AG2-366 Phase I Study Report

v1.00 released 2025-10-29 19:57

Garner Delivery Point - Lancaster 115 kV

20.0 MW Capacity / 50.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Virginia Electric and Power Company (d/b/a) Dominion Energy Virginia, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed a Storage facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — Lancaster County, Virginia. The installed facilities will have a total capability of 50.0 MW with 20.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-366
Project Name:
Garner Delivery Point - Lancaster 115 kV
Project Developer Name:
Virginia Electric and Power Company (d/b/a) Dominion Energy Virginia
State:
Virginia
County:
Lancaster
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
50.0
MWE:
50.0
MWC:
20.0
Battery Storage Specification:
200.0 MWh, 4.0-hr class
Grid Charging:
Yes
Fuel Type:
Storage
Basecase Study Year:
2028

Capacity Interconnection Rights (CIR) Transfer Details

This project intends to claim and transfer CIRs from the following Deactivation capacity generation resources. PJM performed a reliability analysis of the impacts to the system capability for the proposed transfer of CIRs from the Deactivation generation resources.

Unit NameStatusCIR ClaimedPOI Transfer
Possum Point 5Deactivated Generator20.0Yes

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AG2-366 will interconnect on the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) transmission system via a new breaker position in a new interconnection switchyard being constructed for AG1-146/AG1-147 along the Garner DP to Lancaster 115 kV transmission line.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AG2-366 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-366Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$3,200,000$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$2,500,000$2,500,000
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$112,878,868$112,878,868
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$118,578,868$115,378,868

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AG2-366

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AG2-366 Project due at DP1
ABA - B
AG2-366$11,537,887$200,000$11,337,887

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Interconnection Facilities
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Install the Point of Change in Ownership (PCO) disconnect switch, the overhead line conductor from the PCO to the bus position that serves as the Point of Interconnection (POI), as well as any metering and associated protection equipment.$3,200,000 $3,200,000
Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Add one (1) new 115 kV breaker to the planned Garner DP - Lancaster 115 kV AG1-146/AG1-147 Substation. Additional substation modification/expansion cost may be required after detailed design. Projects AG1-146 and AG1-147 will have a seperate POI and will not share interconnection facilities with AG2-366.$2,500,000 $2,500,000

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 36 to 40 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2028 load flow model and the results were verified by Dominion.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-366 was evaluated as a 50.0 MW (20.0 MW Capacity) injection in the Dominion area.

AG2-366 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 50.0 MW (50.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
3GARNER-AE1-155 TAP 115.0 kV Ckt 1 line
DVP_P4-2: 65T1021_SRT-A
BreakerAC114.69 %249.0C285.5719.99
GD2DVP
3GARNER-AE1-155 TAP 115.0 kV Ckt 1 line
DVP_P4-4: LANCAS SC392_SRT-A
BreakerAC114.65 %249.0C285.4819.99
GD2DVP
3GARNER-AE1-155 TAP 115.0 kV Ckt 1 line
DVP_P7-1: LN 2016-85_SRT-A-1
TowerAC108.18 %249.0C269.3612.64
GD2DVP
3GARNER-AE1-155 TAP 115.0 kV Ckt 1 line
DVP_P1-2: LN 65_SRT-A-1
SingleAC107.61 %203.98B219.519.99
GD2DVP
3GREYSPT-3HARMONY 115.0 kV Ckt 1 line
DVP_P4-2: L4T65_SRT-A
BreakerAC123.38 %335.0C413.3319.98
GD2DVP
3GREYSPT-3HARMONY 115.0 kV Ckt 1 line
DVP_P4-2: 6552_SRT-A
BreakerAC123.38 %335.0C413.3319.98
GD2DVP
3GREYSPT-3HARMONY 115.0 kV Ckt 1 line
DVP_P1-2: LN 1059_SRT-A
SingleAC116.8 %269.78B315.0919.98
GD2DVP
3HARMONY-6HARMONY 115.0/230.0 kV Ckt 1 transformer
DVP_P4-2: L4T65_SRT-A
BreakerAC114.53 %249.5C285.769.57
GD2DVP
3HARMONY-6HARMONY 115.0/230.0 kV Ckt 1 transformer
DVP_P4-2: 6552_SRT-A
BreakerAC114.53 %249.5C285.769.57
GD2DVP
3LANCAST-3OCRAN 115.0 kV Ckt 1 line
DVP_P4-2: L4T65_SRT-A
BreakerAC156.61 %269.0C421.2819.98
GD2DVP
3LANCAST-3OCRAN 115.0 kV Ckt 1 line
DVP_P4-2: 6552_SRT-A
BreakerAC156.61 %269.0C421.2819.98
GD2DVP
3LANCAST-3OCRAN 115.0 kV Ckt 1 line
DVP_P1-2: LN 1059_SRT-A
SingleAC145.78 %219.96B320.6719.98
GD2DVP
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer
DVP_P4-3: U52_SRT-A
BreakerAC127.49 %219.8C280.228.21
GD2DVP
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer
DVP_P1-3: 6NORNECK-TX#6_SRT-A
SingleAC118.91 %190.54B226.578.21
GD2DVP
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer
DVP_P4-1: GT52_SRT-A
BreakerAC115.81 %219.8C254.548.21
GD2DVP
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer
DVP_P4-2: 65T1021_SRT-A
BreakerAC107.05 %219.8C235.299.07
GD2DVP
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer
DVP_P4-4: LANCAS SC392_SRT-A
BreakerAC107.02 %219.8C235.239.07
GD2DVP
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
DVP_P4-3: NORTHER H452_SRT-A
BreakerAC141.36 %206.6C292.068.51
GD2DVP
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
DVP_P1-3: 6NORNECK-TX#4_SRT-A
SingleAC133.22 %177.38B236.318.51
GD2DVP
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
DVP_P4-4: LANCAS SC392_SRT-A
BreakerAC131.35 %206.6C271.3710.91
GD2DVP
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
DVP_P4-2: 65T1021_SRT-A
BreakerAC131.33 %206.6C271.3410.91
GD2DVP
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
DVP_P4-5: L4TGT_SRT-A
BreakerAC125.16 %206.6C258.588.51
GD2DVP
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
DVP_P4-4: RAPPAH SR112_SRT-A
BreakerAC122.13 %206.6C252.3110.91
GD2DVP
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
DVP_P1-2: LN 65_SRT-A-1
SingleAC121.19 %177.38B214.9710.91
GD2DVP
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
DVP_P7-1: LN 2016-85_SRT-A-1
TowerAC118.02 %206.6C243.826.9
GD2DVP
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
DVP_P2-2: HARMONY V B2_SRT-A
BusAC111.91 %206.6C231.217.02
GD2DVP
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
DVP_P7-1: LN 2016-85_SRT-A-2
TowerAC105.78 %206.6C218.556.9
GD2DVP
3OCRAN-3WHIT STONE 115.0 kV Ckt 1 line
DVP_P4-2: L4T65_SRT-A
BreakerAC153.79 %269.0C413.6919.98
GD2DVP
3OCRAN-3WHIT STONE 115.0 kV Ckt 1 line
DVP_P4-2: 6552_SRT-A
BreakerAC153.79 %269.0C413.6919.98
GD2DVP
3OCRAN-3WHIT STONE 115.0 kV Ckt 1 line
DVP_P1-2: LN 1059_SRT-A
SingleAC142.85 %219.96B314.2219.98
GD2DVP
3RAPP TR-3GREYSPT 115.0 kV Ckt 1 line
DVP_P4-2: L4T65_SRT-A
BreakerAC141.1 %148.0C208.829.99
GD2DVP
3RAPP TR-3GREYSPT 115.0 kV Ckt 1 line
DVP_P4-2: 6552_SRT-A
BreakerAC141.1 %148.0C208.829.99
GD2DVP
3RAPP TR-3GREYSPT 115.0 kV Ckt 1 line
DVP_P1-2: LN 1059_SRT-A
SingleAC114.8 %139.12B159.719.99
GD2DVP
3RAPP TR-3GREYSPT 115.0 kV Ckt 2 line
DVP_P4-2: L4T65_SRT-A
BreakerAC141.1 %148.0C208.829.99
GD2DVP
3RAPP TR-3GREYSPT 115.0 kV Ckt 2 line
DVP_P4-2: 6552_SRT-A
BreakerAC141.1 %148.0C208.829.99
GD2DVP
3RAPP TR-3GREYSPT 115.0 kV Ckt 2 line
DVP_P1-2: LN 1059_SRT-A
SingleAC114.8 %139.12B159.719.99
GD2DVP
3WAN 89-3WHITEMARSH 115.0 kV Ckt 1 line
DVP_P7-1: LN 2016-85_SRT-A-1
TowerAC118.35 %208.0C246.177.33
GD2DVP
3WHIT STONE-3RAPPAHNCK 115.0 kV Ckt 1 line
DVP_P4-2: L4T65_SRT-A
BreakerAC116.87 %351.0C410.2219.98
GD2DVP
3WHIT STONE-3RAPPAHNCK 115.0 kV Ckt 1 line
DVP_P4-2: 6552_SRT-A
BreakerAC116.87 %351.0C410.2219.98
GD2DVP
3WHITEMARSH-3HAYES89 115.0 kV Ckt 1 line
DVP_P7-1: LN 2016-85_SRT-A-1
TowerAC114.46 %207.0C236.937.33
GD2DVP
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC127.98 %684.0C875.43.79
GD2DVP
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC122.85 %559.3B687.093.66
GD2DVP
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line
DVP_P4-2: 574T575_SRT-S
BreakerAC119.16 %684.0C815.023.69
GD2DVP
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC103.79 %559.3B580.473.68
GD2DVP
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line
DVP_P4-2: H1T574_SRT-S
BreakerAC101.86 %684.0C696.73.66
GD2DVP
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC141.79 %671.0C951.383.79
GD2DVP
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC138.81 %548.02B760.683.66
GD2DVP
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
DVP_P4-2: 574T575_SRT-S
BreakerAC132.27 %671.0C887.513.69
GD2DVP
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC119.94 %548.02B657.283.68
GD2DVP
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
DVP_P4-2: H1T574_SRT-S
BreakerAC115.13 %671.0C772.523.66
GD2DVP
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S
BreakerAC110.91 %671.0C744.213.64
GD2DVP
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
DVP_P4-2: H2T557_SRT-S
BreakerAC109.2 %671.0C732.763.74
GD2DVP
6CHCKAHM-6ELKO 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC110.39 %678.68B749.182.56
GD2DVP
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
DVP_P4-2: 56702_SRT-A
BreakerAC125.13 %1107.0C1385.243.86
GD2DVP
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
DVP_P1-2: LN 567_SRT-A
SingleAC119.77 %935.39B1120.313.86
GD2DVP
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
DVP_P4-2: G2T567_SRT-A
BreakerAC117.33 %1107.0C1298.883.87
GD2DVP
6COMORN-6BIRCHWD 230.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC129.88 %670.0C870.223.79
GD2DVP
6COMORN-6BIRCHWD 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC124.42 %548.02B681.853.66
GD2DVP
6COMORN-6BIRCHWD 230.0 kV Ckt 1 line
DVP_P4-2: 574T575_SRT-S
BreakerAC120.87 %670.0C809.823.69
GD2DVP
6COMORN-6BIRCHWD 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC104.98 %548.02B575.33.68
GD2DVP
6COMORN-6BIRCHWD 230.0 kV Ckt 1 line
DVP_P4-2: H1T574_SRT-S
BreakerAC103.21 %670.0C691.513.66
GD2DVP
6FINES-6FREDBRG 230.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC141.71 %671.0C950.853.79
GD2DVP
6FINES-6FREDBRG 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC138.73 %548.02B760.243.66
GD2DVP
6FINES-6FREDBRG 230.0 kV Ckt 1 line
DVP_P4-2: 574T575_SRT-S
BreakerAC132.2 %671.0C887.043.69
GD2DVP
6FINES-6FREDBRG 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC119.84 %548.02B656.733.68
GD2DVP
6FINES-6FREDBRG 230.0 kV Ckt 1 line
DVP_P4-2: H1T574_SRT-S
BreakerAC115.05 %671.0C771.983.66
GD2DVP
6FINES-6FREDBRG 230.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S
BreakerAC110.84 %671.0C743.723.64
GD2DVP
6FINES-6FREDBRG 230.0 kV Ckt 1 line
DVP_P4-2: H2T557_SRT-S
BreakerAC109.1 %671.0C732.033.74
GD2DVP
6NORNECK-6SANDERS 230.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC115.42 %699.0C806.783.8
GD2DVP
6NORNECK-6SANDERS 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC115.31 %571.52B659.043.67
GD2DVP
6NORNECK-6SANDERS 230.0 kV Ckt 1 line
DVP_P4-2: 574T575_SRT-S
BreakerAC106.01 %699.0C741.023.7
GD2DVP
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC113.39 %699.0C792.633.79
GD2DVP
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC111.12 %571.52B635.053.67
GD2DVP
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line
DVP_P4-2: 574T575_SRT-S
BreakerAC104.65 %699.0C731.513.69
GD2DVP
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC113.69 %699.0C794.663.8
GD2DVP
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC113.11 %571.52B646.443.67
GD2DVP
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line
DVP_P4-2: 574T575_SRT-S
BreakerAC104.3 %699.0C729.053.69
GD2DVP
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC112.58 %699.0C786.973.79
GD2DVP
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC111.62 %571.52B637.963.67
GD2DVP
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line
DVP_P4-2: 574T575_SRT-S
BreakerAC103.93 %699.0C726.473.69
GD2DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P1-2: LN 2083_SRT-S
SingleAC113.74 %2442.12B2777.555.66
GD2DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P1-2: LN 2145_SRT-A-2
SingleAC112.9 %2442.12B2757.115.66
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P7-1: LN 2076-2145_SRT-A-2
TowerAC110.02 %5011.0C5512.935.67
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P7-1: LN 2076-2145_SRT-A-1
TowerAC109.95 %5011.0C5509.425.67
GD2DVP
AD2-074 TAP-AG1-135 TP 115.0 kV Ckt 1 line
DVP_P4-2: 65T1021_SRT-A
BreakerAC102.03 %249.0C254.0419.99
GD2DVP
AD2-074 TAP-AG1-135 TP 115.0 kV Ckt 1 line
DVP_P4-4: LANCAS SC392_SRT-A
BreakerAC102.0 %249.0C253.9819.99
GD2DVP
AD2-074 TAP-AG1-135 TP 115.0 kV Ckt 1 line
DVP_P7-1: LN 2016-85_SRT-A-1
TowerAC100.5 %249.0C250.2512.64
GD2DVP
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
DVP_P4-2: 65T1021_SRT-A
BreakerAC184.88 %249.0C460.3519.98
GD2DVP
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
DVP_P4-4: LANCAS SC392_SRT-A
BreakerAC184.87 %249.0C460.3219.98
GD2DVP
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
DVP_P1-2: LN 65_SRT-A-1
SingleAC175.73 %203.98B358.4619.98
GD2DVP
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
DVP_P4-2: 8962_SRT-A
BreakerAC166.49 %249.0C414.5619.98
GD2DVP
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
DVP_P4-5: L262_SRT-A
BreakerAC166.49 %249.0C414.5619.98
GD2DVP
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
DVP_P4-2: 17662_SRT-A
BreakerAC166.49 %249.0C414.5619.98
GD2DVP
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
DVP_P7-1: LN 2016-85_SRT-A-1
TowerAC165.25 %249.0C411.4812.63
GD2DVP
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
DVP_P1-2: LN 1021_SRT-A
SingleAC155.02 %203.98B316.2119.98
GD2DVP
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
DVP_P2-2: HARMONY V B2_SRT-A
BusAC154.95 %249.0C385.8312.86
GD2DVP
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
DVP_P7-1: LN 2016-85_SRT-A-2
TowerAC144.71 %249.0C360.3212.63
GD2DVP
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
DVP_P2-2: LANEXA B1_SRT-A
BusAC127.12 %249.0C316.529.81
GD2DVP
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
Base Case
SingleAC113.07 %203.98A230.659.27
GD2DVP
AF1-114 TP-6DAHLGREN 230.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC123.86 %699.0C865.753.79
GD2DVP
AF1-114 TP-6DAHLGREN 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC118.84 %571.52B679.23.66
GD2DVP
AF1-114 TP-6DAHLGREN 230.0 kV Ckt 1 line
DVP_P4-2: 574T575_SRT-S
BreakerAC115.42 %699.0C806.793.69
GD2DVP
AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC131.51 %684.0C899.543.79
GD2DVP
AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC127.21 %559.3B711.493.66
GD2DVP
AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line
DVP_P4-2: 574T575_SRT-S
BreakerAC122.7 %684.0C839.283.69
GD2DVP
AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC108.1 %559.3B604.63.68
GD2DVP
AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line
DVP_P4-2: H1T574_SRT-S
BreakerAC105.39 %684.0C720.843.66
GD2DVP
AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S
BreakerAC101.44 %684.0C693.873.64
GD2DVP
AG1-135 TP-3GARNER 115.0 kV Ckt 1 line
DVP_P4-2: 65T1021_SRT-A
BreakerAC121.01 %249.0C301.3119.99
GD2DVP
AG1-135 TP-3GARNER 115.0 kV Ckt 1 line
DVP_P4-4: LANCAS SC392_SRT-A
BreakerAC120.99 %249.0C301.2519.99
GD2DVP
AG1-135 TP-3GARNER 115.0 kV Ckt 1 line
DVP_P1-2: LN 65_SRT-A-1
SingleAC115.34 %203.98B235.2719.99
GD2DVP
AG1-135 TP-3GARNER 115.0 kV Ckt 1 line
DVP_P7-1: LN 2016-85_SRT-A-1
TowerAC114.36 %249.0C284.7512.64
GD2DVP
AG1-135 TP-3GARNER 115.0 kV Ckt 1 line
DVP_P2-2: HARMONY V B2_SRT-A
BusAC103.58 %249.0C257.9212.87
GD2DVP
AG1-135 TP-3GARNER 115.0 kV Ckt 1 line
DVP_P4-2: 8962_SRT-A
BreakerAC103.48 %249.0C257.6619.99
GD2DVP
AG1-135 TP-3GARNER 115.0 kV Ckt 1 line
DVP_P4-2: 17662_SRT-A
BreakerAC103.46 %249.0C257.6219.99
GD2DVP
AG1-135 TP-3GARNER 115.0 kV Ckt 1 line
DVP_P4-5: L262_SRT-A
BreakerAC103.46 %249.0C257.6219.99
GD2DVP
AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
DVP_P4-2: L4T65_SRT-A
BreakerAC183.5 %249.0C456.9319.98
GD2DVP
AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
DVP_P4-2: 6552_SRT-A
BreakerAC183.5 %249.0C456.9319.98
GD2DVP
AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
DVP_P1-2: LN 1059_SRT-A
SingleAC174.07 %203.98B355.0619.98
GD2DVP
AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
DVP_P4-2: 65T1059_SRT-A
BreakerAC119.93 %249.0C298.6219.99
GD2DVP
AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
DVP_P1-2: LN 65_SRT-A-4
SingleAC114.08 %203.98B232.719.99
GD2DVP
AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
DVP_P4-2: 105942_SRT-A
BreakerAC112.09 %249.0C279.0919.99
GD2DVP
AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
DVP_P7-1: LN 224-2208_SRT-S
TowerAC100.26 %249.0C249.6512.35
GD2DVP
AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
DVP_P4-2: 2076T2208_SRT-A
BreakerAC100.23 %249.0C249.5611.58
GD2DVP
AG2-469 TP-6OAKGROV 230.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC116.4 %699.0C813.653.79
GD2DVP
AG2-469 TP-6OAKGROV 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC115.13 %571.52B657.973.67
GD2DVP
AG2-469 TP-6OAKGROV 230.0 kV Ckt 1 line
DVP_P4-2: 574T575_SRT-S
BreakerAC107.7 %699.0C752.833.69

Details for 3GARNER-AE1-155 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 65T1021_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3GARNER-AE1-155 TAP 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 65T1021_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.69 %
Rating:249.0 MVA
Rating Type:C
MVA to Mitigate:285.57
MW Contribution:19.99
Bus #Bus NameTypeMW Contribution
962981AG1-147 GEN
Solar/Wind Harmer
55.278
316487AF1-042 GEN
Solar/Wind Harmer
16.643
961951AG1-038 GEN
Solar/Wind Harmer
16.643
962861AG1-135 GEN
Solar/Wind Harmer
47.381
970575AG2-366 GEN
50/50
19.992
316484AD2-074 GEN
Solar/Wind Harmer
31.807
962971AG1-146 GEN
Solar/Wind Harmer
23.69
970009AG2-005 GEN
Solar/Wind Harmer
15.794
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.023
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.07
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.014
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.105
NYPJM->LTFIMP_NY
CLTF
0.022
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.023

Details for 3GARNER-AE1-155 TAP 115.0 kV Ckt 1 line l/o DVP_P4-4: LANCAS SC392_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3GARNER-AE1-155 TAP 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-4: LANCAS SC392_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.65 %
Rating:249.0 MVA
Rating Type:C
MVA to Mitigate:285.48
MW Contribution:19.99
Bus #Bus NameTypeMW Contribution
970575AG2-366 GEN
50/50
19.992
316484AD2-074 GEN
Solar/Wind Harmer
31.807
962971AG1-146 GEN
Solar/Wind Harmer
23.69
970009AG2-005 GEN
Solar/Wind Harmer
15.794
962981AG1-147 GEN
Solar/Wind Harmer
55.278
961951AG1-038 GEN
Solar/Wind Harmer
16.643
962861AG1-135 GEN
Solar/Wind Harmer
47.381
316487AF1-042 GEN
Solar/Wind Harmer
16.643
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.023
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.07
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.014
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.105
NYPJM->LTFIMP_NY
CLTF
0.022
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.023

Details for 3GARNER-AE1-155 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2016-85_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
3GARNER-AE1-155 TAP 115.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2016-85_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.18 %
Rating:249.0 MVA
Rating Type:C
MVA to Mitigate:269.36
MW Contribution:12.64
Bus #Bus NameTypeMW Contribution
962981AG1-147 GEN
Solar/Wind Harmer
34.948
3141783LANCAST
Solar/Wind Harmer
-0.042
3141783LANCAST
Solar/Wind Harmer
-0.028
3138133OCRAN
Solar/Wind Harmer
-0.02
3141913WHIT STONE
Solar/Wind Harmer
-0.063
315662AE1-191 GEN
Solar/Wind Harmer
6.607
315666AE1-190 GEN
Solar/Wind Harmer
1.652
957601AF2-054 GEN
Solar/Wind Harmer
1.64
3141873WAN 176
Solar/Wind Harmer
-0.011
957831AF2-077 GEN
Solar/Wind Harmer
0.827
3138283WHITEMARSH
Solar/Wind Harmer
0.043
3141813NORNECK
Solar/Wind Helper
0.269
962861AG1-135 GEN
Solar/Wind Harmer
34.61
961951AG1-038 GEN
Solar/Wind Harmer
11.269
3138133OCRAN
Solar/Wind Harmer
-0.039
970575AG2-366 GEN
50/50
12.64
316484AD2-074 GEN
Solar/Wind Harmer
21.536
970009AG2-005 GEN
Solar/Wind Harmer
10.694
962971AG1-146 GEN
Solar/Wind Harmer
14.978
316203AE2-005 GEN
Solar/Wind Harmer
23.11
316280AD1-041 GEN
Solar/Wind Harmer
4.129
316156AD2-030 GEN
Solar/Wind Harmer
1.463
3141873WAN 176
Solar/Wind Harmer
6.504
316404AE1-155 C
Solar/Wind Helper
4.711
316487AF1-042 GEN
Solar/Wind Harmer
11.269
316441AF1-014 GEN
Solar/Wind Harmer
3.695
316077AC2-138 C
Solar/Wind Helper
0.253
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.018
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.054
CPLELTFEXP_CPLE->PJM
CLTF
0.123
MDUPJM->LTFIMP_MDU
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.009
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.221
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.005
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.051
NYPJM->LTFIMP_NY
CLTF
0.07

Details for 3GARNER-AE1-155 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
3GARNER-AE1-155 TAP 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 65_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.61 %
Rating:203.98 MVA
Rating Type:B
MVA to Mitigate:219.5
MW Contribution:19.99
Bus #Bus NameTypeMW Contribution
962861AG1-135 GEN
Solar/Wind Harmer
35.985
962981AG1-147 GEN
Solar/Wind Harmer
41.983
970327AG2-215 GEN
Solar/Wind Harmer
36.905
970575AG2-366 GEN
50/50
19.992
962971AG1-146 GEN
Solar/Wind Harmer
17.993
970009AG2-005 GEN
Solar/Wind Harmer
8.397
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.023
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.07
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.014
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.105
NYPJM->LTFIMP_NY
CLTF
0.022
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.023

Details for 3GREYSPT-3HARMONY 115.0 kV Ckt 1 line l/o DVP_P4-2: L4T65_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3GREYSPT-3HARMONY 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: L4T65_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.38 %
Rating:335.0 MVA
Rating Type:C
MVA to Mitigate:413.33
MW Contribution:19.98
Bus #Bus NameTypeMW Contribution
970575AG2-366 GEN
50/50
19.982
316484AD2-074 GEN
Solar/Wind Harmer
31.791
316404AE1-155 C
Solar/Wind Harmer
24.361
962971AG1-146 GEN
Solar/Wind Harmer
23.678
970009AG2-005 GEN
Solar/Wind Harmer
15.785
3141913WHIT STONE
Solar/Wind Harmer
-0.126
3141783LANCAST
Solar/Wind Harmer
-0.075
3141783LANCAST
Solar/Wind Harmer
-0.05
3138133OCRAN
Solar/Wind Harmer
-0.038
962981AG1-147 GEN
Solar/Wind Harmer
55.249
316487AF1-042 GEN
Solar/Wind Harmer
16.635
958261AF2-120 GEN
Solar/Wind Harmer
48.935
966661AG1-536 GEN
50/50
31.97
961951AG1-038 GEN
Solar/Wind Harmer
16.635
3138133OCRAN
Solar/Wind Harmer
-0.075
962861AG1-135 GEN
Solar/Wind Harmer
47.356
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.051
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.16
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.032
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.238
NYPJM->LTFIMP_NY
CLTF
0.051
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.053

Details for 3GREYSPT-3HARMONY 115.0 kV Ckt 1 line l/o DVP_P4-2: 6552_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3GREYSPT-3HARMONY 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 6552_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.38 %
Rating:335.0 MVA
Rating Type:C
MVA to Mitigate:413.33
MW Contribution:19.98
Bus #Bus NameTypeMW Contribution
970575AG2-366 GEN
50/50
19.982
316484AD2-074 GEN
Solar/Wind Harmer
31.791
316404AE1-155 C
Solar/Wind Harmer
24.361
962971AG1-146 GEN
Solar/Wind Harmer
23.678
970009AG2-005 GEN
Solar/Wind Harmer
15.785
316487AF1-042 GEN
Solar/Wind Harmer
16.635
958261AF2-120 GEN
Solar/Wind Harmer
48.935
3141913WHIT STONE
Solar/Wind Harmer
-0.126
3141783LANCAST
Solar/Wind Harmer
-0.075
3141783LANCAST
Solar/Wind Harmer
-0.05
3138133OCRAN
Solar/Wind Harmer
-0.038
962981AG1-147 GEN
Solar/Wind Harmer
55.249
966661AG1-536 GEN
50/50
31.97
961951AG1-038 GEN
Solar/Wind Harmer
16.635
3138133OCRAN
Solar/Wind Harmer
-0.075
962861AG1-135 GEN
Solar/Wind Harmer
47.356
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.051
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.16
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.032
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.238
NYPJM->LTFIMP_NY
CLTF
0.051
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.053

Details for 3GREYSPT-3HARMONY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1059_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3GREYSPT-3HARMONY 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1059_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.8 %
Rating:269.78 MVA
Rating Type:B
MVA to Mitigate:315.09
MW Contribution:19.98
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
31.97
3138133OCRAN
Solar/Wind Harmer
0.674
962861AG1-135 GEN
Solar/Wind Harmer
35.967
970575AG2-366 GEN
50/50
19.982
316404AE1-155 C
Solar/Wind Harmer
0.253
962971AG1-146 GEN
Solar/Wind Harmer
17.983
970009AG2-005 GEN
Solar/Wind Harmer
8.392
958261AF2-120 GEN
Solar/Wind Harmer
37.166
3141913WHIT STONE
Solar/Wind Harmer
1.123
3141783LANCAST
Solar/Wind Harmer
0.674
3141783LANCAST
Solar/Wind Harmer
0.45
3138133OCRAN
Solar/Wind Harmer
0.337
962981AG1-147 GEN
Solar/Wind Harmer
41.961
970327AG2-215 GEN
Solar/Wind Harmer
36.886
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.051
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.16
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.032
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.238
NYPJM->LTFIMP_NY
CLTF
0.051
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.053

Details for 3HARMONY-6HARMONY 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: L4T65_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3HARMONY-6HARMONY 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: L4T65_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.53 %
Rating:249.5 MVA
Rating Type:C
MVA to Mitigate:285.76
MW Contribution:9.57
Bus #Bus NameTypeMW Contribution
957601AF2-054 GEN
Solar/Wind Harmer
1.81
3141913WHIT STONE
Solar/Wind Harmer
-0.06
3141783LANCAST
Solar/Wind Harmer
-0.036
3141783LANCAST
Solar/Wind Harmer
-0.024
3138133OCRAN
Solar/Wind Harmer
-0.018
3141873WAN 176
Solar/Wind Harmer
-0.012
962981AG1-147 GEN
Solar/Wind Harmer
26.465
315662AE1-191 GEN
Solar/Wind Harmer
5.692
315666AE1-190 GEN
Solar/Wind Harmer
1.423
957831AF2-077 GEN
Solar/Wind Harmer
0.906
3138283WHITEMARSH
Solar/Wind Harmer
0.047
316059AD1-063 C
Solar/Wind Helper
0.533
970575AG2-366 GEN
50/50
9.572
3141843SHACKLE
50/50
1.803
316484AD2-074 GEN
Solar/Wind Harmer
15.228
316404AE1-155 C
Solar/Wind Harmer
11.669
316156AD2-030 GEN
Solar/Wind Harmer
1.615
962971AG1-146 GEN
Solar/Wind Harmer
11.342
3141873WAN 176
Solar/Wind Harmer
7.179
970009AG2-005 GEN
Solar/Wind Harmer
7.562
316280AD1-041 GEN
Solar/Wind Harmer
3.557
316203AE2-005 GEN
Solar/Wind Harmer
15.867
316487AF1-042 GEN
Solar/Wind Harmer
7.968
958261AF2-120 GEN
Solar/Wind Harmer
23.441
316441AF1-014 GEN
Solar/Wind Harmer
2.537
966661AG1-536 GEN
50/50
15.315
3141843SHACKLE
50/50
1.803
961951AG1-038 GEN
Solar/Wind Harmer
7.968
3138133OCRAN
Solar/Wind Harmer
-0.036
962861AG1-135 GEN
Solar/Wind Harmer
22.685
971777AH1-397 GEN
Solar/Wind Harmer
4.393
3141766HARMONY
Solar/Wind Helper
0.106
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.035
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.107
CPLELTFEXP_CPLE->PJM
CLTF
0.053
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.057
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.139
NYPJM->LTFIMP_NY
CLTF
0.067

Details for 3HARMONY-6HARMONY 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 6552_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3HARMONY-6HARMONY 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: 6552_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.53 %
Rating:249.5 MVA
Rating Type:C
MVA to Mitigate:285.76
MW Contribution:9.57
Bus #Bus NameTypeMW Contribution
957601AF2-054 GEN
Solar/Wind Harmer
1.81
3141913WHIT STONE
Solar/Wind Harmer
-0.06
3141783LANCAST
Solar/Wind Harmer
-0.036
3141783LANCAST
Solar/Wind Harmer
-0.024
3138133OCRAN
Solar/Wind Harmer
-0.018
3141873WAN 176
Solar/Wind Harmer
-0.012
962981AG1-147 GEN
Solar/Wind Harmer
26.465
315662AE1-191 GEN
Solar/Wind Harmer
5.692
315666AE1-190 GEN
Solar/Wind Harmer
1.423
957831AF2-077 GEN
Solar/Wind Harmer
0.906
3138283WHITEMARSH
Solar/Wind Harmer
0.047
316059AD1-063 C
Solar/Wind Helper
0.533
316487AF1-042 GEN
Solar/Wind Harmer
7.968
958261AF2-120 GEN
Solar/Wind Harmer
23.441
316441AF1-014 GEN
Solar/Wind Harmer
2.537
966661AG1-536 GEN
50/50
15.315
3141843SHACKLE
50/50
1.803
961951AG1-038 GEN
Solar/Wind Harmer
7.968
3138133OCRAN
Solar/Wind Harmer
-0.036
962861AG1-135 GEN
Solar/Wind Harmer
22.685
971777AH1-397 GEN
Solar/Wind Harmer
4.393
3141766HARMONY
Solar/Wind Helper
0.106
970575AG2-366 GEN
50/50
9.572
3141843SHACKLE
50/50
1.803
316484AD2-074 GEN
Solar/Wind Harmer
15.228
316404AE1-155 C
Solar/Wind Harmer
11.669
316156AD2-030 GEN
Solar/Wind Harmer
1.615
962971AG1-146 GEN
Solar/Wind Harmer
11.342
3141873WAN 176
Solar/Wind Harmer
7.179
970009AG2-005 GEN
Solar/Wind Harmer
7.562
316280AD1-041 GEN
Solar/Wind Harmer
3.557
316203AE2-005 GEN
Solar/Wind Harmer
15.867
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.035
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.107
CPLELTFEXP_CPLE->PJM
CLTF
0.053
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.057
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.139
NYPJM->LTFIMP_NY
CLTF
0.067

Details for 3LANCAST-3OCRAN 115.0 kV Ckt 1 line l/o DVP_P4-2: L4T65_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3LANCAST-3OCRAN 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: L4T65_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:156.61 %
Rating:269.0 MVA
Rating Type:C
MVA to Mitigate:421.28
MW Contribution:19.98
Bus #Bus NameTypeMW Contribution
970575AG2-366 GEN
50/50
19.982
316484AD2-074 GEN
Solar/Wind Harmer
31.792
316404AE1-155 C
Solar/Wind Harmer
24.362
962971AG1-146 GEN
Solar/Wind Harmer
23.679
970009AG2-005 GEN
Solar/Wind Harmer
15.786
316487AF1-042 GEN
Solar/Wind Harmer
16.635
958261AF2-120 GEN
Solar/Wind Harmer
48.937
3141783LANCAST
Solar/Wind Harmer
-0.075
3141783LANCAST
Solar/Wind Harmer
-0.05
962981AG1-147 GEN
Solar/Wind Harmer
55.251
966661AG1-536 GEN
50/50
31.972
961951AG1-038 GEN
Solar/Wind Harmer
16.635
962861AG1-135 GEN
Solar/Wind Harmer
47.358
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.049
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.152
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.031
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.227
NYPJM->LTFIMP_NY
CLTF
0.049
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.051

Details for 3LANCAST-3OCRAN 115.0 kV Ckt 1 line l/o DVP_P4-2: 6552_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3LANCAST-3OCRAN 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 6552_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:156.61 %
Rating:269.0 MVA
Rating Type:C
MVA to Mitigate:421.28
MW Contribution:19.98
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
31.972
961951AG1-038 GEN
Solar/Wind Harmer
16.635
962861AG1-135 GEN
Solar/Wind Harmer
47.358
3141783LANCAST
Solar/Wind Harmer
-0.075
3141783LANCAST
Solar/Wind Harmer
-0.05
962981AG1-147 GEN
Solar/Wind Harmer
55.251
970575AG2-366 GEN
50/50
19.982
316484AD2-074 GEN
Solar/Wind Harmer
31.792
316404AE1-155 C
Solar/Wind Harmer
24.362
962971AG1-146 GEN
Solar/Wind Harmer
23.679
970009AG2-005 GEN
Solar/Wind Harmer
15.786
316487AF1-042 GEN
Solar/Wind Harmer
16.635
958261AF2-120 GEN
Solar/Wind Harmer
48.937
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.049
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.152
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.031
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.227
NYPJM->LTFIMP_NY
CLTF
0.049
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.051

Details for 3LANCAST-3OCRAN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1059_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3LANCAST-3OCRAN 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1059_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:145.78 %
Rating:219.96 MVA
Rating Type:B
MVA to Mitigate:320.67
MW Contribution:19.98
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
31.972
962861AG1-135 GEN
Solar/Wind Harmer
35.968
970575AG2-366 GEN
50/50
19.982
316404AE1-155 C
Solar/Wind Harmer
0.253
962971AG1-146 GEN
Solar/Wind Harmer
17.984
970009AG2-005 GEN
Solar/Wind Harmer
8.393
958261AF2-120 GEN
Solar/Wind Harmer
37.167
3141783LANCAST
Solar/Wind Harmer
0.674
3141783LANCAST
Solar/Wind Harmer
0.45
962981AG1-147 GEN
Solar/Wind Harmer
41.963
970327AG2-215 GEN
Solar/Wind Harmer
36.888
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.049
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.152
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.031
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.227
NYPJM->LTFIMP_NY
CLTF
0.049
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.051

Details for 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-3: U52_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-3: U52_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.49 %
Rating:219.8 MVA
Rating Type:C
MVA to Mitigate:280.22
MW Contribution:8.21
Bus #Bus NameTypeMW Contribution
3141813NORNECK
Solar/Wind Harmer
-0.093
962981AG1-147 GEN
Solar/Wind Harmer
22.691
3141783LANCAST
Solar/Wind Harmer
-0.023
3141783LANCAST
Solar/Wind Harmer
-0.015
3138133OCRAN
Solar/Wind Harmer
-0.01
3141913WHIT STONE
Solar/Wind Harmer
-0.03
957601AF2-054 GEN
Solar/Wind Harmer
0.557
3141873WAN 176
Solar/Wind Harmer
-0.004
315662AE1-191 GEN
Solar/Wind Harmer
1.771
315666AE1-190 GEN
Solar/Wind Harmer
0.443
957831AF2-077 GEN
Solar/Wind Harmer
0.284
3138283WHITEMARSH
Solar/Wind Harmer
0.015
316059AD1-063 C
Solar/Wind Harmer
0.181
3150351NORNECKC2
50/50
8.933
970575AG2-366 GEN
50/50
8.207
316404AE1-155 C
Solar/Wind Harmer
13.801
316484AD2-074 GEN
Solar/Wind Harmer
14.948
970009AG2-005 GEN
Solar/Wind Harmer
7.422
962971AG1-146 GEN
Solar/Wind Harmer
9.725
316156AD2-030 GEN
Solar/Wind Harmer
0.497
3141873WAN 176
Solar/Wind Harmer
2.209
316280AD1-041 GEN
Solar/Wind Harmer
1.107
316203AE2-005 GEN
Solar/Wind Harmer
4.998
3141843SHACKLE
Adder
0.535
3141766HARMONY
Solar/Wind Harmer
0.715
3150341NORNECKC1
50/50
9.228
3150341NORNECKC1
50/50
9.154
963611AG1-210 GEN
50/50
2.953
316077AC2-138 C
Solar/Wind Harmer
1.968
958261AF2-120 GEN
Solar/Wind Harmer
27.723
316487AF1-042 GEN
Solar/Wind Harmer
7.822
316441AF1-014 GEN
Solar/Wind Harmer
0.799
3150351NORNECKC2
50/50
8.785
966661AG1-536 GEN
50/50
18.112
962861AG1-135 GEN
Solar/Wind Harmer
25.621
961951AG1-038 GEN
Solar/Wind Harmer
7.822
3138133OCRAN
Solar/Wind Harmer
-0.019
971777AH1-397 GEN
Solar/Wind Harmer
1.384
3141843SHACKLE
Adder
0.535
3141766HARMONY
Solar/Wind Harmer
-0.002
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.021
CPLELTFEXP_CPLE->PJM
CLTF
0.072
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.063
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.119
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.074
NYPJM->LTFIMP_NY
CLTF
0.063

Details for 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6NORNECK-TX#6_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-3: 6NORNECK-TX#6_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.91 %
Rating:190.54 MVA
Rating Type:B
MVA to Mitigate:226.57
MW Contribution:8.21
Bus #Bus NameTypeMW Contribution
3150341NORNECKC1
50/50
9.228
3150341NORNECKC1
50/50
9.154
963611AG1-210 GEN
50/50
2.953
316077AC2-138 C
Solar/Wind Harmer
0.004
958261AF2-120 GEN
Solar/Wind Harmer
21.056
3150351NORNECKC2
50/50
8.933
970575AG2-366 GEN
50/50
8.207
3141843SHACKLE
50/50
0.568
315749AE2-041 GEN
50/50
2.541
316404AE1-155 C
Solar/Wind Harmer
0.143
970009AG2-005 GEN
Solar/Wind Harmer
3.946
962971AG1-146 GEN
Solar/Wind Harmer
7.386
316156AD2-030 GEN
Solar/Wind Harmer
0.123
3141873WAN 176
Solar/Wind Harmer
2.946
316280AD1-041 GEN
Solar/Wind Harmer
0.003
316203AE2-005 GEN
Solar/Wind Harmer
0
3141766HARMONY
Solar/Wind Harmer
0.953
3150351NORNECKC2
50/50
8.785
966661AG1-536 GEN
50/50
18.112
3141843SHACKLE
50/50
0.568
962861AG1-135 GEN
Solar/Wind Harmer
19.459
3138133OCRAN
Solar/Wind Harmer
0.174
971777AH1-397 GEN
Solar/Wind Harmer
0.277
3141766HARMONY
Solar/Wind Harmer
0.014
315759AF1-018 GEN
50/50
2.541
3141813NORNECK
Solar/Wind Harmer
0.83
970327AG2-215 GEN
Solar/Wind Harmer
17.344
962981AG1-147 GEN
Solar/Wind Harmer
17.234
3141783LANCAST
Solar/Wind Harmer
0.208
3141783LANCAST
Solar/Wind Harmer
0.139
3138133OCRAN
Solar/Wind Harmer
0.087
3141913WHIT STONE
Solar/Wind Harmer
0.265
3141873WAN 176
Solar/Wind Harmer
0.033
315662AE1-191 GEN
Solar/Wind Harmer
0.004
315666AE1-190 GEN
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
3.127
3138283WHITEMARSH
Solar/Wind Harmer
0.02
316059AD1-063 C
Solar/Wind Harmer
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.021
CPLELTFEXP_CPLE->PJM
CLTF
0.072
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.063
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.119
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.074
NYPJM->LTFIMP_NY
CLTF
0.063

Details for 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-1: GT52_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-1: GT52_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.81 %
Rating:219.8 MVA
Rating Type:C
MVA to Mitigate:254.54
MW Contribution:8.21
Bus #Bus NameTypeMW Contribution
3141813NORNECK
Solar/Wind Harmer
-0.093
962981AG1-147 GEN
Solar/Wind Harmer
22.691
3141783LANCAST
Solar/Wind Harmer
-0.023
3141783LANCAST
Solar/Wind Harmer
-0.015
3138133OCRAN
Solar/Wind Harmer
-0.01
3141913WHIT STONE
Solar/Wind Harmer
-0.03
957601AF2-054 GEN
Solar/Wind Harmer
0.557
3141873WAN 176
Solar/Wind Harmer
-0.004
315662AE1-191 GEN
Solar/Wind Harmer
1.771
315666AE1-190 GEN
Solar/Wind Harmer
0.443
957831AF2-077 GEN
Solar/Wind Harmer
0.284
3138283WHITEMARSH
Solar/Wind Harmer
0.015
316059AD1-063 C
Solar/Wind Harmer
0.181
970575AG2-366 GEN
50/50
8.207
316404AE1-155 C
Solar/Wind Harmer
13.801
316484AD2-074 GEN
Solar/Wind Harmer
14.948
970009AG2-005 GEN
Solar/Wind Harmer
7.422
962971AG1-146 GEN
Solar/Wind Harmer
9.725
316156AD2-030 GEN
Solar/Wind Harmer
0.497
3141873WAN 176
Solar/Wind Harmer
2.209
316280AD1-041 GEN
Solar/Wind Harmer
1.107
316203AE2-005 GEN
Solar/Wind Harmer
4.998
3141843SHACKLE
Adder
0.535
3141766HARMONY
Solar/Wind Harmer
0.715
963611AG1-210 GEN
50/50
2.953
316077AC2-138 C
Solar/Wind Harmer
1.968
958261AF2-120 GEN
Solar/Wind Harmer
27.723
316487AF1-042 GEN
Solar/Wind Harmer
7.822
316441AF1-014 GEN
Solar/Wind Harmer
0.799
966661AG1-536 GEN
50/50
18.112
962861AG1-135 GEN
Solar/Wind Harmer
25.621
961951AG1-038 GEN
Solar/Wind Harmer
7.822
3138133OCRAN
Solar/Wind Harmer
-0.019
971777AH1-397 GEN
Solar/Wind Harmer
1.384
3141843SHACKLE
Adder
0.535
3141766HARMONY
Solar/Wind Harmer
-0.002
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.021
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.063
CPLELTFEXP_CPLE->PJM
CLTF
0.072
MDUPJM->LTFIMP_MDU
CLTF
0
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.119
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.074
NYPJM->LTFIMP_NY
CLTF
0.063

Details for 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 65T1021_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: 65T1021_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.05 %
Rating:219.8 MVA
Rating Type:C
MVA to Mitigate:235.29
MW Contribution:9.07
Bus #Bus NameTypeMW Contribution
970575AG2-366 GEN
50/50
9.07
3150351NORNECKC2
50/50
5.488
316484AD2-074 GEN
Solar/Wind Harmer
14.431
316404AE1-155 C
Solar/Wind Harmer
11.058
962971AG1-146 GEN
Solar/Wind Harmer
10.748
970009AG2-005 GEN
Solar/Wind Harmer
7.166
3141813NORNECK
Solar/Wind Harmer
-0.057
962981AG1-147 GEN
Solar/Wind Harmer
25.079
3150341NORNECKC1
50/50
5.669
3150341NORNECKC1
50/50
5.624
963611AG1-210 GEN
50/50
1.814
316487AF1-042 GEN
Solar/Wind Harmer
7.551
316077AC2-138 C
Solar/Wind Harmer
1.209
958261AF2-120 GEN
Solar/Wind Harmer
22.213
966661AG1-536 GEN
50/50
14.512
3150351NORNECKC2
50/50
5.397
961951AG1-038 GEN
Solar/Wind Harmer
7.551
962861AG1-135 GEN
Solar/Wind Harmer
21.497
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.023
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.073
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.015
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.109
NYPJM->LTFIMP_NY
CLTF
0.023
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.024

Details for 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-4: LANCAS SC392_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-4: LANCAS SC392_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.02 %
Rating:219.8 MVA
Rating Type:C
MVA to Mitigate:235.23
MW Contribution:9.07
Bus #Bus NameTypeMW Contribution
970575AG2-366 GEN
50/50
9.07
3150351NORNECKC2
50/50
5.488
316484AD2-074 GEN
Solar/Wind Harmer
14.431
316404AE1-155 C
Solar/Wind Harmer
11.058
962971AG1-146 GEN
Solar/Wind Harmer
10.748
970009AG2-005 GEN
Solar/Wind Harmer
7.166
3141813NORNECK
Solar/Wind Harmer
-0.057
962981AG1-147 GEN
Solar/Wind Harmer
25.079
3150341NORNECKC1
50/50
5.669
3150341NORNECKC1
50/50
5.624
963611AG1-210 GEN
50/50
1.814
316487AF1-042 GEN
Solar/Wind Harmer
7.551
316077AC2-138 C
Solar/Wind Harmer
1.209
958261AF2-120 GEN
Solar/Wind Harmer
22.213
966661AG1-536 GEN
50/50
14.512
3150351NORNECKC2
50/50
5.397
961951AG1-038 GEN
Solar/Wind Harmer
7.551
962861AG1-135 GEN
Solar/Wind Harmer
21.497
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.023
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.073
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.015
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.109
NYPJM->LTFIMP_NY
CLTF
0.023
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.024

Details for 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-3: NORTHER H452_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-3: NORTHER H452_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:141.36 %
Rating:206.6 MVA
Rating Type:C
MVA to Mitigate:292.06
MW Contribution:8.51
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
9.107
966661AG1-536 GEN
50/50
18.775
962861AG1-135 GEN
Solar/Wind Harmer
26.558
961951AG1-038 GEN
Solar/Wind Harmer
8.108
3138133OCRAN
Solar/Wind Harmer
-0.02
971777AH1-397 GEN
Solar/Wind Harmer
1.435
3141843SHACKLE
Adder
0.555
3141766HARMONY
Solar/Wind Harmer
-0.002
316337AD2-073 GEN
Solar/Wind Helper
0.174
3141813NORNECK
Solar/Wind Harmer
-0.096
962981AG1-147 GEN
Solar/Wind Harmer
23.522
3141783LANCAST
Solar/Wind Harmer
-0.024
3141783LANCAST
Solar/Wind Harmer
-0.016
3138133OCRAN
Solar/Wind Harmer
-0.01
3141913WHIT STONE
Solar/Wind Harmer
-0.031
957601AF2-054 GEN
Solar/Wind Harmer
0.577
3141873WAN 176
Solar/Wind Harmer
-0.004
315662AE1-191 GEN
Solar/Wind Harmer
1.836
315666AE1-190 GEN
Solar/Wind Harmer
0.459
957831AF2-077 GEN
Solar/Wind Harmer
0.294
3138283WHITEMARSH
Solar/Wind Harmer
0.015
316059AD1-063 C
Solar/Wind Harmer
0.188
3150351NORNECKC2
50/50
9.26
970575AG2-366 GEN
50/50
8.507
316404AE1-155 C
Solar/Wind Harmer
14.306
316484AD2-074 GEN
Solar/Wind Harmer
15.495
970009AG2-005 GEN
Solar/Wind Harmer
7.694
962971AG1-146 GEN
Solar/Wind Harmer
10.081
316156AD2-030 GEN
Solar/Wind Harmer
0.515
3141873WAN 176
Solar/Wind Harmer
2.29
316280AD1-041 GEN
Solar/Wind Harmer
1.147
316203AE2-005 GEN
Solar/Wind Harmer
5.181
3141843SHACKLE
Adder
0.555
3141766HARMONY
Solar/Wind Harmer
0.741
3150341NORNECKC1
50/50
9.566
3150341NORNECKC1
50/50
9.49
963611AG1-210 GEN
50/50
3.061
316077AC2-138 C
Solar/Wind Harmer
2.04
958261AF2-120 GEN
Solar/Wind Harmer
28.738
316487AF1-042 GEN
Solar/Wind Harmer
8.108
316441AF1-014 GEN
Solar/Wind Harmer
0.828
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.021
CPLELTFEXP_CPLE->PJM
CLTF
0.075
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.066
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.123
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.077
NYPJM->LTFIMP_NY
CLTF
0.065

Details for 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6NORNECK-TX#4_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-3: 6NORNECK-TX#4_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.22 %
Rating:177.38 MVA
Rating Type:B
MVA to Mitigate:236.31
MW Contribution:8.51
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
9.26
970575AG2-366 GEN
50/50
8.507
3141843SHACKLE
50/50
0.589
315749AE2-041 GEN
50/50
2.634
316404AE1-155 C
Solar/Wind Harmer
0.149
970009AG2-005 GEN
Solar/Wind Harmer
4.091
962971AG1-146 GEN
Solar/Wind Harmer
7.656
316156AD2-030 GEN
Solar/Wind Harmer
0.127
3141873WAN 176
Solar/Wind Harmer
3.054
316280AD1-041 GEN
Solar/Wind Harmer
0.003
316203AE2-005 GEN
Solar/Wind Harmer
0
3141766HARMONY
Solar/Wind Harmer
0.988
315759AF1-018 GEN
50/50
2.634
3141813NORNECK
Solar/Wind Harmer
0.86
970327AG2-215 GEN
Solar/Wind Harmer
17.979
962981AG1-147 GEN
Solar/Wind Harmer
17.865
3141783LANCAST
Solar/Wind Harmer
0.216
3141783LANCAST
Solar/Wind Harmer
0.144
3138133OCRAN
Solar/Wind Harmer
0.09
3141913WHIT STONE
Solar/Wind Harmer
0.274
3141873WAN 176
Solar/Wind Harmer
0.034
315662AE1-191 GEN
Solar/Wind Harmer
0.004
315666AE1-190 GEN
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
3.241
3138283WHITEMARSH
Solar/Wind Harmer
0.02
316059AD1-063 C
Solar/Wind Harmer
0
3150341NORNECKC1
50/50
9.566
3150341NORNECKC1
50/50
9.49
963611AG1-210 GEN
50/50
3.061
316077AC2-138 C
Solar/Wind Harmer
0.005
958261AF2-120 GEN
Solar/Wind Harmer
21.826
3150351NORNECKC2
50/50
9.107
966661AG1-536 GEN
50/50
18.775
3141843SHACKLE
50/50
0.589
962861AG1-135 GEN
Solar/Wind Harmer
20.171
3138133OCRAN
Solar/Wind Harmer
0.18
971777AH1-397 GEN
Solar/Wind Harmer
0.287
3141766HARMONY
Solar/Wind Harmer
0.015
316337AD2-073 GEN
Solar/Wind Helper
0.174
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.021
CPLELTFEXP_CPLE->PJM
CLTF
0.075
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.066
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.123
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.077
NYPJM->LTFIMP_NY
CLTF
0.065

Details for 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-4: LANCAS SC392_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-4: LANCAS SC392_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.35 %
Rating:206.6 MVA
Rating Type:C
MVA to Mitigate:271.37
MW Contribution:10.91
Bus #Bus NameTypeMW Contribution
970575AG2-366 GEN
50/50
10.911
3150351NORNECKC2
50/50
6.601
316484AD2-074 GEN
Solar/Wind Harmer
17.36
316404AE1-155 C
Solar/Wind Harmer
13.303
962971AG1-146 GEN
Solar/Wind Harmer
12.93
970009AG2-005 GEN
Solar/Wind Harmer
8.62
3150341NORNECKC1
50/50
6.819
3150341NORNECKC1
50/50
6.765
963611AG1-210 GEN
50/50
2.182
316487AF1-042 GEN
Solar/Wind Harmer
9.084
316077AC2-138 C
Solar/Wind Harmer
1.454
958261AF2-120 GEN
Solar/Wind Harmer
26.721
3141813NORNECK
Solar/Wind Harmer
-0.069
962981AG1-147 GEN
Solar/Wind Harmer
30.169
966661AG1-536 GEN
50/50
17.458
3150351NORNECKC2
50/50
6.492
961951AG1-038 GEN
Solar/Wind Harmer
9.084
962861AG1-135 GEN
Solar/Wind Harmer
25.859
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.028
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.088
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.018
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.131
NYPJM->LTFIMP_NY
CLTF
0.028
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.029

Details for 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 65T1021_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-2: 65T1021_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.33 %
Rating:206.6 MVA
Rating Type:C
MVA to Mitigate:271.34
MW Contribution:10.91
Bus #Bus NameTypeMW Contribution
3141813NORNECK
Solar/Wind Harmer
-0.069
962981AG1-147 GEN
Solar/Wind Harmer
30.169
970575AG2-366 GEN
50/50
10.911
3150351NORNECKC2
50/50
6.601
316484AD2-074 GEN
Solar/Wind Harmer
17.36
316404AE1-155 C
Solar/Wind Harmer
13.303
962971AG1-146 GEN
Solar/Wind Harmer
12.93
970009AG2-005 GEN
Solar/Wind Harmer
8.62
966661AG1-536 GEN
50/50
17.458
3150351NORNECKC2
50/50
6.492
961951AG1-038 GEN
Solar/Wind Harmer
9.084
962861AG1-135 GEN
Solar/Wind Harmer
25.859
3150341NORNECKC1
50/50
6.819
3150341NORNECKC1
50/50
6.765
963611AG1-210 GEN
50/50
2.182
316487AF1-042 GEN
Solar/Wind Harmer
9.084
316077AC2-138 C
Solar/Wind Harmer
1.454
958261AF2-120 GEN
Solar/Wind Harmer
26.721
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.028
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.088
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.018
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.131
NYPJM->LTFIMP_NY
CLTF
0.028
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.029

Details for 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-5: L4TGT_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-5: L4TGT_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.16 %
Rating:206.6 MVA
Rating Type:C
MVA to Mitigate:258.58
MW Contribution:8.51
Bus #Bus NameTypeMW Contribution
970575AG2-366 GEN
50/50
8.507
316404AE1-155 C
Solar/Wind Harmer
14.306
316484AD2-074 GEN
Solar/Wind Harmer
15.495
970009AG2-005 GEN
Solar/Wind Harmer
7.694
962971AG1-146 GEN
Solar/Wind Harmer
10.081
316156AD2-030 GEN
Solar/Wind Harmer
0.515
3141873WAN 176
Solar/Wind Harmer
2.29
316280AD1-041 GEN
Solar/Wind Harmer
1.147
316203AE2-005 GEN
Solar/Wind Harmer
5.181
3141843SHACKLE
Adder
0.555
3141766HARMONY
Solar/Wind Harmer
0.741
963611AG1-210 GEN
50/50
3.061
316077AC2-138 C
Solar/Wind Harmer
2.04
958261AF2-120 GEN
Solar/Wind Harmer
28.738
316487AF1-042 GEN
Solar/Wind Harmer
8.108
316441AF1-014 GEN
Solar/Wind Harmer
0.828
3141813NORNECK
Solar/Wind Harmer
-0.096
962981AG1-147 GEN
Solar/Wind Harmer
23.522
3141783LANCAST
Solar/Wind Harmer
-0.024
3141783LANCAST
Solar/Wind Harmer
-0.016
3138133OCRAN
Solar/Wind Harmer
-0.01
3141913WHIT STONE
Solar/Wind Harmer
-0.031
957601AF2-054 GEN
Solar/Wind Harmer
0.577
3141873WAN 176
Solar/Wind Harmer
-0.004
315662AE1-191 GEN
Solar/Wind Harmer
1.836
315666AE1-190 GEN
Solar/Wind Harmer
0.459
957831AF2-077 GEN
Solar/Wind Harmer
0.294
3138283WHITEMARSH
Solar/Wind Harmer
0.015
316059AD1-063 C
Solar/Wind Harmer
0.188
966661AG1-536 GEN
50/50
18.775
962861AG1-135 GEN
Solar/Wind Harmer
26.558
961951AG1-038 GEN
Solar/Wind Harmer
8.108
3138133OCRAN
Solar/Wind Harmer
-0.02
971777AH1-397 GEN
Solar/Wind Harmer
1.435
3141843SHACKLE
Adder
0.555
3141766HARMONY
Solar/Wind Harmer
-0.002
316337AD2-073 GEN
Solar/Wind Helper
0.174
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.021
CPLELTFEXP_CPLE->PJM
CLTF
0.075
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.066
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.123
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.077
NYPJM->LTFIMP_NY
CLTF
0.065

Details for 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-4: RAPPAH SR112_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-4: RAPPAH SR112_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.13 %
Rating:206.6 MVA
Rating Type:C
MVA to Mitigate:252.31
MW Contribution:10.91
Bus #Bus NameTypeMW Contribution
970575AG2-366 GEN
50/50
10.91
3150351NORNECKC2
50/50
6.601
316484AD2-074 GEN
Solar/Wind Harmer
17.359
316404AE1-155 C
Solar/Wind Harmer
13.302
962971AG1-146 GEN
Solar/Wind Harmer
12.929
970009AG2-005 GEN
Solar/Wind Harmer
8.619
3150341NORNECKC1
50/50
6.819
3150341NORNECKC1
50/50
6.764
963611AG1-210 GEN
50/50
2.182
316487AF1-042 GEN
Solar/Wind Harmer
9.083
316077AC2-138 C
Solar/Wind Harmer
1.454
958261AF2-120 GEN
Solar/Wind Harmer
26.72
3141813NORNECK
Solar/Wind Harmer
-0.069
3141913WHIT STONE
Solar/Wind Harmer
-0.069
3141783LANCAST
Solar/Wind Harmer
-0.041
3141783LANCAST
Solar/Wind Harmer
-0.027
3138133OCRAN
Solar/Wind Harmer
-0.021
962981AG1-147 GEN
Solar/Wind Harmer
30.167
966661AG1-536 GEN
50/50
17.457
3150351NORNECKC2
50/50
6.492
961951AG1-038 GEN
Solar/Wind Harmer
9.083
3138133OCRAN
Solar/Wind Harmer
-0.041
962861AG1-135 GEN
Solar/Wind Harmer
25.858
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.03
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.094
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.019
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.14
NYPJM->LTFIMP_NY
CLTF
0.03
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.031

Details for 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 65_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-2: LN 65_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.19 %
Rating:177.38 MVA
Rating Type:B
MVA to Mitigate:214.97
MW Contribution:10.91
Bus #Bus NameTypeMW Contribution
970575AG2-366 GEN
50/50
10.911
3150351NORNECKC2
50/50
6.601
316404AE1-155 C
Solar/Wind Harmer
0.138
962971AG1-146 GEN
Solar/Wind Harmer
9.82
970009AG2-005 GEN
Solar/Wind Harmer
4.583
3141813NORNECK
Solar/Wind Harmer
0.613
962981AG1-147 GEN
Solar/Wind Harmer
22.913
970327AG2-215 GEN
Solar/Wind Harmer
20.142
3150341NORNECKC1
50/50
6.819
3150341NORNECKC1
50/50
6.765
963611AG1-210 GEN
50/50
2.182
316077AC2-138 C
Solar/Wind Harmer
0.003
958261AF2-120 GEN
Solar/Wind Harmer
20.295
966661AG1-536 GEN
50/50
17.458
3150351NORNECKC2
50/50
6.492
962861AG1-135 GEN
Solar/Wind Harmer
19.64
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.028
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.088
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.018
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.131
NYPJM->LTFIMP_NY
CLTF
0.028
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.029

Details for 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer l/o DVP_P7-1: LN 2016-85_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P7-1: LN 2016-85_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:118.02 %
Rating:206.6 MVA
Rating Type:C
MVA to Mitigate:243.82
MW Contribution:6.9
Bus #Bus NameTypeMW Contribution
3141813NORNECK
Solar/Wind Harmer
-0.06
962981AG1-147 GEN
Solar/Wind Harmer
19.068
3141783LANCAST
Solar/Wind Harmer
-0.023
3141783LANCAST
Solar/Wind Harmer
-0.015
3138133OCRAN
Solar/Wind Harmer
-0.011
3141913WHIT STONE
Solar/Wind Harmer
-0.034
315662AE1-191 GEN
Solar/Wind Harmer
3.604
315666AE1-190 GEN
Solar/Wind Harmer
0.901
957601AF2-054 GEN
Solar/Wind Harmer
0.894
3141873WAN 176
Solar/Wind Harmer
-0.006
957831AF2-077 GEN
Solar/Wind Harmer
0.45
3138283WHITEMARSH
Solar/Wind Harmer
0.023
3150341NORNECKC1
50/50
5.998
3150341NORNECKC1
50/50
5.95
963611AG1-210 GEN
50/50
1.919
316077AC2-138 C
Solar/Wind Harmer
1.279
958261AF2-120 GEN
Solar/Wind Harmer
20.029
316487AF1-042 GEN
Solar/Wind Harmer
6.149
316441AF1-014 GEN
Solar/Wind Harmer
2.015
3150351NORNECKC2
50/50
5.806
970575AG2-366 GEN
50/50
6.896
316404AE1-155 C
Solar/Wind Harmer
9.971
316484AD2-074 GEN
Solar/Wind Harmer
11.751
970009AG2-005 GEN
Solar/Wind Harmer
5.835
962971AG1-146 GEN
Solar/Wind Harmer
8.172
316203AE2-005 GEN
Solar/Wind Harmer
12.604
316280AD1-041 GEN
Solar/Wind Harmer
2.252
316156AD2-030 GEN
Solar/Wind Harmer
0.798
3141873WAN 176
Solar/Wind Harmer
3.547
3150351NORNECKC2
50/50
5.71
966661AG1-536 GEN
50/50
13.086
962861AG1-135 GEN
Solar/Wind Harmer
18.886
961951AG1-038 GEN
Solar/Wind Harmer
6.149
3138133OCRAN
Solar/Wind Harmer
-0.021
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.026
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.079
CPLELTFEXP_CPLE->PJM
CLTF
0.04
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.046
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.102
NYPJM->LTFIMP_NY
CLTF
0.054

Details for 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer l/o DVP_P2-2: HARMONY V B2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P2-2: HARMONY V B2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:111.91 %
Rating:206.6 MVA
Rating Type:C
MVA to Mitigate:231.21
MW Contribution:7.02
Bus #Bus NameTypeMW Contribution
3141813NORNECK
Solar/Wind Harmer
-0.061
962981AG1-147 GEN
Solar/Wind Harmer
19.417
3141783LANCAST
Solar/Wind Harmer
-0.023
3141783LANCAST
Solar/Wind Harmer
-0.015
3138133OCRAN
Solar/Wind Harmer
-0.011
3141913WHIT STONE
Solar/Wind Harmer
-0.035
315662AE1-191 GEN
Solar/Wind Harmer
2.922
315666AE1-190 GEN
Solar/Wind Harmer
0.731
3150341NORNECKC1
50/50
6.076
3150341NORNECKC1
50/50
6.027
963611AG1-210 GEN
50/50
1.944
316077AC2-138 C
Solar/Wind Harmer
1.296
958261AF2-120 GEN
Solar/Wind Harmer
20.335
316487AF1-042 GEN
Solar/Wind Harmer
6.253
316441AF1-014 GEN
Solar/Wind Harmer
1.32
3150351NORNECKC2
50/50
5.784
966661AG1-536 GEN
50/50
13.286
3141843SHACKLE
50/50
0.938
962861AG1-135 GEN
Solar/Wind Harmer
19.182
961951AG1-038 GEN
Solar/Wind Harmer
6.253
3138133OCRAN
Solar/Wind Harmer
-0.022
971777AH1-397 GEN
Solar/Wind Harmer
2.287
3150351NORNECKC2
50/50
5.881
970575AG2-366 GEN
50/50
7.023
3141843SHACKLE
50/50
0.938
316404AE1-155 C
Solar/Wind Harmer
10.123
316484AD2-074 GEN
Solar/Wind Harmer
11.951
970009AG2-005 GEN
Solar/Wind Harmer
5.934
962971AG1-146 GEN
Solar/Wind Harmer
8.322
316280AD1-041 GEN
Solar/Wind Harmer
1.826
316203AE2-005 GEN
Solar/Wind Harmer
8.255
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.025
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.079
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.008
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.112
NYPJM->LTFIMP_NY
CLTF
0.039
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.009

Details for 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer l/o DVP_P7-1: LN 2016-85_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P7-1: LN 2016-85_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.78 %
Rating:206.6 MVA
Rating Type:C
MVA to Mitigate:218.55
MW Contribution:6.9
Bus #Bus NameTypeMW Contribution
3141813NORNECK
Solar/Wind Harmer
-0.06
962981AG1-147 GEN
Solar/Wind Harmer
19.073
3141783LANCAST
Solar/Wind Harmer
-0.023
3141783LANCAST
Solar/Wind Harmer
-0.015
3138133OCRAN
Solar/Wind Harmer
-0.011
3141913WHIT STONE
Solar/Wind Harmer
-0.034
3150351NORNECKC2
50/50
5.711
966661AG1-536 GEN
50/50
13.088
962861AG1-135 GEN
Solar/Wind Harmer
18.889
315662AE1-191 GEN
Solar/Wind Harmer
3.605
315666AE1-190 GEN
Solar/Wind Harmer
0.901
957601AF2-054 GEN
Solar/Wind Harmer
0.895
3141873WAN 176
Solar/Wind Harmer
-0.006
957831AF2-077 GEN
Solar/Wind Harmer
0.451
3138283WHITEMARSH
Solar/Wind Harmer
0.023
3150351NORNECKC2
50/50
5.807
970575AG2-366 GEN
50/50
6.898
316404AE1-155 C
Solar/Wind Harmer
9.973
316484AD2-074 GEN
Solar/Wind Harmer
11.754
970009AG2-005 GEN
Solar/Wind Harmer
5.836
962971AG1-146 GEN
Solar/Wind Harmer
8.174
316280AD1-041 GEN
Solar/Wind Harmer
2.253
316156AD2-030 GEN
Solar/Wind Harmer
0.798
3141873WAN 176
Solar/Wind Harmer
3.549
961951AG1-038 GEN
Solar/Wind Harmer
6.15
3138133OCRAN
Solar/Wind Harmer
-0.021
3150341NORNECKC1
50/50
5.999
3150341NORNECKC1
50/50
5.951
963611AG1-210 GEN
50/50
1.92
316077AC2-138 C
Solar/Wind Harmer
1.28
958261AF2-120 GEN
Solar/Wind Harmer
20.033
316487AF1-042 GEN
Solar/Wind Harmer
6.15
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.021
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.065
CPLELTFEXP_CPLE->PJM
CLTF
0.048
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.067
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.081
NYPJM->LTFIMP_NY
CLTF
0.05

Details for 3OCRAN-3WHIT STONE 115.0 kV Ckt 1 line l/o DVP_P4-2: L4T65_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3OCRAN-3WHIT STONE 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: L4T65_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:153.79 %
Rating:269.0 MVA
Rating Type:C
MVA to Mitigate:413.69
MW Contribution:19.98
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
31.971
961951AG1-038 GEN
Solar/Wind Harmer
16.635
3138133OCRAN
Solar/Wind Harmer
-0.075
962861AG1-135 GEN
Solar/Wind Harmer
47.357
970575AG2-366 GEN
50/50
19.982
316484AD2-074 GEN
Solar/Wind Harmer
31.791
316404AE1-155 C
Solar/Wind Harmer
24.361
962971AG1-146 GEN
Solar/Wind Harmer
23.679
970009AG2-005 GEN
Solar/Wind Harmer
15.786
316487AF1-042 GEN
Solar/Wind Harmer
16.635
958261AF2-120 GEN
Solar/Wind Harmer
48.936
3141783LANCAST
Solar/Wind Harmer
-0.075
3141783LANCAST
Solar/Wind Harmer
-0.05
3138133OCRAN
Solar/Wind Harmer
-0.038
962981AG1-147 GEN
Solar/Wind Harmer
55.25
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.05
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.156
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.031
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.232
NYPJM->LTFIMP_NY
CLTF
0.05
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.052

Details for 3OCRAN-3WHIT STONE 115.0 kV Ckt 1 line l/o DVP_P4-2: 6552_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3OCRAN-3WHIT STONE 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 6552_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:153.79 %
Rating:269.0 MVA
Rating Type:C
MVA to Mitigate:413.69
MW Contribution:19.98
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
31.971
961951AG1-038 GEN
Solar/Wind Harmer
16.635
3138133OCRAN
Solar/Wind Harmer
-0.075
962861AG1-135 GEN
Solar/Wind Harmer
47.357
970575AG2-366 GEN
50/50
19.982
316484AD2-074 GEN
Solar/Wind Harmer
31.791
316404AE1-155 C
Solar/Wind Harmer
24.361
962971AG1-146 GEN
Solar/Wind Harmer
23.679
970009AG2-005 GEN
Solar/Wind Harmer
15.786
316487AF1-042 GEN
Solar/Wind Harmer
16.635
958261AF2-120 GEN
Solar/Wind Harmer
48.936
3141783LANCAST
Solar/Wind Harmer
-0.075
3141783LANCAST
Solar/Wind Harmer
-0.05
3138133OCRAN
Solar/Wind Harmer
-0.038
962981AG1-147 GEN
Solar/Wind Harmer
55.25
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.05
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.156
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.031
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.232
NYPJM->LTFIMP_NY
CLTF
0.05
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.052

Details for 3OCRAN-3WHIT STONE 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1059_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3OCRAN-3WHIT STONE 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1059_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:142.85 %
Rating:219.96 MVA
Rating Type:B
MVA to Mitigate:314.22
MW Contribution:19.98
Bus #Bus NameTypeMW Contribution
970575AG2-366 GEN
50/50
19.982
316404AE1-155 C
Solar/Wind Harmer
0.253
962971AG1-146 GEN
Solar/Wind Harmer
17.984
970009AG2-005 GEN
Solar/Wind Harmer
8.392
3141783LANCAST
Solar/Wind Harmer
0.674
3141783LANCAST
Solar/Wind Harmer
0.45
3138133OCRAN
Solar/Wind Harmer
0.337
962981AG1-147 GEN
Solar/Wind Harmer
41.962
970327AG2-215 GEN
Solar/Wind Harmer
36.887
958261AF2-120 GEN
Solar/Wind Harmer
37.167
966661AG1-536 GEN
50/50
31.971
3138133OCRAN
Solar/Wind Harmer
0.674
962861AG1-135 GEN
Solar/Wind Harmer
35.968
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.05
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.156
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.031
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.232
NYPJM->LTFIMP_NY
CLTF
0.05
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.052

Details for 3RAPP TR-3GREYSPT 115.0 kV Ckt 1 line l/o DVP_P4-2: L4T65_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3RAPP TR-3GREYSPT 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: L4T65_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:141.1 %
Rating:148.0 MVA
Rating Type:C
MVA to Mitigate:208.82
MW Contribution:9.99
Bus #Bus NameTypeMW Contribution
970575AG2-366 GEN
50/50
9.991
316484AD2-074 GEN
Solar/Wind Harmer
15.895
316404AE1-155 C
Solar/Wind Harmer
12.18
962971AG1-146 GEN
Solar/Wind Harmer
11.839
970009AG2-005 GEN
Solar/Wind Harmer
7.893
316487AF1-042 GEN
Solar/Wind Harmer
8.317
958261AF2-120 GEN
Solar/Wind Harmer
24.467
3141913WHIT STONE
Solar/Wind Harmer
-0.063
3141783LANCAST
Solar/Wind Harmer
-0.037
3141783LANCAST
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.019
962981AG1-147 GEN
Solar/Wind Harmer
27.625
966661AG1-536 GEN
50/50
15.985
961951AG1-038 GEN
Solar/Wind Harmer
8.317
3138133OCRAN
Solar/Wind Harmer
-0.037
962861AG1-135 GEN
Solar/Wind Harmer
23.678
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.026
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.08
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.016
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.119
NYPJM->LTFIMP_NY
CLTF
0.025
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.027

Details for 3RAPP TR-3GREYSPT 115.0 kV Ckt 1 line l/o DVP_P4-2: 6552_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3RAPP TR-3GREYSPT 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 6552_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:141.1 %
Rating:148.0 MVA
Rating Type:C
MVA to Mitigate:208.82
MW Contribution:9.99
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
15.985
961951AG1-038 GEN
Solar/Wind Harmer
8.317
3138133OCRAN
Solar/Wind Harmer
-0.037
962861AG1-135 GEN
Solar/Wind Harmer
23.678
3141913WHIT STONE
Solar/Wind Harmer
-0.063
3141783LANCAST
Solar/Wind Harmer
-0.037
3141783LANCAST
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.019
962981AG1-147 GEN
Solar/Wind Harmer
27.625
970575AG2-366 GEN
50/50
9.991
316484AD2-074 GEN
Solar/Wind Harmer
15.895
316404AE1-155 C
Solar/Wind Harmer
12.18
962971AG1-146 GEN
Solar/Wind Harmer
11.839
970009AG2-005 GEN
Solar/Wind Harmer
7.893
316487AF1-042 GEN
Solar/Wind Harmer
8.317
958261AF2-120 GEN
Solar/Wind Harmer
24.467
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.026
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.08
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.016
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.119
NYPJM->LTFIMP_NY
CLTF
0.025
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.027

Details for 3RAPP TR-3GREYSPT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1059_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3RAPP TR-3GREYSPT 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1059_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.8 %
Rating:139.12 MVA
Rating Type:B
MVA to Mitigate:159.71
MW Contribution:9.99
Bus #Bus NameTypeMW Contribution
970575AG2-366 GEN
50/50
9.991
316404AE1-155 C
Solar/Wind Harmer
0.127
962971AG1-146 GEN
Solar/Wind Harmer
8.992
970009AG2-005 GEN
Solar/Wind Harmer
4.196
3141913WHIT STONE
Solar/Wind Harmer
0.561
3141783LANCAST
Solar/Wind Harmer
0.337
3141783LANCAST
Solar/Wind Harmer
0.225
3138133OCRAN
Solar/Wind Harmer
0.168
962981AG1-147 GEN
Solar/Wind Harmer
20.981
970327AG2-215 GEN
Solar/Wind Harmer
18.443
966661AG1-536 GEN
50/50
15.985
3138133OCRAN
Solar/Wind Harmer
0.337
962861AG1-135 GEN
Solar/Wind Harmer
17.983
958261AF2-120 GEN
Solar/Wind Harmer
18.583
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.026
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.08
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.016
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.119
NYPJM->LTFIMP_NY
CLTF
0.025
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.027

Details for 3RAPP TR-3GREYSPT 115.0 kV Ckt 2 line l/o DVP_P4-2: L4T65_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3RAPP TR-3GREYSPT 115.0 kV Ckt 2 line
Contingency Name:
DVP_P4-2: L4T65_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:141.1 %
Rating:148.0 MVA
Rating Type:C
MVA to Mitigate:208.82
MW Contribution:9.99
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
15.985
961951AG1-038 GEN
Solar/Wind Harmer
8.317
3138133OCRAN
Solar/Wind Harmer
-0.037
962861AG1-135 GEN
Solar/Wind Harmer
23.678
3141913WHIT STONE
Solar/Wind Harmer
-0.063
3141783LANCAST
Solar/Wind Harmer
-0.037
3141783LANCAST
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.019
962981AG1-147 GEN
Solar/Wind Harmer
27.625
970575AG2-366 GEN
50/50
9.991
316484AD2-074 GEN
Solar/Wind Harmer
15.895
316404AE1-155 C
Solar/Wind Harmer
12.18
962971AG1-146 GEN
Solar/Wind Harmer
11.839
970009AG2-005 GEN
Solar/Wind Harmer
7.893
316487AF1-042 GEN
Solar/Wind Harmer
8.317
958261AF2-120 GEN
Solar/Wind Harmer
24.467
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.026
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.08
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.016
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.119
NYPJM->LTFIMP_NY
CLTF
0.025
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.027

Details for 3RAPP TR-3GREYSPT 115.0 kV Ckt 2 line l/o DVP_P4-2: 6552_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3RAPP TR-3GREYSPT 115.0 kV Ckt 2 line
Contingency Name:
DVP_P4-2: 6552_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:141.1 %
Rating:148.0 MVA
Rating Type:C
MVA to Mitigate:208.82
MW Contribution:9.99
Bus #Bus NameTypeMW Contribution
970575AG2-366 GEN
50/50
9.991
316484AD2-074 GEN
Solar/Wind Harmer
15.895
316404AE1-155 C
Solar/Wind Harmer
12.18
962971AG1-146 GEN
Solar/Wind Harmer
11.839
970009AG2-005 GEN
Solar/Wind Harmer
7.893
316487AF1-042 GEN
Solar/Wind Harmer
8.317
958261AF2-120 GEN
Solar/Wind Harmer
24.467
3141913WHIT STONE
Solar/Wind Harmer
-0.063
3141783LANCAST
Solar/Wind Harmer
-0.037
3141783LANCAST
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.019
962981AG1-147 GEN
Solar/Wind Harmer
27.625
966661AG1-536 GEN
50/50
15.985
961951AG1-038 GEN
Solar/Wind Harmer
8.317
3138133OCRAN
Solar/Wind Harmer
-0.037
962861AG1-135 GEN
Solar/Wind Harmer
23.678
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.026
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.08
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.016
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.119
NYPJM->LTFIMP_NY
CLTF
0.025
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.027

Details for 3RAPP TR-3GREYSPT 115.0 kV Ckt 2 line l/o DVP_P1-2: LN 1059_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3RAPP TR-3GREYSPT 115.0 kV Ckt 2 line
Contingency Name:
DVP_P1-2: LN 1059_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.8 %
Rating:139.12 MVA
Rating Type:B
MVA to Mitigate:159.71
MW Contribution:9.99
Bus #Bus NameTypeMW Contribution
970575AG2-366 GEN
50/50
9.991
316404AE1-155 C
Solar/Wind Harmer
0.127
962971AG1-146 GEN
Solar/Wind Harmer
8.992
970009AG2-005 GEN
Solar/Wind Harmer
4.196
3141913WHIT STONE
Solar/Wind Harmer
0.561
3141783LANCAST
Solar/Wind Harmer
0.337
3141783LANCAST
Solar/Wind Harmer
0.225
3138133OCRAN
Solar/Wind Harmer
0.168
962981AG1-147 GEN
Solar/Wind Harmer
20.981
970327AG2-215 GEN
Solar/Wind Harmer
18.443
966661AG1-536 GEN
50/50
15.985
3138133OCRAN
Solar/Wind Harmer
0.337
962861AG1-135 GEN
Solar/Wind Harmer
17.983
958261AF2-120 GEN
Solar/Wind Harmer
18.583
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.026
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.08
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.016
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.119
NYPJM->LTFIMP_NY
CLTF
0.025
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.027

Details for 3WAN 89-3WHITEMARSH 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2016-85_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
3WAN 89-3WHITEMARSH 115.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2016-85_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:118.35 %
Rating:208.0 MVA
Rating Type:C
MVA to Mitigate:246.17
MW Contribution:7.33
Bus #Bus NameTypeMW Contribution
315662AE1-191 GEN
Solar/Wind Harmer
8.607
315666AE1-190 GEN
Solar/Wind Harmer
2.152
957601AF2-054 GEN
Solar/Wind Harmer
2.136
3141873WAN 176
Solar/Wind Harmer
-0.014
3141913WHIT STONE
Solar/Wind Harmer
-0.063
3138133OCRAN
Solar/Wind Harmer
-0.018
3141783LANCAST
Solar/Wind Harmer
-0.033
3141783LANCAST
Solar/Wind Harmer
-0.022
962981AG1-147 GEN
Solar/Wind Harmer
20.269
3141813NORNECK
Solar/Wind Harmer
-0.015
957831AF2-077 GEN
Solar/Wind Helper
0.657
3150341NORNECKC1
50/50
1.49
3150341NORNECKC1
50/50
1.478
963611AG1-210 GEN
50/50
0.477
316441AF1-014 GEN
Solar/Wind Harmer
4.813
316487AF1-042 GEN
Solar/Wind Harmer
5.356
958261AF2-120 GEN
Solar/Wind Harmer
12.202
316077AC2-138 C
Solar/Wind Harmer
0.318
970575AG2-366 GEN
50/50
7.331
3150351NORNECKC2
50/50
1.443
316203AE2-005 GEN
Solar/Wind Harmer
30.106
316280AD1-041 GEN
Solar/Wind Harmer
5.38
316156AD2-030 GEN
Solar/Wind Harmer
1.907
3141873WAN 176
Solar/Wind Harmer
8.473
962971AG1-146 GEN
Solar/Wind Harmer
8.687
316484AD2-074 GEN
Solar/Wind Harmer
10.237
970009AG2-005 GEN
Solar/Wind Harmer
5.083
316404AE1-155 C
Solar/Wind Harmer
6.075
966661AG1-536 GEN
50/50
7.972
3150351NORNECKC2
50/50
1.419
3138133OCRAN
Solar/Wind Harmer
-0.036
961951AG1-038 GEN
Solar/Wind Harmer
5.356
962861AG1-135 GEN
Solar/Wind Harmer
12.72
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.065
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.204
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.078
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.333
NYPJM->LTFIMP_NY
CLTF
0.012
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.148

Details for 3WHIT STONE-3RAPPAHNCK 115.0 kV Ckt 1 line l/o DVP_P4-2: L4T65_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3WHIT STONE-3RAPPAHNCK 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: L4T65_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.87 %
Rating:351.0 MVA
Rating Type:C
MVA to Mitigate:410.22
MW Contribution:19.98
Bus #Bus NameTypeMW Contribution
970575AG2-366 GEN
50/50
19.982
316484AD2-074 GEN
Solar/Wind Harmer
31.791
316404AE1-155 C
Solar/Wind Harmer
24.361
962971AG1-146 GEN
Solar/Wind Harmer
23.678
970009AG2-005 GEN
Solar/Wind Harmer
15.785
3141913WHIT STONE
Solar/Wind Harmer
-0.126
3141783LANCAST
Solar/Wind Harmer
-0.075
3141783LANCAST
Solar/Wind Harmer
-0.05
3138133OCRAN
Solar/Wind Harmer
-0.038
962981AG1-147 GEN
Solar/Wind Harmer
55.249
966661AG1-536 GEN
50/50
31.97
961951AG1-038 GEN
Solar/Wind Harmer
16.635
3138133OCRAN
Solar/Wind Harmer
-0.075
962861AG1-135 GEN
Solar/Wind Harmer
47.356
316487AF1-042 GEN
Solar/Wind Harmer
16.635
958261AF2-120 GEN
Solar/Wind Harmer
48.935
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.051
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.16
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.032
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.238
NYPJM->LTFIMP_NY
CLTF
0.051
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.053

Details for 3WHIT STONE-3RAPPAHNCK 115.0 kV Ckt 1 line l/o DVP_P4-2: 6552_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3WHIT STONE-3RAPPAHNCK 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 6552_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.87 %
Rating:351.0 MVA
Rating Type:C
MVA to Mitigate:410.22
MW Contribution:19.98
Bus #Bus NameTypeMW Contribution
3141913WHIT STONE
Solar/Wind Harmer
-0.126
3141783LANCAST
Solar/Wind Harmer
-0.075
3141783LANCAST
Solar/Wind Harmer
-0.05
3138133OCRAN
Solar/Wind Harmer
-0.038
962981AG1-147 GEN
Solar/Wind Harmer
55.249
316487AF1-042 GEN
Solar/Wind Harmer
16.635
958261AF2-120 GEN
Solar/Wind Harmer
48.935
966661AG1-536 GEN
50/50
31.97
961951AG1-038 GEN
Solar/Wind Harmer
16.635
3138133OCRAN
Solar/Wind Harmer
-0.075
962861AG1-135 GEN
Solar/Wind Harmer
47.356
970575AG2-366 GEN
50/50
19.982
316484AD2-074 GEN
Solar/Wind Harmer
31.791
316404AE1-155 C
Solar/Wind Harmer
24.361
962971AG1-146 GEN
Solar/Wind Harmer
23.678
970009AG2-005 GEN
Solar/Wind Harmer
15.785
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.051
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.16
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.032
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.238
NYPJM->LTFIMP_NY
CLTF
0.051
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.053

Details for 3WHITEMARSH-3HAYES89 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2016-85_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
3WHITEMARSH-3HAYES89 115.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2016-85_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:114.46 %
Rating:207.0 MVA
Rating Type:C
MVA to Mitigate:236.93
MW Contribution:7.33
Bus #Bus NameTypeMW Contribution
957831AF2-077 GEN
Solar/Wind Harmer
2.967
3138283WHITEMARSH
Solar/Wind Harmer
0.153
315662AE1-191 GEN
Solar/Wind Harmer
8.606
315666AE1-190 GEN
Solar/Wind Harmer
2.151
957601AF2-054 GEN
Solar/Wind Harmer
2.136
3141873WAN 176
Solar/Wind Harmer
-0.014
3141913WHIT STONE
Solar/Wind Harmer
-0.063
3138133OCRAN
Solar/Wind Harmer
-0.018
3141783LANCAST
Solar/Wind Harmer
-0.033
3141783LANCAST
Solar/Wind Harmer
-0.022
962981AG1-147 GEN
Solar/Wind Harmer
20.265
3141813NORNECK
Solar/Wind Harmer
-0.015
3150341NORNECKC1
50/50
1.489
3150341NORNECKC1
50/50
1.478
963611AG1-210 GEN
50/50
0.477
316441AF1-014 GEN
Solar/Wind Harmer
4.813
316487AF1-042 GEN
Solar/Wind Harmer
5.355
958261AF2-120 GEN
Solar/Wind Harmer
12.199
316077AC2-138 C
Solar/Wind Harmer
0.318
966661AG1-536 GEN
50/50
7.97
3150351NORNECKC2
50/50
1.418
3138133OCRAN
Solar/Wind Harmer
-0.036
961951AG1-038 GEN
Solar/Wind Harmer
5.355
962861AG1-135 GEN
Solar/Wind Harmer
12.717
970575AG2-366 GEN
50/50
7.329
3150351NORNECKC2
50/50
1.442
316203AE2-005 GEN
Solar/Wind Harmer
30.103
316280AD1-041 GEN
Solar/Wind Harmer
5.379
316156AD2-030 GEN
Solar/Wind Harmer
1.906
3141873WAN 176
Solar/Wind Harmer
8.472
962971AG1-146 GEN
Solar/Wind Harmer
8.685
316484AD2-074 GEN
Solar/Wind Harmer
10.234
970009AG2-005 GEN
Solar/Wind Harmer
5.082
316404AE1-155 C
Solar/Wind Harmer
6.073
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.069
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.216
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.08
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.351
NYPJM->LTFIMP_NY
CLTF
0.016
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.152

Details for 6ARNOLDS-6COMORN 230.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.98 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:875.4
MW Contribution:3.79
Bus #Bus NameTypeMW Contribution
3141316ARNOLDS
50/50
2.024
3150351NORNECKC2
50/50
3.077
970575AG2-366 GEN
50/50
3.788
315749AE2-041 GEN
50/50
5.221
3141843SHACKLE
50/50
0.787
3142433PROV 92
50/50
0.233
3142433PROV 92
50/50
0.233
970737AG2-469 GEN
Solar/Wind Harmer
26.848
3141906WESTMOR
Solar/Wind Harmer
-0.019
316404AE1-155 C
Solar/Wind Harmer
5.369
316484AD2-074 GEN
Solar/Wind Harmer
6.401
970009AG2-005 GEN
Solar/Wind Harmer
3.178
962971AG1-146 GEN
Solar/Wind Harmer
4.489
316156AD2-030 GEN
Solar/Wind Harmer
0.464
3141873WAN 176
Solar/Wind Harmer
2.06
316280AD1-041 GEN
Solar/Wind Harmer
1.262
3141766HARMONY
Solar/Wind Harmer
1.469
316203AE2-005 GEN
Solar/Wind Harmer
6.877
316382AG1-145 C
Solar/Wind Harmer
0.285
3150921YORKTN3
Adder
2.048
3144216WINCHST
Adder
0.297
3142946ENON
Solar/Wind Harmer
-0.003
970293AG2-193 GEN
Solar/Wind Harmer
0.932
3151221GRAVEL6
Adder
4.627
3151171GRAVELC
Adder
0.89
961611AG1-000B GEN
Solar/Wind Harmer
1.491
3145336SMITFLD
Solar/Wind Harmer
-0.003
315778AD1-151 GEN
Solar/Wind Harmer
5.997
970129AG2-093 GEN
Solar/Wind Harmer
3.855
970133AG2-095 GEN
Solar/Wind Harmer
0.758
3144536CHRHLND
Solar/Wind Harmer
-0.001
315773AC2-141 GEN
Solar/Wind Harmer
2.81
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.478
3143096IRON208
Adder
0.246
3143096IRON208
Adder
0.241
3142416OLDCHRC
Solar/Wind Harmer
0.665
944581AF1-123 GEN
Solar/Wind Harmer
29.902
944601AF1-125 GEN
Solar/Wind Harmer
29.435
3146456SLIGO L269
Solar/Wind Harmer
-0.006
971153AH1-033 GEN
Solar/Wind Harmer
0.79
316320Y1-086
Solar/Wind Harmer
0.374
957191AF2-013 GEN
50/50
65.961
3150341NORNECKC1
50/50
3.178
3150341NORNECKC1
50/50
3.153
963611AG1-210 GEN
50/50
1.017
316077AC2-138 C
Solar/Wind Harmer
0.678
958261AF2-120 GEN
Solar/Wind Harmer
10.785
316487AF1-042 GEN
Solar/Wind Harmer
3.349
316441AF1-014 GEN
Solar/Wind Harmer
1.1
316075AC2-137 C
Solar/Wind Harmer
0.231
3142946ENON
Solar/Wind Harmer
-0.001
316033AB2-134 GEN
Solar/Wind Harmer
2.247
315697AD1-025 GEN
Solar/Wind Harmer
1.409
316236AE1-162_GEN
Solar/Wind Harmer
0.21
316036AC1-147 C
Solar/Wind Harmer
0.179
3150991CHESPKB
Adder
0.619
3150991CHESPKB
Adder
0.604
316316AC1-027 C
Solar/Wind Harmer
0.203
3142956BIRDNECK
Solar/Wind Harmer
0.354
316185AD1-033 GEN
Solar/Wind Harmer
0.693
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316339AD2-160 GEN
Solar/Wind Harmer
0.439
316018AA1-139 ULT2
Solar/Wind Harmer
0.557
316017AA1-139 ULT1
Solar/Wind Harmer
0.526
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.766
3130086AYDLETT
Solar/Wind Harmer
-0.026
3150691DARBY 3
Adder
4.114
3150701DARBY 4
Adder
4.104
3150681DARBY 2
Adder
4.1
3150671DARBY 1
Adder
4.095
3146386ELIZ CT
Solar/Wind Harmer
-0.006
315759AF1-018 GEN
50/50
5.221
3142433PROV 92
50/50
0.233
3142433PROV 92
50/50
0.233
944491AF1-114 GEN
Solar/Wind Harmer
18.883
316223AC1-118
Solar/Wind Harmer
1.264
3141813NORNECK
Solar/Wind Harmer
-0.032
962981AG1-147 GEN
Solar/Wind Harmer
10.474
3141783LANCAST
Solar/Wind Harmer
-0.013
3141783LANCAST
Solar/Wind Harmer
-0.008
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.02
957601AF2-054 GEN
Solar/Wind Harmer
0.519
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
2.019
315666AE1-190 GEN
Solar/Wind Harmer
0.505
316059AD1-063 C
Solar/Wind Harmer
0.373
316314AB2-024 C
Solar/Wind Harmer
1.365
3143873LANEXA
Solar/Wind Harmer
-0.009
957831AF2-077 GEN
Solar/Wind Harmer
0.393
3138283WHITEMARSH
Solar/Wind Harmer
0.02
971167AH1-042 GEN
Solar/Wind Harmer
11.736
315976AC1-164 GENA
Solar/Wind Harmer
10.45
316169AC1-164_GENC
Solar/Wind Harmer
9.028
315975AC1-164 GENB
Solar/Wind Harmer
0.309
972265AH1-717 GEN
Adder
4.942
3151201GRAVEL4
Adder
4.633
3151191GRAVEL3
Adder
4.574
3151211GRAVEL5
Adder
4.574
971445AH1-216 GEN
Solar/Wind Harmer
4.315
316369SG1_INVT
Solar/Wind Harmer
1.245
316132AB2-190 GEN1
Solar/Wind Harmer
0.694
3152611GOSPORTB
Adder
0.752
3152621GOSPORTC
Adder
0.638
3152601GOSPORTA
Adder
0.589
3151081ELIZAR1
Adder
5.409
3151091ELIZAR2
Adder
5.315
316312AB1-027
Solar/Wind Harmer
0.222
316305AF2-043 C
Solar/Wind Harmer
0.196
957871AF2-081 GEN
Solar/Wind Harmer
3.251
319010AE1-072 C
Solar/Wind Harmer
1.31
3146406KITTY HAWK
Solar/Wind Harmer
0.005
313526AB2-022
Solar/Wind Harmer
0.172
315835AF2-110_GEN
Solar/Wind Harmer
0.797
3146486SUNBURY
Solar/Wind Harmer
-0.006
3146486SUNBURY
Solar/Wind Harmer
-0.006
316321Z2-027
Solar/Wind Harmer
0.171
3146396TANGLEW
Solar/Wind Harmer
0.117
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3141426STAFORD
Solar/Wind Helper
0.031
3150351NORNECKC2
50/50
3.026
966661AG1-536 GEN
50/50
7.046
3141843SHACKLE
50/50
0.787
3142433PROV 92
50/50
0.233
3142433PROV 92
50/50
0.233
957971AF2-091 GEN
Solar/Wind Harmer
6.42
972135AH1-637 GEN
Solar/Wind Harmer
5.832
316337AD2-073 GEN
Solar/Wind Harmer
1.054
964211AG1-282 GEN
Solar/Wind Harmer
0.905
3141726DUNNSVL
Solar/Wind Harmer
-0.12
962861AG1-135 GEN
Solar/Wind Harmer
10.198
961951AG1-038 GEN
Solar/Wind Harmer
3.349
3138133OCRAN
Solar/Wind Harmer
-0.012
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.916
3142433PROV 92
Solar/Wind Harmer
-0.051
971317AH1-138 GEN
Solar/Wind Harmer
1.283
316159AE1-175 C
Solar/Wind Harmer
0.254
3138126ROCKLANDING
Solar/Wind Harmer
0.027
944631AF1-128 GEN
Adder
32.493
3151171GRAVELC
Adder
0.677
961611AG1-000B GEN
Solar/Wind Harmer
3.494
971647AH1-324 GEN
Solar/Wind Harmer
3.511
3145336SMITFLD
Solar/Wind Harmer
-0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.095
316458AB2-190 GEN2
Solar/Wind Harmer
0.694
970129AG2-093 GEN
Solar/Wind Harmer
1.562
316072AD1-144
Solar/Wind Harmer
0.138
316294AC1-161 GEN
Solar/Wind Harmer
2.172
316375AC2-012 GEN
Solar/Wind Harmer
2.296
3150981CHESPKA
Adder
0.737
3143096IRON208
Adder
0.246
3142416OLDCHRC
Solar/Wind Harmer
-0.017
3142416OLDCHRC
Solar/Wind Harmer
-0.007
944591AF1-124 GEN
Solar/Wind Harmer
30.01
316246AF1-032 C
Solar/Wind Harmer
0.132
316388AE2-253 GEN
Solar/Wind Harmer
0.439
3146456SLIGO L269
Solar/Wind Harmer
-0.006
316093AE2-104_GEN
Solar/Wind Harmer
1.855
CPLELTFEXP_CPLE->PJM
CLTF
2.221
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.105
LAGNLTFEXP_LAGN->PJM
CLTF
1.55
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.805
TVALTFEXP_TVA->PJM
CLTF
0.781
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.555
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.668
MECLTFEXP_MEC->PJM
CLTF
0.73
SIGELTFEXP_SIGE->PJM
CLTF
0.022
NYPJM->LTFIMP_NY
CLTF
0.582
LGEELTFEXP_LGEE->PJM
CLTF
0.268
WECLTFEXP_WEC->PJM
CLTF
0.133

