFORD
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.89
316327AA2-057 GEN
Solar/Wind Harmer
0.714
315813AE1-149 C
Solar/Wind Harmer
4.418
970659AG2-427 GEN
Solar/Wind Harmer
0.658
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
0.4
3145273HOLLAND
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
1.304
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315737AD1-076 GEN
Solar/Wind Harmer
1.285
971157AH1-035 GEN
Solar/Wind Harmer
0.844
970129AG2-093 GEN
Solar/Wind Harmer
3.791
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.725
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.787
961601AG1-000A GEN
Solar/Wind Harmer
2.655
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.235
315742AE1-103 GEN
Solar/Wind Harmer
0.736
970657AG2-426 GEN
Solar/Wind Harmer
2.172
970657AG2-426 GEN
Solar/Wind Harmer
0.454
316222AC1-221 GEN
Solar/Wind Harmer
0.698
316065AD1-022 GEN
Solar/Wind Harmer
3.4
942751AE2-291 GEN
Solar/Wind Harmer
4.316
316263AC1-034 GEN
Solar/Wind Harmer
3.148
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.622
316033AB2-134 GEN
Solar/Wind Harmer
2.144
315697AD1-025 GEN
Solar/Wind Harmer
1.345
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.2
316433W1029_GEN2
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316018AA1-139 ULT2
Solar/Wind Harmer
0.563
316017AA1-139 ULT1
Solar/Wind Harmer
0.531
316339AD2-160 GEN
Solar/Wind Harmer
0.443
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.691
3142956BIRDNECK
Solar/Wind Harmer
0.351
316316AC1-027 C
Solar/Wind Harmer
0.201
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.082
3150701DARBY 4
Adder
4.072
3150681DARBY 2
Adder
4.067
3150671DARBY 1
Adder
4.063
966001AG1-469 GEN
Solar/Wind Helper
0.202
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.827
316320Y1-086
Solar/Wind Harmer
0.387
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.801
961611AG1-000B GEN
Solar/Wind Harmer
1.383
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.404
3151221GRAVEL6
Adder
4.219
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
315616AA1-038_C
Solar/Wind Helper
0.514
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.86
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
963171AG1-166 GEN
Solar/Wind Harmer
2.905
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
18.606
3143226MDLTHAN
Solar/Wind Harmer
-0.015
962491AG1-098 GEN
Solar/Wind Harmer
9.894
315693AD1-088 GEN
Solar/Wind Harmer
7.12
316237AB2-079_GEN
Solar/Wind Harmer
0.427
3143526WINTERP
Solar/Wind Harmer
-0.065
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.362
315687AD1-152 GEN
Solar/Wind Harmer
1.282
971065AG2-659 GEN
Solar/Wind Harmer
5.251
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.904
971795AH1-408 GEN
Solar/Wind Harmer
7.449
3150851SPRUNCC
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.906
960081AF2-299 GEN
Solar/Wind Harmer
0.983
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
970919AG2-571 GEN
Solar/Wind Harmer
2.482
970087AG2-069 GEN
Solar/Wind Harmer
7.326
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.518
940641AE2-051 GEN
Solar/Wind Harmer
6.973
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.551
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
316212AC1-099_GEN
Solar/Wind Harmer
0.635
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.08
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
5.319
970659AG2-427 GEN
Solar/Wind Harmer
3.71
316381AD1-082 GEN
Solar/Wind Harmer
0.639
315722AD1-056 GEN
Solar/Wind Harmer
0.728
970661AG2-428 GEN
Solar/Wind Harmer
7.356
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
970129AG2-093 GEN
Solar/Wind Harmer
1.536
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316458AB2-190 GEN2
Solar/Wind Harmer
0.68
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.303
316359AB2-059 GEN
Solar/Wind Harmer
0.905
316049AB1-081 GEN
Solar/Wind Harmer
0.725
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.951
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
316174AB2-169 GEN
Solar/Wind Harmer
1.029
315800Z1-036_GEN1
Solar/Wind Harmer
1.645
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
971647AH1-324 GEN
Solar/Wind Harmer
3.305
316246AF1-032 C
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.913
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.242
316388AE2-253 GEN
Solar/Wind Harmer
0.443
316375AC2-012 GEN
Solar/Wind Harmer
2.263
3150981CHESPKA
Adder
0.727
3151171GRAVELC
Adder
0.617
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.88
3147666LOUISA
Solar/Wind Helper
0.508
944591AF1-124 GEN
Solar/Wind Harmer
8.419
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.055
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.782
MECLTFEXP_MEC->PJM
CLTF
0.452
SIGELTFEXP_SIGE->PJM
CLTF
0.012
CPLELTFEXP_CPLE->PJM
CLTF
3.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.641
LAGNLTFEXP_LAGN->PJM
CLTF
1.764
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.761
TVALTFEXP_TVA->PJM
CLTF
0.87
NYPJM->LTFIMP_NY
CLTF
0.577
LGEELTFEXP_LGEE->PJM
CLTF
0.104
WECLTFEXP_WEC->PJM
CLTF
0.046

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:162.3 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1101.51
MW Contribution:2.05
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
7.21
3151911BEARGRDN G1
50/50
5.587
3144293JTRSVLE
50/50
0.823
3151601KERR 3
50/50
0.202
3151581KERR 1
50/50
0.072
3151531CLOVER1
50/50
2.069
3147043LAWRENC
50/50
0.777
970937AG2-583 GEN
Solar/Wind Harmer
36.866
316336AC2-165 C
Solar/Wind Harmer
0.024
972003AH1-546 GEN
Solar/Wind Harmer
24.522
971377AH1-170 GEN
Solar/Wind Harmer
5.701
3147623JAMES R
Solar/Wind Harmer
1.238
316322AB2-045
Solar/Wind Harmer
0.004
3146776BUCKING
Solar/Wind Harmer
0.188
3146926FARMVIL
Solar/Wind Harmer
0.218
963171AG1-166 GEN
Solar/Wind Harmer
1.299
971563AH1-280 GEN
Solar/Wind Harmer
2.599
970685AG2-442 GEN
Solar/Wind Harmer
16.367
962491AG1-098 GEN
Solar/Wind Harmer
7.651
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
6.098
970401AG2-262 GEN
Solar/Wind Harmer
0.618
957481AF2-042 GEN
Solar/Wind Harmer
24.997
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.611
316129AC1-054 GEN
Solar/Wind Harmer
0.309
316003AC1-222 GEN
Solar/Wind Harmer
0.002
971795AH1-408 GEN
Solar/Wind Harmer
4.899
962751AG1-124 GEN
Solar/Wind Harmer
3.147
960081AF2-299 GEN
Solar/Wind Harmer
0.55
3144293JTRSVLE
50/50
0.823
3144293JTRSVLE
50/50
0.693
970535AG2-341 GEN
50/50
2.047
3152661PLYWOOD A
50/50
0.202
971489AH1-241 GEN
Solar/Wind Harmer
28.504
3146776BUCKING
Solar/Wind Harmer
1.881
3146776BUCKING
Solar/Wind Harmer
0.152
315821AE2-092 GEN
Solar/Wind Harmer
0.02
970301AG2-198 GEN
Solar/Wind Harmer
11.214
3147133PAMPLIN
Solar/Wind Harmer
0.26
3147133PAMPLIN
Solar/Wind Harmer
0.208
958211AF2-115 GEN
Solar/Wind Harmer
2.924
963191AG1-168 GEN
Solar/Wind Harmer
0.975
971741AH1-377 GEN
Solar/Wind Harmer
22.982
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.246
971775AH1-396 GEN
Solar/Wind Harmer
0.309
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
5.277
964791AG1-342 GEN
Solar/Wind Harmer
2.024
3146843MT LREL
Solar/Wind Harmer
0.105
3146843MT LREL
Solar/Wind Harmer
0.105
939181AE1-148 GEN
Solar/Wind Harmer
5.007
970099AG2-077 GEN
Solar/Wind Harmer
9.999
970933AG2-581 GEN
Solar/Wind Harmer
5.154
942751AE2-291 GEN
Solar/Wind Harmer
3.374
966001AG1-469 GEN
Solar/Wind Helper
0.159
3151921BEARGRDN G2
50/50
5.587
3144293JTRSVLE
50/50
0.823
3151591KERR 2
50/50
0.202
970413AG2-270 GEN
50/50
9.029
966251AG1-494 GEN
50/50
1.716
970221AG2-151 GEN
Solar/Wind Harmer
28.504
3146776BUCKING
Solar/Wind Harmer
0.169
3146926FARMVIL
Solar/Wind Harmer
0.218
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
970909AG2-566 GEN
Solar/Wind Harmer
2.804
3147133PAMPLIN
Solar/Wind Harmer
0.818
971193AH1-056 GEN
Solar/Wind Harmer
15.872
963181AG1-167 GEN
Solar/Wind Harmer
0.975
959311AF2-222 GEN
Solar/Wind Harmer
17.841
970257AG2-171 GEN
Solar/Wind Harmer
6.184
315785AD2-033 C
Solar/Wind Harmer
1.488
958131AF2-107 GEN
Solar/Wind Harmer
4.835
964241AG1-285 GEN
Solar/Wind Harmer
10.382
316131AB2-060 GEN
Solar/Wind Harmer
0.438
316478AD1-087 GEN
Solar/Wind Harmer
0.337
316486AD2-202 GEN
Solar/Wind Harmer
0.099
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.582
3147043LAWRENC
Solar/Wind Harmer
0.049
971683AH1-343 GEN
Solar/Wind Harmer
2.828
3132273ORANGE
Solar/Wind Helper
0.023
972205AH1-687 GEN
50/50
27.249
3151611KERR 4
50/50
0.202
3151621KERR 5
50/50
0.202
3151631KERR 6
50/50
0.202
3151641KERR 7
50/50
0.202
3151541CLOVER2
50/50
2.059
971447AH1-217 GEN
Solar/Wind Harmer
15.037
971845AH1-439 GEN
Solar/Wind Harmer
20.916
970285AG2-188 GEN
Solar/Wind Harmer
35.131
270494AE1-108_GEN
Solar/Wind Harmer
5.032
315657AE1-056 GEN
Solar/Wind Harmer
8.99
946301AF1-294 GEN
Solar/Wind Harmer
4.808
961791AG1-021 GEN
Solar/Wind Harmer
2.339
970683AG2-441 GEN
Solar/Wind Harmer
14.613
970681AG2-440 GEN
Solar/Wind Harmer
11.691
3144303KENBRDG
Solar/Wind Harmer
0.154
971443AH1-215 GEN
Solar/Wind Harmer
3.209
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.244
3147173SINAI
Solar/Wind Harmer
0.084
3147243WELCO
Solar/Wind Harmer
0.052
970831AG2-522 GEN
Solar/Wind Harmer
3.381
970865AG2-541 GEN
Solar/Wind Harmer
2.545
316123AC1-075 GEN
Solar/Wind Harmer
0.091
970165AG2-112 GEN
Solar/Wind Harmer
0.539
970163AG2-111 GEN
Solar/Wind Harmer
0.514
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.084
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.539
MECLTFEXP_MEC->PJM
CLTF
0.508
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CPLELTFEXP_CPLE->PJM
CLTF
2.979
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.201
LAGNLTFEXP_LAGN->PJM
CLTF
1.554
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.128
TVALTFEXP_TVA->PJM
CLTF
0.776
NYPJM->LTFIMP_NY
CLTF
0.525
LGEELTFEXP_LGEE->PJM
CLTF
0.153
WECLTFEXP_WEC->PJM
CLTF
0.071

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P4-2: 202712_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 202712_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:153.09 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1270.66
MW Contribution:2.05
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.823
3144293JTRSVLE
50/50
0.693
970535AG2-341 GEN
50/50
2.047
971489AH1-241 GEN
Solar/Wind Harmer
35.629
3146776BUCKING
Solar/Wind Harmer
-0.21
3146776BUCKING
Solar/Wind Harmer
-0.017
315821AE2-092 GEN
Solar/Wind Harmer
7.77
970301AG2-198 GEN
Solar/Wind Harmer
14.765
3147133PAMPLIN
Solar/Wind Harmer
-0.029
3147133PAMPLIN
Solar/Wind Harmer
-0.023
958211AF2-115 GEN
Solar/Wind Harmer
4.277
963191AG1-168 GEN
Solar/Wind Harmer
2.566
971741AH1-377 GEN
Solar/Wind Harmer
30.26
316034AC1-036 C
Solar/Wind Harmer
0.404
970323AG2-213 GEN
Solar/Wind Harmer
10.857
971775AH1-396 GEN
Solar/Wind Harmer
1.546
313527AB2-043 GEN
Solar/Wind Harmer
2.466
962561AG1-105 GEN
Solar/Wind Harmer
6.948
964791AG1-342 GEN
Solar/Wind Harmer
2.529
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
3151921BEARGRDN G2
50/50
5.587
3144293JTRSVLE
50/50
0.823
970221AG2-151 GEN
Solar/Wind Harmer
37.53
3146776BUCKING
Solar/Wind Harmer
-0.019
3146926FARMVIL
Solar/Wind Harmer
-0.024
942461AE2-259 GEN
Solar/Wind Harmer
5.218
970909AG2-566 GEN
Solar/Wind Harmer
2.804
3147133PAMPLIN
Solar/Wind Harmer
-0.092
971193AH1-056 GEN
Solar/Wind Harmer
18.305
963181AG1-167 GEN
Solar/Wind Harmer
2.566
3151931BEARGRDN S1
50/50
7.21
3151911BEARGRDN G1
50/50
5.587
3144293JTRSVLE
50/50
0.823
970937AG2-583 GEN
Solar/Wind Harmer
48.541
316336AC2-165 C
Solar/Wind Harmer
11.736
972003AH1-546 GEN
Solar/Wind Harmer
32.342
971377AH1-170 GEN
Solar/Wind Harmer
7.506
3147623JAMES R
Solar/Wind Harmer
0.929
316322AB2-045
Solar/Wind Harmer
1.778
3146776BUCKING
Solar/Wind Harmer
-0.021
3146926FARMVIL
Solar/Wind Harmer
-0.024
963171AG1-166 GEN
Solar/Wind Harmer
3.422
971563AH1-280 GEN
Solar/Wind Harmer
3.422
970685AG2-442 GEN
Solar/Wind Harmer
21.55
962491AG1-098 GEN
Solar/Wind Harmer
10.074
316237AB2-079_GEN
Solar/Wind Harmer
0.446
315693AD1-088 GEN
Solar/Wind Harmer
7.137
970401AG2-262 GEN
Solar/Wind Harmer
0.773
957481AF2-042 GEN
Solar/Wind Harmer
32.913
315687AD1-152 GEN
Solar/Wind Harmer
1.189
971065AG2-659 GEN
Solar/Wind Harmer
4.755
316129AC1-054 GEN
Solar/Wind Harmer
0.808
3147043LAWRENC
Adder
0.732
316003AC1-222 GEN
Solar/Wind Harmer
0.879
971795AH1-408 GEN
Solar/Wind Harmer
6.192
962751AG1-124 GEN
Solar/Wind Harmer
4.595
960081AF2-299 GEN
Solar/Wind Harmer
0.724
972205AH1-687 GEN
50/50
27.249
971447AH1-217 GEN
Solar/Wind Harmer
19.799
971845AH1-439 GEN
Solar/Wind Harmer
27.54
970285AG2-188 GEN
Solar/Wind Harmer
43.657
270494AE1-108_GEN
Solar/Wind Harmer
12.267
315657AE1-056 GEN
Solar/Wind Harmer
10.983
946301AF1-294 GEN
Solar/Wind Harmer
7.014
961791AG1-021 GEN
Solar/Wind Harmer
3.422
970683AG2-441 GEN
Solar/Wind Harmer
19.241
970681AG2-440 GEN
Solar/Wind Harmer
15.393
3144303KENBRDG
Solar/Wind Harmer
-0.017
971443AH1-215 GEN
Solar/Wind Harmer
4.225
316239AB2-077_GEN
Solar/Wind Harmer
0.446
316238AB2-078_GEN
Solar/Wind Harmer
0.446
316118AC1-105 GEN
Solar/Wind Harmer
0.73
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
970831AG2-522 GEN
Solar/Wind Harmer
4.452
970865AG2-541 GEN
Solar/Wind Harmer
3.351
316123AC1-075 GEN
Solar/Wind Harmer
0.806
970165AG2-112 GEN
Solar/Wind Harmer
0.709
970163AG2-111 GEN
Solar/Wind Harmer
0.677
946281AF1-292 GEN
Solar/Wind Harmer
0.144
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
939181AE1-148 GEN
Solar/Wind Harmer
6.592
970099AG2-077 GEN
Solar/Wind Harmer
13.165
970933AG2-581 GEN
Solar/Wind Harmer
6.786
942751AE2-291 GEN
Solar/Wind Harmer
4.443
966001AG1-469 GEN
Solar/Wind Helper
0.159
959311AF2-222 GEN
Solar/Wind Harmer
23.538
970257AG2-171 GEN
Solar/Wind Harmer
8.143
315785AD2-033 C
Solar/Wind Harmer
4.66
958131AF2-107 GEN
Solar/Wind Harmer
6.437
964241AG1-285 GEN
Solar/Wind Harmer
13.669
316131AB2-060 GEN
Solar/Wind Harmer
1.687
316478AD1-087 GEN
Solar/Wind Harmer
0.939
316486AD2-202 GEN
Solar/Wind Harmer
0.275
316248AF1-058 C
Solar/Wind Harmer
0.284
960061AF2-297 GEN
Solar/Wind Harmer
4.717
3147043LAWRENC
Solar/Wind Harmer
-0.005
971683AH1-343 GEN
Solar/Wind Harmer
3.724
966621AG1-532 GEN
Solar/Wind Harmer
0.131
3132273ORANGE
Solar/Wind Helper
0.023
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.084
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.539
MECLTFEXP_MEC->PJM
CLTF
0.508
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CPLELTFEXP_CPLE->PJM
CLTF
2.979
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.201
LAGNLTFEXP_LAGN->PJM
CLTF
1.554
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.128
TVALTFEXP_TVA->PJM
CLTF
0.776
NYPJM->LTFIMP_NY
CLTF
0.525
LGEELTFEXP_LGEE->PJM
CLTF
0.153
WECLTFEXP_WEC->PJM
CLTF
0.071

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.58 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:736.92
MW Contribution:1.77
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.083
3151541CLOVER2
50/50
1.876
3151611KERR 4
50/50
0.18
3151621KERR 5
50/50
0.18
3151631KERR 6
50/50
0.18
3151641KERR 7
50/50
0.18
316303AF2-085
50/50
1.546
3151281ROARAP4
50/50
0.07
3151281ROARAP4
50/50
0.066
971447AH1-217 GEN
Solar/Wind Harmer
11.004
971845AH1-439 GEN
Solar/Wind Harmer
15.632
970285AG2-188 GEN
Solar/Wind Harmer
26.316
270494AE1-108_GEN
Solar/Wind Harmer
3.693
315657AE1-056 GEN
Solar/Wind Harmer
6.997
946301AF1-294 GEN
Solar/Wind Harmer
3.764
961791AG1-021 GEN
Solar/Wind Harmer
1.831
970683AG2-441 GEN
Solar/Wind Harmer
11.558
970681AG2-440 GEN
Solar/Wind Harmer
9.247
3144303KENBRDG
Solar/Wind Harmer
0.124
971443AH1-215 GEN
Solar/Wind Harmer
2.576
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.212
970831AG2-522 GEN
Solar/Wind Harmer
3.201
3147173SINAI
Solar/Wind Harmer
0.074
3147243WELCO
Solar/Wind Harmer
0.046
316233AE1-074 FULL
Solar/Wind Harmer
0.058
971281AH1-106 GEN
Solar/Wind Harmer
1.006
971283AH1-107 GEN
Solar/Wind Harmer
1.006
970865AG2-541 GEN
Solar/Wind Harmer
2.17
316087AB2-174 GEN
Solar/Wind Harmer
0.002
971967AH1-528 GEN
Solar/Wind Harmer
9.597
3137643SOCKMAN
Solar/Wind Harmer
0.235
3138266HYDRAULIC
Solar/Wind Helper
0.021
3151921BEARGRDN G2
50/50
4.118
3144293JTRSVLE
50/50
0.644
970413AG2-270 GEN
50/50
8.224
3151591KERR 2
50/50
0.18
966251AG1-494 GEN
50/50
1.173
3151261ROARAP2
50/50
0.07
970221AG2-151 GEN
Solar/Wind Harmer
21.013
3146776BUCKING
Solar/Wind Harmer
0.126
3146926FARMVIL
Solar/Wind Harmer
0.165
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.144
316258AE1-075 C
Solar/Wind Harmer
0.173
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.463
970909AG2-566 GEN
Solar/Wind Harmer
2.192
3147133PAMPLIN
Solar/Wind Harmer
0.637
971193AH1-056 GEN
Solar/Wind Harmer
12.353
963181AG1-167 GEN
Solar/Wind Harmer
0.763
959311AF2-222 GEN
Solar/Wind Harmer
14.242
970257AG2-171 GEN
Solar/Wind Harmer
4.957
315785AD2-033 C
Solar/Wind Harmer
1.2
964241AG1-285 GEN
Solar/Wind Harmer
8.548
958131AF2-107 GEN
Solar/Wind Harmer
3.44
316131AB2-060 GEN
Solar/Wind Harmer
0.366
316478AD1-087 GEN
Solar/Wind Harmer
0.307
316486AD2-202 GEN
Solar/Wind Harmer
0.09
3147043LAWRENC
Solar/Wind Harmer
0.047
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.155
971683AH1-343 GEN
Solar/Wind Harmer
2.44
313506AB2-031 GEN
Solar/Wind Harmer
0.186
316499AE2-029_GEN
Solar/Wind Helper
0.505
3148013FISHERV
Solar/Wind Helper
0.133
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.54
3151931BEARGRDN S1
50/50
5.314
3151911BEARGRDN G1
50/50
4.118
3144293JTRSVLE
50/50
0.644
3151531CLOVER1
50/50
1.885
3151601KERR 3
50/50
0.18
3151581KERR 1
50/50
0.064
970119AG2-088 GEN
50/50
11.599
3147043LAWRENC
50/50
0.746
3151261ROARAP2
50/50
0.072
972003AH1-546 GEN
Solar/Wind Harmer
18.108
971377AH1-170 GEN
Solar/Wind Harmer
4.203
3147623JAMES R
Solar/Wind Harmer
0.913
970937AG2-583 GEN
Solar/Wind Harmer
22.204
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.14
3146926FARMVIL
Solar/Wind Harmer
0.165
316336AC2-165 C
Solar/Wind Harmer
0.01
3143336POWHATN
Solar/Wind Harmer
4.074
963171AG1-166 GEN
Solar/Wind Harmer
1.017
971563AH1-280 GEN
Solar/Wind Harmer
2.035
970685AG2-442 GEN
Solar/Wind Harmer
12.945
962491AG1-098 GEN
Solar/Wind Harmer
6.577
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
5.296
970401AG2-262 GEN
Solar/Wind Harmer
0.531
957481AF2-042 GEN
Solar/Wind Harmer
23.244
3143226MDLTHAN
Solar/Wind Harmer
0.087
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.352
316129AC1-054 GEN
Solar/Wind Harmer
0.289
971795AH1-408 GEN
Solar/Wind Harmer
4.849
3143526WINTERP
Solar/Wind Harmer
0.377
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.595
3145783HORNRTN
Solar/Wind Harmer
0.057
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.752
3144293JTRSVLE
50/50
0.644
3144293JTRSVLE
50/50
0.543
970535AG2-341 GEN
50/50
1.768
3152661PLYWOOD A
50/50
0.177
971489AH1-241 GEN
Solar/Wind Harmer
21.013
3146776BUCKING
Solar/Wind Harmer
1.404
3146776BUCKING
Solar/Wind Harmer
0.114
315821AE2-092 GEN
Solar/Wind Harmer
0.014
970301AG2-198 GEN
Solar/Wind Harmer
8.767
3147133PAMPLIN
Solar/Wind Harmer
0.203
3147133PAMPLIN
Solar/Wind Harmer
0.162
958211AF2-115 GEN
Solar/Wind Harmer
2.289
963191AG1-168 GEN
Solar/Wind Harmer
0.763
971741AH1-377 GEN
Solar/Wind Harmer
18.217
316034AC1-036 C
Solar/Wind Harmer
0.011
970323AG2-213 GEN
Solar/Wind Harmer
6.61
971775AH1-396 GEN
Solar/Wind Harmer
0.248
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
4.515
939181AE1-148 GEN
Solar/Wind Harmer
4.407
964791AG1-342 GEN
Solar/Wind Harmer
1.738
3146843MT LREL
Solar/Wind Harmer
0.09
3146843MT LREL
Solar/Wind Harmer
0.09
970099AG2-077 GEN
Solar/Wind Harmer
9.298
971223AH1-071 GEN
Solar/Wind Harmer
0.928
3143526WINTERP
Solar/Wind Harmer
0.377
970933AG2-581 GEN
Solar/Wind Harmer
5.476
316181AB2-040 GEN
Solar/Wind Harmer
0.087
3145593CAROLNA
Solar/Wind Harmer
0.058
3145593CAROLNA
Solar/Wind Harmer
0.058
966811AG1-552 GEN
Solar/Wind Harmer
0.627
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.01
3145783HORNRTN
Solar/Wind Harmer
0.808
3145783HORNRTN
Solar/Wind Harmer
0.253
3145783HORNRTN
Solar/Wind Harmer
0.101
966001AG1-469 GEN
Solar/Wind Helper
0.19
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.08
3148013FISHERV
Solar/Wind Helper
0.077
3148463FAIRFLD
Solar/Wind Helper
0.119
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.673
MECLTFEXP_MEC->PJM
CLTF
0.138
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CPLELTFEXP_CPLE->PJM
CLTF
2.992
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.238
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.029
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.072
LAGNLTFEXP_LAGN->PJM
CLTF
1.122
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.815
TVALTFEXP_TVA->PJM
CLTF
0.547
NYPJM->LTFIMP_NY
CLTF
0.391

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:198.54 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:1313.88
MW Contribution:2.11
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.706
3144293JTRSVLE
50/50
0.594
970535AG2-341 GEN
50/50
2.11
3152661PLYWOOD A
50/50
0.217
3151041BRUNSWICKG3
50/50
1.059
972187AH1-678 GEN
50/50
2.43
3151921BEARGRDN G2
50/50
4.238
3144293JTRSVLE
50/50
0.706
970413AG2-270 GEN
50/50
10.245
3151591KERR 2
50/50
0.22
3151031BRUNSWICKG2
50/50
1.059
3151261ROARAP2
50/50
0.095
3150861SPRUNCD
50/50
0.364
966251AG1-494 GEN
50/50
1.288
970221AG2-151 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
0.132
3146926FARMVIL
Solar/Wind Harmer
0.176
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.159
316258AE1-075 C
Solar/Wind Harmer
0.19
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.801
970909AG2-566 GEN
Solar/Wind Harmer
2.396
3147133PAMPLIN
Solar/Wind Harmer
0.693
971193AH1-056 GEN
Solar/Wind Harmer
13.448
963181AG1-167 GEN
Solar/Wind Harmer
0.835
959311AF2-222 GEN
Solar/Wind Harmer
15.884
970257AG2-171 GEN
Solar/Wind Harmer
5.55
315785AD2-033 C
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
9.804
316131AB2-060 GEN
Solar/Wind Harmer
0.426
958131AF2-107 GEN
Solar/Wind Harmer
3.651
316478AD1-087 GEN
Solar/Wind Harmer
0.382
316486AD2-202 GEN
Solar/Wind Harmer
0.112
3147043LAWRENC
Solar/Wind Harmer
0.059
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.912
971683AH1-343 GEN
Solar/Wind Harmer
3.032
313506AB2-031 GEN
Solar/Wind Harmer
0.248
972205AH1-687 GEN
50/50
20.67
316303AF2-085
50/50
2.055
3151541CLOVER2
50/50
2.336
3151611KERR 4
50/50
0.22
3151621KERR 5
50/50
0.22
3151631KERR 6
50/50
0.22
3151641KERR 7
50/50
0.22
963041AG1-153 GEN
50/50
2.144
315244AE2-183_ST
50/50
2.284
3151281ROARAP4
50/50
0.094
3151281ROARAP4
50/50
0.088
971285AH1-108 GEN
50/50
0.596
315779AE2-040
50/50
1.013
971447AH1-217 GEN
Solar/Wind Harmer
11.337
971845AH1-439 GEN
Solar/Wind Harmer
16.33
970285AG2-188 GEN
Solar/Wind Harmer
27.559
270494AE1-108_GEN
Solar/Wind Harmer
3.817
315657AE1-056 GEN
Solar/Wind Harmer
7.617
946301AF1-294 GEN
Solar/Wind Harmer
4.122
961791AG1-021 GEN
Solar/Wind Harmer
2.005
970683AG2-441 GEN
Solar/Wind Harmer
12.78
970681AG2-440 GEN
Solar/Wind Harmer
10.224
3144303KENBRDG
Solar/Wind Harmer
0.139
971443AH1-215 GEN
Solar/Wind Harmer
2.888
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.258
316233AE1-074 FULL
Solar/Wind Harmer
0.078
971281AH1-106 GEN
Solar/Wind Harmer
1.344
971283AH1-107 GEN
Solar/Wind Harmer
1.344
970831AG2-522 GEN
Solar/Wind Harmer
4.036
3147173SINAI
Solar/Wind Harmer
0.092
3147243WELCO
Solar/Wind Harmer
0.057
971967AH1-528 GEN
Solar/Wind Harmer
13.711
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
16.986
970673AG2-436 GEN
Solar/Wind Harmer
11.324
941031AE2-094 GEN
Solar/Wind Harmer
14.544
944011AF1-069 GEN
Solar/Wind Harmer
4.752
3137643SOCKMAN
Solar/Wind Harmer
0.315
970865AG2-541 GEN
Solar/Wind Harmer
2.702
970085AG2-068 GEN
Solar/Wind Harmer
4.124
970581AG2-369 GEN
Solar/Wind Harmer
3.547
315607AA1-063A GEN
Solar/Wind Harmer
0.154
3146043SEABORD
Solar/Wind Harmer
0.075
315814AE2-033 C
Solar/Wind Harmer
5.747
316315AB2-025 C
Solar/Wind Harmer
0.059
965291AG1-394 GEN
Solar/Wind Harmer
0.317
3151931BEARGRDN S1
50/50
5.469
3151911BEARGRDN G1
50/50
4.238
3144293JTRSVLE
50/50
0.706
970119AG2-088 GEN
50/50
15.414
3151531CLOVER1
50/50
2.348
3151601KERR 3
50/50
0.22
3151581KERR 1
50/50
0.079
3147043LAWRENC
50/50
0.939
3151051BRUNSWICKS1
50/50
2.197
3151021BRUNSWICKG1
50/50
1.059
971451AH1-221 GEN
50/50
3.216
315243AE2-183_GT3
50/50
1.321
3151261ROARAP2
50/50
0.097
3150851SPRUNCC
50/50
0.364
972003AH1-546 GEN
Solar/Wind Harmer
18.676
971377AH1-170 GEN
Solar/Wind Harmer
4.327
3147623JAMES R
Solar/Wind Harmer
0.94
970937AG2-583 GEN
Solar/Wind Harmer
23.217
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.147
3146926FARMVIL
Solar/Wind Harmer
0.176
316336AC2-165 C
Solar/Wind Harmer
0.011
3143336POWHATN
Solar/Wind Harmer
4.472
963171AG1-166 GEN
Solar/Wind Harmer
1.114
971563AH1-280 GEN
Solar/Wind Harmer
2.228
970685AG2-442 GEN
Solar/Wind Harmer
14.313
962491AG1-098 GEN
Solar/Wind Harmer
7.815
315693AD1-088 GEN
Solar/Wind Harmer
6.344
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Harmer
0.116
957481AF2-042 GEN
Solar/Wind Harmer
29.295
970401AG2-262 GEN
Solar/Wind Harmer
0.638
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
4.184
3143526WINTERP
Solar/Wind Harmer
0.504
316129AC1-054 GEN
Solar/Wind Harmer
0.363
971795AH1-408 GEN
Solar/Wind Harmer
6.199
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.793
970919AG2-571 GEN
Solar/Wind Harmer
2.76
970087AG2-069 GEN
Solar/Wind Harmer
6.187
3145783HORNRTN
Solar/Wind Harmer
0.076
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
5.984
316023GEN1_S
Solar/Wind Harmer
0.164
939411AE1-173 GEN
Solar/Wind Harmer
30.681
316011AB1-132 GEN
Solar/Wind Harmer
1.286
962571AG1-106 GEN
Solar/Wind Harmer
1.007
3146263WOODLND
Solar/Wind Harmer
0.071
3145893MURPHYS
Solar/Wind Harmer
0.281
3145893MURPHYS
Solar/Wind Harmer
0.312
3145796HORNRTN
Solar/Wind Harmer
0.23
3145796HORNRTN
Solar/Wind Harmer
0.07
316212AC1-099_GEN
Solar/Wind Harmer
0.359
3146173TUNIS
Solar/Wind Harmer
0.069
3145823KELFORD
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
315722AD1-056 GEN
Solar/Wind Harmer
0.422
3146233WITAKRS
Solar/Wind Harmer
0.263
3146206CASHIE
Solar/Wind Harmer
0.065
971547AH1-271 GEN
Solar/Wind Harmer
1.396
970659AG2-427 GEN
Solar/Wind Harmer
3.146
316381AD1-082 GEN
Solar/Wind Harmer
0.068
970661AG2-428 GEN
Solar/Wind Harmer
6.453
3145663CRESWEL
Solar/Wind Harmer
0.181
971163AH1-040 GEN
Solar/Wind Harmer
5.167
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.052
316359AB2-059 GEN
Solar/Wind Harmer
0.231
316049AB1-081 GEN
Solar/Wind Harmer
0.368
3142053HEARTS
Solar/Wind Harmer
0.113
316093AE2-104_GEN
Solar/Wind Harmer
1.081
3130156CHOWAN
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3142543TWELFTH
Solar/Wind Harmer
0.006
3146516WINFALL
Solar/Wind Harmer
0.207
3146516WINFALL
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.283
316246AF1-032 C
Solar/Wind Harmer
0.029
3146293MARTNCO
Solar/Wind Harmer
0.059
316494AC1-189 GEN
Solar/Wind Harmer
0.214
3146456SLIGO L269
Solar/Wind Harmer
0.063
316388AE2-253 GEN
Solar/Wind Harmer
0.198
944591AF1-124 GEN
Solar/Wind Harmer
14.289
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
315671AE2-027_GEN
Solar/Wind Harmer
4.043
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
1.077
3145336SMITFLD
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
0.644
961611AG1-000B GEN
Solar/Wind Harmer
3.17
971647AH1-324 GEN
Solar/Wind Harmer
2.576
3143096IRON208
Adder
0.252
971069AG2-661 GEN
Solar/Wind Harmer
1.071
316458AB2-190 GEN2
Solar/Wind Harmer
0.323
970129AG2-093 GEN
Solar/Wind Harmer
1.71
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.903
3147666LOUISA
Solar/Wind Helper
0.521
970917AG2-570 GEN
Solar/Wind Harmer
6.901
316365GEN2_N
Solar/Wind Harmer
0.164
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
0.117
3145893MURPHYS
Solar/Wind Harmer
0.07
957521AF2-046 GEN
Solar/Wind Harmer
5.202
961681AG1-008 GEN
Solar/Wind Harmer
5.202
3145796HORNRTN
Solar/Wind Harmer
0.279
3145796HORNRTN
Solar/Wind Harmer
0.07
316210AC1-098 GEN
Solar/Wind Harmer
0.644
3146173TUNIS
Solar/Wind Harmer
0.069
316463AE2-346 GEN
Solar/Wind Harmer
0.059
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.732
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.069
316327AA2-057 GEN
Solar/Wind Harmer
0.102
315724AD1-057 GEN
Solar/Wind Harmer
0.25
3145273HOLLAND
Solar/Wind Harmer
0.05
3156021HOLLOMANSOL
Solar/Wind Harmer
0.301
3146233WITAKRS
Solar/Wind Harmer
0.331
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3146206CASHIE
Solar/Wind Harmer
0.065
315813AE1-149 C
Solar/Wind Harmer
3.482
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316283AC2-100 C
Solar/Wind Harmer
0.127
315839AE2-212 C
Solar/Wind Harmer
0.001
315737AD1-076 GEN
Solar/Wind Harmer
0.835
970661AG2-428 GEN
Solar/Wind Harmer
1.373
971157AH1-035 GEN
Solar/Wind Harmer
0.778
315614AA2-178 GEN
Solar/Wind Harmer
0.37
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.129
3146376EDENTON
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
4.548
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
315242AE2-183_GT2
50/50
1.321
315241AE2-183_GT1
50/50
1.313
972185AH1-677 GEN
50/50
4.762
970533AG2-339 GEN
50/50
7.019
970531AG2-338 GEN
50/50
2.808
971489AH1-241 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
1.465
3146776BUCKING
Solar/Wind Harmer
0.119
315821AE2-092 GEN
Solar/Wind Harmer
0.014
970301AG2-198 GEN
Solar/Wind Harmer
9.583
3147133PAMPLIN
Solar/Wind Harmer
0.221
3147133PAMPLIN
Solar/Wind Harmer
0.176
958211AF2-115 GEN
Solar/Wind Harmer
2.506
963191AG1-168 GEN
Solar/Wind Harmer
0.835
971741AH1-377 GEN
Solar/Wind Harmer
20.177
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.401
971775AH1-396 GEN
Solar/Wind Harmer
0.278
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971223AH1-071 GEN
Solar/Wind Harmer
1.233
316435W1029_GEN3
Solar/Wind Harmer
0
965281AG1-393 GEN
Solar/Wind Harmer
0.68
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
316320Y1-086
Solar/Wind Harmer
0
3145933PARMELE
Solar/Wind Harmer
0.063
966801AG1-551 GEN
Solar/Wind Harmer
0.74
3146456SLIGO L269
Solar/Wind Harmer
0.063
971153AH1-033 GEN
Solar/Wind Harmer
0.732
944581AF1-123 GEN
Solar/Wind Harmer
14.239
944601AF1-125 GEN
Solar/Wind Harmer
14.019
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3151101ELIZAR3
Adder
5.847
3144873MCLAUGH
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.009
315773AC2-141 GEN
Solar/Wind Harmer
2.27
3145336SMITFLD
Solar/Wind Harmer
0.025
3151221GRAVEL6
Adder
4.403
3151171GRAVELC
Adder
0.847
961611AG1-000B GEN
Solar/Wind Harmer
1.612
3143096IRON208
Adder
0.252
3143096IRON208
Adder
0.247
315778AD1-151 GEN
Solar/Wind Harmer
4.818
970129AG2-093 GEN
Solar/Wind Harmer
3.634
970133AG2-095 GEN
Solar/Wind Harmer
0.576
316499AE2-029_GEN
Solar/Wind Helper
0.501
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.3
3148013FISHERV
Solar/Wind Helper
0.129
315616AA1-038_C
Solar/Wind Helper
0.524
962561AG1-105 GEN
Solar/Wind Harmer
5.397
939181AE1-148 GEN
Solar/Wind Harmer
5.333
970099AG2-077 GEN
Solar/Wind Harmer
11.718
964791AG1-342 GEN
Solar/Wind Harmer
2.089
3146843MT LREL
Solar/Wind Harmer
0.109
3146843MT LREL
Solar/Wind Harmer
0.109
3143526WINTERP
Solar/Wind Harmer
0.504
970933AG2-581 GEN
Solar/Wind Harmer
7.465
316181AB2-040 GEN
Solar/Wind Harmer
0.116
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.078
966811AG1-552 GEN
Solar/Wind Harmer
0.843
3145593CAROLNA
Solar/Wind Harmer
0.097
3145783HORNRTN
Solar/Wind Harmer
1.361
3145783HORNRTN
Solar/Wind Harmer
1.089
3145783HORNRTN
Solar/Wind Harmer
0.34
3145783HORNRTN
Solar/Wind Harmer
0.136
316426AA2-053 GEN
Solar/Wind Harmer
0.256
3144356SAPONY
Solar/Wind Harmer
0.607
316274AC1-208 GEN
Solar/Wind Harmer
0.366
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.042
3145893MURPHYS
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
0.126
3145796HORNRTN
Solar/Wind Harmer
0.209
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
315742AE1-103 GEN
Solar/Wind Harmer
0.001
316222AC1-221 GEN
Solar/Wind Harmer
0.272
316065AD1-022 GEN
Solar/Wind Harmer
3.004
970657AG2-426 GEN
Solar/Wind Harmer
2.275
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
2.446
3146376EDENTON
Solar/Wind Harmer
0.286
3146376EDENTON
Solar/Wind Harmer
0.286
961601AG1-000A GEN
Solar/Wind Harmer
1.137
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3145493TOT1
Solar/Wind Harmer
0.148
3145453TOT5
Solar/Wind Harmer
0.089
3145603CNETO
Solar/Wind Harmer
0.059
3146386ELIZ CT
Solar/Wind Harmer
0.064
3145933PARMELE
Solar/Wind Harmer
0.127
3145933PARMELE
Solar/Wind Harmer
0.063
3130086AYDLETT
Solar/Wind Harmer
0.253
3137176SLIGO L2192
Solar/Wind Harmer
0.252
3146456SLIGO L269
Solar/Wind Harmer
1.121
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.035
316339AD2-160 GEN
Solar/Wind Harmer
0.103
3145506HICKORY
Solar/Wind Harmer
0.253
3145506HICKORY
Solar/Wind Harmer
0.152
3145506HICKORY
Solar/Wind Harmer
0.038
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.061
942751AE2-291 GEN
Solar/Wind Harmer
3.43
316240AF1-291 C
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.012
3150991CHESPKB
Adder
0.659
3150991CHESPKB
Adder
0.643
944641AF1-129 GEN
Adder
29.755
316236AE1-162_GEN
Solar/Wind Harmer
0
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.068
966001AG1-469 GEN
Solar/Wind Helper
0.206
315652AC1-086 GEN
Solar/Wind Harmer
7.782
3145893MURPHYS
Solar/Wind Harmer
0.19
3145893MURPHYS
Solar/Wind Harmer
0.07
3145796HORNRTN
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.028
3146033SCOT NK
Solar/Wind Harmer
0.276
316123AC1-075 GEN
Solar/Wind Harmer
0.094
970165AG2-112 GEN
Solar/Wind Harmer
0.558
970163AG2-111 GEN
Solar/Wind Harmer
0.532
3145513AHOSKIE
Solar/Wind Harmer
0.143
3145513AHOSKIE
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3143316POE
Solar/Wind Harmer
0.269
316319Z2-044 C
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.065
970601AG2-382 GEN
Solar/Wind Harmer
2.444
315732AD1-074 GEN1
Solar/Wind Harmer
0.373
315733AD1-074 GEN2
Solar/Wind Harmer
0.373
315735AD1-075 GEN1
Solar/Wind Harmer
0.187
3130546PLYMOUTH
Solar/Wind Harmer
0.065
315816AE2-034 GEN
Solar/Wind Harmer
0.277
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.044
316311AC2-079 GEN
Solar/Wind Harmer
1.853
315835AF2-110_GEN
Solar/Wind Harmer
0.441
3130156CHOWAN
Solar/Wind Harmer
0.064
3130156CHOWAN
Solar/Wind Harmer
0.064
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
316321Z2-027
Solar/Wind Harmer
0.012
3145176PASQUOTANK
Solar/Wind Harmer
0.039
3146396TANGLEW
Solar/Wind Harmer
0.175
316420AA1-050 GEN
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.034
316305AF2-043 C
Solar/Wind Harmer
0.001
957861AF2-080 GEN
Solar/Wind Harmer
2.737
3146406KITTY HAWK
Solar/Wind Harmer
0.008
319010AE1-072 C
Solar/Wind Harmer
0.319
957871AF2-081 GEN
Solar/Wind Harmer
3.153
316005AA1-067
Solar/Wind Harmer
0.068
3145746EVERETS
Solar/Wind Harmer
0.252
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
970181AG2-120 GEN
Solar/Wind Harmer
0.787
3151081ELIZAR1
Adder
5.773
3151091ELIZAR2
Adder
5.672
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.68
3152601GOSPORTA
Adder
0.628
971445AH1-216 GEN
Solar/Wind Harmer
4.321
972265AH1-717 GEN
Adder
4.702
3151201GRAVEL4
Adder
4.408
3151191GRAVEL3
Adder
4.352
3151211GRAVEL5
Adder
4.352
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.323
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.077
3148013FISHERV
Solar/Wind Helper
0.074
3148463FAIRFLD
Solar/Wind Helper
0.116
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.131
MECLTFEXP_MEC->PJM
CLTF
0.546
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CPLELTFEXP_CPLE->PJM
CLTF
4.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.705
LAGNLTFEXP_LAGN->PJM
CLTF
1.972
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.458
TVALTFEXP_TVA->PJM
CLTF
0.973
NYPJM->LTFIMP_NY
CLTF
0.616
LGEELTFEXP_LGEE->PJM
CLTF
0.137
WECLTFEXP_WEC->PJM
CLTF
0.063

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:185.18 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1498.1
MW Contribution:2.11
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.704
970221AG2-151 GEN
Solar/Wind Harmer
28.432
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.296
316313AB2-026
Solar/Wind Harmer
0.761
316258AE1-075 C
Solar/Wind Harmer
0.685
316405AF2-144 C
Solar/Wind Harmer
0.723
3143336POWHATN
Solar/Wind Harmer
2.847
970909AG2-566 GEN
Solar/Wind Harmer
2.392
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.485
963181AG1-167 GEN
Solar/Wind Harmer
2.197
959311AF2-222 GEN
Solar/Wind Harmer
20.924
970257AG2-171 GEN
Solar/Wind Harmer
7.297
315785AD2-033 C
Solar/Wind Harmer
4.227
964241AG1-285 GEN
Solar/Wind Harmer
12.89
316131AB2-060 GEN
Solar/Wind Harmer
1.639
958131AF2-107 GEN
Solar/Wind Harmer
4.847
316478AD1-087 GEN
Solar/Wind Harmer
1.065
3144293JTRSVLE
50/50
0.704
3144293JTRSVLE
50/50
0.593
970535AG2-341 GEN
50/50
2.107
971489AH1-241 GEN
Solar/Wind Harmer
26.992
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.547
970301AG2-198 GEN
Solar/Wind Harmer
12.599
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
963191AG1-168 GEN
Solar/Wind Harmer
2.197
971741AH1-377 GEN
Solar/Wind Harmer
26.527
316034AC1-036 C
Solar/Wind Harmer
0.362
970323AG2-213 GEN
Solar/Wind Harmer
9.73
971775AH1-396 GEN
Solar/Wind Harmer
1.386
313527AB2-043 GEN
Solar/Wind Harmer
2.416
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.096
939181AE1-148 GEN
Solar/Wind Harmer
7.013
970099AG2-077 GEN
Solar/Wind Harmer
15.412
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
972205AH1-687 GEN
50/50
20.633
316303AF2-085
50/50
2.054
971447AH1-217 GEN
Solar/Wind Harmer
14.897
971845AH1-439 GEN
Solar/Wind Harmer
21.465
970285AG2-188 GEN
Solar/Wind Harmer
34.19
270494AE1-108_GEN
Solar/Wind Harmer
9.286
315657AE1-056 GEN
Solar/Wind Harmer
9.291
946301AF1-294 GEN
Solar/Wind Harmer
6.004
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
16.801
970681AG2-440 GEN
Solar/Wind Harmer
13.441
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.796
316239AB2-077_GEN
Solar/Wind Harmer
0.439
316238AB2-078_GEN
Solar/Wind Harmer
0.439
316118AC1-105 GEN
Solar/Wind Harmer
0.773
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.769
971283AH1-107 GEN
Solar/Wind Harmer
1.769
970831AG2-522 GEN
Solar/Wind Harmer
5.308
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.09
946281AF1-292 GEN
Solar/Wind Harmer
0.208
316087AB2-174 GEN
Solar/Wind Harmer
1.297
970673AG2-436 GEN
Solar/Wind Harmer
18.787
970673AG2-436 GEN
Solar/Wind Harmer
9.512
941031AE2-094 GEN
Solar/Wind Harmer
16.63
944011AF1-069 GEN
Solar/Wind Harmer
5.211
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970865AG2-541 GEN
Solar/Wind Harmer
3.55
970085AG2-068 GEN
Solar/Wind Harmer
5.427
970581AG2-369 GEN
Solar/Wind Harmer
4.667
315607AA1-063A GEN
Solar/Wind Harmer
0.852
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.6
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.71
315652AC1-086 GEN
Solar/Wind Harmer
8.941
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
316123AC1-075 GEN
Solar/Wind Harmer
0.832
970165AG2-112 GEN
Solar/Wind Harmer
0.733
970163AG2-111 GEN
Solar/Wind Harmer
0.699
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3151931BEARGRDN S1
50/50
5.46
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.704
970119AG2-088 GEN
50/50
15.406
972003AH1-546 GEN
Solar/Wind Harmer
24.588
971377AH1-170 GEN
Solar/Wind Harmer
5.686
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.518
316322AB2-045
Solar/Wind Harmer
1.382
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.598
3143336POWHATN
Solar/Wind Harmer
3.349
316486AD2-202 GEN
Solar/Wind Harmer
0.312
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.31
960061AF2-297 GEN
Solar/Wind Harmer
5.143
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.986
313506AB2-031 GEN
Solar/Wind Harmer
0.724
970917AG2-570 GEN
Solar/Wind Harmer
21.795
3150861SPRUNCD
Adder
0.344
316365GEN2_N
Solar/Wind Harmer
0.555
3156081AA2-088 GEN
Solar/Wind Harmer
2.586
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.185
961681AG1-008 GEN
Solar/Wind Harmer
6.185
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146173TUNIS
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.125
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.963
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.821
972187AH1-678 GEN
Adder
2.289
316181AB2-040 GEN
Solar/Wind Harmer
1.257
972185AH1-677 GEN
Adder
4.486
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.855
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.79
316222AC1-221 GEN
Solar/Wind Harmer
0.745
316065AD1-022 GEN
Solar/Wind Harmer
3.665
970657AG2-426 GEN
Solar/Wind Harmer
2.282
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
3.387
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.822
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.78
966001AG1-469 GEN
Solar/Wind Helper
0.216
963171AG1-166 GEN
Solar/Wind Harmer
2.929
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
18.817
962491AG1-098 GEN
Solar/Wind Harmer
10.277
315693AD1-088 GEN
Solar/Wind Harmer
7.416
316237AB2-079_GEN
Solar/Wind Harmer
0.439
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.531
970401AG2-262 GEN
Solar/Wind Harmer
0.797
315687AD1-152 GEN
Solar/Wind Harmer
1.353
971065AG2-659 GEN
Solar/Wind Harmer
5.503
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.948
971795AH1-408 GEN
Solar/Wind Harmer
7.828
316003AC1-222 GEN
Solar/Wind Harmer
0.95
960081AF2-299 GEN
Solar/Wind Harmer
1.043
970919AG2-571 GEN
Solar/Wind Harmer
2.759
970087AG2-069 GEN
Solar/Wind Harmer
8.141
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
940641AE2-051 GEN
Solar/Wind Harmer
7.878
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.555
939411AE1-173 GEN
Solar/Wind Harmer
40.398
316011AB1-132 GEN
Solar/Wind Harmer
1.663
962571AG1-106 GEN
Solar/Wind Harmer
1.142
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.68
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.782
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.838
970659AG2-427 GEN
Solar/Wind Harmer
3.885
316381AD1-082 GEN
Solar/Wind Harmer
0.67
970661AG2-428 GEN
Solar/Wind Harmer
7.748
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.803
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.974
316049AB1-081 GEN
Solar/Wind Harmer
0.78
316093AE2-104_GEN
Solar/Wind Harmer
2.1
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
315800Z1-036_GEN1
Solar/Wind Harmer
1.779
316174AB2-169 GEN
Solar/Wind Harmer
1.109
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
316246AF1-032 C
Solar/Wind Harmer
0.144
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
944591AF1-124 GEN
Solar/Wind Harmer
32.454
3150981CHESPKA
Adder
0.786
3151171GRAVELC
Adder
0.645
3143096IRON208
Adder
0.253
944631AF1-128 GEN
Adder
26.841
316192AB2-158 GEN
Solar/Wind Helper
1.013
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316319Z2-044 C
Solar/Wind Harmer
0.41
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.217
315732AD1-074 GEN1
Solar/Wind Harmer
1.475
315733AD1-074 GEN2
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.737
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316349AD2-085 GEN
Solar/Wind Harmer
0.645
315816AE2-034 GEN
Solar/Wind Harmer
0.587
316311AC2-079 GEN
Solar/Wind Harmer
3.659
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.779
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
316321Z2-027
Solar/Wind Harmer
0.193
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.193
316420AA1-050 GEN
Solar/Wind Harmer
0.816
316305AF2-043 C
Solar/Wind Harmer
0.215
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
3151081ELIZAR1
Adder
5.776
3151091ELIZAR2
Adder
5.675
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.681
3152601GOSPORTA
Adder
0.628
972265AH1-717 GEN
Adder
4.706
3151201GRAVEL4
Adder
4.411
3151191GRAVEL3
Adder
4.355
3151211GRAVEL5
Adder
4.355
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
316317KELFORD C
Solar/Wind Harmer
0.363
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.766
315724AD1-057 GEN
Solar/Wind Harmer
0.43
3145273HOLLAND
Solar/Wind Harmer
-0.006
3156021HOLLOMANSOL
Solar/Wind Harmer
1.002
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.587
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
1.186
315839AE2-212 C
Solar/Wind Harmer
0.22
970661AG2-428 GEN
Solar/Wind Harmer
1.373
315737AD1-076 GEN
Solar/Wind Harmer
1.386
316283AC2-100 C
Solar/Wind Harmer
0.686
971157AH1-035 GEN
Solar/Wind Harmer
0.911
315614AA2-178 GEN
Solar/Wind Harmer
0.783
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.858
3146516WINFALL
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.896
316435W1029_GEN3
Solar/Wind Harmer
1.299
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.419
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.891
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151101ELIZAR3
Adder
5.849
3151221GRAVEL6
Adder
4.406
3151171GRAVELC
Adder
0.848
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.338
3148013FISHERV
Solar/Wind Helper
0.13
315616AA1-038_C
Solar/Wind Helper
0.528
944581AF1-123 GEN
Solar/Wind Harmer
20.452
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.573
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.107
MECLTFEXP_MEC->PJM
CLTF
0.537
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CPLELTFEXP_CPLE->PJM
CLTF
4.206
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.627
LAGNLTFEXP_LAGN->PJM
CLTF
1.959
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.437
TVALTFEXP_TVA->PJM
CLTF
0.967
NYPJM->LTFIMP_NY
CLTF
0.612
LGEELTFEXP_LGEE->PJM
CLTF
0.133
WECLTFEXP_WEC->PJM
CLTF
0.061

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:185.18 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1498.08
MW Contribution:2.11
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.46
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.704
970119AG2-088 GEN
50/50
15.406
972003AH1-546 GEN
Solar/Wind Harmer
24.587
971377AH1-170 GEN
Solar/Wind Harmer
5.686
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.517
316322AB2-045
Solar/Wind Harmer
1.382
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.597
3143336POWHATN
Solar/Wind Harmer
3.349
963171AG1-166 GEN
Solar/Wind Harmer
2.929
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
18.817
962491AG1-098 GEN
Solar/Wind Harmer
10.277
315693AD1-088 GEN
Solar/Wind Harmer
7.416
316237AB2-079_GEN
Solar/Wind Harmer
0.439
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.531
970401AG2-262 GEN
Solar/Wind Harmer
0.797
315687AD1-152 GEN
Solar/Wind Harmer
1.353
971065AG2-659 GEN
Solar/Wind Harmer
5.503
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.948
971795AH1-408 GEN
Solar/Wind Harmer
7.828
316003AC1-222 GEN
Solar/Wind Harmer
0.95
960081AF2-299 GEN
Solar/Wind Harmer
1.043
970919AG2-571 GEN
Solar/Wind Harmer
2.759
970087AG2-069 GEN
Solar/Wind Harmer
8.141
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
940641AE2-051 GEN
Solar/Wind Harmer
7.878
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.555
939411AE1-173 GEN
Solar/Wind Harmer
40.398
316011AB1-132 GEN
Solar/Wind Harmer
1.663
962571AG1-106 GEN
Solar/Wind Harmer
1.142
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.68
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.782
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.838
970659AG2-427 GEN
Solar/Wind Harmer
3.885
316381AD1-082 GEN
Solar/Wind Harmer
0.67
970661AG2-428 GEN
Solar/Wind Harmer
7.748
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.803
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.974
316049AB1-081 GEN
Solar/Wind Harmer
0.78
316093AE2-104_GEN
Solar/Wind Harmer
2.1
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
315800Z1-036_GEN1
Solar/Wind Harmer
1.779
316174AB2-169 GEN
Solar/Wind Harmer
1.109
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
316246AF1-032 C
Solar/Wind Harmer
0.144
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
944591AF1-124 GEN
Solar/Wind Harmer
32.454
3150981CHESPKA
Adder
0.786
3151171GRAVELC
Adder
0.645
3143096IRON208
Adder
0.253
944631AF1-128 GEN
Adder
26.842
316192AB2-158 GEN
Solar/Wind Helper
1.014
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.704
970221AG2-151 GEN
Solar/Wind Harmer
28.431
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.296
316313AB2-026
Solar/Wind Harmer
0.761
316258AE1-075 C
Solar/Wind Harmer
0.685
316405AF2-144 C
Solar/Wind Harmer
0.723
3143336POWHATN
Solar/Wind Harmer
2.847
970909AG2-566 GEN
Solar/Wind Harmer
2.392
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.484
963181AG1-167 GEN
Solar/Wind Harmer
2.197
959311AF2-222 GEN
Solar/Wind Harmer
20.924
970257AG2-171 GEN
Solar/Wind Harmer
7.297
315785AD2-033 C
Solar/Wind Harmer
4.227
964241AG1-285 GEN
Solar/Wind Harmer
12.89
316131AB2-060 GEN
Solar/Wind Harmer
1.639
958131AF2-107 GEN
Solar/Wind Harmer
4.847
316478AD1-087 GEN
Solar/Wind Harmer
1.065
316486AD2-202 GEN
Solar/Wind Harmer
0.312
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.31
960061AF2-297 GEN
Solar/Wind Harmer
5.143
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.986
313506AB2-031 GEN
Solar/Wind Harmer
0.724
970917AG2-570 GEN
Solar/Wind Harmer
21.795
3150861SPRUNCD
Adder
0.344
316365GEN2_N
Solar/Wind Harmer
0.555
3156081AA2-088 GEN
Solar/Wind Harmer
2.585
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.185
961681AG1-008 GEN
Solar/Wind Harmer
6.185
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146173TUNIS
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.125
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.963
316317KELFORD C
Solar/Wind Harmer
0.363
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.766
315724AD1-057 GEN
Solar/Wind Harmer
0.43
3145273HOLLAND
Solar/Wind Harmer
-0.006
3156021HOLLOMANSOL
Solar/Wind Harmer
1.002
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.587
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
1.186
315839AE2-212 C
Solar/Wind Harmer
0.22
970661AG2-428 GEN
Solar/Wind Harmer
1.373
315737AD1-076 GEN
Solar/Wind Harmer
1.386
316283AC2-100 C
Solar/Wind Harmer
0.686
971157AH1-035 GEN
Solar/Wind Harmer
0.911
315614AA2-178 GEN
Solar/Wind Harmer
0.783
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.858
3146516WINFALL
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.896
316435W1029_GEN3
Solar/Wind Harmer
1.299
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.419
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.891
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151101ELIZAR3
Adder
5.85
3151221GRAVEL6
Adder
4.406
3151171GRAVELC
Adder
0.848
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.339
3148013FISHERV
Solar/Wind Helper
0.13
315616AA1-038_C
Solar/Wind Helper
0.528
944581AF1-123 GEN
Solar/Wind Harmer
20.452
3144293JTRSVLE
50/50
0.704
3144293JTRSVLE
50/50
0.593
970535AG2-341 GEN
50/50
2.107
971489AH1-241 GEN
Solar/Wind Harmer
26.992
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.547
970301AG2-198 GEN
Solar/Wind Harmer
12.599
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
963191AG1-168 GEN
Solar/Wind Harmer
2.197
971741AH1-377 GEN
Solar/Wind Harmer
26.527
316034AC1-036 C
Solar/Wind Harmer
0.361
970323AG2-213 GEN
Solar/Wind Harmer
9.729
971775AH1-396 GEN
Solar/Wind Harmer
1.386
313527AB2-043 GEN
Solar/Wind Harmer
2.416
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.096
939181AE1-148 GEN
Solar/Wind Harmer
7.013
970099AG2-077 GEN
Solar/Wind Harmer
15.412
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.821
972187AH1-678 GEN
Adder
2.289
316181AB2-040 GEN
Solar/Wind Harmer
1.257
972185AH1-677 GEN
Adder
4.486
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.855
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.79
316222AC1-221 GEN
Solar/Wind Harmer
0.745
316065AD1-022 GEN
Solar/Wind Harmer
3.665
970657AG2-426 GEN
Solar/Wind Harmer
2.282
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
3.387
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.822
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.781
966001AG1-469 GEN
Solar/Wind Helper
0.216
972205AH1-687 GEN
50/50
20.633
316303AF2-085
50/50
2.054
971447AH1-217 GEN
Solar/Wind Harmer
14.896
971845AH1-439 GEN
Solar/Wind Harmer
21.465
970285AG2-188 GEN
Solar/Wind Harmer
34.19
270494AE1-108_GEN
Solar/Wind Harmer
9.286
315657AE1-056 GEN
Solar/Wind Harmer
9.291
946301AF1-294 GEN
Solar/Wind Harmer
6.004
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
16.8
970681AG2-440 GEN
Solar/Wind Harmer
13.44
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.796
316239AB2-077_GEN
Solar/Wind Harmer
0.439
316238AB2-078_GEN
Solar/Wind Harmer
0.439
316118AC1-105 GEN
Solar/Wind Harmer
0.773
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.769
971283AH1-107 GEN
Solar/Wind Harmer
1.769
970831AG2-522 GEN
Solar/Wind Harmer
5.308
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.09
946281AF1-292 GEN
Solar/Wind Harmer
0.208
316087AB2-174 GEN
Solar/Wind Harmer
1.297
970673AG2-436 GEN
Solar/Wind Harmer
18.787
970673AG2-436 GEN
Solar/Wind Harmer
9.512
941031AE2-094 GEN
Solar/Wind Harmer
16.63
944011AF1-069 GEN
Solar/Wind Harmer
5.211
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970865AG2-541 GEN
Solar/Wind Harmer
3.55
970085AG2-068 GEN
Solar/Wind Harmer
5.427
970581AG2-369 GEN
Solar/Wind Harmer
4.667
315607AA1-063A GEN
Solar/Wind Harmer
0.852
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.6
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.71
315652AC1-086 GEN
Solar/Wind Harmer
8.941
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
316123AC1-075 GEN
Solar/Wind Harmer
0.832
970165AG2-112 GEN
Solar/Wind Harmer
0.733
970163AG2-111 GEN
Solar/Wind Harmer
0.699
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316319Z2-044 C
Solar/Wind Harmer
0.41
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.217
315732AD1-074 GEN1
Solar/Wind Harmer
1.475
315733AD1-074 GEN2
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.737
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316349AD2-085 GEN
Solar/Wind Harmer
0.645
315816AE2-034 GEN
Solar/Wind Harmer
0.587
316311AC2-079 GEN
Solar/Wind Harmer
3.659
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.779
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.193
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.193
316305AF2-043 C
Solar/Wind Harmer
0.215
316420AA1-050 GEN
Solar/Wind Harmer
0.816
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
3151081ELIZAR1
Adder
5.776
3151091ELIZAR2
Adder
5.675
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.681
3152601GOSPORTA
Adder
0.628
972265AH1-717 GEN
Adder
4.706
3151201GRAVEL4
Adder
4.411
3151191GRAVEL3
Adder
4.355
3151211GRAVEL5
Adder
4.355
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.572
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.107
MECLTFEXP_MEC->PJM
CLTF
0.537
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CPLELTFEXP_CPLE->PJM
CLTF
4.206
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.626
LAGNLTFEXP_LAGN->PJM
CLTF
1.959
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.437
TVALTFEXP_TVA->PJM
CLTF
0.967
NYPJM->LTFIMP_NY
CLTF
0.612
LGEELTFEXP_LGEE->PJM
CLTF
0.133
WECLTFEXP_WEC->PJM
CLTF
0.061

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:177.73 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1437.82
MW Contribution:2.03
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.588
970535AG2-341 GEN
50/50
2.034
971489AH1-241 GEN
Solar/Wind Harmer
27.358
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.65
970301AG2-198 GEN
Solar/Wind Harmer
12.49
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3151931BEARGRDN S1
50/50
5.533
3151911BEARGRDN G1
50/50
4.287
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
18.19
972003AH1-546 GEN
Solar/Wind Harmer
24.898
971377AH1-170 GEN
Solar/Wind Harmer
5.763
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.282
316322AB2-045
Solar/Wind Harmer
1.394
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.86
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
963171AG1-166 GEN
Solar/Wind Harmer
2.905
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
18.606
3143226MDLTHAN
Solar/Wind Harmer
-0.015
962491AG1-098 GEN
Solar/Wind Harmer
9.894
315693AD1-088 GEN
Solar/Wind Harmer
7.12
316237AB2-079_GEN
Solar/Wind Harmer
0.427
3143526WINTERP
Solar/Wind Harmer
-0.065
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.362
315687AD1-152 GEN
Solar/Wind Harmer
1.282
971065AG2-659 GEN
Solar/Wind Harmer
5.251
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.904
971795AH1-408 GEN
Solar/Wind Harmer
7.449
3150851SPRUNCC
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.906
960081AF2-299 GEN
Solar/Wind Harmer
0.983
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
970919AG2-571 GEN
Solar/Wind Harmer
2.482
970087AG2-069 GEN
Solar/Wind Harmer
7.326
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.518
940641AE2-051 GEN
Solar/Wind Harmer
6.973
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.551
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
316212AC1-099_GEN
Solar/Wind Harmer
0.635
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.08
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
5.319
970659AG2-427 GEN
Solar/Wind Harmer
3.71
316381AD1-082 GEN
Solar/Wind Harmer
0.639
315722AD1-056 GEN
Solar/Wind Harmer
0.728
970661AG2-428 GEN
Solar/Wind Harmer
7.356
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
970129AG2-093 GEN
Solar/Wind Harmer
1.536
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316458AB2-190 GEN2
Solar/Wind Harmer
0.68
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.303
316359AB2-059 GEN
Solar/Wind Harmer
0.905
316049AB1-081 GEN
Solar/Wind Harmer
0.725
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.951
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
316174AB2-169 GEN
Solar/Wind Harmer
1.029
315800Z1-036_GEN1
Solar/Wind Harmer
1.645
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
971647AH1-324 GEN
Solar/Wind Harmer
3.305
316246AF1-032 C
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.913
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.242
316388AE2-253 GEN
Solar/Wind Harmer
0.443
316375AC2-012 GEN
Solar/Wind Harmer
2.263
3150981CHESPKA
Adder
0.727
3151171GRAVELC
Adder
0.617
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.88
3147666LOUISA
Solar/Wind Helper
0.508
944591AF1-124 GEN
Solar/Wind Harmer
8.419
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.631
963191AG1-168 GEN
Solar/Wind Harmer
2.179
971741AH1-377 GEN
Solar/Wind Harmer
26.175
316034AC1-036 C
Solar/Wind Harmer
0.356
970323AG2-213 GEN
Solar/Wind Harmer
9.582
971775AH1-396 GEN
Solar/Wind Harmer
1.365
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.349
3143526WINTERP
Solar/Wind Harmer
-0.065
962561AG1-105 GEN
Solar/Wind Harmer
6.845
939181AE1-148 GEN
Solar/Wind Harmer
6.741
964791AG1-342 GEN
Solar/Wind Harmer
2.511
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.545
970933AG2-581 GEN
Solar/Wind Harmer
9.023
316181AB2-040 GEN
Solar/Wind Harmer
1.184
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.923
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.055
3145783HORNRTN
Solar/Wind Harmer
0.958
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.016
316426AA2-053 GEN
Solar/Wind Harmer
0.809
3144356SAPONY
Solar/Wind Harmer
0.264
316274AC1-208 GEN
Solar/Wind Harmer
0.799
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.235
315742AE1-103 GEN
Solar/Wind Harmer
0.736
970657AG2-426 GEN
Solar/Wind Harmer
2.172
970657AG2-426 GEN
Solar/Wind Harmer
0.454
316222AC1-221 GEN
Solar/Wind Harmer
0.698
316065AD1-022 GEN
Solar/Wind Harmer
3.4
942751AE2-291 GEN
Solar/Wind Harmer
4.316
316263AC1-034 GEN
Solar/Wind Harmer
3.148
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.622
316033AB2-134 GEN
Solar/Wind Harmer
2.144
315697AD1-025 GEN
Solar/Wind Harmer
1.345
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.2
972205AH1-687 GEN
50/50
20.91
316303AF2-085
50/50
2.425
971447AH1-217 GEN
Solar/Wind Harmer
15.108
971845AH1-439 GEN
Solar/Wind Harmer
21.634
970285AG2-188 GEN
Solar/Wind Harmer
34.428
270494AE1-108_GEN
Solar/Wind Harmer
9.407
315657AE1-056 GEN
Solar/Wind Harmer
9.233
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
16.612
970681AG2-440 GEN
Solar/Wind Harmer
13.29
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.737
316239AB2-077_GEN
Solar/Wind Harmer
0.427
316238AB2-078_GEN
Solar/Wind Harmer
0.427
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316118AC1-105 GEN
Solar/Wind Harmer
0.741
970831AG2-522 GEN
Solar/Wind Harmer
5.054
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
946281AF1-292 GEN
Solar/Wind Harmer
0.196
971967AH1-528 GEN
Solar/Wind Harmer
16.369
3151921BEARGRDN G2
50/50
4.287
3144293JTRSVLE
50/50
0.699
970221AG2-151 GEN
Solar/Wind Harmer
28.817
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.807
316258AE1-075 C
Solar/Wind Harmer
0.726
316405AF2-144 C
Solar/Wind Harmer
0.766
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.288
970909AG2-566 GEN
Solar/Wind Harmer
2.372
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.388
963181AG1-167 GEN
Solar/Wind Harmer
2.179
959311AF2-222 GEN
Solar/Wind Harmer
20.632
970257AG2-171 GEN
Solar/Wind Harmer
7.186
315785AD2-033 C
Solar/Wind Harmer
4.155
964241AG1-285 GEN
Solar/Wind Harmer
12.598
316131AB2-060 GEN
Solar/Wind Harmer
1.595
958131AF2-107 GEN
Solar/Wind Harmer
4.893
316478AD1-087 GEN
Solar/Wind Harmer
1.01
316486AD2-202 GEN
Solar/Wind Harmer
0.296
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.904
3150861SPRUNCD
Adder
0.382
971683AH1-343 GEN
Solar/Wind Harmer
3.805
966621AG1-532 GEN
Solar/Wind Harmer
0.177
313506AB2-031 GEN
Solar/Wind Harmer
0.682
970917AG2-570 GEN
Solar/Wind Harmer
19.61
316365GEN2_N
Solar/Wind Harmer
0.518
3156081AA2-088 GEN
Solar/Wind Harmer
2.417
3146263WOODLND
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.773
961681AG1-008 GEN
Solar/Wind Harmer
5.773
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316210AC1-098 GEN
Solar/Wind Harmer
1.142
3146173TUNIS
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
316140AB2-099
Solar/Wind Harmer
0.048
962331AG1-082 GEN
Solar/Wind Harmer
0.898
316317KELFORD C
Solar/Wind Harmer
0.338
3145823KELFORD
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.89
316327AA2-057 GEN
Solar/Wind Harmer
0.714
315813AE1-149 C
Solar/Wind Harmer
4.418
970659AG2-427 GEN
Solar/Wind Harmer
0.658
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
0.4
3145273HOLLAND
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
1.304
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315737AD1-076 GEN
Solar/Wind Harmer
1.285
971157AH1-035 GEN
Solar/Wind Harmer
0.844
970129AG2-093 GEN
Solar/Wind Harmer
3.791
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.725
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.787
961601AG1-000A GEN
Solar/Wind Harmer
2.655
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.827
316320Y1-086
Solar/Wind Harmer
0.387
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.801
961611AG1-000B GEN
Solar/Wind Harmer
1.383
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.404
3151221GRAVEL6
Adder
4.219
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
315616AA1-038_C
Solar/Wind Helper
0.514
316087AB2-174 GEN
Solar/Wind Harmer
1.222
970865AG2-541 GEN
Solar/Wind Harmer
3.392
3137643SOCKMAN
Solar/Wind Harmer
-0.033
970673AG2-436 GEN
Solar/Wind Harmer
16.777
970673AG2-436 GEN
Solar/Wind Harmer
8.495
315607AA1-063A GEN
Solar/Wind Harmer
0.8
941031AE2-094 GEN
Solar/Wind Harmer
14.78
944011AF1-069 GEN
Solar/Wind Harmer
4.631
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.884
970581AG2-369 GEN
Solar/Wind Harmer
4.201
315814AE2-033 C
Solar/Wind Harmer
7.048
316315AB2-025 C
Solar/Wind Harmer
0.204
965291AG1-394 GEN
Solar/Wind Harmer
0.664
315652AC1-086 GEN
Solar/Wind Harmer
8.34
316123AC1-075 GEN
Solar/Wind Harmer
0.797
970165AG2-112 GEN
Solar/Wind Harmer
0.701
970163AG2-111 GEN
Solar/Wind Harmer
0.669
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.381
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.985
315833AF1-017_GEN
Solar/Wind Harmer
1.293
316349AD2-085 GEN
Solar/Wind Harmer
0.606
316311AC2-079 GEN
Solar/Wind Harmer
3.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.367
315733AD1-074 GEN2
Solar/Wind Harmer
1.367
315735AD1-075 GEN1
Solar/Wind Harmer
0.684
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.68
315816AE2-034 GEN
Solar/Wind Harmer
0.544
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.645
316369SG1_INVT
Solar/Wind Harmer
1.188
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.757
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.895
316321Z2-027
Solar/Wind Harmer
0.178
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
316305AF2-043 C
Solar/Wind Harmer
0.199
313526AB2-022
Solar/Wind Harmer
0.178
316005AA1-067
Solar/Wind Harmer
0.133
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.865
3146406KITTY HAWK
Solar/Wind Harmer
0.005
319010AE1-072 C
Solar/Wind Harmer
1.33
957871AF2-081 GEN
Solar/Wind Harmer
3.284
3152611GOSPORTB
Adder
0.742
3152621GOSPORTC
Adder
0.629
3152601GOSPORTA
Adder
0.581
3151081ELIZAR1
Adder
5.335
3151091ELIZAR2
Adder
5.243
972265AH1-717 GEN
Adder
4.506
3151201GRAVEL4
Adder
4.224
3151191GRAVEL3
Adder
4.17
3151211GRAVEL5
Adder
4.17
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
316433W1029_GEN2
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316018AA1-139 ULT2
Solar/Wind Harmer
0.563
316017AA1-139 ULT1
Solar/Wind Harmer
0.531
316339AD2-160 GEN
Solar/Wind Harmer
0.443
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.691
3142956BIRDNECK
Solar/Wind Harmer
0.351
316316AC1-027 C
Solar/Wind Harmer
0.201
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.082
3150701DARBY 4
Adder
4.072
3150681DARBY 2
Adder
4.067
3150671DARBY 1
Adder
4.063
966001AG1-469 GEN
Solar/Wind Helper
0.202
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.055
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.782
MECLTFEXP_MEC->PJM
CLTF
0.452
SIGELTFEXP_SIGE->PJM
CLTF
0.012
CPLELTFEXP_CPLE->PJM
CLTF
3.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.641
LAGNLTFEXP_LAGN->PJM
CLTF
1.764
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.761
TVALTFEXP_TVA->PJM
CLTF
0.87
NYPJM->LTFIMP_NY
CLTF
0.577
LGEELTFEXP_LGEE->PJM
CLTF
0.104
WECLTFEXP_WEC->PJM
CLTF
0.046

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:177.73 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1437.82
MW Contribution:2.03
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.287
3144293JTRSVLE
50/50
0.699
970221AG2-151 GEN
Solar/Wind Harmer
28.817
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.807
316258AE1-075 C
Solar/Wind Harmer
0.726
316405AF2-144 C
Solar/Wind Harmer
0.766
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.288
970909AG2-566 GEN
Solar/Wind Harmer
2.372
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.388
963181AG1-167 GEN
Solar/Wind Harmer
2.179
959311AF2-222 GEN
Solar/Wind Harmer
20.632
970257AG2-171 GEN
Solar/Wind Harmer
7.186
315785AD2-033 C
Solar/Wind Harmer
4.155
964241AG1-285 GEN
Solar/Wind Harmer
12.598
316131AB2-060 GEN
Solar/Wind Harmer
1.595
958131AF2-107 GEN
Solar/Wind Harmer
4.893
316478AD1-087 GEN
Solar/Wind Harmer
1.01
316486AD2-202 GEN
Solar/Wind Harmer
0.296
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.904
3150861SPRUNCD
Adder
0.382
971683AH1-343 GEN
Solar/Wind Harmer
3.805
966621AG1-532 GEN
Solar/Wind Harmer
0.177
313506AB2-031 GEN
Solar/Wind Harmer
0.682
970917AG2-570 GEN
Solar/Wind Harmer
19.61
316365GEN2_N
Solar/Wind Harmer
0.518
3156081AA2-088 GEN
Solar/Wind Harmer
2.417
3146263WOODLND
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.773
961681AG1-008 GEN
Solar/Wind Harmer
5.773
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316210AC1-098 GEN
Solar/Wind Harmer
1.142
3146173TUNIS
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
316140AB2-099
Solar/Wind Harmer
0.048
962331AG1-082 GEN
Solar/Wind Harmer
0.898
316317KELFORD C
Solar/Wind Harmer
0.338
3145823KELFORD
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.89
316327AA2-057 GEN
Solar/Wind Harmer
0.714
315813AE1-149 C
Solar/Wind Harmer
4.418
970659AG2-427 GEN
Solar/Wind Harmer
0.658
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
0.4
3145273HOLLAND
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
1.304
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315737AD1-076 GEN
Solar/Wind Harmer
1.285
971157AH1-035 GEN
Solar/Wind Harmer
0.844
970129AG2-093 GEN
Solar/Wind Harmer
3.791
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.725
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.787
961601AG1-000A GEN
Solar/Wind Harmer
2.655
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.827
316320Y1-086
Solar/Wind Harmer
0.387
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.801
961611AG1-000B GEN
Solar/Wind Harmer
1.383
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.404
3151221GRAVEL6
Adder
4.219
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
315616AA1-038_C
Solar/Wind Helper
0.514
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.588
970535AG2-341 GEN
50/50
2.034
971489AH1-241 GEN
Solar/Wind Harmer
27.358
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.65
970301AG2-198 GEN
Solar/Wind Harmer
12.49
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.631
963191AG1-168 GEN
Solar/Wind Harmer
2.179
971741AH1-377 GEN
Solar/Wind Harmer
26.175
316034AC1-036 C
Solar/Wind Harmer
0.356
970323AG2-213 GEN
Solar/Wind Harmer
9.582
971775AH1-396 GEN
Solar/Wind Harmer
1.365
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.349
3143526WINTERP
Solar/Wind Harmer
-0.065
962561AG1-105 GEN
Solar/Wind Harmer
6.845
939181AE1-148 GEN
Solar/Wind Harmer
6.741
964791AG1-342 GEN
Solar/Wind Harmer
2.511
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.545
970933AG2-581 GEN
Solar/Wind Harmer
9.023
316181AB2-040 GEN
Solar/Wind Harmer
1.184
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.923
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.055
3145783HORNRTN
Solar/Wind Harmer
0.958
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.016
316426AA2-053 GEN
Solar/Wind Harmer
0.809
3144356SAPONY
Solar/Wind Harmer
0.264
316274AC1-208 GEN
Solar/Wind Harmer
0.799
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.235
315742AE1-103 GEN
Solar/Wind Harmer
0.736
970657AG2-426 GEN
Solar/Wind Harmer
2.172
970657AG2-426 GEN
Solar/Wind Harmer
0.454
316222AC1-221 GEN
Solar/Wind Harmer
0.698
316065AD1-022 GEN
Solar/Wind Harmer
3.4
942751AE2-291 GEN
Solar/Wind Harmer
4.316
316263AC1-034 GEN
Solar/Wind Harmer
3.148
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.622
316033AB2-134 GEN
Solar/Wind Harmer
2.144
315697AD1-025 GEN
Solar/Wind Harmer
1.345
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.2
316433W1029_GEN2
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316018AA1-139 ULT2
Solar/Wind Harmer
0.563
316017AA1-139 ULT1
Solar/Wind Harmer
0.531
316339AD2-160 GEN
Solar/Wind Harmer
0.443
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.691
3142956BIRDNECK
Solar/Wind Harmer
0.351
316316AC1-027 C
Solar/Wind Harmer
0.201
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.082
3150701DARBY 4
Adder
4.072
3150681DARBY 2
Adder
4.067
3150671DARBY 1
Adder
4.063
966001AG1-469 GEN
Solar/Wind Helper
0.202
972205AH1-687 GEN
50/50
20.91
316303AF2-085
50/50
2.425
971447AH1-217 GEN
Solar/Wind Harmer
15.108
971845AH1-439 GEN
Solar/Wind Harmer
21.634
970285AG2-188 GEN
Solar/Wind Harmer
34.428
270494AE1-108_GEN
Solar/Wind Harmer
9.407
315657AE1-056 GEN
Solar/Wind Harmer
9.233
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
16.612
970681AG2-440 GEN
Solar/Wind Harmer
13.29
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.737
316239AB2-077_GEN
Solar/Wind Harmer
0.427
316238AB2-078_GEN
Solar/Wind Harmer
0.427
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316118AC1-105 GEN
Solar/Wind Harmer
0.741
970831AG2-522 GEN
Solar/Wind Harmer
5.054
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
946281AF1-292 GEN
Solar/Wind Harmer
0.196
971967AH1-528 GEN
Solar/Wind Harmer
16.369
3151931BEARGRDN S1
50/50
5.533
3151911BEARGRDN G1
50/50
4.287
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
18.19
972003AH1-546 GEN
Solar/Wind Harmer
24.898
971377AH1-170 GEN
Solar/Wind Harmer
5.763
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.282
316322AB2-045
Solar/Wind Harmer
1.394
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.86
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
963171AG1-166 GEN
Solar/Wind Harmer
2.905
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
18.606
3143226MDLTHAN
Solar/Wind Harmer
-0.015
962491AG1-098 GEN
Solar/Wind Harmer
9.894
315693AD1-088 GEN
Solar/Wind Harmer
7.12
316237AB2-079_GEN
Solar/Wind Harmer
0.427
3143526WINTERP
Solar/Wind Harmer
-0.065
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.362
315687AD1-152 GEN
Solar/Wind Harmer
1.282
971065AG2-659 GEN
Solar/Wind Harmer
5.251
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.904
971795AH1-408 GEN
Solar/Wind Harmer
7.449
3150851SPRUNCC
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.906
960081AF2-299 GEN
Solar/Wind Harmer
0.983
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
970919AG2-571 GEN
Solar/Wind Harmer
2.482
970087AG2-069 GEN
Solar/Wind Harmer
7.326
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.518
940641AE2-051 GEN
Solar/Wind Harmer
6.973
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.551
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
316212AC1-099_GEN
Solar/Wind Harmer
0.635
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.08
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
5.319
970659AG2-427 GEN
Solar/Wind Harmer
3.71
316381AD1-082 GEN
Solar/Wind Harmer
0.639
315722AD1-056 GEN
Solar/Wind Harmer
0.728
970661AG2-428 GEN
Solar/Wind Harmer
7.356
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
970129AG2-093 GEN
Solar/Wind Harmer
1.536
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316458AB2-190 GEN2
Solar/Wind Harmer
0.68
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.303
316359AB2-059 GEN
Solar/Wind Harmer
0.905
316049AB1-081 GEN
Solar/Wind Harmer
0.725
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.951
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
316174AB2-169 GEN
Solar/Wind Harmer
1.029
315800Z1-036_GEN1
Solar/Wind Harmer
1.645
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
971647AH1-324 GEN
Solar/Wind Harmer
3.305
316246AF1-032 C
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.913
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.242
316388AE2-253 GEN
Solar/Wind Harmer
0.443
316375AC2-012 GEN
Solar/Wind Harmer
2.263
3150981CHESPKA
Adder
0.727
3151171GRAVELC
Adder
0.617
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.88
3147666LOUISA
Solar/Wind Helper
0.508
944591AF1-124 GEN
Solar/Wind Harmer
8.419
316087AB2-174 GEN
Solar/Wind Harmer
1.222
970865AG2-541 GEN
Solar/Wind Harmer
3.392
3137643SOCKMAN
Solar/Wind Harmer
-0.033
970673AG2-436 GEN
Solar/Wind Harmer
16.777
970673AG2-436 GEN
Solar/Wind Harmer
8.495
315607AA1-063A GEN
Solar/Wind Harmer
0.8
941031AE2-094 GEN
Solar/Wind Harmer
14.78
944011AF1-069 GEN
Solar/Wind Harmer
4.631
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.884
970581AG2-369 GEN
Solar/Wind Harmer
4.201
315814AE2-033 C
Solar/Wind Harmer
7.048
316315AB2-025 C
Solar/Wind Harmer
0.204
965291AG1-394 GEN
Solar/Wind Harmer
0.664
315652AC1-086 GEN
Solar/Wind Harmer
8.34
316123AC1-075 GEN
Solar/Wind Harmer
0.797
970165AG2-112 GEN
Solar/Wind Harmer
0.701
970163AG2-111 GEN
Solar/Wind Harmer
0.669
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.381
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.985
315833AF1-017_GEN
Solar/Wind Harmer
1.293
316349AD2-085 GEN
Solar/Wind Harmer
0.606
316311AC2-079 GEN
Solar/Wind Harmer
3.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.367
315733AD1-074 GEN2
Solar/Wind Harmer
1.367
315735AD1-075 GEN1
Solar/Wind Harmer
0.684
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.68
315816AE2-034 GEN
Solar/Wind Harmer
0.544
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.645
316369SG1_INVT
Solar/Wind Harmer
1.188
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.757
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.895
316321Z2-027
Solar/Wind Harmer
0.178
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
316305AF2-043 C
Solar/Wind Harmer
0.199
313526AB2-022
Solar/Wind Harmer
0.178
316005AA1-067
Solar/Wind Harmer
0.133
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.865
3146406KITTY HAWK
Solar/Wind Harmer
0.005
319010AE1-072 C
Solar/Wind Harmer
1.33
957871AF2-081 GEN
Solar/Wind Harmer
3.284
3152611GOSPORTB
Adder
0.742
3152621GOSPORTC
Adder
0.629
3152601GOSPORTA
Adder
0.581
3151081ELIZAR1
Adder
5.335
3151091ELIZAR2
Adder
5.243
972265AH1-717 GEN
Adder
4.506
3151201GRAVEL4
Adder
4.224
3151191GRAVEL3
Adder
4.17
3151211GRAVEL5
Adder
4.17
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.055
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.782
MECLTFEXP_MEC->PJM
CLTF
0.452
SIGELTFEXP_SIGE->PJM
CLTF
0.012
CPLELTFEXP_CPLE->PJM
CLTF
3.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.641
LAGNLTFEXP_LAGN->PJM
CLTF
1.764
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.761
TVALTFEXP_TVA->PJM
CLTF
0.87
NYPJM->LTFIMP_NY
CLTF
0.577
LGEELTFEXP_LGEE->PJM
CLTF
0.104
WECLTFEXP_WEC->PJM
CLTF
0.046

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:163.84 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:1084.23
MW Contribution:2.05
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
7.21
3151911BEARGRDN G1
50/50
5.587
3144293JTRSVLE
50/50
0.823
3151601KERR 3
50/50
0.202
3151581KERR 1
50/50
0.072
3151531CLOVER1
50/50
2.069
3147043LAWRENC
50/50
0.777
970937AG2-583 GEN
Solar/Wind Harmer
36.866
316336AC2-165 C
Solar/Wind Harmer
0.024
972003AH1-546 GEN
Solar/Wind Harmer
24.522
971377AH1-170 GEN
Solar/Wind Harmer
5.701
3147623JAMES R
Solar/Wind Harmer
1.238
316322AB2-045
Solar/Wind Harmer
0.004
3146776BUCKING
Solar/Wind Harmer
0.188
3146926FARMVIL
Solar/Wind Harmer
0.218
963171AG1-166 GEN
Solar/Wind Harmer
1.299
971563AH1-280 GEN
Solar/Wind Harmer
2.599
970685AG2-442 GEN
Solar/Wind Harmer
16.367
962491AG1-098 GEN
Solar/Wind Harmer
7.651
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
6.098
970401AG2-262 GEN
Solar/Wind Harmer
0.618
957481AF2-042 GEN
Solar/Wind Harmer
24.997
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.611
316129AC1-054 GEN
Solar/Wind Harmer
0.309
316003AC1-222 GEN
Solar/Wind Harmer
0.002
971795AH1-408 GEN
Solar/Wind Harmer
4.899
962751AG1-124 GEN
Solar/Wind Harmer
3.147
960081AF2-299 GEN
Solar/Wind Harmer
0.55
3151921BEARGRDN G2
50/50
5.587
3144293JTRSVLE
50/50
0.823
3151591KERR 2
50/50
0.202
970413AG2-270 GEN
50/50
9.029
966251AG1-494 GEN
50/50
1.716
970221AG2-151 GEN
Solar/Wind Harmer
28.504
3146776BUCKING
Solar/Wind Harmer
0.169
3146926FARMVIL
Solar/Wind Harmer
0.218
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
970909AG2-566 GEN
Solar/Wind Harmer
2.804
3147133PAMPLIN
Solar/Wind Harmer
0.818
971193AH1-056 GEN
Solar/Wind Harmer
15.872
963181AG1-167 GEN
Solar/Wind Harmer
0.975
959311AF2-222 GEN
Solar/Wind Harmer
17.841
970257AG2-171 GEN
Solar/Wind Harmer
6.184
315785AD2-033 C
Solar/Wind Harmer
1.488
958131AF2-107 GEN
Solar/Wind Harmer
4.835
964241AG1-285 GEN
Solar/Wind Harmer
10.382
316131AB2-060 GEN
Solar/Wind Harmer
0.438
316478AD1-087 GEN
Solar/Wind Harmer
0.337
316486AD2-202 GEN
Solar/Wind Harmer
0.099
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.582
3147043LAWRENC
Solar/Wind Harmer
0.049
971683AH1-343 GEN
Solar/Wind Harmer
2.828
3132273ORANGE
Solar/Wind Helper
0.023
3144293JTRSVLE
50/50
0.823
3144293JTRSVLE
50/50
0.693
970535AG2-341 GEN
50/50
2.047
3152661PLYWOOD A
50/50
0.202
971489AH1-241 GEN
Solar/Wind Harmer
28.504
3146776BUCKING
Solar/Wind Harmer
1.881
3146776BUCKING
Solar/Wind Harmer
0.152
315821AE2-092 GEN
Solar/Wind Harmer
0.02
970301AG2-198 GEN
Solar/Wind Harmer
11.214
3147133PAMPLIN
Solar/Wind Harmer
0.26
3147133PAMPLIN
Solar/Wind Harmer
0.208
958211AF2-115 GEN
Solar/Wind Harmer
2.924
963191AG1-168 GEN
Solar/Wind Harmer
0.975
971741AH1-377 GEN
Solar/Wind Harmer
22.982
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.246
971775AH1-396 GEN
Solar/Wind Harmer
0.309
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
5.277
964791AG1-342 GEN
Solar/Wind Harmer
2.024
3146843MT LREL
Solar/Wind Harmer
0.105
3146843MT LREL
Solar/Wind Harmer
0.105
939181AE1-148 GEN
Solar/Wind Harmer
5.007
970099AG2-077 GEN
Solar/Wind Harmer
9.999
970933AG2-581 GEN
Solar/Wind Harmer
5.154
942751AE2-291 GEN
Solar/Wind Harmer
3.374
966001AG1-469 GEN
Solar/Wind Helper
0.159
972205AH1-687 GEN
50/50
27.249
3151611KERR 4
50/50
0.202
3151621KERR 5
50/50
0.202
3151631KERR 6
50/50
0.202
3151641KERR 7
50/50
0.202
3151541CLOVER2
50/50
2.059
971447AH1-217 GEN
Solar/Wind Harmer
15.037
971845AH1-439 GEN
Solar/Wind Harmer
20.916
970285AG2-188 GEN
Solar/Wind Harmer
35.131
270494AE1-108_GEN
Solar/Wind Harmer
5.032
315657AE1-056 GEN
Solar/Wind Harmer
8.99
946301AF1-294 GEN
Solar/Wind Harmer
4.808
961791AG1-021 GEN
Solar/Wind Harmer
2.339
970683AG2-441 GEN
Solar/Wind Harmer
14.613
970681AG2-440 GEN
Solar/Wind Harmer
11.691
3144303KENBRDG
Solar/Wind Harmer
0.154
971443AH1-215 GEN
Solar/Wind Harmer
3.209
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.244
3147173SINAI
Solar/Wind Harmer
0.084
3147243WELCO
Solar/Wind Harmer
0.052
970831AG2-522 GEN
Solar/Wind Harmer
3.381
970865AG2-541 GEN
Solar/Wind Harmer
2.545
316123AC1-075 GEN
Solar/Wind Harmer
0.091
970165AG2-112 GEN
Solar/Wind Harmer
0.539
970163AG2-111 GEN
Solar/Wind Harmer
0.514
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.084
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.539
MECLTFEXP_MEC->PJM
CLTF
0.508
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CPLELTFEXP_CPLE->PJM
CLTF
2.979
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.201
LAGNLTFEXP_LAGN->PJM
CLTF
1.554
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.128
TVALTFEXP_TVA->PJM
CLTF
0.776
NYPJM->LTFIMP_NY
CLTF
0.525
LGEELTFEXP_LGEE->PJM
CLTF
0.153
WECLTFEXP_WEC->PJM
CLTF
0.071

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 242T2027_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 242T2027_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.93 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1253.38
MW Contribution:2.05
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.823
3144293JTRSVLE
50/50
0.693
970535AG2-341 GEN
50/50
2.047
971489AH1-241 GEN
Solar/Wind Harmer
35.629
3146776BUCKING
Solar/Wind Harmer
-0.21
3146776BUCKING
Solar/Wind Harmer
-0.017
315821AE2-092 GEN
Solar/Wind Harmer
7.77
970301AG2-198 GEN
Solar/Wind Harmer
14.765
3147133PAMPLIN
Solar/Wind Harmer
-0.029
3147133PAMPLIN
Solar/Wind Harmer
-0.023
958211AF2-115 GEN
Solar/Wind Harmer
4.277
963191AG1-168 GEN
Solar/Wind Harmer
2.566
971741AH1-377 GEN
Solar/Wind Harmer
30.26
316034AC1-036 C
Solar/Wind Harmer
0.404
970323AG2-213 GEN
Solar/Wind Harmer
10.857
971775AH1-396 GEN
Solar/Wind Harmer
1.546
313527AB2-043 GEN
Solar/Wind Harmer
2.466
962561AG1-105 GEN
Solar/Wind Harmer
6.948
964791AG1-342 GEN
Solar/Wind Harmer
2.529
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
939181AE1-148 GEN
Solar/Wind Harmer
6.592
970099AG2-077 GEN
Solar/Wind Harmer
13.165
970933AG2-581 GEN
Solar/Wind Harmer
6.786
942751AE2-291 GEN
Solar/Wind Harmer
4.443
966001AG1-469 GEN
Solar/Wind Helper
0.159
3151931BEARGRDN S1
50/50
7.21
3151911BEARGRDN G1
50/50
5.587
3144293JTRSVLE
50/50
0.823
970937AG2-583 GEN
Solar/Wind Harmer
48.541
316336AC2-165 C
Solar/Wind Harmer
11.736
972003AH1-546 GEN
Solar/Wind Harmer
32.342
971377AH1-170 GEN
Solar/Wind Harmer
7.506
3147623JAMES R
Solar/Wind Harmer
0.929
316322AB2-045
Solar/Wind Harmer
1.778
3146776BUCKING
Solar/Wind Harmer
-0.021
3146926FARMVIL
Solar/Wind Harmer
-0.024
963171AG1-166 GEN
Solar/Wind Harmer
3.422
971563AH1-280 GEN
Solar/Wind Harmer
3.422
970685AG2-442 GEN
Solar/Wind Harmer
21.55
962491AG1-098 GEN
Solar/Wind Harmer
10.074
316237AB2-079_GEN
Solar/Wind Harmer
0.446
315693AD1-088 GEN
Solar/Wind Harmer
7.137
970401AG2-262 GEN
Solar/Wind Harmer
0.773
957481AF2-042 GEN
Solar/Wind Harmer
32.913
315687AD1-152 GEN
Solar/Wind Harmer
1.189
971065AG2-659 GEN
Solar/Wind Harmer
4.755
316129AC1-054 GEN
Solar/Wind Harmer
0.808
3147043LAWRENC
Adder
0.732
316003AC1-222 GEN
Solar/Wind Harmer
0.879
971795AH1-408 GEN
Solar/Wind Harmer
6.192
962751AG1-124 GEN
Solar/Wind Harmer
4.595
960081AF2-299 GEN
Solar/Wind Harmer
0.724
972205AH1-687 GEN
50/50
27.249
971447AH1-217 GEN
Solar/Wind Harmer
19.799
971845AH1-439 GEN
Solar/Wind Harmer
27.54
970285AG2-188 GEN
Solar/Wind Harmer
43.657
270494AE1-108_GEN
Solar/Wind Harmer
12.267
315657AE1-056 GEN
Solar/Wind Harmer
10.983
946301AF1-294 GEN
Solar/Wind Harmer
7.014
961791AG1-021 GEN
Solar/Wind Harmer
3.422
970683AG2-441 GEN
Solar/Wind Harmer
19.241
970681AG2-440 GEN
Solar/Wind Harmer
15.393
3144303KENBRDG
Solar/Wind Harmer
-0.017
971443AH1-215 GEN
Solar/Wind Harmer
4.225
316239AB2-077_GEN
Solar/Wind Harmer
0.446
316238AB2-078_GEN
Solar/Wind Harmer
0.446
316118AC1-105 GEN
Solar/Wind Harmer
0.73
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
970831AG2-522 GEN
Solar/Wind Harmer
4.452
970865AG2-541 GEN
Solar/Wind Harmer
3.351
316123AC1-075 GEN
Solar/Wind Harmer
0.806
970165AG2-112 GEN
Solar/Wind Harmer
0.709
970163AG2-111 GEN
Solar/Wind Harmer
0.677
946281AF1-292 GEN
Solar/Wind Harmer
0.144
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
3151921BEARGRDN G2
50/50
5.587
3144293JTRSVLE
50/50
0.823
970221AG2-151 GEN
Solar/Wind Harmer
37.53
3146776BUCKING
Solar/Wind Harmer
-0.019
3146926FARMVIL
Solar/Wind Harmer
-0.024
942461AE2-259 GEN
Solar/Wind Harmer
5.218
970909AG2-566 GEN
Solar/Wind Harmer
2.804
3147133PAMPLIN
Solar/Wind Harmer
-0.092
971193AH1-056 GEN
Solar/Wind Harmer
18.305
963181AG1-167 GEN
Solar/Wind Harmer
2.566
959311AF2-222 GEN
Solar/Wind Harmer
23.538
970257AG2-171 GEN
Solar/Wind Harmer
8.143
315785AD2-033 C
Solar/Wind Harmer
4.66
958131AF2-107 GEN
Solar/Wind Harmer
6.437
964241AG1-285 GEN
Solar/Wind Harmer
13.669
316131AB2-060 GEN
Solar/Wind Harmer
1.687
316478AD1-087 GEN
Solar/Wind Harmer
0.939
316486AD2-202 GEN
Solar/Wind Harmer
0.275
316248AF1-058 C
Solar/Wind Harmer
0.284
960061AF2-297 GEN
Solar/Wind Harmer
4.717
3147043LAWRENC
Solar/Wind Harmer
-0.005
971683AH1-343 GEN
Solar/Wind Harmer
3.724
966621AG1-532 GEN
Solar/Wind Harmer
0.131
3132273ORANGE
Solar/Wind Helper
0.023
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.084
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.539
MECLTFEXP_MEC->PJM
CLTF
0.508
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CPLELTFEXP_CPLE->PJM
CLTF
2.979
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.201
LAGNLTFEXP_LAGN->PJM
CLTF
1.554
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.128
TVALTFEXP_TVA->PJM
CLTF
0.776
NYPJM->LTFIMP_NY
CLTF
0.525
LGEELTFEXP_LGEE->PJM
CLTF
0.153
WECLTFEXP_WEC->PJM
CLTF
0.071

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.74 %
Rating:661.76 MVA
Rating Type:A
MVA to Mitigate:719.62
MW Contribution:1.77
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.314
3151911BEARGRDN G1
50/50
4.118
3144293JTRSVLE
50/50
0.644
3151531CLOVER1
50/50
1.885
3151601KERR 3
50/50
0.18
3151581KERR 1
50/50
0.064
970119AG2-088 GEN
50/50
11.599
3147043LAWRENC
50/50
0.746
3151261ROARAP2
50/50
0.072
972003AH1-546 GEN
Solar/Wind Harmer
18.108
971377AH1-170 GEN
Solar/Wind Harmer
4.203
3147623JAMES R
Solar/Wind Harmer
0.913
970937AG2-583 GEN
Solar/Wind Harmer
22.204
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.14
3146926FARMVIL
Solar/Wind Harmer
0.165
316336AC2-165 C
Solar/Wind Harmer
0.01
3143336POWHATN
Solar/Wind Harmer
4.074
963171AG1-166 GEN
Solar/Wind Harmer
1.017
971563AH1-280 GEN
Solar/Wind Harmer
2.035
970685AG2-442 GEN
Solar/Wind Harmer
12.945
962491AG1-098 GEN
Solar/Wind Harmer
6.577
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
5.296
970401AG2-262 GEN
Solar/Wind Harmer
0.531
957481AF2-042 GEN
Solar/Wind Harmer
23.244
3143226MDLTHAN
Solar/Wind Harmer
0.087
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.352
316129AC1-054 GEN
Solar/Wind Harmer
0.289
971795AH1-408 GEN
Solar/Wind Harmer
4.849
3143526WINTERP
Solar/Wind Harmer
0.377
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.595
3145783HORNRTN
Solar/Wind Harmer
0.057
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.752
3151921BEARGRDN G2
50/50
4.118
3144293JTRSVLE
50/50
0.644
970413AG2-270 GEN
50/50
8.224
3151591KERR 2
50/50
0.18
966251AG1-494 GEN
50/50
1.173
3144293JTRSVLE
50/50
0.644
3144293JTRSVLE
50/50
0.543
970535AG2-341 GEN
50/50
1.768
3152661PLYWOOD A
50/50
0.177
971489AH1-241 GEN
Solar/Wind Harmer
21.013
3146776BUCKING
Solar/Wind Harmer
1.404
3146776BUCKING
Solar/Wind Harmer
0.114
315821AE2-092 GEN
Solar/Wind Harmer
0.014
970301AG2-198 GEN
Solar/Wind Harmer
8.767
3147133PAMPLIN
Solar/Wind Harmer
0.203
3147133PAMPLIN
Solar/Wind Harmer
0.162
958211AF2-115 GEN
Solar/Wind Harmer
2.289
963191AG1-168 GEN
Solar/Wind Harmer
0.763
971741AH1-377 GEN
Solar/Wind Harmer
18.217
316034AC1-036 C
Solar/Wind Harmer
0.011
972205AH1-687 GEN
50/50
20.083
3151541CLOVER2
50/50
1.876
3151611KERR 4
50/50
0.18
3151621KERR 5
50/50
0.18
3151631KERR 6
50/50
0.18
3151641KERR 7
50/50
0.18
316303AF2-085
50/50
1.546
3151281ROARAP4
50/50
0.07
3151281ROARAP4
50/50
0.066
971447AH1-217 GEN
Solar/Wind Harmer
11.004
971845AH1-439 GEN
Solar/Wind Harmer
15.632
970285AG2-188 GEN
Solar/Wind Harmer
26.316
270494AE1-108_GEN
Solar/Wind Harmer
3.693
315657AE1-056 GEN
Solar/Wind Harmer
6.997
946301AF1-294 GEN
Solar/Wind Harmer
3.764
961791AG1-021 GEN
Solar/Wind Harmer
1.831
970683AG2-441 GEN
Solar/Wind Harmer
11.558
970681AG2-440 GEN
Solar/Wind Harmer
9.247
3144303KENBRDG
Solar/Wind Harmer
0.124
971443AH1-215 GEN
Solar/Wind Harmer
2.576
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.212
970831AG2-522 GEN
Solar/Wind Harmer
3.201
3147173SINAI
Solar/Wind Harmer
0.074
3147243WELCO
Solar/Wind Harmer
0.046
316233AE1-074 FULL
Solar/Wind Harmer
0.058
971281AH1-106 GEN
Solar/Wind Harmer
1.006
971283AH1-107 GEN
Solar/Wind Harmer
1.006
970865AG2-541 GEN
Solar/Wind Harmer
2.17
316087AB2-174 GEN
Solar/Wind Harmer
0.002
971967AH1-528 GEN
Solar/Wind Harmer
9.597
3137643SOCKMAN
Solar/Wind Harmer
0.235
3138266HYDRAULIC
Solar/Wind Helper
0.021
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.08
3148013FISHERV
Solar/Wind Helper
0.077
3148463FAIRFLD
Solar/Wind Helper
0.119
970323AG2-213 GEN
Solar/Wind Harmer
6.61
971775AH1-396 GEN
Solar/Wind Harmer
0.248
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
4.515
939181AE1-148 GEN
Solar/Wind Harmer
4.407
964791AG1-342 GEN
Solar/Wind Harmer
1.738
3146843MT LREL
Solar/Wind Harmer
0.09
3146843MT LREL
Solar/Wind Harmer
0.09
970099AG2-077 GEN
Solar/Wind Harmer
9.298
971223AH1-071 GEN
Solar/Wind Harmer
0.928
3143526WINTERP
Solar/Wind Harmer
0.377
970933AG2-581 GEN
Solar/Wind Harmer
5.476
316181AB2-040 GEN
Solar/Wind Harmer
0.087
3145593CAROLNA
Solar/Wind Harmer
0.058
3145593CAROLNA
Solar/Wind Harmer
0.058
966811AG1-552 GEN
Solar/Wind Harmer
0.627
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.01
3145783HORNRTN
Solar/Wind Harmer
0.808
3145783HORNRTN
Solar/Wind Harmer
0.253
3145783HORNRTN
Solar/Wind Harmer
0.101
966001AG1-469 GEN
Solar/Wind Helper
0.19
3151261ROARAP2
50/50
0.07
970221AG2-151 GEN
Solar/Wind Harmer
21.013
3146776BUCKING
Solar/Wind Harmer
0.126
3146926FARMVIL
Solar/Wind Harmer
0.165
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.144
316258AE1-075 C
Solar/Wind Harmer
0.173
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.463
970909AG2-566 GEN
Solar/Wind Harmer
2.192
3147133PAMPLIN
Solar/Wind Harmer
0.637
971193AH1-056 GEN
Solar/Wind Harmer
12.353
963181AG1-167 GEN
Solar/Wind Harmer
0.763
959311AF2-222 GEN
Solar/Wind Harmer
14.242
970257AG2-171 GEN
Solar/Wind Harmer
4.957
315785AD2-033 C
Solar/Wind Harmer
1.2
964241AG1-285 GEN
Solar/Wind Harmer
8.548
958131AF2-107 GEN
Solar/Wind Harmer
3.44
316131AB2-060 GEN
Solar/Wind Harmer
0.366
316478AD1-087 GEN
Solar/Wind Harmer
0.307
316486AD2-202 GEN
Solar/Wind Harmer
0.09
3147043LAWRENC
Solar/Wind Harmer
0.047
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.155
971683AH1-343 GEN
Solar/Wind Harmer
2.44
313506AB2-031 GEN
Solar/Wind Harmer
0.186
316499AE2-029_GEN
Solar/Wind Helper
0.505
3148013FISHERV
Solar/Wind Helper
0.133
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.54
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.673
MECLTFEXP_MEC->PJM
CLTF
0.138
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CPLELTFEXP_CPLE->PJM
CLTF
2.992
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.238
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.029
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.072
LAGNLTFEXP_LAGN->PJM
CLTF
1.122
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.815
TVALTFEXP_TVA->PJM
CLTF
0.547
NYPJM->LTFIMP_NY
CLTF
0.391

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:195.13 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:1291.31
MW Contribution:2.11
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.469
3151911BEARGRDN G1
50/50
4.238
3144293JTRSVLE
50/50
0.706
970119AG2-088 GEN
50/50
15.414
3151531CLOVER1
50/50
2.348
3151601KERR 3
50/50
0.22
3151581KERR 1
50/50
0.079
3147043LAWRENC
50/50
0.939
3151051BRUNSWICKS1
50/50
2.197
3151021BRUNSWICKG1
50/50
1.059
971451AH1-221 GEN
50/50
3.216
315243AE2-183_GT3
50/50
1.321
3151261ROARAP2
50/50
0.097
3150851SPRUNCC
50/50
0.364
972003AH1-546 GEN
Solar/Wind Harmer
18.676
971377AH1-170 GEN
Solar/Wind Harmer
4.327
3147623JAMES R
Solar/Wind Harmer
0.94
970937AG2-583 GEN
Solar/Wind Harmer
23.217
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.147
3146926FARMVIL
Solar/Wind Harmer
0.176
316336AC2-165 C
Solar/Wind Harmer
0.011
3143336POWHATN
Solar/Wind Harmer
4.472
963171AG1-166 GEN
Solar/Wind Harmer
1.114
971563AH1-280 GEN
Solar/Wind Harmer
2.228
970685AG2-442 GEN
Solar/Wind Harmer
14.313
962491AG1-098 GEN
Solar/Wind Harmer
7.815
315693AD1-088 GEN
Solar/Wind Harmer
6.344
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Harmer
0.116
957481AF2-042 GEN
Solar/Wind Harmer
29.295
970401AG2-262 GEN
Solar/Wind Harmer
0.638
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
4.184
3143526WINTERP
Solar/Wind Harmer
0.504
316129AC1-054 GEN
Solar/Wind Harmer
0.363
971795AH1-408 GEN
Solar/Wind Harmer
6.199
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.793
970919AG2-571 GEN
Solar/Wind Harmer
2.76
970087AG2-069 GEN
Solar/Wind Harmer
6.187
3145783HORNRTN
Solar/Wind Harmer
0.076
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
5.984
316023GEN1_S
Solar/Wind Harmer
0.164
939411AE1-173 GEN
Solar/Wind Harmer
30.681
316011AB1-132 GEN
Solar/Wind Harmer
1.286
962571AG1-106 GEN
Solar/Wind Harmer
1.007
3146263WOODLND
Solar/Wind Harmer
0.071
3145893MURPHYS
Solar/Wind Harmer
0.281
3145893MURPHYS
Solar/Wind Harmer
0.312
3145796HORNRTN
Solar/Wind Harmer
0.23
3145796HORNRTN
Solar/Wind Harmer
0.07
316212AC1-099_GEN
Solar/Wind Harmer
0.359
3146173TUNIS
Solar/Wind Harmer
0.069
3145823KELFORD
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
315722AD1-056 GEN
Solar/Wind Harmer
0.422
3146233WITAKRS
Solar/Wind Harmer
0.263
3146206CASHIE
Solar/Wind Harmer
0.065
971547AH1-271 GEN
Solar/Wind Harmer
1.396
970659AG2-427 GEN
Solar/Wind Harmer
3.146
316381AD1-082 GEN
Solar/Wind Harmer
0.068
970661AG2-428 GEN
Solar/Wind Harmer
6.453
3145663CRESWEL
Solar/Wind Harmer
0.181
971163AH1-040 GEN
Solar/Wind Harmer
5.167
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.052
316359AB2-059 GEN
Solar/Wind Harmer
0.231
316049AB1-081 GEN
Solar/Wind Harmer
0.368
3142053HEARTS
Solar/Wind Harmer
0.113
316093AE2-104_GEN
Solar/Wind Harmer
1.081
3130156CHOWAN
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3142543TWELFTH
Solar/Wind Harmer
0.006
3146516WINFALL
Solar/Wind Harmer
0.207
3146516WINFALL
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.283
316246AF1-032 C
Solar/Wind Harmer
0.029
3146293MARTNCO
Solar/Wind Harmer
0.059
316494AC1-189 GEN
Solar/Wind Harmer
0.214
3146456SLIGO L269
Solar/Wind Harmer
0.063
316388AE2-253 GEN
Solar/Wind Harmer
0.198
944591AF1-124 GEN
Solar/Wind Harmer
14.289
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
315671AE2-027_GEN
Solar/Wind Harmer
4.043
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
1.077
3145336SMITFLD
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
0.644
961611AG1-000B GEN
Solar/Wind Harmer
3.17
971647AH1-324 GEN
Solar/Wind Harmer
2.576
3143096IRON208
Adder
0.252
971069AG2-661 GEN
Solar/Wind Harmer
1.071
316458AB2-190 GEN2
Solar/Wind Harmer
0.323
970129AG2-093 GEN
Solar/Wind Harmer
1.71
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.903
3147666LOUISA
Solar/Wind Helper
0.521
3151921BEARGRDN G2
50/50
4.238
3144293JTRSVLE
50/50
0.706
970413AG2-270 GEN
50/50
10.245
3151591KERR 2
50/50
0.22
3151031BRUNSWICKG2
50/50
1.059
3151261ROARAP2
50/50
0.095
3150861SPRUNCD
50/50
0.364
966251AG1-494 GEN
50/50
1.288
970221AG2-151 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
0.132
3146926FARMVIL
Solar/Wind Harmer
0.176
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.159
316258AE1-075 C
Solar/Wind Harmer
0.19
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.801
970909AG2-566 GEN
Solar/Wind Harmer
2.396
3147133PAMPLIN
Solar/Wind Harmer
0.693
971193AH1-056 GEN
Solar/Wind Harmer
13.448
963181AG1-167 GEN
Solar/Wind Harmer
0.835
959311AF2-222 GEN
Solar/Wind Harmer
15.884
970257AG2-171 GEN
Solar/Wind Harmer
5.55
315785AD2-033 C
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
9.804
316131AB2-060 GEN
Solar/Wind Harmer
0.426
958131AF2-107 GEN
Solar/Wind Harmer
3.651
316478AD1-087 GEN
Solar/Wind Harmer
0.382
316486AD2-202 GEN
Solar/Wind Harmer
0.112
3147043LAWRENC
Solar/Wind Harmer
0.059
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.912
971683AH1-343 GEN
Solar/Wind Harmer
3.032
313506AB2-031 GEN
Solar/Wind Harmer
0.248
970917AG2-570 GEN
Solar/Wind Harmer
6.901
316365GEN2_N
Solar/Wind Harmer
0.164
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
0.117
3145893MURPHYS
Solar/Wind Harmer
0.07
957521AF2-046 GEN
Solar/Wind Harmer
5.202
961681AG1-008 GEN
Solar/Wind Harmer
5.202
3145796HORNRTN
Solar/Wind Harmer
0.279
3145796HORNRTN
Solar/Wind Harmer
0.07
316210AC1-098 GEN
Solar/Wind Harmer
0.644
3146173TUNIS
Solar/Wind Harmer
0.069
316463AE2-346 GEN
Solar/Wind Harmer
0.059
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.732
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.069
316327AA2-057 GEN
Solar/Wind Harmer
0.102
315724AD1-057 GEN
Solar/Wind Harmer
0.25
3145273HOLLAND
Solar/Wind Harmer
0.05
3156021HOLLOMANSOL
Solar/Wind Harmer
0.301
3146233WITAKRS
Solar/Wind Harmer
0.331
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3146206CASHIE
Solar/Wind Harmer
0.065
315813AE1-149 C
Solar/Wind Harmer
3.482
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316283AC2-100 C
Solar/Wind Harmer
0.127
315839AE2-212 C
Solar/Wind Harmer
0.001
315737AD1-076 GEN
Solar/Wind Harmer
0.835
970661AG2-428 GEN
Solar/Wind Harmer
1.373
971157AH1-035 GEN
Solar/Wind Harmer
0.778
315614AA2-178 GEN
Solar/Wind Harmer
0.37
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.129
3146376EDENTON
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
4.548
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316435W1029_GEN3
Solar/Wind Harmer
0
965281AG1-393 GEN
Solar/Wind Harmer
0.68
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
316320Y1-086
Solar/Wind Harmer
0
3145933PARMELE
Solar/Wind Harmer
0.063
966801AG1-551 GEN
Solar/Wind Harmer
0.74
3146456SLIGO L269
Solar/Wind Harmer
0.063
971153AH1-033 GEN
Solar/Wind Harmer
0.732
944581AF1-123 GEN
Solar/Wind Harmer
14.239
944601AF1-125 GEN
Solar/Wind Harmer
14.019
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3151101ELIZAR3
Adder
5.847
3144873MCLAUGH
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.009
315773AC2-141 GEN
Solar/Wind Harmer
2.27
3145336SMITFLD
Solar/Wind Harmer
0.025
3151221GRAVEL6
Adder
4.403
3151171GRAVELC
Adder
0.847
961611AG1-000B GEN
Solar/Wind Harmer
1.612
3143096IRON208
Adder
0.252
3143096IRON208
Adder
0.247
315778AD1-151 GEN
Solar/Wind Harmer
4.818
970129AG2-093 GEN
Solar/Wind Harmer
3.634
970133AG2-095 GEN
Solar/Wind Harmer
0.576
316499AE2-029_GEN
Solar/Wind Helper
0.501
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.3
3148013FISHERV
Solar/Wind Helper
0.129
315616AA1-038_C
Solar/Wind Helper
0.524
972205AH1-687 GEN
50/50
20.67
316303AF2-085
50/50
2.055
3151541CLOVER2
50/50
2.336
3151611KERR 4
50/50
0.22
3151621KERR 5
50/50
0.22
3151631KERR 6
50/50
0.22
3151641KERR 7
50/50
0.22
963041AG1-153 GEN
50/50
2.144
315244AE2-183_ST
50/50
2.284
3151281ROARAP4
50/50
0.094
3151281ROARAP4
50/50
0.088
971285AH1-108 GEN
50/50
0.596
315779AE2-040
50/50
1.013
971447AH1-217 GEN
Solar/Wind Harmer
11.337
971845AH1-439 GEN
Solar/Wind Harmer
16.33
970285AG2-188 GEN
Solar/Wind Harmer
27.559
270494AE1-108_GEN
Solar/Wind Harmer
3.817
315657AE1-056 GEN
Solar/Wind Harmer
7.617
946301AF1-294 GEN
Solar/Wind Harmer
4.122
961791AG1-021 GEN
Solar/Wind Harmer
2.005
970683AG2-441 GEN
Solar/Wind Harmer
12.78
970681AG2-440 GEN
Solar/Wind Harmer
10.224
3144303KENBRDG
Solar/Wind Harmer
0.139
971443AH1-215 GEN
Solar/Wind Harmer
2.888
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.258
316233AE1-074 FULL
Solar/Wind Harmer
0.078
971281AH1-106 GEN
Solar/Wind Harmer
1.344
971283AH1-107 GEN
Solar/Wind Harmer
1.344
970831AG2-522 GEN
Solar/Wind Harmer
4.036
3147173SINAI
Solar/Wind Harmer
0.092
3147243WELCO
Solar/Wind Harmer
0.057
971967AH1-528 GEN
Solar/Wind Harmer
13.711
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
16.986
970673AG2-436 GEN
Solar/Wind Harmer
11.324
941031AE2-094 GEN
Solar/Wind Harmer
14.544
944011AF1-069 GEN
Solar/Wind Harmer
4.752
3137643SOCKMAN
Solar/Wind Harmer
0.315
970865AG2-541 GEN
Solar/Wind Harmer
2.702
970085AG2-068 GEN
Solar/Wind Harmer
4.124
970581AG2-369 GEN
Solar/Wind Harmer
3.547
315607AA1-063A GEN
Solar/Wind Harmer
0.154
3146043SEABORD
Solar/Wind Harmer
0.075
315814AE2-033 C
Solar/Wind Harmer
5.747
316315AB2-025 C
Solar/Wind Harmer
0.059
965291AG1-394 GEN
Solar/Wind Harmer
0.317
315652AC1-086 GEN
Solar/Wind Harmer
7.782
3145893MURPHYS
Solar/Wind Harmer
0.19
3145893MURPHYS
Solar/Wind Harmer
0.07
3145796HORNRTN
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.028
3146033SCOT NK
Solar/Wind Harmer
0.276
316123AC1-075 GEN
Solar/Wind Harmer
0.094
970165AG2-112 GEN
Solar/Wind Harmer
0.558
970163AG2-111 GEN
Solar/Wind Harmer
0.532
3145513AHOSKIE
Solar/Wind Harmer
0.143
3145513AHOSKIE
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3143316POE
Solar/Wind Harmer
0.269
316319Z2-044 C
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.065
970601AG2-382 GEN
Solar/Wind Harmer
2.444
315732AD1-074 GEN1
Solar/Wind Harmer
0.373
315733AD1-074 GEN2
Solar/Wind Harmer
0.373
315735AD1-075 GEN1
Solar/Wind Harmer
0.187
3130546PLYMOUTH
Solar/Wind Harmer
0.065
315816AE2-034 GEN
Solar/Wind Harmer
0.277
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.044
316311AC2-079 GEN
Solar/Wind Harmer
1.853
315835AF2-110_GEN
Solar/Wind Harmer
0.441
3130156CHOWAN
Solar/Wind Harmer
0.064
3130156CHOWAN
Solar/Wind Harmer
0.064
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
316321Z2-027
Solar/Wind Harmer
0.012
3145176PASQUOTANK
Solar/Wind Harmer
0.039
3146396TANGLEW
Solar/Wind Harmer
0.175
316420AA1-050 GEN
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.034
316305AF2-043 C
Solar/Wind Harmer
0.001
957861AF2-080 GEN
Solar/Wind Harmer
2.737
3146406KITTY HAWK
Solar/Wind Harmer
0.008
319010AE1-072 C
Solar/Wind Harmer
0.319
957871AF2-081 GEN
Solar/Wind Harmer
3.153
316005AA1-067
Solar/Wind Harmer
0.068
3145746EVERETS
Solar/Wind Harmer
0.252
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
970181AG2-120 GEN
Solar/Wind Harmer
0.787
3151081ELIZAR1
Adder
5.773
3151091ELIZAR2
Adder
5.672
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.68
3152601GOSPORTA
Adder
0.628
971445AH1-216 GEN
Solar/Wind Harmer
4.321
972265AH1-717 GEN
Adder
4.702
3151201GRAVEL4
Adder
4.408
3151191GRAVEL3
Adder
4.352
3151211GRAVEL5
Adder
4.352
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.323
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.077
3148013FISHERV
Solar/Wind Helper
0.074
3148463FAIRFLD
Solar/Wind Helper
0.116
3144293JTRSVLE
50/50
0.706
3144293JTRSVLE
50/50
0.594
970535AG2-341 GEN
50/50
2.11
3152661PLYWOOD A
50/50
0.217
3151041BRUNSWICKG3
50/50
1.059
972187AH1-678 GEN
50/50
2.43
315242AE2-183_GT2
50/50
1.321
315241AE2-183_GT1
50/50
1.313
972185AH1-677 GEN
50/50
4.762
970533AG2-339 GEN
50/50
7.019
970531AG2-338 GEN
50/50
2.808
971489AH1-241 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
1.465
3146776BUCKING
Solar/Wind Harmer
0.119
315821AE2-092 GEN
Solar/Wind Harmer
0.014
970301AG2-198 GEN
Solar/Wind Harmer
9.583
3147133PAMPLIN
Solar/Wind Harmer
0.221
3147133PAMPLIN
Solar/Wind Harmer
0.176
958211AF2-115 GEN
Solar/Wind Harmer
2.506
963191AG1-168 GEN
Solar/Wind Harmer
0.835
971741AH1-377 GEN
Solar/Wind Harmer
20.177
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.401
971775AH1-396 GEN
Solar/Wind Harmer
0.278
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971223AH1-071 GEN
Solar/Wind Harmer
1.233
962561AG1-105 GEN
Solar/Wind Harmer
5.397
939181AE1-148 GEN
Solar/Wind Harmer
5.333
970099AG2-077 GEN
Solar/Wind Harmer
11.718
964791AG1-342 GEN
Solar/Wind Harmer
2.089
3146843MT LREL
Solar/Wind Harmer
0.109
3146843MT LREL
Solar/Wind Harmer
0.109
3143526WINTERP
Solar/Wind Harmer
0.504
970933AG2-581 GEN
Solar/Wind Harmer
7.465
316181AB2-040 GEN
Solar/Wind Harmer
0.116
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.078
966811AG1-552 GEN
Solar/Wind Harmer
0.843
3145593CAROLNA
Solar/Wind Harmer
0.097
3145783HORNRTN
Solar/Wind Harmer
1.361
3145783HORNRTN
Solar/Wind Harmer
1.089
3145783HORNRTN
Solar/Wind Harmer
0.34
3145783HORNRTN
Solar/Wind Harmer
0.136
316426AA2-053 GEN
Solar/Wind Harmer
0.256
3144356SAPONY
Solar/Wind Harmer
0.607
316274AC1-208 GEN
Solar/Wind Harmer
0.366
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.042
3145893MURPHYS
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
0.126
3145796HORNRTN
Solar/Wind Harmer
0.209
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
315742AE1-103 GEN
Solar/Wind Harmer
0.001
316222AC1-221 GEN
Solar/Wind Harmer
0.272
316065AD1-022 GEN
Solar/Wind Harmer
3.004
970657AG2-426 GEN
Solar/Wind Harmer
2.275
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
2.446
3146376EDENTON
Solar/Wind Harmer
0.286
3146376EDENTON
Solar/Wind Harmer
0.286
961601AG1-000A GEN
Solar/Wind Harmer
1.137
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3145493TOT1
Solar/Wind Harmer
0.148
3145453TOT5
Solar/Wind Harmer
0.089
3145603CNETO
Solar/Wind Harmer
0.059
3146386ELIZ CT
Solar/Wind Harmer
0.064
3145933PARMELE
Solar/Wind Harmer
0.127
3145933PARMELE
Solar/Wind Harmer
0.063
3130086AYDLETT
Solar/Wind Harmer
0.253
3137176SLIGO L2192
Solar/Wind Harmer
0.252
3146456SLIGO L269
Solar/Wind Harmer
1.121
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.035
316339AD2-160 GEN
Solar/Wind Harmer
0.103
3145506HICKORY
Solar/Wind Harmer
0.253
3145506HICKORY
Solar/Wind Harmer
0.152
3145506HICKORY
Solar/Wind Harmer
0.038
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.061
942751AE2-291 GEN
Solar/Wind Harmer
3.43
316240AF1-291 C
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.012
3150991CHESPKB
Adder
0.659
3150991CHESPKB
Adder
0.643
944641AF1-129 GEN
Adder
29.755
316236AE1-162_GEN
Solar/Wind Harmer
0
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.068
966001AG1-469 GEN
Solar/Wind Helper
0.206
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.131
MECLTFEXP_MEC->PJM
CLTF
0.546
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CPLELTFEXP_CPLE->PJM
CLTF
4.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.705
LAGNLTFEXP_LAGN->PJM
CLTF
1.972
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.458
TVALTFEXP_TVA->PJM
CLTF
0.973
NYPJM->LTFIMP_NY
CLTF
0.616
LGEELTFEXP_LGEE->PJM
CLTF
0.137
WECLTFEXP_WEC->PJM
CLTF
0.063

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:182.39 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1475.57
MW Contribution:2.11
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.704
3144293JTRSVLE
50/50
0.593
970535AG2-341 GEN
50/50
2.107
971489AH1-241 GEN
Solar/Wind Harmer
26.992
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.547
970301AG2-198 GEN
Solar/Wind Harmer
12.599
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
963191AG1-168 GEN
Solar/Wind Harmer
2.197
971741AH1-377 GEN
Solar/Wind Harmer
26.527
316034AC1-036 C
Solar/Wind Harmer
0.362
970323AG2-213 GEN
Solar/Wind Harmer
9.73
971775AH1-396 GEN
Solar/Wind Harmer
1.386
313527AB2-043 GEN
Solar/Wind Harmer
2.416
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.096
939181AE1-148 GEN
Solar/Wind Harmer
7.013
970099AG2-077 GEN
Solar/Wind Harmer
15.412
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.821
972187AH1-678 GEN
Adder
2.289
316181AB2-040 GEN
Solar/Wind Harmer
1.257
972185AH1-677 GEN
Adder
4.486
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.855
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.79
316222AC1-221 GEN
Solar/Wind Harmer
0.745
316065AD1-022 GEN
Solar/Wind Harmer
3.665
970657AG2-426 GEN
Solar/Wind Harmer
2.282
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
3.387
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.822
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.78
966001AG1-469 GEN
Solar/Wind Helper
0.216
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.704
970221AG2-151 GEN
Solar/Wind Harmer
28.432
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.296
316313AB2-026
Solar/Wind Harmer
0.761
316258AE1-075 C
Solar/Wind Harmer
0.685
316405AF2-144 C
Solar/Wind Harmer
0.723
3143336POWHATN
Solar/Wind Harmer
2.847
970909AG2-566 GEN
Solar/Wind Harmer
2.392
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.485
963181AG1-167 GEN
Solar/Wind Harmer
2.197
959311AF2-222 GEN
Solar/Wind Harmer
20.924
970257AG2-171 GEN
Solar/Wind Harmer
7.297
315785AD2-033 C
Solar/Wind Harmer
4.227
964241AG1-285 GEN
Solar/Wind Harmer
12.89
316131AB2-060 GEN
Solar/Wind Harmer
1.639
958131AF2-107 GEN
Solar/Wind Harmer
4.847
316478AD1-087 GEN
Solar/Wind Harmer
1.065
316486AD2-202 GEN
Solar/Wind Harmer
0.312
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.31
960061AF2-297 GEN
Solar/Wind Harmer
5.143
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.986
313506AB2-031 GEN
Solar/Wind Harmer
0.724
970917AG2-570 GEN
Solar/Wind Harmer
21.795
3150861SPRUNCD
Adder
0.344
316365GEN2_N
Solar/Wind Harmer
0.555
3156081AA2-088 GEN
Solar/Wind Harmer
2.586
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3151931BEARGRDN S1
50/50
5.46
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.704
970119AG2-088 GEN
50/50
15.406
972003AH1-546 GEN
Solar/Wind Harmer
24.588
971377AH1-170 GEN
Solar/Wind Harmer
5.686
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.518
316322AB2-045
Solar/Wind Harmer
1.382
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.598
3143336POWHATN
Solar/Wind Harmer
3.349
963171AG1-166 GEN
Solar/Wind Harmer
2.929
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
18.817
962491AG1-098 GEN
Solar/Wind Harmer
10.277
315693AD1-088 GEN
Solar/Wind Harmer
7.416
316237AB2-079_GEN
Solar/Wind Harmer
0.439
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.531
970401AG2-262 GEN
Solar/Wind Harmer
0.797
315687AD1-152 GEN
Solar/Wind Harmer
1.353
971065AG2-659 GEN
Solar/Wind Harmer
5.503
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.948
971795AH1-408 GEN
Solar/Wind Harmer
7.828
316003AC1-222 GEN
Solar/Wind Harmer
0.95
960081AF2-299 GEN
Solar/Wind Harmer
1.043
970919AG2-571 GEN
Solar/Wind Harmer
2.759
970087AG2-069 GEN
Solar/Wind Harmer
8.141
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
940641AE2-051 GEN
Solar/Wind Harmer
7.878
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.555
939411AE1-173 GEN
Solar/Wind Harmer
40.398
316011AB1-132 GEN
Solar/Wind Harmer
1.663
962571AG1-106 GEN
Solar/Wind Harmer
1.142
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.68
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.782
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.838
970659AG2-427 GEN
Solar/Wind Harmer
3.885
316381AD1-082 GEN
Solar/Wind Harmer
0.67
970661AG2-428 GEN
Solar/Wind Harmer
7.748
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.803
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.974
316049AB1-081 GEN
Solar/Wind Harmer
0.78
316093AE2-104_GEN
Solar/Wind Harmer
2.1
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
315800Z1-036_GEN1
Solar/Wind Harmer
1.779
316174AB2-169 GEN
Solar/Wind Harmer
1.109
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.185
961681AG1-008 GEN
Solar/Wind Harmer
6.185
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146173TUNIS
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.125
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.963
316317KELFORD C
Solar/Wind Harmer
0.363
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.766
315724AD1-057 GEN
Solar/Wind Harmer
0.43
3145273HOLLAND
Solar/Wind Harmer
-0.006
3156021HOLLOMANSOL
Solar/Wind Harmer
1.002
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.587
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
1.186
315839AE2-212 C
Solar/Wind Harmer
0.22
970661AG2-428 GEN
Solar/Wind Harmer
1.373
315737AD1-076 GEN
Solar/Wind Harmer
1.386
316283AC2-100 C
Solar/Wind Harmer
0.686
971157AH1-035 GEN
Solar/Wind Harmer
0.911
315614AA2-178 GEN
Solar/Wind Harmer
0.783
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.858
3146516WINFALL
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.896
316435W1029_GEN3
Solar/Wind Harmer
1.299
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.419
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.891
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151101ELIZAR3
Adder
5.849
3151221GRAVEL6
Adder
4.406
3151171GRAVELC
Adder
0.848
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.338
3148013FISHERV
Solar/Wind Helper
0.13
315616AA1-038_C
Solar/Wind Helper
0.528
944581AF1-123 GEN
Solar/Wind Harmer
20.452
972205AH1-687 GEN
50/50
20.633
316303AF2-085
50/50
2.054
971447AH1-217 GEN
Solar/Wind Harmer
14.897
971845AH1-439 GEN
Solar/Wind Harmer
21.465
970285AG2-188 GEN
Solar/Wind Harmer
34.19
270494AE1-108_GEN
Solar/Wind Harmer
9.286
315657AE1-056 GEN
Solar/Wind Harmer
9.291
946301AF1-294 GEN
Solar/Wind Harmer
6.004
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
16.801
970681AG2-440 GEN
Solar/Wind Harmer
13.441
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.796
316239AB2-077_GEN
Solar/Wind Harmer
0.439
316238AB2-078_GEN
Solar/Wind Harmer
0.439
316118AC1-105 GEN
Solar/Wind Harmer
0.773
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.769
971283AH1-107 GEN
Solar/Wind Harmer
1.769
970831AG2-522 GEN
Solar/Wind Harmer
5.308
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.09
946281AF1-292 GEN
Solar/Wind Harmer
0.208
316087AB2-174 GEN
Solar/Wind Harmer
1.297
970673AG2-436 GEN
Solar/Wind Harmer
18.787
970673AG2-436 GEN
Solar/Wind Harmer
9.512
941031AE2-094 GEN
Solar/Wind Harmer
16.63
944011AF1-069 GEN
Solar/Wind Harmer
5.211
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970865AG2-541 GEN
Solar/Wind Harmer
3.55
970085AG2-068 GEN
Solar/Wind Harmer
5.427
970581AG2-369 GEN
Solar/Wind Harmer
4.667
315607AA1-063A GEN
Solar/Wind Harmer
0.852
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.6
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.71
315652AC1-086 GEN
Solar/Wind Harmer
8.941
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
316123AC1-075 GEN
Solar/Wind Harmer
0.832
970165AG2-112 GEN
Solar/Wind Harmer
0.733
970163AG2-111 GEN
Solar/Wind Harmer
0.699
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316319Z2-044 C
Solar/Wind Harmer
0.41
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.217
315732AD1-074 GEN1
Solar/Wind Harmer
1.475
315733AD1-074 GEN2
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.737
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316349AD2-085 GEN
Solar/Wind Harmer
0.645
315816AE2-034 GEN
Solar/Wind Harmer
0.587
316311AC2-079 GEN
Solar/Wind Harmer
3.659
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.779
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
316321Z2-027
Solar/Wind Harmer
0.193
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.193
316420AA1-050 GEN
Solar/Wind Harmer
0.816
316305AF2-043 C
Solar/Wind Harmer
0.215
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
3151081ELIZAR1
Adder
5.776
3151091ELIZAR2
Adder
5.675
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.681
3152601GOSPORTA
Adder
0.628
972265AH1-717 GEN
Adder
4.706
3151201GRAVEL4
Adder
4.411
3151191GRAVEL3
Adder
4.355
3151211GRAVEL5
Adder
4.355
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
316246AF1-032 C
Solar/Wind Harmer
0.144
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
944591AF1-124 GEN
Solar/Wind Harmer
32.454
3150981CHESPKA
Adder
0.786
3151171GRAVELC
Adder
0.645
3143096IRON208
Adder
0.253
944631AF1-128 GEN
Adder
26.841
316192AB2-158 GEN
Solar/Wind Helper
1.013
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.573
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.107
MECLTFEXP_MEC->PJM
CLTF
0.537
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CPLELTFEXP_CPLE->PJM
CLTF
4.206
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.627
LAGNLTFEXP_LAGN->PJM
CLTF
1.959
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.437
TVALTFEXP_TVA->PJM
CLTF
0.967
NYPJM->LTFIMP_NY
CLTF
0.612
LGEELTFEXP_LGEE->PJM
CLTF
0.133
WECLTFEXP_WEC->PJM
CLTF
0.061

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:182.39 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1475.54
MW Contribution:2.11
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.704
3144293JTRSVLE
50/50
0.593
970535AG2-341 GEN
50/50
2.107
971489AH1-241 GEN
Solar/Wind Harmer
26.992
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.547
970301AG2-198 GEN
Solar/Wind Harmer
12.599
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.704
970221AG2-151 GEN
Solar/Wind Harmer
28.431
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.296
316313AB2-026
Solar/Wind Harmer
0.761
316258AE1-075 C
Solar/Wind Harmer
0.685
316405AF2-144 C
Solar/Wind Harmer
0.723
3143336POWHATN
Solar/Wind Harmer
2.847
970909AG2-566 GEN
Solar/Wind Harmer
2.392
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.484
963181AG1-167 GEN
Solar/Wind Harmer
2.197
959311AF2-222 GEN
Solar/Wind Harmer
20.924
970257AG2-171 GEN
Solar/Wind Harmer
7.297
315785AD2-033 C
Solar/Wind Harmer
4.227
964241AG1-285 GEN
Solar/Wind Harmer
12.89
316131AB2-060 GEN
Solar/Wind Harmer
1.639
958131AF2-107 GEN
Solar/Wind Harmer
4.847
316478AD1-087 GEN
Solar/Wind Harmer
1.065
316486AD2-202 GEN
Solar/Wind Harmer
0.312
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.31
972205AH1-687 GEN
50/50
20.633
316303AF2-085
50/50
2.054
971447AH1-217 GEN
Solar/Wind Harmer
14.896
971845AH1-439 GEN
Solar/Wind Harmer
21.465
970285AG2-188 GEN
Solar/Wind Harmer
34.19
270494AE1-108_GEN
Solar/Wind Harmer
9.286
315657AE1-056 GEN
Solar/Wind Harmer
9.291
946301AF1-294 GEN
Solar/Wind Harmer
6.004
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
16.8
970681AG2-440 GEN
Solar/Wind Harmer
13.44
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.796
316239AB2-077_GEN
Solar/Wind Harmer
0.439
316238AB2-078_GEN
Solar/Wind Harmer
0.439
316118AC1-105 GEN
Solar/Wind Harmer
0.773
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.769
971283AH1-107 GEN
Solar/Wind Harmer
1.769
970831AG2-522 GEN
Solar/Wind Harmer
5.308
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.09
960061AF2-297 GEN
Solar/Wind Harmer
5.143
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.986
313506AB2-031 GEN
Solar/Wind Harmer
0.724
970917AG2-570 GEN
Solar/Wind Harmer
21.795
3150861SPRUNCD
Adder
0.344
316365GEN2_N
Solar/Wind Harmer
0.555
3156081AA2-088 GEN
Solar/Wind Harmer
2.585
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.185
961681AG1-008 GEN
Solar/Wind Harmer
6.185
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146173TUNIS
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.125
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.963
316317KELFORD C
Solar/Wind Harmer
0.363
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.766
315724AD1-057 GEN
Solar/Wind Harmer
0.43
3145273HOLLAND
Solar/Wind Harmer
-0.006
3156021HOLLOMANSOL
Solar/Wind Harmer
1.002
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.587
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
1.186
315839AE2-212 C
Solar/Wind Harmer
0.22
970661AG2-428 GEN
Solar/Wind Harmer
1.373
315737AD1-076 GEN
Solar/Wind Harmer
1.386
316283AC2-100 C
Solar/Wind Harmer
0.686
971157AH1-035 GEN
Solar/Wind Harmer
0.911
315614AA2-178 GEN
Solar/Wind Harmer
0.783
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.858
3146516WINFALL
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.896
316435W1029_GEN3
Solar/Wind Harmer
1.299
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.419
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.891
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151101ELIZAR3
Adder
5.85
3151221GRAVEL6
Adder
4.406
3151171GRAVELC
Adder
0.848
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.339
3148013FISHERV
Solar/Wind Helper
0.13
315616AA1-038_C
Solar/Wind Helper
0.528
944581AF1-123 GEN
Solar/Wind Harmer
20.452
958211AF2-115 GEN
Solar/Wind Harmer
3.661
963191AG1-168 GEN
Solar/Wind Harmer
2.197
971741AH1-377 GEN
Solar/Wind Harmer
26.527
316034AC1-036 C
Solar/Wind Harmer
0.361
970323AG2-213 GEN
Solar/Wind Harmer
9.729
971775AH1-396 GEN
Solar/Wind Harmer
1.386
313527AB2-043 GEN
Solar/Wind Harmer
2.416
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.096
939181AE1-148 GEN
Solar/Wind Harmer
7.013
970099AG2-077 GEN
Solar/Wind Harmer
15.412
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.821
972187AH1-678 GEN
Adder
2.289
316181AB2-040 GEN
Solar/Wind Harmer
1.257
972185AH1-677 GEN
Adder
4.486
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.855
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.79
316222AC1-221 GEN
Solar/Wind Harmer
0.745
316065AD1-022 GEN
Solar/Wind Harmer
3.665
970657AG2-426 GEN
Solar/Wind Harmer
2.282
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
3.387
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.822
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.781
966001AG1-469 GEN
Solar/Wind Helper
0.216
946281AF1-292 GEN
Solar/Wind Harmer
0.208
316087AB2-174 GEN
Solar/Wind Harmer
1.297
970673AG2-436 GEN
Solar/Wind Harmer
18.787
970673AG2-436 GEN
Solar/Wind Harmer
9.512
941031AE2-094 GEN
Solar/Wind Harmer
16.63
944011AF1-069 GEN
Solar/Wind Harmer
5.211
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970865AG2-541 GEN
Solar/Wind Harmer
3.55
970085AG2-068 GEN
Solar/Wind Harmer
5.427
970581AG2-369 GEN
Solar/Wind Harmer
4.667
315607AA1-063A GEN
Solar/Wind Harmer
0.852
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.6
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.71
315652AC1-086 GEN
Solar/Wind Harmer
8.941
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
316123AC1-075 GEN
Solar/Wind Harmer
0.832
970165AG2-112 GEN
Solar/Wind Harmer
0.733
970163AG2-111 GEN
Solar/Wind Harmer
0.699
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316319Z2-044 C
Solar/Wind Harmer
0.41
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.217
315732AD1-074 GEN1
Solar/Wind Harmer
1.475
315733AD1-074 GEN2
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.737
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316349AD2-085 GEN
Solar/Wind Harmer
0.645
315816AE2-034 GEN
Solar/Wind Harmer
0.587
316311AC2-079 GEN
Solar/Wind Harmer
3.659
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.779
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.193
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.193
316305AF2-043 C
Solar/Wind Harmer
0.215
316420AA1-050 GEN
Solar/Wind Harmer
0.816
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
3151081ELIZAR1
Adder
5.776
3151091ELIZAR2
Adder
5.675
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.681
3152601GOSPORTA
Adder
0.628
972265AH1-717 GEN
Adder
4.706
3151201GRAVEL4
Adder
4.411
3151191GRAVEL3
Adder
4.355
3151211GRAVEL5
Adder
4.355
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
3151931BEARGRDN S1
50/50
5.46
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.704
970119AG2-088 GEN
50/50
15.406
972003AH1-546 GEN
Solar/Wind Harmer
24.587
971377AH1-170 GEN
Solar/Wind Harmer
5.686
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.517
316322AB2-045
Solar/Wind Harmer
1.382
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.597
3143336POWHATN
Solar/Wind Harmer
3.349
963171AG1-166 GEN
Solar/Wind Harmer
2.929
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
18.817
962491AG1-098 GEN
Solar/Wind Harmer
10.277
315693AD1-088 GEN
Solar/Wind Harmer
7.416
316237AB2-079_GEN
Solar/Wind Harmer
0.439
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.531
970401AG2-262 GEN
Solar/Wind Harmer
0.797
315687AD1-152 GEN
Solar/Wind Harmer
1.353
971065AG2-659 GEN
Solar/Wind Harmer
5.503
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.948
971795AH1-408 GEN
Solar/Wind Harmer
7.828
316003AC1-222 GEN
Solar/Wind Harmer
0.95
960081AF2-299 GEN
Solar/Wind Harmer
1.043
970919AG2-571 GEN
Solar/Wind Harmer
2.759
970087AG2-069 GEN
Solar/Wind Harmer
8.141
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
940641AE2-051 GEN
Solar/Wind Harmer
7.878
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.555
939411AE1-173 GEN
Solar/Wind Harmer
40.398
316011AB1-132 GEN
Solar/Wind Harmer
1.663
962571AG1-106 GEN
Solar/Wind Harmer
1.142
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.68
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.782
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.838
970659AG2-427 GEN
Solar/Wind Harmer
3.885
316381AD1-082 GEN
Solar/Wind Harmer
0.67
970661AG2-428 GEN
Solar/Wind Harmer
7.748
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.803
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.974
316049AB1-081 GEN
Solar/Wind Harmer
0.78
316093AE2-104_GEN
Solar/Wind Harmer
2.1
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
315800Z1-036_GEN1
Solar/Wind Harmer
1.779
316174AB2-169 GEN
Solar/Wind Harmer
1.109
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
316246AF1-032 C
Solar/Wind Harmer
0.144
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
944591AF1-124 GEN
Solar/Wind Harmer
32.454
3150981CHESPKA
Adder
0.786
3151171GRAVELC
Adder
0.645
3143096IRON208
Adder
0.253
944631AF1-128 GEN
Adder
26.842
316192AB2-158 GEN
Solar/Wind Helper
1.014
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.572
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.107
MECLTFEXP_MEC->PJM
CLTF
0.537
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CPLELTFEXP_CPLE->PJM
CLTF
4.206
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.626
LAGNLTFEXP_LAGN->PJM
CLTF
1.959
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.437
TVALTFEXP_TVA->PJM
CLTF
0.967
NYPJM->LTFIMP_NY
CLTF
0.612
LGEELTFEXP_LGEE->PJM
CLTF
0.133
WECLTFEXP_WEC->PJM
CLTF
0.061

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:174.94 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1415.27
MW Contribution:2.03
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.533
3151911BEARGRDN G1
50/50
4.287
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
18.19
972003AH1-546 GEN
Solar/Wind Harmer
24.898
971377AH1-170 GEN
Solar/Wind Harmer
5.763
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.282
316322AB2-045
Solar/Wind Harmer
1.394
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.86
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
963171AG1-166 GEN
Solar/Wind Harmer
2.905
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
18.606
3143226MDLTHAN
Solar/Wind Harmer
-0.015
962491AG1-098 GEN
Solar/Wind Harmer
9.894
315693AD1-088 GEN
Solar/Wind Harmer
7.12
316237AB2-079_GEN
Solar/Wind Harmer
0.427
3143526WINTERP
Solar/Wind Harmer
-0.065
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.362
315687AD1-152 GEN
Solar/Wind Harmer
1.282
971065AG2-659 GEN
Solar/Wind Harmer
5.251
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.904
971795AH1-408 GEN
Solar/Wind Harmer
7.449
3150851SPRUNCC
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.906
960081AF2-299 GEN
Solar/Wind Harmer
0.983
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
970919AG2-571 GEN
Solar/Wind Harmer
2.482
970087AG2-069 GEN
Solar/Wind Harmer
7.326
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.518
940641AE2-051 GEN
Solar/Wind Harmer
6.973
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.551
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
316212AC1-099_GEN
Solar/Wind Harmer
0.635
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.08
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
5.319
970659AG2-427 GEN
Solar/Wind Harmer
3.71
316381AD1-082 GEN
Solar/Wind Harmer
0.639
315722AD1-056 GEN
Solar/Wind Harmer
0.728
970661AG2-428 GEN
Solar/Wind Harmer
7.356
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
970129AG2-093 GEN
Solar/Wind Harmer
1.536
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316458AB2-190 GEN2
Solar/Wind Harmer
0.68
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.303
316359AB2-059 GEN
Solar/Wind Harmer
0.905
316049AB1-081 GEN
Solar/Wind Harmer
0.725
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.951
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
316174AB2-169 GEN
Solar/Wind Harmer
1.029
315800Z1-036_GEN1
Solar/Wind Harmer
1.645
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
971647AH1-324 GEN
Solar/Wind Harmer
3.305
316246AF1-032 C
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.913
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.242
3151921BEARGRDN G2
50/50
4.287
3144293JTRSVLE
50/50
0.699
970221AG2-151 GEN
Solar/Wind Harmer
28.817
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.807
316258AE1-075 C
Solar/Wind Harmer
0.726
316405AF2-144 C
Solar/Wind Harmer
0.766
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.288
970909AG2-566 GEN
Solar/Wind Harmer
2.372
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.388
963181AG1-167 GEN
Solar/Wind Harmer
2.179
959311AF2-222 GEN
Solar/Wind Harmer
20.632
970257AG2-171 GEN
Solar/Wind Harmer
7.186
315785AD2-033 C
Solar/Wind Harmer
4.155
964241AG1-285 GEN
Solar/Wind Harmer
12.598
972205AH1-687 GEN
50/50
20.91
316303AF2-085
50/50
2.425
971447AH1-217 GEN
Solar/Wind Harmer
15.108
971845AH1-439 GEN
Solar/Wind Harmer
21.634
970285AG2-188 GEN
Solar/Wind Harmer
34.428
270494AE1-108_GEN
Solar/Wind Harmer
9.407
315657AE1-056 GEN
Solar/Wind Harmer
9.233
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
16.612
970681AG2-440 GEN
Solar/Wind Harmer
13.29
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.737
316239AB2-077_GEN
Solar/Wind Harmer
0.427
316238AB2-078_GEN
Solar/Wind Harmer
0.427
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316118AC1-105 GEN
Solar/Wind Harmer
0.741
970831AG2-522 GEN
Solar/Wind Harmer
5.054
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
946281AF1-292 GEN
Solar/Wind Harmer
0.196
971967AH1-528 GEN
Solar/Wind Harmer
16.369
316087AB2-174 GEN
Solar/Wind Harmer
1.222
970865AG2-541 GEN
Solar/Wind Harmer
3.392
316131AB2-060 GEN
Solar/Wind Harmer
1.595
958131AF2-107 GEN
Solar/Wind Harmer
4.893
316478AD1-087 GEN
Solar/Wind Harmer
1.01
316486AD2-202 GEN
Solar/Wind Harmer
0.296
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.904
3150861SPRUNCD
Adder
0.382
971683AH1-343 GEN
Solar/Wind Harmer
3.805
966621AG1-532 GEN
Solar/Wind Harmer
0.177
313506AB2-031 GEN
Solar/Wind Harmer
0.682
970917AG2-570 GEN
Solar/Wind Harmer
19.61
316365GEN2_N
Solar/Wind Harmer
0.518
3156081AA2-088 GEN
Solar/Wind Harmer
2.417
3146263WOODLND
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.773
961681AG1-008 GEN
Solar/Wind Harmer
5.773
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316210AC1-098 GEN
Solar/Wind Harmer
1.142
3146173TUNIS
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
316140AB2-099
Solar/Wind Harmer
0.048
962331AG1-082 GEN
Solar/Wind Harmer
0.898
316317KELFORD C
Solar/Wind Harmer
0.338
3145823KELFORD
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.89
316327AA2-057 GEN
Solar/Wind Harmer
0.714
315813AE1-149 C
Solar/Wind Harmer
4.418
970659AG2-427 GEN
Solar/Wind Harmer
0.658
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
0.4
3145273HOLLAND
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
1.304
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
316388AE2-253 GEN
Solar/Wind Harmer
0.443
316375AC2-012 GEN
Solar/Wind Harmer
2.263
3150981CHESPKA
Adder
0.727
3151171GRAVELC
Adder
0.617
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.88
3147666LOUISA
Solar/Wind Helper
0.508
944591AF1-124 GEN
Solar/Wind Harmer
8.419
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.588
970535AG2-341 GEN
50/50
2.034
971489AH1-241 GEN
Solar/Wind Harmer
27.358
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.65
970301AG2-198 GEN
Solar/Wind Harmer
12.49
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.631
963191AG1-168 GEN
Solar/Wind Harmer
2.179
971741AH1-377 GEN
Solar/Wind Harmer
26.175
316034AC1-036 C
Solar/Wind Harmer
0.356
970323AG2-213 GEN
Solar/Wind Harmer
9.582
971775AH1-396 GEN
Solar/Wind Harmer
1.365
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.349
3143526WINTERP
Solar/Wind Harmer
-0.065
962561AG1-105 GEN
Solar/Wind Harmer
6.845
939181AE1-148 GEN
Solar/Wind Harmer
6.741
964791AG1-342 GEN
Solar/Wind Harmer
2.511
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.545
970933AG2-581 GEN
Solar/Wind Harmer
9.023
316181AB2-040 GEN
Solar/Wind Harmer
1.184
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.923
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.055
3145783HORNRTN
Solar/Wind Harmer
0.958
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.016
316426AA2-053 GEN
Solar/Wind Harmer
0.809
3144356SAPONY
Solar/Wind Harmer
0.264
316274AC1-208 GEN
Solar/Wind Harmer
0.799
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.235
315742AE1-103 GEN
Solar/Wind Harmer
0.736
970657AG2-426 GEN
Solar/Wind Harmer
2.172
970657AG2-426 GEN
Solar/Wind Harmer
0.454
316222AC1-221 GEN
Solar/Wind Harmer
0.698
316065AD1-022 GEN
Solar/Wind Harmer
3.4
942751AE2-291 GEN
Solar/Wind Harmer
4.316
316263AC1-034 GEN
Solar/Wind Harmer
3.148
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.622
316033AB2-134 GEN
Solar/Wind Harmer
2.144
315697AD1-025 GEN
Solar/Wind Harmer
1.345
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.2
316433W1029_GEN2
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316018AA1-139 ULT2
Solar/Wind Harmer
0.563
316017AA1-139 ULT1
Solar/Wind Harmer
0.531
316339AD2-160 GEN
Solar/Wind Harmer
0.443
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.691
3142956BIRDNECK
Solar/Wind Harmer
0.351
316316AC1-027 C
Solar/Wind Harmer
0.201
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.082
3150701DARBY 4
Adder
4.072
3150681DARBY 2
Adder
4.067
3150671DARBY 1
Adder
4.063
966001AG1-469 GEN
Solar/Wind Helper
0.202
3137643SOCKMAN
Solar/Wind Harmer
-0.033
970673AG2-436 GEN
Solar/Wind Harmer
16.777
970673AG2-436 GEN
Solar/Wind Harmer
8.495
315607AA1-063A GEN
Solar/Wind Harmer
0.8
941031AE2-094 GEN
Solar/Wind Harmer
14.78
944011AF1-069 GEN
Solar/Wind Harmer
4.631
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.884
970581AG2-369 GEN
Solar/Wind Harmer
4.201
315814AE2-033 C
Solar/Wind Harmer
7.048
316315AB2-025 C
Solar/Wind Harmer
0.204
965291AG1-394 GEN
Solar/Wind Harmer
0.664
315652AC1-086 GEN
Solar/Wind Harmer
8.34
316123AC1-075 GEN
Solar/Wind Harmer
0.797
970165AG2-112 GEN
Solar/Wind Harmer
0.701
970163AG2-111 GEN
Solar/Wind Harmer
0.669
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.381
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.985
315833AF1-017_GEN
Solar/Wind Harmer
1.293
316349AD2-085 GEN
Solar/Wind Harmer
0.606
316311AC2-079 GEN
Solar/Wind Harmer
3.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.367
315733AD1-074 GEN2
Solar/Wind Harmer
1.367
315735AD1-075 GEN1
Solar/Wind Harmer
0.684
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.68
315816AE2-034 GEN
Solar/Wind Harmer
0.544
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.645
316369SG1_INVT
Solar/Wind Harmer
1.188
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.757
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.895
316321Z2-027
Solar/Wind Harmer
0.178
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
316305AF2-043 C
Solar/Wind Harmer
0.199
313526AB2-022
Solar/Wind Harmer
0.178
316005AA1-067
Solar/Wind Harmer
0.133
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.865
3146406KITTY HAWK
Solar/Wind Harmer
0.005
319010AE1-072 C
Solar/Wind Harmer
1.33
957871AF2-081 GEN
Solar/Wind Harmer
3.284
3152611GOSPORTB
Adder
0.742
3152621GOSPORTC
Adder
0.629
3152601GOSPORTA
Adder
0.581
3151081ELIZAR1
Adder
5.335
3151091ELIZAR2
Adder
5.243
972265AH1-717 GEN
Adder
4.506
3151201GRAVEL4
Adder
4.224
3151191GRAVEL3
Adder
4.17
3151211GRAVEL5
Adder
4.17
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
315737AD1-076 GEN
Solar/Wind Harmer
1.285
971157AH1-035 GEN
Solar/Wind Harmer
0.844
970129AG2-093 GEN
Solar/Wind Harmer
3.791
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.725
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.787
961601AG1-000A GEN
Solar/Wind Harmer
2.655
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.827
316320Y1-086
Solar/Wind Harmer
0.387
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.801
961611AG1-000B GEN
Solar/Wind Harmer
1.383
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.404
3151221GRAVEL6
Adder
4.219
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
315616AA1-038_C
Solar/Wind Helper
0.514
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.055
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.782
MECLTFEXP_MEC->PJM
CLTF
0.452
SIGELTFEXP_SIGE->PJM
CLTF
0.012
CPLELTFEXP_CPLE->PJM
CLTF
3.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.641
LAGNLTFEXP_LAGN->PJM
CLTF
1.764
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.761
TVALTFEXP_TVA->PJM
CLTF
0.87
NYPJM->LTFIMP_NY
CLTF
0.577
LGEELTFEXP_LGEE->PJM
CLTF
0.104
WECLTFEXP_WEC->PJM
CLTF
0.046

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:174.94 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1415.27
MW Contribution:2.03
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.533
3151911BEARGRDN G1
50/50
4.287
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
18.19
972003AH1-546 GEN
Solar/Wind Harmer
24.898
971377AH1-170 GEN
Solar/Wind Harmer
5.763
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.282
316322AB2-045
Solar/Wind Harmer
1.394
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.86
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
963171AG1-166 GEN
Solar/Wind Harmer
2.905
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
18.606
3143226MDLTHAN
Solar/Wind Harmer
-0.015
962491AG1-098 GEN
Solar/Wind Harmer
9.894
315693AD1-088 GEN
Solar/Wind Harmer
7.12
316237AB2-079_GEN
Solar/Wind Harmer
0.427
3143526WINTERP
Solar/Wind Harmer
-0.065
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.362
315687AD1-152 GEN
Solar/Wind Harmer
1.282
971065AG2-659 GEN
Solar/Wind Harmer
5.251
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.904
971795AH1-408 GEN
Solar/Wind Harmer
7.449
3150851SPRUNCC
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.906
960081AF2-299 GEN
Solar/Wind Harmer
0.983
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
970919AG2-571 GEN
Solar/Wind Harmer
2.482
970087AG2-069 GEN
Solar/Wind Harmer
7.326
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.518
940641AE2-051 GEN
Solar/Wind Harmer
6.973
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.551
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
316212AC1-099_GEN
Solar/Wind Harmer
0.635
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.08
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
5.319
970659AG2-427 GEN
Solar/Wind Harmer
3.71
316381AD1-082 GEN
Solar/Wind Harmer
0.639
315722AD1-056 GEN
Solar/Wind Harmer
0.728
970661AG2-428 GEN
Solar/Wind Harmer
7.356
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
970129AG2-093 GEN
Solar/Wind Harmer
1.536
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316458AB2-190 GEN2
Solar/Wind Harmer
0.68
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.303
316359AB2-059 GEN
Solar/Wind Harmer
0.905
316049AB1-081 GEN
Solar/Wind Harmer
0.725
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.951
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
316174AB2-169 GEN
Solar/Wind Harmer
1.029
315800Z1-036_GEN1
Solar/Wind Harmer
1.645
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3151921BEARGRDN G2
50/50
4.287
3144293JTRSVLE
50/50
0.699
970221AG2-151 GEN
Solar/Wind Harmer
28.817
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.807
316258AE1-075 C
Solar/Wind Harmer
0.726
316405AF2-144 C
Solar/Wind Harmer
0.766
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.288
970909AG2-566 GEN
Solar/Wind Harmer
2.372
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.388
963181AG1-167 GEN
Solar/Wind Harmer
2.179
959311AF2-222 GEN
Solar/Wind Harmer
20.632
970257AG2-171 GEN
Solar/Wind Harmer
7.186
315785AD2-033 C
Solar/Wind Harmer
4.155
964241AG1-285 GEN
Solar/Wind Harmer
12.598
316131AB2-060 GEN
Solar/Wind Harmer
1.595
958131AF2-107 GEN
Solar/Wind Harmer
4.893
316478AD1-087 GEN
Solar/Wind Harmer
1.01
316486AD2-202 GEN
Solar/Wind Harmer
0.296
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.904
3150861SPRUNCD
Adder
0.382
971683AH1-343 GEN
Solar/Wind Harmer
3.805
966621AG1-532 GEN
Solar/Wind Harmer
0.177
313506AB2-031 GEN
Solar/Wind Harmer
0.682
970917AG2-570 GEN
Solar/Wind Harmer
19.61
316365GEN2_N
Solar/Wind Harmer
0.518
3156081AA2-088 GEN
Solar/Wind Harmer
2.417
3146263WOODLND
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.773
961681AG1-008 GEN
Solar/Wind Harmer
5.773
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316210AC1-098 GEN
Solar/Wind Harmer
1.142
3146173TUNIS
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
316140AB2-099
Solar/Wind Harmer
0.048
962331AG1-082 GEN
Solar/Wind Harmer
0.898
316317KELFORD C
Solar/Wind Harmer
0.338
3145823KELFORD
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.89
316327AA2-057 GEN
Solar/Wind Harmer
0.714
315813AE1-149 C
Solar/Wind Harmer
4.418
970659AG2-427 GEN
Solar/Wind Harmer
0.658
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
0.4
3145273HOLLAND
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
1.304
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315737AD1-076 GEN
Solar/Wind Harmer
1.285
971157AH1-035 GEN
Solar/Wind Harmer
0.844
970129AG2-093 GEN
Solar/Wind Harmer
3.791
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.725
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.787
961601AG1-000A GEN
Solar/Wind Harmer
2.655
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.827
316320Y1-086
Solar/Wind Harmer
0.387
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.801
961611AG1-000B GEN
Solar/Wind Harmer
1.383
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.404
3151221GRAVEL6
Adder
4.219
972205AH1-687 GEN
50/50
20.91
316303AF2-085
50/50
2.425
971447AH1-217 GEN
Solar/Wind Harmer
15.108
971845AH1-439 GEN
Solar/Wind Harmer
21.634
970285AG2-188 GEN
Solar/Wind Harmer
34.428
270494AE1-108_GEN
Solar/Wind Harmer
9.407
315657AE1-056 GEN
Solar/Wind Harmer
9.233
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
16.612
970681AG2-440 GEN
Solar/Wind Harmer
13.29
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.737
316239AB2-077_GEN
Solar/Wind Harmer
0.427
316238AB2-078_GEN
Solar/Wind Harmer
0.427
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316118AC1-105 GEN
Solar/Wind Harmer
0.741
970831AG2-522 GEN
Solar/Wind Harmer
5.054
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
946281AF1-292 GEN
Solar/Wind Harmer
0.196
971967AH1-528 GEN
Solar/Wind Harmer
16.369
316087AB2-174 GEN
Solar/Wind Harmer
1.222
970865AG2-541 GEN
Solar/Wind Harmer
3.392
3137643SOCKMAN
Solar/Wind Harmer
-0.033
970673AG2-436 GEN
Solar/Wind Harmer
16.777
970673AG2-436 GEN
Solar/Wind Harmer
8.495
315607AA1-063A GEN
Solar/Wind Harmer
0.8
941031AE2-094 GEN
Solar/Wind Harmer
14.78
944011AF1-069 GEN
Solar/Wind Harmer
4.631
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.884
970581AG2-369 GEN
Solar/Wind Harmer
4.201
315814AE2-033 C
Solar/Wind Harmer
7.048
316315AB2-025 C
Solar/Wind Harmer
0.204
965291AG1-394 GEN
Solar/Wind Harmer
0.664
315652AC1-086 GEN
Solar/Wind Harmer
8.34
316123AC1-075 GEN
Solar/Wind Harmer
0.797
970165AG2-112 GEN
Solar/Wind Harmer
0.701
970163AG2-111 GEN
Solar/Wind Harmer
0.669
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
971647AH1-324 GEN
Solar/Wind Harmer
3.305
316246AF1-032 C
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.913
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.242
316388AE2-253 GEN
Solar/Wind Harmer
0.443
316375AC2-012 GEN
Solar/Wind Harmer
2.263
3150981CHESPKA
Adder
0.727
3151171GRAVELC
Adder
0.617
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.88
3147666LOUISA
Solar/Wind Helper
0.508
944591AF1-124 GEN
Solar/Wind Harmer
8.419
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.588
970535AG2-341 GEN
50/50
2.034
971489AH1-241 GEN
Solar/Wind Harmer
27.358
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.65
970301AG2-198 GEN
Solar/Wind Harmer
12.49
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.631
963191AG1-168 GEN
Solar/Wind Harmer
2.179
971741AH1-377 GEN
Solar/Wind Harmer
26.175
316034AC1-036 C
Solar/Wind Harmer
0.356
970323AG2-213 GEN
Solar/Wind Harmer
9.582
971775AH1-396 GEN
Solar/Wind Harmer
1.365
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.349
3143526WINTERP
Solar/Wind Harmer
-0.065
962561AG1-105 GEN
Solar/Wind Harmer
6.845
939181AE1-148 GEN
Solar/Wind Harmer
6.741
964791AG1-342 GEN
Solar/Wind Harmer
2.511
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.545
970933AG2-581 GEN
Solar/Wind Harmer
9.023
316181AB2-040 GEN
Solar/Wind Harmer
1.184
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.923
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.055
3145783HORNRTN
Solar/Wind Harmer
0.958
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.016
316426AA2-053 GEN
Solar/Wind Harmer
0.809
3144356SAPONY
Solar/Wind Harmer
0.264
316274AC1-208 GEN
Solar/Wind Harmer
0.799
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.235
315742AE1-103 GEN
Solar/Wind Harmer
0.736
970657AG2-426 GEN
Solar/Wind Harmer
2.172
970657AG2-426 GEN
Solar/Wind Harmer
0.454
316222AC1-221 GEN
Solar/Wind Harmer
0.698
316065AD1-022 GEN
Solar/Wind Harmer
3.4
942751AE2-291 GEN
Solar/Wind Harmer
4.316
316263AC1-034 GEN
Solar/Wind Harmer
3.148
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.622
316033AB2-134 GEN
Solar/Wind Harmer
2.144
315697AD1-025 GEN
Solar/Wind Harmer
1.345
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.2
316433W1029_GEN2
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316018AA1-139 ULT2
Solar/Wind Harmer
0.563
316017AA1-139 ULT1
Solar/Wind Harmer
0.531
316339AD2-160 GEN
Solar/Wind Harmer
0.443
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.691
3142956BIRDNECK
Solar/Wind Harmer
0.351
316316AC1-027 C
Solar/Wind Harmer
0.201
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.082
3150701DARBY 4
Adder
4.072
3150681DARBY 2
Adder
4.067
3150671DARBY 1
Adder
4.063
966001AG1-469 GEN
Solar/Wind Helper
0.202
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
315616AA1-038_C
Solar/Wind Helper
0.514
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.381
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.985
315833AF1-017_GEN
Solar/Wind Harmer
1.293
316349AD2-085 GEN
Solar/Wind Harmer
0.606
316311AC2-079 GEN
Solar/Wind Harmer
3.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.367
315733AD1-074 GEN2
Solar/Wind Harmer
1.367
315735AD1-075 GEN1
Solar/Wind Harmer
0.684
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.68
315816AE2-034 GEN
Solar/Wind Harmer
0.544
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.645
316369SG1_INVT
Solar/Wind Harmer
1.188
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.757
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.895
316321Z2-027
Solar/Wind Harmer
0.178
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
316305AF2-043 C
Solar/Wind Harmer
0.199
313526AB2-022
Solar/Wind Harmer
0.178
316005AA1-067
Solar/Wind Harmer
0.133
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.865
3146406KITTY HAWK
Solar/Wind Harmer
0.005
319010AE1-072 C
Solar/Wind Harmer
1.33
957871AF2-081 GEN
Solar/Wind Harmer
3.284
3152611GOSPORTB
Adder
0.742
3152621GOSPORTC
Adder
0.629
3152601GOSPORTA
Adder
0.581
3151081ELIZAR1
Adder
5.335
3151091ELIZAR2
Adder
5.243
972265AH1-717 GEN
Adder
4.506
3151201GRAVEL4
Adder
4.224
3151191GRAVEL3
Adder
4.17
3151211GRAVEL5
Adder
4.17
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.055
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.782
MECLTFEXP_MEC->PJM
CLTF
0.452
SIGELTFEXP_SIGE->PJM
CLTF
0.012
CPLELTFEXP_CPLE->PJM
CLTF
3.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.641
LAGNLTFEXP_LAGN->PJM
CLTF
1.764
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.761
TVALTFEXP_TVA->PJM
CLTF
0.87
NYPJM->LTFIMP_NY
CLTF
0.577
LGEELTFEXP_LGEE->PJM
CLTF
0.104
WECLTFEXP_WEC->PJM
CLTF
0.046

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2027_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:160.44 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:1061.7
MW Contribution:2.05
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
7.21
3151911BEARGRDN G1
50/50
5.587
3144293JTRSVLE
50/50
0.823
3151601KERR 3
50/50
0.202
3151581KERR 1
50/50
0.072
3151531CLOVER1
50/50
2.069
3147043LAWRENC
50/50
0.777
970937AG2-583 GEN
Solar/Wind Harmer
36.866
316336AC2-165 C
Solar/Wind Harmer
0.024
972003AH1-546 GEN
Solar/Wind Harmer
24.522
971377AH1-170 GEN
Solar/Wind Harmer
5.701
3147623JAMES R
Solar/Wind Harmer
1.238
316322AB2-045
Solar/Wind Harmer
0.004
3146776BUCKING
Solar/Wind Harmer
0.188
3146926FARMVIL
Solar/Wind Harmer
0.218
963171AG1-166 GEN
Solar/Wind Harmer
1.299
971563AH1-280 GEN
Solar/Wind Harmer
2.599
970685AG2-442 GEN
Solar/Wind Harmer
16.367
962491AG1-098 GEN
Solar/Wind Harmer
7.651
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
6.098
970401AG2-262 GEN
Solar/Wind Harmer
0.618
957481AF2-042 GEN
Solar/Wind Harmer
24.997
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.611
316129AC1-054 GEN
Solar/Wind Harmer
0.309
316003AC1-222 GEN
Solar/Wind Harmer
0.002
971795AH1-408 GEN
Solar/Wind Harmer
4.899
962751AG1-124 GEN
Solar/Wind Harmer
3.147
960081AF2-299 GEN
Solar/Wind Harmer
0.55
3151921BEARGRDN G2
50/50
5.587
3144293JTRSVLE
50/50
0.823
3151591KERR 2
50/50
0.202
970413AG2-270 GEN
50/50
9.029
966251AG1-494 GEN
50/50
1.716
970221AG2-151 GEN
Solar/Wind Harmer
28.504
3146776BUCKING
Solar/Wind Harmer
0.169
3146926FARMVIL
Solar/Wind Harmer
0.218
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
970909AG2-566 GEN
Solar/Wind Harmer
2.804
3147133PAMPLIN
Solar/Wind Harmer
0.818
971193AH1-056 GEN
Solar/Wind Harmer
15.872
963181AG1-167 GEN
Solar/Wind Harmer
0.975
959311AF2-222 GEN
Solar/Wind Harmer
17.841
970257AG2-171 GEN
Solar/Wind Harmer
6.184
315785AD2-033 C
Solar/Wind Harmer
1.488
958131AF2-107 GEN
Solar/Wind Harmer
4.835
964241AG1-285 GEN
Solar/Wind Harmer
10.382
316131AB2-060 GEN
Solar/Wind Harmer
0.438
316478AD1-087 GEN
Solar/Wind Harmer
0.337
316486AD2-202 GEN
Solar/Wind Harmer
0.099
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.582
3147043LAWRENC
Solar/Wind Harmer
0.049
971683AH1-343 GEN
Solar/Wind Harmer
2.828
3132273ORANGE
Solar/Wind Helper
0.023
3144293JTRSVLE
50/50
0.823
3144293JTRSVLE
50/50
0.693
970535AG2-341 GEN
50/50
2.047
3152661PLYWOOD A
50/50
0.202
971489AH1-241 GEN
Solar/Wind Harmer
28.504
3146776BUCKING
Solar/Wind Harmer
1.881
3146776BUCKING
Solar/Wind Harmer
0.152
315821AE2-092 GEN
Solar/Wind Harmer
0.02
970301AG2-198 GEN
Solar/Wind Harmer
11.214
3147133PAMPLIN
Solar/Wind Harmer
0.26
3147133PAMPLIN
Solar/Wind Harmer
0.208
958211AF2-115 GEN
Solar/Wind Harmer
2.924
963191AG1-168 GEN
Solar/Wind Harmer
0.975
971741AH1-377 GEN
Solar/Wind Harmer
22.982
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
8.246
971775AH1-396 GEN
Solar/Wind Harmer
0.309
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
5.277
964791AG1-342 GEN
Solar/Wind Harmer
2.024
3146843MT LREL
Solar/Wind Harmer
0.105
3146843MT LREL
Solar/Wind Harmer
0.105
939181AE1-148 GEN
Solar/Wind Harmer
5.007
970099AG2-077 GEN
Solar/Wind Harmer
9.999
970933AG2-581 GEN
Solar/Wind Harmer
5.154
942751AE2-291 GEN
Solar/Wind Harmer
3.374
966001AG1-469 GEN
Solar/Wind Helper
0.159
972205AH1-687 GEN
50/50
27.249
3151611KERR 4
50/50
0.202
3151621KERR 5
50/50
0.202
3151631KERR 6
50/50
0.202
3151641KERR 7
50/50
0.202
3151541CLOVER2
50/50
2.059
971447AH1-217 GEN
Solar/Wind Harmer
15.037
971845AH1-439 GEN
Solar/Wind Harmer
20.916
970285AG2-188 GEN
Solar/Wind Harmer
35.131
270494AE1-108_GEN
Solar/Wind Harmer
5.032
315657AE1-056 GEN
Solar/Wind Harmer
8.99
946301AF1-294 GEN
Solar/Wind Harmer
4.808
961791AG1-021 GEN
Solar/Wind Harmer
2.339
970683AG2-441 GEN
Solar/Wind Harmer
14.613
970681AG2-440 GEN
Solar/Wind Harmer
11.691
3144303KENBRDG
Solar/Wind Harmer
0.154
971443AH1-215 GEN
Solar/Wind Harmer
3.209
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.244
3147173SINAI
Solar/Wind Harmer
0.084
3147243WELCO
Solar/Wind Harmer
0.052
970831AG2-522 GEN
Solar/Wind Harmer
3.381
970865AG2-541 GEN
Solar/Wind Harmer
2.545
316123AC1-075 GEN
Solar/Wind Harmer
0.091
970165AG2-112 GEN
Solar/Wind Harmer
0.539
970163AG2-111 GEN
Solar/Wind Harmer
0.514
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.084
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.539
MECLTFEXP_MEC->PJM
CLTF
0.508
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CPLELTFEXP_CPLE->PJM
CLTF
2.979
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.201
LAGNLTFEXP_LAGN->PJM
CLTF
1.554
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.128
TVALTFEXP_TVA->PJM
CLTF
0.776
NYPJM->LTFIMP_NY
CLTF
0.525
LGEELTFEXP_LGEE->PJM
CLTF
0.153
WECLTFEXP_WEC->PJM
CLTF
0.071