Details for 6ARNOLDS-6COMORN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.85 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:687.09
MW Contribution:3.66
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
2.956
966661AG1-536 GEN
50/50
6.849
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
971353AH1-157 GEN
50/50
7.408
970017AG2-010 GEN
50/50
4.699
3150641CHESTS8
50/50
0.203
944631AF1-128 GEN
50/50
31.925
972135AH1-637 GEN
Solar/Wind Harmer
4.389
316337AD2-073 GEN
Solar/Wind Harmer
0.299
3141726DUNNSVL
Solar/Wind Harmer
1.044
962861AG1-135 GEN
Solar/Wind Harmer
7.523
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
971317AH1-138 GEN
Solar/Wind Harmer
0.613
316159AE1-175 C
Solar/Wind Harmer
0.065
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3142416OLDCHRC
Solar/Wind Harmer
0.149
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.6
3141316ARNOLDS
50/50
2.018
3150351NORNECKC2
50/50
3.006
970575AG2-366 GEN
50/50
3.66
315749AE2-041 GEN
50/50
4.946
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150921YORKTN3
50/50
1.929
3144216WINCHST
50/50
0.279
3151161SURRY 1
50/50
2.166
970737AG2-469 GEN
Solar/Wind Harmer
20.178
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.637
962971AG1-146 GEN
Solar/Wind Harmer
3.294
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.61
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.855
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.668
3142416OLDCHRC
Solar/Wind Harmer
0.555
3151221GRAVEL6
Adder
4.099
3151171GRAVELC
Adder
0.789
957191AF2-013 GEN
50/50
65.713
3150341NORNECKC1
50/50
3.105
3150341NORNECKC1
50/50
3.08
963611AG1-210 GEN
50/50
0.994
3150621CHESTS7
50/50
0.184
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
7.962
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.007
315759AF1-018 GEN
50/50
4.946
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150611CHESTG7
50/50
0.401
3150631CHESTG8
50/50
0.394
971047AG2-646 GEN
50/50
11.221
972263AH1-716 GEN
50/50
32.871
944491AF1-114 GEN
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Harmer
0.296
3141813NORNECK
Solar/Wind Harmer
0.279
970327AG2-215 GEN
Solar/Wind Harmer
7.194
962981AG1-147 GEN
Solar/Wind Harmer
7.685
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.051
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
0.029
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.081
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
9.122
315976AC1-164 GENA
Solar/Wind Harmer
8.292
316169AC1-164_GENC
Solar/Wind Harmer
7.163
315975AC1-164 GENB
Solar/Wind Harmer
0.245
316312AB1-027
Solar/Wind Harmer
0.102
972265AH1-717 GEN
Adder
4.377
3151201GRAVEL4
Adder
4.104
3151191GRAVEL3
Adder
4.052
3151211GRAVEL5
Adder
4.052
3141426STAFORD
Solar/Wind Helper
0.031
CPLELTFEXP_CPLE->PJM
CLTF
1.997
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.895
LAGNLTFEXP_LAGN->PJM
CLTF
1.483
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.388
TVALTFEXP_TVA->PJM
CLTF
0.749
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.711
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.577
MECLTFEXP_MEC->PJM
CLTF
0.732
SIGELTFEXP_SIGE->PJM
CLTF
0.022
NYPJM->LTFIMP_NY
CLTF
0.564
LGEELTFEXP_LGEE->PJM
CLTF
0.274
WECLTFEXP_WEC->PJM
CLTF
0.137

Details for 6ARNOLDS-6COMORN 230.0 kV Ckt 1 line l/o DVP_P4-2: 574T575_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 574T575_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.16 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:815.02
MW Contribution:3.69
Bus #Bus NameTypeMW Contribution
3141316ARNOLDS
50/50
2.011
3150351NORNECKC2
50/50
3.016
970575AG2-366 GEN
50/50
3.687
315749AE2-041 GEN
50/50
5.017
3141843SHACKLE
50/50
0.757
970737AG2-469 GEN
Solar/Wind Harmer
26.539
3141906WESTMOR
Solar/Wind Harmer
-0.018
316404AE1-155 C
Solar/Wind Harmer
5.246
316484AD2-074 GEN
Solar/Wind Harmer
6.24
970009AG2-005 GEN
Solar/Wind Harmer
3.098
962971AG1-146 GEN
Solar/Wind Harmer
4.369
316156AD2-030 GEN
Solar/Wind Harmer
0.446
3141873WAN 176
Solar/Wind Harmer
1.984
316280AD1-041 GEN
Solar/Wind Harmer
1.215
3141766HARMONY
Solar/Wind Harmer
1.411
316203AE2-005 GEN
Solar/Wind Harmer
6.619
3142433PROV 92
Adder
0.212
3142433PROV 92
Adder
0.212
316382AG1-145 C
Solar/Wind Harmer
0.264
3150921YORKTN3
Adder
1.889
3144216WINCHST
Adder
0.274
3142946ENON
Solar/Wind Harmer
-0.003
970293AG2-193 GEN
Solar/Wind Harmer
0.911
957191AF2-013 GEN
50/50
65.491
3150341NORNECKC1
50/50
3.116
3150341NORNECKC1
50/50
3.091
963611AG1-210 GEN
50/50
0.997
316077AC2-138 C
Solar/Wind Harmer
0.664
958261AF2-120 GEN
Solar/Wind Harmer
10.538
316487AF1-042 GEN
Solar/Wind Harmer
3.265
316441AF1-014 GEN
Solar/Wind Harmer
1.058
316075AC2-137 C
Solar/Wind Harmer
0.221
3142946ENON
Solar/Wind Harmer
-0.001
316033AB2-134 GEN
Solar/Wind Harmer
2.132
315697AD1-025 GEN
Solar/Wind Harmer
1.337
3150691DARBY 3
Adder
4.134
3150701DARBY 4
Adder
4.124
3150681DARBY 2
Adder
4.12
3150671DARBY 1
Adder
4.115
316236AE1-162_GEN
Solar/Wind Harmer
0.194
3151221GRAVEL6
Adder
4.32
3151171GRAVELC
Adder
0.831
961611AG1-000B GEN
Solar/Wind Harmer
1.4
3142416OLDCHRC
Solar/Wind Harmer
0.671
315778AD1-151 GEN
Solar/Wind Harmer
5.713
970129AG2-093 GEN
Solar/Wind Harmer
3.698
3143096IRON208
Adder
0.244
3143096IRON208
Adder
0.239
970133AG2-095 GEN
Solar/Wind Harmer
0.735
3145336SMITFLD
Solar/Wind Harmer
-0.003
315759AF1-018 GEN
50/50
5.017
944491AF1-114 GEN
Solar/Wind Harmer
18.704
316223AC1-118
Solar/Wind Harmer
1.247
3141813NORNECK
Solar/Wind Harmer
-0.031
962981AG1-147 GEN
Solar/Wind Harmer
10.194
3141783LANCAST
Solar/Wind Harmer
-0.012
3141783LANCAST
Solar/Wind Harmer
-0.008
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.019
957601AF2-054 GEN
Solar/Wind Harmer
0.5
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
1.944
315666AE1-190 GEN
Solar/Wind Harmer
0.486
316059AD1-063 C
Solar/Wind Harmer
0.358
316314AB2-024 C
Solar/Wind Harmer
1.31
3143873LANEXA
Solar/Wind Harmer
-0.008
957831AF2-077 GEN
Solar/Wind Harmer
0.373
3138283WHITEMARSH
Solar/Wind Harmer
0.019
3142433PROV 92
Adder
0.212
3142433PROV 92
Adder
0.212
971167AH1-042 GEN
Solar/Wind Harmer
11.35
315976AC1-164 GENA
Solar/Wind Harmer
9.762
316169AC1-164_GENC
Solar/Wind Harmer
8.433
315975AC1-164 GENB
Solar/Wind Harmer
0.289
972265AH1-717 GEN
Adder
4.614
3151201GRAVEL4
Adder
4.325
3151191GRAVEL3
Adder
4.27
3151211GRAVEL5
Adder
4.27
316312AB1-027
Solar/Wind Harmer
0.224
316369SG1_INVT
Solar/Wind Harmer
1.181
316132AB2-190 GEN1
Solar/Wind Harmer
0.665
971445AH1-216 GEN
Solar/Wind Harmer
4
3141426STAFORD
Solar/Wind Helper
0.033
3150351NORNECKC2
50/50
2.966
966661AG1-536 GEN
50/50
6.885
3141843SHACKLE
50/50
0.757
957971AF2-091 GEN
Solar/Wind Harmer
6.359
972135AH1-637 GEN
Solar/Wind Harmer
5.77
316337AD2-073 GEN
Solar/Wind Harmer
1.037
964211AG1-282 GEN
Solar/Wind Harmer
0.886
3141726DUNNSVL
Solar/Wind Harmer
-0.117
962861AG1-135 GEN
Solar/Wind Harmer
9.959
961951AG1-038 GEN
Solar/Wind Harmer
3.265
3138133OCRAN
Solar/Wind Harmer
-0.012
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.845
3142433PROV 92
Solar/Wind Harmer
-0.049
3142433PROV 92
Adder
0.212
3142433PROV 92
Adder
0.212
971317AH1-138 GEN
Solar/Wind Harmer
1.192
316159AE1-175 C
Solar/Wind Harmer
0.235
3138126ROCKLANDING
Solar/Wind Harmer
0.025
944631AF1-128 GEN
Adder
31.292
3151171GRAVELC
Adder
0.632
961611AG1-000B GEN
Solar/Wind Harmer
3.282
3142416OLDCHRC
Solar/Wind Harmer
-0.017
3142416OLDCHRC
Solar/Wind Harmer
-0.007
971647AH1-324 GEN
Solar/Wind Harmer
3.315
971069AG2-661 GEN
Solar/Wind Harmer
1.043
316458AB2-190 GEN2
Solar/Wind Harmer
0.665
970129AG2-093 GEN
Solar/Wind Harmer
1.498
3143096IRON208
Adder
0.244
3145336SMITFLD
Solar/Wind Harmer
-0.026
CPLELTFEXP_CPLE->PJM
CLTF
2.196
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.727
LAGNLTFEXP_LAGN->PJM
CLTF
1.637
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.831
TVALTFEXP_TVA->PJM
CLTF
0.827
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.235
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.846
MECLTFEXP_MEC->PJM
CLTF
0.811
SIGELTFEXP_SIGE->PJM
CLTF
0.025
NYPJM->LTFIMP_NY
CLTF
0.625
LGEELTFEXP_LGEE->PJM
CLTF
0.304
WECLTFEXP_WEC->PJM
CLTF
0.152

Details for 6ARNOLDS-6COMORN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.79 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:580.47
MW Contribution:3.68
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
2.97
966661AG1-536 GEN
50/50
6.884
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
971353AH1-157 GEN
50/50
7.642
970017AG2-010 GEN
50/50
4.875
3150641CHESTS8
50/50
0.192
944631AF1-128 GEN
50/50
30.156
3152331SURRY 2
50/50
2.455
972135AH1-637 GEN
Solar/Wind Harmer
4.407
316337AD2-073 GEN
Solar/Wind Harmer
0.3
3141726DUNNSVL
Solar/Wind Harmer
1.049
962861AG1-135 GEN
Solar/Wind Harmer
7.561
3138133OCRAN
Solar/Wind Harmer
0.104
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.365
3142433PROV 92
Solar/Wind Harmer
0.422
971317AH1-138 GEN
Solar/Wind Harmer
0.633
316159AE1-175 C
Solar/Wind Harmer
0.067
3138126ROCKLANDING
Solar/Wind Harmer
0.034
3151171GRAVELC
Adder
0.607
315759AF1-018 GEN
50/50
4.976
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
972263AH1-716 GEN
50/50
35.649
3150611CHESTG7
50/50
0.379
3150631CHESTG8
50/50
0.372
971047AG2-646 GEN
50/50
10.599
944491AF1-114 GEN
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Harmer
0.297
3141813NORNECK
Solar/Wind Harmer
0.28
970327AG2-215 GEN
Solar/Wind Harmer
7.232
962981AG1-147 GEN
Solar/Wind Harmer
7.729
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.074
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.168
3141873WAN 176
Solar/Wind Harmer
0.03
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.097
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
8.942
315976AC1-164 GENA
Solar/Wind Harmer
8.275
316169AC1-164_GENC
Solar/Wind Harmer
7.149
315975AC1-164 GENB
Solar/Wind Harmer
0.245
972265AH1-717 GEN
Adder
4.429
3151201GRAVEL4
Adder
4.152
3151191GRAVEL3
Adder
4.099
3151211GRAVEL5
Adder
4.099
3141426STAFORD
Solar/Wind Helper
0.029
3141316ARNOLDS
50/50
2.026
3150351NORNECKC2
50/50
3.02
970575AG2-366 GEN
50/50
3.68
315749AE2-041 GEN
50/50
4.976
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
3150921YORKTN3
50/50
2.003
3144216WINCHST
50/50
0.289
3151161SURRY 1
50/50
2.191
970737AG2-469 GEN
Solar/Wind Harmer
20.26
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.646
962971AG1-146 GEN
Solar/Wind Harmer
3.312
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.629
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.866
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.022
3151221GRAVEL6
Adder
4.147
3151171GRAVELC
Adder
0.798
970293AG2-193 GEN
Solar/Wind Harmer
0.603
957191AF2-013 GEN
50/50
65.968
3150341NORNECKC1
50/50
3.119
3150341NORNECKC1
50/50
3.094
963611AG1-210 GEN
50/50
0.998
3150621CHESTS7
50/50
0.174
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
8.003
316075AC2-137 C
Solar/Wind Harmer
0.018
3142946ENON
Solar/Wind Harmer
0.007
CPLELTFEXP_CPLE->PJM
CLTF
1.912
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.152
LAGNLTFEXP_LAGN->PJM
CLTF
1.213
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.047
TVALTFEXP_TVA->PJM
CLTF
0.609
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.061
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.057
MECLTFEXP_MEC->PJM
CLTF
0.525
SIGELTFEXP_SIGE->PJM
CLTF
0.016
NYPJM->LTFIMP_NY
CLTF
0.465
LGEELTFEXP_LGEE->PJM
CLTF
0.185
WECLTFEXP_WEC->PJM
CLTF
0.092

Details for 6ARNOLDS-6COMORN 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.86 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:696.7
MW Contribution:3.66
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
4.944
944491AF1-114 GEN
Solar/Wind Harmer
18.743
316223AC1-118
Solar/Wind Harmer
1.247
3141813NORNECK
Solar/Wind Harmer
-0.031
962981AG1-147 GEN
Solar/Wind Harmer
10.117
3141783LANCAST
Solar/Wind Harmer
-0.012
3141783LANCAST
Solar/Wind Harmer
-0.008
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.019
957601AF2-054 GEN
Solar/Wind Harmer
0.493
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
1.916
315666AE1-190 GEN
Solar/Wind Harmer
0.479
316059AD1-063 C
Solar/Wind Harmer
0.353
316314AB2-024 C
Solar/Wind Harmer
1.29
3143873LANEXA
Solar/Wind Harmer
-0.008
957831AF2-077 GEN
Solar/Wind Harmer
0.364
3138283WHITEMARSH
Solar/Wind Harmer
0.019
3142433PROV 92
Adder
0.208
3142433PROV 92
Adder
0.208
971167AH1-042 GEN
Solar/Wind Harmer
11.098
315976AC1-164 GENA
Solar/Wind Harmer
9.485
316169AC1-164_GENC
Solar/Wind Harmer
8.194
315975AC1-164 GENB
Solar/Wind Harmer
0.281
316312AB1-027
Solar/Wind Harmer
0.216
972265AH1-717 GEN
Adder
4.374
3151201GRAVEL4
Adder
4.1
3151191GRAVEL3
Adder
4.048
3151211GRAVEL5
Adder
4.048
3141426STAFORD
Solar/Wind Helper
0.031
957191AF2-013 GEN
50/50
65.707
3150341NORNECKC1
50/50
3.104
3150341NORNECKC1
50/50
3.08
963611AG1-210 GEN
50/50
0.993
316077AC2-138 C
Solar/Wind Harmer
0.662
958261AF2-120 GEN
Solar/Wind Harmer
10.482
316487AF1-042 GEN
Solar/Wind Harmer
3.243
316441AF1-014 GEN
Solar/Wind Harmer
1.042
316075AC2-137 C
Solar/Wind Harmer
0.214
3142946ENON
Solar/Wind Harmer
-0.001
3141316ARNOLDS
50/50
2.018
3150351NORNECKC2
50/50
3.005
970575AG2-366 GEN
50/50
3.659
315749AE2-041 GEN
50/50
4.944
3141843SHACKLE
50/50
0.746
970737AG2-469 GEN
Solar/Wind Harmer
26.564
3141906WESTMOR
Solar/Wind Harmer
-0.018
316404AE1-155 C
Solar/Wind Harmer
5.218
316484AD2-074 GEN
Solar/Wind Harmer
6.199
970009AG2-005 GEN
Solar/Wind Harmer
3.078
962971AG1-146 GEN
Solar/Wind Harmer
4.336
316156AD2-030 GEN
Solar/Wind Harmer
0.44
3141873WAN 176
Solar/Wind Harmer
1.957
316280AD1-041 GEN
Solar/Wind Harmer
1.198
3141766HARMONY
Solar/Wind Harmer
1.39
316203AE2-005 GEN
Solar/Wind Harmer
6.52
3142433PROV 92
Adder
0.208
3142433PROV 92
Adder
0.208
316382AG1-145 C
Solar/Wind Harmer
0.255
3150921YORKTN3
Adder
1.818
3144216WINCHST
Adder
0.263
3142946ENON
Solar/Wind Harmer
-0.003
970293AG2-193 GEN
Solar/Wind Harmer
0.877
3142416OLDCHRC
Solar/Wind Harmer
0.646
3151221GRAVEL6
Adder
4.095
3151171GRAVELC
Adder
0.788
3150351NORNECKC2
50/50
2.955
966661AG1-536 GEN
50/50
6.848
3141843SHACKLE
50/50
0.746
957971AF2-091 GEN
Solar/Wind Harmer
6.372
972135AH1-637 GEN
Solar/Wind Harmer
5.779
316337AD2-073 GEN
Solar/Wind Harmer
1.036
964211AG1-282 GEN
Solar/Wind Harmer
0.882
3141726DUNNSVL
Solar/Wind Harmer
-0.117
962861AG1-135 GEN
Solar/Wind Harmer
9.902
961951AG1-038 GEN
Solar/Wind Harmer
3.243
3138133OCRAN
Solar/Wind Harmer
-0.011
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.817
3142433PROV 92
Solar/Wind Harmer
-0.048
3142433PROV 92
Adder
0.208
3142433PROV 92
Adder
0.208
971317AH1-138 GEN
Solar/Wind Harmer
1.154
316159AE1-175 C
Solar/Wind Harmer
0.227
3138126ROCKLANDING
Solar/Wind Harmer
0.024
944631AF1-128 GEN
Adder
30.026
3142416OLDCHRC
Solar/Wind Harmer
-0.017
3142416OLDCHRC
Solar/Wind Harmer
-0.006
3151171GRAVELC
Adder
0.599
CPLELTFEXP_CPLE->PJM
CLTF
1.996
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.91
LAGNLTFEXP_LAGN->PJM
CLTF
1.485
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.39
TVALTFEXP_TVA->PJM
CLTF
0.75
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.728
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.582
MECLTFEXP_MEC->PJM
CLTF
0.734
SIGELTFEXP_SIGE->PJM
CLTF
0.022
NYPJM->LTFIMP_NY
CLTF
0.565
LGEELTFEXP_LGEE->PJM
CLTF
0.275
WECLTFEXP_WEC->PJM
CLTF
0.137

Details for 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:141.79 %
Rating:671.0 MVA
Rating Type:C
MVA to Mitigate:951.38
MW Contribution:3.79
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
3.026
966661AG1-536 GEN
50/50
7.046
3141843SHACKLE
50/50
0.787
3142433PROV 92
50/50
0.233
3142433PROV 92
50/50
0.233
957971AF2-091 GEN
Solar/Wind Harmer
6.42
972135AH1-637 GEN
Solar/Wind Harmer
5.832
316337AD2-073 GEN
Solar/Wind Harmer
1.054
964211AG1-282 GEN
Solar/Wind Harmer
0.905
3141726DUNNSVL
Solar/Wind Harmer
-0.12
962861AG1-135 GEN
Solar/Wind Harmer
10.198
961951AG1-038 GEN
Solar/Wind Harmer
3.349
3138133OCRAN
Solar/Wind Harmer
-0.012
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.916
3142433PROV 92
Solar/Wind Harmer
-0.051
971317AH1-138 GEN
Solar/Wind Harmer
1.283
316159AE1-175 C
Solar/Wind Harmer
0.254
3138126ROCKLANDING
Solar/Wind Harmer
0.027
944631AF1-128 GEN
Adder
32.493
3151171GRAVELC
Adder
0.677
961611AG1-000B GEN
Solar/Wind Harmer
3.494
971647AH1-324 GEN
Solar/Wind Harmer
3.511
3145336SMITFLD
Solar/Wind Harmer
-0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.095
316458AB2-190 GEN2
Solar/Wind Harmer
0.694
970129AG2-093 GEN
Solar/Wind Harmer
1.562
316072AD1-144
Solar/Wind Harmer
0.138
316294AC1-161 GEN
Solar/Wind Harmer
2.172
316375AC2-012 GEN
Solar/Wind Harmer
2.296
3150981CHESPKA
Adder
0.737
3143096IRON208
Adder
0.246
3142416OLDCHRC
Solar/Wind Harmer
-0.017
3142416OLDCHRC
Solar/Wind Harmer
-0.007
944591AF1-124 GEN
Solar/Wind Harmer
30.01
316246AF1-032 C
Solar/Wind Harmer
0.132
316388AE2-253 GEN
Solar/Wind Harmer
0.439
3146456SLIGO L269
Solar/Wind Harmer
-0.006
316093AE2-104_GEN
Solar/Wind Harmer
1.855
3150331BIRCHWDA
50/50
158.648
3141316ARNOLDS
50/50
2.024
3150351NORNECKC2
50/50
3.077
970575AG2-366 GEN
50/50
3.788
315749AE2-041 GEN
50/50
5.221
3141843SHACKLE
50/50
0.787
3142433PROV 92
50/50
0.233
3142433PROV 92
50/50
0.233
970737AG2-469 GEN
Solar/Wind Harmer
26.848
3141906WESTMOR
Solar/Wind Harmer
-0.019
316404AE1-155 C
Solar/Wind Harmer
5.369
316484AD2-074 GEN
Solar/Wind Harmer
6.401
970009AG2-005 GEN
Solar/Wind Harmer
3.178
962971AG1-146 GEN
Solar/Wind Harmer
4.489
316156AD2-030 GEN
Solar/Wind Harmer
0.464
3141873WAN 176
Solar/Wind Harmer
2.06
316280AD1-041 GEN
Solar/Wind Harmer
1.262
3141766HARMONY
Solar/Wind Harmer
1.469
316203AE2-005 GEN
Solar/Wind Harmer
6.877
316382AG1-145 C
Solar/Wind Harmer
0.285
3150921YORKTN3
Adder
2.048
3144216WINCHST
Adder
0.297
3142946ENON
Solar/Wind Harmer
-0.003
970293AG2-193 GEN
Solar/Wind Harmer
0.932
3151221GRAVEL6
Adder
4.627
3151171GRAVELC
Adder
0.89
961611AG1-000B GEN
Solar/Wind Harmer
1.491
3145336SMITFLD
Solar/Wind Harmer
-0.003
315778AD1-151 GEN
Solar/Wind Harmer
5.997
970129AG2-093 GEN
Solar/Wind Harmer
3.855
970133AG2-095 GEN
Solar/Wind Harmer
0.758
3144536CHRHLND
Solar/Wind Harmer
-0.001
315773AC2-141 GEN
Solar/Wind Harmer
2.81
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.478
3143096IRON208
Adder
0.246
3143096IRON208
Adder
0.241
3142416OLDCHRC
Solar/Wind Harmer
0.665
944581AF1-123 GEN
Solar/Wind Harmer
29.902
944601AF1-125 GEN
Solar/Wind Harmer
29.435
3146456SLIGO L269
Solar/Wind Harmer
-0.006
971153AH1-033 GEN
Solar/Wind Harmer
0.79
316320Y1-086
Solar/Wind Harmer
0.374
957191AF2-013 GEN
50/50
65.961
3150341NORNECKC1
50/50
3.178
3150341NORNECKC1
50/50
3.153
963611AG1-210 GEN
50/50
1.017
316077AC2-138 C
Solar/Wind Harmer
0.678
958261AF2-120 GEN
Solar/Wind Harmer
10.785
316487AF1-042 GEN
Solar/Wind Harmer
3.349
316441AF1-014 GEN
Solar/Wind Harmer
1.1
316075AC2-137 C
Solar/Wind Harmer
0.231
3142946ENON
Solar/Wind Harmer
-0.001
316033AB2-134 GEN
Solar/Wind Harmer
2.247
315697AD1-025 GEN
Solar/Wind Harmer
1.409
316236AE1-162_GEN
Solar/Wind Harmer
0.21
316036AC1-147 C
Solar/Wind Harmer
0.179
3150991CHESPKB
Adder
0.619
3150991CHESPKB
Adder
0.604
316316AC1-027 C
Solar/Wind Harmer
0.203
3142956BIRDNECK
Solar/Wind Harmer
0.354
316185AD1-033 GEN
Solar/Wind Harmer
0.693
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316339AD2-160 GEN
Solar/Wind Harmer
0.439
316018AA1-139 ULT2
Solar/Wind Harmer
0.557
316017AA1-139 ULT1
Solar/Wind Harmer
0.526
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.766
3130086AYDLETT
Solar/Wind Harmer
-0.026
3150691DARBY 3
Adder
4.114
3150701DARBY 4
Adder
4.104
3150681DARBY 2
Adder
4.1
3150671DARBY 1
Adder
4.095
3146386ELIZ CT
Solar/Wind Harmer
-0.006
315759AF1-018 GEN
50/50
5.221
3142433PROV 92
50/50
0.233
3142433PROV 92
50/50
0.233
944491AF1-114 GEN
Solar/Wind Harmer
18.883
316223AC1-118
Solar/Wind Harmer
1.264
3141813NORNECK
Solar/Wind Harmer
-0.032
962981AG1-147 GEN
Solar/Wind Harmer
10.474
3141783LANCAST
Solar/Wind Harmer
-0.013
3141783LANCAST
Solar/Wind Harmer
-0.008
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.02
957601AF2-054 GEN
Solar/Wind Harmer
0.519
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
2.019
315666AE1-190 GEN
Solar/Wind Harmer
0.505
316059AD1-063 C
Solar/Wind Harmer
0.373
316314AB2-024 C
Solar/Wind Harmer
1.365
3143873LANEXA
Solar/Wind Harmer
-0.009
957831AF2-077 GEN
Solar/Wind Harmer
0.393
3138283WHITEMARSH
Solar/Wind Harmer
0.02
971167AH1-042 GEN
Solar/Wind Harmer
11.736
315976AC1-164 GENA
Solar/Wind Harmer
10.45
316169AC1-164_GENC
Solar/Wind Harmer
9.028
315975AC1-164 GENB
Solar/Wind Harmer
0.309
972265AH1-717 GEN
Adder
4.942
3151201GRAVEL4
Adder
4.633
3151191GRAVEL3
Adder
4.574
3151211GRAVEL5
Adder
4.574
971445AH1-216 GEN
Solar/Wind Harmer
4.315
316369SG1_INVT
Solar/Wind Harmer
1.245
316132AB2-190 GEN1
Solar/Wind Harmer
0.694
3152611GOSPORTB
Adder
0.752
3152621GOSPORTC
Adder
0.638
3152601GOSPORTA
Adder
0.589
3151081ELIZAR1
Adder
5.409
3151091ELIZAR2
Adder
5.315
316312AB1-027
Solar/Wind Harmer
0.222
316305AF2-043 C
Solar/Wind Harmer
0.196
957871AF2-081 GEN
Solar/Wind Harmer
3.251
319010AE1-072 C
Solar/Wind Harmer
1.31
3146406KITTY HAWK
Solar/Wind Harmer
0.005
313526AB2-022
Solar/Wind Harmer
0.172
315835AF2-110_GEN
Solar/Wind Harmer
0.797
3146486SUNBURY
Solar/Wind Harmer
-0.006
3146486SUNBURY
Solar/Wind Harmer
-0.006
316321Z2-027
Solar/Wind Harmer
0.171
3146396TANGLEW
Solar/Wind Harmer
0.117
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3141426STAFORD
Solar/Wind Helper
0.031
CPLELTFEXP_CPLE->PJM
CLTF
2.221
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.105
LAGNLTFEXP_LAGN->PJM
CLTF
1.55
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.805
TVALTFEXP_TVA->PJM
CLTF
0.781
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.555
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.668
MECLTFEXP_MEC->PJM
CLTF
0.73
SIGELTFEXP_SIGE->PJM
CLTF
0.022
NYPJM->LTFIMP_NY
CLTF
0.582
LGEELTFEXP_LGEE->PJM
CLTF
0.268
WECLTFEXP_WEC->PJM
CLTF
0.133

Details for 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.81 %
Rating:548.02 MVA
Rating Type:B
MVA to Mitigate:760.68
MW Contribution:3.66
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
2.956
966661AG1-536 GEN
50/50
6.849
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
971353AH1-157 GEN
50/50
7.408
970017AG2-010 GEN
50/50
4.699
3150641CHESTS8
50/50
0.203
944631AF1-128 GEN
50/50
31.925
972135AH1-637 GEN
Solar/Wind Harmer
4.389
316337AD2-073 GEN
Solar/Wind Harmer
0.299
3141726DUNNSVL
Solar/Wind Harmer
1.044
962861AG1-135 GEN
Solar/Wind Harmer
7.523
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
971317AH1-138 GEN
Solar/Wind Harmer
0.613
316159AE1-175 C
Solar/Wind Harmer
0.065
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3142416OLDCHRC
Solar/Wind Harmer
0.149
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.6
3150331BIRCHWDA
50/50
158.356
3141316ARNOLDS
50/50
2.018
3150351NORNECKC2
50/50
3.006
970575AG2-366 GEN
50/50
3.66
315749AE2-041 GEN
50/50
4.946
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150921YORKTN3
50/50
1.929
3144216WINCHST
50/50
0.279
3151161SURRY 1
50/50
2.166
970737AG2-469 GEN
Solar/Wind Harmer
20.178
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.637
962971AG1-146 GEN
Solar/Wind Harmer
3.294
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.61
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.855
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.668
3142416OLDCHRC
Solar/Wind Harmer
0.555
3151221GRAVEL6
Adder
4.099
3151171GRAVELC
Adder
0.789
957191AF2-013 GEN
50/50
65.713
3150341NORNECKC1
50/50
3.105
3150341NORNECKC1
50/50
3.08
963611AG1-210 GEN
50/50
0.994
3150621CHESTS7
50/50
0.184
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
7.962
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.007
315759AF1-018 GEN
50/50
4.946
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150611CHESTG7
50/50
0.401
3150631CHESTG8
50/50
0.394
971047AG2-646 GEN
50/50
11.221
972263AH1-716 GEN
50/50
32.871
944491AF1-114 GEN
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Harmer
0.296
3141813NORNECK
Solar/Wind Harmer
0.279
970327AG2-215 GEN
Solar/Wind Harmer
7.194
962981AG1-147 GEN
Solar/Wind Harmer
7.685
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.051
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
0.029
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.081
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
9.122
315976AC1-164 GENA
Solar/Wind Harmer
8.292
316169AC1-164_GENC
Solar/Wind Harmer
7.163
315975AC1-164 GENB
Solar/Wind Harmer
0.245
316312AB1-027
Solar/Wind Harmer
0.102
972265AH1-717 GEN
Adder
4.377
3151201GRAVEL4
Adder
4.104
3151191GRAVEL3
Adder
4.052
3151211GRAVEL5
Adder
4.052
3141426STAFORD
Solar/Wind Helper
0.031
CPLELTFEXP_CPLE->PJM
CLTF
1.997
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.895
LAGNLTFEXP_LAGN->PJM
CLTF
1.483
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.388
TVALTFEXP_TVA->PJM
CLTF
0.749
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.711
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.577
MECLTFEXP_MEC->PJM
CLTF
0.732
SIGELTFEXP_SIGE->PJM
CLTF
0.022
NYPJM->LTFIMP_NY
CLTF
0.564
LGEELTFEXP_LGEE->PJM
CLTF
0.274
WECLTFEXP_WEC->PJM
CLTF
0.137

Details for 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: 574T575_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 574T575_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.27 %
Rating:671.0 MVA
Rating Type:C
MVA to Mitigate:887.51
MW Contribution:3.69
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
2.966
966661AG1-536 GEN
50/50
6.885
3141843SHACKLE
50/50
0.757
957971AF2-091 GEN
Solar/Wind Harmer
6.359
972135AH1-637 GEN
Solar/Wind Harmer
5.77
316337AD2-073 GEN
Solar/Wind Harmer
1.037
964211AG1-282 GEN
Solar/Wind Harmer
0.886
3141726DUNNSVL
Solar/Wind Harmer
-0.117
962861AG1-135 GEN
Solar/Wind Harmer
9.959
961951AG1-038 GEN
Solar/Wind Harmer
3.265
3138133OCRAN
Solar/Wind Harmer
-0.012
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.845
3142433PROV 92
Solar/Wind Harmer
-0.049
3142433PROV 92
Adder
0.212
3142433PROV 92
Adder
0.212
971317AH1-138 GEN
Solar/Wind Harmer
1.192
316159AE1-175 C
Solar/Wind Harmer
0.235
3138126ROCKLANDING
Solar/Wind Harmer
0.025
944631AF1-128 GEN
Adder
31.292
3151171GRAVELC
Adder
0.632
961611AG1-000B GEN
Solar/Wind Harmer
3.282
3142416OLDCHRC
Solar/Wind Harmer
-0.017
3142416OLDCHRC
Solar/Wind Harmer
-0.007
971647AH1-324 GEN
Solar/Wind Harmer
3.315
971069AG2-661 GEN
Solar/Wind Harmer
1.043
316458AB2-190 GEN2
Solar/Wind Harmer
0.665
970129AG2-093 GEN
Solar/Wind Harmer
1.498
3143096IRON208
Adder
0.244
3145336SMITFLD
Solar/Wind Harmer
-0.026
315759AF1-018 GEN
50/50
5.017
944491AF1-114 GEN
Solar/Wind Harmer
18.704
316223AC1-118
Solar/Wind Harmer
1.247
3141813NORNECK
Solar/Wind Harmer
-0.031
962981AG1-147 GEN
Solar/Wind Harmer
10.194
3141783LANCAST
Solar/Wind Harmer
-0.012
3141783LANCAST
Solar/Wind Harmer
-0.008
3150331BIRCHWDA
50/50
157.717
3141316ARNOLDS
50/50
2.011
3150351NORNECKC2
50/50
3.016
970575AG2-366 GEN
50/50
3.687
315749AE2-041 GEN
50/50
5.017
3141843SHACKLE
50/50
0.757
970737AG2-469 GEN
Solar/Wind Harmer
26.539
3141906WESTMOR
Solar/Wind Harmer
-0.018
957191AF2-013 GEN
50/50
65.491
3150341NORNECKC1
50/50
3.116
3150341NORNECKC1
50/50
3.091
963611AG1-210 GEN
50/50
0.997
316077AC2-138 C
Solar/Wind Harmer
0.664
958261AF2-120 GEN
Solar/Wind Harmer
10.538
316487AF1-042 GEN
Solar/Wind Harmer
3.265
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.019
957601AF2-054 GEN
Solar/Wind Harmer
0.5
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
1.944
315666AE1-190 GEN
Solar/Wind Harmer
0.486
316059AD1-063 C
Solar/Wind Harmer
0.358
316314AB2-024 C
Solar/Wind Harmer
1.31
3143873LANEXA
Solar/Wind Harmer
-0.008
957831AF2-077 GEN
Solar/Wind Harmer
0.373
3138283WHITEMARSH
Solar/Wind Harmer
0.019
3142433PROV 92
Adder
0.212
3142433PROV 92
Adder
0.212
971167AH1-042 GEN
Solar/Wind Harmer
11.35
315976AC1-164 GENA
Solar/Wind Harmer
9.762
316169AC1-164_GENC
Solar/Wind Harmer
8.433
315975AC1-164 GENB
Solar/Wind Harmer
0.289
972265AH1-717 GEN
Adder
4.614
3151201GRAVEL4
Adder
4.325
3151191GRAVEL3
Adder
4.27
3151211GRAVEL5
Adder
4.27
316312AB1-027
Solar/Wind Harmer
0.224
316369SG1_INVT
Solar/Wind Harmer
1.181
316132AB2-190 GEN1
Solar/Wind Harmer
0.665
971445AH1-216 GEN
Solar/Wind Harmer
4
3141426STAFORD
Solar/Wind Helper
0.033
316404AE1-155 C
Solar/Wind Harmer
5.246
316484AD2-074 GEN
Solar/Wind Harmer
6.24
970009AG2-005 GEN
Solar/Wind Harmer
3.098
962971AG1-146 GEN
Solar/Wind Harmer
4.369
316156AD2-030 GEN
Solar/Wind Harmer
0.446
3141873WAN 176
Solar/Wind Harmer
1.984
316280AD1-041 GEN
Solar/Wind Harmer
1.215
3141766HARMONY
Solar/Wind Harmer
1.411
316203AE2-005 GEN
Solar/Wind Harmer
6.619
3142433PROV 92
Adder
0.212
3142433PROV 92
Adder
0.212
316382AG1-145 C
Solar/Wind Harmer
0.264
3150921YORKTN3
Adder
1.889
3144216WINCHST
Adder
0.274
3142946ENON
Solar/Wind Harmer
-0.003
970293AG2-193 GEN
Solar/Wind Harmer
0.911
3151221GRAVEL6
Adder
4.32
3151171GRAVELC
Adder
0.831
961611AG1-000B GEN
Solar/Wind Harmer
1.4
3142416OLDCHRC
Solar/Wind Harmer
0.671
315778AD1-151 GEN
Solar/Wind Harmer
5.713
970129AG2-093 GEN
Solar/Wind Harmer
3.698
3143096IRON208
Adder
0.244
3143096IRON208
Adder
0.239
970133AG2-095 GEN
Solar/Wind Harmer
0.735
3145336SMITFLD
Solar/Wind Harmer
-0.003
316441AF1-014 GEN
Solar/Wind Harmer
1.058
316075AC2-137 C
Solar/Wind Harmer
0.221
3142946ENON
Solar/Wind Harmer
-0.001
316033AB2-134 GEN
Solar/Wind Harmer
2.132
315697AD1-025 GEN
Solar/Wind Harmer
1.337
3150691DARBY 3
Adder
4.134
3150701DARBY 4
Adder
4.124
3150681DARBY 2
Adder
4.12
3150671DARBY 1
Adder
4.115
316236AE1-162_GEN
Solar/Wind Harmer
0.194
CPLELTFEXP_CPLE->PJM
CLTF
2.196
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.727
LAGNLTFEXP_LAGN->PJM
CLTF
1.637
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.831
TVALTFEXP_TVA->PJM
CLTF
0.827
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.235
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.846
MECLTFEXP_MEC->PJM
CLTF
0.811
SIGELTFEXP_SIGE->PJM
CLTF
0.025
NYPJM->LTFIMP_NY
CLTF
0.625
LGEELTFEXP_LGEE->PJM
CLTF
0.304
WECLTFEXP_WEC->PJM
CLTF
0.152

Details for 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.94 %
Rating:548.02 MVA
Rating Type:B
MVA to Mitigate:657.28
MW Contribution:3.68
Bus #Bus NameTypeMW Contribution
3150331BIRCHWDA
50/50
158.961
3141316ARNOLDS
50/50
2.026
3150351NORNECKC2
50/50
3.02
970575AG2-366 GEN
50/50
3.68
315749AE2-041 GEN
50/50
4.976
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
3150921YORKTN3
50/50
2.003
3144216WINCHST
50/50
0.289
3151161SURRY 1
50/50
2.191
970737AG2-469 GEN
Solar/Wind Harmer
20.26
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.646
962971AG1-146 GEN
Solar/Wind Harmer
3.312
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.629
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.866
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.022
3151221GRAVEL6
Adder
4.147
3151171GRAVELC
Adder
0.798
970293AG2-193 GEN
Solar/Wind Harmer
0.603
315759AF1-018 GEN
50/50
4.976
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
972263AH1-716 GEN
50/50
35.649
3150611CHESTG7
50/50
0.379
3150631CHESTG8
50/50
0.372
971047AG2-646 GEN
50/50
10.599
944491AF1-114 GEN
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Harmer
0.297
3141813NORNECK
Solar/Wind Harmer
0.28
970327AG2-215 GEN
Solar/Wind Harmer
7.232
962981AG1-147 GEN
Solar/Wind Harmer
7.729
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.074
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.168
3141873WAN 176
Solar/Wind Harmer
0.03
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.097
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
8.942
315976AC1-164 GENA
Solar/Wind Harmer
8.275
316169AC1-164_GENC
Solar/Wind Harmer
7.149
315975AC1-164 GENB
Solar/Wind Harmer
0.245
972265AH1-717 GEN
Adder
4.429
3151201GRAVEL4
Adder
4.152
3151191GRAVEL3
Adder
4.099
3151211GRAVEL5
Adder
4.099
3141426STAFORD
Solar/Wind Helper
0.029
957191AF2-013 GEN
50/50
65.968
3150341NORNECKC1
50/50
3.119
3150341NORNECKC1
50/50
3.094
963611AG1-210 GEN
50/50
0.998
3150621CHESTS7
50/50
0.174
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
8.003
316075AC2-137 C
Solar/Wind Harmer
0.018
3142946ENON
Solar/Wind Harmer
0.007
3150351NORNECKC2
50/50
2.97
966661AG1-536 GEN
50/50
6.884
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
971353AH1-157 GEN
50/50
7.642
970017AG2-010 GEN
50/50
4.875
3150641CHESTS8
50/50
0.192
944631AF1-128 GEN
50/50
30.156
3152331SURRY 2
50/50
2.455
972135AH1-637 GEN
Solar/Wind Harmer
4.407
316337AD2-073 GEN
Solar/Wind Harmer
0.3
3141726DUNNSVL
Solar/Wind Harmer
1.049
962861AG1-135 GEN
Solar/Wind Harmer
7.561
3138133OCRAN
Solar/Wind Harmer
0.104
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.365
3142433PROV 92
Solar/Wind Harmer
0.422
971317AH1-138 GEN
Solar/Wind Harmer
0.633
316159AE1-175 C
Solar/Wind Harmer
0.067
3138126ROCKLANDING
Solar/Wind Harmer
0.034
3151171GRAVELC
Adder
0.607
CPLELTFEXP_CPLE->PJM
CLTF
1.912
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.152
LAGNLTFEXP_LAGN->PJM
CLTF
1.213
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.047
TVALTFEXP_TVA->PJM
CLTF
0.609
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.061
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.057
MECLTFEXP_MEC->PJM
CLTF
0.525
SIGELTFEXP_SIGE->PJM
CLTF
0.016
NYPJM->LTFIMP_NY
CLTF
0.465
LGEELTFEXP_LGEE->PJM
CLTF
0.185
WECLTFEXP_WEC->PJM
CLTF
0.092

Details for 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.13 %
Rating:671.0 MVA
Rating Type:C
MVA to Mitigate:772.52
MW Contribution:3.66
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
4.944
944491AF1-114 GEN
Solar/Wind Harmer
18.743
316223AC1-118
Solar/Wind Harmer
1.247
3141813NORNECK
Solar/Wind Harmer
-0.031
962981AG1-147 GEN
Solar/Wind Harmer
10.117
3141783LANCAST
Solar/Wind Harmer
-0.012
3141783LANCAST
Solar/Wind Harmer
-0.008
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.019
957601AF2-054 GEN
Solar/Wind Harmer
0.493
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
1.916
315666AE1-190 GEN
Solar/Wind Harmer
0.479
316059AD1-063 C
Solar/Wind Harmer
0.353
316314AB2-024 C
Solar/Wind Harmer
1.29
3143873LANEXA
Solar/Wind Harmer
-0.008
957831AF2-077 GEN
Solar/Wind Harmer
0.364
3138283WHITEMARSH
Solar/Wind Harmer
0.019
3142433PROV 92
Adder
0.208
3142433PROV 92
Adder
0.208
971167AH1-042 GEN
Solar/Wind Harmer
11.098
315976AC1-164 GENA
Solar/Wind Harmer
9.485
316169AC1-164_GENC
Solar/Wind Harmer
8.194
315975AC1-164 GENB
Solar/Wind Harmer
0.281
316312AB1-027
Solar/Wind Harmer
0.216
972265AH1-717 GEN
Adder
4.374
3151201GRAVEL4
Adder
4.1
3151191GRAVEL3
Adder
4.048
3151211GRAVEL5
Adder
4.048
3141426STAFORD
Solar/Wind Helper
0.031
3150331BIRCHWDA
50/50
158.344
3141316ARNOLDS
50/50
2.018
3150351NORNECKC2
50/50
3.005
970575AG2-366 GEN
50/50
3.659
315749AE2-041 GEN
50/50
4.944
3141843SHACKLE
50/50
0.746
970737AG2-469 GEN
Solar/Wind Harmer
26.564
3141906WESTMOR
Solar/Wind Harmer
-0.018
316404AE1-155 C
Solar/Wind Harmer
5.218
316484AD2-074 GEN
Solar/Wind Harmer
6.199
970009AG2-005 GEN
Solar/Wind Harmer
3.078
962971AG1-146 GEN
Solar/Wind Harmer
4.336
316156AD2-030 GEN
Solar/Wind Harmer
0.44
3141873WAN 176
Solar/Wind Harmer
1.957
316280AD1-041 GEN
Solar/Wind Harmer
1.198
3141766HARMONY
Solar/Wind Harmer
1.39
316203AE2-005 GEN
Solar/Wind Harmer
6.52
3142433PROV 92
Adder
0.208
3142433PROV 92
Adder
0.208
316382AG1-145 C
Solar/Wind Harmer
0.255
3150921YORKTN3
Adder
1.818
3144216WINCHST
Adder
0.263
3142946ENON
Solar/Wind Harmer
-0.003
970293AG2-193 GEN
Solar/Wind Harmer
0.877
3142416OLDCHRC
Solar/Wind Harmer
0.646
3151221GRAVEL6
Adder
4.095
3151171GRAVELC
Adder
0.788
957191AF2-013 GEN
50/50
65.707
3150341NORNECKC1
50/50
3.104
3150341NORNECKC1
50/50
3.08
963611AG1-210 GEN
50/50
0.993
316077AC2-138 C
Solar/Wind Harmer
0.662
958261AF2-120 GEN
Solar/Wind Harmer
10.482
316487AF1-042 GEN
Solar/Wind Harmer
3.243
316441AF1-014 GEN
Solar/Wind Harmer
1.042
316075AC2-137 C
Solar/Wind Harmer
0.214
3142946ENON
Solar/Wind Harmer
-0.001
3150351NORNECKC2
50/50
2.955
966661AG1-536 GEN
50/50
6.848
3141843SHACKLE
50/50
0.746
957971AF2-091 GEN
Solar/Wind Harmer
6.372
972135AH1-637 GEN
Solar/Wind Harmer
5.779
316337AD2-073 GEN
Solar/Wind Harmer
1.036
964211AG1-282 GEN
Solar/Wind Harmer
0.882
3141726DUNNSVL
Solar/Wind Harmer
-0.117
962861AG1-135 GEN
Solar/Wind Harmer
9.902
961951AG1-038 GEN
Solar/Wind Harmer
3.243
3138133OCRAN
Solar/Wind Harmer
-0.011
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.817
3142433PROV 92
Solar/Wind Harmer
-0.048
3142433PROV 92
Adder
0.208
3142433PROV 92
Adder
0.208
971317AH1-138 GEN
Solar/Wind Harmer
1.154
316159AE1-175 C
Solar/Wind Harmer
0.227
3138126ROCKLANDING
Solar/Wind Harmer
0.024
944631AF1-128 GEN
Adder
30.026
3142416OLDCHRC
Solar/Wind Harmer
-0.017
3142416OLDCHRC
Solar/Wind Harmer
-0.006
3151171GRAVELC
Adder
0.599
CPLELTFEXP_CPLE->PJM
CLTF
1.996
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.91
LAGNLTFEXP_LAGN->PJM
CLTF
1.485
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.39
TVALTFEXP_TVA->PJM
CLTF
0.75
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.728
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.582
MECLTFEXP_MEC->PJM
CLTF
0.734
SIGELTFEXP_SIGE->PJM
CLTF
0.022
NYPJM->LTFIMP_NY
CLTF
0.565
LGEELTFEXP_LGEE->PJM
CLTF
0.275
WECLTFEXP_WEC->PJM
CLTF
0.137

Details for 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.91 %
Rating:671.0 MVA
Rating Type:C
MVA to Mitigate:744.21
MW Contribution:3.64
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
4.91
944491AF1-114 GEN
Solar/Wind Harmer
18.689
316223AC1-118
Solar/Wind Harmer
1.243
3141813NORNECK
Solar/Wind Harmer
-0.031
962981AG1-147 GEN
Solar/Wind Harmer
10.065
3141783LANCAST
Solar/Wind Harmer
-0.012
3141783LANCAST
Solar/Wind Harmer
-0.008
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.019
957601AF2-054 GEN
Solar/Wind Harmer
0.49
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
1.903
315666AE1-190 GEN
Solar/Wind Harmer
0.476
316059AD1-063 C
Solar/Wind Harmer
0.351
316314AB2-024 C
Solar/Wind Harmer
1.281
3143873LANEXA
Solar/Wind Harmer
-0.008
957831AF2-077 GEN
Solar/Wind Harmer
0.361
3138283WHITEMARSH
Solar/Wind Harmer
0.019
3142433PROV 92
Adder
0.206
3142433PROV 92
Adder
0.206
971167AH1-042 GEN
Solar/Wind Harmer
11.004
315976AC1-164 GENA
Solar/Wind Harmer
9.38
316169AC1-164_GENC
Solar/Wind Harmer
8.103
315975AC1-164 GENB
Solar/Wind Harmer
0.278
3141426STAFORD
Solar/Wind Helper
0.031
3150331BIRCHWDA
50/50
157.958
3141316ARNOLDS
50/50
2.013
3150351NORNECKC2
50/50
2.993
970575AG2-366 GEN
50/50
3.64
315749AE2-041 GEN
50/50
4.91
3141843SHACKLE
50/50
0.741
970737AG2-469 GEN
Solar/Wind Harmer
26.481
3141906WESTMOR
Solar/Wind Harmer
-0.018
316404AE1-155 C
Solar/Wind Harmer
5.194
316484AD2-074 GEN
Solar/Wind Harmer
6.168
970009AG2-005 GEN
Solar/Wind Harmer
3.063
962971AG1-146 GEN
Solar/Wind Harmer
4.314
316156AD2-030 GEN
Solar/Wind Harmer
0.438
3141873WAN 176
Solar/Wind Harmer
1.944
316280AD1-041 GEN
Solar/Wind Harmer
1.19
3141766HARMONY
Solar/Wind Harmer
1.381
316203AE2-005 GEN
Solar/Wind Harmer
6.476
3142433PROV 92
Adder
0.206
3142433PROV 92
Adder
0.206
316382AG1-145 C
Solar/Wind Harmer
0.252
3150921YORKTN3
Adder
1.799
3144216WINCHST
Adder
0.26
3142946ENON
Solar/Wind Harmer
-0.002
970293AG2-193 GEN
Solar/Wind Harmer
0.865
3150351NORNECKC2
50/50
2.943
966661AG1-536 GEN
50/50
6.816
3141843SHACKLE
50/50
0.741
957971AF2-091 GEN
Solar/Wind Harmer
6.354
972135AH1-637 GEN
Solar/Wind Harmer
5.761
316337AD2-073 GEN
Solar/Wind Harmer
1.032
964211AG1-282 GEN
Solar/Wind Harmer
0.878
3141726DUNNSVL
Solar/Wind Harmer
-0.116
962861AG1-135 GEN
Solar/Wind Harmer
9.856
961951AG1-038 GEN
Solar/Wind Harmer
3.228
3138133OCRAN
Solar/Wind Harmer
-0.011
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.805
3142433PROV 92
Solar/Wind Harmer
-0.047
3142433PROV 92
Adder
0.206
3142433PROV 92
Adder
0.206
971317AH1-138 GEN
Solar/Wind Harmer
1.142
316159AE1-175 C
Solar/Wind Harmer
0.224
3138126ROCKLANDING
Solar/Wind Harmer
0.024
944631AF1-128 GEN
Adder
29.65
957191AF2-013 GEN
50/50
65.537
3150341NORNECKC1
50/50
3.091
3150341NORNECKC1
50/50
3.067
963611AG1-210 GEN
50/50
0.989
316077AC2-138 C
Solar/Wind Harmer
0.659
958261AF2-120 GEN
Solar/Wind Harmer
10.433
316487AF1-042 GEN
Solar/Wind Harmer
3.228
316441AF1-014 GEN
Solar/Wind Harmer
1.035
316075AC2-137 C
Solar/Wind Harmer
0.211
3142946ENON
Solar/Wind Harmer
-0.001
CPLELTFEXP_CPLE->PJM
CLTF
1.972
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.797
LAGNLTFEXP_LAGN->PJM
CLTF
1.464
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.333
TVALTFEXP_TVA->PJM
CLTF
0.74
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.655
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.545
MECLTFEXP_MEC->PJM
CLTF
0.723
SIGELTFEXP_SIGE->PJM
CLTF
0.022
NYPJM->LTFIMP_NY
CLTF
0.557
LGEELTFEXP_LGEE->PJM
CLTF
0.271
WECLTFEXP_WEC->PJM
CLTF
0.135

Details for 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T557_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.2 %
Rating:671.0 MVA
Rating Type:C
MVA to Mitigate:732.76
MW Contribution:3.74
Bus #Bus NameTypeMW Contribution
3150331BIRCHWDA
50/50
159.142
3141316ARNOLDS
50/50
2.03
3150351NORNECKC2
50/50
3.056
970575AG2-366 GEN
50/50
3.744
315749AE2-041 GEN
50/50
5.114
3141843SHACKLE
50/50
0.77
970737AG2-469 GEN
Solar/Wind Harmer
26.822
3141906WESTMOR
Solar/Wind Harmer
-0.018
316404AE1-155 C
Solar/Wind Harmer
5.321
316484AD2-074 GEN
Solar/Wind Harmer
6.333
970009AG2-005 GEN
Solar/Wind Harmer
3.145
962971AG1-146 GEN
Solar/Wind Harmer
4.437
316156AD2-030 GEN
Solar/Wind Harmer
0.455
3141873WAN 176
Solar/Wind Harmer
2.022
316280AD1-041 GEN
Solar/Wind Harmer
1.237
3141766HARMONY
Solar/Wind Harmer
1.438
316203AE2-005 GEN
Solar/Wind Harmer
6.733
3142433PROV 92
Adder
0.213
3142433PROV 92
Adder
0.213
316382AG1-145 C
Solar/Wind Harmer
0.274
3150921YORKTN3
Adder
1.977
3144216WINCHST
Adder
0.286
3142946ENON
Solar/Wind Harmer
-0.003
970293AG2-193 GEN
Solar/Wind Harmer
0.865
3151221GRAVEL6
Adder
4.409
3151171GRAVELC
Adder
0.848
961611AG1-000B GEN
Solar/Wind Harmer
1.417
3145336SMITFLD
Solar/Wind Harmer
-0.003
315778AD1-151 GEN
Solar/Wind Harmer
5.662
315773AC2-141 GEN
Solar/Wind Harmer
2.698
970129AG2-093 GEN
Solar/Wind Harmer
3.628
3144536CHRHLND
Solar/Wind Harmer
-0.001
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.246
315759AF1-018 GEN
50/50
5.114
944491AF1-114 GEN
Solar/Wind Harmer
18.893
316223AC1-118
Solar/Wind Harmer
1.261
3141813NORNECK
Solar/Wind Harmer
-0.032
962981AG1-147 GEN
Solar/Wind Harmer
10.352
3141783LANCAST
Solar/Wind Harmer
-0.013
3141783LANCAST
Solar/Wind Harmer
-0.008
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.019
957601AF2-054 GEN
Solar/Wind Harmer
0.51
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
1.979
315666AE1-190 GEN
Solar/Wind Harmer
0.495
316059AD1-063 C
Solar/Wind Harmer
0.365
316314AB2-024 C
Solar/Wind Harmer
1.335
3143873LANEXA
Solar/Wind Harmer
-0.009
957831AF2-077 GEN
Solar/Wind Harmer
0.383
3138283WHITEMARSH
Solar/Wind Harmer
0.02
3142433PROV 92
Adder
0.213
3142433PROV 92
Adder
0.213
971167AH1-042 GEN
Solar/Wind Harmer
11.347
315976AC1-164 GENA
Solar/Wind Harmer
9.993
316169AC1-164_GENC
Solar/Wind Harmer
8.633
315975AC1-164 GENB
Solar/Wind Harmer
0.296
972265AH1-717 GEN
Adder
4.709
3151201GRAVEL4
Adder
4.414
3151191GRAVEL3
Adder
4.359
3151211GRAVEL5
Adder
4.359
971445AH1-216 GEN
Solar/Wind Harmer
4.118
316369SG1_INVT
Solar/Wind Harmer
1.177
316132AB2-190 GEN1
Solar/Wind Harmer
0.653
3152611GOSPORTB
Adder
0.72
3152621GOSPORTC
Adder
0.611
3152601GOSPORTA
Adder
0.564
3151081ELIZAR1
Adder
5.18
3151091ELIZAR2
Adder
5.09
3141426STAFORD
Solar/Wind Helper
0.029
957191AF2-013 GEN
50/50
66.107
3150341NORNECKC1
50/50
3.157
3150341NORNECKC1
50/50
3.131
963611AG1-210 GEN
50/50
1.01
316077AC2-138 C
Solar/Wind Harmer
0.673
958261AF2-120 GEN
Solar/Wind Harmer
10.688
316487AF1-042 GEN
Solar/Wind Harmer
3.314
316441AF1-014 GEN
Solar/Wind Harmer
1.076
316075AC2-137 C
Solar/Wind Harmer
0.218
3142946ENON
Solar/Wind Harmer
-0.001
316236AE1-162_GEN
Solar/Wind Harmer
0.2
316033AB2-134 GEN
Solar/Wind Harmer
2.125
315697AD1-025 GEN
Solar/Wind Harmer
1.333
316036AC1-147 C
Solar/Wind Harmer
0.171
3150991CHESPKB
Adder
0.592
3150991CHESPKB
Adder
0.578
316316AC1-027 C
Solar/Wind Harmer
0.194
3142956BIRDNECK
Solar/Wind Harmer
0.339
3150351NORNECKC2
50/50
3.005
966661AG1-536 GEN
50/50
6.983
3141843SHACKLE
50/50
0.77
957971AF2-091 GEN
Solar/Wind Harmer
6.423
972135AH1-637 GEN
Solar/Wind Harmer
5.83
316337AD2-073 GEN
Solar/Wind Harmer
1.05
964211AG1-282 GEN
Solar/Wind Harmer
0.898
3141726DUNNSVL
Solar/Wind Harmer
-0.119
962861AG1-135 GEN
Solar/Wind Harmer
10.102
961951AG1-038 GEN
Solar/Wind Harmer
3.314
3138133OCRAN
Solar/Wind Harmer
-0.012
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.876
3142433PROV 92
Solar/Wind Harmer
-0.049
3142433PROV 92
Adder
0.213
3142433PROV 92
Adder
0.213
971317AH1-138 GEN
Solar/Wind Harmer
1.242
316159AE1-175 C
Solar/Wind Harmer
0.244
3138126ROCKLANDING
Solar/Wind Harmer
0.026
944631AF1-128 GEN
Adder
30.563
3151171GRAVELC
Adder
0.645
961611AG1-000B GEN
Solar/Wind Harmer
3.32
971647AH1-324 GEN
Solar/Wind Harmer
3.329
3145336SMITFLD
Solar/Wind Harmer
-0.026
316072AD1-144
Solar/Wind Harmer
0.132
971069AG2-661 GEN
Solar/Wind Harmer
1.034
316458AB2-190 GEN2
Solar/Wind Harmer
0.653
316294AC1-161 GEN
Solar/Wind Harmer
2.086
970129AG2-093 GEN
Solar/Wind Harmer
1.47
316375AC2-012 GEN
Solar/Wind Harmer
2.199
3150981CHESPKA
Adder
0.706
CPLELTFEXP_CPLE->PJM
CLTF
2.028
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.37
LAGNLTFEXP_LAGN->PJM
CLTF
1.264
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.275
TVALTFEXP_TVA->PJM
CLTF
0.634
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.084
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.136
MECLTFEXP_MEC->PJM
CLTF
0.538
SIGELTFEXP_SIGE->PJM
CLTF
0.016
NYPJM->LTFIMP_NY
CLTF
0.485
LGEELTFEXP_LGEE->PJM
CLTF
0.188
WECLTFEXP_WEC->PJM
CLTF
0.093

Details for 6CHCKAHM-6ELKO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHCKAHM-6ELKO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.39 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:749.18
MW Contribution:2.56
Bus #Bus NameTypeMW Contribution
3150341NORNECKC1
50/50
1.541
3150341NORNECKC1
50/50
1.528
963611AG1-210 GEN
50/50
0.493
3150621CHESTS7
50/50
0.297
958261AF2-120 GEN
Solar/Wind Harmer
4.681
316077AC2-138 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.013
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.015
3150991CHESPKB
Adder
0.825
3150991CHESPKB
Adder
0.805
316316AC1-027 C
Solar/Wind Harmer
0.075
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3145506HICKORY
Solar/Wind Harmer
0.311
3145506HICKORY
Solar/Wind Harmer
0.187
3145506HICKORY
Solar/Wind Harmer
0.047
316339AD2-160 GEN
Solar/Wind Harmer
0.125
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.043
3137176SLIGO L2192
Solar/Wind Harmer
0.305
3146456SLIGO L269
Solar/Wind Harmer
1.356
3130086AYDLETT
Solar/Wind Harmer
0.305
3146386ELIZ CT
Solar/Wind Harmer
0.075
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.072
3141843SHACKLE
50/50
0.805
966661AG1-536 GEN
50/50
4.027
3150351NORNECKC2
50/50
1.467
971353AH1-157 GEN
50/50
11.629
3142433PROV 92
50/50
0.237
3142433PROV 92
50/50
0.237
970017AG2-010 GEN
50/50
7.587
3150641CHESTS8
50/50
0.328
944631AF1-128 GEN
50/50
51.528
3152331SURRY 2
50/50
4.05
3141766HARMONY
Solar/Wind Harmer
0.032
316159AE1-175 C
Solar/Wind Harmer
0.131
971777AH1-397 GEN
Solar/Wind Harmer
0.392
3138133OCRAN
Solar/Wind Harmer
0.088
3141726DUNNSVL
Solar/Wind Harmer
0.58
962861AG1-135 GEN
Solar/Wind Harmer
4.544
971317AH1-138 GEN
Solar/Wind Harmer
0.97
316337AD2-073 GEN
Solar/Wind Harmer
0.112
3142433PROV 92
Solar/Wind Harmer
0.459
3138126ROCKLANDING
Solar/Wind Harmer
0.052
972135AH1-637 GEN
Solar/Wind Harmer
0.821
316294AC1-161 GEN
Solar/Wind Harmer
1.466
316072AD1-144
Solar/Wind Harmer
0.029
3151171GRAVELC
Adder
0.845
3145336SMITFLD
Solar/Wind Harmer
0.317
944591AF1-124 GEN
Solar/Wind Harmer
17.87
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.984
316388AE2-253 GEN
Solar/Wind Harmer
0.242
3146456SLIGO L269
Solar/Wind Harmer
0.077
316246AF1-032 C
Solar/Wind Harmer
0.034
961611AG1-000B GEN
Solar/Wind Harmer
3.97
971647AH1-324 GEN
Solar/Wind Harmer
3.105
3146516WINFALL
Solar/Wind Harmer
0.234
3146516WINFALL
Solar/Wind Harmer
0.072
316093AE2-104_GEN
Solar/Wind Harmer
1.204
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
971069AG2-661 GEN
Solar/Wind Harmer
1.201
3130156CHOWAN
Solar/Wind Harmer
0.067
316458AB2-190 GEN2
Solar/Wind Harmer
0.345
970129AG2-093 GEN
Solar/Wind Harmer
1.811
3145663CRESWEL
Solar/Wind Harmer
0.178
971163AH1-040 GEN
Solar/Wind Harmer
5.075
939411AE1-173 GEN
Solar/Wind Harmer
25.398
3146206CASHIE
Solar/Wind Harmer
0.058
971547AH1-271 GEN
Solar/Wind Harmer
1.231
3142416OLDCHRC
Solar/Wind Helper
1.057
3142416OLDCHRC
Solar/Wind Helper
0.405
315759AF1-018 GEN
50/50
5.733
3142433PROV 92
50/50
0.237
3142433PROV 92
50/50
0.237
3150611CHESTG7
50/50
0.647
3150631CHESTG8
50/50
0.636
971047AG2-646 GEN
50/50
18.112
972263AH1-716 GEN
50/50
58.57
315976AC1-164 GENA
Solar/Wind Harmer
22.099
316169AC1-164_GENC
Solar/Wind Harmer
19.091
315975AC1-164 GENB
Solar/Wind Harmer
0.654
316314AB2-024 C
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.03
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.4
3143873LANEXA
Solar/Wind Harmer
0.089
3141913WHIT STONE
Solar/Wind Harmer
0.147
3138133OCRAN
Solar/Wind Harmer
0.044
3141783LANCAST
Solar/Wind Harmer
0.088
3141783LANCAST
Solar/Wind Harmer
0.058
962981AG1-147 GEN
Solar/Wind Harmer
5.383
970327AG2-215 GEN
Solar/Wind Harmer
4.699
3141813NORNECK
Solar/Wind Harmer
0.139
3138283WHITEMARSH
Solar/Wind Harmer
0.031
316223AC1-118
Solar/Wind Harmer
0.083
971167AH1-042 GEN
Solar/Wind Harmer
9.459
944491AF1-114 GEN
Solar/Wind Harmer
0
972265AH1-717 GEN
Adder
6.165
3151201GRAVEL4
Adder
5.779
3151191GRAVEL3
Adder
5.706
3151211GRAVEL5
Adder
5.706
971445AH1-216 GEN
Solar/Wind Harmer
5.578
3151081ELIZAR1
Adder
7.23
3151091ELIZAR2
Adder
7.104
3152611GOSPORTB
Adder
1.003
3152621GOSPORTC
Adder
0.851
3152601GOSPORTA
Adder
0.785
957871AF2-081 GEN
Solar/Wind Harmer
3.833
319010AE1-072 C
Solar/Wind Harmer
0.385
3146406KITTY HAWK
Solar/Wind Harmer
0.01
316305AF2-043 C
Solar/Wind Harmer
0.001
313526AB2-022
Solar/Wind Harmer
0.04
3146486SUNBURY
Solar/Wind Harmer
0.074
3146486SUNBURY
Solar/Wind Harmer
0.074
316321Z2-027
Solar/Wind Harmer
0.014
3146396TANGLEW
Solar/Wind Harmer
0.204
3145176PASQUOTANK
Solar/Wind Harmer
0.046
315835AF2-110_GEN
Solar/Wind Harmer
0.491
316369SG1_INVT
Solar/Wind Harmer
0.003
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.067
3130156CHOWAN
Solar/Wind Harmer
0.067
316132AB2-190 GEN1
Solar/Wind Harmer
0.345
316311AC2-079 GEN
Solar/Wind Harmer
1.828
315749AE2-041 GEN
50/50
5.733
3141843SHACKLE
50/50
0.805
970575AG2-366 GEN
50/50
2.564
3150351NORNECKC2
50/50
1.491
3150921YORKTN3
50/50
3.133
3142433PROV 92
50/50
0.237
3142433PROV 92
50/50
0.237
3144216WINCHST
50/50
0.45
3151161SURRY 1
50/50
3.05
3141766HARMONY
Solar/Wind Harmer
2.15
316382AG1-145 C
Solar/Wind Harmer
0.001
316156AD2-030 GEN
Solar/Wind Harmer
0.11
3141873WAN 176
Solar/Wind Harmer
2.643
316280AD1-041 GEN
Solar/Wind Harmer
0.003
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
962971AG1-146 GEN
Solar/Wind Harmer
2.307
970009AG2-005 GEN
Solar/Wind Harmer
1.069
316404AE1-155 C
Solar/Wind Harmer
0.032
3142946ENON
Solar/Wind Harmer
0.045
3141906WESTMOR
Solar/Wind Harmer
0.046
970737AG2-469 GEN
Solar/Wind Harmer
4.442
315773AC2-141 GEN
Solar/Wind Harmer
3.089
3151221GRAVEL6
Adder
5.773
3151171GRAVELC
Adder
1.111
3145336SMITFLD
Solar/Wind Harmer
0.032
944581AF1-123 GEN
Solar/Wind Harmer
17.807
944601AF1-125 GEN
Solar/Wind Harmer
17.533
3144536CHRHLND
Solar/Wind Harmer
0.012
3151101ELIZAR3
Adder
7.322
3144873MCLAUGH
Solar/Wind Harmer
0.002
3146456SLIGO L269
Solar/Wind Harmer
0.077
971153AH1-033 GEN
Solar/Wind Harmer
0.886
961611AG1-000B GEN
Solar/Wind Harmer
2.019
316320Y1-086
Solar/Wind Harmer
0
316435W1029_GEN3
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.072
3146626S HERTFORD
Solar/Wind Harmer
0.071
315778AD1-151 GEN
Solar/Wind Harmer
5.404
3146376EDENTON
Solar/Wind Harmer
0.067
3145273HOLLAND
Solar/Wind Harmer
0.05
970129AG2-093 GEN
Solar/Wind Harmer
3.847
315614AA2-178 GEN
Solar/Wind Harmer
0.363
971157AH1-035 GEN
Solar/Wind Harmer
0.726
315737AD1-076 GEN
Solar/Wind Harmer
0.771
970133AG2-095 GEN
Solar/Wind Harmer
0.559
3146206CASHIE
Solar/Wind Harmer
0.058
3146516WINFALL
Solar/Wind Harmer
0.072
3146516WINFALL
Solar/Wind Harmer
0.072
3146626S HERTFORD
Solar/Wind Harmer
0.071
3146626S HERTFORD
Solar/Wind Harmer
0.071
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.079
3146376EDENTON
Solar/Wind Harmer
0.299
3146376EDENTON
Solar/Wind Harmer
0.299
315742AE1-103 GEN
Solar/Wind Harmer
0.001
316065AD1-022 GEN
Solar/Wind Harmer
2.693
316075AC2-137 C
Solar/Wind Helper
1.022
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.044
315816AE2-034 GEN
Solar/Wind Harmer
0.272
3130546PLYMOUTH
Solar/Wind Harmer
0.06
315732AD1-074 GEN1
Solar/Wind Harmer
0.344
315733AD1-074 GEN2
Solar/Wind Harmer
0.344
315735AD1-075 GEN1
Solar/Wind Harmer
0.172
3146206CASHIE
Solar/Wind Harmer
0.058
970601AG2-382 GEN
Solar/Wind Harmer
2.153
316312AB1-027
Solar/Wind Helper
0.774
CPLELTFEXP_CPLE->PJM
CLTF
2.113
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.142
LAGNLTFEXP_LAGN->PJM
CLTF
1.093
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.265
TVALTFEXP_TVA->PJM
CLTF
0.541
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.783
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.778
MECLTFEXP_MEC->PJM
CLTF
0.38
SIGELTFEXP_SIGE->PJM
CLTF
0.011
NYPJM->LTFIMP_NY
CLTF
0.351
LGEELTFEXP_LGEE->PJM
CLTF
0.115
WECLTFEXP_WEC->PJM
CLTF
0.057

Details for 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: 56702_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: 56702_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:125.13 %
Rating:1107.0 MVA
Rating Type:C
MVA to Mitigate:1385.24
MW Contribution:3.86
Bus #Bus NameTypeMW Contribution
315749AE2-041 GEN
50/50
8.574
3141843SHACKLE
50/50
1.242
970575AG2-366 GEN
50/50
3.862
3142433PROV 92
50/50
0.435
3142433PROV 92
50/50
0.435
3150351NORNECKC2
50/50
2.24
3150921YORKTN3
50/50
4.627
3144216WINCHST
50/50
0.678
3143096IRON208
50/50
0.7
3143096IRON208
50/50
0.686
3150801HOPHCF4
50/50
0.906
971211AH1-065 GEN
50/50
1.092
3141766HARMONY
Solar/Wind Harmer
2.412
3142946ENON
Solar/Wind Harmer
-0.009
316203AE2-005 GEN
Solar/Wind Harmer
10.85
316280AD1-041 GEN
Solar/Wind Harmer
1.923
316156AD2-030 GEN
Solar/Wind Harmer
0.673
3141873WAN 176
Solar/Wind Harmer
2.993
316382AG1-145 C
Solar/Wind Harmer
0.746
962971AG1-146 GEN
Solar/Wind Harmer
4.577
316484AD2-074 GEN
Solar/Wind Harmer
6.098
970009AG2-005 GEN
Solar/Wind Harmer
3.028
316404AE1-155 C
Solar/Wind Harmer
4.616
970293AG2-193 GEN
Solar/Wind Harmer
2.767
3141906WESTMOR
Solar/Wind Harmer
-0.008
970737AG2-469 GEN
Solar/Wind Harmer
8.897
3142416OLDCHRC
Solar/Wind Harmer
1.744
970133AG2-095 GEN
Solar/Wind Harmer
1.942
970129AG2-093 GEN
Solar/Wind Harmer
9.555
315778AD1-151 GEN
Solar/Wind Harmer
14.522
961611AG1-000B GEN
Solar/Wind Harmer
3.439
3151221GRAVEL6
Adder
10.443
3151171GRAVELC
Adder
2.009
3145336SMITFLD
Solar/Wind Harmer
-0.006
3144536CHRHLND
Solar/Wind Harmer
-0.002
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
11.542
965281AG1-393 GEN
Solar/Wind Harmer
1.744
315773AC2-141 GEN
Solar/Wind Harmer
5.752
944581AF1-123 GEN
Solar/Wind Harmer
62.362
944601AF1-125 GEN
Solar/Wind Harmer
61.389
315813AE1-149 C
Solar/Wind Harmer
8.496
3146456SLIGO L269
Solar/Wind Harmer
-0.014
971153AH1-033 GEN
Solar/Wind Harmer
1.655
970659AG2-427 GEN
Solar/Wind Harmer
1.277
316083AB2-161 GEN
Solar/Wind Harmer
2.202
970661AG2-428 GEN
Solar/Wind Harmer
2.552
316320Y1-086
Solar/Wind Harmer
0.783
316435W1029_GEN3
Solar/Wind Harmer
2.383
3146516WINFALL
Solar/Wind Harmer
-0.013
3146626S HERTFORD
Solar/Wind Harmer
-0.013
3145273HOLLAND
Solar/Wind Harmer
-0.01
315839AE2-212 C
Solar/Wind Harmer
0.383
3146376EDENTON
Solar/Wind Harmer
-0.012
315614AA2-178 GEN
Solar/Wind Harmer
1.285
3150861SPRUNCD
Adder
0.485
971157AH1-035 GEN
Solar/Wind Harmer
1.439
315737AD1-076 GEN
Solar/Wind Harmer
2.174
3146206CASHIE
Solar/Wind Harmer
-0.011
3156081AA2-088 GEN
Solar/Wind Harmer
3.619
3145893MURPHYS
Solar/Wind Harmer
0.076
3145893MURPHYS
Solar/Wind Harmer
-0.011
957521AF2-046 GEN
Solar/Wind Harmer
8.535
961681AG1-008 GEN
Solar/Wind Harmer
8.535
3156021HOLLOMANSOL
Solar/Wind Harmer
1.456
3146173TUNIS
Solar/Wind Harmer
-0.011
316463AE2-346 GEN
Solar/Wind Harmer
0.172
316140AB2-099
Solar/Wind Harmer
0.072
962331AG1-082 GEN
Solar/Wind Harmer
1.33
3145963POPLR C
Solar/Wind Harmer
-0.01
3146263WOODLND
Solar/Wind Harmer
-0.01
316317KELFORD C
Solar/Wind Harmer
0.478
3145823KELFORD
Solar/Wind Harmer
-0.01
316365GEN2_N
Solar/Wind Harmer
0.678
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3145933PARMELE
Solar/Wind Harmer
-0.01
966801AG1-551 GEN
Solar/Wind Harmer
1.208
966621AG1-532 GEN
Solar/Wind Harmer
0.194
313506AB2-031 GEN
Solar/Wind Harmer
0.769
3145796HORNRTN
Solar/Wind Harmer
-0.038
3145796HORNRTN
Solar/Wind Harmer
-0.009
316210AC1-098 GEN
Solar/Wind Harmer
1.47
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
970917AG2-570 GEN
Solar/Wind Harmer
22.162
3147043LAWRENC
Solar/Wind Harmer
-0.005
315724AD1-057 GEN
Solar/Wind Harmer
0.507
316327AA2-057 GEN
Solar/Wind Harmer
0.886
3146073TAR RVR
Solar/Wind Harmer
-0.009
3146083TARBORO
Solar/Wind Harmer
-0.009
3146233WITAKRS
Solar/Wind Harmer
0.178
3146233WITAKRS
Solar/Wind Harmer
-0.006
3138543CONSLDL
Solar/Wind Harmer
-0.006
961601AG1-000A GEN
Solar/Wind Harmer
3.293
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3141316ARNOLDS
Adder
0.161
3150341NORNECKC1
50/50
2.314
3150341NORNECKC1
50/50
2.295
963611AG1-210 GEN
50/50
0.74
3150621CHESTS7
50/50
0.591
3150781HOPHCF2
50/50
0.623
3150791HOPHCF3
50/50
0.623
3150761HOPPOLC
50/50
0.395
971213AH1-066 GEN
50/50
0.546
316075AC2-137 C
Solar/Wind Harmer
0.756
3142946ENON
Solar/Wind Harmer
-0.003
316441AF1-014 GEN
Solar/Wind Harmer
1.735
316487AF1-042 GEN
Solar/Wind Harmer
3.191
958261AF2-120 GEN
Solar/Wind Harmer
9.272
316077AC2-138 C
Solar/Wind Harmer
0.493
3150691DARBY 3
Adder
10.705
3150701DARBY 4
Adder
10.68
3150681DARBY 2
Adder
10.668
3150671DARBY 1
Adder
10.655
316033AB2-134 GEN
Solar/Wind Harmer
5.366
315697AD1-025 GEN
Solar/Wind Harmer
3.366
316236AE1-162_GEN
Solar/Wind Harmer
0.462
316036AC1-147 C
Solar/Wind Harmer
0.378
3150991CHESPKB
Adder
1.305
3150991CHESPKB
Adder
1.274
316316AC1-027 C
Solar/Wind Harmer
0.426
3142956BIRDNECK
Solar/Wind Harmer
0.744
316185AD1-033 GEN
Solar/Wind Harmer
1.453
3145506HICKORY
Solar/Wind Harmer
-0.055
3145506HICKORY
Solar/Wind Harmer
-0.033
3145506HICKORY
Solar/Wind Harmer
-0.008
3142366NRTHEST
Adder
0.397
316339AD2-160 GEN
Solar/Wind Harmer
0.92
316018AA1-139 ULT2
Solar/Wind Harmer
1.167
316017AA1-139 ULT1
Solar/Wind Harmer
1.102
3137176SLIGO L2192
Solar/Wind Harmer
-0.054
3146456SLIGO L269
Solar/Wind Harmer
1.603
970657AG2-426 GEN
Solar/Wind Harmer
4.237
970657AG2-426 GEN
Solar/Wind Harmer
0.886
3130086AYDLETT
Solar/Wind Harmer
-0.054
3146386ELIZ CT
Solar/Wind Harmer
-0.013
316431W1029_GEN1
Solar/Wind Harmer
2.383
316433W1029_GEN2
Solar/Wind Harmer
2.383
3146516WINFALL
Solar/Wind Harmer
-0.013
3146516WINFALL
Solar/Wind Harmer
-0.013
3146516WINFALL
Solar/Wind Harmer
-0.013
944641AF1-129 GEN
Adder
55.399
316240AF1-291 C
Solar/Wind Harmer
0.391
3146626S HERTFORD
Solar/Wind Harmer
-0.013
3146626S HERTFORD
Solar/Wind Harmer
-0.013
315742AE1-103 GEN
Solar/Wind Harmer
1.299
3146376EDENTON
Solar/Wind Harmer
0.369
3146376EDENTON
Solar/Wind Harmer
0.369
316065AD1-022 GEN
Solar/Wind Harmer
5.637
3145893MURPHYS
Solar/Wind Harmer
0.304
3145893MURPHYS
Solar/Wind Harmer
-0.02
3144356SAPONY
Solar/Wind Harmer
0.378
3146173TUNIS
Solar/Wind Harmer
-0.011
3146173TUNIS
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
316426AA2-053 GEN
Solar/Wind Harmer
0.983
3145933PARMELE
Solar/Wind Harmer
-0.019
3145933PARMELE
Solar/Wind Harmer
-0.01
316181AB2-040 GEN
Solar/Wind Harmer
1.334
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.075
3145593CAROLNA
Solar/Wind Harmer
0.079
3145796HORNRTN
Solar/Wind Harmer
-0.028
3145783HORNRTN
Solar/Wind Harmer
1.127
3145783HORNRTN
Solar/Wind Harmer
0.901
3145783HORNRTN
Solar/Wind Harmer
0.282
3145783HORNRTN
Solar/Wind Harmer
0.113
3143526WINTERP
Solar/Wind Harmer
-0.049
972185AH1-677 GEN
Adder
4.674
972187AH1-678 GEN
Adder
2.339
316274AC1-208 GEN
Solar/Wind Harmer
0.989
970933AG2-581 GEN
Solar/Wind Harmer
8.378
3145493TOT1
Solar/Wind Harmer
0.134
3145453TOT5
Solar/Wind Harmer
0.08
3145603CNETO
Solar/Wind Harmer
0.053
961601AG1-000A GEN
Solar/Wind Harmer
3.252
316263AC1-034 GEN
Solar/Wind Harmer
3.871
970099AG2-077 GEN
Solar/Wind Harmer
8.478
315759AF1-018 GEN
50/50
8.574
3142433PROV 92
50/50
0.435
3142433PROV 92
50/50
0.435
3150611CHESTG7
50/50
1.286
3150631CHESTG8
50/50
1.265
971047AG2-646 GEN
50/50
36.002
315976AC1-164 GENA
Solar/Wind Harmer
37.032
316169AC1-164_GENC
Solar/Wind Harmer
31.992
315975AC1-164 GENB
Solar/Wind Harmer
1.096
316314AB2-024 C
Solar/Wind Harmer
2.414
316059AD1-063 C
Solar/Wind Harmer
0.612
3143873LANEXA
Solar/Wind Harmer
-0.016
315662AE1-191 GEN
Solar/Wind Harmer
3.076
315666AE1-190 GEN
Solar/Wind Harmer
0.769
957601AF2-054 GEN
Solar/Wind Harmer
0.754
3141873WAN 176
Solar/Wind Harmer
-0.005
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.007
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
10.679
3141813NORNECK
Solar/Wind Harmer
-0.023
971167AH1-042 GEN
Solar/Wind Harmer
22.181
957831AF2-077 GEN
Solar/Wind Harmer
0.668
3138283WHITEMARSH
Solar/Wind Harmer
0.034
316223AC1-118
Solar/Wind Harmer
0.531
316312AB1-027
Solar/Wind Harmer
0.583
316132AB2-190 GEN1
Solar/Wind Harmer
1.714
316369SG1_INVT
Solar/Wind Harmer
2.973
972265AH1-717 GEN
Adder
11.153
3151201GRAVEL4
Adder
10.455
3151191GRAVEL3
Adder
10.323
3151211GRAVEL5
Adder
10.323
971445AH1-216 GEN
Solar/Wind Harmer
9.527
944491AF1-114 GEN
Solar/Wind Harmer
4.333
3152611GOSPORTB
Adder
1.587
3152621GOSPORTC
Adder
1.347
3152601GOSPORTA
Adder
1.242
3151081ELIZAR1
Adder
11.396
3151091ELIZAR2
Adder
11.198
316305AF2-043 C
Solar/Wind Harmer
0.413
957871AF2-081 GEN
Solar/Wind Harmer
6.809
319010AE1-072 C
Solar/Wind Harmer
2.743
3146406KITTY HAWK
Solar/Wind Harmer
0.011
315833AF1-017_GEN
Solar/Wind Harmer
2.567
316349AD2-085 GEN
Solar/Wind Harmer
1.202
316311AC2-079 GEN
Solar/Wind Harmer
6.818
315835AF2-110_GEN
Solar/Wind Harmer
1.686
3146486SUNBURY
Solar/Wind Harmer
-0.013
3146486SUNBURY
Solar/Wind Harmer
-0.013
313526AB2-022
Solar/Wind Harmer
0.36
316321Z2-027
Solar/Wind Harmer
0.358
3146396TANGLEW
Solar/Wind Harmer
0.244
3145176PASQUOTANK
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
3.14
3130156CHOWAN
Solar/Wind Harmer
-0.012
3130156CHOWAN
Solar/Wind Harmer
-0.012
3143316POE
Solar/Wind Harmer
-0.048
315816AE2-034 GEN
Solar/Wind Harmer
0.963
971285AH1-108 GEN
Adder
0.794
3130546PLYMOUTH
Solar/Wind Harmer
-0.011
315732AD1-074 GEN1
Solar/Wind Harmer
2.314
315733AD1-074 GEN2
Solar/Wind Harmer
2.314
315735AD1-075 GEN1
Solar/Wind Harmer
1.157
3146206CASHIE
Solar/Wind Harmer
-0.011
970601AG2-382 GEN
Solar/Wind Harmer
4.891
965291AG1-394 GEN
Solar/Wind Harmer
0.979
316318V4-068
Solar/Wind Harmer
0.271
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
-0.011
316315AB2-025 C
Solar/Wind Harmer
0.293
315814AE2-033 C
Solar/Wind Harmer
10.064
3145513AHOSKIE
Solar/Wind Harmer
0.093
961941AG1-037 GEN
Solar/Wind Harmer
0.08
3145513AHOSKIE
Solar/Wind Harmer
-0.011
3145683EARLEYS
Solar/Wind Harmer
-0.021
3145683EARLEYS
Solar/Wind Harmer
-0.011
3145683EARLEYS
Solar/Wind Harmer
-0.011
3146043SEABORD
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
1.024
315652AC1-086 GEN
Solar/Wind Harmer
10.943
3146033SCOT NK
Solar/Wind Harmer
-0.039
941031AE2-094 GEN
Solar/Wind Harmer
18.106
944011AF1-069 GEN
Solar/Wind Harmer
5.673
946281AF1-292 GEN
Solar/Wind Harmer
0.214
316087AB2-174 GEN
Solar/Wind Harmer
1.364
3137643SOCKMAN
Solar/Wind Harmer
-0.038
3145796HORNRTN
Solar/Wind Harmer
-0.03
3145796HORNRTN
Solar/Wind Harmer
-0.004
316233AE1-074 FULL
Solar/Wind Harmer
0.255
971281AH1-106 GEN
Solar/Wind Harmer
1.542
971283AH1-107 GEN
Solar/Wind Harmer
1.542
970673AG2-436 GEN
Solar/Wind Harmer
19.87
970673AG2-436 GEN
Solar/Wind Harmer
10.061
316005AA1-067
Solar/Wind Harmer
0.188
3145746EVERETS
Solar/Wind Harmer
-0.037
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
970181AG2-120 GEN
Solar/Wind Harmer
1.218
971967AH1-528 GEN
Solar/Wind Harmer
17.421
957861AF2-080 GEN
Solar/Wind Harmer
3.908
970085AG2-068 GEN
Solar/Wind Harmer
5.516
970581AG2-369 GEN
Solar/Wind Harmer
4.743
316420AA1-050 GEN
Solar/Wind Harmer
1.001
3145573BETHELC
Solar/Wind Harmer
-0.009
3145573BETHELC
Solar/Wind Harmer
-0.009
316319Z2-044 C
Solar/Wind Harmer
0.471
970831AG2-522 GEN
Solar/Wind Harmer
4.197
3141843SHACKLE
50/50
1.242
966661AG1-536 GEN
50/50
6.058
3142433PROV 92
50/50
0.435
3142433PROV 92
50/50
0.435
3150351NORNECKC2
50/50
2.203
3150641CHESTS8
50/50
0.652
944631AF1-128 GEN
50/50
102.426
971353AH1-157 GEN
50/50
16.966
970017AG2-010 GEN
50/50
11.364
3143096IRON208
50/50
0.7
3150771HOPHCF1
50/50
0.623
3141766HARMONY
Solar/Wind Harmer
-0.005
971777AH1-397 GEN
Solar/Wind Harmer
3.027
3138133OCRAN
Solar/Wind Harmer
-0.015
316159AE1-175 C
Solar/Wind Harmer
0.665
964211AG1-282 GEN
Solar/Wind Harmer
0.733
3141726DUNNSVL
Solar/Wind Harmer
-0.097
961951AG1-038 GEN
Solar/Wind Harmer
3.191
962861AG1-135 GEN
Solar/Wind Harmer
9.003
3142433PROV 92
Solar/Wind Harmer
-0.094
316337AD2-073 GEN
Solar/Wind Harmer
0.586
971317AH1-138 GEN
Solar/Wind Harmer
2.659
3138126ROCKLANDING
Solar/Wind Harmer
0.059
3142416OLDCHRC
Solar/Wind Harmer
-0.045
3142416OLDCHRC
Solar/Wind Harmer
-0.017
970129AG2-093 GEN
Solar/Wind Harmer
3.87
316458AB2-190 GEN2
Solar/Wind Harmer
1.714
971069AG2-661 GEN
Solar/Wind Harmer
2.652
972135AH1-637 GEN
Solar/Wind Harmer
1.651
971647AH1-324 GEN
Solar/Wind Harmer
8.244
961611AG1-000B GEN
Solar/Wind Harmer
8.06
3151171GRAVELC
Adder
1.528
3145336SMITFLD
Solar/Wind Harmer
-0.061
957971AF2-091 GEN
Solar/Wind Harmer
1.473
316072AD1-144
Solar/Wind Harmer
0.294
315671AE2-027_GEN
Solar/Wind Harmer
10.644
316375AC2-012 GEN
Solar/Wind Harmer
4.845
3150981CHESPKA
Adder
1.556
316294AC1-161 GEN
Solar/Wind Harmer
4.447
944591AF1-124 GEN
Solar/Wind Harmer
62.587
3142543TWELFTH
Solar/Wind Harmer
-0.001
316246AF1-032 C
Solar/Wind Harmer
0.277
316388AE2-253 GEN
Solar/Wind Harmer
0.92
3146456SLIGO L269
Solar/Wind Harmer
-0.014
970659AG2-427 GEN
Solar/Wind Harmer
7.209
316381AD1-082 GEN
Solar/Wind Harmer
1.244
970661AG2-428 GEN
Solar/Wind Harmer
14.398
316093AE2-104_GEN
Solar/Wind Harmer
3.922
3146516WINFALL
Solar/Wind Harmer
-0.042
3146516WINFALL
Solar/Wind Harmer
-0.013
315800Z1-036_GEN1
Solar/Wind Harmer
3.14
3130156CHOWAN
Solar/Wind Harmer
-0.012
3145663CRESWEL
Solar/Wind Harmer
-0.033
971163AH1-040 GEN
Solar/Wind Harmer
11.163
3150851SPRUNCC
Adder
0.485
939411AE1-173 GEN
Solar/Wind Harmer
57.436
3146206CASHIE
Solar/Wind Harmer
-0.011
971547AH1-271 GEN
Solar/Wind Harmer
2.795
3145893MURPHYS
Solar/Wind Harmer
-0.043
3145893MURPHYS
Solar/Wind Harmer
0.323
940641AE2-051 GEN
Solar/Wind Harmer
10.065
3146173TUNIS
Solar/Wind Harmer
-0.011
3145683EARLEYS
Solar/Wind Harmer
-0.011
3145963POPLR C
Solar/Wind Harmer
-0.01
316174AB2-169 GEN
Solar/Wind Harmer
1.591
3146263WOODLND
Solar/Wind Harmer
-0.01
3145823KELFORD
Solar/Wind Harmer
-0.01
316023GEN1_S
Solar/Wind Harmer
0.678
316190AA2-174 GEN
Solar/Wind Harmer
0.12
316011AB1-132 GEN
Solar/Wind Harmer
2.035
962571AG1-106 GEN
Solar/Wind Harmer
1.398
3146293MARTNCO
Solar/Wind Harmer
0.06
960081AF2-299 GEN
Solar/Wind Harmer
1.076
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.009
3145783HORNRTN
Solar/Wind Harmer
-0.009
3143526WINTERP
Solar/Wind Harmer
-0.049
316212AC1-099_GEN
Solar/Wind Harmer
0.816
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
971795AH1-408 GEN
Solar/Wind Harmer
6.798
316494AC1-189 GEN
Solar/Wind Harmer
0.961
970919AG2-571 GEN
Solar/Wind Harmer
2.805
3147043LAWRENC
Adder
0.711
970087AG2-069 GEN
Solar/Wind Harmer
8.273
315722AD1-056 GEN
Solar/Wind Harmer
0.923
961671AG1-007 GEN
Solar/Wind Harmer
0.109
3146083TARBORO
Solar/Wind Harmer
-0.009
3145493TOT1
Solar/Wind Harmer
0.256
3146233WITAKRS
Solar/Wind Harmer
-0.034
316129AC1-054 GEN
Solar/Wind Harmer
0.725
316359AB2-059 GEN
Solar/Wind Harmer
1.113
316049AB1-081 GEN
Solar/Wind Harmer
0.891
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3142053HEARTS
Solar/Wind Harmer
0.097
971065AG2-659 GEN
Solar/Wind Harmer
4.078
957481AF2-042 GEN
Solar/Wind Harmer
21.195
CPLELTFEXP_CPLE->PJM
CLTF
4.035
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.643
LAGNLTFEXP_LAGN->PJM
CLTF
1.924
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.054
TVALTFEXP_TVA->PJM
CLTF
0.95
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.999
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.074
MECLTFEXP_MEC->PJM
CLTF
0.569
SIGELTFEXP_SIGE->PJM
CLTF
0.015
NYPJM->LTFIMP_NY
CLTF
0.699
LGEELTFEXP_LGEE->PJM
CLTF
0.151
WECLTFEXP_WEC->PJM
CLTF
0.071