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 242T2027_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 242T2027_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:152.15 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1230.87
MW Contribution:2.05
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
27.249
971447AH1-217 GEN
Solar/Wind Harmer
19.799
971845AH1-439 GEN
Solar/Wind Harmer
27.54
970285AG2-188 GEN
Solar/Wind Harmer
43.657
270494AE1-108_GEN
Solar/Wind Harmer
12.267
315657AE1-056 GEN
Solar/Wind Harmer
10.983
946301AF1-294 GEN
Solar/Wind Harmer
7.014
961791AG1-021 GEN
Solar/Wind Harmer
3.422
970683AG2-441 GEN
Solar/Wind Harmer
19.241
970681AG2-440 GEN
Solar/Wind Harmer
15.393
3144303KENBRDG
Solar/Wind Harmer
-0.017
971443AH1-215 GEN
Solar/Wind Harmer
4.225
316239AB2-077_GEN
Solar/Wind Harmer
0.446
3144293JTRSVLE
50/50
0.823
3144293JTRSVLE
50/50
0.693
970535AG2-341 GEN
50/50
2.047
971489AH1-241 GEN
Solar/Wind Harmer
35.629
3146776BUCKING
Solar/Wind Harmer
-0.21
3146776BUCKING
Solar/Wind Harmer
-0.017
315821AE2-092 GEN
Solar/Wind Harmer
7.77
970301AG2-198 GEN
Solar/Wind Harmer
14.765
3147133PAMPLIN
Solar/Wind Harmer
-0.029
3147133PAMPLIN
Solar/Wind Harmer
-0.023
958211AF2-115 GEN
Solar/Wind Harmer
4.277
963191AG1-168 GEN
Solar/Wind Harmer
2.566
971741AH1-377 GEN
Solar/Wind Harmer
30.26
316034AC1-036 C
Solar/Wind Harmer
0.404
970323AG2-213 GEN
Solar/Wind Harmer
10.857
971775AH1-396 GEN
Solar/Wind Harmer
1.546
313527AB2-043 GEN
Solar/Wind Harmer
2.466
962561AG1-105 GEN
Solar/Wind Harmer
6.948
964791AG1-342 GEN
Solar/Wind Harmer
2.529
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
939181AE1-148 GEN
Solar/Wind Harmer
6.592
970099AG2-077 GEN
Solar/Wind Harmer
13.165
970933AG2-581 GEN
Solar/Wind Harmer
6.786
942751AE2-291 GEN
Solar/Wind Harmer
4.443
966001AG1-469 GEN
Solar/Wind Helper
0.159
3151921BEARGRDN G2
50/50
5.587
3144293JTRSVLE
50/50
0.823
970221AG2-151 GEN
Solar/Wind Harmer
37.53
3146776BUCKING
Solar/Wind Harmer
-0.019
3146926FARMVIL
Solar/Wind Harmer
-0.024
942461AE2-259 GEN
Solar/Wind Harmer
5.218
970909AG2-566 GEN
Solar/Wind Harmer
2.804
3147133PAMPLIN
Solar/Wind Harmer
-0.092
971193AH1-056 GEN
Solar/Wind Harmer
18.305
963181AG1-167 GEN
Solar/Wind Harmer
2.566
959311AF2-222 GEN
Solar/Wind Harmer
23.538
970257AG2-171 GEN
Solar/Wind Harmer
8.143
315785AD2-033 C
Solar/Wind Harmer
4.66
958131AF2-107 GEN
Solar/Wind Harmer
6.437
964241AG1-285 GEN
Solar/Wind Harmer
13.669
316131AB2-060 GEN
Solar/Wind Harmer
1.687
316478AD1-087 GEN
Solar/Wind Harmer
0.939
316486AD2-202 GEN
Solar/Wind Harmer
0.275
316248AF1-058 C
Solar/Wind Harmer
0.284
960061AF2-297 GEN
Solar/Wind Harmer
4.717
3147043LAWRENC
Solar/Wind Harmer
-0.005
971683AH1-343 GEN
Solar/Wind Harmer
3.724
966621AG1-532 GEN
Solar/Wind Harmer
0.131
3132273ORANGE
Solar/Wind Helper
0.023
316238AB2-078_GEN
Solar/Wind Harmer
0.446
316118AC1-105 GEN
Solar/Wind Harmer
0.73
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
970831AG2-522 GEN
Solar/Wind Harmer
4.452
970865AG2-541 GEN
Solar/Wind Harmer
3.351
316123AC1-075 GEN
Solar/Wind Harmer
0.806
970165AG2-112 GEN
Solar/Wind Harmer
0.709
970163AG2-111 GEN
Solar/Wind Harmer
0.677
946281AF1-292 GEN
Solar/Wind Harmer
0.144
3138266HYDRAULIC
Solar/Wind Helper
0.016
3138266HYDRAULIC
Solar/Wind Helper
0.01
3151931BEARGRDN S1
50/50
7.21
3151911BEARGRDN G1
50/50
5.587
3144293JTRSVLE
50/50
0.823
970937AG2-583 GEN
Solar/Wind Harmer
48.541
316336AC2-165 C
Solar/Wind Harmer
11.736
972003AH1-546 GEN
Solar/Wind Harmer
32.342
971377AH1-170 GEN
Solar/Wind Harmer
7.506
3147623JAMES R
Solar/Wind Harmer
0.929
316322AB2-045
Solar/Wind Harmer
1.778
3146776BUCKING
Solar/Wind Harmer
-0.021
3146926FARMVIL
Solar/Wind Harmer
-0.024
963171AG1-166 GEN
Solar/Wind Harmer
3.422
971563AH1-280 GEN
Solar/Wind Harmer
3.422
970685AG2-442 GEN
Solar/Wind Harmer
21.55
962491AG1-098 GEN
Solar/Wind Harmer
10.074
316237AB2-079_GEN
Solar/Wind Harmer
0.446
315693AD1-088 GEN
Solar/Wind Harmer
7.137
970401AG2-262 GEN
Solar/Wind Harmer
0.773
957481AF2-042 GEN
Solar/Wind Harmer
32.913
315687AD1-152 GEN
Solar/Wind Harmer
1.189
971065AG2-659 GEN
Solar/Wind Harmer
4.755
316129AC1-054 GEN
Solar/Wind Harmer
0.808
3147043LAWRENC
Adder
0.732
316003AC1-222 GEN
Solar/Wind Harmer
0.879
971795AH1-408 GEN
Solar/Wind Harmer
6.192
962751AG1-124 GEN
Solar/Wind Harmer
4.595
960081AF2-299 GEN
Solar/Wind Harmer
0.724
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.084
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.539
MECLTFEXP_MEC->PJM
CLTF
0.508
SIGELTFEXP_SIGE->PJM
CLTF
0.014
CPLELTFEXP_CPLE->PJM
CLTF
2.979
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.201
LAGNLTFEXP_LAGN->PJM
CLTF
1.554
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.128
TVALTFEXP_TVA->PJM
CLTF
0.776
NYPJM->LTFIMP_NY
CLTF
0.525
LGEELTFEXP_LGEE->PJM
CLTF
0.153
WECLTFEXP_WEC->PJM
CLTF
0.071

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.36 %
Rating:661.76 MVA
Rating Type:A
MVA to Mitigate:697.23
MW Contribution:1.77
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.314
3151911BEARGRDN G1
50/50
4.118
3144293JTRSVLE
50/50
0.644
3151531CLOVER1
50/50
1.885
3151601KERR 3
50/50
0.18
3151581KERR 1
50/50
0.064
970119AG2-088 GEN
50/50
11.599
3147043LAWRENC
50/50
0.746
3151261ROARAP2
50/50
0.072
972003AH1-546 GEN
Solar/Wind Harmer
18.108
971377AH1-170 GEN
Solar/Wind Harmer
4.203
3147623JAMES R
Solar/Wind Harmer
0.913
970937AG2-583 GEN
Solar/Wind Harmer
22.204
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.14
3146926FARMVIL
Solar/Wind Harmer
0.165
316336AC2-165 C
Solar/Wind Harmer
0.01
3143336POWHATN
Solar/Wind Harmer
4.074
963171AG1-166 GEN
Solar/Wind Harmer
1.017
971563AH1-280 GEN
Solar/Wind Harmer
2.035
970685AG2-442 GEN
Solar/Wind Harmer
12.945
962491AG1-098 GEN
Solar/Wind Harmer
6.577
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
5.296
970401AG2-262 GEN
Solar/Wind Harmer
0.531
957481AF2-042 GEN
Solar/Wind Harmer
23.244
3143226MDLTHAN
Solar/Wind Harmer
0.087
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.352
316129AC1-054 GEN
Solar/Wind Harmer
0.289
971795AH1-408 GEN
Solar/Wind Harmer
4.849
3143526WINTERP
Solar/Wind Harmer
0.377
3144293JTRSVLE
50/50
0.644
3144293JTRSVLE
50/50
0.543
970535AG2-341 GEN
50/50
1.768
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.595
3145783HORNRTN
Solar/Wind Harmer
0.057
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.752
972205AH1-687 GEN
50/50
20.083
3151541CLOVER2
50/50
1.876
3151611KERR 4
50/50
0.18
3151621KERR 5
50/50
0.18
3151631KERR 6
50/50
0.18
3151641KERR 7
50/50
0.18
316303AF2-085
50/50
1.546
3151281ROARAP4
50/50
0.07
3151281ROARAP4
50/50
0.066
971447AH1-217 GEN
Solar/Wind Harmer
11.004
971845AH1-439 GEN
Solar/Wind Harmer
15.632
970285AG2-188 GEN
Solar/Wind Harmer
26.316
270494AE1-108_GEN
Solar/Wind Harmer
3.693
315657AE1-056 GEN
Solar/Wind Harmer
6.997
946301AF1-294 GEN
Solar/Wind Harmer
3.764
961791AG1-021 GEN
Solar/Wind Harmer
1.831
970683AG2-441 GEN
Solar/Wind Harmer
11.558
970681AG2-440 GEN
Solar/Wind Harmer
9.247
3144303KENBRDG
Solar/Wind Harmer
0.124
971443AH1-215 GEN
Solar/Wind Harmer
2.576
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.212
970831AG2-522 GEN
Solar/Wind Harmer
3.201
3147173SINAI
Solar/Wind Harmer
0.074
3147243WELCO
Solar/Wind Harmer
0.046
316233AE1-074 FULL
Solar/Wind Harmer
0.058
971281AH1-106 GEN
Solar/Wind Harmer
1.006
971283AH1-107 GEN
Solar/Wind Harmer
1.006
970865AG2-541 GEN
Solar/Wind Harmer
2.17
316087AB2-174 GEN
Solar/Wind Harmer
0.002
971967AH1-528 GEN
Solar/Wind Harmer
9.597
3137643SOCKMAN
Solar/Wind Harmer
0.235
3138266HYDRAULIC
Solar/Wind Helper
0.021
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.08
3148013FISHERV
Solar/Wind Helper
0.077
3148463FAIRFLD
Solar/Wind Helper
0.119
3152661PLYWOOD A
50/50
0.177
971489AH1-241 GEN
Solar/Wind Harmer
21.013
3146776BUCKING
Solar/Wind Harmer
1.404
3146776BUCKING
Solar/Wind Harmer
0.114
315821AE2-092 GEN
Solar/Wind Harmer
0.014
970301AG2-198 GEN
Solar/Wind Harmer
8.767
3147133PAMPLIN
Solar/Wind Harmer
0.203
3147133PAMPLIN
Solar/Wind Harmer
0.162
958211AF2-115 GEN
Solar/Wind Harmer
2.289
963191AG1-168 GEN
Solar/Wind Harmer
0.763
971741AH1-377 GEN
Solar/Wind Harmer
18.217
316034AC1-036 C
Solar/Wind Harmer
0.011
970323AG2-213 GEN
Solar/Wind Harmer
6.61
971775AH1-396 GEN
Solar/Wind Harmer
0.248
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
4.515
939181AE1-148 GEN
Solar/Wind Harmer
4.407
964791AG1-342 GEN
Solar/Wind Harmer
1.738
3146843MT LREL
Solar/Wind Harmer
0.09
3146843MT LREL
Solar/Wind Harmer
0.09
970099AG2-077 GEN
Solar/Wind Harmer
9.298
971223AH1-071 GEN
Solar/Wind Harmer
0.928
3143526WINTERP
Solar/Wind Harmer
0.377
970933AG2-581 GEN
Solar/Wind Harmer
5.476
316181AB2-040 GEN
Solar/Wind Harmer
0.087
3145593CAROLNA
Solar/Wind Harmer
0.058
3145593CAROLNA
Solar/Wind Harmer
0.058
966811AG1-552 GEN
Solar/Wind Harmer
0.627
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.01
3145783HORNRTN
Solar/Wind Harmer
0.808
3145783HORNRTN
Solar/Wind Harmer
0.253
3145783HORNRTN
Solar/Wind Harmer
0.101
966001AG1-469 GEN
Solar/Wind Helper
0.19
3151921BEARGRDN G2
50/50
4.118
3144293JTRSVLE
50/50
0.644
970413AG2-270 GEN
50/50
8.224
3151591KERR 2
50/50
0.18
966251AG1-494 GEN
50/50
1.173
3151261ROARAP2
50/50
0.07
970221AG2-151 GEN
Solar/Wind Harmer
21.013
3146776BUCKING
Solar/Wind Harmer
0.126
3146926FARMVIL
Solar/Wind Harmer
0.165
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.144
316258AE1-075 C
Solar/Wind Harmer
0.173
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.463
970909AG2-566 GEN
Solar/Wind Harmer
2.192
3147133PAMPLIN
Solar/Wind Harmer
0.637
971193AH1-056 GEN
Solar/Wind Harmer
12.353
963181AG1-167 GEN
Solar/Wind Harmer
0.763
959311AF2-222 GEN
Solar/Wind Harmer
14.242
970257AG2-171 GEN
Solar/Wind Harmer
4.957
315785AD2-033 C
Solar/Wind Harmer
1.2
964241AG1-285 GEN
Solar/Wind Harmer
8.548
958131AF2-107 GEN
Solar/Wind Harmer
3.44
316131AB2-060 GEN
Solar/Wind Harmer
0.366
316478AD1-087 GEN
Solar/Wind Harmer
0.307
316486AD2-202 GEN
Solar/Wind Harmer
0.09
3147043LAWRENC
Solar/Wind Harmer
0.047
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.155
971683AH1-343 GEN
Solar/Wind Harmer
2.44
313506AB2-031 GEN
Solar/Wind Harmer
0.186
316499AE2-029_GEN
Solar/Wind Helper
0.505
3148013FISHERV
Solar/Wind Helper
0.133
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.54
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.673
MECLTFEXP_MEC->PJM
CLTF
0.138
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CPLELTFEXP_CPLE->PJM
CLTF
2.992
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.238
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.029
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.072
LAGNLTFEXP_LAGN->PJM
CLTF
1.122
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.815
TVALTFEXP_TVA->PJM
CLTF
0.547
NYPJM->LTFIMP_NY
CLTF
0.391

Details for 6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.64 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:893.44
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3147043LAWRENC
50/50
3.141
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.27
3151581KERR 1
50/50
0.096
3144293JTRSVLE
50/50
0.305
3151531CLOVER1
50/50
1.558
316023GEN1_S
Solar/Wind Harmer
1.155
960081AF2-299 GEN
Solar/Wind Harmer
3.965
971795AH1-408 GEN
Solar/Wind Harmer
23.615
316011AB1-132 GEN
Solar/Wind Harmer
6.186
962571AG1-106 GEN
Solar/Wind Harmer
4.841
3145796HORNRTN
Solar/Wind Harmer
1.046
3145796HORNRTN
Solar/Wind Harmer
0.317
3145783HORNRTN
Solar/Wind Harmer
0.249
315722AD1-056 GEN
Solar/Wind Harmer
1.531
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
1.015
3146263WOODLND
Solar/Wind Harmer
0.191
3146233WITAKRS
Solar/Wind Harmer
0.73
3145823KELFORD
Solar/Wind Harmer
0.177
316359AB2-059 GEN
Solar/Wind Harmer
0.634
316049AB1-081 GEN
Solar/Wind Harmer
1.01
3142053HEARTS
Solar/Wind Harmer
0.311
3145543BTLEBRO
Solar/Wind Harmer
0.175
3145543BTLEBRO
Solar/Wind Harmer
0.14
316129AC1-054 GEN
Solar/Wind Harmer
0.656
971065AG2-659 GEN
Solar/Wind Harmer
7.13
3145683EARLEYS
Solar/Wind Harmer
0.166
961671AG1-007 GEN
Solar/Wind Harmer
0.025
3146083TARBORO
Solar/Wind Harmer
0.165
3145493TOT1
Solar/Wind Harmer
0.732
3146173TUNIS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
0.64
3145893MURPHYS
Solar/Wind Harmer
0.712
316494AC1-189 GEN
Solar/Wind Harmer
0.514
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3146293MARTNCO
Solar/Wind Harmer
0.122
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.122
971547AH1-271 GEN
Solar/Wind Harmer
2.614
316174AB2-169 GEN
Solar/Wind Harmer
0.003
3145963POPLR C
Solar/Wind Harmer
0.118
970685AG2-442 GEN
Solar/Wind Harmer
7.425
970401AG2-262 GEN
Solar/Wind Harmer
0.583
963171AG1-166 GEN
Solar/Wind Harmer
0.482
971563AH1-280 GEN
Solar/Wind Harmer
0.963
3145663CRESWEL
Solar/Wind Harmer
0.224
971163AH1-040 GEN
Solar/Wind Harmer
6.407
957481AF2-042 GEN
Solar/Wind Harmer
19.308
316003AC1-222 GEN
Solar/Wind Harmer
0.002
315693AD1-088 GEN
Solar/Wind Harmer
3.442
315687AD1-152 GEN
Solar/Wind Harmer
0.002
962491AG1-098 GEN
Solar/Wind Harmer
4.048
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.27
3151621KERR 5
50/50
0.27
3151631KERR 6
50/50
0.27
3151641KERR 7
50/50
0.27
3151151S HAMPT1
50/50
0.285
3151541CLOVER2
50/50
1.551
316087AB2-174 GEN
Solar/Wind Harmer
0.01
315652AC1-086 GEN
Solar/Wind Harmer
37.428
3145796HORNRTN
Solar/Wind Harmer
1.015
3145796HORNRTN
Solar/Wind Harmer
0.127
3137643SOCKMAN
Solar/Wind Harmer
1.176
315607AA1-063A GEN
Solar/Wind Harmer
0.444
3146043SEABORD
Solar/Wind Harmer
0.211
3146033SCOT NK
Solar/Wind Harmer
0.75
316319Z2-044 C
Solar/Wind Harmer
0
970831AG2-522 GEN
Solar/Wind Harmer
7.783
3145683EARLEYS
Solar/Wind Harmer
0.333
3145683EARLEYS
Solar/Wind Harmer
0.166
3145683EARLEYS
Solar/Wind Harmer
0.166
3145513AHOSKIE
Solar/Wind Harmer
0.345
3145513AHOSKIE
Solar/Wind Harmer
0.165
3145573BETHELC
Solar/Wind Harmer
0.165
3145573BETHELC
Solar/Wind Harmer
0.165
3145893MURPHYS
Solar/Wind Harmer
0.432
3145893MURPHYS
Solar/Wind Harmer
0.16
316420AA1-050 GEN
Solar/Wind Harmer
0.005
965291AG1-394 GEN
Solar/Wind Harmer
0.698
957861AF2-080 GEN
Solar/Wind Harmer
6.563
316005AA1-067
Solar/Wind Harmer
0.148
3145746EVERETS
Solar/Wind Harmer
0.548
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
970181AG2-120 GEN
Solar/Wind Harmer
1.713
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.122
970601AG2-382 GEN
Solar/Wind Harmer
4.575
971443AH1-215 GEN
Solar/Wind Harmer
1.848
3144303KENBRDG
Solar/Wind Harmer
0.087
315732AD1-074 GEN1
Solar/Wind Harmer
0.587
315733AD1-074 GEN2
Solar/Wind Harmer
0.587
315735AD1-075 GEN1
Solar/Wind Harmer
0.294
970683AG2-441 GEN
Solar/Wind Harmer
6.63
970681AG2-440 GEN
Solar/Wind Harmer
5.304
3130546PLYMOUTH
Solar/Wind Harmer
0.098
946301AF1-294 GEN
Solar/Wind Harmer
1.782
961791AG1-021 GEN
Solar/Wind Harmer
0.867
316118AC1-105 GEN
Solar/Wind Harmer
0.227
315657AE1-056 GEN
Solar/Wind Harmer
2.895
315816AE2-034 GEN
Solar/Wind Harmer
0.344
3147173SINAI
Solar/Wind Harmer
0.077
3147243WELCO
Solar/Wind Harmer
0.048
970865AG2-541 GEN
Solar/Wind Harmer
2.227
316315AB2-025 C
Solar/Wind Helper
0.826
3143316POE
Solar/Wind Helper
0.688
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3151261ROARAP2
50/50
0.313
3151591KERR 2
50/50
0.27
3144293JTRSVLE
50/50
0.305
970413AG2-270 GEN
50/50
6.801
316365GEN2_N
Solar/Wind Harmer
1.155
313506AB2-031 GEN
Solar/Wind Harmer
1.049
3147043LAWRENC
Solar/Wind Harmer
0.196
3145796HORNRTN
Solar/Wind Harmer
1.268
3145796HORNRTN
Solar/Wind Harmer
0.317
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
315724AD1-057 GEN
Solar/Wind Harmer
0.907
316210AC1-098 GEN
Solar/Wind Harmer
1.821
316327AA2-057 GEN
Solar/Wind Harmer
0.289
3146263WOODLND
Solar/Wind Harmer
0.191
3146233WITAKRS
Solar/Wind Harmer
0.921
3146233WITAKRS
Solar/Wind Harmer
0.125
3138543CONSLDL
Solar/Wind Harmer
0.12
961601AG1-000A GEN
Solar/Wind Harmer
12.805
316317KELFORD C
Solar/Wind Harmer
0.017
3145823KELFORD
Solar/Wind Harmer
0.177
971623AH1-311 GEN
Solar/Wind Harmer
0.353
3145543BTLEBRO
Solar/Wind Harmer
0.175
3145543BTLEBRO
Solar/Wind Harmer
0.175
316463AE2-346 GEN
Solar/Wind Harmer
0.142
316140AB2-099
Solar/Wind Harmer
0.059
962331AG1-082 GEN
Solar/Wind Harmer
1.76
3146073TAR RVR
Solar/Wind Harmer
0.165
3146083TARBORO
Solar/Wind Harmer
0.165
3146173TUNIS
Solar/Wind Harmer
0.163
957521AF2-046 GEN
Solar/Wind Harmer
11.982
961681AG1-008 GEN
Solar/Wind Harmer
11.982
3145893MURPHYS
Solar/Wind Harmer
0.268
3145893MURPHYS
Solar/Wind Harmer
0.16
3156021HOLLOMANSOL
Solar/Wind Harmer
0.689
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3145933PARMELE
Solar/Wind Harmer
0.131
966801AG1-551 GEN
Solar/Wind Harmer
1.529
316131AB2-060 GEN
Solar/Wind Harmer
0.407
964241AG1-285 GEN
Solar/Wind Harmer
8.211
3146206CASHIE
Solar/Wind Harmer
0.122
3145963POPLR C
Solar/Wind Harmer
0.118
315785AD2-033 C
Solar/Wind Harmer
0.918
970257AG2-171 GEN
Solar/Wind Harmer
3.491
959311AF2-222 GEN
Solar/Wind Harmer
9.454
315737AD1-076 GEN
Solar/Wind Harmer
1.314
971157AH1-035 GEN
Solar/Wind Harmer
1.183
963181AG1-167 GEN
Solar/Wind Harmer
0.361
3147133PAMPLIN
Solar/Wind Harmer
0.263
971193AH1-056 GEN
Solar/Wind Harmer
5.112
315614AA2-178 GEN
Solar/Wind Harmer
0.458
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.273
316478AD1-087 GEN
Solar/Wind Harmer
0.254
316486AD2-202 GEN
Solar/Wind Harmer
0.075
971683AH1-343 GEN
Solar/Wind Harmer
2.513
942461AE2-259 GEN
Solar/Wind Harmer
0
316283AC2-100 C
Solar/Wind Harmer
0.113
970909AG2-566 GEN
Solar/Wind Harmer
0.605
315839AE2-212 C
Solar/Wind Helper
0.197
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.321
3144293JTRSVLE
50/50
0.305
3144293JTRSVLE
50/50
0.257
3152661PLYWOOD A
50/50
0.195
316181AB2-040 GEN
Solar/Wind Harmer
0.492
3145796HORNRTN
Solar/Wind Harmer
0.951
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3145593CAROLNA
Solar/Wind Harmer
0.257
3145593CAROLNA
Solar/Wind Harmer
0.257
966811AG1-552 GEN
Solar/Wind Harmer
2.785
3145593CAROLNA
Solar/Wind Harmer
0.32
3145783HORNRTN
Solar/Wind Harmer
4.428
3145783HORNRTN
Solar/Wind Harmer
3.543
3145783HORNRTN
Solar/Wind Harmer
1.107
3145783HORNRTN
Solar/Wind Harmer
0.443
316426AA2-053 GEN
Solar/Wind Harmer
0.813
316274AC1-208 GEN
Solar/Wind Harmer
1.081
961601AG1-000A GEN
Solar/Wind Harmer
3.201
316263AC1-034 GEN
Solar/Wind Harmer
6.707
3145493TOT1
Solar/Wind Harmer
0.382
3145453TOT5
Solar/Wind Harmer
0.229
3145603CNETO
Solar/Wind Harmer
0.153
3146173TUNIS
Solar/Wind Harmer
0.163
3146173TUNIS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
1.071
3145893MURPHYS
Solar/Wind Harmer
0.288
3145933PARMELE
Solar/Wind Harmer
0.262
3145933PARMELE
Solar/Wind Harmer
0.131
313527AB2-043 GEN
Solar/Wind Harmer
0.002
939181AE1-148 GEN
Solar/Wind Harmer
6.26
316065AD1-022 GEN
Solar/Wind Harmer
5.298
970323AG2-213 GEN
Solar/Wind Harmer
4.655
971775AH1-396 GEN
Solar/Wind Harmer
0.175
316034AC1-036 C
Solar/Wind Harmer
0.008
962561AG1-105 GEN
Solar/Wind Harmer
5
964791AG1-342 GEN
Solar/Wind Harmer
1.908
3146843MT LREL
Solar/Wind Harmer
0.099
3146843MT LREL
Solar/Wind Harmer
0.099
958211AF2-115 GEN
Solar/Wind Harmer
1.083
963191AG1-168 GEN
Solar/Wind Harmer
0.361
3147133PAMPLIN
Solar/Wind Harmer
0.084
3147133PAMPLIN
Solar/Wind Harmer
0.067
970099AG2-077 GEN
Solar/Wind Harmer
7.723
315742AE1-103 GEN
Solar/Wind Harmer
0.001
971741AH1-377 GEN
Solar/Wind Harmer
5.969
316222AC1-221 GEN
Solar/Wind Harmer
0.242
970301AG2-198 GEN
Solar/Wind Harmer
2.421
3144356SAPONY
Solar/Wind Helper
0.972
316240AF1-291 C
Solar/Wind Helper
0.168
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.85
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.587
MECLTFEXP_MEC->PJM
CLTF
1.327
SIGELTFEXP_SIGE->PJM
CLTF
0.04
CPLELTFEXP_CPLE->PJM
CLTF
4.45
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.218
LAGNLTFEXP_LAGN->PJM
CLTF
2.678
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.707
TVALTFEXP_TVA->PJM
CLTF
1.336
NYPJM->LTFIMP_NY
CLTF
0.49
LGEELTFEXP_LGEE->PJM
CLTF
0.481
WECLTFEXP_WEC->PJM
CLTF
0.25

Details for 6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.99 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:889.03
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.321
3144293JTRSVLE
50/50
0.305
3144293JTRSVLE
50/50
0.257
3152661PLYWOOD A
50/50
0.195
316181AB2-040 GEN
Solar/Wind Harmer
0.492
3145796HORNRTN
Solar/Wind Harmer
0.951
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3145593CAROLNA
Solar/Wind Harmer
0.257
3145593CAROLNA
Solar/Wind Harmer
0.257
966811AG1-552 GEN
Solar/Wind Harmer
2.785
3145593CAROLNA
Solar/Wind Harmer
0.32
3145783HORNRTN
Solar/Wind Harmer
4.428
3145783HORNRTN
Solar/Wind Harmer
3.543
3145783HORNRTN
Solar/Wind Harmer
1.107
3145783HORNRTN
Solar/Wind Harmer
0.443
316426AA2-053 GEN
Solar/Wind Harmer
0.813
316274AC1-208 GEN
Solar/Wind Harmer
1.081
961601AG1-000A GEN
Solar/Wind Harmer
3.201
316263AC1-034 GEN
Solar/Wind Harmer
6.707
3145493TOT1
Solar/Wind Harmer
0.382
3145453TOT5
Solar/Wind Harmer
0.229
3145603CNETO
Solar/Wind Harmer
0.153
3146173TUNIS
Solar/Wind Harmer
0.163
3146173TUNIS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
1.071
3145893MURPHYS
Solar/Wind Harmer
0.288
3145933PARMELE
Solar/Wind Harmer
0.262
3145933PARMELE
Solar/Wind Harmer
0.131
313527AB2-043 GEN
Solar/Wind Harmer
0.002
939181AE1-148 GEN
Solar/Wind Harmer
6.26
316065AD1-022 GEN
Solar/Wind Harmer
5.298
970323AG2-213 GEN
Solar/Wind Harmer
4.655
971775AH1-396 GEN
Solar/Wind Harmer
0.175
316034AC1-036 C
Solar/Wind Harmer
0.008
962561AG1-105 GEN
Solar/Wind Harmer
5
964791AG1-342 GEN
Solar/Wind Harmer
1.908
3146843MT LREL
Solar/Wind Harmer
0.099
3146843MT LREL
Solar/Wind Harmer
0.099
958211AF2-115 GEN
Solar/Wind Harmer
1.083
963191AG1-168 GEN
Solar/Wind Harmer
0.361
3147133PAMPLIN
Solar/Wind Harmer
0.084
3147133PAMPLIN
Solar/Wind Harmer
0.067
970099AG2-077 GEN
Solar/Wind Harmer
7.723
970933AG2-581 GEN
Solar/Wind Harmer
5.779
315742AE1-103 GEN
Solar/Wind Harmer
0.001
971741AH1-377 GEN
Solar/Wind Harmer
5.969
316222AC1-221 GEN
Solar/Wind Harmer
0.242
970301AG2-198 GEN
Solar/Wind Harmer
2.421
3144356SAPONY
Solar/Wind Helper
0.972
316240AF1-291 C
Solar/Wind Helper
0.168
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3151261ROARAP2
50/50
0.313
3151591KERR 2
50/50
0.27
3144293JTRSVLE
50/50
0.305
970413AG2-270 GEN
50/50
6.801
316365GEN2_N
Solar/Wind Harmer
1.155
313506AB2-031 GEN
Solar/Wind Harmer
1.049
3147043LAWRENC
Solar/Wind Harmer
0.196
3145796HORNRTN
Solar/Wind Harmer
1.268
3145796HORNRTN
Solar/Wind Harmer
0.317
3142666NORTHAMPTON
Solar/Wind Harmer
0.315
315724AD1-057 GEN
Solar/Wind Harmer
0.907
316210AC1-098 GEN
Solar/Wind Harmer
1.821
316327AA2-057 GEN
Solar/Wind Harmer
0.289
3146263WOODLND
Solar/Wind Harmer
0.191
3146233WITAKRS
Solar/Wind Harmer
0.921
3146233WITAKRS
Solar/Wind Harmer
0.125
3138543CONSLDL
Solar/Wind Harmer
0.12
961601AG1-000A GEN
Solar/Wind Harmer
12.805
316317KELFORD C
Solar/Wind Harmer
0.017
3145823KELFORD
Solar/Wind Harmer
0.177
971623AH1-311 GEN
Solar/Wind Harmer
0.353
3145543BTLEBRO
Solar/Wind Harmer
0.175
3145543BTLEBRO
Solar/Wind Harmer
0.175
316463AE2-346 GEN
Solar/Wind Harmer
0.142
316140AB2-099
Solar/Wind Harmer
0.059
962331AG1-082 GEN
Solar/Wind Harmer
1.76
3146073TAR RVR
Solar/Wind Harmer
0.165
3146083TARBORO
Solar/Wind Harmer
0.165
3146173TUNIS
Solar/Wind Harmer
0.163
957521AF2-046 GEN
Solar/Wind Harmer
11.982
961681AG1-008 GEN
Solar/Wind Harmer
11.982
3145893MURPHYS
Solar/Wind Harmer
0.268
3145893MURPHYS
Solar/Wind Harmer
0.16
3156021HOLLOMANSOL
Solar/Wind Harmer
0.689
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3145933PARMELE
Solar/Wind Harmer
0.131
966801AG1-551 GEN
Solar/Wind Harmer
1.529
316131AB2-060 GEN
Solar/Wind Harmer
0.407
964241AG1-285 GEN
Solar/Wind Harmer
8.211
3146206CASHIE
Solar/Wind Harmer
0.122
3145963POPLR C
Solar/Wind Harmer
0.118
315785AD2-033 C
Solar/Wind Harmer
0.918
970257AG2-171 GEN
Solar/Wind Harmer
3.491
959311AF2-222 GEN
Solar/Wind Harmer
9.454
315737AD1-076 GEN
Solar/Wind Harmer
1.314
971157AH1-035 GEN
Solar/Wind Harmer
1.183
963181AG1-167 GEN
Solar/Wind Harmer
0.361
3147133PAMPLIN
Solar/Wind Harmer
0.263
971193AH1-056 GEN
Solar/Wind Harmer
5.112
315614AA2-178 GEN
Solar/Wind Harmer
0.458
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.273
316478AD1-087 GEN
Solar/Wind Harmer
0.254
316486AD2-202 GEN
Solar/Wind Harmer
0.075
971683AH1-343 GEN
Solar/Wind Harmer
2.513
942461AE2-259 GEN
Solar/Wind Harmer
0
316283AC2-100 C
Solar/Wind Harmer
0.113
970909AG2-566 GEN
Solar/Wind Harmer
0.605
315839AE2-212 C
Solar/Wind Helper
0.197
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3147043LAWRENC
50/50
3.141
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.27
3151581KERR 1
50/50
0.096
3144293JTRSVLE
50/50
0.305
3151531CLOVER1
50/50
1.558
316023GEN1_S
Solar/Wind Harmer
1.155
960081AF2-299 GEN
Solar/Wind Harmer
3.965
971795AH1-408 GEN
Solar/Wind Harmer
23.615
316011AB1-132 GEN
Solar/Wind Harmer
6.186
962571AG1-106 GEN
Solar/Wind Harmer
4.841
3145796HORNRTN
Solar/Wind Harmer
1.046
3145796HORNRTN
Solar/Wind Harmer
0.317
3145783HORNRTN
Solar/Wind Harmer
0.249
315722AD1-056 GEN
Solar/Wind Harmer
1.531
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
1.015
3146263WOODLND
Solar/Wind Harmer
0.191
3146233WITAKRS
Solar/Wind Harmer
0.73
3145823KELFORD
Solar/Wind Harmer
0.177
316359AB2-059 GEN
Solar/Wind Harmer
0.634
316049AB1-081 GEN
Solar/Wind Harmer
1.01
3142053HEARTS
Solar/Wind Harmer
0.311
3145543BTLEBRO
Solar/Wind Harmer
0.175
3145543BTLEBRO
Solar/Wind Harmer
0.14
316129AC1-054 GEN
Solar/Wind Harmer
0.656
971065AG2-659 GEN
Solar/Wind Harmer
7.13
3145683EARLEYS
Solar/Wind Harmer
0.166
961671AG1-007 GEN
Solar/Wind Harmer
0.025
3146083TARBORO
Solar/Wind Harmer
0.165
3145493TOT1
Solar/Wind Harmer
0.732
3146173TUNIS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
0.64
3145893MURPHYS
Solar/Wind Harmer
0.712
316494AC1-189 GEN
Solar/Wind Harmer
0.514
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3146293MARTNCO
Solar/Wind Harmer
0.122
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.122
971547AH1-271 GEN
Solar/Wind Harmer
2.614
316174AB2-169 GEN
Solar/Wind Harmer
0.003
3145963POPLR C
Solar/Wind Harmer
0.118
970685AG2-442 GEN
Solar/Wind Harmer
7.425
970401AG2-262 GEN
Solar/Wind Harmer
0.583
963171AG1-166 GEN
Solar/Wind Harmer
0.482
971563AH1-280 GEN
Solar/Wind Harmer
0.963
3145663CRESWEL
Solar/Wind Harmer
0.224
971163AH1-040 GEN
Solar/Wind Harmer
6.407
957481AF2-042 GEN
Solar/Wind Harmer
19.308
316003AC1-222 GEN
Solar/Wind Harmer
0.002
315693AD1-088 GEN
Solar/Wind Harmer
3.442
315687AD1-152 GEN
Solar/Wind Harmer
0.002
962491AG1-098 GEN
Solar/Wind Harmer
4.048
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.27
3151621KERR 5
50/50
0.27
3151631KERR 6
50/50
0.27
3151641KERR 7
50/50
0.27
3151151S HAMPT1
50/50
0.285
3151541CLOVER2
50/50
1.551
316087AB2-174 GEN
Solar/Wind Harmer
0.01
315652AC1-086 GEN
Solar/Wind Harmer
37.428
3145796HORNRTN
Solar/Wind Harmer
1.015
3145796HORNRTN
Solar/Wind Harmer
0.127
3137643SOCKMAN
Solar/Wind Harmer
1.176
315607AA1-063A GEN
Solar/Wind Harmer
0.444
3146043SEABORD
Solar/Wind Harmer
0.211
3146033SCOT NK
Solar/Wind Harmer
0.75
316319Z2-044 C
Solar/Wind Harmer
0
970831AG2-522 GEN
Solar/Wind Harmer
7.783
3145683EARLEYS
Solar/Wind Harmer
0.333
3145683EARLEYS
Solar/Wind Harmer
0.166
3145683EARLEYS
Solar/Wind Harmer
0.166
3145513AHOSKIE
Solar/Wind Harmer
0.345
3145513AHOSKIE
Solar/Wind Harmer
0.165
3145573BETHELC
Solar/Wind Harmer
0.165
3145573BETHELC
Solar/Wind Harmer
0.165
3145893MURPHYS
Solar/Wind Harmer
0.432
3145893MURPHYS
Solar/Wind Harmer
0.16
316420AA1-050 GEN
Solar/Wind Harmer
0.005
965291AG1-394 GEN
Solar/Wind Harmer
0.698
957861AF2-080 GEN
Solar/Wind Harmer
6.563
316005AA1-067
Solar/Wind Harmer
0.148
3145746EVERETS
Solar/Wind Harmer
0.548
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
3145746EVERETS
Solar/Wind Harmer
0.138
970181AG2-120 GEN
Solar/Wind Harmer
1.713
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.122
970601AG2-382 GEN
Solar/Wind Harmer
4.575
971443AH1-215 GEN
Solar/Wind Harmer
1.848
3144303KENBRDG
Solar/Wind Harmer
0.087
315732AD1-074 GEN1
Solar/Wind Harmer
0.587
315733AD1-074 GEN2
Solar/Wind Harmer
0.587
315735AD1-075 GEN1
Solar/Wind Harmer
0.294
970683AG2-441 GEN
Solar/Wind Harmer
6.63
970681AG2-440 GEN
Solar/Wind Harmer
5.304
3130546PLYMOUTH
Solar/Wind Harmer
0.098
946301AF1-294 GEN
Solar/Wind Harmer
1.782
961791AG1-021 GEN
Solar/Wind Harmer
0.867
316118AC1-105 GEN
Solar/Wind Harmer
0.227
315657AE1-056 GEN
Solar/Wind Harmer
2.895
315816AE2-034 GEN
Solar/Wind Harmer
0.344
3147173SINAI
Solar/Wind Harmer
0.077
3147243WELCO
Solar/Wind Harmer
0.048
971967AH1-528 GEN
Solar/Wind Harmer
11.557
970865AG2-541 GEN
Solar/Wind Harmer
2.227
316315AB2-025 C
Solar/Wind Helper
0.826
3143316POE
Solar/Wind Helper
0.688
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.85
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.587
MECLTFEXP_MEC->PJM
CLTF
1.327
SIGELTFEXP_SIGE->PJM
CLTF
0.04
CPLELTFEXP_CPLE->PJM
CLTF
4.45
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.218
LAGNLTFEXP_LAGN->PJM
CLTF
2.678
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.707
TVALTFEXP_TVA->PJM
CLTF
1.336
NYPJM->LTFIMP_NY
CLTF
0.49
LGEELTFEXP_LGEE->PJM
CLTF
0.481
WECLTFEXP_WEC->PJM
CLTF
0.25

Details for 6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.02 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1045.98
MW Contribution:2.34
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3147043LAWRENC
50/50
3.142
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.272
3151581KERR 1
50/50
0.097
316023GEN1_S
Solar/Wind Harmer
3.898
960081AF2-299 GEN
Solar/Wind Harmer
5.218
971795AH1-408 GEN
Solar/Wind Harmer
29.85
316011AB1-132 GEN
Solar/Wind Harmer
8.002
962571AG1-106 GEN
Solar/Wind Harmer
5.498
3145796HORNRTN
Solar/Wind Harmer
-0.117
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145783HORNRTN
Solar/Wind Harmer
-0.028
315722AD1-056 GEN
Solar/Wind Harmer
2.85
316190AA2-174 GEN
Solar/Wind Harmer
0.332
316212AC1-099_GEN
Solar/Wind Harmer
1.927
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
-0.082
316359AB2-059 GEN
Solar/Wind Harmer
2.691
316049AB1-081 GEN
Solar/Wind Harmer
2.154
3142053HEARTS
Solar/Wind Harmer
0.235
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316129AC1-054 GEN
Solar/Wind Harmer
1.725
971065AG2-659 GEN
Solar/Wind Harmer
9.428
3145683EARLEYS
Solar/Wind Harmer
-0.019
961671AG1-007 GEN
Solar/Wind Harmer
0.235
3146083TARBORO
Solar/Wind Harmer
-0.019
3145493TOT1
Solar/Wind Harmer
0.552
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.071
3145893MURPHYS
Solar/Wind Harmer
0.532
316494AC1-189 GEN
Solar/Wind Harmer
1.85
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146293MARTNCO
Solar/Wind Harmer
0.092
316237AB2-079_GEN
Solar/Wind Harmer
0.44
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.431
316174AB2-169 GEN
Solar/Wind Harmer
2.09
3145963POPLR C
Solar/Wind Harmer
-0.013
970401AG2-262 GEN
Solar/Wind Harmer
0.737
970685AG2-442 GEN
Solar/Wind Harmer
9.839
963171AG1-166 GEN
Solar/Wind Harmer
1.276
971563AH1-280 GEN
Solar/Wind Harmer
1.276
3144293JTRSVLE
Adder
0.289
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.359
957481AF2-042 GEN
Solar/Wind Harmer
25.811
316003AC1-222 GEN
Solar/Wind Harmer
0.806
315693AD1-088 GEN
Solar/Wind Harmer
4.085
315687AD1-152 GEN
Solar/Wind Harmer
0.98
962491AG1-098 GEN
Solar/Wind Harmer
5.404
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.337
316181AB2-040 GEN
Solar/Wind Harmer
5.319
3145796HORNRTN
Solar/Wind Harmer
-0.106
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3145593CAROLNA
Solar/Wind Harmer
-0.029
3145593CAROLNA
Solar/Wind Harmer
-0.029
966811AG1-552 GEN
Solar/Wind Harmer
3.248
3145593CAROLNA
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
3.324
3145783HORNRTN
Solar/Wind Harmer
2.659
3145783HORNRTN
Solar/Wind Harmer
0.831
3145783HORNRTN
Solar/Wind Harmer
0.332
316426AA2-053 GEN
Solar/Wind Harmer
2.733
316274AC1-208 GEN
Solar/Wind Harmer
2.531
961601AG1-000A GEN
Solar/Wind Harmer
8.004
316263AC1-034 GEN
Solar/Wind Harmer
9.357
3145493TOT1
Solar/Wind Harmer
0.288
3145453TOT5
Solar/Wind Harmer
0.173
3145603CNETO
Solar/Wind Harmer
0.115
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.501
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.029
3145933PARMELE
Solar/Wind Harmer
-0.015
313527AB2-043 GEN
Solar/Wind Harmer
2.404
939181AE1-148 GEN
Solar/Wind Harmer
8.303
316065AD1-022 GEN
Solar/Wind Harmer
6.44
970323AG2-213 GEN
Solar/Wind Harmer
6.168
971775AH1-396 GEN
Solar/Wind Harmer
0.878
316034AC1-036 C
Solar/Wind Harmer
0.229
962561AG1-105 GEN
Solar/Wind Harmer
6.652
964791AG1-342 GEN
Solar/Wind Harmer
2.412
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
958211AF2-115 GEN
Solar/Wind Harmer
1.595
963191AG1-168 GEN
Solar/Wind Harmer
0.957
3144293JTRSVLE
Adder
0.289
3144293JTRSVLE
Adder
0.244
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.324
970933AG2-581 GEN
Solar/Wind Harmer
7.724
315742AE1-103 GEN
Solar/Wind Harmer
0.835
971741AH1-377 GEN
Solar/Wind Harmer
7.95
316222AC1-221 GEN
Solar/Wind Harmer
0.686
970301AG2-198 GEN
Solar/Wind Harmer
3.221
3144356SAPONY
Solar/Wind Helper
0.977
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.272
3151621KERR 5
50/50
0.272
3151631KERR 6
50/50
0.272
3151641KERR 7
50/50
0.272
946281AF1-292 GEN
Solar/Wind Harmer
1.039
316087AB2-174 GEN
Solar/Wind Harmer
5.795
315652AC1-086 GEN
Solar/Wind Harmer
43.026
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.014
3137643SOCKMAN
Solar/Wind Harmer
-0.132
315607AA1-063A GEN
Solar/Wind Harmer
2.467
3146043SEABORD
Solar/Wind Harmer
-0.024
3146033SCOT NK
Solar/Wind Harmer
-0.084
316319Z2-044 C
Solar/Wind Harmer
1.146
970831AG2-522 GEN
Solar/Wind Harmer
10.282
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.161
961941AG1-037 GEN
Solar/Wind Harmer
0.139
3145513AHOSKIE
Solar/Wind Harmer
-0.018
316420AA1-050 GEN
Solar/Wind Harmer
2.056
316318V4-068
Solar/Wind Harmer
0.447
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
965291AG1-394 GEN
Solar/Wind Harmer
1.561
957861AF2-080 GEN
Solar/Wind Harmer
7.524
316005AA1-067
Solar/Wind Harmer
0.314
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3151261ROARAP2
50/50
0.313
3151591KERR 2
50/50
0.272
316365GEN2_N
Solar/Wind Harmer
3.898
966621AG1-532 GEN
Solar/Wind Harmer
0.941
313506AB2-031 GEN
Solar/Wind Harmer
3.065
3147043LAWRENC
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.142
3145796HORNRTN
Solar/Wind Harmer
-0.036
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
315724AD1-057 GEN
Solar/Wind Harmer
1.567
316210AC1-098 GEN
Solar/Wind Harmer
3.469
316327AA2-057 GEN
Solar/Wind Harmer
2.181
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
0.434
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
8.106
316317KELFORD C
Solar/Wind Harmer
0.938
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3146073TAR RVR
Solar/Wind Harmer
-0.019
3146083TARBORO
Solar/Wind Harmer
-0.019
316463AE2-346 GEN
Solar/Wind Harmer
0.3
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.315
3146173TUNIS
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.221
961681AG1-008 GEN
Solar/Wind Harmer
14.221
3145893MURPHYS
Solar/Wind Harmer
0.125
3145893MURPHYS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.293
3156081AA2-088 GEN
Solar/Wind Harmer
5.454
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.85
316131AB2-060 GEN
Solar/Wind Harmer
1.577
964241AG1-285 GEN
Solar/Wind Harmer
10.88
3146206CASHIE
Solar/Wind Harmer
-0.014
3145963POPLR C
Solar/Wind Harmer
-0.013
315785AD2-033 C
Solar/Wind Harmer
2.894
970257AG2-171 GEN
Solar/Wind Harmer
4.626
959311AF2-222 GEN
Solar/Wind Harmer
12.552
315737AD1-076 GEN
Solar/Wind Harmer
2.17
971157AH1-035 GEN
Solar/Wind Harmer
1.377
963181AG1-167 GEN
Solar/Wind Harmer
0.957
3144293JTRSVLE
Adder
0.289
3147133PAMPLIN
Solar/Wind Harmer
-0.03
971193AH1-056 GEN
Solar/Wind Harmer
5.933
315614AA2-178 GEN
Solar/Wind Harmer
0.962
316248AF1-058 C
Solar/Wind Harmer
0.264
960061AF2-297 GEN
Solar/Wind Harmer
4.385
316478AD1-087 GEN
Solar/Wind Harmer
0.72
316486AD2-202 GEN
Solar/Wind Harmer
0.211
971683AH1-343 GEN
Solar/Wind Harmer
3.369
942461AE2-259 GEN
Solar/Wind Harmer
1.119
316283AC2-100 C
Solar/Wind Harmer
0.635
970909AG2-566 GEN
Solar/Wind Harmer
0.612
315839AE2-212 C
Solar/Wind Helper
0.202
970181AG2-120 GEN
Solar/Wind Harmer
2.04
316239AB2-077_GEN
Solar/Wind Harmer
0.44
316238AB2-078_GEN
Solar/Wind Harmer
0.44
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
6.005
971443AH1-215 GEN
Solar/Wind Harmer
2.448
3144303KENBRDG
Solar/Wind Harmer
-0.01
315732AD1-074 GEN1
Solar/Wind Harmer
2.309
315733AD1-074 GEN2
Solar/Wind Harmer
2.309
315735AD1-075 GEN1
Solar/Wind Harmer
1.155
970683AG2-441 GEN
Solar/Wind Harmer
8.785
970681AG2-440 GEN
Solar/Wind Harmer
7.028
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
946301AF1-294 GEN
Solar/Wind Harmer
2.616
961791AG1-021 GEN
Solar/Wind Harmer
1.276
316118AC1-105 GEN
Solar/Wind Harmer
0.689
315657AE1-056 GEN
Solar/Wind Harmer
3.56
315816AE2-034 GEN
Solar/Wind Harmer
0.721
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
971967AH1-528 GEN
Solar/Wind Harmer
15.486
970865AG2-541 GEN
Solar/Wind Harmer
2.987
316123AC1-075 GEN
Solar/Wind Harmer
0.692
970165AG2-112 GEN
Solar/Wind Harmer
0.609
970163AG2-111 GEN
Solar/Wind Harmer
0.581
316315AB2-025 C
Solar/Wind Helper
0.83
3143316POE
Solar/Wind Helper
0.701
316240AF1-291 C
Solar/Wind Helper
0.173
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.344
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.843
MECLTFEXP_MEC->PJM
CLTF
1.401
SIGELTFEXP_SIGE->PJM
CLTF
0.042
CPLELTFEXP_CPLE->PJM
CLTF
4.654
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.01
LAGNLTFEXP_LAGN->PJM
CLTF
2.828
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.165
TVALTFEXP_TVA->PJM
CLTF
1.41
NYPJM->LTFIMP_NY
CLTF
0.512
LGEELTFEXP_LGEE->PJM
CLTF
0.508
WECLTFEXP_WEC->PJM
CLTF
0.264

Details for 6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.95 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1045.35
MW Contribution:2.34
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3151261ROARAP2
50/50
0.313
3151591KERR 2
50/50
0.272
316365GEN2_N
Solar/Wind Harmer
3.898
966621AG1-532 GEN
Solar/Wind Harmer
0.941
313506AB2-031 GEN
Solar/Wind Harmer
3.065
3147043LAWRENC
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.142
3145796HORNRTN
Solar/Wind Harmer
-0.036
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
315724AD1-057 GEN
Solar/Wind Harmer
1.567
316210AC1-098 GEN
Solar/Wind Harmer
3.469
316327AA2-057 GEN
Solar/Wind Harmer
2.181
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
0.434
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
8.106
316317KELFORD C
Solar/Wind Harmer
0.938
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3146073TAR RVR
Solar/Wind Harmer
-0.019
3146083TARBORO
Solar/Wind Harmer
-0.019
316463AE2-346 GEN
Solar/Wind Harmer
0.3
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.315
3146173TUNIS
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.221
961681AG1-008 GEN
Solar/Wind Harmer
14.221
3145893MURPHYS
Solar/Wind Harmer
0.125
3145893MURPHYS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.293
3156081AA2-088 GEN
Solar/Wind Harmer
5.454
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.337
316181AB2-040 GEN
Solar/Wind Harmer
5.319
3145796HORNRTN
Solar/Wind Harmer
-0.106
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3145593CAROLNA
Solar/Wind Harmer
-0.029
3145593CAROLNA
Solar/Wind Harmer
-0.029
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3147043LAWRENC
50/50
3.142
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.272
3151581KERR 1
50/50
0.097
316023GEN1_S
Solar/Wind Harmer
3.898
960081AF2-299 GEN
Solar/Wind Harmer
5.218
971795AH1-408 GEN
Solar/Wind Harmer
29.85
316011AB1-132 GEN
Solar/Wind Harmer
8.002
962571AG1-106 GEN
Solar/Wind Harmer
5.498
3145796HORNRTN
Solar/Wind Harmer
-0.117
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145783HORNRTN
Solar/Wind Harmer
-0.028
315722AD1-056 GEN
Solar/Wind Harmer
2.85
316190AA2-174 GEN
Solar/Wind Harmer
0.332
966811AG1-552 GEN
Solar/Wind Harmer
3.248
3145593CAROLNA
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
3.324
3145783HORNRTN
Solar/Wind Harmer
2.659
3145783HORNRTN
Solar/Wind Harmer
0.831
3145783HORNRTN
Solar/Wind Harmer
0.332
316426AA2-053 GEN
Solar/Wind Harmer
2.733
316274AC1-208 GEN
Solar/Wind Harmer
2.531
961601AG1-000A GEN
Solar/Wind Harmer
8.004
316263AC1-034 GEN
Solar/Wind Harmer
9.357
3145493TOT1
Solar/Wind Harmer
0.288
3145453TOT5
Solar/Wind Harmer
0.173
3145603CNETO
Solar/Wind Harmer
0.115
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.501
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.029
3145933PARMELE
Solar/Wind Harmer
-0.015
313527AB2-043 GEN
Solar/Wind Harmer
2.404
939181AE1-148 GEN
Solar/Wind Harmer
8.303
316065AD1-022 GEN
Solar/Wind Harmer
6.44
970323AG2-213 GEN
Solar/Wind Harmer
6.168
971775AH1-396 GEN
Solar/Wind Harmer
0.878
316034AC1-036 C
Solar/Wind Harmer
0.229
962561AG1-105 GEN
Solar/Wind Harmer
6.652
964791AG1-342 GEN
Solar/Wind Harmer
2.412
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
958211AF2-115 GEN
Solar/Wind Harmer
1.595
963191AG1-168 GEN
Solar/Wind Harmer
0.957
3144293JTRSVLE
Adder
0.289
3144293JTRSVLE
Adder
0.244
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.324
970933AG2-581 GEN
Solar/Wind Harmer
7.724
315742AE1-103 GEN
Solar/Wind Harmer
0.835
971741AH1-377 GEN
Solar/Wind Harmer
7.95
316222AC1-221 GEN
Solar/Wind Harmer
0.686
970301AG2-198 GEN
Solar/Wind Harmer
3.221
3144356SAPONY
Solar/Wind Helper
0.977
316240AF1-291 C
Solar/Wind Helper
0.173
316212AC1-099_GEN
Solar/Wind Harmer
1.927
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
-0.082
316359AB2-059 GEN
Solar/Wind Harmer
2.691
316049AB1-081 GEN
Solar/Wind Harmer
2.154
3142053HEARTS
Solar/Wind Harmer
0.235
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316129AC1-054 GEN
Solar/Wind Harmer
1.725
971065AG2-659 GEN
Solar/Wind Harmer
9.428
3145683EARLEYS
Solar/Wind Harmer
-0.019
961671AG1-007 GEN
Solar/Wind Harmer
0.235
3146083TARBORO
Solar/Wind Harmer
-0.019
3145493TOT1
Solar/Wind Harmer
0.552
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.071
3145893MURPHYS
Solar/Wind Harmer
0.532
316494AC1-189 GEN
Solar/Wind Harmer
1.85
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146293MARTNCO
Solar/Wind Harmer
0.092
316237AB2-079_GEN
Solar/Wind Harmer
0.44
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.431
316174AB2-169 GEN
Solar/Wind Harmer
2.09
3145963POPLR C
Solar/Wind Harmer
-0.013
970401AG2-262 GEN
Solar/Wind Harmer
0.737
970685AG2-442 GEN
Solar/Wind Harmer
9.839
963171AG1-166 GEN
Solar/Wind Harmer
1.276
971563AH1-280 GEN
Solar/Wind Harmer
1.276
3144293JTRSVLE
Adder
0.289
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.359
957481AF2-042 GEN
Solar/Wind Harmer
25.811
316003AC1-222 GEN
Solar/Wind Harmer
0.806
315693AD1-088 GEN
Solar/Wind Harmer
4.085
315687AD1-152 GEN
Solar/Wind Harmer
0.98
962491AG1-098 GEN
Solar/Wind Harmer
5.404
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.272
3151621KERR 5
50/50
0.272
3151631KERR 6
50/50
0.272
3151641KERR 7
50/50
0.272
946281AF1-292 GEN
Solar/Wind Harmer
1.039
316087AB2-174 GEN
Solar/Wind Harmer
5.795
315652AC1-086 GEN
Solar/Wind Harmer
43.026
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.014
3137643SOCKMAN
Solar/Wind Harmer
-0.132
315607AA1-063A GEN
Solar/Wind Harmer
2.467
3146043SEABORD
Solar/Wind Harmer
-0.024
3146033SCOT NK
Solar/Wind Harmer
-0.084
316319Z2-044 C
Solar/Wind Harmer
1.146
970831AG2-522 GEN
Solar/Wind Harmer
10.282
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.161
961941AG1-037 GEN
Solar/Wind Harmer
0.139
3145513AHOSKIE
Solar/Wind Harmer
-0.018
316420AA1-050 GEN
Solar/Wind Harmer
2.056
316318V4-068
Solar/Wind Harmer
0.447
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
965291AG1-394 GEN
Solar/Wind Harmer
1.561
957861AF2-080 GEN
Solar/Wind Harmer
7.524
316005AA1-067
Solar/Wind Harmer
0.314
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
2.04
316239AB2-077_GEN
Solar/Wind Harmer
0.44
316238AB2-078_GEN
Solar/Wind Harmer
0.44
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
6.005
971443AH1-215 GEN
Solar/Wind Harmer
2.448
3144303KENBRDG
Solar/Wind Harmer
-0.01
315732AD1-074 GEN1
Solar/Wind Harmer
2.309
315733AD1-074 GEN2
Solar/Wind Harmer
2.309
315735AD1-075 GEN1
Solar/Wind Harmer
1.155
970683AG2-441 GEN
Solar/Wind Harmer
8.785
970681AG2-440 GEN
Solar/Wind Harmer
7.028
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
946301AF1-294 GEN
Solar/Wind Harmer
2.616
961791AG1-021 GEN
Solar/Wind Harmer
1.276
316118AC1-105 GEN
Solar/Wind Harmer
0.689
315657AE1-056 GEN
Solar/Wind Harmer
3.56
315816AE2-034 GEN
Solar/Wind Harmer
0.721
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
971967AH1-528 GEN
Solar/Wind Harmer
15.486
970865AG2-541 GEN
Solar/Wind Harmer
2.987
316123AC1-075 GEN
Solar/Wind Harmer
0.692
970165AG2-112 GEN
Solar/Wind Harmer
0.609
970163AG2-111 GEN
Solar/Wind Harmer
0.581
316315AB2-025 C
Solar/Wind Helper
0.83
3143316POE
Solar/Wind Helper
0.701
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.85
316131AB2-060 GEN
Solar/Wind Harmer
1.577
964241AG1-285 GEN
Solar/Wind Harmer
10.88
3146206CASHIE
Solar/Wind Harmer
-0.014
3145963POPLR C
Solar/Wind Harmer
-0.013
315785AD2-033 C
Solar/Wind Harmer
2.894
970257AG2-171 GEN
Solar/Wind Harmer
4.626
959311AF2-222 GEN
Solar/Wind Harmer
12.552
315737AD1-076 GEN
Solar/Wind Harmer
2.17
971157AH1-035 GEN
Solar/Wind Harmer
1.377
963181AG1-167 GEN
Solar/Wind Harmer
0.957
3144293JTRSVLE
Adder
0.289
3147133PAMPLIN
Solar/Wind Harmer
-0.03
971193AH1-056 GEN
Solar/Wind Harmer
5.933
315614AA2-178 GEN
Solar/Wind Harmer
0.962
316248AF1-058 C
Solar/Wind Harmer
0.264
960061AF2-297 GEN
Solar/Wind Harmer
4.385
316478AD1-087 GEN
Solar/Wind Harmer
0.72
316486AD2-202 GEN
Solar/Wind Harmer
0.211
971683AH1-343 GEN
Solar/Wind Harmer
3.369
942461AE2-259 GEN
Solar/Wind Harmer
1.119
316283AC2-100 C
Solar/Wind Harmer
0.635
970909AG2-566 GEN
Solar/Wind Harmer
0.612
315839AE2-212 C
Solar/Wind Helper
0.202
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.344
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.843
MECLTFEXP_MEC->PJM
CLTF
1.401
SIGELTFEXP_SIGE->PJM
CLTF
0.042
CPLELTFEXP_CPLE->PJM
CLTF
4.654
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.01
LAGNLTFEXP_LAGN->PJM
CLTF
2.828
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.165
TVALTFEXP_TVA->PJM
CLTF
1.41
NYPJM->LTFIMP_NY
CLTF
0.512
LGEELTFEXP_LGEE->PJM
CLTF
0.508
WECLTFEXP_WEC->PJM
CLTF
0.264

Details for 6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.01 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1004.4
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3147043LAWRENC
50/50
3.141
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.27
3151581KERR 1
50/50
0.096
316023GEN1_S
Solar/Wind Harmer
3.902
960081AF2-299 GEN
Solar/Wind Harmer
5.22
971795AH1-408 GEN
Solar/Wind Harmer
29.849
316011AB1-132 GEN
Solar/Wind Harmer
8.002
962571AG1-106 GEN
Solar/Wind Harmer
5.498
3145796HORNRTN
Solar/Wind Harmer
-0.117
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145783HORNRTN
Solar/Wind Harmer
-0.028
315722AD1-056 GEN
Solar/Wind Harmer
2.841
316190AA2-174 GEN
Solar/Wind Harmer
0.332
316212AC1-099_GEN
Solar/Wind Harmer
1.923
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
-0.082
3145823KELFORD
Solar/Wind Harmer
-0.02
316359AB2-059 GEN
Solar/Wind Harmer
2.674
316049AB1-081 GEN
Solar/Wind Harmer
2.14
3142053HEARTS
Solar/Wind Harmer
0.233
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316129AC1-054 GEN
Solar/Wind Harmer
1.719
971065AG2-659 GEN
Solar/Wind Harmer
9.387
3145683EARLEYS
Solar/Wind Harmer
-0.019
961671AG1-007 GEN
Solar/Wind Harmer
0.234
3146083TARBORO
Solar/Wind Harmer
-0.018
3145493TOT1
Solar/Wind Harmer
0.549
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.072
3145893MURPHYS
Solar/Wind Harmer
0.534
316494AC1-189 GEN
Solar/Wind Harmer
1.84
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146293MARTNCO
Solar/Wind Harmer
0.091
316237AB2-079_GEN
Solar/Wind Harmer
0.437
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.442
316174AB2-169 GEN
Solar/Wind Harmer
2.088
3145963POPLR C
Solar/Wind Harmer
-0.013
970685AG2-442 GEN
Solar/Wind Harmer
9.773
970401AG2-262 GEN
Solar/Wind Harmer
0.729
963171AG1-166 GEN
Solar/Wind Harmer
1.268
971563AH1-280 GEN
Solar/Wind Harmer
1.268
3144293JTRSVLE
Adder
0.287
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.436
957481AF2-042 GEN
Solar/Wind Harmer
25.486
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.27
3151621KERR 5
50/50
0.27
3151631KERR 6
50/50
0.27
3151641KERR 7
50/50
0.27
946281AF1-292 GEN
Solar/Wind Harmer
1.039
316087AB2-174 GEN
Solar/Wind Harmer
5.796
315652AC1-086 GEN
Solar/Wind Harmer
43.026
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.014
3137643SOCKMAN
Solar/Wind Harmer
-0.132
315607AA1-063A GEN
Solar/Wind Harmer
2.468
3146043SEABORD
Solar/Wind Harmer
-0.024
3146033SCOT NK
Solar/Wind Harmer
-0.084
316319Z2-044 C
Solar/Wind Harmer
1.139
970831AG2-522 GEN
Solar/Wind Harmer
10.247
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.162
961941AG1-037 GEN
Solar/Wind Harmer
0.139
3145513AHOSKIE
Solar/Wind Harmer
-0.018
3145573BETHELC
Solar/Wind Harmer
-0.018
3145573BETHELC
Solar/Wind Harmer
-0.018
316318V4-068
Solar/Wind Harmer
0.448
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
316420AA1-050 GEN
Solar/Wind Harmer
2.044
965291AG1-394 GEN
Solar/Wind Harmer
1.566
957861AF2-080 GEN
Solar/Wind Harmer
7.484
316005AA1-067
Solar/Wind Harmer
0.313
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
2.03
316239AB2-077_GEN
Solar/Wind Harmer
0.437
316238AB2-078_GEN
Solar/Wind Harmer
0.437
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
6.024
971443AH1-215 GEN
Solar/Wind Harmer
2.432
3144303KENBRDG
Solar/Wind Harmer
-0.01
315732AD1-074 GEN1
Solar/Wind Harmer
2.32
315733AD1-074 GEN2
Solar/Wind Harmer
2.32
315735AD1-075 GEN1
Solar/Wind Harmer
1.16
970683AG2-441 GEN
Solar/Wind Harmer
8.726
970681AG2-440 GEN
Solar/Wind Harmer
6.981
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
946301AF1-294 GEN
Solar/Wind Harmer
2.598
961791AG1-021 GEN
Solar/Wind Harmer
1.268
316118AC1-105 GEN
Solar/Wind Harmer
0.679
315657AE1-056 GEN
Solar/Wind Harmer
3.535
315816AE2-034 GEN
Solar/Wind Harmer
0.728
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
970865AG2-541 GEN
Solar/Wind Harmer
2.933
316315AB2-025 C
Solar/Wind Helper
0.826
3143316POE
Solar/Wind Helper
0.688
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3151261ROARAP2
50/50
0.313
3151591KERR 2
50/50
0.27
316365GEN2_N
Solar/Wind Harmer
3.902
966621AG1-532 GEN
Solar/Wind Harmer
0.942
313506AB2-031 GEN
Solar/Wind Harmer
3.065
3147043LAWRENC
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.142
3145796HORNRTN
Solar/Wind Harmer
-0.036
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
315724AD1-057 GEN
Solar/Wind Harmer
1.563
316210AC1-098 GEN
Solar/Wind Harmer
3.461
316327AA2-057 GEN
Solar/Wind Harmer
2.172
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
0.432
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
8.054
316317KELFORD C
Solar/Wind Harmer
0.938
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
316463AE2-346 GEN
Solar/Wind Harmer
0.3
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.318
3146073TAR RVR
Solar/Wind Harmer
-0.018
3146083TARBORO
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.25
961681AG1-008 GEN
Solar/Wind Harmer
14.25
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.297
3156081AA2-088 GEN
Solar/Wind Harmer
5.472
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.843
316131AB2-060 GEN
Solar/Wind Harmer
1.567
964241AG1-285 GEN
Solar/Wind Harmer
10.81
3146206CASHIE
Solar/Wind Harmer
-0.014
3145963POPLR C
Solar/Wind Harmer
-0.013
315785AD2-033 C
Solar/Wind Harmer
2.875
970257AG2-171 GEN
Solar/Wind Harmer
4.596
959311AF2-222 GEN
Solar/Wind Harmer
12.469
315737AD1-076 GEN
Solar/Wind Harmer
2.181
971157AH1-035 GEN
Solar/Wind Harmer
1.384
963181AG1-167 GEN
Solar/Wind Harmer
0.951
3144293JTRSVLE
Adder
0.287
3147133PAMPLIN
Solar/Wind Harmer
-0.029
971193AH1-056 GEN
Solar/Wind Harmer
5.892
315614AA2-178 GEN
Solar/Wind Harmer
0.971
316248AF1-058 C
Solar/Wind Harmer
0.26
960061AF2-297 GEN
Solar/Wind Harmer
4.312
316478AD1-087 GEN
Solar/Wind Harmer
0.709
316486AD2-202 GEN
Solar/Wind Harmer
0.208
971683AH1-343 GEN
Solar/Wind Harmer
3.31
942461AE2-259 GEN
Solar/Wind Harmer
1.111
316283AC2-100 C
Solar/Wind Harmer
0.613
970909AG2-566 GEN
Solar/Wind Harmer
0.604
315839AE2-212 C
Solar/Wind Helper
0.197
316003AC1-222 GEN
Solar/Wind Harmer
0.792
315693AD1-088 GEN
Solar/Wind Harmer
4.021
315687AD1-152 GEN
Solar/Wind Harmer
0.963
962491AG1-098 GEN
Solar/Wind Harmer
5.32
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.321
316181AB2-040 GEN
Solar/Wind Harmer
5.319
3145796HORNRTN
Solar/Wind Harmer
-0.106
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3145593CAROLNA
Solar/Wind Harmer
-0.029
3145593CAROLNA
Solar/Wind Harmer
-0.029
966811AG1-552 GEN
Solar/Wind Harmer
3.246
3145593CAROLNA
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
3.321
3145783HORNRTN
Solar/Wind Harmer
2.657
3145783HORNRTN
Solar/Wind Harmer
0.83
3145783HORNRTN
Solar/Wind Harmer
0.332
316426AA2-053 GEN
Solar/Wind Harmer
2.732
316274AC1-208 GEN
Solar/Wind Harmer
2.525
961601AG1-000A GEN
Solar/Wind Harmer
7.953
316263AC1-034 GEN
Solar/Wind Harmer
9.296
3145493TOT1
Solar/Wind Harmer
0.286
3145453TOT5
Solar/Wind Harmer
0.172
3145603CNETO
Solar/Wind Harmer
0.115
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.502
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.029
3145933PARMELE
Solar/Wind Harmer
-0.015
313527AB2-043 GEN
Solar/Wind Harmer
2.389
939181AE1-148 GEN
Solar/Wind Harmer
8.242
316065AD1-022 GEN
Solar/Wind Harmer
6.465
970323AG2-213 GEN
Solar/Wind Harmer
6.127
971775AH1-396 GEN
Solar/Wind Harmer
0.873
316034AC1-036 C
Solar/Wind Harmer
0.227
962561AG1-105 GEN
Solar/Wind Harmer
6.584
964791AG1-342 GEN
Solar/Wind Harmer
2.385
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
958211AF2-115 GEN
Solar/Wind Harmer
1.584
963191AG1-168 GEN
Solar/Wind Harmer
0.951
3144293JTRSVLE
Adder
0.287
3144293JTRSVLE
Adder
0.242
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.194
315742AE1-103 GEN
Solar/Wind Harmer
0.847
971741AH1-377 GEN
Solar/Wind Harmer
7.846
316222AC1-221 GEN
Solar/Wind Harmer
0.662
970301AG2-198 GEN
Solar/Wind Harmer
3.182
3144356SAPONY
Solar/Wind Helper
0.972
316240AF1-291 C
Solar/Wind Helper
0.168
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.852
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.588
MECLTFEXP_MEC->PJM
CLTF
1.327
SIGELTFEXP_SIGE->PJM
CLTF
0.04
CPLELTFEXP_CPLE->PJM
CLTF
4.451
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.221
LAGNLTFEXP_LAGN->PJM
CLTF
2.679
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.709
TVALTFEXP_TVA->PJM
CLTF
1.336
NYPJM->LTFIMP_NY
CLTF
0.49
LGEELTFEXP_LGEE->PJM
CLTF
0.481
WECLTFEXP_WEC->PJM
CLTF
0.25

Details for 6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.01 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1004.4
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.27
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3151261ROARAP2
50/50
0.313
3151591KERR 2
50/50
0.27
316365GEN2_N
Solar/Wind Harmer
3.902
966621AG1-532 GEN
Solar/Wind Harmer
0.942
313506AB2-031 GEN
Solar/Wind Harmer
3.065
3147043LAWRENC
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.142
3145796HORNRTN
Solar/Wind Harmer
-0.036
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
315724AD1-057 GEN
Solar/Wind Harmer
1.563
316210AC1-098 GEN
Solar/Wind Harmer
3.461
316327AA2-057 GEN
Solar/Wind Harmer
2.172
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
0.432
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
8.054
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3147043LAWRENC
50/50
3.141
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.27
3151581KERR 1
50/50
0.096
316023GEN1_S
Solar/Wind Harmer
3.902
960081AF2-299 GEN
Solar/Wind Harmer
5.22
971795AH1-408 GEN
Solar/Wind Harmer
29.849
316011AB1-132 GEN
Solar/Wind Harmer
8.002
962571AG1-106 GEN
Solar/Wind Harmer
5.498
3145796HORNRTN
Solar/Wind Harmer
-0.117
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145783HORNRTN
Solar/Wind Harmer
-0.028
315722AD1-056 GEN
Solar/Wind Harmer
2.841
316190AA2-174 GEN
Solar/Wind Harmer
0.332
316212AC1-099_GEN
Solar/Wind Harmer
1.923
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
-0.082
3145823KELFORD
Solar/Wind Harmer
-0.02
316359AB2-059 GEN
Solar/Wind Harmer
2.674
316049AB1-081 GEN
Solar/Wind Harmer
2.14
3142053HEARTS
Solar/Wind Harmer
0.233
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316129AC1-054 GEN
Solar/Wind Harmer
1.719
971065AG2-659 GEN
Solar/Wind Harmer
9.387
3145683EARLEYS
Solar/Wind Harmer
-0.019
961671AG1-007 GEN
Solar/Wind Harmer
0.234
3146083TARBORO
Solar/Wind Harmer
-0.018
3145493TOT1
Solar/Wind Harmer
0.549
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.072
3145893MURPHYS
Solar/Wind Harmer
0.534
316494AC1-189 GEN
Solar/Wind Harmer
1.84
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146293MARTNCO
Solar/Wind Harmer
0.091
316237AB2-079_GEN
Solar/Wind Harmer
0.437
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.442
316174AB2-169 GEN
Solar/Wind Harmer
2.088
3145963POPLR C
Solar/Wind Harmer
-0.013
970685AG2-442 GEN
Solar/Wind Harmer
9.773
970401AG2-262 GEN
Solar/Wind Harmer
0.729
963171AG1-166 GEN
Solar/Wind Harmer
1.268
971563AH1-280 GEN
Solar/Wind Harmer
1.268
3144293JTRSVLE
Adder
0.287
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.436
957481AF2-042 GEN
Solar/Wind Harmer
25.485
316003AC1-222 GEN
Solar/Wind Harmer
0.792
315693AD1-088 GEN
Solar/Wind Harmer
4.021
315687AD1-152 GEN
Solar/Wind Harmer
0.963
962491AG1-098 GEN
Solar/Wind Harmer
5.32
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.321
316181AB2-040 GEN
Solar/Wind Harmer
5.319
3145796HORNRTN
Solar/Wind Harmer
-0.106
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3145593CAROLNA
Solar/Wind Harmer
-0.029
3145593CAROLNA
Solar/Wind Harmer
-0.029
966811AG1-552 GEN
Solar/Wind Harmer
3.246
3145593CAROLNA
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
3.321
3145783HORNRTN
Solar/Wind Harmer
2.657
3145783HORNRTN
Solar/Wind Harmer
0.83
3145783HORNRTN
Solar/Wind Harmer
0.332
316426AA2-053 GEN
Solar/Wind Harmer
2.732
316274AC1-208 GEN
Solar/Wind Harmer
2.525
961601AG1-000A GEN
Solar/Wind Harmer
7.953
316263AC1-034 GEN
Solar/Wind Harmer
9.296
3145493TOT1
Solar/Wind Harmer
0.286
3145453TOT5
Solar/Wind Harmer
0.172
3145603CNETO
Solar/Wind Harmer
0.115
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.502
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.029
3145933PARMELE
Solar/Wind Harmer
-0.015
313527AB2-043 GEN
Solar/Wind Harmer
2.389
939181AE1-148 GEN
Solar/Wind Harmer
8.242
316065AD1-022 GEN
Solar/Wind Harmer
6.465
970323AG2-213 GEN
Solar/Wind Harmer
6.127
971775AH1-396 GEN
Solar/Wind Harmer
0.873
316034AC1-036 C
Solar/Wind Harmer
0.227
962561AG1-105 GEN
Solar/Wind Harmer
6.584
964791AG1-342 GEN
Solar/Wind Harmer
2.385
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
958211AF2-115 GEN
Solar/Wind Harmer
1.584
963191AG1-168 GEN
Solar/Wind Harmer
0.951
3144293JTRSVLE
Adder
0.287
3144293JTRSVLE
Adder
0.242
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.194
315742AE1-103 GEN
Solar/Wind Harmer
0.847
971741AH1-377 GEN
Solar/Wind Harmer
7.846
316222AC1-221 GEN
Solar/Wind Harmer
0.662
970301AG2-198 GEN
Solar/Wind Harmer
3.182
3144356SAPONY
Solar/Wind Helper
0.972
316240AF1-291 C
Solar/Wind Helper
0.168
316317KELFORD C
Solar/Wind Harmer
0.938
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
316463AE2-346 GEN
Solar/Wind Harmer
0.3
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.318
3146073TAR RVR
Solar/Wind Harmer
-0.018
3146083TARBORO
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.25
961681AG1-008 GEN
Solar/Wind Harmer
14.25
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.297
3156081AA2-088 GEN
Solar/Wind Harmer
5.472
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.843
316131AB2-060 GEN
Solar/Wind Harmer
1.567
964241AG1-285 GEN
Solar/Wind Harmer
10.81
3146206CASHIE
Solar/Wind Harmer
-0.014
3145963POPLR C
Solar/Wind Harmer
-0.013
315785AD2-033 C
Solar/Wind Harmer
2.875
970257AG2-171 GEN
Solar/Wind Harmer
4.596
959311AF2-222 GEN
Solar/Wind Harmer
12.469
315737AD1-076 GEN
Solar/Wind Harmer
2.181
971157AH1-035 GEN
Solar/Wind Harmer
1.384
963181AG1-167 GEN
Solar/Wind Harmer
0.951
3144293JTRSVLE
Adder
0.287
3147133PAMPLIN
Solar/Wind Harmer
-0.029
971193AH1-056 GEN
Solar/Wind Harmer
5.892
315614AA2-178 GEN
Solar/Wind Harmer
0.971
316248AF1-058 C
Solar/Wind Harmer
0.26
960061AF2-297 GEN
Solar/Wind Harmer
4.312
316478AD1-087 GEN
Solar/Wind Harmer
0.709
316486AD2-202 GEN
Solar/Wind Harmer
0.208
971683AH1-343 GEN
Solar/Wind Harmer
3.31
942461AE2-259 GEN
Solar/Wind Harmer
1.111
316283AC2-100 C
Solar/Wind Harmer
0.613
970909AG2-566 GEN
Solar/Wind Harmer
0.604
315839AE2-212 C
Solar/Wind Helper
0.197
3151621KERR 5
50/50
0.27
3151631KERR 6
50/50
0.27
3151641KERR 7
50/50
0.27
946281AF1-292 GEN
Solar/Wind Harmer
1.039
316087AB2-174 GEN
Solar/Wind Harmer
5.796
315652AC1-086 GEN
Solar/Wind Harmer
43.026
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.014
3137643SOCKMAN
Solar/Wind Harmer
-0.132
315607AA1-063A GEN
Solar/Wind Harmer
2.468
3146043SEABORD
Solar/Wind Harmer
-0.024
3146033SCOT NK
Solar/Wind Harmer
-0.084
316319Z2-044 C
Solar/Wind Harmer
1.139
970831AG2-522 GEN
Solar/Wind Harmer
10.247
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.162
961941AG1-037 GEN
Solar/Wind Harmer
0.139
3145513AHOSKIE
Solar/Wind Harmer
-0.018
3145573BETHELC
Solar/Wind Harmer
-0.018
3145573BETHELC
Solar/Wind Harmer
-0.018
316318V4-068
Solar/Wind Harmer
0.448
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
316420AA1-050 GEN
Solar/Wind Harmer
2.044
965291AG1-394 GEN
Solar/Wind Harmer
1.566
957861AF2-080 GEN
Solar/Wind Harmer
7.484
316005AA1-067
Solar/Wind Harmer
0.313
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
2.03
316239AB2-077_GEN
Solar/Wind Harmer
0.437
316238AB2-078_GEN
Solar/Wind Harmer
0.437
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
6.024
971443AH1-215 GEN
Solar/Wind Harmer
2.432
3144303KENBRDG
Solar/Wind Harmer
-0.01
315732AD1-074 GEN1
Solar/Wind Harmer
2.32
315733AD1-074 GEN2
Solar/Wind Harmer
2.32
315735AD1-075 GEN1
Solar/Wind Harmer
1.16
970683AG2-441 GEN
Solar/Wind Harmer
8.726
970681AG2-440 GEN
Solar/Wind Harmer
6.981
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
946301AF1-294 GEN
Solar/Wind Harmer
2.598
961791AG1-021 GEN
Solar/Wind Harmer
1.268
316118AC1-105 GEN
Solar/Wind Harmer
0.679
315657AE1-056 GEN
Solar/Wind Harmer
3.535
315816AE2-034 GEN
Solar/Wind Harmer
0.728
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
970865AG2-541 GEN
Solar/Wind Harmer
2.933
316315AB2-025 C
Solar/Wind Helper
0.826
3143316POE
Solar/Wind Helper
0.688
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.852
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.588
MECLTFEXP_MEC->PJM
CLTF
1.327
SIGELTFEXP_SIGE->PJM
CLTF
0.04
CPLELTFEXP_CPLE->PJM
CLTF
4.451
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.221
LAGNLTFEXP_LAGN->PJM
CLTF
2.679
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.709
TVALTFEXP_TVA->PJM
CLTF
1.336
NYPJM->LTFIMP_NY
CLTF
0.49
LGEELTFEXP_LGEE->PJM
CLTF
0.481
WECLTFEXP_WEC->PJM
CLTF
0.25

Details for 6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.0 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1004.26
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3147043LAWRENC
50/50
3.141
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.27
3151581KERR 1
50/50
0.096
316023GEN1_S
Solar/Wind Harmer
3.902
960081AF2-299 GEN
Solar/Wind Harmer
5.22
971795AH1-408 GEN
Solar/Wind Harmer
29.849
316011AB1-132 GEN
Solar/Wind Harmer
8.002
962571AG1-106 GEN
Solar/Wind Harmer
5.498
3145796HORNRTN
Solar/Wind Harmer
-0.117
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145783HORNRTN
Solar/Wind Harmer
-0.028
315722AD1-056 GEN
Solar/Wind Harmer
2.841
316190AA2-174 GEN
Solar/Wind Harmer
0.332
316212AC1-099_GEN
Solar/Wind Harmer
1.922
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
-0.082
3145823KELFORD
Solar/Wind Harmer
-0.02
316359AB2-059 GEN
Solar/Wind Harmer
2.673
316049AB1-081 GEN
Solar/Wind Harmer
2.14
3142053HEARTS
Solar/Wind Harmer
0.233
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316129AC1-054 GEN
Solar/Wind Harmer
1.719
971065AG2-659 GEN
Solar/Wind Harmer
9.387
3145683EARLEYS
Solar/Wind Harmer
-0.019
961671AG1-007 GEN
Solar/Wind Harmer
0.234
3146083TARBORO
Solar/Wind Harmer
-0.018
3145493TOT1
Solar/Wind Harmer
0.549
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.072
3145893MURPHYS
Solar/Wind Harmer
0.534
316494AC1-189 GEN
Solar/Wind Harmer
1.84
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146293MARTNCO
Solar/Wind Harmer
0.091
316237AB2-079_GEN
Solar/Wind Harmer
0.437
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.442
316174AB2-169 GEN
Solar/Wind Harmer
2.088
3145963POPLR C
Solar/Wind Harmer
-0.013
970685AG2-442 GEN
Solar/Wind Harmer
9.777
970401AG2-262 GEN
Solar/Wind Harmer
0.729
963171AG1-166 GEN
Solar/Wind Harmer
1.268
971563AH1-280 GEN
Solar/Wind Harmer
1.268
3144293JTRSVLE
Adder
0.287
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.436
957481AF2-042 GEN
Solar/Wind Harmer
25.422
316003AC1-222 GEN
Solar/Wind Harmer
0.792
315693AD1-088 GEN
Solar/Wind Harmer
4.029
315687AD1-152 GEN
Solar/Wind Harmer
0.962
962491AG1-098 GEN
Solar/Wind Harmer
5.33
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.321
316181AB2-040 GEN
Solar/Wind Harmer
5.319
3145796HORNRTN
Solar/Wind Harmer
-0.106
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3145593CAROLNA
Solar/Wind Harmer
-0.029
3145593CAROLNA
Solar/Wind Harmer
-0.029
966811AG1-552 GEN
Solar/Wind Harmer
3.246
3145593CAROLNA
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
3.321
3145783HORNRTN
Solar/Wind Harmer
2.657
3145783HORNRTN
Solar/Wind Harmer
0.83
3145783HORNRTN
Solar/Wind Harmer
0.332
316426AA2-053 GEN
Solar/Wind Harmer
2.732
316274AC1-208 GEN
Solar/Wind Harmer
2.525
961601AG1-000A GEN
Solar/Wind Harmer
7.953
316263AC1-034 GEN
Solar/Wind Harmer
9.295
3145493TOT1
Solar/Wind Harmer
0.286
3145453TOT5
Solar/Wind Harmer
0.172
3145603CNETO
Solar/Wind Harmer
0.115
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.502
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.029
3145933PARMELE
Solar/Wind Harmer
-0.015
313527AB2-043 GEN
Solar/Wind Harmer
2.389
939181AE1-148 GEN
Solar/Wind Harmer
8.243
316065AD1-022 GEN
Solar/Wind Harmer
6.465
970323AG2-213 GEN
Solar/Wind Harmer
6.129
971775AH1-396 GEN
Solar/Wind Harmer
0.873
316034AC1-036 C
Solar/Wind Harmer
0.227
962561AG1-105 GEN
Solar/Wind Harmer
6.583
964791AG1-342 GEN
Solar/Wind Harmer
2.385
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
958211AF2-115 GEN
Solar/Wind Harmer
1.585
963191AG1-168 GEN
Solar/Wind Harmer
0.951
3144293JTRSVLE
Adder
0.287
3144293JTRSVLE
Adder
0.242
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.169
315742AE1-103 GEN
Solar/Wind Harmer
0.847
971741AH1-377 GEN
Solar/Wind Harmer
7.86
316222AC1-221 GEN
Solar/Wind Harmer
0.662
970301AG2-198 GEN
Solar/Wind Harmer
3.187
3144356SAPONY
Solar/Wind Helper
0.972
316240AF1-291 C
Solar/Wind Helper
0.168
3151391GASTONA
50/50
0.921
3151411GASTONB
50/50
0.921
3151261ROARAP2
50/50
0.313
3151591KERR 2
50/50
0.27
316365GEN2_N
Solar/Wind Harmer
3.902
966621AG1-532 GEN
Solar/Wind Harmer
0.942
313506AB2-031 GEN
Solar/Wind Harmer
3.065
3147043LAWRENC
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.142
3145796HORNRTN
Solar/Wind Harmer
-0.036
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
315724AD1-057 GEN
Solar/Wind Harmer
1.563
316210AC1-098 GEN
Solar/Wind Harmer
3.461
316327AA2-057 GEN
Solar/Wind Harmer
2.172
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
0.432
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
8.053
316317KELFORD C
Solar/Wind Harmer
0.938
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
316463AE2-346 GEN
Solar/Wind Harmer
0.3
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.318
3146073TAR RVR
Solar/Wind Harmer
-0.018
3146083TARBORO
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.25
961681AG1-008 GEN
Solar/Wind Harmer
14.25
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.297
3156081AA2-088 GEN
Solar/Wind Harmer
5.472
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.843
316131AB2-060 GEN
Solar/Wind Harmer
1.567
964241AG1-285 GEN
Solar/Wind Harmer
10.812
3146206CASHIE
Solar/Wind Harmer
-0.014
3145963POPLR C
Solar/Wind Harmer
-0.013
315785AD2-033 C
Solar/Wind Harmer
2.876
970257AG2-171 GEN
Solar/Wind Harmer
4.597
959311AF2-222 GEN
Solar/Wind Harmer
12.472
315737AD1-076 GEN
Solar/Wind Harmer
2.181
971157AH1-035 GEN
Solar/Wind Harmer
1.384
963181AG1-167 GEN
Solar/Wind Harmer
0.951
3144293JTRSVLE
Adder
0.287
3147133PAMPLIN
Solar/Wind Harmer
-0.029
971193AH1-056 GEN
Solar/Wind Harmer
5.895
315614AA2-178 GEN
Solar/Wind Harmer
0.971
316248AF1-058 C
Solar/Wind Harmer
0.26
960061AF2-297 GEN
Solar/Wind Harmer
4.309
316478AD1-087 GEN
Solar/Wind Harmer
0.709
316486AD2-202 GEN
Solar/Wind Harmer
0.207
971683AH1-343 GEN
Solar/Wind Harmer
3.309
942461AE2-259 GEN
Solar/Wind Harmer
1.112
316283AC2-100 C
Solar/Wind Harmer
0.612
970909AG2-566 GEN
Solar/Wind Harmer
0.605
315839AE2-212 C
Solar/Wind Helper
0.197
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.27
3151621KERR 5
50/50
0.27
3151631KERR 6
50/50
0.27
3151641KERR 7
50/50
0.27
946281AF1-292 GEN
Solar/Wind Harmer
1.039
316087AB2-174 GEN
Solar/Wind Harmer
5.796
315652AC1-086 GEN
Solar/Wind Harmer
43.026
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.014
3137643SOCKMAN
Solar/Wind Harmer
-0.132
315607AA1-063A GEN
Solar/Wind Harmer
2.468
3146043SEABORD
Solar/Wind Harmer
-0.024
3146033SCOT NK
Solar/Wind Harmer
-0.084
316319Z2-044 C
Solar/Wind Harmer
1.139
970831AG2-522 GEN
Solar/Wind Harmer
10.247
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.162
961941AG1-037 GEN
Solar/Wind Harmer
0.139
3145513AHOSKIE
Solar/Wind Harmer
-0.018
3145573BETHELC
Solar/Wind Harmer
-0.018
3145573BETHELC
Solar/Wind Harmer
-0.018
316318V4-068
Solar/Wind Harmer
0.448
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
316420AA1-050 GEN
Solar/Wind Harmer
2.044
965291AG1-394 GEN
Solar/Wind Harmer
1.566
957861AF2-080 GEN
Solar/Wind Harmer
7.483
316005AA1-067
Solar/Wind Harmer
0.313
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
2.03
316239AB2-077_GEN
Solar/Wind Harmer
0.437
316238AB2-078_GEN
Solar/Wind Harmer
0.437
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
6.024
971443AH1-215 GEN
Solar/Wind Harmer
2.433
3144303KENBRDG
Solar/Wind Harmer
-0.01
315732AD1-074 GEN1
Solar/Wind Harmer
2.32
315733AD1-074 GEN2
Solar/Wind Harmer
2.32
315735AD1-075 GEN1
Solar/Wind Harmer
1.16
970683AG2-441 GEN
Solar/Wind Harmer
8.729
970681AG2-440 GEN
Solar/Wind Harmer
6.983
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
946301AF1-294 GEN
Solar/Wind Harmer
2.6
961791AG1-021 GEN
Solar/Wind Harmer
1.268
316118AC1-105 GEN
Solar/Wind Harmer
0.679
315657AE1-056 GEN
Solar/Wind Harmer
3.537
315816AE2-034 GEN
Solar/Wind Harmer
0.728
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
970865AG2-541 GEN
Solar/Wind Harmer
2.932
316315AB2-025 C
Solar/Wind Helper
0.826
3143316POE
Solar/Wind Helper
0.688
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.85
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.587
MECLTFEXP_MEC->PJM
CLTF
1.327
SIGELTFEXP_SIGE->PJM
CLTF
0.04
CPLELTFEXP_CPLE->PJM
CLTF
4.45
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.218
LAGNLTFEXP_LAGN->PJM
CLTF
2.678
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.707
TVALTFEXP_TVA->PJM
CLTF
1.336
NYPJM->LTFIMP_NY
CLTF
0.49
LGEELTFEXP_LGEE->PJM
CLTF
0.481
WECLTFEXP_WEC->PJM
CLTF
0.25

Details for 6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2012-54_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2012-54_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:107.04 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:888.46
MW Contribution:2.08
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
1.161
3151411GASTONB
50/50
1.161
3147043LAWRENC
50/50
3.414
3151261ROARAP2
50/50
0.385
3151601KERR 3
50/50
0.246
3151581KERR 1
50/50
0.088
316023GEN1_S
Solar/Wind Harmer
4.384
960081AF2-299 GEN
Solar/Wind Harmer
5.827
316011AB1-132 GEN
Solar/Wind Harmer
10.086
962571AG1-106 GEN
Solar/Wind Harmer
6.93
3145796HORNRTN
Solar/Wind Harmer
-0.146
3145796HORNRTN
Solar/Wind Harmer
-0.044
971795AH1-408 GEN
Solar/Wind Harmer
32.769
316190AA2-174 GEN
Solar/Wind Harmer
0.426
3145783HORNRTN
Solar/Wind Harmer
-0.033
315722AD1-056 GEN
Solar/Wind Harmer
3.384
3146233WITAKRS
Solar/Wind Harmer
-0.088
316359AB2-059 GEN
Solar/Wind Harmer
2.933
316049AB1-081 GEN
Solar/Wind Harmer
2.347
3151361ROSEMG1
50/50
1.426
3151371ROSEMS1
50/50
0.883
3151381ROSEMG2
50/50
0.668
970535AG2-341 GEN
50/50
2.078
3145796HORNRTN
Solar/Wind Harmer
-0.133
316181AB2-040 GEN
Solar/Wind Harmer
6.101
316426AA2-053 GEN
Solar/Wind Harmer
3.505
3145593CAROLNA
Solar/Wind Harmer
-0.035
3145593CAROLNA
Solar/Wind Harmer
-0.035
966811AG1-552 GEN
Solar/Wind Harmer
3.903
3145593CAROLNA
Solar/Wind Harmer
0.288
3145783HORNRTN
Solar/Wind Harmer
3.938
3145783HORNRTN
Solar/Wind Harmer
3.15
3145783HORNRTN
Solar/Wind Harmer
0.985
3145783HORNRTN
Solar/Wind Harmer
0.394
316274AC1-208 GEN
Solar/Wind Harmer
2.719
961601AG1-000A GEN
Solar/Wind Harmer
8.791
316263AC1-034 GEN
Solar/Wind Harmer
10.196
3145493TOT1
Solar/Wind Harmer
0.283
3145453TOT5
Solar/Wind Harmer
0.17
3145603CNETO
Solar/Wind Harmer
0.113
3145893MURPHYS
Solar/Wind Harmer
0.426
3145893MURPHYS
Solar/Wind Harmer
-0.027
939181AE1-148 GEN
Solar/Wind Harmer
7.468
313527AB2-043 GEN
Solar/Wind Harmer
2.093
3146173TUNIS
Solar/Wind Harmer
-0.013
3146173TUNIS
Solar/Wind Harmer
-0.013
3151391GASTONA
50/50
1.161
3151411GASTONB
50/50
1.161
3151261ROARAP2
50/50
0.376
3151591KERR 2
50/50
0.246
316365GEN2_N
Solar/Wind Harmer
4.384
966621AG1-532 GEN
Solar/Wind Harmer
1.051
3145796HORNRTN
Solar/Wind Harmer
-0.177
3145796HORNRTN
Solar/Wind Harmer
-0.044
313506AB2-031 GEN
Solar/Wind Harmer
3.516
3147043LAWRENC
Solar/Wind Harmer
-0.024
315724AD1-057 GEN
Solar/Wind Harmer
1.861
316327AA2-057 GEN
Solar/Wind Harmer
2.326
961601AG1-000A GEN
Solar/Wind Harmer
8.903
3146233WITAKRS
Solar/Wind Harmer
0.467
3146233WITAKRS
Solar/Wind Harmer
-0.015
3138543CONSLDL
Solar/Wind Harmer
-0.015
316210AC1-098 GEN
Solar/Wind Harmer
3.389
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3146073TAR RVR
Solar/Wind Harmer
-0.018
3146083TARBORO
Solar/Wind Harmer
-0.018
3156081AA2-088 GEN
Solar/Wind Harmer
5.553
3145893MURPHYS
Solar/Wind Harmer
0.107
3145893MURPHYS
Solar/Wind Harmer
-0.015
957521AF2-046 GEN
Solar/Wind Harmer
11.382
961681AG1-008 GEN
Solar/Wind Harmer
11.382
316317KELFORD C
Solar/Wind Harmer
0.654
3145823KELFORD
Solar/Wind Harmer
-0.014
316131AB2-060 GEN
Solar/Wind Harmer
1.368
3146173TUNIS
Solar/Wind Harmer
-0.013
964241AG1-285 GEN
Solar/Wind Harmer
9.271
3145746EVERETS
Solar/Wind Harmer
-0.011
3145746EVERETS
Solar/Wind Harmer
-0.011
316463AE2-346 GEN
Solar/Wind Harmer
0.178
316140AB2-099
Solar/Wind Harmer
0.074
962331AG1-082 GEN
Solar/Wind Harmer
1.372
315785AD2-033 C
Solar/Wind Harmer
2.384
3145933PARMELE
Solar/Wind Harmer
-0.01
966801AG1-551 GEN
Solar/Wind Harmer
1.254
970257AG2-171 GEN
Solar/Wind Harmer
3.755
959311AF2-222 GEN
Solar/Wind Harmer
10.074
3145963POPLR C
Solar/Wind Harmer
-0.008
963181AG1-167 GEN
Solar/Wind Harmer
0.706
3144293JTRSVLE
Adder
0.213
3156021HOLLOMANSOL
Solar/Wind Harmer
0.928
3147133PAMPLIN
Solar/Wind Harmer
-0.021
971193AH1-056 GEN
Solar/Wind Harmer
4.188
315839AE2-212 C
Solar/Wind Helper
0.172
3151281ROARAP4
50/50
0.374
3151281ROARAP4
50/50
0.35
3151611KERR 4
50/50
0.246
3151621KERR 5
50/50
0.246
3151631KERR 6
50/50
0.246
3151641KERR 7
50/50
0.246
946281AF1-292 GEN
Solar/Wind Harmer
1.16
315652AC1-086 GEN
Solar/Wind Harmer
54.232
316087AB2-174 GEN
Solar/Wind Harmer
6.587
3145796HORNRTN
Solar/Wind Harmer
-0.141
3145796HORNRTN
Solar/Wind Harmer
-0.018
3137643SOCKMAN
Solar/Wind Harmer
-0.154
315607AA1-063A GEN
Solar/Wind Harmer
2.838
3146043SEABORD
Solar/Wind Harmer
-0.027
316319Z2-044 C
Solar/Wind Harmer
1.232
970831AG2-522 GEN
Solar/Wind Harmer
11.073
3145573BETHELC
Solar/Wind Harmer
-0.018
3145573BETHELC
Solar/Wind Harmer
-0.018
3146033SCOT NK
Solar/Wind Harmer
-0.072
965291AG1-394 GEN
Solar/Wind Harmer
1.593
316420AA1-050 GEN
Solar/Wind Harmer
1.925
316318V4-068
Solar/Wind Harmer
0.381
3145893MURPHYS
Solar/Wind Harmer
-0.041
3145893MURPHYS
Solar/Wind Harmer
-0.015
957861AF2-080 GEN
Solar/Wind Harmer
6.557
316239AB2-077_GEN
Solar/Wind Harmer
0.382
316238AB2-078_GEN
Solar/Wind Harmer
0.382
316005AA1-067
Solar/Wind Harmer
0.225
3145746EVERETS
Solar/Wind Harmer
-0.044
3145746EVERETS
Solar/Wind Harmer
-0.011
3145746EVERETS
Solar/Wind Harmer
-0.011
3145746EVERETS
Solar/Wind Harmer
-0.011
970181AG2-120 GEN
Solar/Wind Harmer
1.46
3145513AHOSKIE
Solar/Wind Harmer
0.096
961941AG1-037 GEN
Solar/Wind Harmer
0.082
3145513AHOSKIE
Solar/Wind Harmer
-0.011
971443AH1-215 GEN
Solar/Wind Harmer
1.994
3144303KENBRDG
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.01
970683AG2-441 GEN
Solar/Wind Harmer
6.829
970681AG2-440 GEN
Solar/Wind Harmer
5.464
946301AF1-294 GEN
Solar/Wind Harmer
1.931
961791AG1-021 GEN
Solar/Wind Harmer
0.942
316118AC1-105 GEN
Solar/Wind Harmer
0.483
315657AE1-056 GEN
Solar/Wind Harmer
2.513
316315AB2-025 C
Solar/Wind Helper
0.732
3143316POE
Solar/Wind Helper
0.597
3142053HEARTS
Solar/Wind Harmer
0.256
316212AC1-099_GEN
Solar/Wind Harmer
1.883
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3145543BTLEBRO
Solar/Wind Harmer
-0.017
316129AC1-054 GEN
Solar/Wind Harmer
1.824
971065AG2-659 GEN
Solar/Wind Harmer
9.783
961671AG1-007 GEN
Solar/Wind Harmer
0.231
3146083TARBORO
Solar/Wind Harmer
-0.018
3145493TOT1
Solar/Wind Harmer
0.543
3145893MURPHYS
Solar/Wind Harmer
-0.061
3145893MURPHYS
Solar/Wind Harmer
0.453
316494AC1-189 GEN
Solar/Wind Harmer
1.612
3145823KELFORD
Solar/Wind Harmer
-0.014
316237AB2-079_GEN
Solar/Wind Harmer
0.382
3146173TUNIS
Solar/Wind Harmer
-0.013
3145746EVERETS
Solar/Wind Harmer
-0.011
3145746EVERETS
Solar/Wind Harmer
-0.011
3146293MARTNCO
Solar/Wind Harmer
0.062
3145683EARLEYS
Solar/Wind Harmer
-0.01
970685AG2-442 GEN
Solar/Wind Harmer
7.649
970401AG2-262 GEN
Solar/Wind Harmer
0.56
316174AB2-169 GEN
Solar/Wind Harmer
1.265
3145963POPLR C
Solar/Wind Harmer
-0.008
963171AG1-166 GEN
Solar/Wind Harmer
0.942
971563AH1-280 GEN
Solar/Wind Harmer
0.942
3144293JTRSVLE
Adder
0.213
3145933PARMELE
Solar/Wind Harmer
-0.02
3145933PARMELE
Solar/Wind Harmer
-0.01
970323AG2-213 GEN
Solar/Wind Harmer
5.007
971775AH1-396 GEN
Solar/Wind Harmer
0.713
316034AC1-036 C
Solar/Wind Harmer
0.185
962561AG1-105 GEN
Solar/Wind Harmer
5.198
964791AG1-342 GEN
Solar/Wind Harmer
1.834
3146843MT LREL
Solar/Wind Harmer
-0.009
3146843MT LREL
Solar/Wind Harmer
-0.009
315742AE1-103 GEN
Solar/Wind Harmer
0.81
958211AF2-115 GEN
Solar/Wind Harmer
1.177
963191AG1-168 GEN
Solar/Wind Harmer
0.706
3144293JTRSVLE
Adder
0.213
3144293JTRSVLE
Adder
0.18
3147133PAMPLIN
Solar/Wind Harmer
-0.007
3147133PAMPLIN
Solar/Wind Harmer
-0.005
3144356SAPONY
Solar/Wind Helper
0.862
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.796
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.185
MECLTFEXP_MEC->PJM
CLTF
1.187
SIGELTFEXP_SIGE->PJM
CLTF
0.035
CPLELTFEXP_CPLE->PJM
CLTF
4.184
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.918
LAGNLTFEXP_LAGN->PJM
CLTF
2.459
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.164
TVALTFEXP_TVA->PJM
CLTF
1.224
NYPJM->LTFIMP_NY
CLTF
0.447
LGEELTFEXP_LGEE->PJM
CLTF
0.424
WECLTFEXP_WEC->PJM
CLTF
0.221

Details for 6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 1010-2012_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 1010-2012_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.06 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:880.33
MW Contribution:2.14
Bus #Bus NameTypeMW Contribution
3151361ROSEMG1
50/50
1.448
3151371ROSEMS1
50/50
0.897
3151381ROSEMG2
50/50
0.678
970535AG2-341 GEN
50/50
2.143
3151391GASTONA
50/50
1.178
3151411GASTONB
50/50
1.178
3147043LAWRENC
50/50
3.466
3151261ROARAP2
50/50
0.401
3151601KERR 3
50/50
0.255
3151581KERR 1
50/50
0.091
316023GEN1_S
Solar/Wind Harmer
4.421
960081AF2-299 GEN
Solar/Wind Harmer
5.909
316011AB1-132 GEN
Solar/Wind Harmer
10.237
962571AG1-106 GEN
Solar/Wind Harmer
7.034
3145796HORNRTN
Solar/Wind Harmer
-0.148
3145796HORNRTN
Solar/Wind Harmer
-0.045
971795AH1-408 GEN
Solar/Wind Harmer
33.253
3145783HORNRTN
Solar/Wind Harmer
-0.034
315722AD1-056 GEN
Solar/Wind Harmer
3.448
316190AA2-174 GEN
Solar/Wind Harmer
0.39
3146233WITAKRS
Solar/Wind Harmer
-0.091
316212AC1-099_GEN
Solar/Wind Harmer
1.994
316359AB2-059 GEN
Solar/Wind Harmer
3.015
316049AB1-081 GEN
Solar/Wind Harmer
2.413
3142053HEARTS
Solar/Wind Harmer
0.263
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3145543BTLEBRO
Solar/Wind Harmer
-0.018
316129AC1-054 GEN
Solar/Wind Harmer
1.896
971065AG2-659 GEN
Solar/Wind Harmer
10.164
961671AG1-007 GEN
Solar/Wind Harmer
0.238
3146083TARBORO
Solar/Wind Harmer
-0.019
3145493TOT1
Solar/Wind Harmer
0.559
3146263WOODLND
Solar/Wind Harmer
-0.018
3145823KELFORD
Solar/Wind Harmer
-0.016
316494AC1-189 GEN
Solar/Wind Harmer
1.673
316237AB2-079_GEN
Solar/Wind Harmer
0.392
3145746EVERETS
Solar/Wind Harmer
-0.012
3145746EVERETS
Solar/Wind Harmer
-0.012
3145683EARLEYS
Solar/Wind Harmer
-0.012
3146293MARTNCO
Solar/Wind Harmer
0.065
970685AG2-442 GEN
Solar/Wind Harmer
7.857
3146173TUNIS
Solar/Wind Harmer
-0.009
970401AG2-262 GEN
Solar/Wind Harmer
0.576
316174AB2-169 GEN
Solar/Wind Harmer
1.341
3151391GASTONA
50/50
1.178
3151411GASTONB
50/50
1.178
3151261ROARAP2
50/50
0.391
3151591KERR 2
50/50
0.255
316365GEN2_N
Solar/Wind Harmer
4.421
966621AG1-532 GEN
Solar/Wind Harmer
1.066
3145796HORNRTN
Solar/Wind Harmer
-0.18
3145796HORNRTN
Solar/Wind Harmer
-0.045
313506AB2-031 GEN
Solar/Wind Harmer
3.601
3147043LAWRENC
Solar/Wind Harmer
-0.024
315724AD1-057 GEN
Solar/Wind Harmer
1.896
316327AA2-057 GEN
Solar/Wind Harmer
2.42
3146233WITAKRS
Solar/Wind Harmer
0.483
3146233WITAKRS
Solar/Wind Harmer
-0.016
3138543CONSLDL
Solar/Wind Harmer
-0.015
961601AG1-000A GEN
Solar/Wind Harmer
9.12
316210AC1-098 GEN
Solar/Wind Harmer
3.589
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3146073TAR RVR
Solar/Wind Harmer
-0.019
3146083TARBORO
Solar/Wind Harmer
-0.019
3146263WOODLND
Solar/Wind Harmer
-0.018
316317KELFORD C
Solar/Wind Harmer
0.734
3145823KELFORD
Solar/Wind Harmer
-0.016
3151281ROARAP4
50/50
0.39
3151281ROARAP4
50/50
0.365
3151611KERR 4
50/50
0.255
3151621KERR 5
50/50
0.255
3151631KERR 6
50/50
0.255
3151641KERR 7
50/50
0.255
946281AF1-292 GEN
Solar/Wind Harmer
1.176
315652AC1-086 GEN
Solar/Wind Harmer
55.047
316087AB2-174 GEN
Solar/Wind Harmer
6.724
3145796HORNRTN
Solar/Wind Harmer
-0.144
3145796HORNRTN
Solar/Wind Harmer
-0.018
3137643SOCKMAN
Solar/Wind Harmer
-0.159
316319Z2-044 C
Solar/Wind Harmer
1.275
970831AG2-522 GEN
Solar/Wind Harmer
11.512
3146033SCOT NK
Solar/Wind Harmer
-0.078
3145573BETHELC
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
316420AA1-050 GEN
Solar/Wind Harmer
1.988
957861AF2-080 GEN
Solar/Wind Harmer
6.801
316239AB2-077_GEN
Solar/Wind Harmer
0.392
316238AB2-078_GEN
Solar/Wind Harmer
0.392
316005AA1-067
Solar/Wind Harmer
0.236
3145746EVERETS
Solar/Wind Harmer
-0.046
3145746EVERETS
Solar/Wind Harmer
-0.012
3145746EVERETS
Solar/Wind Harmer
-0.012
3145746EVERETS
Solar/Wind Harmer
-0.012
970181AG2-120 GEN
Solar/Wind Harmer
1.534
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.012
3145683EARLEYS
Solar/Wind Harmer
-0.012
971443AH1-215 GEN
Solar/Wind Harmer
2.047
3145513AHOSKIE
Solar/Wind Harmer
0.09
961941AG1-037 GEN
Solar/Wind Harmer
0.078
3145513AHOSKIE
Solar/Wind Harmer
-0.01
3144303KENBRDG
Solar/Wind Harmer
-0.008
970683AG2-441 GEN
Solar/Wind Harmer
7.015
970681AG2-440 GEN
Solar/Wind Harmer
5.612
946301AF1-294 GEN
Solar/Wind Harmer
1.985
961791AG1-021 GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
0.497
315657AE1-056 GEN
Solar/Wind Harmer
2.584
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
3146206CASHIE
Solar/Wind Harmer
-0.006
970601AG2-382 GEN
Solar/Wind Harmer
2.791
316315AB2-025 C
Solar/Wind Helper
0.728
3143316POE
Solar/Wind Helper
0.602
3145796HORNRTN
Solar/Wind Harmer
-0.135
316181AB2-040 GEN
Solar/Wind Harmer
6.25
3145593CAROLNA
Solar/Wind Harmer
-0.036
3145593CAROLNA
Solar/Wind Harmer
-0.036
966811AG1-552 GEN
Solar/Wind Harmer
4.066
3145593CAROLNA
Solar/Wind Harmer
0.3
3145783HORNRTN
Solar/Wind Harmer
4.104
3145783HORNRTN
Solar/Wind Harmer
3.283
3145783HORNRTN
Solar/Wind Harmer
1.026
3145783HORNRTN
Solar/Wind Harmer
0.41
316426AA2-053 GEN
Solar/Wind Harmer
3.206
316274AC1-208 GEN
Solar/Wind Harmer
2.846
961601AG1-000A GEN
Solar/Wind Harmer
9.006
316263AC1-034 GEN
Solar/Wind Harmer
10.482
3145493TOT1
Solar/Wind Harmer
0.292
3145453TOT5
Solar/Wind Harmer
0.175
3145603CNETO
Solar/Wind Harmer
0.117
939181AE1-148 GEN
Solar/Wind Harmer
7.724
313527AB2-043 GEN
Solar/Wind Harmer
2.147
3145933PARMELE
Solar/Wind Harmer
-0.021
3145933PARMELE
Solar/Wind Harmer
-0.011
970323AG2-213 GEN
Solar/Wind Harmer
5.14
971775AH1-396 GEN
Solar/Wind Harmer
0.732
316034AC1-036 C
Solar/Wind Harmer
0.19
962561AG1-105 GEN
Solar/Wind Harmer
5.343
3146173TUNIS
Solar/Wind Harmer
-0.009
3146173TUNIS
Solar/Wind Harmer
-0.009
964791AG1-342 GEN
Solar/Wind Harmer
1.886
3146843MT LREL
Solar/Wind Harmer
-0.009
3146843MT LREL
Solar/Wind Harmer
-0.009
958211AF2-115 GEN
Solar/Wind Harmer
1.21
963191AG1-168 GEN
Solar/Wind Harmer
0.726
3144293JTRSVLE
Adder
0.219
3144293JTRSVLE
Adder
0.185
3145963POPLR C
Solar/Wind Harmer
-0.008
963171AG1-166 GEN
Solar/Wind Harmer
0.968
971563AH1-280 GEN
Solar/Wind Harmer
0.968
3144293JTRSVLE
Adder
0.219
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.19
3146206CASHIE
Solar/Wind Harmer
-0.006
971547AH1-271 GEN
Solar/Wind Harmer
1.595
316131AB2-060 GEN
Solar/Wind Harmer
1.403
964241AG1-285 GEN
Solar/Wind Harmer
9.513
3145746EVERETS
Solar/Wind Harmer
-0.012
3145746EVERETS
Solar/Wind Harmer
-0.012
315785AD2-033 C
Solar/Wind Harmer
2.447
3145933PARMELE
Solar/Wind Harmer
-0.011
966801AG1-551 GEN
Solar/Wind Harmer
1.322
316463AE2-346 GEN
Solar/Wind Harmer
0.167
316140AB2-099
Solar/Wind Harmer
0.07
962331AG1-082 GEN
Solar/Wind Harmer
1.289
970257AG2-171 GEN
Solar/Wind Harmer
3.855
959311AF2-222 GEN
Solar/Wind Harmer
10.344
3146173TUNIS
Solar/Wind Harmer
-0.009
3145963POPLR C
Solar/Wind Harmer
-0.008
963181AG1-167 GEN
Solar/Wind Harmer
0.726
3144293JTRSVLE
Adder
0.219
3156021HOLLOMANSOL
Solar/Wind Harmer
1.032
957521AF2-046 GEN
Solar/Wind Harmer
5.637
961681AG1-008 GEN
Solar/Wind Harmer
5.637
3147133PAMPLIN
Solar/Wind Harmer
-0.022
971193AH1-056 GEN
Solar/Wind Harmer
4.307
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
3146206CASHIE
Solar/Wind Harmer
-0.006
315839AE2-212 C
Solar/Wind Helper
0.173
3147133PAMPLIN
Solar/Wind Harmer
-0.007
3147133PAMPLIN
Solar/Wind Harmer
-0.006
3145893MURPHYS
Solar/Wind Harmer
0.179
3145893MURPHYS
Solar/Wind Harmer
-0.012
3144356SAPONY
Solar/Wind Helper
0.857
316240AF1-291 C
Solar/Wind Helper
0.15
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.238
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.367
MECLTFEXP_MEC->PJM
CLTF
1.247
SIGELTFEXP_SIGE->PJM
CLTF
0.037
CPLELTFEXP_CPLE->PJM
CLTF
4.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.503
LAGNLTFEXP_LAGN->PJM
CLTF
2.563
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.458
TVALTFEXP_TVA->PJM
CLTF
1.275
NYPJM->LTFIMP_NY
CLTF
0.451
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.233

Details for 6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6OTTERDAM-6ENCLAVE 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.76 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:710.98
MW Contribution:1.74
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.917
3151411GASTONB
50/50
0.917
3147043LAWRENC
50/50
3.005
3151261ROARAP2
50/50
0.311
3151601KERR 3
50/50
0.204
3151581KERR 1
50/50
0.073
3144293JTRSVLE
50/50
0.19
316023GEN1_S
Solar/Wind Harmer
1.156
960081AF2-299 GEN
Solar/Wind Harmer
3.909
971795AH1-408 GEN
Solar/Wind Harmer
22.85
316011AB1-132 GEN
Solar/Wind Harmer
6.163
962571AG1-106 GEN
Solar/Wind Harmer
4.823
3145796HORNRTN
Solar/Wind Harmer
1.041
3145796HORNRTN
Solar/Wind Harmer
0.315
3145783HORNRTN
Solar/Wind Harmer
0.242
315722AD1-056 GEN
Solar/Wind Harmer
1.516
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
0.998
3146263WOODLND
Solar/Wind Harmer
0.189
3146233WITAKRS
Solar/Wind Harmer
0.716
3145823KELFORD
Solar/Wind Harmer
0.176
316359AB2-059 GEN
Solar/Wind Harmer
0.622
316049AB1-081 GEN
Solar/Wind Harmer
0.992
3142053HEARTS
Solar/Wind Harmer
0.305
3145543BTLEBRO
Solar/Wind Harmer
0.172
3145543BTLEBRO
Solar/Wind Harmer
0.138
3145683EARLEYS
Solar/Wind Harmer
0.166
3146173TUNIS
Solar/Wind Harmer
0.163
961671AG1-007 GEN
Solar/Wind Harmer
0.025
3146083TARBORO
Solar/Wind Harmer
0.163
3145493TOT1
Solar/Wind Harmer
0.723
3145893MURPHYS
Solar/Wind Harmer
0.637
3145893MURPHYS
Solar/Wind Harmer
0.709
316129AC1-054 GEN
Solar/Wind Harmer
0.569
316494AC1-189 GEN
Solar/Wind Harmer
0.51
971065AG2-659 GEN
Solar/Wind Harmer
6.081
3145746EVERETS
Solar/Wind Harmer
0.137
3145746EVERETS
Solar/Wind Harmer
0.137
3146293MARTNCO
Solar/Wind Harmer
0.122
3146206CASHIE
Solar/Wind Harmer
0.125
971547AH1-271 GEN
Solar/Wind Harmer
2.665
316174AB2-169 GEN
Solar/Wind Harmer
0.003
3145963POPLR C
Solar/Wind Harmer
0.119
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3145663CRESWEL
Solar/Wind Harmer
0.236
971163AH1-040 GEN
Solar/Wind Harmer
6.734
970685AG2-442 GEN
Solar/Wind Harmer
4.905
970401AG2-262 GEN
Solar/Wind Harmer
0.382
3130156CHOWAN
Solar/Wind Harmer
0.061
963171AG1-166 GEN
Solar/Wind Harmer
0.3
971563AH1-280 GEN
Solar/Wind Harmer
0.601
3151281ROARAP4
50/50
0.303
3151281ROARAP4
50/50
0.283
3151151S HAMPT1
50/50
0.289
3151611KERR 4
50/50
0.204
3151621KERR 5
50/50
0.204
3151631KERR 6
50/50
0.204
3151641KERR 7
50/50
0.204
316087AB2-174 GEN
Solar/Wind Harmer
0.01
315652AC1-086 GEN
Solar/Wind Harmer
37.288
3145796HORNRTN
Solar/Wind Harmer
1.01
3145796HORNRTN
Solar/Wind Harmer
0.126
3137643SOCKMAN
Solar/Wind Harmer
1.149
315607AA1-063A GEN
Solar/Wind Harmer
0.435
3146043SEABORD
Solar/Wind Harmer
0.207
3146033SCOT NK
Solar/Wind Harmer
0.741
316319Z2-044 C
Solar/Wind Harmer
0
3145683EARLEYS
Solar/Wind Harmer
0.333
3145683EARLEYS
Solar/Wind Harmer
0.166
3145683EARLEYS
Solar/Wind Harmer
0.166
3145513AHOSKIE
Solar/Wind Harmer
0.345
3145513AHOSKIE
Solar/Wind Harmer
0.165
3145573BETHELC
Solar/Wind Harmer
0.163
3145573BETHELC
Solar/Wind Harmer
0.163
970831AG2-522 GEN
Solar/Wind Harmer
6.862
3145893MURPHYS
Solar/Wind Harmer
0.43
3145893MURPHYS
Solar/Wind Harmer
0.159
316420AA1-050 GEN
Solar/Wind Harmer
0.005
965291AG1-394 GEN
Solar/Wind Harmer
0.694
957861AF2-080 GEN
Solar/Wind Harmer
6.503
316005AA1-067
Solar/Wind Harmer
0.147
3145746EVERETS
Solar/Wind Harmer
0.545
3145746EVERETS
Solar/Wind Harmer
0.137
3145746EVERETS
Solar/Wind Harmer
0.137
3145746EVERETS
Solar/Wind Harmer
0.137
970181AG2-120 GEN
Solar/Wind Harmer
1.706
3146206CASHIE
Solar/Wind Harmer
0.125
970601AG2-382 GEN
Solar/Wind Harmer
4.665
315732AD1-074 GEN1
Solar/Wind Harmer
0.604
315733AD1-074 GEN2
Solar/Wind Harmer
0.604
315735AD1-075 GEN1
Solar/Wind Harmer
0.303
3130546PLYMOUTH
Solar/Wind Harmer
0.102
3151361ROSEMG1
50/50
1.137
3151371ROSEMS1
50/50
0.704
3151381ROSEMG2
50/50
0.532
970535AG2-341 GEN
50/50
1.744
3144293JTRSVLE
50/50
0.19
3144293JTRSVLE
50/50
0.16
316181AB2-040 GEN
Solar/Wind Harmer
0.483
3145796HORNRTN
Solar/Wind Harmer
0.947
3142666NORTHAMPTON
Solar/Wind Harmer
0.313
3142666NORTHAMPTON
Solar/Wind Harmer
0.313
3142666NORTHAMPTON
Solar/Wind Harmer
0.313
3142666NORTHAMPTON
Solar/Wind Harmer
0.188
3145593CAROLNA
Solar/Wind Harmer
0.25
3145593CAROLNA
Solar/Wind Harmer
0.25
966811AG1-552 GEN
Solar/Wind Harmer
2.71
3145593CAROLNA
Solar/Wind Harmer
0.311
3145783HORNRTN
Solar/Wind Harmer
4.313
3145783HORNRTN
Solar/Wind Harmer
3.451
3145783HORNRTN
Solar/Wind Harmer
1.078
3145783HORNRTN
Solar/Wind Harmer
0.431
316426AA2-053 GEN
Solar/Wind Harmer
0.793
316274AC1-208 GEN
Solar/Wind Harmer
1.059
961601AG1-000A GEN
Solar/Wind Harmer
3.149
316263AC1-034 GEN
Solar/Wind Harmer
6.585
3146173TUNIS
Solar/Wind Harmer
0.163
3146173TUNIS
Solar/Wind Harmer
0.163
3145493TOT1
Solar/Wind Harmer
0.377
3145453TOT5
Solar/Wind Harmer
0.226
3145603CNETO
Solar/Wind Harmer
0.151
3145893MURPHYS
Solar/Wind Harmer
1.067
3145893MURPHYS
Solar/Wind Harmer
0.287
3145933PARMELE
Solar/Wind Harmer
0.263
3145933PARMELE
Solar/Wind Harmer
0.131
316065AD1-022 GEN
Solar/Wind Harmer
5.42
939181AE1-148 GEN
Solar/Wind Harmer
4.721
313527AB2-043 GEN
Solar/Wind Harmer
0.001
315742AE1-103 GEN
Solar/Wind Harmer
0.001
970323AG2-213 GEN
Solar/Wind Harmer
3.223
971775AH1-396 GEN
Solar/Wind Harmer
0.121
316034AC1-036 C
Solar/Wind Harmer
0.005
962561AG1-105 GEN
Solar/Wind Harmer
3.364
964791AG1-342 GEN
Solar/Wind Harmer
1.25
3146843MT LREL
Solar/Wind Harmer
0.065
3146843MT LREL
Solar/Wind Harmer
0.065
3146376EDENTON
Solar/Wind Harmer
0.271
3146376EDENTON
Solar/Wind Harmer
0.271
958211AF2-115 GEN
Solar/Wind Harmer
0.676
963191AG1-168 GEN
Solar/Wind Harmer
0.225
3144356SAPONY
Solar/Wind Helper
0.949
3151391GASTONA
50/50
0.917
3151411GASTONB
50/50
0.917
3151261ROARAP2
50/50
0.304
3151591KERR 2
50/50
0.204
3144293JTRSVLE
50/50
0.19
316365GEN2_N
Solar/Wind Harmer
1.156
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
315816AE2-034 GEN
Solar/Wind Harmer
0.361
971443AH1-215 GEN
Solar/Wind Harmer
1.284
3144303KENBRDG
Solar/Wind Harmer
0.06
970683AG2-441 GEN
Solar/Wind Harmer
4.379
970681AG2-440 GEN
Solar/Wind Harmer
3.503
3130156CHOWAN
Solar/Wind Harmer
0.061
3130156CHOWAN
Solar/Wind Harmer
0.061
946301AF1-294 GEN
Solar/Wind Harmer
1.112
961791AG1-021 GEN
Solar/Wind Harmer
0.541
316315AB2-025 C
Solar/Wind Helper
0.806
3143316POE
Solar/Wind Helper
0.622
313506AB2-031 GEN
Solar/Wind Harmer
1.029
3145796HORNRTN
Solar/Wind Harmer
1.262
3145796HORNRTN
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.313
3147043LAWRENC
Solar/Wind Harmer
0.188
315724AD1-057 GEN
Solar/Wind Harmer
0.899
316210AC1-098 GEN
Solar/Wind Harmer
1.79
3146263WOODLND
Solar/Wind Harmer
0.189
316327AA2-057 GEN
Solar/Wind Harmer
0.283
3146233WITAKRS
Solar/Wind Harmer
0.904
3146233WITAKRS
Solar/Wind Harmer
0.122
3138543CONSLDL
Solar/Wind Harmer
0.118
961601AG1-000A GEN
Solar/Wind Harmer
12.598
316317KELFORD C
Solar/Wind Harmer
0.017
3145823KELFORD
Solar/Wind Harmer
0.176
971623AH1-311 GEN
Solar/Wind Harmer
0.347
3145543BTLEBRO
Solar/Wind Harmer
0.172
3145543BTLEBRO
Solar/Wind Harmer
0.172
316463AE2-346 GEN
Solar/Wind Harmer
0.142
316140AB2-099
Solar/Wind Harmer
0.059
962331AG1-082 GEN
Solar/Wind Harmer
1.758
3146173TUNIS
Solar/Wind Harmer
0.163
3146073TAR RVR
Solar/Wind Harmer
0.163
3146083TARBORO
Solar/Wind Harmer
0.163
957521AF2-046 GEN
Solar/Wind Harmer
11.941
961681AG1-008 GEN
Solar/Wind Harmer
11.941
3145893MURPHYS
Solar/Wind Harmer
0.267
3145893MURPHYS
Solar/Wind Harmer
0.159
3156021HOLLOMANSOL
Solar/Wind Harmer
0.695
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
3145746EVERETS
Solar/Wind Harmer
0.137
3145746EVERETS
Solar/Wind Harmer
0.137
3145933PARMELE
Solar/Wind Harmer
0.131
966801AG1-551 GEN
Solar/Wind Harmer
1.53
3146206CASHIE
Solar/Wind Harmer
0.125
3145963POPLR C
Solar/Wind Harmer
0.119
315737AD1-076 GEN
Solar/Wind Harmer
1.353
971157AH1-035 GEN
Solar/Wind Harmer
1.222
316131AB2-060 GEN
Solar/Wind Harmer
0.302
964241AG1-285 GEN
Solar/Wind Harmer
5.993
315614AA2-178 GEN
Solar/Wind Harmer
0.482
315785AD2-033 C
Solar/Wind Harmer
0.646
970257AG2-171 GEN
Solar/Wind Harmer
2.417
959311AF2-222 GEN
Solar/Wind Harmer
6.465
3146376EDENTON
Solar/Wind Harmer
0.061
963181AG1-167 GEN
Solar/Wind Harmer
0.225
315839AE2-212 C
Solar/Wind Helper
0.177
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.202
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.915
MECLTFEXP_MEC->PJM
CLTF
1.103
SIGELTFEXP_SIGE->PJM
CLTF
0.033
CPLELTFEXP_CPLE->PJM
CLTF
4.021
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.068
LAGNLTFEXP_LAGN->PJM
CLTF
2.305
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.741
TVALTFEXP_TVA->PJM
CLTF
1.146
NYPJM->LTFIMP_NY
CLTF
0.422
LGEELTFEXP_LGEE->PJM
CLTF
0.392
WECLTFEXP_WEC->PJM
CLTF
0.205

Details for 6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.75 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:1023.09
MW Contribution:1.29
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.616
3144293JTRSVLE
50/50
0.519
970535AG2-341 GEN
50/50
1.287
971489AH1-241 GEN
Solar/Wind Harmer
23.276
3146776BUCKING
Solar/Wind Harmer
1.51
3146776BUCKING
Solar/Wind Harmer
0.122
315821AE2-092 GEN
Solar/Wind Harmer
0.018
970301AG2-198 GEN
Solar/Wind Harmer
8.415
3147133PAMPLIN
Solar/Wind Harmer
0.197
3147133PAMPLIN
Solar/Wind Harmer
0.157
3151931BEARGRDN S1
50/50
5.89
3151911BEARGRDN G1
50/50
4.564
3144293JTRSVLE
50/50
0.616
3151601KERR 3
50/50
0.118
3151581KERR 1
50/50
0.042
3143336POWHATN
Solar/Wind Harmer
14.336
316336AC2-165 C
Solar/Wind Harmer
0.029
970937AG2-583 GEN
Solar/Wind Harmer
37.444
972003AH1-546 GEN
Solar/Wind Harmer
19.982
971377AH1-170 GEN
Solar/Wind Harmer
4.655
3147623JAMES R
Solar/Wind Harmer
1.011
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.151
3146926FARMVIL
Solar/Wind Harmer
0.171
963171AG1-166 GEN
Solar/Wind Harmer
0.973
971563AH1-280 GEN
Solar/Wind Harmer
1.945
970685AG2-442 GEN
Solar/Wind Harmer
12.058
316237AB2-079_GEN
Solar/Wind Harmer
0.001
962491AG1-098 GEN
Solar/Wind Harmer
4.857
315693AD1-088 GEN
Solar/Wind Harmer
3.792
970401AG2-262 GEN
Solar/Wind Harmer
0.393
962751AG1-124 GEN
Solar/Wind Harmer
2.954
3143226MDLTHAN
Solar/Wind Helper
0.215
3143526WINTERP
Solar/Wind Helper
0.91
972205AH1-687 GEN
50/50
22.262
3151611KERR 4
50/50
0.118
3151621KERR 5
50/50
0.118
3151631KERR 6
50/50
0.118
3151641KERR 7
50/50
0.118
971447AH1-217 GEN
Solar/Wind Harmer
12.398
971845AH1-439 GEN
Solar/Wind Harmer
16.766
970285AG2-188 GEN
Solar/Wind Harmer
28.069
270494AE1-108_GEN
Solar/Wind Harmer
4.133
315657AE1-056 GEN
Solar/Wind Harmer
6.793
946301AF1-294 GEN
Solar/Wind Harmer
3.599
961791AG1-021 GEN
Solar/Wind Harmer
1.751
970683AG2-441 GEN
Solar/Wind Harmer
10.766
970681AG2-440 GEN
Solar/Wind Harmer
8.613
3144303KENBRDG
Solar/Wind Harmer
0.111
971443AH1-215 GEN
Solar/Wind Harmer
2.308
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.151
316233AE1-074 FULL
Solar/Wind Helper
0.267
3151921BEARGRDN G2
50/50
4.564
3144293JTRSVLE
50/50
0.616
966251AG1-494 GEN
50/50
1.534
3151591KERR 2
50/50
0.118
316313AB2-026
Solar/Wind Harmer
0.508
316258AE1-075 C
Solar/Wind Harmer
0.609
316405AF2-144 C
Solar/Wind Harmer
0.006
3143336POWHATN
Solar/Wind Harmer
12.186
970221AG2-151 GEN
Solar/Wind Harmer
23.276
3146776BUCKING
Solar/Wind Harmer
0.136
3146926FARMVIL
Solar/Wind Harmer
0.171
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
2.104
3147133PAMPLIN
Solar/Wind Harmer
0.618
971193AH1-056 GEN
Solar/Wind Harmer
11.992
963181AG1-167 GEN
Solar/Wind Harmer
0.73
959311AF2-222 GEN
Solar/Wind Harmer
12.95
958131AF2-107 GEN
Solar/Wind Harmer
4.127
970257AG2-171 GEN
Solar/Wind Harmer
4.458
315785AD2-033 C
Solar/Wind Harmer
1.061
964241AG1-285 GEN
Solar/Wind Harmer
7.147
316131AB2-060 GEN
Solar/Wind Harmer
0.293
958211AF2-115 GEN
Solar/Wind Harmer
2.189
963191AG1-168 GEN
Solar/Wind Harmer
0.73
971741AH1-377 GEN
Solar/Wind Harmer
16.874
316034AC1-036 C
Solar/Wind Harmer
0.01
970323AG2-213 GEN
Solar/Wind Harmer
5.944
971775AH1-396 GEN
Solar/Wind Harmer
0.223
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.379
964791AG1-342 GEN
Solar/Wind Harmer
1.285
3146843MT LREL
Solar/Wind Harmer
0.067
3146843MT LREL
Solar/Wind Harmer
0.067
939181AE1-148 GEN
Solar/Wind Harmer
3.025
3143526WINTERP
Solar/Wind Helper
0.91
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.166
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.3
MECLTFEXP_MEC->PJM
CLTF
0.735
SIGELTFEXP_SIGE->PJM
CLTF
0.023
CPLELTFEXP_CPLE->PJM
CLTF
1.241
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.227
LAGNLTFEXP_LAGN->PJM
CLTF
1.269
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.039
TVALTFEXP_TVA->PJM
CLTF
0.652
NYPJM->LTFIMP_NY
CLTF
0.434
LGEELTFEXP_LGEE->PJM
CLTF
0.296
WECLTFEXP_WEC->PJM
CLTF
0.147

Details for 6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6POWHATN-6MDLTHAN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.17 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:1002.46
MW Contribution:1.34
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.501
3144293JTRSVLE
50/50
0.422
970535AG2-341 GEN
50/50
1.338
3152661PLYWOOD A
50/50
0.156
971489AH1-241 GEN
Solar/Wind Harmer
15.103
3146776BUCKING
Solar/Wind Harmer
1.047
3146776BUCKING
Solar/Wind Harmer
0.085
315821AE2-092 GEN
Solar/Wind Harmer
0.012
970301AG2-198 GEN
Solar/Wind Harmer
7.451
971741AH1-377 GEN
Solar/Wind Harmer
16.073
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.126
958211AF2-115 GEN
Solar/Wind Harmer
1.778
963191AG1-168 GEN
Solar/Wind Harmer
0.593
316034AC1-036 C
Solar/Wind Harmer
0.009
970323AG2-213 GEN
Solar/Wind Harmer
5.119
971775AH1-396 GEN
Solar/Wind Harmer
0.192
970099AG2-077 GEN
Solar/Wind Harmer
11.601
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.739
964791AG1-342 GEN
Solar/Wind Harmer
1.463
3146843MT LREL
Solar/Wind Harmer
0.076
3146843MT LREL
Solar/Wind Harmer
0.076
939181AE1-148 GEN
Solar/Wind Harmer
3.296
3143526WINTERP
Solar/Wind Helper
1.3
316240AF1-291 C
Solar/Wind Helper
0.164
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.158
316075AC2-137 C
Solar/Wind Helper
0.174
3151921BEARGRDN G2
50/50
2.961
3144293JTRSVLE
50/50
0.501
970413AG2-270 GEN
50/50
9.49
966251AG1-494 GEN
50/50
1.187
3151591KERR 2
50/50
0.134
316313AB2-026
Solar/Wind Harmer
0.448
316258AE1-075 C
Solar/Wind Harmer
0.537
316405AF2-144 C
Solar/Wind Harmer
0.005
3143336POWHATN
Solar/Wind Harmer
10.75
970221AG2-151 GEN
Solar/Wind Harmer
15.103
3146776BUCKING
Solar/Wind Harmer
0.094
3146926FARMVIL
Solar/Wind Harmer
0.129
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
1.863
3147133PAMPLIN
Solar/Wind Harmer
0.495
971193AH1-056 GEN
Solar/Wind Harmer
9.605
963181AG1-167 GEN
Solar/Wind Harmer
0.593
959311AF2-222 GEN
Solar/Wind Harmer
11.036
970257AG2-171 GEN
Solar/Wind Harmer
3.839
315785AD2-033 C
Solar/Wind Harmer
0.929
958131AF2-107 GEN
Solar/Wind Harmer
2.937
316478AD1-087 GEN
Solar/Wind Harmer
0.354
316486AD2-202 GEN
Solar/Wind Harmer
0.104
964241AG1-285 GEN
Solar/Wind Harmer
6.596
316131AB2-060 GEN
Solar/Wind Harmer
0.282
3148013FISHERV
Solar/Wind Harmer
0.07
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.906
971683AH1-343 GEN
Solar/Wind Harmer
2.326
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.716
315839AE2-212 C
Solar/Wind Helper
0.157
3151931BEARGRDN S1
50/50
3.821
3151911BEARGRDN G1
50/50
2.961
3144293JTRSVLE
50/50
0.501
3151531CLOVER1
50/50
2.175
3151601KERR 3
50/50
0.134
3151581KERR 1
50/50
0.048
3143336POWHATN
Solar/Wind Harmer
12.647
316336AC2-165 C
Solar/Wind Harmer
0.025
970937AG2-583 GEN
Solar/Wind Harmer
28.662
972003AH1-546 GEN
Solar/Wind Harmer
13.092
971377AH1-170 GEN
Solar/Wind Harmer
3.021
3147623JAMES R
Solar/Wind Harmer
0.656
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
963171AG1-166 GEN
Solar/Wind Harmer
0.79
971563AH1-280 GEN
Solar/Wind Harmer
1.581
970685AG2-442 GEN
Solar/Wind Harmer
10.044
962491AG1-098 GEN
Solar/Wind Harmer
6.995
315693AD1-088 GEN
Solar/Wind Harmer
5.748
957481AF2-042 GEN
Solar/Wind Harmer
29.002
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.003
970401AG2-262 GEN
Solar/Wind Harmer
0.447
316003AC1-222 GEN
Solar/Wind Harmer
0.002
3143226MDLTHAN
Solar/Wind Helper
0.301
3143526WINTERP
Solar/Wind Helper
1.3
3142543TWELFTH
Solar/Wind Helper
0.014
3142416OLDCHRC
Solar/Wind Helper
0.299
3142416OLDCHRC
Solar/Wind Helper
0.115
316458AB2-190 GEN2
Solar/Wind Helper
0.646
3142433PROV 92
Solar/Wind Helper
0.449
972205AH1-687 GEN
50/50
14.44
3151541CLOVER2
50/50
2.164
3151611KERR 4
50/50
0.134
3151621KERR 5
50/50
0.134
3151631KERR 6
50/50
0.134
3151641KERR 7
50/50
0.134
971447AH1-217 GEN
Solar/Wind Harmer
8.127
971845AH1-439 GEN
Solar/Wind Harmer
11.689
970285AG2-188 GEN
Solar/Wind Harmer
19.803
270494AE1-108_GEN
Solar/Wind Harmer
2.716
315657AE1-056 GEN
Solar/Wind Harmer
5.441
946301AF1-294 GEN
Solar/Wind Harmer
2.925
961791AG1-021 GEN
Solar/Wind Harmer
1.423
970683AG2-441 GEN
Solar/Wind Harmer
8.968
970681AG2-440 GEN
Solar/Wind Harmer
7.174
3144303KENBRDG
Solar/Wind Harmer
0.096
971443AH1-215 GEN
Solar/Wind Harmer
1.995
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.186
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.04
3147173SINAI
Solar/Wind Harmer
0.068
3147243WELCO
Solar/Wind Harmer
0.043
970865AG2-541 GEN
Solar/Wind Harmer
2.11
316233AE1-074 FULL
Solar/Wind Helper
0.382
316312AB1-027
Solar/Wind Helper
0.219
316132AB2-190 GEN1
Solar/Wind Helper
0.646
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.906
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.527
MECLTFEXP_MEC->PJM
CLTF
0.991
SIGELTFEXP_SIGE->PJM
CLTF
0.032
CPLELTFEXP_CPLE->PJM
CLTF
0.56
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.43
LAGNLTFEXP_LAGN->PJM
CLTF
1.312
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.9
TVALTFEXP_TVA->PJM
CLTF
0.684
NYPJM->LTFIMP_NY
CLTF
0.361
LGEELTFEXP_LGEE->PJM
CLTF
0.427
WECLTFEXP_WEC->PJM
CLTF
0.217

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:145.19 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:985.37
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.92
3151411GASTONB
50/50
0.92
3147043LAWRENC
50/50
3.139
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.269
3151581KERR 1
50/50
0.096
3144293JTRSVLE
50/50
0.304
3151531CLOVER1
50/50
1.555
316023GEN1_S
Solar/Wind Harmer
1.155
960081AF2-299 GEN
Solar/Wind Harmer
3.963
971795AH1-408 GEN
Solar/Wind Harmer
23.605
316011AB1-132 GEN
Solar/Wind Harmer
6.184
962571AG1-106 GEN
Solar/Wind Harmer
4.839
3145796HORNRTN
Solar/Wind Harmer
1.046
3145796HORNRTN
Solar/Wind Harmer
0.317
3145783HORNRTN
Solar/Wind Harmer
0.249
315722AD1-056 GEN
Solar/Wind Harmer
1.53
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
1.015
3146263WOODLND
Solar/Wind Harmer
0.191
3146233WITAKRS
Solar/Wind Harmer
0.73
3145823KELFORD
Solar/Wind Harmer
0.177
3151391GASTONA
50/50
0.92
3151411GASTONB
50/50
0.92
3151261ROARAP2
50/50
0.312
3151591KERR 2
50/50
0.269
3144293JTRSVLE
50/50
0.304
970413AG2-270 GEN
50/50
6.787
316365GEN2_N
Solar/Wind Harmer
1.155
313506AB2-031 GEN
Solar/Wind Harmer
1.048
3147043LAWRENC
Solar/Wind Harmer
0.196
3145796HORNRTN
Solar/Wind Harmer
1.267
3145796HORNRTN
Solar/Wind Harmer
0.317
3142666NORTHAMPTON
Solar/Wind Harmer
0.314
315724AD1-057 GEN
Solar/Wind Harmer
0.907
316210AC1-098 GEN
Solar/Wind Harmer
1.819
316327AA2-057 GEN
Solar/Wind Harmer
0.289
3146263WOODLND
Solar/Wind Harmer
0.191
3146233WITAKRS
Solar/Wind Harmer
0.92
3146233WITAKRS
Solar/Wind Harmer
0.125
3138543CONSLDL
Solar/Wind Harmer
0.12
961601AG1-000A GEN
Solar/Wind Harmer
12.794
316317KELFORD C
Solar/Wind Harmer
0.017
3145823KELFORD
Solar/Wind Harmer
0.177
971623AH1-311 GEN
Solar/Wind Harmer
0.353
3145543BTLEBRO
Solar/Wind Harmer
0.175
3145543BTLEBRO
Solar/Wind Harmer
0.175
316463AE2-346 GEN
Solar/Wind Harmer
0.142
316140AB2-099
Solar/Wind Harmer
0.059
962331AG1-082 GEN
Solar/Wind Harmer
1.759
3146073TAR RVR
Solar/Wind Harmer
0.164
3146083TARBORO
Solar/Wind Harmer
0.164
3151361ROSEMG1
50/50
1.142
3151371ROSEMS1
50/50
0.707
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.318
3144293JTRSVLE
50/50
0.304
3144293JTRSVLE
50/50
0.256
3152661PLYWOOD A
50/50
0.195
3144356SAPONY
Solar/Wind Harmer
7.116
316181AB2-040 GEN
Solar/Wind Harmer
0.492
3145796HORNRTN
Solar/Wind Harmer
0.951
3142666NORTHAMPTON
Solar/Wind Harmer
0.314
3142666NORTHAMPTON
Solar/Wind Harmer
0.314
3142666NORTHAMPTON
Solar/Wind Harmer
0.314
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3145593CAROLNA
Solar/Wind Harmer
0.256
3145593CAROLNA
Solar/Wind Harmer
0.256
966811AG1-552 GEN
Solar/Wind Harmer
2.783
3145593CAROLNA
Solar/Wind Harmer
0.319
3145783HORNRTN
Solar/Wind Harmer
4.426
3145783HORNRTN
Solar/Wind Harmer
3.54
3145783HORNRTN
Solar/Wind Harmer
1.106
3145783HORNRTN
Solar/Wind Harmer
0.443
316426AA2-053 GEN
Solar/Wind Harmer
0.812
316274AC1-208 GEN
Solar/Wind Harmer
1.08
961601AG1-000A GEN
Solar/Wind Harmer
3.199
316263AC1-034 GEN
Solar/Wind Harmer
6.701
3145493TOT1
Solar/Wind Harmer
0.381
3145453TOT5
Solar/Wind Harmer
0.229
3145603CNETO
Solar/Wind Harmer
0.153
3146173TUNIS
Solar/Wind Harmer
0.163
315779AE2-040
50/50
11.875
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.269
3151621KERR 5
50/50
0.269
3151631KERR 6
50/50
0.269
3151641KERR 7
50/50
0.269
3151151S HAMPT1
50/50
0.284
3151541CLOVER2
50/50
1.548
316315AB2-025 C
Solar/Wind Harmer
0.688
315814AE2-033 C
Solar/Wind Harmer
65.911
316087AB2-174 GEN
Solar/Wind Harmer
0.01
315652AC1-086 GEN
Solar/Wind Harmer
37.411
3145796HORNRTN
Solar/Wind Harmer
1.014
3145796HORNRTN
Solar/Wind Harmer
0.127
3137643SOCKMAN
Solar/Wind Harmer
1.175
315607AA1-063A GEN
Solar/Wind Harmer
0.444
3146043SEABORD
Solar/Wind Harmer
0.211
3146033SCOT NK
Solar/Wind Harmer
0.75
316319Z2-044 C
Solar/Wind Harmer
0
970831AG2-522 GEN
Solar/Wind Harmer
7.776
3145683EARLEYS
Solar/Wind Harmer
0.333
3145683EARLEYS
Solar/Wind Harmer
0.166
3145683EARLEYS
Solar/Wind Harmer
0.166
3145513AHOSKIE
Solar/Wind Harmer
0.345
3145513AHOSKIE
Solar/Wind Harmer
0.165
3145573BETHELC
Solar/Wind Harmer
0.164
3145573BETHELC
Solar/Wind Harmer
0.164
3145893MURPHYS
Solar/Wind Harmer
0.432
3145893MURPHYS
Solar/Wind Harmer
0.16
316420AA1-050 GEN
Solar/Wind Harmer
0.005
965291AG1-394 GEN
Solar/Wind Harmer
0.697
957861AF2-080 GEN
Solar/Wind Harmer
6.557
316005AA1-067
Solar/Wind Harmer
0.148
3145746EVERETS
Solar/Wind Harmer
0.547
3145746EVERETS
Solar/Wind Harmer
0.137
3145746EVERETS
Solar/Wind Harmer
0.137
3145746EVERETS
Solar/Wind Harmer
0.137
970181AG2-120 GEN
Solar/Wind Harmer
1.711
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.122
970601AG2-382 GEN
Solar/Wind Harmer
4.57
971443AH1-215 GEN
Solar/Wind Harmer
1.845
3144303KENBRDG
Solar/Wind Harmer
0.087
315732AD1-074 GEN1
Solar/Wind Harmer
0.586
315733AD1-074 GEN2
Solar/Wind Harmer
0.586
315735AD1-075 GEN1
Solar/Wind Harmer
0.293
970683AG2-441 GEN
Solar/Wind Harmer
6.62
970681AG2-440 GEN
Solar/Wind Harmer
5.296
3130546PLYMOUTH
Solar/Wind Harmer
0.098
946301AF1-294 GEN
Solar/Wind Harmer
1.779
961791AG1-021 GEN
Solar/Wind Harmer
0.865
316118AC1-105 GEN
Solar/Wind Harmer
0.226
315657AE1-056 GEN
Solar/Wind Harmer
2.89
315816AE2-034 GEN
Solar/Wind Harmer
0.343
3147173SINAI
Solar/Wind Harmer
0.076
3147243WELCO
Solar/Wind Harmer
0.048
970865AG2-541 GEN
Solar/Wind Harmer
2.221
3143316POE
Solar/Wind Helper
0.689
3146173TUNIS
Solar/Wind Harmer
0.163
957521AF2-046 GEN
Solar/Wind Harmer
11.971
961681AG1-008 GEN
Solar/Wind Harmer
11.971
3145893MURPHYS
Solar/Wind Harmer
0.268
3145893MURPHYS
Solar/Wind Harmer
0.16
3156021HOLLOMANSOL
Solar/Wind Harmer
0.688
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
3145746EVERETS
Solar/Wind Harmer
0.137
3145746EVERETS
Solar/Wind Harmer
0.137
3145933PARMELE
Solar/Wind Harmer
0.131
966801AG1-551 GEN
Solar/Wind Harmer
1.527
316131AB2-060 GEN
Solar/Wind Harmer
0.406
964241AG1-285 GEN
Solar/Wind Harmer
8.201
3146206CASHIE
Solar/Wind Harmer
0.122
3145963POPLR C
Solar/Wind Harmer
0.117
315785AD2-033 C
Solar/Wind Harmer
0.917
970257AG2-171 GEN
Solar/Wind Harmer
3.486
959311AF2-222 GEN
Solar/Wind Harmer
9.44
315737AD1-076 GEN
Solar/Wind Harmer
1.312
971157AH1-035 GEN
Solar/Wind Harmer
1.181
963181AG1-167 GEN
Solar/Wind Harmer
0.361
3147133PAMPLIN
Solar/Wind Harmer
0.263
971193AH1-056 GEN
Solar/Wind Harmer
5.102
315614AA2-178 GEN
Solar/Wind Harmer
0.457
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.266
316478AD1-087 GEN
Solar/Wind Harmer
0.254
316486AD2-202 GEN
Solar/Wind Harmer
0.074
971683AH1-343 GEN
Solar/Wind Harmer
2.507
942461AE2-259 GEN
Solar/Wind Harmer
0
316283AC2-100 C
Solar/Wind Harmer
0.113
970909AG2-566 GEN
Solar/Wind Harmer
0.604
315839AE2-212 C
Solar/Wind Helper
0.198
316359AB2-059 GEN
Solar/Wind Harmer
0.633
316049AB1-081 GEN
Solar/Wind Harmer
1.009
3142053HEARTS
Solar/Wind Harmer
0.311
3145543BTLEBRO
Solar/Wind Harmer
0.175
3145543BTLEBRO
Solar/Wind Harmer
0.14
316129AC1-054 GEN
Solar/Wind Harmer
0.656
971065AG2-659 GEN
Solar/Wind Harmer
7.123
3145683EARLEYS
Solar/Wind Harmer
0.166
961671AG1-007 GEN
Solar/Wind Harmer
0.025
3146083TARBORO
Solar/Wind Harmer
0.164
3145493TOT1
Solar/Wind Harmer
0.732
3146173TUNIS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
0.639
3145893MURPHYS
Solar/Wind Harmer
0.711
316494AC1-189 GEN
Solar/Wind Harmer
0.514
3145746EVERETS
Solar/Wind Harmer
0.137
3145746EVERETS
Solar/Wind Harmer
0.137
3146293MARTNCO
Solar/Wind Harmer
0.122
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.122
971547AH1-271 GEN
Solar/Wind Harmer
2.611
316174AB2-169 GEN
Solar/Wind Harmer
0.003
3145963POPLR C
Solar/Wind Harmer
0.117
970685AG2-442 GEN
Solar/Wind Harmer
7.414
970401AG2-262 GEN
Solar/Wind Harmer
0.582
963171AG1-166 GEN
Solar/Wind Harmer
0.481
971563AH1-280 GEN
Solar/Wind Harmer
0.961
3145663CRESWEL
Solar/Wind Harmer
0.224
971163AH1-040 GEN
Solar/Wind Harmer
6.395
957481AF2-042 GEN
Solar/Wind Harmer
19.267
316003AC1-222 GEN
Solar/Wind Harmer
0.002
315693AD1-088 GEN
Solar/Wind Harmer
3.435
315687AD1-152 GEN
Solar/Wind Harmer
0.002
962491AG1-098 GEN
Solar/Wind Harmer
4.04
3146173TUNIS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
1.07
3145893MURPHYS
Solar/Wind Harmer
0.288
3145933PARMELE
Solar/Wind Harmer
0.262
3145933PARMELE
Solar/Wind Harmer
0.131
313527AB2-043 GEN
Solar/Wind Harmer
0.002
939181AE1-148 GEN
Solar/Wind Harmer
6.253
316065AD1-022 GEN
Solar/Wind Harmer
5.291
970323AG2-213 GEN
Solar/Wind Harmer
4.648
971775AH1-396 GEN
Solar/Wind Harmer
0.174
316034AC1-036 C
Solar/Wind Harmer
0.008
962561AG1-105 GEN
Solar/Wind Harmer
4.993
964791AG1-342 GEN
Solar/Wind Harmer
1.905
3146843MT LREL
Solar/Wind Harmer
0.099
3146843MT LREL
Solar/Wind Harmer
0.099
958211AF2-115 GEN
Solar/Wind Harmer
1.082
963191AG1-168 GEN
Solar/Wind Harmer
0.361
3147133PAMPLIN
Solar/Wind Harmer
0.084
3147133PAMPLIN
Solar/Wind Harmer
0.067
970099AG2-077 GEN
Solar/Wind Harmer
7.707
315742AE1-103 GEN
Solar/Wind Harmer
0.001
971741AH1-377 GEN
Solar/Wind Harmer
5.954
316222AC1-221 GEN
Solar/Wind Harmer
0.241
970301AG2-198 GEN
Solar/Wind Harmer
2.414
316240AF1-291 C
Solar/Wind Helper
0.169
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.679
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.543
MECLTFEXP_MEC->PJM
CLTF
1.307
SIGELTFEXP_SIGE->PJM
CLTF
0.039
CPLELTFEXP_CPLE->PJM
CLTF
4.437
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.06
LAGNLTFEXP_LAGN->PJM
CLTF
2.654
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.672
TVALTFEXP_TVA->PJM
CLTF
1.324
NYPJM->LTFIMP_NY
CLTF
0.497
LGEELTFEXP_LGEE->PJM
CLTF
0.473
WECLTFEXP_WEC->PJM
CLTF
0.246

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:144.54 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:980.94
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.92
3151411GASTONB
50/50
0.92
3147043LAWRENC
50/50
3.139
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.269
3151581KERR 1
50/50
0.096
3144293JTRSVLE
50/50
0.304
3151531CLOVER1
50/50
1.555
316023GEN1_S
Solar/Wind Harmer
1.155
960081AF2-299 GEN
Solar/Wind Harmer
3.963
971795AH1-408 GEN
Solar/Wind Harmer
23.605
316011AB1-132 GEN
Solar/Wind Harmer
6.184
962571AG1-106 GEN
Solar/Wind Harmer
4.839
3145796HORNRTN
Solar/Wind Harmer
1.046
3145796HORNRTN
Solar/Wind Harmer
0.317
3145783HORNRTN
Solar/Wind Harmer
0.249
315722AD1-056 GEN
Solar/Wind Harmer
1.53
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
1.015
3146263WOODLND
Solar/Wind Harmer
0.191
3146233WITAKRS
Solar/Wind Harmer
0.73
3145823KELFORD
Solar/Wind Harmer
0.177
316359AB2-059 GEN
Solar/Wind Harmer
0.633
316049AB1-081 GEN
Solar/Wind Harmer
1.009
3142053HEARTS
Solar/Wind Harmer
0.311
3151361ROSEMG1
50/50
1.142
3151371ROSEMS1
50/50
0.707
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.318
3144293JTRSVLE
50/50
0.304
3144293JTRSVLE
50/50
0.256
3152661PLYWOOD A
50/50
0.195
3144356SAPONY
Solar/Wind Harmer
7.116
316181AB2-040 GEN
Solar/Wind Harmer
0.492
3145796HORNRTN
Solar/Wind Harmer
0.951
3142666NORTHAMPTON
Solar/Wind Harmer
0.314
3142666NORTHAMPTON
Solar/Wind Harmer
0.314
3142666NORTHAMPTON
Solar/Wind Harmer
0.314
3142666NORTHAMPTON
Solar/Wind Harmer
0.189
3145593CAROLNA
Solar/Wind Harmer
0.256
3145593CAROLNA
Solar/Wind Harmer
0.256
966811AG1-552 GEN
Solar/Wind Harmer
2.783
3145593CAROLNA
Solar/Wind Harmer
0.319
3145783HORNRTN
Solar/Wind Harmer
4.426
3145783HORNRTN
Solar/Wind Harmer
3.54
3151391GASTONA
50/50
0.92
3151411GASTONB
50/50
0.92
3145543BTLEBRO
Solar/Wind Harmer
0.175
3145543BTLEBRO
Solar/Wind Harmer
0.14
316129AC1-054 GEN
Solar/Wind Harmer
0.656
971065AG2-659 GEN
Solar/Wind Harmer
7.123
3145683EARLEYS
Solar/Wind Harmer
0.166
961671AG1-007 GEN
Solar/Wind Harmer
0.025
3146083TARBORO
Solar/Wind Harmer
0.164
3145493TOT1
Solar/Wind Harmer
0.732
3146173TUNIS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
0.639
3145893MURPHYS
Solar/Wind Harmer
0.711
316494AC1-189 GEN
Solar/Wind Harmer
0.514
3145746EVERETS
Solar/Wind Harmer
0.137
3145746EVERETS
Solar/Wind Harmer
0.137
3146293MARTNCO
Solar/Wind Harmer
0.122
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.122
971547AH1-271 GEN
Solar/Wind Harmer
2.611
316174AB2-169 GEN
Solar/Wind Harmer
0.003
3145963POPLR C
Solar/Wind Harmer
0.117
970685AG2-442 GEN
Solar/Wind Harmer
7.414
970401AG2-262 GEN
Solar/Wind Harmer
0.582
963171AG1-166 GEN
Solar/Wind Harmer
0.481
971563AH1-280 GEN
Solar/Wind Harmer
0.961
3145663CRESWEL
Solar/Wind Harmer
0.224
971163AH1-040 GEN
Solar/Wind Harmer
6.395
957481AF2-042 GEN
Solar/Wind Harmer
19.267
316003AC1-222 GEN
Solar/Wind Harmer
0.002
315693AD1-088 GEN
Solar/Wind Harmer
3.435
315687AD1-152 GEN
Solar/Wind Harmer
0.002
962491AG1-098 GEN
Solar/Wind Harmer
4.04
315779AE2-040
50/50
11.875
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.269
3151621KERR 5
50/50
0.269
3151631KERR 6
50/50
0.269
3151641KERR 7
50/50
0.269
3151151S HAMPT1
50/50
0.284
3151541CLOVER2
50/50
1.548
316315AB2-025 C
Solar/Wind Harmer
0.688
315814AE2-033 C
Solar/Wind Harmer
65.911
316087AB2-174 GEN
Solar/Wind Harmer
0.01
315652AC1-086 GEN
Solar/Wind Harmer
37.411
3145796HORNRTN
Solar/Wind Harmer
1.014
3145796HORNRTN
Solar/Wind Harmer
0.127
3137643SOCKMAN
Solar/Wind Harmer
1.175
315607AA1-063A GEN
Solar/Wind Harmer
0.444
3146043SEABORD
Solar/Wind Harmer
0.211
3146033SCOT NK
Solar/Wind Harmer
0.75
316319Z2-044 C
Solar/Wind Harmer
0
970831AG2-522 GEN
Solar/Wind Harmer
7.776
3145683EARLEYS
Solar/Wind Harmer
0.333
3145683EARLEYS
Solar/Wind Harmer
0.166
3145683EARLEYS
Solar/Wind Harmer
0.166
3145513AHOSKIE
Solar/Wind Harmer
0.345
3145513AHOSKIE
Solar/Wind Harmer
0.165
3145573BETHELC
Solar/Wind Harmer
0.164
3145573BETHELC
Solar/Wind Harmer
0.164
3145893MURPHYS
Solar/Wind Harmer
0.432
3145893MURPHYS
Solar/Wind Harmer
0.16
316420AA1-050 GEN
Solar/Wind Harmer
0.005
965291AG1-394 GEN
Solar/Wind Harmer
0.697
957861AF2-080 GEN
Solar/Wind Harmer
6.557
316005AA1-067
Solar/Wind Harmer
0.148
3145746EVERETS
Solar/Wind Harmer
0.547
3145746EVERETS
Solar/Wind Harmer
0.137
3145746EVERETS
Solar/Wind Harmer
0.137
3145746EVERETS
Solar/Wind Harmer
0.137
970181AG2-120 GEN
Solar/Wind Harmer
1.711
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.122
970601AG2-382 GEN
Solar/Wind Harmer
4.57
971443AH1-215 GEN
Solar/Wind Harmer
1.845
3144303KENBRDG
Solar/Wind Harmer
0.087
315732AD1-074 GEN1
Solar/Wind Harmer
0.586
315733AD1-074 GEN2
Solar/Wind Harmer
0.586
315735AD1-075 GEN1
Solar/Wind Harmer
0.293
970683AG2-441 GEN
Solar/Wind Harmer
6.62
970681AG2-440 GEN
Solar/Wind Harmer
5.296
3130546PLYMOUTH
Solar/Wind Harmer
0.098
946301AF1-294 GEN
Solar/Wind Harmer
1.779
961791AG1-021 GEN
Solar/Wind Harmer
0.865
316118AC1-105 GEN
Solar/Wind Harmer
0.226
315657AE1-056 GEN
Solar/Wind Harmer
2.89
315816AE2-034 GEN
Solar/Wind Harmer
0.343
3147173SINAI
Solar/Wind Harmer
0.076
3147243WELCO
Solar/Wind Harmer
0.048
971967AH1-528 GEN
Solar/Wind Harmer
11.533
970865AG2-541 GEN
Solar/Wind Harmer
2.221
3143316POE
Solar/Wind Helper
0.689
3151261ROARAP2
50/50
0.312
3151591KERR 2
50/50
0.269
3144293JTRSVLE
50/50
0.304
970413AG2-270 GEN
50/50
6.787
316365GEN2_N
Solar/Wind Harmer
1.155
313506AB2-031 GEN
Solar/Wind Harmer
1.048
3147043LAWRENC
Solar/Wind Harmer
0.196
3145796HORNRTN
Solar/Wind Harmer
1.267
3145796HORNRTN
Solar/Wind Harmer
0.317
3142666NORTHAMPTON
Solar/Wind Harmer
0.314
315724AD1-057 GEN
Solar/Wind Harmer
0.907
316210AC1-098 GEN
Solar/Wind Harmer
1.819
316327AA2-057 GEN
Solar/Wind Harmer
0.289
3146263WOODLND
Solar/Wind Harmer
0.191
3146233WITAKRS
Solar/Wind Harmer
0.92
3146233WITAKRS
Solar/Wind Harmer
0.125
3138543CONSLDL
Solar/Wind Harmer
0.12
961601AG1-000A GEN
Solar/Wind Harmer
12.794
316317KELFORD C
Solar/Wind Harmer
0.017
3145823KELFORD
Solar/Wind Harmer
0.177
971623AH1-311 GEN
Solar/Wind Harmer
0.353
3145543BTLEBRO
Solar/Wind Harmer
0.175
3145543BTLEBRO
Solar/Wind Harmer
0.175
316463AE2-346 GEN
Solar/Wind Harmer
0.142
316140AB2-099
Solar/Wind Harmer
0.059
962331AG1-082 GEN
Solar/Wind Harmer
1.759
3146073TAR RVR
Solar/Wind Harmer
0.164
3146083TARBORO
Solar/Wind Harmer
0.164
3146173TUNIS
Solar/Wind Harmer
0.163
957521AF2-046 GEN
Solar/Wind Harmer
11.971
961681AG1-008 GEN
Solar/Wind Harmer
11.971
3145893MURPHYS
Solar/Wind Harmer
0.268
3145893MURPHYS
Solar/Wind Harmer
0.16
3156021HOLLOMANSOL
Solar/Wind Harmer
0.688
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
3145746EVERETS
Solar/Wind Harmer
0.137
3145746EVERETS
Solar/Wind Harmer
0.137
3145933PARMELE
Solar/Wind Harmer
0.131
966801AG1-551 GEN
Solar/Wind Harmer
1.527
316131AB2-060 GEN
Solar/Wind Harmer
0.406
964241AG1-285 GEN
Solar/Wind Harmer
8.201
3146206CASHIE
Solar/Wind Harmer
0.122
3145963POPLR C
Solar/Wind Harmer
0.117
315785AD2-033 C
Solar/Wind Harmer
0.917
970257AG2-171 GEN
Solar/Wind Harmer
3.486
959311AF2-222 GEN
Solar/Wind Harmer
9.44
315737AD1-076 GEN
Solar/Wind Harmer
1.312
971157AH1-035 GEN
Solar/Wind Harmer
1.181
963181AG1-167 GEN
Solar/Wind Harmer
0.361
3147133PAMPLIN
Solar/Wind Harmer
0.263
971193AH1-056 GEN
Solar/Wind Harmer
5.102
315614AA2-178 GEN
Solar/Wind Harmer
0.457
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.266
316478AD1-087 GEN
Solar/Wind Harmer
0.254
316486AD2-202 GEN
Solar/Wind Harmer
0.074
971683AH1-343 GEN
Solar/Wind Harmer
2.507
942461AE2-259 GEN
Solar/Wind Harmer
0
316283AC2-100 C
Solar/Wind Harmer
0.113
970909AG2-566 GEN
Solar/Wind Harmer
0.604
315839AE2-212 C
Solar/Wind Helper
0.198
3145783HORNRTN
Solar/Wind Harmer
1.106
3145783HORNRTN
Solar/Wind Harmer
0.443
316426AA2-053 GEN
Solar/Wind Harmer
0.812
316274AC1-208 GEN
Solar/Wind Harmer
1.08
961601AG1-000A GEN
Solar/Wind Harmer
3.199
316263AC1-034 GEN
Solar/Wind Harmer
6.701
3145493TOT1
Solar/Wind Harmer
0.381
3145453TOT5
Solar/Wind Harmer
0.229
3145603CNETO
Solar/Wind Harmer
0.153
3146173TUNIS
Solar/Wind Harmer
0.163
3146173TUNIS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
1.07
3145893MURPHYS
Solar/Wind Harmer
0.288
3145933PARMELE
Solar/Wind Harmer
0.262
3145933PARMELE
Solar/Wind Harmer
0.131
313527AB2-043 GEN
Solar/Wind Harmer
0.002
939181AE1-148 GEN
Solar/Wind Harmer
6.253
316065AD1-022 GEN
Solar/Wind Harmer
5.291
970323AG2-213 GEN
Solar/Wind Harmer
4.648
971775AH1-396 GEN
Solar/Wind Harmer
0.174
316034AC1-036 C
Solar/Wind Harmer
0.008
962561AG1-105 GEN
Solar/Wind Harmer
4.993
964791AG1-342 GEN
Solar/Wind Harmer
1.905
3146843MT LREL
Solar/Wind Harmer
0.099
3146843MT LREL
Solar/Wind Harmer
0.099
958211AF2-115 GEN
Solar/Wind Harmer
1.082
963191AG1-168 GEN
Solar/Wind Harmer
0.361
3147133PAMPLIN
Solar/Wind Harmer
0.084
3147133PAMPLIN
Solar/Wind Harmer
0.067
970099AG2-077 GEN
Solar/Wind Harmer
7.707
970933AG2-581 GEN
Solar/Wind Harmer
5.767
315742AE1-103 GEN
Solar/Wind Harmer
0.001
971741AH1-377 GEN
Solar/Wind Harmer
5.954
316222AC1-221 GEN
Solar/Wind Harmer
0.241
970301AG2-198 GEN
Solar/Wind Harmer
2.414
316240AF1-291 C
Solar/Wind Helper
0.169
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.679
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.543
MECLTFEXP_MEC->PJM
CLTF
1.307
SIGELTFEXP_SIGE->PJM
CLTF
0.039
CPLELTFEXP_CPLE->PJM
CLTF
4.437
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.06
LAGNLTFEXP_LAGN->PJM
CLTF
2.654
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.672
TVALTFEXP_TVA->PJM
CLTF
1.324
NYPJM->LTFIMP_NY
CLTF
0.497
LGEELTFEXP_LGEE->PJM
CLTF
0.473
WECLTFEXP_WEC->PJM
CLTF
0.246

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.4 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1156.99
MW Contribution:2.33
Bus #Bus NameTypeMW Contribution
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
3151391GASTONA
50/50
0.92
3151411GASTONB
50/50
0.92
3151261ROARAP2
50/50
0.312
3151591KERR 2
50/50
0.271
316365GEN2_N
Solar/Wind Harmer
3.897
966621AG1-532 GEN
Solar/Wind Harmer
0.941
313506AB2-031 GEN
Solar/Wind Harmer
3.063
3147043LAWRENC
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.142
3145796HORNRTN
Solar/Wind Harmer
-0.036
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
315724AD1-057 GEN
Solar/Wind Harmer
1.566
316210AC1-098 GEN
Solar/Wind Harmer
3.466
316327AA2-057 GEN
Solar/Wind Harmer
2.179
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
0.434
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.014
970535AG2-341 GEN
50/50
2.334
3144356SAPONY
Solar/Wind Harmer
3.329
316181AB2-040 GEN
Solar/Wind Harmer
5.316
3145796HORNRTN
Solar/Wind Harmer
-0.106
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3145593CAROLNA
Solar/Wind Harmer
-0.029
3145593CAROLNA
Solar/Wind Harmer
-0.029
966811AG1-552 GEN
Solar/Wind Harmer
3.246
3145593CAROLNA
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
3.322
3145783HORNRTN
Solar/Wind Harmer
2.657
3145783HORNRTN
Solar/Wind Harmer
0.83
3145783HORNRTN
Solar/Wind Harmer
0.332
316426AA2-053 GEN
Solar/Wind Harmer
2.731
316274AC1-208 GEN
Solar/Wind Harmer
2.529
961601AG1-000A GEN
Solar/Wind Harmer
7.998
316263AC1-034 GEN
Solar/Wind Harmer
9.349
3145493TOT1
Solar/Wind Harmer
0.288
3145453TOT5
Solar/Wind Harmer
0.173
3145603CNETO
Solar/Wind Harmer
0.115
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.5
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.029
3145933PARMELE
Solar/Wind Harmer
-0.015
313527AB2-043 GEN
Solar/Wind Harmer
2.401
939181AE1-148 GEN
Solar/Wind Harmer
8.293
316065AD1-022 GEN
Solar/Wind Harmer
6.431
970323AG2-213 GEN
Solar/Wind Harmer
6.159
971775AH1-396 GEN
Solar/Wind Harmer
0.877
316034AC1-036 C
Solar/Wind Harmer
0.228
962561AG1-105 GEN
Solar/Wind Harmer
6.642
964791AG1-342 GEN
Solar/Wind Harmer
2.408
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
958211AF2-115 GEN
Solar/Wind Harmer
1.593
963191AG1-168 GEN
Solar/Wind Harmer
0.956
3144293JTRSVLE
Adder
0.289
3144293JTRSVLE
Adder
0.243
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.303
970933AG2-581 GEN
Solar/Wind Harmer
7.708
315742AE1-103 GEN
Solar/Wind Harmer
0.833
971741AH1-377 GEN
Solar/Wind Harmer
7.93
316222AC1-221 GEN
Solar/Wind Harmer
0.684
970301AG2-198 GEN
Solar/Wind Harmer
3.213
316240AF1-291 C
Solar/Wind Helper
0.173
315779AE2-040
50/50
11.856
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.271
3151621KERR 5
50/50
0.271
3151631KERR 6
50/50
0.271
3151641KERR 7
50/50
0.271
316315AB2-025 C
Solar/Wind Harmer
2.574
315814AE2-033 C
Solar/Wind Harmer
87.029
946281AF1-292 GEN
Solar/Wind Harmer
1.038
316087AB2-174 GEN
Solar/Wind Harmer
5.792
315652AC1-086 GEN
Solar/Wind Harmer
43.007
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.014
3137643SOCKMAN
Solar/Wind Harmer
-0.131
315607AA1-063A GEN
Solar/Wind Harmer
2.465
3146043SEABORD
Solar/Wind Harmer
-0.024
3146033SCOT NK
Solar/Wind Harmer
-0.084
316319Z2-044 C
Solar/Wind Harmer
1.145
970831AG2-522 GEN
Solar/Wind Harmer
10.274
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.161
961941AG1-037 GEN
Solar/Wind Harmer
0.139
3145513AHOSKIE
Solar/Wind Harmer
-0.018
316420AA1-050 GEN
Solar/Wind Harmer
2.054
316318V4-068
Solar/Wind Harmer
0.447
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
965291AG1-394 GEN
Solar/Wind Harmer
1.56
957861AF2-080 GEN
Solar/Wind Harmer
7.517
316005AA1-067
Solar/Wind Harmer
0.314
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
2.038
316239AB2-077_GEN
Solar/Wind Harmer
0.44
316238AB2-078_GEN
Solar/Wind Harmer
0.44
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
5.997
971443AH1-215 GEN
Solar/Wind Harmer
2.445
3144303KENBRDG
Solar/Wind Harmer
-0.01
315732AD1-074 GEN1
Solar/Wind Harmer
2.305
315733AD1-074 GEN2
Solar/Wind Harmer
2.305
315735AD1-075 GEN1
Solar/Wind Harmer
1.153
970683AG2-441 GEN
Solar/Wind Harmer
8.771
970681AG2-440 GEN
Solar/Wind Harmer
7.017
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
946301AF1-294 GEN
Solar/Wind Harmer
2.612
961791AG1-021 GEN
Solar/Wind Harmer
1.274
316118AC1-105 GEN
Solar/Wind Harmer
0.687
315657AE1-056 GEN
Solar/Wind Harmer
3.553
315816AE2-034 GEN
Solar/Wind Harmer
0.72
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
971967AH1-528 GEN
Solar/Wind Harmer
15.454
970865AG2-541 GEN
Solar/Wind Harmer
2.98
3151391GASTONA
50/50
0.92
3151411GASTONB
50/50
0.92
3147043LAWRENC
50/50
3.14
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.271
3151581KERR 1
50/50
0.097
316023GEN1_S
Solar/Wind Harmer
3.897
960081AF2-299 GEN
Solar/Wind Harmer
5.216
971795AH1-408 GEN
Solar/Wind Harmer
29.838
316011AB1-132 GEN
Solar/Wind Harmer
7.998
962571AG1-106 GEN
Solar/Wind Harmer
5.495
3145796HORNRTN
Solar/Wind Harmer
-0.117
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145783HORNRTN
Solar/Wind Harmer
-0.028
315722AD1-056 GEN
Solar/Wind Harmer
2.848
316190AA2-174 GEN
Solar/Wind Harmer
0.332
316212AC1-099_GEN
Solar/Wind Harmer
1.925
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
-0.082
316359AB2-059 GEN
Solar/Wind Harmer
2.689
316049AB1-081 GEN
Solar/Wind Harmer
2.152
3142053HEARTS
Solar/Wind Harmer
0.234
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316129AC1-054 GEN
Solar/Wind Harmer
1.724
971065AG2-659 GEN
Solar/Wind Harmer
9.42
3145683EARLEYS
Solar/Wind Harmer
-0.019
961671AG1-007 GEN
Solar/Wind Harmer
0.235
3146083TARBORO
Solar/Wind Harmer
-0.019
3145493TOT1
Solar/Wind Harmer
0.552
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.071
3145893MURPHYS
Solar/Wind Harmer
0.532
316494AC1-189 GEN
Solar/Wind Harmer
1.849
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146293MARTNCO
Solar/Wind Harmer
0.092
316237AB2-079_GEN
Solar/Wind Harmer
0.44
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.427
316174AB2-169 GEN
Solar/Wind Harmer
2.087
3145963POPLR C
Solar/Wind Harmer
-0.013
970401AG2-262 GEN
Solar/Wind Harmer
0.736
970685AG2-442 GEN
Solar/Wind Harmer
9.824
963171AG1-166 GEN
Solar/Wind Harmer
1.274
971563AH1-280 GEN
Solar/Wind Harmer
1.274
3144293JTRSVLE
Adder
0.289
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.342
957481AF2-042 GEN
Solar/Wind Harmer
25.757
316003AC1-222 GEN
Solar/Wind Harmer
0.805
315693AD1-088 GEN
Solar/Wind Harmer
4.077
315687AD1-152 GEN
Solar/Wind Harmer
0.978
962491AG1-098 GEN
Solar/Wind Harmer
5.393
961601AG1-000A GEN
Solar/Wind Harmer
8.099
316317KELFORD C
Solar/Wind Harmer
0.938
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3146073TAR RVR
Solar/Wind Harmer
-0.019
3146083TARBORO
Solar/Wind Harmer
-0.019
316463AE2-346 GEN
Solar/Wind Harmer
0.3
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.313
3146173TUNIS
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.207
961681AG1-008 GEN
Solar/Wind Harmer
14.207
3145893MURPHYS
Solar/Wind Harmer
0.125
3145893MURPHYS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.291
3156081AA2-088 GEN
Solar/Wind Harmer
5.448
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.847
316131AB2-060 GEN
Solar/Wind Harmer
1.576
964241AG1-285 GEN
Solar/Wind Harmer
10.867
3146206CASHIE
Solar/Wind Harmer
-0.014
3145963POPLR C
Solar/Wind Harmer
-0.013
315785AD2-033 C
Solar/Wind Harmer
2.89
970257AG2-171 GEN
Solar/Wind Harmer
4.619
959311AF2-222 GEN
Solar/Wind Harmer
12.534
315737AD1-076 GEN
Solar/Wind Harmer
2.166
971157AH1-035 GEN
Solar/Wind Harmer
1.375
963181AG1-167 GEN
Solar/Wind Harmer
0.956
3144293JTRSVLE
Adder
0.289
3147133PAMPLIN
Solar/Wind Harmer
-0.03
971193AH1-056 GEN
Solar/Wind Harmer
5.922
315614AA2-178 GEN
Solar/Wind Harmer
0.96
316248AF1-058 C
Solar/Wind Harmer
0.264
960061AF2-297 GEN
Solar/Wind Harmer
4.376
316478AD1-087 GEN
Solar/Wind Harmer
0.718
316486AD2-202 GEN
Solar/Wind Harmer
0.21
971683AH1-343 GEN
Solar/Wind Harmer
3.362
942461AE2-259 GEN
Solar/Wind Harmer
1.117
316283AC2-100 C
Solar/Wind Harmer
0.633
970909AG2-566 GEN
Solar/Wind Harmer
0.61
315839AE2-212 C
Solar/Wind Helper
0.202
316123AC1-075 GEN
Solar/Wind Harmer
0.69
970165AG2-112 GEN
Solar/Wind Harmer
0.608
970163AG2-111 GEN
Solar/Wind Harmer
0.58
3143316POE
Solar/Wind Helper
0.702
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.173
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.798
MECLTFEXP_MEC->PJM
CLTF
1.381
SIGELTFEXP_SIGE->PJM
CLTF
0.041
CPLELTFEXP_CPLE->PJM
CLTF
4.641
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.852
LAGNLTFEXP_LAGN->PJM
CLTF
2.804
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.13
TVALTFEXP_TVA->PJM
CLTF
1.399
NYPJM->LTFIMP_NY
CLTF
0.52
LGEELTFEXP_LGEE->PJM
CLTF
0.5
WECLTFEXP_WEC->PJM
CLTF
0.26

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.34 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1156.56
MW Contribution:2.33
Bus #Bus NameTypeMW Contribution
3151361ROSEMG1
50/50
1.143
3151371ROSEMS1
50/50
0.708
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.334
3144356SAPONY
Solar/Wind Harmer
3.329
316181AB2-040 GEN
Solar/Wind Harmer
5.316
3145796HORNRTN
Solar/Wind Harmer
-0.106
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3145593CAROLNA
Solar/Wind Harmer
-0.029
3145593CAROLNA
Solar/Wind Harmer
-0.029
966811AG1-552 GEN
Solar/Wind Harmer
3.246
3145593CAROLNA
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
3.322
3145783HORNRTN
Solar/Wind Harmer
2.657
3145783HORNRTN
Solar/Wind Harmer
0.83
3145783HORNRTN
Solar/Wind Harmer
0.332
316426AA2-053 GEN
Solar/Wind Harmer
2.731
316274AC1-208 GEN
Solar/Wind Harmer
2.529
961601AG1-000A GEN
Solar/Wind Harmer
7.998
316263AC1-034 GEN
Solar/Wind Harmer
9.349
3145493TOT1
Solar/Wind Harmer
0.288
3145453TOT5
Solar/Wind Harmer
0.173
3145603CNETO
Solar/Wind Harmer
0.115
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.5
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.029
3145933PARMELE
Solar/Wind Harmer
-0.015
313527AB2-043 GEN
Solar/Wind Harmer
2.401
939181AE1-148 GEN
Solar/Wind Harmer
8.293
316065AD1-022 GEN
Solar/Wind Harmer
6.431
970323AG2-213 GEN
Solar/Wind Harmer
6.159
971775AH1-396 GEN
Solar/Wind Harmer
0.877
316034AC1-036 C
Solar/Wind Harmer
0.228
962561AG1-105 GEN
Solar/Wind Harmer
6.642
964791AG1-342 GEN
Solar/Wind Harmer
2.408
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
958211AF2-115 GEN
Solar/Wind Harmer
1.593
963191AG1-168 GEN
Solar/Wind Harmer
0.956
3144293JTRSVLE
Adder
0.289
3144293JTRSVLE
Adder
0.243
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.303
970933AG2-581 GEN
Solar/Wind Harmer
7.708
315742AE1-103 GEN
Solar/Wind Harmer
0.833
971741AH1-377 GEN
Solar/Wind Harmer
7.93
316222AC1-221 GEN
Solar/Wind Harmer
0.684
970301AG2-198 GEN
Solar/Wind Harmer
3.213
3151391GASTONA
50/50
0.92
3151411GASTONB
50/50
0.92
3147043LAWRENC
50/50
3.14
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.271
3151581KERR 1
50/50
0.097
316023GEN1_S
Solar/Wind Harmer
3.897
960081AF2-299 GEN
Solar/Wind Harmer
5.216
971795AH1-408 GEN
Solar/Wind Harmer
29.838
316011AB1-132 GEN
Solar/Wind Harmer
7.998
962571AG1-106 GEN
Solar/Wind Harmer
5.495
3145796HORNRTN
Solar/Wind Harmer
-0.117
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145783HORNRTN
Solar/Wind Harmer
-0.028
315722AD1-056 GEN
Solar/Wind Harmer
2.848
316190AA2-174 GEN
Solar/Wind Harmer
0.332
316212AC1-099_GEN
Solar/Wind Harmer
1.925
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
-0.082
316359AB2-059 GEN
Solar/Wind Harmer
2.689
316049AB1-081 GEN
Solar/Wind Harmer
2.152
3142053HEARTS
Solar/Wind Harmer
0.234
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316129AC1-054 GEN
Solar/Wind Harmer
1.724
971065AG2-659 GEN
Solar/Wind Harmer
9.42
3145683EARLEYS
Solar/Wind Harmer
-0.019
961671AG1-007 GEN
Solar/Wind Harmer
0.235
3146083TARBORO
Solar/Wind Harmer
-0.019
3145493TOT1
Solar/Wind Harmer
0.552
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.071
3145893MURPHYS
Solar/Wind Harmer
0.532
316494AC1-189 GEN
Solar/Wind Harmer
1.849
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146293MARTNCO
Solar/Wind Harmer
0.092
316237AB2-079_GEN
Solar/Wind Harmer
0.44
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.427
316174AB2-169 GEN
Solar/Wind Harmer
2.087
3145963POPLR C
Solar/Wind Harmer
-0.013
970401AG2-262 GEN
Solar/Wind Harmer
0.736
970685AG2-442 GEN
Solar/Wind Harmer
9.824
963171AG1-166 GEN
Solar/Wind Harmer
1.274
971563AH1-280 GEN
Solar/Wind Harmer
1.274
3144293JTRSVLE
Adder
0.289
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.342
957481AF2-042 GEN
Solar/Wind Harmer
25.757
316003AC1-222 GEN
Solar/Wind Harmer
0.805
315693AD1-088 GEN
Solar/Wind Harmer
4.077
315687AD1-152 GEN
Solar/Wind Harmer
0.978
962491AG1-098 GEN
Solar/Wind Harmer
5.393
316240AF1-291 C
Solar/Wind Helper
0.173
3151391GASTONA
50/50
0.92
3151411GASTONB
50/50
0.92
3151261ROARAP2
50/50
0.312
3151591KERR 2
50/50
0.271
316365GEN2_N
Solar/Wind Harmer
3.897
966621AG1-532 GEN
Solar/Wind Harmer
0.941
313506AB2-031 GEN
Solar/Wind Harmer
3.063
3147043LAWRENC
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.142
3145796HORNRTN
Solar/Wind Harmer
-0.036
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
315724AD1-057 GEN
Solar/Wind Harmer
1.566
316210AC1-098 GEN
Solar/Wind Harmer
3.466
316327AA2-057 GEN
Solar/Wind Harmer
2.179
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
0.434
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
8.099
316317KELFORD C
Solar/Wind Harmer
0.938
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3146073TAR RVR
Solar/Wind Harmer
-0.019
3146083TARBORO
Solar/Wind Harmer
-0.019
316463AE2-346 GEN
Solar/Wind Harmer
0.3
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.313
3146173TUNIS
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.207
961681AG1-008 GEN
Solar/Wind Harmer
14.207
3145893MURPHYS
Solar/Wind Harmer
0.125
3145893MURPHYS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.291
3156081AA2-088 GEN
Solar/Wind Harmer
5.448
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.847
316131AB2-060 GEN
Solar/Wind Harmer
1.576
964241AG1-285 GEN
Solar/Wind Harmer
10.867
3146206CASHIE
Solar/Wind Harmer
-0.014
3145963POPLR C
Solar/Wind Harmer
-0.013
315785AD2-033 C
Solar/Wind Harmer
2.89
970257AG2-171 GEN
Solar/Wind Harmer
4.619
959311AF2-222 GEN
Solar/Wind Harmer
12.534
315737AD1-076 GEN
Solar/Wind Harmer
2.166
971157AH1-035 GEN
Solar/Wind Harmer
1.375
963181AG1-167 GEN
Solar/Wind Harmer
0.956
3144293JTRSVLE
Adder
0.289
3147133PAMPLIN
Solar/Wind Harmer
-0.03
971193AH1-056 GEN
Solar/Wind Harmer
5.922
315614AA2-178 GEN
Solar/Wind Harmer
0.96
316248AF1-058 C
Solar/Wind Harmer
0.264
960061AF2-297 GEN
Solar/Wind Harmer
4.376
316478AD1-087 GEN
Solar/Wind Harmer
0.718
316486AD2-202 GEN
Solar/Wind Harmer
0.21
971683AH1-343 GEN
Solar/Wind Harmer
3.362
942461AE2-259 GEN
Solar/Wind Harmer
1.117
316283AC2-100 C
Solar/Wind Harmer
0.633
970909AG2-566 GEN
Solar/Wind Harmer
0.61
315839AE2-212 C
Solar/Wind Helper
0.202
315779AE2-040
50/50
11.856
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.271
3151621KERR 5
50/50
0.271
3151631KERR 6
50/50
0.271
3151641KERR 7
50/50
0.271
316315AB2-025 C
Solar/Wind Harmer
2.574
315814AE2-033 C
Solar/Wind Harmer
87.029
946281AF1-292 GEN
Solar/Wind Harmer
1.038
316087AB2-174 GEN
Solar/Wind Harmer
5.792
315652AC1-086 GEN
Solar/Wind Harmer
43.007
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.014
3137643SOCKMAN
Solar/Wind Harmer
-0.131
315607AA1-063A GEN
Solar/Wind Harmer
2.465
3146043SEABORD
Solar/Wind Harmer
-0.024
3146033SCOT NK
Solar/Wind Harmer
-0.084
316319Z2-044 C
Solar/Wind Harmer
1.145
970831AG2-522 GEN
Solar/Wind Harmer
10.274
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.161
961941AG1-037 GEN
Solar/Wind Harmer
0.139
3145513AHOSKIE
Solar/Wind Harmer
-0.018
316420AA1-050 GEN
Solar/Wind Harmer
2.054
316318V4-068
Solar/Wind Harmer
0.447
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
965291AG1-394 GEN
Solar/Wind Harmer
1.56
957861AF2-080 GEN
Solar/Wind Harmer
7.517
316005AA1-067
Solar/Wind Harmer
0.314
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
2.038
316239AB2-077_GEN
Solar/Wind Harmer
0.44
316238AB2-078_GEN
Solar/Wind Harmer
0.44
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
5.997
971443AH1-215 GEN
Solar/Wind Harmer
2.445
3144303KENBRDG
Solar/Wind Harmer
-0.01
315732AD1-074 GEN1
Solar/Wind Harmer
2.305
315733AD1-074 GEN2
Solar/Wind Harmer
2.305
315735AD1-075 GEN1
Solar/Wind Harmer
1.153
970683AG2-441 GEN
Solar/Wind Harmer
8.771
970681AG2-440 GEN
Solar/Wind Harmer
7.017
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
946301AF1-294 GEN
Solar/Wind Harmer
2.612
961791AG1-021 GEN
Solar/Wind Harmer
1.274
316118AC1-105 GEN
Solar/Wind Harmer
0.687
315657AE1-056 GEN
Solar/Wind Harmer
3.553
315816AE2-034 GEN
Solar/Wind Harmer
0.72
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
971967AH1-528 GEN
Solar/Wind Harmer
15.454
970865AG2-541 GEN
Solar/Wind Harmer
2.98
316123AC1-075 GEN
Solar/Wind Harmer
0.69
970165AG2-112 GEN
Solar/Wind Harmer
0.608
970163AG2-111 GEN
Solar/Wind Harmer
0.58
3143316POE
Solar/Wind Helper
0.702
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.173
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.798
MECLTFEXP_MEC->PJM
CLTF
1.381
SIGELTFEXP_SIGE->PJM
CLTF
0.041
CPLELTFEXP_CPLE->PJM
CLTF
4.641
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.852
LAGNLTFEXP_LAGN->PJM
CLTF
2.804
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.13
TVALTFEXP_TVA->PJM
CLTF
1.399
NYPJM->LTFIMP_NY
CLTF
0.52
LGEELTFEXP_LGEE->PJM
CLTF
0.5
WECLTFEXP_WEC->PJM
CLTF
0.26

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.4 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1115.54
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.92
3151411GASTONB
50/50
0.92
3147043LAWRENC
50/50
3.139
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.269
3151581KERR 1
50/50
0.096
316023GEN1_S
Solar/Wind Harmer
3.901
960081AF2-299 GEN
Solar/Wind Harmer
5.218
971795AH1-408 GEN
Solar/Wind Harmer
29.836
316011AB1-132 GEN
Solar/Wind Harmer
7.998
962571AG1-106 GEN
Solar/Wind Harmer
5.495
3145796HORNRTN
Solar/Wind Harmer
-0.117
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145783HORNRTN
Solar/Wind Harmer
-0.028
315722AD1-056 GEN
Solar/Wind Harmer
2.839
316190AA2-174 GEN
Solar/Wind Harmer
0.332
316212AC1-099_GEN
Solar/Wind Harmer
1.921
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
-0.082
3145823KELFORD
Solar/Wind Harmer
-0.02
316359AB2-059 GEN
Solar/Wind Harmer
2.671
316049AB1-081 GEN
Solar/Wind Harmer
2.138
3142053HEARTS
Solar/Wind Harmer
0.233
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316129AC1-054 GEN
Solar/Wind Harmer
1.717
971065AG2-659 GEN
Solar/Wind Harmer
9.378
3145683EARLEYS
Solar/Wind Harmer
-0.019
961671AG1-007 GEN
Solar/Wind Harmer
0.234
3146083TARBORO
Solar/Wind Harmer
-0.018
3145493TOT1
Solar/Wind Harmer
0.549
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.072
3145893MURPHYS
Solar/Wind Harmer
0.533
316494AC1-189 GEN
Solar/Wind Harmer
1.839
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146293MARTNCO
Solar/Wind Harmer
0.091
316237AB2-079_GEN
Solar/Wind Harmer
0.437
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.438
316174AB2-169 GEN
Solar/Wind Harmer
2.085
3145963POPLR C
Solar/Wind Harmer
-0.013
970685AG2-442 GEN
Solar/Wind Harmer
9.758
970401AG2-262 GEN
Solar/Wind Harmer
0.728
963171AG1-166 GEN
Solar/Wind Harmer
1.265
971563AH1-280 GEN
Solar/Wind Harmer
1.265
3144293JTRSVLE
Adder
0.287
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.42
957481AF2-042 GEN
Solar/Wind Harmer
25.432
316003AC1-222 GEN
Solar/Wind Harmer
0.791
315693AD1-088 GEN
Solar/Wind Harmer
4.013
315687AD1-152 GEN
Solar/Wind Harmer
0.961
962491AG1-098 GEN
Solar/Wind Harmer
5.309
3151361ROSEMG1
50/50
1.142
3151371ROSEMS1
50/50
0.707
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.318
3144356SAPONY
Solar/Wind Harmer
3.334
316181AB2-040 GEN
Solar/Wind Harmer
5.317
3145796HORNRTN
Solar/Wind Harmer
-0.106
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3145593CAROLNA
Solar/Wind Harmer
-0.029
3145593CAROLNA
Solar/Wind Harmer
-0.029
966811AG1-552 GEN
Solar/Wind Harmer
3.244
3145593CAROLNA
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
3.319
3145783HORNRTN
Solar/Wind Harmer
2.655
3145783HORNRTN
Solar/Wind Harmer
0.83
3145783HORNRTN
Solar/Wind Harmer
0.332
316426AA2-053 GEN
Solar/Wind Harmer
2.73
316274AC1-208 GEN
Solar/Wind Harmer
2.523
961601AG1-000A GEN
Solar/Wind Harmer
7.946
316263AC1-034 GEN
Solar/Wind Harmer
9.288
3145493TOT1
Solar/Wind Harmer
0.286
3145453TOT5
Solar/Wind Harmer
0.172
3145603CNETO
Solar/Wind Harmer
0.114
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.501
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.029
3145933PARMELE
Solar/Wind Harmer
-0.015
313527AB2-043 GEN
Solar/Wind Harmer
2.386
939181AE1-148 GEN
Solar/Wind Harmer
8.232
316065AD1-022 GEN
Solar/Wind Harmer
6.456
970323AG2-213 GEN
Solar/Wind Harmer
6.119
971775AH1-396 GEN
Solar/Wind Harmer
0.871
316034AC1-036 C
Solar/Wind Harmer
0.227
962561AG1-105 GEN
Solar/Wind Harmer
6.574
964791AG1-342 GEN
Solar/Wind Harmer
2.382
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
958211AF2-115 GEN
Solar/Wind Harmer
1.582
963191AG1-168 GEN
Solar/Wind Harmer
0.949
3144293JTRSVLE
Adder
0.287
3144293JTRSVLE
Adder
0.242
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.173
315742AE1-103 GEN
Solar/Wind Harmer
0.845
971741AH1-377 GEN
Solar/Wind Harmer
7.826
316222AC1-221 GEN
Solar/Wind Harmer
0.66
970301AG2-198 GEN
Solar/Wind Harmer
3.173
316240AF1-291 C
Solar/Wind Helper
0.169
3151391GASTONA
50/50
0.92
3151411GASTONB
50/50
0.92
3151261ROARAP2
50/50
0.312
3151591KERR 2
50/50
0.269
316365GEN2_N
Solar/Wind Harmer
3.901
966621AG1-532 GEN
Solar/Wind Harmer
0.941
313506AB2-031 GEN
Solar/Wind Harmer
3.064
3147043LAWRENC
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.142
3145796HORNRTN
Solar/Wind Harmer
-0.036
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
315724AD1-057 GEN
Solar/Wind Harmer
1.562
316210AC1-098 GEN
Solar/Wind Harmer
3.458
316327AA2-057 GEN
Solar/Wind Harmer
2.17
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
0.431
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
8.047
316317KELFORD C
Solar/Wind Harmer
0.937
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
316463AE2-346 GEN
Solar/Wind Harmer
0.3
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.316
3146073TAR RVR
Solar/Wind Harmer
-0.018
3146083TARBORO
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.236
961681AG1-008 GEN
Solar/Wind Harmer
14.236
3145893MURPHYS
Solar/Wind Harmer
0.125
3145893MURPHYS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.295
3156081AA2-088 GEN
Solar/Wind Harmer
5.466
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.841
316131AB2-060 GEN
Solar/Wind Harmer
1.565
964241AG1-285 GEN
Solar/Wind Harmer
10.797
3146206CASHIE
Solar/Wind Harmer
-0.014
3145963POPLR C
Solar/Wind Harmer
-0.013
315785AD2-033 C
Solar/Wind Harmer
2.871
970257AG2-171 GEN
Solar/Wind Harmer
4.589
959311AF2-222 GEN
Solar/Wind Harmer
12.451
315737AD1-076 GEN
Solar/Wind Harmer
2.177
971157AH1-035 GEN
Solar/Wind Harmer
1.382
963181AG1-167 GEN
Solar/Wind Harmer
0.949
3144293JTRSVLE
Adder
0.287
3147133PAMPLIN
Solar/Wind Harmer
-0.029
971193AH1-056 GEN
Solar/Wind Harmer
5.881
315614AA2-178 GEN
Solar/Wind Harmer
0.969
316248AF1-058 C
Solar/Wind Harmer
0.259
960061AF2-297 GEN
Solar/Wind Harmer
4.303
316478AD1-087 GEN
Solar/Wind Harmer
0.708
316486AD2-202 GEN
Solar/Wind Harmer
0.207
971683AH1-343 GEN
Solar/Wind Harmer
3.303
942461AE2-259 GEN
Solar/Wind Harmer
1.109
316283AC2-100 C
Solar/Wind Harmer
0.611
970909AG2-566 GEN
Solar/Wind Harmer
0.603
315839AE2-212 C
Solar/Wind Helper
0.198
315779AE2-040
50/50
11.875
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.269
3151621KERR 5
50/50
0.269
3151631KERR 6
50/50
0.269
3151641KERR 7
50/50
0.269
316315AB2-025 C
Solar/Wind Harmer
2.579
315814AE2-033 C
Solar/Wind Harmer
87.173
946281AF1-292 GEN
Solar/Wind Harmer
1.039
316087AB2-174 GEN
Solar/Wind Harmer
5.794
315652AC1-086 GEN
Solar/Wind Harmer
43.006
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.014
3137643SOCKMAN
Solar/Wind Harmer
-0.131
315607AA1-063A GEN
Solar/Wind Harmer
2.466
3146043SEABORD
Solar/Wind Harmer
-0.024
3146033SCOT NK
Solar/Wind Harmer
-0.084
316319Z2-044 C
Solar/Wind Harmer
1.138
970831AG2-522 GEN
Solar/Wind Harmer
10.238
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.162
961941AG1-037 GEN
Solar/Wind Harmer
0.139
3145513AHOSKIE
Solar/Wind Harmer
-0.018
3145573BETHELC
Solar/Wind Harmer
-0.018
3145573BETHELC
Solar/Wind Harmer
-0.018
316318V4-068
Solar/Wind Harmer
0.448
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
316420AA1-050 GEN
Solar/Wind Harmer
2.042
965291AG1-394 GEN
Solar/Wind Harmer
1.564
957861AF2-080 GEN
Solar/Wind Harmer
7.476
316005AA1-067
Solar/Wind Harmer
0.313
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
2.028
316239AB2-077_GEN
Solar/Wind Harmer
0.437
316238AB2-078_GEN
Solar/Wind Harmer
0.437
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
6.017
971443AH1-215 GEN
Solar/Wind Harmer
2.429
3144303KENBRDG
Solar/Wind Harmer
-0.01
315732AD1-074 GEN1
Solar/Wind Harmer
2.317
315733AD1-074 GEN2
Solar/Wind Harmer
2.317
315735AD1-075 GEN1
Solar/Wind Harmer
1.159
970683AG2-441 GEN
Solar/Wind Harmer
8.713
970681AG2-440 GEN
Solar/Wind Harmer
6.97
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
946301AF1-294 GEN
Solar/Wind Harmer
2.594
961791AG1-021 GEN
Solar/Wind Harmer
1.265
316118AC1-105 GEN
Solar/Wind Harmer
0.678
315657AE1-056 GEN
Solar/Wind Harmer
3.529
315816AE2-034 GEN
Solar/Wind Harmer
0.727
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
970865AG2-541 GEN
Solar/Wind Harmer
2.926
3143316POE
Solar/Wind Helper
0.689
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.681
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.544
MECLTFEXP_MEC->PJM
CLTF
1.308
SIGELTFEXP_SIGE->PJM
CLTF
0.039
CPLELTFEXP_CPLE->PJM
CLTF
4.438
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.063
LAGNLTFEXP_LAGN->PJM
CLTF
2.655
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.673
TVALTFEXP_TVA->PJM
CLTF
1.324
NYPJM->LTFIMP_NY
CLTF
0.497
LGEELTFEXP_LGEE->PJM
CLTF
0.473
WECLTFEXP_WEC->PJM
CLTF
0.246

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.4 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1115.54
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.92
3151411GASTONB
50/50
0.92
3147043LAWRENC
50/50
3.139
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.269
3151581KERR 1
50/50
0.096
316023GEN1_S
Solar/Wind Harmer
3.901
960081AF2-299 GEN
Solar/Wind Harmer
5.218
971795AH1-408 GEN
Solar/Wind Harmer
29.836
316011AB1-132 GEN
Solar/Wind Harmer
7.998
962571AG1-106 GEN
Solar/Wind Harmer
5.495
3145796HORNRTN
Solar/Wind Harmer
-0.117
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145783HORNRTN
Solar/Wind Harmer
-0.028
315722AD1-056 GEN
Solar/Wind Harmer
2.839
316190AA2-174 GEN
Solar/Wind Harmer
0.332
316212AC1-099_GEN
Solar/Wind Harmer
1.921
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
-0.082
3145823KELFORD
Solar/Wind Harmer
-0.02
316359AB2-059 GEN
Solar/Wind Harmer
2.671
316049AB1-081 GEN
Solar/Wind Harmer
2.138
3142053HEARTS
Solar/Wind Harmer
0.233
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316129AC1-054 GEN
Solar/Wind Harmer
1.717
971065AG2-659 GEN
Solar/Wind Harmer
9.378
3145683EARLEYS
Solar/Wind Harmer
-0.019
961671AG1-007 GEN
Solar/Wind Harmer
0.234
3146083TARBORO
Solar/Wind Harmer
-0.018
3145493TOT1
Solar/Wind Harmer
0.549
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.072
3145893MURPHYS
Solar/Wind Harmer
0.533
316494AC1-189 GEN
Solar/Wind Harmer
1.839
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146293MARTNCO
Solar/Wind Harmer
0.091
316237AB2-079_GEN
Solar/Wind Harmer
0.437
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.438
316174AB2-169 GEN
Solar/Wind Harmer
2.085
3145963POPLR C
Solar/Wind Harmer
-0.013
970685AG2-442 GEN
Solar/Wind Harmer
9.758
970401AG2-262 GEN
Solar/Wind Harmer
0.728
963171AG1-166 GEN
Solar/Wind Harmer
1.265
971563AH1-280 GEN
Solar/Wind Harmer
1.265
3144293JTRSVLE
Adder
0.287
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.42
957481AF2-042 GEN
Solar/Wind Harmer
25.432
316003AC1-222 GEN
Solar/Wind Harmer
0.791
315693AD1-088 GEN
Solar/Wind Harmer
4.013
315687AD1-152 GEN
Solar/Wind Harmer
0.961
962491AG1-098 GEN
Solar/Wind Harmer
5.309
3151361ROSEMG1
50/50
1.142
3151371ROSEMS1
50/50
0.707
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.318
3144356SAPONY
Solar/Wind Harmer
3.334
316181AB2-040 GEN
Solar/Wind Harmer
5.317
3145796HORNRTN
Solar/Wind Harmer
-0.106
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3145593CAROLNA
Solar/Wind Harmer
-0.029
3145593CAROLNA
Solar/Wind Harmer
-0.029
966811AG1-552 GEN
Solar/Wind Harmer
3.244
3145593CAROLNA
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
3.319
3145783HORNRTN
Solar/Wind Harmer
2.655
3145783HORNRTN
Solar/Wind Harmer
0.83
3145783HORNRTN
Solar/Wind Harmer
0.332
316426AA2-053 GEN
Solar/Wind Harmer
2.73
316274AC1-208 GEN
Solar/Wind Harmer
2.523
961601AG1-000A GEN
Solar/Wind Harmer
7.946
316263AC1-034 GEN
Solar/Wind Harmer
9.288
3145493TOT1
Solar/Wind Harmer
0.286
3145453TOT5
Solar/Wind Harmer
0.172
3145603CNETO
Solar/Wind Harmer
0.114
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.501
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.029
3145933PARMELE
Solar/Wind Harmer
-0.015
313527AB2-043 GEN
Solar/Wind Harmer
2.386
939181AE1-148 GEN
Solar/Wind Harmer
8.232
316065AD1-022 GEN
Solar/Wind Harmer
6.456
970323AG2-213 GEN
Solar/Wind Harmer
6.119
971775AH1-396 GEN
Solar/Wind Harmer
0.871
316034AC1-036 C
Solar/Wind Harmer
0.227
962561AG1-105 GEN
Solar/Wind Harmer
6.574
964791AG1-342 GEN
Solar/Wind Harmer
2.382
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
958211AF2-115 GEN
Solar/Wind Harmer
1.582
963191AG1-168 GEN
Solar/Wind Harmer
0.949
3144293JTRSVLE
Adder
0.287
3144293JTRSVLE
Adder
0.242
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.173
315742AE1-103 GEN
Solar/Wind Harmer
0.845
971741AH1-377 GEN
Solar/Wind Harmer
7.826
316222AC1-221 GEN
Solar/Wind Harmer
0.66
970301AG2-198 GEN
Solar/Wind Harmer
3.173
316240AF1-291 C
Solar/Wind Helper
0.169
3151391GASTONA
50/50
0.92
3151411GASTONB
50/50
0.92
3151261ROARAP2
50/50
0.312
3151591KERR 2
50/50
0.269
316365GEN2_N
Solar/Wind Harmer
3.901
966621AG1-532 GEN
Solar/Wind Harmer
0.941
313506AB2-031 GEN
Solar/Wind Harmer
3.064
3147043LAWRENC
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.142
3145796HORNRTN
Solar/Wind Harmer
-0.036
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
315779AE2-040
50/50
11.875
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.269
3151621KERR 5
50/50
0.269
3151631KERR 6
50/50
0.269
3151641KERR 7
50/50
0.269
316315AB2-025 C
Solar/Wind Harmer
2.579
315814AE2-033 C
Solar/Wind Harmer
87.173
946281AF1-292 GEN
Solar/Wind Harmer
1.039
316087AB2-174 GEN
Solar/Wind Harmer
5.794
315652AC1-086 GEN
Solar/Wind Harmer
43.006
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.014
3137643SOCKMAN
Solar/Wind Harmer
-0.131
315607AA1-063A GEN
Solar/Wind Harmer
2.466
3146043SEABORD
Solar/Wind Harmer
-0.024
3146033SCOT NK
Solar/Wind Harmer
-0.084
316319Z2-044 C
Solar/Wind Harmer
1.138
970831AG2-522 GEN
Solar/Wind Harmer
10.238
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.162
961941AG1-037 GEN
Solar/Wind Harmer
0.139
3145513AHOSKIE
Solar/Wind Harmer
-0.018
315724AD1-057 GEN
Solar/Wind Harmer
1.562
316210AC1-098 GEN
Solar/Wind Harmer
3.458
316327AA2-057 GEN
Solar/Wind Harmer
2.17
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
0.431
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
8.047
316317KELFORD C
Solar/Wind Harmer
0.937
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
316463AE2-346 GEN
Solar/Wind Harmer
0.3
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.316
3146073TAR RVR
Solar/Wind Harmer
-0.018
3146083TARBORO
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.236
961681AG1-008 GEN
Solar/Wind Harmer
14.236
3145893MURPHYS
Solar/Wind Harmer
0.125
3145893MURPHYS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.295
3156081AA2-088 GEN
Solar/Wind Harmer
5.466
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.841
316131AB2-060 GEN
Solar/Wind Harmer
1.565
964241AG1-285 GEN
Solar/Wind Harmer
10.797
3146206CASHIE
Solar/Wind Harmer
-0.014
3145963POPLR C
Solar/Wind Harmer
-0.013
315785AD2-033 C
Solar/Wind Harmer
2.871
970257AG2-171 GEN
Solar/Wind Harmer
4.589
959311AF2-222 GEN
Solar/Wind Harmer
12.451
315737AD1-076 GEN
Solar/Wind Harmer
2.177
971157AH1-035 GEN
Solar/Wind Harmer
1.382
963181AG1-167 GEN
Solar/Wind Harmer
0.949
3144293JTRSVLE
Adder
0.287
3147133PAMPLIN
Solar/Wind Harmer
-0.029
971193AH1-056 GEN
Solar/Wind Harmer
5.881
315614AA2-178 GEN
Solar/Wind Harmer
0.969
316248AF1-058 C
Solar/Wind Harmer
0.259
960061AF2-297 GEN
Solar/Wind Harmer
4.303
316478AD1-087 GEN
Solar/Wind Harmer
0.708
316486AD2-202 GEN
Solar/Wind Harmer
0.207
971683AH1-343 GEN
Solar/Wind Harmer
3.303
942461AE2-259 GEN
Solar/Wind Harmer
1.109
316283AC2-100 C
Solar/Wind Harmer
0.611
970909AG2-566 GEN
Solar/Wind Harmer
0.603
315839AE2-212 C
Solar/Wind Helper
0.198
3145573BETHELC
Solar/Wind Harmer
-0.018
3145573BETHELC
Solar/Wind Harmer
-0.018
316318V4-068
Solar/Wind Harmer
0.448
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
316420AA1-050 GEN
Solar/Wind Harmer
2.042
965291AG1-394 GEN
Solar/Wind Harmer
1.564
957861AF2-080 GEN
Solar/Wind Harmer
7.476
316005AA1-067
Solar/Wind Harmer
0.313
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
2.028
316239AB2-077_GEN
Solar/Wind Harmer
0.437
316238AB2-078_GEN
Solar/Wind Harmer
0.437
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
6.017
971443AH1-215 GEN
Solar/Wind Harmer
2.429
3144303KENBRDG
Solar/Wind Harmer
-0.01
315732AD1-074 GEN1
Solar/Wind Harmer
2.317
315733AD1-074 GEN2
Solar/Wind Harmer
2.317
315735AD1-075 GEN1
Solar/Wind Harmer
1.159
970683AG2-441 GEN
Solar/Wind Harmer
8.713
970681AG2-440 GEN
Solar/Wind Harmer
6.97
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
946301AF1-294 GEN
Solar/Wind Harmer
2.594
961791AG1-021 GEN
Solar/Wind Harmer
1.265
316118AC1-105 GEN
Solar/Wind Harmer
0.678
315657AE1-056 GEN
Solar/Wind Harmer
3.529
315816AE2-034 GEN
Solar/Wind Harmer
0.727
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
970865AG2-541 GEN
Solar/Wind Harmer
2.926
3143316POE
Solar/Wind Helper
0.689
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.681
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.544
MECLTFEXP_MEC->PJM
CLTF
1.308
SIGELTFEXP_SIGE->PJM
CLTF
0.039
CPLELTFEXP_CPLE->PJM
CLTF
4.438
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.063
LAGNLTFEXP_LAGN->PJM
CLTF
2.655
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.673
TVALTFEXP_TVA->PJM
CLTF
1.324
NYPJM->LTFIMP_NY
CLTF
0.497
LGEELTFEXP_LGEE->PJM
CLTF
0.473
WECLTFEXP_WEC->PJM
CLTF
0.246

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.39 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1115.4
MW Contribution:2.32
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.92
3151411GASTONB
50/50
0.92
3147043LAWRENC
50/50
3.139
3151261ROARAP2
50/50
0.32
3151601KERR 3
50/50
0.269
3151581KERR 1
50/50
0.096
316023GEN1_S
Solar/Wind Harmer
3.901
960081AF2-299 GEN
Solar/Wind Harmer
5.218
971795AH1-408 GEN
Solar/Wind Harmer
29.836
316011AB1-132 GEN
Solar/Wind Harmer
7.998
962571AG1-106 GEN
Solar/Wind Harmer
5.495
3145796HORNRTN
Solar/Wind Harmer
-0.117
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145783HORNRTN
Solar/Wind Harmer
-0.028
315722AD1-056 GEN
Solar/Wind Harmer
2.839
316190AA2-174 GEN
Solar/Wind Harmer
0.332
316212AC1-099_GEN
Solar/Wind Harmer
1.921
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
-0.082
3145823KELFORD
Solar/Wind Harmer
-0.02
316359AB2-059 GEN
Solar/Wind Harmer
2.671
316049AB1-081 GEN
Solar/Wind Harmer
2.138
3142053HEARTS
Solar/Wind Harmer
0.233
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316129AC1-054 GEN
Solar/Wind Harmer
1.717
971065AG2-659 GEN
Solar/Wind Harmer
9.379
3145683EARLEYS
Solar/Wind Harmer
-0.019
961671AG1-007 GEN
Solar/Wind Harmer
0.234
3146083TARBORO
Solar/Wind Harmer
-0.018
3145493TOT1
Solar/Wind Harmer
0.549
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.072
3145893MURPHYS
Solar/Wind Harmer
0.533
316494AC1-189 GEN
Solar/Wind Harmer
1.839
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146293MARTNCO
Solar/Wind Harmer
0.091
316237AB2-079_GEN
Solar/Wind Harmer
0.437
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.438
316174AB2-169 GEN
Solar/Wind Harmer
2.085
3145963POPLR C
Solar/Wind Harmer
-0.013
970685AG2-442 GEN
Solar/Wind Harmer
9.762
970401AG2-262 GEN
Solar/Wind Harmer
0.728
963171AG1-166 GEN
Solar/Wind Harmer
1.266
971563AH1-280 GEN
Solar/Wind Harmer
1.266
3144293JTRSVLE
Adder
0.287
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.42
957481AF2-042 GEN
Solar/Wind Harmer
25.369
316003AC1-222 GEN
Solar/Wind Harmer
0.79
315693AD1-088 GEN
Solar/Wind Harmer
4.02
315687AD1-152 GEN
Solar/Wind Harmer
0.96
962491AG1-098 GEN
Solar/Wind Harmer
5.319
3151361ROSEMG1
50/50
1.142
3151371ROSEMS1
50/50
0.707
3151381ROSEMG2
50/50
0.535
970535AG2-341 GEN
50/50
2.318
3144356SAPONY
Solar/Wind Harmer
3.334
316181AB2-040 GEN
Solar/Wind Harmer
5.317
3145796HORNRTN
Solar/Wind Harmer
-0.106
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
3142666NORTHAMPTON
Solar/Wind Harmer
-0.021
3145593CAROLNA
Solar/Wind Harmer
-0.029
3145593CAROLNA
Solar/Wind Harmer
-0.029
966811AG1-552 GEN
Solar/Wind Harmer
3.244
3145593CAROLNA
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
3.319
3145783HORNRTN
Solar/Wind Harmer
2.655
3145783HORNRTN
Solar/Wind Harmer
0.83
3145783HORNRTN
Solar/Wind Harmer
0.332
316426AA2-053 GEN
Solar/Wind Harmer
2.73
316274AC1-208 GEN
Solar/Wind Harmer
2.523
961601AG1-000A GEN
Solar/Wind Harmer
7.946
316263AC1-034 GEN
Solar/Wind Harmer
9.287
3145493TOT1
Solar/Wind Harmer
0.286
3145453TOT5
Solar/Wind Harmer
0.172
3145603CNETO
Solar/Wind Harmer
0.114
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.501
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.029
3145933PARMELE
Solar/Wind Harmer
-0.015
313527AB2-043 GEN
Solar/Wind Harmer
2.386
939181AE1-148 GEN
Solar/Wind Harmer
8.233
316065AD1-022 GEN
Solar/Wind Harmer
6.456
970323AG2-213 GEN
Solar/Wind Harmer
6.12
971775AH1-396 GEN
Solar/Wind Harmer
0.872
316034AC1-036 C
Solar/Wind Harmer
0.227
962561AG1-105 GEN
Solar/Wind Harmer
6.574
964791AG1-342 GEN
Solar/Wind Harmer
2.381
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
958211AF2-115 GEN
Solar/Wind Harmer
1.582
963191AG1-168 GEN
Solar/Wind Harmer
0.949
3144293JTRSVLE
Adder
0.287
3144293JTRSVLE
Adder
0.242
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.147
315742AE1-103 GEN
Solar/Wind Harmer
0.846
971741AH1-377 GEN
Solar/Wind Harmer
7.84
316222AC1-221 GEN
Solar/Wind Harmer
0.66
970301AG2-198 GEN
Solar/Wind Harmer
3.179
316240AF1-291 C
Solar/Wind Helper
0.169
3151391GASTONA
50/50
0.92
3151411GASTONB
50/50
0.92
3151261ROARAP2
50/50
0.312
3151591KERR 2
50/50
0.269
316365GEN2_N
Solar/Wind Harmer
3.901
966621AG1-532 GEN
Solar/Wind Harmer
0.941
313506AB2-031 GEN
Solar/Wind Harmer
3.064
3147043LAWRENC
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.142
3145796HORNRTN
Solar/Wind Harmer
-0.036
3142666NORTHAMPTON
Solar/Wind Harmer
-0.035
315724AD1-057 GEN
Solar/Wind Harmer
1.562
316210AC1-098 GEN
Solar/Wind Harmer
3.458
316327AA2-057 GEN
Solar/Wind Harmer
2.17
3146263WOODLND
Solar/Wind Harmer
-0.021
3146233WITAKRS
Solar/Wind Harmer
0.431
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
8.047
316317KELFORD C
Solar/Wind Harmer
0.937
3145823KELFORD
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
316463AE2-346 GEN
Solar/Wind Harmer
0.3
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.316
3146073TAR RVR
Solar/Wind Harmer
-0.018
3146083TARBORO
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.236
961681AG1-008 GEN
Solar/Wind Harmer
14.236
3145893MURPHYS
Solar/Wind Harmer
0.125
3145893MURPHYS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.295
3156081AA2-088 GEN
Solar/Wind Harmer
5.466
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.841
316131AB2-060 GEN
Solar/Wind Harmer
1.566
964241AG1-285 GEN
Solar/Wind Harmer
10.798
3146206CASHIE
Solar/Wind Harmer
-0.014
3145963POPLR C
Solar/Wind Harmer
-0.013
315785AD2-033 C
Solar/Wind Harmer
2.872
970257AG2-171 GEN
Solar/Wind Harmer
4.59
959311AF2-222 GEN
Solar/Wind Harmer
12.455
315737AD1-076 GEN
Solar/Wind Harmer
2.177
971157AH1-035 GEN
Solar/Wind Harmer
1.382
963181AG1-167 GEN
Solar/Wind Harmer
0.949
3144293JTRSVLE
Adder
0.287
3147133PAMPLIN
Solar/Wind Harmer
-0.029
971193AH1-056 GEN
Solar/Wind Harmer
5.884
315614AA2-178 GEN
Solar/Wind Harmer
0.969
316248AF1-058 C
Solar/Wind Harmer
0.259
960061AF2-297 GEN
Solar/Wind Harmer
4.301
316478AD1-087 GEN
Solar/Wind Harmer
0.707
316486AD2-202 GEN
Solar/Wind Harmer
0.207
971683AH1-343 GEN
Solar/Wind Harmer
3.301
942461AE2-259 GEN
Solar/Wind Harmer
1.109
316283AC2-100 C
Solar/Wind Harmer
0.611
970909AG2-566 GEN
Solar/Wind Harmer
0.604
315839AE2-212 C
Solar/Wind Helper
0.198
315779AE2-040
50/50
11.875
3151281ROARAP4
50/50
0.311
3151281ROARAP4
50/50
0.291
3151611KERR 4
50/50
0.269
3151621KERR 5
50/50
0.269
3151631KERR 6
50/50
0.269
3151641KERR 7
50/50
0.269
316315AB2-025 C
Solar/Wind Harmer
2.579
315814AE2-033 C
Solar/Wind Harmer
87.173
946281AF1-292 GEN
Solar/Wind Harmer
1.039
316087AB2-174 GEN
Solar/Wind Harmer
5.794
315652AC1-086 GEN
Solar/Wind Harmer
43.006
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.014
3137643SOCKMAN
Solar/Wind Harmer
-0.131
315607AA1-063A GEN
Solar/Wind Harmer
2.466
3146043SEABORD
Solar/Wind Harmer
-0.024
3146033SCOT NK
Solar/Wind Harmer
-0.084
316319Z2-044 C
Solar/Wind Harmer
1.138
970831AG2-522 GEN
Solar/Wind Harmer
10.239
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.162
961941AG1-037 GEN
Solar/Wind Harmer
0.139
3145513AHOSKIE
Solar/Wind Harmer
-0.018
3145573BETHELC
Solar/Wind Harmer
-0.018
3145573BETHELC
Solar/Wind Harmer
-0.018
316318V4-068
Solar/Wind Harmer
0.448
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
316420AA1-050 GEN
Solar/Wind Harmer
2.042
965291AG1-394 GEN
Solar/Wind Harmer
1.564
957861AF2-080 GEN
Solar/Wind Harmer
7.476
316005AA1-067
Solar/Wind Harmer
0.313
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
2.028
316239AB2-077_GEN
Solar/Wind Harmer
0.437
316238AB2-078_GEN
Solar/Wind Harmer
0.437
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
6.017
971443AH1-215 GEN
Solar/Wind Harmer
2.429
3144303KENBRDG
Solar/Wind Harmer
-0.01
315732AD1-074 GEN1
Solar/Wind Harmer
2.317
315733AD1-074 GEN2
Solar/Wind Harmer
2.317
315735AD1-075 GEN1
Solar/Wind Harmer
1.159
970683AG2-441 GEN
Solar/Wind Harmer
8.716
970681AG2-440 GEN
Solar/Wind Harmer
6.973
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
946301AF1-294 GEN
Solar/Wind Harmer
2.595
961791AG1-021 GEN
Solar/Wind Harmer
1.266
316118AC1-105 GEN
Solar/Wind Harmer
0.678
315657AE1-056 GEN
Solar/Wind Harmer
3.531
315816AE2-034 GEN
Solar/Wind Harmer
0.727
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
970865AG2-541 GEN
Solar/Wind Harmer
2.925
3143316POE
Solar/Wind Helper
0.689
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.679
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.543
MECLTFEXP_MEC->PJM
CLTF
1.307
SIGELTFEXP_SIGE->PJM
CLTF
0.039
CPLELTFEXP_CPLE->PJM
CLTF
4.437
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.06
LAGNLTFEXP_LAGN->PJM
CLTF
2.654
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.672
TVALTFEXP_TVA->PJM
CLTF
1.324
NYPJM->LTFIMP_NY
CLTF
0.497
LGEELTFEXP_LGEE->PJM
CLTF
0.473
WECLTFEXP_WEC->PJM
CLTF
0.246

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2012-54_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2012-54_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:120.98 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1004.15
MW Contribution:2.08
Bus #Bus NameTypeMW Contribution
3151361ROSEMG1
50/50
1.425
3151371ROSEMS1
50/50
0.883
3151381ROSEMG2
50/50
0.667
970535AG2-341 GEN
50/50
2.075
3144356SAPONY
Solar/Wind Harmer
3.455
3145796HORNRTN
Solar/Wind Harmer
-0.133
316181AB2-040 GEN
Solar/Wind Harmer
6.099
3145593CAROLNA
Solar/Wind Harmer
-0.035
3145593CAROLNA
Solar/Wind Harmer
-0.035
966811AG1-552 GEN
Solar/Wind Harmer
3.901
3145593CAROLNA
Solar/Wind Harmer
0.288
316426AA2-053 GEN
Solar/Wind Harmer
3.503
3145783HORNRTN
Solar/Wind Harmer
3.936
3145783HORNRTN
Solar/Wind Harmer
3.149
3145783HORNRTN
Solar/Wind Harmer
0.984
3145783HORNRTN
Solar/Wind Harmer
0.394
316274AC1-208 GEN
Solar/Wind Harmer
2.717
961601AG1-000A GEN
Solar/Wind Harmer
8.785
316263AC1-034 GEN
Solar/Wind Harmer
10.188
3145493TOT1
Solar/Wind Harmer
0.283
3145453TOT5
Solar/Wind Harmer
0.17
3145603CNETO
Solar/Wind Harmer
0.113
3145893MURPHYS
Solar/Wind Harmer
0.426
3145893MURPHYS
Solar/Wind Harmer
-0.027
939181AE1-148 GEN
Solar/Wind Harmer
7.458
313527AB2-043 GEN
Solar/Wind Harmer
2.09
3146173TUNIS
Solar/Wind Harmer
-0.012
3146173TUNIS
Solar/Wind Harmer
-0.012
3145933PARMELE
Solar/Wind Harmer
-0.02
3145933PARMELE
Solar/Wind Harmer
-0.01
970323AG2-213 GEN
Solar/Wind Harmer
4.998
971775AH1-396 GEN
Solar/Wind Harmer
0.712
316034AC1-036 C
Solar/Wind Harmer
0.185
962561AG1-105 GEN
Solar/Wind Harmer
5.188
964791AG1-342 GEN
Solar/Wind Harmer
1.83
3146843MT LREL
Solar/Wind Harmer
-0.009
3146843MT LREL
Solar/Wind Harmer
-0.009
315742AE1-103 GEN
Solar/Wind Harmer
0.808
958211AF2-115 GEN
Solar/Wind Harmer
1.175
963191AG1-168 GEN
Solar/Wind Harmer
0.705
3144293JTRSVLE
Adder
0.213
3144293JTRSVLE
Adder
0.179
3147133PAMPLIN
Solar/Wind Harmer
-0.007
3147133PAMPLIN
Solar/Wind Harmer
-0.005
3151391GASTONA
50/50
1.16
3151411GASTONB
50/50
1.16
3147043LAWRENC
50/50
3.413
3151261ROARAP2
50/50
0.384
3151601KERR 3
50/50
0.246
3151581KERR 1
50/50
0.088
316023GEN1_S
Solar/Wind Harmer
4.383
960081AF2-299 GEN
Solar/Wind Harmer
5.825
316011AB1-132 GEN
Solar/Wind Harmer
10.082
962571AG1-106 GEN
Solar/Wind Harmer
6.927
3145796HORNRTN
Solar/Wind Harmer
-0.146
3145796HORNRTN
Solar/Wind Harmer
-0.044
971795AH1-408 GEN
Solar/Wind Harmer
32.756
316190AA2-174 GEN
Solar/Wind Harmer
0.426
3145783HORNRTN
Solar/Wind Harmer
-0.033
315722AD1-056 GEN
Solar/Wind Harmer
3.382
3146233WITAKRS
Solar/Wind Harmer
-0.088
316359AB2-059 GEN
Solar/Wind Harmer
2.93
316049AB1-081 GEN
Solar/Wind Harmer
2.345
3142053HEARTS
Solar/Wind Harmer
0.255
316212AC1-099_GEN
Solar/Wind Harmer
1.881
3145543BTLEBRO
Solar/Wind Harmer
-0.021
3145543BTLEBRO
Solar/Wind Harmer
-0.017
316129AC1-054 GEN
Solar/Wind Harmer
1.823
971065AG2-659 GEN
Solar/Wind Harmer
9.774
961671AG1-007 GEN
Solar/Wind Harmer
0.231
3146083TARBORO
Solar/Wind Harmer
-0.018
3145493TOT1
Solar/Wind Harmer
0.543
3145893MURPHYS
Solar/Wind Harmer
-0.061
3145893MURPHYS
Solar/Wind Harmer
0.453
316494AC1-189 GEN
Solar/Wind Harmer
1.611
3145823KELFORD
Solar/Wind Harmer
-0.014
316237AB2-079_GEN
Solar/Wind Harmer
0.381
3146173TUNIS
Solar/Wind Harmer
-0.012
3145746EVERETS
Solar/Wind Harmer
-0.011
3145746EVERETS
Solar/Wind Harmer
-0.011
3146293MARTNCO
Solar/Wind Harmer
0.062
3145683EARLEYS
Solar/Wind Harmer
-0.01
970685AG2-442 GEN
Solar/Wind Harmer
7.634
970401AG2-262 GEN
Solar/Wind Harmer
0.559
316174AB2-169 GEN
Solar/Wind Harmer
1.262
3145963POPLR C
Solar/Wind Harmer
-0.008
963171AG1-166 GEN
Solar/Wind Harmer
0.94
971563AH1-280 GEN
Solar/Wind Harmer
0.94
3144293JTRSVLE
Adder
0.213
315779AE2-040
50/50
12.307
3151281ROARAP4
50/50
0.374
3151281ROARAP4
50/50
0.35
3151611KERR 4
50/50
0.246
3151621KERR 5
50/50
0.246
3151631KERR 6
50/50
0.246
3151641KERR 7
50/50
0.246
316315AB2-025 C
Solar/Wind Harmer
2.672
315814AE2-033 C
Solar/Wind Harmer
90.584
946281AF1-292 GEN
Solar/Wind Harmer
1.16
315652AC1-086 GEN
Solar/Wind Harmer
54.213
316087AB2-174 GEN
Solar/Wind Harmer
6.585
3145796HORNRTN
Solar/Wind Harmer
-0.141
3145796HORNRTN
Solar/Wind Harmer
-0.018
3137643SOCKMAN
Solar/Wind Harmer
-0.154
315607AA1-063A GEN
Solar/Wind Harmer
2.836
3146043SEABORD
Solar/Wind Harmer
-0.027
316319Z2-044 C
Solar/Wind Harmer
1.231
970831AG2-522 GEN
Solar/Wind Harmer
11.065
3145573BETHELC
Solar/Wind Harmer
-0.018
3145573BETHELC
Solar/Wind Harmer
-0.018
3146033SCOT NK
Solar/Wind Harmer
-0.072
965291AG1-394 GEN
Solar/Wind Harmer
1.591
316420AA1-050 GEN
Solar/Wind Harmer
1.923
316318V4-068
Solar/Wind Harmer
0.38
3145893MURPHYS
Solar/Wind Harmer
-0.041
3145893MURPHYS
Solar/Wind Harmer
-0.015
957861AF2-080 GEN
Solar/Wind Harmer
6.549
316239AB2-077_GEN
Solar/Wind Harmer
0.381
316238AB2-078_GEN
Solar/Wind Harmer
0.381
316005AA1-067
Solar/Wind Harmer
0.225
3145746EVERETS
Solar/Wind Harmer
-0.044
3145746EVERETS
Solar/Wind Harmer
-0.011
3145746EVERETS
Solar/Wind Harmer
-0.011
3145746EVERETS
Solar/Wind Harmer
-0.011
970181AG2-120 GEN
Solar/Wind Harmer
1.458
3145513AHOSKIE
Solar/Wind Harmer
0.096
961941AG1-037 GEN
Solar/Wind Harmer
0.082
3145513AHOSKIE
Solar/Wind Harmer
-0.011
971443AH1-215 GEN
Solar/Wind Harmer
1.991
3144303KENBRDG
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.01
970683AG2-441 GEN
Solar/Wind Harmer
6.816
970681AG2-440 GEN
Solar/Wind Harmer
5.453
946301AF1-294 GEN
Solar/Wind Harmer
1.927
961791AG1-021 GEN
Solar/Wind Harmer
0.94
316118AC1-105 GEN
Solar/Wind Harmer
0.482
315657AE1-056 GEN
Solar/Wind Harmer
2.506
3143316POE
Solar/Wind Helper
0.598
3151391GASTONA
50/50
1.16
3151411GASTONB
50/50
1.16
3151261ROARAP2
50/50
0.376
3151591KERR 2
50/50
0.246
316365GEN2_N
Solar/Wind Harmer
4.383
966621AG1-532 GEN
Solar/Wind Harmer
1.051
3145796HORNRTN
Solar/Wind Harmer
-0.177
3145796HORNRTN
Solar/Wind Harmer
-0.044
313506AB2-031 GEN
Solar/Wind Harmer
3.514
3147043LAWRENC
Solar/Wind Harmer
-0.024
315724AD1-057 GEN
Solar/Wind Harmer
1.86
316327AA2-057 GEN
Solar/Wind Harmer
2.324
961601AG1-000A GEN
Solar/Wind Harmer
8.896
3146233WITAKRS
Solar/Wind Harmer
0.467
3146233WITAKRS
Solar/Wind Harmer
-0.015
3138543CONSLDL
Solar/Wind Harmer
-0.015
316210AC1-098 GEN
Solar/Wind Harmer
3.387
3145543BTLEBRO
Solar/Wind Harmer
-0.021
3145543BTLEBRO
Solar/Wind Harmer
-0.021
3146073TAR RVR
Solar/Wind Harmer
-0.018
3146083TARBORO
Solar/Wind Harmer
-0.018
3156081AA2-088 GEN
Solar/Wind Harmer
5.548
3145893MURPHYS
Solar/Wind Harmer
0.107
3145893MURPHYS
Solar/Wind Harmer
-0.015
957521AF2-046 GEN
Solar/Wind Harmer
11.369
961681AG1-008 GEN
Solar/Wind Harmer
11.369
316317KELFORD C
Solar/Wind Harmer
0.653
3145823KELFORD
Solar/Wind Harmer
-0.014
316131AB2-060 GEN
Solar/Wind Harmer
1.366
3146173TUNIS
Solar/Wind Harmer
-0.012
964241AG1-285 GEN
Solar/Wind Harmer
9.257
3145746EVERETS
Solar/Wind Harmer
-0.011
3145746EVERETS
Solar/Wind Harmer
-0.011
316463AE2-346 GEN
Solar/Wind Harmer
0.177
316140AB2-099
Solar/Wind Harmer
0.074
962331AG1-082 GEN
Solar/Wind Harmer
1.37
315785AD2-033 C
Solar/Wind Harmer
2.38
3145933PARMELE
Solar/Wind Harmer
-0.01
966801AG1-551 GEN
Solar/Wind Harmer
1.252
970257AG2-171 GEN
Solar/Wind Harmer
3.748
959311AF2-222 GEN
Solar/Wind Harmer
10.056
3145963POPLR C
Solar/Wind Harmer
-0.008
963181AG1-167 GEN
Solar/Wind Harmer
0.705
3144293JTRSVLE
Adder
0.213
3156021HOLLOMANSOL
Solar/Wind Harmer
0.925
3147133PAMPLIN
Solar/Wind Harmer
-0.021
971193AH1-056 GEN
Solar/Wind Harmer
4.177
315839AE2-212 C
Solar/Wind Helper
0.172
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.624
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.141
MECLTFEXP_MEC->PJM
CLTF
1.167
SIGELTFEXP_SIGE->PJM
CLTF
0.035
CPLELTFEXP_CPLE->PJM
CLTF
4.171
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.76
LAGNLTFEXP_LAGN->PJM
CLTF
2.435
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.128
TVALTFEXP_TVA->PJM
CLTF
1.212
NYPJM->LTFIMP_NY
CLTF
0.454
LGEELTFEXP_LGEE->PJM
CLTF
0.416
WECLTFEXP_WEC->PJM
CLTF
0.217

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 1010-2012_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 1010-2012_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:120.03 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:996.24
MW Contribution:2.14
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
1.178
3151411GASTONB
50/50
1.178
3147043LAWRENC
50/50
3.465
3151261ROARAP2
50/50
0.4
3151601KERR 3
50/50
0.255
3151581KERR 1
50/50
0.091
316023GEN1_S
Solar/Wind Harmer
4.42
960081AF2-299 GEN
Solar/Wind Harmer
5.907
316011AB1-132 GEN
Solar/Wind Harmer
10.234
962571AG1-106 GEN
Solar/Wind Harmer
7.031
3145796HORNRTN
Solar/Wind Harmer
-0.148
3145796HORNRTN
Solar/Wind Harmer
-0.045
971795AH1-408 GEN
Solar/Wind Harmer
33.24
3145783HORNRTN
Solar/Wind Harmer
-0.034
315722AD1-056 GEN
Solar/Wind Harmer
3.446
316190AA2-174 GEN
Solar/Wind Harmer
0.39
3146233WITAKRS
Solar/Wind Harmer
-0.091
316212AC1-099_GEN
Solar/Wind Harmer
1.992
316359AB2-059 GEN
Solar/Wind Harmer
3.012
316049AB1-081 GEN
Solar/Wind Harmer
2.411
3142053HEARTS
Solar/Wind Harmer
0.263
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3145543BTLEBRO
Solar/Wind Harmer
-0.018
316129AC1-054 GEN
Solar/Wind Harmer
1.895
971065AG2-659 GEN
Solar/Wind Harmer
10.155
961671AG1-007 GEN
Solar/Wind Harmer
0.238
3146083TARBORO
Solar/Wind Harmer
-0.019
3145493TOT1
Solar/Wind Harmer
0.559
3146263WOODLND
Solar/Wind Harmer
-0.018
3145823KELFORD
Solar/Wind Harmer
-0.015
316494AC1-189 GEN
Solar/Wind Harmer
1.671
316237AB2-079_GEN
Solar/Wind Harmer
0.392
3145746EVERETS
Solar/Wind Harmer
-0.012
3145746EVERETS
Solar/Wind Harmer
-0.012
3145683EARLEYS
Solar/Wind Harmer
-0.011
3146293MARTNCO
Solar/Wind Harmer
0.065
970685AG2-442 GEN
Solar/Wind Harmer
7.842
3146173TUNIS
Solar/Wind Harmer
-0.009
970401AG2-262 GEN
Solar/Wind Harmer
0.575
316174AB2-169 GEN
Solar/Wind Harmer
1.339
3145963POPLR C
Solar/Wind Harmer
-0.008
963171AG1-166 GEN
Solar/Wind Harmer
0.966
971563AH1-280 GEN
Solar/Wind Harmer
0.966
3144293JTRSVLE
Adder
0.219
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.189
3146206CASHIE
Solar/Wind Harmer
-0.006
971547AH1-271 GEN
Solar/Wind Harmer
1.591
315779AE2-040
50/50
12.329
3151281ROARAP4
50/50
0.39
3151281ROARAP4
50/50
0.364
3151611KERR 4
50/50
0.255
3151621KERR 5
50/50
0.255
3151631KERR 6
50/50
0.255
3151641KERR 7
50/50
0.255
316315AB2-025 C
Solar/Wind Harmer
2.677
315814AE2-033 C
Solar/Wind Harmer
90.763
946281AF1-292 GEN
Solar/Wind Harmer
1.176
315652AC1-086 GEN
Solar/Wind Harmer
55.027
316087AB2-174 GEN
Solar/Wind Harmer
6.722
3145796HORNRTN
Solar/Wind Harmer
-0.144
3145796HORNRTN
Solar/Wind Harmer
-0.018
3137643SOCKMAN
Solar/Wind Harmer
-0.159
316319Z2-044 C
Solar/Wind Harmer
1.274
970831AG2-522 GEN
Solar/Wind Harmer
11.504
3146033SCOT NK
Solar/Wind Harmer
-0.078
3145573BETHELC
Solar/Wind Harmer
-0.019
3145573BETHELC
Solar/Wind Harmer
-0.019
316420AA1-050 GEN
Solar/Wind Harmer
1.986
957861AF2-080 GEN
Solar/Wind Harmer
6.793
316239AB2-077_GEN
Solar/Wind Harmer
0.392
316238AB2-078_GEN
Solar/Wind Harmer
0.392
316005AA1-067
Solar/Wind Harmer
0.236
3145746EVERETS
Solar/Wind Harmer
-0.046
3145746EVERETS
Solar/Wind Harmer
-0.012
3145746EVERETS
Solar/Wind Harmer
-0.012
3145746EVERETS
Solar/Wind Harmer
-0.012
970181AG2-120 GEN
Solar/Wind Harmer
1.532
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.011
3145683EARLEYS
Solar/Wind Harmer
-0.011
971443AH1-215 GEN
Solar/Wind Harmer
2.044
3145513AHOSKIE
Solar/Wind Harmer
0.09
961941AG1-037 GEN
Solar/Wind Harmer
0.077
3145513AHOSKIE
Solar/Wind Harmer
-0.01
3144303KENBRDG
Solar/Wind Harmer
-0.008
970683AG2-441 GEN
Solar/Wind Harmer
7.002
970681AG2-440 GEN
Solar/Wind Harmer
5.601
946301AF1-294 GEN
Solar/Wind Harmer
1.98
961791AG1-021 GEN
Solar/Wind Harmer
0.966
316118AC1-105 GEN
Solar/Wind Harmer
0.496
315657AE1-056 GEN
Solar/Wind Harmer
2.578
316318V4-068
Solar/Wind Harmer
0.159
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
3146206CASHIE
Solar/Wind Harmer
-0.006
970601AG2-382 GEN
Solar/Wind Harmer
2.784
3143316POE
Solar/Wind Helper
0.603
3151391GASTONA
50/50
1.178
3151411GASTONB
50/50
1.178
3151261ROARAP2
50/50
0.391
3151591KERR 2
50/50
0.255
316365GEN2_N
Solar/Wind Harmer
4.42
966621AG1-532 GEN
Solar/Wind Harmer
1.066
3145796HORNRTN
Solar/Wind Harmer
-0.18
3145796HORNRTN
Solar/Wind Harmer
-0.045
313506AB2-031 GEN
Solar/Wind Harmer
3.6
3147043LAWRENC
Solar/Wind Harmer
-0.024
315724AD1-057 GEN
Solar/Wind Harmer
1.895
316327AA2-057 GEN
Solar/Wind Harmer
2.418
3146233WITAKRS
Solar/Wind Harmer
0.483
3146233WITAKRS
Solar/Wind Harmer
-0.016
3138543CONSLDL
Solar/Wind Harmer
-0.015
961601AG1-000A GEN
Solar/Wind Harmer
9.113
316210AC1-098 GEN
Solar/Wind Harmer
3.586
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3146073TAR RVR
Solar/Wind Harmer
-0.019
3146083TARBORO
Solar/Wind Harmer
-0.019
3146263WOODLND
Solar/Wind Harmer
-0.018
316317KELFORD C
Solar/Wind Harmer
0.733
3145823KELFORD
Solar/Wind Harmer
-0.015
316131AB2-060 GEN
Solar/Wind Harmer
1.401
964241AG1-285 GEN
Solar/Wind Harmer
9.5
3145746EVERETS
Solar/Wind Harmer
-0.012
3145746EVERETS
Solar/Wind Harmer
-0.012
315785AD2-033 C
Solar/Wind Harmer
2.443
3145933PARMELE
Solar/Wind Harmer
-0.011
966801AG1-551 GEN
Solar/Wind Harmer
1.32
316463AE2-346 GEN
Solar/Wind Harmer
0.167
316140AB2-099
Solar/Wind Harmer
0.069
962331AG1-082 GEN
Solar/Wind Harmer
1.287
970257AG2-171 GEN
Solar/Wind Harmer
3.849
959311AF2-222 GEN
Solar/Wind Harmer
10.326
3146173TUNIS
Solar/Wind Harmer
-0.009
3145963POPLR C
Solar/Wind Harmer
-0.008
963181AG1-167 GEN
Solar/Wind Harmer
0.725
3144293JTRSVLE
Adder
0.219
3156021HOLLOMANSOL
Solar/Wind Harmer
1.029
3151361ROSEMG1
50/50
1.448
3151371ROSEMS1
50/50
0.897
3151381ROSEMG2
50/50
0.678
970535AG2-341 GEN
50/50
2.141
3144356SAPONY
Solar/Wind Harmer
3.461
3145796HORNRTN
Solar/Wind Harmer
-0.135
316181AB2-040 GEN
Solar/Wind Harmer
6.248
3145593CAROLNA
Solar/Wind Harmer
-0.036
3145593CAROLNA
Solar/Wind Harmer
-0.036
966811AG1-552 GEN
Solar/Wind Harmer
4.064
3145593CAROLNA
Solar/Wind Harmer
0.3
3145783HORNRTN
Solar/Wind Harmer
4.102
3145783HORNRTN
Solar/Wind Harmer
3.282
3145783HORNRTN
Solar/Wind Harmer
1.026
3145783HORNRTN
Solar/Wind Harmer
0.41
316426AA2-053 GEN
Solar/Wind Harmer
3.205
316274AC1-208 GEN
Solar/Wind Harmer
2.844
961601AG1-000A GEN
Solar/Wind Harmer
8.999
316263AC1-034 GEN
Solar/Wind Harmer
10.474
3145493TOT1
Solar/Wind Harmer
0.291
3145453TOT5
Solar/Wind Harmer
0.175
3145603CNETO
Solar/Wind Harmer
0.117
939181AE1-148 GEN
Solar/Wind Harmer
7.715
313527AB2-043 GEN
Solar/Wind Harmer
2.144
3145933PARMELE
Solar/Wind Harmer
-0.021
3145933PARMELE
Solar/Wind Harmer
-0.011
970323AG2-213 GEN
Solar/Wind Harmer
5.132
971775AH1-396 GEN
Solar/Wind Harmer
0.731
316034AC1-036 C
Solar/Wind Harmer
0.19
962561AG1-105 GEN
Solar/Wind Harmer
5.333
3146173TUNIS
Solar/Wind Harmer
-0.009
3146173TUNIS
Solar/Wind Harmer
-0.009
964791AG1-342 GEN
Solar/Wind Harmer
1.883
3146843MT LREL
Solar/Wind Harmer
-0.009
3146843MT LREL
Solar/Wind Harmer
-0.009
958211AF2-115 GEN
Solar/Wind Harmer
1.208
963191AG1-168 GEN
Solar/Wind Harmer
0.725
3144293JTRSVLE
Adder
0.219
3144293JTRSVLE
Adder
0.184
3147133PAMPLIN
Solar/Wind Harmer
-0.007
3147133PAMPLIN
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.178
3145893MURPHYS
Solar/Wind Harmer
-0.011
316240AF1-291 C
Solar/Wind Helper
0.15
957521AF2-046 GEN
Solar/Wind Harmer
5.624
961681AG1-008 GEN
Solar/Wind Harmer
5.624
3147133PAMPLIN
Solar/Wind Harmer
-0.021
971193AH1-056 GEN
Solar/Wind Harmer
4.296
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
3146206CASHIE
Solar/Wind Harmer
-0.006
315839AE2-212 C
Solar/Wind Helper
0.174
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.067
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.322
MECLTFEXP_MEC->PJM
CLTF
1.227
SIGELTFEXP_SIGE->PJM
CLTF
0.037
CPLELTFEXP_CPLE->PJM
CLTF
4.317
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.345
LAGNLTFEXP_LAGN->PJM
CLTF
2.539
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.423
TVALTFEXP_TVA->PJM
CLTF
1.264
NYPJM->LTFIMP_NY
CLTF
0.459
LGEELTFEXP_LGEE->PJM
CLTF
0.439
WECLTFEXP_WEC->PJM
CLTF
0.229

Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6SAPONY-6CARSON 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.79 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:799.44
MW Contribution:1.74
Bus #Bus NameTypeMW Contribution
3151361ROSEMG1
50/50
1.137
3151371ROSEMS1
50/50
0.704
3151381ROSEMG2
50/50
0.532
970535AG2-341 GEN
50/50
1.742
3144356SAPONY
Solar/Wind Harmer
7.169
316181AB2-040 GEN
Solar/Wind Harmer
0.483
3145796HORNRTN
Solar/Wind Harmer
0.946
3142666NORTHAMPTON
Solar/Wind Harmer
0.313
3142666NORTHAMPTON
Solar/Wind Harmer
0.313
3142666NORTHAMPTON
Solar/Wind Harmer
0.313
3142666NORTHAMPTON
Solar/Wind Harmer
0.188
3145593CAROLNA
Solar/Wind Harmer
0.25
3145593CAROLNA
Solar/Wind Harmer
0.25
966811AG1-552 GEN
Solar/Wind Harmer
2.709
3145593CAROLNA
Solar/Wind Harmer
0.311
3145783HORNRTN
Solar/Wind Harmer
4.31
3145783HORNRTN
Solar/Wind Harmer
3.448
3145783HORNRTN
Solar/Wind Harmer
1.078
3145783HORNRTN
Solar/Wind Harmer
0.431
316426AA2-053 GEN
Solar/Wind Harmer
0.793
316274AC1-208 GEN
Solar/Wind Harmer
1.058
961601AG1-000A GEN
Solar/Wind Harmer
3.147
316263AC1-034 GEN
Solar/Wind Harmer
6.579
3146173TUNIS
Solar/Wind Harmer
0.163
3151391GASTONA
50/50
0.917
3151411GASTONB
50/50
0.917
3151261ROARAP2
50/50
0.304
3151591KERR 2
50/50
0.203
316365GEN2_N
Solar/Wind Harmer
1.156
313506AB2-031 GEN
Solar/Wind Harmer
1.029
3145796HORNRTN
Solar/Wind Harmer
1.261
3145796HORNRTN
Solar/Wind Harmer
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
0.313
3147043LAWRENC
Solar/Wind Harmer
0.188
315724AD1-057 GEN
Solar/Wind Harmer
0.898
316210AC1-098 GEN
Solar/Wind Harmer
1.789
3146263WOODLND
Solar/Wind Harmer
0.189
316327AA2-057 GEN
Solar/Wind Harmer
0.283
3146233WITAKRS
Solar/Wind Harmer
0.903
3146233WITAKRS
Solar/Wind Harmer
0.122
3138543CONSLDL
Solar/Wind Harmer
0.118
961601AG1-000A GEN
Solar/Wind Harmer
12.587
3151391GASTONA
50/50
0.917
3151411GASTONB
50/50
0.917
3147043LAWRENC
50/50
3.004
3151261ROARAP2
50/50
0.311
3151601KERR 3
50/50
0.203
3151581KERR 1
50/50
0.073
316023GEN1_S
Solar/Wind Harmer
1.156
960081AF2-299 GEN
Solar/Wind Harmer
3.908
971795AH1-408 GEN
Solar/Wind Harmer
22.84
316011AB1-132 GEN
Solar/Wind Harmer
6.16
962571AG1-106 GEN
Solar/Wind Harmer
4.821
3145796HORNRTN
Solar/Wind Harmer
1.041
3145796HORNRTN
Solar/Wind Harmer
0.315
3145783HORNRTN
Solar/Wind Harmer
0.242
315722AD1-056 GEN
Solar/Wind Harmer
1.515
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
0.997
3146263WOODLND
Solar/Wind Harmer
0.189
3146233WITAKRS
Solar/Wind Harmer
0.716
3145823KELFORD
Solar/Wind Harmer
0.176
316359AB2-059 GEN
Solar/Wind Harmer
0.622
316049AB1-081 GEN
Solar/Wind Harmer
0.991
3142053HEARTS
Solar/Wind Harmer
0.305
3145543BTLEBRO
Solar/Wind Harmer
0.172
3145543BTLEBRO
Solar/Wind Harmer
0.138
3145683EARLEYS
Solar/Wind Harmer
0.166
3146173TUNIS
Solar/Wind Harmer
0.163
315779AE2-040
50/50
11.964
3151281ROARAP4
50/50
0.303
3151281ROARAP4
50/50
0.283
3151151S HAMPT1
50/50
0.289
3151611KERR 4
50/50
0.203
3151621KERR 5
50/50
0.203
3151631KERR 6
50/50
0.203
3151641KERR 7
50/50
0.203
316315AB2-025 C
Solar/Wind Harmer
0.693
315814AE2-033 C
Solar/Wind Harmer
66.388
316087AB2-174 GEN
Solar/Wind Harmer
0.01
315652AC1-086 GEN
Solar/Wind Harmer
37.271
3145796HORNRTN
Solar/Wind Harmer
1.009
3145796HORNRTN
Solar/Wind Harmer
0.126
3137643SOCKMAN
Solar/Wind Harmer
1.149
315607AA1-063A GEN
Solar/Wind Harmer
0.435
3146043SEABORD
Solar/Wind Harmer
0.207
3146033SCOT NK
Solar/Wind Harmer
0.74
316319Z2-044 C
Solar/Wind Harmer
0
3145683EARLEYS
Solar/Wind Harmer
0.333
3145683EARLEYS
Solar/Wind Harmer
0.166
3145683EARLEYS
Solar/Wind Harmer
0.166
3145513AHOSKIE
Solar/Wind Harmer
0.344
3145513AHOSKIE
Solar/Wind Harmer
0.165
3145573BETHELC
Solar/Wind Harmer
0.162
3145573BETHELC
Solar/Wind Harmer
0.162
970831AG2-522 GEN
Solar/Wind Harmer
6.856
3145893MURPHYS
Solar/Wind Harmer
0.43
3145893MURPHYS
Solar/Wind Harmer
0.159
316420AA1-050 GEN
Solar/Wind Harmer
0.005
965291AG1-394 GEN
Solar/Wind Harmer
0.693
957861AF2-080 GEN
Solar/Wind Harmer
6.497
316005AA1-067
Solar/Wind Harmer
0.147
3145746EVERETS
Solar/Wind Harmer
0.545
3145746EVERETS
Solar/Wind Harmer
0.137
3145746EVERETS
Solar/Wind Harmer
0.137
3145746EVERETS
Solar/Wind Harmer
0.137
970181AG2-120 GEN
Solar/Wind Harmer
1.704
3146206CASHIE
Solar/Wind Harmer
0.125
970601AG2-382 GEN
Solar/Wind Harmer
4.659
315732AD1-074 GEN1
Solar/Wind Harmer
0.604
315733AD1-074 GEN2
Solar/Wind Harmer
0.604
315735AD1-075 GEN1
Solar/Wind Harmer
0.302
3130546PLYMOUTH
Solar/Wind Harmer
0.102
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
315816AE2-034 GEN
Solar/Wind Harmer
0.361
971443AH1-215 GEN
Solar/Wind Harmer
1.281
3144303KENBRDG
Solar/Wind Harmer
0.06
970683AG2-441 GEN
Solar/Wind Harmer
4.369
970681AG2-440 GEN
Solar/Wind Harmer
3.495
3130156CHOWAN
Solar/Wind Harmer
0.061
3130156CHOWAN
Solar/Wind Harmer
0.061
3143316POE
Solar/Wind Helper
0.623
3146173TUNIS
Solar/Wind Harmer
0.163
3145493TOT1
Solar/Wind Harmer
0.377
3145453TOT5
Solar/Wind Harmer
0.226
3145603CNETO
Solar/Wind Harmer
0.151
3145893MURPHYS
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
0.286
3145933PARMELE
Solar/Wind Harmer
0.262
3145933PARMELE
Solar/Wind Harmer
0.131
316065AD1-022 GEN
Solar/Wind Harmer
5.413
939181AE1-148 GEN
Solar/Wind Harmer
4.714
313527AB2-043 GEN
Solar/Wind Harmer
0.001
315742AE1-103 GEN
Solar/Wind Harmer
0.001
970323AG2-213 GEN
Solar/Wind Harmer
3.216
971775AH1-396 GEN
Solar/Wind Harmer
0.121
316034AC1-036 C
Solar/Wind Harmer
0.005
962561AG1-105 GEN
Solar/Wind Harmer
3.357
964791AG1-342 GEN
Solar/Wind Harmer
1.247
3146843MT LREL
Solar/Wind Harmer
0.065
3146843MT LREL
Solar/Wind Harmer
0.065
3146376EDENTON
Solar/Wind Harmer
0.271
3146376EDENTON
Solar/Wind Harmer
0.271
316240AF1-291 C
Solar/Wind Helper
0.15
961671AG1-007 GEN
Solar/Wind Harmer
0.025
3146083TARBORO
Solar/Wind Harmer
0.162
3145493TOT1
Solar/Wind Harmer
0.722
3145893MURPHYS
Solar/Wind Harmer
0.637
3145893MURPHYS
Solar/Wind Harmer
0.708
316129AC1-054 GEN
Solar/Wind Harmer
0.569
316494AC1-189 GEN
Solar/Wind Harmer
0.509
971065AG2-659 GEN
Solar/Wind Harmer
6.074
3145746EVERETS
Solar/Wind Harmer
0.137
3145746EVERETS
Solar/Wind Harmer
0.137
3146293MARTNCO
Solar/Wind Harmer
0.122
3146206CASHIE
Solar/Wind Harmer
0.125
971547AH1-271 GEN
Solar/Wind Harmer
2.662
316174AB2-169 GEN
Solar/Wind Harmer
0.003
3145963POPLR C
Solar/Wind Harmer
0.119
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3145663CRESWEL
Solar/Wind Harmer
0.235
971163AH1-040 GEN
Solar/Wind Harmer
6.722
970685AG2-442 GEN
Solar/Wind Harmer
4.893
970401AG2-262 GEN
Solar/Wind Harmer
0.381
3130156CHOWAN
Solar/Wind Harmer
0.061
316317KELFORD C
Solar/Wind Harmer
0.017
3145823KELFORD
Solar/Wind Harmer
0.176
971623AH1-311 GEN
Solar/Wind Harmer
0.346
3145543BTLEBRO
Solar/Wind Harmer
0.172
3145543BTLEBRO
Solar/Wind Harmer
0.172
316463AE2-346 GEN
Solar/Wind Harmer
0.141
316140AB2-099
Solar/Wind Harmer
0.059
962331AG1-082 GEN
Solar/Wind Harmer
1.757
3146173TUNIS
Solar/Wind Harmer
0.163
3146073TAR RVR
Solar/Wind Harmer
0.162
3146083TARBORO
Solar/Wind Harmer
0.162
957521AF2-046 GEN
Solar/Wind Harmer
11.93
961681AG1-008 GEN
Solar/Wind Harmer
11.93
3145893MURPHYS
Solar/Wind Harmer
0.267
3145893MURPHYS
Solar/Wind Harmer
0.159
3156021HOLLOMANSOL
Solar/Wind Harmer
0.695
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
3145746EVERETS
Solar/Wind Harmer
0.137
3145746EVERETS
Solar/Wind Harmer
0.137
3145933PARMELE
Solar/Wind Harmer
0.131
966801AG1-551 GEN
Solar/Wind Harmer
1.528
3146206CASHIE
Solar/Wind Harmer
0.125
3145963POPLR C
Solar/Wind Harmer
0.119
315737AD1-076 GEN
Solar/Wind Harmer
1.351
971157AH1-035 GEN
Solar/Wind Harmer
1.22
316131AB2-060 GEN
Solar/Wind Harmer
0.302
964241AG1-285 GEN
Solar/Wind Harmer
5.983
315614AA2-178 GEN
Solar/Wind Harmer
0.481
315785AD2-033 C
Solar/Wind Harmer
0.645
970257AG2-171 GEN
Solar/Wind Harmer
2.412
959311AF2-222 GEN
Solar/Wind Harmer
6.452
3146376EDENTON
Solar/Wind Harmer
0.061
315839AE2-212 C
Solar/Wind Helper
0.177
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.03
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.87
MECLTFEXP_MEC->PJM
CLTF
1.083
SIGELTFEXP_SIGE->PJM
CLTF
0.032
CPLELTFEXP_CPLE->PJM
CLTF
4.008
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.91
LAGNLTFEXP_LAGN->PJM
CLTF
2.281
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.706
TVALTFEXP_TVA->PJM
CLTF
1.134
NYPJM->LTFIMP_NY
CLTF
0.43
LGEELTFEXP_LGEE->PJM
CLTF
0.384
WECLTFEXP_WEC->PJM
CLTF
0.2

Details for 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.88 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1203.12
MW Contribution:5.16
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
10.817
3144293JTRSVLE
50/50
1.01
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3147043LAWRENC
50/50
1.438
3151561HALLBR1
50/50
0.348
3151931BEARGRDN S1
50/50
1.386
3151911BEARGRDN G1
50/50
1.074
315687AD1-152 GEN
Solar/Wind Harmer
7.758
316003AC1-222 GEN
Solar/Wind Harmer
5.37
957481AF2-042 GEN
Solar/Wind Harmer
169.864
315693AD1-088 GEN
Solar/Wind Harmer
25.266
962491AG1-098 GEN
Solar/Wind Harmer
33.395
970401AG2-262 GEN
Solar/Wind Harmer
3.255
316237AB2-079_GEN
Solar/Wind Harmer
1.109
970685AG2-442 GEN
Solar/Wind Harmer
29.964
963171AG1-166 GEN
Solar/Wind Harmer
4.201
971563AH1-280 GEN
Solar/Wind Harmer
4.201
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.371
316322AB2-045
Solar/Wind Harmer
0.76
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.88
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.352
971795AH1-408 GEN
Solar/Wind Harmer
10.596
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.538
971377AH1-170 GEN
Solar/Wind Harmer
1.457
3147623JAMES R
Solar/Wind Harmer
0.18
970937AG2-583 GEN
Solar/Wind Harmer
7.58
960081AF2-299 GEN
Solar/Wind Harmer
0.929
316336AC2-165 C
Solar/Wind Harmer
1.333
3143336POWHATN
Solar/Wind Harmer
0.777
3152661PLYWOOD A
50/50
1.087
3144293JTRSVLE
50/50
1.01
3144293JTRSVLE
50/50
0.851
970535AG2-341 GEN
50/50
5.156
970099AG2-077 GEN
Solar/Wind Harmer
67.945
970933AG2-581 GEN
Solar/Wind Harmer
50.247
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.651
962561AG1-105 GEN
Solar/Wind Harmer
26.897
971741AH1-377 GEN
Solar/Wind Harmer
48.415
970301AG2-198 GEN
Solar/Wind Harmer
19.501
313527AB2-043 GEN
Solar/Wind Harmer
5.92
970323AG2-213 GEN
Solar/Wind Harmer
17.464
971775AH1-396 GEN
Solar/Wind Harmer
2.487
316034AC1-036 C
Solar/Wind Harmer
0.648
958211AF2-115 GEN
Solar/Wind Harmer
5.252
963191AG1-168 GEN
Solar/Wind Harmer
3.151
942751AE2-291 GEN
Solar/Wind Harmer
21.312
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.148
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.964
316197AC1-042 GEN
Solar/Wind Harmer
1.489
942671AE2-283 GEN
Solar/Wind Harmer
4.009
971489AH1-241 GEN
Solar/Wind Harmer
6.918
315821AE2-092 GEN
Solar/Wind Harmer
1.803
316181AB2-040 GEN
Solar/Wind Harmer
1.071
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.79
3145593CAROLNA
Solar/Wind Harmer
0.058
316222AC1-221 GEN
Solar/Wind Helper
2.556
3151541CLOVER2
50/50
10.765
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
972205AH1-687 GEN
50/50
5.237
3147173SINAI
Solar/Wind Harmer
-0.059
970413AG2-270 GEN
50/50
47.203
3144293JTRSVLE
50/50
1.01
3151591KERR 2
50/50
0.537
3151921BEARGRDN G2
50/50
1.074
316248AF1-058 C
Solar/Wind Harmer
1.794
960061AF2-297 GEN
Solar/Wind Harmer
29.766
316478AD1-087 GEN
Solar/Wind Harmer
4.933
316486AD2-202 GEN
Solar/Wind Harmer
1.445
971683AH1-343 GEN
Solar/Wind Harmer
22.023
970909AG2-566 GEN
Solar/Wind Harmer
3.703
316131AB2-060 GEN
Solar/Wind Harmer
3.921
964241AG1-285 GEN
Solar/Wind Harmer
28.048
315785AD2-033 C
Solar/Wind Harmer
7.977
970257AG2-171 GEN
Solar/Wind Harmer
13.098
959311AF2-222 GEN
Solar/Wind Harmer
36.247
963181AG1-167 GEN
Solar/Wind Harmer
3.151
3147133PAMPLIN
Solar/Wind Harmer
-0.104
971193AH1-056 GEN
Solar/Wind Harmer
20.727
942461AE2-259 GEN
Solar/Wind Harmer
4.793
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.538
970221AG2-151 GEN
Solar/Wind Harmer
7.287
966621AG1-532 GEN
Solar/Wind Harmer
0.168
313506AB2-031 GEN
Solar/Wind Harmer
0.617
316313AB2-026
Solar/Wind Harmer
0.177
316258AE1-075 C
Solar/Wind Harmer
0.159
316405AF2-144 C
Solar/Wind Harmer
0.168
3143336POWHATN
Solar/Wind Harmer
0.661
316283AC2-100 C
Solar/Wind Helper
2.321
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.767
971967AH1-528 GEN
Solar/Wind Harmer
100.764
970865AG2-541 GEN
Solar/Wind Harmer
19.09
316123AC1-075 GEN
Solar/Wind Harmer
4.175
970165AG2-112 GEN
Solar/Wind Harmer
3.676
970163AG2-111 GEN
Solar/Wind Harmer
3.506
316239AB2-077_GEN
Solar/Wind Harmer
1.109
316238AB2-078_GEN
Solar/Wind Harmer
1.109
971443AH1-215 GEN
Solar/Wind Harmer
6.887
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.754
970681AG2-440 GEN
Solar/Wind Harmer
21.403
946301AF1-294 GEN
Solar/Wind Harmer
8.613
961791AG1-021 GEN
Solar/Wind Harmer
4.201
315657AE1-056 GEN
Solar/Wind Harmer
12.436
970285AG2-188 GEN
Solar/Wind Harmer
21.464
971845AH1-439 GEN
Solar/Wind Harmer
12.355
970831AG2-522 GEN
Solar/Wind Harmer
10.03
971447AH1-217 GEN
Solar/Wind Harmer
3.932
270494AE1-108_GEN
Solar/Wind Harmer
2.515
946281AF1-292 GEN
Solar/Wind Harmer
0.185
316087AB2-174 GEN
Solar/Wind Harmer
1.12
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.372
270457AD2-023 GEN
Solar/Wind Helper
0.904
VTFLTFEXP_VFT->PJM
CMTX
1.304
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.8
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.891
G-007ALTFEXP_G-007A->PJM
CMTX
0.495
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.478
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.834
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.63
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.359

Details for 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.72 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1179.24
MW Contribution:5.14
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
10.796
3144293JTRSVLE
50/50
1.009
3151601KERR 3
50/50
0.536
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.437
3151561HALLBR1
50/50
0.346
3151931BEARGRDN S1
50/50
1.389
3151911BEARGRDN G1
50/50
1.077
315687AD1-152 GEN
Solar/Wind Harmer
7.743
316003AC1-222 GEN
Solar/Wind Harmer
5.358
957481AF2-042 GEN
Solar/Wind Harmer
169.548
315693AD1-088 GEN
Solar/Wind Harmer
25.22
962491AG1-098 GEN
Solar/Wind Harmer
33.335
970401AG2-262 GEN
Solar/Wind Harmer
3.248
316237AB2-079_GEN
Solar/Wind Harmer
1.106
970685AG2-442 GEN
Solar/Wind Harmer
29.914
963171AG1-166 GEN
Solar/Wind Harmer
4.195
971563AH1-280 GEN
Solar/Wind Harmer
4.195
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.337
316322AB2-045
Solar/Wind Harmer
0.76
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.875
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.366
971795AH1-408 GEN
Solar/Wind Harmer
10.594
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.511
971377AH1-170 GEN
Solar/Wind Harmer
1.461
3147623JAMES R
Solar/Wind Harmer
0.181
970937AG2-583 GEN
Solar/Wind Harmer
7.619
960081AF2-299 GEN
Solar/Wind Harmer
0.931
316336AC2-165 C
Solar/Wind Harmer
1.347
3143336POWHATN
Solar/Wind Harmer
0.788
3152661PLYWOOD A
50/50
1.084
3144293JTRSVLE
50/50
1.009
3144293JTRSVLE
50/50
0.85
970535AG2-341 GEN
50/50
5.143
970099AG2-077 GEN
Solar/Wind Harmer
67.819
970933AG2-581 GEN
Solar/Wind Harmer
50.154
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.629
962561AG1-105 GEN
Solar/Wind Harmer
26.841
971741AH1-377 GEN
Solar/Wind Harmer
48.342
970301AG2-198 GEN
Solar/Wind Harmer
19.474
313527AB2-043 GEN
Solar/Wind Harmer
5.908
970323AG2-213 GEN
Solar/Wind Harmer
17.432
971775AH1-396 GEN
Solar/Wind Harmer
2.482
316034AC1-036 C
Solar/Wind Harmer
0.646
958211AF2-115 GEN
Solar/Wind Harmer
5.244
963191AG1-168 GEN
Solar/Wind Harmer
3.146
942751AE2-291 GEN
Solar/Wind Harmer
21.251
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.099
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.952
316197AC1-042 GEN
Solar/Wind Harmer
1.48
942671AE2-283 GEN
Solar/Wind Harmer
3.984
971489AH1-241 GEN
Solar/Wind Harmer
6.936
315821AE2-092 GEN
Solar/Wind Harmer
1.81
316181AB2-040 GEN
Solar/Wind Harmer
1.071
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.789
3145593CAROLNA
Solar/Wind Harmer
0.058
316222AC1-221 GEN
Solar/Wind Helper
2.576
970413AG2-270 GEN
50/50
47.114
3144293JTRSVLE
50/50
1.009
3151591KERR 2
50/50
0.536
3151921BEARGRDN G2
50/50
1.077
316248AF1-058 C
Solar/Wind Harmer
1.79
960061AF2-297 GEN
Solar/Wind Harmer
29.705
316478AD1-087 GEN
Solar/Wind Harmer
4.923
316486AD2-202 GEN
Solar/Wind Harmer
1.442
971683AH1-343 GEN
Solar/Wind Harmer
21.974
970909AG2-566 GEN
Solar/Wind Harmer
3.698
316131AB2-060 GEN
Solar/Wind Harmer
3.913
964241AG1-285 GEN
Solar/Wind Harmer
27.993
315785AD2-033 C
Solar/Wind Harmer
7.962
970257AG2-171 GEN
Solar/Wind Harmer
13.074
959311AF2-222 GEN
Solar/Wind Harmer
36.183
963181AG1-167 GEN
Solar/Wind Harmer
3.146
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.696
942461AE2-259 GEN
Solar/Wind Harmer
4.788
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.511
970221AG2-151 GEN
Solar/Wind Harmer
7.306
966621AG1-532 GEN
Solar/Wind Harmer
0.168
313506AB2-031 GEN
Solar/Wind Harmer
0.617
316313AB2-026
Solar/Wind Harmer
0.179
316258AE1-075 C
Solar/Wind Harmer
0.161
316405AF2-144 C
Solar/Wind Harmer
0.17
3143336POWHATN
Solar/Wind Harmer
0.67
316283AC2-100 C
Solar/Wind Helper
2.34
270018AE2-047 C O1
Solar/Wind Helper
0.398
3151541CLOVER2
50/50
10.745
3151611KERR 4
50/50
0.536
3151621KERR 5
50/50
0.536
3151631KERR 6
50/50
0.536
3151641KERR 7
50/50
0.536
972205AH1-687 GEN
50/50
5.251
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.759
971967AH1-528 GEN
Solar/Wind Harmer
100.577
970865AG2-541 GEN
Solar/Wind Harmer
19.046
316123AC1-075 GEN
Solar/Wind Harmer
4.164
970165AG2-112 GEN
Solar/Wind Harmer
3.666
970163AG2-111 GEN
Solar/Wind Harmer
3.497
316239AB2-077_GEN
Solar/Wind Harmer
1.106
316238AB2-078_GEN
Solar/Wind Harmer
1.106
971443AH1-215 GEN
Solar/Wind Harmer
6.874
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.709
970681AG2-440 GEN
Solar/Wind Harmer
21.367
946301AF1-294 GEN
Solar/Wind Harmer
8.599
961791AG1-021 GEN
Solar/Wind Harmer
4.195
315657AE1-056 GEN
Solar/Wind Harmer
12.418
970285AG2-188 GEN
Solar/Wind Harmer
21.458
971845AH1-439 GEN
Solar/Wind Harmer
12.354
970831AG2-522 GEN
Solar/Wind Harmer
10.001
971447AH1-217 GEN
Solar/Wind Harmer
3.943
270494AE1-108_GEN
Solar/Wind Harmer
2.518
946281AF1-292 GEN
Solar/Wind Harmer
0.185
316087AB2-174 GEN
Solar/Wind Harmer
1.121
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.392
270457AD2-023 GEN
Solar/Wind Helper
0.917
VTFLTFEXP_VFT->PJM
CMTX
1.552
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.847
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.009
G-007ALTFEXP_G-007A->PJM
CMTX
0.588
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.64
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.854
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.69
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.461

Details for 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.7 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1179.05
MW Contribution:5.14
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
10.796
3144293JTRSVLE
50/50
1.009
3151601KERR 3
50/50
0.536
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.437
3151561HALLBR1
50/50
0.346
3151931BEARGRDN S1
50/50
1.389
3151911BEARGRDN G1
50/50
1.077
315687AD1-152 GEN
Solar/Wind Harmer
7.743
316003AC1-222 GEN
Solar/Wind Harmer
5.358
957481AF2-042 GEN
Solar/Wind Harmer
169.548
315693AD1-088 GEN
Solar/Wind Harmer
25.22
962491AG1-098 GEN
Solar/Wind Harmer
33.335
970401AG2-262 GEN
Solar/Wind Harmer
3.248
316237AB2-079_GEN
Solar/Wind Harmer
1.106
970685AG2-442 GEN
Solar/Wind Harmer
29.914
963171AG1-166 GEN
Solar/Wind Harmer
4.195
971563AH1-280 GEN
Solar/Wind Harmer
4.195
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.337
316322AB2-045
Solar/Wind Harmer
0.76
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.875
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.366
971795AH1-408 GEN
Solar/Wind Harmer
10.594
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.511
971377AH1-170 GEN
Solar/Wind Harmer
1.461
3147623JAMES R
Solar/Wind Harmer
0.181
970937AG2-583 GEN
Solar/Wind Harmer
7.619
960081AF2-299 GEN
Solar/Wind Harmer
0.931
316336AC2-165 C
Solar/Wind Harmer
1.347
3143336POWHATN
Solar/Wind Harmer
0.788
3152661PLYWOOD A
50/50
1.084
3144293JTRSVLE
50/50
1.009
3144293JTRSVLE
50/50
0.85
970535AG2-341 GEN
50/50
5.143
970099AG2-077 GEN
Solar/Wind Harmer
67.819
970933AG2-581 GEN
Solar/Wind Harmer
50.154
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.629
962561AG1-105 GEN
Solar/Wind Harmer
26.841
971741AH1-377 GEN
Solar/Wind Harmer
48.342
970301AG2-198 GEN
Solar/Wind Harmer
19.474
313527AB2-043 GEN
Solar/Wind Harmer
5.908
970323AG2-213 GEN
Solar/Wind Harmer
17.432
971775AH1-396 GEN
Solar/Wind Harmer
2.482
316034AC1-036 C
Solar/Wind Harmer
0.646
958211AF2-115 GEN
Solar/Wind Harmer
5.244
963191AG1-168 GEN
Solar/Wind Harmer
3.146
942751AE2-291 GEN
Solar/Wind Harmer
21.251
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.099
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.952
970413AG2-270 GEN
50/50
47.114
3144293JTRSVLE
50/50
1.009
3151591KERR 2
50/50
0.536
3151921BEARGRDN G2
50/50
1.077
316248AF1-058 C
Solar/Wind Harmer
1.79
960061AF2-297 GEN
Solar/Wind Harmer
29.705
316478AD1-087 GEN
Solar/Wind Harmer
4.923
316486AD2-202 GEN
Solar/Wind Harmer
1.442
971683AH1-343 GEN
Solar/Wind Harmer
21.974
970909AG2-566 GEN
Solar/Wind Harmer
3.698
316131AB2-060 GEN
Solar/Wind Harmer
3.913
964241AG1-285 GEN
Solar/Wind Harmer
27.993
315785AD2-033 C
Solar/Wind Harmer
7.962
970257AG2-171 GEN
Solar/Wind Harmer
13.074
959311AF2-222 GEN
Solar/Wind Harmer
36.183
963181AG1-167 GEN
Solar/Wind Harmer
3.146
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.696
942461AE2-259 GEN
Solar/Wind Harmer
4.788
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.511
970221AG2-151 GEN
Solar/Wind Harmer
7.306
966621AG1-532 GEN
Solar/Wind Harmer
0.168
313506AB2-031 GEN
Solar/Wind Harmer
0.617
316313AB2-026
Solar/Wind Harmer
0.179
316258AE1-075 C
Solar/Wind Harmer
0.161
316405AF2-144 C
Solar/Wind Harmer
0.17
3143336POWHATN
Solar/Wind Harmer
0.67
316283AC2-100 C
Solar/Wind Helper
2.34
270018AE2-047 C O1
Solar/Wind Helper
0.398
3151541CLOVER2
50/50
10.745
3151611KERR 4
50/50
0.536
3151621KERR 5
50/50
0.536
3151631KERR 6
50/50
0.536
3151641KERR 7
50/50
0.536
972205AH1-687 GEN
50/50
5.251
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.759
971967AH1-528 GEN
Solar/Wind Harmer
100.577
970865AG2-541 GEN
Solar/Wind Harmer
19.046
316123AC1-075 GEN
Solar/Wind Harmer
4.164
970165AG2-112 GEN
Solar/Wind Harmer
3.666
970163AG2-111 GEN
Solar/Wind Harmer
3.497
316239AB2-077_GEN
Solar/Wind Harmer
1.106
316238AB2-078_GEN
Solar/Wind Harmer
1.106
971443AH1-215 GEN
Solar/Wind Harmer
6.874
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.709
970681AG2-440 GEN
Solar/Wind Harmer
21.367
946301AF1-294 GEN
Solar/Wind Harmer
8.599
961791AG1-021 GEN
Solar/Wind Harmer
4.195
315657AE1-056 GEN
Solar/Wind Harmer
12.418
970285AG2-188 GEN
Solar/Wind Harmer
21.458
971845AH1-439 GEN
Solar/Wind Harmer
12.354
970831AG2-522 GEN
Solar/Wind Harmer
10.001
971447AH1-217 GEN
Solar/Wind Harmer
3.943
270494AE1-108_GEN
Solar/Wind Harmer
2.518
946281AF1-292 GEN
Solar/Wind Harmer
0.185
316087AB2-174 GEN
Solar/Wind Harmer
1.121
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.392
270457AD2-023 GEN
Solar/Wind Helper
0.917
316197AC1-042 GEN
Solar/Wind Harmer
1.48
942671AE2-283 GEN
Solar/Wind Harmer
3.984
971489AH1-241 GEN
Solar/Wind Harmer
6.936
315821AE2-092 GEN
Solar/Wind Harmer
1.81
316181AB2-040 GEN
Solar/Wind Harmer
1.071
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.789
3145593CAROLNA
Solar/Wind Harmer
0.058
316222AC1-221 GEN
Solar/Wind Helper
2.576
VTFLTFEXP_VFT->PJM
CMTX
1.552
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.847
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.009
G-007ALTFEXP_G-007A->PJM
CMTX
0.588
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.64
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.854
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.69
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.461

Details for 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.45 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1154.15
MW Contribution:5.14
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
47.647
3144293JTRSVLE
50/50
1.004
3151591KERR 2
50/50
0.536
3151921BEARGRDN G2
50/50
1.06
316248AF1-058 C
Solar/Wind Harmer
1.8
960061AF2-297 GEN
Solar/Wind Harmer
29.874
316478AD1-087 GEN
Solar/Wind Harmer
4.979
316486AD2-202 GEN
Solar/Wind Harmer
1.458
971683AH1-343 GEN
Solar/Wind Harmer
22.104
970909AG2-566 GEN
Solar/Wind Harmer
3.651
316131AB2-060 GEN
Solar/Wind Harmer
3.913
964241AG1-285 GEN
Solar/Wind Harmer
27.972
315785AD2-033 C
Solar/Wind Harmer
7.946
970257AG2-171 GEN
Solar/Wind Harmer
13.041
959311AF2-222 GEN
Solar/Wind Harmer
36.078
963181AG1-167 GEN
Solar/Wind Harmer
3.13
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.572
942461AE2-259 GEN
Solar/Wind Harmer
4.746
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
3151531CLOVER1
50/50
10.918
3144293JTRSVLE
50/50
1.004
3151601KERR 3
50/50
0.536
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.435
3151561HALLBR1
50/50
0.35
3151931BEARGRDN S1
50/50
1.368
3151911BEARGRDN G1
50/50
1.06
315687AD1-152 GEN
Solar/Wind Harmer
7.81
957481AF2-042 GEN
Solar/Wind Harmer
173.007
316003AC1-222 GEN
Solar/Wind Harmer
5.389
970401AG2-262 GEN
Solar/Wind Harmer
3.261
315693AD1-088 GEN
Solar/Wind Harmer
24.89
962491AG1-098 GEN
Solar/Wind Harmer
32.899
316237AB2-079_GEN
Solar/Wind Harmer
1.107
970685AG2-442 GEN
Solar/Wind Harmer
29.8
963171AG1-166 GEN
Solar/Wind Harmer
4.173
971563AH1-280 GEN
Solar/Wind Harmer
4.173
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.345
316322AB2-045
Solar/Wind Harmer
0.75
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.876
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.257
971795AH1-408 GEN
Solar/Wind Harmer
10.577
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.561
971377AH1-170 GEN
Solar/Wind Harmer
1.439
3147623JAMES R
Solar/Wind Harmer
0.178
970937AG2-583 GEN
Solar/Wind Harmer
7.48
960081AF2-299 GEN
Solar/Wind Harmer
0.928
316336AC2-165 C
Solar/Wind Harmer
1.315
3143336POWHATN
Solar/Wind Harmer
0.767
3152661PLYWOOD A
50/50
1.09
3144293JTRSVLE
50/50
1.004
3144293JTRSVLE
50/50
0.845
970535AG2-341 GEN
50/50
5.145
970099AG2-077 GEN
Solar/Wind Harmer
69.203
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.672
962561AG1-105 GEN
Solar/Wind Harmer
26.937
971741AH1-377 GEN
Solar/Wind Harmer
47.726
970301AG2-198 GEN
Solar/Wind Harmer
19.228
313527AB2-043 GEN
Solar/Wind Harmer
5.909
970323AG2-213 GEN
Solar/Wind Harmer
17.388
971775AH1-396 GEN
Solar/Wind Harmer
2.476
316034AC1-036 C
Solar/Wind Harmer
0.645
942751AE2-291 GEN
Solar/Wind Harmer
21.395
958211AF2-115 GEN
Solar/Wind Harmer
5.217
963191AG1-168 GEN
Solar/Wind Harmer
3.13
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.11
3146776BUCKING
Solar/Wind Harmer
-0.089
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.974
316197AC1-042 GEN
Solar/Wind Harmer
1.496
942671AE2-283 GEN
Solar/Wind Harmer
4.029
971489AH1-241 GEN
Solar/Wind Harmer
6.83
315821AE2-092 GEN
Solar/Wind Harmer
1.78
316181AB2-040 GEN
Solar/Wind Harmer
1.069
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.789
3145593CAROLNA
Solar/Wind Harmer
0.058
316222AC1-221 GEN
Solar/Wind Helper
2.541
941821AE2-187 GEN
Solar/Wind Harmer
4.561
970221AG2-151 GEN
Solar/Wind Harmer
7.194
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.616
316313AB2-026
Solar/Wind Harmer
0.174
316258AE1-075 C
Solar/Wind Harmer
0.157
316405AF2-144 C
Solar/Wind Harmer
0.166
3143336POWHATN
Solar/Wind Harmer
0.652
316283AC2-100 C
Solar/Wind Helper
2.307
3151541CLOVER2
50/50
10.866
3151611KERR 4
50/50
0.536
3151621KERR 5
50/50
0.536
3151631KERR 6
50/50
0.536
3151641KERR 7
50/50
0.536
972205AH1-687 GEN
50/50
5.169
3147173SINAI
Solar/Wind Harmer
-0.06
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.778
970865AG2-541 GEN
Solar/Wind Harmer
19.161
316123AC1-075 GEN
Solar/Wind Harmer
4.191
970165AG2-112 GEN
Solar/Wind Harmer
3.69
970163AG2-111 GEN
Solar/Wind Harmer
3.52
316239AB2-077_GEN
Solar/Wind Harmer
1.107
316238AB2-078_GEN
Solar/Wind Harmer
1.107
971443AH1-215 GEN
Solar/Wind Harmer
6.858
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.607
970681AG2-440 GEN
Solar/Wind Harmer
21.285
946301AF1-294 GEN
Solar/Wind Harmer
8.556
961791AG1-021 GEN
Solar/Wind Harmer
4.173
315657AE1-056 GEN
Solar/Wind Harmer
12.343
970285AG2-188 GEN
Solar/Wind Harmer
21.187
971845AH1-439 GEN
Solar/Wind Harmer
12.195
970831AG2-522 GEN
Solar/Wind Harmer
10.008
971447AH1-217 GEN
Solar/Wind Harmer
3.882
270494AE1-108_GEN
Solar/Wind Harmer
2.486
946281AF1-292 GEN
Solar/Wind Harmer
0.185
316087AB2-174 GEN
Solar/Wind Harmer
1.118
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.363
270457AD2-023 GEN
Solar/Wind Helper
0.898
VTFLTFEXP_VFT->PJM
CMTX
1.248
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.788
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.862
G-007ALTFEXP_G-007A->PJM
CMTX
0.474
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.441
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.83
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.615
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.337

Details for 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.44 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1154.09
MW Contribution:5.14
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
10.918
3144293JTRSVLE
50/50
1.004
3151601KERR 3
50/50
0.536
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.436
3151561HALLBR1
50/50
0.35
3151931BEARGRDN S1
50/50
1.368
970413AG2-270 GEN
50/50
47.644
3144293JTRSVLE
50/50
1.004
3151591KERR 2
50/50
0.536
3151921BEARGRDN G2
50/50
1.06
316248AF1-058 C
Solar/Wind Harmer
1.8
960061AF2-297 GEN
Solar/Wind Harmer
29.873
316478AD1-087 GEN
Solar/Wind Harmer
4.978
316486AD2-202 GEN
Solar/Wind Harmer
1.458
971683AH1-343 GEN
Solar/Wind Harmer
22.104
970909AG2-566 GEN
Solar/Wind Harmer
3.651
316131AB2-060 GEN
Solar/Wind Harmer
3.913
964241AG1-285 GEN
Solar/Wind Harmer
27.973
315785AD2-033 C
Solar/Wind Harmer
7.946
970257AG2-171 GEN
Solar/Wind Harmer
13.042
959311AF2-222 GEN
Solar/Wind Harmer
36.079
963181AG1-167 GEN
Solar/Wind Harmer
3.13
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.573
942461AE2-259 GEN
Solar/Wind Harmer
4.746
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.561
970221AG2-151 GEN
Solar/Wind Harmer
7.195
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.616
316313AB2-026
Solar/Wind Harmer
0.174
316258AE1-075 C
Solar/Wind Harmer
0.157
316405AF2-144 C
Solar/Wind Harmer
0.166
3143336POWHATN
Solar/Wind Harmer
0.652
316283AC2-100 C
Solar/Wind Helper
2.307
3151911BEARGRDN G1
50/50
1.06
315687AD1-152 GEN
Solar/Wind Harmer
7.809
957481AF2-042 GEN
Solar/Wind Harmer
172.984
316003AC1-222 GEN
Solar/Wind Harmer
5.389
970401AG2-262 GEN
Solar/Wind Harmer
3.261
315693AD1-088 GEN
Solar/Wind Harmer
24.893
962491AG1-098 GEN
Solar/Wind Harmer
32.903
316237AB2-079_GEN
Solar/Wind Harmer
1.107
970685AG2-442 GEN
Solar/Wind Harmer
29.801
963171AG1-166 GEN
Solar/Wind Harmer
4.174
971563AH1-280 GEN
Solar/Wind Harmer
4.174
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.345
316322AB2-045
Solar/Wind Harmer
0.75
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.876
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.258
971795AH1-408 GEN
Solar/Wind Harmer
10.578
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.561
971377AH1-170 GEN
Solar/Wind Harmer
1.439
3147623JAMES R
Solar/Wind Harmer
0.178
970937AG2-583 GEN
Solar/Wind Harmer
7.481
960081AF2-299 GEN
Solar/Wind Harmer
0.928
316336AC2-165 C
Solar/Wind Harmer
1.315
3143336POWHATN
Solar/Wind Harmer
0.767
3151541CLOVER2
50/50
10.865
3151611KERR 4
50/50
0.536
3151621KERR 5
50/50
0.536
3151631KERR 6
50/50
0.536
3151641KERR 7
50/50
0.536
972205AH1-687 GEN
50/50
5.17
3147173SINAI
Solar/Wind Harmer
-0.06
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.778
970865AG2-541 GEN
Solar/Wind Harmer
19.161
316123AC1-075 GEN
Solar/Wind Harmer
4.19
970165AG2-112 GEN
Solar/Wind Harmer
3.69
970163AG2-111 GEN
Solar/Wind Harmer
3.52
316239AB2-077_GEN
Solar/Wind Harmer
1.107
316238AB2-078_GEN
Solar/Wind Harmer
1.107
971443AH1-215 GEN
Solar/Wind Harmer
6.858
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.608
970681AG2-440 GEN
Solar/Wind Harmer
21.286
946301AF1-294 GEN
Solar/Wind Harmer
8.556
961791AG1-021 GEN
Solar/Wind Harmer
4.174
315657AE1-056 GEN
Solar/Wind Harmer
12.344
970285AG2-188 GEN
Solar/Wind Harmer
21.189
971845AH1-439 GEN
Solar/Wind Harmer
12.197
970831AG2-522 GEN
Solar/Wind Harmer
10.008
971447AH1-217 GEN
Solar/Wind Harmer
3.882
270494AE1-108_GEN
Solar/Wind Harmer
2.486
946281AF1-292 GEN
Solar/Wind Harmer
0.185
316087AB2-174 GEN
Solar/Wind Harmer
1.118
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.363
270457AD2-023 GEN
Solar/Wind Helper
0.898
3152661PLYWOOD A
50/50
1.09
3144293JTRSVLE
50/50
1.004
3144293JTRSVLE
50/50
0.845
970535AG2-341 GEN
50/50
5.145
970099AG2-077 GEN
Solar/Wind Harmer
69.194
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.672
962561AG1-105 GEN
Solar/Wind Harmer
26.937
971741AH1-377 GEN
Solar/Wind Harmer
47.731
970301AG2-198 GEN
Solar/Wind Harmer
19.23
313527AB2-043 GEN
Solar/Wind Harmer
5.909
970323AG2-213 GEN
Solar/Wind Harmer
17.389
971775AH1-396 GEN
Solar/Wind Harmer
2.476
316034AC1-036 C
Solar/Wind Harmer
0.645
942751AE2-291 GEN
Solar/Wind Harmer
21.394
958211AF2-115 GEN
Solar/Wind Harmer
5.217
963191AG1-168 GEN
Solar/Wind Harmer
3.13
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.11
3146776BUCKING
Solar/Wind Harmer
-0.089
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.974
316197AC1-042 GEN
Solar/Wind Harmer
1.496
942671AE2-283 GEN
Solar/Wind Harmer
4.029
971489AH1-241 GEN
Solar/Wind Harmer
6.83
315821AE2-092 GEN
Solar/Wind Harmer
1.78
316181AB2-040 GEN
Solar/Wind Harmer
1.069
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.789
3145593CAROLNA
Solar/Wind Harmer
0.058
316222AC1-221 GEN
Solar/Wind Helper
2.541
VTFLTFEXP_VFT->PJM
CMTX
1.249
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.788
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.862
G-007ALTFEXP_G-007A->PJM
CMTX
0.475
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.441
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.83
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.615
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.337

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 56272_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56272_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.96 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:4114.65
MW Contribution:3.83
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
9.95
963041AG1-153 GEN
50/50
9.127
3151541CLOVER2
50/50
5.691
315779AE2-040
50/50
3.626
3151611KERR 4
50/50
0.458
3151621KERR 5
50/50
0.458
3151631KERR 6
50/50
0.458
3151641KERR 7
50/50
0.458
3151281ROARAP4
50/50
0.259
3151281ROARAP4
50/50
0.243
941031AE2-094 GEN
Solar/Wind Harmer
76.337
944011AF1-069 GEN
Solar/Wind Harmer
23.919
970673AG2-436 GEN
Solar/Wind Harmer
83.349
970673AG2-436 GEN
Solar/Wind Harmer
42.202
971967AH1-528 GEN
Solar/Wind Harmer
72.452
970085AG2-068 GEN
Solar/Wind Harmer
22.787
970581AG2-369 GEN
Solar/Wind Harmer
19.597
316315AB2-025 C
Solar/Wind Harmer
0.787
315814AE2-033 C
Solar/Wind Harmer
27.034
946281AF1-292 GEN
Solar/Wind Harmer
0.568
316087AB2-174 GEN
Solar/Wind Harmer
3.556
970831AG2-522 GEN
Solar/Wind Harmer
12.26
315652AC1-086 GEN
Solar/Wind Harmer
27.499
3137643SOCKMAN
Solar/Wind Harmer
-0.097
3145796HORNRTN
Solar/Wind Harmer
-0.077
3145796HORNRTN
Solar/Wind Harmer
-0.01
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
316118AC1-105 GEN
Solar/Wind Harmer
1.62
316239AB2-077_GEN
Solar/Wind Harmer
0.708
316238AB2-078_GEN
Solar/Wind Harmer
0.708
315607AA1-063A GEN
Solar/Wind Harmer
2.372
3146043SEABORD
Solar/Wind Harmer
-0.023
316319Z2-044 C
Solar/Wind Harmer
1.269
3146033SCOT NK
Solar/Wind Harmer
-0.091
3143316POE
Solar/Wind Harmer
-0.09
3145573BETHELC
Solar/Wind Harmer
-0.023
3145573BETHELC
Solar/Wind Harmer
-0.023
965291AG1-394 GEN
Solar/Wind Harmer
2.008
316318V4-068
Solar/Wind Harmer
0.563
3145893MURPHYS
Solar/Wind Harmer
-0.061
3145893MURPHYS
Solar/Wind Harmer
-0.023
970533AG2-339 GEN
50/50
32.21
970531AG2-338 GEN
50/50
12.884
315242AE2-183_GT2
50/50
5.755
315241AE2-183_GT1
50/50
5.72
972185AH1-677 GEN
50/50
20.748
3151041BRUNSWICKG3
50/50
4.507
972187AH1-678 GEN
50/50
10.344
3151361ROSEMG1
50/50
0.776
3151371ROSEMS1
50/50
0.481
3151381ROSEMG2
50/50
0.363
970535AG2-341 GEN
50/50
3.826
3152661PLYWOOD A
50/50
0.474
970933AG2-581 GEN
Solar/Wind Harmer
34.364
3151031BRUNSWICKG2
50/50
4.507
970413AG2-270 GEN
50/50
24.952
3151591KERR 2
50/50
0.458
3151391GASTONA
50/50
0.588
3151411GASTONB
50/50
0.588
3151261ROARAP2
50/50
0.26
970917AG2-570 GEN
Solar/Wind Harmer
91.647
316478AD1-087 GEN
Solar/Wind Harmer
2.597
316486AD2-202 GEN
Solar/Wind Harmer
0.761
316365GEN2_N
Solar/Wind Harmer
1.761
966621AG1-532 GEN
Solar/Wind Harmer
0.515
3147043LAWRENC
Solar/Wind Harmer
-0.015
313506AB2-031 GEN
Solar/Wind Harmer
1.989
3145796HORNRTN
Solar/Wind Harmer
-0.096
3145796HORNRTN
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
316248AF1-058 C
Solar/Wind Harmer
0.711
960061AF2-297 GEN
Solar/Wind Harmer
11.79
315724AD1-057 GEN
Solar/Wind Harmer
1.351
316131AB2-060 GEN
Solar/Wind Harmer
2.509
316210AC1-098 GEN
Solar/Wind Harmer
3.629
316327AA2-057 GEN
Solar/Wind Harmer
2.332
3146263WOODLND
Solar/Wind Harmer
-0.023
3146233WITAKRS
Solar/Wind Harmer
0.481
3146233WITAKRS
Solar/Wind Harmer
-0.015
3138543CONSLDL
Solar/Wind Harmer
-0.015
961601AG1-000A GEN
Solar/Wind Harmer
9.103
3145543BTLEBRO
Solar/Wind Harmer
-0.023
3145543BTLEBRO
Solar/Wind Harmer
-0.023
316317KELFORD C
Solar/Wind Harmer
1.074
3145823KELFORD
Solar/Wind Harmer
-0.023
3146073TAR RVR
Solar/Wind Harmer
-0.023
3146083TARBORO
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
0.158
3145893MURPHYS
Solar/Wind Harmer
-0.023
957521AF2-046 GEN
Solar/Wind Harmer
17.808
961681AG1-008 GEN
Solar/Wind Harmer
17.808
964241AG1-285 GEN
Solar/Wind Harmer
17.664
3146173TUNIS
Solar/Wind Harmer
-0.023
316463AE2-346 GEN
Solar/Wind Harmer
0.366
316140AB2-099
Solar/Wind Harmer
0.152
962331AG1-082 GEN
Solar/Wind Harmer
2.826
3156081AA2-088 GEN
Solar/Wind Harmer
7.311
3156021HOLLOMANSOL
Solar/Wind Harmer
3.009
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3145933PARMELE
Solar/Wind Harmer
-0.022
966801AG1-551 GEN
Solar/Wind Harmer
2.766
3146206CASHIE
Solar/Wind Harmer
-0.022
3145963POPLR C
Solar/Wind Harmer
-0.022
316283AC2-100 C
Solar/Wind Harmer
2.053
315737AD1-076 GEN
Solar/Wind Harmer
4.121
971157AH1-035 GEN
Solar/Wind Harmer
2.704
315785AD2-033 C
Solar/Wind Harmer
4.883
315614AA2-178 GEN
Solar/Wind Harmer
2.306
3145273HOLLAND
Solar/Wind Harmer
-0.016
971683AH1-343 GEN
Solar/Wind Harmer
9.136
970257AG2-171 GEN
Solar/Wind Harmer
7.93
3146376EDENTON
Solar/Wind Harmer
-0.021
970909AG2-566 GEN
Solar/Wind Harmer
1.981
959311AF2-222 GEN
Solar/Wind Harmer
21.769
3146626S HERTFORD
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.021
316435W1029_GEN3
Solar/Wind Harmer
3.733
316320Y1-086
Solar/Wind Harmer
1.19
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.444
970661AG2-428 GEN
Solar/Wind Harmer
3.756
944581AF1-123 GEN
Solar/Wind Harmer
90.622
944601AF1-125 GEN
Solar/Wind Harmer
89.208
316083AB2-161 GEN
Solar/Wind Harmer
3.214
970659AG2-427 GEN
Solar/Wind Harmer
1.86
315813AE1-149 C
Solar/Wind Harmer
12.185
3151101ELIZAR3
Adder
16.095
3144873MCLAUGH
Solar/Wind Harmer
0
963181AG1-167 GEN
Solar/Wind Harmer
1.798
3144293JTRSVLE
Adder
0.543
3144536CHRHLND
Solar/Wind Harmer
-0.003
3147133PAMPLIN
Solar/Wind Harmer
-0.058
971193AH1-056 GEN
Solar/Wind Harmer
11.575
3145336SMITFLD
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.509
3151221GRAVEL6
Adder
9.984
3151171GRAVELC
Adder
1.921
3144216WINCHST
Adder
0.443
3150921YORKTN3
Adder
2.878
316044AC1-158 PL1
Solar/Wind Helper
1.293
316450AC1-158 RIC
Solar/Wind Helper
0.345
315243AE2-183_GT3
50/50
5.755
3151051BRUNSWICKS1
50/50
9.355
3151021BRUNSWICKG1
50/50
4.507
971451AH1-221 GEN
50/50
13.69
3151531CLOVER1
50/50
5.718
3151601KERR 3
50/50
0.458
3151581KERR 1
50/50
0.163
3147043LAWRENC
50/50
2.116
3151391GASTONA
50/50
0.588
3151411GASTONB
50/50
0.588
3151261ROARAP2
50/50
0.266
970919AG2-571 GEN
Solar/Wind Harmer
11.601
970087AG2-069 GEN
Solar/Wind Harmer
34.181
939411AE1-173 GEN
Solar/Wind Harmer
170.129
957481AF2-042 GEN
Solar/Wind Harmer
99.882
315693AD1-088 GEN
Solar/Wind Harmer
14.731
962491AG1-098 GEN
Solar/Wind Harmer
19.405
315687AD1-152 GEN
Solar/Wind Harmer
3.35
316023GEN1_S
Solar/Wind Harmer
1.761
960081AF2-299 GEN
Solar/Wind Harmer
2.853
971795AH1-408 GEN
Solar/Wind Harmer
18.718
971065AG2-659 GEN
Solar/Wind Harmer
12.309
316129AC1-054 GEN
Solar/Wind Harmer
2.154
316011AB1-132 GEN
Solar/Wind Harmer
5.114
962571AG1-106 GEN
Solar/Wind Harmer
3.514
3145796HORNRTN
Solar/Wind Harmer
-0.08
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145783HORNRTN
Solar/Wind Harmer
-0.024
316190AA2-174 GEN
Solar/Wind Harmer
0.292
970401AG2-262 GEN
Solar/Wind Harmer
1.534
316237AB2-079_GEN
Solar/Wind Harmer
0.708
315722AD1-056 GEN
Solar/Wind Harmer
2.456
316212AC1-099_GEN
Solar/Wind Harmer
2.016
3146263WOODLND
Solar/Wind Harmer
-0.023
3146233WITAKRS
Solar/Wind Harmer
-0.091
316359AB2-059 GEN
Solar/Wind Harmer
3.083
316049AB1-081 GEN
Solar/Wind Harmer
2.467
3142053HEARTS
Solar/Wind Harmer
0.269
3145543BTLEBRO
Solar/Wind Harmer
-0.023
3145543BTLEBRO
Solar/Wind Harmer
-0.018
3145823KELFORD
Solar/Wind Harmer
-0.023
961671AG1-007 GEN
Solar/Wind Harmer
0.286
3146083TARBORO
Solar/Wind Harmer
-0.023
3145493TOT1
Solar/Wind Harmer
0.672
3145893MURPHYS
Solar/Wind Harmer
-0.09
3145893MURPHYS
Solar/Wind Harmer
0.671
3146173TUNIS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
316494AC1-189 GEN
Solar/Wind Harmer
2.416
316003AC1-222 GEN
Solar/Wind Harmer
2.177
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3146293MARTNCO
Solar/Wind Harmer
0.137
316174AB2-169 GEN
Solar/Wind Harmer
3.387
3146206CASHIE
Solar/Wind Harmer
-0.022
971547AH1-271 GEN
Solar/Wind Harmer
5.488
3145963POPLR C
Solar/Wind Harmer
-0.022
3145663CRESWEL
Solar/Wind Harmer
-0.06
971163AH1-040 GEN
Solar/Wind Harmer
20.04
3130156CHOWAN
Solar/Wind Harmer
-0.021
315800Z1-036_GEN1
Solar/Wind Harmer
5.153
3146516WINFALL
Solar/Wind Harmer
-0.066
3146516WINFALL
Solar/Wind Harmer
-0.021
316093AE2-104_GEN
Solar/Wind Harmer
5.989
316246AF1-032 C
Solar/Wind Harmer
0.415
970685AG2-442 GEN
Solar/Wind Harmer
17.619
3146456SLIGO L269
Solar/Wind Harmer
-0.02
316388AE2-253 GEN
Solar/Wind Harmer
1.348
970661AG2-428 GEN
Solar/Wind Harmer
21.192
944591AF1-124 GEN
Solar/Wind Harmer
90.948
316381AD1-082 GEN
Solar/Wind Harmer
1.816
970659AG2-427 GEN
Solar/Wind Harmer
10.495
316375AC2-012 GEN
Solar/Wind Harmer
6.72
3150981CHESPKA
Adder
2.158
963171AG1-166 GEN
Solar/Wind Harmer
2.398
971563AH1-280 GEN
Solar/Wind Harmer
2.398
3144293JTRSVLE
Adder
0.543
316072AD1-144
Solar/Wind Harmer
0.387
3145336SMITFLD
Solar/Wind Harmer
-0.067
3151171GRAVELC
Adder
1.461
3143226MDLTHAN
Solar/Wind Helper
0.294
316045AC1-158 PL2
Solar/Wind Helper
4.138
970099AG2-077 GEN
Solar/Wind Harmer
39.953
3144356SAPONY
Solar/Wind Harmer
1.018
316181AB2-040 GEN
Solar/Wind Harmer
3.451
939181AE1-148 GEN
Solar/Wind Harmer
13.835
3145796HORNRTN
Solar/Wind Harmer
-0.072
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
966811AG1-552 GEN
Solar/Wind Harmer
2.705
3145593CAROLNA
Solar/Wind Harmer
0.2
3145783HORNRTN
Solar/Wind Harmer
2.839
3145783HORNRTN
Solar/Wind Harmer
2.272
3145783HORNRTN
Solar/Wind Harmer
0.71
3145783HORNRTN
Solar/Wind Harmer
0.284
316426AA2-053 GEN
Solar/Wind Harmer
2.403
3146843MT LREL
Solar/Wind Harmer
-0.023
3146843MT LREL
Solar/Wind Harmer
-0.023
964791AG1-342 GEN
Solar/Wind Harmer
5.022
962561AG1-105 GEN
Solar/Wind Harmer
13.216
313527AB2-043 GEN
Solar/Wind Harmer
3.804
316274AC1-208 GEN
Solar/Wind Harmer
2.516
961601AG1-000A GEN
Solar/Wind Harmer
8.989
316263AC1-034 GEN
Solar/Wind Harmer
10.719
971741AH1-377 GEN
Solar/Wind Harmer
26.554
3145493TOT1
Solar/Wind Harmer
0.35
3145453TOT5
Solar/Wind Harmer
0.21
3145603CNETO
Solar/Wind Harmer
0.14
3145893MURPHYS
Solar/Wind Harmer
0.631
3145893MURPHYS
Solar/Wind Harmer
-0.041
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
3145933PARMELE
Solar/Wind Harmer
-0.044
3145933PARMELE
Solar/Wind Harmer
-0.022
316222AC1-221 GEN
Solar/Wind Harmer
2.217
316065AD1-022 GEN
Solar/Wind Harmer
10.926
315742AE1-103 GEN
Solar/Wind Harmer
2.245
970323AG2-213 GEN
Solar/Wind Harmer
10.573
971775AH1-396 GEN
Solar/Wind Harmer
1.506
316034AC1-036 C
Solar/Wind Harmer
0.392
3146376EDENTON
Solar/Wind Harmer
0.624
3146376EDENTON
Solar/Wind Harmer
0.624
970301AG2-198 GEN
Solar/Wind Harmer
10.435
3146626S HERTFORD
Solar/Wind Harmer
-0.021
3146626S HERTFORD
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.021
316431W1029_GEN1
Solar/Wind Harmer
3.733
316433W1029_GEN2
Solar/Wind Harmer
3.733
3146386ELIZ CT
Solar/Wind Harmer
-0.02
3130086AYDLETT
Solar/Wind Harmer
-0.08
3146456SLIGO L269
Solar/Wind Harmer
2.368
3137176SLIGO L2192
Solar/Wind Harmer
-0.079
316018AA1-139 ULT2
Solar/Wind Harmer
1.714
316017AA1-139 ULT1
Solar/Wind Harmer
1.619
316339AD2-160 GEN
Solar/Wind Harmer
1.348
3145506HICKORY
Solar/Wind Harmer
-0.079
3145506HICKORY
Solar/Wind Harmer
-0.048
3145506HICKORY
Solar/Wind Harmer
-0.012
970657AG2-426 GEN
Solar/Wind Harmer
6.206
970657AG2-426 GEN
Solar/Wind Harmer
1.298
316185AD1-033 GEN
Solar/Wind Harmer
2.091
3142956BIRDNECK
Solar/Wind Harmer
1.055
316316AC1-027 C
Solar/Wind Harmer
0.603
316036AC1-147 C
Solar/Wind Harmer
0.524
3150991CHESPKB
Adder
1.81
3150991CHESPKB
Adder
1.767
958211AF2-115 GEN
Solar/Wind Harmer
2.997
963191AG1-168 GEN
Solar/Wind Harmer
1.798
3144293JTRSVLE
Adder
0.543
3144293JTRSVLE
Adder
0.458
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.015
316236AE1-162_GEN
Solar/Wind Harmer
0.511
316447AC1-158 HLD
Solar/Wind Helper
2.845
3145513AHOSKIE
Solar/Wind Harmer
0.197
961941AG1-037 GEN
Solar/Wind Harmer
0.17
3145513AHOSKIE
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.045
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
316420AA1-050 GEN
Solar/Wind Harmer
2.577
957861AF2-080 GEN
Solar/Wind Harmer
9.823
316005AA1-067
Solar/Wind Harmer
0.45
3145746EVERETS
Solar/Wind Harmer
-0.088
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
970181AG2-120 GEN
Solar/Wind Harmer
2.918
3146206CASHIE
Solar/Wind Harmer
-0.022
970601AG2-382 GEN
Solar/Wind Harmer
9.603
315732AD1-074 GEN1
Solar/Wind Harmer
4.385
315733AD1-074 GEN2
Solar/Wind Harmer
4.385
315735AD1-075 GEN1
Solar/Wind Harmer
2.193
3130546PLYMOUTH
Solar/Wind Harmer
-0.022
315816AE2-034 GEN
Solar/Wind Harmer
1.73
971443AH1-215 GEN
Solar/Wind Harmer
4.181
3144303KENBRDG
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.021
3130156CHOWAN
Solar/Wind Harmer
-0.021
315611Z1-036_GEN2
Solar/Wind Harmer
5.153
315835AF2-110_GEN
Solar/Wind Harmer
2.575
3146486SUNBURY
Solar/Wind Harmer
-0.021
3146486SUNBURY
Solar/Wind Harmer
-0.021
316305AF2-043 C
Solar/Wind Harmer
0.619
3145176PASQUOTANK
Solar/Wind Harmer
-0.013
316321Z2-027
Solar/Wind Harmer
0.551
3146396TANGLEW
Solar/Wind Harmer
0.375
313526AB2-022
Solar/Wind Harmer
0.548
316311AC2-079 GEN
Solar/Wind Harmer
10.237
315833AF1-017_GEN
Solar/Wind Harmer
3.854
316349AD2-085 GEN
Solar/Wind Harmer
1.805
970683AG2-441 GEN
Solar/Wind Harmer
15.731
970681AG2-440 GEN
Solar/Wind Harmer
12.585
3146406KITTY HAWK
Solar/Wind Harmer
0.017
319010AE1-072 C
Solar/Wind Harmer
4.06
970865AG2-541 GEN
Solar/Wind Harmer
8.137
957871AF2-081 GEN
Solar/Wind Harmer
10.005
3151081ELIZAR1
Adder
15.891
3151091ELIZAR2
Adder
15.615
3152611GOSPORTB
Adder
2.203
3152621GOSPORTC
Adder
1.869
3152601GOSPORTA
Adder
1.724
946301AF1-294 GEN
Solar/Wind Harmer
4.916
961791AG1-021 GEN
Solar/Wind Harmer
2.398
270455AD2-022 GEN
Solar/Wind Harmer
3.325
270457AD2-023 GEN
Solar/Wind Harmer
1.686
315657AE1-056 GEN
Solar/Wind Harmer
6.945
316123AC1-075 GEN
Solar/Wind Harmer
1.908
970165AG2-112 GEN
Solar/Wind Harmer
1.68
970163AG2-111 GEN
Solar/Wind Harmer
1.602
972265AH1-717 GEN
Adder
10.663
3151201GRAVEL4
Adder
9.996
3151191GRAVEL3
Adder
9.869
3151211GRAVEL5
Adder
9.869
971445AH1-216 GEN
Solar/Wind Harmer
2.771
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.472
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.988
MECLTFEXP_MEC->PJM
CLTF
4.732
SIGELTFEXP_SIGE->PJM
CLTF
0.141
CPLELTFEXP_CPLE->PJM
CLTF
14.701
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.1
LAGNLTFEXP_LAGN->PJM
CLTF
9.968
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.656
TVALTFEXP_TVA->PJM
CLTF
4.976
NYPJM->LTFIMP_NY
CLTF
2.22
LGEELTFEXP_LGEE->PJM
CLTF
1.693
WECLTFEXP_WEC->PJM
CLTF
0.873

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 562_SRT-S-1


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 562_SRT-S-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.67 %
Rating:3118.0 MVA
Rating Type:B
MVA to Mitigate:3606.7
MW Contribution:3.83
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
5.755
3151031BRUNSWICKG2
50/50
4.507
970413AG2-270 GEN
50/50
24.952
3151591KERR 2
50/50
0.458
3151391GASTONA
50/50
0.588
3151411GASTONB
50/50
0.588
3151261ROARAP2
50/50
0.26
970917AG2-570 GEN
Solar/Wind Harmer
29.002
316478AD1-087 GEN
Solar/Wind Harmer
0.932
316486AD2-202 GEN
Solar/Wind Harmer
0.274
316365GEN2_N
Solar/Wind Harmer
0.521
3147043LAWRENC
Solar/Wind Harmer
0.132
313506AB2-031 GEN
Solar/Wind Harmer
0.68
3145796HORNRTN
Solar/Wind Harmer
0.862
3145796HORNRTN
Solar/Wind Harmer
0.215
3142666NORTHAMPTON
Solar/Wind Harmer
0.215
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
8.955
315724AD1-057 GEN
Solar/Wind Harmer
0.784
316131AB2-060 GEN
Solar/Wind Harmer
0.651
316210AC1-098 GEN
Solar/Wind Harmer
1.909
316327AA2-057 GEN
Solar/Wind Harmer
0.31
3146263WOODLND
Solar/Wind Harmer
0.205
3146233WITAKRS
Solar/Wind Harmer
1.026
3146233WITAKRS
Solar/Wind Harmer
0.139
3138543CONSLDL
Solar/Wind Harmer
0.135
961601AG1-000A GEN
Solar/Wind Harmer
14.474
971623AH1-311 GEN
Solar/Wind Harmer
0.407
3145543BTLEBRO
Solar/Wind Harmer
0.203
3145543BTLEBRO
Solar/Wind Harmer
0.203
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.203
3146073TAR RVR
Solar/Wind Harmer
0.201
315244AE2-183_ST
50/50
9.95
963041AG1-153 GEN
50/50
9.127
3151541CLOVER2
50/50
5.691
315779AE2-040
50/50
3.626
3151611KERR 4
50/50
0.458
3151621KERR 5
50/50
0.458
3151631KERR 6
50/50
0.458
3151641KERR 7
50/50
0.458
3151281ROARAP4
50/50
0.259
3151281ROARAP4
50/50
0.243
941031AE2-094 GEN
Solar/Wind Harmer
66.739
944011AF1-069 GEN
Solar/Wind Harmer
21.806
970673AG2-436 GEN
Solar/Wind Harmer
75.33
970673AG2-436 GEN
Solar/Wind Harmer
50.22
971967AH1-528 GEN
Solar/Wind Harmer
54.881
970085AG2-068 GEN
Solar/Wind Harmer
17.307
970581AG2-369 GEN
Solar/Wind Harmer
14.884
316315AB2-025 C
Solar/Wind Harmer
0.21
315814AE2-033 C
Solar/Wind Harmer
20.441
316087AB2-174 GEN
Solar/Wind Harmer
0.006
970831AG2-522 GEN
Solar/Wind Harmer
9.311
315652AC1-086 GEN
Solar/Wind Harmer
23.921
3137643SOCKMAN
Solar/Wind Harmer
0.866
3145796HORNRTN
Solar/Wind Harmer
0.689
3145796HORNRTN
Solar/Wind Harmer
0.086
3147173SINAI
Solar/Wind Harmer
0.21
3147243WELCO
Solar/Wind Harmer
0.131
316118AC1-105 GEN
Solar/Wind Harmer
0.541
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
315607AA1-063A GEN
Solar/Wind Harmer
0.427
3146043SEABORD
Solar/Wind Harmer
0.208
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.817
3143316POE
Solar/Wind Harmer
0.807
3145573BETHELC
Solar/Wind Harmer
0.201
3145573BETHELC
Solar/Wind Harmer
0.201
965291AG1-394 GEN
Solar/Wind Harmer
0.895
3145893MURPHYS
Solar/Wind Harmer
0.543
3145893MURPHYS
Solar/Wind Harmer
0.201
3145513AHOSKIE
Solar/Wind Harmer
0.421
3145513AHOSKIE
Solar/Wind Harmer
0.201
3145683EARLEYS
Solar/Wind Harmer
0.402
3146083TARBORO
Solar/Wind Harmer
0.201
3145893MURPHYS
Solar/Wind Harmer
0.337
3145893MURPHYS
Solar/Wind Harmer
0.201
957521AF2-046 GEN
Solar/Wind Harmer
14.974
961681AG1-008 GEN
Solar/Wind Harmer
14.974
964241AG1-285 GEN
Solar/Wind Harmer
13.416
3146173TUNIS
Solar/Wind Harmer
0.201
316463AE2-346 GEN
Solar/Wind Harmer
0.173
316140AB2-099
Solar/Wind Harmer
0.072
962331AG1-082 GEN
Solar/Wind Harmer
2.146
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
3156021HOLLOMANSOL
Solar/Wind Harmer
0.903
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
3145933PARMELE
Solar/Wind Harmer
0.197
966801AG1-551 GEN
Solar/Wind Harmer
2.294
3146206CASHIE
Solar/Wind Harmer
0.195
3145963POPLR C
Solar/Wind Harmer
0.195
316283AC2-100 C
Solar/Wind Harmer
0.379
315737AD1-076 GEN
Solar/Wind Harmer
2.483
971157AH1-035 GEN
Solar/Wind Harmer
2.31
315785AD2-033 C
Solar/Wind Harmer
1.559
315614AA2-178 GEN
Solar/Wind Harmer
1.089
3145273HOLLAND
Solar/Wind Harmer
0.141
971683AH1-343 GEN
Solar/Wind Harmer
6.939
970257AG2-171 GEN
Solar/Wind Harmer
6.023
3146376EDENTON
Solar/Wind Harmer
0.187
970909AG2-566 GEN
Solar/Wind Harmer
1.981
959311AF2-222 GEN
Solar/Wind Harmer
16.501
3146626S HERTFORD
Solar/Wind Harmer
0.184
3146516WINFALL
Solar/Wind Harmer
0.183
3151051BRUNSWICKS1
50/50
9.355
3151021BRUNSWICKG1
50/50
4.507
971451AH1-221 GEN
50/50
13.69
3151531CLOVER1
50/50
5.718
3151601KERR 3
50/50
0.458
3151581KERR 1
50/50
0.163
3147043LAWRENC
50/50
2.116
3151391GASTONA
50/50
0.588
3151411GASTONB
50/50
0.588
3151261ROARAP2
50/50
0.266
970919AG2-571 GEN
Solar/Wind Harmer
11.601
970087AG2-069 GEN
Solar/Wind Harmer
25.96
939411AE1-173 GEN
Solar/Wind Harmer
129.212
957481AF2-042 GEN
Solar/Wind Harmer
75.86
315693AD1-088 GEN
Solar/Wind Harmer
12.586
962491AG1-098 GEN
Solar/Wind Harmer
14.738
315687AD1-152 GEN
Solar/Wind Harmer
0.008
316023GEN1_S
Solar/Wind Harmer
0.521
960081AF2-299 GEN
Solar/Wind Harmer
2.167
971795AH1-408 GEN
Solar/Wind Harmer
14.808
971065AG2-659 GEN
Solar/Wind Harmer
9.349
316129AC1-054 GEN
Solar/Wind Harmer
0.822
316011AB1-132 GEN
Solar/Wind Harmer
3.954
962571AG1-106 GEN
Solar/Wind Harmer
3.094
3145796HORNRTN
Solar/Wind Harmer
0.711
3145796HORNRTN
Solar/Wind Harmer
0.215
3145783HORNRTN
Solar/Wind Harmer
0.213
316190AA2-174 GEN
Solar/Wind Harmer
0
970401AG2-262 GEN
Solar/Wind Harmer
1.228
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315722AD1-056 GEN
Solar/Wind Harmer
1.323
316212AC1-099_GEN
Solar/Wind Harmer
1.065
3146263WOODLND
Solar/Wind Harmer
0.205
3146233WITAKRS
Solar/Wind Harmer
0.813
316359AB2-059 GEN
Solar/Wind Harmer
0.731
316049AB1-081 GEN
Solar/Wind Harmer
1.165
3142053HEARTS
Solar/Wind Harmer
0.358
3145543BTLEBRO
Solar/Wind Harmer
0.203
3145543BTLEBRO
Solar/Wind Harmer
0.163
3145823KELFORD
Solar/Wind Harmer
0.203
961671AG1-007 GEN
Solar/Wind Harmer
0.031
3146083TARBORO
Solar/Wind Harmer
0.201
3145493TOT1
Solar/Wind Harmer
0.896
3145893MURPHYS
Solar/Wind Harmer
0.805
3145893MURPHYS
Solar/Wind Harmer
0.895
3146173TUNIS
Solar/Wind Harmer
0.201
3145683EARLEYS
Solar/Wind Harmer
0.201
316494AC1-189 GEN
Solar/Wind Harmer
0.675
316003AC1-222 GEN
Solar/Wind Harmer
0.005
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
3146293MARTNCO
Solar/Wind Harmer
0.183
316174AB2-169 GEN
Solar/Wind Harmer
0.005
3146206CASHIE
Solar/Wind Harmer
0.195
971547AH1-271 GEN
Solar/Wind Harmer
4.168
3145963POPLR C
Solar/Wind Harmer
0.195
3145663CRESWEL
Solar/Wind Harmer
0.532
971163AH1-040 GEN
Solar/Wind Harmer
15.22
3130156CHOWAN
Solar/Wind Harmer
0.187
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.594
3146516WINFALL
Solar/Wind Harmer
0.183
316093AE2-104_GEN
Solar/Wind Harmer
3.083
316246AF1-032 C
Solar/Wind Harmer
0.082
970685AG2-442 GEN
Solar/Wind Harmer
13.382
3146456SLIGO L269
Solar/Wind Harmer
0.178
316388AE2-253 GEN
Solar/Wind Harmer
0.557
970661AG2-428 GEN
Solar/Wind Harmer
17.657
944591AF1-124 GEN
Solar/Wind Harmer
40.063
970533AG2-339 GEN
50/50
32.21
970531AG2-338 GEN
50/50
12.884
315242AE2-183_GT2
50/50
5.755
315241AE2-183_GT1
50/50
5.72
972185AH1-677 GEN
50/50
20.748
3151041BRUNSWICKG3
50/50
4.507
972187AH1-678 GEN
50/50
10.344
3151361ROSEMG1
50/50
0.776
3151371ROSEMS1
50/50
0.481
3151381ROSEMG2
50/50
0.363
970535AG2-341 GEN
50/50
3.826
3152661PLYWOOD A
50/50
0.474
970933AG2-581 GEN
Solar/Wind Harmer
26.1
970099AG2-077 GEN
Solar/Wind Harmer
30.344
3144356SAPONY
Solar/Wind Harmer
2.173
316181AB2-040 GEN
Solar/Wind Harmer
0.319
939181AE1-148 GEN
Solar/Wind Harmer
10.508
3145796HORNRTN
Solar/Wind Harmer
0.646
3142666NORTHAMPTON
Solar/Wind Harmer
0.215
3142666NORTHAMPTON
Solar/Wind Harmer
0.215
3142666NORTHAMPTON
Solar/Wind Harmer
0.215
3142666NORTHAMPTON
Solar/Wind Harmer
0.129
3145593CAROLNA
Solar/Wind Harmer
0.214
3145593CAROLNA
Solar/Wind Harmer
0.214
966811AG1-552 GEN
Solar/Wind Harmer
2.321
3145593CAROLNA
Solar/Wind Harmer
0.266
3145783HORNRTN
Solar/Wind Harmer
3.786
3145783HORNRTN
Solar/Wind Harmer
3.029
3145783HORNRTN
Solar/Wind Harmer
0.946
3145783HORNRTN
Solar/Wind Harmer
0.379
316426AA2-053 GEN
Solar/Wind Harmer
0.715
3146843MT LREL
Solar/Wind Harmer
0.209
3146843MT LREL
Solar/Wind Harmer
0.209
964791AG1-342 GEN
Solar/Wind Harmer
4.018
962561AG1-105 GEN
Solar/Wind Harmer
10.037
313527AB2-043 GEN
Solar/Wind Harmer
0.003
316274AC1-208 GEN
Solar/Wind Harmer
1.077
961601AG1-000A GEN
Solar/Wind Harmer
3.618
316263AC1-034 GEN
Solar/Wind Harmer
7.734
971741AH1-377 GEN
Solar/Wind Harmer
20.167
3145493TOT1
Solar/Wind Harmer
0.467
3145453TOT5
Solar/Wind Harmer
0.28
3145603CNETO
Solar/Wind Harmer
0.187
3145893MURPHYS
Solar/Wind Harmer
1.347
3145893MURPHYS
Solar/Wind Harmer
0.362
3146173TUNIS
Solar/Wind Harmer
0.201
3146173TUNIS
Solar/Wind Harmer
0.201
3145933PARMELE
Solar/Wind Harmer
0.394
3145933PARMELE
Solar/Wind Harmer
0.197
316222AC1-221 GEN
Solar/Wind Harmer
0.81
316065AD1-022 GEN
Solar/Wind Harmer
8.955
315742AE1-103 GEN
Solar/Wind Harmer
0.002
970323AG2-213 GEN
Solar/Wind Harmer
8.03
971775AH1-396 GEN
Solar/Wind Harmer
0.301
316034AC1-036 C
Solar/Wind Harmer
0.014
3146376EDENTON
Solar/Wind Harmer
0.832
3146376EDENTON
Solar/Wind Harmer
0.832
970301AG2-198 GEN
Solar/Wind Harmer
7.926
3146626S HERTFORD
Solar/Wind Harmer
0.184
3146626S HERTFORD
Solar/Wind Harmer
0.184
3146516WINFALL
Solar/Wind Harmer
0.183
3146516WINFALL
Solar/Wind Harmer
0.183
3146516WINFALL
Solar/Wind Harmer
0.183
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146386ELIZ CT
Solar/Wind Harmer
0.181
3130086AYDLETT
Solar/Wind Harmer
0.715
3146456SLIGO L269
Solar/Wind Harmer
3.157
3137176SLIGO L2192
Solar/Wind Harmer
0.71
316018AA1-139 ULT2
Solar/Wind Harmer
0.004
316017AA1-139 ULT1
Solar/Wind Harmer
0.099
316339AD2-160 GEN
Solar/Wind Harmer
0.288
3145506HICKORY
Solar/Wind Harmer
0.708
3145506HICKORY
Solar/Wind Harmer
0.425
3145506HICKORY
Solar/Wind Harmer
0.106
970657AG2-426 GEN
Solar/Wind Harmer
6.19
3145683EARLEYS
Solar/Wind Harmer
0.201
3145683EARLEYS
Solar/Wind Harmer
0.201
316420AA1-050 GEN
Solar/Wind Harmer
0.007
957861AF2-080 GEN
Solar/Wind Harmer
8.615
316005AA1-067
Solar/Wind Harmer
0.212
3145746EVERETS
Solar/Wind Harmer
0.787
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
970181AG2-120 GEN
Solar/Wind Harmer
2.463
3146206CASHIE
Solar/Wind Harmer
0.195
970601AG2-382 GEN
Solar/Wind Harmer
7.294
315732AD1-074 GEN1
Solar/Wind Harmer
1.109
315733AD1-074 GEN2
Solar/Wind Harmer
1.109
315735AD1-075 GEN1
Solar/Wind Harmer
0.555
3130546PLYMOUTH
Solar/Wind Harmer
0.192
315816AE2-034 GEN
Solar/Wind Harmer
0.816
971443AH1-215 GEN
Solar/Wind Harmer
3.175
3144303KENBRDG
Solar/Wind Harmer
0.15
3130156CHOWAN
Solar/Wind Harmer
0.187
3130156CHOWAN
Solar/Wind Harmer
0.187
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
315835AF2-110_GEN
Solar/Wind Harmer
1.258
3146486SUNBURY
Solar/Wind Harmer
0.183
3146486SUNBURY
Solar/Wind Harmer
0.183
316305AF2-043 C
Solar/Wind Harmer
0.001
3145176PASQUOTANK
Solar/Wind Harmer
0.113
316321Z2-027
Solar/Wind Harmer
0.034
3146396TANGLEW
Solar/Wind Harmer
0.501
313526AB2-022
Solar/Wind Harmer
0.098
316311AC2-079 GEN
Solar/Wind Harmer
5.187
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.124
970683AG2-441 GEN
Solar/Wind Harmer
11.948
970681AG2-440 GEN
Solar/Wind Harmer
9.558
3146406KITTY HAWK
Solar/Wind Harmer
0.022
319010AE1-072 C
Solar/Wind Harmer
0.9
970865AG2-541 GEN
Solar/Wind Harmer
6.18
957871AF2-081 GEN
Solar/Wind Harmer
8.865
316435W1029_GEN3
Solar/Wind Harmer
0.001
316320Y1-086
Solar/Wind Harmer
0.001
3146456SLIGO L269
Solar/Wind Harmer
0.178
971153AH1-033 GEN
Solar/Wind Harmer
2.063
970661AG2-428 GEN
Solar/Wind Harmer
3.756
944581AF1-123 GEN
Solar/Wind Harmer
39.921
944601AF1-125 GEN
Solar/Wind Harmer
39.306
316083AB2-161 GEN
Solar/Wind Harmer
0.002
970659AG2-427 GEN
Solar/Wind Harmer
1.86
315813AE1-149 C
Solar/Wind Harmer
9.255
3151101ELIZAR3
Adder
16.095
3144873MCLAUGH
Solar/Wind Harmer
0.004
316381AD1-082 GEN
Solar/Wind Harmer
0.184
970657AG2-426 GEN
Solar/Wind Harmer
1.298
316185AD1-033 GEN
Solar/Wind Harmer
0.005
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.168
316036AC1-147 C
Solar/Wind Harmer
0.032
3150991CHESPKB
Adder
1.81
3150991CHESPKB
Adder
1.767
958211AF2-115 GEN
Solar/Wind Harmer
2.049
963191AG1-168 GEN
Solar/Wind Harmer
0.683
3144293JTRSVLE
Adder
0.543
970659AG2-427 GEN
Solar/Wind Harmer
8.503
316375AC2-012 GEN
Solar/Wind Harmer
0.004
3150981CHESPKA
Adder
2.158
963171AG1-166 GEN
Solar/Wind Harmer
0.911
971563AH1-280 GEN
Solar/Wind Harmer
1.821
3144293JTRSVLE
Adder
0.543
316072AD1-144
Solar/Wind Harmer
0.062
3145336SMITFLD
Solar/Wind Harmer
0.603
940641AE2-051 GEN
Solar/Wind Harmer
11.478
316294AC1-161 GEN
Solar/Wind Harmer
2.485
3151171GRAVELC
Adder
1.461
961611AG1-000B GEN
Solar/Wind Harmer
6.829
3146926FARMVIL
Solar/Wind Harmer
0.078
315671AE2-027_GEN
Solar/Wind Harmer
8.236
971647AH1-324 GEN
Solar/Wind Harmer
5.314
970223AG2-152 GEN
Solar/Wind Harmer
8.513
3138126ROCKLANDING
Solar/Wind Harmer
0.053
270016AE1-250 BESS
Solar/Wind Harmer
0.003
971069AG2-661 GEN
Solar/Wind Harmer
2.035
3143226MDLTHAN
Solar/Wind Helper
0.294
316045AC1-158 PL2
Solar/Wind Helper
4.138
3144293JTRSVLE
Adder
0.458
3147133PAMPLIN
Solar/Wind Harmer
0.165
3147133PAMPLIN
Solar/Wind Harmer
0.132
316236AE1-162_GEN
Solar/Wind Harmer
0.001
942751AE2-291 GEN
Solar/Wind Harmer
7.84
316033AB2-134 GEN
Solar/Wind Harmer
0.007
315697AD1-025 GEN
Solar/Wind Harmer
0.134
316240AF1-291 C
Solar/Wind Harmer
0.001
270013AE1-250 PV
Solar/Wind Harmer
0.003
316447AC1-158 HLD
Solar/Wind Helper
2.845
3151081ELIZAR1
Adder
15.891
3151091ELIZAR2
Adder
15.615
3152611GOSPORTB
Adder
2.203
3152621GOSPORTC
Adder
1.869
3152601GOSPORTA
Adder
1.724
946301AF1-294 GEN
Solar/Wind Harmer
3.369
961791AG1-021 GEN
Solar/Wind Harmer
1.639
315657AE1-056 GEN
Solar/Wind Harmer
5.685
316123AC1-075 GEN
Solar/Wind Harmer
0.215
970165AG2-112 GEN
Solar/Wind Harmer
1.276
970163AG2-111 GEN
Solar/Wind Harmer
1.217
971445AH1-216 GEN
Solar/Wind Harmer
10.534
972265AH1-717 GEN
Adder
10.663
3151201GRAVEL4
Adder
9.996
3151191GRAVEL3
Adder
9.869
3151211GRAVEL5
Adder
9.869
316369SG1_INVT
Solar/Wind Harmer
0.004
963181AG1-167 GEN
Solar/Wind Harmer
0.683
3144293JTRSVLE
Adder
0.543
3144536CHRHLND
Solar/Wind Harmer
0.025
3147133PAMPLIN
Solar/Wind Harmer
0.517
971193AH1-056 GEN
Solar/Wind Harmer
10.036
3145336SMITFLD
Solar/Wind Harmer
0.06
315839AE2-212 C
Solar/Wind Harmer
0.001
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
315773AC2-141 GEN
Solar/Wind Harmer
5.238
965281AG1-393 GEN
Solar/Wind Harmer
1.472
3151221GRAVEL6
Adder
9.984
3151171GRAVELC
Adder
1.921
961611AG1-000B GEN
Solar/Wind Harmer
3.472
3146926FARMVIL
Solar/Wind Harmer
0.078
3144216WINCHST
Adder
0.443
3150921YORKTN3
Adder
2.878
315778AD1-151 GEN
Solar/Wind Harmer
9.159
316044AC1-158 PL1
Solar/Wind Helper
1.293
316450AC1-158 RIC
Solar/Wind Helper
0.345
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.472
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.988
MECLTFEXP_MEC->PJM
CLTF
4.732
SIGELTFEXP_SIGE->PJM
CLTF
0.141
CPLELTFEXP_CPLE->PJM
CLTF
14.701
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.1
LAGNLTFEXP_LAGN->PJM
CLTF
9.968
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.656
TVALTFEXP_TVA->PJM
CLTF
4.976
NYPJM->LTFIMP_NY
CLTF
2.22
LGEELTFEXP_LGEE->PJM
CLTF
1.693
WECLTFEXP_WEC->PJM
CLTF
0.873