Details for 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 567_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 567_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.77 %
Rating:935.39 MVA
Rating Type:B
MVA to Mitigate:1120.31
MW Contribution:3.86
Bus #Bus NameTypeMW Contribution
3150341NORNECKC1
50/50
2.314
3150341NORNECKC1
50/50
2.295
963611AG1-210 GEN
50/50
0.74
3150621CHESTS7
50/50
0.591
3150781HOPHCF2
50/50
0.623
3150791HOPHCF3
50/50
0.623
3150761HOPPOLC
50/50
0.395
971213AH1-066 GEN
50/50
0.546
316075AC2-137 C
Solar/Wind Harmer
0.069
3142946ENON
Solar/Wind Harmer
0.023
958261AF2-120 GEN
Solar/Wind Harmer
7.042
316077AC2-138 C
Solar/Wind Harmer
0.001
3150691DARBY 3
Adder
10.705
3150701DARBY 4
Adder
10.68
3150681DARBY 2
Adder
10.668
3150671DARBY 1
Adder
10.655
316033AB2-134 GEN
Solar/Wind Harmer
0.009
315697AD1-025 GEN
Solar/Wind Harmer
0.167
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.023
3150991CHESPKB
Adder
1.305
3150991CHESPKB
Adder
1.274
316316AC1-027 C
Solar/Wind Harmer
0.119
3142956BIRDNECK
Solar/Wind Harmer
0
316185AD1-033 GEN
Solar/Wind Harmer
0.003
3145506HICKORY
Solar/Wind Harmer
0.488
3145506HICKORY
Solar/Wind Harmer
0.293
3145506HICKORY
Solar/Wind Harmer
0.073
3142366NRTHEST
Adder
0.397
316339AD2-160 GEN
Solar/Wind Harmer
0.197
316018AA1-139 ULT2
Solar/Wind Harmer
0.003
316017AA1-139 ULT1
Solar/Wind Harmer
0.068
3137176SLIGO L2192
Solar/Wind Harmer
0.481
3146456SLIGO L269
Solar/Wind Harmer
2.138
970657AG2-426 GEN
Solar/Wind Harmer
4.227
970657AG2-426 GEN
Solar/Wind Harmer
0.886
3130086AYDLETT
Solar/Wind Harmer
0.482
3146386ELIZ CT
Solar/Wind Harmer
0.119
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.116
3146516WINFALL
Solar/Wind Harmer
0.116
3146516WINFALL
Solar/Wind Harmer
0.116
944641AF1-129 GEN
Adder
55.399
316240AF1-291 C
Solar/Wind Harmer
0.001
3146626S HERTFORD
Solar/Wind Harmer
0.115
3146626S HERTFORD
Solar/Wind Harmer
0.115
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.491
3146376EDENTON
Solar/Wind Harmer
0.491
316065AD1-022 GEN
Solar/Wind Harmer
4.62
3145893MURPHYS
Solar/Wind Harmer
0.648
3145893MURPHYS
Solar/Wind Harmer
0.174
3144356SAPONY
Solar/Wind Harmer
0.808
3146173TUNIS
Solar/Wind Harmer
0.095
3146173TUNIS
Solar/Wind Harmer
0.095
3142666NORTHAMPTON
Solar/Wind Harmer
0.088
3142666NORTHAMPTON
Solar/Wind Harmer
0.088
3142666NORTHAMPTON
Solar/Wind Harmer
0.088
3142666NORTHAMPTON
Solar/Wind Harmer
0.053
316426AA2-053 GEN
Solar/Wind Harmer
0.293
3145933PARMELE
Solar/Wind Harmer
0.172
3145933PARMELE
Solar/Wind Harmer
0.086
316181AB2-040 GEN
Solar/Wind Harmer
0.123
3145593CAROLNA
Solar/Wind Harmer
0.085
3145593CAROLNA
Solar/Wind Harmer
0.085
966811AG1-552 GEN
Solar/Wind Harmer
0.922
3145593CAROLNA
Solar/Wind Harmer
0.106
3145796HORNRTN
Solar/Wind Harmer
0.254
3145783HORNRTN
Solar/Wind Harmer
1.502
3145783HORNRTN
Solar/Wind Harmer
1.202
3145783HORNRTN
Solar/Wind Harmer
0.376
3145783HORNRTN
Solar/Wind Harmer
0.15
3143526WINTERP
Solar/Wind Harmer
0.439
972185AH1-677 GEN
Adder
4.674
972187AH1-678 GEN
Adder
2.339
316274AC1-208 GEN
Solar/Wind Harmer
0.423
970933AG2-581 GEN
Solar/Wind Harmer
6.363
3145493TOT1
Solar/Wind Harmer
0.178
3145453TOT5
Solar/Wind Harmer
0.107
3145603CNETO
Solar/Wind Harmer
0.071
961601AG1-000A GEN
Solar/Wind Harmer
1.309
316263AC1-034 GEN
Solar/Wind Harmer
2.793
970099AG2-077 GEN
Solar/Wind Harmer
7.694
971223AH1-071 GEN
Solar/Wind Harmer
0.72
939181AE1-148 GEN
Solar/Wind Harmer
3.206
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
2.881
964791AG1-342 GEN
Solar/Wind Harmer
1.14
3146843MT LREL
Solar/Wind Harmer
0.059
3146843MT LREL
Solar/Wind Harmer
0.059
970323AG2-213 GEN
Solar/Wind Harmer
2.53
971775AH1-396 GEN
Solar/Wind Harmer
0.095
316034AC1-036 C
Solar/Wind Harmer
0.004
971741AH1-377 GEN
Solar/Wind Harmer
5.844
966871AG1-558 GEN
Solar/Wind Harmer
0.065
3141843SHACKLE
50/50
1.242
966661AG1-536 GEN
50/50
6.058
3142433PROV 92
50/50
0.435
3142433PROV 92
50/50
0.435
3150351NORNECKC2
50/50
2.203
3150641CHESTS8
50/50
0.652
944631AF1-128 GEN
50/50
102.426
971353AH1-157 GEN
50/50
16.966
970017AG2-010 GEN
50/50
11.364
3143096IRON208
50/50
0.7
3150771HOPHCF1
50/50
0.623
3141766HARMONY
Solar/Wind Harmer
0.048
971777AH1-397 GEN
Solar/Wind Harmer
0.605
3138133OCRAN
Solar/Wind Harmer
0.133
316159AE1-175 C
Solar/Wind Harmer
0.19
3141726DUNNSVL
Solar/Wind Harmer
0.868
962861AG1-135 GEN
Solar/Wind Harmer
6.837
3142433PROV 92
Solar/Wind Harmer
0.844
316337AD2-073 GEN
Solar/Wind Harmer
0.169
971317AH1-138 GEN
Solar/Wind Harmer
1.414
3138126ROCKLANDING
Solar/Wind Harmer
0.078
3142416OLDCHRC
Solar/Wind Harmer
0.4
3142416OLDCHRC
Solar/Wind Harmer
0.153
970129AG2-093 GEN
Solar/Wind Harmer
4.296
316458AB2-190 GEN2
Solar/Wind Harmer
0.809
971069AG2-661 GEN
Solar/Wind Harmer
2.652
972135AH1-637 GEN
Solar/Wind Harmer
1.254
971647AH1-324 GEN
Solar/Wind Harmer
6.261
961611AG1-000B GEN
Solar/Wind Harmer
7.623
3151171GRAVELC
Adder
1.528
3145336SMITFLD
Solar/Wind Harmer
0.545
316072AD1-144
Solar/Wind Harmer
0.047
315671AE2-027_GEN
Solar/Wind Harmer
8.084
316375AC2-012 GEN
Solar/Wind Harmer
0.003
3150981CHESPKA
Adder
1.556
316294AC1-161 GEN
Solar/Wind Harmer
2.12
944591AF1-124 GEN
Solar/Wind Harmer
27.57
3142543TWELFTH
Solar/Wind Harmer
0.012
316246AF1-032 C
Solar/Wind Harmer
0.055
316388AE2-253 GEN
Solar/Wind Harmer
0.38
3146456SLIGO L269
Solar/Wind Harmer
0.121
970659AG2-427 GEN
Solar/Wind Harmer
5.84
316381AD1-082 GEN
Solar/Wind Harmer
0.126
970661AG2-428 GEN
Solar/Wind Harmer
11.997
316093AE2-104_GEN
Solar/Wind Harmer
2.019
3146516WINFALL
Solar/Wind Harmer
0.377
3146516WINFALL
Solar/Wind Harmer
0.116
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.111
3145663CRESWEL
Solar/Wind Harmer
0.297
971163AH1-040 GEN
Solar/Wind Harmer
8.478
3150851SPRUNCC
Adder
0.485
939411AE1-173 GEN
Solar/Wind Harmer
43.623
3146206CASHIE
Solar/Wind Harmer
0.099
971547AH1-271 GEN
Solar/Wind Harmer
2.123
3145893MURPHYS
Solar/Wind Harmer
0.387
3145893MURPHYS
Solar/Wind Harmer
0.431
940641AE2-051 GEN
Solar/Wind Harmer
7.644
3146173TUNIS
Solar/Wind Harmer
0.095
3145683EARLEYS
Solar/Wind Harmer
0.094
3145963POPLR C
Solar/Wind Harmer
0.093
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.091
3145823KELFORD
Solar/Wind Harmer
0.09
316023GEN1_S
Solar/Wind Harmer
0.201
316190AA2-174 GEN
Solar/Wind Harmer
0
316011AB1-132 GEN
Solar/Wind Harmer
1.573
962571AG1-106 GEN
Solar/Wind Harmer
1.231
3146293MARTNCO
Solar/Wind Harmer
0.08
960081AF2-299 GEN
Solar/Wind Harmer
0.817
3145796HORNRTN
Solar/Wind Harmer
0.279
3145796HORNRTN
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
0.084
3143526WINTERP
Solar/Wind Harmer
0.439
316212AC1-099_GEN
Solar/Wind Harmer
0.431
3145746EVERETS
Solar/Wind Harmer
0.083
3145746EVERETS
Solar/Wind Harmer
0.083
971795AH1-408 GEN
Solar/Wind Harmer
5.378
316494AC1-189 GEN
Solar/Wind Harmer
0.269
970919AG2-571 GEN
Solar/Wind Harmer
2.805
3147043LAWRENC
Adder
0.711
970087AG2-069 GEN
Solar/Wind Harmer
6.284
315722AD1-056 GEN
Solar/Wind Harmer
0.497
961671AG1-007 GEN
Solar/Wind Harmer
0.012
3146083TARBORO
Solar/Wind Harmer
0.077
3145493TOT1
Solar/Wind Harmer
0.342
3146233WITAKRS
Solar/Wind Harmer
0.302
316129AC1-054 GEN
Solar/Wind Harmer
0.277
316359AB2-059 GEN
Solar/Wind Harmer
0.264
316049AB1-081 GEN
Solar/Wind Harmer
0.421
3145543BTLEBRO
Solar/Wind Harmer
0.073
3145543BTLEBRO
Solar/Wind Harmer
0.059
3142053HEARTS
Solar/Wind Harmer
0.129
971065AG2-659 GEN
Solar/Wind Harmer
3.097
957481AF2-042 GEN
Solar/Wind Harmer
19.236
315693AD1-088 GEN
Solar/Wind Harmer
3.297
962491AG1-098 GEN
Solar/Wind Harmer
3.883
3143226MDLTHAN
Solar/Wind Harmer
0.067
315687AD1-152 GEN
Solar/Wind Harmer
0.002
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970401AG2-262 GEN
Solar/Wind Harmer
0.348
315749AE2-041 GEN
50/50
8.574
3141843SHACKLE
50/50
1.242
970575AG2-366 GEN
50/50
3.862
3142433PROV 92
50/50
0.435
3142433PROV 92
50/50
0.435
3150351NORNECKC2
50/50
2.24
3150921YORKTN3
50/50
4.627
3144216WINCHST
50/50
0.678
3143096IRON208
50/50
0.7
3143096IRON208
50/50
0.686
3150801HOPHCF4
50/50
0.906
971211AH1-065 GEN
50/50
1.092
3141766HARMONY
Solar/Wind Harmer
3.215
3142946ENON
Solar/Wind Harmer
0.078
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.005
316156AD2-030 GEN
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
3.99
316382AG1-145 C
Solar/Wind Harmer
0.002
962971AG1-146 GEN
Solar/Wind Harmer
3.476
970009AG2-005 GEN
Solar/Wind Harmer
1.61
316404AE1-155 C
Solar/Wind Harmer
0.048
970293AG2-193 GEN
Solar/Wind Harmer
2.101
3141906WESTMOR
Solar/Wind Harmer
0.07
970737AG2-469 GEN
Solar/Wind Harmer
6.757
3142416OLDCHRC
Solar/Wind Harmer
1.491
970133AG2-095 GEN
Solar/Wind Harmer
1.475
970129AG2-093 GEN
Solar/Wind Harmer
9.13
315778AD1-151 GEN
Solar/Wind Harmer
11.936
961611AG1-000B GEN
Solar/Wind Harmer
3.876
3151221GRAVEL6
Adder
10.443
3151171GRAVELC
Adder
2.009
3145336SMITFLD
Solar/Wind Harmer
0.055
3144536CHRHLND
Solar/Wind Harmer
0.019
3144873MCLAUGH
Solar/Wind Harmer
0.003
3151101ELIZAR3
Adder
11.542
965281AG1-393 GEN
Solar/Wind Harmer
1.324
315773AC2-141 GEN
Solar/Wind Harmer
4.468
944581AF1-123 GEN
Solar/Wind Harmer
27.472
944601AF1-125 GEN
Solar/Wind Harmer
27.049
315813AE1-149 C
Solar/Wind Harmer
6.453
3146456SLIGO L269
Solar/Wind Harmer
0.121
971153AH1-033 GEN
Solar/Wind Harmer
1.397
970659AG2-427 GEN
Solar/Wind Harmer
1.277
316083AB2-161 GEN
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
2.552
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.116
3146626S HERTFORD
Solar/Wind Harmer
0.115
3145273HOLLAND
Solar/Wind Harmer
0.085
315839AE2-212 C
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.11
315614AA2-178 GEN
Solar/Wind Harmer
0.606
3150861SPRUNCD
Adder
0.485
971157AH1-035 GEN
Solar/Wind Harmer
1.23
315737AD1-076 GEN
Solar/Wind Harmer
1.31
3146206CASHIE
Solar/Wind Harmer
0.099
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3145893MURPHYS
Solar/Wind Harmer
0.162
3145893MURPHYS
Solar/Wind Harmer
0.097
957521AF2-046 GEN
Solar/Wind Harmer
7.177
961681AG1-008 GEN
Solar/Wind Harmer
7.177
3156021HOLLOMANSOL
Solar/Wind Harmer
0.437
3146173TUNIS
Solar/Wind Harmer
0.095
316463AE2-346 GEN
Solar/Wind Harmer
0.081
316140AB2-099
Solar/Wind Harmer
0.034
962331AG1-082 GEN
Solar/Wind Harmer
1.01
3145963POPLR C
Solar/Wind Harmer
0.093
3146263WOODLND
Solar/Wind Harmer
0.091
316317KELFORD C
Solar/Wind Harmer
0.009
3145823KELFORD
Solar/Wind Harmer
0.09
316365GEN2_N
Solar/Wind Harmer
0.201
3142666NORTHAMPTON
Solar/Wind Harmer
0.088
3145933PARMELE
Solar/Wind Harmer
0.086
966801AG1-551 GEN
Solar/Wind Harmer
1.002
313506AB2-031 GEN
Solar/Wind Harmer
0.263
3145796HORNRTN
Solar/Wind Harmer
0.338
3145796HORNRTN
Solar/Wind Harmer
0.085
316210AC1-098 GEN
Solar/Wind Harmer
0.773
3145746EVERETS
Solar/Wind Harmer
0.083
3145746EVERETS
Solar/Wind Harmer
0.083
970917AG2-570 GEN
Solar/Wind Harmer
7.013
3147043LAWRENC
Solar/Wind Harmer
0.047
315724AD1-057 GEN
Solar/Wind Harmer
0.295
316327AA2-057 GEN
Solar/Wind Harmer
0.118
3146073TAR RVR
Solar/Wind Harmer
0.077
3146083TARBORO
Solar/Wind Harmer
0.077
3146233WITAKRS
Solar/Wind Harmer
0.38
3146233WITAKRS
Solar/Wind Harmer
0.052
3138543CONSLDL
Solar/Wind Harmer
0.05
961601AG1-000A GEN
Solar/Wind Harmer
5.236
3145543BTLEBRO
Solar/Wind Harmer
0.073
3145543BTLEBRO
Solar/Wind Harmer
0.073
971623AH1-311 GEN
Solar/Wind Harmer
0.147
316478AD1-087 GEN
Solar/Wind Harmer
0.24
316486AD2-202 GEN
Solar/Wind Harmer
0.07
3141316ARNOLDS
Adder
0.161
316131AB2-060 GEN
Solar/Wind Harmer
0.199
964241AG1-285 GEN
Solar/Wind Harmer
4.14
315785AD2-033 C
Solar/Wind Harmer
0.488
970257AG2-171 GEN
Solar/Wind Harmer
1.897
959311AF2-222 GEN
Solar/Wind Harmer
5.222
316473AC1-191 GEN
Solar/Wind Harmer
0.191
316248AF1-058 C
Solar/Wind Harmer
0
960061AF2-297 GEN
Solar/Wind Harmer
2.402
315759AF1-018 GEN
50/50
8.574
3142433PROV 92
50/50
0.435
3142433PROV 92
50/50
0.435
3150611CHESTG7
50/50
1.286
3150631CHESTG8
50/50
1.265
971047AG2-646 GEN
50/50
36.002
315976AC1-164 GENA
Solar/Wind Harmer
32.344
316169AC1-164_GENC
Solar/Wind Harmer
27.943
315975AC1-164 GENB
Solar/Wind Harmer
0.957
316314AB2-024 C
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.002
3143873LANEXA
Solar/Wind Harmer
0.141
970189AG2-124 GEN
Solar/Wind Harmer
6.788
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.045
3141913WHIT STONE
Solar/Wind Harmer
0.222
3138133OCRAN
Solar/Wind Harmer
0.066
3141783LANCAST
Solar/Wind Harmer
0.132
3141783LANCAST
Solar/Wind Harmer
0.088
962981AG1-147 GEN
Solar/Wind Harmer
8.11
970327AG2-215 GEN
Solar/Wind Harmer
7.076
3141813NORNECK
Solar/Wind Harmer
0.208
971167AH1-042 GEN
Solar/Wind Harmer
18.214
3138283WHITEMARSH
Solar/Wind Harmer
0.046
316223AC1-118
Solar/Wind Harmer
0.126
316312AB1-027
Solar/Wind Harmer
0.275
316132AB2-190 GEN1
Solar/Wind Harmer
0.809
316369SG1_INVT
Solar/Wind Harmer
0.006
972265AH1-717 GEN
Adder
11.153
3151201GRAVEL4
Adder
10.455
3151191GRAVEL3
Adder
10.323
3151211GRAVEL5
Adder
10.323
971445AH1-216 GEN
Solar/Wind Harmer
9.647
944491AF1-114 GEN
Solar/Wind Harmer
0
3152611GOSPORTB
Adder
1.587
3152621GOSPORTC
Adder
1.347
3152601GOSPORTA
Adder
1.242
3151081ELIZAR1
Adder
11.396
3151091ELIZAR2
Adder
11.198
316305AF2-043 C
Solar/Wind Harmer
0.001
957871AF2-081 GEN
Solar/Wind Harmer
6.034
319010AE1-072 C
Solar/Wind Harmer
0.608
3146406KITTY HAWK
Solar/Wind Harmer
0.015
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.082
316311AC2-079 GEN
Solar/Wind Harmer
3.454
315835AF2-110_GEN
Solar/Wind Harmer
0.824
3146486SUNBURY
Solar/Wind Harmer
0.119
3146486SUNBURY
Solar/Wind Harmer
0.119
313526AB2-022
Solar/Wind Harmer
0.064
316321Z2-027
Solar/Wind Harmer
0.022
3146396TANGLEW
Solar/Wind Harmer
0.325
3145176PASQUOTANK
Solar/Wind Harmer
0.073
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.111
3130156CHOWAN
Solar/Wind Harmer
0.111
3143316POE
Solar/Wind Harmer
0.433
315816AE2-034 GEN
Solar/Wind Harmer
0.455
971285AH1-108 GEN
Adder
0.794
3130546PLYMOUTH
Solar/Wind Harmer
0.102
315732AD1-074 GEN1
Solar/Wind Harmer
0.585
315733AD1-074 GEN2
Solar/Wind Harmer
0.585
315735AD1-075 GEN1
Solar/Wind Harmer
0.293
3146206CASHIE
Solar/Wind Harmer
0.099
970601AG2-382 GEN
Solar/Wind Harmer
3.715
965291AG1-394 GEN
Solar/Wind Harmer
0.437
3145893MURPHYS
Solar/Wind Harmer
0.261
3145893MURPHYS
Solar/Wind Harmer
0.097
316315AB2-025 C
Solar/Wind Harmer
0.078
315814AE2-033 C
Solar/Wind Harmer
7.609
3145513AHOSKIE
Solar/Wind Harmer
0.198
3145513AHOSKIE
Solar/Wind Harmer
0.095
3145683EARLEYS
Solar/Wind Harmer
0.188
3145683EARLEYS
Solar/Wind Harmer
0.094
3145683EARLEYS
Solar/Wind Harmer
0.094
3146043SEABORD
Solar/Wind Harmer
0.091
315607AA1-063A GEN
Solar/Wind Harmer
0.184
315652AC1-086 GEN
Solar/Wind Harmer
9.519
3146033SCOT NK
Solar/Wind Harmer
0.346
941031AE2-094 GEN
Solar/Wind Harmer
15.83
944011AF1-069 GEN
Solar/Wind Harmer
5.172
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.34
3145796HORNRTN
Solar/Wind Harmer
0.271
3145796HORNRTN
Solar/Wind Harmer
0.034
316233AE1-074 FULL
Solar/Wind Harmer
0.068
971281AH1-106 GEN
Solar/Wind Harmer
1.171
971283AH1-107 GEN
Solar/Wind Harmer
1.171
970673AG2-436 GEN
Solar/Wind Harmer
17.959
970673AG2-436 GEN
Solar/Wind Harmer
11.973
316005AA1-067
Solar/Wind Harmer
0.089
3145746EVERETS
Solar/Wind Harmer
0.329
3145746EVERETS
Solar/Wind Harmer
0.083
3145746EVERETS
Solar/Wind Harmer
0.083
3145746EVERETS
Solar/Wind Harmer
0.083
970181AG2-120 GEN
Solar/Wind Harmer
1.028
971967AH1-528 GEN
Solar/Wind Harmer
13.196
970685AG2-442 GEN
Solar/Wind Harmer
4.283
957861AF2-080 GEN
Solar/Wind Harmer
3.428
970085AG2-068 GEN
Solar/Wind Harmer
4.189
970581AG2-369 GEN
Solar/Wind Harmer
3.603
316420AA1-050 GEN
Solar/Wind Harmer
0.003
3145573BETHELC
Solar/Wind Harmer
0.077
3145573BETHELC
Solar/Wind Harmer
0.077
316319Z2-044 C
Solar/Wind Harmer
0
970831AG2-522 GEN
Solar/Wind Harmer
3.188
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
0.999
3144303KENBRDG
Solar/Wind Harmer
0.047
316118AC1-105 GEN
Solar/Wind Harmer
0.149
970683AG2-441 GEN
Solar/Wind Harmer
3.824
970681AG2-440 GEN
Solar/Wind Harmer
3.059
3147173SINAI
Solar/Wind Harmer
0.056
3147243WELCO
Solar/Wind Harmer
0.035
CPLELTFEXP_CPLE->PJM
CLTF
4.035
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.643
LAGNLTFEXP_LAGN->PJM
CLTF
1.924
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.054
TVALTFEXP_TVA->PJM
CLTF
0.95
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.999
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.074
MECLTFEXP_MEC->PJM
CLTF
0.569
SIGELTFEXP_SIGE->PJM
CLTF
0.015
NYPJM->LTFIMP_NY
CLTF
0.699
LGEELTFEXP_LGEE->PJM
CLTF
0.151
WECLTFEXP_WEC->PJM
CLTF
0.071

Details for 6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer l/o DVP_P4-2: G2T567_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: G2T567_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.33 %
Rating:1107.0 MVA
Rating Type:C
MVA to Mitigate:1298.88
MW Contribution:3.87
Bus #Bus NameTypeMW Contribution
3150341NORNECKC1
50/50
2.321
3150341NORNECKC1
50/50
2.302
963611AG1-210 GEN
50/50
0.743
3150621CHESTS7
50/50
0.592
3150781HOPHCF2
50/50
0.625
3150791HOPHCF3
50/50
0.625
3150761HOPPOLC
50/50
0.397
971213AH1-066 GEN
50/50
0.548
316075AC2-137 C
Solar/Wind Harmer
0.758
3142946ENON
Solar/Wind Harmer
-0.003
316441AF1-014 GEN
Solar/Wind Harmer
1.74
316487AF1-042 GEN
Solar/Wind Harmer
3.2
958261AF2-120 GEN
Solar/Wind Harmer
9.3
316077AC2-138 C
Solar/Wind Harmer
0.495
3150691DARBY 3
Adder
10.751
3150701DARBY 4
Adder
10.726
3150681DARBY 2
Adder
10.713
3150671DARBY 1
Adder
10.701
316033AB2-134 GEN
Solar/Wind Harmer
5.389
315697AD1-025 GEN
Solar/Wind Harmer
3.38
316236AE1-162_GEN
Solar/Wind Harmer
0.464
315749AE2-041 GEN
50/50
8.597
3141843SHACKLE
50/50
1.246
970575AG2-366 GEN
50/50
3.873
3142433PROV 92
50/50
0.437
3142433PROV 92
50/50
0.437
3150351NORNECKC2
50/50
2.247
3150921YORKTN3
50/50
4.644
316036AC1-147 C
Solar/Wind Harmer
0.38
3150991CHESPKB
Adder
1.312
3150991CHESPKB
Adder
1.28
316316AC1-027 C
Solar/Wind Harmer
0.428
3142956BIRDNECK
Solar/Wind Harmer
0.748
316185AD1-033 GEN
Solar/Wind Harmer
1.461
3145506HICKORY
Solar/Wind Harmer
-0.055
3145506HICKORY
Solar/Wind Harmer
-0.033
3145506HICKORY
Solar/Wind Harmer
-0.008
3142366NRTHEST
Adder
0.399
316339AD2-160 GEN
Solar/Wind Harmer
0.925
316018AA1-139 ULT2
Solar/Wind Harmer
1.173
316017AA1-139 ULT1
Solar/Wind Harmer
1.108
3137176SLIGO L2192
Solar/Wind Harmer
-0.054
3146456SLIGO L269
Solar/Wind Harmer
1.612
970657AG2-426 GEN
Solar/Wind Harmer
4.26
315759AF1-018 GEN
50/50
8.597
3142433PROV 92
50/50
0.437
3142433PROV 92
50/50
0.437
3150611CHESTG7
50/50
1.29
3150631CHESTG8
50/50
1.269
971047AG2-646 GEN
50/50
36.115
315976AC1-164 GENA
Solar/Wind Harmer
37.107
316169AC1-164_GENC
Solar/Wind Harmer
32.057
315975AC1-164 GENB
Solar/Wind Harmer
1.098
316314AB2-024 C
Solar/Wind Harmer
2.42
316059AD1-063 C
Solar/Wind Harmer
0.614
3143873LANEXA
Solar/Wind Harmer
-0.016
315662AE1-191 GEN
Solar/Wind Harmer
3.085
315666AE1-190 GEN
Solar/Wind Harmer
0.771
957601AF2-054 GEN
Solar/Wind Harmer
0.757
3141873WAN 176
Solar/Wind Harmer
-0.005
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.008
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
10.71
3141813NORNECK
Solar/Wind Harmer
-0.023
971167AH1-042 GEN
Solar/Wind Harmer
22.25
957831AF2-077 GEN
Solar/Wind Harmer
0.67
3138283WHITEMARSH
Solar/Wind Harmer
0.035
316223AC1-118
Solar/Wind Harmer
0.533
316312AB1-027
Solar/Wind Harmer
0.585
316132AB2-190 GEN1
Solar/Wind Harmer
1.721
316369SG1_INVT
Solar/Wind Harmer
2.986
972265AH1-717 GEN
Adder
11.202
3151201GRAVEL4
Adder
10.501
3151191GRAVEL3
Adder
10.368
3151211GRAVEL5
Adder
10.368
971445AH1-216 GEN
Solar/Wind Harmer
9.571
944491AF1-114 GEN
Solar/Wind Harmer
4.354
3152611GOSPORTB
Adder
1.595
3152621GOSPORTC
Adder
1.353
3152601GOSPORTA
Adder
1.249
3151081ELIZAR1
Adder
11.454
3151091ELIZAR2
Adder
11.255
316305AF2-043 C
Solar/Wind Harmer
0.415
957871AF2-081 GEN
Solar/Wind Harmer
6.845
319010AE1-072 C
Solar/Wind Harmer
2.757
3146406KITTY HAWK
Solar/Wind Harmer
0.011
315833AF1-017_GEN
Solar/Wind Harmer
2.581
316349AD2-085 GEN
Solar/Wind Harmer
1.209
316311AC2-079 GEN
Solar/Wind Harmer
6.853
315835AF2-110_GEN
Solar/Wind Harmer
1.695
3146486SUNBURY
Solar/Wind Harmer
-0.013
3146486SUNBURY
Solar/Wind Harmer
-0.013
313526AB2-022
Solar/Wind Harmer
0.362
316321Z2-027
Solar/Wind Harmer
0.36
3146396TANGLEW
Solar/Wind Harmer
0.245
3145176PASQUOTANK
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
3.157
3130156CHOWAN
Solar/Wind Harmer
-0.012
3130156CHOWAN
Solar/Wind Harmer
-0.012
3143316POE
Solar/Wind Harmer
-0.049
315816AE2-034 GEN
Solar/Wind Harmer
0.969
971285AH1-108 GEN
Adder
0.799
3130546PLYMOUTH
Solar/Wind Harmer
-0.012
315732AD1-074 GEN1
Solar/Wind Harmer
2.328
315733AD1-074 GEN2
Solar/Wind Harmer
2.328
315735AD1-075 GEN1
Solar/Wind Harmer
1.164
3146206CASHIE
Solar/Wind Harmer
-0.011
970601AG2-382 GEN
Solar/Wind Harmer
4.922
965291AG1-394 GEN
Solar/Wind Harmer
0.986
316318V4-068
Solar/Wind Harmer
0.273
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
-0.011
316315AB2-025 C
Solar/Wind Harmer
0.295
315814AE2-033 C
Solar/Wind Harmer
10.13
3145513AHOSKIE
Solar/Wind Harmer
0.093
961941AG1-037 GEN
Solar/Wind Harmer
0.081
3145513AHOSKIE
Solar/Wind Harmer
-0.011
3145683EARLEYS
Solar/Wind Harmer
-0.021
3145683EARLEYS
Solar/Wind Harmer
-0.011
3145683EARLEYS
Solar/Wind Harmer
-0.011
3146043SEABORD
Solar/Wind Harmer
-0.01
315607AA1-063A GEN
Solar/Wind Harmer
1.031
315652AC1-086 GEN
Solar/Wind Harmer
11.023
3146033SCOT NK
Solar/Wind Harmer
-0.039
941031AE2-094 GEN
Solar/Wind Harmer
18.24
944011AF1-069 GEN
Solar/Wind Harmer
5.715
946281AF1-292 GEN
Solar/Wind Harmer
0.216
316087AB2-174 GEN
Solar/Wind Harmer
1.374
3137643SOCKMAN
Solar/Wind Harmer
-0.038
3145796HORNRTN
Solar/Wind Harmer
-0.03
3145796HORNRTN
Solar/Wind Harmer
-0.004
316233AE1-074 FULL
Solar/Wind Harmer
0.257
971281AH1-106 GEN
Solar/Wind Harmer
1.554
971283AH1-107 GEN
Solar/Wind Harmer
1.554
970673AG2-436 GEN
Solar/Wind Harmer
20.02
970673AG2-436 GEN
Solar/Wind Harmer
10.137
316005AA1-067
Solar/Wind Harmer
0.189
3145746EVERETS
Solar/Wind Harmer
-0.037
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
970181AG2-120 GEN
Solar/Wind Harmer
1.227
971967AH1-528 GEN
Solar/Wind Harmer
17.555
957861AF2-080 GEN
Solar/Wind Harmer
3.94
970085AG2-068 GEN
Solar/Wind Harmer
5.56
970581AG2-369 GEN
Solar/Wind Harmer
4.782
316420AA1-050 GEN
Solar/Wind Harmer
1.009
3144216WINCHST
50/50
0.681
3143096IRON208
50/50
0.703
3143096IRON208
50/50
0.689
3150801HOPHCF4
50/50
0.909
971211AH1-065 GEN
50/50
1.097
3141766HARMONY
Solar/Wind Harmer
2.418
3142946ENON
Solar/Wind Harmer
-0.009
316203AE2-005 GEN
Solar/Wind Harmer
10.88
316280AD1-041 GEN
Solar/Wind Harmer
1.928
316156AD2-030 GEN
Solar/Wind Harmer
0.675
3141873WAN 176
Solar/Wind Harmer
3.001
316382AG1-145 C
Solar/Wind Harmer
0.748
962971AG1-146 GEN
Solar/Wind Harmer
4.59
316484AD2-074 GEN
Solar/Wind Harmer
6.116
970009AG2-005 GEN
Solar/Wind Harmer
3.037
316404AE1-155 C
Solar/Wind Harmer
4.63
970293AG2-193 GEN
Solar/Wind Harmer
2.776
3141906WESTMOR
Solar/Wind Harmer
-0.008
970737AG2-469 GEN
Solar/Wind Harmer
8.932
3142416OLDCHRC
Solar/Wind Harmer
1.751
970133AG2-095 GEN
Solar/Wind Harmer
1.95
970129AG2-093 GEN
Solar/Wind Harmer
9.595
315778AD1-151 GEN
Solar/Wind Harmer
14.584
961611AG1-000B GEN
Solar/Wind Harmer
3.454
3151221GRAVEL6
Adder
10.489
3151171GRAVELC
Adder
2.018
3145336SMITFLD
Solar/Wind Harmer
-0.006
3144536CHRHLND
Solar/Wind Harmer
-0.002
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
11.601
965281AG1-393 GEN
Solar/Wind Harmer
1.753
315773AC2-141 GEN
Solar/Wind Harmer
5.781
944581AF1-123 GEN
Solar/Wind Harmer
62.686
944601AF1-125 GEN
Solar/Wind Harmer
61.708
315813AE1-149 C
Solar/Wind Harmer
8.541
3146456SLIGO L269
Solar/Wind Harmer
-0.014
971153AH1-033 GEN
Solar/Wind Harmer
1.664
970659AG2-427 GEN
Solar/Wind Harmer
1.284
316083AB2-161 GEN
Solar/Wind Harmer
2.213
970661AG2-428 GEN
Solar/Wind Harmer
2.565
316320Y1-086
Solar/Wind Harmer
0.787
316435W1029_GEN3
Solar/Wind Harmer
2.396
3146516WINFALL
Solar/Wind Harmer
-0.013
3146626S HERTFORD
Solar/Wind Harmer
-0.013
3145273HOLLAND
Solar/Wind Harmer
-0.01
315839AE2-212 C
Solar/Wind Harmer
0.385
3146376EDENTON
Solar/Wind Harmer
-0.012
315614AA2-178 GEN
Solar/Wind Harmer
1.292
3150861SPRUNCD
Adder
0.488
971157AH1-035 GEN
Solar/Wind Harmer
1.448
315737AD1-076 GEN
Solar/Wind Harmer
2.188
3146206CASHIE
Solar/Wind Harmer
-0.011
3156081AA2-088 GEN
Solar/Wind Harmer
3.642
3145893MURPHYS
Solar/Wind Harmer
0.076
3145893MURPHYS
Solar/Wind Harmer
-0.011
957521AF2-046 GEN
Solar/Wind Harmer
8.591
961681AG1-008 GEN
Solar/Wind Harmer
8.591
3156021HOLLOMANSOL
Solar/Wind Harmer
1.466
3146173TUNIS
Solar/Wind Harmer
-0.011
316463AE2-346 GEN
Solar/Wind Harmer
0.173
316140AB2-099
Solar/Wind Harmer
0.072
962331AG1-082 GEN
Solar/Wind Harmer
1.339
3145963POPLR C
Solar/Wind Harmer
-0.011
3146263WOODLND
Solar/Wind Harmer
-0.01
316317KELFORD C
Solar/Wind Harmer
0.481
3145823KELFORD
Solar/Wind Harmer
-0.01
316365GEN2_N
Solar/Wind Harmer
0.683
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3145933PARMELE
Solar/Wind Harmer
-0.01
966801AG1-551 GEN
Solar/Wind Harmer
1.217
966621AG1-532 GEN
Solar/Wind Harmer
0.196
313506AB2-031 GEN
Solar/Wind Harmer
0.774
3145796HORNRTN
Solar/Wind Harmer
-0.038
3145796HORNRTN
Solar/Wind Harmer
-0.01
316210AC1-098 GEN
Solar/Wind Harmer
1.481
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
970917AG2-570 GEN
Solar/Wind Harmer
22.341
3147043LAWRENC
Solar/Wind Harmer
-0.005
315724AD1-057 GEN
Solar/Wind Harmer
0.511
316327AA2-057 GEN
Solar/Wind Harmer
0.893
3146073TAR RVR
Solar/Wind Harmer
-0.009
3146083TARBORO
Solar/Wind Harmer
-0.009
3146233WITAKRS
Solar/Wind Harmer
0.18
3146233WITAKRS
Solar/Wind Harmer
-0.006
3138543CONSLDL
Solar/Wind Harmer
-0.006
961601AG1-000A GEN
Solar/Wind Harmer
3.321
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3141316ARNOLDS
Adder
0.162
3141843SHACKLE
50/50
1.246
966661AG1-536 GEN
50/50
6.076
3142433PROV 92
50/50
0.437
3142433PROV 92
50/50
0.437
3150351NORNECKC2
50/50
2.209
3150641CHESTS8
50/50
0.654
944631AF1-128 GEN
50/50
102.747
971353AH1-157 GEN
50/50
17.022
970017AG2-010 GEN
50/50
11.407
3143096IRON208
50/50
0.703
3150771HOPHCF1
50/50
0.625
3141766HARMONY
Solar/Wind Harmer
-0.005
971777AH1-397 GEN
Solar/Wind Harmer
3.035
3138133OCRAN
Solar/Wind Harmer
-0.015
316159AE1-175 C
Solar/Wind Harmer
0.666
964211AG1-282 GEN
Solar/Wind Harmer
0.735
3141726DUNNSVL
Solar/Wind Harmer
-0.097
961951AG1-038 GEN
Solar/Wind Harmer
3.2
962861AG1-135 GEN
Solar/Wind Harmer
9.029
3142433PROV 92
Solar/Wind Harmer
-0.095
316337AD2-073 GEN
Solar/Wind Harmer
0.587
971317AH1-138 GEN
Solar/Wind Harmer
2.668
3138126ROCKLANDING
Solar/Wind Harmer
0.059
3142416OLDCHRC
Solar/Wind Harmer
-0.045
3142416OLDCHRC
Solar/Wind Harmer
-0.017
970129AG2-093 GEN
Solar/Wind Harmer
3.887
316458AB2-190 GEN2
Solar/Wind Harmer
1.721
971069AG2-661 GEN
Solar/Wind Harmer
2.664
972135AH1-637 GEN
Solar/Wind Harmer
1.659
971647AH1-324 GEN
Solar/Wind Harmer
8.279
961611AG1-000B GEN
Solar/Wind Harmer
8.096
3151171GRAVELC
Adder
1.535
3145336SMITFLD
Solar/Wind Harmer
-0.061
957971AF2-091 GEN
Solar/Wind Harmer
1.48
316072AD1-144
Solar/Wind Harmer
0.296
315671AE2-027_GEN
Solar/Wind Harmer
10.697
316375AC2-012 GEN
Solar/Wind Harmer
4.87
3150981CHESPKA
Adder
1.564
316294AC1-161 GEN
Solar/Wind Harmer
4.47
944591AF1-124 GEN
Solar/Wind Harmer
62.912
3142543TWELFTH
Solar/Wind Harmer
-0.001
316246AF1-032 C
Solar/Wind Harmer
0.279
316388AE2-253 GEN
Solar/Wind Harmer
0.925
3145573BETHELC
Solar/Wind Harmer
-0.009
3145573BETHELC
Solar/Wind Harmer
-0.009
316319Z2-044 C
Solar/Wind Harmer
0.475
970831AG2-522 GEN
Solar/Wind Harmer
4.233
3146456SLIGO L269
Solar/Wind Harmer
-0.014
970659AG2-427 GEN
Solar/Wind Harmer
7.247
316381AD1-082 GEN
Solar/Wind Harmer
1.251
970661AG2-428 GEN
Solar/Wind Harmer
14.474
316093AE2-104_GEN
Solar/Wind Harmer
3.942
3146516WINFALL
Solar/Wind Harmer
-0.042
3146516WINFALL
Solar/Wind Harmer
-0.013
315800Z1-036_GEN1
Solar/Wind Harmer
3.157
3130156CHOWAN
Solar/Wind Harmer
-0.012
3145663CRESWEL
Solar/Wind Harmer
-0.033
971163AH1-040 GEN
Solar/Wind Harmer
11.23
3150851SPRUNCC
Adder
0.488
939411AE1-173 GEN
Solar/Wind Harmer
57.793
3146206CASHIE
Solar/Wind Harmer
-0.011
971547AH1-271 GEN
Solar/Wind Harmer
2.813
3145893MURPHYS
Solar/Wind Harmer
-0.044
3145893MURPHYS
Solar/Wind Harmer
0.325
940641AE2-051 GEN
Solar/Wind Harmer
10.131
3146173TUNIS
Solar/Wind Harmer
-0.011
3145683EARLEYS
Solar/Wind Harmer
-0.011
3145963POPLR C
Solar/Wind Harmer
-0.011
316174AB2-169 GEN
Solar/Wind Harmer
1.602
3146263WOODLND
Solar/Wind Harmer
-0.01
3145823KELFORD
Solar/Wind Harmer
-0.01
316023GEN1_S
Solar/Wind Harmer
0.683
316190AA2-174 GEN
Solar/Wind Harmer
0.12
316011AB1-132 GEN
Solar/Wind Harmer
2.05
962571AG1-106 GEN
Solar/Wind Harmer
1.408
3146293MARTNCO
Solar/Wind Harmer
0.06
960081AF2-299 GEN
Solar/Wind Harmer
1.084
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.01
3145783HORNRTN
Solar/Wind Harmer
-0.01
3143526WINTERP
Solar/Wind Harmer
-0.049
316212AC1-099_GEN
Solar/Wind Harmer
0.823
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
971795AH1-408 GEN
Solar/Wind Harmer
6.851
316494AC1-189 GEN
Solar/Wind Harmer
0.969
970919AG2-571 GEN
Solar/Wind Harmer
2.828
3147043LAWRENC
Adder
0.717
970087AG2-069 GEN
Solar/Wind Harmer
8.34
315722AD1-056 GEN
Solar/Wind Harmer
0.93
961671AG1-007 GEN
Solar/Wind Harmer
0.11
3146083TARBORO
Solar/Wind Harmer
-0.009
3145493TOT1
Solar/Wind Harmer
0.258
3146233WITAKRS
Solar/Wind Harmer
-0.034
316129AC1-054 GEN
Solar/Wind Harmer
0.731
316359AB2-059 GEN
Solar/Wind Harmer
1.123
316049AB1-081 GEN
Solar/Wind Harmer
0.899
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3142053HEARTS
Solar/Wind Harmer
0.098
971065AG2-659 GEN
Solar/Wind Harmer
4.113
957481AF2-042 GEN
Solar/Wind Harmer
21.381
970657AG2-426 GEN
Solar/Wind Harmer
0.891
3130086AYDLETT
Solar/Wind Harmer
-0.054
3146386ELIZ CT
Solar/Wind Harmer
-0.013
316431W1029_GEN1
Solar/Wind Harmer
2.396
316433W1029_GEN2
Solar/Wind Harmer
2.396
3146516WINFALL
Solar/Wind Harmer
-0.013
3146516WINFALL
Solar/Wind Harmer
-0.013
3146516WINFALL
Solar/Wind Harmer
-0.013
944641AF1-129 GEN
Adder
55.701
316240AF1-291 C
Solar/Wind Harmer
0.393
3146626S HERTFORD
Solar/Wind Harmer
-0.013
3146626S HERTFORD
Solar/Wind Harmer
-0.013
315742AE1-103 GEN
Solar/Wind Harmer
1.307
3146376EDENTON
Solar/Wind Harmer
0.371
3146376EDENTON
Solar/Wind Harmer
0.371
316065AD1-022 GEN
Solar/Wind Harmer
5.673
3145893MURPHYS
Solar/Wind Harmer
0.306
3145893MURPHYS
Solar/Wind Harmer
-0.02
3144356SAPONY
Solar/Wind Harmer
0.381
3146173TUNIS
Solar/Wind Harmer
-0.011
3146173TUNIS
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
316426AA2-053 GEN
Solar/Wind Harmer
0.991
3145933PARMELE
Solar/Wind Harmer
-0.019
3145933PARMELE
Solar/Wind Harmer
-0.01
316181AB2-040 GEN
Solar/Wind Harmer
1.344
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.083
3145593CAROLNA
Solar/Wind Harmer
0.08
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145783HORNRTN
Solar/Wind Harmer
1.135
3145783HORNRTN
Solar/Wind Harmer
0.908
3145783HORNRTN
Solar/Wind Harmer
0.284
3145783HORNRTN
Solar/Wind Harmer
0.114
3143526WINTERP
Solar/Wind Harmer
-0.049
972185AH1-677 GEN
Adder
4.71
972187AH1-678 GEN
Adder
2.357
316274AC1-208 GEN
Solar/Wind Harmer
0.997
970933AG2-581 GEN
Solar/Wind Harmer
8.445
3145493TOT1
Solar/Wind Harmer
0.135
3145453TOT5
Solar/Wind Harmer
0.081
3145603CNETO
Solar/Wind Harmer
0.054
961601AG1-000A GEN
Solar/Wind Harmer
3.28
316263AC1-034 GEN
Solar/Wind Harmer
3.905
970099AG2-077 GEN
Solar/Wind Harmer
8.553
CPLELTFEXP_CPLE->PJM
CLTF
4.088
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.298
LAGNLTFEXP_LAGN->PJM
CLTF
2.023
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.202
TVALTFEXP_TVA->PJM
CLTF
0.999
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.709
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.259
MECLTFEXP_MEC->PJM
CLTF
0.651
SIGELTFEXP_SIGE->PJM
CLTF
0.018
NYPJM->LTFIMP_NY
CLTF
0.668
LGEELTFEXP_LGEE->PJM
CLTF
0.185
WECLTFEXP_WEC->PJM
CLTF
0.09

Details for 6COMORN-6BIRCHWD 230.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6COMORN-6BIRCHWD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:129.88 %
Rating:670.0 MVA
Rating Type:C
MVA to Mitigate:870.22
MW Contribution:3.79
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
5.221
3142433PROV 92
50/50
0.233
3142433PROV 92
50/50
0.233
944491AF1-114 GEN
Solar/Wind Harmer
18.883
316223AC1-118
Solar/Wind Harmer
1.264
3141813NORNECK
Solar/Wind Harmer
-0.032
962981AG1-147 GEN
Solar/Wind Harmer
10.474
3141783LANCAST
Solar/Wind Harmer
-0.013
3141783LANCAST
Solar/Wind Harmer
-0.008
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.02
957601AF2-054 GEN
Solar/Wind Harmer
0.519
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
2.019
315666AE1-190 GEN
Solar/Wind Harmer
0.505
316059AD1-063 C
Solar/Wind Harmer
0.373
316314AB2-024 C
Solar/Wind Harmer
1.365
3143873LANEXA
Solar/Wind Harmer
-0.009
957831AF2-077 GEN
Solar/Wind Harmer
0.393
3138283WHITEMARSH
Solar/Wind Harmer
0.02
971167AH1-042 GEN
Solar/Wind Harmer
11.736
315976AC1-164 GENA
Solar/Wind Harmer
10.45
316169AC1-164_GENC
Solar/Wind Harmer
9.028
315975AC1-164 GENB
Solar/Wind Harmer
0.309
972265AH1-717 GEN
Adder
4.942
3151201GRAVEL4
Adder
4.633
3151191GRAVEL3
Adder
4.574
3151211GRAVEL5
Adder
4.574
971445AH1-216 GEN
Solar/Wind Harmer
4.315
316369SG1_INVT
Solar/Wind Harmer
1.245
316132AB2-190 GEN1
Solar/Wind Harmer
0.694
3152611GOSPORTB
Adder
0.752
3152621GOSPORTC
Adder
0.638
3152601GOSPORTA
Adder
0.589
3151081ELIZAR1
Adder
5.409
3151091ELIZAR2
Adder
5.315
316312AB1-027
Solar/Wind Harmer
0.222
316305AF2-043 C
Solar/Wind Harmer
0.196
957871AF2-081 GEN
Solar/Wind Harmer
3.251
319010AE1-072 C
Solar/Wind Harmer
1.31
3146406KITTY HAWK
Solar/Wind Harmer
0.005
313526AB2-022
Solar/Wind Harmer
0.172
315835AF2-110_GEN
Solar/Wind Harmer
0.797
3146486SUNBURY
Solar/Wind Harmer
-0.006
3146486SUNBURY
Solar/Wind Harmer
-0.006
316321Z2-027
Solar/Wind Harmer
0.171
3146396TANGLEW
Solar/Wind Harmer
0.117
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3141426STAFORD
Solar/Wind Helper
0.031
3141316ARNOLDS
50/50
2.024
3150351NORNECKC2
50/50
3.077
970575AG2-366 GEN
50/50
3.788
315749AE2-041 GEN
50/50
5.221
3141843SHACKLE
50/50
0.787
3142433PROV 92
50/50
0.233
3142433PROV 92
50/50
0.233
970737AG2-469 GEN
Solar/Wind Harmer
26.848
3141906WESTMOR
Solar/Wind Harmer
-0.019
316404AE1-155 C
Solar/Wind Harmer
5.369
316484AD2-074 GEN
Solar/Wind Harmer
6.401
970009AG2-005 GEN
Solar/Wind Harmer
3.178
962971AG1-146 GEN
Solar/Wind Harmer
4.489
316156AD2-030 GEN
Solar/Wind Harmer
0.464
3141873WAN 176
Solar/Wind Harmer
2.06
316280AD1-041 GEN
Solar/Wind Harmer
1.262
3141766HARMONY
Solar/Wind Harmer
1.469
316203AE2-005 GEN
Solar/Wind Harmer
6.877
316382AG1-145 C
Solar/Wind Harmer
0.285
3150921YORKTN3
Adder
2.048
3144216WINCHST
Adder
0.297
3142946ENON
Solar/Wind Harmer
-0.003
970293AG2-193 GEN
Solar/Wind Harmer
0.932
3151221GRAVEL6
Adder
4.627
3151171GRAVELC
Adder
0.89
961611AG1-000B GEN
Solar/Wind Harmer
1.491
3145336SMITFLD
Solar/Wind Harmer
-0.003
315778AD1-151 GEN
Solar/Wind Harmer
5.997
970129AG2-093 GEN
Solar/Wind Harmer
3.855
970133AG2-095 GEN
Solar/Wind Harmer
0.758
3144536CHRHLND
Solar/Wind Harmer
-0.001
315773AC2-141 GEN
Solar/Wind Harmer
2.81
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.478
3143096IRON208
Adder
0.246
3143096IRON208
Adder
0.241
3142416OLDCHRC
Solar/Wind Harmer
0.665
944581AF1-123 GEN
Solar/Wind Harmer
29.902
944601AF1-125 GEN
Solar/Wind Harmer
29.435
3146456SLIGO L269
Solar/Wind Harmer
-0.006
971153AH1-033 GEN
Solar/Wind Harmer
0.79
316320Y1-086
Solar/Wind Harmer
0.374
957191AF2-013 GEN
50/50
65.961
3150341NORNECKC1
50/50
3.178
3150341NORNECKC1
50/50
3.153
963611AG1-210 GEN
50/50
1.017
316077AC2-138 C
Solar/Wind Harmer
0.678
958261AF2-120 GEN
Solar/Wind Harmer
10.785
316487AF1-042 GEN
Solar/Wind Harmer
3.349
316441AF1-014 GEN
Solar/Wind Harmer
1.1
316075AC2-137 C
Solar/Wind Harmer
0.231
3142946ENON
Solar/Wind Harmer
-0.001
316033AB2-134 GEN
Solar/Wind Harmer
2.247
315697AD1-025 GEN
Solar/Wind Harmer
1.409
316236AE1-162_GEN
Solar/Wind Harmer
0.21
316036AC1-147 C
Solar/Wind Harmer
0.179
3150991CHESPKB
Adder
0.619
3150991CHESPKB
Adder
0.604
316316AC1-027 C
Solar/Wind Harmer
0.203
3142956BIRDNECK
Solar/Wind Harmer
0.354
316185AD1-033 GEN
Solar/Wind Harmer
0.693
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316339AD2-160 GEN
Solar/Wind Harmer
0.439
316018AA1-139 ULT2
Solar/Wind Harmer
0.557
316017AA1-139 ULT1
Solar/Wind Harmer
0.526
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.766
3130086AYDLETT
Solar/Wind Harmer
-0.026
3150691DARBY 3
Adder
4.114
3150701DARBY 4
Adder
4.104
3150681DARBY 2
Adder
4.1
3150671DARBY 1
Adder
4.095
3146386ELIZ CT
Solar/Wind Harmer
-0.006
3150351NORNECKC2
50/50
3.026
966661AG1-536 GEN
50/50
7.046
3141843SHACKLE
50/50
0.787
3142433PROV 92
50/50
0.233
3142433PROV 92
50/50
0.233
957971AF2-091 GEN
Solar/Wind Harmer
6.42
972135AH1-637 GEN
Solar/Wind Harmer
5.832
316337AD2-073 GEN
Solar/Wind Harmer
1.054
964211AG1-282 GEN
Solar/Wind Harmer
0.905
3141726DUNNSVL
Solar/Wind Harmer
-0.12
962861AG1-135 GEN
Solar/Wind Harmer
10.198
961951AG1-038 GEN
Solar/Wind Harmer
3.349
3138133OCRAN
Solar/Wind Harmer
-0.012
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.916
3142433PROV 92
Solar/Wind Harmer
-0.051
971317AH1-138 GEN
Solar/Wind Harmer
1.283
316159AE1-175 C
Solar/Wind Harmer
0.254
3138126ROCKLANDING
Solar/Wind Harmer
0.027
944631AF1-128 GEN
Adder
32.493
3151171GRAVELC
Adder
0.677
961611AG1-000B GEN
Solar/Wind Harmer
3.494
971647AH1-324 GEN
Solar/Wind Harmer
3.511
3145336SMITFLD
Solar/Wind Harmer
-0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.095
316458AB2-190 GEN2
Solar/Wind Harmer
0.694
970129AG2-093 GEN
Solar/Wind Harmer
1.562
316072AD1-144
Solar/Wind Harmer
0.138
316294AC1-161 GEN
Solar/Wind Harmer
2.172
316375AC2-012 GEN
Solar/Wind Harmer
2.296
3150981CHESPKA
Adder
0.737
3143096IRON208
Adder
0.246
3142416OLDCHRC
Solar/Wind Harmer
-0.017
3142416OLDCHRC
Solar/Wind Harmer
-0.007
944591AF1-124 GEN
Solar/Wind Harmer
30.01
316246AF1-032 C
Solar/Wind Harmer
0.132
316388AE2-253 GEN
Solar/Wind Harmer
0.439
3146456SLIGO L269
Solar/Wind Harmer
-0.006
316093AE2-104_GEN
Solar/Wind Harmer
1.855
CPLELTFEXP_CPLE->PJM
CLTF
2.221
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.105
LAGNLTFEXP_LAGN->PJM
CLTF
1.55
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.805
TVALTFEXP_TVA->PJM
CLTF
0.781
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.555
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.668
MECLTFEXP_MEC->PJM
CLTF
0.73
SIGELTFEXP_SIGE->PJM
CLTF
0.022
NYPJM->LTFIMP_NY
CLTF
0.582
LGEELTFEXP_LGEE->PJM
CLTF
0.268
WECLTFEXP_WEC->PJM
CLTF
0.133

Details for 6COMORN-6BIRCHWD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6COMORN-6BIRCHWD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.42 %
Rating:548.02 MVA
Rating Type:B
MVA to Mitigate:681.85
MW Contribution:3.66
Bus #Bus NameTypeMW Contribution
3141316ARNOLDS
50/50
2.018
3150351NORNECKC2
50/50
3.006
970575AG2-366 GEN
50/50
3.66
315749AE2-041 GEN
50/50
4.946
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150921YORKTN3
50/50
1.929
3144216WINCHST
50/50
0.279
3151161SURRY 1
50/50
2.166
970737AG2-469 GEN
Solar/Wind Harmer
20.178
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.637
962971AG1-146 GEN
Solar/Wind Harmer
3.294
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.61
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.855
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.668
3142416OLDCHRC
Solar/Wind Harmer
0.555
3151221GRAVEL6
Adder
4.099
3151171GRAVELC
Adder
0.789
315759AF1-018 GEN
50/50
4.946
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150611CHESTG7
50/50
0.401
3150631CHESTG8
50/50
0.394
971047AG2-646 GEN
50/50
11.221
972263AH1-716 GEN
50/50
32.871
944491AF1-114 GEN
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Harmer
0.296
3141813NORNECK
Solar/Wind Harmer
0.279
970327AG2-215 GEN
Solar/Wind Harmer
7.194
962981AG1-147 GEN
Solar/Wind Harmer
7.685
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.051
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
0.029
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.081
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
9.122
315976AC1-164 GENA
Solar/Wind Harmer
8.292
316169AC1-164_GENC
Solar/Wind Harmer
7.163
315975AC1-164 GENB
Solar/Wind Harmer
0.245
316312AB1-027
Solar/Wind Harmer
0.102
972265AH1-717 GEN
Adder
4.377
3151201GRAVEL4
Adder
4.104
3151191GRAVEL3
Adder
4.052
3151211GRAVEL5
Adder
4.052
3141426STAFORD
Solar/Wind Helper
0.031
957191AF2-013 GEN
50/50
65.713
3150341NORNECKC1
50/50
3.105
3150341NORNECKC1
50/50
3.08
963611AG1-210 GEN
50/50
0.994
3150621CHESTS7
50/50
0.184
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
7.962
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.007
3150351NORNECKC2
50/50
2.956
966661AG1-536 GEN
50/50
6.849
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
971353AH1-157 GEN
50/50
7.408
970017AG2-010 GEN
50/50
4.699
3150641CHESTS8
50/50
0.203
944631AF1-128 GEN
50/50
31.925
972135AH1-637 GEN
Solar/Wind Harmer
4.389
316337AD2-073 GEN
Solar/Wind Harmer
0.299
3141726DUNNSVL
Solar/Wind Harmer
1.044
962861AG1-135 GEN
Solar/Wind Harmer
7.523
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
971317AH1-138 GEN
Solar/Wind Harmer
0.613
316159AE1-175 C
Solar/Wind Harmer
0.065
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3142416OLDCHRC
Solar/Wind Harmer
0.149
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.6
CPLELTFEXP_CPLE->PJM
CLTF
1.997
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.895
LAGNLTFEXP_LAGN->PJM
CLTF
1.483
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.388
TVALTFEXP_TVA->PJM
CLTF
0.749
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.711
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.577
MECLTFEXP_MEC->PJM
CLTF
0.732
SIGELTFEXP_SIGE->PJM
CLTF
0.022
NYPJM->LTFIMP_NY
CLTF
0.564
LGEELTFEXP_LGEE->PJM
CLTF
0.274
WECLTFEXP_WEC->PJM
CLTF
0.137

Details for 6COMORN-6BIRCHWD 230.0 kV Ckt 1 line l/o DVP_P4-2: 574T575_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6COMORN-6BIRCHWD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 574T575_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.87 %
Rating:670.0 MVA
Rating Type:C
MVA to Mitigate:809.82
MW Contribution:3.69
Bus #Bus NameTypeMW Contribution
3141316ARNOLDS
50/50
2.011
3150351NORNECKC2
50/50
3.016
970575AG2-366 GEN
50/50
3.687
315749AE2-041 GEN
50/50
5.017
3141843SHACKLE
50/50
0.757
970737AG2-469 GEN
Solar/Wind Harmer
26.539
3141906WESTMOR
Solar/Wind Harmer
-0.018
316404AE1-155 C
Solar/Wind Harmer
5.246
316484AD2-074 GEN
Solar/Wind Harmer
6.24
970009AG2-005 GEN
Solar/Wind Harmer
3.098
962971AG1-146 GEN
Solar/Wind Harmer
4.369
316156AD2-030 GEN
Solar/Wind Harmer
0.446
3141873WAN 176
Solar/Wind Harmer
1.984
316280AD1-041 GEN
Solar/Wind Harmer
1.215
3141766HARMONY
Solar/Wind Harmer
1.411
316203AE2-005 GEN
Solar/Wind Harmer
6.619
3142433PROV 92
Adder
0.212
3142433PROV 92
Adder
0.212
316382AG1-145 C
Solar/Wind Harmer
0.264
3150921YORKTN3
Adder
1.889
3144216WINCHST
Adder
0.274
3142946ENON
Solar/Wind Harmer
-0.003
970293AG2-193 GEN
Solar/Wind Harmer
0.911
3151221GRAVEL6
Adder
4.32
3151171GRAVELC
Adder
0.831
961611AG1-000B GEN
Solar/Wind Harmer
1.4
3142416OLDCHRC
Solar/Wind Harmer
0.671
315778AD1-151 GEN
Solar/Wind Harmer
5.713
970129AG2-093 GEN
Solar/Wind Harmer
3.698
3143096IRON208
Adder
0.244
3143096IRON208
Adder
0.239
970133AG2-095 GEN
Solar/Wind Harmer
0.735
3145336SMITFLD
Solar/Wind Harmer
-0.003
957191AF2-013 GEN
50/50
65.491
3150341NORNECKC1
50/50
3.116
3150341NORNECKC1
50/50
3.091
963611AG1-210 GEN
50/50
0.997
316077AC2-138 C
Solar/Wind Harmer
0.664
958261AF2-120 GEN
Solar/Wind Harmer
10.538
316487AF1-042 GEN
Solar/Wind Harmer
3.265
316441AF1-014 GEN
Solar/Wind Harmer
1.058
316075AC2-137 C
Solar/Wind Harmer
0.221
3142946ENON
Solar/Wind Harmer
-0.001
316033AB2-134 GEN
Solar/Wind Harmer
2.132
315697AD1-025 GEN
Solar/Wind Harmer
1.337
3150691DARBY 3
Adder
4.134
3150701DARBY 4
Adder
4.124
3150681DARBY 2
Adder
4.12
3150671DARBY 1
Adder
4.115
316236AE1-162_GEN
Solar/Wind Harmer
0.194
315759AF1-018 GEN
50/50
5.017
944491AF1-114 GEN
Solar/Wind Harmer
18.704
316223AC1-118
Solar/Wind Harmer
1.247
3141813NORNECK
Solar/Wind Harmer
-0.031
962981AG1-147 GEN
Solar/Wind Harmer
10.194
3141783LANCAST
Solar/Wind Harmer
-0.012
3141783LANCAST
Solar/Wind Harmer
-0.008
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.019
957601AF2-054 GEN
Solar/Wind Harmer
0.5
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
1.944
315666AE1-190 GEN
Solar/Wind Harmer
0.486
316059AD1-063 C
Solar/Wind Harmer
0.358
316314AB2-024 C
Solar/Wind Harmer
1.31
3143873LANEXA
Solar/Wind Harmer
-0.008
957831AF2-077 GEN
Solar/Wind Harmer
0.373
3138283WHITEMARSH
Solar/Wind Harmer
0.019
3142433PROV 92
Adder
0.212
3142433PROV 92
Adder
0.212
971167AH1-042 GEN
Solar/Wind Harmer
11.35
315976AC1-164 GENA
Solar/Wind Harmer
9.762
316169AC1-164_GENC
Solar/Wind Harmer
8.433
315975AC1-164 GENB
Solar/Wind Harmer
0.289
972265AH1-717 GEN
Adder
4.614
3151201GRAVEL4
Adder
4.325
3151191GRAVEL3
Adder
4.27
3151211GRAVEL5
Adder
4.27
316312AB1-027
Solar/Wind Harmer
0.224
316369SG1_INVT
Solar/Wind Harmer
1.181
316132AB2-190 GEN1
Solar/Wind Harmer
0.665
971445AH1-216 GEN
Solar/Wind Harmer
4
3141426STAFORD
Solar/Wind Helper
0.033
3150351NORNECKC2
50/50
2.966
966661AG1-536 GEN
50/50
6.885
3141843SHACKLE
50/50
0.757
957971AF2-091 GEN
Solar/Wind Harmer
6.359
972135AH1-637 GEN
Solar/Wind Harmer
5.77
316337AD2-073 GEN
Solar/Wind Harmer
1.037
964211AG1-282 GEN
Solar/Wind Harmer
0.886
3141726DUNNSVL
Solar/Wind Harmer
-0.117
962861AG1-135 GEN
Solar/Wind Harmer
9.959
961951AG1-038 GEN
Solar/Wind Harmer
3.265
3138133OCRAN
Solar/Wind Harmer
-0.012
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.845
3142433PROV 92
Solar/Wind Harmer
-0.049
3142433PROV 92
Adder
0.212
3142433PROV 92
Adder
0.212
971317AH1-138 GEN
Solar/Wind Harmer
1.192
316159AE1-175 C
Solar/Wind Harmer
0.235
3138126ROCKLANDING
Solar/Wind Harmer
0.025
944631AF1-128 GEN
Adder
31.292
3151171GRAVELC
Adder
0.632
961611AG1-000B GEN
Solar/Wind Harmer
3.282
3142416OLDCHRC
Solar/Wind Harmer
-0.017
3142416OLDCHRC
Solar/Wind Harmer
-0.007
971647AH1-324 GEN
Solar/Wind Harmer
3.315
971069AG2-661 GEN
Solar/Wind Harmer
1.043
316458AB2-190 GEN2
Solar/Wind Harmer
0.665
970129AG2-093 GEN
Solar/Wind Harmer
1.498
3143096IRON208
Adder
0.244
3145336SMITFLD
Solar/Wind Harmer
-0.026
CPLELTFEXP_CPLE->PJM
CLTF
2.196
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.727
LAGNLTFEXP_LAGN->PJM
CLTF
1.637
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.831
TVALTFEXP_TVA->PJM
CLTF
0.827
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.235
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.846
MECLTFEXP_MEC->PJM
CLTF
0.811
SIGELTFEXP_SIGE->PJM
CLTF
0.025
NYPJM->LTFIMP_NY
CLTF
0.625
LGEELTFEXP_LGEE->PJM
CLTF
0.304
WECLTFEXP_WEC->PJM
CLTF
0.152

Details for 6COMORN-6BIRCHWD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6COMORN-6BIRCHWD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.98 %
Rating:548.02 MVA
Rating Type:B
MVA to Mitigate:575.3
MW Contribution:3.68
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
2.97
966661AG1-536 GEN
50/50
6.884
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
971353AH1-157 GEN
50/50
7.642
970017AG2-010 GEN
50/50
4.875
3150641CHESTS8
50/50
0.192
944631AF1-128 GEN
50/50
30.156
3152331SURRY 2
50/50
2.455
972135AH1-637 GEN
Solar/Wind Harmer
4.407
316337AD2-073 GEN
Solar/Wind Harmer
0.3
3141726DUNNSVL
Solar/Wind Harmer
1.049
962861AG1-135 GEN
Solar/Wind Harmer
7.561
3138133OCRAN
Solar/Wind Harmer
0.104
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.365
3142433PROV 92
Solar/Wind Harmer
0.422
971317AH1-138 GEN
Solar/Wind Harmer
0.633
316159AE1-175 C
Solar/Wind Harmer
0.067
3138126ROCKLANDING
Solar/Wind Harmer
0.034
3151171GRAVELC
Adder
0.607
315759AF1-018 GEN
50/50
4.976
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
972263AH1-716 GEN
50/50
35.649
3150611CHESTG7
50/50
0.379
3150631CHESTG8
50/50
0.372
971047AG2-646 GEN
50/50
10.599
944491AF1-114 GEN
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Harmer
0.297
3141813NORNECK
Solar/Wind Harmer
0.28
970327AG2-215 GEN
Solar/Wind Harmer
7.232
962981AG1-147 GEN
Solar/Wind Harmer
7.729
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.074
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.168
3141873WAN 176
Solar/Wind Harmer
0.03
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.097
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
8.942
315976AC1-164 GENA
Solar/Wind Harmer
8.275
316169AC1-164_GENC
Solar/Wind Harmer
7.149
315975AC1-164 GENB
Solar/Wind Harmer
0.245
972265AH1-717 GEN
Adder
4.429
3151201GRAVEL4
Adder
4.152
3151191GRAVEL3
Adder
4.099
3151211GRAVEL5
Adder
4.099
3141426STAFORD
Solar/Wind Helper
0.029
3141316ARNOLDS
50/50
2.026
3150351NORNECKC2
50/50
3.02
970575AG2-366 GEN
50/50
3.68
315749AE2-041 GEN
50/50
4.976
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
3150921YORKTN3
50/50
2.003
3144216WINCHST
50/50
0.289
3151161SURRY 1
50/50
2.191
970737AG2-469 GEN
Solar/Wind Harmer
20.26
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.646
962971AG1-146 GEN
Solar/Wind Harmer
3.312
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.629
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.866
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.022
3151221GRAVEL6
Adder
4.147
3151171GRAVELC
Adder
0.798
970293AG2-193 GEN
Solar/Wind Harmer
0.603
957191AF2-013 GEN
50/50
65.968
3150341NORNECKC1
50/50
3.119
3150341NORNECKC1
50/50
3.094
963611AG1-210 GEN
50/50
0.998
3150621CHESTS7
50/50
0.174
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
8.003
316075AC2-137 C
Solar/Wind Harmer
0.018
3142946ENON
Solar/Wind Harmer
0.007
CPLELTFEXP_CPLE->PJM
CLTF
1.912
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.152
LAGNLTFEXP_LAGN->PJM
CLTF
1.213
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.047
TVALTFEXP_TVA->PJM
CLTF
0.609
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.061
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.057
MECLTFEXP_MEC->PJM
CLTF
0.525
SIGELTFEXP_SIGE->PJM
CLTF
0.016
NYPJM->LTFIMP_NY
CLTF
0.465
LGEELTFEXP_LGEE->PJM
CLTF
0.185
WECLTFEXP_WEC->PJM
CLTF
0.092

Details for 6COMORN-6BIRCHWD 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6COMORN-6BIRCHWD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.21 %
Rating:670.0 MVA
Rating Type:C
MVA to Mitigate:691.51
MW Contribution:3.66
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
2.955
966661AG1-536 GEN
50/50
6.848
3141843SHACKLE
50/50
0.746
957971AF2-091 GEN
Solar/Wind Harmer
6.372
972135AH1-637 GEN
Solar/Wind Harmer
5.779
316337AD2-073 GEN
Solar/Wind Harmer
1.036
964211AG1-282 GEN
Solar/Wind Harmer
0.882
3141726DUNNSVL
Solar/Wind Harmer
-0.117
962861AG1-135 GEN
Solar/Wind Harmer
9.902
961951AG1-038 GEN
Solar/Wind Harmer
3.243
3138133OCRAN
Solar/Wind Harmer
-0.011
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.817
3142433PROV 92
Solar/Wind Harmer
-0.048
3142433PROV 92
Adder
0.208
3142433PROV 92
Adder
0.208
971317AH1-138 GEN
Solar/Wind Harmer
1.154
316159AE1-175 C
Solar/Wind Harmer
0.227
3138126ROCKLANDING
Solar/Wind Harmer
0.024
944631AF1-128 GEN
Adder
30.026
3142416OLDCHRC
Solar/Wind Harmer
-0.017
3142416OLDCHRC
Solar/Wind Harmer
-0.006
3151171GRAVELC
Adder
0.599
315759AF1-018 GEN
50/50
4.944
944491AF1-114 GEN
Solar/Wind Harmer
18.743
316223AC1-118
Solar/Wind Harmer
1.247
3141813NORNECK
Solar/Wind Harmer
-0.031
962981AG1-147 GEN
Solar/Wind Harmer
10.117
3141783LANCAST
Solar/Wind Harmer
-0.012
3141783LANCAST
Solar/Wind Harmer
-0.008
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.019
957601AF2-054 GEN
Solar/Wind Harmer
0.493
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
1.916
315666AE1-190 GEN
Solar/Wind Harmer
0.479
316059AD1-063 C
Solar/Wind Harmer
0.353
316314AB2-024 C
Solar/Wind Harmer
1.29
3143873LANEXA
Solar/Wind Harmer
-0.008
957831AF2-077 GEN
Solar/Wind Harmer
0.364
3138283WHITEMARSH
Solar/Wind Harmer
0.019
3142433PROV 92
Adder
0.208
3142433PROV 92
Adder
0.208
971167AH1-042 GEN
Solar/Wind Harmer
11.098
315976AC1-164 GENA
Solar/Wind Harmer
9.485
316169AC1-164_GENC
Solar/Wind Harmer
8.194
315975AC1-164 GENB
Solar/Wind Harmer
0.281
316312AB1-027
Solar/Wind Harmer
0.216
972265AH1-717 GEN
Adder
4.374
3151201GRAVEL4
Adder
4.1
3151191GRAVEL3
Adder
4.048
3151211GRAVEL5
Adder
4.048
3141426STAFORD
Solar/Wind Helper
0.031
3141316ARNOLDS
50/50
2.018
3150351NORNECKC2
50/50
3.005
970575AG2-366 GEN
50/50
3.659
315749AE2-041 GEN
50/50
4.944
3141843SHACKLE
50/50
0.746
970737AG2-469 GEN
Solar/Wind Harmer
26.564
3141906WESTMOR
Solar/Wind Harmer
-0.018
316404AE1-155 C
Solar/Wind Harmer
5.218
316484AD2-074 GEN
Solar/Wind Harmer
6.199
970009AG2-005 GEN
Solar/Wind Harmer
3.078
962971AG1-146 GEN
Solar/Wind Harmer
4.336
316156AD2-030 GEN
Solar/Wind Harmer
0.44
3141873WAN 176
Solar/Wind Harmer
1.957
316280AD1-041 GEN
Solar/Wind Harmer
1.198
3141766HARMONY
Solar/Wind Harmer
1.39
316203AE2-005 GEN
Solar/Wind Harmer
6.52
3142433PROV 92
Adder
0.208
3142433PROV 92
Adder
0.208
316382AG1-145 C
Solar/Wind Harmer
0.255
3150921YORKTN3
Adder
1.818
3144216WINCHST
Adder
0.263
3142946ENON
Solar/Wind Harmer
-0.003
970293AG2-193 GEN
Solar/Wind Harmer
0.877
3142416OLDCHRC
Solar/Wind Harmer
0.646
3151221GRAVEL6
Adder
4.095
3151171GRAVELC
Adder
0.788
957191AF2-013 GEN
50/50
65.707
3150341NORNECKC1
50/50
3.104
3150341NORNECKC1
50/50
3.08
963611AG1-210 GEN
50/50
0.993
316077AC2-138 C
Solar/Wind Harmer
0.662
958261AF2-120 GEN
Solar/Wind Harmer
10.482
316487AF1-042 GEN
Solar/Wind Harmer
3.243
316441AF1-014 GEN
Solar/Wind Harmer
1.042
316075AC2-137 C
Solar/Wind Harmer
0.214
3142946ENON
Solar/Wind Harmer
-0.001
CPLELTFEXP_CPLE->PJM
CLTF
1.996
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.91
LAGNLTFEXP_LAGN->PJM
CLTF
1.485
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.39
TVALTFEXP_TVA->PJM
CLTF
0.75
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.728
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.582
MECLTFEXP_MEC->PJM
CLTF
0.734
SIGELTFEXP_SIGE->PJM
CLTF
0.022
NYPJM->LTFIMP_NY
CLTF
0.565
LGEELTFEXP_LGEE->PJM
CLTF
0.275
WECLTFEXP_WEC->PJM
CLTF
0.137

Details for 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FINES-6FREDBRG 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:141.71 %
Rating:671.0 MVA
Rating Type:C
MVA to Mitigate:950.85
MW Contribution:3.79
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
3.026
966661AG1-536 GEN
50/50
7.046
3141843SHACKLE
50/50
0.787
3142433PROV 92
50/50
0.233
3142433PROV 92
50/50
0.233
957971AF2-091 GEN
Solar/Wind Harmer
6.42
972135AH1-637 GEN
Solar/Wind Harmer
5.832
316337AD2-073 GEN
Solar/Wind Harmer
1.054
964211AG1-282 GEN
Solar/Wind Harmer
0.905
3141726DUNNSVL
Solar/Wind Harmer
-0.12
962861AG1-135 GEN
Solar/Wind Harmer
10.198
961951AG1-038 GEN
Solar/Wind Harmer
3.349
3138133OCRAN
Solar/Wind Harmer
-0.012
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.916
3142433PROV 92
Solar/Wind Harmer
-0.051
971317AH1-138 GEN
Solar/Wind Harmer
1.283
316159AE1-175 C
Solar/Wind Harmer
0.254
3138126ROCKLANDING
Solar/Wind Harmer
0.027
944631AF1-128 GEN
Adder
32.493
3151171GRAVELC
Adder
0.677
961611AG1-000B GEN
Solar/Wind Harmer
3.494
971647AH1-324 GEN
Solar/Wind Harmer
3.511
3145336SMITFLD
Solar/Wind Harmer
-0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.095
316458AB2-190 GEN2
Solar/Wind Harmer
0.694
970129AG2-093 GEN
Solar/Wind Harmer
1.562
316072AD1-144
Solar/Wind Harmer
0.138
316294AC1-161 GEN
Solar/Wind Harmer
2.172
3150331BIRCHWDA
50/50
158.648
3141316ARNOLDS
50/50
2.024
3150351NORNECKC2
50/50
3.077
970575AG2-366 GEN
50/50
3.788
315749AE2-041 GEN
50/50
5.221
3141843SHACKLE
50/50
0.787
3142433PROV 92
50/50
0.233
3142433PROV 92
50/50
0.233
970737AG2-469 GEN
Solar/Wind Harmer
26.848
3141906WESTMOR
Solar/Wind Harmer
-0.019
316404AE1-155 C
Solar/Wind Harmer
5.369
957191AF2-013 GEN
50/50
65.961
315759AF1-018 GEN
50/50
5.221
3142433PROV 92
50/50
0.233
3142433PROV 92
50/50
0.233
944491AF1-114 GEN
Solar/Wind Harmer
18.883
316223AC1-118
Solar/Wind Harmer
1.264
3141813NORNECK
Solar/Wind Harmer
-0.032
962981AG1-147 GEN
Solar/Wind Harmer
10.474
3141783LANCAST
Solar/Wind Harmer
-0.013
3141783LANCAST
Solar/Wind Harmer
-0.008
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.02
957601AF2-054 GEN
Solar/Wind Harmer
0.519
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
2.019
315666AE1-190 GEN
Solar/Wind Harmer
0.505
316059AD1-063 C
Solar/Wind Harmer
0.373
316314AB2-024 C
Solar/Wind Harmer
1.365
3143873LANEXA
Solar/Wind Harmer
-0.009
957831AF2-077 GEN
Solar/Wind Harmer
0.393
3138283WHITEMARSH
Solar/Wind Harmer
0.02
971167AH1-042 GEN
Solar/Wind Harmer
11.736
315976AC1-164 GENA
Solar/Wind Harmer
10.45
316169AC1-164_GENC
Solar/Wind Harmer
9.028
315975AC1-164 GENB
Solar/Wind Harmer
0.309
972265AH1-717 GEN
Adder
4.942
3151201GRAVEL4
Adder
4.633
3151191GRAVEL3
Adder
4.574
3151211GRAVEL5
Adder
4.574
971445AH1-216 GEN
Solar/Wind Harmer
4.315
316369SG1_INVT
Solar/Wind Harmer
1.245
316132AB2-190 GEN1
Solar/Wind Harmer
0.694
3152611GOSPORTB
Adder
0.752
3152621GOSPORTC
Adder
0.638
3152601GOSPORTA
Adder
0.589
3151081ELIZAR1
Adder
5.409
3151091ELIZAR2
Adder
5.315
316312AB1-027
Solar/Wind Harmer
0.222
316305AF2-043 C
Solar/Wind Harmer
0.196
957871AF2-081 GEN
Solar/Wind Harmer
3.251
319010AE1-072 C
Solar/Wind Harmer
1.31
3146406KITTY HAWK
Solar/Wind Harmer
0.005
313526AB2-022
Solar/Wind Harmer
0.172
315835AF2-110_GEN
Solar/Wind Harmer
0.797
3146486SUNBURY
Solar/Wind Harmer
-0.006
3146486SUNBURY
Solar/Wind Harmer
-0.006
316321Z2-027
Solar/Wind Harmer
0.171
3146396TANGLEW
Solar/Wind Harmer
0.117
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3141426STAFORD
Solar/Wind Helper
0.031
316484AD2-074 GEN
Solar/Wind Harmer
6.401
970009AG2-005 GEN
Solar/Wind Harmer
3.178
962971AG1-146 GEN
Solar/Wind Harmer
4.489
316156AD2-030 GEN
Solar/Wind Harmer
0.464
3141873WAN 176
Solar/Wind Harmer
2.06
316280AD1-041 GEN
Solar/Wind Harmer
1.262
3141766HARMONY
Solar/Wind Harmer
1.469
316203AE2-005 GEN
Solar/Wind Harmer
6.877
316382AG1-145 C
Solar/Wind Harmer
0.285
3150921YORKTN3
Adder
2.048
3144216WINCHST
Adder
0.297
3142946ENON
Solar/Wind Harmer
-0.003
970293AG2-193 GEN
Solar/Wind Harmer
0.932
3151221GRAVEL6
Adder
4.627
3151171GRAVELC
Adder
0.89
961611AG1-000B GEN
Solar/Wind Harmer
1.491
3145336SMITFLD
Solar/Wind Harmer
-0.003
315778AD1-151 GEN
Solar/Wind Harmer
5.997
970129AG2-093 GEN
Solar/Wind Harmer
3.855
970133AG2-095 GEN
Solar/Wind Harmer
0.758
3144536CHRHLND
Solar/Wind Harmer
-0.001
315773AC2-141 GEN
Solar/Wind Harmer
2.81
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.478
3143096IRON208
Adder
0.246
3143096IRON208
Adder
0.241
3142416OLDCHRC
Solar/Wind Harmer
0.665
944581AF1-123 GEN
Solar/Wind Harmer
29.902
944601AF1-125 GEN
Solar/Wind Harmer
29.435
3146456SLIGO L269
Solar/Wind Harmer
-0.006
971153AH1-033 GEN
Solar/Wind Harmer
0.79
316320Y1-086
Solar/Wind Harmer
0.374
3150341NORNECKC1
50/50
3.178
3150341NORNECKC1
50/50
3.153
963611AG1-210 GEN
50/50
1.017
316077AC2-138 C
Solar/Wind Harmer
0.678
958261AF2-120 GEN
Solar/Wind Harmer
10.785
316487AF1-042 GEN
Solar/Wind Harmer
3.349
316441AF1-014 GEN
Solar/Wind Harmer
1.1
316075AC2-137 C
Solar/Wind Harmer
0.231
3142946ENON
Solar/Wind Harmer
-0.001
316033AB2-134 GEN
Solar/Wind Harmer
2.247
315697AD1-025 GEN
Solar/Wind Harmer
1.409
316236AE1-162_GEN
Solar/Wind Harmer
0.21
316036AC1-147 C
Solar/Wind Harmer
0.179
3150991CHESPKB
Adder
0.619
3150991CHESPKB
Adder
0.604
316316AC1-027 C
Solar/Wind Harmer
0.203
3142956BIRDNECK
Solar/Wind Harmer
0.354
316185AD1-033 GEN
Solar/Wind Harmer
0.693
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316339AD2-160 GEN
Solar/Wind Harmer
0.439
316018AA1-139 ULT2
Solar/Wind Harmer
0.557
316017AA1-139 ULT1
Solar/Wind Harmer
0.526
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.766
3130086AYDLETT
Solar/Wind Harmer
-0.026
3150691DARBY 3
Adder
4.114
3150701DARBY 4
Adder
4.104
3150681DARBY 2
Adder
4.1
3150671DARBY 1
Adder
4.095
3146386ELIZ CT
Solar/Wind Harmer
-0.006
316375AC2-012 GEN
Solar/Wind Harmer
2.296
3150981CHESPKA
Adder
0.737
3143096IRON208
Adder
0.246
3142416OLDCHRC
Solar/Wind Harmer
-0.017
3142416OLDCHRC
Solar/Wind Harmer
-0.007
944591AF1-124 GEN
Solar/Wind Harmer
30.01
316246AF1-032 C
Solar/Wind Harmer
0.132
316388AE2-253 GEN
Solar/Wind Harmer
0.439
3146456SLIGO L269
Solar/Wind Harmer
-0.006
316093AE2-104_GEN
Solar/Wind Harmer
1.855
CPLELTFEXP_CPLE->PJM
CLTF
2.221
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.105
LAGNLTFEXP_LAGN->PJM
CLTF
1.55
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.805
TVALTFEXP_TVA->PJM
CLTF
0.781
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.555
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.668
MECLTFEXP_MEC->PJM
CLTF
0.73
SIGELTFEXP_SIGE->PJM
CLTF
0.022
NYPJM->LTFIMP_NY
CLTF
0.582
LGEELTFEXP_LGEE->PJM
CLTF
0.268
WECLTFEXP_WEC->PJM
CLTF
0.133

Details for 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FINES-6FREDBRG 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.73 %
Rating:548.02 MVA
Rating Type:B
MVA to Mitigate:760.24
MW Contribution:3.66
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
2.956
966661AG1-536 GEN
50/50
6.849
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
971353AH1-157 GEN
50/50
7.408
970017AG2-010 GEN
50/50
4.699
3150641CHESTS8
50/50
0.203
944631AF1-128 GEN
50/50
31.925
972135AH1-637 GEN
Solar/Wind Harmer
4.389
316337AD2-073 GEN
Solar/Wind Harmer
0.299
3141726DUNNSVL
Solar/Wind Harmer
1.044
962861AG1-135 GEN
Solar/Wind Harmer
7.523
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
971317AH1-138 GEN
Solar/Wind Harmer
0.613
316159AE1-175 C
Solar/Wind Harmer
0.065
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3142416OLDCHRC
Solar/Wind Harmer
0.149
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.6
3150331BIRCHWDA
50/50
158.356
3141316ARNOLDS
50/50
2.018
3150351NORNECKC2
50/50
3.006
970575AG2-366 GEN
50/50
3.66
315749AE2-041 GEN
50/50
4.946
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150921YORKTN3
50/50
1.929
3144216WINCHST
50/50
0.279
3151161SURRY 1
50/50
2.166
970737AG2-469 GEN
Solar/Wind Harmer
20.178
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.637
962971AG1-146 GEN
Solar/Wind Harmer
3.294
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.61
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.855
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.668
3142416OLDCHRC
Solar/Wind Harmer
0.555
3151221GRAVEL6
Adder
4.099
3151171GRAVELC
Adder
0.789
957191AF2-013 GEN
50/50
65.713
3150341NORNECKC1
50/50
3.105
3150341NORNECKC1
50/50
3.08
963611AG1-210 GEN
50/50
0.994
3150621CHESTS7
50/50
0.184
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
7.962
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.007
315759AF1-018 GEN
50/50
4.946
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150611CHESTG7
50/50
0.401
3150631CHESTG8
50/50
0.394
971047AG2-646 GEN
50/50
11.221
972263AH1-716 GEN
50/50
32.871
944491AF1-114 GEN
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Harmer
0.296
3141813NORNECK
Solar/Wind Harmer
0.279
970327AG2-215 GEN
Solar/Wind Harmer
7.194
962981AG1-147 GEN
Solar/Wind Harmer
7.685
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.051
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
0.029
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.081
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
9.122
315976AC1-164 GENA
Solar/Wind Harmer
8.292
316169AC1-164_GENC
Solar/Wind Harmer
7.163
315975AC1-164 GENB
Solar/Wind Harmer
0.245
316312AB1-027
Solar/Wind Harmer
0.102
972265AH1-717 GEN
Adder
4.377
3151201GRAVEL4
Adder
4.104
3151191GRAVEL3
Adder
4.052
3151211GRAVEL5
Adder
4.052
3141426STAFORD
Solar/Wind Helper
0.031
CPLELTFEXP_CPLE->PJM
CLTF
1.997
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.895
LAGNLTFEXP_LAGN->PJM
CLTF
1.483
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.388
TVALTFEXP_TVA->PJM
CLTF
0.749
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.711
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.577
MECLTFEXP_MEC->PJM
CLTF
0.732
SIGELTFEXP_SIGE->PJM
CLTF
0.022
NYPJM->LTFIMP_NY
CLTF
0.564
LGEELTFEXP_LGEE->PJM
CLTF
0.274
WECLTFEXP_WEC->PJM
CLTF
0.137

Details for 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 574T575_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FINES-6FREDBRG 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 574T575_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.2 %
Rating:671.0 MVA
Rating Type:C
MVA to Mitigate:887.04
MW Contribution:3.69
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
5.017
944491AF1-114 GEN
Solar/Wind Harmer
18.704
316223AC1-118
Solar/Wind Harmer
1.247
3141813NORNECK
Solar/Wind Harmer
-0.031
962981AG1-147 GEN
Solar/Wind Harmer
10.194
3141783LANCAST
Solar/Wind Harmer
-0.012
3141783LANCAST
Solar/Wind Harmer
-0.008
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.019
957601AF2-054 GEN
Solar/Wind Harmer
0.5
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
1.944
315666AE1-190 GEN
Solar/Wind Harmer
0.486
316059AD1-063 C
Solar/Wind Harmer
0.358
316314AB2-024 C
Solar/Wind Harmer
1.31
3143873LANEXA
Solar/Wind Harmer
-0.008
957831AF2-077 GEN
Solar/Wind Harmer
0.373
3138283WHITEMARSH
Solar/Wind Harmer
0.019
3142433PROV 92
Adder
0.212
3142433PROV 92
Adder
0.212
971167AH1-042 GEN
Solar/Wind Harmer
11.35
315976AC1-164 GENA
Solar/Wind Harmer
9.762
316169AC1-164_GENC
Solar/Wind Harmer
8.433
315975AC1-164 GENB
Solar/Wind Harmer
0.289
972265AH1-717 GEN
Adder
4.614
3151201GRAVEL4
Adder
4.325
3151191GRAVEL3
Adder
4.27
3151211GRAVEL5
Adder
4.27
316312AB1-027
Solar/Wind Harmer
0.224
316369SG1_INVT
Solar/Wind Harmer
1.181
316132AB2-190 GEN1
Solar/Wind Harmer
0.665
971445AH1-216 GEN
Solar/Wind Harmer
4
3141426STAFORD
Solar/Wind Helper
0.033
3150331BIRCHWDA
50/50
157.717
3141316ARNOLDS
50/50
2.011
3150351NORNECKC2
50/50
3.016
970575AG2-366 GEN
50/50
3.687
315749AE2-041 GEN
50/50
5.017
3141843SHACKLE
50/50
0.757
970737AG2-469 GEN
Solar/Wind Harmer
26.539
3141906WESTMOR
Solar/Wind Harmer
-0.018
316404AE1-155 C
Solar/Wind Harmer
5.246
316484AD2-074 GEN
Solar/Wind Harmer
6.24
970009AG2-005 GEN
Solar/Wind Harmer
3.098
962971AG1-146 GEN
Solar/Wind Harmer
4.369
316156AD2-030 GEN
Solar/Wind Harmer
0.446
3141873WAN 176
Solar/Wind Harmer
1.984
316280AD1-041 GEN
Solar/Wind Harmer
1.215
3141766HARMONY
Solar/Wind Harmer
1.411
316203AE2-005 GEN
Solar/Wind Harmer
6.619
3142433PROV 92
Adder
0.212
3142433PROV 92
Adder
0.212
316382AG1-145 C
Solar/Wind Harmer
0.264
3150921YORKTN3
Adder
1.889
3144216WINCHST
Adder
0.274
3142946ENON
Solar/Wind Harmer
-0.003
970293AG2-193 GEN
Solar/Wind Harmer
0.911
3151221GRAVEL6
Adder
4.32
3151171GRAVELC
Adder
0.831
961611AG1-000B GEN
Solar/Wind Harmer
1.4
3142416OLDCHRC
Solar/Wind Harmer
0.671
315778AD1-151 GEN
Solar/Wind Harmer
5.713
970129AG2-093 GEN
Solar/Wind Harmer
3.698
3143096IRON208
Adder
0.244
3143096IRON208
Adder
0.239
970133AG2-095 GEN
Solar/Wind Harmer
0.735
3145336SMITFLD
Solar/Wind Harmer
-0.003
957191AF2-013 GEN
50/50
65.491
3150341NORNECKC1
50/50
3.116
3150341NORNECKC1
50/50
3.091
963611AG1-210 GEN
50/50
0.997
316077AC2-138 C
Solar/Wind Harmer
0.664
958261AF2-120 GEN
Solar/Wind Harmer
10.538
316487AF1-042 GEN
Solar/Wind Harmer
3.265
316441AF1-014 GEN
Solar/Wind Harmer
1.058
316075AC2-137 C
Solar/Wind Harmer
0.221
3142946ENON
Solar/Wind Harmer
-0.001
316033AB2-134 GEN
Solar/Wind Harmer
2.132
315697AD1-025 GEN
Solar/Wind Harmer
1.337
3150691DARBY 3
Adder
4.134
3150701DARBY 4
Adder
4.124
3150681DARBY 2
Adder
4.12
3150671DARBY 1
Adder
4.115
316236AE1-162_GEN
Solar/Wind Harmer
0.194
3150351NORNECKC2
50/50
2.966
966661AG1-536 GEN
50/50
6.885
3141843SHACKLE
50/50
0.757
957971AF2-091 GEN
Solar/Wind Harmer
6.359
972135AH1-637 GEN
Solar/Wind Harmer
5.77
316337AD2-073 GEN
Solar/Wind Harmer
1.037
964211AG1-282 GEN
Solar/Wind Harmer
0.886
3141726DUNNSVL
Solar/Wind Harmer
-0.117
962861AG1-135 GEN
Solar/Wind Harmer
9.959
961951AG1-038 GEN
Solar/Wind Harmer
3.265
3138133OCRAN
Solar/Wind Harmer
-0.012
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.845
3142433PROV 92
Solar/Wind Harmer
-0.049
3142433PROV 92
Adder
0.212
3142433PROV 92
Adder
0.212
971317AH1-138 GEN
Solar/Wind Harmer
1.192
316159AE1-175 C
Solar/Wind Harmer
0.235
3138126ROCKLANDING
Solar/Wind Harmer
0.025
944631AF1-128 GEN
Adder
31.292
3151171GRAVELC
Adder
0.632
961611AG1-000B GEN
Solar/Wind Harmer
3.282
3142416OLDCHRC
Solar/Wind Harmer
-0.017
3142416OLDCHRC
Solar/Wind Harmer
-0.007
971647AH1-324 GEN
Solar/Wind Harmer
3.315
971069AG2-661 GEN
Solar/Wind Harmer
1.043
316458AB2-190 GEN2
Solar/Wind Harmer
0.665
970129AG2-093 GEN
Solar/Wind Harmer
1.498
3143096IRON208
Adder
0.244
3145336SMITFLD
Solar/Wind Harmer
-0.026
CPLELTFEXP_CPLE->PJM
CLTF
2.196
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.727
LAGNLTFEXP_LAGN->PJM
CLTF
1.637
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.831
TVALTFEXP_TVA->PJM
CLTF
0.827
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.235
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.846
MECLTFEXP_MEC->PJM
CLTF
0.811
SIGELTFEXP_SIGE->PJM
CLTF
0.025
NYPJM->LTFIMP_NY
CLTF
0.625
LGEELTFEXP_LGEE->PJM
CLTF
0.304
WECLTFEXP_WEC->PJM
CLTF
0.152