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 298_SRT-A-4


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 298_SRT-A-4
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.73 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:3694.83
MW Contribution:4.47
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
5.473
3151051BRUNSWICKS1
50/50
8.931
3151021BRUNSWICKG1
50/50
4.303
971451AH1-221 GEN
50/50
13.069
3151531CLOVER1
50/50
6.102
3144293JTRSVLE
50/50
0.91
3151601KERR 3
50/50
0.516
3151581KERR 1
50/50
0.184
3147043LAWRENC
50/50
2.357
3151261ROARAP2
50/50
0.292
3151391GASTONA
50/50
0.627
3151411GASTONB
50/50
0.627
940641AE2-051 GEN
Solar/Wind Harmer
26.708
970919AG2-571 GEN
Solar/Wind Harmer
11.113
970087AG2-069 GEN
Solar/Wind Harmer
24.879
939411AE1-173 GEN
Solar/Wind Harmer
131.626
957481AF2-042 GEN
Solar/Wind Harmer
79.711
315693AD1-088 GEN
Solar/Wind Harmer
14.154
962491AG1-098 GEN
Solar/Wind Harmer
16.814
3146926FARMVIL
Solar/Wind Harmer
0.172
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.115
972003AH1-546 GEN
Solar/Wind Harmer
12.173
963171AG1-166 GEN
Solar/Wind Harmer
1.437
971563AH1-280 GEN
Solar/Wind Harmer
2.875
970685AG2-442 GEN
Solar/Wind Harmer
19.861
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316237AB2-079_GEN
Solar/Wind Harmer
0.002
971065AG2-659 GEN
Solar/Wind Harmer
10.458
971795AH1-408 GEN
Solar/Wind Harmer
16.29
316129AC1-054 GEN
Solar/Wind Harmer
0.918
960081AF2-299 GEN
Solar/Wind Harmer
2.322
316023GEN1_S
Solar/Wind Harmer
0.541
970401AG2-262 GEN
Solar/Wind Harmer
1.401
316294AC1-161 GEN
Solar/Wind Harmer
4.128
944591AF1-124 GEN
Solar/Wind Harmer
53.196
316190AA2-174 GEN
Solar/Wind Harmer
0
3145783HORNRTN
Solar/Wind Harmer
0.232
316011AB1-132 GEN
Solar/Wind Harmer
4.212
962571AG1-106 GEN
Solar/Wind Harmer
3.296
316388AE2-253 GEN
Solar/Wind Harmer
0.724
3146456SLIGO L269
Solar/Wind Harmer
0.231
3145796HORNRTN
Solar/Wind Harmer
0.756
3145796HORNRTN
Solar/Wind Harmer
0.229
3146516WINFALL
Solar/Wind Harmer
0.741
3146516WINFALL
Solar/Wind Harmer
0.229
316246AF1-032 C
Solar/Wind Harmer
0.103
3146263WOODLND
Solar/Wind Harmer
0.228
3145893MURPHYS
Solar/Wind Harmer
0.913
3145893MURPHYS
Solar/Wind Harmer
1.016
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.842
3146173TUNIS
Solar/Wind Harmer
0.227
3130156CHOWAN
Solar/Wind Harmer
0.227
3145683EARLEYS
Solar/Wind Harmer
0.226
3145663CRESWEL
Solar/Wind Harmer
0.634
971163AH1-040 GEN
Solar/Wind Harmer
18.113
3145823KELFORD
Solar/Wind Harmer
0.226
3146206CASHIE
Solar/Wind Harmer
0.225
971547AH1-271 GEN
Solar/Wind Harmer
4.81
316093AE2-104_GEN
Solar/Wind Harmer
3.782
316212AC1-099_GEN
Solar/Wind Harmer
1.161
3145963POPLR C
Solar/Wind Harmer
0.221
315722AD1-056 GEN
Solar/Wind Harmer
1.402
316174AB2-169 GEN
Solar/Wind Harmer
0.006
3146293MARTNCO
Solar/Wind Harmer
0.202
3146233WITAKRS
Solar/Wind Harmer
0.867
3145746EVERETS
Solar/Wind Harmer
0.216
3145746EVERETS
Solar/Wind Harmer
0.216
316494AC1-189 GEN
Solar/Wind Harmer
0.73
316072AD1-144
Solar/Wind Harmer
0.078
961671AG1-007 GEN
Solar/Wind Harmer
0.033
3146083TARBORO
Solar/Wind Harmer
0.215
3145493TOT1
Solar/Wind Harmer
0.958
3145543BTLEBRO
Solar/Wind Harmer
0.215
3145543BTLEBRO
Solar/Wind Harmer
0.172
316359AB2-059 GEN
Solar/Wind Harmer
0.773
316049AB1-081 GEN
Solar/Wind Harmer
1.232
3142053HEARTS
Solar/Wind Harmer
0.379
316003AC1-222 GEN
Solar/Wind Harmer
0.006
970661AG2-428 GEN
Solar/Wind Harmer
20.056
3145336SMITFLD
Solar/Wind Harmer
0.789
316381AD1-082 GEN
Solar/Wind Harmer
0.205
970659AG2-427 GEN
Solar/Wind Harmer
9.423
3151171GRAVELC
Adder
1.898
3138126ROCKLANDING
Solar/Wind Harmer
0.077
961611AG1-000B GEN
Solar/Wind Harmer
8.775
971647AH1-324 GEN
Solar/Wind Harmer
6.762
971317AH1-138 GEN
Solar/Wind Harmer
1.142
971069AG2-661 GEN
Solar/Wind Harmer
2.539
316159AE1-175 C
Solar/Wind Harmer
0.117
315671AE2-027_GEN
Solar/Wind Harmer
8.622
315244AE2-183_ST
50/50
9.462
963041AG1-153 GEN
50/50
8.713
3151541CLOVER2
50/50
6.073
315779AE2-040
50/50
3.571
3151611KERR 4
50/50
0.516
3151621KERR 5
50/50
0.516
3151631KERR 6
50/50
0.516
3151641KERR 7
50/50
0.516
3151281ROARAP4
50/50
0.284
3151281ROARAP4
50/50
0.265
941031AE2-094 GEN
Solar/Wind Harmer
62.928
944011AF1-069 GEN
Solar/Wind Harmer
20.561
970673AG2-436 GEN
Solar/Wind Harmer
71.425
970673AG2-436 GEN
Solar/Wind Harmer
47.616
971967AH1-528 GEN
Solar/Wind Harmer
52.878
970085AG2-068 GEN
Solar/Wind Harmer
16.586
970581AG2-369 GEN
Solar/Wind Harmer
14.264
970285AG2-188 GEN
Solar/Wind Harmer
22.671
971845AH1-439 GEN
Solar/Wind Harmer
12.991
315657AE1-056 GEN
Solar/Wind Harmer
9.379
946301AF1-294 GEN
Solar/Wind Harmer
5.318
961791AG1-021 GEN
Solar/Wind Harmer
2.587
970683AG2-441 GEN
Solar/Wind Harmer
17.733
970681AG2-440 GEN
Solar/Wind Harmer
14.186
3144303KENBRDG
Solar/Wind Harmer
0.21
971443AH1-215 GEN
Solar/Wind Harmer
4.401
316315AB2-025 C
Solar/Wind Harmer
0.207
315814AE2-033 C
Solar/Wind Harmer
20.184
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
970831AG2-522 GEN
Solar/Wind Harmer
10.378
316087AB2-174 GEN
Solar/Wind Harmer
0.007
3137643SOCKMAN
Solar/Wind Harmer
0.942
316118AC1-105 GEN
Solar/Wind Harmer
0.602
315607AA1-063A GEN
Solar/Wind Harmer
0.474
3146043SEABORD
Solar/Wind Harmer
0.232
315652AC1-086 GEN
Solar/Wind Harmer
25.484
957871AF2-081 GEN
Solar/Wind Harmer
11.507
319010AE1-072 C
Solar/Wind Harmer
1.163
3146406KITTY HAWK
Solar/Wind Harmer
0.029
313526AB2-022
Solar/Wind Harmer
0.125
316321Z2-027
Solar/Wind Harmer
0.043
3146396TANGLEW
Solar/Wind Harmer
0.633
3145176PASQUOTANK
Solar/Wind Harmer
0.142
965291AG1-394 GEN
Solar/Wind Harmer
1.02
3145796HORNRTN
Solar/Wind Harmer
0.733
3145796HORNRTN
Solar/Wind Harmer
0.092
3146486SUNBURY
Solar/Wind Harmer
0.229
3146486SUNBURY
Solar/Wind Harmer
0.229
3151081ELIZAR1
Adder
20.965
3151091ELIZAR2
Adder
20.6
316305AF2-043 C
Solar/Wind Harmer
0.002
3145893MURPHYS
Solar/Wind Harmer
0.617
3145893MURPHYS
Solar/Wind Harmer
0.228
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3147173SINAI
Solar/Wind Harmer
0.228
3147243WELCO
Solar/Wind Harmer
0.142
3152611GOSPORTB
Adder
2.9
3152621GOSPORTC
Adder
2.461
3152601GOSPORTA
Adder
2.27
3130156CHOWAN
Solar/Wind Harmer
0.227
3130156CHOWAN
Solar/Wind Harmer
0.227
3145513AHOSKIE
Solar/Wind Harmer
0.475
3145513AHOSKIE
Solar/Wind Harmer
0.227
3145683EARLEYS
Solar/Wind Harmer
0.453
3145683EARLEYS
Solar/Wind Harmer
0.226
3145683EARLEYS
Solar/Wind Harmer
0.226
315816AE2-034 GEN
Solar/Wind Harmer
0.972
3130546PLYMOUTH
Solar/Wind Harmer
0.225
3146206CASHIE
Solar/Wind Harmer
0.225
970601AG2-382 GEN
Solar/Wind Harmer
8.417
315732AD1-074 GEN1
Solar/Wind Harmer
1.295
315733AD1-074 GEN2
Solar/Wind Harmer
1.295
315735AD1-075 GEN1
Solar/Wind Harmer
0.648
3146033SCOT NK
Solar/Wind Harmer
0.899
315835AF2-110_GEN
Solar/Wind Harmer
1.543
316319Z2-044 C
Solar/Wind Harmer
0
316005AA1-067
Solar/Wind Harmer
0.232
3145746EVERETS
Solar/Wind Harmer
0.861
3145746EVERETS
Solar/Wind Harmer
0.216
3145746EVERETS
Solar/Wind Harmer
0.216
3145746EVERETS
Solar/Wind Harmer
0.216
970181AG2-120 GEN
Solar/Wind Harmer
2.694
957861AF2-080 GEN
Solar/Wind Harmer
9.312
316420AA1-050 GEN
Solar/Wind Harmer
0.007
3145573BETHELC
Solar/Wind Harmer
0.215
3145573BETHELC
Solar/Wind Harmer
0.215
316311AC2-079 GEN
Solar/Wind Harmer
6.15
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.147
3143316POE
Solar/Wind Harmer
0.803
971445AH1-216 GEN
Solar/Wind Harmer
13.774
970865AG2-541 GEN
Solar/Wind Harmer
6.632
972265AH1-717 GEN
Adder
13.853
3151201GRAVEL4
Adder
12.986
3151191GRAVEL3
Adder
12.822
3151211GRAVEL5
Adder
12.822
316123AC1-075 GEN
Solar/Wind Harmer
0.229
970165AG2-112 GEN
Solar/Wind Harmer
1.355
970163AG2-111 GEN
Solar/Wind Harmer
1.293
316369SG1_INVT
Solar/Wind Harmer
0.006
3138283WHITEMARSH
Solar/Wind Harmer
0.031
316132AB2-190 GEN1
Solar/Wind Harmer
0.712
3151031BRUNSWICKG2
50/50
4.303
970413AG2-270 GEN
50/50
26.631
3144293JTRSVLE
50/50
0.91
3151591KERR 2
50/50
0.516
3151261ROARAP2
50/50
0.285
3151391GASTONA
50/50
0.627
3151411GASTONB
50/50
0.627
970917AG2-570 GEN
Solar/Wind Harmer
27.783
970909AG2-566 GEN
Solar/Wind Harmer
3.095
3146926FARMVIL
Solar/Wind Harmer
0.172
3146776BUCKING
Solar/Wind Harmer
0.103
316478AD1-087 GEN
Solar/Wind Harmer
0.994
316486AD2-202 GEN
Solar/Wind Harmer
0.292
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
3147133PAMPLIN
Solar/Wind Harmer
0.853
971193AH1-056 GEN
Solar/Wind Harmer
16.558
963181AG1-167 GEN
Solar/Wind Harmer
1.078
959311AF2-222 GEN
Solar/Wind Harmer
23.408
970257AG2-171 GEN
Solar/Wind Harmer
8.392
315785AD2-033 C
Solar/Wind Harmer
2.12
964241AG1-285 GEN
Solar/Wind Harmer
17.126
316131AB2-060 GEN
Solar/Wind Harmer
0.8
3147043LAWRENC
Solar/Wind Harmer
0.147
316365GEN2_N
Solar/Wind Harmer
0.541
315773AC2-141 GEN
Solar/Wind Harmer
8.701
313506AB2-031 GEN
Solar/Wind Harmer
0.736
944581AF1-123 GEN
Solar/Wind Harmer
53.008
944601AF1-125 GEN
Solar/Wind Harmer
52.191
3142666NORTHAMPTON
Solar/Wind Harmer
0.231
3146456SLIGO L269
Solar/Wind Harmer
0.231
971153AH1-033 GEN
Solar/Wind Harmer
2.669
316320Y1-086
Solar/Wind Harmer
0.001
3145796HORNRTN
Solar/Wind Harmer
0.917
3145796HORNRTN
Solar/Wind Harmer
0.229
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
3146516WINFALL
Solar/Wind Harmer
0.229
316435W1029_GEN3
Solar/Wind Harmer
0.001
3151101ELIZAR3
Adder
21.233
3146263WOODLND
Solar/Wind Harmer
0.228
3146626S HERTFORD
Solar/Wind Harmer
0.228
3145893MURPHYS
Solar/Wind Harmer
0.382
3145893MURPHYS
Solar/Wind Harmer
0.228
957521AF2-046 GEN
Solar/Wind Harmer
16.981
961681AG1-008 GEN
Solar/Wind Harmer
16.981
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.719
3144873MCLAUGH
Solar/Wind Harmer
0.006
3146173TUNIS
Solar/Wind Harmer
0.227
3146376EDENTON
Solar/Wind Harmer
0.227
316463AE2-346 GEN
Solar/Wind Harmer
0.195
316140AB2-099
Solar/Wind Harmer
0.081
962331AG1-082 GEN
Solar/Wind Harmer
2.421
315614AA2-178 GEN
Solar/Wind Harmer
1.296
3145273HOLLAND
Solar/Wind Harmer
0.17
316317KELFORD C
Solar/Wind Harmer
0.022
3145823KELFORD
Solar/Wind Harmer
0.226
971157AH1-035 GEN
Solar/Wind Harmer
2.707
3156021HOLLOMANSOL
Solar/Wind Harmer
1.024
3146206CASHIE
Solar/Wind Harmer
0.225
315737AD1-076 GEN
Solar/Wind Harmer
2.901
316210AC1-098 GEN
Solar/Wind Harmer
2.081
3145963POPLR C
Solar/Wind Harmer
0.221
315724AD1-057 GEN
Solar/Wind Harmer
0.831
316327AA2-057 GEN
Solar/Wind Harmer
0.333
3144536CHRHLND
Solar/Wind Harmer
0.033
3145933PARMELE
Solar/Wind Harmer
0.218
966801AG1-551 GEN
Solar/Wind Harmer
2.54
3146233WITAKRS
Solar/Wind Harmer
1.094
3146233WITAKRS
Solar/Wind Harmer
0.148
3138543CONSLDL
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
0.216
3145746EVERETS
Solar/Wind Harmer
0.216
3146073TAR RVR
Solar/Wind Harmer
0.215
3146083TARBORO
Solar/Wind Harmer
0.215
3145543BTLEBRO
Solar/Wind Harmer
0.215
3145543BTLEBRO
Solar/Wind Harmer
0.215
971623AH1-311 GEN
Solar/Wind Harmer
0.431
961601AG1-000A GEN
Solar/Wind Harmer
15.295
971683AH1-343 GEN
Solar/Wind Harmer
7.476
970661AG2-428 GEN
Solar/Wind Harmer
4.266
316283AC2-100 C
Solar/Wind Harmer
0.392
3145336SMITFLD
Solar/Wind Harmer
0.079
316083AB2-161 GEN
Solar/Wind Harmer
0.003
970659AG2-427 GEN
Solar/Wind Harmer
2.061
315813AE1-149 C
Solar/Wind Harmer
9.899
3151221GRAVEL6
Adder
12.971
3151171GRAVELC
Adder
2.496
3144216WINCHST
Adder
0.636
961611AG1-000B GEN
Solar/Wind Harmer
4.462
3150921YORKTN3
Adder
4.197
315839AE2-212 C
Solar/Wind Harmer
0.001
965281AG1-393 GEN
Solar/Wind Harmer
1.528
315778AD1-151 GEN
Solar/Wind Harmer
11.426
316382AG1-145 C
Solar/Wind Harmer
0.001
970129AG2-093 GEN
Solar/Wind Harmer
7.926
970133AG2-095 GEN
Solar/Wind Harmer
1.101
316313AB2-026
Solar/Wind Helper
0.384
316258AE1-075 C
Solar/Wind Helper
0.346
316405AF2-144 C
Solar/Wind Helper
0.288
316044AC1-158 PL1
Solar/Wind Helper
1.299
316450AC1-158 RIC
Solar/Wind Helper
0.346
3147666LOUISA
Solar/Wind Helper
0.521
316458AB2-190 GEN2
Solar/Wind Harmer
0.712
970129AG2-093 GEN
Solar/Wind Harmer
3.73
970223AG2-152 GEN
Solar/Wind Harmer
8.557
270016AE1-250 BESS
Solar/Wind Harmer
0.003
3143226MDLTHAN
Solar/Wind Helper
0.314
316336AC2-165 C
Solar/Wind Helper
1.274
316045AC1-158 PL2
Solar/Wind Helper
4.157
3147666LOUISA
Solar/Wind Helper
0.906
316192AB2-158 GEN
Solar/Wind Helper
1.506
970533AG2-339 GEN
50/50
30.371
970531AG2-338 GEN
50/50
12.148
315242AE2-183_GT2
50/50
5.473
315241AE2-183_GT1
50/50
5.439
972185AH1-677 GEN
50/50
19.73
3151041BRUNSWICKG3
50/50
4.303
972187AH1-678 GEN
50/50
9.875
3144293JTRSVLE
50/50
0.91
3144293JTRSVLE
50/50
0.767
970535AG2-341 GEN
50/50
4.473
3152661PLYWOOD A
50/50
0.522
3151361ROSEMG1
50/50
0.826
3151371ROSEMS1
50/50
0.512
3151381ROSEMG2
50/50
0.387
970933AG2-581 GEN
Solar/Wind Harmer
25.75
970099AG2-077 GEN
Solar/Wind Harmer
31.885
971741AH1-377 GEN
Solar/Wind Harmer
28.889
970301AG2-198 GEN
Solar/Wind Harmer
12.379
3146776BUCKING
Solar/Wind Harmer
1.145
3146776BUCKING
Solar/Wind Harmer
0.093
3147133PAMPLIN
Solar/Wind Harmer
0.272
3147133PAMPLIN
Solar/Wind Harmer
0.217
958211AF2-115 GEN
Solar/Wind Harmer
3.234
963191AG1-168 GEN
Solar/Wind Harmer
1.078
316034AC1-036 C
Solar/Wind Harmer
0.019
970323AG2-213 GEN
Solar/Wind Harmer
11.19
971775AH1-396 GEN
Solar/Wind Harmer
0.42
3144356SAPONY
Solar/Wind Harmer
2.14
313527AB2-043 GEN
Solar/Wind Harmer
0.003
939181AE1-148 GEN
Solar/Wind Harmer
12.018
962561AG1-105 GEN
Solar/Wind Harmer
11.57
964791AG1-342 GEN
Solar/Wind Harmer
4.584
3146843MT LREL
Solar/Wind Harmer
0.238
3146843MT LREL
Solar/Wind Harmer
0.238
316181AB2-040 GEN
Solar/Wind Harmer
0.346
3145593CAROLNA
Solar/Wind Harmer
0.234
3145593CAROLNA
Solar/Wind Harmer
0.234
966811AG1-552 GEN
Solar/Wind Harmer
2.539
3145593CAROLNA
Solar/Wind Harmer
0.291
316426AA2-053 GEN
Solar/Wind Harmer
0.786
3145783HORNRTN
Solar/Wind Harmer
4.136
3145783HORNRTN
Solar/Wind Harmer
3.309
3145783HORNRTN
Solar/Wind Harmer
1.034
3145783HORNRTN
Solar/Wind Harmer
0.414
3145506HICKORY
Solar/Wind Harmer
0.926
3145506HICKORY
Solar/Wind Harmer
0.555
3145506HICKORY
Solar/Wind Harmer
0.139
316185AD1-033 GEN
Solar/Wind Harmer
0.007
316339AD2-160 GEN
Solar/Wind Harmer
0.375
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.129
3142666NORTHAMPTON
Solar/Wind Harmer
0.231
3142666NORTHAMPTON
Solar/Wind Harmer
0.231
3142666NORTHAMPTON
Solar/Wind Harmer
0.231
3142666NORTHAMPTON
Solar/Wind Harmer
0.139
3137176SLIGO L2192
Solar/Wind Harmer
0.919
3146456SLIGO L269
Solar/Wind Harmer
4.086
3130086AYDLETT
Solar/Wind Harmer
0.923
3146386ELIZ CT
Solar/Wind Harmer
0.23
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.22
3145796HORNRTN
Solar/Wind Harmer
0.688
3146516WINFALL
Solar/Wind Harmer
0.229
3146516WINFALL
Solar/Wind Harmer
0.229
3146516WINFALL
Solar/Wind Harmer
0.229
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146626S HERTFORD
Solar/Wind Harmer
0.228
3146626S HERTFORD
Solar/Wind Harmer
0.228
3145893MURPHYS
Solar/Wind Harmer
1.529
3145893MURPHYS
Solar/Wind Harmer
0.411
316036AC1-147 C
Solar/Wind Harmer
0.042
3150991CHESPKB
Adder
2.385
3150991CHESPKB
Adder
2.327
3146173TUNIS
Solar/Wind Harmer
0.227
3146173TUNIS
Solar/Wind Harmer
0.227
3146376EDENTON
Solar/Wind Harmer
1.011
3146376EDENTON
Solar/Wind Harmer
1.011
315742AE1-103 GEN
Solar/Wind Harmer
0.003
316065AD1-022 GEN
Solar/Wind Harmer
10.381
316274AC1-208 GEN
Solar/Wind Harmer
1.168
3145933PARMELE
Solar/Wind Harmer
0.436
3145933PARMELE
Solar/Wind Harmer
0.218
3145493TOT1
Solar/Wind Harmer
0.5
3145453TOT5
Solar/Wind Harmer
0.3
3145603CNETO
Solar/Wind Harmer
0.2
316263AC1-034 GEN
Solar/Wind Harmer
8.182
961601AG1-000A GEN
Solar/Wind Harmer
3.824
316222AC1-221 GEN
Solar/Wind Harmer
0.837
970657AG2-426 GEN
Solar/Wind Harmer
6.952
970657AG2-426 GEN
Solar/Wind Harmer
1.457
316236AE1-162_GEN
Solar/Wind Harmer
0.002
942751AE2-291 GEN
Solar/Wind Harmer
8.262
316033AB2-134 GEN
Solar/Wind Harmer
0.009
315697AD1-025 GEN
Solar/Wind Harmer
0.168
316240AF1-291 C
Solar/Wind Harmer
0.001
270013AE1-250 PV
Solar/Wind Harmer
0.003
316447AC1-158 HLD
Solar/Wind Helper
2.858
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.643
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.605
MECLTFEXP_MEC->PJM
CLTF
4.532
SIGELTFEXP_SIGE->PJM
CLTF
0.135
CPLELTFEXP_CPLE->PJM
CLTF
14.901
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.672
LAGNLTFEXP_LAGN->PJM
CLTF
9.785
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.79
TVALTFEXP_TVA->PJM
CLTF
4.881
NYPJM->LTFIMP_NY
CLTF
2.249
LGEELTFEXP_LGEE->PJM
CLTF
1.604
WECLTFEXP_WEC->PJM
CLTF
0.825

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: BREMO B1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:108.3 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4267.15
MW Contribution:4.4
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
5.38
3151051BRUNSWICKS1
50/50
8.78
3151021BRUNSWICKG1
50/50
4.23
971451AH1-221 GEN
50/50
12.849
3151531CLOVER1
50/50
6.004
3144293JTRSVLE
50/50
0.895
3151601KERR 3
50/50
0.508
3151581KERR 1
50/50
0.181
3147043LAWRENC
50/50
2.311
970533AG2-339 GEN
50/50
29.851
970531AG2-338 GEN
50/50
11.94
315242AE2-183_GT2
50/50
5.38
315241AE2-183_GT1
50/50
5.347
972185AH1-677 GEN
50/50
19.395
3151041BRUNSWICKG3
50/50
4.23
972187AH1-678 GEN
50/50
9.708
3144293JTRSVLE
50/50
0.895
3144293JTRSVLE
50/50
0.754
970535AG2-341 GEN
50/50
4.4
3152661PLYWOOD A
50/50
0.514
3151361ROSEMG1
50/50
0.809
3151371ROSEMS1
50/50
0.501
3151381ROSEMG2
50/50
0.379
970933AG2-581 GEN
Solar/Wind Harmer
33.334
970099AG2-077 GEN
Solar/Wind Harmer
41.293
971741AH1-377 GEN
Solar/Wind Harmer
37.414
970301AG2-198 GEN
Solar/Wind Harmer
16.032
3146776BUCKING
Solar/Wind Harmer
-0.126
3146776BUCKING
Solar/Wind Harmer
-0.01
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
958211AF2-115 GEN
Solar/Wind Harmer
4.654
963191AG1-168 GEN
Solar/Wind Harmer
2.792
316034AC1-036 C
Solar/Wind Harmer
0.538
970323AG2-213 GEN
Solar/Wind Harmer
14.493
971775AH1-396 GEN
Solar/Wind Harmer
2.064
313527AB2-043 GEN
Solar/Wind Harmer
4.56
3144356SAPONY
Solar/Wind Harmer
0.979
3151261ROARAP2
50/50
0.286
3151391GASTONA
50/50
0.614
3151411GASTONB
50/50
0.614
940641AE2-051 GEN
Solar/Wind Harmer
34.524
970919AG2-571 GEN
Solar/Wind Harmer
10.928
970087AG2-069 GEN
Solar/Wind Harmer
32.211
939411AE1-173 GEN
Solar/Wind Harmer
169.915
957481AF2-042 GEN
Solar/Wind Harmer
103.233
315693AD1-088 GEN
Solar/Wind Harmer
16.294
962491AG1-098 GEN
Solar/Wind Harmer
21.776
3146926FARMVIL
Solar/Wind Harmer
-0.019
316322AB2-045
Solar/Wind Harmer
1.065
3146776BUCKING
Solar/Wind Harmer
-0.013
972003AH1-546 GEN
Solar/Wind Harmer
15.792
963171AG1-166 GEN
Solar/Wind Harmer
3.723
971563AH1-280 GEN
Solar/Wind Harmer
3.723
970685AG2-442 GEN
Solar/Wind Harmer
25.722
315687AD1-152 GEN
Solar/Wind Harmer
3.514
316237AB2-079_GEN
Solar/Wind Harmer
0.842
971065AG2-659 GEN
Solar/Wind Harmer
13.526
316129AC1-054 GEN
Solar/Wind Harmer
2.362
971795AH1-408 GEN
Solar/Wind Harmer
20.182
960081AF2-299 GEN
Solar/Wind Harmer
2.993
316023GEN1_S
Solar/Wind Harmer
1.787
970401AG2-262 GEN
Solar/Wind Harmer
1.725
316294AC1-161 GEN
Solar/Wind Harmer
8.447
944591AF1-124 GEN
Solar/Wind Harmer
117.74
316190AA2-174 GEN
Solar/Wind Harmer
0.315
3145783HORNRTN
Solar/Wind Harmer
-0.026
316011AB1-132 GEN
Solar/Wind Harmer
5.334
962571AG1-106 GEN
Solar/Wind Harmer
3.665
316388AE2-253 GEN
Solar/Wind Harmer
1.708
3146456SLIGO L269
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.083
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146263WOODLND
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
-0.1
3145893MURPHYS
Solar/Wind Harmer
0.745
3146516WINFALL
Solar/Wind Harmer
-0.081
3146516WINFALL
Solar/Wind Harmer
-0.025
316246AF1-032 C
Solar/Wind Harmer
0.507
3146173TUNIS
Solar/Wind Harmer
-0.025
315800Z1-036_GEN1
Solar/Wind Harmer
6.178
3130156CHOWAN
Solar/Wind Harmer
-0.025
316375AC2-012 GEN
Solar/Wind Harmer
8.621
3150981CHESPKA
Adder
2.768
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145663CRESWEL
Solar/Wind Harmer
-0.069
971163AH1-040 GEN
Solar/Wind Harmer
23.294
3145823KELFORD
Solar/Wind Harmer
-0.025
3146206CASHIE
Solar/Wind Harmer
-0.025
971547AH1-271 GEN
Solar/Wind Harmer
6.191
316212AC1-099_GEN
Solar/Wind Harmer
2.154
316093AE2-104_GEN
Solar/Wind Harmer
7.155
315722AD1-056 GEN
Solar/Wind Harmer
2.553
3145963POPLR C
Solar/Wind Harmer
-0.024
316174AB2-169 GEN
Solar/Wind Harmer
3.744
3146233WITAKRS
Solar/Wind Harmer
-0.095
3146293MARTNCO
Solar/Wind Harmer
0.149
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
316003AC1-222 GEN
Solar/Wind Harmer
2.327
316494AC1-189 GEN
Solar/Wind Harmer
2.561
961671AG1-007 GEN
Solar/Wind Harmer
0.3
3146083TARBORO
Solar/Wind Harmer
-0.024
3145493TOT1
Solar/Wind Harmer
0.705
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.019
316359AB2-059 GEN
Solar/Wind Harmer
3.202
316049AB1-081 GEN
Solar/Wind Harmer
2.562
3142053HEARTS
Solar/Wind Harmer
0.279
316072AD1-144
Solar/Wind Harmer
0.477
3151171GRAVELC
Adder
1.83
3143226MDLTHAN
Solar/Wind Helper
0.35
316336AC2-165 C
Solar/Wind Helper
1.883
316045AC1-158 PL2
Solar/Wind Helper
4.241
3143526WINTERP
Solar/Wind Helper
1.191
970661AG2-428 GEN
Solar/Wind Harmer
10.44
315244AE2-183_ST
50/50
9.302
963041AG1-153 GEN
50/50
8.566
3151541CLOVER2
50/50
5.976
315779AE2-040
50/50
3.486
3151611KERR 4
50/50
0.508
3151621KERR 5
50/50
0.508
3151631KERR 6
50/50
0.508
3151641KERR 7
50/50
0.508
3151281ROARAP4
50/50
0.278
3151281ROARAP4
50/50
0.26
941031AE2-094 GEN
Solar/Wind Harmer
70.747
944011AF1-069 GEN
Solar/Wind Harmer
22.167
970673AG2-436 GEN
Solar/Wind Harmer
77.682
970673AG2-436 GEN
Solar/Wind Harmer
39.333
971967AH1-528 GEN
Solar/Wind Harmer
68.625
970085AG2-068 GEN
Solar/Wind Harmer
21.474
970581AG2-369 GEN
Solar/Wind Harmer
18.468
970285AG2-188 GEN
Solar/Wind Harmer
27.712
971845AH1-439 GEN
Solar/Wind Harmer
16.825
315657AE1-056 GEN
Solar/Wind Harmer
11.27
946301AF1-294 GEN
Solar/Wind Harmer
7.632
961791AG1-021 GEN
Solar/Wind Harmer
3.723
970683AG2-441 GEN
Solar/Wind Harmer
22.967
970681AG2-440 GEN
Solar/Wind Harmer
18.373
3144303KENBRDG
Solar/Wind Harmer
-0.023
971443AH1-215 GEN
Solar/Wind Harmer
5.7
316315AB2-025 C
Solar/Wind Harmer
0.757
315814AE2-033 C
Solar/Wind Harmer
26.059
316239AB2-077_GEN
Solar/Wind Harmer
0.842
316238AB2-078_GEN
Solar/Wind Harmer
0.842
970831AG2-522 GEN
Solar/Wind Harmer
13.417
946281AF1-292 GEN
Solar/Wind Harmer
0.596
316087AB2-174 GEN
Solar/Wind Harmer
3.756
3137643SOCKMAN
Solar/Wind Harmer
-0.103
316118AC1-105 GEN
Solar/Wind Harmer
1.777
315607AA1-063A GEN
Solar/Wind Harmer
2.581
3146043SEABORD
Solar/Wind Harmer
-0.025
315652AC1-086 GEN
Solar/Wind Harmer
28.68
957871AF2-081 GEN
Solar/Wind Harmer
12.659
319010AE1-072 C
Solar/Wind Harmer
5.115
3146406KITTY HAWK
Solar/Wind Harmer
0.021
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.016
3145796HORNRTN
Solar/Wind Harmer
-0.08
3145796HORNRTN
Solar/Wind Harmer
-0.01
965291AG1-394 GEN
Solar/Wind Harmer
2.237
313526AB2-022
Solar/Wind Harmer
0.68
316321Z2-027
Solar/Wind Harmer
0.679
3146396TANGLEW
Solar/Wind Harmer
0.463
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
316318V4-068
Solar/Wind Harmer
0.626
3145893MURPHYS
Solar/Wind Harmer
-0.067
3145893MURPHYS
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
316305AF2-043 C
Solar/Wind Harmer
0.755
3151081ELIZAR1
Adder
20.42
3151091ELIZAR2
Adder
20.065
315611Z1-036_GEN2
Solar/Wind Harmer
6.178
3145513AHOSKIE
Solar/Wind Harmer
0.218
961941AG1-037 GEN
Solar/Wind Harmer
0.188
3145513AHOSKIE
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
3152611GOSPORTB
Adder
2.824
3152621GOSPORTC
Adder
2.396
3152601GOSPORTA
Adder
2.211
3145683EARLEYS
Solar/Wind Harmer
-0.049
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
315816AE2-034 GEN
Solar/Wind Harmer
2.011
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
3146206CASHIE
Solar/Wind Harmer
-0.025
970601AG2-382 GEN
Solar/Wind Harmer
10.834
3146033SCOT NK
Solar/Wind Harmer
-0.099
315732AD1-074 GEN1
Solar/Wind Harmer
5.007
315733AD1-074 GEN2
Solar/Wind Harmer
5.007
315735AD1-075 GEN1
Solar/Wind Harmer
2.504
315835AF2-110_GEN
Solar/Wind Harmer
3.076
316319Z2-044 C
Solar/Wind Harmer
1.327
316005AA1-067
Solar/Wind Harmer
0.482
3145746EVERETS
Solar/Wind Harmer
-0.094
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
970181AG2-120 GEN
Solar/Wind Harmer
3.13
957861AF2-080 GEN
Solar/Wind Harmer
10.414
316420AA1-050 GEN
Solar/Wind Harmer
2.716
3145573BETHELC
Solar/Wind Harmer
-0.024
3145573BETHELC
Solar/Wind Harmer
-0.024
316311AC2-079 GEN
Solar/Wind Harmer
11.791
315833AF1-017_GEN
Solar/Wind Harmer
4.435
316349AD2-085 GEN
Solar/Wind Harmer
2.077
3143316POE
Solar/Wind Harmer
-0.087
972265AH1-717 GEN
Adder
13.355
3151201GRAVEL4
Adder
12.519
3151191GRAVEL3
Adder
12.361
3151211GRAVEL5
Adder
12.361
316233AE1-074 FULL
Solar/Wind Helper
0.35
939181AE1-148 GEN
Solar/Wind Harmer
15.561
962561AG1-105 GEN
Solar/Wind Harmer
15.007
964791AG1-342 GEN
Solar/Wind Harmer
5.646
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
316181AB2-040 GEN
Solar/Wind Harmer
3.656
3145593CAROLNA
Solar/Wind Harmer
-0.026
3145593CAROLNA
Solar/Wind Harmer
-0.026
966811AG1-552 GEN
Solar/Wind Harmer
2.899
3145593CAROLNA
Solar/Wind Harmer
0.214
316426AA2-053 GEN
Solar/Wind Harmer
2.588
3145783HORNRTN
Solar/Wind Harmer
3.04
3145783HORNRTN
Solar/Wind Harmer
2.432
3145783HORNRTN
Solar/Wind Harmer
0.76
3145783HORNRTN
Solar/Wind Harmer
0.304
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
3145506HICKORY
Solar/Wind Harmer
-0.101
3145506HICKORY
Solar/Wind Harmer
-0.061
3145506HICKORY
Solar/Wind Harmer
-0.015
316185AD1-033 GEN
Solar/Wind Harmer
2.674
316339AD2-160 GEN
Solar/Wind Harmer
1.708
316018AA1-139 ULT2
Solar/Wind Harmer
2.169
316017AA1-139 ULT1
Solar/Wind Harmer
2.049
3137176SLIGO L2192
Solar/Wind Harmer
-0.1
3146456SLIGO L269
Solar/Wind Harmer
2.987
3130086AYDLETT
Solar/Wind Harmer
-0.101
3145796HORNRTN
Solar/Wind Harmer
-0.075
3146386ELIZ CT
Solar/Wind Harmer
-0.025
3142956BIRDNECK
Solar/Wind Harmer
1.35
316316AC1-027 C
Solar/Wind Harmer
0.771
3145893MURPHYS
Solar/Wind Harmer
0.7
3145893MURPHYS
Solar/Wind Harmer
-0.045
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
316431W1029_GEN1
Solar/Wind Harmer
4.542
316433W1029_GEN2
Solar/Wind Harmer
4.542
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
3146376EDENTON
Solar/Wind Harmer
0.74
3146376EDENTON
Solar/Wind Harmer
0.74
316036AC1-147 C
Solar/Wind Harmer
0.672
3150991CHESPKB
Adder
2.322
3150991CHESPKB
Adder
2.267
315742AE1-103 GEN
Solar/Wind Harmer
2.599
316274AC1-208 GEN
Solar/Wind Harmer
2.674
316065AD1-022 GEN
Solar/Wind Harmer
12.38
3145933PARMELE
Solar/Wind Harmer
-0.048
3145933PARMELE
Solar/Wind Harmer
-0.024
3145493TOT1
Solar/Wind Harmer
0.368
3145453TOT5
Solar/Wind Harmer
0.221
3145603CNETO
Solar/Wind Harmer
0.147
316263AC1-034 GEN
Solar/Wind Harmer
11.133
961601AG1-000A GEN
Solar/Wind Harmer
9.326
316222AC1-221 GEN
Solar/Wind Harmer
2.263
316447AC1-158 HLD
Solar/Wind Helper
2.916
3143526WINTERP
Solar/Wind Helper
1.191
3151031BRUNSWICKG2
50/50
4.23
970413AG2-270 GEN
50/50
26.203
3144293JTRSVLE
50/50
0.895
3151591KERR 2
50/50
0.508
3151261ROARAP2
50/50
0.279
3151391GASTONA
50/50
0.614
3151411GASTONB
50/50
0.614
970917AG2-570 GEN
Solar/Wind Harmer
86.33
970909AG2-566 GEN
Solar/Wind Harmer
3.044
3146926FARMVIL
Solar/Wind Harmer
-0.019
3146776BUCKING
Solar/Wind Harmer
-0.011
316478AD1-087 GEN
Solar/Wind Harmer
2.727
316486AD2-202 GEN
Solar/Wind Harmer
0.799
942461AE2-259 GEN
Solar/Wind Harmer
4.631
3147133PAMPLIN
Solar/Wind Harmer
-0.094
971193AH1-056 GEN
Solar/Wind Harmer
18.784
963181AG1-167 GEN
Solar/Wind Harmer
2.792
959311AF2-222 GEN
Solar/Wind Harmer
30.378
970257AG2-171 GEN
Solar/Wind Harmer
10.87
315785AD2-033 C
Solar/Wind Harmer
6.532
964241AG1-285 GEN
Solar/Wind Harmer
22.181
316131AB2-060 GEN
Solar/Wind Harmer
3.035
3147043LAWRENC
Solar/Wind Harmer
-0.016
966621AG1-532 GEN
Solar/Wind Harmer
0.54
316365GEN2_N
Solar/Wind Harmer
1.787
313506AB2-031 GEN
Solar/Wind Harmer
2.107
315773AC2-141 GEN
Solar/Wind Harmer
10.925
944581AF1-123 GEN
Solar/Wind Harmer
117.317
944601AF1-125 GEN
Solar/Wind Harmer
115.486
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3146456SLIGO L269
Solar/Wind Harmer
-0.025
971153AH1-033 GEN
Solar/Wind Harmer
3.083
316248AF1-058 C
Solar/Wind Harmer
0.761
960061AF2-297 GEN
Solar/Wind Harmer
12.626
3145796HORNRTN
Solar/Wind Harmer
-0.1
3145796HORNRTN
Solar/Wind Harmer
-0.025
316320Y1-086
Solar/Wind Harmer
1.477
3156081AA2-088 GEN
Solar/Wind Harmer
8.171
3146263WOODLND
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.175
3145893MURPHYS
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
957521AF2-046 GEN
Solar/Wind Harmer
19.748
961681AG1-008 GEN
Solar/Wind Harmer
19.748
316435W1029_GEN3
Solar/Wind Harmer
4.542
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3151101ELIZAR3
Adder
20.681
3146173TUNIS
Solar/Wind Harmer
-0.025
316463AE2-346 GEN
Solar/Wind Harmer
0.404
316140AB2-099
Solar/Wind Harmer
0.168
962331AG1-082 GEN
Solar/Wind Harmer
3.119
3146376EDENTON
Solar/Wind Harmer
-0.025
3144873MCLAUGH
Solar/Wind Harmer
-0.001
315614AA2-178 GEN
Solar/Wind Harmer
2.681
316317KELFORD C
Solar/Wind Harmer
1.17
3145823KELFORD
Solar/Wind Harmer
-0.025
3145273HOLLAND
Solar/Wind Harmer
-0.019
3156021HOLLOMANSOL
Solar/Wind Harmer
3.338
971157AH1-035 GEN
Solar/Wind Harmer
3.096
3146206CASHIE
Solar/Wind Harmer
-0.025
315737AD1-076 GEN
Solar/Wind Harmer
4.705
316210AC1-098 GEN
Solar/Wind Harmer
3.877
315724AD1-057 GEN
Solar/Wind Harmer
1.404
3145963POPLR C
Solar/Wind Harmer
-0.024
316327AA2-057 GEN
Solar/Wind Harmer
2.454
3146233WITAKRS
Solar/Wind Harmer
0.503
3146233WITAKRS
Solar/Wind Harmer
-0.016
3145933PARMELE
Solar/Wind Harmer
-0.024
966801AG1-551 GEN
Solar/Wind Harmer
2.999
3138543CONSLDL
Solar/Wind Harmer
-0.016
3144536CHRHLND
Solar/Wind Harmer
-0.004
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
3146073TAR RVR
Solar/Wind Harmer
-0.024
3146083TARBORO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.024
961601AG1-000A GEN
Solar/Wind Harmer
9.444
971683AH1-343 GEN
Solar/Wind Harmer
9.745
316283AC2-100 C
Solar/Wind Harmer
2.093
3151221GRAVEL6
Adder
12.505
3151171GRAVELC
Adder
2.406
3144216WINCHST
Adder
0.613
3150921YORKTN3
Adder
4.045
316313AB2-026
Solar/Wind Helper
0.532
316258AE1-075 C
Solar/Wind Helper
0.479
316405AF2-144 C
Solar/Wind Helper
0.399
316044AC1-158 PL1
Solar/Wind Helper
1.325
316450AC1-158 RIC
Solar/Wind Helper
0.353
970661AG2-428 GEN
Solar/Wind Harmer
1.85
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.197
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.662
MECLTFEXP_MEC->PJM
CLTF
4.586
SIGELTFEXP_SIGE->PJM
CLTF
0.137
CPLELTFEXP_CPLE->PJM
CLTF
14.708
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.937
LAGNLTFEXP_LAGN->PJM
CLTF
9.794
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.485
TVALTFEXP_TVA->PJM
CLTF
4.889
NYPJM->LTFIMP_NY
CLTF
2.27
LGEELTFEXP_LGEE->PJM
CLTF
1.633
WECLTFEXP_WEC->PJM
CLTF
0.839

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.73 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5687.33
MW Contribution:5.15
Bus #Bus NameTypeMW Contribution
3151051BRUNSWICKS1
50/50
17.651
3151021BRUNSWICKG1
50/50
8.505
971451AH1-221 GEN
50/50
25.831
315243AE2-183_GT3
50/50
10.667
3151531CLOVER1
50/50
10.644
3151601KERR 3
50/50
0.604
3151581KERR 1
50/50
0.216
3144293JTRSVLE
50/50
0.914
971629AH1-314 GEN
50/50
19.06
3151561HALLBR1
50/50
0.404
970919AG2-571 GEN
Solar/Wind Harmer
21.586
970087AG2-069 GEN
Solar/Wind Harmer
48.225
957481AF2-042 GEN
Solar/Wind Harmer
144.711
315693AD1-088 GEN
Solar/Wind Harmer
23.762
962491AG1-098 GEN
Solar/Wind Harmer
27.839
315687AD1-152 GEN
Solar/Wind Harmer
0.015
316003AC1-222 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.882
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
20.472
963171AG1-166 GEN
Solar/Wind Harmer
1.443
971563AH1-280 GEN
Solar/Wind Harmer
2.885
3146926FARMVIL
Solar/Wind Harmer
0.151
971065AG2-659 GEN
Solar/Wind Harmer
9.511
316129AC1-054 GEN
Solar/Wind Harmer
0.786
970223AG2-152 GEN
Solar/Wind Harmer
12.908
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.097
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.064
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.115
3146802CHATHAM
Solar/Wind Harmer
0.108
941801AE2-185 GEN
Solar/Wind Harmer
4.622
270030AE2-140 GEN
Solar/Wind Harmer
14.688
3145543BTLEBRO
Solar/Wind Harmer
0.123
3145543BTLEBRO
Solar/Wind Harmer
0.099
316359AB2-059 GEN
Solar/Wind Harmer
0.442
316049AB1-081 GEN
Solar/Wind Harmer
0.704
3142053HEARTS
Solar/Wind Harmer
0.217
316294AC1-161 GEN
Solar/Wind Helper
8.153
316375AC2-012 GEN
Solar/Wind Helper
1.068
3145336SMITFLD
Solar/Wind Helper
1.575
316388AE2-253 GEN
Solar/Wind Helper
1.472
3146456SLIGO L269
Solar/Wind Helper
0.379
316381AD1-082 GEN
Solar/Wind Helper
1.955
316072AD1-144
Solar/Wind Helper
0.428
316246AF1-032 C
Solar/Wind Helper
0.424
316159AE1-175 C
Solar/Wind Helper
0.562
316458AB2-190 GEN2
Solar/Wind Helper
2.107
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.376
3138133OCRAN
Solar/Wind Helper
0.206
3142543TWELFTH
Solar/Wind Helper
0.032
964211AG1-282 GEN
Solar/Wind Helper
0.439
3141726DUNNSVL
Solar/Wind Helper
1.304
316337AD2-073 GEN
Solar/Wind Helper
0.478
3142416OLDCHRC
Solar/Wind Helper
0.816
3142416OLDCHRC
Solar/Wind Helper
0.312
3146516WINFALL
Solar/Wind Helper
1.016
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
3143226MDLTHAN
Solar/Wind Helper
0.3
315800Z1-036_GEN1
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
963041AG1-153 GEN
50/50
17.22
315244AE2-183_ST
50/50
18.443
3151541CLOVER2
50/50
10.593
3151611KERR 4
50/50
0.604
3151621KERR 5
50/50
0.604
3151631KERR 6
50/50
0.604
3151641KERR 7
50/50
0.604
971967AH1-528 GEN
Solar/Wind Harmer
109.53
970673AG2-436 GEN
Solar/Wind Harmer
137.75
970673AG2-436 GEN
Solar/Wind Harmer
91.833
941031AE2-094 GEN
Solar/Wind Harmer
118.914
944011AF1-069 GEN
Solar/Wind Harmer
38.854
970085AG2-068 GEN
Solar/Wind Harmer
32.15
970581AG2-369 GEN
Solar/Wind Harmer
27.649
3147173SINAI
Solar/Wind Harmer
0.345
3147243WELCO
Solar/Wind Harmer
0.216
316118AC1-105 GEN
Solar/Wind Harmer
0.86
970865AG2-541 GEN
Solar/Wind Harmer
10.119
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.678
3144303KENBRDG
Solar/Wind Harmer
0.222
970683AG2-441 GEN
Solar/Wind Harmer
18.278
970681AG2-440 GEN
Solar/Wind Harmer
14.623
946301AF1-294 GEN
Solar/Wind Harmer
5.338
961791AG1-021 GEN
Solar/Wind Harmer
2.597
315657AE1-056 GEN
Solar/Wind Harmer
9.239
316123AC1-075 GEN
Solar/Wind Harmer
0.351
970165AG2-112 GEN
Solar/Wind Harmer
2.08
970163AG2-111 GEN
Solar/Wind Harmer
1.985
970831AG2-522 GEN
Solar/Wind Harmer
8.286
970285AG2-188 GEN
Solar/Wind Harmer
14.461
971845AH1-439 GEN
Solar/Wind Harmer
7.612
270069AE2-166 C O1
Solar/Wind Harmer
0.005
3143316POE
Solar/Wind Helper
1.64
319010AE1-072 C
Solar/Wind Helper
4.299
316369SG1_INVT
Solar/Wind Helper
1.8
316305AF2-043 C
Solar/Wind Helper
0.499
316132AB2-190 GEN1
Solar/Wind Helper
2.107
957831AF2-077 GEN
Solar/Wind Helper
0.495
316349AD2-085 GEN
Solar/Wind Helper
1.649
313526AB2-022
Solar/Wind Helper
0.533
957601AF2-054 GEN
Solar/Wind Helper
0.467
3141873WAN 176
Solar/Wind Helper
0.07
315662AE1-191 GEN
Solar/Wind Helper
1.865
315666AE1-190 GEN
Solar/Wind Helper
0.466
316059AD1-063 C
Solar/Wind Helper
0.348
3141913WHIT STONE
Solar/Wind Helper
0.345
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.137
3146486SUNBURY
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.341
316321Z2-027
Solar/Wind Helper
0.514
3145176PASQUOTANK
Solar/Wind Helper
0.209
316315AB2-025 C
Solar/Wind Helper
0.507
3141813NORNECK
Solar/Wind Helper
0.325
316312AB1-027
Solar/Wind Helper
0.597
316233AE1-074 FULL
Solar/Wind Helper
0.469
316223AC1-118
Solar/Wind Helper
0.466
315611Z1-036_GEN2
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
3151031BRUNSWICKG2
50/50
8.505
970413AG2-270 GEN
50/50
46.449
3151591KERR 2
50/50
0.604
3144293JTRSVLE
50/50
0.914
970917AG2-570 GEN
Solar/Wind Harmer
53.965
316478AD1-087 GEN
Solar/Wind Harmer
1.733
316486AD2-202 GEN
Solar/Wind Harmer
0.509
970909AG2-566 GEN
Solar/Wind Harmer
3.791
316248AF1-058 C
Solar/Wind Harmer
0.003
960061AF2-297 GEN
Solar/Wind Harmer
14.727
971683AH1-343 GEN
Solar/Wind Harmer
11.379
316283AC2-100 C
Solar/Wind Harmer
0.592
316131AB2-060 GEN
Solar/Wind Harmer
0.901
964241AG1-285 GEN
Solar/Wind Harmer
18.92
315785AD2-033 C
Solar/Wind Harmer
2.274
970257AG2-171 GEN
Solar/Wind Harmer
8.9
959311AF2-222 GEN
Solar/Wind Harmer
24.62
963181AG1-167 GEN
Solar/Wind Harmer
1.082
3147133PAMPLIN
Solar/Wind Harmer
0.841
971193AH1-056 GEN
Solar/Wind Harmer
16.311
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
3146926FARMVIL
Solar/Wind Harmer
0.151
3146776BUCKING
Solar/Wind Harmer
0.058
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
1.012
3147312GRETNA
Solar/Wind Harmer
0.029
941821AE2-187 GEN
Solar/Wind Harmer
4.622
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.004
3145543BTLEBRO
Solar/Wind Harmer
0.123
3145543BTLEBRO
Solar/Wind Harmer
0.123
971623AH1-311 GEN
Solar/Wind Harmer
0.246
961601AG1-000A GEN
Solar/Wind Harmer
8.544
315773AC2-141 GEN
Solar/Wind Helper
9.595
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3145336SMITFLD
Solar/Wind Helper
0.157
315839AE2-212 C
Solar/Wind Helper
0.523
3146456SLIGO L269
Solar/Wind Helper
0.379
316382AG1-145 C
Solar/Wind Helper
0.498
316320Y1-086
Solar/Wind Helper
0.156
316156AD2-030 GEN
Solar/Wind Helper
0.525
316280AD1-041 GEN
Solar/Wind Helper
1.166
3142946ENON
Solar/Wind Helper
0.114
316484AD2-074 GEN
Solar/Wind Helper
0.648
316404AE1-155 C
Solar/Wind Helper
2.8
316435W1029_GEN3
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3141906WESTMOR
Solar/Wind Helper
0.122
316473AC1-191 GEN
Solar/Wind Helper
1.829
3146626S HERTFORD
Solar/Wind Helper
0.296
3145273HOLLAND
Solar/Wind Helper
0.201
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.24
3151041BRUNSWICKG3
50/50
8.505
972187AH1-678 GEN
50/50
19.517
315242AE2-183_GT2
50/50
10.667
315241AE2-183_GT1
50/50
10.602
972185AH1-677 GEN
50/50
38.457
970533AG2-339 GEN
50/50
57.391
970531AG2-338 GEN
50/50
22.956
3152661PLYWOOD A
50/50
0.751
970535AG2-341 GEN
50/50
5.149
3144293JTRSVLE
50/50
0.914
3144293JTRSVLE
50/50
0.769
970933AG2-581 GEN
Solar/Wind Harmer
51.542
970099AG2-077 GEN
Solar/Wind Harmer
57.884
971741AH1-377 GEN
Solar/Wind Harmer
38.437
970301AG2-198 GEN
Solar/Wind Harmer
15.165
3146843MT LREL
Solar/Wind Harmer
0.321
3146843MT LREL
Solar/Wind Harmer
0.321
964791AG1-342 GEN
Solar/Wind Harmer
6.159
962561AG1-105 GEN
Solar/Wind Harmer
15.15
316222AC1-221 GEN
Solar/Wind Harmer
1.267
939181AE1-148 GEN
Solar/Wind Harmer
13.97
313527AB2-043 GEN
Solar/Wind Harmer
0.004
970323AG2-213 GEN
Solar/Wind Harmer
11.867
971775AH1-396 GEN
Solar/Wind Harmer
0.445
316034AC1-036 C
Solar/Wind Harmer
0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.246
963191AG1-168 GEN
Solar/Wind Harmer
1.082
3147133PAMPLIN
Solar/Wind Harmer
0.268
3147133PAMPLIN
Solar/Wind Harmer
0.214
942751AE2-291 GEN
Solar/Wind Harmer
12.744
270013AE1-250 PV
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.64
3146776BUCKING
Solar/Wind Harmer
0.052
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
3.595
316263AC1-034 GEN
Solar/Wind Harmer
4.676
961601AG1-000A GEN
Solar/Wind Harmer
2.136
316036AC1-147 C
Solar/Wind Helper
0.621
3142956BIRDNECK
Solar/Wind Helper
0.272
316316AC1-027 C
Solar/Wind Helper
0.638
316185AD1-033 GEN
Solar/Wind Helper
1.893
3145506HICKORY
Solar/Wind Helper
1.587
3145506HICKORY
Solar/Wind Helper
0.952
3145506HICKORY
Solar/Wind Helper
0.238
316236AE1-162_GEN
Solar/Wind Helper
0.529
316339AD2-160 GEN
Solar/Wind Helper
1.472
316018AA1-139 ULT2
Solar/Wind Helper
1.65
316017AA1-139 ULT1
Solar/Wind Helper
1.754
3137176SLIGO L2192
Solar/Wind Helper
1.508
3130086AYDLETT
Solar/Wind Helper
1.498
316033AB2-134 GEN
Solar/Wind Helper
1.287
315697AD1-025 GEN
Solar/Wind Helper
4.277
316240AF1-291 C
Solar/Wind Helper
0.501
3146386ELIZ CT
Solar/Wind Helper
0.35
3142946ENON
Solar/Wind Helper
0.034
316487AF1-042 GEN
Solar/Wind Helper
0.339
3144356SAPONY
Solar/Wind Helper
0.597
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.305
316431W1029_GEN1
Solar/Wind Helper
1.295
316433W1029_GEN2
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
966871AG1-558 GEN
Solar/Wind Helper
0.403
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
316468AD1-105 GEN
Solar/Wind Helper
1.402
315742AE1-103 GEN
Solar/Wind Helper
0.368
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.447
MECLTFEXP_MEC->PJM
CLTF
7.78
SIGELTFEXP_SIGE->PJM
CLTF
0.233
CPLELTFEXP_CPLE->PJM
CLTF
20.639
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.343
LAGNLTFEXP_LAGN->PJM
CLTF
15.403
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.288
TVALTFEXP_TVA->PJM
CLTF
7.684
NYPJM->LTFIMP_NY
CLTF
2.484
LGEELTFEXP_LGEE->PJM
CLTF
2.833
WECLTFEXP_WEC->PJM
CLTF
1.482
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.78 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5445.28
MW Contribution:5.15
Bus #Bus NameTypeMW Contribution
963041AG1-153 GEN
50/50
17.22
315244AE2-183_ST
50/50
18.443
3151541CLOVER2
50/50
10.593
3151611KERR 4
50/50
0.604
3151621KERR 5
50/50
0.604
3151631KERR 6
50/50
0.604
3151641KERR 7
50/50
0.604
971967AH1-528 GEN
Solar/Wind Harmer
109.53
970673AG2-436 GEN
Solar/Wind Harmer
137.75
970673AG2-436 GEN
Solar/Wind Harmer
91.833
970085AG2-068 GEN
Solar/Wind Harmer
32.15
970581AG2-369 GEN
Solar/Wind Harmer
27.649
3147173SINAI
Solar/Wind Harmer
0.345
3147243WELCO
Solar/Wind Harmer
0.216
316118AC1-105 GEN
Solar/Wind Harmer
0.86
970865AG2-541 GEN
Solar/Wind Harmer
10.119
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.678
3144303KENBRDG
Solar/Wind Harmer
0.222
970683AG2-441 GEN
Solar/Wind Harmer
18.278
970681AG2-440 GEN
Solar/Wind Harmer
14.623
946301AF1-294 GEN
Solar/Wind Harmer
5.338
961791AG1-021 GEN
Solar/Wind Harmer
2.597
315657AE1-056 GEN
Solar/Wind Harmer
9.239
316123AC1-075 GEN
Solar/Wind Harmer
0.351
970165AG2-112 GEN
Solar/Wind Harmer
2.08
970163AG2-111 GEN
Solar/Wind Harmer
1.985
970831AG2-522 GEN
Solar/Wind Harmer
8.286
970285AG2-188 GEN
Solar/Wind Harmer
14.461
971845AH1-439 GEN
Solar/Wind Harmer
7.612
270069AE2-166 C O1
Solar/Wind Harmer
0.005
3143316POE
Solar/Wind Helper
1.64
319010AE1-072 C
Solar/Wind Helper
4.299
316369SG1_INVT
Solar/Wind Helper
1.8
316305AF2-043 C
Solar/Wind Helper
0.499
316132AB2-190 GEN1
Solar/Wind Helper
2.107
957831AF2-077 GEN
Solar/Wind Helper
0.495
316349AD2-085 GEN
Solar/Wind Helper
1.649
313526AB2-022
Solar/Wind Helper
0.533
957601AF2-054 GEN
Solar/Wind Helper
0.467
3141873WAN 176
Solar/Wind Helper
0.07
315662AE1-191 GEN
Solar/Wind Helper
1.865
315666AE1-190 GEN
Solar/Wind Helper
0.466
316059AD1-063 C
Solar/Wind Helper
0.348
3141913WHIT STONE
Solar/Wind Helper
0.345
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.137
3146486SUNBURY
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.341
316321Z2-027
Solar/Wind Helper
0.514
3145176PASQUOTANK
Solar/Wind Helper
0.209
316315AB2-025 C
Solar/Wind Helper
0.507
3141813NORNECK
Solar/Wind Helper
0.325
316312AB1-027
Solar/Wind Helper
0.597
316233AE1-074 FULL
Solar/Wind Helper
0.469
316223AC1-118
Solar/Wind Helper
0.466
315611Z1-036_GEN2
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
3151031BRUNSWICKG2
50/50
8.505
970413AG2-270 GEN
50/50
46.449
3151591KERR 2
50/50
0.604
3144293JTRSVLE
50/50
0.914
970917AG2-570 GEN
Solar/Wind Harmer
53.965
316478AD1-087 GEN
Solar/Wind Harmer
1.733
316486AD2-202 GEN
Solar/Wind Harmer
0.509
970909AG2-566 GEN
Solar/Wind Harmer
3.791
316248AF1-058 C
Solar/Wind Harmer
0.003
960061AF2-297 GEN
Solar/Wind Harmer
14.727
971683AH1-343 GEN
Solar/Wind Harmer
11.379
316283AC2-100 C
Solar/Wind Harmer
0.592
316131AB2-060 GEN
Solar/Wind Harmer
0.901
964241AG1-285 GEN
Solar/Wind Harmer
18.92
315785AD2-033 C
Solar/Wind Harmer
2.274
970257AG2-171 GEN
Solar/Wind Harmer
8.9
959311AF2-222 GEN
Solar/Wind Harmer
24.62
963181AG1-167 GEN
Solar/Wind Harmer
1.082
3147133PAMPLIN
Solar/Wind Harmer
0.841
971193AH1-056 GEN
Solar/Wind Harmer
16.311
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
3146926FARMVIL
Solar/Wind Harmer
0.151
3146776BUCKING
Solar/Wind Harmer
0.058
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
1.012
3147312GRETNA
Solar/Wind Harmer
0.029
941821AE2-187 GEN
Solar/Wind Harmer
4.622
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.004
3145543BTLEBRO
Solar/Wind Harmer
0.123
3145543BTLEBRO
Solar/Wind Harmer
0.123
971623AH1-311 GEN
Solar/Wind Harmer
0.246
961601AG1-000A GEN
Solar/Wind Harmer
8.544
315773AC2-141 GEN
Solar/Wind Helper
9.595
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3145336SMITFLD
Solar/Wind Helper
0.157
315839AE2-212 C
Solar/Wind Helper
0.523
3146456SLIGO L269
Solar/Wind Helper
0.379
316382AG1-145 C
Solar/Wind Helper
0.498
316320Y1-086
Solar/Wind Helper
0.156
316156AD2-030 GEN
Solar/Wind Helper
0.525
316280AD1-041 GEN
Solar/Wind Helper
1.166
3142946ENON
Solar/Wind Helper
0.114
316484AD2-074 GEN
Solar/Wind Helper
0.648
316404AE1-155 C
Solar/Wind Helper
2.8
316435W1029_GEN3
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3141906WESTMOR
Solar/Wind Helper
0.122
316473AC1-191 GEN
Solar/Wind Helper
1.829
3146626S HERTFORD
Solar/Wind Helper
0.296
3145273HOLLAND
Solar/Wind Helper
0.201
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.24
3151051BRUNSWICKS1
50/50
17.651
3151021BRUNSWICKG1
50/50
8.505
971451AH1-221 GEN
50/50
25.831
315243AE2-183_GT3
50/50
10.667
3151531CLOVER1
50/50
10.644
3151601KERR 3
50/50
0.604
3151581KERR 1
50/50
0.216
3144293JTRSVLE
50/50
0.914
971629AH1-314 GEN
50/50
19.06
3151561HALLBR1
50/50
0.404
970919AG2-571 GEN
Solar/Wind Harmer
21.586
970087AG2-069 GEN
Solar/Wind Harmer
48.225
957481AF2-042 GEN
Solar/Wind Harmer
144.711
315693AD1-088 GEN
Solar/Wind Harmer
23.762
962491AG1-098 GEN
Solar/Wind Harmer
27.839
315687AD1-152 GEN
Solar/Wind Harmer
0.015
316003AC1-222 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.882
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
20.472
963171AG1-166 GEN
Solar/Wind Harmer
1.443
971563AH1-280 GEN
Solar/Wind Harmer
2.885
3146926FARMVIL
Solar/Wind Harmer
0.151
971065AG2-659 GEN
Solar/Wind Harmer
9.511
316129AC1-054 GEN
Solar/Wind Harmer
0.786
970223AG2-152 GEN
Solar/Wind Harmer
12.908
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.097
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.064
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.115
3146802CHATHAM
Solar/Wind Harmer
0.108
941801AE2-185 GEN
Solar/Wind Harmer
4.622
270030AE2-140 GEN
Solar/Wind Harmer
14.688
3145543BTLEBRO
Solar/Wind Harmer
0.123
3145543BTLEBRO
Solar/Wind Harmer
0.099
316359AB2-059 GEN
Solar/Wind Harmer
0.442
316049AB1-081 GEN
Solar/Wind Harmer
0.704
3142053HEARTS
Solar/Wind Harmer
0.217
316294AC1-161 GEN
Solar/Wind Helper
8.153
316375AC2-012 GEN
Solar/Wind Helper
1.068
3145336SMITFLD
Solar/Wind Helper
1.575
316388AE2-253 GEN
Solar/Wind Helper
1.472
3146456SLIGO L269
Solar/Wind Helper
0.379
316381AD1-082 GEN
Solar/Wind Helper
1.955
316072AD1-144
Solar/Wind Helper
0.428
316246AF1-032 C
Solar/Wind Helper
0.424
316159AE1-175 C
Solar/Wind Helper
0.562
316458AB2-190 GEN2
Solar/Wind Helper
2.107
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.376
3138133OCRAN
Solar/Wind Helper
0.206
3142543TWELFTH
Solar/Wind Helper
0.032
964211AG1-282 GEN
Solar/Wind Helper
0.439
3141726DUNNSVL
Solar/Wind Helper
1.304
316337AD2-073 GEN
Solar/Wind Helper
0.478
3142416OLDCHRC
Solar/Wind Helper
0.816
3142416OLDCHRC
Solar/Wind Helper
0.312
3146516WINFALL
Solar/Wind Helper
1.016
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
3143226MDLTHAN
Solar/Wind Helper
0.3
315800Z1-036_GEN1
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3151041BRUNSWICKG3
50/50
8.505
972187AH1-678 GEN
50/50
19.517
315242AE2-183_GT2
50/50
10.667
315241AE2-183_GT1
50/50
10.602
972185AH1-677 GEN
50/50
38.457
3152661PLYWOOD A
50/50
0.751
970535AG2-341 GEN
50/50
5.149
3144293JTRSVLE
50/50
0.914
3144293JTRSVLE
50/50
0.769
970933AG2-581 GEN
Solar/Wind Harmer
51.542
970099AG2-077 GEN
Solar/Wind Harmer
57.884
971741AH1-377 GEN
Solar/Wind Harmer
38.437
970301AG2-198 GEN
Solar/Wind Harmer
15.165
3146843MT LREL
Solar/Wind Harmer
0.321
3146843MT LREL
Solar/Wind Harmer
0.321
964791AG1-342 GEN
Solar/Wind Harmer
6.159
962561AG1-105 GEN
Solar/Wind Harmer
15.15
316222AC1-221 GEN
Solar/Wind Harmer
1.267
939181AE1-148 GEN
Solar/Wind Harmer
13.97
313527AB2-043 GEN
Solar/Wind Harmer
0.004
970323AG2-213 GEN
Solar/Wind Harmer
11.867
971775AH1-396 GEN
Solar/Wind Harmer
0.445
316034AC1-036 C
Solar/Wind Harmer
0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.246
963191AG1-168 GEN
Solar/Wind Harmer
1.082
3147133PAMPLIN
Solar/Wind Harmer
0.268
3147133PAMPLIN
Solar/Wind Harmer
0.214
942751AE2-291 GEN
Solar/Wind Harmer
12.744
270013AE1-250 PV
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.64
3146776BUCKING
Solar/Wind Harmer
0.052
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
3.595
316263AC1-034 GEN
Solar/Wind Harmer
4.676
961601AG1-000A GEN
Solar/Wind Harmer
2.136
316036AC1-147 C
Solar/Wind Helper
0.621
3142956BIRDNECK
Solar/Wind Helper
0.272
316316AC1-027 C
Solar/Wind Helper
0.638
316185AD1-033 GEN
Solar/Wind Helper
1.893
3145506HICKORY
Solar/Wind Helper
1.587
3145506HICKORY
Solar/Wind Helper
0.952
3145506HICKORY
Solar/Wind Helper
0.238
316236AE1-162_GEN
Solar/Wind Helper
0.529
316339AD2-160 GEN
Solar/Wind Helper
1.472
316018AA1-139 ULT2
Solar/Wind Helper
1.65
316017AA1-139 ULT1
Solar/Wind Helper
1.754
3137176SLIGO L2192
Solar/Wind Helper
1.508
3130086AYDLETT
Solar/Wind Helper
1.498
316033AB2-134 GEN
Solar/Wind Helper
1.287
315697AD1-025 GEN
Solar/Wind Helper
4.277
316240AF1-291 C
Solar/Wind Helper
0.501
3146386ELIZ CT
Solar/Wind Helper
0.35
3142946ENON
Solar/Wind Helper
0.034
316487AF1-042 GEN
Solar/Wind Helper
0.339
3144356SAPONY
Solar/Wind Helper
0.597
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.305
316431W1029_GEN1
Solar/Wind Helper
1.295
316433W1029_GEN2
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
966871AG1-558 GEN
Solar/Wind Helper
0.403
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
316468AD1-105 GEN
Solar/Wind Helper
1.402
315742AE1-103 GEN
Solar/Wind Helper
0.368
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.447
MECLTFEXP_MEC->PJM
CLTF
7.78
SIGELTFEXP_SIGE->PJM
CLTF
0.233
CPLELTFEXP_CPLE->PJM
CLTF
20.639
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.343
LAGNLTFEXP_LAGN->PJM
CLTF
15.403
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.288
TVALTFEXP_TVA->PJM
CLTF
7.684
NYPJM->LTFIMP_NY
CLTF
2.484
LGEELTFEXP_LGEE->PJM
CLTF
2.833
WECLTFEXP_WEC->PJM
CLTF
1.482
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 58572_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 58572_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.04 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:6196.95
MW Contribution:5.15
Bus #Bus NameTypeMW Contribution
3151051BRUNSWICKS1
50/50
17.651
3151021BRUNSWICKG1
50/50
8.505
971451AH1-221 GEN
50/50
25.831
315243AE2-183_GT3
50/50
10.667
3151531CLOVER1
50/50
10.644
3151601KERR 3
50/50
0.604
3151581KERR 1
50/50
0.216
3144293JTRSVLE
50/50
0.914
971629AH1-314 GEN
50/50
19.06
3151561HALLBR1
50/50
0.404
970919AG2-571 GEN
Solar/Wind Harmer
21.586
970087AG2-069 GEN
Solar/Wind Harmer
63.496
957481AF2-042 GEN
Solar/Wind Harmer
190.536
315693AD1-088 GEN
Solar/Wind Harmer
27.811
962491AG1-098 GEN
Solar/Wind Harmer
36.654
315687AD1-152 GEN
Solar/Wind Harmer
6.022
316003AC1-222 GEN
Solar/Wind Harmer
3.575
970401AG2-262 GEN
Solar/Wind Harmer
2.352
316237AB2-079_GEN
Solar/Wind Harmer
0.978
970685AG2-442 GEN
Solar/Wind Harmer
26.954
963171AG1-166 GEN
Solar/Wind Harmer
3.799
971563AH1-280 GEN
Solar/Wind Harmer
3.799
3146926FARMVIL
Solar/Wind Harmer
-0.017
971065AG2-659 GEN
Solar/Wind Harmer
12.523
316129AC1-054 GEN
Solar/Wind Harmer
2.059
970223AG2-152 GEN
Solar/Wind Harmer
18.408
270016AE1-250 BESS
Solar/Wind Harmer
3.042
3147123OTTER R
Solar/Wind Harmer
-0.011
316322AB2-045
Solar/Wind Harmer
0.605
3146776BUCKING
Solar/Wind Harmer
-0.007
270574AD1-017 GEN2
Solar/Wind Harmer
5.998
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
941801AE2-185 GEN
Solar/Wind Harmer
6.086
270030AE2-140 GEN
Solar/Wind Harmer
21.053
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3151041BRUNSWICKG3
50/50
8.505
972187AH1-678 GEN
50/50
19.517
315242AE2-183_GT2
50/50
10.667
315241AE2-183_GT1
50/50
10.602
972185AH1-677 GEN
50/50
38.457
970533AG2-339 GEN
50/50
57.391
970531AG2-338 GEN
50/50
22.956
3152661PLYWOOD A
50/50
0.751
970535AG2-341 GEN
50/50
5.149
3144293JTRSVLE
50/50
0.914
3144293JTRSVLE
50/50
0.769
970933AG2-581 GEN
Solar/Wind Harmer
67.863
970099AG2-077 GEN
Solar/Wind Harmer
76.214
971741AH1-377 GEN
Solar/Wind Harmer
50.609
970301AG2-198 GEN
Solar/Wind Harmer
19.968
3146843MT LREL
Solar/Wind Harmer
-0.036
3146843MT LREL
Solar/Wind Harmer
-0.036
964791AG1-342 GEN
Solar/Wind Harmer
7.699
962561AG1-105 GEN
Solar/Wind Harmer
19.948
316222AC1-221 GEN
Solar/Wind Harmer
3.472
939181AE1-148 GEN
Solar/Wind Harmer
18.394
313527AB2-043 GEN
Solar/Wind Harmer
5.237
970323AG2-213 GEN
Solar/Wind Harmer
15.625
971775AH1-396 GEN
Solar/Wind Harmer
2.225
316034AC1-036 C
Solar/Wind Harmer
0.579
958211AF2-115 GEN
Solar/Wind Harmer
4.748
963191AG1-168 GEN
Solar/Wind Harmer
2.849
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
942751AE2-291 GEN
Solar/Wind Harmer
16.78
270013AE1-250 PV
Solar/Wind Harmer
3.042
3146776BUCKING
Solar/Wind Harmer
-0.072
3146776BUCKING
Solar/Wind Harmer
-0.006
316217AC1-145 GEN
Solar/Wind Harmer
2.634
316197AC1-042 GEN
Solar/Wind Harmer
1.997
942671AE2-283 GEN
Solar/Wind Harmer
5.376
316263AC1-034 GEN
Solar/Wind Harmer
6.481
961601AG1-000A GEN
Solar/Wind Harmer
5.306
316036AC1-147 C
Solar/Wind Helper
0.621
3142956BIRDNECK
Solar/Wind Helper
0.272
316316AC1-027 C
Solar/Wind Helper
0.638
316185AD1-033 GEN
Solar/Wind Helper
1.893
3145506HICKORY
Solar/Wind Helper
1.587
3145506HICKORY
Solar/Wind Helper
0.952
3145506HICKORY
Solar/Wind Helper
0.238
316236AE1-162_GEN
Solar/Wind Helper
0.529
316339AD2-160 GEN
Solar/Wind Helper
1.472
316018AA1-139 ULT2
Solar/Wind Helper
1.65
316017AA1-139 ULT1
Solar/Wind Helper
1.754
3137176SLIGO L2192
Solar/Wind Helper
1.508
3130086AYDLETT
Solar/Wind Helper
1.498
316033AB2-134 GEN
Solar/Wind Helper
1.287
315697AD1-025 GEN
Solar/Wind Helper
4.277
316240AF1-291 C
Solar/Wind Helper
0.501
3146386ELIZ CT
Solar/Wind Helper
0.35
3142946ENON
Solar/Wind Helper
0.034
316487AF1-042 GEN
Solar/Wind Helper
0.339
3144356SAPONY
Solar/Wind Helper
0.597
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.305
316431W1029_GEN1
Solar/Wind Helper
1.295
316433W1029_GEN2
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
966871AG1-558 GEN
Solar/Wind Helper
0.403
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
316468AD1-105 GEN
Solar/Wind Helper
1.402
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.864
316049AB1-081 GEN
Solar/Wind Harmer
1.492
3142053HEARTS
Solar/Wind Harmer
0.163
316294AC1-161 GEN
Solar/Wind Helper
8.153
316375AC2-012 GEN
Solar/Wind Helper
1.068
3145336SMITFLD
Solar/Wind Helper
1.575
316388AE2-253 GEN
Solar/Wind Helper
1.472
3146456SLIGO L269
Solar/Wind Helper
0.379
316381AD1-082 GEN
Solar/Wind Helper
1.955
316072AD1-144
Solar/Wind Helper
0.428
316246AF1-032 C
Solar/Wind Helper
0.424
316159AE1-175 C
Solar/Wind Helper
0.562
316458AB2-190 GEN2
Solar/Wind Helper
2.107
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.376
3138133OCRAN
Solar/Wind Helper
0.206
3142543TWELFTH
Solar/Wind Helper
0.032
964211AG1-282 GEN
Solar/Wind Helper
0.439
3141726DUNNSVL
Solar/Wind Helper
1.304
316337AD2-073 GEN
Solar/Wind Helper
0.478
3142416OLDCHRC
Solar/Wind Helper
0.816
3142416OLDCHRC
Solar/Wind Helper
0.312
3146516WINFALL
Solar/Wind Helper
1.016
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
3143226MDLTHAN
Solar/Wind Helper
0.3
315800Z1-036_GEN1
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
315742AE1-103 GEN
Solar/Wind Helper
0.368
3151031BRUNSWICKG2
50/50
8.505
970413AG2-270 GEN
50/50
46.449
3151591KERR 2
50/50
0.604
3144293JTRSVLE
50/50
0.914
970917AG2-570 GEN
Solar/Wind Harmer
170.53
316478AD1-087 GEN
Solar/Wind Harmer
4.831
316486AD2-202 GEN
Solar/Wind Harmer
1.415
970909AG2-566 GEN
Solar/Wind Harmer
3.791
316248AF1-058 C
Solar/Wind Harmer
1.169
960061AF2-297 GEN
Solar/Wind Harmer
19.391
971683AH1-343 GEN
Solar/Wind Harmer
14.982
316283AC2-100 C
Solar/Wind Harmer
3.205
316131AB2-060 GEN
Solar/Wind Harmer
3.471
964241AG1-285 GEN
Solar/Wind Harmer
24.911
315785AD2-033 C
Solar/Wind Harmer
7.122
970257AG2-171 GEN
Solar/Wind Harmer
11.718
959311AF2-222 GEN
Solar/Wind Harmer
32.481
963181AG1-167 GEN
Solar/Wind Harmer
2.849
3147133PAMPLIN
Solar/Wind Harmer
-0.094
971193AH1-056 GEN
Solar/Wind Harmer
18.811
942461AE2-259 GEN
Solar/Wind Harmer
4.399
3146926FARMVIL
Solar/Wind Harmer
-0.017
3146776BUCKING
Solar/Wind Harmer
-0.006
270018AE2-047 C O1
Solar/Wind Harmer
1.466
270197AD1-017 GEN1
Solar/Wind Harmer
1.802
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
6.086
943811AF1-049 GEN
Solar/Wind Harmer
4.09
270336AE1-100 GEN
Solar/Wind Harmer
1.669
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
5.373
315773AC2-141 GEN
Solar/Wind Helper
9.595
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3145336SMITFLD
Solar/Wind Helper
0.157
315839AE2-212 C
Solar/Wind Helper
0.523
3146456SLIGO L269
Solar/Wind Helper
0.379
316382AG1-145 C
Solar/Wind Helper
0.498
316320Y1-086
Solar/Wind Helper
0.156
316156AD2-030 GEN
Solar/Wind Helper
0.525
316280AD1-041 GEN
Solar/Wind Helper
1.166
3142946ENON
Solar/Wind Helper
0.114
316484AD2-074 GEN
Solar/Wind Helper
0.648
316404AE1-155 C
Solar/Wind Helper
2.8
316435W1029_GEN3
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3141906WESTMOR
Solar/Wind Helper
0.122
316473AC1-191 GEN
Solar/Wind Helper
1.829
3146626S HERTFORD
Solar/Wind Helper
0.296
3145273HOLLAND
Solar/Wind Helper
0.201
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.24
963041AG1-153 GEN
50/50
17.22
315244AE2-183_ST
50/50
18.443
3151541CLOVER2
50/50
10.593
3151611KERR 4
50/50
0.604
3151621KERR 5
50/50
0.604
3151631KERR 6
50/50
0.604
3151641KERR 7
50/50
0.604
971967AH1-528 GEN
Solar/Wind Harmer
144.6
970673AG2-436 GEN
Solar/Wind Harmer
152.413
970673AG2-436 GEN
Solar/Wind Harmer
77.171
941031AE2-094 GEN
Solar/Wind Harmer
136.017
944011AF1-069 GEN
Solar/Wind Harmer
42.619
970085AG2-068 GEN
Solar/Wind Harmer
42.331
970581AG2-369 GEN
Solar/Wind Harmer
36.404
3147173SINAI
Solar/Wind Harmer
-0.039
3147243WELCO
Solar/Wind Harmer
-0.024
316118AC1-105 GEN
Solar/Wind Harmer
2.575
970865AG2-541 GEN
Solar/Wind Harmer
13.323
316239AB2-077_GEN
Solar/Wind Harmer
0.978
316238AB2-078_GEN
Solar/Wind Harmer
0.978
971443AH1-215 GEN
Solar/Wind Harmer
6.159
3144303KENBRDG
Solar/Wind Harmer
-0.025
970683AG2-441 GEN
Solar/Wind Harmer
24.066
970681AG2-440 GEN
Solar/Wind Harmer
19.253
946301AF1-294 GEN
Solar/Wind Harmer
7.788
961791AG1-021 GEN
Solar/Wind Harmer
3.799
315657AE1-056 GEN
Solar/Wind Harmer
11.287
316123AC1-075 GEN
Solar/Wind Harmer
3.111
970165AG2-112 GEN
Solar/Wind Harmer
2.739
970163AG2-111 GEN
Solar/Wind Harmer
2.613
270455AD2-022 GEN
Solar/Wind Harmer
5.008
270457AD2-023 GEN
Solar/Wind Harmer
2.539
970831AG2-522 GEN
Solar/Wind Harmer
10.909
970285AG2-188 GEN
Solar/Wind Harmer
17.971
971845AH1-439 GEN
Solar/Wind Harmer
10.023
270069AE2-166 C O1
Solar/Wind Harmer
2.578
3143316POE
Solar/Wind Helper
1.64
319010AE1-072 C
Solar/Wind Helper
4.299
316369SG1_INVT
Solar/Wind Helper
1.8
316305AF2-043 C
Solar/Wind Helper
0.499
316132AB2-190 GEN1
Solar/Wind Helper
2.107
957831AF2-077 GEN
Solar/Wind Helper
0.495
316349AD2-085 GEN
Solar/Wind Helper
1.649
313526AB2-022
Solar/Wind Helper
0.533
957601AF2-054 GEN
Solar/Wind Helper
0.467
3141873WAN 176
Solar/Wind Helper
0.07
315662AE1-191 GEN
Solar/Wind Helper
1.865
315666AE1-190 GEN
Solar/Wind Helper
0.466
316059AD1-063 C
Solar/Wind Helper
0.348
3141913WHIT STONE
Solar/Wind Helper
0.345
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.137
3146486SUNBURY
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.341
316321Z2-027
Solar/Wind Helper
0.514
3145176PASQUOTANK
Solar/Wind Helper
0.209
316315AB2-025 C
Solar/Wind Helper
0.507
3141813NORNECK
Solar/Wind Helper
0.325
316312AB1-027
Solar/Wind Helper
0.597
316233AE1-074 FULL
Solar/Wind Helper
0.469
316223AC1-118
Solar/Wind Helper
0.466
315611Z1-036_GEN2
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.447
MECLTFEXP_MEC->PJM
CLTF
7.78
SIGELTFEXP_SIGE->PJM
CLTF
0.233
CPLELTFEXP_CPLE->PJM
CLTF
20.639
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.343
LAGNLTFEXP_LAGN->PJM
CLTF
15.403
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.288
TVALTFEXP_TVA->PJM
CLTF
7.684
NYPJM->LTFIMP_NY
CLTF
2.484
LGEELTFEXP_LGEE->PJM
CLTF
2.833
WECLTFEXP_WEC->PJM
CLTF
1.482
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-5: W72_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: W72_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.43 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:6166.56
MW Contribution:5.15
Bus #Bus NameTypeMW Contribution
3151051BRUNSWICKS1
50/50
17.522
3151021BRUNSWICKG1
50/50
8.442
971451AH1-221 GEN
50/50
25.642
315243AE2-183_GT3
50/50
10.589
3151531CLOVER1
50/50
10.578
3151601KERR 3
50/50
0.604
3151581KERR 1
50/50
0.216
3144293JTRSVLE
50/50
0.912
971629AH1-314 GEN
50/50
18.997
3151561HALLBR1
50/50
0.403
970919AG2-571 GEN
Solar/Wind Harmer
21.433
970087AG2-069 GEN
Solar/Wind Harmer
63.047
957481AF2-042 GEN
Solar/Wind Harmer
189.269
315693AD1-088 GEN
Solar/Wind Harmer
27.634
962491AG1-098 GEN
Solar/Wind Harmer
36.422
315687AD1-152 GEN
Solar/Wind Harmer
5.988
316003AC1-222 GEN
Solar/Wind Harmer
3.561
970401AG2-262 GEN
Solar/Wind Harmer
2.348
316237AB2-079_GEN
Solar/Wind Harmer
0.98
970685AG2-442 GEN
Solar/Wind Harmer
26.929
963171AG1-166 GEN
Solar/Wind Harmer
3.793
971563AH1-280 GEN
Solar/Wind Harmer
3.793
3146926FARMVIL
Solar/Wind Harmer
-0.017
971065AG2-659 GEN
Solar/Wind Harmer
12.621
316129AC1-054 GEN
Solar/Wind Harmer
2.079
970223AG2-152 GEN
Solar/Wind Harmer
18.347
270016AE1-250 BESS
Solar/Wind Harmer
3.032
3147123OTTER R
Solar/Wind Harmer
-0.011
316322AB2-045
Solar/Wind Harmer
0.602
3146776BUCKING
Solar/Wind Harmer
-0.007
270574AD1-017 GEN2
Solar/Wind Harmer
5.978
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
941801AE2-185 GEN
Solar/Wind Harmer
6.064
270030AE2-140 GEN
Solar/Wind Harmer
20.984
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.909
316049AB1-081 GEN
Solar/Wind Harmer
1.528
3142053HEARTS
Solar/Wind Harmer
0.166
316294AC1-161 GEN
Solar/Wind Helper
8.246
316375AC2-012 GEN
Solar/Wind Helper
1.074
3145336SMITFLD
Solar/Wind Helper
1.568
316388AE2-253 GEN
Solar/Wind Helper
1.48
3146456SLIGO L269
Solar/Wind Helper
0.38
316072AD1-144
Solar/Wind Helper
0.428
316246AF1-032 C
Solar/Wind Helper
0.426
316159AE1-175 C
Solar/Wind Helper
0.559
316381AD1-082 GEN
Solar/Wind Helper
1.857
316458AB2-190 GEN2
Solar/Wind Helper
2.041
3141766HARMONY
Solar/Wind Helper
0.068
3138133OCRAN
Solar/Wind Helper
0.204
3142433PROV 92
Solar/Wind Helper
1.345
3142543TWELFTH
Solar/Wind Helper
0.031
964211AG1-282 GEN
Solar/Wind Helper
0.434
3141726DUNNSVL
Solar/Wind Helper
1.289
3146516WINFALL
Solar/Wind Helper
1.017
3146516WINFALL
Solar/Wind Helper
0.314
316337AD2-073 GEN
Solar/Wind Helper
0.473
3142416OLDCHRC
Solar/Wind Helper
0.799
3142416OLDCHRC
Solar/Wind Helper
0.306
3143526WINTERP
Solar/Wind Helper
1.573
3143226MDLTHAN
Solar/Wind Helper
0.298
315800Z1-036_GEN1
Solar/Wind Helper
1.494
3130156CHOWAN
Solar/Wind Helper
0.24
3151041BRUNSWICKG3
50/50
8.442
972187AH1-678 GEN
50/50
19.374
315242AE2-183_GT2
50/50
10.589
315241AE2-183_GT1
50/50
10.524
972185AH1-677 GEN
50/50
38.176
970533AG2-339 GEN
50/50
56.972
970531AG2-338 GEN
50/50
22.789
3152661PLYWOOD A
50/50
0.749
970535AG2-341 GEN
50/50
5.154
3144293JTRSVLE
50/50
0.912
3144293JTRSVLE
50/50
0.768
970933AG2-581 GEN
Solar/Wind Harmer
67.369
970099AG2-077 GEN
Solar/Wind Harmer
75.708
971741AH1-377 GEN
Solar/Wind Harmer
50.305
970301AG2-198 GEN
Solar/Wind Harmer
19.85
3146843MT LREL
Solar/Wind Harmer
-0.036
3146843MT LREL
Solar/Wind Harmer
-0.036
964791AG1-342 GEN
Solar/Wind Harmer
7.683
962561AG1-105 GEN
Solar/Wind Harmer
19.916
316222AC1-221 GEN
Solar/Wind Harmer
3.458
939181AE1-148 GEN
Solar/Wind Harmer
18.413
313527AB2-043 GEN
Solar/Wind Harmer
5.244
970323AG2-213 GEN
Solar/Wind Harmer
15.621
971775AH1-396 GEN
Solar/Wind Harmer
2.225
316034AC1-036 C
Solar/Wind Harmer
0.579
958211AF2-115 GEN
Solar/Wind Harmer
4.741
963191AG1-168 GEN
Solar/Wind Harmer
2.845
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
942751AE2-291 GEN
Solar/Wind Harmer
16.715
270013AE1-250 PV
Solar/Wind Harmer
3.032
3146776BUCKING
Solar/Wind Harmer
-0.071
3146776BUCKING
Solar/Wind Harmer
-0.006
316217AC1-145 GEN
Solar/Wind Harmer
2.625
316197AC1-042 GEN
Solar/Wind Harmer
1.99
942671AE2-283 GEN
Solar/Wind Harmer
5.357
316263AC1-034 GEN
Solar/Wind Harmer
6.638
961601AG1-000A GEN
Solar/Wind Harmer
5.443
316036AC1-147 C
Solar/Wind Helper
0.624
3142956BIRDNECK
Solar/Wind Helper
0.274
316316AC1-027 C
Solar/Wind Helper
0.642
316185AD1-033 GEN
Solar/Wind Helper
1.905
3145506HICKORY
Solar/Wind Helper
1.596
3145506HICKORY
Solar/Wind Helper
0.958
3145506HICKORY
Solar/Wind Helper
0.239
316236AE1-162_GEN
Solar/Wind Helper
0.527
316339AD2-160 GEN
Solar/Wind Helper
1.48
316018AA1-139 ULT2
Solar/Wind Helper
1.659
316017AA1-139 ULT1
Solar/Wind Helper
1.763
3137176SLIGO L2192
Solar/Wind Helper
1.516
3130086AYDLETT
Solar/Wind Helper
1.505
316033AB2-134 GEN
Solar/Wind Helper
1.257
315697AD1-025 GEN
Solar/Wind Helper
4.177
3146386ELIZ CT
Solar/Wind Helper
0.351
316240AF1-291 C
Solar/Wind Helper
0.468
3142946ENON
Solar/Wind Helper
0.033
316487AF1-042 GEN
Solar/Wind Helper
0.335
316075AC2-137 C
Solar/Wind Helper
0.492
316077AC2-138 C
Solar/Wind Helper
0.302
316431W1029_GEN1
Solar/Wind Helper
1.297
316433W1029_GEN2
Solar/Wind Helper
1.297
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.573
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
966871AG1-558 GEN
Solar/Wind Helper
0.394
3144356SAPONY
Solar/Wind Helper
0.518
316468AD1-105 GEN
Solar/Wind Helper
1.373
315742AE1-103 GEN
Solar/Wind Helper
0.362
3151031BRUNSWICKG2
50/50
8.442
970413AG2-270 GEN
50/50
46.159
3151591KERR 2
50/50
0.604
3144293JTRSVLE
50/50
0.912
970917AG2-570 GEN
Solar/Wind Harmer
169.32
316478AD1-087 GEN
Solar/Wind Harmer
4.801
316486AD2-202 GEN
Solar/Wind Harmer
1.406
970909AG2-566 GEN
Solar/Wind Harmer
3.769
316248AF1-058 C
Solar/Wind Harmer
1.164
960061AF2-297 GEN
Solar/Wind Harmer
19.314
971683AH1-343 GEN
Solar/Wind Harmer
14.923
316283AC2-100 C
Solar/Wind Harmer
3.192
316131AB2-060 GEN
Solar/Wind Harmer
3.475
964241AG1-285 GEN
Solar/Wind Harmer
24.93
315785AD2-033 C
Solar/Wind Harmer
7.122
970257AG2-171 GEN
Solar/Wind Harmer
11.716
959311AF2-222 GEN
Solar/Wind Harmer
32.468
963181AG1-167 GEN
Solar/Wind Harmer
2.845
3147133PAMPLIN
Solar/Wind Harmer
-0.094
971193AH1-056 GEN
Solar/Wind Harmer
18.772
942461AE2-259 GEN
Solar/Wind Harmer
4.384
3146926FARMVIL
Solar/Wind Harmer
-0.017
3146776BUCKING
Solar/Wind Harmer
-0.006
270018AE2-047 C O1
Solar/Wind Harmer
1.461
270197AD1-017 GEN1
Solar/Wind Harmer
1.796
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
6.064
943811AF1-049 GEN
Solar/Wind Harmer
4.077
270336AE1-100 GEN
Solar/Wind Harmer
1.664
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
5.512
3138543CONSLDL
Solar/Wind Harmer
-0.008
315773AC2-141 GEN
Solar/Wind Helper
9.706
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3145336SMITFLD
Solar/Wind Helper
0.157
3146456SLIGO L269
Solar/Wind Helper
0.38
316382AG1-145 C
Solar/Wind Helper
0.496
315839AE2-212 C
Solar/Wind Helper
0.483
316320Y1-086
Solar/Wind Helper
0.157
316156AD2-030 GEN
Solar/Wind Helper
0.52
316280AD1-041 GEN
Solar/Wind Helper
1.152
3142946ENON
Solar/Wind Helper
0.111
316484AD2-074 GEN
Solar/Wind Helper
0.641
316404AE1-155 C
Solar/Wind Helper
2.769
316435W1029_GEN3
Solar/Wind Helper
1.297
3146516WINFALL
Solar/Wind Helper
0.314
3141906WESTMOR
Solar/Wind Helper
0.121
3146626S HERTFORD
Solar/Wind Helper
0.296
316473AC1-191 GEN
Solar/Wind Helper
1.785
3145273HOLLAND
Solar/Wind Helper
0.198
966881AG1-559 GEN
Solar/Wind Helper
0.346
3146376EDENTON
Solar/Wind Helper
0.239
963041AG1-153 GEN
50/50
17.095
315244AE2-183_ST
50/50
18.308
3151541CLOVER2
50/50
10.527
3151611KERR 4
50/50
0.604
3151621KERR 5
50/50
0.604
3151631KERR 6
50/50
0.604
3151641KERR 7
50/50
0.604
971967AH1-528 GEN
Solar/Wind Harmer
143.519
970673AG2-436 GEN
Solar/Wind Harmer
151.3
970673AG2-436 GEN
Solar/Wind Harmer
76.608
941031AE2-094 GEN
Solar/Wind Harmer
135.024
944011AF1-069 GEN
Solar/Wind Harmer
42.308
970085AG2-068 GEN
Solar/Wind Harmer
42.031
970581AG2-369 GEN
Solar/Wind Harmer
36.147
3147173SINAI
Solar/Wind Harmer
-0.039
3147243WELCO
Solar/Wind Harmer
-0.024
316118AC1-105 GEN
Solar/Wind Harmer
2.567
970865AG2-541 GEN
Solar/Wind Harmer
13.271
316239AB2-077_GEN
Solar/Wind Harmer
0.98
316238AB2-078_GEN
Solar/Wind Harmer
0.98
971443AH1-215 GEN
Solar/Wind Harmer
6.158
3144303KENBRDG
Solar/Wind Harmer
-0.025
970683AG2-441 GEN
Solar/Wind Harmer
24.044
970681AG2-440 GEN
Solar/Wind Harmer
19.235
946301AF1-294 GEN
Solar/Wind Harmer
7.775
961791AG1-021 GEN
Solar/Wind Harmer
3.793
315657AE1-056 GEN
Solar/Wind Harmer
11.263
316123AC1-075 GEN
Solar/Wind Harmer
3.099
970165AG2-112 GEN
Solar/Wind Harmer
2.728
970163AG2-111 GEN
Solar/Wind Harmer
2.603
270455AD2-022 GEN
Solar/Wind Harmer
4.991
270457AD2-023 GEN
Solar/Wind Harmer
2.531
970831AG2-522 GEN
Solar/Wind Harmer
11.041
970285AG2-188 GEN
Solar/Wind Harmer
17.881
971845AH1-439 GEN
Solar/Wind Harmer
9.974
270069AE2-166 C O1
Solar/Wind Harmer
2.569
319010AE1-072 C
Solar/Wind Helper
4.32
3143316POE
Solar/Wind Helper
1.486
316305AF2-043 C
Solar/Wind Helper
0.5
316369SG1_INVT
Solar/Wind Helper
1.758
957831AF2-077 GEN
Solar/Wind Helper
0.492
316132AB2-190 GEN1
Solar/Wind Helper
2.041
316349AD2-085 GEN
Solar/Wind Helper
1.61
313526AB2-022
Solar/Wind Helper
0.535
957601AF2-054 GEN
Solar/Wind Helper
0.462
3141873WAN 176
Solar/Wind Helper
0.069
315662AE1-191 GEN
Solar/Wind Helper
1.844
315666AE1-190 GEN
Solar/Wind Helper
0.461
3146486SUNBURY
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.341
316059AD1-063 C
Solar/Wind Helper
0.344
3141913WHIT STONE
Solar/Wind Helper
0.341
3138133OCRAN
Solar/Wind Helper
0.102
3143873LANEXA
Solar/Wind Helper
0.203
3141783LANCAST
Solar/Wind Helper
0.203
3141783LANCAST
Solar/Wind Helper
0.135
316321Z2-027
Solar/Wind Helper
0.515
3145176PASQUOTANK
Solar/Wind Helper
0.209
3141813NORNECK
Solar/Wind Helper
0.321
316312AB1-027
Solar/Wind Helper
0.585
316223AC1-118
Solar/Wind Helper
0.461
316233AE1-074 FULL
Solar/Wind Helper
0.462
316315AB2-025 C
Solar/Wind Helper
0.44
315611Z1-036_GEN2
Solar/Wind Helper
1.494
3130156CHOWAN
Solar/Wind Helper
0.24
3130156CHOWAN
Solar/Wind Helper
0.24
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.486
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.354
MECLTFEXP_MEC->PJM
CLTF
7.751
SIGELTFEXP_SIGE->PJM
CLTF
0.232
CPLELTFEXP_CPLE->PJM
CLTF
20.587
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.048
LAGNLTFEXP_LAGN->PJM
CLTF
15.349
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.145
TVALTFEXP_TVA->PJM
CLTF
7.657
NYPJM->LTFIMP_NY
CLTF
2.481
LGEELTFEXP_LGEE->PJM
CLTF
2.822
WECLTFEXP_WEC->PJM
CLTF
1.476
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: XT585_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: XT585_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.16 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5703.66
MW Contribution:5.15
Bus #Bus NameTypeMW Contribution
3151051BRUNSWICKS1
50/50
17.651
3151021BRUNSWICKG1
50/50
8.505
971451AH1-221 GEN
50/50
25.831
315243AE2-183_GT3
50/50
10.667
3151531CLOVER1
50/50
10.644
3151601KERR 3
50/50
0.604
3151581KERR 1
50/50
0.216
3144293JTRSVLE
50/50
0.914
971629AH1-314 GEN
50/50
19.06
3151561HALLBR1
50/50
0.404
970919AG2-571 GEN
Solar/Wind Harmer
21.586
970087AG2-069 GEN
Solar/Wind Harmer
63.496
957481AF2-042 GEN
Solar/Wind Harmer
190.536
315693AD1-088 GEN
Solar/Wind Harmer
27.811
962491AG1-098 GEN
Solar/Wind Harmer
36.654
315687AD1-152 GEN
Solar/Wind Harmer
6.022
316003AC1-222 GEN
Solar/Wind Harmer
3.575
3151031BRUNSWICKG2
50/50
8.505
970413AG2-270 GEN
50/50
46.449
3151591KERR 2
50/50
0.604
3144293JTRSVLE
50/50
0.914
970917AG2-570 GEN
Solar/Wind Harmer
170.53
316478AD1-087 GEN
Solar/Wind Harmer
4.831
316486AD2-202 GEN
Solar/Wind Harmer
1.415
970909AG2-566 GEN
Solar/Wind Harmer
3.791
316248AF1-058 C
Solar/Wind Harmer
1.169
960061AF2-297 GEN
Solar/Wind Harmer
19.391
971683AH1-343 GEN
Solar/Wind Harmer
14.982
316283AC2-100 C
Solar/Wind Harmer
3.205
316131AB2-060 GEN
Solar/Wind Harmer
3.471
964241AG1-285 GEN
Solar/Wind Harmer
24.911
315785AD2-033 C
Solar/Wind Harmer
7.122
970257AG2-171 GEN
Solar/Wind Harmer
11.718
959311AF2-222 GEN
Solar/Wind Harmer
32.481
963181AG1-167 GEN
Solar/Wind Harmer
2.849
3147133PAMPLIN
Solar/Wind Harmer
-0.094
971193AH1-056 GEN
Solar/Wind Harmer
18.811
942461AE2-259 GEN
Solar/Wind Harmer
4.399
3146926FARMVIL
Solar/Wind Harmer
-0.017
3146776BUCKING
Solar/Wind Harmer
-0.006
270018AE2-047 C O1
Solar/Wind Harmer
1.466
270197AD1-017 GEN1
Solar/Wind Harmer
1.802
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
6.086
943811AF1-049 GEN
Solar/Wind Harmer
4.09
270336AE1-100 GEN
Solar/Wind Harmer
1.669
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
5.373
315773AC2-141 GEN
Solar/Wind Helper
9.595
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3145336SMITFLD
Solar/Wind Helper
0.157
315839AE2-212 C
Solar/Wind Helper
0.523
3146456SLIGO L269
Solar/Wind Helper
0.379
316382AG1-145 C
Solar/Wind Helper
0.498
316320Y1-086
Solar/Wind Helper
0.156
316156AD2-030 GEN
Solar/Wind Helper
0.525
316280AD1-041 GEN
Solar/Wind Helper
1.166
3142946ENON
Solar/Wind Helper
0.114
316484AD2-074 GEN
Solar/Wind Helper
0.648
316404AE1-155 C
Solar/Wind Helper
2.8
316435W1029_GEN3
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3141906WESTMOR
Solar/Wind Helper
0.122
316473AC1-191 GEN
Solar/Wind Helper
1.829
3146626S HERTFORD
Solar/Wind Helper
0.296
3145273HOLLAND
Solar/Wind Helper
0.201
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.24
970401AG2-262 GEN
Solar/Wind Harmer
2.352
316237AB2-079_GEN
Solar/Wind Harmer
0.978
970685AG2-442 GEN
Solar/Wind Harmer
26.954
963171AG1-166 GEN
Solar/Wind Harmer
3.799
971563AH1-280 GEN
Solar/Wind Harmer
3.799
3146926FARMVIL
Solar/Wind Harmer
-0.017
971065AG2-659 GEN
Solar/Wind Harmer
12.523
316129AC1-054 GEN
Solar/Wind Harmer
2.059
970223AG2-152 GEN
Solar/Wind Harmer
18.408
270016AE1-250 BESS
Solar/Wind Harmer
3.042
3147123OTTER R
Solar/Wind Harmer
-0.011
316322AB2-045
Solar/Wind Harmer
0.605
3146776BUCKING
Solar/Wind Harmer
-0.007
270574AD1-017 GEN2
Solar/Wind Harmer
5.998
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
941801AE2-185 GEN
Solar/Wind Harmer
6.086
270030AE2-140 GEN
Solar/Wind Harmer
21.053
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.864
316049AB1-081 GEN
Solar/Wind Harmer
1.492
3142053HEARTS
Solar/Wind Harmer
0.163
316294AC1-161 GEN
Solar/Wind Helper
8.153
316375AC2-012 GEN
Solar/Wind Helper
1.068
3145336SMITFLD
Solar/Wind Helper
1.575
316388AE2-253 GEN
Solar/Wind Helper
1.472
3146456SLIGO L269
Solar/Wind Helper
0.379
316381AD1-082 GEN
Solar/Wind Helper
1.955
316072AD1-144
Solar/Wind Helper
0.428
316246AF1-032 C
Solar/Wind Helper
0.424
316159AE1-175 C
Solar/Wind Helper
0.562
316458AB2-190 GEN2
Solar/Wind Helper
2.107
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.376
3138133OCRAN
Solar/Wind Helper
0.206
3142543TWELFTH
Solar/Wind Helper
0.032
964211AG1-282 GEN
Solar/Wind Helper
0.439
3141726DUNNSVL
Solar/Wind Helper
1.304
316337AD2-073 GEN
Solar/Wind Helper
0.478
3142416OLDCHRC
Solar/Wind Helper
0.816
3142416OLDCHRC
Solar/Wind Helper
0.312
3146516WINFALL
Solar/Wind Helper
1.016
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
3143226MDLTHAN
Solar/Wind Helper
0.3
315800Z1-036_GEN1
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3151041BRUNSWICKG3
50/50
8.505
972187AH1-678 GEN
50/50
19.517
315242AE2-183_GT2
50/50
10.667
315241AE2-183_GT1
50/50
10.602
972185AH1-677 GEN
50/50
38.457
3152661PLYWOOD A
50/50
0.751
970535AG2-341 GEN
50/50
5.149
3144293JTRSVLE
50/50
0.914
3144293JTRSVLE
50/50
0.769
970933AG2-581 GEN
Solar/Wind Harmer
67.863
970099AG2-077 GEN
Solar/Wind Harmer
76.214
971741AH1-377 GEN
Solar/Wind Harmer
50.609
970301AG2-198 GEN
Solar/Wind Harmer
19.968
3146843MT LREL
Solar/Wind Harmer
-0.036
3146843MT LREL
Solar/Wind Harmer
-0.036
964791AG1-342 GEN
Solar/Wind Harmer
7.699
962561AG1-105 GEN
Solar/Wind Harmer
19.948
316222AC1-221 GEN
Solar/Wind Harmer
3.472
939181AE1-148 GEN
Solar/Wind Harmer
18.394
313527AB2-043 GEN
Solar/Wind Harmer
5.237
970323AG2-213 GEN
Solar/Wind Harmer
15.625
971775AH1-396 GEN
Solar/Wind Harmer
2.225
316034AC1-036 C
Solar/Wind Harmer
0.579
958211AF2-115 GEN
Solar/Wind Harmer
4.748
963191AG1-168 GEN
Solar/Wind Harmer
2.849
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
942751AE2-291 GEN
Solar/Wind Harmer
16.78
270013AE1-250 PV
Solar/Wind Harmer
3.042
3146776BUCKING
Solar/Wind Harmer
-0.072
3146776BUCKING
Solar/Wind Harmer
-0.006
316217AC1-145 GEN
Solar/Wind Harmer
2.634
316197AC1-042 GEN
Solar/Wind Harmer
1.997
942671AE2-283 GEN
Solar/Wind Harmer
5.376
316263AC1-034 GEN
Solar/Wind Harmer
6.481
961601AG1-000A GEN
Solar/Wind Harmer
5.306
316036AC1-147 C
Solar/Wind Helper
0.621
3142956BIRDNECK
Solar/Wind Helper
0.272
316316AC1-027 C
Solar/Wind Helper
0.638
316185AD1-033 GEN
Solar/Wind Helper
1.893
3145506HICKORY
Solar/Wind Helper
1.587
3145506HICKORY
Solar/Wind Helper
0.952
3145506HICKORY
Solar/Wind Helper
0.238
316236AE1-162_GEN
Solar/Wind Helper
0.529
316339AD2-160 GEN
Solar/Wind Helper
1.472
316018AA1-139 ULT2
Solar/Wind Helper
1.65
316017AA1-139 ULT1
Solar/Wind Helper
1.754
3137176SLIGO L2192
Solar/Wind Helper
1.508
3130086AYDLETT
Solar/Wind Helper
1.498
316033AB2-134 GEN
Solar/Wind Helper
1.287
315697AD1-025 GEN
Solar/Wind Helper
4.277
316240AF1-291 C
Solar/Wind Helper
0.501
3146386ELIZ CT
Solar/Wind Helper
0.35
3142946ENON
Solar/Wind Helper
0.034
316487AF1-042 GEN
Solar/Wind Helper
0.339
3144356SAPONY
Solar/Wind Helper
0.597
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.305
316431W1029_GEN1
Solar/Wind Helper
1.295
316433W1029_GEN2
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
966871AG1-558 GEN
Solar/Wind Helper
0.403
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
316468AD1-105 GEN
Solar/Wind Helper
1.402
315742AE1-103 GEN
Solar/Wind Helper
0.368
963041AG1-153 GEN
50/50
17.22
315244AE2-183_ST
50/50
18.443
3151541CLOVER2
50/50
10.593
3151611KERR 4
50/50
0.604
3151621KERR 5
50/50
0.604
3151631KERR 6
50/50
0.604
3151641KERR 7
50/50
0.604
971967AH1-528 GEN
Solar/Wind Harmer
144.6
970085AG2-068 GEN
Solar/Wind Harmer
42.331
970581AG2-369 GEN
Solar/Wind Harmer
36.404
3147173SINAI
Solar/Wind Harmer
-0.039
3147243WELCO
Solar/Wind Harmer
-0.024
316118AC1-105 GEN
Solar/Wind Harmer
2.575
970865AG2-541 GEN
Solar/Wind Harmer
13.323
316239AB2-077_GEN
Solar/Wind Harmer
0.978
316238AB2-078_GEN
Solar/Wind Harmer
0.978
971443AH1-215 GEN
Solar/Wind Harmer
6.159
3144303KENBRDG
Solar/Wind Harmer
-0.025
970683AG2-441 GEN
Solar/Wind Harmer
24.066
970681AG2-440 GEN
Solar/Wind Harmer
19.253
946301AF1-294 GEN
Solar/Wind Harmer
7.788
961791AG1-021 GEN
Solar/Wind Harmer
3.799
315657AE1-056 GEN
Solar/Wind Harmer
11.287
316123AC1-075 GEN
Solar/Wind Harmer
3.111
970165AG2-112 GEN
Solar/Wind Harmer
2.739
970163AG2-111 GEN
Solar/Wind Harmer
2.613
270455AD2-022 GEN
Solar/Wind Harmer
5.008
270457AD2-023 GEN
Solar/Wind Harmer
2.539
970831AG2-522 GEN
Solar/Wind Harmer
10.909
970285AG2-188 GEN
Solar/Wind Harmer
17.971
971845AH1-439 GEN
Solar/Wind Harmer
10.023
270069AE2-166 C O1
Solar/Wind Harmer
2.578
3143316POE
Solar/Wind Helper
1.64
319010AE1-072 C
Solar/Wind Helper
4.299
316369SG1_INVT
Solar/Wind Helper
1.8
316305AF2-043 C
Solar/Wind Helper
0.499
316132AB2-190 GEN1
Solar/Wind Helper
2.107
957831AF2-077 GEN
Solar/Wind Helper
0.495
316349AD2-085 GEN
Solar/Wind Helper
1.649
313526AB2-022
Solar/Wind Helper
0.533
957601AF2-054 GEN
Solar/Wind Helper
0.467
3141873WAN 176
Solar/Wind Helper
0.07
315662AE1-191 GEN
Solar/Wind Helper
1.865
315666AE1-190 GEN
Solar/Wind Helper
0.466
316059AD1-063 C
Solar/Wind Helper
0.348
3141913WHIT STONE
Solar/Wind Helper
0.345
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.137
3146486SUNBURY
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.341
316321Z2-027
Solar/Wind Helper
0.514
3145176PASQUOTANK
Solar/Wind Helper
0.209
316315AB2-025 C
Solar/Wind Helper
0.507
3141813NORNECK
Solar/Wind Helper
0.325
316312AB1-027
Solar/Wind Helper
0.597
316233AE1-074 FULL
Solar/Wind Helper
0.469
316223AC1-118
Solar/Wind Helper
0.466
315611Z1-036_GEN2
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.447
MECLTFEXP_MEC->PJM
CLTF
7.78
SIGELTFEXP_SIGE->PJM
CLTF
0.233
CPLELTFEXP_CPLE->PJM
CLTF
20.639
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.343
LAGNLTFEXP_LAGN->PJM
CLTF
15.403
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.288
TVALTFEXP_TVA->PJM
CLTF
7.684
NYPJM->LTFIMP_NY
CLTF
2.484
LGEELTFEXP_LGEE->PJM
CLTF
2.833
WECLTFEXP_WEC->PJM
CLTF
1.482
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 54472_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 54472_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.74 %
Rating:2858.0 MVA
Rating Type:C
MVA to Mitigate:3193.49
MW Contribution:3.78
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
34.77
3151031BRUNSWICKG2
50/50
4.131
3151531CLOVER1
50/50
7.968
3151051BRUNSWICKS1
50/50
8.574
3151021BRUNSWICKG1
50/50
4.131
971451AH1-221 GEN
50/50
12.548
315243AE2-183_GT3
50/50
3.874
3151601KERR 3
50/50
0.44
3151581KERR 1
50/50
0.157
3144293JTRSVLE
50/50
0.691
971629AH1-314 GEN
50/50
11.594
957481AF2-042 GEN
Solar/Wind Harmer
144.035
315693AD1-088 GEN
Solar/Wind Harmer
21.036
962491AG1-098 GEN
Solar/Wind Harmer
27.737
315687AD1-152 GEN
Solar/Wind Harmer
4.411
970919AG2-571 GEN
Solar/Wind Harmer
10.566
970087AG2-069 GEN
Solar/Wind Harmer
31.107
970401AG2-262 GEN
Solar/Wind Harmer
1.7
316003AC1-222 GEN
Solar/Wind Harmer
2.544
316237AB2-079_GEN
Solar/Wind Harmer
0.722
970685AG2-442 GEN
Solar/Wind Harmer
20.27
963171AG1-166 GEN
Solar/Wind Harmer
2.872
971563AH1-280 GEN
Solar/Wind Harmer
2.872
3146926FARMVIL
Solar/Wind Harmer
-0.013
971065AG2-659 GEN
Solar/Wind Harmer
9.218
316129AC1-054 GEN
Solar/Wind Harmer
1.52
316322AB2-045
Solar/Wind Harmer
0.488
3146776BUCKING
Solar/Wind Harmer
-0.006
970223AG2-152 GEN
Solar/Wind Harmer
11.343
316294AC1-161 GEN
Solar/Wind Helper
4.653
3151041BRUNSWICKG3
50/50
4.131
972187AH1-678 GEN
50/50
9.481
3152661PLYWOOD A
50/50
0.538
315242AE2-183_GT2
50/50
3.874
315241AE2-183_GT1
50/50
3.85
972185AH1-677 GEN
50/50
13.967
970535AG2-341 GEN
50/50
3.778
3144293JTRSVLE
50/50
0.691
3144293JTRSVLE
50/50
0.582
970933AG2-581 GEN
Solar/Wind Harmer
51.852
970099AG2-077 GEN
Solar/Wind Harmer
57.614
971741AH1-377 GEN
Solar/Wind Harmer
38.586
970301AG2-198 GEN
Solar/Wind Harmer
15.274
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
964791AG1-342 GEN
Solar/Wind Harmer
5.564
962561AG1-105 GEN
Solar/Wind Harmer
14.462
939181AE1-148 GEN
Solar/Wind Harmer
13.444
313527AB2-043 GEN
Solar/Wind Harmer
3.87
970323AG2-213 GEN
Solar/Wind Harmer
11.685
971775AH1-396 GEN
Solar/Wind Harmer
1.664
316034AC1-036 C
Solar/Wind Harmer
0.433
958211AF2-115 GEN
Solar/Wind Harmer
3.59
963191AG1-168 GEN
Solar/Wind Harmer
2.154
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
316222AC1-221 GEN
Solar/Wind Harmer
2.218
942751AE2-291 GEN
Solar/Wind Harmer
11.754
3146776BUCKING
Solar/Wind Harmer
-0.058
3146776BUCKING
Solar/Wind Harmer
-0.005
316240AF1-291 C
Solar/Wind Helper
0.299
3151541CLOVER2
50/50
7.93
963041AG1-153 GEN
50/50
8.365
315244AE2-183_ST
50/50
6.698
3151611KERR 4
50/50
0.44
3151621KERR 5
50/50
0.44
3151631KERR 6
50/50
0.44
3151641KERR 7
50/50
0.44
971967AH1-528 GEN
Solar/Wind Harmer
110.812
970085AG2-068 GEN
Solar/Wind Harmer
20.738
970581AG2-369 GEN
Solar/Wind Harmer
17.835
3147173SINAI
Solar/Wind Harmer
-0.028
3147243WELCO
Solar/Wind Harmer
-0.017
316118AC1-105 GEN
Solar/Wind Harmer
1.848
316239AB2-077_GEN
Solar/Wind Harmer
0.722
316238AB2-078_GEN
Solar/Wind Harmer
0.722
971443AH1-215 GEN
Solar/Wind Harmer
4.604
3144303KENBRDG
Solar/Wind Harmer
-0.019
970865AG2-541 GEN
Solar/Wind Harmer
9.435
970683AG2-441 GEN
Solar/Wind Harmer
18.098
970681AG2-440 GEN
Solar/Wind Harmer
14.478
946301AF1-294 GEN
Solar/Wind Harmer
5.887
961791AG1-021 GEN
Solar/Wind Harmer
2.872
315657AE1-056 GEN
Solar/Wind Harmer
8.565
316123AC1-075 GEN
Solar/Wind Harmer
2.19
970165AG2-112 GEN
Solar/Wind Harmer
1.928
970163AG2-111 GEN
Solar/Wind Harmer
1.839
970673AG2-436 GEN
Solar/Wind Harmer
40.956
970673AG2-436 GEN
Solar/Wind Harmer
20.737
270455AD2-022 GEN
Solar/Wind Harmer
3.036
270457AD2-023 GEN
Solar/Wind Harmer
1.539
970285AG2-188 GEN
Solar/Wind Harmer
14.324
970831AG2-522 GEN
Solar/Wind Harmer
8.077
971845AH1-439 GEN
Solar/Wind Harmer
8.053
3143316POE
Solar/Wind Helper
1.004
3151591KERR 2
50/50
0.44
3144293JTRSVLE
50/50
0.691
316478AD1-087 GEN
Solar/Wind Harmer
3.615
316486AD2-202 GEN
Solar/Wind Harmer
1.059
970917AG2-570 GEN
Solar/Wind Harmer
83.468
970909AG2-566 GEN
Solar/Wind Harmer
2.9
316248AF1-058 C
Solar/Wind Harmer
0.833
960061AF2-297 GEN
Solar/Wind Harmer
13.826
971683AH1-343 GEN
Solar/Wind Harmer
10.636
316131AB2-060 GEN
Solar/Wind Harmer
2.567
964241AG1-285 GEN
Solar/Wind Harmer
18.486
315785AD2-033 C
Solar/Wind Harmer
5.315
970257AG2-171 GEN
Solar/Wind Harmer
8.764
959311AF2-222 GEN
Solar/Wind Harmer
24.33
963181AG1-167 GEN
Solar/Wind Harmer
2.154
3147133PAMPLIN
Solar/Wind Harmer
-0.071
971193AH1-056 GEN
Solar/Wind Harmer
14.275
942461AE2-259 GEN
Solar/Wind Harmer
3.375
3146926FARMVIL
Solar/Wind Harmer
-0.013
316283AC2-100 C
Solar/Wind Harmer
2.04
3146776BUCKING
Solar/Wind Harmer
-0.005
315773AC2-141 GEN
Solar/Wind Helper
5.476
315839AE2-212 C
Solar/Wind Helper
0.317
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.523
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.401
MECLTFEXP_MEC->PJM
CLTF
4.601
SIGELTFEXP_SIGE->PJM
CLTF
0.139
CPLELTFEXP_CPLE->PJM
CLTF
11.786
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.116
LAGNLTFEXP_LAGN->PJM
CLTF
8.928
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.434
TVALTFEXP_TVA->PJM
CLTF
4.461
NYPJM->LTFIMP_NY
CLTF
1.417
LGEELTFEXP_LGEE->PJM
CLTF
1.692
WECLTFEXP_WEC->PJM
CLTF
0.884

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.06 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5008.65
MW Contribution:4.57
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
47.73
957481AF2-042 GEN
Solar/Wind Harmer
126.807
315693AD1-088 GEN
Solar/Wind Harmer
20.818
962491AG1-098 GEN
Solar/Wind Harmer
24.385
315687AD1-152 GEN
Solar/Wind Harmer
0.013
316003AC1-222 GEN
Solar/Wind Harmer
0.008
970401AG2-262 GEN
Solar/Wind Harmer
1.677
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
17.979
963171AG1-166 GEN
Solar/Wind Harmer
1.264
971563AH1-280 GEN
Solar/Wind Harmer
2.529
3146926FARMVIL
Solar/Wind Harmer
0.131
971065AG2-659 GEN
Solar/Wind Harmer
8.445
316129AC1-054 GEN
Solar/Wind Harmer
0.698
970223AG2-152 GEN
Solar/Wind Harmer
12.094
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.088
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.055
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.099
941801AE2-185 GEN
Solar/Wind Harmer
4.212
270030AE2-140 GEN
Solar/Wind Harmer
13.804
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.094
316359AB2-059 GEN
Solar/Wind Harmer
0.421
316049AB1-081 GEN
Solar/Wind Harmer
0.67
3142053HEARTS
Solar/Wind Harmer
0.206
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
971967AH1-528 GEN
Solar/Wind Harmer
95.481
970085AG2-068 GEN
Solar/Wind Harmer
31.82
970581AG2-369 GEN
Solar/Wind Harmer
27.365
3147173SINAI
Solar/Wind Harmer
0.309
3147243WELCO
Solar/Wind Harmer
0.193
316118AC1-105 GEN
Solar/Wind Harmer
0.768
970865AG2-541 GEN
Solar/Wind Harmer
9.078
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.118
3144303KENBRDG
Solar/Wind Harmer
0.196
970683AG2-441 GEN
Solar/Wind Harmer
16.053
970681AG2-440 GEN
Solar/Wind Harmer
12.842
946301AF1-294 GEN
Solar/Wind Harmer
4.678
961791AG1-021 GEN
Solar/Wind Harmer
2.276
315657AE1-056 GEN
Solar/Wind Harmer
8.085
316123AC1-075 GEN
Solar/Wind Harmer
0.315
970165AG2-112 GEN
Solar/Wind Harmer
1.87
970163AG2-111 GEN
Solar/Wind Harmer
1.784
970831AG2-522 GEN
Solar/Wind Harmer
7.35
970285AG2-188 GEN
Solar/Wind Harmer
12.402
971845AH1-439 GEN
Solar/Wind Harmer
6.507
270069AE2-166 C O1
Solar/Wind Harmer
0.004
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
53.421
316478AD1-087 GEN
Solar/Wind Harmer
1.525
316486AD2-202 GEN
Solar/Wind Harmer
0.448
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
13.182
316283AC2-100 C
Solar/Wind Harmer
0.55
971683AH1-343 GEN
Solar/Wind Harmer
10.2
316131AB2-060 GEN
Solar/Wind Harmer
0.796
964241AG1-285 GEN
Solar/Wind Harmer
16.703
315785AD2-033 C
Solar/Wind Harmer
2.003
970257AG2-171 GEN
Solar/Wind Harmer
7.834
959311AF2-222 GEN
Solar/Wind Harmer
21.656
963181AG1-167 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.736
971193AH1-056 GEN
Solar/Wind Harmer
14.274
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.131
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
0.943
3146776BUCKING
Solar/Wind Harmer
0.049
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.212
270336AE1-100 GEN
Solar/Wind Harmer
0.003
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.117
971623AH1-311 GEN
Solar/Wind Harmer
0.234
961601AG1-000A GEN
Solar/Wind Harmer
8.141
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
44.982
970099AG2-077 GEN
Solar/Wind Harmer
50.723
971741AH1-377 GEN
Solar/Wind Harmer
33.569
970301AG2-198 GEN
Solar/Wind Harmer
13.228
3146843MT LREL
Solar/Wind Harmer
0.286
3146843MT LREL
Solar/Wind Harmer
0.286
964791AG1-342 GEN
Solar/Wind Harmer
5.488
316222AC1-221 GEN
Solar/Wind Harmer
1.175
962561AG1-105 GEN
Solar/Wind Harmer
13.485
939181AE1-148 GEN
Solar/Wind Harmer
12.41
313527AB2-043 GEN
Solar/Wind Harmer
0.003
970323AG2-213 GEN
Solar/Wind Harmer
10.445
971775AH1-396 GEN
Solar/Wind Harmer
0.392
316034AC1-036 C
Solar/Wind Harmer
0.018
958211AF2-115 GEN
Solar/Wind Harmer
2.845
963191AG1-168 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.234
3147133PAMPLIN
Solar/Wind Harmer
0.187
942751AE2-291 GEN
Solar/Wind Harmer
11.476
270013AE1-250 PV
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.546
3146776BUCKING
Solar/Wind Harmer
0.044
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.276
316263AC1-034 GEN
Solar/Wind Harmer
4.449
961601AG1-000A GEN
Solar/Wind Harmer
2.035
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315
NYPJM->LTFIMP_NY
CLTF
2.382
LGEELTFEXP_LGEE->PJM
CLTF
2.675
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51192_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51192_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.25 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5458.06
MW Contribution:4.57
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
62.844
957481AF2-042 GEN
Solar/Wind Harmer
166.962
315693AD1-088 GEN
Solar/Wind Harmer
24.364
962491AG1-098 GEN
Solar/Wind Harmer
32.107
315687AD1-152 GEN
Solar/Wind Harmer
5.339
316003AC1-222 GEN
Solar/Wind Harmer
3.203
970401AG2-262 GEN
Solar/Wind Harmer
2.096
316237AB2-079_GEN
Solar/Wind Harmer
0.866
970685AG2-442 GEN
Solar/Wind Harmer
23.673
963171AG1-166 GEN
Solar/Wind Harmer
3.329
971563AH1-280 GEN
Solar/Wind Harmer
3.329
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.119
316129AC1-054 GEN
Solar/Wind Harmer
1.828
970223AG2-152 GEN
Solar/Wind Harmer
17.247
270016AE1-250 BESS
Solar/Wind Harmer
2.846
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.591
316322AB2-045
Solar/Wind Harmer
0.516
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.545
270030AE2-140 GEN
Solar/Wind Harmer
19.786
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.774
316049AB1-081 GEN
Solar/Wind Harmer
1.419
3142053HEARTS
Solar/Wind Harmer
0.155
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
971967AH1-528 GEN
Solar/Wind Harmer
126.052
970085AG2-068 GEN
Solar/Wind Harmer
41.896
970581AG2-369 GEN
Solar/Wind Harmer
36.031
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.3
970865AG2-541 GEN
Solar/Wind Harmer
11.953
316239AB2-077_GEN
Solar/Wind Harmer
0.866
316238AB2-078_GEN
Solar/Wind Harmer
0.866
971443AH1-215 GEN
Solar/Wind Harmer
5.422
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.136
970681AG2-440 GEN
Solar/Wind Harmer
16.909
946301AF1-294 GEN
Solar/Wind Harmer
6.825
961791AG1-021 GEN
Solar/Wind Harmer
3.329
270455AD2-022 GEN
Solar/Wind Harmer
4.714
270457AD2-023 GEN
Solar/Wind Harmer
2.39
315657AE1-056 GEN
Solar/Wind Harmer
9.877
316123AC1-075 GEN
Solar/Wind Harmer
2.797
970165AG2-112 GEN
Solar/Wind Harmer
2.462
970163AG2-111 GEN
Solar/Wind Harmer
2.349
970831AG2-522 GEN
Solar/Wind Harmer
9.678
970285AG2-188 GEN
Solar/Wind Harmer
15.412
971845AH1-439 GEN
Solar/Wind Harmer
8.567
270069AE2-166 C O1
Solar/Wind Harmer
2.422
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
59.226
970099AG2-077 GEN
Solar/Wind Harmer
66.785
971741AH1-377 GEN
Solar/Wind Harmer
44.199
970301AG2-198 GEN
Solar/Wind Harmer
17.416
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.86
316222AC1-221 GEN
Solar/Wind Harmer
3.218
962561AG1-105 GEN
Solar/Wind Harmer
17.755
939181AE1-148 GEN
Solar/Wind Harmer
16.34
313527AB2-043 GEN
Solar/Wind Harmer
4.631
970323AG2-213 GEN
Solar/Wind Harmer
13.752
971775AH1-396 GEN
Solar/Wind Harmer
1.958
316034AC1-036 C
Solar/Wind Harmer
0.51
958211AF2-115 GEN
Solar/Wind Harmer
4.162
963191AG1-168 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.11
270013AE1-250 PV
Solar/Wind Harmer
2.846
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.4
316197AC1-042 GEN
Solar/Wind Harmer
1.819
942671AE2-283 GEN
Solar/Wind Harmer
4.898
316263AC1-034 GEN
Solar/Wind Harmer
6.166
961601AG1-000A GEN
Solar/Wind Harmer
5.056
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
168.81
316478AD1-087 GEN
Solar/Wind Harmer
4.25
316486AD2-202 GEN
Solar/Wind Harmer
1.245
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
1.046
960061AF2-297 GEN
Solar/Wind Harmer
17.357
316283AC2-100 C
Solar/Wind Harmer
2.974
971683AH1-343 GEN
Solar/Wind Harmer
13.43
316131AB2-060 GEN
Solar/Wind Harmer
3.068
964241AG1-285 GEN
Solar/Wind Harmer
21.992
315785AD2-033 C
Solar/Wind Harmer
6.274
970257AG2-171 GEN
Solar/Wind Harmer
10.314
959311AF2-222 GEN
Solar/Wind Harmer
28.571
963181AG1-167 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.462
942461AE2-259 GEN
Solar/Wind Harmer
3.832
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.378
270197AD1-017 GEN1
Solar/Wind Harmer
1.68
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.844
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.545
270336AE1-100 GEN
Solar/Wind Harmer
1.569
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
5.12
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315
NYPJM->LTFIMP_NY
CLTF
2.382
LGEELTFEXP_LGEE->PJM
CLTF
2.675
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51172_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51172_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.79 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5435.07
MW Contribution:4.58
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
11.056
3151051BRUNSWICKS1
50/50
17.38
3151021BRUNSWICKG1
50/50
8.374
971451AH1-221 GEN
50/50
25.435
3151531CLOVER1
50/50
9.312
3151601KERR 3
50/50
0.538
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.8
971629AH1-314 GEN
50/50
17.875
3151561HALLBR1
50/50
0.366
970919AG2-571 GEN
Solar/Wind Harmer
21.227
970087AG2-069 GEN
Solar/Wind Harmer
62.431
957481AF2-042 GEN
Solar/Wind Harmer
166.01
315693AD1-088 GEN
Solar/Wind Harmer
24.233
962491AG1-098 GEN
Solar/Wind Harmer
31.935
315687AD1-152 GEN
Solar/Wind Harmer
5.313
316003AC1-222 GEN
Solar/Wind Harmer
3.193
970401AG2-262 GEN
Solar/Wind Harmer
2.094
316237AB2-079_GEN
Solar/Wind Harmer
0.868
970685AG2-442 GEN
Solar/Wind Harmer
23.682
963171AG1-166 GEN
Solar/Wind Harmer
3.328
971563AH1-280 GEN
Solar/Wind Harmer
3.328
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.224
316129AC1-054 GEN
Solar/Wind Harmer
1.849
970223AG2-152 GEN
Solar/Wind Harmer
17.201
270016AE1-250 BESS
Solar/Wind Harmer
2.839
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.577
316322AB2-045
Solar/Wind Harmer
0.514
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.53
270030AE2-140 GEN
Solar/Wind Harmer
19.734
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.817
316049AB1-081 GEN
Solar/Wind Harmer
1.454
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.785
316375AC2-012 GEN
Solar/Wind Helper
1.014
3145336SMITFLD
Solar/Wind Helper
1.482
316388AE2-253 GEN
Solar/Wind Helper
1.397
3146456SLIGO L269
Solar/Wind Helper
0.359
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.402
316159AE1-175 C
Solar/Wind Helper
0.529
316381AD1-082 GEN
Solar/Wind Helper
1.758
316458AB2-190 GEN2
Solar/Wind Helper
1.933
3141766HARMONY
Solar/Wind Helper
0.065
3138133OCRAN
Solar/Wind Helper
0.193
3142433PROV 92
Solar/Wind Helper
1.275
3142543TWELFTH
Solar/Wind Helper
0.029
964211AG1-282 GEN
Solar/Wind Helper
0.412
3141726DUNNSVL
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.961
3146516WINFALL
Solar/Wind Helper
0.297
316337AD2-073 GEN
Solar/Wind Helper
0.448
3142416OLDCHRC
Solar/Wind Helper
0.759
3142416OLDCHRC
Solar/Wind Helper
0.291
3143526WINTERP
Solar/Wind Helper
1.499
3143226MDLTHAN
Solar/Wind Helper
0.284
315800Z1-036_GEN1
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
315242AE2-183_GT2
50/50
11.056
315241AE2-183_GT1
50/50
10.988
972185AH1-677 GEN
50/50
39.858
3151041BRUNSWICKG3
50/50
8.374
972187AH1-678 GEN
50/50
19.217
3152661PLYWOOD A
50/50
0.67
970535AG2-341 GEN
50/50
4.577
3144293JTRSVLE
50/50
0.8
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
58.849
970099AG2-077 GEN
Solar/Wind Harmer
66.404
971741AH1-377 GEN
Solar/Wind Harmer
43.978
970301AG2-198 GEN
Solar/Wind Harmer
17.332
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.854
316222AC1-221 GEN
Solar/Wind Harmer
3.208
962561AG1-105 GEN
Solar/Wind Harmer
17.747
939181AE1-148 GEN
Solar/Wind Harmer
16.378
313527AB2-043 GEN
Solar/Wind Harmer
4.643
970323AG2-213 GEN
Solar/Wind Harmer
13.768
971775AH1-396 GEN
Solar/Wind Harmer
1.961
316034AC1-036 C
Solar/Wind Harmer
0.511
958211AF2-115 GEN
Solar/Wind Harmer
4.16
963191AG1-168 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.066
270013AE1-250 PV
Solar/Wind Harmer
2.839
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.394
316197AC1-042 GEN
Solar/Wind Harmer
1.815
942671AE2-283 GEN
Solar/Wind Harmer
4.885
316263AC1-034 GEN
Solar/Wind Harmer
6.316
961601AG1-000A GEN
Solar/Wind Harmer
5.186
316036AC1-147 C
Solar/Wind Helper
0.59
3142956BIRDNECK
Solar/Wind Helper
0.259
316316AC1-027 C
Solar/Wind Helper
0.606
316185AD1-033 GEN
Solar/Wind Helper
1.799
3145506HICKORY
Solar/Wind Helper
1.507
3145506HICKORY
Solar/Wind Helper
0.904
3145506HICKORY
Solar/Wind Helper
0.226
316236AE1-162_GEN
Solar/Wind Helper
0.498
316339AD2-160 GEN
Solar/Wind Helper
1.397
316018AA1-139 ULT2
Solar/Wind Helper
1.567
316017AA1-139 ULT1
Solar/Wind Helper
1.665
3137176SLIGO L2192
Solar/Wind Helper
1.432
3130086AYDLETT
Solar/Wind Helper
1.421
316033AB2-134 GEN
Solar/Wind Helper
1.19
315697AD1-025 GEN
Solar/Wind Helper
3.953
3146386ELIZ CT
Solar/Wind Helper
0.331
316240AF1-291 C
Solar/Wind Helper
0.444
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.318
316075AC2-137 C
Solar/Wind Helper
0.467
316077AC2-138 C
Solar/Wind Helper
0.286
316431W1029_GEN1
Solar/Wind Helper
1.225
316433W1029_GEN2
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3143526WINTERP
Solar/Wind Helper
1.499
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
966871AG1-558 GEN
Solar/Wind Helper
0.374
3144356SAPONY
Solar/Wind Helper
0.492
316468AD1-105 GEN
Solar/Wind Helper
1.305
3151031BRUNSWICKG2
50/50
8.374
970413AG2-270 GEN
50/50
40.637
3151591KERR 2
50/50
0.538
3144293JTRSVLE
50/50
0.8
970917AG2-570 GEN
Solar/Wind Harmer
167.695
316478AD1-087 GEN
Solar/Wind Harmer
4.227
316486AD2-202 GEN
Solar/Wind Harmer
1.238
970909AG2-566 GEN
Solar/Wind Harmer
3.291
316248AF1-058 C
Solar/Wind Harmer
1.043
960061AF2-297 GEN
Solar/Wind Harmer
17.305
316283AC2-100 C
Solar/Wind Harmer
2.965
971683AH1-343 GEN
Solar/Wind Harmer
13.39
316131AB2-060 GEN
Solar/Wind Harmer
3.076
964241AG1-285 GEN
Solar/Wind Harmer
22.038
315785AD2-033 C
Solar/Wind Harmer
6.282
970257AG2-171 GEN
Solar/Wind Harmer
10.326
959311AF2-222 GEN
Solar/Wind Harmer
28.597
963181AG1-167 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.449
942461AE2-259 GEN
Solar/Wind Harmer
3.824
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.375
270197AD1-017 GEN1
Solar/Wind Harmer
1.676
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.834
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.53
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.564
961601AG1-000A GEN
Solar/Wind Harmer
5.252
315773AC2-141 GEN
Solar/Wind Helper
9.163
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.058
3145336SMITFLD
Solar/Wind Helper
0.148
3146456SLIGO L269
Solar/Wind Helper
0.359
316382AG1-145 C
Solar/Wind Helper
0.469
315839AE2-212 C
Solar/Wind Helper
0.457
316320Y1-086
Solar/Wind Helper
0.148
316156AD2-030 GEN
Solar/Wind Helper
0.492
316280AD1-041 GEN
Solar/Wind Helper
1.092
3142946ENON
Solar/Wind Helper
0.105
316484AD2-074 GEN
Solar/Wind Helper
0.607
316404AE1-155 C
Solar/Wind Helper
2.624
316435W1029_GEN3
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3141906WESTMOR
Solar/Wind Helper
0.115
3146626S HERTFORD
Solar/Wind Helper
0.28
316473AC1-191 GEN
Solar/Wind Helper
1.696
3145273HOLLAND
Solar/Wind Helper
0.188
966881AG1-559 GEN
Solar/Wind Helper
0.329
3146376EDENTON
Solar/Wind Helper
0.226
315244AE2-183_ST
50/50
19.115
963041AG1-153 GEN
50/50
16.957
3151541CLOVER2
50/50
9.268
3151611KERR 4
50/50
0.538
3151621KERR 5
50/50
0.538
3151631KERR 6
50/50
0.538
3151641KERR 7
50/50
0.538
971967AH1-528 GEN
Solar/Wind Harmer
125.223
970085AG2-068 GEN
Solar/Wind Harmer
41.62
970581AG2-369 GEN
Solar/Wind Harmer
35.794
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.295
970865AG2-541 GEN
Solar/Wind Harmer
11.917
316239AB2-077_GEN
Solar/Wind Harmer
0.868
316238AB2-078_GEN
Solar/Wind Harmer
0.868
971443AH1-215 GEN
Solar/Wind Harmer
5.428
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.145
970681AG2-440 GEN
Solar/Wind Harmer
16.916
946301AF1-294 GEN
Solar/Wind Harmer
6.823
961791AG1-021 GEN
Solar/Wind Harmer
3.328
270455AD2-022 GEN
Solar/Wind Harmer
4.701
270457AD2-023 GEN
Solar/Wind Harmer
2.384
315657AE1-056 GEN
Solar/Wind Harmer
9.869
316123AC1-075 GEN
Solar/Wind Harmer
2.789
970165AG2-112 GEN
Solar/Wind Harmer
2.455
970163AG2-111 GEN
Solar/Wind Harmer
2.342
970831AG2-522 GEN
Solar/Wind Harmer
9.813
970285AG2-188 GEN
Solar/Wind Harmer
15.354
971845AH1-439 GEN
Solar/Wind Harmer
8.535
270069AE2-166 C O1
Solar/Wind Harmer
2.415
319010AE1-072 C
Solar/Wind Helper
4.079
3143316POE
Solar/Wind Helper
1.407
316305AF2-043 C
Solar/Wind Helper
0.473
316369SG1_INVT
Solar/Wind Helper
1.664
957831AF2-077 GEN
Solar/Wind Helper
0.466
316132AB2-190 GEN1
Solar/Wind Helper
1.933
316349AD2-085 GEN
Solar/Wind Helper
1.523
313526AB2-022
Solar/Wind Helper
0.505
957601AF2-054 GEN
Solar/Wind Helper
0.438
3141873WAN 176
Solar/Wind Helper
0.065
315662AE1-191 GEN
Solar/Wind Helper
1.747
315666AE1-190 GEN
Solar/Wind Helper
0.437
316059AD1-063 C
Solar/Wind Helper
0.326
3141913WHIT STONE
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3138133OCRAN
Solar/Wind Helper
0.097
3143873LANEXA
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.128
316321Z2-027
Solar/Wind Helper
0.487
3145176PASQUOTANK
Solar/Wind Helper
0.198
3141813NORNECK
Solar/Wind Helper
0.304
316312AB1-027
Solar/Wind Helper
0.556
316233AE1-074 FULL
Solar/Wind Helper
0.44
316223AC1-118
Solar/Wind Helper
0.438
316315AB2-025 C
Solar/Wind Helper
0.418
315611Z1-036_GEN2
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
3130156CHOWAN
Solar/Wind Helper
0.226
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.554
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.081
MECLTFEXP_MEC->PJM
CLTF
7.343
SIGELTFEXP_SIGE->PJM
CLTF
0.22
CPLELTFEXP_CPLE->PJM
CLTF
19.708
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.004
LAGNLTFEXP_LAGN->PJM
CLTF
14.626
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.161
TVALTFEXP_TVA->PJM
CLTF
7.294
NYPJM->LTFIMP_NY
CLTF
2.38
LGEELTFEXP_LGEE->PJM
CLTF
2.666
WECLTFEXP_WEC->PJM
CLTF
1.395
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 511T544_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T544_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.19 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5355.19
MW Contribution:4.52
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
10.962
3151051BRUNSWICKS1
50/50
17.232
3151021BRUNSWICKG1
50/50
8.303
971451AH1-221 GEN
50/50
25.218
3151531CLOVER1
50/50
9.227
3151601KERR 3
50/50
0.532
3151581KERR 1
50/50
0.19
3144293JTRSVLE
50/50
0.79
971629AH1-314 GEN
50/50
17.731
3151561HALLBR1
50/50
0.363
970919AG2-571 GEN
Solar/Wind Harmer
21.047
970087AG2-069 GEN
Solar/Wind Harmer
61.902
957481AF2-042 GEN
Solar/Wind Harmer
164.509
315693AD1-088 GEN
Solar/Wind Harmer
24.007
962491AG1-098 GEN
Solar/Wind Harmer
31.634
315687AD1-152 GEN
Solar/Wind Harmer
5.265
316003AC1-222 GEN
Solar/Wind Harmer
3.162
970401AG2-262 GEN
Solar/Wind Harmer
2.07
316237AB2-079_GEN
Solar/Wind Harmer
0.856
970685AG2-442 GEN
Solar/Wind Harmer
23.354
963171AG1-166 GEN
Solar/Wind Harmer
3.283
971563AH1-280 GEN
Solar/Wind Harmer
3.283
3146926FARMVIL
Solar/Wind Harmer
-0.014
971065AG2-659 GEN
Solar/Wind Harmer
11.094
316129AC1-054 GEN
Solar/Wind Harmer
1.827
970223AG2-152 GEN
Solar/Wind Harmer
17.059
270016AE1-250 BESS
Solar/Wind Harmer
2.815
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.528
316322AB2-045
Solar/Wind Harmer
0.506
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.477
270030AE2-140 GEN
Solar/Wind Harmer
19.567
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.809
316049AB1-081 GEN
Solar/Wind Harmer
1.448
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.244
316381AD1-082 GEN
Solar/Wind Helper
1.747
316375AC2-012 GEN
Solar/Wind Helper
0.879
3145336SMITFLD
Solar/Wind Helper
1.331
316458AB2-190 GEN2
Solar/Wind Helper
1.893
316159AE1-175 C
Solar/Wind Helper
0.497
316388AE2-253 GEN
Solar/Wind Helper
1.201
3142433PROV 92
Solar/Wind Helper
1.254
3142543TWELFTH
Solar/Wind Helper
0.03
3141766HARMONY
Solar/Wind Helper
0.062
3146456SLIGO L269
Solar/Wind Helper
0.308
3138133OCRAN
Solar/Wind Helper
0.185
316072AD1-144
Solar/Wind Helper
0.35
316246AF1-032 C
Solar/Wind Helper
0.342
964211AG1-282 GEN
Solar/Wind Helper
0.397
3141726DUNNSVL
Solar/Wind Helper
1.179
3143526WINTERP
Solar/Wind Helper
1.519
3142416OLDCHRC
Solar/Wind Helper
0.752
3143226MDLTHAN
Solar/Wind Helper
0.289
3142416OLDCHRC
Solar/Wind Helper
0.288
316337AD2-073 GEN
Solar/Wind Helper
0.434
3146516WINFALL
Solar/Wind Helper
0.813
3146516WINFALL
Solar/Wind Helper
0.251
315242AE2-183_GT2
50/50
10.962
315241AE2-183_GT1
50/50
10.894
972185AH1-677 GEN
50/50
39.518
3151041BRUNSWICKG3
50/50
8.303
972187AH1-678 GEN
50/50
19.053
3152661PLYWOOD A
50/50
0.663
970535AG2-341 GEN
50/50
4.519
3144293JTRSVLE
50/50
0.79
3144293JTRSVLE
50/50
0.665
970933AG2-581 GEN
Solar/Wind Harmer
58.334
970099AG2-077 GEN
Solar/Wind Harmer
65.804
971741AH1-377 GEN
Solar/Wind Harmer
43.523
970301AG2-198 GEN
Solar/Wind Harmer
17.145
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.775
316222AC1-221 GEN
Solar/Wind Harmer
3.182
962561AG1-105 GEN
Solar/Wind Harmer
17.536
939181AE1-148 GEN
Solar/Wind Harmer
16.186
313527AB2-043 GEN
Solar/Wind Harmer
4.576
970323AG2-213 GEN
Solar/Wind Harmer
13.574
971775AH1-396 GEN
Solar/Wind Harmer
1.933
316034AC1-036 C
Solar/Wind Harmer
0.503
958211AF2-115 GEN
Solar/Wind Harmer
4.103
963191AG1-168 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
14.918
270013AE1-250 PV
Solar/Wind Harmer
2.815
3146776BUCKING
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.37
316197AC1-042 GEN
Solar/Wind Harmer
1.797
942671AE2-283 GEN
Solar/Wind Harmer
4.838
316263AC1-034 GEN
Solar/Wind Harmer
6.29
961601AG1-000A GEN
Solar/Wind Harmer
5.16
316240AF1-291 C
Solar/Wind Helper
0.471
316036AC1-147 C
Solar/Wind Helper
0.511
316236AE1-162_GEN
Solar/Wind Helper
0.447
316316AC1-027 C
Solar/Wind Helper
0.524
3142956BIRDNECK
Solar/Wind Helper
0.223
316033AB2-134 GEN
Solar/Wind Helper
1.137
315697AD1-025 GEN
Solar/Wind Helper
3.779
316185AD1-033 GEN
Solar/Wind Helper
1.551
3145506HICKORY
Solar/Wind Helper
1.298
3145506HICKORY
Solar/Wind Helper
0.779
3145506HICKORY
Solar/Wind Helper
0.195
3144356SAPONY
Solar/Wind Helper
0.581
316339AD2-160 GEN
Solar/Wind Helper
1.201
316018AA1-139 ULT2
Solar/Wind Helper
1.346
316017AA1-139 ULT1
Solar/Wind Helper
1.43
3142946ENON
Solar/Wind Helper
0.031
3137176SLIGO L2192
Solar/Wind Helper
1.229
3130086AYDLETT
Solar/Wind Helper
1.219
316487AF1-042 GEN
Solar/Wind Helper
0.305
316075AC2-137 C
Solar/Wind Helper
0.459
316077AC2-138 C
Solar/Wind Helper
0.276
3143526WINTERP
Solar/Wind Helper
1.519
3146386ELIZ CT
Solar/Wind Helper
0.283
966871AG1-558 GEN
Solar/Wind Helper
0.376
316468AD1-105 GEN
Solar/Wind Helper
1.308
316431W1029_GEN1
Solar/Wind Helper
1.037
316433W1029_GEN2
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146626S HERTFORD
Solar/Wind Helper
0.236
3146626S HERTFORD
Solar/Wind Helper
0.236
3151031BRUNSWICKG2
50/50
8.303
970413AG2-270 GEN
50/50
40.265
3151591KERR 2
50/50
0.532
3144293JTRSVLE
50/50
0.79
970917AG2-570 GEN
Solar/Wind Harmer
166.275
316478AD1-087 GEN
Solar/Wind Harmer
4.189
316486AD2-202 GEN
Solar/Wind Harmer
1.227
970909AG2-566 GEN
Solar/Wind Harmer
3.255
316248AF1-058 C
Solar/Wind Harmer
1.033
960061AF2-297 GEN
Solar/Wind Harmer
17.135
316283AC2-100 C
Solar/Wind Harmer
2.94
971683AH1-343 GEN
Solar/Wind Harmer
13.259
316131AB2-060 GEN
Solar/Wind Harmer
3.032
964241AG1-285 GEN
Solar/Wind Harmer
21.724
315785AD2-033 C
Solar/Wind Harmer
6.194
970257AG2-171 GEN
Solar/Wind Harmer
10.181
959311AF2-222 GEN
Solar/Wind Harmer
28.197
963181AG1-167 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.081
971193AH1-056 GEN
Solar/Wind Harmer
16.225
942461AE2-259 GEN
Solar/Wind Harmer
3.773
3146926FARMVIL
Solar/Wind Harmer
-0.014
270018AE2-047 C O1
Solar/Wind Harmer
1.363
270197AD1-017 GEN1
Solar/Wind Harmer
1.661
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.802
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.477
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.551
961601AG1-000A GEN
Solar/Wind Harmer
5.225
315773AC2-141 GEN
Solar/Wind Helper
8.525
315839AE2-212 C
Solar/Wind Helper
0.497
3144536CHRHLND
Solar/Wind Helper
0.05
3144873MCLAUGH
Solar/Wind Helper
0.008
3145336SMITFLD
Solar/Wind Helper
0.133
316382AG1-145 C
Solar/Wind Helper
0.441
316156AD2-030 GEN
Solar/Wind Helper
0.47
3142946ENON
Solar/Wind Helper
0.104
316280AD1-041 GEN
Solar/Wind Helper
1.046
3146456SLIGO L269
Solar/Wind Helper
0.308
316484AD2-074 GEN
Solar/Wind Helper
0.583
316404AE1-155 C
Solar/Wind Helper
2.523
316320Y1-086
Solar/Wind Helper
0.126
316473AC1-191 GEN
Solar/Wind Helper
1.704
3141906WESTMOR
Solar/Wind Helper
0.111
316435W1029_GEN3
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
966881AG1-559 GEN
Solar/Wind Helper
0.328
3146626S HERTFORD
Solar/Wind Helper
0.236
315244AE2-183_ST
50/50
18.952
963041AG1-153 GEN
50/50
16.812
3151541CLOVER2
50/50
9.183
3151611KERR 4
50/50
0.532
3151621KERR 5
50/50
0.532
3151631KERR 6
50/50
0.532
3151641KERR 7
50/50
0.532
971967AH1-528 GEN
Solar/Wind Harmer
124.141
970085AG2-068 GEN
Solar/Wind Harmer
41.268
970581AG2-369 GEN
Solar/Wind Harmer
35.491
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.271
970865AG2-541 GEN
Solar/Wind Harmer
11.801
316239AB2-077_GEN
Solar/Wind Harmer
0.856
316238AB2-078_GEN
Solar/Wind Harmer
0.856
971443AH1-215 GEN
Solar/Wind Harmer
5.352
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
20.851
970681AG2-440 GEN
Solar/Wind Harmer
16.681
946301AF1-294 GEN
Solar/Wind Harmer
6.73
961791AG1-021 GEN
Solar/Wind Harmer
3.283
270455AD2-022 GEN
Solar/Wind Harmer
4.664
270457AD2-023 GEN
Solar/Wind Harmer
2.365
315657AE1-056 GEN
Solar/Wind Harmer
9.735
316123AC1-075 GEN
Solar/Wind Harmer
2.761
970165AG2-112 GEN
Solar/Wind Harmer
2.431
970163AG2-111 GEN
Solar/Wind Harmer
2.319
970831AG2-522 GEN
Solar/Wind Harmer
9.696
970285AG2-188 GEN
Solar/Wind Harmer
15.118
971845AH1-439 GEN
Solar/Wind Harmer
8.397
270069AE2-166 C O1
Solar/Wind Harmer
2.394
3143316POE
Solar/Wind Helper
1.57
316132AB2-190 GEN1
Solar/Wind Helper
1.893
316369SG1_INVT
Solar/Wind Helper
1.59
957831AF2-077 GEN
Solar/Wind Helper
0.437
316315AB2-025 C
Solar/Wind Helper
0.494
957601AF2-054 GEN
Solar/Wind Helper
0.418
3141873WAN 176
Solar/Wind Helper
0.062
315662AE1-191 GEN
Solar/Wind Helper
1.674
315666AE1-190 GEN
Solar/Wind Helper
0.419
3143873LANEXA
Solar/Wind Helper
0.186
316059AD1-063 C
Solar/Wind Helper
0.312
3141913WHIT STONE
Solar/Wind Helper
0.309
3138133OCRAN
Solar/Wind Helper
0.093
3141783LANCAST
Solar/Wind Helper
0.184
3141783LANCAST
Solar/Wind Helper
0.123
319010AE1-072 C
Solar/Wind Helper
3.5
316349AD2-085 GEN
Solar/Wind Helper
1.396
316305AF2-043 C
Solar/Wind Helper
0.402
3141813NORNECK
Solar/Wind Helper
0.293
316233AE1-074 FULL
Solar/Wind Helper
0.446
316312AB1-027
Solar/Wind Helper
0.55
313526AB2-022
Solar/Wind Helper
0.431
316223AC1-118
Solar/Wind Helper
0.424
3146486SUNBURY
Solar/Wind Helper
0.274
3146486SUNBURY
Solar/Wind Helper
0.274
316321Z2-027
Solar/Wind Helper
0.414
3145176PASQUOTANK
Solar/Wind Helper
0.168
CBM West 1LTFEXP_CBM-W1->PJM
CBM
48.979
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.858
MECLTFEXP_MEC->PJM
CLTF
7.267
SIGELTFEXP_SIGE->PJM
CLTF
0.218
CPLELTFEXP_CPLE->PJM
CLTF
19.58
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.279
LAGNLTFEXP_LAGN->PJM
CLTF
14.499
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.842
TVALTFEXP_TVA->PJM
CLTF
7.231
NYPJM->LTFIMP_NY
CLTF
2.38
LGEELTFEXP_LGEE->PJM
CLTF
2.637
WECLTFEXP_WEC->PJM
CLTF
1.38
AG2-052LTFEXP_AG2-052->PJM
LTF
0.074
AH1-155LTFEXP_AH1-155->PJM
LTF
0.111

Details for AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.0 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1248.61
MW Contribution:5.15
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
10.81
3144293JTRSVLE
50/50
1.009
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3147043LAWRENC
50/50
1.435
3151561HALLBR1
50/50
0.347
3151931BEARGRDN S1
50/50
1.382
3151911BEARGRDN G1
50/50
1.071
315687AD1-152 GEN
Solar/Wind Harmer
7.754
316003AC1-222 GEN
Solar/Wind Harmer
5.366
957481AF2-042 GEN
Solar/Wind Harmer
169.755
315693AD1-088 GEN
Solar/Wind Harmer
25.249
962491AG1-098 GEN
Solar/Wind Harmer
33.372
970401AG2-262 GEN
Solar/Wind Harmer
3.252
316237AB2-079_GEN
Solar/Wind Harmer
1.108
970685AG2-442 GEN
Solar/Wind Harmer
29.934
963171AG1-166 GEN
Solar/Wind Harmer
4.197
971563AH1-280 GEN
Solar/Wind Harmer
4.197
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.353
316322AB2-045
Solar/Wind Harmer
0.758
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.877
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.335
971795AH1-408 GEN
Solar/Wind Harmer
10.57
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.525
971377AH1-170 GEN
Solar/Wind Harmer
1.453
3147623JAMES R
Solar/Wind Harmer
0.18
970937AG2-583 GEN
Solar/Wind Harmer
7.555
960081AF2-299 GEN
Solar/Wind Harmer
0.925
316336AC2-165 C
Solar/Wind Harmer
1.327
3143336POWHATN
Solar/Wind Harmer
0.773
3152661PLYWOOD A
50/50
1.086
3144293JTRSVLE
50/50
1.009
3144293JTRSVLE
50/50
0.85
970535AG2-341 GEN
50/50
5.15
316222AC1-221 GEN
Solar/Wind Harmer
10.229
970099AG2-077 GEN
Solar/Wind Harmer
67.902
970933AG2-581 GEN
Solar/Wind Harmer
50.214
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.644
962561AG1-105 GEN
Solar/Wind Harmer
26.877
971741AH1-377 GEN
Solar/Wind Harmer
48.375
970301AG2-198 GEN
Solar/Wind Harmer
19.484
313527AB2-043 GEN
Solar/Wind Harmer
5.914
970323AG2-213 GEN
Solar/Wind Harmer
17.447
971775AH1-396 GEN
Solar/Wind Harmer
2.485
316034AC1-036 C
Solar/Wind Harmer
0.647
958211AF2-115 GEN
Solar/Wind Harmer
5.246
963191AG1-168 GEN
Solar/Wind Harmer
3.148
942751AE2-291 GEN
Solar/Wind Harmer
21.29
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.128
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.959
316197AC1-042 GEN
Solar/Wind Harmer
1.485
942671AE2-283 GEN
Solar/Wind Harmer
3.997
971489AH1-241 GEN
Solar/Wind Harmer
6.897
315821AE2-092 GEN
Solar/Wind Harmer
1.796
316181AB2-040 GEN
Solar/Wind Harmer
1.066
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.786
3145593CAROLNA
Solar/Wind Harmer
0.058
970413AG2-270 GEN
50/50
47.174
3144293JTRSVLE
50/50
1.009
3151591KERR 2
50/50
0.537
3151921BEARGRDN G2
50/50
1.071
316248AF1-058 C
Solar/Wind Harmer
1.793
960061AF2-297 GEN
Solar/Wind Harmer
29.749
316478AD1-087 GEN
Solar/Wind Harmer
4.929
316486AD2-202 GEN
Solar/Wind Harmer
1.444
971683AH1-343 GEN
Solar/Wind Harmer
22.008
970909AG2-566 GEN
Solar/Wind Harmer
3.699
316131AB2-060 GEN
Solar/Wind Harmer
3.917
964241AG1-285 GEN
Solar/Wind Harmer
28.021
315785AD2-033 C
Solar/Wind Harmer
7.969
970257AG2-171 GEN
Solar/Wind Harmer
13.085
959311AF2-222 GEN
Solar/Wind Harmer
36.211
963181AG1-167 GEN
Solar/Wind Harmer
3.148
3147133PAMPLIN
Solar/Wind Harmer
-0.104
971193AH1-056 GEN
Solar/Wind Harmer
20.705
942461AE2-259 GEN
Solar/Wind Harmer
4.788
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.525
970221AG2-151 GEN
Solar/Wind Harmer
7.265
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.614
316313AB2-026
Solar/Wind Harmer
0.176
316258AE1-075 C
Solar/Wind Harmer
0.158
316405AF2-144 C
Solar/Wind Harmer
0.167
3143336POWHATN
Solar/Wind Harmer
0.657
316283AC2-100 C
Solar/Wind Helper
2.324
3151541CLOVER2
50/50
10.758
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
972205AH1-687 GEN
50/50
5.223
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.765
971967AH1-528 GEN
Solar/Wind Harmer
100.698
970865AG2-541 GEN
Solar/Wind Harmer
19.076
316123AC1-075 GEN
Solar/Wind Harmer
4.171
970165AG2-112 GEN
Solar/Wind Harmer
3.672
970163AG2-111 GEN
Solar/Wind Harmer
3.503
316239AB2-077_GEN
Solar/Wind Harmer
1.108
316238AB2-078_GEN
Solar/Wind Harmer
1.108
971443AH1-215 GEN
Solar/Wind Harmer
6.88
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.727
970681AG2-440 GEN
Solar/Wind Harmer
21.381
946301AF1-294 GEN
Solar/Wind Harmer
8.604
961791AG1-021 GEN
Solar/Wind Harmer
4.197
315657AE1-056 GEN
Solar/Wind Harmer
12.423
970285AG2-188 GEN
Solar/Wind Harmer
21.434
971845AH1-439 GEN
Solar/Wind Harmer
12.337
970831AG2-522 GEN
Solar/Wind Harmer
10.013
971447AH1-217 GEN
Solar/Wind Harmer
3.92
270494AE1-108_GEN
Solar/Wind Harmer
2.506
946281AF1-292 GEN
Solar/Wind Harmer
0.184
316087AB2-174 GEN
Solar/Wind Harmer
1.115
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.376
270457AD2-023 GEN
Solar/Wind Helper
0.907
VTFLTFEXP_VFT->PJM
CMTX
1.127
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.809
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.962
G-007ALTFEXP_G-007A->PJM
CMTX
0.429
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.343
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.85
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.677
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.375

Details for AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.45 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1220.46
MW Contribution:5.14
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
10.79
3144293JTRSVLE
50/50
1.008
3151601KERR 3
50/50
0.535
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.434
3151561HALLBR1
50/50
0.346
3151931BEARGRDN S1
50/50
1.386
3151911BEARGRDN G1
50/50
1.074
315687AD1-152 GEN
Solar/Wind Harmer
7.739
316003AC1-222 GEN
Solar/Wind Harmer
5.355
957481AF2-042 GEN
Solar/Wind Harmer
169.439
315693AD1-088 GEN
Solar/Wind Harmer
25.203
962491AG1-098 GEN
Solar/Wind Harmer
33.312
970401AG2-262 GEN
Solar/Wind Harmer
3.246
316237AB2-079_GEN
Solar/Wind Harmer
1.105
970685AG2-442 GEN
Solar/Wind Harmer
29.883
963171AG1-166 GEN
Solar/Wind Harmer
4.19
971563AH1-280 GEN
Solar/Wind Harmer
4.19
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.32
316322AB2-045
Solar/Wind Harmer
0.758
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.872
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.349
971795AH1-408 GEN
Solar/Wind Harmer
10.568
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.498
971377AH1-170 GEN
Solar/Wind Harmer
1.457
3147623JAMES R
Solar/Wind Harmer
0.18
970937AG2-583 GEN
Solar/Wind Harmer
7.594
960081AF2-299 GEN
Solar/Wind Harmer
0.927
316336AC2-165 C
Solar/Wind Harmer
1.341
3143336POWHATN
Solar/Wind Harmer
0.784
3152661PLYWOOD A
50/50
1.084
3144293JTRSVLE
50/50
1.008
3144293JTRSVLE
50/50
0.849
970535AG2-341 GEN
50/50
5.137
316222AC1-221 GEN
Solar/Wind Harmer
10.209
970099AG2-077 GEN
Solar/Wind Harmer
67.776
970933AG2-581 GEN
Solar/Wind Harmer
50.121
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.622
962561AG1-105 GEN
Solar/Wind Harmer
26.822
971741AH1-377 GEN
Solar/Wind Harmer
48.301
970301AG2-198 GEN
Solar/Wind Harmer
19.456
313527AB2-043 GEN
Solar/Wind Harmer
5.902
970323AG2-213 GEN
Solar/Wind Harmer
17.415
971775AH1-396 GEN
Solar/Wind Harmer
2.48
316034AC1-036 C
Solar/Wind Harmer
0.646
958211AF2-115 GEN
Solar/Wind Harmer
5.238
963191AG1-168 GEN
Solar/Wind Harmer
3.143
942751AE2-291 GEN
Solar/Wind Harmer
21.229
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.08
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.947
316197AC1-042 GEN
Solar/Wind Harmer
1.476
942671AE2-283 GEN
Solar/Wind Harmer
3.973
971489AH1-241 GEN
Solar/Wind Harmer
6.915
315821AE2-092 GEN
Solar/Wind Harmer
1.803
316181AB2-040 GEN
Solar/Wind Harmer
1.066
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.785
3145593CAROLNA
Solar/Wind Harmer
0.058
970413AG2-270 GEN
50/50
47.085
3144293JTRSVLE
50/50
1.008
3151591KERR 2
50/50
0.535
3151921BEARGRDN G2
50/50
1.074
316248AF1-058 C
Solar/Wind Harmer
1.789
960061AF2-297 GEN
Solar/Wind Harmer
29.687
316478AD1-087 GEN
Solar/Wind Harmer
4.92
316486AD2-202 GEN
Solar/Wind Harmer
1.441
971683AH1-343 GEN
Solar/Wind Harmer
21.959
970909AG2-566 GEN
Solar/Wind Harmer
3.694
316131AB2-060 GEN
Solar/Wind Harmer
3.909
964241AG1-285 GEN
Solar/Wind Harmer
27.966
315785AD2-033 C
Solar/Wind Harmer
7.954
970257AG2-171 GEN
Solar/Wind Harmer
13.061
959311AF2-222 GEN
Solar/Wind Harmer
36.146
963181AG1-167 GEN
Solar/Wind Harmer
3.143
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.674
942461AE2-259 GEN
Solar/Wind Harmer
4.782
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.498
970221AG2-151 GEN
Solar/Wind Harmer
7.284
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.615
316313AB2-026
Solar/Wind Harmer
0.178
316258AE1-075 C
Solar/Wind Harmer
0.16
316405AF2-144 C
Solar/Wind Harmer
0.169
3143336POWHATN
Solar/Wind Harmer
0.666
316283AC2-100 C
Solar/Wind Helper
2.343
270018AE2-047 C O1
Solar/Wind Helper
0.4
3151541CLOVER2
50/50
10.738
3151611KERR 4
50/50
0.535
3151621KERR 5
50/50
0.535
3151631KERR 6
50/50
0.535
3151641KERR 7
50/50
0.535
972205AH1-687 GEN
50/50
5.237
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.757
971967AH1-528 GEN
Solar/Wind Harmer
100.512
970865AG2-541 GEN
Solar/Wind Harmer
19.031
316123AC1-075 GEN
Solar/Wind Harmer
4.16
970165AG2-112 GEN
Solar/Wind Harmer
3.663
970163AG2-111 GEN
Solar/Wind Harmer
3.494
316239AB2-077_GEN
Solar/Wind Harmer
1.105
316238AB2-078_GEN
Solar/Wind Harmer
1.105
971443AH1-215 GEN
Solar/Wind Harmer
6.867
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.682
970681AG2-440 GEN
Solar/Wind Harmer
21.345
946301AF1-294 GEN
Solar/Wind Harmer
8.59
961791AG1-021 GEN
Solar/Wind Harmer
4.19
315657AE1-056 GEN
Solar/Wind Harmer
12.405
970285AG2-188 GEN
Solar/Wind Harmer
21.428
971845AH1-439 GEN
Solar/Wind Harmer
12.335
970831AG2-522 GEN
Solar/Wind Harmer
9.984
971447AH1-217 GEN
Solar/Wind Harmer
3.931
270494AE1-108_GEN
Solar/Wind Harmer
2.509
946281AF1-292 GEN
Solar/Wind Harmer
0.185
316087AB2-174 GEN
Solar/Wind Harmer
1.116
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.395
270457AD2-023 GEN
Solar/Wind Helper
0.919
VTFLTFEXP_VFT->PJM
CMTX
1.375
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.857
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.08
G-007ALTFEXP_G-007A->PJM
CMTX
0.522
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.505
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.869
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.738
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.476

Details for AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.42 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1220.19
MW Contribution:5.14
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
10.79
3144293JTRSVLE
50/50
1.008
3151601KERR 3
50/50
0.535
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.434
3151561HALLBR1
50/50
0.346
3151931BEARGRDN S1
50/50
1.386
3151911BEARGRDN G1
50/50
1.074
315687AD1-152 GEN
Solar/Wind Harmer
7.739
316003AC1-222 GEN
Solar/Wind Harmer
5.355
957481AF2-042 GEN
Solar/Wind Harmer
169.439
315693AD1-088 GEN
Solar/Wind Harmer
25.203
962491AG1-098 GEN
Solar/Wind Harmer
33.312
970401AG2-262 GEN
Solar/Wind Harmer
3.246
316237AB2-079_GEN
Solar/Wind Harmer
1.105
970685AG2-442 GEN
Solar/Wind Harmer
29.883
963171AG1-166 GEN
Solar/Wind Harmer
4.19
971563AH1-280 GEN
Solar/Wind Harmer
4.19
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.32
316322AB2-045
Solar/Wind Harmer
0.758
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.872
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.349
971795AH1-408 GEN
Solar/Wind Harmer
10.568
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.498
971377AH1-170 GEN
Solar/Wind Harmer
1.457
3147623JAMES R
Solar/Wind Harmer
0.18
970937AG2-583 GEN
Solar/Wind Harmer
7.594
960081AF2-299 GEN
Solar/Wind Harmer
0.927
316336AC2-165 C
Solar/Wind Harmer
1.341
3143336POWHATN
Solar/Wind Harmer
0.784
3152661PLYWOOD A
50/50
1.084
3144293JTRSVLE
50/50
1.008
3144293JTRSVLE
50/50
0.849
970535AG2-341 GEN
50/50
5.137
316222AC1-221 GEN
Solar/Wind Harmer
10.209
970099AG2-077 GEN
Solar/Wind Harmer
67.776
970933AG2-581 GEN
Solar/Wind Harmer
50.121
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.622
962561AG1-105 GEN
Solar/Wind Harmer
26.822
971741AH1-377 GEN
Solar/Wind Harmer
48.301
970301AG2-198 GEN
Solar/Wind Harmer
19.456
313527AB2-043 GEN
Solar/Wind Harmer
5.902
970323AG2-213 GEN
Solar/Wind Harmer
17.415
971775AH1-396 GEN
Solar/Wind Harmer
2.48
316034AC1-036 C
Solar/Wind Harmer
0.646
958211AF2-115 GEN
Solar/Wind Harmer
5.238
963191AG1-168 GEN
Solar/Wind Harmer
3.143
942751AE2-291 GEN
Solar/Wind Harmer
21.229
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.08
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.947
316197AC1-042 GEN
Solar/Wind Harmer
1.476
942671AE2-283 GEN
Solar/Wind Harmer
3.973
971489AH1-241 GEN
Solar/Wind Harmer
6.915
315821AE2-092 GEN
Solar/Wind Harmer
1.803
316181AB2-040 GEN
Solar/Wind Harmer
1.066
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.785
3145593CAROLNA
Solar/Wind Harmer
0.058
970413AG2-270 GEN
50/50
47.085
3144293JTRSVLE
50/50
1.008
3151591KERR 2
50/50
0.535
3151921BEARGRDN G2
50/50
1.074
316248AF1-058 C
Solar/Wind Harmer
1.789
960061AF2-297 GEN
Solar/Wind Harmer
29.687
316478AD1-087 GEN
Solar/Wind Harmer
4.92
316486AD2-202 GEN
Solar/Wind Harmer
1.441
971683AH1-343 GEN
Solar/Wind Harmer
21.959
970909AG2-566 GEN
Solar/Wind Harmer
3.694
316131AB2-060 GEN
Solar/Wind Harmer
3.909
964241AG1-285 GEN
Solar/Wind Harmer
27.966
315785AD2-033 C
Solar/Wind Harmer
7.954
970257AG2-171 GEN
Solar/Wind Harmer
13.061
959311AF2-222 GEN
Solar/Wind Harmer
36.146
963181AG1-167 GEN
Solar/Wind Harmer
3.143
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.674
942461AE2-259 GEN
Solar/Wind Harmer
4.782
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.498
970221AG2-151 GEN
Solar/Wind Harmer
7.284
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.615
316313AB2-026
Solar/Wind Harmer
0.178
316258AE1-075 C
Solar/Wind Harmer
0.16
316405AF2-144 C
Solar/Wind Harmer
0.169
3143336POWHATN
Solar/Wind Harmer
0.666
316283AC2-100 C
Solar/Wind Helper
2.343
270018AE2-047 C O1
Solar/Wind Helper
0.4
3151541CLOVER2
50/50
10.738
3151611KERR 4
50/50
0.535
3151621KERR 5
50/50
0.535
3151631KERR 6
50/50
0.535
3151641KERR 7
50/50
0.535
972205AH1-687 GEN
50/50
5.237
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.757
971967AH1-528 GEN
Solar/Wind Harmer
100.512
970865AG2-541 GEN
Solar/Wind Harmer
19.031
316123AC1-075 GEN
Solar/Wind Harmer
4.16
970165AG2-112 GEN
Solar/Wind Harmer
3.663
970163AG2-111 GEN
Solar/Wind Harmer
3.494
316239AB2-077_GEN
Solar/Wind Harmer
1.105
316238AB2-078_GEN
Solar/Wind Harmer
1.105
971443AH1-215 GEN
Solar/Wind Harmer
6.867
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.682
970681AG2-440 GEN
Solar/Wind Harmer
21.345
946301AF1-294 GEN
Solar/Wind Harmer
8.59
961791AG1-021 GEN
Solar/Wind Harmer
4.19
315657AE1-056 GEN
Solar/Wind Harmer
12.405
970285AG2-188 GEN
Solar/Wind Harmer
21.428
971845AH1-439 GEN
Solar/Wind Harmer
12.335
970831AG2-522 GEN
Solar/Wind Harmer
9.984
971447AH1-217 GEN
Solar/Wind Harmer
3.931
270494AE1-108_GEN
Solar/Wind Harmer
2.509
946281AF1-292 GEN
Solar/Wind Harmer
0.185
316087AB2-174 GEN
Solar/Wind Harmer
1.116
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.395
270457AD2-023 GEN
Solar/Wind Helper
0.919
VTFLTFEXP_VFT->PJM
CMTX
1.375
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.857
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.08
G-007ALTFEXP_G-007A->PJM
CMTX
0.522
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.505
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.869
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.738
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.476

Details for AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.84 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1202.69
MW Contribution:5.14
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
10.912
3144293JTRSVLE
50/50
1.003
3151601KERR 3
50/50
0.535
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.433
3151561HALLBR1
50/50
0.349
3151931BEARGRDN S1
50/50
1.364
3151911BEARGRDN G1
50/50
1.057
315687AD1-152 GEN
Solar/Wind Harmer
7.805
957481AF2-042 GEN
Solar/Wind Harmer
172.899
316003AC1-222 GEN
Solar/Wind Harmer
5.386
970401AG2-262 GEN
Solar/Wind Harmer
3.259
315693AD1-088 GEN
Solar/Wind Harmer
24.873
962491AG1-098 GEN
Solar/Wind Harmer
32.876
316237AB2-079_GEN
Solar/Wind Harmer
1.106
970685AG2-442 GEN
Solar/Wind Harmer
29.769
963171AG1-166 GEN
Solar/Wind Harmer
4.169
971563AH1-280 GEN
Solar/Wind Harmer
4.169
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.328
316322AB2-045
Solar/Wind Harmer
0.749
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.873
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.24
971795AH1-408 GEN
Solar/Wind Harmer
10.551
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.548
971377AH1-170 GEN
Solar/Wind Harmer
1.434
3147623JAMES R
Solar/Wind Harmer
0.178
970937AG2-583 GEN
Solar/Wind Harmer
7.455
960081AF2-299 GEN
Solar/Wind Harmer
0.924
316336AC2-165 C
Solar/Wind Harmer
1.309
3143336POWHATN
Solar/Wind Harmer
0.763
3151541CLOVER2
50/50
10.86
3151611KERR 4
50/50
0.535
3151621KERR 5
50/50
0.535
3151631KERR 6
50/50
0.535
3151641KERR 7
50/50
0.535
972205AH1-687 GEN
50/50
5.155
3147173SINAI
Solar/Wind Harmer
-0.06
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.776
970865AG2-541 GEN
Solar/Wind Harmer
19.147
316123AC1-075 GEN
Solar/Wind Harmer
4.187
970165AG2-112 GEN
Solar/Wind Harmer
3.686
970163AG2-111 GEN
Solar/Wind Harmer
3.517
316239AB2-077_GEN
Solar/Wind Harmer
1.106
316238AB2-078_GEN
Solar/Wind Harmer
1.106
971443AH1-215 GEN
Solar/Wind Harmer
6.851
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.58
970681AG2-440 GEN
Solar/Wind Harmer
21.264
946301AF1-294 GEN
Solar/Wind Harmer
8.547
961791AG1-021 GEN
Solar/Wind Harmer
4.169
315657AE1-056 GEN
Solar/Wind Harmer
12.33
970285AG2-188 GEN
Solar/Wind Harmer
21.156
971845AH1-439 GEN
Solar/Wind Harmer
12.177
970831AG2-522 GEN
Solar/Wind Harmer
9.991
971447AH1-217 GEN
Solar/Wind Harmer
3.869
3152661PLYWOOD A
50/50
1.089
3144293JTRSVLE
50/50
1.003
3144293JTRSVLE
50/50
0.844
970535AG2-341 GEN
50/50
5.14
316222AC1-221 GEN
Solar/Wind Harmer
10.244
970099AG2-077 GEN
Solar/Wind Harmer
69.159
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.665
962561AG1-105 GEN
Solar/Wind Harmer
26.917
971741AH1-377 GEN
Solar/Wind Harmer
47.685
970301AG2-198 GEN
Solar/Wind Harmer
19.211
313527AB2-043 GEN
Solar/Wind Harmer
5.903
970323AG2-213 GEN
Solar/Wind Harmer
17.371
971775AH1-396 GEN
Solar/Wind Harmer
2.474
316034AC1-036 C
Solar/Wind Harmer
0.644
942751AE2-291 GEN
Solar/Wind Harmer
21.373
958211AF2-115 GEN
Solar/Wind Harmer
5.211
963191AG1-168 GEN
Solar/Wind Harmer
3.127
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.09
3146776BUCKING
Solar/Wind Harmer
-0.089
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.968
316197AC1-042 GEN
Solar/Wind Harmer
1.492
942671AE2-283 GEN
Solar/Wind Harmer
4.017
971489AH1-241 GEN
Solar/Wind Harmer
6.809
315821AE2-092 GEN
Solar/Wind Harmer
1.772
316181AB2-040 GEN
Solar/Wind Harmer
1.064
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.785
3145593CAROLNA
Solar/Wind Harmer
0.058
970413AG2-270 GEN
50/50
47.618
3144293JTRSVLE
50/50
1.003
3151591KERR 2
50/50
0.535
3151921BEARGRDN G2
50/50
1.057
316248AF1-058 C
Solar/Wind Harmer
1.799
960061AF2-297 GEN
Solar/Wind Harmer
29.857
316478AD1-087 GEN
Solar/Wind Harmer
4.976
316486AD2-202 GEN
Solar/Wind Harmer
1.457
971683AH1-343 GEN
Solar/Wind Harmer
22.089
970909AG2-566 GEN
Solar/Wind Harmer
3.648
316131AB2-060 GEN
Solar/Wind Harmer
3.91
964241AG1-285 GEN
Solar/Wind Harmer
27.945
315785AD2-033 C
Solar/Wind Harmer
7.938
970257AG2-171 GEN
Solar/Wind Harmer
13.028
959311AF2-222 GEN
Solar/Wind Harmer
36.042
963181AG1-167 GEN
Solar/Wind Harmer
3.127
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.55
942461AE2-259 GEN
Solar/Wind Harmer
4.741
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.548
970221AG2-151 GEN
Solar/Wind Harmer
7.172
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.613
316313AB2-026
Solar/Wind Harmer
0.173
316258AE1-075 C
Solar/Wind Harmer
0.156
316405AF2-144 C
Solar/Wind Harmer
0.165
3143336POWHATN
Solar/Wind Harmer
0.648
316283AC2-100 C
Solar/Wind Helper
2.31
270494AE1-108_GEN
Solar/Wind Harmer
2.477
946281AF1-292 GEN
Solar/Wind Harmer
0.184
316087AB2-174 GEN
Solar/Wind Harmer
1.113
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.367
270457AD2-023 GEN
Solar/Wind Helper
0.901
VTFLTFEXP_VFT->PJM
CMTX
1.071
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.798
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.933
G-007ALTFEXP_G-007A->PJM
CMTX
0.408
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.306
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.845
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.662
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.353

Details for AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.84 %
Rating:1105.0 MVA
Rating Type:C
MVA to Mitigate:1202.63
MW Contribution:5.14
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
10.911
3144293JTRSVLE
50/50
1.003
3151601KERR 3
50/50
0.535
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.433
3151561HALLBR1
50/50
0.349
3151931BEARGRDN S1
50/50
1.364
3151911BEARGRDN G1
50/50
1.057
315687AD1-152 GEN
Solar/Wind Harmer
7.805
957481AF2-042 GEN
Solar/Wind Harmer
172.875
316003AC1-222 GEN
Solar/Wind Harmer
5.386
970401AG2-262 GEN
Solar/Wind Harmer
3.259
315693AD1-088 GEN
Solar/Wind Harmer
24.876
962491AG1-098 GEN
Solar/Wind Harmer
32.88
316237AB2-079_GEN
Solar/Wind Harmer
1.106
970685AG2-442 GEN
Solar/Wind Harmer
29.77
963171AG1-166 GEN
Solar/Wind Harmer
4.169
971563AH1-280 GEN
Solar/Wind Harmer
4.169
3152661PLYWOOD A
50/50
1.089
3144293JTRSVLE
50/50
1.003
3144293JTRSVLE
50/50
0.844
970535AG2-341 GEN
50/50
5.14
316222AC1-221 GEN
Solar/Wind Harmer
10.244
970099AG2-077 GEN
Solar/Wind Harmer
69.15
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.664
962561AG1-105 GEN
Solar/Wind Harmer
26.917
971741AH1-377 GEN
Solar/Wind Harmer
47.691
970301AG2-198 GEN
Solar/Wind Harmer
19.213
313527AB2-043 GEN
Solar/Wind Harmer
5.903
970323AG2-213 GEN
Solar/Wind Harmer
17.372
971775AH1-396 GEN
Solar/Wind Harmer
2.474
316034AC1-036 C
Solar/Wind Harmer
0.644
942751AE2-291 GEN
Solar/Wind Harmer
21.372
958211AF2-115 GEN
Solar/Wind Harmer
5.212
963191AG1-168 GEN
Solar/Wind Harmer
3.127
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.09
970413AG2-270 GEN
50/50
47.615
3144293JTRSVLE
50/50
1.003
3151591KERR 2
50/50
0.535
3151921BEARGRDN G2
50/50
1.057
316248AF1-058 C
Solar/Wind Harmer
1.799
960061AF2-297 GEN
Solar/Wind Harmer
29.856
316478AD1-087 GEN
Solar/Wind Harmer
4.975
316486AD2-202 GEN
Solar/Wind Harmer
1.457
971683AH1-343 GEN
Solar/Wind Harmer
22.089
970909AG2-566 GEN
Solar/Wind Harmer
3.648
316131AB2-060 GEN
Solar/Wind Harmer
3.91
964241AG1-285 GEN
Solar/Wind Harmer
27.945
315785AD2-033 C
Solar/Wind Harmer
7.938
970257AG2-171 GEN
Solar/Wind Harmer
13.029
959311AF2-222 GEN
Solar/Wind Harmer
36.043
963181AG1-167 GEN
Solar/Wind Harmer
3.127
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.551
942461AE2-259 GEN
Solar/Wind Harmer
4.741
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.328
316322AB2-045
Solar/Wind Harmer
0.749
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.873
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.24
971795AH1-408 GEN
Solar/Wind Harmer
10.551
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.548
971377AH1-170 GEN
Solar/Wind Harmer
1.435
3147623JAMES R
Solar/Wind Harmer
0.178
970937AG2-583 GEN
Solar/Wind Harmer
7.456
960081AF2-299 GEN
Solar/Wind Harmer
0.924
316336AC2-165 C
Solar/Wind Harmer
1.309
3143336POWHATN
Solar/Wind Harmer
0.763
3146776BUCKING
Solar/Wind Harmer
-0.089
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.968
316197AC1-042 GEN
Solar/Wind Harmer
1.492
942671AE2-283 GEN
Solar/Wind Harmer
4.017
971489AH1-241 GEN
Solar/Wind Harmer
6.81
315821AE2-092 GEN
Solar/Wind Harmer
1.772
316181AB2-040 GEN
Solar/Wind Harmer
1.064
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.785
3145593CAROLNA
Solar/Wind Harmer
0.058
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.548
970221AG2-151 GEN
Solar/Wind Harmer
7.173
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.613
316313AB2-026
Solar/Wind Harmer
0.173
316258AE1-075 C
Solar/Wind Harmer
0.156
316405AF2-144 C
Solar/Wind Harmer
0.165
3143336POWHATN
Solar/Wind Harmer
0.648
316283AC2-100 C
Solar/Wind Helper
2.31
3151541CLOVER2
50/50
10.859
3151611KERR 4
50/50
0.535
3151621KERR 5
50/50
0.535
3151631KERR 6
50/50
0.535
3151641KERR 7
50/50
0.535
972205AH1-687 GEN
50/50
5.156
3147173SINAI
Solar/Wind Harmer
-0.06
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.775
970865AG2-541 GEN
Solar/Wind Harmer
19.147
316123AC1-075 GEN
Solar/Wind Harmer
4.187
970165AG2-112 GEN
Solar/Wind Harmer
3.686
970163AG2-111 GEN
Solar/Wind Harmer
3.517
316239AB2-077_GEN
Solar/Wind Harmer
1.106
316238AB2-078_GEN
Solar/Wind Harmer
1.106
971443AH1-215 GEN
Solar/Wind Harmer
6.851
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.581
970681AG2-440 GEN
Solar/Wind Harmer
21.265
946301AF1-294 GEN
Solar/Wind Harmer
8.547
961791AG1-021 GEN
Solar/Wind Harmer
4.169
315657AE1-056 GEN
Solar/Wind Harmer
12.331
970285AG2-188 GEN
Solar/Wind Harmer
21.159
971845AH1-439 GEN
Solar/Wind Harmer
12.178
970831AG2-522 GEN
Solar/Wind Harmer
9.991
971447AH1-217 GEN
Solar/Wind Harmer
3.87
270494AE1-108_GEN
Solar/Wind Harmer
2.477
946281AF1-292 GEN
Solar/Wind Harmer
0.184
316087AB2-174 GEN
Solar/Wind Harmer
1.113
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.367
270457AD2-023 GEN
Solar/Wind Helper
0.901
VTFLTFEXP_VFT->PJM
CMTX
1.071
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.798
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.933
G-007ALTFEXP_G-007A->PJM
CMTX
0.409
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.307
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.845
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.662
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.353