Details for 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FINES-6FREDBRG 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.84 %
Rating:548.02 MVA
Rating Type:B
MVA to Mitigate:656.73
MW Contribution:3.68
Bus #Bus NameTypeMW Contribution
3150331BIRCHWDA
50/50
158.961
3141316ARNOLDS
50/50
2.026
3150351NORNECKC2
50/50
3.02
970575AG2-366 GEN
50/50
3.68
315749AE2-041 GEN
50/50
4.976
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
3150921YORKTN3
50/50
2.003
3144216WINCHST
50/50
0.289
3151161SURRY 1
50/50
2.191
970737AG2-469 GEN
Solar/Wind Harmer
20.26
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.646
962971AG1-146 GEN
Solar/Wind Harmer
3.312
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.629
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.866
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.022
3151221GRAVEL6
Adder
4.147
3151171GRAVELC
Adder
0.798
970293AG2-193 GEN
Solar/Wind Harmer
0.603
315759AF1-018 GEN
50/50
4.976
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
972263AH1-716 GEN
50/50
35.649
3150611CHESTG7
50/50
0.379
3150631CHESTG8
50/50
0.372
971047AG2-646 GEN
50/50
10.599
944491AF1-114 GEN
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Harmer
0.297
3141813NORNECK
Solar/Wind Harmer
0.28
970327AG2-215 GEN
Solar/Wind Harmer
7.232
962981AG1-147 GEN
Solar/Wind Harmer
7.729
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.074
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.168
3141873WAN 176
Solar/Wind Harmer
0.03
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.097
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
8.942
315976AC1-164 GENA
Solar/Wind Harmer
8.275
316169AC1-164_GENC
Solar/Wind Harmer
7.149
315975AC1-164 GENB
Solar/Wind Harmer
0.245
972265AH1-717 GEN
Adder
4.429
3151201GRAVEL4
Adder
4.152
3151191GRAVEL3
Adder
4.099
3151211GRAVEL5
Adder
4.099
3141426STAFORD
Solar/Wind Helper
0.029
3150351NORNECKC2
50/50
2.97
966661AG1-536 GEN
50/50
6.884
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
971353AH1-157 GEN
50/50
7.642
970017AG2-010 GEN
50/50
4.875
3150641CHESTS8
50/50
0.192
944631AF1-128 GEN
50/50
30.156
3152331SURRY 2
50/50
2.455
972135AH1-637 GEN
Solar/Wind Harmer
4.407
316337AD2-073 GEN
Solar/Wind Harmer
0.3
3141726DUNNSVL
Solar/Wind Harmer
1.049
962861AG1-135 GEN
Solar/Wind Harmer
7.561
3138133OCRAN
Solar/Wind Harmer
0.104
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.365
3142433PROV 92
Solar/Wind Harmer
0.422
971317AH1-138 GEN
Solar/Wind Harmer
0.633
316159AE1-175 C
Solar/Wind Harmer
0.067
3138126ROCKLANDING
Solar/Wind Harmer
0.034
3151171GRAVELC
Adder
0.607
957191AF2-013 GEN
50/50
65.968
3150341NORNECKC1
50/50
3.119
3150341NORNECKC1
50/50
3.094
963611AG1-210 GEN
50/50
0.998
3150621CHESTS7
50/50
0.174
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
8.003
316075AC2-137 C
Solar/Wind Harmer
0.018
3142946ENON
Solar/Wind Harmer
0.007
CPLELTFEXP_CPLE->PJM
CLTF
1.912
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.152
LAGNLTFEXP_LAGN->PJM
CLTF
1.213
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.047
TVALTFEXP_TVA->PJM
CLTF
0.609
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.061
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.057
MECLTFEXP_MEC->PJM
CLTF
0.525
SIGELTFEXP_SIGE->PJM
CLTF
0.016
NYPJM->LTFIMP_NY
CLTF
0.465
LGEELTFEXP_LGEE->PJM
CLTF
0.185
WECLTFEXP_WEC->PJM
CLTF
0.092

Details for 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FINES-6FREDBRG 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.05 %
Rating:671.0 MVA
Rating Type:C
MVA to Mitigate:771.98
MW Contribution:3.66
Bus #Bus NameTypeMW Contribution
3150331BIRCHWDA
50/50
158.344
3141316ARNOLDS
50/50
2.018
3150351NORNECKC2
50/50
3.005
970575AG2-366 GEN
50/50
3.659
315749AE2-041 GEN
50/50
4.944
3141843SHACKLE
50/50
0.746
970737AG2-469 GEN
Solar/Wind Harmer
26.564
3141906WESTMOR
Solar/Wind Harmer
-0.018
316404AE1-155 C
Solar/Wind Harmer
5.218
316484AD2-074 GEN
Solar/Wind Harmer
6.199
970009AG2-005 GEN
Solar/Wind Harmer
3.078
962971AG1-146 GEN
Solar/Wind Harmer
4.336
316156AD2-030 GEN
Solar/Wind Harmer
0.44
3141873WAN 176
Solar/Wind Harmer
1.957
316280AD1-041 GEN
Solar/Wind Harmer
1.198
3141766HARMONY
Solar/Wind Harmer
1.39
316203AE2-005 GEN
Solar/Wind Harmer
6.52
3142433PROV 92
Adder
0.208
3142433PROV 92
Adder
0.208
316382AG1-145 C
Solar/Wind Harmer
0.255
3150921YORKTN3
Adder
1.818
3144216WINCHST
Adder
0.263
3142946ENON
Solar/Wind Harmer
-0.003
970293AG2-193 GEN
Solar/Wind Harmer
0.877
3142416OLDCHRC
Solar/Wind Harmer
0.646
3151221GRAVEL6
Adder
4.095
3151171GRAVELC
Adder
0.788
315759AF1-018 GEN
50/50
4.944
944491AF1-114 GEN
Solar/Wind Harmer
18.743
316223AC1-118
Solar/Wind Harmer
1.247
3141813NORNECK
Solar/Wind Harmer
-0.031
962981AG1-147 GEN
Solar/Wind Harmer
10.117
3141783LANCAST
Solar/Wind Harmer
-0.012
3141783LANCAST
Solar/Wind Harmer
-0.008
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.019
957601AF2-054 GEN
Solar/Wind Harmer
0.493
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
1.916
315666AE1-190 GEN
Solar/Wind Harmer
0.479
316059AD1-063 C
Solar/Wind Harmer
0.353
316314AB2-024 C
Solar/Wind Harmer
1.29
3143873LANEXA
Solar/Wind Harmer
-0.008
957831AF2-077 GEN
Solar/Wind Harmer
0.364
3138283WHITEMARSH
Solar/Wind Harmer
0.019
3142433PROV 92
Adder
0.208
3142433PROV 92
Adder
0.208
971167AH1-042 GEN
Solar/Wind Harmer
11.098
315976AC1-164 GENA
Solar/Wind Harmer
9.485
316169AC1-164_GENC
Solar/Wind Harmer
8.194
315975AC1-164 GENB
Solar/Wind Harmer
0.281
316312AB1-027
Solar/Wind Harmer
0.216
972265AH1-717 GEN
Adder
4.374
3151201GRAVEL4
Adder
4.1
3151191GRAVEL3
Adder
4.048
3151211GRAVEL5
Adder
4.048
3141426STAFORD
Solar/Wind Helper
0.031
3150351NORNECKC2
50/50
2.955
966661AG1-536 GEN
50/50
6.848
3141843SHACKLE
50/50
0.746
957971AF2-091 GEN
Solar/Wind Harmer
6.372
972135AH1-637 GEN
Solar/Wind Harmer
5.779
316337AD2-073 GEN
Solar/Wind Harmer
1.036
964211AG1-282 GEN
Solar/Wind Harmer
0.882
3141726DUNNSVL
Solar/Wind Harmer
-0.117
962861AG1-135 GEN
Solar/Wind Harmer
9.902
961951AG1-038 GEN
Solar/Wind Harmer
3.243
3138133OCRAN
Solar/Wind Harmer
-0.011
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.817
3142433PROV 92
Solar/Wind Harmer
-0.048
3142433PROV 92
Adder
0.208
3142433PROV 92
Adder
0.208
971317AH1-138 GEN
Solar/Wind Harmer
1.154
316159AE1-175 C
Solar/Wind Harmer
0.227
3138126ROCKLANDING
Solar/Wind Harmer
0.024
944631AF1-128 GEN
Adder
30.026
3142416OLDCHRC
Solar/Wind Harmer
-0.017
3142416OLDCHRC
Solar/Wind Harmer
-0.006
3151171GRAVELC
Adder
0.599
957191AF2-013 GEN
50/50
65.707
3150341NORNECKC1
50/50
3.104
3150341NORNECKC1
50/50
3.08
963611AG1-210 GEN
50/50
0.993
316077AC2-138 C
Solar/Wind Harmer
0.662
958261AF2-120 GEN
Solar/Wind Harmer
10.482
316487AF1-042 GEN
Solar/Wind Harmer
3.243
316441AF1-014 GEN
Solar/Wind Harmer
1.042
316075AC2-137 C
Solar/Wind Harmer
0.214
3142946ENON
Solar/Wind Harmer
-0.001
CPLELTFEXP_CPLE->PJM
CLTF
1.996
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.91
LAGNLTFEXP_LAGN->PJM
CLTF
1.485
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.39
TVALTFEXP_TVA->PJM
CLTF
0.75
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.728
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.582
MECLTFEXP_MEC->PJM
CLTF
0.734
SIGELTFEXP_SIGE->PJM
CLTF
0.022
NYPJM->LTFIMP_NY
CLTF
0.565
LGEELTFEXP_LGEE->PJM
CLTF
0.275
WECLTFEXP_WEC->PJM
CLTF
0.137

Details for 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FINES-6FREDBRG 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.84 %
Rating:671.0 MVA
Rating Type:C
MVA to Mitigate:743.72
MW Contribution:3.64
Bus #Bus NameTypeMW Contribution
3150331BIRCHWDA
50/50
157.958
3141316ARNOLDS
50/50
2.013
3150351NORNECKC2
50/50
2.993
970575AG2-366 GEN
50/50
3.64
315749AE2-041 GEN
50/50
4.91
3141843SHACKLE
50/50
0.741
970737AG2-469 GEN
Solar/Wind Harmer
26.481
315759AF1-018 GEN
50/50
4.91
944491AF1-114 GEN
Solar/Wind Harmer
18.689
316223AC1-118
Solar/Wind Harmer
1.243
3141813NORNECK
Solar/Wind Harmer
-0.031
962981AG1-147 GEN
Solar/Wind Harmer
10.065
3141783LANCAST
Solar/Wind Harmer
-0.012
3141783LANCAST
Solar/Wind Harmer
-0.008
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.019
957601AF2-054 GEN
Solar/Wind Harmer
0.49
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
1.903
315666AE1-190 GEN
Solar/Wind Harmer
0.476
316059AD1-063 C
Solar/Wind Harmer
0.351
316314AB2-024 C
Solar/Wind Harmer
1.281
3143873LANEXA
Solar/Wind Harmer
-0.008
957831AF2-077 GEN
Solar/Wind Harmer
0.361
3138283WHITEMARSH
Solar/Wind Harmer
0.019
3142433PROV 92
Adder
0.206
3142433PROV 92
Adder
0.206
971167AH1-042 GEN
Solar/Wind Harmer
11.004
315976AC1-164 GENA
Solar/Wind Harmer
9.38
316169AC1-164_GENC
Solar/Wind Harmer
8.103
315975AC1-164 GENB
Solar/Wind Harmer
0.278
3141426STAFORD
Solar/Wind Helper
0.031
3150351NORNECKC2
50/50
2.943
966661AG1-536 GEN
50/50
6.816
3141843SHACKLE
50/50
0.741
957971AF2-091 GEN
Solar/Wind Harmer
6.354
972135AH1-637 GEN
Solar/Wind Harmer
5.761
316337AD2-073 GEN
Solar/Wind Harmer
1.032
964211AG1-282 GEN
Solar/Wind Harmer
0.878
3141726DUNNSVL
Solar/Wind Harmer
-0.116
962861AG1-135 GEN
Solar/Wind Harmer
9.856
961951AG1-038 GEN
Solar/Wind Harmer
3.228
3138133OCRAN
Solar/Wind Harmer
-0.011
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.805
3142433PROV 92
Solar/Wind Harmer
-0.047
3142433PROV 92
Adder
0.206
3142433PROV 92
Adder
0.206
971317AH1-138 GEN
Solar/Wind Harmer
1.142
316159AE1-175 C
Solar/Wind Harmer
0.224
3138126ROCKLANDING
Solar/Wind Harmer
0.024
944631AF1-128 GEN
Adder
29.65
3141906WESTMOR
Solar/Wind Harmer
-0.018
316404AE1-155 C
Solar/Wind Harmer
5.194
316484AD2-074 GEN
Solar/Wind Harmer
6.168
970009AG2-005 GEN
Solar/Wind Harmer
3.063
962971AG1-146 GEN
Solar/Wind Harmer
4.314
316156AD2-030 GEN
Solar/Wind Harmer
0.438
3141873WAN 176
Solar/Wind Harmer
1.944
316280AD1-041 GEN
Solar/Wind Harmer
1.19
3141766HARMONY
Solar/Wind Harmer
1.381
316203AE2-005 GEN
Solar/Wind Harmer
6.476
3142433PROV 92
Adder
0.206
3142433PROV 92
Adder
0.206
316382AG1-145 C
Solar/Wind Harmer
0.252
3150921YORKTN3
Adder
1.799
3144216WINCHST
Adder
0.26
3142946ENON
Solar/Wind Harmer
-0.002
970293AG2-193 GEN
Solar/Wind Harmer
0.865
957191AF2-013 GEN
50/50
65.537
3150341NORNECKC1
50/50
3.091
3150341NORNECKC1
50/50
3.067
963611AG1-210 GEN
50/50
0.989
316077AC2-138 C
Solar/Wind Harmer
0.659
958261AF2-120 GEN
Solar/Wind Harmer
10.433
316487AF1-042 GEN
Solar/Wind Harmer
3.228
316441AF1-014 GEN
Solar/Wind Harmer
1.035
316075AC2-137 C
Solar/Wind Harmer
0.211
3142946ENON
Solar/Wind Harmer
-0.001
CPLELTFEXP_CPLE->PJM
CLTF
1.972
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.797
LAGNLTFEXP_LAGN->PJM
CLTF
1.464
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.333
TVALTFEXP_TVA->PJM
CLTF
0.74
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.655
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.545
MECLTFEXP_MEC->PJM
CLTF
0.723
SIGELTFEXP_SIGE->PJM
CLTF
0.022
NYPJM->LTFIMP_NY
CLTF
0.557
LGEELTFEXP_LGEE->PJM
CLTF
0.271
WECLTFEXP_WEC->PJM
CLTF
0.135

Details for 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FINES-6FREDBRG 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T557_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.1 %
Rating:671.0 MVA
Rating Type:C
MVA to Mitigate:732.03
MW Contribution:3.74
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
5.114
944491AF1-114 GEN
Solar/Wind Harmer
18.893
316223AC1-118
Solar/Wind Harmer
1.261
3141813NORNECK
Solar/Wind Harmer
-0.032
962981AG1-147 GEN
Solar/Wind Harmer
10.352
3141783LANCAST
Solar/Wind Harmer
-0.013
3141783LANCAST
Solar/Wind Harmer
-0.008
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.019
957601AF2-054 GEN
Solar/Wind Harmer
0.51
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
1.979
315666AE1-190 GEN
Solar/Wind Harmer
0.495
316059AD1-063 C
Solar/Wind Harmer
0.365
316314AB2-024 C
Solar/Wind Harmer
1.335
3143873LANEXA
Solar/Wind Harmer
-0.009
957831AF2-077 GEN
Solar/Wind Harmer
0.383
3138283WHITEMARSH
Solar/Wind Harmer
0.02
3142433PROV 92
Adder
0.213
3142433PROV 92
Adder
0.213
971167AH1-042 GEN
Solar/Wind Harmer
11.347
315976AC1-164 GENA
Solar/Wind Harmer
9.993
316169AC1-164_GENC
Solar/Wind Harmer
8.633
315975AC1-164 GENB
Solar/Wind Harmer
0.296
972265AH1-717 GEN
Adder
4.709
3151201GRAVEL4
Adder
4.414
3151191GRAVEL3
Adder
4.359
3151211GRAVEL5
Adder
4.359
971445AH1-216 GEN
Solar/Wind Harmer
4.118
316369SG1_INVT
Solar/Wind Harmer
1.177
316132AB2-190 GEN1
Solar/Wind Harmer
0.653
3152611GOSPORTB
Adder
0.72
3152621GOSPORTC
Adder
0.611
3152601GOSPORTA
Adder
0.564
3151081ELIZAR1
Adder
5.18
3151091ELIZAR2
Adder
5.09
3141426STAFORD
Solar/Wind Helper
0.029
957191AF2-013 GEN
50/50
66.107
3150341NORNECKC1
50/50
3.157
3150341NORNECKC1
50/50
3.131
963611AG1-210 GEN
50/50
1.01
316077AC2-138 C
Solar/Wind Harmer
0.673
958261AF2-120 GEN
Solar/Wind Harmer
10.688
316487AF1-042 GEN
Solar/Wind Harmer
3.314
316441AF1-014 GEN
Solar/Wind Harmer
1.076
316075AC2-137 C
Solar/Wind Harmer
0.218
3142946ENON
Solar/Wind Harmer
-0.001
316236AE1-162_GEN
Solar/Wind Harmer
0.2
316033AB2-134 GEN
Solar/Wind Harmer
2.125
315697AD1-025 GEN
Solar/Wind Harmer
1.333
316036AC1-147 C
Solar/Wind Harmer
0.171
3150991CHESPKB
Adder
0.592
3150991CHESPKB
Adder
0.578
316316AC1-027 C
Solar/Wind Harmer
0.194
3142956BIRDNECK
Solar/Wind Harmer
0.339
3150351NORNECKC2
50/50
3.005
966661AG1-536 GEN
50/50
6.983
3141843SHACKLE
50/50
0.77
957971AF2-091 GEN
Solar/Wind Harmer
6.423
972135AH1-637 GEN
Solar/Wind Harmer
5.83
316337AD2-073 GEN
Solar/Wind Harmer
1.05
964211AG1-282 GEN
Solar/Wind Harmer
0.898
3141726DUNNSVL
Solar/Wind Harmer
-0.119
962861AG1-135 GEN
Solar/Wind Harmer
10.102
961951AG1-038 GEN
Solar/Wind Harmer
3.314
3138133OCRAN
Solar/Wind Harmer
-0.012
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.876
3142433PROV 92
Solar/Wind Harmer
-0.049
3142433PROV 92
Adder
0.213
3142433PROV 92
Adder
0.213
971317AH1-138 GEN
Solar/Wind Harmer
1.242
316159AE1-175 C
Solar/Wind Harmer
0.244
3138126ROCKLANDING
Solar/Wind Harmer
0.026
944631AF1-128 GEN
Adder
30.563
3151171GRAVELC
Adder
0.645
961611AG1-000B GEN
Solar/Wind Harmer
3.32
971647AH1-324 GEN
Solar/Wind Harmer
3.329
3145336SMITFLD
Solar/Wind Harmer
-0.026
316072AD1-144
Solar/Wind Harmer
0.132
971069AG2-661 GEN
Solar/Wind Harmer
1.034
316458AB2-190 GEN2
Solar/Wind Harmer
0.653
316294AC1-161 GEN
Solar/Wind Harmer
2.086
970129AG2-093 GEN
Solar/Wind Harmer
1.47
316375AC2-012 GEN
Solar/Wind Harmer
2.199
3150981CHESPKA
Adder
0.706
3150331BIRCHWDA
50/50
159.142
3141316ARNOLDS
50/50
2.03
3150351NORNECKC2
50/50
3.056
970575AG2-366 GEN
50/50
3.744
315749AE2-041 GEN
50/50
5.114
3141843SHACKLE
50/50
0.77
970737AG2-469 GEN
Solar/Wind Harmer
26.822
3141906WESTMOR
Solar/Wind Harmer
-0.018
316404AE1-155 C
Solar/Wind Harmer
5.321
316484AD2-074 GEN
Solar/Wind Harmer
6.333
970009AG2-005 GEN
Solar/Wind Harmer
3.145
962971AG1-146 GEN
Solar/Wind Harmer
4.437
316156AD2-030 GEN
Solar/Wind Harmer
0.455
3141873WAN 176
Solar/Wind Harmer
2.022
316280AD1-041 GEN
Solar/Wind Harmer
1.237
3141766HARMONY
Solar/Wind Harmer
1.438
316203AE2-005 GEN
Solar/Wind Harmer
6.733
3142433PROV 92
Adder
0.213
3142433PROV 92
Adder
0.213
316382AG1-145 C
Solar/Wind Harmer
0.274
3150921YORKTN3
Adder
1.977
3144216WINCHST
Adder
0.286
3142946ENON
Solar/Wind Harmer
-0.003
970293AG2-193 GEN
Solar/Wind Harmer
0.865
3151221GRAVEL6
Adder
4.409
3151171GRAVELC
Adder
0.848
961611AG1-000B GEN
Solar/Wind Harmer
1.417
3145336SMITFLD
Solar/Wind Harmer
-0.003
315778AD1-151 GEN
Solar/Wind Harmer
5.662
315773AC2-141 GEN
Solar/Wind Harmer
2.698
970129AG2-093 GEN
Solar/Wind Harmer
3.628
3144536CHRHLND
Solar/Wind Harmer
-0.001
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.246
CPLELTFEXP_CPLE->PJM
CLTF
2.028
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.37
LAGNLTFEXP_LAGN->PJM
CLTF
1.264
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.275
TVALTFEXP_TVA->PJM
CLTF
0.634
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.084
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.136
MECLTFEXP_MEC->PJM
CLTF
0.538
SIGELTFEXP_SIGE->PJM
CLTF
0.016
NYPJM->LTFIMP_NY
CLTF
0.485
LGEELTFEXP_LGEE->PJM
CLTF
0.188
WECLTFEXP_WEC->PJM
CLTF
0.093

Details for 6NORNECK-6SANDERS 230.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6NORNECK-6SANDERS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.42 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:806.78
MW Contribution:3.8
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
5.241
3142433PROV 92
50/50
0.235
3142433PROV 92
50/50
0.235
3141813NORNECK
Solar/Wind Harmer
-0.032
962981AG1-147 GEN
Solar/Wind Harmer
10.501
3141783LANCAST
Solar/Wind Harmer
-0.013
3141783LANCAST
Solar/Wind Harmer
-0.008
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.02
957601AF2-054 GEN
Solar/Wind Harmer
0.521
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
2.027
315666AE1-190 GEN
Solar/Wind Harmer
0.507
316059AD1-063 C
Solar/Wind Harmer
0.374
316314AB2-024 C
Solar/Wind Harmer
1.371
3143873LANEXA
Solar/Wind Harmer
-0.009
957831AF2-077 GEN
Solar/Wind Harmer
0.395
3138283WHITEMARSH
Solar/Wind Harmer
0.02
971167AH1-042 GEN
Solar/Wind Harmer
11.796
315976AC1-164 GENA
Solar/Wind Harmer
10.515
316169AC1-164_GENC
Solar/Wind Harmer
9.084
315975AC1-164 GENB
Solar/Wind Harmer
0.311
972265AH1-717 GEN
Adder
4.985
3151201GRAVEL4
Adder
4.673
3151191GRAVEL3
Adder
4.614
3151211GRAVEL5
Adder
4.614
971445AH1-216 GEN
Solar/Wind Harmer
4.353
316369SG1_INVT
Solar/Wind Harmer
1.256
316132AB2-190 GEN1
Solar/Wind Harmer
0.7
3152611GOSPORTB
Adder
0.759
3152621GOSPORTC
Adder
0.644
3152601GOSPORTA
Adder
0.594
3151081ELIZAR1
Adder
5.459
3151091ELIZAR2
Adder
5.365
316312AB1-027
Solar/Wind Harmer
0.224
316305AF2-043 C
Solar/Wind Harmer
0.198
957871AF2-081 GEN
Solar/Wind Harmer
3.282
319010AE1-072 C
Solar/Wind Harmer
1.322
3146406KITTY HAWK
Solar/Wind Harmer
0.005
313526AB2-022
Solar/Wind Harmer
0.174
315835AF2-110_GEN
Solar/Wind Harmer
0.805
3146486SUNBURY
Solar/Wind Harmer
-0.006
3146486SUNBURY
Solar/Wind Harmer
-0.006
316321Z2-027
Solar/Wind Harmer
0.173
3146396TANGLEW
Solar/Wind Harmer
0.118
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
316311AC2-079 GEN
Solar/Wind Harmer
3.194
315833AF1-017_GEN
Solar/Wind Harmer
1.202
316349AD2-085 GEN
Solar/Wind Harmer
0.563
316223AC1-118
Solar/Wind Helper
2.132
3141426STAFORD
Solar/Wind Helper
0.03
3150351NORNECKC2
50/50
3.083
970575AG2-366 GEN
50/50
3.798
315749AE2-041 GEN
50/50
5.241
3141843SHACKLE
50/50
0.79
3142433PROV 92
50/50
0.235
3142433PROV 92
50/50
0.235
316404AE1-155 C
Solar/Wind Harmer
5.381
316484AD2-074 GEN
Solar/Wind Harmer
6.416
970009AG2-005 GEN
Solar/Wind Harmer
3.186
962971AG1-146 GEN
Solar/Wind Harmer
4.5
316156AD2-030 GEN
Solar/Wind Harmer
0.465
3141873WAN 176
Solar/Wind Harmer
2.068
316280AD1-041 GEN
Solar/Wind Harmer
1.267
3141766HARMONY
Solar/Wind Harmer
1.474
316203AE2-005 GEN
Solar/Wind Harmer
6.903
316382AG1-145 C
Solar/Wind Harmer
0.287
3150921YORKTN3
Adder
2.062
3144216WINCHST
Adder
0.299
3142946ENON
Solar/Wind Harmer
-0.003
970293AG2-193 GEN
Solar/Wind Harmer
0.939
3151221GRAVEL6
Adder
4.667
3151171GRAVELC
Adder
0.898
961611AG1-000B GEN
Solar/Wind Harmer
1.504
3145336SMITFLD
Solar/Wind Harmer
-0.003
315778AD1-151 GEN
Solar/Wind Harmer
6.05
970129AG2-093 GEN
Solar/Wind Harmer
3.89
970133AG2-095 GEN
Solar/Wind Harmer
0.765
3144536CHRHLND
Solar/Wind Harmer
-0.001
315773AC2-141 GEN
Solar/Wind Harmer
2.836
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.529
3143096IRON208
Adder
0.248
3143096IRON208
Adder
0.243
3142416OLDCHRC
Solar/Wind Harmer
0.671
944581AF1-123 GEN
Solar/Wind Harmer
30.183
944601AF1-125 GEN
Solar/Wind Harmer
29.712
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.798
316320Y1-086
Solar/Wind Harmer
0.378
316435W1029_GEN3
Solar/Wind Harmer
1.15
3141906WESTMOR
Solar/Wind Helper
0.56
3150341NORNECKC1
50/50
3.184
3150341NORNECKC1
50/50
3.159
963611AG1-210 GEN
50/50
1.019
316077AC2-138 C
Solar/Wind Harmer
0.679
958261AF2-120 GEN
Solar/Wind Harmer
10.809
316487AF1-042 GEN
Solar/Wind Harmer
3.357
316441AF1-014 GEN
Solar/Wind Harmer
1.104
316075AC2-137 C
Solar/Wind Harmer
0.233
3142946ENON
Solar/Wind Harmer
-0.001
316033AB2-134 GEN
Solar/Wind Harmer
2.267
315697AD1-025 GEN
Solar/Wind Harmer
1.422
316236AE1-162_GEN
Solar/Wind Harmer
0.211
316036AC1-147 C
Solar/Wind Harmer
0.181
3150991CHESPKB
Adder
0.624
3150991CHESPKB
Adder
0.609
316316AC1-027 C
Solar/Wind Harmer
0.205
3142956BIRDNECK
Solar/Wind Harmer
0.357
316185AD1-033 GEN
Solar/Wind Harmer
0.7
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316339AD2-160 GEN
Solar/Wind Harmer
0.443
316018AA1-139 ULT2
Solar/Wind Harmer
0.562
316017AA1-139 ULT1
Solar/Wind Harmer
0.531
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.773
3130086AYDLETT
Solar/Wind Harmer
-0.026
3150691DARBY 3
Adder
4.154
3150701DARBY 4
Adder
4.144
3150681DARBY 2
Adder
4.139
3150671DARBY 1
Adder
4.134
3146386ELIZ CT
Solar/Wind Harmer
-0.006
316431W1029_GEN1
Solar/Wind Harmer
1.15
316433W1029_GEN2
Solar/Wind Harmer
1.15
3150351NORNECKC2
50/50
3.032
966661AG1-536 GEN
50/50
7.062
3141843SHACKLE
50/50
0.79
3142433PROV 92
50/50
0.235
3142433PROV 92
50/50
0.235
964211AG1-282 GEN
Solar/Wind Harmer
0.907
3141726DUNNSVL
Solar/Wind Harmer
-0.12
962861AG1-135 GEN
Solar/Wind Harmer
10.221
961951AG1-038 GEN
Solar/Wind Harmer
3.357
3138133OCRAN
Solar/Wind Harmer
-0.012
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.924
3142433PROV 92
Solar/Wind Harmer
-0.051
971317AH1-138 GEN
Solar/Wind Harmer
1.291
316159AE1-175 C
Solar/Wind Harmer
0.256
3138126ROCKLANDING
Solar/Wind Harmer
0.028
944631AF1-128 GEN
Adder
32.755
3151171GRAVELC
Adder
0.683
961611AG1-000B GEN
Solar/Wind Harmer
3.524
971647AH1-324 GEN
Solar/Wind Harmer
3.542
3145336SMITFLD
Solar/Wind Harmer
-0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.105
316458AB2-190 GEN2
Solar/Wind Harmer
0.7
970129AG2-093 GEN
Solar/Wind Harmer
1.576
316072AD1-144
Solar/Wind Harmer
0.14
316294AC1-161 GEN
Solar/Wind Harmer
2.192
316375AC2-012 GEN
Solar/Wind Harmer
2.318
3150981CHESPKA
Adder
0.744
3143096IRON208
Adder
0.248
3142416OLDCHRC
Solar/Wind Harmer
-0.017
3142416OLDCHRC
Solar/Wind Harmer
-0.007
944591AF1-124 GEN
Solar/Wind Harmer
30.292
316246AF1-032 C
Solar/Wind Harmer
0.133
316388AE2-253 GEN
Solar/Wind Harmer
0.443
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316093AE2-104_GEN
Solar/Wind Harmer
1.873
316337AD2-073 GEN
Solar/Wind Helper
2.327
CPLELTFEXP_CPLE->PJM
CLTF
2.268
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.672
LAGNLTFEXP_LAGN->PJM
CLTF
1.635
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.933
TVALTFEXP_TVA->PJM
CLTF
0.824
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.17
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.828
MECLTFEXP_MEC->PJM
CLTF
0.801
SIGELTFEXP_SIGE->PJM
CLTF
0.024
NYPJM->LTFIMP_NY
CLTF
0.555
LGEELTFEXP_LGEE->PJM
CLTF
0.297
WECLTFEXP_WEC->PJM
CLTF
0.15

Details for 6NORNECK-6SANDERS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6NORNECK-6SANDERS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.31 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:659.04
MW Contribution:3.67
Bus #Bus NameTypeMW Contribution
3150341NORNECKC1
50/50
3.111
3150341NORNECKC1
50/50
3.086
963611AG1-210 GEN
50/50
0.996
3150621CHESTS7
50/50
0.186
316077AC2-138 C
Solar/Wind Harmer
0.001
3150351NORNECKC2
50/50
3.012
970575AG2-366 GEN
50/50
3.67
315749AE2-041 GEN
50/50
4.965
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150921YORKTN3
50/50
1.944
3144216WINCHST
50/50
0.281
3151161SURRY 1
50/50
2.187
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.641
962971AG1-146 GEN
Solar/Wind Harmer
3.303
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.62
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.862
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.674
3142416OLDCHRC
Solar/Wind Harmer
0.56
3151221GRAVEL6
Adder
4.139
3151171GRAVELC
Adder
0.796
961611AG1-000B GEN
Solar/Wind Harmer
1.513
315778AD1-151 GEN
Solar/Wind Harmer
4.508
3141906WESTMOR
Solar/Wind Helper
0.564
3150351NORNECKC2
50/50
2.962
966661AG1-536 GEN
50/50
6.865
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
971353AH1-157 GEN
50/50
7.457
970017AG2-010 GEN
50/50
4.736
3150641CHESTS8
50/50
0.205
944631AF1-128 GEN
50/50
32.202
3141726DUNNSVL
Solar/Wind Harmer
1.046
962861AG1-135 GEN
Solar/Wind Harmer
7.54
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.365
3142433PROV 92
Solar/Wind Harmer
0.43
971317AH1-138 GEN
Solar/Wind Harmer
0.617
316159AE1-175 C
Solar/Wind Harmer
0.065
3138126ROCKLANDING
Solar/Wind Harmer
0.033
3142416OLDCHRC
Solar/Wind Harmer
0.15
3142416OLDCHRC
Solar/Wind Harmer
0.058
3151171GRAVELC
Adder
0.606
961611AG1-000B GEN
Solar/Wind Harmer
2.976
971647AH1-324 GEN
Solar/Wind Harmer
2.415
971069AG2-661 GEN
Solar/Wind Harmer
1.002
316337AD2-073 GEN
Solar/Wind Helper
2.345
315759AF1-018 GEN
50/50
4.965
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150611CHESTG7
50/50
0.404
3150631CHESTG8
50/50
0.398
971047AG2-646 GEN
50/50
11.319
972263AH1-716 GEN
50/50
33.189
3141813NORNECK
Solar/Wind Harmer
0.28
970327AG2-215 GEN
Solar/Wind Harmer
7.212
962981AG1-147 GEN
Solar/Wind Harmer
7.706
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
0.029
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.097
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
9.171
315976AC1-164 GENA
Solar/Wind Harmer
8.348
316169AC1-164_GENC
Solar/Wind Harmer
7.212
315975AC1-164 GENB
Solar/Wind Harmer
0.247
316312AB1-027
Solar/Wind Harmer
0.103
972265AH1-717 GEN
Adder
4.42
3151201GRAVEL4
Adder
4.144
3151191GRAVEL3
Adder
4.091
3151211GRAVEL5
Adder
4.091
316369SG1_INVT
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Helper
2.149
3141426STAFORD
Solar/Wind Helper
0.031
958261AF2-120 GEN
Solar/Wind Harmer
7.981
316075AC2-137 C
Solar/Wind Harmer
0.02
3142946ENON
Solar/Wind Harmer
0.007
316033AB2-134 GEN
Solar/Wind Harmer
0.003
315697AD1-025 GEN
Solar/Wind Harmer
0.063
CPLELTFEXP_CPLE->PJM
CLTF
2.043
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.462
LAGNLTFEXP_LAGN->PJM
CLTF
1.568
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.516
TVALTFEXP_TVA->PJM
CLTF
0.792
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.326
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.737
MECLTFEXP_MEC->PJM
CLTF
0.803
SIGELTFEXP_SIGE->PJM
CLTF
0.025
NYPJM->LTFIMP_NY
CLTF
0.537
LGEELTFEXP_LGEE->PJM
CLTF
0.304
WECLTFEXP_WEC->PJM
CLTF
0.153

Details for 6NORNECK-6SANDERS 230.0 kV Ckt 1 line l/o DVP_P4-2: 574T575_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6NORNECK-6SANDERS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 574T575_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.01 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:741.02
MW Contribution:3.7
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
5.036
3141813NORNECK
Solar/Wind Harmer
-0.031
962981AG1-147 GEN
Solar/Wind Harmer
10.221
3141783LANCAST
Solar/Wind Harmer
-0.012
3141783LANCAST
Solar/Wind Harmer
-0.008
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.019
957601AF2-054 GEN
Solar/Wind Harmer
0.502
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
1.951
315666AE1-190 GEN
Solar/Wind Harmer
0.488
316059AD1-063 C
Solar/Wind Harmer
0.36
316314AB2-024 C
Solar/Wind Harmer
1.315
3143873LANEXA
Solar/Wind Harmer
-0.008
957831AF2-077 GEN
Solar/Wind Harmer
0.375
3138283WHITEMARSH
Solar/Wind Harmer
0.019
3142433PROV 92
Adder
0.214
3142433PROV 92
Adder
0.214
971167AH1-042 GEN
Solar/Wind Harmer
11.41
315976AC1-164 GENA
Solar/Wind Harmer
9.827
316169AC1-164_GENC
Solar/Wind Harmer
8.489
315975AC1-164 GENB
Solar/Wind Harmer
0.291
972265AH1-717 GEN
Adder
4.656
3151201GRAVEL4
Adder
4.365
3151191GRAVEL3
Adder
4.31
3151211GRAVEL5
Adder
4.31
316312AB1-027
Solar/Wind Harmer
0.226
316369SG1_INVT
Solar/Wind Harmer
1.192
316132AB2-190 GEN1
Solar/Wind Harmer
0.671
971445AH1-216 GEN
Solar/Wind Harmer
4.038
316223AC1-118
Solar/Wind Helper
2.149
3141426STAFORD
Solar/Wind Helper
0.032
3150351NORNECKC2
50/50
3.022
970575AG2-366 GEN
50/50
3.697
315749AE2-041 GEN
50/50
5.036
3141843SHACKLE
50/50
0.76
316404AE1-155 C
Solar/Wind Harmer
5.258
316484AD2-074 GEN
Solar/Wind Harmer
6.256
970009AG2-005 GEN
Solar/Wind Harmer
3.106
962971AG1-146 GEN
Solar/Wind Harmer
4.38
316156AD2-030 GEN
Solar/Wind Harmer
0.448
3141873WAN 176
Solar/Wind Harmer
1.992
316280AD1-041 GEN
Solar/Wind Harmer
1.22
3141766HARMONY
Solar/Wind Harmer
1.416
316203AE2-005 GEN
Solar/Wind Harmer
6.645
3142433PROV 92
Adder
0.214
3142433PROV 92
Adder
0.214
316382AG1-145 C
Solar/Wind Harmer
0.265
3150921YORKTN3
Adder
1.903
3144216WINCHST
Adder
0.276
3142946ENON
Solar/Wind Harmer
-0.003
970293AG2-193 GEN
Solar/Wind Harmer
0.919
3151221GRAVEL6
Adder
4.36
3151171GRAVELC
Adder
0.839
961611AG1-000B GEN
Solar/Wind Harmer
1.413
3142416OLDCHRC
Solar/Wind Harmer
0.677
315778AD1-151 GEN
Solar/Wind Harmer
5.766
970129AG2-093 GEN
Solar/Wind Harmer
3.733
3143096IRON208
Adder
0.246
3143096IRON208
Adder
0.241
970133AG2-095 GEN
Solar/Wind Harmer
0.742
3145336SMITFLD
Solar/Wind Harmer
-0.003
3141906WESTMOR
Solar/Wind Helper
0.564
3150351NORNECKC2
50/50
2.972
966661AG1-536 GEN
50/50
6.9
3141843SHACKLE
50/50
0.76
964211AG1-282 GEN
Solar/Wind Harmer
0.888
3141726DUNNSVL
Solar/Wind Harmer
-0.117
962861AG1-135 GEN
Solar/Wind Harmer
9.982
961951AG1-038 GEN
Solar/Wind Harmer
3.273
3138133OCRAN
Solar/Wind Harmer
-0.012
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.852
3142433PROV 92
Solar/Wind Harmer
-0.049
3142433PROV 92
Adder
0.214
3142433PROV 92
Adder
0.214
971317AH1-138 GEN
Solar/Wind Harmer
1.199
316159AE1-175 C
Solar/Wind Harmer
0.236
3138126ROCKLANDING
Solar/Wind Harmer
0.025
944631AF1-128 GEN
Adder
31.554
3151171GRAVELC
Adder
0.638
961611AG1-000B GEN
Solar/Wind Harmer
3.313
3142416OLDCHRC
Solar/Wind Harmer
-0.017
3142416OLDCHRC
Solar/Wind Harmer
-0.007
971647AH1-324 GEN
Solar/Wind Harmer
3.346
971069AG2-661 GEN
Solar/Wind Harmer
1.053
316458AB2-190 GEN2
Solar/Wind Harmer
0.671
970129AG2-093 GEN
Solar/Wind Harmer
1.512
3143096IRON208
Adder
0.246
3145336SMITFLD
Solar/Wind Harmer
-0.026
316072AD1-144
Solar/Wind Harmer
0.129
316337AD2-073 GEN
Solar/Wind Helper
2.344
3150341NORNECKC1
50/50
3.122
3150341NORNECKC1
50/50
3.097
963611AG1-210 GEN
50/50
0.999
316077AC2-138 C
Solar/Wind Harmer
0.666
958261AF2-120 GEN
Solar/Wind Harmer
10.562
316487AF1-042 GEN
Solar/Wind Harmer
3.273
316441AF1-014 GEN
Solar/Wind Harmer
1.062
316075AC2-137 C
Solar/Wind Harmer
0.223
3142946ENON
Solar/Wind Harmer
-0.001
316033AB2-134 GEN
Solar/Wind Harmer
2.152
315697AD1-025 GEN
Solar/Wind Harmer
1.349
3150691DARBY 3
Adder
4.174
3150701DARBY 4
Adder
4.164
3150681DARBY 2
Adder
4.159
3150671DARBY 1
Adder
4.154
316236AE1-162_GEN
Solar/Wind Harmer
0.196
CPLELTFEXP_CPLE->PJM
CLTF
2.242
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.294
LAGNLTFEXP_LAGN->PJM
CLTF
1.722
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.959
TVALTFEXP_TVA->PJM
CLTF
0.87
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.85
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.006
MECLTFEXP_MEC->PJM
CLTF
0.882
SIGELTFEXP_SIGE->PJM
CLTF
0.027
NYPJM->LTFIMP_NY
CLTF
0.598
LGEELTFEXP_LGEE->PJM
CLTF
0.333
WECLTFEXP_WEC->PJM
CLTF
0.168

Details for 6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.39 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:792.63
MW Contribution:3.79
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
5.235
3142433PROV 92
50/50
0.234
3142433PROV 92
50/50
0.234
316223AC1-118
Solar/Wind Harmer
1.265
3141813NORNECK
Solar/Wind Harmer
-0.032
962981AG1-147 GEN
Solar/Wind Harmer
10.492
3141783LANCAST
Solar/Wind Harmer
-0.013
3141783LANCAST
Solar/Wind Harmer
-0.008
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.02
957601AF2-054 GEN
Solar/Wind Harmer
0.521
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
2.024
315666AE1-190 GEN
Solar/Wind Harmer
0.506
316059AD1-063 C
Solar/Wind Harmer
0.374
316314AB2-024 C
Solar/Wind Harmer
1.369
3143873LANEXA
Solar/Wind Harmer
-0.009
957831AF2-077 GEN
Solar/Wind Harmer
0.394
3138283WHITEMARSH
Solar/Wind Harmer
0.02
971167AH1-042 GEN
Solar/Wind Harmer
11.777
315976AC1-164 GENA
Solar/Wind Harmer
10.494
316169AC1-164_GENC
Solar/Wind Harmer
9.066
315975AC1-164 GENB
Solar/Wind Harmer
0.31
972265AH1-717 GEN
Adder
4.971
3151201GRAVEL4
Adder
4.66
3151191GRAVEL3
Adder
4.601
3151211GRAVEL5
Adder
4.601
971445AH1-216 GEN
Solar/Wind Harmer
4.341
316369SG1_INVT
Solar/Wind Harmer
1.252
316132AB2-190 GEN1
Solar/Wind Harmer
0.698
3152611GOSPORTB
Adder
0.757
3152621GOSPORTC
Adder
0.642
3152601GOSPORTA
Adder
0.592
3151081ELIZAR1
Adder
5.443
3151091ELIZAR2
Adder
5.349
316312AB1-027
Solar/Wind Harmer
0.224
316305AF2-043 C
Solar/Wind Harmer
0.198
957871AF2-081 GEN
Solar/Wind Harmer
3.272
319010AE1-072 C
Solar/Wind Harmer
1.318
3146406KITTY HAWK
Solar/Wind Harmer
0.005
313526AB2-022
Solar/Wind Harmer
0.173
315835AF2-110_GEN
Solar/Wind Harmer
0.803
3146486SUNBURY
Solar/Wind Harmer
-0.006
3146486SUNBURY
Solar/Wind Harmer
-0.006
316321Z2-027
Solar/Wind Harmer
0.172
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.117
3141426STAFORD
Solar/Wind Helper
0.031
3150351NORNECKC2
50/50
3.081
970575AG2-366 GEN
50/50
3.795
315749AE2-041 GEN
50/50
5.235
3141843SHACKLE
50/50
0.789
3142433PROV 92
50/50
0.234
3142433PROV 92
50/50
0.234
970737AG2-469 GEN
Solar/Wind Harmer
26.869
3141906WESTMOR
Solar/Wind Harmer
-0.019
316404AE1-155 C
Solar/Wind Harmer
5.377
316484AD2-074 GEN
Solar/Wind Harmer
6.411
970009AG2-005 GEN
Solar/Wind Harmer
3.184
962971AG1-146 GEN
Solar/Wind Harmer
4.497
316156AD2-030 GEN
Solar/Wind Harmer
0.465
3141873WAN 176
Solar/Wind Harmer
2.065
316280AD1-041 GEN
Solar/Wind Harmer
1.265
3141766HARMONY
Solar/Wind Harmer
1.472
316203AE2-005 GEN
Solar/Wind Harmer
6.895
316382AG1-145 C
Solar/Wind Harmer
0.286
3150921YORKTN3
Adder
2.058
3144216WINCHST
Adder
0.298
3142946ENON
Solar/Wind Harmer
-0.003
970293AG2-193 GEN
Solar/Wind Harmer
0.937
3151221GRAVEL6
Adder
4.655
3151171GRAVELC
Adder
0.896
961611AG1-000B GEN
Solar/Wind Harmer
1.5
3145336SMITFLD
Solar/Wind Harmer
-0.003
315778AD1-151 GEN
Solar/Wind Harmer
6.033
970129AG2-093 GEN
Solar/Wind Harmer
3.879
970133AG2-095 GEN
Solar/Wind Harmer
0.763
3144536CHRHLND
Solar/Wind Harmer
-0.001
315773AC2-141 GEN
Solar/Wind Harmer
2.827
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.513
3143096IRON208
Adder
0.248
3143096IRON208
Adder
0.243
3142416OLDCHRC
Solar/Wind Harmer
0.669
944581AF1-123 GEN
Solar/Wind Harmer
30.093
944601AF1-125 GEN
Solar/Wind Harmer
29.624
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.795
316320Y1-086
Solar/Wind Harmer
0.376
316435W1029_GEN3
Solar/Wind Harmer
1.147
3150341NORNECKC1
50/50
3.183
3150351NORNECKC2
50/50
3.03
966661AG1-536 GEN
50/50
7.057
3141843SHACKLE
50/50
0.789
3142433PROV 92
50/50
0.234
3142433PROV 92
50/50
0.234
972135AH1-637 GEN
Solar/Wind Harmer
5.836
316337AD2-073 GEN
Solar/Wind Harmer
1.055
964211AG1-282 GEN
Solar/Wind Harmer
0.906
3141726DUNNSVL
Solar/Wind Harmer
-0.12
962861AG1-135 GEN
Solar/Wind Harmer
10.214
961951AG1-038 GEN
Solar/Wind Harmer
3.355
3138133OCRAN
Solar/Wind Harmer
-0.012
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.921
3142433PROV 92
Solar/Wind Harmer
-0.051
971317AH1-138 GEN
Solar/Wind Harmer
1.288
316159AE1-175 C
Solar/Wind Harmer
0.255
3138126ROCKLANDING
Solar/Wind Harmer
0.028
944631AF1-128 GEN
Adder
32.671
3151171GRAVELC
Adder
0.681
961611AG1-000B GEN
Solar/Wind Harmer
3.515
971647AH1-324 GEN
Solar/Wind Harmer
3.532
3145336SMITFLD
Solar/Wind Harmer
-0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.102
316458AB2-190 GEN2
Solar/Wind Harmer
0.698
970129AG2-093 GEN
Solar/Wind Harmer
1.571
316072AD1-144
Solar/Wind Harmer
0.139
316294AC1-161 GEN
Solar/Wind Harmer
2.186
316375AC2-012 GEN
Solar/Wind Harmer
2.311
3150981CHESPKA
Adder
0.742
3143096IRON208
Adder
0.248
3142416OLDCHRC
Solar/Wind Harmer
-0.017
3142416OLDCHRC
Solar/Wind Harmer
-0.007
944591AF1-124 GEN
Solar/Wind Harmer
30.202
316246AF1-032 C
Solar/Wind Harmer
0.133
316388AE2-253 GEN
Solar/Wind Harmer
0.442
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316093AE2-104_GEN
Solar/Wind Harmer
1.867
3150341NORNECKC1
50/50
3.157
963611AG1-210 GEN
50/50
1.018
316077AC2-138 C
Solar/Wind Harmer
0.679
958261AF2-120 GEN
Solar/Wind Harmer
10.801
316487AF1-042 GEN
Solar/Wind Harmer
3.355
316441AF1-014 GEN
Solar/Wind Harmer
1.102
316075AC2-137 C
Solar/Wind Harmer
0.232
3142946ENON
Solar/Wind Harmer
-0.001
316033AB2-134 GEN
Solar/Wind Harmer
2.26
315697AD1-025 GEN
Solar/Wind Harmer
1.418
316236AE1-162_GEN
Solar/Wind Harmer
0.211
316036AC1-147 C
Solar/Wind Harmer
0.18
3150991CHESPKB
Adder
0.623
3150991CHESPKB
Adder
0.608
316316AC1-027 C
Solar/Wind Harmer
0.204
3142956BIRDNECK
Solar/Wind Harmer
0.356
316185AD1-033 GEN
Solar/Wind Harmer
0.698
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316339AD2-160 GEN
Solar/Wind Harmer
0.442
316018AA1-139 ULT2
Solar/Wind Harmer
0.561
316017AA1-139 ULT1
Solar/Wind Harmer
0.53
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.771
3130086AYDLETT
Solar/Wind Harmer
-0.026
3150691DARBY 3
Adder
4.141
3150701DARBY 4
Adder
4.131
3150681DARBY 2
Adder
4.127
3150671DARBY 1
Adder
4.122
3146386ELIZ CT
Solar/Wind Harmer
-0.006
316431W1029_GEN1
Solar/Wind Harmer
1.147
316433W1029_GEN2
Solar/Wind Harmer
1.147
CPLELTFEXP_CPLE->PJM
CLTF
2.253
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.492
LAGNLTFEXP_LAGN->PJM
CLTF
1.608
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.892
TVALTFEXP_TVA->PJM
CLTF
0.81
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.974
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.777
MECLTFEXP_MEC->PJM
CLTF
0.779
SIGELTFEXP_SIGE->PJM
CLTF
0.024
NYPJM->LTFIMP_NY
CLTF
0.564
LGEELTFEXP_LGEE->PJM
CLTF
0.288
WECLTFEXP_WEC->PJM
CLTF
0.144

Details for 6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.12 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:635.05
MW Contribution:3.67
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
2.96
966661AG1-536 GEN
50/50
6.86
3141843SHACKLE
50/50
0.748
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
971353AH1-157 GEN
50/50
7.442
970017AG2-010 GEN
50/50
4.725
3150641CHESTS8
50/50
0.204
944631AF1-128 GEN
50/50
32.114
972135AH1-637 GEN
Solar/Wind Harmer
4.393
316337AD2-073 GEN
Solar/Wind Harmer
0.299
3141726DUNNSVL
Solar/Wind Harmer
1.045
962861AG1-135 GEN
Solar/Wind Harmer
7.535
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.364
3150341NORNECKC1
50/50
3.109
3150341NORNECKC1
50/50
3.084
963611AG1-210 GEN
50/50
0.995
3150621CHESTS7
50/50
0.185
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
7.975
316075AC2-137 C
Solar/Wind Harmer
0.02
3142946ENON
Solar/Wind Harmer
0.007
316033AB2-134 GEN
Solar/Wind Harmer
0.003
315697AD1-025 GEN
Solar/Wind Harmer
0.063
3142433PROV 92
Solar/Wind Harmer
0.43
971317AH1-138 GEN
Solar/Wind Harmer
0.616
316159AE1-175 C
Solar/Wind Harmer
0.065
3138126ROCKLANDING
Solar/Wind Harmer
0.033
3142416OLDCHRC
Solar/Wind Harmer
0.15
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.604
961611AG1-000B GEN
Solar/Wind Harmer
2.967
971647AH1-324 GEN
Solar/Wind Harmer
2.407
315759AF1-018 GEN
50/50
4.959
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150611CHESTG7
50/50
0.403
3150631CHESTG8
50/50
0.397
971047AG2-646 GEN
50/50
11.288
972263AH1-716 GEN
50/50
33.088
316223AC1-118
Solar/Wind Harmer
0.296
3141813NORNECK
Solar/Wind Harmer
0.28
970327AG2-215 GEN
Solar/Wind Harmer
7.206
962981AG1-147 GEN
Solar/Wind Harmer
7.699
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
0.029
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.092
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
9.155
315976AC1-164 GENA
Solar/Wind Harmer
8.33
316169AC1-164_GENC
Solar/Wind Harmer
7.197
315975AC1-164 GENB
Solar/Wind Harmer
0.246
316312AB1-027
Solar/Wind Harmer
0.103
972265AH1-717 GEN
Adder
4.406
3151201GRAVEL4
Adder
4.131
3151191GRAVEL3
Adder
4.078
3151211GRAVEL5
Adder
4.078
316369SG1_INVT
Solar/Wind Harmer
0.002
3141426STAFORD
Solar/Wind Helper
0.031
3150351NORNECKC2
50/50
3.01
970575AG2-366 GEN
50/50
3.666
315749AE2-041 GEN
50/50
4.959
3141843SHACKLE
50/50
0.748
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150921YORKTN3
50/50
1.939
3144216WINCHST
50/50
0.281
3151161SURRY 1
50/50
2.18
970737AG2-469 GEN
Solar/Wind Harmer
20.194
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.64
962971AG1-146 GEN
Solar/Wind Harmer
3.3
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.617
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.86
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.672
3142416OLDCHRC
Solar/Wind Harmer
0.558
3151221GRAVEL6
Adder
4.126
3151171GRAVELC
Adder
0.794
961611AG1-000B GEN
Solar/Wind Harmer
1.508
CPLELTFEXP_CPLE->PJM
CLTF
2.028
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.282
LAGNLTFEXP_LAGN->PJM
CLTF
1.541
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.475
TVALTFEXP_TVA->PJM
CLTF
0.778
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.13
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.686
MECLTFEXP_MEC->PJM
CLTF
0.78
SIGELTFEXP_SIGE->PJM
CLTF
0.024
NYPJM->LTFIMP_NY
CLTF
0.546
LGEELTFEXP_LGEE->PJM
CLTF
0.294
WECLTFEXP_WEC->PJM
CLTF
0.148

Details for 6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 574T575_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 574T575_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.65 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:731.51
MW Contribution:3.69
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
5.03
316223AC1-118
Solar/Wind Harmer
1.248
3141813NORNECK
Solar/Wind Harmer
-0.031
962981AG1-147 GEN
Solar/Wind Harmer
10.212
3141783LANCAST
Solar/Wind Harmer
-0.012
3141783LANCAST
Solar/Wind Harmer
-0.008
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.019
957601AF2-054 GEN
Solar/Wind Harmer
0.501
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
1.949
315666AE1-190 GEN
Solar/Wind Harmer
0.487
316059AD1-063 C
Solar/Wind Harmer
0.359
316314AB2-024 C
Solar/Wind Harmer
1.313
3143873LANEXA
Solar/Wind Harmer
-0.008
957831AF2-077 GEN
Solar/Wind Harmer
0.374
3138283WHITEMARSH
Solar/Wind Harmer
0.019
3142433PROV 92
Adder
0.213
3142433PROV 92
Adder
0.213
971167AH1-042 GEN
Solar/Wind Harmer
11.391
315976AC1-164 GENA
Solar/Wind Harmer
9.806
316169AC1-164_GENC
Solar/Wind Harmer
8.472
315975AC1-164 GENB
Solar/Wind Harmer
0.29
972265AH1-717 GEN
Adder
4.643
3151201GRAVEL4
Adder
4.352
3151191GRAVEL3
Adder
4.297
3151211GRAVEL5
Adder
4.297
316312AB1-027
Solar/Wind Harmer
0.226
316369SG1_INVT
Solar/Wind Harmer
1.189
316132AB2-190 GEN1
Solar/Wind Harmer
0.669
971445AH1-216 GEN
Solar/Wind Harmer
4.026
3141426STAFORD
Solar/Wind Helper
0.032
3150341NORNECKC1
50/50
3.12
3150341NORNECKC1
50/50
3.095
963611AG1-210 GEN
50/50
0.998
316077AC2-138 C
Solar/Wind Harmer
0.665
958261AF2-120 GEN
Solar/Wind Harmer
10.554
316487AF1-042 GEN
Solar/Wind Harmer
3.271
316441AF1-014 GEN
Solar/Wind Harmer
1.061
316075AC2-137 C
Solar/Wind Harmer
0.222
3142946ENON
Solar/Wind Harmer
-0.001
316033AB2-134 GEN
Solar/Wind Harmer
2.145
315697AD1-025 GEN
Solar/Wind Harmer
1.346
3150691DARBY 3
Adder
4.161
3150701DARBY 4
Adder
4.151
3150681DARBY 2
Adder
4.146
3150671DARBY 1
Adder
4.142
316236AE1-162_GEN
Solar/Wind Harmer
0.195
3150351NORNECKC2
50/50
2.97
966661AG1-536 GEN
50/50
6.895
3141843SHACKLE
50/50
0.759
972135AH1-637 GEN
Solar/Wind Harmer
5.774
316337AD2-073 GEN
Solar/Wind Harmer
1.038
964211AG1-282 GEN
Solar/Wind Harmer
0.887
3141726DUNNSVL
Solar/Wind Harmer
-0.117
962861AG1-135 GEN
Solar/Wind Harmer
9.975
961951AG1-038 GEN
Solar/Wind Harmer
3.271
3138133OCRAN
Solar/Wind Harmer
-0.012
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.849
3142433PROV 92
Solar/Wind Harmer
-0.049
3142433PROV 92
Adder
0.213
3142433PROV 92
Adder
0.213
971317AH1-138 GEN
Solar/Wind Harmer
1.197
316159AE1-175 C
Solar/Wind Harmer
0.236
3138126ROCKLANDING
Solar/Wind Harmer
0.025
944631AF1-128 GEN
Adder
31.471
3150351NORNECKC2
50/50
3.02
970575AG2-366 GEN
50/50
3.693
315749AE2-041 GEN
50/50
5.03
3141843SHACKLE
50/50
0.759
970737AG2-469 GEN
Solar/Wind Harmer
26.56
3141906WESTMOR
Solar/Wind Harmer
-0.018
316404AE1-155 C
Solar/Wind Harmer
5.254
316484AD2-074 GEN
Solar/Wind Harmer
6.251
970009AG2-005 GEN
Solar/Wind Harmer
3.104
962971AG1-146 GEN
Solar/Wind Harmer
4.377
316156AD2-030 GEN
Solar/Wind Harmer
0.448
3141873WAN 176
Solar/Wind Harmer
1.989
316280AD1-041 GEN
Solar/Wind Harmer
1.218
3141766HARMONY
Solar/Wind Harmer
1.415
316203AE2-005 GEN
Solar/Wind Harmer
6.637
3142433PROV 92
Adder
0.213
3142433PROV 92
Adder
0.213
316382AG1-145 C
Solar/Wind Harmer
0.265
3150921YORKTN3
Adder
1.899
3144216WINCHST
Adder
0.275
3142946ENON
Solar/Wind Harmer
-0.003
970293AG2-193 GEN
Solar/Wind Harmer
0.916
3151221GRAVEL6
Adder
4.347
3151171GRAVELC
Adder
0.836
961611AG1-000B GEN
Solar/Wind Harmer
1.409
3142416OLDCHRC
Solar/Wind Harmer
0.675
315778AD1-151 GEN
Solar/Wind Harmer
5.749
970129AG2-093 GEN
Solar/Wind Harmer
3.722
3143096IRON208
Adder
0.245
3143096IRON208
Adder
0.24
970133AG2-095 GEN
Solar/Wind Harmer
0.739
3145336SMITFLD
Solar/Wind Harmer
-0.003
3151171GRAVELC
Adder
0.636
961611AG1-000B GEN
Solar/Wind Harmer
3.303
3142416OLDCHRC
Solar/Wind Harmer
-0.017
3142416OLDCHRC
Solar/Wind Harmer
-0.007
971647AH1-324 GEN
Solar/Wind Harmer
3.336
971069AG2-661 GEN
Solar/Wind Harmer
1.05
316458AB2-190 GEN2
Solar/Wind Harmer
0.669
970129AG2-093 GEN
Solar/Wind Harmer
1.508
3143096IRON208
Adder
0.245
3145336SMITFLD
Solar/Wind Harmer
-0.026
316072AD1-144
Solar/Wind Harmer
0.128
CPLELTFEXP_CPLE->PJM
CLTF
2.227
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.114
LAGNLTFEXP_LAGN->PJM
CLTF
1.695
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.918
TVALTFEXP_TVA->PJM
CLTF
0.856
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.654
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.955
MECLTFEXP_MEC->PJM
CLTF
0.859
SIGELTFEXP_SIGE->PJM
CLTF
0.026
NYPJM->LTFIMP_NY
CLTF
0.606
LGEELTFEXP_LGEE->PJM
CLTF
0.324
WECLTFEXP_WEC->PJM
CLTF
0.163

Details for 6SANDERS-6WESTMOR 230.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.69 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:794.66
MW Contribution:3.8
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
5.238
3142433PROV 92
50/50
0.234
3142433PROV 92
50/50
0.234
3141813NORNECK
Solar/Wind Harmer
-0.032
962981AG1-147 GEN
Solar/Wind Harmer
10.497
3141783LANCAST
Solar/Wind Harmer
-0.013
3141783LANCAST
Solar/Wind Harmer
-0.008
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.02
957601AF2-054 GEN
Solar/Wind Harmer
0.521
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
2.026
315666AE1-190 GEN
Solar/Wind Harmer
0.506
316059AD1-063 C
Solar/Wind Harmer
0.374
316314AB2-024 C
Solar/Wind Harmer
1.37
3143873LANEXA
Solar/Wind Harmer
-0.009
957831AF2-077 GEN
Solar/Wind Harmer
0.395
3138283WHITEMARSH
Solar/Wind Harmer
0.02
971167AH1-042 GEN
Solar/Wind Harmer
11.787
315976AC1-164 GENA
Solar/Wind Harmer
10.505
316169AC1-164_GENC
Solar/Wind Harmer
9.075
315975AC1-164 GENB
Solar/Wind Harmer
0.311
972265AH1-717 GEN
Adder
4.978
3151201GRAVEL4
Adder
4.667
3151191GRAVEL3
Adder
4.608
3151211GRAVEL5
Adder
4.608
3150351NORNECKC2
50/50
3.082
970575AG2-366 GEN
50/50
3.796
315749AE2-041 GEN
50/50
5.238
3141843SHACKLE
50/50
0.789
3142433PROV 92
50/50
0.234
3142433PROV 92
50/50
0.234
316404AE1-155 C
Solar/Wind Harmer
5.379
316484AD2-074 GEN
Solar/Wind Harmer
6.414
970009AG2-005 GEN
Solar/Wind Harmer
3.185
962971AG1-146 GEN
Solar/Wind Harmer
4.499
316156AD2-030 GEN
Solar/Wind Harmer
0.465
3141873WAN 176
Solar/Wind Harmer
2.067
316280AD1-041 GEN
Solar/Wind Harmer
1.266
3141766HARMONY
Solar/Wind Harmer
1.473
316203AE2-005 GEN
Solar/Wind Harmer
6.899
316382AG1-145 C
Solar/Wind Harmer
0.287
3150921YORKTN3
Adder
2.06
3144216WINCHST
Adder
0.298
3142946ENON
Solar/Wind Harmer
-0.003
970293AG2-193 GEN
Solar/Wind Harmer
0.938
3151221GRAVEL6
Adder
4.661
3151171GRAVELC
Adder
0.897
961611AG1-000B GEN
Solar/Wind Harmer
1.502
3145336SMITFLD
Solar/Wind Harmer
-0.003
315778AD1-151 GEN
Solar/Wind Harmer
6.042
970129AG2-093 GEN
Solar/Wind Harmer
3.885
970133AG2-095 GEN
Solar/Wind Harmer
0.764
3144536CHRHLND
Solar/Wind Harmer
-0.001
315773AC2-141 GEN
Solar/Wind Harmer
2.832
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.522
3143096IRON208
Adder
0.248
3143096IRON208
Adder
0.243
3142416OLDCHRC
Solar/Wind Harmer
0.67
944581AF1-123 GEN
Solar/Wind Harmer
30.141
944601AF1-125 GEN
Solar/Wind Harmer
29.67
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.797
316320Y1-086
Solar/Wind Harmer
0.377
316435W1029_GEN3
Solar/Wind Harmer
1.148
3141906WESTMOR
Solar/Wind Helper
0.56
3150341NORNECKC1
50/50
3.184
3150341NORNECKC1
50/50
3.158
963611AG1-210 GEN
50/50
1.019
316077AC2-138 C
Solar/Wind Harmer
0.679
958261AF2-120 GEN
Solar/Wind Harmer
10.805
316487AF1-042 GEN
Solar/Wind Harmer
3.356
316441AF1-014 GEN
Solar/Wind Harmer
1.103
316075AC2-137 C
Solar/Wind Harmer
0.233
3142946ENON
Solar/Wind Harmer
-0.001
316033AB2-134 GEN
Solar/Wind Harmer
2.264
315697AD1-025 GEN
Solar/Wind Harmer
1.42
316236AE1-162_GEN
Solar/Wind Harmer
0.211
316036AC1-147 C
Solar/Wind Harmer
0.18
3150991CHESPKB
Adder
0.624
3150991CHESPKB
Adder
0.609
316316AC1-027 C
Solar/Wind Harmer
0.204
3142956BIRDNECK
Solar/Wind Harmer
0.357
316185AD1-033 GEN
Solar/Wind Harmer
0.699
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316339AD2-160 GEN
Solar/Wind Harmer
0.443
316018AA1-139 ULT2
Solar/Wind Harmer
0.561
316017AA1-139 ULT1
Solar/Wind Harmer
0.53
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3150351NORNECKC2
50/50
3.031
966661AG1-536 GEN
50/50
7.059
3141843SHACKLE
50/50
0.789
3142433PROV 92
50/50
0.234
3142433PROV 92
50/50
0.234
316337AD2-073 GEN
Solar/Wind Harmer
1.056
964211AG1-282 GEN
Solar/Wind Harmer
0.906
3141726DUNNSVL
Solar/Wind Harmer
-0.12
962861AG1-135 GEN
Solar/Wind Harmer
10.218
961951AG1-038 GEN
Solar/Wind Harmer
3.356
3138133OCRAN
Solar/Wind Harmer
-0.012
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.923
3142433PROV 92
Solar/Wind Harmer
-0.051
971317AH1-138 GEN
Solar/Wind Harmer
1.289
316159AE1-175 C
Solar/Wind Harmer
0.255
3138126ROCKLANDING
Solar/Wind Harmer
0.028
944631AF1-128 GEN
Adder
32.715
3151171GRAVELC
Adder
0.682
961611AG1-000B GEN
Solar/Wind Harmer
3.52
971647AH1-324 GEN
Solar/Wind Harmer
3.538
3145336SMITFLD
Solar/Wind Harmer
-0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.104
316458AB2-190 GEN2
Solar/Wind Harmer
0.699
970129AG2-093 GEN
Solar/Wind Harmer
1.574
316072AD1-144
Solar/Wind Harmer
0.139
316294AC1-161 GEN
Solar/Wind Harmer
2.189
316375AC2-012 GEN
Solar/Wind Harmer
2.315
3150981CHESPKA
Adder
0.743
3143096IRON208
Adder
0.248
3142416OLDCHRC
Solar/Wind Harmer
-0.017
3142416OLDCHRC
Solar/Wind Harmer
-0.007
971445AH1-216 GEN
Solar/Wind Harmer
4.347
316369SG1_INVT
Solar/Wind Harmer
1.254
316132AB2-190 GEN1
Solar/Wind Harmer
0.699
3152611GOSPORTB
Adder
0.758
3152621GOSPORTC
Adder
0.643
3152601GOSPORTA
Adder
0.593
3151081ELIZAR1
Adder
5.452
3151091ELIZAR2
Adder
5.357
316312AB1-027
Solar/Wind Harmer
0.224
316305AF2-043 C
Solar/Wind Harmer
0.198
957871AF2-081 GEN
Solar/Wind Harmer
3.277
319010AE1-072 C
Solar/Wind Harmer
1.32
3146406KITTY HAWK
Solar/Wind Harmer
0.005
313526AB2-022
Solar/Wind Harmer
0.174
315835AF2-110_GEN
Solar/Wind Harmer
0.804
3146486SUNBURY
Solar/Wind Harmer
-0.006
3146486SUNBURY
Solar/Wind Harmer
-0.006
316321Z2-027
Solar/Wind Harmer
0.172
3146396TANGLEW
Solar/Wind Harmer
0.118
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
316311AC2-079 GEN
Solar/Wind Harmer
3.189
315833AF1-017_GEN
Solar/Wind Harmer
1.2
316349AD2-085 GEN
Solar/Wind Harmer
0.562
316223AC1-118
Solar/Wind Helper
2.133
3141426STAFORD
Solar/Wind Helper
0.031
3146456SLIGO L269
Solar/Wind Harmer
0.772
3130086AYDLETT
Solar/Wind Harmer
-0.026
3150691DARBY 3
Adder
4.148
3150701DARBY 4
Adder
4.138
3150681DARBY 2
Adder
4.133
3150671DARBY 1
Adder
4.128
3146386ELIZ CT
Solar/Wind Harmer
-0.006
316431W1029_GEN1
Solar/Wind Harmer
1.148
316433W1029_GEN2
Solar/Wind Harmer
1.148
944591AF1-124 GEN
Solar/Wind Harmer
30.249
316246AF1-032 C
Solar/Wind Harmer
0.133
316388AE2-253 GEN
Solar/Wind Harmer
0.443
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316093AE2-104_GEN
Solar/Wind Harmer
1.87
CPLELTFEXP_CPLE->PJM
CLTF
2.261
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.588
LAGNLTFEXP_LAGN->PJM
CLTF
1.622
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.914
TVALTFEXP_TVA->PJM
CLTF
0.817
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.078
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.804
MECLTFEXP_MEC->PJM
CLTF
0.791
SIGELTFEXP_SIGE->PJM
CLTF
0.024
NYPJM->LTFIMP_NY
CLTF
0.559
LGEELTFEXP_LGEE->PJM
CLTF
0.293
WECLTFEXP_WEC->PJM
CLTF
0.147

Details for 6SANDERS-6WESTMOR 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.11 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:646.44
MW Contribution:3.67
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
2.961
966661AG1-536 GEN
50/50
6.863
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
971353AH1-157 GEN
50/50
7.45
970017AG2-010 GEN
50/50
4.731
3150641CHESTS8
50/50
0.205
944631AF1-128 GEN
50/50
32.161
316337AD2-073 GEN
Solar/Wind Harmer
0.299
3141726DUNNSVL
Solar/Wind Harmer
1.046
962861AG1-135 GEN
Solar/Wind Harmer
7.538
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.364
3142433PROV 92
Solar/Wind Harmer
0.43
971317AH1-138 GEN
Solar/Wind Harmer
0.617
316159AE1-175 C
Solar/Wind Harmer
0.065
3138126ROCKLANDING
Solar/Wind Harmer
0.033
3142416OLDCHRC
Solar/Wind Harmer
0.15
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.605
961611AG1-000B GEN
Solar/Wind Harmer
2.971
971647AH1-324 GEN
Solar/Wind Harmer
2.411
971069AG2-661 GEN
Solar/Wind Harmer
1
315759AF1-018 GEN
50/50
4.962
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150611CHESTG7
50/50
0.404
3150631CHESTG8
50/50
0.397
971047AG2-646 GEN
50/50
11.304
972263AH1-716 GEN
50/50
33.141
3141813NORNECK
Solar/Wind Harmer
0.28
970327AG2-215 GEN
Solar/Wind Harmer
7.209
962981AG1-147 GEN
Solar/Wind Harmer
7.703
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
0.029
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.094
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
9.163
315976AC1-164 GENA
Solar/Wind Harmer
8.34
316169AC1-164_GENC
Solar/Wind Harmer
7.205
315975AC1-164 GENB
Solar/Wind Harmer
0.247
316312AB1-027
Solar/Wind Harmer
0.103
972265AH1-717 GEN
Adder
4.414
3151201GRAVEL4
Adder
4.138
3151191GRAVEL3
Adder
4.085
3151211GRAVEL5
Adder
4.085
316369SG1_INVT
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Helper
2.149
3141426STAFORD
Solar/Wind Helper
0.031
3150351NORNECKC2
50/50
3.011
970575AG2-366 GEN
50/50
3.668
315749AE2-041 GEN
50/50
4.962
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150921YORKTN3
50/50
1.942
3144216WINCHST
50/50
0.281
3151161SURRY 1
50/50
2.184
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.64
962971AG1-146 GEN
Solar/Wind Harmer
3.301
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.619
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.861
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.673
3142416OLDCHRC
Solar/Wind Harmer
0.559
3151221GRAVEL6
Adder
4.133
3151171GRAVELC
Adder
0.795
961611AG1-000B GEN
Solar/Wind Harmer
1.511
315778AD1-151 GEN
Solar/Wind Harmer
4.501
3141906WESTMOR
Solar/Wind Helper
0.564
3150341NORNECKC1
50/50
3.11
3150341NORNECKC1
50/50
3.085
963611AG1-210 GEN
50/50
0.995
3150621CHESTS7
50/50
0.185
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
7.978
316075AC2-137 C
Solar/Wind Harmer
0.02
3142946ENON
Solar/Wind Harmer
0.007
316033AB2-134 GEN
Solar/Wind Harmer
0.003
315697AD1-025 GEN
Solar/Wind Harmer
0.063
CPLELTFEXP_CPLE->PJM
CLTF
2.036
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.378
LAGNLTFEXP_LAGN->PJM
CLTF
1.555
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.497
TVALTFEXP_TVA->PJM
CLTF
0.786
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.234
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.714
MECLTFEXP_MEC->PJM
CLTF
0.792
SIGELTFEXP_SIGE->PJM
CLTF
0.024
NYPJM->LTFIMP_NY
CLTF
0.541
LGEELTFEXP_LGEE->PJM
CLTF
0.299
WECLTFEXP_WEC->PJM
CLTF
0.151

Details for 6SANDERS-6WESTMOR 230.0 kV Ckt 1 line l/o DVP_P4-2: 574T575_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 574T575_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.3 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:729.05
MW Contribution:3.69
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
3.021
970575AG2-366 GEN
50/50
3.695
315749AE2-041 GEN
50/50
5.033
3141843SHACKLE
50/50
0.76
316404AE1-155 C
Solar/Wind Harmer
5.256
316484AD2-074 GEN
Solar/Wind Harmer
6.253
970009AG2-005 GEN
Solar/Wind Harmer
3.105
962971AG1-146 GEN
Solar/Wind Harmer
4.379
316156AD2-030 GEN
Solar/Wind Harmer
0.448
3141873WAN 176
Solar/Wind Harmer
1.99
316280AD1-041 GEN
Solar/Wind Harmer
1.219
3141766HARMONY
Solar/Wind Harmer
1.416
316203AE2-005 GEN
Solar/Wind Harmer
6.641
3142433PROV 92
Adder
0.213
3142433PROV 92
Adder
0.213
316382AG1-145 C
Solar/Wind Harmer
0.265
3150921YORKTN3
Adder
1.901
3144216WINCHST
Adder
0.276
3142946ENON
Solar/Wind Harmer
-0.003
970293AG2-193 GEN
Solar/Wind Harmer
0.917
3151221GRAVEL6
Adder
4.354
3151171GRAVELC
Adder
0.838
961611AG1-000B GEN
Solar/Wind Harmer
1.411
3142416OLDCHRC
Solar/Wind Harmer
0.676
315778AD1-151 GEN
Solar/Wind Harmer
5.758
970129AG2-093 GEN
Solar/Wind Harmer
3.728
3143096IRON208
Adder
0.246
3143096IRON208
Adder
0.241
970133AG2-095 GEN
Solar/Wind Harmer
0.741
3145336SMITFLD
Solar/Wind Harmer
-0.003
3141906WESTMOR
Solar/Wind Helper
0.564
315759AF1-018 GEN
50/50
5.033
3141813NORNECK
Solar/Wind Harmer
-0.031
962981AG1-147 GEN
Solar/Wind Harmer
10.217
3141783LANCAST
Solar/Wind Harmer
-0.012
3141783LANCAST
Solar/Wind Harmer
-0.008
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.019
957601AF2-054 GEN
Solar/Wind Harmer
0.502
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
1.95
315666AE1-190 GEN
Solar/Wind Harmer
0.488
316059AD1-063 C
Solar/Wind Harmer
0.36
316314AB2-024 C
Solar/Wind Harmer
1.314
3143873LANEXA
Solar/Wind Harmer
-0.008
957831AF2-077 GEN
Solar/Wind Harmer
0.374
3138283WHITEMARSH
Solar/Wind Harmer
0.019
3142433PROV 92
Adder
0.213
3142433PROV 92
Adder
0.213
971167AH1-042 GEN
Solar/Wind Harmer
11.401
315976AC1-164 GENA
Solar/Wind Harmer
9.817
316169AC1-164_GENC
Solar/Wind Harmer
8.481
315975AC1-164 GENB
Solar/Wind Harmer
0.29
972265AH1-717 GEN
Adder
4.65
3151201GRAVEL4
Adder
4.359
3151191GRAVEL3
Adder
4.304
3151211GRAVEL5
Adder
4.304
316312AB1-027
Solar/Wind Harmer
0.226
316369SG1_INVT
Solar/Wind Harmer
1.19
316132AB2-190 GEN1
Solar/Wind Harmer
0.67
971445AH1-216 GEN
Solar/Wind Harmer
4.032
316223AC1-118
Solar/Wind Helper
2.149
3141426STAFORD
Solar/Wind Helper
0.032
3150341NORNECKC1
50/50
3.121
3150341NORNECKC1
50/50
3.096
963611AG1-210 GEN
50/50
0.999
316077AC2-138 C
Solar/Wind Harmer
0.666
958261AF2-120 GEN
Solar/Wind Harmer
10.558
316487AF1-042 GEN
Solar/Wind Harmer
3.272
316441AF1-014 GEN
Solar/Wind Harmer
1.062
316075AC2-137 C
Solar/Wind Harmer
0.222
3142946ENON
Solar/Wind Harmer
-0.001
316033AB2-134 GEN
Solar/Wind Harmer
2.149
315697AD1-025 GEN
Solar/Wind Harmer
1.348
3150691DARBY 3
Adder
4.168
3150701DARBY 4
Adder
4.158
3150681DARBY 2
Adder
4.153
3150671DARBY 1
Adder
4.148
316236AE1-162_GEN
Solar/Wind Harmer
0.196
3150351NORNECKC2
50/50
2.971
966661AG1-536 GEN
50/50
6.898
3141843SHACKLE
50/50
0.76
316337AD2-073 GEN
Solar/Wind Harmer
1.039
964211AG1-282 GEN
Solar/Wind Harmer
0.887
3141726DUNNSVL
Solar/Wind Harmer
-0.117
962861AG1-135 GEN
Solar/Wind Harmer
9.979
961951AG1-038 GEN
Solar/Wind Harmer
3.272
3138133OCRAN
Solar/Wind Harmer
-0.012
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.851
3142433PROV 92
Solar/Wind Harmer
-0.049
3142433PROV 92
Adder
0.213
3142433PROV 92
Adder
0.213
971317AH1-138 GEN
Solar/Wind Harmer
1.198
316159AE1-175 C
Solar/Wind Harmer
0.236
3138126ROCKLANDING
Solar/Wind Harmer
0.025
944631AF1-128 GEN
Adder
31.515
3151171GRAVELC
Adder
0.637
961611AG1-000B GEN
Solar/Wind Harmer
3.308
3142416OLDCHRC
Solar/Wind Harmer
-0.017
3142416OLDCHRC
Solar/Wind Harmer
-0.007
971647AH1-324 GEN
Solar/Wind Harmer
3.341
971069AG2-661 GEN
Solar/Wind Harmer
1.052
316458AB2-190 GEN2
Solar/Wind Harmer
0.67
970129AG2-093 GEN
Solar/Wind Harmer
1.51
3143096IRON208
Adder
0.246
3145336SMITFLD
Solar/Wind Harmer
-0.026
316072AD1-144
Solar/Wind Harmer
0.128
CPLELTFEXP_CPLE->PJM
CLTF
2.235
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.209
LAGNLTFEXP_LAGN->PJM
CLTF
1.71
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.94
TVALTFEXP_TVA->PJM
CLTF
0.863
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.758
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.982
MECLTFEXP_MEC->PJM
CLTF
0.871
SIGELTFEXP_SIGE->PJM
CLTF
0.027
NYPJM->LTFIMP_NY
CLTF
0.602
LGEELTFEXP_LGEE->PJM
CLTF
0.329
WECLTFEXP_WEC->PJM
CLTF
0.166

Details for 6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.58 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:786.97
MW Contribution:3.79
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
5.235
3142433PROV 92
50/50
0.234
3142433PROV 92
50/50
0.234
316223AC1-118
Solar/Wind Harmer
1.265
3141813NORNECK
Solar/Wind Harmer
-0.032
962981AG1-147 GEN
Solar/Wind Harmer
10.492
3141783LANCAST
Solar/Wind Harmer
-0.013
3141783LANCAST
Solar/Wind Harmer
-0.008
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.02
957601AF2-054 GEN
Solar/Wind Harmer
0.521
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
2.024
315666AE1-190 GEN
Solar/Wind Harmer
0.506
316059AD1-063 C
Solar/Wind Harmer
0.374
316314AB2-024 C
Solar/Wind Harmer
1.369
3143873LANEXA
Solar/Wind Harmer
-0.009
957831AF2-077 GEN
Solar/Wind Harmer
0.394
3138283WHITEMARSH
Solar/Wind Harmer
0.02
971167AH1-042 GEN
Solar/Wind Harmer
11.777
315976AC1-164 GENA
Solar/Wind Harmer
10.494
316169AC1-164_GENC
Solar/Wind Harmer
9.066
315975AC1-164 GENB
Solar/Wind Harmer
0.31
972265AH1-717 GEN
Adder
4.971
3151201GRAVEL4
Adder
4.66
3151191GRAVEL3
Adder
4.601
3151211GRAVEL5
Adder
4.601
971445AH1-216 GEN
Solar/Wind Harmer
4.341
316369SG1_INVT
Solar/Wind Harmer
1.252
316132AB2-190 GEN1
Solar/Wind Harmer
0.698
3152611GOSPORTB
Adder
0.757
3152621GOSPORTC
Adder
0.642
3152601GOSPORTA
Adder
0.592
3151081ELIZAR1
Adder
5.443
3151091ELIZAR2
Adder
5.349
316312AB1-027
Solar/Wind Harmer
0.224
316305AF2-043 C
Solar/Wind Harmer
0.198
957871AF2-081 GEN
Solar/Wind Harmer
3.272
319010AE1-072 C
Solar/Wind Harmer
1.318
3146406KITTY HAWK
Solar/Wind Harmer
0.005
313526AB2-022
Solar/Wind Harmer
0.173
315835AF2-110_GEN
Solar/Wind Harmer
0.803
3146486SUNBURY
Solar/Wind Harmer
-0.006
3146486SUNBURY
Solar/Wind Harmer
-0.006
316321Z2-027
Solar/Wind Harmer
0.172
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.117
3141426STAFORD
Solar/Wind Helper
0.031
3150351NORNECKC2
50/50
3.081
970575AG2-366 GEN
50/50
3.795
315749AE2-041 GEN
50/50
5.235
3141843SHACKLE
50/50
0.789
3142433PROV 92
50/50
0.234
3142433PROV 92
50/50
0.234
3141906WESTMOR
Solar/Wind Harmer
-0.019
316404AE1-155 C
Solar/Wind Harmer
5.377
316484AD2-074 GEN
Solar/Wind Harmer
6.411
970009AG2-005 GEN
Solar/Wind Harmer
3.184
962971AG1-146 GEN
Solar/Wind Harmer
4.497
316156AD2-030 GEN
Solar/Wind Harmer
0.465
3141873WAN 176
Solar/Wind Harmer
2.065
316280AD1-041 GEN
Solar/Wind Harmer
1.265
3141766HARMONY
Solar/Wind Harmer
1.472
316203AE2-005 GEN
Solar/Wind Harmer
6.895
316382AG1-145 C
Solar/Wind Harmer
0.286
3150921YORKTN3
Adder
2.058
3144216WINCHST
Adder
0.298
3142946ENON
Solar/Wind Harmer
-0.003
970293AG2-193 GEN
Solar/Wind Harmer
0.937
3151221GRAVEL6
Adder
4.655
3151171GRAVELC
Adder
0.896
961611AG1-000B GEN
Solar/Wind Harmer
1.5
3145336SMITFLD
Solar/Wind Harmer
-0.003
315778AD1-151 GEN
Solar/Wind Harmer
6.033
970129AG2-093 GEN
Solar/Wind Harmer
3.879
970133AG2-095 GEN
Solar/Wind Harmer
0.763
3144536CHRHLND
Solar/Wind Harmer
-0.001
315773AC2-141 GEN
Solar/Wind Harmer
2.827
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.513
3143096IRON208
Adder
0.248
3143096IRON208
Adder
0.243
3142416OLDCHRC
Solar/Wind Harmer
0.669
944581AF1-123 GEN
Solar/Wind Harmer
30.093
944601AF1-125 GEN
Solar/Wind Harmer
29.624
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.795
316320Y1-086
Solar/Wind Harmer
0.376
316435W1029_GEN3
Solar/Wind Harmer
1.147
3150351NORNECKC2
50/50
3.03
966661AG1-536 GEN
50/50
7.057
3141843SHACKLE
50/50
0.789
3142433PROV 92
50/50
0.234
3142433PROV 92
50/50
0.234
316337AD2-073 GEN
Solar/Wind Harmer
1.055
964211AG1-282 GEN
Solar/Wind Harmer
0.906
3141726DUNNSVL
Solar/Wind Harmer
-0.12
962861AG1-135 GEN
Solar/Wind Harmer
10.214
961951AG1-038 GEN
Solar/Wind Harmer
3.355
3138133OCRAN
Solar/Wind Harmer
-0.012
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.921
3142433PROV 92
Solar/Wind Harmer
-0.051
971317AH1-138 GEN
Solar/Wind Harmer
1.288
316159AE1-175 C
Solar/Wind Harmer
0.255
3138126ROCKLANDING
Solar/Wind Harmer
0.028
944631AF1-128 GEN
Adder
32.671
3151171GRAVELC
Adder
0.681
961611AG1-000B GEN
Solar/Wind Harmer
3.515
971647AH1-324 GEN
Solar/Wind Harmer
3.532
3145336SMITFLD
Solar/Wind Harmer
-0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.102
316458AB2-190 GEN2
Solar/Wind Harmer
0.698
970129AG2-093 GEN
Solar/Wind Harmer
1.571
316072AD1-144
Solar/Wind Harmer
0.139
316294AC1-161 GEN
Solar/Wind Harmer
2.186
316375AC2-012 GEN
Solar/Wind Harmer
2.311
3150981CHESPKA
Adder
0.742
3143096IRON208
Adder
0.248
3142416OLDCHRC
Solar/Wind Harmer
-0.017
3142416OLDCHRC
Solar/Wind Harmer
-0.007
944591AF1-124 GEN
Solar/Wind Harmer
30.202
316246AF1-032 C
Solar/Wind Harmer
0.133
316388AE2-253 GEN
Solar/Wind Harmer
0.442
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316093AE2-104_GEN
Solar/Wind Harmer
1.867
3150341NORNECKC1
50/50
3.183
3150341NORNECKC1
50/50
3.157
963611AG1-210 GEN
50/50
1.018
316077AC2-138 C
Solar/Wind Harmer
0.679
958261AF2-120 GEN
Solar/Wind Harmer
10.801
316487AF1-042 GEN
Solar/Wind Harmer
3.355
316441AF1-014 GEN
Solar/Wind Harmer
1.102
316075AC2-137 C
Solar/Wind Harmer
0.232
3142946ENON
Solar/Wind Harmer
-0.001
316033AB2-134 GEN
Solar/Wind Harmer
2.26
315697AD1-025 GEN
Solar/Wind Harmer
1.418
316236AE1-162_GEN
Solar/Wind Harmer
0.211
316036AC1-147 C
Solar/Wind Harmer
0.18
3150991CHESPKB
Adder
0.623
3150991CHESPKB
Adder
0.608
316316AC1-027 C
Solar/Wind Harmer
0.204
3142956BIRDNECK
Solar/Wind Harmer
0.356
316185AD1-033 GEN
Solar/Wind Harmer
0.698
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316339AD2-160 GEN
Solar/Wind Harmer
0.442
316018AA1-139 ULT2
Solar/Wind Harmer
0.561
316017AA1-139 ULT1
Solar/Wind Harmer
0.53
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.771
3130086AYDLETT
Solar/Wind Harmer
-0.026
3150691DARBY 3
Adder
4.141
3150701DARBY 4
Adder
4.131
3150681DARBY 2
Adder
4.127
3150671DARBY 1
Adder
4.122
3146386ELIZ CT
Solar/Wind Harmer
-0.006
316431W1029_GEN1
Solar/Wind Harmer
1.147
316433W1029_GEN2
Solar/Wind Harmer
1.147
CPLELTFEXP_CPLE->PJM
CLTF
2.253
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.492
LAGNLTFEXP_LAGN->PJM
CLTF
1.608
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.892
TVALTFEXP_TVA->PJM
CLTF
0.81
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.974
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.777
MECLTFEXP_MEC->PJM
CLTF
0.779
SIGELTFEXP_SIGE->PJM
CLTF
0.024
NYPJM->LTFIMP_NY
CLTF
0.564
LGEELTFEXP_LGEE->PJM
CLTF
0.288
WECLTFEXP_WEC->PJM
CLTF
0.144

Details for 6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.62 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:637.96
MW Contribution:3.67
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
2.96
966661AG1-536 GEN
50/50
6.86
3141843SHACKLE
50/50
0.748
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
971353AH1-157 GEN
50/50
7.442
970017AG2-010 GEN
50/50
4.725
3150641CHESTS8
50/50
0.204
944631AF1-128 GEN
50/50
32.114
316337AD2-073 GEN
Solar/Wind Harmer
0.299
3141726DUNNSVL
Solar/Wind Harmer
1.045
962861AG1-135 GEN
Solar/Wind Harmer
7.535
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.364
3142433PROV 92
Solar/Wind Harmer
0.43
971317AH1-138 GEN
Solar/Wind Harmer
0.616
316159AE1-175 C
Solar/Wind Harmer
0.065
3138126ROCKLANDING
Solar/Wind Harmer
0.033
3142416OLDCHRC
Solar/Wind Harmer
0.15
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.604
961611AG1-000B GEN
Solar/Wind Harmer
2.967
971647AH1-324 GEN
Solar/Wind Harmer
2.407
3150351NORNECKC2
50/50
3.01
970575AG2-366 GEN
50/50
3.666
315749AE2-041 GEN
50/50
4.959
3141843SHACKLE
50/50
0.748
3142433PROV 92
50/50
0.222
3150341NORNECKC1
50/50
3.109
3150341NORNECKC1
50/50
3.084
963611AG1-210 GEN
50/50
0.995
3150621CHESTS7
50/50
0.185
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
7.975
316075AC2-137 C
Solar/Wind Harmer
0.02
3142946ENON
Solar/Wind Harmer
0.007
316033AB2-134 GEN
Solar/Wind Harmer
0.003
315697AD1-025 GEN
Solar/Wind Harmer
0.063
315759AF1-018 GEN
50/50
4.959
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150611CHESTG7
50/50
0.403
3150631CHESTG8
50/50
0.397
971047AG2-646 GEN
50/50
11.288
972263AH1-716 GEN
50/50
33.088
316223AC1-118
Solar/Wind Harmer
0.296
3141813NORNECK
Solar/Wind Harmer
0.28
970327AG2-215 GEN
Solar/Wind Harmer
7.206
962981AG1-147 GEN
Solar/Wind Harmer
7.699
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
0.029
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.092
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
9.155
315976AC1-164 GENA
Solar/Wind Harmer
8.33
316169AC1-164_GENC
Solar/Wind Harmer
7.197
315975AC1-164 GENB
Solar/Wind Harmer
0.246
316312AB1-027
Solar/Wind Harmer
0.103
972265AH1-717 GEN
Adder
4.406
3151201GRAVEL4
Adder
4.131
3151191GRAVEL3
Adder
4.078
3151211GRAVEL5
Adder
4.078
316369SG1_INVT
Solar/Wind Harmer
0.002
3141426STAFORD
Solar/Wind Helper
0.031
3142433PROV 92
50/50
0.222
3150921YORKTN3
50/50
1.939
3144216WINCHST
50/50
0.281
3151161SURRY 1
50/50
2.18
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.64
962971AG1-146 GEN
Solar/Wind Harmer
3.3
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.617
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.86
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.672
3142416OLDCHRC
Solar/Wind Harmer
0.558
3151221GRAVEL6
Adder
4.126
3151171GRAVELC
Adder
0.794
961611AG1-000B GEN
Solar/Wind Harmer
1.508
CPLELTFEXP_CPLE->PJM
CLTF
2.028
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.282
LAGNLTFEXP_LAGN->PJM
CLTF
1.541
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.475
TVALTFEXP_TVA->PJM
CLTF
0.778
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.13
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.686
MECLTFEXP_MEC->PJM
CLTF
0.78
SIGELTFEXP_SIGE->PJM
CLTF
0.024
NYPJM->LTFIMP_NY
CLTF
0.546
LGEELTFEXP_LGEE->PJM
CLTF
0.294
WECLTFEXP_WEC->PJM
CLTF
0.148

Details for 6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line l/o DVP_P4-2: 574T575_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 574T575_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.93 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:726.47
MW Contribution:3.69
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
5.03
316223AC1-118
Solar/Wind Harmer
1.248
3141813NORNECK
Solar/Wind Harmer
-0.031
962981AG1-147 GEN
Solar/Wind Harmer
10.212
3141783LANCAST
Solar/Wind Harmer
-0.012
3141783LANCAST
Solar/Wind Harmer
-0.008
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.019
957601AF2-054 GEN
Solar/Wind Harmer
0.501
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
1.949
315666AE1-190 GEN
Solar/Wind Harmer
0.487
316059AD1-063 C
Solar/Wind Harmer
0.359
316314AB2-024 C
Solar/Wind Harmer
1.313
3143873LANEXA
Solar/Wind Harmer
-0.008
3150351NORNECKC2
50/50
3.02
970575AG2-366 GEN
50/50
3.693
315749AE2-041 GEN
50/50
5.03
3141843SHACKLE
50/50
0.759
3141906WESTMOR
Solar/Wind Harmer
-0.018
316404AE1-155 C
Solar/Wind Harmer
5.254
316484AD2-074 GEN
Solar/Wind Harmer
6.251
970009AG2-005 GEN
Solar/Wind Harmer
3.104
962971AG1-146 GEN
Solar/Wind Harmer
4.377
316156AD2-030 GEN
Solar/Wind Harmer
0.448
3141873WAN 176
Solar/Wind Harmer
1.989
316280AD1-041 GEN
Solar/Wind Harmer
1.218
3141766HARMONY
Solar/Wind Harmer
1.415
316203AE2-005 GEN
Solar/Wind Harmer
6.637
3150351NORNECKC2
50/50
2.97
966661AG1-536 GEN
50/50
6.895
3141843SHACKLE
50/50
0.759
316337AD2-073 GEN
Solar/Wind Harmer
1.038
964211AG1-282 GEN
Solar/Wind Harmer
0.887
3141726DUNNSVL
Solar/Wind Harmer
-0.117
962861AG1-135 GEN
Solar/Wind Harmer
9.975
961951AG1-038 GEN
Solar/Wind Harmer
3.271
3138133OCRAN
Solar/Wind Harmer
-0.012
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.849
3142433PROV 92
Solar/Wind Harmer
-0.049
3142433PROV 92
Adder
0.213
3142433PROV 92
Adder
0.213
971317AH1-138 GEN
Solar/Wind Harmer
1.197
316159AE1-175 C
Solar/Wind Harmer
0.236
3138126ROCKLANDING
Solar/Wind Harmer
0.025
944631AF1-128 GEN
Adder
31.471
3151171GRAVELC
Adder
0.636
961611AG1-000B GEN
Solar/Wind Harmer
3.303
3142416OLDCHRC
Solar/Wind Harmer
-0.017
3142416OLDCHRC
Solar/Wind Harmer
-0.007
971647AH1-324 GEN
Solar/Wind Harmer
3.336
971069AG2-661 GEN
Solar/Wind Harmer
1.05
316458AB2-190 GEN2
Solar/Wind Harmer
0.669
970129AG2-093 GEN
Solar/Wind Harmer
1.508
3143096IRON208
Adder
0.245
3145336SMITFLD
Solar/Wind Harmer
-0.026
316072AD1-144
Solar/Wind Harmer
0.128
957831AF2-077 GEN
Solar/Wind Harmer
0.374
3138283WHITEMARSH
Solar/Wind Harmer
0.019
3142433PROV 92
Adder
0.213
3142433PROV 92
Adder
0.213
971167AH1-042 GEN
Solar/Wind Harmer
11.391
315976AC1-164 GENA
Solar/Wind Harmer
9.806
316169AC1-164_GENC
Solar/Wind Harmer
8.472
315975AC1-164 GENB
Solar/Wind Harmer
0.29
972265AH1-717 GEN
Adder
4.643
3151201GRAVEL4
Adder
4.352
3151191GRAVEL3
Adder
4.297
3151211GRAVEL5
Adder
4.297
316312AB1-027
Solar/Wind Harmer
0.226
316369SG1_INVT
Solar/Wind Harmer
1.189
316132AB2-190 GEN1
Solar/Wind Harmer
0.669
971445AH1-216 GEN
Solar/Wind Harmer
4.026
3141426STAFORD
Solar/Wind Helper
0.032
3142433PROV 92
Adder
0.213
3142433PROV 92
Adder
0.213
316382AG1-145 C
Solar/Wind Harmer
0.265
3150921YORKTN3
Adder
1.899
3144216WINCHST
Adder
0.275
3142946ENON
Solar/Wind Harmer
-0.003
970293AG2-193 GEN
Solar/Wind Harmer
0.916
3151221GRAVEL6
Adder
4.347
3151171GRAVELC
Adder
0.836
961611AG1-000B GEN
Solar/Wind Harmer
1.409
3142416OLDCHRC
Solar/Wind Harmer
0.675
315778AD1-151 GEN
Solar/Wind Harmer
5.749
970129AG2-093 GEN
Solar/Wind Harmer
3.722
3143096IRON208
Adder
0.245
3143096IRON208
Adder
0.24
970133AG2-095 GEN
Solar/Wind Harmer
0.739
3145336SMITFLD
Solar/Wind Harmer
-0.003
3150341NORNECKC1
50/50
3.12
3150341NORNECKC1
50/50
3.095
963611AG1-210 GEN
50/50
0.998
316077AC2-138 C
Solar/Wind Harmer
0.665
958261AF2-120 GEN
Solar/Wind Harmer
10.554
316487AF1-042 GEN
Solar/Wind Harmer
3.271
316441AF1-014 GEN
Solar/Wind Harmer
1.061
316075AC2-137 C
Solar/Wind Harmer
0.222
3142946ENON
Solar/Wind Harmer
-0.001
316033AB2-134 GEN
Solar/Wind Harmer
2.145
315697AD1-025 GEN
Solar/Wind Harmer
1.346
3150691DARBY 3
Adder
4.161
3150701DARBY 4
Adder
4.151
3150681DARBY 2
Adder
4.146
3150671DARBY 1
Adder
4.142
316236AE1-162_GEN
Solar/Wind Harmer
0.195
CPLELTFEXP_CPLE->PJM
CLTF
2.227
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.114
LAGNLTFEXP_LAGN->PJM
CLTF
1.695
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.918
TVALTFEXP_TVA->PJM
CLTF
0.856
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.654
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.955
MECLTFEXP_MEC->PJM
CLTF
0.859
SIGELTFEXP_SIGE->PJM
CLTF
0.026
NYPJM->LTFIMP_NY
CLTF
0.606
LGEELTFEXP_LGEE->PJM
CLTF
0.324
WECLTFEXP_WEC->PJM
CLTF
0.163

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2083_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2083_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.74 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:2777.55
MW Contribution:5.66
Bus #Bus NameTypeMW Contribution
3150921YORKTN3
50/50
8.877
3144216WINCHST
50/50
1.304
3141316ARNOLDS
50/50
0.802
3150331BIRCHWDA
50/50
57.314
3150351NORNECKC2
50/50
3.428
315749AE2-041 GEN
50/50
11.323
970575AG2-366 GEN
50/50
5.655
3141843SHACKLE
50/50
1.681
3151101ELIZAR3
50/50
29.482
3151161SURRY 1
50/50
10.584
316382AG1-145 C
Solar/Wind Harmer
0.003
315773AC2-141 GEN
Solar/Wind Harmer
12.005
3141906WESTMOR
Solar/Wind Harmer
0.128
970737AG2-469 GEN
Solar/Wind Harmer
13.605
3141766HARMONY
Solar/Wind Harmer
4.246
316404AE1-155 C
Solar/Wind Harmer
0.072
970009AG2-005 GEN
Solar/Wind Harmer
2.376
962971AG1-146 GEN
Solar/Wind Harmer
5.09
316156AD2-030 GEN
Solar/Wind Harmer
0.235
3141873WAN 176
Solar/Wind Harmer
5.646
316280AD1-041 GEN
Solar/Wind Harmer
0.006
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
68.347
944601AF1-125 GEN
Solar/Wind Harmer
67.294
3144873MCLAUGH
Solar/Wind Harmer
0.007
3144536CHRHLND
Solar/Wind Harmer
0.044
3146456SLIGO L269
Solar/Wind Harmer
0.293
971153AH1-033 GEN
Solar/Wind Harmer
3.387
316320Y1-086
Solar/Wind Harmer
0.002
3145336SMITFLD
Solar/Wind Harmer
0.114
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.278
3151221GRAVEL6
Adder
20.031
3151171GRAVELC
Adder
3.854
3146626S HERTFORD
Solar/Wind Harmer
0.274
3142433PROV 92
Adder
0.518
3142433PROV 92
Adder
0.518
961611AG1-000B GEN
Solar/Wind Harmer
7.052
3146376EDENTON
Solar/Wind Harmer
0.262
3145273HOLLAND
Solar/Wind Harmer
0.195
3142946ENON
Solar/Wind Harmer
0.085
315614AA2-178 GEN
Solar/Wind Harmer
1.427
315778AD1-151 GEN
Solar/Wind Harmer
19.197
971157AH1-035 GEN
Solar/Wind Harmer
2.878
315737AD1-076 GEN
Solar/Wind Harmer
3.062
970661AG2-428 GEN
Solar/Wind Harmer
5.016
3146206CASHIE
Solar/Wind Harmer
0.231
316083AB2-161 GEN
Solar/Wind Harmer
0.003
970129AG2-093 GEN
Solar/Wind Harmer
13.798
970659AG2-427 GEN
Solar/Wind Harmer
2.387
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
3156021HOLLOMANSOL
Solar/Wind Harmer
1.005
3145893MURPHYS
Solar/Wind Harmer
0.369
3145893MURPHYS
Solar/Wind Harmer
0.22
957521AF2-046 GEN
Solar/Wind Harmer
16.35
961681AG1-008 GEN
Solar/Wind Harmer
16.35
3146173TUNIS
Solar/Wind Harmer
0.218
3145963POPLR C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.186
316140AB2-099
Solar/Wind Harmer
0.077
962331AG1-082 GEN
Solar/Wind Harmer
2.31
970133AG2-095 GEN
Solar/Wind Harmer
2.034
315813AE1-149 C
Solar/Wind Harmer
11.196
3146263WOODLND
Solar/Wind Harmer
0.208
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.206
970293AG2-193 GEN
Solar/Wind Harmer
2.137
3145933PARMELE
Solar/Wind Harmer
0.198
966801AG1-551 GEN
Solar/Wind Harmer
2.311
3142666NORTHAMPTON
Solar/Wind Harmer
0.194
3145746EVERETS
Solar/Wind Harmer
0.19
3145746EVERETS
Solar/Wind Harmer
0.19
316365GEN2_N
Solar/Wind Harmer
0.426
316210AC1-098 GEN
Solar/Wind Harmer
1.749
3145796HORNRTN
Solar/Wind Harmer
0.746
3145796HORNRTN
Solar/Wind Harmer
0.187
313506AB2-031 GEN
Solar/Wind Harmer
0.575
970917AG2-570 GEN
Solar/Wind Harmer
16.255
965281AG1-393 GEN
Solar/Wind Harmer
1.933
316327AA2-057 GEN
Solar/Wind Harmer
0.266
3143096IRON208
Adder
0.738
3143096IRON208
Adder
0.723
315724AD1-057 GEN
Solar/Wind Harmer
0.658
3146073TAR RVR
Solar/Wind Harmer
0.175
3146083TARBORO
Solar/Wind Harmer
0.175
315839AE2-212 C
Solar/Wind Harmer
0.001
3146233WITAKRS
Solar/Wind Harmer
0.86
3146233WITAKRS
Solar/Wind Harmer
0.117
3138543CONSLDL
Solar/Wind Harmer
0.113
3147043LAWRENC
Solar/Wind Harmer
0.102
961601AG1-000A GEN
Solar/Wind Harmer
11.84
3145543BTLEBRO
Solar/Wind Harmer
0.166
3145543BTLEBRO
Solar/Wind Harmer
0.166
971623AH1-311 GEN
Solar/Wind Harmer
0.333
316478AD1-087 GEN
Solar/Wind Harmer
0.55
316486AD2-202 GEN
Solar/Wind Harmer
0.162
3142416OLDCHRC
Solar/Wind Harmer
1.409
316131AB2-060 GEN
Solar/Wind Harmer
0.445
964241AG1-285 GEN
Solar/Wind Harmer
9.23
315785AD2-033 C
Solar/Wind Harmer
1.084
970257AG2-171 GEN
Solar/Wind Harmer
4.203
959311AF2-222 GEN
Solar/Wind Harmer
11.552
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.512
3150861SPRUNCD
Adder
0.584
970909AG2-566 GEN
Solar/Wind Harmer
1.319
963181AG1-167 GEN
Solar/Wind Harmer
0.487
3144293JTRSVLE
Adder
0.388
316283AC2-100 C
Solar/Wind Harmer
0.234
3152331SURRY 2
50/50
15.432
971353AH1-157 GEN
50/50
29.999
970017AG2-010 GEN
50/50
22.046
3150351NORNECKC2
50/50
3.371
966661AG1-536 GEN
50/50
9.057
3141843SHACKLE
50/50
1.681
971317AH1-138 GEN
Solar/Wind Harmer
2.523
316159AE1-175 C
Solar/Wind Harmer
0.288
316294AC1-161 GEN
Solar/Wind Harmer
5.695
3138126ROCKLANDING
Solar/Wind Harmer
0.151
3141726DUNNSVL
Solar/Wind Harmer
1.275
316337AD2-073 GEN
Solar/Wind Harmer
0.278
972135AH1-637 GEN
Solar/Wind Harmer
2.721
3141766HARMONY
Solar/Wind Harmer
0.064
962861AG1-135 GEN
Solar/Wind Harmer
10.187
3138133OCRAN
Solar/Wind Harmer
0.191
971777AH1-397 GEN
Solar/Wind Harmer
0.818
944591AF1-124 GEN
Solar/Wind Harmer
68.589
316375AC2-012 GEN
Solar/Wind Harmer
0.008
3150981CHESPKA
Adder
3.726
316388AE2-253 GEN
Solar/Wind Harmer
0.924
3146456SLIGO L269
Solar/Wind Harmer
0.293
316072AD1-144
Solar/Wind Harmer
0.105
316246AF1-032 C
Solar/Wind Harmer
0.13
3145336SMITFLD
Solar/Wind Harmer
1.138
3146516WINFALL
Solar/Wind Harmer
0.899
3146516WINFALL
Solar/Wind Harmer
0.278
316093AE2-104_GEN
Solar/Wind Harmer
4.652
3151171GRAVELC
Adder
2.931
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3142433PROV 92
Solar/Wind Harmer
1.065
3142433PROV 92
Adder
0.518
3142433PROV 92
Adder
0.518
961611AG1-000B GEN
Solar/Wind Harmer
13.868
3130156CHOWAN
Solar/Wind Harmer
0.262
971647AH1-324 GEN
Solar/Wind Harmer
10.906
3145663CRESWEL
Solar/Wind Harmer
0.698
971163AH1-040 GEN
Solar/Wind Harmer
19.948
939411AE1-173 GEN
Solar/Wind Harmer
105.555
971069AG2-661 GEN
Solar/Wind Harmer
4.266
970661AG2-428 GEN
Solar/Wind Harmer
23.585
3146206CASHIE
Solar/Wind Harmer
0.231
971547AH1-271 GEN
Solar/Wind Harmer
4.932
940641AE2-051 GEN
Solar/Wind Harmer
18.399
316458AB2-190 GEN2
Solar/Wind Harmer
1.234
944631AF1-128 GEN
Adder
109.323
316381AD1-082 GEN
Solar/Wind Harmer
0.238
970129AG2-093 GEN
Solar/Wind Harmer
6.493
970659AG2-427 GEN
Solar/Wind Harmer
10.912
972263AH1-716 GEN
50/50
212.665
315759AF1-018 GEN
50/50
11.323
3138283WHITEMARSH
Solar/Wind Harmer
0.076
316314AB2-024 C
Solar/Wind Harmer
0.001
316223AC1-118
Solar/Wind Harmer
0.229
944491AF1-114 GEN
Solar/Wind Harmer
0.001
3141813NORNECK
Solar/Wind Harmer
0.318
316059AD1-063 C
Solar/Wind Harmer
0.002
970327AG2-215 GEN
Solar/Wind Harmer
10.443
962981AG1-147 GEN
Solar/Wind Harmer
11.876
315976AC1-164 GENA
Solar/Wind Harmer
32.958
316169AC1-164_GENC
Solar/Wind Harmer
28.472
315975AC1-164 GENB
Solar/Wind Harmer
0.975
3141783LANCAST
Solar/Wind Harmer
0.191
3141783LANCAST
Solar/Wind Harmer
0.127
3138133OCRAN
Solar/Wind Harmer
0.095
3141913WHIT STONE
Solar/Wind Harmer
0.317
3141873WAN 176
Solar/Wind Harmer
0.064
315662AE1-191 GEN
Solar/Wind Harmer
0.01
315666AE1-190 GEN
Solar/Wind Harmer
0.003
970189AG2-124 GEN
Solar/Wind Harmer
9.19
3143873LANEXA
Solar/Wind Harmer
0.18
3151081ELIZAR1
Adder
27.433
3151091ELIZAR2
Adder
26.957
3152611GOSPORTB
Adder
3.799
3152621GOSPORTC
Adder
3.224
3152601GOSPORTA
Adder
2.974
957871AF2-081 GEN
Solar/Wind Harmer
14.651
319010AE1-072 C
Solar/Wind Harmer
1.473
3146406KITTY HAWK
Solar/Wind Harmer
0.036
316305AF2-043 C
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.155
971445AH1-216 GEN
Solar/Wind Harmer
19.976
316321Z2-027
Solar/Wind Harmer
0.053
3146396TANGLEW
Solar/Wind Harmer
0.781
3145176PASQUOTANK
Solar/Wind Harmer
0.176
3146486SUNBURY
Solar/Wind Harmer
0.283
3146486SUNBURY
Solar/Wind Harmer
0.283
315835AF2-110_GEN
Solar/Wind Harmer
1.898
972265AH1-717 GEN
Adder
21.393
3151201GRAVEL4
Adder
20.055
3151191GRAVEL3
Adder
19.801
3151211GRAVEL5
Adder
19.801
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3142433PROV 92
Adder
0.518
3142433PROV 92
Adder
0.518
3130156CHOWAN
Solar/Wind Harmer
0.262
3130156CHOWAN
Solar/Wind Harmer
0.262
316311AC2-079 GEN
Solar/Wind Harmer
7.421
971167AH1-042 GEN
Solar/Wind Harmer
22.923
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.177
315816AE2-034 GEN
Solar/Wind Harmer
1.07
316369SG1_INVT
Solar/Wind Harmer
0.009
3130546PLYMOUTH
Solar/Wind Harmer
0.24
315732AD1-074 GEN1
Solar/Wind Harmer
1.368
315733AD1-074 GEN2
Solar/Wind Harmer
1.368
315735AD1-075 GEN1
Solar/Wind Harmer
0.685
3146206CASHIE
Solar/Wind Harmer
0.231
970601AG2-382 GEN
Solar/Wind Harmer
8.631
316132AB2-190 GEN1
Solar/Wind Harmer
1.234
965291AG1-394 GEN
Solar/Wind Harmer
0.991
3145893MURPHYS
Solar/Wind Harmer
0.595
3145893MURPHYS
Solar/Wind Harmer
0.22
3145513AHOSKIE
Solar/Wind Harmer
0.453
3145513AHOSKIE
Solar/Wind Harmer
0.216
3145683EARLEYS
Solar/Wind Harmer
0.43
3145683EARLEYS
Solar/Wind Harmer
0.215
3145683EARLEYS
Solar/Wind Harmer
0.215
3146043SEABORD
Solar/Wind Harmer
0.205
315607AA1-063A GEN
Solar/Wind Harmer
0.414
941031AE2-094 GEN
Solar/Wind Harmer
36.709
944011AF1-069 GEN
Solar/Wind Harmer
11.994
3146033SCOT NK
Solar/Wind Harmer
0.785
970673AG2-436 GEN
Solar/Wind Harmer
41.632
970673AG2-436 GEN
Solar/Wind Harmer
27.755
316315AB2-025 C
Solar/Wind Harmer
0.155
315814AE2-033 C
Solar/Wind Harmer
15.206
971967AH1-528 GEN
Solar/Wind Harmer
30.542
315652AC1-086 GEN
Solar/Wind Harmer
20.911
316005AA1-067
Solar/Wind Harmer
0.204
3145746EVERETS
Solar/Wind Harmer
0.755
3145746EVERETS
Solar/Wind Harmer
0.19
3145746EVERETS
Solar/Wind Harmer
0.19
3145746EVERETS
Solar/Wind Harmer
0.19
970181AG2-120 GEN
Solar/Wind Harmer
2.363
3137643SOCKMAN
Solar/Wind Harmer
0.75
3143316POE
Solar/Wind Harmer
0.741
957191AF2-013 GEN
50/50
28.335
3150341NORNECKC1
50/50
3.541
3150341NORNECKC1
50/50
3.513
963611AG1-210 GEN
50/50
1.133
316077AC2-138 C
Solar/Wind Harmer
0.002
958261AF2-120 GEN
Solar/Wind Harmer
10.528
316185AD1-033 GEN
Solar/Wind Harmer
0.008
316036AC1-147 C
Solar/Wind Harmer
0.055
3150991CHESPKB
Adder
3.126
3150991CHESPKB
Adder
3.051
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.286
3145506HICKORY
Solar/Wind Harmer
1.189
3145506HICKORY
Solar/Wind Harmer
0.713
3145506HICKORY
Solar/Wind Harmer
0.178
316339AD2-160 GEN
Solar/Wind Harmer
0.478
316018AA1-139 ULT2
Solar/Wind Harmer
0.007
316017AA1-139 ULT1
Solar/Wind Harmer
0.164
3137176SLIGO L2192
Solar/Wind Harmer
1.166
3146456SLIGO L269
Solar/Wind Harmer
5.185
3145893MURPHYS
Solar/Wind Harmer
0.882
3145893MURPHYS
Solar/Wind Harmer
0.98
3146173TUNIS
Solar/Wind Harmer
0.218
3145963POPLR C
Solar/Wind Harmer
0.217
3145683EARLEYS
Solar/Wind Harmer
0.215
316174AB2-169 GEN
Solar/Wind Harmer
0.006
3146263WOODLND
Solar/Wind Harmer
0.208
3145823KELFORD
Solar/Wind Harmer
0.206
3146293MARTNCO
Solar/Wind Harmer
0.184
316190AA2-174 GEN
Solar/Wind Harmer
0
316011AB1-132 GEN
Solar/Wind Harmer
3.456
962571AG1-106 GEN
Solar/Wind Harmer
2.705
3145746EVERETS
Solar/Wind Harmer
0.19
3145746EVERETS
Solar/Wind Harmer
0.19
316023GEN1_S
Solar/Wind Harmer
0.426
316212AC1-099_GEN
Solar/Wind Harmer
0.975
3145783HORNRTN
Solar/Wind Harmer
0.188
3145796HORNRTN
Solar/Wind Harmer
0.616
3145796HORNRTN
Solar/Wind Harmer
0.187
960081AF2-299 GEN
Solar/Wind Harmer
1.759
970919AG2-571 GEN
Solar/Wind Harmer
6.502
970087AG2-069 GEN
Solar/Wind Harmer
14.564
316494AC1-189 GEN
Solar/Wind Harmer
0.614
315671AE2-027_GEN
Solar/Wind Harmer
11.535
3143096IRON208
Adder
0.738
315722AD1-056 GEN
Solar/Wind Harmer
1.11
961671AG1-007 GEN
Solar/Wind Harmer
0.027
3146083TARBORO
Solar/Wind Harmer
0.175
3145493TOT1
Solar/Wind Harmer
0.777
971795AH1-408 GEN
Solar/Wind Harmer
11.647
3146233WITAKRS
Solar/Wind Harmer
0.682
3147043LAWRENC
Adder
1.545
3145543BTLEBRO
Solar/Wind Harmer
0.166
3145543BTLEBRO
Solar/Wind Harmer
0.133
316359AB2-059 GEN
Solar/Wind Harmer
0.597
316049AB1-081 GEN
Solar/Wind Harmer
0.952
3142053HEARTS
Solar/Wind Harmer
0.293
957481AF2-042 GEN
Solar/Wind Harmer
44.163
316129AC1-054 GEN
Solar/Wind Harmer
0.622
971065AG2-659 GEN
Solar/Wind Harmer
6.96
315693AD1-088 GEN
Solar/Wind Harmer
7.519
962491AG1-098 GEN
Solar/Wind Harmer
8.841
315687AD1-152 GEN
Solar/Wind Harmer
0.005
3142416OLDCHRC
Solar/Wind Harmer
0.378
3142416OLDCHRC
Solar/Wind Harmer
0.145
3142543TWELFTH
Solar/Wind Harmer
0.014
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970401AG2-262 GEN
Solar/Wind Harmer
0.79
3150851SPRUNCC
Adder
0.584
970685AG2-442 GEN
Solar/Wind Harmer
9.443
963171AG1-166 GEN
Solar/Wind Harmer
0.65
971563AH1-280 GEN
Solar/Wind Harmer
1.3
3144293JTRSVLE
Adder
0.388
316003AC1-222 GEN
Solar/Wind Harmer
0.003
3145796HORNRTN
Solar/Wind Harmer
0.597
3145796HORNRTN
Solar/Wind Harmer
0.075
316087AB2-174 GEN
Solar/Wind Harmer
0.005
970085AG2-068 GEN
Solar/Wind Harmer
9.709
970581AG2-369 GEN
Solar/Wind Harmer
8.35
957861AF2-080 GEN
Solar/Wind Harmer
7.839
316420AA1-050 GEN
Solar/Wind Harmer
0.006
3145573BETHELC
Solar/Wind Harmer
0.175
3145573BETHELC
Solar/Wind Harmer
0.175
316319Z2-044 C
Solar/Wind Harmer
0
970831AG2-522 GEN
Solar/Wind Harmer
7.152
316312AB1-027
Solar/Wind Harmer
0.26
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.34
971443AH1-215 GEN
Solar/Wind Harmer
2.214
3144303KENBRDG
Solar/Wind Harmer
0.105
3147173SINAI
Solar/Wind Harmer
0.129
3147243WELCO
Solar/Wind Harmer
0.081
971285AH1-108 GEN
Adder
0.956
970683AG2-441 GEN
Solar/Wind Harmer
8.431
970681AG2-440 GEN
Solar/Wind Harmer
6.745
946301AF1-294 GEN
Solar/Wind Harmer
2.405
961791AG1-021 GEN
Solar/Wind Harmer
1.17
315657AE1-056 GEN
Solar/Wind Harmer
4.092
3147133PAMPLIN
Solar/Wind Harmer
0.372
971193AH1-056 GEN
Solar/Wind Harmer
7.224
971683AH1-343 GEN
Solar/Wind Harmer
4.205
3130086AYDLETT
Solar/Wind Harmer
1.168
3146386ELIZ CT
Solar/Wind Harmer
0.286
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.278
3146516WINFALL
Solar/Wind Harmer
0.278
3146516WINFALL
Solar/Wind Harmer
0.278
3146626S HERTFORD
Solar/Wind Harmer
0.274
3146626S HERTFORD
Solar/Wind Harmer
0.274
3146376EDENTON
Solar/Wind Harmer
1.164
3146376EDENTON
Solar/Wind Harmer
1.164
3142946ENON
Solar/Wind Harmer
0.025
315742AE1-103 GEN
Solar/Wind Harmer
0.003
316075AC2-137 C
Solar/Wind Harmer
0.069
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.278
316065AD1-022 GEN
Solar/Wind Harmer
10.76
970657AG2-426 GEN
Solar/Wind Harmer
8.119
970657AG2-426 GEN
Solar/Wind Harmer
1.702
3145893MURPHYS
Solar/Wind Harmer
1.475
3145893MURPHYS
Solar/Wind Harmer
0.397
3146173TUNIS
Solar/Wind Harmer
0.218
3146173TUNIS
Solar/Wind Harmer
0.218
3145933PARMELE
Solar/Wind Harmer
0.397
3145933PARMELE
Solar/Wind Harmer
0.198
316426AA2-053 GEN
Solar/Wind Harmer
0.655
3142666NORTHAMPTON
Solar/Wind Harmer
0.194
3142666NORTHAMPTON
Solar/Wind Harmer
0.194
3142666NORTHAMPTON
Solar/Wind Harmer
0.194
3142666NORTHAMPTON
Solar/Wind Harmer
0.116
972185AH1-677 GEN
Adder
10.833
3144356SAPONY
Solar/Wind Harmer
1.609
972187AH1-678 GEN
Adder
5.419
3145593CAROLNA
Solar/Wind Harmer
0.189
3145593CAROLNA
Solar/Wind Harmer
0.189
966811AG1-552 GEN
Solar/Wind Harmer
2.054
3145593CAROLNA
Solar/Wind Harmer
0.236
3145783HORNRTN
Solar/Wind Harmer
3.351
3145783HORNRTN
Solar/Wind Harmer
2.681
3145783HORNRTN
Solar/Wind Harmer
0.838
3145783HORNRTN
Solar/Wind Harmer
0.335
3145796HORNRTN
Solar/Wind Harmer
0.56
316181AB2-040 GEN
Solar/Wind Harmer
0.27
316274AC1-208 GEN
Solar/Wind Harmer
0.954
970933AG2-581 GEN
Solar/Wind Harmer
14.695
3145493TOT1
Solar/Wind Harmer
0.405
3145453TOT5
Solar/Wind Harmer
0.243
3145603CNETO
Solar/Wind Harmer
0.162
961601AG1-000A GEN
Solar/Wind Harmer
2.96
316263AC1-034 GEN
Solar/Wind Harmer
6.32
316240AF1-291 C
Solar/Wind Harmer
0.001
970099AG2-077 GEN
Solar/Wind Harmer
17.665
944641AF1-129 GEN
Adder
77.95
3150691DARBY 3
Adder
10.969
3150701DARBY 4
Adder
10.943
3150681DARBY 2
Adder
10.93
3150671DARBY 1
Adder
10.918
939181AE1-148 GEN
Solar/Wind Harmer
7.227
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
6.521
964791AG1-342 GEN
Solar/Wind Harmer
2.586
3146843MT LREL
Solar/Wind Harmer
0.135
3146843MT LREL
Solar/Wind Harmer
0.135
970323AG2-213 GEN
Solar/Wind Harmer
5.604
971775AH1-396 GEN
Solar/Wind Harmer
0.21
316034AC1-036 C
Solar/Wind Harmer
0.01
971741AH1-377 GEN
Solar/Wind Harmer
13.018
3142366NRTHEST
Adder
0.409
970301AG2-198 GEN
Solar/Wind Harmer
5.276
958211AF2-115 GEN
Solar/Wind Harmer
1.462
963191AG1-168 GEN
Solar/Wind Harmer
0.487
3144293JTRSVLE
Adder
0.388
3144293JTRSVLE
Adder
0.327
316222AC1-221 GEN
Solar/Wind Harmer
0.499
3147133PAMPLIN
Solar/Wind Harmer
0.119
3147133PAMPLIN
Solar/Wind Harmer
0.095
CPLELTFEXP_CPLE->PJM
CLTF
9.401
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.442
LAGNLTFEXP_LAGN->PJM
CLTF
4.948
CBM South 2LTFEXP_CBM-S2->PJM
CBM
19.074
TVALTFEXP_TVA->PJM
CLTF
2.452
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.483
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.08
MECLTFEXP_MEC->PJM
CLTF
1.76
SIGELTFEXP_SIGE->PJM
CLTF
0.049
NYPJM->LTFIMP_NY
CLTF
1.582
LGEELTFEXP_LGEE->PJM
CLTF
0.54
WECLTFEXP_WEC->PJM
CLTF
0.267

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 2145_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2145_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.9 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:2757.11
MW Contribution:5.66
Bus #Bus NameTypeMW Contribution
3150921YORKTN3
50/50
8.877
3144216WINCHST
50/50
1.304
3150351NORNECKC2
50/50
3.428
315749AE2-041 GEN
50/50
11.323
970575AG2-366 GEN
50/50
5.655
3141843SHACKLE
50/50
1.681
3151101ELIZAR3
50/50
29.482
3151161SURRY 1
50/50
10.584
316382AG1-145 C
Solar/Wind Harmer
0.003
315773AC2-141 GEN
Solar/Wind Harmer
12.005
3141906WESTMOR
Solar/Wind Harmer
0.128
970737AG2-469 GEN
Solar/Wind Harmer
13.605
3141766HARMONY
Solar/Wind Harmer
4.246
316404AE1-155 C
Solar/Wind Harmer
0.072
970009AG2-005 GEN
Solar/Wind Harmer
2.376
962971AG1-146 GEN
Solar/Wind Harmer
5.09
316156AD2-030 GEN
Solar/Wind Harmer
0.235
3141873WAN 176
Solar/Wind Harmer
5.646
316280AD1-041 GEN
Solar/Wind Harmer
0.006
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
68.347
944601AF1-125 GEN
Solar/Wind Harmer
67.294
3144873MCLAUGH
Solar/Wind Harmer
0.007
3144536CHRHLND
Solar/Wind Harmer
0.044
3146456SLIGO L269
Solar/Wind Harmer
0.293
971153AH1-033 GEN
Solar/Wind Harmer
3.387
316320Y1-086
Solar/Wind Harmer
0.002
3145336SMITFLD
Solar/Wind Harmer
0.114
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.278
3151221GRAVEL6
Adder
20.031
3151171GRAVELC
Adder
3.854
3146626S HERTFORD
Solar/Wind Harmer
0.274
3142433PROV 92
Adder
0.518
3142433PROV 92
Adder
0.518
961611AG1-000B GEN
Solar/Wind Harmer
7.052
3146376EDENTON
Solar/Wind Harmer
0.262
3145273HOLLAND
Solar/Wind Harmer
0.195
3142946ENON
Solar/Wind Harmer
0.085
315614AA2-178 GEN
Solar/Wind Harmer
1.427
315778AD1-151 GEN
Solar/Wind Harmer
19.197
971157AH1-035 GEN
Solar/Wind Harmer
2.878
315737AD1-076 GEN
Solar/Wind Harmer
3.062
970661AG2-428 GEN
Solar/Wind Harmer
5.016
3146206CASHIE
Solar/Wind Harmer
0.231
316083AB2-161 GEN
Solar/Wind Harmer
0.003
970129AG2-093 GEN
Solar/Wind Harmer
13.798
970659AG2-427 GEN
Solar/Wind Harmer
2.387
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
3156021HOLLOMANSOL
Solar/Wind Harmer
1.005
3145893MURPHYS
Solar/Wind Harmer
0.369
3145893MURPHYS
Solar/Wind Harmer
0.22
957521AF2-046 GEN
Solar/Wind Harmer
16.35
961681AG1-008 GEN
Solar/Wind Harmer
16.35
3146173TUNIS
Solar/Wind Harmer
0.218
3145963POPLR C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.186
316140AB2-099
Solar/Wind Harmer
0.077
962331AG1-082 GEN
Solar/Wind Harmer
2.31
970133AG2-095 GEN
Solar/Wind Harmer
2.034
315813AE1-149 C
Solar/Wind Harmer
11.196
3146263WOODLND
Solar/Wind Harmer
0.208
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.206
970293AG2-193 GEN
Solar/Wind Harmer
2.137
3145933PARMELE
Solar/Wind Harmer
0.198
966801AG1-551 GEN
Solar/Wind Harmer
2.311
3142666NORTHAMPTON
Solar/Wind Harmer
0.194
3145746EVERETS
Solar/Wind Harmer
0.19
3145746EVERETS
Solar/Wind Harmer
0.19
316365GEN2_N
Solar/Wind Harmer
0.426
316210AC1-098 GEN
Solar/Wind Harmer
1.749
3145796HORNRTN
Solar/Wind Harmer
0.746
3145796HORNRTN
Solar/Wind Harmer
0.187
313506AB2-031 GEN
Solar/Wind Harmer
0.575
970917AG2-570 GEN
Solar/Wind Harmer
16.255
965281AG1-393 GEN
Solar/Wind Harmer
1.933
316327AA2-057 GEN
Solar/Wind Harmer
0.266
3143096IRON208
Adder
0.738
3143096IRON208
Adder
0.723
972263AH1-716 GEN
50/50
212.665
315759AF1-018 GEN
50/50
11.323
3151081ELIZAR1
50/50
29.11
3138283WHITEMARSH
Solar/Wind Harmer
0.076
316314AB2-024 C
Solar/Wind Harmer
0.001
316223AC1-118
Solar/Wind Harmer
0.229
944491AF1-114 GEN
Solar/Wind Harmer
0.001
3141813NORNECK
Solar/Wind Harmer
0.318
316059AD1-063 C
Solar/Wind Harmer
0.002
970327AG2-215 GEN
Solar/Wind Harmer
10.443
962981AG1-147 GEN
Solar/Wind Harmer
11.876
315976AC1-164 GENA
Solar/Wind Harmer
32.958
316169AC1-164_GENC
Solar/Wind Harmer
28.472
315975AC1-164 GENB
Solar/Wind Harmer
0.975
3141783LANCAST
Solar/Wind Harmer
0.191
3141783LANCAST
Solar/Wind Harmer
0.127
3138133OCRAN
Solar/Wind Harmer
0.095
3141913WHIT STONE
Solar/Wind Harmer
0.317
3141873WAN 176
Solar/Wind Harmer
0.064
315662AE1-191 GEN
Solar/Wind Harmer
0.01
315666AE1-190 GEN
Solar/Wind Harmer
0.003
970189AG2-124 GEN
Solar/Wind Harmer
9.19
3143873LANEXA
Solar/Wind Harmer
0.18
3151091ELIZAR2
Adder
26.957
3152611GOSPORTB
Adder
3.799
3152621GOSPORTC
Adder
3.224
3152601GOSPORTA
Adder
2.974
957871AF2-081 GEN
Solar/Wind Harmer
14.651
319010AE1-072 C
Solar/Wind Harmer
1.473
3146406KITTY HAWK
Solar/Wind Harmer
0.036
316305AF2-043 C
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.155
971445AH1-216 GEN
Solar/Wind Harmer
19.976
316321Z2-027
Solar/Wind Harmer
0.053
3146396TANGLEW
Solar/Wind Harmer
0.781
3145176PASQUOTANK
Solar/Wind Harmer
0.176
3146486SUNBURY
Solar/Wind Harmer
0.283
3146486SUNBURY
Solar/Wind Harmer
0.283
315835AF2-110_GEN
Solar/Wind Harmer
1.898
972265AH1-717 GEN
Adder
21.393
3151201GRAVEL4
Adder
20.055
3151191GRAVEL3
Adder
19.801
3151211GRAVEL5
Adder
19.801
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3142433PROV 92
Adder
0.518
3142433PROV 92
Adder
0.518
3130156CHOWAN
Solar/Wind Harmer
0.262
3130156CHOWAN
Solar/Wind Harmer
0.262
316311AC2-079 GEN
Solar/Wind Harmer
7.421
971167AH1-042 GEN
Solar/Wind Harmer
22.923
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.177
315816AE2-034 GEN
Solar/Wind Harmer
1.07
316369SG1_INVT
Solar/Wind Harmer
0.009
3130546PLYMOUTH
Solar/Wind Harmer
0.24
315732AD1-074 GEN1
Solar/Wind Harmer
1.368
315733AD1-074 GEN2
Solar/Wind Harmer
1.368
315735AD1-075 GEN1
Solar/Wind Harmer
0.685
3146206CASHIE
Solar/Wind Harmer
0.231
970601AG2-382 GEN
Solar/Wind Harmer
8.631
316132AB2-190 GEN1
Solar/Wind Harmer
1.234
965291AG1-394 GEN
Solar/Wind Harmer
0.991
3145893MURPHYS
Solar/Wind Harmer
0.595
3145893MURPHYS
Solar/Wind Harmer
0.22
3145513AHOSKIE
Solar/Wind Harmer
0.453
3145513AHOSKIE
Solar/Wind Harmer
0.216
3145683EARLEYS
Solar/Wind Harmer
0.43
3145683EARLEYS
Solar/Wind Harmer
0.215
3152331SURRY 2
50/50
15.432
971353AH1-157 GEN
50/50
29.999
970017AG2-010 GEN
50/50
22.046
3150351NORNECKC2
50/50
3.371
966661AG1-536 GEN
50/50
9.057
3141843SHACKLE
50/50
1.681
971317AH1-138 GEN
Solar/Wind Harmer
2.523
316159AE1-175 C
Solar/Wind Harmer
0.288
316294AC1-161 GEN
Solar/Wind Harmer
5.695
3138126ROCKLANDING
Solar/Wind Harmer
0.151
3141726DUNNSVL
Solar/Wind Harmer
1.275
316337AD2-073 GEN
Solar/Wind Harmer
0.278
972135AH1-637 GEN
Solar/Wind Harmer
2.721
3141766HARMONY
Solar/Wind Harmer
0.064
962861AG1-135 GEN
Solar/Wind Harmer
10.187
3138133OCRAN
Solar/Wind Harmer
0.191
971777AH1-397 GEN
Solar/Wind Harmer
0.818
944591AF1-124 GEN
Solar/Wind Harmer
68.589
316375AC2-012 GEN
Solar/Wind Harmer
0.008
3150981CHESPKA
Adder
3.726
316388AE2-253 GEN
Solar/Wind Harmer
0.924
3146456SLIGO L269
Solar/Wind Harmer
0.293
316072AD1-144
Solar/Wind Harmer
0.105
316246AF1-032 C
Solar/Wind Harmer
0.13
3145336SMITFLD
Solar/Wind Harmer
1.138
3146516WINFALL
Solar/Wind Harmer
0.899
3146516WINFALL
Solar/Wind Harmer
0.278
316093AE2-104_GEN
Solar/Wind Harmer
4.652
3151171GRAVELC
Adder
2.931
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3142433PROV 92
Solar/Wind Harmer
1.065
3142433PROV 92
Adder
0.518
3142433PROV 92
Adder
0.518
961611AG1-000B GEN
Solar/Wind Harmer
13.868
3130156CHOWAN
Solar/Wind Harmer
0.262
971647AH1-324 GEN
Solar/Wind Harmer
10.906
3145663CRESWEL
Solar/Wind Harmer
0.698
971163AH1-040 GEN
Solar/Wind Harmer
19.948
939411AE1-173 GEN
Solar/Wind Harmer
105.555
971069AG2-661 GEN
Solar/Wind Harmer
4.266
970661AG2-428 GEN
Solar/Wind Harmer
23.585
3146206CASHIE
Solar/Wind Harmer
0.231
971547AH1-271 GEN
Solar/Wind Harmer
4.932
940641AE2-051 GEN
Solar/Wind Harmer
18.399
316458AB2-190 GEN2
Solar/Wind Harmer
1.234
944631AF1-128 GEN
Adder
109.323
316381AD1-082 GEN
Solar/Wind Harmer
0.238
970129AG2-093 GEN
Solar/Wind Harmer
6.493
970659AG2-427 GEN
Solar/Wind Harmer
10.912
3145893MURPHYS
Solar/Wind Harmer
0.882
3145893MURPHYS
Solar/Wind Harmer
0.98
3146173TUNIS
Solar/Wind Harmer
0.218
3145963POPLR C
Solar/Wind Harmer
0.217
3145683EARLEYS
Solar/Wind Harmer
0.215
316174AB2-169 GEN
Solar/Wind Harmer
0.006
3146263WOODLND
Solar/Wind Harmer
0.208
3145823KELFORD
Solar/Wind Harmer
0.206
3146293MARTNCO
Solar/Wind Harmer
0.184
316190AA2-174 GEN
Solar/Wind Harmer
0
316011AB1-132 GEN
Solar/Wind Harmer
3.456
962571AG1-106 GEN
Solar/Wind Harmer
2.705
3145746EVERETS
Solar/Wind Harmer
0.19
3145746EVERETS
Solar/Wind Harmer
0.19
316023GEN1_S
Solar/Wind Harmer
0.426
316212AC1-099_GEN
Solar/Wind Harmer
0.975
3145783HORNRTN
Solar/Wind Harmer
0.188
3145796HORNRTN
Solar/Wind Harmer
0.616
3145796HORNRTN
Solar/Wind Harmer
0.187
960081AF2-299 GEN
Solar/Wind Harmer
1.759
970919AG2-571 GEN
Solar/Wind Harmer
6.502
970087AG2-069 GEN
Solar/Wind Harmer
14.564
316494AC1-189 GEN
Solar/Wind Harmer
0.614
315671AE2-027_GEN
Solar/Wind Harmer
11.535
3143096IRON208
Adder
0.738
315722AD1-056 GEN
Solar/Wind Harmer
1.11
961671AG1-007 GEN
Solar/Wind Harmer
0.027
3146083TARBORO
Solar/Wind Harmer
0.175
3145493TOT1
Solar/Wind Harmer
0.777
971795AH1-408 GEN
Solar/Wind Harmer
11.647
3146233WITAKRS
Solar/Wind Harmer
0.682
3147043LAWRENC
Adder
1.545
3145543BTLEBRO
Solar/Wind Harmer
0.166
3145543BTLEBRO
Solar/Wind Harmer
0.133
316359AB2-059 GEN
Solar/Wind Harmer
0.597
316049AB1-081 GEN
Solar/Wind Harmer
0.952
3142053HEARTS
Solar/Wind Harmer
0.293
957481AF2-042 GEN
Solar/Wind Harmer
44.163
316129AC1-054 GEN
Solar/Wind Harmer
0.622
971065AG2-659 GEN
Solar/Wind Harmer
6.96
315693AD1-088 GEN
Solar/Wind Harmer
7.519
962491AG1-098 GEN
Solar/Wind Harmer
8.841
315687AD1-152 GEN
Solar/Wind Harmer
0.005
3142416OLDCHRC
Solar/Wind Harmer
0.378
3142416OLDCHRC
Solar/Wind Harmer
0.145
957191AF2-013 GEN
50/50
28.335
3150341NORNECKC1
50/50
3.541
3150341NORNECKC1
50/50
3.513
963611AG1-210 GEN
50/50
1.133
316077AC2-138 C
Solar/Wind Harmer
0.002
958261AF2-120 GEN
Solar/Wind Harmer
10.528
316185AD1-033 GEN
Solar/Wind Harmer
0.008
316036AC1-147 C
Solar/Wind Harmer
0.055
3150991CHESPKB
Adder
3.126
3150991CHESPKB
Adder
3.051
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.286
3145506HICKORY
Solar/Wind Harmer
1.189
3145506HICKORY
Solar/Wind Harmer
0.713
3145506HICKORY
Solar/Wind Harmer
0.178
316339AD2-160 GEN
Solar/Wind Harmer
0.478
316018AA1-139 ULT2
Solar/Wind Harmer
0.007
316017AA1-139 ULT1
Solar/Wind Harmer
0.164
3137176SLIGO L2192
Solar/Wind Harmer
1.166
3146456SLIGO L269
Solar/Wind Harmer
5.185
3130086AYDLETT
Solar/Wind Harmer
1.168
3146386ELIZ CT
Solar/Wind Harmer
0.286
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.278
3146516WINFALL
Solar/Wind Harmer
0.278
3146516WINFALL
Solar/Wind Harmer
0.278
3146626S HERTFORD
Solar/Wind Harmer
0.274
3146626S HERTFORD
Solar/Wind Harmer
0.274
3146376EDENTON
Solar/Wind Harmer
1.164
3146376EDENTON
Solar/Wind Harmer
1.164
3142946ENON
Solar/Wind Harmer
0.025
315742AE1-103 GEN
Solar/Wind Harmer
0.003
316075AC2-137 C
Solar/Wind Harmer
0.069
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.278
316065AD1-022 GEN
Solar/Wind Harmer
10.76
970657AG2-426 GEN
Solar/Wind Harmer
8.119
970657AG2-426 GEN
Solar/Wind Harmer
1.702
3145893MURPHYS
Solar/Wind Harmer
1.475
3145893MURPHYS
Solar/Wind Harmer
0.397
3146173TUNIS
Solar/Wind Harmer
0.218
3146173TUNIS
Solar/Wind Harmer
0.218
3145933PARMELE
Solar/Wind Harmer
0.397
3145933PARMELE
Solar/Wind Harmer
0.198
316426AA2-053 GEN
Solar/Wind Harmer
0.655
3142666NORTHAMPTON
Solar/Wind Harmer
0.194
3142666NORTHAMPTON
Solar/Wind Harmer
0.194
3142666NORTHAMPTON
Solar/Wind Harmer
0.194
3142666NORTHAMPTON
Solar/Wind Harmer
0.116
972185AH1-677 GEN
Adder
10.833
3144356SAPONY
Solar/Wind Harmer
1.609
972187AH1-678 GEN
Adder
5.419
3145593CAROLNA
Solar/Wind Harmer
0.189
3145593CAROLNA
Solar/Wind Harmer
0.189
966811AG1-552 GEN
Solar/Wind Harmer
2.054
3145593CAROLNA
Solar/Wind Harmer
0.236
3145783HORNRTN
Solar/Wind Harmer
3.351
3145783HORNRTN
Solar/Wind Harmer
2.681
3145783HORNRTN
Solar/Wind Harmer
0.838
3145783HORNRTN
Solar/Wind Harmer
0.335
3145796HORNRTN
Solar/Wind Harmer
0.56
316181AB2-040 GEN
Solar/Wind Harmer
0.27
316274AC1-208 GEN
Solar/Wind Harmer
0.954
970933AG2-581 GEN
Solar/Wind Harmer
14.695
3145493TOT1
Solar/Wind Harmer
0.405
3145453TOT5
Solar/Wind Harmer
0.243
3145603CNETO
Solar/Wind Harmer
0.162
961601AG1-000A GEN
Solar/Wind Harmer
2.96
316263AC1-034 GEN
Solar/Wind Harmer
6.32
316240AF1-291 C
Solar/Wind Harmer
0.001
970099AG2-077 GEN
Solar/Wind Harmer
17.665
944641AF1-129 GEN
Adder
77.95
3150691DARBY 3
Adder
10.969
3150701DARBY 4
Adder
10.943
3150681DARBY 2
Adder
10.93
3145683EARLEYS
Solar/Wind Harmer
0.215
3146043SEABORD
Solar/Wind Harmer
0.205
315607AA1-063A GEN
Solar/Wind Harmer
0.414
941031AE2-094 GEN
Solar/Wind Harmer
36.709
944011AF1-069 GEN
Solar/Wind Harmer
11.994
3146033SCOT NK
Solar/Wind Harmer
0.785
970673AG2-436 GEN
Solar/Wind Harmer
41.632
970673AG2-436 GEN
Solar/Wind Harmer
27.755
316315AB2-025 C
Solar/Wind Harmer
0.155
315814AE2-033 C
Solar/Wind Harmer
15.206
971967AH1-528 GEN
Solar/Wind Harmer
30.542
315652AC1-086 GEN
Solar/Wind Harmer
20.911
316005AA1-067
Solar/Wind Harmer
0.204
3145746EVERETS
Solar/Wind Harmer
0.755
3145746EVERETS
Solar/Wind Harmer
0.19
3145746EVERETS
Solar/Wind Harmer
0.19
3145746EVERETS
Solar/Wind Harmer
0.19
970181AG2-120 GEN
Solar/Wind Harmer
2.363
3137643SOCKMAN
Solar/Wind Harmer
0.75
3143316POE
Solar/Wind Harmer
0.741
3145796HORNRTN
Solar/Wind Harmer
0.597
3145796HORNRTN
Solar/Wind Harmer
0.075
316087AB2-174 GEN
Solar/Wind Harmer
0.005
970085AG2-068 GEN
Solar/Wind Harmer
9.709
970581AG2-369 GEN
Solar/Wind Harmer
8.35
957861AF2-080 GEN
Solar/Wind Harmer
7.839
316420AA1-050 GEN
Solar/Wind Harmer
0.006
3145573BETHELC
Solar/Wind Harmer
0.175
3145573BETHELC
Solar/Wind Harmer
0.175
316319Z2-044 C
Solar/Wind Harmer
0
970831AG2-522 GEN
Solar/Wind Harmer
7.152
316312AB1-027
Solar/Wind Harmer
0.26
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.34
971443AH1-215 GEN
Solar/Wind Harmer
2.214
3144303KENBRDG
Solar/Wind Harmer
0.105
3147173SINAI
Solar/Wind Harmer
0.129
3147243WELCO
Solar/Wind Harmer
0.081
971285AH1-108 GEN
Adder
0.956
970683AG2-441 GEN
Solar/Wind Harmer
8.431
970681AG2-440 GEN
Solar/Wind Harmer
6.745
946301AF1-294 GEN
Solar/Wind Harmer
2.405
961791AG1-021 GEN
Solar/Wind Harmer
1.17
315657AE1-056 GEN
Solar/Wind Harmer
4.092
315724AD1-057 GEN
Solar/Wind Harmer
0.658
3146073TAR RVR
Solar/Wind Harmer
0.175
3146083TARBORO
Solar/Wind Harmer
0.175
315839AE2-212 C
Solar/Wind Harmer
0.001
3146233WITAKRS
Solar/Wind Harmer
0.86
3146233WITAKRS
Solar/Wind Harmer
0.117
3138543CONSLDL
Solar/Wind Harmer
0.113
3147043LAWRENC
Solar/Wind Harmer
0.102
961601AG1-000A GEN
Solar/Wind Harmer
11.84
3145543BTLEBRO
Solar/Wind Harmer
0.166
3145543BTLEBRO
Solar/Wind Harmer
0.166
971623AH1-311 GEN
Solar/Wind Harmer
0.333
316478AD1-087 GEN
Solar/Wind Harmer
0.55
316486AD2-202 GEN
Solar/Wind Harmer
0.162
3142416OLDCHRC
Solar/Wind Harmer
1.409
316131AB2-060 GEN
Solar/Wind Harmer
0.445
964241AG1-285 GEN
Solar/Wind Harmer
9.23
315785AD2-033 C
Solar/Wind Harmer
1.084
970257AG2-171 GEN
Solar/Wind Harmer
4.203
959311AF2-222 GEN
Solar/Wind Harmer
11.552
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.512
3150861SPRUNCD
Adder
0.584
970909AG2-566 GEN
Solar/Wind Harmer
1.319
963181AG1-167 GEN
Solar/Wind Harmer
0.487
3144293JTRSVLE
Adder
0.388
316283AC2-100 C
Solar/Wind Harmer
0.234
3147133PAMPLIN
Solar/Wind Harmer
0.372
971193AH1-056 GEN
Solar/Wind Harmer
7.224
971683AH1-343 GEN
Solar/Wind Harmer
4.205
3150671DARBY 1
Adder
10.918
939181AE1-148 GEN
Solar/Wind Harmer
7.227
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
6.521
964791AG1-342 GEN
Solar/Wind Harmer
2.586
3146843MT LREL
Solar/Wind Harmer
0.135
3146843MT LREL
Solar/Wind Harmer
0.135
970323AG2-213 GEN
Solar/Wind Harmer
5.604
971775AH1-396 GEN
Solar/Wind Harmer
0.21
316034AC1-036 C
Solar/Wind Harmer
0.01
971741AH1-377 GEN
Solar/Wind Harmer
13.018
3142366NRTHEST
Adder
0.409
970301AG2-198 GEN
Solar/Wind Harmer
5.276
958211AF2-115 GEN
Solar/Wind Harmer
1.462
963191AG1-168 GEN
Solar/Wind Harmer
0.487
3144293JTRSVLE
Adder
0.388
3144293JTRSVLE
Adder
0.327
316222AC1-221 GEN
Solar/Wind Harmer
0.499
3147133PAMPLIN
Solar/Wind Harmer
0.119
3147133PAMPLIN
Solar/Wind Harmer
0.095
3142543TWELFTH
Solar/Wind Harmer
0.014
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970401AG2-262 GEN
Solar/Wind Harmer
0.79
3150851SPRUNCC
Adder
0.584
970685AG2-442 GEN
Solar/Wind Harmer
9.443
963171AG1-166 GEN
Solar/Wind Harmer
0.65
971563AH1-280 GEN
Solar/Wind Harmer
1.3
3144293JTRSVLE
Adder
0.388
316003AC1-222 GEN
Solar/Wind Harmer
0.003
CPLELTFEXP_CPLE->PJM
CLTF
9.401
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.442
LAGNLTFEXP_LAGN->PJM
CLTF
4.948
CBM South 2LTFEXP_CBM-S2->PJM
CBM
19.074
TVALTFEXP_TVA->PJM
CLTF
2.452
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.483
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.08
MECLTFEXP_MEC->PJM
CLTF
1.76
SIGELTFEXP_SIGE->PJM
CLTF
0.049
NYPJM->LTFIMP_NY
CLTF
1.582
LGEELTFEXP_LGEE->PJM
CLTF
0.54
WECLTFEXP_WEC->PJM
CLTF
0.267

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2076-2145_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2076-2145_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.02 %
Rating:5011.0 MVA
Rating Type:C
MVA to Mitigate:5512.93
MW Contribution:5.67
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
11.406
3152181CUNINGC
50/50
2.595
972193AH1-681 GEN
50/50
7.633
316312AB1-027
Solar/Wind Harmer
1.278
315976AC1-164 GENA
Solar/Wind Harmer
39.805
316169AC1-164_GENC
Solar/Wind Harmer
34.388
315975AC1-164 GENB
Solar/Wind Harmer
1.178
316314AB2-024 C
Solar/Wind Harmer
3.105
316223AC1-118
Solar/Wind Harmer
0.979
944491AF1-114 GEN
Solar/Wind Harmer
10.62
3141813NORNECK
Solar/Wind Harmer
-0.036
316059AD1-063 C
Solar/Wind Harmer
0.815
962981AG1-147 GEN
Solar/Wind Harmer
15.689
3143873LANEXA
Solar/Wind Harmer
-0.021
3141783LANCAST
Solar/Wind Harmer
-0.021
3141783LANCAST
Solar/Wind Harmer
-0.014
3138133OCRAN
Solar/Wind Harmer
-0.011
3141913WHIT STONE
Solar/Wind Harmer
-0.036
315662AE1-191 GEN
Solar/Wind Harmer
4.296
315666AE1-190 GEN
Solar/Wind Harmer
1.074
957601AF2-054 GEN
Solar/Wind Harmer
1.064
3141873WAN 176
Solar/Wind Harmer
-0.007
3142433PROV 92
Adder
0.606
3142433PROV 92
Adder
0.606
971167AH1-042 GEN
Solar/Wind Harmer
33.529
957831AF2-077 GEN
Solar/Wind Harmer
1.033
3138283WHITEMARSH
Solar/Wind Harmer
0.053
316132AB2-190 GEN1
Solar/Wind Harmer
3.204
316369SG1_INVT
Solar/Wind Harmer
5.606
972265AH1-717 GEN
Adder
21.338
3151201GRAVEL4
Adder
20.003
3151191GRAVEL3
Adder
19.75
3151211GRAVEL5
Adder
19.75
971445AH1-216 GEN
Solar/Wind Harmer
18.761
971285AH1-108 GEN
Adder
2.006
3152611GOSPORTB
Adder
3.315
3152621GOSPORTC
Adder
2.813
3152601GOSPORTA
Adder
2.595
3151081ELIZAR1
Adder
23.856
3151091ELIZAR2
Adder
23.441
957871AF2-081 GEN
Solar/Wind Harmer
14.371
319010AE1-072 C
Solar/Wind Harmer
5.791
3146406KITTY HAWK
Solar/Wind Harmer
0.024
316305AF2-043 C
Solar/Wind Harmer
0.862
315833AF1-017_GEN
Solar/Wind Harmer
5.389
316349AD2-085 GEN
Solar/Wind Harmer
2.524
316311AC2-079 GEN
Solar/Wind Harmer
14.311
315835AF2-110_GEN
Solar/Wind Harmer
3.536
313526AB2-022
Solar/Wind Harmer
0.762
3146486SUNBURY
Solar/Wind Harmer
-0.028
3146486SUNBURY
Solar/Wind Harmer
-0.028
316321Z2-027
Solar/Wind Harmer
0.757
3146396TANGLEW
Solar/Wind Harmer
0.516
3145176PASQUOTANK
Solar/Wind Harmer
-0.017
3143316POE
Solar/Wind Harmer
-0.107
315611Z1-036_GEN2
Solar/Wind Harmer
6.702
3130156CHOWAN
Solar/Wind Harmer
-0.027
3130156CHOWAN
Solar/Wind Harmer
-0.027
3142296MT RD221
50/50
1.125
3150341NORNECKC1
50/50
3.581
3150341NORNECKC1
50/50
3.552
963611AG1-210 GEN
50/50
1.146
3150691DARBY 3
50/50
24.142
3150701DARBY 4
50/50
24.085
3150681DARBY 2
50/50
24.057
3150671DARBY 1
50/50
24.029
316075AC2-137 C
Solar/Wind Harmer
1.004
316077AC2-138 C
Solar/Wind Harmer
0.764
958261AF2-120 GEN
Solar/Wind Harmer
13.96
316487AF1-042 GEN
Solar/Wind Harmer
4.732
316441AF1-014 GEN
Solar/Wind Harmer
2.405
3142946ENON
Solar/Wind Harmer
-0.004
3142366NRTHEST
Adder
1.019
966871AG1-558 GEN
Solar/Wind Harmer
1.032
966871AG1-558 GEN
Solar/Wind Harmer
0.353
316033AB2-134 GEN
Solar/Wind Harmer
10.118
315697AD1-025 GEN
Solar/Wind Harmer
6.346
944641AF1-129 GEN
Adder
130.968
316240AF1-291 C
Solar/Wind Harmer
0.918
316236AE1-162_GEN
Solar/Wind Harmer
0.912
316036AC1-147 C
Solar/Wind Harmer
0.789
3150991CHESPKB
Adder
2.727
3150991CHESPKB
Adder
2.662
316316AC1-027 C
Solar/Wind Harmer
0.894
3142956BIRDNECK
Solar/Wind Harmer
1.562
316185AD1-033 GEN
Solar/Wind Harmer
3.061
3145506HICKORY
Solar/Wind Harmer
-0.115
3145506HICKORY
Solar/Wind Harmer
-0.069
3145506HICKORY
Solar/Wind Harmer
-0.017
316339AD2-160 GEN
Solar/Wind Harmer
1.941
316018AA1-139 ULT2
Solar/Wind Harmer
2.462
316017AA1-139 ULT1
Solar/Wind Harmer
2.326
3137176SLIGO L2192
Solar/Wind Harmer
-0.113
3146456SLIGO L269
Solar/Wind Harmer
3.385
3130086AYDLETT
Solar/Wind Harmer
-0.114
970657AG2-426 GEN
Solar/Wind Harmer
8.908
970657AG2-426 GEN
Solar/Wind Harmer
1.863
3146386ELIZ CT
Solar/Wind Harmer
-0.028
316431W1029_GEN1
Solar/Wind Harmer
5.043
316433W1029_GEN2
Solar/Wind Harmer
5.043
3146516WINFALL
Solar/Wind Harmer
-0.028
3146516WINFALL
Solar/Wind Harmer
-0.028
3146516WINFALL
Solar/Wind Harmer
-0.028
3146626S HERTFORD
Solar/Wind Harmer
-0.027
3146626S HERTFORD
Solar/Wind Harmer
-0.027
3146376EDENTON
Solar/Wind Harmer
0.791
971645AH1-323 GEN
50/50
30.503
3150351NORNECKC2
50/50
3.466
315749AE2-041 GEN
50/50
11.406
970575AG2-366 GEN
50/50
5.674
3141843SHACKLE
50/50
1.722
3152191CUNINGD
50/50
5.651
3152171CUNINGB
50/50
2.44
3142416OLDCHRC
Solar/Wind Harmer
3.824
970293AG2-193 GEN
Solar/Wind Harmer
4.543
3141906WESTMOR
Solar/Wind Harmer
-0.014
970737AG2-469 GEN
Solar/Wind Harmer
18.144
3141766HARMONY
Solar/Wind Harmer
3.208
316404AE1-155 C
Solar/Wind Harmer
6.949
316484AD2-074 GEN
Solar/Wind Harmer
9.043
970009AG2-005 GEN
Solar/Wind Harmer
4.49
962971AG1-146 GEN
Solar/Wind Harmer
6.724
316203AE2-005 GEN
Solar/Wind Harmer
15.045
316280AD1-041 GEN
Solar/Wind Harmer
2.685
316156AD2-030 GEN
Solar/Wind Harmer
0.95
3141873WAN 176
Solar/Wind Harmer
4.223
972255AH1-712 GEN
Adder
161.004
3142946ENON
Solar/Wind Harmer
-0.012
3142433PROV 92
Adder
0.606
3142433PROV 92
Adder
0.606
316382AG1-145 C
Solar/Wind Harmer
1.053
316473AC1-191 GEN
Solar/Wind Harmer
3.695
3143096IRON208
Adder
1.248
3143096IRON208
Adder
1.223
3150921YORKTN3
Adder
7.437
3144216WINCHST
Adder
1.105
970133AG2-095 GEN
Solar/Wind Harmer
3.599
970129AG2-093 GEN
Solar/Wind Harmer
17.851
315816AE2-034 GEN
Solar/Wind Harmer
2.089
316233AE1-074 FULL
Solar/Wind Harmer
0.687
971281AH1-106 GEN
Solar/Wind Harmer
4.151
971283AH1-107 GEN
Solar/Wind Harmer
4.151
972189AH1-679 GEN
Adder
3.806
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
315732AD1-074 GEN1
Solar/Wind Harmer
5.066
315733AD1-074 GEN2
Solar/Wind Harmer
5.066
315735AD1-075 GEN1
Solar/Wind Harmer
2.534
3146206CASHIE
Solar/Wind Harmer
-0.025
970601AG2-382 GEN
Solar/Wind Harmer
10.772
965291AG1-394 GEN
Solar/Wind Harmer
2.166
316318V4-068
Solar/Wind Harmer
0.602
3145893MURPHYS
Solar/Wind Harmer
-0.065
3145893MURPHYS
Solar/Wind Harmer
-0.024
316315AB2-025 C
Solar/Wind Harmer
0.651
315814AE2-033 C
Solar/Wind Harmer
22.406
3145513AHOSKIE
Solar/Wind Harmer
0.207
961941AG1-037 GEN
Solar/Wind Harmer
0.179
3145513AHOSKIE
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
3146043SEABORD
Solar/Wind Harmer
-0.023
315607AA1-063A GEN
Solar/Wind Harmer
2.323
315652AC1-086 GEN
Solar/Wind Harmer
25.099
3146033SCOT NK
Solar/Wind Harmer
-0.089
946281AF1-292 GEN
Solar/Wind Harmer
0.496
316087AB2-174 GEN
Solar/Wind Harmer
3.158
3137643SOCKMAN
Solar/Wind Harmer
-0.088
3145796HORNRTN
Solar/Wind Harmer
-0.07
3145796HORNRTN
Solar/Wind Harmer
-0.009
316005AA1-067
Solar/Wind Harmer
0.436
3145746EVERETS
Solar/Wind Harmer
-0.085
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
970181AG2-120 GEN
Solar/Wind Harmer
2.826
957861AF2-080 GEN
Solar/Wind Harmer
9.177
941031AE2-094 GEN
Solar/Wind Harmer
39.278
944011AF1-069 GEN
Solar/Wind Harmer
12.307
316420AA1-050 GEN
Solar/Wind Harmer
2.365
970673AG2-436 GEN
Solar/Wind Harmer
43.507
970673AG2-436 GEN
Solar/Wind Harmer
22.029
971967AH1-528 GEN
Solar/Wind Harmer
38.619
3145573BETHELC
Solar/Wind Harmer
-0.02
3145573BETHELC
Solar/Wind Harmer
-0.02
316319Z2-044 C
Solar/Wind Harmer
1.123
970831AG2-522 GEN
Solar/Wind Harmer
10.164
970085AG2-068 GEN
Solar/Wind Harmer
12.433
970581AG2-369 GEN
Solar/Wind Harmer
10.692
3151881LOWMORC
Adder
1.506
3151881LOWMORC
Adder
1.482
3151861LOWMORA
Adder
1.458
972205AH1-687 GEN
Adder
6.025
316164AC1-076 GEN
Solar/Wind Helper
1.309
3141426STAFORD
Solar/Wind Helper
0.058
316411AF1-147_GEN1
Solar/Wind Helper
0.832
316415AF1-147_GEN2
Solar/Wind Helper
0.832
3138216PACIFIC
Solar/Wind Helper
0.041
3146376EDENTON
Solar/Wind Harmer
0.791
315742AE1-103 GEN
Solar/Wind Harmer
2.781
3143526WINTERP
Solar/Wind Harmer
-0.132
316065AD1-022 GEN
Solar/Wind Harmer
12.389
3145893MURPHYS
Solar/Wind Harmer
0.674
3145893MURPHYS
Solar/Wind Harmer
-0.043
3144356SAPONY
Solar/Wind Harmer
0.841
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
316468AD1-105 GEN
Solar/Wind Harmer
2.59
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
316426AA2-053 GEN
Solar/Wind Harmer
2.259
3145933PARMELE
Solar/Wind Harmer
-0.044
3145933PARMELE
Solar/Wind Harmer
-0.022
316181AB2-040 GEN
Solar/Wind Harmer
3.086
3145593CAROLNA
Solar/Wind Harmer
-0.022
3145593CAROLNA
Solar/Wind Harmer
-0.022
966811AG1-552 GEN
Solar/Wind Harmer
2.484
3145593CAROLNA
Solar/Wind Harmer
0.183
3145783HORNRTN
Solar/Wind Harmer
2.608
3145783HORNRTN
Solar/Wind Harmer
2.086
3145783HORNRTN
Solar/Wind Harmer
0.652
3145783HORNRTN
Solar/Wind Harmer
0.261
3145796HORNRTN
Solar/Wind Harmer
-0.065
971223AH1-071 GEN
Solar/Wind Harmer
2.682
316274AC1-208 GEN
Solar/Wind Harmer
2.31
972185AH1-677 GEN
Adder
10.284
3145493TOT1
Solar/Wind Harmer
0.317
3145453TOT5
Solar/Wind Harmer
0.19
3150351NORNECKC2
50/50
3.409
966661AG1-536 GEN
50/50
9.12
3141843SHACKLE
50/50
1.722
3152161CUNINGA
50/50
2.429
3142416OLDCHRC
Solar/Wind Harmer
-0.098
3142416OLDCHRC
Solar/Wind Harmer
-0.037
964211AG1-282 GEN
Solar/Wind Harmer
1.092
3141726DUNNSVL
Solar/Wind Harmer
-0.145
316337AD2-073 GEN
Solar/Wind Harmer
0.975
972135AH1-637 GEN
Solar/Wind Harmer
3.628
957971AF2-091 GEN
Solar/Wind Harmer
3.61
3141766HARMONY
Solar/Wind Harmer
-0.007
962861AG1-135 GEN
Solar/Wind Harmer
13.499
961951AG1-038 GEN
Solar/Wind Harmer
4.732
3138133OCRAN
Solar/Wind Harmer
-0.021
971777AH1-397 GEN
Solar/Wind Harmer
4.196
972277AH1-723 GEN
Adder
187.618
3142433PROV 92
Solar/Wind Harmer
-0.139
3142433PROV 92
Adder
0.606
3142433PROV 92
Adder
0.606
316159AE1-175 C
Solar/Wind Harmer
0.938
944631AF1-128 GEN
Adder
145.494
971317AH1-138 GEN
Solar/Wind Harmer
4.26
3143096IRON208
Adder
1.248
3138126ROCKLANDING
Solar/Wind Harmer
0.101
3142543TWELFTH
Solar/Wind Harmer
-0.003
970129AG2-093 GEN
Solar/Wind Harmer
7.231
316458AB2-190 GEN2
Solar/Wind Harmer
3.204
971069AG2-661 GEN
Solar/Wind Harmer
4.984
971647AH1-324 GEN
Solar/Wind Harmer
15.611
961611AG1-000B GEN
Solar/Wind Harmer
15.333
3151171GRAVELC
Adder
2.923
3145336SMITFLD
Solar/Wind Harmer
-0.12
315671AE2-027_GEN
Solar/Wind Harmer
22.629
316294AC1-161 GEN
Solar/Wind Harmer
9.694
3150851SPRUNCC
Adder
1.226
316072AD1-144
Solar/Wind Harmer
0.593
316375AC2-012 GEN
Solar/Wind Harmer
10.123
3150981CHESPKA
Adder
3.251
944591AF1-124 GEN
Solar/Wind Harmer
132.801
316388AE2-253 GEN
Solar/Wind Harmer
1.941
3146456SLIGO L269
Solar/Wind Harmer
-0.029
316246AF1-032 C
Solar/Wind Harmer
0.579
970659AG2-427 GEN
Solar/Wind Harmer
15.161
316381AD1-082 GEN
Solar/Wind Harmer
2.616
970661AG2-428 GEN
Solar/Wind Harmer
30.261
316093AE2-104_GEN
Solar/Wind Harmer
8.224
3146516WINFALL
Solar/Wind Harmer
-0.089
3146516WINFALL
Solar/Wind Harmer
-0.028
315778AD1-151 GEN
Solar/Wind Harmer
27.286
961611AG1-000B GEN
Solar/Wind Harmer
6.542
3151221GRAVEL6
Adder
19.98
3151171GRAVELC
Adder
3.844
3145336SMITFLD
Solar/Wind Harmer
-0.012
315773AC2-141 GEN
Solar/Wind Harmer
12.538
3150861SPRUNCD
Adder
1.226
965281AG1-393 GEN
Solar/Wind Harmer
3.728
3144536CHRHLND
Solar/Wind Harmer
-0.005
3151101ELIZAR3
Adder
24.161
3144873MCLAUGH
Solar/Wind Harmer
-0.001
315839AE2-212 C
Solar/Wind Harmer
0.881
944581AF1-123 GEN
Solar/Wind Harmer
132.324
944601AF1-125 GEN
Solar/Wind Harmer
130.259
3146456SLIGO L269
Solar/Wind Harmer
-0.029
971153AH1-033 GEN
Solar/Wind Harmer
3.494
315813AE1-149 C
Solar/Wind Harmer
17.884
970659AG2-427 GEN
Solar/Wind Harmer
2.687
316083AB2-161 GEN
Solar/Wind Harmer
4.629
970661AG2-428 GEN
Solar/Wind Harmer
5.363
316320Y1-086
Solar/Wind Harmer
1.655
316435W1029_GEN3
Solar/Wind Harmer
5.043
3146516WINFALL
Solar/Wind Harmer
-0.028
3146626S HERTFORD
Solar/Wind Harmer
-0.027
3145273HOLLAND
Solar/Wind Harmer
-0.02
3146376EDENTON
Solar/Wind Harmer
-0.027
315614AA2-178 GEN
Solar/Wind Harmer
2.785
971157AH1-035 GEN
Solar/Wind Harmer
3.146
315737AD1-076 GEN
Solar/Wind Harmer
4.761
3146206CASHIE
Solar/Wind Harmer
-0.025
3156081AA2-088 GEN
Solar/Wind Harmer
7.981
3145893MURPHYS
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
-0.024
957521AF2-046 GEN
Solar/Wind Harmer
18.965
961681AG1-008 GEN
Solar/Wind Harmer
18.965
3156021HOLLOMANSOL
Solar/Wind Harmer
3.235
3146173TUNIS
Solar/Wind Harmer
-0.024
316463AE2-346 GEN
Solar/Wind Harmer
0.385
316140AB2-099
Solar/Wind Harmer
0.16
962331AG1-082 GEN
Solar/Wind Harmer
2.97
3145963POPLR C
Solar/Wind Harmer
-0.023
971781AH1-399 GEN
Solar/Wind Harmer
1.433
3146263WOODLND
Solar/Wind Harmer
-0.023
316317KELFORD C
Solar/Wind Harmer
1.082
3145823KELFORD
Solar/Wind Harmer
-0.023
316365GEN2_N
Solar/Wind Harmer
1.542
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
966621AG1-532 GEN
Solar/Wind Harmer
0.45
3145933PARMELE
Solar/Wind Harmer
-0.022
966801AG1-551 GEN
Solar/Wind Harmer
2.768
313506AB2-031 GEN
Solar/Wind Harmer
1.778
3145796HORNRTN
Solar/Wind Harmer
-0.087
3145796HORNRTN
Solar/Wind Harmer
-0.022
316210AC1-098 GEN
Solar/Wind Harmer
3.408
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
3147043LAWRENC
Solar/Wind Harmer
-0.013
315724AD1-057 GEN
Solar/Wind Harmer
1.198
316327AA2-057 GEN
Solar/Wind Harmer
2.095
3146073TAR RVR
Solar/Wind Harmer
-0.02
3146083TARBORO
Solar/Wind Harmer
-0.02
3146233WITAKRS
Solar/Wind Harmer
0.425
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.013
970917AG2-570 GEN
Solar/Wind Harmer
49.866
961601AG1-000A GEN
Solar/Wind Harmer
7.929
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3144293JTRSVLE
Adder
0.514
3151861LOWMORA
Adder
1.518
316044AC1-158 PL1
Solar/Wind Helper
1.66
316450AC1-158 RIC
Solar/Wind Helper
0.443
3141196NOKESVL
Solar/Wind Helper
1.065
315800Z1-036_GEN1
Solar/Wind Harmer
6.702
3130156CHOWAN
Solar/Wind Harmer
-0.027
3145663CRESWEL
Solar/Wind Harmer
-0.072
971163AH1-040 GEN
Solar/Wind Harmer
24.203
3143526WINTERP
Solar/Wind Harmer
-0.132
3146206CASHIE
Solar/Wind Harmer
-0.025
971547AH1-271 GEN
Solar/Wind Harmer
6.156
939411AE1-173 GEN
Solar/Wind Harmer
122.514
3145893MURPHYS
Solar/Wind Harmer
-0.096
3145893MURPHYS
Solar/Wind Harmer
0.717
3146173TUNIS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145963POPLR C
Solar/Wind Harmer
-0.023
316174AB2-169 GEN
Solar/Wind Harmer
3.581
3146263WOODLND
Solar/Wind Harmer
-0.023
940641AE2-051 GEN
Solar/Wind Harmer
21.565
3145823KELFORD
Solar/Wind Harmer
-0.023
316023GEN1_S
Solar/Wind Harmer
1.542
316190AA2-174 GEN
Solar/Wind Harmer
0.275
316011AB1-132 GEN
Solar/Wind Harmer
4.668
962571AG1-106 GEN
Solar/Wind Harmer
3.207
960081AF2-299 GEN
Solar/Wind Harmer
2.493
3146293MARTNCO
Solar/Wind Harmer
0.137
3145783HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.072
3145796HORNRTN
Solar/Wind Harmer
-0.022
316212AC1-099_GEN
Solar/Wind Harmer
1.893
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
3143226MDLTHAN
Solar/Wind Harmer
-0.021
971795AH1-408 GEN
Solar/Wind Harmer
16.09
3147043LAWRENC
Adder
1.701
316494AC1-189 GEN
Solar/Wind Harmer
2.257
315722AD1-056 GEN
Solar/Wind Harmer
2.178
961671AG1-007 GEN
Solar/Wind Harmer
0.259
3146083TARBORO
Solar/Wind Harmer
-0.02
3145493TOT1
Solar/Wind Harmer
0.608
3146233WITAKRS
Solar/Wind Harmer
-0.08
316129AC1-054 GEN
Solar/Wind Harmer
1.766
971065AG2-659 GEN
Solar/Wind Harmer
9.983
970919AG2-571 GEN
Solar/Wind Harmer
6.312
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316359AB2-059 GEN
Solar/Wind Harmer
2.683
316049AB1-081 GEN
Solar/Wind Harmer
2.147
3142053HEARTS
Solar/Wind Harmer
0.234
970087AG2-069 GEN
Solar/Wind Harmer
18.65
3144293JTRSVLE
Adder
0.514
316045AC1-158 PL2
Solar/Wind Helper
5.315
316006AB2-029 C
Solar/Wind Helper
0.12
316254AC1-120 GEN1
Solar/Wind Helper
1.098
957481AF2-042 GEN
Solar/Wind Harmer
44.546
227287AC2-120 GEN
Solar/Wind Helper
0.341
226910AB2-157 C
Solar/Wind Helper
0.014
316170AC1-121 GEN2
Solar/Wind Helper
0.366
3145603CNETO
Solar/Wind Harmer
0.127
972187AH1-678 GEN
Adder
5.178
970933AG2-581 GEN
Solar/Wind Harmer
18.958
961601AG1-000A GEN
Solar/Wind Harmer
7.83
316263AC1-034 GEN
Solar/Wind Harmer
9.328
3144293JTRSVLE
Adder
0.514
3144293JTRSVLE
Adder
0.433
316447AC1-158 HLD
Solar/Wind Helper
3.654
226929AD2-058 GEN
Solar/Wind Helper
0.101
315651AD1-115 GEN
Solar/Wind Helper
0.812
970099AG2-077 GEN
Solar/Wind Harmer
17.818
CPLELTFEXP_CPLE->PJM
CLTF
11.373
CBM West 2LTFEXP_CBM-W2->PJM
CBM
57.092
LAGNLTFEXP_LAGN->PJM
CLTF
10.202
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.271
TVALTFEXP_TVA->PJM
CLTF
5.187
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.767
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.174
MECLTFEXP_MEC->PJM
CLTF
5.701
SIGELTFEXP_SIGE->PJM
CLTF
0.178
NYPJM->LTFIMP_NY
CLTF
3.519
LGEELTFEXP_LGEE->PJM
CLTF
2.238
WECLTFEXP_WEC->PJM
CLTF
1.128
AG2-052LTFEXP_AG2-052->PJM
LTF
0.063
AH1-155LTFEXP_AH1-155->PJM
LTF
0.094