Details for AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.96 %
Rating:903.34 MVA
Rating Type:B
MVA to Mitigate:939.11
MW Contribution:5.15
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
10.81
3144293JTRSVLE
50/50
1.009
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3147043LAWRENC
50/50
1.435
3151561HALLBR1
50/50
0.347
3151931BEARGRDN S1
50/50
1.382
3151911BEARGRDN G1
50/50
1.071
3151261ROARAP2
50/50
0.077
24728405LEESVG
50/50
0.073
315687AD1-152 GEN
Solar/Wind Harmer
0.019
316003AC1-222 GEN
Solar/Wind Harmer
0.013
957481AF2-042 GEN
Solar/Wind Harmer
128.928
315693AD1-088 GEN
Solar/Wind Harmer
21.573
962491AG1-098 GEN
Solar/Wind Harmer
25.346
970401AG2-262 GEN
Solar/Wind Harmer
2.602
316237AB2-079_GEN
Solar/Wind Harmer
0.003
970685AG2-442 GEN
Solar/Wind Harmer
22.735
963171AG1-166 GEN
Solar/Wind Harmer
1.594
971563AH1-280 GEN
Solar/Wind Harmer
3.188
3146926FARMVIL
Solar/Wind Harmer
0.163
971065AG2-659 GEN
Solar/Wind Harmer
8.623
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.08
316129AC1-054 GEN
Solar/Wind Harmer
0.717
3147123OTTER R
Solar/Wind Harmer
0.087
972003AH1-546 GEN
Solar/Wind Harmer
5.562
971795AH1-408 GEN
Solar/Wind Harmer
8.362
3147312GRETNA
Solar/Wind Harmer
0.086
3146802CHATHAM
Solar/Wind Harmer
0.08
941801AE2-185 GEN
Solar/Wind Harmer
3.437
971377AH1-170 GEN
Solar/Wind Harmer
1.104
3147623JAMES R
Solar/Wind Harmer
0.24
970937AG2-583 GEN
Solar/Wind Harmer
5.738
960081AF2-299 GEN
Solar/Wind Harmer
0.703
316336AC2-165 C
Solar/Wind Harmer
0.003
3143336POWHATN
Solar/Wind Harmer
1.031
3151541CLOVER2
50/50
10.758
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
972205AH1-687 GEN
50/50
5.223
3151281ROARAP4
50/50
0.075
3151281ROARAP4
50/50
0.07
3147173SINAI
Solar/Wind Harmer
0.529
3147243WELCO
Solar/Wind Harmer
0.331
316118AC1-105 GEN
Solar/Wind Harmer
1.258
971967AH1-528 GEN
Solar/Wind Harmer
76.276
970865AG2-541 GEN
Solar/Wind Harmer
14.488
316123AC1-075 GEN
Solar/Wind Harmer
0.47
970165AG2-112 GEN
Solar/Wind Harmer
2.789
970163AG2-111 GEN
Solar/Wind Harmer
2.661
316239AB2-077_GEN
Solar/Wind Harmer
0.003
316238AB2-078_GEN
Solar/Wind Harmer
0.003
971443AH1-215 GEN
Solar/Wind Harmer
5.225
3144303KENBRDG
Solar/Wind Harmer
0.248
970683AG2-441 GEN
Solar/Wind Harmer
20.299
970681AG2-440 GEN
Solar/Wind Harmer
16.239
946301AF1-294 GEN
Solar/Wind Harmer
5.897
961791AG1-021 GEN
Solar/Wind Harmer
2.869
315657AE1-056 GEN
Solar/Wind Harmer
10.169
970285AG2-188 GEN
Solar/Wind Harmer
17.248
971845AH1-439 GEN
Solar/Wind Harmer
9.37
970831AG2-522 GEN
Solar/Wind Harmer
7.605
971447AH1-217 GEN
Solar/Wind Harmer
2.977
270494AE1-108_GEN
Solar/Wind Harmer
1.028
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.259
270455AD2-022 GEN
Solar/Wind Helper
1.376
270457AD2-023 GEN
Solar/Wind Helper
0.907
3152661PLYWOOD A
50/50
1.086
3144293JTRSVLE
50/50
1.009
3144293JTRSVLE
50/50
0.85
970535AG2-341 GEN
50/50
5.15
316222AC1-221 GEN
Solar/Wind Harmer
3.734
970099AG2-077 GEN
Solar/Wind Harmer
51.571
970933AG2-581 GEN
Solar/Wind Harmer
38.137
3146843MT LREL
Solar/Wind Harmer
0.444
3146843MT LREL
Solar/Wind Harmer
0.444
964791AG1-342 GEN
Solar/Wind Harmer
8.515
962561AG1-105 GEN
Solar/Wind Harmer
20.413
971741AH1-377 GEN
Solar/Wind Harmer
36.74
970301AG2-198 GEN
Solar/Wind Harmer
14.798
313527AB2-043 GEN
Solar/Wind Harmer
0.004
970323AG2-213 GEN
Solar/Wind Harmer
13.251
971775AH1-396 GEN
Solar/Wind Harmer
0.497
316034AC1-036 C
Solar/Wind Harmer
0.023
958211AF2-115 GEN
Solar/Wind Harmer
3.586
963191AG1-168 GEN
Solar/Wind Harmer
1.195
942751AE2-291 GEN
Solar/Wind Harmer
16.169
3147133PAMPLIN
Solar/Wind Harmer
0.295
3147133PAMPLIN
Solar/Wind Harmer
0.236
939181AE1-148 GEN
Solar/Wind Harmer
13.009
3146776BUCKING
Solar/Wind Harmer
0.802
3146776BUCKING
Solar/Wind Harmer
0.065
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
2.673
971489AH1-241 GEN
Solar/Wind Harmer
5.518
315821AE2-092 GEN
Solar/Wind Harmer
0.005
316181AB2-040 GEN
Solar/Wind Harmer
0.099
3145593CAROLNA
Solar/Wind Harmer
0.062
3145593CAROLNA
Solar/Wind Harmer
0.062
966811AG1-552 GEN
Solar/Wind Harmer
0.675
3145593CAROLNA
Solar/Wind Harmer
0.077
970413AG2-270 GEN
50/50
47.174
3144293JTRSVLE
50/50
1.009
3151591KERR 2
50/50
0.537
3151921BEARGRDN G2
50/50
1.071
3151261ROARAP2
50/50
0.076
24728405LEESVG
50/50
0.073
316248AF1-058 C
Solar/Wind Harmer
0.004
960061AF2-297 GEN
Solar/Wind Harmer
22.594
316478AD1-087 GEN
Solar/Wind Harmer
1.768
316486AD2-202 GEN
Solar/Wind Harmer
0.519
971683AH1-343 GEN
Solar/Wind Harmer
16.715
970909AG2-566 GEN
Solar/Wind Harmer
3.699
316131AB2-060 GEN
Solar/Wind Harmer
1.016
964241AG1-285 GEN
Solar/Wind Harmer
21.282
315785AD2-033 C
Solar/Wind Harmer
2.544
970257AG2-171 GEN
Solar/Wind Harmer
9.938
959311AF2-222 GEN
Solar/Wind Harmer
27.447
963181AG1-167 GEN
Solar/Wind Harmer
1.195
3147133PAMPLIN
Solar/Wind Harmer
0.925
971193AH1-056 GEN
Solar/Wind Harmer
17.953
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
3146926FARMVIL
Solar/Wind Harmer
0.163
3146776BUCKING
Solar/Wind Harmer
0.072
3147043LAWRENC
Solar/Wind Harmer
0.09
3147312GRETNA
Solar/Wind Harmer
0.021
941821AE2-187 GEN
Solar/Wind Harmer
3.437
970221AG2-151 GEN
Solar/Wind Harmer
5.518
313506AB2-031 GEN
Solar/Wind Harmer
0.21
316313AB2-026
Solar/Wind Harmer
0.037
316258AE1-075 C
Solar/Wind Harmer
0.044
316405AF2-144 C
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
0.876
316283AC2-100 C
Solar/Wind Helper
2.324
VTFLTFEXP_VFT->PJM
CMTX
1.127
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.809
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.962
G-007ALTFEXP_G-007A->PJM
CMTX
0.429
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.343
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.85
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.677
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.375

Details for AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.05 %
Rating:903.34 MVA
Rating Type:B
MVA to Mitigate:921.89
MW Contribution:5.15
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
10.81
3144293JTRSVLE
50/50
1.009
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3147043LAWRENC
50/50
1.435
3151561HALLBR1
50/50
0.347
3151931BEARGRDN S1
50/50
1.382
3151911BEARGRDN G1
50/50
1.071
3151261ROARAP2
50/50
0.077
24728405LEESVG
50/50
0.073
315687AD1-152 GEN
Solar/Wind Harmer
0.019
316003AC1-222 GEN
Solar/Wind Harmer
0.013
957481AF2-042 GEN
Solar/Wind Harmer
128.928
315693AD1-088 GEN
Solar/Wind Harmer
21.573
962491AG1-098 GEN
Solar/Wind Harmer
25.346
970401AG2-262 GEN
Solar/Wind Harmer
2.602
316237AB2-079_GEN
Solar/Wind Harmer
0.003
970685AG2-442 GEN
Solar/Wind Harmer
22.735
963171AG1-166 GEN
Solar/Wind Harmer
1.594
971563AH1-280 GEN
Solar/Wind Harmer
3.188
3146926FARMVIL
Solar/Wind Harmer
0.163
971065AG2-659 GEN
Solar/Wind Harmer
8.623
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.08
316129AC1-054 GEN
Solar/Wind Harmer
0.717
3147123OTTER R
Solar/Wind Harmer
0.087
972003AH1-546 GEN
Solar/Wind Harmer
5.562
971795AH1-408 GEN
Solar/Wind Harmer
8.362
3152661PLYWOOD A
50/50
1.086
3144293JTRSVLE
50/50
1.009
3144293JTRSVLE
50/50
0.85
970535AG2-341 GEN
50/50
5.15
316222AC1-221 GEN
Solar/Wind Harmer
3.734
970099AG2-077 GEN
Solar/Wind Harmer
51.571
3146843MT LREL
Solar/Wind Harmer
0.444
3146843MT LREL
Solar/Wind Harmer
0.444
964791AG1-342 GEN
Solar/Wind Harmer
8.515
962561AG1-105 GEN
Solar/Wind Harmer
20.413
971741AH1-377 GEN
Solar/Wind Harmer
36.74
970301AG2-198 GEN
Solar/Wind Harmer
14.798
313527AB2-043 GEN
Solar/Wind Harmer
0.004
970323AG2-213 GEN
Solar/Wind Harmer
13.251
971775AH1-396 GEN
Solar/Wind Harmer
0.497
316034AC1-036 C
Solar/Wind Harmer
0.023
958211AF2-115 GEN
Solar/Wind Harmer
3.586
963191AG1-168 GEN
Solar/Wind Harmer
1.195
942751AE2-291 GEN
Solar/Wind Harmer
16.169
3147133PAMPLIN
Solar/Wind Harmer
0.295
3147133PAMPLIN
Solar/Wind Harmer
0.236
939181AE1-148 GEN
Solar/Wind Harmer
13.009
3146776BUCKING
Solar/Wind Harmer
0.802
3146776BUCKING
Solar/Wind Harmer
0.065
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
3151541CLOVER2
50/50
10.758
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
972205AH1-687 GEN
50/50
5.223
3151281ROARAP4
50/50
0.075
3151281ROARAP4
50/50
0.07
3147173SINAI
Solar/Wind Harmer
0.529
3147243WELCO
Solar/Wind Harmer
0.331
316118AC1-105 GEN
Solar/Wind Harmer
1.258
970865AG2-541 GEN
Solar/Wind Harmer
14.488
316123AC1-075 GEN
Solar/Wind Harmer
0.47
970165AG2-112 GEN
Solar/Wind Harmer
2.789
970163AG2-111 GEN
Solar/Wind Harmer
2.661
316239AB2-077_GEN
Solar/Wind Harmer
0.003
316238AB2-078_GEN
Solar/Wind Harmer
0.003
971443AH1-215 GEN
Solar/Wind Harmer
5.225
3144303KENBRDG
Solar/Wind Harmer
0.248
970683AG2-441 GEN
Solar/Wind Harmer
20.299
970681AG2-440 GEN
Solar/Wind Harmer
16.239
946301AF1-294 GEN
Solar/Wind Harmer
5.897
961791AG1-021 GEN
Solar/Wind Harmer
2.869
315657AE1-056 GEN
Solar/Wind Harmer
10.169
970285AG2-188 GEN
Solar/Wind Harmer
17.248
971845AH1-439 GEN
Solar/Wind Harmer
9.37
970831AG2-522 GEN
Solar/Wind Harmer
7.605
970413AG2-270 GEN
50/50
47.174
3144293JTRSVLE
50/50
1.009
3151591KERR 2
50/50
0.537
3151921BEARGRDN G2
50/50
1.071
3151261ROARAP2
50/50
0.076
24728405LEESVG
50/50
0.073
316248AF1-058 C
Solar/Wind Harmer
0.004
960061AF2-297 GEN
Solar/Wind Harmer
22.594
316478AD1-087 GEN
Solar/Wind Harmer
1.768
316486AD2-202 GEN
Solar/Wind Harmer
0.519
971683AH1-343 GEN
Solar/Wind Harmer
16.715
970909AG2-566 GEN
Solar/Wind Harmer
3.699
316131AB2-060 GEN
Solar/Wind Harmer
1.016
964241AG1-285 GEN
Solar/Wind Harmer
21.282
315785AD2-033 C
Solar/Wind Harmer
2.544
970257AG2-171 GEN
Solar/Wind Harmer
9.938
959311AF2-222 GEN
Solar/Wind Harmer
27.447
963181AG1-167 GEN
Solar/Wind Harmer
1.195
3147133PAMPLIN
Solar/Wind Harmer
0.925
971193AH1-056 GEN
Solar/Wind Harmer
17.953
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
3146926FARMVIL
Solar/Wind Harmer
0.163
3146776BUCKING
Solar/Wind Harmer
0.072
3147043LAWRENC
Solar/Wind Harmer
0.09
3147312GRETNA
Solar/Wind Harmer
0.086
3146802CHATHAM
Solar/Wind Harmer
0.08
941801AE2-185 GEN
Solar/Wind Harmer
3.437
971377AH1-170 GEN
Solar/Wind Harmer
1.104
3147623JAMES R
Solar/Wind Harmer
0.24
970937AG2-583 GEN
Solar/Wind Harmer
5.738
960081AF2-299 GEN
Solar/Wind Harmer
0.703
316336AC2-165 C
Solar/Wind Harmer
0.003
3143336POWHATN
Solar/Wind Harmer
1.031
3147312GRETNA
Solar/Wind Harmer
0.021
941821AE2-187 GEN
Solar/Wind Harmer
3.437
970221AG2-151 GEN
Solar/Wind Harmer
5.518
313506AB2-031 GEN
Solar/Wind Harmer
0.21
316313AB2-026
Solar/Wind Harmer
0.037
316258AE1-075 C
Solar/Wind Harmer
0.044
316405AF2-144 C
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
0.876
316283AC2-100 C
Solar/Wind Helper
2.324
942671AE2-283 GEN
Solar/Wind Harmer
2.673
971489AH1-241 GEN
Solar/Wind Harmer
5.518
315821AE2-092 GEN
Solar/Wind Harmer
0.005
316181AB2-040 GEN
Solar/Wind Harmer
0.099
3145593CAROLNA
Solar/Wind Harmer
0.062
3145593CAROLNA
Solar/Wind Harmer
0.062
966811AG1-552 GEN
Solar/Wind Harmer
0.675
3145593CAROLNA
Solar/Wind Harmer
0.077
971447AH1-217 GEN
Solar/Wind Harmer
2.977
270494AE1-108_GEN
Solar/Wind Harmer
1.028
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.259
270455AD2-022 GEN
Solar/Wind Helper
1.376
270457AD2-023 GEN
Solar/Wind Helper
0.907
VTFLTFEXP_VFT->PJM
CMTX
1.127
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.809
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.962
G-007ALTFEXP_G-007A->PJM
CMTX
0.429
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.343
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.85
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.677
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.375

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:239.46 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1295.46
MW Contribution:5.14
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
10.804
3144293JTRSVLE
50/50
1.008
3151601KERR 3
50/50
0.536
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.432
3151561HALLBR1
50/50
0.347
3151931BEARGRDN S1
50/50
1.379
3151911BEARGRDN G1
50/50
1.068
315687AD1-152 GEN
Solar/Wind Harmer
7.75
316003AC1-222 GEN
Solar/Wind Harmer
5.363
957481AF2-042 GEN
Solar/Wind Harmer
169.654
315693AD1-088 GEN
Solar/Wind Harmer
25.233
962491AG1-098 GEN
Solar/Wind Harmer
33.35
970401AG2-262 GEN
Solar/Wind Harmer
3.25
316237AB2-079_GEN
Solar/Wind Harmer
1.107
970685AG2-442 GEN
Solar/Wind Harmer
29.906
963171AG1-166 GEN
Solar/Wind Harmer
4.193
971563AH1-280 GEN
Solar/Wind Harmer
4.193
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.337
316322AB2-045
Solar/Wind Harmer
0.757
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.874
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.319
971795AH1-408 GEN
Solar/Wind Harmer
10.545
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.513
971377AH1-170 GEN
Solar/Wind Harmer
1.449
3147623JAMES R
Solar/Wind Harmer
0.179
970937AG2-583 GEN
Solar/Wind Harmer
7.531
960081AF2-299 GEN
Solar/Wind Harmer
0.921
316336AC2-165 C
Solar/Wind Harmer
1.321
3143336POWHATN
Solar/Wind Harmer
0.769
3151541CLOVER2
50/50
10.752
3151611KERR 4
50/50
0.536
3151621KERR 5
50/50
0.536
3151631KERR 6
50/50
0.536
3151641KERR 7
50/50
0.536
972205AH1-687 GEN
50/50
5.21
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.763
971967AH1-528 GEN
Solar/Wind Harmer
100.637
970865AG2-541 GEN
Solar/Wind Harmer
19.063
316123AC1-075 GEN
Solar/Wind Harmer
4.167
970165AG2-112 GEN
Solar/Wind Harmer
3.669
970163AG2-111 GEN
Solar/Wind Harmer
3.5
316239AB2-077_GEN
Solar/Wind Harmer
1.107
316238AB2-078_GEN
Solar/Wind Harmer
1.107
971443AH1-215 GEN
Solar/Wind Harmer
6.874
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.701
970681AG2-440 GEN
Solar/Wind Harmer
21.361
946301AF1-294 GEN
Solar/Wind Harmer
8.596
961791AG1-021 GEN
Solar/Wind Harmer
4.193
315657AE1-056 GEN
Solar/Wind Harmer
12.411
970285AG2-188 GEN
Solar/Wind Harmer
21.406
971845AH1-439 GEN
Solar/Wind Harmer
12.319
970831AG2-522 GEN
Solar/Wind Harmer
9.997
971447AH1-217 GEN
Solar/Wind Harmer
3.908
270494AE1-108_GEN
Solar/Wind Harmer
2.497
946281AF1-292 GEN
Solar/Wind Harmer
0.183
316087AB2-174 GEN
Solar/Wind Harmer
1.111
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.379
270457AD2-023 GEN
Solar/Wind Helper
0.909
3152661PLYWOOD A
50/50
1.085
3144293JTRSVLE
50/50
1.008
3144293JTRSVLE
50/50
0.849
970535AG2-341 GEN
50/50
5.145
316222AC1-221 GEN
Solar/Wind Harmer
10.226
970099AG2-077 GEN
Solar/Wind Harmer
67.861
970933AG2-581 GEN
Solar/Wind Harmer
50.184
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.637
962561AG1-105 GEN
Solar/Wind Harmer
26.859
970413AG2-270 GEN
50/50
47.147
3144293JTRSVLE
50/50
1.008
3151591KERR 2
50/50
0.536
3151921BEARGRDN G2
50/50
1.068
316283AC2-100 C
Solar/Wind Harmer
9.573
316248AF1-058 C
Solar/Wind Harmer
1.792
960061AF2-297 GEN
Solar/Wind Harmer
29.732
316478AD1-087 GEN
Solar/Wind Harmer
4.927
316486AD2-202 GEN
Solar/Wind Harmer
1.443
971683AH1-343 GEN
Solar/Wind Harmer
21.994
970909AG2-566 GEN
Solar/Wind Harmer
3.696
316131AB2-060 GEN
Solar/Wind Harmer
3.914
964241AG1-285 GEN
Solar/Wind Harmer
27.996
315785AD2-033 C
Solar/Wind Harmer
7.961
970257AG2-171 GEN
Solar/Wind Harmer
13.073
959311AF2-222 GEN
Solar/Wind Harmer
36.177
963181AG1-167 GEN
Solar/Wind Harmer
3.145
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.685
942461AE2-259 GEN
Solar/Wind Harmer
4.783
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
971741AH1-377 GEN
Solar/Wind Harmer
48.337
970301AG2-198 GEN
Solar/Wind Harmer
19.467
313527AB2-043 GEN
Solar/Wind Harmer
5.909
970323AG2-213 GEN
Solar/Wind Harmer
17.431
971775AH1-396 GEN
Solar/Wind Harmer
2.482
316034AC1-036 C
Solar/Wind Harmer
0.646
958211AF2-115 GEN
Solar/Wind Harmer
5.241
963191AG1-168 GEN
Solar/Wind Harmer
3.145
942751AE2-291 GEN
Solar/Wind Harmer
21.269
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.11
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.953
316197AC1-042 GEN
Solar/Wind Harmer
1.481
941821AE2-187 GEN
Solar/Wind Harmer
4.513
970221AG2-151 GEN
Solar/Wind Harmer
7.245
966621AG1-532 GEN
Solar/Wind Harmer
0.166
313506AB2-031 GEN
Solar/Wind Harmer
0.612
316313AB2-026
Solar/Wind Harmer
0.175
316258AE1-075 C
Solar/Wind Harmer
0.157
316405AF2-144 C
Solar/Wind Harmer
0.166
3143336POWHATN
Solar/Wind Harmer
0.654
270018AE2-047 C O1
Solar/Wind Helper
0.395
942671AE2-283 GEN
Solar/Wind Harmer
3.987
971489AH1-241 GEN
Solar/Wind Harmer
6.878
315821AE2-092 GEN
Solar/Wind Harmer
1.789
316181AB2-040 GEN
Solar/Wind Harmer
1.061
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.783
3145593CAROLNA
Solar/Wind Harmer
0.058
VTFLTFEXP_VFT->PJM
CMTX
0.961
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.818
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.028
G-007ALTFEXP_G-007A->PJM
CMTX
0.368
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.218
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.864
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.722
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.39

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:234.05 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1266.23
MW Contribution:5.13
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
10.784
3144293JTRSVLE
50/50
1.007
3151601KERR 3
50/50
0.534
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.431
3151561HALLBR1
50/50
0.345
3151931BEARGRDN S1
50/50
1.382
3151911BEARGRDN G1
50/50
1.071
315687AD1-152 GEN
Solar/Wind Harmer
7.735
316003AC1-222 GEN
Solar/Wind Harmer
5.352
957481AF2-042 GEN
Solar/Wind Harmer
169.338
315693AD1-088 GEN
Solar/Wind Harmer
25.187
962491AG1-098 GEN
Solar/Wind Harmer
33.29
970401AG2-262 GEN
Solar/Wind Harmer
3.243
316237AB2-079_GEN
Solar/Wind Harmer
1.104
970685AG2-442 GEN
Solar/Wind Harmer
29.855
963171AG1-166 GEN
Solar/Wind Harmer
4.186
971563AH1-280 GEN
Solar/Wind Harmer
4.186
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.304
316322AB2-045
Solar/Wind Harmer
0.757
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.869
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.333
971795AH1-408 GEN
Solar/Wind Harmer
10.544
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.485
971377AH1-170 GEN
Solar/Wind Harmer
1.453
3147623JAMES R
Solar/Wind Harmer
0.18
970937AG2-583 GEN
Solar/Wind Harmer
7.571
960081AF2-299 GEN
Solar/Wind Harmer
0.923
316336AC2-165 C
Solar/Wind Harmer
1.335
3143336POWHATN
Solar/Wind Harmer
0.78
3151541CLOVER2
50/50
10.732
3151611KERR 4
50/50
0.534
3151621KERR 5
50/50
0.534
3151631KERR 6
50/50
0.534
3151641KERR 7
50/50
0.534
972205AH1-687 GEN
50/50
5.224
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.755
971967AH1-528 GEN
Solar/Wind Harmer
100.451
970865AG2-541 GEN
Solar/Wind Harmer
19.018
316123AC1-075 GEN
Solar/Wind Harmer
4.156
970165AG2-112 GEN
Solar/Wind Harmer
3.66
970163AG2-111 GEN
Solar/Wind Harmer
3.491
316239AB2-077_GEN
Solar/Wind Harmer
1.104
316238AB2-078_GEN
Solar/Wind Harmer
1.104
971443AH1-215 GEN
Solar/Wind Harmer
6.861
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.656
970681AG2-440 GEN
Solar/Wind Harmer
21.325
946301AF1-294 GEN
Solar/Wind Harmer
8.582
961791AG1-021 GEN
Solar/Wind Harmer
4.186
315657AE1-056 GEN
Solar/Wind Harmer
12.392
970285AG2-188 GEN
Solar/Wind Harmer
21.4
971845AH1-439 GEN
Solar/Wind Harmer
12.318
970831AG2-522 GEN
Solar/Wind Harmer
9.968
971447AH1-217 GEN
Solar/Wind Harmer
3.919
270494AE1-108_GEN
Solar/Wind Harmer
2.5
946281AF1-292 GEN
Solar/Wind Harmer
0.184
316087AB2-174 GEN
Solar/Wind Harmer
1.112
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.399
270457AD2-023 GEN
Solar/Wind Helper
0.922
3152661PLYWOOD A
50/50
1.083
3144293JTRSVLE
50/50
1.007
3144293JTRSVLE
50/50
0.848
970535AG2-341 GEN
50/50
5.132
316222AC1-221 GEN
Solar/Wind Harmer
10.206
970099AG2-077 GEN
Solar/Wind Harmer
67.735
970933AG2-581 GEN
Solar/Wind Harmer
50.091
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.615
962561AG1-105 GEN
Solar/Wind Harmer
26.803
971741AH1-377 GEN
Solar/Wind Harmer
48.264
970301AG2-198 GEN
Solar/Wind Harmer
19.44
313527AB2-043 GEN
Solar/Wind Harmer
5.897
970323AG2-213 GEN
Solar/Wind Harmer
17.399
971775AH1-396 GEN
Solar/Wind Harmer
2.478
316034AC1-036 C
Solar/Wind Harmer
0.645
958211AF2-115 GEN
Solar/Wind Harmer
5.233
963191AG1-168 GEN
Solar/Wind Harmer
3.14
942751AE2-291 GEN
Solar/Wind Harmer
21.208
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.061
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.941
316197AC1-042 GEN
Solar/Wind Harmer
1.472
942671AE2-283 GEN
Solar/Wind Harmer
3.962
971489AH1-241 GEN
Solar/Wind Harmer
6.896
315821AE2-092 GEN
Solar/Wind Harmer
1.796
316181AB2-040 GEN
Solar/Wind Harmer
1.062
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.781
3145593CAROLNA
Solar/Wind Harmer
0.058
970413AG2-270 GEN
50/50
47.058
3144293JTRSVLE
50/50
1.007
3151591KERR 2
50/50
0.534
3151921BEARGRDN G2
50/50
1.071
316283AC2-100 C
Solar/Wind Harmer
9.554
316248AF1-058 C
Solar/Wind Harmer
1.788
960061AF2-297 GEN
Solar/Wind Harmer
29.671
316478AD1-087 GEN
Solar/Wind Harmer
4.917
316486AD2-202 GEN
Solar/Wind Harmer
1.44
971683AH1-343 GEN
Solar/Wind Harmer
21.945
970909AG2-566 GEN
Solar/Wind Harmer
3.691
316131AB2-060 GEN
Solar/Wind Harmer
3.906
964241AG1-285 GEN
Solar/Wind Harmer
27.94
315785AD2-033 C
Solar/Wind Harmer
7.947
970257AG2-171 GEN
Solar/Wind Harmer
13.049
959311AF2-222 GEN
Solar/Wind Harmer
36.112
963181AG1-167 GEN
Solar/Wind Harmer
3.14
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.654
942461AE2-259 GEN
Solar/Wind Harmer
4.777
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.485
970221AG2-151 GEN
Solar/Wind Harmer
7.264
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.612
316313AB2-026
Solar/Wind Harmer
0.177
316258AE1-075 C
Solar/Wind Harmer
0.16
316405AF2-144 C
Solar/Wind Harmer
0.168
3143336POWHATN
Solar/Wind Harmer
0.663
270018AE2-047 C O1
Solar/Wind Helper
0.402
VTFLTFEXP_VFT->PJM
CMTX
1.209
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.866
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.147
G-007ALTFEXP_G-007A->PJM
CMTX
0.461
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.38
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.883
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.782
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.491

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:234.0 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1265.96
MW Contribution:5.13
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
10.784
3144293JTRSVLE
50/50
1.007
3151601KERR 3
50/50
0.534
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.431
3151561HALLBR1
50/50
0.345
3151931BEARGRDN S1
50/50
1.382
3151911BEARGRDN G1
50/50
1.071
315687AD1-152 GEN
Solar/Wind Harmer
7.735
316003AC1-222 GEN
Solar/Wind Harmer
5.352
957481AF2-042 GEN
Solar/Wind Harmer
169.338
315693AD1-088 GEN
Solar/Wind Harmer
25.187
962491AG1-098 GEN
Solar/Wind Harmer
33.29
970401AG2-262 GEN
Solar/Wind Harmer
3.243
316237AB2-079_GEN
Solar/Wind Harmer
1.104
970685AG2-442 GEN
Solar/Wind Harmer
29.855
963171AG1-166 GEN
Solar/Wind Harmer
4.186
971563AH1-280 GEN
Solar/Wind Harmer
4.186
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.304
3151541CLOVER2
50/50
10.732
3151611KERR 4
50/50
0.534
3151621KERR 5
50/50
0.534
3151631KERR 6
50/50
0.534
3151641KERR 7
50/50
0.534
972205AH1-687 GEN
50/50
5.224
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.755
971967AH1-528 GEN
Solar/Wind Harmer
100.451
970865AG2-541 GEN
Solar/Wind Harmer
19.018
316123AC1-075 GEN
Solar/Wind Harmer
4.156
970165AG2-112 GEN
Solar/Wind Harmer
3.66
970163AG2-111 GEN
Solar/Wind Harmer
3.491
316239AB2-077_GEN
Solar/Wind Harmer
1.104
316238AB2-078_GEN
Solar/Wind Harmer
1.104
971443AH1-215 GEN
Solar/Wind Harmer
6.861
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.656
970681AG2-440 GEN
Solar/Wind Harmer
21.325
946301AF1-294 GEN
Solar/Wind Harmer
8.582
961791AG1-021 GEN
Solar/Wind Harmer
4.186
315657AE1-056 GEN
Solar/Wind Harmer
12.392
970285AG2-188 GEN
Solar/Wind Harmer
21.4
971845AH1-439 GEN
Solar/Wind Harmer
12.318
970831AG2-522 GEN
Solar/Wind Harmer
9.968
971447AH1-217 GEN
Solar/Wind Harmer
3.919
270494AE1-108_GEN
Solar/Wind Harmer
2.5
946281AF1-292 GEN
Solar/Wind Harmer
0.184
316087AB2-174 GEN
Solar/Wind Harmer
1.112
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.399
270457AD2-023 GEN
Solar/Wind Helper
0.922
316322AB2-045
Solar/Wind Harmer
0.757
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.869
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.333
971795AH1-408 GEN
Solar/Wind Harmer
10.544
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.485
971377AH1-170 GEN
Solar/Wind Harmer
1.453
3147623JAMES R
Solar/Wind Harmer
0.18
970937AG2-583 GEN
Solar/Wind Harmer
7.571
960081AF2-299 GEN
Solar/Wind Harmer
0.923
316336AC2-165 C
Solar/Wind Harmer
1.335
3143336POWHATN
Solar/Wind Harmer
0.78
970413AG2-270 GEN
50/50
47.058
3144293JTRSVLE
50/50
1.007
3151591KERR 2
50/50
0.534
3151921BEARGRDN G2
50/50
1.071
316283AC2-100 C
Solar/Wind Harmer
9.554
316248AF1-058 C
Solar/Wind Harmer
1.788
960061AF2-297 GEN
Solar/Wind Harmer
29.671
316478AD1-087 GEN
Solar/Wind Harmer
4.917
316486AD2-202 GEN
Solar/Wind Harmer
1.44
971683AH1-343 GEN
Solar/Wind Harmer
21.945
970909AG2-566 GEN
Solar/Wind Harmer
3.691
316131AB2-060 GEN
Solar/Wind Harmer
3.906
964241AG1-285 GEN
Solar/Wind Harmer
27.94
315785AD2-033 C
Solar/Wind Harmer
7.947
970257AG2-171 GEN
Solar/Wind Harmer
13.049
959311AF2-222 GEN
Solar/Wind Harmer
36.112
963181AG1-167 GEN
Solar/Wind Harmer
3.14
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.654
942461AE2-259 GEN
Solar/Wind Harmer
4.777
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.485
970221AG2-151 GEN
Solar/Wind Harmer
7.264
966621AG1-532 GEN
Solar/Wind Harmer
0.167
313506AB2-031 GEN
Solar/Wind Harmer
0.612
316313AB2-026
Solar/Wind Harmer
0.177
316258AE1-075 C
Solar/Wind Harmer
0.16
316405AF2-144 C
Solar/Wind Harmer
0.168
3143336POWHATN
Solar/Wind Harmer
0.663
270018AE2-047 C O1
Solar/Wind Helper
0.402
3152661PLYWOOD A
50/50
1.083
3144293JTRSVLE
50/50
1.007
3144293JTRSVLE
50/50
0.848
970535AG2-341 GEN
50/50
5.132
316222AC1-221 GEN
Solar/Wind Harmer
10.206
970099AG2-077 GEN
Solar/Wind Harmer
67.735
970933AG2-581 GEN
Solar/Wind Harmer
50.091
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.615
962561AG1-105 GEN
Solar/Wind Harmer
26.803
971741AH1-377 GEN
Solar/Wind Harmer
48.264
970301AG2-198 GEN
Solar/Wind Harmer
19.44
313527AB2-043 GEN
Solar/Wind Harmer
5.897
970323AG2-213 GEN
Solar/Wind Harmer
17.399
971775AH1-396 GEN
Solar/Wind Harmer
2.478
316034AC1-036 C
Solar/Wind Harmer
0.645
958211AF2-115 GEN
Solar/Wind Harmer
5.233
963191AG1-168 GEN
Solar/Wind Harmer
3.14
942751AE2-291 GEN
Solar/Wind Harmer
21.208
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.061
3146776BUCKING
Solar/Wind Harmer
-0.09
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.941
316197AC1-042 GEN
Solar/Wind Harmer
1.472
942671AE2-283 GEN
Solar/Wind Harmer
3.962
971489AH1-241 GEN
Solar/Wind Harmer
6.896
315821AE2-092 GEN
Solar/Wind Harmer
1.796
316181AB2-040 GEN
Solar/Wind Harmer
1.062
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.781
3145593CAROLNA
Solar/Wind Harmer
0.058
VTFLTFEXP_VFT->PJM
CMTX
1.209
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.866
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.147
G-007ALTFEXP_G-007A->PJM
CMTX
0.461
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.38
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.883
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.782
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.491

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X1_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:231.01 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1249.79
MW Contribution:5.13
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
10.906
3144293JTRSVLE
50/50
1.002
3151601KERR 3
50/50
0.535
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.43
3151561HALLBR1
50/50
0.348
3151931BEARGRDN S1
50/50
1.361
3151911BEARGRDN G1
50/50
1.054
315687AD1-152 GEN
Solar/Wind Harmer
7.801
957481AF2-042 GEN
Solar/Wind Harmer
172.797
316003AC1-222 GEN
Solar/Wind Harmer
5.383
970401AG2-262 GEN
Solar/Wind Harmer
3.256
315693AD1-088 GEN
Solar/Wind Harmer
24.857
962491AG1-098 GEN
Solar/Wind Harmer
32.854
316237AB2-079_GEN
Solar/Wind Harmer
1.105
970685AG2-442 GEN
Solar/Wind Harmer
29.741
963171AG1-166 GEN
Solar/Wind Harmer
4.165
971563AH1-280 GEN
Solar/Wind Harmer
4.165
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.312
316322AB2-045
Solar/Wind Harmer
0.748
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.87
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.224
971795AH1-408 GEN
Solar/Wind Harmer
10.527
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.536
971377AH1-170 GEN
Solar/Wind Harmer
1.43
3147623JAMES R
Solar/Wind Harmer
0.177
970937AG2-583 GEN
Solar/Wind Harmer
7.432
960081AF2-299 GEN
Solar/Wind Harmer
0.92
316336AC2-165 C
Solar/Wind Harmer
1.303
3143336POWHATN
Solar/Wind Harmer
0.759
970413AG2-270 GEN
50/50
47.591
3144293JTRSVLE
50/50
1.002
3151591KERR 2
50/50
0.535
3151921BEARGRDN G2
50/50
1.054
316283AC2-100 C
Solar/Wind Harmer
9.587
316248AF1-058 C
Solar/Wind Harmer
1.798
960061AF2-297 GEN
Solar/Wind Harmer
29.84
316478AD1-087 GEN
Solar/Wind Harmer
4.973
316486AD2-202 GEN
Solar/Wind Harmer
1.456
971683AH1-343 GEN
Solar/Wind Harmer
22.075
970909AG2-566 GEN
Solar/Wind Harmer
3.645
316131AB2-060 GEN
Solar/Wind Harmer
3.906
964241AG1-285 GEN
Solar/Wind Harmer
27.919
315785AD2-033 C
Solar/Wind Harmer
7.93
970257AG2-171 GEN
Solar/Wind Harmer
13.016
959311AF2-222 GEN
Solar/Wind Harmer
36.008
963181AG1-167 GEN
Solar/Wind Harmer
3.124
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.53
942461AE2-259 GEN
Solar/Wind Harmer
4.736
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.536
970221AG2-151 GEN
Solar/Wind Harmer
7.152
966621AG1-532 GEN
Solar/Wind Harmer
0.166
313506AB2-031 GEN
Solar/Wind Harmer
0.611
316313AB2-026
Solar/Wind Harmer
0.172
316258AE1-075 C
Solar/Wind Harmer
0.155
316405AF2-144 C
Solar/Wind Harmer
0.164
3143336POWHATN
Solar/Wind Harmer
0.645
3152661PLYWOOD A
50/50
1.089
3144293JTRSVLE
50/50
1.002
3144293JTRSVLE
50/50
0.844
970535AG2-341 GEN
50/50
5.134
316222AC1-221 GEN
Solar/Wind Harmer
10.241
970099AG2-077 GEN
Solar/Wind Harmer
69.119
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.658
962561AG1-105 GEN
Solar/Wind Harmer
26.899
971741AH1-377 GEN
Solar/Wind Harmer
47.648
970301AG2-198 GEN
Solar/Wind Harmer
19.194
313527AB2-043 GEN
Solar/Wind Harmer
5.898
970323AG2-213 GEN
Solar/Wind Harmer
17.355
971775AH1-396 GEN
Solar/Wind Harmer
2.471
316034AC1-036 C
Solar/Wind Harmer
0.643
942751AE2-291 GEN
Solar/Wind Harmer
21.352
958211AF2-115 GEN
Solar/Wind Harmer
5.206
963191AG1-168 GEN
Solar/Wind Harmer
3.124
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.072
3146776BUCKING
Solar/Wind Harmer
-0.088
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.963
316197AC1-042 GEN
Solar/Wind Harmer
1.488
942671AE2-283 GEN
Solar/Wind Harmer
4.007
971489AH1-241 GEN
Solar/Wind Harmer
6.79
315821AE2-092 GEN
Solar/Wind Harmer
1.766
316181AB2-040 GEN
Solar/Wind Harmer
1.06
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.781
3145593CAROLNA
Solar/Wind Harmer
0.058
3151541CLOVER2
50/50
10.854
3151611KERR 4
50/50
0.535
3151621KERR 5
50/50
0.535
3151631KERR 6
50/50
0.535
3151641KERR 7
50/50
0.535
972205AH1-687 GEN
50/50
5.142
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.773
970865AG2-541 GEN
Solar/Wind Harmer
19.134
316123AC1-075 GEN
Solar/Wind Harmer
4.183
970165AG2-112 GEN
Solar/Wind Harmer
3.683
970163AG2-111 GEN
Solar/Wind Harmer
3.514
316239AB2-077_GEN
Solar/Wind Harmer
1.105
316238AB2-078_GEN
Solar/Wind Harmer
1.105
971443AH1-215 GEN
Solar/Wind Harmer
6.844
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.554
970681AG2-440 GEN
Solar/Wind Harmer
21.243
946301AF1-294 GEN
Solar/Wind Harmer
8.538
961791AG1-021 GEN
Solar/Wind Harmer
4.165
315657AE1-056 GEN
Solar/Wind Harmer
12.318
970285AG2-188 GEN
Solar/Wind Harmer
21.128
971845AH1-439 GEN
Solar/Wind Harmer
12.16
970831AG2-522 GEN
Solar/Wind Harmer
9.974
971447AH1-217 GEN
Solar/Wind Harmer
3.858
270494AE1-108_GEN
Solar/Wind Harmer
2.469
946281AF1-292 GEN
Solar/Wind Harmer
0.183
316087AB2-174 GEN
Solar/Wind Harmer
1.109
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.37
270457AD2-023 GEN
Solar/Wind Helper
0.903
VTFLTFEXP_VFT->PJM
CMTX
0.905
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.807
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.999
G-007ALTFEXP_G-007A->PJM
CMTX
0.347
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.181
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.859
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.707
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.368

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X2_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:231.0 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:1249.74
MW Contribution:5.13
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
10.905
3144293JTRSVLE
50/50
1.002
3151601KERR 3
50/50
0.535
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.43
3151561HALLBR1
50/50
0.348
3151931BEARGRDN S1
50/50
1.361
3151911BEARGRDN G1
50/50
1.054
315687AD1-152 GEN
Solar/Wind Harmer
7.801
957481AF2-042 GEN
Solar/Wind Harmer
172.774
316003AC1-222 GEN
Solar/Wind Harmer
5.383
970401AG2-262 GEN
Solar/Wind Harmer
3.256
315693AD1-088 GEN
Solar/Wind Harmer
24.86
962491AG1-098 GEN
Solar/Wind Harmer
32.858
316237AB2-079_GEN
Solar/Wind Harmer
1.105
970685AG2-442 GEN
Solar/Wind Harmer
29.742
963171AG1-166 GEN
Solar/Wind Harmer
4.165
971563AH1-280 GEN
Solar/Wind Harmer
4.165
3146926FARMVIL
Solar/Wind Harmer
-0.018
971065AG2-659 GEN
Solar/Wind Harmer
11.312
316322AB2-045
Solar/Wind Harmer
0.748
3146776BUCKING
Solar/Wind Harmer
-0.009
316129AC1-054 GEN
Solar/Wind Harmer
1.87
3147123OTTER R
Solar/Wind Harmer
-0.01
972003AH1-546 GEN
Solar/Wind Harmer
7.224
971795AH1-408 GEN
Solar/Wind Harmer
10.527
3147312GRETNA
Solar/Wind Harmer
-0.01
3146802CHATHAM
Solar/Wind Harmer
-0.009
941801AE2-185 GEN
Solar/Wind Harmer
4.536
3151541CLOVER2
50/50
10.853
3151611KERR 4
50/50
0.535
3151621KERR 5
50/50
0.535
3151631KERR 6
50/50
0.535
3151641KERR 7
50/50
0.535
972205AH1-687 GEN
50/50
5.143
3147173SINAI
Solar/Wind Harmer
-0.059
3147243WELCO
Solar/Wind Harmer
-0.037
316118AC1-105 GEN
Solar/Wind Harmer
3.773
970865AG2-541 GEN
Solar/Wind Harmer
19.133
316123AC1-075 GEN
Solar/Wind Harmer
4.183
970165AG2-112 GEN
Solar/Wind Harmer
3.683
970163AG2-111 GEN
Solar/Wind Harmer
3.514
316239AB2-077_GEN
Solar/Wind Harmer
1.105
316238AB2-078_GEN
Solar/Wind Harmer
1.105
971443AH1-215 GEN
Solar/Wind Harmer
6.845
3144303KENBRDG
Solar/Wind Harmer
-0.028
970683AG2-441 GEN
Solar/Wind Harmer
26.555
970681AG2-440 GEN
Solar/Wind Harmer
21.244
946301AF1-294 GEN
Solar/Wind Harmer
8.539
961791AG1-021 GEN
Solar/Wind Harmer
4.165
315657AE1-056 GEN
Solar/Wind Harmer
12.319
970285AG2-188 GEN
Solar/Wind Harmer
21.13
971845AH1-439 GEN
Solar/Wind Harmer
12.161
970831AG2-522 GEN
Solar/Wind Harmer
9.975
971447AH1-217 GEN
Solar/Wind Harmer
3.858
270494AE1-108_GEN
Solar/Wind Harmer
2.469
946281AF1-292 GEN
Solar/Wind Harmer
0.183
316087AB2-174 GEN
Solar/Wind Harmer
1.109
3137643SOCKMAN
Solar/Wind Harmer
-0.029
270455AD2-022 GEN
Solar/Wind Helper
1.37
270457AD2-023 GEN
Solar/Wind Helper
0.903
3152661PLYWOOD A
50/50
1.089
3144293JTRSVLE
50/50
1.002
3144293JTRSVLE
50/50
0.844
970535AG2-341 GEN
50/50
5.134
316222AC1-221 GEN
Solar/Wind Harmer
10.241
970099AG2-077 GEN
Solar/Wind Harmer
69.109
3146843MT LREL
Solar/Wind Harmer
-0.05
3146843MT LREL
Solar/Wind Harmer
-0.05
964791AG1-342 GEN
Solar/Wind Harmer
10.657
962561AG1-105 GEN
Solar/Wind Harmer
26.899
971741AH1-377 GEN
Solar/Wind Harmer
47.653
971377AH1-170 GEN
Solar/Wind Harmer
1.431
3147623JAMES R
Solar/Wind Harmer
0.177
970937AG2-583 GEN
Solar/Wind Harmer
7.433
960081AF2-299 GEN
Solar/Wind Harmer
0.92
316336AC2-165 C
Solar/Wind Harmer
1.304
3143336POWHATN
Solar/Wind Harmer
0.759
970301AG2-198 GEN
Solar/Wind Harmer
19.197
313527AB2-043 GEN
Solar/Wind Harmer
5.898
970323AG2-213 GEN
Solar/Wind Harmer
17.355
971775AH1-396 GEN
Solar/Wind Harmer
2.471
316034AC1-036 C
Solar/Wind Harmer
0.644
942751AE2-291 GEN
Solar/Wind Harmer
21.351
958211AF2-115 GEN
Solar/Wind Harmer
5.207
963191AG1-168 GEN
Solar/Wind Harmer
3.124
3147133PAMPLIN
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.026
939181AE1-148 GEN
Solar/Wind Harmer
17.072
3146776BUCKING
Solar/Wind Harmer
-0.088
3146776BUCKING
Solar/Wind Harmer
-0.007
316217AC1-145 GEN
Solar/Wind Harmer
1.963
316197AC1-042 GEN
Solar/Wind Harmer
1.488
942671AE2-283 GEN
Solar/Wind Harmer
4.007
971489AH1-241 GEN
Solar/Wind Harmer
6.79
315821AE2-092 GEN
Solar/Wind Harmer
1.766
316181AB2-040 GEN
Solar/Wind Harmer
1.06
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.781
3145593CAROLNA
Solar/Wind Harmer
0.058
970413AG2-270 GEN
50/50
47.588
3144293JTRSVLE
50/50
1.002
3151591KERR 2
50/50
0.535
3151921BEARGRDN G2
50/50
1.054
316283AC2-100 C
Solar/Wind Harmer
9.586
316248AF1-058 C
Solar/Wind Harmer
1.798
960061AF2-297 GEN
Solar/Wind Harmer
29.84
316478AD1-087 GEN
Solar/Wind Harmer
4.972
316486AD2-202 GEN
Solar/Wind Harmer
1.456
971683AH1-343 GEN
Solar/Wind Harmer
22.075
970909AG2-566 GEN
Solar/Wind Harmer
3.645
316131AB2-060 GEN
Solar/Wind Harmer
3.906
964241AG1-285 GEN
Solar/Wind Harmer
27.92
315785AD2-033 C
Solar/Wind Harmer
7.931
970257AG2-171 GEN
Solar/Wind Harmer
13.017
959311AF2-222 GEN
Solar/Wind Harmer
36.009
963181AG1-167 GEN
Solar/Wind Harmer
3.124
3147133PAMPLIN
Solar/Wind Harmer
-0.103
971193AH1-056 GEN
Solar/Wind Harmer
20.531
942461AE2-259 GEN
Solar/Wind Harmer
4.736
3146926FARMVIL
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.008
3147043LAWRENC
Solar/Wind Harmer
-0.01
3147312GRETNA
Solar/Wind Harmer
-0.002
941821AE2-187 GEN
Solar/Wind Harmer
4.536
970221AG2-151 GEN
Solar/Wind Harmer
7.153
966621AG1-532 GEN
Solar/Wind Harmer
0.166
313506AB2-031 GEN
Solar/Wind Harmer
0.611
316313AB2-026
Solar/Wind Harmer
0.173
316258AE1-075 C
Solar/Wind Harmer
0.155
316405AF2-144 C
Solar/Wind Harmer
0.164
3143336POWHATN
Solar/Wind Harmer
0.645
VTFLTFEXP_VFT->PJM
CMTX
0.906
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.807
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.999
G-007ALTFEXP_G-007A->PJM
CMTX
0.347
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.181
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.859
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.707
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.368

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:192.41 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:978.46
MW Contribution:5.14
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
10.804
3144293JTRSVLE
50/50
1.008
3151601KERR 3
50/50
0.536
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.432
3151561HALLBR1
50/50
0.347
3151931BEARGRDN S1
50/50
1.379
3151911BEARGRDN G1
50/50
1.068
3151261ROARAP2
50/50
0.077
24728405LEESVG
50/50
0.072
315687AD1-152 GEN
Solar/Wind Harmer
0.019
316003AC1-222 GEN
Solar/Wind Harmer
0.013
957481AF2-042 GEN
Solar/Wind Harmer
128.851
315693AD1-088 GEN
Solar/Wind Harmer
21.559
962491AG1-098 GEN
Solar/Wind Harmer
25.329
970401AG2-262 GEN
Solar/Wind Harmer
2.6
316237AB2-079_GEN
Solar/Wind Harmer
0.003
970685AG2-442 GEN
Solar/Wind Harmer
22.713
963171AG1-166 GEN
Solar/Wind Harmer
1.592
971563AH1-280 GEN
Solar/Wind Harmer
3.185
3146926FARMVIL
Solar/Wind Harmer
0.162
971065AG2-659 GEN
Solar/Wind Harmer
8.611
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.08
316129AC1-054 GEN
Solar/Wind Harmer
0.716
3147123OTTER R
Solar/Wind Harmer
0.087
972003AH1-546 GEN
Solar/Wind Harmer
5.549
971795AH1-408 GEN
Solar/Wind Harmer
8.343
3147312GRETNA
Solar/Wind Harmer
0.086
3146802CHATHAM
Solar/Wind Harmer
0.08
941801AE2-185 GEN
Solar/Wind Harmer
3.428
971377AH1-170 GEN
Solar/Wind Harmer
1.1
3147623JAMES R
Solar/Wind Harmer
0.239
970937AG2-583 GEN
Solar/Wind Harmer
5.72
960081AF2-299 GEN
Solar/Wind Harmer
0.7
316336AC2-165 C
Solar/Wind Harmer
0.003
3143336POWHATN
Solar/Wind Harmer
1.026
970413AG2-270 GEN
50/50
47.147
3144293JTRSVLE
50/50
1.008
3151591KERR 2
50/50
0.536
3151921BEARGRDN G2
50/50
1.068
3151261ROARAP2
50/50
0.075
24728405LEESVG
50/50
0.073
316283AC2-100 C
Solar/Wind Harmer
1.77
316248AF1-058 C
Solar/Wind Harmer
0.004
960061AF2-297 GEN
Solar/Wind Harmer
22.582
316478AD1-087 GEN
Solar/Wind Harmer
1.767
316486AD2-202 GEN
Solar/Wind Harmer
0.519
971683AH1-343 GEN
Solar/Wind Harmer
16.704
970909AG2-566 GEN
Solar/Wind Harmer
3.696
316131AB2-060 GEN
Solar/Wind Harmer
1.015
964241AG1-285 GEN
Solar/Wind Harmer
21.263
315785AD2-033 C
Solar/Wind Harmer
2.542
970257AG2-171 GEN
Solar/Wind Harmer
9.929
959311AF2-222 GEN
Solar/Wind Harmer
27.421
963181AG1-167 GEN
Solar/Wind Harmer
1.194
3147133PAMPLIN
Solar/Wind Harmer
0.924
971193AH1-056 GEN
Solar/Wind Harmer
17.935
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
3146926FARMVIL
Solar/Wind Harmer
0.162
3146776BUCKING
Solar/Wind Harmer
0.072
3147043LAWRENC
Solar/Wind Harmer
0.09
3147312GRETNA
Solar/Wind Harmer
0.021
941821AE2-187 GEN
Solar/Wind Harmer
3.428
970221AG2-151 GEN
Solar/Wind Harmer
5.502
313506AB2-031 GEN
Solar/Wind Harmer
0.209
316313AB2-026
Solar/Wind Harmer
0.036
316258AE1-075 C
Solar/Wind Harmer
0.044
316405AF2-144 C
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
0.872
270018AE2-047 C O1
Solar/Wind Helper
0.395
3151541CLOVER2
50/50
10.752
3151611KERR 4
50/50
0.536
3151621KERR 5
50/50
0.536
3151631KERR 6
50/50
0.536
3151641KERR 7
50/50
0.536
972205AH1-687 GEN
50/50
5.21
3151281ROARAP4
50/50
0.075
3151281ROARAP4
50/50
0.07
3147173SINAI
Solar/Wind Harmer
0.529
3147243WELCO
Solar/Wind Harmer
0.331
316118AC1-105 GEN
Solar/Wind Harmer
1.257
971967AH1-528 GEN
Solar/Wind Harmer
76.23
970865AG2-541 GEN
Solar/Wind Harmer
14.478
316123AC1-075 GEN
Solar/Wind Harmer
0.47
970165AG2-112 GEN
Solar/Wind Harmer
2.787
970163AG2-111 GEN
Solar/Wind Harmer
2.658
316239AB2-077_GEN
Solar/Wind Harmer
0.003
316238AB2-078_GEN
Solar/Wind Harmer
0.003
971443AH1-215 GEN
Solar/Wind Harmer
5.22
3144303KENBRDG
Solar/Wind Harmer
0.248
970683AG2-441 GEN
Solar/Wind Harmer
20.28
970681AG2-440 GEN
Solar/Wind Harmer
16.224
946301AF1-294 GEN
Solar/Wind Harmer
5.891
961791AG1-021 GEN
Solar/Wind Harmer
2.866
315657AE1-056 GEN
Solar/Wind Harmer
10.159
970285AG2-188 GEN
Solar/Wind Harmer
17.225
971845AH1-439 GEN
Solar/Wind Harmer
9.357
970831AG2-522 GEN
Solar/Wind Harmer
7.592
971447AH1-217 GEN
Solar/Wind Harmer
2.968
270494AE1-108_GEN
Solar/Wind Harmer
1.024
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.258
270455AD2-022 GEN
Solar/Wind Helper
1.379
270457AD2-023 GEN
Solar/Wind Helper
0.909
3152661PLYWOOD A
50/50
1.085
3144293JTRSVLE
50/50
1.008
3144293JTRSVLE
50/50
0.849
970535AG2-341 GEN
50/50
5.145
316222AC1-221 GEN
Solar/Wind Harmer
3.733
970099AG2-077 GEN
Solar/Wind Harmer
51.54
970933AG2-581 GEN
Solar/Wind Harmer
38.114
3146843MT LREL
Solar/Wind Harmer
0.444
3146843MT LREL
Solar/Wind Harmer
0.444
964791AG1-342 GEN
Solar/Wind Harmer
8.51
962561AG1-105 GEN
Solar/Wind Harmer
20.399
971741AH1-377 GEN
Solar/Wind Harmer
36.712
970301AG2-198 GEN
Solar/Wind Harmer
14.785
313527AB2-043 GEN
Solar/Wind Harmer
0.004
970323AG2-213 GEN
Solar/Wind Harmer
13.238
971775AH1-396 GEN
Solar/Wind Harmer
0.496
316034AC1-036 C
Solar/Wind Harmer
0.023
958211AF2-115 GEN
Solar/Wind Harmer
3.583
963191AG1-168 GEN
Solar/Wind Harmer
1.194
942751AE2-291 GEN
Solar/Wind Harmer
16.154
3147133PAMPLIN
Solar/Wind Harmer
0.294
3147133PAMPLIN
Solar/Wind Harmer
0.235
939181AE1-148 GEN
Solar/Wind Harmer
12.995
3146776BUCKING
Solar/Wind Harmer
0.801
3146776BUCKING
Solar/Wind Harmer
0.065
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
2.666
971489AH1-241 GEN
Solar/Wind Harmer
5.502
315821AE2-092 GEN
Solar/Wind Harmer
0.005
316181AB2-040 GEN
Solar/Wind Harmer
0.098
3145593CAROLNA
Solar/Wind Harmer
0.062
3145593CAROLNA
Solar/Wind Harmer
0.062
966811AG1-552 GEN
Solar/Wind Harmer
0.671
3145593CAROLNA
Solar/Wind Harmer
0.077
VTFLTFEXP_VFT->PJM
CMTX
0.961
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.818
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.028
G-007ALTFEXP_G-007A->PJM
CMTX
0.368
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.218
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.864
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.722
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.39

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:189.13 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:961.81
MW Contribution:5.14
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
10.804
3144293JTRSVLE
50/50
1.008
3151601KERR 3
50/50
0.536
3151581KERR 1
50/50
0.191
3147043LAWRENC
50/50
1.432
3151561HALLBR1
50/50
0.347
3151931BEARGRDN S1
50/50
1.379
3151911BEARGRDN G1
50/50
1.068
3151261ROARAP2
50/50
0.077
24728405LEESVG
50/50
0.072
315687AD1-152 GEN
Solar/Wind Harmer
0.019
316003AC1-222 GEN
Solar/Wind Harmer
0.013
957481AF2-042 GEN
Solar/Wind Harmer
128.851
315693AD1-088 GEN
Solar/Wind Harmer
21.559
962491AG1-098 GEN
Solar/Wind Harmer
25.329
970401AG2-262 GEN
Solar/Wind Harmer
2.6
316237AB2-079_GEN
Solar/Wind Harmer
0.003
970685AG2-442 GEN
Solar/Wind Harmer
22.713
963171AG1-166 GEN
Solar/Wind Harmer
1.592
971563AH1-280 GEN
Solar/Wind Harmer
3.185
3146926FARMVIL
Solar/Wind Harmer
0.162
971065AG2-659 GEN
Solar/Wind Harmer
8.611
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.08
316129AC1-054 GEN
Solar/Wind Harmer
0.716
3147123OTTER R
Solar/Wind Harmer
0.087
972003AH1-546 GEN
Solar/Wind Harmer
5.549
971795AH1-408 GEN
Solar/Wind Harmer
8.343
3147312GRETNA
Solar/Wind Harmer
0.086
3146802CHATHAM
Solar/Wind Harmer
0.08
941801AE2-185 GEN
Solar/Wind Harmer
3.428
971377AH1-170 GEN
Solar/Wind Harmer
1.1
3147623JAMES R
Solar/Wind Harmer
0.239
970937AG2-583 GEN
Solar/Wind Harmer
5.72
960081AF2-299 GEN
Solar/Wind Harmer
0.7
316336AC2-165 C
Solar/Wind Harmer
0.003
3143336POWHATN
Solar/Wind Harmer
1.026
970413AG2-270 GEN
50/50
47.147
3144293JTRSVLE
50/50
1.008
3151591KERR 2
50/50
0.536
3151921BEARGRDN G2
50/50
1.068
3151261ROARAP2
50/50
0.075
24728405LEESVG
50/50
0.073
316283AC2-100 C
Solar/Wind Harmer
1.77
316248AF1-058 C
Solar/Wind Harmer
0.004
960061AF2-297 GEN
Solar/Wind Harmer
22.582
316478AD1-087 GEN
Solar/Wind Harmer
1.767
316486AD2-202 GEN
Solar/Wind Harmer
0.519
971683AH1-343 GEN
Solar/Wind Harmer
16.704
970909AG2-566 GEN
Solar/Wind Harmer
3.696
316131AB2-060 GEN
Solar/Wind Harmer
1.015
964241AG1-285 GEN
Solar/Wind Harmer
21.263
315785AD2-033 C
Solar/Wind Harmer
2.542
970257AG2-171 GEN
Solar/Wind Harmer
9.929
959311AF2-222 GEN
Solar/Wind Harmer
27.421
963181AG1-167 GEN
Solar/Wind Harmer
1.194
3147133PAMPLIN
Solar/Wind Harmer
0.924
971193AH1-056 GEN
Solar/Wind Harmer
17.935
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
3146926FARMVIL
Solar/Wind Harmer
0.162
3146776BUCKING
Solar/Wind Harmer
0.072
3147043LAWRENC
Solar/Wind Harmer
0.09
3147312GRETNA
Solar/Wind Harmer
0.021
941821AE2-187 GEN
Solar/Wind Harmer
3.428
970221AG2-151 GEN
Solar/Wind Harmer
5.502
313506AB2-031 GEN
Solar/Wind Harmer
0.209
316313AB2-026
Solar/Wind Harmer
0.036
316258AE1-075 C
Solar/Wind Harmer
0.044
316405AF2-144 C
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
0.872
270018AE2-047 C O1
Solar/Wind Helper
0.395
3151541CLOVER2
50/50
10.752
3151611KERR 4
50/50
0.536
3151621KERR 5
50/50
0.536
3151631KERR 6
50/50
0.536
3151641KERR 7
50/50
0.536
972205AH1-687 GEN
50/50
5.21
3151281ROARAP4
50/50
0.075
3151281ROARAP4
50/50
0.07
3147173SINAI
Solar/Wind Harmer
0.529
3147243WELCO
Solar/Wind Harmer
0.331
3152661PLYWOOD A
50/50
1.085
3144293JTRSVLE
50/50
1.008
3144293JTRSVLE
50/50
0.849
970535AG2-341 GEN
50/50
5.145
316222AC1-221 GEN
Solar/Wind Harmer
3.733
970099AG2-077 GEN
Solar/Wind Harmer
51.54
3146843MT LREL
Solar/Wind Harmer
0.444
3146843MT LREL
Solar/Wind Harmer
0.444
964791AG1-342 GEN
Solar/Wind Harmer
8.51
962561AG1-105 GEN
Solar/Wind Harmer
20.399
971741AH1-377 GEN
Solar/Wind Harmer
36.712
970301AG2-198 GEN
Solar/Wind Harmer
14.785
313527AB2-043 GEN
Solar/Wind Harmer
0.004
970323AG2-213 GEN
Solar/Wind Harmer
13.238
971775AH1-396 GEN
Solar/Wind Harmer
0.496
316034AC1-036 C
Solar/Wind Harmer
0.023
958211AF2-115 GEN
Solar/Wind Harmer
3.583
963191AG1-168 GEN
Solar/Wind Harmer
1.194
942751AE2-291 GEN
Solar/Wind Harmer
16.154
3147133PAMPLIN
Solar/Wind Harmer
0.294
3147133PAMPLIN
Solar/Wind Harmer
0.235
939181AE1-148 GEN
Solar/Wind Harmer
12.995
3146776BUCKING
Solar/Wind Harmer
0.801
3146776BUCKING
Solar/Wind Harmer
0.065
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
2.666
971489AH1-241 GEN
Solar/Wind Harmer
5.502
315821AE2-092 GEN
Solar/Wind Harmer
0.005
316181AB2-040 GEN
Solar/Wind Harmer
0.098
3145593CAROLNA
Solar/Wind Harmer
0.062
3145593CAROLNA
Solar/Wind Harmer
0.062
966811AG1-552 GEN
Solar/Wind Harmer
0.671
3145593CAROLNA
Solar/Wind Harmer
0.077
316118AC1-105 GEN
Solar/Wind Harmer
1.257
970865AG2-541 GEN
Solar/Wind Harmer
14.478
316123AC1-075 GEN
Solar/Wind Harmer
0.47
970165AG2-112 GEN
Solar/Wind Harmer
2.787
970163AG2-111 GEN
Solar/Wind Harmer
2.658
316239AB2-077_GEN
Solar/Wind Harmer
0.003
316238AB2-078_GEN
Solar/Wind Harmer
0.003
971443AH1-215 GEN
Solar/Wind Harmer
5.22
3144303KENBRDG
Solar/Wind Harmer
0.248
970683AG2-441 GEN
Solar/Wind Harmer
20.28
970681AG2-440 GEN
Solar/Wind Harmer
16.224
946301AF1-294 GEN
Solar/Wind Harmer
5.891
961791AG1-021 GEN
Solar/Wind Harmer
2.866
315657AE1-056 GEN
Solar/Wind Harmer
10.159
970285AG2-188 GEN
Solar/Wind Harmer
17.225
971845AH1-439 GEN
Solar/Wind Harmer
9.357
970831AG2-522 GEN
Solar/Wind Harmer
7.592
971447AH1-217 GEN
Solar/Wind Harmer
2.968
270494AE1-108_GEN
Solar/Wind Harmer
1.024
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.258
270455AD2-022 GEN
Solar/Wind Helper
1.379
270457AD2-023 GEN
Solar/Wind Helper
0.909
VTFLTFEXP_VFT->PJM
CMTX
0.961
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.818
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
5.028
G-007ALTFEXP_G-007A->PJM
CMTX
0.368
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.218
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.864
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.722
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.39

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: BREMO B1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.04 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:552.01
MW Contribution:3.06
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
0.786
3144293JTRSVLE
50/50
0.694
3144293JTRSVLE
50/50
0.585
970535AG2-341 GEN
50/50
3.063
316222AC1-221 GEN
Solar/Wind Harmer
9.436
3146843MT LREL
Solar/Wind Harmer
-0.035
3146843MT LREL
Solar/Wind Harmer
-0.035
964791AG1-342 GEN
Solar/Wind Harmer
7.565
962561AG1-105 GEN
Solar/Wind Harmer
18.89
942751AE2-291 GEN
Solar/Wind Harmer
14.981
313527AB2-043 GEN
Solar/Wind Harmer
3.802
970323AG2-213 GEN
Solar/Wind Harmer
11.621
971775AH1-396 GEN
Solar/Wind Harmer
1.655
316034AC1-036 C
Solar/Wind Harmer
0.431
958211AF2-115 GEN
Solar/Wind Harmer
3.609
963191AG1-168 GEN
Solar/Wind Harmer
2.165
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3146776BUCKING
Solar/Wind Harmer
-0.091
3146776BUCKING
Solar/Wind Harmer
-0.007
970301AG2-198 GEN
Solar/Wind Harmer
11.339
971741AH1-377 GEN
Solar/Wind Harmer
26.337
970099AG2-077 GEN
Solar/Wind Harmer
28.191
3151541CLOVER2
50/50
5.491
3151611KERR 4
50/50
0.291
3151621KERR 5
50/50
0.291
3151631KERR 6
50/50
0.291
3151641KERR 7
50/50
0.291
3147173SINAI
Solar/Wind Harmer
-0.044
3147243WELCO
Solar/Wind Harmer
-0.027
316118AC1-105 GEN
Solar/Wind Harmer
2.738
970865AG2-541 GEN
Solar/Wind Harmer
13.887
316123AC1-075 GEN
Solar/Wind Harmer
2.983
970165AG2-112 GEN
Solar/Wind Harmer
2.626
970163AG2-111 GEN
Solar/Wind Harmer
2.505
316239AB2-077_GEN
Solar/Wind Harmer
0.713
316238AB2-078_GEN
Solar/Wind Harmer
0.713
3144303KENBRDG
Solar/Wind Harmer
-0.019
971443AH1-215 GEN
Solar/Wind Harmer
4.576
970683AG2-441 GEN
Solar/Wind Harmer
18.096
970681AG2-440 GEN
Solar/Wind Harmer
14.477
946301AF1-294 GEN
Solar/Wind Harmer
5.918
961791AG1-021 GEN
Solar/Wind Harmer
2.887
315657AE1-056 GEN
Solar/Wind Harmer
8.642
971845AH1-439 GEN
Solar/Wind Harmer
12.087
970285AG2-188 GEN
Solar/Wind Harmer
19.908
970831AG2-522 GEN
Solar/Wind Harmer
5.656
971967AH1-528 GEN
Solar/Wind Harmer
18.182
970673AG2-436 GEN
Solar/Wind Harmer
14.386
970673AG2-436 GEN
Solar/Wind Harmer
7.284
946281AF1-292 GEN
Solar/Wind Harmer
0.153
941031AE2-094 GEN
Solar/Wind Harmer
12.694
970413AG2-270 GEN
50/50
24.076
3144293JTRSVLE
50/50
0.694
3151591KERR 2
50/50
0.291
316283AC2-100 C
Solar/Wind Harmer
8.862
316248AF1-058 C
Solar/Wind Harmer
1.328
960061AF2-297 GEN
Solar/Wind Harmer
22.033
971683AH1-343 GEN
Solar/Wind Harmer
16.127
316478AD1-087 GEN
Solar/Wind Harmer
2.53
316486AD2-202 GEN
Solar/Wind Harmer
0.741
316131AB2-060 GEN
Solar/Wind Harmer
2.525
964241AG1-285 GEN
Solar/Wind Harmer
18.238
315785AD2-033 C
Solar/Wind Harmer
5.274
970257AG2-171 GEN
Solar/Wind Harmer
8.716
959311AF2-222 GEN
Solar/Wind Harmer
24.232
963181AG1-167 GEN
Solar/Wind Harmer
2.165
3147133PAMPLIN
Solar/Wind Harmer
-0.072
971193AH1-056 GEN
Solar/Wind Harmer
14.403
942461AE2-259 GEN
Solar/Wind Harmer
3.442
3146776BUCKING
Solar/Wind Harmer
-0.008
3146926FARMVIL
Solar/Wind Harmer
-0.013
970909AG2-566 GEN
Solar/Wind Harmer
2.153
3147043LAWRENC
Solar/Wind Harmer
-0.007
966621AG1-532 GEN
Solar/Wind Harmer
0.138
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.507
270018AE2-047 C O1
Solar/Wind Helper
0.567
943811AF1-049 GEN
Solar/Wind Helper
0.923
270336AE1-100 GEN
Solar/Wind Helper
0.558
3151531CLOVER1
50/50
5.517
3144293JTRSVLE
50/50
0.694
3151601KERR 3
50/50
0.291
3151581KERR 1
50/50
0.104
315687AD1-152 GEN
Solar/Wind Harmer
5.005
316003AC1-222 GEN
Solar/Wind Harmer
3.954
970401AG2-262 GEN
Solar/Wind Harmer
2.311
316237AB2-079_GEN
Solar/Wind Harmer
0.713
970685AG2-442 GEN
Solar/Wind Harmer
20.268
963171AG1-166 GEN
Solar/Wind Harmer
2.887
971563AH1-280 GEN
Solar/Wind Harmer
2.887
972003AH1-546 GEN
Solar/Wind Harmer
11.349
316322AB2-045
Solar/Wind Harmer
0.765
3146776BUCKING
Solar/Wind Harmer
-0.009
3146926FARMVIL
Solar/Wind Harmer
-0.013
962491AG1-098 GEN
Solar/Wind Harmer
15.104
315693AD1-088 GEN
Solar/Wind Harmer
11.29
957481AF2-042 GEN
Solar/Wind Harmer
70.478
971065AG2-659 GEN
Solar/Wind Harmer
6.314
316129AC1-054 GEN
Solar/Wind Harmer
1.051
3147043LAWRENC
Adder
0.955
971795AH1-408 GEN
Solar/Wind Harmer
7.701
3147123OTTER R
Solar/Wind Harmer
-0.006
960081AF2-299 GEN
Solar/Wind Harmer
0.766
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.507
940641AE2-051 GEN
Solar/Wind Harmer
5.976
939411AE1-173 GEN
Solar/Wind Harmer
30.063
270016AE1-250 BESS
Solar/Wind Helper
0.571
944011AF1-069 GEN
Solar/Wind Harmer
3.977
270455AD2-022 GEN
Solar/Wind Helper
1.808
270457AD2-023 GEN
Solar/Wind Helper
1.191
270069AE2-166 C O1
Solar/Wind Helper
0.543
939181AE1-148 GEN
Solar/Wind Harmer
9.651
970933AG2-581 GEN
Solar/Wind Harmer
12.282
972187AH1-678 GEN
Adder
1.759
972185AH1-677 GEN
Adder
3.44
316217AC1-145 GEN
Solar/Wind Harmer
1.085
316197AC1-042 GEN
Solar/Wind Harmer
0.823
942671AE2-283 GEN
Solar/Wind Harmer
2.215
270013AE1-250 PV
Solar/Wind Helper
0.571
VTFLTFEXP_VFT->PJM
CMTX
4.632
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.206
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
6.697
G-007ALTFEXP_G-007A->PJM
CMTX
1.744
CBM NorthLTFEXP_CBM-N->PJM
CBM
2.484
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
1.198
BlueGrassPJM->LTFIMP_BlueG
CLTF
3.768
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.87

Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.59 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:1021.82
MW Contribution:1.29
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.566
3144293JTRSVLE
50/50
0.617
966251AG1-494 GEN
50/50
1.538
3151591KERR 2
50/50
0.119
970221AG2-151 GEN
Solar/Wind Harmer
23.288
3146776BUCKING
Solar/Wind Harmer
0.136
3146926FARMVIL
Solar/Wind Harmer
0.171
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
2.106
3147133PAMPLIN
Solar/Wind Harmer
0.619
971193AH1-056 GEN
Solar/Wind Harmer
12.006
963181AG1-167 GEN
Solar/Wind Harmer
0.73
959311AF2-222 GEN
Solar/Wind Harmer
12.97
958131AF2-107 GEN
Solar/Wind Harmer
4.134
970257AG2-171 GEN
Solar/Wind Harmer
4.465
315785AD2-033 C
Solar/Wind Harmer
1.063
964241AG1-285 GEN
Solar/Wind Harmer
7.162
316131AB2-060 GEN
Solar/Wind Harmer
0.293
316313AB2-026
Solar/Wind Helper
0.96
316258AE1-075 C
Solar/Wind Helper
0.863
316405AF2-144 C
Solar/Wind Helper
0.719
3151931BEARGRDN S1
50/50
5.893
3151911BEARGRDN G1
50/50
4.566
3144293JTRSVLE
50/50
0.617
3151601KERR 3
50/50
0.119
3151581KERR 1
50/50
0.042
316336AC2-165 C
Solar/Wind Harmer
0.029
970937AG2-583 GEN
Solar/Wind Harmer
37.457
972003AH1-546 GEN
Solar/Wind Harmer
19.992
971377AH1-170 GEN
Solar/Wind Harmer
4.658
3147623JAMES R
Solar/Wind Harmer
1.012
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.151
3146926FARMVIL
Solar/Wind Harmer
0.171
963171AG1-166 GEN
Solar/Wind Harmer
0.974
971563AH1-280 GEN
Solar/Wind Harmer
1.948
970685AG2-442 GEN
Solar/Wind Harmer
12.075
316237AB2-079_GEN
Solar/Wind Harmer
0.001
962491AG1-098 GEN
Solar/Wind Harmer
4.869
315693AD1-088 GEN
Solar/Wind Harmer
3.802
970401AG2-262 GEN
Solar/Wind Harmer
0.394
962751AG1-124 GEN
Solar/Wind Harmer
2.965
3143226MDLTHAN
Solar/Wind Helper
0.215
3143526WINTERP
Solar/Wind Helper
0.908
3144293JTRSVLE
50/50
0.617
3144293JTRSVLE
50/50
0.519
970535AG2-341 GEN
50/50
1.291
971489AH1-241 GEN
Solar/Wind Harmer
23.288
3146776BUCKING
Solar/Wind Harmer
1.511
3146776BUCKING
Solar/Wind Harmer
0.122
315821AE2-092 GEN
Solar/Wind Harmer
0.018
970301AG2-198 GEN
Solar/Wind Harmer
8.425
3147133PAMPLIN
Solar/Wind Harmer
0.197
3147133PAMPLIN
Solar/Wind Harmer
0.158
958211AF2-115 GEN
Solar/Wind Harmer
2.191
963191AG1-168 GEN
Solar/Wind Harmer
0.73
971741AH1-377 GEN
Solar/Wind Harmer
16.896
316034AC1-036 C
Solar/Wind Harmer
0.01
970323AG2-213 GEN
Solar/Wind Harmer
5.954
971775AH1-396 GEN
Solar/Wind Harmer
0.223
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.389
964791AG1-342 GEN
Solar/Wind Harmer
1.289
3146843MT LREL
Solar/Wind Harmer
0.067
3146843MT LREL
Solar/Wind Harmer
0.067
939181AE1-148 GEN
Solar/Wind Harmer
3.035
3143526WINTERP
Solar/Wind Helper
0.908
972205AH1-687 GEN
50/50
22.272
3151611KERR 4
50/50
0.119
3151621KERR 5
50/50
0.119
3151631KERR 6
50/50
0.119
3151641KERR 7
50/50
0.119
971447AH1-217 GEN
Solar/Wind Harmer
12.405
971845AH1-439 GEN
Solar/Wind Harmer
16.776
970285AG2-188 GEN
Solar/Wind Harmer
28.087
270494AE1-108_GEN
Solar/Wind Harmer
4.136
315657AE1-056 GEN
Solar/Wind Harmer
6.8
946301AF1-294 GEN
Solar/Wind Harmer
3.603
961791AG1-021 GEN
Solar/Wind Harmer
1.753
970683AG2-441 GEN
Solar/Wind Harmer
10.781
970681AG2-440 GEN
Solar/Wind Harmer
8.625
3144303KENBRDG
Solar/Wind Harmer
0.112
971443AH1-215 GEN
Solar/Wind Harmer
2.312
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.152
316233AE1-074 FULL
Solar/Wind Helper
0.267
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.417
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.366
MECLTFEXP_MEC->PJM
CLTF
0.764
SIGELTFEXP_SIGE->PJM
CLTF
0.024
CPLELTFEXP_CPLE->PJM
CLTF
1.26
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.459
LAGNLTFEXP_LAGN->PJM
CLTF
1.304
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.091
TVALTFEXP_TVA->PJM
CLTF
0.67
NYPJM->LTFIMP_NY
CLTF
0.423
LGEELTFEXP_LGEE->PJM
CLTF
0.308
WECLTFEXP_WEC->PJM
CLTF
0.154

Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.65 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:1006.31
MW Contribution:1.34
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
3.824
3151911BEARGRDN G1
50/50
2.963
3144293JTRSVLE
50/50
0.501
3151531CLOVER1
50/50
2.179
3151601KERR 3
50/50
0.134
3151581KERR 1
50/50
0.048
316336AC2-165 C
Solar/Wind Harmer
0.025
970937AG2-583 GEN
Solar/Wind Harmer
28.676
972003AH1-546 GEN
Solar/Wind Harmer
13.102
971377AH1-170 GEN
Solar/Wind Harmer
3.023
3147623JAMES R
Solar/Wind Harmer
0.657
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
963171AG1-166 GEN
Solar/Wind Harmer
0.792
971563AH1-280 GEN
Solar/Wind Harmer
1.583
970685AG2-442 GEN
Solar/Wind Harmer
10.06
962491AG1-098 GEN
Solar/Wind Harmer
7.008
315693AD1-088 GEN
Solar/Wind Harmer
5.758
957481AF2-042 GEN
Solar/Wind Harmer
29.062
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.003
970401AG2-262 GEN
Solar/Wind Harmer
0.448
316003AC1-222 GEN
Solar/Wind Harmer
0.002
3143226MDLTHAN
Solar/Wind Helper
0.301
3143526WINTERP
Solar/Wind Helper
1.298
3142543TWELFTH
Solar/Wind Helper
0.014
3142416OLDCHRC
Solar/Wind Helper
0.298
3142416OLDCHRC
Solar/Wind Helper
0.114
316458AB2-190 GEN2
Solar/Wind Helper
0.644
3142433PROV 92
Solar/Wind Helper
0.447
3144293JTRSVLE
50/50
0.501
3144293JTRSVLE
50/50
0.422
970535AG2-341 GEN
50/50
1.342
3152661PLYWOOD A
50/50
0.157
971489AH1-241 GEN
Solar/Wind Harmer
15.115
3146776BUCKING
Solar/Wind Harmer
1.047
3146776BUCKING
Solar/Wind Harmer
0.085
315821AE2-092 GEN
Solar/Wind Harmer
0.012
970301AG2-198 GEN
Solar/Wind Harmer
7.46
971741AH1-377 GEN
Solar/Wind Harmer
16.096
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.126
958211AF2-115 GEN
Solar/Wind Harmer
1.781
963191AG1-168 GEN
Solar/Wind Harmer
0.594
316034AC1-036 C
Solar/Wind Harmer
0.009
970323AG2-213 GEN
Solar/Wind Harmer
5.129
971775AH1-396 GEN
Solar/Wind Harmer
0.192
970099AG2-077 GEN
Solar/Wind Harmer
11.625
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.75
964791AG1-342 GEN
Solar/Wind Harmer
1.467
3146843MT LREL
Solar/Wind Harmer
0.076
3146843MT LREL
Solar/Wind Harmer
0.076
939181AE1-148 GEN
Solar/Wind Harmer
3.307
3143526WINTERP
Solar/Wind Helper
1.298
316240AF1-291 C
Solar/Wind Helper
0.163
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.157
316075AC2-137 C
Solar/Wind Helper
0.174
3151921BEARGRDN G2
50/50
2.963
3144293JTRSVLE
50/50
0.501
970413AG2-270 GEN
50/50
9.511
966251AG1-494 GEN
50/50
1.191
3151591KERR 2
50/50
0.134
970221AG2-151 GEN
Solar/Wind Harmer
15.115
3146776BUCKING
Solar/Wind Harmer
0.094
3146926FARMVIL
Solar/Wind Harmer
0.129
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
1.865
3147133PAMPLIN
Solar/Wind Harmer
0.496
971193AH1-056 GEN
Solar/Wind Harmer
9.619
963181AG1-167 GEN
Solar/Wind Harmer
0.594
959311AF2-222 GEN
Solar/Wind Harmer
11.056
970257AG2-171 GEN
Solar/Wind Harmer
3.847
315785AD2-033 C
Solar/Wind Harmer
0.931
958131AF2-107 GEN
Solar/Wind Harmer
2.944
316478AD1-087 GEN
Solar/Wind Harmer
0.355
316486AD2-202 GEN
Solar/Wind Harmer
0.104
964241AG1-285 GEN
Solar/Wind Harmer
6.611
316131AB2-060 GEN
Solar/Wind Harmer
0.283
3148013FISHERV
Solar/Wind Harmer
0.07
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.916
971683AH1-343 GEN
Solar/Wind Harmer
2.335
316313AB2-026
Solar/Wind Helper
1.246
316258AE1-075 C
Solar/Wind Helper
1.121
316405AF2-144 C
Solar/Wind Helper
0.934
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.714
315839AE2-212 C
Solar/Wind Helper
0.156
972205AH1-687 GEN
50/50
14.45
3151541CLOVER2
50/50
2.169
3151611KERR 4
50/50
0.134
3151621KERR 5
50/50
0.134
3151631KERR 6
50/50
0.134
3151641KERR 7
50/50
0.134
971447AH1-217 GEN
Solar/Wind Harmer
8.134
971845AH1-439 GEN
Solar/Wind Harmer
11.699
970285AG2-188 GEN
Solar/Wind Harmer
19.821
270494AE1-108_GEN
Solar/Wind Harmer
2.719
315657AE1-056 GEN
Solar/Wind Harmer
5.448
946301AF1-294 GEN
Solar/Wind Harmer
2.929
961791AG1-021 GEN
Solar/Wind Harmer
1.425
970683AG2-441 GEN
Solar/Wind Harmer
8.983
970681AG2-440 GEN
Solar/Wind Harmer
7.186
3144303KENBRDG
Solar/Wind Harmer
0.096
971443AH1-215 GEN
Solar/Wind Harmer
1.998
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.187
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.068
3147243WELCO
Solar/Wind Harmer
0.043
970865AG2-541 GEN
Solar/Wind Harmer
2.117
316123AC1-075 GEN
Solar/Wind Harmer
0.077
970165AG2-112 GEN
Solar/Wind Harmer
0.456
970163AG2-111 GEN
Solar/Wind Harmer
0.435
316233AE1-074 FULL
Solar/Wind Helper
0.381
316312AB1-027
Solar/Wind Helper
0.218
316132AB2-190 GEN1
Solar/Wind Helper
0.644
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.157
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.592
MECLTFEXP_MEC->PJM
CLTF
1.02
SIGELTFEXP_SIGE->PJM
CLTF
0.033
CPLELTFEXP_CPLE->PJM
CLTF
0.579
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.662
LAGNLTFEXP_LAGN->PJM
CLTF
1.347
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.952
TVALTFEXP_TVA->PJM
CLTF
0.702
NYPJM->LTFIMP_NY
CLTF
0.35
LGEELTFEXP_LGEE->PJM
CLTF
0.439
WECLTFEXP_WEC->PJM
CLTF
0.224

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.1 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5539.41
MW Contribution:4.57
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
47.73
957481AF2-042 GEN
Solar/Wind Harmer
126.807
315693AD1-088 GEN
Solar/Wind Harmer
20.818
962491AG1-098 GEN
Solar/Wind Harmer
24.385
315687AD1-152 GEN
Solar/Wind Harmer
0.013
316003AC1-222 GEN
Solar/Wind Harmer
0.008
970401AG2-262 GEN
Solar/Wind Harmer
1.677
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
17.979
963171AG1-166 GEN
Solar/Wind Harmer
1.264
971563AH1-280 GEN
Solar/Wind Harmer
2.529
3146926FARMVIL
Solar/Wind Harmer
0.131
971065AG2-659 GEN
Solar/Wind Harmer
8.445
316129AC1-054 GEN
Solar/Wind Harmer
0.698
970223AG2-152 GEN
Solar/Wind Harmer
12.094
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.088
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.055
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.099
941801AE2-185 GEN
Solar/Wind Harmer
4.212
270030AE2-140 GEN
Solar/Wind Harmer
13.804
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.094
316359AB2-059 GEN
Solar/Wind Harmer
0.421
316049AB1-081 GEN
Solar/Wind Harmer
0.67
3142053HEARTS
Solar/Wind Harmer
0.206
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
941031AE2-094 GEN
Solar/Wind Harmer
138.271
944011AF1-069 GEN
Solar/Wind Harmer
45.178
970673AG2-436 GEN
Solar/Wind Harmer
149.315
970673AG2-436 GEN
Solar/Wind Harmer
99.544
971967AH1-528 GEN
Solar/Wind Harmer
95.481
970085AG2-068 GEN
Solar/Wind Harmer
31.82
970581AG2-369 GEN
Solar/Wind Harmer
27.365
3147173SINAI
Solar/Wind Harmer
0.309
3147243WELCO
Solar/Wind Harmer
0.193
316118AC1-105 GEN
Solar/Wind Harmer
0.768
970865AG2-541 GEN
Solar/Wind Harmer
9.078
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.118
3144303KENBRDG
Solar/Wind Harmer
0.196
970683AG2-441 GEN
Solar/Wind Harmer
16.053
970681AG2-440 GEN
Solar/Wind Harmer
12.842
946301AF1-294 GEN
Solar/Wind Harmer
4.678
961791AG1-021 GEN
Solar/Wind Harmer
2.276
315657AE1-056 GEN
Solar/Wind Harmer
8.085
316123AC1-075 GEN
Solar/Wind Harmer
0.315
970165AG2-112 GEN
Solar/Wind Harmer
1.87
970163AG2-111 GEN
Solar/Wind Harmer
1.784
970831AG2-522 GEN
Solar/Wind Harmer
7.35
970285AG2-188 GEN
Solar/Wind Harmer
12.402
971845AH1-439 GEN
Solar/Wind Harmer
6.507
270069AE2-166 C O1
Solar/Wind Harmer
0.004
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
53.421
316478AD1-087 GEN
Solar/Wind Harmer
1.525
316486AD2-202 GEN
Solar/Wind Harmer
0.448
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
13.182
316283AC2-100 C
Solar/Wind Harmer
0.55
971683AH1-343 GEN
Solar/Wind Harmer
10.2
316131AB2-060 GEN
Solar/Wind Harmer
0.796
964241AG1-285 GEN
Solar/Wind Harmer
16.703
315785AD2-033 C
Solar/Wind Harmer
2.003
970257AG2-171 GEN
Solar/Wind Harmer
7.834
959311AF2-222 GEN
Solar/Wind Harmer
21.656
963181AG1-167 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.736
971193AH1-056 GEN
Solar/Wind Harmer
14.274
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.131
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
0.943
3146776BUCKING
Solar/Wind Harmer
0.049
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.212
270336AE1-100 GEN
Solar/Wind Harmer
0.003
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.117
971623AH1-311 GEN
Solar/Wind Harmer
0.234
961601AG1-000A GEN
Solar/Wind Harmer
8.141
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
970533AG2-339 GEN
50/50
66.733
970531AG2-338 GEN
50/50
26.693
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
44.982
970099AG2-077 GEN
Solar/Wind Harmer
50.723
971741AH1-377 GEN
Solar/Wind Harmer
33.569
970301AG2-198 GEN
Solar/Wind Harmer
13.228
3146843MT LREL
Solar/Wind Harmer
0.286
3146843MT LREL
Solar/Wind Harmer
0.286
964791AG1-342 GEN
Solar/Wind Harmer
5.488
316222AC1-221 GEN
Solar/Wind Harmer
1.175
962561AG1-105 GEN
Solar/Wind Harmer
13.485
939181AE1-148 GEN
Solar/Wind Harmer
12.41
313527AB2-043 GEN
Solar/Wind Harmer
0.003
970323AG2-213 GEN
Solar/Wind Harmer
10.445
971775AH1-396 GEN
Solar/Wind Harmer
0.392
316034AC1-036 C
Solar/Wind Harmer
0.018
958211AF2-115 GEN
Solar/Wind Harmer
2.845
963191AG1-168 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.234
3147133PAMPLIN
Solar/Wind Harmer
0.187
942751AE2-291 GEN
Solar/Wind Harmer
11.476
270013AE1-250 PV
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.546
3146776BUCKING
Solar/Wind Harmer
0.044
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.276
316263AC1-034 GEN
Solar/Wind Harmer
4.449
961601AG1-000A GEN
Solar/Wind Harmer
2.035
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315
NYPJM->LTFIMP_NY
CLTF
2.382
LGEELTFEXP_LGEE->PJM
CLTF
2.675
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 51192_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51192_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.36 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:6013.11
MW Contribution:4.57
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
62.844
957481AF2-042 GEN
Solar/Wind Harmer
166.962
315693AD1-088 GEN
Solar/Wind Harmer
24.364
962491AG1-098 GEN
Solar/Wind Harmer
32.107
315687AD1-152 GEN
Solar/Wind Harmer
5.339
316003AC1-222 GEN
Solar/Wind Harmer
3.203
970401AG2-262 GEN
Solar/Wind Harmer
2.096
316237AB2-079_GEN
Solar/Wind Harmer
0.866
970685AG2-442 GEN
Solar/Wind Harmer
23.673
963171AG1-166 GEN
Solar/Wind Harmer
3.329
971563AH1-280 GEN
Solar/Wind Harmer
3.329
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.119
316129AC1-054 GEN
Solar/Wind Harmer
1.828
970223AG2-152 GEN
Solar/Wind Harmer
17.247
270016AE1-250 BESS
Solar/Wind Harmer
2.846
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.591
316322AB2-045
Solar/Wind Harmer
0.516
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.545
270030AE2-140 GEN
Solar/Wind Harmer
19.786
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.774
316049AB1-081 GEN
Solar/Wind Harmer
1.419
3142053HEARTS
Solar/Wind Harmer
0.155
970533AG2-339 GEN
50/50
66.733
970531AG2-338 GEN
50/50
26.693
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
168.81
316478AD1-087 GEN
Solar/Wind Harmer
4.25
316486AD2-202 GEN
Solar/Wind Harmer
1.245
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
1.046
960061AF2-297 GEN
Solar/Wind Harmer
17.357
316283AC2-100 C
Solar/Wind Harmer
2.974
971683AH1-343 GEN
Solar/Wind Harmer
13.43
316131AB2-060 GEN
Solar/Wind Harmer
3.068
964241AG1-285 GEN
Solar/Wind Harmer
21.992
315785AD2-033 C
Solar/Wind Harmer
6.274
970257AG2-171 GEN
Solar/Wind Harmer
10.314
959311AF2-222 GEN
Solar/Wind Harmer
28.571
963181AG1-167 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.462
942461AE2-259 GEN
Solar/Wind Harmer
3.832
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.378
270197AD1-017 GEN1
Solar/Wind Harmer
1.68
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.844
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.545
270336AE1-100 GEN
Solar/Wind Harmer
1.569
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
5.12
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
59.226
970099AG2-077 GEN
Solar/Wind Harmer
66.785
971741AH1-377 GEN
Solar/Wind Harmer
44.199
970301AG2-198 GEN
Solar/Wind Harmer
17.416
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.86
316222AC1-221 GEN
Solar/Wind Harmer
3.218
962561AG1-105 GEN
Solar/Wind Harmer
17.755
939181AE1-148 GEN
Solar/Wind Harmer
16.34
313527AB2-043 GEN
Solar/Wind Harmer
4.631
970323AG2-213 GEN
Solar/Wind Harmer
13.752
971775AH1-396 GEN
Solar/Wind Harmer
1.958
316034AC1-036 C
Solar/Wind Harmer
0.51
958211AF2-115 GEN
Solar/Wind Harmer
4.162
963191AG1-168 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.11
270013AE1-250 PV
Solar/Wind Harmer
2.846
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.4
316197AC1-042 GEN
Solar/Wind Harmer
1.819
942671AE2-283 GEN
Solar/Wind Harmer
4.898
316263AC1-034 GEN
Solar/Wind Harmer
6.166
961601AG1-000A GEN
Solar/Wind Harmer
5.056
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
941031AE2-094 GEN
Solar/Wind Harmer
158.157
944011AF1-069 GEN
Solar/Wind Harmer
49.556
970673AG2-436 GEN
Solar/Wind Harmer
165.209
970673AG2-436 GEN
Solar/Wind Harmer
83.65
971967AH1-528 GEN
Solar/Wind Harmer
126.052
970085AG2-068 GEN
Solar/Wind Harmer
41.896
970581AG2-369 GEN
Solar/Wind Harmer
36.031
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.3
970865AG2-541 GEN
Solar/Wind Harmer
11.953
316239AB2-077_GEN
Solar/Wind Harmer
0.866
316238AB2-078_GEN
Solar/Wind Harmer
0.866
971443AH1-215 GEN
Solar/Wind Harmer
5.422
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.136
970681AG2-440 GEN
Solar/Wind Harmer
16.909
946301AF1-294 GEN
Solar/Wind Harmer
6.825
961791AG1-021 GEN
Solar/Wind Harmer
3.329
270455AD2-022 GEN
Solar/Wind Harmer
4.714
270457AD2-023 GEN
Solar/Wind Harmer
2.39
315657AE1-056 GEN
Solar/Wind Harmer
9.877
316123AC1-075 GEN
Solar/Wind Harmer
2.797
970165AG2-112 GEN
Solar/Wind Harmer
2.462
970163AG2-111 GEN
Solar/Wind Harmer
2.349
970831AG2-522 GEN
Solar/Wind Harmer
9.678
970285AG2-188 GEN
Solar/Wind Harmer
15.412
971845AH1-439 GEN
Solar/Wind Harmer
8.567
270069AE2-166 C O1
Solar/Wind Harmer
2.422
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315
NYPJM->LTFIMP_NY
CLTF
2.382
LGEELTFEXP_LGEE->PJM
CLTF
2.675
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 51172_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51172_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.82 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5986.29
MW Contribution:4.58
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
8.374
970413AG2-270 GEN
50/50
40.637
3151591KERR 2
50/50
0.538
3144293JTRSVLE
50/50
0.8
315243AE2-183_GT3
50/50
11.056
3151051BRUNSWICKS1
50/50
17.38
3151021BRUNSWICKG1
50/50
8.374
971451AH1-221 GEN
50/50
25.435
3151531CLOVER1
50/50
9.312
3151601KERR 3
50/50
0.538
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.8
971629AH1-314 GEN
50/50
17.875
3151561HALLBR1
50/50
0.366
970919AG2-571 GEN
Solar/Wind Harmer
21.227
970087AG2-069 GEN
Solar/Wind Harmer
62.431
957481AF2-042 GEN
Solar/Wind Harmer
166.01
315693AD1-088 GEN
Solar/Wind Harmer
24.233
962491AG1-098 GEN
Solar/Wind Harmer
31.935
315687AD1-152 GEN
Solar/Wind Harmer
5.313
316003AC1-222 GEN
Solar/Wind Harmer
3.193
970401AG2-262 GEN
Solar/Wind Harmer
2.094
316237AB2-079_GEN
Solar/Wind Harmer
0.868
970685AG2-442 GEN
Solar/Wind Harmer
23.682
963171AG1-166 GEN
Solar/Wind Harmer
3.328
971563AH1-280 GEN
Solar/Wind Harmer
3.328
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.224
316129AC1-054 GEN
Solar/Wind Harmer
1.849
970223AG2-152 GEN
Solar/Wind Harmer
17.201
270016AE1-250 BESS
Solar/Wind Harmer
2.839
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.577
316322AB2-045
Solar/Wind Harmer
0.514
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.53
270030AE2-140 GEN
Solar/Wind Harmer
19.734
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.817
316049AB1-081 GEN
Solar/Wind Harmer
1.454
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.785
316375AC2-012 GEN
Solar/Wind Helper
1.014
3145336SMITFLD
Solar/Wind Helper
1.482
316388AE2-253 GEN
Solar/Wind Helper
1.397
3146456SLIGO L269
Solar/Wind Helper
0.359
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.402
316159AE1-175 C
Solar/Wind Helper
0.529
316381AD1-082 GEN
Solar/Wind Helper
1.758
316458AB2-190 GEN2
Solar/Wind Helper
1.933
3141766HARMONY
Solar/Wind Helper
0.065
3138133OCRAN
Solar/Wind Helper
0.193
3142433PROV 92
Solar/Wind Helper
1.275
3142543TWELFTH
Solar/Wind Helper
0.029
964211AG1-282 GEN
Solar/Wind Helper
0.412
3141726DUNNSVL
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.961
3146516WINFALL
Solar/Wind Helper
0.297
316337AD2-073 GEN
Solar/Wind Helper
0.448
3142416OLDCHRC
Solar/Wind Helper
0.759
3142416OLDCHRC
Solar/Wind Helper
0.291
3143526WINTERP
Solar/Wind Helper
1.499
3143226MDLTHAN
Solar/Wind Helper
0.284
315800Z1-036_GEN1
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
970917AG2-570 GEN
Solar/Wind Harmer
167.695
316478AD1-087 GEN
Solar/Wind Harmer
4.227
316486AD2-202 GEN
Solar/Wind Harmer
1.238
970909AG2-566 GEN
Solar/Wind Harmer
3.291
316248AF1-058 C
Solar/Wind Harmer
1.043
960061AF2-297 GEN
Solar/Wind Harmer
17.305
316283AC2-100 C
Solar/Wind Harmer
2.965
971683AH1-343 GEN
Solar/Wind Harmer
13.39
316131AB2-060 GEN
Solar/Wind Harmer
3.076
964241AG1-285 GEN
Solar/Wind Harmer
22.038
315785AD2-033 C
Solar/Wind Harmer
6.282
970257AG2-171 GEN
Solar/Wind Harmer
10.326
959311AF2-222 GEN
Solar/Wind Harmer
28.597
963181AG1-167 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.449
942461AE2-259 GEN
Solar/Wind Harmer
3.824
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.375
270197AD1-017 GEN1
Solar/Wind Harmer
1.676
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.834
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.53
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.564
961601AG1-000A GEN
Solar/Wind Harmer
5.252
315773AC2-141 GEN
Solar/Wind Helper
9.163
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.058
3145336SMITFLD
Solar/Wind Helper
0.148
3146456SLIGO L269
Solar/Wind Helper
0.359
316382AG1-145 C
Solar/Wind Helper
0.469
315839AE2-212 C
Solar/Wind Helper
0.457
316320Y1-086
Solar/Wind Helper
0.148
316156AD2-030 GEN
Solar/Wind Helper
0.492
316280AD1-041 GEN
Solar/Wind Helper
1.092
3142946ENON
Solar/Wind Helper
0.105
316484AD2-074 GEN
Solar/Wind Helper
0.607
316404AE1-155 C
Solar/Wind Helper
2.624
316435W1029_GEN3
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3141906WESTMOR
Solar/Wind Helper
0.115
3146626S HERTFORD
Solar/Wind Helper
0.28
316473AC1-191 GEN
Solar/Wind Helper
1.696
3145273HOLLAND
Solar/Wind Helper
0.188
966881AG1-559 GEN
Solar/Wind Helper
0.329
3146376EDENTON
Solar/Wind Helper
0.226
970533AG2-339 GEN
50/50
66.25
970531AG2-338 GEN
50/50
26.5
315242AE2-183_GT2
50/50
11.056
315241AE2-183_GT1
50/50
10.988
972185AH1-677 GEN
50/50
39.858
3151041BRUNSWICKG3
50/50
8.374
972187AH1-678 GEN
50/50
19.217
3152661PLYWOOD A
50/50
0.67
970535AG2-341 GEN
50/50
4.577
3144293JTRSVLE
50/50
0.8
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
58.849
970099AG2-077 GEN
Solar/Wind Harmer
66.404
971741AH1-377 GEN
Solar/Wind Harmer
43.978
970301AG2-198 GEN
Solar/Wind Harmer
17.332
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.854
316222AC1-221 GEN
Solar/Wind Harmer
3.208
962561AG1-105 GEN
Solar/Wind Harmer
17.747
939181AE1-148 GEN
Solar/Wind Harmer
16.378
313527AB2-043 GEN
Solar/Wind Harmer
4.643
970323AG2-213 GEN
Solar/Wind Harmer
13.768
971775AH1-396 GEN
Solar/Wind Harmer
1.961
316034AC1-036 C
Solar/Wind Harmer
0.511
958211AF2-115 GEN
Solar/Wind Harmer
4.16
963191AG1-168 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.066
270013AE1-250 PV
Solar/Wind Harmer
2.839
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.394
316197AC1-042 GEN
Solar/Wind Harmer
1.815
942671AE2-283 GEN
Solar/Wind Harmer
4.885
316263AC1-034 GEN
Solar/Wind Harmer
6.316
961601AG1-000A GEN
Solar/Wind Harmer
5.186
316036AC1-147 C
Solar/Wind Helper
0.59
3142956BIRDNECK
Solar/Wind Helper
0.259
316316AC1-027 C
Solar/Wind Helper
0.606
316185AD1-033 GEN
Solar/Wind Helper
1.799
3145506HICKORY
Solar/Wind Helper
1.507
3145506HICKORY
Solar/Wind Helper
0.904
3145506HICKORY
Solar/Wind Helper
0.226
316236AE1-162_GEN
Solar/Wind Helper
0.498
316339AD2-160 GEN
Solar/Wind Helper
1.397
316018AA1-139 ULT2
Solar/Wind Helper
1.567
316017AA1-139 ULT1
Solar/Wind Helper
1.665
3137176SLIGO L2192
Solar/Wind Helper
1.432
3130086AYDLETT
Solar/Wind Helper
1.421
316033AB2-134 GEN
Solar/Wind Helper
1.19
315697AD1-025 GEN
Solar/Wind Helper
3.953
3146386ELIZ CT
Solar/Wind Helper
0.331
316240AF1-291 C
Solar/Wind Helper
0.444
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.318
316075AC2-137 C
Solar/Wind Helper
0.467
316077AC2-138 C
Solar/Wind Helper
0.286
316431W1029_GEN1
Solar/Wind Helper
1.225
316433W1029_GEN2
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3143526WINTERP
Solar/Wind Helper
1.499
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
966871AG1-558 GEN
Solar/Wind Helper
0.374
3144356SAPONY
Solar/Wind Helper
0.492
316468AD1-105 GEN
Solar/Wind Helper
1.305
315244AE2-183_ST
50/50
19.115
963041AG1-153 GEN
50/50
16.957
3151541CLOVER2
50/50
9.268
3151611KERR 4
50/50
0.538
3151621KERR 5
50/50
0.538
3151631KERR 6
50/50
0.538
3151641KERR 7
50/50
0.538
941031AE2-094 GEN
Solar/Wind Harmer
157.012
944011AF1-069 GEN
Solar/Wind Harmer
49.197
970673AG2-436 GEN
Solar/Wind Harmer
164.043
970673AG2-436 GEN
Solar/Wind Harmer
83.06
971967AH1-528 GEN
Solar/Wind Harmer
125.223
970085AG2-068 GEN
Solar/Wind Harmer
41.62
970581AG2-369 GEN
Solar/Wind Harmer
35.794
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.295
970865AG2-541 GEN
Solar/Wind Harmer
11.917
316239AB2-077_GEN
Solar/Wind Harmer
0.868
316238AB2-078_GEN
Solar/Wind Harmer
0.868
971443AH1-215 GEN
Solar/Wind Harmer
5.428
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.145
970681AG2-440 GEN
Solar/Wind Harmer
16.916
946301AF1-294 GEN
Solar/Wind Harmer
6.823
961791AG1-021 GEN
Solar/Wind Harmer
3.328
270455AD2-022 GEN
Solar/Wind Harmer
4.701
270457AD2-023 GEN
Solar/Wind Harmer
2.384
315657AE1-056 GEN
Solar/Wind Harmer
9.869
316123AC1-075 GEN
Solar/Wind Harmer
2.789
970165AG2-112 GEN
Solar/Wind Harmer
2.455
970163AG2-111 GEN
Solar/Wind Harmer
2.342
970831AG2-522 GEN
Solar/Wind Harmer
9.813
970285AG2-188 GEN
Solar/Wind Harmer
15.354
971845AH1-439 GEN
Solar/Wind Harmer
8.535
270069AE2-166 C O1
Solar/Wind Harmer
2.415
319010AE1-072 C
Solar/Wind Helper
4.079
3143316POE
Solar/Wind Helper
1.407
316305AF2-043 C
Solar/Wind Helper
0.473
316369SG1_INVT
Solar/Wind Helper
1.664
957831AF2-077 GEN
Solar/Wind Helper
0.466
316132AB2-190 GEN1
Solar/Wind Helper
1.933
316349AD2-085 GEN
Solar/Wind Helper
1.523
313526AB2-022
Solar/Wind Helper
0.505
957601AF2-054 GEN
Solar/Wind Helper
0.438
3141873WAN 176
Solar/Wind Helper
0.065
315662AE1-191 GEN
Solar/Wind Helper
1.747
315666AE1-190 GEN
Solar/Wind Helper
0.437
316059AD1-063 C
Solar/Wind Helper
0.326
3141913WHIT STONE
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3138133OCRAN
Solar/Wind Helper
0.097
3143873LANEXA
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.128
316321Z2-027
Solar/Wind Helper
0.487
3145176PASQUOTANK
Solar/Wind Helper
0.198
3141813NORNECK
Solar/Wind Helper
0.304
316312AB1-027
Solar/Wind Helper
0.556
316233AE1-074 FULL
Solar/Wind Helper
0.44
316223AC1-118
Solar/Wind Helper
0.438
316315AB2-025 C
Solar/Wind Helper
0.418
315611Z1-036_GEN2
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
3130156CHOWAN
Solar/Wind Helper
0.226
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.554
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.081
MECLTFEXP_MEC->PJM
CLTF
7.343
SIGELTFEXP_SIGE->PJM
CLTF
0.22
CPLELTFEXP_CPLE->PJM
CLTF
19.708
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.004
LAGNLTFEXP_LAGN->PJM
CLTF
14.626
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.161
TVALTFEXP_TVA->PJM
CLTF
7.294
NYPJM->LTFIMP_NY
CLTF
2.38
LGEELTFEXP_LGEE->PJM
CLTF
2.666
WECLTFEXP_WEC->PJM
CLTF
1.395
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 511T544_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T544_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.15 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5902.9
MW Contribution:4.52
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
10.962
3151051BRUNSWICKS1
50/50
17.232
3151021BRUNSWICKG1
50/50
8.303
971451AH1-221 GEN
50/50
25.218
3151531CLOVER1
50/50
9.227
3151601KERR 3
50/50
0.532
3151581KERR 1
50/50
0.19
3144293JTRSVLE
50/50
0.79
971629AH1-314 GEN
50/50
17.731
3151561HALLBR1
50/50
0.363
970919AG2-571 GEN
Solar/Wind Harmer
21.047
970087AG2-069 GEN
Solar/Wind Harmer
61.902
957481AF2-042 GEN
Solar/Wind Harmer
164.509
315693AD1-088 GEN
Solar/Wind Harmer
24.007
962491AG1-098 GEN
Solar/Wind Harmer
31.634
315687AD1-152 GEN
Solar/Wind Harmer
5.265
316003AC1-222 GEN
Solar/Wind Harmer
3.162
970401AG2-262 GEN
Solar/Wind Harmer
2.07
316237AB2-079_GEN
Solar/Wind Harmer
0.856
970685AG2-442 GEN
Solar/Wind Harmer
23.354
963171AG1-166 GEN
Solar/Wind Harmer
3.283
971563AH1-280 GEN
Solar/Wind Harmer
3.283
3146926FARMVIL
Solar/Wind Harmer
-0.014
971065AG2-659 GEN
Solar/Wind Harmer
11.094
316129AC1-054 GEN
Solar/Wind Harmer
1.827
970223AG2-152 GEN
Solar/Wind Harmer
17.059
270016AE1-250 BESS
Solar/Wind Harmer
2.815
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.528
316322AB2-045
Solar/Wind Harmer
0.506
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.477
270030AE2-140 GEN
Solar/Wind Harmer
19.567
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.809
316049AB1-081 GEN
Solar/Wind Harmer
1.448
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.244
316381AD1-082 GEN
Solar/Wind Helper
1.747
316375AC2-012 GEN
Solar/Wind Helper
0.879
3145336SMITFLD
Solar/Wind Helper
1.331
316458AB2-190 GEN2
Solar/Wind Helper
1.893
316159AE1-175 C
Solar/Wind Helper
0.497
316388AE2-253 GEN
Solar/Wind Helper
1.201
3142433PROV 92
Solar/Wind Helper
1.254
3142543TWELFTH
Solar/Wind Helper
0.03
3141766HARMONY
Solar/Wind Helper
0.062
3146456SLIGO L269
Solar/Wind Helper
0.308
3138133OCRAN
Solar/Wind Helper
0.185
316072AD1-144
Solar/Wind Helper
0.35
316246AF1-032 C
Solar/Wind Helper
0.342
964211AG1-282 GEN
Solar/Wind Helper
0.397
3141726DUNNSVL
Solar/Wind Helper
1.179
3143526WINTERP
Solar/Wind Helper
1.519
3142416OLDCHRC
Solar/Wind Helper
0.752
3143226MDLTHAN
Solar/Wind Helper
0.289
3142416OLDCHRC
Solar/Wind Helper
0.288
316337AD2-073 GEN
Solar/Wind Helper
0.434
3146516WINFALL
Solar/Wind Helper
0.813
3146516WINFALL
Solar/Wind Helper
0.251
970533AG2-339 GEN
50/50
65.686
970531AG2-338 GEN
50/50
26.274
315242AE2-183_GT2
50/50
10.962
315241AE2-183_GT1
50/50
10.894
972185AH1-677 GEN
50/50
39.518
3151041BRUNSWICKG3
50/50
8.303
972187AH1-678 GEN
50/50
19.053
3152661PLYWOOD A
50/50
0.663
970535AG2-341 GEN
50/50
4.519
3144293JTRSVLE
50/50
0.79
3144293JTRSVLE
50/50
0.665
970933AG2-581 GEN
Solar/Wind Harmer
58.334
970099AG2-077 GEN
Solar/Wind Harmer
65.804
971741AH1-377 GEN
Solar/Wind Harmer
43.523
970301AG2-198 GEN
Solar/Wind Harmer
17.145
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.775
316222AC1-221 GEN
Solar/Wind Harmer
3.182
962561AG1-105 GEN
Solar/Wind Harmer
17.536
939181AE1-148 GEN
Solar/Wind Harmer
16.186
313527AB2-043 GEN
Solar/Wind Harmer
4.576
970323AG2-213 GEN
Solar/Wind Harmer
13.574
971775AH1-396 GEN
Solar/Wind Harmer
1.933
316034AC1-036 C
Solar/Wind Harmer
0.503
958211AF2-115 GEN
Solar/Wind Harmer
4.103
963191AG1-168 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
14.918
270013AE1-250 PV
Solar/Wind Harmer
2.815
3146776BUCKING
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.37
316197AC1-042 GEN
Solar/Wind Harmer
1.797
942671AE2-283 GEN
Solar/Wind Harmer
4.838
316263AC1-034 GEN
Solar/Wind Harmer
6.29
961601AG1-000A GEN
Solar/Wind Harmer
5.16
316240AF1-291 C
Solar/Wind Helper
0.471
316036AC1-147 C
Solar/Wind Helper
0.511
316236AE1-162_GEN
Solar/Wind Helper
0.447
316316AC1-027 C
Solar/Wind Helper
0.524
3142956BIRDNECK
Solar/Wind Helper
0.223
316033AB2-134 GEN
Solar/Wind Helper
1.137
315697AD1-025 GEN
Solar/Wind Helper
3.779
316185AD1-033 GEN
Solar/Wind Helper
1.551
3145506HICKORY
Solar/Wind Helper
1.298
3145506HICKORY
Solar/Wind Helper
0.779
3145506HICKORY
Solar/Wind Helper
0.195
3144356SAPONY
Solar/Wind Helper
0.581
316339AD2-160 GEN
Solar/Wind Helper
1.201
316018AA1-139 ULT2
Solar/Wind Helper
1.346
316017AA1-139 ULT1
Solar/Wind Helper
1.43
3142946ENON
Solar/Wind Helper
0.031
3137176SLIGO L2192
Solar/Wind Helper
1.229
3130086AYDLETT
Solar/Wind Helper
1.219
316487AF1-042 GEN
Solar/Wind Helper
0.305
316075AC2-137 C
Solar/Wind Helper
0.459
316077AC2-138 C
Solar/Wind Helper
0.276
3143526WINTERP
Solar/Wind Helper
1.519
3146386ELIZ CT
Solar/Wind Helper
0.283
966871AG1-558 GEN
Solar/Wind Helper
0.376
316468AD1-105 GEN
Solar/Wind Helper
1.308
316431W1029_GEN1
Solar/Wind Helper
1.037
316433W1029_GEN2
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146626S HERTFORD
Solar/Wind Helper
0.236
3146626S HERTFORD
Solar/Wind Helper
0.236
3151031BRUNSWICKG2
50/50
8.303
970413AG2-270 GEN
50/50
40.265
3151591KERR 2
50/50
0.532
3144293JTRSVLE
50/50
0.79
970917AG2-570 GEN
Solar/Wind Harmer
166.275
316478AD1-087 GEN
Solar/Wind Harmer
4.189
316486AD2-202 GEN
Solar/Wind Harmer
1.227
970909AG2-566 GEN
Solar/Wind Harmer
3.255
316248AF1-058 C
Solar/Wind Harmer
1.033
960061AF2-297 GEN
Solar/Wind Harmer
17.135
316283AC2-100 C
Solar/Wind Harmer
2.94
971683AH1-343 GEN
Solar/Wind Harmer
13.259
316131AB2-060 GEN
Solar/Wind Harmer
3.032
964241AG1-285 GEN
Solar/Wind Harmer
21.724
315785AD2-033 C
Solar/Wind Harmer
6.194
970257AG2-171 GEN
Solar/Wind Harmer
10.181
959311AF2-222 GEN
Solar/Wind Harmer
28.197
963181AG1-167 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.081
971193AH1-056 GEN
Solar/Wind Harmer
16.225
942461AE2-259 GEN
Solar/Wind Harmer
3.773
3146926FARMVIL
Solar/Wind Harmer
-0.014
270018AE2-047 C O1
Solar/Wind Harmer
1.363
270197AD1-017 GEN1
Solar/Wind Harmer
1.661
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.802
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.477
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.551
961601AG1-000A GEN
Solar/Wind Harmer
5.225
315773AC2-141 GEN
Solar/Wind Helper
8.525
315839AE2-212 C
Solar/Wind Helper
0.497
3144536CHRHLND
Solar/Wind Helper
0.05
3144873MCLAUGH
Solar/Wind Helper
0.008
3145336SMITFLD
Solar/Wind Helper
0.133
316382AG1-145 C
Solar/Wind Helper
0.441
316156AD2-030 GEN
Solar/Wind Helper
0.47
3142946ENON
Solar/Wind Helper
0.104
316280AD1-041 GEN
Solar/Wind Helper
1.046
3146456SLIGO L269
Solar/Wind Helper
0.308
316484AD2-074 GEN
Solar/Wind Helper
0.583
316404AE1-155 C
Solar/Wind Helper
2.523
316320Y1-086
Solar/Wind Helper
0.126
316473AC1-191 GEN
Solar/Wind Helper
1.704
3141906WESTMOR
Solar/Wind Helper
0.111
316435W1029_GEN3
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
966881AG1-559 GEN
Solar/Wind Helper
0.328
3146626S HERTFORD
Solar/Wind Helper
0.236
315244AE2-183_ST
50/50
18.952
963041AG1-153 GEN
50/50
16.812
3151541CLOVER2
50/50
9.183
3151611KERR 4
50/50
0.532
3151621KERR 5
50/50
0.532
3151631KERR 6
50/50
0.532
3151641KERR 7
50/50
0.532
941031AE2-094 GEN
Solar/Wind Harmer
155.676
944011AF1-069 GEN
Solar/Wind Harmer
48.778
970673AG2-436 GEN
Solar/Wind Harmer
162.646
970673AG2-436 GEN
Solar/Wind Harmer
82.352
971967AH1-528 GEN
Solar/Wind Harmer
124.141
970085AG2-068 GEN
Solar/Wind Harmer
41.268
970581AG2-369 GEN
Solar/Wind Harmer
35.491
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.271
970865AG2-541 GEN
Solar/Wind Harmer
11.801
316239AB2-077_GEN
Solar/Wind Harmer
0.856
316238AB2-078_GEN
Solar/Wind Harmer
0.856
971443AH1-215 GEN
Solar/Wind Harmer
5.352
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
20.851
970681AG2-440 GEN
Solar/Wind Harmer
16.681
946301AF1-294 GEN
Solar/Wind Harmer
6.73
961791AG1-021 GEN
Solar/Wind Harmer
3.283
270455AD2-022 GEN
Solar/Wind Harmer
4.664
270457AD2-023 GEN
Solar/Wind Harmer
2.365
315657AE1-056 GEN
Solar/Wind Harmer
9.735
316123AC1-075 GEN
Solar/Wind Harmer
2.761
970165AG2-112 GEN
Solar/Wind Harmer
2.431
970163AG2-111 GEN
Solar/Wind Harmer
2.319
970831AG2-522 GEN
Solar/Wind Harmer
9.696
970285AG2-188 GEN
Solar/Wind Harmer
15.118
971845AH1-439 GEN
Solar/Wind Harmer
8.397
270069AE2-166 C O1
Solar/Wind Harmer
2.394
3143316POE
Solar/Wind Helper
1.57
316132AB2-190 GEN1
Solar/Wind Helper
1.893
316369SG1_INVT
Solar/Wind Helper
1.59
957831AF2-077 GEN
Solar/Wind Helper
0.437
316315AB2-025 C
Solar/Wind Helper
0.494
957601AF2-054 GEN
Solar/Wind Helper
0.418
3141873WAN 176
Solar/Wind Helper
0.062
315662AE1-191 GEN
Solar/Wind Helper
1.674
315666AE1-190 GEN
Solar/Wind Helper
0.419
3143873LANEXA
Solar/Wind Helper
0.186
316059AD1-063 C
Solar/Wind Helper
0.312
3141913WHIT STONE
Solar/Wind Helper
0.309
3138133OCRAN
Solar/Wind Helper
0.093
3141783LANCAST
Solar/Wind Helper
0.184
3141783LANCAST
Solar/Wind Helper
0.123
319010AE1-072 C
Solar/Wind Helper
3.5
316349AD2-085 GEN
Solar/Wind Helper
1.396
316305AF2-043 C
Solar/Wind Helper
0.402
3141813NORNECK
Solar/Wind Helper
0.293
316233AE1-074 FULL
Solar/Wind Helper
0.446
316312AB1-027
Solar/Wind Helper
0.55
313526AB2-022
Solar/Wind Helper
0.431
316223AC1-118
Solar/Wind Helper
0.424
3146486SUNBURY
Solar/Wind Helper
0.274
3146486SUNBURY
Solar/Wind Helper
0.274
316321Z2-027
Solar/Wind Helper
0.414
3145176PASQUOTANK
Solar/Wind Helper
0.168
CBM West 1LTFEXP_CBM-W1->PJM
CBM
48.979
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.858
MECLTFEXP_MEC->PJM
CLTF
7.267
SIGELTFEXP_SIGE->PJM
CLTF
0.218
CPLELTFEXP_CPLE->PJM
CLTF
19.58
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.279
LAGNLTFEXP_LAGN->PJM
CLTF
14.499
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.842
TVALTFEXP_TVA->PJM
CLTF
7.231
NYPJM->LTFIMP_NY
CLTF
2.38
LGEELTFEXP_LGEE->PJM
CLTF
2.637
WECLTFEXP_WEC->PJM
CLTF
1.38
AG2-052LTFEXP_AG2-052->PJM
LTF
0.074
AH1-155LTFEXP_AH1-155->PJM
LTF
0.111

Details for AG1-098 TP-6FINNEYWOOD 230.0 kV Ckt 1 line l/o DVP_P4-2: 211122_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG1-098 TP-6FINNEYWOOD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 211122_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.55 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:856.6
MW Contribution:2.1
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.776
962491AG1-098 GEN
Solar/Wind Harmer
81.061
316322AB2-045
Solar/Wind Harmer
3.419
3146926FARMVIL
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.04
972003AH1-546 GEN
Solar/Wind Harmer
50.704
963171AG1-166 GEN
Solar/Wind Harmer
7.386
971563AH1-280 GEN
Solar/Wind Harmer
7.386
970685AG2-442 GEN
Solar/Wind Harmer
44.081
316237AB2-079_GEN
Solar/Wind Harmer
0.579
970401AG2-262 GEN
Solar/Wind Harmer
0.702
3147043LAWRENC
Adder
0.748
971795AH1-408 GEN
Solar/Wind Harmer
5.817
3144293JTRSVLE
50/50
1.776
3144293JTRSVLE
50/50
1.496
970535AG2-341 GEN
50/50
2.1
971741AH1-377 GEN
Solar/Wind Harmer
131.224
970301AG2-198 GEN
Solar/Wind Harmer
55.111
3146776BUCKING
Solar/Wind Harmer
-0.405
3146776BUCKING
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.065
3147133PAMPLIN
Solar/Wind Harmer
-0.052
958211AF2-115 GEN
Solar/Wind Harmer
9.232
963191AG1-168 GEN
Solar/Wind Harmer
5.539
316034AC1-036 C
Solar/Wind Harmer
0.765
970323AG2-213 GEN
Solar/Wind Harmer
20.566
971775AH1-396 GEN
Solar/Wind Harmer
2.929
313527AB2-043 GEN
Solar/Wind Harmer
3.315
962561AG1-105 GEN
Solar/Wind Harmer
6.878
964791AG1-342 GEN
Solar/Wind Harmer
2.297
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
939181AE1-148 GEN
Solar/Wind Harmer
5.28
3144293JTRSVLE
50/50
1.776
970909AG2-566 GEN
Solar/Wind Harmer
10.464
3146926FARMVIL
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.036
942461AE2-259 GEN
Solar/Wind Harmer
12.382
3147133PAMPLIN
Solar/Wind Harmer
-0.204
971193AH1-056 GEN
Solar/Wind Harmer
40.725
963181AG1-167 GEN
Solar/Wind Harmer
5.539
959311AF2-222 GEN
Solar/Wind Harmer
45.705
970257AG2-171 GEN
Solar/Wind Harmer
15.425
315785AD2-033 C
Solar/Wind Harmer
8.494
964241AG1-285 GEN
Solar/Wind Harmer
21.682
316131AB2-060 GEN
Solar/Wind Harmer
2.357
3147043LAWRENC
Solar/Wind Harmer
-0.006
970285AG2-188 GEN
Solar/Wind Harmer
88.955
971845AH1-439 GEN
Solar/Wind Harmer
54.008
315657AE1-056 GEN
Solar/Wind Harmer
24.435
946301AF1-294 GEN
Solar/Wind Harmer
15.141
961791AG1-021 GEN
Solar/Wind Harmer
7.386
970683AG2-441 GEN
Solar/Wind Harmer
39.358
970681AG2-440 GEN
Solar/Wind Harmer
31.486
3144303KENBRDG
Solar/Wind Harmer
-0.033
971443AH1-215 GEN
Solar/Wind Harmer
7.941
316239AB2-077_GEN
Solar/Wind Harmer
0.579
316238AB2-078_GEN
Solar/Wind Harmer
0.579
316118AC1-105 GEN
Solar/Wind Harmer
0.497
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.057
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.173
MECLTFEXP_MEC->PJM
CLTF
0.029
SIGELTFEXP_SIGE->PJM
CLTF
0.001
CPLELTFEXP_CPLE->PJM
CLTF
0.247
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.466
LAGNLTFEXP_LAGN->PJM
CLTF
0.104
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.452
TVALTFEXP_TVA->PJM
CLTF
0.053
NYPJM->LTFIMP_NY
CLTF
0.076
LGEELTFEXP_LGEE->PJM
CLTF
0.009
WECLTFEXP_WEC->PJM
CLTF
0.003

Details for AG1-098 TP-6FINNEYWOOD 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG1-098 TP-6FINNEYWOOD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 219322_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.55 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:856.6
MW Contribution:2.1
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.776
3144293JTRSVLE
50/50
1.496
970535AG2-341 GEN
50/50
2.1
971741AH1-377 GEN
Solar/Wind Harmer
131.224
970301AG2-198 GEN
Solar/Wind Harmer
55.111
3146776BUCKING
Solar/Wind Harmer
-0.405
3146776BUCKING
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.065
3147133PAMPLIN
Solar/Wind Harmer
-0.052
958211AF2-115 GEN
Solar/Wind Harmer
9.232
963191AG1-168 GEN
Solar/Wind Harmer
5.539
316034AC1-036 C
Solar/Wind Harmer
0.765
3144293JTRSVLE
50/50
1.776
962491AG1-098 GEN
Solar/Wind Harmer
81.061
316322AB2-045
Solar/Wind Harmer
3.419
3146926FARMVIL
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.04
972003AH1-546 GEN
Solar/Wind Harmer
50.704
963171AG1-166 GEN
Solar/Wind Harmer
7.386
971563AH1-280 GEN
Solar/Wind Harmer
7.386
970685AG2-442 GEN
Solar/Wind Harmer
44.081
316237AB2-079_GEN
Solar/Wind Harmer
0.579
970401AG2-262 GEN
Solar/Wind Harmer
0.702
3147043LAWRENC
Adder
0.748
971795AH1-408 GEN
Solar/Wind Harmer
5.817
970285AG2-188 GEN
Solar/Wind Harmer
88.955
971845AH1-439 GEN
Solar/Wind Harmer
54.008
315657AE1-056 GEN
Solar/Wind Harmer
24.435
946301AF1-294 GEN
Solar/Wind Harmer
15.141
961791AG1-021 GEN
Solar/Wind Harmer
7.386
970683AG2-441 GEN
Solar/Wind Harmer
39.358
970681AG2-440 GEN
Solar/Wind Harmer
31.486
3144303KENBRDG
Solar/Wind Harmer
-0.033
971443AH1-215 GEN
Solar/Wind Harmer
7.941
316239AB2-077_GEN
Solar/Wind Harmer
0.579
316238AB2-078_GEN
Solar/Wind Harmer
0.579
316118AC1-105 GEN
Solar/Wind Harmer
0.497
970323AG2-213 GEN
Solar/Wind Harmer
20.566
971775AH1-396 GEN
Solar/Wind Harmer
2.929
313527AB2-043 GEN
Solar/Wind Harmer
3.315
962561AG1-105 GEN
Solar/Wind Harmer
6.878
964791AG1-342 GEN
Solar/Wind Harmer
2.297
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
939181AE1-148 GEN
Solar/Wind Harmer
5.28
3144293JTRSVLE
50/50
1.776
970909AG2-566 GEN
Solar/Wind Harmer
10.464
3146926FARMVIL
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.036
942461AE2-259 GEN
Solar/Wind Harmer
12.382
3147133PAMPLIN
Solar/Wind Harmer
-0.204
971193AH1-056 GEN
Solar/Wind Harmer
40.725
963181AG1-167 GEN
Solar/Wind Harmer
5.539
959311AF2-222 GEN
Solar/Wind Harmer
45.705
970257AG2-171 GEN
Solar/Wind Harmer
15.425
315785AD2-033 C
Solar/Wind Harmer
8.494
964241AG1-285 GEN
Solar/Wind Harmer
21.682
316131AB2-060 GEN
Solar/Wind Harmer
2.357
3147043LAWRENC
Solar/Wind Harmer
-0.006
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.057
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.173
MECLTFEXP_MEC->PJM
CLTF
0.029
SIGELTFEXP_SIGE->PJM
CLTF
0.001
CPLELTFEXP_CPLE->PJM
CLTF
0.247
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.466
LAGNLTFEXP_LAGN->PJM
CLTF
0.104
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.452
TVALTFEXP_TVA->PJM
CLTF
0.053
NYPJM->LTFIMP_NY
CLTF
0.076
LGEELTFEXP_LGEE->PJM
CLTF
0.009
WECLTFEXP_WEC->PJM
CLTF
0.003

Details for AG1-098 TP-6FINNEYWOOD 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG1-098 TP-6FINNEYWOOD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: BREMO B1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:122.55 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:856.6
MW Contribution:2.1
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.776
962491AG1-098 GEN
Solar/Wind Harmer
81.061
316322AB2-045
Solar/Wind Harmer
3.419
3146926FARMVIL
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.04
972003AH1-546 GEN
Solar/Wind Harmer
50.704
963171AG1-166 GEN
Solar/Wind Harmer
7.386
971563AH1-280 GEN
Solar/Wind Harmer
7.386
970685AG2-442 GEN
Solar/Wind Harmer
44.081
316237AB2-079_GEN
Solar/Wind Harmer
0.579
970401AG2-262 GEN
Solar/Wind Harmer
0.702
3147043LAWRENC
Adder
0.748
971795AH1-408 GEN
Solar/Wind Harmer
5.817
970285AG2-188 GEN
Solar/Wind Harmer
88.955
971845AH1-439 GEN
Solar/Wind Harmer
54.008
315657AE1-056 GEN
Solar/Wind Harmer
24.435
946301AF1-294 GEN
Solar/Wind Harmer
15.141
961791AG1-021 GEN
Solar/Wind Harmer
7.386
970683AG2-441 GEN
Solar/Wind Harmer
39.358
970681AG2-440 GEN
Solar/Wind Harmer
31.486
3144303KENBRDG
Solar/Wind Harmer
-0.033
971443AH1-215 GEN
Solar/Wind Harmer
7.941
316239AB2-077_GEN
Solar/Wind Harmer
0.579
316238AB2-078_GEN
Solar/Wind Harmer
0.579
316118AC1-105 GEN
Solar/Wind Harmer
0.497
3144293JTRSVLE
50/50
1.776
970909AG2-566 GEN
Solar/Wind Harmer
10.464
3146926FARMVIL
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.036
942461AE2-259 GEN
Solar/Wind Harmer
12.382
3147133PAMPLIN
Solar/Wind Harmer
-0.204
971193AH1-056 GEN
Solar/Wind Harmer
40.725
963181AG1-167 GEN
Solar/Wind Harmer
5.539
959311AF2-222 GEN
Solar/Wind Harmer
45.705
970257AG2-171 GEN
Solar/Wind Harmer
15.425
315785AD2-033 C
Solar/Wind Harmer
8.494
964241AG1-285 GEN
Solar/Wind Harmer
21.682
316131AB2-060 GEN
Solar/Wind Harmer
2.357
3147043LAWRENC
Solar/Wind Harmer
-0.006
3144293JTRSVLE
50/50
1.776
3144293JTRSVLE
50/50
1.496
970535AG2-341 GEN
50/50
2.1
971741AH1-377 GEN
Solar/Wind Harmer
131.224
970301AG2-198 GEN
Solar/Wind Harmer
55.111
3146776BUCKING
Solar/Wind Harmer
-0.405
3146776BUCKING
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.065
3147133PAMPLIN
Solar/Wind Harmer
-0.052
958211AF2-115 GEN
Solar/Wind Harmer
9.232
963191AG1-168 GEN
Solar/Wind Harmer
5.539
316034AC1-036 C
Solar/Wind Harmer
0.765
970323AG2-213 GEN
Solar/Wind Harmer
20.566
971775AH1-396 GEN
Solar/Wind Harmer
2.929
313527AB2-043 GEN
Solar/Wind Harmer
3.315
962561AG1-105 GEN
Solar/Wind Harmer
6.878
964791AG1-342 GEN
Solar/Wind Harmer
2.297
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
939181AE1-148 GEN
Solar/Wind Harmer
5.28
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.057
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.173
MECLTFEXP_MEC->PJM
CLTF
0.029
SIGELTFEXP_SIGE->PJM
CLTF
0.001
CPLELTFEXP_CPLE->PJM
CLTF
0.247
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.466
LAGNLTFEXP_LAGN->PJM
CLTF
0.104
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.452
TVALTFEXP_TVA->PJM
CLTF
0.053
NYPJM->LTFIMP_NY
CLTF
0.076
LGEELTFEXP_LGEE->PJM
CLTF
0.009
WECLTFEXP_WEC->PJM
CLTF
0.003

Details for AG1-098 TP-6FINNEYWOOD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 298_SRT-A-4


Base Case Flowgate

Area:DVP
Facility Description:
AG1-098 TP-6FINNEYWOOD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 298_SRT-A-4
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.11 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:635.03
MW Contribution:2.1
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.129
3151621KERR 5
50/50
0.129
3151631KERR 6
50/50
0.129
3151641KERR 7
50/50
0.129
970285AG2-188 GEN
Solar/Wind Harmer
71.589
971845AH1-439 GEN
Solar/Wind Harmer
41.023
315657AE1-056 GEN
Solar/Wind Harmer
20.004
946301AF1-294 GEN
Solar/Wind Harmer
10.379
961791AG1-021 GEN
Solar/Wind Harmer
5.049
970683AG2-441 GEN
Solar/Wind Harmer
29.897
970681AG2-440 GEN
Solar/Wind Harmer
23.918
3144303KENBRDG
Solar/Wind Harmer
0.293
971443AH1-215 GEN
Solar/Wind Harmer
6.032
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.166
3144293JTRSVLE
50/50
1.777
3147043LAWRENC
50/50
0.794
3151601KERR 3
50/50
0.129
3151581KERR 1
50/50
0.046
962491AG1-098 GEN
Solar/Wind Harmer
61.57
316322AB2-045
Solar/Wind Harmer
0.007
3146926FARMVIL
Solar/Wind Harmer
0.543
3146776BUCKING
Solar/Wind Harmer
0.362
972003AH1-546 GEN
Solar/Wind Harmer
38.449
963171AG1-166 GEN
Solar/Wind Harmer
2.805
971563AH1-280 GEN
Solar/Wind Harmer
5.61
970685AG2-442 GEN
Solar/Wind Harmer
33.485
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970401AG2-262 GEN
Solar/Wind Harmer
0.562
971795AH1-408 GEN
Solar/Wind Harmer
4.608
3144293JTRSVLE
50/50
1.777
3144293JTRSVLE
50/50
1.496
970535AG2-341 GEN
50/50
2.101
971741AH1-377 GEN
Solar/Wind Harmer
99.672
970301AG2-198 GEN
Solar/Wind Harmer
41.86
3146776BUCKING
Solar/Wind Harmer
3.617
3146776BUCKING
Solar/Wind Harmer
0.293
3147133PAMPLIN
Solar/Wind Harmer
0.58
3147133PAMPLIN
Solar/Wind Harmer
0.463
958211AF2-115 GEN
Solar/Wind Harmer
6.312
963191AG1-168 GEN
Solar/Wind Harmer
2.104
316034AC1-036 C
Solar/Wind Harmer
0.027
970323AG2-213 GEN
Solar/Wind Harmer
15.623
971775AH1-396 GEN
Solar/Wind Harmer
0.586
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
5.227
964791AG1-342 GEN
Solar/Wind Harmer
1.839
3146843MT LREL
Solar/Wind Harmer
0.095
3146843MT LREL
Solar/Wind Harmer
0.095
939181AE1-148 GEN
Solar/Wind Harmer
4.014
3144293JTRSVLE
50/50
1.777
3151591KERR 2
50/50
0.129
970909AG2-566 GEN
Solar/Wind Harmer
10.465
3146926FARMVIL
Solar/Wind Harmer
0.543
3146776BUCKING
Solar/Wind Harmer
0.326
942461AE2-259 GEN
Solar/Wind Harmer
-0.004
3147133PAMPLIN
Solar/Wind Harmer
1.82
971193AH1-056 GEN
Solar/Wind Harmer
35.317
963181AG1-167 GEN
Solar/Wind Harmer
2.104
959311AF2-222 GEN
Solar/Wind Harmer
34.65
970257AG2-171 GEN
Solar/Wind Harmer
11.717
315785AD2-033 C
Solar/Wind Harmer
2.712
964241AG1-285 GEN
Solar/Wind Harmer
16.472
316131AB2-060 GEN
Solar/Wind Harmer
0.612
3147043LAWRENC
Solar/Wind Harmer
0.05
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.046
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.172
MECLTFEXP_MEC->PJM
CLTF
0.028
SIGELTFEXP_SIGE->PJM
CLTF
0.001
CPLELTFEXP_CPLE->PJM
CLTF
0.25
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.46
LAGNLTFEXP_LAGN->PJM
CLTF
0.104
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.457
TVALTFEXP_TVA->PJM
CLTF
0.053
NYPJM->LTFIMP_NY
CLTF
0.075
LGEELTFEXP_LGEE->PJM
CLTF
0.008
WECLTFEXP_WEC->PJM
CLTF
0.003

Details for AG1-098 TP-6FINNEYWOOD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 298_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
AG1-098 TP-6FINNEYWOOD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 298_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.38 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:596.58
MW Contribution:2.1
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.777
3147043LAWRENC
50/50
0.796
3151601KERR 3
50/50
0.129
3151581KERR 1
50/50
0.046
962491AG1-098 GEN
Solar/Wind Harmer
61.58
3146926FARMVIL
Solar/Wind Harmer
0.543
963171AG1-166 GEN
Solar/Wind Harmer
2.806
971563AH1-280 GEN
Solar/Wind Harmer
5.612
970685AG2-442 GEN
Solar/Wind Harmer
33.497
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970401AG2-262 GEN
Solar/Wind Harmer
0.563
971795AH1-408 GEN
Solar/Wind Harmer
4.619
3151611KERR 4
50/50
0.129
3151621KERR 5
50/50
0.129
3151631KERR 6
50/50
0.129
3151641KERR 7
50/50
0.129
970285AG2-188 GEN
Solar/Wind Harmer
71.602
971845AH1-439 GEN
Solar/Wind Harmer
41.03
315657AE1-056 GEN
Solar/Wind Harmer
20.01
946301AF1-294 GEN
Solar/Wind Harmer
10.382
961791AG1-021 GEN
Solar/Wind Harmer
5.051
970683AG2-441 GEN
Solar/Wind Harmer
29.908
970681AG2-440 GEN
Solar/Wind Harmer
23.927
3144303KENBRDG
Solar/Wind Harmer
0.293
971443AH1-215 GEN
Solar/Wind Harmer
6.035
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.166
3144293JTRSVLE
50/50
1.777
3144293JTRSVLE
50/50
1.497
970535AG2-341 GEN
50/50
2.104
971741AH1-377 GEN
Solar/Wind Harmer
99.688
970301AG2-198 GEN
Solar/Wind Harmer
41.867
3147133PAMPLIN
Solar/Wind Harmer
0.58
3147133PAMPLIN
Solar/Wind Harmer
0.464
958211AF2-115 GEN
Solar/Wind Harmer
6.314
963191AG1-168 GEN
Solar/Wind Harmer
2.105
316034AC1-036 C
Solar/Wind Harmer
0.027
970323AG2-213 GEN
Solar/Wind Harmer
15.63
971775AH1-396 GEN
Solar/Wind Harmer
0.586
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
5.235
964791AG1-342 GEN
Solar/Wind Harmer
1.842
3146843MT LREL
Solar/Wind Harmer
0.095
3146843MT LREL
Solar/Wind Harmer
0.095
939181AE1-148 GEN
Solar/Wind Harmer
4.022
3144293JTRSVLE
50/50
1.777
3151591KERR 2
50/50
0.129
970909AG2-566 GEN
Solar/Wind Harmer
10.467
3146926FARMVIL
Solar/Wind Harmer
0.543
942461AE2-259 GEN
Solar/Wind Harmer
-0.004
3147133PAMPLIN
Solar/Wind Harmer
1.82
971193AH1-056 GEN
Solar/Wind Harmer
35.327
963181AG1-167 GEN
Solar/Wind Harmer
2.105
959311AF2-222 GEN
Solar/Wind Harmer
34.665
970257AG2-171 GEN
Solar/Wind Harmer
11.723
315785AD2-033 C
Solar/Wind Harmer
2.714
964241AG1-285 GEN
Solar/Wind Harmer
16.483
316131AB2-060 GEN
Solar/Wind Harmer
0.612
3147043LAWRENC
Solar/Wind Harmer
0.05
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.233
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.22
MECLTFEXP_MEC->PJM
CLTF
0.049
SIGELTFEXP_SIGE->PJM
CLTF
0.001
CPLELTFEXP_CPLE->PJM
CLTF
0.264
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.632
LAGNLTFEXP_LAGN->PJM
CLTF
0.13
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.495
TVALTFEXP_TVA->PJM
CLTF
0.066
NYPJM->LTFIMP_NY
CLTF
0.067
LGEELTFEXP_LGEE->PJM
CLTF
0.017
WECLTFEXP_WEC->PJM
CLTF
0.008

Details for AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.76 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:673.04
MW Contribution:1.99
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
971967AH1-528 GEN
Solar/Wind Harmer
55.717
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
316118AC1-105 GEN
Solar/Wind Harmer
0.376
970865AG2-541 GEN
Solar/Wind Harmer
4.593
316123AC1-075 GEN
Solar/Wind Harmer
0.152
970165AG2-112 GEN
Solar/Wind Harmer
0.903
970163AG2-111 GEN
Solar/Wind Harmer
0.862
970831AG2-522 GEN
Solar/Wind Harmer
4.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3152661PLYWOOD A
50/50
0.346
970535AG2-341 GEN
50/50
1.993
970933AG2-581 GEN
Solar/Wind Harmer
27.859
970099AG2-077 GEN
Solar/Wind Harmer
36.299
939181AE1-148 GEN
Solar/Wind Harmer
6.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.689
316222AC1-221 GEN
Solar/Wind Harmer
0.447
942751AE2-291 GEN
Solar/Wind Harmer
5.336
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
971629AH1-314 GEN
50/50
5.006
962491AG1-098 GEN
Solar/Wind Harmer
22.331
315693AD1-088 GEN
Solar/Wind Harmer
18.25
957481AF2-042 GEN
Solar/Wind Harmer
90.747
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.071
316129AC1-054 GEN
Solar/Wind Harmer
0.427
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
316478AD1-087 GEN
Solar/Wind Harmer
1.094
316486AD2-202 GEN
Solar/Wind Harmer
0.321
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.01
971683AH1-343 GEN
Solar/Wind Harmer
5.256
316283AC2-100 C
Solar/Wind Harmer
0.206
316131AB2-060 GEN
Solar/Wind Harmer
0.208
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.2 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:658.38
MW Contribution:1.99
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
316118AC1-105 GEN
Solar/Wind Harmer
0.376
970865AG2-541 GEN
Solar/Wind Harmer
4.593
316123AC1-075 GEN
Solar/Wind Harmer
0.152
970165AG2-112 GEN
Solar/Wind Harmer
0.903
970163AG2-111 GEN
Solar/Wind Harmer
0.862
970831AG2-522 GEN
Solar/Wind Harmer
4.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
316478AD1-087 GEN
Solar/Wind Harmer
1.094
316486AD2-202 GEN
Solar/Wind Harmer
0.321
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.01
971683AH1-343 GEN
Solar/Wind Harmer
5.256
316283AC2-100 C
Solar/Wind Harmer
0.206
316131AB2-060 GEN
Solar/Wind Harmer
0.208
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
971629AH1-314 GEN
50/50
5.006
962491AG1-098 GEN
Solar/Wind Harmer
22.331
315693AD1-088 GEN
Solar/Wind Harmer
18.25
957481AF2-042 GEN
Solar/Wind Harmer
90.747
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.071
316129AC1-054 GEN
Solar/Wind Harmer
0.427
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
3152661PLYWOOD A
50/50
0.346
970535AG2-341 GEN
50/50
1.993
970099AG2-077 GEN
Solar/Wind Harmer
36.299
939181AE1-148 GEN
Solar/Wind Harmer
6.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.689
316222AC1-221 GEN
Solar/Wind Harmer
0.447
942751AE2-291 GEN
Solar/Wind Harmer
5.336
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.07 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:797.37
MW Contribution:2.0
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
6.74
3151601KERR 3
50/50
0.302
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.44
315693AD1-088 GEN
Solar/Wind Harmer
21.388
957481AF2-042 GEN
Solar/Wind Harmer
119.681
315687AD1-152 GEN
Solar/Wind Harmer
3.524
316003AC1-222 GEN
Solar/Wind Harmer
1.683
970401AG2-262 GEN
Solar/Wind Harmer
0.932
971065AG2-659 GEN
Solar/Wind Harmer
6.697
316129AC1-054 GEN
Solar/Wind Harmer
1.121
316237AB2-079_GEN
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Helper
0.44
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
1.003
3152661PLYWOOD A
50/50
0.348
970535AG2-341 GEN
50/50
2.001
970933AG2-581 GEN
Solar/Wind Harmer
36.739
970099AG2-077 GEN
Solar/Wind Harmer
47.872
939181AE1-148 GEN
Solar/Wind Harmer
8.421
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.05
962561AG1-105 GEN
Solar/Wind Harmer
7.525
316222AC1-221 GEN
Solar/Wind Harmer
1.236
942751AE2-291 GEN
Solar/Wind Harmer
7.063
313527AB2-043 GEN
Solar/Wind Harmer
1.361
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.338
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.919
970413AG2-270 GEN
50/50
29.414
3151591KERR 2
50/50
0.302
316478AD1-087 GEN
Solar/Wind Harmer
3.055
316486AD2-202 GEN
Solar/Wind Harmer
0.895
316248AF1-058 C
Solar/Wind Harmer
0.559
960061AF2-297 GEN
Solar/Wind Harmer
9.268
971683AH1-343 GEN
Solar/Wind Harmer
6.951
316283AC2-100 C
Solar/Wind Harmer
1.124
316131AB2-060 GEN
Solar/Wind Harmer
0.808
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.542
3147133PAMPLIN
Solar/Wind Helper
1.062
316313AB2-026
Solar/Wind Helper
0.243
316258AE1-075 C
Solar/Wind Helper
0.219
316405AF2-144 C
Solar/Wind Helper
0.182
3151541CLOVER2
50/50
6.708
3151611KERR 4
50/50
0.302
3151621KERR 5
50/50
0.302
3151631KERR 6
50/50
0.302
3151641KERR 7
50/50
0.302
971967AH1-528 GEN
Solar/Wind Harmer
73.672
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.131
970865AG2-541 GEN
Solar/Wind Harmer
6.075
316123AC1-075 GEN
Solar/Wind Harmer
1.358
970165AG2-112 GEN
Solar/Wind Harmer
1.195
970163AG2-111 GEN
Solar/Wind Harmer
1.14
970831AG2-522 GEN
Solar/Wind Harmer
6.069
316239AB2-077_GEN
Solar/Wind Harmer
0.274
316238AB2-078_GEN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Harmer
1.371
270457AD2-023 GEN
Solar/Wind Harmer
0.695
270494AE1-108_GEN
Solar/Wind Helper
2.769
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.6
MECLTFEXP_MEC->PJM
CLTF
1.297
SIGELTFEXP_SIGE->PJM
CLTF
0.038
CPLELTFEXP_CPLE->PJM
CLTF
4.232
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.165
LAGNLTFEXP_LAGN->PJM
CLTF
2.703
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.92
TVALTFEXP_TVA->PJM
CLTF
1.347
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.461
WECLTFEXP_WEC->PJM
CLTF
0.241

Details for AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.03 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:797.08
MW Contribution:2.0
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
6.74
3151601KERR 3
50/50
0.302
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.44
315693AD1-088 GEN
Solar/Wind Harmer
21.388
957481AF2-042 GEN
Solar/Wind Harmer
119.681
315687AD1-152 GEN
Solar/Wind Harmer
3.524
316003AC1-222 GEN
Solar/Wind Harmer
1.683
970401AG2-262 GEN
Solar/Wind Harmer
0.932
971065AG2-659 GEN
Solar/Wind Harmer
6.697
316129AC1-054 GEN
Solar/Wind Harmer
1.121
316237AB2-079_GEN
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Helper
0.44
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
1.003
3152661PLYWOOD A
50/50
0.348
970535AG2-341 GEN
50/50
2.001
970933AG2-581 GEN
Solar/Wind Harmer
36.739
970099AG2-077 GEN
Solar/Wind Harmer
47.872
939181AE1-148 GEN
Solar/Wind Harmer
8.421
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.05
962561AG1-105 GEN
Solar/Wind Harmer
7.525
316222AC1-221 GEN
Solar/Wind Harmer
1.236
942751AE2-291 GEN
Solar/Wind Harmer
7.063
313527AB2-043 GEN
Solar/Wind Harmer
1.361
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.338
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.919
970413AG2-270 GEN
50/50
29.414
3151591KERR 2
50/50
0.302
316478AD1-087 GEN
Solar/Wind Harmer
3.055
316486AD2-202 GEN
Solar/Wind Harmer
0.895
316248AF1-058 C
Solar/Wind Harmer
0.559
960061AF2-297 GEN
Solar/Wind Harmer
9.268
971683AH1-343 GEN
Solar/Wind Harmer
6.951
316283AC2-100 C
Solar/Wind Harmer
1.124
316131AB2-060 GEN
Solar/Wind Harmer
0.808
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.542
3147133PAMPLIN
Solar/Wind Helper
1.062
316313AB2-026
Solar/Wind Helper
0.243
316258AE1-075 C
Solar/Wind Helper
0.219
316405AF2-144 C
Solar/Wind Helper
0.182
3151541CLOVER2
50/50
6.708
3151611KERR 4
50/50
0.302
3151621KERR 5
50/50
0.302
3151631KERR 6
50/50
0.302
3151641KERR 7
50/50
0.302
971967AH1-528 GEN
Solar/Wind Harmer
73.672
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.131
970865AG2-541 GEN
Solar/Wind Harmer
6.075
316123AC1-075 GEN
Solar/Wind Harmer
1.358
970165AG2-112 GEN
Solar/Wind Harmer
1.195
970163AG2-111 GEN
Solar/Wind Harmer
1.14
970831AG2-522 GEN
Solar/Wind Harmer
6.069
316239AB2-077_GEN
Solar/Wind Harmer
0.274
316238AB2-078_GEN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Harmer
1.371
270457AD2-023 GEN
Solar/Wind Harmer
0.695
270494AE1-108_GEN
Solar/Wind Helper
2.769
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.6
MECLTFEXP_MEC->PJM
CLTF
1.297
SIGELTFEXP_SIGE->PJM
CLTF
0.038
CPLELTFEXP_CPLE->PJM
CLTF
4.232
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.165
LAGNLTFEXP_LAGN->PJM
CLTF
2.703
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.92
TVALTFEXP_TVA->PJM
CLTF
1.347
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.461
WECLTFEXP_WEC->PJM
CLTF
0.241

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:211.67 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1447.79
MW Contribution:4.63
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.536
3151531CLOVER1
50/50
6.868
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.479
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.387
971563AH1-280 GEN
Solar/Wind Harmer
6.387
970685AG2-442 GEN
Solar/Wind Harmer
41.098
962491AG1-098 GEN
Solar/Wind Harmer
28.527
315693AD1-088 GEN
Solar/Wind Harmer
20.89
957481AF2-042 GEN
Solar/Wind Harmer
119.73
316237AB2-079_GEN
Solar/Wind Harmer
0.97
315687AD1-152 GEN
Solar/Wind Harmer
3.722
970401AG2-262 GEN
Solar/Wind Harmer
1.828
316003AC1-222 GEN
Solar/Wind Harmer
2.23
971065AG2-659 GEN
Solar/Wind Harmer
10.784
316129AC1-054 GEN
Solar/Wind Harmer
1.809
971795AH1-408 GEN
Solar/Wind Harmer
11.382
960081AF2-299 GEN
Solar/Wind Harmer
1.187
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.663
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.965
316049AB1-081 GEN
Solar/Wind Harmer
0.772
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.715
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
970223AG2-152 GEN
Solar/Wind Harmer
5.79
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.192
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.414
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.314
3144293JTRSVLE
50/50
1.536
970413AG2-270 GEN
50/50
29.97
3151591KERR 2
50/50
0.482
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.339
970909AG2-566 GEN
Solar/Wind Harmer
5.578
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.735
963181AG1-167 GEN
Solar/Wind Harmer
4.79
959311AF2-222 GEN
Solar/Wind Harmer
45.765
970257AG2-171 GEN
Solar/Wind Harmer
15.97
315785AD2-033 C
Solar/Wind Harmer
9.259
964241AG1-285 GEN
Solar/Wind Harmer
28.316
316478AD1-087 GEN
Solar/Wind Harmer
3.115
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.609
316248AF1-058 C
Solar/Wind Harmer
0.741
960061AF2-297 GEN
Solar/Wind Harmer
12.289
971683AH1-343 GEN
Solar/Wind Harmer
9.199
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.303
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.775
316210AC1-098 GEN
Solar/Wind Harmer
1.194
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.767
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.393
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.414
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.317
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
3144293JTRSVLE
50/50
1.536
3144293JTRSVLE
50/50
1.294
970535AG2-341 GEN
50/50
4.631
3152661PLYWOOD A
50/50
0.509
970301AG2-198 GEN
Solar/Wind Harmer
29.375
971741AH1-377 GEN
Solar/Wind Harmer
63.77
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.984
963191AG1-168 GEN
Solar/Wind Harmer
4.79
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.293
971775AH1-396 GEN
Solar/Wind Harmer
3.032
970933AG2-581 GEN
Solar/Wind Harmer
36.564
970099AG2-077 GEN
Solar/Wind Harmer
47.892
313527AB2-043 GEN
Solar/Wind Harmer
5.323
962561AG1-105 GEN
Solar/Wind Harmer
16.163
964791AG1-342 GEN
Solar/Wind Harmer
5.983
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.395
942751AE2-291 GEN
Solar/Wind Harmer
9.282
316222AC1-221 GEN
Solar/Wind Harmer
1.431
316181AB2-040 GEN
Solar/Wind Harmer
1.454
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.157
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.182
3145783HORNRTN
Solar/Wind Harmer
0.946
3145783HORNRTN
Solar/Wind Harmer
0.296
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.956
316274AC1-208 GEN
Solar/Wind Harmer
0.891
316263AC1-034 GEN
Solar/Wind Harmer
3.354
961601AG1-000A GEN
Solar/Wind Harmer
2.733
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.045
316197AC1-042 GEN
Solar/Wind Harmer
0.792
942671AE2-283 GEN
Solar/Wind Harmer
2.132
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.531
3151541CLOVER2
50/50
6.835
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
970285AG2-188 GEN
Solar/Wind Harmer
71.83
315657AE1-056 GEN
Solar/Wind Harmer
20.241
946301AF1-294 GEN
Solar/Wind Harmer
13.094
961791AG1-021 GEN
Solar/Wind Harmer
6.387
970683AG2-441 GEN
Solar/Wind Harmer
36.695
970681AG2-440 GEN
Solar/Wind Harmer
29.356
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.31
971967AH1-528 GEN
Solar/Wind Harmer
73.321
316239AB2-077_GEN
Solar/Wind Harmer
0.97
316238AB2-078_GEN
Solar/Wind Harmer
0.97
316118AC1-105 GEN
Solar/Wind Harmer
1.807
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.03
970831AG2-522 GEN
Solar/Wind Harmer
9.822
316123AC1-075 GEN
Solar/Wind Harmer
1.789
970165AG2-112 GEN
Solar/Wind Harmer
1.575
970163AG2-111 GEN
Solar/Wind Harmer
1.503
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.493
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.635
270457AD2-023 GEN
Solar/Wind Harmer
0.829
315607AA1-063A GEN
Solar/Wind Harmer
0.882
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.411
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.563
270494AE1-108_GEN
Solar/Wind Helper
3.665
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.51
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.435
MECLTFEXP_MEC->PJM
CLTF
1.488
SIGELTFEXP_SIGE->PJM
CLTF
0.044
CPLELTFEXP_CPLE->PJM
CLTF
5.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.616
LAGNLTFEXP_LAGN->PJM
CLTF
3.212
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.896
TVALTFEXP_TVA->PJM
CLTF
1.599
NYPJM->LTFIMP_NY
CLTF
0.52
LGEELTFEXP_LGEE->PJM
CLTF
0.521
WECLTFEXP_WEC->PJM
CLTF
0.271

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:211.61 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1447.4
MW Contribution:4.63
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.536
3151531CLOVER1
50/50
6.868
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.479
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.387
971563AH1-280 GEN
Solar/Wind Harmer
6.387
970685AG2-442 GEN
Solar/Wind Harmer
41.098
962491AG1-098 GEN
Solar/Wind Harmer
28.527
315693AD1-088 GEN
Solar/Wind Harmer
20.89
957481AF2-042 GEN
Solar/Wind Harmer
119.73
316237AB2-079_GEN
Solar/Wind Harmer
0.97
315687AD1-152 GEN
Solar/Wind Harmer
3.722
970401AG2-262 GEN
Solar/Wind Harmer
1.828
316003AC1-222 GEN
Solar/Wind Harmer
2.23
971065AG2-659 GEN
Solar/Wind Harmer
10.784
316129AC1-054 GEN
Solar/Wind Harmer
1.809
971795AH1-408 GEN
Solar/Wind Harmer
11.382
960081AF2-299 GEN
Solar/Wind Harmer
1.187
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.663
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.965
316049AB1-081 GEN
Solar/Wind Harmer
0.772
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.715
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
970223AG2-152 GEN
Solar/Wind Harmer
5.79
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.192
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.414
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.314
3144293JTRSVLE
50/50
1.536
970413AG2-270 GEN
50/50
29.97
3151591KERR 2
50/50
0.482
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.339
970909AG2-566 GEN
Solar/Wind Harmer
5.578
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.735
963181AG1-167 GEN
Solar/Wind Harmer
4.79
959311AF2-222 GEN
Solar/Wind Harmer
45.765
970257AG2-171 GEN
Solar/Wind Harmer
15.97
315785AD2-033 C
Solar/Wind Harmer
9.259
964241AG1-285 GEN
Solar/Wind Harmer
28.316
316478AD1-087 GEN
Solar/Wind Harmer
3.115
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.609
316248AF1-058 C
Solar/Wind Harmer
0.741
960061AF2-297 GEN
Solar/Wind Harmer
12.289
971683AH1-343 GEN
Solar/Wind Harmer
9.199
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.303
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.775
316210AC1-098 GEN
Solar/Wind Harmer
1.194
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.767
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.393
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.414
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.317
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
3144293JTRSVLE
50/50
1.536
3144293JTRSVLE
50/50
1.294
970535AG2-341 GEN
50/50
4.631
3152661PLYWOOD A
50/50
0.509
970301AG2-198 GEN
Solar/Wind Harmer
29.375
971741AH1-377 GEN
Solar/Wind Harmer
63.77
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.984
963191AG1-168 GEN
Solar/Wind Harmer
4.79
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.293
971775AH1-396 GEN
Solar/Wind Harmer
3.032
970933AG2-581 GEN
Solar/Wind Harmer
36.564
970099AG2-077 GEN
Solar/Wind Harmer
47.892
313527AB2-043 GEN
Solar/Wind Harmer
5.323
962561AG1-105 GEN
Solar/Wind Harmer
16.163
964791AG1-342 GEN
Solar/Wind Harmer
5.983
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.395
942751AE2-291 GEN
Solar/Wind Harmer
9.282
316222AC1-221 GEN
Solar/Wind Harmer
1.431
316181AB2-040 GEN
Solar/Wind Harmer
1.454
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.157
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.182
3145783HORNRTN
Solar/Wind Harmer
0.946
3145783HORNRTN
Solar/Wind Harmer
0.296
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.956
316274AC1-208 GEN
Solar/Wind Harmer
0.891
316263AC1-034 GEN
Solar/Wind Harmer
3.354
961601AG1-000A GEN
Solar/Wind Harmer
2.733
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.045
316197AC1-042 GEN
Solar/Wind Harmer
0.792
942671AE2-283 GEN
Solar/Wind Harmer
2.132
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.531
3151541CLOVER2
50/50
6.835
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
970285AG2-188 GEN
Solar/Wind Harmer
71.83
315657AE1-056 GEN
Solar/Wind Harmer
20.241
946301AF1-294 GEN
Solar/Wind Harmer
13.094
961791AG1-021 GEN
Solar/Wind Harmer
6.387
970683AG2-441 GEN
Solar/Wind Harmer
36.695
970681AG2-440 GEN
Solar/Wind Harmer
29.356
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.31
971967AH1-528 GEN
Solar/Wind Harmer
73.321
316239AB2-077_GEN
Solar/Wind Harmer
0.97
316238AB2-078_GEN
Solar/Wind Harmer
0.97
316118AC1-105 GEN
Solar/Wind Harmer
1.807
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.03
970831AG2-522 GEN
Solar/Wind Harmer
9.822
316123AC1-075 GEN
Solar/Wind Harmer
1.789
970165AG2-112 GEN
Solar/Wind Harmer
1.575
970163AG2-111 GEN
Solar/Wind Harmer
1.503
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.493
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.635
270457AD2-023 GEN
Solar/Wind Harmer
0.829
315607AA1-063A GEN
Solar/Wind Harmer
0.882
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.411
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.563
270494AE1-108_GEN
Solar/Wind Helper
3.665
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.51
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.435
MECLTFEXP_MEC->PJM
CLTF
1.488
SIGELTFEXP_SIGE->PJM
CLTF
0.044
CPLELTFEXP_CPLE->PJM
CLTF
5.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.616
LAGNLTFEXP_LAGN->PJM
CLTF
3.212
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.896
TVALTFEXP_TVA->PJM
CLTF
1.599
NYPJM->LTFIMP_NY
CLTF
0.52
LGEELTFEXP_LGEE->PJM
CLTF
0.521
WECLTFEXP_WEC->PJM
CLTF
0.271

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:207.99 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1422.62
MW Contribution:4.62
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
970285AG2-188 GEN
Solar/Wind Harmer
71.826
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
971967AH1-528 GEN
Solar/Wind Harmer
73.183
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970933AG2-581 GEN
Solar/Wind Harmer
36.495
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:206.17 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:1153.12
MW Contribution:4.62
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.213
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.1
970301AG2-198 GEN
Solar/Wind Harmer
22.295
971741AH1-377 GEN
Solar/Wind Harmer
48.392
3147133PAMPLIN
Solar/Wind Harmer
0.48
3147133PAMPLIN
Solar/Wind Harmer
0.384
958211AF2-115 GEN
Solar/Wind Harmer
5.453
963191AG1-168 GEN
Solar/Wind Harmer
1.818
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.154
971775AH1-396 GEN
Solar/Wind Harmer
0.606
970933AG2-581 GEN
Solar/Wind Harmer
27.718
970099AG2-077 GEN
Solar/Wind Harmer
36.303
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.244
964791AG1-342 GEN
Solar/Wind Harmer
4.773
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.665
942751AE2-291 GEN
Solar/Wind Harmer
7.016
316222AC1-221 GEN
Solar/Wind Harmer
0.517
316181AB2-040 GEN
Solar/Wind Harmer
0.135
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.992
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.575
3145783HORNRTN
Solar/Wind Harmer
1.26
3145783HORNRTN
Solar/Wind Harmer
0.394
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.38
316263AC1-034 GEN
Solar/Wind Harmer
2.393
961601AG1-000A GEN
Solar/Wind Harmer
1.088
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.132
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.414
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.232
963181AG1-167 GEN
Solar/Wind Harmer
1.818
959311AF2-222 GEN
Solar/Wind Harmer
34.653
970257AG2-171 GEN
Solar/Wind Harmer
12.116
315785AD2-033 C
Solar/Wind Harmer
2.953
964241AG1-285 GEN
Solar/Wind Harmer
21.475
316478AD1-087 GEN
Solar/Wind Harmer
1.115
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.935
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.299
971683AH1-343 GEN
Solar/Wind Harmer
6.959
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.287
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.626
3146233WITAKRS
Solar/Wind Harmer
0.329
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.062
961601AG1-000A GEN
Solar/Wind Harmer
4.35
315724AD1-057 GEN
Solar/Wind Harmer
0.227
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.818
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.104
970285AG2-188 GEN
Solar/Wind Harmer
57.798
315657AE1-056 GEN
Solar/Wind Harmer
16.558
946301AF1-294 GEN
Solar/Wind Harmer
8.968
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.97
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
963171AG1-166 GEN
Solar/Wind Harmer
2.424
971563AH1-280 GEN
Solar/Wind Harmer
4.847
970685AG2-442 GEN
Solar/Wind Harmer
31.186
962491AG1-098 GEN
Solar/Wind Harmer
21.632
315693AD1-088 GEN
Solar/Wind Harmer
17.82
957481AF2-042 GEN
Solar/Wind Harmer
90.757
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.458
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.171
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
9.004
960081AF2-299 GEN
Solar/Wind Harmer
0.903
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.349
3146233WITAKRS
Solar/Wind Harmer
0.261
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.051
316359AB2-059 GEN
Solar/Wind Harmer
0.226
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.062
315722AD1-056 GEN
Solar/Wind Harmer
0.382
3145796HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.068
962571AG1-106 GEN
Solar/Wind Harmer
0.836
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.253
970223AG2-152 GEN
Solar/Wind Harmer
3.997
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.043
941801AE2-185 GEN
Solar/Wind Harmer
1.818
3145823KELFORD
Solar/Wind Harmer
0.056
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
961791AG1-021 GEN
Solar/Wind Harmer
4.363
970683AG2-441 GEN
Solar/Wind Harmer
27.844
970681AG2-440 GEN
Solar/Wind Harmer
22.275
3144303KENBRDG
Solar/Wind Harmer
0.303
971443AH1-215 GEN
Solar/Wind Harmer
6.304
971967AH1-528 GEN
Solar/Wind Harmer
55.434
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.602
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.073
970831AG2-522 GEN
Solar/Wind Harmer
7.443
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.191
970163AG2-111 GEN
Solar/Wind Harmer
1.136
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.368
315607AA1-063A GEN
Solar/Wind Harmer
0.159
3146043SEABORD
Solar/Wind Harmer
0.076
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.25
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.462
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.252
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:203.59 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:1138.68
MW Contribution:4.62
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.213
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.1
970301AG2-198 GEN
Solar/Wind Harmer
22.295
971741AH1-377 GEN
Solar/Wind Harmer
48.392
3147133PAMPLIN
Solar/Wind Harmer
0.48
3147133PAMPLIN
Solar/Wind Harmer
0.384
958211AF2-115 GEN
Solar/Wind Harmer
5.453
963191AG1-168 GEN
Solar/Wind Harmer
1.818
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.154
971775AH1-396 GEN
Solar/Wind Harmer
0.606
970099AG2-077 GEN
Solar/Wind Harmer
36.303
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.244
964791AG1-342 GEN
Solar/Wind Harmer
4.773
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.665
942751AE2-291 GEN
Solar/Wind Harmer
7.016
316222AC1-221 GEN
Solar/Wind Harmer
0.517
316181AB2-040 GEN
Solar/Wind Harmer
0.135
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.232
963181AG1-167 GEN
Solar/Wind Harmer
1.818
959311AF2-222 GEN
Solar/Wind Harmer
34.653
970257AG2-171 GEN
Solar/Wind Harmer
12.116
315785AD2-033 C
Solar/Wind Harmer
2.953
964241AG1-285 GEN
Solar/Wind Harmer
21.475
316478AD1-087 GEN
Solar/Wind Harmer
1.115
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.935
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.97
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
963171AG1-166 GEN
Solar/Wind Harmer
2.424
971563AH1-280 GEN
Solar/Wind Harmer
4.847
970685AG2-442 GEN
Solar/Wind Harmer
31.186
962491AG1-098 GEN
Solar/Wind Harmer
21.632
315693AD1-088 GEN
Solar/Wind Harmer
17.82
957481AF2-042 GEN
Solar/Wind Harmer
90.757
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.458
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.171
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
9.004
960081AF2-299 GEN
Solar/Wind Harmer
0.903
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.349
3146233WITAKRS
Solar/Wind Harmer
0.261
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.051
316359AB2-059 GEN
Solar/Wind Harmer
0.226
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.062
315722AD1-056 GEN
Solar/Wind Harmer
0.382
3145796HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.068
962571AG1-106 GEN
Solar/Wind Harmer
0.836
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.253
970223AG2-152 GEN
Solar/Wind Harmer
3.997
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.043
941801AE2-185 GEN
Solar/Wind Harmer
1.818
3145823KELFORD
Solar/Wind Harmer
0.056
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.299
971683AH1-343 GEN
Solar/Wind Harmer
6.959
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.287
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.626
3146233WITAKRS
Solar/Wind Harmer
0.329
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.104
970285AG2-188 GEN
Solar/Wind Harmer
57.798
315657AE1-056 GEN
Solar/Wind Harmer
16.558
946301AF1-294 GEN
Solar/Wind Harmer
8.968
961791AG1-021 GEN
Solar/Wind Harmer
4.363
970683AG2-441 GEN
Solar/Wind Harmer
27.844
970681AG2-440 GEN
Solar/Wind Harmer
22.275
3144303KENBRDG
Solar/Wind Harmer
0.303
971443AH1-215 GEN
Solar/Wind Harmer
6.304
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.602
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.073
970831AG2-522 GEN
Solar/Wind Harmer
7.443
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.191
970163AG2-111 GEN
Solar/Wind Harmer
1.136
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.368
315607AA1-063A GEN
Solar/Wind Harmer
0.159
3146043SEABORD
Solar/Wind Harmer
0.076
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.25
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.462
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.252
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.992
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.575
3145783HORNRTN
Solar/Wind Harmer
1.26
3145783HORNRTN
Solar/Wind Harmer
0.394
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.38
316263AC1-034 GEN
Solar/Wind Harmer
2.393
961601AG1-000A GEN
Solar/Wind Harmer
1.088
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.132
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.414
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.062
961601AG1-000A GEN
Solar/Wind Harmer
4.35
315724AD1-057 GEN
Solar/Wind Harmer
0.227
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.818
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:201.95 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1381.35
MW Contribution:4.62
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
970285AG2-188 GEN
Solar/Wind Harmer
71.826
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:201.95 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1381.35
MW Contribution:4.62
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
970285AG2-188 GEN
Solar/Wind Harmer
71.826
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
316239AB2-077_GEN
Solar/Wind Harmer
0.968
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2106-2111_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2106-2111_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:128.21 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:876.96
MW Contribution:2.84
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.18
3144293JTRSVLE
50/50
0.994
970535AG2-341 GEN
50/50
2.836
3152661PLYWOOD A
50/50
0.267
970301AG2-198 GEN
Solar/Wind Harmer
21.257
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.133
963191AG1-168 GEN
Solar/Wind Harmer
3.68
971741AH1-377 GEN
Solar/Wind Harmer
43.417
316034AC1-036 C
Solar/Wind Harmer
0.574
970323AG2-213 GEN
Solar/Wind Harmer
15.434
971775AH1-396 GEN
Solar/Wind Harmer
2.198
313527AB2-043 GEN
Solar/Wind Harmer
3.442
962561AG1-105 GEN
Solar/Wind Harmer
9.457
939181AE1-148 GEN
Solar/Wind Harmer
9.083
964791AG1-342 GEN
Solar/Wind Harmer
3.423
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.098
970933AG2-581 GEN
Solar/Wind Harmer
9.079
316181AB2-040 GEN
Solar/Wind Harmer
1.138
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.878
3145593CAROLNA
Solar/Wind Harmer
0.065
3145783HORNRTN
Solar/Wind Harmer
0.905
3145783HORNRTN
Solar/Wind Harmer
0.724
3145783HORNRTN
Solar/Wind Harmer
0.226
3145783HORNRTN
Solar/Wind Harmer
0.09
316222AC1-221 GEN
Solar/Wind Harmer
0.769
316426AA2-053 GEN
Solar/Wind Harmer
0.748
942751AE2-291 GEN
Solar/Wind Harmer
4.333
316274AC1-208 GEN
Solar/Wind Harmer
0.717
972187AH1-678 GEN
Adder
1.63
3146776BUCKING
Solar/Wind Helper
3.482
3146776BUCKING
Solar/Wind Helper
0.282
315821AE2-092 GEN
Solar/Wind Helper
2.994
3144293JTRSVLE
50/50
1.18
3151601KERR 3
50/50
0.277
3151581KERR 1
50/50
0.099
3151531CLOVER1
50/50
2.843
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.907
971563AH1-280 GEN
Solar/Wind Harmer
4.907
970685AG2-442 GEN
Solar/Wind Harmer
30.788
962491AG1-098 GEN
Solar/Wind Harmer
14.151
316237AB2-079_GEN
Solar/Wind Harmer
0.621
315693AD1-088 GEN
Solar/Wind Harmer
9.998
970401AG2-262 GEN
Solar/Wind Harmer
1.046
957481AF2-042 GEN
Solar/Wind Harmer
45.244
315687AD1-152 GEN
Solar/Wind Harmer
1.611
971065AG2-659 GEN
Solar/Wind Harmer
6.471
316129AC1-054 GEN
Solar/Wind Harmer
1.098
3147043LAWRENC
Adder
0.994
316003AC1-222 GEN
Solar/Wind Harmer
1.108
971795AH1-408 GEN
Solar/Wind Harmer
8.341
960081AF2-299 GEN
Solar/Wind Harmer
0.953
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.091
316212AC1-099_GEN
Solar/Wind Harmer
0.553
316322AB2-045
Solar/Wind Helper
0.97
3146776BUCKING
Solar/Wind Helper
0.348
316336AC2-165 C
Solar/Wind Helper
1.454
3151611KERR 4
50/50
0.277
3151621KERR 5
50/50
0.277
3151631KERR 6
50/50
0.277
3151641KERR 7
50/50
0.277
3151541CLOVER2
50/50
2.829
970285AG2-188 GEN
Solar/Wind Harmer
63.51
315657AE1-056 GEN
Solar/Wind Harmer
15.784
946301AF1-294 GEN
Solar/Wind Harmer
10.059
961791AG1-021 GEN
Solar/Wind Harmer
4.907
970683AG2-441 GEN
Solar/Wind Harmer
27.489
970681AG2-440 GEN
Solar/Wind Harmer
21.992
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.004
316239AB2-077_GEN
Solar/Wind Harmer
0.621
316238AB2-078_GEN
Solar/Wind Harmer
0.621
316118AC1-105 GEN
Solar/Wind Harmer
0.972
3147173SINAI
Solar/Wind Harmer
-0.012
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.033
970865AG2-541 GEN
Solar/Wind Harmer
3.923
946281AF1-292 GEN
Solar/Wind Harmer
0.19
316087AB2-174 GEN
Solar/Wind Harmer
1.178
3137643SOCKMAN
Solar/Wind Harmer
-0.032
316123AC1-075 GEN
Solar/Wind Harmer
0.853
970165AG2-112 GEN
Solar/Wind Harmer
0.751
970163AG2-111 GEN
Solar/Wind Harmer
0.717
971967AH1-528 GEN
Solar/Wind Harmer
14.188
315607AA1-063A GEN
Solar/Wind Harmer
0.715
3146043SEABORD
Solar/Wind Harmer
-0.007
270494AE1-108_GEN
Solar/Wind Helper
4.499
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3144293JTRSVLE
50/50
1.18
3151591KERR 2
50/50
0.277
970413AG2-270 GEN
50/50
12.405
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.535
970909AG2-566 GEN
Solar/Wind Harmer
4.036
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.307
963181AG1-167 GEN
Solar/Wind Harmer
3.68
959311AF2-222 GEN
Solar/Wind Harmer
33.514
970257AG2-171 GEN
Solar/Wind Harmer
11.575
315785AD2-033 C
Solar/Wind Harmer
6.609
964241AG1-285 GEN
Solar/Wind Harmer
19.233
316131AB2-060 GEN
Solar/Wind Harmer
2.359
316478AD1-087 GEN
Solar/Wind Harmer
1.29
316486AD2-202 GEN
Solar/Wind Harmer
0.378
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.371
960061AF2-297 GEN
Solar/Wind Harmer
6.151
971683AH1-343 GEN
Solar/Wind Harmer
4.535
966621AG1-532 GEN
Solar/Wind Harmer
0.172
313506AB2-031 GEN
Solar/Wind Harmer
0.656
316283AC2-100 C
Solar/Wind Harmer
0.705
316210AC1-098 GEN
Solar/Wind Harmer
0.995
3146776BUCKING
Solar/Wind Helper
0.313
316313AB2-026
Solar/Wind Helper
0.341
316258AE1-075 C
Solar/Wind Helper
0.306
316405AF2-144 C
Solar/Wind Helper
0.255
3148013FISHERV
Solar/Wind Helper
0.125
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.19
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.966
MECLTFEXP_MEC->PJM
CLTF
0.645
SIGELTFEXP_SIGE->PJM
CLTF
0.018
CPLELTFEXP_CPLE->PJM
CLTF
3.717
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.651
LAGNLTFEXP_LAGN->PJM
CLTF
1.842
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.457
TVALTFEXP_TVA->PJM
CLTF
0.904
NYPJM->LTFIMP_NY
CLTF
0.34
LGEELTFEXP_LGEE->PJM
CLTF
0.186
WECLTFEXP_WEC->PJM
CLTF
0.097

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:128.06 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:875.95
MW Contribution:2.93
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.195
3144293JTRSVLE
50/50
1.007
970535AG2-341 GEN
50/50
2.934
3152661PLYWOOD A
50/50
0.28
970301AG2-198 GEN
Solar/Wind Harmer
21.495
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.212
963191AG1-168 GEN
Solar/Wind Harmer
3.727
971741AH1-377 GEN
Solar/Wind Harmer
43.991
316034AC1-036 C
Solar/Wind Harmer
0.584
970323AG2-213 GEN
Solar/Wind Harmer
15.706
971775AH1-396 GEN
Solar/Wind Harmer
2.237
313527AB2-043 GEN
Solar/Wind Harmer
3.538
962561AG1-105 GEN
Solar/Wind Harmer
9.795
939181AE1-148 GEN
Solar/Wind Harmer
9.44
964791AG1-342 GEN
Solar/Wind Harmer
3.552
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
970099AG2-077 GEN
Solar/Wind Harmer
18.81
970933AG2-581 GEN
Solar/Wind Harmer
9.592
316181AB2-040 GEN
Solar/Wind Harmer
1.225
316222AC1-221 GEN
Solar/Wind Harmer
0.857
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.951
3145593CAROLNA
Solar/Wind Harmer
0.07
3145783HORNRTN
Solar/Wind Harmer
0.982
3145783HORNRTN
Solar/Wind Harmer
0.786
3145783HORNRTN
Solar/Wind Harmer
0.245
3145783HORNRTN
Solar/Wind Harmer
0.098
316426AA2-053 GEN
Solar/Wind Harmer
0.813
3144293JTRSVLE
50/50
1.195
3151601KERR 3
50/50
0.289
3151581KERR 1
50/50
0.103
3151531CLOVER1
50/50
2.955
3147043LAWRENC
50/50
1.106
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.97
971563AH1-280 GEN
Solar/Wind Harmer
4.97
970685AG2-442 GEN
Solar/Wind Harmer
31.247
962491AG1-098 GEN
Solar/Wind Harmer
14.52
3151611KERR 4
50/50
0.289
3151621KERR 5
50/50
0.289
3151631KERR 6
50/50
0.289
3151641KERR 7
50/50
0.289
3151541CLOVER2
50/50
2.941
970285AG2-188 GEN
Solar/Wind Harmer
63.831
315657AE1-056 GEN
Solar/Wind Harmer
15.969
946301AF1-294 GEN
Solar/Wind Harmer
10.188
961791AG1-021 GEN
Solar/Wind Harmer
4.97
970683AG2-441 GEN
Solar/Wind Harmer
27.899
970681AG2-440 GEN
Solar/Wind Harmer
22.32
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.111
316239AB2-077_GEN
Solar/Wind Harmer
0.639
316238AB2-078_GEN
Solar/Wind Harmer
0.639
316118AC1-105 GEN
Solar/Wind Harmer
1.014
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.355
970865AG2-541 GEN
Solar/Wind Harmer
4.115
946281AF1-292 GEN
Solar/Wind Harmer
0.203
316087AB2-174 GEN
Solar/Wind Harmer
1.265
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.894
970165AG2-112 GEN
Solar/Wind Harmer
0.787
970163AG2-111 GEN
Solar/Wind Harmer
0.751
971967AH1-528 GEN
Solar/Wind Harmer
15.203
315607AA1-063A GEN
Solar/Wind Harmer
0.778
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.327
316274AC1-208 GEN
Solar/Wind Harmer
0.793
942751AE2-291 GEN
Solar/Wind Harmer
4.536
972187AH1-678 GEN
Adder
1.773
972185AH1-677 GEN
Adder
3.35
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
316263AC1-034 GEN
Solar/Wind Harmer
3.126
961601AG1-000A GEN
Solar/Wind Harmer
2.583
3145893MURPHYS
Solar/Wind Harmer
0.18
3145893MURPHYS
Solar/Wind Harmer
-0.012
3145493TOT1
Solar/Wind Harmer
0.098
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
3146776BUCKING
Solar/Wind Helper
3.457
3146776BUCKING
Solar/Wind Helper
0.28
315821AE2-092 GEN
Solar/Wind Helper
2.963
970581AG2-369 GEN
Solar/Wind Harmer
3.722
316319Z2-044 C
Solar/Wind Harmer
0.378
3146033SCOT NK
Solar/Wind Harmer
-0.027
315652AC1-086 GEN
Solar/Wind Harmer
7.562
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
965291AG1-394 GEN
Solar/Wind Harmer
0.582
970673AG2-436 GEN
Solar/Wind Harmer
13.618
970673AG2-436 GEN
Solar/Wind Harmer
6.895
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
270494AE1-108_GEN
Solar/Wind Helper
4.464
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
316237AB2-079_GEN
Solar/Wind Harmer
0.639
315693AD1-088 GEN
Solar/Wind Harmer
10.276
970401AG2-262 GEN
Solar/Wind Harmer
1.085
957481AF2-042 GEN
Solar/Wind Harmer
47.025
315687AD1-152 GEN
Solar/Wind Harmer
1.689
971065AG2-659 GEN
Solar/Wind Harmer
6.793
316129AC1-054 GEN
Solar/Wind Harmer
1.154
316003AC1-222 GEN
Solar/Wind Harmer
1.163
971795AH1-408 GEN
Solar/Wind Harmer
8.792
960081AF2-299 GEN
Solar/Wind Harmer
1.021
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.099
316212AC1-099_GEN
Solar/Wind Harmer
0.614
970919AG2-571 GEN
Solar/Wind Harmer
2.193
970087AG2-069 GEN
Solar/Wind Harmer
6.491
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.406
962571AG1-106 GEN
Solar/Wind Harmer
0.966
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316359AB2-059 GEN
Solar/Wind Harmer
0.899
316049AB1-081 GEN
Solar/Wind Harmer
0.72
3142053HEARTS
Solar/Wind Harmer
0.078
315722AD1-056 GEN
Solar/Wind Harmer
0.694
316023GEN1_S
Solar/Wind Harmer
0.443
3145823KELFORD
Solar/Wind Harmer
-0.006
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.191
961671AG1-007 GEN
Solar/Wind Harmer
0.08
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
316322AB2-045
Solar/Wind Helper
0.963
3146776BUCKING
Solar/Wind Helper
0.346
316336AC2-165 C
Solar/Wind Helper
1.425
3144293JTRSVLE
50/50
1.195
3151591KERR 2
50/50
0.289
970413AG2-270 GEN
50/50
12.897
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.604
970909AG2-566 GEN
Solar/Wind Harmer
4.081
3147133PAMPLIN
Solar/Wind Harmer
-0.133
971193AH1-056 GEN
Solar/Wind Harmer
26.615
963181AG1-167 GEN
Solar/Wind Harmer
3.727
959311AF2-222 GEN
Solar/Wind Harmer
34.076
970257AG2-171 GEN
Solar/Wind Harmer
11.779
315785AD2-033 C
Solar/Wind Harmer
6.734
964241AG1-285 GEN
Solar/Wind Harmer
19.68
316131AB2-060 GEN
Solar/Wind Harmer
2.422
316478AD1-087 GEN
Solar/Wind Harmer
1.342
316486AD2-202 GEN
Solar/Wind Harmer
0.393
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.389
960061AF2-297 GEN
Solar/Wind Harmer
6.458
971683AH1-343 GEN
Solar/Wind Harmer
4.759
966621AG1-532 GEN
Solar/Wind Harmer
0.184
313506AB2-031 GEN
Solar/Wind Harmer
0.706
316283AC2-100 C
Solar/Wind Harmer
0.787
316210AC1-098 GEN
Solar/Wind Harmer
1.105
316327AA2-057 GEN
Solar/Wind Harmer
0.707
970917AG2-570 GEN
Solar/Wind Harmer
17.327
3146233WITAKRS
Solar/Wind Harmer
0.143
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.004
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.382
316365GEN2_N
Solar/Wind Harmer
0.443
961601AG1-000A GEN
Solar/Wind Harmer
2.615
316317KELFORD C
Solar/Wind Harmer
0.306
3145823KELFORD
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.09
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
957521AF2-046 GEN
Solar/Wind Harmer
5.039
961681AG1-008 GEN
Solar/Wind Harmer
5.039
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.311
316313AB2-026
Solar/Wind Helper
0.332
316258AE1-075 C
Solar/Wind Helper
0.299
316405AF2-144 C
Solar/Wind Helper
0.249
3148013FISHERV
Solar/Wind Helper
0.123
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.102
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.96
MECLTFEXP_MEC->PJM
CLTF
0.838
SIGELTFEXP_SIGE->PJM
CLTF
0.022
CPLELTFEXP_CPLE->PJM
CLTF
4.543
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.552
LAGNLTFEXP_LAGN->PJM
CLTF
2.505
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.252
TVALTFEXP_TVA->PJM
CLTF
1.216
NYPJM->LTFIMP_NY
CLTF
0.295
LGEELTFEXP_LGEE->PJM
CLTF
0.219
WECLTFEXP_WEC->PJM
CLTF
0.123

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2003-205_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2003-205_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:124.48 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:851.47
MW Contribution:2.9
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.19
3151601KERR 3
50/50
0.284
3144293JTRSVLE
50/50
1.19
3151591KERR 2
50/50
0.284
3144293JTRSVLE
50/50
1.19
3144293JTRSVLE
50/50
1.002
970535AG2-341 GEN
50/50
2.898
3152661PLYWOOD A
50/50
0.275
970301AG2-198 GEN
Solar/Wind Harmer
21.406
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.183
963191AG1-168 GEN
Solar/Wind Harmer
3.71
971741AH1-377 GEN
Solar/Wind Harmer
43.786
316034AC1-036 C
Solar/Wind Harmer
0.58
970323AG2-213 GEN
Solar/Wind Harmer
15.608
971775AH1-396 GEN
Solar/Wind Harmer
2.223
313527AB2-043 GEN
Solar/Wind Harmer
3.505
962561AG1-105 GEN
Solar/Wind Harmer
9.664
939181AE1-148 GEN
Solar/Wind Harmer
9.308
964791AG1-342 GEN
Solar/Wind Harmer
3.501
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.602
970933AG2-581 GEN
Solar/Wind Harmer
9.49
316181AB2-040 GEN
Solar/Wind Harmer
1.218
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.934
3145593CAROLNA
Solar/Wind Harmer
0.069
3145783HORNRTN
Solar/Wind Harmer
0.963
3145783HORNRTN
Solar/Wind Harmer
0.77
3145783HORNRTN
Solar/Wind Harmer
0.241
3145783HORNRTN
Solar/Wind Harmer
0.096
316222AC1-221 GEN
Solar/Wind Harmer
0.802
316426AA2-053 GEN
Solar/Wind Harmer
0.797
316274AC1-208 GEN
Solar/Wind Harmer
0.766
942751AE2-291 GEN
Solar/Wind Harmer
4.503
972187AH1-678 GEN
Adder
1.745
972185AH1-677 GEN
Adder
3.302
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3146776BUCKING
Solar/Wind Helper
3.47
3146776BUCKING
Solar/Wind Helper
0.281
315821AE2-092 GEN
Solar/Wind Helper
2.982
3151581KERR 1
50/50
0.102
3151531CLOVER1
50/50
2.917
3147043LAWRENC
50/50
1.102
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.946
971563AH1-280 GEN
Solar/Wind Harmer
4.946
970685AG2-442 GEN
Solar/Wind Harmer
31.078
962491AG1-098 GEN
Solar/Wind Harmer
14.404
316237AB2-079_GEN
Solar/Wind Harmer
0.632
315693AD1-088 GEN
Solar/Wind Harmer
10.19
970401AG2-262 GEN
Solar/Wind Harmer
1.07
957481AF2-042 GEN
Solar/Wind Harmer
46.506
315687AD1-152 GEN
Solar/Wind Harmer
1.657
971065AG2-659 GEN
Solar/Wind Harmer
6.686
316129AC1-054 GEN
Solar/Wind Harmer
1.136
971795AH1-408 GEN
Solar/Wind Harmer
8.781
316003AC1-222 GEN
Solar/Wind Harmer
1.14
960081AF2-299 GEN
Solar/Wind Harmer
1.025
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.097
316212AC1-099_GEN
Solar/Wind Harmer
0.591
970919AG2-571 GEN
Solar/Wind Harmer
2.137
970087AG2-069 GEN
Solar/Wind Harmer
6.318
316023GEN1_S
Solar/Wind Harmer
0.452
316011AB1-132 GEN
Solar/Wind Harmer
1.389
962571AG1-106 GEN
Solar/Wind Harmer
0.954
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
-0.026
315722AD1-056 GEN
Solar/Wind Harmer
0.667
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316322AB2-045
Solar/Wind Helper
0.967
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.456
970413AG2-270 GEN
50/50
12.729
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.576
970909AG2-566 GEN
Solar/Wind Harmer
4.064
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.496
963181AG1-167 GEN
Solar/Wind Harmer
3.71
959311AF2-222 GEN
Solar/Wind Harmer
33.872
970257AG2-171 GEN
Solar/Wind Harmer
11.706
315785AD2-033 C
Solar/Wind Harmer
6.689
964241AG1-285 GEN
Solar/Wind Harmer
19.525
316131AB2-060 GEN
Solar/Wind Harmer
2.4
316478AD1-087 GEN
Solar/Wind Harmer
1.324
316486AD2-202 GEN
Solar/Wind Harmer
0.388
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.381
960061AF2-297 GEN
Solar/Wind Harmer
6.325
971683AH1-343 GEN
Solar/Wind Harmer
4.674
966621AG1-532 GEN
Solar/Wind Harmer
0.185
313506AB2-031 GEN
Solar/Wind Harmer
0.702
316283AC2-100 C
Solar/Wind Harmer
0.736
316210AC1-098 GEN
Solar/Wind Harmer
1.064
970917AG2-570 GEN
Solar/Wind Harmer
16.885
316365GEN2_N
Solar/Wind Harmer
0.452
316327AA2-057 GEN
Solar/Wind Harmer
0.676
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.136
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
315724AD1-057 GEN
Solar/Wind Harmer
0.367
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.312
316313AB2-026
Solar/Wind Helper
0.342
316258AE1-075 C
Solar/Wind Helper
0.307
316405AF2-144 C
Solar/Wind Helper
0.256
3148013FISHERV
Solar/Wind Helper
0.124
3151611KERR 4
50/50
0.284
3151621KERR 5
50/50
0.284
3151631KERR 6
50/50
0.284
3151641KERR 7
50/50
0.284
3151541CLOVER2
50/50
2.903
970285AG2-188 GEN
Solar/Wind Harmer
63.671
315657AE1-056 GEN
Solar/Wind Harmer
15.898
946301AF1-294 GEN
Solar/Wind Harmer
10.139
961791AG1-021 GEN
Solar/Wind Harmer
4.946
970683AG2-441 GEN
Solar/Wind Harmer
27.748
970681AG2-440 GEN
Solar/Wind Harmer
22.198
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.073
316239AB2-077_GEN
Solar/Wind Harmer
0.632
316238AB2-078_GEN
Solar/Wind Harmer
0.632
316118AC1-105 GEN
Solar/Wind Harmer
0.997
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.254
970865AG2-541 GEN
Solar/Wind Harmer
4.048
946281AF1-292 GEN
Solar/Wind Harmer
0.204
316087AB2-174 GEN
Solar/Wind Harmer
1.262
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.884
970165AG2-112 GEN
Solar/Wind Harmer
0.778
970163AG2-111 GEN
Solar/Wind Harmer
0.742
971967AH1-528 GEN
Solar/Wind Harmer
15.039
315607AA1-063A GEN
Solar/Wind Harmer
0.762
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.212
970581AG2-369 GEN
Solar/Wind Harmer
3.623
315652AC1-086 GEN
Solar/Wind Harmer
7.469
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.026
316319Z2-044 C
Solar/Wind Harmer
0.36
970673AG2-436 GEN
Solar/Wind Harmer
13.449
970673AG2-436 GEN
Solar/Wind Harmer
6.81
965291AG1-394 GEN
Solar/Wind Harmer
0.565
270494AE1-108_GEN
Solar/Wind Helper
4.476
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.511
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.403
MECLTFEXP_MEC->PJM
CLTF
0.809
SIGELTFEXP_SIGE->PJM
CLTF
0.023
CPLELTFEXP_CPLE->PJM
CLTF
3.951
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.116
LAGNLTFEXP_LAGN->PJM
CLTF
2.085
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.001
TVALTFEXP_TVA->PJM
CLTF
1.025
NYPJM->LTFIMP_NY
CLTF
0.315
LGEELTFEXP_LGEE->PJM
CLTF
0.251
WECLTFEXP_WEC->PJM
CLTF
0.133

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:115.8 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:792.06
MW Contribution:2.87
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.186
3144293JTRSVLE
50/50
0.999
970535AG2-341 GEN
50/50
2.873
3152661PLYWOOD A
50/50
0.275
970301AG2-198 GEN
Solar/Wind Harmer
21.341
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.165
963191AG1-168 GEN
Solar/Wind Harmer
3.699
971741AH1-377 GEN
Solar/Wind Harmer
43.617
316034AC1-036 C
Solar/Wind Harmer
0.578
970323AG2-213 GEN
Solar/Wind Harmer
15.547
971775AH1-396 GEN
Solar/Wind Harmer
2.214
313527AB2-043 GEN
Solar/Wind Harmer
3.483
962561AG1-105 GEN
Solar/Wind Harmer
9.649
964791AG1-342 GEN
Solar/Wind Harmer
3.499
939181AE1-148 GEN
Solar/Wind Harmer
9.211
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.337
970933AG2-581 GEN
Solar/Wind Harmer
9.235
316181AB2-040 GEN
Solar/Wind Harmer
1.163
942751AE2-291 GEN
Solar/Wind Harmer
5.136
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.898
3145593CAROLNA
Solar/Wind Harmer
0.066
316222AC1-221 GEN
Solar/Wind Harmer
0.791
3145783HORNRTN
Solar/Wind Harmer
0.925
3145783HORNRTN
Solar/Wind Harmer
0.74
3145783HORNRTN
Solar/Wind Harmer
0.231
3145783HORNRTN
Solar/Wind Harmer
0.092
316426AA2-053 GEN
Solar/Wind Harmer
0.765
316274AC1-208 GEN
Solar/Wind Harmer
0.735
972187AH1-678 GEN
Adder
1.669
3146776BUCKING
Solar/Wind Helper
3.473
3146776BUCKING
Solar/Wind Helper
0.281
315821AE2-092 GEN
Solar/Wind Helper
2.981
3151611KERR 4
50/50
0.281
3151621KERR 5
50/50
0.281
3151631KERR 6
50/50
0.281
3151641KERR 7
50/50
0.281
3151541CLOVER2
50/50
2.869
970285AG2-188 GEN
Solar/Wind Harmer
63.627
315657AE1-056 GEN
Solar/Wind Harmer
15.857
946301AF1-294 GEN
Solar/Wind Harmer
10.111
961791AG1-021 GEN
Solar/Wind Harmer
4.932
970683AG2-441 GEN
Solar/Wind Harmer
27.657
970681AG2-440 GEN
Solar/Wind Harmer
22.126
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.048
316239AB2-077_GEN
Solar/Wind Harmer
0.628
316238AB2-078_GEN
Solar/Wind Harmer
0.628
316118AC1-105 GEN
Solar/Wind Harmer
1
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.134
970865AG2-541 GEN
Solar/Wind Harmer
4.26
316123AC1-075 GEN
Solar/Wind Harmer
0.971
970165AG2-112 GEN
Solar/Wind Harmer
0.855
970163AG2-111 GEN
Solar/Wind Harmer
0.816
946281AF1-292 GEN
Solar/Wind Harmer
0.194
316087AB2-174 GEN
Solar/Wind Harmer
1.202
3137643SOCKMAN
Solar/Wind Harmer
-0.032
971967AH1-528 GEN
Solar/Wind Harmer
14.485
315607AA1-063A GEN
Solar/Wind Harmer
0.732
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.036
970581AG2-369 GEN
Solar/Wind Harmer
3.471
270494AE1-108_GEN
Solar/Wind Helper
4.511
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.186
3151591KERR 2
50/50
0.281
970413AG2-270 GEN
50/50
12.579
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.561
970909AG2-566 GEN
Solar/Wind Harmer
4.052
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.429
963181AG1-167 GEN
Solar/Wind Harmer
3.699
959311AF2-222 GEN
Solar/Wind Harmer
33.746
970257AG2-171 GEN
Solar/Wind Harmer
11.66
315785AD2-033 C
Solar/Wind Harmer
6.661
964241AG1-285 GEN
Solar/Wind Harmer
19.423
316131AB2-060 GEN
Solar/Wind Harmer
2.386
316478AD1-087 GEN
Solar/Wind Harmer
1.308
316486AD2-202 GEN
Solar/Wind Harmer
0.383
316248AF1-058 C
Solar/Wind Harmer
0.384
960061AF2-297 GEN
Solar/Wind Harmer
6.368
3147043LAWRENC
Solar/Wind Harmer
-0.007
971683AH1-343 GEN
Solar/Wind Harmer
4.838
966621AG1-532 GEN
Solar/Wind Harmer
0.176
313506AB2-031 GEN
Solar/Wind Harmer
0.67
316283AC2-100 C
Solar/Wind Harmer
0.725
316210AC1-098 GEN
Solar/Wind Harmer
1.021
970917AG2-570 GEN
Solar/Wind Harmer
16.174
316327AA2-057 GEN
Solar/Wind Harmer
0.648
3146263WOODLND
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.312
316313AB2-026
Solar/Wind Helper
0.338
316258AE1-075 C
Solar/Wind Helper
0.304
316405AF2-144 C
Solar/Wind Helper
0.253
3148013FISHERV
Solar/Wind Helper
0.124
3144293JTRSVLE
50/50
1.186
3151601KERR 3
50/50
0.281
3151581KERR 1
50/50
0.1
3151531CLOVER1
50/50
2.882
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.932
971563AH1-280 GEN
Solar/Wind Harmer
4.932
970685AG2-442 GEN
Solar/Wind Harmer
30.976
962491AG1-098 GEN
Solar/Wind Harmer
14.277
316237AB2-079_GEN
Solar/Wind Harmer
0.628
315693AD1-088 GEN
Solar/Wind Harmer
10.093
970401AG2-262 GEN
Solar/Wind Harmer
1.069
957481AF2-042 GEN
Solar/Wind Harmer
45.841
315687AD1-152 GEN
Solar/Wind Harmer
1.641
971065AG2-659 GEN
Solar/Wind Harmer
6.575
316129AC1-054 GEN
Solar/Wind Harmer
1.116
3147043LAWRENC
Adder
1.01
316003AC1-222 GEN
Solar/Wind Harmer
1.164
971795AH1-408 GEN
Solar/Wind Harmer
8.484
960081AF2-299 GEN
Solar/Wind Harmer
0.973
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.093
316212AC1-099_GEN
Solar/Wind Harmer
0.567
970919AG2-571 GEN
Solar/Wind Harmer
2.047
970087AG2-069 GEN
Solar/Wind Harmer
6.053
3146263WOODLND
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.968
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.444
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.023
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.205
MECLTFEXP_MEC->PJM
CLTF
0.743
SIGELTFEXP_SIGE->PJM
CLTF
0.021
CPLELTFEXP_CPLE->PJM
CLTF
3.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.48
LAGNLTFEXP_LAGN->PJM
CLTF
1.974
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.732
TVALTFEXP_TVA->PJM
CLTF
0.969
NYPJM->LTFIMP_NY
CLTF
0.299
LGEELTFEXP_LGEE->PJM
CLTF
0.225
WECLTFEXP_WEC->PJM
CLTF
0.119

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.37 %
Rating:559.3 MVA
Rating Type:A
MVA to Mitigate:617.32
MW Contribution:2.85
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.279
3151621KERR 5
50/50
0.279
3151631KERR 6
50/50
0.279
3151641KERR 7
50/50
0.279
3151541CLOVER2
50/50
2.847
3151281ROARAP4
50/50
0.085
3151281ROARAP4
50/50
0.08
963041AG1-153 GEN
50/50
1.549
970285AG2-188 GEN
Solar/Wind Harmer
51.175
315657AE1-056 GEN
Solar/Wind Harmer
12.95
946301AF1-294 GEN
Solar/Wind Harmer
6.911
961791AG1-021 GEN
Solar/Wind Harmer
3.362
970683AG2-441 GEN
Solar/Wind Harmer
20.935
970681AG2-440 GEN
Solar/Wind Harmer
16.748
3144303KENBRDG
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
4.574
316239AB2-077_GEN
Solar/Wind Harmer
0.001
3144293JTRSVLE
50/50
1.183
3151601KERR 3
50/50
0.279
3151581KERR 1
50/50
0.1
3151531CLOVER1
50/50
2.861
3147043LAWRENC
50/50
1.063
3151261ROARAP2
50/50
0.088
3151051BRUNSWICKS1
50/50
1.588
3151021BRUNSWICKG1
50/50
0.765
971451AH1-221 GEN
50/50
2.324
3146926FARMVIL
Solar/Wind Harmer
0.316
963171AG1-166 GEN
Solar/Wind Harmer
1.868
971563AH1-280 GEN
Solar/Wind Harmer
3.736
970685AG2-442 GEN
Solar/Wind Harmer
23.448
3144293JTRSVLE
50/50
1.183
3144293JTRSVLE
50/50
0.996
970535AG2-341 GEN
50/50
2.851
3152661PLYWOOD A
50/50
0.269
3151041BRUNSWICKG3
50/50
0.765
972187AH1-678 GEN
50/50
1.756
970301AG2-198 GEN
Solar/Wind Harmer
16.182
3147133PAMPLIN
Solar/Wind Harmer
0.375
3147133PAMPLIN
Solar/Wind Harmer
0.3
958211AF2-115 GEN
Solar/Wind Harmer
4.203
963191AG1-168 GEN
Solar/Wind Harmer
1.401
971741AH1-377 GEN
Solar/Wind Harmer
33.06
316034AC1-036 C
Solar/Wind Harmer
0.02
970323AG2-213 GEN
Solar/Wind Harmer
11.759
971775AH1-396 GEN
Solar/Wind Harmer
0.441
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
7.224
939181AE1-148 GEN
Solar/Wind Harmer
6.94
964791AG1-342 GEN
Solar/Wind Harmer
2.755
3146843MT LREL
Solar/Wind Harmer
0.143
3146843MT LREL
Solar/Wind Harmer
0.143
970099AG2-077 GEN
Solar/Wind Harmer
13.837
962491AG1-098 GEN
Solar/Wind Harmer
10.797
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
8.584
970401AG2-262 GEN
Solar/Wind Harmer
0.842
957481AF2-042 GEN
Solar/Wind Harmer
34.592
315687AD1-152 GEN
Solar/Wind Harmer
0.004
971065AG2-659 GEN
Solar/Wind Harmer
4.952
316129AC1-054 GEN
Solar/Wind Harmer
0.422
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.327
3147173SINAI
Solar/Wind Harmer
0.11
3147243WELCO
Solar/Wind Harmer
0.069
970831AG2-522 GEN
Solar/Wind Harmer
4.619
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971795AH1-408 GEN
Solar/Wind Harmer
6.656
960081AF2-299 GEN
Solar/Wind Harmer
0.732
3145783HORNRTN
Solar/Wind Harmer
0.069
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
0.296
970919AG2-571 GEN
Solar/Wind Harmer
2.029
970087AG2-069 GEN
Solar/Wind Harmer
4.556
316322AB2-045
Solar/Wind Helper
0.968
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.445
970933AG2-581 GEN
Solar/Wind Harmer
6.964
316181AB2-040 GEN
Solar/Wind Harmer
0.107
3145593CAROLNA
Solar/Wind Harmer
0.07
3145593CAROLNA
Solar/Wind Harmer
0.07
966811AG1-552 GEN
Solar/Wind Harmer
0.763
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.221
3145783HORNRTN
Solar/Wind Harmer
0.977
3145783HORNRTN
Solar/Wind Harmer
0.305
3145783HORNRTN
Solar/Wind Harmer
0.122
316222AC1-221 GEN
Solar/Wind Harmer
0.284
316426AA2-053 GEN
Solar/Wind Harmer
0.225
942751AE2-291 GEN
Solar/Wind Harmer
3.338
316274AC1-208 GEN
Solar/Wind Harmer
0.311
3146776BUCKING
Solar/Wind Helper
3.475
3146776BUCKING
Solar/Wind Helper
0.282
315821AE2-092 GEN
Solar/Wind Helper
2.978
3144293JTRSVLE
50/50
1.183
3151591KERR 2
50/50
0.279
970413AG2-270 GEN
50/50
12.485
3151261ROARAP2
50/50
0.086
3151031BRUNSWICKG2
50/50
0.765
3146926FARMVIL
Solar/Wind Harmer
0.316
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.045
3147133PAMPLIN
Solar/Wind Harmer
1.178
971193AH1-056 GEN
Solar/Wind Harmer
22.863
963181AG1-167 GEN
Solar/Wind Harmer
1.401
959311AF2-222 GEN
Solar/Wind Harmer
25.479
970257AG2-171 GEN
Solar/Wind Harmer
8.819
315785AD2-033 C
Solar/Wind Harmer
2.117
964241AG1-285 GEN
Solar/Wind Harmer
14.665
316131AB2-060 GEN
Solar/Wind Harmer
0.615
316478AD1-087 GEN
Solar/Wind Harmer
0.466
316486AD2-202 GEN
Solar/Wind Harmer
0.137
970865AG2-541 GEN
Solar/Wind Harmer
3.009
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.287
316123AC1-075 GEN
Solar/Wind Harmer
0.097
970165AG2-112 GEN
Solar/Wind Harmer
0.577
970163AG2-111 GEN
Solar/Wind Harmer
0.551
971967AH1-528 GEN
Solar/Wind Harmer
10.885
315607AA1-063A GEN
Solar/Wind Harmer
0.13
3146043SEABORD
Solar/Wind Harmer
0.063
970085AG2-068 GEN
Solar/Wind Harmer
3.037
970581AG2-369 GEN
Solar/Wind Harmer
2.612
270494AE1-108_GEN
Solar/Wind Helper
4.476
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3147043LAWRENC
Solar/Wind Harmer
0.066
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.708
971683AH1-343 GEN
Solar/Wind Harmer
3.476
313506AB2-031 GEN
Solar/Wind Harmer
0.227
316283AC2-100 C
Solar/Wind Harmer
0.132
316210AC1-098 GEN
Solar/Wind Harmer
0.531
970917AG2-570 GEN
Solar/Wind Harmer
5.072
316327AA2-057 GEN
Solar/Wind Harmer
0.085
3146776BUCKING
Solar/Wind Helper
0.313
316313AB2-026
Solar/Wind Helper
0.338
316258AE1-075 C
Solar/Wind Helper
0.304
316405AF2-144 C
Solar/Wind Helper
0.253
3148013FISHERV
Solar/Wind Helper
0.123
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.153
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.217
MECLTFEXP_MEC->PJM
CLTF
0.756
SIGELTFEXP_SIGE->PJM
CLTF
0.021
CPLELTFEXP_CPLE->PJM
CLTF
3.789
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.54
LAGNLTFEXP_LAGN->PJM
CLTF
1.976
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.656
TVALTFEXP_TVA->PJM
CLTF
0.971
NYPJM->LTFIMP_NY
CLTF
0.298
LGEELTFEXP_LGEE->PJM
CLTF
0.232
WECLTFEXP_WEC->PJM
CLTF
0.123

Details for AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:132.79 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:758.93
MW Contribution:1.99
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
971629AH1-314 GEN
50/50
5.006
962491AG1-098 GEN
Solar/Wind Harmer
22.331
315693AD1-088 GEN
Solar/Wind Harmer
18.25
957481AF2-042 GEN
Solar/Wind Harmer
90.747
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.071
316129AC1-054 GEN
Solar/Wind Harmer
0.427
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
971967AH1-528 GEN
Solar/Wind Harmer
55.717
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
316118AC1-105 GEN
Solar/Wind Harmer
0.376
970865AG2-541 GEN
Solar/Wind Harmer
4.593
316123AC1-075 GEN
Solar/Wind Harmer
0.152
970165AG2-112 GEN
Solar/Wind Harmer
0.903
970163AG2-111 GEN
Solar/Wind Harmer
0.862
970831AG2-522 GEN
Solar/Wind Harmer
4.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
970909AG2-566 GEN
Solar/Wind Harmer
6.347
316478AD1-087 GEN
Solar/Wind Harmer
1.094
316486AD2-202 GEN
Solar/Wind Harmer
0.321
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.01
971683AH1-343 GEN
Solar/Wind Harmer
5.256
316283AC2-100 C
Solar/Wind Harmer
0.206
316131AB2-060 GEN
Solar/Wind Harmer
0.208
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
3152661PLYWOOD A
50/50
0.346
970535AG2-341 GEN
50/50
1.993
970301AG2-198 GEN
Solar/Wind Harmer
25.388
971741AH1-377 GEN
Solar/Wind Harmer
54.138
970933AG2-581 GEN
Solar/Wind Harmer
27.859
970099AG2-077 GEN
Solar/Wind Harmer
36.299
939181AE1-148 GEN
Solar/Wind Harmer
6.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.689
316222AC1-221 GEN
Solar/Wind Harmer
0.447
942751AE2-291 GEN
Solar/Wind Harmer
5.336
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.22 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:744.24
MW Contribution:1.99
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
0.346
970535AG2-341 GEN
50/50
1.993
970301AG2-198 GEN
Solar/Wind Harmer
25.388
971741AH1-377 GEN
Solar/Wind Harmer
54.138
970099AG2-077 GEN
Solar/Wind Harmer
36.299
939181AE1-148 GEN
Solar/Wind Harmer
6.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.689
316222AC1-221 GEN
Solar/Wind Harmer
0.447
942751AE2-291 GEN
Solar/Wind Harmer
5.336
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
971629AH1-314 GEN
50/50
5.006
962491AG1-098 GEN
Solar/Wind Harmer
22.331
315693AD1-088 GEN
Solar/Wind Harmer
18.25
957481AF2-042 GEN
Solar/Wind Harmer
90.747
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.071
316129AC1-054 GEN
Solar/Wind Harmer
0.427
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
316118AC1-105 GEN
Solar/Wind Harmer
0.376
970865AG2-541 GEN
Solar/Wind Harmer
4.593
316123AC1-075 GEN
Solar/Wind Harmer
0.152
970165AG2-112 GEN
Solar/Wind Harmer
0.903
970163AG2-111 GEN
Solar/Wind Harmer
0.862
970831AG2-522 GEN
Solar/Wind Harmer
4.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
970909AG2-566 GEN
Solar/Wind Harmer
6.347
316478AD1-087 GEN
Solar/Wind Harmer
1.094
316486AD2-202 GEN
Solar/Wind Harmer
0.321
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.01
971683AH1-343 GEN
Solar/Wind Harmer
5.256
316283AC2-100 C
Solar/Wind Harmer
0.206
316131AB2-060 GEN
Solar/Wind Harmer
0.208
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:129.97 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:908.5
MW Contribution:2.0
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
29.414
3151591KERR 2
50/50
0.302
970909AG2-566 GEN
Solar/Wind Harmer
6.35
316478AD1-087 GEN
Solar/Wind Harmer
3.055
316486AD2-202 GEN
Solar/Wind Harmer
0.895
316248AF1-058 C
Solar/Wind Harmer
0.559
960061AF2-297 GEN
Solar/Wind Harmer
9.268
971683AH1-343 GEN
Solar/Wind Harmer
6.951
316283AC2-100 C
Solar/Wind Harmer
1.124
316131AB2-060 GEN
Solar/Wind Harmer
0.808
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.542
3147133PAMPLIN
Solar/Wind Helper
1.062
316313AB2-026
Solar/Wind Helper
0.243
316258AE1-075 C
Solar/Wind Helper
0.219
316405AF2-144 C
Solar/Wind Helper
0.182
3152661PLYWOOD A
50/50
0.348
970535AG2-341 GEN
50/50
2.001
970301AG2-198 GEN
Solar/Wind Harmer
33.445
971741AH1-377 GEN
Solar/Wind Harmer
71.327
970933AG2-581 GEN
Solar/Wind Harmer
36.739
970099AG2-077 GEN
Solar/Wind Harmer
47.872
939181AE1-148 GEN
Solar/Wind Harmer
8.421
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.05
962561AG1-105 GEN
Solar/Wind Harmer
7.525
316222AC1-221 GEN
Solar/Wind Harmer
1.236
942751AE2-291 GEN
Solar/Wind Harmer
7.063
313527AB2-043 GEN
Solar/Wind Harmer
1.361
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.338
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.919
3151531CLOVER1
50/50
6.74
3151601KERR 3
50/50
0.302
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.44
315693AD1-088 GEN
Solar/Wind Harmer
21.388
957481AF2-042 GEN
Solar/Wind Harmer
119.681
315687AD1-152 GEN
Solar/Wind Harmer
3.524
316003AC1-222 GEN
Solar/Wind Harmer
1.683
970401AG2-262 GEN
Solar/Wind Harmer
0.932
971065AG2-659 GEN
Solar/Wind Harmer
6.697
316129AC1-054 GEN
Solar/Wind Harmer
1.121
316237AB2-079_GEN
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Helper
0.44
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
1.003
3151541CLOVER2
50/50
6.708
3151611KERR 4
50/50
0.302
3151621KERR 5
50/50
0.302
3151631KERR 6
50/50
0.302
3151641KERR 7
50/50
0.302
971967AH1-528 GEN
Solar/Wind Harmer
73.672
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.131
970865AG2-541 GEN
Solar/Wind Harmer
6.075
316123AC1-075 GEN
Solar/Wind Harmer
1.358
970165AG2-112 GEN
Solar/Wind Harmer
1.195
970163AG2-111 GEN
Solar/Wind Harmer
1.14
970831AG2-522 GEN
Solar/Wind Harmer
6.069
316239AB2-077_GEN
Solar/Wind Harmer
0.274
316238AB2-078_GEN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Harmer
1.371
270457AD2-023 GEN
Solar/Wind Harmer
0.695
270494AE1-108_GEN
Solar/Wind Helper
2.769
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.6
MECLTFEXP_MEC->PJM
CLTF
1.297
SIGELTFEXP_SIGE->PJM
CLTF
0.038
CPLELTFEXP_CPLE->PJM
CLTF
4.232
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.165
LAGNLTFEXP_LAGN->PJM
CLTF
2.703
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.92
TVALTFEXP_TVA->PJM
CLTF
1.347
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.461
WECLTFEXP_WEC->PJM
CLTF
0.241

Details for AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-198 TP-6BRIERY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:129.93 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:908.21
MW Contribution:2.0
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
6.74
3151601KERR 3
50/50
0.302
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.44
315693AD1-088 GEN
Solar/Wind Harmer
21.388
957481AF2-042 GEN
Solar/Wind Harmer
119.681
315687AD1-152 GEN
Solar/Wind Harmer
3.524
316003AC1-222 GEN
Solar/Wind Harmer
1.683
970401AG2-262 GEN
Solar/Wind Harmer
0.932
971065AG2-659 GEN
Solar/Wind Harmer
6.697
3151541CLOVER2
50/50
6.708
3151611KERR 4
50/50
0.302
3151621KERR 5
50/50
0.302
3151631KERR 6
50/50
0.302
3151641KERR 7
50/50
0.302
971967AH1-528 GEN
Solar/Wind Harmer
73.672
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.131
970865AG2-541 GEN
Solar/Wind Harmer
6.075
316123AC1-075 GEN
Solar/Wind Harmer
1.358
970165AG2-112 GEN
Solar/Wind Harmer
1.195
970163AG2-111 GEN
Solar/Wind Harmer
1.14
970831AG2-522 GEN
Solar/Wind Harmer
6.069
316239AB2-077_GEN
Solar/Wind Harmer
0.274
316238AB2-078_GEN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Harmer
1.371
270457AD2-023 GEN
Solar/Wind Harmer
0.695
270494AE1-108_GEN
Solar/Wind Helper
2.769
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
316129AC1-054 GEN
Solar/Wind Harmer
1.121
316237AB2-079_GEN
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Helper
0.44
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
1.003
3152661PLYWOOD A
50/50
0.348
970535AG2-341 GEN
50/50
2.001
970301AG2-198 GEN
Solar/Wind Harmer
33.445
971741AH1-377 GEN
Solar/Wind Harmer
71.327
970933AG2-581 GEN
Solar/Wind Harmer
36.739
970099AG2-077 GEN
Solar/Wind Harmer
47.872
939181AE1-148 GEN
Solar/Wind Harmer
8.421
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.05
962561AG1-105 GEN
Solar/Wind Harmer
7.525
316222AC1-221 GEN
Solar/Wind Harmer
1.236
942751AE2-291 GEN
Solar/Wind Harmer
7.063
313527AB2-043 GEN
Solar/Wind Harmer
1.361
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.338
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.919
970413AG2-270 GEN
50/50
29.414
3151591KERR 2
50/50
0.302
970909AG2-566 GEN
Solar/Wind Harmer
6.35
316478AD1-087 GEN
Solar/Wind Harmer
3.055
316486AD2-202 GEN
Solar/Wind Harmer
0.895
316248AF1-058 C
Solar/Wind Harmer
0.559
960061AF2-297 GEN
Solar/Wind Harmer
9.268
971683AH1-343 GEN
Solar/Wind Harmer
6.951
316283AC2-100 C
Solar/Wind Harmer
1.124
316131AB2-060 GEN
Solar/Wind Harmer
0.808
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.542
3147133PAMPLIN
Solar/Wind Helper
1.062
316313AB2-026
Solar/Wind Helper
0.243
316258AE1-075 C
Solar/Wind Helper
0.219
316405AF2-144 C
Solar/Wind Helper
0.182
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.6
MECLTFEXP_MEC->PJM
CLTF
1.297
SIGELTFEXP_SIGE->PJM
CLTF
0.038
CPLELTFEXP_CPLE->PJM
CLTF
4.232
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.165
LAGNLTFEXP_LAGN->PJM
CLTF
2.703
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.92
TVALTFEXP_TVA->PJM
CLTF
1.347
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.461
WECLTFEXP_WEC->PJM
CLTF
0.241

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:129.2 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5258.72
MW Contribution:4.57
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
53.421
316478AD1-087 GEN
Solar/Wind Harmer
1.525
316486AD2-202 GEN
Solar/Wind Harmer
0.448
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
13.182
316283AC2-100 C
Solar/Wind Harmer
0.55
971683AH1-343 GEN
Solar/Wind Harmer
10.2
316131AB2-060 GEN
Solar/Wind Harmer
0.796
964241AG1-285 GEN
Solar/Wind Harmer
16.703
315785AD2-033 C
Solar/Wind Harmer
2.003
970257AG2-171 GEN
Solar/Wind Harmer
7.834
959311AF2-222 GEN
Solar/Wind Harmer
21.656
963181AG1-167 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.736
971193AH1-056 GEN
Solar/Wind Harmer
14.274
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.131
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
0.943
3146776BUCKING
Solar/Wind Harmer
0.049
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.212
270336AE1-100 GEN
Solar/Wind Harmer
0.003
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.117
971623AH1-311 GEN
Solar/Wind Harmer
0.234
961601AG1-000A GEN
Solar/Wind Harmer
8.141
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
47.73
957481AF2-042 GEN
Solar/Wind Harmer
126.807
315693AD1-088 GEN
Solar/Wind Harmer
20.818
962491AG1-098 GEN
Solar/Wind Harmer
24.385
315687AD1-152 GEN
Solar/Wind Harmer
0.013
316003AC1-222 GEN
Solar/Wind Harmer
0.008
970401AG2-262 GEN
Solar/Wind Harmer
1.677
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
17.979
963171AG1-166 GEN
Solar/Wind Harmer
1.264
971563AH1-280 GEN
Solar/Wind Harmer
2.529
3146926FARMVIL
Solar/Wind Harmer
0.131
971065AG2-659 GEN
Solar/Wind Harmer
8.445
316129AC1-054 GEN
Solar/Wind Harmer
0.698
970223AG2-152 GEN
Solar/Wind Harmer
12.094
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.088
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.055
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.099
941801AE2-185 GEN
Solar/Wind Harmer
4.212
270030AE2-140 GEN
Solar/Wind Harmer
13.804
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.094
316359AB2-059 GEN
Solar/Wind Harmer
0.421
316049AB1-081 GEN
Solar/Wind Harmer
0.67
3142053HEARTS
Solar/Wind Harmer
0.206
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
44.982
970099AG2-077 GEN
Solar/Wind Harmer
50.723
971741AH1-377 GEN
Solar/Wind Harmer
33.569
970301AG2-198 GEN
Solar/Wind Harmer
13.228
3146843MT LREL
Solar/Wind Harmer
0.286
3146843MT LREL
Solar/Wind Harmer
0.286
964791AG1-342 GEN
Solar/Wind Harmer
5.488
316222AC1-221 GEN
Solar/Wind Harmer
1.175
962561AG1-105 GEN
Solar/Wind Harmer
13.485
939181AE1-148 GEN
Solar/Wind Harmer
12.41
313527AB2-043 GEN
Solar/Wind Harmer
0.003
970323AG2-213 GEN
Solar/Wind Harmer
10.445
971775AH1-396 GEN
Solar/Wind Harmer
0.392
316034AC1-036 C
Solar/Wind Harmer
0.018
958211AF2-115 GEN
Solar/Wind Harmer
2.845
963191AG1-168 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.234
3147133PAMPLIN
Solar/Wind Harmer
0.187
942751AE2-291 GEN
Solar/Wind Harmer
11.476
270013AE1-250 PV
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.546
3146776BUCKING
Solar/Wind Harmer
0.044
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.276
316263AC1-034 GEN
Solar/Wind Harmer
4.449
961601AG1-000A GEN
Solar/Wind Harmer
2.035
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
970673AG2-436 GEN
Solar/Wind Harmer
149.315
970673AG2-436 GEN
Solar/Wind Harmer
99.544
971967AH1-528 GEN
Solar/Wind Harmer
95.481
970085AG2-068 GEN
Solar/Wind Harmer
31.82
970581AG2-369 GEN
Solar/Wind Harmer
27.365
3147173SINAI
Solar/Wind Harmer
0.309
3147243WELCO
Solar/Wind Harmer
0.193
316118AC1-105 GEN
Solar/Wind Harmer
0.768
970865AG2-541 GEN
Solar/Wind Harmer
9.078
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.118
3144303KENBRDG
Solar/Wind Harmer
0.196
970683AG2-441 GEN
Solar/Wind Harmer
16.053
970681AG2-440 GEN
Solar/Wind Harmer
12.842
946301AF1-294 GEN
Solar/Wind Harmer
4.678
961791AG1-021 GEN
Solar/Wind Harmer
2.276
315657AE1-056 GEN
Solar/Wind Harmer
8.085
316123AC1-075 GEN
Solar/Wind Harmer
0.315
970165AG2-112 GEN
Solar/Wind Harmer
1.87
970163AG2-111 GEN
Solar/Wind Harmer
1.784
970831AG2-522 GEN
Solar/Wind Harmer
7.35
970285AG2-188 GEN
Solar/Wind Harmer
12.402
971845AH1-439 GEN
Solar/Wind Harmer
6.507
270069AE2-166 C O1
Solar/Wind Harmer
0.004
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315
NYPJM->LTFIMP_NY
CLTF
2.382
LGEELTFEXP_LGEE->PJM
CLTF
2.675
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51192_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51192_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.25 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5708.12
MW Contribution:4.57
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
62.844
957481AF2-042 GEN
Solar/Wind Harmer
166.962
315693AD1-088 GEN
Solar/Wind Harmer
24.364
962491AG1-098 GEN
Solar/Wind Harmer
32.107
315687AD1-152 GEN
Solar/Wind Harmer
5.339
316003AC1-222 GEN
Solar/Wind Harmer
3.203
970401AG2-262 GEN
Solar/Wind Harmer
2.096
316237AB2-079_GEN
Solar/Wind Harmer
0.866
970685AG2-442 GEN
Solar/Wind Harmer
23.673
963171AG1-166 GEN
Solar/Wind Harmer
3.329
971563AH1-280 GEN
Solar/Wind Harmer
3.329
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.119
316129AC1-054 GEN
Solar/Wind Harmer
1.828
970223AG2-152 GEN
Solar/Wind Harmer
17.247
270016AE1-250 BESS
Solar/Wind Harmer
2.846
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.591
316322AB2-045
Solar/Wind Harmer
0.516
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.545
270030AE2-140 GEN
Solar/Wind Harmer
19.786
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.774
316049AB1-081 GEN
Solar/Wind Harmer
1.419
3142053HEARTS
Solar/Wind Harmer
0.155
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
970673AG2-436 GEN
Solar/Wind Harmer
165.209
970673AG2-436 GEN
Solar/Wind Harmer
83.65
971967AH1-528 GEN
Solar/Wind Harmer
126.052
970085AG2-068 GEN
Solar/Wind Harmer
41.896
970581AG2-369 GEN
Solar/Wind Harmer
36.031
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.3
970865AG2-541 GEN
Solar/Wind Harmer
11.953
316239AB2-077_GEN
Solar/Wind Harmer
0.866
316238AB2-078_GEN
Solar/Wind Harmer
0.866
971443AH1-215 GEN
Solar/Wind Harmer
5.422
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.136
970681AG2-440 GEN
Solar/Wind Harmer
16.909
946301AF1-294 GEN
Solar/Wind Harmer
6.825
961791AG1-021 GEN
Solar/Wind Harmer
3.329
270455AD2-022 GEN
Solar/Wind Harmer
4.714
270457AD2-023 GEN
Solar/Wind Harmer
2.39
315657AE1-056 GEN
Solar/Wind Harmer
9.877
316123AC1-075 GEN
Solar/Wind Harmer
2.797
970165AG2-112 GEN
Solar/Wind Harmer
2.462
970163AG2-111 GEN
Solar/Wind Harmer
2.349
970831AG2-522 GEN
Solar/Wind Harmer
9.678
970285AG2-188 GEN
Solar/Wind Harmer
15.412
971845AH1-439 GEN
Solar/Wind Harmer
8.567
270069AE2-166 C O1
Solar/Wind Harmer
2.422
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
59.226
970099AG2-077 GEN
Solar/Wind Harmer
66.785
971741AH1-377 GEN
Solar/Wind Harmer
44.199
970301AG2-198 GEN
Solar/Wind Harmer
17.416
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.86
316222AC1-221 GEN
Solar/Wind Harmer
3.218
962561AG1-105 GEN
Solar/Wind Harmer
17.755
939181AE1-148 GEN
Solar/Wind Harmer
16.34
313527AB2-043 GEN
Solar/Wind Harmer
4.631
970323AG2-213 GEN
Solar/Wind Harmer
13.752
971775AH1-396 GEN
Solar/Wind Harmer
1.958
316034AC1-036 C
Solar/Wind Harmer
0.51
958211AF2-115 GEN
Solar/Wind Harmer
4.162
963191AG1-168 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.11
270013AE1-250 PV
Solar/Wind Harmer
2.846
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.4
316197AC1-042 GEN
Solar/Wind Harmer
1.819
942671AE2-283 GEN
Solar/Wind Harmer
4.898
316263AC1-034 GEN
Solar/Wind Harmer
6.166
961601AG1-000A GEN
Solar/Wind Harmer
5.056
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
168.81
316478AD1-087 GEN
Solar/Wind Harmer
4.25
316486AD2-202 GEN
Solar/Wind Harmer
1.245
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
1.046
960061AF2-297 GEN
Solar/Wind Harmer
17.357
316283AC2-100 C
Solar/Wind Harmer
2.974
971683AH1-343 GEN
Solar/Wind Harmer
13.43
316131AB2-060 GEN
Solar/Wind Harmer
3.068
964241AG1-285 GEN
Solar/Wind Harmer
21.992
315785AD2-033 C
Solar/Wind Harmer
6.274
970257AG2-171 GEN
Solar/Wind Harmer
10.314
959311AF2-222 GEN
Solar/Wind Harmer
28.571
963181AG1-167 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.462
942461AE2-259 GEN
Solar/Wind Harmer
3.832
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.378
270197AD1-017 GEN1
Solar/Wind Harmer
1.68
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.844
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.545
270336AE1-100 GEN
Solar/Wind Harmer
1.569
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
5.12
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315
NYPJM->LTFIMP_NY
CLTF
2.382
LGEELTFEXP_LGEE->PJM
CLTF
2.675
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51172_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51172_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.76 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5683.44
MW Contribution:4.58
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
11.056
3151051BRUNSWICKS1
50/50
17.38
3151021BRUNSWICKG1
50/50
8.374
971451AH1-221 GEN
50/50
25.435
3151531CLOVER1
50/50
9.312
3151601KERR 3
50/50
0.538
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.8
971629AH1-314 GEN
50/50
17.875
3151561HALLBR1
50/50
0.366
970919AG2-571 GEN
Solar/Wind Harmer
21.227
970087AG2-069 GEN
Solar/Wind Harmer
62.431
957481AF2-042 GEN
Solar/Wind Harmer
166.01
315693AD1-088 GEN
Solar/Wind Harmer
24.233
962491AG1-098 GEN
Solar/Wind Harmer
31.935
315687AD1-152 GEN
Solar/Wind Harmer
5.313
316003AC1-222 GEN
Solar/Wind Harmer
3.193
970401AG2-262 GEN
Solar/Wind Harmer
2.094
316237AB2-079_GEN
Solar/Wind Harmer
0.868
970685AG2-442 GEN
Solar/Wind Harmer
23.682
963171AG1-166 GEN
Solar/Wind Harmer
3.328
971563AH1-280 GEN
Solar/Wind Harmer
3.328
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.224
316129AC1-054 GEN
Solar/Wind Harmer
1.849
970223AG2-152 GEN
Solar/Wind Harmer
17.201
270016AE1-250 BESS
Solar/Wind Harmer
2.839
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.577
316322AB2-045
Solar/Wind Harmer
0.514
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.53
270030AE2-140 GEN
Solar/Wind Harmer
19.734
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.817
316049AB1-081 GEN
Solar/Wind Harmer
1.454
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.785
316375AC2-012 GEN
Solar/Wind Helper
1.014
3145336SMITFLD
Solar/Wind Helper
1.482
316388AE2-253 GEN
Solar/Wind Helper
1.397
3146456SLIGO L269
Solar/Wind Helper
0.359
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.402
316159AE1-175 C
Solar/Wind Helper
0.529
316381AD1-082 GEN
Solar/Wind Helper
1.758
316458AB2-190 GEN2
Solar/Wind Helper
1.933
3141766HARMONY
Solar/Wind Helper
0.065
3138133OCRAN
Solar/Wind Helper
0.193
3142433PROV 92
Solar/Wind Helper
1.275
3142543TWELFTH
Solar/Wind Helper
0.029
964211AG1-282 GEN
Solar/Wind Helper
0.412
3141726DUNNSVL
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.961
3146516WINFALL
Solar/Wind Helper
0.297
316337AD2-073 GEN
Solar/Wind Helper
0.448
3142416OLDCHRC
Solar/Wind Helper
0.759
3142416OLDCHRC
Solar/Wind Helper
0.291
3143526WINTERP
Solar/Wind Helper
1.499
3143226MDLTHAN
Solar/Wind Helper
0.284
315800Z1-036_GEN1
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
315242AE2-183_GT2
50/50
11.056
315241AE2-183_GT1
50/50
10.988
972185AH1-677 GEN
50/50
39.858
3151041BRUNSWICKG3
50/50
8.374
972187AH1-678 GEN
50/50
19.217
3152661PLYWOOD A
50/50
0.67
970535AG2-341 GEN
50/50
4.577
3144293JTRSVLE
50/50
0.8
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
58.849
970099AG2-077 GEN
Solar/Wind Harmer
66.404
971741AH1-377 GEN
Solar/Wind Harmer
43.978
970301AG2-198 GEN
Solar/Wind Harmer
17.332
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.854
316222AC1-221 GEN
Solar/Wind Harmer
3.208
962561AG1-105 GEN
Solar/Wind Harmer
17.747
939181AE1-148 GEN
Solar/Wind Harmer
16.378
313527AB2-043 GEN
Solar/Wind Harmer
4.643
970323AG2-213 GEN
Solar/Wind Harmer
13.768
971775AH1-396 GEN
Solar/Wind Harmer
1.961
316034AC1-036 C
Solar/Wind Harmer
0.511
958211AF2-115 GEN
Solar/Wind Harmer
4.16
963191AG1-168 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.066
270013AE1-250 PV
Solar/Wind Harmer
2.839
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.394
316197AC1-042 GEN
Solar/Wind Harmer
1.815
942671AE2-283 GEN
Solar/Wind Harmer
4.885
316263AC1-034 GEN
Solar/Wind Harmer
6.316
961601AG1-000A GEN
Solar/Wind Harmer
5.186
316036AC1-147 C
Solar/Wind Helper
0.59
3142956BIRDNECK
Solar/Wind Helper
0.259
316316AC1-027 C
Solar/Wind Helper
0.606
316185AD1-033 GEN
Solar/Wind Helper
1.799
3145506HICKORY
Solar/Wind Helper
1.507
3145506HICKORY
Solar/Wind Helper
0.904
3145506HICKORY
Solar/Wind Helper
0.226
316236AE1-162_GEN
Solar/Wind Helper
0.498
316339AD2-160 GEN
Solar/Wind Helper
1.397
316018AA1-139 ULT2
Solar/Wind Helper
1.567
316017AA1-139 ULT1
Solar/Wind Helper
1.665
3137176SLIGO L2192
Solar/Wind Helper
1.432
3130086AYDLETT
Solar/Wind Helper
1.421
316033AB2-134 GEN
Solar/Wind Helper
1.19
315697AD1-025 GEN
Solar/Wind Helper
3.953
3146386ELIZ CT
Solar/Wind Helper
0.331
316240AF1-291 C
Solar/Wind Helper
0.444
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.318
316075AC2-137 C
Solar/Wind Helper
0.467
316077AC2-138 C
Solar/Wind Helper
0.286
316431W1029_GEN1
Solar/Wind Helper
1.225
316433W1029_GEN2
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3143526WINTERP
Solar/Wind Helper
1.499
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
966871AG1-558 GEN
Solar/Wind Helper
0.374
3144356SAPONY
Solar/Wind Helper
0.492
316468AD1-105 GEN
Solar/Wind Helper
1.305
3151031BRUNSWICKG2
50/50
8.374
970413AG2-270 GEN
50/50
40.637
3151591KERR 2
50/50
0.538
3144293JTRSVLE
50/50
0.8
970917AG2-570 GEN
Solar/Wind Harmer
167.695
316478AD1-087 GEN
Solar/Wind Harmer
4.227
316486AD2-202 GEN
Solar/Wind Harmer
1.238
970909AG2-566 GEN
Solar/Wind Harmer
3.291
316248AF1-058 C
Solar/Wind Harmer
1.043
960061AF2-297 GEN
Solar/Wind Harmer
17.305
316283AC2-100 C
Solar/Wind Harmer
2.965
971683AH1-343 GEN
Solar/Wind Harmer
13.39
316131AB2-060 GEN
Solar/Wind Harmer
3.076
964241AG1-285 GEN
Solar/Wind Harmer
22.038
315785AD2-033 C
Solar/Wind Harmer
6.282
970257AG2-171 GEN
Solar/Wind Harmer
10.326
959311AF2-222 GEN
Solar/Wind Harmer
28.597
963181AG1-167 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.449
942461AE2-259 GEN
Solar/Wind Harmer
3.824
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.375
270197AD1-017 GEN1
Solar/Wind Harmer
1.676
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.834
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.53
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.564
961601AG1-000A GEN
Solar/Wind Harmer
5.252
315773AC2-141 GEN
Solar/Wind Helper
9.163
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.058
3145336SMITFLD
Solar/Wind Helper
0.148
3146456SLIGO L269
Solar/Wind Helper
0.359
316382AG1-145 C
Solar/Wind Helper
0.469
315839AE2-212 C
Solar/Wind Helper
0.457
316320Y1-086
Solar/Wind Helper
0.148
316156AD2-030 GEN
Solar/Wind Helper
0.492
316280AD1-041 GEN
Solar/Wind Helper
1.092
3142946ENON
Solar/Wind Helper
0.105
316484AD2-074 GEN
Solar/Wind Helper
0.607
316404AE1-155 C
Solar/Wind Helper
2.624
316435W1029_GEN3
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3141906WESTMOR
Solar/Wind Helper
0.115
3146626S HERTFORD
Solar/Wind Helper
0.28
316473AC1-191 GEN
Solar/Wind Helper
1.696
3145273HOLLAND
Solar/Wind Helper
0.188
966881AG1-559 GEN
Solar/Wind Helper
0.329
3146376EDENTON
Solar/Wind Helper
0.226
315244AE2-183_ST
50/50
19.115
963041AG1-153 GEN
50/50
16.957
3151541CLOVER2
50/50
9.268
3151611KERR 4
50/50
0.538
3151621KERR 5
50/50
0.538
3151631KERR 6
50/50
0.538
3151641KERR 7
50/50
0.538
970673AG2-436 GEN
Solar/Wind Harmer
164.043
970673AG2-436 GEN
Solar/Wind Harmer
83.06
971967AH1-528 GEN
Solar/Wind Harmer
125.223
970085AG2-068 GEN
Solar/Wind Harmer
41.62
970581AG2-369 GEN
Solar/Wind Harmer
35.794
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.295
970865AG2-541 GEN
Solar/Wind Harmer
11.917
316239AB2-077_GEN
Solar/Wind Harmer
0.868
316238AB2-078_GEN
Solar/Wind Harmer
0.868
971443AH1-215 GEN
Solar/Wind Harmer
5.428
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.145
970681AG2-440 GEN
Solar/Wind Harmer
16.916
946301AF1-294 GEN
Solar/Wind Harmer
6.823
961791AG1-021 GEN
Solar/Wind Harmer
3.328
270455AD2-022 GEN
Solar/Wind Harmer
4.701
270457AD2-023 GEN
Solar/Wind Harmer
2.384
315657AE1-056 GEN
Solar/Wind Harmer
9.869
316123AC1-075 GEN
Solar/Wind Harmer
2.789
970165AG2-112 GEN
Solar/Wind Harmer
2.455
970163AG2-111 GEN
Solar/Wind Harmer
2.342
970831AG2-522 GEN
Solar/Wind Harmer
9.813
970285AG2-188 GEN
Solar/Wind Harmer
15.354
971845AH1-439 GEN
Solar/Wind Harmer
8.535
270069AE2-166 C O1
Solar/Wind Harmer
2.415
319010AE1-072 C
Solar/Wind Helper
4.079
3143316POE
Solar/Wind Helper
1.407
316305AF2-043 C
Solar/Wind Helper
0.473
316369SG1_INVT
Solar/Wind Helper
1.664
957831AF2-077 GEN
Solar/Wind Helper
0.466
316132AB2-190 GEN1
Solar/Wind Helper
1.933
316349AD2-085 GEN
Solar/Wind Helper
1.523
313526AB2-022
Solar/Wind Helper
0.505
957601AF2-054 GEN
Solar/Wind Helper
0.438
3141873WAN 176
Solar/Wind Helper
0.065
315662AE1-191 GEN
Solar/Wind Helper
1.747
315666AE1-190 GEN
Solar/Wind Helper
0.437
316059AD1-063 C
Solar/Wind Helper
0.326
3141913WHIT STONE
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3138133OCRAN
Solar/Wind Helper
0.097
3143873LANEXA
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.128
316321Z2-027
Solar/Wind Helper
0.487
3145176PASQUOTANK
Solar/Wind Helper
0.198
3141813NORNECK
Solar/Wind Helper
0.304
316312AB1-027
Solar/Wind Helper
0.556
316233AE1-074 FULL
Solar/Wind Helper
0.44
316223AC1-118
Solar/Wind Helper
0.438
316315AB2-025 C
Solar/Wind Helper
0.418
315611Z1-036_GEN2
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
3130156CHOWAN
Solar/Wind Helper
0.226
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.554
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.081
MECLTFEXP_MEC->PJM
CLTF
7.343
SIGELTFEXP_SIGE->PJM
CLTF
0.22
CPLELTFEXP_CPLE->PJM
CLTF
19.708
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.004
LAGNLTFEXP_LAGN->PJM
CLTF
14.626
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.161
TVALTFEXP_TVA->PJM
CLTF
7.294
NYPJM->LTFIMP_NY
CLTF
2.38
LGEELTFEXP_LGEE->PJM
CLTF
2.666
WECLTFEXP_WEC->PJM
CLTF
1.395
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 511T544_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T544_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.13 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5601.8
MW Contribution:4.52
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
10.962
3151051BRUNSWICKS1
50/50
17.232
3151021BRUNSWICKG1
50/50
8.303
971451AH1-221 GEN
50/50
25.218
3151531CLOVER1
50/50
9.227
3151601KERR 3
50/50
0.532
3151581KERR 1
50/50
0.19
3144293JTRSVLE
50/50
0.79
971629AH1-314 GEN
50/50
17.731
3151561HALLBR1
50/50
0.363
970919AG2-571 GEN
Solar/Wind Harmer
21.047
970087AG2-069 GEN
Solar/Wind Harmer
61.902
957481AF2-042 GEN
Solar/Wind Harmer
164.509
315693AD1-088 GEN
Solar/Wind Harmer
24.007
962491AG1-098 GEN
Solar/Wind Harmer
31.634
315687AD1-152 GEN
Solar/Wind Harmer
5.265
316003AC1-222 GEN
Solar/Wind Harmer
3.162
970401AG2-262 GEN
Solar/Wind Harmer
2.07
316237AB2-079_GEN
Solar/Wind Harmer
0.856
970685AG2-442 GEN
Solar/Wind Harmer
23.354
963171AG1-166 GEN
Solar/Wind Harmer
3.283
971563AH1-280 GEN
Solar/Wind Harmer
3.283
3146926FARMVIL
Solar/Wind Harmer
-0.014
971065AG2-659 GEN
Solar/Wind Harmer
11.094
316129AC1-054 GEN
Solar/Wind Harmer
1.827
970223AG2-152 GEN
Solar/Wind Harmer
17.059
270016AE1-250 BESS
Solar/Wind Harmer
2.815
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.528
316322AB2-045
Solar/Wind Harmer
0.506
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.477
270030AE2-140 GEN
Solar/Wind Harmer
19.567
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.809
316049AB1-081 GEN
Solar/Wind Harmer
1.448
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.244
316381AD1-082 GEN
Solar/Wind Helper
1.747
316375AC2-012 GEN
Solar/Wind Helper
0.879
3145336SMITFLD
Solar/Wind Helper
1.331
316458AB2-190 GEN2
Solar/Wind Helper
1.893
316159AE1-175 C
Solar/Wind Helper
0.497
316388AE2-253 GEN
Solar/Wind Helper
1.201
3142433PROV 92
Solar/Wind Helper
1.254
3142543TWELFTH
Solar/Wind Helper
0.03
3141766HARMONY
Solar/Wind Helper
0.062
3146456SLIGO L269
Solar/Wind Helper
0.308
3138133OCRAN
Solar/Wind Helper
0.185
316072AD1-144
Solar/Wind Helper
0.35
316246AF1-032 C
Solar/Wind Helper
0.342
964211AG1-282 GEN
Solar/Wind Helper
0.397
3141726DUNNSVL
Solar/Wind Helper
1.179
3143526WINTERP
Solar/Wind Helper
1.519
3142416OLDCHRC
Solar/Wind Helper
0.752
3143226MDLTHAN
Solar/Wind Helper
0.289
3142416OLDCHRC
Solar/Wind Helper
0.288
316337AD2-073 GEN
Solar/Wind Helper
0.434
3146516WINFALL
Solar/Wind Helper
0.813
3146516WINFALL
Solar/Wind Helper
0.251
315242AE2-183_GT2
50/50
10.962
315241AE2-183_GT1
50/50
10.894
972185AH1-677 GEN
50/50
39.518
3151041BRUNSWICKG3
50/50
8.303
972187AH1-678 GEN
50/50
19.053
3152661PLYWOOD A
50/50
0.663
970535AG2-341 GEN
50/50
4.519
3144293JTRSVLE
50/50
0.79
3144293JTRSVLE
50/50
0.665
970933AG2-581 GEN
Solar/Wind Harmer
58.334
970099AG2-077 GEN
Solar/Wind Harmer
65.804
971741AH1-377 GEN
Solar/Wind Harmer
43.523
970301AG2-198 GEN
Solar/Wind Harmer
17.145
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.775
316222AC1-221 GEN
Solar/Wind Harmer
3.182
962561AG1-105 GEN
Solar/Wind Harmer
17.536
939181AE1-148 GEN
Solar/Wind Harmer
16.186
313527AB2-043 GEN
Solar/Wind Harmer
4.576
970323AG2-213 GEN
Solar/Wind Harmer
13.574
971775AH1-396 GEN
Solar/Wind Harmer
1.933
316034AC1-036 C
Solar/Wind Harmer
0.503
958211AF2-115 GEN
Solar/Wind Harmer
4.103
963191AG1-168 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
14.918
270013AE1-250 PV
Solar/Wind Harmer
2.815
3146776BUCKING
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.37
316197AC1-042 GEN
Solar/Wind Harmer
1.797
942671AE2-283 GEN
Solar/Wind Harmer
4.838
316263AC1-034 GEN
Solar/Wind Harmer
6.29
961601AG1-000A GEN
Solar/Wind Harmer
5.16
316240AF1-291 C
Solar/Wind Helper
0.471
316036AC1-147 C
Solar/Wind Helper
0.511
316236AE1-162_GEN
Solar/Wind Helper
0.447
316316AC1-027 C
Solar/Wind Helper
0.524
3142956BIRDNECK
Solar/Wind Helper
0.223
316033AB2-134 GEN
Solar/Wind Helper
1.137
315697AD1-025 GEN
Solar/Wind Helper
3.779
316185AD1-033 GEN
Solar/Wind Helper
1.551
3145506HICKORY
Solar/Wind Helper
1.298
3145506HICKORY
Solar/Wind Helper
0.779
3145506HICKORY
Solar/Wind Helper
0.195
3144356SAPONY
Solar/Wind Helper
0.581
316339AD2-160 GEN
Solar/Wind Helper
1.201
316018AA1-139 ULT2
Solar/Wind Helper
1.346
316017AA1-139 ULT1
Solar/Wind Helper
1.43
3142946ENON
Solar/Wind Helper
0.031
3137176SLIGO L2192
Solar/Wind Helper
1.229
3130086AYDLETT
Solar/Wind Helper
1.219
316487AF1-042 GEN
Solar/Wind Helper
0.305
316075AC2-137 C
Solar/Wind Helper
0.459
316077AC2-138 C
Solar/Wind Helper
0.276
3143526WINTERP
Solar/Wind Helper
1.519
3146386ELIZ CT
Solar/Wind Helper
0.283
966871AG1-558 GEN
Solar/Wind Helper
0.376
316468AD1-105 GEN
Solar/Wind Helper
1.308
316431W1029_GEN1
Solar/Wind Helper
1.037
316433W1029_GEN2
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146626S HERTFORD
Solar/Wind Helper
0.236
3146626S HERTFORD
Solar/Wind Helper
0.236
3151031BRUNSWICKG2
50/50
8.303
970413AG2-270 GEN
50/50
40.265
3151591KERR 2
50/50
0.532
3144293JTRSVLE
50/50
0.79
970917AG2-570 GEN
Solar/Wind Harmer
166.275
316478AD1-087 GEN
Solar/Wind Harmer
4.189
316486AD2-202 GEN
Solar/Wind Harmer
1.227
970909AG2-566 GEN
Solar/Wind Harmer
3.255
316248AF1-058 C
Solar/Wind Harmer
1.033
960061AF2-297 GEN
Solar/Wind Harmer
17.135
316283AC2-100 C
Solar/Wind Harmer
2.94
971683AH1-343 GEN
Solar/Wind Harmer
13.259
316131AB2-060 GEN
Solar/Wind Harmer
3.032
964241AG1-285 GEN
Solar/Wind Harmer
21.724
315785AD2-033 C
Solar/Wind Harmer
6.194
970257AG2-171 GEN
Solar/Wind Harmer
10.181
959311AF2-222 GEN
Solar/Wind Harmer
28.197
963181AG1-167 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.081
971193AH1-056 GEN
Solar/Wind Harmer
16.225
942461AE2-259 GEN
Solar/Wind Harmer
3.773
3146926FARMVIL
Solar/Wind Harmer
-0.014
270018AE2-047 C O1
Solar/Wind Harmer
1.363
270197AD1-017 GEN1
Solar/Wind Harmer
1.661
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.802
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.477
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.551
961601AG1-000A GEN
Solar/Wind Harmer
5.225
315773AC2-141 GEN
Solar/Wind Helper
8.525
315839AE2-212 C
Solar/Wind Helper
0.497
3144536CHRHLND
Solar/Wind Helper
0.05
3144873MCLAUGH
Solar/Wind Helper
0.008
3145336SMITFLD
Solar/Wind Helper
0.133
316382AG1-145 C
Solar/Wind Helper
0.441
316156AD2-030 GEN
Solar/Wind Helper
0.47
3142946ENON
Solar/Wind Helper
0.104
316280AD1-041 GEN
Solar/Wind Helper
1.046
3146456SLIGO L269
Solar/Wind Helper
0.308
316484AD2-074 GEN
Solar/Wind Helper
0.583
316404AE1-155 C
Solar/Wind Helper
2.523
316320Y1-086
Solar/Wind Helper
0.126
316473AC1-191 GEN
Solar/Wind Helper
1.704
3141906WESTMOR
Solar/Wind Helper
0.111
316435W1029_GEN3
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
966881AG1-559 GEN
Solar/Wind Helper
0.328
3146626S HERTFORD
Solar/Wind Helper
0.236
315244AE2-183_ST
50/50
18.952
963041AG1-153 GEN
50/50
16.812
3151541CLOVER2
50/50
9.183
3151611KERR 4
50/50
0.532
3151621KERR 5
50/50
0.532
3151631KERR 6
50/50
0.532
3151641KERR 7
50/50
0.532
970673AG2-436 GEN
Solar/Wind Harmer
162.646
970673AG2-436 GEN
Solar/Wind Harmer
82.352
971967AH1-528 GEN
Solar/Wind Harmer
124.141
970085AG2-068 GEN
Solar/Wind Harmer
41.268
970581AG2-369 GEN
Solar/Wind Harmer
35.491
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.271
970865AG2-541 GEN
Solar/Wind Harmer
11.801
316239AB2-077_GEN
Solar/Wind Harmer
0.856
316238AB2-078_GEN
Solar/Wind Harmer
0.856
971443AH1-215 GEN
Solar/Wind Harmer
5.352
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
20.851
970681AG2-440 GEN
Solar/Wind Harmer
16.681
946301AF1-294 GEN
Solar/Wind Harmer
6.73
961791AG1-021 GEN
Solar/Wind Harmer
3.283
270455AD2-022 GEN
Solar/Wind Harmer
4.664
270457AD2-023 GEN
Solar/Wind Harmer
2.365
315657AE1-056 GEN
Solar/Wind Harmer
9.735
316123AC1-075 GEN
Solar/Wind Harmer
2.761
970165AG2-112 GEN
Solar/Wind Harmer
2.431
970163AG2-111 GEN
Solar/Wind Harmer
2.319
970831AG2-522 GEN
Solar/Wind Harmer
9.696
970285AG2-188 GEN
Solar/Wind Harmer
15.118
971845AH1-439 GEN
Solar/Wind Harmer
8.397
270069AE2-166 C O1
Solar/Wind Harmer
2.394
3143316POE
Solar/Wind Helper
1.57
316132AB2-190 GEN1
Solar/Wind Helper
1.893
316369SG1_INVT
Solar/Wind Helper
1.59
957831AF2-077 GEN
Solar/Wind Helper
0.437
316315AB2-025 C
Solar/Wind Helper
0.494
957601AF2-054 GEN
Solar/Wind Helper
0.418
3141873WAN 176
Solar/Wind Helper
0.062
315662AE1-191 GEN
Solar/Wind Helper
1.674
315666AE1-190 GEN
Solar/Wind Helper
0.419
3143873LANEXA
Solar/Wind Helper
0.186
316059AD1-063 C
Solar/Wind Helper
0.312
3141913WHIT STONE
Solar/Wind Helper
0.309
3138133OCRAN
Solar/Wind Helper
0.093
3141783LANCAST
Solar/Wind Helper
0.184
3141783LANCAST
Solar/Wind Helper
0.123
319010AE1-072 C
Solar/Wind Helper
3.5
316349AD2-085 GEN
Solar/Wind Helper
1.396
316305AF2-043 C
Solar/Wind Helper
0.402
3141813NORNECK
Solar/Wind Helper
0.293
316233AE1-074 FULL
Solar/Wind Helper
0.446
316312AB1-027
Solar/Wind Helper
0.55
313526AB2-022
Solar/Wind Helper
0.431
316223AC1-118
Solar/Wind Helper
0.424
3146486SUNBURY
Solar/Wind Helper
0.274
3146486SUNBURY
Solar/Wind Helper
0.274
316321Z2-027
Solar/Wind Helper
0.414
3145176PASQUOTANK
Solar/Wind Helper
0.168
CBM West 1LTFEXP_CBM-W1->PJM
CBM
48.979
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.858
MECLTFEXP_MEC->PJM
CLTF
7.267
SIGELTFEXP_SIGE->PJM
CLTF
0.218
CPLELTFEXP_CPLE->PJM
CLTF
19.58
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.279
LAGNLTFEXP_LAGN->PJM
CLTF
14.499
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.842
TVALTFEXP_TVA->PJM
CLTF
7.231
NYPJM->LTFIMP_NY
CLTF
2.38
LGEELTFEXP_LGEE->PJM
CLTF
2.637
WECLTFEXP_WEC->PJM
CLTF
1.38
AG2-052LTFEXP_AG2-052->PJM
LTF
0.074
AH1-155LTFEXP_AH1-155->PJM
LTF
0.111

Details for AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.8 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:983.47
MW Contribution:1.3
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.618
3144293JTRSVLE
50/50
0.52
970535AG2-341 GEN
50/50
1.297
971489AH1-241 GEN
Solar/Wind Harmer
23.308
3146776BUCKING
Solar/Wind Harmer
1.512
3146776BUCKING
Solar/Wind Harmer
0.122
315821AE2-092 GEN
Solar/Wind Harmer
0.018
970301AG2-198 GEN
Solar/Wind Harmer
8.441
3147133PAMPLIN
Solar/Wind Harmer
0.197
3147133PAMPLIN
Solar/Wind Harmer
0.158
958211AF2-115 GEN
Solar/Wind Harmer
2.196
963191AG1-168 GEN
Solar/Wind Harmer
0.732
971741AH1-377 GEN
Solar/Wind Harmer
16.934
316034AC1-036 C
Solar/Wind Harmer
0.01
970323AG2-213 GEN
Solar/Wind Harmer
5.97
971775AH1-396 GEN
Solar/Wind Harmer
0.224
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.408
964791AG1-342 GEN
Solar/Wind Harmer
1.297
3146843MT LREL
Solar/Wind Harmer
0.067
3146843MT LREL
Solar/Wind Harmer
0.067
939181AE1-148 GEN
Solar/Wind Harmer
3.054
3143526WINTERP
Solar/Wind Helper
0.904
3151921BEARGRDN G2
50/50
4.57
3144293JTRSVLE
50/50
0.618
966251AG1-494 GEN
50/50
1.545
3151591KERR 2
50/50
0.12
970221AG2-151 GEN
Solar/Wind Harmer
23.308
3146776BUCKING
Solar/Wind Harmer
0.136
3146926FARMVIL
Solar/Wind Harmer
0.171
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
2.11
3147133PAMPLIN
Solar/Wind Harmer
0.62
971193AH1-056 GEN
Solar/Wind Harmer
12.029
963181AG1-167 GEN
Solar/Wind Harmer
0.732
959311AF2-222 GEN
Solar/Wind Harmer
13.003
958131AF2-107 GEN
Solar/Wind Harmer
4.145
970257AG2-171 GEN
Solar/Wind Harmer
4.477
315785AD2-033 C
Solar/Wind Harmer
1.066
964241AG1-285 GEN
Solar/Wind Harmer
7.188
316131AB2-060 GEN
Solar/Wind Harmer
0.295
316313AB2-026
Solar/Wind Helper
0.958
316258AE1-075 C
Solar/Wind Helper
0.862
316405AF2-144 C
Solar/Wind Helper
0.719
3151931BEARGRDN S1
50/50
5.898
3151911BEARGRDN G1
50/50
4.57
3144293JTRSVLE
50/50
0.618
3151601KERR 3
50/50
0.12
3151581KERR 1
50/50
0.043
970937AG2-583 GEN
Solar/Wind Harmer
37.481
972003AH1-546 GEN
Solar/Wind Harmer
20.008
971377AH1-170 GEN
Solar/Wind Harmer
4.662
3147623JAMES R
Solar/Wind Harmer
1.013
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.151
3146926FARMVIL
Solar/Wind Harmer
0.171
963171AG1-166 GEN
Solar/Wind Harmer
0.976
971563AH1-280 GEN
Solar/Wind Harmer
1.952
970685AG2-442 GEN
Solar/Wind Harmer
12.103
316237AB2-079_GEN
Solar/Wind Harmer
0.001
962491AG1-098 GEN
Solar/Wind Harmer
4.891
315693AD1-088 GEN
Solar/Wind Harmer
3.821
970401AG2-262 GEN
Solar/Wind Harmer
0.396
962751AG1-124 GEN
Solar/Wind Harmer
2.983
316336AC2-165 C
Solar/Wind Helper
3.978
3143226MDLTHAN
Solar/Wind Helper
0.214
3143526WINTERP
Solar/Wind Helper
0.904
972205AH1-687 GEN
50/50
22.289
3151611KERR 4
50/50
0.12
3151621KERR 5
50/50
0.12
3151631KERR 6
50/50
0.12
3151641KERR 7
50/50
0.12
971447AH1-217 GEN
Solar/Wind Harmer
12.416
971845AH1-439 GEN
Solar/Wind Harmer
16.793
970285AG2-188 GEN
Solar/Wind Harmer
28.117
270494AE1-108_GEN
Solar/Wind Harmer
4.14
315657AE1-056 GEN
Solar/Wind Harmer
6.813
946301AF1-294 GEN
Solar/Wind Harmer
3.611
961791AG1-021 GEN
Solar/Wind Harmer
1.757
970683AG2-441 GEN
Solar/Wind Harmer
10.806
970681AG2-440 GEN
Solar/Wind Harmer
8.645
3144303KENBRDG
Solar/Wind Harmer
0.112
971443AH1-215 GEN
Solar/Wind Harmer
2.318
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.153
316233AE1-074 FULL
Solar/Wind Helper
0.266
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.841
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.476
MECLTFEXP_MEC->PJM
CLTF
0.813
SIGELTFEXP_SIGE->PJM
CLTF
0.026
CPLELTFEXP_CPLE->PJM
CLTF
1.292
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.85
LAGNLTFEXP_LAGN->PJM
CLTF
1.363
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.179
TVALTFEXP_TVA->PJM
CLTF
0.699
NYPJM->LTFIMP_NY
CLTF
0.404
LGEELTFEXP_LGEE->PJM
CLTF
0.328
WECLTFEXP_WEC->PJM
CLTF
0.165

Details for AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-583 TP-6CARTERV 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.99 %
Rating:800.88 MVA
Rating Type:B
MVA to Mitigate:969.01
MW Contribution:1.35
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
3.828
3151911BEARGRDN G1
50/50
2.966
3144293JTRSVLE
50/50
0.503
3151531CLOVER1
50/50
2.188
3151601KERR 3
50/50
0.135
3151581KERR 1
50/50
0.048
970937AG2-583 GEN
Solar/Wind Harmer
28.699
972003AH1-546 GEN
Solar/Wind Harmer
13.118
971377AH1-170 GEN
Solar/Wind Harmer
3.027
3147623JAMES R
Solar/Wind Harmer
0.658
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.105
3146926FARMVIL
Solar/Wind Harmer
0.129
963171AG1-166 GEN
Solar/Wind Harmer
0.794
971563AH1-280 GEN
Solar/Wind Harmer
1.587
970685AG2-442 GEN
Solar/Wind Harmer
10.089
962491AG1-098 GEN
Solar/Wind Harmer
7.03
315693AD1-088 GEN
Solar/Wind Harmer
5.777
957481AF2-042 GEN
Solar/Wind Harmer
29.163
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315687AD1-152 GEN
Solar/Wind Harmer
0.003
3144293JTRSVLE
50/50
0.503
3144293JTRSVLE
50/50
0.423
970535AG2-341 GEN
50/50
1.349
3152661PLYWOOD A
50/50
0.157
971489AH1-241 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
1.049
3146776BUCKING
Solar/Wind Harmer
0.085
315821AE2-092 GEN
Solar/Wind Harmer
0.013
970301AG2-198 GEN
Solar/Wind Harmer
7.476
971741AH1-377 GEN
Solar/Wind Harmer
16.133
3147133PAMPLIN
Solar/Wind Harmer
0.158
3147133PAMPLIN
Solar/Wind Harmer
0.127
958211AF2-115 GEN
Solar/Wind Harmer
1.786
963191AG1-168 GEN
Solar/Wind Harmer
0.595
316034AC1-036 C
Solar/Wind Harmer
0.009
970323AG2-213 GEN
Solar/Wind Harmer
5.145
971775AH1-396 GEN
Solar/Wind Harmer
0.193
970099AG2-077 GEN
Solar/Wind Harmer
11.665
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.768
964791AG1-342 GEN
Solar/Wind Harmer
1.475
3146843MT LREL
Solar/Wind Harmer
0.077
3146843MT LREL
Solar/Wind Harmer
0.077
939181AE1-148 GEN
Solar/Wind Harmer
3.325
3143526WINTERP
Solar/Wind Helper
1.294
316240AF1-291 C
Solar/Wind Helper
0.162
3142946ENON
Solar/Wind Helper
0.012
966871AG1-558 GEN
Solar/Wind Helper
0.156
316075AC2-137 C
Solar/Wind Helper
0.172
3151921BEARGRDN G2
50/50
2.966
3144293JTRSVLE
50/50
0.503
970413AG2-270 GEN
50/50
9.546
966251AG1-494 GEN
50/50
1.198
3151591KERR 2
50/50
0.135
970221AG2-151 GEN
Solar/Wind Harmer
15.135
3146776BUCKING
Solar/Wind Harmer
0.094
3146926FARMVIL
Solar/Wind Harmer
0.129
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970909AG2-566 GEN
Solar/Wind Harmer
1.869
3147133PAMPLIN
Solar/Wind Harmer
0.497
971193AH1-056 GEN
Solar/Wind Harmer
9.642
963181AG1-167 GEN
Solar/Wind Harmer
0.595
959311AF2-222 GEN
Solar/Wind Harmer
11.09
970257AG2-171 GEN
Solar/Wind Harmer
3.859
315785AD2-033 C
Solar/Wind Harmer
0.934
958131AF2-107 GEN
Solar/Wind Harmer
2.955
316478AD1-087 GEN
Solar/Wind Harmer
0.356
316486AD2-202 GEN
Solar/Wind Harmer
0.105
964241AG1-285 GEN
Solar/Wind Harmer
6.636
316131AB2-060 GEN
Solar/Wind Harmer
0.284
3148013FISHERV
Solar/Wind Harmer
0.071
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.932
971683AH1-343 GEN
Solar/Wind Harmer
2.348
316313AB2-026
Solar/Wind Helper
1.245
316258AE1-075 C
Solar/Wind Helper
1.12
316405AF2-144 C
Solar/Wind Helper
0.933
3142946ENON
Solar/Wind Helper
0.04
316473AC1-191 GEN
Solar/Wind Helper
0.709
315839AE2-212 C
Solar/Wind Helper
0.155
970401AG2-262 GEN
Solar/Wind Harmer
0.451
316003AC1-222 GEN
Solar/Wind Harmer
0.002
316336AC2-165 C
Solar/Wind Helper
5.135
3143226MDLTHAN
Solar/Wind Helper
0.3
3143526WINTERP
Solar/Wind Helper
1.294
3142543TWELFTH
Solar/Wind Helper
0.014
3142416OLDCHRC
Solar/Wind Helper
0.296
3142416OLDCHRC
Solar/Wind Helper
0.113
316458AB2-190 GEN2
Solar/Wind Helper
0.639
972205AH1-687 GEN
50/50
14.467
3151541CLOVER2
50/50
2.177
3151611KERR 4
50/50
0.135
3151621KERR 5
50/50
0.135
3151631KERR 6
50/50
0.135
3151641KERR 7
50/50
0.135
971447AH1-217 GEN
Solar/Wind Harmer
8.145
971845AH1-439 GEN
Solar/Wind Harmer
11.716
970285AG2-188 GEN
Solar/Wind Harmer
19.851
270494AE1-108_GEN
Solar/Wind Harmer
2.723
315657AE1-056 GEN
Solar/Wind Harmer
5.462
946301AF1-294 GEN
Solar/Wind Harmer
2.936
961791AG1-021 GEN
Solar/Wind Harmer
1.429
970683AG2-441 GEN
Solar/Wind Harmer
9.008
970681AG2-440 GEN
Solar/Wind Harmer
7.206
3144303KENBRDG
Solar/Wind Harmer
0.096
971443AH1-215 GEN
Solar/Wind Harmer
2.005
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.188
3148133STUARTS
Solar/Wind Harmer
0.042
3148013FISHERV
Solar/Wind Harmer
0.041
3147173SINAI
Solar/Wind Harmer
0.069
3147243WELCO
Solar/Wind Harmer
0.043
970865AG2-541 GEN
Solar/Wind Harmer
2.13
316123AC1-075 GEN
Solar/Wind Harmer
0.077
970165AG2-112 GEN
Solar/Wind Harmer
0.459
970163AG2-111 GEN
Solar/Wind Harmer
0.438
316233AE1-074 FULL
Solar/Wind Helper
0.38
316312AB1-027
Solar/Wind Helper
0.217
316132AB2-190 GEN1
Solar/Wind Helper
0.639
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.581
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
1.069
SIGELTFEXP_SIGE->PJM
CLTF
0.035
CPLELTFEXP_CPLE->PJM
CLTF
0.611
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.053
LAGNLTFEXP_LAGN->PJM
CLTF
1.406
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.04
TVALTFEXP_TVA->PJM
CLTF
0.731
NYPJM->LTFIMP_NY
CLTF
0.331
LGEELTFEXP_LGEE->PJM
CLTF
0.459
WECLTFEXP_WEC->PJM
CLTF
0.235

Details for AH1-377 TP-AG1-098 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 211122_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-377 TP-AG1-098 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 211122_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.18 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:770.15
MW Contribution:2.1
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.776
316322AB2-045
Solar/Wind Harmer
3.419
3146926FARMVIL
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.04
972003AH1-546 GEN
Solar/Wind Harmer
50.704
963171AG1-166 GEN
Solar/Wind Harmer
7.386
971563AH1-280 GEN
Solar/Wind Harmer
7.386
970685AG2-442 GEN
Solar/Wind Harmer
44.081
316237AB2-079_GEN
Solar/Wind Harmer
0.579
970401AG2-262 GEN
Solar/Wind Harmer
0.702
3147043LAWRENC
Adder
0.748
971795AH1-408 GEN
Solar/Wind Harmer
5.817
970285AG2-188 GEN
Solar/Wind Harmer
88.955
971845AH1-439 GEN
Solar/Wind Harmer
54.008
315657AE1-056 GEN
Solar/Wind Harmer
24.435
946301AF1-294 GEN
Solar/Wind Harmer
15.141
961791AG1-021 GEN
Solar/Wind Harmer
7.386
970683AG2-441 GEN
Solar/Wind Harmer
39.358
970681AG2-440 GEN
Solar/Wind Harmer
31.486
3144303KENBRDG
Solar/Wind Harmer
-0.033
971443AH1-215 GEN
Solar/Wind Harmer
7.941
316239AB2-077_GEN
Solar/Wind Harmer
0.579
316238AB2-078_GEN
Solar/Wind Harmer
0.579
316118AC1-105 GEN
Solar/Wind Harmer
0.497
3144293JTRSVLE
50/50
1.776
3144293JTRSVLE
50/50
1.496
970535AG2-341 GEN
50/50
2.1
971741AH1-377 GEN
Solar/Wind Harmer
131.224
970301AG2-198 GEN
Solar/Wind Harmer
55.111
3146776BUCKING
Solar/Wind Harmer
-0.405
3146776BUCKING
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.065
3147133PAMPLIN
Solar/Wind Harmer
-0.052
958211AF2-115 GEN
Solar/Wind Harmer
9.232
963191AG1-168 GEN
Solar/Wind Harmer
5.539
316034AC1-036 C
Solar/Wind Harmer
0.765
970323AG2-213 GEN
Solar/Wind Harmer
20.566
971775AH1-396 GEN
Solar/Wind Harmer
2.929
313527AB2-043 GEN
Solar/Wind Harmer
3.315
962561AG1-105 GEN
Solar/Wind Harmer
6.878
964791AG1-342 GEN
Solar/Wind Harmer
2.297
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
939181AE1-148 GEN
Solar/Wind Harmer
5.28
3144293JTRSVLE
50/50
1.776
970909AG2-566 GEN
Solar/Wind Harmer
10.464
3146926FARMVIL
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.036
942461AE2-259 GEN
Solar/Wind Harmer
12.382
3147133PAMPLIN
Solar/Wind Harmer
-0.204
971193AH1-056 GEN
Solar/Wind Harmer
40.725
963181AG1-167 GEN
Solar/Wind Harmer
5.539
959311AF2-222 GEN
Solar/Wind Harmer
45.705
970257AG2-171 GEN
Solar/Wind Harmer
15.425
315785AD2-033 C
Solar/Wind Harmer
8.494
964241AG1-285 GEN
Solar/Wind Harmer
21.682
316131AB2-060 GEN
Solar/Wind Harmer
2.357
3147043LAWRENC
Solar/Wind Harmer
-0.006
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.057
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.173
MECLTFEXP_MEC->PJM
CLTF
0.029
SIGELTFEXP_SIGE->PJM
CLTF
0.001
CPLELTFEXP_CPLE->PJM
CLTF
0.247
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.466
LAGNLTFEXP_LAGN->PJM
CLTF
0.104
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.452
TVALTFEXP_TVA->PJM
CLTF
0.053
NYPJM->LTFIMP_NY
CLTF
0.076
LGEELTFEXP_LGEE->PJM
CLTF
0.009
WECLTFEXP_WEC->PJM
CLTF
0.003

Details for AH1-377 TP-AG1-098 TP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-377 TP-AG1-098 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: BREMO B1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:110.18 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:770.15
MW Contribution:2.1
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.776
3144293JTRSVLE
50/50
1.496
970535AG2-341 GEN
50/50
2.1
971741AH1-377 GEN
Solar/Wind Harmer
131.224
970301AG2-198 GEN
Solar/Wind Harmer
55.111
3146776BUCKING
Solar/Wind Harmer
-0.405
3146776BUCKING
Solar/Wind Harmer
-0.033
3147133PAMPLIN
Solar/Wind Harmer
-0.065
3147133PAMPLIN
Solar/Wind Harmer
-0.052
958211AF2-115 GEN
Solar/Wind Harmer
9.232
963191AG1-168 GEN
Solar/Wind Harmer
5.539
316034AC1-036 C
Solar/Wind Harmer
0.765
970323AG2-213 GEN
Solar/Wind Harmer
20.566
971775AH1-396 GEN
Solar/Wind Harmer
2.929
313527AB2-043 GEN
Solar/Wind Harmer
3.315
962561AG1-105 GEN
Solar/Wind Harmer
6.878
964791AG1-342 GEN
Solar/Wind Harmer
2.297
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
939181AE1-148 GEN
Solar/Wind Harmer
5.28
970285AG2-188 GEN
Solar/Wind Harmer
88.955
971845AH1-439 GEN
Solar/Wind Harmer
54.008
315657AE1-056 GEN
Solar/Wind Harmer
24.435
946301AF1-294 GEN
Solar/Wind Harmer
15.141
961791AG1-021 GEN
Solar/Wind Harmer
7.386
970683AG2-441 GEN
Solar/Wind Harmer
39.358
970681AG2-440 GEN
Solar/Wind Harmer
31.486
3144303KENBRDG
Solar/Wind Harmer
-0.033
971443AH1-215 GEN
Solar/Wind Harmer
7.941
316239AB2-077_GEN
Solar/Wind Harmer
0.579
316238AB2-078_GEN
Solar/Wind Harmer
0.579
316118AC1-105 GEN
Solar/Wind Harmer
0.497
3144293JTRSVLE
50/50
1.776
970909AG2-566 GEN
Solar/Wind Harmer
10.464
3146926FARMVIL
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.036
942461AE2-259 GEN
Solar/Wind Harmer
12.382
3147133PAMPLIN
Solar/Wind Harmer
-0.204
971193AH1-056 GEN
Solar/Wind Harmer
40.725
963181AG1-167 GEN
Solar/Wind Harmer
5.539
959311AF2-222 GEN
Solar/Wind Harmer
45.705
970257AG2-171 GEN
Solar/Wind Harmer
15.425
315785AD2-033 C
Solar/Wind Harmer
8.494
964241AG1-285 GEN
Solar/Wind Harmer
21.682
316131AB2-060 GEN
Solar/Wind Harmer
2.357
3147043LAWRENC
Solar/Wind Harmer
-0.006
3144293JTRSVLE
50/50
1.776
316322AB2-045
Solar/Wind Harmer
3.419
3146926FARMVIL
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.04
972003AH1-546 GEN
Solar/Wind Harmer
50.704
963171AG1-166 GEN
Solar/Wind Harmer
7.386
971563AH1-280 GEN
Solar/Wind Harmer
7.386
970685AG2-442 GEN
Solar/Wind Harmer
44.081
316237AB2-079_GEN
Solar/Wind Harmer
0.579
970401AG2-262 GEN
Solar/Wind Harmer
0.702
3147043LAWRENC
Adder
0.748
971795AH1-408 GEN
Solar/Wind Harmer
5.817
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.057
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.173
MECLTFEXP_MEC->PJM
CLTF
0.029
SIGELTFEXP_SIGE->PJM
CLTF
0.001
CPLELTFEXP_CPLE->PJM
CLTF
0.247
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.466
LAGNLTFEXP_LAGN->PJM
CLTF
0.104
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.452
TVALTFEXP_TVA->PJM
CLTF
0.053
NYPJM->LTFIMP_NY
CLTF
0.076
LGEELTFEXP_LGEE->PJM
CLTF
0.009
WECLTFEXP_WEC->PJM
CLTF
0.003

Details for AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.24 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:727.2
MW Contribution:1.99
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
971629AH1-314 GEN
50/50
5.006
962491AG1-098 GEN
Solar/Wind Harmer
22.331
315693AD1-088 GEN
Solar/Wind Harmer
18.25
957481AF2-042 GEN
Solar/Wind Harmer
90.747
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.071
316129AC1-054 GEN
Solar/Wind Harmer
0.427
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
3152661PLYWOOD A
50/50
0.346
970535AG2-341 GEN
50/50
1.993
971741AH1-377 GEN
Solar/Wind Harmer
54.138
970933AG2-581 GEN
Solar/Wind Harmer
27.859
970099AG2-077 GEN
Solar/Wind Harmer
36.299
939181AE1-148 GEN
Solar/Wind Harmer
6.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.689
316222AC1-221 GEN
Solar/Wind Harmer
0.447
942751AE2-291 GEN
Solar/Wind Harmer
5.336
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
316478AD1-087 GEN
Solar/Wind Harmer
1.094
316486AD2-202 GEN
Solar/Wind Harmer
0.321
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.01
971683AH1-343 GEN
Solar/Wind Harmer
5.256
316283AC2-100 C
Solar/Wind Harmer
0.206
316131AB2-060 GEN
Solar/Wind Harmer
0.208
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
971967AH1-528 GEN
Solar/Wind Harmer
55.717
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
316118AC1-105 GEN
Solar/Wind Harmer
0.376
970865AG2-541 GEN
Solar/Wind Harmer
4.593
316123AC1-075 GEN
Solar/Wind Harmer
0.152
970165AG2-112 GEN
Solar/Wind Harmer
0.903
970163AG2-111 GEN
Solar/Wind Harmer
0.862
970831AG2-522 GEN
Solar/Wind Harmer
4.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.67 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:712.52
MW Contribution:1.99
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
6.727
3151601KERR 3
50/50
0.301
3151581KERR 1
50/50
0.108
971629AH1-314 GEN
50/50
5.006
962491AG1-098 GEN
Solar/Wind Harmer
22.331
315693AD1-088 GEN
Solar/Wind Harmer
18.25
957481AF2-042 GEN
Solar/Wind Harmer
90.747
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970401AG2-262 GEN
Solar/Wind Harmer
0.742
971065AG2-659 GEN
Solar/Wind Harmer
5.071
316129AC1-054 GEN
Solar/Wind Harmer
0.427
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3146926FARMVIL
Solar/Wind Helper
0.441
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
0.999
3152661PLYWOOD A
50/50
0.346
970535AG2-341 GEN
50/50
1.993
971741AH1-377 GEN
Solar/Wind Harmer
54.138
970099AG2-077 GEN
Solar/Wind Harmer
36.299
939181AE1-148 GEN
Solar/Wind Harmer
6.373
3146843MT LREL
Solar/Wind Harmer
0.127
3146843MT LREL
Solar/Wind Harmer
0.127
964791AG1-342 GEN
Solar/Wind Harmer
2.429
962561AG1-105 GEN
Solar/Wind Harmer
5.689
316222AC1-221 GEN
Solar/Wind Harmer
0.447
942751AE2-291 GEN
Solar/Wind Harmer
5.336
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.339
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.916
970413AG2-270 GEN
50/50
29.358
3151591KERR 2
50/50
0.301
316478AD1-087 GEN
Solar/Wind Harmer
1.094
316486AD2-202 GEN
Solar/Wind Harmer
0.321
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.01
971683AH1-343 GEN
Solar/Wind Harmer
5.256
316283AC2-100 C
Solar/Wind Harmer
0.206
316131AB2-060 GEN
Solar/Wind Harmer
0.208
3146926FARMVIL
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.545
3147133PAMPLIN
Solar/Wind Helper
1.064
316313AB2-026
Solar/Wind Helper
0.242
316258AE1-075 C
Solar/Wind Helper
0.217
316405AF2-144 C
Solar/Wind Helper
0.181
3151541CLOVER2
50/50
6.695
3151611KERR 4
50/50
0.301
3151621KERR 5
50/50
0.301
3151631KERR 6
50/50
0.301
3151641KERR 7
50/50
0.301
3147173SINAI
Solar/Wind Harmer
0.164
3147243WELCO
Solar/Wind Harmer
0.103
316118AC1-105 GEN
Solar/Wind Harmer
0.376
970865AG2-541 GEN
Solar/Wind Harmer
4.593
316123AC1-075 GEN
Solar/Wind Harmer
0.152
970165AG2-112 GEN
Solar/Wind Harmer
0.903
970163AG2-111 GEN
Solar/Wind Harmer
0.862
970831AG2-522 GEN
Solar/Wind Harmer
4.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Helper
2.768
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.254
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.47
MECLTFEXP_MEC->PJM
CLTF
1.259
SIGELTFEXP_SIGE->PJM
CLTF
0.037
CPLELTFEXP_CPLE->PJM
CLTF
4.129
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.762
LAGNLTFEXP_LAGN->PJM
CLTF
2.627
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.688
TVALTFEXP_TVA->PJM
CLTF
1.309
NYPJM->LTFIMP_NY
CLTF
0.384
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.234

Details for AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.28 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:868.71
MW Contribution:2.0
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.708
3151611KERR 4
50/50
0.302
3151531CLOVER1
50/50
6.74
3151601KERR 3
50/50
0.302
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.44
315693AD1-088 GEN
Solar/Wind Harmer
21.388
957481AF2-042 GEN
Solar/Wind Harmer
119.681
315687AD1-152 GEN
Solar/Wind Harmer
3.524
316003AC1-222 GEN
Solar/Wind Harmer
1.683
970401AG2-262 GEN
Solar/Wind Harmer
0.932
971065AG2-659 GEN
Solar/Wind Harmer
6.697
316129AC1-054 GEN
Solar/Wind Harmer
1.121
316237AB2-079_GEN
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Helper
0.44
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
1.003
3152661PLYWOOD A
50/50
0.348
970535AG2-341 GEN
50/50
2.001
971741AH1-377 GEN
Solar/Wind Harmer
71.327
970933AG2-581 GEN
Solar/Wind Harmer
36.739
970099AG2-077 GEN
Solar/Wind Harmer
47.872
939181AE1-148 GEN
Solar/Wind Harmer
8.421
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.05
962561AG1-105 GEN
Solar/Wind Harmer
7.525
316222AC1-221 GEN
Solar/Wind Harmer
1.236
942751AE2-291 GEN
Solar/Wind Harmer
7.063
313527AB2-043 GEN
Solar/Wind Harmer
1.361
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.338
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.919
970413AG2-270 GEN
50/50
29.414
3151591KERR 2
50/50
0.302
316478AD1-087 GEN
Solar/Wind Harmer
3.055
316486AD2-202 GEN
Solar/Wind Harmer
0.895
316248AF1-058 C
Solar/Wind Harmer
0.559
960061AF2-297 GEN
Solar/Wind Harmer
9.268
971683AH1-343 GEN
Solar/Wind Harmer
6.951
316283AC2-100 C
Solar/Wind Harmer
1.124
316131AB2-060 GEN
Solar/Wind Harmer
0.808
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.542
3147133PAMPLIN
Solar/Wind Helper
1.062
316313AB2-026
Solar/Wind Helper
0.243
316258AE1-075 C
Solar/Wind Helper
0.219
316405AF2-144 C
Solar/Wind Helper
0.182
3151621KERR 5
50/50
0.302
3151631KERR 6
50/50
0.302
3151641KERR 7
50/50
0.302
971967AH1-528 GEN
Solar/Wind Harmer
73.672
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.131
970865AG2-541 GEN
Solar/Wind Harmer
6.075
316123AC1-075 GEN
Solar/Wind Harmer
1.358
970165AG2-112 GEN
Solar/Wind Harmer
1.195
970163AG2-111 GEN
Solar/Wind Harmer
1.14
970831AG2-522 GEN
Solar/Wind Harmer
6.069
316239AB2-077_GEN
Solar/Wind Harmer
0.274
316238AB2-078_GEN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Harmer
1.371
270457AD2-023 GEN
Solar/Wind Harmer
0.695
270494AE1-108_GEN
Solar/Wind Helper
2.769
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.6
MECLTFEXP_MEC->PJM
CLTF
1.297
SIGELTFEXP_SIGE->PJM
CLTF
0.038
CPLELTFEXP_CPLE->PJM
CLTF
4.232
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.165
LAGNLTFEXP_LAGN->PJM
CLTF
2.703
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.92
TVALTFEXP_TVA->PJM
CLTF
1.347
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.461
WECLTFEXP_WEC->PJM
CLTF
0.241

Details for AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-377 TP-AG2-198 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.24 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:868.41
MW Contribution:2.0
Bus #Bus NameTypeMW Contribution
3151531CLOVER1
50/50
6.74
3151601KERR 3
50/50
0.302
3151581KERR 1
50/50
0.108
962491AG1-098 GEN
Solar/Wind Harmer
29.44
315693AD1-088 GEN
Solar/Wind Harmer
21.388
957481AF2-042 GEN
Solar/Wind Harmer
119.681
315687AD1-152 GEN
Solar/Wind Harmer
3.524
316003AC1-222 GEN
Solar/Wind Harmer
1.683
970401AG2-262 GEN
Solar/Wind Harmer
0.932
971065AG2-659 GEN
Solar/Wind Harmer
6.697
316129AC1-054 GEN
Solar/Wind Harmer
1.121
316237AB2-079_GEN
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Helper
0.44
316322AB2-045
Solar/Wind Helper
0.606
3146776BUCKING
Solar/Wind Helper
0.217
316336AC2-165 C
Solar/Wind Helper
1.003
3152661PLYWOOD A
50/50
0.348
970535AG2-341 GEN
50/50
2.001
971741AH1-377 GEN
Solar/Wind Harmer
71.327
970933AG2-581 GEN
Solar/Wind Harmer
36.739
970099AG2-077 GEN
Solar/Wind Harmer
47.872
939181AE1-148 GEN
Solar/Wind Harmer
8.421
3146843MT LREL
Solar/Wind Harmer
-0.014
3146843MT LREL
Solar/Wind Harmer
-0.014
964791AG1-342 GEN
Solar/Wind Harmer
3.05
962561AG1-105 GEN
Solar/Wind Harmer
7.525
316222AC1-221 GEN
Solar/Wind Harmer
1.236
942751AE2-291 GEN
Solar/Wind Harmer
7.063
313527AB2-043 GEN
Solar/Wind Harmer
1.361
3146776BUCKING
Solar/Wind Helper
2.175
3146776BUCKING
Solar/Wind Helper
0.176
3147133PAMPLIN
Solar/Wind Helper
0.338
3147133PAMPLIN
Solar/Wind Helper
0.271
315821AE2-092 GEN
Solar/Wind Helper
1.919
970413AG2-270 GEN
50/50
29.414
3151591KERR 2
50/50
0.302
316478AD1-087 GEN
Solar/Wind Harmer
3.055
316486AD2-202 GEN
Solar/Wind Harmer
0.895
316248AF1-058 C
Solar/Wind Harmer
0.559
960061AF2-297 GEN
Solar/Wind Harmer
9.268
971683AH1-343 GEN
Solar/Wind Harmer
6.951
316283AC2-100 C
Solar/Wind Harmer
1.124
316131AB2-060 GEN
Solar/Wind Harmer
0.808
3146926FARMVIL
Solar/Wind Helper
0.44
3146776BUCKING
Solar/Wind Helper
0.196
942461AE2-259 GEN
Solar/Wind Helper
3.542
3147133PAMPLIN
Solar/Wind Helper
1.062
316313AB2-026
Solar/Wind Helper
0.243
316258AE1-075 C
Solar/Wind Helper
0.219
316405AF2-144 C
Solar/Wind Helper
0.182
3151541CLOVER2
50/50
6.708
3151611KERR 4
50/50
0.302
3151621KERR 5
50/50
0.302
3151631KERR 6
50/50
0.302
3151641KERR 7
50/50
0.302
971967AH1-528 GEN
Solar/Wind Harmer
73.672
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.131
970865AG2-541 GEN
Solar/Wind Harmer
6.075
316123AC1-075 GEN
Solar/Wind Harmer
1.358
970165AG2-112 GEN
Solar/Wind Harmer
1.195
970163AG2-111 GEN
Solar/Wind Harmer
1.14
970831AG2-522 GEN
Solar/Wind Harmer
6.069
316239AB2-077_GEN
Solar/Wind Harmer
0.274
316238AB2-078_GEN
Solar/Wind Harmer
0.274
270455AD2-022 GEN
Solar/Wind Harmer
1.371
270457AD2-023 GEN
Solar/Wind Harmer
0.695
270494AE1-108_GEN
Solar/Wind Helper
2.769
3138266HYDRAULIC
Solar/Wind Helper
0.006
3138266HYDRAULIC
Solar/Wind Helper
0.004
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.6
MECLTFEXP_MEC->PJM
CLTF
1.297
SIGELTFEXP_SIGE->PJM
CLTF
0.038
CPLELTFEXP_CPLE->PJM
CLTF
4.232
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.165
LAGNLTFEXP_LAGN->PJM
CLTF
2.703
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.92
TVALTFEXP_TVA->PJM
CLTF
1.347
NYPJM->LTFIMP_NY
CLTF
0.396
LGEELTFEXP_LGEE->PJM
CLTF
0.461
WECLTFEXP_WEC->PJM
CLTF
0.241

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:218.2 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1492.5
MW Contribution:4.63
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.536
3144293JTRSVLE
50/50
1.294
970535AG2-341 GEN
50/50
4.631
3152661PLYWOOD A
50/50
0.509
970301AG2-198 GEN
Solar/Wind Harmer
29.375
971741AH1-377 GEN
Solar/Wind Harmer
63.77
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.984
963191AG1-168 GEN
Solar/Wind Harmer
4.79
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.293
3144293JTRSVLE
50/50
1.536
3151531CLOVER1
50/50
6.868
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.479
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.387
971563AH1-280 GEN
Solar/Wind Harmer
6.387
970685AG2-442 GEN
Solar/Wind Harmer
41.098
962491AG1-098 GEN
Solar/Wind Harmer
28.527
315693AD1-088 GEN
Solar/Wind Harmer
20.89
957481AF2-042 GEN
Solar/Wind Harmer
119.73
316237AB2-079_GEN
Solar/Wind Harmer
0.97
315687AD1-152 GEN
Solar/Wind Harmer
3.722
970401AG2-262 GEN
Solar/Wind Harmer
1.828
316003AC1-222 GEN
Solar/Wind Harmer
2.23
971065AG2-659 GEN
Solar/Wind Harmer
10.784
316129AC1-054 GEN
Solar/Wind Harmer
1.809
971795AH1-408 GEN
Solar/Wind Harmer
11.382
960081AF2-299 GEN
Solar/Wind Harmer
1.187
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.663
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.965
316049AB1-081 GEN
Solar/Wind Harmer
0.772
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.715
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
970223AG2-152 GEN
Solar/Wind Harmer
5.79
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.192
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.414
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.314
3151541CLOVER2
50/50
6.835
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
971845AH1-439 GEN
Solar/Wind Harmer
44.839
970285AG2-188 GEN
Solar/Wind Harmer
71.83
315657AE1-056 GEN
Solar/Wind Harmer
20.241
946301AF1-294 GEN
Solar/Wind Harmer
13.094
961791AG1-021 GEN
Solar/Wind Harmer
6.387
970683AG2-441 GEN
Solar/Wind Harmer
36.695
970681AG2-440 GEN
Solar/Wind Harmer
29.356
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.31
971967AH1-528 GEN
Solar/Wind Harmer
73.321
316239AB2-077_GEN
Solar/Wind Harmer
0.97
316238AB2-078_GEN
Solar/Wind Harmer
0.97
316118AC1-105 GEN
Solar/Wind Harmer
1.807
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.03
970831AG2-522 GEN
Solar/Wind Harmer
9.822
316123AC1-075 GEN
Solar/Wind Harmer
1.789
970165AG2-112 GEN
Solar/Wind Harmer
1.575
970163AG2-111 GEN
Solar/Wind Harmer
1.503
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.493
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.635
270457AD2-023 GEN
Solar/Wind Harmer
0.829
315607AA1-063A GEN
Solar/Wind Harmer
0.882
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.411
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.563
270494AE1-108_GEN
Solar/Wind Helper
3.665
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
971775AH1-396 GEN
Solar/Wind Harmer
3.032
970933AG2-581 GEN
Solar/Wind Harmer
36.564
970099AG2-077 GEN
Solar/Wind Harmer
47.892
313527AB2-043 GEN
Solar/Wind Harmer
5.323
962561AG1-105 GEN
Solar/Wind Harmer
16.163
964791AG1-342 GEN
Solar/Wind Harmer
5.983
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.395
942751AE2-291 GEN
Solar/Wind Harmer
9.282
316222AC1-221 GEN
Solar/Wind Harmer
1.431
316181AB2-040 GEN
Solar/Wind Harmer
1.454
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.157
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.182
3145783HORNRTN
Solar/Wind Harmer
0.946
3145783HORNRTN
Solar/Wind Harmer
0.296
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.956
316274AC1-208 GEN
Solar/Wind Harmer
0.891
316263AC1-034 GEN
Solar/Wind Harmer
3.354
961601AG1-000A GEN
Solar/Wind Harmer
2.733
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.045
316197AC1-042 GEN
Solar/Wind Harmer
0.792
942671AE2-283 GEN
Solar/Wind Harmer
2.132
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.531
3144293JTRSVLE
50/50
1.536
970413AG2-270 GEN
50/50
29.97
3151591KERR 2
50/50
0.482
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.339
970909AG2-566 GEN
Solar/Wind Harmer
5.578
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.735
963181AG1-167 GEN
Solar/Wind Harmer
4.79
959311AF2-222 GEN
Solar/Wind Harmer
45.765
970257AG2-171 GEN
Solar/Wind Harmer
15.97
315785AD2-033 C
Solar/Wind Harmer
9.259
964241AG1-285 GEN
Solar/Wind Harmer
28.316
316478AD1-087 GEN
Solar/Wind Harmer
3.115
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.609
316248AF1-058 C
Solar/Wind Harmer
0.741
960061AF2-297 GEN
Solar/Wind Harmer
12.289
971683AH1-343 GEN
Solar/Wind Harmer
9.199
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.303
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.775
316210AC1-098 GEN
Solar/Wind Harmer
1.194
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.767
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.393
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.414
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.317
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.51
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.435
MECLTFEXP_MEC->PJM
CLTF
1.488
SIGELTFEXP_SIGE->PJM
CLTF
0.044
CPLELTFEXP_CPLE->PJM
CLTF
5.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.616
LAGNLTFEXP_LAGN->PJM
CLTF
3.212
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.896
TVALTFEXP_TVA->PJM
CLTF
1.599
NYPJM->LTFIMP_NY
CLTF
0.52
LGEELTFEXP_LGEE->PJM
CLTF
0.521
WECLTFEXP_WEC->PJM
CLTF
0.271

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:218.14 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1492.11
MW Contribution:4.63
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.536
3151531CLOVER1
50/50
6.868
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.479
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.387
971563AH1-280 GEN
Solar/Wind Harmer
6.387
970685AG2-442 GEN
Solar/Wind Harmer
41.098
962491AG1-098 GEN
Solar/Wind Harmer
28.527
315693AD1-088 GEN
Solar/Wind Harmer
20.89
957481AF2-042 GEN
Solar/Wind Harmer
119.73
316237AB2-079_GEN
Solar/Wind Harmer
0.97
315687AD1-152 GEN
Solar/Wind Harmer
3.722
970401AG2-262 GEN
Solar/Wind Harmer
1.828
316003AC1-222 GEN
Solar/Wind Harmer
2.23
971065AG2-659 GEN
Solar/Wind Harmer
10.784
316129AC1-054 GEN
Solar/Wind Harmer
1.809
971795AH1-408 GEN
Solar/Wind Harmer
11.382
960081AF2-299 GEN
Solar/Wind Harmer
1.187
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.663
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.965
316049AB1-081 GEN
Solar/Wind Harmer
0.772
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.715
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
970223AG2-152 GEN
Solar/Wind Harmer
5.79
961671AG1-007 GEN
Solar/Wind Harmer
0.082
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.192
3147312GRETNA
Solar/Wind Harmer
-0.005
3151541CLOVER2
50/50
6.835
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
971845AH1-439 GEN
Solar/Wind Harmer
44.839
970285AG2-188 GEN
Solar/Wind Harmer
71.83
315657AE1-056 GEN
Solar/Wind Harmer
20.241
946301AF1-294 GEN
Solar/Wind Harmer
13.094
961791AG1-021 GEN
Solar/Wind Harmer
6.387
970683AG2-441 GEN
Solar/Wind Harmer
36.695
970681AG2-440 GEN
Solar/Wind Harmer
29.356
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.31
971967AH1-528 GEN
Solar/Wind Harmer
73.321
316239AB2-077_GEN
Solar/Wind Harmer
0.97
316238AB2-078_GEN
Solar/Wind Harmer
0.97
316118AC1-105 GEN
Solar/Wind Harmer
1.807
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.03
970831AG2-522 GEN
Solar/Wind Harmer
9.822
316123AC1-075 GEN
Solar/Wind Harmer
1.789
970165AG2-112 GEN
Solar/Wind Harmer
1.575
970163AG2-111 GEN
Solar/Wind Harmer
1.503
946281AF1-292 GEN
Solar/Wind Harmer
0.236
3144293JTRSVLE
50/50
1.536
3144293JTRSVLE
50/50
1.294
970535AG2-341 GEN
50/50
4.631
3152661PLYWOOD A
50/50
0.509
970301AG2-198 GEN
Solar/Wind Harmer
29.375
971741AH1-377 GEN
Solar/Wind Harmer
63.77
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.984
963191AG1-168 GEN
Solar/Wind Harmer
4.79
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.293
971775AH1-396 GEN
Solar/Wind Harmer
3.032
970933AG2-581 GEN
Solar/Wind Harmer
36.564
970099AG2-077 GEN
Solar/Wind Harmer
47.892
313527AB2-043 GEN
Solar/Wind Harmer
5.323
962561AG1-105 GEN
Solar/Wind Harmer
16.163
964791AG1-342 GEN
Solar/Wind Harmer
5.983
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.395
942751AE2-291 GEN
Solar/Wind Harmer
9.282
316222AC1-221 GEN
Solar/Wind Harmer
1.431
316181AB2-040 GEN
Solar/Wind Harmer
1.454
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.157
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.182
3145783HORNRTN
Solar/Wind Harmer
0.946
3145783HORNRTN
Solar/Wind Harmer
0.296
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.956
316274AC1-208 GEN
Solar/Wind Harmer
0.891
316263AC1-034 GEN
Solar/Wind Harmer
3.354
961601AG1-000A GEN
Solar/Wind Harmer
2.733
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.045
316197AC1-042 GEN
Solar/Wind Harmer
0.792
942671AE2-283 GEN
Solar/Wind Harmer
2.132
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.531
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.414
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.314
316087AB2-174 GEN
Solar/Wind Harmer
1.493
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.635
270457AD2-023 GEN
Solar/Wind Harmer
0.829
315607AA1-063A GEN
Solar/Wind Harmer
0.882
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.411
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.563
270494AE1-108_GEN
Solar/Wind Helper
3.665
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.536
970413AG2-270 GEN
50/50
29.97
3151591KERR 2
50/50
0.482
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.339
970909AG2-566 GEN
Solar/Wind Harmer
5.578
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.735
963181AG1-167 GEN
Solar/Wind Harmer
4.79
959311AF2-222 GEN
Solar/Wind Harmer
45.765
970257AG2-171 GEN
Solar/Wind Harmer
15.97
315785AD2-033 C
Solar/Wind Harmer
9.259
964241AG1-285 GEN
Solar/Wind Harmer
28.316
316478AD1-087 GEN
Solar/Wind Harmer
3.115
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.609
316248AF1-058 C
Solar/Wind Harmer
0.741
960061AF2-297 GEN
Solar/Wind Harmer
12.289
971683AH1-343 GEN
Solar/Wind Harmer
9.199
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.303
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.775
316210AC1-098 GEN
Solar/Wind Harmer
1.194
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.767
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.393
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.414
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.317
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.51
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.435
MECLTFEXP_MEC->PJM
CLTF
1.488
SIGELTFEXP_SIGE->PJM
CLTF
0.044
CPLELTFEXP_CPLE->PJM
CLTF
5.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.616
LAGNLTFEXP_LAGN->PJM
CLTF
3.212
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.896
TVALTFEXP_TVA->PJM
CLTF
1.599
NYPJM->LTFIMP_NY
CLTF
0.52
LGEELTFEXP_LGEE->PJM
CLTF
0.521
WECLTFEXP_WEC->PJM
CLTF
0.271

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:214.52 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1467.34
MW Contribution:4.62
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.838
970285AG2-188 GEN
Solar/Wind Harmer
71.826
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
971967AH1-528 GEN
Solar/Wind Harmer
73.183
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970933AG2-581 GEN
Solar/Wind Harmer
36.495
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:212.24 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:1187.04
MW Contribution:4.62
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.213
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.1
970301AG2-198 GEN
Solar/Wind Harmer
22.295
971741AH1-377 GEN
Solar/Wind Harmer
48.392
3147133PAMPLIN
Solar/Wind Harmer
0.48
3147133PAMPLIN
Solar/Wind Harmer
0.384
958211AF2-115 GEN
Solar/Wind Harmer
5.453
963191AG1-168 GEN
Solar/Wind Harmer
1.818
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.154
971775AH1-396 GEN
Solar/Wind Harmer
0.606
970933AG2-581 GEN
Solar/Wind Harmer
27.718
970099AG2-077 GEN
Solar/Wind Harmer
36.303
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.244
964791AG1-342 GEN
Solar/Wind Harmer
4.773
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.665
942751AE2-291 GEN
Solar/Wind Harmer
7.016
316222AC1-221 GEN
Solar/Wind Harmer
0.517
316181AB2-040 GEN
Solar/Wind Harmer
0.135
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.992
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.575
3145783HORNRTN
Solar/Wind Harmer
1.26
3145783HORNRTN
Solar/Wind Harmer
0.394
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.38
316263AC1-034 GEN
Solar/Wind Harmer
2.393
961601AG1-000A GEN
Solar/Wind Harmer
1.088
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.132
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.414
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.232
963181AG1-167 GEN
Solar/Wind Harmer
1.818
959311AF2-222 GEN
Solar/Wind Harmer
34.653
970257AG2-171 GEN
Solar/Wind Harmer
12.116
315785AD2-033 C
Solar/Wind Harmer
2.953
964241AG1-285 GEN
Solar/Wind Harmer
21.475
316478AD1-087 GEN
Solar/Wind Harmer
1.115
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.935
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.299
971683AH1-343 GEN
Solar/Wind Harmer
6.959
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.287
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.626
3146233WITAKRS
Solar/Wind Harmer
0.329
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.062
961601AG1-000A GEN
Solar/Wind Harmer
4.35
315724AD1-057 GEN
Solar/Wind Harmer
0.227
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.818
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.104
971845AH1-439 GEN
Solar/Wind Harmer
34.055
970285AG2-188 GEN
Solar/Wind Harmer
57.798
315657AE1-056 GEN
Solar/Wind Harmer
16.558
946301AF1-294 GEN
Solar/Wind Harmer
8.968
961791AG1-021 GEN
Solar/Wind Harmer
4.363
970683AG2-441 GEN
Solar/Wind Harmer
27.844
970681AG2-440 GEN
Solar/Wind Harmer
22.275
3144303KENBRDG
Solar/Wind Harmer
0.303
971443AH1-215 GEN
Solar/Wind Harmer
6.304
971967AH1-528 GEN
Solar/Wind Harmer
55.434
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.602
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.073
970831AG2-522 GEN
Solar/Wind Harmer
7.443
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.191
970163AG2-111 GEN
Solar/Wind Harmer
1.136
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.368
315607AA1-063A GEN
Solar/Wind Harmer
0.159
3146043SEABORD
Solar/Wind Harmer
0.076
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.25
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.462
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.252
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.97
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
963171AG1-166 GEN
Solar/Wind Harmer
2.424
971563AH1-280 GEN
Solar/Wind Harmer
4.847
970685AG2-442 GEN
Solar/Wind Harmer
31.186
962491AG1-098 GEN
Solar/Wind Harmer
21.632
315693AD1-088 GEN
Solar/Wind Harmer
17.82
957481AF2-042 GEN
Solar/Wind Harmer
90.757
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.458
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.171
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
9.004
960081AF2-299 GEN
Solar/Wind Harmer
0.903
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.349
3146233WITAKRS
Solar/Wind Harmer
0.261
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.051
316359AB2-059 GEN
Solar/Wind Harmer
0.226
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.062
315722AD1-056 GEN
Solar/Wind Harmer
0.382
3145796HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.068
962571AG1-106 GEN
Solar/Wind Harmer
0.836
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.253
970223AG2-152 GEN
Solar/Wind Harmer
3.997
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.043
941801AE2-185 GEN
Solar/Wind Harmer
1.818
3145823KELFORD
Solar/Wind Harmer
0.056
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:209.65 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:1172.59
MW Contribution:4.62
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.104
971845AH1-439 GEN
Solar/Wind Harmer
34.055
970285AG2-188 GEN
Solar/Wind Harmer
57.798
315657AE1-056 GEN
Solar/Wind Harmer
16.558
946301AF1-294 GEN
Solar/Wind Harmer
8.968
961791AG1-021 GEN
Solar/Wind Harmer
4.363
970683AG2-441 GEN
Solar/Wind Harmer
27.844
970681AG2-440 GEN
Solar/Wind Harmer
22.275
3144303KENBRDG
Solar/Wind Harmer
0.303
971443AH1-215 GEN
Solar/Wind Harmer
6.304
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.602
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.073
970831AG2-522 GEN
Solar/Wind Harmer
7.443
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.191
970163AG2-111 GEN
Solar/Wind Harmer
1.136
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.368
315607AA1-063A GEN
Solar/Wind Harmer
0.159
3146043SEABORD
Solar/Wind Harmer
0.076
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.25
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.462
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.252
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.213
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.1
970301AG2-198 GEN
Solar/Wind Harmer
22.295
971741AH1-377 GEN
Solar/Wind Harmer
48.392
3147133PAMPLIN
Solar/Wind Harmer
0.48
3147133PAMPLIN
Solar/Wind Harmer
0.384
958211AF2-115 GEN
Solar/Wind Harmer
5.453
963191AG1-168 GEN
Solar/Wind Harmer
1.818
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.154
971775AH1-396 GEN
Solar/Wind Harmer
0.606
970099AG2-077 GEN
Solar/Wind Harmer
36.303
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.244
964791AG1-342 GEN
Solar/Wind Harmer
4.773
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.665
942751AE2-291 GEN
Solar/Wind Harmer
7.016
316222AC1-221 GEN
Solar/Wind Harmer
0.517
316181AB2-040 GEN
Solar/Wind Harmer
0.135
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.992
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.97
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
963171AG1-166 GEN
Solar/Wind Harmer
2.424
971563AH1-280 GEN
Solar/Wind Harmer
4.847
970685AG2-442 GEN
Solar/Wind Harmer
31.186
962491AG1-098 GEN
Solar/Wind Harmer
21.632
315693AD1-088 GEN
Solar/Wind Harmer
17.82
957481AF2-042 GEN
Solar/Wind Harmer
90.757
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.458
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.171
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
9.004
960081AF2-299 GEN
Solar/Wind Harmer
0.903
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.349
3146233WITAKRS
Solar/Wind Harmer
0.261
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.051
316359AB2-059 GEN
Solar/Wind Harmer
0.226
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.062
315722AD1-056 GEN
Solar/Wind Harmer
0.382
3145796HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.068
962571AG1-106 GEN
Solar/Wind Harmer
0.836
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.253
970223AG2-152 GEN
Solar/Wind Harmer
3.997
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.043
941801AE2-185 GEN
Solar/Wind Harmer
1.818
3145823KELFORD
Solar/Wind Harmer
0.056
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.159
3151411GASTONB
50/50
0.159
3146926FARMVIL
Solar/Wind Harmer
0.381
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.232
963181AG1-167 GEN
Solar/Wind Harmer
1.818
959311AF2-222 GEN
Solar/Wind Harmer
34.653
970257AG2-171 GEN
Solar/Wind Harmer
12.116
315785AD2-033 C
Solar/Wind Harmer
2.953
964241AG1-285 GEN
Solar/Wind Harmer
21.475
316478AD1-087 GEN
Solar/Wind Harmer
1.115
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.935
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.299
971683AH1-343 GEN
Solar/Wind Harmer
6.959
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.287
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.626
3146233WITAKRS
Solar/Wind Harmer
0.329
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.062
961601AG1-000A GEN
Solar/Wind Harmer
4.35
315724AD1-057 GEN
Solar/Wind Harmer
0.227
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.818
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.575
3145783HORNRTN
Solar/Wind Harmer
1.26
3145783HORNRTN
Solar/Wind Harmer
0.394
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.38
316263AC1-034 GEN
Solar/Wind Harmer
2.393
961601AG1-000A GEN
Solar/Wind Harmer
1.088
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.132
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.414
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:208.48 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1426.03
MW Contribution:4.62
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.838
970285AG2-188 GEN
Solar/Wind Harmer
71.826
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
315821AE2-092 GEN
Solar/Wind Helper
2.527
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:208.48 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:1426.03
MW Contribution:4.62
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.853
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.478
3146926FARMVIL
Solar/Wind Harmer
-0.042
3151541CLOVER2
50/50
6.82
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.838
970285AG2-188 GEN
Solar/Wind Harmer
71.826
315657AE1-056 GEN
Solar/Wind Harmer
20.228
946301AF1-294 GEN
Solar/Wind Harmer
13.084
961791AG1-021 GEN
Solar/Wind Harmer
6.382
970683AG2-441 GEN
Solar/Wind Harmer
36.662
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.621
3152661PLYWOOD A
50/50
0.507
970301AG2-198 GEN
Solar/Wind Harmer
29.355
971741AH1-377 GEN
Solar/Wind Harmer
63.716
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.978
963191AG1-168 GEN
Solar/Wind Harmer
4.787
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.27
971775AH1-396 GEN
Solar/Wind Harmer
3.029
970099AG2-077 GEN
Solar/Wind Harmer
47.799
313527AB2-043 GEN
Solar/Wind Harmer
5.313
962561AG1-105 GEN
Solar/Wind Harmer
16.121
964791AG1-342 GEN
Solar/Wind Harmer
5.966
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.359
942751AE2-291 GEN
Solar/Wind Harmer
9.237
316222AC1-221 GEN
Solar/Wind Harmer
1.416
316181AB2-040 GEN
Solar/Wind Harmer
1.455
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.156
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.181
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.955
316274AC1-208 GEN
Solar/Wind Harmer
0.887
316263AC1-034 GEN
Solar/Wind Harmer
3.317
961601AG1-000A GEN
Solar/Wind Harmer
2.702
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.036
316197AC1-042 GEN
Solar/Wind Harmer
0.785
942671AE2-283 GEN
Solar/Wind Harmer
2.114
3146776BUCKING
Solar/Wind Helper
2.872
3146776BUCKING
Solar/Wind Helper
0.233
963171AG1-166 GEN
Solar/Wind Harmer
6.382
971563AH1-280 GEN
Solar/Wind Harmer
6.382
970685AG2-442 GEN
Solar/Wind Harmer
41.061
962491AG1-098 GEN
Solar/Wind Harmer
28.482
315693AD1-088 GEN
Solar/Wind Harmer
20.856
957481AF2-042 GEN
Solar/Wind Harmer
119.496
316237AB2-079_GEN
Solar/Wind Harmer
0.968
315687AD1-152 GEN
Solar/Wind Harmer
3.711
970401AG2-262 GEN
Solar/Wind Harmer
1.823
316003AC1-222 GEN
Solar/Wind Harmer
2.221
971065AG2-659 GEN
Solar/Wind Harmer
10.759
316129AC1-054 GEN
Solar/Wind Harmer
1.805
971795AH1-408 GEN
Solar/Wind Harmer
11.381
960081AF2-299 GEN
Solar/Wind Harmer
1.188
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.954
316049AB1-081 GEN
Solar/Wind Harmer
0.763
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.71
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.382
962571AG1-106 GEN
Solar/Wind Harmer
0.949
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.19
970223AG2-152 GEN
Solar/Wind Harmer
5.701
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.394
3145823KELFORD
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.8
3146776BUCKING
Solar/Wind Helper
0.287
316336AC2-165 C
Solar/Wind Helper
1.308
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.904
3151591KERR 2
50/50
0.481
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.335
970909AG2-566 GEN
Solar/Wind Harmer
5.574
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.713
963181AG1-167 GEN
Solar/Wind Harmer
4.787
959311AF2-222 GEN
Solar/Wind Harmer
45.717
970257AG2-171 GEN
Solar/Wind Harmer
15.953
315785AD2-033 C
Solar/Wind Harmer
9.248
964241AG1-285 GEN
Solar/Wind Harmer
28.275
316478AD1-087 GEN
Solar/Wind Harmer
3.108
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.603
316248AF1-058 C
Solar/Wind Harmer
0.738
960061AF2-297 GEN
Solar/Wind Harmer
12.244
971683AH1-343 GEN
Solar/Wind Harmer
9.162
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.29
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.838
316327AA2-057 GEN
Solar/Wind Harmer
0.77
316210AC1-098 GEN
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.736
315724AD1-057 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.394
316317KELFORD C
Solar/Wind Harmer
0.299
3145823KELFORD
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.258
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.284
316405AF2-144 C
Solar/Wind Helper
0.237
970681AG2-440 GEN
Solar/Wind Harmer
29.329
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.301
316239AB2-077_GEN
Solar/Wind Harmer
0.968
316238AB2-078_GEN
Solar/Wind Harmer
0.968
316118AC1-105 GEN
Solar/Wind Harmer
1.801
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.997
970831AG2-522 GEN
Solar/Wind Harmer
9.8
316123AC1-075 GEN
Solar/Wind Harmer
1.781
970165AG2-112 GEN
Solar/Wind Harmer
1.568
970163AG2-111 GEN
Solar/Wind Harmer
1.496
946281AF1-292 GEN
Solar/Wind Harmer
0.237
316087AB2-174 GEN
Solar/Wind Harmer
1.494
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.61
270457AD2-023 GEN
Solar/Wind Harmer
0.816
315607AA1-063A GEN
Solar/Wind Harmer
0.883
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.407
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.429
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.566
270494AE1-108_GEN
Solar/Wind Helper
3.663
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
315821AE2-092 GEN
Solar/Wind Helper
2.527
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.212
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.281
MECLTFEXP_MEC->PJM
CLTF
1.444
SIGELTFEXP_SIGE->PJM
CLTF
0.043
CPLELTFEXP_CPLE->PJM
CLTF
5.106
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.139
LAGNLTFEXP_LAGN->PJM
CLTF
3.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.62
TVALTFEXP_TVA->PJM
CLTF
1.554
NYPJM->LTFIMP_NY
CLTF
0.506
LGEELTFEXP_LGEE->PJM
CLTF
0.505
WECLTFEXP_WEC->PJM
CLTF
0.263

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2106-2111_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2106-2111_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:134.05 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:916.91
MW Contribution:2.84
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.18
3151591KERR 2
50/50
0.277
970413AG2-270 GEN
50/50
12.405
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.535
970909AG2-566 GEN
Solar/Wind Harmer
4.036
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.307
963181AG1-167 GEN
Solar/Wind Harmer
3.68
959311AF2-222 GEN
Solar/Wind Harmer
33.514
970257AG2-171 GEN
Solar/Wind Harmer
11.575
315785AD2-033 C
Solar/Wind Harmer
6.609
964241AG1-285 GEN
Solar/Wind Harmer
19.233
316131AB2-060 GEN
Solar/Wind Harmer
2.359
316478AD1-087 GEN
Solar/Wind Harmer
1.29
316486AD2-202 GEN
Solar/Wind Harmer
0.378
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.371
960061AF2-297 GEN
Solar/Wind Harmer
6.151
971683AH1-343 GEN
Solar/Wind Harmer
4.535
966621AG1-532 GEN
Solar/Wind Harmer
0.172
313506AB2-031 GEN
Solar/Wind Harmer
0.656
316283AC2-100 C
Solar/Wind Harmer
0.705
316210AC1-098 GEN
Solar/Wind Harmer
0.995
3146776BUCKING
Solar/Wind Helper
0.313
316313AB2-026
Solar/Wind Helper
0.341
316258AE1-075 C
Solar/Wind Helper
0.306
316405AF2-144 C
Solar/Wind Helper
0.255
3148013FISHERV
Solar/Wind Helper
0.125
3144293JTRSVLE
50/50
1.18
3151601KERR 3
50/50
0.277
3151581KERR 1
50/50
0.099
3151531CLOVER1
50/50
2.843
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.907
971563AH1-280 GEN
Solar/Wind Harmer
4.907
970685AG2-442 GEN
Solar/Wind Harmer
30.788
962491AG1-098 GEN
Solar/Wind Harmer
14.151
316237AB2-079_GEN
Solar/Wind Harmer
0.621
315693AD1-088 GEN
Solar/Wind Harmer
9.998
970401AG2-262 GEN
Solar/Wind Harmer
1.046
957481AF2-042 GEN
Solar/Wind Harmer
45.244
315687AD1-152 GEN
Solar/Wind Harmer
1.611
971065AG2-659 GEN
Solar/Wind Harmer
6.471
316129AC1-054 GEN
Solar/Wind Harmer
1.098
3147043LAWRENC
Adder
0.994
316003AC1-222 GEN
Solar/Wind Harmer
1.108
971795AH1-408 GEN
Solar/Wind Harmer
8.341
960081AF2-299 GEN
Solar/Wind Harmer
0.953
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.091
316212AC1-099_GEN
Solar/Wind Harmer
0.553
316322AB2-045
Solar/Wind Helper
0.97
3146776BUCKING
Solar/Wind Helper
0.348
316336AC2-165 C
Solar/Wind Helper
1.454
3151611KERR 4
50/50
0.277
3151621KERR 5
50/50
0.277
3151631KERR 6
50/50
0.277
3151641KERR 7
50/50
0.277
3144293JTRSVLE
50/50
1.18
3144293JTRSVLE
50/50
0.994
970535AG2-341 GEN
50/50
2.836
3152661PLYWOOD A
50/50
0.267
970301AG2-198 GEN
Solar/Wind Harmer
21.257
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.133
963191AG1-168 GEN
Solar/Wind Harmer
3.68
971741AH1-377 GEN
Solar/Wind Harmer
43.417
316034AC1-036 C
Solar/Wind Harmer
0.574
970323AG2-213 GEN
Solar/Wind Harmer
15.434
971775AH1-396 GEN
Solar/Wind Harmer
2.198
313527AB2-043 GEN
Solar/Wind Harmer
3.442
962561AG1-105 GEN
Solar/Wind Harmer
9.457
939181AE1-148 GEN
Solar/Wind Harmer
9.083
964791AG1-342 GEN
Solar/Wind Harmer
3.423
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.098
970933AG2-581 GEN
Solar/Wind Harmer
9.079
316181AB2-040 GEN
Solar/Wind Harmer
1.138
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.878
3145593CAROLNA
Solar/Wind Harmer
0.065
3145783HORNRTN
Solar/Wind Harmer
0.905
3145783HORNRTN
Solar/Wind Harmer
0.724
3145783HORNRTN
Solar/Wind Harmer
0.226
3145783HORNRTN
Solar/Wind Harmer
0.09
316222AC1-221 GEN
Solar/Wind Harmer
0.769
316426AA2-053 GEN
Solar/Wind Harmer
0.748
942751AE2-291 GEN
Solar/Wind Harmer
4.333
316274AC1-208 GEN
Solar/Wind Harmer
0.717
972187AH1-678 GEN
Adder
1.63
3146776BUCKING
Solar/Wind Helper
3.482
3146776BUCKING
Solar/Wind Helper
0.282
315821AE2-092 GEN
Solar/Wind Helper
2.994
3151541CLOVER2
50/50
2.829
971845AH1-439 GEN
Solar/Wind Harmer
40.087
970285AG2-188 GEN
Solar/Wind Harmer
63.51
315657AE1-056 GEN
Solar/Wind Harmer
15.784
946301AF1-294 GEN
Solar/Wind Harmer
10.059
961791AG1-021 GEN
Solar/Wind Harmer
4.907
970683AG2-441 GEN
Solar/Wind Harmer
27.489
970681AG2-440 GEN
Solar/Wind Harmer
21.992
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.004
316239AB2-077_GEN
Solar/Wind Harmer
0.621
316238AB2-078_GEN
Solar/Wind Harmer
0.621
316118AC1-105 GEN
Solar/Wind Harmer
0.972
3147173SINAI
Solar/Wind Harmer
-0.012
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.033
970865AG2-541 GEN
Solar/Wind Harmer
3.923
946281AF1-292 GEN
Solar/Wind Harmer
0.19
316087AB2-174 GEN
Solar/Wind Harmer
1.178
3137643SOCKMAN
Solar/Wind Harmer
-0.032
316123AC1-075 GEN
Solar/Wind Harmer
0.853
970165AG2-112 GEN
Solar/Wind Harmer
0.751
970163AG2-111 GEN
Solar/Wind Harmer
0.717
971967AH1-528 GEN
Solar/Wind Harmer
14.188
315607AA1-063A GEN
Solar/Wind Harmer
0.715
3146043SEABORD
Solar/Wind Harmer
-0.007
270494AE1-108_GEN
Solar/Wind Helper
4.499
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.19
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.966
MECLTFEXP_MEC->PJM
CLTF
0.645
SIGELTFEXP_SIGE->PJM
CLTF
0.018
CPLELTFEXP_CPLE->PJM
CLTF
3.717
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.651
LAGNLTFEXP_LAGN->PJM
CLTF
1.842
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.457
TVALTFEXP_TVA->PJM
CLTF
0.904
NYPJM->LTFIMP_NY
CLTF
0.34
LGEELTFEXP_LGEE->PJM
CLTF
0.186
WECLTFEXP_WEC->PJM
CLTF
0.097

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:133.94 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:916.12
MW Contribution:2.93
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.195
3151601KERR 3
50/50
0.289
3151581KERR 1
50/50
0.103
3151611KERR 4
50/50
0.289
3151621KERR 5
50/50
0.289
3151631KERR 6
50/50
0.289
3151641KERR 7
50/50
0.289
3151541CLOVER2
50/50
2.941
971845AH1-439 GEN
Solar/Wind Harmer
40.276
970285AG2-188 GEN
Solar/Wind Harmer
63.831
315657AE1-056 GEN
Solar/Wind Harmer
15.969
946301AF1-294 GEN
Solar/Wind Harmer
10.188
961791AG1-021 GEN
Solar/Wind Harmer
4.97
970683AG2-441 GEN
Solar/Wind Harmer
27.899
970681AG2-440 GEN
Solar/Wind Harmer
22.32
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.111
3144293JTRSVLE
50/50
1.195
3151591KERR 2
50/50
0.289
970413AG2-270 GEN
50/50
12.897
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.604
970909AG2-566 GEN
Solar/Wind Harmer
4.081
3147133PAMPLIN
Solar/Wind Harmer
-0.133
971193AH1-056 GEN
Solar/Wind Harmer
26.615
963181AG1-167 GEN
Solar/Wind Harmer
3.727
959311AF2-222 GEN
Solar/Wind Harmer
34.076
970257AG2-171 GEN
Solar/Wind Harmer
11.779
315785AD2-033 C
Solar/Wind Harmer
6.734
964241AG1-285 GEN
Solar/Wind Harmer
19.68
316131AB2-060 GEN
Solar/Wind Harmer
2.422
316478AD1-087 GEN
Solar/Wind Harmer
1.342
316486AD2-202 GEN
Solar/Wind Harmer
0.393
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.389
960061AF2-297 GEN
Solar/Wind Harmer
6.458
971683AH1-343 GEN
Solar/Wind Harmer
4.759
966621AG1-532 GEN
Solar/Wind Harmer
0.184
313506AB2-031 GEN
Solar/Wind Harmer
0.706
316283AC2-100 C
Solar/Wind Harmer
0.787
316210AC1-098 GEN
Solar/Wind Harmer
1.105
316327AA2-057 GEN
Solar/Wind Harmer
0.707
970917AG2-570 GEN
Solar/Wind Harmer
17.327
3146233WITAKRS
Solar/Wind Harmer
0.143
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.004
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3151531CLOVER1
50/50
2.955
3147043LAWRENC
50/50
1.106
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.97
971563AH1-280 GEN
Solar/Wind Harmer
4.97
970685AG2-442 GEN
Solar/Wind Harmer
31.247
962491AG1-098 GEN
Solar/Wind Harmer
14.52
316237AB2-079_GEN
Solar/Wind Harmer
0.639
315693AD1-088 GEN
Solar/Wind Harmer
10.276
970401AG2-262 GEN
Solar/Wind Harmer
1.085
957481AF2-042 GEN
Solar/Wind Harmer
47.025
315687AD1-152 GEN
Solar/Wind Harmer
1.689
971065AG2-659 GEN
Solar/Wind Harmer
6.793
316129AC1-054 GEN
Solar/Wind Harmer
1.154
316003AC1-222 GEN
Solar/Wind Harmer
1.163
971795AH1-408 GEN
Solar/Wind Harmer
8.792
960081AF2-299 GEN
Solar/Wind Harmer
1.021
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.099
316212AC1-099_GEN
Solar/Wind Harmer
0.614
970919AG2-571 GEN
Solar/Wind Harmer
2.193
970087AG2-069 GEN
Solar/Wind Harmer
6.491
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.406
962571AG1-106 GEN
Solar/Wind Harmer
0.966
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3144293JTRSVLE
50/50
1.195
3144293JTRSVLE
50/50
1.007
970535AG2-341 GEN
50/50
2.934
3152661PLYWOOD A
50/50
0.28
970301AG2-198 GEN
Solar/Wind Harmer
21.495
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.212
963191AG1-168 GEN
Solar/Wind Harmer
3.727
971741AH1-377 GEN
Solar/Wind Harmer
43.991
316034AC1-036 C
Solar/Wind Harmer
0.584
970323AG2-213 GEN
Solar/Wind Harmer
15.706
971775AH1-396 GEN
Solar/Wind Harmer
2.237
313527AB2-043 GEN
Solar/Wind Harmer
3.538
962561AG1-105 GEN
Solar/Wind Harmer
9.795
939181AE1-148 GEN
Solar/Wind Harmer
9.44
964791AG1-342 GEN
Solar/Wind Harmer
3.552
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
970099AG2-077 GEN
Solar/Wind Harmer
18.81
970933AG2-581 GEN
Solar/Wind Harmer
9.592
316181AB2-040 GEN
Solar/Wind Harmer
1.225
316222AC1-221 GEN
Solar/Wind Harmer
0.857
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.951
3145593CAROLNA
Solar/Wind Harmer
0.07
3145783HORNRTN
Solar/Wind Harmer
0.982
3145783HORNRTN
Solar/Wind Harmer
0.786
3145783HORNRTN
Solar/Wind Harmer
0.245
3145783HORNRTN
Solar/Wind Harmer
0.098
316426AA2-053 GEN
Solar/Wind Harmer
0.813
316274AC1-208 GEN
Solar/Wind Harmer
0.793
942751AE2-291 GEN
Solar/Wind Harmer
4.536
972187AH1-678 GEN
Adder
1.773
972185AH1-677 GEN
Adder
3.35
3145796HORNRTN
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316359AB2-059 GEN
Solar/Wind Harmer
0.899
316049AB1-081 GEN
Solar/Wind Harmer
0.72
3142053HEARTS
Solar/Wind Harmer
0.078
315722AD1-056 GEN
Solar/Wind Harmer
0.694
316023GEN1_S
Solar/Wind Harmer
0.443
3145823KELFORD
Solar/Wind Harmer
-0.006
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.191
961671AG1-007 GEN
Solar/Wind Harmer
0.08
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
316322AB2-045
Solar/Wind Helper
0.963
3146776BUCKING
Solar/Wind Helper
0.346
316336AC2-165 C
Solar/Wind Helper
1.425
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
316263AC1-034 GEN
Solar/Wind Harmer
3.126
961601AG1-000A GEN
Solar/Wind Harmer
2.583
3145893MURPHYS
Solar/Wind Harmer
0.18
3145893MURPHYS
Solar/Wind Harmer
-0.012
3145493TOT1
Solar/Wind Harmer
0.098
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
3146776BUCKING
Solar/Wind Helper
3.457
3146776BUCKING
Solar/Wind Helper
0.28
315821AE2-092 GEN
Solar/Wind Helper
2.963
316239AB2-077_GEN
Solar/Wind Harmer
0.639
316238AB2-078_GEN
Solar/Wind Harmer
0.639
316118AC1-105 GEN
Solar/Wind Harmer
1.014
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.355
970865AG2-541 GEN
Solar/Wind Harmer
4.115
946281AF1-292 GEN
Solar/Wind Harmer
0.203
316087AB2-174 GEN
Solar/Wind Harmer
1.265
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.894
970165AG2-112 GEN
Solar/Wind Harmer
0.787
970163AG2-111 GEN
Solar/Wind Harmer
0.751
971967AH1-528 GEN
Solar/Wind Harmer
15.203
315607AA1-063A GEN
Solar/Wind Harmer
0.778
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.327
970581AG2-369 GEN
Solar/Wind Harmer
3.722
316319Z2-044 C
Solar/Wind Harmer
0.378
3146033SCOT NK
Solar/Wind Harmer
-0.027
315652AC1-086 GEN
Solar/Wind Harmer
7.562
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
965291AG1-394 GEN
Solar/Wind Harmer
0.582
970673AG2-436 GEN
Solar/Wind Harmer
13.618
970673AG2-436 GEN
Solar/Wind Harmer
6.895
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
270494AE1-108_GEN
Solar/Wind Helper
4.464
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.382
316365GEN2_N
Solar/Wind Harmer
0.443
961601AG1-000A GEN
Solar/Wind Harmer
2.615
316317KELFORD C
Solar/Wind Harmer
0.306
3145823KELFORD
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.09
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
957521AF2-046 GEN
Solar/Wind Harmer
5.039
961681AG1-008 GEN
Solar/Wind Harmer
5.039
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.311
316313AB2-026
Solar/Wind Helper
0.332
316258AE1-075 C
Solar/Wind Helper
0.299
316405AF2-144 C
Solar/Wind Helper
0.249
3148013FISHERV
Solar/Wind Helper
0.123
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.102
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.96
MECLTFEXP_MEC->PJM
CLTF
0.838
SIGELTFEXP_SIGE->PJM
CLTF
0.022
CPLELTFEXP_CPLE->PJM
CLTF
4.543
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.552
LAGNLTFEXP_LAGN->PJM
CLTF
2.505
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.252
TVALTFEXP_TVA->PJM
CLTF
1.216
NYPJM->LTFIMP_NY
CLTF
0.295
LGEELTFEXP_LGEE->PJM
CLTF
0.219
WECLTFEXP_WEC->PJM
CLTF
0.123

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2003-205_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2003-205_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:130.34 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:891.54
MW Contribution:2.9
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.19
3151601KERR 3
50/50
0.284
3151581KERR 1
50/50
0.102
3151531CLOVER1
50/50
2.917
3147043LAWRENC
50/50
1.102
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.946
971563AH1-280 GEN
Solar/Wind Harmer
4.946
970685AG2-442 GEN
Solar/Wind Harmer
31.078
962491AG1-098 GEN
Solar/Wind Harmer
14.404
316237AB2-079_GEN
Solar/Wind Harmer
0.632
315693AD1-088 GEN
Solar/Wind Harmer
10.19
970401AG2-262 GEN
Solar/Wind Harmer
1.07
3151611KERR 4
50/50
0.284
3151621KERR 5
50/50
0.284
3151631KERR 6
50/50
0.284
3151641KERR 7
50/50
0.284
3151541CLOVER2
50/50
2.903
971845AH1-439 GEN
Solar/Wind Harmer
40.178
970285AG2-188 GEN
Solar/Wind Harmer
63.671
315657AE1-056 GEN
Solar/Wind Harmer
15.898
946301AF1-294 GEN
Solar/Wind Harmer
10.139
961791AG1-021 GEN
Solar/Wind Harmer
4.946
970683AG2-441 GEN
Solar/Wind Harmer
27.748
970681AG2-440 GEN
Solar/Wind Harmer
22.198
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.073
316239AB2-077_GEN
Solar/Wind Harmer
0.632
316238AB2-078_GEN
Solar/Wind Harmer
0.632
316118AC1-105 GEN
Solar/Wind Harmer
0.997
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.254
970865AG2-541 GEN
Solar/Wind Harmer
4.048
946281AF1-292 GEN
Solar/Wind Harmer
0.204
316087AB2-174 GEN
Solar/Wind Harmer
1.262
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.884
970165AG2-112 GEN
Solar/Wind Harmer
0.778
970163AG2-111 GEN
Solar/Wind Harmer
0.742
971967AH1-528 GEN
Solar/Wind Harmer
15.039
315607AA1-063A GEN
Solar/Wind Harmer
0.762
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.212
970581AG2-369 GEN
Solar/Wind Harmer
3.623
315652AC1-086 GEN
Solar/Wind Harmer
7.469
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.026
316319Z2-044 C
Solar/Wind Harmer
0.36
970673AG2-436 GEN
Solar/Wind Harmer
13.449
970673AG2-436 GEN
Solar/Wind Harmer
6.81
965291AG1-394 GEN
Solar/Wind Harmer
0.565
270494AE1-108_GEN
Solar/Wind Helper
4.476
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
957481AF2-042 GEN
Solar/Wind Harmer
46.506
315687AD1-152 GEN
Solar/Wind Harmer
1.657
971065AG2-659 GEN
Solar/Wind Harmer
6.686
316129AC1-054 GEN
Solar/Wind Harmer
1.136
971795AH1-408 GEN
Solar/Wind Harmer
8.781
316003AC1-222 GEN
Solar/Wind Harmer
1.14
960081AF2-299 GEN
Solar/Wind Harmer
1.025
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.097
316212AC1-099_GEN
Solar/Wind Harmer
0.591
970919AG2-571 GEN
Solar/Wind Harmer
2.137
970087AG2-069 GEN
Solar/Wind Harmer
6.318
316023GEN1_S
Solar/Wind Harmer
0.452
316011AB1-132 GEN
Solar/Wind Harmer
1.389
962571AG1-106 GEN
Solar/Wind Harmer
0.954
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
-0.026
315722AD1-056 GEN
Solar/Wind Harmer
0.667
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316322AB2-045
Solar/Wind Helper
0.967
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.456
3144293JTRSVLE
50/50
1.19
3144293JTRSVLE
50/50
1.002
970535AG2-341 GEN
50/50
2.898
3152661PLYWOOD A
50/50
0.275
970301AG2-198 GEN
Solar/Wind Harmer
21.406
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.183
963191AG1-168 GEN
Solar/Wind Harmer
3.71
971741AH1-377 GEN
Solar/Wind Harmer
43.786
316034AC1-036 C
Solar/Wind Harmer
0.58
970323AG2-213 GEN
Solar/Wind Harmer
15.608
971775AH1-396 GEN
Solar/Wind Harmer
2.223
313527AB2-043 GEN
Solar/Wind Harmer
3.505
962561AG1-105 GEN
Solar/Wind Harmer
9.664
939181AE1-148 GEN
Solar/Wind Harmer
9.308
964791AG1-342 GEN
Solar/Wind Harmer
3.501
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.602
970933AG2-581 GEN
Solar/Wind Harmer
9.49
316181AB2-040 GEN
Solar/Wind Harmer
1.218
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.934
3145593CAROLNA
Solar/Wind Harmer
0.069
3145783HORNRTN
Solar/Wind Harmer
0.963
3145783HORNRTN
Solar/Wind Harmer
0.77
3145783HORNRTN
Solar/Wind Harmer
0.241
3145783HORNRTN
Solar/Wind Harmer
0.096
316222AC1-221 GEN
Solar/Wind Harmer
0.802
316426AA2-053 GEN
Solar/Wind Harmer
0.797
316274AC1-208 GEN
Solar/Wind Harmer
0.766
942751AE2-291 GEN
Solar/Wind Harmer
4.503
972187AH1-678 GEN
Adder
1.745
972185AH1-677 GEN
Adder
3.302
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3146776BUCKING
Solar/Wind Helper
3.47
3146776BUCKING
Solar/Wind Helper
0.281
315821AE2-092 GEN
Solar/Wind Helper
2.982
3144293JTRSVLE
50/50
1.19
3151591KERR 2
50/50
0.284
970413AG2-270 GEN
50/50
12.729
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.576
970909AG2-566 GEN
Solar/Wind Harmer
4.064
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.496
963181AG1-167 GEN
Solar/Wind Harmer
3.71
959311AF2-222 GEN
Solar/Wind Harmer
33.872
970257AG2-171 GEN
Solar/Wind Harmer
11.706
315785AD2-033 C
Solar/Wind Harmer
6.689
964241AG1-285 GEN
Solar/Wind Harmer
19.525
316131AB2-060 GEN
Solar/Wind Harmer
2.4
316478AD1-087 GEN
Solar/Wind Harmer
1.324
316486AD2-202 GEN
Solar/Wind Harmer
0.388
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.381
960061AF2-297 GEN
Solar/Wind Harmer
6.325
971683AH1-343 GEN
Solar/Wind Harmer
4.674
966621AG1-532 GEN
Solar/Wind Harmer
0.185
313506AB2-031 GEN
Solar/Wind Harmer
0.702
316283AC2-100 C
Solar/Wind Harmer
0.736
316210AC1-098 GEN
Solar/Wind Harmer
1.064
970917AG2-570 GEN
Solar/Wind Harmer
16.885
316365GEN2_N
Solar/Wind Harmer
0.452
316327AA2-057 GEN
Solar/Wind Harmer
0.676
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.136
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
315724AD1-057 GEN
Solar/Wind Harmer
0.367
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.312
316313AB2-026
Solar/Wind Helper
0.342
316258AE1-075 C
Solar/Wind Helper
0.307
316405AF2-144 C
Solar/Wind Helper
0.256
3148013FISHERV
Solar/Wind Helper
0.124
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.511
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.403
MECLTFEXP_MEC->PJM
CLTF
0.809
SIGELTFEXP_SIGE->PJM
CLTF
0.023
CPLELTFEXP_CPLE->PJM
CLTF
3.951
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.116
LAGNLTFEXP_LAGN->PJM
CLTF
2.085
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.001
TVALTFEXP_TVA->PJM
CLTF
1.025
NYPJM->LTFIMP_NY
CLTF
0.315
LGEELTFEXP_LGEE->PJM
CLTF
0.251
WECLTFEXP_WEC->PJM
CLTF
0.133

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:121.65 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:832.11
MW Contribution:2.87
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.186
3151601KERR 3
50/50
0.281
3151581KERR 1
50/50
0.1
3151531CLOVER1
50/50
2.882
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.932
971563AH1-280 GEN
Solar/Wind Harmer
4.932
970685AG2-442 GEN
Solar/Wind Harmer
30.976
962491AG1-098 GEN
Solar/Wind Harmer
14.277
316237AB2-079_GEN
Solar/Wind Harmer
0.628
315693AD1-088 GEN
Solar/Wind Harmer
10.093
970401AG2-262 GEN
Solar/Wind Harmer
1.069
957481AF2-042 GEN
Solar/Wind Harmer
45.841
315687AD1-152 GEN
Solar/Wind Harmer
1.641
971065AG2-659 GEN
Solar/Wind Harmer
6.575
316129AC1-054 GEN
Solar/Wind Harmer
1.116
3147043LAWRENC
Adder
1.01
316003AC1-222 GEN
Solar/Wind Harmer
1.164
971795AH1-408 GEN
Solar/Wind Harmer
8.484
960081AF2-299 GEN
Solar/Wind Harmer
0.973
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.093
316212AC1-099_GEN
Solar/Wind Harmer
0.567
970919AG2-571 GEN
Solar/Wind Harmer
2.047
970087AG2-069 GEN
Solar/Wind Harmer
6.053
3146263WOODLND
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.968
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.444
3151611KERR 4
50/50
0.281
3151621KERR 5
50/50
0.281
3151631KERR 6
50/50
0.281
3151641KERR 7
50/50
0.281
3151541CLOVER2
50/50
2.869
971845AH1-439 GEN
Solar/Wind Harmer
40.155
970285AG2-188 GEN
Solar/Wind Harmer
63.627
315657AE1-056 GEN
Solar/Wind Harmer
15.857
946301AF1-294 GEN
Solar/Wind Harmer
10.111
961791AG1-021 GEN
Solar/Wind Harmer
4.932
970683AG2-441 GEN
Solar/Wind Harmer
27.657
970681AG2-440 GEN
Solar/Wind Harmer
22.126
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.048
316239AB2-077_GEN
Solar/Wind Harmer
0.628
316238AB2-078_GEN
Solar/Wind Harmer
0.628
316118AC1-105 GEN
Solar/Wind Harmer
1
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.134
970865AG2-541 GEN
Solar/Wind Harmer
4.26
316123AC1-075 GEN
Solar/Wind Harmer
0.971
970165AG2-112 GEN
Solar/Wind Harmer
0.855
970163AG2-111 GEN
Solar/Wind Harmer
0.816
946281AF1-292 GEN
Solar/Wind Harmer
0.194
316087AB2-174 GEN
Solar/Wind Harmer
1.202
3137643SOCKMAN
Solar/Wind Harmer
-0.032
971967AH1-528 GEN
Solar/Wind Harmer
14.485
315607AA1-063A GEN
Solar/Wind Harmer
0.732
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.036
970581AG2-369 GEN
Solar/Wind Harmer
3.471
270494AE1-108_GEN
Solar/Wind Helper
4.511
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.186
3144293JTRSVLE
50/50
0.999
970535AG2-341 GEN
50/50
2.873
3152661PLYWOOD A
50/50
0.275
970301AG2-198 GEN
Solar/Wind Harmer
21.341
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.165
963191AG1-168 GEN
Solar/Wind Harmer
3.699
971741AH1-377 GEN
Solar/Wind Harmer
43.617
316034AC1-036 C
Solar/Wind Harmer
0.578
970323AG2-213 GEN
Solar/Wind Harmer
15.547
971775AH1-396 GEN
Solar/Wind Harmer
2.214
313527AB2-043 GEN
Solar/Wind Harmer
3.483
962561AG1-105 GEN
Solar/Wind Harmer
9.649
964791AG1-342 GEN
Solar/Wind Harmer
3.499
939181AE1-148 GEN
Solar/Wind Harmer
9.211
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.337
970933AG2-581 GEN
Solar/Wind Harmer
9.235
316181AB2-040 GEN
Solar/Wind Harmer
1.163
942751AE2-291 GEN
Solar/Wind Harmer
5.136
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.898
3145593CAROLNA
Solar/Wind Harmer
0.066
316222AC1-221 GEN
Solar/Wind Harmer
0.791
3145783HORNRTN
Solar/Wind Harmer
0.925
3145783HORNRTN
Solar/Wind Harmer
0.74
3145783HORNRTN
Solar/Wind Harmer
0.231
3145783HORNRTN
Solar/Wind Harmer
0.092
316426AA2-053 GEN
Solar/Wind Harmer
0.765
316274AC1-208 GEN
Solar/Wind Harmer
0.735
972187AH1-678 GEN
Adder
1.669
3146776BUCKING
Solar/Wind Helper
3.473
3146776BUCKING
Solar/Wind Helper
0.281
315821AE2-092 GEN
Solar/Wind Helper
2.981
3144293JTRSVLE
50/50
1.186
3151591KERR 2
50/50
0.281
970413AG2-270 GEN
50/50
12.579
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.561
970909AG2-566 GEN
Solar/Wind Harmer
4.052
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.429
963181AG1-167 GEN
Solar/Wind Harmer
3.699
959311AF2-222 GEN
Solar/Wind Harmer
33.746
970257AG2-171 GEN
Solar/Wind Harmer
11.66
315785AD2-033 C
Solar/Wind Harmer
6.661
964241AG1-285 GEN
Solar/Wind Harmer
19.423
316131AB2-060 GEN
Solar/Wind Harmer
2.386
316478AD1-087 GEN
Solar/Wind Harmer
1.308
316486AD2-202 GEN
Solar/Wind Harmer
0.383
316248AF1-058 C
Solar/Wind Harmer
0.384
960061AF2-297 GEN
Solar/Wind Harmer
6.368
3147043LAWRENC
Solar/Wind Harmer
-0.007
971683AH1-343 GEN
Solar/Wind Harmer
4.838
966621AG1-532 GEN
Solar/Wind Harmer
0.176
313506AB2-031 GEN
Solar/Wind Harmer
0.67
316283AC2-100 C
Solar/Wind Harmer
0.725
316210AC1-098 GEN
Solar/Wind Harmer
1.021
970917AG2-570 GEN
Solar/Wind Harmer
16.174
316327AA2-057 GEN
Solar/Wind Harmer
0.648
3146263WOODLND
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.312
316313AB2-026
Solar/Wind Helper
0.338
316258AE1-075 C
Solar/Wind Helper
0.304
316405AF2-144 C
Solar/Wind Helper
0.253
3148013FISHERV
Solar/Wind Helper
0.124
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.023
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.205
MECLTFEXP_MEC->PJM
CLTF
0.743
SIGELTFEXP_SIGE->PJM
CLTF
0.021
CPLELTFEXP_CPLE->PJM
CLTF
3.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.48
LAGNLTFEXP_LAGN->PJM
CLTF
1.974
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.732
TVALTFEXP_TVA->PJM
CLTF
0.969
NYPJM->LTFIMP_NY
CLTF
0.299
LGEELTFEXP_LGEE->PJM
CLTF
0.225
WECLTFEXP_WEC->PJM
CLTF
0.119