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2076-2145_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2076-2145_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:109.95 %
Rating:5011.0 MVA
Rating Type:C
MVA to Mitigate:5509.42
MW Contribution:5.67
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
11.406
3152181CUNINGC
50/50
2.595
972193AH1-681 GEN
50/50
7.633
316312AB1-027
Solar/Wind Harmer
1.278
315976AC1-164 GENA
Solar/Wind Harmer
39.805
971645AH1-323 GEN
50/50
30.503
3150351NORNECKC2
50/50
3.466
315749AE2-041 GEN
50/50
11.406
970575AG2-366 GEN
50/50
5.674
3141843SHACKLE
50/50
1.722
3152191CUNINGD
50/50
5.651
3152171CUNINGB
50/50
2.44
3142416OLDCHRC
Solar/Wind Harmer
3.824
970293AG2-193 GEN
Solar/Wind Harmer
4.543
3141906WESTMOR
Solar/Wind Harmer
-0.014
970737AG2-469 GEN
Solar/Wind Harmer
18.144
3141766HARMONY
Solar/Wind Harmer
3.208
316404AE1-155 C
Solar/Wind Harmer
6.949
316484AD2-074 GEN
Solar/Wind Harmer
9.043
970009AG2-005 GEN
Solar/Wind Harmer
4.49
962971AG1-146 GEN
Solar/Wind Harmer
6.724
316203AE2-005 GEN
Solar/Wind Harmer
15.045
316280AD1-041 GEN
Solar/Wind Harmer
2.685
316156AD2-030 GEN
Solar/Wind Harmer
0.95
3141873WAN 176
Solar/Wind Harmer
4.223
972255AH1-712 GEN
Adder
161.004
3142946ENON
Solar/Wind Harmer
-0.012
3142433PROV 92
Adder
0.606
3142433PROV 92
Adder
0.606
316382AG1-145 C
Solar/Wind Harmer
1.053
316473AC1-191 GEN
Solar/Wind Harmer
3.695
3143096IRON208
Adder
1.248
3143096IRON208
Adder
1.223
3150921YORKTN3
Adder
7.437
3144216WINCHST
Adder
1.105
970133AG2-095 GEN
Solar/Wind Harmer
3.599
970129AG2-093 GEN
Solar/Wind Harmer
17.851
315778AD1-151 GEN
Solar/Wind Harmer
27.286
961611AG1-000B GEN
Solar/Wind Harmer
6.542
3151221GRAVEL6
Adder
19.98
3151171GRAVELC
Adder
3.844
3145336SMITFLD
Solar/Wind Harmer
-0.012
315773AC2-141 GEN
Solar/Wind Harmer
12.538
3150861SPRUNCD
Adder
1.226
965281AG1-393 GEN
Solar/Wind Harmer
3.728
3144536CHRHLND
Solar/Wind Harmer
-0.005
3151101ELIZAR3
Adder
24.161
3144873MCLAUGH
Solar/Wind Harmer
-0.001
315839AE2-212 C
Solar/Wind Harmer
0.881
944581AF1-123 GEN
Solar/Wind Harmer
132.324
944601AF1-125 GEN
Solar/Wind Harmer
130.259
3146456SLIGO L269
Solar/Wind Harmer
-0.029
971153AH1-033 GEN
Solar/Wind Harmer
3.494
315813AE1-149 C
Solar/Wind Harmer
17.884
970659AG2-427 GEN
Solar/Wind Harmer
2.687
316083AB2-161 GEN
Solar/Wind Harmer
4.629
3150351NORNECKC2
50/50
3.409
966661AG1-536 GEN
50/50
9.12
3141843SHACKLE
50/50
1.722
3152161CUNINGA
50/50
2.429
3142416OLDCHRC
Solar/Wind Harmer
-0.098
3142416OLDCHRC
Solar/Wind Harmer
-0.037
964211AG1-282 GEN
Solar/Wind Harmer
1.092
3141726DUNNSVL
Solar/Wind Harmer
-0.145
316337AD2-073 GEN
Solar/Wind Harmer
0.975
972135AH1-637 GEN
Solar/Wind Harmer
3.628
957971AF2-091 GEN
Solar/Wind Harmer
3.61
3141766HARMONY
Solar/Wind Harmer
-0.007
962861AG1-135 GEN
Solar/Wind Harmer
13.499
961951AG1-038 GEN
Solar/Wind Harmer
4.732
3138133OCRAN
Solar/Wind Harmer
-0.021
971777AH1-397 GEN
Solar/Wind Harmer
4.196
972277AH1-723 GEN
Adder
187.618
3142433PROV 92
Solar/Wind Harmer
-0.139
3142433PROV 92
Adder
0.606
3142433PROV 92
Adder
0.606
316159AE1-175 C
Solar/Wind Harmer
0.938
944631AF1-128 GEN
Adder
145.494
971317AH1-138 GEN
Solar/Wind Harmer
4.26
3143096IRON208
Adder
1.248
3138126ROCKLANDING
Solar/Wind Harmer
0.101
3142543TWELFTH
Solar/Wind Harmer
-0.003
970129AG2-093 GEN
Solar/Wind Harmer
7.231
316458AB2-190 GEN2
Solar/Wind Harmer
3.204
971069AG2-661 GEN
Solar/Wind Harmer
4.984
971647AH1-324 GEN
Solar/Wind Harmer
15.611
961611AG1-000B GEN
Solar/Wind Harmer
15.333
3151171GRAVELC
Adder
2.923
3145336SMITFLD
Solar/Wind Harmer
-0.12
315671AE2-027_GEN
Solar/Wind Harmer
22.629
316294AC1-161 GEN
Solar/Wind Harmer
9.694
3150851SPRUNCC
Adder
1.226
316072AD1-144
Solar/Wind Harmer
0.593
316375AC2-012 GEN
Solar/Wind Harmer
10.123
3150981CHESPKA
Adder
3.251
944591AF1-124 GEN
Solar/Wind Harmer
132.801
316388AE2-253 GEN
Solar/Wind Harmer
1.941
3146456SLIGO L269
Solar/Wind Harmer
-0.029
316246AF1-032 C
Solar/Wind Harmer
0.579
970659AG2-427 GEN
Solar/Wind Harmer
15.161
316381AD1-082 GEN
Solar/Wind Harmer
2.616
970661AG2-428 GEN
Solar/Wind Harmer
30.261
316093AE2-104_GEN
Solar/Wind Harmer
8.224
3146516WINFALL
Solar/Wind Harmer
-0.089
3146516WINFALL
Solar/Wind Harmer
-0.028
315800Z1-036_GEN1
Solar/Wind Harmer
6.702
3130156CHOWAN
Solar/Wind Harmer
-0.027
3145663CRESWEL
Solar/Wind Harmer
-0.072
971163AH1-040 GEN
Solar/Wind Harmer
24.203
3143526WINTERP
Solar/Wind Harmer
-0.132
3146206CASHIE
Solar/Wind Harmer
-0.025
971547AH1-271 GEN
Solar/Wind Harmer
6.156
939411AE1-173 GEN
Solar/Wind Harmer
122.514
3145893MURPHYS
Solar/Wind Harmer
-0.096
3145893MURPHYS
Solar/Wind Harmer
0.717
3146173TUNIS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145963POPLR C
Solar/Wind Harmer
-0.023
316174AB2-169 GEN
Solar/Wind Harmer
3.581
3146263WOODLND
Solar/Wind Harmer
-0.023
940641AE2-051 GEN
Solar/Wind Harmer
21.565
3145823KELFORD
Solar/Wind Harmer
-0.023
316023GEN1_S
Solar/Wind Harmer
1.542
316190AA2-174 GEN
Solar/Wind Harmer
0.275
316011AB1-132 GEN
Solar/Wind Harmer
4.668
962571AG1-106 GEN
Solar/Wind Harmer
3.207
960081AF2-299 GEN
Solar/Wind Harmer
2.493
3146293MARTNCO
Solar/Wind Harmer
0.137
316169AC1-164_GENC
Solar/Wind Harmer
34.388
315975AC1-164 GENB
Solar/Wind Harmer
1.178
316314AB2-024 C
Solar/Wind Harmer
3.105
316223AC1-118
Solar/Wind Harmer
0.979
944491AF1-114 GEN
Solar/Wind Harmer
10.62
3141813NORNECK
Solar/Wind Harmer
-0.036
316059AD1-063 C
Solar/Wind Harmer
0.815
962981AG1-147 GEN
Solar/Wind Harmer
15.689
3143873LANEXA
Solar/Wind Harmer
-0.021
3141783LANCAST
Solar/Wind Harmer
-0.021
3141783LANCAST
Solar/Wind Harmer
-0.014
3138133OCRAN
Solar/Wind Harmer
-0.011
3141913WHIT STONE
Solar/Wind Harmer
-0.036
315662AE1-191 GEN
Solar/Wind Harmer
4.296
315666AE1-190 GEN
Solar/Wind Harmer
1.074
957601AF2-054 GEN
Solar/Wind Harmer
1.064
3141873WAN 176
Solar/Wind Harmer
-0.007
3142433PROV 92
Adder
0.606
3142433PROV 92
Adder
0.606
971167AH1-042 GEN
Solar/Wind Harmer
33.529
957831AF2-077 GEN
Solar/Wind Harmer
1.033
3138283WHITEMARSH
Solar/Wind Harmer
0.053
316132AB2-190 GEN1
Solar/Wind Harmer
3.204
316369SG1_INVT
Solar/Wind Harmer
5.606
972265AH1-717 GEN
Adder
21.338
3151201GRAVEL4
Adder
20.003
3151191GRAVEL3
Adder
19.75
3151211GRAVEL5
Adder
19.75
971445AH1-216 GEN
Solar/Wind Harmer
18.761
971285AH1-108 GEN
Adder
2.006
3152611GOSPORTB
Adder
3.315
3152621GOSPORTC
Adder
2.813
3152601GOSPORTA
Adder
2.595
3151081ELIZAR1
Adder
23.856
3151091ELIZAR2
Adder
23.441
957871AF2-081 GEN
Solar/Wind Harmer
14.371
319010AE1-072 C
Solar/Wind Harmer
5.791
3146406KITTY HAWK
Solar/Wind Harmer
0.024
316305AF2-043 C
Solar/Wind Harmer
0.862
315833AF1-017_GEN
Solar/Wind Harmer
5.389
316349AD2-085 GEN
Solar/Wind Harmer
2.524
316311AC2-079 GEN
Solar/Wind Harmer
14.311
315835AF2-110_GEN
Solar/Wind Harmer
3.536
313526AB2-022
Solar/Wind Harmer
0.762
3146486SUNBURY
Solar/Wind Harmer
-0.028
3146486SUNBURY
Solar/Wind Harmer
-0.028
316321Z2-027
Solar/Wind Harmer
0.757
3146396TANGLEW
Solar/Wind Harmer
0.516
3145176PASQUOTANK
Solar/Wind Harmer
-0.017
3143316POE
Solar/Wind Harmer
-0.107
315611Z1-036_GEN2
Solar/Wind Harmer
6.702
3130156CHOWAN
Solar/Wind Harmer
-0.027
3130156CHOWAN
Solar/Wind Harmer
-0.027
315816AE2-034 GEN
Solar/Wind Harmer
2.089
316233AE1-074 FULL
Solar/Wind Harmer
0.687
971281AH1-106 GEN
Solar/Wind Harmer
4.151
971283AH1-107 GEN
Solar/Wind Harmer
4.151
972189AH1-679 GEN
Adder
3.806
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
315732AD1-074 GEN1
Solar/Wind Harmer
5.066
315733AD1-074 GEN2
Solar/Wind Harmer
5.066
315735AD1-075 GEN1
Solar/Wind Harmer
2.534
3146206CASHIE
Solar/Wind Harmer
-0.025
970601AG2-382 GEN
Solar/Wind Harmer
10.772
965291AG1-394 GEN
Solar/Wind Harmer
2.166
316318V4-068
Solar/Wind Harmer
0.602
3145893MURPHYS
Solar/Wind Harmer
-0.065
3145893MURPHYS
Solar/Wind Harmer
-0.024
316315AB2-025 C
Solar/Wind Harmer
0.651
315814AE2-033 C
Solar/Wind Harmer
22.406
3145513AHOSKIE
Solar/Wind Harmer
0.207
961941AG1-037 GEN
Solar/Wind Harmer
0.179
3145513AHOSKIE
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
3146043SEABORD
Solar/Wind Harmer
-0.023
315607AA1-063A GEN
Solar/Wind Harmer
2.323
315652AC1-086 GEN
Solar/Wind Harmer
25.099
3146033SCOT NK
Solar/Wind Harmer
-0.089
946281AF1-292 GEN
Solar/Wind Harmer
0.496
316087AB2-174 GEN
Solar/Wind Harmer
3.158
3137643SOCKMAN
Solar/Wind Harmer
-0.088
3145796HORNRTN
Solar/Wind Harmer
-0.07
3145796HORNRTN
Solar/Wind Harmer
-0.009
316005AA1-067
Solar/Wind Harmer
0.436
3145746EVERETS
Solar/Wind Harmer
-0.085
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
970181AG2-120 GEN
Solar/Wind Harmer
2.826
957861AF2-080 GEN
Solar/Wind Harmer
9.177
941031AE2-094 GEN
Solar/Wind Harmer
39.278
944011AF1-069 GEN
Solar/Wind Harmer
12.307
316420AA1-050 GEN
Solar/Wind Harmer
2.365
970673AG2-436 GEN
Solar/Wind Harmer
43.507
970673AG2-436 GEN
Solar/Wind Harmer
22.029
971967AH1-528 GEN
Solar/Wind Harmer
38.619
3145573BETHELC
Solar/Wind Harmer
-0.02
3145573BETHELC
Solar/Wind Harmer
-0.02
316319Z2-044 C
Solar/Wind Harmer
1.123
970831AG2-522 GEN
Solar/Wind Harmer
10.164
970085AG2-068 GEN
Solar/Wind Harmer
12.433
970581AG2-369 GEN
Solar/Wind Harmer
10.692
3151881LOWMORC
Adder
1.506
3151881LOWMORC
Adder
1.482
3151861LOWMORA
Adder
1.458
972205AH1-687 GEN
Adder
6.025
316164AC1-076 GEN
Solar/Wind Helper
1.309
3141426STAFORD
Solar/Wind Helper
0.058
316411AF1-147_GEN1
Solar/Wind Helper
0.832
316415AF1-147_GEN2
Solar/Wind Helper
0.832
3138216PACIFIC
Solar/Wind Helper
0.041
3145783HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.072
3145796HORNRTN
Solar/Wind Harmer
-0.022
316212AC1-099_GEN
Solar/Wind Harmer
1.893
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
3143226MDLTHAN
Solar/Wind Harmer
-0.021
971795AH1-408 GEN
Solar/Wind Harmer
16.09
3147043LAWRENC
Adder
1.701
316494AC1-189 GEN
Solar/Wind Harmer
2.257
315722AD1-056 GEN
Solar/Wind Harmer
2.178
961671AG1-007 GEN
Solar/Wind Harmer
0.259
3146083TARBORO
Solar/Wind Harmer
-0.02
3145493TOT1
Solar/Wind Harmer
0.608
3146233WITAKRS
Solar/Wind Harmer
-0.08
316129AC1-054 GEN
Solar/Wind Harmer
1.766
971065AG2-659 GEN
Solar/Wind Harmer
9.983
970919AG2-571 GEN
Solar/Wind Harmer
6.312
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316359AB2-059 GEN
Solar/Wind Harmer
2.683
316049AB1-081 GEN
Solar/Wind Harmer
2.147
3142053HEARTS
Solar/Wind Harmer
0.234
970087AG2-069 GEN
Solar/Wind Harmer
18.65
3144293JTRSVLE
Adder
0.514
316045AC1-158 PL2
Solar/Wind Helper
5.315
316006AB2-029 C
Solar/Wind Helper
0.12
316254AC1-120 GEN1
Solar/Wind Helper
1.098
957481AF2-042 GEN
Solar/Wind Harmer
44.546
970661AG2-428 GEN
Solar/Wind Harmer
5.363
316320Y1-086
Solar/Wind Harmer
1.655
316435W1029_GEN3
Solar/Wind Harmer
5.043
3146516WINFALL
Solar/Wind Harmer
-0.028
3146626S HERTFORD
Solar/Wind Harmer
-0.027
3145273HOLLAND
Solar/Wind Harmer
-0.02
3146376EDENTON
Solar/Wind Harmer
-0.027
315614AA2-178 GEN
Solar/Wind Harmer
2.785
971157AH1-035 GEN
Solar/Wind Harmer
3.146
315737AD1-076 GEN
Solar/Wind Harmer
4.761
3146206CASHIE
Solar/Wind Harmer
-0.025
3156081AA2-088 GEN
Solar/Wind Harmer
7.981
3145893MURPHYS
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
-0.024
957521AF2-046 GEN
Solar/Wind Harmer
18.965
961681AG1-008 GEN
Solar/Wind Harmer
18.965
3156021HOLLOMANSOL
Solar/Wind Harmer
3.235
3146173TUNIS
Solar/Wind Harmer
-0.024
316463AE2-346 GEN
Solar/Wind Harmer
0.385
316140AB2-099
Solar/Wind Harmer
0.16
962331AG1-082 GEN
Solar/Wind Harmer
2.97
3145963POPLR C
Solar/Wind Harmer
-0.023
971781AH1-399 GEN
Solar/Wind Harmer
1.433
3146263WOODLND
Solar/Wind Harmer
-0.023
316317KELFORD C
Solar/Wind Harmer
1.082
3145823KELFORD
Solar/Wind Harmer
-0.023
316365GEN2_N
Solar/Wind Harmer
1.542
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
966621AG1-532 GEN
Solar/Wind Harmer
0.45
3145933PARMELE
Solar/Wind Harmer
-0.022
966801AG1-551 GEN
Solar/Wind Harmer
2.768
313506AB2-031 GEN
Solar/Wind Harmer
1.778
3142296MT RD221
50/50
1.125
3150341NORNECKC1
50/50
3.581
3150341NORNECKC1
50/50
3.552
963611AG1-210 GEN
50/50
1.146
3150691DARBY 3
50/50
24.142
3150701DARBY 4
50/50
24.085
3150681DARBY 2
50/50
24.057
3150671DARBY 1
50/50
24.029
316075AC2-137 C
Solar/Wind Harmer
1.004
316077AC2-138 C
Solar/Wind Harmer
0.764
958261AF2-120 GEN
Solar/Wind Harmer
13.96
316487AF1-042 GEN
Solar/Wind Harmer
4.732
316441AF1-014 GEN
Solar/Wind Harmer
2.405
3142946ENON
Solar/Wind Harmer
-0.004
3142366NRTHEST
Adder
1.019
966871AG1-558 GEN
Solar/Wind Harmer
1.032
966871AG1-558 GEN
Solar/Wind Harmer
0.353
316033AB2-134 GEN
Solar/Wind Harmer
10.118
315697AD1-025 GEN
Solar/Wind Harmer
6.346
944641AF1-129 GEN
Adder
130.968
316240AF1-291 C
Solar/Wind Harmer
0.918
316236AE1-162_GEN
Solar/Wind Harmer
0.912
316036AC1-147 C
Solar/Wind Harmer
0.789
3150991CHESPKB
Adder
2.727
3150991CHESPKB
Adder
2.662
316316AC1-027 C
Solar/Wind Harmer
0.894
3142956BIRDNECK
Solar/Wind Harmer
1.562
316185AD1-033 GEN
Solar/Wind Harmer
3.061
3145506HICKORY
Solar/Wind Harmer
-0.115
3145506HICKORY
Solar/Wind Harmer
-0.069
3145506HICKORY
Solar/Wind Harmer
-0.017
316339AD2-160 GEN
Solar/Wind Harmer
1.941
316018AA1-139 ULT2
Solar/Wind Harmer
2.462
316017AA1-139 ULT1
Solar/Wind Harmer
2.326
3137176SLIGO L2192
Solar/Wind Harmer
-0.113
3146456SLIGO L269
Solar/Wind Harmer
3.385
3130086AYDLETT
Solar/Wind Harmer
-0.114
970657AG2-426 GEN
Solar/Wind Harmer
8.908
970657AG2-426 GEN
Solar/Wind Harmer
1.863
3146386ELIZ CT
Solar/Wind Harmer
-0.028
316431W1029_GEN1
Solar/Wind Harmer
5.043
316433W1029_GEN2
Solar/Wind Harmer
5.043
3145796HORNRTN
Solar/Wind Harmer
-0.087
3145796HORNRTN
Solar/Wind Harmer
-0.022
316210AC1-098 GEN
Solar/Wind Harmer
3.408
3145746EVERETS
Solar/Wind Harmer
-0.021
3145746EVERETS
Solar/Wind Harmer
-0.021
3147043LAWRENC
Solar/Wind Harmer
-0.013
315724AD1-057 GEN
Solar/Wind Harmer
1.198
316327AA2-057 GEN
Solar/Wind Harmer
2.095
3146073TAR RVR
Solar/Wind Harmer
-0.02
3146083TARBORO
Solar/Wind Harmer
-0.02
3146233WITAKRS
Solar/Wind Harmer
0.425
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.013
970917AG2-570 GEN
Solar/Wind Harmer
49.866
961601AG1-000A GEN
Solar/Wind Harmer
7.929
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3144293JTRSVLE
Adder
0.514
3151861LOWMORA
Adder
1.518
316044AC1-158 PL1
Solar/Wind Helper
1.66
316450AC1-158 RIC
Solar/Wind Helper
0.443
3141196NOKESVL
Solar/Wind Helper
1.065
227287AC2-120 GEN
Solar/Wind Helper
0.341
226910AB2-157 C
Solar/Wind Helper
0.014
316170AC1-121 GEN2
Solar/Wind Helper
0.366
3146516WINFALL
Solar/Wind Harmer
-0.028
3146516WINFALL
Solar/Wind Harmer
-0.028
3146516WINFALL
Solar/Wind Harmer
-0.028
3146626S HERTFORD
Solar/Wind Harmer
-0.027
3146626S HERTFORD
Solar/Wind Harmer
-0.027
3146376EDENTON
Solar/Wind Harmer
0.791
3146376EDENTON
Solar/Wind Harmer
0.791
315742AE1-103 GEN
Solar/Wind Harmer
2.781
3143526WINTERP
Solar/Wind Harmer
-0.132
316065AD1-022 GEN
Solar/Wind Harmer
12.389
3145893MURPHYS
Solar/Wind Harmer
0.674
3145893MURPHYS
Solar/Wind Harmer
-0.043
3144356SAPONY
Solar/Wind Harmer
0.841
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
316468AD1-105 GEN
Solar/Wind Harmer
2.59
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
316426AA2-053 GEN
Solar/Wind Harmer
2.259
3145933PARMELE
Solar/Wind Harmer
-0.044
3145933PARMELE
Solar/Wind Harmer
-0.022
316181AB2-040 GEN
Solar/Wind Harmer
3.086
3145593CAROLNA
Solar/Wind Harmer
-0.022
3145593CAROLNA
Solar/Wind Harmer
-0.022
966811AG1-552 GEN
Solar/Wind Harmer
2.484
3145593CAROLNA
Solar/Wind Harmer
0.183
3145783HORNRTN
Solar/Wind Harmer
2.608
3145783HORNRTN
Solar/Wind Harmer
2.086
3145783HORNRTN
Solar/Wind Harmer
0.652
3145783HORNRTN
Solar/Wind Harmer
0.261
3145796HORNRTN
Solar/Wind Harmer
-0.065
971223AH1-071 GEN
Solar/Wind Harmer
2.682
316274AC1-208 GEN
Solar/Wind Harmer
2.31
972185AH1-677 GEN
Adder
10.284
3145493TOT1
Solar/Wind Harmer
0.317
3145453TOT5
Solar/Wind Harmer
0.19
3145603CNETO
Solar/Wind Harmer
0.127
972187AH1-678 GEN
Adder
5.178
970933AG2-581 GEN
Solar/Wind Harmer
18.958
961601AG1-000A GEN
Solar/Wind Harmer
7.83
316263AC1-034 GEN
Solar/Wind Harmer
9.328
3144293JTRSVLE
Adder
0.514
3144293JTRSVLE
Adder
0.433
316447AC1-158 HLD
Solar/Wind Helper
3.654
226929AD2-058 GEN
Solar/Wind Helper
0.101
315651AD1-115 GEN
Solar/Wind Helper
0.812
970099AG2-077 GEN
Solar/Wind Harmer
17.818
CPLELTFEXP_CPLE->PJM
CLTF
11.373
CBM West 2LTFEXP_CBM-W2->PJM
CBM
57.092
LAGNLTFEXP_LAGN->PJM
CLTF
10.202
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.271
TVALTFEXP_TVA->PJM
CLTF
5.187
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.767
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.174
MECLTFEXP_MEC->PJM
CLTF
5.701
SIGELTFEXP_SIGE->PJM
CLTF
0.178
NYPJM->LTFIMP_NY
CLTF
3.519
LGEELTFEXP_LGEE->PJM
CLTF
2.238
WECLTFEXP_WEC->PJM
CLTF
1.128
AG2-052LTFEXP_AG2-052->PJM
LTF
0.063
AH1-155LTFEXP_AH1-155->PJM
LTF
0.094

Details for AD2-074 TAP-AG1-135 TP 115.0 kV Ckt 1 line l/o DVP_P4-2: 65T1021_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AD2-074 TAP-AG1-135 TP 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 65T1021_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.03 %
Rating:249.0 MVA
Rating Type:C
MVA to Mitigate:254.04
MW Contribution:19.99
Bus #Bus NameTypeMW Contribution
961951AG1-038 GEN
Solar/Wind Harmer
16.643
962981AG1-147 GEN
Solar/Wind Harmer
55.278
970575AG2-366 GEN
50/50
19.992
316484AD2-074 GEN
Solar/Wind Harmer
31.807
962971AG1-146 GEN
Solar/Wind Harmer
23.69
970009AG2-005 GEN
Solar/Wind Harmer
15.794
316487AF1-042 GEN
Solar/Wind Harmer
16.643
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.023
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.07
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.014
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.105
NYPJM->LTFIMP_NY
CLTF
0.022
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.023

Details for AD2-074 TAP-AG1-135 TP 115.0 kV Ckt 1 line l/o DVP_P4-4: LANCAS SC392_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AD2-074 TAP-AG1-135 TP 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-4: LANCAS SC392_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.0 %
Rating:249.0 MVA
Rating Type:C
MVA to Mitigate:253.98
MW Contribution:19.99
Bus #Bus NameTypeMW Contribution
962981AG1-147 GEN
Solar/Wind Harmer
55.278
316487AF1-042 GEN
Solar/Wind Harmer
16.643
970575AG2-366 GEN
50/50
19.992
316484AD2-074 GEN
Solar/Wind Harmer
31.807
962971AG1-146 GEN
Solar/Wind Harmer
23.69
970009AG2-005 GEN
Solar/Wind Harmer
15.794
961951AG1-038 GEN
Solar/Wind Harmer
16.643
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.023
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.07
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.014
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.105
NYPJM->LTFIMP_NY
CLTF
0.022
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.023

Details for AD2-074 TAP-AG1-135 TP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2016-85_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
AD2-074 TAP-AG1-135 TP 115.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2016-85_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.5 %
Rating:249.0 MVA
Rating Type:C
MVA to Mitigate:250.25
MW Contribution:12.64
Bus #Bus NameTypeMW Contribution
962981AG1-147 GEN
Solar/Wind Harmer
34.948
3141783LANCAST
Solar/Wind Harmer
-0.042
3141783LANCAST
Solar/Wind Harmer
-0.028
3138133OCRAN
Solar/Wind Harmer
-0.02
3141913WHIT STONE
Solar/Wind Harmer
-0.063
315662AE1-191 GEN
Solar/Wind Harmer
6.607
315666AE1-190 GEN
Solar/Wind Harmer
1.652
957601AF2-054 GEN
Solar/Wind Harmer
1.64
3141873WAN 176
Solar/Wind Harmer
-0.011
957831AF2-077 GEN
Solar/Wind Harmer
0.827
3138283WHITEMARSH
Solar/Wind Harmer
0.043
3141813NORNECK
Solar/Wind Helper
0.269
961951AG1-038 GEN
Solar/Wind Harmer
11.269
3138133OCRAN
Solar/Wind Harmer
-0.039
970575AG2-366 GEN
50/50
12.64
316484AD2-074 GEN
Solar/Wind Harmer
21.536
970009AG2-005 GEN
Solar/Wind Harmer
10.694
962971AG1-146 GEN
Solar/Wind Harmer
14.978
316203AE2-005 GEN
Solar/Wind Harmer
23.11
316280AD1-041 GEN
Solar/Wind Harmer
4.129
316156AD2-030 GEN
Solar/Wind Harmer
1.463
3141873WAN 176
Solar/Wind Harmer
6.504
316404AE1-155 C
Solar/Wind Helper
4.711
316487AF1-042 GEN
Solar/Wind Harmer
11.269
316441AF1-014 GEN
Solar/Wind Harmer
3.695
316077AC2-138 C
Solar/Wind Helper
0.253
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.018
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.054
CPLELTFEXP_CPLE->PJM
CLTF
0.123
MDUPJM->LTFIMP_MDU
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.009
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.221
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.005
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.051
NYPJM->LTFIMP_NY
CLTF
0.07

Details for AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P4-2: 65T1021_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 65T1021_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:184.88 %
Rating:249.0 MVA
Rating Type:C
MVA to Mitigate:460.35
MW Contribution:19.98
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
31.973
961951AG1-038 GEN
Solar/Wind Harmer
16.636
962861AG1-135 GEN
Solar/Wind Harmer
47.359
962981AG1-147 GEN
Solar/Wind Harmer
55.253
970575AG2-366 GEN
50/50
19.983
316484AD2-074 GEN
Solar/Wind Harmer
31.793
316404AE1-155 C
Solar/Wind Harmer
24.362
962971AG1-146 GEN
Solar/Wind Harmer
23.68
970009AG2-005 GEN
Solar/Wind Harmer
15.786
316487AF1-042 GEN
Solar/Wind Harmer
16.636
958261AF2-120 GEN
Solar/Wind Harmer
48.938
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.048
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.148
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.03
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.221
NYPJM->LTFIMP_NY
CLTF
0.047
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.049

Details for AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P4-4: LANCAS SC392_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-4: LANCAS SC392_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:184.87 %
Rating:249.0 MVA
Rating Type:C
MVA to Mitigate:460.32
MW Contribution:19.98
Bus #Bus NameTypeMW Contribution
962981AG1-147 GEN
Solar/Wind Harmer
55.253
970575AG2-366 GEN
50/50
19.983
316484AD2-074 GEN
Solar/Wind Harmer
31.793
316404AE1-155 C
Solar/Wind Harmer
24.362
962971AG1-146 GEN
Solar/Wind Harmer
23.68
970009AG2-005 GEN
Solar/Wind Harmer
15.786
316487AF1-042 GEN
Solar/Wind Harmer
16.636
958261AF2-120 GEN
Solar/Wind Harmer
48.938
966661AG1-536 GEN
50/50
31.973
961951AG1-038 GEN
Solar/Wind Harmer
16.636
962861AG1-135 GEN
Solar/Wind Harmer
47.359
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.048
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.148
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.03
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.221
NYPJM->LTFIMP_NY
CLTF
0.047
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.049

Details for AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 65_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:175.73 %
Rating:203.98 MVA
Rating Type:B
MVA to Mitigate:358.46
MW Contribution:19.98
Bus #Bus NameTypeMW Contribution
958261AF2-120 GEN
Solar/Wind Harmer
37.168
966661AG1-536 GEN
50/50
31.973
962861AG1-135 GEN
Solar/Wind Harmer
35.969
970575AG2-366 GEN
50/50
19.983
316404AE1-155 C
Solar/Wind Harmer
0.253
962971AG1-146 GEN
Solar/Wind Harmer
17.985
970009AG2-005 GEN
Solar/Wind Harmer
8.393
962981AG1-147 GEN
Solar/Wind Harmer
41.964
970327AG2-215 GEN
Solar/Wind Harmer
36.888
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.048
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.148
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.03
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.221
NYPJM->LTFIMP_NY
CLTF
0.047
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.049

Details for AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P4-2: 8962_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 8962_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:166.49 %
Rating:249.0 MVA
Rating Type:C
MVA to Mitigate:414.56
MW Contribution:19.98
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
31.97
961951AG1-038 GEN
Solar/Wind Harmer
16.635
3138133OCRAN
Solar/Wind Harmer
-0.075
962861AG1-135 GEN
Solar/Wind Harmer
47.356
3141913WHIT STONE
Solar/Wind Harmer
-0.126
3141783LANCAST
Solar/Wind Harmer
-0.075
3141783LANCAST
Solar/Wind Harmer
-0.05
3138133OCRAN
Solar/Wind Harmer
-0.038
962981AG1-147 GEN
Solar/Wind Harmer
55.249
970575AG2-366 GEN
50/50
19.982
316484AD2-074 GEN
Solar/Wind Harmer
31.791
316404AE1-155 C
Solar/Wind Harmer
24.361
962971AG1-146 GEN
Solar/Wind Harmer
23.678
970009AG2-005 GEN
Solar/Wind Harmer
15.785
316487AF1-042 GEN
Solar/Wind Harmer
16.635
958261AF2-120 GEN
Solar/Wind Harmer
48.935
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.051
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.16
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.032
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.238
NYPJM->LTFIMP_NY
CLTF
0.051
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.053

Details for AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P4-5: L262_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: L262_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:166.49 %
Rating:249.0 MVA
Rating Type:C
MVA to Mitigate:414.56
MW Contribution:19.98
Bus #Bus NameTypeMW Contribution
970575AG2-366 GEN
50/50
19.982
316484AD2-074 GEN
Solar/Wind Harmer
31.791
316404AE1-155 C
Solar/Wind Harmer
24.361
962971AG1-146 GEN
Solar/Wind Harmer
23.678
970009AG2-005 GEN
Solar/Wind Harmer
15.785
316487AF1-042 GEN
Solar/Wind Harmer
16.635
958261AF2-120 GEN
Solar/Wind Harmer
48.935
3141913WHIT STONE
Solar/Wind Harmer
-0.126
3141783LANCAST
Solar/Wind Harmer
-0.075
3141783LANCAST
Solar/Wind Harmer
-0.05
3138133OCRAN
Solar/Wind Harmer
-0.038
962981AG1-147 GEN
Solar/Wind Harmer
55.249
966661AG1-536 GEN
50/50
31.97
961951AG1-038 GEN
Solar/Wind Harmer
16.635
3138133OCRAN
Solar/Wind Harmer
-0.075
962861AG1-135 GEN
Solar/Wind Harmer
47.356
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.051
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.16
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.032
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.238
NYPJM->LTFIMP_NY
CLTF
0.051
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.053

Details for AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P4-2: 17662_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 17662_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:166.49 %
Rating:249.0 MVA
Rating Type:C
MVA to Mitigate:414.56
MW Contribution:19.98
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
31.97
961951AG1-038 GEN
Solar/Wind Harmer
16.635
3138133OCRAN
Solar/Wind Harmer
-0.075
962861AG1-135 GEN
Solar/Wind Harmer
47.356
3141913WHIT STONE
Solar/Wind Harmer
-0.126
3141783LANCAST
Solar/Wind Harmer
-0.075
3141783LANCAST
Solar/Wind Harmer
-0.05
3138133OCRAN
Solar/Wind Harmer
-0.038
962981AG1-147 GEN
Solar/Wind Harmer
55.249
970575AG2-366 GEN
50/50
19.982
316484AD2-074 GEN
Solar/Wind Harmer
31.791
316404AE1-155 C
Solar/Wind Harmer
24.361
962971AG1-146 GEN
Solar/Wind Harmer
23.678
970009AG2-005 GEN
Solar/Wind Harmer
15.785
316487AF1-042 GEN
Solar/Wind Harmer
16.635
958261AF2-120 GEN
Solar/Wind Harmer
48.935
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.051
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.16
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.032
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.238
NYPJM->LTFIMP_NY
CLTF
0.051
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.053

Details for AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2016-85_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2016-85_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:165.25 %
Rating:249.0 MVA
Rating Type:C
MVA to Mitigate:411.48
MW Contribution:12.63
Bus #Bus NameTypeMW Contribution
962981AG1-147 GEN
Solar/Wind Harmer
34.924
3141783LANCAST
Solar/Wind Harmer
-0.042
3141783LANCAST
Solar/Wind Harmer
-0.028
3138133OCRAN
Solar/Wind Harmer
-0.02
3141913WHIT STONE
Solar/Wind Harmer
-0.063
315662AE1-191 GEN
Solar/Wind Harmer
6.6
315666AE1-190 GEN
Solar/Wind Harmer
1.65
957601AF2-054 GEN
Solar/Wind Harmer
1.638
3141873WAN 176
Solar/Wind Harmer
-0.011
957831AF2-077 GEN
Solar/Wind Harmer
0.825
3138283WHITEMARSH
Solar/Wind Harmer
0.042
3141813NORNECK
Solar/Wind Helper
0.27
966661AG1-536 GEN
50/50
23.966
962861AG1-135 GEN
Solar/Wind Harmer
34.588
961951AG1-038 GEN
Solar/Wind Harmer
11.261
3138133OCRAN
Solar/Wind Harmer
-0.039
970575AG2-366 GEN
50/50
12.631
316404AE1-155 C
Solar/Wind Harmer
18.261
316484AD2-074 GEN
Solar/Wind Harmer
21.522
970009AG2-005 GEN
Solar/Wind Harmer
10.687
962971AG1-146 GEN
Solar/Wind Harmer
14.967
316203AE2-005 GEN
Solar/Wind Harmer
23.086
316280AD1-041 GEN
Solar/Wind Harmer
4.125
316156AD2-030 GEN
Solar/Wind Harmer
1.462
3141873WAN 176
Solar/Wind Harmer
6.498
958261AF2-120 GEN
Solar/Wind Harmer
36.683
316487AF1-042 GEN
Solar/Wind Harmer
11.261
316441AF1-014 GEN
Solar/Wind Harmer
3.691
316077AC2-138 C
Solar/Wind Helper
0.254
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.043
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.132
CPLELTFEXP_CPLE->PJM
CLTF
0.081
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.104
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.168
NYPJM->LTFIMP_NY
CLTF
0.095

Details for AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1021_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1021_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:155.02 %
Rating:203.98 MVA
Rating Type:B
MVA to Mitigate:316.21
MW Contribution:19.98
Bus #Bus NameTypeMW Contribution
958261AF2-120 GEN
Solar/Wind Harmer
37.166
966661AG1-536 GEN
50/50
31.97
3138133OCRAN
Solar/Wind Harmer
0.674
962861AG1-135 GEN
Solar/Wind Harmer
35.967
970575AG2-366 GEN
50/50
19.982
316404AE1-155 C
Solar/Wind Harmer
0.253
962971AG1-146 GEN
Solar/Wind Harmer
17.983
970009AG2-005 GEN
Solar/Wind Harmer
8.392
3141913WHIT STONE
Solar/Wind Harmer
1.123
3141783LANCAST
Solar/Wind Harmer
0.674
3141783LANCAST
Solar/Wind Harmer
0.45
3138133OCRAN
Solar/Wind Harmer
0.337
962981AG1-147 GEN
Solar/Wind Harmer
41.961
970327AG2-215 GEN
Solar/Wind Harmer
36.886
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.051
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.16
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.032
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.238
NYPJM->LTFIMP_NY
CLTF
0.051
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.053

Details for AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P2-2: HARMONY V B2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: HARMONY V B2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:154.95 %
Rating:249.0 MVA
Rating Type:C
MVA to Mitigate:385.83
MW Contribution:12.86
Bus #Bus NameTypeMW Contribution
962981AG1-147 GEN
Solar/Wind Harmer
35.562
3141783LANCAST
Solar/Wind Harmer
-0.042
3141783LANCAST
Solar/Wind Harmer
-0.028
3138133OCRAN
Solar/Wind Harmer
-0.02
3141913WHIT STONE
Solar/Wind Harmer
-0.064
315662AE1-191 GEN
Solar/Wind Harmer
5.353
315666AE1-190 GEN
Solar/Wind Harmer
1.338
3143873LANEXA
Solar/Wind Harmer
-0.004
3141813NORNECK
Solar/Wind Helper
0.245
970575AG2-366 GEN
50/50
12.862
3141843SHACKLE
50/50
1.719
316404AE1-155 C
Solar/Wind Harmer
18.54
316484AD2-074 GEN
Solar/Wind Harmer
21.888
970009AG2-005 GEN
Solar/Wind Harmer
10.868
962971AG1-146 GEN
Solar/Wind Harmer
15.241
316280AD1-041 GEN
Solar/Wind Harmer
3.345
316203AE2-005 GEN
Solar/Wind Harmer
15.121
966661AG1-536 GEN
50/50
24.332
3141843SHACKLE
50/50
1.719
962861AG1-135 GEN
Solar/Wind Harmer
35.131
961951AG1-038 GEN
Solar/Wind Harmer
11.453
3138133OCRAN
Solar/Wind Harmer
-0.04
971777AH1-397 GEN
Solar/Wind Harmer
4.188
958261AF2-120 GEN
Solar/Wind Harmer
37.243
316487AF1-042 GEN
Solar/Wind Harmer
11.453
316441AF1-014 GEN
Solar/Wind Harmer
2.418
316077AC2-138 C
Solar/Wind Helper
0.23
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.043
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.132
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.012
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.186
NYPJM->LTFIMP_NY
CLTF
0.068
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.013

Details for AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2016-85_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2016-85_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:144.71 %
Rating:249.0 MVA
Rating Type:C
MVA to Mitigate:360.32
MW Contribution:12.63
Bus #Bus NameTypeMW Contribution
962981AG1-147 GEN
Solar/Wind Harmer
34.932
3141783LANCAST
Solar/Wind Harmer
-0.042
3141783LANCAST
Solar/Wind Harmer
-0.028
3138133OCRAN
Solar/Wind Harmer
-0.02
3141913WHIT STONE
Solar/Wind Harmer
-0.063
315662AE1-191 GEN
Solar/Wind Harmer
6.602
315666AE1-190 GEN
Solar/Wind Harmer
1.651
957601AF2-054 GEN
Solar/Wind Harmer
1.638
3141873WAN 176
Solar/Wind Harmer
-0.011
957831AF2-077 GEN
Solar/Wind Harmer
0.826
3138283WHITEMARSH
Solar/Wind Harmer
0.043
3141813NORNECK
Solar/Wind Helper
0.269
970575AG2-366 GEN
50/50
12.634
316404AE1-155 C
Solar/Wind Harmer
18.265
316484AD2-074 GEN
Solar/Wind Harmer
21.527
970009AG2-005 GEN
Solar/Wind Harmer
10.689
962971AG1-146 GEN
Solar/Wind Harmer
14.971
316280AD1-041 GEN
Solar/Wind Harmer
4.126
316156AD2-030 GEN
Solar/Wind Harmer
1.462
3141873WAN 176
Solar/Wind Harmer
6.5
966661AG1-536 GEN
50/50
23.971
962861AG1-135 GEN
Solar/Wind Harmer
34.595
961951AG1-038 GEN
Solar/Wind Harmer
11.264
3138133OCRAN
Solar/Wind Harmer
-0.039
958261AF2-120 GEN
Solar/Wind Harmer
36.69
316487AF1-042 GEN
Solar/Wind Harmer
11.264
316077AC2-138 C
Solar/Wind Helper
0.253
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.034
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.106
CPLELTFEXP_CPLE->PJM
CLTF
0.095
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.142
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.129
NYPJM->LTFIMP_NY
CLTF
0.087

Details for AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P2-2: LANEXA B1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: LANEXA B1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:127.12 %
Rating:249.0 MVA
Rating Type:C
MVA to Mitigate:316.52
MW Contribution:9.81
Bus #Bus NameTypeMW Contribution
970575AG2-366 GEN
50/50
9.811
3141843SHACKLE
50/50
1.276
316404AE1-155 C
Solar/Wind Harmer
16.022
316484AD2-074 GEN
Solar/Wind Harmer
17.633
970009AG2-005 GEN
Solar/Wind Harmer
8.755
962971AG1-146 GEN
Solar/Wind Harmer
11.626
316203AE2-005 GEN
Solar/Wind Harmer
11.148
316280AD1-041 GEN
Solar/Wind Harmer
1.992
316156AD2-030 GEN
Solar/Wind Harmer
0.706
962981AG1-147 GEN
Solar/Wind Harmer
27.127
3141783LANCAST
Solar/Wind Harmer
-0.029
3141783LANCAST
Solar/Wind Harmer
-0.019
3138133OCRAN
Solar/Wind Harmer
-0.012
3141913WHIT STONE
Solar/Wind Harmer
-0.038
315662AE1-191 GEN
Solar/Wind Harmer
3.187
315666AE1-190 GEN
Solar/Wind Harmer
0.797
957601AF2-054 GEN
Solar/Wind Harmer
0.791
3141873WAN 176
Solar/Wind Harmer
-0.005
957831AF2-077 GEN
Solar/Wind Harmer
0.402
3138283WHITEMARSH
Solar/Wind Harmer
0.021
316059AD1-063 C
Solar/Wind Harmer
0.256
3141813NORNECK
Solar/Wind Helper
0.353
958261AF2-120 GEN
Solar/Wind Harmer
32.184
316487AF1-042 GEN
Solar/Wind Harmer
9.226
316441AF1-014 GEN
Solar/Wind Harmer
1.782
316077AC2-138 C
Solar/Wind Helper
0.332
966661AG1-536 GEN
50/50
21.027
3141843SHACKLE
50/50
1.276
962861AG1-135 GEN
Solar/Wind Harmer
29.853
961951AG1-038 GEN
Solar/Wind Harmer
9.226
3138133OCRAN
Solar/Wind Harmer
-0.025
971777AH1-397 GEN
Solar/Wind Harmer
3.109
3141766HARMONY
Solar/Wind Harmer
-0.002
316337AD2-073 GEN
Solar/Wind Helper
0.183
3141873WAN 176
Solar/Wind Harmer
3.138
3141766HARMONY
Solar/Wind Harmer
1.008
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.025
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.077
CPLELTFEXP_CPLE->PJM
CLTF
0.083
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.134
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.091
NYPJM->LTFIMP_NY
CLTF
0.073

Details for AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.07 %
Rating:203.98 MVA
Rating Type:A
MVA to Mitigate:230.65
MW Contribution:9.27
Bus #Bus NameTypeMW Contribution
970575AG2-366 GEN
50/50
9.267
3141843SHACKLE
50/50
0.642
315749AE2-041 GEN
50/50
2.872
316404AE1-155 C
Solar/Wind Harmer
0.162
970009AG2-005 GEN
Solar/Wind Harmer
4.456
962971AG1-146 GEN
Solar/Wind Harmer
8.34
316156AD2-030 GEN
Solar/Wind Harmer
0.139
3141873WAN 176
Solar/Wind Harmer
3.327
316280AD1-041 GEN
Solar/Wind Harmer
0.003
316203AE2-005 GEN
Solar/Wind Harmer
0
3141766HARMONY
Solar/Wind Harmer
1.077
3141906WESTMOR
Solar/Wind Helper
0.046
315759AF1-018 GEN
50/50
2.872
970327AG2-215 GEN
Solar/Wind Harmer
19.585
962981AG1-147 GEN
Solar/Wind Harmer
19.461
3141783LANCAST
Solar/Wind Harmer
0.235
3141783LANCAST
Solar/Wind Harmer
0.157
3138133OCRAN
Solar/Wind Harmer
0.098
3141913WHIT STONE
Solar/Wind Harmer
0.299
3141873WAN 176
Solar/Wind Harmer
0.037
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
3.533
3138283WHITEMARSH
Solar/Wind Harmer
0.022
316059AD1-063 C
Solar/Wind Harmer
0.001
3141813NORNECK
Solar/Wind Helper
0.37
316223AC1-118
Solar/Wind Helper
0.174
966661AG1-536 GEN
50/50
20.452
3141843SHACKLE
50/50
0.642
962861AG1-135 GEN
Solar/Wind Harmer
21.972
3138133OCRAN
Solar/Wind Harmer
0.197
971777AH1-397 GEN
Solar/Wind Harmer
0.313
3141766HARMONY
Solar/Wind Harmer
0.016
316337AD2-073 GEN
Solar/Wind Helper
0.189
958261AF2-120 GEN
Solar/Wind Harmer
23.775
316077AC2-138 C
Solar/Wind Helper
0.348
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.019
CPLELTFEXP_CPLE->PJM
CLTF
0.088
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.059
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.153
GibsonPJM->LTFIMP_GIBSON
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.065
NYPJM->LTFIMP_NY
CLTF
0.067

Details for AF1-114 TP-6DAHLGREN 230.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AF1-114 TP-6DAHLGREN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.86 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:865.75
MW Contribution:3.79
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
5.221
3142433PROV 92
50/50
0.233
3142433PROV 92
50/50
0.233
944491AF1-114 GEN
Solar/Wind Harmer
18.883
316223AC1-118
Solar/Wind Harmer
1.264
3141813NORNECK
Solar/Wind Harmer
-0.032
962981AG1-147 GEN
Solar/Wind Harmer
10.474
3141783LANCAST
Solar/Wind Harmer
-0.013
3141783LANCAST
Solar/Wind Harmer
-0.008
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.02
957601AF2-054 GEN
Solar/Wind Harmer
0.519
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
2.019
315666AE1-190 GEN
Solar/Wind Harmer
0.505
3150351NORNECKC2
50/50
3.077
970575AG2-366 GEN
50/50
3.788
315749AE2-041 GEN
50/50
5.221
3141843SHACKLE
50/50
0.787
3142433PROV 92
50/50
0.233
3142433PROV 92
50/50
0.233
970737AG2-469 GEN
Solar/Wind Harmer
26.848
3141906WESTMOR
Solar/Wind Harmer
-0.019
316404AE1-155 C
Solar/Wind Harmer
5.369
316484AD2-074 GEN
Solar/Wind Harmer
6.401
970009AG2-005 GEN
Solar/Wind Harmer
3.178
962971AG1-146 GEN
Solar/Wind Harmer
4.489
316156AD2-030 GEN
Solar/Wind Harmer
0.464
3141873WAN 176
Solar/Wind Harmer
2.06
316280AD1-041 GEN
Solar/Wind Harmer
1.262
3141766HARMONY
Solar/Wind Harmer
1.469
316203AE2-005 GEN
Solar/Wind Harmer
6.877
316382AG1-145 C
Solar/Wind Harmer
0.285
3150921YORKTN3
Adder
2.048
3144216WINCHST
Adder
0.297
3142946ENON
Solar/Wind Harmer
-0.003
970293AG2-193 GEN
Solar/Wind Harmer
0.932
3151221GRAVEL6
Adder
4.627
3151171GRAVELC
Adder
0.89
961611AG1-000B GEN
Solar/Wind Harmer
1.491
3145336SMITFLD
Solar/Wind Harmer
-0.003
315778AD1-151 GEN
Solar/Wind Harmer
5.997
970129AG2-093 GEN
Solar/Wind Harmer
3.855
970133AG2-095 GEN
Solar/Wind Harmer
0.758
3144536CHRHLND
Solar/Wind Harmer
-0.001
315773AC2-141 GEN
Solar/Wind Harmer
2.81
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.478
3143096IRON208
Adder
0.246
3143096IRON208
Adder
0.241
3142416OLDCHRC
Solar/Wind Harmer
0.665
944581AF1-123 GEN
Solar/Wind Harmer
29.902
944601AF1-125 GEN
Solar/Wind Harmer
29.435
3146456SLIGO L269
Solar/Wind Harmer
-0.006
971153AH1-033 GEN
Solar/Wind Harmer
0.79
316320Y1-086
Solar/Wind Harmer
0.374
3150351NORNECKC2
50/50
3.026
966661AG1-536 GEN
50/50
7.046
3141843SHACKLE
50/50
0.787
3142433PROV 92
50/50
0.233
3142433PROV 92
50/50
0.233
957971AF2-091 GEN
Solar/Wind Harmer
6.42
972135AH1-637 GEN
Solar/Wind Harmer
5.832
316337AD2-073 GEN
Solar/Wind Harmer
1.054
964211AG1-282 GEN
Solar/Wind Harmer
0.905
3141726DUNNSVL
Solar/Wind Harmer
-0.12
962861AG1-135 GEN
Solar/Wind Harmer
10.198
961951AG1-038 GEN
Solar/Wind Harmer
3.349
3138133OCRAN
Solar/Wind Harmer
-0.012
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.916
3142433PROV 92
Solar/Wind Harmer
-0.051
971317AH1-138 GEN
Solar/Wind Harmer
1.283
316159AE1-175 C
Solar/Wind Harmer
0.254
3138126ROCKLANDING
Solar/Wind Harmer
0.027
944631AF1-128 GEN
Adder
32.493
3151171GRAVELC
Adder
0.677
961611AG1-000B GEN
Solar/Wind Harmer
3.494
316059AD1-063 C
Solar/Wind Harmer
0.373
316314AB2-024 C
Solar/Wind Harmer
1.365
3143873LANEXA
Solar/Wind Harmer
-0.009
957831AF2-077 GEN
Solar/Wind Harmer
0.393
3138283WHITEMARSH
Solar/Wind Harmer
0.02
971167AH1-042 GEN
Solar/Wind Harmer
11.736
315976AC1-164 GENA
Solar/Wind Harmer
10.45
316169AC1-164_GENC
Solar/Wind Harmer
9.028
315975AC1-164 GENB
Solar/Wind Harmer
0.309
972265AH1-717 GEN
Adder
4.942
3151201GRAVEL4
Adder
4.633
3151191GRAVEL3
Adder
4.574
3151211GRAVEL5
Adder
4.574
971445AH1-216 GEN
Solar/Wind Harmer
4.315
316369SG1_INVT
Solar/Wind Harmer
1.245
316132AB2-190 GEN1
Solar/Wind Harmer
0.694
3152611GOSPORTB
Adder
0.752
3152621GOSPORTC
Adder
0.638
3152601GOSPORTA
Adder
0.589
3151081ELIZAR1
Adder
5.409
3151091ELIZAR2
Adder
5.315
316312AB1-027
Solar/Wind Harmer
0.222
316305AF2-043 C
Solar/Wind Harmer
0.196
957871AF2-081 GEN
Solar/Wind Harmer
3.251
319010AE1-072 C
Solar/Wind Harmer
1.31
3146406KITTY HAWK
Solar/Wind Harmer
0.005
313526AB2-022
Solar/Wind Harmer
0.172
315835AF2-110_GEN
Solar/Wind Harmer
0.797
3146486SUNBURY
Solar/Wind Harmer
-0.006
3146486SUNBURY
Solar/Wind Harmer
-0.006
316321Z2-027
Solar/Wind Harmer
0.171
3146396TANGLEW
Solar/Wind Harmer
0.117
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3141426STAFORD
Solar/Wind Helper
0.031
3150341NORNECKC1
50/50
3.178
3150341NORNECKC1
50/50
3.153
963611AG1-210 GEN
50/50
1.017
316077AC2-138 C
Solar/Wind Harmer
0.678
958261AF2-120 GEN
Solar/Wind Harmer
10.785
316487AF1-042 GEN
Solar/Wind Harmer
3.349
316441AF1-014 GEN
Solar/Wind Harmer
1.1
316075AC2-137 C
Solar/Wind Harmer
0.231
3142946ENON
Solar/Wind Harmer
-0.001
316033AB2-134 GEN
Solar/Wind Harmer
2.247
315697AD1-025 GEN
Solar/Wind Harmer
1.409
316236AE1-162_GEN
Solar/Wind Harmer
0.21
316036AC1-147 C
Solar/Wind Harmer
0.179
3150991CHESPKB
Adder
0.619
3150991CHESPKB
Adder
0.604
316316AC1-027 C
Solar/Wind Harmer
0.203
3142956BIRDNECK
Solar/Wind Harmer
0.354
316185AD1-033 GEN
Solar/Wind Harmer
0.693
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316339AD2-160 GEN
Solar/Wind Harmer
0.439
316018AA1-139 ULT2
Solar/Wind Harmer
0.557
316017AA1-139 ULT1
Solar/Wind Harmer
0.526
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.766
3130086AYDLETT
Solar/Wind Harmer
-0.026
3150691DARBY 3
Adder
4.114
3150701DARBY 4
Adder
4.104
3150681DARBY 2
Adder
4.1
3150671DARBY 1
Adder
4.095
3146386ELIZ CT
Solar/Wind Harmer
-0.006
971647AH1-324 GEN
Solar/Wind Harmer
3.511
3145336SMITFLD
Solar/Wind Harmer
-0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.095
316458AB2-190 GEN2
Solar/Wind Harmer
0.694
970129AG2-093 GEN
Solar/Wind Harmer
1.562
316072AD1-144
Solar/Wind Harmer
0.138
316294AC1-161 GEN
Solar/Wind Harmer
2.172
316375AC2-012 GEN
Solar/Wind Harmer
2.296
3150981CHESPKA
Adder
0.737
3143096IRON208
Adder
0.246
3142416OLDCHRC
Solar/Wind Harmer
-0.017
3142416OLDCHRC
Solar/Wind Harmer
-0.007
944591AF1-124 GEN
Solar/Wind Harmer
30.01
316246AF1-032 C
Solar/Wind Harmer
0.132
316388AE2-253 GEN
Solar/Wind Harmer
0.439
3146456SLIGO L269
Solar/Wind Harmer
-0.006
316093AE2-104_GEN
Solar/Wind Harmer
1.855
CPLELTFEXP_CPLE->PJM
CLTF
2.221
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.105
LAGNLTFEXP_LAGN->PJM
CLTF
1.55
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.805
TVALTFEXP_TVA->PJM
CLTF
0.781
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.555
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.668
MECLTFEXP_MEC->PJM
CLTF
0.73
SIGELTFEXP_SIGE->PJM
CLTF
0.022
NYPJM->LTFIMP_NY
CLTF
0.582
LGEELTFEXP_LGEE->PJM
CLTF
0.268
WECLTFEXP_WEC->PJM
CLTF
0.133

Details for AF1-114 TP-6DAHLGREN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AF1-114 TP-6DAHLGREN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.84 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:679.2
MW Contribution:3.66
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
3.006
970575AG2-366 GEN
50/50
3.66
315749AE2-041 GEN
50/50
4.946
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150921YORKTN3
50/50
1.929
3144216WINCHST
50/50
0.279
3151161SURRY 1
50/50
2.166
970737AG2-469 GEN
Solar/Wind Harmer
20.178
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.637
962971AG1-146 GEN
Solar/Wind Harmer
3.294
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.61
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.855
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.668
3142416OLDCHRC
Solar/Wind Harmer
0.555
3151221GRAVEL6
Adder
4.099
3151171GRAVELC
Adder
0.789
315759AF1-018 GEN
50/50
4.946
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150611CHESTG7
50/50
0.401
3150631CHESTG8
50/50
0.394
971047AG2-646 GEN
50/50
11.221
972263AH1-716 GEN
50/50
32.871
944491AF1-114 GEN
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Harmer
0.296
3141813NORNECK
Solar/Wind Harmer
0.279
970327AG2-215 GEN
Solar/Wind Harmer
7.194
962981AG1-147 GEN
Solar/Wind Harmer
7.685
3150341NORNECKC1
50/50
3.105
3150341NORNECKC1
50/50
3.08
963611AG1-210 GEN
50/50
0.994
3150621CHESTS7
50/50
0.184
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
7.962
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.007
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.051
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
0.029
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.081
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
9.122
315976AC1-164 GENA
Solar/Wind Harmer
8.292
316169AC1-164_GENC
Solar/Wind Harmer
7.163
315975AC1-164 GENB
Solar/Wind Harmer
0.245
316312AB1-027
Solar/Wind Harmer
0.102
972265AH1-717 GEN
Adder
4.377
3151201GRAVEL4
Adder
4.104
3151191GRAVEL3
Adder
4.052
3151211GRAVEL5
Adder
4.052
3141426STAFORD
Solar/Wind Helper
0.031
3150351NORNECKC2
50/50
2.956
966661AG1-536 GEN
50/50
6.849
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
971353AH1-157 GEN
50/50
7.408
970017AG2-010 GEN
50/50
4.699
3150641CHESTS8
50/50
0.203
944631AF1-128 GEN
50/50
31.925
972135AH1-637 GEN
Solar/Wind Harmer
4.389
316337AD2-073 GEN
Solar/Wind Harmer
0.299
3141726DUNNSVL
Solar/Wind Harmer
1.044
962861AG1-135 GEN
Solar/Wind Harmer
7.523
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
971317AH1-138 GEN
Solar/Wind Harmer
0.613
316159AE1-175 C
Solar/Wind Harmer
0.065
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3142416OLDCHRC
Solar/Wind Harmer
0.149
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.6
CPLELTFEXP_CPLE->PJM
CLTF
1.997
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.895
LAGNLTFEXP_LAGN->PJM
CLTF
1.483
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.388
TVALTFEXP_TVA->PJM
CLTF
0.749
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.711
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.577
MECLTFEXP_MEC->PJM
CLTF
0.732
SIGELTFEXP_SIGE->PJM
CLTF
0.022
NYPJM->LTFIMP_NY
CLTF
0.564
LGEELTFEXP_LGEE->PJM
CLTF
0.274
WECLTFEXP_WEC->PJM
CLTF
0.137

Details for AF1-114 TP-6DAHLGREN 230.0 kV Ckt 1 line l/o DVP_P4-2: 574T575_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AF1-114 TP-6DAHLGREN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 574T575_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.42 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:806.79
MW Contribution:3.69
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
5.017
944491AF1-114 GEN
Solar/Wind Harmer
18.704
316223AC1-118
Solar/Wind Harmer
1.247
3141813NORNECK
Solar/Wind Harmer
-0.031
962981AG1-147 GEN
Solar/Wind Harmer
10.194
3141783LANCAST
Solar/Wind Harmer
-0.012
3141783LANCAST
Solar/Wind Harmer
-0.008
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.019
957601AF2-054 GEN
Solar/Wind Harmer
0.5
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
1.944
315666AE1-190 GEN
Solar/Wind Harmer
0.486
316059AD1-063 C
Solar/Wind Harmer
0.358
316314AB2-024 C
Solar/Wind Harmer
1.31
3143873LANEXA
Solar/Wind Harmer
-0.008
957831AF2-077 GEN
Solar/Wind Harmer
0.373
3138283WHITEMARSH
Solar/Wind Harmer
0.019
3142433PROV 92
Adder
0.212
3142433PROV 92
Adder
0.212
971167AH1-042 GEN
Solar/Wind Harmer
11.35
315976AC1-164 GENA
Solar/Wind Harmer
9.762
316169AC1-164_GENC
Solar/Wind Harmer
8.433
315975AC1-164 GENB
Solar/Wind Harmer
0.289
972265AH1-717 GEN
Adder
4.614
3151201GRAVEL4
Adder
4.325
3151191GRAVEL3
Adder
4.27
3151211GRAVEL5
Adder
4.27
316312AB1-027
Solar/Wind Harmer
0.224
316369SG1_INVT
Solar/Wind Harmer
1.181
316132AB2-190 GEN1
Solar/Wind Harmer
0.665
971445AH1-216 GEN
Solar/Wind Harmer
4
3141426STAFORD
Solar/Wind Helper
0.033
3150351NORNECKC2
50/50
3.016
970575AG2-366 GEN
50/50
3.687
315749AE2-041 GEN
50/50
5.017
3141843SHACKLE
50/50
0.757
970737AG2-469 GEN
Solar/Wind Harmer
26.539
3141906WESTMOR
Solar/Wind Harmer
-0.018
316404AE1-155 C
Solar/Wind Harmer
5.246
316484AD2-074 GEN
Solar/Wind Harmer
6.24
970009AG2-005 GEN
Solar/Wind Harmer
3.098
962971AG1-146 GEN
Solar/Wind Harmer
4.369
316156AD2-030 GEN
Solar/Wind Harmer
0.446
3141873WAN 176
Solar/Wind Harmer
1.984
316280AD1-041 GEN
Solar/Wind Harmer
1.215
3141766HARMONY
Solar/Wind Harmer
1.411
316203AE2-005 GEN
Solar/Wind Harmer
6.619
3142433PROV 92
Adder
0.212
3142433PROV 92
Adder
0.212
316382AG1-145 C
Solar/Wind Harmer
0.264
3150921YORKTN3
Adder
1.889
3144216WINCHST
Adder
0.274
3142946ENON
Solar/Wind Harmer
-0.003
970293AG2-193 GEN
Solar/Wind Harmer
0.911
3151221GRAVEL6
Adder
4.32
3151171GRAVELC
Adder
0.831
961611AG1-000B GEN
Solar/Wind Harmer
1.4
3142416OLDCHRC
Solar/Wind Harmer
0.671
315778AD1-151 GEN
Solar/Wind Harmer
5.713
970129AG2-093 GEN
Solar/Wind Harmer
3.698
3143096IRON208
Adder
0.244
3143096IRON208
Adder
0.239
970133AG2-095 GEN
Solar/Wind Harmer
0.735
3145336SMITFLD
Solar/Wind Harmer
-0.003
3150341NORNECKC1
50/50
3.116
3150341NORNECKC1
50/50
3.091
963611AG1-210 GEN
50/50
0.997
316077AC2-138 C
Solar/Wind Harmer
0.664
958261AF2-120 GEN
Solar/Wind Harmer
10.538
316487AF1-042 GEN
Solar/Wind Harmer
3.265
316441AF1-014 GEN
Solar/Wind Harmer
1.058
316075AC2-137 C
Solar/Wind Harmer
0.221
3142946ENON
Solar/Wind Harmer
-0.001
316033AB2-134 GEN
Solar/Wind Harmer
2.132
315697AD1-025 GEN
Solar/Wind Harmer
1.337
3150691DARBY 3
Adder
4.134
3150701DARBY 4
Adder
4.124
3150681DARBY 2
Adder
4.12
3150671DARBY 1
Adder
4.115
316236AE1-162_GEN
Solar/Wind Harmer
0.194
3150351NORNECKC2
50/50
2.966
966661AG1-536 GEN
50/50
6.885
3141843SHACKLE
50/50
0.757
957971AF2-091 GEN
Solar/Wind Harmer
6.359
972135AH1-637 GEN
Solar/Wind Harmer
5.77
316337AD2-073 GEN
Solar/Wind Harmer
1.037
964211AG1-282 GEN
Solar/Wind Harmer
0.886
3141726DUNNSVL
Solar/Wind Harmer
-0.117
962861AG1-135 GEN
Solar/Wind Harmer
9.959
961951AG1-038 GEN
Solar/Wind Harmer
3.265
3138133OCRAN
Solar/Wind Harmer
-0.012
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.845
3142433PROV 92
Solar/Wind Harmer
-0.049
3142433PROV 92
Adder
0.212
3142433PROV 92
Adder
0.212
971317AH1-138 GEN
Solar/Wind Harmer
1.192
316159AE1-175 C
Solar/Wind Harmer
0.235
3138126ROCKLANDING
Solar/Wind Harmer
0.025
944631AF1-128 GEN
Adder
31.292
3151171GRAVELC
Adder
0.632
961611AG1-000B GEN
Solar/Wind Harmer
3.282
3142416OLDCHRC
Solar/Wind Harmer
-0.017
3142416OLDCHRC
Solar/Wind Harmer
-0.007
971647AH1-324 GEN
Solar/Wind Harmer
3.315
971069AG2-661 GEN
Solar/Wind Harmer
1.043
316458AB2-190 GEN2
Solar/Wind Harmer
0.665
970129AG2-093 GEN
Solar/Wind Harmer
1.498
3143096IRON208
Adder
0.244
3145336SMITFLD
Solar/Wind Harmer
-0.026
CPLELTFEXP_CPLE->PJM
CLTF
2.196
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.727
LAGNLTFEXP_LAGN->PJM
CLTF
1.637
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.831
TVALTFEXP_TVA->PJM
CLTF
0.827
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.235
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.846
MECLTFEXP_MEC->PJM
CLTF
0.811
SIGELTFEXP_SIGE->PJM
CLTF
0.025
NYPJM->LTFIMP_NY
CLTF
0.625
LGEELTFEXP_LGEE->PJM
CLTF
0.304
WECLTFEXP_WEC->PJM
CLTF
0.152

Details for AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.51 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:899.54
MW Contribution:3.79
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
3.026
966661AG1-536 GEN
50/50
7.046
3141843SHACKLE
50/50
0.787
3142433PROV 92
50/50
0.233
3142433PROV 92
50/50
0.233
957971AF2-091 GEN
Solar/Wind Harmer
6.42
972135AH1-637 GEN
Solar/Wind Harmer
5.832
316337AD2-073 GEN
Solar/Wind Harmer
1.054
964211AG1-282 GEN
Solar/Wind Harmer
0.905
3141726DUNNSVL
Solar/Wind Harmer
-0.12
962861AG1-135 GEN
Solar/Wind Harmer
10.198
961951AG1-038 GEN
Solar/Wind Harmer
3.349
3138133OCRAN
Solar/Wind Harmer
-0.012
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.916
3142433PROV 92
Solar/Wind Harmer
-0.051
971317AH1-138 GEN
Solar/Wind Harmer
1.283
316159AE1-175 C
Solar/Wind Harmer
0.254
3138126ROCKLANDING
Solar/Wind Harmer
0.027
944631AF1-128 GEN
Adder
32.493
3151171GRAVELC
Adder
0.677
961611AG1-000B GEN
Solar/Wind Harmer
3.494
971647AH1-324 GEN
Solar/Wind Harmer
3.511
315759AF1-018 GEN
50/50
5.221
3142433PROV 92
50/50
0.233
3142433PROV 92
50/50
0.233
944491AF1-114 GEN
Solar/Wind Harmer
18.883
316223AC1-118
Solar/Wind Harmer
1.264
3141813NORNECK
Solar/Wind Harmer
-0.032
962981AG1-147 GEN
Solar/Wind Harmer
10.474
3141783LANCAST
Solar/Wind Harmer
-0.013
3141783LANCAST
Solar/Wind Harmer
-0.008
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.02
957601AF2-054 GEN
Solar/Wind Harmer
0.519
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
2.019
315666AE1-190 GEN
Solar/Wind Harmer
0.505
316059AD1-063 C
Solar/Wind Harmer
0.373
316314AB2-024 C
Solar/Wind Harmer
1.365
3143873LANEXA
Solar/Wind Harmer
-0.009
957831AF2-077 GEN
Solar/Wind Harmer
0.393
3138283WHITEMARSH
Solar/Wind Harmer
0.02
971167AH1-042 GEN
Solar/Wind Harmer
11.736
315976AC1-164 GENA
Solar/Wind Harmer
10.45
316169AC1-164_GENC
Solar/Wind Harmer
9.028
315975AC1-164 GENB
Solar/Wind Harmer
0.309
972265AH1-717 GEN
Adder
4.942
3151201GRAVEL4
Adder
4.633
3151191GRAVEL3
Adder
4.574
3151211GRAVEL5
Adder
4.574
971445AH1-216 GEN
Solar/Wind Harmer
4.315
316369SG1_INVT
Solar/Wind Harmer
1.245
316132AB2-190 GEN1
Solar/Wind Harmer
0.694
3152611GOSPORTB
Adder
0.752
3152621GOSPORTC
Adder
0.638
3152601GOSPORTA
Adder
0.589
3151081ELIZAR1
Adder
5.409
3151091ELIZAR2
Adder
5.315
316312AB1-027
Solar/Wind Harmer
0.222
316305AF2-043 C
Solar/Wind Harmer
0.196
957871AF2-081 GEN
Solar/Wind Harmer
3.251
319010AE1-072 C
Solar/Wind Harmer
1.31
3146406KITTY HAWK
Solar/Wind Harmer
0.005
313526AB2-022
Solar/Wind Harmer
0.172
315835AF2-110_GEN
Solar/Wind Harmer
0.797
3146486SUNBURY
Solar/Wind Harmer
-0.006
3146486SUNBURY
Solar/Wind Harmer
-0.006
316321Z2-027
Solar/Wind Harmer
0.171
3146396TANGLEW
Solar/Wind Harmer
0.117
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3141426STAFORD
Solar/Wind Helper
0.031
3150351NORNECKC2
50/50
3.077
970575AG2-366 GEN
50/50
3.788
315749AE2-041 GEN
50/50
5.221
3141843SHACKLE
50/50
0.787
3142433PROV 92
50/50
0.233
3142433PROV 92
50/50
0.233
970737AG2-469 GEN
Solar/Wind Harmer
26.848
3141906WESTMOR
Solar/Wind Harmer
-0.019
316404AE1-155 C
Solar/Wind Harmer
5.369
316484AD2-074 GEN
Solar/Wind Harmer
6.401
970009AG2-005 GEN
Solar/Wind Harmer
3.178
962971AG1-146 GEN
Solar/Wind Harmer
4.489
316156AD2-030 GEN
Solar/Wind Harmer
0.464
3141873WAN 176
Solar/Wind Harmer
2.06
316280AD1-041 GEN
Solar/Wind Harmer
1.262
3141766HARMONY
Solar/Wind Harmer
1.469
316203AE2-005 GEN
Solar/Wind Harmer
6.877
316382AG1-145 C
Solar/Wind Harmer
0.285
3150921YORKTN3
Adder
2.048
3144216WINCHST
Adder
0.297
3142946ENON
Solar/Wind Harmer
-0.003
970293AG2-193 GEN
Solar/Wind Harmer
0.932
3151221GRAVEL6
Adder
4.627
3151171GRAVELC
Adder
0.89
961611AG1-000B GEN
Solar/Wind Harmer
1.491
3145336SMITFLD
Solar/Wind Harmer
-0.003
315778AD1-151 GEN
Solar/Wind Harmer
5.997
970129AG2-093 GEN
Solar/Wind Harmer
3.855
970133AG2-095 GEN
Solar/Wind Harmer
0.758
3144536CHRHLND
Solar/Wind Harmer
-0.001
315773AC2-141 GEN
Solar/Wind Harmer
2.81
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.478
3143096IRON208
Adder
0.246
3143096IRON208
Adder
0.241
3142416OLDCHRC
Solar/Wind Harmer
0.665
944581AF1-123 GEN
Solar/Wind Harmer
29.902
944601AF1-125 GEN
Solar/Wind Harmer
29.435
3146456SLIGO L269
Solar/Wind Harmer
-0.006
971153AH1-033 GEN
Solar/Wind Harmer
0.79
316320Y1-086
Solar/Wind Harmer
0.374
3145336SMITFLD
Solar/Wind Harmer
-0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.095
316458AB2-190 GEN2
Solar/Wind Harmer
0.694
970129AG2-093 GEN
Solar/Wind Harmer
1.562
316072AD1-144
Solar/Wind Harmer
0.138
316294AC1-161 GEN
Solar/Wind Harmer
2.172
316375AC2-012 GEN
Solar/Wind Harmer
2.296
3150981CHESPKA
Adder
0.737
3143096IRON208
Adder
0.246
3142416OLDCHRC
Solar/Wind Harmer
-0.017
3142416OLDCHRC
Solar/Wind Harmer
-0.007
944591AF1-124 GEN
Solar/Wind Harmer
30.01
316246AF1-032 C
Solar/Wind Harmer
0.132
316388AE2-253 GEN
Solar/Wind Harmer
0.439
3146456SLIGO L269
Solar/Wind Harmer
-0.006
316093AE2-104_GEN
Solar/Wind Harmer
1.855
957191AF2-013 GEN
50/50
65.961
3150341NORNECKC1
50/50
3.178
3150341NORNECKC1
50/50
3.153
963611AG1-210 GEN
50/50
1.017
316077AC2-138 C
Solar/Wind Harmer
0.678
958261AF2-120 GEN
Solar/Wind Harmer
10.785
316487AF1-042 GEN
Solar/Wind Harmer
3.349
316441AF1-014 GEN
Solar/Wind Harmer
1.1
316075AC2-137 C
Solar/Wind Harmer
0.231
3142946ENON
Solar/Wind Harmer
-0.001
316033AB2-134 GEN
Solar/Wind Harmer
2.247
315697AD1-025 GEN
Solar/Wind Harmer
1.409
316236AE1-162_GEN
Solar/Wind Harmer
0.21
316036AC1-147 C
Solar/Wind Harmer
0.179
3150991CHESPKB
Adder
0.619
3150991CHESPKB
Adder
0.604
316316AC1-027 C
Solar/Wind Harmer
0.203
3142956BIRDNECK
Solar/Wind Harmer
0.354
316185AD1-033 GEN
Solar/Wind Harmer
0.693
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316339AD2-160 GEN
Solar/Wind Harmer
0.439
316018AA1-139 ULT2
Solar/Wind Harmer
0.557
316017AA1-139 ULT1
Solar/Wind Harmer
0.526
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.766
3130086AYDLETT
Solar/Wind Harmer
-0.026
3150691DARBY 3
Adder
4.114
3150701DARBY 4
Adder
4.104
3150681DARBY 2
Adder
4.1
3150671DARBY 1
Adder
4.095
3146386ELIZ CT
Solar/Wind Harmer
-0.006
CPLELTFEXP_CPLE->PJM
CLTF
2.221
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.105
LAGNLTFEXP_LAGN->PJM
CLTF
1.55
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.805
TVALTFEXP_TVA->PJM
CLTF
0.781
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.555
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.668
MECLTFEXP_MEC->PJM
CLTF
0.73
SIGELTFEXP_SIGE->PJM
CLTF
0.022
NYPJM->LTFIMP_NY
CLTF
0.582
LGEELTFEXP_LGEE->PJM
CLTF
0.268
WECLTFEXP_WEC->PJM
CLTF
0.133

Details for AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.21 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:711.49
MW Contribution:3.66
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
3.006
970575AG2-366 GEN
50/50
3.66
315749AE2-041 GEN
50/50
4.946
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150921YORKTN3
50/50
1.929
3144216WINCHST
50/50
0.279
3151161SURRY 1
50/50
2.166
970737AG2-469 GEN
Solar/Wind Harmer
20.178
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.637
962971AG1-146 GEN
Solar/Wind Harmer
3.294
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.61
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.855
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.668
3142416OLDCHRC
Solar/Wind Harmer
0.555
3151221GRAVEL6
Adder
4.099
3151171GRAVELC
Adder
0.789
315759AF1-018 GEN
50/50
4.946
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
3150611CHESTG7
50/50
0.401
3150631CHESTG8
50/50
0.394
971047AG2-646 GEN
50/50
11.221
972263AH1-716 GEN
50/50
32.871
944491AF1-114 GEN
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Harmer
0.296
3141813NORNECK
Solar/Wind Harmer
0.279
970327AG2-215 GEN
Solar/Wind Harmer
7.194
962981AG1-147 GEN
Solar/Wind Harmer
7.685
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.051
3141913WHIT STONE
Solar/Wind Harmer
0.166
3141873WAN 176
Solar/Wind Harmer
0.029
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.081
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
9.122
315976AC1-164 GENA
Solar/Wind Harmer
8.292
316169AC1-164_GENC
Solar/Wind Harmer
7.163
315975AC1-164 GENB
Solar/Wind Harmer
0.245
316312AB1-027
Solar/Wind Harmer
0.102
972265AH1-717 GEN
Adder
4.377
3151201GRAVEL4
Adder
4.104
3151191GRAVEL3
Adder
4.052
3151211GRAVEL5
Adder
4.052
3141426STAFORD
Solar/Wind Helper
0.031
957191AF2-013 GEN
50/50
65.713
3150341NORNECKC1
50/50
3.105
3150341NORNECKC1
50/50
3.08
963611AG1-210 GEN
50/50
0.994
3150621CHESTS7
50/50
0.184
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
7.962
316075AC2-137 C
Solar/Wind Harmer
0.019
3142946ENON
Solar/Wind Harmer
0.007
3150351NORNECKC2
50/50
2.956
966661AG1-536 GEN
50/50
6.849
3141843SHACKLE
50/50
0.746
3142433PROV 92
50/50
0.221
3142433PROV 92
50/50
0.221
971353AH1-157 GEN
50/50
7.408
970017AG2-010 GEN
50/50
4.699
3150641CHESTS8
50/50
0.203
944631AF1-128 GEN
50/50
31.925
972135AH1-637 GEN
Solar/Wind Harmer
4.389
316337AD2-073 GEN
Solar/Wind Harmer
0.299
3141726DUNNSVL
Solar/Wind Harmer
1.044
962861AG1-135 GEN
Solar/Wind Harmer
7.523
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.363
3142433PROV 92
Solar/Wind Harmer
0.428
971317AH1-138 GEN
Solar/Wind Harmer
0.613
316159AE1-175 C
Solar/Wind Harmer
0.065
3138126ROCKLANDING
Solar/Wind Harmer
0.032
3142416OLDCHRC
Solar/Wind Harmer
0.149
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.6
CPLELTFEXP_CPLE->PJM
CLTF
1.997
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.895
LAGNLTFEXP_LAGN->PJM
CLTF
1.483
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.388
TVALTFEXP_TVA->PJM
CLTF
0.749
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.711
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.577
MECLTFEXP_MEC->PJM
CLTF
0.732
SIGELTFEXP_SIGE->PJM
CLTF
0.022
NYPJM->LTFIMP_NY
CLTF
0.564
LGEELTFEXP_LGEE->PJM
CLTF
0.274
WECLTFEXP_WEC->PJM
CLTF
0.137

Details for AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line l/o DVP_P4-2: 574T575_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 574T575_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.7 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:839.28
MW Contribution:3.69
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
3.016
970575AG2-366 GEN
50/50
3.687
315749AE2-041 GEN
50/50
5.017
3141843SHACKLE
50/50
0.757
970737AG2-469 GEN
Solar/Wind Harmer
26.539
3141906WESTMOR
Solar/Wind Harmer
-0.018
316404AE1-155 C
Solar/Wind Harmer
5.246
316484AD2-074 GEN
Solar/Wind Harmer
6.24
970009AG2-005 GEN
Solar/Wind Harmer
3.098
962971AG1-146 GEN
Solar/Wind Harmer
4.369
316156AD2-030 GEN
Solar/Wind Harmer
0.446
3141873WAN 176
Solar/Wind Harmer
1.984
316280AD1-041 GEN
Solar/Wind Harmer
1.215
3141766HARMONY
Solar/Wind Harmer
1.411
316203AE2-005 GEN
Solar/Wind Harmer
6.619
3142433PROV 92
Adder
0.212
315759AF1-018 GEN
50/50
5.017
944491AF1-114 GEN
Solar/Wind Harmer
18.704
316223AC1-118
Solar/Wind Harmer
1.247
3141813NORNECK
Solar/Wind Harmer
-0.031
962981AG1-147 GEN
Solar/Wind Harmer
10.194
3141783LANCAST
Solar/Wind Harmer
-0.012
3141783LANCAST
Solar/Wind Harmer
-0.008
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.019
957601AF2-054 GEN
Solar/Wind Harmer
0.5
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
1.944
315666AE1-190 GEN
Solar/Wind Harmer
0.486
316059AD1-063 C
Solar/Wind Harmer
0.358
316314AB2-024 C
Solar/Wind Harmer
1.31
3143873LANEXA
Solar/Wind Harmer
-0.008
957831AF2-077 GEN
Solar/Wind Harmer
0.373
3138283WHITEMARSH
Solar/Wind Harmer
0.019
3142433PROV 92
Adder
0.212
3142433PROV 92
Adder
0.212
971167AH1-042 GEN
Solar/Wind Harmer
11.35
315976AC1-164 GENA
Solar/Wind Harmer
9.762
316169AC1-164_GENC
Solar/Wind Harmer
8.433
315975AC1-164 GENB
Solar/Wind Harmer
0.289
972265AH1-717 GEN
Adder
4.614
3151201GRAVEL4
Adder
4.325
3151191GRAVEL3
Adder
4.27
3151211GRAVEL5
Adder
4.27
316312AB1-027
Solar/Wind Harmer
0.224
316369SG1_INVT
Solar/Wind Harmer
1.181
316132AB2-190 GEN1
Solar/Wind Harmer
0.665
971445AH1-216 GEN
Solar/Wind Harmer
4
3141426STAFORD
Solar/Wind Helper
0.033
957191AF2-013 GEN
50/50
65.491
3150341NORNECKC1
50/50
3.116
3150341NORNECKC1
50/50
3.091
963611AG1-210 GEN
50/50
0.997
316077AC2-138 C
Solar/Wind Harmer
0.664
958261AF2-120 GEN
Solar/Wind Harmer
10.538
316487AF1-042 GEN
Solar/Wind Harmer
3.265
316441AF1-014 GEN
Solar/Wind Harmer
1.058
316075AC2-137 C
Solar/Wind Harmer
0.221
3142946ENON
Solar/Wind Harmer
-0.001
316033AB2-134 GEN
Solar/Wind Harmer
2.132
315697AD1-025 GEN
Solar/Wind Harmer
1.337
3150691DARBY 3
Adder
4.134
3150701DARBY 4
Adder
4.124
3150681DARBY 2
Adder
4.12
3150671DARBY 1
Adder
4.115
316236AE1-162_GEN
Solar/Wind Harmer
0.194
3150351NORNECKC2
50/50
2.966
966661AG1-536 GEN
50/50
6.885
3141843SHACKLE
50/50
0.757
957971AF2-091 GEN
Solar/Wind Harmer
6.359
972135AH1-637 GEN
Solar/Wind Harmer
5.77
316337AD2-073 GEN
Solar/Wind Harmer
1.037
964211AG1-282 GEN
Solar/Wind Harmer
0.886
3141726DUNNSVL
Solar/Wind Harmer
-0.117
962861AG1-135 GEN
Solar/Wind Harmer
9.959
961951AG1-038 GEN
Solar/Wind Harmer
3.265
3138133OCRAN
Solar/Wind Harmer
-0.012
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.845
3142433PROV 92
Solar/Wind Harmer
-0.049
3142433PROV 92
Adder
0.212
3142433PROV 92
Adder
0.212
971317AH1-138 GEN
Solar/Wind Harmer
1.192
316159AE1-175 C
Solar/Wind Harmer
0.235
3138126ROCKLANDING
Solar/Wind Harmer
0.025
944631AF1-128 GEN
Adder
31.292
3151171GRAVELC
Adder
0.632
961611AG1-000B GEN
Solar/Wind Harmer
3.282
3142416OLDCHRC
Solar/Wind Harmer
-0.017
3142416OLDCHRC
Solar/Wind Harmer
-0.007
971647AH1-324 GEN
Solar/Wind Harmer
3.315
971069AG2-661 GEN
Solar/Wind Harmer
1.043
316458AB2-190 GEN2
Solar/Wind Harmer
0.665
970129AG2-093 GEN
Solar/Wind Harmer
1.498
3143096IRON208
Adder
0.244
3145336SMITFLD
Solar/Wind Harmer
-0.026
3142433PROV 92
Adder
0.212
316382AG1-145 C
Solar/Wind Harmer
0.264
3150921YORKTN3
Adder
1.889
3144216WINCHST
Adder
0.274
3142946ENON
Solar/Wind Harmer
-0.003
970293AG2-193 GEN
Solar/Wind Harmer
0.911
3151221GRAVEL6
Adder
4.32
3151171GRAVELC
Adder
0.831
961611AG1-000B GEN
Solar/Wind Harmer
1.4
3142416OLDCHRC
Solar/Wind Harmer
0.671
315778AD1-151 GEN
Solar/Wind Harmer
5.713
970129AG2-093 GEN
Solar/Wind Harmer
3.698
3143096IRON208
Adder
0.244
3143096IRON208
Adder
0.239
970133AG2-095 GEN
Solar/Wind Harmer
0.735
3145336SMITFLD
Solar/Wind Harmer
-0.003
CPLELTFEXP_CPLE->PJM
CLTF
2.196
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.727
LAGNLTFEXP_LAGN->PJM
CLTF
1.637
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.831
TVALTFEXP_TVA->PJM
CLTF
0.827
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.235
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.846
MECLTFEXP_MEC->PJM
CLTF
0.811
SIGELTFEXP_SIGE->PJM
CLTF
0.025
NYPJM->LTFIMP_NY
CLTF
0.625
LGEELTFEXP_LGEE->PJM
CLTF
0.304
WECLTFEXP_WEC->PJM
CLTF
0.152

Details for AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.1 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:604.6
MW Contribution:3.68
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
3.02
970575AG2-366 GEN
50/50
3.68
315749AE2-041 GEN
50/50
4.976
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
3150921YORKTN3
50/50
2.003
3144216WINCHST
50/50
0.289
3151161SURRY 1
50/50
2.191
970737AG2-469 GEN
Solar/Wind Harmer
20.26
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.646
962971AG1-146 GEN
Solar/Wind Harmer
3.312
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.629
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.866
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.022
3151221GRAVEL6
Adder
4.147
3151171GRAVELC
Adder
0.798
970293AG2-193 GEN
Solar/Wind Harmer
0.603
957191AF2-013 GEN
50/50
65.968
3150341NORNECKC1
50/50
3.119
3150341NORNECKC1
50/50
3.094
963611AG1-210 GEN
50/50
0.998
3150621CHESTS7
50/50
0.174
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
8.003
316075AC2-137 C
Solar/Wind Harmer
0.018
3142946ENON
Solar/Wind Harmer
0.007
315759AF1-018 GEN
50/50
4.976
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
972263AH1-716 GEN
50/50
35.649
3150611CHESTG7
50/50
0.379
3150631CHESTG8
50/50
0.372
971047AG2-646 GEN
50/50
10.599
944491AF1-114 GEN
Solar/Wind Harmer
0.002
316223AC1-118
Solar/Wind Harmer
0.297
3141813NORNECK
Solar/Wind Harmer
0.28
970327AG2-215 GEN
Solar/Wind Harmer
7.232
962981AG1-147 GEN
Solar/Wind Harmer
7.729
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.074
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.168
3141873WAN 176
Solar/Wind Harmer
0.03
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.097
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
8.942
315976AC1-164 GENA
Solar/Wind Harmer
8.275
316169AC1-164_GENC
Solar/Wind Harmer
7.149
315975AC1-164 GENB
Solar/Wind Harmer
0.245
972265AH1-717 GEN
Adder
4.429
3151201GRAVEL4
Adder
4.152
3151191GRAVEL3
Adder
4.099
3151211GRAVEL5
Adder
4.099
3141426STAFORD
Solar/Wind Helper
0.029
3150351NORNECKC2
50/50
2.97
966661AG1-536 GEN
50/50
6.884
3141843SHACKLE
50/50
0.749
3142433PROV 92
50/50
0.218
3142433PROV 92
50/50
0.218
971353AH1-157 GEN
50/50
7.642
970017AG2-010 GEN
50/50
4.875
3150641CHESTS8
50/50
0.192
944631AF1-128 GEN
50/50
30.156
3152331SURRY 2
50/50
2.455
972135AH1-637 GEN
Solar/Wind Harmer
4.407
316337AD2-073 GEN
Solar/Wind Harmer
0.3
3141726DUNNSVL
Solar/Wind Harmer
1.049
962861AG1-135 GEN
Solar/Wind Harmer
7.561
3138133OCRAN
Solar/Wind Harmer
0.104
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.365
3142433PROV 92
Solar/Wind Harmer
0.422
971317AH1-138 GEN
Solar/Wind Harmer
0.633
316159AE1-175 C
Solar/Wind Harmer
0.067
3138126ROCKLANDING
Solar/Wind Harmer
0.034
3151171GRAVELC
Adder
0.607
CPLELTFEXP_CPLE->PJM
CLTF
1.912
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.152
LAGNLTFEXP_LAGN->PJM
CLTF
1.213
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.047
TVALTFEXP_TVA->PJM
CLTF
0.609
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.061
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.057
MECLTFEXP_MEC->PJM
CLTF
0.525
SIGELTFEXP_SIGE->PJM
CLTF
0.016
NYPJM->LTFIMP_NY
CLTF
0.465
LGEELTFEXP_LGEE->PJM
CLTF
0.185
WECLTFEXP_WEC->PJM
CLTF
0.092

Details for AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.39 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:720.84
MW Contribution:3.66
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
4.944
944491AF1-114 GEN
Solar/Wind Harmer
18.743
316223AC1-118
Solar/Wind Harmer
1.247
3141813NORNECK
Solar/Wind Harmer
-0.031
962981AG1-147 GEN
Solar/Wind Harmer
10.117
3141783LANCAST
Solar/Wind Harmer
-0.012
3141783LANCAST
Solar/Wind Harmer
-0.008
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.019
957601AF2-054 GEN
Solar/Wind Harmer
0.493
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
1.916
315666AE1-190 GEN
Solar/Wind Harmer
0.479
316059AD1-063 C
Solar/Wind Harmer
0.353
316314AB2-024 C
Solar/Wind Harmer
1.29
3143873LANEXA
Solar/Wind Harmer
-0.008
957831AF2-077 GEN
Solar/Wind Harmer
0.364
3138283WHITEMARSH
Solar/Wind Harmer
0.019
3142433PROV 92
Adder
0.208
3142433PROV 92
Adder
0.208
971167AH1-042 GEN
Solar/Wind Harmer
11.098
315976AC1-164 GENA
Solar/Wind Harmer
9.485
316169AC1-164_GENC
Solar/Wind Harmer
8.194
315975AC1-164 GENB
Solar/Wind Harmer
0.281
316312AB1-027
Solar/Wind Harmer
0.216
972265AH1-717 GEN
Adder
4.374
3151201GRAVEL4
Adder
4.1
3151191GRAVEL3
Adder
4.048
3151211GRAVEL5
Adder
4.048
3141426STAFORD
Solar/Wind Helper
0.031
957191AF2-013 GEN
50/50
65.707
3150341NORNECKC1
50/50
3.104
3150341NORNECKC1
50/50
3.08
963611AG1-210 GEN
50/50
0.993
316077AC2-138 C
Solar/Wind Harmer
0.662
958261AF2-120 GEN
Solar/Wind Harmer
10.482
316487AF1-042 GEN
Solar/Wind Harmer
3.243
316441AF1-014 GEN
Solar/Wind Harmer
1.042
316075AC2-137 C
Solar/Wind Harmer
0.214
3142946ENON
Solar/Wind Harmer
-0.001
3150351NORNECKC2
50/50
2.955
966661AG1-536 GEN
50/50
6.848
3141843SHACKLE
50/50
0.746
957971AF2-091 GEN
Solar/Wind Harmer
6.372
972135AH1-637 GEN
Solar/Wind Harmer
5.779
316337AD2-073 GEN
Solar/Wind Harmer
1.036
964211AG1-282 GEN
Solar/Wind Harmer
0.882
3141726DUNNSVL
Solar/Wind Harmer
-0.117
962861AG1-135 GEN
Solar/Wind Harmer
9.902
961951AG1-038 GEN
Solar/Wind Harmer
3.243
3138133OCRAN
Solar/Wind Harmer
-0.011
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.817
3142433PROV 92
Solar/Wind Harmer
-0.048
3142433PROV 92
Adder
0.208
3142433PROV 92
Adder
0.208
971317AH1-138 GEN
Solar/Wind Harmer
1.154
316159AE1-175 C
Solar/Wind Harmer
0.227
3138126ROCKLANDING
Solar/Wind Harmer
0.024
944631AF1-128 GEN
Adder
30.026
3142416OLDCHRC
Solar/Wind Harmer
-0.017
3142416OLDCHRC
Solar/Wind Harmer
-0.006
3151171GRAVELC
Adder
0.599
3150351NORNECKC2
50/50
3.005
970575AG2-366 GEN
50/50
3.659
315749AE2-041 GEN
50/50
4.944
3141843SHACKLE
50/50
0.746
970737AG2-469 GEN
Solar/Wind Harmer
26.564
3141906WESTMOR
Solar/Wind Harmer
-0.018
316404AE1-155 C
Solar/Wind Harmer
5.218
316484AD2-074 GEN
Solar/Wind Harmer
6.199
970009AG2-005 GEN
Solar/Wind Harmer
3.078
962971AG1-146 GEN
Solar/Wind Harmer
4.336
316156AD2-030 GEN
Solar/Wind Harmer
0.44
3141873WAN 176
Solar/Wind Harmer
1.957
316280AD1-041 GEN
Solar/Wind Harmer
1.198
3141766HARMONY
Solar/Wind Harmer
1.39
316203AE2-005 GEN
Solar/Wind Harmer
6.52
3142433PROV 92
Adder
0.208
3142433PROV 92
Adder
0.208
316382AG1-145 C
Solar/Wind Harmer
0.255
3150921YORKTN3
Adder
1.818
3144216WINCHST
Adder
0.263
3142946ENON
Solar/Wind Harmer
-0.003
970293AG2-193 GEN
Solar/Wind Harmer
0.877
3142416OLDCHRC
Solar/Wind Harmer
0.646
3151221GRAVEL6
Adder
4.095
3151171GRAVELC
Adder
0.788
CPLELTFEXP_CPLE->PJM
CLTF
1.996
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.91
LAGNLTFEXP_LAGN->PJM
CLTF
1.485
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.39
TVALTFEXP_TVA->PJM
CLTF
0.75
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.728
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.582
MECLTFEXP_MEC->PJM
CLTF
0.734
SIGELTFEXP_SIGE->PJM
CLTF
0.022
NYPJM->LTFIMP_NY
CLTF
0.565
LGEELTFEXP_LGEE->PJM
CLTF
0.275
WECLTFEXP_WEC->PJM
CLTF
0.137

Details for AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AF2-013 TP-6ARNOLDS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.44 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:693.87
MW Contribution:3.64
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
4.91
944491AF1-114 GEN
Solar/Wind Harmer
18.689
316223AC1-118
Solar/Wind Harmer
1.243
3141813NORNECK
Solar/Wind Harmer
-0.031
962981AG1-147 GEN
Solar/Wind Harmer
10.065
3141783LANCAST
Solar/Wind Harmer
-0.012
3141783LANCAST
Solar/Wind Harmer
-0.008
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.019
957601AF2-054 GEN
Solar/Wind Harmer
0.49
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
1.903
957191AF2-013 GEN
50/50
65.537
3150341NORNECKC1
50/50
3.091
3150341NORNECKC1
50/50
3.067
963611AG1-210 GEN
50/50
0.989
316077AC2-138 C
Solar/Wind Harmer
0.659
958261AF2-120 GEN
Solar/Wind Harmer
10.433
316487AF1-042 GEN
Solar/Wind Harmer
3.228
3150351NORNECKC2
50/50
2.993
970575AG2-366 GEN
50/50
3.64
315749AE2-041 GEN
50/50
4.91
3141843SHACKLE
50/50
0.741
970737AG2-469 GEN
Solar/Wind Harmer
26.481
3141906WESTMOR
Solar/Wind Harmer
-0.018
316404AE1-155 C
Solar/Wind Harmer
5.194
316484AD2-074 GEN
Solar/Wind Harmer
6.168
970009AG2-005 GEN
Solar/Wind Harmer
3.063
962971AG1-146 GEN
Solar/Wind Harmer
4.314
316156AD2-030 GEN
Solar/Wind Harmer
0.438
3141873WAN 176
Solar/Wind Harmer
1.944
316280AD1-041 GEN
Solar/Wind Harmer
1.19
315666AE1-190 GEN
Solar/Wind Harmer
0.476
316059AD1-063 C
Solar/Wind Harmer
0.351
316314AB2-024 C
Solar/Wind Harmer
1.281
3150351NORNECKC2
50/50
2.943
966661AG1-536 GEN
50/50
6.816
3141843SHACKLE
50/50
0.741
957971AF2-091 GEN
Solar/Wind Harmer
6.354
972135AH1-637 GEN
Solar/Wind Harmer
5.761
316337AD2-073 GEN
Solar/Wind Harmer
1.032
964211AG1-282 GEN
Solar/Wind Harmer
0.878
3141726DUNNSVL
Solar/Wind Harmer
-0.116
962861AG1-135 GEN
Solar/Wind Harmer
9.856
961951AG1-038 GEN
Solar/Wind Harmer
3.228
3138133OCRAN
Solar/Wind Harmer
-0.011
3143873LANEXA
Solar/Wind Harmer
-0.008
957831AF2-077 GEN
Solar/Wind Harmer
0.361
3138283WHITEMARSH
Solar/Wind Harmer
0.019
3142433PROV 92
Adder
0.206
3142433PROV 92
Adder
0.206
971167AH1-042 GEN
Solar/Wind Harmer
11.004
315976AC1-164 GENA
Solar/Wind Harmer
9.38
316169AC1-164_GENC
Solar/Wind Harmer
8.103
315975AC1-164 GENB
Solar/Wind Harmer
0.278
3141426STAFORD
Solar/Wind Helper
0.031
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.805
3142433PROV 92
Solar/Wind Harmer
-0.047
3142433PROV 92
Adder
0.206
3142433PROV 92
Adder
0.206
971317AH1-138 GEN
Solar/Wind Harmer
1.142
316159AE1-175 C
Solar/Wind Harmer
0.224
3138126ROCKLANDING
Solar/Wind Harmer
0.024
944631AF1-128 GEN
Adder
29.65
3141766HARMONY
Solar/Wind Harmer
1.381
316203AE2-005 GEN
Solar/Wind Harmer
6.476
3142433PROV 92
Adder
0.206
3142433PROV 92
Adder
0.206
316382AG1-145 C
Solar/Wind Harmer
0.252
3150921YORKTN3
Adder
1.799
3144216WINCHST
Adder
0.26
3142946ENON
Solar/Wind Harmer
-0.002
970293AG2-193 GEN
Solar/Wind Harmer
0.865
316441AF1-014 GEN
Solar/Wind Harmer
1.035
316075AC2-137 C
Solar/Wind Harmer
0.211
3142946ENON
Solar/Wind Harmer
-0.001
CPLELTFEXP_CPLE->PJM
CLTF
1.972
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.797
LAGNLTFEXP_LAGN->PJM
CLTF
1.464
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.333
TVALTFEXP_TVA->PJM
CLTF
0.74
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.655
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.545
MECLTFEXP_MEC->PJM
CLTF
0.723
SIGELTFEXP_SIGE->PJM
CLTF
0.022
NYPJM->LTFIMP_NY
CLTF
0.557
LGEELTFEXP_LGEE->PJM
CLTF
0.271
WECLTFEXP_WEC->PJM
CLTF
0.135

Details for AG1-135 TP-3GARNER 115.0 kV Ckt 1 line l/o DVP_P4-2: 65T1021_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG1-135 TP-3GARNER 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 65T1021_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.01 %
Rating:249.0 MVA
Rating Type:C
MVA to Mitigate:301.31
MW Contribution:19.99
Bus #Bus NameTypeMW Contribution
962981AG1-147 GEN
Solar/Wind Harmer
55.278
970575AG2-366 GEN
50/50
19.992
316484AD2-074 GEN
Solar/Wind Harmer
31.807
962971AG1-146 GEN
Solar/Wind Harmer
23.69
970009AG2-005 GEN
Solar/Wind Harmer
15.794
316487AF1-042 GEN
Solar/Wind Harmer
16.643
961951AG1-038 GEN
Solar/Wind Harmer
16.643
962861AG1-135 GEN
Solar/Wind Harmer
47.381
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.023
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.07
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.014
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.105
NYPJM->LTFIMP_NY
CLTF
0.022
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.023

Details for AG1-135 TP-3GARNER 115.0 kV Ckt 1 line l/o DVP_P4-4: LANCAS SC392_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG1-135 TP-3GARNER 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-4: LANCAS SC392_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.99 %
Rating:249.0 MVA
Rating Type:C
MVA to Mitigate:301.25
MW Contribution:19.99
Bus #Bus NameTypeMW Contribution
962981AG1-147 GEN
Solar/Wind Harmer
55.278
316487AF1-042 GEN
Solar/Wind Harmer
16.643
961951AG1-038 GEN
Solar/Wind Harmer
16.643
962861AG1-135 GEN
Solar/Wind Harmer
47.381
970575AG2-366 GEN
50/50
19.992
316484AD2-074 GEN
Solar/Wind Harmer
31.807
962971AG1-146 GEN
Solar/Wind Harmer
23.69
970009AG2-005 GEN
Solar/Wind Harmer
15.794
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.023
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.07
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.014
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.105
NYPJM->LTFIMP_NY
CLTF
0.022
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.023

Details for AG1-135 TP-3GARNER 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
AG1-135 TP-3GARNER 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 65_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.34 %
Rating:203.98 MVA
Rating Type:B
MVA to Mitigate:235.27
MW Contribution:19.99
Bus #Bus NameTypeMW Contribution
970575AG2-366 GEN
50/50
19.992
962971AG1-146 GEN
Solar/Wind Harmer
17.993
970009AG2-005 GEN
Solar/Wind Harmer
8.397
962861AG1-135 GEN
Solar/Wind Harmer
35.985
962981AG1-147 GEN
Solar/Wind Harmer
41.983
970327AG2-215 GEN
Solar/Wind Harmer
36.905
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.023
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.07
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.014
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.105
NYPJM->LTFIMP_NY
CLTF
0.022
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.023

Details for AG1-135 TP-3GARNER 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2016-85_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
AG1-135 TP-3GARNER 115.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2016-85_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:114.36 %
Rating:249.0 MVA
Rating Type:C
MVA to Mitigate:284.75
MW Contribution:12.64
Bus #Bus NameTypeMW Contribution
962981AG1-147 GEN
Solar/Wind Harmer
34.948
3141783LANCAST
Solar/Wind Harmer
-0.042
3141783LANCAST
Solar/Wind Harmer
-0.028
3138133OCRAN
Solar/Wind Harmer
-0.02
3141913WHIT STONE
Solar/Wind Harmer
-0.063
315662AE1-191 GEN
Solar/Wind Harmer
6.607
315666AE1-190 GEN
Solar/Wind Harmer
1.652
957601AF2-054 GEN
Solar/Wind Harmer
1.64
3141873WAN 176
Solar/Wind Harmer
-0.011
957831AF2-077 GEN
Solar/Wind Harmer
0.827
3138283WHITEMARSH
Solar/Wind Harmer
0.043
3141813NORNECK
Solar/Wind Helper
0.269
316487AF1-042 GEN
Solar/Wind Harmer
11.269
316441AF1-014 GEN
Solar/Wind Harmer
3.695
316077AC2-138 C
Solar/Wind Helper
0.253
970575AG2-366 GEN
50/50
12.64
316484AD2-074 GEN
Solar/Wind Harmer
21.536
970009AG2-005 GEN
Solar/Wind Harmer
10.694
962971AG1-146 GEN
Solar/Wind Harmer
14.978
316203AE2-005 GEN
Solar/Wind Harmer
23.11
316280AD1-041 GEN
Solar/Wind Harmer
4.129
316156AD2-030 GEN
Solar/Wind Harmer
1.463
3141873WAN 176
Solar/Wind Harmer
6.504
316404AE1-155 C
Solar/Wind Helper
4.711
962861AG1-135 GEN
Solar/Wind Harmer
34.61
961951AG1-038 GEN
Solar/Wind Harmer
11.269
3138133OCRAN
Solar/Wind Harmer
-0.039
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.018
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.054
CPLELTFEXP_CPLE->PJM
CLTF
0.123
MDUPJM->LTFIMP_MDU
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.009
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.221
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.005
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.051
NYPJM->LTFIMP_NY
CLTF
0.07