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.81 %
Rating:559.3 MVA
Rating Type:A
MVA to Mitigate:647.7
MW Contribution:2.85
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.279
3151621KERR 5
50/50
0.279
3151631KERR 6
50/50
0.279
3151641KERR 7
50/50
0.279
3151541CLOVER2
50/50
2.847
3151281ROARAP4
50/50
0.085
3151281ROARAP4
50/50
0.08
963041AG1-153 GEN
50/50
1.549
971845AH1-439 GEN
Solar/Wind Harmer
30.485
970285AG2-188 GEN
Solar/Wind Harmer
51.175
315657AE1-056 GEN
Solar/Wind Harmer
12.95
946301AF1-294 GEN
Solar/Wind Harmer
6.911
961791AG1-021 GEN
Solar/Wind Harmer
3.362
970683AG2-441 GEN
Solar/Wind Harmer
20.935
970681AG2-440 GEN
Solar/Wind Harmer
16.748
3144303KENBRDG
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
4.574
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.327
3147173SINAI
Solar/Wind Harmer
0.11
3147243WELCO
Solar/Wind Harmer
0.069
970831AG2-522 GEN
Solar/Wind Harmer
4.619
970865AG2-541 GEN
Solar/Wind Harmer
3.009
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.287
316123AC1-075 GEN
Solar/Wind Harmer
0.097
970165AG2-112 GEN
Solar/Wind Harmer
0.577
970163AG2-111 GEN
Solar/Wind Harmer
0.551
971967AH1-528 GEN
Solar/Wind Harmer
10.885
315607AA1-063A GEN
Solar/Wind Harmer
0.13
3146043SEABORD
Solar/Wind Harmer
0.063
970085AG2-068 GEN
Solar/Wind Harmer
3.037
970581AG2-369 GEN
Solar/Wind Harmer
2.612
270494AE1-108_GEN
Solar/Wind Helper
4.476
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.183
3144293JTRSVLE
50/50
0.996
970535AG2-341 GEN
50/50
2.851
3152661PLYWOOD A
50/50
0.269
3151041BRUNSWICKG3
50/50
0.765
972187AH1-678 GEN
50/50
1.756
970301AG2-198 GEN
Solar/Wind Harmer
16.182
3147133PAMPLIN
Solar/Wind Harmer
0.375
3147133PAMPLIN
Solar/Wind Harmer
0.3
958211AF2-115 GEN
Solar/Wind Harmer
4.203
963191AG1-168 GEN
Solar/Wind Harmer
1.401
971741AH1-377 GEN
Solar/Wind Harmer
33.06
316034AC1-036 C
Solar/Wind Harmer
0.02
970323AG2-213 GEN
Solar/Wind Harmer
11.759
971775AH1-396 GEN
Solar/Wind Harmer
0.441
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
7.224
939181AE1-148 GEN
Solar/Wind Harmer
6.94
964791AG1-342 GEN
Solar/Wind Harmer
2.755
3146843MT LREL
Solar/Wind Harmer
0.143
3146843MT LREL
Solar/Wind Harmer
0.143
970099AG2-077 GEN
Solar/Wind Harmer
13.837
970933AG2-581 GEN
Solar/Wind Harmer
6.964
316181AB2-040 GEN
Solar/Wind Harmer
0.107
3145593CAROLNA
Solar/Wind Harmer
0.07
3145593CAROLNA
Solar/Wind Harmer
0.07
966811AG1-552 GEN
Solar/Wind Harmer
0.763
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.221
3145783HORNRTN
Solar/Wind Harmer
0.977
3144293JTRSVLE
50/50
1.183
3151601KERR 3
50/50
0.279
3151581KERR 1
50/50
0.1
3151531CLOVER1
50/50
2.861
3147043LAWRENC
50/50
1.063
3151261ROARAP2
50/50
0.088
3151051BRUNSWICKS1
50/50
1.588
3151021BRUNSWICKG1
50/50
0.765
971451AH1-221 GEN
50/50
2.324
3146926FARMVIL
Solar/Wind Harmer
0.316
963171AG1-166 GEN
Solar/Wind Harmer
1.868
971563AH1-280 GEN
Solar/Wind Harmer
3.736
970685AG2-442 GEN
Solar/Wind Harmer
23.448
962491AG1-098 GEN
Solar/Wind Harmer
10.797
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
8.584
970401AG2-262 GEN
Solar/Wind Harmer
0.842
957481AF2-042 GEN
Solar/Wind Harmer
34.592
315687AD1-152 GEN
Solar/Wind Harmer
0.004
971065AG2-659 GEN
Solar/Wind Harmer
4.952
316129AC1-054 GEN
Solar/Wind Harmer
0.422
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971795AH1-408 GEN
Solar/Wind Harmer
6.656
960081AF2-299 GEN
Solar/Wind Harmer
0.732
3145783HORNRTN
Solar/Wind Harmer
0.069
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
0.296
970919AG2-571 GEN
Solar/Wind Harmer
2.029
970087AG2-069 GEN
Solar/Wind Harmer
4.556
316322AB2-045
Solar/Wind Helper
0.968
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.445
3144293JTRSVLE
50/50
1.183
3151591KERR 2
50/50
0.279
970413AG2-270 GEN
50/50
12.485
3151261ROARAP2
50/50
0.086
3151031BRUNSWICKG2
50/50
0.765
3146926FARMVIL
Solar/Wind Harmer
0.316
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.045
3147133PAMPLIN
Solar/Wind Harmer
1.178
971193AH1-056 GEN
Solar/Wind Harmer
22.863
963181AG1-167 GEN
Solar/Wind Harmer
1.401
959311AF2-222 GEN
Solar/Wind Harmer
25.479
970257AG2-171 GEN
Solar/Wind Harmer
8.819
315785AD2-033 C
Solar/Wind Harmer
2.117
964241AG1-285 GEN
Solar/Wind Harmer
14.665
316131AB2-060 GEN
Solar/Wind Harmer
0.615
316478AD1-087 GEN
Solar/Wind Harmer
0.466
316486AD2-202 GEN
Solar/Wind Harmer
0.137
3147043LAWRENC
Solar/Wind Harmer
0.066
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.708
971683AH1-343 GEN
Solar/Wind Harmer
3.476
313506AB2-031 GEN
Solar/Wind Harmer
0.227
316283AC2-100 C
Solar/Wind Harmer
0.132
316210AC1-098 GEN
Solar/Wind Harmer
0.531
970917AG2-570 GEN
Solar/Wind Harmer
5.072
316327AA2-057 GEN
Solar/Wind Harmer
0.085
3146776BUCKING
Solar/Wind Helper
0.313
316313AB2-026
Solar/Wind Helper
0.338
316258AE1-075 C
Solar/Wind Helper
0.304
316405AF2-144 C
Solar/Wind Helper
0.253
3148013FISHERV
Solar/Wind Helper
0.123
3145783HORNRTN
Solar/Wind Harmer
0.305
3145783HORNRTN
Solar/Wind Harmer
0.122
316222AC1-221 GEN
Solar/Wind Harmer
0.284
316426AA2-053 GEN
Solar/Wind Harmer
0.225
942751AE2-291 GEN
Solar/Wind Harmer
3.338
316274AC1-208 GEN
Solar/Wind Harmer
0.311
3146776BUCKING
Solar/Wind Helper
3.475
3146776BUCKING
Solar/Wind Helper
0.282
315821AE2-092 GEN
Solar/Wind Helper
2.978
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.153
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.217
MECLTFEXP_MEC->PJM
CLTF
0.756
SIGELTFEXP_SIGE->PJM
CLTF
0.021
CPLELTFEXP_CPLE->PJM
CLTF
3.789
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.54
LAGNLTFEXP_LAGN->PJM
CLTF
1.976
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.656
TVALTFEXP_TVA->PJM
CLTF
0.971
NYPJM->LTFIMP_NY
CLTF
0.298
LGEELTFEXP_LGEE->PJM
CLTF
0.232
WECLTFEXP_WEC->PJM
CLTF
0.123

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T556_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:219.98 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1537.65
MW Contribution:4.63
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.627
3152661PLYWOOD A
50/50
0.509
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.363
971741AH1-377 GEN
Solar/Wind Harmer
63.743
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.98
963191AG1-168 GEN
Solar/Wind Harmer
4.788
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.282
971775AH1-396 GEN
Solar/Wind Harmer
3.031
970933AG2-581 GEN
Solar/Wind Harmer
36.542
970099AG2-077 GEN
Solar/Wind Harmer
47.863
313527AB2-043 GEN
Solar/Wind Harmer
5.319
962561AG1-105 GEN
Solar/Wind Harmer
16.15
964791AG1-342 GEN
Solar/Wind Harmer
5.978
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.382
942751AE2-291 GEN
Solar/Wind Harmer
9.268
316222AC1-221 GEN
Solar/Wind Harmer
1.428
316181AB2-040 GEN
Solar/Wind Harmer
1.451
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.155
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.18
3145783HORNRTN
Solar/Wind Harmer
0.944
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.888
316263AC1-034 GEN
Solar/Wind Harmer
3.343
961601AG1-000A GEN
Solar/Wind Harmer
2.724
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.041
316197AC1-042 GEN
Solar/Wind Harmer
0.789
942671AE2-283 GEN
Solar/Wind Harmer
2.125
315821AE2-092 GEN
Solar/Wind Helper
2.535
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.863
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.477
972003AH1-546 GEN
Solar/Wind Harmer
49.791
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.384
971563AH1-280 GEN
Solar/Wind Harmer
6.384
970685AG2-442 GEN
Solar/Wind Harmer
41.078
962491AG1-098 GEN
Solar/Wind Harmer
28.511
315693AD1-088 GEN
Solar/Wind Harmer
20.878
957481AF2-042 GEN
Solar/Wind Harmer
119.657
316237AB2-079_GEN
Solar/Wind Harmer
0.969
315687AD1-152 GEN
Solar/Wind Harmer
3.719
970401AG2-262 GEN
Solar/Wind Harmer
1.826
316003AC1-222 GEN
Solar/Wind Harmer
2.228
971065AG2-659 GEN
Solar/Wind Harmer
10.772
316129AC1-054 GEN
Solar/Wind Harmer
1.807
971795AH1-408 GEN
Solar/Wind Harmer
11.365
960081AF2-299 GEN
Solar/Wind Harmer
1.184
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.962
316049AB1-081 GEN
Solar/Wind Harmer
0.77
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.712
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
970223AG2-152 GEN
Solar/Wind Harmer
5.769
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.191
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.405
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.316
3151541CLOVER2
50/50
6.83
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
971845AH1-439 GEN
Solar/Wind Harmer
44.827
970285AG2-188 GEN
Solar/Wind Harmer
71.81
315657AE1-056 GEN
Solar/Wind Harmer
20.233
946301AF1-294 GEN
Solar/Wind Harmer
13.088
961791AG1-021 GEN
Solar/Wind Harmer
6.384
970683AG2-441 GEN
Solar/Wind Harmer
36.677
970681AG2-440 GEN
Solar/Wind Harmer
29.342
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.305
971967AH1-528 GEN
Solar/Wind Harmer
73.277
316239AB2-077_GEN
Solar/Wind Harmer
0.969
316238AB2-078_GEN
Solar/Wind Harmer
0.969
316118AC1-105 GEN
Solar/Wind Harmer
1.805
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.02
970831AG2-522 GEN
Solar/Wind Harmer
9.81
316123AC1-075 GEN
Solar/Wind Harmer
1.786
970165AG2-112 GEN
Solar/Wind Harmer
1.573
970163AG2-111 GEN
Solar/Wind Harmer
1.5
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.489
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.631
270457AD2-023 GEN
Solar/Wind Harmer
0.827
315607AA1-063A GEN
Solar/Wind Harmer
0.88
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.41
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.561
270494AE1-108_GEN
Solar/Wind Helper
3.67
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.067
3148013FISHERV
Solar/Wind Helper
0.064
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.951
3151591KERR 2
50/50
0.482
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.336
970909AG2-566 GEN
Solar/Wind Harmer
5.575
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.721
963181AG1-167 GEN
Solar/Wind Harmer
4.788
959311AF2-222 GEN
Solar/Wind Harmer
45.74
970257AG2-171 GEN
Solar/Wind Harmer
15.961
315785AD2-033 C
Solar/Wind Harmer
9.254
964241AG1-285 GEN
Solar/Wind Harmer
28.298
316478AD1-087 GEN
Solar/Wind Harmer
3.113
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.606
316248AF1-058 C
Solar/Wind Harmer
0.74
960061AF2-297 GEN
Solar/Wind Harmer
12.278
971683AH1-343 GEN
Solar/Wind Harmer
9.189
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.301
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.773
316210AC1-098 GEN
Solar/Wind Harmer
1.19
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.758
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.392
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.405
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.318
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
3148013FISHERV
Solar/Wind Helper
0.111
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.278
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.374
MECLTFEXP_MEC->PJM
CLTF
1.462
SIGELTFEXP_SIGE->PJM
CLTF
0.043
CPLELTFEXP_CPLE->PJM
CLTF
5.212
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.402
LAGNLTFEXP_LAGN->PJM
CLTF
3.179
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.848
TVALTFEXP_TVA->PJM
CLTF
1.583
NYPJM->LTFIMP_NY
CLTF
0.53
LGEELTFEXP_LGEE->PJM
CLTF
0.51
WECLTFEXP_WEC->PJM
CLTF
0.265

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 587T591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 587T591_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:219.92 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1537.26
MW Contribution:4.63
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.535
3144293JTRSVLE
50/50
1.293
970535AG2-341 GEN
50/50
4.627
3152661PLYWOOD A
50/50
0.509
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.363
971741AH1-377 GEN
Solar/Wind Harmer
63.743
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.98
963191AG1-168 GEN
Solar/Wind Harmer
4.788
316034AC1-036 C
Solar/Wind Harmer
0.791
970323AG2-213 GEN
Solar/Wind Harmer
21.282
971775AH1-396 GEN
Solar/Wind Harmer
3.031
970933AG2-581 GEN
Solar/Wind Harmer
36.542
970099AG2-077 GEN
Solar/Wind Harmer
47.863
313527AB2-043 GEN
Solar/Wind Harmer
5.319
962561AG1-105 GEN
Solar/Wind Harmer
16.15
964791AG1-342 GEN
Solar/Wind Harmer
5.978
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.382
942751AE2-291 GEN
Solar/Wind Harmer
9.268
316222AC1-221 GEN
Solar/Wind Harmer
1.428
316181AB2-040 GEN
Solar/Wind Harmer
1.451
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.155
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.18
3145783HORNRTN
Solar/Wind Harmer
0.944
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.888
316263AC1-034 GEN
Solar/Wind Harmer
3.343
961601AG1-000A GEN
Solar/Wind Harmer
2.724
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.1
3145453TOT5
Solar/Wind Harmer
0.06
3145603CNETO
Solar/Wind Harmer
0.04
316217AC1-145 GEN
Solar/Wind Harmer
1.041
316197AC1-042 GEN
Solar/Wind Harmer
0.789
942671AE2-283 GEN
Solar/Wind Harmer
2.125
315821AE2-092 GEN
Solar/Wind Helper
2.535
3144293JTRSVLE
50/50
1.535
3151531CLOVER1
50/50
6.863
3151601KERR 3
50/50
0.482
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.477
972003AH1-546 GEN
Solar/Wind Harmer
49.791
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.384
971563AH1-280 GEN
Solar/Wind Harmer
6.384
970685AG2-442 GEN
Solar/Wind Harmer
41.078
962491AG1-098 GEN
Solar/Wind Harmer
28.511
315693AD1-088 GEN
Solar/Wind Harmer
20.878
957481AF2-042 GEN
Solar/Wind Harmer
119.657
316237AB2-079_GEN
Solar/Wind Harmer
0.969
315687AD1-152 GEN
Solar/Wind Harmer
3.719
970401AG2-262 GEN
Solar/Wind Harmer
1.826
316003AC1-222 GEN
Solar/Wind Harmer
2.228
971065AG2-659 GEN
Solar/Wind Harmer
10.772
316129AC1-054 GEN
Solar/Wind Harmer
1.807
971795AH1-408 GEN
Solar/Wind Harmer
11.365
960081AF2-299 GEN
Solar/Wind Harmer
1.184
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.661
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.962
316049AB1-081 GEN
Solar/Wind Harmer
0.77
3142053HEARTS
Solar/Wind Harmer
0.084
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.712
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
970223AG2-152 GEN
Solar/Wind Harmer
5.769
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.191
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.405
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.316
3151541CLOVER2
50/50
6.83
3151611KERR 4
50/50
0.482
3151621KERR 5
50/50
0.482
3151631KERR 6
50/50
0.482
3151641KERR 7
50/50
0.482
971845AH1-439 GEN
Solar/Wind Harmer
44.827
970285AG2-188 GEN
Solar/Wind Harmer
71.81
315657AE1-056 GEN
Solar/Wind Harmer
20.233
946301AF1-294 GEN
Solar/Wind Harmer
13.088
961791AG1-021 GEN
Solar/Wind Harmer
6.384
970683AG2-441 GEN
Solar/Wind Harmer
36.677
970681AG2-440 GEN
Solar/Wind Harmer
29.342
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.305
971967AH1-528 GEN
Solar/Wind Harmer
73.277
316239AB2-077_GEN
Solar/Wind Harmer
0.969
316238AB2-078_GEN
Solar/Wind Harmer
0.969
316118AC1-105 GEN
Solar/Wind Harmer
1.805
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
8.02
970831AG2-522 GEN
Solar/Wind Harmer
9.81
316123AC1-075 GEN
Solar/Wind Harmer
1.786
970165AG2-112 GEN
Solar/Wind Harmer
1.573
970163AG2-111 GEN
Solar/Wind Harmer
1.5
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.489
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.631
270457AD2-023 GEN
Solar/Wind Harmer
0.827
315607AA1-063A GEN
Solar/Wind Harmer
0.88
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.41
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.561
270494AE1-108_GEN
Solar/Wind Helper
3.67
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.067
3148013FISHERV
Solar/Wind Helper
0.064
3144293JTRSVLE
50/50
1.535
970413AG2-270 GEN
50/50
29.951
3151591KERR 2
50/50
0.482
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.336
970909AG2-566 GEN
Solar/Wind Harmer
5.575
3147133PAMPLIN
Solar/Wind Harmer
-0.169
971193AH1-056 GEN
Solar/Wind Harmer
33.721
963181AG1-167 GEN
Solar/Wind Harmer
4.788
959311AF2-222 GEN
Solar/Wind Harmer
45.74
970257AG2-171 GEN
Solar/Wind Harmer
15.961
315785AD2-033 C
Solar/Wind Harmer
9.254
964241AG1-285 GEN
Solar/Wind Harmer
28.298
316478AD1-087 GEN
Solar/Wind Harmer
3.113
316486AD2-202 GEN
Solar/Wind Harmer
0.912
316131AB2-060 GEN
Solar/Wind Harmer
3.606
316248AF1-058 C
Solar/Wind Harmer
0.74
960061AF2-297 GEN
Solar/Wind Harmer
12.278
971683AH1-343 GEN
Solar/Wind Harmer
9.189
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.301
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.773
316210AC1-098 GEN
Solar/Wind Harmer
1.19
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.758
3146263WOODLND
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.392
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.405
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.318
316258AE1-075 C
Solar/Wind Helper
0.286
316405AF2-144 C
Solar/Wind Helper
0.238
3148013FISHERV
Solar/Wind Helper
0.111
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.278
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.374
MECLTFEXP_MEC->PJM
CLTF
1.462
SIGELTFEXP_SIGE->PJM
CLTF
0.043
CPLELTFEXP_CPLE->PJM
CLTF
5.212
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.402
LAGNLTFEXP_LAGN->PJM
CLTF
3.179
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.848
TVALTFEXP_TVA->PJM
CLTF
1.583
NYPJM->LTFIMP_NY
CLTF
0.53
LGEELTFEXP_LGEE->PJM
CLTF
0.51
WECLTFEXP_WEC->PJM
CLTF
0.265

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 55692_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55692_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:216.35 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1512.31
MW Contribution:4.62
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.343
971741AH1-377 GEN
Solar/Wind Harmer
63.689
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.974
963191AG1-168 GEN
Solar/Wind Harmer
4.785
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.258
971775AH1-396 GEN
Solar/Wind Harmer
3.027
970933AG2-581 GEN
Solar/Wind Harmer
36.473
970099AG2-077 GEN
Solar/Wind Harmer
47.77
313527AB2-043 GEN
Solar/Wind Harmer
5.31
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
972003AH1-546 GEN
Solar/Wind Harmer
49.802
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.379
971563AH1-280 GEN
Solar/Wind Harmer
6.379
970685AG2-442 GEN
Solar/Wind Harmer
41.041
962491AG1-098 GEN
Solar/Wind Harmer
28.467
315693AD1-088 GEN
Solar/Wind Harmer
20.844
957481AF2-042 GEN
Solar/Wind Harmer
119.424
316237AB2-079_GEN
Solar/Wind Harmer
0.967
315687AD1-152 GEN
Solar/Wind Harmer
3.708
970401AG2-262 GEN
Solar/Wind Harmer
1.822
316003AC1-222 GEN
Solar/Wind Harmer
2.219
971065AG2-659 GEN
Solar/Wind Harmer
10.747
316129AC1-054 GEN
Solar/Wind Harmer
1.803
971795AH1-408 GEN
Solar/Wind Harmer
11.364
960081AF2-299 GEN
Solar/Wind Harmer
1.186
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.658
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.951
316049AB1-081 GEN
Solar/Wind Harmer
0.761
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.707
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
970223AG2-152 GEN
Solar/Wind Harmer
5.68
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.385
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.31
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.826
970285AG2-188 GEN
Solar/Wind Harmer
71.806
315657AE1-056 GEN
Solar/Wind Harmer
20.219
946301AF1-294 GEN
Solar/Wind Harmer
13.078
961791AG1-021 GEN
Solar/Wind Harmer
6.379
970683AG2-441 GEN
Solar/Wind Harmer
36.643
970681AG2-440 GEN
Solar/Wind Harmer
29.315
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.296
971967AH1-528 GEN
Solar/Wind Harmer
73.139
316239AB2-077_GEN
Solar/Wind Harmer
0.967
316238AB2-078_GEN
Solar/Wind Harmer
0.967
316118AC1-105 GEN
Solar/Wind Harmer
1.799
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.987
970831AG2-522 GEN
Solar/Wind Harmer
9.789
316123AC1-075 GEN
Solar/Wind Harmer
1.778
970165AG2-112 GEN
Solar/Wind Harmer
1.566
970163AG2-111 GEN
Solar/Wind Harmer
1.494
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.49
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.605
270457AD2-023 GEN
Solar/Wind Harmer
0.814
315607AA1-063A GEN
Solar/Wind Harmer
0.881
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.406
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.564
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
962561AG1-105 GEN
Solar/Wind Harmer
16.108
964791AG1-342 GEN
Solar/Wind Harmer
5.961
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.346
942751AE2-291 GEN
Solar/Wind Harmer
9.222
316222AC1-221 GEN
Solar/Wind Harmer
1.414
316181AB2-040 GEN
Solar/Wind Harmer
1.452
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.154
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.178
3145783HORNRTN
Solar/Wind Harmer
0.943
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.884
316263AC1-034 GEN
Solar/Wind Harmer
3.306
961601AG1-000A GEN
Solar/Wind Harmer
2.693
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
316217AC1-145 GEN
Solar/Wind Harmer
1.032
316197AC1-042 GEN
Solar/Wind Harmer
0.782
942671AE2-283 GEN
Solar/Wind Harmer
2.107
315821AE2-092 GEN
Solar/Wind Helper
2.531
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.331
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
-0.168
971193AH1-056 GEN
Solar/Wind Harmer
33.698
963181AG1-167 GEN
Solar/Wind Harmer
4.785
959311AF2-222 GEN
Solar/Wind Harmer
45.693
970257AG2-171 GEN
Solar/Wind Harmer
15.944
315785AD2-033 C
Solar/Wind Harmer
9.243
964241AG1-285 GEN
Solar/Wind Harmer
28.257
316478AD1-087 GEN
Solar/Wind Harmer
3.106
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.6
316248AF1-058 C
Solar/Wind Harmer
0.737
960061AF2-297 GEN
Solar/Wind Harmer
12.232
971683AH1-343 GEN
Solar/Wind Harmer
9.152
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.287
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.767
316210AC1-098 GEN
Solar/Wind Harmer
1.185
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.727
315724AD1-057 GEN
Solar/Wind Harmer
0.389
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.385
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 587_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 587_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:213.74 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:1221.6
MW Contribution:4.62
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.212
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.099
3146776BUCKING
Solar/Wind Harmer
3.045
3146776BUCKING
Solar/Wind Harmer
0.247
970301AG2-198 GEN
Solar/Wind Harmer
22.286
971741AH1-377 GEN
Solar/Wind Harmer
48.371
3147133PAMPLIN
Solar/Wind Harmer
0.479
3147133PAMPLIN
Solar/Wind Harmer
0.383
958211AF2-115 GEN
Solar/Wind Harmer
5.451
963191AG1-168 GEN
Solar/Wind Harmer
1.817
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.146
971775AH1-396 GEN
Solar/Wind Harmer
0.605
970933AG2-581 GEN
Solar/Wind Harmer
27.701
970099AG2-077 GEN
Solar/Wind Harmer
36.281
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.234
964791AG1-342 GEN
Solar/Wind Harmer
4.769
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.655
942751AE2-291 GEN
Solar/Wind Harmer
7.004
316222AC1-221 GEN
Solar/Wind Harmer
0.516
316181AB2-040 GEN
Solar/Wind Harmer
0.134
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.99
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.571
3145783HORNRTN
Solar/Wind Harmer
1.257
3145783HORNRTN
Solar/Wind Harmer
0.393
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.283
316274AC1-208 GEN
Solar/Wind Harmer
0.379
316263AC1-034 GEN
Solar/Wind Harmer
2.385
961601AG1-000A GEN
Solar/Wind Harmer
1.084
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.131
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.409
315821AE2-092 GEN
Solar/Wind Helper
2.531
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.952
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.158
3151411GASTONB
50/50
0.158
972003AH1-546 GEN
Solar/Wind Harmer
37.761
316322AB2-045
Solar/Wind Harmer
0.006
3146776BUCKING
Solar/Wind Harmer
0.305
3146926FARMVIL
Solar/Wind Harmer
0.38
963171AG1-166 GEN
Solar/Wind Harmer
2.423
971563AH1-280 GEN
Solar/Wind Harmer
4.845
970685AG2-442 GEN
Solar/Wind Harmer
31.17
962491AG1-098 GEN
Solar/Wind Harmer
21.62
315693AD1-088 GEN
Solar/Wind Harmer
17.81
957481AF2-042 GEN
Solar/Wind Harmer
90.702
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.457
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.163
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
8.991
960081AF2-299 GEN
Solar/Wind Harmer
0.901
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.158
3151411GASTONB
50/50
0.158
3146776BUCKING
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Harmer
0.38
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.219
963181AG1-167 GEN
Solar/Wind Harmer
1.817
959311AF2-222 GEN
Solar/Wind Harmer
34.634
970257AG2-171 GEN
Solar/Wind Harmer
12.109
315785AD2-033 C
Solar/Wind Harmer
2.951
964241AG1-285 GEN
Solar/Wind Harmer
21.461
316478AD1-087 GEN
Solar/Wind Harmer
1.114
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.934
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.29
971683AH1-343 GEN
Solar/Wind Harmer
6.951
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.286
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.624
3146233WITAKRS
Solar/Wind Harmer
0.328
3146233WITAKRS
Solar/Wind Harmer
0.044
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.061
961601AG1-000A GEN
Solar/Wind Harmer
4.335
315724AD1-057 GEN
Solar/Wind Harmer
0.226
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.811
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.103
971845AH1-439 GEN
Solar/Wind Harmer
34.045
970285AG2-188 GEN
Solar/Wind Harmer
57.782
315657AE1-056 GEN
Solar/Wind Harmer
16.55
946301AF1-294 GEN
Solar/Wind Harmer
8.963
961791AG1-021 GEN
Solar/Wind Harmer
4.361
970683AG2-441 GEN
Solar/Wind Harmer
27.831
970681AG2-440 GEN
Solar/Wind Harmer
22.264
3144303KENBRDG
Solar/Wind Harmer
0.302
971443AH1-215 GEN
Solar/Wind Harmer
6.301
971967AH1-528 GEN
Solar/Wind Harmer
55.401
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.601
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.066
970831AG2-522 GEN
Solar/Wind Harmer
7.435
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.134
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.367
315607AA1-063A GEN
Solar/Wind Harmer
0.158
3146043SEABORD
Solar/Wind Harmer
0.075
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.249
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.44
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.251
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.348
3146233WITAKRS
Solar/Wind Harmer
0.26
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
316359AB2-059 GEN
Solar/Wind Harmer
0.225
316049AB1-081 GEN
Solar/Wind Harmer
0.359
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.061
315722AD1-056 GEN
Solar/Wind Harmer
0.381
3145796HORNRTN
Solar/Wind Harmer
0.194
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.064
962571AG1-106 GEN
Solar/Wind Harmer
0.833
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.252
970223AG2-152 GEN
Solar/Wind Harmer
3.983
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.042
941801AE2-185 GEN
Solar/Wind Harmer
1.811
3145823KELFORD
Solar/Wind Harmer
0.056
316336AC2-165 C
Solar/Wind Helper
1.31
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:211.19 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:1206.97
MW Contribution:4.62
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
3151281ROARAP4
50/50
0.111
3151281ROARAP4
50/50
0.103
971845AH1-439 GEN
Solar/Wind Harmer
34.045
970285AG2-188 GEN
Solar/Wind Harmer
57.782
315657AE1-056 GEN
Solar/Wind Harmer
16.55
946301AF1-294 GEN
Solar/Wind Harmer
8.963
961791AG1-021 GEN
Solar/Wind Harmer
4.361
970683AG2-441 GEN
Solar/Wind Harmer
27.831
970681AG2-440 GEN
Solar/Wind Harmer
22.264
3144303KENBRDG
Solar/Wind Harmer
0.302
971443AH1-215 GEN
Solar/Wind Harmer
6.301
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.601
3147173SINAI
Solar/Wind Harmer
0.218
3147243WELCO
Solar/Wind Harmer
0.136
970865AG2-541 GEN
Solar/Wind Harmer
6.066
970831AG2-522 GEN
Solar/Wind Harmer
7.435
316123AC1-075 GEN
Solar/Wind Harmer
0.201
970165AG2-112 GEN
Solar/Wind Harmer
1.189
970163AG2-111 GEN
Solar/Wind Harmer
1.134
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.367
315607AA1-063A GEN
Solar/Wind Harmer
0.158
3146043SEABORD
Solar/Wind Harmer
0.075
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.249
3145796HORNRTN
Solar/Wind Harmer
0.189
3145796HORNRTN
Solar/Wind Harmer
0.024
315652AC1-086 GEN
Solar/Wind Harmer
6.44
3145573BETHELC
Solar/Wind Harmer
0.057
3145573BETHELC
Solar/Wind Harmer
0.057
965291AG1-394 GEN
Solar/Wind Harmer
0.251
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3151361ROSEMG1
50/50
0.212
3151371ROSEMS1
50/50
0.132
3151381ROSEMG2
50/50
0.099
3146776BUCKING
Solar/Wind Harmer
3.045
3146776BUCKING
Solar/Wind Harmer
0.247
970301AG2-198 GEN
Solar/Wind Harmer
22.286
971741AH1-377 GEN
Solar/Wind Harmer
48.371
3147133PAMPLIN
Solar/Wind Harmer
0.479
3147133PAMPLIN
Solar/Wind Harmer
0.383
958211AF2-115 GEN
Solar/Wind Harmer
5.451
963191AG1-168 GEN
Solar/Wind Harmer
1.817
316034AC1-036 C
Solar/Wind Harmer
0.028
970323AG2-213 GEN
Solar/Wind Harmer
16.146
971775AH1-396 GEN
Solar/Wind Harmer
0.605
970099AG2-077 GEN
Solar/Wind Harmer
36.281
313527AB2-043 GEN
Solar/Wind Harmer
0.004
962561AG1-105 GEN
Solar/Wind Harmer
12.234
964791AG1-342 GEN
Solar/Wind Harmer
4.769
3146843MT LREL
Solar/Wind Harmer
0.248
3146843MT LREL
Solar/Wind Harmer
0.248
939181AE1-148 GEN
Solar/Wind Harmer
11.655
942751AE2-291 GEN
Solar/Wind Harmer
7.004
316222AC1-221 GEN
Solar/Wind Harmer
0.516
316181AB2-040 GEN
Solar/Wind Harmer
0.134
3145593CAROLNA
Solar/Wind Harmer
0.091
3145593CAROLNA
Solar/Wind Harmer
0.091
966811AG1-552 GEN
Solar/Wind Harmer
0.99
3145593CAROLNA
Solar/Wind Harmer
0.114
3145783HORNRTN
Solar/Wind Harmer
1.571
3145783HORNRTN
Solar/Wind Harmer
1.257
3145783HORNRTN
Solar/Wind Harmer
0.393
3145783HORNRTN
Solar/Wind Harmer
0.157
316426AA2-053 GEN
Solar/Wind Harmer
0.283
316274AC1-208 GEN
Solar/Wind Harmer
0.379
316263AC1-034 GEN
Solar/Wind Harmer
2.385
961601AG1-000A GEN
Solar/Wind Harmer
1.084
3145796HORNRTN
Solar/Wind Harmer
0.177
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3142666NORTHAMPTON
Solar/Wind Harmer
0.035
3145493TOT1
Solar/Wind Harmer
0.131
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
316217AC1-145 GEN
Solar/Wind Harmer
0.001
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
1.409
315821AE2-092 GEN
Solar/Wind Helper
2.531
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
3151261ROARAP2
50/50
0.114
971629AH1-314 GEN
50/50
5.952
3151561HALLBR1
50/50
0.172
3151391GASTONA
50/50
0.158
3151411GASTONB
50/50
0.158
972003AH1-546 GEN
Solar/Wind Harmer
37.761
316322AB2-045
Solar/Wind Harmer
0.006
3146776BUCKING
Solar/Wind Harmer
0.305
3146926FARMVIL
Solar/Wind Harmer
0.38
963171AG1-166 GEN
Solar/Wind Harmer
2.423
971563AH1-280 GEN
Solar/Wind Harmer
4.845
970685AG2-442 GEN
Solar/Wind Harmer
31.17
962491AG1-098 GEN
Solar/Wind Harmer
21.62
315693AD1-088 GEN
Solar/Wind Harmer
17.81
957481AF2-042 GEN
Solar/Wind Harmer
90.702
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315687AD1-152 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.457
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
8.163
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
8.991
960081AF2-299 GEN
Solar/Wind Harmer
0.901
3145783HORNRTN
Solar/Wind Harmer
0.088
316190AA2-174 GEN
Solar/Wind Harmer
0
3147123OTTER R
Solar/Wind Harmer
0.042
316212AC1-099_GEN
Solar/Wind Harmer
0.348
3146233WITAKRS
Solar/Wind Harmer
0.26
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
316359AB2-059 GEN
Solar/Wind Harmer
0.225
316049AB1-081 GEN
Solar/Wind Harmer
0.359
3142053HEARTS
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.061
315722AD1-056 GEN
Solar/Wind Harmer
0.381
3145796HORNRTN
Solar/Wind Harmer
0.194
3145796HORNRTN
Solar/Wind Harmer
0.059
316011AB1-132 GEN
Solar/Wind Harmer
1.064
962571AG1-106 GEN
Solar/Wind Harmer
0.833
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.057
3145493TOT1
Solar/Wind Harmer
0.252
970223AG2-152 GEN
Solar/Wind Harmer
3.983
3147312GRETNA
Solar/Wind Harmer
0.045
3146802CHATHAM
Solar/Wind Harmer
0.042
941801AE2-185 GEN
Solar/Wind Harmer
1.811
3145823KELFORD
Solar/Wind Harmer
0.056
316336AC2-165 C
Solar/Wind Helper
1.31
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3151261ROARAP2
50/50
0.111
3151391GASTONA
50/50
0.158
3151411GASTONB
50/50
0.158
3146776BUCKING
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Harmer
0.38
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
1.506
971193AH1-056 GEN
Solar/Wind Harmer
29.219
963181AG1-167 GEN
Solar/Wind Harmer
1.817
959311AF2-222 GEN
Solar/Wind Harmer
34.634
970257AG2-171 GEN
Solar/Wind Harmer
12.109
315785AD2-033 C
Solar/Wind Harmer
2.951
964241AG1-285 GEN
Solar/Wind Harmer
21.461
316478AD1-087 GEN
Solar/Wind Harmer
1.114
316486AD2-202 GEN
Solar/Wind Harmer
0.327
316131AB2-060 GEN
Solar/Wind Harmer
0.934
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.29
971683AH1-343 GEN
Solar/Wind Harmer
6.951
3147043LAWRENC
Solar/Wind Harmer
0.092
316283AC2-100 C
Solar/Wind Harmer
0.238
313506AB2-031 GEN
Solar/Wind Harmer
0.286
316327AA2-057 GEN
Solar/Wind Harmer
0.102
316210AC1-098 GEN
Solar/Wind Harmer
0.624
3146233WITAKRS
Solar/Wind Harmer
0.328
3146233WITAKRS
Solar/Wind Harmer
0.044
3138543CONSLDL
Solar/Wind Harmer
0.043
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3146263WOODLND
Solar/Wind Harmer
0.061
961601AG1-000A GEN
Solar/Wind Harmer
4.335
315724AD1-057 GEN
Solar/Wind Harmer
0.226
3145796HORNRTN
Solar/Wind Harmer
0.236
3145796HORNRTN
Solar/Wind Harmer
0.059
3142666NORTHAMPTON
Solar/Wind Harmer
0.058
3146073TAR RVR
Solar/Wind Harmer
0.057
3146083TARBORO
Solar/Wind Harmer
0.057
3147312GRETNA
Solar/Wind Harmer
0.011
941821AE2-187 GEN
Solar/Wind Harmer
1.811
316317KELFORD C
Solar/Wind Harmer
0.005
3145823KELFORD
Solar/Wind Harmer
0.056
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:210.43 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1470.9
MW Contribution:4.62
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
972003AH1-546 GEN
Solar/Wind Harmer
49.802
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.379
971563AH1-280 GEN
Solar/Wind Harmer
6.379
970685AG2-442 GEN
Solar/Wind Harmer
41.041
962491AG1-098 GEN
Solar/Wind Harmer
28.467
315693AD1-088 GEN
Solar/Wind Harmer
20.844
957481AF2-042 GEN
Solar/Wind Harmer
119.424
316237AB2-079_GEN
Solar/Wind Harmer
0.967
315687AD1-152 GEN
Solar/Wind Harmer
3.708
970401AG2-262 GEN
Solar/Wind Harmer
1.822
316003AC1-222 GEN
Solar/Wind Harmer
2.219
971065AG2-659 GEN
Solar/Wind Harmer
10.747
316129AC1-054 GEN
Solar/Wind Harmer
1.803
971795AH1-408 GEN
Solar/Wind Harmer
11.364
960081AF2-299 GEN
Solar/Wind Harmer
1.186
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.658
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.951
316049AB1-081 GEN
Solar/Wind Harmer
0.761
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.707
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
970223AG2-152 GEN
Solar/Wind Harmer
5.68
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.385
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.31
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.331
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
-0.168
971193AH1-056 GEN
Solar/Wind Harmer
33.698
963181AG1-167 GEN
Solar/Wind Harmer
4.785
959311AF2-222 GEN
Solar/Wind Harmer
45.693
970257AG2-171 GEN
Solar/Wind Harmer
15.944
315785AD2-033 C
Solar/Wind Harmer
9.243
964241AG1-285 GEN
Solar/Wind Harmer
28.257
316478AD1-087 GEN
Solar/Wind Harmer
3.106
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.6
316248AF1-058 C
Solar/Wind Harmer
0.737
960061AF2-297 GEN
Solar/Wind Harmer
12.232
971683AH1-343 GEN
Solar/Wind Harmer
9.152
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.287
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.767
316210AC1-098 GEN
Solar/Wind Harmer
1.185
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.727
315724AD1-057 GEN
Solar/Wind Harmer
0.389
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.385
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.343
971741AH1-377 GEN
Solar/Wind Harmer
63.689
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.974
963191AG1-168 GEN
Solar/Wind Harmer
4.785
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.258
971775AH1-396 GEN
Solar/Wind Harmer
3.027
970099AG2-077 GEN
Solar/Wind Harmer
47.77
313527AB2-043 GEN
Solar/Wind Harmer
5.31
962561AG1-105 GEN
Solar/Wind Harmer
16.108
964791AG1-342 GEN
Solar/Wind Harmer
5.961
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.346
942751AE2-291 GEN
Solar/Wind Harmer
9.222
316222AC1-221 GEN
Solar/Wind Harmer
1.414
316181AB2-040 GEN
Solar/Wind Harmer
1.452
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.154
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.178
3145783HORNRTN
Solar/Wind Harmer
0.943
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.884
316263AC1-034 GEN
Solar/Wind Harmer
3.306
961601AG1-000A GEN
Solar/Wind Harmer
2.693
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
316217AC1-145 GEN
Solar/Wind Harmer
1.032
316197AC1-042 GEN
Solar/Wind Harmer
0.782
942671AE2-283 GEN
Solar/Wind Harmer
2.107
315821AE2-092 GEN
Solar/Wind Helper
2.531
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.826
970285AG2-188 GEN
Solar/Wind Harmer
71.806
315657AE1-056 GEN
Solar/Wind Harmer
20.219
946301AF1-294 GEN
Solar/Wind Harmer
13.078
961791AG1-021 GEN
Solar/Wind Harmer
6.379
970683AG2-441 GEN
Solar/Wind Harmer
36.643
970681AG2-440 GEN
Solar/Wind Harmer
29.315
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.296
316239AB2-077_GEN
Solar/Wind Harmer
0.967
316238AB2-078_GEN
Solar/Wind Harmer
0.967
316118AC1-105 GEN
Solar/Wind Harmer
1.799
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.987
970831AG2-522 GEN
Solar/Wind Harmer
9.789
316123AC1-075 GEN
Solar/Wind Harmer
1.778
970165AG2-112 GEN
Solar/Wind Harmer
1.566
970163AG2-111 GEN
Solar/Wind Harmer
1.494
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.49
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.605
270457AD2-023 GEN
Solar/Wind Harmer
0.814
315607AA1-063A GEN
Solar/Wind Harmer
0.881
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.406
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.564
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:210.43 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:1470.9
MW Contribution:4.62
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.534
970413AG2-270 GEN
50/50
29.885
3151591KERR 2
50/50
0.481
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.042
942461AE2-259 GEN
Solar/Wind Harmer
9.331
970909AG2-566 GEN
Solar/Wind Harmer
5.571
3147133PAMPLIN
Solar/Wind Harmer
-0.168
971193AH1-056 GEN
Solar/Wind Harmer
33.698
963181AG1-167 GEN
Solar/Wind Harmer
4.785
959311AF2-222 GEN
Solar/Wind Harmer
45.693
3144293JTRSVLE
50/50
1.534
3144293JTRSVLE
50/50
1.292
970535AG2-341 GEN
50/50
4.618
3152661PLYWOOD A
50/50
0.507
3146776BUCKING
Solar/Wind Harmer
-0.341
3146776BUCKING
Solar/Wind Harmer
-0.028
970301AG2-198 GEN
Solar/Wind Harmer
29.343
971741AH1-377 GEN
Solar/Wind Harmer
63.689
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.043
958211AF2-115 GEN
Solar/Wind Harmer
7.974
963191AG1-168 GEN
Solar/Wind Harmer
4.785
316034AC1-036 C
Solar/Wind Harmer
0.79
970323AG2-213 GEN
Solar/Wind Harmer
21.258
971775AH1-396 GEN
Solar/Wind Harmer
3.027
970099AG2-077 GEN
Solar/Wind Harmer
47.77
313527AB2-043 GEN
Solar/Wind Harmer
5.31
962561AG1-105 GEN
Solar/Wind Harmer
16.108
964791AG1-342 GEN
Solar/Wind Harmer
5.961
3146843MT LREL
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.028
939181AE1-148 GEN
Solar/Wind Harmer
15.346
942751AE2-291 GEN
Solar/Wind Harmer
9.222
316222AC1-221 GEN
Solar/Wind Harmer
1.414
316181AB2-040 GEN
Solar/Wind Harmer
1.452
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.154
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.178
3145783HORNRTN
Solar/Wind Harmer
0.943
3145783HORNRTN
Solar/Wind Harmer
0.295
3145783HORNRTN
Solar/Wind Harmer
0.118
316426AA2-053 GEN
Solar/Wind Harmer
0.953
316274AC1-208 GEN
Solar/Wind Harmer
0.884
316263AC1-034 GEN
Solar/Wind Harmer
3.306
961601AG1-000A GEN
Solar/Wind Harmer
2.693
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.099
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
316217AC1-145 GEN
Solar/Wind Harmer
1.032
316197AC1-042 GEN
Solar/Wind Harmer
0.782
942671AE2-283 GEN
Solar/Wind Harmer
2.107
315821AE2-092 GEN
Solar/Wind Helper
2.531
3144293JTRSVLE
50/50
1.534
3151531CLOVER1
50/50
6.848
3151601KERR 3
50/50
0.481
3151581KERR 1
50/50
0.172
3147043LAWRENC
50/50
1.476
972003AH1-546 GEN
Solar/Wind Harmer
49.802
316322AB2-045
Solar/Wind Harmer
2.879
3146776BUCKING
Solar/Wind Harmer
-0.034
3146926FARMVIL
Solar/Wind Harmer
-0.042
963171AG1-166 GEN
Solar/Wind Harmer
6.379
971563AH1-280 GEN
Solar/Wind Harmer
6.379
970685AG2-442 GEN
Solar/Wind Harmer
41.041
962491AG1-098 GEN
Solar/Wind Harmer
28.467
315693AD1-088 GEN
Solar/Wind Harmer
20.844
957481AF2-042 GEN
Solar/Wind Harmer
119.424
316237AB2-079_GEN
Solar/Wind Harmer
0.967
315687AD1-152 GEN
Solar/Wind Harmer
3.708
970401AG2-262 GEN
Solar/Wind Harmer
1.822
316003AC1-222 GEN
Solar/Wind Harmer
2.219
971065AG2-659 GEN
Solar/Wind Harmer
10.747
316129AC1-054 GEN
Solar/Wind Harmer
1.803
971795AH1-408 GEN
Solar/Wind Harmer
11.364
960081AF2-299 GEN
Solar/Wind Harmer
1.186
3145783HORNRTN
Solar/Wind Harmer
-0.01
316190AA2-174 GEN
Solar/Wind Harmer
0.116
3147123OTTER R
Solar/Wind Harmer
-0.005
316212AC1-099_GEN
Solar/Wind Harmer
0.658
3146233WITAKRS
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.951
316049AB1-081 GEN
Solar/Wind Harmer
0.761
3142053HEARTS
Solar/Wind Harmer
0.083
3146263WOODLND
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.707
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.377
962571AG1-106 GEN
Solar/Wind Harmer
0.946
961671AG1-007 GEN
Solar/Wind Harmer
0.081
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
970223AG2-152 GEN
Solar/Wind Harmer
5.68
3147312GRETNA
Solar/Wind Harmer
-0.005
3146802CHATHAM
Solar/Wind Harmer
-0.005
941801AE2-185 GEN
Solar/Wind Harmer
2.385
3145823KELFORD
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
1.31
970257AG2-171 GEN
Solar/Wind Harmer
15.944
315785AD2-033 C
Solar/Wind Harmer
9.243
964241AG1-285 GEN
Solar/Wind Harmer
28.257
316478AD1-087 GEN
Solar/Wind Harmer
3.106
316486AD2-202 GEN
Solar/Wind Harmer
0.91
316131AB2-060 GEN
Solar/Wind Harmer
3.6
316248AF1-058 C
Solar/Wind Harmer
0.737
960061AF2-297 GEN
Solar/Wind Harmer
12.232
971683AH1-343 GEN
Solar/Wind Harmer
9.152
3147043LAWRENC
Solar/Wind Harmer
-0.01
316283AC2-100 C
Solar/Wind Harmer
1.287
966621AG1-532 GEN
Solar/Wind Harmer
0.214
313506AB2-031 GEN
Solar/Wind Harmer
0.836
316327AA2-057 GEN
Solar/Wind Harmer
0.767
316210AC1-098 GEN
Solar/Wind Harmer
1.185
3146233WITAKRS
Solar/Wind Harmer
0.154
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.727
315724AD1-057 GEN
Solar/Wind Harmer
0.389
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.001
941821AE2-187 GEN
Solar/Wind Harmer
2.385
316317KELFORD C
Solar/Wind Harmer
0.298
3145823KELFORD
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.316
316258AE1-075 C
Solar/Wind Helper
0.285
316405AF2-144 C
Solar/Wind Helper
0.237
3151541CLOVER2
50/50
6.815
3151611KERR 4
50/50
0.481
3151621KERR 5
50/50
0.481
3151631KERR 6
50/50
0.481
3151641KERR 7
50/50
0.481
971845AH1-439 GEN
Solar/Wind Harmer
44.826
970285AG2-188 GEN
Solar/Wind Harmer
71.806
315657AE1-056 GEN
Solar/Wind Harmer
20.219
946301AF1-294 GEN
Solar/Wind Harmer
13.078
961791AG1-021 GEN
Solar/Wind Harmer
6.379
970683AG2-441 GEN
Solar/Wind Harmer
36.643
970681AG2-440 GEN
Solar/Wind Harmer
29.315
3144303KENBRDG
Solar/Wind Harmer
-0.034
971443AH1-215 GEN
Solar/Wind Harmer
8.296
316239AB2-077_GEN
Solar/Wind Harmer
0.967
316238AB2-078_GEN
Solar/Wind Harmer
0.967
316118AC1-105 GEN
Solar/Wind Harmer
1.799
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
7.987
970831AG2-522 GEN
Solar/Wind Harmer
9.789
316123AC1-075 GEN
Solar/Wind Harmer
1.778
970165AG2-112 GEN
Solar/Wind Harmer
1.566
970163AG2-111 GEN
Solar/Wind Harmer
1.494
946281AF1-292 GEN
Solar/Wind Harmer
0.236
316087AB2-174 GEN
Solar/Wind Harmer
1.49
3137643SOCKMAN
Solar/Wind Harmer
-0.041
270455AD2-022 GEN
Solar/Wind Harmer
1.605
270457AD2-023 GEN
Solar/Wind Harmer
0.814
315607AA1-063A GEN
Solar/Wind Harmer
0.881
3146043SEABORD
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.406
3146033SCOT NK
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
315652AC1-086 GEN
Solar/Wind Harmer
7.403
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.564
270494AE1-108_GEN
Solar/Wind Helper
3.668
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.005
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.981
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.221
MECLTFEXP_MEC->PJM
CLTF
1.417
SIGELTFEXP_SIGE->PJM
CLTF
0.042
CPLELTFEXP_CPLE->PJM
CLTF
5.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.925
LAGNLTFEXP_LAGN->PJM
CLTF
3.089
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.572
TVALTFEXP_TVA->PJM
CLTF
1.538
NYPJM->LTFIMP_NY
CLTF
0.516
LGEELTFEXP_LGEE->PJM
CLTF
0.494
WECLTFEXP_WEC->PJM
CLTF
0.257

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:137.05 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:957.97
MW Contribution:2.93
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.195
3151601KERR 3
50/50
0.288
3151581KERR 1
50/50
0.103
3151531CLOVER1
50/50
2.951
3147043LAWRENC
50/50
1.104
972003AH1-546 GEN
Solar/Wind Harmer
47.347
316322AB2-045
Solar/Wind Harmer
2.6
3146776BUCKING
Solar/Wind Harmer
-0.031
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.967
971563AH1-280 GEN
Solar/Wind Harmer
4.967
970685AG2-442 GEN
Solar/Wind Harmer
31.227
962491AG1-098 GEN
Solar/Wind Harmer
14.504
316237AB2-079_GEN
Solar/Wind Harmer
0.638
315693AD1-088 GEN
Solar/Wind Harmer
10.264
970401AG2-262 GEN
Solar/Wind Harmer
1.084
957481AF2-042 GEN
Solar/Wind Harmer
46.952
315687AD1-152 GEN
Solar/Wind Harmer
1.686
971065AG2-659 GEN
Solar/Wind Harmer
6.782
316129AC1-054 GEN
Solar/Wind Harmer
1.152
316003AC1-222 GEN
Solar/Wind Harmer
1.16
971795AH1-408 GEN
Solar/Wind Harmer
8.774
960081AF2-299 GEN
Solar/Wind Harmer
1.019
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
316212AC1-099_GEN
Solar/Wind Harmer
0.612
970919AG2-571 GEN
Solar/Wind Harmer
2.186
970087AG2-069 GEN
Solar/Wind Harmer
6.469
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.401
962571AG1-106 GEN
Solar/Wind Harmer
0.963
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316359AB2-059 GEN
Solar/Wind Harmer
0.896
316049AB1-081 GEN
Solar/Wind Harmer
0.717
3142053HEARTS
Solar/Wind Harmer
0.078
315722AD1-056 GEN
Solar/Wind Harmer
0.692
316023GEN1_S
Solar/Wind Harmer
0.442
3145823KELFORD
Solar/Wind Harmer
-0.006
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.19
961671AG1-007 GEN
Solar/Wind Harmer
0.08
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.188
316336AC2-165 C
Solar/Wind Helper
1.427
3144293JTRSVLE
50/50
1.195
3144293JTRSVLE
50/50
1.006
970535AG2-341 GEN
50/50
2.93
3152661PLYWOOD A
50/50
0.279
3146776BUCKING
Solar/Wind Harmer
-0.308
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.483
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.209
963191AG1-168 GEN
Solar/Wind Harmer
3.725
971741AH1-377 GEN
Solar/Wind Harmer
43.964
316034AC1-036 C
Solar/Wind Harmer
0.583
970323AG2-213 GEN
Solar/Wind Harmer
15.694
971775AH1-396 GEN
Solar/Wind Harmer
2.235
313527AB2-043 GEN
Solar/Wind Harmer
3.534
962561AG1-105 GEN
Solar/Wind Harmer
9.782
939181AE1-148 GEN
Solar/Wind Harmer
9.427
964791AG1-342 GEN
Solar/Wind Harmer
3.547
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
3151611KERR 4
50/50
0.288
3151621KERR 5
50/50
0.288
3151631KERR 6
50/50
0.288
3151641KERR 7
50/50
0.288
3151541CLOVER2
50/50
2.937
971845AH1-439 GEN
Solar/Wind Harmer
40.264
970285AG2-188 GEN
Solar/Wind Harmer
63.811
315657AE1-056 GEN
Solar/Wind Harmer
15.96
946301AF1-294 GEN
Solar/Wind Harmer
10.183
961791AG1-021 GEN
Solar/Wind Harmer
4.967
970683AG2-441 GEN
Solar/Wind Harmer
27.881
970681AG2-440 GEN
Solar/Wind Harmer
22.305
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.107
316239AB2-077_GEN
Solar/Wind Harmer
0.638
316238AB2-078_GEN
Solar/Wind Harmer
0.638
316118AC1-105 GEN
Solar/Wind Harmer
1.013
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.344
970865AG2-541 GEN
Solar/Wind Harmer
4.105
946281AF1-292 GEN
Solar/Wind Harmer
0.203
316087AB2-174 GEN
Solar/Wind Harmer
1.262
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.891
970165AG2-112 GEN
Solar/Wind Harmer
0.785
970163AG2-111 GEN
Solar/Wind Harmer
0.749
971967AH1-528 GEN
Solar/Wind Harmer
15.159
315607AA1-063A GEN
Solar/Wind Harmer
0.776
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.313
970581AG2-369 GEN
Solar/Wind Harmer
3.709
316319Z2-044 C
Solar/Wind Harmer
0.377
3146033SCOT NK
Solar/Wind Harmer
-0.027
315652AC1-086 GEN
Solar/Wind Harmer
7.536
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
965291AG1-394 GEN
Solar/Wind Harmer
0.58
970673AG2-436 GEN
Solar/Wind Harmer
13.57
970673AG2-436 GEN
Solar/Wind Harmer
6.871
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
270494AE1-108_GEN
Solar/Wind Helper
4.47
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.195
3151591KERR 2
50/50
0.288
970413AG2-270 GEN
50/50
12.878
3146776BUCKING
Solar/Wind Harmer
-0.028
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.6
970909AG2-566 GEN
Solar/Wind Harmer
4.079
3147133PAMPLIN
Solar/Wind Harmer
-0.133
971193AH1-056 GEN
Solar/Wind Harmer
26.601
963181AG1-167 GEN
Solar/Wind Harmer
3.725
959311AF2-222 GEN
Solar/Wind Harmer
34.052
970257AG2-171 GEN
Solar/Wind Harmer
11.771
315785AD2-033 C
Solar/Wind Harmer
6.728
964241AG1-285 GEN
Solar/Wind Harmer
19.662
316131AB2-060 GEN
Solar/Wind Harmer
2.419
316478AD1-087 GEN
Solar/Wind Harmer
1.34
316486AD2-202 GEN
Solar/Wind Harmer
0.392
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.389
960061AF2-297 GEN
Solar/Wind Harmer
6.446
971683AH1-343 GEN
Solar/Wind Harmer
4.749
966621AG1-532 GEN
Solar/Wind Harmer
0.184
313506AB2-031 GEN
Solar/Wind Harmer
0.704
316283AC2-100 C
Solar/Wind Harmer
0.785
316210AC1-098 GEN
Solar/Wind Harmer
1.101
316327AA2-057 GEN
Solar/Wind Harmer
0.705
970917AG2-570 GEN
Solar/Wind Harmer
17.269
3146233WITAKRS
Solar/Wind Harmer
0.143
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.004
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.38
316365GEN2_N
Solar/Wind Harmer
0.442
961601AG1-000A GEN
Solar/Wind Harmer
2.606
316317KELFORD C
Solar/Wind Harmer
0.305
3145823KELFORD
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.082
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
957521AF2-046 GEN
Solar/Wind Harmer
5.021
961681AG1-008 GEN
Solar/Wind Harmer
5.021
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.333
316258AE1-075 C
Solar/Wind Helper
0.299
316405AF2-144 C
Solar/Wind Helper
0.249
3148013FISHERV
Solar/Wind Helper
0.124
970099AG2-077 GEN
Solar/Wind Harmer
18.781
970933AG2-581 GEN
Solar/Wind Harmer
9.57
316181AB2-040 GEN
Solar/Wind Harmer
1.222
316222AC1-221 GEN
Solar/Wind Harmer
0.854
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.948
3145593CAROLNA
Solar/Wind Harmer
0.07
3145783HORNRTN
Solar/Wind Harmer
0.979
3145783HORNRTN
Solar/Wind Harmer
0.783
3145783HORNRTN
Solar/Wind Harmer
0.245
3145783HORNRTN
Solar/Wind Harmer
0.098
316426AA2-053 GEN
Solar/Wind Harmer
0.81
316274AC1-208 GEN
Solar/Wind Harmer
0.791
942751AE2-291 GEN
Solar/Wind Harmer
4.521
972187AH1-678 GEN
Adder
1.767
972185AH1-677 GEN
Adder
3.338
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
316263AC1-034 GEN
Solar/Wind Harmer
3.115
961601AG1-000A GEN
Solar/Wind Harmer
2.573
3145893MURPHYS
Solar/Wind Harmer
0.179
3145893MURPHYS
Solar/Wind Harmer
-0.012
3145493TOT1
Solar/Wind Harmer
0.098
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
315821AE2-092 GEN
Solar/Wind Helper
2.966
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.871
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.899
MECLTFEXP_MEC->PJM
CLTF
0.811
SIGELTFEXP_SIGE->PJM
CLTF
0.021
CPLELTFEXP_CPLE->PJM
CLTF
4.525
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.338
LAGNLTFEXP_LAGN->PJM
CLTF
2.472
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.204
TVALTFEXP_TVA->PJM
CLTF
1.2
NYPJM->LTFIMP_NY
CLTF
0.305
LGEELTFEXP_LGEE->PJM
CLTF
0.208
WECLTFEXP_WEC->PJM
CLTF
0.117

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2106-2111_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2106-2111_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:136.87 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:956.69
MW Contribution:2.83
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.179
3151601KERR 3
50/50
0.277
3151581KERR 1
50/50
0.099
3151531CLOVER1
50/50
2.838
972003AH1-546 GEN
Solar/Wind Harmer
47.205
316322AB2-045
Solar/Wind Harmer
2.588
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.904
971563AH1-280 GEN
Solar/Wind Harmer
4.904
970685AG2-442 GEN
Solar/Wind Harmer
30.768
962491AG1-098 GEN
Solar/Wind Harmer
14.136
316237AB2-079_GEN
Solar/Wind Harmer
0.62
315693AD1-088 GEN
Solar/Wind Harmer
9.987
970401AG2-262 GEN
Solar/Wind Harmer
1.044
957481AF2-042 GEN
Solar/Wind Harmer
45.172
315687AD1-152 GEN
Solar/Wind Harmer
1.609
971065AG2-659 GEN
Solar/Wind Harmer
6.46
316129AC1-054 GEN
Solar/Wind Harmer
1.096
3147043LAWRENC
Adder
0.992
316003AC1-222 GEN
Solar/Wind Harmer
1.105
971795AH1-408 GEN
Solar/Wind Harmer
8.324
960081AF2-299 GEN
Solar/Wind Harmer
0.951
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.091
316336AC2-165 C
Solar/Wind Helper
1.456
3151611KERR 4
50/50
0.277
3151621KERR 5
50/50
0.277
3151631KERR 6
50/50
0.277
3151641KERR 7
50/50
0.277
3151541CLOVER2
50/50
2.825
971845AH1-439 GEN
Solar/Wind Harmer
40.074
970285AG2-188 GEN
Solar/Wind Harmer
63.49
315657AE1-056 GEN
Solar/Wind Harmer
15.775
946301AF1-294 GEN
Solar/Wind Harmer
10.053
961791AG1-021 GEN
Solar/Wind Harmer
4.904
970683AG2-441 GEN
Solar/Wind Harmer
27.471
970681AG2-440 GEN
Solar/Wind Harmer
21.977
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
5.999
316239AB2-077_GEN
Solar/Wind Harmer
0.62
316238AB2-078_GEN
Solar/Wind Harmer
0.62
316118AC1-105 GEN
Solar/Wind Harmer
0.971
3147173SINAI
Solar/Wind Harmer
-0.012
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.022
970865AG2-541 GEN
Solar/Wind Harmer
3.914
946281AF1-292 GEN
Solar/Wind Harmer
0.189
316087AB2-174 GEN
Solar/Wind Harmer
1.174
3137643SOCKMAN
Solar/Wind Harmer
-0.032
316123AC1-075 GEN
Solar/Wind Harmer
0.851
970165AG2-112 GEN
Solar/Wind Harmer
0.749
970163AG2-111 GEN
Solar/Wind Harmer
0.714
971967AH1-528 GEN
Solar/Wind Harmer
14.144
315607AA1-063A GEN
Solar/Wind Harmer
0.713
3146043SEABORD
Solar/Wind Harmer
-0.007
270494AE1-108_GEN
Solar/Wind Helper
4.505
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3144293JTRSVLE
50/50
1.179
3144293JTRSVLE
50/50
0.993
970535AG2-341 GEN
50/50
2.832
3152661PLYWOOD A
50/50
0.267
3146776BUCKING
Solar/Wind Harmer
-0.306
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.246
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.13
963191AG1-168 GEN
Solar/Wind Harmer
3.678
971741AH1-377 GEN
Solar/Wind Harmer
43.39
316034AC1-036 C
Solar/Wind Harmer
0.573
970323AG2-213 GEN
Solar/Wind Harmer
15.422
971775AH1-396 GEN
Solar/Wind Harmer
2.196
313527AB2-043 GEN
Solar/Wind Harmer
3.438
962561AG1-105 GEN
Solar/Wind Harmer
9.444
939181AE1-148 GEN
Solar/Wind Harmer
9.07
964791AG1-342 GEN
Solar/Wind Harmer
3.418
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.069
970933AG2-581 GEN
Solar/Wind Harmer
9.057
316181AB2-040 GEN
Solar/Wind Harmer
1.135
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.876
3145593CAROLNA
Solar/Wind Harmer
0.065
3145783HORNRTN
Solar/Wind Harmer
0.902
3145783HORNRTN
Solar/Wind Harmer
0.721
3145783HORNRTN
Solar/Wind Harmer
0.225
3145783HORNRTN
Solar/Wind Harmer
0.09
316222AC1-221 GEN
Solar/Wind Harmer
0.766
316426AA2-053 GEN
Solar/Wind Harmer
0.746
942751AE2-291 GEN
Solar/Wind Harmer
4.318
316274AC1-208 GEN
Solar/Wind Harmer
0.714
972187AH1-678 GEN
Adder
1.624
315821AE2-092 GEN
Solar/Wind Helper
2.997
3144293JTRSVLE
50/50
1.179
3151591KERR 2
50/50
0.277
970413AG2-270 GEN
50/50
12.386
3146776BUCKING
Solar/Wind Harmer
-0.027
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.532
970909AG2-566 GEN
Solar/Wind Harmer
4.034
3147133PAMPLIN
Solar/Wind Harmer
-0.131
971193AH1-056 GEN
Solar/Wind Harmer
26.292
963181AG1-167 GEN
Solar/Wind Harmer
3.678
959311AF2-222 GEN
Solar/Wind Harmer
33.489
970257AG2-171 GEN
Solar/Wind Harmer
11.567
315785AD2-033 C
Solar/Wind Harmer
6.603
964241AG1-285 GEN
Solar/Wind Harmer
19.215
316131AB2-060 GEN
Solar/Wind Harmer
2.356
316478AD1-087 GEN
Solar/Wind Harmer
1.288
316486AD2-202 GEN
Solar/Wind Harmer
0.377
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.37
960061AF2-297 GEN
Solar/Wind Harmer
6.139
971683AH1-343 GEN
Solar/Wind Harmer
4.525
966621AG1-532 GEN
Solar/Wind Harmer
0.171
313506AB2-031 GEN
Solar/Wind Harmer
0.654
316283AC2-100 C
Solar/Wind Harmer
0.703
316313AB2-026
Solar/Wind Helper
0.341
316258AE1-075 C
Solar/Wind Helper
0.307
316405AF2-144 C
Solar/Wind Helper
0.256
3148013FISHERV
Solar/Wind Helper
0.125
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.959
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.906
MECLTFEXP_MEC->PJM
CLTF
0.618
SIGELTFEXP_SIGE->PJM
CLTF
0.017
CPLELTFEXP_CPLE->PJM
CLTF
3.699
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.437
LAGNLTFEXP_LAGN->PJM
CLTF
1.81
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.409
TVALTFEXP_TVA->PJM
CLTF
0.888
NYPJM->LTFIMP_NY
CLTF
0.351
LGEELTFEXP_LGEE->PJM
CLTF
0.175
WECLTFEXP_WEC->PJM
CLTF
0.091

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2003-205_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2003-205_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:133.52 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:933.31
MW Contribution:2.9
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.189
3151591KERR 2
50/50
0.284
970413AG2-270 GEN
50/50
12.71
3146776BUCKING
Solar/Wind Harmer
-0.027
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.572
970909AG2-566 GEN
Solar/Wind Harmer
4.062
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.482
963181AG1-167 GEN
Solar/Wind Harmer
3.707
959311AF2-222 GEN
Solar/Wind Harmer
33.848
970257AG2-171 GEN
Solar/Wind Harmer
11.697
315785AD2-033 C
Solar/Wind Harmer
6.684
3144293JTRSVLE
50/50
1.189
3151601KERR 3
50/50
0.284
3151581KERR 1
50/50
0.101
3151531CLOVER1
50/50
2.913
3147043LAWRENC
50/50
1.1
972003AH1-546 GEN
Solar/Wind Harmer
47.254
316322AB2-045
Solar/Wind Harmer
2.593
3146776BUCKING
Solar/Wind Harmer
-0.031
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.943
971563AH1-280 GEN
Solar/Wind Harmer
4.943
970685AG2-442 GEN
Solar/Wind Harmer
31.058
962491AG1-098 GEN
Solar/Wind Harmer
14.389
316237AB2-079_GEN
Solar/Wind Harmer
0.632
315693AD1-088 GEN
Solar/Wind Harmer
10.178
970401AG2-262 GEN
Solar/Wind Harmer
1.068
957481AF2-042 GEN
Solar/Wind Harmer
46.433
315687AD1-152 GEN
Solar/Wind Harmer
1.654
971065AG2-659 GEN
Solar/Wind Harmer
6.674
316129AC1-054 GEN
Solar/Wind Harmer
1.134
971795AH1-408 GEN
Solar/Wind Harmer
8.763
316003AC1-222 GEN
Solar/Wind Harmer
1.138
960081AF2-299 GEN
Solar/Wind Harmer
1.022
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.097
316212AC1-099_GEN
Solar/Wind Harmer
0.589
970919AG2-571 GEN
Solar/Wind Harmer
2.13
970087AG2-069 GEN
Solar/Wind Harmer
6.297
316023GEN1_S
Solar/Wind Harmer
0.451
316011AB1-132 GEN
Solar/Wind Harmer
1.384
962571AG1-106 GEN
Solar/Wind Harmer
0.951
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
-0.026
315722AD1-056 GEN
Solar/Wind Harmer
0.665
316336AC2-165 C
Solar/Wind Helper
1.458
964241AG1-285 GEN
Solar/Wind Harmer
19.507
316131AB2-060 GEN
Solar/Wind Harmer
2.398
316478AD1-087 GEN
Solar/Wind Harmer
1.322
316486AD2-202 GEN
Solar/Wind Harmer
0.387
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.38
960061AF2-297 GEN
Solar/Wind Harmer
6.313
971683AH1-343 GEN
Solar/Wind Harmer
4.664
966621AG1-532 GEN
Solar/Wind Harmer
0.184
313506AB2-031 GEN
Solar/Wind Harmer
0.7
316283AC2-100 C
Solar/Wind Harmer
0.734
316210AC1-098 GEN
Solar/Wind Harmer
1.061
970917AG2-570 GEN
Solar/Wind Harmer
16.827
316365GEN2_N
Solar/Wind Harmer
0.451
316327AA2-057 GEN
Solar/Wind Harmer
0.674
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.136
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
315724AD1-057 GEN
Solar/Wind Harmer
0.366
316313AB2-026
Solar/Wind Helper
0.342
316258AE1-075 C
Solar/Wind Helper
0.308
316405AF2-144 C
Solar/Wind Helper
0.257
3148013FISHERV
Solar/Wind Helper
0.124
3144293JTRSVLE
50/50
1.189
3144293JTRSVLE
50/50
1.001
970535AG2-341 GEN
50/50
2.895
3152661PLYWOOD A
50/50
0.274
3146776BUCKING
Solar/Wind Harmer
-0.307
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.395
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.179
963191AG1-168 GEN
Solar/Wind Harmer
3.707
971741AH1-377 GEN
Solar/Wind Harmer
43.759
316034AC1-036 C
Solar/Wind Harmer
0.58
970323AG2-213 GEN
Solar/Wind Harmer
15.596
971775AH1-396 GEN
Solar/Wind Harmer
2.221
313527AB2-043 GEN
Solar/Wind Harmer
3.501
962561AG1-105 GEN
Solar/Wind Harmer
9.651
939181AE1-148 GEN
Solar/Wind Harmer
9.294
964791AG1-342 GEN
Solar/Wind Harmer
3.496
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.573
970933AG2-581 GEN
Solar/Wind Harmer
9.469
316181AB2-040 GEN
Solar/Wind Harmer
1.215
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.932
3145593CAROLNA
Solar/Wind Harmer
0.069
3145783HORNRTN
Solar/Wind Harmer
0.96
3145783HORNRTN
Solar/Wind Harmer
0.768
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
316222AC1-221 GEN
Solar/Wind Harmer
0.8
316426AA2-053 GEN
Solar/Wind Harmer
0.794
316274AC1-208 GEN
Solar/Wind Harmer
0.763
942751AE2-291 GEN
Solar/Wind Harmer
4.488
972187AH1-678 GEN
Adder
1.739
972185AH1-677 GEN
Adder
3.291
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
315821AE2-092 GEN
Solar/Wind Helper
2.986
3151611KERR 4
50/50
0.284
3151621KERR 5
50/50
0.284
3151631KERR 6
50/50
0.284
3151641KERR 7
50/50
0.284
3151541CLOVER2
50/50
2.899
971845AH1-439 GEN
Solar/Wind Harmer
40.166
970285AG2-188 GEN
Solar/Wind Harmer
63.65
315657AE1-056 GEN
Solar/Wind Harmer
15.889
946301AF1-294 GEN
Solar/Wind Harmer
10.133
961791AG1-021 GEN
Solar/Wind Harmer
4.943
970683AG2-441 GEN
Solar/Wind Harmer
27.73
970681AG2-440 GEN
Solar/Wind Harmer
22.184
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.068
316239AB2-077_GEN
Solar/Wind Harmer
0.632
316238AB2-078_GEN
Solar/Wind Harmer
0.632
316118AC1-105 GEN
Solar/Wind Harmer
0.995
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.242
970865AG2-541 GEN
Solar/Wind Harmer
4.039
946281AF1-292 GEN
Solar/Wind Harmer
0.204
316087AB2-174 GEN
Solar/Wind Harmer
1.259
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.881
970165AG2-112 GEN
Solar/Wind Harmer
0.776
970163AG2-111 GEN
Solar/Wind Harmer
0.74
971967AH1-528 GEN
Solar/Wind Harmer
14.996
315607AA1-063A GEN
Solar/Wind Harmer
0.76
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.198
970581AG2-369 GEN
Solar/Wind Harmer
3.61
315652AC1-086 GEN
Solar/Wind Harmer
7.443
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.026
316319Z2-044 C
Solar/Wind Harmer
0.358
970673AG2-436 GEN
Solar/Wind Harmer
13.401
970673AG2-436 GEN
Solar/Wind Harmer
6.785
965291AG1-394 GEN
Solar/Wind Harmer
0.563
270494AE1-108_GEN
Solar/Wind Helper
4.481
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.279
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.343
MECLTFEXP_MEC->PJM
CLTF
0.782
SIGELTFEXP_SIGE->PJM
CLTF
0.022
CPLELTFEXP_CPLE->PJM
CLTF
3.934
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.902
LAGNLTFEXP_LAGN->PJM
CLTF
2.053
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.953
TVALTFEXP_TVA->PJM
CLTF
1.009
NYPJM->LTFIMP_NY
CLTF
0.325
LGEELTFEXP_LGEE->PJM
CLTF
0.24
WECLTFEXP_WEC->PJM
CLTF
0.127

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:125.05 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:874.1
MW Contribution:2.87
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.186
3144293JTRSVLE
50/50
0.998
970535AG2-341 GEN
50/50
2.87
3152661PLYWOOD A
50/50
0.275
3146776BUCKING
Solar/Wind Harmer
-0.307
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.329
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.162
963191AG1-168 GEN
Solar/Wind Harmer
3.697
971741AH1-377 GEN
Solar/Wind Harmer
43.59
316034AC1-036 C
Solar/Wind Harmer
0.577
970323AG2-213 GEN
Solar/Wind Harmer
15.535
971775AH1-396 GEN
Solar/Wind Harmer
2.212
313527AB2-043 GEN
Solar/Wind Harmer
3.479
962561AG1-105 GEN
Solar/Wind Harmer
9.636
964791AG1-342 GEN
Solar/Wind Harmer
3.494
3151611KERR 4
50/50
0.281
3151621KERR 5
50/50
0.281
3151631KERR 6
50/50
0.281
3151641KERR 7
50/50
0.281
3151541CLOVER2
50/50
2.864
971845AH1-439 GEN
Solar/Wind Harmer
40.143
970285AG2-188 GEN
Solar/Wind Harmer
63.606
315657AE1-056 GEN
Solar/Wind Harmer
15.849
946301AF1-294 GEN
Solar/Wind Harmer
10.105
961791AG1-021 GEN
Solar/Wind Harmer
4.929
970683AG2-441 GEN
Solar/Wind Harmer
27.639
970681AG2-440 GEN
Solar/Wind Harmer
22.111
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.044
316239AB2-077_GEN
Solar/Wind Harmer
0.628
316238AB2-078_GEN
Solar/Wind Harmer
0.628
316118AC1-105 GEN
Solar/Wind Harmer
0.998
3144293JTRSVLE
50/50
1.186
3151601KERR 3
50/50
0.281
3151581KERR 1
50/50
0.1
3151531CLOVER1
50/50
2.878
972003AH1-546 GEN
Solar/Wind Harmer
47.257
316322AB2-045
Solar/Wind Harmer
2.592
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.929
971563AH1-280 GEN
Solar/Wind Harmer
4.929
970685AG2-442 GEN
Solar/Wind Harmer
30.955
962491AG1-098 GEN
Solar/Wind Harmer
14.261
316237AB2-079_GEN
Solar/Wind Harmer
0.628
315693AD1-088 GEN
Solar/Wind Harmer
10.081
970401AG2-262 GEN
Solar/Wind Harmer
1.068
957481AF2-042 GEN
Solar/Wind Harmer
45.769
315687AD1-152 GEN
Solar/Wind Harmer
1.638
971065AG2-659 GEN
Solar/Wind Harmer
6.564
316129AC1-054 GEN
Solar/Wind Harmer
1.114
3147043LAWRENC
Adder
1.008
316003AC1-222 GEN
Solar/Wind Harmer
1.162
971795AH1-408 GEN
Solar/Wind Harmer
8.467
960081AF2-299 GEN
Solar/Wind Harmer
0.97
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.093
316212AC1-099_GEN
Solar/Wind Harmer
0.565
970919AG2-571 GEN
Solar/Wind Harmer
2.04
970087AG2-069 GEN
Solar/Wind Harmer
6.032
316336AC2-165 C
Solar/Wind Helper
1.446
939181AE1-148 GEN
Solar/Wind Harmer
9.198
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.308
970933AG2-581 GEN
Solar/Wind Harmer
9.214
316181AB2-040 GEN
Solar/Wind Harmer
1.159
942751AE2-291 GEN
Solar/Wind Harmer
5.121
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.895
3145593CAROLNA
Solar/Wind Harmer
0.066
316222AC1-221 GEN
Solar/Wind Harmer
0.788
3145783HORNRTN
Solar/Wind Harmer
0.922
3145783HORNRTN
Solar/Wind Harmer
0.738
3145783HORNRTN
Solar/Wind Harmer
0.231
3145783HORNRTN
Solar/Wind Harmer
0.092
316426AA2-053 GEN
Solar/Wind Harmer
0.763
316274AC1-208 GEN
Solar/Wind Harmer
0.732
972187AH1-678 GEN
Adder
1.663
315821AE2-092 GEN
Solar/Wind Helper
2.985
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.123
970865AG2-541 GEN
Solar/Wind Harmer
4.251
316123AC1-075 GEN
Solar/Wind Harmer
0.968
970165AG2-112 GEN
Solar/Wind Harmer
0.853
970163AG2-111 GEN
Solar/Wind Harmer
0.813
946281AF1-292 GEN
Solar/Wind Harmer
0.193
316087AB2-174 GEN
Solar/Wind Harmer
1.199
3137643SOCKMAN
Solar/Wind Harmer
-0.032
971967AH1-528 GEN
Solar/Wind Harmer
14.441
315607AA1-063A GEN
Solar/Wind Harmer
0.73
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.021
970581AG2-369 GEN
Solar/Wind Harmer
3.458
270494AE1-108_GEN
Solar/Wind Helper
4.516
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.186
3151591KERR 2
50/50
0.281
970413AG2-270 GEN
50/50
12.559
3146776BUCKING
Solar/Wind Harmer
-0.027
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.558
970909AG2-566 GEN
Solar/Wind Harmer
4.05
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.415
963181AG1-167 GEN
Solar/Wind Harmer
3.697
959311AF2-222 GEN
Solar/Wind Harmer
33.722
970257AG2-171 GEN
Solar/Wind Harmer
11.651
315785AD2-033 C
Solar/Wind Harmer
6.656
964241AG1-285 GEN
Solar/Wind Harmer
19.405
316131AB2-060 GEN
Solar/Wind Harmer
2.383
316478AD1-087 GEN
Solar/Wind Harmer
1.306
316486AD2-202 GEN
Solar/Wind Harmer
0.383
316248AF1-058 C
Solar/Wind Harmer
0.383
960061AF2-297 GEN
Solar/Wind Harmer
6.356
3147043LAWRENC
Solar/Wind Harmer
-0.007
971683AH1-343 GEN
Solar/Wind Harmer
4.828
966621AG1-532 GEN
Solar/Wind Harmer
0.175
313506AB2-031 GEN
Solar/Wind Harmer
0.668
316283AC2-100 C
Solar/Wind Harmer
0.723
316210AC1-098 GEN
Solar/Wind Harmer
1.017
970917AG2-570 GEN
Solar/Wind Harmer
16.116
316327AA2-057 GEN
Solar/Wind Harmer
0.646
316313AB2-026
Solar/Wind Helper
0.338
316258AE1-075 C
Solar/Wind Helper
0.304
316405AF2-144 C
Solar/Wind Helper
0.253
3148013FISHERV
Solar/Wind Helper
0.124
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.791
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.144
MECLTFEXP_MEC->PJM
CLTF
0.716
SIGELTFEXP_SIGE->PJM
CLTF
0.02
CPLELTFEXP_CPLE->PJM
CLTF
3.818
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.266
LAGNLTFEXP_LAGN->PJM
CLTF
1.942
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.684
TVALTFEXP_TVA->PJM
CLTF
0.953
NYPJM->LTFIMP_NY
CLTF
0.309
LGEELTFEXP_LGEE->PJM
CLTF
0.214
WECLTFEXP_WEC->PJM
CLTF
0.113

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.94 %
Rating:571.52 MVA
Rating Type:A
MVA to Mitigate:679.77
MW Contribution:2.85
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.182
3151601KERR 3
50/50
0.278
3151581KERR 1
50/50
0.099
3151531CLOVER1
50/50
2.857
3147043LAWRENC
50/50
1.061
3151261ROARAP2
50/50
0.087
3151051BRUNSWICKS1
50/50
1.582
3151021BRUNSWICKG1
50/50
0.762
971451AH1-221 GEN
50/50
2.315
972003AH1-546 GEN
Solar/Wind Harmer
35.828
316322AB2-045
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Harmer
0.316
963171AG1-166 GEN
Solar/Wind Harmer
1.867
971563AH1-280 GEN
Solar/Wind Harmer
3.734
970685AG2-442 GEN
Solar/Wind Harmer
23.432
962491AG1-098 GEN
Solar/Wind Harmer
10.785
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
8.574
970401AG2-262 GEN
Solar/Wind Harmer
0.841
957481AF2-042 GEN
Solar/Wind Harmer
34.537
315687AD1-152 GEN
Solar/Wind Harmer
0.004
971065AG2-659 GEN
Solar/Wind Harmer
4.943
316129AC1-054 GEN
Solar/Wind Harmer
0.422
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971795AH1-408 GEN
Solar/Wind Harmer
6.643
960081AF2-299 GEN
Solar/Wind Harmer
0.73
3145783HORNRTN
Solar/Wind Harmer
0.068
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
0.295
970919AG2-571 GEN
Solar/Wind Harmer
2.021
970087AG2-069 GEN
Solar/Wind Harmer
4.539
316336AC2-165 C
Solar/Wind Helper
1.447
3144293JTRSVLE
50/50
1.182
3151591KERR 2
50/50
0.278
970413AG2-270 GEN
50/50
12.466
3151261ROARAP2
50/50
0.085
3151031BRUNSWICKG2
50/50
0.762
3146776BUCKING
Solar/Wind Harmer
0.247
3146926FARMVIL
Solar/Wind Harmer
0.316
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.043
3147133PAMPLIN
Solar/Wind Harmer
1.178
971193AH1-056 GEN
Solar/Wind Harmer
22.85
963181AG1-167 GEN
Solar/Wind Harmer
1.4
959311AF2-222 GEN
Solar/Wind Harmer
25.461
970257AG2-171 GEN
Solar/Wind Harmer
8.812
315785AD2-033 C
Solar/Wind Harmer
2.115
964241AG1-285 GEN
Solar/Wind Harmer
14.651
316131AB2-060 GEN
Solar/Wind Harmer
0.614
316478AD1-087 GEN
Solar/Wind Harmer
0.465
316486AD2-202 GEN
Solar/Wind Harmer
0.137
3147043LAWRENC
Solar/Wind Harmer
0.066
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.699
971683AH1-343 GEN
Solar/Wind Harmer
3.468
313506AB2-031 GEN
Solar/Wind Harmer
0.226
316283AC2-100 C
Solar/Wind Harmer
0.132
316210AC1-098 GEN
Solar/Wind Harmer
0.53
970917AG2-570 GEN
Solar/Wind Harmer
5.054
316327AA2-057 GEN
Solar/Wind Harmer
0.085
316313AB2-026
Solar/Wind Helper
0.339
316258AE1-075 C
Solar/Wind Helper
0.305
316405AF2-144 C
Solar/Wind Helper
0.254
3148013FISHERV
Solar/Wind Helper
0.124
3144293JTRSVLE
50/50
1.182
3144293JTRSVLE
50/50
0.996
970535AG2-341 GEN
50/50
2.848
3152661PLYWOOD A
50/50
0.269
3151041BRUNSWICKG3
50/50
0.762
972187AH1-678 GEN
50/50
1.749
3146776BUCKING
Solar/Wind Harmer
2.741
3146776BUCKING
Solar/Wind Harmer
0.222
970301AG2-198 GEN
Solar/Wind Harmer
16.173
3147133PAMPLIN
Solar/Wind Harmer
0.375
3147133PAMPLIN
Solar/Wind Harmer
0.3
958211AF2-115 GEN
Solar/Wind Harmer
4.2
963191AG1-168 GEN
Solar/Wind Harmer
1.4
971741AH1-377 GEN
Solar/Wind Harmer
33.04
316034AC1-036 C
Solar/Wind Harmer
0.02
970323AG2-213 GEN
Solar/Wind Harmer
11.75
971775AH1-396 GEN
Solar/Wind Harmer
0.441
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
7.214
939181AE1-148 GEN
Solar/Wind Harmer
6.93
964791AG1-342 GEN
Solar/Wind Harmer
2.751
3146843MT LREL
Solar/Wind Harmer
0.143
3146843MT LREL
Solar/Wind Harmer
0.143
970099AG2-077 GEN
Solar/Wind Harmer
13.815
970933AG2-581 GEN
Solar/Wind Harmer
6.948
316181AB2-040 GEN
Solar/Wind Harmer
0.106
3145593CAROLNA
Solar/Wind Harmer
0.07
3145593CAROLNA
Solar/Wind Harmer
0.07
966811AG1-552 GEN
Solar/Wind Harmer
0.761
3145593CAROLNA
Solar/Wind Harmer
0.087
3145783HORNRTN
Solar/Wind Harmer
1.218
3145783HORNRTN
Solar/Wind Harmer
0.974
3145783HORNRTN
Solar/Wind Harmer
0.304
3145783HORNRTN
Solar/Wind Harmer
0.122
316222AC1-221 GEN
Solar/Wind Harmer
0.283
316426AA2-053 GEN
Solar/Wind Harmer
0.225
942751AE2-291 GEN
Solar/Wind Harmer
3.327
316274AC1-208 GEN
Solar/Wind Harmer
0.31
315821AE2-092 GEN
Solar/Wind Helper
2.982
3151611KERR 4
50/50
0.278
3151621KERR 5
50/50
0.278
3151631KERR 6
50/50
0.278
3151641KERR 7
50/50
0.278
3151541CLOVER2
50/50
2.843
3151281ROARAP4
50/50
0.085
3151281ROARAP4
50/50
0.079
963041AG1-153 GEN
50/50
1.544
971845AH1-439 GEN
Solar/Wind Harmer
30.475
970285AG2-188 GEN
Solar/Wind Harmer
51.158
315657AE1-056 GEN
Solar/Wind Harmer
12.943
946301AF1-294 GEN
Solar/Wind Harmer
6.907
961791AG1-021 GEN
Solar/Wind Harmer
3.36
970683AG2-441 GEN
Solar/Wind Harmer
20.922
970681AG2-440 GEN
Solar/Wind Harmer
16.737
3144303KENBRDG
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
4.571
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.326
3147173SINAI
Solar/Wind Harmer
0.11
3147243WELCO
Solar/Wind Harmer
0.069
970831AG2-522 GEN
Solar/Wind Harmer
4.61
970865AG2-541 GEN
Solar/Wind Harmer
3.002
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.286
316123AC1-075 GEN
Solar/Wind Harmer
0.097
970165AG2-112 GEN
Solar/Wind Harmer
0.576
970163AG2-111 GEN
Solar/Wind Harmer
0.549
971967AH1-528 GEN
Solar/Wind Harmer
10.852
315607AA1-063A GEN
Solar/Wind Harmer
0.13
3146043SEABORD
Solar/Wind Harmer
0.063
970085AG2-068 GEN
Solar/Wind Harmer
3.026
970581AG2-369 GEN
Solar/Wind Harmer
2.602
270494AE1-108_GEN
Solar/Wind Helper
4.482
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.922
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.157
MECLTFEXP_MEC->PJM
CLTF
0.729
SIGELTFEXP_SIGE->PJM
CLTF
0.02
CPLELTFEXP_CPLE->PJM
CLTF
3.771
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.326
LAGNLTFEXP_LAGN->PJM
CLTF
1.944
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.608
TVALTFEXP_TVA->PJM
CLTF
0.955
NYPJM->LTFIMP_NY
CLTF
0.308
LGEELTFEXP_LGEE->PJM
CLTF
0.221
WECLTFEXP_WEC->PJM
CLTF
0.117
CONTINGENCY 'DVP_P1-2: LN 593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P1-2: LN 587_SRT-A-1'
 OPEN BRANCH FROM BUS 313985 TO BUS 970932 CKT 1   /*8UNITY       500.0 - AG2-581 TP   500.0
END
CONTINGENCY 'DVP_P4-3: CLOUD H222_SRT-A'
 OPEN BRANCH FROM BUS 313757 TO BUS 313785 CKT 2   /*3CLOUD       115.0 - 6CLOUD       230.0
END
CONTINGENCY 'DVP_P4-2: 222922-4_SRT-A'
 OPEN BRANCH FROM BUS 313757 TO BUS 313785 CKT 2   /*3CLOUD       115.0 - 6CLOUD       230.0
 OPEN BRANCH FROM BUS 313785 TO BUS 313786 CKT 1   /*6CLOUD       230.0 - 6EASTERS     230.0
END
CONTINGENCY 'DVP_P4-3: CLOUD H122_SRT-A'
 OPEN BRANCH FROM BUS 313757 TO BUS 313785 CKT 1   /*3CLOUD       115.0 - 6CLOUD       230.0
END
CONTINGENCY 'DVP_P4-2: 222922-3_SRT-A'
 OPEN BRANCH FROM BUS 313757 TO BUS 313785 CKT 1   /*3CLOUD       115.0 - 6CLOUD       230.0
 OPEN BRANCH FROM BUS 313785 TO BUS 313786 CKT 1   /*6CLOUD       230.0 - 6EASTERS     230.0
END
CONTINGENCY 'DVP_P1-2: LN 2201_SRT-S'
 OPEN BRANCH FROM BUS 313725 TO BUS 314563 CKT 1                /*6DRY BREAD   230.0 - 6CLUBHSE     230.0
 SET POSTCONTRATING 1047 BRANCH FROM BUS 313725 TO BUS 314583 CKT 1 /*6DRY BREAD   230.0 - 6LAKEVEW     230.0
 SET PRECONTRATING 956 BRANCH FROM BUS 313725 TO BUS 314583 CKT 1 /*6DRY BREAD   230.0 - 6LAKEVEW     230.0
END
CONTINGENCY 'DVP_P1-2: LN 254_SRT-S'
 OPEN BRANCH FROM BUS 313725 TO BUS 314583 CKT 1                /*6DRY BREAD   230.0 - 6LAKEVEW     230.0
 SET POSTCONTRATING 1047 BRANCH FROM BUS 313725 TO BUS 314563 CKT 1 /*6DRY BREAD   230.0 - 6CLUBHSE     230.0
 SET POSTCONTRATING 1292 BRANCH FROM BUS 314561 TO BUS 314583 CKT 1 /*6CAROLNA     230.0 - 6LAKEVEW     230.0
 SET PRECONTRATING 1168 BRANCH FROM BUS 314561 TO BUS 314583 CKT 1 /*6CAROLNA     230.0 - 6LAKEVEW     230.0
 SET PRECONTRATING 956 BRANCH FROM BUS 313725 TO BUS 314563 CKT 1 /*6DRY BREAD   230.0 - 6CLUBHSE     230.0
END
CONTINGENCY 'DVP_P1-2: LN 298_SRT-A-1'
 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2   /*3FARMVIL     115.0 - 6FARMVIL     230.0
 OPEN BRANCH FROM BUS 970284 TO BUS 314692 CKT 1   /*AG2-188 TP   230.0 - 6FARMVIL     230.0
END
CONTINGENCY 'DVP_P1-2: LN 235_SRT-A-4'
 OPEN BRANCH FROM BUS 314268 TO BUS 314692 CKT 1   /*6BRIERY      230.0 - 6FARMVIL     230.0
 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1   /*3FARMVIL     115.0 - 6FARMVIL     230.0
 OPEN BRANCH FROM BUS 970300 TO BUS 314268 CKT 1   /*AG2-198 TP   230.0 - 6BRIERY      230.0
 OPEN BUS 314268                                   /*6BRIERY      230.0
END
CONTINGENCY 'DVP_P1-2: LN 1012_SRT-A-2'
 OPEN BRANCH FROM BUS 964240 TO BUS 314681 CKT 1   /*AG1-285 TP   115.0 - 3CHASCTY     115.0
END
CONTINGENCY 'DVP_P7-1: LN 1041-38_SRT-A'
 OPEN BRANCH FROM BUS 313099 TO BUS 314674 CKT 1   /*3BOYDTON DP  115.0 - 3BOYDTON TAP 115.0
 OPEN BRANCH FROM BUS 313757 TO BUS 314674 CKT 1   /*3CLOUD       115.0 - 3BOYDTON TAP 115.0
 OPEN BRANCH FROM BUS 313757 TO BUS 314702 CKT 1   /*3CLOUD       115.0 - 3KERR        115.0
 OPEN BRANCH FROM BUS 314255 TO BUS 314674 CKT 1   /*3BOYDPLK     115.0 - 3BOYDTON TAP 115.0
 OPEN BUS 313099                                   /*3BOYDTON DP  115.0
 OPEN BUS 314674                                   /*3BOYDTON TAP 115.0
END
CONTINGENCY 'DVP_P7-1: LN 1041-137_SRT-A'
 OPEN BRANCH FROM BUS 313099 TO BUS 314674 CKT 1   /*3BOYDTON DP  115.0 - 3BOYDTON TAP 115.0
 OPEN BRANCH FROM BUS 313757 TO BUS 314674 CKT 1   /*3CLOUD       115.0 - 3BOYDTON TAP 115.0
 OPEN BRANCH FROM BUS 313791 TO BUS 314702 CKT 1   /*3BISHOP      115.0 - 3KERR        115.0
 OPEN BRANCH FROM BUS 314255 TO BUS 314674 CKT 1   /*3BOYDPLK     115.0 - 3BOYDTON TAP 115.0
 OPEN BUS 313099                                   /*3BOYDTON DP  115.0
 OPEN BUS 314674                                   /*3BOYDTON TAP 115.0
END
CONTINGENCY 'DVP_P4-2: 55692_SRT-S'
 OPEN BRANCH FROM BUS 314936 TO BUS 971966 CKT 1                /*8RAWLINGS    500.0 - AH1-528 TP   500.0
 OPEN BUS 314920                                                /*8RAWLIN_STC1 500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-5: 593X2_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
 OPEN BRANCH FROM BUS 313995 TO BUS 313996 CKT 2   /*8FINNEYWOOD  500.0 - 6FINNEYWOOD  230.0
END
CONTINGENCY 'DVP_P4-5: 593X1_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
 OPEN BRANCH FROM BUS 313995 TO BUS 313996 CKT 1   /*8FINNEYWOOD  500.0 - 6FINNEYWOOD  230.0
END
CONTINGENCY 'DVP_P4-2: H2T593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313986 CKT 2   /*8UNITY       500.0 - 6UNITY       230.0
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P4-2: H1T593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313986 CKT 1   /*8UNITY       500.0 - 6UNITY       230.0
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P4-6: SEDGE H T452_SRT-A'
 OPEN BRANCH FROM BUS 314696 TO BUS 314697 CKT 2   /*3SEDGE HILL  115.0 - 6SEDGE HILL  230.0
 OPEN BUS 314520                                   /*3SEDGE_1     115.0
END
CONTINGENCY 'DVP_P4-5: SEDGE H L202_SRT-A'
 OPEN BRANCH FROM BUS 314696 TO BUS 314697 CKT 2   /*3SEDGE HILL  115.0 - 6SEDGE HILL  230.0
END
CONTINGENCY 'DVP_P1-3: 6SEDGE HILL-TX#2_SRT-A'
 OPEN BRANCH FROM BUS 314696 TO BUS 314697 CKT 2   /*3SEDGE HILL  115.0 - 6SEDGE HILL  230.0
END
CONTINGENCY 'DVP_P4-2: 3202_SRT-A'
 OPEN BRANCH FROM BUS 313852 TO BUS 314716 CKT 1   /*3WELCOTAP    115.0 - 3REEDY C     115.0
 OPEN BRANCH FROM BUS 313852 TO BUS 314718 CKT 1   /*3WELCOTAP    115.0 - 3S BOSTN     115.0
 OPEN BRANCH FROM BUS 313852 TO BUS 314724 CKT 1   /*3WELCOTAP    115.0 - 3WELCO       115.0
 OPEN BRANCH FROM BUS 314696 TO BUS 314697 CKT 1   /*3SEDGE HILL  115.0 - 6SEDGE HILL  230.0
 OPEN BRANCH FROM BUS 314696 TO BUS 314717 CKT 1   /*3SEDGE HILL  115.0 - 3SINAI       115.0
 OPEN BRANCH FROM BUS 314717 TO BUS 314718 CKT 1   /*3SINAI       115.0 - 3S BOSTN     115.0
 OPEN BUS 313852                                   /*3WELCOTAP    115.0
 OPEN BUS 314717                                   /*3SINAI       115.0
 OPEN BUS 314718                                   /*3S BOSTN     115.0
 OPEN BUS 314724                                   /*3WELCO       115.0
 OPEN BUS 316248                                   /*AF1-058 C    115.0
END
CONTINGENCY 'DVP_P4-5: SEDGE H L102_SRT-A'
 OPEN BRANCH FROM BUS 314696 TO BUS 314697 CKT 1   /*3SEDGE HILL  115.0 - 6SEDGE HILL  230.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-S'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: WT576_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 2                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: 57602_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 1                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: H6T563_SRT-S'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1                /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: H6T576_SRT-A'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1   /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1   /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 2027_SRT-A-3'
 OPEN BRANCH FROM BUS 314322 TO BUS 314333 CKT 1   /*6MDLTHAN     230.0 - 6POWHATN     230.0
 OPEN BRANCH FROM BUS 314333 TO BUS 316335 CKT 1   /*6POWHATN     230.0 - AC2-165 TAP  230.0
 OPEN BUS 314333                                   /*6POWHATN     230.0
 OPEN BUS 316258                                   /*AE1-075 C    230.0
 OPEN BUS 316313                                   /*AB2-026      230.0
 OPEN BUS 316405                                   /*AF2-144 C    230.0
END
CONTINGENCY 'DVP_P4-2: 242T2027_SRT-A'
 OPEN BRANCH FROM BUS 314322 TO BUS 314333 CKT 1   /*6MDLTHAN     230.0 - 6POWHATN     230.0
 OPEN BRANCH FROM BUS 314333 TO BUS 316335 CKT 1   /*6POWHATN     230.0 - AC2-165 TAP  230.0
 OPEN BUS 314333                                   /*6POWHATN     230.0
 OPEN BUS 316258                                   /*AE1-075 C    230.0
 OPEN BUS 316313                                   /*AB2-026      230.0
 OPEN BUS 316405                                   /*AF2-144 C    230.0
END
CONTINGENCY 'DVP_P2-2: BREMO B3_SRT-A'
 OPEN BRANCH FROM BUS 313708 TO BUS 314744 CKT 2   /*3FORK UNION  115.0 - 3BREMO       115.0
 OPEN BRANCH FROM BUS 314744 TO BUS 314746 CKT 1   /*3BREMO       115.0 - 4BREMO       138.0
 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1   /*3BREMO       115.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 2   /*3BREMO       115.0 - 6BREMO       230.0
 OPEN BUS 314868                                   /*3BREMO_1     115.0
END
CONTINGENCY 'DVP_P1-2: LN 2028_SRT-A'
 OPEN BRANCH FROM BUS 313373 TO BUS 313707 CKT 1   /*6GRAPEVINE   230.0 - 6FORK UNION  230.0
 OPEN BRANCH FROM BUS 313373 TO BUS 314765 CKT 1   /*6GRAPEVINE   230.0 - 6MTEAGLE     230.0
 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1   /*6CHARLVL     230.0 - 6MTEAGLE     230.0
 OPEN BUS 313373                                   /*6GRAPEVINE   230.0
 OPEN BUS 313493                                   /*3GRAPEVINE   115.0
 OPEN BUS 314754                                   /*3CUNNING     115.0
 OPEN BUS 314765                                   /*6MTEAGLE     230.0
END
CONTINGENCY 'DVP_P4-2: 202712_SRT-S'
 OPEN BRANCH FROM BUS 314322 TO BUS 314333 CKT 1                /*6MDLTHAN     230.0 - 6POWHATN     230.0
 OPEN BRANCH FROM BUS 314333 TO BUS 316335 CKT 1                /*6POWHATN     230.0 - AC2-165 TAP  230.0
 OPEN BUS 314333                                                /*6POWHATN     230.0
 OPEN BUS 316258                                                /*AE1-075 C    230.0
 OPEN BUS 316313                                                /*AB2-026      230.0
 OPEN BUS 316405                                                /*AF2-144 C    230.0
 SET POSTCONTRATING 876 BRANCH FROM BUS 314233 TO BUS 314322 CKT 1 /*6N POLE      230.0 - 6MDLTHAN     230.0
 SET PRECONTRATING 813 BRANCH FROM BUS 314233 TO BUS 314322 CKT 1 /*6N POLE      230.0 - 6MDLTHAN     230.0
END
CONTINGENCY 'DVP_P1-2: LN 587_SRT-A-3'
 OPEN BRANCH FROM BUS 971966 TO BUS 314936 CKT 1   /*AH1-528 TP   500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 511T556_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 OPEN BRANCH FROM BUS 971966 TO BUS 314936 CKT 1                /*AH1-528 TP   500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 587T591_SRT-S'
 OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1                /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 OPEN BRANCH FROM BUS 971966 TO BUS 314936 CKT 1                /*AH1-528 TP   500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'AEP_P2-2_#1377_05J.FERR 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242514 TO BUS 290022 CKT 1   /*05J.FERR     765.0 - 05J.FERR 1EQ   1.0
 OPEN BRANCH FROM BUS 242520 TO BUS 290022 CKT 1   /*05J.FERR     500.0 - 05J.FERR 1EQ   1.0
 OPEN BRANCH FROM BUS 242520 TO BUS 306719 CKT 1   /*05J.FERR     500.0 - 8ANTIOCH     500.0
 OPEN BRANCH FROM BUS 290022 TO BUS 290023 CKT 1   /*05J.FERR 1EQ   1.0 - 05J.FERR T1   13.8
END
CONTINGENCY 'DVP_P7-1: LN 2106-2111_SRT-A'
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2   /*6BEARGRDN    230.0 - 6BREMO       230.0
END
CONTINGENCY 'DVP_P7-1: LN 2003-205_SRT-S'
 OPEN BRANCH FROM BUS 314263 TO BUS 314287 CKT 1                /*6TYLER1      230.0 - 6CHESTF B    230.0
 OPEN BRANCH FROM BUS 314263 TO BUS 314331 CKT 1                /*6TYLER1      230.0 - 6POE         230.0
 OPEN BRANCH FROM BUS 314287 TO BUS 314346 CKT 1                /*6CHESTF B    230.0 - 6TYLER       230.0
 OPEN BRANCH FROM BUS 314301 TO BUS 314316 CKT 1                /*6HARR205     230.0 - 6LOCKS       230.0
 OPEN BRANCH FROM BUS 314301 TO BUS 314346 CKT 1                /*6HARR205     230.0 - 6TYLER       230.0
 OPEN BRANCH FROM BUS 314314 TO BUS 314316 CKT 1                /*3LOCKS       115.0 - 6LOCKS       230.0
 OPEN BRANCH FROM BUS 314329 TO BUS 314331 CKT 2                /*3POE         115.0 - 6POE         230.0
 OPEN BUS 314263                                                /*6TYLER1      230.0
 OPEN BUS 314301                                                /*6HARR205     230.0
 OPEN BUS 314346                                                /*6TYLER       230.0
 OPEN BUS 315839                                                /*AE2-212 C    230.0
 OPEN BUS 316240                                                /*AF1-291 C    230.0
 SET POSTCONTRATING 956 BRANCH FROM BUS 314260 TO BUS 314287 CKT 1 /*6VARINA      230.0 - 6CHESTF B    230.0
 SET PRECONTRATING 876 BRANCH FROM BUS 314260 TO BUS 314287 CKT 1 /*6VARINA      230.0 - 6CHESTF B    230.0
END
CONTINGENCY 'AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A'
 OPEN BRANCH FROM BUS 242569 TO BUS 242734 CKT 1   /*05BRUSHT     138.0 - 05NEWLDN     138.0
 OPEN BRANCH FROM BUS 242641 TO BUS 242734 CKT 1   /*05FOREST     138.0 - 05NEWLDN     138.0
 OPEN BRANCH FROM BUS 242687 TO BUS 242734 CKT 1   /*05JOHNMT     138.0 - 05NEWLDN     138.0
END
CONTINGENCY 'DVP_P1-2: LN 238_SRT-A'
 OPEN BRANCH FROM BUS 313178 TO BUS 314435 CKT 1   /*6ENCLAVE     230.0 - 6SAPONY      230.0
 OPEN BRANCH FROM BUS 314282 TO BUS 314435 CKT 1   /*6CARSON      230.0 - 6SAPONY      230.0
 OPEN BUS 314435                                   /*6SAPONY      230.0
 OPEN BUS 315779                                   /*AE2-040      230.0
 OPEN BUS 316315                                   /*AB2-025 C    230.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 2002_SRT-A'
 OPEN BRANCH FROM BUS 314282 TO BUS 314331 CKT 1   /*6CARSON      230.0 - 6POE         230.0
 OPEN BRANCH FROM BUS 314329 TO BUS 314331 CKT 1   /*3POE         115.0 - 6POE         230.0
END
CONTINGENCY 'DVP_P1-2: LN 249_SRT-A'
 OPEN BRANCH FROM BUS 313014 TO BUS 314285 CKT 1   /*6CHAPARRAL   230.0 - 6CHAPARRAL T 230.0
 OPEN BRANCH FROM BUS 314282 TO BUS 314285 CKT 1   /*6CARSON      230.0 - 6CHAPARRAL T 230.0
 OPEN BRANCH FROM BUS 314285 TO BUS 314316 CKT 1   /*6CHAPARRAL T 230.0 - 6LOCKS       230.0
 OPEN BRANCH FROM BUS 314314 TO BUS 314316 CKT 2   /*3LOCKS       115.0 - 6LOCKS       230.0
 OPEN BUS 313014                                   /*6CHAPARRAL   230.0
 OPEN BUS 314285                                   /*6CHAPARRAL T 230.0
END
CONTINGENCY 'DVP_P7-1: LN 2012-54_SRT-A'
 OPEN BRANCH FROM BUS 313722 TO BUS 314581 CKT 1   /*3OCCONEECHEE 115.0 - 3JACKSON     115.0
 OPEN BRANCH FROM BUS 314266 TO BUS 314561 CKT 1   /*6NORTHAMPTON 230.0 - 6CAROLNA     230.0
 OPEN BRANCH FROM BUS 314266 TO BUS 314569 CKT 1   /*6NORTHAMPTON 230.0 - 6EARLEYS     230.0
 OPEN BRANCH FROM BUS 314568 TO BUS 314625 CKT 1   /*3EARLEYS     115.0 - 3AULANDR     115.0
 OPEN BRANCH FROM BUS 314581 TO BUS 314626 CKT 1   /*3JACKSON     115.0 - 3WOODLND     115.0
 OPEN BRANCH FROM BUS 314625 TO BUS 314626 CKT 1   /*3AULANDR     115.0 - 3WOODLND     115.0
 OPEN BUS 314266                                   /*6NORTHAMPTON 230.0
 OPEN BUS 314581                                   /*3JACKSON     115.0
 OPEN BUS 314625                                   /*3AULANDR     115.0
 OPEN BUS 314626                                   /*3WOODLND     115.0
END
CONTINGENCY 'DVP_P7-1: LN 1010-2012_SRT-A'
 OPEN BRANCH FROM BUS 313723 TO BUS 314559 CKT 1   /*AA1-063A POI 115.0 - 3CAROLNA     115.0
 OPEN BRANCH FROM BUS 314266 TO BUS 314561 CKT 1   /*6NORTHAMPTON 230.0 - 6CAROLNA     230.0
 OPEN BRANCH FROM BUS 314266 TO BUS 314569 CKT 1   /*6NORTHAMPTON 230.0 - 6EARLEYS     230.0
 OPEN BRANCH FROM BUS 314559 TO BUS 314835 CKT 1   /*3CAROLNA     115.0 - 3CAROL_1     115.0
 OPEN BUS 314266                                   /*6NORTHAMPTON 230.0
 OPEN BUS 314835                                   /*3CAROL_1     115.0
END
CONTINGENCY 'DVP_P2-2: ALTAVISTA 115KV_SRT-A'
 OPEN BUS 313162   /*3HALL BR TAP 115.0
 OPEN BUS 314515   /*3ALTVS_1     115.0
 OPEN BUS 314666   /*3ALTVSTA     115.0
 OPEN BUS 314700   /*3HALL BR     115.0
 OPEN BUS 314705   /*3HURT        115.0
 OPEN BUS 315156   /*1HALLBR1      13.8
END
CONTINGENCY 'DVP_P4-5: 556X2_SRT-S'
 OPEN BRANCH FROM BUS 313995 TO BUS 313996 CKT 2   /*8FINNEYWOOD  500.0 - 6FINNEYWOOD  230.0
 OPEN BRANCH FROM BUS 313995 TO BUS 957480 CKT 1   /*8FINNEYWOOD  500.0 - AF2-042 TP   500.0
END
CONTINGENCY 'DVP_P4-5: 556X1_SRT-S'
 OPEN BRANCH FROM BUS 313995 TO BUS 313996 CKT 1   /*8FINNEYWOOD  500.0 - 6FINNEYWOOD  230.0
 OPEN BRANCH FROM BUS 313995 TO BUS 957480 CKT 1   /*8FINNEYWOOD  500.0 - AF2-042 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 56272_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1                /*8CARSON      500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON      500.0 - 8MDLTHAN     500.0
END
CONTINGENCY 'DVP_P1-2: LN 562_SRT-S-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1                /*8CARSON      500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON      500.0 - 8MDLTHAN     500.0
END
CONTINGENCY 'DVP_P1-2: LN 298_SRT-A-4'
 OPEN BRANCH FROM BUS 972002 TO BUS 314747 CKT 1   /*AH1-546 TP   230.0 - 6BREMO       230.0
END
CONTINGENCY 'DVP_P2-2: BREMO B1_SRT-A'
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1   /*3BREMO       115.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 970936 TO BUS 314747 CKT 1   /*AG2-583 TP   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 972002 TO BUS 314747 CKT 1   /*AH1-546 TP   230.0 - 6BREMO       230.0
 OPEN BUS 314326                                   /*6BEARGRDN    230.0
 OPEN BUS 314747                                   /*6BREMO       230.0
 OPEN BUS 315191                                   /*1BEARGRDN G1  18.0
 OPEN BUS 315192                                   /*1BEARGRDN G2  18.0
 OPEN BUS 315193                                   /*1BEARGRDN S1  18.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-2'
 OPEN BRANCH FROM BUS 941030 TO BUS 970672 CKT 1   /*AE2-094 TP   500.0 - AG2-436 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 58572_SRT-A'
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P4-5: W72_SRT-A'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1   /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P4-2: XT585_SRT-S'
 OPEN BRANCH FROM BUS 970672 TO BUS 314940 CKT 1                /*AG2-436 TP   500.0 - 8ROGERS RD   500.0
 SET POSTCONTRATING 3464 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET PRECONTRATING 3464 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
END
CONTINGENCY 'DVP_P4-2: 54472_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 939410 CKT 1                /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P1-2: LN 511_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 51192_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 OPEN BUS 314921                                                /*8RAWLIN_STC2 500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 51172_SRT-S'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1                /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 511T544_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 939410 CKT 1                /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 211122_SRT-A'
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1   /*3BREMO       115.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 970936 TO BUS 314747 CKT 1   /*AG2-583 TP   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 972002 TO BUS 314747 CKT 1   /*AH1-546 TP   230.0 - 6BREMO       230.0
 OPEN BUS 314326                                   /*6BEARGRDN    230.0
 OPEN BUS 314747                                   /*6BREMO       230.0
 OPEN BUS 315191                                   /*1BEARGRDN G1  18.0
 OPEN BUS 315192                                   /*1BEARGRDN G2  18.0
 OPEN BUS 315193                                   /*1BEARGRDN S1  18.0
END
CONTINGENCY 'DVP_P4-2: 219322_SRT-A'
 OPEN BRANCH FROM BUS 313707 TO BUS 313867 CKT 1   /*6FORK UNION  230.0 - 6BREMODIST   230.0
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1   /*3BREMO       115.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 970936 TO BUS 314747 CKT 1   /*AG2-583 TP   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 972002 TO BUS 314747 CKT 1   /*AH1-546 TP   230.0 - 6BREMO       230.0
 OPEN BUS 313867                                   /*6BREMODIST   230.0
 OPEN BUS 314326                                   /*6BEARGRDN    230.0
 OPEN BUS 314747                                   /*6BREMO       230.0
 OPEN BUS 315191                                   /*1BEARGRDN G1  18.0
 OPEN BUS 315192                                   /*1BEARGRDN G2  18.0
 OPEN BUS 315193                                   /*1BEARGRDN S1  18.0
END
CONTINGENCY 'DVP_P1-2: LN 298_SRT-A-3'
 OPEN BRANCH FROM BUS 314677 TO BUS 971844 CKT 1   /*6BUCKING     230.0 - AH1-439 TP   230.0
 OPEN BRANCH FROM BUS 314677 TO BUS 972002 CKT 1   /*6BUCKING     230.0 - AH1-546 TP   230.0
 OPEN BUS 314677                                   /*6BUCKING     230.0
 OPEN BUS 316322                                   /*AB2-045      230.0
END
314559 to 314561 ckt 1
313757 to 313785 ckt 1
313757 to 313785 ckt 2
314562 to 314563 ckt 1
314691 to 314692 ckt 1
314691 to 314692 ckt 2
314702 to 304102 ckt 1
314696 to 314697 ckt 1
314696 to 314697 ckt 2
314726 to 314691 ckt 1
314747 to 313867 ckt 1
314747 to 970936 ckt 1
313867 to 313707 ckt 1
314268 to 314692 ckt 1
314677 to 972002 ckt 1
314561 to 314266 ckt 1
314282 to 314285 ckt 1
314282 to 314331 ckt 1
313868 to 316335 ckt 1
314285 to 314316 ckt 1
314563 to 313994 ckt 1
315684 to 314697 ckt 1
313178 to 314435 ckt 1
314692 to 970284 ckt 1
313996 to 313995 ckt 1
313996 to 313995 ckt 2
313996 to 962490 ckt 1
313707 to 313373 ckt 1
313373 to 314765 ckt 1
314765 to 314749 ckt 1
313994 to 313178 ckt 1
314333 to 314322 ckt 1
314435 to 314282 ckt 1
314697 to 316218 ckt 1
314902 to 314914 ckt 1
314936 to 314902 ckt 1
314940 to 970672 ckt 1
316218 to 316281 ckt 1
316281 to 304070 ckt 1
316335 to 314333 ckt 1
941030 to 314902 ckt 1
962490 to 313996 ckt 1
962490 to 971740 ckt 1
970284 to 971844 ckt 1
970300 to 314268 ckt 1
970672 to 941030 ckt 1
970936 to 313868 ckt 1
971740 to 962490 ckt 1
971740 to 970300 ckt 1
971844 to 314677 ckt 1
972002 to 314747 ckt 1

Winter Peak Analysis

The New Service Request AG2-341 was evaluated as a 50.0 MW (20.0 MW Capacity) injection in the Dominion area.

AG2-341 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 50.0 MW (50.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Light Load Analysis

The New Service Request AG2-341 was evaluated as a 50.0 MW injection and 50.0 MW withdrawal in the Dominion area.

AG2-341 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 50.0 MW (50.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
3CLOUD-6CLOUD 115.0/230.0 kV Ckt 1 transformer
DVP_P1-3: 6CLOUD-TX#2_SRT-A
SingleAC101.49 %298.45B302.8912.2
GD2DVP
3CLOUD-6CLOUD 115.0/230.0 kV Ckt 2 transformer
DVP_P1-3: 6CLOUD-TX#1_SRT-A
SingleAC118.9 %254.74B302.8912.2
GD2DVP
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 2201_SRT-L
SingleAC116.26 %250.89B291.684.13
GD2DVP
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 254_SRT-L
SingleAC112.03 %250.89B281.084.14
GD2DVP
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 298_SRT-A-1
SingleAC136.3 %235.94B321.584.62
GD2DVP
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
DVP_P1-2: LN 235_SRT-A-4
SingleAC212.46 %206.05B437.776.21
GD2DVP
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
DVP_P1-2: LN 1012_SRT-A-2
SingleAC161.98 %206.05B333.762.51
GD2DVP
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
DVP_P7-1: LN 1041-38_SRT-A
TowerAC125.94 %230.3C290.055.1
GD2DVP
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
Base Case
SingleAC120.71 %201.54A243.283.66
GD2DVP
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
DVP_P7-1: LN 1041-137_SRT-A
TowerAC119.93 %230.3C276.198.0
GD2DVP
3FLAT CREEK-3MORAN 115.0 kV Ckt 1 line
DVP_P1-2: LN 84_SRT-A
SingleAC101.95 %221.84B226.164.55
GD2DVP
3MORAN-3FARMVIL 115.0 kV Ckt 1 line
DVP_P1-2: LN 84_SRT-A
SingleAC101.29 %221.84B224.74.55
GD2DVP
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
Base Case
SingleAC129.58 %228.42A295.992.87
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-L
SingleAC118.65 %830.96B985.925.5
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC112.18 %830.96B932.174.56
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-L
SingleAC118.47 %830.96B984.415.5
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC112.0 %830.96B930.644.56
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-L
SingleAC116.61 %698.42B814.457.8
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC113.33 %698.42B791.511.54
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-L
SingleAC108.55 %687.14B745.877.81
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC107.24 %687.14B736.9211.55
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-L
SingleAC121.87 %830.96B1012.685.18
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC117.54 %830.96B976.744.27
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-L
SingleAC124.77 %808.4B1008.615.18
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC120.34 %808.4B972.834.27
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-L
SingleAC124.16 %808.4B1003.75.18
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC119.74 %808.4B967.954.27
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 509T570_SRT-A
BreakerAC109.87 %541.0B594.426.53
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-3
SingleAC118.15 %508.54B600.826.45
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-1
SingleAC115.23 %508.54B585.986.45
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-5: 593X1_SRT-A
BreakerAC108.28 %541.0B585.7812.86
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-5: 593X2_SRT-A
BreakerAC108.27 %541.0B585.7512.86
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-2: H1T593_SRT-A
BreakerAC107.54 %541.0B581.7812.89
GD2CPLE/DVP
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
DVP_P4-2: H2T593_SRT-A
BreakerAC107.54 %541.0B581.7812.89
GD2DVP
AG1-098 TP-6FINNEYWOOD 230.0 kV Ckt 1 line
DVP_P1-2: LN 298_SRT-A-4
SingleAC103.34 %698.42B721.775.23
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-L
SingleAC113.74 %687.14B781.567.81
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC111.28 %687.14B764.6411.55
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-L
SingleAC117.02 %687.14B804.117.81
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC113.89 %687.14B782.5611.55
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-L
SingleAC120.47 %698.42B841.427.8
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P1-2: LN 593_SRT-A
SingleAC116.45 %698.42B813.2911.54

Details for 3CLOUD-6CLOUD 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6CLOUD-TX#2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3CLOUD-6CLOUD 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-3: 6CLOUD-TX#2_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.49 %
Rating:298.45 MVA
Rating Type:B
MVA to Mitigate:302.89
MW Contribution:12.2
Bus #Bus NameTypeMW Contribution
963171AG1-166 GEN
Solar/Wind Harmer
1.153
315785AD2-033 C
Solar/Wind Harmer
0.001
970323AG2-213 GEN
Solar/Wind Harmer
6.776
3145593CAROLNA
Solar/Wind Harmer
0.237
3145593CAROLNA
Solar/Wind Harmer
0.237
970683AG2-441 GEN
Solar/Wind Harmer
8.849
962561AG1-105 GEN
Solar/Wind Harmer
6.204
971193AH1-056 GEN
Solar/Wind Harmer
4.849
3145783HORNRTN
Solar/Wind Harmer
0.223
960081AF2-299 GEN
Solar/Wind Harmer
0.697
970535AG2-341 GEN
50/50
12.202
939181AE1-148 GEN
Solar/Wind Harmer
13.99
964791AG1-342 GEN
Solar/Wind Harmer
2.177
970257AG2-171 GEN
Solar/Wind Harmer
5.082
963181AG1-167 GEN
Solar/Wind Harmer
0.864
3145593CAROLNA
Solar/Wind Harmer
0.066
970413AG2-270 GEN
50/50
Charging
8.551
970831AG2-522 GEN
Solar/Wind Harmer
9.281
3144303KENBRDG
Solar/Wind Harmer
0.339
946301AF1-294 GEN
Solar/Wind Harmer
2.363
3137643SOCKMAN
Solar/Wind Harmer
0.904
3147133PAMPLIN
Solar/Wind Harmer
0.761
3146043SEABORD
Solar/Wind Harmer
0.188
316478AD1-087 GEN
Solar/Wind Helper
0.98
3147043LAWRENC
Solar/Wind Harmer
0.187
316486AD2-202 GEN
Solar/Wind Helper
0.287
3147043LAWRENC
50/50
1.159
961791AG1-021 GEN
Solar/Wind Harmer
1.153
971795AH1-408 GEN
Solar/Wind Harmer
6.581
3147133PAMPLIN
Solar/Wind Harmer
0.194
959311AF2-222 GEN
Solar/Wind Harmer
13.483
3146843MT LREL
Solar/Wind Harmer
0.3
3146843MT LREL
Solar/Wind Harmer
0.3
958211AF2-115 GEN
Solar/Wind Harmer
1.441
3147133PAMPLIN
Solar/Wind Harmer
0.242
971065AG2-659 GEN
Solar/Wind Harmer
10.411
3145783HORNRTN
Solar/Wind Harmer
0.712
3145783HORNRTN
Solar/Wind Harmer
0.089
315657AE1-056 GEN
Solar/Wind Harmer
2.909
966811AG1-552 GEN
Solar/Wind Harmer
0.852
964241AG1-285 GEN
Solar/Wind Harmer
13.117
970681AG2-440 GEN
Solar/Wind Harmer
7.079
970401AG2-262 GEN
Solar/Wind Harmer
0.665
963191AG1-168 GEN
Solar/Wind Harmer
0.864
3145783HORNRTN
Solar/Wind Harmer
0.89
3145783HORNRTN
Solar/Wind Harmer
0.223
971775AH1-396 GEN
Solar/Wind Harmer
1.016
970685AG2-442 GEN
Solar/Wind Harmer
9.911
971563AH1-280 GEN
Solar/Wind Harmer
1.153
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.594
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.644
MECLTFEXP_MEC->PJM
CLTF
0.132
SIGELTFEXP_SIGE->PJM
CLTF
0.004
CPLELTFEXP_CPLE->PJM
CLTF
0.74
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.79
LAGNLTFEXP_LAGN->PJM
CLTF
0.378
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.399
TVALTFEXP_TVA->PJM
CLTF
0.196
NYPJM->LTFIMP_NY
CLTF
0.164
LGEELTFEXP_LGEE->PJM
CLTF
0.039
WECLTFEXP_WEC->PJM
CLTF
0.019
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.866

Details for 3CLOUD-6CLOUD 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6CLOUD-TX#1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3CLOUD-6CLOUD 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-3: 6CLOUD-TX#1_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.9 %
Rating:254.74 MVA
Rating Type:B
MVA to Mitigate:302.89
MW Contribution:12.2
Bus #Bus NameTypeMW Contribution
963171AG1-166 GEN
Solar/Wind Harmer
1.153
315785AD2-033 C
Solar/Wind Harmer
0.001
970323AG2-213 GEN
Solar/Wind Harmer
6.776
3145593CAROLNA
Solar/Wind Harmer
0.237
3145593CAROLNA
Solar/Wind Harmer
0.237
970683AG2-441 GEN
Solar/Wind Harmer
8.849
962561AG1-105 GEN
Solar/Wind Harmer
6.204
971193AH1-056 GEN
Solar/Wind Harmer
4.849
3145783HORNRTN
Solar/Wind Harmer
0.223
960081AF2-299 GEN
Solar/Wind Harmer
0.697
970535AG2-341 GEN
50/50
12.202
939181AE1-148 GEN
Solar/Wind Harmer
13.99
964791AG1-342 GEN
Solar/Wind Harmer
2.177
970257AG2-171 GEN
Solar/Wind Harmer
5.082
963181AG1-167 GEN
Solar/Wind Harmer
0.864
3145593CAROLNA
Solar/Wind Harmer
0.066
970413AG2-270 GEN
50/50
Charging
8.551
970831AG2-522 GEN
Solar/Wind Harmer
9.281
3144303KENBRDG
Solar/Wind Harmer
0.339
946301AF1-294 GEN
Solar/Wind Harmer
2.363
3137643SOCKMAN
Solar/Wind Harmer
0.904
3147133PAMPLIN
Solar/Wind Harmer
0.761
3146043SEABORD
Solar/Wind Harmer
0.188
316478AD1-087 GEN
Solar/Wind Helper
0.98
3147043LAWRENC
Solar/Wind Harmer
0.187
316486AD2-202 GEN
Solar/Wind Helper
0.287
3147043LAWRENC
50/50
1.159
961791AG1-021 GEN
Solar/Wind Harmer
1.153
971795AH1-408 GEN
Solar/Wind Harmer
6.581
3147133PAMPLIN
Solar/Wind Harmer
0.194
959311AF2-222 GEN
Solar/Wind Harmer
13.483
3146843MT LREL
Solar/Wind Harmer
0.3
3146843MT LREL
Solar/Wind Harmer
0.3
958211AF2-115 GEN
Solar/Wind Harmer
1.441
3147133PAMPLIN
Solar/Wind Harmer
0.242
971065AG2-659 GEN
Solar/Wind Harmer
10.411
3145783HORNRTN
Solar/Wind Harmer
0.712
3145783HORNRTN
Solar/Wind Harmer
0.089
315657AE1-056 GEN
Solar/Wind Harmer
2.909
966811AG1-552 GEN
Solar/Wind Harmer
0.852
964241AG1-285 GEN
Solar/Wind Harmer
13.117
970681AG2-440 GEN
Solar/Wind Harmer
7.079
970401AG2-262 GEN
Solar/Wind Harmer
0.665
963191AG1-168 GEN
Solar/Wind Harmer
0.864
3145783HORNRTN
Solar/Wind Harmer
0.89
3145783HORNRTN
Solar/Wind Harmer
0.223
971775AH1-396 GEN
Solar/Wind Harmer
1.016
970685AG2-442 GEN
Solar/Wind Harmer
9.911
971563AH1-280 GEN
Solar/Wind Harmer
1.153
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.594
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.644
MECLTFEXP_MEC->PJM
CLTF
0.132
SIGELTFEXP_SIGE->PJM
CLTF
0.004
CPLELTFEXP_CPLE->PJM
CLTF
0.74
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.79
LAGNLTFEXP_LAGN->PJM
CLTF
0.378
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.399
TVALTFEXP_TVA->PJM
CLTF
0.196
NYPJM->LTFIMP_NY
CLTF
0.164
LGEELTFEXP_LGEE->PJM
CLTF
0.039
WECLTFEXP_WEC->PJM
CLTF
0.019
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.866

Details for 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 2201_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.26 %
Rating:250.89 MVA
Rating Type:B
MVA to Mitigate:291.68
MW Contribution:4.13
Bus #Bus NameTypeMW Contribution
971775AH1-396 GEN
Solar/Wind Harmer
0.537
3156081AA2-088 GEN
Solar/Wind Harmer
0
970685AG2-442 GEN
Solar/Wind Harmer
5.506
3146033SCOT NK
Solar/Wind Harmer
0.509
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3146233WITAKRS
Solar/Wind Harmer
0.071
3145493TOT1
Solar/Wind Harmer
0.073
3145933PARMELE
Solar/Wind Harmer
0.061
3146926FARMVIL
Solar/Wind Harmer
0.018
3146926FARMVIL
Solar/Wind Harmer
0.018
3146626S HERTFORD
Solar/Wind Harmer
0.013
3146626S HERTFORD
Solar/Wind Harmer
0.013
965291AG1-394 GEN
Solar/Wind Harmer
0.597
957521AF2-046 GEN
Solar/Wind Harmer
4.704
3137643SOCKMAN
Solar/Wind Harmer
1.699
3144303KENBRDG
Solar/Wind Harmer
0.117
3145893MURPHYS
Solar/Wind Harmer
0.502
3145893MURPHYS
Solar/Wind Harmer
0.339
3145513AHOSKIE
Solar/Wind Harmer
0.107
3145513AHOSKIE
Solar/Wind Harmer
0.107
3145963POPLR C
Solar/Wind Harmer
0.054
3145963POPLR C
Solar/Wind Harmer
0.054
3146776BUCKING
Solar/Wind Harmer
0.074
3146776BUCKING
Solar/Wind Harmer
0.006
3146516WINFALL
Solar/Wind Harmer
0.03
964241AG1-285 GEN
Solar/Wind Harmer
6.579
970681AG2-440 GEN
Solar/Wind Harmer
3.933
316315AB2-025 C
Solar/Wind Helper
0.576
3145783HORNRTN
Solar/Wind Harmer
0.934
3145783HORNRTN
Solar/Wind Harmer
0.233
3144356SAPONY
Solar/Wind Harmer
-0.807
3147043LAWRENC
50/50
4.227
971795AH1-408 GEN
Solar/Wind Harmer
30.053
3145683EARLEYS
Solar/Wind Harmer
0.101
3147133PAMPLIN
Solar/Wind Harmer
0.08
3146073TAR RVR
Solar/Wind Harmer
0.073
3146206CASHIE
Solar/Wind Harmer
0.057
3146206CASHIE
Solar/Wind Harmer
0.057
3146376EDENTON
Solar/Wind Harmer
0.024
3147123OTTER R
Solar/Wind Harmer
0.014
959311AF2-222 GEN
Solar/Wind Harmer
7.215
3146843MT LREL
Solar/Wind Harmer
0.113
3146843MT LREL
Solar/Wind Harmer
0.113
3145683EARLEYS
Solar/Wind Harmer
0.201
3145683EARLEYS
Solar/Wind Harmer
0.101
3147133PAMPLIN
Solar/Wind Harmer
0.1
3145273HOLLAND
Solar/Wind Harmer
0.033
315785AD2-033 C
Solar/Wind Harmer
0
970323AG2-213 GEN
Solar/Wind Harmer
3.578
3145593CAROLNA
Solar/Wind Harmer
0.248
3145593CAROLNA
Solar/Wind Harmer
0.248
3130156CHOWAN
Solar/Wind Harmer
0.024
3146486SUNBURY
Solar/Wind Harmer
0.004
3146486SUNBURY
Solar/Wind Harmer
0.004
3145893MURPHYS
Solar/Wind Harmer
0.154
315652AC1-086 GEN
Solar/Wind Harmer
6.919
3146263WOODLND
Solar/Wind Harmer
0.141
3145893MURPHYS
Solar/Wind Harmer
0.226
3145543BTLEBRO
Solar/Wind Harmer
0.087
3146776BUCKING
Solar/Wind Harmer
0.007
3146516WINFALL
Solar/Wind Harmer
0.009
3146516WINFALL
Solar/Wind Harmer
0.009
315779AE2-040
50/50
Charging
1.673
970535AG2-341 GEN
50/50
4.126
939181AE1-148 GEN
Solar/Wind Harmer
3.866
3145796HORNRTN
Solar/Wind Harmer
0.119
3145573BETHELC
Solar/Wind Harmer
0.073
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3147312GRETNA
Solar/Wind Harmer
0.016
960081AF2-299 GEN
Solar/Wind Harmer
5.424
970683AG2-441 GEN
Solar/Wind Harmer
4.916
962561AG1-105 GEN
Solar/Wind Harmer
3.429
3145783HORNRTN
Solar/Wind Harmer
0.233
3145796HORNRTN
Solar/Wind Harmer
0.119
3145746EVERETS
Solar/Wind Harmer
0.063
970257AG2-171 GEN
Solar/Wind Harmer
2.684
3145593CAROLNA
Solar/Wind Harmer
0.069
970831AG2-522 GEN
Solar/Wind Harmer
4.379
3145796HORNRTN
Solar/Wind Harmer
0.475
3145746EVERETS
Solar/Wind Harmer
0.253
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3147312GRETNA
Solar/Wind Harmer
0.004
3145893MURPHYS
Solar/Wind Harmer
0.615
3145893MURPHYS
Solar/Wind Harmer
0.126
3145543BTLEBRO
Solar/Wind Harmer
0.087
3145543BTLEBRO
Solar/Wind Harmer
0.087
3145543BTLEBRO
Solar/Wind Harmer
0.07
3146776BUCKING
Solar/Wind Harmer
0.007
3146516WINFALL
Solar/Wind Harmer
0.009
3142666NORTHAMPTON
Solar/Wind Harmer
0.124
3142666NORTHAMPTON
Solar/Wind Harmer
0.124
3146233WITAKRS
Solar/Wind Harmer
0.417
3130546PLYMOUTH
Solar/Wind Harmer
0.045
3130156CHOWAN
Solar/Wind Harmer
0.024
3146626S HERTFORD
Solar/Wind Harmer
0.013
971065AG2-659 GEN
Solar/Wind Harmer
4.03
3145783HORNRTN
Solar/Wind Harmer
0.747
3145783HORNRTN
Solar/Wind Harmer
0.093
3145796HORNRTN
Solar/Wind Harmer
0.392
3145796HORNRTN
Solar/Wind Harmer
0.38
3145796HORNRTN
Solar/Wind Harmer
0.356
3145796HORNRTN
Solar/Wind Harmer
0.048
3145823KELFORD
Solar/Wind Harmer
0.114
3145823KELFORD
Solar/Wind Harmer
0.114
3145573BETHELC
Solar/Wind Harmer
0.073
966811AG1-552 GEN
Solar/Wind Harmer
1.366
3146263WOODLND
Solar/Wind Harmer
0.141
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.126
3146516WINFALL
Solar/Wind Harmer
0.009
3146516WINFALL
Solar/Wind Harmer
0.009
316318V4-068
Solar/Wind Harmer
0
3146043SEABORD
Solar/Wind Harmer
0.197
3146173TUNIS
Solar/Wind Harmer
0.114
3145683EARLEYS
Solar/Wind Harmer
0.101
3147133PAMPLIN
Solar/Wind Harmer
0.314
3146083TARBORO
Solar/Wind Harmer
0.073
3147173SINAI
Solar/Wind Harmer
0.061
3147243WELCO
Solar/Wind Harmer
0.038
3146206CASHIE
Solar/Wind Harmer
0.057
3145663CRESWEL
Solar/Wind Harmer
0.102
3146376EDENTON
Solar/Wind Harmer
0.024
3147043LAWRENC
Solar/Wind Harmer
0.445
3146173TUNIS
Solar/Wind Harmer
0.114
3146173TUNIS
Solar/Wind Harmer
0.114
3146173TUNIS
Solar/Wind Harmer
0.114
3138543CONSLDL
Solar/Wind Harmer
0.068
3146083TARBORO
Solar/Wind Harmer
0.073
3146376EDENTON
Solar/Wind Harmer
0.024
3146396TANGLEW
Solar/Wind Harmer
0.003
3146802CHATHAM
Solar/Wind Harmer
0.015
961681AG1-008 GEN
Solar/Wind Harmer
4.704
3142666NORTHAMPTON
Solar/Wind Harmer
0.124
3142666NORTHAMPTON
Solar/Wind Harmer
0.124
3146233WITAKRS
Solar/Wind Harmer
0.252
3145933PARMELE
Solar/Wind Harmer
0.121
3145933PARMELE
Solar/Wind Harmer
0.061
3130156CHOWAN
Solar/Wind Harmer
0.024
3145176PASQUOTANK
Solar/Wind Harmer
0.003
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.026
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.307
MECLTFEXP_MEC->PJM
CLTF
0.334
SIGELTFEXP_SIGE->PJM
CLTF
0.01
CPLELTFEXP_CPLE->PJM
CLTF
1.253
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.85
LAGNLTFEXP_LAGN->PJM
CLTF
0.753
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.457
TVALTFEXP_TVA->PJM
CLTF
0.387
NYPJM->LTFIMP_NY
CLTF
0.213
LGEELTFEXP_LGEE->PJM
CLTF
0.112
WECLTFEXP_WEC->PJM
CLTF
0.059
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.975

Details for 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 254_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.03 %
Rating:250.89 MVA
Rating Type:B
MVA to Mitigate:281.08
MW Contribution:4.14
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
4.229
971795AH1-408 GEN
Solar/Wind Harmer
30.067
3145683EARLEYS
Solar/Wind Harmer
0.101
3147133PAMPLIN
Solar/Wind Harmer
0.08
3146073TAR RVR
Solar/Wind Harmer
0.074
3146206CASHIE
Solar/Wind Harmer
0.057
3146206CASHIE
Solar/Wind Harmer
0.057
3146376EDENTON
Solar/Wind Harmer
0.025
3147123OTTER R
Solar/Wind Harmer
0.014
959311AF2-222 GEN
Solar/Wind Harmer
7.234
316365GEN2_N
Solar/Wind Helper
3.15
3146843MT LREL
Solar/Wind Harmer
0.113
3146843MT LREL
Solar/Wind Harmer
0.113
3145683EARLEYS
Solar/Wind Harmer
0.202
3145683EARLEYS
Solar/Wind Harmer
0.101
3147133PAMPLIN
Solar/Wind Harmer
0.1
3145273HOLLAND
Solar/Wind Harmer
0.033
315785AD2-033 C
Solar/Wind Harmer
0
970323AG2-213 GEN
Solar/Wind Harmer
3.587
3145593CAROLNA
Solar/Wind Harmer
0.248
3145593CAROLNA
Solar/Wind Harmer
0.248
3130156CHOWAN
Solar/Wind Harmer
0.025
3146486SUNBURY
Solar/Wind Harmer
0.004
3146486SUNBURY
Solar/Wind Harmer
0.004
965291AG1-394 GEN
Solar/Wind Harmer
0.598
957521AF2-046 GEN
Solar/Wind Harmer
4.718
3137643SOCKMAN
Solar/Wind Harmer
1.697
3144303KENBRDG
Solar/Wind Harmer
0.117
3145893MURPHYS
Solar/Wind Harmer
0.154
315652AC1-086 GEN
Solar/Wind Harmer
6.939
3146263WOODLND
Solar/Wind Harmer
0.141
3145893MURPHYS
Solar/Wind Harmer
0.226
3145543BTLEBRO
Solar/Wind Harmer
0.087
3146776BUCKING
Solar/Wind Harmer
0.007
3146516WINFALL
Solar/Wind Harmer
0.01
3146516WINFALL
Solar/Wind Harmer
0.01
960081AF2-299 GEN
Solar/Wind Harmer
5.426
970683AG2-441 GEN
Solar/Wind Harmer
4.931
962561AG1-105 GEN
Solar/Wind Harmer
3.439
3145783HORNRTN
Solar/Wind Harmer
0.233
3145796HORNRTN
Solar/Wind Harmer
0.119
3145746EVERETS
Solar/Wind Harmer
0.064
315779AE2-040
50/50
Charging
1.67
970535AG2-341 GEN
50/50
4.136
939181AE1-148 GEN
Solar/Wind Harmer
3.876
3145893MURPHYS
Solar/Wind Harmer
0.617
3145893MURPHYS
Solar/Wind Harmer
0.126
3145543BTLEBRO
Solar/Wind Harmer
0.087
3145543BTLEBRO
Solar/Wind Harmer
0.087
3145543BTLEBRO
Solar/Wind Harmer
0.07
3146776BUCKING
Solar/Wind Harmer
0.008
3146516WINFALL
Solar/Wind Harmer
0.01
3145893MURPHYS
Solar/Wind Harmer
0.503
3145893MURPHYS
Solar/Wind Harmer
0.339
3145513AHOSKIE
Solar/Wind Harmer
0.107
3145513AHOSKIE
Solar/Wind Harmer
0.107
3145963POPLR C
Solar/Wind Harmer
0.055
3145963POPLR C
Solar/Wind Harmer
0.055
3146776BUCKING
Solar/Wind Harmer
0.076
3146776BUCKING
Solar/Wind Harmer
0.006
3146516WINFALL
Solar/Wind Harmer
0.032
970257AG2-171 GEN
Solar/Wind Harmer
2.691
3145593CAROLNA
Solar/Wind Harmer
0.069
3142666NORTHAMPTON
Solar/Wind Harmer
0.124
3142666NORTHAMPTON
Solar/Wind Harmer
0.124
3146233WITAKRS
Solar/Wind Harmer
0.418
3130546PLYMOUTH
Solar/Wind Harmer
0.046
3130156CHOWAN
Solar/Wind Harmer
0.025
3146626S HERTFORD
Solar/Wind Harmer
0.013
971775AH1-396 GEN
Solar/Wind Harmer
0.538
3156081AA2-088 GEN
Solar/Wind Harmer
0
970685AG2-442 GEN
Solar/Wind Harmer
5.522
3146033SCOT NK
Solar/Wind Harmer
0.509
3142666NORTHAMPTON
Solar/Wind Harmer
0.074
3146233WITAKRS
Solar/Wind Harmer
0.071
3145493TOT1
Solar/Wind Harmer
0.074
3145933PARMELE
Solar/Wind Harmer
0.061
3146926FARMVIL
Solar/Wind Harmer
0.018
3146926FARMVIL
Solar/Wind Harmer
0.018
3146626S HERTFORD
Solar/Wind Harmer
0.013
3146626S HERTFORD
Solar/Wind Harmer
0.013
970831AG2-522 GEN
Solar/Wind Harmer
4.388
3145796HORNRTN
Solar/Wind Harmer
0.476
3145746EVERETS
Solar/Wind Harmer
0.254
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3147312GRETNA
Solar/Wind Harmer
0.004
966811AG1-552 GEN
Solar/Wind Harmer
1.369
3146263WOODLND
Solar/Wind Harmer
0.141
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.126
3146516WINFALL
Solar/Wind Harmer
0.01
3146516WINFALL
Solar/Wind Harmer
0.01
316318V4-068
Solar/Wind Harmer
0
316023GEN1_S
Solar/Wind Helper
3.15
3146043SEABORD
Solar/Wind Harmer
0.197
3146173TUNIS
Solar/Wind Harmer
0.114
3145683EARLEYS
Solar/Wind Harmer
0.101
3147133PAMPLIN
Solar/Wind Harmer
0.315
3146083TARBORO
Solar/Wind Harmer
0.074
3147173SINAI
Solar/Wind Harmer
0.061
3147243WELCO
Solar/Wind Harmer
0.038
3146206CASHIE
Solar/Wind Harmer
0.057
3145663CRESWEL
Solar/Wind Harmer
0.102
3146376EDENTON
Solar/Wind Harmer
0.025
3146386ELIZ CT
Solar/Wind Harmer
0.002
3147043LAWRENC
Solar/Wind Harmer
0.444
3146173TUNIS
Solar/Wind Harmer
0.114
3146173TUNIS
Solar/Wind Harmer
0.114
3146173TUNIS
Solar/Wind Harmer
0.114
3138543CONSLDL
Solar/Wind Harmer
0.068
3146083TARBORO
Solar/Wind Harmer
0.074
3146376EDENTON
Solar/Wind Harmer
0.025
3146396TANGLEW
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
4.039
3145783HORNRTN
Solar/Wind Harmer
0.747
3145783HORNRTN
Solar/Wind Harmer
0.093
3145796HORNRTN
Solar/Wind Harmer
0.393
3145796HORNRTN
Solar/Wind Harmer
0.381
3145796HORNRTN
Solar/Wind Harmer
0.357
3145796HORNRTN
Solar/Wind Harmer
0.048
3145823KELFORD
Solar/Wind Harmer
0.114
3145823KELFORD
Solar/Wind Harmer
0.114
3145573BETHELC
Solar/Wind Harmer
0.074
3146802CHATHAM
Solar/Wind Harmer
0.015
964241AG1-285 GEN
Solar/Wind Harmer
6.593
970681AG2-440 GEN
Solar/Wind Harmer
3.944
316315AB2-025 C
Solar/Wind Helper
0.574
3145783HORNRTN
Solar/Wind Harmer
0.933
3145783HORNRTN
Solar/Wind Harmer
0.233
3144356SAPONY
Solar/Wind Harmer
-0.804
3145796HORNRTN
Solar/Wind Harmer
0.119
3145573BETHELC
Solar/Wind Harmer
0.074
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3147312GRETNA
Solar/Wind Harmer
0.016
961681AG1-008 GEN
Solar/Wind Harmer
4.718
3142666NORTHAMPTON
Solar/Wind Harmer
0.124
3142666NORTHAMPTON
Solar/Wind Harmer
0.124
3146233WITAKRS
Solar/Wind Harmer
0.252
3145933PARMELE
Solar/Wind Harmer
0.122
3145933PARMELE
Solar/Wind Harmer
0.061
3130156CHOWAN
Solar/Wind Harmer
0.025
3145176PASQUOTANK
Solar/Wind Harmer
0.003
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.273
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.372
MECLTFEXP_MEC->PJM
CLTF
0.362
SIGELTFEXP_SIGE->PJM
CLTF
0.011
CPLELTFEXP_CPLE->PJM
CLTF
1.272
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.078
LAGNLTFEXP_LAGN->PJM
CLTF
0.788
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.508
TVALTFEXP_TVA->PJM
CLTF
0.404
NYPJM->LTFIMP_NY
CLTF
0.203
LGEELTFEXP_LGEE->PJM
CLTF
0.124
WECLTFEXP_WEC->PJM
CLTF
0.065
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
2.975

Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 298_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.3 %
Rating:235.94 MVA
Rating Type:B
MVA to Mitigate:321.58
MW Contribution:4.62
Bus #Bus NameTypeMW Contribution
970685AG2-442 GEN
Solar/Wind Harmer
28.552
971775AH1-396 GEN
Solar/Wind Harmer
1.998
946301AF1-294 GEN
Solar/Wind Harmer
9.808
3144303KENBRDG
Solar/Wind Harmer
0.666
970909AG2-566 GEN
50/50
Charging
3.398
942461AE2-259 GEN
Solar/Wind Harmer
0
963191AG1-168 GEN
Solar/Wind Harmer
3.588
970681AG2-440 GEN
Solar/Wind Harmer
20.394
964241AG1-285 GEN
Solar/Wind Harmer
14.035
970401AG2-262 GEN
Solar/Wind Harmer
0.477
3147043LAWRENC
50/50
0.698
3147133PAMPLIN
Solar/Wind Harmer
1.055
961791AG1-021 GEN
Solar/Wind Harmer
4.784
971795AH1-408 GEN
Solar/Wind Harmer
3.753
3147133PAMPLIN
Solar/Wind Harmer
1.319
958211AF2-115 GEN
Solar/Wind Harmer
5.98
959311AF2-222 GEN
Solar/Wind Harmer
29.601
3146843MT LREL
Solar/Wind Harmer
0.216
3146843MT LREL
Solar/Wind Harmer
0.216
3147133PAMPLIN
Solar/Wind Harmer
4.142
970323AG2-213 GEN
Solar/Wind Harmer
13.319
315785AD2-033 C
Solar/Wind Harmer
0.001
963171AG1-166 GEN
Solar/Wind Harmer
4.784
970535AG2-341 GEN
50/50
4.621
964791AG1-342 GEN
Solar/Wind Harmer
1.563
939181AE1-148 GEN
Solar/Wind Harmer
3.409
971193AH1-056 GEN
Solar/Wind Harmer
26.382
970683AG2-441 GEN
Solar/Wind Harmer
25.493
962561AG1-105 GEN
Solar/Wind Harmer
4.444
963181AG1-167 GEN
Solar/Wind Harmer
3.588
970257AG2-171 GEN
Solar/Wind Harmer
9.989
315657AE1-056 GEN
Solar/Wind Harmer
15.829
3147043LAWRENC
Solar/Wind Harmer
0.112
971563AH1-280 GEN
Solar/Wind Harmer
4.784
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.021
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.053
CPLELTFEXP_CPLE->PJM
CLTF
0.148
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.042
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.012
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.036
LAGNLTFEXP_LAGN->PJM
CLTF
0.036
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.268
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.021
NYPJM->LTFIMP_NY
CLTF
0.084
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.557

Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235_SRT-A-4


Base Case Flowgate

Area:DVP
Facility Description:
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-2: LN 235_SRT-A-4
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:212.46 %
Rating:206.05 MVA
Rating Type:B
MVA to Mitigate:437.77
MW Contribution:6.21
Bus #Bus NameTypeMW Contribution
970685AG2-442 GEN
Solar/Wind Harmer
30.786
971775AH1-396 GEN
Solar/Wind Harmer
2.196
957481AF2-042 GEN
Solar/Wind Harmer
3.137
946301AF1-294 GEN
Solar/Wind Harmer
10.439
3144303KENBRDG
Solar/Wind Harmer
0.732
942461AE2-259 GEN
Solar/Wind Harmer
0.001
963191AG1-168 GEN
Solar/Wind Harmer
3.819
970681AG2-440 GEN
Solar/Wind Harmer
21.99
964241AG1-285 GEN
Solar/Wind Harmer
16.212
970401AG2-262 GEN
Solar/Wind Harmer
0.669
960061AF2-297 GEN
Solar/Wind Harmer
2.583
970099AG2-077 GEN
Solar/Wind Harmer
1.255
3147043LAWRENC
50/50
0.932
3147133PAMPLIN
Solar/Wind Harmer
1.115
961791AG1-021 GEN
Solar/Wind Harmer
5.092
971795AH1-408 GEN
Solar/Wind Harmer
5.172
3147133PAMPLIN
Solar/Wind Harmer
1.394
958211AF2-115 GEN
Solar/Wind Harmer
6.365
959311AF2-222 GEN
Solar/Wind Harmer
32.336
3146843MT LREL
Solar/Wind Harmer
0.303
3146843MT LREL
Solar/Wind Harmer
0.303
3147133PAMPLIN
Solar/Wind Harmer
4.378
3147173SINAI
Solar/Wind Harmer
0.161
3147243WELCO
Solar/Wind Harmer
0.101
970323AG2-213 GEN
Solar/Wind Harmer
14.643
315785AD2-033 C
Solar/Wind Harmer
0.001
963171AG1-166 GEN
Solar/Wind Harmer
5.092
270494AE1-108_GEN
Solar/Wind Helper
2.478
970535AG2-341 GEN
50/50
6.213
964791AG1-342 GEN
Solar/Wind Harmer
2.19
939181AE1-148 GEN
Solar/Wind Harmer
5.099
971193AH1-056 GEN
Solar/Wind Harmer
27.883
970683AG2-441 GEN
Solar/Wind Harmer
27.487
962561AG1-105 GEN
Solar/Wind Harmer
6.019
963181AG1-167 GEN
Solar/Wind Harmer
3.819
970257AG2-171 GEN
Solar/Wind Harmer
10.982
970831AG2-522 GEN
Solar/Wind Harmer
2.923
316322AB2-045
Solar/Wind Helper
0.751
971065AG2-659 GEN
Solar/Wind Harmer
3.171
315821AE2-092 GEN
Solar/Wind Helper
2.005
315657AE1-056 GEN
Solar/Wind Harmer
16.73
3147043LAWRENC
Solar/Wind Harmer
0.15
971563AH1-280 GEN
Solar/Wind Harmer
5.092
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.676
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.086
MECLTFEXP_MEC->PJM
CLTF
0.19
SIGELTFEXP_SIGE->PJM
CLTF
0.005
CPLELTFEXP_CPLE->PJM
CLTF
1.329
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.938
LAGNLTFEXP_LAGN->PJM
CLTF
0.658
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.658
TVALTFEXP_TVA->PJM
CLTF
0.337
NYPJM->LTFIMP_NY
CLTF
0.2
LGEELTFEXP_LGEE->PJM
CLTF
0.043
WECLTFEXP_WEC->PJM
CLTF
0.023
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
3.411

Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-2: LN 1012_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:161.98 %
Rating:206.05 MVA
Rating Type:B
MVA to Mitigate:333.76
MW Contribution:2.51
Bus #Bus NameTypeMW Contribution
970685AG2-442 GEN
Solar/Wind Harmer
38.099
971775AH1-396 GEN
Solar/Wind Harmer
1.354
946301AF1-294 GEN
Solar/Wind Harmer
7.12
3144303KENBRDG
Solar/Wind Harmer
0.451
942461AE2-259 GEN
Solar/Wind Harmer
0
964241AG1-285 GEN
Solar/Wind Harmer
34.017
970681AG2-440 GEN
Solar/Wind Harmer
27.213
963191AG1-168 GEN
Solar/Wind Harmer
2.605
3147133PAMPLIN
Solar/Wind Harmer
1.089
961791AG1-021 GEN
Solar/Wind Harmer
3.473
959311AF2-222 GEN
Solar/Wind Harmer
45.446
3147133PAMPLIN
Solar/Wind Harmer
1.361
958211AF2-115 GEN
Solar/Wind Harmer
4.341
3147133PAMPLIN
Solar/Wind Harmer
4.272
970323AG2-213 GEN
Solar/Wind Harmer
9.028
315785AD2-033 C
Solar/Wind Harmer
0.001
963171AG1-166 GEN
Solar/Wind Harmer
3.473
970535AG2-341 GEN
50/50
2.506
970683AG2-441 GEN
Solar/Wind Harmer
34.017
971193AH1-056 GEN
Solar/Wind Harmer
27.213
963181AG1-167 GEN
Solar/Wind Harmer
2.605
970257AG2-171 GEN
Solar/Wind Harmer
6.771
315657AE1-056 GEN
Solar/Wind Harmer
16.328
971563AH1-280 GEN
Solar/Wind Harmer
3.473
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.173
MECLTFEXP_MEC->PJM
CLTF
0.005
CPLELTFEXP_CPLE->PJM
CLTF
0.294
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.387
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.007
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.019
LAGNLTFEXP_LAGN->PJM
CLTF
0.11
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.566
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.058
NYPJM->LTFIMP_NY
CLTF
0.074
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.848

Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P7-1: LN 1041-38_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P7-1: LN 1041-38_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:125.94 %
Rating:230.3 MVA
Rating Type:C
MVA to Mitigate:290.05
MW Contribution:5.1
Bus #Bus NameTypeMW Contribution
970831AG2-522 GEN
Solar/Wind Harmer
2.362
971193AH1-056 GEN
Solar/Wind Harmer
19.483
970683AG2-441 GEN
Solar/Wind Harmer
19.67
962561AG1-105 GEN
Solar/Wind Harmer
4.551
946301AF1-294 GEN
Solar/Wind Harmer
7.356
3144303KENBRDG
Solar/Wind Harmer
0.536
970535AG2-341 GEN
50/50
5.096
971443AH1-215 GEN
Solar/Wind Harmer
3.642
939181AE1-148 GEN
Solar/Wind Harmer
4.231
964791AG1-342 GEN
Solar/Wind Harmer
1.62
3147043LAWRENC
Solar/Wind Harmer
0.117
3147133PAMPLIN
Solar/Wind Harmer
0.779
961791AG1-021 GEN
Solar/Wind Harmer
3.588
971795AH1-408 GEN
Solar/Wind Harmer
3.966
971065AG2-659 GEN
Solar/Wind Harmer
2.596
315657AE1-056 GEN
Solar/Wind Harmer
11.69
963171AG1-166 GEN
Solar/Wind Harmer
3.588
971443AH1-215 GEN
Solar/Wind Harmer
3.521
942461AE2-259 GEN
Solar/Wind Harmer
0
963191AG1-168 GEN
Solar/Wind Harmer
2.691
970681AG2-440 GEN
Solar/Wind Harmer
15.736
964241AG1-285 GEN
Solar/Wind Harmer
12.5
970401AG2-262 GEN
Solar/Wind Harmer
0.495
3147133PAMPLIN
Solar/Wind Harmer
0.974
958211AF2-115 GEN
Solar/Wind Harmer
4.486
959311AF2-222 GEN
Solar/Wind Harmer
23.489
3146843MT LREL
Solar/Wind Harmer
0.224
3146843MT LREL
Solar/Wind Harmer
0.224
3147133PAMPLIN
Solar/Wind Harmer
3.059
970685AG2-442 GEN
Solar/Wind Harmer
22.03
971775AH1-396 GEN
Solar/Wind Harmer
1.607
963181AG1-167 GEN
Solar/Wind Harmer
2.691
970257AG2-171 GEN
Solar/Wind Harmer
8.034
970323AG2-213 GEN
Solar/Wind Harmer
10.713
315785AD2-033 C
Solar/Wind Harmer
0.001
971563AH1-280 GEN
Solar/Wind Harmer
3.588
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.112
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.401
MECLTFEXP_MEC->PJM
CLTF
0.06
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CPLELTFEXP_CPLE->PJM
CLTF
0.518
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.049
LAGNLTFEXP_LAGN->PJM
CLTF
0.243
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.018
TVALTFEXP_TVA->PJM
CLTF
0.126
NYPJM->LTFIMP_NY
CLTF
0.11
LGEELTFEXP_LGEE->PJM
CLTF
0.012
WECLTFEXP_WEC->PJM
CLTF
0.005
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.406

Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.71 %
Rating:201.54 MVA
Rating Type:A
MVA to Mitigate:243.28
MW Contribution:3.66
Bus #Bus NameTypeMW Contribution
970685AG2-442 GEN
Solar/Wind Harmer
20.334
971775AH1-396 GEN
Solar/Wind Harmer
1.435
946301AF1-294 GEN
Solar/Wind Harmer
6.945
3144303KENBRDG
Solar/Wind Harmer
0.478
942461AE2-259 GEN
Solar/Wind Harmer
0
963191AG1-168 GEN
Solar/Wind Harmer
2.541
970681AG2-440 GEN
Solar/Wind Harmer
14.525
964241AG1-285 GEN
Solar/Wind Harmer
10.317
970401AG2-262 GEN
Solar/Wind Harmer
0.386
3147043LAWRENC
50/50
0.55
3147133PAMPLIN
Solar/Wind Harmer
0.745
961791AG1-021 GEN
Solar/Wind Harmer
3.388
3147133PAMPLIN
Solar/Wind Harmer
0.931
958211AF2-115 GEN
Solar/Wind Harmer
4.235
959311AF2-222 GEN
Solar/Wind Harmer
21.206
3146843MT LREL
Solar/Wind Harmer
0.175
3146843MT LREL
Solar/Wind Harmer
0.175
3147133PAMPLIN
Solar/Wind Harmer
2.924
970323AG2-213 GEN
Solar/Wind Harmer
9.57
315785AD2-033 C
Solar/Wind Harmer
0.001
963171AG1-166 GEN
Solar/Wind Harmer
3.388
970535AG2-341 GEN
50/50
3.657
964791AG1-342 GEN
Solar/Wind Harmer
1.263
939181AE1-148 GEN
Solar/Wind Harmer
2.852
971193AH1-056 GEN
Solar/Wind Harmer
18.622
970683AG2-441 GEN
Solar/Wind Harmer
18.156
962561AG1-105 GEN
Solar/Wind Harmer
3.531
963181AG1-167 GEN
Solar/Wind Harmer
2.541
970257AG2-171 GEN
Solar/Wind Harmer
7.177
315657AE1-056 GEN
Solar/Wind Harmer
11.173
3147043LAWRENC
Solar/Wind Harmer
0.089
971563AH1-280 GEN
Solar/Wind Harmer
3.388
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.064
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.344
MECLTFEXP_MEC->PJM
CLTF
0.048
SIGELTFEXP_SIGE->PJM
CLTF
0.001
CPLELTFEXP_CPLE->PJM
CLTF
0.454
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.891
LAGNLTFEXP_LAGN->PJM
CLTF
0.21
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.896
TVALTFEXP_TVA->PJM
CLTF
0.109
NYPJM->LTFIMP_NY
CLTF
0.093
LGEELTFEXP_LGEE->PJM
CLTF
0.008
WECLTFEXP_WEC->PJM
CLTF
0.004
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.233

Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P7-1: LN 1041-137_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P7-1: LN 1041-137_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:119.93 %
Rating:230.3 MVA
Rating Type:C
MVA to Mitigate:276.19
MW Contribution:8.0
Bus #Bus NameTypeMW Contribution
971193AH1-056 GEN
Solar/Wind Harmer
20.158
970683AG2-441 GEN
Solar/Wind Harmer
20.707
962561AG1-105 GEN
Solar/Wind Harmer
5.142
946301AF1-294 GEN
Solar/Wind Harmer
7.66
3144303KENBRDG
Solar/Wind Harmer
0.573
970535AG2-341 GEN
50/50
8.003
971443AH1-215 GEN
Solar/Wind Harmer
3.9
939181AE1-148 GEN
Solar/Wind Harmer
8.355
964791AG1-342 GEN
Solar/Wind Harmer
1.826
3147043LAWRENC
Solar/Wind Harmer
0.125
3147133PAMPLIN
Solar/Wind Harmer
0.806
961791AG1-021 GEN
Solar/Wind Harmer
3.736
971795AH1-408 GEN
Solar/Wind Harmer
4.175
315657AE1-056 GEN
Solar/Wind Harmer
12.095
963171AG1-166 GEN
Solar/Wind Harmer
3.736
971443AH1-215 GEN
Solar/Wind Harmer
3.77
942461AE2-259 GEN
Solar/Wind Harmer
0
963191AG1-168 GEN
Solar/Wind Harmer
2.802
970681AG2-440 GEN
Solar/Wind Harmer
16.565
964241AG1-285 GEN
Solar/Wind Harmer
13.833
970401AG2-262 GEN
Solar/Wind Harmer
0.558
3147133PAMPLIN
Solar/Wind Harmer
1.008
958211AF2-115 GEN
Solar/Wind Harmer
4.67
959311AF2-222 GEN
Solar/Wind Harmer
24.99
3146843MT LREL
Solar/Wind Harmer
0.252
3146843MT LREL
Solar/Wind Harmer
0.252
3147133PAMPLIN
Solar/Wind Harmer
3.165
970685AG2-442 GEN
Solar/Wind Harmer
23.191
971775AH1-396 GEN
Solar/Wind Harmer
1.718
963181AG1-167 GEN
Solar/Wind Harmer
2.802
970257AG2-171 GEN
Solar/Wind Harmer
8.591
970323AG2-213 GEN
Solar/Wind Harmer
11.455
315785AD2-033 C
Solar/Wind Harmer
0.001
971563AH1-280 GEN
Solar/Wind Harmer
3.736
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.299
MECLTFEXP_MEC->PJM
CLTF
0.038
SIGELTFEXP_SIGE->PJM
CLTF
0.001
CPLELTFEXP_CPLE->PJM
CLTF
0.397
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.76
LAGNLTFEXP_LAGN->PJM
CLTF
0.183
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.789
TVALTFEXP_TVA->PJM
CLTF
0.095
NYPJM->LTFIMP_NY
CLTF
0.094
LGEELTFEXP_LGEE->PJM
CLTF
0.005
WECLTFEXP_WEC->PJM
CLTF
0.002
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.131

Details for 3FLAT CREEK-3MORAN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3FLAT CREEK-3MORAN 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 84_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.95 %
Rating:221.84 MVA
Rating Type:B
MVA to Mitigate:226.16
MW Contribution:4.55
Bus #Bus NameTypeMW Contribution
963171AG1-166 GEN
Solar/Wind Harmer
6.278
970323AG2-213 GEN
Solar/Wind Harmer
16.328
315785AD2-033 C
Solar/Wind Harmer
0.001
970683AG2-441 GEN
Solar/Wind Harmer
9.661
971193AH1-056 GEN
Solar/Wind Harmer
7.728
962561AG1-105 GEN
Solar/Wind Harmer
4.398
970535AG2-341 GEN
50/50
4.555
964791AG1-342 GEN
Solar/Wind Harmer
1.574
939181AE1-148 GEN
Solar/Wind Harmer
3.554
963181AG1-167 GEN
Solar/Wind Harmer
4.708
970257AG2-171 GEN
Solar/Wind Harmer
12.246
316322AB2-045
Solar/Wind Helper
0.281
946301AF1-294 GEN
Solar/Wind Harmer
12.869
3144303KENBRDG
Solar/Wind Harmer
0.816
3147133PAMPLIN
Solar/Wind Harmer
1.213
3147043LAWRENC
Solar/Wind Harmer
0.11
3147043LAWRENC
50/50
0.686
961791AG1-021 GEN
Solar/Wind Harmer
6.278
3147133PAMPLIN
Solar/Wind Harmer
0.309
971795AH1-408 GEN
Solar/Wind Harmer
3.75
958211AF2-115 GEN
Solar/Wind Harmer
7.847
959311AF2-222 GEN
Solar/Wind Harmer
12.907
3147133PAMPLIN
Solar/Wind Harmer
0.386
3146843MT LREL
Solar/Wind Harmer
0.218
3146843MT LREL
Solar/Wind Harmer
0.218
315657AE1-056 GEN
Solar/Wind Harmer
4.637
963191AG1-168 GEN
Solar/Wind Harmer
4.708
964241AG1-285 GEN
Solar/Wind Harmer
9.661
970681AG2-440 GEN
Solar/Wind Harmer
7.729
970401AG2-262 GEN
Solar/Wind Harmer
0.481
971775AH1-396 GEN
Solar/Wind Harmer
2.449
970685AG2-442 GEN
Solar/Wind Harmer
10.82
971563AH1-280 GEN
Solar/Wind Harmer
6.278
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.419
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.516
MECLTFEXP_MEC->PJM
CLTF
0.099
SIGELTFEXP_SIGE->PJM
CLTF
0.003
CPLELTFEXP_CPLE->PJM
CLTF
0.589
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.419
LAGNLTFEXP_LAGN->PJM
CLTF
0.308
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.183
TVALTFEXP_TVA->PJM
CLTF
0.158
NYPJM->LTFIMP_NY
CLTF
0.1
LGEELTFEXP_LGEE->PJM
CLTF
0.026
WECLTFEXP_WEC->PJM
CLTF
0.013
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.531

Details for 3MORAN-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3MORAN-3FARMVIL 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 84_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.29 %
Rating:221.84 MVA
Rating Type:B
MVA to Mitigate:224.7
MW Contribution:4.55
Bus #Bus NameTypeMW Contribution
963171AG1-166 GEN
Solar/Wind Harmer
6.278
970323AG2-213 GEN
Solar/Wind Harmer
16.328
315785AD2-033 C
Solar/Wind Harmer
0.001
970683AG2-441 GEN
Solar/Wind Harmer
9.661
971193AH1-056 GEN
Solar/Wind Harmer
7.728
962561AG1-105 GEN
Solar/Wind Harmer
4.398
970535AG2-341 GEN
50/50
4.555
964791AG1-342 GEN
Solar/Wind Harmer
1.574
939181AE1-148 GEN
Solar/Wind Harmer
3.554
963181AG1-167 GEN
Solar/Wind Harmer
4.708
970257AG2-171 GEN
Solar/Wind Harmer
12.246
316322AB2-045
Solar/Wind Helper
0.281
946301AF1-294 GEN
Solar/Wind Harmer
12.869
3144303KENBRDG
Solar/Wind Harmer
0.816
3147133PAMPLIN
Solar/Wind Harmer
1.213
3147043LAWRENC
Solar/Wind Harmer
0.11
3147043LAWRENC
50/50
0.686
961791AG1-021 GEN
Solar/Wind Harmer
6.278
3147133PAMPLIN
Solar/Wind Harmer
0.309
971795AH1-408 GEN
Solar/Wind Harmer
3.75
958211AF2-115 GEN
Solar/Wind Harmer
7.847
959311AF2-222 GEN
Solar/Wind Harmer
12.907
3147133PAMPLIN
Solar/Wind Harmer
0.386
315657AE1-056 GEN
Solar/Wind Harmer
4.637
963191AG1-168 GEN
Solar/Wind Harmer
4.708
964241AG1-285 GEN
Solar/Wind Harmer
9.661
970681AG2-440 GEN
Solar/Wind Harmer
7.729
970401AG2-262 GEN
Solar/Wind Harmer
0.481
3146843MT LREL
Solar/Wind Harmer
0.218
3146843MT LREL
Solar/Wind Harmer
0.218
971775AH1-396 GEN
Solar/Wind Harmer
2.449
970685AG2-442 GEN
Solar/Wind Harmer
10.82
971563AH1-280 GEN
Solar/Wind Harmer
6.278
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.419
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.516
MECLTFEXP_MEC->PJM
CLTF
0.099
SIGELTFEXP_SIGE->PJM
CLTF
0.003
CPLELTFEXP_CPLE->PJM
CLTF
0.589
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.419
LAGNLTFEXP_LAGN->PJM
CLTF
0.308
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.183
TVALTFEXP_TVA->PJM
CLTF
0.158
NYPJM->LTFIMP_NY
CLTF
0.1
LGEELTFEXP_LGEE->PJM
CLTF
0.026
WECLTFEXP_WEC->PJM
CLTF
0.013
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
1.531

Details for 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:129.58 %
Rating:228.42 MVA
Rating Type:A
MVA to Mitigate:295.99
MW Contribution:2.87
Bus #Bus NameTypeMW Contribution
970685AG2-442 GEN
Solar/Wind Harmer
36.25
942461AE2-259 GEN
Solar/Wind Harmer
0.001
970681AG2-440 GEN
Solar/Wind Harmer
25.893
964241AG1-285 GEN
Solar/Wind Harmer
12.558
3147133PAMPLIN
Solar/Wind Harmer
1.45
3147133PAMPLIN
Solar/Wind Harmer
1.812
959311AF2-222 GEN
Solar/Wind Harmer
35.535
3147133PAMPLIN
Solar/Wind Harmer
5.691
970535AG2-341 GEN
50/50
2.873
971193AH1-056 GEN
Solar/Wind Harmer
36.246
970683AG2-441 GEN
Solar/Wind Harmer
32.366
962561AG1-105 GEN
Solar/Wind Harmer
2.772
315657AE1-056 GEN
Solar/Wind Harmer
21.748
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.188
MECLTFEXP_MEC->PJM
CLTF
0.001
CPLELTFEXP_CPLE->PJM
CLTF
0.334
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.408
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.01
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.028
LAGNLTFEXP_LAGN->PJM
CLTF
0.121
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.642
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.063
NYPJM->LTFIMP_NY
CLTF
0.087
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.974

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.65 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:985.92
MW Contribution:5.5
Bus #Bus NameTypeMW Contribution
941591AE2-156 GEN
50/50
5.885
3146926FARMVIL
Solar/Wind Harmer
0.482
3146926FARMVIL
Solar/Wind Harmer
0.482
970685AG2-442 GEN
Solar/Wind Harmer
14.615
971775AH1-396 GEN
Solar/Wind Harmer
1.131
966001AG1-469 GEN
Solar/Wind Helper
0.309
315616AA1-038_C
Solar/Wind Helper
1.093
970531AG2-338 GEN
50/50
2.942
3146776BUCKING
Solar/Wind Harmer
4.03
3146776BUCKING
Solar/Wind Harmer
0.326
946301AF1-294 GEN
Solar/Wind Harmer
4.672
971741AH1-377 GEN
Solar/Wind Harmer
20.67
3144303KENBRDG
Solar/Wind Harmer
0.377
972185AH1-677 GEN
50/50
4.982
944641AF1-129 GEN
50/50
18.776
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
6.356
963191AG1-168 GEN
Solar/Wind Harmer
1.709
970681AG2-440 GEN
Solar/Wind Harmer
10.44
964241AG1-285 GEN
Solar/Wind Harmer
9.945
316303AF2-085
50/50
2.185
3147043LAWRENC
50/50
0.98
3147133PAMPLIN
Solar/Wind Harmer
0.482
961791AG1-021 GEN
Solar/Wind Harmer
2.279
316192AB2-158 GEN
Solar/Wind Helper
1.356
970285AG2-188 GEN
Solar/Wind Harmer
26.806
3147133PAMPLIN
Solar/Wind Harmer
0.603
958211AF2-115 GEN
Solar/Wind Harmer
2.849
959311AF2-222 GEN
Solar/Wind Harmer
16.226
970937AG2-583 GEN
Solar/Wind Harmer
23.968
971845AH1-439 GEN
Solar/Wind Harmer
16.834
3147133PAMPLIN
Solar/Wind Harmer
1.894
316499AE2-029_GEN
Solar/Wind Helper
0.95
970301AG2-198 GEN
Solar/Wind Harmer
9.831
970323AG2-213 GEN
Solar/Wind Harmer
7.539
315785AD2-033 C
Solar/Wind Harmer
0.001
970119AG2-088 GEN
50/50
16.39
3146776BUCKING
Solar/Wind Harmer
0.363
963171AG1-166 GEN
Solar/Wind Harmer
2.279
962491AG1-098 GEN
Solar/Wind Harmer
5.987
970535AG2-341 GEN
50/50
5.504
972187AH1-678 GEN
50/50
2.54
315779AE2-040
50/50
1.062
3146776BUCKING
Solar/Wind Harmer
0.403
3143336POWHATN
Solar/Wind Harmer
2.767
3143336POWHATN
Solar/Wind Harmer
2.352
971193AH1-056 GEN
Solar/Wind Harmer
12.062
970683AG2-441 GEN
Solar/Wind Harmer
13.049
963181AG1-167 GEN
Solar/Wind Harmer
1.709
970257AG2-171 GEN
Solar/Wind Harmer
5.655
970413AG2-270 GEN
50/50
15.291
316322AB2-045
Solar/Wind Harmer
0.029
972003AH1-546 GEN
Solar/Wind Harmer
19.314
315657AE1-056 GEN
Solar/Wind Harmer
7.237
963041AG1-153 GEN
50/50
5.603
972205AH1-687 GEN
50/50
22.082
970533AG2-339 GEN
50/50
7.355
971563AH1-280 GEN
Solar/Wind Harmer
2.279
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.233
MECLTFEXP_MEC->PJM
CLTF
0.086
CPLELTFEXP_CPLE->PJM
CLTF
3.897
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.1
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.088
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.247
LAGNLTFEXP_LAGN->PJM
CLTF
1.443
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.452
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.744
NYPJM->LTFIMP_NY
CLTF
0.685
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.518

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.18 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:932.17
MW Contribution:4.56
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
1.49
3147043LAWRENC
50/50
0.755
3147133PAMPLIN
Solar/Wind Harmer
0.434
961791AG1-021 GEN
Solar/Wind Harmer
2.039
316192AB2-158 GEN
Solar/Wind Helper
1.361
970285AG2-188 GEN
Solar/Wind Harmer
24.963
3147133PAMPLIN
Solar/Wind Harmer
0.542
958211AF2-115 GEN
Solar/Wind Harmer
2.549
959311AF2-222 GEN
Solar/Wind Harmer
14.287
3146926FARMVIL
Solar/Wind Harmer
0.443
3146926FARMVIL
Solar/Wind Harmer
0.443
970685AG2-442 GEN
Solar/Wind Harmer
12.965
971775AH1-396 GEN
Solar/Wind Harmer
0.992
970301AG2-198 GEN
Solar/Wind Harmer
8.766
970323AG2-213 GEN
Solar/Wind Harmer
6.616
315785AD2-033 C
Solar/Wind Harmer
0
3146776BUCKING
Solar/Wind Harmer
3.767
3146776BUCKING
Solar/Wind Harmer
0.305
946301AF1-294 GEN
Solar/Wind Harmer
4.18
971741AH1-377 GEN
Solar/Wind Harmer
18.185
3144303KENBRDG
Solar/Wind Harmer
0.331
970119AG2-088 GEN
50/50
11.178
3146776BUCKING
Solar/Wind Harmer
0.339
963171AG1-166 GEN
Solar/Wind Harmer
2.039
962491AG1-098 GEN
Solar/Wind Harmer
4.897
3143336POWHATN
Solar/Wind Harmer
2.42
3143336POWHATN
Solar/Wind Harmer
2.057
971193AH1-056 GEN
Solar/Wind Harmer
10.845
970683AG2-441 GEN
Solar/Wind Harmer
11.576
970535AG2-341 GEN
50/50
4.562
3146776BUCKING
Solar/Wind Harmer
0.377
315760AF1-028 GEN
50/50
Charging
15.615
970117AG2-086 GEN
50/50
Charging
1.26
963181AG1-167 GEN
Solar/Wind Harmer
1.529
970257AG2-171 GEN
Solar/Wind Harmer
4.962
315616AA1-038_C
Solar/Wind Helper
1.713
966001AG1-469 GEN
Solar/Wind Helper
0.327
970413AG2-270 GEN
50/50
11.997
316322AB2-045
Solar/Wind Harmer
0.027
315657AE1-056 GEN
Solar/Wind Harmer
6.507
970937AG2-583 GEN
Solar/Wind Harmer
22.266
971845AH1-439 GEN
Solar/Wind Harmer
15.715
3147133PAMPLIN
Solar/Wind Harmer
1.703
316499AE2-029_GEN
Solar/Wind Helper
1.238
972003AH1-546 GEN
Solar/Wind Harmer
18.259
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
5.668
963191AG1-168 GEN
Solar/Wind Harmer
1.529
970681AG2-440 GEN
Solar/Wind Harmer
9.261
964241AG1-285 GEN
Solar/Wind Harmer
8.546
972205AH1-687 GEN
50/50
20.919
971563AH1-280 GEN
Solar/Wind Harmer
2.039
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.845
MECLTFEXP_MEC->PJM
CLTF
0.888
SIGELTFEXP_SIGE->PJM
CLTF
0.027
CPLELTFEXP_CPLE->PJM
CLTF
3.207
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.948
LAGNLTFEXP_LAGN->PJM
CLTF
2.195
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.99
TVALTFEXP_TVA->PJM
CLTF
1.148
NYPJM->LTFIMP_NY
CLTF
0.687
LGEELTFEXP_LGEE->PJM
CLTF
0.301
WECLTFEXP_WEC->PJM
CLTF
0.145
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
9.963

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.47 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:984.41
MW Contribution:5.5
Bus #Bus NameTypeMW Contribution
941591AE2-156 GEN
50/50
5.885
3146926FARMVIL
Solar/Wind Harmer
0.482
3146926FARMVIL
Solar/Wind Harmer
0.482
970685AG2-442 GEN
Solar/Wind Harmer
14.615
971775AH1-396 GEN
Solar/Wind Harmer
1.131
966001AG1-469 GEN
Solar/Wind Helper
0.309
315616AA1-038_C
Solar/Wind Helper
1.093
970531AG2-338 GEN
50/50
2.942
3146776BUCKING
Solar/Wind Harmer
4.03
3146776BUCKING
Solar/Wind Harmer
0.326
946301AF1-294 GEN
Solar/Wind Harmer
4.672
971741AH1-377 GEN
Solar/Wind Harmer
20.67
3144303KENBRDG
Solar/Wind Harmer
0.377
972185AH1-677 GEN
50/50
4.982
944641AF1-129 GEN
50/50
18.776
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
6.356
963191AG1-168 GEN
Solar/Wind Harmer
1.709
970681AG2-440 GEN
Solar/Wind Harmer
10.44
964241AG1-285 GEN
Solar/Wind Harmer
9.945
316303AF2-085
50/50
2.185
3147043LAWRENC
50/50
0.98
3147133PAMPLIN
Solar/Wind Harmer
0.482
961791AG1-021 GEN
Solar/Wind Harmer
2.279
316192AB2-158 GEN
Solar/Wind Helper
1.356
970285AG2-188 GEN
Solar/Wind Harmer
26.806
3147133PAMPLIN
Solar/Wind Harmer
0.603
958211AF2-115 GEN
Solar/Wind Harmer
2.849
959311AF2-222 GEN
Solar/Wind Harmer
16.226
970937AG2-583 GEN
Solar/Wind Harmer
23.968
971845AH1-439 GEN
Solar/Wind Harmer
16.834
3147133PAMPLIN
Solar/Wind Harmer
1.894
316499AE2-029_GEN
Solar/Wind Helper
0.95
970301AG2-198 GEN
Solar/Wind Harmer
9.831
970323AG2-213 GEN
Solar/Wind Harmer
7.539
315785AD2-033 C
Solar/Wind Harmer
0.001
970119AG2-088 GEN
50/50
16.39
3146776BUCKING
Solar/Wind Harmer
0.363
963171AG1-166 GEN
Solar/Wind Harmer
2.279
962491AG1-098 GEN
Solar/Wind Harmer
5.987
970535AG2-341 GEN
50/50
5.504
972187AH1-678 GEN
50/50
2.54
315779AE2-040
50/50
1.062
3146776BUCKING
Solar/Wind Harmer
0.403
3143336POWHATN
Solar/Wind Harmer
2.767
3143336POWHATN
Solar/Wind Harmer
2.352
971193AH1-056 GEN
Solar/Wind Harmer
12.062
970683AG2-441 GEN
Solar/Wind Harmer
13.049
963181AG1-167 GEN
Solar/Wind Harmer
1.709
970257AG2-171 GEN
Solar/Wind Harmer
5.655
970413AG2-270 GEN
50/50
15.291
316322AB2-045
Solar/Wind Harmer
0.029
972003AH1-546 GEN
Solar/Wind Harmer
19.314
315657AE1-056 GEN
Solar/Wind Harmer
7.237
963041AG1-153 GEN
50/50
5.603
972205AH1-687 GEN
50/50
22.082
970533AG2-339 GEN
50/50
7.355
971563AH1-280 GEN
Solar/Wind Harmer
2.279
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.233
MECLTFEXP_MEC->PJM
CLTF
0.086
CPLELTFEXP_CPLE->PJM
CLTF
3.897
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.1
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.088
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.247
LAGNLTFEXP_LAGN->PJM
CLTF
1.443
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.452
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.744
NYPJM->LTFIMP_NY
CLTF
0.685
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.518

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.0 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:930.64
MW Contribution:4.56
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
1.49
3147043LAWRENC
50/50
0.755
3147133PAMPLIN
Solar/Wind Harmer
0.434
961791AG1-021 GEN
Solar/Wind Harmer
2.039
316192AB2-158 GEN
Solar/Wind Helper
1.361
970285AG2-188 GEN
Solar/Wind Harmer
24.963
3147133PAMPLIN
Solar/Wind Harmer
0.542
958211AF2-115 GEN
Solar/Wind Harmer
2.549
959311AF2-222 GEN
Solar/Wind Harmer
14.287
970301AG2-198 GEN
Solar/Wind Harmer
8.766
970119AG2-088 GEN
50/50
11.178
3146776BUCKING
Solar/Wind Harmer
0.339
963171AG1-166 GEN
Solar/Wind Harmer
2.039
962491AG1-098 GEN
Solar/Wind Harmer
4.897
970323AG2-213 GEN
Solar/Wind Harmer
6.616
315785AD2-033 C
Solar/Wind Harmer
0
3143336POWHATN
Solar/Wind Harmer
2.42
3143336POWHATN
Solar/Wind Harmer
2.057
971193AH1-056 GEN
Solar/Wind Harmer
10.845
970683AG2-441 GEN
Solar/Wind Harmer
11.576
970535AG2-341 GEN
50/50
4.562
3146776BUCKING
Solar/Wind Harmer
0.377
3146776BUCKING
Solar/Wind Harmer
3.767
3146776BUCKING
Solar/Wind Harmer
0.305
946301AF1-294 GEN
Solar/Wind Harmer
4.18
971741AH1-377 GEN
Solar/Wind Harmer
18.185
3144303KENBRDG
Solar/Wind Harmer
0.331
315760AF1-028 GEN
50/50
Charging
15.615
970117AG2-086 GEN
50/50
Charging
1.26
963181AG1-167 GEN
Solar/Wind Harmer
1.529
970257AG2-171 GEN
Solar/Wind Harmer
4.962
3146926FARMVIL
Solar/Wind Harmer
0.443
3146926FARMVIL
Solar/Wind Harmer
0.443
970685AG2-442 GEN
Solar/Wind Harmer
12.965
971775AH1-396 GEN
Solar/Wind Harmer
0.992
315616AA1-038_C
Solar/Wind Helper
1.713
966001AG1-469 GEN
Solar/Wind Helper
0.327
970413AG2-270 GEN
50/50
11.997
316322AB2-045
Solar/Wind Harmer
0.027
315657AE1-056 GEN
Solar/Wind Harmer
6.507
970937AG2-583 GEN
Solar/Wind Harmer
22.266
971845AH1-439 GEN
Solar/Wind Harmer
15.715
3147133PAMPLIN
Solar/Wind Harmer
1.703
316499AE2-029_GEN
Solar/Wind Helper
1.238
972003AH1-546 GEN
Solar/Wind Harmer
18.259
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
5.668
963191AG1-168 GEN
Solar/Wind Harmer
1.529
970681AG2-440 GEN
Solar/Wind Harmer
9.261
964241AG1-285 GEN
Solar/Wind Harmer
8.546
972205AH1-687 GEN
50/50
20.919
971563AH1-280 GEN
Solar/Wind Harmer
2.039
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.845
MECLTFEXP_MEC->PJM
CLTF
0.888
SIGELTFEXP_SIGE->PJM
CLTF
0.027
CPLELTFEXP_CPLE->PJM
CLTF
3.207
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.948
LAGNLTFEXP_LAGN->PJM
CLTF
2.195
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.99
TVALTFEXP_TVA->PJM
CLTF
1.148
NYPJM->LTFIMP_NY
CLTF
0.687
LGEELTFEXP_LGEE->PJM
CLTF
0.301
WECLTFEXP_WEC->PJM
CLTF
0.145
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
9.963

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.61 %
Rating:698.42 MVA
Rating Type:B
MVA to Mitigate:814.45
MW Contribution:7.8
Bus #Bus NameTypeMW Contribution
3146926FARMVIL
Solar/Wind Harmer
0.828
3146926FARMVIL
Solar/Wind Harmer
0.828
970685AG2-442 GEN
Solar/Wind Harmer
23.537
971775AH1-396 GEN
Solar/Wind Harmer
1.784
970531AG2-338 GEN
50/50
2.696
3146776BUCKING
Solar/Wind Harmer
7.109
3146776BUCKING
Solar/Wind Harmer
0.576
946301AF1-294 GEN
Solar/Wind Harmer
7.643
971741AH1-377 GEN
Solar/Wind Harmer
33.27
3144303KENBRDG
Solar/Wind Harmer
0.595
315693AD1-088 GEN
Solar/Wind Harmer
8.129
972185AH1-677 GEN
50/50
4.788
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
10.442
963191AG1-168 GEN
Solar/Wind Harmer
2.796
970681AG2-440 GEN
Solar/Wind Harmer
16.812
964241AG1-285 GEN
Solar/Wind Harmer
15.072
3147043LAWRENC
50/50
1.216
3147133PAMPLIN
Solar/Wind Harmer
0.797
961791AG1-021 GEN
Solar/Wind Harmer
3.728
316336AC2-165 C
Solar/Wind Helper
3.444
970285AG2-188 GEN
Solar/Wind Harmer
47.021
3147133PAMPLIN
Solar/Wind Harmer
0.996
958211AF2-115 GEN
Solar/Wind Harmer
4.66
959311AF2-222 GEN
Solar/Wind Harmer
25.764
971845AH1-439 GEN
Solar/Wind Harmer
29.639
3147133PAMPLIN
Solar/Wind Harmer
3.127
970301AG2-198 GEN
Solar/Wind Harmer
16.15
970323AG2-213 GEN
Solar/Wind Harmer
11.895
315785AD2-033 C
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.64
963171AG1-166 GEN
Solar/Wind Harmer
3.728
962491AG1-098 GEN
Solar/Wind Harmer
11.428
270494AE1-108_GEN
Solar/Wind Helper
6.761
316313AB2-026
Solar/Wind Helper
0.584
970535AG2-341 GEN
50/50
7.8
972187AH1-678 GEN
50/50
2.49
315779AE2-040
50/50
0.838
3146776BUCKING
Solar/Wind Harmer
0.711
939181AE1-148 GEN
Solar/Wind Harmer
2.918
971193AH1-056 GEN
Solar/Wind Harmer
19.918
970683AG2-441 GEN
Solar/Wind Harmer
21.015
962561AG1-105 GEN
Solar/Wind Harmer
7.655
316405AF2-144 C
50/50
Charging
1.189
963181AG1-167 GEN
Solar/Wind Harmer
2.796
970257AG2-171 GEN
Solar/Wind Harmer
8.921
970413AG2-270 GEN
50/50
20.33
316322AB2-045
Solar/Wind Harmer
0.051
316258AE1-075 C
Solar/Wind Helper
0.526
315821AE2-092 GEN
Solar/Wind Helper
5.451
315657AE1-056 GEN
Solar/Wind Harmer
11.951
963041AG1-153 GEN
50/50
5.493
970533AG2-339 GEN
50/50
6.74
971563AH1-280 GEN
Solar/Wind Harmer
3.728
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.646
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.154
MECLTFEXP_MEC->PJM
CLTF
0.898
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
4.455
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.777
LAGNLTFEXP_LAGN->PJM
CLTF
2.469
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.083
TVALTFEXP_TVA->PJM
CLTF
1.262
NYPJM->LTFIMP_NY
CLTF
0.569
LGEELTFEXP_LGEE->PJM
CLTF
0.255
WECLTFEXP_WEC->PJM
CLTF
0.138
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.052

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.33 %
Rating:698.42 MVA
Rating Type:B
MVA to Mitigate:791.5
MW Contribution:11.54
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
1.476
971629AH1-314 GEN
50/50
5.948
3147133PAMPLIN
Solar/Wind Harmer
0.99
961791AG1-021 GEN
Solar/Wind Harmer
4.683
316336AC2-165 C
Solar/Wind Helper
2.946
970285AG2-188 GEN
Solar/Wind Harmer
52.716
3147133PAMPLIN
Solar/Wind Harmer
1.237
958211AF2-115 GEN
Solar/Wind Harmer
5.854
959311AF2-222 GEN
Solar/Wind Harmer
33.544
3146926FARMVIL
Solar/Wind Harmer
0.981
3146926FARMVIL
Solar/Wind Harmer
0.981
970685AG2-442 GEN
Solar/Wind Harmer
30.129
971775AH1-396 GEN
Solar/Wind Harmer
2.341
957481AF2-042 GEN
Solar/Wind Harmer
31.356
970301AG2-198 GEN
Solar/Wind Harmer
21.542
970323AG2-213 GEN
Solar/Wind Harmer
15.606
315785AD2-033 C
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
7.855
3146776BUCKING
Solar/Wind Harmer
0.636
971741AH1-377 GEN
Solar/Wind Harmer
46.756
946301AF1-294 GEN
Solar/Wind Harmer
9.601
3144303KENBRDG
Solar/Wind Harmer
0.78
315693AD1-088 GEN
Solar/Wind Harmer
15.302
3146776BUCKING
Solar/Wind Harmer
0.707
963171AG1-166 GEN
Solar/Wind Harmer
4.683
962491AG1-098 GEN
Solar/Wind Harmer
20.898
270494AE1-108_GEN
Solar/Wind Helper
5.515
316313AB2-026
Solar/Wind Helper
0.504
971193AH1-056 GEN
Solar/Wind Harmer
24.739
970683AG2-441 GEN
Solar/Wind Harmer
26.901
970535AG2-341 GEN
50/50
11.543
3146776BUCKING
Solar/Wind Harmer
0.786
316405AF2-144 C
50/50
Charging
1.026
963181AG1-167 GEN
Solar/Wind Harmer
3.512
970257AG2-171 GEN
Solar/Wind Harmer
11.705
970413AG2-270 GEN
50/50
42.688
316322AB2-045
Solar/Wind Harmer
0.057
316258AE1-075 C
Solar/Wind Helper
0.453
315657AE1-056 GEN
Solar/Wind Harmer
14.843
971845AH1-439 GEN
Solar/Wind Harmer
32.909
3147133PAMPLIN
Solar/Wind Harmer
3.884
315821AE2-092 GEN
Solar/Wind Helper
4.572
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
13.928
963191AG1-168 GEN
Solar/Wind Harmer
3.512
970681AG2-440 GEN
Solar/Wind Harmer
21.52
970099AG2-077 GEN
Solar/Wind Harmer
12.542
971563AH1-280 GEN
Solar/Wind Harmer
4.683
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.131
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.348
MECLTFEXP_MEC->PJM
CLTF
1.425
SIGELTFEXP_SIGE->PJM
CLTF
0.042
CPLELTFEXP_CPLE->PJM
CLTF
4.444
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.958
LAGNLTFEXP_LAGN->PJM
CLTF
3.082
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.689
TVALTFEXP_TVA->PJM
CLTF
1.577
NYPJM->LTFIMP_NY
CLTF
0.518
LGEELTFEXP_LGEE->PJM
CLTF
0.481
WECLTFEXP_WEC->PJM
CLTF
0.258
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.194

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.55 %
Rating:687.14 MVA
Rating Type:B
MVA to Mitigate:745.87
MW Contribution:7.81
Bus #Bus NameTypeMW Contribution
963171AG1-166 GEN
Solar/Wind Harmer
3.73
962491AG1-098 GEN
Solar/Wind Harmer
11.436
270494AE1-108_GEN
Solar/Wind Helper
6.756
316313AB2-026
Solar/Wind Helper
0.583
970301AG2-198 GEN
Solar/Wind Harmer
16.156
970323AG2-213 GEN
Solar/Wind Harmer
11.901
315785AD2-033 C
Solar/Wind Harmer
0.001
971193AH1-056 GEN
Solar/Wind Harmer
19.926
970683AG2-441 GEN
Solar/Wind Harmer
21.024
962561AG1-105 GEN
Solar/Wind Harmer
7.662
970535AG2-341 GEN
50/50
7.806
972187AH1-678 GEN
50/50
2.495
315779AE2-040
50/50
0.84
939181AE1-148 GEN
Solar/Wind Harmer
7.432
964791AG1-342 GEN
Solar/Wind Harmer
2.934
970531AG2-338 GEN
50/50
2.701
946301AF1-294 GEN
Solar/Wind Harmer
7.646
971741AH1-377 GEN
Solar/Wind Harmer
33.284
3144303KENBRDG
Solar/Wind Harmer
0.595
315693AD1-088 GEN
Solar/Wind Harmer
8.135
316405AF2-144 C
50/50
Charging
1.188
963181AG1-167 GEN
Solar/Wind Harmer
2.797
970257AG2-171 GEN
Solar/Wind Harmer
8.926
3146926FARMVIL
Solar/Wind Harmer
0.828
3146926FARMVIL
Solar/Wind Harmer
0.828
970685AG2-442 GEN
Solar/Wind Harmer
23.547
971775AH1-396 GEN
Solar/Wind Harmer
1.785
970413AG2-270 GEN
50/50
20.349
316322AB2-045
Solar/Wind Helper
2.037
316258AE1-075 C
Solar/Wind Helper
0.525
3147133PAMPLIN
Solar/Wind Harmer
3.128
963041AG1-153 GEN
50/50
5.503
3147043LAWRENC
50/50
1.217
3147133PAMPLIN
Solar/Wind Harmer
0.797
961791AG1-021 GEN
Solar/Wind Harmer
3.73
316336AC2-165 C
Solar/Wind Helper
3.441
3147133PAMPLIN
Solar/Wind Harmer
0.996
958211AF2-115 GEN
Solar/Wind Harmer
4.662
959311AF2-222 GEN
Solar/Wind Harmer
25.776
3146843MT LREL
Solar/Wind Harmer
0.407
3146843MT LREL
Solar/Wind Harmer
0.407
315821AE2-092 GEN
Solar/Wind Helper
5.447
972185AH1-677 GEN
50/50
4.797
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
10.446
963191AG1-168 GEN
Solar/Wind Harmer
2.797
970681AG2-440 GEN
Solar/Wind Harmer
16.82
964241AG1-285 GEN
Solar/Wind Harmer
15.081
970401AG2-262 GEN
Solar/Wind Harmer
0.897
970099AG2-077 GEN
Solar/Wind Harmer
3.066
315657AE1-056 GEN
Solar/Wind Harmer
11.956
957481AF2-042 GEN
Solar/Wind Harmer
7.666
970533AG2-339 GEN
50/50
6.753
971563AH1-280 GEN
Solar/Wind Harmer
3.73
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.808
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.196
MECLTFEXP_MEC->PJM
CLTF
0.917
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
4.467
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.926
LAGNLTFEXP_LAGN->PJM
CLTF
2.492
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.117
TVALTFEXP_TVA->PJM
CLTF
1.273
NYPJM->LTFIMP_NY
CLTF
0.562
LGEELTFEXP_LGEE->PJM
CLTF
0.263
WECLTFEXP_WEC->PJM
CLTF
0.142
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.052

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.24 %
Rating:687.14 MVA
Rating Type:B
MVA to Mitigate:736.92
MW Contribution:11.55
Bus #Bus NameTypeMW Contribution
963171AG1-166 GEN
Solar/Wind Harmer
4.685
962491AG1-098 GEN
Solar/Wind Harmer
20.906
270494AE1-108_GEN
Solar/Wind Helper
5.509
316313AB2-026
Solar/Wind Helper
0.503
970301AG2-198 GEN
Solar/Wind Harmer
21.548
970323AG2-213 GEN
Solar/Wind Harmer
15.612
315785AD2-033 C
Solar/Wind Harmer
0.001
971193AH1-056 GEN
Solar/Wind Harmer
24.746
970683AG2-441 GEN
Solar/Wind Harmer
26.91
970535AG2-341 GEN
50/50
11.549
971741AH1-377 GEN
Solar/Wind Harmer
46.769
946301AF1-294 GEN
Solar/Wind Harmer
9.604
3144303KENBRDG
Solar/Wind Harmer
0.781
315693AD1-088 GEN
Solar/Wind Harmer
15.308
316405AF2-144 C
50/50
Charging
1.025
963181AG1-167 GEN
Solar/Wind Harmer
3.514
970257AG2-171 GEN
Solar/Wind Harmer
11.709
970413AG2-270 GEN
50/50
42.707
316322AB2-045
Solar/Wind Helper
1.698
316258AE1-075 C
Solar/Wind Helper
0.453
3147133PAMPLIN
Solar/Wind Harmer
3.885
3147043LAWRENC
50/50
1.477
971629AH1-314 GEN
50/50
5.961
3147133PAMPLIN
Solar/Wind Harmer
0.99
961791AG1-021 GEN
Solar/Wind Harmer
4.685
316336AC2-165 C
Solar/Wind Helper
2.942
3147133PAMPLIN
Solar/Wind Harmer
1.237
958211AF2-115 GEN
Solar/Wind Harmer
5.856
959311AF2-222 GEN
Solar/Wind Harmer
33.556
315821AE2-092 GEN
Solar/Wind Helper
4.568
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
13.932
963191AG1-168 GEN
Solar/Wind Harmer
3.514
970681AG2-440 GEN
Solar/Wind Harmer
21.528
970099AG2-077 GEN
Solar/Wind Harmer
25.106
315657AE1-056 GEN
Solar/Wind Harmer
14.848
3146926FARMVIL
Solar/Wind Harmer
0.981
3146926FARMVIL
Solar/Wind Harmer
0.981
970685AG2-442 GEN
Solar/Wind Harmer
30.139
971775AH1-396 GEN
Solar/Wind Harmer
2.342
957481AF2-042 GEN
Solar/Wind Harmer
62.764
971563AH1-280 GEN
Solar/Wind Harmer
4.685
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.293
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.39
MECLTFEXP_MEC->PJM
CLTF
1.443
SIGELTFEXP_SIGE->PJM
CLTF
0.042
CPLELTFEXP_CPLE->PJM
CLTF
4.456
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.108
LAGNLTFEXP_LAGN->PJM
CLTF
3.105
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.723
TVALTFEXP_TVA->PJM
CLTF
1.589
NYPJM->LTFIMP_NY
CLTF
0.511
LGEELTFEXP_LGEE->PJM
CLTF
0.489
WECLTFEXP_WEC->PJM
CLTF
0.262
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.194

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.87 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:1012.68
MW Contribution:5.18
Bus #Bus NameTypeMW Contribution
941591AE2-156 GEN
50/50
5.412
3146926FARMVIL
Solar/Wind Harmer
0.45
3146926FARMVIL
Solar/Wind Harmer
0.45
970685AG2-442 GEN
Solar/Wind Harmer
13.686
966001AG1-469 GEN
Solar/Wind Helper
0.334
315616AA1-038_C
Solar/Wind Helper
1.051
970531AG2-338 GEN
50/50
2.734
3146776BUCKING
Solar/Wind Harmer
3.757
3146776BUCKING
Solar/Wind Harmer
0.304
946301AF1-294 GEN
Solar/Wind Harmer
4.371
971741AH1-377 GEN
Solar/Wind Harmer
19.305
972185AH1-677 GEN
50/50
4.638
944641AF1-129 GEN
50/50
25.205
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
5.934
963191AG1-168 GEN
Solar/Wind Harmer
1.599
970681AG2-440 GEN
Solar/Wind Harmer
9.775
316303AF2-085
50/50
2.018
3147043LAWRENC
50/50
0.919
3147133PAMPLIN
Solar/Wind Harmer
0.451
961791AG1-021 GEN
Solar/Wind Harmer
2.132
316192AB2-158 GEN
Solar/Wind Helper
1.482
970285AG2-188 GEN
Solar/Wind Harmer
24.994
3147133PAMPLIN
Solar/Wind Harmer
0.564
958211AF2-115 GEN
Solar/Wind Harmer
2.665
959311AF2-222 GEN
Solar/Wind Harmer
15.206
966251AG1-494 GEN
50/50
3.128
970937AG2-583 GEN
Solar/Wind Harmer
22.319
971845AH1-439 GEN
Solar/Wind Harmer
15.695
3147133PAMPLIN
Solar/Wind Harmer
1.771
316499AE2-029_GEN
Solar/Wind Helper
0.927
970301AG2-198 GEN
Solar/Wind Harmer
9.178
970323AG2-213 GEN
Solar/Wind Harmer
7.068
970119AG2-088 GEN
50/50
15.136
970221AG2-151 GEN
Solar/Wind Harmer
20.807
3146776BUCKING
Solar/Wind Harmer
0.338
270494AE1-108_GEN
Solar/Wind Harmer
0
963171AG1-166 GEN
Solar/Wind Harmer
2.132
970535AG2-341 GEN
50/50
5.181
972187AH1-678 GEN
50/50
2.367
315779AE2-040
50/50
0.984
3146776BUCKING
Solar/Wind Harmer
0.376
3143336POWHATN
Solar/Wind Harmer
2.572
3143336POWHATN
Solar/Wind Harmer
2.186
971193AH1-056 GEN
Solar/Wind Harmer
11.279
970683AG2-441 GEN
Solar/Wind Harmer
12.219
315760AF1-028 GEN
50/50
Charging
11.333
971377AH1-170 GEN
Solar/Wind Harmer
4.161
963181AG1-167 GEN
Solar/Wind Harmer
1.599
970257AG2-171 GEN
Solar/Wind Harmer
0.174
970413AG2-270 GEN
50/50
14.358
316322AB2-045
Solar/Wind Harmer
0.027
972003AH1-546 GEN
Solar/Wind Harmer
17.998
3147623JAMES R
Solar/Wind Harmer
0.542
971447AH1-217 GEN
Solar/Wind Harmer
10.898
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
971489AH1-241 GEN
Solar/Wind Harmer
20.807
315657AE1-056 GEN
Solar/Wind Harmer
6.767
963041AG1-153 GEN
50/50
5.221
972205AH1-687 GEN
50/50
20.575
970533AG2-339 GEN
50/50
6.834
971563AH1-280 GEN
Solar/Wind Harmer
2.132
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.656
MECLTFEXP_MEC->PJM
CLTF
0.289
SIGELTFEXP_SIGE->PJM
CLTF
0.006
CPLELTFEXP_CPLE->PJM
CLTF
3.782
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.617
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
1.646
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.434
TVALTFEXP_TVA->PJM
CLTF
0.852
NYPJM->LTFIMP_NY
CLTF
0.718
LGEELTFEXP_LGEE->PJM
CLTF
0.016
WECLTFEXP_WEC->PJM
CLTF
0.003
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.463

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.54 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:976.74
MW Contribution:4.27
Bus #Bus NameTypeMW Contribution
3146926FARMVIL
Solar/Wind Harmer
0.41
3146926FARMVIL
Solar/Wind Harmer
0.41
970685AG2-442 GEN
Solar/Wind Harmer
12.063
966001AG1-469 GEN
Solar/Wind Helper
0.358
315616AA1-038_C
Solar/Wind Helper
1.725
3146776BUCKING
Solar/Wind Harmer
3.491
3146776BUCKING
Solar/Wind Harmer
0.283
946301AF1-294 GEN
Solar/Wind Harmer
3.885
971741AH1-377 GEN
Solar/Wind Harmer
16.848
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
5.252
963191AG1-168 GEN
Solar/Wind Harmer
1.421
970681AG2-440 GEN
Solar/Wind Harmer
8.617
316303AF2-085
50/50
1.328
3147043LAWRENC
50/50
0.699
3147133PAMPLIN
Solar/Wind Harmer
0.403
961791AG1-021 GEN
Solar/Wind Harmer
1.895
316192AB2-158 GEN
Solar/Wind Helper
1.52
970285AG2-188 GEN
Solar/Wind Harmer
23.134
3147133PAMPLIN
Solar/Wind Harmer
0.504
958211AF2-115 GEN
Solar/Wind Harmer
2.369
959311AF2-222 GEN
Solar/Wind Harmer
13.304
966251AG1-494 GEN
50/50
3.897
970937AG2-583 GEN
Solar/Wind Harmer
20.592
971845AH1-439 GEN
Solar/Wind Harmer
14.563
3147133PAMPLIN
Solar/Wind Harmer
1.582
316499AE2-029_GEN
Solar/Wind Helper
1.242
970301AG2-198 GEN
Solar/Wind Harmer
8.122
970323AG2-213 GEN
Solar/Wind Harmer
6.163
970119AG2-088 GEN
50/50
9.961
970221AG2-151 GEN
Solar/Wind Harmer
19.574
3146776BUCKING
Solar/Wind Harmer
0.314
270494AE1-108_GEN
Solar/Wind Harmer
0
963171AG1-166 GEN
Solar/Wind Harmer
1.895
970535AG2-341 GEN
50/50
4.269
3146776BUCKING
Solar/Wind Harmer
0.349
3143336POWHATN
Solar/Wind Harmer
2.224
3143336POWHATN
Solar/Wind Harmer
1.89
971193AH1-056 GEN
Solar/Wind Harmer
10.075
970683AG2-441 GEN
Solar/Wind Harmer
10.771
315760AF1-028 GEN
50/50
Charging
15.678
970117AG2-086 GEN
50/50
Charging
1.272
971377AH1-170 GEN
Solar/Wind Harmer
3.915
963181AG1-167 GEN
Solar/Wind Harmer
1.421
970257AG2-171 GEN
Solar/Wind Harmer
0.152
970413AG2-270 GEN
50/50
11.154
316322AB2-045
Solar/Wind Harmer
0.025
972003AH1-546 GEN
Solar/Wind Harmer
16.919
3147623JAMES R
Solar/Wind Harmer
0.51
971447AH1-217 GEN
Solar/Wind Harmer
10.18
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
971489AH1-241 GEN
Solar/Wind Harmer
19.574
315657AE1-056 GEN
Solar/Wind Harmer
6.045
972205AH1-687 GEN
50/50
19.383
971563AH1-280 GEN
Solar/Wind Harmer
1.895
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.46
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.628
MECLTFEXP_MEC->PJM
CLTF
1.224
SIGELTFEXP_SIGE->PJM
CLTF
0.038
CPLELTFEXP_CPLE->PJM
CLTF
3.191
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.642
LAGNLTFEXP_LAGN->PJM
CLTF
2.588
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.28
TVALTFEXP_TVA->PJM
CLTF
1.354
NYPJM->LTFIMP_NY
CLTF
0.753
LGEELTFEXP_LGEE->PJM
CLTF
0.45
WECLTFEXP_WEC->PJM
CLTF
0.221
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.284

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.77 %
Rating:808.4 MVA
Rating Type:B
MVA to Mitigate:1008.61
MW Contribution:5.18
Bus #Bus NameTypeMW Contribution
941591AE2-156 GEN
50/50
5.412
3146926FARMVIL
Solar/Wind Harmer
0.45
3146926FARMVIL
Solar/Wind Harmer
0.45
970685AG2-442 GEN
Solar/Wind Harmer
13.686
966001AG1-469 GEN
Solar/Wind Helper
0.334
315616AA1-038_C
Solar/Wind Helper
1.051
970531AG2-338 GEN
50/50
2.734
3146776BUCKING
Solar/Wind Harmer
3.757
3146776BUCKING
Solar/Wind Harmer
0.304
946301AF1-294 GEN
Solar/Wind Harmer
4.371
971741AH1-377 GEN
Solar/Wind Harmer
19.305
972185AH1-677 GEN
50/50
4.638
944641AF1-129 GEN
50/50
25.205
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
5.934
963191AG1-168 GEN
Solar/Wind Harmer
1.599
970681AG2-440 GEN
Solar/Wind Harmer
9.775
316303AF2-085
50/50
2.018
3147043LAWRENC
50/50
0.919
3147133PAMPLIN
Solar/Wind Harmer
0.451
961791AG1-021 GEN
Solar/Wind Harmer
2.132
316192AB2-158 GEN
Solar/Wind Helper
1.482
970285AG2-188 GEN
Solar/Wind Harmer
24.994
3147133PAMPLIN
Solar/Wind Harmer
0.564
958211AF2-115 GEN
Solar/Wind Harmer
2.665
959311AF2-222 GEN
Solar/Wind Harmer
15.206
966251AG1-494 GEN
50/50
3.128
970937AG2-583 GEN
Solar/Wind Harmer
22.319
971845AH1-439 GEN
Solar/Wind Harmer
15.695
3147133PAMPLIN
Solar/Wind Harmer
1.771
316499AE2-029_GEN
Solar/Wind Helper
0.927
970301AG2-198 GEN
Solar/Wind Harmer
9.178
970323AG2-213 GEN
Solar/Wind Harmer
7.068
970119AG2-088 GEN
50/50
15.136
970221AG2-151 GEN
Solar/Wind Harmer
20.807
3146776BUCKING
Solar/Wind Harmer
0.338
270494AE1-108_GEN
Solar/Wind Harmer
0
963171AG1-166 GEN
Solar/Wind Harmer
2.132
970535AG2-341 GEN
50/50
5.181
972187AH1-678 GEN
50/50
2.367
315779AE2-040
50/50
0.984
3146776BUCKING
Solar/Wind Harmer
0.376
3143336POWHATN
Solar/Wind Harmer
2.572
3143336POWHATN
Solar/Wind Harmer
2.186
971193AH1-056 GEN
Solar/Wind Harmer
11.279
970683AG2-441 GEN
Solar/Wind Harmer
12.219
315760AF1-028 GEN
50/50
Charging
11.333
971377AH1-170 GEN
Solar/Wind Harmer
4.161
963181AG1-167 GEN
Solar/Wind Harmer
1.599
970257AG2-171 GEN
Solar/Wind Harmer
0.174
970413AG2-270 GEN
50/50
14.358
316322AB2-045
Solar/Wind Harmer
0.027
972003AH1-546 GEN
Solar/Wind Harmer
17.998
3147623JAMES R
Solar/Wind Harmer
0.542
971447AH1-217 GEN
Solar/Wind Harmer
10.898
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
971489AH1-241 GEN
Solar/Wind Harmer
20.807
315657AE1-056 GEN
Solar/Wind Harmer
6.767
963041AG1-153 GEN
50/50
5.221
972205AH1-687 GEN
50/50
20.575
970533AG2-339 GEN
50/50
6.834
971563AH1-280 GEN
Solar/Wind Harmer
2.132
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.656
MECLTFEXP_MEC->PJM
CLTF
0.289
SIGELTFEXP_SIGE->PJM
CLTF
0.006
CPLELTFEXP_CPLE->PJM
CLTF
3.782
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.617
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
1.646
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.434
TVALTFEXP_TVA->PJM
CLTF
0.852
NYPJM->LTFIMP_NY
CLTF
0.718
LGEELTFEXP_LGEE->PJM
CLTF
0.016
WECLTFEXP_WEC->PJM
CLTF
0.003
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.463

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.34 %
Rating:808.4 MVA
Rating Type:B
MVA to Mitigate:972.83
MW Contribution:4.27
Bus #Bus NameTypeMW Contribution
3146926FARMVIL
Solar/Wind Harmer
0.41
3146926FARMVIL
Solar/Wind Harmer
0.41
970685AG2-442 GEN
Solar/Wind Harmer
12.063
966001AG1-469 GEN
Solar/Wind Helper
0.358
315616AA1-038_C
Solar/Wind Helper
1.725
3146776BUCKING
Solar/Wind Harmer
3.491
3146776BUCKING
Solar/Wind Harmer
0.283
946301AF1-294 GEN
Solar/Wind Harmer
3.885
971741AH1-377 GEN
Solar/Wind Harmer
16.848
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
5.252
963191AG1-168 GEN
Solar/Wind Harmer
1.421
970681AG2-440 GEN
Solar/Wind Harmer
8.617
316303AF2-085
50/50
1.328
3147043LAWRENC
50/50
0.699
3147133PAMPLIN
Solar/Wind Harmer
0.403
961791AG1-021 GEN
Solar/Wind Harmer
1.895
316192AB2-158 GEN
Solar/Wind Helper
1.52
970285AG2-188 GEN
Solar/Wind Harmer
23.134
3147133PAMPLIN
Solar/Wind Harmer
0.504
958211AF2-115 GEN
Solar/Wind Harmer
2.369
959311AF2-222 GEN
Solar/Wind Harmer
13.304
966251AG1-494 GEN
50/50
3.897
970937AG2-583 GEN
Solar/Wind Harmer
20.592
971845AH1-439 GEN
Solar/Wind Harmer
14.563
3147133PAMPLIN
Solar/Wind Harmer
1.582
316499AE2-029_GEN
Solar/Wind Helper
1.242
970301AG2-198 GEN
Solar/Wind Harmer
8.122
970323AG2-213 GEN
Solar/Wind Harmer
6.163
970119AG2-088 GEN
50/50
9.961
970221AG2-151 GEN
Solar/Wind Harmer
19.574
3146776BUCKING
Solar/Wind Harmer
0.314
270494AE1-108_GEN
Solar/Wind Harmer
0
963171AG1-166 GEN
Solar/Wind Harmer
1.895
970535AG2-341 GEN
50/50
4.269
3146776BUCKING
Solar/Wind Harmer
0.349
3143336POWHATN
Solar/Wind Harmer
2.224
3143336POWHATN
Solar/Wind Harmer
1.89
971193AH1-056 GEN
Solar/Wind Harmer
10.075
970683AG2-441 GEN
Solar/Wind Harmer
10.771
315760AF1-028 GEN
50/50
Charging
15.678
970117AG2-086 GEN
50/50
Charging
1.272
971377AH1-170 GEN
Solar/Wind Harmer
3.915
963181AG1-167 GEN
Solar/Wind Harmer
1.421
970257AG2-171 GEN
Solar/Wind Harmer
0.152
970413AG2-270 GEN
50/50
11.154
316322AB2-045
Solar/Wind Harmer
0.025
972003AH1-546 GEN
Solar/Wind Harmer
16.919
3147623JAMES R
Solar/Wind Harmer
0.51
971447AH1-217 GEN
Solar/Wind Harmer
10.18
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
971489AH1-241 GEN
Solar/Wind Harmer
19.574
315657AE1-056 GEN
Solar/Wind Harmer
6.045
972205AH1-687 GEN
50/50
19.383
971563AH1-280 GEN
Solar/Wind Harmer
1.895
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.46
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.628
MECLTFEXP_MEC->PJM
CLTF
1.224
SIGELTFEXP_SIGE->PJM
CLTF
0.038
CPLELTFEXP_CPLE->PJM
CLTF
3.191
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.642
LAGNLTFEXP_LAGN->PJM
CLTF
2.588
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.28
TVALTFEXP_TVA->PJM
CLTF
1.354
NYPJM->LTFIMP_NY
CLTF
0.753
LGEELTFEXP_LGEE->PJM
CLTF
0.45
WECLTFEXP_WEC->PJM
CLTF
0.221
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.284

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.16 %
Rating:808.4 MVA
Rating Type:B
MVA to Mitigate:1003.7
MW Contribution:5.18
Bus #Bus NameTypeMW Contribution
941591AE2-156 GEN
50/50
5.412
3146926FARMVIL
Solar/Wind Harmer
0.45
3146926FARMVIL
Solar/Wind Harmer
0.45
970685AG2-442 GEN
Solar/Wind Harmer
13.686
966001AG1-469 GEN
Solar/Wind Helper
0.334
315616AA1-038_C
Solar/Wind Helper
1.051
970531AG2-338 GEN
50/50
2.734
3146776BUCKING
Solar/Wind Harmer
3.757
3146776BUCKING
Solar/Wind Harmer
0.304
946301AF1-294 GEN
Solar/Wind Harmer
4.371
971741AH1-377 GEN
Solar/Wind Harmer
19.305
972185AH1-677 GEN
50/50
4.638
944641AF1-129 GEN
50/50
25.205
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
5.934
963191AG1-168 GEN
Solar/Wind Harmer
1.599
970681AG2-440 GEN
Solar/Wind Harmer
9.775
316303AF2-085
50/50
2.018
3147043LAWRENC
50/50
0.919
3147133PAMPLIN
Solar/Wind Harmer
0.451
961791AG1-021 GEN
Solar/Wind Harmer
2.132
316192AB2-158 GEN
Solar/Wind Helper
1.482
970285AG2-188 GEN
Solar/Wind Harmer
24.994
3147133PAMPLIN
Solar/Wind Harmer
0.564
958211AF2-115 GEN
Solar/Wind Harmer
2.665
959311AF2-222 GEN
Solar/Wind Harmer
15.206
966251AG1-494 GEN
50/50
3.128
970937AG2-583 GEN
Solar/Wind Harmer
22.319
971845AH1-439 GEN
Solar/Wind Harmer
15.695
3147133PAMPLIN
Solar/Wind Harmer
1.771
316499AE2-029_GEN
Solar/Wind Helper
0.927
970301AG2-198 GEN
Solar/Wind Harmer
9.178
970323AG2-213 GEN
Solar/Wind Harmer
7.068
970119AG2-088 GEN
50/50
15.136
970221AG2-151 GEN
Solar/Wind Harmer
20.807
3146776BUCKING
Solar/Wind Harmer
0.338
270494AE1-108_GEN
Solar/Wind Harmer
0
963171AG1-166 GEN
Solar/Wind Harmer
2.132
970535AG2-341 GEN
50/50
5.181
972187AH1-678 GEN
50/50
2.367
315779AE2-040
50/50
0.984
3146776BUCKING
Solar/Wind Harmer
0.376
3143336POWHATN
Solar/Wind Harmer
2.572
3143336POWHATN
Solar/Wind Harmer
2.186
971193AH1-056 GEN
Solar/Wind Harmer
11.279
970683AG2-441 GEN
Solar/Wind Harmer
12.219
315760AF1-028 GEN
50/50
Charging
11.333
971377AH1-170 GEN
Solar/Wind Harmer
4.161
963181AG1-167 GEN
Solar/Wind Harmer
1.599
970257AG2-171 GEN
Solar/Wind Harmer
0.174
970413AG2-270 GEN
50/50
14.358
316322AB2-045
Solar/Wind Harmer
0.027
972003AH1-546 GEN
Solar/Wind Harmer
17.998
3147623JAMES R
Solar/Wind Harmer
0.542
971447AH1-217 GEN
Solar/Wind Harmer
10.898
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
971489AH1-241 GEN
Solar/Wind Harmer
20.807
315657AE1-056 GEN
Solar/Wind Harmer
6.767
963041AG1-153 GEN
50/50
5.221
972205AH1-687 GEN
50/50
20.575
970533AG2-339 GEN
50/50
6.834
971563AH1-280 GEN
Solar/Wind Harmer
2.132
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.656
MECLTFEXP_MEC->PJM
CLTF
0.289
SIGELTFEXP_SIGE->PJM
CLTF
0.006
CPLELTFEXP_CPLE->PJM
CLTF
3.782
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.617
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
1.646
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.434
TVALTFEXP_TVA->PJM
CLTF
0.852
NYPJM->LTFIMP_NY
CLTF
0.718
LGEELTFEXP_LGEE->PJM
CLTF
0.016
WECLTFEXP_WEC->PJM
CLTF
0.003
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.463

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.74 %
Rating:808.4 MVA
Rating Type:B
MVA to Mitigate:967.95
MW Contribution:4.27
Bus #Bus NameTypeMW Contribution
3146926FARMVIL
Solar/Wind Harmer
0.41
3146926FARMVIL
Solar/Wind Harmer
0.41
970685AG2-442 GEN
Solar/Wind Harmer
12.063
966001AG1-469 GEN
Solar/Wind Helper
0.358
315616AA1-038_C
Solar/Wind Helper
1.725
3146776BUCKING
Solar/Wind Harmer
3.491
3146776BUCKING
Solar/Wind Harmer
0.283
946301AF1-294 GEN
Solar/Wind Harmer
3.885
971741AH1-377 GEN
Solar/Wind Harmer
16.848
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
5.252
963191AG1-168 GEN
Solar/Wind Harmer
1.421
970681AG2-440 GEN
Solar/Wind Harmer
8.617
316303AF2-085
50/50
1.328
3147043LAWRENC
50/50
0.699
3147133PAMPLIN
Solar/Wind Harmer
0.403
961791AG1-021 GEN
Solar/Wind Harmer
1.895
316192AB2-158 GEN
Solar/Wind Helper
1.52
970285AG2-188 GEN
Solar/Wind Harmer
23.134
3147133PAMPLIN
Solar/Wind Harmer
0.504
958211AF2-115 GEN
Solar/Wind Harmer
2.369
959311AF2-222 GEN
Solar/Wind Harmer
13.304
966251AG1-494 GEN
50/50
3.897
970937AG2-583 GEN
Solar/Wind Harmer
20.592
971845AH1-439 GEN
Solar/Wind Harmer
14.563
3147133PAMPLIN
Solar/Wind Harmer
1.582
316499AE2-029_GEN
Solar/Wind Helper
1.242
970301AG2-198 GEN
Solar/Wind Harmer
8.122
970323AG2-213 GEN
Solar/Wind Harmer
6.163
970119AG2-088 GEN
50/50
9.961
970221AG2-151 GEN
Solar/Wind Harmer
19.574
3146776BUCKING
Solar/Wind Harmer
0.314
270494AE1-108_GEN
Solar/Wind Harmer
0
963171AG1-166 GEN
Solar/Wind Harmer
1.895
970535AG2-341 GEN
50/50
4.269
3146776BUCKING
Solar/Wind Harmer
0.349
3143336POWHATN
Solar/Wind Harmer
2.224
3143336POWHATN
Solar/Wind Harmer
1.89
971193AH1-056 GEN
Solar/Wind Harmer
10.075
970683AG2-441 GEN
Solar/Wind Harmer
10.771
315760AF1-028 GEN
50/50
Charging
15.678
970117AG2-086 GEN
50/50
Charging
1.272
971377AH1-170 GEN
Solar/Wind Harmer
3.915
963181AG1-167 GEN
Solar/Wind Harmer
1.421
970257AG2-171 GEN
Solar/Wind Harmer
0.152
970413AG2-270 GEN
50/50
11.154
316322AB2-045
Solar/Wind Harmer
0.025
972003AH1-546 GEN
Solar/Wind Harmer
16.919
3147623JAMES R
Solar/Wind Harmer
0.51
971447AH1-217 GEN
Solar/Wind Harmer
10.18
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
971489AH1-241 GEN
Solar/Wind Harmer
19.574
315657AE1-056 GEN
Solar/Wind Harmer
6.045
972205AH1-687 GEN
50/50
19.383
971563AH1-280 GEN
Solar/Wind Harmer
1.895
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.46
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.628
MECLTFEXP_MEC->PJM
CLTF
1.224
SIGELTFEXP_SIGE->PJM
CLTF
0.038
CPLELTFEXP_CPLE->PJM
CLTF
3.191
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.642
LAGNLTFEXP_LAGN->PJM
CLTF
2.588
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.28
TVALTFEXP_TVA->PJM
CLTF
1.354
NYPJM->LTFIMP_NY
CLTF
0.753
LGEELTFEXP_LGEE->PJM
CLTF
0.45
WECLTFEXP_WEC->PJM
CLTF
0.221
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
10.284

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 509T570_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.87 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:594.42
MW Contribution:6.53
Bus #Bus NameTypeMW Contribution
3145543BTLEBRO
Solar/Wind Harmer
0.188
970087AG2-069 GEN
Solar/Wind Harmer
13.39
970223AG2-152 GEN
Solar/Wind Harmer
8.162
971981AH1-535 GEN
Solar/Wind Harmer
2.856
3145493TOT1
Solar/Wind Harmer
0.087
315785AD2-033 C
Solar/Wind Helper
4.938
316381AD1-082 GEN
Solar/Wind Helper
1.054
316033AB2-134 GEN
Solar/Wind Helper
2.184
316369SG1_INVT
Solar/Wind Helper
1.502
316458AB2-190 GEN2
Solar/Wind Helper
1.145
319010AE1-072 C
Solar/Wind Helper
2.194
316280AD1-041 GEN
Solar/Wind Helper
0.717
970865AG2-541 GEN
50/50
Charging
16.223
316248AF1-058 C
Solar/Wind Helper
1.76
316123AC1-075 GEN
Solar/Wind Helper
4.3
316129AC1-054 GEN
Solar/Wind Helper
1.347
316441AF1-014 GEN
Solar/Wind Helper
0.285
316314AB2-024 C
Solar/Wind Helper
0.285
971443AH1-215 GEN
50/50
Charging
2.844
970535AG2-341 GEN
50/50
Charging
6.525
3145543BTLEBRO
Solar/Wind Harmer
0.188
3145543BTLEBRO
Solar/Wind Harmer
0.188
3145543BTLEBRO
Solar/Wind Harmer
0.151
961671AG1-007 GEN
Solar/Wind Harmer
0.313
3145453TOT5
Solar/Wind Harmer
0.052
957601AF2-054 GEN
Solar/Wind Helper
0.286
316484AD2-074 GEN
Solar/Wind Helper
1.103
3146233WITAKRS
Solar/Wind Harmer
0.595
316405AF2-144 C
Solar/Wind Helper
0.205
316236AE1-162_GEN
Solar/Wind Helper
0.315
316339AD2-160 GEN
Solar/Wind Helper
0.754
316246AF1-032 C
Solar/Wind Helper
0.219
315662AE1-191 GEN
Solar/Wind Helper
1.147
316404AE1-155 C
Solar/Wind Helper
1.741
970413AG2-270 GEN
50/50
Charging
34.023
316034AC1-036 C
Solar/Wind Helper
0.557
316322AB2-045
Solar/Wind Helper
0.501
316258AE1-075 C
Solar/Wind Helper
0.293
970919AG2-571 GEN
Solar/Wind Harmer
15.391
961601AG1-000A GEN
Solar/Wind Harmer
2.81
961601AG1-000A GEN
Solar/Wind Harmer
3.875
316118AC1-105 GEN
Solar/Wind Helper
4.018
315666AE1-190 GEN
Solar/Wind Helper
0.287
3146083TARBORO
Solar/Wind Harmer
0.166
3138543CONSLDL
Solar/Wind Harmer
0.102
316222AC1-221 GEN
Solar/Wind Helper
13.996
316486AD2-202 GEN
Solar/Wind Helper
1.16
316131AB2-060 GEN
Solar/Wind Helper
3.454
316294AC1-161 GEN
Solar/Wind Helper
4.209
316349AD2-085 GEN
Solar/Wind Helper
0.696
316487AF1-042 GEN
Solar/Wind Helper
0.577
971629AH1-314 GEN
50/50
15.462
943811AF1-049 GEN
Solar/Wind Harmer
0
3146073TAR RVR
Solar/Wind Harmer
0.166
316003AC1-222 GEN
Solar/Wind Helper
5.211
316336AC2-165 C
Solar/Wind Helper
1.653
316375AC2-012 GEN
Solar/Wind Helper
1.755
316263AC1-034 GEN
Solar/Wind Harmer
2.844
3145573BETHELC
Solar/Wind Harmer
0.166
3145603CNETO
Solar/Wind Harmer
0.035
316237AB2-079_GEN
Solar/Wind Helper
0.88
316238AB2-078_GEN
Solar/Wind Helper
0.88
316239AB2-077_GEN
Solar/Wind Helper
0.88
315839AE2-212 C
Solar/Wind Helper
0.324
316316AC1-027 C
Solar/Wind Helper
0.259
316185AD1-033 GEN
Solar/Wind Helper
1.106
315697AD1-025 GEN
Solar/Wind Helper
2.301
315833AF1-017_GEN
Solar/Wind Helper
0.589
964211AG1-282 GEN
Solar/Wind Helper
0.27
970085AG2-068 GEN
Solar/Wind Harmer
8.927
316036AC1-147 C
Solar/Wind Helper
0.321
3142956BIRDNECK
Solar/Wind Helper
0.29
316132AB2-190 GEN1
Solar/Wind Helper
1.145
316018AA1-139 ULT2
Solar/Wind Helper
0.898
316233AE1-074 FULL
Solar/Wind Helper
0.298
315773AC2-141 GEN
Solar/Wind Helper
3.897
316313AB2-026
Solar/Wind Helper
0.326
316240AF1-291 C
Solar/Wind Helper
0.313
316305AF2-043 C
Solar/Wind Helper
0.292
316156AD2-030 GEN
Solar/Wind Helper
0.284
316203AE2-005 GEN
Solar/Wind Helper
1.863
970909AG2-566 GEN
50/50
Charging
4.285
3145573BETHELC
Solar/Wind Harmer
0.166
315687AD1-152 GEN
Solar/Wind Helper
6.825
942461AE2-259 GEN
Solar/Wind Helper
3.485
957831AF2-077 GEN
Solar/Wind Helper
0.299
316072AD1-144
Solar/Wind Helper
0.222
316315AB2-025 C
Solar/Wind Helper
0.294
316075AC2-137 C
Solar/Wind Helper
0.279
270030AE2-140 GEN
Solar/Wind Harmer
10.168
316283AC2-100 C
Solar/Wind Helper
13.179
316083AB2-161 GEN
Solar/Wind Helper
0.201
316017AA1-139 ULT1
Solar/Wind Helper
0.898
316059AD1-063 C
Solar/Wind Helper
0.214
961951AG1-038 GEN
Solar/Wind Helper
0.624
316359AB2-059 GEN
Solar/Wind Harmer
0
3142053HEARTS
Solar/Wind Harmer
0.075
971367AH1-164 GEN
Solar/Wind Harmer
1.119
3146083TARBORO
Solar/Wind Harmer
0.166
316478AD1-087 GEN
Solar/Wind Helper
3.961
3145493TOT1
Solar/Wind Harmer
0.166
3146233WITAKRS
Solar/Wind Harmer
0.102
316382AG1-145 C
Solar/Wind Helper
0.302
970581AG2-369 GEN
Solar/Wind Harmer
7.677
970917AG2-570 GEN
Solar/Wind Harmer
35.706
971981AH1-535 GEN
Solar/Wind Harmer
3.116
3146233WITAKRS
Solar/Wind Harmer
0.359
313527AB2-043 GEN
Solar/Wind Helper
2.164
316159AE1-175 C
Solar/Wind Helper
0.301
316388AE2-253 GEN
Solar/Wind Helper
0.754
957141AF2-008_MTX
Adder
14.034
944201AF1-088_MTX
Adder
35.322
900033ID_568986
External Queue
3.5454747676849365
CBM West 1LTFEXP_CBM-W1->PJM
CBM
43.161
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.69
MECLTFEXP_MEC->PJM
CLTF
5.904
SIGELTFEXP_SIGE->PJM
CLTF
0.178
CPLELTFEXP_CPLE->PJM
CLTF
12.214
CBM West 2LTFEXP_CBM-W2->PJM
CBM
58.725
LAGNLTFEXP_LAGN->PJM
CLTF
10.551
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.334
TVALTFEXP_TVA->PJM
CLTF
5.364
NYPJM->LTFIMP_NY
CLTF
0.559
LGEELTFEXP_LGEE->PJM
CLTF
2.162
WECLTFEXP_WEC->PJM
CLTF
1.175
AG2-052LTFEXP_AG2-052->PJM
LTF
0.066
AH1-155LTFEXP_AH1-155->PJM
LTF
0.099
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
28.118

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-3


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.15 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:600.82
MW Contribution:6.45
Bus #Bus NameTypeMW Contribution
970417AG2-272 GEN
50/50
Charging
5.345
941591AE2-156 GEN
50/50
5.817
957481AF2-042 GEN
Solar/Wind Harmer
52.946
971775AH1-396 GEN
Solar/Wind Harmer
1.034
270018AE2-047 C O1
Solar/Wind Helper
1.413
316049AB1-081 GEN
Solar/Wind Helper
1.444
970685AG2-442 GEN
Solar/Wind Harmer
6.971
970919AG2-571 GEN
50/50
Charging
15.537
970531AG2-338 GEN
50/50
3.538
961601AG1-000A GEN
50/50
Charging
5.465
315693AD1-088 GEN
Solar/Wind Harmer
8.041
971741AH1-377 GEN
Solar/Wind Harmer
16.042
3144303KENBRDG
Solar/Wind Harmer
0.345
972185AH1-677 GEN
50/50
6.349
944641AF1-129 GEN
50/50
8.974
960061AF2-297 GEN
Solar/Wind Harmer
15.055
970401AG2-262 GEN
Solar/Wind Harmer
1.628
970099AG2-077 GEN
Solar/Wind Harmer
21.178
964241AG1-285 GEN
Solar/Wind Harmer
11.266
971629AH1-314 GEN
50/50
Charging
15.608
3147043LAWRENC
50/50
0.859
943811AF1-049 GEN
Solar/Wind Helper
3.28
316319Z2-044 C
Solar/Wind Helper
0.172
3146843MT LREL
Solar/Wind Harmer
0.742
3146843MT LREL
Solar/Wind Harmer
0.742
959311AF2-222 GEN
Solar/Wind Harmer
14.262
270197AD1-017 GEN1
Solar/Wind Helper
1.326
270574AD1-017 GEN2
Solar/Wind Helper
1.193
316420AA1-050 GEN
Solar/Wind Helper
1.199
3147173SINAI
Solar/Wind Harmer
0.941
3147243WELCO
Solar/Wind Harmer
0.588
970165AG2-112 GEN
Solar/Wind Harmer
1.742
270455AD2-022 GEN
Solar/Wind Helper
4.93
270336AE1-100 GEN
Solar/Wind Helper
1.52
316359AB2-059 GEN
Solar/Wind Helper
1.805
315785AD2-033 C
Solar/Wind Harmer
0.001
970323AG2-213 GEN
Solar/Wind Harmer
6.896
962491AG1-098 GEN
Solar/Wind Harmer
10.652
970535AG2-341 GEN
50/50
6.451
972187AH1-678 GEN
50/50
3.316
964791AG1-342 GEN
Solar/Wind Harmer
5.329
270457AD2-023 GEN
Solar/Wind Helper
2.773
962561AG1-105 GEN
Solar/Wind Harmer
12.558
972263AH1-716 GEN
50/50
38.484
970257AG2-171 GEN
Solar/Wind Harmer
5.172
270069AE2-166 C O1
Solar/Wind Helper
1.986
970413AG2-270 GEN
50/50
33.803
971683AH1-343 GEN
Solar/Wind Harmer
10.923
270013AE1-250 PV
Solar/Wind Helper
2.088
270016AE1-250 BESS
Solar/Wind Helper
2.088
3150921YORKTN3
50/50
1.678
942751AE2-291 GEN
Solar/Wind Harmer
9.796
316494AC1-189 GEN
Solar/Wind Helper
1.105
963041AG1-153 GEN
50/50
7.315
970163AG2-111 GEN
Solar/Wind Harmer
1.662
970533AG2-339 GEN
50/50
8.846
972205AH1-687 GEN
50/50
3.283
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.892
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
11.676
G-007ALTFEXP_G-007A->PJM
CMTX
2.959
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.232
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.063
BlueGrassPJM->LTFIMP_BlueG
CLTF
6.491
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
7.441
VFTLTFEXP_VFT->PJM
CMTX
7.862

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-1


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.23 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:585.98
MW Contribution:6.45
Bus #Bus NameTypeMW Contribution
970417AG2-272 GEN
50/50
Charging
5.345
941591AE2-156 GEN
50/50
5.817
957481AF2-042 GEN
Solar/Wind Harmer
52.946
971775AH1-396 GEN
Solar/Wind Harmer
1.034
270018AE2-047 C O1
Solar/Wind Helper
1.413
316049AB1-081 GEN
Solar/Wind Helper
1.444
970685AG2-442 GEN
Solar/Wind Harmer
6.971
970531AG2-338 GEN
50/50
3.538
961601AG1-000A GEN
50/50
Charging
5.465
315693AD1-088 GEN
Solar/Wind Harmer
8.041
971741AH1-377 GEN
Solar/Wind Harmer
16.042
3144303KENBRDG
Solar/Wind Harmer
0.345
971629AH1-314 GEN
50/50
Charging
15.608
3147043LAWRENC
50/50
0.859
943811AF1-049 GEN
Solar/Wind Helper
3.28
316319Z2-044 C
Solar/Wind Helper
0.172
3146843MT LREL
Solar/Wind Harmer
0.742
3146843MT LREL
Solar/Wind Harmer
0.742
959311AF2-222 GEN
Solar/Wind Harmer
14.262
270197AD1-017 GEN1
Solar/Wind Helper
1.326
270574AD1-017 GEN2
Solar/Wind Helper
1.193
316420AA1-050 GEN
Solar/Wind Helper
1.199
315785AD2-033 C
Solar/Wind Harmer
0.001
970323AG2-213 GEN
Solar/Wind Harmer
6.896
962491AG1-098 GEN
Solar/Wind Harmer
10.652
972185AH1-677 GEN
50/50
6.349
944641AF1-129 GEN
50/50
3.386
960061AF2-297 GEN
Solar/Wind Harmer
15.055
970401AG2-262 GEN
Solar/Wind Harmer
1.628
970099AG2-077 GEN
Solar/Wind Harmer
21.178
964241AG1-285 GEN
Solar/Wind Harmer
11.266
962561AG1-105 GEN
Solar/Wind Harmer
12.558
970413AG2-270 GEN
50/50
33.803
971683AH1-343 GEN
Solar/Wind Harmer
10.923
270013AE1-250 PV
Solar/Wind Helper
2.088
270016AE1-250 BESS
Solar/Wind Helper
2.088
970535AG2-341 GEN
50/50
6.451
972187AH1-678 GEN
50/50
3.316
964791AG1-342 GEN
Solar/Wind Harmer
5.329
270457AD2-023 GEN
Solar/Wind Helper
2.773
972263AH1-716 GEN
50/50
38.484
970257AG2-171 GEN
Solar/Wind Harmer
5.172
270069AE2-166 C O1
Solar/Wind Helper
1.986
3150921YORKTN3
50/50
1.678
942751AE2-291 GEN
Solar/Wind Harmer
9.796
316494AC1-189 GEN
Solar/Wind Helper
1.105
3147173SINAI
Solar/Wind Harmer
0.941
3147243WELCO
Solar/Wind Harmer
0.588
970165AG2-112 GEN
Solar/Wind Harmer
1.742
270455AD2-022 GEN
Solar/Wind Helper
4.93
270336AE1-100 GEN
Solar/Wind Helper
1.52
316359AB2-059 GEN
Solar/Wind Helper
1.805
963041AG1-153 GEN
50/50
7.315
970163AG2-111 GEN
Solar/Wind Harmer
1.662
970533AG2-339 GEN
50/50
8.846
972205AH1-687 GEN
50/50
3.283
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.892
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
11.676
G-007ALTFEXP_G-007A->PJM
CMTX
2.959
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.232
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
2.063
BlueGrassPJM->LTFIMP_BlueG
CLTF
6.491
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
7.441
VFTLTFEXP_VFT->PJM
CMTX
7.862

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X1_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.28 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:585.78
MW Contribution:12.86
Bus #Bus NameTypeMW Contribution
970301AG2-198 GEN
Solar/Wind Harmer
14.117
315785AD2-033 C
Solar/Wind Harmer
0.001
970323AG2-213 GEN
Solar/Wind Harmer
12.766
962561AG1-105 GEN
Solar/Wind Harmer
19.777
970865AG2-541 GEN
Solar/Wind Harmer
15.351
970535AG2-341 GEN
50/50
12.863
964791AG1-342 GEN
Solar/Wind Harmer
8.253
971443AH1-215 GEN
Solar/Wind Harmer
4.414
270457AD2-023 GEN
Solar/Wind Helper
1.534
970257AG2-171 GEN
Solar/Wind Harmer
9.575
970413AG2-270 GEN
50/50
68.067
971683AH1-343 GEN
Solar/Wind Harmer
16.229
970865AG2-541 GEN
Solar/Wind Harmer
8.904
315693AD1-088 GEN
Solar/Wind Harmer
18.274
971741AH1-377 GEN
Solar/Wind Harmer
35.039
3144303KENBRDG
Solar/Wind Harmer
0.638
970163AG2-111 GEN
Solar/Wind Harmer
2.584
3147043LAWRENC
50/50
1.436
962491AG1-098 GEN
Solar/Wind Harmer
24.154
971443AH1-215 GEN
Solar/Wind Harmer
4.267
960061AF2-297 GEN
Solar/Wind Harmer
21.933
970099AG2-077 GEN
Solar/Wind Harmer
50.807
970401AG2-262 GEN
Solar/Wind Harmer
2.522
970909AG2-566 GEN
Solar/Wind Harmer
9.127
964241AG1-285 GEN
Solar/Wind Harmer
20.536
3146843MT LREL
Solar/Wind Harmer
1.148
3146843MT LREL
Solar/Wind Harmer
1.148
959311AF2-222 GEN
Solar/Wind Harmer
8.633
3147173SINAI
Solar/Wind Harmer
1.371
3147243WELCO
Solar/Wind Harmer
0.857
970165AG2-112 GEN
Solar/Wind Harmer
2.709
270455AD2-022 GEN
Solar/Wind Helper
2.726
957481AF2-042 GEN
Solar/Wind Harmer
127.018
971775AH1-396 GEN
Solar/Wind Harmer
1.915
972205AH1-687 GEN
50/50
5.169
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.788
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.864
G-007ALTFEXP_G-007A->PJM
CMTX
0.476
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.442
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.83
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.615
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.337
VFTLTFEXP_VFT->PJM
CMTX
1.251

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-5: 593X2_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: 593X2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.27 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:585.75
MW Contribution:12.86
Bus #Bus NameTypeMW Contribution
970301AG2-198 GEN
Solar/Wind Harmer
14.118
315785AD2-033 C
Solar/Wind Harmer
0.001
970323AG2-213 GEN
Solar/Wind Harmer
12.767
962561AG1-105 GEN
Solar/Wind Harmer
19.776
970865AG2-541 GEN
Solar/Wind Harmer
15.351
970535AG2-341 GEN
50/50
12.863
964791AG1-342 GEN
Solar/Wind Harmer
8.253
971443AH1-215 GEN
Solar/Wind Harmer
4.414
270457AD2-023 GEN
Solar/Wind Helper
1.534
970257AG2-171 GEN
Solar/Wind Harmer
9.575
970413AG2-270 GEN
50/50
68.062
971683AH1-343 GEN
Solar/Wind Harmer
16.228
970865AG2-541 GEN
Solar/Wind Harmer
8.903
315693AD1-088 GEN
Solar/Wind Harmer
18.276
971741AH1-377 GEN
Solar/Wind Harmer
35.043
3144303KENBRDG
Solar/Wind Harmer
0.638
970163AG2-111 GEN
Solar/Wind Harmer
2.584
3147043LAWRENC
50/50
1.436
962491AG1-098 GEN
Solar/Wind Harmer
24.157
971443AH1-215 GEN
Solar/Wind Harmer
4.267
960061AF2-297 GEN
Solar/Wind Harmer
21.932
970099AG2-077 GEN
Solar/Wind Harmer
50.8
970401AG2-262 GEN
Solar/Wind Harmer
2.522
970909AG2-566 GEN
Solar/Wind Harmer
9.128
964241AG1-285 GEN
Solar/Wind Harmer
20.537
3146843MT LREL
Solar/Wind Harmer
1.148
3146843MT LREL
Solar/Wind Harmer
1.148
959311AF2-222 GEN
Solar/Wind Harmer
8.633
3147173SINAI
Solar/Wind Harmer
1.371
3147243WELCO
Solar/Wind Harmer
0.857
970165AG2-112 GEN
Solar/Wind Harmer
2.709
270455AD2-022 GEN
Solar/Wind Helper
2.726
957481AF2-042 GEN
Solar/Wind Harmer
127.001
971775AH1-396 GEN
Solar/Wind Harmer
1.915
972205AH1-687 GEN
50/50
5.17
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.788
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.864
G-007ALTFEXP_G-007A->PJM
CMTX
0.476
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.442
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.83
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.615
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.337
VFTLTFEXP_VFT->PJM
CMTX
1.252

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T593_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.54 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:581.78
MW Contribution:12.89
Bus #Bus NameTypeMW Contribution
970301AG2-198 GEN
Solar/Wind Harmer
14.316
315785AD2-033 C
Solar/Wind Harmer
0.001
970323AG2-213 GEN
Solar/Wind Harmer
12.821
962561AG1-105 GEN
Solar/Wind Harmer
19.746
970535AG2-341 GEN
50/50
12.889
964791AG1-342 GEN
Solar/Wind Harmer
8.237
970413AG2-270 GEN
50/50
67.43
971683AH1-343 GEN
Solar/Wind Harmer
16.168
970865AG2-541 GEN
Solar/Wind Harmer
8.87
970865AG2-541 GEN
Solar/Wind Harmer
15.293
315693AD1-088 GEN
Solar/Wind Harmer
18.549
971741AH1-377 GEN
Solar/Wind Harmer
35.543
3144303KENBRDG
Solar/Wind Harmer
0.641
971443AH1-215 GEN
Solar/Wind Harmer
4.432
270457AD2-023 GEN
Solar/Wind Helper
1.544
970163AG2-111 GEN
Solar/Wind Harmer
2.574
3147043LAWRENC
50/50
1.438
962491AG1-098 GEN
Solar/Wind Harmer
24.516
971443AH1-215 GEN
Solar/Wind Harmer
4.285
960061AF2-297 GEN
Solar/Wind Harmer
21.853
970099AG2-077 GEN
Solar/Wind Harmer
49.882
970401AG2-262 GEN
Solar/Wind Harmer
2.517
970909AG2-566 GEN
Solar/Wind Harmer
9.256
964241AG1-285 GEN
Solar/Wind Harmer
20.591
3146843MT LREL
Solar/Wind Harmer
1.146
3146843MT LREL
Solar/Wind Harmer
1.146
959311AF2-222 GEN
Solar/Wind Harmer
8.672
3147173SINAI
Solar/Wind Harmer
1.366
3147243WELCO
Solar/Wind Harmer
0.854
970165AG2-112 GEN
Solar/Wind Harmer
2.698
270455AD2-022 GEN
Solar/Wind Helper
2.745
957481AF2-042 GEN
Solar/Wind Harmer
124.704
971775AH1-396 GEN
Solar/Wind Harmer
1.923
970257AG2-171 GEN
Solar/Wind Harmer
9.616
972205AH1-687 GEN
50/50
5.236
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.8
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.898
G-007ALTFEXP_G-007A->PJM
CMTX
0.492
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.469
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.836
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.634
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.36
VFTLTFEXP_VFT->PJM
CMTX
1.294

Details for AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T593_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
AC2-100 TAP-6PERSON230 T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T593_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.54 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:581.78
MW Contribution:12.89
Bus #Bus NameTypeMW Contribution
970301AG2-198 GEN
Solar/Wind Harmer
14.316
315785AD2-033 C
Solar/Wind Harmer
0.001
970413AG2-270 GEN
50/50
67.43
971683AH1-343 GEN
Solar/Wind Harmer
16.168
970865AG2-541 GEN
Solar/Wind Harmer
8.87
962561AG1-105 GEN
Solar/Wind Harmer
19.746
970865AG2-541 GEN
Solar/Wind Harmer
15.293
315693AD1-088 GEN
Solar/Wind Harmer
18.549
971741AH1-377 GEN
Solar/Wind Harmer
35.543
3144303KENBRDG
Solar/Wind Harmer
0.641
970535AG2-341 GEN
50/50
12.889
964791AG1-342 GEN
Solar/Wind Harmer
8.237
971443AH1-215 GEN
Solar/Wind Harmer
4.432
270457AD2-023 GEN
Solar/Wind Helper
1.544
970163AG2-111 GEN
Solar/Wind Harmer
2.574
3147043LAWRENC
50/50
1.438
962491AG1-098 GEN
Solar/Wind Harmer
24.516
971443AH1-215 GEN
Solar/Wind Harmer
4.285
960061AF2-297 GEN
Solar/Wind Harmer
21.853
970099AG2-077 GEN
Solar/Wind Harmer
49.882
970401AG2-262 GEN
Solar/Wind Harmer
2.517
970909AG2-566 GEN
Solar/Wind Harmer
9.256
964241AG1-285 GEN
Solar/Wind Harmer
20.591
3146843MT LREL
Solar/Wind Harmer
1.146
3146843MT LREL
Solar/Wind Harmer
1.146
959311AF2-222 GEN
Solar/Wind Harmer
8.672
3147173SINAI
Solar/Wind Harmer
1.366
3147243WELCO
Solar/Wind Harmer
0.854
970165AG2-112 GEN
Solar/Wind Harmer
2.698
270455AD2-022 GEN
Solar/Wind Helper
2.745
957481AF2-042 GEN
Solar/Wind Harmer
124.704
971775AH1-396 GEN
Solar/Wind Harmer
1.923
970257AG2-171 GEN
Solar/Wind Harmer
9.616
970323AG2-213 GEN
Solar/Wind Harmer
12.821
972205AH1-687 GEN
50/50
5.236
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.8
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
4.898
G-007ALTFEXP_G-007A->PJM
CMTX
0.492
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.469
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.836
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.634
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.36
VFTLTFEXP_VFT->PJM
CMTX
1.294

Details for AG1-098 TP-6FINNEYWOOD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 298_SRT-A-4


Base Case Flowgate

Area:DVP
Facility Description:
AG1-098 TP-6FINNEYWOOD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 298_SRT-A-4
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.34 %
Rating:698.42 MVA
Rating Type:B
MVA to Mitigate:721.77
MW Contribution:5.23
Bus #Bus NameTypeMW Contribution
962491AG1-098 GEN
Solar/Wind Harmer
59.489
3146776BUCKING
Solar/Wind Harmer
0.839
963171AG1-166 GEN
Solar/Wind Harmer
5.418
970301AG2-198 GEN
Solar/Wind Harmer
40.443
970323AG2-213 GEN
Solar/Wind Harmer
15.081
315785AD2-033 C
Solar/Wind Harmer
0.001
971193AH1-056 GEN
Solar/Wind Harmer
29.876
970683AG2-441 GEN
Solar/Wind Harmer
28.867
962561AG1-105 GEN
Solar/Wind Harmer
5.028
970535AG2-341 GEN
50/50
5.229
3146776BUCKING
Solar/Wind Harmer
0.933
964791AG1-342 GEN
Solar/Wind Harmer
1.338
963181AG1-167 GEN
Solar/Wind Harmer
4.063
970257AG2-171 GEN
Solar/Wind Harmer
11.311
316322AB2-045
Solar/Wind Harmer
0.068
971741AH1-377 GEN
Solar/Wind Harmer
96.3
3146776BUCKING
Solar/Wind Harmer
9.325
3146776BUCKING
Solar/Wind Harmer
0.755
946301AF1-294 GEN
Solar/Wind Harmer
11.107
3144303KENBRDG
Solar/Wind Harmer
0.754
971845AH1-439 GEN
Solar/Wind Harmer
39.632
3147133PAMPLIN
Solar/Wind Harmer
4.691
3147043LAWRENC
50/50
0.789
3147133PAMPLIN
Solar/Wind Harmer
1.195
961791AG1-021 GEN
Solar/Wind Harmer
5.418
970285AG2-188 GEN
Solar/Wind Harmer
65.277
3147133PAMPLIN
Solar/Wind Harmer
1.494
958211AF2-115 GEN
Solar/Wind Harmer
6.772
959311AF2-222 GEN
Solar/Wind Harmer
33.517
972003AH1-546 GEN
Solar/Wind Harmer
37.208
970909AG2-566 GEN
Solar/Wind Harmer
26.148
942461AE2-259 GEN
Solar/Wind Harmer
0.001
315657AE1-056 GEN
Solar/Wind Harmer
17.926
963191AG1-168 GEN
Solar/Wind Harmer
4.063
970681AG2-440 GEN
Solar/Wind Harmer
23.094
964241AG1-285 GEN
Solar/Wind Harmer
15.89
970401AG2-262 GEN
Solar/Wind Harmer
0.409
3146926FARMVIL
Solar/Wind Harmer
1.399
3146926FARMVIL
Solar/Wind Harmer
1.399
970685AG2-442 GEN
Solar/Wind Harmer
32.331
971775AH1-396 GEN
Solar/Wind Harmer
2.262
971563AH1-280 GEN
Solar/Wind Harmer
5.418
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.051
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.026
CPLELTFEXP_CPLE->PJM
CLTF
0.158
MDUPJM->LTFIMP_MDU
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.019
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.059
LAGNLTFEXP_LAGN->PJM
CLTF
0.023
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.277
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.015
NYPJM->LTFIMP_NY
CLTF
0.101
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.631

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.74 %
Rating:687.14 MVA
Rating Type:B
MVA to Mitigate:781.56
MW Contribution:7.81
Bus #Bus NameTypeMW Contribution
970531AG2-338 GEN
50/50
2.701
946301AF1-294 GEN
Solar/Wind Harmer
7.646
971741AH1-377 GEN
Solar/Wind Harmer
33.284
315693AD1-088 GEN
Solar/Wind Harmer
8.135
3146776BUCKING
Solar/Wind Harmer
-1.201
3147043LAWRENC
50/50
1.217
961791AG1-021 GEN
Solar/Wind Harmer
3.73
316336AC2-165 C
Solar/Wind Helper
3.441
3147133PAMPLIN
Solar/Wind Harmer
0.213
3138266HYDRAULIC
Solar/Wind Harmer
-0.002
3145683EARLEYS
Solar/Wind Harmer
0.046
3146073TAR RVR
Solar/Wind Harmer
0.045
3146206CASHIE
Solar/Wind Harmer
0.041
3146206CASHIE
Solar/Wind Harmer
0.041
3146376EDENTON
Solar/Wind Harmer
0.037
3146456SLIGO L269
Solar/Wind Harmer
0.135
3146456SLIGO L269
Solar/Wind Harmer
0.034
3145336SMITFLD
Solar/Wind Harmer
0.112
3147123OTTER R
Solar/Wind Harmer
0.015
3141766HARMONY
Solar/Wind Harmer
0.003
3142416OLDCHRC
Solar/Wind Harmer
0.008
970285AG2-188 GEN
Solar/Wind Harmer
47.032
958211AF2-115 GEN
Solar/Wind Harmer
4.662
959311AF2-222 GEN
Solar/Wind Harmer
25.776
3147133PAMPLIN
Solar/Wind Harmer
0.267
3146843MT LREL
Solar/Wind Harmer
0.109
3146843MT LREL
Solar/Wind Harmer
0.109
3145683EARLEYS
Solar/Wind Harmer
0.092
3145683EARLEYS
Solar/Wind Harmer
0.046
3145273HOLLAND
Solar/Wind Harmer
0.029
3145336SMITFLD
Solar/Wind Harmer
0.011
3141766HARMONY
Solar/Wind Harmer
0.038
3141783LANCAST
Solar/Wind Harmer
0.005
3142433PROV 92
Solar/Wind Harmer
0.044
970685AG2-442 GEN
Solar/Wind Harmer
23.547
971775AH1-396 GEN
Solar/Wind Harmer
1.785
3146926FARMVIL
Solar/Wind Harmer
0.221
3146926FARMVIL
Solar/Wind Harmer
0.221
3146033SCOT NK
Solar/Wind Harmer
0.196
3142666NORTHAMPTON
Solar/Wind Harmer
0.029
3146233WITAKRS
Solar/Wind Harmer
0.033
3145493TOT1
Solar/Wind Harmer
0.045
3148013FISHERV
Solar/Wind Harmer
-0.045
3145933PARMELE
Solar/Wind Harmer
0.043
3146626S HERTFORD
Solar/Wind Harmer
0.036
3146626S HERTFORD
Solar/Wind Harmer
0.036
3141873WAN 176
Solar/Wind Harmer
0.003
3143873LANEXA
Solar/Wind Harmer
0.007
3142543TWELFTH
Solar/Wind Harmer
0.001
970301AG2-198 GEN
Solar/Wind Harmer
16.156
970323AG2-213 GEN
Solar/Wind Harmer
11.901
315785AD2-033 C
Solar/Wind Harmer
0.001
3145593CAROLNA
Solar/Wind Harmer
0.06
3145593CAROLNA
Solar/Wind Harmer
0.06
3130156CHOWAN
Solar/Wind Harmer
0.037
3146486SUNBURY
Solar/Wind Harmer
0.035
3146486SUNBURY
Solar/Wind Harmer
0.035
3145506HICKORY
Solar/Wind Harmer
0.133
3145506HICKORY
Solar/Wind Harmer
0.08
3143316POE
Solar/Wind Harmer
0.114
3141873WAN 176
Solar/Wind Harmer
0.054
3141906WESTMOR
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
-0.097
3144303KENBRDG
Solar/Wind Harmer
0.159
3137643SOCKMAN
Solar/Wind Harmer
0.243
3145893MURPHYS
Solar/Wind Harmer
0.19
3145893MURPHYS
Solar/Wind Harmer
0.129
3145513AHOSKIE
Solar/Wind Harmer
0.046
3145513AHOSKIE
Solar/Wind Harmer
0.046
3145963POPLR C
Solar/Wind Harmer
0.042
3145963POPLR C
Solar/Wind Harmer
0.042
3146516WINFALL
Solar/Wind Harmer
0.115
963171AG1-166 GEN
Solar/Wind Harmer
3.73
962491AG1-098 GEN
Solar/Wind Harmer
11.436
270494AE1-108_GEN
Solar/Wind Helper
6.756
316313AB2-026
Solar/Wind Helper
0.583
3146776BUCKING
Solar/Wind Harmer
-0.108
3146263WOODLND
Solar/Wind Harmer
0.05
3145893MURPHYS
Solar/Wind Harmer
0.086
3145543BTLEBRO
Solar/Wind Harmer
0.047
3146516WINFALL
Solar/Wind Harmer
0.035
3146516WINFALL
Solar/Wind Harmer
0.035
3146406KITTY HAWK
Solar/Wind Harmer
0.001
3144536CHRHLND
Solar/Wind Harmer
0.005
972185AH1-677 GEN
50/50
4.797
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
10.446
963191AG1-168 GEN
Solar/Wind Harmer
2.797
970681AG2-440 GEN
Solar/Wind Harmer
16.82
964241AG1-285 GEN
Solar/Wind Harmer
15.081
970401AG2-262 GEN
Solar/Wind Harmer
0.897
3145783HORNRTN
Solar/Wind Harmer
0.234
3145783HORNRTN
Solar/Wind Harmer
0.059
3145796HORNRTN
Solar/Wind Harmer
0.049
3145573BETHELC
Solar/Wind Harmer
0.045
971193AH1-056 GEN
Solar/Wind Harmer
19.926
970683AG2-441 GEN
Solar/Wind Harmer
21.024
962561AG1-105 GEN
Solar/Wind Harmer
7.662
3143336POWHATN
Solar/Wind Harmer
-0.285
3145783HORNRTN
Solar/Wind Harmer
0.059
3145796HORNRTN
Solar/Wind Harmer
0.049
3145746EVERETS
Solar/Wind Harmer
0.043
970413AG2-270 GEN
50/50
20.349
316322AB2-045
Solar/Wind Helper
2.037
316258AE1-075 C
Solar/Wind Helper
0.525
3145796HORNRTN
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.173
3145746EVERETS
Solar/Wind Harmer
0.043
970535AG2-341 GEN
50/50
7.806
972187AH1-678 GEN
50/50
2.495
315779AE2-040
50/50
0.84
939181AE1-148 GEN
Solar/Wind Harmer
7.432
964791AG1-342 GEN
Solar/Wind Harmer
2.934
3146776BUCKING
Solar/Wind Harmer
-0.12
3145893MURPHYS
Solar/Wind Harmer
0.048
3145543BTLEBRO
Solar/Wind Harmer
0.047
3145543BTLEBRO
Solar/Wind Harmer
0.047
3145543BTLEBRO
Solar/Wind Harmer
0.038
3146516WINFALL
Solar/Wind Harmer
0.035
316405AF2-144 C
50/50
Charging
1.188
963181AG1-167 GEN
Solar/Wind Harmer
2.797
970257AG2-171 GEN
Solar/Wind Harmer
8.926
3145593CAROLNA
Solar/Wind Harmer
0.017
3142666NORTHAMPTON
Solar/Wind Harmer
0.049
3142666NORTHAMPTON
Solar/Wind Harmer
0.049
3146233WITAKRS
Solar/Wind Harmer
0.193
3148013FISHERV
Solar/Wind Harmer
-0.026
3130546PLYMOUTH
Solar/Wind Harmer
0.04
3130156CHOWAN
Solar/Wind Harmer
0.037
3146626S HERTFORD
Solar/Wind Harmer
0.036
3130086AYDLETT
Solar/Wind Harmer
0.136
3145506HICKORY
Solar/Wind Harmer
0.02
3144873MCLAUGH
Solar/Wind Harmer
0.001
3138133OCRAN
Solar/Wind Harmer
0.008
3145746EVERETS
Solar/Wind Harmer
0.043
3145746EVERETS
Solar/Wind Harmer
0.043
3145746EVERETS
Solar/Wind Harmer
0.043
3147312GRETNA
Solar/Wind Harmer
0.004
315657AE1-056 GEN
Solar/Wind Harmer
11.956
3146263WOODLND
Solar/Wind Harmer
0.05
3145893MURPHYS
Solar/Wind Harmer
0.048
3145893MURPHYS
Solar/Wind Harmer
0.048
3146516WINFALL
Solar/Wind Harmer
0.035
3146516WINFALL
Solar/Wind Harmer
0.035
3141726DUNNSVL
Solar/Wind Harmer
0.037
3141813NORNECK
Solar/Wind Harmer
0.009
3147133PAMPLIN
Solar/Wind Harmer
0.837
3147173SINAI
Solar/Wind Harmer
0.086
3147243WELCO
Solar/Wind Harmer
0.054
3146043SEABORD
Solar/Wind Harmer
0.055
3146173TUNIS
Solar/Wind Harmer
0.047
3145683EARLEYS
Solar/Wind Harmer
0.046
3146083TARBORO
Solar/Wind Harmer
0.045
3146206CASHIE
Solar/Wind Harmer
0.041
3145663CRESWEL
Solar/Wind Harmer
0.109
3146376EDENTON
Solar/Wind Harmer
0.037
3146386ELIZ CT
Solar/Wind Harmer
0.035
3146456SLIGO L269
Solar/Wind Harmer
0.034
3141783LANCAST
Solar/Wind Harmer
0.007
3142416OLDCHRC
Solar/Wind Harmer
0.003
963041AG1-153 GEN
50/50
5.503
3147043LAWRENC
Solar/Wind Harmer
0.052
3138266HYDRAULIC
Solar/Wind Harmer
-0.003
3138543CONSLDL
Solar/Wind Harmer
0.032
3146173TUNIS
Solar/Wind Harmer
0.047
3146173TUNIS
Solar/Wind Harmer
0.047
3146173TUNIS
Solar/Wind Harmer
0.047
3146083TARBORO
Solar/Wind Harmer
0.045
3146376EDENTON
Solar/Wind Harmer
0.037
3146396TANGLEW
Solar/Wind Harmer
0.022
3142946ENON
Solar/Wind Harmer
0.003
3142946ENON
Solar/Wind Harmer
0.001
315821AE2-092 GEN
Solar/Wind Helper
5.447
3145783HORNRTN
Solar/Wind Harmer
0.187
3145783HORNRTN
Solar/Wind Harmer
0.023
3145796HORNRTN
Solar/Wind Harmer
0.161
3145796HORNRTN
Solar/Wind Harmer
0.156
3145796HORNRTN
Solar/Wind Harmer
0.146
3145796HORNRTN
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.047
3145823KELFORD
Solar/Wind Harmer
0.047
3145573BETHELC
Solar/Wind Harmer
0.045
316316AC1-027 C
Solar/Wind Harmer
0
3146802CHATHAM
Solar/Wind Harmer
0.014
3141913WHIT STONE
Solar/Wind Harmer
0.013
3148133STUARTS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
0.043
3145746EVERETS
Solar/Wind Harmer
0.043
3144356SAPONY
Solar/Wind Harmer
0.166
3147312GRETNA
Solar/Wind Harmer
0.015
970533AG2-339 GEN
50/50
6.753
971563AH1-280 GEN
Solar/Wind Harmer
3.73
3142666NORTHAMPTON
Solar/Wind Harmer
0.049
3142666NORTHAMPTON
Solar/Wind Harmer
0.049
3146233WITAKRS
Solar/Wind Harmer
0.116
3145933PARMELE
Solar/Wind Harmer
0.086
3145933PARMELE
Solar/Wind Harmer
0.043
3130156CHOWAN
Solar/Wind Harmer
0.037
3145176PASQUOTANK
Solar/Wind Harmer
0.022
3137176SLIGO L2192
Solar/Wind Harmer
0.134
3138133OCRAN
Solar/Wind Harmer
0.004
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.808
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.196
MECLTFEXP_MEC->PJM
CLTF
0.917
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
4.467
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.926
LAGNLTFEXP_LAGN->PJM
CLTF
2.492
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.117
TVALTFEXP_TVA->PJM
CLTF
1.273
NYPJM->LTFIMP_NY
CLTF
0.562
LGEELTFEXP_LGEE->PJM
CLTF
0.263
WECLTFEXP_WEC->PJM
CLTF
0.142
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.052

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.28 %
Rating:687.14 MVA
Rating Type:B
MVA to Mitigate:764.64
MW Contribution:11.55
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
1.477
970285AG2-188 GEN
Solar/Wind Harmer
52.726
3147133PAMPLIN
Solar/Wind Harmer
1.237
958211AF2-115 GEN
Solar/Wind Harmer
5.856
963171AG1-166 GEN
Solar/Wind Harmer
4.685
962491AG1-098 GEN
Solar/Wind Harmer
20.906
270494AE1-108_GEN
Solar/Wind Helper
5.509
316313AB2-026
Solar/Wind Helper
0.503
970301AG2-198 GEN
Solar/Wind Harmer
21.548
970323AG2-213 GEN
Solar/Wind Harmer
15.612
315785AD2-033 C
Solar/Wind Harmer
0.001
971193AH1-056 GEN
Solar/Wind Harmer
24.746
970683AG2-441 GEN
Solar/Wind Harmer
26.91
970535AG2-341 GEN
50/50
11.549
971741AH1-377 GEN
Solar/Wind Harmer
46.769
946301AF1-294 GEN
Solar/Wind Harmer
9.604
3144303KENBRDG
Solar/Wind Harmer
0.781
315693AD1-088 GEN
Solar/Wind Harmer
15.308
316405AF2-144 C
50/50
Charging
1.025
963181AG1-167 GEN
Solar/Wind Harmer
3.514
970257AG2-171 GEN
Solar/Wind Harmer
11.709
3146926FARMVIL
Solar/Wind Harmer
0.981
3146926FARMVIL
Solar/Wind Harmer
0.981
970685AG2-442 GEN
Solar/Wind Harmer
30.139
971775AH1-396 GEN
Solar/Wind Harmer
2.342
957481AF2-042 GEN
Solar/Wind Harmer
45.223
970413AG2-270 GEN
50/50
42.707
316322AB2-045
Solar/Wind Helper
1.698
316258AE1-075 C
Solar/Wind Helper
0.453
3147133PAMPLIN
Solar/Wind Harmer
3.885
971629AH1-314 GEN
50/50
5.961
3147133PAMPLIN
Solar/Wind Harmer
0.99
961791AG1-021 GEN
Solar/Wind Harmer
4.685
316336AC2-165 C
Solar/Wind Helper
2.942
959311AF2-222 GEN
Solar/Wind Harmer
33.556
315821AE2-092 GEN
Solar/Wind Helper
4.568
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
13.932
963191AG1-168 GEN
Solar/Wind Harmer
3.514
970681AG2-440 GEN
Solar/Wind Harmer
21.528
970099AG2-077 GEN
Solar/Wind Harmer
18.089
315657AE1-056 GEN
Solar/Wind Harmer
14.848
971563AH1-280 GEN
Solar/Wind Harmer
4.685
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.293
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.39
MECLTFEXP_MEC->PJM
CLTF
1.443
SIGELTFEXP_SIGE->PJM
CLTF
0.042
CPLELTFEXP_CPLE->PJM
CLTF
4.456
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.108
LAGNLTFEXP_LAGN->PJM
CLTF
3.105
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.723
TVALTFEXP_TVA->PJM
CLTF
1.589
NYPJM->LTFIMP_NY
CLTF
0.511
LGEELTFEXP_LGEE->PJM
CLTF
0.489
WECLTFEXP_WEC->PJM
CLTF
0.262
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.194

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.02 %
Rating:687.14 MVA
Rating Type:B
MVA to Mitigate:804.11
MW Contribution:7.81
Bus #Bus NameTypeMW Contribution
3146926FARMVIL
Solar/Wind Harmer
0.828
3146926FARMVIL
Solar/Wind Harmer
0.828
970685AG2-442 GEN
Solar/Wind Harmer
23.547
971775AH1-396 GEN
Solar/Wind Harmer
1.785
970531AG2-338 GEN
50/50
2.701
946301AF1-294 GEN
Solar/Wind Harmer
7.646
971741AH1-377 GEN
Solar/Wind Harmer
33.284
3144303KENBRDG
Solar/Wind Harmer
0.595
315693AD1-088 GEN
Solar/Wind Harmer
8.135
972185AH1-677 GEN
50/50
4.797
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
10.446
963191AG1-168 GEN
Solar/Wind Harmer
2.797
970681AG2-440 GEN
Solar/Wind Harmer
16.82
964241AG1-285 GEN
Solar/Wind Harmer
15.081
3147043LAWRENC
50/50
1.217
3147133PAMPLIN
Solar/Wind Harmer
0.797
961791AG1-021 GEN
Solar/Wind Harmer
3.73
316336AC2-165 C
Solar/Wind Helper
3.441
970285AG2-188 GEN
Solar/Wind Harmer
47.032
3147133PAMPLIN
Solar/Wind Harmer
0.996
958211AF2-115 GEN
Solar/Wind Harmer
4.662
959311AF2-222 GEN
Solar/Wind Harmer
25.776
971845AH1-439 GEN
Solar/Wind Harmer
29.645
3147133PAMPLIN
Solar/Wind Harmer
3.128
970301AG2-198 GEN
Solar/Wind Harmer
16.156
970323AG2-213 GEN
Solar/Wind Harmer
11.901
315785AD2-033 C
Solar/Wind Harmer
0.001
963171AG1-166 GEN
Solar/Wind Harmer
3.73
962491AG1-098 GEN
Solar/Wind Harmer
11.436
270494AE1-108_GEN
Solar/Wind Helper
6.756
316313AB2-026
Solar/Wind Helper
0.583
970535AG2-341 GEN
50/50
7.806
972187AH1-678 GEN
50/50
2.495
315779AE2-040
50/50
0.84
939181AE1-148 GEN
Solar/Wind Harmer
5.031
971193AH1-056 GEN
Solar/Wind Harmer
19.926
970683AG2-441 GEN
Solar/Wind Harmer
21.024
962561AG1-105 GEN
Solar/Wind Harmer
7.662
316405AF2-144 C
50/50
Charging
1.188
963181AG1-167 GEN
Solar/Wind Harmer
2.797
970257AG2-171 GEN
Solar/Wind Harmer
8.926
970413AG2-270 GEN
50/50
20.349
316322AB2-045
Solar/Wind Helper
2.037
316258AE1-075 C
Solar/Wind Helper
0.525
315821AE2-092 GEN
Solar/Wind Helper
5.447
315657AE1-056 GEN
Solar/Wind Harmer
11.956
963041AG1-153 GEN
50/50
5.503
970533AG2-339 GEN
50/50
6.753
971563AH1-280 GEN
Solar/Wind Harmer
3.73
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.808
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.196
MECLTFEXP_MEC->PJM
CLTF
0.917
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
4.467
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.926
LAGNLTFEXP_LAGN->PJM
CLTF
2.492
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.117
TVALTFEXP_TVA->PJM
CLTF
1.273
NYPJM->LTFIMP_NY
CLTF
0.562
LGEELTFEXP_LGEE->PJM
CLTF
0.263
WECLTFEXP_WEC->PJM
CLTF
0.142
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.052

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.89 %
Rating:687.14 MVA
Rating Type:B
MVA to Mitigate:782.56
MW Contribution:11.55
Bus #Bus NameTypeMW Contribution
3146926FARMVIL
Solar/Wind Harmer
0.981
3146926FARMVIL
Solar/Wind Harmer
0.981
970685AG2-442 GEN
Solar/Wind Harmer
30.139
971775AH1-396 GEN
Solar/Wind Harmer
2.342
971741AH1-377 GEN
Solar/Wind Harmer
46.769
946301AF1-294 GEN
Solar/Wind Harmer
9.604
3144303KENBRDG
Solar/Wind Harmer
0.781
315693AD1-088 GEN
Solar/Wind Harmer
15.308
3147043LAWRENC
50/50
1.477
971629AH1-314 GEN
50/50
5.961
3147133PAMPLIN
Solar/Wind Harmer
0.99
961791AG1-021 GEN
Solar/Wind Harmer
4.685
316336AC2-165 C
Solar/Wind Helper
2.942
970285AG2-188 GEN
Solar/Wind Harmer
52.726
3147133PAMPLIN
Solar/Wind Harmer
1.237
958211AF2-115 GEN
Solar/Wind Harmer
5.856
959311AF2-222 GEN
Solar/Wind Harmer
33.556
957481AF2-042 GEN
Solar/Wind Harmer
34.573
970301AG2-198 GEN
Solar/Wind Harmer
21.548
970323AG2-213 GEN
Solar/Wind Harmer
15.612
315785AD2-033 C
Solar/Wind Harmer
0.001
963171AG1-166 GEN
Solar/Wind Harmer
4.685
962491AG1-098 GEN
Solar/Wind Harmer
20.906
270494AE1-108_GEN
Solar/Wind Helper
5.509
316313AB2-026
Solar/Wind Helper
0.503
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
13.932
963191AG1-168 GEN
Solar/Wind Harmer
3.514
970681AG2-440 GEN
Solar/Wind Harmer
21.528
970099AG2-077 GEN
Solar/Wind Harmer
13.829
971193AH1-056 GEN
Solar/Wind Harmer
24.746
970683AG2-441 GEN
Solar/Wind Harmer
26.91
970413AG2-270 GEN
50/50
42.707
316322AB2-045
Solar/Wind Helper
1.698
316258AE1-075 C
Solar/Wind Helper
0.453
970535AG2-341 GEN
50/50
11.549
316405AF2-144 C
50/50
Charging
1.025
963181AG1-167 GEN
Solar/Wind Harmer
3.514
970257AG2-171 GEN
Solar/Wind Harmer
11.709
315657AE1-056 GEN
Solar/Wind Harmer
14.848
971845AH1-439 GEN
Solar/Wind Harmer
32.915
3147133PAMPLIN
Solar/Wind Harmer
3.885
315821AE2-092 GEN
Solar/Wind Helper
4.568
971563AH1-280 GEN
Solar/Wind Harmer
4.685
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.293
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.39
MECLTFEXP_MEC->PJM
CLTF
1.443
SIGELTFEXP_SIGE->PJM
CLTF
0.042
CPLELTFEXP_CPLE->PJM
CLTF
4.456
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.108
LAGNLTFEXP_LAGN->PJM
CLTF
3.105
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.723
TVALTFEXP_TVA->PJM
CLTF
1.589
NYPJM->LTFIMP_NY
CLTF
0.511
LGEELTFEXP_LGEE->PJM
CLTF
0.489
WECLTFEXP_WEC->PJM
CLTF
0.262
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.194

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.47 %
Rating:698.42 MVA
Rating Type:B
MVA to Mitigate:841.42
MW Contribution:7.8
Bus #Bus NameTypeMW Contribution
3146926FARMVIL
Solar/Wind Harmer
0.828
3146926FARMVIL
Solar/Wind Harmer
0.828
970685AG2-442 GEN
Solar/Wind Harmer
23.537
971775AH1-396 GEN
Solar/Wind Harmer
1.784
970531AG2-338 GEN
50/50
2.696
3146776BUCKING
Solar/Wind Harmer
7.109
3146776BUCKING
Solar/Wind Harmer
0.576
946301AF1-294 GEN
Solar/Wind Harmer
7.643
971741AH1-377 GEN
Solar/Wind Harmer
33.27
3144303KENBRDG
Solar/Wind Harmer
0.595
315693AD1-088 GEN
Solar/Wind Harmer
8.129
972185AH1-677 GEN
50/50
4.788
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
10.442
963191AG1-168 GEN
Solar/Wind Harmer
2.796
970681AG2-440 GEN
Solar/Wind Harmer
16.812
964241AG1-285 GEN
Solar/Wind Harmer
15.072
3147043LAWRENC
50/50
1.216
3147133PAMPLIN
Solar/Wind Harmer
0.797
961791AG1-021 GEN
Solar/Wind Harmer
3.728
316336AC2-165 C
Solar/Wind Helper
3.444
970285AG2-188 GEN
Solar/Wind Harmer
47.021
3147133PAMPLIN
Solar/Wind Harmer
0.996
958211AF2-115 GEN
Solar/Wind Harmer
4.66
959311AF2-222 GEN
Solar/Wind Harmer
25.764
971845AH1-439 GEN
Solar/Wind Harmer
29.639
3147133PAMPLIN
Solar/Wind Harmer
3.127
970301AG2-198 GEN
Solar/Wind Harmer
16.15
970323AG2-213 GEN
Solar/Wind Harmer
11.895
315785AD2-033 C
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.64
963171AG1-166 GEN
Solar/Wind Harmer
3.728
962491AG1-098 GEN
Solar/Wind Harmer
11.428
270494AE1-108_GEN
Solar/Wind Helper
6.761
316313AB2-026
Solar/Wind Helper
0.584
970535AG2-341 GEN
50/50
7.8
972187AH1-678 GEN
50/50
2.49
315779AE2-040
50/50
0.838
3146776BUCKING
Solar/Wind Harmer
0.711
971193AH1-056 GEN
Solar/Wind Harmer
19.918
970683AG2-441 GEN
Solar/Wind Harmer
21.015
962561AG1-105 GEN
Solar/Wind Harmer
3.875
316405AF2-144 C
50/50
Charging
1.189
963181AG1-167 GEN
Solar/Wind Harmer
2.796
970257AG2-171 GEN
Solar/Wind Harmer
8.921
970413AG2-270 GEN
50/50
20.33
316322AB2-045
Solar/Wind Harmer
0.051
316258AE1-075 C
Solar/Wind Helper
0.526
972003AH1-546 GEN
Solar/Wind Harmer
34.665
315821AE2-092 GEN
Solar/Wind Helper
5.451
315657AE1-056 GEN
Solar/Wind Harmer
11.951
963041AG1-153 GEN
50/50
5.493
970533AG2-339 GEN
50/50
6.74
971563AH1-280 GEN
Solar/Wind Harmer
3.728
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.646
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.154
MECLTFEXP_MEC->PJM
CLTF
0.898
SIGELTFEXP_SIGE->PJM
CLTF
0.025
CPLELTFEXP_CPLE->PJM
CLTF
4.455
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.777
LAGNLTFEXP_LAGN->PJM
CLTF
2.469
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.083
TVALTFEXP_TVA->PJM
CLTF
1.262
NYPJM->LTFIMP_NY
CLTF
0.569
LGEELTFEXP_LGEE->PJM
CLTF
0.255
WECLTFEXP_WEC->PJM
CLTF
0.138
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.052

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 593_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 593_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.45 %
Rating:698.42 MVA
Rating Type:B
MVA to Mitigate:813.29
MW Contribution:11.54
Bus #Bus NameTypeMW Contribution
3146926FARMVIL
Solar/Wind Harmer
0.981
3146926FARMVIL
Solar/Wind Harmer
0.981
970685AG2-442 GEN
Solar/Wind Harmer
30.129
971775AH1-396 GEN
Solar/Wind Harmer
2.341
957481AF2-042 GEN
Solar/Wind Harmer
21.362
3146776BUCKING
Solar/Wind Harmer
7.855
3146776BUCKING
Solar/Wind Harmer
0.636
971741AH1-377 GEN
Solar/Wind Harmer
46.756
946301AF1-294 GEN
Solar/Wind Harmer
9.601
3144303KENBRDG
Solar/Wind Harmer
0.78
315693AD1-088 GEN
Solar/Wind Harmer
15.302
942461AE2-259 GEN
Solar/Wind Harmer
0
970909AG2-566 GEN
Solar/Wind Harmer
13.928
963191AG1-168 GEN
Solar/Wind Harmer
3.512
970681AG2-440 GEN
Solar/Wind Harmer
21.52
970099AG2-077 GEN
Solar/Wind Harmer
8.545
3147043LAWRENC
50/50
1.476
971629AH1-314 GEN
50/50
5.948
3147133PAMPLIN
Solar/Wind Harmer
0.99
961791AG1-021 GEN
Solar/Wind Harmer
4.683
316336AC2-165 C
Solar/Wind Helper
2.946
970285AG2-188 GEN
Solar/Wind Harmer
52.716
3147133PAMPLIN
Solar/Wind Harmer
1.237
958211AF2-115 GEN
Solar/Wind Harmer
5.854
959311AF2-222 GEN
Solar/Wind Harmer
33.544
970301AG2-198 GEN
Solar/Wind Harmer
21.542
970323AG2-213 GEN
Solar/Wind Harmer
15.606
315785AD2-033 C
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.707
963171AG1-166 GEN
Solar/Wind Harmer
4.683
962491AG1-098 GEN
Solar/Wind Harmer
20.898
270494AE1-108_GEN
Solar/Wind Helper
5.515
316313AB2-026
Solar/Wind Helper
0.504
970535AG2-341 GEN
50/50
11.543
3146776BUCKING
Solar/Wind Harmer
0.786
971193AH1-056 GEN
Solar/Wind Harmer
24.739
970683AG2-441 GEN
Solar/Wind Harmer
26.901
316405AF2-144 C
50/50
Charging
1.026
963181AG1-167 GEN
Solar/Wind Harmer
3.512
970257AG2-171 GEN
Solar/Wind Harmer
11.705
970413AG2-270 GEN
50/50
42.688
316322AB2-045
Solar/Wind Harmer
0.057
316258AE1-075 C
Solar/Wind Helper
0.453
972003AH1-546 GEN
Solar/Wind Harmer
36.562
315821AE2-092 GEN
Solar/Wind Helper
4.572
315657AE1-056 GEN
Solar/Wind Harmer
14.843
971845AH1-439 GEN
Solar/Wind Harmer
32.909
3147133PAMPLIN
Solar/Wind Harmer
3.884
971563AH1-280 GEN
Solar/Wind Harmer
4.683
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.131
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.348
MECLTFEXP_MEC->PJM
CLTF
1.425
SIGELTFEXP_SIGE->PJM
CLTF
0.042
CPLELTFEXP_CPLE->PJM
CLTF
4.444
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.958
LAGNLTFEXP_LAGN->PJM
CLTF
3.082
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.689
TVALTFEXP_TVA->PJM
CLTF
1.577
NYPJM->LTFIMP_NY
CLTF
0.518
LGEELTFEXP_LGEE->PJM
CLTF
0.481
WECLTFEXP_WEC->PJM
CLTF
0.258
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
11.194
CONTINGENCY 'DVP_P1-3: 6CLOUD-TX#2_SRT-A'
 OPEN BRANCH FROM BUS 313757 TO BUS 313785 CKT 2   /*3CLOUD       115.0 - 6CLOUD       230.0
END
CONTINGENCY 'DVP_P1-3: 6CLOUD-TX#1_SRT-A'
 OPEN BRANCH FROM BUS 313757 TO BUS 313785 CKT 1   /*3CLOUD       115.0 - 6CLOUD       230.0
END
CONTINGENCY 'DVP_P1-2: LN 2201_SRT-L'
 OPEN BRANCH FROM BUS 313725 TO BUS 314563 CKT 1                /*6DRY BREAD   230.0 - 6CLUBHSE     230.0
 SET POSTCONTRATING 1141 BRANCH FROM BUS 313725 TO BUS 314583 CKT 1 /*6DRY BREAD   230.0 - 6LAKEVEW     230.0
 SET PRECONTRATING 1090 BRANCH FROM BUS 313725 TO BUS 314583 CKT 1 /*6DRY BREAD   230.0 - 6LAKEVEW     230.0
END
CONTINGENCY 'DVP_P1-2: LN 254_SRT-L'
 OPEN BRANCH FROM BUS 313725 TO BUS 314583 CKT 1                /*6DRY BREAD   230.0 - 6LAKEVEW     230.0
 SET POSTCONTRATING 1141 BRANCH FROM BUS 313725 TO BUS 314563 CKT 1 /*6DRY BREAD   230.0 - 6CLUBHSE     230.0
 SET POSTCONTRATING 1518 BRANCH FROM BUS 314561 TO BUS 314583 CKT 1 /*6CAROLNA     230.0 - 6LAKEVEW     230.0
 SET PRECONTRATING 1090 BRANCH FROM BUS 313725 TO BUS 314563 CKT 1 /*6DRY BREAD   230.0 - 6CLUBHSE     230.0
 SET PRECONTRATING 1434 BRANCH FROM BUS 314561 TO BUS 314583 CKT 1 /*6CAROLNA     230.0 - 6LAKEVEW     230.0
END
CONTINGENCY 'DVP_P1-2: LN 298_SRT-A-1'
 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2   /*3FARMVIL     115.0 - 6FARMVIL     230.0
 OPEN BRANCH FROM BUS 970284 TO BUS 314692 CKT 1   /*AG2-188 TP   230.0 - 6FARMVIL     230.0
END
CONTINGENCY 'DVP_P1-2: LN 235_SRT-A-4'
 OPEN BRANCH FROM BUS 314268 TO BUS 314692 CKT 1   /*6BRIERY      230.0 - 6FARMVIL     230.0
 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1   /*3FARMVIL     115.0 - 6FARMVIL     230.0
 OPEN BRANCH FROM BUS 970300 TO BUS 314268 CKT 1   /*AG2-198 TP   230.0 - 6BRIERY      230.0
 OPEN BUS 314268                                   /*6BRIERY      230.0
END
CONTINGENCY 'DVP_P1-2: LN 1012_SRT-A-2'
 OPEN BRANCH FROM BUS 964240 TO BUS 314681 CKT 1   /*AG1-285 TP   115.0 - 3CHASCTY     115.0
END
CONTINGENCY 'DVP_P7-1: LN 1041-38_SRT-A'
 OPEN BRANCH FROM BUS 313099 TO BUS 314674 CKT 1   /*3BOYDTON DP  115.0 - 3BOYDTON TAP 115.0
 OPEN BRANCH FROM BUS 313757 TO BUS 314674 CKT 1   /*3CLOUD       115.0 - 3BOYDTON TAP 115.0
 OPEN BRANCH FROM BUS 313757 TO BUS 314702 CKT 1   /*3CLOUD       115.0 - 3KERR        115.0
 OPEN BRANCH FROM BUS 314255 TO BUS 314674 CKT 1   /*3BOYDPLK     115.0 - 3BOYDTON TAP 115.0
 OPEN BUS 313099                                   /*3BOYDTON DP  115.0
 OPEN BUS 314674                                   /*3BOYDTON TAP 115.0
END
CONTINGENCY 'DVP_P7-1: LN 1041-137_SRT-A'
 OPEN BRANCH FROM BUS 313099 TO BUS 314674 CKT 1   /*3BOYDTON DP  115.0 - 3BOYDTON TAP 115.0
 OPEN BRANCH FROM BUS 313757 TO BUS 314674 CKT 1   /*3CLOUD       115.0 - 3BOYDTON TAP 115.0
 OPEN BRANCH FROM BUS 313791 TO BUS 314702 CKT 1   /*3BISHOP      115.0 - 3KERR        115.0
 OPEN BRANCH FROM BUS 314255 TO BUS 314674 CKT 1   /*3BOYDPLK     115.0 - 3BOYDTON TAP 115.0
 OPEN BUS 313099                                   /*3BOYDTON DP  115.0
 OPEN BUS 314674                                   /*3BOYDTON TAP 115.0
END
CONTINGENCY 'DVP_P1-2: LN 84_SRT-A'
 OPEN BRANCH FROM BUS 314521 TO BUS 314713 CKT 1   /*3PAMPL_1     115.0 - 3PAMPLIN     115.0
 OPEN BRANCH FROM BUS 314691 TO BUS 314726 CKT 1   /*3FARMVIL     115.0 - 3WILLIS      115.0
 OPEN BRANCH FROM BUS 314713 TO BUS 314726 CKT 1   /*3PAMPLIN     115.0 - 3WILLIS      115.0
 OPEN BUS 313127                                   /*3CURDSVILLE  115.0
 OPEN BUS 314521                                   /*3PAMPL_1     115.0
 OPEN BUS 314726                                   /*3WILLIS      115.0
END
CONTINGENCY 'DVP_P1-2: LN 576_SRT-L'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3914 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET PRECONTRATING 3880 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON      500.0 - 8MDLTHAN     500.0
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-L'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3359 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 3377 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P4-2: 509T570_SRT-A'
 OPEN BRANCH FROM BUS 314935 TO BUS 314945 CKT 1   /*8HERITAGE    500.0 - 8BRUNSWICK   500.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315102 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG1  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315103 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG2  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315104 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG3  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315105 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKS1  19.0
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 OPEN BUS 314945                                   /*8BRUNSWICK   500.0
 OPEN BUS 315102                                   /*1BRUNSWICKG1  21.0
 OPEN BUS 315103                                   /*1BRUNSWICKG2  21.0
 OPEN BUS 315104                                   /*1BRUNSWICKG3  21.0
 OPEN BUS 315105                                   /*1BRUNSWICKS1  19.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-3'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-1'
 OPEN BRANCH FROM BUS 304183 TO BUS 970084 CKT 1   /*8WAKE 500 TT 500.0 - AG2-068 TP   500.0
END
CONTINGENCY 'DVP_P4-5: 593X1_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
 OPEN BRANCH FROM BUS 313995 TO BUS 313996 CKT 1   /*8FINNEYWOOD  500.0 - 6FINNEYWOOD  230.0
END
CONTINGENCY 'DVP_P4-5: 593X2_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
 OPEN BRANCH FROM BUS 313995 TO BUS 313996 CKT 2   /*8FINNEYWOOD  500.0 - 6FINNEYWOOD  230.0
END
CONTINGENCY 'DVP_P4-2: H1T593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313986 CKT 1   /*8UNITY       500.0 - 6UNITY       230.0
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P4-2: H2T593_SRT-A'
 OPEN BRANCH FROM BUS 313985 TO BUS 313986 CKT 2   /*8UNITY       500.0 - 6UNITY       230.0
 OPEN BRANCH FROM BUS 313985 TO BUS 313995 CKT 1   /*8UNITY       500.0 - 8FINNEYWOOD  500.0
END
CONTINGENCY 'DVP_P1-2: LN 298_SRT-A-4'
 OPEN BRANCH FROM BUS 972002 TO BUS 314747 CKT 1   /*AH1-546 TP   230.0 - 6BREMO       230.0
END
313757 to 313785 ckt 1
313757 to 313785 ckt 2
314562 to 314563 ckt 1
314691 to 314692 ckt 1
314691 to 314692 ckt 2
313755 to 314707 ckt 1
314707 to 314691 ckt 1
314726 to 314691 ckt 1
314747 to 313867 ckt 1
313867 to 313707 ckt 1
314677 to 972002 ckt 1
314692 to 970284 ckt 1
313707 to 313373 ckt 1
313373 to 314765 ckt 1
314765 to 314749 ckt 1
304070 to 316281 ckt 1
316281 to 304070 ckt 1
962490 to 313996 ckt 1
970284 to 971844 ckt 1
971844 to 314677 ckt 1
972002 to 314747 ckt 1

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-038Lexington-Low Moor 230kVUnder Construction
AA1-050Tarboro-Everetts 230kVIn Service
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-067Everetts 34.5kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-057Hornertown-Whitakers 115kVIn Service
AA2-174Carolina-Jackson 115kVIn Service
AA2-178Mackeys 230kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-132Thelma 230kVIn Service
AB2-022Elizabeth City 34.5kVIn Service
AB2-024Correctional 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-031Brink-Trego 115kVIn Service
AB2-040Brink 115kVIn Service
AB2-043Chase City 115kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-134Hopewell-Surry 230kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-169Pantago-Five Points 115kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVSuspended
AC1-036Twittys Creek 34.5kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-086Thelma 230kVSuspended
AC1-098Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-099Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-191Elmont 115kVEngineering & Procurement
AC1-208Cox-Whitakers 115kVUnder Construction
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-079Ivor-Oak Ridge 115kVSuspended
AC2-100Halifax-Person 230kVIn Service
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-165Bremo-Powhatan 230kVSuspended
AD1-017Smith Mountain-Bearskin 138 kVIn Service
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVUnder Construction
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-063Harmony Village 34.5 kVIn Service
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-088Briery-Clover 230 kVSuspended
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-144Kings Fork 34.5 kVIn Service
AD1-151Hopewell-Surry 230 kVSuspended
AD1-152Clover-Sedge Hill 230 kVIn Service
AD2-022East Danville - Roxborough 230 kVEngineering & Procurement
AD2-023East Danville - Roxborough 230 kVEngineering & Procurement
AD2-030Wan 34.5 kVIn Service
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVEngineering & Procurement
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-160Hickory-Moyock 230kVIn Service
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-056Red House-South Creek 115 kVWithdrawn
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-100Axton 138 kVIn Service
AE1-103Holland-Union Camp 115 kVUnder Construction
AE1-108Bremo-Scottsville 138 kVEngineering & Procurement
AE1-148Kerr Dam-Ridge Rd 115 kVActive
AE1-149Disputanta-Poe 115 kVSuspended
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-162Smithfield 34.5 kVIn Service
AE1-173Carson-Suffolk 500 kVUnder Construction
AE1-175Light Foot 34.5 kVIn Service
AE1-190Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-191Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-250Smith Mountain-E. Danville 138 kVEngineering & Procurement
AE2-005Harmony Village-Shackleford 115 kVUnder Construction
AE2-027Harrowgate-Locks 115kVUnder Construction
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-033Clubhouse-Sapony 230 kVSuspended
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-040Sapony 34.5 kVPartially in Service - Under Construction
AE2-047Ridgeway-Solite 69 kVEngineering & Procurement
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-094Carson-Rogers Road 500 kVEngineering & Procurement
AE2-104Suffolk 115 kVSuspended
AE2-140Axton-Danville 138 kVSuspended
AE2-156Yadkin 115 kVActive
AE2-166Stockton 138 kVSuspended
AE2-183Rogers Road 500 kVIn Service
AE2-185Gladys DP-Stonemill Switching Station 69 kVActive
AE2-187Shockoe DP-Chatham 69 kVActive
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-253Hickory-Moyock 230 kVIn Service
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVActive
AE2-291Grit DP-Perth 115 kVActive
AE2-346Ahoskie 34.5 kVIn Service
AF1-014Harmony Village-Shackleford 115 kVUnder Construction
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-028Endless Caverns 115 kVUnder Construction
AF1-032Suffolk 34.5 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-049Berry Hill 138 kVUnder Construction
AF1-058Welco 34.5 kVIn Service
AF1-069Carson-Rogers Rd 500 kVEngineering & Procurement
AF1-088Sullivan 345 kVActive
AF1-123Harper 230 kVActive
AF1-124Harper 230 kVActive
AF1-125Harper 230 kVActive
AF1-128Chesterfield 230 kVActive
AF1-129Chesterfield 230 kVEngineering & Procurement
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-292Fields 34.5kVEngineering & Procurement
AF1-294Jetersville-Ponton 115 kVActive
AF2-008Sullivan 345 kVActive
AF2-042Clover-Rawlings 500 kVActive
AF2-043Suffolk 34.5 kVIn Service
AF2-046Tunis-Mapleton 115 kVActive
AF2-054Wan 34.5 kVIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-080Chinquapin-Everetts 230 kVActive
AF2-081Moyock 230 kVActive
AF2-085Midlothian 34.5 kVIn Service
AF2-107Clifford 138 kVEngineering & Procurement
AF2-110Suffolk 115 kVSuspended
AF2-115Jetersville-Ponton 115 kVActive
AF2-144Powhatan 34.5 kVIn Service
AF2-222Madisonville DP-Twitty's Creek 115 kVActive
AF2-297Sedge Hill 115 kVActive
AF2-299Fields 34.5 kVActive
AG1-007Tar River 12.5 kVEngineering & Procurement
AG1-008Tunis-Mapleton 115 kVActive
AG1-021Jetersville-Ponton 115 kVActive
AG1-037Ahoskie 34.5 kVEngineering & Procurement
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-082Ahoskie 34.5 kVActive
AG1-098Briery-Clover 230 kVActive
AG1-105Mount Laurel-Barnes Junction 115 kVActive
AG1-106Thelma 230 kVActive
AG1-124Gladstone 138 kVActive
AG1-145Lightfoot 34.5 kVIn Service
AG1-153Heritage 500 kVActive
AG1-166Lone Pine 115 kVActive
AG1-167Lone Pine 115 kVActive
AG1-168Lone Pine 115 kVActive
AG1-282Dunnsville 34.5 kVEngineering & Procurement
AG1-285Chase City-Central 115 kVActive
AG1-342Dryburg 115 kVActive
AG1-393Sapony 34.5 kVActive
AG1-394Boykins 34.5 kVActive
AG1-469Gordonsville 34.5 kVEngineering & Procurement
AG1-494Boxwood-Riverville 138 kVActive
AG1-532Fields 34.5 kVEngineering & Procurement
AG1-551Parmele 34.5 kVActive
AG1-552Carolina 34.5 kVActive
AG1-558Buckner 34.5 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
AG2-068Heritage - Wake 500 kVActive
AG2-069Heritage - Wake 500 kVActive
AG2-077Clover-Rawlings 500 kVActive
AG2-086Mt. Jackson DP-Mt. Jackson 115 kVActive
AG2-088Midlothian 230 kVActive
AG2-093Colonial Trail-Hopewell 230 kVActive
AG2-095Hopewell 34.5 kV (Circuit 313)Active
AG2-111Perth 34.5 kV Substation (Circuit 408)Active
AG2-112Perth 34.5 kV Substation (Circuit 404)Active
AG2-120Everetts 34.5 kVActive
AG2-151Trices Lake - James River Tap 115 kVActive
AG2-152Banister-Bear Skin 138 kVActive
AG2-171Lunenburg-Nutbush 115 kVActive
AG2-188Farmville - Buckingham 230 kVActive
AG2-198Briery - Finneywood 230 kVActive
AG2-213Gary D.P Tap - Gary D.P 115 kVActive
AG2-262Dryburg 115 kVActive
AG2-270Clover 230 kVActive
AG2-272Berry Hill 138 kVActive
AG2-338Rogers Road - Carson 500 kVActive
AG2-339Rogers Road - Carson 500 kVActive
AG2-369Heritage - Wake 500 kVActive
AG2-382Cashie 230 kVActive
AG2-426Wakefield - Waverly 115 kVActive
AG2-427Waverly 115 kVActive
AG2-428Wakefield 115 kVActive
AG2-436Carson - Rogers Road 500 kVActive
AG2-440Twittys Creek - Madisonville 115 kVActive
AG2-441Twittys Creek - Madisonville 115 kVActive
AG2-442Twittys Creek - Madisonville 115 kVActive
AG2-522Five Forks DP 115 kVActive
AG2-541Perth - Crystal Hill 115 kVActive
AG2-566Briery - Finneywood 230 kVActive
AG2-570Heritage - Wake 500 kVActive
AG2-571Heritage - Wake 500 kVActive
AG2-581Rawlings-Clover 500 kVActive
AG2-583Bremo - Cartersville 230 kVActive
AG2-659Kerr Dam – Hawtree 115 kVActive
AG2-661Hopewell - Colonial Trail 230 kVActive
AH1-033Sligo 34.5 kVActive
AH1-035Plymouth 34.5 kVActive
AH1-040Mackeys - Creswell 115 kVActive
AH1-042Providence Forge-Turner 115kVActive
AH1-056Red House DP 115kVActive
AH1-071Midlothian 34.5 kVActive
AH1-106Winterpock 34.5kVActive
AH1-107Winterpock 34.5kVActive
AH1-108Spruance NUG 230 kVActive
AH1-138Penniman 34.5 kVActive
AH1-164Oak Level - Tank Hill 138 kVActive
AH1-170Columbia DP 115kVActive
AH1-215Central VA-Twitty 115 kVActive
AH1-216Smithfield-Surry 230 kVActive
AH1-217Kidds Store - Fork Union 115 kV IIActive
AH1-221Heritage 500 kVActive
AH1-241Cobbs Creek - James River Industrial 115kVActive
AH1-271Cashie 230 kVActive
AH1-280Jetersville-Ponton 115 kVActive
AH1-311Heartsease DP - Mayo Dunbar 115kVActive
AH1-314East Danville 138 kVActive
AH1-324Colonial Trail – Surry 230 kVActive
AH1-343Crystal Hill DP- Perth 115kVActive
AH1-377Clover- Farmville 230kVActive
AH1-396Gary 24.94 kVActive
AH1-408Freeman DP – Lawrenceville 115 kVActive
AH1-439Buckingham- Farmville 230kVActive
AH1-528Rawlings - Unity 500 kVActive
AH1-535Nagel - Cane River 230 kVActive
AH1-546Bremo - Buckingham 230 kVActive
AH1-677Rogers Road 500 kVActive
AH1-678Heritage 500 kVActive
AH1-687Bear Garden 230kVActive
AH1-716Surry-Skiffes Creek 500kVActive
AH1-717Surry 230kVActive
V4-068Murphy's 34.5kVIn Service
Y1-086Morgans CornerIn Service
Z1-036WinFall-Chowan 230kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-044Whitakers 34.5kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)Identified Impacts

No cost allocated AFS Tie Line reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.


System Reinforcement
Type
Load Flow
TO
CPLE
RTEP ID / TO ID
(Pending) / TC2-CPLE-0003
Title
Henderson - VP Kerr Dam 115kV Line (Reconductor)
Description
Current DEP project to reconductor approx 1 mile of existing line (estimated ISD is 6/1/2029). Estimated costs are for the remainder of the existing line Date assumes 2 years of construction (4 outage seasons) after the current DEP project is expected to be completed. The Kerr-GW King Tap rating is 239MVA for all temps (1200A switch).
Total Cost ($USD)
$23,615,000
Allocated Cost ($USD)
$0
Time Estimate
0 to 54 Months

Info

Note: AG2-341 contributes to the loading of an overloaded tie line facility between PJM and an affected system entity, which was identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line and will be confirmed in subsequent study phases, along with cost allocation of such upgrade if applicable, in coordination with the affected system.

FacilityContingency
3GW KING TAP-3KERR 115.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
CPLE
RTEP ID / TO ID
(Pending) / TC2-CPLE-0001
Title
Person - VP Hendrick 230kV Line (Existing Line Uprate)
Description
Currently no costs since there is already a DEP project to reconductor to upgrade this line. This is the estimated ISD for the current project CPLE is developing. The Person - Hendrick 230 kV line will be reconductored with bundled 795 ACSS/TW and will have a rating 1195MVA.
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
0 to 48 Months

Info

Note: AG2-341 contributes to the loading of an overloaded tie line facility between PJM and an affected system entity, which was identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line and will be confirmed in subsequent study phases, along with cost allocation of such upgrade if applicable, in coordination with the affected system.

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
CPLE
RTEP ID / TO ID
(Pending) / TC2-CPLE-0002
Title
Person - VP Hendrick 230kV line (New Line)
Description
This project is to add second line that would be built to 1195MVA. Assumed ~5 mile 230kV line with bundled conductor and can utilize last remaining CB bay at Person (no fence expansion). Estimated ISD Assumed 5 years from Kick off to complete work (Site & acquire ROW, engineering, construction) and assuming no other outage constraints (DEP or PJM) from previous projects already planned. The new line will also be bundled 795 ACSS/TW.
Total Cost ($USD)
$28,300,000
Allocated Cost ($USD)
$0
Time Estimate
0 to 60 Months

Info

Note: AG2-341 contributes to the loading of an overloaded tie line facility between PJM and an affected system entity, which was identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line and will be confirmed in subsequent study phases, along with cost allocation of such upgrade if applicable, in coordination with the affected system.

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)

Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Study Pending
Duke Energy Progress – East (CPLE)Study Pending
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase I analysis results, this project may have a cost responsibility for the following System Reinforcements:

AG2-341 System Reinforcements:
TORTEP IDTitleAllocated Cost ($USD)
Dominion(Pending) / TC1-PH1-DOM-006Add a 3rd new 224 MVA 115/230 kV Transformer at Cloud substation, one (1) 230 kV breaker and one (1) 115 kV breaker.$1,165,567
Dominionn9305.0 / TC1-PH2-DOM-037Replace existing 115/230 kV Transformers #4 and #5 and add two additional 115/230 kV transformers at Farmville Substation. Farmville Substation will be reconfigured as a breaker and a half.$259,794
Dominion(Pending) / TC2-PH1-DOM-2043Wreck and rebuild 0.93 miles of 230 kV Line 2241 between Hendrick and Persons with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Dominion portion of line only.$27,834
Dominionn9221.0 / TC1-PH3-DOM-015-TC2Replace 230 kV Breaker 29822 at Bremo with a higher-rated device (Buckingham - Bremo).$20,843
Dominion(Pending) / TC2-PH1-DOM-2077Replace switches 29824 and 29825 at Bremo 230 kV$8,105
Dominion(Pending) / TC2-PH1-DOM-2087Replace 2-1590 AAC 61 line lead on line 298 at Farmville 230 kV$7,298
Dominion(Pending) / TC2-PH1-DOM-2086Replace 3 1/2' AL Pipe line lead on line 298 at Farmville 230 kV$7,298
Dominion(Pending) / TC2-PH1-DOM-2085Replace wavetrap 298WT at Farmville 230 kV$6,369
Dominion(Pending) / TC2-PH1-DOM-2079Replace 3 1/2 " AL Pipe line lead on line 298 at Bremo 230 kV$5,517
Dominion(Pending) / TC2-PH1-DOM-2078Replace 2-636 ACSR line lead on line 298 at Bremo 230 kV$5,065
Dominion(Pending) / TC2-PH1-DOM-2076Replace wave trap 298 WT at Bremo 230 kV$4,052
Grand Total:$1,517,742

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH1-DOM-006
Title
Add a 3rd new 224 MVA 115/230 kV Transformer at Cloud substation, one (1) 230 kV breaker and one (1) 115 kV breaker.
Description
Add a 3rd new 224 MVA 115/230 kV Transformer at Cloud substation, one (1) 230 kV breaker and one (1) 115 kV breaker.
Total Cost ($USD)
$11,000,000
Allocated Cost ($USD)
$1,165,567
Time Estimate
42 to 44 Months

Contributor

FacilityContingency
3CLOUD-6CLOUD 115.0/230.0 kV Ckt 1 transformer(Any)
3CLOUD-6CLOUD 115.0/230.0 kV Ckt 2 transformer(Any)
(Any)DVP_P1-3: 6CLOUD-TX#1_SRT-A
(Any)DVP_P1-3: 6CLOUD-TX#2_SRT-A
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-171
13.9 MW6.1%$665,506
AG2-213
18.6 MW8.1%$887,405
AG2-270
17.1 MW7.4%$816,814
AG2-341
24.4 MW10.6%$1,165,567
AG2-440
19.4 MW8.4%$928,289
AG2-441
24.3 MW10.5%$1,160,313
AG2-442
27.2 MW11.8%$1,299,585
AG2-522
25.4 MW11.0%$1,213,328
AG2-659
28.5 MW12.4%$1,360,337
AH1-056
13.4 MW5.8%$637,995
AH1-408
18.1 MW7.9%$864,862

System Reinforcement: n9305.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9305.0 / TC1-PH2-DOM-037
Title
Replace existing 115/230 kV Transformers #4 and #5 and add two additional 115/230 kV transformers at Farmville Substation. Farmville Substation will be reconfigured as a breaker and a half.
Description
Replace existing 115/230 kV Transformers #4 and #5 with 224 MVA transformers (rated 260/271/295 MVA) and add two additional 115/230 kV 224 MVA transformers (rated 260/271/295 MVA) at Farmville Substation. Farmville Substation will be rebuilt in a breaker and a half configuration on the 115 kV and 230 kV side.
Total Cost ($USD)
$121,800,000
Allocated Cost ($USD)
$259,794
Time Estimate
42 to 48 Months

Contributor

FacilityContingency
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer(Any)
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-171
79.0 MW2.7%$3,303,063
AG2-213
105.3 MW3.6%$4,404,084
AG2-341
6.2 MW0.2%$259,794
AG2-440
552.7 MW19.0%$23,109,441
AG2-441
690.8 MW23.7%$28,886,885
AG2-442
773.7 MW26.6%$32,353,277
AH1-056
552.7 MW19.0%$23,109,441
AH1-215
125.9 MW4.3%$5,262,957
AH1-280
15.8 MW0.5%$659,877
AH1-408
10.8 MW0.4%$451,180

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2043
Title
Wreck and rebuild 0.93 miles of 230 kV Line 2241 between Hendrick and Persons with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Dominion portion of line only.
Description
Wreck and rebuild 0.93 miles of 230 kV Line 2241 between Hendrick and Persons with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Dominion portion of line only.
Total Cost ($USD)
$3,534,000
Allocated Cost ($USD)
$27,834
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
9.2 MW1.1%$39,652
AG2-069
13.8 MW1.7%$59,477
AG2-077
67.9 MW8.3%$292,796
AG2-111
3.5 MW0.4%$15,101
AG2-112
3.7 MW0.4%$15,830
AG2-151
7.2 MW0.9%$31,260
AG2-152
14.7 MW1.8%$63,434
AG2-171
13.1 MW1.6%$56,405
AG2-188
21.4 MW2.6%$92,359
AG2-198
19.5 MW2.4%$83,993
AG2-213
17.4 MW2.1%$75,209
AG2-270
47.1 MW5.8%$203,423
AG2-272
5.3 MW0.7%$23,062
AG2-341
6.5 MW0.8%$27,834
AG2-369
7.9 MW1.0%$34,099
AG2-440
21.4 MW2.6%$92,165
AG2-441
26.7 MW3.3%$115,205
AG2-442
29.9 MW3.7%$129,034
AG2-522
10.0 MW1.2%$43,134
AG2-541
19.1 MW2.3%$82,250
AG2-566
9.3 MW1.1%$39,936
AG2-570
35.7 MW4.4%$154,059
AG2-571
15.5 MW1.9%$67,037
AG2-581
50.2 MW6.1%$216,526
AG2-583
7.5 MW0.9%$32,494
AG2-659
11.3 MW1.4%$48,915
AH1-056
20.7 MW2.5%$89,249
AH1-215
8.7 MW1.1%$37,455
AH1-241
6.9 MW0.8%$29,676
AH1-314
15.6 MW1.9%$67,343
AH1-343
22.0 MW2.7%$94,896
AH1-377
48.3 MW5.9%$208,557
AH1-408
10.5 MW1.3%$45,498
AH1-439
12.3 MW1.5%$53,152
AH1-528
100.6 MW12.3%$434,213
AH1-535
6.0 MW0.7%$25,767
AH1-546
7.3 MW0.9%$31,579
AH1-687
5.2 MW0.6%$22,479
AH1-690
28.7 MW3.5%$123,688
AH1-721
31.5 MW3.8%$135,756

System Reinforcement: n9221.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9221.0 / TC1-PH3-DOM-015-TC2
Title
Replace 230 kV Breaker 29822 at Bremo with a higher-rated device (Buckingham - Bremo).
Description
Replace 230 kV Breaker 29822 at Bremo with a higher-rated device (Buckingham - Bremo).
Total Cost ($USD)
$2,057,335
Allocated Cost ($USD)
$20,843
Time Estimate
38 to 39 Months

Contributor

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.3 MW0.6%$11,624
AG2-069
6.5 MW0.8%$17,436
AG2-077
47.9 MW6.2%$127,897
AG2-171
16.0 MW2.1%$42,650
AG2-188
71.8 MW9.3%$191,886
AG2-198
29.4 MW3.8%$78,462
AG2-213
21.3 MW2.8%$56,868
AG2-270
30.0 MW3.9%$80,033
AG2-338
2.8 MW0.4%$7,356
AG2-339
6.9 MW0.9%$18,392
AG2-341
7.8 MW1.0%$20,843
AG2-369
3.7 MW0.5%$9,996
AG2-436
28.6 MW3.7%$76,439
AG2-440
29.3 MW3.8%$78,406
AG2-441
36.7 MW4.8%$98,006
AG2-442
41.1 MW5.3%$109,766
AG2-522
9.8 MW1.3%$26,214
AG2-541
8.0 MW1.0%$21,431
AG2-566
10.4 MW1.4%$27,902
AG2-570
7.3 MW0.9%$19,429
AG2-571
2.9 MW0.4%$7,773
AG2-581
36.5 MW4.7%$97,645
AG2-659
10.8 MW1.4%$28,784
AH1-056
33.7 MW4.4%$90,107
AH1-215
8.3 MW1.1%$22,192
AH1-314
6.0 MW0.8%$15,905
AH1-343
9.2 MW1.2%$24,554
AH1-377
63.7 MW8.3%$170,330
AH1-408
11.4 MW1.5%$30,369
AH1-439
44.8 MW5.8%$119,784
AH1-528
73.3 MW9.5%$195,806
AH1-546
49.8 MW6.5%$133,048

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2077
Title
Replace switches 29824 and 29825 at Bremo 230 kV
Description
Replace switches 29824 and 29825 at Bremo 230 kV
Total Cost ($USD)
$800,000
Allocated Cost ($USD)
$8,105
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.3 MW0.6%$4,520
AG2-069
6.5 MW0.8%$6,780
AG2-077
47.9 MW6.2%$49,733
AG2-171
16.0 MW2.1%$16,585
AG2-188
71.8 MW9.3%$74,615
AG2-198
29.4 MW3.8%$30,510
AG2-213
21.3 MW2.8%$22,113
AG2-270
30.0 MW3.9%$31,121
AG2-338
2.8 MW0.4%$2,861
AG2-339
6.9 MW0.9%$7,152
AG2-341
7.8 MW1.0%$8,105
AG2-369
3.7 MW0.5%$3,887
AG2-436
28.6 MW3.7%$29,724
AG2-440
29.3 MW3.8%$30,488
AG2-441
36.7 MW4.8%$38,110
AG2-442
41.1 MW5.3%$42,683
AG2-522
9.8 MW1.3%$10,193
AG2-541
8.0 MW1.0%$8,333
AG2-566
10.4 MW1.4%$10,850
AG2-570
7.3 MW0.9%$7,555
AG2-571
2.9 MW0.4%$3,023
AG2-581
36.5 MW4.7%$37,970
AG2-659
10.8 MW1.4%$11,193
AH1-056
33.7 MW4.4%$35,038
AH1-215
8.3 MW1.1%$8,629
AH1-314
6.0 MW0.8%$6,185
AH1-343
9.2 MW1.2%$9,548
AH1-377
63.7 MW8.3%$66,233
AH1-408
11.4 MW1.5%$11,809
AH1-439
44.8 MW5.8%$46,578
AH1-528
73.3 MW9.5%$76,140
AH1-546
49.8 MW6.5%$51,736

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2087
Title
Replace 2-1590 AAC 61 line lead on line 298 at Farmville 230 kV
Description
Replace 2-1590 AAC 61 line lead on line 298 at Farmville 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$7,298
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-077
47.9 MW9.0%$44,774
AG2-171
16.0 MW3.0%$14,930
AG2-198
29.4 MW5.5%$27,463
AG2-213
21.3 MW4.0%$19,907
AG2-270
30.0 MW5.6%$28,019
AG2-341
7.8 MW1.5%$7,298
AG2-440
29.4 MW5.5%$27,445
AG2-441
36.7 MW6.9%$34,306
AG2-442
41.1 MW7.7%$38,422
AG2-522
9.8 MW1.8%$9,183
AG2-541
8.0 MW1.5%$7,507
AG2-566
10.4 MW2.0%$9,766
AG2-581
36.6 MW6.8%$34,184
AG2-659
10.8 MW2.0%$10,082
AH1-056
33.7 MW6.3%$31,539
AH1-215
8.3 MW1.6%$7,769
AH1-343
9.2 MW1.7%$8,600
AH1-377
63.8 MW11.9%$59,618
AH1-408
11.4 MW2.1%$10,641
AH1-528
73.3 MW13.7%$68,548

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2086
Title
Replace 3 1/2' AL Pipe line lead on line 298 at Farmville 230 kV
Description
Replace 3 1/2' AL Pipe line lead on line 298 at Farmville 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$7,298
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-077
47.9 MW9.0%$44,774
AG2-171
16.0 MW3.0%$14,930
AG2-198
29.4 MW5.5%$27,463
AG2-213
21.3 MW4.0%$19,907
AG2-270
30.0 MW5.6%$28,019
AG2-341
7.8 MW1.5%$7,298
AG2-440
29.4 MW5.5%$27,445
AG2-441
36.7 MW6.9%$34,306
AG2-442
41.1 MW7.7%$38,422
AG2-522
9.8 MW1.8%$9,183
AG2-541
8.0 MW1.5%$7,507
AG2-566
10.4 MW2.0%$9,766
AG2-581
36.6 MW6.8%$34,184
AG2-659
10.8 MW2.0%$10,082
AH1-056
33.7 MW6.3%$31,539
AH1-215
8.3 MW1.6%$7,769
AH1-343
9.2 MW1.7%$8,600
AH1-377
63.8 MW11.9%$59,618
AH1-408
11.4 MW2.1%$10,641
AH1-528
73.3 MW13.7%$68,548

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2085
Title
Replace wavetrap 298WT at Farmville 230 kV
Description
Replace wavetrap 298WT at Farmville 230 kV
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$6,369
Time Estimate
16 to 18 Months

Contributor

FacilityContingency
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.4 MW0.9%$3,558
AG2-069
6.5 MW1.3%$5,337
AG2-077
36.3 MW7.4%$29,621
AG2-171
12.1 MW2.5%$9,886
AG2-198
22.3 MW4.5%$18,192
AG2-213
16.2 MW3.3%$13,181
AG2-270
29.9 MW6.1%$24,400
AG2-338
2.8 MW0.6%$2,252
AG2-339
6.9 MW1.4%$5,631
AG2-341
7.8 MW1.6%$6,369
AG2-369
3.8 MW0.8%$3,060
AG2-436
28.7 MW5.9%$23,401
AG2-440
22.3 MW4.5%$18,175
AG2-441
27.8 MW5.7%$22,719
AG2-442
31.2 MW6.4%$25,446
AG2-522
7.4 MW1.5%$6,073
AG2-541
6.1 MW1.2%$4,955
AG2-566
10.4 MW2.1%$8,523
AG2-570
7.3 MW1.5%$5,948
AG2-571
2.9 MW0.6%$2,379
AG2-581
27.7 MW5.7%$22,616
AG2-659
8.2 MW1.7%$6,667
AH1-056
29.2 MW6.0%$23,852
AH1-215
6.3 MW1.3%$5,144
AH1-314
6.0 MW1.2%$4,871
AH1-343
7.0 MW1.4%$5,678
AH1-377
48.4 MW9.9%$39,485
AH1-408
9.0 MW1.8%$7,347
AH1-528
55.4 MW11.3%$45,231

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2079
Title
Replace 3 1/2 " AL Pipe line lead on line 298 at Bremo 230 kV
Description
Replace 3 1/2 " AL Pipe line lead on line 298 at Bremo 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$5,517
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-077
47.9 MW6.8%$33,855
AG2-171
16.0 MW2.3%$11,290
AG2-188
71.8 MW10.2%$50,793
AG2-198
29.4 MW4.2%$20,769
AG2-213
21.3 MW3.0%$15,053
AG2-270
30.0 MW4.2%$21,185
AG2-341
7.8 MW1.1%$5,517
AG2-440
29.3 MW4.2%$20,754
AG2-441
36.7 MW5.2%$25,943
AG2-442
41.1 MW5.8%$29,056
AG2-522
9.8 MW1.4%$6,939
AG2-541
8.0 MW1.1%$5,673
AG2-566
10.4 MW1.5%$7,386
AG2-581
36.5 MW5.2%$25,847
AG2-659
10.8 MW1.5%$7,619
AH1-056
33.7 MW4.8%$23,852
AH1-215
8.3 MW1.2%$5,874
AH1-314
6.0 MW0.8%$4,210
AH1-343
9.2 MW1.3%$6,500
AH1-377
63.7 MW9.0%$45,087
AH1-408
11.4 MW1.6%$8,039
AH1-439
44.8 MW6.3%$31,708
AH1-528
73.3 MW10.4%$51,831
AH1-546
49.8 MW7.0%$35,219

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2078
Title
Replace 2-636 ACSR line lead on line 298 at Bremo 230 kV
Description
Replace 2-636 ACSR line lead on line 298 at Bremo 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$5,065
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.3 MW0.6%$2,825
AG2-069
6.5 MW0.8%$4,237
AG2-077
47.9 MW6.2%$31,083
AG2-171
16.0 MW2.1%$10,365
AG2-188
71.8 MW9.3%$46,635
AG2-198
29.4 MW3.8%$19,069
AG2-213
21.3 MW2.8%$13,821
AG2-270
30.0 MW3.9%$19,451
AG2-338
2.8 MW0.4%$1,788
AG2-339
6.9 MW0.9%$4,470
AG2-341
7.8 MW1.0%$5,065
AG2-369
3.7 MW0.5%$2,429
AG2-436
28.6 MW3.7%$18,577
AG2-440
29.3 MW3.8%$19,055
AG2-441
36.7 MW4.8%$23,819
AG2-442
41.1 MW5.3%$26,677
AG2-522
9.8 MW1.3%$6,371
AG2-541
8.0 MW1.0%$5,208
AG2-566
10.4 MW1.4%$6,781
AG2-570
7.3 MW0.9%$4,722
AG2-571
2.9 MW0.4%$1,889
AG2-581
36.5 MW4.7%$23,731
AG2-659
10.8 MW1.4%$6,996
AH1-056
33.7 MW4.4%$21,899
AH1-215
8.3 MW1.1%$5,393
AH1-314
6.0 MW0.8%$3,865
AH1-343
9.2 MW1.2%$5,967
AH1-377
63.7 MW8.3%$41,396
AH1-408
11.4 MW1.5%$7,381
AH1-439
44.8 MW5.8%$29,111
AH1-528
73.3 MW9.5%$47,587
AH1-546
49.8 MW6.5%$32,335

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2076
Title
Replace wave trap 298 WT at Bremo 230 kV
Description
Replace wave trap 298 WT at Bremo 230 kV
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$4,052
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.3 MW0.6%$2,260
AG2-069
6.5 MW0.8%$3,390
AG2-077
47.9 MW6.2%$24,866
AG2-171
16.0 MW2.1%$8,292
AG2-188
71.8 MW9.3%$37,308
AG2-198
29.4 MW3.8%$15,255
AG2-213
21.3 MW2.8%$11,057
AG2-270
30.0 MW3.9%$15,561
AG2-338
2.8 MW0.4%$1,430
AG2-339
6.9 MW0.9%$3,576
AG2-341
7.8 MW1.0%$4,052
AG2-369
3.7 MW0.5%$1,944
AG2-436
28.6 MW3.7%$14,862
AG2-440
29.3 MW3.8%$15,244
AG2-441
36.7 MW4.8%$19,055
AG2-442
41.1 MW5.3%$21,341
AG2-522
9.8 MW1.3%$5,097
AG2-541
8.0 MW1.0%$4,167
AG2-566
10.4 MW1.4%$5,425
AG2-570
7.3 MW0.9%$3,778
AG2-571
2.9 MW0.4%$1,511
AG2-581
36.5 MW4.7%$18,985
AG2-659
10.8 MW1.4%$5,596
AH1-056
33.7 MW4.4%$17,519
AH1-215
8.3 MW1.1%$4,315
AH1-314
6.0 MW0.8%$3,092
AH1-343
9.2 MW1.2%$4,774
AH1-377
63.7 MW8.3%$33,117
AH1-408
11.4 MW1.5%$5,905
AH1-439
44.8 MW5.8%$23,289
AH1-528
73.3 MW9.5%$38,070
AH1-546
49.8 MW6.5%$25,868

System Reinforcement: n6113
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n6113
Title
Add a 2nd new 224 MVA 115/230 kV Transformer at Carolina substation, expand 230 kV station to form a ring bus, add two (2) 230 kV breakers and one (1) 115 kV breaker.
Description
Add a 2nd new 224 MVA 115/230 kV Transformer at Carolina substation, expand 230 kV station to form a ring bus, add two (2) 230 kV breakers and one (1) 115 kV breaker.
Total Cost ($USD)
$11,000,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 44 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer(Any)

System Reinforcement: n6114
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n6114
Title
Add a 2nd 224 MVA 230/115 kV transformer and associated breakers at Clubhouse substation.
Description
Add a 2nd 224 MVA 230/115 kV transformer and associated breakers at Clubhouse substation.
Total Cost ($USD)
$24,500,000
Allocated Cost ($USD)
$0
Time Estimate
Feb 28 2027

Contingent

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 may need this upgrade in-service to be deliverable to the PJM system. If AG2-341 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0011
Title
Replace 795 AAC Line Lead on Line 158 at Farmville 115 kV.
Description
Replace 795 AAC Line Lead on Line 158 at Farmville 115 kV.
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 may need this upgrade in-service to be deliverable to the PJM system. If AG2-341 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
3FARMVIL-3MORAN 115.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0010
Title
Wreck and Rebuild 5.36 miles of 115 kV Line 158 between Farmville and Moran DP with (1) 768.2 ACSS/TW (20/7) "MAUMEE".
Description
Wreck and Rebuild 5.36 miles of 115 kV Line 158 between Farmville and Moran DP with (1) 768.2 ACSS/TW (20/7) "MAUMEE".
Total Cost ($USD)
$17,152,000
Allocated Cost ($USD)
$0
Time Estimate
30 to 36 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 may need this upgrade in-service to be deliverable to the PJM system. If AG2-341 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
3FARMVIL-3MORAN 115.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2027
Title
Replace switches 8434 and 8435 at Farmville 115 kV
Description
Replace switches 8434 and 8435 at Farmville 115 kV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 may need this upgrade in-service to be deliverable to the PJM system. If AG2-341 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
3FARMVIL-3WILLIS 115.0 kV Ckt 1 line(Any)

System Reinforcement: n9643.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9643.0 / TC1-PH3-DOM-009-TC2
Title
Replace 795 AAC 37 line lead at Farmville 115 kV.
Description
Replace 795 AAC 37 line lead at Farmville 115 kV.
Total Cost ($USD)
$391,643
Allocated Cost ($USD)
$0
Time Estimate
Mar 31 2027

Contingent

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 may need this upgrade in-service to be deliverable to the PJM system. If AG2-341 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
3FARMVIL-3WILLIS 115.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0009
Title
Wreck and Rebuild 0.05 miles of 115 kV Line 158 between Flat Creek and Moran DP with (1) 768.2 ACSS/TW (20/7) "MAUMEE".
Description
Wreck and Rebuild 0.05 miles of 115 kV Line 158 between Flat Creek and Moran DP with (1) 768.2 ACSS/TW (20/7) "MAUMEE".
Total Cost ($USD)
$160,000
Allocated Cost ($USD)
$0
Time Estimate
30 to 36 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 may need this upgrade in-service to be deliverable to the PJM system. If AG2-341 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
3FLAT CREEK-3MORAN 115.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending)
Title
DVP Rating: 393/393/452 MVA
Description
DVP Rating: 393/393/452 MVA - Dominion end ratings increased due to s2614
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
3GW KING TAP-3KERR 115.0 kV Ckt 1 line(Any)

System Reinforcement: n7687
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7687 / dom-046-TC2
Title
Add a 3rd 230/115 kV transformer at Sedge Hill Substation and associated breakers (230 kV and 115 kV).
Description
Add a 3rd 230/115 kV transformer at Sedge Hill Substation and associated breakers (230 kV and 115 kV).
Total Cost ($USD)
$10,595,849
Allocated Cost ($USD)
$0
Time Estimate
Jun 01 2029

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer(Any)
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH2-DOM-0012
Title
Wreck and rebuild 8.1 miles of 230 kV Line 2027 (future Line 2323) between Bremo and AG2-583 with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Description
Wreck and rebuild 8.1 miles of 230 kV Line 2027 (future Line 2323) between Bremo and AG2-583 with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Total Cost ($USD)
$30,780,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6BREMO-AG2-583 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2067
Title
Replace 3 1/2" pipe line lead on line 2193 at Bremo 230 kV
Description
Replace 3 1/2" pipe line lead on line 2193 at Bremo 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2065
Title
Replace switches 219324 and 219325 at Bremo 230 kV
Description
Replace switches 219324 and 219325 at Bremo 230 kV
Total Cost ($USD)
$800,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2066
Title
Replace 2-636 ACSR line lead on line 2193 at Bremo 230 kV
Description
Replace 2-636 ACSR line lead on line 2193 at Bremo 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-1031
Title
Wreck and rebuild 12.94 miles of 230 kV Line 235 from Briery to Farmville with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 degrees C.
Description
Wreck and rebuild 12.94 miles of 230 kV Line 235 from Briery to Farmville with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 degrees C.
Total Cost ($USD)
$49,172,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6BRIERY-6FARMVIL 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9376.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9376.0 / TC1-PH3-DOM-003-TC2
Title
Wreck and Rebuild 22.98 miles of 230 kV Line 235 from Briery to AG1-098 with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"" at 250 C.
Description
Wreck and Rebuild 22.98 miles of 230 kV Line 235 from Briery to AG1-098 with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"" at 250 C.
Total Cost ($USD)
$69,323,785
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2029

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6BRIERY-AG2-198 TP 230.0 kV Ckt 1 line(Any)
AG1-098 TP-AH1-377 TP 230.0 kV Ckt 1 line(Any)
AG2-198 TP-AH1-377 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9217.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9217.0 / TC1-PH2-DOM-028
Title
Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.
Total Cost ($USD)
$40,414,822
Allocated Cost ($USD)
$0
Time Estimate
45 to 46 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 may need this upgrade in-service to be deliverable to the PJM system. If AG2-341 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6BUCKING-AH1-439 TP 230.0 kV Ckt 1 line(Any)
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line(Any)
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9220.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9220.0 / TC1-PH2-DOM-033
Title
Wreck and rebuild 15.42 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 15.42 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Total Cost ($USD)
$44,465,922
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 may need this upgrade in-service to be deliverable to the PJM system. If AG2-341 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line(Any)
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3694.8
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3694.8
Title
Partial wreck and rebuild 10.34 miles of 230 kV line #249 Carson-Locks to achieve a minimum summer emergency rating of 1572 MVA.
Description
Partial wreck and rebuild 10.34 miles of 230 kV line #249 Carson-Locks to achieve a minimum summer emergency rating of 1572 MVA. Upgrade terminal equipment at Carson and Locks to not limit the new conductor rating.
Cost Information
Time Estimate
May 03 2025

Not Contingent

Note: AG2-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-341 is not contingent on this baseline upgrade as it is already in-service.

FacilityContingency
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.319
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.319
Title
Reconductor 230kV Line #2002 Carson – Poe. New conductor has a summer rating of 1573 MVA.
Description
Reconductor 230kV Line #2002 Carson – Poe. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Mar 20 2030

Not Contingent

Note: AG2-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6CARSON-6POE 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.320
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.320
Title
At Carson substation, upgrade all line #2002 terminal equipment at Carson to 4000A. CCVTs will also be replaced due to aging.
Description
At Carson substation, upgrade all line #2002 terminal equipment at Carson to 4000A. CCVTs will also be replaced due to aging.
Cost Information
Time Estimate
Mar 20 2030

Not Contingent

Note: AG2-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6CARSON-6POE 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.321
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.321
Title
At Poe substation, upgrade all line #2002 terminal equipment at Carson to 4000A. CCVTs will also be replaced due to aging.
Description
At Poe substation, upgrade all line #2002 terminal equipment at Carson to 4000A. CCVTs will also be replaced due to aging.
Cost Information
Time Estimate
Mar 20 2030

Not Contingent

Note: AG2-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6CARSON-6POE 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9200.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9200.0 / TC1-PH2-DOM-005
Title
Rebuild 11.79 miles of line 238 between Sapony and Carson with twin bundled (2) 768.2 ACSS/TW (20/7) "Maumee" conductors.
Description
Rebuild 11.79 miles of line 238 between Sapony and Carson with twin bundled (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Total Cost ($USD)
$38,691,326
Allocated Cost ($USD)
$0
Time Estimate
45 to 46 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6CARSON-6SAPONY 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9201.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9201.0 / TC1-PH2-DOM-006
Title
Replace wave trap at Carson 230 kV (Carson - Sapony).
Description
Replace wave trap at Carson 230 kV (Carson - Sapony).
Total Cost ($USD)
$521,941
Allocated Cost ($USD)
$0
Time Estimate
14 to 15 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6CARSON-6SAPONY 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9202.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9202.0 / TC1-PH2-DOM-007
Title
Replace Line Switch 23886 at Sapony 230 kV (Carson - Sapony).
Description
Replace Line Switch 23886 at Sapony 230 kV (Carson - Sapony).
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6CARSON-6SAPONY 230.0 kV Ckt 1 line(Any)

System Reinforcement: n8256
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n8256 / dom-277
Title
Wreck and rebuild 5.9 miles of 230 kV Line 2027 (future Line 2323) between Cartersville and AC2-165 (Sallee Creek) with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Description
Wreck and rebuild 5.9 miles of 230 kV Line 2027 (future Line 2323) between Cartersville and AC2-165 (Sallee Creek) with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Total Cost ($USD)
$22,420,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0013
Title
Wreck and rebuild 1.51 miles of 230 kV Line 2027 (future Line 2323) between Cartersville and AG2-583 with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Description
Wreck and rebuild 1.51 miles of 230 kV Line 2027 (future Line 2323) between Cartersville and AG2-583 with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Total Cost ($USD)
$5,738,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6CARTERV-AG2-583 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2072
Title
Replace 2500 ACAR line lead on line 2028 at Charlottesville 230 kV
Description
Replace 2500 ACAR line lead on line 2028 at Charlottesville 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)

System Reinforcement: n7568
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7568 / dom-369-TC2
Title
Wreck and rebuild 6.47 miles of 230 kV transmission line 2028 between Charlottesville and Mt. Eagle with (2) 768.2 ACSS/TW (20/7) ""Maumee"" @ 250C and replace line lead at Mt. Eagle.
Description
Wreck and rebuild 6.47 miles of 230 kV transmission line 2028 between Charlottesville and Mt. Eagle with (2) 768.2 ACSS/TW (20/7) ""Maumee"" @ 250C and replace line lead at Mt. Eagle.
Total Cost ($USD)
$36,802,018
Allocated Cost ($USD)
$0
Time Estimate
43 to 44 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2073
Title
Replace 2-1590 line lead on line 2028 at Charlottesville and Mt Eagle 230 kV
Description
Replace 2-1590 line lead on line 2028 at Charlottesville and Mt Eagle 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH3-DOM-007
Title
Replace Wave Trap 2028WT at Charlottesville
Description
Replace Wave Trap 2028WT at Charlottesville
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$0
Time Estimate
16 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)

System Reinforcement: n6872
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n6872 / dom-047
Title
Wreck and rebuild 15.05 miles of 230 kV line No. 238 between Clubhouse and AE2-033 tap with (2) 768.2 ACSS/TW (20/7) at 250C.
Description
Wreck and rebuild 15.05 miles of 230 kV line No. 238 between Clubhouse and AE2-033 tap with (2) 768.2 ACSS/TW (20/7) at 250C
Total Cost ($USD)
$59,572,939
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2029

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6OTTERDAM-6CLUBHSE 230.0 kV Ckt 1 line(Any)
6ENCLAVE-6OTTERDAM 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9203.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9203.0 / TC1-PH2-DOM-008-TC2
Title
Wreck and rebuild 10.74 miles of line 2028 between Fork Union and Cunningham (Grape Vine) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C.
Description
Wreck and rebuild 10.74 miles of line 2028 between Fork Union and Cunningham (Grape Vine) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C.
Total Cost ($USD)
$29,539,973
Allocated Cost ($USD)
$0
Time Estimate
45 to 46 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6GRAPEVINE-6FORK UNION 230.0 kV Ckt 1 line(Any)

System Reinforcement: n7569
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7569 / dom-490-TC2
Title
Upgrade a 3.78 mile segment of 230kV transmission line 2028 between Mt. Eagle and Grape Vine Substations at structure 2080/73.
Description
Uograde 3.78 miles of transmission line 2028 between Mt. Eagle and Grape Vine with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"". The segment runs from Mt Eagle to structure 2080/73.
Total Cost ($USD)
$13,360,242
Allocated Cost ($USD)
$0
Time Estimate
43 to 44 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9644.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9644.0 / TC1-PH3-DOM-006-TC2
Title
Upgrade a 2.73 mile segment of 230kV transmission line 2028 between Mt. Eagle and Grape Vine. This segment runs from Grape Vine substation to structure 2080/73.
Description
Rebuild a 2.73 mile segment of 230kV line 2028 between Mt. Eagle and Grape Vinew with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @250 degrees C.
Total Cost ($USD)
$8,415,380
Allocated Cost ($USD)
$0
Time Estimate
Mar 31 2029

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9205.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9205.0 / TC1-PH2-DOM-015
Title
Replace Line Switch 23889 at Sapony 230 kV (Sapony - AE2-033 Tap)
Description
Replace Line Switch 23889 at Sapony 230 kV (Sapony - AE2-033 Tap)
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-1032
Title
Wreck and rebuild 0.73 miles of 230 kV line 235 between AG1-098 and Finneywood with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C
Description
Wreck and rebuild 0.73 miles of 230 kV line 235 between AG1-098 and Finneywood with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C
Total Cost ($USD)
$2,774,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6FINNEYWOOD-AG1-098 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9199.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9199.0 / TC1-PH2-DOM-004
Title
Wreck and rebuild 1.63 miles of line 2193 between Fork Union and Bremo with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C and replace line lead at Bremo.
Description
Wreck and rebuild 1.63 miles of line 2193 between Fork Union and Bremo with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C and replace line lead at Bremo.
Total Cost ($USD)
$7,947,612
Allocated Cost ($USD)
$0
Time Estimate
42 to 43 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9198.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9198.0 / TC1-PH2-DOM-003-TC2
Title
Replace Circuit Breaker 219322 and Circuit Breaker Lead at Bremo 230 kV (Bremo - Fork Union).
Description
Replace Circuit Breaker 219322 and Circuit Breaker Lead at Bremo 230 kV (Bremo - Fork Union).
Total Cost ($USD)
$2,113,879
Allocated Cost ($USD)
$0
Time Estimate
40 to 41 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2064
Title
Replace 2-1590 line lead on line 2193 at Fork Union 230 kV
Description
Replace 2-1590 line lead on line 2193 at Fork Union 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2063
Title
Wreck and rebuild 0.11 miles of 230 kV line 2193 between Fork Union and Bremo Dist with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Description
Wreck and rebuild 0.11 miles of 230 kV line 2193 between Fork Union and Bremo Dist with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Total Cost ($USD)
$418,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0080
Title
Replace switch 219326 at Bremo 230 kV
Description
Replace switch 219326 at Bremo 230 kV
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2070
Title
Replace wave trap 2028WT at Fork Union 230 kV
Description
Replace wave trap 2028WT at Fork Union 230 kV
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$0
Time Estimate
16 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6GRAPEVINE-6FORK UNION 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2069
Title
Replace 2-1590 AAC line lead on line 2028 at Fork Union 230 kV
Description
Replace 2-1590 AAC line lead on line 2028 at Fork Union 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6GRAPEVINE-6FORK UNION 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2068
Title
Wreck and rebuild 0.12 miles of 230 kV line 2028 between Fork Union and Grape Vine with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Description
Wreck and rebuild 0.12 miles of 230 kV line 2028 between Fork Union and Grape Vine with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Total Cost ($USD)
$456,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6GRAPEVINE-6FORK UNION 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2071
Title
Replace 2-1590 line lead on line 2028 at Mt. Eagle 230 kV
Description
Replace 2-1590 line lead on line 2028 at Mt. Eagle 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line(Any)

System Reinforcement: n7796
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7796 / dom-302/3
Title
Wreck and rebuild 14.01 miles of 230 kV Line 2027 between Midlothian and Powhatan with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Description
Wreck and rebuild 14.01 miles of 230 kV Line 2027 between Midlothian and Powhatan with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Total Cost ($USD)
$53,238,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0014
Title
Wreck and rebuild 0.17 miles of 230 kV Line 2027 between Midlothian and Powhatan with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Description
Wreck and rebuild 0.17 miles of 230 kV Line 2027 between Midlothian and Powhatan with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Total Cost ($USD)
$646,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6MDLTHAN-6POWHATN 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending)
Title
DVP Rating: 961/961/1106 MVA
Description
DVP Rating: 961/961/1106 MVA
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending)
Title
Dominion work to accomodate new Person - Hendrick 230 kV tie line
Description
Add a breaker to existing three-breaker ring bus at Hendrick and construct 0.93 miles of new 230 kV line between Pesrons - Hendrick
Total Cost ($USD)
$8,894,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 may need this upgrade in-service to be deliverable to the PJM system. If AG2-341 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement: n8243
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n8243 / dom-389
Title
Wreck and rebuild 5.8 miles of 230 kV Line 2027 between AC2-165 (Sallee Creek) and Powhatan with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Description
Wreck and rebuild 5.8 miles of 230 kV Line 2027 between AC2-165 (Sallee Creek) and Powhatan with (2) 768.2 ACSS/TW (20/7) "MAUMEE".
Total Cost ($USD)
$22,040,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6POWHATN-AC2-165 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9204.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9204.0 / TC1-PH2-DOM-014
Title
Wreck and rebuild 1.63 miles of line 238 between AE2-033 tap and Sapony with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 1.63 miles of line 238 between AE2-033 tap and Sapony with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C
Total Cost ($USD)
$6,764,273
Allocated Cost ($USD)
$0
Time Estimate
42 to 43 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6ENCLAVE-6SAPONY 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0045
Title
Wreck and rebuild 8.3 miles of 230 kV Line 2250 between Edmonson and Sedge Hill with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 8.3 miles of 230 kV Line 2250 between Edmonson and Sedge Hill with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$31,540,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)

System Reinforcement: n6215
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n6215
Title
Wreck and rebuild 18.56 miles of 230 kV Line 296 between Sedge Hill and Alton Post (AC1-221) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 18.56 miles of 230 kV Line 296 between Sedge Hill and Alton Post (AC1-221) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$70,528,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0051
Title
Wreck and rebuild 0.003 miles of 230 kV Line 296 between Sedge Hill and Alton Post (AC1-221) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 0.003 miles of 230 kV Line 296 between Sedge Hill and Alton Post (AC1-221) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$11,400
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
6NORTHAMPTON-6CAROLNA 230.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AG2-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
6NORTHAMPTON-6CAROLNA 230.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AG2-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
6NORTHAMPTON-6CAROLNA 230.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
6NORTHAMPTON-6CAROLNA 230.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
6NORTHAMPTON-6CAROLNA 230.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
6NORTHAMPTON-6CAROLNA 230.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
6NORTHAMPTON-6CAROLNA 230.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
6NORTHAMPTON-6CAROLNA 230.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
6NORTHAMPTON-6CAROLNA 230.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AG2-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
6NORTHAMPTON-6CAROLNA 230.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AG2-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
6NORTHAMPTON-6CAROLNA 230.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
6NORTHAMPTON-6CAROLNA 230.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
6NORTHAMPTON-6CAROLNA 230.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AG2-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
6NORTHAMPTON-6CAROLNA 230.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S

System Reinforcement: b4000.355
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
6NORTHAMPTON-6CAROLNA 230.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-341 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-341 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
6NORTHAMPTON-6CAROLNA 230.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-1037
Title
Replace Breaker 56372 at Carson 500 kV with 5000 Amp device
Description
Replace Breaker 56372 at Carson 500 kV with 5000 Amp device
Total Cost ($USD)
$2,750,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-1
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-1036
Title
Wreck and rebuild 37.41 mi of 500 kV line 563 between Carson and Midlothian with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN" at 145 degrees C
Description
Wreck and rebuild 37.41 mi of 500 kV line 563 between Carson and Midlothian with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN" at 145 degrees C
Total Cost ($USD)
$157,122,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: n9139.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9139.0 / TC1-PH1-DOM-073
Title
Wreck and rebuild 37.41 miles of 500kV line 563 between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" and associated substation work.
Description
Wreck and rebuild 37.41 miles of 500kV transmission line 563 between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA. Remove wave traps.
Total Cost ($USD)
$245,455,768
Allocated Cost ($USD)
$0
Time Estimate
69 to 70 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: n9138.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9138.0 / TC1-PH1-DOM-070
Title
Wreck and rebuild 22.59 miles of Line #511 between Carson and Rawlings Substations with three (3) 1351 ACSS/TW and associated substation work.
Description
Wreck and rebuild 22.59 miles of Line 511 between Carson and Rawlings with three (3) 1351 ACSS/TW and associated substation work.
Total Cost ($USD)
$111,130,292
Allocated Cost ($USD)
$0
Time Estimate
60 to 61 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)

System Reinforcement: n9250.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9250.0 / TC1-PH2-DOM-044
Title
Construct a new 22.59 mile line between Carson and Rawlings Substations.
Description
Construct a new 22.59 mile line between Carson and Rawlings Substations.
Total Cost ($USD)
$108,728,086
Allocated Cost ($USD)
$0
Time Estimate
60 to 61 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2091
Title
Replace the existing Finneywood 230/500 kV XFRM T1 with a 3-480 MVA rated device
Description
Replace the existing Finneywood 230/500 kV XFRM T1 with a 3-480 MVA rated device
Total Cost ($USD)
$40,000,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
8FINNEYWOOD-6FINNEYWOOD 500.0/230.0 kV Ckt 1 transformer(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2092
Title
Replace the existing Finneywood 230/500 kV XFRM T2 with a 3-480 MVA rated device
Description
Replace the existing Finneywood 230/500 kV XFRM T2 with a 3-480 MVA rated device
Total Cost ($USD)
$40,000,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
8FINNEYWOOD-6FINNEYWOOD 500.0/230.0 kV Ckt 2 transformer(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2008
Title
Wreck and rebuild 0.47 miles of 230 kV Line 2241 between Hendrick and Alton Post with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 0.47 miles of 230 kV Line 2241 between Hendrick and Alton Post with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$1,786,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-341 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-341 could receive cost allocation. Although AG2-341 may not presently have cost responsibility for this upgrade, AG2-341 is a potential Aggregate Pool Contributor.

FacilityContingency
AC1-221 TAP-AC2-100 TAP 230.0 kV Ckt 1 line(Any)
          AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-440, AG2-441, AG2-442
        
          AG2-068 500 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-068, AG2-069, AG2-369
        
          Perth 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-111, AG2-112
        
          AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-198, AG2-566
        
          AG2-570 500 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-570, AG2-571
        
          AE2-094 500 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-338, AG2-339
        

Attachments

AG2-341 One Line Diagram

AG2-341 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.