Details for AG1-135 TP-3GARNER 115.0 kV Ckt 1 line l/o DVP_P2-2: HARMONY V B2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG1-135 TP-3GARNER 115.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: HARMONY V B2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:103.58 %
Rating:249.0 MVA
Rating Type:C
MVA to Mitigate:257.92
MW Contribution:12.87
Bus #Bus NameTypeMW Contribution
962981AG1-147 GEN
Solar/Wind Harmer
35.587
3141783LANCAST
Solar/Wind Harmer
-0.043
3141783LANCAST
Solar/Wind Harmer
-0.028
3138133OCRAN
Solar/Wind Harmer
-0.02
3141913WHIT STONE
Solar/Wind Harmer
-0.064
315662AE1-191 GEN
Solar/Wind Harmer
5.36
315666AE1-190 GEN
Solar/Wind Harmer
1.34
3143873LANEXA
Solar/Wind Harmer
-0.004
3141813NORNECK
Solar/Wind Helper
0.244
970575AG2-366 GEN
50/50
12.871
3141843SHACKLE
50/50
1.722
316484AD2-074 GEN
Solar/Wind Harmer
21.902
3141843SHACKLE
50/50
1.722
962861AG1-135 GEN
Solar/Wind Harmer
35.153
961951AG1-038 GEN
Solar/Wind Harmer
11.461
3138133OCRAN
Solar/Wind Harmer
-0.04
971777AH1-397 GEN
Solar/Wind Harmer
4.195
970009AG2-005 GEN
Solar/Wind Harmer
10.875
962971AG1-146 GEN
Solar/Wind Harmer
15.252
316280AD1-041 GEN
Solar/Wind Harmer
3.35
316203AE2-005 GEN
Solar/Wind Harmer
15.145
316404AE1-155 C
Solar/Wind Helper
4.496
316487AF1-042 GEN
Solar/Wind Harmer
11.461
316441AF1-014 GEN
Solar/Wind Harmer
2.421
316077AC2-138 C
Solar/Wind Helper
0.229
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.018
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.054
CPLELTFEXP_CPLE->PJM
CLTF
0.028
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.035
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.07
NYPJM->LTFIMP_NY
CLTF
0.043

Details for AG1-135 TP-3GARNER 115.0 kV Ckt 1 line l/o DVP_P4-2: 8962_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG1-135 TP-3GARNER 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 8962_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.48 %
Rating:249.0 MVA
Rating Type:C
MVA to Mitigate:257.66
MW Contribution:19.99
Bus #Bus NameTypeMW Contribution
970575AG2-366 GEN
50/50
19.991
316484AD2-074 GEN
Solar/Wind Harmer
31.805
962971AG1-146 GEN
Solar/Wind Harmer
23.689
970009AG2-005 GEN
Solar/Wind Harmer
15.793
3141913WHIT STONE
Solar/Wind Harmer
-0.126
3141783LANCAST
Solar/Wind Harmer
-0.075
3141783LANCAST
Solar/Wind Harmer
-0.05
3138133OCRAN
Solar/Wind Harmer
-0.038
962981AG1-147 GEN
Solar/Wind Harmer
55.274
316487AF1-042 GEN
Solar/Wind Harmer
16.642
961951AG1-038 GEN
Solar/Wind Harmer
16.642
3138133OCRAN
Solar/Wind Harmer
-0.075
962861AG1-135 GEN
Solar/Wind Harmer
47.378
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.026
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.082
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.017
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.122
NYPJM->LTFIMP_NY
CLTF
0.026
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.027

Details for AG1-135 TP-3GARNER 115.0 kV Ckt 1 line l/o DVP_P4-2: 17662_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG1-135 TP-3GARNER 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 17662_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.46 %
Rating:249.0 MVA
Rating Type:C
MVA to Mitigate:257.62
MW Contribution:19.99
Bus #Bus NameTypeMW Contribution
3141913WHIT STONE
Solar/Wind Harmer
-0.126
3141783LANCAST
Solar/Wind Harmer
-0.075
3141783LANCAST
Solar/Wind Harmer
-0.05
3138133OCRAN
Solar/Wind Harmer
-0.038
962981AG1-147 GEN
Solar/Wind Harmer
55.274
970575AG2-366 GEN
50/50
19.991
316484AD2-074 GEN
Solar/Wind Harmer
31.805
962971AG1-146 GEN
Solar/Wind Harmer
23.689
970009AG2-005 GEN
Solar/Wind Harmer
15.793
961951AG1-038 GEN
Solar/Wind Harmer
16.642
3138133OCRAN
Solar/Wind Harmer
-0.075
962861AG1-135 GEN
Solar/Wind Harmer
47.378
316487AF1-042 GEN
Solar/Wind Harmer
16.642
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.026
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.082
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.017
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.122
NYPJM->LTFIMP_NY
CLTF
0.026
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.027

Details for AG1-135 TP-3GARNER 115.0 kV Ckt 1 line l/o DVP_P4-5: L262_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG1-135 TP-3GARNER 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: L262_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.46 %
Rating:249.0 MVA
Rating Type:C
MVA to Mitigate:257.62
MW Contribution:19.99
Bus #Bus NameTypeMW Contribution
3141913WHIT STONE
Solar/Wind Harmer
-0.126
3141783LANCAST
Solar/Wind Harmer
-0.075
3141783LANCAST
Solar/Wind Harmer
-0.05
3138133OCRAN
Solar/Wind Harmer
-0.038
962981AG1-147 GEN
Solar/Wind Harmer
55.274
316487AF1-042 GEN
Solar/Wind Harmer
16.642
970575AG2-366 GEN
50/50
19.991
316484AD2-074 GEN
Solar/Wind Harmer
31.805
962971AG1-146 GEN
Solar/Wind Harmer
23.689
970009AG2-005 GEN
Solar/Wind Harmer
15.793
961951AG1-038 GEN
Solar/Wind Harmer
16.642
3138133OCRAN
Solar/Wind Harmer
-0.075
962861AG1-135 GEN
Solar/Wind Harmer
47.378
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.026
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.082
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.017
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.122
NYPJM->LTFIMP_NY
CLTF
0.026
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.027

Details for AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: L4T65_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: L4T65_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:183.5 %
Rating:249.0 MVA
Rating Type:C
MVA to Mitigate:456.93
MW Contribution:19.98
Bus #Bus NameTypeMW Contribution
962981AG1-147 GEN
Solar/Wind Harmer
55.253
970575AG2-366 GEN
50/50
19.983
316484AD2-074 GEN
Solar/Wind Harmer
31.793
316404AE1-155 C
Solar/Wind Harmer
24.362
962971AG1-146 GEN
Solar/Wind Harmer
23.68
970009AG2-005 GEN
Solar/Wind Harmer
15.786
316487AF1-042 GEN
Solar/Wind Harmer
16.636
958261AF2-120 GEN
Solar/Wind Harmer
48.938
966661AG1-536 GEN
50/50
31.973
961951AG1-038 GEN
Solar/Wind Harmer
16.636
962861AG1-135 GEN
Solar/Wind Harmer
47.359
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.048
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.148
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.03
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.221
NYPJM->LTFIMP_NY
CLTF
0.047
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.049

Details for AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 6552_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 6552_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:183.5 %
Rating:249.0 MVA
Rating Type:C
MVA to Mitigate:456.93
MW Contribution:19.98
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
31.973
961951AG1-038 GEN
Solar/Wind Harmer
16.636
962861AG1-135 GEN
Solar/Wind Harmer
47.359
962981AG1-147 GEN
Solar/Wind Harmer
55.253
970575AG2-366 GEN
50/50
19.983
316484AD2-074 GEN
Solar/Wind Harmer
31.793
316404AE1-155 C
Solar/Wind Harmer
24.362
962971AG1-146 GEN
Solar/Wind Harmer
23.68
970009AG2-005 GEN
Solar/Wind Harmer
15.786
316487AF1-042 GEN
Solar/Wind Harmer
16.636
958261AF2-120 GEN
Solar/Wind Harmer
48.938
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.048
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.148
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.03
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.221
NYPJM->LTFIMP_NY
CLTF
0.047
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.049

Details for AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1059_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1059_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:174.07 %
Rating:203.98 MVA
Rating Type:B
MVA to Mitigate:355.06
MW Contribution:19.98
Bus #Bus NameTypeMW Contribution
970575AG2-366 GEN
50/50
19.983
316404AE1-155 C
Solar/Wind Harmer
0.253
962971AG1-146 GEN
Solar/Wind Harmer
17.985
970009AG2-005 GEN
Solar/Wind Harmer
8.393
962981AG1-147 GEN
Solar/Wind Harmer
41.964
970327AG2-215 GEN
Solar/Wind Harmer
36.888
966661AG1-536 GEN
50/50
31.973
962861AG1-135 GEN
Solar/Wind Harmer
35.969
958261AF2-120 GEN
Solar/Wind Harmer
37.168
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.048
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.148
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.03
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.221
NYPJM->LTFIMP_NY
CLTF
0.047
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.049

Details for AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 65T1059_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 65T1059_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.93 %
Rating:249.0 MVA
Rating Type:C
MVA to Mitigate:298.62
MW Contribution:19.99
Bus #Bus NameTypeMW Contribution
962981AG1-147 GEN
Solar/Wind Harmer
55.278
970575AG2-366 GEN
50/50
19.992
316484AD2-074 GEN
Solar/Wind Harmer
31.807
962971AG1-146 GEN
Solar/Wind Harmer
23.69
970009AG2-005 GEN
Solar/Wind Harmer
15.794
316487AF1-042 GEN
Solar/Wind Harmer
16.643
961951AG1-038 GEN
Solar/Wind Harmer
16.643
962861AG1-135 GEN
Solar/Wind Harmer
47.381
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.023
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.07
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.014
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.105
NYPJM->LTFIMP_NY
CLTF
0.022
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.023

Details for AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65_SRT-A-4


Base Case Flowgate

Area:DVP
Facility Description:
AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 65_SRT-A-4
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.08 %
Rating:203.98 MVA
Rating Type:B
MVA to Mitigate:232.7
MW Contribution:19.99
Bus #Bus NameTypeMW Contribution
970575AG2-366 GEN
50/50
19.992
962971AG1-146 GEN
Solar/Wind Harmer
17.993
970009AG2-005 GEN
Solar/Wind Harmer
8.397
962981AG1-147 GEN
Solar/Wind Harmer
41.983
970327AG2-215 GEN
Solar/Wind Harmer
36.905
962861AG1-135 GEN
Solar/Wind Harmer
35.985
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.023
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.07
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.014
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.105
NYPJM->LTFIMP_NY
CLTF
0.022
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.023

Details for AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 105942_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 105942_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.09 %
Rating:249.0 MVA
Rating Type:C
MVA to Mitigate:279.09
MW Contribution:19.99
Bus #Bus NameTypeMW Contribution
962981AG1-147 GEN
Solar/Wind Harmer
55.278
316487AF1-042 GEN
Solar/Wind Harmer
16.643
961951AG1-038 GEN
Solar/Wind Harmer
16.643
962861AG1-135 GEN
Solar/Wind Harmer
47.381
970575AG2-366 GEN
50/50
19.992
316484AD2-074 GEN
Solar/Wind Harmer
31.807
962971AG1-146 GEN
Solar/Wind Harmer
23.69
970009AG2-005 GEN
Solar/Wind Harmer
15.794
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.023
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.07
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.014
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.105
NYPJM->LTFIMP_NY
CLTF
0.022
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.023

Details for AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 224-2208_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 224-2208_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.26 %
Rating:249.0 MVA
Rating Type:C
MVA to Mitigate:249.65
MW Contribution:12.35
Bus #Bus NameTypeMW Contribution
962981AG1-147 GEN
Solar/Wind Harmer
34.134
3141813NORNECK
Solar/Wind Harmer
-0.042
316223AC1-118
Solar/Wind Harmer
0.734
944491AF1-114 GEN
Solar/Wind Harmer
6.179
3141783LANCAST
Solar/Wind Helper
0.393
3141783LANCAST
Solar/Wind Helper
0.262
3138133OCRAN
Solar/Wind Helper
0.167
3141913WHIT STONE
Solar/Wind Helper
0.513
957601AF2-054 GEN
Solar/Wind Helper
0.459
3141873WAN 176
Solar/Wind Helper
0.068
315662AE1-191 GEN
Solar/Wind Helper
1.522
315666AE1-190 GEN
Solar/Wind Helper
0.381
957831AF2-077 GEN
Solar/Wind Helper
0.255
316059AD1-063 C
Solar/Wind Helper
0.188
3150341NORNECKC1
50/50
4.148
3150341NORNECKC1
50/50
4.115
963611AG1-210 GEN
50/50
1.327
966661AG1-536 GEN
50/50
15.416
3150351NORNECKC2
50/50
3.949
961951AG1-038 GEN
Solar/Wind Harmer
9.416
962861AG1-135 GEN
Solar/Wind Harmer
23.887
316337AD2-073 GEN
Solar/Wind Harmer
0.802
972135AH1-637 GEN
Solar/Wind Harmer
2.325
957971AF2-091 GEN
Solar/Wind Harmer
2.101
3138133OCRAN
Solar/Wind Helper
0.334
3141766HARMONY
Solar/Wind Helper
0.037
970575AG2-366 GEN
50/50
12.345
3150351NORNECKC2
50/50
4.016
962971AG1-146 GEN
Solar/Wind Harmer
14.629
316484AD2-074 GEN
Solar/Wind Harmer
17.994
970009AG2-005 GEN
Solar/Wind Harmer
8.935
316404AE1-155 C
Solar/Wind Harmer
11.747
3141906WESTMOR
Solar/Wind Harmer
-0.011
970737AG2-469 GEN
Solar/Wind Harmer
12.426
3141316ARNOLDS
Adder
0.256
3150331BIRCHWDA
Adder
13.746
316156AD2-030 GEN
Solar/Wind Helper
0.516
316280AD1-041 GEN
Solar/Wind Helper
0.951
957191AF2-013 GEN
50/50
11.527
316487AF1-042 GEN
Solar/Wind Harmer
9.416
958261AF2-120 GEN
Solar/Wind Harmer
23.597
316077AC2-138 C
Solar/Wind Harmer
0.885
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.082
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.257
G-007ALTFEXP_G-007A->PJM
CMTX
0.514
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.882
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.373
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.155
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.464
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.307

Details for AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 2076T2208_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 2076T2208_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.23 %
Rating:249.0 MVA
Rating Type:C
MVA to Mitigate:249.56
MW Contribution:11.58
Bus #Bus NameTypeMW Contribution
962981AG1-147 GEN
Solar/Wind Harmer
32.026
3141813NORNECK
Solar/Wind Harmer
-0.03
3141783LANCAST
Solar/Wind Helper
0.421
3141783LANCAST
Solar/Wind Helper
0.28
3138133OCRAN
Solar/Wind Helper
0.175
3141913WHIT STONE
Solar/Wind Helper
0.533
957601AF2-054 GEN
Solar/Wind Helper
0.44
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.377
315666AE1-190 GEN
Solar/Wind Helper
0.344
957831AF2-077 GEN
Solar/Wind Helper
0.221
316059AD1-063 C
Solar/Wind Helper
0.134
966661AG1-536 GEN
50/50
13.355
3150351NORNECKC2
50/50
2.836
961951AG1-038 GEN
Solar/Wind Harmer
8.614
962861AG1-135 GEN
Solar/Wind Harmer
21.038
964211AG1-282 GEN
Solar/Wind Harmer
0.411
3141726DUNNSVL
Solar/Wind Harmer
-0.054
3138133OCRAN
Solar/Wind Helper
0.35
3141766HARMONY
Solar/Wind Helper
0.027
970575AG2-366 GEN
50/50
11.583
3150351NORNECKC2
50/50
2.884
962971AG1-146 GEN
Solar/Wind Harmer
13.726
316484AD2-074 GEN
Solar/Wind Harmer
16.462
970009AG2-005 GEN
Solar/Wind Harmer
8.174
316404AE1-155 C
Solar/Wind Harmer
10.176
316156AD2-030 GEN
Solar/Wind Helper
0.495
316280AD1-041 GEN
Solar/Wind Helper
0.861
3150341NORNECKC1
50/50
2.979
3150341NORNECKC1
50/50
2.955
963611AG1-210 GEN
50/50
0.953
316487AF1-042 GEN
Solar/Wind Harmer
8.614
958261AF2-120 GEN
Solar/Wind Harmer
20.442
316077AC2-138 C
Solar/Wind Harmer
0.635
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.018
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.057
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.018
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.089
NYPJM->LTFIMP_NY
CLTF
0.012
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.033

Details for AG2-469 TP-6OAKGROV 230.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-469 TP-6OAKGROV 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.4 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:813.65
MW Contribution:3.79
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
5.235
3142433PROV 92
50/50
0.234
3142433PROV 92
50/50
0.234
316223AC1-118
Solar/Wind Harmer
1.265
3141813NORNECK
Solar/Wind Harmer
-0.032
962981AG1-147 GEN
Solar/Wind Harmer
10.492
3141783LANCAST
Solar/Wind Harmer
-0.013
3141783LANCAST
Solar/Wind Harmer
-0.008
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.02
957601AF2-054 GEN
Solar/Wind Harmer
0.521
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
2.024
315666AE1-190 GEN
Solar/Wind Harmer
0.506
316059AD1-063 C
Solar/Wind Harmer
0.374
316314AB2-024 C
Solar/Wind Harmer
1.369
3143873LANEXA
Solar/Wind Harmer
-0.009
957831AF2-077 GEN
Solar/Wind Harmer
0.394
3138283WHITEMARSH
Solar/Wind Harmer
0.02
971167AH1-042 GEN
Solar/Wind Harmer
11.777
315976AC1-164 GENA
Solar/Wind Harmer
10.494
316169AC1-164_GENC
Solar/Wind Harmer
9.066
315975AC1-164 GENB
Solar/Wind Harmer
0.31
972265AH1-717 GEN
Adder
4.971
3151201GRAVEL4
Adder
4.66
3151191GRAVEL3
Adder
4.601
3151211GRAVEL5
Adder
4.601
971445AH1-216 GEN
Solar/Wind Harmer
4.341
316369SG1_INVT
Solar/Wind Harmer
1.252
316132AB2-190 GEN1
Solar/Wind Harmer
0.698
3152611GOSPORTB
Adder
0.757
3152621GOSPORTC
Adder
0.642
3152601GOSPORTA
Adder
0.592
3151081ELIZAR1
Adder
5.443
3151091ELIZAR2
Adder
5.349
316312AB1-027
Solar/Wind Harmer
0.224
316305AF2-043 C
Solar/Wind Harmer
0.198
957871AF2-081 GEN
Solar/Wind Harmer
3.272
319010AE1-072 C
Solar/Wind Harmer
1.318
3146406KITTY HAWK
Solar/Wind Harmer
0.005
313526AB2-022
Solar/Wind Harmer
0.173
315835AF2-110_GEN
Solar/Wind Harmer
0.803
3146486SUNBURY
Solar/Wind Harmer
-0.006
3146486SUNBURY
Solar/Wind Harmer
-0.006
316321Z2-027
Solar/Wind Harmer
0.172
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.117
3141426STAFORD
Solar/Wind Helper
0.031
3150351NORNECKC2
50/50
3.081
970575AG2-366 GEN
50/50
3.795
315749AE2-041 GEN
50/50
5.235
3141843SHACKLE
50/50
0.789
3142433PROV 92
50/50
0.234
3142433PROV 92
50/50
0.234
970737AG2-469 GEN
Solar/Wind Harmer
26.869
3141906WESTMOR
Solar/Wind Harmer
-0.019
316404AE1-155 C
Solar/Wind Harmer
5.377
316484AD2-074 GEN
Solar/Wind Harmer
6.411
970009AG2-005 GEN
Solar/Wind Harmer
3.184
962971AG1-146 GEN
Solar/Wind Harmer
4.497
316156AD2-030 GEN
Solar/Wind Harmer
0.465
3141873WAN 176
Solar/Wind Harmer
2.065
316280AD1-041 GEN
Solar/Wind Harmer
1.265
3141766HARMONY
Solar/Wind Harmer
1.472
316203AE2-005 GEN
Solar/Wind Harmer
6.895
316382AG1-145 C
Solar/Wind Harmer
0.286
3150921YORKTN3
Adder
2.058
3144216WINCHST
Adder
0.298
3142946ENON
Solar/Wind Harmer
-0.003
970293AG2-193 GEN
Solar/Wind Harmer
0.937
3151221GRAVEL6
Adder
4.655
3151171GRAVELC
Adder
0.896
961611AG1-000B GEN
Solar/Wind Harmer
1.5
3145336SMITFLD
Solar/Wind Harmer
-0.003
315778AD1-151 GEN
Solar/Wind Harmer
6.033
970129AG2-093 GEN
Solar/Wind Harmer
3.879
970133AG2-095 GEN
Solar/Wind Harmer
0.763
3144536CHRHLND
Solar/Wind Harmer
-0.001
315773AC2-141 GEN
Solar/Wind Harmer
2.827
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.513
3143096IRON208
Adder
0.248
3143096IRON208
Adder
0.243
3142416OLDCHRC
Solar/Wind Harmer
0.669
944581AF1-123 GEN
Solar/Wind Harmer
30.093
944601AF1-125 GEN
Solar/Wind Harmer
29.624
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.795
316320Y1-086
Solar/Wind Harmer
0.376
316435W1029_GEN3
Solar/Wind Harmer
1.147
3150341NORNECKC1
50/50
3.183
3150341NORNECKC1
50/50
3.157
963611AG1-210 GEN
50/50
1.018
316077AC2-138 C
Solar/Wind Harmer
0.679
958261AF2-120 GEN
Solar/Wind Harmer
10.801
316487AF1-042 GEN
Solar/Wind Harmer
3.355
316441AF1-014 GEN
Solar/Wind Harmer
1.102
316075AC2-137 C
Solar/Wind Harmer
0.232
3142946ENON
Solar/Wind Harmer
-0.001
316033AB2-134 GEN
Solar/Wind Harmer
2.26
315697AD1-025 GEN
Solar/Wind Harmer
1.418
316236AE1-162_GEN
Solar/Wind Harmer
0.211
316036AC1-147 C
Solar/Wind Harmer
0.18
3150991CHESPKB
Adder
0.623
3150991CHESPKB
Adder
0.608
316316AC1-027 C
Solar/Wind Harmer
0.204
3142956BIRDNECK
Solar/Wind Harmer
0.356
316185AD1-033 GEN
Solar/Wind Harmer
0.698
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316339AD2-160 GEN
Solar/Wind Harmer
0.442
316018AA1-139 ULT2
Solar/Wind Harmer
0.561
316017AA1-139 ULT1
Solar/Wind Harmer
0.53
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.771
3130086AYDLETT
Solar/Wind Harmer
-0.026
3150691DARBY 3
Adder
4.141
3150701DARBY 4
Adder
4.131
3150681DARBY 2
Adder
4.127
3150671DARBY 1
Adder
4.122
3146386ELIZ CT
Solar/Wind Harmer
-0.006
316431W1029_GEN1
Solar/Wind Harmer
1.147
316433W1029_GEN2
Solar/Wind Harmer
1.147
3150351NORNECKC2
50/50
3.03
966661AG1-536 GEN
50/50
7.057
3141843SHACKLE
50/50
0.789
3142433PROV 92
50/50
0.234
3142433PROV 92
50/50
0.234
316337AD2-073 GEN
Solar/Wind Harmer
1.055
964211AG1-282 GEN
Solar/Wind Harmer
0.906
3141726DUNNSVL
Solar/Wind Harmer
-0.12
962861AG1-135 GEN
Solar/Wind Harmer
10.214
961951AG1-038 GEN
Solar/Wind Harmer
3.355
3138133OCRAN
Solar/Wind Harmer
-0.012
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.921
3142433PROV 92
Solar/Wind Harmer
-0.051
971317AH1-138 GEN
Solar/Wind Harmer
1.288
316159AE1-175 C
Solar/Wind Harmer
0.255
3138126ROCKLANDING
Solar/Wind Harmer
0.028
944631AF1-128 GEN
Adder
32.671
3151171GRAVELC
Adder
0.681
961611AG1-000B GEN
Solar/Wind Harmer
3.515
971647AH1-324 GEN
Solar/Wind Harmer
3.532
3145336SMITFLD
Solar/Wind Harmer
-0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.102
316458AB2-190 GEN2
Solar/Wind Harmer
0.698
970129AG2-093 GEN
Solar/Wind Harmer
1.571
316072AD1-144
Solar/Wind Harmer
0.139
316294AC1-161 GEN
Solar/Wind Harmer
2.186
316375AC2-012 GEN
Solar/Wind Harmer
2.311
3150981CHESPKA
Adder
0.742
3143096IRON208
Adder
0.248
3142416OLDCHRC
Solar/Wind Harmer
-0.017
3142416OLDCHRC
Solar/Wind Harmer
-0.007
944591AF1-124 GEN
Solar/Wind Harmer
30.202
316246AF1-032 C
Solar/Wind Harmer
0.133
316388AE2-253 GEN
Solar/Wind Harmer
0.442
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316093AE2-104_GEN
Solar/Wind Harmer
1.867
CPLELTFEXP_CPLE->PJM
CLTF
2.253
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.492
LAGNLTFEXP_LAGN->PJM
CLTF
1.608
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.892
TVALTFEXP_TVA->PJM
CLTF
0.81
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.974
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.777
MECLTFEXP_MEC->PJM
CLTF
0.779
SIGELTFEXP_SIGE->PJM
CLTF
0.024
NYPJM->LTFIMP_NY
CLTF
0.564
LGEELTFEXP_LGEE->PJM
CLTF
0.288
WECLTFEXP_WEC->PJM
CLTF
0.144

Details for AG2-469 TP-6OAKGROV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-469 TP-6OAKGROV 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.13 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:657.97
MW Contribution:3.67
Bus #Bus NameTypeMW Contribution
3150351NORNECKC2
50/50
2.96
966661AG1-536 GEN
50/50
6.86
3141843SHACKLE
50/50
0.748
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
971353AH1-157 GEN
50/50
7.442
970017AG2-010 GEN
50/50
4.725
3150641CHESTS8
50/50
0.204
944631AF1-128 GEN
50/50
32.114
316337AD2-073 GEN
Solar/Wind Harmer
0.299
3141726DUNNSVL
Solar/Wind Harmer
1.045
962861AG1-135 GEN
Solar/Wind Harmer
7.535
3138133OCRAN
Solar/Wind Harmer
0.103
3141766HARMONY
Solar/Wind Harmer
0.028
971777AH1-397 GEN
Solar/Wind Harmer
0.364
3142433PROV 92
Solar/Wind Harmer
0.43
971317AH1-138 GEN
Solar/Wind Harmer
0.616
316159AE1-175 C
Solar/Wind Harmer
0.065
3138126ROCKLANDING
Solar/Wind Harmer
0.033
3142416OLDCHRC
Solar/Wind Harmer
0.15
3142416OLDCHRC
Solar/Wind Harmer
0.057
3151171GRAVELC
Adder
0.604
961611AG1-000B GEN
Solar/Wind Harmer
2.967
971647AH1-324 GEN
Solar/Wind Harmer
2.407
3150351NORNECKC2
50/50
3.01
970575AG2-366 GEN
50/50
3.666
315749AE2-041 GEN
50/50
4.959
3141843SHACKLE
50/50
0.748
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150921YORKTN3
50/50
1.939
3144216WINCHST
50/50
0.281
3151161SURRY 1
50/50
2.18
970737AG2-469 GEN
Solar/Wind Harmer
20.194
3141906WESTMOR
Solar/Wind Harmer
0.165
316404AE1-155 C
Solar/Wind Harmer
0.054
970009AG2-005 GEN
Solar/Wind Harmer
1.64
962971AG1-146 GEN
Solar/Wind Harmer
3.3
316156AD2-030 GEN
Solar/Wind Harmer
0.109
3141873WAN 176
Solar/Wind Harmer
2.617
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
1.86
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
3142946ENON
Solar/Wind Harmer
0.023
970293AG2-193 GEN
Solar/Wind Harmer
0.672
3142416OLDCHRC
Solar/Wind Harmer
0.558
3151221GRAVEL6
Adder
4.126
3151171GRAVELC
Adder
0.794
961611AG1-000B GEN
Solar/Wind Harmer
1.508
3150341NORNECKC1
50/50
3.109
3150341NORNECKC1
50/50
3.084
963611AG1-210 GEN
50/50
0.995
3150621CHESTS7
50/50
0.185
316077AC2-138 C
Solar/Wind Harmer
0.001
958261AF2-120 GEN
Solar/Wind Harmer
7.975
316075AC2-137 C
Solar/Wind Harmer
0.02
3142946ENON
Solar/Wind Harmer
0.007
316033AB2-134 GEN
Solar/Wind Harmer
0.003
315697AD1-025 GEN
Solar/Wind Harmer
0.063
315759AF1-018 GEN
50/50
4.959
3142433PROV 92
50/50
0.222
3142433PROV 92
50/50
0.222
3150611CHESTG7
50/50
0.403
3150631CHESTG8
50/50
0.397
971047AG2-646 GEN
50/50
11.288
972263AH1-716 GEN
50/50
33.088
316223AC1-118
Solar/Wind Harmer
0.296
3141813NORNECK
Solar/Wind Harmer
0.28
970327AG2-215 GEN
Solar/Wind Harmer
7.206
962981AG1-147 GEN
Solar/Wind Harmer
7.699
3141783LANCAST
Solar/Wind Harmer
0.11
3141783LANCAST
Solar/Wind Harmer
0.073
3138133OCRAN
Solar/Wind Harmer
0.052
3141913WHIT STONE
Solar/Wind Harmer
0.167
3141873WAN 176
Solar/Wind Harmer
0.029
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.092
316314AB2-024 C
Solar/Wind Harmer
0
3143873LANEXA
Solar/Wind Harmer
0.075
3138283WHITEMARSH
Solar/Wind Harmer
0.025
971167AH1-042 GEN
Solar/Wind Harmer
9.155
315976AC1-164 GENA
Solar/Wind Harmer
8.33
316169AC1-164_GENC
Solar/Wind Harmer
7.197
315975AC1-164 GENB
Solar/Wind Harmer
0.246
316312AB1-027
Solar/Wind Harmer
0.103
972265AH1-717 GEN
Adder
4.406
3151201GRAVEL4
Adder
4.131
3151191GRAVEL3
Adder
4.078
3151211GRAVEL5
Adder
4.078
316369SG1_INVT
Solar/Wind Harmer
0.002
3141426STAFORD
Solar/Wind Helper
0.031
CPLELTFEXP_CPLE->PJM
CLTF
2.028
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.282
LAGNLTFEXP_LAGN->PJM
CLTF
1.541
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.475
TVALTFEXP_TVA->PJM
CLTF
0.778
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.13
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.686
MECLTFEXP_MEC->PJM
CLTF
0.78
SIGELTFEXP_SIGE->PJM
CLTF
0.024
NYPJM->LTFIMP_NY
CLTF
0.546
LGEELTFEXP_LGEE->PJM
CLTF
0.294
WECLTFEXP_WEC->PJM
CLTF
0.148

Details for AG2-469 TP-6OAKGROV 230.0 kV Ckt 1 line l/o DVP_P4-2: 574T575_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-469 TP-6OAKGROV 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 574T575_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.7 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:752.83
MW Contribution:3.69
Bus #Bus NameTypeMW Contribution
315759AF1-018 GEN
50/50
5.03
316223AC1-118
Solar/Wind Harmer
1.248
3141813NORNECK
Solar/Wind Harmer
-0.031
962981AG1-147 GEN
Solar/Wind Harmer
10.212
3141783LANCAST
Solar/Wind Harmer
-0.012
3141783LANCAST
Solar/Wind Harmer
-0.008
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.019
957601AF2-054 GEN
Solar/Wind Harmer
0.501
3141873WAN 176
Solar/Wind Harmer
-0.003
315662AE1-191 GEN
Solar/Wind Harmer
1.949
315666AE1-190 GEN
Solar/Wind Harmer
0.487
316059AD1-063 C
Solar/Wind Harmer
0.359
316314AB2-024 C
Solar/Wind Harmer
1.313
3143873LANEXA
Solar/Wind Harmer
-0.008
957831AF2-077 GEN
Solar/Wind Harmer
0.374
3138283WHITEMARSH
Solar/Wind Harmer
0.019
3142433PROV 92
Adder
0.213
3142433PROV 92
Adder
0.213
971167AH1-042 GEN
Solar/Wind Harmer
11.391
315976AC1-164 GENA
Solar/Wind Harmer
9.806
316169AC1-164_GENC
Solar/Wind Harmer
8.472
315975AC1-164 GENB
Solar/Wind Harmer
0.29
972265AH1-717 GEN
Adder
4.643
3151201GRAVEL4
Adder
4.352
3151191GRAVEL3
Adder
4.297
3151211GRAVEL5
Adder
4.297
316312AB1-027
Solar/Wind Harmer
0.226
316369SG1_INVT
Solar/Wind Harmer
1.189
316132AB2-190 GEN1
Solar/Wind Harmer
0.669
971445AH1-216 GEN
Solar/Wind Harmer
4.026
3150351NORNECKC2
50/50
2.97
966661AG1-536 GEN
50/50
6.895
3141843SHACKLE
50/50
0.759
316337AD2-073 GEN
Solar/Wind Harmer
1.038
964211AG1-282 GEN
Solar/Wind Harmer
0.887
3141726DUNNSVL
Solar/Wind Harmer
-0.117
962861AG1-135 GEN
Solar/Wind Harmer
9.975
961951AG1-038 GEN
Solar/Wind Harmer
3.271
3138133OCRAN
Solar/Wind Harmer
-0.012
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.849
3142433PROV 92
Solar/Wind Harmer
-0.049
3142433PROV 92
Adder
0.213
3142433PROV 92
Adder
0.213
971317AH1-138 GEN
Solar/Wind Harmer
1.197
316159AE1-175 C
Solar/Wind Harmer
0.236
3138126ROCKLANDING
Solar/Wind Harmer
0.025
944631AF1-128 GEN
Adder
31.471
3151171GRAVELC
Adder
0.636
961611AG1-000B GEN
Solar/Wind Harmer
3.303
3142416OLDCHRC
Solar/Wind Harmer
-0.017
3142416OLDCHRC
Solar/Wind Harmer
-0.007
971647AH1-324 GEN
Solar/Wind Harmer
3.336
971069AG2-661 GEN
Solar/Wind Harmer
1.05
316458AB2-190 GEN2
Solar/Wind Harmer
0.669
970129AG2-093 GEN
Solar/Wind Harmer
1.508
3143096IRON208
Adder
0.245
3141426STAFORD
Solar/Wind Helper
0.032
3150351NORNECKC2
50/50
3.02
970575AG2-366 GEN
50/50
3.693
315749AE2-041 GEN
50/50
5.03
3141843SHACKLE
50/50
0.759
970737AG2-469 GEN
Solar/Wind Harmer
26.56
3141906WESTMOR
Solar/Wind Harmer
-0.018
316404AE1-155 C
Solar/Wind Harmer
5.254
316484AD2-074 GEN
Solar/Wind Harmer
6.251
970009AG2-005 GEN
Solar/Wind Harmer
3.104
962971AG1-146 GEN
Solar/Wind Harmer
4.377
316156AD2-030 GEN
Solar/Wind Harmer
0.448
3141873WAN 176
Solar/Wind Harmer
1.989
316280AD1-041 GEN
Solar/Wind Harmer
1.218
3141766HARMONY
Solar/Wind Harmer
1.415
316203AE2-005 GEN
Solar/Wind Harmer
6.637
3142433PROV 92
Adder
0.213
3142433PROV 92
Adder
0.213
316382AG1-145 C
Solar/Wind Harmer
0.265
3150921YORKTN3
Adder
1.899
3144216WINCHST
Adder
0.275
3142946ENON
Solar/Wind Harmer
-0.003
970293AG2-193 GEN
Solar/Wind Harmer
0.916
3151221GRAVEL6
Adder
4.347
3151171GRAVELC
Adder
0.836
961611AG1-000B GEN
Solar/Wind Harmer
1.409
3142416OLDCHRC
Solar/Wind Harmer
0.675
315778AD1-151 GEN
Solar/Wind Harmer
5.749
970129AG2-093 GEN
Solar/Wind Harmer
3.722
3143096IRON208
Adder
0.245
3143096IRON208
Adder
0.24
970133AG2-095 GEN
Solar/Wind Harmer
0.739
3145336SMITFLD
Solar/Wind Harmer
-0.003
3145336SMITFLD
Solar/Wind Harmer
-0.026
316072AD1-144
Solar/Wind Harmer
0.128
3150341NORNECKC1
50/50
3.12
3150341NORNECKC1
50/50
3.095
963611AG1-210 GEN
50/50
0.998
316077AC2-138 C
Solar/Wind Harmer
0.665
958261AF2-120 GEN
Solar/Wind Harmer
10.554
316487AF1-042 GEN
Solar/Wind Harmer
3.271
316441AF1-014 GEN
Solar/Wind Harmer
1.061
316075AC2-137 C
Solar/Wind Harmer
0.222
3142946ENON
Solar/Wind Harmer
-0.001
316033AB2-134 GEN
Solar/Wind Harmer
2.145
315697AD1-025 GEN
Solar/Wind Harmer
1.346
3150691DARBY 3
Adder
4.161
3150701DARBY 4
Adder
4.151
3150681DARBY 2
Adder
4.146
3150671DARBY 1
Adder
4.142
316236AE1-162_GEN
Solar/Wind Harmer
0.195
CPLELTFEXP_CPLE->PJM
CLTF
2.227
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.114
LAGNLTFEXP_LAGN->PJM
CLTF
1.695
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.918
TVALTFEXP_TVA->PJM
CLTF
0.856
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.654
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.955
MECLTFEXP_MEC->PJM
CLTF
0.859
SIGELTFEXP_SIGE->PJM
CLTF
0.026
NYPJM->LTFIMP_NY
CLTF
0.606
LGEELTFEXP_LGEE->PJM
CLTF
0.324
WECLTFEXP_WEC->PJM
CLTF
0.163
CONTINGENCY 'DVP_P4-2: 65T1021_SRT-A'
 OPEN BRANCH FROM BUS 313813 TO BUS 314178 CKT 1    /*3OCRAN       115.0 - 3LANCAST     115.0
 OPEN BRANCH FROM BUS 313813 TO BUS 314191 CKT 1    /*3OCRAN       115.0 - 3WHIT STONE  115.0
 OPEN BRANCH FROM BUS 313842 TO BUS 313870 CKT Z1   /*3RAPPAHNCK_1 115.0 - 3RAPPAHNCK   115.0
 OPEN BRANCH FROM BUS 313843 TO BUS 313870 CKT Z1   /*3RAPPAHNCK_2 115.0 - 3RAPPAHNCK   115.0
 OPEN BRANCH FROM BUS 313870 TO BUS 313900 CKT Z1   /*3RAPPAHNCK   115.0 - 3RAPP TR     115.0
 OPEN BRANCH FROM BUS 313870 TO BUS 314191 CKT 1    /*3RAPPAHNCK   115.0 - 3WHIT STONE  115.0
 OPEN BRANCH FROM BUS 313886 TO BUS 313900 CKT 1    /*3GREYSPT     115.0 - 3RAPP TR     115.0
 OPEN BRANCH FROM BUS 313886 TO BUS 313900 CKT 2    /*3GREYSPT     115.0 - 3RAPP TR     115.0
 OPEN BRANCH FROM BUS 313886 TO BUS 314174 CKT 1    /*3GREYSPT     115.0 - 3HARMONY     115.0
 OPEN BRANCH FROM BUS 314178 TO BUS 314400 CKT 1    /*3LANCAST     115.0 - 3LANCA_1     115.0
 OPEN BRANCH FROM BUS 314178 TO BUS 962970 CKT 1    /*3LANCAST     115.0 - AG1-146 TP   115.0
 OPEN BUS 313813                                    /*3OCRAN       115.0
 OPEN BUS 313842                                    /*3RAPPAHNCK_1 115.0
 OPEN BUS 313843                                    /*3RAPPAHNCK_2 115.0
 OPEN BUS 313870                                    /*3RAPPAHNCK   115.0
 OPEN BUS 313886                                    /*3GREYSPT     115.0
 OPEN BUS 313900                                    /*3RAPP TR     115.0
 OPEN BUS 314178                                    /*3LANCAST     115.0
 OPEN BUS 314191                                    /*3WHIT STONE  115.0
 OPEN BUS 314400                                    /*3LANCA_1     115.0
END
CONTINGENCY 'DVP_P4-4: LANCAS SC392_SRT-A'
 OPEN BRANCH FROM BUS 313813 TO BUS 314178 CKT 1   /*3OCRAN       115.0 - 3LANCAST     115.0
 OPEN BRANCH FROM BUS 313813 TO BUS 314191 CKT 1   /*3OCRAN       115.0 - 3WHIT STONE  115.0
 OPEN BRANCH FROM BUS 313870 TO BUS 314191 CKT 1   /*3RAPPAHNCK   115.0 - 3WHIT STONE  115.0
 OPEN BRANCH FROM BUS 314178 TO BUS 314400 CKT 1   /*3LANCAST     115.0 - 3LANCA_1     115.0
 OPEN BRANCH FROM BUS 314178 TO BUS 962970 CKT 1   /*3LANCAST     115.0 - AG1-146 TP   115.0
 OPEN BUS 313813                                   /*3OCRAN       115.0
 OPEN BUS 314178                                   /*3LANCAST     115.0
 OPEN BUS 314191                                   /*3WHIT STONE  115.0
 OPEN BUS 314400                                   /*3LANCA_1     115.0
END
CONTINGENCY 'DVP_P7-1: LN 2016-85_SRT-A-1'
 OPEN BRANCH FROM BUS 313053 TO BUS 314189 CKT 1   /*6PAPERMILL   230.0 - 6PAPERMIL TP 230.0
 OPEN BRANCH FROM BUS 314174 TO BUS 314176 CKT 1   /*3HARMONY     115.0 - 6HARMONY     230.0
 OPEN BRANCH FROM BUS 314176 TO BUS 314189 CKT 1   /*6HARMONY     230.0 - 6PAPERMIL TP 230.0
 OPEN BRANCH FROM BUS 314184 TO BUS 314188 CKT 1   /*3SHACKLE     115.0 - 3WEST PT     115.0
 OPEN BRANCH FROM BUS 314184 TO BUS 316439 CKT 1   /*3SHACKLE     115.0 - AE2-005 TAP  115.0
 OPEN BRANCH FROM BUS 314188 TO BUS 314387 CKT 1   /*3WEST PT     115.0 - 3LANEXA      115.0
 OPEN BRANCH FROM BUS 314189 TO BUS 314375 CKT 1   /*6PAPERMIL TP 230.0 - 6CORRCTN     230.0
 OPEN BRANCH FROM BUS 314375 TO BUS 314388 CKT 1   /*6CORRCTN     230.0 - 6LANEXA      230.0
 OPEN BUS 313053                                   /*6PAPERMILL   230.0
 OPEN BUS 313846                                   /*6HARMONY_1   230.0
 OPEN BUS 314176                                   /*6HARMONY     230.0
 OPEN BUS 314184                                   /*3SHACKLE     115.0
 OPEN BUS 314188                                   /*3WEST PT     115.0
 OPEN BUS 314189                                   /*6PAPERMIL TP 230.0
 OPEN BUS 314375                                   /*6CORRCTN     230.0
 OPEN BUS 315748                                   /*AE2-041 GSU   34.5
 OPEN BUS 315749                                   /*AE2-041 GEN    0.4
 OPEN BUS 315755                                   /*AF1-018 MAIN 230.0
 OPEN BUS 315756                                   /*AF1-018 COL   34.5
 OPEN BUS 315757                                   /*AF1-018 TER   13.8
 OPEN BUS 315758                                   /*AF1-018 GSU   34.5
 OPEN BUS 315759                                   /*AF1-018 GEN    0.4
 OPEN BUS 316059                                   /*AD1-063 C    230.0
 OPEN BUS 316314                                   /*AB2-024 C    230.0
END
CONTINGENCY 'DVP_P1-2: LN 65_SRT-A-1'
 OPEN BRANCH FROM BUS 313813 TO BUS 314178 CKT 1   /*3OCRAN       115.0 - 3LANCAST     115.0
 OPEN BRANCH FROM BUS 313813 TO BUS 314191 CKT 1   /*3OCRAN       115.0 - 3WHIT STONE  115.0
 OPEN BRANCH FROM BUS 313870 TO BUS 314191 CKT 1   /*3RAPPAHNCK   115.0 - 3WHIT STONE  115.0
 OPEN BRANCH FROM BUS 314178 TO BUS 314400 CKT 1   /*3LANCAST     115.0 - 3LANCA_1     115.0
 OPEN BRANCH FROM BUS 962970 TO BUS 314178 CKT 1   /*AG1-146 TP   115.0 - 3LANCAST     115.0
 OPEN BUS 313813                                   /*3OCRAN       115.0
 OPEN BUS 314178                                   /*3LANCAST     115.0
 OPEN BUS 314191                                   /*3WHIT STONE  115.0
 OPEN BUS 314400                                   /*3LANCA_1     115.0
END
CONTINGENCY 'DVP_P4-2: L4T65_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 1   /*3NORNECK     115.0 - 6NORNECK     230.0
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
CONTINGENCY 'DVP_P4-2: 6552_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 2   /*3NORNECK     115.0 - 6NORNECK     230.0
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
CONTINGENCY 'DVP_P1-2: LN 1059_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
CONTINGENCY 'DVP_P4-3: U52_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 2   /*3NORNECK     115.0 - 6NORNECK     230.0
END
CONTINGENCY 'DVP_P1-3: 6NORNECK-TX#6_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 2   /*3NORNECK     115.0 - 6NORNECK     230.0
END
CONTINGENCY 'DVP_P4-1: GT52_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 2   /*3NORNECK     115.0 - 6NORNECK     230.0
 OPEN BRANCH FROM BUS 314181 TO BUS 315034 CKT 1   /*3NORNECK     115.0 - 1NORNECKC1    13.2
 OPEN BRANCH FROM BUS 314181 TO BUS 315035 CKT 1   /*3NORNECK     115.0 - 1NORNECKC2    13.2
 OPEN BUS 315034                                   /*1NORNECKC1    13.2
 OPEN BUS 315035                                   /*1NORNECKC2    13.2
END
CONTINGENCY 'DVP_P4-3: NORTHER H452_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 1   /*3NORNECK     115.0 - 6NORNECK     230.0
END
CONTINGENCY 'DVP_P1-3: 6NORNECK-TX#4_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 1   /*3NORNECK     115.0 - 6NORNECK     230.0
END
CONTINGENCY 'DVP_P4-5: L4TGT_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 1   /*3NORNECK     115.0 - 6NORNECK     230.0
 OPEN BRANCH FROM BUS 314181 TO BUS 315034 CKT 1   /*3NORNECK     115.0 - 1NORNECKC1    13.2
 OPEN BRANCH FROM BUS 314181 TO BUS 315035 CKT 1   /*3NORNECK     115.0 - 1NORNECKC2    13.2
 OPEN BUS 315034                                   /*1NORNECKC1    13.2
 OPEN BUS 315035                                   /*1NORNECKC2    13.2
END
CONTINGENCY 'DVP_P4-4: RAPPAH SR112_SRT-A'
 OPEN BRANCH FROM BUS 313842 TO BUS 313870 CKT Z1   /*3RAPPAHNCK_1 115.0 - 3RAPPAHNCK   115.0
 OPEN BRANCH FROM BUS 313843 TO BUS 313870 CKT Z1   /*3RAPPAHNCK_2 115.0 - 3RAPPAHNCK   115.0
 OPEN BRANCH FROM BUS 313870 TO BUS 313900 CKT Z1   /*3RAPPAHNCK   115.0 - 3RAPP TR     115.0
 OPEN BRANCH FROM BUS 313870 TO BUS 314191 CKT 1    /*3RAPPAHNCK   115.0 - 3WHIT STONE  115.0
 OPEN BRANCH FROM BUS 313886 TO BUS 313900 CKT 1    /*3GREYSPT     115.0 - 3RAPP TR     115.0
 OPEN BRANCH FROM BUS 313886 TO BUS 313900 CKT 2    /*3GREYSPT     115.0 - 3RAPP TR     115.0
 OPEN BRANCH FROM BUS 313886 TO BUS 314174 CKT 1    /*3GREYSPT     115.0 - 3HARMONY     115.0
 OPEN BUS 313842                                    /*3RAPPAHNCK_1 115.0
 OPEN BUS 313843                                    /*3RAPPAHNCK_2 115.0
 OPEN BUS 313870                                    /*3RAPPAHNCK   115.0
 OPEN BUS 313886                                    /*3GREYSPT     115.0
 OPEN BUS 313900                                    /*3RAPP TR     115.0
END
CONTINGENCY 'DVP_P2-2: HARMONY V B2_SRT-A'
 OPEN BRANCH FROM BUS 313284 TO BUS 314174 CKT 1   /*3WAN 89      115.0 - 3HARMONY     115.0
 OPEN BRANCH FROM BUS 314174 TO BUS 314176 CKT 1   /*3HARMONY     115.0 - 6HARMONY     230.0
 OPEN BRANCH FROM BUS 314174 TO BUS 314187 CKT 1   /*3HARMONY     115.0 - 3WAN 176     115.0
 OPEN BUS 314385                                   /*3HARMO_1     115.0
 OPEN BUS 314395                                   /*3HARMO_2     115.0
END
CONTINGENCY 'DVP_P7-1: LN 2016-85_SRT-A-2'
 OPEN BRANCH FROM BUS 313053 TO BUS 314189 CKT 1   /*6PAPERMILL   230.0 - 6PAPERMIL TP 230.0
 OPEN BRANCH FROM BUS 314174 TO BUS 314176 CKT 1   /*3HARMONY     115.0 - 6HARMONY     230.0
 OPEN BRANCH FROM BUS 314176 TO BUS 314189 CKT 1   /*6HARMONY     230.0 - 6PAPERMIL TP 230.0
 OPEN BRANCH FROM BUS 314189 TO BUS 314375 CKT 1   /*6PAPERMIL TP 230.0 - 6CORRCTN     230.0
 OPEN BRANCH FROM BUS 314375 TO BUS 314388 CKT 1   /*6CORRCTN     230.0 - 6LANEXA      230.0
 OPEN BRANCH FROM BUS 316439 TO BUS 316275 CKT 1   /*AE2-005 TAP  115.0 - AD1-041 TAP  115.0
 OPEN BUS 313053                                   /*6PAPERMILL   230.0
 OPEN BUS 313846                                   /*6HARMONY_1   230.0
 OPEN BUS 314176                                   /*6HARMONY     230.0
 OPEN BUS 314189                                   /*6PAPERMIL TP 230.0
 OPEN BUS 314375                                   /*6CORRCTN     230.0
 OPEN BUS 315748                                   /*AE2-041 GSU   34.5
 OPEN BUS 315749                                   /*AE2-041 GEN    0.4
 OPEN BUS 315755                                   /*AF1-018 MAIN 230.0
 OPEN BUS 315756                                   /*AF1-018 COL   34.5
 OPEN BUS 315757                                   /*AF1-018 TER   13.8
 OPEN BUS 315758                                   /*AF1-018 GSU   34.5
 OPEN BUS 315759                                   /*AF1-018 GEN    0.4
 OPEN BUS 316059                                   /*AD1-063 C    230.0
 OPEN BUS 316314                                   /*AB2-024 C    230.0
END
CONTINGENCY 'DVP_P4-2: 557T574_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 574T575_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1                /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H1T574_SRT-S'
 OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 1                /*6ELMONT      230.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H2T574_SRT-S'
 OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 2                /*6LADYSMITH   230.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H2T557_SRT-S'
 OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 2                /*6ELMONT      230.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 4149 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3221 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
END
CONTINGENCY 'DVP_P4-2: 56702_SRT-A'
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
END
CONTINGENCY 'DVP_P1-2: LN 567_SRT-A'
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
END
CONTINGENCY 'DVP_P4-2: G2T567_SRT-A'
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
 OPEN BRANCH FROM BUS 314924 TO BUS 315233 CKT 1   /*8SURRY       500.0 - 1SURRY 2      22.0
 OPEN BUS 315233                                   /*1SURRY 2      22.0
END
CONTINGENCY 'DVP_P1-2: LN 2083_SRT-S'
 OPEN BRANCH FROM BUS 314132 TO BUS 314163 CKT 1                /*6BIRCHWD     230.0 - 6FINES       230.0
 OPEN BRANCH FROM BUS 314137 TO BUS 314163 CKT 1                /*6FREDBRG     230.0 - 6FINES       230.0
 OPEN BUS 314163                                                /*6FINES       230.0
 SET POSTCONTRATING 956 BRANCH FROM BUS 314137 TO BUS 314138 CKT 1 /*6FREDBRG     230.0 - 6MINE RD     230.0
 SET PRECONTRATING 876 BRANCH FROM BUS 314137 TO BUS 314138 CKT 1 /*6FREDBRG     230.0 - 6MINE RD     230.0
END
CONTINGENCY 'DVP_P1-2: LN 2145_SRT-A-2'
 OPEN BRANCH FROM BUS 314131 TO BUS 314175 CKT 1   /*6ARNOLDS     230.0 - 6COMORN      230.0
 OPEN BRANCH FROM BUS 314132 TO BUS 314175 CKT 1   /*6BIRCHWD     230.0 - 6COMORN      230.0
 OPEN BRANCH FROM BUS 957190 TO BUS 314131 CKT 1   /*AF2-013 TP   230.0 - 6ARNOLDS     230.0
 OPEN BUS 314131                                   /*6ARNOLDS     230.0
 OPEN BUS 314175                                   /*6COMORN      230.0
END
CONTINGENCY 'DVP_P7-1: LN 2076-2145_SRT-A-2'
 OPEN BRANCH FROM BUS 313810 TO BUS 944490 CKT 1   /*6DAHLGREN    230.0 - AF1-114 TP   230.0
 OPEN BRANCH FROM BUS 313810 TO BUS 957190 CKT 1   /*6DAHLGREN    230.0 - AF2-013 TP   230.0
END
CONTINGENCY 'DVP_P7-1: LN 2076-2145_SRT-A-1'
 OPEN BRANCH FROM BUS 313810 TO BUS 944490 CKT 1   /*6DAHLGREN    230.0 - AF1-114 TP   230.0
 OPEN BRANCH FROM BUS 314131 TO BUS 314175 CKT 1   /*6ARNOLDS     230.0 - 6COMORN      230.0
 OPEN BRANCH FROM BUS 314132 TO BUS 314175 CKT 1   /*6BIRCHWD     230.0 - 6COMORN      230.0
 OPEN BRANCH FROM BUS 957190 TO BUS 314131 CKT 1   /*AF2-013 TP   230.0 - 6ARNOLDS     230.0
 OPEN BUS 314131                                   /*6ARNOLDS     230.0
 OPEN BUS 314175                                   /*6COMORN      230.0
END
CONTINGENCY 'DVP_P4-2: 8962_SRT-A'
 OPEN BRANCH FROM BUS 313284 TO BUS 313828 CKT 1   /*3WAN 89      115.0 - 3WHITEMARSH  115.0
 OPEN BRANCH FROM BUS 313284 TO BUS 314174 CKT 1   /*3WAN 89      115.0 - 3HARMONY     115.0
 OPEN BRANCH FROM BUS 313828 TO BUS 314177 CKT 1   /*3WHITEMARSH  115.0 - 3HAYES89     115.0
 OPEN BUS 313284                                   /*3WAN 89      115.0
 OPEN BUS 313828                                   /*3WHITEMARSH  115.0
 OPEN BUS 314174                                   /*3HARMONY     115.0
 OPEN BUS 314385                                   /*3HARMO_1     115.0
 OPEN BUS 314395                                   /*3HARMO_2     115.0
END
CONTINGENCY 'DVP_P4-5: L262_SRT-A'
 OPEN BRANCH FROM BUS 314174 TO BUS 314176 CKT 1   /*3HARMONY     115.0 - 6HARMONY     230.0
 OPEN BUS 314174                                   /*3HARMONY     115.0
 OPEN BUS 314385                                   /*3HARMO_1     115.0
 OPEN BUS 314395                                   /*3HARMO_2     115.0
END
CONTINGENCY 'DVP_P4-2: 17662_SRT-A'
 OPEN BRANCH FROM BUS 314174 TO BUS 314187 CKT 1   /*3HARMONY     115.0 - 3WAN 176     115.0
 OPEN BUS 314174                                   /*3HARMONY     115.0
 OPEN BUS 314187                                   /*3WAN 176     115.0
 OPEN BUS 314385                                   /*3HARMO_1     115.0
 OPEN BUS 314395                                   /*3HARMO_2     115.0
 OPEN BUS 316156                                   /*AD2-030 GEN  115.0
END
CONTINGENCY 'DVP_P1-2: LN 1021_SRT-A'
 OPEN BRANCH FROM BUS 313842 TO BUS 313870 CKT Z1   /*3RAPPAHNCK_1 115.0 - 3RAPPAHNCK   115.0
 OPEN BRANCH FROM BUS 313843 TO BUS 313870 CKT Z1   /*3RAPPAHNCK_2 115.0 - 3RAPPAHNCK   115.0
 OPEN BRANCH FROM BUS 313870 TO BUS 313900 CKT Z1   /*3RAPPAHNCK   115.0 - 3RAPP TR     115.0
 OPEN BRANCH FROM BUS 313886 TO BUS 313900 CKT 1    /*3GREYSPT     115.0 - 3RAPP TR     115.0
 OPEN BRANCH FROM BUS 313886 TO BUS 313900 CKT 2    /*3GREYSPT     115.0 - 3RAPP TR     115.0
 OPEN BRANCH FROM BUS 313886 TO BUS 314174 CKT 1    /*3GREYSPT     115.0 - 3HARMONY     115.0
 OPEN BUS 313842                                    /*3RAPPAHNCK_1 115.0
 OPEN BUS 313843                                    /*3RAPPAHNCK_2 115.0
 OPEN BUS 313886                                    /*3GREYSPT     115.0
 OPEN BUS 313900                                    /*3RAPP TR     115.0
END
CONTINGENCY 'DVP_P2-2: LANEXA B1_SRT-A'
 OPEN BRANCH FROM BUS 314188 TO BUS 314387 CKT 1   /*3WEST PT     115.0 - 3LANEXA      115.0
 OPEN BRANCH FROM BUS 314243 TO BUS 314387 CKT 1   /*3PROV 92     115.0 - 3LANEXA      115.0
 OPEN BRANCH FROM BUS 314387 TO BUS 314388 CKT 2   /*3LANEXA      115.0 - 6LANEXA      230.0
END
CONTINGENCY 'DVP_P4-2: 65T1059_SRT-A'
 OPEN BRANCH FROM BUS 314173 TO BUS 316399 CKT 1   /*3GARNER      115.0 - AE1-155 TAP  115.0
 OPEN BRANCH FROM BUS 314173 TO BUS 962860 CKT 1   /*3GARNER      115.0 - AG1-135 TP   115.0
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
 OPEN BUS 316399                                   /*AE1-155 TAP  115.0
 OPEN BUS 316400                                   /*AE1-155 MAIN 115.0
 OPEN BUS 316401                                   /*AE1-155 COL1  34.5
 OPEN BUS 316402                                   /*AE1-155 TER   13.8
 OPEN BUS 316403                                   /*AE1-155 COL2  34.5
 OPEN BUS 316404                                   /*AE1-155 C      0.6
END
CONTINGENCY 'DVP_P1-2: LN 65_SRT-A-4'
 OPEN BRANCH FROM BUS 314173 TO BUS 962860 CKT 1   /*3GARNER      115.0 - AG1-135 TP   115.0
 OPEN BRANCH FROM BUS 316399 TO BUS 314173 CKT 1   /*AE1-155 TAP  115.0 - 3GARNER      115.0
 OPEN BUS 314173                                   /*3GARNER      115.0
END
CONTINGENCY 'DVP_P4-2: 105942_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
 OPEN BUS 316399                                   /*AE1-155 TAP  115.0
 OPEN BUS 316400                                   /*AE1-155 MAIN 115.0
 OPEN BUS 316401                                   /*AE1-155 COL1  34.5
 OPEN BUS 316402                                   /*AE1-155 TER   13.8
 OPEN BUS 316403                                   /*AE1-155 COL2  34.5
 OPEN BUS 316404                                   /*AE1-155 C      0.6
END
CONTINGENCY 'DVP_P7-1: LN 224-2208_SRT-S'
 OPEN BRANCH FROM BUS 313732 TO BUS 314172 CKT 1                /*6KING QUEEN  230.0 - 6DUNNSVL     230.0
 OPEN BRANCH FROM BUS 313732 TO BUS 314388 CKT 1                /*6KING QUEEN  230.0 - 6LANEXA      230.0
 OPEN BRANCH FROM BUS 314172 TO BUS 314182 CKT 1                /*6DUNNSVL     230.0 - 6NORNECK     230.0
 OPEN BRANCH FROM BUS 314182 TO BUS 314388 CKT 1                /*6NORNECK     230.0 - 6LANEXA      230.0
 OPEN BUS 313732                                                /*6KING QUEEN  230.0
 OPEN BUS 314172                                                /*6DUNNSVL     230.0
 SET POSTCONTRATING 608 BRANCH FROM BUS 314182 TO BUS 314183 CKT 1 /*6NORNECK     230.0 - 6SANDERS     230.0
 SET PRECONTRATING 605 BRANCH FROM BUS 314182 TO BUS 314183 CKT 1 /*6NORNECK     230.0 - 6SANDERS     230.0
END
CONTINGENCY 'DVP_P4-2: 2076T2208_SRT-A'
 OPEN BRANCH FROM BUS 314182 TO BUS 314183 CKT 1   /*6NORNECK     230.0 - 6SANDERS     230.0
 OPEN BRANCH FROM BUS 314182 TO BUS 314388 CKT 1   /*6NORNECK     230.0 - 6LANEXA      230.0
 OPEN BRANCH FROM BUS 314183 TO BUS 314190 CKT 1   /*6SANDERS     230.0 - 6WESTMOR     230.0
 OPEN BRANCH FROM BUS 970736 TO BUS 314190 CKT 1   /*AG2-469 TP   230.0 - 6WESTMOR     230.0
 OPEN BUS 314183                                   /*6SANDERS     230.0
 OPEN BUS 314190                                   /*6WESTMOR     230.0
 OPEN BUS 316223                                   /*AC1-118      230.0
 OPEN BUS 316337                                   /*AD2-073 GEN  230.0
END
314173 to 316399 ckt 1
313886 to 314174 ckt 1
314174 to 314176 ckt 1
314178 to 313813 ckt 1
314181 to 314182 ckt 1
314181 to 314182 ckt 2
313813 to 314191 ckt 1
313900 to 313886 ckt 1
313900 to 313886 ckt 2
313284 to 313828 ckt 1
314191 to 313870 ckt 1
313828 to 314177 ckt 1
314131 to 314175 ckt 1
314132 to 314163 ckt 1
314214 to 314258 ckt 1
314214 to 314903 ckt 1
314175 to 314132 ckt 1
314163 to 314137 ckt 1
314182 to 314183 ckt 1
314139 to 944490 ckt 1
314183 to 314190 ckt 1
314190 to 970736 ckt 1
314903 to 314908 ckt 1
314908 to 314911 ckt 1
316479 to 962860 ckt 1
316399 to 314181 ckt 1
944490 to 313810 ckt 1
957190 to 314131 ckt 1
962860 to 314173 ckt 1
962970 to 314178 ckt 1
970736 to 314139 ckt 1

Winter Peak Analysis

The New Service Request AG2-366 was evaluated as a 50.0 MW (20.0 MW Capacity) injection in the Dominion area.

AG2-366 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 50.0 MW (50.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Light Load Analysis

The New Service Request AG2-366 was evaluated as a 50.0 MW injection and 50.0 MW withdrawal in the Dominion area.

AG2-366 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 50.0 MW (50.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
3GARNER-AE1-155 TAP 115.0 kV Ckt 1 line
DVP_P1-2: LN 65_SRT-A-1
SingleAC115.95 %221.84B257.2249.94
GD2DVP
3GARNER-AE1-155 TAP 115.0 kV Ckt 1 line
DVP_P1-2_AG1-146 TP-3LANCAST-115_SRT-A
SingleAC115.94 %221.84B257.2149.94
GD2DVP
3GARNER-AE1-155 TAP 115.0 kV Ckt 1 line
DVP_P7-1: LN 2016-85_SRT-A-1
TowerAC105.86 %272.0C287.9431.55
GD2DVP
3GREYSPT-3HARMONY 115.0 kV Ckt 1 line
DVP_P1-2: LN 1059_SRT-A
SingleAC140.12 %307.38B430.749.9
GD2DVP
3GREYSPT-3HARMONY 115.0 kV Ckt 1 line
DVP_P4-2: L4T65_SRT-A
BreakerAC105.31 %409.0C430.749.9
GD2DVP
3GREYSPT-3HARMONY 115.0 kV Ckt 1 line
DVP_P4-2: 6552_SRT-A
BreakerAC105.31 %409.0C430.749.9
GD2DVP
3HARMONY-6HARMONY 115.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 1059_SRT-A
SingleAC130.74 %252.67B330.3423.88
GD2DVP
3HARMONY-6HARMONY 115.0/230.0 kV Ckt 1 transformer
DVP_P4-2: L4T65_SRT-A
BreakerAC122.9 %268.8C330.3423.88
GD2DVP
3HARMONY-6HARMONY 115.0/230.0 kV Ckt 1 transformer
DVP_P4-2: 6552_SRT-A
BreakerAC122.9 %268.8C330.3423.88
GD2DVP
3LANCAST-3OCRAN 115.0 kV Ckt 1 line
DVP_P1-2: LN 1059_SRT-A
SingleAC143.46 %297.04B426.1349.9
GD2DVP
3LANCAST-3OCRAN 115.0 kV Ckt 1 line
DVP_P4-2: L4T65_SRT-A
BreakerAC117.07 %364.0C426.1349.9
GD2DVP
3LANCAST-3OCRAN 115.0 kV Ckt 1 line
DVP_P4-2: 6552_SRT-A
BreakerAC117.07 %364.0C426.1349.9
GD2DVP
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer
DVP_P1-3: 6NORNECK-TX#6_SRT-A
SingleAC122.76 %227.39B279.1420.48
GD2DVP
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer
DVP_P4-3: U52_SRT-A
BreakerAC103.95 %264.3C274.7520.48
GD2DVP
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer
DVP_P4-1: GT52_SRT-A
BreakerAC103.95 %264.3C274.7520.48
GD2DVP
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
DVP_P1-3: 6NORNECK-TX#4_SRT-A
SingleAC137.11 %209.9B287.7921.23
GD2DVP
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
DVP_P4-3: NORTHER H452_SRT-A
BreakerAC115.8 %244.6C283.2421.23
GD2DVP
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
DVP_P4-5: L4TGT_SRT-A
BreakerAC115.8 %244.6C283.2421.23
GD2DVP
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
DVP_P1-2_AG1-146 TP-3LANCAST-115_SRT-A
SingleAC115.51 %209.9B242.4627.25
GD2DVP
3OCRAN-3WHIT STONE 115.0 kV Ckt 1 line
DVP_P1-2: LN 1059_SRT-A
SingleAC143.57 %297.04B426.4549.9
GD2DVP
3OCRAN-3WHIT STONE 115.0 kV Ckt 1 line
DVP_P4-2: L4T65_SRT-A
BreakerAC117.16 %364.0C426.4549.9
GD2DVP
3OCRAN-3WHIT STONE 115.0 kV Ckt 1 line
DVP_P4-2: 6552_SRT-A
BreakerAC117.16 %364.0C426.4549.9
GD2DVP
3RAPP TR-3GREYSPT 115.0 kV Ckt 1 line
DVP_P1-2: LN 1059_SRT-A
SingleAC156.07 %139.12B217.1224.95
GD2DVP
3RAPP TR-3GREYSPT 115.0 kV Ckt 1 line
DVP_P4-2: L4T65_SRT-A
BreakerAC146.7 %148.0C217.1224.95
GD2DVP
3RAPP TR-3GREYSPT 115.0 kV Ckt 1 line
DVP_P4-2: 6552_SRT-A
BreakerAC146.7 %148.0C217.1224.95
GD2DVP
3RAPP TR-3GREYSPT 115.0 kV Ckt 2 line
DVP_P1-2: LN 1059_SRT-A
SingleAC156.07 %139.12B217.1224.95
GD2DVP
3RAPP TR-3GREYSPT 115.0 kV Ckt 2 line
DVP_P4-2: 6552_SRT-A
BreakerAC146.7 %148.0C217.1224.95
GD2DVP
3RAPP TR-3GREYSPT 115.0 kV Ckt 2 line
DVP_P4-2: L4T65_SRT-A
BreakerAC146.7 %148.0C217.1224.95
GD2DVP
3WHIT STONE-3RAPPAHNCK 115.0 kV Ckt 1 line
DVP_P1-2: LN 1059_SRT-A
SingleAC135.46 %315.84B427.8349.9
GD2DVP
3WHIT STONE-3RAPPAHNCK 115.0 kV Ckt 1 line
DVP_P4-2: 6552_SRT-A
BreakerAC121.89 %351.0C427.8349.9
GD2DVP
3WHIT STONE-3RAPPAHNCK 115.0 kV Ckt 1 line
DVP_P4-2: L4T65_SRT-A
BreakerAC121.89 %351.0C427.8349.9
GD2DVP
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-L
SingleAC107.78 %673.04B725.379.14
GD2DVP
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-L
SingleAC104.69 %673.04B704.629.12
GD2DVP
6FINES-6FREDBRG 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-L
SingleAC107.7 %673.04B724.879.14
GD2DVP
6FINES-6FREDBRG 230.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-L
SingleAC104.62 %673.04B704.159.12
GD2DVP
AD2-074 TAP-AG1-135 TP 115.0 kV Ckt 1 line
DVP_P1-2: LN 65_SRT-A-1
SingleAC101.95 %221.84B226.1649.94
GD2DVP
AD2-074 TAP-AG1-135 TP 115.0 kV Ckt 1 line
DVP_P1-2_AG1-146 TP-3LANCAST-115_SRT-A
SingleAC101.94 %221.84B226.1549.94
GD2DVP
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
DVP_P1-2_AG1-146 TP-3LANCAST-115_SRT-A
SingleAC197.74 %221.84B438.6749.9
GD2DVP
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
DVP_P1-2: LN 65_SRT-A-1
SingleAC197.69 %221.84B438.5649.9
GD2DVP
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
DVP_P4-2: 65T1021_SRT-A
BreakerAC161.25 %272.0C438.649.9
GD2DVP
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
DVP_P4-4: LANCAS SC392_SRT-A
BreakerAC161.23 %272.0C438.5649.9
GD2DVP
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
DVP_P7-1: LN 2016-85_SRT-A-1
TowerAC152.65 %272.0C415.2131.51
GD2DVP
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
DVP_P7-1: LN 2016-85_SRT-A-2
TowerAC138.75 %272.0C377.431.54
GD2DVP
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
DVP_P2-2: HARMONY V B2_SRT-A
BusAC137.69 %272.0C374.5232.1
GD2DVP
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
Base Case
SingleAC133.94 %221.84A297.1223.13
GD2DVP
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
DVP_P2-2: LANEXA B1_SRT-A
BusAC117.48 %272.0C319.5424.49
GD2DVP
AG1-135 TP-3GARNER 115.0 kV Ckt 1 line
DVP_P1-2: LN 65_SRT-A-1
SingleAC117.58 %221.84B260.8349.94
GD2DVP
AG1-135 TP-3GARNER 115.0 kV Ckt 1 line
DVP_P1-2_AG1-146 TP-3LANCAST-115_SRT-A
SingleAC117.58 %221.84B260.8349.94
GD2DVP
AG1-135 TP-3GARNER 115.0 kV Ckt 1 line
DVP_P7-1: LN 2016-85_SRT-A-1
TowerAC107.24 %272.0C291.6931.55
GD2DVP
AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
DVP_P1-2: LN 1059_SRT-A
SingleAC195.99 %221.84B434.7949.9
GD2DVP
AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
DVP_P4-2: L4T65_SRT-A
BreakerAC159.85 %272.0C434.7949.9
GD2DVP
AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
DVP_P4-2: 6552_SRT-A
BreakerAC159.85 %272.0C434.7949.9
GD2DVP
AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
DVP_P1-2_AG1-135 TP-3GARNER-115_SRT-A
SingleAC116.54 %221.84B258.5249.94

Details for 3GARNER-AE1-155 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
3GARNER-AE1-155 TAP 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 65_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.95 %
Rating:221.84 MVA
Rating Type:B
MVA to Mitigate:257.22
MW Contribution:49.94
Bus #Bus NameTypeMW Contribution
970009AG2-005 GEN
Solar/Wind Harmer
11.587
962981AG1-147 GEN
Solar/Wind Harmer
40.553
962861AG1-135 GEN
Solar/Wind Harmer
34.76
962971AG1-146 GEN
Solar/Wind Harmer
17.38
970575AG2-366 GEN
50/50
49.942
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.064
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.2
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.064
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.067
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.04
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.298
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3GARNER-AE1-155 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2_AG1-146 TP-3LANCAST-115_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3GARNER-AE1-155 TAP 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2_AG1-146 TP-3LANCAST-115_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.94 %
Rating:221.84 MVA
Rating Type:B
MVA to Mitigate:257.21
MW Contribution:49.94
Bus #Bus NameTypeMW Contribution
970009AG2-005 GEN
Solar/Wind Harmer
11.587
962981AG1-147 GEN
Solar/Wind Harmer
40.553
962861AG1-135 GEN
Solar/Wind Harmer
34.76
962971AG1-146 GEN
Solar/Wind Harmer
17.38
970575AG2-366 GEN
50/50
49.942
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.064
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.2
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.064
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.067
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.04
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.298
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3GARNER-AE1-155 TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2016-85_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
3GARNER-AE1-155 TAP 115.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2016-85_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.86 %
Rating:272.0 MVA
Rating Type:C
MVA to Mitigate:287.94
MW Contribution:31.55
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
Charging
18.851
963611AG1-210 GEN
50/50
Charging
1.217
970009AG2-005 GEN
Solar/Wind Harmer
7.841
3141783LANCAST
Solar/Wind Harmer
0.643
3141913WHIT STONE
Solar/Wind Harmer
1.448
3141873WAN 176
Solar/Wind Harmer
5.019
970575AG2-366 GEN
50/50
31.555
3141783LANCAST
Solar/Wind Harmer
0.964
3138133OCRAN
Solar/Wind Harmer
0.449
316203AE2-005 GEN
Solar/Wind Harmer
0.001
962861AG1-135 GEN
Solar/Wind Harmer
25.379
962981AG1-147 GEN
Solar/Wind Harmer
25.623
962971AG1-146 GEN
Solar/Wind Harmer
10.981
3141873WAN 176
Solar/Wind Harmer
0.251
3138133OCRAN
Solar/Wind Harmer
0.898
3138283WHITEMARSH
Solar/Wind Harmer
0.033
316404AE1-155 C
Solar/Wind Helper
8.618
316077AC2-138 C
Solar/Wind Helper
0.46
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.072
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.223
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.124
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.448
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.009
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.304
CPLELTFEXP_CPLE->PJM
CLTF
0.025
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3GREYSPT-3HARMONY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1059_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3GREYSPT-3HARMONY 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1059_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:140.12 %
Rating:307.38 MVA
Rating Type:B
MVA to Mitigate:430.7
MW Contribution:49.9
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
74.851
958261AF2-120 GEN
Solar/Wind Harmer
35.889
970009AG2-005 GEN
Solar/Wind Harmer
11.577
3141913WHIT STONE
Solar/Wind Harmer
2.894
3141783LANCAST
Solar/Wind Harmer
1.158
962981AG1-147 GEN
Solar/Wind Harmer
40.519
962861AG1-135 GEN
Solar/Wind Harmer
34.731
962971AG1-146 GEN
Solar/Wind Harmer
17.365
316404AE1-155 C
Solar/Wind Harmer
0.004
3138133OCRAN
Solar/Wind Harmer
1.737
970575AG2-366 GEN
50/50
49.901
3141783LANCAST
Solar/Wind Harmer
1.737
3138133OCRAN
Solar/Wind Harmer
0.868
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.111
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.344
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.11
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.115
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.07
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.513
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3GREYSPT-3HARMONY 115.0 kV Ckt 1 line l/o DVP_P4-2: L4T65_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3GREYSPT-3HARMONY 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: L4T65_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.31 %
Rating:409.0 MVA
Rating Type:C
MVA to Mitigate:430.7
MW Contribution:49.9
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
74.851
958261AF2-120 GEN
Solar/Wind Harmer
35.889
970009AG2-005 GEN
Solar/Wind Harmer
11.577
3141913WHIT STONE
Solar/Wind Harmer
2.894
3141783LANCAST
Solar/Wind Harmer
1.158
962981AG1-147 GEN
Solar/Wind Harmer
40.519
962861AG1-135 GEN
Solar/Wind Harmer
34.731
962971AG1-146 GEN
Solar/Wind Harmer
17.365
970575AG2-366 GEN
50/50
49.901
3141783LANCAST
Solar/Wind Harmer
1.737
3138133OCRAN
Solar/Wind Harmer
0.868
316404AE1-155 C
Solar/Wind Harmer
0.004
3138133OCRAN
Solar/Wind Harmer
1.737
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.111
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.344
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.11
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.115
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.07
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.513
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3GREYSPT-3HARMONY 115.0 kV Ckt 1 line l/o DVP_P4-2: 6552_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3GREYSPT-3HARMONY 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 6552_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.31 %
Rating:409.0 MVA
Rating Type:C
MVA to Mitigate:430.7
MW Contribution:49.9
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
74.851
958261AF2-120 GEN
Solar/Wind Harmer
35.889
970009AG2-005 GEN
Solar/Wind Harmer
11.577
3141913WHIT STONE
Solar/Wind Harmer
2.894
3141783LANCAST
Solar/Wind Harmer
1.158
962981AG1-147 GEN
Solar/Wind Harmer
40.519
962861AG1-135 GEN
Solar/Wind Harmer
34.731
962971AG1-146 GEN
Solar/Wind Harmer
17.365
970575AG2-366 GEN
50/50
49.901
3141783LANCAST
Solar/Wind Harmer
1.737
3138133OCRAN
Solar/Wind Harmer
0.868
316404AE1-155 C
Solar/Wind Harmer
0.004
3138133OCRAN
Solar/Wind Harmer
1.737
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.111
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.344
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.11
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.115
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.07
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.513
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3HARMONY-6HARMONY 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1059_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3HARMONY-6HARMONY 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 1059_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.74 %
Rating:252.67 MVA
Rating Type:B
MVA to Mitigate:330.34
MW Contribution:23.88
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
35.819
958261AF2-120 GEN
Solar/Wind Harmer
17.174
3141873WAN 176
Solar/Wind Harmer
5.54
970009AG2-005 GEN
Solar/Wind Harmer
5.54
3141913WHIT STONE
Solar/Wind Harmer
1.385
3141783LANCAST
Solar/Wind Harmer
0.554
316059AD1-063 C
Solar/Wind Helper
0.966
962981AG1-147 GEN
Solar/Wind Harmer
19.39
962861AG1-135 GEN
Solar/Wind Harmer
16.62
962971AG1-146 GEN
Solar/Wind Harmer
8.31
3141873WAN 176
Solar/Wind Harmer
0.277
315749AE2-041 GEN
50/50
Charging
9.538
316404AE1-155 C
Solar/Wind Harmer
0.002
3138133OCRAN
Solar/Wind Harmer
0.831
971777AH1-397 GEN
Solar/Wind Harmer
3.386
3138283WHITEMARSH
Solar/Wind Harmer
0.036
316314AB2-024 C
Solar/Wind Helper
0.354
970575AG2-366 GEN
50/50
23.879
315759AF1-018 GEN
50/50
Charging
9.538
3141783LANCAST
Solar/Wind Harmer
0.831
3138133OCRAN
Solar/Wind Harmer
0.415
316203AE2-005 GEN
Solar/Wind Harmer
0.001
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.09
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.28
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.122
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.035
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.31
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.03
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.396
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3HARMONY-6HARMONY 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: L4T65_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3HARMONY-6HARMONY 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: L4T65_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.9 %
Rating:268.8 MVA
Rating Type:C
MVA to Mitigate:330.34
MW Contribution:23.88
Bus #Bus NameTypeMW Contribution
315749AE2-041 GEN
50/50
Charging
9.538
316404AE1-155 C
Solar/Wind Harmer
0.002
3138133OCRAN
Solar/Wind Harmer
0.831
971777AH1-397 GEN
Solar/Wind Harmer
3.386
3138283WHITEMARSH
Solar/Wind Harmer
0.036
316314AB2-024 C
Solar/Wind Helper
0.354
970575AG2-366 GEN
50/50
23.879
315759AF1-018 GEN
50/50
Charging
9.538
3141783LANCAST
Solar/Wind Harmer
0.831
3138133OCRAN
Solar/Wind Harmer
0.415
316203AE2-005 GEN
Solar/Wind Harmer
0.001
966661AG1-536 GEN
50/50
35.819
958261AF2-120 GEN
Solar/Wind Harmer
17.174
3141873WAN 176
Solar/Wind Harmer
5.54
970009AG2-005 GEN
Solar/Wind Harmer
5.54
3141913WHIT STONE
Solar/Wind Harmer
1.385
3141783LANCAST
Solar/Wind Harmer
0.554
316059AD1-063 C
Solar/Wind Helper
0.966
962981AG1-147 GEN
Solar/Wind Harmer
19.39
962861AG1-135 GEN
Solar/Wind Harmer
16.62
962971AG1-146 GEN
Solar/Wind Harmer
8.31
3141873WAN 176
Solar/Wind Harmer
0.277
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.09
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.28
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.122
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.035
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.31
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.03
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.396
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3HARMONY-6HARMONY 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 6552_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3HARMONY-6HARMONY 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: 6552_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.9 %
Rating:268.8 MVA
Rating Type:C
MVA to Mitigate:330.34
MW Contribution:23.88
Bus #Bus NameTypeMW Contribution
970575AG2-366 GEN
50/50
23.879
966661AG1-536 GEN
50/50
35.819
958261AF2-120 GEN
Solar/Wind Harmer
17.174
3141873WAN 176
Solar/Wind Harmer
5.54
970009AG2-005 GEN
Solar/Wind Harmer
5.54
3141913WHIT STONE
Solar/Wind Harmer
1.385
3141783LANCAST
Solar/Wind Harmer
0.554
316059AD1-063 C
Solar/Wind Helper
0.966
962981AG1-147 GEN
Solar/Wind Harmer
19.39
962861AG1-135 GEN
Solar/Wind Harmer
16.62
962971AG1-146 GEN
Solar/Wind Harmer
8.31
3141873WAN 176
Solar/Wind Harmer
0.277
315759AF1-018 GEN
50/50
Charging
9.538
3141783LANCAST
Solar/Wind Harmer
0.831
3138133OCRAN
Solar/Wind Harmer
0.415
316203AE2-005 GEN
Solar/Wind Harmer
0.001
315749AE2-041 GEN
50/50
Charging
9.538
316404AE1-155 C
Solar/Wind Harmer
0.002
3138133OCRAN
Solar/Wind Harmer
0.831
971777AH1-397 GEN
Solar/Wind Harmer
3.386
3138283WHITEMARSH
Solar/Wind Harmer
0.036
316314AB2-024 C
Solar/Wind Helper
0.354
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.09
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.28
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.122
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.035
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.31
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.03
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.396
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3LANCAST-3OCRAN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1059_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3LANCAST-3OCRAN 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1059_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:143.46 %
Rating:297.04 MVA
Rating Type:B
MVA to Mitigate:426.13
MW Contribution:49.9
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
74.851
958261AF2-120 GEN
Solar/Wind Harmer
35.889
970009AG2-005 GEN
Solar/Wind Harmer
11.577
3141783LANCAST
Solar/Wind Harmer
1.158
962981AG1-147 GEN
Solar/Wind Harmer
40.519
962861AG1-135 GEN
Solar/Wind Harmer
34.731
962971AG1-146 GEN
Solar/Wind Harmer
17.365
316404AE1-155 C
Solar/Wind Harmer
0.004
970575AG2-366 GEN
50/50
49.901
3141783LANCAST
Solar/Wind Harmer
1.737
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.111
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.344
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.11
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.115
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.07
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.513
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3LANCAST-3OCRAN 115.0 kV Ckt 1 line l/o DVP_P4-2: L4T65_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3LANCAST-3OCRAN 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: L4T65_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.07 %
Rating:364.0 MVA
Rating Type:C
MVA to Mitigate:426.13
MW Contribution:49.9
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
74.851
958261AF2-120 GEN
Solar/Wind Harmer
35.889
970009AG2-005 GEN
Solar/Wind Harmer
11.577
3141783LANCAST
Solar/Wind Harmer
1.158
962981AG1-147 GEN
Solar/Wind Harmer
40.519
962861AG1-135 GEN
Solar/Wind Harmer
34.731
962971AG1-146 GEN
Solar/Wind Harmer
17.365
970575AG2-366 GEN
50/50
49.901
3141783LANCAST
Solar/Wind Harmer
1.737
316404AE1-155 C
Solar/Wind Harmer
0.004
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.111
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.344
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.11
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.115
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.07
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.513
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3LANCAST-3OCRAN 115.0 kV Ckt 1 line l/o DVP_P4-2: 6552_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3LANCAST-3OCRAN 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 6552_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.07 %
Rating:364.0 MVA
Rating Type:C
MVA to Mitigate:426.13
MW Contribution:49.9
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
74.851
958261AF2-120 GEN
Solar/Wind Harmer
35.889
970009AG2-005 GEN
Solar/Wind Harmer
11.577
3141783LANCAST
Solar/Wind Harmer
1.158
962981AG1-147 GEN
Solar/Wind Harmer
40.519
962861AG1-135 GEN
Solar/Wind Harmer
34.731
962971AG1-146 GEN
Solar/Wind Harmer
17.365
970575AG2-366 GEN
50/50
49.901
3141783LANCAST
Solar/Wind Harmer
1.737
316404AE1-155 C
Solar/Wind Harmer
0.004
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.111
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.344
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.11
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.115
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.07
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.513
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6NORNECK-TX#6_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-3: 6NORNECK-TX#6_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.76 %
Rating:227.39 MVA
Rating Type:B
MVA to Mitigate:279.14
MW Contribution:20.48
Bus #Bus NameTypeMW Contribution
963611AG1-210 GEN
50/50
7.375
966661AG1-536 GEN
50/50
42.418
3141813NORNECK
Solar/Wind Harmer
2.139
958261AF2-120 GEN
Solar/Wind Harmer
20.338
970009AG2-005 GEN
Solar/Wind Harmer
5.442
3141783LANCAST
Solar/Wind Harmer
0.357
3141913WHIT STONE
Solar/Wind Harmer
0.681
3141873WAN 176
Solar/Wind Harmer
1.701
3141766HARMONY
Solar/Wind Harmer
0.547
962861AG1-135 GEN
Solar/Wind Harmer
18.789
962981AG1-147 GEN
Solar/Wind Harmer
16.634
962971AG1-146 GEN
Solar/Wind Harmer
7.129
3141873WAN 176
Solar/Wind Harmer
0.085
316337AD2-073 GEN
Solar/Wind Helper
0.271
315749AE2-041 GEN
50/50
2.513
316404AE1-155 C
Solar/Wind Harmer
0.002
3138133OCRAN
Solar/Wind Harmer
0.448
971777AH1-397 GEN
Solar/Wind Harmer
1.063
3138283WHITEMARSH
Solar/Wind Harmer
0.011
3141766HARMONY
Solar/Wind Harmer
0.036
970575AG2-366 GEN
50/50
20.485
315759AF1-018 GEN
50/50
2.513
3141783LANCAST
Solar/Wind Harmer
0.536
3138133OCRAN
Solar/Wind Harmer
0.224
316203AE2-005 GEN
Solar/Wind Harmer
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.06
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.102
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.006
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.33
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.012
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.258
CPLELTFEXP_CPLE->PJM
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-3: U52_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-3: U52_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.95 %
Rating:264.3 MVA
Rating Type:C
MVA to Mitigate:274.75
MW Contribution:20.48
Bus #Bus NameTypeMW Contribution
963611AG1-210 GEN
50/50
7.375
966661AG1-536 GEN
50/50
42.418
3141813NORNECK
Solar/Wind Harmer
2.139
958261AF2-120 GEN
Solar/Wind Harmer
20.338
970009AG2-005 GEN
Solar/Wind Harmer
5.442
3141783LANCAST
Solar/Wind Harmer
0.357
3141913WHIT STONE
Solar/Wind Harmer
0.681
3141873WAN 176
Solar/Wind Harmer
1.701
3141766HARMONY
Solar/Wind Harmer
0.547
962861AG1-135 GEN
Solar/Wind Harmer
18.789
962981AG1-147 GEN
Solar/Wind Harmer
16.634
962971AG1-146 GEN
Solar/Wind Harmer
7.129
3141873WAN 176
Solar/Wind Harmer
0.085
316337AD2-073 GEN
Solar/Wind Helper
0.271
970575AG2-366 GEN
50/50
20.485
3141783LANCAST
Solar/Wind Harmer
0.536
3138133OCRAN
Solar/Wind Harmer
0.224
316203AE2-005 GEN
Solar/Wind Harmer
0
316404AE1-155 C
Solar/Wind Harmer
0.002
3138133OCRAN
Solar/Wind Harmer
0.448
971777AH1-397 GEN
Solar/Wind Harmer
1.063
3138283WHITEMARSH
Solar/Wind Harmer
0.011
3141766HARMONY
Solar/Wind Harmer
0.036
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.06
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.102
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.006
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.33
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.012
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.258
CPLELTFEXP_CPLE->PJM
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-1: GT52_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-1: GT52_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.95 %
Rating:264.3 MVA
Rating Type:C
MVA to Mitigate:274.75
MW Contribution:20.48
Bus #Bus NameTypeMW Contribution
963611AG1-210 GEN
50/50
7.375
966661AG1-536 GEN
50/50
42.418
3141813NORNECK
Solar/Wind Harmer
2.139
958261AF2-120 GEN
Solar/Wind Harmer
20.338
970009AG2-005 GEN
Solar/Wind Harmer
5.442
3141783LANCAST
Solar/Wind Harmer
0.357
3141913WHIT STONE
Solar/Wind Harmer
0.681
3141873WAN 176
Solar/Wind Harmer
1.701
3141766HARMONY
Solar/Wind Harmer
0.547
962861AG1-135 GEN
Solar/Wind Harmer
18.789
962981AG1-147 GEN
Solar/Wind Harmer
16.634
962971AG1-146 GEN
Solar/Wind Harmer
7.129
3141873WAN 176
Solar/Wind Harmer
0.085
316337AD2-073 GEN
Solar/Wind Helper
0.271
970575AG2-366 GEN
50/50
20.485
3141783LANCAST
Solar/Wind Harmer
0.536
3138133OCRAN
Solar/Wind Harmer
0.224
316203AE2-005 GEN
Solar/Wind Harmer
0
316404AE1-155 C
Solar/Wind Harmer
0.002
3138133OCRAN
Solar/Wind Harmer
0.448
971777AH1-397 GEN
Solar/Wind Harmer
1.063
3138283WHITEMARSH
Solar/Wind Harmer
0.011
3141766HARMONY
Solar/Wind Harmer
0.036
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.06
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.102
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.006
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.33
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.012
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.258
CPLELTFEXP_CPLE->PJM
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6NORNECK-TX#4_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-3: 6NORNECK-TX#4_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:137.11 %
Rating:209.9 MVA
Rating Type:B
MVA to Mitigate:287.79
MW Contribution:21.23
Bus #Bus NameTypeMW Contribution
963611AG1-210 GEN
50/50
7.645
966661AG1-536 GEN
50/50
43.971
3141813NORNECK
Solar/Wind Harmer
2.217
958261AF2-120 GEN
Solar/Wind Harmer
21.083
970009AG2-005 GEN
Solar/Wind Harmer
5.641
3141783LANCAST
Solar/Wind Harmer
0.37
3141913WHIT STONE
Solar/Wind Harmer
0.706
3141873WAN 176
Solar/Wind Harmer
1.763
3141766HARMONY
Solar/Wind Harmer
0.567
962861AG1-135 GEN
Solar/Wind Harmer
19.477
962981AG1-147 GEN
Solar/Wind Harmer
17.243
962971AG1-146 GEN
Solar/Wind Harmer
7.39
3141873WAN 176
Solar/Wind Harmer
0.088
316337AD2-073 GEN
Solar/Wind Helper
0.281
315749AE2-041 GEN
50/50
2.605
316404AE1-155 C
Solar/Wind Harmer
0.002
3138133OCRAN
Solar/Wind Harmer
0.464
971777AH1-397 GEN
Solar/Wind Harmer
1.102
3138283WHITEMARSH
Solar/Wind Harmer
0.012
3141766HARMONY
Solar/Wind Harmer
0.038
970575AG2-366 GEN
50/50
21.235
315759AF1-018 GEN
50/50
2.605
3141783LANCAST
Solar/Wind Harmer
0.555
3138133OCRAN
Solar/Wind Harmer
0.232
316203AE2-005 GEN
Solar/Wind Harmer
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.063
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.194
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.106
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.006
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.342
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.012
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.268
CPLELTFEXP_CPLE->PJM
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-3: NORTHER H452_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-3: NORTHER H452_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.8 %
Rating:244.6 MVA
Rating Type:C
MVA to Mitigate:283.24
MW Contribution:21.23
Bus #Bus NameTypeMW Contribution
963611AG1-210 GEN
50/50
7.645
966661AG1-536 GEN
50/50
43.971
3141813NORNECK
Solar/Wind Harmer
2.217
958261AF2-120 GEN
Solar/Wind Harmer
21.083
970009AG2-005 GEN
Solar/Wind Harmer
5.641
3141783LANCAST
Solar/Wind Harmer
0.37
3141913WHIT STONE
Solar/Wind Harmer
0.706
3141873WAN 176
Solar/Wind Harmer
1.763
3141766HARMONY
Solar/Wind Harmer
0.567
962861AG1-135 GEN
Solar/Wind Harmer
19.477
962981AG1-147 GEN
Solar/Wind Harmer
17.243
962971AG1-146 GEN
Solar/Wind Harmer
7.39
3141873WAN 176
Solar/Wind Harmer
0.088
316337AD2-073 GEN
Solar/Wind Helper
0.281
970575AG2-366 GEN
50/50
21.235
3141783LANCAST
Solar/Wind Harmer
0.555
3138133OCRAN
Solar/Wind Harmer
0.232
316203AE2-005 GEN
Solar/Wind Harmer
0
316404AE1-155 C
Solar/Wind Harmer
0.002
3138133OCRAN
Solar/Wind Harmer
0.464
971777AH1-397 GEN
Solar/Wind Harmer
1.102
3138283WHITEMARSH
Solar/Wind Harmer
0.012
3141766HARMONY
Solar/Wind Harmer
0.038
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.063
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.194
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.106
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.006
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.342
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.012
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.268
CPLELTFEXP_CPLE->PJM
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-5: L4TGT_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-5: L4TGT_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.8 %
Rating:244.6 MVA
Rating Type:C
MVA to Mitigate:283.24
MW Contribution:21.23
Bus #Bus NameTypeMW Contribution
963611AG1-210 GEN
50/50
7.645
966661AG1-536 GEN
50/50
43.971
3141813NORNECK
Solar/Wind Harmer
2.217
958261AF2-120 GEN
Solar/Wind Harmer
21.083
970009AG2-005 GEN
Solar/Wind Harmer
5.641
3141783LANCAST
Solar/Wind Harmer
0.37
3141913WHIT STONE
Solar/Wind Harmer
0.706
3141873WAN 176
Solar/Wind Harmer
1.763
3141766HARMONY
Solar/Wind Harmer
0.567
962861AG1-135 GEN
Solar/Wind Harmer
19.477
962981AG1-147 GEN
Solar/Wind Harmer
17.243
962971AG1-146 GEN
Solar/Wind Harmer
7.39
3141873WAN 176
Solar/Wind Harmer
0.088
316337AD2-073 GEN
Solar/Wind Helper
0.281
970575AG2-366 GEN
50/50
21.235
3141783LANCAST
Solar/Wind Harmer
0.555
3138133OCRAN
Solar/Wind Harmer
0.232
316203AE2-005 GEN
Solar/Wind Harmer
0
316404AE1-155 C
Solar/Wind Harmer
0.002
3138133OCRAN
Solar/Wind Harmer
0.464
971777AH1-397 GEN
Solar/Wind Harmer
1.102
3138283WHITEMARSH
Solar/Wind Harmer
0.012
3141766HARMONY
Solar/Wind Harmer
0.038
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.063
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.194
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.106
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.006
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.342
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.012
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.268
CPLELTFEXP_CPLE->PJM
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2_AG1-146 TP-3LANCAST-115_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P1-2_AG1-146 TP-3LANCAST-115_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.51 %
Rating:209.9 MVA
Rating Type:B
MVA to Mitigate:242.46
MW Contribution:27.25
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
40.87
963611AG1-210 GEN
50/50
5.449
958261AF2-120 GEN
Solar/Wind Harmer
19.596
970009AG2-005 GEN
Solar/Wind Harmer
6.321
3141813NORNECK
Solar/Wind Harmer
1.58
962981AG1-147 GEN
Solar/Wind Harmer
22.124
962861AG1-135 GEN
Solar/Wind Harmer
18.964
962971AG1-146 GEN
Solar/Wind Harmer
9.482
316404AE1-155 C
Solar/Wind Harmer
0.002
970575AG2-366 GEN
50/50
27.247
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.063
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.197
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.063
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.066
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.04
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.293
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3OCRAN-3WHIT STONE 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1059_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3OCRAN-3WHIT STONE 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1059_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:143.57 %
Rating:297.04 MVA
Rating Type:B
MVA to Mitigate:426.45
MW Contribution:49.9
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
74.851
958261AF2-120 GEN
Solar/Wind Harmer
35.889
970009AG2-005 GEN
Solar/Wind Harmer
11.577
3141783LANCAST
Solar/Wind Harmer
1.158
962981AG1-147 GEN
Solar/Wind Harmer
40.519
962861AG1-135 GEN
Solar/Wind Harmer
34.731
962971AG1-146 GEN
Solar/Wind Harmer
17.365
316404AE1-155 C
Solar/Wind Harmer
0.004
3138133OCRAN
Solar/Wind Harmer
1.737
970575AG2-366 GEN
50/50
49.901
3141783LANCAST
Solar/Wind Harmer
1.737
3138133OCRAN
Solar/Wind Harmer
0.868
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.111
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.344
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.11
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.115
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.07
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.513
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3OCRAN-3WHIT STONE 115.0 kV Ckt 1 line l/o DVP_P4-2: L4T65_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3OCRAN-3WHIT STONE 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: L4T65_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.16 %
Rating:364.0 MVA
Rating Type:C
MVA to Mitigate:426.45
MW Contribution:49.9
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
74.851
958261AF2-120 GEN
Solar/Wind Harmer
35.889
970009AG2-005 GEN
Solar/Wind Harmer
11.577
3141783LANCAST
Solar/Wind Harmer
1.158
962981AG1-147 GEN
Solar/Wind Harmer
40.519
962861AG1-135 GEN
Solar/Wind Harmer
34.731
962971AG1-146 GEN
Solar/Wind Harmer
17.365
970575AG2-366 GEN
50/50
49.901
3141783LANCAST
Solar/Wind Harmer
1.737
3138133OCRAN
Solar/Wind Harmer
0.868
316404AE1-155 C
Solar/Wind Harmer
0.004
3138133OCRAN
Solar/Wind Harmer
1.737
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.111
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.344
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.11
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.115
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.07
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.513
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3OCRAN-3WHIT STONE 115.0 kV Ckt 1 line l/o DVP_P4-2: 6552_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3OCRAN-3WHIT STONE 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 6552_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.16 %
Rating:364.0 MVA
Rating Type:C
MVA to Mitigate:426.45
MW Contribution:49.9
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
74.851
958261AF2-120 GEN
Solar/Wind Harmer
35.889
970009AG2-005 GEN
Solar/Wind Harmer
11.577
3141783LANCAST
Solar/Wind Harmer
1.158
962981AG1-147 GEN
Solar/Wind Harmer
40.519
962861AG1-135 GEN
Solar/Wind Harmer
34.731
962971AG1-146 GEN
Solar/Wind Harmer
17.365
970575AG2-366 GEN
50/50
49.901
3141783LANCAST
Solar/Wind Harmer
1.737
3138133OCRAN
Solar/Wind Harmer
0.868
316404AE1-155 C
Solar/Wind Harmer
0.004
3138133OCRAN
Solar/Wind Harmer
1.737
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.111
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.344
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.11
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.115
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.07
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.513
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3RAPP TR-3GREYSPT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1059_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3RAPP TR-3GREYSPT 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1059_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:156.07 %
Rating:139.12 MVA
Rating Type:B
MVA to Mitigate:217.12
MW Contribution:24.95
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
37.426
958261AF2-120 GEN
Solar/Wind Harmer
17.944
970009AG2-005 GEN
Solar/Wind Harmer
5.788
3141913WHIT STONE
Solar/Wind Harmer
1.447
3141783LANCAST
Solar/Wind Harmer
0.579
962981AG1-147 GEN
Solar/Wind Harmer
20.26
962861AG1-135 GEN
Solar/Wind Harmer
17.365
962971AG1-146 GEN
Solar/Wind Harmer
8.683
316404AE1-155 C
Solar/Wind Harmer
0.002
3138133OCRAN
Solar/Wind Harmer
0.868
970575AG2-366 GEN
50/50
24.95
3141783LANCAST
Solar/Wind Harmer
0.868
3138133OCRAN
Solar/Wind Harmer
0.434
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.055
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.172
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.055
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.057
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.035
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.256
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3RAPP TR-3GREYSPT 115.0 kV Ckt 1 line l/o DVP_P4-2: L4T65_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3RAPP TR-3GREYSPT 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: L4T65_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.7 %
Rating:148.0 MVA
Rating Type:C
MVA to Mitigate:217.12
MW Contribution:24.95
Bus #Bus NameTypeMW Contribution
316404AE1-155 C
Solar/Wind Harmer
0.002
3138133OCRAN
Solar/Wind Harmer
0.868
970575AG2-366 GEN
50/50
24.95
3141783LANCAST
Solar/Wind Harmer
0.868
3138133OCRAN
Solar/Wind Harmer
0.434
966661AG1-536 GEN
50/50
37.426
958261AF2-120 GEN
Solar/Wind Harmer
17.944
970009AG2-005 GEN
Solar/Wind Harmer
5.788
3141913WHIT STONE
Solar/Wind Harmer
1.447
3141783LANCAST
Solar/Wind Harmer
0.579
962981AG1-147 GEN
Solar/Wind Harmer
20.26
962861AG1-135 GEN
Solar/Wind Harmer
17.365
962971AG1-146 GEN
Solar/Wind Harmer
8.683
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.055
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.172
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.055
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.057
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.035
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.256
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3RAPP TR-3GREYSPT 115.0 kV Ckt 1 line l/o DVP_P4-2: 6552_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3RAPP TR-3GREYSPT 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 6552_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.7 %
Rating:148.0 MVA
Rating Type:C
MVA to Mitigate:217.12
MW Contribution:24.95
Bus #Bus NameTypeMW Contribution
316404AE1-155 C
Solar/Wind Harmer
0.002
3138133OCRAN
Solar/Wind Harmer
0.868
970575AG2-366 GEN
50/50
24.95
3141783LANCAST
Solar/Wind Harmer
0.868
3138133OCRAN
Solar/Wind Harmer
0.434
966661AG1-536 GEN
50/50
37.426
958261AF2-120 GEN
Solar/Wind Harmer
17.944
970009AG2-005 GEN
Solar/Wind Harmer
5.788
3141913WHIT STONE
Solar/Wind Harmer
1.447
3141783LANCAST
Solar/Wind Harmer
0.579
962981AG1-147 GEN
Solar/Wind Harmer
20.26
962861AG1-135 GEN
Solar/Wind Harmer
17.365
962971AG1-146 GEN
Solar/Wind Harmer
8.683
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.055
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.172
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.055
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.057
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.035
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.256
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3RAPP TR-3GREYSPT 115.0 kV Ckt 2 line l/o DVP_P1-2: LN 1059_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3RAPP TR-3GREYSPT 115.0 kV Ckt 2 line
Contingency Name:
DVP_P1-2: LN 1059_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:156.07 %
Rating:139.12 MVA
Rating Type:B
MVA to Mitigate:217.12
MW Contribution:24.95
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
37.426
958261AF2-120 GEN
Solar/Wind Harmer
17.944
970009AG2-005 GEN
Solar/Wind Harmer
5.788
3141913WHIT STONE
Solar/Wind Harmer
1.447
3141783LANCAST
Solar/Wind Harmer
0.579
962981AG1-147 GEN
Solar/Wind Harmer
20.26
962861AG1-135 GEN
Solar/Wind Harmer
17.365
962971AG1-146 GEN
Solar/Wind Harmer
8.683
316404AE1-155 C
Solar/Wind Harmer
0.002
3138133OCRAN
Solar/Wind Harmer
0.868
970575AG2-366 GEN
50/50
24.95
3141783LANCAST
Solar/Wind Harmer
0.868
3138133OCRAN
Solar/Wind Harmer
0.434
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.055
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.172
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.055
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.057
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.035
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.256
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3RAPP TR-3GREYSPT 115.0 kV Ckt 2 line l/o DVP_P4-2: 6552_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3RAPP TR-3GREYSPT 115.0 kV Ckt 2 line
Contingency Name:
DVP_P4-2: 6552_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.7 %
Rating:148.0 MVA
Rating Type:C
MVA to Mitigate:217.12
MW Contribution:24.95
Bus #Bus NameTypeMW Contribution
316404AE1-155 C
Solar/Wind Harmer
0.002
3138133OCRAN
Solar/Wind Harmer
0.868
970575AG2-366 GEN
50/50
24.95
3141783LANCAST
Solar/Wind Harmer
0.868
3138133OCRAN
Solar/Wind Harmer
0.434
966661AG1-536 GEN
50/50
37.426
958261AF2-120 GEN
Solar/Wind Harmer
17.944
970009AG2-005 GEN
Solar/Wind Harmer
5.788
3141913WHIT STONE
Solar/Wind Harmer
1.447
3141783LANCAST
Solar/Wind Harmer
0.579
962981AG1-147 GEN
Solar/Wind Harmer
20.26
962861AG1-135 GEN
Solar/Wind Harmer
17.365
962971AG1-146 GEN
Solar/Wind Harmer
8.683
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.055
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.172
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.055
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.057
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.035
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.256
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3RAPP TR-3GREYSPT 115.0 kV Ckt 2 line l/o DVP_P4-2: L4T65_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3RAPP TR-3GREYSPT 115.0 kV Ckt 2 line
Contingency Name:
DVP_P4-2: L4T65_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.7 %
Rating:148.0 MVA
Rating Type:C
MVA to Mitigate:217.12
MW Contribution:24.95
Bus #Bus NameTypeMW Contribution
316404AE1-155 C
Solar/Wind Harmer
0.002
3138133OCRAN
Solar/Wind Harmer
0.868
970575AG2-366 GEN
50/50
24.95
3141783LANCAST
Solar/Wind Harmer
0.868
3138133OCRAN
Solar/Wind Harmer
0.434
966661AG1-536 GEN
50/50
37.426
958261AF2-120 GEN
Solar/Wind Harmer
17.944
970009AG2-005 GEN
Solar/Wind Harmer
5.788
3141913WHIT STONE
Solar/Wind Harmer
1.447
3141783LANCAST
Solar/Wind Harmer
0.579
962981AG1-147 GEN
Solar/Wind Harmer
20.26
962861AG1-135 GEN
Solar/Wind Harmer
17.365
962971AG1-146 GEN
Solar/Wind Harmer
8.683
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.055
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.172
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.055
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.057
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.035
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.256
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3WHIT STONE-3RAPPAHNCK 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1059_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3WHIT STONE-3RAPPAHNCK 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1059_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:135.46 %
Rating:315.84 MVA
Rating Type:B
MVA to Mitigate:427.83
MW Contribution:49.9
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
74.851
958261AF2-120 GEN
Solar/Wind Harmer
35.889
970009AG2-005 GEN
Solar/Wind Harmer
11.577
3141913WHIT STONE
Solar/Wind Harmer
2.894
3141783LANCAST
Solar/Wind Harmer
1.158
962981AG1-147 GEN
Solar/Wind Harmer
40.519
962861AG1-135 GEN
Solar/Wind Harmer
34.731
962971AG1-146 GEN
Solar/Wind Harmer
17.365
316404AE1-155 C
Solar/Wind Harmer
0.004
3138133OCRAN
Solar/Wind Harmer
1.737
970575AG2-366 GEN
50/50
49.901
3141783LANCAST
Solar/Wind Harmer
1.737
3138133OCRAN
Solar/Wind Harmer
0.868
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.111
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.344
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.11
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.115
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.07
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.513
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3WHIT STONE-3RAPPAHNCK 115.0 kV Ckt 1 line l/o DVP_P4-2: 6552_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3WHIT STONE-3RAPPAHNCK 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 6552_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.89 %
Rating:351.0 MVA
Rating Type:C
MVA to Mitigate:427.83
MW Contribution:49.9
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
74.851
958261AF2-120 GEN
Solar/Wind Harmer
35.889
970009AG2-005 GEN
Solar/Wind Harmer
11.577
3141913WHIT STONE
Solar/Wind Harmer
2.894
3141783LANCAST
Solar/Wind Harmer
1.158
962981AG1-147 GEN
Solar/Wind Harmer
40.519
962861AG1-135 GEN
Solar/Wind Harmer
34.731
962971AG1-146 GEN
Solar/Wind Harmer
17.365
970575AG2-366 GEN
50/50
49.901
3141783LANCAST
Solar/Wind Harmer
1.737
3138133OCRAN
Solar/Wind Harmer
0.868
316404AE1-155 C
Solar/Wind Harmer
0.004
3138133OCRAN
Solar/Wind Harmer
1.737
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.111
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.344
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.11
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.115
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.07
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.513
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 3WHIT STONE-3RAPPAHNCK 115.0 kV Ckt 1 line l/o DVP_P4-2: L4T65_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
3WHIT STONE-3RAPPAHNCK 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: L4T65_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.89 %
Rating:351.0 MVA
Rating Type:C
MVA to Mitigate:427.83
MW Contribution:49.9
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
74.851
958261AF2-120 GEN
Solar/Wind Harmer
35.889
970009AG2-005 GEN
Solar/Wind Harmer
11.577
3141913WHIT STONE
Solar/Wind Harmer
2.894
3141783LANCAST
Solar/Wind Harmer
1.158
962981AG1-147 GEN
Solar/Wind Harmer
40.519
962861AG1-135 GEN
Solar/Wind Harmer
34.731
962971AG1-146 GEN
Solar/Wind Harmer
17.365
970575AG2-366 GEN
50/50
49.901
3141783LANCAST
Solar/Wind Harmer
1.737
3138133OCRAN
Solar/Wind Harmer
0.868
316404AE1-155 C
Solar/Wind Harmer
0.004
3138133OCRAN
Solar/Wind Harmer
1.737
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.111
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.344
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.11
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.115
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.07
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.513
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.78 %
Rating:673.04 MVA
Rating Type:B
MVA to Mitigate:725.37
MW Contribution:9.14
Bus #Bus NameTypeMW Contribution
3150331BIRCHWDA
50/50
158.73
963611AG1-210 GEN
50/50
2.484
966661AG1-536 GEN
50/50
16.054
3142433PROV 92
50/50
0.215
3142433PROV 92
50/50
0.215
3142433PROV 92
50/50
0.215
3150921YORKTN3
50/50
1.969
944491AF1-114 GEN
Solar/Wind Harmer
0
972135AH1-637 GEN
Solar/Wind Harmer
4.25
3141906WESTMOR
Solar/Wind Harmer
0.425
3141813NORNECK
Solar/Wind Harmer
0.72
3141726DUNNSVL
Solar/Wind Harmer
2.692
958261AF2-120 GEN
Solar/Wind Harmer
7.697
970009AG2-005 GEN
Solar/Wind Harmer
2.259
3141783LANCAST
Solar/Wind Harmer
0.189
3141913WHIT STONE
Solar/Wind Harmer
0.429
3141873WAN 176
Solar/Wind Harmer
1.512
3141766HARMONY
Solar/Wind Harmer
1.072
3142433PROV 92
Solar/Wind Harmer
1.074
316169AC1-164_GENC
Solar/Wind Harmer
5.913
957191AF2-013 GEN
50/50
65.854
970737AG2-469 GEN
Solar/Wind Harmer
19.532
316337AD2-073 GEN
Solar/Wind Harmer
0
962861AG1-135 GEN
Solar/Wind Harmer
7.27
962981AG1-147 GEN
Solar/Wind Harmer
7.426
962971AG1-146 GEN
Solar/Wind Harmer
3.182
3141873WAN 176
Solar/Wind Harmer
0.076
3143873LANEXA
Solar/Wind Harmer
0.191
971317AH1-138 GEN
Solar/Wind Harmer
0.861
3142946ENON
Solar/Wind Harmer
0.055
3142946ENON
Solar/Wind Harmer
0.017
315749AE2-041 GEN
50/50
4.931
3142433PROV 92
50/50
0.215
970017AG2-010 GEN
50/50
6.304
972263AH1-716 GEN
50/50
22.676
316404AE1-155 C
Solar/Wind Harmer
0.001
3138133OCRAN
Solar/Wind Harmer
0.265
3141766HARMONY
Solar/Wind Harmer
0.071
971777AH1-397 GEN
Solar/Wind Harmer
1.398
3138283WHITEMARSH
Solar/Wind Harmer
0.015
315976AC1-164 GENA
Solar/Wind Harmer
6.844
315975AC1-164 GENB
Solar/Wind Harmer
0.202
3138126ROCKLANDING
Solar/Wind Harmer
0.019
970575AG2-366 GEN
50/50
9.145
315759AF1-018 GEN
50/50
4.931
3142433PROV 92
50/50
0.215
3142433PROV 92
50/50
0.215
971353AH1-157 GEN
50/50
7.528
3141783LANCAST
Solar/Wind Harmer
0.283
3138133OCRAN
Solar/Wind Harmer
0.133
316203AE2-005 GEN
Solar/Wind Harmer
0
971167AH1-042 GEN
Solar/Wind Harmer
7.894
944591AF1-124 GEN
Solar/Wind Harmer
28.886
LAGNLTFEXP_LAGN->PJM
CLTF
1.014
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.562
TVALTFEXP_TVA->PJM
CLTF
0.527
NYPJM->LTFIMP_NY
CLTF
0.528
LGEELTFEXP_LGEE->PJM
CLTF
0.113
WECLTFEXP_WEC->PJM
CLTF
0.055
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.988
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.707
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.74
MECLTFEXP_MEC->PJM
CLTF
0.366
SIGELTFEXP_SIGE->PJM
CLTF
0.011
CPLELTFEXP_CPLE->PJM
CLTF
1.739
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.865

Details for 6BIRCHWD-6FINES 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6BIRCHWD-6FINES 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.69 %
Rating:673.04 MVA
Rating Type:B
MVA to Mitigate:704.62
MW Contribution:9.12
Bus #Bus NameTypeMW Contribution
957191AF2-013 GEN
50/50
65.646
970737AG2-469 GEN
Solar/Wind Harmer
19.474
316337AD2-073 GEN
Solar/Wind Harmer
0
962861AG1-135 GEN
Solar/Wind Harmer
7.249
962981AG1-147 GEN
Solar/Wind Harmer
7.403
962971AG1-146 GEN
Solar/Wind Harmer
3.173
3141873WAN 176
Solar/Wind Harmer
0.075
3143873LANEXA
Solar/Wind Harmer
0.192
971317AH1-138 GEN
Solar/Wind Harmer
0.839
3142946ENON
Solar/Wind Harmer
0.058
3142946ENON
Solar/Wind Harmer
0.017
315749AE2-041 GEN
50/50
4.919
3142433PROV 92
50/50
0.219
970017AG2-010 GEN
50/50
6.12
944631AF1-128 GEN
50/50
23.405
316404AE1-155 C
Solar/Wind Harmer
0.001
3138133OCRAN
Solar/Wind Harmer
0.264
3141766HARMONY
Solar/Wind Harmer
0.071
971777AH1-397 GEN
Solar/Wind Harmer
1.398
3138283WHITEMARSH
Solar/Wind Harmer
0.014
315976AC1-164 GENA
Solar/Wind Harmer
6.904
315975AC1-164 GENB
Solar/Wind Harmer
0.204
3138126ROCKLANDING
Solar/Wind Harmer
0.019
3142416OLDCHRC
Solar/Wind Harmer
0.379
970575AG2-366 GEN
50/50
9.117
315759AF1-018 GEN
50/50
4.919
3142433PROV 92
50/50
0.219
3142433PROV 92
50/50
0.219
971353AH1-157 GEN
50/50
7.341
3141783LANCAST
Solar/Wind Harmer
0.282
3138133OCRAN
Solar/Wind Harmer
0.132
316203AE2-005 GEN
Solar/Wind Harmer
0
971167AH1-042 GEN
Solar/Wind Harmer
8.096
3142416OLDCHRC
Solar/Wind Harmer
0.495
3142416OLDCHRC
Solar/Wind Harmer
0.145
3150331BIRCHWDA
50/50
158.22
963611AG1-210 GEN
50/50
2.477
966661AG1-536 GEN
50/50
16.008
3142433PROV 92
50/50
0.219
3142433PROV 92
50/50
0.219
3142433PROV 92
50/50
0.219
3150921YORKTN3
50/50
1.909
944491AF1-114 GEN
Solar/Wind Harmer
0
972135AH1-637 GEN
Solar/Wind Harmer
4.237
3141906WESTMOR
Solar/Wind Harmer
0.424
3141813NORNECK
Solar/Wind Harmer
0.718
3141726DUNNSVL
Solar/Wind Harmer
2.685
958261AF2-120 GEN
Solar/Wind Harmer
7.675
970009AG2-005 GEN
Solar/Wind Harmer
2.253
3141783LANCAST
Solar/Wind Harmer
0.188
3141913WHIT STONE
Solar/Wind Harmer
0.428
3141873WAN 176
Solar/Wind Harmer
1.506
3141766HARMONY
Solar/Wind Harmer
1.07
3142433PROV 92
Solar/Wind Harmer
1.097
316169AC1-164_GENC
Solar/Wind Harmer
5.965
970293AG2-193 GEN
Solar/Wind Harmer
0.638
LAGNLTFEXP_LAGN->PJM
CLTF
1.366
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.035
TVALTFEXP_TVA->PJM
CLTF
0.708
NYPJM->LTFIMP_NY
CLTF
0.601
LGEELTFEXP_LGEE->PJM
CLTF
0.23
WECLTFEXP_WEC->PJM
CLTF
0.116
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.397
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.944
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.414
MECLTFEXP_MEC->PJM
CLTF
0.641
SIGELTFEXP_SIGE->PJM
CLTF
0.019
CPLELTFEXP_CPLE->PJM
CLTF
1.87
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.154

Details for 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6FINES-6FREDBRG 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.7 %
Rating:673.04 MVA
Rating Type:B
MVA to Mitigate:724.87
MW Contribution:9.14
Bus #Bus NameTypeMW Contribution
3150331BIRCHWDA
50/50
158.73
963611AG1-210 GEN
50/50
2.484
966661AG1-536 GEN
50/50
16.054
3142433PROV 92
50/50
0.215
3142433PROV 92
50/50
0.215
3142433PROV 92
50/50
0.215
3150921YORKTN3
50/50
1.969
944491AF1-114 GEN
Solar/Wind Harmer
0
957191AF2-013 GEN
50/50
65.854
970737AG2-469 GEN
Solar/Wind Harmer
19.532
316337AD2-073 GEN
Solar/Wind Harmer
0
962861AG1-135 GEN
Solar/Wind Harmer
7.27
962981AG1-147 GEN
Solar/Wind Harmer
7.426
962971AG1-146 GEN
Solar/Wind Harmer
3.182
3141873WAN 176
Solar/Wind Harmer
0.076
3143873LANEXA
Solar/Wind Harmer
0.191
971317AH1-138 GEN
Solar/Wind Harmer
0.861
3142946ENON
Solar/Wind Harmer
0.055
3142946ENON
Solar/Wind Harmer
0.017
315749AE2-041 GEN
50/50
4.931
3142433PROV 92
50/50
0.215
970017AG2-010 GEN
50/50
6.304
972263AH1-716 GEN
50/50
22.676
316404AE1-155 C
Solar/Wind Harmer
0.001
3138133OCRAN
Solar/Wind Harmer
0.265
3141766HARMONY
Solar/Wind Harmer
0.071
971777AH1-397 GEN
Solar/Wind Harmer
1.398
3138283WHITEMARSH
Solar/Wind Harmer
0.015
315976AC1-164 GENA
Solar/Wind Harmer
6.844
315975AC1-164 GENB
Solar/Wind Harmer
0.202
3138126ROCKLANDING
Solar/Wind Harmer
0.019
970575AG2-366 GEN
50/50
9.145
315759AF1-018 GEN
50/50
4.931
3142433PROV 92
50/50
0.215
3142433PROV 92
50/50
0.215
971353AH1-157 GEN
50/50
7.528
3141783LANCAST
Solar/Wind Harmer
0.283
3138133OCRAN
Solar/Wind Harmer
0.133
316203AE2-005 GEN
Solar/Wind Harmer
0
971167AH1-042 GEN
Solar/Wind Harmer
7.894
944591AF1-124 GEN
Solar/Wind Harmer
28.886
972135AH1-637 GEN
Solar/Wind Harmer
4.25
3141906WESTMOR
Solar/Wind Harmer
0.425
3141813NORNECK
Solar/Wind Harmer
0.72
3141726DUNNSVL
Solar/Wind Harmer
2.692
958261AF2-120 GEN
Solar/Wind Harmer
7.697
970009AG2-005 GEN
Solar/Wind Harmer
2.259
3141783LANCAST
Solar/Wind Harmer
0.189
3141913WHIT STONE
Solar/Wind Harmer
0.429
3141873WAN 176
Solar/Wind Harmer
1.512
3141766HARMONY
Solar/Wind Harmer
1.072
3142433PROV 92
Solar/Wind Harmer
1.074
316169AC1-164_GENC
Solar/Wind Harmer
5.913
LAGNLTFEXP_LAGN->PJM
CLTF
1.014
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.562
TVALTFEXP_TVA->PJM
CLTF
0.527
NYPJM->LTFIMP_NY
CLTF
0.528
LGEELTFEXP_LGEE->PJM
CLTF
0.113
WECLTFEXP_WEC->PJM
CLTF
0.055
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.988
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.707
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.74
MECLTFEXP_MEC->PJM
CLTF
0.366
SIGELTFEXP_SIGE->PJM
CLTF
0.011
CPLELTFEXP_CPLE->PJM
CLTF
1.739
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.865

Details for 6FINES-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6FINES-6FREDBRG 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.62 %
Rating:673.04 MVA
Rating Type:B
MVA to Mitigate:704.15
MW Contribution:9.12
Bus #Bus NameTypeMW Contribution
957191AF2-013 GEN
50/50
65.646
970737AG2-469 GEN
Solar/Wind Harmer
19.474
316337AD2-073 GEN
Solar/Wind Harmer
0
962861AG1-135 GEN
Solar/Wind Harmer
7.249
962981AG1-147 GEN
Solar/Wind Harmer
7.403
962971AG1-146 GEN
Solar/Wind Harmer
3.173
315749AE2-041 GEN
50/50
4.919
3142433PROV 92
50/50
0.219
970017AG2-010 GEN
50/50
6.12
944631AF1-128 GEN
50/50
23.405
316404AE1-155 C
Solar/Wind Harmer
0.001
3138133OCRAN
Solar/Wind Harmer
0.264
3141766HARMONY
Solar/Wind Harmer
0.071
971777AH1-397 GEN
Solar/Wind Harmer
1.398
3138283WHITEMARSH
Solar/Wind Harmer
0.014
315976AC1-164 GENA
Solar/Wind Harmer
6.904
315975AC1-164 GENB
Solar/Wind Harmer
0.204
3138126ROCKLANDING
Solar/Wind Harmer
0.019
3142416OLDCHRC
Solar/Wind Harmer
0.379
970575AG2-366 GEN
50/50
9.117
315759AF1-018 GEN
50/50
4.919
3142433PROV 92
50/50
0.219
3142433PROV 92
50/50
0.219
971353AH1-157 GEN
50/50
7.341
3141783LANCAST
Solar/Wind Harmer
0.282
3138133OCRAN
Solar/Wind Harmer
0.132
316203AE2-005 GEN
Solar/Wind Harmer
0
971167AH1-042 GEN
Solar/Wind Harmer
8.096
3142416OLDCHRC
Solar/Wind Harmer
0.495
3142416OLDCHRC
Solar/Wind Harmer
0.145
3150331BIRCHWDA
50/50
158.22
963611AG1-210 GEN
50/50
2.477
966661AG1-536 GEN
50/50
16.008
3142433PROV 92
50/50
0.219
3142433PROV 92
50/50
0.219
3142433PROV 92
50/50
0.219
3150921YORKTN3
50/50
1.909
944491AF1-114 GEN
Solar/Wind Harmer
0
972135AH1-637 GEN
Solar/Wind Harmer
4.237
3141906WESTMOR
Solar/Wind Harmer
0.424
3141813NORNECK
Solar/Wind Harmer
0.718
3141726DUNNSVL
Solar/Wind Harmer
2.685
958261AF2-120 GEN
Solar/Wind Harmer
7.675
970009AG2-005 GEN
Solar/Wind Harmer
2.253
3141783LANCAST
Solar/Wind Harmer
0.188
3141913WHIT STONE
Solar/Wind Harmer
0.428
3141873WAN 176
Solar/Wind Harmer
1.506
3141766HARMONY
Solar/Wind Harmer
1.07
3142433PROV 92
Solar/Wind Harmer
1.097
316169AC1-164_GENC
Solar/Wind Harmer
5.965
970293AG2-193 GEN
Solar/Wind Harmer
0.638
3141873WAN 176
Solar/Wind Harmer
0.075
3143873LANEXA
Solar/Wind Harmer
0.192
971317AH1-138 GEN
Solar/Wind Harmer
0.839
3142946ENON
Solar/Wind Harmer
0.058
3142946ENON
Solar/Wind Harmer
0.017
LAGNLTFEXP_LAGN->PJM
CLTF
1.366
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.035
TVALTFEXP_TVA->PJM
CLTF
0.708
NYPJM->LTFIMP_NY
CLTF
0.601
LGEELTFEXP_LGEE->PJM
CLTF
0.23
WECLTFEXP_WEC->PJM
CLTF
0.116
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.397
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.944
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.414
MECLTFEXP_MEC->PJM
CLTF
0.641
SIGELTFEXP_SIGE->PJM
CLTF
0.019
CPLELTFEXP_CPLE->PJM
CLTF
1.87
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.154

Details for AD2-074 TAP-AG1-135 TP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
AD2-074 TAP-AG1-135 TP 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 65_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.95 %
Rating:221.84 MVA
Rating Type:B
MVA to Mitigate:226.16
MW Contribution:49.94
Bus #Bus NameTypeMW Contribution
970575AG2-366 GEN
50/50
49.942
970009AG2-005 GEN
Solar/Wind Harmer
11.587
962981AG1-147 GEN
Solar/Wind Harmer
40.553
962971AG1-146 GEN
Solar/Wind Harmer
17.38
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.064
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.2
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.064
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.067
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.04
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.298
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AD2-074 TAP-AG1-135 TP 115.0 kV Ckt 1 line l/o DVP_P1-2_AG1-146 TP-3LANCAST-115_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AD2-074 TAP-AG1-135 TP 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2_AG1-146 TP-3LANCAST-115_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.94 %
Rating:221.84 MVA
Rating Type:B
MVA to Mitigate:226.15
MW Contribution:49.94
Bus #Bus NameTypeMW Contribution
970575AG2-366 GEN
50/50
49.942
970009AG2-005 GEN
Solar/Wind Harmer
11.587
962981AG1-147 GEN
Solar/Wind Harmer
40.553
962971AG1-146 GEN
Solar/Wind Harmer
17.38
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.064
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.2
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.064
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.067
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.04
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.298
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P1-2_AG1-146 TP-3LANCAST-115_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2_AG1-146 TP-3LANCAST-115_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:197.74 %
Rating:221.84 MVA
Rating Type:B
MVA to Mitigate:438.67
MW Contribution:49.9
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
74.851
958261AF2-120 GEN
Solar/Wind Harmer
35.889
970009AG2-005 GEN
Solar/Wind Harmer
11.577
962981AG1-147 GEN
Solar/Wind Harmer
40.519
962861AG1-135 GEN
Solar/Wind Harmer
34.731
962971AG1-146 GEN
Solar/Wind Harmer
17.365
316404AE1-155 C
Solar/Wind Harmer
0.004
970575AG2-366 GEN
50/50
49.901
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.111
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.344
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.11
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.115
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.07
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.513
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 65_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:197.69 %
Rating:221.84 MVA
Rating Type:B
MVA to Mitigate:438.56
MW Contribution:49.9
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
74.851
958261AF2-120 GEN
Solar/Wind Harmer
35.889
970009AG2-005 GEN
Solar/Wind Harmer
11.577
962981AG1-147 GEN
Solar/Wind Harmer
40.519
962861AG1-135 GEN
Solar/Wind Harmer
34.731
962971AG1-146 GEN
Solar/Wind Harmer
17.365
316404AE1-155 C
Solar/Wind Harmer
0.004
970575AG2-366 GEN
50/50
49.901
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.111
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.344
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.11
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.115
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.07
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.513
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P4-2: 65T1021_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 65T1021_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:161.25 %
Rating:272.0 MVA
Rating Type:C
MVA to Mitigate:438.6
MW Contribution:49.9
Bus #Bus NameTypeMW Contribution
316404AE1-155 C
Solar/Wind Harmer
0.004
970575AG2-366 GEN
50/50
49.901
966661AG1-536 GEN
50/50
74.851
958261AF2-120 GEN
Solar/Wind Harmer
35.889
970009AG2-005 GEN
Solar/Wind Harmer
11.577
962981AG1-147 GEN
Solar/Wind Harmer
40.519
962861AG1-135 GEN
Solar/Wind Harmer
34.731
962971AG1-146 GEN
Solar/Wind Harmer
17.365
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.111
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.344
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.11
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.115
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.07
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.513
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P4-4: LANCAS SC392_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-4: LANCAS SC392_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:161.23 %
Rating:272.0 MVA
Rating Type:C
MVA to Mitigate:438.56
MW Contribution:49.9
Bus #Bus NameTypeMW Contribution
316404AE1-155 C
Solar/Wind Harmer
0.004
970575AG2-366 GEN
50/50
49.901
966661AG1-536 GEN
50/50
74.851
958261AF2-120 GEN
Solar/Wind Harmer
35.889
970009AG2-005 GEN
Solar/Wind Harmer
11.577
962981AG1-147 GEN
Solar/Wind Harmer
40.519
962861AG1-135 GEN
Solar/Wind Harmer
34.731
962971AG1-146 GEN
Solar/Wind Harmer
17.365
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.111
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.344
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.11
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.115
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.07
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.513
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2016-85_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2016-85_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:152.65 %
Rating:272.0 MVA
Rating Type:C
MVA to Mitigate:415.21
MW Contribution:31.51
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
56.086
963611AG1-210 GEN
50/50
Charging
1.225
958261AF2-120 GEN
Solar/Wind Harmer
26.891
970009AG2-005 GEN
Solar/Wind Harmer
7.831
3141783LANCAST
Solar/Wind Harmer
0.642
3141913WHIT STONE
Solar/Wind Harmer
1.446
3141873WAN 176
Solar/Wind Harmer
5.01
962861AG1-135 GEN
Solar/Wind Harmer
25.35
962981AG1-147 GEN
Solar/Wind Harmer
25.589
962971AG1-146 GEN
Solar/Wind Harmer
10.967
3141873WAN 176
Solar/Wind Harmer
0.25
970575AG2-366 GEN
50/50
31.513
3141783LANCAST
Solar/Wind Harmer
0.963
3138133OCRAN
Solar/Wind Harmer
0.448
316203AE2-005 GEN
Solar/Wind Harmer
0.001
316404AE1-155 C
Solar/Wind Harmer
0.003
3138133OCRAN
Solar/Wind Harmer
0.897
3138283WHITEMARSH
Solar/Wind Harmer
0.033
316077AC2-138 C
Solar/Wind Helper
0.463
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.118
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.368
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.17
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.042
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.448
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.038
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.519
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2016-85_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2016-85_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:138.75 %
Rating:272.0 MVA
Rating Type:C
MVA to Mitigate:377.4
MW Contribution:31.54
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
56.119
963611AG1-210 GEN
50/50
Charging
1.221
958261AF2-120 GEN
Solar/Wind Harmer
26.907
970009AG2-005 GEN
Solar/Wind Harmer
7.836
3141783LANCAST
Solar/Wind Harmer
0.643
3141913WHIT STONE
Solar/Wind Harmer
1.447
3141873WAN 176
Solar/Wind Harmer
5.015
962861AG1-135 GEN
Solar/Wind Harmer
25.366
962981AG1-147 GEN
Solar/Wind Harmer
25.606
962971AG1-146 GEN
Solar/Wind Harmer
10.974
3141873WAN 176
Solar/Wind Harmer
0.251
970575AG2-366 GEN
50/50
31.535
3141783LANCAST
Solar/Wind Harmer
0.964
3138133OCRAN
Solar/Wind Harmer
0.449
316404AE1-155 C
Solar/Wind Harmer
0.003
3138133OCRAN
Solar/Wind Harmer
0.897
3138283WHITEMARSH
Solar/Wind Harmer
0.033
316077AC2-138 C
Solar/Wind Helper
0.462
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.094
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.292
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.146
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.017
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.448
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.023
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.406
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P2-2: HARMONY V B2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: HARMONY V B2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:137.69 %
Rating:272.0 MVA
Rating Type:C
MVA to Mitigate:374.52
MW Contribution:32.1
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
56.964
963611AG1-210 GEN
50/50
Charging
1.11
958261AF2-120 GEN
Solar/Wind Harmer
27.313
970009AG2-005 GEN
Solar/Wind Harmer
7.968
3141783LANCAST
Solar/Wind Harmer
0.656
3141913WHIT STONE
Solar/Wind Harmer
1.48
962861AG1-135 GEN
Solar/Wind Harmer
25.759
962981AG1-147 GEN
Solar/Wind Harmer
26.069
962971AG1-146 GEN
Solar/Wind Harmer
11.172
3143873LANEXA
Solar/Wind Harmer
0.098
970575AG2-366 GEN
50/50
32.104
3141783LANCAST
Solar/Wind Harmer
0.984
3138133OCRAN
Solar/Wind Harmer
0.459
316203AE2-005 GEN
Solar/Wind Harmer
0.001
316404AE1-155 C
Solar/Wind Harmer
0.003
3138133OCRAN
Solar/Wind Harmer
0.917
971777AH1-397 GEN
Solar/Wind Harmer
3.227
316077AC2-138 C
Solar/Wind Helper
0.419
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.104
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.322
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.129
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.076
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.187
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.051
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.469
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.94 %
Rating:221.84 MVA
Rating Type:A
MVA to Mitigate:297.12
MW Contribution:23.13
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
47.9
963611AG1-210 GEN
50/50
Charging
1.672
958261AF2-120 GEN
Solar/Wind Harmer
22.967
970009AG2-005 GEN
Solar/Wind Harmer
6.146
3141783LANCAST
Solar/Wind Harmer
0.403
3141913WHIT STONE
Solar/Wind Harmer
0.769
3141873WAN 176
Solar/Wind Harmer
1.921
3141766HARMONY
Solar/Wind Harmer
0.618
962861AG1-135 GEN
Solar/Wind Harmer
21.217
962981AG1-147 GEN
Solar/Wind Harmer
18.784
962971AG1-146 GEN
Solar/Wind Harmer
8.05
3141873WAN 176
Solar/Wind Harmer
0.096
316337AD2-073 GEN
Solar/Wind Helper
0.306
315749AE2-041 GEN
50/50
2.841
316404AE1-155 C
Solar/Wind Harmer
0.002
3138133OCRAN
Solar/Wind Harmer
0.506
971777AH1-397 GEN
Solar/Wind Harmer
1.201
3138283WHITEMARSH
Solar/Wind Harmer
0.013
3141766HARMONY
Solar/Wind Harmer
0.041
316077AC2-138 C
Solar/Wind Helper
0.632
970575AG2-366 GEN
50/50
23.133
315759AF1-018 GEN
50/50
2.841
3141783LANCAST
Solar/Wind Harmer
0.605
3138133OCRAN
Solar/Wind Harmer
0.253
316203AE2-005 GEN
Solar/Wind Harmer
0
316223AC1-118
Solar/Wind Helper
0.281
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.063
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.195
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.111
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.001
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.372
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.01
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.268
CPLELTFEXP_CPLE->PJM
CLTF
0.009
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line l/o DVP_P2-2: LANEXA B1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AE1-155 TAP-3NORNECK 115.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: LANEXA B1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:117.48 %
Rating:272.0 MVA
Rating Type:C
MVA to Mitigate:319.54
MW Contribution:24.49
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
49.235
963611AG1-210 GEN
50/50
Charging
1.596
958261AF2-120 GEN
Solar/Wind Harmer
23.607
970009AG2-005 GEN
Solar/Wind Harmer
6.419
3141783LANCAST
Solar/Wind Harmer
0.442
3141913WHIT STONE
Solar/Wind Harmer
0.878
3141873WAN 176
Solar/Wind Harmer
2.416
3141766HARMONY
Solar/Wind Harmer
0.772
962861AG1-135 GEN
Solar/Wind Harmer
21.89
962981AG1-147 GEN
Solar/Wind Harmer
19.883
962971AG1-146 GEN
Solar/Wind Harmer
8.521
3141873WAN 176
Solar/Wind Harmer
0.121
316337AD2-073 GEN
Solar/Wind Helper
0.296
970575AG2-366 GEN
50/50
24.486
3141783LANCAST
Solar/Wind Harmer
0.663
3138133OCRAN
Solar/Wind Harmer
0.284
316203AE2-005 GEN
Solar/Wind Harmer
0.001
316223AC1-118
Solar/Wind Helper
0.272
316404AE1-155 C
Solar/Wind Harmer
0.002
3138133OCRAN
Solar/Wind Harmer
0.568
971777AH1-397 GEN
Solar/Wind Harmer
2.394
3138283WHITEMARSH
Solar/Wind Harmer
0.016
3141766HARMONY
Solar/Wind Harmer
0.051
316077AC2-138 C
Solar/Wind Helper
0.603
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.077
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.238
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.125
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.013
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.382
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.018
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.331
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AG1-135 TP-3GARNER 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 65_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
AG1-135 TP-3GARNER 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 65_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.58 %
Rating:221.84 MVA
Rating Type:B
MVA to Mitigate:260.83
MW Contribution:49.94
Bus #Bus NameTypeMW Contribution
970009AG2-005 GEN
Solar/Wind Harmer
11.587
962981AG1-147 GEN
Solar/Wind Harmer
40.553
962861AG1-135 GEN
Solar/Wind Harmer
34.76
962971AG1-146 GEN
Solar/Wind Harmer
17.38
970575AG2-366 GEN
50/50
49.942
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.064
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.2
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.064
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.067
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.04
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.298
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AG1-135 TP-3GARNER 115.0 kV Ckt 1 line l/o DVP_P1-2_AG1-146 TP-3LANCAST-115_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG1-135 TP-3GARNER 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2_AG1-146 TP-3LANCAST-115_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.58 %
Rating:221.84 MVA
Rating Type:B
MVA to Mitigate:260.83
MW Contribution:49.94
Bus #Bus NameTypeMW Contribution
970009AG2-005 GEN
Solar/Wind Harmer
11.587
962981AG1-147 GEN
Solar/Wind Harmer
40.553
962861AG1-135 GEN
Solar/Wind Harmer
34.76
962971AG1-146 GEN
Solar/Wind Harmer
17.38
970575AG2-366 GEN
50/50
49.942
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.064
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.2
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.064
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.067
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.04
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.298
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AG1-135 TP-3GARNER 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2016-85_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
AG1-135 TP-3GARNER 115.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2016-85_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:107.24 %
Rating:272.0 MVA
Rating Type:C
MVA to Mitigate:291.69
MW Contribution:31.55
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
Charging
18.851
963611AG1-210 GEN
50/50
Charging
1.217
970009AG2-005 GEN
Solar/Wind Harmer
7.841
3141783LANCAST
Solar/Wind Harmer
0.643
3141913WHIT STONE
Solar/Wind Harmer
1.448
3141873WAN 176
Solar/Wind Harmer
5.019
970575AG2-366 GEN
50/50
31.555
3141783LANCAST
Solar/Wind Harmer
0.964
3138133OCRAN
Solar/Wind Harmer
0.449
316203AE2-005 GEN
Solar/Wind Harmer
0.001
962861AG1-135 GEN
Solar/Wind Harmer
25.379
962981AG1-147 GEN
Solar/Wind Harmer
25.623
962971AG1-146 GEN
Solar/Wind Harmer
10.981
3141873WAN 176
Solar/Wind Harmer
0.251
3138133OCRAN
Solar/Wind Harmer
0.898
3138283WHITEMARSH
Solar/Wind Harmer
0.033
316404AE1-155 C
Solar/Wind Helper
8.618
316077AC2-138 C
Solar/Wind Helper
0.46
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.072
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.223
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.124
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.448
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.009
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.304
CPLELTFEXP_CPLE->PJM
CLTF
0.025
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1059_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 1059_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:195.99 %
Rating:221.84 MVA
Rating Type:B
MVA to Mitigate:434.79
MW Contribution:49.9
Bus #Bus NameTypeMW Contribution
966661AG1-536 GEN
50/50
74.851
958261AF2-120 GEN
Solar/Wind Harmer
35.889
970009AG2-005 GEN
Solar/Wind Harmer
11.577
962981AG1-147 GEN
Solar/Wind Harmer
40.519
962861AG1-135 GEN
Solar/Wind Harmer
34.731
962971AG1-146 GEN
Solar/Wind Harmer
17.365
316404AE1-155 C
Solar/Wind Harmer
0.004
970575AG2-366 GEN
50/50
49.901
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.111
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.344
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.11
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.115
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.07
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.513
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: L4T65_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: L4T65_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:159.85 %
Rating:272.0 MVA
Rating Type:C
MVA to Mitigate:434.79
MW Contribution:49.9
Bus #Bus NameTypeMW Contribution
316404AE1-155 C
Solar/Wind Harmer
0.004
970575AG2-366 GEN
50/50
49.901
966661AG1-536 GEN
50/50
74.851
958261AF2-120 GEN
Solar/Wind Harmer
35.889
970009AG2-005 GEN
Solar/Wind Harmer
11.577
962981AG1-147 GEN
Solar/Wind Harmer
40.519
962861AG1-135 GEN
Solar/Wind Harmer
34.731
962971AG1-146 GEN
Solar/Wind Harmer
17.365
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.111
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.344
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.11
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.115
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.07
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.513
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P4-2: 6552_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 6552_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:159.85 %
Rating:272.0 MVA
Rating Type:C
MVA to Mitigate:434.79
MW Contribution:49.9
Bus #Bus NameTypeMW Contribution
316404AE1-155 C
Solar/Wind Harmer
0.004
970575AG2-366 GEN
50/50
49.901
966661AG1-536 GEN
50/50
74.851
958261AF2-120 GEN
Solar/Wind Harmer
35.889
970009AG2-005 GEN
Solar/Wind Harmer
11.577
962981AG1-147 GEN
Solar/Wind Harmer
40.519
962861AG1-135 GEN
Solar/Wind Harmer
34.731
962971AG1-146 GEN
Solar/Wind Harmer
17.365
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.111
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.344
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.11
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.115
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.07
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.513
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line l/o DVP_P1-2_AG1-135 TP-3GARNER-115_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG1-146 TP-3LANCAST 115.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2_AG1-135 TP-3GARNER-115_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.54 %
Rating:221.84 MVA
Rating Type:B
MVA to Mitigate:258.52
MW Contribution:49.94
Bus #Bus NameTypeMW Contribution
970009AG2-005 GEN
Solar/Wind Harmer
11.587
962981AG1-147 GEN
Solar/Wind Harmer
40.553
962861AG1-135 GEN
Solar/Wind Harmer
34.76
962971AG1-146 GEN
Solar/Wind Harmer
17.38
970575AG2-366 GEN
50/50
49.942
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.064
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.2
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.064
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.067
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.04
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.298
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CONTINGENCY 'DVP_P1-2: LN 65_SRT-A-1'
 OPEN BRANCH FROM BUS 313813 TO BUS 314178 CKT 1   /*3OCRAN       115.0 - 3LANCAST     115.0
 OPEN BRANCH FROM BUS 313813 TO BUS 314191 CKT 1   /*3OCRAN       115.0 - 3WHIT STONE  115.0
 OPEN BRANCH FROM BUS 313870 TO BUS 314191 CKT 1   /*3RAPPAHNCK   115.0 - 3WHIT STONE  115.0
 OPEN BRANCH FROM BUS 314178 TO BUS 314400 CKT 1   /*3LANCAST     115.0 - 3LANCA_1     115.0
 OPEN BRANCH FROM BUS 962970 TO BUS 314178 CKT 1   /*AG1-146 TP   115.0 - 3LANCAST     115.0
 OPEN BUS 313813                                   /*3OCRAN       115.0
 OPEN BUS 314178                                   /*3LANCAST     115.0
 OPEN BUS 314191                                   /*3WHIT STONE  115.0
 OPEN BUS 314400                                   /*3LANCA_1     115.0
END
CONTINGENCY 'DVP_P1-2_AG1-146 TP-3LANCAST-115_SRT-A'
 DISCONNECT BRANCH FROM BUS 962970 TO BUS 314178 CKT 1   /*AG1-146 TP   115.0 - 3LANCAST     115.0
END
CONTINGENCY 'DVP_P7-1: LN 2016-85_SRT-A-1'
 OPEN BRANCH FROM BUS 313053 TO BUS 314189 CKT 1   /*6PAPERMILL   230.0 - 6PAPERMIL TP 230.0
 OPEN BRANCH FROM BUS 314174 TO BUS 314176 CKT 1   /*3HARMONY     115.0 - 6HARMONY     230.0
 OPEN BRANCH FROM BUS 314176 TO BUS 314189 CKT 1   /*6HARMONY     230.0 - 6PAPERMIL TP 230.0
 OPEN BRANCH FROM BUS 314184 TO BUS 314188 CKT 1   /*3SHACKLE     115.0 - 3WEST PT     115.0
 OPEN BRANCH FROM BUS 314184 TO BUS 316439 CKT 1   /*3SHACKLE     115.0 - AE2-005 TAP  115.0
 OPEN BRANCH FROM BUS 314188 TO BUS 314387 CKT 1   /*3WEST PT     115.0 - 3LANEXA      115.0
 OPEN BRANCH FROM BUS 314189 TO BUS 314375 CKT 1   /*6PAPERMIL TP 230.0 - 6CORRCTN     230.0
 OPEN BRANCH FROM BUS 314375 TO BUS 314388 CKT 1   /*6CORRCTN     230.0 - 6LANEXA      230.0
 OPEN BUS 313053                                   /*6PAPERMILL   230.0
 OPEN BUS 313846                                   /*6HARMONY_1   230.0
 OPEN BUS 314176                                   /*6HARMONY     230.0
 OPEN BUS 314184                                   /*3SHACKLE     115.0
 OPEN BUS 314188                                   /*3WEST PT     115.0
 OPEN BUS 314189                                   /*6PAPERMIL TP 230.0
 OPEN BUS 314375                                   /*6CORRCTN     230.0
 OPEN BUS 315748                                   /*AE2-041 GSU   34.5
 OPEN BUS 315749                                   /*AE2-041 GEN    0.4
 OPEN BUS 315755                                   /*AF1-018 MAIN 230.0
 OPEN BUS 315756                                   /*AF1-018 COL   34.5
 OPEN BUS 315757                                   /*AF1-018 TER   13.8
 OPEN BUS 315758                                   /*AF1-018 GSU   34.5
 OPEN BUS 315759                                   /*AF1-018 GEN    0.4
 OPEN BUS 316059                                   /*AD1-063 C    230.0
 OPEN BUS 316314                                   /*AB2-024 C    230.0
END
CONTINGENCY 'DVP_P1-2: LN 1059_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
CONTINGENCY 'DVP_P4-2: L4T65_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 1   /*3NORNECK     115.0 - 6NORNECK     230.0
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
CONTINGENCY 'DVP_P4-2: 6552_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 2   /*3NORNECK     115.0 - 6NORNECK     230.0
 OPEN BRANCH FROM BUS 314181 TO BUS 316399 CKT 1   /*3NORNECK     115.0 - AE1-155 TAP  115.0
END
CONTINGENCY 'DVP_P1-3: 6NORNECK-TX#6_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 2   /*3NORNECK     115.0 - 6NORNECK     230.0
END
CONTINGENCY 'DVP_P4-3: U52_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 2   /*3NORNECK     115.0 - 6NORNECK     230.0
END
CONTINGENCY 'DVP_P4-1: GT52_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 2   /*3NORNECK     115.0 - 6NORNECK     230.0
 OPEN BRANCH FROM BUS 314181 TO BUS 315034 CKT 1   /*3NORNECK     115.0 - 1NORNECKC1    13.2
 OPEN BRANCH FROM BUS 314181 TO BUS 315035 CKT 1   /*3NORNECK     115.0 - 1NORNECKC2    13.2
 OPEN BUS 315034                                   /*1NORNECKC1    13.2
 OPEN BUS 315035                                   /*1NORNECKC2    13.2
END
CONTINGENCY 'DVP_P1-3: 6NORNECK-TX#4_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 1   /*3NORNECK     115.0 - 6NORNECK     230.0
END
CONTINGENCY 'DVP_P4-3: NORTHER H452_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 1   /*3NORNECK     115.0 - 6NORNECK     230.0
END
CONTINGENCY 'DVP_P4-5: L4TGT_SRT-A'
 OPEN BRANCH FROM BUS 314181 TO BUS 314182 CKT 1   /*3NORNECK     115.0 - 6NORNECK     230.0
 OPEN BRANCH FROM BUS 314181 TO BUS 315034 CKT 1   /*3NORNECK     115.0 - 1NORNECKC1    13.2
 OPEN BRANCH FROM BUS 314181 TO BUS 315035 CKT 1   /*3NORNECK     115.0 - 1NORNECKC2    13.2
 OPEN BUS 315034                                   /*1NORNECKC1    13.2
 OPEN BUS 315035                                   /*1NORNECKC2    13.2
END
CONTINGENCY 'DVP_P1-2: LN 557_SRT-L'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 3300 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3118 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-L'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 4708 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 4401 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 65T1021_SRT-A'
 OPEN BRANCH FROM BUS 313813 TO BUS 314178 CKT 1    /*3OCRAN       115.0 - 3LANCAST     115.0
 OPEN BRANCH FROM BUS 313813 TO BUS 314191 CKT 1    /*3OCRAN       115.0 - 3WHIT STONE  115.0
 OPEN BRANCH FROM BUS 313842 TO BUS 313870 CKT Z1   /*3RAPPAHNCK_1 115.0 - 3RAPPAHNCK   115.0
 OPEN BRANCH FROM BUS 313843 TO BUS 313870 CKT Z1   /*3RAPPAHNCK_2 115.0 - 3RAPPAHNCK   115.0
 OPEN BRANCH FROM BUS 313870 TO BUS 313900 CKT Z1   /*3RAPPAHNCK   115.0 - 3RAPP TR     115.0
 OPEN BRANCH FROM BUS 313870 TO BUS 314191 CKT 1    /*3RAPPAHNCK   115.0 - 3WHIT STONE  115.0
 OPEN BRANCH FROM BUS 313886 TO BUS 313900 CKT 1    /*3GREYSPT     115.0 - 3RAPP TR     115.0
 OPEN BRANCH FROM BUS 313886 TO BUS 313900 CKT 2    /*3GREYSPT     115.0 - 3RAPP TR     115.0
 OPEN BRANCH FROM BUS 313886 TO BUS 314174 CKT 1    /*3GREYSPT     115.0 - 3HARMONY     115.0
 OPEN BRANCH FROM BUS 314178 TO BUS 314400 CKT 1    /*3LANCAST     115.0 - 3LANCA_1     115.0
 OPEN BRANCH FROM BUS 314178 TO BUS 962970 CKT 1    /*3LANCAST     115.0 - AG1-146 TP   115.0
 OPEN BUS 313813                                    /*3OCRAN       115.0
 OPEN BUS 313842                                    /*3RAPPAHNCK_1 115.0
 OPEN BUS 313843                                    /*3RAPPAHNCK_2 115.0
 OPEN BUS 313870                                    /*3RAPPAHNCK   115.0
 OPEN BUS 313886                                    /*3GREYSPT     115.0
 OPEN BUS 313900                                    /*3RAPP TR     115.0
 OPEN BUS 314178                                    /*3LANCAST     115.0
 OPEN BUS 314191                                    /*3WHIT STONE  115.0
 OPEN BUS 314400                                    /*3LANCA_1     115.0
END
CONTINGENCY 'DVP_P4-4: LANCAS SC392_SRT-A'
 OPEN BRANCH FROM BUS 313813 TO BUS 314178 CKT 1   /*3OCRAN       115.0 - 3LANCAST     115.0
 OPEN BRANCH FROM BUS 313813 TO BUS 314191 CKT 1   /*3OCRAN       115.0 - 3WHIT STONE  115.0
 OPEN BRANCH FROM BUS 313870 TO BUS 314191 CKT 1   /*3RAPPAHNCK   115.0 - 3WHIT STONE  115.0
 OPEN BRANCH FROM BUS 314178 TO BUS 314400 CKT 1   /*3LANCAST     115.0 - 3LANCA_1     115.0
 OPEN BRANCH FROM BUS 314178 TO BUS 962970 CKT 1   /*3LANCAST     115.0 - AG1-146 TP   115.0
 OPEN BUS 313813                                   /*3OCRAN       115.0
 OPEN BUS 314178                                   /*3LANCAST     115.0
 OPEN BUS 314191                                   /*3WHIT STONE  115.0
 OPEN BUS 314400                                   /*3LANCA_1     115.0
END
CONTINGENCY 'DVP_P7-1: LN 2016-85_SRT-A-2'
 OPEN BRANCH FROM BUS 313053 TO BUS 314189 CKT 1   /*6PAPERMILL   230.0 - 6PAPERMIL TP 230.0
 OPEN BRANCH FROM BUS 314174 TO BUS 314176 CKT 1   /*3HARMONY     115.0 - 6HARMONY     230.0
 OPEN BRANCH FROM BUS 314176 TO BUS 314189 CKT 1   /*6HARMONY     230.0 - 6PAPERMIL TP 230.0
 OPEN BRANCH FROM BUS 314189 TO BUS 314375 CKT 1   /*6PAPERMIL TP 230.0 - 6CORRCTN     230.0
 OPEN BRANCH FROM BUS 314375 TO BUS 314388 CKT 1   /*6CORRCTN     230.0 - 6LANEXA      230.0
 OPEN BRANCH FROM BUS 316439 TO BUS 316275 CKT 1   /*AE2-005 TAP  115.0 - AD1-041 TAP  115.0
 OPEN BUS 313053                                   /*6PAPERMILL   230.0
 OPEN BUS 313846                                   /*6HARMONY_1   230.0
 OPEN BUS 314176                                   /*6HARMONY     230.0
 OPEN BUS 314189                                   /*6PAPERMIL TP 230.0
 OPEN BUS 314375                                   /*6CORRCTN     230.0
 OPEN BUS 315748                                   /*AE2-041 GSU   34.5
 OPEN BUS 315749                                   /*AE2-041 GEN    0.4
 OPEN BUS 315755                                   /*AF1-018 MAIN 230.0
 OPEN BUS 315756                                   /*AF1-018 COL   34.5
 OPEN BUS 315757                                   /*AF1-018 TER   13.8
 OPEN BUS 315758                                   /*AF1-018 GSU   34.5
 OPEN BUS 315759                                   /*AF1-018 GEN    0.4
 OPEN BUS 316059                                   /*AD1-063 C    230.0
 OPEN BUS 316314                                   /*AB2-024 C    230.0
END
CONTINGENCY 'DVP_P2-2: HARMONY V B2_SRT-A'
 OPEN BRANCH FROM BUS 313284 TO BUS 314174 CKT 1   /*3WAN 89      115.0 - 3HARMONY     115.0
 OPEN BRANCH FROM BUS 314174 TO BUS 314176 CKT 1   /*3HARMONY     115.0 - 6HARMONY     230.0
 OPEN BRANCH FROM BUS 314174 TO BUS 314187 CKT 1   /*3HARMONY     115.0 - 3WAN 176     115.0
 OPEN BUS 314385                                   /*3HARMO_1     115.0
 OPEN BUS 314395                                   /*3HARMO_2     115.0
END
CONTINGENCY 'DVP_P2-2: LANEXA B1_SRT-A'
 OPEN BRANCH FROM BUS 314188 TO BUS 314387 CKT 1   /*3WEST PT     115.0 - 3LANEXA      115.0
 OPEN BRANCH FROM BUS 314243 TO BUS 314387 CKT 1   /*3PROV 92     115.0 - 3LANEXA      115.0
 OPEN BRANCH FROM BUS 314387 TO BUS 314388 CKT 2   /*3LANEXA      115.0 - 6LANEXA      230.0
END
CONTINGENCY 'DVP_P1-2_AG1-135 TP-3GARNER-115_SRT-A'
 DISCONNECT BRANCH FROM BUS 962860 TO BUS 314173 CKT 1   /*AG1-135 TP   115.0 - 3GARNER      115.0
END
314173 to 316399 ckt 1
313886 to 314174 ckt 1
314174 to 314176 ckt 1
314178 to 313813 ckt 1
314181 to 314182 ckt 1
314181 to 314182 ckt 2
313813 to 314191 ckt 1
313900 to 313886 ckt 1
313900 to 313886 ckt 2
314191 to 313870 ckt 1
314132 to 314163 ckt 1
314163 to 314137 ckt 1
316479 to 962860 ckt 1
316399 to 314181 ckt 1
962860 to 314173 ckt 1
962970 to 314178 ckt 1

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-050Tarboro-Everetts 230kVIn Service
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-067Everetts 34.5kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-057Hornertown-Whitakers 115kVIn Service
AA2-174Carolina-Jackson 115kVIn Service
AA2-178Mackeys 230kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-132Thelma 230kVIn Service
AB2-022Elizabeth City 34.5kVIn Service
AB2-024Correctional 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-031Brink-Trego 115kVIn Service
AB2-040Brink 115kVIn Service
AB2-043Chase City 115kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-134Hopewell-Surry 230kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-169Pantago-Five Points 115kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVSuspended
AC1-036Twittys Creek 34.5kVIn Service
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-086Thelma 230kVSuspended
AC1-098Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-099Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-147Grassfield 34.5kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-191Elmont 115kVEngineering & Procurement
AC1-208Cox-Whitakers 115kVUnder Construction
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-079Ivor-Oak Ridge 115kVSuspended
AC2-100Halifax-Person 230kVIn Service
AC2-120Ripley 69kVIn Service
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVUnder Construction
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-063Harmony Village 34.5 kVIn Service
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-088Briery-Clover 230 kVSuspended
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-144Kings Fork 34.5 kVIn Service
AD1-151Hopewell-Surry 230 kVSuspended
AD1-152Clover-Sedge Hill 230 kVIn Service
AD2-030Wan 34.5 kVIn Service
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-058St. Barnabas 13 kVIn Service
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVEngineering & Procurement
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-160Hickory-Moyock 230kVIn Service
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-056Red House-South Creek 115 kVWithdrawn
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-103Holland-Union Camp 115 kVUnder Construction
AE1-148Kerr Dam-Ridge Rd 115 kVActive
AE1-149Disputanta-Poe 115 kVSuspended
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-162Smithfield 34.5 kVIn Service
AE1-173Carson-Suffolk 500 kVUnder Construction
AE1-175Light Foot 34.5 kVIn Service
AE1-190Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-191Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE2-005Harmony Village-Shackleford 115 kVUnder Construction
AE2-027Harrowgate-Locks 115kVUnder Construction
AE2-033Clubhouse-Sapony 230 kVSuspended
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-041Harmony Village 230 kVEngineering & Procurement
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-094Carson-Rogers Road 500 kVEngineering & Procurement
AE2-104Suffolk 115 kVSuspended
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-253Hickory-Moyock 230 kVIn Service
AE2-346Ahoskie 34.5 kVIn Service
AF1-014Harmony Village-Shackleford 115 kVUnder Construction
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-018Harmony Village 230 kVEngineering & Procurement
AF1-032Suffolk 34.5 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-058Welco 34.5 kVIn Service
AF1-069Carson-Rogers Rd 500 kVEngineering & Procurement
AF1-114Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF1-123Harper 230 kVActive
AF1-124Harper 230 kVActive
AF1-125Harper 230 kVActive
AF1-128Chesterfield 230 kVActive
AF1-129Chesterfield 230 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVUnder Construction
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-292Fields 34.5kVEngineering & Procurement
AF1-294Jetersville-Ponton 115 kVActive
AF2-013Arnold's Corner-Dahlgren 230 kVEngineering & Procurement
AF2-042Clover-Rawlings 500 kVActive
AF2-043Suffolk 34.5 kVIn Service
AF2-046Tunis-Mapleton 115 kVActive
AF2-054Wan 34.5 kVIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-080Chinquapin-Everetts 230 kVActive
AF2-081Moyock 230 kVActive
AF2-091Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF2-110Suffolk 115 kVSuspended
AF2-115Jetersville-Ponton 115 kVActive
AF2-120Garner-Northern Neck 115 kVActive
AF2-222Madisonville DP-Twitty's Creek 115 kVActive
AF2-297Sedge Hill 115 kVActive
AF2-299Fields 34.5 kVActive
AG1-007Tar River 12.5 kVEngineering & Procurement
AG1-008Tunis-Mapleton 115 kVActive
AG1-021Jetersville-Ponton 115 kVActive
AG1-037Ahoskie 34.5 kVEngineering & Procurement
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-082Ahoskie 34.5 kVActive
AG1-098Briery-Clover 230 kVActive
AG1-105Mount Laurel-Barnes Junction 115 kVActive
AG1-106Thelma 230 kVActive
AG1-135Garner-Lancaster 115 kVActive
AG1-145Lightfoot 34.5 kVIn Service
AG1-146Garner DP-Lancaster 115 kVActive
AG1-147Garner DP-Lancaster 115 kVActive
AG1-166Lone Pine 115 kVActive
AG1-167Lone Pine 115 kVActive
AG1-168Lone Pine 115 kVActive
AG1-210Northern Neck 34.5 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVEngineering & Procurement
AG1-285Chase City-Central 115 kVActive
AG1-342Dryburg 115 kVActive
AG1-393Sapony 34.5 kVActive
AG1-394Boykins 34.5 kVActive
AG1-532Fields 34.5 kVEngineering & Procurement
AG1-536Garner-Northern Neck 115 kVActive
AG1-551Parmele 34.5 kVActive
AG1-552Carolina 34.5 kVActive
AG1-558Buckner 34.5 kVEngineering & Procurement
AG2-005Garner DP-Lancaster 115 kVActive
AG2-010Peninsula-Whealton 115 kVActive
AG2-068Heritage - Wake 500 kVActive
AG2-069Heritage - Wake 500 kVActive
AG2-077Clover-Rawlings 500 kVActive
AG2-093Colonial Trail-Hopewell 230 kVActive
AG2-095Hopewell 34.5 kV (Circuit 313)Active
AG2-120Everetts 34.5 kVActive
AG2-124Shackleford-Harmony 115 kVActive
AG2-171Lunenburg-Nutbush 115 kVActive
AG2-193Turner 34.5 kVActive
AG2-198Briery - Finneywood 230 kVActive
AG2-213Gary D.P Tap - Gary D.P 115 kVActive
AG2-215Garner DP-Lancaster 115 kVActive
AG2-262Dryburg 115 kVActive
AG2-369Heritage - Wake 500 kVActive
AG2-382Cashie 230 kVActive
AG2-426Wakefield - Waverly 115 kVActive
AG2-427Waverly 115 kVActive
AG2-428Wakefield 115 kVActive
AG2-436Carson - Rogers Road 500 kVActive
AG2-440Twittys Creek - Madisonville 115 kVActive
AG2-441Twittys Creek - Madisonville 115 kVActive
AG2-442Twittys Creek - Madisonville 115 kVActive
AG2-469Westmoreland – Oak Grove 230 kVActive
AG2-522Five Forks DP 115 kVActive
AG2-566Briery - Finneywood 230 kVActive
AG2-570Heritage - Wake 500 kVActive
AG2-571Heritage - Wake 500 kVActive
AG2-581Rawlings-Clover 500 kVActive
AG2-646Chesterfield 230 kVActive
AG2-659Kerr Dam – Hawtree 115 kVActive
AG2-661Hopewell - Colonial Trail 230 kVActive
AH1-033Sligo 34.5 kVActive
AH1-035Plymouth 34.5 kVActive
AH1-040Mackeys - Creswell 115 kVActive
AH1-042Providence Forge-Turner 115kVActive
AH1-056Red House DP 115kVActive
AH1-065Hopewell 34.5kVActive
AH1-066Hopewell 34.5kVActive
AH1-071Midlothian 34.5 kVActive
AH1-106Winterpock 34.5kVActive
AH1-107Winterpock 34.5kVActive
AH1-108Spruance NUG 230 kVActive
AH1-138Penniman 34.5 kVActive
AH1-157Penniman - Waller 230 kVActive
AH1-215Central VA-Twitty 115 kVActive
AH1-216Smithfield-Surry 230 kVActive
AH1-271Cashie 230 kVActive
AH1-280Jetersville-Ponton 115 kVActive
AH1-311Heartsease DP - Mayo Dunbar 115kVActive
AH1-323Elmont 230 kVActive
AH1-324Colonial Trail – Surry 230 kVActive
AH1-343Crystal Hill DP- Perth 115kVActive
AH1-377Clover- Farmville 230kVActive
AH1-396Gary 24.94 kVActive
AH1-397Shacklesford 34.5 kVActive
AH1-399North Doswell 12.5 kVActive
AH1-408Freeman DP – Lawrenceville 115 kVActive
AH1-528Rawlings - Unity 500 kVActive
AH1-637Oak Grove 34.5 kVActive
AH1-677Rogers Road 500 kVActive
AH1-678Heritage 500 kVActive
AH1-679Four Rivers 230 kVActive
AH1-681Cunningham 500 kVActive
AH1-687Bear Garden 230kVActive
AH1-712Cunningham 500 kVActive
AH1-716Surry-Skiffes Creek 500kVActive
AH1-717Surry 230kVActive
AH1-723Cunningham 500 kVActive
V4-068Murphy's 34.5kVIn Service
Y1-086Morgans CornerIn Service
Z1-036WinFall-Chowan 230kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-044Whitakers 34.5kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase I analysis results, this project may have a cost responsibility for the following System Reinforcements:

AG2-366 System Reinforcements:
TORTEP IDTitleAllocated Cost ($USD)
Dominion(Pending) / TC2-PH1-DOM-2074Rebuild underground line from Harmony Village to Greyspoint and operating the line at 230 kV.$25,784,098
Dominionn9222.0 / TC1-PH2-DOM-036-TC2Wreck and Rebuild 6.95 miles of 115 kV Line 89 from White Marsh to Hayes with (1) 768 ACSS/TW (20/7) ""Maumee"" conductor @ 250 degrees C. Replace Line Lead at Hayes.$25,012,771
Dominionn9148.0 / TC1-PH1-DOM-013-TC2Wreck and rebuild 5.63 miles of 115 kV line between Wan and White Marsh with (1) 768.2 ACSS/TW (20/7) ""MAUMEE"" conductor @ 250 degrees C.$22,436,725
Dominion(Pending) / TC2-PH1-DOM-1042Add a 2nd new 224 MVA 115/230 kV Transformer at Harmony Village substation and add one (1) 115 kV breaker and one (1) 230 kV breaker$13,291,005
Dominion(Pending) / TC2-PH1-DOM-2049Wreck and rebuild 5.86 mi of 115 kV line 65 from Lancaster to AG1-146 with (2) 768.2 ACSS/TW (20/7) "Maumee" conductor @ 250 degrees C. and replace 636 ACSR and 1534 ACAR Jumper.$9,359,524
Dominion(Pending) / TC2-PH1-DOM-2048Wreck and rebuild 2.97 mi of 115 kV line 65 from Ocran to Lancaster with (2) 768.2 ACSS/TW (20/7) "Maumee" conductor @ 250 degrees C.$5,317,065
Dominionn7576 / dom-281-TC2Rebuild 7.91 miles of 230 kV Line 2083 from Birchwood to Fines with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"" conductor 250 degrees C.$3,020,931
Dominionn7575 / dom-286-TC2Rebuild 6.46 mi miles of 2-545.6 ACAR (15/7) 90 MOT 230 kV Line 2083 from Fredericksburg to Fines with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"" conductor @ 250 degrees C.$2,836,970
Dominionn9677.0 / dom-429Wreck and rebuild 0.95 miles of 115 kV Line 65 between Rappahannock and White Stone with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C$2,655,876
Dominion(Pending) / TC2-PH1-DOM-2045Wreck and rebuild 1.33 miles of 115 kV Line 65 between White Stone and Ocran with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C$2,381,066
Dominion(Pending) / TC2-PH1-DOM-2042Replace 2-795 AAC line lead on line 1059 at Northern Neck 115 kV$303,871
Dominion(Pending) / TC2-PH1-DOM-1007Wreck and rebuild 0.87 miles of 230 kV Line 2083 between Fredericksburg to Fines with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 Deg. C.$279,473
Dominion(Pending) / TC2-PH1-DOM-2047Wreck and rebuild 0.04 mi of 115 kV line 65 from Ocran to Lancaster with (2) 768.2 ACSS/TW (20/7) "Maumee" conductor @ 250 degrees C.$111,825
Dominion(Pending) / TC2-PH1-DOM-2044Wreck and rebuild 0.03 miles of 115 kV Line 65 between Rappahannock and White Stone with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C$83,870
Dominion(Pending) / TC2-PH1-DOM-2094Replace 115 kV 768.2 Jumper on line 65 between Ocran and Lancaster with (2) 768.2 ACSS/TW (20/7) "Maumee" conductor @ 250 degrees C.$3,798
Grand Total:$112,878,868

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2074
Title
Rebuild underground line from Harmony Village to Greyspoint and operating the line at 230 kV.
Description
Wreck and rebuild existing line 1021, Harmony Village to Greyspoint transition station, as a 230 kV line using (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Expand Harmony Village 230 kV to accommodate the new 230 kV line and associated breaker. Operate the existing underground portion of line 1021 as a 230 kV circuit. Build a new 230 kV station at Rappahannock and connect the existing underground cable, two new reactors and associated breakers and two new 224 MVA 115/230 kV transformers to tie into the existing 115 kV bus at Rappahannock. All 230 kV substation terminal equipment to be rated at 4000 Amps.
Total Cost ($USD)
$53,000,000
Allocated Cost ($USD)
$25,784,098
Time Estimate
48 to 60 Months

Contributor

FacilityContingency
3GREYSPT-3HARMONY 115.0 kV Ckt 1 line(Any)
3GREYSPT-3RAPP TR 115.0 kV Ckt 1 line(Any)
3GREYSPT-3RAPP TR 115.0 kV Ckt 2 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-005
31.6 MW15.4%$8,156,529
AG2-215
73.8 MW36.0%$19,059,373
AG2-366
99.8 MW48.6%$25,784,098

System Reinforcement: n9222.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9222.0 / TC1-PH2-DOM-036-TC2
Title
Wreck and Rebuild 6.95 miles of 115 kV Line 89 from White Marsh to Hayes with (1) 768 ACSS/TW (20/7) ""Maumee"" conductor @ 250 degrees C. Replace Line Lead at Hayes.
Description
Wreck and Rebuild 6.95 miles of 115 kV Line 89 from White Marsh to Hayes with (1) 768 ACSS/TW (20/7) ""Maumee"" conductor @ 250 degrees C. Replace Line Lead at Hayes.
Total Cost ($USD)
$42,356,870
Allocated Cost ($USD)
$25,012,771
Time Estimate
43 to 44 Months

Contributor

FacilityContingency
3WHITEMARSH-3HAYES89 115.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-005
5.1 MW40.9%$17,344,099
AG2-366
7.3 MW59.1%$25,012,771

System Reinforcement: n9148.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9148.0 / TC1-PH1-DOM-013-TC2
Title
Wreck and rebuild 5.63 miles of 115 kV line between Wan and White Marsh with (1) 768.2 ACSS/TW (20/7) ""MAUMEE"" conductor @ 250 degrees C.
Description
Wreck and rebuild 5.63 miles of 115 kV line between Wan and White Marsh with (1) 768.2 ACSS/TW (20/7) ""MAUMEE"" conductor @ 250 degrees C.
Total Cost ($USD)
$37,993,385
Allocated Cost ($USD)
$22,436,725
Time Estimate
43 to 44 Months

Contributor

FacilityContingency
3WAN 89-3WHITEMARSH 115.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-005
5.1 MW40.9%$15,556,660
AG2-366
7.3 MW59.1%$22,436,725

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-1042
Title
Add a 2nd new 224 MVA 115/230 kV Transformer at Harmony Village substation and add one (1) 115 kV breaker and one (1) 230 kV breaker
Description
Add a 2nd new 224 MVA 115/230 kV Transformer at Harmony Village substation and add one (1) 115 kV breaker and one (1) 230 kV breaker
Total Cost ($USD)
$17,500,000
Allocated Cost ($USD)
$13,291,005
Time Estimate
42 to 48 Months

Contributor

FacilityContingency
3HARMONY-6HARMONY 115.0/230.0 kV Ckt 1 transformer(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-005
7.6 MW24.1%$4,208,995
AG2-366
23.9 MW75.9%$13,291,005

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2049
Title
Wreck and rebuild 5.86 mi of 115 kV line 65 from Lancaster to AG1-146 with (2) 768.2 ACSS/TW (20/7) "Maumee" conductor @ 250 degrees C. and replace 636 ACSR and 1534 ACAR Jumper.
Description
Wreck and rebuild 5.86 mi of 115 kV line 65 from Lancaster to AG1-146 with (2) 768.2 ACSS/TW (20/7) "Maumee" conductor @ 250 degrees C. and replace 636 ACSR and 1534 ACAR Jumper.
Total Cost ($USD)
$21,569,800
Allocated Cost ($USD)
$9,359,524
Time Estimate
30 to 36 Months

Contributor

FacilityContingency
3LANCAST-AG1-146 TP 115.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-005
15.8 MW13.7%$2,960,851
AG2-215
36.9 MW32.1%$6,918,781
AG2-366
49.9 MW43.4%$9,359,524
AG2-469
12.4 MW10.8%$2,330,644

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2048
Title
Wreck and rebuild 2.97 mi of 115 kV line 65 from Ocran to Lancaster with (2) 768.2 ACSS/TW (20/7) "Maumee" conductor @ 250 degrees C.
Description
Wreck and rebuild 2.97 mi of 115 kV line 65 from Ocran to Lancaster with (2) 768.2 ACSS/TW (20/7) "Maumee" conductor @ 250 degrees C.
Total Cost ($USD)
$10,929,600
Allocated Cost ($USD)
$5,317,065
Time Estimate
30 to 36 Months

Contributor

FacilityContingency
3OCRAN-3LANCAST 115.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-005
15.8 MW15.4%$1,682,034
AG2-215
36.9 MW36.0%$3,930,500
AG2-366
49.9 MW48.6%$5,317,065

System Reinforcement: n7576
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7576 / dom-281-TC2
Title
Rebuild 7.91 miles of 230 kV Line 2083 from Birchwood to Fines with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"" conductor 250 degrees C.
Description
Rebuild 7.91 miles of 230 kV Line 2083 from Birchwood to Fines with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"" conductor 250 degrees C.
Total Cost ($USD)
$35,735,843
Allocated Cost ($USD)
$3,020,931
Time Estimate
43 to 44 Months

Contributor

FacilityContingency
6BIRCHWD-6FINES 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-005
1.6 MW1.5%$540,761
AG2-215
7.2 MW6.7%$2,376,443
AG2-366
9.1 MW8.5%$3,020,931
AG2-469
26.8 MW24.8%$8,868,884
AG2-646
11.2 MW10.4%$3,706,710
AH1-042
11.7 MW10.8%$3,876,834
AH1-157
7.5 MW7.0%$2,486,776
AH1-716
32.9 MW30.4%$10,858,503

System Reinforcement: n7575
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7575 / dom-286-TC2
Title
Rebuild 6.46 mi miles of 2-545.6 ACAR (15/7) 90 MOT 230 kV Line 2083 from Fredericksburg to Fines with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"" conductor @ 250 degrees C.
Description
Rebuild 6.46 mi miles of 2-545.6 ACAR (15/7) 90 MOT 230 kV Line 2083 from Fredericksburg to Fines with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"" conductor @ 250 degrees C.
Total Cost ($USD)
$33,559,690
Allocated Cost ($USD)
$2,836,970
Time Estimate
43 to 44 Months

Contributor

FacilityContingency
6FREDBRG-6FINES 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-005
1.6 MW1.5%$507,832
AG2-215
7.2 MW6.7%$2,231,729
AG2-366
9.1 MW8.5%$2,836,970
AG2-469
26.8 MW24.8%$8,328,809
AG2-646
11.2 MW10.4%$3,480,988
AH1-042
11.7 MW10.8%$3,640,752
AH1-157
7.5 MW7.0%$2,335,342
AH1-716
32.9 MW30.4%$10,197,269

System Reinforcement: n9677.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9677.0 / dom-429
Title
Wreck and rebuild 0.95 miles of 115 kV Line 65 between Rappahannock and White Stone with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C
Description
Wreck and rebuild 0.95 miles of 115 kV Line 65 between Rappahannock and White Stone with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C
Total Cost ($USD)
$3,496,000
Allocated Cost ($USD)
$2,655,876
Time Estimate
30 to 36 Months

Contributor

FacilityContingency
3RAPPAHNCK-3WHIT STONE 115.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-005
15.8 MW24.0%$840,124
AG2-366
49.9 MW76.0%$2,655,876

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2045
Title
Wreck and rebuild 1.33 miles of 115 kV Line 65 between White Stone and Ocran with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C
Description
Wreck and rebuild 1.33 miles of 115 kV Line 65 between White Stone and Ocran with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C
Total Cost ($USD)
$4,894,400
Allocated Cost ($USD)
$2,381,066
Time Estimate
30 to 36 Months

Contributor

FacilityContingency
3OCRAN-3WHIT STONE 115.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-005
15.8 MW15.4%$753,242
AG2-215
36.9 MW36.0%$1,760,093
AG2-366
49.9 MW48.6%$2,381,066

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2042
Title
Replace 2-795 AAC line lead on line 1059 at Northern Neck 115 kV
Description
Replace 2-795 AAC line lead on line 1059 at Northern Neck 115 kV
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$303,871
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
3NORNECK-AE1-155 TAP 115.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-005
15.8 MW24.0%$96,129
AG2-366
49.9 MW76.0%$303,871

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-1007
Title
Wreck and rebuild 0.87 miles of 230 kV Line 2083 between Fredericksburg to Fines with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 Deg. C.
Description
Wreck and rebuild 0.87 miles of 230 kV Line 2083 between Fredericksburg to Fines with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 Deg. C.
Total Cost ($USD)
$3,306,000
Allocated Cost ($USD)
$279,473
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6FREDBRG-6FINES 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-005
1.6 MW1.5%$50,027
AG2-215
7.2 MW6.7%$219,850
AG2-366
9.1 MW8.5%$279,473
AG2-469
26.8 MW24.8%$820,480
AG2-646
11.2 MW10.4%$342,916
AH1-042
11.7 MW10.8%$358,654
AH1-157
7.5 MW7.0%$230,057
AH1-716
32.9 MW30.4%$1,004,544

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2047
Title
Wreck and rebuild 0.04 mi of 115 kV line 65 from Ocran to Lancaster with (2) 768.2 ACSS/TW (20/7) "Maumee" conductor @ 250 degrees C.
Description
Wreck and rebuild 0.04 mi of 115 kV line 65 from Ocran to Lancaster with (2) 768.2 ACSS/TW (20/7) "Maumee" conductor @ 250 degrees C.
Total Cost ($USD)
$147,200
Allocated Cost ($USD)
$111,825
Time Estimate
30 to 36 Months

Contributor

FacilityContingency
3OCRAN-3LANCAST 115.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-005
15.8 MW24.0%$35,375
AG2-366
49.9 MW76.0%$111,825

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2044
Title
Wreck and rebuild 0.03 miles of 115 kV Line 65 between Rappahannock and White Stone with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C
Description
Wreck and rebuild 0.03 miles of 115 kV Line 65 between Rappahannock and White Stone with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C
Total Cost ($USD)
$110,400
Allocated Cost ($USD)
$83,870
Time Estimate
30 to 36 Months

Contributor

FacilityContingency
3RAPPAHNCK-3WHIT STONE 115.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-005
15.8 MW24.0%$26,530
AG2-366
49.9 MW76.0%$83,870

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2094
Title
Replace 115 kV 768.2 Jumper on line 65 between Ocran and Lancaster with (2) 768.2 ACSS/TW (20/7) "Maumee" conductor @ 250 degrees C.
Description
Replace 115 kV 768.2 Jumper on line 65 between Ocran and Lancaster with (2) 768.2 ACSS/TW (20/7) "Maumee" conductor @ 250 degrees C.
Total Cost ($USD)
$5,000
Allocated Cost ($USD)
$3,798
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
3OCRAN-3LANCAST 115.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-005
15.8 MW24.0%$1,202
AG2-366
49.9 MW76.0%$3,798

System Reinforcement: n9145.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9145.0 / TC1-PH1-DOM-008
Title
Reconductor 0.11 miles of 115 kV line between Garner DP and Moon Corner with single (1) 768.2 aluminum conductor steel supported trapezoidal shaped aluminum strands ("ACSS/TW") (20/7).
Description
Reconductor 0.11 miles of 115 kV line 65 between Garner DP and Moon Corner with single (1) 768.2 aluminum conductor steel supported trapezoidal shaped aluminum strands (ACSS/TW) (20/7) "Maumee" conductor @ 250 degrees C.
Total Cost ($USD)
$2,096,619
Allocated Cost ($USD)
$0
Time Estimate
18 to 19 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-366 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-366 could receive cost allocation. Although AG2-366 may not presently have cost responsibility for this upgrade, AG2-366 may need this upgrade in-service to be deliverable to the PJM system. If AG2-366 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
3GARNER-AE1-155 TAP 115.0 kV Ckt 1 line(Any)

System Reinforcement: n9136.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9136.0 / TC1-PH1-DOM-066
Title
Wreck and rebuild 1.32 miles of 115 kV line from Garner to AG1-135 with 768.2 aluminum conductor steel supported trapezoidal shaped aluminum strands ("ACSS/TW") (20/7). Replace line lead at Garner DP.
Description
Wreck and rebuild 1.32 miles of 115 kV line 65 between Garner and AG1-135 with one (1) 768.2 aluminum conductor steel supported trapezoidal shaped aluminum strands (ACSS/TW) (20/7) "MAUMEE" conductor @ 250 degrees C. Replace line lead at Garner DP substation.
Total Cost ($USD)
$8,145,385
Allocated Cost ($USD)
$0
Time Estimate
42 to 43 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-366 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-366 could receive cost allocation. Although AG2-366 may not presently have cost responsibility for this upgrade, AG2-366 may need this upgrade in-service to be deliverable to the PJM system. If AG2-366 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
3GARNER-AG1-135 TP 115.0 kV Ckt 1 line(Any)

System Reinforcement: n7549
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7549 / dom-428
Title
Replace Northern Neck 115/230 kV transformer #4 with a 224 MVA (260/271/295 MVA).
Description
Replace Northern Neck 115/230 kV transformer #4 with a 224 MVA (260/271/295 MVA).
Total Cost ($USD)
$7,324,554
Allocated Cost ($USD)
$0
Time Estimate
59 to 60 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-366 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-366 could receive cost allocation. Although AG2-366 may not presently have cost responsibility for this upgrade, AG2-366 may need this upgrade in-service to be deliverable to the PJM system. If AG2-366 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 1 transformer(Any)

System Reinforcement: n7553
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7553 / dom-427
Title
Replace Northern Neck 115/230 kV transformer #6 with a 224 MVA (260/271/295 MVA).
Description
Replace Northern Neck 115/230 kV transformer #6 with a 224 MVA (260/271/295 MVA).
Total Cost ($USD)
$7,242,347
Allocated Cost ($USD)
$0
Time Estimate
59 to 60 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-366 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-366 could receive cost allocation. Although AG2-366 may not presently have cost responsibility for this upgrade, AG2-366 may need this upgrade in-service to be deliverable to the PJM system. If AG2-366 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
3NORNECK-6NORNECK 115.0/230.0 kV Ckt 2 transformer(Any)

System Reinforcement: n9651.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9651.0 / TC1-PH2-DOM-009
Title
Wreck and rebuild 10.05 miles of 115 kV Line 1059 between Northern Neck and Moon Corner with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 Deg. C.
Description
Wreck and rebuild 10.05 miles of 115 kV Line 1059 between Northern Neck and Moon Corner with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 Deg. C.
Total Cost ($USD)
$28,476,954
Allocated Cost ($USD)
$0
Time Estimate
Mar 31 2029

Contingent

Note: Based on PJM cost allocation criteria, AG2-366 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-366 could receive cost allocation. Although AG2-366 may not presently have cost responsibility for this upgrade, AG2-366 may need this upgrade in-service to be deliverable to the PJM system. If AG2-366 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
3NORNECK-AE1-155 TAP 115.0 kV Ckt 1 line(Any)

System Reinforcement: n9652.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9652.0 / TC1-PH2-DOM-010
Title
Replace Wave Trap at Northern Neck for increased rating of Line 1059 between Northern Neck and Moon Corner
Description
Replace Wave Trap at Northern Neck for increased rating of Line 1059 between Northern Neck and Moon Corner
Total Cost ($USD)
$1,065,776
Allocated Cost ($USD)
$0
Time Estimate
Mar 01 2027

Contingent

Note: Based on PJM cost allocation criteria, AG2-366 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-366 could receive cost allocation. Although AG2-366 may not presently have cost responsibility for this upgrade, AG2-366 may need this upgrade in-service to be deliverable to the PJM system. If AG2-366 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
3NORNECK-AE1-155 TAP 115.0 kV Ckt 1 line(Any)

System Reinforcement: n9653.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9653.0 / TC1-PH2-DOM-011
Title
Replace Line Switch at Northern Neck for increased rating of Line 1059 between Northern Neck and Moon Corner
Description
Replace Line Switch at Northern Neck for increased rating of Line 1059 between Northern Neck and Moon Corner
Total Cost ($USD)
$454,326
Allocated Cost ($USD)
$0
Time Estimate
Mar 01 2027

Contingent

Note: Based on PJM cost allocation criteria, AG2-366 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-366 could receive cost allocation. Although AG2-366 may not presently have cost responsibility for this upgrade, AG2-366 may need this upgrade in-service to be deliverable to the PJM system. If AG2-366 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
3NORNECK-AE1-155 TAP 115.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0043
Title
Wreck and rebuild 3.62 miles of 230 kV Line 2091 between Chickahominy and Elko with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 3.62 miles of 230 kV Line 2091 between Chickahominy and Elko with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$13,756,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-366 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-366 could receive cost allocation. Although AG2-366 may not presently have cost responsibility for this upgrade, AG2-366 is a potential Aggregate Pool Contributor.

FacilityContingency
6CHCKAHM-6ELKO 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9261.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9261.0 / TC1-PH2-DOM-060
Title
Replace Existing Chickahominy XFRM 1 with 3-480 MVA Single Phase XFRM.
Description
Replace Existing Chickahominy XFRM 1 with 3-480 MVA Single Phase XFRM.
Total Cost ($USD)
$40,000,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-366 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-366 could receive cost allocation. Although AG2-366 may not presently have cost responsibility for this upgrade, AG2-366 is a potential Aggregate Pool Contributor.

FacilityContingency
6CHCKAHM-8CHCKAHM 230.0/500.0 kV Ckt 1 transformer(Any)

System Reinforcement: b3692
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3692
Title
Rebuild approximately 27.7-miles of 500 kV transmission line from Elmont to Chickahominy.
Description
Rebuild approximately 27.7-miles of 500 kV transmission line from Elmont to Chickahominy with current 500 kV standards construction practices to achieve a summer rating of 4330 MVA. Projected ISD: 06/01/2026
Cost Information
Time Estimate
Jun 01 2026

Not Contingent

Note: AG2-366 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-366 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AG2-366 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-366 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.355
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-366 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-366 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-366 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-366 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-366 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-366 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-366 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-366 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-366 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-366 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-366 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-366 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AG2-366 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-366 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AG2-366 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-366 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-366 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-366 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AG2-366 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-366 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-366 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-366 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-366 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-366 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-366 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-366 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-366 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-366 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AG2-366 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-366 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6SANDERS-6WESTMOR 230.0 kV Ckt 1 line(Any)
6BIRCHWD-6COMORN 230.0 kV Ckt 1 line(Any)
6ARNOLDS-6COMORN 230.0 kV Ckt 1 line(Any)
6NORNECK-6SANDERS 230.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6ARNOLDS-AF2-013 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6DAHLGREN-AF1-114 TP 230.0 kV Ckt 1 line(Any)
6OAKGROV-AG2-469 TP 230.0 kV Ckt 1 line(Any)
6WESTMOR-AG2-469 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: n7698
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7698 / dom-394
Title
Rebuild 4.29 miles of 115 kV line 65 from AD2-074 Tap to AG1-135 Tap with single (1) 768.2 ACSS/TW (20/7) "Maumee" conductor.
Description
Rebuild 4.29 miles of 115 kV line 65 from AD2-074 Tap to AG1-135 Tap with single (1) 768.2 ACSS/TW (20/7) "Maumee" conductor at 250 degrees C.
Total Cost ($USD)
$20,146,983
Allocated Cost ($USD)
$0
Time Estimate
43 to 44 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-366 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-366 could receive cost allocation. Although AG2-366 may not presently have cost responsibility for this upgrade, AG2-366 may need this upgrade in-service to be deliverable to the PJM system. If AG2-366 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
AD2-074 TAP-AG1-135 TP 115.0 kV Ckt 1 line(Any)
          AD2-074 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-005, AG2-215
        

Attachments

AG2-366 One Line Diagram

AG2-366 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.